Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:59
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 08:59:24
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 13484.03 | 1188.51 | 1188.51 |
Net Site Energy | 13484.03 | 1188.51 | 1188.51 |
Total Source Energy | 25105.67 | 2212.87 | 2212.87 |
Net Source Energy | 25105.67 | 2212.87 | 2212.87 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3177.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 593.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 766.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 242.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1745.01 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 651.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 556.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 100.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 228.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.75 | 3482.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5035.52 | 8448.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3177.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 593.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 766.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 242.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 32.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 556.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 100.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 228.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 3482.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 3177.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 593.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 766.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 242.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1745.01 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 651.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 556.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 100.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 228.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.75 | 3482.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 88.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 118.20 | 587.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 236.76 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 443.84 | 744.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 88.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 118.20 | 587.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 236.76 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 443.84 | 744.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5035.516 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5035.516 | 100.00 |
Total On-Site and Utility Electric Sources | 5035.516 | 100.00 |
Total Electricity End Uses | 5035.516 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 127.60 | 2.41 |
Air to Air Heat Recovery for Heating | 5168.83 | 97.59 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 5296.43 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 34.67 |
Time Setpoint Not Met During Occupied Cooling | 283.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8039.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:59 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 9.1389 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.3365 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.3365 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 9.2031 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 6.1031 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.8125 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.3656 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 8.7188 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.5531 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.5531 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 6.3938 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.5531 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.3656 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.3656 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7219 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 6.3938 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 6.8557 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 6.8557 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.1389 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.3365 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.3365 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 9.2031 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 6.1031 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.8125 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.3656 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 8.7188 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.5531 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.5531 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 6.3938 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.5531 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.5531 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.5531 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.3656 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.3656 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7219 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 6.3938 | 18.58 | 0.0000 | |
Total | 11345.29 | 6.8557 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 6.8557 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.4542 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-JUN-18:10 | 04-JAN-17:00 | - | - | - | - | - | - | - | - | - | - | 27-JAN-21:00 |
Heating | 0.00 | 968761.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 203641.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 53571.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 79417.81 | 89612.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31835.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 30793.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6905.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4738.71 | 265979.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2416.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 423260.36 | 1324353.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 968761.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 203641.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 53571.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 49434.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 14636.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1532.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 30793.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 6905.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4738.71 | 265979.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 228.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1093.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1093.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3444.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1878.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2426.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 767.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5526.46 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2063.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1762.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 318.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 722.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.41 | 3774.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 194.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 15947.48 | 9158.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 303.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 165.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 213.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 67.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.11 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 155.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 28.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 63.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 332.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1405.65 | 807.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 303.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 165.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 213.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 67.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.11 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 155.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 28.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 63.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 332.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1405.65 | 807.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.57 | 0.587035 | 0.500000 | 1.28 | 1.00 | 0.500000 | 0.000649 | 0.000074 | 1.28 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.462876 | 0.110415 | 0.500000 | 0.231438 | 0.500000 | 0.500000 | 0.003451 | 0.000047 | 0.231438 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.246656 | 0.239944 | 0.500000 | 0.123328 | 0.639851 | 0.500000 | 0.001588 | 0.000018 | 0.123328 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.228979 | 0.546572 | 0.500000 | 0.114489 | 1.00 | 0.500000 | 0.000697 | 0.000029 | 0.121889 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.110607 | 0.652823 | 0.500000 | 0.055303 | 1.00 | 0.500000 | 0.000584 | 0.000018 | 0.076190 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.40 | 0.069459 | 0.500000 | 1.70 | 0.500000 | 0.500000 | 0.021767 | 0.000107 | 1.70 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.81 | 0.079331 | 0.500000 | 0.907035 | 0.500000 | 0.500000 | 0.004803 | 0.000131 | 0.907035 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.13 | 0.194135 | 0.500000 | 2.57 | 0.517694 | 0.500000 | 0.001963 | 0.000332 | 2.57 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.62 | 0.734668 | 0.500000 | 0.807783 | 1.00 | 0.500000 | 0.000519 | 0.000163 | 0.807783 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.22 | 0.113606 | 0.500000 | 1.11 | 0.500000 | 0.500000 | 0.003354 | 0.000131 | 1.11 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.33 | 0.108353 | 0.500000 | 1.17 | 0.500000 | 0.500000 | 0.003516 | 0.000135 | 1.17 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.39 | 0.059208 | 0.500000 | 1.20 | 0.500000 | 0.500000 | 0.011574 | 0.000091 | 1.20 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.813571 | 0.386001 | 0.500000 | 0.406786 | 1.00 | 0.500000 | 0.000987 | 0.000104 | 0.433667 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 8458.89 | 0.000074 | 179.20 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5353.77 | 0.000047 | 137.73 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2044.38 | 0.000018 | 48.42 |
MECH_FLR_1 VAV BOX REHEAT COIL | 3341.04 | 0.000029 | 91.18 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 2088.43 | 0.000018 | 56.99 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 12184.31 | 0.000107 | 259.72 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 14983.31 | 0.000131 | 354.66 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 37961.34 | 0.000332 | 880.31 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 9503.10 | 0.000083 | 271.56 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 9510.66 | 0.000083 | 271.78 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 53725.38 | 0.000470 | 1535.26 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 53884.85 | 0.000471 | 1539.82 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 9519.24 | 0.000083 | 272.02 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 9526.80 | 0.000083 | 272.24 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 18626.81 | 0.000163 | 478.72 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2900.06 | 0.000025 | 82.87 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2900.27 | 0.000025 | 82.87 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 13843.39 | 0.000121 | 395.57 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 14986.45 | 0.000131 | 342.29 |
DINING_FLR_6 VAV BOX REHEAT COIL | 15441.61 | 0.000135 | 351.75 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 10411.67 | 0.000091 | 225.58 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11888.55 | 0.000104 | 324.46 |
VAV WITH REHEAT HEATING COIL | 398780.76 | 0.003489 | 5550.13 |
FLR_3_DOAS HEATING COIL | 35250.36 | 0.000308 | 490.61 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.28 | 0.000083 | 0.000498 |
ROOM_2_FLR_3 FAN COIL | 1.22 | 0.000083 | 0.000474 |
ROOM_3_MULT19_FLR_3 FAN COIL | 7.74 | 0.000470 | 0.002950 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.61 | 0.000471 | 0.002302 |
ROOM_5_FLR_3 FAN COIL | 1.16 | 0.000083 | 0.000453 |
ROOM_6_FLR_3 FAN COIL | 1.10 | 0.000083 | 0.000430 |
ROOM_1_FLR_6 FAN COIL | 0.334027 | 0.000025 | 0.000130 |
ROOM_2_FLR_6 FAN COIL | 0.315682 | 0.000025 | 0.000123 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.62 | 0.000121 | 0.000635 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.28 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.22 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.74 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.61 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.16 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.10 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.334027 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.315682 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.62 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008629 | 12.80 | 0.008500 | 0.000498 | 1.28 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008636 | 12.80 | 0.008500 | 0.000474 | 1.22 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008562 | 12.80 | 0.008500 | 0.002950 | 7.74 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008842 | 12.80 | 0.008500 | 0.002302 | 5.61 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008643 | 12.80 | 0.008500 | 0.000453 | 1.16 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008651 | 12.80 | 0.008500 | 0.000430 | 1.10 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008624 | 12.80 | 0.008500 | 0.000130 | 0.334027 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008631 | 12.80 | 0.008500 | 0.000123 | 0.315682 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.71 | 6.70 | 0.008670 | 12.80 | 0.008500 | 0.000635 | 1.62 | |
VAV WITH REHEAT COOLING COIL | 27.06 | 6.70 | 0.011196 | 10.91 | 0.008500 | 0.022346 | 23.21 | 625639.93 |
FLR_3_DOAS COOLING COIL | 30.10 | 6.70 | 0.012726 | 11.90 | 0.008500 | 0.002484 | 2.05 | 69550.09 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.67 | 11.67 | 23.34 | 11.67 | 23.21 | 23.21 | 0.300000 | 0.502910 | 23.21 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 23.21 | 11.66 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 23.21 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.022346 | 0.000021 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.003489 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002484 | 0.000192 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000308 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.032824 | 6763.86 | |
HEATSYS1 PUMP | 0.006624 | 1994.73 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.006624 | 0.794829 |
COOLSYS1 | 0.032824 | 3.94 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 757115.44 | 757115.44 | 0.006624 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.032824 | 4682.85 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.032824 | 918991.59 | 919625.34 | 104.84 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 9.139 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.519 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.336 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.096 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.336 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.096 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 9.203 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.583 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 6.103 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.793 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.813 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.343 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.366 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.746 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 8.719 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.789 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.366 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 78.186 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.366 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 78.186 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.722 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2946.209 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 18084.325 | 9.139 | 169.807 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18084.325 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 894.495 | 13.336 | 82.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 894.495 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1035.829 | 13.336 | 82.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1035.829 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 1511.551 | 9.203 | 569.967 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1511.551 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 578.329 | 6.103 | 283.494 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 578.329 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 453.605 | 5.813 | 54.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 453.605 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1957.673 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1957.673 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11405.759 | 8.719 | 27.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11405.759 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 111.660 | 4.553 | 74.440 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.660 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 111.691 | 4.553 | 74.460 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.691 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2489.757 | 6.394 | 118.803 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.757 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 111.691 | 4.553 | 74.460 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.691 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3437.839 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3437.839 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3437.839 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3437.839 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1210.923 | 11.722 | 54.453 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1210.923 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2635.024 | 6.394 | 118.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2635.024 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.6889 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 0.9632 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.8896 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.9532 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.284 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8708 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8054 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9567 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8818 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
21 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
22 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
23 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
24 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
25 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
26 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
27 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
28 | 9 | -0.19825490E-14 | 0.26506188E-16 | -0.16094312E-09 | 0.40328149E-16 |
29 | 8 | 0.23449069E-07 | 0.93789827E-13 | 0.39413852E-03 | -0.26662398E-09 |
30 | 7 | -0.12728657E-01 | 0.47902107E-08 | -0.23786953E-01 | 0.14472948E-03 |
31 | 6 | 0.41858495 | 0.16581677E-05 | 0.48334662 | -0.49037666E-02 |
32 | 5 | -5.3197065 | 0.61648545E-04 | -4.5276394 | 0.64785173E-01 |
33 | 4 | 33.574021 | 0.50235132E-03 | 21.777816 | -0.42970649 |
34 | 3 | -112.44126 | 0.10910570E-02 | -56.291144 | 1.5327492 |
35 | 2 | 198.33524 | 0.61183027E-03 | 78.486958 | -2.9198383 |
36 | 1 | -171.60922 | 0.65128965E-04 | -55.433196 | 2.7533813 |
37 | 0 | 57.057407 | 0.36957019E-06 | 15.529586 | |
38 | 9 | -0.85509233E-15 | 0.35217200E-16 | -0.14813881E-09 | 0.22506418E-17 |
39 | 8 | 0.21652630E-07 | 0.12951040E-12 | 0.37545894E-03 | -0.24619788E-09 |
40 | 7 | -0.12171920E-01 | 0.67399561E-08 | -0.22985554E-01 | 0.13839917E-03 |
41 | 6 | 0.40345826 | 0.23507276E-05 | 0.47047975 | -0.47254590E-02 |
42 | 5 | -5.1720992 | 0.87965781E-04 | -4.4288869 | 0.62954898E-01 |
43 | 4 | 32.921184 | 0.72101989E-03 | 21.391978 | -0.42103852 |
44 | 3 | -111.05248 | 0.15742106E-02 | -55.528415 | 1.5126844 |
45 | 2 | 196.95904 | 0.88690553E-03 | 77.787143 | -2.8979836 |
46 | 1 | -171.10097 | 0.94819913E-04 | -55.229177 | 2.7444736 |
47 | 0 | 57.057407 | 0.54066260E-06 | 15.562856 | |
48 | 9 | -0.15009784E-15 | 0.35929976E-16 | -0.14508672E-09 | -0.10757262E-17 |
49 | 8 | 0.21223339E-07 | 0.13773381E-12 | 0.37091876E-03 | -0.24131668E-09 |
50 | 7 | -0.12036342E-01 | 0.72021282E-08 | -0.22790313E-01 | 0.13685759E-03 |
51 | 6 | 0.39977421 | 0.25166957E-05 | 0.46733969 | -0.46820329E-02 |
52 | 5 | -5.1361454 | 0.94330313E-04 | -4.4047585 | 0.62509089E-01 |
53 | 4 | 32.762141 | 0.77432644E-03 | 21.297641 | -0.41892687 |
54 | 3 | -110.71406 | 0.16928112E-02 | -55.341898 | 1.5077952 |
55 | 2 | 196.62360 | 0.95483717E-03 | 77.616126 | -2.8926568 |
56 | 1 | -170.97705 | 0.10219256E-03 | -55.179534 | 2.7423018 |
57 | 0 | 57.057407 | 0.58340349E-06 | 15.571125 | |
58 | 9 | -0.23907624E-14 | 0.31597480E-16 | -0.15159381E-09 | 0.44487065E-16 |
59 | 8 | 0.22138174E-07 | 0.12005614E-12 | 0.38055753E-03 | -0.25171865E-09 |
60 | 7 | -0.12324050E-01 | 0.62153905E-08 | -0.23204591E-01 | 0.14012894E-03 |
61 | 6 | 0.40759191 | 0.21632260E-05 | 0.47399999 | -0.47741848E-02 |
62 | 5 | -5.2124386 | 0.80803221E-04 | -4.4559231 | 0.63455088E-01 |
63 | 4 | 33.099615 | 0.66123170E-03 | 21.497653 | -0.42340758 |
64 | 3 | -111.43211 | 0.14415773E-02 | -55.737335 | 1.5181690 |
65 | 2 | 197.33529 | 0.81112906E-03 | 77.978757 | -2.9039585 |
66 | 1 | -171.23995 | 0.86614752E-04 | -55.284900 | 2.7469094 |
67 | 0 | 57.057407 | 0.49323094E-06 | 15.553656 | |
68 | 9 | 0.63796015E-17 | 0.35026513E-16 | -0.14861226E-09 | 0.64921151E-18 |
69 | 8 | 0.21719229E-07 | 0.12822517E-12 | 0.37616054E-03 | -0.24695511E-09 |
70 | 7 | -0.12192862E-01 | 0.66681186E-08 | -0.23015708E-01 | 0.13863728E-03 |
71 | 6 | 0.40402730 | 0.23249961E-05 | 0.47096453 | -0.47321665E-02 |
72 | 5 | -5.1776524 | 0.86981116E-04 | -4.4326110 | 0.63023755E-01 |
73 | 4 | 32.945748 | 0.71278800E-03 | 21.406536 | -0.42136466 |
74 | 3 | -111.10474 | 0.15559249E-02 | -55.557197 | 1.5134395 |
75 | 2 | 197.01084 | 0.87644643E-03 | 77.813538 | -2.8988062 |
76 | 1 | -171.12011 | 0.93686201E-04 | -55.236846 | 2.7448090 |
77 | 0 | 57.057407 | 0.53410260E-06 | 15.561584 | |
78 | 7 | -0.16359629E-14 | -0.14530353E-16 | -0.22331004E-13 | 0.54056000E-15 |
79 | 6 | 0.18262352E-10 | 0.22801053E-11 | 0.52333849E-09 | -0.18642118E-10 |
80 | 5 | -0.59540244E-07 | 0.11129510E-07 | -0.21928235E-05 | 0.17164558E-06 |
81 | 4 | 0.60861605E-04 | 0.41961443E-05 | 0.17683552E-02 | -0.28248824E-03 |
82 | 3 | -0.87523238E-02 | 0.14809838E-03 | -0.21562890 | 0.43346081E-01 |
83 | 2 | 0.12409989 | 0.64146884E-03 | 2.9009744 | -0.61915653 |
84 | 1 | -0.31397648 | 0.40472017E-03 | -7.1381115 | 1.5697592 |
85 | 0 | 0.19977219 | 0.56546383E-05 | 4.4522022 | |
86 | 7 | -0.22331004E-13 | -0.14530353E-16 | -0.16359629E-14 | 0.54056000E-15 |
87 | 6 | 0.52333849E-09 | 0.22801053E-11 | 0.18262352E-10 | -0.18642118E-10 |
88 | 5 | -0.21928235E-05 | 0.11129510E-07 | -0.59540244E-07 | 0.17164558E-06 |
89 | 4 | 0.17683552E-02 | 0.41961443E-05 | 0.60861605E-04 | -0.28248824E-03 |
90 | 3 | -0.21562890 | 0.14809838E-03 | -0.87523238E-02 | 0.43346081E-01 |
91 | 2 | 2.9009744 | 0.64146884E-03 | 0.12409989 | -0.61915653 |
92 | 1 | -7.1381115 | 0.40472017E-03 | -0.31397648 | 1.5697592 |
93 | 0 | 4.4522022 | 0.56546383E-05 | 0.19977219 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
103 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
104 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
105 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
106 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
107 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
108 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
109 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
110 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
111 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
112 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
113 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
114 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
115 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
116 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
117 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
118 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
119 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
120 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
121 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
122 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
123 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
124 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
125 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
126 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
127 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
128 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
129 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
130 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
131 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
132 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
133 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.2964_SHGC_0.45 | 37 | 1 | VerySmooth | 1.683 | 1.683 | 1.000 | 0.451 | ||
2 | RESWINDOW_U_0.2964_SHGC_0.45 | 38 | 1 | VerySmooth | 1.683 | 1.683 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 4.21322E-002 | 0.36619 | 0.44048 | 0.44048 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.10036 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 4.21322E-002 | 0.36619 | 0.44048 | 0.44048 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.10036 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1730 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.9648E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1977 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 0.1162 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1147 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.6613E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.7474E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.5758E-002 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1970 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1190 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.2259 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1382 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1269 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.8077E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 5.3310E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.1554E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.3656E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.5201E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.3645E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.9093E-002 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.1982E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.2746E-002 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.6736E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.6558E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.3656E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.5201E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.3645E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.9093E-002 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.1982E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.2746E-002 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.6736E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.6558E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 33877.36167 | 33877.36167 | 2.56862 | 2.56862 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 25.03667 | 1.27170E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1960.76428 | 1960.76428 | 8.77035E-002 | 0.85446 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 6104.07859 | 6104.07859 | 0.46288 | 0.46288 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27253E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 4184.32868 | 4184.32868 | 0.18714 | 0.18714 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3252.72157 | 3252.72157 | 0.24666 | 0.24666 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 29.97600 | 1.27256E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1421.09874 | 1421.09874 | 6.35620E-002 | 9.17347E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3020.25097 | 3020.25097 | 0.22898 | 0.22898 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 29.85200 | 1.27254E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 2725.16921 | 2725.16921 | 0.12189 | 0.12189 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1458.90077 | 1458.90077 | 0.11061 | 0.11061 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.10000 | 1.27259E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1703.42897 | 1703.42897 | 7.61895E-002 | 7.61895E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44805.59539 | 44805.59539 | 3.39730 | 3.39730 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.10000 | 1.27259E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 3604.46298 | 3604.46298 | 0.16121 | 0.16121 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 23903.46797 | 23903.46797 | 1.81407 | 1.81407 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27253E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 10399.32582 | 10399.32582 | 0.46511 | 0.67639 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 67694.74676 | 67694.74676 | 5.13476 | 5.13476 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 24985.37574 | 24985.37574 | 1.11753 | 1.89399 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 12557.29334 | 12557.29334 | 1.28302 | 1.28302 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.15733 | 1.27224E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 9503.10178 | 9503.10178 | 0.42751 | 0.42751 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11921.71095 | 11921.71095 | 1.21808 | 1.21808 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 9510.65655 | 9510.65655 | 0.42785 | 0.42785 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 75762.53081 | 75762.53081 | 7.74036 | 7.74036 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 53725.38015 | 53725.38015 | 2.41707 | 2.41707 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 54886.21818 | 54886.21818 | 5.60797 | 5.60797 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.80933 | 1.27166E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 53884.84839 | 53884.84839 | 2.42425 | 2.42425 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 11370.39671 | 11370.39671 | 1.16175 | 1.16175 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 25.38800 | 1.27176E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 9519.24410 | 9519.24410 | 0.42824 | 0.42824 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10770.69808 | 10770.69808 | 1.10048 | 1.10048 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 23.63133 | 1.27146E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 9526.79710 | 9526.79710 | 0.42858 | 0.42858 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 21308.02287 | 21308.02287 | 1.61557 | 1.61557 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.10000 | 1.27259E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 14542.89409 | 14542.89409 | 0.65048 | 0.65048 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3269.21683 | 3269.21683 | 0.33403 | 0.33403 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.36400 | 1.27228E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2900.05734 | 2900.05734 | 0.13046 | 0.13046 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3089.66628 | 3089.66628 | 0.31568 | 0.31568 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2900.26977 | 2900.26977 | 0.13047 | 0.13047 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 15826.22227 | 15826.22227 | 1.61704 | 1.61704 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 13843.39270 | 13843.39270 | 0.62278 | 0.62278 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29303.03704 | 29303.03704 | 2.22455 | 2.22455 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.10000 | 1.27259E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 9362.88169 | 9362.88169 | 0.41878 | 1.18780 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30724.17524 | 30724.17524 | 2.33240 | 2.33240 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10000 | 1.27259E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 9545.33071 | 9545.33071 | 0.42694 | 1.18780 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31456.99147 | 31456.99147 | 2.39128 | 2.39128 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 25.03667 | 1.27170E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 4375.37639 | 4375.37639 | 0.19567 | 0.36735 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -32.70000 | 1.83376E-004 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10730.38911 | 10730.38911 | 0.81357 | 0.81357 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.10000 | 1.27259E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 9695.66135 | 9695.66135 | 0.43367 | 0.43367 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 383663.59 | 23.20617 | 23.20617 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 451951.06 | 7.89009 | 7.89009 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 41147.75 | 18.79513 | 2.05125 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 117497.06 | 7.43722 | 2.05125 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.56862 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.58704 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28431 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.49024E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.40021E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28431 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8458.89167 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.40021E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 179.20217 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.46288 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11041 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23144 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50000 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.45063E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.68371E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23144 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5353.77025 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.68371E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 137.72845 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.24666 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23994 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12333 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63985 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.58787E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.78852E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12333 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2044.38415 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.78852E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 48.42434 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22898 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.54657 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11449 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.97072E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.92289E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12189 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3341.03754 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.92289E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 91.17816 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.11061 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.65282 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.53033E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.83619E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.82705E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.61895E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2088.42551 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.82705E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 56.99425 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.39730 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.94592E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.69865 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.17665E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.06594E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.69865 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12184.31380 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.06594E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 259.71764 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.81407 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.93314E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.90703 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.80264E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.31081E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.90703 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14983.31201 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31081E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 354.65650 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.13476 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19414 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.56738 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51769 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.96255E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.32102E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.56738 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 37961.34499 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.32102E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 880.30510 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.28302 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.28302 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.31373E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.98124E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70752 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62932E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.98124E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.28302 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9503.10178 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.31373E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 271.56291 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.21808 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.21808 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.32034E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.73721E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70750 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63566E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.73721E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.21808 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9510.65655 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.32034E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 271.77874 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.74036 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.74036 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.70013E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.95039E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70817 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56152E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.95039E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.74036 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 53725.38015 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.70013E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1535.26488 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.60797 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.60797 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.71408E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.30213E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70720 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.84205E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.30213E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.60797 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 53884.84839 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.71408E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1539.82084 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.16175 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.16175 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.32785E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.52751E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70749 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64336E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.52751E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.16175 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9519.24410 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.32785E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 272.02408 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.10048 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.10048 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.33446E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.29803E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70747 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.65145E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.29803E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.10048 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9526.79710 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.33446E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 272.23985 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.61557 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.73467 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80778 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.18601E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.62956E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.80778 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18626.81494 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.62956E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 478.71686 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.33403 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.33403 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.53710E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.29502E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70753 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62412E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.29502E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.33403 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2900.05734 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.53710E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 82.86881 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.31568 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.31568 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.53728E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.22617E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70751 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63101E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.22617E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.31568 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2900.26977 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.53728E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 82.87487 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.61704 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.61704 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.21108E-004 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 6.34628E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70735 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.66966E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.34628E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.61704 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 13843.39270 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21108E-004 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 395.57219 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.22455 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11361 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.11228 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.35369E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.31108E-004 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.11228 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14986.45218 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31108E-004 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 342.29060 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.33240 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10835 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.16620 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.51628E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.35090E-004 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.16620 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15441.60553 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.35090E-004 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 351.74828 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.39128 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.92085E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.19564 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.15740E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.10858E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.19564 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10411.67163 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.10858E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 225.58403 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81357 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38600 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40679 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.87045E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.04006E-004 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.43367 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11888.55491 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.04006E-004 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 324.45952 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.67062 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.67062 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 23.34124 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.67062 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 23.20617 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 23.20617 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.50291 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 23.20617 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 23.20617 |
338 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 11.66146 |
339 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.06024 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90681 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.11955E-002 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 625639.92545 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.23464E-002 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 23.20617 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 398780.75767 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.48871E-003 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5550.13398 |
351 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 23.20617 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.23464E-002 |
353 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.13095E-005 |
354 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.48871E-003 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
356 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
357 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 30.10000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.89838 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.27259E-002 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 69550.08568 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.48417E-003 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 35250.35631 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.08385E-004 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 490.60592 |
369 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.48417E-003 |
371 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.91690E-004 |
372 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.08385E-004 |
373 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.28242E-002 |
374 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 6763.86139 |
375 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 6.62358E-003 |
376 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.79483 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 6.62358E-003 |
378 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1994.73027 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 757115.44098 |
381 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 757115.44000 |
382 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 6.62358E-003 |
383 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.28242E-002 |
384 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.93891 |
385 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.28242E-002 |
386 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 4682.84938 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.28242E-002 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 918991.58837 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 919625.34000 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 104.83729 |
391 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
392 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
393 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
394 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
395 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 8502.12 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5375.69 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2053.70 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 3353.95 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 2096.49 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 12246.25 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 15051.64 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 38137.58 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 10236.15 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 10244.28 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 57870.24 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 58041.99 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 10253.53 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 10261.67 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 18703.15 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 3123.68 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 3123.90 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 14910.87 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 15057.00 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 15514.48 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 10463.88 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11934.49 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 228758.66 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 20221.20 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 21528.71 | 17059.06 | 4469.64 | 0.79 | 2588.54 | 26.25 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 20461.65 | 16205.99 | 4255.66 | 0.79 | 2459.60 | 24.95 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 128339.54 | 102209.90 | 26129.64 | 0.80 | 15475.64 | 156.96 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 97517.63 | 76126.80 | 21390.82 | 0.78 | 11632.35 | 117.98 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 19541.54 | 15468.51 | 4073.02 | 0.79 | 2348.26 | 23.82 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 18536.83 | 14664.56 | 3872.27 | 0.79 | 2226.79 | 22.59 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5599.79 | 4438.90 | 1160.89 | 0.79 | 673.45 | 6.83 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 5298.61 | 4198.02 | 1100.58 | 0.79 | 637.04 | 6.46 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 27323.44 | 21587.18 | 5736.26 | 0.79 | 3279.92 | 33.27 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 645476.80 | 424253.30 | 221223.49 | 0.66 | 79511.50 | 806.45 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 60010.76 | 38734.94 | 21275.82 | 0.65 | 6954.16 | 70.53 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.354 | 0.336 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.354 | 0.336 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.890 | 0.785 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.890 | 0.785 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.890 | 0.785 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.890 | 0.785 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.890 | 0.785 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.890 | 0.785 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.890 | 0.785 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.890 | 0.785 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.890 | 0.785 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.890 | 0.785 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.963 | 0.842 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.963 | 0.842 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.963 | 0.842 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.963 | 0.842 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.953 | 0.834 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.953 | 0.834 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.953 | 0.834 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.953 | 0.834 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.953 | 0.834 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 2.6507391622E-002 | 4.9137525062E-002 | Pass | Pass | 1.4816162417E-002 | 7.1174424757E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.9988092162E-002 | 5.9839065371E-002 | Pass | Pass | 0.1971678927 | 1.2503635118 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.1668502484E-003 | 1.2008425636E-002 | Pass | Pass | 4.7832602884E-002 | 8.1502321671E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.6762965783E-004 | 4.0749839593E-004 | Pass | Pass | 2.7275988395E-002 | 6.1198362510E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.5643062861E-004 | 4.3698632182E-004 | Pass | Pass | 1.0189620008E-002 | 1.3784995202E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.5180133490E-002 | 0.2735703982 | Pass | Pass | 2.4464712332E-002 | 5.9850155216E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.2846905698E-002 | 0.1038597443 | Pass | Pass | 6.1867179264E-002 | 0.1592306460 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.4982188589E-002 | 4.4920845774E-002 | Pass | Pass | 3.1626001264E-002 | 5.9661626443E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.8798575104E-002 | 0.3543335284 | Pass | Pass | 0.2145618292 | 0.9297402707 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2686998270E-002 | 0.3797847403 | Pass | Pass | 7.6130347148E-002 | 0.2346685036 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.3312687621E-002 | 8.4608283283E-002 | Pass | Pass | 0.1116837650 | 0.3335792896 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2655085649E-002 | 0.3027978821 | Pass | Pass | 0.2548033513 | 1.0667884945 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2698493803E-002 | 0.3564452669 | Pass | Pass | 0.1617206307 | 0.4583611289 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2700838463E-002 | 0.3732477998 | Pass | Pass | 8.9260043637E-002 | 0.3082410233 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.2629566650E-004 | 3.2672313407E-004 | Pass | Pass | 0.5903345095 | 4.5224802068 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2687255659E-002 | 0.3822270035 | Pass | Pass | 0.1976077006 | 0.7567895784 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2693910877E-002 | 0.3886782618 | Pass | Pass | 5.5491668814E-002 | 0.1665905156 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2097650508E-002 | 0.3336070550 | Pass | Pass | 0.3183774053 | 0.8551703963 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.9934686542E-002 | 0.1333064486 | Pass | Pass | 2.2133761903E-002 | 5.5212155624E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.5741051813E-002 | 0.1424277457 | Pass | Pass | 1.8112637693E-002 | 4.4675027640E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.3142012262E-002 | 0.1537379875 | Pass | Pass | 2.7404009700E-002 | 4.7099137680E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.5413267412E-004 | 7.1082653333E-004 | Pass | Pass | 5.3937086073E-002 | 7.0041900036E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3872.57 | 204.28 | 2398.09 | 10365.63 | 3482.81 | 20323.40 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.340 | 0.354 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.340 | 0.354 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.842 | 0.963 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.842 | 0.963 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.842 | 0.963 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.842 | 0.963 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.834 | 0.953 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.834 | 0.953 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.834 | 0.953 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.834 | 0.953 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.834 | 0.953 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 1.683 | 0.451 | 0.452 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 1.683 | 0.451 | 0.452 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 1.683 | 0.451 | 0.452 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.683 | 0.451 | 0.452 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.683 | 0.451 | 0.452 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.683 | 0.451 | 0.452 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.683 | 0.451 | 0.452 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 1.683 | 0.451 | 0.452 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 1.683 | 0.451 | 0.452 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.683 | 0.451 | 0.452 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.683 | 0.451 | 0.452 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.683 | 0.451 | 0.452 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.683 | 0.451 | 0.452 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.683 | 0.451 | 0.452 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 1.683 | 0.451 | 0.452 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 1.683 | 0.451 | 0.452 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.683 | 0.451 | 0.452 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.683 | 0.451 | 0.452 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.683 | 0.451 | 0.452 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.683 | 0.451 | 0.452 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.683 | 0.451 | 0.452 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 1.683 | 0.451 | 0.452 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.683 | 0.451 | 0.452 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.683 | 0.451 | 0.452 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.683 | 0.451 | 0.452 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.683 | 0.451 | 0.452 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.683 | 0.451 | 0.452 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 1.683 | 0.451 | 0.452 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 1.683 | 0.451 | 0.452 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.683 | 0.451 | 0.452 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 1.683 | 0.451 | 0.452 | |||||||||||||||||
North Total or Average | 432.95 | 1.683 | 0.451 | 0.452 | |||||||||||||||||
Non-North Total or Average | 780.84 | 1.683 | 0.451 | 0.452 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.1389 | 1978.83 | 18084.33 | LightsWired | LTG_SCH_BASEMENT | 51.16 | 168.00 | 51.10 | 0.0000 | Y | 173.46 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.3365 | 67.07 | 894.50 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.61 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.3365 | 77.67 | 1035.83 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 9.97 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 9.2031 | 164.24 | 1511.55 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 16.63 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 6.1031 | 94.76 | 578.33 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 2.78 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.8125 | 78.04 | 453.60 | LightsWired | LTG_SCH_LAUNDRY | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 4.37 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.3656 | 188.86 | 1957.67 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.48 | 0.0000 | Y | 17.82 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 8.7188 | 1308.19 | 11405.76 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 56.87 | 0.0000 | Y | 121.76 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.5531 | 156.09 | 710.69 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.5531 | 156.07 | 710.61 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.5531 | 1863.81 | 8486.17 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 76.02 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.5531 | 1864.32 | 8488.49 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 76.04 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.5531 | 156.09 | 710.69 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.5531 | 156.07 | 710.61 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 6.3938 | 1557.62 | 9959.03 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 109.60 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.5531 | 39.02 | 177.67 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.59 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.5531 | 39.02 | 177.65 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.59 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.5531 | 220.77 | 1005.22 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 9.00 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.3656 | 331.66 | 3437.84 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 53.51 | 0.0000 | Y | 34.53 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.3656 | 331.66 | 3437.84 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 53.51 | 0.0000 | Y | 34.53 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7219 | 103.30 | 1210.92 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.33 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 6.3938 | 412.12 | 2635.02 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 29.00 |
Interior Lighting Total | 6.8557 | 11345.29 | 77780.02 | 506.75 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 11405.76 | 798.40 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 11405.76 | 0.00 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1957.67 | 763.49 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 1957.67 | 0.00 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3437.84 | 687.57 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3437.84 | 0.00 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3437.84 | 687.57 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3437.84 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 15448.40 | AstronomicalClock | - | 83.52 | 83.52 | 242.19 | |
Exterior Lighting Total | 15448.40 | 242.19 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 757115.44 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 919625.34 | 2.96 | 919786.99 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13946.42 | 21528.71 | 17059.06 | 4469.64 | 0.79 | - | 2588.54 | 26.25 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13263.18 | 20461.65 | 16205.99 | 4255.66 | 0.79 | - | 2459.60 | 24.95 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 82604.70 | 128339.54 | 102209.90 | 26129.64 | 0.80 | - | 15475.64 | 156.96 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 64454.82 | 97517.63 | 76126.80 | 21390.82 | 0.78 | - | 11632.35 | 117.98 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12676.05 | 19541.54 | 15468.51 | 4073.02 | 0.79 | - | 2348.26 | 23.82 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12033.57 | 18536.83 | 14664.56 | 3872.27 | 0.79 | - | 2226.79 | 22.59 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3625.78 | 5599.79 | 4438.90 | 1160.89 | 0.79 | - | 673.45 | 6.83 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3433.02 | 5298.61 | 4198.02 | 1100.58 | 0.79 | - | 637.04 | 6.46 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 17768.23 | 27323.44 | 21587.18 | 5736.26 | 0.79 | - | 3279.92 | 33.27 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 625639.93 | 645476.80 | 424253.30 | 221223.49 | 0.66 | - | 79511.50 | 806.45 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 69550.09 | 60010.76 | 38734.94 | 21275.82 | 0.65 | - | 6954.16 | 70.53 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 8458.89 | 8502.12 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 5353.77 | 5375.69 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2044.38 | 2053.70 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3341.04 | 3353.95 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2088.43 | 2096.49 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12184.31 | 12246.25 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 14983.31 | 15051.64 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 37961.34 | 38137.58 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9503.10 | 10236.15 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9510.66 | 10244.28 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 53725.38 | 57870.24 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 53884.85 | 58041.99 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9519.24 | 10253.53 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9526.80 | 10261.67 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 18626.81 | 18703.15 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2900.06 | 3123.68 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2900.27 | 3123.90 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 13843.39 | 14910.87 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14986.45 | 15057.00 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 15441.61 | 15514.48 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10411.67 | 10463.88 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11888.55 | 11934.49 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 398780.76 | 228758.66 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 35250.36 | 20221.20 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.28 | 902.78 | 703.64 | 1.00 | 1.14 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.22 | 857.09 | 703.64 | 1.00 | 1.15 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 7.74 | 5446.40 | 703.64 | 1.00 | 0.94 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.61 | 3945.97 | 703.64 | 1.00 | 0.96 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.16 | 817.45 | 703.64 | 1.00 | 1.16 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.10 | 774.34 | 703.64 | 1.00 | 1.17 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.33 | 235.03 | 703.64 | 1.00 | 1.64 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.32 | 222.13 | 703.64 | 1.00 | 1.68 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.62 | 1137.81 | 703.64 | 1.00 | 1.10 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 23.21 | 51996.65 | 2240.64 | 1.00 | 1.11 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.032824 | 6763.86 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.006624 | 1994.73 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.032824 | 4682.85 | 142664.32 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 33877.36 | 33877.36 | 17.12 | 2.569 | 2.569 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 24.00 | 24.00 | 0.00921 | 25.04 | 0.01272 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 6104.08 | 6104.08 | 91.01 | 0.463 | 0.463 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00898 | 29.79 | 0.01273 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3252.72 | 3252.72 | 41.88 | 0.247 | 0.247 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00942 | 29.98 | 0.01273 | 0.092 | 0.00 |
MECH_FLR_1 | 3020.25 | 3020.25 | 18.39 | 0.229 | 0.229 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00884 | 29.85 | 0.01273 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1458.90 | 1458.90 | 15.40 | 0.111 | 0.111 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00899 | 30.10 | 0.01273 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44805.60 | 44805.60 | 574.14 | 3.397 | 3.397 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00856 | 30.10 | 0.01273 | 0.000 | 0.00 |
CAFE_FLR_1 | 23903.47 | 23903.47 | 126.57 | 1.814 | 1.814 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.00988 | 29.79 | 0.01273 | 0.676 | 0.00 |
LOBBY_FLR_1 | 67694.75 | 67694.75 | 51.75 | 5.135 | 5.135 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.00994 | 29.89 | 0.01273 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 12557.29 | 12557.29 | 321.80 | 1.283 | 1.283 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00863 | 28.16 | 0.01272 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11921.71 | 11921.71 | 305.55 | 1.218 | 1.218 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00864 | 27.95 | 0.01272 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 75762.53 | 75762.53 | 3089.34 | 7.740 | 7.740 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00856 | 29.89 | 0.01273 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 54886.22 | 54886.22 | 2237.46 | 5.608 | 5.608 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 21.11 | 21.11 | 0.00884 | 24.81 | 0.01272 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 11370.40 | 11370.40 | 291.38 | 1.162 | 1.162 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 21.11 | 21.11 | 0.00864 | 25.39 | 0.01272 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10770.70 | 10770.70 | 276.05 | 1.100 | 1.100 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 21.11 | 21.11 | 0.00865 | 23.63 | 0.01271 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 21308.02 | 21308.02 | 54.72 | 1.616 | 1.616 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00945 | 30.10 | 0.01273 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3269.22 | 3269.22 | 83.78 | 0.334 | 0.334 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00862 | 28.36 | 0.01272 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3089.67 | 3089.67 | 79.19 | 0.316 | 0.316 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00863 | 27.95 | 0.01272 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 15826.22 | 15826.22 | 645.16 | 1.617 | 1.617 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00867 | 29.89 | 0.01273 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29303.04 | 29303.04 | 88.35 | 2.225 | 2.225 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.98 | 0.01044 | 30.10 | 0.01273 | 1.188 | 0.00 |
DINING_FLR_6 | 30724.18 | 30724.18 | 92.64 | 2.332 | 2.332 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01035 | 30.10 | 0.01273 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31456.99 | 31456.99 | 304.51 | 2.391 | 2.391 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 23.97 | 0.00998 | 25.04 | 0.01272 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10730.39 | 10730.39 | 26.04 | 0.814 | 0.814 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00902 | 30.10 | 0.01273 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1960.76 | 1960.76 | 0.99 | 0.088 | 0.854 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00799 | -32.70 | 0.00018 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4184.33 | 4184.33 | 62.39 | 0.187 | 0.187 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00753 | -32.70 | 0.00018 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1421.10 | 1421.10 | 18.30 | 0.064 | 0.092 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00747 | -32.70 | 0.00018 | 0.092 | 0.00 |
MECH_FLR_1 | 2725.17 | 2725.17 | 16.59 | 0.122 | 0.122 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00736 | -32.70 | 0.00018 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1703.43 | 1703.43 | 17.98 | 0.076 | 0.076 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00740 | -32.70 | 0.00018 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 3604.46 | 3604.46 | 46.19 | 0.161 | 0.161 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00734 | -32.70 | 0.00018 | 0.000 | 0.00 |
CAFE_FLR_1 | 10399.33 | 10399.33 | 55.06 | 0.465 | 0.676 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00758 | -32.70 | 0.00018 | 0.676 | 0.00 |
LOBBY_FLR_1 | 24985.38 | 24985.38 | 19.10 | 1.118 | 1.894 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00751 | -32.70 | 0.00018 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 9503.10 | 9503.10 | 243.53 | 0.428 | 0.428 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00752 | -32.70 | 0.00018 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9510.66 | 9510.66 | 243.75 | 0.428 | 0.428 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00752 | -32.70 | 0.00018 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 53725.38 | 53725.38 | 2190.74 | 2.417 | 2.417 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00755 | -32.70 | 0.00018 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 53884.85 | 53884.85 | 2196.64 | 2.424 | 2.424 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00755 | -32.70 | 0.00018 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9519.24 | 9519.24 | 243.95 | 0.428 | 0.428 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00752 | -32.70 | 0.00018 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9526.80 | 9526.80 | 244.17 | 0.429 | 0.429 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00752 | -32.70 | 0.00018 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 14542.89 | 14542.89 | 37.35 | 0.650 | 0.650 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00762 | -32.70 | 0.00018 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2900.06 | 2900.06 | 74.32 | 0.130 | 0.130 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00761 | -32.70 | 0.00018 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2900.27 | 2900.27 | 74.33 | 0.130 | 0.130 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00761 | -32.70 | 0.00018 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13843.39 | 13843.39 | 564.33 | 0.623 | 0.623 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00762 | -32.70 | 0.00018 | 0.099 | 0.00 |
BANQUET_FLR_6 | 9362.88 | 9362.88 | 28.23 | 0.419 | 1.188 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00770 | -32.70 | 0.00018 | 1.188 | 0.00 |
DINING_FLR_6 | 9545.33 | 9545.33 | 28.78 | 0.427 | 1.188 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00770 | -32.70 | 0.00018 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 4375.38 | 4375.38 | 42.35 | 0.196 | 0.367 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00720 | -32.70 | 0.00018 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9695.66 | 9695.66 | 23.53 | 0.434 | 0.434 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00774 | -32.70 | 0.00018 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 23.21 | 23.21 | 7.89 | 7.89 | 23.2062 | 11.6706 | 23.2062 | 0.5029 | 0.3000 |
FLR_3_DOAS | 18.80 | 2.05 | 7.44 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 8458.892 | 8458.892 | 1.284309 | 0.00007400 | 179.202 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8458.89 | 8458.89 | 1.284309 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00799429 | 49.5246 | 1960.76 | 0.00 | 8506.17 | 8506.17 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 5353.770 | 5353.770 | 0.231438 | 0.00004684 | 137.728 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 5353.77 | 5353.77 | 0.231438 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00753092 | 46.6943 | 4184.33 | 0.00 | 5380.82 | 5380.82 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 2044.384 | 2044.384 | 0.123328 | 0.00001789 | 48.424 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2044.38 | 2044.38 | 0.123328 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00747123 | 46.3250 | 1421.10 | 0.00 | 2055.25 | 2055.25 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 3341.038 | 3341.038 | 0.121889 | 0.00002923 | 91.178 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3341.04 | 3341.04 | 0.121889 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00735841 | 45.6339 | 2725.17 | 0.00 | 3357.61 | 3357.61 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 2088.426 | 2088.426 | 0.076190 | 0.00001827 | 56.994 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2088.43 | 2088.43 | 0.076190 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00740404 | 45.9135 | 1703.43 | 0.00 | 2098.78 | 2098.78 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12184.314 | 12184.314 | 1.698649 | 0.00010659 | 259.718 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12184.31 | 12184.31 | 1.698649 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00733936 | 45.5209 | 3604.46 | 0.00 | 12252.28 | 12252.28 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 14983.312 | 14983.312 | 0.907035 | 0.00013108 | 354.657 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 14983.31 | 14983.31 | 0.907035 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00758000 | 46.9939 | 10399.33 | 0.00 | 15062.99 | 15062.99 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 37961.345 | 37961.345 | 2.567381 | 0.00033210 | 880.305 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 37961.34 | 37961.34 | 2.567381 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00750557 | 46.5354 | 24985.38 | 0.00 | 38164.41 | 38164.41 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 13946.418 | -999.000 | 1.283020 | 0.00049812 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 13946.42 | 13540.90 | 1.283020 | 21.71 | 15.25 | 0.00862932 | 12.80 | 11.72 | 0.00850000 | 28.16 | 0.01272245 | 20.56 | 0.0000 | 21.11 | 0.00862932 | 53.0444 | 12557.29 | 0.00 | 14514.23 | 13811.83 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 9503.102 | 9503.102 | 0.427511 | 0.00008314 | 271.563 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9503.10 | 9503.10 | 0.427511 | 21.11 | 14.04 | 0.00752372 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00752372 | 46.3339 | 9503.10 | 0.00 | 10244.29 | 10244.29 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 13263.178 | -999.000 | 1.218083 | 0.00047372 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 13263.18 | 12859.18 | 1.218083 | 21.71 | 15.26 | 0.00863566 | 12.80 | 11.72 | 0.00850000 | 27.95 | 0.01272209 | 20.50 | 0.0000 | 21.11 | 0.00863566 | 53.0828 | 11921.71 | 0.00 | 13802.73 | 13115.76 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 9510.657 | 9510.657 | 0.427851 | 0.00008320 | 271.779 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9510.66 | 9510.66 | 0.427851 | 21.11 | 14.04 | 0.00752411 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00752411 | 46.3363 | 9510.66 | 0.00 | 10252.43 | 10252.43 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 82604.699 | -999.000 | 7.740363 | 0.00295039 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 82604.70 | 81444.47 | 7.740363 | 21.71 | 15.19 | 0.00856152 | 12.80 | 11.72 | 0.00850000 | 29.89 | 0.01272550 | 21.07 | 0.0000 | 21.11 | 0.00856152 | 52.6314 | 75762.53 | 0.00 | 85997.78 | 83124.37 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 53725.380 | 53725.380 | 2.417073 | 0.00047001 | 1535.265 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 53725.38 | 53725.38 | 2.417073 | 21.11 | 14.07 | 0.00755172 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00755172 | 46.5008 | 53725.38 | 0.00 | 57916.82 | 57916.82 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 64454.824 | -999.000 | 5.607968 | 0.00230213 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | unknown | 7/21 19:20:00 | 64454.82 | 59723.82 | 5.607968 | 21.71 | 15.44 | 0.00884205 | 12.80 | 11.72 | 0.00850000 | 24.81 | 0.01271660 | 19.55 | 0.0000 | 21.11 | 0.00884205 | 54.3340 | 54886.22 | 0.00 | 67008.92 | 60813.80 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 53884.848 | 53884.848 | 2.424248 | 0.00047141 | 1539.821 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 53884.85 | 53884.85 | 2.424248 | 21.11 | 14.07 | 0.00755286 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00755286 | 46.5077 | 53884.85 | 0.00 | 58088.73 | 58088.73 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 12676.046 | -999.000 | 1.161754 | 0.00045275 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | 7/21 10:00:00 | 12676.05 | 12268.73 | 1.161754 | 21.71 | 15.26 | 0.00864336 | 12.80 | 11.72 | 0.00850000 | 25.39 | 0.01271761 | 19.73 | 0.0000 | 21.11 | 0.00864336 | 53.1295 | 11370.40 | 0.00 | 13191.20 | 12512.68 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9519.244 | 9519.244 | 0.428237 | 0.00008328 | 272.024 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9519.24 | 9519.24 | 0.428237 | 21.11 | 14.04 | 0.00752448 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00752448 | 46.3386 | 9519.24 | 0.00 | 10261.69 | 10261.69 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 12033.565 | -999.000 | 1.100482 | 0.00042980 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | 7/21 09:10:00 | 12033.57 | 11625.82 | 1.100482 | 21.71 | 15.27 | 0.00865145 | 12.80 | 11.72 | 0.00850000 | 23.63 | 0.01271456 | 19.19 | 0.0000 | 21.11 | 0.00865145 | 53.1786 | 10770.70 | 0.00 | 12522.10 | 11856.17 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9526.797 | 9526.797 | 0.428577 | 0.00008334 | 272.240 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9526.80 | 9526.80 | 0.428577 | 21.11 | 14.04 | 0.00752487 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00752487 | 46.3409 | 9526.80 | 0.00 | 10269.83 | 10269.83 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 18626.815 | 18626.815 | 0.807783 | 0.00016296 | 478.717 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 18626.81 | 18626.81 | 0.807783 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00761670 | 47.2148 | 14542.89 | 0.00 | 18720.95 | 18720.95 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3625.777 | -999.000 | 0.334027 | 0.00012950 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3625.78 | 3524.47 | 0.334027 | 21.71 | 15.25 | 0.00862412 | 12.80 | 11.72 | 0.00850000 | 28.36 | 0.01272282 | 20.62 | 0.0000 | 21.11 | 0.00862412 | 53.0128 | 3269.22 | 0.00 | 3773.50 | 3595.15 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2900.057 | 2900.057 | 0.130464 | 0.00002537 | 82.869 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2900.06 | 2900.06 | 0.130464 | 21.11 | 14.12 | 0.00760539 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00760539 | 46.8306 | 2900.06 | 0.00 | 3126.25 | 3126.25 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3433.020 | -999.000 | 0.315682 | 0.00012262 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 3433.02 | 3331.93 | 0.315682 | 21.71 | 15.25 | 0.00863101 | 12.80 | 11.72 | 0.00850000 | 27.95 | 0.01272209 | 20.50 | 0.0000 | 21.11 | 0.00863101 | 53.0546 | 3089.67 | 0.00 | 3572.76 | 3398.55 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2900.270 | 2900.270 | 0.130473 | 0.00002537 | 82.875 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2900.27 | 2900.27 | 0.130473 | 21.11 | 14.12 | 0.00760544 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00760544 | 46.8309 | 2900.27 | 0.00 | 3126.48 | 3126.48 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 17768.230 | -999.000 | 1.617043 | 0.00063463 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 17768.23 | 17096.48 | 1.617043 | 21.71 | 15.29 | 0.00866966 | 12.80 | 11.72 | 0.00850000 | 29.89 | 0.01272550 | 21.07 | 0.0000 | 21.11 | 0.00866966 | 53.2894 | 15826.22 | 0.00 | 18487.88 | 17432.51 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13843.393 | 13843.393 | 0.622782 | 0.00012111 | 395.572 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 13843.39 | 13843.39 | 0.622782 | 21.11 | 14.13 | 0.00761867 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00761867 | 46.9101 | 13843.39 | 0.00 | 14923.22 | 14923.22 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14986.452 | 14986.452 | 1.112276 | 0.00013111 | 342.291 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 14986.45 | 14986.45 | 1.112276 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00769615 | 47.7026 | 9362.88 | 0.00 | 15067.02 | 15067.02 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 15441.606 | 15441.606 | 1.166201 | 0.00013509 | 351.748 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 15441.61 | 15441.61 | 1.166201 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00770174 | 47.7368 | 9545.33 | 0.00 | 15524.70 | 15524.70 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10411.672 | 10411.672 | 1.195642 | 0.00009109 | 225.584 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 10411.67 | 10411.67 | 1.195642 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00720170 | 44.6795 | 4375.38 | 0.00 | 10469.46 | 10469.46 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 11888.555 | 11888.555 | 0.433667 | 0.00010401 | 324.460 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11888.55 | 11888.55 | 0.433667 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00774136 | 47.9786 | 9695.66 | 0.00 | 11947.51 | 11947.51 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 625639.925 | -999.000 | 23.206172 | 0.02234641 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 625639.93 | 441092.57 | 23.206172 | 27.06 | 19.12 | 0.01119553 | 10.91 | 10.91 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 50.2515 | 23.99 | 0.00961538 | 49.5358 | 305817.93 | 0.00 | 642246.78 | 435587.70 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 398780.758 | 398780.758 | 6.961852 | 0.00348871 | 5550.134 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 398780.76 | 398780.76 | 6.961852 | -32.70 | -32.70 | 0.00018338 | 16.70 | 12.79 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 167.5051 | 21.00 | 0.00758402 | 47.0158 | 97410.98 | 0.00 | 276279.94 | 276279.94 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 69550.086 | -999.000 | 2.051317 | 0.00248417 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 69550.09 | 44784.57 | 2.051317 | 30.10 | 21.13 | 0.01272586 | 11.90 | 11.35 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 99.9965 | 21.11 | 0.00868219 | 53.3639 | 183957.63 | 0.00 | 71097.05 | 44995.87 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 35250.356 | 35250.356 | 0.615395 | 0.00030839 | 490.606 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 35250.36 | 35250.36 | 0.615395 | -32.70 | -32.70 | 0.00018338 | 16.70 | 12.79 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 333.3216 | 21.11 | 0.00755280 | 46.5074 | 165313.75 | 0.00 | 24421.86 | 24421.86 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 8458.892 | 8458.892 | 1.284309 | 0.00007400 | 179.202 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 1.0952 | 1.117253 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8458.89 | 8458.89 | 1.0000 | 1.48199593 | 1.284309 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.07399453 | 60.00 | 32.22 | 27.78 | 0.000 | 8458.89 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00799429 | 21.00 | 0.00799429 | 49.5246 | 1960.76 | 0.00 | 8506.17 | 8506.17 | 1.48199593 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.23 | 15.31 | 0.00800000 | 42674.4 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5353.770 | 5353.770 | 0.231438 | 0.00004684 | 137.728 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 0.6932 | 0.707127 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 5353.77 | 5353.77 | 1.0000 | 0.26706234 | 0.231438 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.04683234 | 60.00 | 32.22 | 27.78 | 0.000 | 5353.77 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00753092 | 21.00 | 0.00753092 | 46.6943 | 4184.33 | 0.00 | 5380.82 | 5380.82 | 0.26706234 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 36.36 | 20.08 | 0.00800000 | 57082.9 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2044.384 | 2044.384 | 0.123328 | 0.00001789 | 48.424 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 0.2647 | 0.270023 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2044.38 | 2044.38 | 1.0000 | 0.14231131 | 0.123328 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.01788334 | 60.00 | 32.22 | 27.78 | 0.000 | 2044.38 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00747123 | 21.00 | 0.00747123 | 46.3250 | 1421.10 | 0.00 | 2055.25 | 2055.25 | 0.14231131 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.76 | 18.29 | 0.00800000 | 51376.7 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3341.038 | 3341.038 | 0.121889 | 0.00002923 | 91.178 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 0.4326 | 0.441285 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3341.04 | 3341.04 | 1.0000 | 0.14065067 | 0.121889 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.02922587 | 60.00 | 32.22 | 27.78 | 0.000 | 3341.04 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00735841 | 21.00 | 0.00735841 | 45.6339 | 2725.17 | 0.00 | 3357.61 | 3357.61 | 0.14065067 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60806.7 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2088.426 | 2088.426 | 0.076190 | 0.00001827 | 56.994 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 0.2704 | 0.275840 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2088.43 | 2088.43 | 1.0000 | 0.08791698 | 0.076190 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.01826859 | 60.00 | 32.22 | 27.78 | 0.000 | 2088.43 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00740404 | 21.00 | 0.00740404 | 45.9135 | 1703.43 | 0.00 | 2098.78 | 2098.78 | 0.08791698 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60807.1 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12184.314 | 12184.314 | 1.698649 | 0.00010659 | 259.718 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 1.5776 | 1.609307 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 12184.31 | 12184.31 | 1.0000 | 1.96011297 | 1.698649 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.10658282 | 60.00 | 32.22 | 27.78 | 0.000 | 12184.31 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00733936 | 21.00 | 0.00733936 | 45.5209 | 3604.46 | 0.00 | 12252.28 | 12252.28 | 1.96011297 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.73 | 15.49 | 0.00800000 | 43185.5 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14983.312 | 14983.312 | 0.907035 | 0.00013108 | 354.657 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 1.9400 | 1.979000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 14983.31 | 14983.31 | 1.0000 | 1.04664997 | 0.907035 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.13106718 | 60.00 | 32.22 | 27.78 | 0.000 | 14983.31 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00758000 | 21.00 | 0.00758000 | 46.9939 | 10399.33 | 0.00 | 15062.99 | 15062.99 | 1.04664997 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.71 | 18.27 | 0.00800000 | 51326.4 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 37961.345 | 37961.345 | 2.567381 | 0.00033210 | 880.305 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 4.9150 | 5.013944 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 37961.34 | 37961.34 | 1.0000 | 2.96256495 | 2.567381 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.33206853 | 60.00 | 32.22 | 27.78 | 0.000 | 37961.34 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00750557 | 21.00 | 0.00750557 | 46.5354 | 24985.38 | 0.00 | 38164.41 | 38164.41 | 2.96256495 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.23 | 17.78 | 0.00800000 | 49816.9 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13946.418 | -999.000 | 1.283020 | 0.00049812 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8815 | 1004.8586 | 1.1539 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.283020 | 1.48050919 | 4197.9300 | 999.8980 | 32.82090181 | 13.37 | 6.70 | 6.67 | 918991.59 | 1.5176 | 1.517550 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 13946.42 | 13540.90 | 1.0000 | 1.48050919 | 1.283020 | 21.71 | 15.25 | 0.00862932 | 43742.2 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.49807363 | 6.70 | 13.37 | 6.67 | 0.000 | 13946.42 | 28.16 | 0.01272245 | 20.56 | 0.00000000 | 0.0000 | 21.11 | 0.00862932 | 21.11 | 0.00862932 | 53.0444 | 12557.29 | 0.00 | 14514.23 | 13811.83 | 1.48050919 | 21.71 | 15.68 | 0.00862932 | 43742.2 | 12.57 | 11.95 | 0.00844137 | 33938.7 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9503.102 | 9503.102 | 0.427511 | 0.00008314 | 271.563 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.283020 | 1.48050919 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 1.2304 | 1.255172 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9503.10 | 9503.10 | 1.0000 | 0.49331567 | 0.427511 | 21.11 | 14.04 | 0.00752372 | 40322.4 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.08312880 | 60.00 | 32.22 | 27.78 | 0.000 | 9503.10 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00752372 | 21.11 | 0.00752372 | 46.3339 | 9503.10 | 0.00 | 10244.29 | 10244.29 | 0.49331567 | 16.60 | 12.69 | 0.00752372 | 35728.9 | 36.98 | 19.91 | 0.00752372 | 56495.1 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13263.178 | -999.000 | 1.218083 | 0.00047372 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8933 | 1004.8586 | 1.1539 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.218083 | 1.40557571 | 4197.9300 | 999.8980 | 32.82090181 | 13.37 | 6.70 | 6.67 | 918991.59 | 1.4432 | 1.443205 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 13263.18 | 12859.18 | 1.0000 | 1.40557571 | 1.218083 | 21.71 | 15.26 | 0.00863566 | 43758.3 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.47367281 | 6.70 | 13.37 | 6.67 | 0.000 | 13263.18 | 27.95 | 0.01272209 | 20.50 | 0.00000000 | 0.0000 | 21.11 | 0.00863566 | 21.11 | 0.00863566 | 53.0828 | 11921.71 | 0.00 | 13802.73 | 13115.76 | 1.40557571 | 21.71 | 15.68 | 0.00863566 | 43758.3 | 12.57 | 11.95 | 0.00844204 | 33938.3 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9510.657 | 9510.657 | 0.427851 | 0.00008320 | 271.779 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.218083 | 1.40557571 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 1.2314 | 1.256170 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9510.66 | 9510.66 | 1.0000 | 0.49370785 | 0.427851 | 21.11 | 14.04 | 0.00752411 | 40323.4 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.08319488 | 60.00 | 32.22 | 27.78 | 0.000 | 9510.66 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00752411 | 21.11 | 0.00752411 | 46.3363 | 9510.66 | 0.00 | 10252.43 | 10252.43 | 0.49370785 | 16.60 | 12.69 | 0.00752411 | 35729.9 | 36.98 | 19.91 | 0.00752411 | 56496.1 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 82604.699 | -999.000 | 7.740363 | 0.00295039 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7554 | 1004.8586 | 1.1539 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.740363 | 8.93179747 | 4197.9300 | 999.8980 | 32.82090181 | 13.37 | 6.70 | 6.67 | 918991.59 | 8.9886 | 8.988456 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 82604.70 | 81444.47 | 1.0000 | 8.93179747 | 7.740363 | 21.71 | 15.19 | 0.00856152 | 43570.6 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 2.95009237 | 6.70 | 13.37 | 6.67 | 0.000 | 82604.70 | 29.89 | 0.01272550 | 21.07 | 0.00000000 | 0.0000 | 21.11 | 0.00856152 | 21.11 | 0.00856152 | 52.6314 | 75762.53 | 0.00 | 85997.78 | 83124.37 | 8.93179747 | 21.71 | 15.62 | 0.00856152 | 43570.6 | 12.59 | 11.95 | 0.00843408 | 33942.3 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 53725.380 | 53725.380 | 2.417073 | 0.00047001 | 1535.265 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.740363 | 8.93179747 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 6.9561 | 7.096062 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 53725.38 | 53725.38 | 1.0000 | 2.78912101 | 2.417073 | 21.11 | 14.07 | 0.00755172 | 40394.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.46996512 | 60.00 | 32.22 | 27.78 | 0.000 | 53725.38 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00755172 | 21.11 | 0.00755172 | 46.5008 | 53725.38 | 0.00 | 57916.82 | 57916.82 | 2.78912101 | 16.60 | 12.71 | 0.00755172 | 35799.8 | 36.98 | 19.93 | 0.00755172 | 56565.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 64454.824 | -999.000 | 5.607968 | 0.00230213 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2769 | 1004.8586 | 1.1539 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.607968 | 6.47117420 | 4197.9300 | 999.8980 | 32.82090181 | 13.37 | 6.70 | 6.67 | 918991.59 | 7.0136 | 7.013516 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | unknown | unknown | unknown | 7/21 19:20:00 | Sensible | 64454.82 | 59723.82 | 1.0000 | 6.47117420 | 5.607968 | 21.71 | 15.44 | 0.00884205 | 44282.5 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 2.30189912 | 6.70 | 13.37 | 6.67 | 0.000 | 64454.82 | 24.81 | 0.01271660 | 19.55 | 0.00000000 | 0.0000 | 21.11 | 0.00884205 | 21.11 | 0.00884205 | 54.3340 | 54886.22 | 0.00 | 67008.92 | 60813.80 | 6.47117420 | 21.71 | 15.86 | 0.00884205 | 44282.5 | 12.51 | 11.94 | 0.00846278 | 33927.5 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 53884.848 | 53884.848 | 2.424248 | 0.00047141 | 1539.821 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.607968 | 6.47117420 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 6.9767 | 7.117124 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 53884.85 | 53884.85 | 1.0000 | 2.79739974 | 2.424248 | 21.11 | 14.07 | 0.00755286 | 40397.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.47136007 | 60.00 | 32.22 | 27.78 | 0.000 | 53884.85 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00755286 | 21.11 | 0.00755286 | 46.5077 | 53884.85 | 0.00 | 58088.73 | 58088.73 | 2.79739974 | 16.60 | 12.71 | 0.00755286 | 35802.7 | 36.98 | 19.94 | 0.00755286 | 56567.9 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12676.046 | -999.000 | 1.161754 | 0.00045275 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9076 | 1004.8586 | 1.1539 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.161754 | 1.34057627 | 4197.9300 | 999.8980 | 32.82090181 | 13.37 | 6.70 | 6.67 | 918991.59 | 1.3793 | 1.379317 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | unknown | unknown | 7/21 10:00:00 | Sensible | 12676.05 | 12268.73 | 1.0000 | 1.34057627 | 1.161754 | 21.71 | 15.26 | 0.00864336 | 43777.9 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.45270436 | 6.70 | 13.37 | 6.67 | 0.000 | 12676.05 | 25.39 | 0.01271761 | 19.73 | 0.00000000 | 0.0000 | 21.11 | 0.00864336 | 21.11 | 0.00864336 | 53.1295 | 11370.40 | 0.00 | 13191.20 | 12512.68 | 1.34057627 | 21.71 | 15.69 | 0.00864336 | 43777.9 | 12.56 | 11.95 | 0.00844285 | 33937.9 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9519.244 | 9519.244 | 0.428237 | 0.00008328 | 272.024 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.161754 | 1.34057627 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 1.2325 | 1.257304 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9519.24 | 9519.24 | 1.0000 | 0.49415365 | 0.428237 | 21.11 | 14.04 | 0.00752448 | 40324.3 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.08327000 | 60.00 | 32.22 | 27.78 | 0.000 | 9519.24 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00752448 | 21.11 | 0.00752448 | 46.3386 | 9519.24 | 0.00 | 10261.69 | 10261.69 | 0.49415365 | 16.60 | 12.69 | 0.00752448 | 35730.8 | 36.98 | 19.91 | 0.00752448 | 56497.0 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12033.565 | -999.000 | 1.100482 | 0.00042980 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9226 | 1004.8586 | 1.1539 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.100482 | 1.26987298 | 4197.9300 | 999.8980 | 32.82090181 | 13.37 | 6.70 | 6.67 | 918991.59 | 1.3094 | 1.309407 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | unknown | unknown | 7/21 09:10:00 | Sensible | 12033.57 | 11625.82 | 1.0000 | 1.26987298 | 1.100482 | 21.71 | 15.27 | 0.00865145 | 43798.4 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.42975919 | 6.70 | 13.37 | 6.67 | 0.000 | 12033.57 | 23.63 | 0.01271456 | 19.19 | 0.00000000 | 0.0000 | 21.11 | 0.00865145 | 21.11 | 0.00865145 | 53.1786 | 10770.70 | 0.00 | 12522.10 | 11856.17 | 1.26987298 | 21.71 | 15.70 | 0.00865145 | 43798.4 | 12.56 | 11.95 | 0.00844370 | 33937.5 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9526.797 | 9526.797 | 0.428577 | 0.00008334 | 272.240 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.100482 | 1.26987298 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 1.2335 | 1.258302 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9526.80 | 9526.80 | 1.0000 | 0.49454573 | 0.428577 | 21.11 | 14.04 | 0.00752487 | 40325.3 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.08333607 | 60.00 | 32.22 | 27.78 | 0.000 | 9526.80 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00752487 | 21.11 | 0.00752487 | 46.3409 | 9526.80 | 0.00 | 10269.83 | 10269.83 | 0.49454573 | 16.60 | 12.69 | 0.00752487 | 35731.8 | 36.98 | 19.92 | 0.00752487 | 56498.0 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18626.815 | 18626.815 | 0.807783 | 0.00016296 | 478.717 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 2.4117 | 2.460234 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 18626.81 | 18626.81 | 1.0000 | 0.93212131 | 0.807783 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.16293888 | 60.00 | 32.22 | 27.78 | 0.000 | 18626.81 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00761670 | 21.00 | 0.00761670 | 47.2148 | 14542.89 | 0.00 | 18720.95 | 18720.95 | 0.93212131 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 36.30 | 20.06 | 0.00800000 | 57019.0 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3625.777 | -999.000 | 0.334027 | 0.00012950 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8718 | 1004.8586 | 1.1539 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.334027 | 0.38544165 | 4197.9300 | 999.8980 | 32.82090181 | 13.37 | 6.70 | 6.67 | 918991.59 | 0.3945 | 0.394531 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3625.78 | 3524.47 | 1.0000 | 0.38544165 | 0.334027 | 21.71 | 15.25 | 0.00862412 | 43729.0 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.12948873 | 6.70 | 13.37 | 6.67 | 0.000 | 3625.78 | 28.36 | 0.01272282 | 20.62 | 0.00000000 | 0.0000 | 21.11 | 0.00862412 | 21.11 | 0.00862412 | 53.0128 | 3269.22 | 0.00 | 3773.50 | 3595.15 | 0.38544165 | 21.71 | 15.67 | 0.00862412 | 43729.0 | 12.57 | 11.95 | 0.00844082 | 33938.9 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2900.057 | 2900.057 | 0.130464 | 0.00002537 | 82.869 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.334027 | 0.38544165 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 0.3755 | 0.383040 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2900.06 | 2900.06 | 1.0000 | 0.15054545 | 0.130464 | 21.11 | 14.12 | 0.00760539 | 40529.9 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.02536838 | 60.00 | 32.22 | 27.78 | 0.000 | 2900.06 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00760539 | 21.11 | 0.00760539 | 46.8306 | 2900.06 | 0.00 | 3126.25 | 3126.25 | 0.15054545 | 16.60 | 12.77 | 0.00760539 | 35935.6 | 36.98 | 19.98 | 0.00760539 | 56701.8 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3433.020 | -999.000 | 0.315682 | 0.00012262 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8846 | 1004.8586 | 1.1539 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.315682 | 0.36427301 | 4197.9300 | 999.8980 | 32.82090181 | 13.37 | 6.70 | 6.67 | 918991.59 | 0.3736 | 0.373557 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 3433.02 | 3331.93 | 1.0000 | 0.36427301 | 0.315682 | 21.71 | 15.25 | 0.00863101 | 43746.5 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.12260471 | 6.70 | 13.37 | 6.67 | 0.000 | 3433.02 | 27.95 | 0.01272209 | 20.50 | 0.00000000 | 0.0000 | 21.11 | 0.00863101 | 21.11 | 0.00863101 | 53.0546 | 3089.67 | 0.00 | 3572.76 | 3398.55 | 0.36427301 | 21.71 | 15.68 | 0.00863101 | 43746.5 | 12.57 | 11.95 | 0.00844155 | 33938.6 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2900.270 | 2900.270 | 0.130473 | 0.00002537 | 82.875 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.315682 | 0.36427301 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 0.3755 | 0.383068 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2900.27 | 2900.27 | 1.0000 | 0.15055648 | 0.130473 | 21.11 | 14.12 | 0.00760544 | 40530.1 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.02537024 | 60.00 | 32.22 | 27.78 | 0.000 | 2900.27 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00760544 | 21.11 | 0.00760544 | 46.8309 | 2900.27 | 0.00 | 3126.48 | 3126.48 | 0.15055648 | 16.60 | 12.77 | 0.00760544 | 35935.8 | 36.98 | 19.98 | 0.00760544 | 56701.9 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17768.230 | -999.000 | 1.617043 | 0.00063463 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9565 | 1004.8586 | 1.1539 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.617043 | 1.86594588 | 4197.9300 | 999.8980 | 32.82090181 | 13.37 | 6.70 | 6.67 | 918991.59 | 1.9334 | 1.933412 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 17768.23 | 17096.48 | 1.0000 | 1.86594588 | 1.617043 | 21.71 | 15.29 | 0.00866966 | 43844.6 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.63456342 | 6.70 | 13.37 | 6.67 | 0.000 | 17768.23 | 29.89 | 0.01272550 | 21.07 | 0.00000000 | 0.0000 | 21.11 | 0.00866966 | 21.11 | 0.00866966 | 53.2894 | 15826.22 | 0.00 | 18487.88 | 17432.51 | 1.86594588 | 21.71 | 15.71 | 0.00866966 | 43844.6 | 12.56 | 11.94 | 0.00844560 | 33936.5 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13843.393 | 13843.393 | 0.622782 | 0.00012111 | 395.572 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.617043 | 1.86594588 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 1.7924 | 1.828439 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 13843.39 | 13843.39 | 1.0000 | 0.71864394 | 0.622782 | 21.11 | 14.13 | 0.00761867 | 40564.1 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.12109568 | 60.00 | 32.22 | 27.78 | 0.000 | 13843.39 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00761867 | 21.11 | 0.00761867 | 46.9101 | 13843.39 | 0.00 | 14923.22 | 14923.22 | 0.71864394 | 16.60 | 12.78 | 0.00761867 | 35969.3 | 36.98 | 19.98 | 0.00761867 | 56735.1 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14986.452 | 14986.452 | 1.112276 | 0.00013111 | 342.291 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 1.9404 | 1.979414 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 14986.45 | 14986.45 | 1.0000 | 1.28348287 | 1.112276 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.13109465 | 60.00 | 32.22 | 27.78 | 0.000 | 14986.45 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00769615 | 21.00 | 0.00769615 | 47.7026 | 9362.88 | 0.00 | 15067.02 | 15067.02 | 1.28348287 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.11 | 17.40 | 0.00800000 | 48673.9 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15441.606 | 15441.606 | 1.166201 | 0.00013509 | 351.748 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 1.9993 | 2.039531 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 15441.61 | 15441.61 | 1.0000 | 1.34570860 | 1.166201 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.13507612 | 60.00 | 32.22 | 27.78 | 0.000 | 15441.61 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00770174 | 21.00 | 0.00770174 | 47.7368 | 9545.33 | 0.00 | 15524.70 | 15524.70 | 1.34570860 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.91 | 17.33 | 0.00800000 | 48471.2 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10411.672 | 10411.672 | 1.195642 | 0.00009109 | 225.584 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 1.3480 | 1.375176 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 10411.67 | 10411.67 | 1.0000 | 1.37968048 | 1.195642 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.09107655 | 60.00 | 32.22 | 27.78 | 0.000 | 10411.67 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.77 | 0.00720170 | 21.00 | 0.00720170 | 44.6795 | 4375.38 | 0.00 | 10469.46 | 10469.46 | 1.37968048 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.04 | 15.97 | 0.00800000 | 44523.1 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11888.555 | 11888.555 | 0.433667 | 0.00010401 | 324.460 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 1.5393 | 1.570243 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11888.55 | 11888.55 | 1.0000 | 0.50041875 | 0.433667 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.10399565 | 60.00 | 32.22 | 27.78 | 0.000 | 11888.55 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00774136 | 21.00 | 0.00774136 | 47.9786 | 9695.66 | 0.00 | 11947.51 | 11947.51 | 0.50041875 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60809.8 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 625639.925 | -999.000 | 23.206172 | 0.02234641 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.6519 | 1004.8586 | 1.1539 | VAV WITH REHEAT FAN | Fan:VariableVolume | 23.206172 | 26.77817906 | 4197.9300 | 999.8980 | 32.82090181 | 13.37 | 6.70 | 6.67 | 918991.59 | 68.0790 | 68.078961 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 625639.93 | 441092.57 | 1.0000 | 26.77817906 | 23.206172 | 27.06 | 19.12 | 0.01119553 | 55753.7 | 10.91 | 10.91 | 0.00850000 | 32389.9 | 22.34412896 | 6.70 | 13.37 | 6.67 | 51996.646 | 573643.28 | 30.10 | 0.01272586 | 21.13 | 11.66146000 | 50.2515 | 23.99 | 0.00964927 | 23.99 | 0.00961538 | 49.5358 | 305817.93 | 0.00 | 642246.78 | 435587.70 | 26.77817906 | 27.06 | 19.59 | 0.01119553 | 55753.7 | 11.20 | 11.06 | 0.00813519 | 31769.8 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 398780.758 | 398780.758 | 6.961852 | 0.00348871 | 5550.134 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | VAV WITH REHEAT FAN | Fan:VariableVolume | 23.206172 | 26.77817906 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 51.6320 | 52.671064 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 398780.76 | 398780.76 | 1.0000 | 8.03345372 | 6.961852 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 3.48835215 | 60.00 | 32.22 | 27.78 | 0.000 | 398780.76 | -32.70 | 0.00018338 | -32.70 | 11.66146000 | 167.5051 | 20.95 | 0.00761095 | 21.00 | 0.00758402 | 47.0158 | 97410.98 | 0.00 | 276279.94 | 276279.94 | 8.03345372 | 2.80 | -4.17 | 0.00018338 | 3273.1 | 37.01 | 13.61 | 0.00018338 | 37664.3 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 69550.086 | -999.000 | 2.051317 | 0.00248417 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.4967 | 1004.8586 | 1.1539 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.36698273 | 4197.9300 | 999.8980 | 32.82090181 | 13.37 | 6.70 | 6.67 | 918991.59 | 7.5681 | 7.568087 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 69550.09 | 44784.57 | 1.0000 | 2.36706595 | 2.051317 | 30.10 | 21.13 | 0.01272586 | 62784.4 | 11.90 | 11.35 | 0.00850000 | 33402.0 | 2.48391450 | 6.70 | 13.37 | 6.67 | 2195.006 | 67355.08 | 30.10 | 0.01272586 | 21.13 | 2.05124512 | 99.9965 | 21.11 | 0.00868081 | 21.11 | 0.00868219 | 53.3639 | 183957.63 | 0.00 | 71097.05 | 44995.87 | 2.36706595 | 30.10 | 21.63 | 0.01272586 | 62784.4 | 11.62 | 11.46 | 0.00835454 | 32748.4 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 35250.356 | 35250.356 | 0.615395 | 0.00030839 | 490.606 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.36698273 | 4197.9300 | 999.8980 | 6.62290049 | 54.44 | 82.22 | 27.78 | 772352.69 | 4.5640 | 4.655876 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 35250.36 | 35250.36 | 1.0000 | 0.71011979 | 0.615395 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 0.30835404 | 60.00 | 32.22 | 27.78 | 0.000 | 35250.36 | -32.70 | 0.00018338 | -32.70 | 2.05124512 | 333.3216 | 21.11 | 0.00755327 | 21.11 | 0.00755280 | 46.5074 | 165313.75 | 0.00 | 24421.86 | 24421.86 | 0.71011979 | 2.80 | -4.17 | 0.00018338 | 3273.1 | 37.01 | 13.61 | 0.00018338 | 37664.3 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 11.66 | 23.21 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 682.33 | 6883.33 | 250.00 |
RETAIL_1_FLR_1 | 3413.17 | 7566.50 | 2618.00 |
RETAIL_2_FLR_1 | 2099.67 | 7158.33 | 1356.50 |
MECH_FLR_1 | 2736.83 | 7858.00 | 2427.00 |
STORAGE_FLR_1 | 2882.00 | 8328.50 | 2798.00 |
LAUNDRY_FLR_1 | 6351.67 | 3718.33 | 2440.17 |
CAFE_FLR_1 | 3485.17 | 6346.67 | 1823.83 |
LOBBY_FLR_1 | 2555.00 | 6108.33 | 1065.00 |
ROOM_1_FLR_3 | 3887.50 | 8282.83 | 3718.67 |
ROOM_2_FLR_3 | 4205.67 | 8455.17 | 4110.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 3640.83 | 8760.00 | 3640.83 |
ROOM_5_FLR_3 | 3816.50 | 8201.67 | 3662.67 |
ROOM_6_FLR_3 | 4079.50 | 8340.50 | 4041.33 |
CORRIDOR_FLR_3 | 2776.33 | 7968.50 | 2549.00 |
ROOM_1_FLR_6 | 4346.83 | 8247.83 | 4128.83 |
ROOM_2_FLR_6 | 4599.17 | 8417.83 | 4472.33 |
ROOM_3_MULT9_FLR_6 | 3394.00 | 8199.83 | 3176.00 |
BANQUET_FLR_6 | 3684.83 | 4256.33 | 880.83 |
DINING_FLR_6 | 4062.83 | 3362.17 | 664.50 |
KITCHEN_FLR_6 | 7783.50 | 6330.83 | 5718.50 |
CORRIDOR_FLR_6 | 3139.83 | 7458.83 | 2446.67 |
Facility | 8759.50 | 8760.00 | 8039.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.67 | 0.00 | 0.67 | 0.00 |
RETAIL_1_FLR_1 | 25.67 | 0.00 | 25.67 | 0.00 |
RETAIL_2_FLR_1 | 1.67 | 0.00 | 1.67 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 5.83 | 142.33 | 5.83 | 142.33 |
CAFE_FLR_1 | 7.50 | 0.67 | 7.50 | 0.67 |
LOBBY_FLR_1 | 2.00 | 0.00 | 2.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 5.17 | 0.00 | 5.17 |
ROOM_2_FLR_3 | 0.00 | 2.00 | 0.00 | 2.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 7.67 | 2.67 | 7.67 | 2.67 |
ROOM_5_FLR_3 | 0.00 | 3.67 | 0.00 | 3.67 |
ROOM_6_FLR_3 | 0.00 | 4.50 | 0.00 | 4.50 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 8.50 | 0.00 | 8.50 |
ROOM_2_FLR_6 | 0.00 | 4.50 | 0.00 | 4.50 |
ROOM_3_MULT9_FLR_6 | 0.00 | 3.67 | 0.00 | 3.67 |
BANQUET_FLR_6 | 0.67 | 21.83 | 0.67 | 21.83 |
DINING_FLR_6 | 0.33 | 27.33 | 0.33 | 27.33 |
KITCHEN_FLR_6 | 1.17 | 225.83 | 1.17 | 225.83 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 34.67 | 283.33 | 34.67 | 283.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.937 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.983 | 0.142 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.371 | 0.047 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.594 | 0.053 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.496 | 0.053 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 21.644 | 0.153 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 4.179 | 0.112 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.730 | 0.046 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.472 | 0.184 | 0.000 | 0.041 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.472 | 0.184 | 0.000 | 0.039 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.536 | 0.082 | 0.000 | 0.062 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.472 | 0.184 | 0.000 | 0.041 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.472 | 0.184 | 0.000 | 0.039 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.575 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.472 | 0.184 | 0.000 | 0.048 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.472 | 0.184 | 0.000 | 0.046 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.537 | 0.150 | 0.000 | 0.076 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.425 | 0.053 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.776 | 0.053 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 20.423 | 0.153 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.097 | 0.037 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.545 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.691 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 0.785 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.342 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.286 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 11.094 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 2.455 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.051 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.515 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.454 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.331 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.516 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 2.568 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 2.748 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 8.402 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.629 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.79 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.56 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.09 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.25 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 38907004.35 | 0.00 | 38907004.35 | 0.00 | 38907004.35 | 26946214.98 | 30.52 | 4.40 | 8725.08 | 0.00 |
RETAIL_1_FLR_1 | 6858045.61 | 0.00 | 6858045.61 | 326761.06 | 7184806.68 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3639476.25 | 0.00 | 3639476.25 | 126130.18 | 3765606.44 | 2892943.94 | 218.90 | 82.12 | 8458.98 | 0.00 |
MECH_FLR_1 | 3343307.88 | 0.00 | 3343307.88 | 298096.82 | 3641404.71 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1610832.38 | 0.00 | 1610832.38 | 171985.45 | 1782817.83 | 1821682.01 | 8755.00 | 1.83 | 3.17 | 0.00 |
LAUNDRY_FLR_1 | 57633904.15 | 0.00 | 57633904.15 | 407035.98 | 58040940.13 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 26959329.42 | 0.00 | 26959329.42 | 722323.83 | 27681653.25 | 21330615.53 | 262.23 | 90.52 | 8407.25 | 0.00 |
LOBBY_FLR_1 | 77142822.89 | 0.00 | 77142822.89 | 2063844.16 | 79206667.06 | 59728886.00 | 117.20 | 59.18 | 8583.63 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 41652.98 | 1988528.60 | 189663.05 | 2178191.64 | 1946875.62 | 0.00 | 8086.33 | 673.67 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 40152.93 | 1986800.44 | 189648.58 | 2176449.02 | 1946647.51 | 0.00 | 8086.33 | 673.67 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 45676.00 | 26443563.28 | 52918.12 | 26496481.39 | 26397887.27 | 0.00 | 8103.17 | 656.83 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 39709.87 | 26444815.60 | 52932.59 | 26497748.18 | 26405105.73 | 0.00 | 8115.83 | 644.17 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 41768.96 | 1988644.58 | 189663.05 | 2178307.63 | 1946875.62 | 0.00 | 8086.33 | 673.67 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 40231.66 | 1986879.17 | 189648.58 | 2176527.75 | 1946647.51 | 0.00 | 8086.33 | 673.67 | 0.00 |
CORRIDOR_FLR_3 | 23553966.05 | 0.00 | 23553966.05 | 229340.78 | 23783306.83 | 14972100.18 | 14.87 | 3.71 | 8741.42 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 49064.61 | 535783.51 | 189704.08 | 725487.59 | 486718.90 | 0.00 | 8085.33 | 674.67 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 47093.32 | 533755.20 | 189689.61 | 723444.81 | 486661.88 | 0.00 | 8085.33 | 674.67 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 48992.34 | 3175912.75 | 97059.25 | 3272972.00 | 3126920.42 | 0.00 | 8085.33 | 674.67 | 0.00 |
BANQUET_FLR_6 | 38344235.49 | 0.00 | 38344235.49 | 463209.69 | 38807445.18 | 37458366.31 | 5258.29 | 237.73 | 3263.98 | 0.00 |
DINING_FLR_6 | 41376123.31 | 0.00 | 41376123.31 | 463209.69 | 41839333.00 | 37458366.31 | 3950.46 | 232.38 | 4577.17 | 0.00 |
KITCHEN_FLR_6 | 55110386.47 | 0.00 | 55110386.47 | 414680.06 | 55525066.54 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 11908498.51 | 0.00 | 11908498.51 | 405865.71 | 12314364.21 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.45E+10 | 7681641.53 | 0.45E+10 | 19112579.17 | 0.46E+10 | 0.43E+10 | 8755.00 | 8143.51 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.2337 | 0.0000 | 1.2337 | 0.0000 | 1.2337 | 0.8545 | 30.52 | 4.40 | 8725.08 |
RETAIL_1_FLR_1 | 0.2175 | 0.0000 | 0.2175 | 0.0104 | 0.2278 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1154 | 0.0000 | 0.1154 | 0.0040 | 0.1194 | 0.0917 | 218.90 | 82.12 | 8458.98 |
MECH_FLR_1 | 0.1060 | 0.0000 | 0.1060 | 0.0095 | 0.1155 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0511 | 0.0000 | 0.0511 | 0.0055 | 0.0565 | 0.0578 | 8755.00 | 1.83 | 3.17 |
LAUNDRY_FLR_1 | 1.8276 | 0.0000 | 1.8276 | 0.0129 | 1.8405 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.8549 | 0.0000 | 0.8549 | 0.0229 | 0.8778 | 0.6764 | 262.23 | 90.52 | 8407.25 |
LOBBY_FLR_1 | 2.4462 | 0.0000 | 2.4462 | 0.0654 | 2.5116 | 1.8940 | 117.20 | 59.18 | 8583.63 |
ROOM_1_FLR_3 | 0.0617 | 0.0013 | 0.0631 | 0.0060 | 0.0691 | 0.0617 | 0.00 | 8086.33 | 673.67 |
ROOM_2_FLR_3 | 0.0617 | 0.0013 | 0.0630 | 0.0060 | 0.0690 | 0.0617 | 0.00 | 8086.33 | 673.67 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0013 | 0.8386 | 0.0017 | 0.8402 | 0.8373 | 0.00 | 8115.83 | 644.17 |
ROOM_5_FLR_3 | 0.0617 | 0.0013 | 0.0631 | 0.0060 | 0.0691 | 0.0617 | 0.00 | 8086.33 | 673.67 |
ROOM_6_FLR_3 | 0.0617 | 0.0013 | 0.0630 | 0.0060 | 0.0690 | 0.0617 | 0.00 | 8086.33 | 673.67 |
CORRIDOR_FLR_3 | 0.7469 | 0.0000 | 0.7469 | 0.0073 | 0.7542 | 0.4748 | 14.87 | 3.71 | 8741.42 |
ROOM_1_FLR_6 | 0.0154 | 0.0016 | 0.0170 | 0.0060 | 0.0230 | 0.0154 | 0.00 | 8085.33 | 674.67 |
ROOM_2_FLR_6 | 0.0154 | 0.0015 | 0.0169 | 0.0060 | 0.0229 | 0.0154 | 0.00 | 8085.33 | 674.67 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0016 | 0.1007 | 0.0031 | 0.1038 | 0.0992 | 0.00 | 8085.33 | 674.67 |
BANQUET_FLR_6 | 1.2159 | 0.0000 | 1.2159 | 0.0147 | 1.2306 | 1.1878 | 5258.29 | 237.73 | 3263.98 |
DINING_FLR_6 | 1.3120 | 0.0000 | 1.3120 | 0.0147 | 1.3267 | 1.1878 | 3950.46 | 232.38 | 4577.17 |
KITCHEN_FLR_6 | 1.7475 | 0.0000 | 1.7475 | 0.0131 | 1.7607 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3776 | 0.0000 | 0.3776 | 0.0129 | 0.3905 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 80.0387 | 0.1335 | 80.1722 | 0.4785 | 80.6508 | 73.9670 | 8755.00 | 8143.51 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.51E+09 | 0.00 | 0.51E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 86137942.48 | 394342.67 | 86532285.16 | 64690340.46 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 16.3122 | 0.0000 | 16.3122 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 2.7314 | 0.0125 | 2.7439 | 2.0513 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 6262.44 | 2497.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 15.5288 | 18.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 2.7314 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1318 |
Defaulted Fields | 1181 |
Fields with Defaults | 4005 |
Autosized Fields | 350 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5035.52 | 76119.85 | 31-OCT-02:40 | 423260.36 | 29-JUN-18:10 |
Electricity:Building | 2518.23 | 32537.67 | 27-MAY-05:00 | 151906.32 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 323.72 | 3705.45 | 02-JAN-02:10 | 24299.15 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2511.14 | 32396.52 | 27-MAY-05:00 | 151664.99 | 02-JAN-20:10 |
InteriorLights:Electricity | 766.12 | 6704.72 | 27-MAY-05:00 | 62892.57 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 173.46 | 1576.23 | 02-JAN-02:10 | 14185.34 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 766.12 | 6704.72 | 27-MAY-05:00 | 62892.57 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 766.12 | 6704.72 | 27-MAY-05:00 | 62892.57 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 173.46 | 1576.23 | 02-JAN-02:10 | 14185.34 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 766.12 | 6704.72 | 27-MAY-05:00 | 62892.57 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.80 | 222.61 | 02-JAN-02:10 | 1390.02 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.61 | 78.27 | 02-JAN-02:10 | 704.41 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.61 | 78.27 | 02-JAN-02:10 | 704.41 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.77 | 257.78 | 02-JAN-02:10 | 1609.65 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.97 | 90.64 | 02-JAN-02:10 | 815.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.97 | 90.64 | 02-JAN-02:10 | 815.72 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 29.11 | 327.88 | 02-JAN-02:10 | 2199.84 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 16.64 | 151.16 | 02-JAN-02:10 | 1360.40 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 16.64 | 151.16 | 02-JAN-02:10 | 1360.40 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.38 | 76.28 | 02-JAN-02:10 | 469.87 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.78 | 25.30 | 02-JAN-02:10 | 227.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.78 | 25.30 | 02-JAN-02:10 | 227.72 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.30 | 1002.39 | 02-JAN-02:10 | 4930.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.37 | 39.69 | 02-JAN-02:10 | 357.21 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.37 | 39.69 | 02-JAN-02:10 | 357.21 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 32.16 | 322.63 | 27-MAY-05:00 | 2727.18 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 17.82 | 119.42 | 27-MAY-05:00 | 1761.91 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 17.82 | 119.42 | 27-MAY-05:00 | 1761.91 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 270.76 | 3198.76 | 27-MAY-05:00 | 20294.39 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 121.76 | 1087.35 | 27-MAY-05:00 | 10265.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 121.76 | 1087.35 | 27-MAY-05:00 | 10265.18 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 18.66 | 264.62 | 01-JAN-02:10 | 1227.54 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 18.66 | 264.59 | 01-JAN-02:10 | 1227.39 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 304.77 | 4565.05 | 01-JAN-02:10 | 20923.25 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 76.02 | 643.59 | 01-JAN-02:10 | 5851.22 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 76.02 | 643.59 | 01-JAN-02:10 | 5851.22 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 304.86 | 4566.30 | 01-JAN-02:10 | 20928.98 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 76.04 | 643.77 | 01-JAN-02:10 | 5852.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 76.04 | 643.77 | 01-JAN-02:10 | 5852.82 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 18.66 | 264.62 | 01-JAN-02:10 | 1227.54 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 18.66 | 264.59 | 01-JAN-02:10 | 1227.39 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.66 | 66.15 | 01-JAN-02:10 | 306.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.50 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.50 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.66 | 66.15 | 01-JAN-02:10 | 306.85 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.49 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.49 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.10 | 540.75 | 01-JAN-02:10 | 2478.43 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 9.00 | 76.24 | 01-JAN-02:10 | 693.10 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 9.00 | 76.24 | 01-JAN-02:10 | 693.10 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 210.39 | 2524.33 | 27-MAY-05:00 | 9841.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 34.53 | 275.03 | 27-MAY-05:00 | 3094.06 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 34.53 | 275.03 | 27-MAY-05:00 | 3094.06 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 210.39 | 2524.33 | 27-MAY-05:00 | 9841.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 34.53 | 275.03 | 27-MAY-05:00 | 3094.06 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 34.53 | 275.03 | 27-MAY-05:00 | 3094.06 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 454.16 | 6253.02 | 02-JAN-02:10 | 18944.06 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.33 | 121.09 | 02-JAN-02:10 | 1089.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.33 | 121.09 | 02-JAN-02:10 | 1089.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1745.01 | 25691.80 | 02-JAN-02:10 | 89475.41 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1745.01 | 25691.80 | 02-JAN-02:10 | 89475.41 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.37 | 1026.99 | 10-DEC-23:30 | 3493.09 | 20-OCT-07:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 838.69 | 2596.31 | 19-APR-02:30 | 217473.80 | 29-JUN-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.35 | 0.00 | 01-JAN-11:10 | 2068.90 | 20-OCT-07:20 |
MedTempRefrigeration:Refrigeration:Electricity | 33.93 | 816.31 | 06-JAN-04:10 | 1245.48 | 03-OCT-07:50 |
Fans:Electricity | 556.64 | 12451.64 | 26-SEP-02:30 | 46536.39 | 23-SEP-21:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 817.38 | 14276.70 | 04-SEP-04:10 | 53473.99 | 23-SEP-21:20 |
ExteriorEquipment:Electricity | 651.48 | 9618.58 | 02-JAN-02:20 | 39726.11 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 32.45 | 553.72 | 03-JUN-05:00 | 1868.65 | 20-APR-20:10 |
ElectricityPurchased:Facility | 5035.52 | 76119.85 | 31-OCT-02:40 | 423260.36 | 29-JUN-18:10 |
ElectricityPurchased:Plant | 5035.52 | 76119.85 | 31-OCT-02:40 | 423260.36 | 29-JUN-18:10 |
Cogeneration:ElectricityPurchased | 5035.52 | 76119.85 | 31-OCT-02:40 | 423260.36 | 29-JUN-18:10 |
General:Cogeneration:ElectricityPurchased | 5035.52 | 76119.85 | 31-OCT-02:40 | 423260.36 | 29-JUN-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5035.52 | 76119.85 | 31-OCT-02:40 | 423260.36 | 29-JUN-18:10 |
ElectricityNet:Plant | 5035.52 | 76119.85 | 31-OCT-02:40 | 423260.36 | 29-JUN-18:10 |
Cogeneration:ElectricityNet | 5035.52 | 76119.85 | 31-OCT-02:40 | 423260.36 | 29-JUN-18:10 |
General:Cogeneration:ElectricityNet | 5035.52 | 76119.85 | 31-OCT-02:40 | 423260.36 | 29-JUN-18:10 |
General:Fans:Electricity | 556.64 | 12451.64 | 26-SEP-02:30 | 46536.39 | 23-SEP-21:20 |
ExteriorLights:Electricity | 242.19 | 0.00 | 01-JAN-08:20 | 15448.40 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 242.19 | 0.00 | 01-JAN-08:20 | 15448.40 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 228.29 | 0.00 | 11-APR-11:50 | 9938.94 | 04-FEB-13:30 |
General:HeatRecovery:Electricity | 228.29 | 0.00 | 11-APR-11:50 | 9938.94 | 04-FEB-13:30 |
WaterSystems:Electricity | 90.75 | 1086.56 | 30-JUN-00:40 | 4740.07 | 14-DEC-07:10 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.56 | 30-JUN-00:40 | 4740.07 | 14-DEC-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 593.01 | 0.00 | 01-JAN-00:10 | 203641.74 | 29-JUN-18:10 |
General:Cooling:Electricity | 593.01 | 0.00 | 01-JAN-00:10 | 203641.74 | 29-JUN-18:10 |
Pumps:Electricity | 100.65 | 47.91 | 09-MAY-12:20 | 7224.92 | 21-JUL-19:30 |
General:Pumps:Electricity | 100.65 | 47.91 | 09-MAY-12:20 | 7224.92 | 21-JUL-19:30 |
WIRED_LTG_ELECTRICITY | 26.97 | 0.00 | 01-JAN-00:10 | 2213.82 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 8448.51 | 29270.80 | 05-MAY-01:10 | 1324353.49 | 04-JAN-18:00 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 6659.67 | 15908.90 | 12-APR-10:10 | 1283042.62 | 05-JAN-24:00 |
WaterSystems:NaturalGas | 3482.41 | 15908.90 | 01-JAN-16:10 | 311602.87 | 23-FEB-21:40 |
Water Heater:WaterSystems:NaturalGas | 3482.41 | 15908.90 | 01-JAN-16:10 | 311602.87 | 23-FEB-21:40 |
Heating:NaturalGas | 3177.27 | 0.00 | 10-APR-18:50 | 1101672.72 | 06-JAN-04:50 |
Boiler:Heating:NaturalGas | 3177.27 | 0.00 | 10-APR-18:50 | 1101672.72 | 06-JAN-04:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 1865.55 | 0.00 | 01-JAN-00:10 | 666260.07 | 21-JUL-19:30 |
PlantLoopCoolingDemand:HVAC | 1865.55 | 0.00 | 01-JAN-00:10 | 666260.07 | 21-JUL-19:30 |
CoolingCoils:PlantLoopCoolingDemand | 1865.55 | 0.00 | 01-JAN-00:10 | 666260.07 | 21-JUL-19:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-JAN-22:00 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-JAN-22:00 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-JAN-22:00 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 14-APR-01:00 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-JAN-22:00 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-JAN-22:00 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-JAN-22:00 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 14-APR-01:00 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 06-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 06-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 22678.94 | 146259.73 | 21-NOV-13:50 | 2758665.03 | 29-JUN-18:10 |
EnergyTransfer:Building | 5122.47 | 62991.43 | 03-OCT-07:40 | 365925.04 | 30-JUN-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 696.29 | 8498.33 | 23-SEP-01:10 | 37125.10 | 29-JUL-10:50 |
Refrigeration:EnergyTransfer | 180.44 | 3270.09 | 06-JAN-04:00 | 10745.76 | 20-OCT-07:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.22 | 1635.05 | 06-JAN-04:00 | 5372.88 | 20-OCT-07:20 |
General:Refrigeration:EnergyTransfer | 90.22 | 1635.05 | 06-JAN-04:00 | 5372.88 | 20-OCT-07:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.22 | 1635.05 | 06-JAN-04:00 | 5372.88 | 20-OCT-07:20 |
EnergyTransfer:Plant | 7921.89 | 20030.50 | 24-SEP-03:00 | 1541222.62 | 29-JUN-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.53 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.69 | 1398.92 | 06-JAN-04:10 | 2686.44 | 03-OCT-07:50 |
EnergyTransfer:Zone:BASEMENT | 391.15 | 1486.82 | 22-MAY-03:10 | 27506.39 | 23-OCT-19:40 |
Heating:EnergyTransfer | 523.31 | 0.00 | 08-FEB-11:20 | 134392.97 | 09-JAN-05:00 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.05 | 0.00 | 01-JAN-00:10 | 923.81 | 23-APR-00:20 |
General:Heating:EnergyTransfer | 523.31 | 0.00 | 08-FEB-11:20 | 134392.97 | 09-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.05 | 0.00 | 01-JAN-00:10 | 923.81 | 23-APR-00:20 |
Cooling:EnergyTransfer | 4508.94 | 48250.20 | 25-DEC-15:00 | 363224.83 | 30-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 391.09 | 1486.82 | 22-MAY-03:10 | 27506.39 | 23-OCT-19:40 |
General:Cooling:EnergyTransfer | 4508.94 | 48250.20 | 25-DEC-15:00 | 363224.83 | 30-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 391.09 | 1486.82 | 22-MAY-03:10 | 27506.39 | 23-OCT-19:40 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 41.91 | 0.00 | 05-FEB-06:50 | 5166.54 | 22-OCT-12:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 6.38 | 0.00 | 01-JAN-09:30 | 2213.10 | 26-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 6.38 | 0.00 | 01-JAN-09:30 | 2213.10 | 26-DEC-08:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 35.52 | 0.00 | 01-JAN-00:10 | 5166.54 | 22-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 35.52 | 0.00 | 01-JAN-00:10 | 5166.54 | 22-OCT-12:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.39 | 1.94 | 05-JAN-10:10 | 2242.50 | 30-JUN-20:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 179.75 | 06-JAN-10:30 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 179.75 | 06-JAN-10:30 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.39 | 0.00 | 04-JAN-10:10 | 2242.50 | 30-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.39 | 0.00 | 04-JAN-10:10 | 2242.50 | 30-JUN-20:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 23.95 | 0.03 | 17-DEC-18:50 | 2140.59 | 30-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 3.52 | 0.00 | 02-JAN-20:10 | 1443.01 | 06-JAN-03:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 3.52 | 0.00 | 02-JAN-20:10 | 1443.01 | 06-JAN-03:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 20.43 | 0.00 | 01-JAN-00:10 | 2140.59 | 30-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 20.43 | 0.00 | 01-JAN-00:10 | 2140.59 | 30-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 12.64 | 0.02 | 07-NOV-19:00 | 1109.50 | 06-JAN-11:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 3.98 | 0.00 | 18-JAN-21:00 | 1109.50 | 06-JAN-11:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 3.98 | 0.00 | 18-JAN-21:00 | 1109.50 | 06-JAN-11:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 8.66 | 0.00 | 01-JAN-00:10 | 823.00 | 30-JUN-19:20 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 8.66 | 0.00 | 01-JAN-00:10 | 823.00 | 30-JUN-19:20 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 578.39 | 6912.78 | 22-MAY-03:10 | 39329.11 | 23-OCT-19:40 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 611.69 | 28-SEP-03:40 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 611.69 | 28-SEP-03:40 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 578.37 | 6912.78 | 22-MAY-03:10 | 39329.11 | 23-OCT-19:40 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 578.37 | 6912.78 | 22-MAY-03:10 | 39329.11 | 23-OCT-19:40 |
EnergyTransfer:Zone:CAFE_FLR_1 | 218.28 | 1.80 | 18-DEC-13:40 | 18244.02 | 22-OCT-12:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.24 | 0.00 | 01-JAN-00:10 | 1835.34 | 23-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.24 | 0.00 | 01-JAN-00:10 | 1835.34 | 23-JAN-09:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 218.04 | 0.00 | 04-JAN-07:10 | 18244.02 | 22-OCT-12:00 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 218.04 | 0.00 | 04-JAN-07:10 | 18244.02 | 22-OCT-12:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 712.46 | 990.74 | 25-DEC-15:50 | 42550.23 | 29-JUN-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.02 | 0.00 | 01-JAN-00:10 | 1689.66 | 31-OCT-08:30 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.02 | 0.00 | 01-JAN-00:10 | 1689.66 | 31-OCT-08:30 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 712.44 | 990.74 | 25-DEC-15:50 | 42550.23 | 29-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 712.44 | 990.74 | 25-DEC-15:50 | 42550.23 | 29-JUN-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 82.72 | 0.02 | 05-NOV-12:50 | 13791.85 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 39.83 | 0.00 | 01-JAN-11:10 | 8607.20 | 06-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 39.83 | 0.00 | 01-JAN-11:10 | 8607.20 | 06-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 42.89 | 0.00 | 01-JAN-00:10 | 13791.85 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 42.89 | 0.00 | 01-JAN-00:10 | 13791.85 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 83.02 | 0.07 | 08-MAY-22:30 | 13370.89 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 47.54 | 0.00 | 16-JAN-08:10 | 10229.34 | 06-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 47.54 | 0.00 | 16-JAN-08:10 | 10229.34 | 06-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 35.48 | 0.00 | 01-JAN-00:10 | 13370.89 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 35.48 | 0.00 | 01-JAN-00:10 | 13370.89 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 390.39 | 3.55 | 30-JAN-14:20 | 73071.82 | 22-OCT-12:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 71.93 | 0.00 | 01-JAN-08:50 | 35067.45 | 09-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 71.93 | 0.00 | 01-JAN-08:50 | 35067.45 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 318.46 | 0.00 | 01-JAN-00:10 | 73071.82 | 22-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 318.46 | 0.00 | 01-JAN-00:10 | 73071.82 | 22-OCT-12:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 448.82 | 0.46 | 28-MAR-09:30 | 65989.09 | 30-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 167.93 | 0.00 | 01-JAN-08:10 | 64523.85 | 06-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 167.93 | 0.00 | 01-JAN-08:10 | 64523.85 | 06-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 280.89 | 0.00 | 01-JAN-00:10 | 65989.09 | 30-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 280.89 | 0.00 | 01-JAN-00:10 | 65989.09 | 30-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 82.31 | 0.04 | 09-OCT-20:20 | 11903.85 | 29-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 39.71 | 0.00 | 01-JAN-11:10 | 8670.43 | 04-JAN-19:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 39.71 | 0.00 | 01-JAN-11:10 | 8670.43 | 04-JAN-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 42.60 | 0.00 | 01-JAN-00:10 | 11903.85 | 29-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 42.60 | 0.00 | 01-JAN-00:10 | 11903.85 | 29-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 82.43 | 0.27 | 19-APR-01:40 | 11456.23 | 29-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 47.50 | 0.00 | 02-JAN-11:10 | 10002.92 | 05-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 47.50 | 0.00 | 02-JAN-11:10 | 10002.92 | 05-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 34.93 | 0.00 | 01-JAN-00:10 | 11456.23 | 29-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 34.93 | 0.00 | 01-JAN-00:10 | 11456.23 | 29-JUL-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 158.69 | 0.53 | 07-MAR-03:20 | 14410.48 | 30-JUN-19:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 8.53 | 0.00 | 01-JAN-10:10 | 5784.00 | 05-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 8.53 | 0.00 | 01-JAN-10:10 | 5784.00 | 05-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 150.16 | 0.00 | 01-JAN-00:10 | 14410.48 | 30-JUN-19:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 150.16 | 0.00 | 01-JAN-00:10 | 14410.48 | 30-JUN-19:10 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 24.37 | 0.04 | 10-JUN-02:20 | 3624.35 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 14.16 | 0.00 | 01-JAN-14:50 | 2815.02 | 06-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 14.16 | 0.00 | 01-JAN-14:50 | 2815.02 | 06-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.20 | 0.00 | 01-JAN-00:10 | 3624.35 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.20 | 0.00 | 01-JAN-00:10 | 3624.35 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 24.88 | 0.02 | 22-OCT-09:40 | 3485.27 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 16.56 | 0.00 | 16-JAN-08:10 | 3201.91 | 06-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 16.56 | 0.00 | 16-JAN-08:10 | 3201.91 | 06-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 8.31 | 0.00 | 01-JAN-00:10 | 3485.27 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 8.31 | 0.00 | 01-JAN-00:10 | 3485.27 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 109.40 | 0.27 | 10-OCT-00:20 | 17898.30 | 25-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 42.71 | 0.00 | 01-JAN-10:20 | 10941.32 | 13-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 42.71 | 0.00 | 01-JAN-10:20 | 10941.32 | 13-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 66.69 | 0.00 | 01-JAN-00:10 | 17898.30 | 25-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 66.69 | 0.00 | 01-JAN-00:10 | 17898.30 | 25-AUG-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 403.91 | 3036.90 | 06-JAN-10:20 | 24901.88 | 16-APR-21:30 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 22.65 | 16-OCT-09:00 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 22.65 | 16-OCT-09:00 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 403.91 | 3036.90 | 06-JAN-10:20 | 24901.88 | 16-APR-21:30 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 403.91 | 3036.90 | 06-JAN-10:20 | 24901.88 | 16-APR-21:30 |
EnergyTransfer:Zone:DINING_FLR_6 | 443.10 | 4050.64 | 06-JAN-10:10 | 26428.25 | 16-APR-21:30 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 443.10 | 4050.64 | 06-JAN-10:10 | 26428.25 | 16-APR-21:30 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 443.10 | 4050.64 | 06-JAN-10:10 | 26428.25 | 16-APR-21:30 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 58.47 | 22-OCT-23:40 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 58.47 | 22-OCT-23:40 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 606.07 | 6111.32 | 23-SEP-01:10 | 32060.98 | 29-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 606.07 | 6111.32 | 23-SEP-01:10 | 32060.98 | 29-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 82.98 | 0.08 | 16-DEC-14:10 | 7141.81 | 30-JUN-13:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 12.69 | 0.00 | 02-JAN-11:50 | 5434.06 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 12.69 | 0.00 | 02-JAN-11:50 | 5434.06 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 70.29 | 0.00 | 01-JAN-00:10 | 7141.81 | 30-JUN-13:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 70.29 | 0.00 | 01-JAN-00:10 | 7141.81 | 30-JUN-13:20 |
PlantLoopHeatingDemand:Facility | 3373.18 | 10713.05 | 30-AUG-01:20 | 960356.87 | 06-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 900.58 | 10713.05 | 30-AUG-01:20 | 66774.53 | 24-FEB-08:00 |
WaterSystems:PlantLoopHeatingDemand | 900.58 | 10713.05 | 30-AUG-01:20 | 66774.53 | 24-FEB-08:00 |
General:WaterSystems:PlantLoopHeatingDemand | 900.58 | 10713.05 | 30-AUG-01:20 | 66774.53 | 24-FEB-08:00 |
EnergyTransfer:HVAC | 9634.58 | 209.02 | 17-AUG-07:40 | 906645.19 | 06-JAN-09:10 |
HeatingCoils:EnergyTransfer | 2472.59 | 0.00 | 10-APR-18:50 | 906645.19 | 06-JAN-09:10 |
PlantLoopHeatingDemand:HVAC | 2472.59 | 0.00 | 10-APR-18:50 | 906645.19 | 06-JAN-09:10 |
HeatingCoils:PlantLoopHeatingDemand | 2472.59 | 0.00 | 10-APR-18:50 | 906645.19 | 06-JAN-09:10 |
CoolingCoils:EnergyTransfer | 1865.55 | 0.00 | 01-JAN-00:10 | 666260.07 | 21-JUL-19:30 |
HeatRecoveryForHeating:EnergyTransfer | 5168.83 | 0.00 | 01-JAN-00:40 | 587049.15 | 24-FEB-06:20 |
HeatRecoveryForCooling:EnergyTransfer | 127.60 | 0.00 | 01-JAN-00:10 | 252023.00 | 15-JUL-14:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 900.58 | 10713.05 | 30-AUG-01:20 | 66774.53 | 24-FEB-08:00 |
WaterUse:WaterSystems:EnergyTransfer | 900.58 | 10713.05 | 30-AUG-01:20 | 66774.53 | 24-FEB-08:00 |
Boilers:EnergyTransfer | 2450.88 | 0.00 | 10-APR-18:50 | 898334.36 | 06-JAN-04:50 |
Chillers:EnergyTransfer | 1943.60 | 0.00 | 01-JAN-00:10 | 670607.75 | 21-JUL-19:30 |
HeatRejection:EnergyTransfer | 2536.61 | 0.00 | 01-JAN-00:10 | 852368.93 | 29-JUN-18:10 |
General:HeatRejection:EnergyTransfer | 2536.61 | 0.00 | 01-JAN-00:10 | 852368.93 | 29-JUN-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.055 | -391.093 | 0.000 | 0.000 | 141.725 | 173.462 | 150.255 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -74.404 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 6.384 | -35.521 | 0.000 | 0.000 | 15.765 | 8.614 | 10.186 | 29.044 | 0.000 | 0.055 | 0.000 | 0.000 | -13.399 | 0.000 | -7.327 | -13.800 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.008 | -30.386 | 0.000 | 0.000 | 17.259 | 9.975 | 11.795 | 0.000 | 0.000 | 0.021 | 0.000 | 0.000 | 0.000 | 0.000 | -2.938 | -5.733 |
MECH_FLR_1 | 0.000 | 0.000 | 3.520 | -20.426 | 0.000 | 0.000 | 3.755 | 16.635 | 12.471 | 0.000 | 0.000 | 0.052 | 0.000 | 0.000 | 0.000 | 0.000 | -6.801 | -9.206 |
STORAGE_FLR_1 | 0.000 | 0.000 | 3.975 | -8.665 | 0.000 | 0.000 | 2.914 | 2.785 | 3.598 | 0.000 | 0.000 | 0.031 | 0.000 | 0.000 | 0.000 | 0.000 | -3.897 | -0.741 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.014 | -578.373 | 0.000 | 0.000 | 11.277 | 4.368 | 658.131 | 0.000 | 0.000 | 0.077 | 0.000 | 0.000 | 0.000 | 0.000 | -9.794 | -85.700 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.236 | -218.046 | 0.000 | 0.000 | 197.254 | 17.817 | 14.341 | 80.971 | 0.000 | 0.111 | 0.000 | 0.000 | -38.667 | 0.000 | -16.762 | -37.254 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.020 | -712.449 | 0.000 | 0.000 | 567.376 | 121.762 | 148.998 | 106.428 | 0.000 | 0.317 | 0.000 | 0.000 | -52.518 | 0.000 | -48.958 | -130.976 |
ROOM_1_FLR_3 | 46.917 | -34.178 | 0.000 | -15.793 | 0.000 | 0.000 | 9.772 | 6.366 | 12.292 | 52.940 | 0.000 | 0.243 | 0.000 | 0.000 | -31.129 | 0.000 | -17.195 | -30.235 |
ROOM_2_FLR_3 | 55.126 | -27.522 | 0.000 | -15.545 | 0.000 | 0.000 | 9.795 | 6.366 | 12.291 | 36.575 | 0.000 | 0.240 | 0.000 | 0.000 | -32.858 | 0.000 | -17.090 | -27.377 |
ROOM_3_MULT19_FLR_3 | 117.280 | -139.495 | 0.000 | -224.311 | 0.000 | 0.000 | 0.000 | 76.021 | 228.754 | 348.579 | 0.000 | 0.736 | 0.023 | 0.000 | -166.242 | 0.000 | -105.904 | -135.417 |
ROOM_4_MULT19_FLR_3 | 252.523 | -154.984 | 0.000 | -210.490 | 0.000 | 0.000 | 186.168 | 76.042 | 228.817 | 92.017 | 0.000 | 2.136 | 0.000 | 0.000 | -185.504 | 0.000 | -96.391 | -190.333 |
ROOM_5_FLR_3 | 46.768 | -33.802 | 0.000 | -15.857 | 0.000 | 0.000 | 9.767 | 6.366 | 12.292 | 52.467 | 0.000 | 0.244 | 0.000 | 0.000 | -30.611 | 0.000 | -17.230 | -30.404 |
ROOM_6_FLR_3 | 55.074 | -26.864 | 0.000 | -15.645 | 0.000 | 0.000 | 9.787 | 6.366 | 12.291 | 35.832 | 0.000 | 0.241 | 0.000 | 0.000 | -32.098 | 0.000 | -17.134 | -27.848 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 8.529 | -150.160 | 0.000 | 0.000 | 118.539 | 109.603 | 0.000 | 47.820 | 0.000 | 0.141 | 0.000 | 0.000 | -39.961 | 0.000 | -20.998 | -73.513 |
ROOM_1_FLR_6 | 16.093 | -8.213 | 0.000 | -3.917 | 0.000 | 0.000 | 2.446 | 1.592 | 3.073 | 13.206 | 0.000 | 0.062 | 0.000 | 0.000 | -7.742 | 0.000 | -4.317 | -12.282 |
ROOM_2_FLR_6 | 18.605 | -6.497 | 0.000 | -3.861 | 0.000 | 0.000 | 2.451 | 1.591 | 3.073 | 9.132 | 0.000 | 0.061 | 0.000 | 0.000 | -8.173 | 0.000 | -4.293 | -12.092 |
ROOM_3_MULT9_FLR_6 | 53.018 | -51.109 | 0.000 | -25.882 | 0.000 | 0.000 | 21.922 | 9.005 | 27.097 | 75.404 | 0.000 | 0.360 | 0.000 | 0.000 | -35.797 | 0.000 | -20.671 | -53.347 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -403.912 | 0.000 | 0.000 | 321.454 | 34.531 | 175.857 | 9.590 | 0.000 | 0.060 | 0.000 | 0.000 | -23.408 | 0.000 | -11.432 | -102.740 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -443.101 | 0.000 | 0.000 | 319.753 | 34.531 | 175.857 | 9.425 | 0.000 | 0.060 | 0.000 | 0.000 | -23.880 | 0.000 | -11.501 | -61.143 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -606.057 | 0.000 | 0.000 | 28.599 | 13.327 | 550.372 | 25.600 | 0.000 | 0.053 | 12.877 | 0.000 | -14.401 | 0.000 | -10.370 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 12.685 | -70.293 | 0.000 | 0.000 | 31.554 | 28.999 | 0.000 | 23.849 | 0.000 | 0.055 | 0.133 | 0.000 | -17.704 | 0.000 | -9.279 | -0.001 |
Total Facility | 661.404 | -482.664 | 35.426 | -4199.785 | 0.000 | 0.000 | 2029.330 | 766.124 | 2451.839 | 1048.878 | 0.000 | 5.356 | 13.033 | 0.000 | -754.093 | 0.000 | -460.283 | -1114.545 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 14-SEP-06:29 | 0.00 | 0.00 | 0.00 | -36305.17 | 0.00 | 0.00 | 2970.17 | 7880.79 | 6387.66 | 0.00 | 0.00 | 0.00 | 19066.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 19-APR-13:16 | 0.00 | 0.00 | 0.00 | -6196.79 | 0.00 | 0.00 | 149.35 | 195.67 | 252.59 | 6031.63 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -212.82 | -219.63 |
RETAIL_2_FLR_1 | 20-OCT-21:55 | 0.00 | 0.00 | 0.00 | -3259.40 | 0.00 | 0.00 | 790.25 | 543.81 | 585.00 | 0.00 | 0.00 | 0.00 | 1423.35 | 0.00 | -0.00 | 0.00 | -83.01 | 0.00 |
MECH_FLR_1 | 30-JUN-20:00 | 0.00 | 0.00 | 0.00 | -2140.56 | 0.00 | 0.00 | 129.08 | 1360.40 | 839.45 | 0.00 | 0.00 | 4.06 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -192.42 |
STORAGE_FLR_1 | 15-SEP-00:35 | 0.00 | 0.00 | 0.00 | -1013.31 | 0.00 | 0.00 | 139.66 | 37.96 | 63.73 | 0.00 | 0.00 | 0.00 | 876.49 | 0.00 | -0.00 | 0.00 | -104.52 | 0.00 |
LAUNDRY_FLR_1 | 19-APR-19:09 | 0.00 | 0.00 | 0.00 | -52327.45 | 0.00 | 0.00 | 402.86 | 357.21 | 44299.38 | 0.00 | 0.00 | 0.00 | 7582.55 | 0.00 | -0.00 | 0.00 | -314.56 | 0.00 |
CAFE_FLR_1 | 09-OCT-11:43 | 0.00 | 0.00 | 0.00 | -24384.10 | 0.00 | 0.00 | 2968.73 | 358.25 | 406.43 | 21158.66 | 0.00 | 0.00 | 29.22 | 0.00 | -0.00 | 0.00 | -537.18 | 0.00 |
LOBBY_FLR_1 | 21-NOV-01:33 | 0.00 | 0.00 | 0.00 | -78833.00 | 0.00 | 0.00 | 26797.89 | 1710.86 | 2639.27 | 0.00 | 0.00 | 0.00 | 50705.01 | 0.00 | -1938.06 | 0.00 | -1081.96 | 0.00 |
ROOM_1_FLR_3 | 30-JUN-18:02 | 0.00 | -14488.16 | 0.00 | -726.78 | 0.00 | 0.00 | 335.47 | 436.12 | 516.26 | 10811.52 | 0.00 | 173.57 | 2942.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 30-JUN-18:02 | 0.00 | -13815.81 | 0.00 | -730.45 | 0.00 | 0.00 | 335.48 | 436.07 | 516.20 | 11623.65 | 0.00 | 172.23 | 1462.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 22-OCT-12:30 | 0.00 | -64394.56 | 0.00 | -8677.95 | 0.00 | 0.00 | 0.00 | 1930.94 | 5686.12 | 102108.29 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -831.11 | -35821.73 |
ROOM_4_MULT19_FLR_3 | 17-JUN-18:02 | 0.00 | -65623.39 | 0.00 | -9733.21 | 0.00 | 0.00 | 5419.61 | 5852.82 | 9610.21 | 18820.04 | 0.00 | 845.53 | 34808.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 17-JUN-18:02 | 0.00 | -12737.03 | 0.00 | -692.80 | 0.00 | 0.00 | 283.21 | 490.02 | 516.26 | 1028.72 | 0.00 | 104.62 | 11007.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 29-JUN-15:02 | 0.00 | -12174.98 | 0.00 | -710.31 | 0.00 | 0.00 | 235.29 | 137.19 | 273.90 | 3703.47 | 0.00 | 299.28 | 8236.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 15-SEP-00:35 | 0.00 | 0.00 | 0.00 | -15262.40 | 0.00 | 0.00 | 5584.96 | 1493.85 | 0.00 | 0.00 | 0.00 | 0.00 | 10505.77 | 0.00 | -1747.69 | 0.00 | -574.49 | 0.00 |
ROOM_1_FLR_6 | 17-JUN-18:02 | 0.00 | -3770.53 | 0.00 | -178.65 | 0.00 | 0.00 | 70.80 | 122.50 | 129.07 | 2523.40 | 0.00 | 21.58 | 1081.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 17-JUN-18:02 | 0.00 | -3585.16 | 0.00 | -179.56 | 0.00 | 0.00 | 70.80 | 122.49 | 129.05 | 2734.61 | 0.00 | 15.86 | 691.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 25-AUG-15:02 | 0.00 | -18159.58 | 0.00 | -1170.84 | 0.00 | 0.00 | 529.34 | 194.07 | 603.86 | 10028.51 | 0.00 | 159.98 | 7814.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 16-APR-21:25 | 0.00 | 0.00 | 0.00 | -40731.13 | 0.00 | 0.00 | 12513.32 | 1718.92 | 6747.90 | 0.00 | 0.00 | 0.00 | 21116.08 | 0.00 | -1043.42 | 0.00 | -321.67 | 0.00 |
DINING_FLR_6 | 16-APR-21:25 | 0.00 | 0.00 | 0.00 | -43021.62 | 0.00 | 0.00 | 12370.08 | 1718.92 | 6747.90 | 0.00 | 0.00 | 0.00 | 23573.72 | 0.00 | -1065.29 | 0.00 | -323.72 | 0.00 |
KITCHEN_FLR_6 | 21-FEB-12:24 | 0.00 | 0.00 | 0.00 | -38902.37 | 0.00 | 0.00 | 305.84 | 302.73 | 24259.91 | 1893.28 | 0.00 | 0.00 | 12388.88 | 0.00 | -0.00 | 0.00 | -248.27 | 0.00 |
CORRIDOR_FLR_6 | 15-SEP-00:35 | 0.00 | 0.00 | 0.00 | -7389.53 | 0.00 | 0.00 | 1527.97 | 395.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6474.57 | 0.00 | -762.19 | 0.00 | -246.07 | 0.00 |
Total Facility | 30-JUN-18:02 | 0.00 | -167038.71 | 0.00 | -222903.37 | 0.00 | 0.00 | 74349.15 | 53571.31 | 122326.88 | 78034.11 | 0.00 | 4032.98 | 57627.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 24-APR-02:34 | 0.00 | 0.00 | 2558.26 | 0.00 | 0.00 | 0.00 | 7479.19 | 1576.23 | 2129.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -13742.90 |
RETAIL_1_FLR_1 | 26-DEC-08:02 | 0.00 | 0.00 | 2227.70 | 0.00 | 0.00 | 0.00 | 357.99 | 313.07 | 360.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1540.71 | 0.00 | -644.12 | -1074.78 |
RETAIL_2_FLR_1 | 16-OCT-08:54 | 0.00 | 0.00 | 249.55 | 0.00 | 0.00 | 0.00 | 197.21 | 362.54 | 417.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -76.48 | -1150.68 |
MECH_FLR_1 | 06-JAN-03:10 | 0.00 | 0.00 | 1443.01 | 0.00 | 0.00 | 0.00 | 197.29 | 151.16 | 176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -698.08 | -1270.11 |
STORAGE_FLR_1 | 06-JAN-11:13 | 0.00 | 0.00 | 1114.78 | 0.00 | 0.00 | 0.00 | 33.74 | 63.26 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -352.72 | -948.28 |
LAUNDRY_FLR_1 | 22-OCT-23:34 | 0.00 | 0.00 | 2541.26 | 0.00 | 0.00 | 0.00 | 563.81 | 79.38 | 13989.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -240.65 | -16933.08 |
CAFE_FLR_1 | 16-OCT-08:54 | 0.00 | 0.00 | 2728.20 | 0.00 | 0.00 | 0.00 | 2351.94 | 477.67 | 508.04 | 1213.35 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -415.57 | -6863.63 |
LOBBY_FLR_1 | 20-NOV-09:45 | 0.00 | 0.00 | 4429.64 | 0.00 | 0.00 | 0.00 | 6737.54 | 4242.94 | 5278.53 | 3127.12 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1212.18 | -22603.60 |
ROOM_1_FLR_3 | 12-JAN-19:01 | 13972.94 | 300.85 | 0.00 | -300.85 | 0.00 | 0.00 | 419.21 | 436.12 | 516.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3242.35 | 0.00 | -1306.12 | -10796.06 |
ROOM_2_FLR_3 | 20-DEC-19:01 | 13890.02 | 296.73 | 0.00 | -296.73 | 0.00 | 0.00 | 419.22 | 436.07 | 516.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3284.52 | 0.00 | -1366.13 | -10610.86 |
ROOM_3_MULT19_FLR_3 | 09-JAN-05:00 | 35067.27 | 25898.13 | 0.00 | -25898.13 | 0.00 | 0.00 | 0.00 | 643.59 | 3921.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21715.82 | 0.00 | -9015.63 | -8900.88 |
ROOM_4_MULT19_FLR_3 | 06-JAN-16:01 | 74836.01 | 3654.24 | 0.00 | -3654.24 | 0.00 | 0.00 | 5585.75 | 1638.79 | 5099.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16065.27 | 0.00 | -6946.06 | -64148.51 |
ROOM_5_FLR_3 | 12-JAN-19:01 | 13696.43 | 298.75 | 0.00 | -298.75 | 0.00 | 0.00 | 419.20 | 436.12 | 516.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3240.18 | 0.00 | -1305.21 | -10522.63 |
ROOM_6_FLR_3 | 06-JAN-16:01 | 13657.61 | 290.39 | 0.00 | -290.39 | 0.00 | 0.00 | 293.99 | 137.19 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2973.63 | 0.00 | -1318.96 | -10070.10 |
CORRIDOR_FLR_3 | 05-JAN-07:05 | 0.00 | 0.00 | 5783.97 | 0.00 | 0.00 | 0.00 | 2771.59 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5067.41 | 0.00 | -2103.76 | -6363.90 |
ROOM_1_FLR_6 | 12-JAN-19:01 | 4096.30 | 75.97 | 0.00 | -75.97 | 0.00 | 0.00 | 104.80 | 109.03 | 129.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -810.36 | 0.00 | -327.40 | -3301.45 |
ROOM_2_FLR_6 | 20-DEC-19:01 | 4061.93 | 74.65 | 0.00 | -74.65 | 0.00 | 0.00 | 104.80 | 109.02 | 129.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -819.46 | 0.00 | -342.29 | -3243.05 |
ROOM_3_MULT9_FLR_6 | 13-DEC-16:01 | 19531.92 | 486.38 | 0.00 | -486.38 | 0.00 | 0.00 | 661.48 | 194.07 | 603.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2485.45 | 0.00 | -1021.14 | -17484.73 |
BANQUET_FLR_6 | 16-OCT-08:54 | 0.00 | 0.00 | 203.88 | 0.00 | 0.00 | 0.00 | 3611.39 | 1100.11 | 6747.90 | 83.94 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -309.40 | -11437.83 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 22-OCT-23:34 | 0.00 | 0.00 | 584.66 | 0.00 | 0.00 | 0.00 | 1421.97 | 242.18 | 5415.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -770.73 | 0.00 | -259.85 | -6634.22 |
CORRIDOR_FLR_6 | 09-JAN-06:04 | 0.00 | 0.00 | 5465.46 | 0.00 | 0.00 | 0.00 | 1283.23 | 1054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2195.54 | 0.00 | -915.47 | -4691.69 |
Total Facility | 23-JAN-09:01 | 105888.11 | 78047.06 | 11894.16 | -78047.06 | 0.00 | 0.00 | 23964.44 | 26712.50 | 88432.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -50174.91 | 0.00 | -32568.96 | -174147.56 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 23.3412 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 23.2062 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6706 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6706 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5686 | 2.5686 | 1.2843 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4629 | 0.4629 | 0.2314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2467 | 0.2467 | 0.1233 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2290 | 0.2290 | 0.1145 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1106 | 0.1106 | 0.0553 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3973 | 3.3973 | 1.6986 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8141 | 1.8141 | 0.9070 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1348 | 5.1348 | 2.5674 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6156 | 1.6156 | 0.8078 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2246 | 2.2246 | 1.1123 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3324 | 2.3324 | 1.1662 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3913 | 2.3913 | 1.1956 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8136 | 0.8136 | 0.4068 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 23.3412 | 23.2062 | 23.3412 | 11.6706 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2843 | 1.2843 | 1.2843 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2314 | 0.2314 | 0.2314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1233 | 0.1233 | 0.1233 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1145 | 0.1145 | 0.1145 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0553 | 0.0553 | 0.0553 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6986 | 1.6986 | 1.6986 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9070 | 0.9070 | 0.9070 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5674 | 2.5674 | 2.5674 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8078 | 0.8078 | 0.8078 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1123 | 1.1123 | 1.1123 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1662 | 1.1662 | 1.1662 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1956 | 1.1956 | 1.1956 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4068 | 0.4068 | 0.4068 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6706 | 11.6706 | 11.6706 | 11.6706 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 34.67 |
Number of hours cooling loads not met | 283.33 |
Number of hours not met | 318.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 3177.27 | 1101672.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 593.01 | 203641.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 766.12 | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 242.19 | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.56 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 32.45 | 1868.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 556.64 | 46536.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 100.65 | 7224.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 228.29 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4740.07 | 3482.41 | 311602.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.35 | 2068.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.93 | 1245.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1806.39 | 5035.52 |
Natural Gas | 1788.84 | 8448.51 |
Additional | 0.00 | 0.00 |
Total | 3595.22 | 13484.03 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 67.53 |
Space Heating | 0.00 |
Space Cooling | 52.27 |
Fans (All) | 49.06 |
Service Water Heating | 8.00 |
Receptacle Equipment | 153.81 |
Miscellaneous (All) | 443.84 |
Subtotal | 443.84 |
Natural Gas [MJ/m2] | |
Space Heating | 280.05 |
Service Water Heating | 306.95 |
Miscellaneous (All) | 744.67 |
Subtotal | 744.67 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.68 |
Space Heating | 23.56 |
Space Cooling | 4.40 |
Fans (All) | 4.13 |
Service Water Heating | 26.50 |
Receptacle Equipment | 26.21 |
Miscellaneous | 9.52 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2667. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 2678. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 3061. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8759.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.50 | 0.00 | 0.00 | 0.00 |
Average | 8759.98 | 0.02 | 0.00 | 0.00 | 0.00 |
Sum | 192719.50 | 0.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108265.00 | 4.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 4.00 | 0.00 | 0.00 | 0.00 |
Average | 288886.86 | 0.18 | 0.00 | 0.00 | 0.00 |
Sum | 6355511.00 | 4.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8731.00 | 29.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8455.83 | 304.17 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8403.33 | 356.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8756.17 | 3.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8386.33 | 373.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8427.83 | 332.17 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8729.50 | 30.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8386.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 373.67 | 0.00 | 0.00 | 0.00 |
Average | 8694.94 | 65.06 | 0.00 | 0.00 | 0.00 |
Sum | 191288.67 | 1431.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 58842.00 | 314.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 672361.17 | 38055.83 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1988854.00 | 126575.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100291.00 | 67.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1167592.83 | 78122.17 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1175701.33 | 70013.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108068.50 | 200.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1988854.00 | 126575.00 | 0.00 | 0.00 | 0.00 |
Average | 274643.95 | 14243.10 | 0.00 | 0.00 | 0.00 |
Sum | 6042166.83 | 313348.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:24
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.333143E+11 | 26839.40 | 26-JAN-07:00 | -33.3 | -33.4 | 0.711386E+10 | 4836.93 | 24-JAN-22:19 | -33.3 | -33.4 |
February | 0.278067E+11 | 24236.67 | 14-FEB-06:20 | -32.2 | -32.4 | 0.657877E+10 | 4732.34 | 10-FEB-22:10 | -32.2 | -32.4 |
March | 0.268098E+11 | 20953.74 | 05-MAR-04:00 | -28.3 | -28.5 | 0.692832E+10 | 4581.64 | 01-MAR-22:10 | -28.3 | -28.5 |
April | 0.254719E+11 | 22885.67 | 16-APR-21:25 | 4.15 | 0.67 | 0.664814E+10 | 4392.42 | 24-APR-22:10 | 4.90 | 2.90 |
May | 0.284246E+11 | 19110.19 | 08-MAY-13:05 | 6.92 | 5.03 | 0.710571E+10 | 4526.56 | 09-MAY-21:00 | 4.80 | 2.47 |
June | 0.295217E+11 | 19804.00 | 16-JUN-03:03 | 8.12 | 7.61 | 0.710213E+10 | 4587.99 | 09-JUN-21:10 | 8.12 | 7.61 |
July | 0.336591E+11 | 20039.75 | 02-JUL-03:03 | 8.22 | 8.02 | 0.780083E+10 | 4837.06 | 18-JUL-21:19 | 15.37 | 14.66 |
August | 0.372089E+11 | 32890.14 | 18-AUG-23:00 | 6.70 | 6.40 | 0.815416E+10 | 4877.71 | 19-AUG-00:49 | 7.30 | 7.30 |
September | 0.377555E+11 | 36307.56 | 14-SEP-06:29 | 5.00 | 4.61 | 0.793574E+10 | 5011.05 | 23-SEP-01:19 | 6.50 | 5.04 |
October | 0.391061E+11 | 35705.03 | 23-OCT-06:54 | 5.60 | 4.05 | 0.821249E+10 | 4994.76 | 20-OCT-04:10 | 5.60 | 4.05 |
November | 0.362190E+11 | 34524.07 | 17-NOV-20:57 | 3.30 | -0.9 | 0.792411E+10 | 4924.82 | 21-NOV-00:30 | 7.80 | 7.36 |
December | 0.357947E+11 | 24702.46 | 24-DEC-07:40 | -31.1 | -31.3 | 0.763213E+10 | 4837.03 | 01-DEC-00:20 | -31.1 | -31.3 |
Annual Sum or Average | 0.391092E+12 | 0.891364E+11 | ||||||||
Minimum of Months | 0.254719E+11 | 19110.19 | -33.3 | -33.4 | 0.657877E+10 | 4392.42 | -33.3 | -33.4 | ||
Maximum of Months | 0.391061E+11 | 36307.56 | 8.22 | 8.02 | 0.821249E+10 | 5011.05 | 15.37 | 14.66 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.500219E+09 | 2341.09 | 05-JAN-12:50 | -27.9 | -28.2 | 0.618941E+09 | 364.35 | 25-JAN-04:00 | -23.9 | -24.1 |
February | 0.118472E+10 | 5789.44 | 28-FEB-15:06 | 6.10 | 1.55 | 0.567843E+09 | 364.48 | 28-FEB-22:19 | -0.2 | -3.1 |
March | 0.171842E+10 | 5045.96 | 31-MAR-13:26 | 7.50 | 2.61 | 0.634078E+09 | 396.97 | 31-MAR-21:19 | 4.83 | 0.87 |
April | 0.297155E+10 | 6196.95 | 19-APR-13:16 | 6.30 | 0.57 | 0.627003E+09 | 432.16 | 13-APR-21:30 | 6.30 | 0.57 |
May | 0.463367E+10 | 3890.35 | 18-MAY-13:10 | 28.25 | 16.75 | 0.673852E+09 | 464.55 | 25-MAY-21:30 | 22.35 | 16.43 |
June | 0.484815E+10 | 4006.84 | 30-JUN-13:00 | 31.70 | 24.46 | 0.665174E+09 | 481.94 | 29-JUN-21:19 | 31.70 | 24.46 |
July | 0.555630E+10 | 4118.61 | 23-JUL-13:10 | 30.00 | 22.77 | 0.710544E+09 | 470.71 | 24-JUL-21:30 | 19.15 | 17.68 |
August | 0.536406E+10 | 4527.88 | 26-AUG-12:40 | 25.40 | 19.23 | 0.700511E+09 | 466.85 | 08-AUG-21:30 | 25.40 | 19.23 |
September | 0.439212E+10 | 4531.70 | 01-SEP-13:20 | 24.80 | 18.00 | 0.645125E+09 | 454.78 | 01-SEP-21:30 | 14.45 | 13.76 |
October | 0.285470E+10 | 6194.31 | 09-OCT-11:43 | 4.22 | 0.02 | 0.642189E+09 | 441.40 | 19-OCT-21:30 | 12.50 | 9.82 |
November | 0.114691E+10 | 5029.14 | 16-NOV-11:23 | 5.25 | 0.94 | 0.604065E+09 | 378.38 | 21-NOV-00:30 | 7.80 | 7.36 |
December | 0.350461E+09 | 2806.91 | 10-DEC-12:00 | -23.9 | -24.3 | 0.620339E+09 | 364.35 | 26-DEC-03:30 | -24.4 | -24.6 |
Annual Sum or Average | 0.355213E+11 | 0.770966E+10 | ||||||||
Minimum of Months | 0.350461E+09 | 2341.09 | -27.9 | -28.2 | 0.567843E+09 | 364.35 | -24.4 | -24.6 | ||
Maximum of Months | 0.555630E+10 | 6196.95 | 31.70 | 24.46 | 0.710544E+09 | 481.94 | 31.70 | 24.46 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141253E+10 | 1618.42 | 27-JAN-22:05 | -24.2 | -24.4 | 0.727555E+09 | 479.10 | 19-JAN-22:19 | -24.2 | -24.4 |
February | 0.171416E+10 | 1795.60 | 21-FEB-12:24 | 6.40 | 3.17 | 0.678868E+09 | 520.86 | 22-FEB-22:19 | -6.1 | -7.7 |
March | 0.222442E+10 | 1638.99 | 31-MAR-20:51 | 5.00 | 0.95 | 0.784902E+09 | 556.07 | 31-MAR-21:19 | 4.83 | 0.87 |
April | 0.260160E+10 | 2307.92 | 16-APR-21:25 | 4.15 | 0.67 | 0.821423E+09 | 573.36 | 24-APR-22:10 | 4.90 | 2.90 |
May | 0.311732E+10 | 2078.84 | 20-MAY-21:27 | 7.15 | 3.94 | 0.913045E+09 | 577.16 | 22-MAY-03:20 | 7.00 | 4.08 |
June | 0.319001E+10 | 2749.36 | 17-JUN-01:23 | 5.85 | 5.45 | 0.895109E+09 | 572.34 | 16-JUN-23:40 | 5.85 | 5.45 |
July | 0.349151E+10 | 2626.40 | 02-JUL-03:03 | 8.22 | 8.02 | 0.941744E+09 | 578.92 | 08-JUL-00:00 | 7.80 | 7.48 |
August | 0.336879E+10 | 2024.84 | 19-AUG-01:23 | 6.65 | 6.54 | 0.937232E+09 | 569.54 | 25-AUG-00:20 | 10.57 | 10.36 |
September | 0.294514E+10 | 3223.17 | 05-SEP-21:27 | 6.40 | 5.72 | 0.881001E+09 | 577.97 | 05-SEP-21:00 | 5.60 | 5.09 |
October | 0.266077E+10 | 3259.47 | 20-OCT-21:55 | 6.10 | 4.28 | 0.856070E+09 | 579.03 | 25-OCT-21:40 | 6.70 | 5.00 |
November | 0.217521E+10 | 1844.32 | 21-NOV-01:33 | 8.13 | 7.81 | 0.757360E+09 | 542.37 | 17-NOV-22:19 | 8.13 | 7.81 |
December | 0.148469E+10 | 1535.84 | 02-DEC-00:33 | -23.9 | -24.2 | 0.730392E+09 | 481.20 | 05-DEC-23:10 | 0.00 | -0.0 |
Annual Sum or Average | 0.303861E+11 | 0.992470E+10 | ||||||||
Minimum of Months | 0.141253E+10 | 1535.84 | -24.2 | -24.4 | 0.678868E+09 | 479.10 | -24.2 | -24.4 | ||
Maximum of Months | 0.349151E+10 | 3259.47 | 8.22 | 8.02 | 0.941744E+09 | 579.03 | 10.57 | 10.36 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 91433501.02 | 817.35 | 19-JAN-21:00 | -3.3 | -3.9 | 0.151689E+09 | 90.47 | 19-JAN-22:10 | -3.9 | -4.6 |
February | 0.324683E+09 | 1268.03 | 04-FEB-18:32 | 4.60 | 0.62 | 0.137389E+09 | 94.46 | 21-FEB-22:10 | -3.0 | -4.4 |
March | 0.785658E+09 | 1292.34 | 31-MAR-20:51 | 5.00 | 0.95 | 0.153548E+09 | 99.40 | 27-MAR-21:10 | 5.00 | 0.95 |
April | 0.183894E+10 | 1968.84 | 16-APR-21:25 | 4.15 | 0.67 | 0.155582E+09 | 108.42 | 24-APR-22:10 | 4.90 | 2.90 |
May | 0.264107E+10 | 1703.44 | 08-MAY-13:05 | 6.92 | 5.03 | 0.181658E+09 | 120.45 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.282176E+10 | 2140.59 | 30-JUN-20:00 | 24.40 | 17.93 | 0.183791E+09 | 120.45 | 26-JUN-21:19 | 24.40 | 17.93 |
July | 0.309589E+10 | 1888.40 | 24-JUL-20:00 | 21.70 | 19.11 | 0.196086E+09 | 120.45 | 07-JUL-21:10 | 21.70 | 19.11 |
August | 0.294291E+10 | 1814.56 | 19-AUG-01:23 | 6.65 | 6.54 | 0.192736E+09 | 120.45 | 25-AUG-21:19 | 17.43 | 16.14 |
September | 0.253232E+10 | 2130.94 | 15-SEP-00:35 | 6.10 | 5.73 | 0.176470E+09 | 120.45 | 01-SEP-21:19 | 6.10 | 5.73 |
October | 0.211177E+10 | 2048.93 | 23-OCT-00:23 | 6.10 | 4.83 | 0.165034E+09 | 111.13 | 20-OCT-21:49 | 6.10 | 4.83 |
November | 0.110718E+10 | 1556.96 | 21-NOV-01:33 | 8.13 | 7.81 | 0.148546E+09 | 100.25 | 01-NOV-21:10 | 8.13 | 7.81 |
December | 0.132589E+09 | 825.77 | 05-DEC-21:00 | 0.00 | -0.0 | 0.151715E+09 | 91.10 | 05-DEC-22:10 | 0.00 | -0.0 |
Annual Sum or Average | 0.204262E+11 | 0.199424E+10 | ||||||||
Minimum of Months | 91433501.02 | 817.35 | -3.3 | -3.9 | 0.137389E+09 | 90.47 | -3.9 | -4.6 | ||
Maximum of Months | 0.309589E+10 | 2140.59 | 24.40 | 19.11 | 0.196086E+09 | 120.45 | 24.40 | 19.11 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 960892.08 | 96.83 | 19-JAN-22:00 | -3.9 | -4.6 | 0.116617E+09 | 68.58 | 25-JAN-05:00 | -24.4 | -24.6 |
February | 42871106.41 | 531.29 | 21-FEB-15:55 | 5.00 | 2.18 | 0.105502E+09 | 68.58 | 15-FEB-03:20 | 5.00 | 2.18 |
March | 0.178790E+09 | 587.14 | 31-MAR-20:51 | 5.00 | 0.95 | 0.117435E+09 | 72.12 | 31-MAR-21:19 | 4.83 | 0.87 |
April | 0.728878E+09 | 919.84 | 16-APR-21:25 | 4.15 | 0.67 | 0.117060E+09 | 79.41 | 23-APR-23:10 | 14.63 | 10.70 |
May | 0.122763E+10 | 810.89 | 08-MAY-13:05 | 6.92 | 5.03 | 0.136006E+09 | 90.17 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.131267E+10 | 843.54 | 16-JUN-03:03 | 8.12 | 7.61 | 0.138168E+09 | 92.66 | 30-JUN-21:19 | 20.10 | 16.56 |
July | 0.143822E+10 | 881.06 | 02-JUL-03:03 | 8.22 | 8.02 | 0.147854E+09 | 92.66 | 24-JUL-21:19 | 19.23 | 17.76 |
August | 0.137500E+10 | 858.70 | 19-AUG-01:23 | 6.65 | 6.54 | 0.144764E+09 | 91.16 | 09-AUG-21:49 | 6.65 | 6.54 |
September | 0.117739E+10 | 1013.33 | 15-SEP-00:35 | 6.10 | 5.73 | 0.131815E+09 | 89.63 | 01-SEP-21:30 | 6.10 | 5.73 |
October | 0.894697E+09 | 977.20 | 23-OCT-00:23 | 6.10 | 4.83 | 0.123305E+09 | 81.26 | 20-OCT-22:30 | 6.10 | 4.83 |
November | 0.285240E+09 | 740.50 | 21-NOV-01:33 | 8.13 | 7.81 | 0.113159E+09 | 73.04 | 01-NOV-22:10 | 8.13 | 7.81 |
December | 2254181.56 | 154.16 | 05-DEC-22:00 | 0.00 | -0.0 | 0.116691E+09 | 68.59 | 13-DEC-04:00 | -24.5 | -24.8 |
Annual Sum or Average | 0.866459E+10 | 0.150838E+10 | ||||||||
Minimum of Months | 960892.08 | 96.83 | -3.9 | -4.6 | 0.105502E+09 | 68.58 | -24.5 | -24.8 | ||
Maximum of Months | 0.143822E+10 | 1013.33 | 8.22 | 8.02 | 0.147854E+09 | 92.66 | 21.73 | 17.76 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.449521E+11 | 35826.33 | 19-JAN-21:00 | -3.3 | -3.9 | 0.546243E+09 | 381.62 | 20-JAN-22:10 | -13.5 | -13.7 |
February | 0.415553E+11 | 43944.16 | 20-FEB-19:14 | 4.23 | 1.26 | 0.515284E+09 | 381.58 | 17-FEB-22:10 | 4.23 | 1.26 |
March | 0.472897E+11 | 50696.78 | 27-MAR-20:37 | 4.07 | 1.16 | 0.586073E+09 | 462.22 | 27-MAR-20:19 | 4.07 | 1.16 |
April | 0.476624E+11 | 52328.57 | 19-APR-19:09 | 4.72 | -0.8 | 0.577930E+09 | 567.56 | 24-APR-22:10 | 4.90 | 2.90 |
May | 0.515247E+11 | 50290.65 | 09-MAY-20:56 | 5.60 | 2.96 | 0.602705E+09 | 460.77 | 08-MAY-22:10 | 5.60 | 2.96 |
June | 0.507294E+11 | 46037.38 | 02-JUN-21:28 | 6.65 | 4.99 | 0.583369E+09 | 439.98 | 02-JUN-22:19 | 5.00 | 4.07 |
July | 0.526906E+11 | 38765.93 | 21-JUL-20:00 | 22.20 | 20.61 | 0.601338E+09 | 409.35 | 08-JUL-00:00 | 22.20 | 20.61 |
August | 0.523870E+11 | 38664.32 | 08-AUG-20:00 | 25.00 | 20.33 | 0.601180E+09 | 409.66 | 19-AUG-00:49 | 7.30 | 7.30 |
September | 0.493348E+11 | 49686.26 | 23-SEP-20:56 | 5.60 | 5.09 | 0.585746E+09 | 459.36 | 05-SEP-21:00 | 5.60 | 5.09 |
October | 0.492181E+11 | 51339.81 | 03-OCT-20:57 | 3.30 | 2.37 | 0.604276E+09 | 508.38 | 25-OCT-21:40 | 6.70 | 5.00 |
November | 0.459683E+11 | 50245.36 | 17-NOV-20:40 | 3.67 | -0.6 | 0.569572E+09 | 408.10 | 20-NOV-23:19 | 7.80 | 7.24 |
December | 0.450606E+11 | 35907.28 | 05-DEC-21:00 | 0.00 | -0.0 | 0.558707E+09 | 381.62 | 29-DEC-22:10 | -10.3 | -11.0 |
Annual Sum or Average | 0.578373E+12 | 0.693242E+10 | ||||||||
Minimum of Months | 0.415553E+11 | 35826.33 | -3.3 | -3.9 | 0.515284E+09 | 381.58 | -13.5 | -13.7 | ||
Maximum of Months | 0.526906E+11 | 52328.57 | 25.00 | 20.61 | 0.604276E+09 | 567.56 | 22.20 | 20.61 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104542E+11 | 10310.01 | 27-JAN-13:30 | -15.0 | -16.1 | 0.824398E+10 | 5255.01 | 19-JAN-22:40 | -15.0 | -16.1 |
February | 0.131954E+11 | 22482.99 | 28-FEB-15:06 | 6.10 | 1.55 | 0.775758E+10 | 6051.66 | 28-FEB-22:40 | -0.4 | -3.3 |
March | 0.163235E+11 | 19585.98 | 26-MAR-11:27 | 5.55 | 2.42 | 0.894986E+10 | 6405.26 | 31-MAR-21:49 | 4.58 | 0.73 |
April | 0.191194E+11 | 24222.44 | 19-APR-14:06 | 6.70 | 0.87 | 0.920104E+10 | 6565.42 | 14-APR-02:09 | 6.70 | 0.87 |
May | 0.224339E+11 | 15860.15 | 01-MAY-14:08 | 9.42 | 2.08 | 0.101571E+11 | 6987.63 | 22-MAY-03:20 | 7.00 | 4.08 |
June | 0.225728E+11 | 17548.85 | 16-JUN-23:44 | 6.38 | 6.06 | 0.998292E+10 | 6537.35 | 16-JUN-23:40 | 6.38 | 6.06 |
July | 0.245962E+11 | 15456.11 | 07-JUL-23:53 | 7.80 | 7.48 | 0.104982E+11 | 6675.25 | 08-JUL-00:00 | 7.80 | 7.48 |
August | 0.242940E+11 | 15876.56 | 26-AUG-12:40 | 25.40 | 19.23 | 0.104739E+11 | 6461.95 | 12-AUG-01:19 | 25.40 | 19.23 |
September | 0.217180E+11 | 17558.62 | 15-SEP-00:35 | 6.10 | 5.73 | 0.978760E+10 | 6666.80 | 25-SEP-01:49 | 7.80 | 7.19 |
October | 0.190776E+11 | 24386.54 | 09-OCT-11:43 | 4.22 | 0.02 | 0.948041E+10 | 6744.46 | 25-OCT-21:40 | 6.70 | 5.00 |
November | 0.144754E+11 | 19683.03 | 17-NOV-11:10 | 7.07 | 2.03 | 0.845153E+10 | 6206.00 | 21-NOV-00:30 | 7.80 | 7.36 |
December | 0.978380E+10 | 11938.39 | 10-DEC-11:00 | -24.8 | -25.2 | 0.823055E+10 | 5314.60 | 05-DEC-22:40 | -24.8 | -25.2 |
Annual Sum or Average | 0.218044E+12 | 0.111215E+12 | ||||||||
Minimum of Months | 0.978380E+10 | 10310.01 | -24.8 | -25.2 | 0.775758E+10 | 5255.01 | -24.8 | -25.2 | ||
Maximum of Months | 0.245962E+11 | 24386.54 | 25.40 | 19.23 | 0.104982E+11 | 6987.63 | 25.40 | 19.23 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.428202E+11 | 35147.89 | 27-JAN-22:05 | -24.2 | -24.4 | 0.254322E+11 | 17372.85 | 19-JAN-23:10 | -24.2 | -24.4 |
February | 0.447731E+11 | 39527.23 | 21-FEB-12:24 | 6.40 | 3.17 | 0.242285E+11 | 18767.64 | 22-FEB-22:49 | -6.1 | -7.8 |
March | 0.533225E+11 | 55228.84 | 31-MAR-21:36 | 4.67 | 0.78 | 0.281887E+11 | 19193.00 | 31-MAR-21:19 | 4.67 | 0.78 |
April | 0.588007E+11 | 65667.06 | 11-APR-21:24 | 4.45 | 0.40 | 0.291541E+11 | 19661.01 | 24-APR-22:10 | 4.90 | 2.90 |
May | 0.692895E+11 | 63520.73 | 20-MAY-00:56 | 8.50 | 6.51 | 0.317206E+11 | 20437.80 | 22-MAY-03:20 | 7.00 | 4.08 |
June | 0.707699E+11 | 64195.22 | 16-JUN-23:55 | 6.10 | 5.88 | 0.309673E+11 | 19662.07 | 15-JUN-04:00 | 6.10 | 5.88 |
July | 0.767474E+11 | 69094.11 | 07-JUL-23:53 | 7.80 | 7.48 | 0.321848E+11 | 19874.94 | 08-JUL-00:40 | 7.80 | 7.48 |
August | 0.749356E+11 | 62116.53 | 25-AUG-04:16 | 8.53 | 8.43 | 0.322544E+11 | 19367.58 | 05-AUG-01:19 | 8.53 | 8.43 |
September | 0.664202E+11 | 68448.13 | 05-SEP-21:27 | 6.40 | 5.72 | 0.308071E+11 | 20204.42 | 23-SEP-01:19 | 6.50 | 5.04 |
October | 0.606257E+11 | 73109.78 | 19-OCT-03:43 | 7.70 | 6.14 | 0.304520E+11 | 20280.98 | 20-OCT-04:10 | 6.88 | 6.88 |
November | 0.511517E+11 | 78856.56 | 21-NOV-01:33 | 8.13 | 7.81 | 0.272775E+11 | 19183.36 | 17-NOV-22:40 | 8.13 | 7.81 |
December | 0.427868E+11 | 34442.26 | 02-DEC-00:33 | -23.9 | -24.2 | 0.256832E+11 | 17471.04 | 05-DEC-23:10 | 0.00 | -0.0 |
Annual Sum or Average | 0.712443E+12 | 0.348350E+12 | ||||||||
Minimum of Months | 0.427868E+11 | 34442.26 | -24.2 | -24.4 | 0.242285E+11 | 17372.85 | -24.2 | -24.4 | ||
Maximum of Months | 0.767474E+11 | 78856.56 | 8.53 | 8.43 | 0.322544E+11 | 20437.80 | 8.53 | 8.43 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22305223.47 | 1223.40 | 31-JAN-16:03 | -19.7 | -20.4 | 92483826.94 | 56.69 | 27-JAN-04:19 | -19.7 | -20.4 |
February | 87064730.44 | 3368.45 | 22-FEB-16:01 | -0.7 | -3.9 | 84523397.47 | 56.69 | 10-FEB-04:19 | -0.7 | -3.9 |
March | 0.230524E+09 | 3486.98 | 31-MAR-15:01 | 8.40 | 2.82 | 94596362.92 | 56.69 | 31-MAR-21:10 | 4.92 | 0.91 |
April | 0.686835E+09 | 3608.43 | 13-APR-15:02 | 20.00 | 8.11 | 93303153.34 | 56.69 | 13-APR-21:19 | 12.77 | 6.63 |
May | 0.167609E+10 | 3731.53 | 21-MAY-15:02 | 22.73 | 11.45 | 98467801.39 | 56.70 | 25-MAY-22:00 | 20.90 | 16.25 |
June | 0.196436E+10 | 3803.60 | 30-JUN-18:02 | 29.63 | 20.10 | 95458091.93 | 56.70 | 29-JUN-23:49 | 29.63 | 20.10 |
July | 0.247163E+10 | 3778.20 | 20-JUL-18:02 | 27.62 | 20.32 | 98815073.57 | 56.70 | 21-JUL-22:30 | 21.40 | 19.84 |
August | 0.200348E+10 | 3634.30 | 08-AUG-18:02 | 28.03 | 22.23 | 98618611.01 | 56.70 | 08-AUG-21:49 | 21.88 | 18.46 |
September | 0.111048E+10 | 3646.46 | 06-SEP-15:02 | 20.00 | 11.79 | 94650705.23 | 56.70 | 01-SEP-21:19 | 20.00 | 11.79 |
October | 0.391661E+09 | 3584.09 | 21-OCT-15:02 | 20.00 | 11.21 | 95484545.87 | 56.69 | 22-OCT-04:10 | 10.78 | 9.49 |
November | 60339971.17 | 3302.45 | 17-NOV-16:01 | 9.45 | 2.90 | 90506204.37 | 56.69 | 01-NOV-02:20 | 9.45 | 2.90 |
December | 17450491.90 | 903.62 | 05-DEC-19:04 | 0.00 | -0.0 | 92302141.85 | 56.69 | 22-DEC-04:19 | -15.3 | -15.8 |
Annual Sum or Average | 0.107222E+11 | 0.112921E+10 | ||||||||
Minimum of Months | 17450491.90 | 903.62 | -19.7 | -20.4 | 84523397.47 | 56.69 | -19.7 | -20.4 | ||
Maximum of Months | 0.247163E+10 | 3803.60 | 29.63 | 22.23 | 98815073.57 | 56.70 | 29.63 | 20.10 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8313812.14 | 819.28 | 16-JAN-09:04 | -1.0 | -1.7 | 92292089.45 | 56.69 | 03-JAN-04:19 | -1.0 | -1.7 |
February | 29777551.94 | 2839.10 | 22-FEB-16:01 | -0.7 | -3.9 | 83651845.26 | 56.69 | 03-FEB-04:19 | -0.7 | -3.9 |
March | 0.109168E+09 | 3259.48 | 28-MAR-18:01 | 6.93 | 2.56 | 93455286.10 | 56.69 | 31-MAR-21:10 | 4.92 | 0.91 |
April | 0.452121E+09 | 3380.17 | 13-APR-15:02 | 20.00 | 8.11 | 92445265.67 | 56.69 | 13-APR-21:49 | 11.97 | 6.44 |
May | 0.144802E+10 | 3600.59 | 25-MAY-18:02 | 29.03 | 19.14 | 98209608.58 | 56.70 | 25-MAY-22:49 | 21.07 | 16.29 |
June | 0.183081E+10 | 3636.43 | 30-JUN-18:02 | 29.63 | 20.10 | 95398124.39 | 56.70 | 29-JUN-23:00 | 29.63 | 20.10 |
July | 0.226082E+10 | 3562.46 | 24-JUL-18:02 | 27.85 | 19.74 | 98776084.47 | 56.70 | 03-JUL-21:00 | 27.85 | 19.74 |
August | 0.169798E+10 | 3519.15 | 23-AUG-15:02 | 26.60 | 20.51 | 98467015.68 | 56.70 | 25-AUG-21:30 | 17.25 | 16.01 |
September | 0.791327E+09 | 3419.45 | 06-SEP-15:02 | 20.00 | 11.79 | 94181072.69 | 56.69 | 07-SEP-21:49 | 18.40 | 13.48 |
October | 0.197868E+09 | 3345.93 | 21-OCT-15:02 | 20.00 | 11.21 | 94653554.84 | 56.69 | 22-OCT-03:20 | 9.07 | 7.89 |
November | 35916052.29 | 1495.23 | 21-NOV-16:03 | 5.73 | 5.40 | 89787946.68 | 56.69 | 01-NOV-02:20 | 5.73 | 5.40 |
December | 8211434.80 | 813.40 | 05-DEC-19:04 | 0.00 | -0.0 | 92212062.21 | 56.69 | 08-DEC-04:19 | -19.5 | -19.9 |
Annual Sum or Average | 0.887032E+10 | 0.112353E+10 | ||||||||
Minimum of Months | 8211434.80 | 813.40 | -1.0 | -3.9 | 83651845.26 | 56.69 | -19.5 | -19.9 | ||
Maximum of Months | 0.226082E+10 | 3636.43 | 29.63 | 20.51 | 98776084.47 | 56.70 | 29.63 | 20.10 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 53429097.72 | 302.33 | 05-JAN-11:03 | -29.7 | -29.9 | 0.00 | 0.00 | 01-JAN-00:10 | -29.7 | -29.9 |
February | 0.114186E+09 | 441.97 | 22-FEB-14:30 | -0.6 | -3.8 | 0.00 | 0.00 | 01-FEB-00:10 | -0.6 | -3.8 |
March | 0.175913E+09 | 566.77 | 20-MAR-12:30 | 1.70 | -1.1 | 0.00 | 0.00 | 01-MAR-00:10 | 1.70 | -1.1 |
April | 0.348011E+09 | 682.47 | 13-APR-13:20 | 18.17 | 6.98 | 0.00 | 0.00 | 01-APR-00:10 | 18.17 | 6.98 |
May | 0.529947E+09 | 696.15 | 18-MAY-13:10 | 28.25 | 16.75 | 0.00 | 0.00 | 01-MAY-00:10 | 28.25 | 16.75 |
June | 0.575383E+09 | 685.84 | 30-JUN-13:00 | 31.70 | 24.46 | 0.00 | 0.00 | 01-JUN-00:10 | 31.70 | 24.46 |
July | 0.714158E+09 | 730.55 | 23-JUL-13:20 | 30.00 | 22.71 | 0.00 | 0.00 | 01-JUL-00:10 | 30.00 | 22.71 |
August | 0.671316E+09 | 800.45 | 25-AUG-13:10 | 27.38 | 18.58 | 0.00 | 0.00 | 01-AUG-00:10 | 27.38 | 18.58 |
September | 0.519131E+09 | 804.53 | 01-SEP-13:20 | 24.80 | 18.00 | 0.00 | 0.00 | 01-SEP-00:10 | 24.80 | 18.00 |
October | 0.342922E+09 | 961.47 | 22-OCT-12:30 | 17.50 | 12.84 | 0.00 | 0.00 | 01-OCT-00:10 | 17.50 | 12.84 |
November | 0.115274E+09 | 441.42 | 17-NOV-13:30 | 10.30 | 3.32 | 0.00 | 0.00 | 01-NOV-00:10 | 10.30 | 3.32 |
December | 30600129.00 | 287.89 | 24-DEC-11:10 | -28.3 | -28.6 | 0.00 | 0.00 | 01-DEC-00:10 | -28.3 | -28.6 |
Annual Sum or Average | 0.419027E+10 | 0.00 | ||||||||
Minimum of Months | 30600129.00 | 287.89 | -29.7 | -29.9 | 0.00 | 0.00 | -29.7 | -29.9 | ||
Maximum of Months | 0.714158E+09 | 961.47 | 31.70 | 24.46 | 0.00 | 0.00 | 31.70 | 24.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 24565799.37 | 492.40 | 19-JAN-19:04 | -3.3 | -3.9 | 92765018.16 | 56.69 | 24-JAN-04:19 | -16.5 | -16.8 |
February | 33174165.02 | 553.26 | 21-FEB-19:03 | 0.60 | -0.4 | 84206642.34 | 56.69 | 03-FEB-04:19 | 0.60 | -0.4 |
March | 59820431.27 | 535.00 | 28-MAR-18:01 | 6.93 | 2.56 | 93980692.68 | 56.69 | 31-MAR-21:10 | 4.92 | 0.91 |
April | 0.188184E+09 | 913.09 | 23-APR-18:01 | 25.22 | 16.18 | 92362637.05 | 56.69 | 13-APR-22:10 | 25.22 | 16.18 |
May | 0.563434E+09 | 976.21 | 24-MAY-18:02 | 26.73 | 17.02 | 97184725.46 | 56.69 | 25-MAY-21:19 | 22.50 | 16.44 |
June | 0.714866E+09 | 991.53 | 17-JUN-18:02 | 23.62 | 13.20 | 94545104.35 | 56.69 | 21-JUN-21:49 | 17.30 | 14.89 |
July | 0.793100E+09 | 975.57 | 24-JUL-18:02 | 27.85 | 19.74 | 97784689.55 | 56.69 | 14-JUL-21:40 | 27.85 | 19.74 |
August | 0.644805E+09 | 953.58 | 09-AUG-18:02 | 26.52 | 20.82 | 97351112.19 | 56.69 | 10-AUG-21:10 | 15.40 | 14.50 |
September | 0.408443E+09 | 918.93 | 01-SEP-18:02 | 23.07 | 17.74 | 93422233.91 | 56.69 | 18-SEP-22:10 | 16.10 | 15.79 |
October | 0.176088E+09 | 816.99 | 01-OCT-08:61 | 6.23 | 5.55 | 95314887.62 | 56.69 | 20-OCT-21:40 | 6.10 | 4.28 |
November | 62167788.13 | 607.22 | 20-NOV-16:03 | 8.30 | 6.65 | 90986571.04 | 56.69 | 01-NOV-03:30 | 8.30 | 6.65 |
December | 27236499.18 | 443.37 | 06-DEC-19:04 | -7.2 | -7.4 | 92747270.15 | 56.69 | 15-DEC-04:19 | -14.2 | -15.1 |
Annual Sum or Average | 0.369588E+10 | 0.112265E+10 | ||||||||
Minimum of Months | 24565799.37 | 443.37 | -7.2 | -7.4 | 84206642.34 | 56.69 | -16.5 | -16.8 | ||
Maximum of Months | 0.793100E+09 | 991.53 | 27.85 | 20.82 | 97784689.55 | 56.69 | 27.85 | 19.74 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21655284.27 | 848.91 | 25-JAN-09:04 | -24.7 | -24.9 | 92410702.17 | 56.69 | 12-JAN-00:20 | -24.7 | -24.9 |
February | 71801165.52 | 2800.32 | 28-FEB-16:02 | 6.02 | 1.46 | 84453407.21 | 56.69 | 03-FEB-04:19 | 6.02 | 1.46 |
March | 0.189224E+09 | 3144.67 | 31-MAR-15:01 | 8.40 | 2.82 | 94815866.70 | 56.69 | 31-MAR-21:10 | 4.92 | 0.91 |
April | 0.711513E+09 | 3239.23 | 13-APR-15:02 | 20.00 | 8.11 | 93779329.10 | 56.69 | 13-APR-21:10 | 13.03 | 6.68 |
May | 0.159609E+10 | 3349.28 | 21-MAY-15:02 | 22.73 | 11.45 | 98722323.48 | 56.69 | 24-MAY-21:19 | 18.67 | 13.25 |
June | 0.209341E+10 | 3357.45 | 17-JUN-18:02 | 23.62 | 13.20 | 95725389.88 | 56.70 | 29-JUN-22:30 | 26.40 | 23.52 |
July | 0.247134E+10 | 3315.08 | 22-JUL-15:02 | 29.72 | 22.36 | 98978318.59 | 56.70 | 13-JUL-21:49 | 29.72 | 22.36 |
August | 0.194117E+10 | 3323.40 | 09-AUG-15:02 | 27.62 | 21.62 | 98797910.19 | 56.70 | 08-AUG-21:49 | 27.62 | 21.62 |
September | 0.109776E+10 | 3261.59 | 06-SEP-15:02 | 20.00 | 11.79 | 94701701.95 | 56.69 | 01-SEP-21:10 | 20.00 | 11.79 |
October | 0.365682E+09 | 3232.53 | 21-OCT-15:02 | 20.00 | 11.21 | 95510982.10 | 56.69 | 22-OCT-04:10 | 10.78 | 9.49 |
November | 73996199.34 | 2410.70 | 17-NOV-16:01 | 9.45 | 2.90 | 90434681.86 | 56.69 | 01-NOV-02:20 | 9.45 | 2.90 |
December | 17013425.09 | 906.15 | 02-DEC-09:04 | -25.8 | -26.0 | 92273359.26 | 56.69 | 15-DEC-04:19 | -14.2 | -15.1 |
Annual Sum or Average | 0.106507E+11 | 0.113060E+10 | ||||||||
Minimum of Months | 17013425.09 | 848.91 | -25.8 | -26.0 | 84453407.21 | 56.69 | -24.7 | -24.9 | ||
Maximum of Months | 0.247134E+10 | 3357.45 | 29.72 | 22.36 | 98978318.59 | 56.70 | 29.72 | 23.52 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8668600.14 | 807.11 | 19-JAN-19:04 | -3.3 | -3.9 | 92291219.02 | 56.69 | 03-JAN-04:19 | -3.3 | -3.9 |
February | 23441098.70 | 1329.12 | 20-FEB-09:03 | -6.2 | -7.9 | 83555847.03 | 56.69 | 28-FEB-04:19 | -15.6 | -16.0 |
March | 81957503.04 | 2685.50 | 26-MAR-08:61 | -0.9 | -2.8 | 93528198.54 | 56.69 | 31-MAR-22:10 | 4.43 | 0.70 |
April | 0.446341E+09 | 3032.82 | 13-APR-15:02 | 20.00 | 8.11 | 93086825.06 | 56.69 | 13-APR-21:30 | 12.50 | 6.57 |
May | 0.135687E+10 | 3176.12 | 25-MAY-18:02 | 29.03 | 19.14 | 98585801.55 | 56.69 | 24-MAY-21:19 | 29.03 | 19.14 |
June | 0.195138E+10 | 3221.18 | 29-JUN-15:02 | 34.50 | 24.13 | 95706221.97 | 56.70 | 29-JUN-22:40 | 26.30 | 23.57 |
July | 0.225482E+10 | 3205.75 | 21-JUL-15:02 | 29.50 | 22.27 | 98956459.46 | 56.70 | 13-JUL-21:30 | 29.50 | 22.27 |
August | 0.162689E+10 | 3197.57 | 25-AUG-15:02 | 28.30 | 19.24 | 98716343.28 | 56.69 | 23-AUG-01:00 | 28.30 | 19.24 |
September | 0.765903E+09 | 3079.42 | 01-SEP-15:02 | 26.10 | 17.79 | 94379381.24 | 56.69 | 01-SEP-23:10 | 13.72 | 12.99 |
October | 0.171968E+09 | 2952.73 | 01-OCT-08:61 | 6.23 | 5.55 | 94688063.83 | 56.69 | 22-OCT-03:20 | 9.07 | 7.89 |
November | 35876947.86 | 1543.68 | 14-NOV-19:03 | 4.72 | 3.06 | 89769973.65 | 56.69 | 01-NOV-02:20 | 4.72 | 3.06 |
December | 9101629.35 | 867.53 | 05-DEC-19:04 | 0.00 | -0.0 | 92215484.08 | 56.69 | 29-DEC-04:19 | -15.8 | -16.1 |
Annual Sum or Average | 0.873322E+10 | 0.112548E+10 | ||||||||
Minimum of Months | 8668600.14 | 807.11 | -6.2 | -7.9 | 83555847.03 | 56.69 | -15.8 | -16.1 | ||
Maximum of Months | 0.225482E+10 | 3221.18 | 34.50 | 24.13 | 98956459.46 | 56.70 | 29.50 | 23.57 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.300777E+09 | 1066.82 | 19-JAN-22:10 | -3.9 | -4.6 | 0.119878E+10 | 704.54 | 25-JAN-05:49 | -24.3 | -24.5 |
February | 0.105289E+10 | 2863.92 | 21-FEB-12:24 | 6.40 | 3.17 | 0.108591E+10 | 730.51 | 28-FEB-22:40 | -0.4 | -3.3 |
March | 0.211647E+10 | 2349.73 | 31-MAR-11:48 | 5.32 | 1.54 | 0.121788E+10 | 774.59 | 31-MAR-21:19 | 4.83 | 0.87 |
April | 0.363011E+10 | 3517.71 | 16-APR-21:25 | 4.15 | 0.67 | 0.125669E+10 | 862.11 | 23-APR-23:19 | 14.27 | 10.45 |
May | 0.478633E+10 | 3102.68 | 08-MAY-13:05 | 6.92 | 5.03 | 0.145833E+10 | 948.57 | 25-MAY-21:40 | 22.20 | 16.43 |
June | 0.503441E+10 | 3602.62 | 30-JUN-19:10 | 27.23 | 18.84 | 0.146327E+10 | 951.84 | 30-JUN-21:19 | 20.10 | 16.56 |
July | 0.551015E+10 | 3287.07 | 02-JUL-03:03 | 8.22 | 8.02 | 0.156435E+10 | 951.84 | 24-JUL-21:19 | 19.23 | 17.76 |
August | 0.519357E+10 | 3167.41 | 19-AUG-01:23 | 6.65 | 6.54 | 0.152380E+10 | 951.24 | 25-AUG-21:40 | 17.07 | 15.89 |
September | 0.444347E+10 | 3815.67 | 15-SEP-00:35 | 6.10 | 5.73 | 0.138435E+10 | 938.79 | 01-SEP-21:40 | 6.10 | 5.73 |
October | 0.345568E+10 | 3645.60 | 23-OCT-00:23 | 6.10 | 4.83 | 0.127873E+10 | 849.58 | 22-OCT-23:19 | 6.10 | 4.83 |
November | 0.173469E+10 | 2703.30 | 21-NOV-01:33 | 8.13 | 7.81 | 0.116341E+10 | 744.58 | 17-NOV-22:40 | 8.13 | 7.81 |
December | 0.281278E+09 | 1102.63 | 05-DEC-22:10 | 0.00 | -0.0 | 0.119883E+10 | 704.56 | 14-DEC-05:49 | -23.8 | -24.1 |
Annual Sum or Average | 0.375398E+11 | 0.157943E+11 | ||||||||
Minimum of Months | 0.281278E+09 | 1066.82 | -3.9 | -4.6 | 0.108591E+10 | 704.54 | -24.3 | -24.5 | ||
Maximum of Months | 0.551015E+10 | 3815.67 | 27.23 | 18.84 | 0.156435E+10 | 951.84 | 22.20 | 17.76 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11426034.94 | 1350.52 | 17-JAN-16:03 | -4.2 | -5.3 | 92349162.63 | 56.69 | 03-JAN-04:19 | -4.2 | -5.3 |
February | 72260151.45 | 3489.41 | 22-FEB-16:01 | -0.7 | -3.9 | 84165183.74 | 56.69 | 21-FEB-04:19 | -0.7 | -3.9 |
March | 0.214428E+09 | 3614.12 | 31-MAR-15:01 | 8.40 | 2.82 | 94200416.55 | 56.69 | 31-MAR-21:10 | 4.92 | 0.91 |
April | 0.652746E+09 | 3748.27 | 13-APR-15:02 | 20.00 | 8.11 | 92878839.70 | 56.69 | 13-APR-22:10 | 11.52 | 6.37 |
May | 0.161634E+10 | 3919.14 | 25-MAY-18:02 | 29.03 | 19.14 | 98282007.49 | 56.70 | 25-MAY-22:19 | 21.57 | 16.37 |
June | 0.191888E+10 | 3949.17 | 17-JUN-18:02 | 23.62 | 13.20 | 95330615.84 | 56.70 | 29-JUN-22:49 | 26.20 | 23.62 |
July | 0.242912E+10 | 3918.09 | 24-JUL-18:02 | 27.85 | 19.74 | 98707467.83 | 56.70 | 21-JUL-21:00 | 27.85 | 19.74 |
August | 0.191979E+10 | 3744.75 | 08-AUG-18:02 | 28.03 | 22.23 | 98449683.94 | 56.70 | 11-AUG-21:10 | 19.40 | 17.20 |
September | 0.976703E+09 | 3784.73 | 06-SEP-15:02 | 20.00 | 11.79 | 94341374.91 | 56.69 | 07-SEP-21:19 | 18.70 | 13.61 |
October | 0.339008E+09 | 3715.85 | 21-OCT-15:02 | 20.00 | 11.21 | 94978415.61 | 56.69 | 21-OCT-23:00 | 8.30 | 5.19 |
November | 43124464.56 | 3426.56 | 17-NOV-16:01 | 9.45 | 2.90 | 90104898.29 | 56.69 | 21-NOV-05:19 | 9.60 | 9.49 |
December | 8420781.80 | 473.15 | 24-DEC-08:61 | -31.1 | -31.3 | 92220902.67 | 56.69 | 29-DEC-04:19 | -15.8 | -16.1 |
Annual Sum or Average | 0.102022E+11 | 0.112601E+10 | ||||||||
Minimum of Months | 8420781.80 | 473.15 | -31.1 | -31.3 | 84165183.74 | 56.69 | -15.8 | -16.1 | ||
Maximum of Months | 0.242912E+10 | 3949.17 | 29.03 | 22.23 | 98707467.83 | 56.70 | 27.85 | 23.62 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4573328.69 | 542.94 | 17-JAN-16:04 | -4.2 | -5.3 | 92278792.34 | 56.69 | 14-JAN-05:10 | -4.2 | -5.3 |
February | 17583751.27 | 1612.66 | 04-FEB-19:03 | 4.22 | 0.37 | 83513757.32 | 56.69 | 28-FEB-04:19 | -15.6 | -16.0 |
March | 91749831.08 | 3374.44 | 28-MAR-18:01 | 6.93 | 2.56 | 93209381.16 | 56.69 | 31-MAR-21:10 | 4.92 | 0.91 |
April | 0.414359E+09 | 3487.40 | 13-APR-15:02 | 20.00 | 8.11 | 91987605.57 | 56.69 | 13-APR-21:10 | 13.03 | 6.68 |
May | 0.137418E+10 | 3742.96 | 25-MAY-18:02 | 29.03 | 19.14 | 98004837.24 | 56.70 | 25-MAY-22:19 | 21.57 | 16.37 |
June | 0.177283E+10 | 3764.70 | 17-JUN-18:02 | 23.62 | 13.20 | 95274243.06 | 56.70 | 29-JUN-22:00 | 26.10 | 23.67 |
July | 0.220331E+10 | 3731.43 | 24-JUL-18:02 | 27.85 | 19.74 | 98664009.21 | 56.70 | 03-JUL-21:30 | 27.85 | 19.74 |
August | 0.159387E+10 | 3598.07 | 08-AUG-18:02 | 28.03 | 22.23 | 98281575.17 | 56.69 | 08-AUG-21:10 | 22.62 | 18.95 |
September | 0.655771E+09 | 3524.78 | 06-SEP-15:02 | 20.00 | 11.79 | 93787354.21 | 56.69 | 01-SEP-22:49 | 20.00 | 11.79 |
October | 0.159568E+09 | 3435.07 | 21-OCT-15:02 | 20.00 | 11.21 | 94067390.26 | 56.69 | 22-OCT-03:20 | 9.07 | 7.89 |
November | 21826620.85 | 1745.42 | 15-NOV-19:03 | 4.32 | 1.54 | 89539456.55 | 56.69 | 21-NOV-05:19 | 9.60 | 9.49 |
December | 4432579.99 | 472.95 | 24-DEC-08:61 | -31.1 | -31.3 | 92203036.46 | 56.69 | 29-DEC-04:19 | -15.8 | -16.1 |
Annual Sum or Average | 0.831406E+10 | 0.112081E+10 | ||||||||
Minimum of Months | 4432579.99 | 472.95 | -31.1 | -31.3 | 83513757.32 | 56.69 | -15.8 | -16.1 | ||
Maximum of Months | 0.220331E+10 | 3764.70 | 29.03 | 22.23 | 98664009.21 | 56.70 | 27.85 | 23.67 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105133E+09 | 1938.37 | 27-JAN-16:01 | -14.8 | -15.9 | 93849009.86 | 56.69 | 10-JAN-04:19 | -14.8 | -15.9 |
February | 0.224607E+09 | 1972.10 | 08-FEB-16:01 | 4.22 | -1.0 | 86121794.74 | 56.69 | 21-FEB-00:20 | 2.60 | 0.75 |
March | 0.303963E+09 | 2014.55 | 31-MAR-15:01 | 8.40 | 2.82 | 95848740.72 | 56.69 | 31-MAR-21:10 | 4.92 | 0.91 |
April | 0.541889E+09 | 2083.04 | 13-APR-15:02 | 20.00 | 8.11 | 93822081.41 | 56.69 | 14-APR-21:10 | 8.72 | 5.04 |
May | 0.955607E+09 | 2123.46 | 21-MAY-15:02 | 22.73 | 11.45 | 98370633.86 | 56.70 | 25-MAY-21:00 | 21.90 | 16.42 |
June | 0.108677E+10 | 2101.59 | 17-JUN-18:02 | 23.62 | 13.20 | 95301698.42 | 56.70 | 29-JUN-22:40 | 26.30 | 23.57 |
July | 0.135994E+10 | 2072.23 | 24-JUL-18:02 | 27.85 | 19.74 | 98644756.78 | 56.70 | 03-JUL-21:19 | 27.85 | 19.74 |
August | 0.125258E+10 | 2147.77 | 25-AUG-15:02 | 28.30 | 19.24 | 98510102.31 | 56.70 | 11-AUG-21:30 | 28.30 | 19.24 |
September | 0.865210E+09 | 2135.64 | 01-SEP-15:02 | 26.10 | 17.79 | 94717853.12 | 56.70 | 01-SEP-22:10 | 13.90 | 13.22 |
October | 0.485040E+09 | 2098.72 | 21-OCT-15:02 | 20.00 | 11.21 | 96150612.28 | 56.69 | 18-OCT-21:19 | 20.00 | 11.21 |
November | 0.164940E+09 | 1974.51 | 16-NOV-16:01 | 5.73 | 1.01 | 91687106.93 | 56.69 | 01-NOV-02:20 | 5.73 | 1.01 |
December | 63962676.68 | 1890.36 | 02-DEC-16:01 | -18.7 | -19.4 | 93401842.06 | 56.69 | 22-DEC-04:19 | -15.3 | -15.8 |
Annual Sum or Average | 0.740964E+10 | 0.113643E+10 | ||||||||
Minimum of Months | 63962676.68 | 1890.36 | -18.7 | -19.4 | 86121794.74 | 56.69 | -15.3 | -15.9 | ||
Maximum of Months | 0.135994E+10 | 2147.77 | 28.30 | 19.74 | 98644756.78 | 56.70 | 28.30 | 23.57 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262411E+11 | 18085.65 | 27-JAN-23:55 | -27.8 | -28.0 | 0.168902E+11 | 11347.86 | 17-JAN-00:20 | -27.8 | -28.0 |
February | 0.249565E+11 | 17813.05 | 21-FEB-12:24 | 6.40 | 3.17 | 0.161300E+11 | 11347.87 | 06-FEB-00:20 | 6.40 | 3.17 |
March | 0.296153E+11 | 30064.41 | 31-MAR-20:19 | 5.40 | 1.17 | 0.186660E+11 | 11752.63 | 31-MAR-21:49 | 4.58 | 0.73 |
April | 0.326182E+11 | 40758.98 | 16-APR-21:25 | 4.15 | 0.67 | 0.185410E+11 | 13131.83 | 24-APR-22:10 | 4.90 | 2.90 |
May | 0.396258E+11 | 32487.78 | 02-MAY-23:25 | 7.25 | 3.33 | 0.193379E+11 | 13275.12 | 22-MAY-03:20 | 7.00 | 4.08 |
June | 0.408332E+11 | 31557.35 | 02-JUN-21:57 | 5.00 | 4.00 | 0.187632E+11 | 12308.70 | 15-JUN-04:00 | 8.30 | 7.74 |
July | 0.431790E+11 | 31426.58 | 07-JUL-23:59 | 7.80 | 7.48 | 0.193062E+11 | 12411.13 | 08-JUL-00:00 | 7.80 | 7.48 |
August | 0.413958E+11 | 32012.71 | 18-AUG-22:10 | 7.12 | 6.87 | 0.193725E+11 | 12559.54 | 19-AUG-01:00 | 6.10 | 5.88 |
September | 0.364890E+11 | 34402.89 | 28-SEP-01:50 | 7.20 | 5.55 | 0.186838E+11 | 13208.66 | 23-SEP-01:19 | 7.20 | 5.55 |
October | 0.334678E+11 | 31384.51 | 21-OCT-00:16 | 6.67 | 5.05 | 0.191591E+11 | 12969.41 | 20-OCT-04:10 | 6.67 | 5.05 |
November | 0.288697E+11 | 30642.82 | 20-NOV-23:30 | 7.80 | 7.24 | 0.181525E+11 | 12237.90 | 21-NOV-00:30 | 7.80 | 7.36 |
December | 0.266176E+11 | 16907.50 | 19-DEC-23:00 | -27.0 | -27.3 | 0.172517E+11 | 11347.86 | 05-DEC-04:19 | -27.0 | -27.3 |
Annual Sum or Average | 0.403909E+12 | 0.220254E+12 | ||||||||
Minimum of Months | 0.249565E+11 | 16907.50 | -27.8 | -28.0 | 0.161300E+11 | 11347.86 | -27.8 | -28.0 | ||
Maximum of Months | 0.431790E+11 | 40758.98 | 7.80 | 7.48 | 0.193725E+11 | 13275.12 | 8.30 | 7.74 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.291218E+11 | 19546.02 | 25-JAN-24:00 | -28.9 | -29.0 | 0.171823E+11 | 11347.93 | 30-JAN-00:20 | -4.0 | -4.5 |
February | 0.277737E+11 | 21063.62 | 04-FEB-18:53 | 4.40 | 0.51 | 0.164293E+11 | 11347.93 | 06-FEB-00:20 | -17.8 | -18.1 |
March | 0.331152E+11 | 31937.21 | 27-MAR-20:15 | 4.23 | 1.25 | 0.189087E+11 | 11835.01 | 31-MAR-21:49 | 4.58 | 0.73 |
April | 0.362583E+11 | 43049.07 | 16-APR-21:25 | 4.15 | 0.67 | 0.186521E+11 | 13235.72 | 24-APR-22:10 | 4.90 | 2.90 |
May | 0.430443E+11 | 34203.04 | 02-MAY-23:25 | 7.25 | 3.33 | 0.193672E+11 | 13337.44 | 22-MAY-03:20 | 7.00 | 4.08 |
June | 0.439853E+11 | 33285.66 | 02-JUN-22:22 | 5.00 | 4.11 | 0.187756E+11 | 12351.62 | 15-JUN-04:00 | 8.30 | 7.74 |
July | 0.461849E+11 | 32996.95 | 07-JUL-23:59 | 7.80 | 7.48 | 0.193131E+11 | 12455.85 | 08-JUL-00:00 | 7.80 | 7.48 |
August | 0.445272E+11 | 33779.43 | 18-AUG-22:10 | 7.12 | 6.87 | 0.193889E+11 | 12613.40 | 19-AUG-01:00 | 6.10 | 5.88 |
September | 0.398452E+11 | 37773.20 | 28-SEP-01:50 | 7.20 | 5.55 | 0.187319E+11 | 13295.54 | 23-SEP-01:19 | 7.20 | 5.55 |
October | 0.372435E+11 | 33548.57 | 21-OCT-00:16 | 6.67 | 5.05 | 0.192780E+11 | 13049.83 | 20-OCT-04:10 | 6.67 | 5.05 |
November | 0.323612E+11 | 33023.83 | 20-NOV-23:30 | 7.80 | 7.24 | 0.183780E+11 | 12348.95 | 21-NOV-00:30 | 7.80 | 7.36 |
December | 0.296375E+11 | 17912.79 | 19-DEC-23:00 | -27.0 | -27.3 | 0.175494E+11 | 11347.94 | 04-DEC-00:20 | -27.0 | -27.3 |
Annual Sum or Average | 0.443098E+12 | 0.221955E+12 | ||||||||
Minimum of Months | 0.277737E+11 | 17912.79 | -28.9 | -29.0 | 0.164293E+11 | 11347.93 | -27.0 | -27.3 | ||
Maximum of Months | 0.461849E+11 | 43049.07 | 7.80 | 7.48 | 0.193889E+11 | 13337.44 | 8.30 | 7.74 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.436818E+11 | 25005.09 | 21-JAN-11:50 | -10.6 | -11.1 | 0.186915E+11 | 11319.71 | 07-JAN-18:19 | -10.6 | -11.1 |
February | 0.414656E+11 | 38912.26 | 21-FEB-12:24 | 6.40 | 3.17 | 0.169391E+11 | 11409.17 | 04-FEB-18:40 | 6.40 | 3.17 |
March | 0.483046E+11 | 36434.10 | 31-MAR-11:44 | 5.32 | 1.54 | 0.187997E+11 | 11319.65 | 04-MAR-18:19 | 5.32 | 1.54 |
April | 0.504160E+11 | 37209.71 | 01-APR-10:45 | 4.90 | 2.53 | 0.182309E+11 | 11396.65 | 19-APR-15:00 | 7.20 | 1.06 |
May | 0.560043E+11 | 36596.81 | 08-MAY-13:05 | 6.92 | 5.03 | 0.188614E+11 | 11319.68 | 20-MAY-17:19 | 13.43 | 7.88 |
June | 0.561370E+11 | 34660.72 | 02-JUN-05:30 | 7.80 | 5.40 | 0.182574E+11 | 11319.67 | 24-JUN-17:19 | 29.03 | 22.25 |
July | 0.587194E+11 | 33725.16 | 18-JUL-05:10 | 8.27 | 7.95 | 0.188603E+11 | 11319.69 | 29-JUL-17:19 | 29.43 | 21.23 |
August | 0.572962E+11 | 34047.70 | 19-AUG-06:16 | 6.87 | 6.49 | 0.188650E+11 | 11319.68 | 12-AUG-17:19 | 6.87 | 6.49 |
September | 0.528483E+11 | 35436.96 | 25-SEP-07:07 | 6.38 | 5.77 | 0.182548E+11 | 11337.20 | 21-SEP-15:50 | 6.38 | 5.77 |
October | 0.510407E+11 | 37075.98 | 27-OCT-10:38 | 5.00 | 4.72 | 0.188534E+11 | 11431.19 | 07-OCT-17:49 | 5.00 | 4.72 |
November | 0.462687E+11 | 36816.87 | 18-NOV-11:43 | 4.82 | 1.42 | 0.181999E+11 | 11353.69 | 14-NOV-18:30 | 4.82 | 1.42 |
December | 0.438894E+11 | 25436.64 | 28-DEC-11:50 | -1.8 | -3.3 | 0.187237E+11 | 11319.71 | 02-DEC-18:19 | -1.8 | -3.3 |
Annual Sum or Average | 0.606072E+12 | 0.221537E+12 | ||||||||
Minimum of Months | 0.414656E+11 | 25005.09 | -10.6 | -11.1 | 0.169391E+11 | 11319.65 | -10.6 | -11.1 | ||
Maximum of Months | 0.587194E+11 | 38912.26 | 8.27 | 7.95 | 0.188650E+11 | 11431.19 | 29.43 | 22.25 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178740E+09 | 1522.48 | 27-JAN-13:50 | -14.6 | -15.8 | 0.126836E+10 | 745.80 | 25-JAN-05:49 | -14.6 | -15.8 |
February | 0.124663E+10 | 5804.26 | 21-FEB-12:24 | 6.40 | 3.17 | 0.114835E+10 | 745.93 | 28-FEB-22:19 | -0.2 | -3.1 |
March | 0.300955E+10 | 4824.24 | 31-MAR-11:48 | 5.32 | 1.54 | 0.128470E+10 | 810.42 | 31-MAR-21:19 | 4.83 | 0.87 |
April | 0.642873E+10 | 6871.58 | 16-APR-21:25 | 4.15 | 0.67 | 0.129823E+10 | 896.24 | 23-APR-23:10 | 14.63 | 10.70 |
May | 0.953742E+10 | 6177.51 | 08-MAY-13:05 | 6.92 | 5.03 | 0.151705E+10 | 1007.37 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.102548E+11 | 7141.81 | 30-JUN-13:20 | 31.50 | 24.23 | 0.153403E+10 | 1007.39 | 30-JUN-21:19 | 20.10 | 16.56 |
July | 0.112483E+11 | 6973.44 | 23-JUL-13:20 | 30.00 | 22.71 | 0.163239E+10 | 1007.40 | 24-JUL-21:19 | 19.23 | 17.76 |
August | 0.104601E+11 | 6128.89 | 19-AUG-01:23 | 6.65 | 6.54 | 0.159077E+10 | 1007.38 | 08-AUG-21:40 | 6.65 | 6.54 |
September | 0.867595E+10 | 7389.78 | 15-SEP-00:35 | 6.10 | 5.73 | 0.142157E+10 | 988.15 | 01-SEP-21:30 | 6.10 | 5.73 |
October | 0.639131E+10 | 7191.03 | 23-OCT-00:23 | 6.10 | 4.83 | 0.133211E+10 | 895.17 | 20-OCT-22:30 | 6.10 | 4.83 |
November | 0.270669E+10 | 5386.29 | 21-NOV-01:33 | 8.13 | 7.81 | 0.122997E+10 | 789.56 | 02-NOV-00:20 | 8.13 | 7.81 |
December | 0.154315E+09 | 1545.76 | 28-DEC-12:10 | -1.7 | -3.3 | 0.126880E+10 | 745.83 | 26-DEC-03:30 | -1.7 | -3.3 |
Annual Sum or Average | 0.702926E+11 | 0.165263E+11 | ||||||||
Minimum of Months | 0.154315E+09 | 1522.48 | -14.6 | -15.8 | 0.114835E+10 | 745.80 | -14.6 | -15.8 | ||
Maximum of Months | 0.112483E+11 | 7389.78 | 31.50 | 24.23 | 0.163239E+10 | 1007.40 | 21.73 | 17.76 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -21.9 |
February | 857562.29 | 1289.52 | 21-FEB-15:33 | 5.37 |
March | 673428.27 | 1230.30 | 26-MAR-10:55 | 4.40 |
April | 22078778.05 | 2558.26 | 24-APR-02:34 | 7.43 |
May | 23903482.04 | 1953.34 | 04-MAY-00:39 | 7.07 |
June | 6281959.47 | 1352.98 | 08-JUN-02:30 | 6.95 |
July | 1027218.70 | 1134.91 | 02-JUL-03:15 | 8.13 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 |
Annual Sum or Average | 54822428.82 | |||
Minimum of Months | 0.00 | 0.00 | -21.9 | |
Maximum of Months | 23903482.04 | 2558.26 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207657E+10 | 2144.43 | 04-JAN-08:10 | -29.4 |
February | 0.100552E+10 | 2107.78 | 17-FEB-07:40 | -29.6 |
March | 0.533092E+09 | 1947.11 | 05-MAR-06:50 | -28.6 |
April | 47531197.17 | 749.27 | 15-APR-06:20 | 5.60 |
May | 19121254.71 | 753.83 | 31-MAY-05:06 | 7.97 |
June | 8220611.94 | 702.42 | 02-JUN-23:50 | 6.83 |
July | 3809490.22 | 658.91 | 02-JUL-03:56 | 7.80 |
August | 2291159.69 | 740.11 | 19-AUG-01:04 | 7.02 |
September | 30474610.82 | 760.31 | 23-SEP-00:23 | 6.70 |
October | 59007361.36 | 765.01 | 16-OCT-06:54 | 5.60 |
November | 0.465959E+09 | 1634.39 | 25-NOV-07:10 | -19.2 |
December | 0.213261E+10 | 2227.70 | 26-DEC-08:02 | -26.3 |
Annual Sum or Average | 0.638421E+10 | |||
Minimum of Months | 2291159.69 | 658.91 | -29.6 | |
Maximum of Months | 0.213261E+10 | 2227.70 | 7.97 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 778049.50 | 232.65 | 06-JAN-10:35 | -29.1 |
February | 401531.45 | 191.24 | 21-FEB-15:33 | 5.37 |
March | 72506.94 | 160.94 | 26-MAR-10:55 | 4.40 |
April | 337272.25 | 193.54 | 06-APR-15:10 | 5.60 |
May | 107371.52 | 130.62 | 13-MAY-06:42 | 5.48 |
June | 13286.66 | 44.56 | 03-JUN-04:20 | 7.20 |
July | 1745.80 | 20.05 | 02-JUL-03:15 | 8.13 |
August | 33650.89 | 109.63 | 19-AUG-06:15 | 6.87 |
September | 650772.07 | 142.61 | 21-SEP-06:38 | 5.40 |
October | 2162701.41 | 249.56 | 16-OCT-08:54 | 5.60 |
November | 541031.20 | 248.40 | 20-NOV-09:45 | 5.82 |
December | 2809200.85 | 119.16 | 25-DEC-15:50 | -15.4 |
Annual Sum or Average | 7909120.53 | |||
Minimum of Months | 1745.80 | 20.05 | -29.1 | |
Maximum of Months | 2809200.85 | 249.56 | 8.13 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141331E+10 | 1443.01 | 06-JAN-03:10 | -33.1 |
February | 0.620518E+09 | 1040.07 | 14-FEB-05:00 | -32.2 |
March | 0.250238E+09 | 739.82 | 16-MAR-04:00 | -26.7 |
April | 2881925.82 | 305.80 | 06-APR-15:10 | 5.60 |
May | 2581598.59 | 216.95 | 03-MAY-00:07 | 6.45 |
June | 677321.81 | 144.06 | 03-JUN-04:20 | 7.20 |
July | 122210.16 | 105.84 | 10-JUL-03:23 | 7.80 |
August | 196643.50 | 145.44 | 19-AUG-06:15 | 6.87 |
September | 4101061.65 | 223.28 | 29-SEP-02:30 | 6.95 |
October | 9562279.39 | 335.38 | 30-OCT-23:59 | 7.20 |
November | 92056212.52 | 494.53 | 25-NOV-17:00 | -15.6 |
December | 0.112398E+10 | 1231.81 | 25-DEC-06:00 | -29.4 |
Annual Sum or Average | 0.352022E+10 | |||
Minimum of Months | 122210.16 | 105.84 | -33.1 | |
Maximum of Months | 0.141331E+10 | 1443.01 | 7.80 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141965E+10 | 1114.78 | 06-JAN-11:13 | -27.4 |
February | 0.738027E+09 | 820.67 | 14-FEB-05:00 | -32.2 |
March | 0.382963E+09 | 609.50 | 16-MAR-04:00 | -26.7 |
April | 14053209.41 | 170.08 | 05-APR-09:10 | -6.5 |
May | 1918075.24 | 120.93 | 03-MAY-00:07 | 6.45 |
June | 549680.05 | 83.04 | 03-JUN-04:20 | 7.20 |
July | 113044.35 | 63.88 | 10-JUL-03:23 | 7.80 |
August | 177227.40 | 88.70 | 19-AUG-06:15 | 6.87 |
September | 3137175.54 | 126.50 | 24-SEP-05:57 | 7.20 |
October | 7212550.35 | 178.70 | 16-OCT-06:54 | 5.60 |
November | 0.187355E+09 | 514.22 | 25-NOV-17:00 | -15.6 |
December | 0.122009E+10 | 967.08 | 25-DEC-06:00 | -29.4 |
Annual Sum or Average | 0.397524E+10 | |||
Minimum of Months | 113044.35 | 63.88 | -32.2 | |
Maximum of Months | 0.141965E+10 | 1114.78 | 7.80 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.3 |
April | 909275.91 | 1953.28 | 24-APR-02:34 | 7.43 |
May | 2715393.89 | 2236.74 | 15-MAY-02:13 | 6.97 |
June | 2349087.84 | 1947.20 | 03-JUN-04:20 | 7.20 |
July | 931802.17 | 1705.71 | 10-JUL-03:33 | 7.80 |
August | 114641.85 | 941.97 | 19-AUG-01:04 | 7.02 |
September | 3847284.81 | 2282.36 | 28-SEP-03:33 | 6.47 |
October | 2798242.37 | 2541.23 | 22-OCT-23:34 | 6.30 |
November | 141379.66 | 960.85 | 01-NOV-02:10 | 7.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 |
Annual Sum or Average | 13807108.49 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 3847284.81 | 2541.23 | 7.80 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 72476529.90 | 1893.19 | 23-JAN-09:03 | -22.1 |
February | 15949695.76 | 1404.83 | 02-FEB-10:30 | -23.0 |
March | 88430.56 | 86.13 | 16-MAR-09:30 | -15.6 |
April | 4165280.70 | 1647.87 | 15-APR-09:00 | 5.60 |
May | 3727064.18 | 1601.62 | 13-MAY-06:42 | 5.48 |
June | 78597.01 | 438.62 | 17-JUN-05:30 | 6.65 |
July | 219821.63 | 678.17 | 02-JUL-03:56 | 7.80 |
August | 371760.86 | 1502.27 | 19-AUG-06:15 | 6.87 |
September | 16030820.40 | 2064.15 | 21-SEP-06:38 | 5.40 |
October | 23680155.22 | 2728.22 | 16-OCT-08:54 | 5.60 |
November | 3035769.17 | 2319.17 | 20-NOV-09:45 | 5.82 |
December | 95876605.27 | 1597.46 | 26-DEC-08:02 | -26.3 |
Annual Sum or Average | 0.235701E+09 | |||
Minimum of Months | 78597.01 | 86.13 | -26.3 | |
Maximum of Months | 95876605.27 | 2728.22 | 7.80 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -21.9 |
February | 1215731.53 | 1852.40 | 21-FEB-15:33 | 5.37 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.3 |
April | 1662519.75 | 1971.35 | 08-APR-08:62 | 5.87 |
May | 133570.99 | 1248.82 | 13-MAY-06:42 | 5.48 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 37493.43 | 624.89 | 19-AUG-06:15 | 6.87 |
September | 989957.14 | 1587.91 | 21-SEP-06:38 | 5.40 |
October | 12329312.46 | 4428.40 | 16-OCT-08:54 | 5.60 |
November | 3656726.61 | 4429.69 | 20-NOV-09:45 | 5.82 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 |
Annual Sum or Average | 20025311.90 | |||
Minimum of Months | 0.00 | 0.00 | -21.9 | |
Maximum of Months | 12329312.46 | 4429.69 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.261704E+10 | 3493.23 | 12-JAN-19:01 | -22.3 |
February | 0.161760E+10 | 3475.95 | 02-FEB-16:01 | -15.1 |
March | 0.112981E+10 | 3449.46 | 15-MAR-08:61 | -22.3 |
April | 0.341147E+09 | 3405.32 | 04-APR-08:61 | -7.6 |
May | 15657519.70 | 2404.49 | 01-MAY-08:62 | 1.73 |
June | 2675098.55 | 820.97 | 11-JUN-08:03 | 10.78 |
July | 573732.12 | 689.19 | 09-JUL-08:04 | 13.40 |
August | 2662532.22 | 621.61 | 16-AUG-08:03 | 14.87 |
September | 25316714.36 | 2895.07 | 28-SEP-08:61 | 7.30 |
October | 0.401536E+09 | 3411.90 | 30-OCT-08:61 | -6.1 |
November | 0.120800E+10 | 3460.37 | 25-NOV-19:01 | -15.0 |
December | 0.259653E+10 | 3492.77 | 11-DEC-09:01 | -22.7 |
Annual Sum or Average | 0.995855E+10 | |||
Minimum of Months | 573732.12 | 621.61 | -22.7 | |
Maximum of Months | 0.261704E+10 | 3493.23 | 14.87 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.309063E+10 | 3466.22 | 07-JAN-09:01 | -20.4 |
February | 0.201019E+10 | 3453.71 | 02-FEB-16:01 | -15.1 |
March | 0.141792E+10 | 3441.83 | 15-MAR-08:61 | -22.3 |
April | 0.433331E+09 | 3386.73 | 05-APR-08:61 | -8.5 |
May | 20165641.84 | 2903.02 | 01-MAY-08:62 | 1.73 |
June | 2408698.65 | 795.65 | 02-JUN-08:03 | 11.20 |
July | 542987.48 | 694.92 | 15-JUL-08:04 | 22.07 |
August | 3071405.80 | 663.15 | 10-AUG-15:04 | 16.97 |
September | 31973134.55 | 3215.53 | 28-SEP-08:61 | 7.30 |
October | 0.494106E+09 | 3390.91 | 30-OCT-08:61 | -6.1 |
November | 0.142251E+10 | 3431.57 | 25-NOV-19:01 | -15.0 |
December | 0.295811E+10 | 3472.50 | 20-DEC-19:01 | -23.4 |
Annual Sum or Average | 0.118850E+11 | |||
Minimum of Months | 542987.48 | 663.15 | -23.4 | |
Maximum of Months | 0.309063E+10 | 3472.50 | 22.07 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.317365E+09 | 461.41 | 09-JAN-05:00 | -33.3 |
February | 0.124052E+09 | 400.88 | 17-FEB-06:00 | -31.7 |
March | 54033271.19 | 356.09 | 05-MAR-06:00 | -27.2 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 638680.08 | 42.39 | 30-OCT-05:00 | -10.0 |
November | 92707493.77 | 329.85 | 25-NOV-06:00 | -19.4 |
December | 0.357687E+09 | 450.37 | 24-DEC-06:00 | -31.1 |
Annual Sum or Average | 0.946483E+09 | |||
Minimum of Months | 0.00 | 0.00 | -33.3 | |
Maximum of Months | 0.357687E+09 | 461.41 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.673913E+09 | 984.68 | 06-JAN-16:01 | -22.4 |
February | 0.420353E+09 | 978.71 | 01-FEB-16:01 | -20.2 |
March | 0.263951E+09 | 974.23 | 06-MAR-16:01 | -10.1 |
April | 30606640.62 | 945.59 | 05-APR-08:61 | -8.5 |
May | 391767.81 | 257.43 | 07-MAY-15:04 | 17.08 |
June | 124645.36 | 220.94 | 02-JUN-08:05 | 11.20 |
July | 86108.54 | 181.31 | 08-JUL-18:06 | 13.90 |
August | 237670.66 | 264.41 | 07-AUG-08:05 | 14.50 |
September | 603004.21 | 285.20 | 10-SEP-15:04 | 16.70 |
October | 15080512.77 | 942.04 | 30-OCT-08:61 | -6.1 |
November | 0.194096E+09 | 976.62 | 25-NOV-16:01 | -14.2 |
December | 0.610170E+09 | 984.23 | 24-DEC-16:01 | -22.9 |
Annual Sum or Average | 0.220961E+10 | |||
Minimum of Months | 86108.54 | 181.31 | -22.9 | |
Maximum of Months | 0.673913E+09 | 984.68 | 17.08 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.260874E+10 | 3424.10 | 12-JAN-19:01 | -22.3 |
February | 0.161084E+10 | 3409.61 | 02-FEB-16:01 | -15.1 |
March | 0.111866E+10 | 3378.99 | 07-MAR-09:01 | -16.7 |
April | 0.326942E+09 | 3312.83 | 02-APR-08:61 | -5.5 |
May | 17111744.68 | 963.08 | 20-MAY-08:03 | 6.78 |
June | 864989.41 | 658.21 | 02-JUN-18:04 | 14.32 |
July | 228372.70 | 414.43 | 08-JUL-18:04 | 13.90 |
August | 2247105.35 | 679.65 | 31-AUG-18:04 | 24.82 |
September | 28586226.21 | 2734.13 | 28-SEP-08:61 | 7.30 |
October | 0.418576E+09 | 3298.23 | 29-OCT-18:01 | -3.0 |
November | 0.121409E+10 | 3394.54 | 25-NOV-19:01 | -15.0 |
December | 0.258078E+10 | 3423.43 | 18-DEC-16:01 | -23.2 |
Annual Sum or Average | 0.992767E+10 | |||
Minimum of Months | 228372.70 | 414.43 | -23.2 | |
Maximum of Months | 0.260874E+10 | 3424.10 | 24.82 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.309031E+10 | 3414.39 | 06-JAN-16:01 | -22.4 |
February | 0.201350E+10 | 3381.79 | 02-FEB-16:01 | -15.1 |
March | 0.140901E+10 | 3348.61 | 07-MAR-09:01 | -16.7 |
April | 0.408723E+09 | 3286.42 | 02-APR-08:61 | -5.5 |
May | 23299292.54 | 954.87 | 20-MAY-08:03 | 6.78 |
June | 869761.02 | 569.19 | 02-JUN-18:04 | 14.32 |
July | 275677.67 | 464.51 | 09-JUL-15:05 | 18.48 |
August | 2583300.14 | 644.36 | 31-AUG-18:04 | 24.82 |
September | 37700619.59 | 3013.05 | 28-SEP-08:61 | 7.30 |
October | 0.518068E+09 | 3280.95 | 30-OCT-08:61 | -6.1 |
November | 0.142236E+10 | 3371.03 | 25-NOV-16:01 | -14.2 |
December | 0.294735E+10 | 3413.75 | 24-DEC-16:01 | -22.9 |
Annual Sum or Average | 0.118741E+11 | |||
Minimum of Months | 275677.67 | 464.51 | -22.9 | |
Maximum of Months | 0.309031E+10 | 3414.39 | 24.82 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.854541E+09 | 1446.02 | 05-JAN-07:05 | -32.2 |
February | 0.228409E+09 | 1065.01 | 17-FEB-07:10 | -30.7 |
March | 68166773.46 | 620.18 | 07-MAR-09:03 | -16.7 |
April | 3513739.74 | 546.59 | 08-APR-08:62 | 5.87 |
May | 3350278.22 | 325.71 | 13-MAY-06:49 | 5.48 |
June | 773051.14 | 207.48 | 03-JUN-04:20 | 7.20 |
July | 98747.00 | 125.25 | 10-JUL-03:23 | 7.80 |
August | 525761.52 | 305.99 | 19-AUG-06:15 | 6.87 |
September | 10948632.69 | 495.37 | 21-SEP-06:38 | 5.40 |
October | 21091980.30 | 687.57 | 16-OCT-06:54 | 5.60 |
November | 0.100047E+09 | 766.77 | 25-NOV-17:00 | -15.6 |
December | 0.840920E+09 | 1376.35 | 25-DEC-16:00 | -15.4 |
Annual Sum or Average | 0.213239E+10 | |||
Minimum of Months | 98747.00 | 125.25 | -32.2 | |
Maximum of Months | 0.854541E+09 | 1446.02 | 7.80 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.354927E+10 | 4096.29 | 12-JAN-19:01 | -22.3 |
February | 0.226729E+10 | 4076.08 | 15-FEB-09:01 | -21.0 |
March | 0.164326E+10 | 4044.26 | 15-MAR-08:61 | -22.3 |
April | 0.587774E+09 | 3972.52 | 04-APR-08:61 | -7.6 |
May | 51875712.93 | 3508.92 | 01-MAY-08:62 | 1.73 |
June | 9336539.76 | 867.91 | 03-JUN-18:03 | 14.32 |
July | 1017368.97 | 762.13 | 08-JUL-08:04 | 13.90 |
August | 10102188.10 | 794.89 | 07-AUG-08:03 | 14.50 |
September | 90813566.67 | 3844.17 | 28-SEP-08:61 | 7.30 |
October | 0.700189E+09 | 3984.43 | 30-OCT-08:61 | -6.1 |
November | 0.174539E+10 | 4056.84 | 25-NOV-19:01 | -15.0 |
December | 0.350858E+10 | 4095.91 | 11-DEC-09:01 | -22.7 |
Annual Sum or Average | 0.141649E+11 | |||
Minimum of Months | 1017368.97 | 762.13 | -22.7 | |
Maximum of Months | 0.354927E+10 | 4096.29 | 14.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.409110E+10 | 4050.52 | 07-JAN-09:01 | -20.4 |
February | 0.274384E+10 | 4036.50 | 02-FEB-16:01 | -15.1 |
March | 0.200902E+10 | 4022.07 | 15-MAR-08:61 | -22.3 |
April | 0.722667E+09 | 3936.81 | 05-APR-08:61 | -8.5 |
May | 64322098.36 | 3738.08 | 01-MAY-08:62 | 1.73 |
June | 8863047.99 | 864.68 | 03-JUN-18:03 | 14.32 |
July | 1048989.94 | 738.49 | 22-JUL-08:04 | 22.12 |
August | 10931824.08 | 788.61 | 27-AUG-08:03 | 13.48 |
September | 0.122185E+09 | 3797.93 | 28-SEP-08:61 | 7.30 |
October | 0.851671E+09 | 3954.04 | 30-OCT-08:61 | -6.1 |
November | 0.201680E+10 | 4010.65 | 25-NOV-19:01 | -15.0 |
December | 0.391958E+10 | 4061.92 | 20-DEC-19:01 | -23.4 |
Annual Sum or Average | 0.165620E+11 | |||
Minimum of Months | 1048989.94 | 738.49 | -23.4 | |
Maximum of Months | 0.409110E+10 | 4061.92 | 22.12 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126493E+10 | 2169.30 | 12-JAN-19:01 | -22.3 |
February | 0.733102E+09 | 2154.50 | 02-FEB-16:01 | -15.1 |
March | 0.517084E+09 | 2143.91 | 07-MAR-09:01 | -16.7 |
April | 0.161251E+09 | 2105.87 | 04-APR-08:61 | -7.6 |
May | 10057897.77 | 807.84 | 01-MAY-08:62 | 1.73 |
June | 2251703.56 | 531.19 | 29-JUN-08:04 | 23.48 |
July | 550552.22 | 442.16 | 25-JUL-08:04 | 24.18 |
August | 1452108.69 | 474.40 | 19-AUG-08:03 | 12.77 |
September | 9598218.69 | 1603.11 | 28-SEP-08:61 | 7.30 |
October | 0.174991E+09 | 2116.25 | 30-OCT-08:61 | -6.1 |
November | 0.561568E+09 | 2151.53 | 25-NOV-19:01 | -15.0 |
December | 0.130900E+10 | 2170.20 | 13-DEC-16:01 | -10.3 |
Annual Sum or Average | 0.474584E+10 | |||
Minimum of Months | 550552.22 | 442.16 | -22.3 | |
Maximum of Months | 0.130900E+10 | 2170.20 | 24.18 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 13592.31 | 203.88 | 16-OCT-08:54 | 5.60 |
November | 12209.80 | 203.50 | 20-NOV-09:45 | 5.82 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 |
Annual Sum or Average | 25802.11 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 13592.31 | 203.88 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.00 | 0.00 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 35081.72 | 584.70 | 22-OCT-23:34 | 6.30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 |
Annual Sum or Average | 35081.72 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 35081.72 | 584.70 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.489293E+10 | 5465.50 | 09-JAN-06:04 | -31.8 |
February | 0.209317E+10 | 4775.58 | 17-FEB-07:10 | -30.7 |
March | 0.767760E+09 | 3667.85 | 05-MAR-06:50 | -28.6 |
April | 18905403.90 | 1084.04 | 08-APR-08:62 | 5.87 |
May | 12028917.64 | 901.11 | 13-MAY-06:42 | 5.48 |
June | 3650698.88 | 654.59 | 03-JUN-04:20 | 7.20 |
July | 1078216.77 | 486.28 | 10-JUL-03:23 | 7.80 |
August | 1766454.68 | 901.32 | 19-AUG-06:15 | 6.87 |
September | 31609423.60 | 1182.73 | 21-SEP-06:38 | 5.40 |
October | 56988980.83 | 1376.48 | 16-OCT-06:54 | 5.60 |
November | 0.485871E+09 | 2486.88 | 25-NOV-07:20 | -19.0 |
December | 0.431949E+10 | 5147.43 | 25-DEC-05:50 | -29.5 |
Annual Sum or Average | 0.126852E+11 | |||
Minimum of Months | 1078216.77 | 486.28 | -31.8 | |
Maximum of Months | 0.489293E+10 | 5465.50 | 7.80 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.147273E+11 | 14185.34 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.132974E+11 | 14185.34 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.147727E+11 | 14185.34 | 01-MAR-20:10 | 0.127855E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.142280E+11 | 14185.34 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.147528E+11 | 14185.34 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.142932E+11 | 14185.34 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.146876E+11 | 14185.34 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.147784E+11 | 14185.34 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.142337E+11 | 14185.34 | 01-SEP-19:10 | 0.123352E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.147216E+11 | 14185.34 | 02-OCT-19:10 | 0.127549E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.142819E+11 | 14185.34 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.146876E+11 | 14185.34 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.173462E+12 | 0.150255E+12 | ||||
Minimum of Months | 0.132974E+11 | 14185.34 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.147784E+11 | 14185.34 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.731324E+09 | 704.41 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.660319E+09 | 704.41 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.733578E+09 | 704.41 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.706528E+09 | 704.41 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.732592E+09 | 704.41 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.709769E+09 | 704.41 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.729351E+09 | 704.41 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.733860E+09 | 704.41 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.706810E+09 | 704.41 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.731042E+09 | 704.41 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.709205E+09 | 704.41 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.729351E+09 | 704.41 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.861373E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.660319E+09 | 704.41 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.733860E+09 | 704.41 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.846876E+09 | 815.72 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.764651E+09 | 815.72 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.849486E+09 | 815.72 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.818162E+09 | 815.72 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.848344E+09 | 815.72 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.821915E+09 | 815.72 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.844592E+09 | 815.72 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.849812E+09 | 815.72 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.818489E+09 | 815.72 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.846549E+09 | 815.72 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.821262E+09 | 815.72 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.844592E+09 | 815.72 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.997473E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.764651E+09 | 815.72 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.849812E+09 | 815.72 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.141236E+10 | 1360.40 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.127524E+10 | 1360.40 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.141672E+10 | 1360.40 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.136448E+10 | 1360.40 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.141481E+10 | 1360.40 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.137074E+10 | 1360.40 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.140855E+10 | 1360.40 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.141726E+10 | 1360.40 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.136502E+10 | 1360.40 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.141182E+10 | 1360.40 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.136965E+10 | 1360.40 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.140855E+10 | 1360.40 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.166352E+11 | 0.124712E+11 | ||||
Minimum of Months | 0.127524E+10 | 1360.40 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.141726E+10 | 1360.40 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.236418E+09 | 227.72 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.213464E+09 | 227.72 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.237147E+09 | 227.72 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.228402E+09 | 227.72 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.236828E+09 | 227.72 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.229450E+09 | 227.72 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.235780E+09 | 227.72 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.237238E+09 | 227.72 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.228493E+09 | 227.72 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.236327E+09 | 227.72 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.229268E+09 | 227.72 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.235780E+09 | 227.72 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.278459E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.213464E+09 | 227.72 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.237238E+09 | 227.72 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.370859E+09 | 357.21 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.334852E+09 | 357.21 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.372002E+09 | 357.21 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.358285E+09 | 357.21 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.371502E+09 | 357.21 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.359929E+09 | 357.21 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.369859E+09 | 357.21 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.372145E+09 | 357.21 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.358428E+09 | 357.21 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.370717E+09 | 357.21 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.359643E+09 | 357.21 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.369859E+09 | 357.21 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.436808E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.334852E+09 | 357.21 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.372145E+09 | 357.21 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.163250E+10 | 1761.91 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.143724E+10 | 1761.91 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.154555E+10 | 1761.91 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.141557E+10 | 1761.91 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.139829E+10 | 1761.91 | 01-MAY-19:19 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.131777E+10 | 1761.91 | 01-JUN-19:40 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.137130E+10 | 1761.91 | 07-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.145178E+10 | 1761.91 | 01-AUG-19:30 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.146247E+10 | 1761.91 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.158064E+10 | 1761.91 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.156840E+10 | 1761.91 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.163571E+10 | 1761.91 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.178172E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.131777E+10 | 1761.91 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.163571E+10 | 1761.91 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104561E+11 | 10265.18 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.940270E+10 | 10265.18 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.103987E+11 | 10265.18 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.994463E+10 | 10265.18 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.102379E+11 | 10265.18 | 01-MAY-19:19 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.988474E+10 | 10265.18 | 01-JUN-19:40 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.101725E+11 | 10265.18 | 07-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.103077E+11 | 10265.18 | 01-AUG-19:30 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.999273E+10 | 10265.18 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.104021E+11 | 10265.18 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.101253E+11 | 10265.18 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.104371E+11 | 10265.18 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.121762E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.940270E+10 | 10265.18 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.104561E+11 | 10265.18 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85091918.49 | 76.99 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 76846309.13 | 76.99 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 84415649.14 | 76.99 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 82445007.08 | 76.99 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 84753783.81 | 76.99 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 81790910.76 | 76.99 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 85418966.65 | 76.99 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 84415649.14 | 76.99 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 82467180.11 | 76.99 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 85080831.98 | 76.99 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 82117958.92 | 76.99 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 85430053.17 | 76.99 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.100027E+10 | 0.300992E+10 | ||||
Minimum of Months | 76846309.13 | 76.99 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 85430053.17 | 76.99 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85115186.72 | 77.01 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 76867322.62 | 77.01 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 84438732.44 | 77.01 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 82467551.52 | 77.01 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 84776959.58 | 77.01 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 81813276.33 | 77.01 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 85442324.32 | 77.01 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 84438732.44 | 77.01 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 82489730.61 | 77.01 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 85104097.18 | 77.01 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 82140413.93 | 77.01 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 85453413.86 | 77.01 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.100055E+10 | 0.301074E+10 | ||||
Minimum of Months | 76867322.62 | 77.01 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 85453413.86 | 77.01 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.232638E+10 | 2240.78 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.210051E+10 | 2240.78 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.233355E+10 | 2240.78 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.224750E+10 | 2240.78 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.233041E+10 | 2240.78 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.225781E+10 | 2240.78 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.232011E+10 | 2240.78 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.233445E+10 | 2240.78 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.224840E+10 | 2240.78 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.232548E+10 | 2240.78 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.225602E+10 | 2240.78 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.232011E+10 | 2240.78 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.274007E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.210051E+10 | 2240.78 | 0.00 | 0.00 | |
Maximum of Months | 0.233445E+10 | 2240.78 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85115186.72 | 77.01 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 76867322.62 | 77.01 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 84438732.44 | 77.01 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 82467551.52 | 77.01 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 84776959.58 | 77.01 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 81813276.33 | 77.01 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 85442324.32 | 77.01 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 84438732.44 | 77.01 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 82489730.61 | 77.01 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 85104097.18 | 77.01 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 82140413.93 | 77.01 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 85453413.86 | 77.01 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.100055E+10 | 0.301074E+10 | ||||
Minimum of Months | 76867322.62 | 77.01 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 85453413.86 | 77.01 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.305140E+10 | 3094.06 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.271838E+10 | 3094.06 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.297058E+10 | 3094.06 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.278795E+10 | 3094.06 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.281844E+10 | 3094.06 | 01-MAY-19:30 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.269458E+10 | 3094.06 | 01-JUN-19:49 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.278563E+10 | 3094.06 | 07-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.287557E+10 | 3094.06 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.283510E+10 | 3094.06 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.299846E+10 | 3094.06 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.294420E+10 | 3094.06 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.305057E+10 | 3094.06 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.345309E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.269458E+10 | 3094.06 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.305140E+10 | 3094.06 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.305140E+10 | 3094.06 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.271838E+10 | 3094.06 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.297058E+10 | 3094.06 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.278795E+10 | 3094.06 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.281844E+10 | 3094.06 | 01-MAY-19:30 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.269458E+10 | 3094.06 | 01-JUN-19:49 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.278563E+10 | 3094.06 | 07-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.287557E+10 | 3094.06 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.283510E+10 | 3094.06 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.299846E+10 | 3094.06 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.294420E+10 | 3094.06 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.305057E+10 | 3094.06 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.345309E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.269458E+10 | 3094.06 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.305140E+10 | 3094.06 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113146E+10 | 1089.83 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.102161E+10 | 1089.83 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.113495E+10 | 1089.83 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.109310E+10 | 1089.83 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.113342E+10 | 1089.83 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.109811E+10 | 1089.83 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.112841E+10 | 1089.83 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.113539E+10 | 1089.83 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.109354E+10 | 1089.83 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.113103E+10 | 1089.83 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.109724E+10 | 1089.83 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.112841E+10 | 1089.83 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.133267E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.102161E+10 | 1089.83 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.113539E+10 | 1089.83 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.246211E+10 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.222306E+10 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.246970E+10 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.237864E+10 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.246638E+10 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.238954E+10 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.245547E+10 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.247065E+10 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.237958E+10 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.246116E+10 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.238765E+10 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.245547E+10 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.289994E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.222306E+10 | 2371.52 | 0.00 | 0.00 | |
Maximum of Months | 0.247065E+10 | 2371.52 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.147273E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.132974E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.147727E+11 | 0.127855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.142280E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.147528E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.142932E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.146876E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.147784E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.142337E+11 | 0.123352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.147216E+11 | 0.127549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.142819E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.146876E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.173462E+12 | 0.150255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.132974E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.147784E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.731324E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133841E+10 |
February | 0.179968E+10 | 0.660319E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102690E+10 |
March | 0.199990E+10 | 0.733578E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.930142E+09 |
April | 0.192973E+10 | 0.706528E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 437967.75 | 0.555494E+09 |
May | 0.199475E+10 | 0.732592E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6306161.58 | 0.275571E+09 |
June | 0.193394E+10 | 0.709769E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17899870.20 | 0.140921E+09 |
July | 0.199054E+10 | 0.729351E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22314805.37 | 0.109802E+09 |
August | 0.199896E+10 | 0.733860E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7572547.89 | 0.142403E+09 |
September | 0.192879E+10 | 0.706810E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 287790.43 | 0.292270E+09 |
October | 0.199148E+10 | 0.731042E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519080E+09 |
November | 0.192552E+10 | 0.709205E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742948E+09 |
December | 0.199054E+10 | 0.729351E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125258E+10 |
Annual Sum or Average | 0.234744E+11 | 0.861373E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54819143.22 | 0.732653E+10 |
Minimum of Months | 0.179968E+10 | 0.660319E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109802E+09 |
Maximum of Months | 0.199990E+10 | 0.733860E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22314805.37 | 0.133841E+10 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.846876E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517241E+09 |
February | 0.208403E+10 | 0.764651E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397246E+09 |
March | 0.231589E+10 | 0.849486E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363405E+09 |
April | 0.223463E+10 | 0.818162E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 191500.71 | 0.224824E+09 |
May | 0.230993E+10 | 0.848344E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2536580.57 | 0.121865E+09 |
June | 0.223950E+10 | 0.821915E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6555790.79 | 68428816.51 |
July | 0.230505E+10 | 0.844592E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8358572.16 | 55352051.64 |
August | 0.231480E+10 | 0.849812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3202436.67 | 69522016.18 |
September | 0.223354E+10 | 0.818489E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 170094.70 | 0.128647E+09 |
October | 0.230614E+10 | 0.846549E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213961E+09 |
November | 0.222975E+10 | 0.821262E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293052E+09 |
December | 0.230505E+10 | 0.844592E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484547E+09 |
Annual Sum or Average | 0.271834E+11 | 0.997473E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21014975.60 | 0.293809E+10 |
Minimum of Months | 0.208403E+10 | 0.764651E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55352051.64 |
Maximum of Months | 0.231589E+10 | 0.849812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8358572.16 | 0.517241E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.141236E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121961E+10 |
February | 0.440737E+09 | 0.127524E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929739E+09 |
March | 0.489771E+09 | 0.141672E+10 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840729E+09 |
April | 0.472586E+09 | 0.136448E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 686476.13 | 0.504399E+09 |
May | 0.488511E+09 | 0.141481E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6863618.57 | 0.273362E+09 |
June | 0.473617E+09 | 0.137074E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15612962.44 | 0.155857E+09 |
July | 0.487480E+09 | 0.140855E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19821532.20 | 0.128243E+09 |
August | 0.489542E+09 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8232975.83 | 0.158828E+09 |
September | 0.472357E+09 | 0.136502E+10 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 535606.04 | 0.291066E+09 |
October | 0.487709E+09 | 0.141182E+10 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 302.35 | 0.482045E+09 |
November | 0.471555E+09 | 0.136965E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675450E+09 |
December | 0.487480E+09 | 0.140855E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114153E+10 |
Annual Sum or Average | 0.574883E+10 | 0.166352E+11 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51753473.56 | 0.680086E+10 |
Minimum of Months | 0.440737E+09 | 0.127524E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128243E+09 |
Maximum of Months | 0.489771E+09 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19821532.20 | 0.121961E+10 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.236418E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703541E+09 |
February | 0.339028E+09 | 0.213464E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536231E+09 |
March | 0.376747E+09 | 0.237147E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484383E+09 |
April | 0.363528E+09 | 0.228402E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 406885.28 | 0.288071E+09 |
May | 0.375778E+09 | 0.236828E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4128056.89 | 0.153816E+09 |
June | 0.364321E+09 | 0.229450E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9266743.84 | 86782466.05 |
July | 0.374985E+09 | 0.235780E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11855988.43 | 71330871.25 |
August | 0.376571E+09 | 0.237238E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4957962.38 | 88162511.87 |
September | 0.363352E+09 | 0.228493E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 330213.42 | 0.163550E+09 |
October | 0.375161E+09 | 0.236327E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 392.92 | 0.273890E+09 |
November | 0.362735E+09 | 0.229268E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388557E+09 |
December | 0.374985E+09 | 0.235780E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658591E+09 |
Annual Sum or Average | 0.442217E+10 | 0.278459E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30946243.16 | 0.389691E+10 |
Minimum of Months | 0.339028E+09 | 0.213464E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71330871.25 |
Maximum of Months | 0.376747E+09 | 0.237238E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11855988.43 | 0.703541E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.370859E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171852E+10 |
February | 0.139600E+10 | 0.334852E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133352E+10 |
March | 0.155131E+10 | 0.372002E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122653E+10 |
April | 0.149688E+10 | 0.358285E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 722810.52 | 0.753956E+09 |
May | 0.154732E+10 | 0.371502E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 8903115.61 | 0.396132E+09 |
June | 0.150015E+10 | 0.359929E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 23497037.42 | 0.219571E+09 |
July | 0.154405E+10 | 0.369859E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 30648532.65 | 0.168805E+09 |
August | 0.155059E+10 | 0.372145E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 12787305.31 | 0.216432E+09 |
September | 0.149615E+10 | 0.358428E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 824506.46 | 0.419895E+09 |
October | 0.154478E+10 | 0.370717E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720997E+09 |
November | 0.149361E+10 | 0.359643E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998964E+09 |
December | 0.154405E+10 | 0.369859E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162076E+10 |
Annual Sum or Average | 0.182090E+11 | 0.436808E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 77383307.98 | 0.979407E+10 |
Minimum of Months | 0.139600E+10 | 0.334852E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168805E+09 |
Maximum of Months | 0.155131E+10 | 0.372145E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 30648532.65 | 0.171852E+10 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.163250E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296746E+10 |
February | 0.236489E+11 | 0.143724E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229102E+10 |
March | 0.262800E+11 | 0.154555E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209497E+10 |
April | 0.253579E+11 | 0.141557E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 873854.42 | 0.128495E+10 |
May | 0.262123E+11 | 0.139829E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12633693.68 | 0.683490E+09 |
June | 0.254132E+11 | 0.131777E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36029485.28 | 0.377730E+09 |
July | 0.261570E+11 | 0.137130E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45534344.24 | 0.301985E+09 |
August | 0.262677E+11 | 0.145178E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15451110.09 | 0.382935E+09 |
September | 0.253456E+11 | 0.146247E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 606975.05 | 0.721708E+09 |
October | 0.261693E+11 | 0.158064E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120814E+10 |
November | 0.253025E+11 | 0.156840E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167263E+10 |
December | 0.261570E+11 | 0.163571E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277514E+10 |
Annual Sum or Average | 0.308468E+12 | 0.178172E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111129E+09 | 0.167622E+11 |
Minimum of Months | 0.236489E+11 | 0.131777E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301985E+09 |
Maximum of Months | 0.262800E+11 | 0.163571E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45534344.24 | 0.296746E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.104561E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.852066E+10 |
February | 0.702046E+11 | 0.940270E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659506E+10 |
March | 0.780153E+11 | 0.103987E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606343E+10 |
April | 0.752779E+11 | 0.994463E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2744012.97 | 0.377768E+10 |
May | 0.778146E+11 | 0.102379E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37681498.73 | 0.205207E+10 |
June | 0.754422E+11 | 0.988474E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101272E+09 | 0.116433E+10 |
July | 0.776503E+11 | 0.101725E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128053E+09 | 0.927846E+09 |
August | 0.779788E+11 | 0.103077E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45260970.99 | 0.117507E+10 |
September | 0.752414E+11 | 0.999273E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1721446.88 | 0.217686E+10 |
October | 0.776868E+11 | 0.104021E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360426E+10 |
November | 0.751137E+11 | 0.101253E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490787E+10 |
December | 0.776503E+11 | 0.104371E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.799288E+10 |
Annual Sum or Average | 0.915726E+12 | 0.121762E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316734E+09 | 0.489580E+11 |
Minimum of Months | 0.702046E+11 | 0.940270E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.927846E+09 |
Maximum of Months | 0.780153E+11 | 0.104561E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128053E+09 | 0.852066E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767234E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587823E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532814E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 435878.89 | 0.318193E+09 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5386906.22 | 0.157448E+09 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14322281.39 | 79709863.19 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18404786.59 | 56866770.40 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7767764.12 | 75959195.15 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 494404.40 | 0.165218E+09 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16307.43 | 0.295832E+09 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424352E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717084E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46828329.04 | 0.417853E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56866770.40 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18404786.59 | 0.767234E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766192E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583902E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527910E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 437628.27 | 0.314505E+09 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5420680.46 | 0.156423E+09 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14369912.90 | 79484253.15 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18497876.03 | 56776485.44 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7856388.10 | 75487548.43 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 516590.10 | 0.163512E+09 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17492.20 | 0.292679E+09 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421126E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716523E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47116568.05 | 0.415452E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56776485.44 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18497876.03 | 0.766192E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 85091918.49 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206469E+09 |
February | 0.00 | 76846309.13 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160041E+09 |
March | 0.00 | 84415649.14 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146619E+09 |
April | 0.00 | 82445007.08 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72140.11 | 92028061.39 |
May | 0.00 | 84753783.81 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1027075.88 | 50817778.93 |
June | 0.00 | 81790910.76 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2786933.32 | 28374847.00 |
July | 0.00 | 85418966.65 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3549628.54 | 22136048.30 |
August | 0.00 | 84415649.14 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1370707.67 | 28414289.82 |
September | 0.00 | 82467180.11 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77361.38 | 53222549.04 |
October | 0.00 | 85080831.98 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84636877.92 |
November | 0.00 | 82117958.92 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113946E+09 |
December | 0.00 | 85430053.17 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191972E+09 |
Annual Sum or Average | 0.00 | 0.100027E+10 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8883846.89 | 0.117868E+10 |
Minimum of Months | 0.00 | 76846309.13 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22136048.30 |
Maximum of Months | 0.00 | 85430053.17 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3549628.54 | 0.206469E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 85115186.72 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214297E+09 |
February | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163491E+09 |
March | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147992E+09 |
April | 0.293479E+09 | 82467551.52 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 148935.41 | 87881568.46 |
May | 0.303504E+09 | 84776959.58 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1728286.46 | 42970796.06 |
June | 0.293842E+09 | 81813276.33 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4264936.60 | 21661211.68 |
July | 0.303141E+09 | 85442324.32 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5572189.14 | 15390924.15 |
August | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2561904.41 | 20435376.76 |
September | 0.293479E+09 | 82489730.61 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 215699.29 | 45071812.43 |
October | 0.303322E+09 | 85104097.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12261.62 | 82360589.24 |
November | 0.293661E+09 | 82140413.93 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118670E+09 |
December | 0.303141E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200487E+09 |
Annual Sum or Average | 0.357224E+10 | 0.100055E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14504212.93 | 0.116071E+10 |
Minimum of Months | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15390924.15 |
Maximum of Months | 0.303685E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5572189.14 | 0.214297E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767006E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587749E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534445E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 444954.86 | 0.320267E+09 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5412133.37 | 0.158328E+09 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14331664.06 | 80518033.80 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18404148.40 | 57319366.46 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7805515.51 | 76461342.92 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 500762.03 | 0.165595E+09 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17332.29 | 0.296136E+09 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424053E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716966E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46916510.52 | 0.418484E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57319366.46 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18404148.40 | 0.767006E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766217E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583690E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529109E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 449736.39 | 0.317743E+09 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5424526.19 | 0.157905E+09 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14339820.96 | 80462990.05 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18422973.46 | 57268180.73 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7838695.93 | 76233720.18 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 504840.52 | 0.164607E+09 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18191.82 | 0.293159E+09 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421032E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716557E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46998785.27 | 0.416398E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57268180.73 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18422973.46 | 0.766217E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.232638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939373E+09 |
February | 0.348285E+10 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716383E+09 |
March | 0.387034E+10 | 0.233355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648787E+09 |
April | 0.373454E+10 | 0.224750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385805.02 | 0.393863E+09 |
May | 0.386038E+10 | 0.233041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4502671.33 | 0.214803E+09 |
June | 0.374269E+10 | 0.225781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11070408.39 | 0.122146E+09 |
July | 0.385223E+10 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13614851.92 | 0.100802E+09 |
August | 0.386853E+10 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5516601.97 | 0.123048E+09 |
September | 0.373273E+10 | 0.224840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268954.33 | 0.223639E+09 |
October | 0.385404E+10 | 0.232548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368203E+09 |
November | 0.372639E+10 | 0.225602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519293E+09 |
December | 0.385223E+10 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.879283E+09 |
Annual Sum or Average | 0.454292E+11 | 0.274007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35359292.95 | 0.524962E+10 |
Minimum of Months | 0.348285E+10 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100802E+09 |
Maximum of Months | 0.387034E+10 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13614851.92 | 0.939373E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767897E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587415E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532377E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 425838.85 | 0.317787E+09 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5259035.12 | 0.157871E+09 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14061028.09 | 80121406.23 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18059020.39 | 57306598.90 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7568517.10 | 76319790.83 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 472039.35 | 0.165253E+09 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14482.43 | 0.295079E+09 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423925E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717989E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45859961.33 | 0.417934E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57306598.90 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18059020.39 | 0.767897E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767462E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584525E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528164E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 428021.27 | 0.313948E+09 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5295053.45 | 0.156792E+09 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14104411.83 | 79904544.41 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18143417.58 | 57193270.61 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7664369.14 | 75797578.42 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 499433.84 | 0.163216E+09 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15954.55 | 0.291627E+09 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421289E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717789E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46150661.65 | 0.415771E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57193270.61 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18143417.58 | 0.767462E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 85115186.72 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396731E+09 |
February | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304817E+09 |
March | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276023E+09 |
April | 0.293479E+09 | 82467551.52 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 220228.65 | 0.164516E+09 |
May | 0.303504E+09 | 84776959.58 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2708978.04 | 80992218.25 |
June | 0.293842E+09 | 81813276.33 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7237505.98 | 40996765.50 |
July | 0.303141E+09 | 85442324.32 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9267120.99 | 29249342.60 |
August | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3878479.14 | 39157500.59 |
September | 0.293479E+09 | 82489730.61 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 241963.24 | 85264357.38 |
October | 0.303322E+09 | 85104097.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1829.79 | 0.153135E+09 |
November | 0.293661E+09 | 82140413.93 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220060E+09 |
December | 0.303141E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370333E+09 |
Annual Sum or Average | 0.357224E+10 | 0.100055E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23556105.84 | 0.216128E+10 |
Minimum of Months | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29249342.60 |
Maximum of Months | 0.303685E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9267120.99 | 0.396731E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.305140E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196408E+10 |
February | 0.415303E+11 | 0.271838E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152985E+10 |
March | 0.461508E+11 | 0.297058E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141845E+10 |
April | 0.445315E+11 | 0.278795E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 422030.75 | 0.889246E+09 |
May | 0.460320E+11 | 0.281844E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6703205.93 | 0.484125E+09 |
June | 0.446286E+11 | 0.269458E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19680110.57 | 0.280220E+09 |
July | 0.459349E+11 | 0.278563E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23987039.02 | 0.219736E+09 |
August | 0.461292E+11 | 0.287557E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8602512.88 | 0.279117E+09 |
September | 0.445099E+11 | 0.283510E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 339750.38 | 0.508892E+09 |
October | 0.459565E+11 | 0.299846E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.847326E+09 |
November | 0.444343E+11 | 0.294420E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115976E+10 |
December | 0.459349E+11 | 0.305057E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185098E+10 |
Annual Sum or Average | 0.541708E+12 | 0.345309E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 59734649.54 | 0.114318E+11 |
Minimum of Months | 0.415303E+11 | 0.269458E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219736E+09 |
Maximum of Months | 0.461508E+11 | 0.305140E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23987039.02 | 0.196408E+10 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.305140E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197455E+10 |
February | 0.415303E+11 | 0.271838E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154069E+10 |
March | 0.461508E+11 | 0.297058E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142881E+10 |
April | 0.445315E+11 | 0.278795E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 419479.35 | 0.894899E+09 |
May | 0.460320E+11 | 0.281844E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6674573.29 | 0.485792E+09 |
June | 0.446286E+11 | 0.269458E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19664781.38 | 0.280895E+09 |
July | 0.459349E+11 | 0.278563E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23910618.53 | 0.220028E+09 |
August | 0.461292E+11 | 0.287557E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8562189.31 | 0.280107E+09 |
September | 0.445099E+11 | 0.283510E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 339714.19 | 0.511463E+09 |
October | 0.459565E+11 | 0.299846E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853224E+09 |
November | 0.444343E+11 | 0.294420E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116943E+10 |
December | 0.459349E+11 | 0.305057E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186161E+10 |
Annual Sum or Average | 0.541708E+12 | 0.345309E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 59571356.06 | 0.115015E+11 |
Minimum of Months | 0.415303E+11 | 0.269458E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220028E+09 |
Maximum of Months | 0.461508E+11 | 0.305140E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23910618.53 | 0.197455E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113146E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179183E+10 |
February | 0.369574E+10 | 0.102161E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139281E+10 |
March | 0.410691E+10 | 0.113495E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128485E+10 |
April | 0.396281E+10 | 0.109310E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 377771.98 | 0.801112E+09 |
May | 0.409635E+10 | 0.113342E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 5988567.87 | 0.434523E+09 |
June | 0.397146E+10 | 0.109811E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 17629361.57 | 0.250027E+09 |
July | 0.408770E+10 | 0.112841E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 21431842.85 | 0.195653E+09 |
August | 0.410499E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 7678053.83 | 0.249272E+09 |
September | 0.396089E+10 | 0.109354E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 306244.95 | 0.458901E+09 |
October | 0.408962E+10 | 0.113103E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767998E+09 |
November | 0.395417E+10 | 0.109724E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105078E+10 |
December | 0.408770E+10 | 0.112841E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169195E+10 |
Annual Sum or Average | 0.482060E+11 | 0.133267E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 53411843.05 | 0.103697E+11 |
Minimum of Months | 0.369574E+10 | 0.102161E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195653E+09 |
Maximum of Months | 0.410691E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 21431842.85 | 0.179183E+10 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.246211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166489E+10 |
February | 0.368610E+10 | 0.222306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127013E+10 |
March | 0.409620E+10 | 0.246970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115055E+10 |
April | 0.395248E+10 | 0.237864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 618512.49 | 0.692647E+09 |
May | 0.408566E+10 | 0.246638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6634370.12 | 0.376784E+09 |
June | 0.396110E+10 | 0.238954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17925681.52 | 0.215278E+09 |
July | 0.407704E+10 | 0.245547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21879437.53 | 0.174981E+09 |
August | 0.409429E+10 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8010674.60 | 0.214992E+09 |
September | 0.395056E+10 | 0.237958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321734.71 | 0.388739E+09 |
October | 0.407896E+10 | 0.246116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649953E+09 |
November | 0.394385E+10 | 0.238765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921329E+09 |
December | 0.407704E+10 | 0.245547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155867E+10 |
Annual Sum or Average | 0.480803E+11 | 0.289994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55390410.97 | 0.927895E+10 |
Minimum of Months | 0.368610E+10 | 0.222306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174981E+09 |
Maximum of Months | 0.409620E+10 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21879437.53 | 0.166489E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 14185.34 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 14185.34 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 14185.34 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 14185.34 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 14185.34 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 14185.34 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 14185.34 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 14185.34 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 14185.34 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 14185.34 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 14185.34 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 14185.34 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 14185.34 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 14185.34 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 704.41 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 795.99 | 06-JAN-09:00 |
February | 1169.53 | 01-FEB-00:10 | 704.41 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 758.84 | 14-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 704.41 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 687.26 | 05-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 704.41 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.51 | 23-APR-17:00 | 451.56 | 05-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 704.41 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.29 | 25-MAY-18:00 | 312.14 | 01-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 704.41 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.90 | 29-JUN-16:00 | 242.34 | 04-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 704.41 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.85 | 15-JUL-15:20 | 181.69 | 02-JUL-04:53 |
August | 1169.53 | 01-AUG-00:10 | 704.41 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.10 | 08-AUG-15:30 | 199.86 | 19-AUG-04:20 |
September | 1169.53 | 01-SEP-00:10 | 704.41 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 01-SEP-15:30 | 242.61 | 06-SEP-04:03 |
October | 1169.53 | 01-OCT-23:10 | 704.41 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 398.40 | 30-OCT-04:00 |
November | 1169.53 | 01-NOV-00:10 | 704.41 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 553.03 | 29-NOV-06:00 |
December | 1169.53 | 01-DEC-00:10 | 704.41 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 734.34 | 24-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 704.41 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.69 | |||||
Maximum of Months | 1169.53 | 704.41 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 118.90 | 795.99 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 815.72 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 308.84 | 06-JAN-09:00 |
February | 1354.32 | 01-FEB-00:10 | 815.72 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 295.44 | 14-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 815.72 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 265.27 | 05-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 815.72 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.55 | 23-APR-16:00 | 177.71 | 05-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 815.72 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.96 | 25-MAY-17:01 | 126.38 | 01-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 815.72 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.61 | 29-JUN-16:00 | 100.64 | 04-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 815.72 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.46 | 15-JUL-14:00 | 81.10 | 02-JUL-04:53 |
August | 1354.32 | 01-AUG-00:10 | 815.72 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.13 | 08-AUG-15:00 | 85.43 | 19-AUG-04:00 |
September | 1354.32 | 01-SEP-00:10 | 815.72 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.49 | 01-SEP-15:00 | 104.50 | 06-SEP-04:50 |
October | 1354.32 | 01-OCT-23:10 | 815.72 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 156.82 | 30-OCT-04:30 |
November | 1354.32 | 01-NOV-00:10 | 815.72 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 213.46 | 29-NOV-06:00 |
December | 1354.32 | 01-DEC-00:10 | 815.72 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 283.47 | 24-DEC-08:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 815.72 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.10 | |||||
Maximum of Months | 1354.32 | 815.72 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 46.61 | 308.84 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 1360.40 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 738.38 | 06-JAN-09:00 |
February | 286.42 | 01-FEB-00:10 | 1360.40 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 698.24 | 14-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 1360.40 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 626.91 | 05-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 1360.40 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.85 | 23-APR-16:00 | 411.92 | 05-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 1360.40 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.55 | 25-MAY-17:01 | 286.13 | 01-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 1360.40 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.90 | 29-JUN-16:00 | 234.35 | 04-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 1360.40 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.68 | 15-JUL-14:00 | 189.49 | 02-JUL-04:53 |
August | 286.42 | 01-AUG-00:10 | 1360.40 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.47 | 08-AUG-16:00 | 196.80 | 19-AUG-04:00 |
September | 286.42 | 01-SEP-00:10 | 1360.40 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.82 | 01-SEP-16:00 | 238.26 | 06-SEP-04:50 |
October | 286.42 | 01-OCT-23:10 | 1360.40 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 19-OCT-15:00 | 363.45 | 30-OCT-04:00 |
November | 286.42 | 01-NOV-00:10 | 1360.40 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 504.48 | 29-NOV-06:00 |
December | 286.42 | 01-DEC-00:10 | 1360.40 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 669.94 | 24-DEC-08:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.49 | |||||
Maximum of Months | 286.42 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 110.90 | 738.38 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 227.72 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 422.55 | 06-JAN-09:00 |
February | 220.32 | 01-FEB-00:10 | 227.72 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 402.85 | 14-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 227.72 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 361.69 | 05-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 227.72 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 | 23-APR-16:00 | 237.65 | 05-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 227.72 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.29 | 25-MAY-18:00 | 164.29 | 01-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 227.72 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.86 | 29-JUN-16:00 | 133.55 | 04-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 227.72 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.49 | 15-JUL-14:00 | 107.83 | 02-JUL-04:53 |
August | 220.32 | 01-AUG-00:10 | 227.72 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.98 | 08-AUG-16:00 | 112.31 | 19-AUG-04:00 |
September | 220.32 | 01-SEP-00:10 | 227.72 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.26 | 01-SEP-16:00 | 136.07 | 06-SEP-04:10 |
October | 220.32 | 01-OCT-23:10 | 227.72 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 | 19-OCT-15:00 | 209.69 | 30-OCT-04:00 |
November | 220.32 | 01-NOV-00:10 | 227.72 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 291.06 | 29-NOV-06:00 |
December | 220.32 | 01-DEC-00:10 | 227.72 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 386.52 | 24-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 227.72 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.83 | |||||
Maximum of Months | 220.32 | 227.72 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 63.86 | 422.55 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 357.21 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 972.45 | 06-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 357.21 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 944.65 | 14-FEB-07:10 |
March | 907.20 | 01-MAR-00:10 | 357.21 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 856.00 | 05-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 357.21 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 65.33 | 23-APR-16:00 | 610.59 | 05-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 357.21 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 94.71 | 25-MAY-17:00 | 435.56 | 01-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 357.21 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 169.14 | 29-JUN-16:00 | 331.81 | 02-JUN-21:53 |
July | 907.20 | 01-JUL-00:10 | 357.21 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 112.75 | 23-JUL-16:00 | 268.30 | 02-JUL-04:41 |
August | 907.20 | 01-AUG-00:10 | 357.21 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 112.38 | 08-AUG-16:00 | 284.49 | 18-AUG-22:07 |
September | 907.20 | 01-SEP-00:10 | 357.21 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 49.94 | 01-SEP-16:00 | 343.42 | 06-SEP-05:10 |
October | 907.20 | 01-OCT-23:10 | 357.21 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 537.26 | 30-OCT-05:10 |
November | 907.20 | 01-NOV-00:10 | 357.21 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 723.92 | 29-NOV-06:10 |
December | 907.20 | 01-DEC-00:10 | 357.21 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 914.90 | 24-DEC-08:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 268.30 | ||||||
Maximum of Months | 907.20 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 169.14 | 972.45 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1761.91 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1765.15 | 06-JAN-05:00 |
February | 15368.40 | 01-FEB-00:10 | 1761.91 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1692.06 | 14-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1761.91 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1519.21 | 05-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1761.91 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.32 | 23-APR-17:20 | 998.15 | 05-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 1761.91 | 01-MAY-19:19 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.45 | 25-MAY-18:00 | 706.75 | 01-MAY-06:00 |
June | 15368.40 | 01-JUN-00:10 | 1761.91 | 01-JUN-19:40 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.89 | 29-JUN-16:00 | 556.39 | 04-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1761.91 | 07-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.98 | 15-JUL-15:20 | 450.50 | 02-JUL-04:53 |
August | 15368.40 | 01-AUG-00:10 | 1761.91 | 01-AUG-19:30 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.63 | 08-AUG-15:30 | 485.34 | 19-AUG-04:00 |
September | 15368.40 | 01-SEP-00:10 | 1761.91 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 01-SEP-15:40 | 591.76 | 06-SEP-04:10 |
October | 15368.40 | 01-OCT-23:10 | 1761.91 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 886.83 | 30-OCT-04:20 |
November | 15368.40 | 01-NOV-00:10 | 1761.91 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1222.50 | 29-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1761.91 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1623.66 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1761.91 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.50 | |||||
Maximum of Months | 15368.40 | 1761.91 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 262.89 | 1765.15 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 10265.18 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5055.55 | 06-JAN-09:00 |
February | 45622.98 | 01-FEB-00:10 | 10265.18 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4834.44 | 14-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 10265.18 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 4340.59 | 05-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 10265.18 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.79 | 23-APR-16:00 | 2958.99 | 05-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 10265.18 | 01-MAY-19:19 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 388.57 | 25-MAY-17:01 | 2118.31 | 01-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 10265.18 | 01-JUN-19:40 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 752.11 | 29-JUN-16:00 | 1691.82 | 04-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 10265.18 | 07-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 508.08 | 15-JUL-15:00 | 1343.08 | 02-JUL-04:53 |
August | 45622.98 | 01-AUG-00:10 | 10265.18 | 01-AUG-19:30 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 463.86 | 08-AUG-16:00 | 1460.79 | 19-AUG-04:00 |
September | 45622.98 | 01-SEP-00:10 | 10265.18 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.62 | 01-SEP-15:40 | 1758.07 | 06-SEP-04:50 |
October | 45622.98 | 01-OCT-23:10 | 10265.18 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2640.45 | 30-OCT-04:40 |
November | 45622.98 | 01-NOV-00:10 | 10265.18 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 3572.26 | 29-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 10265.18 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4638.37 | 24-DEC-08:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 10265.18 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.08 | |||||
Maximum of Months | 45622.98 | 10265.18 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 752.11 | 5055.55 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 465.51 | 06-JAN-07:20 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 445.49 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 400.09 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.16 | 23-APR-16:00 | 263.23 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.43 | 25-MAY-17:00 | 182.29 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.87 | 29-JUN-16:00 | 141.73 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 | 15-JUL-15:10 | 103.69 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 08-AUG-15:10 | 117.04 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.95 | 01-SEP-16:00 | 141.89 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 19-OCT-15:10 | 232.39 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 322.16 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 427.49 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.69 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.87 | 465.51 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 465.48 | 06-JAN-07:10 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 445.47 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 400.06 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 23-APR-16:00 | 263.21 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.42 | 25-MAY-17:00 | 182.27 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 29-JUN-16:00 | 141.72 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 | 15-JUL-15:10 | 103.68 | 02-JUL-04:52 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 08-AUG-15:10 | 117.04 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 | 01-SEP-15:10 | 141.88 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 19-OCT-15:10 | 232.36 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 322.12 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 427.46 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.68 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 465.48 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 76.99 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 126.45 | 06-JAN-09:00 |
February | 0.00 | 01-FEB-00:10 | 76.99 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 119.23 | 14-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 76.99 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 106.68 | 05-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 76.99 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.88 | 23-APR-16:00 | 69.64 | 05-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 76.99 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.73 | 25-MAY-18:00 | 50.02 | 01-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 76.99 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.35 | 29-JUN-16:00 | 40.80 | 04-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 76.99 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 15-JUL-14:00 | 32.10 | 02-JUL-04:51 |
August | 0.00 | 01-AUG-00:10 | 76.99 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.96 | 08-AUG-15:00 | 34.19 | 19-AUG-04:00 |
September | 0.00 | 01-SEP-00:10 | 76.99 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 | 01-SEP-15:00 | 42.49 | 06-SEP-04:00 |
October | 0.00 | 01-OCT-00:10 | 76.99 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 60.22 | 30-OCT-04:00 |
November | 0.00 | 01-NOV-00:10 | 76.99 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 85.10 | 29-NOV-06:00 |
December | 0.00 | 01-DEC-00:10 | 76.99 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 114.21 | 24-DEC-08:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 76.99 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.10 | |||||
Maximum of Months | 0.00 | 76.99 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 20.35 | 126.45 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 77.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 129.92 | 06-JAN-07:10 |
February | 180.00 | 01-FEB-00:10 | 77.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 124.33 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 77.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 111.66 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 77.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 | 23-APR-16:00 | 73.47 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 77.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 | 25-MAY-17:00 | 50.88 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 77.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.24 | 29-JUN-16:00 | 39.56 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 77.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.23 | 15-JUL-15:10 | 28.94 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 77.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.95 | 08-AUG-15:10 | 32.67 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 77.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.92 | 01-SEP-15:30 | 39.60 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 77.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 | 19-OCT-15:00 | 64.86 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 77.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 89.91 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 77.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 119.31 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.94 | |||||
Maximum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 24.24 | 129.92 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 465.51 | 06-JAN-07:10 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 445.50 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 400.09 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 23-APR-16:00 | 263.23 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.43 | 25-MAY-17:00 | 182.29 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 29-JUN-16:00 | 141.74 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 | 15-JUL-15:08 | 103.69 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.73 | 08-AUG-15:10 | 117.04 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 | 01-SEP-15:10 | 141.89 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 19-OCT-15:10 | 232.38 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 322.15 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 427.49 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.69 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 465.51 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 465.48 | 06-JAN-07:10 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 445.47 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 400.06 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 23-APR-16:00 | 263.21 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.42 | 25-MAY-17:00 | 182.28 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 29-JUN-16:00 | 141.72 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 | 15-JUL-15:08 | 103.68 | 02-JUL-04:53 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 08-AUG-15:08 | 117.04 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 | 01-SEP-15:10 | 141.88 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 19-OCT-15:07 | 232.37 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 322.13 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 427.46 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.68 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 465.48 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 2240.78 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 567.99 | 06-JAN-09:00 |
February | 2263.36 | 01-FEB-00:10 | 2240.78 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 537.63 | 14-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 2240.78 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 482.75 | 05-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 2240.78 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.28 | 23-APR-16:00 | 317.31 | 05-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 2240.78 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.24 | 25-MAY-18:00 | 221.64 | 01-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 2240.78 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.12 | 29-JUN-16:00 | 182.09 | 04-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 2240.78 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.91 | 15-JUL-14:00 | 146.59 | 02-JUL-04:53 |
August | 2263.36 | 01-AUG-00:10 | 2240.78 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.81 | 08-AUG-16:00 | 151.52 | 19-AUG-04:00 |
September | 2263.36 | 01-SEP-00:10 | 2240.78 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 | 01-SEP-16:00 | 186.69 | 06-SEP-04:10 |
October | 2263.36 | 01-OCT-23:10 | 2240.78 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 280.02 | 30-OCT-04:00 |
November | 2263.36 | 01-NOV-00:10 | 2240.78 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 388.53 | 29-NOV-06:00 |
December | 2263.36 | 01-DEC-00:10 | 2240.78 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 515.86 | 24-DEC-08:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.59 | ||||
Maximum of Months | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.12 | 567.99 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 466.12 | 06-JAN-07:10 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 446.10 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 400.66 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.79 | 23-APR-16:00 | 263.73 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.05 | 25-MAY-17:00 | 182.76 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.51 | 29-JUN-16:00 | 142.18 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.37 | 15-JUL-15:10 | 104.12 | 02-JUL-04:53 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.35 | 08-AUG-16:00 | 117.48 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.55 | 01-SEP-16:00 | 142.34 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.95 | 19-OCT-15:10 | 232.88 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 322.69 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 428.08 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.12 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.51 | 466.12 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 466.09 | 06-JAN-07:10 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 446.06 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 400.63 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.80 | 23-APR-16:00 | 263.72 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.05 | 25-MAY-17:00 | 182.75 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.50 | 29-JUN-16:00 | 142.17 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.36 | 15-JUL-15:10 | 104.12 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.35 | 08-AUG-15:10 | 117.48 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.58 | 01-SEP-15:10 | 142.33 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.95 | 19-OCT-15:10 | 232.86 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 322.66 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 428.05 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.12 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.50 | 466.09 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 77.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 238.48 | 06-JAN-07:10 |
February | 180.00 | 01-FEB-00:10 | 77.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 228.24 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 77.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 204.99 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 77.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.80 | 23-APR-16:00 | 134.94 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 77.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.12 | 25-MAY-17:00 | 93.51 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 77.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.26 | 29-JUN-16:00 | 72.75 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 77.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.40 | 15-JUL-15:10 | 53.27 | 02-JUL-04:53 |
August | 180.00 | 01-AUG-00:10 | 77.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.88 | 08-AUG-15:10 | 60.11 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 77.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.16 | 01-SEP-16:00 | 72.83 | 06-SEP-04:10 |
October | 180.00 | 01-OCT-00:10 | 77.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 | 19-OCT-16:00 | 119.15 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 77.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 165.10 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 77.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 219.02 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.27 | |||||
Maximum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 44.26 | 238.48 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3094.06 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1145.40 | 06-JAN-09:00 |
February | 26988.77 | 01-FEB-00:10 | 3094.06 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1087.08 | 14-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3094.06 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 976.18 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3094.06 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 | 23-APR-16:00 | 696.16 | 05-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 3094.06 | 01-MAY-19:30 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.68 | 25-MAY-18:00 | 497.51 | 01-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 3094.06 | 01-JUN-19:49 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.03 | 29-JUN-16:00 | 396.96 | 04-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3094.06 | 07-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.47 | 15-JUL-14:00 | 308.25 | 02-JUL-04:53 |
August | 26988.77 | 01-AUG-00:10 | 3094.06 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.06 | 08-AUG-15:40 | 336.06 | 19-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 3094.06 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.56 | 01-SEP-15:50 | 397.44 | 06-SEP-04:10 |
October | 26988.77 | 01-OCT-23:10 | 3094.06 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 621.17 | 30-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 3094.06 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 835.84 | 29-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 3094.06 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1043.16 | 24-DEC-08:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.25 | |||||
Maximum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 167.03 | 1145.40 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3094.06 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1147.53 | 06-JAN-09:00 |
February | 26988.77 | 01-FEB-00:10 | 3094.06 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1087.07 | 14-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3094.06 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 976.21 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3094.06 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 | 23-APR-16:00 | 696.88 | 05-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 3094.06 | 01-MAY-19:30 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.67 | 25-MAY-18:00 | 497.52 | 01-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 3094.06 | 01-JUN-19:49 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.02 | 29-JUN-16:00 | 396.97 | 04-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3094.06 | 07-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.47 | 15-JUL-14:00 | 308.58 | 02-JUL-04:53 |
August | 26988.77 | 01-AUG-00:10 | 3094.06 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.06 | 08-AUG-15:40 | 336.07 | 19-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 3094.06 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.56 | 01-SEP-15:50 | 397.44 | 06-SEP-04:10 |
October | 26988.77 | 01-OCT-23:10 | 3094.06 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 621.17 | 30-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 3094.06 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 840.17 | 29-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 3094.06 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1043.13 | 24-DEC-08:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.58 | |||||
Maximum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 167.02 | 1147.53 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1089.83 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1030.28 | 06-JAN-09:00 |
February | 2401.70 | 01-FEB-00:10 | 1089.83 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 973.17 | 14-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1089.83 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 873.95 | 05-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1089.83 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 36.19 | 23-APR-16:00 | 623.77 | 05-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1089.83 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 74.17 | 25-MAY-18:00 | 445.31 | 01-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 1089.83 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 149.69 | 29-JUN-16:00 | 354.75 | 04-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1089.83 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 97.20 | 15-JUL-14:00 | 283.32 | 02-JUL-04:53 |
August | 2401.70 | 01-AUG-00:10 | 1089.83 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 91.54 | 08-AUG-15:40 | 303.81 | 18-AUG-22:47 |
September | 2401.70 | 01-SEP-00:10 | 1089.83 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 28.43 | 01-SEP-15:40 | 352.63 | 06-SEP-05:10 |
October | 2401.70 | 01-OCT-23:10 | 1089.83 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 552.46 | 30-OCT-05:10 |
November | 2401.70 | 01-NOV-00:10 | 1089.83 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 742.24 | 29-NOV-06:20 |
December | 2401.70 | 01-DEC-00:10 | 1089.83 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 933.83 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1089.83 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 283.32 | ||||||
Maximum of Months | 2401.70 | 1089.83 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 149.69 | 1030.28 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1001.05 | 06-JAN-09:00 |
February | 2395.44 | 01-FEB-00:10 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 952.52 | 14-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 855.35 | 05-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.97 | 23-APR-16:00 | 562.48 | 05-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.40 | 25-MAY-18:00 | 389.30 | 01-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.30 | 29-JUN-16:00 | 310.20 | 04-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.01 | 15-JUL-14:00 | 251.29 | 02-JUL-04:53 |
August | 2395.44 | 01-AUG-00:10 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.38 | 08-AUG-15:00 | 259.39 | 19-AUG-04:00 |
September | 2395.44 | 01-SEP-00:10 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.61 | 01-SEP-15:30 | 317.29 | 06-SEP-04:03 |
October | 2395.44 | 01-OCT-23:10 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 496.51 | 30-OCT-04:00 |
November | 2395.44 | 01-NOV-00:10 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 688.57 | 29-NOV-06:00 |
December | 2395.44 | 01-DEC-00:10 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 913.99 | 24-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.29 | ||||
Maximum of Months | 2395.44 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.30 | 1001.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 26839.40 | 26-JAN-07:00 | 8945.92 | 6304.56 | 5323.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24236.67 | 14-FEB-06:20 | 17891.83 | 12609.11 | 10646.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20953.74 | 05-MAR-04:00 | 8945.92 | 3152.28 | 3193.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22885.67 | 16-APR-21:25 | 20447.81 | 15761.57 | 12775.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19110.19 | 08-MAY-13:05 | 25559.76 | 39403.94 | 37261.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19804.00 | 16-JUN-03:03 | 34505.68 | 4728.69 | 6387.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20039.75 | 02-JUL-03:03 | 26837.75 | 9456.84 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32890.14 | 18-AUG-23:00 | 46007.57 | 18914.03 | 17033.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 36307.56 | 14-SEP-06:29 | 35783.66 | 55165.51 | 44713.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35705.03 | 23-OCT-06:54 | 46007.57 | 70927.09 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 34524.07 | 17-NOV-20:57 | 35783.66 | 56741.38 | 40455.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24702.46 | 24-DEC-07:40 | 8945.92 | 6304.56 | 5323.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 19110.19 | 8945.92 | 3152.28 | 3193.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36307.56 | 46007.57 | 70927.09 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2341.09 | 05-JAN-12:50 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.58 |
February | 5789.44 | 28-FEB-15:06 | 3898.44 | 1956.71 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.30 |
March | 5045.96 | 31-MAR-13:26 | 2598.96 | 1956.71 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.66 |
April | 6196.95 | 19-APR-13:16 | 1819.27 | 1369.70 | 1768.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.82 |
May | 3890.35 | 18-MAY-13:10 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 47.28 | 0.00 |
June | 4006.84 | 30-JUN-13:00 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 84.05 | 0.00 |
July | 4118.61 | 23-JUL-13:10 | 259.90 | 156.54 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 66.03 | 0.00 |
August | 4527.88 | 26-AUG-12:40 | 389.84 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 15.75 | 0.00 |
September | 4531.70 | 01-SEP-13:20 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 8.92 | 0.00 |
October | 6194.31 | 09-OCT-11:43 | 3898.44 | 2348.05 | 2886.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.47 |
November | 5029.14 | 16-NOV-11:23 | 2598.96 | 1956.71 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.99 |
December | 2806.91 | 10-DEC-12:00 | 389.84 | 234.80 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 606.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2341.09 | 259.90 | 156.54 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6196.95 | 3898.44 | 2348.05 | 2886.75 | 0.00 | 0.00 | 0.00 | 0.00 | 84.05 | 676.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1618.42 | 27-JAN-22:05 | 2708.64 | 1087.62 | 1170.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.10 |
February | 1795.60 | 21-FEB-12:24 | 3009.60 | 2265.88 | 2925.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.09 |
March | 1638.99 | 31-MAR-20:51 | 12038.40 | 7250.80 | 7521.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.83 |
April | 2307.92 | 16-APR-21:25 | 2407.68 | 906.35 | 1002.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.82 |
May | 2078.84 | 20-MAY-21:27 | 8426.88 | 4350.48 | 4680.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.13 |
June | 2749.36 | 17-JUN-01:23 | 5417.28 | 362.54 | 668.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.72 |
July | 2626.40 | 02-JUL-03:03 | 3160.08 | 543.81 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.00 |
August | 2024.84 | 19-AUG-01:23 | 4062.96 | 271.91 | 501.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.00 |
September | 3223.17 | 05-SEP-21:27 | 12188.88 | 4894.29 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.29 |
October | 3259.47 | 20-OCT-21:55 | 10834.56 | 4350.48 | 4680.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.01 |
November | 1844.32 | 21-NOV-01:33 | 4062.96 | 407.86 | 626.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.70 |
December | 1535.84 | 02-DEC-00:33 | 5417.28 | 725.08 | 1002.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1535.84 | 2407.68 | 271.91 | 501.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.70 | |
Maximum of Months | 3259.47 | 12188.88 | 7250.80 | 7521.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 817.35 | 19-JAN-21:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.77 |
February | 1268.03 | 04-FEB-18:32 | 1145.66 | 5441.59 | 3711.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.39 |
March | 1292.34 | 31-MAR-20:51 | 2545.92 | 12092.41 | 7952.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.65 |
April | 1968.84 | 16-APR-21:25 | 509.18 | 1511.55 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.99 |
May | 1703.44 | 08-MAY-13:05 | 636.48 | 3778.88 | 3092.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.30 |
June | 2140.59 | 30-JUN-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 0.00 |
July | 1888.40 | 24-JUL-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 |
August | 1814.56 | 19-AUG-01:23 | 859.25 | 453.47 | 530.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.66 |
September | 2130.94 | 15-SEP-00:35 | 2291.33 | 1813.86 | 1767.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.92 |
October | 2048.93 | 23-OCT-00:23 | 2864.16 | 2267.33 | 2209.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.48 |
November | 1556.96 | 21-NOV-01:33 | 859.25 | 680.20 | 662.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.96 |
December | 825.77 | 05-DEC-21:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 817.35 | 222.77 | 453.47 | 530.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2140.59 | 2864.16 | 12092.41 | 7952.65 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 275.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 96.83 | 19-JAN-22:00 | 195.84 | 202.41 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.82 |
February | 531.29 | 21-FEB-15:55 | 293.76 | 253.03 | 356.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.96 |
March | 587.14 | 31-MAR-20:51 | 1958.40 | 2024.15 | 2294.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.04 |
April | 919.84 | 16-APR-21:25 | 391.68 | 253.02 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.00 |
May | 810.89 | 08-MAY-13:05 | 489.60 | 632.58 | 892.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.34 |
June | 843.54 | 16-JUN-03:03 | 660.96 | 75.91 | 152.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.76 |
July | 881.06 | 02-JUL-03:03 | 514.08 | 151.81 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.12 |
August | 858.70 | 19-AUG-01:23 | 660.96 | 75.91 | 152.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.02 |
September | 1013.33 | 15-SEP-00:35 | 1762.56 | 303.65 | 509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.52 |
October | 977.20 | 23-OCT-00:23 | 2203.20 | 379.56 | 637.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.46 |
November | 740.50 | 21-NOV-01:33 | 660.96 | 113.87 | 191.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.23 |
December | 154.16 | 05-DEC-22:00 | 195.84 | 202.41 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 96.83 | 195.84 | 75.91 | 152.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.23 | |
Maximum of Months | 1013.33 | 2203.20 | 2024.15 | 2294.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35826.33 | 19-JAN-21:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 421.57 |
February | 43944.16 | 20-FEB-19:14 | 6048.00 | 2778.33 | 38507.80 | 334539.59 | 0.00 | 0.00 | 0.00 | 0.00 | 298.30 |
March | 50696.78 | 27-MAR-20:37 | 4838.40 | 1905.14 | 25992.76 | 225814.22 | 0.00 | 0.00 | 0.00 | 0.00 | 314.16 |
April | 52328.57 | 19-APR-19:09 | 7056.00 | 3572.14 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 314.56 |
May | 50290.65 | 09-MAY-20:56 | 8064.00 | 3175.23 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 291.55 |
June | 46037.38 | 02-JUN-21:28 | 8164.80 | 2143.28 | 30324.89 | 263449.93 | 0.00 | 0.00 | 0.00 | 0.00 | 263.40 |
July | 38765.93 | 21-JUL-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 25.45 |
August | 38664.32 | 08-AUG-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.02 | 0.00 |
September | 49686.26 | 23-SEP-20:56 | 7056.00 | 2778.33 | 38507.80 | 334539.59 | 0.00 | 0.00 | 0.00 | 0.00 | 291.06 |
October | 51339.81 | 03-OCT-20:57 | 8064.00 | 3175.23 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 336.35 |
November | 50245.36 | 17-NOV-20:40 | 7056.00 | 3572.14 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 326.99 |
December | 35907.28 | 05-DEC-21:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 365.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 35826.33 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52328.57 | 8164.80 | 3572.14 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 14.02 | 421.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10310.01 | 27-JAN-13:30 | 3415.20 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1125.72 |
February | 22482.99 | 28-FEB-15:06 | 51228.00 | 2985.45 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.96 |
March | 19585.98 | 26-MAR-11:27 | 46105.20 | 3224.29 | 3657.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.28 |
April | 24222.44 | 19-APR-14:06 | 51228.00 | 2985.45 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.13 |
May | 15860.15 | 01-MAY-14:08 | 20491.20 | 1194.18 | 1422.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.64 |
June | 17548.85 | 16-JUN-23:44 | 138315.60 | 3523.81 | 2743.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.55 |
July | 15456.11 | 07-JUL-23:53 | 107578.80 | 2740.74 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.09 |
August | 15876.56 | 26-AUG-12:40 | 5122.80 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 34.85 | 0.00 |
September | 17558.62 | 15-SEP-00:35 | 122947.20 | 2349.21 | 2032.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.34 |
October | 24386.54 | 09-OCT-11:43 | 51228.00 | 3582.54 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537.18 |
November | 19683.03 | 17-NOV-11:10 | 23906.40 | 2089.82 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.75 |
December | 11938.39 | 10-DEC-11:00 | 8538.00 | 358.25 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1371.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10310.01 | 3415.20 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24386.54 | 138315.60 | 3582.54 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 34.85 | 1371.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35147.89 | 27-JAN-22:05 | 91245.96 | 13686.91 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3952.80 |
February | 39527.23 | 21-FEB-12:24 | 101384.40 | 26518.39 | 36949.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1167.18 |
March | 55228.84 | 31-MAR-21:36 | 456229.80 | 68434.56 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1465.70 |
April | 65667.06 | 11-APR-21:24 | 456229.80 | 68434.56 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1498.32 |
May | 63520.73 | 20-MAY-00:56 | 456229.80 | 22811.52 | 31671.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1162.65 |
June | 64195.22 | 16-JUN-23:55 | 364983.84 | 18249.22 | 25336.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1350.29 |
July | 69094.11 | 07-JUL-23:53 | 319360.86 | 15968.06 | 22169.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1220.09 |
August | 62116.53 | 25-AUG-04:16 | 456229.80 | 22811.52 | 31671.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1161.61 |
September | 68448.13 | 05-SEP-21:27 | 410606.82 | 61591.10 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.98 |
October | 73109.78 | 19-OCT-03:43 | 136868.94 | 3421.73 | 6334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.86 |
November | 78856.56 | 21-NOV-01:33 | 136868.94 | 5132.59 | 7917.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.96 |
December | 34442.26 | 02-DEC-00:33 | 182491.92 | 9124.61 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3928.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 34442.26 | 91245.96 | 3421.73 | 6334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.96 | |
Maximum of Months | 78856.56 | 456229.80 | 68434.56 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3952.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1223.40 | 31-JAN-16:03 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.06 |
February | 3368.45 | 22-FEB-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.35 |
March | 3486.98 | 31-MAR-15:01 | 972.00 | 343.01 | 684.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.20 |
April | 3608.43 | 13-APR-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.90 |
May | 3731.53 | 21-MAY-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 0.00 |
June | 3803.60 | 30-JUN-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 43.39 | 0.00 |
July | 3778.20 | 20-JUL-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 31.41 | 0.00 |
August | 3634.30 | 08-AUG-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 35.34 | 0.00 |
September | 3646.46 | 06-SEP-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.74 |
October | 3584.09 | 21-OCT-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.75 |
November | 3302.45 | 17-NOV-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.26 |
December | 903.62 | 05-DEC-19:04 | 970.20 | 763.21 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 903.62 | 324.00 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3803.60 | 972.00 | 763.21 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 43.39 | 313.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 819.28 | 16-JAN-09:04 | 378.00 | 480.16 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.64 |
February | 2839.10 | 22-FEB-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.46 |
March | 3259.48 | 28-MAR-18:01 | 1247.40 | 981.16 | 1161.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.52 |
April | 3380.17 | 13-APR-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.91 |
May | 3600.59 | 25-MAY-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 39.90 | 0.00 |
June | 3636.43 | 30-JUN-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 43.06 | 0.00 |
July | 3562.46 | 24-JUL-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 32.67 | 0.00 |
August | 3519.15 | 23-AUG-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 26.35 | 0.00 |
September | 3419.45 | 06-SEP-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.79 |
October | 3345.93 | 21-OCT-15:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.55 |
November | 1495.23 | 21-NOV-16:03 | 972.00 | 342.97 | 684.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.71 |
December | 813.40 | 05-DEC-19:04 | 970.20 | 763.12 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 813.40 | 324.00 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3636.43 | 1247.40 | 981.16 | 1161.45 | 0.00 | 0.00 | 0.00 | 0.00 | 43.06 | 155.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 302.33 | 05-JAN-11:03 | 0.00 | 172.46 | 536.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.86 |
February | 441.97 | 22-FEB-14:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.48 |
March | 566.77 | 20-MAR-12:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.48 |
April | 682.47 | 13-APR-13:20 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 |
May | 696.15 | 18-MAY-13:10 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 8.78 | 0.00 |
June | 685.84 | 30-JUN-13:00 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 14.71 | 0.00 |
July | 730.55 | 23-JUL-13:20 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 11.81 | 0.00 |
August | 800.45 | 25-AUG-13:10 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 7.25 | 0.00 |
September | 804.53 | 01-SEP-13:20 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 0.00 |
October | 961.47 | 22-OCT-12:30 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.94 |
November | 441.42 | 17-NOV-13:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.98 |
December | 287.89 | 24-DEC-11:10 | 0.00 | 203.26 | 598.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 287.89 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 961.47 | 0.00 | 203.26 | 598.54 | 0.00 | 0.00 | 0.00 | 0.00 | 14.71 | 109.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 492.40 | 19-JAN-19:04 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.16 |
February | 553.26 | 21-FEB-19:03 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.33 |
March | 535.00 | 28-MAR-18:01 | 1247.40 | 616.86 | 1138.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.19 |
April | 913.09 | 23-APR-18:01 | 819.00 | 539.08 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.47 | 0.00 |
May | 976.21 | 24-MAY-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 | 0.00 |
June | 991.53 | 17-JUN-18:02 | 702.00 | 462.06 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 | 0.00 |
July | 975.57 | 24-JUL-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 8.91 | 0.00 |
August | 953.58 | 09-AUG-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 6.86 | 0.00 |
September | 918.93 | 01-SEP-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 | 0.00 |
October | 816.99 | 01-OCT-08:61 | 540.00 | 431.26 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.03 |
November | 607.22 | 20-NOV-16:03 | 972.00 | 215.63 | 670.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.51 |
December | 443.37 | 06-DEC-19:04 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 443.37 | 540.00 | 215.63 | 670.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 991.53 | 1247.40 | 616.86 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 8.91 | 58.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 848.91 | 25-JAN-09:04 | 252.00 | 377.32 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.92 |
February | 2800.32 | 28-FEB-16:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.18 |
March | 3144.67 | 31-MAR-15:01 | 972.00 | 343.01 | 684.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.61 |
April | 3239.23 | 13-APR-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.99 |
May | 3349.28 | 21-MAY-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 0.00 |
June | 3357.45 | 17-JUN-18:02 | 702.00 | 735.03 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | 0.00 |
July | 3315.08 | 22-JUL-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 45.89 | 0.00 |
August | 3323.40 | 09-AUG-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 32.90 | 0.00 |
September | 3261.59 | 06-SEP-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.60 |
October | 3232.53 | 21-OCT-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.11 |
November | 2410.70 | 17-NOV-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.75 |
December | 906.15 | 02-DEC-09:04 | 378.00 | 480.22 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 848.91 | 252.00 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3357.45 | 972.00 | 735.03 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 45.89 | 373.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 807.11 | 19-JAN-19:04 | 970.20 | 763.12 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.11 |
February | 1329.12 | 20-FEB-09:03 | 378.00 | 480.16 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.07 |
March | 2685.50 | 26-MAR-08:61 | 378.00 | 480.16 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.47 |
April | 3032.82 | 13-APR-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.09 |
May | 3176.12 | 25-MAY-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 42.06 | 0.00 |
June | 3221.18 | 29-JUN-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 74.82 | 0.00 |
July | 3205.75 | 21-JUL-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 44.33 | 0.00 |
August | 3197.57 | 25-AUG-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 37.35 | 0.00 |
September | 3079.42 | 01-SEP-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 23.23 | 0.00 |
October | 2952.73 | 01-OCT-08:61 | 540.00 | 685.95 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.38 |
November | 1543.68 | 14-NOV-19:03 | 1386.00 | 1090.18 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.84 |
December | 867.53 | 05-DEC-19:04 | 970.20 | 763.12 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 807.11 | 378.00 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3221.18 | 1386.00 | 1090.18 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 74.82 | 199.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1066.82 | 19-JAN-22:10 | 2263.36 | 1493.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.46 |
February | 2863.92 | 21-FEB-12:24 | 5029.68 | 6224.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.44 |
March | 2349.73 | 31-MAR-11:48 | 5029.68 | 6224.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.13 |
April | 3517.71 | 16-APR-21:25 | 4023.74 | 2489.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.58 |
May | 3102.68 | 08-MAY-13:05 | 5029.68 | 6224.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.01 |
June | 3602.62 | 30-JUN-19:10 | 1760.39 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.84 | 0.00 |
July | 3287.07 | 02-JUL-03:03 | 5281.16 | 1493.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.13 |
August | 3167.41 | 19-AUG-01:23 | 6790.07 | 746.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.33 |
September | 3815.67 | 15-SEP-00:35 | 18106.85 | 2987.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.62 |
October | 3645.60 | 23-OCT-00:23 | 22633.56 | 3734.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.87 |
November | 2703.30 | 21-NOV-01:33 | 6790.07 | 1120.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.17 |
December | 1102.63 | 05-DEC-22:10 | 2263.36 | 1493.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1066.82 | 1760.39 | 746.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3815.67 | 22633.56 | 6224.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.84 | 217.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1350.52 | 17-JAN-16:03 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 |
February | 3489.41 | 22-FEB-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.62 |
March | 3614.12 | 31-MAR-15:01 | 972.00 | 343.01 | 684.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.47 |
April | 3748.27 | 13-APR-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.28 |
May | 3919.14 | 25-MAY-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 39.57 | 0.00 |
June | 3949.17 | 17-JUN-18:02 | 702.00 | 735.03 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 | 0.00 |
July | 3918.09 | 24-JUL-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 32.39 | 0.00 |
August | 3744.75 | 08-AUG-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 34.82 | 0.00 |
September | 3784.73 | 06-SEP-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.08 |
October | 3715.85 | 21-OCT-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.03 |
November | 3426.56 | 17-NOV-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.66 |
December | 473.15 | 24-DEC-08:61 | 763.20 | 548.82 | 1896.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 473.15 | 324.00 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3949.17 | 972.00 | 735.03 | 1896.47 | 0.00 | 0.00 | 0.00 | 0.00 | 39.57 | 422.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 542.94 | 17-JAN-16:04 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.59 |
February | 1612.66 | 04-FEB-19:03 | 1170.00 | 1224.91 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.63 |
March | 3374.44 | 28-MAR-18:01 | 1247.40 | 981.16 | 1161.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.99 |
April | 3487.40 | 13-APR-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.16 |
May | 3742.96 | 25-MAY-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 39.28 | 0.00 |
June | 3764.70 | 17-JUN-18:02 | 702.00 | 734.94 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 5.19 | 0.00 |
July | 3731.43 | 24-JUL-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 32.18 | 0.00 |
August | 3598.07 | 08-AUG-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 34.79 | 0.00 |
September | 3524.78 | 06-SEP-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.99 |
October | 3435.07 | 21-OCT-15:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.51 |
November | 1745.42 | 15-NOV-19:03 | 1386.00 | 1090.18 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.15 |
December | 472.95 | 24-DEC-08:61 | 763.20 | 548.76 | 1896.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 472.95 | 324.00 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3764.70 | 1386.00 | 1224.91 | 1896.25 | 0.00 | 0.00 | 0.00 | 0.00 | 39.28 | 422.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1938.37 | 27-JAN-16:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.29 |
February | 1972.10 | 08-FEB-16:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.51 |
March | 2014.55 | 31-MAR-15:01 | 972.00 | 215.63 | 670.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.46 |
April | 2083.04 | 13-APR-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.22 |
May | 2123.46 | 21-MAY-15:02 | 324.00 | 152.48 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 0.00 |
June | 2101.59 | 17-JUN-18:02 | 702.00 | 462.06 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 | 0.00 |
July | 2072.23 | 24-JUL-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 17.34 | 0.00 |
August | 2147.77 | 25-AUG-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 17.78 | 0.00 |
September | 2135.64 | 01-SEP-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 | 0.00 |
October | 2098.72 | 21-OCT-15:02 | 324.00 | 152.48 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.60 |
November | 1974.51 | 16-NOV-16:01 | 972.00 | 215.63 | 670.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.31 |
December | 1890.36 | 02-DEC-16:01 | 378.00 | 177.90 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1890.36 | 324.00 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2147.77 | 972.00 | 462.06 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 17.78 | 163.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18085.65 | 27-JAN-23:55 | 53977.54 | 2062.70 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 961.96 |
February | 17813.05 | 21-FEB-12:24 | 59975.04 | 6875.68 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.45 |
March | 30064.41 | 31-MAR-20:19 | 239900.16 | 27502.72 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.26 |
April | 40758.98 | 16-APR-21:25 | 47980.03 | 3437.84 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.67 |
May | 32487.78 | 02-MAY-23:25 | 215910.14 | 5500.54 | 17994.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.57 |
June | 31557.35 | 02-JUN-21:57 | 80966.30 | 6188.11 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.03 |
July | 31426.58 | 07-JUL-23:59 | 188921.38 | 4812.98 | 15745.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.76 |
August | 32012.71 | 18-AUG-22:10 | 80966.30 | 3094.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.08 |
September | 34402.89 | 28-SEP-01:50 | 269887.68 | 3437.84 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.12 |
October | 31384.51 | 21-OCT-00:16 | 215910.14 | 5500.54 | 17994.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.31 |
November | 30642.82 | 20-NOV-23:30 | 53977.54 | 2062.70 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.24 |
December | 16907.50 | 19-DEC-23:00 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 948.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16907.50 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.45 | |
Maximum of Months | 40758.98 | 269887.68 | 27502.72 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 961.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19546.02 | 25-JAN-24:00 | 26988.77 | 1031.35 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 976.45 |
February | 21063.62 | 04-FEB-18:53 | 179925.12 | 20627.04 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.93 |
March | 31937.21 | 27-MAR-20:15 | 95960.06 | 11001.09 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.86 |
April | 43049.07 | 16-APR-21:25 | 47980.03 | 3437.84 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.72 |
May | 34203.04 | 02-MAY-23:25 | 215910.14 | 5500.54 | 17994.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.49 |
June | 33285.66 | 02-JUN-22:22 | 134943.84 | 5156.76 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.65 |
July | 32996.95 | 07-JUL-23:59 | 188921.38 | 4812.98 | 15745.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.09 |
August | 33779.43 | 18-AUG-22:10 | 80966.30 | 3094.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.45 |
September | 37773.20 | 28-SEP-01:50 | 269887.68 | 3437.84 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.87 |
October | 33548.57 | 21-OCT-00:16 | 215910.14 | 5500.54 | 17994.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.21 |
November | 33023.83 | 20-NOV-23:30 | 53977.54 | 2062.70 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.89 |
December | 17912.79 | 19-DEC-23:00 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 950.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17912.79 | 26988.77 | 1031.35 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.89 | |
Maximum of Months | 43049.07 | 269887.68 | 20627.04 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 976.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25005.09 | 21-JAN-11:50 | 800.57 | 302.73 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 559.90 |
February | 38912.26 | 21-FEB-12:24 | 5337.12 | 3027.31 | 149128.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 0.00 | 248.27 |
March | 36434.10 | 31-MAR-11:44 | 5337.12 | 3027.31 | 149128.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 0.00 | 291.56 |
April | 37209.71 | 01-APR-10:45 | 8005.68 | 3027.31 | 149128.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 0.00 | 299.20 |
May | 36596.81 | 08-MAY-13:05 | 5337.12 | 3027.31 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 238.35 |
June | 34660.72 | 02-JUN-05:30 | 18679.92 | 4843.69 | 125511.30 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 258.49 |
July | 33725.16 | 18-JUL-05:10 | 18679.92 | 4843.69 | 125511.30 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 248.53 |
August | 34047.70 | 19-AUG-06:16 | 13342.80 | 3632.77 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 269.70 |
September | 35436.96 | 25-SEP-07:07 | 6404.54 | 2906.22 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 0.00 | 287.30 |
October | 37075.98 | 27-OCT-10:38 | 5337.12 | 3027.31 | 149128.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 0.00 | 296.48 |
November | 36816.87 | 18-NOV-11:43 | 8005.68 | 3027.31 | 149128.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 0.00 | 297.28 |
December | 25436.64 | 28-DEC-11:50 | 1067.42 | 605.46 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 406.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 25005.09 | 800.57 | 302.73 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 238.35 | |
Maximum of Months | 38912.26 | 18679.92 | 4843.69 | 149128.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 0.00 | 559.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1522.48 | 27-JAN-13:50 | 532.32 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 578.17 |
February | 5804.26 | 21-FEB-12:24 | 5323.20 | 6587.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.99 |
March | 4824.24 | 31-MAR-11:48 | 5323.20 | 6587.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.97 |
April | 6871.58 | 16-APR-21:25 | 4258.56 | 2635.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.29 |
May | 6177.51 | 08-MAY-13:05 | 5323.20 | 6587.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.51 |
June | 7141.81 | 30-JUN-13:20 | 532.32 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.35 | 0.00 |
July | 6973.44 | 23-JUL-13:20 | 532.32 | 527.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.61 | 0.00 |
August | 6128.89 | 19-AUG-01:23 | 7186.32 | 790.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.31 |
September | 7389.78 | 15-SEP-00:35 | 19163.52 | 3162.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.07 |
October | 7191.03 | 23-OCT-00:23 | 23954.40 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.67 |
November | 5386.29 | 21-NOV-01:33 | 7186.32 | 1185.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.81 |
December | 1545.76 | 28-DEC-12:10 | 532.32 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1522.48 | 532.32 | 527.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7389.78 | 23954.40 | 6587.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.35 | 578.17 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.383225E+12 | 242298.23 | 18-JAN-20:49 | 0.145318E+13 | 1324353.49 | 04-JAN-17:00 |
February | 0.345007E+12 | 242436.32 | 08-FEB-20:10 | 0.956325E+12 | 1212837.71 | 14-FEB-07:10 |
March | 0.380384E+12 | 253046.41 | 28-MAR-19:49 | 0.785808E+12 | 1058187.27 | 05-MAR-07:10 |
April | 0.379774E+12 | 311057.67 | 23-APR-19:10 | 0.518018E+12 | 469195.29 | 16-APR-21:19 |
May | 0.442844E+12 | 356409.03 | 25-MAY-19:00 | 0.479491E+12 | 433855.24 | 08-MAY-20:40 |
June | 0.493295E+12 | 423260.36 | 29-JUN-18:10 | 0.440462E+12 | 391859.02 | 01-JUN-17:49 |
July | 0.549408E+12 | 392538.46 | 21-JUL-19:30 | 0.437508E+12 | 379077.92 | 14-JUL-17:00 |
August | 0.500915E+12 | 389734.17 | 31-AUG-19:19 | 0.432698E+12 | 376769.55 | 18-AUG-18:10 |
September | 0.410374E+12 | 316731.09 | 01-SEP-19:10 | 0.448896E+12 | 429085.44 | 23-SEP-21:19 |
October | 0.394709E+12 | 259112.61 | 20-OCT-19:10 | 0.520384E+12 | 473806.44 | 30-OCT-18:10 |
November | 0.371835E+12 | 248594.35 | 17-NOV-20:10 | 0.646051E+12 | 630750.51 | 25-NOV-17:40 |
December | 0.383748E+12 | 243197.97 | 04-DEC-20:49 | 0.132969E+13 | 1271929.41 | 24-DEC-23:00 |
Annual Sum or Average | 0.503552E+13 | 0.844851E+13 | ||||
Minimum of Months | 0.345007E+12 | 242298.23 | 0.432698E+12 | 376769.55 | ||
Maximum of Months | 0.549408E+12 | 423260.36 | 0.145318E+13 | 1324353.49 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.655545E+11 | 0.265743E+11 | 0.148212E+12 | 0.553310E+11 | 0.440137E+11 | 0.374328E+10 | 0.00 | 0.411749E+09 | 0.00 | 0.00 | 0.266205E+11 | 0.770680E+10 | 0.00 |
February | 0.590442E+11 | 0.218286E+11 | 0.133859E+12 | 0.499765E+11 | 0.387850E+11 | 0.428630E+10 | 0.00 | 0.161272E+10 | 0.00 | 0.00 | 0.240382E+11 | 0.696319E+10 | 0.00 |
March | 0.652164E+11 | 0.212168E+11 | 0.148223E+12 | 0.553337E+11 | 0.428204E+11 | 0.505892E+10 | 0.00 | 0.308771E+10 | 0.00 | 0.00 | 0.265716E+11 | 0.770393E+10 | 0.00 |
April | 0.627385E+11 | 0.175648E+11 | 0.143397E+12 | 0.535454E+11 | 0.432107E+11 | 0.819611E+10 | 0.00 | 0.162507E+11 | 0.00 | 0.00 | 0.223898E+11 | 0.746508E+10 | 0.00 |
May | 0.646261E+11 | 0.154793E+11 | 0.148223E+12 | 0.553317E+11 | 0.499350E+11 | 0.125133E+11 | 0.00 | 0.696911E+11 | 0.00 | 0.00 | 0.140854E+11 | 0.770426E+10 | 0.00 |
June | 0.624083E+11 | 0.135328E+11 | 0.143446E+12 | 0.535478E+11 | 0.503365E+11 | 0.129317E+11 | 0.00 | 0.134620E+12 | 0.00 | 0.00 | 0.986397E+10 | 0.745697E+10 | 0.00 |
July | 0.644559E+11 | 0.146636E+11 | 0.148174E+12 | 0.553287E+11 | 0.534411E+11 | 0.137343E+11 | 0.00 | 0.176770E+12 | 0.00 | 0.00 | 0.980224E+10 | 0.771255E+10 | 0.00 |
August | 0.648537E+11 | 0.169531E+11 | 0.148234E+12 | 0.553335E+11 | 0.518075E+11 | 0.132481E+11 | 0.00 | 0.130707E+12 | 0.00 | 0.00 | 0.672799E+10 | 0.770439E+10 | 0.00 |
September | 0.629440E+11 | 0.192333E+11 | 0.143408E+12 | 0.535457E+11 | 0.484717E+11 | 0.114312E+11 | 0.00 | 0.453790E+11 | 0.00 | 0.00 | 0.133656E+11 | 0.746624E+10 | 0.00 |
October | 0.653285E+11 | 0.229501E+11 | 0.148201E+12 | 0.553308E+11 | 0.471780E+11 | 0.757176E+10 | 0.00 | 0.120530E+11 | 0.00 | 0.00 | 0.231491E+11 | 0.770285E+10 | 0.00 |
November | 0.634367E+11 | 0.249059E+11 | 0.143462E+12 | 0.535469E+11 | 0.424661E+11 | 0.440664E+10 | 0.00 | 0.211175E+10 | 0.00 | 0.00 | 0.250505E+11 | 0.744955E+10 | 0.00 |
December | 0.655169E+11 | 0.272881E+11 | 0.148174E+12 | 0.553298E+11 | 0.441780E+11 | 0.352470E+10 | 0.00 | 0.314278E+09 | 0.00 | 0.00 | 0.266205E+11 | 0.771432E+10 | 0.00 |
Annual Sum or Average | 0.766124E+12 | 0.242191E+12 | 0.174501E+13 | 0.651481E+12 | 0.556644E+12 | 0.100646E+12 | 0.00 | 0.593009E+12 | 0.00 | 0.00 | 0.228285E+12 | 0.907501E+11 | 0.00 |
Minimum of Months | 0.590442E+11 | 0.135328E+11 | 0.133859E+12 | 0.499765E+11 | 0.387850E+11 | 0.352470E+10 | 0.00 | 0.314278E+09 | 0.00 | 0.00 | 0.672799E+10 | 0.696319E+10 | 0.00 |
Maximum of Months | 0.655545E+11 | 0.272881E+11 | 0.148234E+12 | 0.553337E+11 | 0.534411E+11 | 0.137343E+11 | 0.00 | 0.176770E+12 | 0.00 | 0.00 | 0.266205E+11 | 0.771432E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.992011E+12 | 0.00 | 0.309249E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.537390E+12 | 0.00 | 0.281731E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.322176E+12 | 0.00 | 0.311609E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.729943E+11 | 0.00 | 0.298068E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.252667E+11 | 0.00 | 0.302246E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.109773E+11 | 0.00 | 0.282371E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.467912E+10 | 0.00 | 0.281008E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.519212E+10 | 0.00 | 0.275467E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.344223E+11 | 0.00 | 0.267503E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.849242E+11 | 0.00 | 0.283556E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.213275E+12 | 0.00 | 0.285684E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.873960E+12 | 0.00 | 0.303914E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.317727E+13 | 0.00 | 0.348241E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.467912E+10 | 0.00 | 0.267503E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.992011E+12 | 0.00 | 0.311609E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 62892.57 | 02-JAN-20:10 | 15448.40 | 01-JAN-00:10 | 89475.41 | 02-JAN-07:10 | 39726.11 | 02-JAN-07:19 | 22803.67 | 12-JAN-19:10 | 6384.02 | 26-JAN-10:39 | 0.00 | 01-JAN-00:10 |
February | 62892.57 | 01-FEB-20:10 | 15448.40 | 01-FEB-00:10 | 89475.41 | 01-FEB-07:10 | 39726.11 | 01-FEB-07:19 | 24339.62 | 28-FEB-16:49 | 6231.59 | 14-FEB-10:39 | 0.00 | 01-FEB-00:10 |
March | 62892.57 | 01-MAR-20:10 | 15448.40 | 01-MAR-00:10 | 89475.41 | 01-MAR-07:10 | 39726.11 | 01-MAR-07:19 | 31538.53 | 27-MAR-20:10 | 5751.16 | 15-MAR-08:39 | 0.00 | 01-MAR-00:10 |
April | 62892.57 | 03-APR-19:10 | 15448.40 | 01-APR-00:10 | 89475.41 | 03-APR-06:10 | 39725.67 | 03-APR-06:19 | 34575.70 | 19-APR-13:30 | 5542.26 | 23-APR-19:19 | 0.00 | 01-APR-00:10 |
May | 62892.57 | 01-MAY-19:30 | 15448.40 | 01-MAY-00:10 | 89475.41 | 01-MAY-06:10 | 39724.33 | 01-MAY-06:19 | 34396.61 | 18-MAY-21:10 | 5824.16 | 18-MAY-19:19 | 0.00 | 01-MAY-00:10 |
June | 62892.57 | 01-JUN-19:49 | 15448.40 | 01-JUN-00:10 | 89475.41 | 01-JUN-06:10 | 39724.49 | 09-JUN-06:19 | 38567.59 | 30-JUN-20:10 | 6930.30 | 27-JUN-19:49 | 0.00 | 01-JUN-00:10 |
July | 62892.57 | 07-JUL-19:30 | 15448.40 | 01-JUL-00:10 | 89475.41 | 03-JUL-06:10 | 39724.33 | 03-JUL-06:19 | 36818.46 | 24-JUL-21:10 | 7224.92 | 21-JUL-19:30 | 0.00 | 01-JUL-00:10 |
August | 62892.57 | 01-AUG-19:40 | 15448.40 | 01-AUG-00:10 | 89475.41 | 01-AUG-06:10 | 39725.67 | 31-AUG-06:19 | 36859.80 | 25-AUG-21:10 | 6554.76 | 31-AUG-19:10 | 0.00 | 01-AUG-00:10 |
September | 62892.57 | 01-SEP-19:10 | 15448.40 | 01-SEP-00:10 | 89475.41 | 01-SEP-06:10 | 39726.11 | 18-SEP-06:19 | 46536.39 | 23-SEP-21:19 | 5618.42 | 01-SEP-18:10 | 0.00 | 01-SEP-00:10 |
October | 62892.57 | 02-OCT-19:10 | 15448.40 | 01-OCT-00:10 | 89475.41 | 02-OCT-06:10 | 39726.11 | 02-OCT-06:19 | 37483.16 | 20-OCT-22:19 | 5569.98 | 19-OCT-15:50 | 0.00 | 01-OCT-00:10 |
November | 62892.57 | 01-NOV-19:10 | 15448.40 | 01-NOV-00:10 | 89475.41 | 01-NOV-06:10 | 39726.11 | 01-NOV-06:19 | 33476.13 | 21-NOV-05:19 | 5528.31 | 28-NOV-16:10 | 0.00 | 01-NOV-00:10 |
December | 62892.57 | 01-DEC-20:10 | 15448.40 | 01-DEC-00:10 | 89475.41 | 01-DEC-07:10 | 39726.11 | 01-DEC-07:19 | 23149.64 | 01-DEC-19:10 | 6393.20 | 20-DEC-10:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 62892.57 | 15448.40 | 89475.41 | 39724.33 | 22803.67 | 5528.31 | 0.00 | |||||||
Maximum of Months | 62892.57 | 15448.40 | 89475.41 | 39726.11 | 46536.39 | 7224.92 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 4712.28 | 27-JAN-14:00 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:20 | 4740.02 | 04-JAN-19:10 | 0.00 |
February | 15546.52 | 22-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 4739.76 | 02-FEB-07:40 | 0.00 |
March | 19680.22 | 19-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:20 | 4738.46 | 15-MAR-06:00 | 0.00 |
April | 95263.53 | 23-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4738.47 | 10-APR-18:10 | 0.00 |
May | 138349.63 | 25-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:10 | 4738.30 | 31-MAY-06:40 | 0.00 |
June | 203641.74 | 29-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-00:10 | 4738.71 | 29-JUN-18:10 | 0.00 |
July | 170607.57 | 15-JUL-15:09 | 0.00 | 0.00 | 9938.94 | 01-JUL-01:00 | 4738.30 | 17-JUL-06:10 | 0.00 |
August | 167920.88 | 08-AUG-15:09 | 0.00 | 0.00 | 9938.94 | 01-AUG-23:49 | 4738.36 | 21-AUG-18:10 | 0.00 |
September | 115214.95 | 01-SEP-15:20 | 0.00 | 0.00 | 9938.94 | 01-SEP-11:30 | 4738.28 | 26-SEP-06:49 | 0.00 |
October | 78924.01 | 19-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:10 | 4738.24 | 03-OCT-18:00 | 0.00 |
November | 24943.05 | 01-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4738.29 | 20-NOV-19:40 | 0.00 |
December | 3116.03 | 02-DEC-16:10 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 4740.07 | 14-DEC-07:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3116.03 | 0.00 | 0.00 | 9938.94 | 4738.24 | 0.00 | |||
Maximum of Months | 203641.74 | 0.00 | 0.00 | 9938.94 | 4740.07 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 242298.23 | 18-JAN-20:49 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 20391.58 | 5239.11 | 0.00 | 1323.09 | 0.00 |
February | 242436.32 | 08-FEB-20:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 20284.52 | 4985.95 | 0.00 | 1797.15 | 0.00 |
March | 253046.41 | 28-MAR-19:49 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 29518.63 | 4976.51 | 0.00 | 3771.87 | 0.00 |
April | 311057.67 | 23-APR-19:10 | 57527.06 | 87285.99 | 15448.40 | 32094.91 | 24311.60 | 5466.41 | 0.00 | 81902.52 | 0.00 |
May | 356409.03 | 25-MAY-19:00 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 29567.76 | 5505.14 | 0.00 | 106191.27 | 0.00 |
June | 423260.36 | 29-JUN-18:10 | 53571.31 | 79417.81 | 0.00 | 31835.81 | 30793.88 | 6905.94 | 0.00 | 203641.74 | 0.00 |
July | 392538.46 | 21-JUL-19:30 | 62892.57 | 88772.42 | 0.00 | 32157.42 | 31972.46 | 7224.92 | 0.00 | 162508.02 | 0.00 |
August | 389734.17 | 31-AUG-19:19 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 28807.01 | 6507.63 | 0.00 | 147466.78 | 0.00 |
September | 316731.09 | 01-SEP-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 29943.20 | 5398.03 | 0.00 | 76717.06 | 0.00 |
October | 259112.61 | 20-OCT-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 26271.80 | 4801.16 | 0.00 | 12970.35 | 0.00 |
November | 248594.35 | 17-NOV-20:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 26571.27 | 5080.88 | 0.00 | 1985.19 | 0.00 |
December | 243197.97 | 04-DEC-20:49 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 21052.75 | 5252.66 | 0.00 | 1333.45 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 242298.23 | 53571.31 | 79417.81 | 0.00 | 31835.81 | 20284.52 | 4801.16 | 0.00 | 1323.09 | 0.00 | |
Maximum of Months | 423260.36 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 31972.46 | 7224.92 | 0.00 | 203641.74 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 1101672.72 | 06-JAN-04:49 | 0.00 | 310273.61 | 30-JAN-21:19 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 1029174.22 | 14-FEB-07:10 | 0.00 | 311602.87 | 23-FEB-21:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 946630.91 | 05-MAR-04:00 | 0.00 | 311596.73 | 01-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 204985.37 | 05-APR-08:09 | 0.00 | 308837.94 | 04-APR-20:19 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 115531.08 | 22-MAY-03:09 | 0.00 | 303900.47 | 01-MAY-20:40 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 95137.45 | 03-JUN-22:49 | 0.00 | 295488.03 | 01-JUN-20:49 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 96123.03 | 08-JUL-00:49 | 0.00 | 284479.69 | 10-JUL-20:49 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 86781.51 | 19-AUG-01:49 | 0.00 | 279622.62 | 01-AUG-20:30 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 124213.58 | 23-SEP-21:19 | 0.00 | 282993.35 | 05-SEP-20:10 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 193371.02 | 30-OCT-08:09 | 0.00 | 288233.46 | 27-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 320445.59 | 25-NOV-09:09 | 0.00 | 297891.62 | 30-NOV-21:40 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 1036097.08 | 24-DEC-05:00 | 0.00 | 305172.30 | 29-DEC-21:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 86781.51 | 0.00 | 279622.62 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 1101672.72 | 0.00 | 311602.87 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.39 | 0.67 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 20.39 | 0.67 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.39 | 0.67 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.83 | 19.95 | 22.83 | 19.95 | 0.00 | 19.95 | 0.00 | 19.95 |
February | 0.17 | 20.44 | 0.17 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.67 | 20.35 | 2.67 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Annual Sum or Average | 25.67 | 20.00 | 25.67 | 20.00 | 0.00 | 20.00 | 0.00 | 20.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.83 | 20.44 | 22.83 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 20.32 | 1.67 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.67 | 20.32 | 1.67 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 20.32 | 1.67 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.50 | 16.36 | 5.50 | 16.36 | 0.00 | 16.36 | 0.00 | 16.36 |
February | 0.33 | 17.53 | 0.33 | 17.53 | 0.67 | 21.42 | 0.67 | 22.72 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 25.03 | 9.83 | 25.03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 25.01 | 22.83 | 25.01 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 25.01 | 15.00 | 25.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 25.11 | 2.33 | 25.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.78 | 0.33 | 24.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.82 | 1.67 | 24.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 25.09 | 26.83 | 25.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 57.50 | 25.05 | 57.50 | 25.05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 25.01 | 5.33 | 25.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5.83 | 16.43 | 5.83 | 16.43 | 142.33 | 24.39 | 142.33 | 24.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.50 | 17.53 | 5.50 | 17.53 | 57.50 | 25.11 | 57.50 | 25.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.33 | 19.86 | 7.33 | 19.86 | 0.00 | 19.86 | 0.00 | 19.86 |
February | 0.17 | 20.44 | 0.17 | 20.44 | 0.17 | 21.87 | 0.17 | 22.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.57 | 0.17 | 24.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.60 | 0.17 | 24.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.56 | 0.17 | 24.56 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7.50 | 19.88 | 7.50 | 19.88 | 0.67 | 20.08 | 0.67 | 20.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.33 | 20.44 | 7.33 | 20.44 | 0.17 | 24.60 | 0.17 | 24.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 20.25 | 2.00 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.00 | 20.25 | 2.00 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 20.25 | 2.00 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.78 | 0.50 | 21.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.80 | 1.17 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.74 | 1.67 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.74 | 1.33 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.74 | 0.33 | 21.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.17 | 21.75 | 5.17 | 21.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.80 | 1.67 | 21.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.81 | 1.00 | 21.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.77 | 0.83 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.00 | 21.79 | 2.00 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.81 | 1.00 | 21.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 20.35 | 3.50 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
February | 1.17 | 20.47 | 1.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.76 | 1.50 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.71 | 1.17 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.00 | 20.45 | 3.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
Annual Sum or Average | 7.67 | 20.41 | 7.67 | 20.41 | 2.67 | 20.61 | 2.67 | 20.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 20.47 | 3.50 | 20.47 | 1.50 | 21.76 | 1.50 | 21.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.87 | 0.67 | 21.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.89 | 1.33 | 21.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.73 | 0.83 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.73 | 0.50 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.67 | 21.81 | 3.67 | 21.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.89 | 1.33 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.90 | 0.67 | 21.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.86 | 2.33 | 21.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.81 | 1.00 | 21.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.74 | 0.50 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.50 | 21.84 | 4.50 | 21.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.90 | 2.33 | 21.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.77 | 1.50 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.80 | 2.33 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.74 | 2.17 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.75 | 2.00 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.75 | 0.33 | 21.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.50 | 21.77 | 8.50 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.80 | 2.33 | 21.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.72 | 0.83 | 21.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.83 | 1.83 | 21.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.75 | 1.33 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.50 | 21.77 | 4.50 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.83 | 1.83 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.74 | 1.00 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.79 | 0.83 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.98 | 1.50 | 21.98 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.67 | 21.85 | 3.67 | 21.85 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.98 | 1.50 | 21.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.31 | 0.67 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.60 | 0.17 | 24.60 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.75 | 2.50 | 24.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.74 | 3.67 | 24.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.73 | 3.83 | 24.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.64 | 1.00 | 24.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.66 | 1.00 | 24.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.71 | 5.17 | 24.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.76 | 4.17 | 24.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.76 | 0.33 | 24.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 20.31 | 0.67 | 20.31 | 21.83 | 24.47 | 21.83 | 24.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.31 | 0.67 | 20.31 | 5.17 | 24.76 | 5.17 | 24.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.43 | 0.33 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.67 | 0.33 | 24.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.81 | 2.67 | 24.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.76 | 4.17 | 24.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.77 | 4.00 | 24.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.66 | 1.17 | 24.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.69 | 1.17 | 24.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 24.72 | 6.83 | 24.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 24.76 | 6.17 | 24.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.70 | 0.83 | 24.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.43 | 0.33 | 20.43 | 27.33 | 24.65 | 27.33 | 24.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.43 | 0.33 | 20.43 | 6.83 | 24.81 | 6.83 | 24.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 18.17 | 1.17 | 18.17 | 0.00 | 18.17 | 0.00 | 18.17 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 25.38 | 6.50 | 25.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 25.04 | 10.83 | 25.04 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 | 25.06 | 35.33 | 25.06 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 25.11 | 31.50 | 25.11 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 25.04 | 7.50 | 25.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.90 | 1.50 | 24.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.02 | 1.67 | 25.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 45.00 | 25.15 | 45.00 | 25.15 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 25.16 | 75.00 | 25.16 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 25.18 | 11.00 | 25.18 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 18.17 | 1.17 | 18.17 | 225.83 | 25.06 | 225.83 | 25.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 18.17 | 1.17 | 18.17 | 75.00 | 25.38 | 75.00 | 25.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.40 | 80.67 | 22.26 | 80.67 | 22.14 |
February | 672.00 | 22.62 | 2.17 | 22.61 | 2.17 | 22.61 |
March | 744.00 | 22.07 | 2.83 | 22.06 | 2.83 | 22.06 |
April | 720.00 | 22.01 | 0.00 | 22.01 | 0.00 | 22.01 |
May | 744.00 | 22.34 | 0.00 | 22.34 | 0.00 | 22.34 |
June | 720.00 | 22.64 | 35.50 | 22.65 | 35.50 | 22.65 |
July | 516.33 | 23.15 | 111.00 | 23.23 | 66.17 | 23.25 |
August | 132.33 | 23.58 | 301.67 | 23.84 | 46.17 | 23.84 |
September | 171.33 | 23.74 | 143.50 | 23.84 | 12.00 | 23.85 |
October | 347.50 | 23.87 | 0.00 | 23.87 | 0.00 | 23.87 |
November | 628.00 | 23.90 | 0.50 | 23.90 | 0.00 | 23.90 |
December | 743.83 | 23.11 | 4.50 | 23.10 | 4.50 | 23.08 |
Annual Sum or Average | 6883.33 | 22.76 | 682.33 | 22.82 | 250.00 | 22.82 |
Minimum of Months | 132.33 | 22.01 | 0.00 | 22.01 | 0.00 | 22.01 |
Maximum of Months | 744.00 | 23.90 | 301.67 | 23.90 | 80.67 | 23.90 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 738.83 | 21.03 | 644.83 | 21.00 | 644.83 | 20.98 |
February | 639.83 | 21.14 | 442.83 | 21.11 | 432.17 | 21.08 |
March | 702.00 | 21.16 | 375.50 | 21.14 | 362.33 | 21.10 |
April | 650.33 | 21.32 | 114.33 | 21.39 | 83.83 | 21.35 |
May | 619.17 | 21.58 | 79.83 | 21.81 | 4.50 | 21.81 |
June | 549.50 | 21.62 | 120.17 | 21.99 | 0.00 | 21.99 |
July | 453.00 | 21.86 | 207.83 | 22.40 | 0.00 | 22.40 |
August | 502.67 | 21.68 | 181.83 | 22.21 | 0.00 | 22.21 |
September | 595.33 | 21.45 | 97.17 | 21.79 | 0.00 | 21.79 |
October | 676.00 | 21.19 | 103.00 | 21.37 | 49.50 | 21.35 |
November | 696.67 | 21.08 | 376.00 | 21.06 | 371.00 | 21.05 |
December | 743.17 | 21.03 | 669.83 | 21.02 | 669.83 | 21.01 |
Annual Sum or Average | 7566.50 | 21.31 | 3413.17 | 21.41 | 2618.00 | 21.33 |
Minimum of Months | 453.00 | 21.03 | 79.83 | 21.00 | 0.00 | 20.98 |
Maximum of Months | 743.17 | 21.86 | 669.83 | 22.40 | 669.83 | 22.40 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.09 | 413.83 | 21.06 | 413.83 | 21.04 |
February | 672.00 | 21.34 | 182.17 | 21.27 | 182.17 | 21.22 |
March | 744.00 | 21.65 | 77.17 | 21.59 | 77.17 | 21.54 |
April | 710.17 | 22.40 | 2.50 | 22.41 | 0.00 | 22.41 |
May | 567.67 | 22.99 | 56.17 | 23.07 | 0.00 | 23.07 |
June | 451.67 | 23.05 | 206.17 | 23.29 | 75.00 | 23.34 |
July | 260.83 | 23.35 | 389.00 | 23.65 | 116.83 | 23.68 |
August | 297.00 | 23.13 | 311.17 | 23.49 | 74.33 | 23.52 |
September | 536.50 | 22.98 | 62.83 | 23.06 | 18.50 | 23.07 |
October | 710.50 | 22.46 | 0.00 | 22.46 | 0.00 | 22.46 |
November | 720.00 | 21.68 | 34.17 | 21.65 | 34.17 | 21.62 |
December | 744.00 | 21.12 | 364.50 | 21.08 | 364.50 | 21.06 |
Annual Sum or Average | 7158.33 | 22.08 | 2099.67 | 22.15 | 1356.50 | 22.08 |
Minimum of Months | 260.83 | 21.09 | 0.00 | 21.06 | 0.00 | 21.04 |
Maximum of Months | 744.00 | 23.35 | 413.83 | 23.65 | 413.83 | 23.68 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 663.50 | 21.00 | 663.50 | 21.00 |
February | 672.00 | 21.01 | 527.83 | 21.01 | 527.83 | 21.00 |
March | 744.00 | 21.05 | 360.17 | 21.03 | 360.17 | 21.03 |
April | 720.00 | 21.46 | 47.67 | 21.44 | 47.67 | 21.41 |
May | 697.83 | 22.57 | 7.67 | 22.58 | 1.00 | 22.57 |
June | 540.50 | 22.87 | 83.17 | 23.01 | 0.00 | 23.01 |
July | 319.17 | 23.17 | 157.67 | 23.40 | 0.00 | 23.40 |
August | 522.67 | 23.05 | 58.33 | 23.14 | 0.00 | 23.14 |
September | 689.83 | 22.66 | 4.00 | 22.67 | 0.00 | 22.67 |
October | 744.00 | 21.72 | 0.00 | 21.72 | 0.00 | 21.72 |
November | 720.00 | 21.09 | 206.33 | 21.07 | 206.33 | 21.05 |
December | 744.00 | 21.00 | 620.50 | 21.00 | 620.50 | 21.00 |
Annual Sum or Average | 7858.00 | 21.76 | 2736.83 | 21.65 | 2427.00 | 21.53 |
Minimum of Months | 319.17 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.17 | 663.50 | 23.40 | 663.50 | 23.40 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.99 | 710.67 | 20.99 | 710.67 | 20.99 |
February | 672.00 | 21.00 | 566.50 | 21.00 | 566.50 | 21.00 |
March | 744.00 | 21.01 | 440.17 | 21.01 | 440.17 | 21.01 |
April | 720.00 | 21.28 | 91.17 | 21.25 | 91.17 | 21.23 |
May | 734.83 | 22.38 | 5.83 | 22.37 | 5.83 | 22.36 |
June | 618.33 | 22.73 | 49.67 | 22.81 | 0.00 | 22.81 |
July | 496.33 | 23.11 | 34.00 | 23.16 | 0.00 | 23.16 |
August | 677.17 | 22.95 | 0.33 | 22.95 | 0.00 | 22.95 |
September | 713.83 | 22.42 | 0.00 | 22.42 | 0.00 | 22.42 |
October | 744.00 | 21.47 | 7.33 | 21.47 | 7.33 | 21.46 |
November | 720.00 | 21.02 | 308.50 | 21.01 | 308.50 | 21.01 |
December | 744.00 | 21.00 | 667.83 | 21.00 | 667.83 | 21.00 |
Annual Sum or Average | 8328.50 | 21.72 | 2882.00 | 21.56 | 2798.00 | 21.45 |
Minimum of Months | 496.33 | 20.99 | 0.00 | 20.99 | 0.00 | 20.99 |
Maximum of Months | 744.00 | 23.11 | 710.67 | 23.16 | 710.67 | 23.16 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 446.33 | 21.66 | 289.83 | 22.28 | 117.50 | 22.33 |
February | 326.67 | 22.20 | 313.00 | 22.90 | 116.00 | 23.01 |
March | 264.67 | 22.65 | 409.33 | 23.30 | 131.67 | 23.43 |
April | 237.67 | 23.22 | 536.00 | 23.48 | 160.00 | 23.60 |
May | 278.83 | 23.78 | 655.83 | 23.54 | 250.33 | 23.66 |
June | 296.50 | 23.94 | 686.67 | 23.48 | 291.00 | 23.60 |
July | 332.83 | 23.96 | 728.17 | 23.47 | 332.50 | 23.59 |
August | 316.67 | 23.95 | 718.33 | 23.46 | 313.50 | 23.58 |
September | 291.50 | 23.99 | 666.33 | 23.61 | 277.33 | 23.72 |
October | 256.00 | 23.71 | 621.67 | 23.63 | 203.33 | 23.77 |
November | 251.00 | 22.84 | 443.67 | 23.37 | 137.83 | 23.48 |
December | 419.67 | 21.95 | 282.83 | 22.67 | 109.17 | 22.82 |
Annual Sum or Average | 3718.33 | 23.06 | 6351.67 | 23.31 | 2440.17 | 23.44 |
Minimum of Months | 237.67 | 21.66 | 282.83 | 22.28 | 109.17 | 22.33 |
Maximum of Months | 446.33 | 23.99 | 728.17 | 23.63 | 332.50 | 23.77 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 725.83 | 21.10 | 434.00 | 21.06 | 432.00 | 21.04 |
February | 613.17 | 21.37 | 248.33 | 21.38 | 216.83 | 21.30 |
March | 675.17 | 21.64 | 138.33 | 21.68 | 97.83 | 21.61 |
April | 576.17 | 22.05 | 74.17 | 22.26 | 0.50 | 22.26 |
May | 408.67 | 22.54 | 194.00 | 22.93 | 7.17 | 22.94 |
June | 347.83 | 22.73 | 367.00 | 23.19 | 106.50 | 23.25 |
July | 292.17 | 23.26 | 582.83 | 23.49 | 199.17 | 23.53 |
August | 317.50 | 22.96 | 521.17 | 23.39 | 165.50 | 23.44 |
September | 380.00 | 22.39 | 244.67 | 22.92 | 30.17 | 22.94 |
October | 590.33 | 21.90 | 92.67 | 22.17 | 1.17 | 22.17 |
November | 682.67 | 21.48 | 120.50 | 21.48 | 100.33 | 21.43 |
December | 737.17 | 21.10 | 467.50 | 21.06 | 466.67 | 21.05 |
Annual Sum or Average | 6346.67 | 21.84 | 3485.17 | 22.13 | 1823.83 | 22.07 |
Minimum of Months | 292.17 | 21.10 | 74.17 | 21.06 | 0.50 | 21.04 |
Maximum of Months | 737.17 | 23.26 | 582.83 | 23.49 | 466.67 | 23.53 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.36 | 255.83 | 21.26 | 255.83 | 21.21 |
February | 672.00 | 21.83 | 76.00 | 21.75 | 76.00 | 21.68 |
March | 740.83 | 22.20 | 14.33 | 22.18 | 14.33 | 22.15 |
April | 645.33 | 22.81 | 9.83 | 22.82 | 0.00 | 22.82 |
May | 355.83 | 23.12 | 152.67 | 23.35 | 6.33 | 23.36 |
June | 271.00 | 23.32 | 373.00 | 23.63 | 110.33 | 23.68 |
July | 217.83 | 23.81 | 619.50 | 23.82 | 187.50 | 23.85 |
August | 225.33 | 23.63 | 586.83 | 23.78 | 163.67 | 23.81 |
September | 246.50 | 23.06 | 231.67 | 23.46 | 43.50 | 23.50 |
October | 529.83 | 22.69 | 27.67 | 22.76 | 0.00 | 22.76 |
November | 715.83 | 22.23 | 2.33 | 22.23 | 2.17 | 22.22 |
December | 744.00 | 21.42 | 205.33 | 21.33 | 205.33 | 21.27 |
Annual Sum or Average | 6108.33 | 22.32 | 2555.00 | 22.59 | 1065.00 | 22.57 |
Minimum of Months | 217.83 | 21.36 | 2.33 | 21.26 | 0.00 | 21.21 |
Maximum of Months | 744.00 | 23.81 | 619.50 | 23.82 | 255.83 | 23.85 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.52 | 741.33 | 20.52 | 741.33 | 20.52 |
February | 672.00 | 20.76 | 598.67 | 20.72 | 598.67 | 20.70 |
March | 744.00 | 20.90 | 555.33 | 20.81 | 555.33 | 20.78 |
April | 709.50 | 21.24 | 225.67 | 21.15 | 223.33 | 21.08 |
May | 686.50 | 21.49 | 22.17 | 21.53 | 6.67 | 21.52 |
June | 628.67 | 21.42 | 30.50 | 21.51 | 0.67 | 21.51 |
July | 600.67 | 21.33 | 61.00 | 21.51 | 0.17 | 21.51 |
August | 629.17 | 21.35 | 50.83 | 21.50 | 0.17 | 21.50 |
September | 673.33 | 21.40 | 7.67 | 21.42 | 0.00 | 21.42 |
October | 731.00 | 21.06 | 247.83 | 20.96 | 245.83 | 20.90 |
November | 720.00 | 20.75 | 602.50 | 20.70 | 602.50 | 20.69 |
December | 744.00 | 20.50 | 744.00 | 20.50 | 744.00 | 20.50 |
Annual Sum or Average | 8282.83 | 21.04 | 3887.50 | 20.94 | 3718.67 | 20.87 |
Minimum of Months | 600.67 | 20.50 | 7.67 | 20.50 | 0.00 | 20.50 |
Maximum of Months | 744.00 | 21.49 | 744.00 | 21.53 | 744.00 | 21.52 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.47 | 744.00 | 20.47 | 744.00 | 20.47 |
February | 672.00 | 20.54 | 656.33 | 20.53 | 656.33 | 20.53 |
March | 744.00 | 20.65 | 649.83 | 20.61 | 649.83 | 20.59 |
April | 717.67 | 21.06 | 320.17 | 20.96 | 319.00 | 20.91 |
May | 708.50 | 21.49 | 21.50 | 21.50 | 13.83 | 21.49 |
June | 651.50 | 21.47 | 19.00 | 21.52 | 0.17 | 21.52 |
July | 630.50 | 21.41 | 41.00 | 21.52 | 0.33 | 21.52 |
August | 670.83 | 21.43 | 24.67 | 21.50 | 0.00 | 21.50 |
September | 708.17 | 21.39 | 2.83 | 21.40 | 0.50 | 21.40 |
October | 744.00 | 20.93 | 316.83 | 20.83 | 316.83 | 20.77 |
November | 720.00 | 20.57 | 665.50 | 20.56 | 665.50 | 20.55 |
December | 744.00 | 20.47 | 744.00 | 20.47 | 744.00 | 20.47 |
Annual Sum or Average | 8455.17 | 20.98 | 4205.67 | 20.85 | 4110.33 | 20.77 |
Minimum of Months | 630.50 | 20.47 | 2.83 | 20.47 | 0.00 | 20.47 |
Maximum of Months | 744.00 | 21.49 | 744.00 | 21.52 | 744.00 | 21.52 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.56 | 744.00 | 20.56 | 744.00 | 20.56 |
February | 672.00 | 20.65 | 662.83 | 20.64 | 662.83 | 20.64 |
March | 744.00 | 20.77 | 621.83 | 20.74 | 621.83 | 20.73 |
April | 720.00 | 21.08 | 201.17 | 21.04 | 201.17 | 21.01 |
May | 744.00 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
June | 720.00 | 21.48 | 0.67 | 21.48 | 0.67 | 21.48 |
July | 744.00 | 21.52 | 0.83 | 21.52 | 0.83 | 21.52 |
August | 744.00 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
September | 720.00 | 21.29 | 0.00 | 21.29 | 0.00 | 21.29 |
October | 744.00 | 21.05 | 97.17 | 21.02 | 97.17 | 20.99 |
November | 720.00 | 20.80 | 579.33 | 20.77 | 579.33 | 20.75 |
December | 744.00 | 20.56 | 733.00 | 20.56 | 733.00 | 20.56 |
Annual Sum or Average | 8760.00 | 21.05 | 3640.83 | 20.93 | 3640.83 | 20.87 |
Minimum of Months | 672.00 | 20.56 | 0.00 | 20.56 | 0.00 | 20.56 |
Maximum of Months | 744.00 | 21.52 | 744.00 | 21.52 | 744.00 | 21.52 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.51 | 741.17 | 20.51 | 741.17 | 20.51 |
February | 672.00 | 20.76 | 596.00 | 20.71 | 596.00 | 20.70 |
March | 744.00 | 20.99 | 527.83 | 20.88 | 527.83 | 20.83 |
April | 712.17 | 21.36 | 200.83 | 21.26 | 200.83 | 21.19 |
May | 686.17 | 21.54 | 9.17 | 21.55 | 3.67 | 21.55 |
June | 592.33 | 21.36 | 34.00 | 21.47 | 0.50 | 21.47 |
July | 578.17 | 21.28 | 72.33 | 21.51 | 0.17 | 21.51 |
August | 617.17 | 21.34 | 37.50 | 21.45 | 0.00 | 21.45 |
September | 660.50 | 21.38 | 6.17 | 21.40 | 1.00 | 21.40 |
October | 731.17 | 21.08 | 247.00 | 20.97 | 247.00 | 20.91 |
November | 720.00 | 20.73 | 604.67 | 20.69 | 604.67 | 20.68 |
December | 744.00 | 20.49 | 739.83 | 20.49 | 739.83 | 20.49 |
Annual Sum or Average | 8201.67 | 21.05 | 3816.50 | 20.95 | 3662.67 | 20.87 |
Minimum of Months | 578.17 | 20.49 | 6.17 | 20.49 | 0.00 | 20.49 |
Maximum of Months | 744.00 | 21.54 | 741.17 | 21.55 | 741.17 | 21.55 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.47 | 744.00 | 20.47 | 744.00 | 20.47 |
February | 672.00 | 20.53 | 662.33 | 20.52 | 662.33 | 20.52 |
March | 744.00 | 20.71 | 628.67 | 20.67 | 628.67 | 20.65 |
April | 719.83 | 21.25 | 277.17 | 21.13 | 277.17 | 21.07 |
May | 703.33 | 21.56 | 8.50 | 21.56 | 7.67 | 21.55 |
June | 616.50 | 21.43 | 11.33 | 21.47 | 0.17 | 21.47 |
July | 585.33 | 21.30 | 20.50 | 21.37 | 0.00 | 21.37 |
August | 639.17 | 21.39 | 5.00 | 21.40 | 0.00 | 21.40 |
September | 708.33 | 21.46 | 2.83 | 21.46 | 2.17 | 21.46 |
October | 744.00 | 20.95 | 320.83 | 20.86 | 320.83 | 20.80 |
November | 720.00 | 20.57 | 654.33 | 20.55 | 654.33 | 20.54 |
December | 744.00 | 20.48 | 744.00 | 20.48 | 744.00 | 20.48 |
Annual Sum or Average | 8340.50 | 20.99 | 4079.50 | 20.86 | 4041.33 | 20.78 |
Minimum of Months | 585.33 | 20.47 | 2.83 | 20.47 | 0.00 | 20.47 |
Maximum of Months | 744.00 | 21.56 | 744.00 | 21.56 | 744.00 | 21.55 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 651.50 | 21.00 | 651.50 | 21.00 |
February | 672.00 | 21.02 | 472.83 | 21.01 | 472.83 | 21.01 |
March | 744.00 | 21.09 | 285.83 | 21.07 | 285.83 | 21.05 |
April | 720.00 | 21.70 | 21.50 | 21.68 | 21.50 | 21.66 |
May | 697.00 | 22.78 | 4.50 | 22.79 | 0.00 | 22.79 |
June | 583.67 | 23.06 | 133.50 | 23.18 | 74.67 | 23.21 |
July | 339.83 | 23.43 | 255.00 | 23.58 | 120.67 | 23.59 |
August | 553.50 | 23.14 | 98.17 | 23.19 | 70.33 | 23.21 |
September | 706.50 | 22.63 | 18.83 | 22.64 | 17.00 | 22.65 |
October | 744.00 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
November | 720.00 | 21.03 | 217.33 | 21.02 | 217.33 | 21.02 |
December | 744.00 | 21.00 | 617.33 | 21.00 | 617.33 | 21.00 |
Annual Sum or Average | 7968.50 | 21.83 | 2776.33 | 21.74 | 2549.00 | 21.65 |
Minimum of Months | 339.83 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.43 | 651.50 | 23.58 | 651.50 | 23.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.49 | 744.00 | 20.49 | 744.00 | 20.49 |
February | 672.00 | 20.67 | 628.33 | 20.64 | 628.33 | 20.63 |
March | 744.00 | 20.81 | 601.67 | 20.74 | 601.67 | 20.71 |
April | 706.17 | 21.15 | 357.67 | 21.03 | 355.17 | 20.97 |
May | 680.17 | 21.45 | 36.67 | 21.48 | 17.67 | 21.47 |
June | 615.17 | 21.37 | 49.00 | 21.50 | 6.50 | 21.50 |
July | 594.67 | 21.30 | 80.17 | 21.54 | 2.67 | 21.55 |
August | 625.83 | 21.32 | 72.50 | 21.50 | 7.83 | 21.50 |
September | 671.67 | 21.33 | 25.50 | 21.35 | 16.00 | 21.34 |
October | 730.17 | 20.95 | 364.33 | 20.84 | 362.00 | 20.78 |
November | 720.00 | 20.66 | 643.00 | 20.63 | 643.00 | 20.62 |
December | 744.00 | 20.48 | 744.00 | 20.48 | 744.00 | 20.48 |
Annual Sum or Average | 8247.83 | 20.98 | 4346.83 | 20.89 | 4128.83 | 20.82 |
Minimum of Months | 594.67 | 20.48 | 25.50 | 20.48 | 2.67 | 20.48 |
Maximum of Months | 744.00 | 21.45 | 744.00 | 21.54 | 744.00 | 21.55 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.47 | 744.00 | 20.47 | 744.00 | 20.47 |
February | 672.00 | 20.51 | 663.83 | 20.50 | 663.83 | 20.50 |
March | 744.00 | 20.59 | 686.17 | 20.56 | 686.17 | 20.55 |
April | 717.67 | 20.97 | 445.83 | 20.87 | 444.50 | 20.82 |
May | 701.50 | 21.44 | 38.50 | 21.45 | 26.67 | 21.43 |
June | 640.83 | 21.42 | 32.67 | 21.50 | 5.67 | 21.50 |
July | 620.33 | 21.36 | 53.17 | 21.51 | 2.50 | 21.52 |
August | 661.83 | 21.38 | 41.83 | 21.47 | 9.33 | 21.47 |
September | 707.67 | 21.31 | 27.50 | 21.31 | 24.00 | 21.29 |
October | 744.00 | 20.81 | 438.33 | 20.71 | 438.33 | 20.67 |
November | 720.00 | 20.52 | 683.33 | 20.51 | 683.33 | 20.50 |
December | 744.00 | 20.47 | 744.00 | 20.47 | 744.00 | 20.47 |
Annual Sum or Average | 8417.83 | 20.92 | 4599.17 | 20.81 | 4472.33 | 20.74 |
Minimum of Months | 620.33 | 20.47 | 27.50 | 20.47 | 2.50 | 20.47 |
Maximum of Months | 744.00 | 21.44 | 744.00 | 21.51 | 744.00 | 21.52 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.86 | 659.33 | 20.77 | 659.33 | 20.74 |
February | 658.50 | 21.10 | 486.33 | 20.97 | 486.33 | 20.92 |
March | 727.17 | 21.13 | 459.33 | 21.00 | 459.33 | 20.94 |
April | 687.83 | 21.30 | 198.00 | 21.21 | 195.17 | 21.14 |
May | 687.00 | 21.48 | 22.17 | 21.52 | 6.17 | 21.51 |
June | 630.67 | 21.39 | 27.83 | 21.47 | 2.50 | 21.48 |
July | 622.50 | 21.36 | 60.67 | 21.53 | 3.33 | 21.54 |
August | 637.50 | 21.35 | 63.17 | 21.53 | 0.50 | 21.53 |
September | 644.67 | 21.33 | 30.00 | 21.42 | 0.00 | 21.42 |
October | 703.33 | 21.10 | 201.83 | 21.08 | 178.00 | 21.02 |
November | 712.67 | 20.97 | 500.50 | 20.88 | 500.50 | 20.84 |
December | 744.00 | 20.76 | 684.83 | 20.69 | 684.83 | 20.67 |
Annual Sum or Average | 8199.83 | 21.17 | 3394.00 | 21.09 | 3176.00 | 21.01 |
Minimum of Months | 622.50 | 20.76 | 22.17 | 20.69 | 0.00 | 20.67 |
Maximum of Months | 744.00 | 21.48 | 684.83 | 21.53 | 684.83 | 21.54 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 730.00 | 22.28 | 161.50 | 22.05 | 161.50 | 21.89 |
February | 634.00 | 22.80 | 32.33 | 22.71 | 32.33 | 22.63 |
March | 588.17 | 23.13 | 0.00 | 23.13 | 0.00 | 23.13 |
April | 271.00 | 23.37 | 42.67 | 23.46 | 0.00 | 23.46 |
May | 23.33 | 23.54 | 410.17 | 23.98 | 6.17 | 23.98 |
June | 121.17 | 23.99 | 687.50 | 23.99 | 121.17 | 23.99 |
July | 193.33 | 24.00 | 744.00 | 23.99 | 193.33 | 23.99 |
August | 177.50 | 23.99 | 738.83 | 23.97 | 177.50 | 23.98 |
September | 67.83 | 23.79 | 537.00 | 23.98 | 50.17 | 23.98 |
October | 211.83 | 23.25 | 163.33 | 23.60 | 0.00 | 23.60 |
November | 512.33 | 23.20 | 28.83 | 23.25 | 0.00 | 23.25 |
December | 725.83 | 22.45 | 138.67 | 22.22 | 138.67 | 22.05 |
Annual Sum or Average | 4256.33 | 22.96 | 3684.83 | 23.32 | 880.83 | 23.27 |
Minimum of Months | 23.33 | 22.28 | 0.00 | 22.05 | 0.00 | 21.89 |
Maximum of Months | 730.00 | 24.00 | 744.00 | 23.99 | 193.33 | 23.99 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 681.17 | 22.40 | 92.33 | 22.23 | 92.33 | 22.10 |
February | 560.67 | 22.94 | 8.83 | 22.91 | 8.83 | 22.88 |
March | 434.50 | 23.20 | 7.33 | 23.22 | 0.00 | 23.22 |
April | 113.67 | 23.36 | 102.67 | 23.69 | 0.00 | 23.69 |
May | 8.33 | 23.84 | 537.67 | 24.01 | 6.00 | 24.01 |
June | 111.00 | 24.00 | 709.83 | 24.00 | 111.00 | 24.00 |
July | 177.50 | 24.00 | 744.00 | 24.00 | 177.50 | 24.00 |
August | 160.00 | 24.00 | 744.00 | 23.99 | 160.00 | 23.99 |
September | 37.50 | 23.99 | 658.50 | 24.01 | 37.50 | 24.01 |
October | 80.50 | 23.26 | 331.00 | 23.89 | 0.00 | 23.89 |
November | 343.67 | 23.27 | 55.33 | 23.37 | 0.00 | 23.37 |
December | 653.67 | 22.53 | 71.33 | 22.38 | 71.33 | 22.26 |
Annual Sum or Average | 3362.17 | 23.00 | 4062.83 | 23.48 | 664.50 | 23.46 |
Minimum of Months | 8.33 | 22.40 | 7.33 | 22.23 | 0.00 | 22.10 |
Maximum of Months | 681.17 | 24.00 | 744.00 | 24.01 | 177.50 | 24.01 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.33 | 22.93 | 516.00 | 23.33 | 316.50 | 23.42 |
February | 489.50 | 23.42 | 499.33 | 23.70 | 359.67 | 23.78 |
March | 531.00 | 23.73 | 600.17 | 23.86 | 452.67 | 23.91 |
April | 503.83 | 24.06 | 655.83 | 24.02 | 491.83 | 24.05 |
May | 545.83 | 24.08 | 736.67 | 24.04 | 545.83 | 24.05 |
June | 561.17 | 24.01 | 720.00 | 23.98 | 561.17 | 23.99 |
July | 593.50 | 23.99 | 744.00 | 23.98 | 593.50 | 23.98 |
August | 578.17 | 23.99 | 744.00 | 23.97 | 578.17 | 23.98 |
September | 533.00 | 24.11 | 720.00 | 24.05 | 533.00 | 24.07 |
October | 521.33 | 24.21 | 711.17 | 24.12 | 518.00 | 24.15 |
November | 497.17 | 23.85 | 604.00 | 23.91 | 444.33 | 23.95 |
December | 489.00 | 23.14 | 532.33 | 23.52 | 323.83 | 23.62 |
Annual Sum or Average | 6330.83 | 23.81 | 7783.50 | 23.89 | 5718.50 | 23.93 |
Minimum of Months | 487.33 | 22.93 | 499.33 | 23.33 | 316.50 | 23.42 |
Maximum of Months | 593.50 | 24.21 | 744.00 | 24.12 | 593.50 | 24.15 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 673.50 | 21.00 | 673.50 | 21.00 |
February | 672.00 | 21.02 | 487.17 | 21.01 | 487.17 | 21.01 |
March | 744.00 | 21.09 | 330.83 | 21.06 | 330.83 | 21.05 |
April | 720.00 | 21.53 | 23.17 | 21.51 | 23.17 | 21.50 |
May | 627.67 | 22.55 | 52.83 | 22.65 | 0.00 | 22.65 |
June | 442.83 | 22.80 | 146.83 | 23.07 | 0.00 | 23.07 |
July | 198.17 | 22.96 | 332.17 | 23.52 | 0.00 | 23.52 |
August | 417.83 | 22.81 | 148.00 | 23.09 | 0.00 | 23.09 |
September | 684.33 | 22.35 | 13.33 | 22.38 | 0.00 | 22.38 |
October | 744.00 | 21.46 | 11.50 | 21.46 | 11.50 | 21.45 |
November | 720.00 | 21.03 | 266.67 | 21.02 | 266.67 | 21.01 |
December | 744.00 | 21.00 | 653.83 | 21.00 | 653.83 | 21.00 |
Annual Sum or Average | 7458.83 | 21.63 | 3139.83 | 21.63 | 2446.67 | 21.51 |
Minimum of Months | 198.17 | 21.00 | 11.50 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.96 | 673.50 | 23.52 | 673.50 | 23.52 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.39893 | 14.84257 | -0.2203 | 6.96222 |
February | 672.00000 | 22.61826 | 17.50539 | -0.1599 | 5.90833 |
March | 744.00000 | 22.06894 | 22.33328 | -0.2715 | 6.82021 |
April | 720.00000 | 22.01339 | 26.78249 | -0.2602 | 6.61891 |
May | 744.00000 | 22.34167 | 37.86432 | -1.1862 | 34.82977 |
June | 720.00000 | 22.64175 | 51.69043 | -0.9869 | 25.89180 |
July | 744.00000 | 23.31504 | 56.53878 | -0.7073 | 15.82291 |
August | 744.00000 | 23.77816 | 53.93267 | -0.5470 | 11.42410 |
September | 720.00000 | 23.90071 | 42.16241 | -0.5766 | 12.13685 |
October | 744.00000 | 23.93760 | 31.48305 | 0.27581 | 6.64285 |
November | 720.00000 | 23.90305 | 23.88699 | 0.21050 | 6.02060 |
December | 744.00000 | 23.10997 | 16.04874 | -0.0366 | 5.84578 |
Annual Sum or Average | 8760.00000 | 23.00421 | 33.01415 | -0.3736 | 12.12126 |
Minimum of Months | 672.00000 | 22.01339 | 14.84257 | -1.1862 | 5.84578 |
Maximum of Months | 744.00000 | 23.93760 | 56.53878 | 0.27581 | 34.82977 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.04560 | 13.74576 | -0.6773 | 15.54081 |
February | 672.00000 | 21.26973 | 16.43067 | -0.5304 | 12.72603 |
March | 744.00000 | 21.31054 | 21.02504 | -0.4542 | 11.00874 |
April | 720.00000 | 21.56612 | 25.40510 | -0.2916 | 8.72727 |
May | 744.00000 | 21.91462 | 36.64456 | -1.1271 | 34.71797 |
June | 720.00000 | 22.05778 | 51.70241 | -0.9665 | 27.86764 |
July | 744.00000 | 22.44569 | 57.72711 | -0.7627 | 20.12083 |
August | 744.00000 | 22.25964 | 57.13376 | -0.8431 | 23.50894 |
September | 720.00000 | 21.83819 | 45.82274 | -1.1076 | 34.29292 |
October | 744.00000 | 21.43826 | 34.24561 | -0.2834 | 8.73541 |
November | 720.00000 | 21.16561 | 25.49745 | -0.4962 | 11.20346 |
December | 744.00000 | 21.03689 | 15.55143 | -0.6859 | 15.40959 |
Annual Sum or Average | 8760.00000 | 21.61472 | 33.51003 | -0.6864 | 18.68323 |
Minimum of Months | 672.00000 | 21.03689 | 13.74576 | -1.1271 | 8.72727 |
Maximum of Months | 744.00000 | 22.44569 | 57.72711 | -0.2834 | 34.71797 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.09163 | 16.23380 | -0.5423 | 11.34374 |
February | 672.00000 | 21.34226 | 18.87181 | -0.4463 | 9.59161 |
March | 744.00000 | 21.65147 | 23.15490 | -0.3347 | 7.97354 |
April | 720.00000 | 22.41997 | 26.82806 | -0.1127 | 6.02940 |
May | 744.00000 | 23.17994 | 36.80287 | -0.8216 | 20.23847 |
June | 720.00000 | 23.29754 | 50.62964 | -0.6811 | 15.66952 |
July | 744.00000 | 23.55426 | 56.54390 | -0.5398 | 11.53720 |
August | 744.00000 | 23.44855 | 55.83419 | -0.5888 | 12.83557 |
September | 720.00000 | 23.17381 | 45.02947 | -0.7737 | 18.37593 |
October | 744.00000 | 22.52712 | 34.88035 | -0.0370 | 5.85311 |
November | 720.00000 | 21.67965 | 27.29063 | -0.3056 | 7.48597 |
December | 744.00000 | 21.11823 | 18.00753 | -0.5239 | 10.95755 |
Annual Sum or Average | 8760.00000 | 22.37923 | 34.26556 | -0.4759 | 11.50220 |
Minimum of Months | 672.00000 | 21.09163 | 16.23380 | -0.8216 | 5.85311 |
Maximum of Months | 744.00000 | 23.55426 | 56.54390 | -0.0370 | 20.23847 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.25504 | 11.02693 | 0.26823 | 11.15905 |
February | 672.00000 | 22.69106 | 13.51935 | 0.40849 | 12.08652 |
March | 744.00000 | 22.93571 | 17.64174 | 0.51842 | 13.69278 |
April | 720.00000 | 23.14321 | 21.57730 | 0.63451 | 16.12510 |
May | 744.00000 | 23.23396 | 32.34510 | 0.07107 | 9.93733 |
June | 720.00000 | 23.19999 | 46.42904 | 0.17730 | 10.30832 |
July | 744.00000 | 23.20124 | 53.09211 | 0.23399 | 10.59916 |
August | 744.00000 | 23.17937 | 52.13776 | 0.20760 | 10.57772 |
September | 720.00000 | 23.28992 | 40.22966 | 0.12779 | 10.06024 |
October | 744.00000 | 23.28336 | 29.26173 | 0.71603 | 18.42856 |
November | 720.00000 | 23.01982 | 21.43516 | 0.56396 | 14.44238 |
December | 744.00000 | 22.45314 | 12.62640 | 0.32668 | 10.99382 |
Annual Sum or Average | 8760.00000 | 22.99105 | 29.37195 | 0.35383 | 12.36587 |
Minimum of Months | 672.00000 | 22.25504 | 11.02693 | 0.07107 | 9.93733 |
Maximum of Months | 744.00000 | 23.28992 | 53.09211 | 0.71603 | 18.42856 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.15945 | 18.71994 | -0.5322 | 11.94293 |
February | 672.00000 | 21.58406 | 21.23824 | -0.3432 | 9.66803 |
March | 744.00000 | 21.84105 | 25.60287 | -0.2263 | 8.11835 |
April | 720.00000 | 22.39138 | 29.52377 | -0.0141 | 6.88608 |
May | 744.00000 | 23.00241 | 39.80033 | -0.6928 | 17.29318 |
June | 720.00000 | 23.10861 | 53.82430 | -0.5450 | 13.17493 |
July | 744.00000 | 23.36948 | 59.77722 | -0.3838 | 9.42947 |
August | 744.00000 | 23.27095 | 59.05986 | -0.4326 | 11.01010 |
September | 720.00000 | 22.95969 | 48.10978 | -0.6581 | 16.79555 |
October | 744.00000 | 22.29055 | 37.75771 | -0.0007 | 7.26431 |
November | 720.00000 | 21.59986 | 29.98064 | -0.2896 | 8.16890 |
December | 744.00000 | 21.11858 | 20.54226 | -0.5481 | 11.95276 |
Annual Sum or Average | 8760.00000 | 22.31169 | 37.08737 | -0.3894 | 10.98305 |
Minimum of Months | 672.00000 | 21.11858 | 18.71994 | -0.6928 | 6.88608 |
Maximum of Months | 744.00000 | 23.36948 | 59.77722 | -0.0007 | 17.29318 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.35585 | 18.92913 | -0.4469 | 9.61966 |
February | 672.00000 | 21.83374 | 21.46159 | -0.2967 | 7.60084 |
March | 744.00000 | 22.20534 | 25.64573 | -0.1716 | 6.49114 |
April | 720.00000 | 22.92092 | 29.22675 | 0.04411 | 5.74506 |
May | 744.00000 | 23.49135 | 39.03113 | -0.6576 | 14.85795 |
June | 720.00000 | 23.56549 | 52.55332 | -0.5261 | 11.47000 |
July | 744.00000 | 23.71362 | 58.52248 | -0.4171 | 8.94571 |
August | 744.00000 | 23.67761 | 57.71333 | -0.4432 | 9.54470 |
September | 720.00000 | 23.55394 | 46.85732 | -0.5851 | 12.89199 |
October | 744.00000 | 23.03395 | 36.94050 | 0.12193 | 6.25223 |
November | 720.00000 | 22.24005 | 29.62263 | -0.1440 | 6.26310 |
December | 744.00000 | 21.41571 | 20.67088 | -0.4245 | 9.27290 |
Annual Sum or Average | 8760.00000 | 22.75467 | 36.51993 | -0.3294 | 9.09162 |
Minimum of Months | 672.00000 | 21.35585 | 18.92913 | -0.6576 | 5.74506 |
Maximum of Months | 744.00000 | 23.71362 | 58.52248 | 0.12193 | 14.85795 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.52238 | 17.65463 | -0.8644 | 21.24437 |
February | 672.00000 | 20.76446 | 19.63918 | -0.7363 | 17.29235 |
March | 744.00000 | 20.90207 | 23.88766 | -0.6263 | 14.31866 |
April | 720.00000 | 21.27332 | 28.87259 | -0.4188 | 9.90204 |
May | 744.00000 | 21.63191 | 40.40295 | -1.2635 | 39.95446 |
June | 720.00000 | 21.65934 | 52.30615 | -1.1493 | 34.47340 |
July | 744.00000 | 21.70368 | 55.48941 | -1.0691 | 30.98183 |
August | 744.00000 | 21.65085 | 56.64517 | -1.1276 | 33.54583 |
September | 720.00000 | 21.52147 | 49.96755 | -1.3028 | 41.73833 |
October | 744.00000 | 21.09916 | 38.99367 | -0.4368 | 10.09890 |
November | 720.00000 | 20.74959 | 28.63028 | -0.6744 | 15.26340 |
December | 744.00000 | 20.49872 | 19.24264 | -0.8665 | 21.34174 |
Annual Sum or Average | 8760.00000 | 21.16654 | 36.06848 | -0.8791 | 24.22345 |
Minimum of Months | 672.00000 | 20.49872 | 17.65463 | -1.3028 | 9.90204 |
Maximum of Months | 744.00000 | 21.70368 | 56.64517 | -0.4188 | 41.73833 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.47345 | 17.71655 | -0.9135 | 23.18536 |
February | 672.00000 | 20.54124 | 19.88522 | -0.8293 | 20.11335 |
March | 744.00000 | 20.64835 | 24.19263 | -0.7208 | 16.74043 |
April | 720.00000 | 21.06951 | 29.14076 | -0.4957 | 11.10456 |
May | 744.00000 | 21.57415 | 40.61152 | -1.3071 | 41.85739 |
June | 720.00000 | 21.64369 | 52.45856 | -1.1677 | 35.11553 |
July | 744.00000 | 21.69344 | 55.97664 | -1.0906 | 31.69852 |
August | 744.00000 | 21.61963 | 57.54046 | -1.1651 | 34.95194 |
September | 720.00000 | 21.42293 | 50.45163 | -1.3733 | 44.86089 |
October | 744.00000 | 20.92932 | 39.35065 | -0.5035 | 10.97186 |
November | 720.00000 | 20.57478 | 28.88321 | -0.7370 | 17.02514 |
December | 744.00000 | 20.47370 | 19.28485 | -0.9013 | 22.73881 |
Annual Sum or Average | 8760.00000 | 21.05823 | 36.38269 | -0.9345 | 25.89817 |
Minimum of Months | 672.00000 | 20.47345 | 17.71655 | -1.3733 | 10.97186 |
Maximum of Months | 744.00000 | 21.69344 | 57.54046 | -0.4957 | 44.86089 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.55521 | 16.31161 | -0.7933 | 18.86760 |
February | 672.00000 | 20.64696 | 18.59022 | -0.7377 | 16.93046 |
March | 744.00000 | 20.76769 | 22.95147 | -0.6608 | 14.56408 |
April | 720.00000 | 21.07940 | 28.04229 | -0.5090 | 10.63459 |
May | 744.00000 | 21.39175 | 39.98249 | -1.4655 | 49.23358 |
June | 720.00000 | 21.48042 | 52.09092 | -1.3328 | 42.34726 |
July | 744.00000 | 21.51709 | 56.80727 | -1.2835 | 39.87174 |
August | 744.00000 | 21.41624 | 57.42798 | -1.3400 | 42.58061 |
September | 720.00000 | 21.28937 | 49.18839 | -1.4724 | 49.50842 |
October | 744.00000 | 21.05387 | 38.18866 | -0.4586 | 9.53582 |
November | 720.00000 | 20.79563 | 27.48207 | -0.6247 | 13.59347 |
December | 744.00000 | 20.56481 | 17.89350 | -0.7768 | 18.32299 |
Annual Sum or Average | 8760.00000 | 21.04856 | 35.50983 | -0.9560 | 27.22968 |
Minimum of Months | 672.00000 | 20.55521 | 16.31161 | -1.4724 | 9.53582 |
Maximum of Months | 744.00000 | 21.51709 | 57.42798 | -0.4586 | 49.50842 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.51085 | 17.65473 | -0.8657 | 21.30824 |
February | 672.00000 | 20.75874 | 19.63022 | -0.7376 | 17.22533 |
March | 744.00000 | 20.98522 | 23.79241 | -0.6080 | 13.92488 |
April | 720.00000 | 21.38596 | 28.77857 | -0.3865 | 9.49359 |
May | 744.00000 | 21.67819 | 40.31120 | -1.2532 | 39.48988 |
June | 720.00000 | 21.70521 | 51.90966 | -1.1190 | 33.22909 |
July | 744.00000 | 21.72903 | 55.16109 | -1.0599 | 30.69796 |
August | 744.00000 | 21.67644 | 56.49813 | -1.1237 | 33.40838 |
September | 720.00000 | 21.54209 | 50.02348 | -1.2970 | 41.51807 |
October | 744.00000 | 21.11490 | 38.95713 | -0.4371 | 10.09921 |
November | 720.00000 | 20.73321 | 28.63727 | -0.6771 | 15.31716 |
December | 744.00000 | 20.49301 | 19.24026 | -0.8662 | 21.36783 |
Annual Sum or Average | 8760.00000 | 21.19467 | 35.97309 | -0.8703 | 23.96777 |
Minimum of Months | 672.00000 | 20.49301 | 17.65473 | -1.2970 | 9.49359 |
Maximum of Months | 744.00000 | 21.72903 | 56.49813 | -0.3865 | 41.51807 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.47463 | 17.70170 | -0.9137 | 23.22668 |
February | 672.00000 | 20.52768 | 19.88201 | -0.8331 | 20.20540 |
March | 744.00000 | 20.70981 | 24.07892 | -0.7078 | 16.26220 |
April | 720.00000 | 21.24789 | 28.92682 | -0.4502 | 10.28470 |
May | 744.00000 | 21.65488 | 40.43817 | -1.2873 | 40.91600 |
June | 720.00000 | 21.70184 | 52.06897 | -1.1337 | 33.71221 |
July | 744.00000 | 21.72525 | 55.62821 | -1.0796 | 31.34531 |
August | 744.00000 | 21.66208 | 57.21468 | -1.1568 | 34.63496 |
September | 720.00000 | 21.48598 | 50.35271 | -1.3554 | 44.04241 |
October | 744.00000 | 20.95477 | 39.25453 | -0.5027 | 10.93876 |
November | 720.00000 | 20.56939 | 28.87293 | -0.7379 | 17.10294 |
December | 744.00000 | 20.47536 | 19.27791 | -0.9005 | 22.74594 |
Annual Sum or Average | 8760.00000 | 21.10216 | 36.23221 | -0.9223 | 25.48544 |
Minimum of Months | 672.00000 | 20.47463 | 17.70170 | -1.3554 | 10.28470 |
Maximum of Months | 744.00000 | 21.72525 | 57.21468 | -0.4502 | 44.04241 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.48628 | 17.82015 | -0.9364 | 23.99865 |
February | 672.00000 | 20.67283 | 19.88312 | -0.8111 | 19.78157 |
March | 744.00000 | 20.81330 | 24.20284 | -0.6891 | 16.21655 |
April | 720.00000 | 21.18835 | 29.26089 | -0.4667 | 11.07486 |
May | 744.00000 | 21.60141 | 40.77636 | -1.2897 | 41.47776 |
June | 720.00000 | 21.63825 | 53.25941 | -1.1615 | 35.29999 |
July | 744.00000 | 21.68824 | 56.69585 | -1.0750 | 31.49221 |
August | 744.00000 | 21.62201 | 58.15332 | -1.1434 | 34.50000 |
September | 720.00000 | 21.46358 | 50.91596 | -1.3508 | 44.31216 |
October | 744.00000 | 20.99595 | 39.54077 | -0.4938 | 11.43768 |
November | 720.00000 | 20.66078 | 29.07994 | -0.7394 | 17.24504 |
December | 744.00000 | 20.47578 | 19.42737 | -0.9340 | 23.93310 |
Annual Sum or Average | 8760.00000 | 21.11107 | 36.67762 | -0.9251 | 25.93583 |
Minimum of Months | 672.00000 | 20.47578 | 17.82015 | -1.3508 | 11.07486 |
Maximum of Months | 744.00000 | 21.68824 | 58.15332 | -0.4667 | 44.31216 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.46757 | 17.85793 | -0.9796 | 25.84029 |
February | 672.00000 | 20.50747 | 20.08555 | -0.8952 | 22.52638 |
March | 744.00000 | 20.59452 | 24.48296 | -0.7799 | 18.69320 |
April | 720.00000 | 20.97578 | 29.55831 | -0.5487 | 12.48232 |
May | 744.00000 | 21.54052 | 41.01216 | -1.3368 | 43.51901 |
June | 720.00000 | 21.62340 | 53.41846 | -1.1808 | 35.95614 |
July | 744.00000 | 21.67721 | 57.20659 | -1.0979 | 32.23687 |
August | 744.00000 | 21.58756 | 59.16122 | -1.1837 | 36.00598 |
September | 720.00000 | 21.34572 | 51.47869 | -1.4319 | 47.96459 |
October | 744.00000 | 20.80954 | 39.95176 | -0.5674 | 12.54168 |
November | 720.00000 | 20.51789 | 29.29996 | -0.7976 | 19.04782 |
December | 744.00000 | 20.46854 | 19.45762 | -0.9652 | 25.27419 |
Annual Sum or Average | 8760.00000 | 21.01261 | 37.00848 | -0.9810 | 27.70332 |
Minimum of Months | 672.00000 | 20.46757 | 17.85793 | -1.4319 | 12.48232 |
Maximum of Months | 744.00000 | 21.67721 | 59.16122 | -0.5487 | 47.96459 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.85640 | 19.11724 | -0.7363 | 17.75727 |
February | 672.00000 | 21.14338 | 21.01985 | -0.5929 | 14.26295 |
March | 744.00000 | 21.18015 | 25.19523 | -0.5269 | 12.51806 |
April | 720.00000 | 21.39468 | 30.21931 | -0.3829 | 9.59197 |
May | 744.00000 | 21.62255 | 41.43645 | -1.3104 | 42.36056 |
June | 720.00000 | 21.63357 | 53.04379 | -1.2103 | 37.38547 |
July | 744.00000 | 21.67736 | 56.43122 | -1.1364 | 34.06853 |
August | 744.00000 | 21.63314 | 56.98055 | -1.1665 | 35.51543 |
September | 720.00000 | 21.54257 | 50.62952 | -1.2969 | 41.80371 |
October | 744.00000 | 21.22306 | 40.28642 | -0.3814 | 9.50747 |
November | 720.00000 | 20.99895 | 29.71524 | -0.5801 | 13.36807 |
December | 744.00000 | 20.75997 | 20.65567 | -0.7661 | 18.50445 |
Annual Sum or Average | 8760.00000 | 21.30586 | 37.15063 | -0.8423 | 23.94801 |
Minimum of Months | 672.00000 | 20.75997 | 19.11724 | -1.3104 | 9.50747 |
Maximum of Months | 744.00000 | 21.67736 | 56.98055 | -0.3814 | 42.36056 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.31586 | 21.17696 | -0.2308 | 7.96926 |
February | 672.00000 | 22.86784 | 23.52361 | -0.0619 | 6.50380 |
March | 744.00000 | 23.31061 | 27.04207 | 0.09593 | 6.15499 |
April | 720.00000 | 23.75253 | 29.79376 | 0.27133 | 6.89753 |
May | 744.00000 | 23.96137 | 38.84229 | -0.4075 | 8.81334 |
June | 720.00000 | 23.98467 | 51.85038 | -0.2698 | 6.71986 |
July | 744.00000 | 23.98770 | 58.07611 | -0.2092 | 5.99041 |
August | 744.00000 | 23.96407 | 57.44123 | -0.2504 | 6.42406 |
September | 720.00000 | 23.92545 | 46.77245 | -0.3950 | 8.54989 |
October | 744.00000 | 23.76789 | 37.17950 | 0.32222 | 7.49831 |
November | 720.00000 | 23.42517 | 30.49280 | 0.14832 | 6.21397 |
December | 744.00000 | 22.48795 | 22.73685 | -0.1734 | 7.55788 |
Annual Sum or Average | 8760.00000 | 23.48108 | 37.15969 | -0.0974 | 7.11288 |
Minimum of Months | 672.00000 | 22.31586 | 21.17696 | -0.4075 | 5.99041 |
Maximum of Months | 744.00000 | 23.98770 | 58.07611 | 0.32222 | 8.81334 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.53037 | 20.45484 | -0.1419 | 7.40836 |
February | 672.00000 | 23.11642 | 22.68203 | 0.03659 | 6.39337 |
March | 744.00000 | 23.52825 | 26.03973 | 0.18766 | 6.48975 |
April | 720.00000 | 23.88031 | 28.83562 | 0.34035 | 7.64439 |
May | 744.00000 | 23.99966 | 38.17930 | -0.3470 | 7.77362 |
June | 720.00000 | 24.00101 | 51.27514 | -0.2203 | 6.18588 |
July | 744.00000 | 23.99621 | 57.57506 | -0.1663 | 5.64794 |
August | 744.00000 | 23.98769 | 56.84308 | -0.1998 | 5.92110 |
September | 720.00000 | 23.98535 | 46.00285 | -0.3251 | 7.40324 |
October | 744.00000 | 23.89722 | 36.18466 | 0.39219 | 8.41540 |
November | 720.00000 | 23.63927 | 29.42645 | 0.24055 | 6.73873 |
December | 744.00000 | 22.70607 | 21.95382 | -0.0820 | 7.16574 |
Annual Sum or Average | 8760.00000 | 23.60671 | 36.37108 | -0.0246 | 6.93606 |
Minimum of Months | 672.00000 | 22.53037 | 20.45484 | -0.3470 | 5.64794 |
Maximum of Months | 744.00000 | 24.00101 | 57.57506 | 0.39219 | 8.41540 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.07728 | 19.93364 | 0.59248 | 17.98373 |
February | 672.00000 | 23.46169 | 21.27495 | 0.73921 | 20.98721 |
March | 744.00000 | 23.66632 | 24.58974 | 0.85948 | 24.07261 |
April | 720.00000 | 23.88350 | 27.94864 | 1.00832 | 28.97839 |
May | 744.00000 | 23.99109 | 37.68350 | 0.62402 | 18.03973 |
June | 720.00000 | 23.96297 | 50.50824 | 0.75233 | 21.10379 |
July | 744.00000 | 23.96213 | 56.66125 | 0.81337 | 22.91304 |
August | 744.00000 | 23.94999 | 55.80395 | 0.76149 | 21.25274 |
September | 720.00000 | 24.01167 | 45.24282 | 0.63986 | 17.92989 |
October | 744.00000 | 24.00162 | 35.50635 | 1.06427 | 31.14070 |
November | 720.00000 | 23.73874 | 28.09668 | 0.88739 | 24.36950 |
December | 744.00000 | 23.27426 | 21.07787 | 0.65080 | 18.67018 |
Annual Sum or Average | 8760.00000 | 23.74914 | 35.44804 | 0.78268 | 22.28861 |
Minimum of Months | 672.00000 | 23.07728 | 19.93364 | 0.59248 | 17.92989 |
Maximum of Months | 744.00000 | 24.01167 | 56.66125 | 1.06427 | 31.14070 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.99432 | 13.01945 | -0.6600 | 14.24566 |
February | 672.00000 | 21.00023 | 15.78032 | -0.6151 | 13.01741 |
March | 744.00000 | 21.01090 | 20.43406 | -0.5621 | 11.71126 |
April | 720.00000 | 21.28442 | 24.85071 | -0.4346 | 9.25014 |
May | 744.00000 | 22.39224 | 34.88302 | -1.1558 | 34.07070 |
June | 720.00000 | 22.86402 | 48.90430 | -0.9017 | 23.04007 |
July | 744.00000 | 23.27060 | 54.90766 | -0.7184 | 16.16337 |
August | 744.00000 | 23.00500 | 54.33681 | -0.8174 | 19.43640 |
September | 720.00000 | 22.42723 | 43.56698 | -1.0899 | 30.55279 |
October | 744.00000 | 21.47368 | 33.44528 | -0.3309 | 7.71093 |
November | 720.00000 | 21.01675 | 24.76062 | -0.5233 | 10.84624 |
December | 744.00000 | 21.00016 | 14.78515 | -0.6410 | 13.72591 |
Annual Sum or Average | 8760.00000 | 21.81735 | 32.06707 | -0.7045 | 16.99769 |
Minimum of Months | 672.00000 | 20.99432 | 13.01945 | -1.1558 | 7.71093 |
Maximum of Months | 744.00000 | 23.27060 | 54.90766 | -0.3309 | 34.07070 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00002 | 16.40789 | -0.6073 | 12.79606 |
February | 672.00000 | 21.01932 | 19.23205 | -0.5666 | 11.79260 |
March | 744.00000 | 21.09280 | 23.84586 | -0.5088 | 10.54143 |
April | 720.00000 | 21.69706 | 27.79021 | -0.3248 | 7.75763 |
May | 744.00000 | 22.83780 | 37.48513 | -1.0067 | 27.34616 |
June | 720.00000 | 23.19033 | 51.08546 | -0.7924 | 18.93031 |
July | 744.00000 | 23.59549 | 56.78500 | -0.6090 | 12.98577 |
August | 744.00000 | 23.26703 | 56.63380 | -0.7296 | 16.60205 |
September | 720.00000 | 22.65460 | 46.40009 | -1.0155 | 27.52338 |
October | 744.00000 | 21.56369 | 36.66694 | -0.3065 | 7.47904 |
November | 720.00000 | 21.02588 | 28.21454 | -0.5073 | 10.47133 |
December | 744.00000 | 21.00054 | 18.21379 | -0.5989 | 12.59207 |
Annual Sum or Average | 8760.00000 | 22.00180 | 34.98739 | -0.6313 | 14.74327 |
Minimum of Months | 672.00000 | 21.00002 | 16.40789 | -1.0155 | 7.47904 |
Maximum of Months | 744.00000 | 23.59549 | 56.78500 | -0.3065 | 27.52338 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.99727 | 14.24926 | -0.6551 | 14.13767 |
February | 672.00000 | 21.02073 | 17.08921 | -0.5948 | 12.56176 |
March | 744.00000 | 21.09065 | 21.69799 | -0.5198 | 10.86363 |
April | 720.00000 | 21.52892 | 25.82012 | -0.3506 | 8.14385 |
May | 744.00000 | 22.73196 | 35.31017 | -0.9925 | 27.35784 |
June | 720.00000 | 23.15600 | 48.82565 | -0.7472 | 17.94012 |
July | 744.00000 | 23.50832 | 54.61447 | -0.5784 | 12.60269 |
August | 744.00000 | 23.18458 | 54.50204 | -0.7020 | 16.22632 |
September | 720.00000 | 22.41611 | 44.62980 | -1.0501 | 29.27499 |
October | 744.00000 | 21.46429 | 34.63964 | -0.3160 | 7.68107 |
November | 720.00000 | 21.02553 | 26.09298 | -0.5129 | 10.63507 |
December | 744.00000 | 21.00058 | 16.04494 | -0.6407 | 13.74320 |
Annual Sum or Average | 8760.00000 | 21.93338 | 32.88320 | -0.6384 | 15.10284 |
Minimum of Months | 672.00000 | 20.99727 | 14.24926 | -1.0501 | 7.68107 |
Maximum of Months | 744.00000 | 23.50832 | 54.61447 | -0.3160 | 29.27499 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.99973 | 12.54626 | -0.6365 | 13.59802 |
February | 672.00000 | 21.01158 | 15.31566 | -0.5913 | 12.41920 |
March | 744.00000 | 21.05013 | 19.93182 | -0.5346 | 11.11047 |
April | 720.00000 | 21.46463 | 24.12395 | -0.3836 | 8.47550 |
May | 744.00000 | 22.63914 | 33.85023 | -1.0642 | 30.05014 |
June | 720.00000 | 23.07986 | 47.66353 | -0.8186 | 20.01671 |
July | 744.00000 | 23.46115 | 53.59393 | -0.6426 | 14.00092 |
August | 744.00000 | 23.23115 | 52.98901 | -0.7308 | 16.65964 |
September | 720.00000 | 22.70177 | 42.31671 | -0.9896 | 26.27037 |
October | 744.00000 | 21.72255 | 32.46859 | -0.2658 | 6.98147 |
November | 720.00000 | 21.08600 | 24.20386 | -0.4902 | 10.19230 |
December | 744.00000 | 21.00086 | 14.31412 | -0.6175 | 13.10220 |
Annual Sum or Average | 8760.00000 | 21.96038 | 31.20162 | -0.6473 | 15.25198 |
Minimum of Months | 672.00000 | 20.99973 | 12.54626 | -1.0642 | 6.98147 |
Maximum of Months | 744.00000 | 23.46115 | 53.59393 | -0.2658 | 30.05014 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.411749E+09 | 14051.37 | 19-JAN-19:04 | 47.21 | 0.131201E+10 | 0.00 | 0.172376E+10 | 0.20 | 3.19 | 01-JAN-15:10 | 0.00 | 0.00 |
February | 0.161272E+10 | 20215.98 | 08-FEB-16:04 | 140.31 | 0.513884E+10 | 0.00 | 0.675156E+10 | 0.67 | 3.19 | 01-FEB-14:50 | 0.00 | 0.00 |
March | 0.308771E+10 | 26447.37 | 26-MAR-15:03 | 213.77 | 0.983879E+10 | 0.00 | 0.129265E+11 | 0.92 | 3.19 | 01-MAR-02:10 | 0.00 | 0.00 |
April | 0.162507E+11 | 105956.51 | 23-APR-18:03 | 450.58 | 0.501513E+11 | 0.00 | 0.664020E+11 | 1.98 | 3.51 | 23-APR-18:03 | 0.00 | 0.00 |
May | 0.696911E+11 | 146669.74 | 25-MAY-18:03 | 708.34 | 0.213595E+12 | 0.00 | 0.283286E+12 | 2.96 | 3.86 | 26-MAY-18:03 | 0.00 | 0.00 |
June | 0.134620E+12 | 212692.13 | 29-JUN-18:03 | 713.29 | 0.442380E+12 | 0.00 | 0.577000E+12 | 3.16 | 4.32 | 22-JUN-18:02 | 0.00 | 0.00 |
July | 0.176770E+12 | 180251.25 | 15-JUL-15:03 | 742.83 | 0.603347E+12 | 0.00 | 0.780117E+12 | 3.28 | 4.34 | 25-JUL-18:03 | 0.00 | 0.00 |
August | 0.130707E+12 | 178644.53 | 08-AUG-15:03 | 734.67 | 0.433605E+12 | 0.00 | 0.564312E+12 | 3.16 | 4.28 | 28-AUG-18:02 | 0.00 | 0.00 |
September | 0.453790E+11 | 123882.08 | 01-SEP-15:03 | 651.15 | 0.139505E+12 | 0.00 | 0.184884E+12 | 2.83 | 4.23 | 18-SEP-18:02 | 0.00 | 0.00 |
October | 0.120530E+11 | 81838.18 | 19-OCT-15:02 | 409.91 | 0.371062E+11 | 0.00 | 0.491592E+11 | 1.74 | 3.58 | 21-OCT-15:02 | 0.00 | 0.00 |
November | 0.211175E+10 | 26213.41 | 01-NOV-15:07 | 188.29 | 0.662081E+10 | 0.00 | 0.873256E+10 | 0.83 | 3.19 | 01-NOV-18:03 | 0.00 | 0.00 |
December | 0.314278E+09 | 19950.23 | 06-DEC-09:04 | 43.04 | 0.100143E+10 | 0.00 | 0.131571E+10 | 0.18 | 3.19 | 06-DEC-05:40 | 0.00 | 0.00 |
Annual Sum or Average | 0.593009E+12 | 5043.39 | 0.194360E+13 | 0.00 | 0.253661E+13 | 1.83 | 0.00 | 0.00 | ||||
Minimum of Months | 0.314278E+09 | 14051.37 | 43.04 | 0.100143E+10 | 0.00 | 0.131571E+10 | 0.18 | 3.19 | 0.00 | 0.00 | ||
Maximum of Months | 0.176770E+12 | 212692.13 | 742.83 | 0.603347E+12 | 0.00 | 0.780117E+12 | 3.28 | 4.34 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.792108E+12 | 0.00 | 744.00 | 908538.53 | 06-JAN-09:03 | 0.00 | 48.60 | 82.10 | 2.14 | 0.00 | 0.39 | 1.20 | 06-JAN-09:03 |
February | 0.416974E+12 | 0.00 | 672.00 | 840413.38 | 14-FEB-07:03 | 0.00 | 49.34 | 81.90 | 1.25 | 0.00 | 0.23 | 1.11 | 14-FEB-07:03 |
March | 0.237772E+12 | 0.00 | 743.80 | 771264.71 | 05-MAR-05:00 | 0.00 | 51.74 | 81.62 | 0.68 | 0.00 | 0.12 | 1.02 | 05-MAR-05:00 |
April | 0.482132E+11 | 0.00 | 633.94 | 244064.46 | 02-APR-08:61 | 0.00 | 51.99 | 76.30 | 0.18 | 0.00 | 0.02 | 0.32 | 02-APR-08:61 |
May | 0.172601E+11 | 0.00 | 347.94 | 121100.19 | 20-MAY-22:35 | 0.00 | 38.66 | 56.59 | 0.04 | 0.00 | 0.01 | 0.16 | 20-MAY-22:35 |
June | 0.748304E+10 | 0.00 | 200.41 | 206398.61 | 16-JUN-23:43 | 0.00 | 42.80 | 53.72 | 0.02 | 0.00 | 0.00 | 0.27 | 16-JUN-23:43 |
July | 0.324795E+10 | 0.00 | 95.80 | 123928.93 | 02-JUL-04:50 | 0.00 | 37.92 | 43.13 | 0.01 | 0.00 | 0.00 | 0.16 | 02-JUL-04:50 |
August | 0.344740E+10 | 0.00 | 135.66 | 102550.70 | 19-AUG-01:09 | 0.00 | 40.51 | 47.57 | 0.01 | 0.00 | 0.00 | 0.14 | 19-AUG-01:09 |
September | 0.232066E+11 | 0.00 | 424.32 | 194928.07 | 15-SEP-00:10 | 0.00 | 43.62 | 64.23 | 0.06 | 0.00 | 0.01 | 0.26 | 15-SEP-00:10 |
October | 0.563377E+11 | 0.00 | 682.42 | 250673.18 | 30-OCT-08:61 | 0.00 | 53.27 | 77.58 | 0.20 | 0.00 | 0.03 | 0.33 | 30-OCT-08:61 |
November | 0.151175E+12 | 0.00 | 719.88 | 320389.59 | 25-NOV-09:03 | 0.00 | 54.32 | 81.29 | 0.51 | 0.00 | 0.08 | 0.42 | 25-NOV-09:03 |
December | 0.693652E+12 | 0.00 | 744.00 | 844035.07 | 21-DEC-09:03 | 0.00 | 49.61 | 82.07 | 1.90 | 0.00 | 0.34 | 1.11 | 21-DEC-09:03 |
Annual Sum or Average | 0.245088E+13 | 0.00 | 6144.17 | 0.00 | 46.83 | 68.90 | 0.58 | 0.00 | 0.10 | ||||
Minimum of Months | 0.324795E+10 | 0.00 | 95.80 | 102550.70 | 0.00 | 37.92 | 43.13 | 0.01 | 0.00 | 0.00 | 0.14 | ||
Maximum of Months | 0.792108E+12 | 0.00 | 744.00 | 908538.53 | 0.00 | 54.32 | 82.10 | 2.14 | 0.00 | 0.39 | 1.20 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3064782.52 | 0.00 | 2.83 | 3064782.52 | 0.00 | 0.00 | 0.00 | 0.00 | 1530.89 | 19-JAN-06:20 | 1530.89 | 19-JAN-06:20 | 0.00 | 0.00 | 0.00 |
February | 66508632.19 | 0.00 | 31.81 | 66508632.19 | 0.00 | 0.00 | 0.00 | 0.00 | 9670.01 | 21-FEB-12:26 | 9670.01 | 21-FEB-12:26 | 0.00 | 0.00 | 0.00 |
March | 0.132392E+09 | 0.00 | 56.38 | 0.132392E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13301.12 | 29-MAR-18:02 | 13301.12 | 29-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.137219E+11 | 0.00 | 196.20 | 0.137219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 184309.34 | 23-APR-18:10 | 184309.34 | 23-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.104816E+12 | 0.00 | 386.90 | 0.102182E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 288154.16 | 25-MAY-18:07 | 235655.22 | 25-MAY-18:07 | 0.00 | 0.00 | 0.00 |
June | 0.273797E+12 | 0.00 | 534.00 | 0.191608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 489061.48 | 27-JUN-19:50 | 269195.32 | 29-JUN-18:20 | 0.00 | 0.00 | 0.00 |
July | 0.383689E+12 | 0.00 | 627.17 | 0.247432E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 506988.45 | 21-JUL-19:30 | 238352.83 | 24-JUL-18:20 | 0.00 | 0.00 | 0.00 |
August | 0.261848E+12 | 0.00 | 593.04 | 0.182301E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 466196.74 | 31-AUG-19:10 | 232004.78 | 08-AUG-18:20 | 0.00 | 0.00 | 0.00 |
September | 0.591455E+11 | 0.00 | 295.96 | 0.508356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 257574.02 | 01-SEP-10:50 | 190380.01 | 01-SEP-18:07 | 0.00 | 0.00 | 0.00 |
October | 0.865124E+10 | 0.00 | 174.68 | 0.865124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 134259.68 | 19-OCT-15:03 | 134259.68 | 19-OCT-15:03 | 0.00 | 0.00 | 0.00 |
November | 0.131481E+10 | 0.00 | 107.25 | 0.131481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53522.25 | 01-NOV-15:30 | 53522.25 | 01-NOV-15:30 | 0.00 | 0.00 | 0.00 |
December | 17323470.05 | 0.00 | 14.35 | 17323470.05 | 0.00 | 0.00 | 0.00 | 0.00 | 5299.59 | 05-DEC-19:07 | 5299.59 | 05-DEC-19:07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110720E+13 | 0.00 | 3020.57 | 0.798266E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3064782.52 | 0.00 | 2.83 | 3064782.52 | 0.00 | 0.00 | 0.00 | 0.00 | 1530.89 | 1530.89 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.383689E+12 | 0.00 | 627.17 | 0.247432E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 506988.45 | 269195.32 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 |
April | 0.220258E+10 | 0.00 | 64.33 | 0.220258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28339.06 | 23-APR-18:00 | 28339.06 | 23-APR-18:00 | 0.00 | 0.00 | 0.00 |
May | 0.180784E+11 | 0.00 | 313.00 | 0.173026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41200.12 | 26-MAY-09:30 | 31316.13 | 25-MAY-18:00 | 0.00 | 0.00 | 0.00 |
June | 0.472590E+11 | 0.00 | 495.69 | 0.325465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64248.31 | 19-JUN-17:30 | 34823.58 | 29-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.662562E+11 | 0.00 | 611.33 | 0.420267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67702.20 | 04-JUL-02:50 | 32903.58 | 15-JUL-14:00 | 0.00 | 0.00 | 0.00 |
August | 0.468520E+11 | 0.00 | 576.33 | 0.314665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57885.44 | 30-AUG-08:50 | 32156.08 | 08-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.106541E+11 | 0.00 | 227.07 | 0.878652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41432.39 | 01-SEP-10:30 | 28803.39 | 01-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.144276E+10 | 0.00 | 42.04 | 0.144276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24823.26 | 19-OCT-15:00 | 24823.26 | 19-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.223311E+09 | 0.00 | 8.83 | 0.223311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12274.36 | 01-NOV-15:00 | 12274.36 | 01-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192968E+12 | 0.00 | 2338.63 | 0.135998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.662562E+11 | 0.00 | 611.33 | 0.420267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67702.20 | 34823.58 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 8048998.02 | 0.00 | 1.50 | 8048998.02 | 0.00 | 0.00 | 0.00 | 0.00 | 4707.38 | 31-JAN-16:03 | 4707.38 | 31-JAN-16:03 | 0.00 | 0.00 | 0.00 |
February | 0.166043E+09 | 0.00 | 22.04 | 0.166043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15184.14 | 28-FEB-16:02 | 15184.14 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.638566E+09 | 0.00 | 67.96 | 0.638566E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15200.58 | 28-MAR-18:01 | 15200.58 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.226576E+10 | 0.00 | 235.30 | 0.218882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15818.93 | 13-APR-15:02 | 15818.93 | 13-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.599108E+10 | 0.00 | 579.41 | 0.473202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16243.84 | 21-MAY-15:02 | 16243.84 | 21-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.757757E+10 | 0.00 | 618.63 | 0.495931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19519.47 | 19-JUN-18:02 | 16400.57 | 17-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.101108E+11 | 0.00 | 686.32 | 0.613519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19279.38 | 23-JUL-08:62 | 16247.33 | 20-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.793568E+10 | 0.00 | 642.16 | 0.459543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18419.53 | 30-AUG-08:62 | 15960.22 | 31-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.379408E+10 | 0.00 | 473.73 | 0.259131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17204.47 | 18-SEP-18:02 | 15851.04 | 06-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.111000E+10 | 0.00 | 155.85 | 0.945847E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15849.24 | 21-OCT-15:02 | 15849.24 | 21-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 37994652.24 | 0.00 | 8.94 | 37262279.90 | 0.00 | 0.00 | 0.00 | 0.00 | 15156.73 | 17-NOV-16:01 | 15156.73 | 17-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 8406495.11 | 0.00 | 1.55 | 8406495.11 | 0.00 | 0.00 | 0.00 | 0.00 | 3390.38 | 05-DEC-19:04 | 3390.38 | 05-DEC-19:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.396440E+11 | 0.00 | 3493.39 | 0.270063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8048998.02 | 0.00 | 1.50 | 8048998.02 | 0.00 | 0.00 | 0.00 | 0.00 | 3390.38 | 3390.38 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.101108E+11 | 0.00 | 686.32 | 0.613519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19519.47 | 16400.57 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6072970.24 | 0.00 | 0.95 | 6072970.24 | 0.00 | 0.00 | 0.00 | 0.00 | 3036.34 | 16-JAN-09:04 | 3036.34 | 16-JAN-09:04 | 0.00 | 0.00 | 0.00 |
February | 33720419.68 | 0.00 | 7.64 | 33720419.68 | 0.00 | 0.00 | 0.00 | 0.00 | 12965.58 | 22-FEB-16:01 | 12965.58 | 22-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.256128E+09 | 0.00 | 34.89 | 0.256128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14441.85 | 28-MAR-18:01 | 14441.85 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.137472E+10 | 0.00 | 162.59 | 0.131420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15028.11 | 13-APR-15:02 | 15028.11 | 13-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.503985E+10 | 0.00 | 532.02 | 0.389469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15616.87 | 23-MAY-15:02 | 15432.14 | 21-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.699659E+10 | 0.00 | 600.95 | 0.458607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18245.83 | 25-JUN-08:62 | 15582.77 | 17-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.917153E+10 | 0.00 | 672.36 | 0.547076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18400.00 | 30-JUL-08:62 | 15399.74 | 03-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.654664E+10 | 0.00 | 616.41 | 0.359455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17229.61 | 30-AUG-08:62 | 15435.91 | 23-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.247348E+10 | 0.00 | 381.17 | 0.161336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16284.38 | 18-SEP-18:02 | 15059.71 | 06-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.415143E+09 | 0.00 | 71.96 | 0.364197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15057.65 | 21-OCT-15:02 | 15057.65 | 21-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 18429204.84 | 0.00 | 2.43 | 17575499.90 | 0.00 | 0.00 | 0.00 | 0.00 | 6147.22 | 21-NOV-16:03 | 5146.89 | 14-NOV-19:03 | 0.00 | 0.00 | 0.00 |
December | 6346305.34 | 0.00 | 1.12 | 6346305.34 | 0.00 | 0.00 | 0.00 | 0.00 | 3004.32 | 05-DEC-19:04 | 3004.32 | 05-DEC-19:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.323386E+11 | 0.00 | 3084.48 | 0.211577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6072970.24 | 0.00 | 0.95 | 6072970.24 | 0.00 | 0.00 | 0.00 | 0.00 | 3004.32 | 3004.32 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.917153E+10 | 0.00 | 672.36 | 0.547076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18400.00 | 15582.77 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 20150665.99 | 0.00 | 1.83 | 20150665.99 | 0.00 | 0.00 | 0.00 | 0.00 | 4782.39 | 27-JAN-15:10 | 4782.39 | 27-JAN-15:10 | 0.00 | 0.00 | 0.00 |
February | 0.103361E+10 | 0.00 | 23.10 | 0.103361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27275.68 | 22-FEB-14:30 | 27275.68 | 22-FEB-14:30 | 0.00 | 0.00 | 0.00 |
March | 0.239396E+10 | 0.00 | 59.02 | 0.239396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37122.40 | 20-MAR-12:30 | 37122.40 | 20-MAR-12:30 | 0.00 | 0.00 | 0.00 |
April | 0.105106E+11 | 0.00 | 172.93 | 0.102417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45932.63 | 22-APR-13:00 | 45932.63 | 22-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.199001E+11 | 0.00 | 442.16 | 0.153370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45951.22 | 18-MAY-14:00 | 43023.27 | 06-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.233532E+11 | 0.00 | 466.44 | 0.142941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52712.93 | 30-JUN-14:00 | 42819.75 | 30-JUN-12:30 | 0.00 | 0.00 | 0.00 |
July | 0.339515E+11 | 0.00 | 591.83 | 0.177732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52994.81 | 23-JUL-14:20 | 42455.24 | 23-JUL-11:50 | 0.00 | 0.00 | 0.00 |
August | 0.309438E+11 | 0.00 | 543.63 | 0.174849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54132.91 | 25-AUG-13:10 | 42488.76 | 08-AUG-12:30 | 0.00 | 0.00 | 0.00 |
September | 0.208610E+11 | 0.00 | 350.37 | 0.174213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54646.13 | 01-SEP-13:20 | 52201.49 | 04-SEP-12:30 | 0.00 | 0.00 | 0.00 |
October | 0.108937E+11 | 0.00 | 137.56 | 0.106118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69884.14 | 22-OCT-12:15 | 69142.40 | 22-OCT-12:03 | 0.00 | 0.00 | 0.00 |
November | 0.701114E+09 | 0.00 | 20.19 | 0.701114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27223.12 | 17-NOV-13:30 | 27223.12 | 17-NOV-13:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154563E+12 | 0.00 | 2809.07 | 0.107313E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.339515E+11 | 0.00 | 591.83 | 0.177732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69884.14 | 69142.40 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 30182333.38 | 0.00 | 0.52 | 30182333.38 | 0.00 | 0.00 | 0.00 | 0.00 | 33997.95 | 19-JAN-19:04 | 33997.95 | 19-JAN-19:04 | 0.00 | 0.00 | 0.00 |
February | 54714030.21 | 0.00 | 1.12 | 54714030.21 | 0.00 | 0.00 | 0.00 | 0.00 | 38800.31 | 21-FEB-19:03 | 38800.31 | 21-FEB-19:03 | 0.00 | 0.00 | 0.00 |
March | 0.281771E+09 | 0.00 | 23.77 | 0.281771E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38165.50 | 28-MAR-18:01 | 38165.50 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.474627E+10 | 0.00 | 210.80 | 0.444747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66886.58 | 23-APR-18:01 | 66886.58 | 23-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.285358E+11 | 0.00 | 503.42 | 0.232584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75196.95 | 25-MAY-15:02 | 71532.95 | 24-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.439516E+11 | 0.00 | 517.17 | 0.306618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88894.32 | 25-JUN-08:62 | 72899.31 | 17-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.521515E+11 | 0.00 | 533.30 | 0.333047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88705.63 | 30-JUL-08:62 | 71297.60 | 24-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.396282E+11 | 0.00 | 525.13 | 0.229394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81055.92 | 07-AUG-18:02 | 69864.69 | 09-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.184010E+11 | 0.00 | 487.24 | 0.109900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74246.09 | 18-SEP-18:02 | 67539.36 | 01-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.316562E+10 | 0.00 | 204.44 | 0.240631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61969.85 | 01-OCT-18:02 | 61969.85 | 01-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.342895E+09 | 0.00 | 24.23 | 0.206272E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43101.37 | 20-NOV-16:03 | 43101.37 | 20-NOV-16:03 | 0.00 | 0.00 | 0.00 |
December | 34757529.08 | 0.00 | 0.67 | 34757529.08 | 0.00 | 0.00 | 0.00 | 0.00 | 29903.77 | 06-DEC-19:04 | 29903.77 | 06-DEC-19:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191324E+12 | 0.00 | 3031.79 | 0.128616E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 30182333.38 | 0.00 | 0.52 | 30182333.38 | 0.00 | 0.00 | 0.00 | 0.00 | 29903.77 | 29903.77 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.521515E+11 | 0.00 | 533.30 | 0.333047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88894.32 | 72899.31 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 9115506.75 | 0.00 | 1.40 | 9115506.75 | 0.00 | 0.00 | 0.00 | 0.00 | 2948.02 | 21-JAN-09:04 | 2948.02 | 21-JAN-09:04 | 0.00 | 0.00 | 0.00 |
February | 80485757.81 | 0.00 | 18.24 | 80485757.81 | 0.00 | 0.00 | 0.00 | 0.00 | 12896.53 | 28-FEB-16:02 | 12896.53 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.426993E+09 | 0.00 | 74.68 | 0.426993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13783.72 | 26-MAR-15:02 | 13783.72 | 26-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.231747E+10 | 0.00 | 272.31 | 0.225216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14346.62 | 13-APR-15:02 | 14346.62 | 13-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.565721E+10 | 0.00 | 590.17 | 0.443912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14731.86 | 21-MAY-15:02 | 14731.86 | 21-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.816232E+10 | 0.00 | 649.35 | 0.552143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17725.33 | 19-JUN-18:02 | 14874.66 | 17-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.101838E+11 | 0.00 | 703.76 | 0.624166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17103.76 | 22-JUL-08:61 | 14484.44 | 24-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.769894E+10 | 0.00 | 655.83 | 0.443795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16875.18 | 30-AUG-08:62 | 14563.18 | 09-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.374730E+10 | 0.00 | 466.05 | 0.259225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15158.89 | 18-SEP-18:02 | 14376.90 | 06-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.101087E+10 | 0.00 | 153.70 | 0.847620E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14374.86 | 21-OCT-15:02 | 14374.86 | 21-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 92548647.27 | 0.00 | 14.25 | 91697752.99 | 0.00 | 0.00 | 0.00 | 0.00 | 10856.07 | 17-NOV-16:01 | 10856.07 | 17-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 8734441.66 | 0.00 | 1.69 | 8734441.66 | 0.00 | 0.00 | 0.00 | 0.00 | 3132.16 | 05-DEC-19:04 | 3132.16 | 05-DEC-19:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.393958E+11 | 0.00 | 3601.44 | 0.269492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8734441.66 | 0.00 | 1.40 | 8734441.66 | 0.00 | 0.00 | 0.00 | 0.00 | 2948.02 | 2948.02 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.101838E+11 | 0.00 | 703.76 | 0.624166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17725.33 | 14874.66 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 5990347.19 | 0.00 | 0.86 | 5990347.19 | 0.00 | 0.00 | 0.00 | 0.00 | 2974.99 | 19-JAN-19:04 | 2974.99 | 19-JAN-19:04 | 0.00 | 0.00 | 0.00 |
February | 12437203.83 | 0.00 | 2.08 | 12437203.83 | 0.00 | 0.00 | 0.00 | 0.00 | 5193.59 | 20-FEB-09:03 | 5193.59 | 20-FEB-09:03 | 0.00 | 0.00 | 0.00 |
March | 0.121430E+09 | 0.00 | 24.20 | 0.121430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12188.23 | 26-MAR-08:61 | 12188.23 | 26-MAR-08:61 | 0.00 | 0.00 | 0.00 |
April | 0.126996E+10 | 0.00 | 192.02 | 0.122903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13602.34 | 13-APR-15:02 | 13602.34 | 13-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.465763E+10 | 0.00 | 554.48 | 0.355387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14359.93 | 25-MAY-15:02 | 13975.00 | 25-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.753923E+10 | 0.00 | 644.59 | 0.506715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16234.29 | 19-JUN-18:02 | 14104.13 | 17-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.921204E+10 | 0.00 | 698.02 | 0.552946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16245.55 | 22-JUL-08:61 | 13953.24 | 28-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.627425E+10 | 0.00 | 645.17 | 0.341321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16132.12 | 31-AUG-15:02 | 13978.20 | 25-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.236676E+10 | 0.00 | 392.96 | 0.151920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14321.89 | 18-SEP-18:02 | 13630.93 | 06-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.312762E+09 | 0.00 | 55.70 | 0.254975E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12970.09 | 21-OCT-15:02 | 12970.09 | 21-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 20249472.34 | 0.00 | 4.41 | 19358862.95 | 0.00 | 0.00 | 0.00 | 0.00 | 6260.38 | 21-NOV-16:03 | 6116.07 | 14-NOV-19:03 | 0.00 | 0.00 | 0.00 |
December | 5922600.51 | 0.00 | 0.93 | 5922600.51 | 0.00 | 0.00 | 0.00 | 0.00 | 3226.18 | 05-DEC-19:04 | 3226.18 | 05-DEC-19:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317987E+11 | 0.00 | 3215.42 | 0.207320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5922600.51 | 0.00 | 0.86 | 5922600.51 | 0.00 | 0.00 | 0.00 | 0.00 | 2974.99 | 2974.99 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.921204E+10 | 0.00 | 698.02 | 0.552946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16245.55 | 14104.13 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 834634.68 | 0.00 | 0.69 | 834634.68 | 0.00 | 0.00 | 0.00 | 0.00 | 1312.19 | 17-JAN-16:03 | 1312.19 | 17-JAN-16:03 | 0.00 | 0.00 | 0.00 |
February | 38381653.41 | 0.00 | 18.12 | 38381653.41 | 0.00 | 0.00 | 0.00 | 0.00 | 3950.69 | 28-FEB-16:02 | 3950.69 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.159402E+09 | 0.00 | 58.43 | 0.159402E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3954.94 | 28-MAR-18:01 | 3954.94 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.552065E+09 | 0.00 | 198.68 | 0.535287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4115.76 | 13-APR-15:02 | 4115.76 | 13-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.146002E+10 | 0.00 | 511.20 | 0.116711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4317.06 | 26-MAY-08:62 | 4226.33 | 21-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.185627E+10 | 0.00 | 577.70 | 0.123242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5231.72 | 19-JUN-18:02 | 4266.98 | 17-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.248012E+10 | 0.00 | 672.44 | 0.151740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5276.31 | 30-JUL-08:62 | 4220.77 | 23-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.188992E+10 | 0.00 | 623.75 | 0.111968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4930.40 | 30-AUG-08:62 | 4172.55 | 31-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.833329E+09 | 0.00 | 384.05 | 0.597800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4531.17 | 18-SEP-18:02 | 4124.20 | 06-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.251994E+09 | 0.00 | 109.91 | 0.220836E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4123.75 | 21-OCT-15:02 | 4123.75 | 21-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 6770580.78 | 0.00 | 5.23 | 6535260.72 | 0.00 | 0.00 | 0.00 | 0.00 | 3950.49 | 17-NOV-16:01 | 3950.49 | 17-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 405020.09 | 0.00 | 0.60 | 405020.09 | 0.00 | 0.00 | 0.00 | 0.00 | 383.37 | 28-DEC-16:04 | 383.37 | 28-DEC-16:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.952951E+10 | 0.00 | 3160.80 | 0.659609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 405020.09 | 0.00 | 0.60 | 405020.09 | 0.00 | 0.00 | 0.00 | 0.00 | 383.37 | 383.37 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.248012E+10 | 0.00 | 672.44 | 0.151740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5276.31 | 4266.98 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 376793.91 | 0.00 | 0.36 | 376793.91 | 0.00 | 0.00 | 0.00 | 0.00 | 472.27 | 17-JAN-16:04 | 472.27 | 17-JAN-16:04 | 0.00 | 0.00 | 0.00 |
February | 4367250.25 | 0.00 | 5.68 | 4367250.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1600.32 | 04-FEB-19:03 | 1600.32 | 04-FEB-19:03 | 0.00 | 0.00 | 0.00 |
March | 58301296.54 | 0.00 | 29.83 | 58301296.54 | 0.00 | 0.00 | 0.00 | 0.00 | 3740.74 | 28-MAR-18:01 | 3740.74 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.327368E+09 | 0.00 | 124.68 | 0.314432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3892.79 | 13-APR-15:02 | 3892.79 | 13-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.120864E+10 | 0.00 | 461.32 | 0.940618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4059.60 | 26-MAY-08:62 | 3997.27 | 21-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.169743E+10 | 0.00 | 561.06 | 0.112580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4891.99 | 25-JUN-08:62 | 4036.26 | 17-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.222742E+10 | 0.00 | 660.45 | 0.133625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5030.69 | 30-JUL-08:62 | 3987.73 | 24-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.151749E+10 | 0.00 | 593.41 | 0.851068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4600.77 | 30-AUG-08:62 | 3954.36 | 30-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.508828E+09 | 0.00 | 284.07 | 0.355749E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4266.29 | 18-SEP-18:02 | 3900.80 | 06-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 86936601.79 | 0.00 | 49.67 | 78660747.14 | 0.00 | 0.00 | 0.00 | 0.00 | 3900.22 | 21-OCT-15:02 | 3900.22 | 21-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 2998205.38 | 0.00 | 1.67 | 2754683.43 | 0.00 | 0.00 | 0.00 | 0.00 | 1738.74 | 15-NOV-19:03 | 1738.74 | 15-NOV-19:03 | 0.00 | 0.00 | 0.00 |
December | 156125.28 | 0.00 | 0.24 | 156125.28 | 0.00 | 0.00 | 0.00 | 0.00 | 319.83 | 28-DEC-16:04 | 319.83 | 28-DEC-16:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.764030E+10 | 0.00 | 2772.44 | 0.506853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 156125.28 | 0.00 | 0.24 | 156125.28 | 0.00 | 0.00 | 0.00 | 0.00 | 319.83 | 319.83 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.222742E+10 | 0.00 | 660.45 | 0.133625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5030.69 | 4036.26 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.510652E+09 | 0.00 | 43.85 | 0.510652E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19212.97 | 27-JAN-16:01 | 19212.97 | 27-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.151652E+10 | 0.00 | 120.22 | 0.151652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19250.24 | 21-FEB-16:02 | 19250.24 | 21-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.212182E+10 | 0.00 | 154.47 | 0.212182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19248.64 | 26-MAR-15:02 | 19248.64 | 26-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.399165E+10 | 0.00 | 299.06 | 0.389646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20137.31 | 23-APR-18:01 | 20137.31 | 23-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.729723E+10 | 0.00 | 557.91 | 0.569455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21057.44 | 25-MAY-18:02 | 20571.35 | 21-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.902627E+10 | 0.00 | 598.73 | 0.562785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26335.75 | 19-JUN-18:02 | 20766.92 | 17-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.121569E+11 | 0.00 | 670.69 | 0.714872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25636.66 | 30-JUL-08:62 | 20256.08 | 24-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.109763E+11 | 0.00 | 638.19 | 0.655264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24210.64 | 07-AUG-18:02 | 20311.99 | 31-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.674804E+10 | 0.00 | 499.94 | 0.488604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21492.82 | 18-SEP-18:02 | 20171.34 | 01-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.353817E+10 | 0.00 | 232.63 | 0.317377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20073.20 | 21-OCT-15:02 | 20073.20 | 21-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.100398E+10 | 0.00 | 77.40 | 0.999727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19235.86 | 16-NOV-16:01 | 19235.86 | 16-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.258314E+09 | 0.00 | 27.90 | 0.258314E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19087.45 | 02-DEC-16:01 | 19087.45 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.591459E+11 | 0.00 | 3921.00 | 0.423871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.258314E+09 | 0.00 | 27.90 | 0.258314E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19087.45 | 19087.45 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.121569E+11 | 0.00 | 670.69 | 0.714872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26335.75 | 20766.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 957.48 | 666.94 | 290.54 | 825.66 | 860.35 | 0.00 | 0.00 | 0.00 |
February | 1196.15 | 804.58 | 391.58 | 1147.18 | 722.33 | 0.00 | 0.00 | 0.00 |
March | 1052.49 | 662.62 | 389.87 | 1033.46 | 590.67 | 0.00 | 0.00 | 0.00 |
April | 962.07 | 522.14 | 439.93 | 1025.47 | 383.15 | 0.00 | 0.00 | 0.00 |
May | 823.67 | 291.34 | 532.33 | 966.10 | 199.61 | 0.00 | 0.00 | 0.00 |
June | 723.78 | 191.46 | 532.32 | 906.56 | 126.54 | 0.00 | 0.00 | 0.00 |
July | 796.43 | 254.27 | 542.17 | 1031.31 | 116.05 | 0.00 | 0.00 | 0.00 |
August | 844.86 | 351.86 | 493.00 | 1060.80 | 136.11 | 0.00 | 0.00 | 0.00 |
September | 890.64 | 466.29 | 424.35 | 1035.44 | 231.03 | 0.00 | 0.00 | 0.00 |
October | 791.15 | 471.57 | 319.58 | 819.40 | 368.41 | 0.00 | 0.00 | 0.00 |
November | 690.53 | 432.74 | 257.79 | 630.97 | 547.71 | 0.00 | 0.00 | 0.00 |
December | 735.39 | 482.18 | 253.21 | 588.37 | 832.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 870.00 | 464.41 | 405.58 | 920.97 | 424.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 690.53 | 191.46 | 253.21 | 588.37 | 116.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1196.15 | 804.58 | 542.17 | 1147.18 | 860.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2696.21 | 1878.05 | 818.15 | 2308.60 | 2423.10 | 0.00 | 0.00 | 0.00 |
February | 3368.29 | 2265.64 | 1102.65 | 3207.82 | 2046.39 | 0.00 | 0.00 | 0.00 |
March | 2963.73 | 1865.90 | 1097.84 | 2887.73 | 1691.31 | 0.00 | 0.00 | 0.00 |
April | 2709.13 | 1470.30 | 1238.82 | 2860.66 | 1120.59 | 0.00 | 0.00 | 0.00 |
May | 2319.39 | 820.40 | 1499.00 | 2684.02 | 604.02 | 0.00 | 0.00 | 0.00 |
June | 2038.11 | 539.13 | 1498.98 | 2513.28 | 393.25 | 0.00 | 0.00 | 0.00 |
July | 2242.71 | 716.00 | 1526.70 | 2871.91 | 356.21 | 0.00 | 0.00 | 0.00 |
August | 2379.07 | 990.81 | 1388.26 | 2956.39 | 423.62 | 0.00 | 0.00 | 0.00 |
September | 2507.98 | 1313.05 | 1194.93 | 2885.62 | 704.22 | 0.00 | 0.00 | 0.00 |
October | 2227.83 | 1327.92 | 899.92 | 2285.12 | 1083.86 | 0.00 | 0.00 | 0.00 |
November | 1944.49 | 1218.58 | 725.91 | 1759.86 | 1567.02 | 0.00 | 0.00 | 0.00 |
December | 2070.81 | 1357.79 | 713.02 | 1643.69 | 2343.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2449.85 | 1307.76 | 1142.09 | 2567.57 | 1226.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1944.49 | 539.13 | 713.02 | 1643.69 | 356.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3368.29 | 2265.64 | 1526.70 | 3207.82 | 2423.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3502.53 | 2439.70 | 1062.83 | 3034.53 | 3253.30 | 0.00 | 0.00 | 0.00 |
February | 4375.60 | 2943.19 | 1432.41 | 4228.90 | 2751.58 | 0.00 | 0.00 | 0.00 |
March | 3850.06 | 2423.91 | 1426.15 | 3807.34 | 2285.55 | 0.00 | 0.00 | 0.00 |
April | 3519.31 | 1910.01 | 1609.30 | 3766.39 | 1531.10 | 0.00 | 0.00 | 0.00 |
May | 3013.03 | 1065.74 | 1947.28 | 3528.86 | 828.56 | 0.00 | 0.00 | 0.00 |
June | 2647.62 | 700.36 | 1947.26 | 3301.36 | 543.62 | 0.00 | 0.00 | 0.00 |
July | 2913.40 | 930.13 | 1983.28 | 3778.78 | 484.46 | 0.00 | 0.00 | 0.00 |
August | 3090.54 | 1287.11 | 1803.43 | 3885.36 | 578.16 | 0.00 | 0.00 | 0.00 |
September | 3258.00 | 1705.72 | 1552.28 | 3785.64 | 970.73 | 0.00 | 0.00 | 0.00 |
October | 2894.08 | 1725.04 | 1169.04 | 2989.93 | 1498.57 | 0.00 | 0.00 | 0.00 |
November | 2526.00 | 1583.00 | 943.00 | 2306.78 | 2153.26 | 0.00 | 0.00 | 0.00 |
December | 2690.10 | 1763.84 | 926.26 | 2155.44 | 3163.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3182.50 | 1698.85 | 1483.64 | 3374.80 | 1665.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2526.00 | 700.36 | 926.26 | 2155.44 | 484.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4375.60 | 2943.19 | 1983.28 | 4228.90 | 3253.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 189.31 | 131.87 | 57.45 | 165.04 | 174.51 | 0.00 | 0.00 | 0.00 |
February | 236.50 | 159.08 | 77.42 | 228.42 | 145.78 | 0.00 | 0.00 | 0.00 |
March | 208.10 | 131.01 | 77.08 | 206.01 | 119.05 | 0.00 | 0.00 | 0.00 |
April | 190.22 | 103.24 | 86.98 | 203.69 | 77.11 | 0.00 | 0.00 | 0.00 |
May | 162.85 | 57.60 | 105.25 | 190.88 | 39.29 | 0.00 | 0.00 | 0.00 |
June | 143.10 | 37.85 | 105.25 | 179.95 | 24.04 | 0.00 | 0.00 | 0.00 |
July | 157.47 | 50.27 | 107.20 | 205.64 | 20.93 | 0.00 | 0.00 | 0.00 |
August | 167.04 | 69.57 | 97.48 | 210.97 | 24.92 | 0.00 | 0.00 | 0.00 |
September | 176.09 | 92.19 | 83.90 | 205.73 | 45.28 | 0.00 | 0.00 | 0.00 |
October | 156.42 | 93.24 | 63.19 | 163.70 | 72.79 | 0.00 | 0.00 | 0.00 |
November | 136.53 | 85.56 | 50.97 | 126.19 | 109.64 | 0.00 | 0.00 | 0.00 |
December | 145.40 | 95.34 | 50.06 | 117.55 | 168.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 172.01 | 91.82 | 80.19 | 183.33 | 84.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.53 | 37.85 | 50.06 | 117.55 | 20.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 236.50 | 159.08 | 107.20 | 228.42 | 174.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.71 | 48.59 | 66.11 | 51.83 | 373.56 | 0.00 | 0.00 | 0.00 |
February | 185.50 | 85.16 | 100.34 | 124.16 | 299.76 | 0.00 | 0.00 | 0.00 |
March | 243.24 | 124.74 | 118.51 | 197.08 | 232.31 | 0.00 | 0.00 | 0.00 |
April | 310.38 | 157.39 | 152.99 | 301.18 | 141.11 | 0.00 | 0.00 | 0.00 |
May | 381.67 | 182.52 | 199.15 | 436.04 | 71.35 | 0.00 | 0.00 | 0.00 |
June | 366.76 | 158.34 | 208.43 | 446.56 | 44.11 | 0.00 | 0.00 | 0.00 |
July | 392.11 | 182.30 | 209.81 | 491.24 | 38.65 | 0.00 | 0.00 | 0.00 |
August | 321.88 | 145.81 | 176.06 | 391.17 | 46.15 | 0.00 | 0.00 | 0.00 |
September | 252.67 | 113.39 | 139.28 | 274.42 | 83.94 | 0.00 | 0.00 | 0.00 |
October | 159.86 | 64.33 | 95.53 | 137.63 | 140.23 | 0.00 | 0.00 | 0.00 |
November | 97.31 | 33.11 | 64.20 | 52.97 | 222.56 | 0.00 | 0.00 | 0.00 |
December | 85.79 | 29.76 | 56.03 | 28.97 | 360.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.97 | 110.61 | 132.37 | 245.16 | 170.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.79 | 29.76 | 56.03 | 28.97 | 38.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 392.11 | 182.52 | 209.81 | 491.24 | 373.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.33 | 0.00 | 27.33 | 0.45 | 215.79 | 0.00 | 0.00 | 0.00 |
February | 41.98 | 0.00 | 41.98 | 4.52 | 169.95 | 0.00 | 0.00 | 0.00 |
March | 51.66 | 0.00 | 51.66 | 11.79 | 129.77 | 0.00 | 0.00 | 0.00 |
April | 67.94 | 0.71 | 67.23 | 37.16 | 75.91 | 0.00 | 0.00 | 0.00 |
May | 95.31 | 5.09 | 90.21 | 91.37 | 35.55 | 0.00 | 0.00 | 0.00 |
June | 106.53 | 11.91 | 94.62 | 123.58 | 22.23 | 0.00 | 0.00 | 0.00 |
July | 101.84 | 8.99 | 92.85 | 123.00 | 19.56 | 0.00 | 0.00 | 0.00 |
August | 77.31 | 1.48 | 75.82 | 85.45 | 23.87 | 0.00 | 0.00 | 0.00 |
September | 60.18 | 0.06 | 60.12 | 51.05 | 45.15 | 0.00 | 0.00 | 0.00 |
October | 41.72 | 0.00 | 41.72 | 19.92 | 76.41 | 0.00 | 0.00 | 0.00 |
November | 27.62 | 0.00 | 27.62 | 3.55 | 124.12 | 0.00 | 0.00 | 0.00 |
December | 23.15 | 0.00 | 23.15 | 0.03 | 206.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.30 | 2.36 | 57.94 | 46.24 | 95.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.15 | 0.00 | 23.15 | 0.03 | 19.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.53 | 11.91 | 94.62 | 123.58 | 215.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.71 | 48.59 | 66.11 | 53.36 | 371.92 | 0.00 | 0.00 | 0.00 |
February | 185.50 | 85.16 | 100.34 | 128.18 | 297.15 | 0.00 | 0.00 | 0.00 |
March | 243.24 | 124.74 | 118.51 | 201.42 | 229.78 | 0.00 | 0.00 | 0.00 |
April | 310.38 | 157.39 | 152.99 | 305.66 | 139.72 | 0.00 | 0.00 | 0.00 |
May | 381.67 | 182.52 | 199.15 | 438.19 | 70.84 | 0.00 | 0.00 | 0.00 |
June | 366.76 | 158.34 | 208.43 | 447.67 | 43.82 | 0.00 | 0.00 | 0.00 |
July | 392.11 | 182.30 | 209.81 | 492.64 | 38.28 | 0.00 | 0.00 | 0.00 |
August | 321.88 | 145.81 | 176.06 | 393.33 | 45.56 | 0.00 | 0.00 | 0.00 |
September | 252.67 | 113.39 | 139.28 | 277.62 | 82.95 | 0.00 | 0.00 | 0.00 |
October | 159.86 | 64.33 | 95.53 | 140.79 | 138.67 | 0.00 | 0.00 | 0.00 |
November | 97.31 | 33.11 | 64.20 | 55.36 | 220.79 | 0.00 | 0.00 | 0.00 |
December | 85.79 | 29.76 | 56.03 | 29.92 | 359.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.97 | 110.61 | 132.37 | 247.72 | 169.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.79 | 29.76 | 56.03 | 29.92 | 38.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 392.11 | 182.52 | 209.81 | 492.64 | 371.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 151.42 | 105.47 | 45.95 | 131.35 | 136.79 | 0.00 | 0.00 | 0.00 |
February | 189.16 | 127.24 | 61.93 | 181.65 | 115.80 | 0.00 | 0.00 | 0.00 |
March | 166.44 | 104.79 | 61.65 | 163.89 | 95.49 | 0.00 | 0.00 | 0.00 |
April | 152.14 | 82.57 | 69.57 | 161.49 | 64.56 | 0.00 | 0.00 | 0.00 |
May | 130.26 | 46.07 | 84.18 | 151.19 | 35.24 | 0.00 | 0.00 | 0.00 |
June | 114.46 | 30.28 | 84.18 | 142.18 | 22.63 | 0.00 | 0.00 | 0.00 |
July | 125.95 | 40.21 | 85.74 | 163.21 | 20.08 | 0.00 | 0.00 | 0.00 |
August | 133.61 | 55.64 | 77.97 | 167.18 | 24.16 | 0.00 | 0.00 | 0.00 |
September | 140.85 | 73.74 | 67.11 | 162.44 | 41.17 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 74.58 | 50.54 | 129.53 | 61.00 | 0.00 | 0.00 | 0.00 |
November | 109.20 | 68.43 | 40.77 | 100.48 | 86.29 | 0.00 | 0.00 | 0.00 |
December | 116.30 | 76.25 | 40.04 | 93.71 | 131.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 137.58 | 73.44 | 64.14 | 145.44 | 69.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.20 | 30.28 | 40.04 | 93.71 | 20.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 189.16 | 127.24 | 85.74 | 181.65 | 136.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.87 | 0.00 | 21.87 | 0.26 | 177.77 | 0.00 | 0.00 | 0.00 |
February | 33.59 | 0.00 | 33.59 | 3.24 | 139.43 | 0.00 | 0.00 | 0.00 |
March | 41.33 | 0.00 | 41.33 | 9.19 | 105.57 | 0.00 | 0.00 | 0.00 |
April | 54.36 | 0.56 | 53.79 | 30.81 | 60.91 | 0.00 | 0.00 | 0.00 |
May | 76.25 | 4.07 | 72.18 | 76.61 | 27.65 | 0.00 | 0.00 | 0.00 |
June | 85.24 | 9.53 | 75.71 | 102.60 | 16.96 | 0.00 | 0.00 | 0.00 |
July | 81.48 | 7.19 | 74.29 | 102.70 | 14.45 | 0.00 | 0.00 | 0.00 |
August | 61.85 | 1.19 | 60.67 | 71.91 | 17.94 | 0.00 | 0.00 | 0.00 |
September | 48.15 | 0.05 | 48.10 | 42.70 | 35.45 | 0.00 | 0.00 | 0.00 |
October | 33.38 | 0.00 | 33.38 | 15.65 | 62.41 | 0.00 | 0.00 | 0.00 |
November | 22.10 | 0.00 | 22.10 | 2.44 | 103.00 | 0.00 | 0.00 | 0.00 |
December | 18.53 | 0.00 | 18.53 | 0.01 | 170.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.25 | 1.89 | 46.36 | 38.39 | 77.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.53 | 0.00 | 18.53 | 0.01 | 14.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.24 | 9.53 | 75.71 | 102.70 | 177.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.63 | 46.33 | 65.30 | 44.72 | 368.50 | 0.00 | 0.00 | 0.00 |
February | 177.32 | 76.29 | 101.03 | 106.56 | 289.68 | 0.00 | 0.00 | 0.00 |
March | 240.89 | 121.07 | 119.82 | 186.21 | 224.59 | 0.00 | 0.00 | 0.00 |
April | 331.70 | 178.76 | 152.95 | 323.04 | 135.62 | 0.00 | 0.00 | 0.00 |
May | 360.29 | 158.83 | 201.46 | 404.83 | 66.87 | 0.00 | 0.00 | 0.00 |
June | 406.53 | 194.36 | 212.17 | 495.79 | 42.20 | 0.00 | 0.00 | 0.00 |
July | 399.08 | 187.66 | 211.42 | 497.81 | 36.58 | 0.00 | 0.00 | 0.00 |
August | 307.20 | 134.19 | 173.01 | 369.79 | 44.56 | 0.00 | 0.00 | 0.00 |
September | 246.70 | 110.66 | 136.04 | 264.59 | 81.38 | 0.00 | 0.00 | 0.00 |
October | 148.58 | 55.87 | 92.70 | 120.08 | 136.77 | 0.00 | 0.00 | 0.00 |
November | 95.22 | 31.74 | 63.47 | 47.39 | 218.32 | 0.00 | 0.00 | 0.00 |
December | 87.56 | 32.91 | 54.65 | 28.26 | 356.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.96 | 110.81 | 132.16 | 241.40 | 166.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.56 | 31.74 | 54.65 | 28.26 | 36.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 406.53 | 194.36 | 212.17 | 497.81 | 368.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 189.31 | 131.87 | 57.45 | 164.89 | 174.36 | 0.00 | 0.00 | 0.00 |
February | 236.50 | 159.08 | 77.42 | 228.12 | 145.45 | 0.00 | 0.00 | 0.00 |
March | 208.10 | 131.01 | 77.08 | 205.00 | 118.59 | 0.00 | 0.00 | 0.00 |
April | 190.22 | 103.24 | 86.98 | 202.23 | 76.74 | 0.00 | 0.00 | 0.00 |
May | 162.85 | 57.60 | 105.25 | 190.32 | 38.83 | 0.00 | 0.00 | 0.00 |
June | 143.10 | 37.85 | 105.25 | 178.71 | 23.73 | 0.00 | 0.00 | 0.00 |
July | 157.47 | 50.27 | 107.20 | 204.95 | 20.45 | 0.00 | 0.00 | 0.00 |
August | 167.04 | 69.57 | 97.48 | 210.61 | 24.56 | 0.00 | 0.00 | 0.00 |
September | 176.09 | 92.19 | 83.90 | 205.24 | 44.84 | 0.00 | 0.00 | 0.00 |
October | 156.42 | 93.24 | 63.19 | 163.46 | 72.45 | 0.00 | 0.00 | 0.00 |
November | 136.53 | 85.56 | 50.97 | 126.09 | 109.48 | 0.00 | 0.00 | 0.00 |
December | 145.40 | 95.34 | 50.06 | 117.39 | 168.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 172.01 | 91.82 | 80.19 | 182.77 | 84.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.53 | 37.85 | 50.06 | 117.39 | 20.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 236.50 | 159.08 | 107.20 | 228.12 | 174.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.33 | 0.00 | 27.33 | 0.44 | 215.80 | 0.00 | 0.00 | 0.00 |
February | 41.98 | 0.00 | 41.98 | 4.33 | 169.78 | 0.00 | 0.00 | 0.00 |
March | 51.66 | 0.00 | 51.66 | 11.17 | 129.55 | 0.00 | 0.00 | 0.00 |
April | 67.94 | 0.71 | 67.23 | 35.67 | 75.93 | 0.00 | 0.00 | 0.00 |
May | 95.31 | 5.09 | 90.21 | 90.72 | 35.22 | 0.00 | 0.00 | 0.00 |
June | 106.53 | 11.91 | 94.62 | 122.31 | 22.03 | 0.00 | 0.00 | 0.00 |
July | 101.84 | 8.99 | 92.85 | 122.34 | 19.20 | 0.00 | 0.00 | 0.00 |
August | 77.31 | 1.48 | 75.82 | 84.98 | 23.53 | 0.00 | 0.00 | 0.00 |
September | 60.18 | 0.06 | 60.12 | 50.31 | 44.77 | 0.00 | 0.00 | 0.00 |
October | 41.72 | 0.00 | 41.72 | 19.53 | 75.98 | 0.00 | 0.00 | 0.00 |
November | 27.62 | 0.00 | 27.62 | 3.45 | 124.06 | 0.00 | 0.00 | 0.00 |
December | 23.15 | 0.00 | 23.15 | 0.03 | 206.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.30 | 2.36 | 57.94 | 45.70 | 94.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.15 | 0.00 | 23.15 | 0.03 | 19.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.53 | 11.91 | 94.62 | 122.34 | 215.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.63 | 46.33 | 65.30 | 45.64 | 366.27 | 0.00 | 0.00 | 0.00 |
February | 177.32 | 76.29 | 101.03 | 109.47 | 285.92 | 0.00 | 0.00 | 0.00 |
March | 240.89 | 121.07 | 119.82 | 190.08 | 221.23 | 0.00 | 0.00 | 0.00 |
April | 331.70 | 178.76 | 152.95 | 326.73 | 134.10 | 0.00 | 0.00 | 0.00 |
May | 360.29 | 158.83 | 201.46 | 406.69 | 66.37 | 0.00 | 0.00 | 0.00 |
June | 406.53 | 194.36 | 212.17 | 496.86 | 41.97 | 0.00 | 0.00 | 0.00 |
July | 399.08 | 187.66 | 211.42 | 499.21 | 36.25 | 0.00 | 0.00 | 0.00 |
August | 307.20 | 134.19 | 173.01 | 371.78 | 43.97 | 0.00 | 0.00 | 0.00 |
September | 246.70 | 110.66 | 136.04 | 267.29 | 80.33 | 0.00 | 0.00 | 0.00 |
October | 148.58 | 55.87 | 92.70 | 122.97 | 134.98 | 0.00 | 0.00 | 0.00 |
November | 95.22 | 31.74 | 63.47 | 48.81 | 215.72 | 0.00 | 0.00 | 0.00 |
December | 87.56 | 32.91 | 54.65 | 28.79 | 355.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.96 | 110.81 | 132.16 | 243.50 | 164.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.56 | 31.74 | 54.65 | 28.79 | 36.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 406.53 | 194.36 | 212.17 | 499.21 | 366.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.61 | 0.00 | 34.61 | 0.28 | 289.85 | 0.00 | 0.00 | 0.00 |
February | 53.16 | 0.00 | 53.16 | 4.19 | 227.83 | 0.00 | 0.00 | 0.00 |
March | 65.42 | 0.00 | 65.42 | 12.96 | 172.63 | 0.00 | 0.00 | 0.00 |
April | 86.04 | 0.89 | 85.14 | 45.73 | 101.45 | 0.00 | 0.00 | 0.00 |
May | 120.70 | 6.45 | 114.25 | 115.24 | 49.96 | 0.00 | 0.00 | 0.00 |
June | 134.92 | 15.08 | 119.83 | 154.80 | 32.86 | 0.00 | 0.00 | 0.00 |
July | 128.98 | 11.38 | 117.59 | 153.43 | 30.30 | 0.00 | 0.00 | 0.00 |
August | 97.90 | 1.88 | 96.02 | 106.59 | 36.67 | 0.00 | 0.00 | 0.00 |
September | 76.21 | 0.08 | 76.13 | 62.89 | 64.14 | 0.00 | 0.00 | 0.00 |
October | 52.83 | 0.00 | 52.83 | 22.85 | 103.87 | 0.00 | 0.00 | 0.00 |
November | 34.98 | 0.00 | 34.98 | 3.42 | 168.31 | 0.00 | 0.00 | 0.00 |
December | 29.32 | 0.00 | 29.32 | 0.00 | 277.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 76.37 | 2.99 | 73.38 | 57.19 | 129.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.32 | 0.00 | 29.32 | 0.00 | 30.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 134.92 | 15.08 | 119.83 | 154.80 | 289.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.76 | 0.00 | 12.76 | 0.10 | 106.85 | 0.00 | 0.00 | 0.00 |
February | 19.60 | 0.00 | 19.60 | 1.54 | 83.99 | 0.00 | 0.00 | 0.00 |
March | 24.12 | 0.00 | 24.12 | 4.78 | 63.64 | 0.00 | 0.00 | 0.00 |
April | 31.72 | 0.33 | 31.39 | 16.86 | 37.40 | 0.00 | 0.00 | 0.00 |
May | 44.49 | 2.38 | 42.12 | 42.48 | 18.42 | 0.00 | 0.00 | 0.00 |
June | 49.74 | 5.56 | 44.18 | 57.07 | 12.11 | 0.00 | 0.00 | 0.00 |
July | 47.55 | 4.20 | 43.35 | 56.56 | 11.17 | 0.00 | 0.00 | 0.00 |
August | 36.09 | 0.69 | 35.40 | 39.29 | 13.52 | 0.00 | 0.00 | 0.00 |
September | 28.10 | 0.03 | 28.07 | 23.18 | 23.64 | 0.00 | 0.00 | 0.00 |
October | 19.48 | 0.00 | 19.48 | 8.42 | 38.29 | 0.00 | 0.00 | 0.00 |
November | 12.90 | 0.00 | 12.90 | 1.26 | 62.05 | 0.00 | 0.00 | 0.00 |
December | 10.81 | 0.00 | 10.81 | 0.00 | 102.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.15 | 1.10 | 27.05 | 21.08 | 47.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.81 | 0.00 | 10.81 | 0.00 | 11.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.74 | 5.56 | 44.18 | 57.07 | 106.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.33 | 61.53 | 26.80 | 75.78 | 84.75 | 0.00 | 0.00 | 0.00 |
February | 110.35 | 74.23 | 36.12 | 106.08 | 70.46 | 0.00 | 0.00 | 0.00 |
March | 97.10 | 61.13 | 35.97 | 96.10 | 57.39 | 0.00 | 0.00 | 0.00 |
April | 88.76 | 48.17 | 40.59 | 95.50 | 37.48 | 0.00 | 0.00 | 0.00 |
May | 75.99 | 26.88 | 49.11 | 89.44 | 20.20 | 0.00 | 0.00 | 0.00 |
June | 66.77 | 17.66 | 49.11 | 83.66 | 13.15 | 0.00 | 0.00 | 0.00 |
July | 73.47 | 23.46 | 50.02 | 95.50 | 11.97 | 0.00 | 0.00 | 0.00 |
August | 77.94 | 32.46 | 45.48 | 98.38 | 13.97 | 0.00 | 0.00 | 0.00 |
September | 82.17 | 43.02 | 39.15 | 96.05 | 23.40 | 0.00 | 0.00 | 0.00 |
October | 72.99 | 43.50 | 29.48 | 76.28 | 35.89 | 0.00 | 0.00 | 0.00 |
November | 63.70 | 39.92 | 23.78 | 58.32 | 53.64 | 0.00 | 0.00 | 0.00 |
December | 67.84 | 44.48 | 23.36 | 53.72 | 82.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.26 | 42.84 | 37.42 | 85.25 | 41.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.70 | 17.66 | 23.36 | 53.72 | 11.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.35 | 74.23 | 50.02 | 106.08 | 84.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 239.75 | 167.00 | 72.75 | 205.68 | 230.02 | 0.00 | 0.00 | 0.00 |
February | 299.51 | 201.46 | 98.05 | 287.93 | 191.23 | 0.00 | 0.00 | 0.00 |
March | 263.54 | 165.92 | 97.62 | 260.84 | 155.78 | 0.00 | 0.00 | 0.00 |
April | 240.90 | 130.74 | 110.16 | 259.19 | 101.74 | 0.00 | 0.00 | 0.00 |
May | 206.24 | 72.95 | 133.29 | 242.75 | 54.82 | 0.00 | 0.00 | 0.00 |
June | 181.23 | 47.94 | 133.29 | 227.08 | 35.70 | 0.00 | 0.00 | 0.00 |
July | 199.43 | 63.67 | 135.76 | 259.20 | 32.49 | 0.00 | 0.00 | 0.00 |
August | 211.55 | 88.10 | 123.45 | 267.02 | 37.91 | 0.00 | 0.00 | 0.00 |
September | 223.01 | 116.76 | 106.26 | 260.71 | 63.51 | 0.00 | 0.00 | 0.00 |
October | 198.10 | 118.08 | 80.02 | 207.04 | 97.40 | 0.00 | 0.00 | 0.00 |
November | 172.91 | 108.36 | 64.55 | 158.29 | 145.58 | 0.00 | 0.00 | 0.00 |
December | 184.14 | 120.74 | 63.40 | 145.80 | 223.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 217.84 | 116.29 | 101.56 | 231.39 | 113.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 172.91 | 47.94 | 63.40 | 145.80 | 32.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 299.51 | 201.46 | 135.76 | 287.93 | 230.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 189.31 | 131.87 | 57.45 | 164.83 | 174.37 | 0.00 | 0.00 | 0.00 |
February | 236.50 | 159.08 | 77.42 | 227.98 | 145.43 | 0.00 | 0.00 | 0.00 |
March | 208.10 | 131.01 | 77.08 | 205.77 | 118.62 | 0.00 | 0.00 | 0.00 |
April | 190.22 | 103.24 | 86.98 | 203.31 | 76.56 | 0.00 | 0.00 | 0.00 |
May | 162.85 | 57.60 | 105.25 | 190.16 | 38.88 | 0.00 | 0.00 | 0.00 |
June | 143.10 | 37.85 | 105.25 | 179.33 | 23.61 | 0.00 | 0.00 | 0.00 |
July | 157.47 | 50.27 | 107.20 | 204.95 | 20.50 | 0.00 | 0.00 | 0.00 |
August | 167.04 | 69.57 | 97.48 | 210.29 | 24.43 | 0.00 | 0.00 | 0.00 |
September | 176.09 | 92.19 | 83.90 | 205.30 | 44.66 | 0.00 | 0.00 | 0.00 |
October | 156.42 | 93.24 | 63.19 | 163.72 | 71.98 | 0.00 | 0.00 | 0.00 |
November | 136.53 | 85.56 | 50.97 | 126.17 | 109.01 | 0.00 | 0.00 | 0.00 |
December | 145.40 | 95.34 | 50.06 | 117.34 | 168.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 172.01 | 91.82 | 80.19 | 182.95 | 84.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.53 | 37.85 | 50.06 | 117.34 | 20.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 236.50 | 159.08 | 107.20 | 227.98 | 174.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.71 | 48.59 | 66.11 | 51.73 | 373.38 | 0.00 | 0.00 | 0.00 |
February | 185.50 | 85.16 | 100.34 | 123.96 | 299.20 | 0.00 | 0.00 | 0.00 |
March | 243.24 | 124.74 | 118.51 | 196.75 | 231.42 | 0.00 | 0.00 | 0.00 |
April | 310.38 | 157.39 | 152.99 | 300.42 | 140.01 | 0.00 | 0.00 | 0.00 |
May | 381.67 | 182.52 | 199.15 | 434.61 | 70.51 | 0.00 | 0.00 | 0.00 |
June | 366.76 | 158.34 | 208.43 | 445.23 | 43.30 | 0.00 | 0.00 | 0.00 |
July | 392.11 | 182.30 | 209.81 | 489.72 | 37.82 | 0.00 | 0.00 | 0.00 |
August | 321.88 | 145.81 | 176.06 | 390.04 | 45.22 | 0.00 | 0.00 | 0.00 |
September | 252.67 | 113.39 | 139.28 | 273.91 | 82.67 | 0.00 | 0.00 | 0.00 |
October | 159.86 | 64.33 | 95.53 | 137.87 | 138.56 | 0.00 | 0.00 | 0.00 |
November | 97.31 | 33.11 | 64.20 | 53.25 | 221.32 | 0.00 | 0.00 | 0.00 |
December | 85.79 | 29.76 | 56.03 | 28.90 | 360.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.97 | 110.61 | 132.37 | 244.58 | 169.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.79 | 29.76 | 56.03 | 28.90 | 37.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 392.11 | 182.52 | 209.81 | 489.72 | 373.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.33 | 0.00 | 27.33 | 0.45 | 215.56 | 0.00 | 0.00 | 0.00 |
February | 41.98 | 0.00 | 41.98 | 4.62 | 169.59 | 0.00 | 0.00 | 0.00 |
March | 51.66 | 0.00 | 51.66 | 11.93 | 129.37 | 0.00 | 0.00 | 0.00 |
April | 67.94 | 0.71 | 67.23 | 37.45 | 75.33 | 0.00 | 0.00 | 0.00 |
May | 95.31 | 5.09 | 90.21 | 91.08 | 35.15 | 0.00 | 0.00 | 0.00 |
June | 106.53 | 11.91 | 94.62 | 123.27 | 21.86 | 0.00 | 0.00 | 0.00 |
July | 101.84 | 8.99 | 92.85 | 122.71 | 19.18 | 0.00 | 0.00 | 0.00 |
August | 77.31 | 1.48 | 75.82 | 85.39 | 23.37 | 0.00 | 0.00 | 0.00 |
September | 60.18 | 0.06 | 60.12 | 51.39 | 44.39 | 0.00 | 0.00 | 0.00 |
October | 41.72 | 0.00 | 41.72 | 20.44 | 75.38 | 0.00 | 0.00 | 0.00 |
November | 27.62 | 0.00 | 27.62 | 3.71 | 123.30 | 0.00 | 0.00 | 0.00 |
December | 23.15 | 0.00 | 23.15 | 0.04 | 206.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.30 | 2.36 | 57.94 | 46.29 | 94.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.15 | 0.00 | 23.15 | 0.04 | 19.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.53 | 11.91 | 94.62 | 123.27 | 215.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.71 | 48.59 | 66.11 | 53.20 | 371.86 | 0.00 | 0.00 | 0.00 |
February | 185.50 | 85.16 | 100.34 | 127.88 | 296.72 | 0.00 | 0.00 | 0.00 |
March | 243.24 | 124.74 | 118.51 | 201.15 | 228.96 | 0.00 | 0.00 | 0.00 |
April | 310.38 | 157.39 | 152.99 | 305.28 | 138.51 | 0.00 | 0.00 | 0.00 |
May | 381.67 | 182.52 | 199.15 | 436.93 | 69.95 | 0.00 | 0.00 | 0.00 |
June | 366.76 | 158.34 | 208.43 | 446.41 | 43.00 | 0.00 | 0.00 | 0.00 |
July | 392.11 | 182.30 | 209.81 | 491.20 | 37.43 | 0.00 | 0.00 | 0.00 |
August | 321.88 | 145.81 | 176.06 | 392.36 | 44.57 | 0.00 | 0.00 | 0.00 |
September | 252.67 | 113.39 | 139.28 | 277.53 | 81.50 | 0.00 | 0.00 | 0.00 |
October | 159.86 | 64.33 | 95.53 | 141.40 | 136.80 | 0.00 | 0.00 | 0.00 |
November | 97.31 | 33.11 | 64.20 | 55.66 | 219.66 | 0.00 | 0.00 | 0.00 |
December | 85.79 | 29.76 | 56.03 | 29.83 | 359.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.97 | 110.61 | 132.37 | 247.27 | 168.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.79 | 29.76 | 56.03 | 29.83 | 37.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 392.11 | 182.52 | 209.81 | 491.20 | 371.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 277.64 | 193.39 | 84.25 | 235.05 | 261.58 | 0.00 | 0.00 | 0.00 |
February | 346.85 | 233.30 | 113.55 | 326.75 | 218.89 | 0.00 | 0.00 | 0.00 |
March | 305.19 | 192.14 | 113.05 | 296.34 | 177.91 | 0.00 | 0.00 | 0.00 |
April | 278.97 | 151.40 | 127.57 | 295.09 | 113.56 | 0.00 | 0.00 | 0.00 |
May | 238.84 | 84.48 | 154.36 | 279.78 | 56.25 | 0.00 | 0.00 | 0.00 |
June | 209.88 | 55.52 | 154.36 | 264.85 | 33.92 | 0.00 | 0.00 | 0.00 |
July | 230.94 | 73.73 | 157.21 | 302.83 | 28.99 | 0.00 | 0.00 | 0.00 |
August | 244.99 | 102.03 | 142.96 | 309.20 | 35.27 | 0.00 | 0.00 | 0.00 |
September | 258.26 | 135.21 | 123.05 | 299.51 | 66.01 | 0.00 | 0.00 | 0.00 |
October | 229.41 | 136.74 | 92.67 | 236.59 | 108.42 | 0.00 | 0.00 | 0.00 |
November | 200.23 | 125.48 | 74.75 | 180.26 | 164.69 | 0.00 | 0.00 | 0.00 |
December | 213.24 | 139.82 | 73.42 | 166.99 | 252.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 252.27 | 134.67 | 117.61 | 265.67 | 126.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 200.23 | 55.52 | 73.42 | 166.99 | 28.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 346.85 | 233.30 | 157.21 | 326.75 | 261.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 191.29 | 0.00 | 191.29 | 0.95 | 1619.67 | 0.00 | 0.00 | 0.00 |
February | 293.84 | 0.00 | 293.84 | 19.05 | 1301.13 | 0.00 | 0.00 | 0.00 |
March | 361.60 | 0.01 | 361.59 | 60.74 | 1009.32 | 0.00 | 0.00 | 0.00 |
April | 475.54 | 4.94 | 470.60 | 227.82 | 602.85 | 0.00 | 0.00 | 0.00 |
May | 667.11 | 35.64 | 631.47 | 612.68 | 285.09 | 0.00 | 0.00 | 0.00 |
June | 745.70 | 83.37 | 662.33 | 836.79 | 185.63 | 0.00 | 0.00 | 0.00 |
July | 712.87 | 62.93 | 649.95 | 841.56 | 163.54 | 0.00 | 0.00 | 0.00 |
August | 541.12 | 10.39 | 530.73 | 576.70 | 204.12 | 0.00 | 0.00 | 0.00 |
September | 421.24 | 0.44 | 420.80 | 329.67 | 370.47 | 0.00 | 0.00 | 0.00 |
October | 292.01 | 0.00 | 292.01 | 108.22 | 624.99 | 0.00 | 0.00 | 0.00 |
November | 193.35 | 0.00 | 193.35 | 13.57 | 1002.78 | 0.00 | 0.00 | 0.00 |
December | 162.08 | 0.00 | 162.08 | 0.00 | 1565.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 422.12 | 16.55 | 405.57 | 304.10 | 742.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.08 | 0.00 | 162.08 | 0.00 | 163.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 745.70 | 83.37 | 662.33 | 841.56 | 1619.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 191.29 | 0.00 | 191.29 | 0.67 | 1644.87 | 0.00 | 0.00 | 0.00 |
February | 293.84 | 0.00 | 293.84 | 16.76 | 1327.03 | 0.00 | 0.00 | 0.00 |
March | 361.60 | 0.01 | 361.59 | 55.94 | 1031.31 | 0.00 | 0.00 | 0.00 |
April | 475.54 | 4.94 | 470.60 | 218.76 | 615.75 | 0.00 | 0.00 | 0.00 |
May | 667.11 | 35.64 | 631.47 | 603.97 | 290.65 | 0.00 | 0.00 | 0.00 |
June | 745.70 | 83.37 | 662.33 | 828.90 | 189.89 | 0.00 | 0.00 | 0.00 |
July | 712.87 | 62.93 | 649.95 | 834.87 | 167.33 | 0.00 | 0.00 | 0.00 |
August | 541.12 | 10.39 | 530.73 | 569.76 | 209.44 | 0.00 | 0.00 | 0.00 |
September | 421.24 | 0.44 | 420.80 | 322.05 | 379.03 | 0.00 | 0.00 | 0.00 |
October | 292.01 | 0.00 | 292.01 | 101.66 | 640.23 | 0.00 | 0.00 | 0.00 |
November | 193.35 | 0.00 | 193.35 | 11.87 | 1028.44 | 0.00 | 0.00 | 0.00 |
December | 162.08 | 0.00 | 162.08 | 0.00 | 1591.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 422.12 | 16.55 | 405.57 | 298.87 | 757.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.08 | 0.00 | 162.08 | 0.00 | 167.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 745.70 | 83.37 | 662.33 | 834.87 | 1644.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.33 | 0.00 | 27.33 | 1.31 | 195.66 | 0.00 | 0.00 | 0.00 |
February | 41.98 | 0.00 | 41.98 | 7.99 | 155.49 | 0.00 | 0.00 | 0.00 |
March | 51.66 | 0.00 | 51.66 | 19.03 | 118.19 | 0.00 | 0.00 | 0.00 |
April | 67.94 | 0.71 | 67.23 | 54.31 | 71.24 | 0.00 | 0.00 | 0.00 |
May | 95.31 | 5.09 | 90.21 | 122.80 | 35.44 | 0.00 | 0.00 | 0.00 |
June | 106.53 | 11.91 | 94.62 | 157.44 | 23.34 | 0.00 | 0.00 | 0.00 |
July | 101.84 | 8.99 | 92.85 | 158.96 | 20.11 | 0.00 | 0.00 | 0.00 |
August | 77.31 | 1.48 | 75.82 | 117.69 | 23.10 | 0.00 | 0.00 | 0.00 |
September | 60.18 | 0.06 | 60.12 | 74.35 | 40.69 | 0.00 | 0.00 | 0.00 |
October | 41.72 | 0.00 | 41.72 | 32.46 | 68.03 | 0.00 | 0.00 | 0.00 |
November | 27.62 | 0.00 | 27.62 | 7.48 | 111.34 | 0.00 | 0.00 | 0.00 |
December | 23.15 | 0.00 | 23.15 | 0.53 | 187.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.30 | 2.36 | 57.94 | 63.20 | 87.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.15 | 0.00 | 23.15 | 0.53 | 20.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.53 | 11.91 | 94.62 | 158.96 | 195.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 223.25 | 92.66 | 130.59 | 109.42 | 670.81 | 0.00 | 0.00 | 0.00 |
February | 354.62 | 152.58 | 202.05 | 247.59 | 530.61 | 0.00 | 0.00 | 0.00 |
March | 481.75 | 242.13 | 239.62 | 422.87 | 410.94 | 0.00 | 0.00 | 0.00 |
April | 663.36 | 357.49 | 305.87 | 732.77 | 256.80 | 0.00 | 0.00 | 0.00 |
May | 720.53 | 317.64 | 402.89 | 932.11 | 132.38 | 0.00 | 0.00 | 0.00 |
June | 813.01 | 388.69 | 424.32 | 1122.91 | 87.46 | 0.00 | 0.00 | 0.00 |
July | 798.10 | 375.29 | 422.81 | 1134.84 | 75.30 | 0.00 | 0.00 | 0.00 |
August | 614.36 | 268.36 | 346.00 | 865.88 | 86.51 | 0.00 | 0.00 | 0.00 |
September | 493.36 | 221.30 | 272.06 | 630.00 | 149.57 | 0.00 | 0.00 | 0.00 |
October | 297.13 | 111.73 | 185.40 | 302.89 | 246.65 | 0.00 | 0.00 | 0.00 |
November | 190.42 | 63.48 | 126.94 | 123.11 | 392.45 | 0.00 | 0.00 | 0.00 |
December | 175.11 | 65.81 | 109.30 | 70.60 | 649.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 485.89 | 221.60 | 264.30 | 559.43 | 306.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.11 | 63.48 | 109.30 | 70.60 | 75.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 813.01 | 388.69 | 424.32 | 1134.84 | 670.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 189.31 | 131.87 | 57.45 | 175.62 | 161.21 | 0.00 | 0.00 | 0.00 |
February | 236.50 | 159.08 | 77.42 | 241.69 | 135.73 | 0.00 | 0.00 | 0.00 |
March | 208.10 | 131.01 | 77.08 | 221.40 | 109.96 | 0.00 | 0.00 | 0.00 |
April | 190.22 | 103.24 | 86.98 | 224.92 | 71.55 | 0.00 | 0.00 | 0.00 |
May | 162.85 | 57.60 | 105.25 | 222.52 | 37.43 | 0.00 | 0.00 | 0.00 |
June | 143.10 | 37.85 | 105.25 | 213.69 | 24.47 | 0.00 | 0.00 | 0.00 |
July | 157.47 | 50.27 | 107.20 | 241.93 | 20.87 | 0.00 | 0.00 | 0.00 |
August | 167.04 | 69.57 | 97.48 | 243.96 | 23.41 | 0.00 | 0.00 | 0.00 |
September | 176.09 | 92.19 | 83.90 | 231.92 | 40.59 | 0.00 | 0.00 | 0.00 |
October | 156.42 | 93.24 | 63.19 | 181.68 | 65.87 | 0.00 | 0.00 | 0.00 |
November | 136.53 | 85.56 | 50.97 | 137.09 | 100.49 | 0.00 | 0.00 | 0.00 |
December | 145.40 | 95.34 | 50.06 | 126.21 | 156.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 172.01 | 91.82 | 80.19 | 204.96 | 78.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.53 | 37.85 | 50.06 | 126.21 | 20.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 236.50 | 159.08 | 107.20 | 243.96 | 161.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.61 | 0.00 | 34.61 | 0.23 | 291.70 | 0.00 | 0.00 | 0.00 |
February | 53.16 | 0.00 | 53.16 | 3.75 | 230.11 | 0.00 | 0.00 | 0.00 |
March | 65.42 | 0.00 | 65.42 | 11.86 | 174.63 | 0.00 | 0.00 | 0.00 |
April | 86.04 | 0.89 | 85.14 | 43.89 | 101.79 | 0.00 | 0.00 | 0.00 |
May | 120.70 | 6.45 | 114.25 | 112.46 | 50.30 | 0.00 | 0.00 | 0.00 |
June | 134.92 | 15.08 | 119.83 | 151.66 | 33.42 | 0.00 | 0.00 | 0.00 |
July | 128.98 | 11.38 | 117.59 | 150.68 | 30.77 | 0.00 | 0.00 | 0.00 |
August | 97.90 | 1.88 | 96.02 | 104.05 | 37.30 | 0.00 | 0.00 | 0.00 |
September | 76.21 | 0.08 | 76.13 | 61.16 | 64.15 | 0.00 | 0.00 | 0.00 |
October | 52.83 | 0.00 | 52.83 | 21.44 | 104.91 | 0.00 | 0.00 | 0.00 |
November | 34.98 | 0.00 | 34.98 | 3.09 | 170.87 | 0.00 | 0.00 | 0.00 |
December | 29.32 | 0.00 | 29.32 | 0.00 | 279.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 76.37 | 2.99 | 73.38 | 55.68 | 130.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.32 | 0.00 | 29.32 | 0.00 | 30.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 134.92 | 15.08 | 119.83 | 151.66 | 291.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.97 | 0.00 | 30.97 | 0.20 | 260.94 | 0.00 | 0.00 | 0.00 |
February | 47.57 | 0.00 | 47.57 | 3.36 | 205.88 | 0.00 | 0.00 | 0.00 |
March | 58.53 | 0.00 | 58.53 | 10.62 | 156.24 | 0.00 | 0.00 | 0.00 |
April | 76.98 | 0.80 | 76.18 | 39.27 | 91.07 | 0.00 | 0.00 | 0.00 |
May | 107.99 | 5.77 | 102.22 | 100.62 | 45.00 | 0.00 | 0.00 | 0.00 |
June | 120.71 | 13.50 | 107.21 | 135.70 | 29.90 | 0.00 | 0.00 | 0.00 |
July | 115.40 | 10.19 | 105.21 | 134.81 | 27.53 | 0.00 | 0.00 | 0.00 |
August | 87.59 | 1.68 | 85.91 | 93.09 | 33.38 | 0.00 | 0.00 | 0.00 |
September | 68.19 | 0.07 | 68.12 | 54.72 | 57.39 | 0.00 | 0.00 | 0.00 |
October | 47.27 | 0.00 | 47.27 | 19.18 | 93.87 | 0.00 | 0.00 | 0.00 |
November | 31.30 | 0.00 | 31.30 | 2.77 | 152.87 | 0.00 | 0.00 | 0.00 |
December | 26.24 | 0.00 | 26.24 | 0.00 | 250.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 68.33 | 2.68 | 65.65 | 49.81 | 116.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.24 | 0.00 | 26.24 | 0.00 | 27.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.71 | 13.50 | 107.21 | 135.70 | 260.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 706.75 | 492.29 | 214.46 | 601.58 | 681.60 | 0.00 | 0.00 | 0.00 |
February | 882.93 | 593.89 | 289.04 | 840.87 | 567.38 | 0.00 | 0.00 | 0.00 |
March | 776.88 | 489.11 | 287.78 | 761.59 | 463.12 | 0.00 | 0.00 | 0.00 |
April | 710.14 | 385.41 | 324.73 | 756.42 | 300.86 | 0.00 | 0.00 | 0.00 |
May | 607.98 | 215.05 | 392.93 | 706.23 | 162.87 | 0.00 | 0.00 | 0.00 |
June | 534.25 | 141.32 | 392.93 | 659.29 | 107.25 | 0.00 | 0.00 | 0.00 |
July | 587.88 | 187.68 | 400.20 | 754.74 | 97.32 | 0.00 | 0.00 | 0.00 |
August | 623.62 | 259.72 | 363.91 | 777.78 | 113.96 | 0.00 | 0.00 | 0.00 |
September | 657.42 | 344.19 | 313.23 | 761.35 | 187.64 | 0.00 | 0.00 | 0.00 |
October | 583.98 | 348.09 | 235.90 | 603.66 | 289.93 | 0.00 | 0.00 | 0.00 |
November | 509.71 | 319.42 | 190.28 | 461.08 | 434.75 | 0.00 | 0.00 | 0.00 |
December | 542.82 | 355.92 | 186.90 | 425.91 | 663.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 642.18 | 342.80 | 299.38 | 674.70 | 338.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 509.71 | 141.32 | 186.90 | 425.91 | 97.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 882.93 | 593.89 | 400.20 | 840.87 | 681.60 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.256452E+10 | 0.178633E+10 | 0.778194E+09 | 0.221145E+10 | 0.230437E+10 |
February | 0.289374E+10 | 0.194644E+10 | 0.947301E+09 | 0.277527E+10 | 0.174745E+10 |
March | 0.281898E+10 | 0.177477E+10 | 0.104422E+10 | 0.276802E+10 | 0.158205E+10 |
April | 0.249369E+10 | 0.135338E+10 | 0.114031E+10 | 0.265803E+10 | 0.993119E+09 |
May | 0.220611E+10 | 0.780327E+09 | 0.142579E+10 | 0.258761E+10 | 0.534638E+09 |
June | 0.187603E+10 | 0.496257E+09 | 0.137978E+10 | 0.234981E+10 | 0.327984E+09 |
July | 0.213317E+10 | 0.681032E+09 | 0.145214E+10 | 0.276227E+10 | 0.310820E+09 |
August | 0.226287E+10 | 0.942414E+09 | 0.132045E+10 | 0.284124E+10 | 0.364560E+09 |
September | 0.230853E+10 | 0.120863E+10 | 0.109990E+10 | 0.268386E+10 | 0.598832E+09 |
October | 0.211902E+10 | 0.126306E+10 | 0.855962E+09 | 0.219469E+10 | 0.986753E+09 |
November | 0.178985E+10 | 0.112167E+10 | 0.668184E+09 | 0.163547E+10 | 0.141967E+10 |
December | 0.196967E+10 | 0.129147E+10 | 0.678197E+09 | 0.157589E+10 | 0.222847E+10 |
Annual Sum or Average | 0.274362E+11 | 0.146458E+11 | 0.127904E+11 | 0.290436E+11 | 0.133987E+11 |
Minimum of Months | 0.178985E+10 | 0.496257E+09 | 0.668184E+09 | 0.157589E+10 | 0.310820E+09 |
Maximum of Months | 0.289374E+10 | 0.194644E+10 | 0.145214E+10 | 0.284124E+10 | 0.230437E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.722152E+10 | 0.503018E+10 | 0.219134E+10 | 0.618336E+10 | 0.649002E+10 |
February | 0.814857E+10 | 0.548103E+10 | 0.266754E+10 | 0.776037E+10 | 0.495063E+10 |
March | 0.793806E+10 | 0.499762E+10 | 0.294044E+10 | 0.773451E+10 | 0.453001E+10 |
April | 0.702205E+10 | 0.381102E+10 | 0.321103E+10 | 0.741482E+10 | 0.290456E+10 |
May | 0.621227E+10 | 0.219735E+10 | 0.401492E+10 | 0.718888E+10 | 0.161782E+10 |
June | 0.528278E+10 | 0.139743E+10 | 0.388536E+10 | 0.651442E+10 | 0.101930E+10 |
July | 0.600687E+10 | 0.191774E+10 | 0.408912E+10 | 0.769212E+10 | 0.954077E+09 |
August | 0.637209E+10 | 0.265378E+10 | 0.371831E+10 | 0.791840E+10 | 0.113462E+10 |
September | 0.650068E+10 | 0.340342E+10 | 0.309726E+10 | 0.747952E+10 | 0.182534E+10 |
October | 0.596703E+10 | 0.355670E+10 | 0.241033E+10 | 0.612046E+10 | 0.290301E+10 |
November | 0.504011E+10 | 0.315855E+10 | 0.188156E+10 | 0.456156E+10 | 0.406172E+10 |
December | 0.554646E+10 | 0.363670E+10 | 0.190976E+10 | 0.440246E+10 | 0.627581E+10 |
Annual Sum or Average | 0.772585E+11 | 0.412415E+11 | 0.360170E+11 | 0.809709E+11 | 0.386669E+11 |
Minimum of Months | 0.504011E+10 | 0.139743E+10 | 0.188156E+10 | 0.440246E+10 | 0.954077E+09 |
Maximum of Months | 0.814857E+10 | 0.548103E+10 | 0.408912E+10 | 0.791840E+10 | 0.649002E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.938116E+10 | 0.653449E+10 | 0.284668E+10 | 0.812768E+10 | 0.871365E+10 |
February | 0.105855E+11 | 0.712017E+10 | 0.346528E+10 | 0.102306E+11 | 0.665662E+10 |
March | 0.103120E+11 | 0.649219E+10 | 0.381980E+10 | 0.101976E+11 | 0.612161E+10 |
April | 0.912205E+10 | 0.495073E+10 | 0.417132E+10 | 0.976248E+10 | 0.396860E+10 |
May | 0.807009E+10 | 0.285448E+10 | 0.521561E+10 | 0.945170E+10 | 0.221922E+10 |
June | 0.686263E+10 | 0.181534E+10 | 0.504730E+10 | 0.855713E+10 | 0.140906E+10 |
July | 0.780326E+10 | 0.249126E+10 | 0.531200E+10 | 0.101211E+11 | 0.129757E+10 |
August | 0.827770E+10 | 0.344741E+10 | 0.483030E+10 | 0.104065E+11 | 0.154854E+10 |
September | 0.844475E+10 | 0.442123E+10 | 0.402351E+10 | 0.981239E+10 | 0.251613E+10 |
October | 0.775151E+10 | 0.462035E+10 | 0.313116E+10 | 0.800822E+10 | 0.401376E+10 |
November | 0.654739E+10 | 0.410313E+10 | 0.244426E+10 | 0.597917E+10 | 0.558125E+10 |
December | 0.720517E+10 | 0.472428E+10 | 0.248089E+10 | 0.577312E+10 | 0.847238E+10 |
Annual Sum or Average | 0.100363E+12 | 0.535751E+11 | 0.467881E+11 | 0.106428E+12 | 0.525184E+11 |
Minimum of Months | 0.654739E+10 | 0.181534E+10 | 0.244426E+10 | 0.577312E+10 | 0.129757E+10 |
Maximum of Months | 0.105855E+11 | 0.712017E+10 | 0.531200E+10 | 0.104065E+11 | 0.871365E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.507050E+09 | 0.353187E+09 | 0.153863E+09 | 0.442050E+09 | 0.467413E+09 |
February | 0.572142E+09 | 0.384844E+09 | 0.187299E+09 | 0.552590E+09 | 0.352677E+09 |
March | 0.557363E+09 | 0.350902E+09 | 0.206461E+09 | 0.551772E+09 | 0.318853E+09 |
April | 0.493047E+09 | 0.267586E+09 | 0.225461E+09 | 0.527965E+09 | 0.199864E+09 |
May | 0.436189E+09 | 0.154284E+09 | 0.281905E+09 | 0.511257E+09 | 0.105243E+09 |
June | 0.370926E+09 | 98118509.68 | 0.272808E+09 | 0.466435E+09 | 62307749.15 |
July | 0.421767E+09 | 0.134652E+09 | 0.287115E+09 | 0.550780E+09 | 56052812.45 |
August | 0.447410E+09 | 0.186331E+09 | 0.261079E+09 | 0.565058E+09 | 66736730.92 |
September | 0.456438E+09 | 0.238967E+09 | 0.217472E+09 | 0.533247E+09 | 0.117356E+09 |
October | 0.418968E+09 | 0.249729E+09 | 0.169239E+09 | 0.438444E+09 | 0.194957E+09 |
November | 0.353885E+09 | 0.221773E+09 | 0.132112E+09 | 0.327088E+09 | 0.284183E+09 |
December | 0.389438E+09 | 0.255346E+09 | 0.134092E+09 | 0.314840E+09 | 0.451888E+09 |
Annual Sum or Average | 0.542462E+10 | 0.289572E+10 | 0.252891E+10 | 0.578153E+10 | 0.267753E+10 |
Minimum of Months | 0.353885E+09 | 98118509.68 | 0.132112E+09 | 0.314840E+09 | 56052812.45 |
Maximum of Months | 0.572142E+09 | 0.384844E+09 | 0.287115E+09 | 0.565058E+09 | 0.467413E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.307231E+09 | 0.130149E+09 | 0.177082E+09 | 0.138815E+09 | 0.100056E+10 |
February | 0.448761E+09 | 0.206014E+09 | 0.242747E+09 | 0.300372E+09 | 0.725190E+09 |
March | 0.651502E+09 | 0.334092E+09 | 0.317410E+09 | 0.527854E+09 | 0.622214E+09 |
April | 0.804500E+09 | 0.407943E+09 | 0.396557E+09 | 0.780649E+09 | 0.365744E+09 |
May | 0.102228E+10 | 0.488871E+09 | 0.533405E+09 | 0.116789E+10 | 0.191092E+09 |
June | 0.950654E+09 | 0.410413E+09 | 0.540241E+09 | 0.115747E+10 | 0.114337E+09 |
July | 0.105023E+10 | 0.488269E+09 | 0.561960E+09 | 0.131574E+10 | 0.103528E+09 |
August | 0.862115E+09 | 0.390544E+09 | 0.471571E+09 | 0.104771E+10 | 0.123602E+09 |
September | 0.654928E+09 | 0.293903E+09 | 0.361025E+09 | 0.711290E+09 | 0.217569E+09 |
October | 0.428161E+09 | 0.172305E+09 | 0.255855E+09 | 0.368620E+09 | 0.375586E+09 |
November | 0.252239E+09 | 85826290.04 | 0.166413E+09 | 0.137306E+09 | 0.576871E+09 |
December | 0.229790E+09 | 79717529.27 | 0.150073E+09 | 77597753.60 | 0.966251E+09 |
Annual Sum or Average | 0.766239E+10 | 0.348805E+10 | 0.417434E+10 | 0.773132E+10 | 0.538254E+10 |
Minimum of Months | 0.229790E+09 | 79717529.27 | 0.150073E+09 | 77597753.60 | 0.103528E+09 |
Maximum of Months | 0.105023E+10 | 0.488871E+09 | 0.561960E+09 | 0.131574E+10 | 0.100056E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73196226.91 | 0.00 | 73196226.91 | 1193892.35 | 0.577976E+09 |
February | 0.101554E+09 | 0.00 | 0.101554E+09 | 10923043.39 | 0.411148E+09 |
March | 0.138364E+09 | 5398.29 | 0.138358E+09 | 31582732.75 | 0.347586E+09 |
April | 0.176094E+09 | 1829975.10 | 0.174264E+09 | 96330823.81 | 0.196750E+09 |
May | 0.255266E+09 | 13638445.42 | 0.241628E+09 | 0.244715E+09 | 95204246.39 |
June | 0.276133E+09 | 30872694.36 | 0.245260E+09 | 0.320310E+09 | 57626556.15 |
July | 0.272775E+09 | 24077951.73 | 0.248697E+09 | 0.329446E+09 | 52402142.39 |
August | 0.207056E+09 | 3976857.93 | 0.203080E+09 | 0.228876E+09 | 63933697.44 |
September | 0.155985E+09 | 163465.80 | 0.155821E+09 | 0.132315E+09 | 0.117024E+09 |
October | 0.111735E+09 | 0.00 | 0.111735E+09 | 53364490.15 | 0.204649E+09 |
November | 71596193.86 | 0.00 | 71596193.86 | 9200587.94 | 0.321720E+09 |
December | 62017652.81 | 0.00 | 62017652.81 | 93653.41 | 0.552984E+09 |
Annual Sum or Average | 0.190177E+10 | 74564788.63 | 0.182721E+10 | 0.145835E+10 | 0.299900E+10 |
Minimum of Months | 62017652.81 | 0.00 | 62017652.81 | 93653.41 | 52402142.39 |
Maximum of Months | 0.276133E+09 | 30872694.36 | 0.248697E+09 | 0.329446E+09 | 0.577976E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.307231E+09 | 0.130149E+09 | 0.177082E+09 | 0.142919E+09 | 0.996160E+09 |
February | 0.448761E+09 | 0.206014E+09 | 0.242747E+09 | 0.310088E+09 | 0.718874E+09 |
March | 0.651502E+09 | 0.334092E+09 | 0.317410E+09 | 0.539474E+09 | 0.615455E+09 |
April | 0.804500E+09 | 0.407943E+09 | 0.396557E+09 | 0.792264E+09 | 0.362147E+09 |
May | 0.102228E+10 | 0.488871E+09 | 0.533405E+09 | 0.117365E+10 | 0.189736E+09 |
June | 0.950654E+09 | 0.410413E+09 | 0.540241E+09 | 0.116037E+10 | 0.113582E+09 |
July | 0.105023E+10 | 0.488269E+09 | 0.561960E+09 | 0.131949E+10 | 0.102518E+09 |
August | 0.862115E+09 | 0.390544E+09 | 0.471571E+09 | 0.105349E+10 | 0.122030E+09 |
September | 0.654928E+09 | 0.293903E+09 | 0.361025E+09 | 0.719579E+09 | 0.215012E+09 |
October | 0.428161E+09 | 0.172305E+09 | 0.255855E+09 | 0.377086E+09 | 0.371425E+09 |
November | 0.252239E+09 | 85826290.04 | 0.166413E+09 | 0.143505E+09 | 0.572293E+09 |
December | 0.229790E+09 | 79717529.27 | 0.150073E+09 | 80138560.75 | 0.962978E+09 |
Annual Sum or Average | 0.766239E+10 | 0.348805E+10 | 0.417434E+10 | 0.781204E+10 | 0.534221E+10 |
Minimum of Months | 0.229790E+09 | 79717529.27 | 0.150073E+09 | 80138560.75 | 0.102518E+09 |
Maximum of Months | 0.105023E+10 | 0.488871E+09 | 0.561960E+09 | 0.131949E+10 | 0.996160E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.405560E+09 | 0.282494E+09 | 0.123066E+09 | 0.351798E+09 | 0.366391E+09 |
February | 0.457623E+09 | 0.307814E+09 | 0.149809E+09 | 0.439444E+09 | 0.280149E+09 |
March | 0.445801E+09 | 0.280665E+09 | 0.165136E+09 | 0.438957E+09 | 0.255765E+09 |
April | 0.394359E+09 | 0.214026E+09 | 0.180333E+09 | 0.418572E+09 | 0.167342E+09 |
May | 0.348882E+09 | 0.123403E+09 | 0.225479E+09 | 0.404959E+09 | 94374927.08 |
June | 0.296682E+09 | 78479200.34 | 0.218203E+09 | 0.368532E+09 | 58663808.25 |
July | 0.337347E+09 | 0.107700E+09 | 0.229647E+09 | 0.437147E+09 | 53769622.91 |
August | 0.357857E+09 | 0.149035E+09 | 0.208822E+09 | 0.447770E+09 | 64710544.47 |
September | 0.365078E+09 | 0.191135E+09 | 0.173943E+09 | 0.421039E+09 | 0.106702E+09 |
October | 0.335108E+09 | 0.199743E+09 | 0.135365E+09 | 0.346925E+09 | 0.163394E+09 |
November | 0.283052E+09 | 0.177383E+09 | 0.105669E+09 | 0.260437E+09 | 0.223658E+09 |
December | 0.311488E+09 | 0.204236E+09 | 0.107252E+09 | 0.250987E+09 | 0.352475E+09 |
Annual Sum or Average | 0.433884E+10 | 0.231611E+10 | 0.202272E+10 | 0.458657E+10 | 0.218740E+10 |
Minimum of Months | 0.283052E+09 | 78479200.34 | 0.105669E+09 | 0.250987E+09 | 53769622.91 |
Maximum of Months | 0.457623E+09 | 0.307814E+09 | 0.229647E+09 | 0.447770E+09 | 0.366391E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58564743.59 | 0.00 | 58564743.59 | 692581.66 | 0.476126E+09 |
February | 81254233.52 | 0.00 | 81254233.52 | 7834002.75 | 0.337299E+09 |
March | 0.110706E+09 | 4319.21 | 0.110701E+09 | 24613625.56 | 0.282752E+09 |
April | 0.140894E+09 | 1464174.14 | 0.139430E+09 | 79869616.54 | 0.157868E+09 |
May | 0.204240E+09 | 10912202.62 | 0.193328E+09 | 0.205195E+09 | 74045373.00 |
June | 0.220936E+09 | 24701429.37 | 0.196234E+09 | 0.265928E+09 | 43958305.00 |
July | 0.218249E+09 | 19264914.72 | 0.198984E+09 | 0.275073E+09 | 38703187.63 |
August | 0.165667E+09 | 3181908.07 | 0.162485E+09 | 0.192599E+09 | 48063178.49 |
September | 0.124804E+09 | 130789.97 | 0.124674E+09 | 0.110684E+09 | 91878062.81 |
October | 89399861.49 | 0.00 | 89399861.49 | 41922995.65 | 0.167166E+09 |
November | 57284547.47 | 0.00 | 57284547.47 | 6321327.17 | 0.266964E+09 |
December | 49620698.88 | 0.00 | 49620698.88 | 17346.61 | 0.456025E+09 |
Annual Sum or Average | 0.152162E+10 | 59659738.10 | 0.146196E+10 | 0.121075E+10 | 0.244085E+10 |
Minimum of Months | 49620698.88 | 0.00 | 49620698.88 | 17346.61 | 38703187.63 |
Maximum of Months | 0.220936E+09 | 24701429.37 | 0.198984E+09 | 0.275073E+09 | 0.476126E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.299000E+09 | 0.124099E+09 | 0.174901E+09 | 0.119771E+09 | 0.987001E+09 |
February | 0.428982E+09 | 0.184569E+09 | 0.244413E+09 | 0.257802E+09 | 0.700794E+09 |
March | 0.645207E+09 | 0.324279E+09 | 0.320927E+09 | 0.498755E+09 | 0.601529E+09 |
April | 0.859773E+09 | 0.463340E+09 | 0.396434E+09 | 0.837322E+09 | 0.351530E+09 |
May | 0.964998E+09 | 0.425408E+09 | 0.539590E+09 | 0.108431E+10 | 0.179114E+09 |
June | 0.105373E+10 | 0.503777E+09 | 0.549953E+09 | 0.128510E+10 | 0.109375E+09 |
July | 0.106889E+10 | 0.502619E+09 | 0.566270E+09 | 0.133334E+10 | 97978719.42 |
August | 0.822805E+09 | 0.359411E+09 | 0.463394E+09 | 0.990445E+09 | 0.119345E+09 |
September | 0.639440E+09 | 0.286824E+09 | 0.352616E+09 | 0.685825E+09 | 0.210931E+09 |
October | 0.397946E+09 | 0.149645E+09 | 0.248301E+09 | 0.321624E+09 | 0.366337E+09 |
November | 0.246803E+09 | 82278208.38 | 0.164525E+09 | 0.122824E+09 | 0.565881E+09 |
December | 0.234521E+09 | 88133196.08 | 0.146388E+09 | 75693410.79 | 0.955724E+09 |
Annual Sum or Average | 0.766209E+10 | 0.349438E+10 | 0.416771E+10 | 0.761280E+10 | 0.524554E+10 |
Minimum of Months | 0.234521E+09 | 82278208.38 | 0.146388E+09 | 75693410.79 | 97978719.42 |
Maximum of Months | 0.106889E+10 | 0.503777E+09 | 0.566270E+09 | 0.133334E+10 | 0.987001E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.507050E+09 | 0.353187E+09 | 0.153863E+09 | 0.441634E+09 | 0.467008E+09 |
February | 0.572142E+09 | 0.384844E+09 | 0.187299E+09 | 0.551880E+09 | 0.351881E+09 |
March | 0.557363E+09 | 0.350902E+09 | 0.206461E+09 | 0.549063E+09 | 0.317629E+09 |
April | 0.493047E+09 | 0.267586E+09 | 0.225461E+09 | 0.524189E+09 | 0.198918E+09 |
May | 0.436189E+09 | 0.154284E+09 | 0.281905E+09 | 0.509764E+09 | 0.103999E+09 |
June | 0.370926E+09 | 98118509.68 | 0.272808E+09 | 0.463210E+09 | 61507605.22 |
July | 0.421767E+09 | 0.134652E+09 | 0.287115E+09 | 0.548942E+09 | 54772278.68 |
August | 0.447410E+09 | 0.186331E+09 | 0.261079E+09 | 0.564103E+09 | 65784923.25 |
September | 0.456438E+09 | 0.238967E+09 | 0.217472E+09 | 0.531990E+09 | 0.116213E+09 |
October | 0.418968E+09 | 0.249729E+09 | 0.169239E+09 | 0.437822E+09 | 0.194039E+09 |
November | 0.353885E+09 | 0.221773E+09 | 0.132112E+09 | 0.326826E+09 | 0.283772E+09 |
December | 0.389438E+09 | 0.255346E+09 | 0.134092E+09 | 0.314428E+09 | 0.451629E+09 |
Annual Sum or Average | 0.542462E+10 | 0.289572E+10 | 0.252891E+10 | 0.576385E+10 | 0.266715E+10 |
Minimum of Months | 0.353885E+09 | 98118509.68 | 0.132112E+09 | 0.314428E+09 | 54772278.68 |
Maximum of Months | 0.572142E+09 | 0.384844E+09 | 0.287115E+09 | 0.564103E+09 | 0.467008E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73196226.91 | 0.00 | 73196226.91 | 1172199.80 | 0.577999E+09 |
February | 0.101554E+09 | 0.00 | 0.101554E+09 | 10480101.02 | 0.410741E+09 |
March | 0.138364E+09 | 5398.29 | 0.138358E+09 | 29930574.14 | 0.346989E+09 |
April | 0.176094E+09 | 1829975.10 | 0.174264E+09 | 92455711.86 | 0.196823E+09 |
May | 0.255266E+09 | 13638445.42 | 0.241628E+09 | 0.242994E+09 | 94342523.01 |
June | 0.276133E+09 | 30872694.36 | 0.245260E+09 | 0.317020E+09 | 57090598.20 |
July | 0.272775E+09 | 24077951.73 | 0.248697E+09 | 0.327682E+09 | 51428431.37 |
August | 0.207056E+09 | 3976857.93 | 0.203080E+09 | 0.227605E+09 | 63028685.11 |
September | 0.155985E+09 | 163465.80 | 0.155821E+09 | 0.130403E+09 | 0.116047E+09 |
October | 0.111735E+09 | 0.00 | 0.111735E+09 | 52309888.79 | 0.203497E+09 |
November | 71596193.86 | 0.00 | 71596193.86 | 8944012.56 | 0.321571E+09 |
December | 62017652.81 | 0.00 | 62017652.81 | 89280.17 | 0.552792E+09 |
Annual Sum or Average | 0.190177E+10 | 74564788.63 | 0.182721E+10 | 0.144109E+10 | 0.299235E+10 |
Minimum of Months | 62017652.81 | 0.00 | 62017652.81 | 89280.17 | 51428431.37 |
Maximum of Months | 0.276133E+09 | 30872694.36 | 0.248697E+09 | 0.327682E+09 | 0.577999E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.299000E+09 | 0.124099E+09 | 0.174901E+09 | 0.122237E+09 | 0.981005E+09 |
February | 0.428982E+09 | 0.184569E+09 | 0.244413E+09 | 0.264833E+09 | 0.691696E+09 |
March | 0.645207E+09 | 0.324279E+09 | 0.320927E+09 | 0.509098E+09 | 0.592540E+09 |
April | 0.859773E+09 | 0.463340E+09 | 0.396434E+09 | 0.846893E+09 | 0.347575E+09 |
May | 0.964998E+09 | 0.425408E+09 | 0.539590E+09 | 0.108929E+10 | 0.177769E+09 |
June | 0.105373E+10 | 0.503777E+09 | 0.549953E+09 | 0.128787E+10 | 0.108779E+09 |
July | 0.106889E+10 | 0.502619E+09 | 0.566270E+09 | 0.133709E+10 | 97097624.69 |
August | 0.822805E+09 | 0.359411E+09 | 0.463394E+09 | 0.995775E+09 | 0.117780E+09 |
September | 0.639440E+09 | 0.286824E+09 | 0.352616E+09 | 0.692805E+09 | 0.208222E+09 |
October | 0.397946E+09 | 0.149645E+09 | 0.248301E+09 | 0.329351E+09 | 0.361518E+09 |
November | 0.246803E+09 | 82278208.38 | 0.164525E+09 | 0.126523E+09 | 0.559137E+09 |
December | 0.234521E+09 | 88133196.08 | 0.146388E+09 | 77120944.17 | 0.951046E+09 |
Annual Sum or Average | 0.766209E+10 | 0.349438E+10 | 0.416771E+10 | 0.767889E+10 | 0.519416E+10 |
Minimum of Months | 0.234521E+09 | 82278208.38 | 0.146388E+09 | 77120944.17 | 97097624.69 |
Maximum of Months | 0.106889E+10 | 0.503777E+09 | 0.566270E+09 | 0.133709E+10 | 0.981005E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92698402.95 | 0.00 | 92698402.95 | 740625.74 | 0.776328E+09 |
February | 0.128612E+09 | 0.00 | 0.128612E+09 | 10126089.25 | 0.551176E+09 |
March | 0.175229E+09 | 6836.60 | 0.175222E+09 | 34712697.91 | 0.462380E+09 |
April | 0.223012E+09 | 2317548.00 | 0.220694E+09 | 0.118542E+09 | 0.262952E+09 |
May | 0.323279E+09 | 17272230.58 | 0.306006E+09 | 0.308669E+09 | 0.133807E+09 |
June | 0.349705E+09 | 39098319.45 | 0.310607E+09 | 0.401251E+09 | 85176529.89 |
July | 0.345452E+09 | 30493206.63 | 0.314959E+09 | 0.410941E+09 | 81159158.94 |
August | 0.262224E+09 | 5036439.64 | 0.257187E+09 | 0.285478E+09 | 98222202.04 |
September | 0.197545E+09 | 207019.12 | 0.197338E+09 | 0.163004E+09 | 0.166242E+09 |
October | 0.141505E+09 | 0.00 | 0.141505E+09 | 61205356.44 | 0.278197E+09 |
November | 90672062.05 | 0.00 | 90672062.05 | 8868234.05 | 0.436268E+09 |
December | 78541444.19 | 0.00 | 78541444.19 | 2362.59 | 0.743567E+09 |
Annual Sum or Average | 0.240847E+10 | 94431600.03 | 0.231404E+10 | 0.180354E+10 | 0.407547E+10 |
Minimum of Months | 78541444.19 | 0.00 | 78541444.19 | 2362.59 | 81159158.94 |
Maximum of Months | 0.349705E+09 | 39098319.45 | 0.314959E+09 | 0.410941E+09 | 0.776328E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34172469.67 | 0.00 | 34172469.67 | 273025.32 | 0.286187E+09 |
February | 47411764.49 | 0.00 | 47411764.49 | 3732895.79 | 0.203186E+09 |
March | 64596683.78 | 2520.25 | 64594163.53 | 12796537.79 | 0.170452E+09 |
April | 82211369.81 | 854344.16 | 81357025.66 | 43699654.77 | 96934972.73 |
May | 0.119174E+09 | 6367259.38 | 0.112807E+09 | 0.113788E+09 | 49326656.39 |
June | 0.128916E+09 | 14413259.48 | 0.114502E+09 | 0.147918E+09 | 31399595.80 |
July | 0.127348E+09 | 11241058.59 | 0.116107E+09 | 0.151490E+09 | 29918626.52 |
August | 96666571.17 | 1856640.19 | 94809930.98 | 0.105239E+09 | 36208770.73 |
September | 72823244.90 | 76315.82 | 72746929.08 | 60089856.69 | 61283529.69 |
October | 52164730.31 | 0.00 | 52164730.31 | 22562828.70 | 0.102555E+09 |
November | 33425476.51 | 0.00 | 33425476.51 | 3269198.28 | 0.160827E+09 |
December | 28953628.47 | 0.00 | 28953628.47 | 870.95 | 0.274110E+09 |
Annual Sum or Average | 0.887864E+09 | 34811397.87 | 0.853052E+09 | 0.664859E+09 | 0.150239E+10 |
Minimum of Months | 28953628.47 | 0.00 | 28953628.47 | 870.95 | 29918626.52 |
Maximum of Months | 0.128916E+09 | 14413259.48 | 0.116107E+09 | 0.151490E+09 | 0.286187E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.236588E+09 | 0.164796E+09 | 71791813.57 | 0.202964E+09 | 0.226984E+09 |
February | 0.266959E+09 | 0.179566E+09 | 87392835.18 | 0.256631E+09 | 0.170445E+09 |
March | 0.260063E+09 | 0.163729E+09 | 96333865.29 | 0.257403E+09 | 0.153726E+09 |
April | 0.230054E+09 | 0.124855E+09 | 0.105199E+09 | 0.247524E+09 | 97155535.31 |
May | 0.203524E+09 | 71988297.24 | 0.131536E+09 | 0.239551E+09 | 54098122.18 |
June | 0.173073E+09 | 45781701.23 | 0.127291E+09 | 0.216852E+09 | 34091859.90 |
July | 0.196795E+09 | 62827971.53 | 0.133967E+09 | 0.255782E+09 | 32063882.48 |
August | 0.208760E+09 | 86941480.81 | 0.121818E+09 | 0.263498E+09 | 37407325.48 |
September | 0.212972E+09 | 0.111501E+09 | 0.101471E+09 | 0.248972E+09 | 60650103.92 |
October | 0.195489E+09 | 0.116523E+09 | 78966456.61 | 0.204304E+09 | 96116313.69 |
November | 0.165121E+09 | 0.103479E+09 | 61642963.96 | 0.151168E+09 | 0.139028E+09 |
December | 0.181710E+09 | 0.119144E+09 | 62566686.01 | 0.143878E+09 | 0.220598E+09 |
Annual Sum or Average | 0.253111E+10 | 0.135113E+10 | 0.117998E+10 | 0.268853E+10 | 0.132236E+10 |
Minimum of Months | 0.165121E+09 | 45781701.23 | 61642963.96 | 0.143878E+09 | 32063882.48 |
Maximum of Months | 0.266959E+09 | 0.179566E+09 | 0.133967E+09 | 0.263498E+09 | 0.226984E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.642147E+09 | 0.447290E+09 | 0.194858E+09 | 0.550886E+09 | 0.616080E+09 |
February | 0.724582E+09 | 0.487380E+09 | 0.237202E+09 | 0.696548E+09 | 0.462624E+09 |
March | 0.705864E+09 | 0.444395E+09 | 0.261470E+09 | 0.698643E+09 | 0.417245E+09 |
April | 0.624412E+09 | 0.338881E+09 | 0.285532E+09 | 0.671830E+09 | 0.263700E+09 |
May | 0.552406E+09 | 0.195391E+09 | 0.357015E+09 | 0.650191E+09 | 0.146833E+09 |
June | 0.469755E+09 | 0.124261E+09 | 0.345494E+09 | 0.588580E+09 | 92532281.11 |
July | 0.534142E+09 | 0.170528E+09 | 0.363614E+09 | 0.694246E+09 | 87027935.57 |
August | 0.566617E+09 | 0.235977E+09 | 0.330640E+09 | 0.715189E+09 | 0.101531E+09 |
September | 0.578050E+09 | 0.302636E+09 | 0.275414E+09 | 0.675762E+09 | 0.164617E+09 |
October | 0.530597E+09 | 0.316266E+09 | 0.214331E+09 | 0.554524E+09 | 0.260879E+09 |
November | 0.448173E+09 | 0.280862E+09 | 0.167312E+09 | 0.410300E+09 | 0.377350E+09 |
December | 0.493199E+09 | 0.323380E+09 | 0.169819E+09 | 0.390515E+09 | 0.598748E+09 |
Annual Sum or Average | 0.686994E+10 | 0.366725E+10 | 0.320270E+10 | 0.729721E+10 | 0.358917E+10 |
Minimum of Months | 0.448173E+09 | 0.124261E+09 | 0.167312E+09 | 0.390515E+09 | 87027935.57 |
Maximum of Months | 0.724582E+09 | 0.487380E+09 | 0.363614E+09 | 0.715189E+09 | 0.616080E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.507050E+09 | 0.353187E+09 | 0.153863E+09 | 0.441468E+09 | 0.467026E+09 |
February | 0.572142E+09 | 0.384844E+09 | 0.187299E+09 | 0.551526E+09 | 0.351829E+09 |
March | 0.557363E+09 | 0.350902E+09 | 0.206461E+09 | 0.551132E+09 | 0.317700E+09 |
April | 0.493047E+09 | 0.267586E+09 | 0.225461E+09 | 0.526972E+09 | 0.198453E+09 |
May | 0.436189E+09 | 0.154284E+09 | 0.281905E+09 | 0.509323E+09 | 0.104142E+09 |
June | 0.370926E+09 | 98118509.68 | 0.272808E+09 | 0.464825E+09 | 61209021.64 |
July | 0.421767E+09 | 0.134652E+09 | 0.287115E+09 | 0.548931E+09 | 54906440.04 |
August | 0.447410E+09 | 0.186331E+09 | 0.261079E+09 | 0.563231E+09 | 65445124.14 |
September | 0.456438E+09 | 0.238967E+09 | 0.217472E+09 | 0.532134E+09 | 0.115748E+09 |
October | 0.418968E+09 | 0.249729E+09 | 0.169239E+09 | 0.438517E+09 | 0.192779E+09 |
November | 0.353885E+09 | 0.221773E+09 | 0.132112E+09 | 0.327031E+09 | 0.282554E+09 |
December | 0.389438E+09 | 0.255346E+09 | 0.134092E+09 | 0.314278E+09 | 0.451664E+09 |
Annual Sum or Average | 0.542462E+10 | 0.289572E+10 | 0.252891E+10 | 0.576937E+10 | 0.266345E+10 |
Minimum of Months | 0.353885E+09 | 98118509.68 | 0.132112E+09 | 0.314278E+09 | 54906440.04 |
Maximum of Months | 0.572142E+09 | 0.384844E+09 | 0.287115E+09 | 0.563231E+09 | 0.467026E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.307231E+09 | 0.130149E+09 | 0.177082E+09 | 0.138551E+09 | 0.100006E+10 |
February | 0.448761E+09 | 0.206014E+09 | 0.242747E+09 | 0.299888E+09 | 0.723829E+09 |
March | 0.651502E+09 | 0.334092E+09 | 0.317410E+09 | 0.526969E+09 | 0.619844E+09 |
April | 0.804500E+09 | 0.407943E+09 | 0.396557E+09 | 0.778696E+09 | 0.362897E+09 |
May | 0.102228E+10 | 0.488871E+09 | 0.533405E+09 | 0.116406E+10 | 0.188862E+09 |
June | 0.950654E+09 | 0.410413E+09 | 0.540241E+09 | 0.115404E+10 | 0.112224E+09 |
July | 0.105023E+10 | 0.488269E+09 | 0.561960E+09 | 0.131166E+10 | 0.101306E+09 |
August | 0.862115E+09 | 0.390544E+09 | 0.471571E+09 | 0.104467E+10 | 0.121112E+09 |
September | 0.654928E+09 | 0.293903E+09 | 0.361025E+09 | 0.709968E+09 | 0.214289E+09 |
October | 0.428161E+09 | 0.172305E+09 | 0.255855E+09 | 0.369270E+09 | 0.371130E+09 |
November | 0.252239E+09 | 85826290.04 | 0.166413E+09 | 0.138033E+09 | 0.573658E+09 |
December | 0.229790E+09 | 79717529.27 | 0.150073E+09 | 77411254.85 | 0.966547E+09 |
Annual Sum or Average | 0.766239E+10 | 0.348805E+10 | 0.417434E+10 | 0.771321E+10 | 0.535575E+10 |
Minimum of Months | 0.229790E+09 | 79717529.27 | 0.150073E+09 | 77411254.85 | 0.101306E+09 |
Maximum of Months | 0.105023E+10 | 0.488871E+09 | 0.561960E+09 | 0.131166E+10 | 0.100006E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73196226.91 | 0.00 | 73196226.91 | 1201737.03 | 0.577344E+09 |
February | 0.101554E+09 | 0.00 | 0.101554E+09 | 11173729.78 | 0.410269E+09 |
March | 0.138364E+09 | 5398.29 | 0.138358E+09 | 31941344.23 | 0.346514E+09 |
April | 0.176094E+09 | 1829975.10 | 0.174264E+09 | 97069289.96 | 0.195254E+09 |
May | 0.255266E+09 | 13638445.42 | 0.241628E+09 | 0.243944E+09 | 94155816.66 |
June | 0.276133E+09 | 30872694.36 | 0.245260E+09 | 0.319503E+09 | 56651919.17 |
July | 0.272775E+09 | 24077951.73 | 0.248697E+09 | 0.328676E+09 | 51377986.16 |
August | 0.207056E+09 | 3976857.93 | 0.203080E+09 | 0.228696E+09 | 62592126.13 |
September | 0.155985E+09 | 163465.80 | 0.155821E+09 | 0.133194E+09 | 0.115047E+09 |
October | 0.111735E+09 | 0.00 | 0.111735E+09 | 54744477.05 | 0.201888E+09 |
November | 71596193.86 | 0.00 | 71596193.86 | 9607380.97 | 0.319586E+09 |
December | 62017652.81 | 0.00 | 62017652.81 | 96394.21 | 0.552685E+09 |
Annual Sum or Average | 0.190177E+10 | 74564788.63 | 0.182721E+10 | 0.145985E+10 | 0.298336E+10 |
Minimum of Months | 62017652.81 | 0.00 | 62017652.81 | 96394.21 | 51377986.16 |
Maximum of Months | 0.276133E+09 | 30872694.36 | 0.248697E+09 | 0.328676E+09 | 0.577344E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.307231E+09 | 0.130149E+09 | 0.177082E+09 | 0.142499E+09 | 0.996000E+09 |
February | 0.448761E+09 | 0.206014E+09 | 0.242747E+09 | 0.309359E+09 | 0.717826E+09 |
March | 0.651502E+09 | 0.334092E+09 | 0.317410E+09 | 0.538765E+09 | 0.613244E+09 |
April | 0.804500E+09 | 0.407943E+09 | 0.396557E+09 | 0.791295E+09 | 0.359010E+09 |
May | 0.102228E+10 | 0.488871E+09 | 0.533405E+09 | 0.117027E+10 | 0.187357E+09 |
June | 0.950654E+09 | 0.410413E+09 | 0.540241E+09 | 0.115710E+10 | 0.111445E+09 |
July | 0.105023E+10 | 0.488269E+09 | 0.561960E+09 | 0.131564E+10 | 0.100253E+09 |
August | 0.862115E+09 | 0.390544E+09 | 0.471571E+09 | 0.105089E+10 | 0.119376E+09 |
September | 0.654928E+09 | 0.293903E+09 | 0.361025E+09 | 0.719365E+09 | 0.211248E+09 |
October | 0.428161E+09 | 0.172305E+09 | 0.255855E+09 | 0.378720E+09 | 0.366418E+09 |
November | 0.252239E+09 | 85826290.04 | 0.166413E+09 | 0.144258E+09 | 0.569369E+09 |
December | 0.229790E+09 | 79717529.27 | 0.150073E+09 | 79890397.76 | 0.963476E+09 |
Annual Sum or Average | 0.766239E+10 | 0.348805E+10 | 0.417434E+10 | 0.779805E+10 | 0.531502E+10 |
Minimum of Months | 0.229790E+09 | 79717529.27 | 0.150073E+09 | 79890397.76 | 0.100253E+09 |
Maximum of Months | 0.105023E+10 | 0.488871E+09 | 0.561960E+09 | 0.131564E+10 | 0.996000E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.743638E+09 | 0.517983E+09 | 0.225655E+09 | 0.629557E+09 | 0.700606E+09 |
February | 0.839102E+09 | 0.564410E+09 | 0.274692E+09 | 0.790476E+09 | 0.529534E+09 |
March | 0.817426E+09 | 0.514631E+09 | 0.302795E+09 | 0.793723E+09 | 0.476518E+09 |
April | 0.723100E+09 | 0.392440E+09 | 0.330660E+09 | 0.764882E+09 | 0.294353E+09 |
May | 0.639713E+09 | 0.226272E+09 | 0.413441E+09 | 0.749360E+09 | 0.150672E+09 |
June | 0.543999E+09 | 0.143900E+09 | 0.400099E+09 | 0.686492E+09 | 87914792.66 |
July | 0.618562E+09 | 0.197480E+09 | 0.421082E+09 | 0.811098E+09 | 77638123.01 |
August | 0.656170E+09 | 0.273273E+09 | 0.382897E+09 | 0.828160E+09 | 94467035.72 |
September | 0.669410E+09 | 0.350467E+09 | 0.318943E+09 | 0.776324E+09 | 0.171098E+09 |
October | 0.614457E+09 | 0.366251E+09 | 0.248206E+09 | 0.633683E+09 | 0.290379E+09 |
November | 0.519007E+09 | 0.325252E+09 | 0.193755E+09 | 0.467231E+09 | 0.426881E+09 |
December | 0.571148E+09 | 0.374490E+09 | 0.196658E+09 | 0.447269E+09 | 0.677423E+09 |
Annual Sum or Average | 0.795573E+10 | 0.424685E+10 | 0.370888E+10 | 0.837825E+10 | 0.397749E+10 |
Minimum of Months | 0.519007E+09 | 0.143900E+09 | 0.193755E+09 | 0.447269E+09 | 77638123.01 |
Maximum of Months | 0.839102E+09 | 0.564410E+09 | 0.421082E+09 | 0.828160E+09 | 0.700606E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.512354E+09 | 0.00 | 0.512354E+09 | 2540827.65 | 0.433814E+10 |
February | 0.710853E+09 | 0.00 | 0.710853E+09 | 46093679.20 | 0.314770E+10 |
March | 0.968510E+09 | 37786.62 | 0.968472E+09 | 0.162694E+09 | 0.270336E+10 |
April | 0.123261E+10 | 12809340.58 | 0.121980E+10 | 0.590517E+09 | 0.156258E+10 |
May | 0.178680E+10 | 95465502.22 | 0.169133E+10 | 0.164101E+10 | 0.763590E+09 |
June | 0.193286E+10 | 0.216101E+09 | 0.171676E+10 | 0.216896E+10 | 0.481151E+09 |
July | 0.190935E+10 | 0.168539E+09 | 0.174081E+10 | 0.225403E+10 | 0.438033E+09 |
August | 0.144934E+10 | 27836951.19 | 0.142150E+10 | 0.154463E+10 | 0.546704E+09 |
September | 0.109185E+10 | 1144217.24 | 0.109071E+10 | 0.854507E+09 | 0.960260E+09 |
October | 0.782115E+09 | 0.00 | 0.782115E+09 | 0.289870E+09 | 0.167397E+10 |
November | 0.501154E+09 | 0.00 | 0.501154E+09 | 35178575.34 | 0.259922E+10 |
December | 0.434107E+09 | 0.00 | 0.434107E+09 | 0.00 | 0.419283E+10 |
Annual Sum or Average | 0.133119E+11 | 0.521934E+09 | 0.127900E+11 | 0.959003E+10 | 0.234075E+11 |
Minimum of Months | 0.434107E+09 | 0.00 | 0.434107E+09 | 0.00 | 0.438033E+09 |
Maximum of Months | 0.193286E+10 | 0.216101E+09 | 0.174081E+10 | 0.225403E+10 | 0.433814E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.512354E+09 | 0.00 | 0.512354E+09 | 1799588.04 | 0.440562E+10 |
February | 0.710853E+09 | 0.00 | 0.710853E+09 | 40537379.05 | 0.321036E+10 |
March | 0.968510E+09 | 37786.62 | 0.968472E+09 | 0.149840E+09 | 0.276227E+10 |
April | 0.123261E+10 | 12809340.58 | 0.121980E+10 | 0.567017E+09 | 0.159604E+10 |
May | 0.178680E+10 | 95465502.22 | 0.169133E+10 | 0.161768E+10 | 0.778479E+09 |
June | 0.193286E+10 | 0.216101E+09 | 0.171676E+10 | 0.214851E+10 | 0.492184E+09 |
July | 0.190935E+10 | 0.168539E+09 | 0.174081E+10 | 0.223611E+10 | 0.448171E+09 |
August | 0.144934E+10 | 27836951.19 | 0.142150E+10 | 0.152604E+10 | 0.560954E+09 |
September | 0.109185E+10 | 1144217.24 | 0.109071E+10 | 0.834744E+09 | 0.982441E+09 |
October | 0.782115E+09 | 0.00 | 0.782115E+09 | 0.272279E+09 | 0.171479E+10 |
November | 0.501154E+09 | 0.00 | 0.501154E+09 | 30765571.42 | 0.266571E+10 |
December | 0.434107E+09 | 0.00 | 0.434107E+09 | 0.00 | 0.426340E+10 |
Annual Sum or Average | 0.133119E+11 | 0.521934E+09 | 0.127900E+11 | 0.942532E+10 | 0.238804E+11 |
Minimum of Months | 0.434107E+09 | 0.00 | 0.434107E+09 | 0.00 | 0.448171E+09 |
Maximum of Months | 0.193286E+10 | 0.216101E+09 | 0.174081E+10 | 0.223611E+10 | 0.440562E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73196226.91 | 0.00 | 73196226.91 | 3516969.34 | 0.524051E+09 |
February | 0.101554E+09 | 0.00 | 0.101554E+09 | 19329522.56 | 0.376156E+09 |
March | 0.138364E+09 | 5398.29 | 0.138358E+09 | 50981331.26 | 0.316559E+09 |
April | 0.176094E+09 | 1829975.10 | 0.174264E+09 | 0.140784E+09 | 0.184651E+09 |
May | 0.255266E+09 | 13638445.42 | 0.241628E+09 | 0.328912E+09 | 94929750.92 |
June | 0.276133E+09 | 30872694.36 | 0.245260E+09 | 0.408076E+09 | 60505900.31 |
July | 0.272775E+09 | 24077951.73 | 0.248697E+09 | 0.425768E+09 | 53861837.62 |
August | 0.207056E+09 | 3976857.93 | 0.203080E+09 | 0.315222E+09 | 61859719.39 |
September | 0.155985E+09 | 163465.80 | 0.155821E+09 | 0.192727E+09 | 0.105472E+09 |
October | 0.111735E+09 | 0.00 | 0.111735E+09 | 86929736.70 | 0.182219E+09 |
November | 71596193.86 | 0.00 | 71596193.86 | 19401038.52 | 0.288587E+09 |
December | 62017652.81 | 0.00 | 62017652.81 | 1422854.24 | 0.502325E+09 |
Annual Sum or Average | 0.190177E+10 | 74564788.63 | 0.182721E+10 | 0.199307E+10 | 0.275118E+10 |
Minimum of Months | 62017652.81 | 0.00 | 62017652.81 | 1422854.24 | 53861837.62 |
Maximum of Months | 0.276133E+09 | 30872694.36 | 0.248697E+09 | 0.425768E+09 | 0.524051E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.597957E+09 | 0.248180E+09 | 0.349777E+09 | 0.293071E+09 | 0.179670E+10 |
February | 0.857902E+09 | 0.369112E+09 | 0.488791E+09 | 0.598965E+09 | 0.128365E+10 |
March | 0.129032E+10 | 0.648513E+09 | 0.641809E+09 | 0.113261E+10 | 0.110067E+10 |
April | 0.171942E+10 | 0.926613E+09 | 0.792812E+09 | 0.189935E+10 | 0.665624E+09 |
May | 0.192986E+10 | 0.850756E+09 | 0.107910E+10 | 0.249655E+10 | 0.354566E+09 |
June | 0.210731E+10 | 0.100748E+10 | 0.109983E+10 | 0.291059E+10 | 0.226696E+09 |
July | 0.213763E+10 | 0.100517E+10 | 0.113246E+10 | 0.303956E+10 | 0.201678E+09 |
August | 0.164549E+10 | 0.718770E+09 | 0.926722E+09 | 0.231917E+10 | 0.231708E+09 |
September | 0.127879E+10 | 0.573607E+09 | 0.705182E+09 | 0.163296E+10 | 0.387680E+09 |
October | 0.795836E+09 | 0.299270E+09 | 0.496566E+09 | 0.811249E+09 | 0.660627E+09 |
November | 0.493571E+09 | 0.164545E+09 | 0.329026E+09 | 0.319112E+09 | 0.101723E+10 |
December | 0.469008E+09 | 0.176254E+09 | 0.292755E+09 | 0.189097E+09 | 0.173975E+10 |
Annual Sum or Average | 0.153231E+11 | 0.698827E+10 | 0.833483E+10 | 0.176423E+11 | 0.966659E+10 |
Minimum of Months | 0.469008E+09 | 0.164545E+09 | 0.292755E+09 | 0.189097E+09 | 0.201678E+09 |
Maximum of Months | 0.213763E+10 | 0.100748E+10 | 0.113246E+10 | 0.303956E+10 | 0.179670E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.507050E+09 | 0.353187E+09 | 0.153863E+09 | 0.470380E+09 | 0.431780E+09 |
February | 0.572142E+09 | 0.384844E+09 | 0.187299E+09 | 0.584706E+09 | 0.328353E+09 |
March | 0.557363E+09 | 0.350902E+09 | 0.206461E+09 | 0.592990E+09 | 0.294528E+09 |
April | 0.493047E+09 | 0.267586E+09 | 0.225461E+09 | 0.583005E+09 | 0.185470E+09 |
May | 0.436189E+09 | 0.154284E+09 | 0.281905E+09 | 0.595999E+09 | 0.100253E+09 |
June | 0.370926E+09 | 98118509.68 | 0.272808E+09 | 0.553887E+09 | 63423008.84 |
July | 0.421767E+09 | 0.134652E+09 | 0.287115E+09 | 0.647985E+09 | 55904357.96 |
August | 0.447410E+09 | 0.186331E+09 | 0.261079E+09 | 0.653429E+09 | 62699766.54 |
September | 0.456438E+09 | 0.238967E+09 | 0.217472E+09 | 0.601141E+09 | 0.105214E+09 |
October | 0.418968E+09 | 0.249729E+09 | 0.169239E+09 | 0.486598E+09 | 0.176415E+09 |
November | 0.353885E+09 | 0.221773E+09 | 0.132112E+09 | 0.355340E+09 | 0.260477E+09 |
December | 0.389438E+09 | 0.255346E+09 | 0.134092E+09 | 0.338051E+09 | 0.417861E+09 |
Annual Sum or Average | 0.542462E+10 | 0.289572E+10 | 0.252891E+10 | 0.646351E+10 | 0.248238E+10 |
Minimum of Months | 0.353885E+09 | 98118509.68 | 0.132112E+09 | 0.338051E+09 | 55904357.96 |
Maximum of Months | 0.572142E+09 | 0.384844E+09 | 0.287115E+09 | 0.653429E+09 | 0.431780E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92698402.95 | 0.00 | 92698402.95 | 609089.25 | 0.781295E+09 |
February | 0.128612E+09 | 0.00 | 0.128612E+09 | 9077125.07 | 0.556687E+09 |
March | 0.175229E+09 | 6836.60 | 0.175222E+09 | 31778305.02 | 0.467737E+09 |
April | 0.223012E+09 | 2317548.00 | 0.220694E+09 | 0.113770E+09 | 0.263837E+09 |
May | 0.323279E+09 | 17272230.58 | 0.306006E+09 | 0.301218E+09 | 0.134717E+09 |
June | 0.349705E+09 | 39098319.45 | 0.310607E+09 | 0.393115E+09 | 86611900.16 |
July | 0.345452E+09 | 30493206.63 | 0.314959E+09 | 0.403569E+09 | 82401793.59 |
August | 0.262224E+09 | 5036439.64 | 0.257187E+09 | 0.278689E+09 | 99916826.49 |
September | 0.197545E+09 | 207019.12 | 0.197338E+09 | 0.158518E+09 | 0.166265E+09 |
October | 0.141505E+09 | 0.00 | 0.141505E+09 | 57420509.36 | 0.281002E+09 |
November | 90672062.05 | 0.00 | 90672062.05 | 8021730.11 | 0.442903E+09 |
December | 78541444.19 | 0.00 | 78541444.19 | 132.66 | 0.749497E+09 |
Annual Sum or Average | 0.240847E+10 | 94431600.03 | 0.231404E+10 | 0.175579E+10 | 0.411287E+10 |
Minimum of Months | 78541444.19 | 0.00 | 78541444.19 | 132.66 | 82401793.59 |
Maximum of Months | 0.349705E+09 | 39098319.45 | 0.314959E+09 | 0.403569E+09 | 0.781295E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82937612.36 | 0.00 | 82937612.36 | 544954.46 | 0.698905E+09 |
February | 0.115070E+09 | 0.00 | 0.115070E+09 | 8121338.20 | 0.498060E+09 |
March | 0.156778E+09 | 6116.73 | 0.156772E+09 | 28432169.91 | 0.418486E+09 |
April | 0.199529E+09 | 2073518.98 | 0.197456E+09 | 0.101791E+09 | 0.236056E+09 |
May | 0.289239E+09 | 15453530.15 | 0.273785E+09 | 0.269501E+09 | 0.120532E+09 |
June | 0.312882E+09 | 34981414.56 | 0.277901E+09 | 0.351722E+09 | 77491995.24 |
July | 0.309078E+09 | 27282387.51 | 0.281795E+09 | 0.361075E+09 | 73725196.94 |
August | 0.234613E+09 | 4506121.63 | 0.230107E+09 | 0.249344E+09 | 89395963.25 |
September | 0.176744E+09 | 185220.79 | 0.176559E+09 | 0.141827E+09 | 0.148758E+09 |
October | 0.126605E+09 | 0.00 | 0.126605E+09 | 51374347.29 | 0.251413E+09 |
November | 81124637.48 | 0.00 | 81124637.48 | 7177072.32 | 0.396243E+09 |
December | 70271327.71 | 0.00 | 70271327.71 | 118.69 | 0.670495E+09 |
Annual Sum or Average | 0.215487E+10 | 84488310.34 | 0.207038E+10 | 0.157091E+10 | 0.367956E+10 |
Minimum of Months | 70271327.71 | 0.00 | 70271327.71 | 118.69 | 73725196.94 |
Maximum of Months | 0.312882E+09 | 34981414.56 | 0.281795E+09 | 0.361075E+09 | 0.698905E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189297E+10 | 0.131855E+10 | 0.574416E+09 | 0.161128E+10 | 0.182559E+10 |
February | 0.213598E+10 | 0.143674E+10 | 0.699242E+09 | 0.203423E+10 | 0.137260E+10 |
March | 0.208080E+10 | 0.131002E+10 | 0.770780E+09 | 0.203985E+10 | 0.124041E+10 |
April | 0.184069E+10 | 0.998978E+09 | 0.841712E+09 | 0.196064E+10 | 0.779830E+09 |
May | 0.162842E+10 | 0.575988E+09 | 0.105243E+10 | 0.189157E+10 | 0.436231E+09 |
June | 0.138478E+10 | 0.366306E+09 | 0.101847E+10 | 0.170889E+10 | 0.277996E+09 |
July | 0.157458E+10 | 0.502695E+09 | 0.107189E+10 | 0.202149E+10 | 0.260655E+09 |
August | 0.167032E+10 | 0.695631E+09 | 0.974685E+09 | 0.208320E+10 | 0.305233E+09 |
September | 0.170402E+10 | 0.892134E+09 | 0.811886E+09 | 0.197343E+10 | 0.486365E+09 |
October | 0.156413E+10 | 0.932313E+09 | 0.631821E+09 | 0.161686E+10 | 0.776555E+09 |
November | 0.132116E+10 | 0.827946E+09 | 0.493214E+09 | 0.119512E+10 | 0.112687E+10 |
December | 0.145389E+10 | 0.953284E+09 | 0.500605E+09 | 0.114074E+10 | 0.177802E+10 |
Annual Sum or Average | 0.202517E+11 | 0.108106E+11 | 0.944116E+10 | 0.212773E+11 | 0.106664E+11 |
Minimum of Months | 0.132116E+10 | 0.366306E+09 | 0.493214E+09 | 0.114074E+10 | 0.260655E+09 |
Maximum of Months | 0.213598E+10 | 0.143674E+10 | 0.107189E+10 | 0.208320E+10 | 0.182559E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 825.66 | 860.35 | 957.48 | 666.94 | 290.54 | 0.00 | 0.00 |
February | 1147.18 | 722.33 | 1196.15 | 804.58 | 391.58 | 0.00 | 0.00 |
March | 1033.46 | 590.67 | 1052.49 | 662.62 | 389.87 | 0.00 | 0.00 |
April | 1025.47 | 383.15 | 962.07 | 522.14 | 439.93 | 0.00 | 0.00 |
May | 966.10 | 199.61 | 823.67 | 291.34 | 532.33 | 0.00 | 0.00 |
June | 906.56 | 126.54 | 723.78 | 191.46 | 532.32 | 0.00 | 0.00 |
July | 1031.31 | 116.05 | 796.43 | 254.27 | 542.17 | 0.00 | 0.00 |
August | 1060.80 | 136.11 | 844.86 | 351.86 | 493.00 | 0.00 | 0.00 |
September | 1035.44 | 231.03 | 890.64 | 466.29 | 424.35 | 0.00 | 0.00 |
October | 819.40 | 368.41 | 791.15 | 471.57 | 319.58 | 0.00 | 0.00 |
November | 630.97 | 547.71 | 690.53 | 432.74 | 257.79 | 0.00 | 0.00 |
December | 588.37 | 832.02 | 735.39 | 482.18 | 253.21 | 0.00 | 0.00 |
Annual Sum or Average | 920.97 | 424.87 | 870.00 | 464.41 | 405.58 | 0.00 | 0.00 |
Minimum of Months | 588.37 | 116.05 | 690.53 | 191.46 | 253.21 | 0.00 | 0.00 |
Maximum of Months | 1147.18 | 860.35 | 1196.15 | 804.58 | 542.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2308.60 | 2423.10 | 2696.21 | 1878.05 | 818.15 | 0.00 | 0.00 |
February | 3207.82 | 2046.39 | 3368.29 | 2265.64 | 1102.65 | 0.00 | 0.00 |
March | 2887.73 | 1691.31 | 2963.73 | 1865.90 | 1097.84 | 0.00 | 0.00 |
April | 2860.66 | 1120.59 | 2709.13 | 1470.30 | 1238.82 | 0.00 | 0.00 |
May | 2684.02 | 604.02 | 2319.39 | 820.40 | 1499.00 | 0.00 | 0.00 |
June | 2513.28 | 393.25 | 2038.11 | 539.13 | 1498.98 | 0.00 | 0.00 |
July | 2871.91 | 356.21 | 2242.71 | 716.00 | 1526.70 | 0.00 | 0.00 |
August | 2956.39 | 423.62 | 2379.07 | 990.81 | 1388.26 | 0.00 | 0.00 |
September | 2885.62 | 704.22 | 2507.98 | 1313.05 | 1194.93 | 0.00 | 0.00 |
October | 2285.12 | 1083.86 | 2227.83 | 1327.92 | 899.92 | 0.00 | 0.00 |
November | 1759.86 | 1567.02 | 1944.49 | 1218.58 | 725.91 | 0.00 | 0.00 |
December | 1643.69 | 2343.12 | 2070.81 | 1357.79 | 713.02 | 0.00 | 0.00 |
Annual Sum or Average | 2567.57 | 1226.12 | 2449.85 | 1307.76 | 1142.09 | 0.00 | 0.00 |
Minimum of Months | 1643.69 | 356.21 | 1944.49 | 539.13 | 713.02 | 0.00 | 0.00 |
Maximum of Months | 3207.82 | 2423.10 | 3368.29 | 2265.64 | 1526.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3034.53 | 3253.30 | 3502.53 | 2439.70 | 1062.83 | 0.00 | 0.00 |
February | 4228.90 | 2751.58 | 4375.60 | 2943.19 | 1432.41 | 0.00 | 0.00 |
March | 3807.34 | 2285.55 | 3850.06 | 2423.91 | 1426.15 | 0.00 | 0.00 |
April | 3766.39 | 1531.10 | 3519.31 | 1910.01 | 1609.30 | 0.00 | 0.00 |
May | 3528.86 | 828.56 | 3013.03 | 1065.74 | 1947.28 | 0.00 | 0.00 |
June | 3301.36 | 543.62 | 2647.62 | 700.36 | 1947.26 | 0.00 | 0.00 |
July | 3778.78 | 484.46 | 2913.40 | 930.13 | 1983.28 | 0.00 | 0.00 |
August | 3885.36 | 578.16 | 3090.54 | 1287.11 | 1803.43 | 0.00 | 0.00 |
September | 3785.64 | 970.73 | 3258.00 | 1705.72 | 1552.28 | 0.00 | 0.00 |
October | 2989.93 | 1498.57 | 2894.08 | 1725.04 | 1169.04 | 0.00 | 0.00 |
November | 2306.78 | 2153.26 | 2526.00 | 1583.00 | 943.00 | 0.00 | 0.00 |
December | 2155.44 | 3163.22 | 2690.10 | 1763.84 | 926.26 | 0.00 | 0.00 |
Annual Sum or Average | 3374.80 | 1665.35 | 3182.50 | 1698.85 | 1483.64 | 0.00 | 0.00 |
Minimum of Months | 2155.44 | 484.46 | 2526.00 | 700.36 | 926.26 | 0.00 | 0.00 |
Maximum of Months | 4228.90 | 3253.30 | 4375.60 | 2943.19 | 1983.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 184.35 | 515.56 | 304.02 | 180.46 | 123.56 | 0.00 | 0.00 |
February | 334.21 | 427.18 | 422.00 | 244.24 | 177.76 | 0.00 | 0.00 |
March | 393.63 | 341.90 | 451.34 | 255.75 | 195.59 | 0.00 | 0.00 |
April | 501.46 | 214.81 | 500.60 | 260.62 | 239.98 | 0.00 | 0.00 |
May | 625.96 | 109.67 | 544.53 | 240.13 | 304.40 | 0.00 | 0.00 |
June | 626.05 | 67.70 | 509.87 | 196.19 | 313.68 | 0.00 | 0.00 |
July | 696.64 | 59.34 | 549.58 | 232.57 | 317.01 | 0.00 | 0.00 |
August | 601.91 | 70.83 | 488.92 | 215.38 | 273.54 | 0.00 | 0.00 |
September | 479.25 | 128.32 | 428.77 | 205.58 | 223.19 | 0.00 | 0.00 |
October | 298.63 | 210.32 | 316.28 | 157.57 | 158.71 | 0.00 | 0.00 |
November | 170.17 | 323.20 | 233.84 | 118.67 | 115.17 | 0.00 | 0.00 |
December | 118.82 | 501.77 | 231.19 | 125.10 | 106.09 | 0.00 | 0.00 |
Annual Sum or Average | 419.68 | 246.77 | 414.99 | 202.43 | 212.56 | 0.00 | 0.00 |
Minimum of Months | 118.82 | 59.34 | 231.19 | 118.67 | 106.09 | 0.00 | 0.00 |
Maximum of Months | 696.64 | 515.56 | 549.58 | 260.62 | 317.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 41.90 | 575.81 | 142.04 | 48.59 | 93.44 | 0.00 | 0.00 |
February | 123.85 | 458.26 | 227.48 | 85.16 | 142.32 | 0.00 | 0.00 |
March | 207.08 | 353.43 | 294.90 | 124.74 | 170.16 | 0.00 | 0.00 |
April | 340.84 | 213.64 | 378.32 | 158.09 | 220.22 | 0.00 | 0.00 |
May | 528.00 | 104.83 | 476.98 | 187.62 | 289.36 | 0.00 | 0.00 |
June | 569.78 | 64.58 | 473.30 | 170.25 | 303.05 | 0.00 | 0.00 |
July | 614.51 | 56.71 | 493.95 | 191.29 | 302.66 | 0.00 | 0.00 |
August | 478.41 | 69.06 | 399.18 | 147.30 | 251.89 | 0.00 | 0.00 |
September | 327.99 | 127.43 | 312.85 | 113.45 | 199.40 | 0.00 | 0.00 |
October | 159.20 | 213.57 | 201.57 | 64.33 | 137.24 | 0.00 | 0.00 |
November | 54.75 | 340.75 | 124.94 | 33.11 | 91.82 | 0.00 | 0.00 |
December | 21.28 | 557.32 | 108.95 | 29.76 | 79.19 | 0.00 | 0.00 |
Annual Sum or Average | 289.94 | 260.48 | 303.28 | 112.97 | 190.31 | 0.00 | 0.00 |
Minimum of Months | 21.28 | 56.71 | 108.95 | 29.76 | 79.19 | 0.00 | 0.00 |
Maximum of Months | 614.51 | 575.81 | 493.95 | 191.29 | 303.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 131.35 | 136.79 | 151.42 | 105.47 | 45.95 | 0.00 | 0.00 |
February | 181.65 | 115.80 | 189.16 | 127.24 | 61.93 | 0.00 | 0.00 |
March | 163.89 | 95.49 | 166.44 | 104.79 | 61.65 | 0.00 | 0.00 |
April | 161.49 | 64.56 | 152.14 | 82.57 | 69.57 | 0.00 | 0.00 |
May | 151.19 | 35.24 | 130.26 | 46.07 | 84.18 | 0.00 | 0.00 |
June | 142.18 | 22.63 | 114.46 | 30.28 | 84.18 | 0.00 | 0.00 |
July | 163.21 | 20.08 | 125.95 | 40.21 | 85.74 | 0.00 | 0.00 |
August | 167.18 | 24.16 | 133.61 | 55.64 | 77.97 | 0.00 | 0.00 |
September | 162.44 | 41.17 | 140.85 | 73.74 | 67.11 | 0.00 | 0.00 |
October | 129.53 | 61.00 | 125.12 | 74.58 | 50.54 | 0.00 | 0.00 |
November | 100.48 | 86.29 | 109.20 | 68.43 | 40.77 | 0.00 | 0.00 |
December | 93.71 | 131.60 | 116.30 | 76.25 | 40.04 | 0.00 | 0.00 |
Annual Sum or Average | 145.44 | 69.36 | 137.58 | 73.44 | 64.14 | 0.00 | 0.00 |
Minimum of Months | 93.71 | 20.08 | 109.20 | 30.28 | 40.04 | 0.00 | 0.00 |
Maximum of Months | 181.65 | 136.79 | 189.16 | 127.24 | 85.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.26 | 177.77 | 21.87 | 0.00 | 21.87 | 0.00 | 0.00 |
February | 3.24 | 139.43 | 33.59 | 0.00 | 33.59 | 0.00 | 0.00 |
March | 9.19 | 105.57 | 41.33 | 0.00 | 41.33 | 0.00 | 0.00 |
April | 30.81 | 60.91 | 54.36 | 0.56 | 53.79 | 0.00 | 0.00 |
May | 76.61 | 27.65 | 76.25 | 4.07 | 72.18 | 0.00 | 0.00 |
June | 102.60 | 16.96 | 85.24 | 9.53 | 75.71 | 0.00 | 0.00 |
July | 102.70 | 14.45 | 81.48 | 7.19 | 74.29 | 0.00 | 0.00 |
August | 71.91 | 17.94 | 61.85 | 1.19 | 60.67 | 0.00 | 0.00 |
September | 42.70 | 35.45 | 48.15 | 0.05 | 48.10 | 0.00 | 0.00 |
October | 15.65 | 62.41 | 33.38 | 0.00 | 33.38 | 0.00 | 0.00 |
November | 2.44 | 103.00 | 22.10 | 0.00 | 22.10 | 0.00 | 0.00 |
December | 0.01 | 170.26 | 18.53 | 0.00 | 18.53 | 0.00 | 0.00 |
Annual Sum or Average | 38.39 | 77.40 | 48.25 | 1.89 | 46.36 | 0.00 | 0.00 |
Minimum of Months | 0.01 | 14.45 | 18.53 | 0.00 | 18.53 | 0.00 | 0.00 |
Maximum of Months | 102.70 | 177.77 | 85.24 | 9.53 | 75.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 179.45 | 512.71 | 300.94 | 178.20 | 122.75 | 0.00 | 0.00 |
February | 319.67 | 420.11 | 413.82 | 235.37 | 178.45 | 0.00 | 0.00 |
March | 382.43 | 334.39 | 448.99 | 252.08 | 196.90 | 0.00 | 0.00 |
April | 520.75 | 207.84 | 521.92 | 281.99 | 239.93 | 0.00 | 0.00 |
May | 592.44 | 102.99 | 523.14 | 216.43 | 306.71 | 0.00 | 0.00 |
June | 673.40 | 64.82 | 549.64 | 232.21 | 317.42 | 0.00 | 0.00 |
July | 701.96 | 56.22 | 556.55 | 237.93 | 318.62 | 0.00 | 0.00 |
August | 579.69 | 68.41 | 474.24 | 203.76 | 270.49 | 0.00 | 0.00 |
September | 468.52 | 124.90 | 422.79 | 202.85 | 219.94 | 0.00 | 0.00 |
October | 282.09 | 207.77 | 305.00 | 149.11 | 155.89 | 0.00 | 0.00 |
November | 165.30 | 319.62 | 231.75 | 117.30 | 114.44 | 0.00 | 0.00 |
December | 121.47 | 501.26 | 232.96 | 128.24 | 104.72 | 0.00 | 0.00 |
Annual Sum or Average | 415.93 | 242.67 | 414.98 | 202.63 | 212.35 | 0.00 | 0.00 |
Minimum of Months | 121.47 | 56.22 | 231.75 | 117.30 | 104.72 | 0.00 | 0.00 |
Maximum of Months | 701.96 | 512.71 | 556.55 | 281.99 | 318.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 32.24 | 568.23 | 138.96 | 46.33 | 92.63 | 0.00 | 0.00 |
February | 101.53 | 443.43 | 219.30 | 76.29 | 143.01 | 0.00 | 0.00 |
March | 191.55 | 341.08 | 292.55 | 121.07 | 171.48 | 0.00 | 0.00 |
April | 357.82 | 205.44 | 399.64 | 179.46 | 220.18 | 0.00 | 0.00 |
May | 496.27 | 100.45 | 455.59 | 163.92 | 291.67 | 0.00 | 0.00 |
June | 618.45 | 63.27 | 513.06 | 206.27 | 306.80 | 0.00 | 0.00 |
July | 621.17 | 55.07 | 500.92 | 196.65 | 304.27 | 0.00 | 0.00 |
August | 456.44 | 67.19 | 384.51 | 135.67 | 248.83 | 0.00 | 0.00 |
September | 315.97 | 123.47 | 306.88 | 110.72 | 196.16 | 0.00 | 0.00 |
October | 139.98 | 208.44 | 190.29 | 55.87 | 134.42 | 0.00 | 0.00 |
November | 47.32 | 334.84 | 122.84 | 31.74 | 91.10 | 0.00 | 0.00 |
December | 18.81 | 551.45 | 110.71 | 32.91 | 77.81 | 0.00 | 0.00 |
Annual Sum or Average | 284.05 | 254.45 | 303.27 | 113.17 | 190.10 | 0.00 | 0.00 |
Minimum of Months | 18.81 | 55.07 | 110.71 | 31.74 | 77.81 | 0.00 | 0.00 |
Maximum of Months | 621.17 | 568.23 | 513.06 | 206.27 | 306.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 221.81 | 651.44 | 375.45 | 228.53 | 146.92 | 0.00 | 0.00 |
February | 366.02 | 539.79 | 482.62 | 275.69 | 206.94 | 0.00 | 0.00 |
March | 360.29 | 435.06 | 450.18 | 227.05 | 223.13 | 0.00 | 0.00 |
April | 415.64 | 276.43 | 447.41 | 180.13 | 267.28 | 0.00 | 0.00 |
May | 486.82 | 140.29 | 447.42 | 108.65 | 338.77 | 0.00 | 0.00 |
June | 519.61 | 90.83 | 432.66 | 86.25 | 346.41 | 0.00 | 0.00 |
July | 562.43 | 83.67 | 449.42 | 102.71 | 346.72 | 0.00 | 0.00 |
August | 510.51 | 101.29 | 423.49 | 123.14 | 300.35 | 0.00 | 0.00 |
September | 442.38 | 174.23 | 409.49 | 159.88 | 249.60 | 0.00 | 0.00 |
October | 310.39 | 271.25 | 343.40 | 161.58 | 181.81 | 0.00 | 0.00 |
November | 203.28 | 411.56 | 284.49 | 148.28 | 136.21 | 0.00 | 0.00 |
December | 150.68 | 637.03 | 292.12 | 165.22 | 126.90 | 0.00 | 0.00 |
Annual Sum or Average | 379.09 | 316.79 | 402.63 | 163.23 | 239.40 | 0.00 | 0.00 |
Minimum of Months | 150.68 | 83.67 | 284.49 | 86.25 | 126.90 | 0.00 | 0.00 |
Maximum of Months | 562.43 | 651.44 | 482.62 | 275.69 | 346.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 184.06 | 515.25 | 304.02 | 180.46 | 123.56 | 0.00 | 0.00 |
February | 333.59 | 426.28 | 422.00 | 244.24 | 177.76 | 0.00 | 0.00 |
March | 393.15 | 340.68 | 451.34 | 255.75 | 195.59 | 0.00 | 0.00 |
April | 500.31 | 213.15 | 500.60 | 260.62 | 239.98 | 0.00 | 0.00 |
May | 623.77 | 108.39 | 544.53 | 240.13 | 304.40 | 0.00 | 0.00 |
June | 624.10 | 66.45 | 509.87 | 196.19 | 313.68 | 0.00 | 0.00 |
July | 694.41 | 58.07 | 549.58 | 232.57 | 317.01 | 0.00 | 0.00 |
August | 600.08 | 69.41 | 488.92 | 215.38 | 273.54 | 0.00 | 0.00 |
September | 478.31 | 126.43 | 428.77 | 205.58 | 223.19 | 0.00 | 0.00 |
October | 298.99 | 207.93 | 316.28 | 157.57 | 158.71 | 0.00 | 0.00 |
November | 170.56 | 321.47 | 233.84 | 118.67 | 115.17 | 0.00 | 0.00 |
December | 118.53 | 501.79 | 231.19 | 125.10 | 106.09 | 0.00 | 0.00 |
Annual Sum or Average | 418.74 | 245.50 | 414.99 | 202.43 | 212.56 | 0.00 | 0.00 |
Minimum of Months | 118.53 | 58.07 | 231.19 | 118.67 | 106.09 | 0.00 | 0.00 |
Maximum of Months | 694.41 | 515.25 | 549.58 | 260.62 | 317.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 41.83 | 575.60 | 142.04 | 48.59 | 93.44 | 0.00 | 0.00 |
February | 123.72 | 457.54 | 227.48 | 85.16 | 142.32 | 0.00 | 0.00 |
March | 206.95 | 352.21 | 294.90 | 124.74 | 170.16 | 0.00 | 0.00 |
April | 340.72 | 211.83 | 378.32 | 158.09 | 220.22 | 0.00 | 0.00 |
May | 526.45 | 103.54 | 476.98 | 187.62 | 289.36 | 0.00 | 0.00 |
June | 568.26 | 63.43 | 473.30 | 170.25 | 303.05 | 0.00 | 0.00 |
July | 612.83 | 55.53 | 493.95 | 191.29 | 302.66 | 0.00 | 0.00 |
August | 477.38 | 67.57 | 399.18 | 147.30 | 251.89 | 0.00 | 0.00 |
September | 328.23 | 125.20 | 312.85 | 113.45 | 199.40 | 0.00 | 0.00 |
October | 160.34 | 210.69 | 201.57 | 64.33 | 137.24 | 0.00 | 0.00 |
November | 55.32 | 338.92 | 124.94 | 33.11 | 91.82 | 0.00 | 0.00 |
December | 21.23 | 557.44 | 108.95 | 29.76 | 79.19 | 0.00 | 0.00 |
Annual Sum or Average | 289.58 | 259.16 | 303.28 | 112.97 | 190.31 | 0.00 | 0.00 |
Minimum of Months | 21.23 | 55.53 | 108.95 | 29.76 | 79.19 | 0.00 | 0.00 |
Maximum of Months | 612.83 | 575.60 | 493.95 | 191.29 | 303.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 235.05 | 261.58 | 277.64 | 193.39 | 84.25 | 0.00 | 0.00 |
February | 326.75 | 218.89 | 346.85 | 233.30 | 113.55 | 0.00 | 0.00 |
March | 296.34 | 177.91 | 305.19 | 192.14 | 113.05 | 0.00 | 0.00 |
April | 295.09 | 113.56 | 278.97 | 151.40 | 127.57 | 0.00 | 0.00 |
May | 279.78 | 56.25 | 238.84 | 84.48 | 154.36 | 0.00 | 0.00 |
June | 264.85 | 33.92 | 209.88 | 55.52 | 154.36 | 0.00 | 0.00 |
July | 302.83 | 28.99 | 230.94 | 73.73 | 157.21 | 0.00 | 0.00 |
August | 309.20 | 35.27 | 244.99 | 102.03 | 142.96 | 0.00 | 0.00 |
September | 299.51 | 66.01 | 258.26 | 135.21 | 123.05 | 0.00 | 0.00 |
October | 236.59 | 108.42 | 229.41 | 136.74 | 92.67 | 0.00 | 0.00 |
November | 180.26 | 164.69 | 200.23 | 125.48 | 74.75 | 0.00 | 0.00 |
December | 166.99 | 252.92 | 213.24 | 139.82 | 73.42 | 0.00 | 0.00 |
Annual Sum or Average | 265.67 | 126.13 | 252.27 | 134.67 | 117.61 | 0.00 | 0.00 |
Minimum of Months | 166.99 | 28.99 | 200.23 | 55.52 | 73.42 | 0.00 | 0.00 |
Maximum of Months | 326.75 | 261.58 | 346.85 | 233.30 | 157.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.95 | 1619.67 | 191.29 | 0.00 | 191.29 | 0.00 | 0.00 |
February | 19.05 | 1301.13 | 293.84 | 0.00 | 293.84 | 0.00 | 0.00 |
March | 60.74 | 1009.32 | 361.60 | 0.01 | 361.59 | 0.00 | 0.00 |
April | 227.82 | 602.85 | 475.54 | 4.94 | 470.60 | 0.00 | 0.00 |
May | 612.68 | 285.09 | 667.11 | 35.64 | 631.47 | 0.00 | 0.00 |
June | 836.79 | 185.63 | 745.70 | 83.37 | 662.33 | 0.00 | 0.00 |
July | 841.56 | 163.54 | 712.87 | 62.93 | 649.95 | 0.00 | 0.00 |
August | 576.70 | 204.12 | 541.12 | 10.39 | 530.73 | 0.00 | 0.00 |
September | 329.67 | 370.47 | 421.24 | 0.44 | 420.80 | 0.00 | 0.00 |
October | 108.22 | 624.99 | 292.01 | 0.00 | 292.01 | 0.00 | 0.00 |
November | 13.57 | 1002.78 | 193.35 | 0.00 | 193.35 | 0.00 | 0.00 |
December | 0.00 | 1565.42 | 162.08 | 0.00 | 162.08 | 0.00 | 0.00 |
Annual Sum or Average | 304.10 | 742.25 | 422.12 | 16.55 | 405.57 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 163.54 | 162.08 | 0.00 | 162.08 | 0.00 | 0.00 |
Maximum of Months | 841.56 | 1619.67 | 745.70 | 83.37 | 662.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.67 | 1644.87 | 191.29 | 0.00 | 191.29 | 0.00 | 0.00 |
February | 16.76 | 1327.03 | 293.84 | 0.00 | 293.84 | 0.00 | 0.00 |
March | 55.94 | 1031.31 | 361.60 | 0.01 | 361.59 | 0.00 | 0.00 |
April | 218.76 | 615.75 | 475.54 | 4.94 | 470.60 | 0.00 | 0.00 |
May | 603.97 | 290.65 | 667.11 | 35.64 | 631.47 | 0.00 | 0.00 |
June | 828.90 | 189.89 | 745.70 | 83.37 | 662.33 | 0.00 | 0.00 |
July | 834.87 | 167.33 | 712.87 | 62.93 | 649.95 | 0.00 | 0.00 |
August | 569.76 | 209.44 | 541.12 | 10.39 | 530.73 | 0.00 | 0.00 |
September | 322.05 | 379.03 | 421.24 | 0.44 | 420.80 | 0.00 | 0.00 |
October | 101.66 | 640.23 | 292.01 | 0.00 | 292.01 | 0.00 | 0.00 |
November | 11.87 | 1028.44 | 193.35 | 0.00 | 193.35 | 0.00 | 0.00 |
December | 0.00 | 1591.77 | 162.08 | 0.00 | 162.08 | 0.00 | 0.00 |
Annual Sum or Average | 298.87 | 757.24 | 422.12 | 16.55 | 405.57 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 167.33 | 162.08 | 0.00 | 162.08 | 0.00 | 0.00 |
Maximum of Months | 834.87 | 1644.87 | 745.70 | 83.37 | 662.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 222.64 | 963.97 | 439.89 | 224.52 | 215.37 | 0.00 | 0.00 |
February | 465.83 | 790.39 | 633.10 | 311.65 | 321.45 | 0.00 | 0.00 |
March | 648.75 | 624.55 | 741.51 | 373.14 | 368.36 | 0.00 | 0.00 |
April | 1006.01 | 393.59 | 921.51 | 461.43 | 460.08 | 0.00 | 0.00 |
May | 1274.99 | 202.82 | 978.69 | 380.33 | 598.36 | 0.00 | 0.00 |
June | 1492.86 | 134.09 | 1062.64 | 438.45 | 624.19 | 0.00 | 0.00 |
July | 1534.97 | 115.52 | 1057.41 | 434.55 | 622.86 | 0.00 | 0.00 |
August | 1227.15 | 132.63 | 858.71 | 339.41 | 519.30 | 0.00 | 0.00 |
September | 934.91 | 229.48 | 729.63 | 313.56 | 416.08 | 0.00 | 0.00 |
October | 514.84 | 378.37 | 495.27 | 204.97 | 290.30 | 0.00 | 0.00 |
November | 253.65 | 590.24 | 354.57 | 149.04 | 205.53 | 0.00 | 0.00 |
December | 145.45 | 941.21 | 343.66 | 161.14 | 182.52 | 0.00 | 0.00 |
Annual Sum or Average | 811.78 | 456.67 | 718.21 | 315.78 | 402.43 | 0.00 | 0.00 |
Minimum of Months | 145.45 | 115.52 | 343.66 | 149.04 | 182.52 | 0.00 | 0.00 |
Maximum of Months | 1534.97 | 963.97 | 1062.64 | 461.43 | 624.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 514.02 | 1146.24 | 772.33 | 492.29 | 280.04 | 0.00 | 0.00 |
February | 797.19 | 952.58 | 983.66 | 593.89 | 389.77 | 0.00 | 0.00 |
March | 762.04 | 771.96 | 900.84 | 489.11 | 411.73 | 0.00 | 0.00 |
April | 837.06 | 491.20 | 873.16 | 387.10 | 486.06 | 0.00 | 0.00 |
May | 913.82 | 252.68 | 836.67 | 227.27 | 609.40 | 0.00 | 0.00 |
June | 940.60 | 164.51 | 789.88 | 169.90 | 619.98 | 0.00 | 0.00 |
July | 1035.68 | 151.07 | 832.26 | 209.26 | 623.00 | 0.00 | 0.00 |
August | 973.46 | 183.18 | 809.12 | 263.28 | 545.84 | 0.00 | 0.00 |
September | 876.54 | 308.49 | 801.82 | 344.34 | 457.48 | 0.00 | 0.00 |
October | 637.74 | 482.17 | 684.08 | 348.09 | 336.00 | 0.00 | 0.00 |
November | 439.33 | 730.88 | 575.99 | 319.42 | 256.56 | 0.00 | 0.00 |
December | 353.62 | 1121.71 | 598.38 | 355.92 | 242.46 | 0.00 | 0.00 |
Annual Sum or Average | 756.24 | 561.38 | 786.88 | 348.47 | 438.41 | 0.00 | 0.00 |
Minimum of Months | 353.62 | 151.07 | 575.99 | 169.90 | 242.46 | 0.00 | 0.00 |
Maximum of Months | 1035.68 | 1146.24 | 983.66 | 593.89 | 623.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.221145E+10 | 0.230437E+10 | 0.256452E+10 | 0.178633E+10 | 0.778194E+09 | 0.00 | 0.00 |
February | 0.277527E+10 | 0.174745E+10 | 0.289374E+10 | 0.194644E+10 | 0.947301E+09 | 0.00 | 0.00 |
March | 0.276802E+10 | 0.158205E+10 | 0.281898E+10 | 0.177477E+10 | 0.104422E+10 | 0.00 | 0.00 |
April | 0.265803E+10 | 0.993119E+09 | 0.249369E+10 | 0.135338E+10 | 0.114031E+10 | 0.00 | 0.00 |
May | 0.258761E+10 | 0.534638E+09 | 0.220611E+10 | 0.780327E+09 | 0.142579E+10 | 0.00 | 0.00 |
June | 0.234981E+10 | 0.327984E+09 | 0.187603E+10 | 0.496257E+09 | 0.137978E+10 | 0.00 | 0.00 |
July | 0.276227E+10 | 0.310820E+09 | 0.213317E+10 | 0.681032E+09 | 0.145214E+10 | 0.00 | 0.00 |
August | 0.284124E+10 | 0.364560E+09 | 0.226287E+10 | 0.942414E+09 | 0.132045E+10 | 0.00 | 0.00 |
September | 0.268386E+10 | 0.598832E+09 | 0.230853E+10 | 0.120863E+10 | 0.109990E+10 | 0.00 | 0.00 |
October | 0.219469E+10 | 0.986753E+09 | 0.211902E+10 | 0.126306E+10 | 0.855962E+09 | 0.00 | 0.00 |
November | 0.163547E+10 | 0.141967E+10 | 0.178985E+10 | 0.112167E+10 | 0.668184E+09 | 0.00 | 0.00 |
December | 0.157589E+10 | 0.222847E+10 | 0.196967E+10 | 0.129147E+10 | 0.678197E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.290436E+11 | 0.133987E+11 | 0.274362E+11 | 0.146458E+11 | 0.127904E+11 | 0.00 | 0.00 |
Minimum of Months | 0.157589E+10 | 0.310820E+09 | 0.178985E+10 | 0.496257E+09 | 0.668184E+09 | 0.00 | 0.00 |
Maximum of Months | 0.284124E+10 | 0.230437E+10 | 0.289374E+10 | 0.194644E+10 | 0.145214E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.618336E+10 | 0.649002E+10 | 0.722152E+10 | 0.503018E+10 | 0.219134E+10 | 0.00 | 0.00 |
February | 0.776037E+10 | 0.495063E+10 | 0.814857E+10 | 0.548103E+10 | 0.266754E+10 | 0.00 | 0.00 |
March | 0.773451E+10 | 0.453001E+10 | 0.793806E+10 | 0.499762E+10 | 0.294044E+10 | 0.00 | 0.00 |
April | 0.741482E+10 | 0.290456E+10 | 0.702205E+10 | 0.381102E+10 | 0.321103E+10 | 0.00 | 0.00 |
May | 0.718888E+10 | 0.161782E+10 | 0.621227E+10 | 0.219735E+10 | 0.401492E+10 | 0.00 | 0.00 |
June | 0.651442E+10 | 0.101930E+10 | 0.528278E+10 | 0.139743E+10 | 0.388536E+10 | 0.00 | 0.00 |
July | 0.769212E+10 | 0.954077E+09 | 0.600687E+10 | 0.191774E+10 | 0.408912E+10 | 0.00 | 0.00 |
August | 0.791840E+10 | 0.113462E+10 | 0.637209E+10 | 0.265378E+10 | 0.371831E+10 | 0.00 | 0.00 |
September | 0.747952E+10 | 0.182534E+10 | 0.650068E+10 | 0.340342E+10 | 0.309726E+10 | 0.00 | 0.00 |
October | 0.612046E+10 | 0.290301E+10 | 0.596703E+10 | 0.355670E+10 | 0.241033E+10 | 0.00 | 0.00 |
November | 0.456156E+10 | 0.406172E+10 | 0.504011E+10 | 0.315855E+10 | 0.188156E+10 | 0.00 | 0.00 |
December | 0.440246E+10 | 0.627581E+10 | 0.554646E+10 | 0.363670E+10 | 0.190976E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.809709E+11 | 0.386669E+11 | 0.772585E+11 | 0.412415E+11 | 0.360170E+11 | 0.00 | 0.00 |
Minimum of Months | 0.440246E+10 | 0.954077E+09 | 0.504011E+10 | 0.139743E+10 | 0.188156E+10 | 0.00 | 0.00 |
Maximum of Months | 0.791840E+10 | 0.649002E+10 | 0.814857E+10 | 0.548103E+10 | 0.408912E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.812768E+10 | 0.871365E+10 | 0.938116E+10 | 0.653449E+10 | 0.284668E+10 | 0.00 | 0.00 |
February | 0.102306E+11 | 0.665662E+10 | 0.105855E+11 | 0.712017E+10 | 0.346528E+10 | 0.00 | 0.00 |
March | 0.101976E+11 | 0.612161E+10 | 0.103120E+11 | 0.649219E+10 | 0.381980E+10 | 0.00 | 0.00 |
April | 0.976248E+10 | 0.396860E+10 | 0.912205E+10 | 0.495073E+10 | 0.417132E+10 | 0.00 | 0.00 |
May | 0.945170E+10 | 0.221922E+10 | 0.807009E+10 | 0.285448E+10 | 0.521561E+10 | 0.00 | 0.00 |
June | 0.855713E+10 | 0.140906E+10 | 0.686263E+10 | 0.181534E+10 | 0.504730E+10 | 0.00 | 0.00 |
July | 0.101211E+11 | 0.129757E+10 | 0.780326E+10 | 0.249126E+10 | 0.531200E+10 | 0.00 | 0.00 |
August | 0.104065E+11 | 0.154854E+10 | 0.827770E+10 | 0.344741E+10 | 0.483030E+10 | 0.00 | 0.00 |
September | 0.981239E+10 | 0.251613E+10 | 0.844475E+10 | 0.442123E+10 | 0.402351E+10 | 0.00 | 0.00 |
October | 0.800822E+10 | 0.401376E+10 | 0.775151E+10 | 0.462035E+10 | 0.313116E+10 | 0.00 | 0.00 |
November | 0.597917E+10 | 0.558125E+10 | 0.654739E+10 | 0.410313E+10 | 0.244426E+10 | 0.00 | 0.00 |
December | 0.577312E+10 | 0.847238E+10 | 0.720517E+10 | 0.472428E+10 | 0.248089E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.106428E+12 | 0.525184E+11 | 0.100363E+12 | 0.535751E+11 | 0.467881E+11 | 0.00 | 0.00 |
Minimum of Months | 0.577312E+10 | 0.129757E+10 | 0.654739E+10 | 0.181534E+10 | 0.244426E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104065E+11 | 0.871365E+10 | 0.105855E+11 | 0.712017E+10 | 0.531200E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.493760E+09 | 0.138086E+10 | 0.814281E+09 | 0.483337E+09 | 0.330945E+09 | 0.00 | 0.00 |
February | 0.808530E+09 | 0.103343E+10 | 0.102090E+10 | 0.590858E+09 | 0.430046E+09 | 0.00 | 0.00 |
March | 0.105430E+10 | 0.915741E+09 | 0.120886E+10 | 0.684993E+09 | 0.523871E+09 | 0.00 | 0.00 |
April | 0.129979E+10 | 0.556786E+09 | 0.129755E+10 | 0.675529E+09 | 0.622018E+09 | 0.00 | 0.00 |
May | 0.167656E+10 | 0.293742E+09 | 0.145847E+10 | 0.643155E+09 | 0.815310E+09 | 0.00 | 0.00 |
June | 0.162273E+10 | 0.175467E+09 | 0.132158E+10 | 0.508531E+09 | 0.813049E+09 | 0.00 | 0.00 |
July | 0.186587E+10 | 0.158931E+09 | 0.147200E+10 | 0.622921E+09 | 0.849075E+09 | 0.00 | 0.00 |
August | 0.161215E+10 | 0.189720E+09 | 0.130952E+10 | 0.576875E+09 | 0.732650E+09 | 0.00 | 0.00 |
September | 0.124221E+10 | 0.332601E+09 | 0.111137E+10 | 0.532870E+09 | 0.578497E+09 | 0.00 | 0.00 |
October | 0.799840E+09 | 0.563321E+09 | 0.847129E+09 | 0.422034E+09 | 0.425095E+09 | 0.00 | 0.00 |
November | 0.441075E+09 | 0.837735E+09 | 0.606125E+09 | 0.307600E+09 | 0.298525E+09 | 0.00 | 0.00 |
December | 0.318241E+09 | 0.134394E+10 | 0.619228E+09 | 0.335064E+09 | 0.284165E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132351E+11 | 0.778228E+10 | 0.130870E+11 | 0.638377E+10 | 0.670324E+10 | 0.00 | 0.00 |
Minimum of Months | 0.318241E+09 | 0.158931E+09 | 0.606125E+09 | 0.307600E+09 | 0.284165E+09 | 0.00 | 0.00 |
Maximum of Months | 0.186587E+10 | 0.138086E+10 | 0.147200E+10 | 0.684993E+09 | 0.849075E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112213E+09 | 0.154224E+10 | 0.380427E+09 | 0.130149E+09 | 0.250278E+09 | 0.00 | 0.00 |
February | 0.299613E+09 | 0.110862E+10 | 0.550316E+09 | 0.206014E+09 | 0.344302E+09 | 0.00 | 0.00 |
March | 0.554636E+09 | 0.946620E+09 | 0.789866E+09 | 0.334097E+09 | 0.455769E+09 | 0.00 | 0.00 |
April | 0.883455E+09 | 0.553758E+09 | 0.980594E+09 | 0.409773E+09 | 0.570821E+09 | 0.00 | 0.00 |
May | 0.141419E+10 | 0.280768E+09 | 0.127754E+10 | 0.502510E+09 | 0.775033E+09 | 0.00 | 0.00 |
June | 0.147686E+10 | 0.167388E+09 | 0.122679E+10 | 0.441285E+09 | 0.785501E+09 | 0.00 | 0.00 |
July | 0.164591E+10 | 0.151895E+09 | 0.132300E+10 | 0.512347E+09 | 0.810657E+09 | 0.00 | 0.00 |
August | 0.128137E+10 | 0.184969E+09 | 0.106917E+10 | 0.394521E+09 | 0.674650E+09 | 0.00 | 0.00 |
September | 0.850145E+09 | 0.330286E+09 | 0.810913E+09 | 0.294067E+09 | 0.516847E+09 | 0.00 | 0.00 |
October | 0.426407E+09 | 0.572030E+09 | 0.539896E+09 | 0.172305E+09 | 0.367590E+09 | 0.00 | 0.00 |
November | 0.141912E+09 | 0.883220E+09 | 0.323835E+09 | 85826290.04 | 0.238009E+09 | 0.00 | 0.00 |
December | 56996639.49 | 0.149273E+10 | 0.291808E+09 | 79717529.27 | 0.212090E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.914370E+10 | 0.821452E+10 | 0.956416E+10 | 0.356261E+10 | 0.600155E+10 | 0.00 | 0.00 |
Minimum of Months | 56996639.49 | 0.151895E+09 | 0.291808E+09 | 79717529.27 | 0.212090E+09 | 0.00 | 0.00 |
Maximum of Months | 0.164591E+10 | 0.154224E+10 | 0.132300E+10 | 0.512347E+09 | 0.810657E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.351798E+09 | 0.366391E+09 | 0.405560E+09 | 0.282494E+09 | 0.123066E+09 | 0.00 | 0.00 |
February | 0.439444E+09 | 0.280149E+09 | 0.457623E+09 | 0.307814E+09 | 0.149809E+09 | 0.00 | 0.00 |
March | 0.438957E+09 | 0.255765E+09 | 0.445801E+09 | 0.280665E+09 | 0.165136E+09 | 0.00 | 0.00 |
April | 0.418572E+09 | 0.167342E+09 | 0.394359E+09 | 0.214026E+09 | 0.180333E+09 | 0.00 | 0.00 |
May | 0.404959E+09 | 94374927.08 | 0.348882E+09 | 0.123403E+09 | 0.225479E+09 | 0.00 | 0.00 |
June | 0.368532E+09 | 58663808.25 | 0.296682E+09 | 78479200.34 | 0.218203E+09 | 0.00 | 0.00 |
July | 0.437147E+09 | 53769622.91 | 0.337347E+09 | 0.107700E+09 | 0.229647E+09 | 0.00 | 0.00 |
August | 0.447770E+09 | 64710544.47 | 0.357857E+09 | 0.149035E+09 | 0.208822E+09 | 0.00 | 0.00 |
September | 0.421039E+09 | 0.106702E+09 | 0.365078E+09 | 0.191135E+09 | 0.173943E+09 | 0.00 | 0.00 |
October | 0.346925E+09 | 0.163394E+09 | 0.335108E+09 | 0.199743E+09 | 0.135365E+09 | 0.00 | 0.00 |
November | 0.260437E+09 | 0.223658E+09 | 0.283052E+09 | 0.177383E+09 | 0.105669E+09 | 0.00 | 0.00 |
December | 0.250987E+09 | 0.352475E+09 | 0.311488E+09 | 0.204236E+09 | 0.107252E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.458657E+10 | 0.218740E+10 | 0.433884E+10 | 0.231611E+10 | 0.202272E+10 | 0.00 | 0.00 |
Minimum of Months | 0.250987E+09 | 53769622.91 | 0.283052E+09 | 78479200.34 | 0.105669E+09 | 0.00 | 0.00 |
Maximum of Months | 0.447770E+09 | 0.366391E+09 | 0.457623E+09 | 0.307814E+09 | 0.229647E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 692581.66 | 0.476126E+09 | 58564743.59 | 0.00 | 58564743.59 | 0.00 | 0.00 |
February | 7834002.75 | 0.337299E+09 | 81254233.52 | 0.00 | 81254233.52 | 0.00 | 0.00 |
March | 24613625.56 | 0.282752E+09 | 0.110706E+09 | 4319.21 | 0.110701E+09 | 0.00 | 0.00 |
April | 79869616.54 | 0.157868E+09 | 0.140894E+09 | 1464174.14 | 0.139430E+09 | 0.00 | 0.00 |
May | 0.205195E+09 | 74045373.00 | 0.204240E+09 | 10912202.62 | 0.193328E+09 | 0.00 | 0.00 |
June | 0.265928E+09 | 43958305.00 | 0.220936E+09 | 24701429.37 | 0.196234E+09 | 0.00 | 0.00 |
July | 0.275073E+09 | 38703187.63 | 0.218249E+09 | 19264914.72 | 0.198984E+09 | 0.00 | 0.00 |
August | 0.192599E+09 | 48063178.49 | 0.165667E+09 | 3181908.07 | 0.162485E+09 | 0.00 | 0.00 |
September | 0.110684E+09 | 91878062.81 | 0.124804E+09 | 130789.97 | 0.124674E+09 | 0.00 | 0.00 |
October | 41922995.65 | 0.167166E+09 | 89399861.49 | 0.00 | 89399861.49 | 0.00 | 0.00 |
November | 6321327.17 | 0.266964E+09 | 57284547.47 | 0.00 | 57284547.47 | 0.00 | 0.00 |
December | 17346.61 | 0.456025E+09 | 49620698.88 | 0.00 | 49620698.88 | 0.00 | 0.00 |
Annual Sum or Average | 0.121075E+10 | 0.244085E+10 | 0.152162E+10 | 59659738.10 | 0.146196E+10 | 0.00 | 0.00 |
Minimum of Months | 17346.61 | 38703187.63 | 49620698.88 | 0.00 | 49620698.88 | 0.00 | 0.00 |
Maximum of Months | 0.275073E+09 | 0.476126E+09 | 0.220936E+09 | 24701429.37 | 0.198984E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.480649E+09 | 0.137325E+10 | 0.806050E+09 | 0.477286E+09 | 0.328764E+09 | 0.00 | 0.00 |
February | 0.773340E+09 | 0.101633E+10 | 0.100112E+10 | 0.569413E+09 | 0.431711E+09 | 0.00 | 0.00 |
March | 0.102430E+10 | 0.895638E+09 | 0.120257E+10 | 0.675181E+09 | 0.527388E+09 | 0.00 | 0.00 |
April | 0.134978E+10 | 0.538717E+09 | 0.135282E+10 | 0.730925E+09 | 0.621895E+09 | 0.00 | 0.00 |
May | 0.158680E+10 | 0.275845E+09 | 0.140119E+10 | 0.579692E+09 | 0.821495E+09 | 0.00 | 0.00 |
June | 0.174545E+10 | 0.168025E+09 | 0.142466E+10 | 0.601896E+09 | 0.822761E+09 | 0.00 | 0.00 |
July | 0.188012E+10 | 0.150586E+09 | 0.149066E+10 | 0.637271E+09 | 0.853385E+09 | 0.00 | 0.00 |
August | 0.155264E+10 | 0.183224E+09 | 0.127021E+10 | 0.545742E+09 | 0.724473E+09 | 0.00 | 0.00 |
September | 0.121441E+10 | 0.323738E+09 | 0.109588E+10 | 0.525791E+09 | 0.570088E+09 | 0.00 | 0.00 |
October | 0.755557E+09 | 0.556487E+09 | 0.816915E+09 | 0.399374E+09 | 0.417540E+09 | 0.00 | 0.00 |
November | 0.428449E+09 | 0.828452E+09 | 0.600688E+09 | 0.304052E+09 | 0.296637E+09 | 0.00 | 0.00 |
December | 0.325346E+09 | 0.134258E+10 | 0.623959E+09 | 0.343479E+09 | 0.280479E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.131168E+11 | 0.765287E+10 | 0.130867E+11 | 0.639010E+10 | 0.669662E+10 | 0.00 | 0.00 |
Minimum of Months | 0.325346E+09 | 0.150586E+09 | 0.600688E+09 | 0.304052E+09 | 0.280479E+09 | 0.00 | 0.00 |
Maximum of Months | 0.188012E+10 | 0.137325E+10 | 0.149066E+10 | 0.730925E+09 | 0.853385E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 86339646.41 | 0.152193E+10 | 0.372196E+09 | 0.124099E+09 | 0.248097E+09 | 0.00 | 0.00 |
February | 0.245629E+09 | 0.107275E+10 | 0.530536E+09 | 0.184569E+09 | 0.345967E+09 | 0.00 | 0.00 |
March | 0.513037E+09 | 0.913538E+09 | 0.783570E+09 | 0.324285E+09 | 0.459286E+09 | 0.00 | 0.00 |
April | 0.927457E+09 | 0.532506E+09 | 0.103587E+10 | 0.465169E+09 | 0.570698E+09 | 0.00 | 0.00 |
May | 0.132920E+10 | 0.269033E+09 | 0.122026E+10 | 0.439047E+09 | 0.781218E+09 | 0.00 | 0.00 |
June | 0.160302E+10 | 0.163998E+09 | 0.132986E+10 | 0.534650E+09 | 0.795214E+09 | 0.00 | 0.00 |
July | 0.166374E+10 | 0.147493E+09 | 0.134166E+10 | 0.526697E+09 | 0.814967E+09 | 0.00 | 0.00 |
August | 0.122252E+10 | 0.179951E+09 | 0.102986E+10 | 0.363387E+09 | 0.666474E+09 | 0.00 | 0.00 |
September | 0.818985E+09 | 0.320045E+09 | 0.795425E+09 | 0.286988E+09 | 0.508437E+09 | 0.00 | 0.00 |
October | 0.374935E+09 | 0.558289E+09 | 0.509681E+09 | 0.149645E+09 | 0.360036E+09 | 0.00 | 0.00 |
November | 0.122660E+09 | 0.867901E+09 | 0.318399E+09 | 82278208.38 | 0.236121E+09 | 0.00 | 0.00 |
December | 50369621.01 | 0.147700E+10 | 0.296539E+09 | 88133196.08 | 0.208405E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.895790E+10 | 0.802444E+10 | 0.956387E+10 | 0.356895E+10 | 0.599492E+10 | 0.00 | 0.00 |
Minimum of Months | 50369621.01 | 0.147493E+09 | 0.296539E+09 | 82278208.38 | 0.208405E+09 | 0.00 | 0.00 |
Maximum of Months | 0.166374E+10 | 0.152193E+10 | 0.134166E+10 | 0.534650E+09 | 0.814967E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.594093E+09 | 0.174481E+10 | 0.100561E+10 | 0.612085E+09 | 0.393520E+09 | 0.00 | 0.00 |
February | 0.885468E+09 | 0.130586E+10 | 0.116757E+10 | 0.666947E+09 | 0.500619E+09 | 0.00 | 0.00 |
March | 0.965011E+09 | 0.116526E+10 | 0.120575E+10 | 0.608133E+09 | 0.597620E+09 | 0.00 | 0.00 |
April | 0.107735E+10 | 0.716497E+09 | 0.115969E+10 | 0.466907E+09 | 0.692782E+09 | 0.00 | 0.00 |
May | 0.130390E+10 | 0.375761E+09 | 0.119838E+10 | 0.291019E+09 | 0.907363E+09 | 0.00 | 0.00 |
June | 0.134683E+10 | 0.235433E+09 | 0.112145E+10 | 0.223554E+09 | 0.897894E+09 | 0.00 | 0.00 |
July | 0.150640E+10 | 0.224114E+09 | 0.120374E+10 | 0.275090E+09 | 0.928647E+09 | 0.00 | 0.00 |
August | 0.136734E+10 | 0.271308E+09 | 0.113427E+10 | 0.329812E+09 | 0.804455E+09 | 0.00 | 0.00 |
September | 0.114665E+10 | 0.451613E+09 | 0.106139E+10 | 0.414420E+09 | 0.646970E+09 | 0.00 | 0.00 |
October | 0.831355E+09 | 0.726506E+09 | 0.919756E+09 | 0.432788E+09 | 0.486968E+09 | 0.00 | 0.00 |
November | 0.526901E+09 | 0.106677E+10 | 0.737393E+09 | 0.384340E+09 | 0.353052E+09 | 0.00 | 0.00 |
December | 0.403590E+09 | 0.170622E+10 | 0.782404E+09 | 0.442523E+09 | 0.339881E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.119549E+11 | 0.999015E+10 | 0.126974E+11 | 0.514762E+10 | 0.754977E+10 | 0.00 | 0.00 |
Minimum of Months | 0.403590E+09 | 0.224114E+09 | 0.737393E+09 | 0.223554E+09 | 0.339881E+09 | 0.00 | 0.00 |
Maximum of Months | 0.150640E+10 | 0.174481E+10 | 0.120575E+10 | 0.666947E+09 | 0.928647E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.492984E+09 | 0.138005E+10 | 0.814281E+09 | 0.483337E+09 | 0.330945E+09 | 0.00 | 0.00 |
February | 0.807013E+09 | 0.103126E+10 | 0.102090E+10 | 0.590858E+09 | 0.430046E+09 | 0.00 | 0.00 |
March | 0.105302E+10 | 0.912464E+09 | 0.120886E+10 | 0.684993E+09 | 0.523871E+09 | 0.00 | 0.00 |
April | 0.129680E+10 | 0.552487E+09 | 0.129755E+10 | 0.675529E+09 | 0.622018E+09 | 0.00 | 0.00 |
May | 0.167069E+10 | 0.290314E+09 | 0.145847E+10 | 0.643155E+09 | 0.815310E+09 | 0.00 | 0.00 |
June | 0.161767E+10 | 0.172235E+09 | 0.132158E+10 | 0.508531E+09 | 0.813049E+09 | 0.00 | 0.00 |
July | 0.185991E+10 | 0.155540E+09 | 0.147200E+10 | 0.622921E+09 | 0.849075E+09 | 0.00 | 0.00 |
August | 0.160725E+10 | 0.185901E+09 | 0.130952E+10 | 0.576875E+09 | 0.732650E+09 | 0.00 | 0.00 |
September | 0.123977E+10 | 0.327707E+09 | 0.111137E+10 | 0.532870E+09 | 0.578497E+09 | 0.00 | 0.00 |
October | 0.800809E+09 | 0.556931E+09 | 0.847129E+09 | 0.422034E+09 | 0.425095E+09 | 0.00 | 0.00 |
November | 0.442104E+09 | 0.833252E+09 | 0.606125E+09 | 0.307600E+09 | 0.298525E+09 | 0.00 | 0.00 |
December | 0.317482E+09 | 0.134400E+10 | 0.619228E+09 | 0.335064E+09 | 0.284165E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132055E+11 | 0.774214E+10 | 0.130870E+11 | 0.638377E+10 | 0.670324E+10 | 0.00 | 0.00 |
Minimum of Months | 0.317482E+09 | 0.155540E+09 | 0.606125E+09 | 0.307600E+09 | 0.284165E+09 | 0.00 | 0.00 |
Maximum of Months | 0.185991E+10 | 0.138005E+10 | 0.147200E+10 | 0.684993E+09 | 0.849075E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112046E+09 | 0.154169E+10 | 0.380427E+09 | 0.130149E+09 | 0.250278E+09 | 0.00 | 0.00 |
February | 0.299313E+09 | 0.110688E+10 | 0.550316E+09 | 0.206014E+09 | 0.344302E+09 | 0.00 | 0.00 |
March | 0.554297E+09 | 0.943348E+09 | 0.789866E+09 | 0.334097E+09 | 0.455769E+09 | 0.00 | 0.00 |
April | 0.883156E+09 | 0.549055E+09 | 0.980594E+09 | 0.409773E+09 | 0.570821E+09 | 0.00 | 0.00 |
May | 0.141003E+10 | 0.277330E+09 | 0.127754E+10 | 0.502510E+09 | 0.775033E+09 | 0.00 | 0.00 |
June | 0.147292E+10 | 0.164412E+09 | 0.122679E+10 | 0.441285E+09 | 0.785501E+09 | 0.00 | 0.00 |
July | 0.164142E+10 | 0.148732E+09 | 0.132300E+10 | 0.512347E+09 | 0.810657E+09 | 0.00 | 0.00 |
August | 0.127861E+10 | 0.180990E+09 | 0.106917E+10 | 0.394521E+09 | 0.674650E+09 | 0.00 | 0.00 |
September | 0.850776E+09 | 0.324512E+09 | 0.810913E+09 | 0.294067E+09 | 0.516847E+09 | 0.00 | 0.00 |
October | 0.429466E+09 | 0.564308E+09 | 0.539896E+09 | 0.172305E+09 | 0.367590E+09 | 0.00 | 0.00 |
November | 0.143388E+09 | 0.878477E+09 | 0.323835E+09 | 85826290.04 | 0.238009E+09 | 0.00 | 0.00 |
December | 56875395.87 | 0.149305E+10 | 0.291808E+09 | 79717529.27 | 0.212090E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.913229E+10 | 0.817278E+10 | 0.956416E+10 | 0.356261E+10 | 0.600155E+10 | 0.00 | 0.00 |
Minimum of Months | 56875395.87 | 0.148732E+09 | 0.291808E+09 | 79717529.27 | 0.212090E+09 | 0.00 | 0.00 |
Maximum of Months | 0.164142E+10 | 0.154169E+10 | 0.132300E+10 | 0.512347E+09 | 0.810657E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.629557E+09 | 0.700606E+09 | 0.743638E+09 | 0.517983E+09 | 0.225655E+09 | 0.00 | 0.00 |
February | 0.790476E+09 | 0.529534E+09 | 0.839102E+09 | 0.564410E+09 | 0.274692E+09 | 0.00 | 0.00 |
March | 0.793723E+09 | 0.476518E+09 | 0.817426E+09 | 0.514631E+09 | 0.302795E+09 | 0.00 | 0.00 |
April | 0.764882E+09 | 0.294353E+09 | 0.723100E+09 | 0.392440E+09 | 0.330660E+09 | 0.00 | 0.00 |
May | 0.749360E+09 | 0.150672E+09 | 0.639713E+09 | 0.226272E+09 | 0.413441E+09 | 0.00 | 0.00 |
June | 0.686492E+09 | 87914792.66 | 0.543999E+09 | 0.143900E+09 | 0.400099E+09 | 0.00 | 0.00 |
July | 0.811098E+09 | 77638123.01 | 0.618562E+09 | 0.197480E+09 | 0.421082E+09 | 0.00 | 0.00 |
August | 0.828160E+09 | 94467035.72 | 0.656170E+09 | 0.273273E+09 | 0.382897E+09 | 0.00 | 0.00 |
September | 0.776324E+09 | 0.171098E+09 | 0.669410E+09 | 0.350467E+09 | 0.318943E+09 | 0.00 | 0.00 |
October | 0.633683E+09 | 0.290379E+09 | 0.614457E+09 | 0.366251E+09 | 0.248206E+09 | 0.00 | 0.00 |
November | 0.467231E+09 | 0.426881E+09 | 0.519007E+09 | 0.325252E+09 | 0.193755E+09 | 0.00 | 0.00 |
December | 0.447269E+09 | 0.677423E+09 | 0.571148E+09 | 0.374490E+09 | 0.196658E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.837825E+10 | 0.397749E+10 | 0.795573E+10 | 0.424685E+10 | 0.370888E+10 | 0.00 | 0.00 |
Minimum of Months | 0.447269E+09 | 77638123.01 | 0.519007E+09 | 0.143900E+09 | 0.193755E+09 | 0.00 | 0.00 |
Maximum of Months | 0.828160E+09 | 0.700606E+09 | 0.839102E+09 | 0.564410E+09 | 0.421082E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 2540827.65 | 0.433814E+10 | 0.512354E+09 | 0.00 | 0.512354E+09 | 0.00 | 0.00 |
February | 46093679.20 | 0.314770E+10 | 0.710853E+09 | 0.00 | 0.710853E+09 | 0.00 | 0.00 |
March | 0.162694E+09 | 0.270336E+10 | 0.968510E+09 | 37786.62 | 0.968472E+09 | 0.00 | 0.00 |
April | 0.590517E+09 | 0.156258E+10 | 0.123261E+10 | 12809340.58 | 0.121980E+10 | 0.00 | 0.00 |
May | 0.164101E+10 | 0.763590E+09 | 0.178680E+10 | 95465502.22 | 0.169133E+10 | 0.00 | 0.00 |
June | 0.216896E+10 | 0.481151E+09 | 0.193286E+10 | 0.216101E+09 | 0.171676E+10 | 0.00 | 0.00 |
July | 0.225403E+10 | 0.438033E+09 | 0.190935E+10 | 0.168539E+09 | 0.174081E+10 | 0.00 | 0.00 |
August | 0.154463E+10 | 0.546704E+09 | 0.144934E+10 | 27836951.19 | 0.142150E+10 | 0.00 | 0.00 |
September | 0.854507E+09 | 0.960260E+09 | 0.109185E+10 | 1144217.24 | 0.109071E+10 | 0.00 | 0.00 |
October | 0.289870E+09 | 0.167397E+10 | 0.782115E+09 | 0.00 | 0.782115E+09 | 0.00 | 0.00 |
November | 35178575.34 | 0.259922E+10 | 0.501154E+09 | 0.00 | 0.501154E+09 | 0.00 | 0.00 |
December | 0.00 | 0.419283E+10 | 0.434107E+09 | 0.00 | 0.434107E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.959003E+10 | 0.234075E+11 | 0.133119E+11 | 0.521934E+09 | 0.127900E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.438033E+09 | 0.434107E+09 | 0.00 | 0.434107E+09 | 0.00 | 0.00 |
Maximum of Months | 0.225403E+10 | 0.433814E+10 | 0.193286E+10 | 0.216101E+09 | 0.174081E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1799588.04 | 0.440562E+10 | 0.512354E+09 | 0.00 | 0.512354E+09 | 0.00 | 0.00 |
February | 40537379.05 | 0.321036E+10 | 0.710853E+09 | 0.00 | 0.710853E+09 | 0.00 | 0.00 |
March | 0.149840E+09 | 0.276227E+10 | 0.968510E+09 | 37786.62 | 0.968472E+09 | 0.00 | 0.00 |
April | 0.567017E+09 | 0.159604E+10 | 0.123261E+10 | 12809340.58 | 0.121980E+10 | 0.00 | 0.00 |
May | 0.161768E+10 | 0.778479E+09 | 0.178680E+10 | 95465502.22 | 0.169133E+10 | 0.00 | 0.00 |
June | 0.214851E+10 | 0.492184E+09 | 0.193286E+10 | 0.216101E+09 | 0.171676E+10 | 0.00 | 0.00 |
July | 0.223611E+10 | 0.448171E+09 | 0.190935E+10 | 0.168539E+09 | 0.174081E+10 | 0.00 | 0.00 |
August | 0.152604E+10 | 0.560954E+09 | 0.144934E+10 | 27836951.19 | 0.142150E+10 | 0.00 | 0.00 |
September | 0.834744E+09 | 0.982441E+09 | 0.109185E+10 | 1144217.24 | 0.109071E+10 | 0.00 | 0.00 |
October | 0.272279E+09 | 0.171479E+10 | 0.782115E+09 | 0.00 | 0.782115E+09 | 0.00 | 0.00 |
November | 30765571.42 | 0.266571E+10 | 0.501154E+09 | 0.00 | 0.501154E+09 | 0.00 | 0.00 |
December | 0.00 | 0.426340E+10 | 0.434107E+09 | 0.00 | 0.434107E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.942532E+10 | 0.238804E+11 | 0.133119E+11 | 0.521934E+09 | 0.127900E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.448171E+09 | 0.434107E+09 | 0.00 | 0.434107E+09 | 0.00 | 0.00 |
Maximum of Months | 0.223611E+10 | 0.440562E+10 | 0.193286E+10 | 0.216101E+09 | 0.174081E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.596322E+09 | 0.258189E+10 | 0.117820E+10 | 0.601368E+09 | 0.576836E+09 | 0.00 | 0.00 |
February | 0.112695E+10 | 0.191211E+10 | 0.153160E+10 | 0.753955E+09 | 0.777644E+09 | 0.00 | 0.00 |
March | 0.173761E+10 | 0.167278E+10 | 0.198605E+10 | 0.999420E+09 | 0.986628E+09 | 0.00 | 0.00 |
April | 0.260759E+10 | 0.102019E+10 | 0.238857E+10 | 0.119603E+10 | 0.119254E+10 | 0.00 | 0.00 |
May | 0.341494E+10 | 0.543225E+09 | 0.262131E+10 | 0.101868E+10 | 0.160264E+10 | 0.00 | 0.00 |
June | 0.386948E+10 | 0.347558E+09 | 0.275437E+10 | 0.113647E+10 | 0.161790E+10 | 0.00 | 0.00 |
July | 0.411127E+10 | 0.309399E+09 | 0.283217E+10 | 0.116390E+10 | 0.166827E+10 | 0.00 | 0.00 |
August | 0.328680E+10 | 0.355244E+09 | 0.229996E+10 | 0.909078E+09 | 0.139088E+10 | 0.00 | 0.00 |
September | 0.242329E+10 | 0.594825E+09 | 0.189121E+10 | 0.812738E+09 | 0.107847E+10 | 0.00 | 0.00 |
October | 0.137894E+10 | 0.101342E+10 | 0.132654E+10 | 0.548999E+09 | 0.777541E+09 | 0.00 | 0.00 |
November | 0.657448E+09 | 0.152989E+10 | 0.919052E+09 | 0.386318E+09 | 0.532734E+09 | 0.00 | 0.00 |
December | 0.389561E+09 | 0.252093E+10 | 0.920464E+09 | 0.431600E+09 | 0.488864E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.256002E+11 | 0.144015E+11 | 0.226495E+11 | 0.995855E+10 | 0.126909E+11 | 0.00 | 0.00 |
Minimum of Months | 0.389561E+09 | 0.309399E+09 | 0.919052E+09 | 0.386318E+09 | 0.488864E+09 | 0.00 | 0.00 |
Maximum of Months | 0.411127E+10 | 0.258189E+10 | 0.283217E+10 | 0.119603E+10 | 0.166827E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.137674E+10 | 0.307010E+10 | 0.206861E+10 | 0.131855E+10 | 0.750052E+09 | 0.00 | 0.00 |
February | 0.192857E+10 | 0.230449E+10 | 0.237966E+10 | 0.143674E+10 | 0.942924E+09 | 0.00 | 0.00 |
March | 0.204105E+10 | 0.206762E+10 | 0.241281E+10 | 0.131003E+10 | 0.110277E+10 | 0.00 | 0.00 |
April | 0.216967E+10 | 0.127319E+10 | 0.226323E+10 | 0.100337E+10 | 0.125986E+10 | 0.00 | 0.00 |
May | 0.244757E+10 | 0.676770E+09 | 0.224094E+10 | 0.608714E+09 | 0.163223E+10 | 0.00 | 0.00 |
June | 0.243803E+10 | 0.426403E+09 | 0.204737E+10 | 0.440385E+09 | 0.160698E+10 | 0.00 | 0.00 |
July | 0.277397E+10 | 0.404624E+09 | 0.222911E+10 | 0.560471E+09 | 0.166864E+10 | 0.00 | 0.00 |
August | 0.260731E+10 | 0.490630E+09 | 0.216715E+10 | 0.705173E+09 | 0.146198E+10 | 0.00 | 0.00 |
September | 0.227200E+10 | 0.799613E+09 | 0.207831E+10 | 0.892526E+09 | 0.118578E+10 | 0.00 | 0.00 |
October | 0.170812E+10 | 0.129144E+10 | 0.183224E+10 | 0.932313E+09 | 0.899932E+09 | 0.00 | 0.00 |
November | 0.113874E+10 | 0.189443E+10 | 0.149296E+10 | 0.827946E+09 | 0.665010E+09 | 0.00 | 0.00 |
December | 0.947130E+09 | 0.300440E+10 | 0.160270E+10 | 0.953284E+09 | 0.649417E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.238489E+11 | 0.177037E+11 | 0.248151E+11 | 0.109895E+11 | 0.138256E+11 | 0.00 | 0.00 |
Minimum of Months | 0.947130E+09 | 0.404624E+09 | 0.149296E+10 | 0.440385E+09 | 0.649417E+09 | 0.00 | 0.00 |
Maximum of Months | 0.277397E+10 | 0.307010E+10 | 0.241281E+10 | 0.143674E+10 | 0.166864E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770676E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163976401.4 | 81.21 | 0.00 | 0.00 |
February | 0.696309E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -147128096.5 | 81.21 | 0.00 | 0.00 |
March | 0.770378E+10 | -0.754148E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162295730.1 | 81.21 | 0.00 | 0.00 |
April | 0.746504E+10 | -0.730858E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156458352.8 | 81.21 | 0.00 | 0.00 |
May | 0.770417E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161380840.9 | 81.21 | 0.00 | 0.00 |
June | 0.745680E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156276824.8 | 81.21 | 0.00 | 0.00 |
July | 0.771234E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161491354.0 | 81.21 | 0.00 | 0.00 |
August | 0.770432E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161524713.0 | 81.21 | 0.00 | 0.00 |
September | 0.746606E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156125742.8 | 81.21 | 0.00 | 0.00 |
October | 0.770274E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161316151.7 | 81.21 | 0.00 | 0.00 |
November | 0.744931E+10 | -0.729244E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156868532.5 | 81.21 | 0.00 | 0.00 |
December | 0.771427E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163425391.7 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907487E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190827E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696309E+10 | -0.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -163976401.4 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771427E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -147128096.5 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.129311E+12 | -0.127572E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173936E+10 | 80.10 | 0.00 | 0.00 |
February | 0.116963E+12 | -0.115408E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.155564E+10 | 79.76 | 0.00 | 0.00 |
March | 0.129473E+12 | -0.127732E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174073E+10 | 79.82 | 0.00 | 0.00 |
April | 0.125052E+12 | -0.123353E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169972E+10 | 80.28 | 0.00 | 0.00 |
May | 0.128804E+12 | -0.127035E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176916E+10 | 81.03 | 0.00 | 0.00 |
June | 0.120979E+12 | -0.119267E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.171119E+10 | 81.30 | 0.00 | 0.00 |
July | 0.120311E+12 | -0.118564E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174680E+10 | 81.27 | 0.00 | 0.00 |
August | 0.117890E+12 | -0.116157E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173259E+10 | 81.26 | 0.00 | 0.00 |
September | 0.114495E+12 | -0.112822E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167313E+10 | 81.26 | 0.00 | 0.00 |
October | 0.121420E+12 | -0.119692E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172790E+10 | 81.26 | 0.00 | 0.00 |
November | 0.122515E+12 | -0.120840E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167475E+10 | 81.32 | 0.00 | 0.00 |
December | 0.128915E+12 | -0.127177E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173892E+10 | 80.80 | 0.00 | 0.00 |
Annual Sum or Average | 0.147613E+13 | -0.145562E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205099E+11 | 80.79 | 0.00 | 0.00 |
Minimum of Months | 0.114495E+12 | -0.127732E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.176916E+10 | 79.76 | 0.00 | 0.00 |
Maximum of Months | 0.129473E+12 | -0.112822E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.155564E+10 | 81.32 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.849592E+11 | -0.834305E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152879E+10 | 58.99 | 0.00 | 0.00 |
February | 0.784796E+11 | -0.771071E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.137256E+10 | 58.99 | 0.00 | 0.00 |
March | 0.866281E+11 | -0.850856E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154253E+10 | 58.99 | 0.00 | 0.00 |
April | 0.812945E+11 | -0.797995E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.149501E+10 | 58.99 | 0.00 | 0.00 |
May | 0.798223E+11 | -0.782911E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153116E+10 | 58.99 | 0.00 | 0.00 |
June | 0.727639E+11 | -0.712943E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146961E+10 | 58.98 | 0.00 | 0.00 |
July | 0.712293E+11 | -0.697389E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149040E+10 | 58.98 | 0.00 | 0.00 |
August | 0.692249E+11 | -0.677539E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147100E+10 | 58.98 | 0.00 | 0.00 |
September | 0.673039E+11 | -0.658852E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141867E+10 | 58.99 | 0.00 | 0.00 |
October | 0.721646E+11 | -0.707002E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146438E+10 | 58.99 | 0.00 | 0.00 |
November | 0.739080E+11 | -0.724894E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141857E+10 | 58.98 | 0.00 | 0.00 |
December | 0.810434E+11 | -0.795443E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149903E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.918822E+12 | -0.901120E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.177017E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.673039E+11 | -0.850856E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.154253E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.866281E+11 | -0.658852E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.137256E+10 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.93 | 0.93 | 01-JAN-08:30 | 4389.18 | 35.74 | 234.67 | 241.50 | 3638.90 | 36.72 | 240.00 | 222.33 |
February | 265.33 | 0.93 | 0.93 | 01-FEB-08:39 | 6976.38 | 35.88 | 258.17 | 258.50 | 2924.77 | 31.96 | 258.33 | 238.33 |
March | 254.17 | 0.93 | 0.93 | 02-MAR-10:39 | 9095.85 | 33.65 | 210.17 | 322.67 | 818.19 | 22.90 | 226.17 | 270.67 |
April | 296.33 | 0.93 | 0.93 | 01-APR-07:19 | 1555.62 | 20.70 | 92.67 | 353.17 | 632.89 | 22.30 | 243.00 | 294.00 |
May | 437.50 | 0.93 | 0.93 | 01-MAY-05:49 | 1461.17 | 20.34 | 121.00 | 413.00 | 570.35 | 22.03 | 316.33 | 341.50 |
June | 401.83 | 0.93 | 0.93 | 01-JUN-04:00 | 1389.28 | 20.38 | 147.33 | 414.00 | 553.59 | 22.09 | 284.67 | 343.50 |
July | 409.17 | 0.93 | 0.93 | 01-JUL-05:10 | 1493.47 | 20.74 | 172.83 | 421.00 | 598.74 | 22.45 | 311.50 | 353.67 |
August | 352.83 | 0.93 | 0.93 | 01-AUG-07:40 | 1755.33 | 20.90 | 158.00 | 379.67 | 691.99 | 22.60 | 270.33 | 318.67 |
September | 344.17 | 0.93 | 0.93 | 01-SEP-06:10 | 3068.80 | 23.98 | 184.33 | 331.67 | 696.43 | 22.15 | 242.00 | 281.83 |
October | 299.00 | 0.93 | 0.93 | 01-OCT-06:49 | 5025.84 | 31.94 | 269.50 | 297.83 | 989.85 | 24.65 | 217.67 | 260.83 |
November | 255.50 | 0.93 | 0.93 | 01-NOV-07:00 | 3493.57 | 34.35 | 245.17 | 243.17 | 2754.80 | 34.96 | 245.67 | 214.33 |
December | 226.33 | 0.93 | 0.93 | 01-DEC-08:09 | 3213.04 | 33.79 | 210.33 | 226.50 | 2549.08 | 34.83 | 216.00 | 199.67 |
Annual Sum or Average | 3785.50 | 0.93 | 3248.87 | 26.44 | 2304.17 | 3902.67 | 1277.13 | 25.71 | 3071.67 | 3339.33 | ||
Minimum of Months | 226.33 | 0.93 | 0.93 | 1389.28 | 20.34 | 92.67 | 226.50 | 553.59 | 22.03 | 216.00 | 199.67 | |
Maximum of Months | 437.50 | 0.93 | 0.93 | 9095.85 | 35.88 | 269.50 | 421.00 | 3638.90 | 36.72 | 316.33 | 353.67 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.62 | 0.61 | 01-JAN-08:30 | 4820.98 | 35.83 | 235.83 | 248.33 | 4068.66 | 36.80 | 241.50 | 234.00 |
February | 265.33 | 0.62 | 0.61 | 01-FEB-08:39 | 7479.89 | 35.97 | 258.67 | 265.00 | 3423.47 | 31.83 | 235.83 | 250.83 |
March | 254.17 | 0.62 | 0.61 | 02-MAR-10:39 | 9606.02 | 33.83 | 212.83 | 333.50 | 1326.43 | 22.67 | 218.17 | 303.17 |
April | 296.33 | 0.62 | 0.61 | 01-APR-06:00 | 1954.68 | 20.75 | 91.00 | 368.83 | 1030.84 | 22.23 | 243.50 | 334.33 |
May | 437.50 | 0.62 | 0.61 | 01-MAY-05:30 | 1736.41 | 20.77 | 156.83 | 427.50 | 844.61 | 22.30 | 326.17 | 391.17 |
June | 401.83 | 0.62 | 0.61 | 01-JUN-04:00 | 1641.80 | 20.88 | 181.83 | 431.50 | 805.24 | 22.41 | 309.33 | 389.67 |
July | 409.17 | 0.62 | 0.61 | 01-JUL-04:00 | 1776.34 | 21.15 | 209.17 | 436.17 | 880.68 | 22.68 | 330.00 | 397.00 |
August | 352.83 | 0.62 | 0.61 | 01-AUG-07:40 | 2092.53 | 21.21 | 173.50 | 392.17 | 1027.96 | 22.76 | 287.83 | 355.17 |
September | 344.17 | 0.62 | 0.61 | 01-SEP-05:00 | 3419.30 | 24.19 | 190.50 | 342.83 | 1045.87 | 22.30 | 244.33 | 314.33 |
October | 299.00 | 0.62 | 0.61 | 01-OCT-06:40 | 5369.34 | 32.11 | 273.33 | 308.00 | 1334.12 | 24.77 | 216.33 | 282.67 |
November | 255.50 | 0.62 | 0.61 | 01-NOV-07:49 | 3802.51 | 34.44 | 245.67 | 251.50 | 3063.06 | 35.05 | 248.50 | 231.50 |
December | 226.33 | 0.62 | 0.61 | 01-DEC-07:00 | 3548.91 | 33.93 | 211.33 | 236.33 | 2882.99 | 34.94 | 216.83 | 214.00 |
Annual Sum or Average | 3785.50 | 0.62 | 3597.96 | 26.69 | 2440.50 | 4041.67 | 1624.92 | 25.83 | 3118.33 | 3697.83 | ||
Minimum of Months | 226.33 | 0.62 | 0.61 | 1641.80 | 20.75 | 91.00 | 236.33 | 805.24 | 22.23 | 216.33 | 214.00 | |
Maximum of Months | 437.50 | 0.62 | 0.61 | 9606.02 | 35.97 | 273.33 | 436.17 | 4068.66 | 36.80 | 330.00 | 397.00 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.82 | 0.80 | 01-JAN-09:09 | 437.03 | 15.15 | 0.00 | 217.33 | 199.80 | 18.59 | 0.00 | 118.50 |
February | 265.33 | 0.81 | 0.80 | 01-FEB-08:39 | 535.58 | 16.22 | 0.00 | 245.00 | 251.83 | 19.58 | 0.83 | 181.00 |
March | 254.17 | 0.81 | 0.80 | 02-MAR-10:39 | 548.63 | 16.94 | 0.00 | 321.17 | 273.58 | 20.26 | 17.67 | 235.50 |
April | 296.33 | 0.81 | 0.80 | 01-APR-07:19 | 627.63 | 17.67 | 0.00 | 367.17 | 305.25 | 20.97 | 73.00 | 313.17 |
May | 437.50 | 0.80 | 0.80 | 01-MAY-05:10 | 913.72 | 19.25 | 22.50 | 436.00 | 413.02 | 23.04 | 240.50 | 409.83 |
June | 401.83 | 0.80 | 0.80 | 01-JUN-04:49 | 1095.23 | 21.05 | 62.50 | 443.67 | 510.67 | 24.69 | 292.67 | 414.17 |
July | 409.17 | 0.80 | 0.80 | 01-JUL-04:49 | 1038.05 | 20.74 | 51.50 | 445.67 | 487.65 | 24.18 | 304.50 | 417.17 |
August | 352.83 | 0.80 | 0.80 | 01-AUG-07:40 | 856.31 | 18.79 | 7.17 | 394.33 | 395.52 | 21.93 | 193.00 | 348.83 |
September | 344.17 | 0.81 | 0.80 | 01-SEP-05:00 | 647.34 | 17.21 | 0.00 | 336.17 | 293.36 | 20.38 | 24.17 | 268.17 |
October | 299.00 | 0.81 | 0.80 | 01-OCT-06:00 | 550.09 | 16.16 | 0.00 | 288.83 | 238.74 | 19.38 | 0.00 | 194.00 |
November | 255.50 | 0.82 | 0.80 | 01-NOV-07:00 | 431.11 | 14.91 | 0.00 | 225.00 | 187.66 | 18.18 | 0.00 | 111.17 |
December | 226.33 | 0.82 | 0.80 | 01-DEC-08:50 | 412.51 | 14.85 | 0.00 | 202.33 | 181.36 | 18.21 | 0.00 | 77.17 |
Annual Sum or Average | 3785.50 | 0.81 | 721.54 | 17.82 | 143.67 | 3922.67 | 333.31 | 21.21 | 1146.33 | 3088.67 | ||
Minimum of Months | 226.33 | 0.80 | 0.80 | 412.51 | 14.85 | 0.00 | 202.33 | 181.36 | 18.18 | 0.00 | 77.17 | |
Maximum of Months | 437.50 | 0.82 | 0.80 | 1095.23 | 21.05 | 62.50 | 445.67 | 510.67 | 24.69 | 304.50 | 417.17 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.82 | 0.80 | 01-JAN-09:09 | 437.03 | 15.15 | 0.00 | 217.33 | 199.80 | 18.59 | 0.00 | 118.50 |
February | 265.33 | 0.81 | 0.80 | 01-FEB-08:39 | 535.58 | 16.22 | 0.00 | 245.00 | 251.83 | 19.58 | 0.83 | 181.00 |
March | 254.17 | 0.81 | 0.80 | 02-MAR-10:39 | 548.63 | 16.94 | 0.00 | 321.17 | 273.58 | 20.26 | 17.67 | 235.50 |
April | 296.33 | 0.81 | 0.80 | 01-APR-07:19 | 627.63 | 17.67 | 0.00 | 367.17 | 305.25 | 20.97 | 73.00 | 313.17 |
May | 437.50 | 0.80 | 0.80 | 01-MAY-05:10 | 913.72 | 19.25 | 22.50 | 436.00 | 413.02 | 23.04 | 240.50 | 409.83 |
June | 401.83 | 0.80 | 0.80 | 01-JUN-04:49 | 1095.23 | 21.05 | 62.50 | 443.67 | 510.67 | 24.69 | 292.67 | 414.17 |
July | 409.17 | 0.80 | 0.80 | 01-JUL-04:49 | 1038.05 | 20.74 | 51.50 | 445.67 | 487.65 | 24.18 | 304.33 | 417.17 |
August | 352.83 | 0.80 | 0.80 | 01-AUG-07:40 | 856.31 | 18.79 | 7.17 | 394.33 | 395.52 | 21.93 | 193.00 | 348.83 |
September | 344.17 | 0.81 | 0.80 | 01-SEP-05:00 | 647.34 | 17.21 | 0.00 | 336.17 | 293.36 | 20.38 | 24.17 | 268.17 |
October | 299.00 | 0.81 | 0.80 | 01-OCT-06:00 | 550.09 | 16.16 | 0.00 | 288.83 | 238.74 | 19.38 | 0.00 | 194.00 |
November | 255.50 | 0.82 | 0.80 | 01-NOV-07:00 | 431.11 | 14.91 | 0.00 | 225.00 | 187.66 | 18.18 | 0.00 | 111.17 |
December | 226.33 | 0.82 | 0.80 | 01-DEC-08:50 | 412.51 | 14.85 | 0.00 | 202.33 | 181.36 | 18.21 | 0.00 | 77.17 |
Annual Sum or Average | 3785.50 | 0.81 | 721.54 | 17.82 | 143.67 | 3922.67 | 333.31 | 21.21 | 1146.17 | 3088.67 | ||
Minimum of Months | 226.33 | 0.80 | 0.80 | 412.51 | 14.85 | 0.00 | 202.33 | 181.36 | 18.18 | 0.00 | 77.17 | |
Maximum of Months | 437.50 | 0.82 | 0.80 | 1095.23 | 21.05 | 62.50 | 445.67 | 510.67 | 24.69 | 304.33 | 417.17 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.459995E+12 | 490206.07 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244014E+12 | 483313.22 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132166E+12 | 469728.51 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252956E+11 | 129142.83 | 15-APR-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158847E+11 | 126042.66 | 06-MAY-00:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.714807E+10 | 122936.19 | 17-JUN-00:28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.321186E+10 | 132079.82 | 02-JUL-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.313145E+10 | 100346.95 | 19-AUG-01:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.211853E+11 | 191958.45 | 06-SEP-23:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.329376E+11 | 135175.98 | 23-OCT-23:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.595265E+11 | 137418.58 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.394786E+12 | 476586.08 | 24-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139928E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.313145E+10 | 100346.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.459995E+12 | 490206.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.165522E+10 | 10091.67 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 57946284.81 | 3480.22 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18149409.99 | 2226.26 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71043857.17 | 3629.92 | 25-DEC-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.165522E+10 | 10091.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.688941E+10 | 6406.07 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.400258E+10 | 6288.60 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.314262E+10 | 5779.27 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146730E+10 | 2131.67 | 25-APR-17:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.288295E+09 | 1891.34 | 31-MAY-02:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143883E+09 | 1781.54 | 14-JUN-03:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 25904243.85 | 1883.17 | 10-JUL-05:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 86001050.11 | 2039.92 | 19-AUG-01:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.378326E+09 | 2423.46 | 30-SEP-01:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161278E+10 | 2443.70 | 30-OCT-17:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.325019E+10 | 3087.85 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.663494E+10 | 6175.72 | 24-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 25904243.85 | 1781.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.688941E+10 | 6406.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.143986E+10 | 2443.31 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.517133E+09 | 2250.46 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190886E+09 | 1619.51 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2240034.99 | 203.35 | 04-APR-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1503921.90 | 143.80 | 30-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103093E+09 | 596.49 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113824E+10 | 2161.17 | 24-DEC-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.339295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.143986E+10 | 2443.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.393412E+10 | 3864.73 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.225771E+10 | 3294.30 | 14-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148845E+10 | 2484.56 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.239936E+09 | 874.21 | 05-APR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1707843.24 | 302.00 | 01-MAY-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 65097066.28 | 582.61 | 15-OCT-15:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.890778E+09 | 1213.30 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.337958E+10 | 3258.10 | 25-DEC-02:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.393412E+10 | 3864.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.267923E+10 | 2105.03 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164086E+10 | 1942.39 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117489E+10 | 1529.59 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.257857E+09 | 567.63 | 05-APR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5292414.73 | 236.43 | 01-MAY-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116349E+09 | 506.07 | 30-OCT-17:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.811091E+09 | 861.37 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.237101E+10 | 1950.00 | 25-DEC-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.905659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.267923E+10 | 2105.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.599161E+10 | 14537.69 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.206274E+10 | 14280.34 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.816776E+09 | 13715.17 | 05-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46603873.21 | 9201.31 | 24-APR-01:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22715905.65 | 8603.49 | 31-MAY-02:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 51919557.21 | 8803.33 | 14-JUN-03:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17013745.33 | 7297.94 | 18-JUL-01:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19344296.98 | 7690.04 | 19-AUG-01:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81578720.26 | 11838.64 | 05-SEP-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 59461847.00 | 8321.75 | 02-OCT-01:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136242E+09 | 5120.14 | 21-NOV-01:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.422022E+10 | 14032.59 | 24-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 17013745.33 | 5120.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.599161E+10 | 14537.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107983E+11 | 17906.87 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.410915E+10 | 17545.84 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226754E+10 | 13740.74 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.463123E+09 | 3846.66 | 27-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5561555.03 | 1780.13 | 09-MAY-10:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1195964.47 | 1209.07 | 09-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9658279.04 | 1363.66 | 15-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 40930098.23 | 5366.21 | 22-SEP-08:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.689152E+09 | 5533.66 | 31-OCT-08:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.218943E+10 | 5870.83 | 24-NOV-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.959253E+10 | 17272.33 | 24-DEC-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107983E+11 | 17906.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.187228E+11 | 45353.13 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.528792E+10 | 43668.19 | 14-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150950E+10 | 26463.44 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 262612.31 | 262.23 | 30-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.715526E+09 | 9158.63 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142047E+11 | 39896.41 | 24-DEC-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.404408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.187228E+11 | 45353.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.206450E+11 | 22287.62 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105655E+11 | 20632.27 | 14-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.620370E+10 | 15735.66 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.726964E+09 | 4328.70 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116669E+10 | 5979.74 | 31-OCT-08:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.676869E+10 | 8136.96 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190861E+11 | 20226.83 | 24-DEC-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.651625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.206450E+11 | 22287.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.139897E+11 | 13741.51 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.782669E+10 | 13010.89 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.500140E+10 | 10438.26 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104825E+10 | 3482.99 | 05-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17848714.70 | 1124.64 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.103935E+10 | 3384.15 | 30-OCT-17:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.447716E+10 | 5037.81 | 25-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126477E+11 | 12555.40 | 24-DEC-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.460481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139897E+11 | 13741.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.418742E+10 | 17900.17 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.811045E+09 | 14010.26 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 87788675.80 | 5630.73 | 05-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.236116E+10 | 14212.93 | 20-DEC-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.744742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.418742E+10 | 17900.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.397266E+10 | 18443.02 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.701863E+09 | 13957.32 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 69552781.48 | 5167.70 | 05-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.206081E+10 | 13968.00 | 20-DEC-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.680489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.397266E+10 | 18443.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.304168E+10 | 12368.62 | 06-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107319E+10 | 12099.34 | 14-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352722E+09 | 11564.48 | 05-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 237112.46 | 790.37 | 26-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 341491.73 | 1138.31 | 22-OCT-02:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199522E+10 | 11992.95 | 24-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.646339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.304168E+10 | 12368.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.577763E+11 | 59422.61 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.312162E+11 | 58514.14 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169366E+11 | 56736.81 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179057E+10 | 10724.69 | 05-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33792337.41 | 2622.73 | 01-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23866.36 | 0.46 | 28-JUN-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21627.87 | 0.46 | 16-JUL-10:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26467.19 | 0.47 | 11-AUG-00:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15651.22 | 0.44 | 07-SEP-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.757660E+09 | 8307.42 | 30-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.841080E+10 | 15790.04 | 29-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.503452E+11 | 57631.86 | 24-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167267E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 15651.22 | 0.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.577763E+11 | 59422.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.117412E+11 | 14569.27 | 17-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.718854E+10 | 14568.32 | 18-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.508421E+10 | 14568.45 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171776E+10 | 14567.44 | 04-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125575E+09 | 10250.90 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21296292.79 | 3497.23 | 11-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3358522.81 | 2977.49 | 09-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 25407191.29 | 2743.32 | 28-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.224159E+09 | 12060.01 | 28-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.204520E+10 | 14565.57 | 30-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.536189E+10 | 14568.92 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114732E+11 | 14568.82 | 07-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.450117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3358522.81 | 2743.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117412E+11 | 14569.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136218E+11 | 14390.15 | 17-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.878267E+10 | 14389.16 | 18-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.628239E+10 | 14389.23 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.213842E+10 | 14388.23 | 04-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158649E+09 | 12583.76 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19890471.63 | 3400.93 | 02-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3522433.47 | 3207.97 | 15-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28543693.28 | 3017.44 | 21-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.293951E+09 | 13443.46 | 28-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.249366E+10 | 14386.40 | 30-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.624408E+10 | 14389.80 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129115E+11 | 14389.70 | 07-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.529792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3522433.47 | 3017.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136218E+11 | 14390.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.391783E+11 | 57947.50 | 09-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154756E+11 | 53353.51 | 17-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.694015E+10 | 47238.52 | 05-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17209353.11 | 2734.45 | 04-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173459E+09 | 6089.36 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.954449E+10 | 27261.11 | 25-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.406639E+11 | 56554.85 | 24-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111993E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.406639E+11 | 57947.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.712391E+11 | 76972.84 | 12-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.439261E+11 | 76965.95 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.295415E+11 | 76963.21 | 07-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.641847E+10 | 75822.41 | 05-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.208265E+09 | 24763.48 | 07-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30290136.32 | 21453.07 | 02-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20455382.33 | 18512.23 | 08-JUL-18:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 45999664.42 | 24711.18 | 07-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126576E+09 | 26723.58 | 10-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.511410E+10 | 75688.49 | 30-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.228530E+11 | 76970.30 | 28-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.636446E+11 | 76976.44 | 07-DEC-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243169E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 20455382.33 | 18512.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.712391E+11 | 76976.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.117283E+11 | 14223.92 | 17-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.716428E+10 | 14222.95 | 18-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.504293E+10 | 14223.09 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164598E+10 | 14141.09 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142924E+09 | 4083.29 | 20-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10582480.49 | 2878.53 | 02-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2042112.58 | 1923.33 | 08-JUL-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 21385983.86 | 3156.47 | 31-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.253157E+09 | 11359.98 | 28-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.213170E+10 | 14120.70 | 30-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.539576E+10 | 14223.61 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114343E+11 | 14223.51 | 07-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.449733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2042112.58 | 1923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117283E+11 | 14223.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136341E+11 | 14025.91 | 17-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.881758E+10 | 14024.88 | 18-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.626224E+10 | 14025.04 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.201325E+10 | 13981.18 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.184498E+09 | 4057.69 | 20-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10921672.76 | 2532.54 | 02-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2525202.96 | 2247.17 | 09-JUL-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 24503866.04 | 3029.88 | 31-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.332315E+09 | 12558.23 | 28-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.260572E+10 | 13997.67 | 30-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.626141E+10 | 14025.59 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128854E+11 | 14025.41 | 07-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.530345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2525202.96 | 2247.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136341E+11 | 14025.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.385141E+10 | 4266.25 | 17-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.243968E+10 | 4265.84 | 18-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.178258E+10 | 4265.94 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.684327E+09 | 4265.67 | 04-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86578199.23 | 3849.27 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22360681.63 | 919.78 | 03-JUN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2459479.57 | 827.57 | 22-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18074411.43 | 850.87 | 07-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145990E+09 | 4039.32 | 28-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.823011E+09 | 4265.12 | 30-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187405E+10 | 4266.16 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.376446E+10 | 4266.10 | 07-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2459479.57 | 827.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.385141E+10 | 4266.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.438076E+10 | 4199.25 | 17-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.291876E+10 | 4198.82 | 18-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.215679E+10 | 4198.93 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.832861E+09 | 4198.63 | 04-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103905E+09 | 4100.35 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22319801.36 | 918.69 | 03-JUN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2604639.17 | 845.25 | 22-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19517507.22 | 844.71 | 27-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.193537E+09 | 3981.62 | 28-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.986399E+09 | 4198.06 | 30-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215027E+10 | 4199.12 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.416691E+10 | 4199.09 | 07-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2604639.17 | 844.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.438076E+10 | 4199.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.134281E+11 | 20442.57 | 17-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.774230E+10 | 20441.37 | 18-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.555878E+10 | 20441.54 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198996E+10 | 20349.85 | 04-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.220441E+09 | 7869.17 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 47078337.07 | 5488.42 | 29-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8828255.31 | 4710.44 | 25-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32318642.69 | 4686.99 | 19-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.256287E+09 | 15061.63 | 28-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.218583E+10 | 20416.17 | 30-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.590717E+10 | 20442.18 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135855E+11 | 20441.95 | 07-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.509626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8828255.31 | 4686.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135855E+11 | 20442.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3064782.52 | 3064782.52 | 1530.89 | 19-JAN-06:20 | 1530.89 | 0.00 |
February | 0.00 | 0.00 | 66508632.19 | 66508632.19 | 9670.01 | 21-FEB-12:26 | 9670.01 | 0.00 |
March | 0.00 | 0.00 | 0.132392E+09 | 0.132392E+09 | 13301.12 | 29-MAR-18:02 | 13301.12 | 0.00 |
April | 0.00 | 0.00 | 0.137219E+11 | 0.137219E+11 | 184309.34 | 23-APR-18:10 | 184309.34 | 0.02 |
May | 0.00 | 0.00 | 0.104816E+12 | 0.102182E+12 | 288154.16 | 25-MAY-18:07 | 235655.22 | 0.26 |
June | 0.00 | 0.00 | 0.273797E+12 | 0.191608E+12 | 489061.48 | 27-JUN-19:50 | 216141.35 | 0.60 |
July | 0.00 | 0.00 | 0.383689E+12 | 0.247432E+12 | 506988.45 | 21-JUL-19:30 | 206695.02 | 0.84 |
August | 0.00 | 0.00 | 0.261848E+12 | 0.182301E+12 | 466196.74 | 31-AUG-19:10 | 207311.39 | 0.80 |
September | 0.00 | 0.00 | 0.591455E+11 | 0.508356E+11 | 257574.02 | 01-SEP-10:50 | 166278.05 | 0.23 |
October | 0.00 | 0.00 | 0.865124E+10 | 0.865124E+10 | 134259.68 | 19-OCT-15:03 | 134259.68 | 0.02 |
November | 0.00 | 0.00 | 0.131481E+10 | 0.131481E+10 | 53522.25 | 01-NOV-15:30 | 53522.25 | 0.01 |
December | 0.00 | 0.00 | 17323470.05 | 17323470.05 | 5299.59 | 05-DEC-19:07 | 5299.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.110720E+13 | 0.798266E+12 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 3064782.52 | 3064782.52 | 1530.89 | 1530.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.383689E+12 | 0.247432E+12 | 506988.45 | 235655.22 | 0.84 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.220258E+10 | 0.220258E+10 | 28339.06 | 23-APR-18:00 | 28339.06 | 0.02 |
May | 0.00 | 0.00 | 0.180784E+11 | 0.173026E+11 | 41200.12 | 26-MAY-09:30 | 24202.75 | 0.26 |
June | 0.00 | 0.00 | 0.472590E+11 | 0.325465E+11 | 64248.31 | 19-JUN-17:30 | 26412.76 | 0.56 |
July | 0.00 | 0.00 | 0.662562E+11 | 0.420267E+11 | 67702.20 | 04-JUL-02:50 | 23107.30 | 0.82 |
August | 0.00 | 0.00 | 0.468520E+11 | 0.314665E+11 | 57885.44 | 30-AUG-08:50 | 24525.22 | 0.77 |
September | 0.00 | 0.00 | 0.106541E+11 | 0.878652E+10 | 41432.39 | 01-SEP-10:30 | 25771.47 | 0.20 |
October | 0.00 | 0.00 | 0.144276E+10 | 0.144276E+10 | 24823.26 | 19-OCT-15:00 | 24823.26 | 0.01 |
November | 0.00 | 0.00 | 0.223311E+09 | 0.223311E+09 | 12274.36 | 01-NOV-15:00 | 12274.36 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.192968E+12 | 0.135998E+12 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.662562E+11 | 0.420267E+11 | 67702.20 | 28339.06 | 0.82 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8048998.02 | 8048998.02 | 4707.38 | 31-JAN-16:03 | 4707.38 | 0.00 |
February | 0.00 | 0.00 | 0.166043E+09 | 0.166043E+09 | 15184.14 | 28-FEB-16:02 | 15184.14 | 0.00 |
March | 0.00 | 0.00 | 0.638566E+09 | 0.638566E+09 | 15200.58 | 28-MAR-18:01 | 15200.58 | 0.00 |
April | 0.00 | 0.00 | 0.226576E+10 | 0.218882E+10 | 15818.93 | 13-APR-15:02 | 15818.93 | 0.03 |
May | 0.00 | 0.00 | 0.599108E+10 | 0.473202E+10 | 16243.84 | 21-MAY-15:02 | 16243.84 | 0.42 |
June | 0.00 | 0.00 | 0.757757E+10 | 0.495931E+10 | 19519.47 | 19-JUN-18:02 | 13046.95 | 0.75 |
July | 0.00 | 0.00 | 0.101108E+11 | 0.613519E+10 | 19279.38 | 23-JUL-08:62 | 13586.29 | 0.92 |
August | 0.00 | 0.00 | 0.793568E+10 | 0.459543E+10 | 18419.53 | 30-AUG-08:62 | 12583.43 | 0.86 |
September | 0.00 | 0.00 | 0.379408E+10 | 0.259131E+10 | 17204.47 | 18-SEP-18:02 | 13162.79 | 0.51 |
October | 0.00 | 0.00 | 0.111000E+10 | 0.945847E+09 | 15849.24 | 21-OCT-15:02 | 15849.24 | 0.09 |
November | 0.00 | 0.00 | 37994652.24 | 37262279.90 | 15156.73 | 17-NOV-16:01 | 15156.73 | 0.00 |
December | 0.00 | 0.00 | 8406495.11 | 8406495.11 | 3390.38 | 05-DEC-19:04 | 3390.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.396440E+11 | 0.270063E+11 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 8048998.02 | 8048998.02 | 3390.38 | 3390.38 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101108E+11 | 0.613519E+10 | 19519.47 | 16243.84 | 0.92 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6072970.24 | 6072970.24 | 3036.34 | 16-JAN-09:04 | 3036.34 | 0.00 |
February | 0.00 | 0.00 | 33720419.68 | 33720419.68 | 12965.58 | 22-FEB-16:01 | 12965.58 | 0.00 |
March | 0.00 | 0.00 | 0.256128E+09 | 0.256128E+09 | 14441.85 | 28-MAR-18:01 | 14441.85 | 0.00 |
April | 0.00 | 0.00 | 0.137472E+10 | 0.131420E+10 | 15028.11 | 13-APR-15:02 | 15028.11 | 0.02 |
May | 0.00 | 0.00 | 0.503985E+10 | 0.389469E+10 | 15616.87 | 23-MAY-15:02 | 15153.82 | 0.41 |
June | 0.00 | 0.00 | 0.699659E+10 | 0.458607E+10 | 18245.83 | 25-JUN-08:62 | 13072.77 | 0.73 |
July | 0.00 | 0.00 | 0.917153E+10 | 0.547076E+10 | 18400.00 | 30-JUL-08:62 | 13081.02 | 0.90 |
August | 0.00 | 0.00 | 0.654664E+10 | 0.359455E+10 | 17229.61 | 30-AUG-08:62 | 11950.30 | 0.83 |
September | 0.00 | 0.00 | 0.247348E+10 | 0.161336E+10 | 16284.38 | 18-SEP-18:02 | 12351.06 | 0.42 |
October | 0.00 | 0.00 | 0.415143E+09 | 0.364197E+09 | 15057.65 | 21-OCT-15:02 | 15057.65 | 0.04 |
November | 0.00 | 0.00 | 18429204.84 | 17575499.90 | 6147.22 | 21-NOV-16:03 | 4171.40 | 0.00 |
December | 0.00 | 0.00 | 6346305.34 | 6346305.34 | 3004.32 | 05-DEC-19:04 | 3004.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.323386E+11 | 0.211577E+11 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 6072970.24 | 6072970.24 | 3004.32 | 3004.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.917153E+10 | 0.547076E+10 | 18400.00 | 15153.82 | 0.90 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 20150665.99 | 20150665.99 | 4782.39 | 27-JAN-15:10 | 4782.39 | 0.00 |
February | 0.00 | 0.00 | 0.103361E+10 | 0.103361E+10 | 27275.68 | 22-FEB-14:30 | 27275.68 | 0.00 |
March | 0.00 | 0.00 | 0.239396E+10 | 0.239396E+10 | 37122.40 | 20-MAR-12:30 | 37122.40 | 0.00 |
April | 0.00 | 0.00 | 0.105106E+11 | 0.102417E+11 | 45932.63 | 22-APR-13:00 | 45932.63 | 0.02 |
May | 0.00 | 0.00 | 0.199001E+11 | 0.153370E+11 | 45951.22 | 18-MAY-14:00 | 42210.49 | 0.26 |
June | 0.00 | 0.00 | 0.233532E+11 | 0.142941E+11 | 52712.93 | 30-JUN-14:00 | 42143.59 | 0.50 |
July | 0.00 | 0.00 | 0.339515E+11 | 0.177732E+11 | 52994.81 | 23-JUL-14:20 | 41414.75 | 0.80 |
August | 0.00 | 0.00 | 0.309438E+11 | 0.174849E+11 | 54132.91 | 25-AUG-13:10 | 40184.61 | 0.73 |
September | 0.00 | 0.00 | 0.208610E+11 | 0.174213E+11 | 54646.13 | 01-SEP-13:20 | 41295.07 | 0.24 |
October | 0.00 | 0.00 | 0.108937E+11 | 0.106118E+11 | 69884.14 | 22-OCT-12:15 | 69096.96 | 0.03 |
November | 0.00 | 0.00 | 0.701114E+09 | 0.701114E+09 | 27223.12 | 17-NOV-13:30 | 27223.12 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.154563E+12 | 0.107313E+12 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.339515E+11 | 0.177732E+11 | 69884.14 | 69096.96 | 0.80 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 30182333.38 | 30182333.38 | 33997.95 | 19-JAN-19:04 | 33997.95 | 0.00 |
February | 0.00 | 0.00 | 54714030.21 | 54714030.21 | 38800.31 | 21-FEB-19:03 | 38800.31 | 0.00 |
March | 0.00 | 0.00 | 0.281771E+09 | 0.281771E+09 | 38165.50 | 28-MAR-18:01 | 38165.50 | 0.00 |
April | 0.00 | 0.00 | 0.474627E+10 | 0.444747E+10 | 66886.58 | 23-APR-18:01 | 66886.58 | 0.03 |
May | 0.00 | 0.00 | 0.285358E+11 | 0.232584E+11 | 75196.95 | 25-MAY-15:02 | 68735.61 | 0.33 |
June | 0.00 | 0.00 | 0.439516E+11 | 0.306618E+11 | 88894.32 | 25-JUN-08:62 | 60413.16 | 0.60 |
July | 0.00 | 0.00 | 0.521515E+11 | 0.333047E+11 | 88705.63 | 30-JUL-08:62 | 59877.90 | 0.72 |
August | 0.00 | 0.00 | 0.396282E+11 | 0.229394E+11 | 81055.92 | 07-AUG-18:02 | 60943.35 | 0.71 |
September | 0.00 | 0.00 | 0.184010E+11 | 0.109900E+11 | 74246.09 | 18-SEP-18:02 | 52926.10 | 0.55 |
October | 0.00 | 0.00 | 0.316562E+10 | 0.240631E+10 | 61969.85 | 01-OCT-18:02 | 61969.85 | 0.11 |
November | 0.00 | 0.00 | 0.342895E+09 | 0.206272E+09 | 43101.37 | 20-NOV-16:03 | 43101.37 | 0.02 |
December | 0.00 | 0.00 | 34757529.08 | 34757529.08 | 29903.77 | 06-DEC-19:04 | 29903.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.191324E+12 | 0.128616E+12 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 30182333.38 | 30182333.38 | 29903.77 | 29903.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.521515E+11 | 0.333047E+11 | 88894.32 | 68735.61 | 0.72 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 9115506.75 | 9115506.75 | 2948.02 | 21-JAN-09:04 | 2948.02 | 0.00 |
February | 0.00 | 0.00 | 80485757.81 | 80485757.81 | 12896.53 | 28-FEB-16:02 | 12896.53 | 0.00 |
March | 0.00 | 0.00 | 0.426993E+09 | 0.426993E+09 | 13783.72 | 26-MAR-15:02 | 13783.72 | 0.00 |
April | 0.00 | 0.00 | 0.231747E+10 | 0.225216E+10 | 14346.62 | 13-APR-15:02 | 14346.62 | 0.03 |
May | 0.00 | 0.00 | 0.565721E+10 | 0.443912E+10 | 14731.86 | 21-MAY-15:02 | 14731.86 | 0.43 |
June | 0.00 | 0.00 | 0.816232E+10 | 0.552143E+10 | 17725.33 | 19-JUN-18:02 | 11828.58 | 0.78 |
July | 0.00 | 0.00 | 0.101838E+11 | 0.624166E+10 | 17103.76 | 22-JUL-08:61 | 12304.97 | 0.95 |
August | 0.00 | 0.00 | 0.769894E+10 | 0.443795E+10 | 16875.18 | 30-AUG-08:62 | 12139.04 | 0.88 |
September | 0.00 | 0.00 | 0.374730E+10 | 0.259225E+10 | 15158.89 | 18-SEP-18:02 | 10946.55 | 0.51 |
October | 0.00 | 0.00 | 0.101087E+10 | 0.847620E+09 | 14374.86 | 21-OCT-15:02 | 14374.86 | 0.09 |
November | 0.00 | 0.00 | 92548647.27 | 91697752.99 | 10856.07 | 17-NOV-16:01 | 10856.07 | 0.00 |
December | 0.00 | 0.00 | 8734441.66 | 8734441.66 | 3132.16 | 05-DEC-19:04 | 3132.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.393958E+11 | 0.269492E+11 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 8734441.66 | 8734441.66 | 2948.02 | 2948.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101838E+11 | 0.624166E+10 | 17725.33 | 14731.86 | 0.95 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 5990347.19 | 5990347.19 | 2974.99 | 19-JAN-19:04 | 2974.99 | 0.00 |
February | 0.00 | 0.00 | 12437203.83 | 12437203.83 | 5193.59 | 20-FEB-09:03 | 5193.59 | 0.00 |
March | 0.00 | 0.00 | 0.121430E+09 | 0.121430E+09 | 12188.23 | 26-MAR-08:61 | 12188.23 | 0.00 |
April | 0.00 | 0.00 | 0.126996E+10 | 0.122903E+10 | 13602.34 | 13-APR-15:02 | 13602.34 | 0.02 |
May | 0.00 | 0.00 | 0.465763E+10 | 0.355387E+10 | 14359.93 | 25-MAY-15:02 | 13603.18 | 0.43 |
June | 0.00 | 0.00 | 0.753923E+10 | 0.506715E+10 | 16234.29 | 19-JUN-18:02 | 11559.48 | 0.77 |
July | 0.00 | 0.00 | 0.921204E+10 | 0.552946E+10 | 16245.55 | 22-JUL-08:61 | 11650.70 | 0.94 |
August | 0.00 | 0.00 | 0.627425E+10 | 0.341321E+10 | 16132.12 | 31-AUG-15:02 | 12581.39 | 0.87 |
September | 0.00 | 0.00 | 0.236676E+10 | 0.151920E+10 | 14321.89 | 18-SEP-18:02 | 10216.08 | 0.43 |
October | 0.00 | 0.00 | 0.312762E+09 | 0.254975E+09 | 12970.09 | 21-OCT-15:02 | 12970.09 | 0.04 |
November | 0.00 | 0.00 | 20249472.34 | 19358862.95 | 6260.38 | 21-NOV-16:03 | 4551.05 | 0.00 |
December | 0.00 | 0.00 | 5922600.51 | 5922600.51 | 3226.18 | 05-DEC-19:04 | 3226.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.317987E+11 | 0.207320E+11 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 5922600.51 | 5922600.51 | 2974.99 | 2974.99 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.921204E+10 | 0.552946E+10 | 16245.55 | 13603.18 | 0.94 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 834634.68 | 834634.68 | 1312.19 | 17-JAN-16:03 | 1312.19 | 0.00 |
February | 0.00 | 0.00 | 38381653.41 | 38381653.41 | 3950.69 | 28-FEB-16:02 | 3950.69 | 0.00 |
March | 0.00 | 0.00 | 0.159402E+09 | 0.159402E+09 | 3954.94 | 28-MAR-18:01 | 3954.94 | 0.00 |
April | 0.00 | 0.00 | 0.552065E+09 | 0.535287E+09 | 4115.76 | 13-APR-15:02 | 4115.76 | 0.03 |
May | 0.00 | 0.00 | 0.146002E+10 | 0.116711E+10 | 4317.06 | 26-MAY-08:62 | 3732.07 | 0.40 |
June | 0.00 | 0.00 | 0.185627E+10 | 0.123242E+10 | 5231.72 | 19-JUN-18:02 | 3301.16 | 0.71 |
July | 0.00 | 0.00 | 0.248012E+10 | 0.151740E+10 | 5276.31 | 30-JUL-08:62 | 3436.93 | 0.90 |
August | 0.00 | 0.00 | 0.188992E+10 | 0.111968E+10 | 4930.40 | 30-AUG-08:62 | 3068.56 | 0.84 |
September | 0.00 | 0.00 | 0.833329E+09 | 0.597800E+09 | 4531.17 | 18-SEP-18:02 | 3377.91 | 0.41 |
October | 0.00 | 0.00 | 0.251994E+09 | 0.220836E+09 | 4123.75 | 21-OCT-15:02 | 4123.75 | 0.06 |
November | 0.00 | 0.00 | 6770580.78 | 6535260.72 | 3950.49 | 17-NOV-16:01 | 3950.49 | 0.00 |
December | 0.00 | 0.00 | 405020.09 | 405020.09 | 383.37 | 28-DEC-16:04 | 383.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.952951E+10 | 0.659609E+10 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 405020.09 | 405020.09 | 383.37 | 383.37 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.248012E+10 | 0.151740E+10 | 5276.31 | 4123.75 | 0.90 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 376793.91 | 376793.91 | 472.27 | 17-JAN-16:04 | 472.27 | 0.00 |
February | 0.00 | 0.00 | 4367250.25 | 4367250.25 | 1600.32 | 04-FEB-19:03 | 1600.32 | 0.00 |
March | 0.00 | 0.00 | 58301296.54 | 58301296.54 | 3740.74 | 28-MAR-18:01 | 3740.74 | 0.00 |
April | 0.00 | 0.00 | 0.327368E+09 | 0.314432E+09 | 3892.79 | 13-APR-15:02 | 3892.79 | 0.02 |
May | 0.00 | 0.00 | 0.120864E+10 | 0.940618E+09 | 4059.60 | 26-MAY-08:62 | 3532.71 | 0.39 |
June | 0.00 | 0.00 | 0.169743E+10 | 0.112580E+10 | 4891.99 | 25-JUN-08:62 | 3285.95 | 0.69 |
July | 0.00 | 0.00 | 0.222742E+10 | 0.133625E+10 | 5030.69 | 30-JUL-08:62 | 3227.51 | 0.89 |
August | 0.00 | 0.00 | 0.151749E+10 | 0.851068E+09 | 4600.77 | 30-AUG-08:62 | 2899.66 | 0.80 |
September | 0.00 | 0.00 | 0.508828E+09 | 0.355749E+09 | 4266.29 | 18-SEP-18:02 | 3146.57 | 0.30 |
October | 0.00 | 0.00 | 86936601.79 | 78660747.14 | 3900.22 | 21-OCT-15:02 | 3900.22 | 0.02 |
November | 0.00 | 0.00 | 2998205.38 | 2754683.43 | 1738.74 | 15-NOV-19:03 | 1738.74 | 0.00 |
December | 0.00 | 0.00 | 156125.28 | 156125.28 | 319.83 | 28-DEC-16:04 | 319.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.764030E+10 | 0.506853E+10 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 156125.28 | 156125.28 | 319.83 | 319.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.222742E+10 | 0.133625E+10 | 5030.69 | 3900.22 | 0.89 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.510652E+09 | 0.510652E+09 | 19212.97 | 27-JAN-16:01 | 19212.97 | 0.00 |
February | 0.00 | 0.00 | 0.151652E+10 | 0.151652E+10 | 19250.24 | 21-FEB-16:02 | 19250.24 | 0.00 |
March | 0.00 | 0.00 | 0.212182E+10 | 0.212182E+10 | 19248.64 | 26-MAR-15:02 | 19248.64 | 0.00 |
April | 0.00 | 0.00 | 0.399165E+10 | 0.389646E+10 | 20137.31 | 23-APR-18:01 | 20137.31 | 0.03 |
May | 0.00 | 0.00 | 0.729723E+10 | 0.569455E+10 | 21057.44 | 25-MAY-18:02 | 20080.36 | 0.42 |
June | 0.00 | 0.00 | 0.902627E+10 | 0.562785E+10 | 26335.75 | 19-JUN-18:02 | 15473.65 | 0.74 |
July | 0.00 | 0.00 | 0.121569E+11 | 0.714872E+10 | 25636.66 | 30-JUL-08:62 | 16792.04 | 0.90 |
August | 0.00 | 0.00 | 0.109763E+11 | 0.655264E+10 | 24210.64 | 07-AUG-18:02 | 17306.25 | 0.86 |
September | 0.00 | 0.00 | 0.674804E+10 | 0.488604E+10 | 21492.82 | 18-SEP-18:02 | 15423.17 | 0.57 |
October | 0.00 | 0.00 | 0.353817E+10 | 0.317377E+10 | 20073.20 | 21-OCT-15:02 | 20073.20 | 0.16 |
November | 0.00 | 0.00 | 0.100398E+10 | 0.999727E+09 | 19235.86 | 16-NOV-16:01 | 19235.86 | 0.00 |
December | 0.00 | 0.00 | 0.258314E+09 | 0.258314E+09 | 19087.45 | 02-DEC-16:01 | 19087.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.591459E+11 | 0.423871E+11 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.258314E+09 | 0.258314E+09 | 19087.45 | 15423.17 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.121569E+11 | 0.714872E+10 | 26335.75 | 20137.31 | 0.90 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 295739.60 | 922354.78 | 06-JAN-09:03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 172360.20 | 840413.38 | 14-FEB-07:03 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 88774.01 | 771264.71 | 05-MAR-05:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 18600.79 | 244064.46 | 02-APR-08:61 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6444.20 | 121100.19 | 20-MAY-22:35 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 2886.98 | 206398.61 | 16-JUN-23:43 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1212.65 | 123928.93 | 02-JUL-04:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 1287.12 | 102550.70 | 19-AUG-01:09 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 8953.16 | 194928.07 | 15-SEP-00:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21034.09 | 250673.18 | 30-OCT-08:61 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 58323.84 | 320389.59 | 25-NOV-09:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 258979.99 | 844035.07 | 21-DEC-09:03 |
Annual Sum or Average | 0.00 | 77716.85 | ||||
Minimum of Months | 0.00 | 0.00 | 1212.65 | 102550.70 | ||
Maximum of Months | 0.00 | 0.00 | 295739.60 | 922354.78 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 489.85 | 44773.77 | 19-JAN-19:04 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 2124.19 | 64416.93 | 08-FEB-16:04 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 3673.38 | 84272.82 | 26-MAR-15:03 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 19348.51 | 371473.14 | 23-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 79747.09 | 498029.69 | 25-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 170671.33 | 679557.62 | 29-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 225263.96 | 670607.75 | 21-JUL-19:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 161889.38 | 596129.82 | 08-AUG-15:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 53821.32 | 447474.03 | 01-SEP-18:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 13853.87 | 281308.17 | 21-OCT-15:02 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2554.32 | 76225.99 | 01-NOV-15:07 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 373.89 | 63570.12 | 06-DEC-09:04 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 61631.17 | 0.00 | ||||
Minimum of Months | 373.89 | 44773.77 | 0.00 | 0.00 | ||
Maximum of Months | 225263.96 | 679557.62 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 32705.24 | 67620.69 | 31-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 33428.35 | 68310.07 | 24-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 33321.56 | 68290.86 | 02-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 32325.75 | 76329.00 | 18-APR-20:31 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30763.56 | 74679.17 | 01-MAY-20:11 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 29053.10 | 68703.37 | 03-JUN-07:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27588.76 | 62030.21 | 18-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 26848.25 | 60976.53 | 02-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26938.76 | 67873.65 | 26-SEP-06:41 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27930.91 | 65027.97 | 10-OCT-20:31 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 29524.64 | 64859.75 | 21-NOV-07:15 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 31256.99 | 65021.74 | 29-DEC-07:10 |
Annual Sum or Average | 0.00 | 30120.92 | ||||
Minimum of Months | 0.00 | 0.00 | 26848.25 | 60976.53 | ||
Maximum of Months | 0.00 | 0.00 | 33428.35 | 76329.00 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 0.92 | 2194.93 | 01-JAN-00:03 | 0.92 |
February | 0.530997E+10 | 0.92 | 2194.93 | 01-FEB-00:03 | 0.92 |
March | 0.587890E+10 | 0.92 | 2194.93 | 01-MAR-00:03 | 0.92 |
April | 0.568926E+10 | 0.92 | 2194.93 | 01-APR-00:10 | 0.92 |
May | 0.587890E+10 | 0.91 | 2194.93 | 01-MAY-00:05 | 0.92 |
June | 0.568926E+10 | 0.91 | 2194.93 | 01-JUN-00:05 | 0.91 |
July | 0.587890E+10 | 0.91 | 2194.93 | 01-JUL-00:10 | 0.91 |
August | 0.587890E+10 | 0.91 | 2194.93 | 01-AUG-00:05 | 0.91 |
September | 0.568926E+10 | 0.91 | 2194.93 | 01-SEP-00:05 | 0.91 |
October | 0.587890E+10 | 0.91 | 2194.93 | 01-OCT-00:10 | 0.91 |
November | 0.568926E+10 | 0.92 | 2194.93 | 01-NOV-00:05 | 0.92 |
December | 0.587890E+10 | 0.92 | 2194.93 | 01-DEC-00:03 | 0.92 |
Annual Sum or Average | 0.692193E+11 | 0.91 | |||
Minimum of Months | 0.530997E+10 | 0.91 | 2194.93 | 0.91 | |
Maximum of Months | 0.587890E+10 | 0.92 | 2194.93 | 0.92 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.294408E+11 | 0.76 | 16861.20 | 19-JAN-21:10 | 0.96 |
February | 0.278663E+11 | 0.78 | 26220.92 | 04-FEB-13:45 | 1.25 |
March | 0.321722E+11 | 0.79 | 33817.54 | 31-MAR-20:35 | 1.46 |
April | 0.335884E+11 | 0.83 | 37272.12 | 19-APR-13:25 | 1.56 |
May | 0.379824E+11 | 0.86 | 36747.07 | 04-MAY-23:25 | 1.54 |
June | 0.375275E+11 | 0.87 | 36747.07 | 02-JUN-21:53 | 1.53 |
July | 0.392725E+11 | 0.87 | 36747.07 | 02-JUL-02:07 | 1.53 |
August | 0.389491E+11 | 0.87 | 37989.10 | 18-AUG-21:57 | 1.56 |
September | 0.378574E+11 | 0.87 | 43345.80 | 05-SEP-21:26 | 1.70 |
October | 0.375282E+11 | 0.86 | 43345.80 | 20-OCT-21:05 | 1.70 |
November | 0.322710E+11 | 0.81 | 37989.10 | 02-NOV-00:43 | 1.57 |
December | 0.299190E+11 | 0.77 | 17906.93 | 05-DEC-21:10 | 0.99 |
Annual Sum or Average | 0.414375E+12 | 0.83 | |||
Minimum of Months | 0.278663E+11 | 0.76 | 16861.20 | 0.96 | |
Maximum of Months | 0.392725E+11 | 0.87 | 43345.80 | 1.70 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:03 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:03 | 0.28 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:03 | 0.28 |
April | 0.198586E+09 | 0.28 | 76.61 | 01-APR-00:10 | 0.28 |
May | 0.205205E+09 | 0.28 | 76.61 | 01-MAY-00:05 | 0.28 |
June | 0.198586E+09 | 0.28 | 76.61 | 01-JUN-00:05 | 0.28 |
July | 0.205205E+09 | 0.28 | 76.61 | 01-JUL-00:10 | 0.28 |
August | 0.205205E+09 | 0.28 | 76.61 | 01-AUG-00:05 | 0.27 |
September | 0.198586E+09 | 0.28 | 76.61 | 01-SEP-00:05 | 0.27 |
October | 0.205205E+09 | 0.28 | 76.61 | 01-OCT-00:10 | 0.28 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:05 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:03 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.28 | |||
Minimum of Months | 0.185347E+09 | 0.28 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.20 | 612.92 | 01-JAN-07:10 | 0.28 |
February | 0.105030E+10 | 0.20 | 612.92 | 01-FEB-07:05 | 0.28 |
March | 0.116283E+10 | 0.20 | 612.92 | 01-MAR-07:05 | 0.28 |
April | 0.112532E+10 | 0.20 | 612.92 | 01-APR-06:05 | 0.28 |
May | 0.116283E+10 | 0.20 | 612.92 | 01-MAY-06:05 | 0.28 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.28 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:05 | 0.28 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.20 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.20 | 612.92 | 01-OCT-06:10 | 0.28 |
November | 0.112532E+10 | 0.20 | 612.92 | 01-NOV-06:10 | 0.28 |
December | 0.116283E+10 | 0.20 | 612.92 | 01-DEC-07:05 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.20 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.20 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.467009E+09 | 0.55 | 902.78 | 01-JAN-09:01 | 0.60 |
February | 0.315604E+09 | 0.49 | 902.78 | 01-FEB-09:01 | 0.60 |
March | 0.283137E+09 | 0.47 | 902.78 | 01-MAR-09:01 | 0.60 |
April | 0.246426E+09 | 0.47 | 902.78 | 02-APR-08:61 | 0.60 |
May | 0.373650E+09 | 0.52 | 902.78 | 01-MAY-15:02 | 0.60 |
June | 0.419886E+09 | 0.53 | 902.78 | 01-JUN-15:02 | 0.60 |
July | 0.521805E+09 | 0.55 | 902.78 | 01-JUL-08:62 | 0.60 |
August | 0.421420E+09 | 0.53 | 902.78 | 01-AUG-15:02 | 0.60 |
September | 0.254321E+09 | 0.50 | 902.78 | 01-SEP-08:62 | 0.59 |
October | 0.199134E+09 | 0.46 | 902.78 | 01-OCT-15:02 | 0.60 |
November | 0.264073E+09 | 0.48 | 902.78 | 01-NOV-08:62 | 0.60 |
December | 0.458024E+09 | 0.57 | 902.78 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.422449E+10 | 0.51 | |||
Minimum of Months | 0.199134E+09 | 0.46 | 902.78 | 0.59 | |
Maximum of Months | 0.521805E+09 | 0.57 | 902.78 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.526691E+09 | 0.59 | 857.09 | 01-JAN-09:01 | 0.60 |
February | 0.353341E+09 | 0.55 | 857.09 | 01-FEB-09:01 | 0.60 |
March | 0.296845E+09 | 0.51 | 857.09 | 01-MAR-09:01 | 0.60 |
April | 0.208421E+09 | 0.45 | 857.09 | 01-APR-18:01 | 0.60 |
May | 0.319531E+09 | 0.50 | 857.09 | 01-MAY-15:02 | 0.60 |
June | 0.389613E+09 | 0.51 | 857.09 | 01-JUN-15:02 | 0.60 |
July | 0.476702E+09 | 0.54 | 857.09 | 01-JUL-08:62 | 0.60 |
August | 0.351550E+09 | 0.51 | 857.09 | 01-AUG-15:02 | 0.60 |
September | 0.181580E+09 | 0.46 | 857.09 | 01-SEP-15:02 | 0.60 |
October | 0.173552E+09 | 0.44 | 857.09 | 01-OCT-15:02 | 0.60 |
November | 0.287525E+09 | 0.51 | 857.09 | 01-NOV-08:62 | 0.60 |
December | 0.496332E+09 | 0.59 | 857.09 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.406168E+10 | 0.51 | |||
Minimum of Months | 0.173552E+09 | 0.44 | 857.09 | 0.60 | |
Maximum of Months | 0.526691E+09 | 0.59 | 857.09 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.175382E+10 | 0.48 | 3018.26 | 09-JAN-05:00 | 0.61 |
February | 0.789267E+09 | 0.27 | 1725.88 | 17-FEB-06:00 | 0.61 |
March | 0.519334E+09 | 0.20 | 1694.23 | 20-MAR-12:30 | 0.60 |
April | 0.562664E+09 | 0.15 | 2673.64 | 23-APR-12:40 | 0.60 |
May | 0.108810E+10 | 0.36 | 2582.76 | 18-MAY-13:00 | 0.60 |
June | 0.114913E+10 | 0.39 | 2437.34 | 30-JUN-12:40 | 0.60 |
July | 0.155767E+10 | 0.47 | 2490.16 | 24-JUL-12:50 | 0.60 |
August | 0.148101E+10 | 0.44 | 2811.11 | 13-AUG-13:20 | 0.60 |
September | 0.114889E+10 | 0.29 | 3260.34 | 04-SEP-11:10 | 0.60 |
October | 0.643357E+09 | 0.12 | 5403.29 | 22-OCT-12:00 | 0.60 |
November | 0.586908E+09 | 0.25 | 1321.71 | 17-NOV-13:30 | 0.60 |
December | 0.186222E+10 | 0.53 | 1795.47 | 24-DEC-06:00 | 0.61 |
Annual Sum or Average | 0.131424E+11 | 0.33 | |||
Minimum of Months | 0.519334E+09 | 0.12 | 1321.71 | 0.60 | |
Maximum of Months | 0.186222E+10 | 0.53 | 5403.29 | 0.61 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.278224E+10 | 0.52 | 3945.97 | 01-JAN-09:01 | 0.61 |
February | 0.169475E+10 | 0.48 | 3945.97 | 01-FEB-09:01 | 0.60 |
March | 0.123211E+10 | 0.44 | 3945.97 | 01-MAR-09:01 | 0.60 |
April | 0.688026E+09 | 0.43 | 3945.97 | 02-APR-15:02 | 0.60 |
May | 0.167651E+10 | 0.42 | 3945.97 | 01-MAY-18:02 | 0.60 |
June | 0.230695E+10 | 0.43 | 3945.97 | 01-JUN-08:62 | 0.60 |
July | 0.255008E+10 | 0.43 | 3945.97 | 01-JUL-08:62 | 0.60 |
August | 0.189224E+10 | 0.42 | 3945.97 | 01-AUG-15:02 | 0.60 |
September | 0.106064E+10 | 0.42 | 3945.97 | 01-SEP-08:62 | 0.59 |
October | 0.572749E+09 | 0.42 | 3945.97 | 01-OCT-08:61 | 0.60 |
November | 0.102332E+10 | 0.43 | 3945.97 | 02-NOV-15:01 | 0.60 |
December | 0.247409E+10 | 0.52 | 3945.97 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.199537E+11 | 0.45 | |||
Minimum of Months | 0.572749E+09 | 0.42 | 3945.97 | 0.59 | |
Maximum of Months | 0.278224E+10 | 0.52 | 3945.97 | 0.61 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.448017E+09 | 0.56 | 817.45 | 01-JAN-09:01 | 0.60 |
February | 0.288492E+09 | 0.48 | 817.45 | 01-FEB-09:01 | 0.60 |
March | 0.250934E+09 | 0.47 | 817.45 | 01-MAR-09:01 | 0.60 |
April | 0.235090E+09 | 0.49 | 817.45 | 01-APR-18:01 | 0.60 |
May | 0.345533E+09 | 0.54 | 817.45 | 01-MAY-08:62 | 0.60 |
June | 0.443022E+09 | 0.55 | 817.45 | 01-JUN-08:62 | 0.60 |
July | 0.512581E+09 | 0.57 | 817.45 | 01-JUL-08:62 | 0.60 |
August | 0.398351E+09 | 0.54 | 817.45 | 01-AUG-08:62 | 0.59 |
September | 0.253568E+09 | 0.50 | 817.45 | 01-SEP-08:62 | 0.60 |
October | 0.187982E+09 | 0.46 | 817.45 | 01-OCT-08:61 | 0.60 |
November | 0.250908E+09 | 0.48 | 817.45 | 01-NOV-08:62 | 0.60 |
December | 0.433775E+09 | 0.57 | 817.45 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.404825E+10 | 0.52 | |||
Minimum of Months | 0.187982E+09 | 0.46 | 817.45 | 0.59 | |
Maximum of Months | 0.512581E+09 | 0.57 | 817.45 | 0.60 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.510573E+09 | 0.59 | 774.34 | 01-JAN-09:01 | 0.60 |
February | 0.334306E+09 | 0.55 | 774.34 | 01-FEB-09:01 | 0.60 |
March | 0.268671E+09 | 0.50 | 774.34 | 01-MAR-09:01 | 0.60 |
April | 0.188027E+09 | 0.46 | 774.34 | 01-APR-18:01 | 0.60 |
May | 0.293220E+09 | 0.52 | 774.34 | 01-MAY-08:62 | 0.60 |
June | 0.413712E+09 | 0.55 | 774.34 | 01-JUN-08:62 | 0.60 |
July | 0.466975E+09 | 0.56 | 774.34 | 01-JUL-08:62 | 0.60 |
August | 0.328089E+09 | 0.53 | 774.34 | 01-AUG-08:62 | 0.59 |
September | 0.178551E+09 | 0.47 | 774.34 | 01-SEP-08:62 | 0.59 |
October | 0.162023E+09 | 0.43 | 774.34 | 01-OCT-08:61 | 0.60 |
November | 0.269942E+09 | 0.52 | 774.34 | 01-NOV-08:62 | 0.60 |
December | 0.474146E+09 | 0.59 | 774.34 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.388824E+10 | 0.52 | |||
Minimum of Months | 0.162023E+09 | 0.43 | 774.34 | 0.59 | |
Maximum of Months | 0.510573E+09 | 0.59 | 774.34 | 0.60 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140997E+09 | 0.58 | 235.03 | 01-JAN-09:01 | 0.60 |
February | 93928209.19 | 0.52 | 235.03 | 01-FEB-09:01 | 0.60 |
March | 84596824.27 | 0.50 | 235.03 | 01-MAR-09:01 | 0.60 |
April | 69692476.02 | 0.48 | 235.03 | 01-APR-18:01 | 0.60 |
May | 94602374.71 | 0.52 | 235.03 | 01-MAY-15:02 | 0.60 |
June | 0.105031E+09 | 0.52 | 235.03 | 01-JUN-15:02 | 0.60 |
July | 0.129664E+09 | 0.55 | 235.03 | 01-JUL-08:62 | 0.60 |
August | 0.102495E+09 | 0.53 | 235.03 | 01-AUG-15:02 | 0.60 |
September | 61887891.12 | 0.49 | 235.03 | 01-SEP-15:02 | 0.60 |
October | 59717849.34 | 0.47 | 235.03 | 01-OCT-15:02 | 0.60 |
November | 80511527.89 | 0.51 | 235.03 | 01-NOV-08:62 | 0.60 |
December | 0.136654E+09 | 0.58 | 235.03 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.115978E+10 | 0.52 | |||
Minimum of Months | 59717849.34 | 0.47 | 235.03 | 0.60 | |
Maximum of Months | 0.140997E+09 | 0.58 | 235.03 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.159506E+09 | 0.59 | 222.13 | 01-JAN-09:01 | 0.60 |
February | 0.105823E+09 | 0.57 | 222.13 | 01-FEB-09:01 | 0.60 |
March | 88422885.18 | 0.53 | 222.13 | 01-MAR-09:01 | 0.60 |
April | 60991922.76 | 0.47 | 222.13 | 01-APR-18:01 | 0.60 |
May | 80985050.32 | 0.49 | 222.13 | 01-MAY-08:62 | 0.60 |
June | 96914381.26 | 0.51 | 222.13 | 01-JUN-15:02 | 0.60 |
July | 0.117570E+09 | 0.54 | 222.13 | 01-JUL-08:62 | 0.60 |
August | 83972369.31 | 0.50 | 222.13 | 01-AUG-15:02 | 0.60 |
September | 45239741.66 | 0.46 | 222.13 | 01-SEP-15:02 | 0.60 |
October | 54571422.26 | 0.46 | 222.13 | 01-OCT-15:02 | 0.60 |
November | 86817042.12 | 0.55 | 222.13 | 01-NOV-08:62 | 0.60 |
December | 0.148866E+09 | 0.59 | 222.13 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.112968E+10 | 0.52 | |||
Minimum of Months | 45239741.66 | 0.46 | 222.13 | 0.60 | |
Maximum of Months | 0.159506E+09 | 0.59 | 222.13 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.537178E+09 | 0.52 | 1137.81 | 01-JAN-09:01 | 0.60 |
February | 0.397659E+09 | 0.51 | 1137.81 | 01-FEB-09:01 | 0.60 |
March | 0.377165E+09 | 0.49 | 1137.81 | 01-MAR-09:01 | 0.60 |
April | 0.349769E+09 | 0.50 | 1137.81 | 02-APR-08:61 | 0.60 |
May | 0.433462E+09 | 0.52 | 1137.81 | 01-MAY-15:02 | 0.60 |
June | 0.471605E+09 | 0.52 | 1137.81 | 01-JUN-15:02 | 0.60 |
July | 0.588622E+09 | 0.54 | 1137.81 | 01-JUL-08:62 | 0.60 |
August | 0.552422E+09 | 0.52 | 1137.81 | 01-AUG-15:02 | 0.60 |
September | 0.416414E+09 | 0.50 | 1137.81 | 01-SEP-08:62 | 0.59 |
October | 0.349787E+09 | 0.46 | 1137.81 | 01-OCT-08:61 | 0.60 |
November | 0.331896E+09 | 0.48 | 1137.81 | 02-NOV-15:01 | 0.60 |
December | 0.527954E+09 | 0.54 | 1137.81 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.533393E+10 | 0.51 | |||
Minimum of Months | 0.331896E+09 | 0.46 | 1137.81 | 0.59 | |
Maximum of Months | 0.588622E+09 | 0.54 | 1137.81 | 0.60 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.281882E+10 | 0.253694E+10 | 2026.09 | 06-JAN-09:02 | 1823.48 | 1823.48 | 48.97 | 6.46 |
February | 0.180281E+10 | 0.162253E+10 | 1900.95 | 14-FEB-07:07 | 1710.86 | 1710.86 | 49.35 | 6.09 |
March | 0.132125E+10 | 0.118912E+10 | 1790.49 | 05-MAR-05:00 | 1611.44 | 1611.44 | 49.63 | 5.66 |
April | 0.420271E+09 | 0.378244E+09 | 884.43 | 02-APR-08:61 | 795.99 | 795.99 | 32.41 | 1.18 |
May | 0.106126E+09 | 95513309.00 | 540.04 | 09-MAY-06:18 | 486.04 | 486.04 | 52.59 | 0.63 |
June | 40674268.26 | 36606841.43 | 835.88 | 16-JUN-23:43 | 752.29 | 752.29 | 34.68 | 1.09 |
July | 17186339.36 | 15467705.42 | 542.40 | 02-JUL-04:50 | 488.16 | 488.16 | 33.43 | 0.64 |
August | 20973583.53 | 18876225.18 | 566.74 | 19-AUG-01:12 | 510.07 | 510.07 | 44.23 | 0.67 |
September | 0.150796E+09 | 0.135716E+09 | 873.71 | 15-SEP-00:10 | 786.34 | 786.34 | 39.67 | 1.15 |
October | 0.495735E+09 | 0.446161E+09 | 940.12 | 25-OCT-23:34 | 846.11 | 846.11 | 52.69 | 1.27 |
November | 0.110568E+10 | 0.995111E+09 | 1209.99 | 25-NOV-09:01 | 1088.99 | 1088.99 | 42.69 | 1.91 |
December | 0.267061E+10 | 0.240355E+10 | 1893.43 | 24-DEC-06:00 | 1704.09 | 1704.09 | 48.95 | 6.07 |
Annual Sum or Average | 0.109709E+11 | 0.987383E+10 | ||||||
Minimum of Months | 17186339.36 | 15467705.42 | 540.04 | 486.04 | 486.04 | 32.41 | 0.63 | |
Maximum of Months | 0.281882E+10 | 0.253694E+10 | 2026.09 | 1823.48 | 1823.48 | 52.69 | 6.46 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 328944.18 | 296049.76 | 54.82 | 30-JAN-09:04 | 49.34 | 49.34 | 8.40 | 3.64 |
February | 2259693.20 | 2033723.88 | 67.61 | 08-FEB-16:04 | 60.85 | 60.85 | 8.40 | 4.08 |
March | 5644434.12 | 5079990.71 | 115.35 | 31-MAR-15:02 | 103.81 | 103.81 | 8.40 | 5.40 |
April | 55695853.46 | 50126268.11 | 811.50 | 23-APR-19:20 | 730.35 | 730.35 | 7.32 | 13.61 |
May | 0.337447E+09 | 0.303702E+09 | 1174.64 | 15-MAY-18:03 | 1057.17 | 1057.17 | 7.36 | 15.98 |
June | 0.742025E+09 | 0.667823E+09 | 2294.88 | 29-JUN-18:03 | 2065.40 | 2065.40 | 6.73 | 21.20 |
July | 0.106593E+10 | 0.959340E+09 | 2494.16 | 21-JUL-19:30 | 2244.74 | 2244.74 | 7.23 | 21.94 |
August | 0.713570E+09 | 0.642213E+09 | 1824.01 | 31-AUG-19:10 | 1641.61 | 1641.61 | 7.16 | 19.26 |
September | 0.178954E+09 | 0.161059E+09 | 1023.56 | 01-SEP-18:02 | 921.20 | 921.20 | 7.20 | 15.06 |
October | 37311266.01 | 33580139.41 | 839.22 | 19-OCT-15:50 | 755.30 | 755.30 | 7.47 | 13.81 |
November | 2477421.88 | 2229679.69 | 64.29 | 17-NOV-16:04 | 57.86 | 57.86 | 8.40 | 3.97 |
December | 201290.51 | 181161.46 | 57.95 | 06-DEC-09:04 | 52.16 | 52.16 | 8.40 | 3.75 |
Annual Sum or Average | 0.314185E+10 | 0.282766E+10 | ||||||
Minimum of Months | 201290.51 | 181161.46 | 54.82 | 49.34 | 49.34 | 6.73 | 3.64 | |
Maximum of Months | 0.106593E+10 | 0.959340E+09 | 2494.16 | 2244.74 | 2244.74 | 8.40 | 21.94 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.795817E+09 | 0.716235E+09 | 4682.85 | 01-JAN-09:04 | 4214.56 | 4214.56 | 8.42 | 32.82 |
February | 0.236534E+10 | 0.212881E+10 | 4682.85 | 01-FEB-10:50 | 4214.56 | 4214.56 | 8.41 | 32.82 |
March | 0.360371E+10 | 0.324334E+10 | 4682.85 | 01-MAR-00:03 | 4214.56 | 4214.56 | 8.40 | 32.82 |
April | 0.759597E+10 | 0.683637E+10 | 4682.85 | 01-APR-01:07 | 4214.56 | 4214.56 | 8.40 | 32.82 |
May | 0.119414E+11 | 0.107473E+11 | 4682.85 | 01-MAY-00:10 | 4214.56 | 4214.56 | 8.40 | 32.82 |
June | 0.120248E+11 | 0.108223E+11 | 4682.85 | 01-JUN-00:05 | 4214.56 | 4214.56 | 8.46 | 32.82 |
July | 0.125229E+11 | 0.112706E+11 | 4682.85 | 01-JUL-00:10 | 4214.56 | 4214.56 | 8.90 | 32.82 |
August | 0.123852E+11 | 0.111467E+11 | 4682.85 | 01-AUG-00:05 | 4214.56 | 4214.56 | 8.77 | 32.82 |
September | 0.109773E+11 | 0.987958E+10 | 4682.85 | 01-SEP-00:05 | 4214.56 | 4214.56 | 9.44 | 32.82 |
October | 0.691040E+10 | 0.621936E+10 | 4682.85 | 01-OCT-00:10 | 4214.56 | 4214.56 | 8.45 | 32.82 |
November | 0.317431E+10 | 0.285687E+10 | 4682.85 | 01-NOV-00:10 | 4214.56 | 4214.56 | 8.40 | 32.82 |
December | 0.725574E+09 | 0.653017E+09 | 4682.85 | 01-DEC-09:03 | 4214.56 | 4214.56 | 8.43 | 32.82 |
Annual Sum or Average | 0.850227E+11 | 0.765205E+11 | ||||||
Minimum of Months | 0.725574E+09 | 0.653017E+09 | 4682.85 | 4214.56 | 4214.56 | 8.40 | 32.82 | |
Maximum of Months | 0.125229E+11 | 0.112706E+11 | 4682.85 | 4214.56 | 4214.56 | 9.44 | 32.82 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:03 | 14.37 | 14.37 | 45.78 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 46.57 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 46.59 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 49.90 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 50.49 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 50.72 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 51.02 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 51.77 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 51.62 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 50.68 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 51.21 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 47.50 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 45.78 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 51.77 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 48.17 | 82.20 | 295739.60 | 922354.78 | 06-JAN-09:03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 48.51 | 82.20 | 172360.20 | 840413.38 | 14-FEB-07:03 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 62.60 | 81.30 | 88774.01 | 771264.71 | 05-MAR-05:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 68.95 | 80.49 | 18600.79 | 244064.46 | 02-APR-08:61 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 68.36 | 81.08 | 6444.20 | 121100.19 | 20-MAY-22:35 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 37.06 | 79.40 | 2886.98 | 206398.61 | 16-JUN-23:43 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.45 | 52.45 | 1212.65 | 123928.93 | 02-JUL-04:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 39.36 | 39.36 | 1287.12 | 102550.70 | 19-AUG-01:09 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 51.72 | 51.72 | 8953.16 | 194928.07 | 15-SEP-00:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 43.21 | 79.82 | 21034.09 | 250673.18 | 30-OCT-08:61 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 65.86 | 80.48 | 58323.84 | 320389.59 | 25-NOV-09:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 54.06 | 82.20 | 258979.99 | 844035.07 | 21-DEC-09:03 |
Annual Sum or Average | 0.00 | 77716.85 | ||||||
Minimum of Months | 0.00 | 0.00 | 37.06 | 39.36 | 1212.65 | 102550.70 | ||
Maximum of Months | 0.00 | 0.00 | 68.95 | 82.20 | 295739.60 | 922354.78 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 489.85 | 44773.77 | 19-JAN-19:04 | 8.70 | 8.37 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 2124.19 | 64416.93 | 08-FEB-16:04 | 8.84 | 8.37 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 3673.38 | 84272.82 | 26-MAR-15:03 | 8.98 | 8.37 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 19348.51 | 371473.14 | 23-APR-18:03 | 9.62 | 6.92 | 0.00 | 0.00 | 01-APR-00:10 |
May | 79747.09 | 498029.69 | 25-MAY-18:03 | 10.32 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 170671.33 | 679557.62 | 29-JUN-18:03 | 11.64 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 225263.96 | 670607.75 | 21-JUL-19:30 | 12.09 | 7.21 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 161889.38 | 596129.82 | 08-AUG-15:03 | 11.04 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 53821.32 | 447474.03 | 01-SEP-18:03 | 10.50 | 7.25 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 13853.87 | 281308.17 | 21-OCT-15:02 | 9.75 | 7.71 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2554.32 | 76225.99 | 01-NOV-15:07 | 8.53 | 7.98 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 373.89 | 63570.12 | 06-DEC-09:04 | 8.83 | 8.37 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 61631.17 | 0.00 | ||||||
Minimum of Months | 373.89 | 44773.77 | 8.53 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 225263.96 | 679557.62 | 12.09 | 8.37 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 45.78 | 59.76 | 32705.24 | 67620.69 | 31-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 46.57 | 58.93 | 33428.35 | 68310.07 | 24-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 46.59 | 59.64 | 33321.56 | 68290.86 | 02-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 49.90 | 58.69 | 32325.75 | 76329.00 | 18-APR-20:31 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 50.49 | 59.78 | 30763.56 | 74679.17 | 01-MAY-20:11 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 50.72 | 59.22 | 29053.10 | 68703.37 | 03-JUN-07:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 51.02 | 58.36 | 27588.76 | 62030.21 | 18-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 51.77 | 59.58 | 26848.25 | 60976.53 | 02-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 51.62 | 59.24 | 26938.76 | 67873.65 | 26-SEP-06:41 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 50.68 | 58.83 | 27930.91 | 65027.97 | 10-OCT-20:31 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 51.21 | 59.29 | 29524.64 | 64859.75 | 21-NOV-07:15 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 47.50 | 58.38 | 31256.99 | 65021.74 | 29-DEC-07:10 |
Annual Sum or Average | 0.00 | 30120.92 | ||||||
Minimum of Months | 0.00 | 0.00 | 45.78 | 58.36 | 26848.25 | 60976.53 | ||
Maximum of Months | 0.00 | 0.00 | 51.77 | 59.78 | 33428.35 | 76329.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.557941E+12 | 0.00 | 3064782.52 | 0.294408E+11 | 0.00 | 0.00 |
February | 0.284928E+12 | 0.00 | 66508632.19 | 0.278663E+11 | 0.00 | 0.00 |
March | 0.154490E+12 | 0.00 | 0.132392E+09 | 0.321722E+11 | 0.00 | 0.00 |
April | 0.295479E+11 | 0.00 | 0.137219E+11 | 0.335884E+11 | 0.00 | 0.00 |
May | 0.162261E+11 | 0.00 | 0.104816E+12 | 0.379824E+11 | 0.00 | 0.00 |
June | 0.734507E+10 | 0.00 | 0.273797E+12 | 0.375275E+11 | 0.00 | 0.00 |
July | 0.325478E+10 | 0.00 | 0.383689E+12 | 0.392725E+11 | 0.00 | 0.00 |
August | 0.324646E+10 | 0.00 | 0.261848E+12 | 0.389491E+11 | 0.00 | 0.00 |
September | 0.216864E+11 | 0.00 | 0.591455E+11 | 0.378574E+11 | 0.00 | 0.00 |
October | 0.376886E+11 | 0.00 | 0.865124E+10 | 0.375282E+11 | 0.00 | 0.00 |
November | 0.788687E+11 | 0.00 | 0.131481E+10 | 0.322710E+11 | 0.00 | 0.00 |
December | 0.474549E+12 | 0.00 | 17323470.05 | 0.299190E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.166977E+13 | 0.00 | 0.110720E+13 | 0.414375E+12 | 0.00 | 0.00 |
Minimum of Months | 0.324646E+10 | 0.00 | 3064782.52 | 0.278663E+11 | 0.00 | 0.00 |
Maximum of Months | 0.557941E+12 | 0.00 | 0.383689E+12 | 0.392725E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.577763E+11 | 0.00 | 0.00 | 0.587890E+10 | 0.00 | 0.00 |
February | 0.312162E+11 | 0.00 | 0.00 | 0.530997E+10 | 0.00 | 0.00 |
March | 0.169366E+11 | 0.00 | 0.00 | 0.587890E+10 | 0.00 | 0.00 |
April | 0.179057E+10 | 0.00 | 0.220258E+10 | 0.568926E+10 | 0.00 | 0.00 |
May | 33792337.41 | 0.00 | 0.180784E+11 | 0.587890E+10 | 0.00 | 0.00 |
June | 23866.36 | 0.00 | 0.472590E+11 | 0.568926E+10 | 0.00 | 0.00 |
July | 21627.87 | 0.00 | 0.662562E+11 | 0.587890E+10 | 0.00 | 0.00 |
August | 26467.19 | 0.00 | 0.468520E+11 | 0.587890E+10 | 0.00 | 0.00 |
September | 15651.22 | 0.00 | 0.106541E+11 | 0.568926E+10 | 0.00 | 0.00 |
October | 0.757660E+09 | 0.00 | 0.144276E+10 | 0.587890E+10 | 0.00 | 0.00 |
November | 0.841080E+10 | 0.00 | 0.223311E+09 | 0.568926E+10 | 0.00 | 0.00 |
December | 0.503452E+11 | 0.00 | 0.00 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.167267E+12 | 0.00 | 0.192968E+12 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 15651.22 | 0.00 | 0.00 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 0.577763E+11 | 0.00 | 0.662562E+11 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.294408E+11 | 3064782.52 | 0.557941E+12 | 0.686123E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.278663E+11 | 66509022.62 | 0.284928E+12 | 0.665832E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.321722E+11 | 0.132392E+09 | 0.154490E+12 | 0.699215E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.335884E+11 | 0.137220E+11 | 0.295479E+11 | 0.408155E+12 | 58996649.79 | 0.00 | 0.00 | 0.00 |
May | 0.379824E+11 | 0.104816E+12 | 0.162261E+11 | 0.112513E+12 | 0.193245E+10 | 0.00 | 0.00 | 0.00 |
June | 0.375275E+11 | 0.273797E+12 | 0.734507E+10 | 0.268021E+11 | 0.321267E+11 | 0.00 | 0.00 | 0.00 |
July | 0.392725E+11 | 0.383689E+12 | 0.325478E+10 | 0.120865E+11 | 0.421342E+11 | 0.00 | 0.00 | 0.00 |
August | 0.389491E+11 | 0.261848E+12 | 0.324646E+10 | 0.142432E+11 | 0.150104E+11 | 0.00 | 0.00 | 0.00 |
September | 0.378574E+11 | 0.591456E+11 | 0.216864E+11 | 0.909860E+11 | 0.103901E+09 | 0.00 | 0.00 | 0.00 |
October | 0.375282E+11 | 0.865124E+10 | 0.376886E+11 | 0.339019E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.322710E+11 | 0.131481E+10 | 0.788687E+11 | 0.598895E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.299190E+11 | 17323470.05 | 0.474549E+12 | 0.695928E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.414375E+12 | 0.110720E+13 | 0.166977E+13 | 0.434980E+13 | 0.913667E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.278663E+11 | 3064782.52 | 0.324646E+10 | 0.120865E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.392725E+11 | 0.383689E+12 | 0.557941E+12 | 0.699215E+12 | 0.421342E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.00 | 0.577763E+11 | 0.125450E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.00 | 0.312162E+11 | 0.120730E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.00 | 0.169366E+11 | 0.126025E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.220258E+10 | 0.179057E+10 | 0.763430E+11 | 0.132239E+09 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.180784E+11 | 33792337.41 | 0.261079E+11 | 0.172697E+10 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.472590E+11 | 23866.36 | 0.761014E+10 | 0.109358E+11 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.662562E+11 | 21627.87 | 0.363883E+10 | 0.162060E+11 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.468520E+11 | 26467.19 | 0.434224E+10 | 0.694452E+10 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.106541E+11 | 15651.22 | 0.252554E+11 | 0.292488E+09 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.144276E+10 | 0.757660E+09 | 0.700162E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.223311E+09 | 0.841080E+10 | 0.107371E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.00 | 0.503452E+11 | 0.126140E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.192968E+12 | 0.167267E+12 | 0.819030E+12 | 0.362380E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.00 | 15651.22 | 0.363883E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.662562E+11 | 0.577763E+11 | 0.126140E+12 | 0.162060E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.294408E+11 | 0.557941E+12 | 3064782.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.278663E+11 | 0.284928E+12 | 66508632.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.321722E+11 | 0.154490E+12 | 0.132392E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.335884E+11 | 0.295479E+11 | 0.137219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.379824E+11 | 0.162261E+11 | 0.104816E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.375275E+11 | 0.734507E+10 | 0.273797E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.392725E+11 | 0.325478E+10 | 0.383689E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.389491E+11 | 0.324646E+10 | 0.261848E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.378574E+11 | 0.216864E+11 | 0.591455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.375282E+11 | 0.376886E+11 | 0.865124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.322710E+11 | 0.788687E+11 | 0.131481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.299190E+11 | 0.474549E+12 | 17323470.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.414375E+12 | 0.166977E+13 | 0.110720E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.278663E+11 | 0.324646E+10 | 3064782.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.392725E+11 | 0.557941E+12 | 0.383689E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 0.577763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.312162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.169366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.179057E+10 | 0.220258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 33792337.41 | 0.180784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 23866.36 | 0.472590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 21627.87 | 0.662562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 26467.19 | 0.468520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 15651.22 | 0.106541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.757660E+09 | 0.144276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.841080E+10 | 0.223311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.503452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.167267E+12 | 0.192968E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 15651.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.577763E+11 | 0.662562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.908405E+11 | 0.00 | 0.00 | 1681545.37 | 0.00 | 0.125400E+10 | 0.369672E+10 | 0.00 | 0.92 |
February | 0.629708E+11 | 0.00 | 0.00 | 319021.89 | 0.00 | 0.00 | 0.179836E+10 | 0.00 | 0.90 |
March | 0.560519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 |
April | 0.437192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
May | 0.385800E+11 | 0.00 | 0.00 | 0.00 | 0.103294E+09 | 0.00 | 0.00 | 0.00 | 0.90 |
June | 0.258768E+11 | 0.00 | 0.00 | 0.00 | 0.356321E+10 | 0.00 | 0.00 | 0.00 | 0.92 |
July | 0.142242E+11 | 0.137763E+10 | 0.00 | 5308404.45 | 0.457681E+10 | 0.00 | 0.652891E+10 | 0.00 | 0.93 |
August | 0.304311E+10 | 0.133224E+10 | 0.00 | 39062815.49 | 0.109355E+10 | 0.00 | 0.262261E+11 | 0.00 | 1.00 |
September | 0.210882E+10 | 2027945.32 | 0.00 | 99789245.90 | 15271877.87 | 0.00 | 0.468840E+11 | 0.00 | 1.02 |
October | 0.279483E+10 | 0.00 | 0.00 | 0.130451E+09 | 0.00 | 0.00 | 0.531600E+11 | 0.00 | 1.00 |
November | 0.221246E+10 | 0.00 | 0.00 | 70832482.25 | 0.00 | 0.00 | 0.504245E+11 | 0.00 | 0.98 |
December | 0.663415E+11 | 0.00 | 0.00 | 13607742.11 | 0.00 | 0.00 | 0.215264E+11 | 0.00 | 0.92 |
Annual Sum or Average | 0.408764E+12 | 0.271190E+10 | 0.00 | 0.361052E+09 | 0.935214E+10 | 0.125400E+10 | 0.210245E+12 | 0.00 | 0.94 |
Minimum of Months | 0.210882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Maximum of Months | 0.908405E+11 | 0.137763E+10 | 0.00 | 0.130451E+09 | 0.457681E+10 | 0.125400E+10 | 0.531600E+11 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.249506E+10 | 0.00 | 0.00 | 79747.94 | 0.00 | 0.145529E+11 | 0.210812E+09 | 0.00 | 2.98 |
February | 0.336162E+10 | 0.00 | 0.00 | 832308.55 | 0.00 | 0.781233E+10 | 0.561153E+09 | 0.00 | 2.95 |
March | 0.509187E+10 | 0.00 | 0.00 | 1345374.94 | 0.00 | 0.446268E+10 | 0.610521E+09 | 0.00 | 2.90 |
April | 0.633715E+10 | 0.00 | 0.00 | 1773421.10 | 0.00 | 0.799101E+09 | 0.861816E+09 | 0.00 | 2.92 |
May | 0.636037E+10 | 18040531.62 | 0.00 | 1462458.59 | 2306507.55 | 650423.83 | 0.626295E+09 | 0.00 | 2.97 |
June | 0.433697E+10 | 0.408694E+09 | 0.00 | 847036.87 | 0.275369E+09 | 0.00 | 0.329385E+09 | 0.00 | 3.04 |
July | 0.328821E+10 | 0.694871E+09 | 0.00 | 837223.54 | 0.433006E+09 | 0.00 | 0.455282E+09 | 0.00 | 3.10 |
August | 0.440974E+10 | 0.296653E+09 | 0.00 | 1574397.95 | 0.148245E+09 | 1502126.44 | 0.600301E+09 | 0.00 | 3.18 |
September | 0.656231E+10 | 4091677.71 | 0.00 | 2218764.05 | 39437.77 | 14769807.53 | 0.111228E+10 | 0.00 | 3.02 |
October | 0.726861E+10 | 0.00 | 0.00 | 2025375.14 | 0.00 | 0.460923E+09 | 0.885910E+09 | 0.00 | 2.89 |
November | 0.463261E+10 | 0.00 | 0.00 | 578576.24 | 0.00 | 0.353630E+10 | 0.344846E+09 | 0.00 | 2.88 |
December | 0.181333E+10 | 0.00 | 0.00 | 17133.45 | 0.00 | 0.137871E+11 | 52229131.31 | 0.00 | 2.95 |
Annual Sum or Average | 0.559578E+11 | 0.142235E+10 | 0.00 | 13591818.37 | 0.858965E+09 | 0.454283E+11 | 0.665083E+10 | 0.00 | 2.98 |
Minimum of Months | 0.181333E+10 | 0.00 | 0.00 | 17133.45 | 0.00 | 0.00 | 52229131.31 | 0.00 | 2.88 |
Maximum of Months | 0.726861E+10 | 0.694871E+09 | 0.00 | 2218764.05 | 0.433006E+09 | 0.145529E+11 | 0.111228E+10 | 0.00 | 3.18 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.882038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376330E+09 | 0.00 | 0.00 | 1.37 |
February | 0.620219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17409806.56 | 0.00 | 0.00 | 1.35 |
March | 0.532304E+10 | 0.00 | 0.00 | 19545.63 | 0.00 | 0.00 | 59428504.85 | 0.00 | 1.33 |
April | 0.375135E+10 | 0.00 | 0.00 | 588426.57 | 0.00 | 0.00 | 0.462138E+09 | 0.00 | 1.32 |
May | 0.233334E+10 | 4819889.82 | 0.00 | 1490521.25 | 5244713.20 | 0.00 | 0.143187E+10 | 0.00 | 1.38 |
June | 0.135104E+10 | 0.241178E+09 | 0.00 | 1383268.98 | 0.123006E+09 | 0.00 | 0.118620E+10 | 0.00 | 1.43 |
July | 0.534002E+09 | 0.441724E+09 | 0.00 | 2062397.61 | 0.168248E+09 | 0.00 | 0.153562E+10 | 0.00 | 1.47 |
August | 0.916326E+09 | 0.126685E+09 | 0.00 | 2050417.36 | 0.103273E+09 | 0.00 | 0.181244E+10 | 0.00 | 1.47 |
September | 0.257852E+10 | 149501.58 | 0.00 | 1355088.27 | 1512257.24 | 0.00 | 0.148764E+10 | 0.00 | 1.36 |
October | 0.394902E+10 | 0.00 | 0.00 | 577574.70 | 0.00 | 0.00 | 0.542926E+09 | 0.00 | 1.29 |
November | 0.450521E+10 | 0.00 | 0.00 | 4066.29 | 0.00 | 0.00 | 14362323.70 | 0.00 | 1.32 |
December | 0.820595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135017E+09 | 0.00 | 0.00 | 1.36 |
Annual Sum or Average | 0.484704E+11 | 0.814557E+09 | 0.00 | 9531306.65 | 0.401284E+09 | 0.528757E+09 | 0.853263E+10 | 0.00 | 1.37 |
Minimum of Months | 0.534002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.29 |
Maximum of Months | 0.882038E+10 | 0.441724E+09 | 0.00 | 2062397.61 | 0.168248E+09 | 0.376330E+09 | 0.181244E+10 | 0.00 | 1.47 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.770289E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776731E+10 | 0.00 | 0.00 | 0.60 |
February | 0.161969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415417E+10 | 0.00 | 0.00 | 0.59 |
March | 0.287271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212402E+10 | 0.00 | 0.00 | 0.58 |
April | 0.388680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10534820.43 | 0.00 | 0.00 | 0.58 |
May | 0.330802E+10 | 382337.25 | 0.00 | 140312.59 | 8826578.11 | 0.00 | 0.133364E+09 | 0.00 | 0.59 |
June | 0.217832E+10 | 0.167085E+09 | 0.00 | 194936.96 | 0.164061E+09 | 0.00 | 0.133313E+09 | 0.00 | 0.62 |
July | 0.145115E+10 | 0.220996E+09 | 0.00 | 531529.80 | 0.328058E+09 | 0.00 | 0.407541E+09 | 0.00 | 0.62 |
August | 0.220127E+10 | 38777078.62 | 0.00 | 341234.15 | 0.168085E+09 | 0.00 | 0.267227E+09 | 0.00 | 0.63 |
September | 0.365865E+10 | 13310.49 | 0.00 | 44793.05 | 1528705.35 | 0.00 | 66058980.75 | 0.00 | 0.59 |
October | 0.415339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
November | 0.344368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751993E+09 | 0.00 | 0.00 | 0.58 |
December | 0.864042E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687914E+10 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.304080E+11 | 0.427254E+09 | 0.00 | 1252806.56 | 0.670558E+09 | 0.216872E+11 | 0.100750E+10 | 0.00 | 0.59 |
Minimum of Months | 0.770289E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.415339E+10 | 0.220996E+09 | 0.00 | 531529.80 | 0.328058E+09 | 0.776731E+10 | 0.407541E+09 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 16181997.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410785E+10 | 0.00 | 0.00 | 0.50 |
February | 0.282247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250678E+10 | 0.00 | 0.00 | 0.49 |
March | 0.747006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166663E+10 | 0.00 | 0.00 | 0.49 |
April | 0.173282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149760E+09 | 0.00 | 0.00 | 0.48 |
May | 0.166129E+10 | 0.00 | 0.00 | 0.00 | 4447939.87 | 0.00 | 0.00 | 0.00 | 0.50 |
June | 0.110601E+10 | 52835278.61 | 0.00 | 17661.66 | 0.101908E+09 | 0.00 | 8820640.85 | 0.00 | 0.51 |
July | 0.872221E+09 | 35312678.33 | 0.00 | 13851.38 | 0.220713E+09 | 0.00 | 19839685.51 | 0.00 | 0.51 |
August | 0.119051E+10 | 2842443.05 | 0.00 | 31.98 | 95603533.49 | 0.00 | 36206.45 | 0.00 | 0.52 |
September | 0.179824E+10 | 0.00 | 0.00 | 0.00 | 744860.96 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 0.197432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31946713.36 | 0.00 | 0.00 | 0.47 |
November | 0.112310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903594E+09 | 0.00 | 0.00 | 0.48 |
December | 29949945.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371035E+10 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.125339E+11 | 90990399.99 | 0.00 | 31545.01 | 0.423418E+09 | 0.130769E+11 | 28696532.82 | 0.00 | 0.50 |
Minimum of Months | 16181997.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.197432E+10 | 52835278.61 | 0.00 | 17661.66 | 0.220713E+09 | 0.410785E+10 | 19839685.51 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.141656E+11 | 0.00 | 0.00 | 80170143.15 | 0.00 | 0.222364E+10 | 0.120645E+12 | 0.00 | 20.93 |
February | 0.581314E+10 | 0.00 | 0.00 | 82169738.04 | 0.00 | 0.157102E+09 | 0.907653E+11 | 0.00 | 21.19 |
March | 0.126556E+10 | 0.00 | 0.00 | 0.110207E+09 | 0.00 | 0.00 | 0.848408E+11 | 0.00 | 21.13 |
April | 0.531544E+09 | 0.00 | 0.00 | 0.137724E+09 | 0.00 | 0.00 | 0.684788E+11 | 0.00 | 21.17 |
May | 0.831088E+09 | 0.146550E+09 | 0.00 | 0.139036E+09 | 0.00 | 0.00 | 0.607745E+11 | 0.00 | 22.17 |
June | 0.674692E+09 | 0.571818E+10 | 0.00 | 85998211.39 | 0.00 | 0.00 | 0.398281E+11 | 0.00 | 22.66 |
July | 0.382078E+09 | 0.955326E+10 | 0.00 | 67371872.57 | 0.00 | 0.00 | 0.314339E+11 | 0.00 | 22.64 |
August | 0.247197E+09 | 0.372521E+10 | 0.00 | 84144293.81 | 0.00 | 0.00 | 0.425845E+11 | 0.00 | 23.18 |
September | 0.112779E+10 | 23190368.24 | 0.00 | 0.143611E+09 | 0.00 | 0.00 | 0.657778E+11 | 0.00 | 21.86 |
October | 0.162690E+10 | 0.00 | 0.00 | 0.184706E+09 | 0.00 | 0.00 | 0.727398E+11 | 0.00 | 20.75 |
November | 0.676586E+09 | 0.00 | 0.00 | 0.104752E+09 | 0.00 | 0.00 | 0.725761E+11 | 0.00 | 21.06 |
December | 0.625039E+10 | 0.00 | 0.00 | 81659847.93 | 0.00 | 0.00 | 0.119577E+12 | 0.00 | 20.95 |
Annual Sum or Average | 0.335925E+11 | 0.191664E+11 | 0.00 | 0.130155E+10 | 0.00 | 0.238075E+10 | 0.870022E+12 | 0.00 | 21.64 |
Minimum of Months | 0.247197E+09 | 0.00 | 0.00 | 67371872.57 | 0.00 | 0.00 | 0.314339E+11 | 0.00 | 20.75 |
Maximum of Months | 0.141656E+11 | 0.955326E+10 | 0.00 | 0.184706E+09 | 0.00 | 0.222364E+10 | 0.120645E+12 | 0.00 | 23.18 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.608200E+11 | 0.00 | 0.00 | 904025.81 | 0.00 | 0.497671E+10 | 0.185855E+10 | 0.00 | 4.16 |
February | 0.389639E+11 | 0.00 | 0.00 | 5879560.33 | 0.00 | 0.126392E+10 | 0.586459E+10 | 0.00 | 4.13 |
March | 0.312878E+11 | 0.00 | 0.00 | 8970280.85 | 0.00 | 28322775.95 | 0.864922E+10 | 0.00 | 4.07 |
April | 0.174691E+11 | 0.00 | 0.00 | 16877257.73 | 0.00 | 0.00 | 0.140495E+11 | 0.00 | 4.10 |
May | 0.909165E+10 | 72403309.21 | 0.00 | 22342737.28 | 5488337.23 | 0.00 | 0.185386E+11 | 0.00 | 4.19 |
June | 0.511106E+10 | 0.230916E+10 | 0.00 | 18030106.08 | 0.346707E+09 | 0.00 | 0.133228E+11 | 0.00 | 4.28 |
July | 0.230086E+10 | 0.398300E+10 | 0.00 | 18708270.27 | 0.412936E+09 | 0.00 | 0.124676E+11 | 0.00 | 4.34 |
August | 0.397613E+10 | 0.155614E+10 | 0.00 | 23756671.80 | 0.171087E+09 | 0.00 | 0.157389E+11 | 0.00 | 4.45 |
September | 0.100533E+11 | 14931266.65 | 0.00 | 24548871.34 | 0.00 | 0.00 | 0.202789E+11 | 0.00 | 4.24 |
October | 0.201331E+11 | 0.00 | 0.00 | 17952533.48 | 0.00 | 0.00 | 0.137890E+11 | 0.00 | 4.05 |
November | 0.286157E+11 | 0.00 | 0.00 | 4243181.93 | 0.00 | 49324165.80 | 0.473971E+10 | 0.00 | 4.02 |
December | 0.559994E+11 | 0.00 | 0.00 | 364543.41 | 0.00 | 0.440025E+10 | 0.952870E+09 | 0.00 | 4.12 |
Annual Sum or Average | 0.283822E+12 | 0.793564E+10 | 0.00 | 0.162578E+09 | 0.936218E+09 | 0.107185E+11 | 0.130250E+12 | 0.00 | 4.18 |
Minimum of Months | 0.230086E+10 | 0.00 | 0.00 | 364543.41 | 0.00 | 0.00 | 0.952870E+09 | 0.00 | 4.02 |
Maximum of Months | 0.608200E+11 | 0.398300E+10 | 0.00 | 24548871.34 | 0.412936E+09 | 0.497671E+10 | 0.202789E+11 | 0.00 | 4.45 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.188865E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258744E+10 | 0.00 | 0.00 | 1.70 |
February | 0.126017E+12 | 0.00 | 0.00 | 1157727.57 | 0.00 | 0.00 | 0.345864E+10 | 0.00 | 1.67 |
March | 0.101589E+12 | 0.00 | 0.00 | 6678986.60 | 0.00 | 0.00 | 0.105519E+11 | 0.00 | 1.65 |
April | 0.540885E+11 | 0.00 | 0.00 | 43477006.92 | 0.00 | 0.00 | 0.347384E+11 | 0.00 | 1.65 |
May | 0.234609E+11 | 0.143815E+09 | 0.00 | 91938443.40 | 65007033.36 | 0.00 | 0.580558E+11 | 0.00 | 1.76 |
June | 0.114117E+11 | 0.638101E+10 | 0.00 | 77279052.14 | 0.129232E+10 | 0.00 | 0.440408E+11 | 0.00 | 1.84 |
July | 0.424753E+10 | 0.112340E+11 | 0.00 | 78885297.54 | 0.152899E+10 | 0.00 | 0.417014E+11 | 0.00 | 1.89 |
August | 0.799183E+10 | 0.403196E+10 | 0.00 | 86875648.88 | 0.796035E+09 | 0.00 | 0.519924E+11 | 0.00 | 1.90 |
September | 0.225894E+11 | 29197744.32 | 0.00 | 0.107316E+09 | 5473663.98 | 0.00 | 0.656032E+11 | 0.00 | 1.74 |
October | 0.515741E+11 | 0.00 | 0.00 | 67622227.47 | 0.00 | 0.00 | 0.439265E+11 | 0.00 | 1.63 |
November | 0.834811E+11 | 0.00 | 0.00 | 4704417.12 | 0.00 | 0.00 | 0.106490E+11 | 0.00 | 1.64 |
December | 0.173638E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.68 |
Annual Sum or Average | 0.848954E+12 | 0.218200E+11 | 0.00 | 0.565935E+09 | 0.368782E+10 | 0.258744E+10 | 0.364718E+12 | 0.00 | 1.73 |
Minimum of Months | 0.424753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 |
Maximum of Months | 0.188865E+12 | 0.112340E+11 | 0.00 | 0.107316E+09 | 0.152899E+10 | 0.258744E+10 | 0.656032E+11 | 0.00 | 1.90 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.223319E+09 | 0.00 | 0.00 | 115485.66 | 0.00 | 0.369026E+10 | 5504764.06 | 0.00 | 0.47 |
February | 0.313242E+09 | 0.00 | 0.00 | 1386522.82 | 0.00 | 0.213614E+10 | 58328174.89 | 0.00 | 0.47 |
March | 0.371796E+09 | 0.00 | 0.00 | 4451922.26 | 0.00 | 0.151069E+10 | 0.185728E+09 | 0.00 | 0.47 |
April | 0.333951E+09 | 1711196.26 | 0.00 | 9568814.70 | 14766.82 | 0.662571E+09 | 0.590148E+09 | 0.00 | 0.47 |
May | 0.191500E+09 | 24951556.23 | 8131.53 | 14346204.29 | 1259774.79 | 83044752.37 | 0.106815E+10 | 447.38 | 0.47 |
June | 0.104031E+09 | 0.281198E+09 | 258823.29 | 10629767.18 | 19577849.42 | 13051825.62 | 0.659106E+09 | 13081.96 | 0.48 |
July | 44846311.79 | 0.493388E+09 | 377616.55 | 8434511.72 | 26056139.70 | 410863.02 | 0.459954E+09 | 12420.05 | 0.48 |
August | 92023619.81 | 0.229395E+09 | 168424.61 | 9165437.43 | 17298043.95 | 15658290.23 | 0.614567E+09 | 9990.77 | 0.48 |
September | 0.239154E+09 | 13877940.57 | 23016.76 | 10719540.42 | 802339.73 | 0.177405E+09 | 0.100490E+10 | 3574.98 | 0.48 |
October | 0.367070E+09 | 0.00 | 0.00 | 4916278.05 | 0.00 | 0.781748E+09 | 0.456563E+09 | 0.00 | 0.47 |
November | 0.312849E+09 | 0.00 | 0.00 | 505535.47 | 0.00 | 0.127003E+10 | 36942482.57 | 0.00 | 0.47 |
December | 0.169269E+09 | 0.00 | 0.00 | 118375.98 | 0.00 | 0.329502E+10 | 4578408.95 | 0.00 | 0.47 |
Annual Sum or Average | 0.276305E+10 | 0.104452E+10 | 836012.74 | 74358395.98 | 65008914.41 | 0.136360E+11 | 0.514447E+10 | 39515.14 | 0.47 |
Minimum of Months | 44846311.79 | 0.00 | 0.00 | 115485.66 | 0.00 | 410863.02 | 4578408.95 | 0.00 | 0.47 |
Maximum of Months | 0.371796E+09 | 0.493388E+09 | 377616.55 | 14346204.29 | 26056139.70 | 0.369026E+10 | 0.106815E+10 | 13081.96 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 71414255.14 | 0.00 | 0.00 | 82181.18 | 0.00 | 0.384472E+10 | 2516682.86 | 0.00 | 0.47 |
February | 0.169663E+09 | 0.00 | 0.00 | 371504.09 | 0.00 | 0.231803E+10 | 20731778.09 | 0.00 | 0.47 |
March | 0.283446E+09 | 0.00 | 0.00 | 2122746.13 | 0.00 | 0.168331E+10 | 0.103540E+09 | 0.00 | 0.47 |
April | 0.395640E+09 | 1614214.29 | 0.00 | 6063387.02 | 111546.58 | 0.779848E+09 | 0.414501E+09 | 0.00 | 0.47 |
May | 0.243589E+09 | 24417017.46 | 12835.30 | 12382308.09 | 1785946.48 | 98030062.50 | 0.100288E+10 | 1038.64 | 0.47 |
June | 0.113852E+09 | 0.277927E+09 | 305363.25 | 10053425.82 | 22765288.24 | 11947374.56 | 0.650873E+09 | 14879.39 | 0.48 |
July | 47979039.73 | 0.488444E+09 | 412917.95 | 7977461.54 | 30903132.32 | 416164.07 | 0.457213E+09 | 12751.62 | 0.48 |
August | 99068116.95 | 0.220485E+09 | 267318.13 | 7996330.43 | 26077616.32 | 16504219.49 | 0.607760E+09 | 12786.73 | 0.48 |
September | 0.312289E+09 | 12962144.83 | 22265.58 | 7371763.68 | 1716415.45 | 0.215230E+09 | 0.897123E+09 | 4323.05 | 0.47 |
October | 0.419939E+09 | 0.00 | 0.00 | 1981855.58 | 0.00 | 0.937750E+09 | 0.250437E+09 | 0.00 | 0.47 |
November | 0.232414E+09 | 0.00 | 0.00 | 246371.06 | 0.00 | 0.137946E+10 | 8014185.23 | 0.00 | 0.47 |
December | 66065575.10 | 0.00 | 0.00 | 88537.22 | 0.00 | 0.339938E+10 | 3042890.69 | 0.00 | 0.47 |
Annual Sum or Average | 0.245536E+10 | 0.102585E+10 | 1020700.20 | 56737871.83 | 83359945.39 | 0.146846E+11 | 0.441863E+10 | 45779.43 | 0.47 |
Minimum of Months | 47979039.73 | 0.00 | 0.00 | 82181.18 | 0.00 | 416164.07 | 2516682.86 | 0.00 | 0.47 |
Maximum of Months | 0.419939E+09 | 0.488444E+09 | 412917.95 | 12382308.09 | 30903132.32 | 0.384472E+10 | 0.100288E+10 | 14879.39 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119431E+11 | 0.00 | 0.00 | 131312.34 | 0.00 | 0.410965E+11 | 0.101075E+09 | 0.00 | 0.53 |
February | 0.155316E+11 | 0.00 | 0.00 | 6001783.80 | 0.00 | 0.176278E+11 | 0.855588E+09 | 0.00 | 0.53 |
March | 0.168581E+11 | 0.00 | 0.00 | 19615121.93 | 0.00 | 0.896504E+10 | 0.226069E+10 | 0.00 | 0.53 |
April | 0.159418E+11 | 23402511.52 | 0.00 | 48668682.63 | 0.00 | 0.00 | 0.565305E+10 | 0.00 | 0.54 |
May | 0.726902E+10 | 0.355518E+09 | 0.00 | 63615926.00 | 0.00 | 0.00 | 0.110676E+11 | 0.00 | 0.54 |
June | 0.413545E+10 | 0.400871E+10 | 0.00 | 44004644.75 | 73226725.65 | 0.00 | 0.648909E+10 | 0.00 | 0.54 |
July | 0.181789E+10 | 0.698583E+10 | 0.00 | 35636847.43 | 62655009.39 | 0.00 | 0.511104E+10 | 0.00 | 0.54 |
August | 0.281842E+10 | 0.334432E+10 | 0.00 | 47783744.93 | 3045257.39 | 0.00 | 0.705112E+10 | 0.00 | 0.54 |
September | 0.891153E+10 | 0.196227E+09 | 0.00 | 71558518.21 | 3185016.56 | 0.00 | 0.104360E+11 | 0.00 | 0.54 |
October | 0.167537E+11 | 0.00 | 0.00 | 45796308.05 | 0.00 | 0.269215E+09 | 0.476550E+10 | 0.00 | 0.53 |
November | 0.132245E+11 | 0.00 | 0.00 | 4805540.87 | 0.00 | 0.794328E+10 | 0.797564E+09 | 0.00 | 0.53 |
December | 0.717122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398651E+11 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.122376E+12 | 0.149140E+11 | 0.00 | 0.387618E+09 | 0.142112E+09 | 0.115767E+12 | 0.545883E+11 | 0.00 | 0.54 |
Minimum of Months | 0.181789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.168581E+11 | 0.698583E+10 | 0.00 | 71558518.21 | 73226725.65 | 0.410965E+11 | 0.110676E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.500745E+10 | 0.00 | 0.00 | 459765.53 | 0.00 | 0.481182E+11 | 29251931.48 | 0.00 | 0.53 |
February | 0.596751E+10 | 0.00 | 0.00 | 1028155.32 | 0.00 | 0.277391E+11 | 0.322735E+09 | 0.00 | 0.53 |
March | 0.671027E+10 | 0.00 | 0.00 | 6708171.97 | 0.00 | 0.189120E+11 | 0.248210E+10 | 0.00 | 0.53 |
April | 0.606893E+10 | 11132185.46 | 120248.54 | 37088029.06 | 12148100.12 | 0.464743E+10 | 0.108960E+11 | 8376.78 | 0.54 |
May | 0.449560E+10 | 0.173977E+09 | 0.00 | 0.105659E+09 | 0.181638E+09 | 32318118.97 | 0.137717E+11 | 0.00 | 0.54 |
June | 0.214770E+10 | 0.299958E+10 | 1731380.59 | 86035353.85 | 0.108170E+10 | 7891734.94 | 0.842983E+10 | 33540.73 | 0.54 |
July | 0.111982E+10 | 0.527003E+10 | 1458622.53 | 61511741.28 | 0.177888E+10 | 2078937.65 | 0.578307E+10 | 39194.48 | 0.54 |
August | 0.169558E+10 | 0.195797E+10 | 3728202.80 | 63337884.14 | 0.138651E+10 | 12637324.44 | 0.814847E+10 | 67288.05 | 0.54 |
September | 0.502212E+10 | 0.128088E+09 | 0.00 | 81877725.14 | 71378946.06 | 54650857.56 | 0.142658E+11 | 0.00 | 0.54 |
October | 0.599243E+10 | 0.00 | 0.00 | 40999017.64 | 0.00 | 0.310717E+10 | 0.126996E+11 | 0.00 | 0.53 |
November | 0.580491E+10 | 0.00 | 0.00 | 5088388.11 | 0.00 | 0.134760E+11 | 0.269021E+10 | 0.00 | 0.54 |
December | 0.563386E+10 | 0.00 | 0.00 | 550796.09 | 0.00 | 0.413651E+11 | 49699613.15 | 0.00 | 0.53 |
Annual Sum or Average | 0.556662E+11 | 0.105408E+11 | 7038454.46 | 0.490344E+09 | 0.451226E+10 | 0.157475E+12 | 0.795684E+11 | 148400.04 | 0.54 |
Minimum of Months | 0.111982E+10 | 0.00 | 0.00 | 459765.53 | 0.00 | 2078937.65 | 29251931.48 | 0.00 | 0.53 |
Maximum of Months | 0.671027E+10 | 0.527003E+10 | 3728202.80 | 0.105659E+09 | 0.177888E+10 | 0.481182E+11 | 0.142658E+11 | 67288.05 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.208480E+09 | 0.00 | 0.00 | 130887.15 | 0.00 | 0.370461E+10 | 5974739.85 | 0.00 | 0.47 |
February | 0.361523E+09 | 0.00 | 0.00 | 531672.79 | 0.00 | 0.208118E+10 | 65863501.48 | 0.00 | 0.47 |
March | 0.387893E+09 | 0.00 | 0.00 | 2591036.51 | 0.00 | 0.146833E+10 | 0.213851E+09 | 0.00 | 0.47 |
April | 0.282908E+09 | 1596085.08 | 1574.67 | 10410203.21 | 126577.40 | 0.623888E+09 | 0.679032E+09 | 1725.93 | 0.47 |
May | 0.143028E+09 | 25324209.53 | 0.00 | 15892937.23 | 895700.39 | 0.103875E+09 | 0.109424E+10 | 0.00 | 0.47 |
June | 52332170.58 | 0.286296E+09 | 129850.51 | 13761375.84 | 14617271.47 | 5539685.45 | 0.715185E+09 | 4379.05 | 0.48 |
July | 29843454.17 | 0.501059E+09 | 176084.04 | 9513145.33 | 18595978.33 | 335797.08 | 0.473953E+09 | 2965.34 | 0.48 |
August | 72789856.77 | 0.229751E+09 | 240180.41 | 10068667.67 | 16867892.75 | 13441993.82 | 0.635114E+09 | 12523.90 | 0.48 |
September | 0.221585E+09 | 14115618.40 | 21676.89 | 11647715.82 | 564661.90 | 0.193388E+09 | 0.100556E+10 | 4914.86 | 0.48 |
October | 0.356098E+09 | 0.00 | 0.00 | 4903519.59 | 0.00 | 0.821001E+09 | 0.428295E+09 | 0.00 | 0.47 |
November | 0.317065E+09 | 0.00 | 0.00 | 532912.63 | 0.00 | 0.125941E+10 | 43321648.69 | 0.00 | 0.47 |
December | 0.166886E+09 | 0.00 | 0.00 | 128813.50 | 0.00 | 0.329464E+10 | 7335042.22 | 0.00 | 0.47 |
Annual Sum or Average | 0.260043E+10 | 0.105814E+10 | 569366.53 | 80112887.28 | 51668082.24 | 0.135696E+11 | 0.536773E+10 | 26509.08 | 0.47 |
Minimum of Months | 29843454.17 | 0.00 | 0.00 | 128813.50 | 0.00 | 335797.08 | 5974739.85 | 0.00 | 0.47 |
Maximum of Months | 0.387893E+09 | 0.501059E+09 | 240180.41 | 15892937.23 | 18595978.33 | 0.370461E+10 | 0.109424E+10 | 12523.90 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 75708028.40 | 0.00 | 0.00 | 80869.55 | 0.00 | 0.384062E+10 | 2332924.42 | 0.00 | 0.47 |
February | 0.186177E+09 | 0.00 | 0.00 | 166939.94 | 0.00 | 0.230874E+10 | 13714111.31 | 0.00 | 0.47 |
March | 0.330623E+09 | 0.00 | 0.00 | 655492.93 | 0.00 | 0.165406E+10 | 87084584.83 | 0.00 | 0.47 |
April | 0.370451E+09 | 1542238.33 | 9127.11 | 6206010.89 | 170739.76 | 0.708112E+09 | 0.511282E+09 | 3655.68 | 0.47 |
May | 0.189086E+09 | 24928065.25 | 4914.94 | 13614142.43 | 1283476.60 | 0.127111E+09 | 0.102707E+10 | 381.10 | 0.47 |
June | 55210157.21 | 0.285275E+09 | 129936.37 | 13150971.03 | 15603261.91 | 5516628.66 | 0.712848E+09 | 4277.46 | 0.48 |
July | 31834679.48 | 0.498879E+09 | 121997.43 | 9042455.60 | 20769224.64 | 335757.74 | 0.472372E+09 | 3171.48 | 0.48 |
August | 77112398.10 | 0.222837E+09 | 338652.18 | 8801886.61 | 23650140.57 | 14284424.56 | 0.631130E+09 | 16994.82 | 0.48 |
September | 0.268003E+09 | 13016945.89 | 51822.07 | 7975258.68 | 1631264.41 | 0.249004E+09 | 0.907030E+09 | 5116.54 | 0.47 |
October | 0.436143E+09 | 0.00 | 0.00 | 1764767.62 | 0.00 | 0.964649E+09 | 0.207551E+09 | 0.00 | 0.47 |
November | 0.224499E+09 | 0.00 | 0.00 | 261241.23 | 0.00 | 0.137594E+10 | 19435569.00 | 0.00 | 0.47 |
December | 77345808.03 | 0.00 | 0.00 | 84245.80 | 0.00 | 0.338801E+10 | 3140978.24 | 0.00 | 0.47 |
Annual Sum or Average | 0.232219E+10 | 0.104648E+10 | 656450.09 | 61804282.30 | 63108107.89 | 0.146364E+11 | 0.459499E+10 | 33597.08 | 0.47 |
Minimum of Months | 31834679.48 | 0.00 | 0.00 | 80869.55 | 0.00 | 335757.74 | 2332924.42 | 0.00 | 0.47 |
Maximum of Months | 0.436143E+09 | 0.498879E+09 | 338652.18 | 13614142.43 | 23650140.57 | 0.384062E+10 | 0.102707E+10 | 16994.82 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.149537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452837E+11 | 0.00 | 0.00 | 0.58 |
February | 0.240278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167099E+11 | 0.00 | 0.00 | 0.57 |
March | 0.291275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612711E+10 | 0.00 | 0.00 | 0.56 |
April | 0.274978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
May | 0.237881E+11 | 2692215.37 | 0.00 | 391775.30 | 62276229.17 | 0.00 | 0.476904E+09 | 0.00 | 0.57 |
June | 0.156659E+11 | 0.120450E+10 | 0.00 | 857247.59 | 0.112763E+10 | 0.00 | 0.628070E+09 | 0.00 | 0.59 |
July | 0.963952E+10 | 0.201117E+10 | 0.00 | 3629149.00 | 0.179641E+10 | 0.00 | 0.341555E+10 | 0.00 | 0.60 |
August | 0.162348E+11 | 0.178347E+09 | 0.00 | 890615.56 | 0.125960E+10 | 0.00 | 0.115389E+10 | 0.00 | 0.60 |
September | 0.261157E+11 | 0.00 | 0.00 | 109758.06 | 10879746.46 | 0.00 | 0.150027E+09 | 0.00 | 0.57 |
October | 0.293000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4385028.41 | 0.00 | 0.00 | 0.54 |
November | 0.253250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427764E+10 | 0.00 | 0.00 | 0.56 |
December | 0.125268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421055E+11 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.254203E+12 | 0.339670E+10 | 0.00 | 5878545.52 | 0.425679E+10 | 0.114508E+12 | 0.582444E+10 | 0.00 | 0.57 |
Minimum of Months | 0.963952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.293000E+11 | 0.201117E+10 | 0.00 | 3629149.00 | 0.179641E+10 | 0.452837E+11 | 0.341555E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 28433562.58 | 0.00 | 0.00 | 12355.22 | 0.00 | 0.950795E+09 | 558225.53 | 0.00 | 0.47 |
February | 58537849.54 | 0.00 | 0.00 | 317069.07 | 0.00 | 0.557121E+09 | 11297909.03 | 0.00 | 0.47 |
March | 74512161.50 | 0.00 | 0.00 | 1076869.35 | 0.00 | 0.404924E+09 | 37652694.27 | 0.00 | 0.47 |
April | 78482626.34 | 427799.07 | 0.00 | 2258415.80 | 3691.71 | 0.198042E+09 | 0.120276E+09 | 0.00 | 0.47 |
May | 50703524.53 | 6233939.59 | 2103.94 | 3186434.47 | 318893.16 | 54612453.93 | 0.230757E+09 | 40.79 | 0.47 |
June | 26111314.73 | 69759956.58 | 67777.37 | 2388246.72 | 5430610.15 | 14735597.83 | 0.153469E+09 | 3499.59 | 0.48 |
July | 11563264.24 | 0.122571E+09 | 71725.08 | 1847617.13 | 7312257.44 | 160447.47 | 0.114840E+09 | 3883.41 | 0.48 |
August | 23529580.56 | 56744194.31 | 43469.29 | 2022056.91 | 4927649.25 | 10913744.03 | 0.146388E+09 | 2655.16 | 0.48 |
September | 62400030.46 | 3464350.64 | 5839.12 | 2220843.04 | 205719.43 | 88265329.27 | 0.205159E+09 | 808.82 | 0.48 |
October | 86251070.65 | 0.00 | 0.00 | 980554.29 | 0.00 | 0.241462E+09 | 73880346.77 | 0.00 | 0.47 |
November | 59209758.67 | 0.00 | 0.00 | 95069.10 | 0.00 | 0.341418E+09 | 4358557.19 | 0.00 | 0.47 |
December | 22057684.38 | 0.00 | 0.00 | 7014.16 | 0.00 | 0.844762E+09 | 419772.32 | 0.00 | 0.47 |
Annual Sum or Average | 0.581792E+09 | 0.259201E+09 | 190914.81 | 16412545.26 | 18198821.14 | 0.370721E+10 | 0.109906E+10 | 10887.77 | 0.47 |
Minimum of Months | 11563264.24 | 0.00 | 0.00 | 7014.16 | 0.00 | 160447.47 | 419772.32 | 0.00 | 0.47 |
Maximum of Months | 86251070.65 | 0.122571E+09 | 71725.08 | 3186434.47 | 7312257.44 | 0.950795E+09 | 0.230757E+09 | 3883.41 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 10629017.95 | 0.00 | 0.00 | 6132.91 | 0.00 | 0.968705E+09 | 344437.95 | 0.00 | 0.47 |
February | 24768411.17 | 0.00 | 0.00 | 55919.94 | 0.00 | 0.598312E+09 | 4063906.62 | 0.00 | 0.47 |
March | 50505102.38 | 0.00 | 0.00 | 467823.95 | 0.00 | 0.446237E+09 | 20894431.42 | 0.00 | 0.47 |
April | 89459758.80 | 391875.13 | 0.00 | 1376822.21 | 39565.08 | 0.225227E+09 | 82949569.10 | 0.00 | 0.47 |
May | 62352900.06 | 6114704.94 | 2029.26 | 2672647.73 | 437360.05 | 63483991.67 | 0.210710E+09 | 115.21 | 0.47 |
June | 28489336.89 | 69029369.54 | 67456.41 | 2223151.77 | 6152387.51 | 14648001.17 | 0.151321E+09 | 3812.19 | 0.48 |
July | 12590422.41 | 0.121112E+09 | 117152.65 | 1722963.53 | 8709583.75 | 151348.54 | 0.113932E+09 | 4513.89 | 0.48 |
August | 25267527.44 | 54804520.68 | 49606.27 | 1717151.58 | 6853019.88 | 11315222.77 | 0.144532E+09 | 3590.02 | 0.48 |
September | 79267710.25 | 3265809.40 | 5607.80 | 1424711.53 | 403830.67 | 0.116632E+09 | 0.160679E+09 | 1039.35 | 0.47 |
October | 94154192.33 | 0.00 | 0.00 | 379507.96 | 0.00 | 0.275773E+09 | 32220250.75 | 0.00 | 0.47 |
November | 37877651.56 | 0.00 | 0.00 | 41531.21 | 0.00 | 0.365969E+09 | 1145610.77 | 0.00 | 0.47 |
December | 10187561.59 | 0.00 | 0.00 | 3205.35 | 0.00 | 0.856697E+09 | 256599.94 | 0.00 | 0.47 |
Annual Sum or Average | 0.525550E+09 | 0.254718E+09 | 241852.40 | 12091569.67 | 22595746.95 | 0.394315E+10 | 0.923049E+09 | 13070.67 | 0.47 |
Minimum of Months | 10187561.59 | 0.00 | 0.00 | 3205.35 | 0.00 | 151348.54 | 256599.94 | 0.00 | 0.47 |
Maximum of Months | 94154192.33 | 0.121112E+09 | 117152.65 | 2672647.73 | 8709583.75 | 0.968705E+09 | 0.210710E+09 | 4513.89 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.648885E+09 | 0.00 | 0.00 | 1919052.99 | 0.00 | 0.530176E+10 | 0.342143E+09 | 0.00 | 0.53 |
February | 0.478072E+09 | 0.00 | 0.00 | 7177764.36 | 0.00 | 0.301521E+10 | 0.529454E+09 | 0.00 | 0.53 |
March | 0.489153E+09 | 0.00 | 0.00 | 11111916.30 | 0.00 | 0.215785E+10 | 0.670832E+09 | 0.00 | 0.53 |
April | 0.406379E+09 | 2664249.28 | 0.00 | 16475526.20 | 107858.59 | 0.926203E+09 | 0.121470E+10 | 0.00 | 0.54 |
May | 0.302306E+09 | 39889384.62 | 0.00 | 18013420.51 | 2222998.34 | 0.153833E+09 | 0.170541E+10 | 0.00 | 0.54 |
June | 0.165516E+09 | 0.444115E+09 | 381093.00 | 12667862.02 | 38997516.15 | 26339076.61 | 0.105920E+10 | 25338.65 | 0.54 |
July | 74799319.22 | 0.780378E+09 | 653688.36 | 9353301.73 | 53858257.73 | 1221124.33 | 0.739604E+09 | 27021.55 | 0.54 |
August | 0.145364E+09 | 0.366024E+09 | 259634.25 | 11850432.03 | 30212240.91 | 21258359.81 | 0.996268E+09 | 10772.42 | 0.54 |
September | 0.365698E+09 | 22676204.54 | 15227.13 | 18758986.06 | 927673.95 | 0.213490E+09 | 0.170231E+10 | 1930.05 | 0.54 |
October | 0.542413E+09 | 0.00 | 0.00 | 15535241.05 | 0.00 | 0.971602E+09 | 0.105678E+10 | 0.00 | 0.54 |
November | 0.452397E+09 | 0.00 | 0.00 | 4942049.81 | 0.00 | 0.179340E+10 | 0.351700E+09 | 0.00 | 0.54 |
December | 0.491859E+09 | 0.00 | 0.00 | 1104076.43 | 0.00 | 0.481945E+10 | 0.259201E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.456284E+10 | 0.165575E+10 | 1309642.74 | 0.128910E+09 | 0.126327E+09 | 0.194016E+11 | 0.106276E+11 | 65062.68 | 0.54 |
Minimum of Months | 74799319.22 | 0.00 | 0.00 | 1104076.43 | 0.00 | 1221124.33 | 0.259201E+09 | 0.00 | 0.53 |
Maximum of Months | 0.648885E+09 | 0.780378E+09 | 653688.36 | 18758986.06 | 53858257.73 | 0.530176E+10 | 0.170541E+10 | 27021.55 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.587531E+11 | 0.00 | 0.00 | 16003763.54 | 0.00 | 0.229086E+09 | 0.245947E+11 | 0.00 | 3.84 |
February | 0.272774E+11 | 0.00 | 0.00 | 23453553.63 | 0.00 | 0.00 | 0.301075E+11 | 0.00 | 3.83 |
March | 0.133499E+11 | 0.00 | 0.00 | 46575692.75 | 0.00 | 0.00 | 0.383335E+11 | 0.00 | 3.92 |
April | 0.180975E+10 | 0.00 | 0.00 | 85017703.05 | 0.00 | 0.00 | 0.427391E+11 | 0.00 | 4.22 |
May | 0.263199E+09 | 0.105914E+09 | 0.00 | 0.118541E+09 | 0.00 | 0.00 | 0.447525E+11 | 0.00 | 4.89 |
June | 4228817.35 | 0.411326E+10 | 0.00 | 86341881.08 | 0.00 | 0.00 | 0.316157E+11 | 0.00 | 5.19 |
July | 0.00 | 0.680371E+10 | 0.00 | 68380405.29 | 0.00 | 0.00 | 0.260542E+11 | 0.00 | 5.31 |
August | 3797549.59 | 0.246672E+10 | 0.00 | 76143199.32 | 0.00 | 0.00 | 0.332743E+11 | 0.00 | 5.22 |
September | 0.466770E+09 | 15217550.03 | 0.00 | 0.115720E+09 | 0.00 | 0.00 | 0.467115E+11 | 0.00 | 4.68 |
October | 0.289733E+10 | 0.00 | 0.00 | 0.112427E+09 | 0.00 | 0.00 | 0.457375E+11 | 0.00 | 4.19 |
November | 0.774620E+10 | 0.00 | 0.00 | 47407381.50 | 0.00 | 0.00 | 0.364984E+11 | 0.00 | 3.95 |
December | 0.491289E+11 | 0.00 | 0.00 | 19533444.95 | 0.00 | 0.00 | 0.269337E+11 | 0.00 | 3.82 |
Annual Sum or Average | 0.161701E+12 | 0.135048E+11 | 0.00 | 0.815544E+09 | 0.00 | 0.229086E+09 | 0.427353E+12 | 0.00 | 4.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 16003763.54 | 0.00 | 0.00 | 0.245947E+11 | 0.00 | 3.82 |
Maximum of Months | 0.587531E+11 | 0.680371E+10 | 0.00 | 0.118541E+09 | 0.00 | 0.229086E+09 | 0.467115E+11 | 0.00 | 5.31 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.553729E+11 | 0.00 | 0.00 | 22567777.68 | 0.00 | 84092031.49 | 0.328607E+11 | 0.00 | 4.08 |
February | 0.226955E+11 | 0.00 | 0.00 | 33856616.49 | 0.00 | 0.00 | 0.385507E+11 | 0.00 | 4.11 |
March | 0.858260E+10 | 0.00 | 0.00 | 63926792.77 | 0.00 | 0.00 | 0.474831E+11 | 0.00 | 4.26 |
April | 0.705722E+09 | 0.00 | 0.00 | 0.105587E+09 | 0.00 | 0.00 | 0.481686E+11 | 0.00 | 4.63 |
May | 46709691.33 | 0.114584E+09 | 0.00 | 0.134572E+09 | 0.00 | 0.00 | 0.486214E+11 | 0.00 | 5.29 |
June | 4433838.62 | 0.441104E+10 | 0.00 | 94548718.73 | 0.00 | 0.00 | 0.339544E+11 | 0.00 | 5.59 |
July | 0.00 | 0.729711E+10 | 0.00 | 73790159.06 | 0.00 | 0.00 | 0.277242E+11 | 0.00 | 5.67 |
August | 3417239.71 | 0.266426E+10 | 0.00 | 83360609.98 | 0.00 | 0.00 | 0.355964E+11 | 0.00 | 5.61 |
September | 82858270.96 | 16115940.04 | 0.00 | 0.134048E+09 | 0.00 | 0.00 | 0.510854E+11 | 0.00 | 5.07 |
October | 0.115015E+10 | 0.00 | 0.00 | 0.142155E+09 | 0.00 | 0.00 | 0.522286E+11 | 0.00 | 4.58 |
November | 0.329338E+10 | 0.00 | 0.00 | 64240111.81 | 0.00 | 0.00 | 0.450242E+11 | 0.00 | 4.31 |
December | 0.451968E+11 | 0.00 | 0.00 | 27329878.87 | 0.00 | 0.00 | 0.353994E+11 | 0.00 | 4.07 |
Annual Sum or Average | 0.137135E+12 | 0.145031E+11 | 0.00 | 0.979983E+09 | 0.00 | 84092031.49 | 0.496697E+12 | 0.00 | 4.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22567777.68 | 0.00 | 0.00 | 0.277242E+11 | 0.00 | 4.07 |
Maximum of Months | 0.553729E+11 | 0.729711E+10 | 0.00 | 0.142155E+09 | 0.00 | 84092031.49 | 0.522286E+11 | 0.00 | 5.67 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.787740E+10 | 0.00 | 0.00 | 95896601.37 | 0.00 | 0.342214E+09 | 0.102298E+12 | 0.00 | 17.76 |
February | 0.197801E+10 | 0.00 | 0.00 | 0.107293E+09 | 0.00 | 0.00 | 0.810642E+11 | 0.00 | 18.84 |
March | 0.641754E+09 | 0.00 | 0.00 | 0.141315E+09 | 0.00 | 0.00 | 0.773612E+11 | 0.00 | 19.47 |
April | 5040502.22 | 0.00 | 0.00 | 0.176267E+09 | 0.00 | 0.00 | 0.652450E+11 | 0.00 | 20.34 |
May | 7216938.21 | 0.192085E+09 | 0.00 | 0.180895E+09 | 0.00 | 0.00 | 0.578117E+11 | 0.00 | 21.85 |
June | 6500837.96 | 0.642115E+10 | 0.00 | 0.112692E+09 | 0.00 | 0.00 | 0.374116E+11 | 0.00 | 22.71 |
July | 7069597.81 | 0.105697E+11 | 0.00 | 85739583.48 | 0.00 | 0.00 | 0.289860E+11 | 0.00 | 22.80 |
August | 1731038.02 | 0.423175E+10 | 0.00 | 0.105058E+09 | 0.00 | 0.00 | 0.391023E+11 | 0.00 | 22.94 |
September | 43652834.78 | 32173526.81 | 0.00 | 0.179489E+09 | 0.00 | 0.00 | 0.627920E+11 | 0.00 | 21.44 |
October | 29310848.57 | 0.00 | 0.00 | 0.248403E+09 | 0.00 | 0.00 | 0.690423E+11 | 0.00 | 19.66 |
November | 10947213.90 | 0.00 | 0.00 | 0.133197E+09 | 0.00 | 0.00 | 0.667214E+11 | 0.00 | 19.29 |
December | 0.364373E+10 | 0.00 | 0.00 | 98710160.69 | 0.00 | 0.00 | 0.995678E+11 | 0.00 | 17.89 |
Annual Sum or Average | 0.142524E+11 | 0.214469E+11 | 0.00 | 0.166495E+10 | 0.00 | 0.342214E+09 | 0.787403E+12 | 0.00 | 20.42 |
Minimum of Months | 1731038.02 | 0.00 | 0.00 | 85739583.48 | 0.00 | 0.00 | 0.289860E+11 | 0.00 | 17.76 |
Maximum of Months | 0.787740E+10 | 0.105697E+11 | 0.00 | 0.248403E+09 | 0.00 | 0.342214E+09 | 0.102298E+12 | 0.00 | 22.94 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.242340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279111E+11 | 0.00 | 0.00 | 1.11 |
February | 0.604538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144694E+11 | 0.00 | 0.00 | 1.09 |
March | 0.109574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.679623E+10 | 0.00 | 0.00 | 1.07 |
April | 0.136326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214780E+09 | 0.00 | 0.00 | 1.06 |
May | 0.113970E+11 | 32496178.59 | 0.00 | 1546498.40 | 2822971.60 | 0.00 | 0.823010E+09 | 0.00 | 1.10 |
June | 0.726383E+10 | 0.106586E+10 | 0.00 | 2001720.81 | 0.211206E+09 | 0.00 | 0.936847E+09 | 0.00 | 1.14 |
July | 0.470766E+10 | 0.169006E+10 | 0.00 | 3372639.23 | 0.344109E+09 | 0.00 | 0.186020E+10 | 0.00 | 1.16 |
August | 0.746397E+10 | 0.509723E+09 | 0.00 | 2154908.61 | 0.234986E+09 | 0.00 | 0.129480E+10 | 0.00 | 1.16 |
September | 0.128298E+11 | 4539062.72 | 0.00 | 419873.96 | 1073958.34 | 0.00 | 0.397243E+09 | 0.00 | 1.08 |
October | 0.145856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171566E+09 | 0.00 | 0.00 | 1.03 |
November | 0.107682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413920E+10 | 0.00 | 0.00 | 1.07 |
December | 0.215363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253583E+11 | 0.00 | 0.00 | 1.10 |
Annual Sum or Average | 0.104228E+12 | 0.330269E+10 | 0.00 | 9495641.01 | 0.794199E+09 | 0.790605E+11 | 0.531211E+10 | 0.00 | 1.10 |
Minimum of Months | 0.215363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
Maximum of Months | 0.145856E+11 | 0.169006E+10 | 0.00 | 3372639.23 | 0.344109E+09 | 0.279111E+11 | 0.186020E+10 | 0.00 | 1.16 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:59:24
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.149578E+12 | 0.345071E+11 | 0.396418E+12 | 0.163742E+13 | 0.217204E+12 |
February | 0.234860E+12 | 0.274044E+11 | 0.315141E+12 | 0.133144E+13 | 0.141986E+12 |
March | 0.332902E+12 | 0.259770E+11 | 0.305161E+12 | 0.129162E+13 | 0.114741E+12 |
April | 0.446932E+12 | 0.170364E+11 | 0.202661E+12 | 0.885425E+12 | 0.110748E+12 |
May | 0.500896E+12 | 0.972869E+10 | 0.111318E+12 | 0.537177E+12 | 0.312036E+12 |
June | 0.522793E+12 | 0.376807E+10 | 0.397329E+11 | 0.230438E+12 | 0.597716E+12 |
July | 0.532194E+12 | 0.139796E+10 | 0.110815E+11 | 0.114574E+12 | 0.798390E+12 |
August | 0.441410E+12 | 0.404511E+10 | 0.473312E+11 | 0.264125E+12 | 0.582076E+12 |
September | 0.332926E+12 | 0.999479E+10 | 0.121448E+12 | 0.554908E+12 | 0.217950E+12 |
October | 0.179082E+12 | 0.161947E+11 | 0.202276E+12 | 0.854569E+12 | 0.105235E+12 |
November | 0.937959E+11 | 0.215201E+11 | 0.265188E+12 | 0.109970E+13 | 0.877488E+11 |
December | 0.105206E+12 | 0.327104E+11 | 0.380338E+12 | 0.156408E+13 | 0.196964E+12 |
Annual Sum or Average | 0.387257E+13 | 0.204285E+12 | 0.239809E+13 | 0.103655E+14 | 0.348279E+13 |
Minimum of Months | 0.937959E+11 | 0.139796E+10 | 0.110815E+11 | 0.114574E+12 | 0.877488E+11 |
Maximum of Months | 0.532194E+12 | 0.345071E+11 | 0.396418E+12 | 0.163742E+13 | 0.798390E+12 |