Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2023-10-16 08:59:47
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10850.12 | 956.35 | 956.35 |
Net Site Energy | 10850.12 | 956.35 | 956.35 |
Total Source Energy | 23453.23 | 2067.22 | 2067.22 |
Net Source Energy | 23453.23 | 2067.22 | 2067.22 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 405.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1051.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 766.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 242.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1745.01 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 651.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 655.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 164.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 183.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 3043.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5612.91 | 5237.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 405.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1051.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 766.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 242.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 32.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 655.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 164.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 183.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 3043.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 405.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1051.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 766.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 242.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1745.01 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 651.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 655.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 164.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 183.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 3043.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 88.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 172.92 | 303.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 232.86 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 494.74 | 461.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 88.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 172.92 | 303.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 232.86 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 494.74 | 461.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5612.914 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5612.914 | 100.00 |
Total On-Site and Utility Electric Sources | 5612.914 | 100.00 |
Total Electricity End Uses | 5612.914 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 101.82 | 5.14 |
Air to Air Heat Recovery for Heating | 1877.30 | 94.86 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 1979.12 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 537.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7863.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 9.1389 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.3365 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.3365 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 9.2031 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 6.1031 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.8125 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.3656 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 8.7188 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.5531 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.5531 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 6.3938 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.5531 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.3656 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.3656 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7219 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 6.3938 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 6.8557 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 6.8557 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.1389 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.3365 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.3365 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 9.2031 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 6.1031 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.8125 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.3656 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 8.7188 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.5531 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.5531 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 6.3938 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.5531 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.5531 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.5531 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.3656 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.3656 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7219 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 6.3938 | 18.58 | 0.0000 | |
Total | 11345.29 | 6.8557 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 6.8557 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.4542 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-JUL-19:19 | 15-JAN-22:30 | - | - | - | - | - | - | - | - | - | - | 02-JAN-21:19 |
Heating | 0.00 | 181318.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 142141.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 88772.42 | 50082.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 32159.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42761.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 7664.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3979.24 | 264159.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1828.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 407587.22 | 495560.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 181318.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 142141.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58789.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 24992.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 25090.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1855.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 42761.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 7664.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3979.24 | 264159.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 530.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1056.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 439.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3331.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2427.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 768.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5526.46 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2063.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2075.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 519.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 581.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.37 | 3298.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 195.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 17776.10 | 5677.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 38.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 293.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 213.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 67.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.11 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 182.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 45.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 51.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 290.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1566.83 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 38.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 293.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 213.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 67.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.11 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 182.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 45.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 51.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 290.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1566.83 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 3.11 | 0.484605 | 0.413000 | 1.29 | 1.00 | 0.500000 | 0.000786 | 0.000049 | 1.29 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.434528 | 0.117618 | 0.300000 | 0.130358 | 0.325816 | 0.500000 | 0.003239 | 0.000028 | 0.137983 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.292383 | 0.202419 | 0.472000 | 0.138005 | 0.539783 | 0.500000 | 0.001882 | 0.000013 | 0.138005 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.283182 | 0.441953 | 0.300000 | 0.084955 | 1.00 | 0.500000 | 0.000862 | 0.000018 | 0.087685 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.137687 | 0.524424 | 0.632000 | 0.087018 | 1.00 | 0.500000 | 0.000727 | 0.000012 | 0.087018 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.97 | 0.059465 | 0.300000 | 1.19 | 0.300000 | 0.500000 | 0.025425 | 0.000065 | 1.19 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.80 | 0.080049 | 0.566000 | 1.02 | 0.566000 | 0.500000 | 0.004760 | 0.000097 | 1.02 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.63 | 0.176992 | 0.506000 | 2.85 | 0.506000 | 0.500000 | 0.002153 | 0.000246 | 2.85 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.78 | 0.667183 | 0.402000 | 0.715150 | 1.00 | 0.500000 | 0.000571 | 0.000111 | 0.715150 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.68 | 0.094219 | 0.667000 | 1.79 | 0.667000 | 0.500000 | 0.004044 | 0.000120 | 1.79 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.81 | 0.089904 | 0.636000 | 1.79 | 0.636000 | 0.500000 | 0.004238 | 0.000121 | 1.79 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.76 | 0.051258 | 0.300000 | 0.828662 | 0.300000 | 0.500000 | 0.013369 | 0.000049 | 0.828662 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.947701 | 0.331369 | 0.300000 | 0.284310 | 0.883651 | 0.500000 | 0.001150 | 0.000067 | 0.325243 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 5580.66 | 0.000049 | 116.38 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3246.54 | 0.000028 | 88.60 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1515.34 | 0.000013 | 34.34 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2062.98 | 0.000018 | 56.30 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1395.18 | 0.000012 | 33.90 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 7418.08 | 0.000065 | 158.27 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 11043.99 | 0.000097 | 249.88 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 28127.03 | 0.000246 | 628.24 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5973.65 | 0.000052 | 170.70 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5973.32 | 0.000052 | 170.69 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 34368.81 | 0.000301 | 982.10 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 34379.45 | 0.000301 | 982.41 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5973.65 | 0.000052 | 170.70 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5973.32 | 0.000052 | 170.69 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12641.59 | 0.000111 | 314.66 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1829.30 | 0.000016 | 52.27 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1830.32 | 0.000016 | 52.30 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8764.28 | 0.000077 | 250.43 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 13738.33 | 0.000120 | 298.43 |
DINING_FLR_6 VAV BOX REHEAT COIL | 13866.67 | 0.000121 | 301.51 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 5647.48 | 0.000049 | 121.36 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7652.90 | 0.000067 | 208.86 |
VAV WITH REHEAT HEATING COIL | 194543.04 | 0.001702 | 3255.58 |
FLR_3_DOAS HEATING COIL | 15066.37 | 0.000132 | 252.13 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.44 | 0.000052 | 0.000471 |
ROOM_2_FLR_3 FAN COIL | 1.42 | 0.000052 | 0.000466 |
ROOM_3_MULT19_FLR_3 FAN COIL | 7.17 | 0.000301 | 0.002331 |
ROOM_4_MULT19_FLR_3 FAN COIL | 7.09 | 0.000301 | 0.002430 |
ROOM_5_FLR_3 FAN COIL | 1.26 | 0.000052 | 0.000413 |
ROOM_6_FLR_3 FAN COIL | 1.25 | 0.000052 | 0.000409 |
ROOM_1_FLR_6 FAN COIL | 0.382476 | 0.000016 | 0.000125 |
ROOM_2_FLR_6 FAN COIL | 0.377274 | 0.000016 | 0.000123 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.52 | 0.000077 | 0.000507 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.44 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.42 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.17 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.09 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.26 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.25 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.382476 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.377274 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.52 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008520 | 12.80 | 0.008500 | 0.000471 | 1.44 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008520 | 12.80 | 0.008500 | 0.000466 | 1.42 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008456 | 12.80 | 0.008456 | 0.002331 | 7.17 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008693 | 12.80 | 0.008500 | 0.002430 | 7.09 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008522 | 12.80 | 0.008500 | 0.000413 | 1.26 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008522 | 12.80 | 0.008500 | 0.000409 | 1.25 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008519 | 12.80 | 0.008500 | 0.000125 | 0.382476 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008519 | 12.80 | 0.008500 | 0.000123 | 0.377274 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008586 | 12.80 | 0.008500 | 0.000507 | 1.52 | |
VAV WITH REHEAT COOLING COIL | 28.88 | 6.70 | 0.007893 | 10.58 | 0.007893 | 0.017481 | 26.49 | 489425.10 |
FLR_3_DOAS COOLING COIL | 35.10 | 6.70 | 0.005699 | 11.74 | 0.005699 | 0.001722 | 2.05 | 48199.93 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 14.32 | 12.19 | 26.64 | 12.19 | 26.49 | 26.49 | 0.300000 | 0.460155 | 26.49 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 26.49 | 11.66 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 26.49 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.017481 | 0.000027 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001702 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001722 | 0.000277 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000132 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.026479 | 5456.32 | |
HEATSYS1 PUMP | 0.003750 | 1129.24 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003750 | 0.449962 |
COOLSYS1 | 0.026479 | 3.18 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 428612.26 | 428612.26 | 0.003750 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.026479 | 3777.60 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.026479 | 741339.06 | 742040.49 | 84.59 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 9.139 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.519 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.336 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.096 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.336 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.096 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 9.203 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.583 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 6.103 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.793 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.813 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.343 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.366 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.746 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 8.719 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.789 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.366 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 78.186 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.366 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 78.186 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.722 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2946.209 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 18084.325 | 9.139 | 169.807 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18084.325 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 894.495 | 13.336 | 82.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 894.495 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1035.829 | 13.336 | 82.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1035.829 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 1511.551 | 9.203 | 569.967 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1511.551 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 578.329 | 6.103 | 283.494 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 578.329 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 453.605 | 5.813 | 54.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 453.605 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1957.673 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1957.673 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11405.759 | 8.719 | 27.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11405.759 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 111.660 | 4.553 | 74.440 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.660 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 111.691 | 4.553 | 74.460 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.691 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2489.757 | 6.394 | 118.803 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.757 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 111.691 | 4.553 | 74.460 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.691 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3437.839 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3437.839 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3437.839 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3437.839 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1210.923 | 11.722 | 54.453 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1210.923 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2635.024 | 6.394 | 118.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2635.024 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.9242 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.217 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.286 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.107 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.174 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9147 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6546 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6103 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7359 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6841 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.28612306E-14 | 0.35438919E-16 | -0.14997333E-09 | 0.48037931E-16 |
29 | 8 | 0.21910456E-07 | 0.12451452E-12 | 0.37817107E-03 | -0.24912943E-09 |
30 | 7 | -0.12252860E-01 | 0.64616398E-08 | -0.23102096E-01 | 0.13931948E-03 |
31 | 6 | 0.40565756 | 0.22511349E-05 | 0.47235308 | -0.47513834E-02 |
32 | 5 | -5.1935619 | 0.84157732E-04 | -4.4432762 | 0.63221026E-01 |
33 | 4 | 33.016121 | 0.68920660E-03 | 21.448225 | -0.42229901 |
34 | 3 | -111.25447 | 0.15035857E-02 | -55.639617 | 1.5156026 |
35 | 2 | 197.15924 | 0.84653085E-03 | 77.889127 | -2.9011628 |
36 | 1 | -171.17492 | 0.90445513E-04 | -55.258822 | 2.7457697 |
37 | 0 | 57.057407 | 0.51539406E-06 | 15.557951 | |
38 | 9 | 0.12430042E-14 | 0.43603463E-16 | -0.13615479E-09 | -0.52742981E-17 |
39 | 8 | 0.19963588E-07 | 0.16114398E-12 | 0.35741204E-03 | -0.22699287E-09 |
40 | 7 | -0.11632381E-01 | 0.85488282E-08 | -0.22208377E-01 | 0.13226440E-03 |
41 | 6 | 0.38879653 | 0.30047059E-05 | 0.45796739 | -0.45526330E-02 |
42 | 5 | -5.0290001 | 0.11318598E-03 | -4.3326723 | 0.61180550E-01 |
43 | 4 | 32.288109 | 0.93328928E-03 | 21.015642 | -0.41263319 |
44 | 3 | -109.70522 | 0.20484795E-02 | -54.784283 | 1.4932205 |
45 | 2 | 195.62339 | 0.11595496E-02 | 77.105128 | -2.8767741 |
46 | 1 | -170.60747 | 0.12450863E-03 | -55.031726 | 2.7358244 |
47 | 0 | 57.057407 | 0.71328115E-06 | 15.596176 | |
48 | 9 | 0.10418955E-14 | 0.45554749E-16 | -0.13285794E-09 | -0.34221686E-17 |
49 | 8 | 0.19498290E-07 | 0.16949498E-12 | 0.35235048E-03 | -0.22170227E-09 |
50 | 7 | -0.11480752E-01 | 0.90423087E-08 | -0.21989859E-01 | 0.13054032E-03 |
51 | 6 | 0.38467563 | 0.31853038E-05 | 0.45444290 | -0.45040579E-02 |
52 | 5 | -4.9887746 | 0.12022067E-03 | -4.3055366 | 0.60681782E-01 |
53 | 4 | 32.110117 | 0.99300969E-03 | 20.909427 | -0.41027004 |
54 | 3 | -109.32633 | 0.21828955E-02 | -54.574228 | 1.4877470 |
55 | 2 | 195.24766 | 0.12373115E-02 | 76.912747 | -2.8708078 |
56 | 1 | -170.46860 | 0.13302463E-03 | -54.976289 | 2.7333905 |
57 | 0 | 57.057407 | 0.76310210E-06 | 15.605744 | |
58 | 9 | -0.19728226E-15 | 0.38070760E-16 | -0.14134637E-09 | 0.10329039E-17 |
59 | 8 | 0.20696804E-07 | 0.14765672E-12 | 0.36530744E-03 | -0.23532978E-09 |
60 | 7 | -0.11868633E-01 | 0.77667999E-08 | -0.22548754E-01 | 0.13495068E-03 |
61 | 6 | 0.39521686 | 0.27204939E-05 | 0.46345169 | -0.46283129E-02 |
62 | 5 | -5.0916664 | 0.10217830E-03 | -4.3748670 | 0.61957574E-01 |
63 | 4 | 32.565369 | 0.84029717E-03 | 21.180735 | -0.41631434 |
64 | 3 | -110.29532 | 0.18400486E-02 | -55.110745 | 1.5017457 |
65 | 2 | 196.20849 | 0.10394005E-02 | 77.404245 | -2.8860650 |
66 | 1 | -170.82368 | 0.11139293E-03 | -55.118150 | 2.7396138 |
67 | 0 | 57.057407 | 0.63685742E-06 | 15.581450 | |
68 | 9 | 0.13059652E-14 | 0.41030072E-16 | -0.13816519E-09 | -0.47111965E-17 |
69 | 8 | 0.20247126E-07 | 0.15597406E-12 | 0.36047671E-03 | -0.23021680E-09 |
70 | 7 | -0.11724123E-01 | 0.82470298E-08 | -0.22340566E-01 | 0.13330755E-03 |
71 | 6 | 0.39128975 | 0.28947446E-05 | 0.46009809 | -0.45820219E-02 |
72 | 5 | -5.0533361 | 0.10891817E-03 | -4.3490697 | 0.61482301E-01 |
73 | 4 | 32.395785 | 0.89717001E-03 | 21.079809 | -0.41406279 |
74 | 3 | -109.93440 | 0.19673976E-02 | -54.911173 | 1.4965315 |
75 | 2 | 195.85064 | 0.11127485E-02 | 77.221372 | -2.8803827 |
76 | 1 | -170.69145 | 0.11939355E-03 | -55.065279 | 2.7372963 |
77 | 0 | 57.057407 | 0.68346468E-06 | 15.590432 | |
78 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
79 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
80 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
81 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
82 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
83 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
84 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
85 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
86 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
87 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
88 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
89 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
90 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
91 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
92 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
93 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3856_SHGC_0.4 | 37 | 1 | VerySmooth | 2.191 | 2.191 | 1.000 | 0.401 | ||
2 | RESWINDOW_U_0.3856_SHGC_0.4 | 38 | 1 | VerySmooth | 2.191 | 2.191 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.40174E-002 | 0.31435 | 0.47878 | 0.47878 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11969 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.40174E-002 | 0.31435 | 0.47878 | 0.47878 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11969 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1410 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 6.6789E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1572 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 7.3808E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1048 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.9875E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.2077E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.3979E-002 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1599 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 8.1248E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1788 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 8.9635E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1161 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.0104E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 4.7248E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.9114E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.4238E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.9690E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.6310E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.4840E-002 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.5281E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0124E-002 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.1419E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.4687E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.4238E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.9690E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.6310E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.4840E-002 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.5281E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0124E-002 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.1419E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.4687E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 35222.30123 | 35222.30123 | 3.11154 | 3.11154 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:00:00 | 28.35000 | 5.68899E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4918.48384 | 4918.48384 | 0.43453 | 0.43453 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76250 | 5.69886E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2647.84697 | 2647.84697 | 0.13798 | 0.13798 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3309.37925 | 3309.37925 | 0.29238 | 0.29238 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.98500 | 5.69610E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 916.55026 | 916.55026 | 4.77642E-002 | 9.17347E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3206.01097 | 3206.01097 | 0.28318 | 0.28318 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 31.18500 | 5.69333E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1682.61027 | 1682.61027 | 8.76852E-002 | 8.76852E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1558.79363 | 1558.79363 | 0.13769 | 0.13769 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 32.31000 | 5.69506E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1017.68192 | 1017.68192 | 5.30341E-002 | 5.77652E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44922.58052 | 44922.58052 | 3.96830 | 3.96830 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 34.83000 | 5.69897E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2254.51083 | 2254.51083 | 0.11748 | 0.11748 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 20331.04071 | 20331.04071 | 1.79780 | 1.79780 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76250 | 5.69886E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 6628.58040 | 6628.58040 | 0.34542 | 0.67639 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 63728.00914 | 63728.00914 | 5.63210 | 5.63210 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.87500 | 5.69904E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 15761.52566 | 15761.52566 | 0.82138 | 1.89399 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 12111.55142 | 12111.55142 | 1.44167 | 1.44167 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.39000 | 5.69673E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5973.77382 | 5973.77382 | 0.31313 | 0.31313 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11968.77561 | 11968.77561 | 1.42467 | 1.42467 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5973.44532 | 5973.44532 | 0.31311 | 0.31311 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 60227.48318 | 60227.48318 | 7.16881 | 7.16881 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.98750 | 5.69921E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 34369.15747 | 34369.15747 | 1.80159 | 1.80159 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 59580.43822 | 59580.43822 | 7.09239 | 7.09239 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.96500 | 5.69918E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 34379.79905 | 34379.79905 | 1.80215 | 1.80215 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10606.88481 | 10606.88481 | 1.26256 | 1.26256 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 29.58750 | 5.69088E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5973.77382 | 5973.77382 | 0.31313 | 0.31313 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10506.24764 | 10506.24764 | 1.25059 | 1.25059 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 28.82250 | 5.68971E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5973.44532 | 5973.44532 | 0.31311 | 0.31311 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 20138.52991 | 20138.52991 | 1.77898 | 1.77898 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.69938E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 9537.81458 | 9537.81458 | 0.49705 | 0.49705 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3213.20632 | 3213.20632 | 0.38248 | 0.38248 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.39000 | 5.69673E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1829.34061 | 1829.34061 | 9.58891E-002 | 9.58891E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3169.49924 | 3169.49924 | 0.37727 | 0.37727 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1830.35951 | 1830.35951 | 9.59425E-002 | 9.59425E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 12804.96687 | 12804.96687 | 1.52426 | 1.52426 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.98750 | 5.69921E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 8764.42040 | 8764.42040 | 0.45941 | 0.45941 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 30323.59435 | 30323.59435 | 2.68229 | 2.68229 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.69938E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5973.03234 | 5973.03234 | 0.31127 | 1.18780 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31779.60448 | 31779.60448 | 2.81103 | 2.81103 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.69938E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 6106.89822 | 6106.89822 | 0.31825 | 1.18780 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31182.27584 | 31182.27584 | 2.76221 | 2.76221 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.88500 | 5.69749E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2059.13360 | 2059.13360 | 0.10729 | 0.36735 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -7.90000 | 2.34317E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10728.36939 | 10728.36939 | 0.94770 | 0.94770 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 35.10000 | 5.69938E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6241.10059 | 6241.10059 | 0.32524 | 0.32524 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 423894.52 | 26.48743 | 26.48743 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 183195.00 | 7.48271 | 7.48271 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 45524.16 | 20.57976 | 2.05125 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 50219.47 | 5.50746 | 2.05125 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.11154 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.48461 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.41300 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28507 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.86207E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.88221E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28507 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5580.66158 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.88221E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 116.37508 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.43453 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11762 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13036 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32582 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.23930E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.84021E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13798 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3246.53711 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.84021E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 88.60246 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.29238 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20242 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47200 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13800 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53978 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.88224E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.32568E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13800 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1515.33846 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.32568E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 34.34273 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.28318 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.44195 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49547E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.62083E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.80478E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.76852E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2062.97907 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.80478E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 56.30021 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.13769 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.52442 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.63200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.70184E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.26511E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.22056E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.70184E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1395.17508 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.22056E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 33.90140 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.96830 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.94648E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.19049 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54249E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.48966E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.19049 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7418.08370 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.48966E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 158.26673 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.79780 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.00493E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.56600 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.01756 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56600 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.75956E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.66176E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.01756 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11043.98771 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.66176E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 249.87519 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.63210 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17699 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50600 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.84984 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50600 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.15264E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.46068E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.84984 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 28127.02735 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.46068E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 628.24372 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.44167 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.44167 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.22601E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.71445E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80693 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.52026E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.71445E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.44167 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5973.64782 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.22601E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 170.70176 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.42467 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.42467 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.22572E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.65914E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80693 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.52047E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.65914E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.42467 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5973.31932 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.22572E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 170.69237 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.16881 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.16881 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.00673E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.33114E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80727 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.45624E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.45624E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.33114E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.16881 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 34368.80880 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.00673E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 982.10246 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.09239 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.09239 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.00766E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.42956E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80627 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.69344E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.42956E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.09239 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 34379.45026 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.00766E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 982.40654 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.26256 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.26256 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.22601E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.13105E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80693 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.52228E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.13105E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.26256 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5973.64782 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.22601E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 170.70176 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.25059 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.25059 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.22572E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.09190E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80693 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.52232E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.09190E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.25059 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5973.31932 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.22572E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 170.69237 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.77898 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.66718 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.40200 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.71515 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.71058E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.10594E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71515 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12641.58645 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.10594E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 314.66320 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.38248 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.38248 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.60035E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.25036E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80693 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51912E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.25036E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.38248 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1829.30327 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.60035E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 52.27159 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.37727 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.37727 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.60125E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.23343E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80693 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51935E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.23343E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.37727 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1830.32215 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.60125E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 52.30069 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.52426 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.52426 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.66737E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.07462E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80656 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58615E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.07462E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.52426 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8764.27736 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.66737E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 250.43409 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.68229 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.42192E-002 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.66700 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78909 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66700 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.04376E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.20189E-004 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78909 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13738.33060 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.20189E-004 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 298.42645 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.81103 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.99041E-002 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.63600 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78781 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63600 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.23785E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21312E-004 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78781 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13866.67495 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21312E-004 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 301.50681 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.76221 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.12576E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.82866 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.33693E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.94066E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.82866 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5647.47647 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.94066E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 121.36118 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94770 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33137 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28431 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88365 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14977E-003 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.69509E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32524 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7652.89564 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.69509E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 208.86239 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 14.32073 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 12.18831 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 26.63972 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 12.18831 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 26.48743 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 26.48743 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.46015 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 26.48743 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 26.48743 |
338 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 11.66146 |
339 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.88046 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.58096 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.89307E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.89307E-003 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 489425.09967 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.74811E-002 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 26.48743 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 194543.04016 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.70195E-003 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3255.58388 |
351 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 26.48743 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.74811E-002 |
353 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.72403E-005 |
354 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.70195E-003 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
356 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
357 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 35.10000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.73601 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 5.69938E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 5.69938E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 48199.92810 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.72159E-003 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 15066.37152 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31807E-004 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 252.12846 |
369 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.72159E-003 |
371 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.76599E-004 |
372 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.31807E-004 |
373 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.64789E-002 |
374 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 5456.32265 |
375 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.74969E-003 |
376 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.44996 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.74969E-003 |
378 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1129.24107 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 428612.26198 |
381 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 428612.26000 |
382 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.74969E-003 |
383 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.64789E-002 |
384 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.17747 |
385 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.64789E-002 |
386 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3777.59620 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.64789E-002 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 741339.05610 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 742040.49000 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 84.59262 |
391 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
392 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
393 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
394 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
395 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 5609.98 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3260.47 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1522.80 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2071.83 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1401.68 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 7456.53 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 11098.46 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 28266.92 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 6436.77 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 6436.41 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 37033.16 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 37044.62 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 6436.77 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 6436.41 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12699.64 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1971.07 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1972.17 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 9443.49 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 13808.82 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 13937.79 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 5676.62 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7685.73 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 142162.94 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 11009.80 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 24534.81 | 17959.76 | 6575.05 | 0.73 | 5428.15 | 55.06 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 24246.49 | 17748.33 | 6498.16 | 0.73 | 5363.92 | 54.40 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 122066.83 | 89406.08 | 32660.75 | 0.73 | 28197.71 | 286.00 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 124404.14 | 89529.46 | 34874.69 | 0.72 | 25951.32 | 263.21 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 21494.53 | 15730.98 | 5763.55 | 0.73 | 4751.76 | 48.20 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 21290.76 | 15581.77 | 5708.98 | 0.73 | 4706.64 | 47.74 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 6507.77 | 4764.32 | 1743.45 | 0.73 | 1440.44 | 14.61 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 6419.52 | 4699.60 | 1719.92 | 0.73 | 1420.78 | 14.41 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 26244.22 | 19084.12 | 7160.09 | 0.73 | 5665.42 | 57.46 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 722730.57 | 428023.66 | 294706.91 | 0.59 | 152391.69 | 1545.64 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 47472.21 | 29284.36 | 18187.85 | 0.62 | 4618.55 | 46.84 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.217 | 1.029 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.217 | 1.029 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.217 | 1.029 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.217 | 1.029 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.174 | 0.999 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.174 | 0.999 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.174 | 0.999 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.174 | 0.999 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.174 | 0.999 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.1600724142E-002 | 2.2246415793E-002 | Fail | Pass | 0.1359914797 | 0.7406153930 | Fail | Fail |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.1621880021E-002 | 0.1126082455 | Pass | Pass | 0.1585890654 | 0.6350035820 | Fail | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.3951115246E-002 | 5.9010822162E-002 | Pass | Pass | 0.2027242117 | 1.4153514787 | Fail | Fail |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.3073101100E-002 | 2.3513148256E-002 | Pass | Pass | 0.1102682119 | 0.3014540816 | Fail | Fail |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.9875933674E-002 | 3.2452884993E-002 | Pass | Pass | 0.1192271783 | 0.2573751712 | Fail | Fail |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.5163909702E-002 | 0.2177439434 | Fail | Pass | 6.4376648260E-002 | 0.1711520496 | Pass | Fail |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.2841729587E-002 | 0.1508355419 | Pass | Pass | 0.1229966551 | 0.4852662966 | Fail | Fail |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.8832556312E-002 | 5.8175622102E-002 | Fail | Pass | 0.1410263265 | 0.8033519200 | Fail | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.2925679057E-002 | 0.2148921550 | Pass | Pass | 0.2299719869 | 0.6166698855 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.7177610576E-002 | 0.2205606926 | Pass | Pass | 0.4465649685 | 1.8275086035 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.7022029326E-002 | 3.6118165652E-002 | Pass | Pass | 3.4897837237E-002 | 6.1685109075E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.4080313932E-002 | 5.5384646706E-002 | Pass | Pass | 0.8289467686 | 6.0265397748 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.1918557955E-002 | 0.2933573666 | Pass | Pass | 0.2445730540 | 0.6805399165 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.8516942485E-002 | 0.1516810787 | Pass | Pass | 0.3091640452 | 1.2518387442 | Pass | Fail |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.9348568346E-002 | 2.2469610762E-002 | Pass | Pass | 0.1312960806 | 0.5045295885 | Fail | Fail |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.2201103206E-002 | 0.2027100330 | Pass | Pass | 0.2810086573 | 0.8357781613 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.5483827980E-002 | 0.2815023099 | Pass | Pass | 1.4871760697 | 14.4618105353 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.1805043568E-002 | 0.3399177658 | Pass | Pass | 0.5068027018 | 3.2718322413 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1180056595 | 0.1809013854 | Fail | Pass | 0.3106389342 | 2.7223422430 | Fail | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1089576897 | 0.1651145517 | Fail | Pass | 0.1849559331 | 1.2947109493 | Fail | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1182400184 | 0.3423520706 | Fail | Pass | 9.6037836260E-002 | 0.2842368051 | Pass | Fail |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.4682955697E-002 | 3.5461507634E-002 | Pass | Pass | 0.1229237327 | 0.4222887920 | Fail | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5187.34 | 104.22 | 1176.96 | 5872.23 | 4780.64 | 17121.40 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.191 | 0.401 | 0.402 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.191 | 0.401 | 0.402 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.191 | 0.401 | 0.402 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.191 | 0.401 | 0.402 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.191 | 0.401 | 0.402 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.191 | 0.401 | 0.402 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.191 | 0.401 | 0.402 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.191 | 0.401 | 0.402 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.191 | 0.401 | 0.402 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.191 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 432.95 | 2.191 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.191 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.1389 | 1978.83 | 18084.33 | LightsWired | LTG_SCH_BASEMENT | 51.16 | 168.00 | 51.10 | 0.0000 | Y | 173.46 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.3365 | 67.07 | 894.50 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.61 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.3365 | 77.67 | 1035.83 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 9.97 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 9.2031 | 164.24 | 1511.55 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 16.63 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 6.1031 | 94.76 | 578.33 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 2.78 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.8125 | 78.04 | 453.60 | LightsWired | LTG_SCH_LAUNDRY | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 4.37 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.3656 | 188.86 | 1957.67 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.72 | 0.0000 | Y | 17.90 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 8.7188 | 1308.19 | 11405.76 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 56.90 | 0.0000 | Y | 121.82 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.5531 | 156.09 | 710.69 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.5531 | 156.07 | 710.61 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.5531 | 1863.81 | 8486.17 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 76.02 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.5531 | 1864.32 | 8488.49 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 76.04 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.5531 | 156.09 | 710.69 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.5531 | 156.07 | 710.61 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 6.3938 | 1557.62 | 9959.03 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 109.60 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.5531 | 39.02 | 177.67 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.59 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.5531 | 39.02 | 177.65 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.59 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.5531 | 220.77 | 1005.22 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 9.00 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.3656 | 331.66 | 3437.84 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 53.66 | 0.0000 | Y | 34.63 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.3656 | 331.66 | 3437.84 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 53.66 | 0.0000 | Y | 34.63 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7219 | 103.30 | 1210.92 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.33 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 6.3938 | 412.12 | 2635.02 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 29.00 |
Interior Lighting Total | 6.8557 | 11345.29 | 77780.02 | 507.09 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 11405.76 | 798.40 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 11405.76 | 0.00 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1957.67 | 763.49 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 1957.67 | 0.00 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3437.84 | 687.57 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3437.84 | 0.00 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3437.84 | 687.57 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3437.84 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 15448.40 | AstronomicalClock | - | 83.71 | 83.71 | 242.74 | |
Exterior Lighting Total | 15448.40 | 242.74 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 428612.26 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 742040.49 | 2.96 | 742170.92 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13199.45 | 24534.81 | 17959.76 | 6575.05 | 0.73 | - | 5428.15 | 55.06 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13044.60 | 24246.49 | 17748.33 | 6498.16 | 0.73 | - | 5363.92 | 54.40 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 65266.91 | 122066.83 | 89406.08 | 32660.75 | 0.73 | - | 28197.71 | 286.00 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 68022.47 | 124404.14 | 89529.46 | 34874.69 | 0.72 | - | 25951.32 | 263.21 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11566.05 | 21494.53 | 15730.98 | 5763.55 | 0.73 | - | 4751.76 | 48.20 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11456.44 | 21290.76 | 15581.77 | 5708.98 | 0.73 | - | 4706.64 | 47.74 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3500.73 | 6507.77 | 4764.32 | 1743.45 | 0.73 | - | 1440.44 | 14.61 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3453.33 | 6419.52 | 4699.60 | 1719.92 | 0.73 | - | 1420.78 | 14.41 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 14207.85 | 26244.22 | 19084.12 | 7160.09 | 0.73 | - | 5665.42 | 57.46 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 489425.10 | 722730.57 | 428023.66 | 294706.91 | 0.59 | - | 152391.69 | 1545.64 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 48199.93 | 47472.21 | 29284.36 | 18187.85 | 0.62 | - | 4618.55 | 46.84 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 5580.66 | 5609.98 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3246.54 | 3260.47 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1515.34 | 1522.80 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2062.98 | 2071.83 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1395.18 | 1401.68 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 7418.08 | 7456.53 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11043.99 | 11098.46 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 28127.03 | 28266.92 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5973.65 | 6436.77 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5973.32 | 6436.41 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 34368.81 | 37033.16 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 34379.45 | 37044.62 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5973.65 | 6436.77 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5973.32 | 6436.41 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12641.59 | 12699.64 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1829.30 | 1971.07 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1830.32 | 1972.17 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 8764.28 | 9443.49 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 13738.33 | 13808.82 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 13866.67 | 13937.79 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 5647.48 | 5676.62 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7652.90 | 7685.73 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 194543.04 | 142162.94 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 15066.37 | 11009.80 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.44 | 1014.41 | 703.64 | 1.00 | 1.12 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.42 | 1002.45 | 703.64 | 1.00 | 1.12 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 7.17 | 5044.24 | 703.64 | 1.00 | 0.95 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 7.09 | 4990.47 | 703.64 | 1.00 | 0.95 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.26 | 888.39 | 703.64 | 1.00 | 1.14 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.25 | 879.96 | 703.64 | 1.00 | 1.15 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.38 | 269.12 | 703.64 | 1.00 | 1.56 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.38 | 265.46 | 703.64 | 1.00 | 1.57 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.52 | 1072.53 | 703.64 | 1.00 | 1.11 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 26.49 | 59348.76 | 2240.64 | 1.00 | 1.11 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.026479 | 5456.32 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003750 | 1129.24 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.026479 | 3777.60 | 142664.32 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 35222.30 | 35222.30 | 17.80 | 3.112 | 3.112 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:00:00 | 24.00 | 24.00 | 0.00919 | 28.35 | 0.00569 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4918.48 | 4918.48 | 73.33 | 0.435 | 0.435 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00893 | 34.76 | 0.00570 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3309.38 | 3309.38 | 42.61 | 0.292 | 0.292 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00931 | 32.98 | 0.00570 | 0.092 | 0.00 |
MECH_FLR_1 | 3206.01 | 3206.01 | 19.52 | 0.283 | 0.283 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00860 | 31.19 | 0.00569 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1558.79 | 1558.79 | 16.45 | 0.138 | 0.138 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00869 | 32.31 | 0.00570 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44922.58 | 44922.58 | 575.64 | 3.968 | 3.968 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00853 | 34.83 | 0.00570 | 0.000 | 0.00 |
CAFE_FLR_1 | 20331.04 | 20331.04 | 107.65 | 1.798 | 1.798 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.01003 | 34.76 | 0.00570 | 0.676 | 0.00 |
LOBBY_FLR_1 | 63728.01 | 63728.01 | 48.71 | 5.632 | 5.632 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.00996 | 34.88 | 0.00570 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 12111.55 | 12111.55 | 310.38 | 1.442 | 1.442 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 33.39 | 0.00570 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11968.78 | 11968.78 | 306.75 | 1.425 | 1.425 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 33.21 | 0.00570 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 60227.48 | 60227.48 | 2455.87 | 7.169 | 7.169 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 21.11 | 21.11 | 0.00846 | 34.99 | 0.00570 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 59580.44 | 59580.44 | 2428.83 | 7.092 | 7.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 21.11 | 21.11 | 0.00869 | 34.97 | 0.00570 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10606.88 | 10606.88 | 271.82 | 1.263 | 1.263 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 21.11 | 21.11 | 0.00852 | 29.59 | 0.00569 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10506.25 | 10506.25 | 269.27 | 1.251 | 1.251 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 21.11 | 21.11 | 0.00852 | 28.82 | 0.00569 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 20138.53 | 20138.53 | 51.72 | 1.779 | 1.779 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00939 | 35.10 | 0.00570 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3213.21 | 3213.21 | 82.34 | 0.382 | 0.382 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 33.39 | 0.00570 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3169.50 | 3169.50 | 81.23 | 0.377 | 0.377 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 33.21 | 0.00570 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 12804.97 | 12804.97 | 522.00 | 1.524 | 1.524 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 21.11 | 21.11 | 0.00859 | 34.99 | 0.00570 | 0.099 | 0.00 |
BANQUET_FLR_6 | 30323.59 | 30323.59 | 91.43 | 2.682 | 2.682 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.98 | 0.01034 | 35.10 | 0.00570 | 1.188 | 0.00 |
DINING_FLR_6 | 31779.60 | 31779.60 | 95.82 | 2.811 | 2.811 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.98 | 0.01026 | 35.10 | 0.00570 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31182.28 | 31182.28 | 301.85 | 2.762 | 2.762 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01005 | 33.89 | 0.00570 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10728.37 | 10728.37 | 26.03 | 0.948 | 0.948 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00893 | 35.10 | 0.00570 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 22.88 | 0.00234 | -7.90 | 0.00234 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2647.85 | 2647.85 | 39.48 | 0.138 | 0.138 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00759 | -7.90 | 0.00234 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 916.55 | 916.55 | 11.80 | 0.048 | 0.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00755 | -7.90 | 0.00234 | 0.092 | 0.00 |
MECH_FLR_1 | 1682.61 | 1682.61 | 10.24 | 0.088 | 0.088 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00743 | -7.90 | 0.00234 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1017.68 | 1017.68 | 10.74 | 0.053 | 0.058 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00745 | -7.90 | 0.00234 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2254.51 | 2254.51 | 28.89 | 0.117 | 0.117 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00742 | -7.90 | 0.00234 | 0.000 | 0.00 |
CAFE_FLR_1 | 6628.58 | 6628.58 | 35.10 | 0.345 | 0.676 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00763 | -7.90 | 0.00234 | 0.676 | 0.00 |
LOBBY_FLR_1 | 15761.53 | 15761.53 | 12.05 | 0.821 | 1.894 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00757 | -7.90 | 0.00234 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5973.77 | 5973.77 | 153.09 | 0.313 | 0.313 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00758 | -7.90 | 0.00234 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5973.45 | 5973.45 | 153.10 | 0.313 | 0.313 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00758 | -7.90 | 0.00234 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 34369.16 | 34369.16 | 1401.46 | 1.802 | 1.802 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00761 | -7.90 | 0.00234 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 34379.80 | 34379.80 | 1401.51 | 1.802 | 1.802 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00761 | -7.90 | 0.00234 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5973.77 | 5973.77 | 153.09 | 0.313 | 0.313 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00758 | -7.90 | 0.00234 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5973.45 | 5973.45 | 153.10 | 0.313 | 0.313 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00758 | -7.90 | 0.00234 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 9537.81 | 9537.81 | 24.49 | 0.497 | 0.497 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00767 | -7.90 | 0.00234 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1829.34 | 1829.34 | 46.88 | 0.096 | 0.096 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00765 | -7.90 | 0.00234 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1830.36 | 1830.36 | 46.91 | 0.096 | 0.096 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00765 | -7.90 | 0.00234 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8764.42 | 8764.42 | 357.29 | 0.459 | 0.459 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00767 | -7.90 | 0.00234 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5973.03 | 5973.03 | 18.01 | 0.311 | 1.188 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00774 | -7.90 | 0.00234 | 1.188 | 0.00 |
DINING_FLR_6 | 6106.90 | 6106.90 | 18.41 | 0.318 | 1.188 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00774 | -7.90 | 0.00234 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2059.13 | 2059.13 | 19.93 | 0.107 | 0.367 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00680 | -7.90 | 0.00234 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 6241.10 | 6241.10 | 15.14 | 0.325 | 0.325 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00778 | -7.90 | 0.00234 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 26.49 | 26.49 | 7.48 | 7.48 | 26.4874 | 12.1883 | 26.4874 | 0.4602 | 0.3000 |
FLR_3_DOAS | 20.58 | 2.05 | 5.51 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 5580.662 | 5580.662 | 1.285066 | 0.00004882 | 116.375 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5580.66 | 5580.66 | 1.285066 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 5612.03 | 5612.03 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3246.537 | 3246.537 | 0.137983 | 0.00002840 | 88.602 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3246.54 | 3246.54 | 0.137983 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00758969 | 40.3828 | 2647.85 | 0.00 | 3262.64 | 3262.64 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1515.338 | 1515.338 | 0.138005 | 0.00001326 | 34.343 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1515.34 | 1515.34 | 0.138005 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00754619 | 40.1532 | 916.55 | 0.00 | 1523.51 | 1523.51 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2062.979 | 2062.979 | 0.087685 | 0.00001805 | 56.300 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 2062.98 | 2062.98 | 0.087685 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00742889 | 39.5366 | 1682.61 | 0.00 | 2073.21 | 2073.21 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1395.175 | 1395.175 | 0.087018 | 0.00001221 | 33.901 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 1395.18 | 1395.18 | 0.087018 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00745268 | 39.6617 | 1017.68 | 0.00 | 1402.44 | 1402.44 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7418.084 | 7418.084 | 1.190489 | 0.00006490 | 158.267 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 7418.08 | 7418.08 | 1.190489 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00741917 | 39.4866 | 2254.51 | 0.00 | 7459.45 | 7459.45 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 11043.988 | 11043.988 | 1.017555 | 0.00009662 | 249.875 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 11043.99 | 11043.99 | 1.017555 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00763457 | 40.6187 | 6628.58 | 0.00 | 11103.57 | 11103.57 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 28127.027 | 28127.027 | 2.849844 | 0.00024607 | 628.244 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 28127.03 | 28127.03 | 2.849844 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00756649 | 40.2601 | 15761.53 | 0.00 | 28279.51 | 28279.51 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 13199.452 | -999.000 | 1.441670 | 0.00047145 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 13199.45 | 13148.92 | 1.441670 | 21.81 | 13.66 | 0.00852026 | 12.80 | 10.33 | 0.00850000 | 33.39 | 0.00569673 | 15.22 | 0.0000 | 21.11 | 0.00852026 | 44.9583 | 12111.55 | 0.00 | 16330.01 | 15374.80 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5973.648 | 5973.648 | 0.313129 | 0.00005226 | 170.702 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5973.65 | 5973.65 | 0.313129 | 21.11 | 12.61 | 0.00758092 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00758092 | 40.0628 | 5973.77 | 0.00 | 6439.73 | 6439.73 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 13044.602 | -999.000 | 1.424675 | 0.00046591 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 13044.60 | 12994.15 | 1.424675 | 21.81 | 13.66 | 0.00852047 | 12.80 | 10.33 | 0.00850000 | 33.21 | 0.00569645 | 15.16 | 0.0000 | 21.11 | 0.00852047 | 44.9594 | 11968.78 | 0.00 | 16138.33 | 15193.58 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5973.319 | 5973.319 | 0.313111 | 0.00005226 | 170.692 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5973.32 | 5973.32 | 0.313111 | 21.11 | 12.61 | 0.00758093 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00758093 | 40.0629 | 5973.45 | 0.00 | 6439.38 | 6439.38 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 65266.911 | -999.000 | 7.168811 | 0.00233114 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | 7/21 13:50:00 | 65266.91 | 65266.91 | 7.168811 | 21.81 | 13.60 | 0.00845624 | 12.80 | 10.29 | 0.00845624 | 34.99 | 0.00569921 | 15.74 | 0.0000 | 21.11 | 0.00845624 | 44.6243 | 60227.48 | 0.00 | 80891.15 | 76862.90 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 34368.809 | 34368.809 | 1.801591 | 0.00030067 | 982.102 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 34368.81 | 34368.81 | 1.801591 | 21.11 | 12.63 | 0.00761158 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00761158 | 40.2220 | 34369.16 | 0.00 | 37050.61 | 37050.61 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 68022.466 | -999.000 | 7.092392 | 0.00242956 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | unknown | 7/21 15:10:00 | 68022.47 | 65614.96 | 7.092392 | 21.81 | 13.80 | 0.00869344 | 12.80 | 10.33 | 0.00850000 | 34.97 | 0.00569918 | 15.73 | 0.0000 | 21.11 | 0.00869344 | 45.8608 | 59580.44 | 0.00 | 83735.80 | 75751.37 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 34379.450 | 34379.450 | 1.802149 | 0.00030077 | 982.407 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 34379.45 | 34379.45 | 1.802149 | 21.11 | 12.63 | 0.00761159 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00761159 | 40.2221 | 34379.80 | 0.00 | 37062.09 | 37062.09 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11566.046 | -999.000 | 1.262564 | 0.00041310 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | 7/21 09:50:00 | 11566.05 | 11517.37 | 1.262564 | 21.81 | 13.66 | 0.00852228 | 12.80 | 10.33 | 0.00850000 | 29.59 | 0.00569088 | 13.95 | 0.0000 | 21.11 | 0.00852228 | 44.9688 | 10606.88 | 0.00 | 14308.28 | 13464.92 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5973.648 | 5973.648 | 0.313129 | 0.00005226 | 170.702 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5973.65 | 5973.65 | 0.313129 | 21.11 | 12.61 | 0.00758092 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00758092 | 40.0628 | 5973.77 | 0.00 | 6439.73 | 6439.73 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 11456.444 | -999.000 | 1.250585 | 0.00040919 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | unknown | 7/21 09:30:00 | 11456.44 | 11408.14 | 1.250585 | 21.81 | 13.66 | 0.00852232 | 12.80 | 10.33 | 0.00850000 | 28.82 | 0.00568971 | 13.69 | 0.0000 | 21.11 | 0.00852232 | 44.9691 | 10506.25 | 0.00 | 14172.68 | 13337.17 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5973.319 | 5973.319 | 0.313111 | 0.00005226 | 170.692 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5973.32 | 5973.32 | 0.313111 | 21.11 | 12.61 | 0.00758093 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00758093 | 40.0629 | 5973.45 | 0.00 | 6439.38 | 6439.38 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 12641.586 | 12641.586 | 0.715150 | 0.00011059 | 314.663 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 12641.59 | 12641.59 | 0.715150 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00767492 | 40.8296 | 9537.81 | 0.00 | 12706.84 | 12706.84 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3500.728 | -999.000 | 0.382476 | 0.00012504 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3500.73 | 3488.08 | 0.382476 | 21.81 | 13.66 | 0.00851912 | 12.80 | 10.33 | 0.00850000 | 33.39 | 0.00569673 | 15.22 | 0.0000 | 21.11 | 0.00851912 | 44.9524 | 3213.21 | 0.00 | 4331.16 | 4078.91 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1829.303 | 1829.303 | 0.095889 | 0.00001600 | 52.272 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1829.30 | 1829.30 | 0.095889 | 21.11 | 12.67 | 0.00765308 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00765308 | 40.4395 | 1829.34 | 0.00 | 1972.03 | 1972.03 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3453.331 | -999.000 | 0.377274 | 0.00012334 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3453.33 | 3440.70 | 0.377274 | 21.81 | 13.66 | 0.00851935 | 12.80 | 10.33 | 0.00850000 | 33.21 | 0.00569645 | 15.16 | 0.0000 | 21.11 | 0.00851935 | 44.9536 | 3169.50 | 0.00 | 4272.49 | 4023.44 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1830.322 | 1830.322 | 0.095942 | 0.00001601 | 52.301 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1830.32 | 1830.32 | 0.095942 | 21.11 | 12.67 | 0.00765328 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00765328 | 40.4406 | 1830.36 | 0.00 | 1973.13 | 1973.13 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 14207.853 | -999.000 | 1.524261 | 0.00050746 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | 7/21 13:50:00 | 14207.85 | 13979.43 | 1.524261 | 21.81 | 13.71 | 0.00858615 | 12.80 | 10.33 | 0.00850000 | 34.99 | 0.00569921 | 15.74 | 0.0000 | 21.11 | 0.00858615 | 45.3021 | 12804.97 | 0.00 | 17541.30 | 16263.23 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 8764.277 | 8764.277 | 0.459412 | 0.00007667 | 250.434 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 8764.28 | 8764.28 | 0.459412 | 21.11 | 12.68 | 0.00766577 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00766577 | 40.5055 | 8764.42 | 0.00 | 9448.12 | 9448.12 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 13738.331 | 13738.331 | 1.789085 | 0.00012019 | 298.426 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 13738.33 | 13738.33 | 1.789085 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00773501 | 41.1456 | 5973.03 | 0.00 | 13814.53 | 13814.53 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 13866.675 | 13866.675 | 1.787815 | 0.00012131 | 301.507 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 13866.67 | 13866.67 | 1.787815 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00774054 | 41.1748 | 6106.90 | 0.00 | 13943.56 | 13943.56 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 5647.476 | 5647.476 | 0.828662 | 0.00004941 | 121.361 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 5647.48 | 5647.48 | 0.828662 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00679590 | 36.2100 | 2059.13 | 0.00 | 5678.90 | 5678.90 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7652.896 | 7652.896 | 0.325243 | 0.00006695 | 208.862 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 7652.90 | 7652.90 | 0.325243 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00777608 | 41.3614 | 6241.10 | 0.00 | 7690.85 | 7690.85 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 489425.100 | -999.000 | 26.487432 | 0.01748113 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 489425.10 | 489425.10 | 26.487432 | 28.88 | 15.50 | 0.00789307 | 10.58 | 8.85 | 0.00789307 | 35.10 | 0.00569938 | 15.77 | 44.0264 | 23.99 | 0.00958156 | 42.3700 | 299629.28 | 0.00 | 571904.73 | 526694.41 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 194543.040 | 194543.040 | 7.946230 | 0.00170195 | 3255.584 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 194543.04 | 194543.04 | 7.946230 | -7.90 | -7.90 | 0.00234317 | 16.70 | 11.36 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 146.7546 | 21.33 | 0.00674558 | 35.2228 | 60530.44 | 0.00 | 171832.80 | 171832.80 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 48199.928 | -999.000 | 2.051317 | 0.00172159 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 48199.93 | 48199.93 | 2.051317 | 35.10 | 15.77 | 0.00569938 | 11.74 | 7.07 | 0.00569938 | 35.10 | 0.00569938 | 15.77 | 99.9965 | 21.11 | 0.00857465 | 45.2417 | 172889.93 | 0.00 | 48236.96 | 48236.96 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 15066.372 | 15066.372 | 0.615395 | 0.00013181 | 252.128 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 15066.37 | 15066.37 | 0.615395 | -7.90 | -7.90 | 0.00234317 | 16.70 | 11.36 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 333.3216 | 21.11 | 0.00761186 | 40.2235 | 105067.52 | 0.00 | 13307.58 | 13307.58 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 5580.662 | 5580.662 | 1.285066 | 0.00004882 | 116.375 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 1.2763 | 1.302030 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5580.66 | 5580.66 | 1.0000 | 1.27274052 | 1.285066 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.04881708 | 60.00 | 32.22 | 27.78 | 0.000 | 5580.66 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 5612.03 | 5612.03 | 1.27274052 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3246.537 | 3246.537 | 0.137983 | 0.00002840 | 88.602 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 0.7425 | 0.757453 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3246.54 | 3246.54 | 1.0000 | 0.13665964 | 0.137983 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.02839923 | 60.00 | 32.22 | 27.78 | 0.000 | 3246.54 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00758969 | 21.00 | 0.00758969 | 40.3828 | 2647.85 | 0.00 | 3262.64 | 3262.64 | 0.13665964 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60808.9 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1515.338 | 1515.338 | 0.138005 | 0.00001326 | 34.343 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 0.3466 | 0.353545 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1515.34 | 1515.34 | 1.0000 | 0.13668106 | 0.138005 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01325549 | 60.00 | 32.22 | 27.78 | 0.000 | 1515.34 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00754619 | 21.00 | 0.00754619 | 40.1532 | 916.55 | 0.00 | 1523.51 | 1523.51 | 0.13668106 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.53 | 17.20 | 0.00800000 | 48081.2 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2062.979 | 2062.979 | 0.087685 | 0.00001805 | 56.300 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 0.4718 | 0.481316 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 2062.98 | 2062.98 | 1.0000 | 0.08684417 | 0.087685 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01804600 | 60.00 | 32.22 | 27.78 | 0.000 | 2062.98 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00742889 | 21.00 | 0.00742889 | 39.5366 | 1682.61 | 0.00 | 2073.21 | 2073.21 | 0.08684417 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60807.5 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1395.175 | 1395.175 | 0.087018 | 0.00001221 | 33.901 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 0.3191 | 0.325510 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 1395.18 | 1395.18 | 1.0000 | 0.08618381 | 0.087018 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01220436 | 60.00 | 32.22 | 27.78 | 0.000 | 1395.18 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00745268 | 21.00 | 0.00745268 | 39.6617 | 1017.68 | 0.00 | 1402.44 | 1402.44 | 0.08618381 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.56 | 18.88 | 0.00800000 | 53207.3 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7418.084 | 7418.084 | 1.190489 | 0.00006490 | 158.267 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 1.6966 | 1.730721 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 7418.08 | 7418.08 | 1.0000 | 1.17907062 | 1.190489 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.06489001 | 60.00 | 32.22 | 27.78 | 0.000 | 7418.08 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00741917 | 21.00 | 0.00741917 | 39.4866 | 2254.51 | 0.00 | 7459.45 | 7459.45 | 1.17907062 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.80 | 15.52 | 0.00800000 | 43261.3 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11043.988 | 11043.988 | 1.017555 | 0.00009662 | 249.875 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 2.5259 | 2.576685 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 11043.99 | 11043.99 | 1.0000 | 1.00779568 | 1.017555 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.09660777 | 60.00 | 32.22 | 27.78 | 0.000 | 11043.99 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00763457 | 21.00 | 0.00763457 | 40.6187 | 6628.58 | 0.00 | 11103.57 | 11103.57 | 1.00779568 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.40 | 17.16 | 0.00800000 | 47952.4 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 28127.027 | 28127.027 | 2.849844 | 0.00024607 | 628.244 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 6.4329 | 6.562348 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 28127.03 | 28127.03 | 1.0000 | 2.82251064 | 2.849844 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.24604240 | 60.00 | 32.22 | 27.78 | 0.000 | 28127.03 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00756649 | 21.00 | 0.00756649 | 40.2601 | 15761.53 | 0.00 | 28279.51 | 28279.51 | 2.82251064 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.43 | 16.82 | 0.00800000 | 46954.0 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13199.452 | -999.000 | 1.441670 | 0.00047145 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6787 | 1004.8586 | 0.9904 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.441670 | 1.42784247 | 4197.9300 | 999.8980 | 26.47621227 | 13.37 | 6.70 | 6.67 | 741339.06 | 1.7805 | 1.780455 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 13199.45 | 13148.92 | 1.0000 | 1.42784247 | 1.441670 | 21.81 | 13.66 | 0.00852026 | 43566.5 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.47139694 | 6.70 | 13.37 | 6.67 | 0.000 | 13199.45 | 33.39 | 0.00569673 | 15.22 | 0.00000000 | 0.0000 | 21.11 | 0.00852026 | 21.11 | 0.00852026 | 44.9583 | 12111.55 | 0.00 | 16330.01 | 15374.80 | 1.42784247 | 21.81 | 15.62 | 0.00852026 | 43566.5 | 11.26 | 11.20 | 0.00825499 | 32129.7 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5973.648 | 5973.648 | 0.313129 | 0.00005226 | 170.702 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.441670 | 1.42784247 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 1.3662 | 1.393718 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5973.65 | 5973.65 | 1.0000 | 0.31012535 | 0.313129 | 21.11 | 12.61 | 0.00758092 | 40469.4 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.05225475 | 60.00 | 32.22 | 27.78 | 0.000 | 5973.65 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00758092 | 21.11 | 0.00758092 | 40.0628 | 5973.77 | 0.00 | 6439.73 | 6439.73 | 0.31012535 | 16.60 | 12.74 | 0.00758092 | 35873.7 | 36.98 | 19.96 | 0.00758092 | 56638.6 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13044.602 | -999.000 | 1.424675 | 0.00046591 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6791 | 1004.8586 | 0.9904 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.424675 | 1.41101051 | 4197.9300 | 999.8980 | 26.47621227 | 13.37 | 6.70 | 6.67 | 741339.06 | 1.7596 | 1.759567 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 13044.60 | 12994.15 | 1.0000 | 1.41101051 | 1.424675 | 21.81 | 13.66 | 0.00852047 | 43567.1 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.46586672 | 6.70 | 13.37 | 6.67 | 0.000 | 13044.60 | 33.21 | 0.00569645 | 15.16 | 0.00000000 | 0.0000 | 21.11 | 0.00852047 | 21.11 | 0.00852047 | 44.9594 | 11968.78 | 0.00 | 16138.33 | 15193.58 | 1.41101051 | 21.81 | 15.62 | 0.00852047 | 43567.1 | 11.26 | 11.20 | 0.00825497 | 32129.6 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5973.319 | 5973.319 | 0.313111 | 0.00005226 | 170.692 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.424675 | 1.41101051 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 1.3661 | 1.393642 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5973.32 | 5973.32 | 1.0000 | 0.31010830 | 0.313111 | 21.11 | 12.61 | 0.00758093 | 40469.4 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.05225187 | 60.00 | 32.22 | 27.78 | 0.000 | 5973.32 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00758093 | 21.11 | 0.00758093 | 40.0629 | 5973.45 | 0.00 | 6439.38 | 6439.38 | 0.31010830 | 16.60 | 12.74 | 0.00758093 | 35873.7 | 36.98 | 19.96 | 0.00758093 | 56638.7 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 65266.911 | -999.000 | 7.168811 | 0.00233114 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5597 | 1004.8586 | 0.9904 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.168811 | 7.10005368 | 4197.9300 | 999.8980 | 26.47621227 | 13.37 | 6.70 | 6.67 | 741339.06 | 8.8039 | 8.803757 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | unknown | unknown | 7/21 13:50:00 | Sensible | 65266.91 | 65266.91 | 1.0000 | 7.10005368 | 7.168811 | 21.81 | 13.60 | 0.00845624 | 43404.2 | 12.80 | 10.29 | 0.00845624 | 34211.7 | 2.33090149 | 6.70 | 13.37 | 6.67 | 0.000 | 65266.91 | 34.99 | 0.00569921 | 15.74 | 0.00000000 | 0.0000 | 21.11 | 0.00845624 | 21.11 | 0.00845624 | 44.6243 | 60227.48 | 0.00 | 80891.15 | 76862.90 | 7.10005368 | 21.81 | 15.56 | 0.00845624 | 43404.2 | 11.20 | 11.16 | 0.00823126 | 32011.1 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34368.809 | 34368.809 | 1.801591 | 0.00030067 | 982.102 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.168811 | 7.10005368 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 7.8604 | 8.018625 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 34368.81 | 34368.81 | 1.0000 | 1.78431145 | 1.801591 | 21.11 | 12.63 | 0.00761158 | 40547.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.30064266 | 60.00 | 32.22 | 27.78 | 0.000 | 34368.81 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00761158 | 21.11 | 0.00761158 | 40.2220 | 34369.16 | 0.00 | 37050.61 | 37050.61 | 1.78431145 | 16.60 | 12.77 | 0.00761158 | 35951.3 | 36.98 | 19.98 | 0.00761158 | 56716.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 68022.466 | -999.000 | 7.092392 | 0.00242956 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0007 | 1004.8586 | 0.9904 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.092392 | 7.02436830 | 4197.9300 | 999.8980 | 26.47621227 | 13.37 | 6.70 | 6.67 | 741339.06 | 9.1756 | 9.175450 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | unknown | unknown | unknown | 7/21 15:10:00 | Sensible | 68022.47 | 65614.96 | 1.0000 | 7.02436830 | 7.092392 | 21.81 | 13.80 | 0.00869344 | 44006.0 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 2.42931167 | 6.70 | 13.37 | 6.67 | 0.000 | 68022.47 | 34.97 | 0.00569918 | 15.73 | 0.00000000 | 0.0000 | 21.11 | 0.00869344 | 21.11 | 0.00869344 | 45.8608 | 59580.44 | 0.00 | 83735.80 | 75751.37 | 7.02436830 | 21.81 | 15.77 | 0.00869344 | 44006.0 | 11.24 | 11.19 | 0.00824271 | 32085.2 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34379.450 | 34379.450 | 1.802149 | 0.00030077 | 982.407 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.092392 | 7.02436830 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 7.8629 | 8.021107 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 34379.45 | 34379.45 | 1.0000 | 1.78486392 | 1.802149 | 21.11 | 12.63 | 0.00761159 | 40547.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.30073575 | 60.00 | 32.22 | 27.78 | 0.000 | 34379.45 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00761159 | 21.11 | 0.00761159 | 40.2221 | 34379.80 | 0.00 | 37062.09 | 37062.09 | 1.78486392 | 16.60 | 12.77 | 0.00761159 | 35951.4 | 36.98 | 19.98 | 0.00761159 | 56716.0 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11566.046 | -999.000 | 1.262564 | 0.00041310 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6825 | 1004.8586 | 0.9904 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.262564 | 1.25045503 | 4197.9300 | 999.8980 | 26.47621227 | 13.37 | 6.70 | 6.67 | 741339.06 | 1.5602 | 1.560127 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | unknown | unknown | 7/21 09:50:00 | Sensible | 11566.05 | 11517.37 | 1.0000 | 1.25045503 | 1.262564 | 21.81 | 13.66 | 0.00852228 | 43571.7 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.41306252 | 6.70 | 13.37 | 6.67 | 0.000 | 11566.05 | 29.59 | 0.00569088 | 13.95 | 0.00000000 | 0.0000 | 21.11 | 0.00852228 | 21.11 | 0.00852228 | 44.9688 | 10606.88 | 0.00 | 14308.28 | 13464.92 | 1.25045503 | 21.81 | 15.62 | 0.00852228 | 43571.7 | 11.26 | 11.20 | 0.00825484 | 32129.2 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5973.648 | 5973.648 | 0.313129 | 0.00005226 | 170.702 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.262564 | 1.25045503 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 1.3662 | 1.393718 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5973.65 | 5973.65 | 1.0000 | 0.31012535 | 0.313129 | 21.11 | 12.61 | 0.00758092 | 40469.4 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.05225475 | 60.00 | 32.22 | 27.78 | 0.000 | 5973.65 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00758092 | 21.11 | 0.00758092 | 40.0628 | 5973.77 | 0.00 | 6439.73 | 6439.73 | 0.31012535 | 16.60 | 12.74 | 0.00758092 | 35873.7 | 36.98 | 19.96 | 0.00758092 | 56638.6 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11456.444 | -999.000 | 1.250585 | 0.00040919 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6826 | 1004.8586 | 0.9904 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.250585 | 1.23859078 | 4197.9300 | 999.8980 | 26.47621227 | 13.37 | 6.70 | 6.67 | 741339.06 | 1.5454 | 1.545343 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | unknown | unknown | unknown | 7/21 09:30:00 | Sensible | 11456.44 | 11408.14 | 1.0000 | 1.23859078 | 1.250585 | 21.81 | 13.66 | 0.00852232 | 43571.8 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.40914826 | 6.70 | 13.37 | 6.67 | 0.000 | 11456.44 | 28.82 | 0.00568971 | 13.69 | 0.00000000 | 0.0000 | 21.11 | 0.00852232 | 21.11 | 0.00852232 | 44.9691 | 10506.25 | 0.00 | 14172.68 | 13337.17 | 1.23859078 | 21.81 | 15.62 | 0.00852232 | 43571.8 | 11.26 | 11.20 | 0.00825484 | 32129.2 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5973.319 | 5973.319 | 0.313111 | 0.00005226 | 170.692 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.250585 | 1.23859078 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 1.3661 | 1.393642 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5973.32 | 5973.32 | 1.0000 | 0.31010830 | 0.313111 | 21.11 | 12.61 | 0.00758093 | 40469.4 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.05225187 | 60.00 | 32.22 | 27.78 | 0.000 | 5973.32 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00758093 | 21.11 | 0.00758093 | 40.0629 | 5973.45 | 0.00 | 6439.38 | 6439.38 | 0.31010830 | 16.60 | 12.74 | 0.00758093 | 35873.7 | 36.98 | 19.96 | 0.00758093 | 56638.7 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12641.586 | 12641.586 | 0.715150 | 0.00011059 | 314.663 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 2.8912 | 2.949422 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 12641.59 | 12641.59 | 1.0000 | 0.70829091 | 0.715150 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.11058283 | 60.00 | 32.22 | 27.78 | 0.000 | 12641.59 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00767492 | 21.00 | 0.00767492 | 40.8296 | 9537.81 | 0.00 | 12706.84 | 12706.84 | 0.70829091 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.19 | 19.40 | 0.00800000 | 54874.9 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3500.728 | -999.000 | 0.382476 | 0.00012504 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6766 | 1004.8586 | 0.9904 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.382476 | 0.37880792 | 4197.9300 | 999.8980 | 26.47621227 | 13.37 | 6.70 | 6.67 | 741339.06 | 0.4722 | 0.472208 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 3500.73 | 3488.08 | 1.0000 | 0.37880792 | 0.382476 | 21.81 | 13.66 | 0.00851912 | 43563.6 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.12502279 | 6.70 | 13.37 | 6.67 | 0.000 | 3500.73 | 33.39 | 0.00569673 | 15.22 | 0.00000000 | 0.0000 | 21.11 | 0.00851912 | 21.11 | 0.00851912 | 44.9524 | 3213.21 | 0.00 | 4331.16 | 4078.91 | 0.37880792 | 21.81 | 15.62 | 0.00851912 | 43563.6 | 11.26 | 11.20 | 0.00825507 | 32130.0 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1829.303 | 1829.303 | 0.095889 | 0.00001600 | 52.272 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.382476 | 0.37880792 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 0.4184 | 0.426797 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1829.30 | 1829.30 | 1.0000 | 0.09496937 | 0.095889 | 21.11 | 12.67 | 0.00765308 | 40652.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01600191 | 60.00 | 32.22 | 27.78 | 0.000 | 1829.30 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00765308 | 21.11 | 0.00765308 | 40.4395 | 1829.34 | 0.00 | 1972.03 | 1972.03 | 0.09496937 | 16.60 | 12.81 | 0.00765308 | 36056.4 | 36.98 | 20.01 | 0.00765308 | 56821.3 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3453.331 | -999.000 | 0.377274 | 0.00012334 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6770 | 1004.8586 | 0.9904 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.377274 | 0.37365526 | 4197.9300 | 999.8980 | 26.47621227 | 13.37 | 6.70 | 6.67 | 741339.06 | 0.4658 | 0.465815 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3453.33 | 3440.70 | 1.0000 | 0.37365526 | 0.377274 | 21.81 | 13.66 | 0.00851935 | 43564.2 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.12333010 | 6.70 | 13.37 | 6.67 | 0.000 | 3453.33 | 33.21 | 0.00569645 | 15.16 | 0.00000000 | 0.0000 | 21.11 | 0.00851935 | 21.11 | 0.00851935 | 44.9536 | 3169.50 | 0.00 | 4272.49 | 4023.44 | 0.37365526 | 21.81 | 15.62 | 0.00851935 | 43564.2 | 11.26 | 11.20 | 0.00825505 | 32129.9 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1830.322 | 1830.322 | 0.095942 | 0.00001601 | 52.301 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.377274 | 0.37365526 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 0.4186 | 0.427034 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1830.32 | 1830.32 | 1.0000 | 0.09502226 | 0.095942 | 21.11 | 12.67 | 0.00765328 | 40653.2 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01601082 | 60.00 | 32.22 | 27.78 | 0.000 | 1830.32 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00765328 | 21.11 | 0.00765328 | 40.4406 | 1830.36 | 0.00 | 1973.13 | 1973.13 | 0.09502226 | 16.60 | 12.81 | 0.00765328 | 36056.9 | 36.98 | 20.01 | 0.00765328 | 56821.8 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14207.853 | -999.000 | 1.524261 | 0.00050746 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8012 | 1004.8586 | 0.9904 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.524261 | 1.50964204 | 4197.9300 | 999.8980 | 26.47621227 | 13.37 | 6.70 | 6.67 | 741339.06 | 1.9165 | 1.916476 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | unknown | unknown | 7/21 13:50:00 | Sensible | 14207.85 | 13979.43 | 1.0000 | 1.50964204 | 1.524261 | 21.81 | 13.71 | 0.00858615 | 43733.6 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.50741034 | 6.70 | 13.37 | 6.67 | 0.000 | 14207.85 | 34.99 | 0.00569921 | 15.74 | 0.00000000 | 0.0000 | 21.11 | 0.00858615 | 21.11 | 0.00858615 | 45.3021 | 12804.97 | 0.00 | 17541.30 | 16263.23 | 1.50964204 | 21.81 | 15.68 | 0.00858615 | 43733.6 | 11.25 | 11.20 | 0.00825044 | 32114.1 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8764.277 | 8764.277 | 0.459412 | 0.00007667 | 250.434 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.524261 | 1.50964204 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 2.0045 | 2.044803 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 8764.28 | 8764.28 | 1.0000 | 0.45500580 | 0.459412 | 21.11 | 12.68 | 0.00766577 | 40685.1 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.07666590 | 60.00 | 32.22 | 27.78 | 0.000 | 8764.28 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00766577 | 21.11 | 0.00766577 | 40.5055 | 8764.42 | 0.00 | 9448.12 | 9448.12 | 0.45500580 | 16.60 | 12.83 | 0.00766577 | 36088.5 | 36.98 | 20.02 | 0.00766577 | 56853.4 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13738.331 | 13738.331 | 1.789085 | 0.00012019 | 298.426 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 3.1421 | 3.205305 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 13738.33 | 13738.33 | 1.0000 | 1.77192593 | 1.789085 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.12017665 | 60.00 | 32.22 | 27.78 | 0.000 | 13738.33 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00773501 | 21.00 | 0.00773501 | 41.1456 | 5973.03 | 0.00 | 13814.53 | 13814.53 | 1.77192593 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.25 | 16.04 | 0.00800000 | 44731.1 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13866.675 | 13866.675 | 1.787815 | 0.00012131 | 301.507 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 3.1714 | 3.235249 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 13866.67 | 13866.67 | 1.0000 | 1.77066748 | 1.787815 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.12129935 | 60.00 | 32.22 | 27.78 | 0.000 | 13866.67 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00774054 | 21.00 | 0.00774054 | 41.1748 | 6106.90 | 0.00 | 13943.56 | 13943.56 | 1.77066748 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.32 | 16.07 | 0.00800000 | 44809.5 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5647.476 | 5647.476 | 0.828662 | 0.00004941 | 121.361 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 1.2916 | 1.317619 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 5647.48 | 5647.48 | 1.0000 | 0.82071470 | 0.828662 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.04940155 | 60.00 | 32.22 | 27.78 | 0.000 | 5647.48 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.51 | 0.00679590 | 21.00 | 0.00679590 | 36.2100 | 2059.13 | 0.00 | 5678.90 | 5678.90 | 0.82071470 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.39 | 15.73 | 0.00800000 | 43854.2 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7652.896 | 7652.896 | 0.325243 | 0.00006695 | 208.862 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 1.7503 | 1.785506 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 7652.90 | 7652.90 | 1.0000 | 0.32212370 | 0.325243 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.06694404 | 60.00 | 32.22 | 27.78 | 0.000 | 7652.90 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00777608 | 21.00 | 0.00777608 | 41.3614 | 6241.10 | 0.00 | 7690.85 | 7690.85 | 0.32212370 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60810.2 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 489425.100 | -999.000 | 26.487432 | 0.01748113 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5128 | 1004.8586 | 0.9904 | VAV WITH REHEAT FAN | Fan:VariableVolume | 26.487432 | 26.23338829 | 4197.9300 | 999.8980 | 26.47621227 | 13.37 | 6.70 | 6.67 | 741339.06 | 66.0191 | 66.019063 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | Sensible | 489425.10 | 489425.10 | 1.0000 | 26.23338829 | 26.487432 | 28.88 | 15.50 | 0.00789307 | 49184.1 | 10.58 | 8.85 | 0.00789307 | 30527.5 | 17.47934730 | 6.70 | 13.37 | 6.67 | 59348.763 | 430076.34 | 35.10 | 0.00569938 | 15.77 | 11.66146000 | 44.0264 | 23.99 | 0.00961853 | 23.99 | 0.00958156 | 42.3700 | 299629.28 | 0.00 | 571904.73 | 526694.41 | 26.23338829 | 28.88 | 17.57 | 0.00789307 | 49184.1 | 9.19 | 9.17 | 0.00720865 | 27383.4 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 194543.040 | 194543.040 | 7.946230 | 0.00170195 | 3255.584 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV WITH REHEAT FAN | Fan:VariableVolume | 26.487432 | 26.23338829 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 44.4936 | 45.389051 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 194543.04 | 194543.04 | 1.0000 | 7.87001649 | 7.946230 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 1.70177377 | 60.00 | 32.22 | 27.78 | 0.000 | 194543.04 | -7.90 | 0.00234317 | -7.90 | 11.66146000 | 146.7546 | 18.58 | 0.00700595 | 21.33 | 0.00674558 | 35.2228 | 60530.44 | 0.00 | 171832.80 | 171832.80 | 7.87001649 | 2.80 | -0.65 | 0.00234317 | 8685.9 | 24.43 | 10.64 | 0.00234317 | 30519.7 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 48199.928 | -999.000 | 2.051317 | 0.00172159 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1015.4349 | 1004.8586 | 0.9904 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.03157141 | 4197.9300 | 999.8980 | 26.47621227 | 13.37 | 6.70 | 6.67 | 741339.06 | 6.5017 | 6.501739 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 48199.93 | 48199.93 | 1.0000 | 2.03164284 | 2.051317 | 35.10 | 15.77 | 0.00569938 | 49895.6 | 11.74 | 7.07 | 0.00569938 | 26171.0 | 1.72141413 | 6.70 | 13.37 | 6.67 | 2195.006 | 46004.92 | 35.10 | 0.00569938 | 15.77 | 2.05124512 | 99.9965 | 21.11 | 0.00856422 | 21.11 | 0.00857465 | 45.2417 | 172889.93 | 0.00 | 48236.96 | 48236.96 | 2.03164284 | 35.10 | 17.86 | 0.00569938 | 49895.6 | 11.72 | 8.65 | 0.00569938 | 26152.7 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15066.372 | 15066.372 | 0.615395 | 0.00013181 | 252.128 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.03157141 | 4197.9300 | 999.8980 | 3.74930454 | 54.44 | 82.22 | 27.78 | 437238.25 | 3.4458 | 3.515152 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 15066.37 | 15066.37 | 1.0000 | 0.60949285 | 0.615395 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 0.13179374 | 60.00 | 32.22 | 27.78 | 0.000 | 15066.37 | -7.90 | 0.00234317 | -7.90 | 2.05124512 | 333.3216 | 21.11 | 0.00761058 | 21.11 | 0.00761186 | 40.2235 | 105067.52 | 0.00 | 13307.58 | 13307.58 | 0.60949285 | 2.80 | -0.65 | 0.00234317 | 8685.9 | 24.43 | 10.64 | 0.00234317 | 30519.7 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 11.66 | 26.49 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1651.33 | 5599.83 | 499.17 |
RETAIL_1_FLR_1 | 3424.17 | 4406.67 | 535.83 |
RETAIL_2_FLR_1 | 2273.33 | 5768.17 | 551.00 |
MECH_FLR_1 | 1579.50 | 6036.50 | 245.00 |
STORAGE_FLR_1 | 423.83 | 8161.33 | 353.50 |
LAUNDRY_FLR_1 | 8726.83 | 4003.17 | 4003.17 |
CAFE_FLR_1 | 3671.67 | 4687.83 | 887.17 |
LOBBY_FLR_1 | 2768.33 | 4688.67 | 861.33 |
ROOM_1_FLR_3 | 1150.00 | 7983.50 | 881.50 |
ROOM_2_FLR_3 | 2155.50 | 8198.17 | 1976.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1916.67 | 8760.00 | 1916.67 |
ROOM_5_FLR_3 | 1299.00 | 7861.33 | 915.50 |
ROOM_6_FLR_3 | 2109.33 | 7975.67 | 1966.83 |
CORRIDOR_FLR_3 | 1641.67 | 6469.33 | 670.67 |
ROOM_1_FLR_6 | 2194.17 | 7886.50 | 1805.83 |
ROOM_2_FLR_6 | 3133.00 | 8109.00 | 2868.67 |
ROOM_3_MULT9_FLR_6 | 772.83 | 7660.17 | 486.83 |
BANQUET_FLR_6 | 3081.33 | 5071.00 | 881.00 |
DINING_FLR_6 | 3567.00 | 3925.50 | 854.83 |
KITCHEN_FLR_6 | 8755.50 | 6434.00 | 6434.00 |
CORRIDOR_FLR_6 | 2144.33 | 5708.33 | 399.33 |
Facility | 8760.00 | 8760.00 | 7863.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 6.00 | 0.00 | 6.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 325.67 | 0.00 | 325.67 |
CAFE_FLR_1 | 0.00 | 13.67 | 0.00 | 13.67 |
LOBBY_FLR_1 | 0.00 | 0.33 | 0.00 | 0.33 |
ROOM_1_FLR_3 | 0.00 | 7.17 | 0.00 | 7.17 |
ROOM_2_FLR_3 | 0.00 | 3.67 | 0.00 | 3.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 2.17 | 0.00 | 2.17 |
ROOM_5_FLR_3 | 0.00 | 4.67 | 0.00 | 4.67 |
ROOM_6_FLR_3 | 0.00 | 3.83 | 0.00 | 3.83 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 11.67 | 0.00 | 11.67 |
ROOM_2_FLR_6 | 0.00 | 7.33 | 0.00 | 7.33 |
ROOM_3_MULT9_FLR_6 | 0.00 | 16.00 | 0.00 | 16.00 |
BANQUET_FLR_6 | 0.00 | 23.50 | 0.00 | 23.50 |
DINING_FLR_6 | 0.00 | 36.00 | 0.00 | 36.00 |
KITCHEN_FLR_6 | 0.00 | 449.00 | 0.00 | 449.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 537.83 | 0.00 | 537.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 106.50 | 4826.41 | 1.008 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.26 | 10.83 | 265.76 | 2.181 | 0.138 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.25 | 12.54 | 307.76 | 1.499 | 0.046 | 0.000 | 0.000 |
MECH_FLR_1 | 1.53 | 2.65 | 650.80 | 0.482 | 0.051 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.718 | 0.051 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 21.151 | 0.148 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.31 | 142.30 | 748.35 | 4.484 | 0.108 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.35 | 422.44 | 5183.56 | 1.871 | 0.045 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.471 | 0.177 | 0.000 | 0.058 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.471 | 0.177 | 0.000 | 0.056 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.534 | 0.079 | 0.000 | 0.088 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.471 | 0.177 | 0.000 | 0.058 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.471 | 0.177 | 0.000 | 0.056 |
CORRIDOR_FLR_3 | 12.12 | 20.96 | 1186.91 | 0.509 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.471 | 0.177 | 0.000 | 0.069 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.471 | 0.177 | 0.000 | 0.067 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.535 | 0.145 | 0.000 | 0.110 |
BANQUET_FLR_6 | 144.55 | 249.90 | 1010.89 | 5.749 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 144.55 | 249.90 | 1010.89 | 5.889 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.86 | 22.24 | 314.87 | 22.249 | 0.148 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.83 | 22.18 | 1256.16 | 0.881 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 106.50 | 4826.41 | 0.459 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.26 | 10.83 | 265.76 | 0.843 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.25 | 12.54 | 307.76 | 0.780 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.53 | 2.65 | 650.80 | 0.223 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.394 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 6.678 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.31 | 142.30 | 748.35 | 2.417 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.35 | 422.44 | 5183.56 | 0.948 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.459 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.455 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.518 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.459 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.456 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.12 | 20.96 | 1186.91 | 0.258 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.458 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.455 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.521 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.55 | 249.90 | 1010.89 | 3.058 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.55 | 249.90 | 1010.89 | 3.056 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.86 | 22.24 | 314.87 | 4.568 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.83 | 22.18 | 1256.16 | 0.387 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.60 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.26 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.25 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.53 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.86 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.31 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.35 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.12 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.55 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.55 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.86 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.83 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 870.81 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 41931251.52 | 0.00 | 41931251.52 | 0.00 | 41931251.52 | 26946214.98 | 18.72 | 3.16 | 8738.12 | 0.00 |
RETAIL_1_FLR_1 | 5005807.67 | 0.00 | 5005807.67 | 315975.89 | 5321783.55 | 2498216.28 | 67.32 | 15.89 | 8676.79 | 0.00 |
RETAIL_2_FLR_1 | 3980347.00 | 0.00 | 3980347.00 | 121967.09 | 4102314.09 | 2892943.94 | 242.73 | 103.23 | 8414.03 | 0.00 |
MECH_FLR_1 | 2708560.99 | 0.00 | 2708560.99 | 288257.75 | 2996818.74 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 2340562.93 | 0.00 | 2340562.93 | 166308.84 | 2506871.77 | 1821682.01 | 595.44 | 125.93 | 8038.64 | 0.00 |
LAUNDRY_FLR_1 | 56405891.06 | 0.00 | 56405891.06 | 393601.23 | 56799492.29 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 28961738.51 | 0.00 | 28961738.51 | 698482.59 | 29660221.10 | 21330615.53 | 491.06 | 140.53 | 8128.41 | 0.00 |
LOBBY_FLR_1 | 83549025.76 | 0.00 | 83549025.76 | 1995724.30 | 85544750.06 | 59728886.00 | 133.67 | 72.64 | 8553.69 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 59670.55 | 2006546.17 | 183401.85 | 2189948.02 | 1946875.62 | 0.00 | 7918.33 | 841.67 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 57707.56 | 2004355.07 | 183387.86 | 2187742.93 | 1946647.51 | 0.00 | 7918.33 | 841.67 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 64333.63 | 26462220.90 | 51171.17 | 26513392.08 | 26397887.27 | 0.00 | 7937.50 | 822.50 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 57311.71 | 26462417.43 | 51185.17 | 26513602.60 | 26405105.73 | 0.00 | 7967.77 | 792.23 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 59925.59 | 2006801.20 | 183401.85 | 2190203.05 | 1946875.62 | 0.00 | 7918.33 | 841.67 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 57922.19 | 2004569.71 | 183387.86 | 2187957.56 | 1946647.51 | 0.00 | 7918.33 | 841.67 | 0.00 |
CORRIDOR_FLR_3 | 20841626.69 | 0.00 | 20841626.69 | 221769.73 | 21063396.43 | 14972100.18 | 323.94 | 114.31 | 8321.75 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 71588.93 | 558307.84 | 183439.96 | 741747.80 | 486718.90 | 0.00 | 7917.17 | 842.83 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 69041.08 | 555702.96 | 183425.97 | 739128.93 | 486661.88 | 0.00 | 7917.17 | 842.83 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 71576.29 | 3198496.71 | 93854.31 | 3292351.01 | 3126920.42 | 0.00 | 7917.19 | 842.81 | 0.00 |
BANQUET_FLR_6 | 50138792.66 | 0.00 | 50138792.66 | 447914.29 | 50586706.94 | 37458366.31 | 301.90 | 146.11 | 8311.99 | 0.00 |
DINING_FLR_6 | 51315069.21 | 0.00 | 51315069.21 | 447914.29 | 51762983.49 | 37458366.31 | 169.44 | 89.28 | 8501.28 | 0.00 |
KITCHEN_FLR_6 | 60297163.78 | 0.00 | 60297163.78 | 400987.13 | 60698150.91 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 9554756.14 | 0.00 | 9554756.14 | 392463.83 | 9947219.97 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.46E+10 | 10970765.81 | 0.46E+10 | 18481630.20 | 0.46E+10 | 0.43E+10 | 601.41 | 7976.37 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3296 | 0.0000 | 1.3296 | 0.0000 | 1.3296 | 0.8545 | 18.72 | 3.16 | 8738.12 |
RETAIL_1_FLR_1 | 0.1587 | 0.0000 | 0.1587 | 0.0100 | 0.1688 | 0.0792 | 67.32 | 15.89 | 8676.79 |
RETAIL_2_FLR_1 | 0.1262 | 0.0000 | 0.1262 | 0.0039 | 0.1301 | 0.0917 | 242.73 | 103.23 | 8414.03 |
MECH_FLR_1 | 0.0859 | 0.0000 | 0.0859 | 0.0091 | 0.0950 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0742 | 0.0000 | 0.0742 | 0.0053 | 0.0795 | 0.0578 | 595.44 | 125.93 | 8038.64 |
LAUNDRY_FLR_1 | 1.7886 | 0.0000 | 1.7886 | 0.0125 | 1.8011 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.9184 | 0.0000 | 0.9184 | 0.0221 | 0.9405 | 0.6764 | 491.06 | 140.53 | 8128.41 |
LOBBY_FLR_1 | 2.6493 | 0.0000 | 2.6493 | 0.0633 | 2.7126 | 1.8940 | 133.67 | 72.64 | 8553.69 |
ROOM_1_FLR_3 | 0.0617 | 0.0019 | 0.0636 | 0.0058 | 0.0694 | 0.0617 | 0.00 | 7918.33 | 841.67 |
ROOM_2_FLR_3 | 0.0617 | 0.0018 | 0.0636 | 0.0058 | 0.0694 | 0.0617 | 0.00 | 7918.33 | 841.67 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0018 | 0.8391 | 0.0016 | 0.8407 | 0.8373 | 0.00 | 7967.77 | 792.23 |
ROOM_5_FLR_3 | 0.0617 | 0.0019 | 0.0636 | 0.0058 | 0.0695 | 0.0617 | 0.00 | 7918.33 | 841.67 |
ROOM_6_FLR_3 | 0.0617 | 0.0018 | 0.0636 | 0.0058 | 0.0694 | 0.0617 | 0.00 | 7918.33 | 841.67 |
CORRIDOR_FLR_3 | 0.6609 | 0.0000 | 0.6609 | 0.0070 | 0.6679 | 0.4748 | 323.94 | 114.31 | 8321.75 |
ROOM_1_FLR_6 | 0.0154 | 0.0023 | 0.0177 | 0.0058 | 0.0235 | 0.0154 | 0.00 | 7917.17 | 842.83 |
ROOM_2_FLR_6 | 0.0154 | 0.0022 | 0.0176 | 0.0058 | 0.0234 | 0.0154 | 0.00 | 7917.17 | 842.83 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0023 | 0.1014 | 0.0030 | 0.1044 | 0.0992 | 0.00 | 7917.19 | 842.81 |
BANQUET_FLR_6 | 1.5899 | 0.0000 | 1.5899 | 0.0142 | 1.6041 | 1.1878 | 301.90 | 146.11 | 8311.99 |
DINING_FLR_6 | 1.6272 | 0.0000 | 1.6272 | 0.0142 | 1.6414 | 1.1878 | 169.44 | 89.28 | 8501.28 |
KITCHEN_FLR_6 | 1.9120 | 0.0000 | 1.9120 | 0.0127 | 1.9247 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3030 | 0.0000 | 0.3030 | 0.0124 | 0.3154 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 80.7524 | 0.1928 | 80.9452 | 0.4627 | 81.4080 | 73.9670 | 601.41 | 7976.37 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.41E+09 | 0.00 | 0.41E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 63455387.45 | 569077.53 | 64024464.98 | 64690340.46 | 7915.83 | 15.77 | 828.40 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 12.9718 | 0.0000 | 12.9718 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 2.0122 | 0.0180 | 2.0302 | 2.0513 | 7915.83 | 15.77 | 828.40 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 4893.10 | 3866.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 11.4391 | 14.9151 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 2.0124 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1318 |
Defaulted Fields | 1181 |
Fields with Defaults | 4005 |
Autosized Fields | 350 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5612.91 | 75860.68 | 01-APR-03:10 | 407587.22 | 21-JUL-19:20 |
Electricity:Building | 2518.57 | 32615.18 | 17-JUN-05:00 | 151906.32 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 323.72 | 3705.45 | 02-JAN-02:10 | 24299.15 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2511.48 | 32474.03 | 17-JUN-05:00 | 151664.99 | 02-JAN-20:10 |
InteriorLights:Electricity | 766.47 | 6782.24 | 17-JUN-05:00 | 62892.57 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 173.46 | 1576.23 | 02-JAN-02:10 | 14185.34 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 766.47 | 6782.24 | 17-JUN-05:00 | 62892.57 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 766.47 | 6782.24 | 17-JUN-05:00 | 62892.57 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 173.46 | 1576.23 | 02-JAN-02:10 | 14185.34 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 766.47 | 6782.24 | 17-JUN-05:00 | 62892.57 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.80 | 222.61 | 02-JAN-02:10 | 1390.02 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.61 | 78.27 | 02-JAN-02:10 | 704.41 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.61 | 78.27 | 02-JAN-02:10 | 704.41 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.77 | 257.78 | 02-JAN-02:10 | 1609.65 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.97 | 90.64 | 02-JAN-02:10 | 815.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.97 | 90.64 | 02-JAN-02:10 | 815.72 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 29.11 | 327.88 | 02-JAN-02:10 | 2199.84 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 16.64 | 151.16 | 02-JAN-02:10 | 1360.40 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 16.64 | 151.16 | 02-JAN-02:10 | 1360.40 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.38 | 76.28 | 02-JAN-02:10 | 469.87 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.78 | 25.30 | 02-JAN-02:10 | 227.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.78 | 25.30 | 02-JAN-02:10 | 227.72 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.30 | 1002.39 | 02-JAN-02:10 | 4930.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.37 | 39.69 | 02-JAN-02:10 | 357.21 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.37 | 39.69 | 02-JAN-02:10 | 357.21 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 32.24 | 373.53 | 03-JUN-05:00 | 2727.18 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 17.90 | 170.32 | 03-JUN-05:00 | 1761.91 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 17.90 | 170.32 | 03-JUN-05:00 | 1761.91 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 270.82 | 3225.37 | 03-JUN-05:00 | 20294.39 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 121.82 | 1113.96 | 03-JUN-05:00 | 10265.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 121.82 | 1113.96 | 03-JUN-05:00 | 10265.18 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 18.66 | 264.62 | 01-JAN-02:10 | 1227.54 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 18.66 | 264.59 | 01-JAN-02:10 | 1227.39 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 304.77 | 4565.05 | 01-JAN-02:10 | 20923.25 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 76.02 | 643.59 | 01-JAN-02:10 | 5851.22 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 76.02 | 643.59 | 01-JAN-02:10 | 5851.22 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 304.86 | 4566.30 | 01-JAN-02:10 | 20928.98 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 76.04 | 643.77 | 01-JAN-02:10 | 5852.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 76.04 | 643.77 | 01-JAN-02:10 | 5852.82 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 18.66 | 264.62 | 01-JAN-02:10 | 1227.54 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 18.66 | 264.59 | 01-JAN-02:10 | 1227.39 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.66 | 66.15 | 01-JAN-02:10 | 306.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.50 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.50 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.66 | 66.15 | 01-JAN-02:10 | 306.85 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.49 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.49 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.10 | 540.75 | 01-JAN-02:10 | 2478.43 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 9.00 | 76.24 | 01-JAN-02:10 | 693.10 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 9.00 | 76.24 | 01-JAN-02:10 | 693.10 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 210.49 | 2524.33 | 17-JUN-05:00 | 9841.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 34.63 | 275.03 | 17-JUN-05:00 | 3094.06 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 34.63 | 275.03 | 17-JUN-05:00 | 3094.06 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 210.49 | 2524.33 | 17-JUN-05:00 | 9841.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 34.63 | 275.03 | 17-JUN-05:00 | 3094.06 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 34.63 | 275.03 | 17-JUN-05:00 | 3094.06 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 454.16 | 6253.02 | 02-JAN-02:10 | 18944.06 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.33 | 121.09 | 02-JAN-02:10 | 1089.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.33 | 121.09 | 02-JAN-02:10 | 1089.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1745.01 | 25691.80 | 02-JAN-02:10 | 89475.41 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1745.01 | 25691.80 | 02-JAN-02:10 | 89475.41 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.67 | 1114.61 | 13-DEC-23:30 | 3497.76 | 07-NOV-07:50 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1361.23 | 2596.94 | 07-APR-00:50 | 179965.71 | 21-JUL-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.53 | 0.00 | 01-JAN-11:10 | 2061.05 | 07-NOV-07:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.05 | 973.96 | 12-OCT-03:30 | 1245.48 | 15-JAN-11:00 |
Fans:Electricity | 655.22 | 11985.43 | 09-OCT-04:10 | 52674.29 | 18-AUG-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 871.35 | 14294.42 | 10-APR-03:20 | 63829.92 | 18-AUG-21:10 |
ExteriorEquipment:Electricity | 651.48 | 9618.58 | 02-JAN-02:20 | 39726.11 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 32.45 | 553.78 | 11-JAN-02:30 | 1868.65 | 11-JAN-21:10 |
ElectricityPurchased:Facility | 5612.91 | 75860.68 | 01-APR-03:10 | 407587.22 | 21-JUL-19:20 |
ElectricityPurchased:Plant | 5612.91 | 75860.68 | 01-APR-03:10 | 407587.22 | 21-JUL-19:20 |
Cogeneration:ElectricityPurchased | 5612.91 | 75860.68 | 01-APR-03:10 | 407587.22 | 21-JUL-19:20 |
General:Cogeneration:ElectricityPurchased | 5612.91 | 75860.68 | 01-APR-03:10 | 407587.22 | 21-JUL-19:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5612.91 | 75860.68 | 01-APR-03:10 | 407587.22 | 21-JUL-19:20 |
ElectricityNet:Plant | 5612.91 | 75860.68 | 01-APR-03:10 | 407587.22 | 21-JUL-19:20 |
Cogeneration:ElectricityNet | 5612.91 | 75860.68 | 01-APR-03:10 | 407587.22 | 21-JUL-19:20 |
General:Cogeneration:ElectricityNet | 5612.91 | 75860.68 | 01-APR-03:10 | 407587.22 | 21-JUL-19:20 |
General:Fans:Electricity | 655.22 | 11985.43 | 09-OCT-04:10 | 52674.29 | 18-AUG-21:10 |
ExteriorLights:Electricity | 242.74 | 0.00 | 01-JAN-07:20 | 15448.40 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 242.74 | 0.00 | 01-JAN-07:20 | 15448.40 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 183.68 | 0.00 | 01-JAN-13:30 | 9938.94 | 02-JAN-09:20 |
General:HeatRecovery:Electricity | 183.68 | 0.00 | 01-JAN-13:30 | 9938.94 | 02-JAN-09:20 |
WaterSystems:Electricity | 90.74 | 1086.50 | 20-NOV-02:50 | 4738.80 | 17-OCT-06:30 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.50 | 20-NOV-02:50 | 4738.80 | 17-OCT-06:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1051.87 | 0.00 | 01-JAN-02:10 | 166185.81 | 21-JUL-18:10 |
General:Cooling:Electricity | 1051.87 | 0.00 | 01-JAN-02:10 | 166185.81 | 21-JUL-18:10 |
Pumps:Electricity | 164.04 | 47.91 | 21-FEB-18:10 | 8181.19 | 26-JUN-18:30 |
General:Pumps:Electricity | 164.04 | 47.91 | 21-FEB-18:10 | 8181.19 | 26-JUN-18:30 |
WIRED_LTG_ELECTRICITY | 26.98 | 0.00 | 01-JAN-00:10 | 2213.82 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5237.21 | 29270.80 | 11-APR-01:20 | 495560.61 | 15-JAN-22:30 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3448.37 | 15908.90 | 25-MAR-10:10 | 445478.10 | 15-JAN-22:30 |
WaterSystems:NaturalGas | 3043.21 | 15908.90 | 07-JAN-11:40 | 284693.62 | 30-JAN-21:20 |
Water Heater:WaterSystems:NaturalGas | 3043.21 | 15908.90 | 07-JAN-11:40 | 284693.62 | 30-JAN-21:20 |
Heating:NaturalGas | 405.16 | 0.00 | 01-JAN-14:30 | 199884.92 | 01-DEC-03:20 |
Boiler:Heating:NaturalGas | 405.16 | 0.00 | 01-JAN-14:30 | 199884.92 | 01-DEC-03:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 3243.70 | -1992.95 | 06-APR-00:30 | 501059.78 | 31-JUL-18:30 |
PlantLoopCoolingDemand:HVAC | 3243.70 | -1992.95 | 06-APR-00:30 | 501059.78 | 31-JUL-18:30 |
CoolingCoils:PlantLoopCoolingDemand | 3243.70 | -1992.95 | 06-APR-00:30 | 501059.78 | 31-JUL-18:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:20 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:20 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:20 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 13-OCT-00:50 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:20 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:20 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:20 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 13-OCT-00:50 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 15-FEB-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 15-FEB-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 20164.51 | 142511.24 | 10-NOV-15:00 | 2051581.91 | 21-JUL-18:10 |
EnergyTransfer:Building | 5743.50 | 45946.43 | 16-APR-03:40 | 373161.83 | 21-JUL-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 732.35 | 7167.39 | 11-JAN-03:10 | 37063.12 | 23-JUL-10:50 |
Refrigeration:EnergyTransfer | 181.16 | 3985.64 | 17-NOV-23:10 | 10745.76 | 07-NOV-07:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.58 | 1992.82 | 17-NOV-23:10 | 5372.88 | 07-NOV-07:50 |
General:Refrigeration:EnergyTransfer | 90.58 | 1992.82 | 17-NOV-23:10 | 5372.88 | 07-NOV-07:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.58 | 1992.82 | 17-NOV-23:10 | 5372.88 | 07-NOV-07:50 |
EnergyTransfer:Plant | 8915.35 | 13730.88 | 05-APR-02:40 | 1162276.77 | 31-JUL-18:30 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.55 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.04 | 1871.89 | 12-OCT-03:30 | 2686.44 | 15-JAN-11:00 |
EnergyTransfer:Zone:BASEMENT | 429.26 | 301.89 | 25-FEB-23:10 | 27034.45 | 15-DEC-20:30 |
Heating:EnergyTransfer | 79.48 | 0.00 | 01-JAN-08:10 | 55329.90 | 21-DEC-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.11 | 0.00 | 01-JAN-00:10 | 2732.00 | 29-MAR-01:10 |
General:Heating:EnergyTransfer | 79.48 | 0.00 | 01-JAN-08:10 | 55329.90 | 21-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.11 | 0.00 | 01-JAN-00:10 | 2732.00 | 29-MAR-01:10 |
Cooling:EnergyTransfer | 5573.43 | 31342.89 | 25-DEC-04:20 | 370592.55 | 21-JUL-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 429.14 | 301.89 | 25-FEB-23:10 | 27034.45 | 15-DEC-20:30 |
General:Cooling:EnergyTransfer | 5573.43 | 31342.89 | 25-DEC-04:20 | 370592.55 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 429.14 | 301.89 | 25-FEB-23:10 | 27034.45 | 15-DEC-20:30 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 49.12 | 0.06 | 10-DEC-06:50 | 4971.61 | 31-DEC-13:00 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.12 | 0.00 | 01-JAN-00:10 | 603.95 | 09-DEC-07:20 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.12 | 0.00 | 01-JAN-00:10 | 603.95 | 09-DEC-07:20 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 49.00 | 0.00 | 12-JAN-07:10 | 4971.61 | 31-DEC-13:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 49.00 | 0.00 | 12-JAN-07:10 | 4971.61 | 31-DEC-13:00 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 38.60 | 22.12 | 25-FEB-23:10 | 2431.40 | 21-JUL-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 230.71 | 18-NOV-24:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 230.71 | 18-NOV-24:00 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 38.57 | 0.00 | 20-JAN-17:20 | 2431.40 | 21-JUL-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 38.57 | 0.00 | 20-JAN-17:20 | 2431.40 | 21-JUL-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 25.76 | 27.88 | 04-FEB-18:50 | 2417.45 | 21-JUL-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 192.45 | 20-JAN-17:20 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 192.45 | 20-JAN-17:20 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 25.72 | 0.00 | 20-JAN-17:20 | 2417.45 | 21-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 25.72 | 0.00 | 20-JAN-17:20 | 2417.45 | 21-JUL-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 18.00 | 0.06 | 06-FEB-08:40 | 934.58 | 23-JUL-10:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.08 | 0.00 | 01-JAN-00:10 | 323.35 | 09-DEC-18:30 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.08 | 0.00 | 01-JAN-00:10 | 323.35 | 09-DEC-18:30 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 17.92 | 0.00 | 17-JAN-10:10 | 934.58 | 23-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 17.92 | 0.00 | 17-JAN-10:10 | 934.58 | 23-JUL-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 595.35 | 5106.72 | 22-NOV-04:30 | 39637.68 | 21-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 685.27 | 20-NOV-01:30 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 685.27 | 20-NOV-01:30 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 595.34 | 5106.72 | 22-NOV-04:30 | 39637.68 | 21-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 595.34 | 5106.72 | 22-NOV-04:30 | 39637.68 | 21-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 274.23 | 621.20 | 23-MAR-06:40 | 17437.57 | 31-DEC-13:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.14 | 0.00 | 01-JAN-00:10 | 1119.45 | 25-DEC-13:50 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.14 | 0.00 | 01-JAN-00:10 | 1119.45 | 25-DEC-13:50 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 274.09 | 429.99 | 23-MAR-06:40 | 17437.57 | 31-DEC-13:00 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 274.09 | 429.99 | 23-MAR-06:40 | 17437.57 | 31-DEC-13:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 828.54 | 1189.05 | 20-JAN-17:20 | 43769.54 | 21-JUL-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.28 | 0.00 | 01-JAN-00:10 | 4453.60 | 24-APR-02:20 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.28 | 0.00 | 01-JAN-00:10 | 4453.60 | 24-APR-02:20 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 828.26 | 714.15 | 20-JAN-17:20 | 43769.54 | 21-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 828.26 | 714.15 | 20-JAN-17:20 | 43769.54 | 21-JUL-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 80.99 | 0.04 | 25-FEB-09:30 | 13904.80 | 20-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 6.34 | 0.00 | 01-JAN-08:10 | 4459.11 | 17-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 6.34 | 0.00 | 01-JAN-08:10 | 4459.11 | 17-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 74.66 | 0.00 | 01-JAN-00:10 | 13904.80 | 20-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 74.66 | 0.00 | 01-JAN-00:10 | 13904.80 | 20-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 71.86 | 0.04 | 03-DEC-19:00 | 13946.16 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 11.33 | 0.00 | 01-JAN-08:10 | 4810.10 | 15-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 11.33 | 0.00 | 01-JAN-08:10 | 4810.10 | 15-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 60.53 | 0.00 | 01-JAN-00:10 | 13946.16 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 60.53 | 0.00 | 01-JAN-00:10 | 13946.16 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 570.27 | 23.95 | 20-JAN-06:00 | 66662.43 | 19-OCT-12:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.06 | 0.00 | 01-JAN-00:10 | 4514.49 | 19-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.06 | 0.00 | 01-JAN-00:10 | 4514.49 | 19-JAN-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 570.20 | 0.00 | 19-JAN-00:50 | 66662.43 | 19-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 570.20 | 0.00 | 19-JAN-00:50 | 66662.43 | 19-OCT-12:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 434.32 | 0.82 | 30-MAR-03:50 | 68784.52 | 04-JUL-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 28.79 | 0.00 | 01-JAN-08:10 | 31659.95 | 21-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 28.79 | 0.00 | 01-JAN-08:10 | 31659.95 | 21-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 405.53 | 0.00 | 01-JAN-00:10 | 68784.52 | 04-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 405.53 | 0.00 | 01-JAN-00:10 | 68784.52 | 04-JUL-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 85.99 | 0.30 | 17-MAR-04:50 | 12118.81 | 17-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 6.66 | 0.00 | 01-JAN-07:40 | 4444.89 | 20-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 6.66 | 0.00 | 01-JAN-07:40 | 4444.89 | 20-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 79.33 | 0.00 | 01-JAN-00:10 | 12118.81 | 17-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 79.33 | 0.00 | 01-JAN-00:10 | 12118.81 | 17-JUN-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 76.12 | 0.40 | 30-JAN-17:00 | 12284.62 | 17-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 11.37 | 0.00 | 01-JAN-08:10 | 4538.81 | 17-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 11.37 | 0.00 | 01-JAN-08:10 | 4538.81 | 17-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 64.75 | 0.00 | 01-JAN-00:10 | 12284.62 | 17-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 64.75 | 0.00 | 01-JAN-00:10 | 12284.62 | 17-JUN-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 199.19 | 52.30 | 04-FEB-18:50 | 14645.61 | 21-JUL-18:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.28 | 0.00 | 01-JAN-00:10 | 1405.38 | 20-JAN-17:20 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.28 | 0.00 | 01-JAN-00:10 | 1405.38 | 20-JAN-17:20 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 198.91 | 0.00 | 20-JAN-17:20 | 14645.61 | 21-JUL-18:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 198.91 | 0.00 | 20-JAN-17:20 | 14645.61 | 21-JUL-18:30 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 21.23 | 0.01 | 05-NOV-09:00 | 3788.23 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 3.24 | 0.00 | 01-JAN-08:10 | 1316.00 | 17-JAN-19:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 3.24 | 0.00 | 01-JAN-08:10 | 1316.00 | 17-JAN-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.99 | 0.00 | 01-JAN-00:10 | 3788.23 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.99 | 0.00 | 01-JAN-00:10 | 3788.23 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 19.76 | 0.07 | 10-APR-06:30 | 3838.31 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.17 | 0.00 | 01-JAN-08:10 | 1549.47 | 22-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.17 | 0.00 | 01-JAN-08:10 | 1549.47 | 22-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 14.59 | 0.00 | 01-JAN-00:10 | 3838.31 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 14.59 | 0.00 | 01-JAN-00:10 | 3838.31 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 126.30 | 0.00 | 22-NOV-02:40 | 18437.88 | 31-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 4.98 | 0.00 | 01-JAN-00:10 | 5906.34 | 17-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 4.98 | 0.00 | 01-JAN-00:10 | 5906.34 | 17-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 121.32 | 0.00 | 01-JAN-03:40 | 18437.88 | 31-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 121.32 | 0.00 | 01-JAN-03:40 | 18437.88 | 31-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 473.85 | 1364.18 | 05-FEB-13:20 | 23573.84 | 21-JUL-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.16 | 0.00 | 01-JAN-00:10 | 1437.86 | 06-JAN-11:20 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.16 | 0.00 | 01-JAN-00:10 | 1437.86 | 06-JAN-11:20 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 473.69 | 1176.70 | 05-FEB-13:20 | 23573.84 | 21-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 473.69 | 1176.70 | 05-FEB-13:20 | 23573.84 | 21-JUL-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 499.79 | 1951.73 | 05-FEB-13:20 | 24943.20 | 21-JUL-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.09 | 0.00 | 01-JAN-00:10 | 1032.08 | 06-JAN-11:20 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.09 | 0.00 | 01-JAN-00:10 | 1032.08 | 06-JAN-11:20 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 499.70 | 1951.73 | 05-FEB-13:20 | 24943.20 | 21-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 499.70 | 1951.73 | 05-FEB-13:20 | 24943.20 | 21-JUL-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 258.86 | 16-FEB-01:20 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 258.86 | 16-FEB-01:20 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 641.77 | 4780.90 | 25-DEC-04:20 | 32002.15 | 23-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 641.77 | 4780.90 | 25-DEC-04:20 | 32002.15 | 23-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 92.63 | 0.01 | 17-JAN-09:00 | 7704.56 | 03-SEP-13:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.19 | 0.00 | 01-JAN-00:10 | 956.23 | 21-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.19 | 0.00 | 01-JAN-00:10 | 956.23 | 21-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 92.44 | 0.00 | 17-JAN-07:10 | 7704.56 | 03-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 92.44 | 0.00 | 17-JAN-07:10 | 7704.56 | 03-SEP-13:30 |
PlantLoopHeatingDemand:Facility | 1005.48 | 8273.48 | 05-AUG-01:00 | 186119.19 | 31-DEC-10:20 |
PlantLoopHeatingDemand:Plant | 722.65 | 8273.48 | 05-AUG-01:00 | 54957.76 | 06-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 722.65 | 8273.48 | 05-AUG-01:00 | 54957.76 | 06-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 722.65 | 8273.48 | 05-AUG-01:00 | 54957.76 | 06-FEB-07:10 |
EnergyTransfer:HVAC | 5505.66 | 4.21 | 28-MAR-10:20 | 539988.25 | 28-JUN-18:10 |
HeatingCoils:EnergyTransfer | 282.84 | 0.00 | 01-JAN-14:30 | 157611.00 | 29-NOV-04:50 |
PlantLoopHeatingDemand:HVAC | 282.84 | 0.00 | 01-JAN-14:30 | 157611.00 | 29-NOV-04:50 |
HeatingCoils:PlantLoopHeatingDemand | 282.84 | 0.00 | 01-JAN-14:30 | 157611.00 | 29-NOV-04:50 |
CoolingCoils:EnergyTransfer | 3243.70 | -1992.95 | 06-APR-00:30 | 501059.78 | 31-JUL-18:30 |
HeatRecoveryForHeating:EnergyTransfer | 1877.30 | 0.00 | 01-JAN-13:30 | 391523.76 | 15-DEC-05:00 |
HeatRecoveryForCooling:EnergyTransfer | 101.82 | 0.00 | 01-JAN-00:10 | 102744.18 | 28-JUN-18:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 722.65 | 8273.48 | 05-AUG-01:00 | 54957.76 | 06-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 722.65 | 8273.48 | 05-AUG-01:00 | 54957.76 | 06-FEB-07:10 |
Boilers:EnergyTransfer | 279.13 | 0.00 | 01-JAN-14:30 | 151222.08 | 01-DEC-03:20 |
Chillers:EnergyTransfer | 3385.56 | 0.00 | 01-JAN-02:10 | 507105.73 | 31-JUL-18:30 |
HeatRejection:EnergyTransfer | 4437.43 | 0.00 | 01-JAN-02:10 | 644623.81 | 21-JUL-18:10 |
General:HeatRejection:EnergyTransfer | 4437.43 | 0.00 | 01-JAN-02:10 | 644623.81 | 21-JUL-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.114 | -429.145 | 0.000 | 0.000 | 134.397 | 173.462 | 150.255 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -29.083 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.119 | -49.003 | 0.000 | 0.000 | 14.373 | 8.614 | 10.186 | 37.492 | 0.000 | 0.223 | 0.000 | 0.000 | -10.585 | 0.000 | -3.366 | -8.053 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.025 | -38.570 | 0.000 | 0.000 | 16.258 | 9.975 | 11.795 | 0.000 | 0.000 | 0.091 | 1.749 | 0.000 | 0.000 | 0.000 | -1.323 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.038 | -25.719 | 0.000 | 0.000 | 3.520 | 16.635 | 12.471 | 0.000 | 0.000 | 0.206 | 0.000 | 0.000 | 0.000 | 0.000 | -3.021 | -4.130 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.077 | -17.924 | 0.000 | 0.000 | 2.867 | 2.785 | 3.598 | 0.000 | 0.000 | 0.144 | 10.058 | 0.000 | 0.000 | 0.000 | -1.604 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.010 | -595.343 | 0.000 | 0.000 | 10.535 | 4.368 | 658.131 | 0.000 | 0.000 | 0.278 | 0.000 | 0.000 | 0.000 | 0.000 | -4.508 | -73.471 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.143 | -274.089 | 0.000 | 0.000 | 187.296 | 17.902 | 14.341 | 105.542 | 0.000 | 0.544 | 0.004 | 0.000 | -30.032 | 0.000 | -7.472 | -14.174 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.285 | -828.262 | 0.000 | 0.000 | 539.777 | 121.824 | 148.998 | 139.336 | 0.000 | 1.495 | 0.001 | 0.000 | -40.514 | 0.000 | -22.128 | -60.810 |
ROOM_1_FLR_3 | 8.471 | -63.018 | 0.000 | -13.774 | 0.000 | 0.000 | 9.672 | 6.366 | 12.292 | 73.567 | 0.000 | 0.857 | 0.000 | 0.000 | -21.935 | 0.000 | -7.396 | -5.103 |
ROOM_2_FLR_3 | 14.252 | -50.013 | 0.000 | -13.434 | 0.000 | 0.000 | 9.711 | 6.366 | 12.291 | 51.788 | 0.000 | 0.855 | 0.000 | 0.000 | -22.381 | 0.000 | -7.253 | -2.182 |
ROOM_3_MULT19_FLR_3 | 0.150 | -345.310 | 0.000 | -224.970 | 0.000 | 0.000 | 0.000 | 76.021 | 228.754 | 456.813 | 0.000 | 3.240 | 0.012 | 0.000 | -129.832 | 0.000 | -59.421 | -5.444 |
ROOM_4_MULT19_FLR_3 | 58.999 | -256.802 | 0.000 | -178.926 | 0.000 | 0.000 | 185.081 | 76.042 | 228.817 | 124.401 | 0.000 | 5.835 | 0.000 | 0.000 | -119.644 | 0.000 | -44.421 | -79.381 |
ROOM_5_FLR_3 | 8.779 | -67.579 | 0.000 | -13.876 | 0.000 | 0.000 | 9.657 | 6.366 | 12.292 | 77.282 | 0.000 | 0.856 | 0.000 | 0.000 | -21.304 | 0.000 | -7.449 | -5.025 |
ROOM_6_FLR_3 | 14.152 | -53.987 | 0.000 | -13.543 | 0.000 | 0.000 | 9.698 | 6.366 | 12.291 | 55.005 | 0.000 | 0.853 | 0.000 | 0.000 | -21.270 | 0.000 | -7.305 | -2.261 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.284 | -198.906 | 0.000 | 0.000 | 110.804 | 109.603 | 0.000 | 64.105 | 0.000 | 0.625 | 0.001 | 0.000 | -29.705 | 0.000 | -9.416 | -47.394 |
ROOM_1_FLR_6 | 3.950 | -15.274 | 0.000 | -3.420 | 0.000 | 0.000 | 2.421 | 1.592 | 3.073 | 18.327 | 0.000 | 0.216 | 0.000 | 0.000 | -5.397 | 0.000 | -1.870 | -3.616 |
ROOM_2_FLR_6 | 6.046 | -12.136 | 0.000 | -3.327 | 0.000 | 0.000 | 2.432 | 1.591 | 3.073 | 12.921 | 0.000 | 0.215 | 0.000 | 0.000 | -5.491 | 0.000 | -1.830 | -3.495 |
ROOM_3_MULT9_FLR_6 | 7.518 | -101.518 | 0.000 | -22.335 | 0.000 | 0.000 | 21.722 | 9.005 | 27.097 | 99.632 | 0.000 | 1.098 | 0.002 | 0.000 | -25.111 | 0.000 | -9.363 | -7.744 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.157 | -473.692 | 0.000 | 0.000 | 324.759 | 34.629 | 175.857 | 12.901 | 0.000 | 0.352 | 0.000 | 0.000 | -16.291 | 0.000 | -4.847 | -53.825 |
DINING_FLR_6 | 0.000 | 0.000 | 0.091 | -499.704 | 0.000 | 0.000 | 320.675 | 34.629 | 175.857 | 12.568 | 0.000 | 0.335 | 0.000 | 0.000 | -16.819 | 0.000 | -4.942 | -22.690 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.003 | -641.755 | 0.000 | 0.000 | 27.811 | 13.327 | 550.372 | 35.692 | 0.000 | 0.277 | 30.684 | 0.000 | -11.766 | 0.000 | -4.646 | -0.002 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.188 | -92.437 | 0.000 | 0.000 | 29.495 | 28.999 | 0.000 | 31.719 | 0.000 | 0.271 | 19.146 | 0.000 | -13.218 | 0.000 | -4.164 | -0.000 |
Total Facility | 122.317 | -965.637 | 1.533 | -4652.153 | 0.000 | 0.000 | 1972.960 | 766.466 | 2451.839 | 1409.092 | 0.000 | 18.865 | 61.660 | 0.000 | -541.295 | 0.000 | -217.744 | -427.882 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 25-NOV-23:30 | 0.00 | 0.00 | 0.00 | -45138.26 | 0.00 | 0.00 | 5196.60 | 4728.51 | 4258.44 | 0.00 | 0.00 | 0.00 | 30954.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 23-DEC-12:41 | 0.00 | 0.00 | 0.00 | -6218.18 | 0.00 | 0.00 | 216.18 | 195.67 | 252.59 | 7558.64 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -201.70 | -1803.20 |
RETAIL_2_FLR_1 | 27-MAR-06:02 | 0.00 | 0.00 | 0.00 | -3758.60 | 0.00 | 0.00 | 350.00 | 453.18 | 501.43 | 0.00 | 0.00 | 0.00 | 2527.02 | 0.00 | -0.00 | 0.00 | -73.02 | 0.00 |
MECH_FLR_1 | 21-JUL-20:00 | 0.00 | 0.00 | 0.00 | -2417.47 | 0.00 | 0.00 | 129.08 | 1360.40 | 839.45 | 0.00 | 0.00 | 57.03 | 31.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 24-APR-00:33 | 0.00 | 0.00 | 0.00 | -1335.29 | 0.00 | 0.00 | 142.84 | 37.96 | 63.73 | 0.00 | 0.00 | 0.00 | 1184.69 | 0.00 | -0.00 | 0.00 | -93.92 | 0.00 |
LAUNDRY_FLR_1 | 04-DEC-20:57 | 0.00 | 0.00 | 0.00 | -54228.83 | 0.00 | 0.00 | 404.23 | 357.21 | 44299.38 | 0.00 | 0.00 | 0.00 | 9493.62 | 0.00 | -0.00 | 0.00 | -325.60 | 0.00 |
CAFE_FLR_1 | 19-NOV-09:07 | 0.00 | 0.00 | 0.00 | -25660.79 | 0.00 | 0.00 | 4840.06 | 358.25 | 406.43 | 15708.80 | 0.00 | 0.00 | 4847.65 | 0.00 | -0.00 | 0.00 | -500.41 | 0.00 |
LOBBY_FLR_1 | 04-MAY-05:47 | 0.00 | 0.00 | 0.00 | -71885.57 | 0.00 | 0.00 | 20889.63 | 4349.40 | 5278.53 | 0.00 | 0.00 | 0.00 | 44820.01 | 0.00 | -2348.14 | 0.00 | -1103.85 | 0.00 |
ROOM_1_FLR_3 | 20-SEP-15:01 | 0.00 | -17805.70 | 0.00 | -604.16 | 0.00 | 0.00 | 235.29 | 137.21 | 273.93 | 13400.65 | 0.00 | 174.85 | 4187.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 13-JUN-18:01 | 0.00 | -17602.00 | 0.00 | -603.86 | 0.00 | 0.00 | 335.51 | 436.07 | 516.20 | 11085.02 | 0.00 | 203.80 | 5629.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 19-OCT-12:30 | 0.00 | -58005.43 | 0.00 | -8653.75 | 0.00 | 0.00 | 0.00 | 1638.34 | 5097.90 | 85926.69 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -341.80 | -25661.95 |
ROOM_4_MULT19_FLR_3 | 16-JUN-18:01 | 0.00 | -90091.81 | 0.00 | -8395.60 | 0.00 | 0.00 | 6374.69 | 5209.05 | 9610.21 | 24730.09 | 0.00 | 907.94 | 51655.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 28-JUN-15:01 | 0.00 | -15431.22 | 0.00 | -595.62 | 0.00 | 0.00 | 235.30 | 137.21 | 273.93 | 3306.60 | 0.00 | 343.57 | 11730.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 28-JUN-15:01 | 0.00 | -15284.42 | 0.00 | -595.53 | 0.00 | 0.00 | 235.30 | 137.19 | 273.90 | 3251.12 | 0.00 | 343.55 | 11638.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 21-JUL-18:30 | 0.00 | 0.00 | 0.00 | -14646.12 | 0.00 | 0.00 | 4080.29 | 7967.22 | 0.00 | 2898.65 | 0.00 | 293.61 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -593.66 |
ROOM_1_FLR_6 | 20-SEP-15:01 | 0.00 | -4721.15 | 0.00 | -150.95 | 0.00 | 0.00 | 58.82 | 34.30 | 68.48 | 3334.09 | 0.00 | 43.43 | 1332.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 13-JUN-18:01 | 0.00 | -4663.69 | 0.00 | -151.08 | 0.00 | 0.00 | 83.87 | 109.02 | 129.05 | 2756.17 | 0.00 | 50.59 | 1686.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 27-SEP-15:01 | 0.00 | -19278.97 | 0.00 | -995.99 | 0.00 | 0.00 | 529.38 | 194.07 | 603.86 | 9356.56 | 0.00 | 164.83 | 9426.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 17-MAR-22:54 | 0.00 | 0.00 | 0.00 | -38411.73 | 0.00 | 0.00 | 15614.75 | 1031.35 | 6747.90 | 0.00 | 0.00 | 0.00 | 16671.97 | 0.00 | -1331.06 | 0.00 | -323.19 | 0.00 |
DINING_FLR_6 | 17-MAR-22:54 | 0.00 | 0.00 | 0.00 | -42364.70 | 0.00 | 0.00 | 15606.70 | 1031.35 | 6747.90 | 0.00 | 0.00 | 0.00 | 20652.84 | 0.00 | -1350.68 | 0.00 | -323.42 | 0.00 |
KITCHEN_FLR_6 | 29-NOV-08:41 | 0.00 | 0.00 | 0.00 | -42427.82 | 0.00 | 0.00 | 491.87 | 484.37 | 21760.70 | 4626.93 | 0.00 | 0.00 | 15374.08 | 0.00 | -0.00 | 0.00 | -310.13 | 0.00 |
CORRIDOR_FLR_6 | 03-SEP-13:30 | 0.00 | 0.00 | 0.00 | -7703.39 | 0.00 | 0.00 | 308.46 | 527.00 | 0.00 | 4725.06 | 0.00 | 91.92 | 2050.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-JUL-18:02 | 0.00 | -206705.73 | 0.00 | -226191.21 | 0.00 | 0.00 | 73937.15 | 53784.22 | 122326.88 | 71235.89 | 0.00 | 6856.00 | 104756.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 02-MAR-04:38 | 0.00 | 0.00 | 5982.70 | 0.00 | 0.00 | 0.00 | 6693.28 | 1576.23 | 2129.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -16381.43 |
RETAIL_1_FLR_1 | 25-DEC-22:49 | 0.00 | 0.00 | 626.84 | 0.00 | 0.00 | 0.00 | 716.04 | 391.34 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -845.72 | 0.00 | -201.41 | -1120.12 |
RETAIL_2_FLR_1 | 15-JAN-22:33 | 0.00 | 0.00 | 513.61 | 0.00 | 0.00 | 0.00 | 692.41 | 453.18 | 501.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -91.72 | -2068.91 |
MECH_FLR_1 | 29-NOV-01:35 | 0.00 | 0.00 | 347.68 | 0.00 | 0.00 | 0.00 | 185.63 | 226.73 | 220.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -168.13 | -812.82 |
STORAGE_FLR_1 | 01-FEB-19:01 | 0.00 | 0.00 | 867.14 | 0.00 | 0.00 | 0.00 | 118.46 | 202.41 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -105.66 | -1311.77 |
LAUNDRY_FLR_1 | 27-OCT-01:06 | 0.00 | 0.00 | 3763.92 | 0.00 | 0.00 | 0.00 | 523.91 | 39.69 | 9326.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -274.16 | -13379.54 |
CAFE_FLR_1 | 07-JAN-21:33 | 0.00 | 0.00 | 3296.14 | 0.00 | 0.00 | 0.00 | 7646.98 | 1370.37 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2408.30 | 0.00 | -464.09 | -10253.96 |
LOBBY_FLR_1 | 20-NOV-01:26 | 0.00 | 0.00 | 11641.78 | 0.00 | 0.00 | 0.00 | 26893.74 | 1710.86 | 2639.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3317.03 | 0.00 | -1269.82 | -38298.80 |
ROOM_1_FLR_3 | 16-FEB-19:01 | 9525.58 | 285.08 | 0.00 | -285.08 | 0.00 | 0.00 | 409.51 | 436.12 | 516.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1824.96 | 0.00 | -448.27 | -8614.24 |
ROOM_2_FLR_3 | 15-DEC-09:01 | 9635.88 | 256.49 | 0.00 | -256.49 | 0.00 | 0.00 | 108.88 | 215.58 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1397.09 | 0.00 | -658.58 | -8357.67 |
ROOM_3_MULT19_FLR_3 | 19-JAN-05:00 | 4514.65 | 2845.42 | 0.00 | -2845.42 | 0.00 | 0.00 | 0.00 | 643.59 | 3921.46 | 0.00 | 0.00 | 0.00 | 5217.42 | 0.00 | -11442.18 | 0.00 | -2854.94 | 0.00 |
ROOM_4_MULT19_FLR_3 | 15-DEC-09:01 | 53332.35 | 3896.44 | 0.00 | -3896.44 | 0.00 | 0.00 | 1997.61 | 2575.24 | 8433.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7959.66 | 0.00 | -3559.62 | -54819.36 |
ROOM_5_FLR_3 | 16-FEB-19:01 | 9330.97 | 273.73 | 0.00 | -273.73 | 0.00 | 0.00 | 412.41 | 436.12 | 516.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1801.64 | 0.00 | -443.83 | -8450.29 |
ROOM_6_FLR_3 | 16-FEB-19:01 | 9371.56 | 257.41 | 0.00 | -257.41 | 0.00 | 0.00 | 416.85 | 436.07 | 516.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1775.93 | 0.00 | -437.43 | -8527.32 |
CORRIDOR_FLR_3 | 25-DEC-22:49 | 0.00 | 0.00 | 3092.47 | 0.00 | 0.00 | 0.00 | 5395.21 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2519.54 | 0.00 | -581.09 | -10366.56 |
ROOM_1_FLR_6 | 16-FEB-19:01 | 2840.37 | 63.66 | 0.00 | -63.66 | 0.00 | 0.00 | 104.80 | 109.03 | 129.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -441.08 | 0.00 | -109.48 | -2632.71 |
ROOM_2_FLR_6 | 15-DEC-09:01 | 2863.51 | 65.10 | 0.00 | -65.10 | 0.00 | 0.00 | 27.22 | 53.90 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -346.74 | 0.00 | -165.45 | -2545.68 |
ROOM_3_MULT9_FLR_6 | 17-JAN-09:01 | 12973.98 | 432.01 | 0.00 | -432.01 | 0.00 | 0.00 | 243.58 | 304.96 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -349.83 | 0.00 | -646.01 | -13525.39 |
BANQUET_FLR_6 | 14-DEC-15:44 | 0.00 | 0.00 | 5309.04 | 0.00 | 0.00 | 0.00 | 6062.37 | 744.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -981.68 | 0.00 | -292.92 | -17589.59 |
DINING_FLR_6 | 10-NOV-04:59 | 0.00 | 0.00 | 4591.84 | 0.00 | 0.00 | 0.00 | 16117.45 | 343.78 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1157.09 | 0.00 | -283.41 | -21861.88 |
KITCHEN_FLR_6 | 16-FEB-01:15 | 0.00 | 0.00 | 2588.89 | 0.00 | 0.00 | 0.00 | 1392.25 | 181.64 | 5415.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1172.33 | 0.00 | -279.90 | -8126.53 |
CORRIDOR_FLR_6 | 25-DEC-22:49 | 0.00 | 0.00 | 1355.69 | 0.00 | 0.00 | 0.00 | 1462.54 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1107.33 | 0.00 | -252.02 | -2776.39 |
Total Facility | 20-JAN-09:01 | 13302.96 | 100971.58 | 725.76 | -100971.58 | 0.00 | 0.00 | 23665.43 | 26712.50 | 88432.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16529.86 | 0.00 | -14825.66 | -121483.35 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 26.6397 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 26.4874 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 14.3207 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 12.1883 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1115 | 3.1115 | 1.2851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4345 | 0.4345 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2924 | 0.2924 | 0.1380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2832 | 0.2832 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1377 | 0.1377 | 0.0870 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.9683 | 3.9683 | 1.1905 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7978 | 1.7978 | 1.0176 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6321 | 5.6321 | 2.8498 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7790 | 1.7790 | 0.7151 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6823 | 2.6823 | 1.7891 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8110 | 2.8110 | 1.7878 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7622 | 2.7622 | 0.8287 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9477 | 0.9477 | 0.2843 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 26.6397 | 26.4874 | 26.6397 | 12.1883 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5558 | 1.5558 | 1.2851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2173 | 0.2173 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1462 | 0.1462 | 0.1380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1416 | 0.1416 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0870 | 0.0870 | 0.0870 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9841 | 1.9841 | 1.1905 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0176 | 1.0176 | 1.0176 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8498 | 2.8498 | 2.8498 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8895 | 0.8895 | 0.7151 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7891 | 1.7891 | 1.7891 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7878 | 1.7878 | 1.7878 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3811 | 1.3811 | 0.8287 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4739 | 0.4739 | 0.2843 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 14.3207 | 12.1883 | 12.1883 | 12.1883 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 537.83 |
Number of hours not met | 537.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 405.16 | 199884.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1051.87 | 166185.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 766.47 | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 242.74 | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.56 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 32.45 | 1868.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 655.22 | 52674.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 164.04 | 8181.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 183.68 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.80 | 3043.21 | 284693.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.53 | 2061.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.05 | 1245.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1806.68 | 5612.91 |
Natural Gas | 1788.84 | 5237.21 |
Additional | 0.00 | 0.00 |
Total | 3595.52 | 10850.12 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 67.56 |
Space Heating | 0.00 |
Space Cooling | 92.71 |
Fans (All) | 57.75 |
Service Water Heating | 8.00 |
Receptacle Equipment | 153.81 |
Miscellaneous (All) | 494.74 |
Subtotal | 494.74 |
Natural Gas [MJ/m2] | |
Space Heating | 35.71 |
Service Water Heating | 268.24 |
Miscellaneous (All) | 461.62 |
Subtotal | 461.62 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.06 |
Space Heating | 3.73 |
Space Cooling | 9.69 |
Fans (All) | 6.04 |
Service Water Heating | 28.88 |
Receptacle Equipment | 32.57 |
Miscellaneous | 12.01 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2667. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 2678. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 3061. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8755.83 | 4.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8755.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 4.17 | 0.00 | 0.00 | 0.00 |
Average | 8759.79 | 0.21 | 0.00 | 0.00 | 0.00 |
Sum | 192715.33 | 4.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37200.17 | 2.83 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108221.83 | 47.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 47.17 | 0.00 | 0.00 | 0.00 |
Average | 288884.77 | 2.27 | 0.00 | 0.00 | 0.00 |
Sum | 6355465.00 | 50.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8696.33 | 63.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8691.33 | 68.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8747.33 | 12.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8686.33 | 73.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8688.67 | 71.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8686.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 73.67 | 0.00 | 0.00 | 0.00 |
Average | 8746.82 | 13.18 | 0.00 | 0.00 | 0.00 |
Sum | 192430.00 | 290.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 702312.00 | 8105.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2091871.17 | 23557.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100142.00 | 216.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1230113.67 | 15601.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1231086.33 | 14628.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2091871.17 | 23557.83 | 0.00 | 0.00 | 0.00 |
Average | 286063.92 | 2823.13 | 0.00 | 0.00 | 0.00 |
Sum | 6293406.17 | 62108.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:47
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.356943E+11 | 37258.42 | 28-JAN-21:21 | 3.60 | 1.24 | 0.821684E+10 | 5031.12 | 11-JAN-03:20 | 3.60 | 1.24 |
February | 0.294681E+11 | 36875.47 | 24-FEB-20:17 | 2.03 | -2.0 | 0.739946E+10 | 5065.09 | 21-FEB-22:49 | 2.03 | -2.0 |
March | 0.304793E+11 | 36384.95 | 03-MAR-21:50 | 2.38 | -1.4 | 0.813187E+10 | 4987.48 | 03-MAR-22:49 | 1.78 | -2.0 |
April | 0.297570E+11 | 34126.58 | 23-APR-04:47 | 4.18 | 0.07 | 0.782427E+10 | 4981.21 | 07-APR-04:30 | 4.18 | 0.07 |
May | 0.315750E+11 | 28452.34 | 07-MAY-05:41 | 5.82 | 0.03 | 0.811471E+10 | 4913.39 | 05-MAY-04:40 | 5.82 | 0.03 |
June | 0.329588E+11 | 19359.10 | 08-JUN-21:00 | 11.70 | 10.04 | 0.793120E+10 | 4837.38 | 23-JUN-21:10 | 26.60 | 15.77 |
July | 0.367433E+11 | 20927.99 | 27-JUL-21:00 | 21.70 | 14.57 | 0.819325E+10 | 4837.48 | 01-JUL-00:40 | 21.70 | 14.57 |
August | 0.390527E+11 | 22320.57 | 23-AUG-21:00 | 21.10 | 15.01 | 0.824611E+10 | 4837.20 | 29-AUG-22:49 | 18.07 | 16.08 |
September | 0.404341E+11 | 23796.27 | 15-SEP-21:00 | 16.70 | 12.85 | 0.797184E+10 | 4837.60 | 22-SEP-22:10 | 19.03 | 14.04 |
October | 0.429745E+11 | 41251.01 | 29-OCT-04:29 | 4.20 | 0.32 | 0.823434E+10 | 5068.99 | 26-OCT-23:10 | 4.20 | 0.32 |
November | 0.405419E+11 | 45138.72 | 25-NOV-23:30 | 2.25 | -0.8 | 0.796669E+10 | 5070.42 | 04-NOV-04:10 | 2.25 | -0.8 |
December | 0.394635E+11 | 44775.32 | 01-DEC-02:15 | 4.13 | -0.7 | 0.823423E+10 | 5005.10 | 04-DEC-22:10 | 0.00 | -2.4 |
Annual Sum or Average | 0.429142E+12 | 0.964648E+11 | ||||||||
Minimum of Months | 0.294681E+11 | 19359.10 | 2.03 | -2.0 | 0.739946E+10 | 4837.20 | 0.00 | -2.4 | ||
Maximum of Months | 0.429745E+11 | 45138.72 | 21.70 | 15.01 | 0.824611E+10 | 5070.42 | 26.60 | 16.08 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316765E+10 | 5338.59 | 27-JAN-10:47 | 5.55 | -1.0 | 0.698092E+09 | 487.72 | 02-JAN-22:10 | 5.55 | -1.0 |
February | 0.308564E+10 | 5442.77 | 04-FEB-11:38 | 2.57 | -2.6 | 0.644843E+09 | 492.39 | 10-FEB-22:19 | 3.33 | -0.5 |
March | 0.338896E+10 | 4427.77 | 08-MAR-13:30 | 21.40 | 9.29 | 0.736950E+09 | 491.82 | 08-MAR-22:19 | 10.53 | 4.18 |
April | 0.353083E+10 | 3491.59 | 13-APR-12:50 | 23.62 | 8.92 | 0.753819E+09 | 491.82 | 24-APR-21:19 | 16.33 | 6.14 |
May | 0.359121E+10 | 2775.03 | 13-MAY-13:00 | 28.30 | 11.84 | 0.791212E+09 | 491.86 | 17-MAY-21:00 | 18.90 | 9.98 |
June | 0.421848E+10 | 3073.79 | 29-JUN-14:30 | 37.25 | 15.80 | 0.795497E+09 | 491.86 | 23-JUN-21:10 | 37.25 | 15.80 |
July | 0.506936E+10 | 3294.55 | 22-JUL-13:30 | 36.95 | 17.78 | 0.834260E+09 | 491.92 | 01-JUL-00:40 | 36.95 | 17.78 |
August | 0.543720E+10 | 4069.11 | 22-AUG-13:20 | 31.13 | 16.59 | 0.837195E+09 | 491.85 | 21-AUG-00:10 | 31.13 | 16.59 |
September | 0.531611E+10 | 4910.88 | 28-SEP-13:10 | 29.08 | 15.59 | 0.799655E+09 | 491.89 | 22-SEP-22:10 | 29.08 | 15.59 |
October | 0.498846E+10 | 4945.10 | 19-OCT-12:30 | 20.55 | 8.60 | 0.791092E+09 | 491.84 | 20-OCT-21:10 | 14.22 | 8.62 |
November | 0.390667E+10 | 5881.06 | 19-NOV-09:07 | 2.57 | -1.8 | 0.719685E+09 | 492.25 | 07-NOV-22:19 | 2.57 | -1.8 |
December | 0.330278E+10 | 6218.53 | 23-DEC-12:41 | 5.22 | -1.6 | 0.699085E+09 | 477.41 | 19-DEC-22:10 | 5.22 | -1.6 |
Annual Sum or Average | 0.490033E+11 | 0.910139E+10 | ||||||||
Minimum of Months | 0.308564E+10 | 2775.03 | 2.57 | -2.6 | 0.644843E+09 | 477.41 | 2.57 | -1.8 | ||
Maximum of Months | 0.543720E+10 | 6218.53 | 37.25 | 17.78 | 0.837195E+09 | 492.39 | 37.25 | 17.78 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265114E+10 | 3297.33 | 03-JAN-21:50 | 0.65 | -1.9 | 0.868997E+09 | 582.23 | 05-JAN-22:19 | 3.53 | -1.3 |
February | 0.248474E+10 | 3072.38 | 25-FEB-23:11 | 2.03 | -0.7 | 0.800479E+09 | 591.19 | 21-FEB-22:49 | 2.03 | -0.7 |
March | 0.290408E+10 | 3759.13 | 27-MAR-06:02 | 5.10 | 1.00 | 0.913016E+09 | 592.17 | 10-MAR-23:30 | 5.10 | 1.00 |
April | 0.310121E+10 | 2733.93 | 05-APR-23:12 | 4.40 | -0.5 | 0.906974E+09 | 573.81 | 07-APR-04:30 | 4.40 | -1.5 |
May | 0.336798E+10 | 2088.13 | 19-MAY-20:50 | 23.68 | 8.47 | 0.945029E+09 | 570.88 | 16-MAY-04:30 | 23.68 | 8.47 |
June | 0.365878E+10 | 2363.15 | 28-JUN-20:10 | 29.82 | 16.20 | 0.930964E+09 | 570.56 | 20-JUN-02:49 | 29.82 | 16.20 |
July | 0.397996E+10 | 2431.40 | 21-JUL-21:00 | 30.00 | 14.72 | 0.964850E+09 | 569.64 | 01-JUL-00:40 | 30.00 | 14.72 |
August | 0.397821E+10 | 2365.88 | 18-AUG-20:10 | 27.02 | 13.59 | 0.969505E+09 | 569.56 | 29-AUG-22:40 | 18.33 | 15.84 |
September | 0.363115E+10 | 2186.72 | 13-SEP-20:10 | 23.53 | 12.84 | 0.932542E+09 | 569.61 | 22-SEP-22:10 | 19.03 | 14.04 |
October | 0.335320E+10 | 2879.35 | 24-OCT-21:14 | 1.70 | 0.05 | 0.941621E+09 | 571.05 | 12-OCT-03:49 | 1.70 | 0.05 |
November | 0.281783E+10 | 3119.71 | 24-NOV-22:48 | 4.50 | 1.16 | 0.881473E+09 | 588.77 | 16-NOV-23:40 | 4.50 | 1.16 |
December | 0.264155E+10 | 3010.47 | 18-DEC-22:51 | 1.70 | -2.4 | 0.870045E+09 | 574.08 | 29-DEC-22:00 | 1.70 | -1.6 |
Annual Sum or Average | 0.385698E+11 | 0.109255E+11 | ||||||||
Minimum of Months | 0.248474E+10 | 2088.13 | 0.65 | -2.4 | 0.800479E+09 | 569.56 | 1.70 | -1.6 | ||
Maximum of Months | 0.397996E+10 | 3759.13 | 30.00 | 16.20 | 0.969505E+09 | 592.17 | 30.00 | 16.20 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136514E+10 | 1246.30 | 29-JAN-20:00 | 1.10 | -2.7 | 0.165777E+09 | 110.67 | 05-JAN-22:19 | 1.10 | -2.7 |
February | 0.132327E+10 | 1247.34 | 08-FEB-22:05 | 1.60 | -1.7 | 0.153637E+09 | 116.69 | 15-FEB-22:19 | 6.50 | 2.35 |
March | 0.163742E+10 | 1305.82 | 09-MAR-05:17 | 3.67 | 0.65 | 0.182134E+09 | 118.45 | 16-MAR-21:10 | 14.17 | 4.07 |
April | 0.184760E+10 | 1525.82 | 28-APR-20:00 | 22.20 | 8.52 | 0.187466E+09 | 120.46 | 18-APR-21:10 | 22.20 | 8.52 |
May | 0.224701E+10 | 1900.64 | 19-MAY-20:00 | 25.60 | 9.31 | 0.200519E+09 | 120.46 | 01-MAY-21:40 | 25.60 | 9.31 |
June | 0.298078E+10 | 2389.76 | 29-JUN-20:00 | 26.70 | 13.56 | 0.198470E+09 | 120.53 | 20-JUN-02:49 | 26.70 | 13.56 |
July | 0.349740E+10 | 2417.45 | 21-JUL-20:00 | 30.60 | 12.57 | 0.205008E+09 | 120.46 | 01-JUL-00:40 | 30.60 | 12.57 |
August | 0.327566E+10 | 2286.19 | 18-AUG-20:00 | 27.20 | 13.67 | 0.205853E+09 | 120.46 | 04-AUG-21:10 | 27.20 | 13.67 |
September | 0.257102E+10 | 1979.40 | 01-SEP-20:00 | 22.80 | 14.95 | 0.198065E+09 | 120.46 | 22-SEP-22:10 | 19.03 | 14.04 |
October | 0.203458E+10 | 1802.03 | 02-OCT-20:00 | 18.90 | 14.94 | 0.194391E+09 | 120.46 | 20-OCT-21:10 | 14.22 | 8.62 |
November | 0.155543E+10 | 1301.23 | 25-NOV-23:26 | 2.25 | -0.8 | 0.173189E+09 | 119.70 | 02-NOV-21:10 | 2.25 | -0.8 |
December | 0.138338E+10 | 1182.06 | 04-DEC-11:33 | 3.13 | -0.6 | 0.164542E+09 | 111.68 | 01-DEC-22:10 | 3.13 | -0.6 |
Annual Sum or Average | 0.257187E+11 | 0.222905E+10 | ||||||||
Minimum of Months | 0.132327E+10 | 1182.06 | 1.10 | -2.7 | 0.153637E+09 | 110.67 | 1.10 | -2.7 | ||
Maximum of Months | 0.349740E+10 | 2417.45 | 30.60 | 14.95 | 0.205853E+09 | 120.53 | 30.60 | 14.04 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.894298E+09 | 1144.50 | 11-JAN-17:51 | 2.20 | 0.10 | 0.117495E+09 | 73.97 | 05-JAN-22:00 | 2.20 | 0.10 |
February | 0.963786E+09 | 1160.47 | 08-FEB-22:05 | 1.60 | -1.7 | 0.107273E+09 | 76.44 | 15-FEB-22:30 | 6.40 | 2.29 |
March | 0.138175E+10 | 1242.27 | 09-MAR-05:17 | 3.67 | 0.65 | 0.123358E+09 | 77.40 | 16-MAR-21:40 | 11.67 | 2.90 |
April | 0.153236E+10 | 1335.35 | 24-APR-00:33 | 4.40 | 1.10 | 0.126580E+09 | 84.03 | 28-APR-21:40 | 19.60 | 6.84 |
May | 0.172032E+10 | 1135.27 | 02-MAY-00:07 | 7.52 | 4.37 | 0.136752E+09 | 87.09 | 19-MAY-21:40 | 22.57 | 7.89 |
June | 0.185426E+10 | 933.08 | 29-JUN-10:35 | 32.60 | 16.86 | 0.141094E+09 | 92.63 | 29-JUN-21:40 | 24.47 | 13.56 |
July | 0.200537E+10 | 936.44 | 23-JUL-10:35 | 31.83 | 17.15 | 0.149204E+09 | 92.66 | 21-JUL-21:40 | 31.83 | 17.15 |
August | 0.196801E+10 | 920.37 | 19-AUG-10:35 | 29.03 | 16.32 | 0.148199E+09 | 91.65 | 18-AUG-21:40 | 29.03 | 16.32 |
September | 0.179874E+10 | 896.79 | 03-SEP-10:35 | 28.53 | 16.32 | 0.137848E+09 | 88.21 | 01-SEP-21:40 | 28.53 | 16.32 |
October | 0.163005E+10 | 1278.96 | 12-OCT-03:53 | 6.10 | 1.56 | 0.132346E+09 | 86.66 | 02-OCT-21:40 | 6.10 | 1.56 |
November | 0.131416E+10 | 1222.62 | 25-NOV-23:26 | 2.25 | -0.8 | 0.117742E+09 | 78.06 | 02-NOV-21:40 | 2.25 | -0.8 |
December | 0.860888E+09 | 1055.86 | 20-DEC-18:05 | 3.30 | -2.9 | 0.117338E+09 | 73.15 | 01-DEC-22:30 | 3.30 | -2.9 |
Annual Sum or Average | 0.179240E+11 | 0.155523E+10 | ||||||||
Minimum of Months | 0.860888E+09 | 896.79 | 1.60 | -2.9 | 0.107273E+09 | 73.15 | 2.20 | -2.9 | ||
Maximum of Months | 0.200537E+10 | 1335.35 | 32.60 | 17.15 | 0.149204E+09 | 92.66 | 31.83 | 17.15 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.476592E+11 | 53436.15 | 03-JAN-21:39 | 1.30 | -1.6 | 0.652204E+09 | 547.82 | 12-JAN-22:30 | 1.65 | 0.12 |
February | 0.435042E+11 | 52860.24 | 01-FEB-21:30 | 0.25 | -0.5 | 0.591231E+09 | 620.51 | 28-FEB-23:10 | 3.27 | -0.7 |
March | 0.494592E+11 | 51649.42 | 02-MAR-21:58 | 4.40 | 1.67 | 0.654466E+09 | 552.65 | 10-MAR-23:30 | 1.15 | -3.0 |
April | 0.491096E+11 | 48827.73 | 23-APR-21:46 | 4.37 | 1.12 | 0.630778E+09 | 521.53 | 07-APR-04:30 | 4.37 | 1.12 |
May | 0.515763E+11 | 40982.72 | 04-MAY-06:10 | 5.78 | 2.63 | 0.650211E+09 | 481.97 | 05-MAY-04:40 | 5.60 | 1.69 |
June | 0.512774E+11 | 39613.86 | 28-JUN-20:00 | 30.00 | 16.25 | 0.630699E+09 | 384.67 | 20-JUN-02:49 | 30.00 | 16.25 |
July | 0.533696E+11 | 39637.68 | 21-JUL-20:00 | 30.60 | 12.57 | 0.649420E+09 | 382.03 | 21-JUL-21:10 | 29.72 | 14.71 |
August | 0.533202E+11 | 39462.99 | 17-AUG-20:00 | 28.30 | 14.86 | 0.652185E+09 | 382.08 | 30-AUG-21:10 | 23.72 | 13.61 |
September | 0.505445E+11 | 39040.49 | 13-SEP-20:00 | 23.90 | 12.88 | 0.629103E+09 | 381.96 | 11-SEP-21:10 | 23.90 | 12.88 |
October | 0.506236E+11 | 52155.04 | 24-OCT-19:09 | 2.12 | 0.37 | 0.649989E+09 | 533.14 | 26-OCT-23:10 | 3.30 | -0.7 |
November | 0.473768E+11 | 51038.12 | 27-NOV-21:49 | -0.2 | -3.1 | 0.631200E+09 | 567.94 | 16-NOV-23:40 | -0.2 | -3.1 |
December | 0.475212E+11 | 54234.20 | 04-DEC-20:57 | 1.10 | -1.8 | 0.652870E+09 | 533.90 | 04-DEC-22:10 | 0.00 | -2.4 |
Annual Sum or Average | 0.595342E+12 | 0.767436E+10 | ||||||||
Minimum of Months | 0.435042E+11 | 39040.49 | -0.2 | -3.1 | 0.591231E+09 | 381.96 | -0.2 | -3.1 | ||
Maximum of Months | 0.533696E+11 | 54234.20 | 30.60 | 16.25 | 0.654466E+09 | 620.51 | 30.00 | 16.25 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.211470E+11 | 22123.99 | 01-JAN-10:00 | 5.00 | 0.19 | 0.972458E+10 | 6990.81 | 11-JAN-03:20 | 3.70 | -1.2 |
February | 0.196507E+11 | 22025.27 | 04-FEB-13:00 | 4.40 | -1.7 | 0.893801E+10 | 6817.22 | 10-FEB-22:30 | 3.05 | -0.6 |
March | 0.214459E+11 | 19547.64 | 05-MAR-23:30 | 2.50 | -1.0 | 0.100469E+11 | 6969.86 | 10-MAR-23:30 | 1.15 | -3.0 |
April | 0.212442E+11 | 16810.31 | 23-APR-23:41 | 4.50 | 1.14 | 0.993017E+10 | 6952.21 | 07-APR-04:30 | 4.50 | 1.14 |
May | 0.218142E+11 | 13682.71 | 02-MAY-00:07 | 7.52 | 4.37 | 0.102278E+11 | 6466.39 | 05-MAY-04:19 | 5.60 | 1.69 |
June | 0.227052E+11 | 11808.91 | 28-JUN-21:10 | 28.62 | 15.82 | 0.101814E+11 | 6461.53 | 29-JUN-04:10 | 24.40 | 15.17 |
July | 0.249760E+11 | 12112.50 | 21-JUL-21:10 | 29.72 | 14.71 | 0.107244E+11 | 6463.30 | 01-JUL-00:40 | 29.72 | 14.71 |
August | 0.259287E+11 | 13385.32 | 20-AUG-12:00 | 32.80 | 17.08 | 0.108519E+11 | 6461.51 | 18-AUG-22:49 | 32.80 | 17.08 |
September | 0.255161E+11 | 15573.25 | 28-SEP-13:10 | 29.08 | 15.59 | 0.104124E+11 | 6461.94 | 22-SEP-22:10 | 29.08 | 15.59 |
October | 0.254700E+11 | 20130.61 | 28-OCT-04:35 | 3.67 | 0.13 | 0.105164E+11 | 6899.73 | 26-OCT-23:10 | 3.67 | 0.13 |
November | 0.225812E+11 | 25664.03 | 19-NOV-09:07 | 2.57 | -1.8 | 0.983419E+10 | 7038.92 | 16-NOV-23:40 | 2.57 | -1.8 |
December | 0.216089E+11 | 25541.39 | 23-DEC-12:41 | 5.22 | -1.6 | 0.978399E+10 | 6570.98 | 29-DEC-22:00 | 1.70 | -1.6 |
Annual Sum or Average | 0.274088E+12 | 0.121172E+12 | ||||||||
Minimum of Months | 0.196507E+11 | 11808.91 | 2.50 | -1.8 | 0.893801E+10 | 6461.51 | 1.15 | -3.0 | ||
Maximum of Months | 0.259287E+11 | 25664.03 | 32.80 | 17.08 | 0.108519E+11 | 7038.92 | 32.80 | 17.08 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.601079E+11 | 66062.70 | 15-JAN-22:37 | 1.70 | -1.8 | 0.308775E+11 | 20330.47 | 11-JAN-03:20 | 1.70 | -1.8 |
February | 0.557620E+11 | 63849.34 | 16-FEB-00:43 | 4.60 | 1.56 | 0.282530E+11 | 20571.36 | 21-FEB-22:49 | 1.10 | 0.54 |
March | 0.639176E+11 | 64900.80 | 17-MAR-23:00 | 2.20 | 1.65 | 0.317994E+11 | 20289.73 | 27-MAR-04:10 | 5.10 | 0.37 |
April | 0.661220E+11 | 65137.38 | 23-APR-23:40 | 4.60 | 1.19 | 0.309782E+11 | 20507.83 | 07-APR-04:30 | 4.60 | 1.19 |
May | 0.706411E+11 | 71921.87 | 04-MAY-05:47 | 5.60 | 2.64 | 0.320554E+11 | 19738.02 | 05-MAY-04:40 | 5.60 | 1.69 |
June | 0.747698E+11 | 43055.22 | 28-JUN-21:10 | 28.62 | 15.82 | 0.313339E+11 | 19232.98 | 20-JUN-02:49 | 28.62 | 15.82 |
July | 0.812789E+11 | 43769.54 | 21-JUL-21:10 | 29.72 | 14.71 | 0.324335E+11 | 19188.69 | 01-JUL-00:40 | 29.72 | 14.71 |
August | 0.819893E+11 | 43338.01 | 18-AUG-21:10 | 25.73 | 12.99 | 0.326325E+11 | 19185.05 | 29-AUG-22:40 | 18.33 | 15.84 |
September | 0.769793E+11 | 41620.28 | 13-SEP-20:10 | 23.53 | 12.84 | 0.314853E+11 | 19186.69 | 22-SEP-22:10 | 19.03 | 14.04 |
October | 0.732826E+11 | 63570.44 | 28-OCT-04:35 | 3.67 | 0.13 | 0.322639E+11 | 20414.00 | 26-OCT-23:10 | 3.67 | 0.13 |
November | 0.633287E+11 | 64995.01 | 24-NOV-23:13 | 4.23 | 1.02 | 0.308084E+11 | 20489.53 | 16-NOV-23:40 | 4.23 | 1.02 |
December | 0.600772E+11 | 65024.57 | 29-DEC-23:07 | 1.97 | -1.5 | 0.310287E+11 | 19782.97 | 04-DEC-22:10 | 1.97 | -1.5 |
Annual Sum or Average | 0.828257E+12 | 0.375949E+12 | ||||||||
Minimum of Months | 0.557620E+11 | 41620.28 | 1.70 | -1.8 | 0.282530E+11 | 19185.05 | 1.10 | -1.8 | ||
Maximum of Months | 0.819893E+11 | 71921.87 | 29.72 | 15.82 | 0.326325E+11 | 20571.36 | 29.72 | 15.84 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.404624E+09 | 4007.49 | 20-JAN-16:01 | 6.32 | 2.45 | 96386870.74 | 56.69 | 23-JAN-22:10 | 1.20 | -3.3 |
February | 0.548163E+09 | 4319.82 | 13-FEB-16:01 | 21.52 | 7.11 | 87621309.19 | 56.69 | 14-FEB-22:19 | 10.60 | 3.54 |
March | 0.851555E+09 | 4355.85 | 08-MAR-16:01 | 22.70 | 8.91 | 97749394.29 | 56.69 | 08-MAR-22:30 | 9.70 | 3.76 |
April | 0.151653E+10 | 4492.00 | 26-APR-15:01 | 25.50 | 10.03 | 95278303.21 | 56.69 | 21-APR-21:30 | 25.50 | 10.03 |
May | 0.185384E+10 | 4530.57 | 09-MAY-15:01 | 26.70 | 9.89 | 98605646.60 | 56.69 | 01-MAY-02:00 | 26.70 | 9.89 |
June | 0.253250E+10 | 4587.06 | 28-JUN-15:01 | 38.40 | 14.30 | 95773229.59 | 56.70 | 24-JUN-04:40 | 38.40 | 14.30 |
July | 0.289017E+10 | 4559.55 | 21-JUL-18:02 | 35.82 | 14.43 | 99054460.99 | 56.70 | 17-JUL-00:20 | 35.82 | 14.43 |
August | 0.287798E+10 | 3803.62 | 17-AUG-08:61 | 25.78 | 17.70 | 99101175.69 | 56.70 | 15-AUG-02:30 | 25.78 | 17.70 |
September | 0.239779E+10 | 4602.46 | 20-SEP-15:01 | 30.50 | 13.70 | 95665956.92 | 56.70 | 05-SEP-21:30 | 30.50 | 13.70 |
October | 0.170588E+10 | 4597.82 | 05-OCT-15:01 | 26.70 | 12.29 | 98342683.68 | 56.70 | 10-OCT-23:19 | 18.30 | 13.64 |
November | 0.730863E+09 | 4115.71 | 02-NOV-15:01 | 17.12 | 9.39 | 94408342.98 | 56.69 | 01-NOV-01:30 | 17.12 | 9.39 |
December | 0.354416E+09 | 4030.89 | 04-DEC-16:01 | 5.50 | -0.4 | 96321709.89 | 56.69 | 29-DEC-22:19 | 2.03 | -1.4 |
Annual Sum or Average | 0.186643E+11 | 0.115431E+10 | ||||||||
Minimum of Months | 0.354416E+09 | 3803.62 | 5.50 | -0.4 | 87621309.19 | 56.69 | 1.20 | -3.3 | ||
Maximum of Months | 0.289017E+10 | 4602.46 | 38.40 | 17.70 | 99101175.69 | 56.70 | 38.40 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120773E+09 | 3851.54 | 01-JAN-16:01 | 14.95 | 5.48 | 94394452.98 | 56.69 | 04-JAN-22:00 | 3.30 | 0.47 |
February | 0.222827E+09 | 4180.90 | 13-FEB-16:01 | 21.52 | 7.11 | 86035993.91 | 56.69 | 16-FEB-01:30 | 3.60 | 1.05 |
March | 0.487722E+09 | 4244.45 | 08-MAR-16:01 | 22.70 | 8.91 | 96764082.80 | 56.69 | 30-MAR-21:19 | 10.20 | 4.46 |
April | 0.123068E+10 | 4416.99 | 26-APR-15:01 | 25.50 | 10.03 | 94904001.85 | 56.69 | 17-APR-22:40 | 25.50 | 10.03 |
May | 0.174074E+10 | 4485.26 | 20-MAY-18:01 | 26.23 | 10.63 | 98507556.76 | 56.69 | 01-MAY-02:20 | 26.23 | 10.63 |
June | 0.253426E+10 | 4551.43 | 13-JUN-18:01 | 31.83 | 12.85 | 95790246.87 | 56.69 | 24-JUN-04:49 | 20.18 | 14.68 |
July | 0.281693E+10 | 4521.15 | 21-JUL-18:02 | 35.82 | 14.43 | 99066410.03 | 56.70 | 17-JUL-00:10 | 35.82 | 14.43 |
August | 0.263594E+10 | 3757.99 | 17-AUG-08:61 | 25.78 | 17.70 | 99064040.81 | 56.70 | 12-AUG-02:20 | 25.78 | 17.70 |
September | 0.192691E+10 | 4495.10 | 21-SEP-15:01 | 30.00 | 14.18 | 95514143.00 | 56.69 | 01-SEP-00:30 | 30.00 | 14.18 |
October | 0.107857E+10 | 4478.13 | 05-OCT-15:01 | 26.70 | 12.29 | 97507744.89 | 56.70 | 10-OCT-21:30 | 20.00 | 14.22 |
November | 0.244878E+09 | 3986.87 | 02-NOV-15:01 | 17.12 | 9.39 | 92812779.42 | 56.69 | 01-NOV-01:10 | 17.12 | 9.39 |
December | 92316732.26 | 3834.31 | 29-DEC-16:01 | 11.42 | 3.74 | 94019213.58 | 56.69 | 25-DEC-03:30 | 11.42 | 3.74 |
Annual Sum or Average | 0.151326E+11 | 0.114438E+10 | ||||||||
Minimum of Months | 92316732.26 | 3757.99 | 11.42 | 3.74 | 86035993.91 | 56.69 | 3.30 | 0.47 | ||
Maximum of Months | 0.281693E+10 | 4551.43 | 35.82 | 17.70 | 99066410.03 | 56.70 | 35.82 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.521179E+09 | 847.23 | 03-JAN-12:40 | 13.17 | 5.04 | 0.00 | 0.00 | 01-JAN-00:10 | 13.17 | 5.04 |
February | 0.489070E+09 | 871.58 | 14-FEB-13:00 | 19.40 | 6.65 | 0.00 | 0.00 | 01-FEB-00:10 | 19.40 | 6.65 |
March | 0.473484E+09 | 744.66 | 08-MAR-13:30 | 21.40 | 9.29 | 0.00 | 0.00 | 01-MAR-00:10 | 21.40 | 9.29 |
April | 0.478592E+09 | 573.51 | 13-APR-13:20 | 24.07 | 9.13 | 0.00 | 0.00 | 01-APR-00:10 | 24.07 | 9.13 |
May | 0.465282E+09 | 422.39 | 13-MAY-13:10 | 28.40 | 11.85 | 0.00 | 0.00 | 01-MAY-00:10 | 28.40 | 11.85 |
June | 0.588166E+09 | 469.87 | 29-JUN-14:30 | 37.25 | 15.80 | 0.00 | 0.00 | 01-JUN-00:10 | 37.25 | 15.80 |
July | 0.763827E+09 | 515.72 | 23-JUL-13:30 | 36.15 | 17.47 | 0.00 | 0.00 | 01-JUL-00:10 | 36.15 | 17.47 |
August | 0.831131E+09 | 649.19 | 22-AUG-13:30 | 31.40 | 16.68 | 0.00 | 0.00 | 01-AUG-00:10 | 31.40 | 16.68 |
September | 0.843081E+09 | 820.19 | 28-SEP-13:30 | 29.45 | 15.27 | 0.00 | 0.00 | 01-SEP-00:10 | 29.45 | 15.27 |
October | 0.820294E+09 | 877.14 | 19-OCT-12:30 | 20.55 | 8.60 | 0.00 | 0.00 | 01-OCT-00:10 | 20.55 | 8.60 |
November | 0.665947E+09 | 854.81 | 20-NOV-13:30 | 13.85 | 4.44 | 0.00 | 0.00 | 01-NOV-00:10 | 13.85 | 4.44 |
December | 0.562609E+09 | 861.84 | 31-DEC-13:40 | 9.43 | 1.41 | 0.00 | 0.00 | 01-DEC-00:10 | 9.43 | 1.41 |
Annual Sum or Average | 0.750266E+10 | 0.00 | ||||||||
Minimum of Months | 0.465282E+09 | 422.39 | 9.43 | 1.41 | 0.00 | 0.00 | 9.43 | 1.41 | ||
Maximum of Months | 0.843081E+09 | 877.14 | 37.25 | 17.47 | 0.00 | 0.00 | 37.25 | 17.47 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57389684.33 | 456.07 | 22-JAN-19:03 | 2.48 | -2.1 | 94527804.76 | 56.69 | 30-JAN-23:49 | 3.07 | 0.26 |
February | 86543428.63 | 899.31 | 15-FEB-19:01 | 9.50 | 2.34 | 85753005.62 | 56.69 | 23-FEB-22:10 | 0.68 | 0.38 |
March | 0.218192E+09 | 1071.61 | 27-MAR-15:01 | 18.40 | 7.10 | 95961118.32 | 56.70 | 29-MAR-00:49 | 4.18 | 3.36 |
April | 0.433908E+09 | 1236.50 | 29-APR-15:01 | 25.60 | 10.24 | 93718573.30 | 56.69 | 02-APR-23:40 | 25.60 | 10.24 |
May | 0.626168E+09 | 1286.76 | 19-MAY-18:01 | 29.03 | 11.19 | 97516569.27 | 56.74 | 05-MAY-04:19 | 29.03 | 11.19 |
June | 0.862923E+09 | 1295.88 | 16-JUN-18:01 | 30.63 | 13.23 | 95230641.58 | 56.70 | 23-JUN-21:40 | 26.30 | 15.96 |
July | 0.972681E+09 | 1287.94 | 21-JUL-18:02 | 35.82 | 14.43 | 98595399.00 | 56.69 | 21-JUL-21:49 | 28.58 | 14.64 |
August | 0.879528E+09 | 1154.90 | 21-AUG-15:02 | 32.30 | 17.61 | 98426293.37 | 56.69 | 26-AUG-02:39 | 16.87 | 15.75 |
September | 0.647802E+09 | 1247.06 | 20-SEP-18:01 | 27.23 | 12.14 | 94452812.60 | 56.69 | 05-SEP-04:10 | 27.23 | 12.14 |
October | 0.371323E+09 | 1219.18 | 11-OCT-18:01 | 23.43 | 9.92 | 96336831.91 | 56.69 | 10-OCT-22:40 | 23.43 | 9.92 |
November | 0.127298E+09 | 1013.26 | 02-NOV-18:01 | 15.00 | 8.23 | 92203705.79 | 56.69 | 01-NOV-01:30 | 15.00 | 8.23 |
December | 52099859.68 | 435.33 | 23-DEC-19:04 | 3.85 | -2.4 | 94234355.76 | 56.69 | 26-DEC-22:10 | 1.93 | -0.1 |
Annual Sum or Average | 0.533586E+10 | 0.113696E+10 | ||||||||
Minimum of Months | 52099859.68 | 435.33 | 2.48 | -2.4 | 85753005.62 | 56.69 | 0.68 | -0.1 | ||
Maximum of Months | 0.972681E+09 | 1295.88 | 35.82 | 17.61 | 98595399.00 | 56.74 | 29.03 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.397186E+09 | 3513.11 | 01-JAN-09:01 | 2.67 | -1.3 | 96713387.06 | 56.69 | 31-JAN-00:10 | 2.62 | 0.23 |
February | 0.499128E+09 | 3752.68 | 13-FEB-16:01 | 21.52 | 7.11 | 87878791.45 | 56.69 | 14-FEB-22:19 | 10.60 | 3.54 |
March | 0.929275E+09 | 3802.86 | 08-MAR-16:01 | 22.70 | 8.91 | 98210965.88 | 56.69 | 24-MAR-21:10 | 9.82 | 2.11 |
April | 0.171653E+10 | 3922.13 | 29-APR-15:01 | 25.60 | 10.24 | 95765852.69 | 56.69 | 15-APR-01:39 | 25.60 | 10.24 |
May | 0.204932E+10 | 3964.81 | 21-MAY-15:01 | 28.22 | 12.52 | 99044883.03 | 56.69 | 22-MAY-00:40 | 20.73 | 13.56 |
June | 0.274432E+10 | 4006.71 | 28-JUN-15:01 | 38.40 | 14.30 | 95963314.29 | 56.69 | 24-JUN-04:30 | 38.40 | 14.30 |
July | 0.315764E+10 | 3961.25 | 04-JUL-15:02 | 35.60 | 14.14 | 99128669.82 | 56.69 | 11-JUL-01:39 | 22.40 | 16.00 |
August | 0.307208E+10 | 3353.77 | 25-AUG-18:01 | 27.05 | 17.23 | 99231047.52 | 56.69 | 23-AUG-22:00 | 27.05 | 17.23 |
September | 0.246176E+10 | 4004.24 | 21-SEP-15:01 | 30.00 | 14.18 | 95880096.69 | 56.70 | 22-SEP-22:10 | 19.03 | 14.04 |
October | 0.172388E+10 | 3999.24 | 06-OCT-15:01 | 27.80 | 12.71 | 98649117.17 | 56.69 | 10-OCT-23:40 | 18.30 | 13.55 |
November | 0.737857E+09 | 3586.93 | 13-NOV-09:01 | 2.67 | -0.6 | 94754990.83 | 56.69 | 01-NOV-01:30 | 2.67 | -0.6 |
December | 0.344424E+09 | 3515.99 | 31-DEC-09:01 | -0.3 | -4.0 | 96660800.31 | 56.69 | 25-DEC-05:10 | -0.3 | -4.0 |
Annual Sum or Average | 0.198334E+11 | 0.115788E+10 | ||||||||
Minimum of Months | 0.344424E+09 | 3353.77 | -0.3 | -4.0 | 87878791.45 | 56.69 | -0.3 | -4.0 | ||
Maximum of Months | 0.315764E+10 | 4006.71 | 38.40 | 17.23 | 99231047.52 | 56.70 | 38.40 | 17.23 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115256E+09 | 3277.11 | 01-JAN-09:01 | 2.67 | -1.3 | 94380638.92 | 56.69 | 24-JAN-00:10 | 1.60 | -2.7 |
February | 0.181335E+09 | 3494.40 | 14-FEB-16:02 | 22.02 | 7.76 | 86028418.22 | 56.69 | 20-FEB-05:40 | 4.60 | 1.55 |
March | 0.525538E+09 | 3711.79 | 08-MAR-16:01 | 22.70 | 8.91 | 97498510.93 | 56.69 | 17-MAR-21:19 | 2.93 | 2.08 |
April | 0.140594E+10 | 3876.50 | 29-APR-15:01 | 25.60 | 10.24 | 95660075.17 | 56.69 | 15-APR-00:00 | 25.60 | 10.24 |
May | 0.192765E+10 | 3926.30 | 21-MAY-15:01 | 28.22 | 12.52 | 99022641.96 | 56.69 | 22-MAY-00:10 | 21.83 | 13.88 |
June | 0.274250E+10 | 3969.99 | 28-JUN-15:01 | 38.40 | 14.30 | 95962701.29 | 56.69 | 24-JUN-04:40 | 38.40 | 14.30 |
July | 0.308137E+10 | 3915.49 | 21-JUL-18:02 | 35.82 | 14.43 | 99128410.60 | 56.69 | 09-JUL-01:19 | 35.82 | 14.43 |
August | 0.282398E+10 | 3372.63 | 23-AUG-15:02 | 24.72 | 18.18 | 99227270.57 | 56.69 | 22-AUG-04:49 | 24.72 | 18.18 |
September | 0.197598E+10 | 3917.48 | 21-SEP-15:01 | 30.00 | 14.18 | 95841502.63 | 56.69 | 01-SEP-01:30 | 30.00 | 14.18 |
October | 0.106003E+10 | 3899.67 | 06-OCT-15:01 | 27.80 | 12.71 | 98117421.35 | 56.69 | 10-OCT-22:10 | 19.72 | 14.02 |
November | 0.256171E+09 | 3458.42 | 07-NOV-09:01 | 4.87 | 0.96 | 92902380.55 | 56.69 | 01-NOV-00:00 | 4.87 | 0.96 |
December | 91606996.52 | 3283.71 | 30-DEC-09:01 | 1.15 | -2.7 | 93850164.79 | 56.69 | 01-DEC-05:49 | 1.15 | -2.7 |
Annual Sum or Average | 0.161874E+11 | 0.114762E+10 | ||||||||
Minimum of Months | 91606996.52 | 3277.11 | 1.15 | -2.7 | 86028418.22 | 56.69 | 1.15 | -2.7 | ||
Maximum of Months | 0.308137E+10 | 3969.99 | 38.40 | 18.18 | 99227270.57 | 56.69 | 38.40 | 18.18 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.300652E+10 | 2611.10 | 29-JAN-20:00 | 1.10 | -2.7 | 0.133226E+10 | 877.79 | 02-JAN-22:00 | 1.10 | -2.7 |
February | 0.288633E+10 | 2586.41 | 08-FEB-22:05 | 1.60 | -1.7 | 0.123185E+10 | 906.70 | 15-FEB-22:30 | 6.40 | 2.29 |
March | 0.350623E+10 | 2796.59 | 09-MAR-05:17 | 3.67 | 0.65 | 0.144778E+10 | 917.27 | 13-MAR-21:40 | 12.43 | 3.82 |
April | 0.384235E+10 | 2995.24 | 24-APR-00:33 | 4.40 | 1.10 | 0.149151E+10 | 951.82 | 14-APR-23:49 | 4.40 | 1.10 |
May | 0.430183E+10 | 2936.26 | 19-MAY-18:30 | 28.30 | 10.89 | 0.157992E+10 | 951.88 | 17-MAY-22:10 | 28.30 | 10.89 |
June | 0.505561E+10 | 3523.09 | 16-JUN-18:30 | 29.70 | 12.88 | 0.156363E+10 | 951.93 | 01-JUN-01:10 | 29.70 | 12.88 |
July | 0.568877E+10 | 3661.40 | 21-JUL-18:30 | 35.25 | 14.38 | 0.161927E+10 | 951.90 | 01-JUL-00:40 | 35.25 | 14.38 |
August | 0.567867E+10 | 3441.04 | 18-AUG-18:15 | 31.67 | 15.79 | 0.162542E+10 | 951.87 | 21-AUG-00:49 | 24.78 | 16.59 |
September | 0.499973E+10 | 2909.10 | 13-SEP-18:15 | 26.67 | 13.74 | 0.156279E+10 | 951.91 | 22-SEP-22:10 | 19.03 | 14.04 |
October | 0.435157E+10 | 2864.79 | 12-OCT-03:53 | 6.10 | 1.56 | 0.155869E+10 | 951.86 | 20-OCT-21:10 | 14.22 | 8.62 |
November | 0.340560E+10 | 2768.92 | 25-NOV-23:26 | 2.25 | -0.8 | 0.139830E+10 | 926.41 | 01-NOV-21:40 | 2.25 | -0.8 |
December | 0.300308E+10 | 2542.44 | 04-DEC-11:33 | 3.13 | -0.6 | 0.131680E+10 | 849.55 | 01-DEC-22:30 | 3.13 | -0.6 |
Annual Sum or Average | 0.497263E+11 | 0.177282E+11 | ||||||||
Minimum of Months | 0.288633E+10 | 2542.44 | 1.10 | -2.7 | 0.123185E+10 | 849.55 | 1.10 | -2.7 | ||
Maximum of Months | 0.568877E+10 | 3661.40 | 35.25 | 15.79 | 0.162542E+10 | 951.93 | 35.25 | 16.59 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351558E+09 | 4217.73 | 09-JAN-16:01 | 14.45 | 4.55 | 95838193.21 | 56.69 | 31-JAN-00:10 | 2.62 | 0.23 |
February | 0.495610E+09 | 4566.58 | 13-FEB-16:01 | 21.52 | 7.11 | 87212708.93 | 56.69 | 15-FEB-22:10 | 6.60 | 2.40 |
March | 0.748447E+09 | 4596.59 | 08-MAR-16:01 | 22.70 | 8.91 | 97341481.76 | 56.69 | 10-MAR-22:40 | 3.00 | -2.0 |
April | 0.139813E+10 | 4748.26 | 13-APR-15:01 | 25.10 | 9.79 | 95048887.66 | 56.69 | 24-APR-21:30 | 16.15 | 6.12 |
May | 0.176494E+10 | 4793.36 | 20-MAY-18:01 | 26.23 | 10.63 | 98416520.03 | 56.70 | 24-MAY-22:49 | 12.30 | 10.30 |
June | 0.256388E+10 | 4867.36 | 28-JUN-15:01 | 38.40 | 14.30 | 95705739.50 | 56.70 | 29-JUN-03:30 | 23.60 | 14.82 |
July | 0.297568E+10 | 4838.39 | 21-JUL-18:02 | 35.82 | 14.43 | 99027997.28 | 56.70 | 25-JUL-01:10 | 22.80 | 15.77 |
August | 0.293463E+10 | 3948.90 | 18-AUG-08:61 | 24.55 | 15.85 | 99051984.46 | 56.70 | 12-AUG-00:49 | 24.55 | 15.85 |
September | 0.232608E+10 | 4872.10 | 20-SEP-15:01 | 30.50 | 13.70 | 95536613.45 | 56.70 | 06-SEP-22:10 | 30.50 | 13.70 |
October | 0.154318E+10 | 4866.59 | 05-OCT-15:01 | 26.70 | 12.29 | 98052881.76 | 56.70 | 02-OCT-21:30 | 26.70 | 12.29 |
November | 0.585777E+09 | 4338.03 | 02-NOV-15:01 | 17.12 | 9.39 | 93920095.00 | 56.69 | 06-NOV-22:49 | 5.78 | 0.64 |
December | 0.299236E+09 | 4252.27 | 04-DEC-16:01 | 5.50 | -0.4 | 95772893.86 | 56.69 | 25-DEC-05:49 | 5.10 | 0.53 |
Annual Sum or Average | 0.179871E+11 | 0.115093E+10 | ||||||||
Minimum of Months | 0.299236E+09 | 3948.90 | 5.50 | -0.4 | 87212708.93 | 56.69 | 2.62 | -2.0 | ||
Maximum of Months | 0.297568E+10 | 4872.10 | 38.40 | 15.85 | 99051984.46 | 56.70 | 30.50 | 15.85 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 99920203.61 | 4046.78 | 05-JAN-16:01 | 15.63 | 6.64 | 93722639.35 | 56.69 | 12-JAN-22:00 | 1.10 | -0.4 |
February | 0.191124E+09 | 4394.13 | 13-FEB-16:01 | 21.52 | 7.11 | 85514964.99 | 56.69 | 22-FEB-22:10 | 3.30 | 0.33 |
March | 0.412893E+09 | 4462.21 | 08-MAR-16:01 | 22.70 | 8.91 | 96247500.57 | 56.69 | 16-MAR-03:49 | 3.98 | 1.90 |
April | 0.110737E+10 | 4655.28 | 26-APR-15:01 | 25.50 | 10.03 | 94654724.07 | 56.69 | 02-APR-23:40 | 25.50 | 10.03 |
May | 0.164531E+10 | 4741.48 | 20-MAY-18:01 | 26.23 | 10.63 | 98319399.51 | 56.70 | 07-MAY-00:00 | 26.23 | 10.63 |
June | 0.256303E+10 | 4814.73 | 13-JUN-18:01 | 31.83 | 12.85 | 95725718.86 | 56.70 | 29-JUN-03:39 | 23.87 | 14.88 |
July | 0.289735E+10 | 4790.53 | 21-JUL-18:02 | 35.82 | 14.43 | 99044791.06 | 56.70 | 12-JUL-01:10 | 35.82 | 14.43 |
August | 0.267863E+10 | 3898.76 | 18-AUG-08:61 | 24.55 | 15.85 | 99008794.55 | 56.70 | 04-AUG-23:40 | 24.55 | 15.85 |
September | 0.182839E+10 | 4746.30 | 21-SEP-15:01 | 30.00 | 14.18 | 95379138.30 | 56.69 | 06-SEP-21:10 | 30.00 | 14.18 |
October | 0.915695E+09 | 4723.65 | 05-OCT-15:01 | 26.70 | 12.29 | 97107458.01 | 56.69 | 01-OCT-01:30 | 26.70 | 12.29 |
November | 0.179622E+09 | 4177.83 | 02-NOV-15:01 | 17.12 | 9.39 | 92059198.28 | 56.69 | 02-NOV-22:10 | 10.00 | 7.26 |
December | 69181055.23 | 4012.61 | 02-DEC-16:01 | 11.10 | 3.02 | 93382703.57 | 56.69 | 25-DEC-05:19 | 5.40 | 0.77 |
Annual Sum or Average | 0.145885E+11 | 0.114017E+10 | ||||||||
Minimum of Months | 69181055.23 | 3898.76 | 11.10 | 3.02 | 85514964.99 | 56.69 | 1.10 | -0.4 | ||
Maximum of Months | 0.289735E+10 | 4814.73 | 35.82 | 15.85 | 99044791.06 | 56.70 | 35.82 | 15.85 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.798430E+09 | 2000.33 | 03-JAN-16:01 | 14.53 | 5.76 | 97709523.96 | 56.69 | 02-JAN-22:30 | 14.53 | 5.76 |
February | 0.775429E+09 | 2144.47 | 14-FEB-16:02 | 22.02 | 7.76 | 88519008.95 | 56.69 | 15-FEB-23:30 | 5.85 | 2.15 |
March | 0.768387E+09 | 2143.32 | 08-MAR-16:01 | 22.70 | 8.91 | 98097418.16 | 56.69 | 30-MAR-21:49 | 9.60 | 4.25 |
April | 0.868823E+09 | 2183.21 | 13-APR-15:01 | 25.10 | 9.79 | 95197465.84 | 56.69 | 17-APR-22:00 | 12.20 | 3.16 |
May | 0.900317E+09 | 2188.09 | 31-MAY-15:01 | 27.38 | 11.00 | 98412528.46 | 56.69 | 21-MAY-23:10 | 27.38 | 11.00 |
June | 0.119489E+10 | 2208.78 | 28-JUN-15:01 | 38.40 | 14.30 | 95638167.78 | 56.69 | 24-JUN-03:39 | 38.40 | 14.30 |
July | 0.154247E+10 | 2172.75 | 21-JUL-18:02 | 35.82 | 14.43 | 98963863.72 | 56.70 | 21-JUL-21:19 | 29.43 | 14.70 |
August | 0.165446E+10 | 1901.96 | 11-AUG-18:01 | 27.93 | 17.26 | 99017073.66 | 56.69 | 08-AUG-03:09 | 27.93 | 17.26 |
September | 0.160075E+10 | 2252.76 | 27-SEP-15:01 | 29.32 | 12.99 | 95659775.67 | 56.69 | 07-SEP-01:19 | 29.32 | 12.99 |
October | 0.145463E+10 | 2203.32 | 31-OCT-15:01 | 23.80 | 8.59 | 98634638.87 | 56.69 | 11-OCT-02:09 | 23.80 | 8.59 |
November | 0.104755E+10 | 2027.99 | 02-NOV-15:01 | 17.12 | 9.39 | 95208669.67 | 56.69 | 01-NOV-01:00 | 17.12 | 9.39 |
December | 0.873657E+09 | 1999.78 | 31-DEC-16:01 | 9.82 | 1.41 | 97676155.55 | 56.69 | 06-DEC-22:19 | 9.82 | 1.41 |
Annual Sum or Average | 0.134798E+11 | 0.115873E+10 | ||||||||
Minimum of Months | 0.768387E+09 | 1901.96 | 9.82 | 1.41 | 88519008.95 | 56.69 | 5.85 | 1.41 | ||
Maximum of Months | 0.165446E+10 | 2252.76 | 38.40 | 17.26 | 99017073.66 | 56.70 | 38.40 | 17.26 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.340228E+11 | 32229.98 | 23-JAN-23:15 | 1.70 | -2.9 | 0.174662E+11 | 13248.42 | 11-JAN-03:20 | 1.70 | -2.9 |
February | 0.317154E+11 | 31077.12 | 23-FEB-22:53 | 1.10 | 0.57 | 0.160245E+11 | 13292.87 | 21-FEB-22:49 | 1.10 | 0.57 |
March | 0.374641E+11 | 38416.08 | 17-MAR-22:54 | 2.20 | 1.65 | 0.183266E+11 | 13103.70 | 10-MAR-23:30 | 2.20 | 1.65 |
April | 0.392691E+11 | 34421.42 | 07-APR-06:00 | 3.30 | -1.8 | 0.180670E+11 | 13208.21 | 24-APR-00:40 | 4.40 | 1.10 |
May | 0.427145E+11 | 31253.53 | 04-MAY-04:04 | 6.02 | 3.44 | 0.188646E+11 | 12269.87 | 05-MAY-04:40 | 5.60 | 1.69 |
June | 0.444313E+11 | 23453.36 | 28-JUN-21:20 | 28.33 | 15.66 | 0.184806E+11 | 11407.32 | 20-JUN-02:49 | 28.33 | 15.66 |
July | 0.469540E+11 | 23573.84 | 21-JUL-21:20 | 29.43 | 14.70 | 0.190669E+11 | 11378.65 | 21-JUL-21:19 | 29.43 | 14.70 |
August | 0.462025E+11 | 22737.17 | 17-AUG-22:00 | 27.20 | 14.57 | 0.191036E+11 | 11347.58 | 01-AUG-21:19 | 27.20 | 14.57 |
September | 0.422940E+11 | 21581.51 | 01-SEP-21:10 | 20.92 | 14.02 | 0.182781E+11 | 11347.14 | 22-SEP-22:10 | 19.03 | 14.04 |
October | 0.399577E+11 | 31651.41 | 25-OCT-22:37 | 2.60 | -0.6 | 0.184538E+11 | 13356.86 | 26-OCT-23:10 | 3.30 | -0.7 |
November | 0.350490E+11 | 33245.10 | 15-NOV-23:30 | 3.05 | 0.07 | 0.173809E+11 | 13428.23 | 16-NOV-23:40 | 1.70 | -1.9 |
December | 0.336153E+11 | 33601.87 | 13-DEC-23:58 | 3.90 | -1.9 | 0.174357E+11 | 12021.73 | 08-DEC-22:30 | 3.90 | -1.9 |
Annual Sum or Average | 0.473690E+12 | 0.216948E+12 | ||||||||
Minimum of Months | 0.317154E+11 | 21581.51 | 1.10 | -2.9 | 0.160245E+11 | 11347.14 | 1.10 | -2.9 | ||
Maximum of Months | 0.469540E+11 | 38416.08 | 29.43 | 15.66 | 0.191036E+11 | 13428.23 | 29.43 | 15.66 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362592E+11 | 34072.17 | 23-JAN-23:15 | 1.70 | -2.9 | 0.180836E+11 | 13500.17 | 11-JAN-03:20 | 1.70 | -2.9 |
February | 0.337115E+11 | 33296.25 | 20-FEB-22:31 | 3.13 | 0.19 | 0.165461E+11 | 13423.50 | 21-FEB-22:49 | 1.10 | 0.54 |
March | 0.396621E+11 | 42370.64 | 17-MAR-22:54 | 2.20 | 1.65 | 0.187952E+11 | 13255.03 | 29-MAR-02:09 | 5.10 | 3.70 |
April | 0.413939E+11 | 36513.93 | 07-APR-06:00 | 3.30 | -1.8 | 0.183467E+11 | 13417.71 | 24-APR-00:40 | 4.40 | 1.10 |
May | 0.449647E+11 | 33076.99 | 04-MAY-04:04 | 6.02 | 3.44 | 0.190831E+11 | 12501.30 | 05-MAY-04:40 | 5.60 | 1.69 |
June | 0.467217E+11 | 24804.48 | 28-JUN-21:20 | 28.33 | 15.66 | 0.186182E+11 | 11414.00 | 23-JUN-21:19 | 28.33 | 15.66 |
July | 0.493133E+11 | 24943.20 | 21-JUL-21:20 | 29.43 | 14.70 | 0.191997E+11 | 11404.04 | 21-JUL-21:19 | 29.43 | 14.70 |
August | 0.484832E+11 | 24087.07 | 07-AUG-21:20 | 26.33 | 15.17 | 0.192472E+11 | 11380.99 | 22-AUG-21:19 | 21.33 | 15.41 |
September | 0.443410E+11 | 22927.03 | 01-SEP-21:10 | 20.92 | 14.02 | 0.184485E+11 | 11347.33 | 22-SEP-22:10 | 19.03 | 14.04 |
October | 0.419541E+11 | 34131.60 | 30-OCT-03:58 | 3.30 | -1.3 | 0.187526E+11 | 13465.60 | 26-OCT-23:10 | 3.30 | -1.3 |
November | 0.370300E+11 | 36202.51 | 15-NOV-23:30 | 3.05 | 0.07 | 0.178464E+11 | 13769.92 | 16-NOV-23:40 | 1.70 | -1.9 |
December | 0.358659E+11 | 36855.76 | 13-DEC-23:58 | 3.90 | -1.9 | 0.180657E+11 | 12335.13 | 04-DEC-22:10 | 3.90 | -1.9 |
Annual Sum or Average | 0.499701E+12 | 0.221033E+12 | ||||||||
Minimum of Months | 0.337115E+11 | 22927.03 | 1.70 | -2.9 | 0.165461E+11 | 11347.33 | 1.10 | -2.9 | ||
Maximum of Months | 0.493133E+11 | 42370.64 | 29.43 | 15.66 | 0.192472E+11 | 13769.92 | 29.43 | 15.66 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.489750E+11 | 37798.68 | 31-JAN-12:51 | 5.00 | -1.3 | 0.188907E+11 | 11523.11 | 20-JAN-17:30 | 5.00 | -1.3 |
February | 0.452090E+11 | 39788.84 | 06-FEB-17:01 | 4.03 | -1.0 | 0.170672E+11 | 11655.37 | 04-FEB-18:00 | 4.03 | -1.0 |
March | 0.522657E+11 | 36794.87 | 22-MAR-07:57 | 4.40 | 0.35 | 0.188938E+11 | 11382.43 | 04-MAR-18:10 | 4.40 | 0.35 |
April | 0.533792E+11 | 36239.88 | 09-APR-05:22 | 4.45 | -0.6 | 0.182734E+11 | 11351.07 | 15-APR-17:49 | 7.77 | 4.13 |
May | 0.565743E+11 | 33221.12 | 04-MAY-06:10 | 5.78 | 2.63 | 0.188736E+11 | 11319.63 | 13-MAY-17:19 | 27.80 | 11.54 |
June | 0.572179E+11 | 31720.83 | 29-JUN-10:40 | 32.60 | 16.86 | 0.182664E+11 | 11319.64 | 24-JUN-17:19 | 32.60 | 16.86 |
July | 0.601450E+11 | 32013.48 | 23-JUL-10:40 | 31.83 | 17.15 | 0.188685E+11 | 11319.69 | 29-JUL-17:19 | 29.80 | 16.42 |
August | 0.596853E+11 | 31964.77 | 20-AUG-10:40 | 30.17 | 17.03 | 0.188758E+11 | 11319.65 | 05-AUG-17:19 | 30.17 | 17.03 |
September | 0.558084E+11 | 31792.73 | 03-SEP-10:40 | 28.53 | 16.32 | 0.182616E+11 | 11319.64 | 09-SEP-17:19 | 23.70 | 15.03 |
October | 0.544037E+11 | 36970.14 | 24-OCT-16:58 | 2.80 | 0.24 | 0.188770E+11 | 11405.10 | 24-OCT-16:30 | 2.80 | 0.24 |
November | 0.493544E+11 | 42462.57 | 29-NOV-08:41 | 2.62 | -2.0 | 0.182806E+11 | 11418.15 | 04-NOV-17:40 | 2.62 | -2.0 |
December | 0.487473E+11 | 37773.06 | 16-DEC-10:37 | 3.30 | -3.7 | 0.188965E+11 | 11551.67 | 09-DEC-18:40 | 3.30 | -3.7 |
Annual Sum or Average | 0.641765E+12 | 0.222325E+12 | ||||||||
Minimum of Months | 0.452090E+11 | 31720.83 | 2.62 | -3.7 | 0.170672E+11 | 11319.63 | 2.62 | -3.7 | ||
Maximum of Months | 0.601450E+11 | 42462.57 | 32.60 | 17.15 | 0.188965E+11 | 11655.37 | 32.60 | 17.03 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.424580E+10 | 4074.44 | 29-JAN-20:00 | 1.10 | -2.7 | 0.136236E+10 | 895.65 | 02-JAN-22:00 | 1.10 | -2.7 |
February | 0.434573E+10 | 4098.59 | 08-FEB-22:05 | 1.60 | -1.7 | 0.127509E+10 | 968.83 | 14-FEB-22:30 | 10.60 | 3.54 |
March | 0.564772E+10 | 4368.31 | 09-MAR-05:17 | 3.67 | 0.65 | 0.152317E+10 | 986.19 | 13-MAR-21:30 | 12.25 | 3.71 |
April | 0.690116E+10 | 5622.33 | 13-APR-14:10 | 24.50 | 9.26 | 0.158524E+10 | 1007.38 | 21-APR-21:19 | 15.00 | 7.43 |
May | 0.842868E+10 | 5960.19 | 30-MAY-14:30 | 27.20 | 12.25 | 0.167568E+10 | 1007.45 | 17-MAY-22:10 | 27.20 | 12.25 |
June | 0.107396E+11 | 7450.79 | 28-JUN-15:03 | 38.40 | 14.30 | 0.165754E+10 | 1007.52 | 01-JUN-01:10 | 38.40 | 14.30 |
July | 0.125772E+11 | 7542.23 | 22-JUL-13:30 | 36.95 | 17.78 | 0.171420E+10 | 1007.51 | 01-JUL-00:40 | 36.95 | 17.78 |
August | 0.122647E+11 | 7696.74 | 20-AUG-13:10 | 33.07 | 17.06 | 0.172082E+10 | 1007.43 | 21-AUG-00:30 | 25.55 | 16.53 |
September | 0.100783E+11 | 7704.56 | 03-SEP-13:30 | 31.95 | 16.76 | 0.165212E+10 | 1007.48 | 22-SEP-22:10 | 19.03 | 14.04 |
October | 0.772226E+10 | 7007.70 | 01-OCT-12:00 | 25.60 | 14.51 | 0.162968E+10 | 1007.41 | 20-OCT-21:10 | 14.22 | 8.62 |
November | 0.530206E+10 | 4301.31 | 25-NOV-23:26 | 2.25 | -0.8 | 0.144033E+10 | 983.65 | 02-NOV-21:30 | 2.25 | -0.8 |
December | 0.418433E+10 | 4031.73 | 04-DEC-11:33 | 3.13 | -0.6 | 0.134891E+10 | 878.97 | 01-DEC-22:30 | 3.13 | -0.6 |
Annual Sum or Average | 0.924375E+11 | 0.185851E+11 | ||||||||
Minimum of Months | 0.418433E+10 | 4031.73 | 1.10 | -2.7 | 0.127509E+10 | 878.97 | 1.10 | -2.7 | ||
Maximum of Months | 0.125772E+11 | 7704.56 | 38.40 | 17.78 | 0.172082E+10 | 1007.52 | 38.40 | 17.78 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9760574.53 | 5102.52 | 15-JAN-22:33 | 1.70 |
February | 7542493.80 | 5052.73 | 16-FEB-00:42 | 4.60 |
March | 29400584.16 | 5982.71 | 02-MAR-04:38 | 4.60 |
April | 25369894.59 | 5867.14 | 20-APR-05:53 | 4.40 |
May | 703530.77 | 1867.28 | 04-MAY-04:02 | 6.02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 11272866.61 | 5477.56 | 27-OCT-01:06 | 3.80 |
November | 25489809.23 | 5889.26 | 15-NOV-01:26 | 4.40 |
December | 4252101.44 | 4930.52 | 25-DEC-22:49 | 2.15 |
Annual Sum or Average | 0.113792E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.70 | |
Maximum of Months | 29400584.16 | 5982.71 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44973065.20 | 529.53 | 19-JAN-07:10 | -2.8 |
February | 9322717.47 | 460.02 | 28-FEB-23:50 | 2.73 |
March | 9709024.85 | 607.17 | 03-MAR-04:30 | 4.40 |
April | 7686343.57 | 557.48 | 24-APR-02:20 | 4.60 |
May | 1351534.39 | 467.59 | 04-MAY-04:02 | 6.02 |
June | 71238.09 | 237.46 | 09-JUN-05:00 | 7.80 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 6504070.29 | 497.34 | 27-OCT-01:06 | 3.80 |
November | 9849777.82 | 592.87 | 10-NOV-04:59 | 5.00 |
December | 29936743.38 | 626.83 | 25-DEC-22:49 | 2.15 |
Annual Sum or Average | 0.119405E+09 | |||
Minimum of Months | 0.00 | 0.00 | -2.8 | |
Maximum of Months | 44973065.20 | 626.83 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3731960.80 | 513.59 | 15-JAN-22:33 | 1.70 |
February | 3019002.67 | 345.53 | 28-FEB-23:50 | 2.73 |
March | 3745027.45 | 389.88 | 03-MAR-04:30 | 4.40 |
April | 2847880.02 | 434.23 | 19-APR-05:35 | 4.63 |
May | 345361.63 | 271.59 | 04-MAY-04:02 | 6.02 |
June | 9005.22 | 30.02 | 09-JUN-05:00 | 7.80 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 2104011.15 | 347.08 | 27-OCT-01:06 | 3.80 |
November | 4875572.33 | 461.41 | 18-NOV-23:55 | 1.70 |
December | 4582590.31 | 392.77 | 25-DEC-22:49 | 2.15 |
Annual Sum or Average | 25260411.59 | |||
Minimum of Months | 0.00 | 0.00 | 1.70 | |
Maximum of Months | 4875572.33 | 513.59 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6181663.48 | 339.33 | 11-JAN-03:12 | 3.70 |
February | 5366303.52 | 329.90 | 28-FEB-23:50 | 2.73 |
March | 4515641.64 | 322.81 | 02-MAR-04:38 | 4.60 |
April | 2979932.67 | 285.36 | 07-APR-03:59 | 4.40 |
May | 378328.77 | 191.58 | 04-MAY-04:02 | 6.02 |
June | 7344.18 | 24.48 | 09-JUN-05:00 | 7.80 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 2506825.32 | 317.58 | 28-OCT-04:10 | 4.22 |
November | 7338986.76 | 347.67 | 29-NOV-01:35 | 4.60 |
December | 8525622.66 | 335.55 | 25-DEC-22:49 | 2.15 |
Annual Sum or Average | 37800649.00 | |||
Minimum of Months | 0.00 | 0.00 | 2.15 | |
Maximum of Months | 8525622.66 | 347.67 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19077206.30 | 685.52 | 12-JAN-18:05 | 3.12 |
February | 9763239.15 | 867.26 | 01-FEB-19:01 | 1.70 |
March | 8298833.85 | 405.53 | 02-MAR-04:38 | 4.60 |
April | 5860199.64 | 378.96 | 07-APR-03:59 | 4.40 |
May | 848153.39 | 296.51 | 04-MAY-04:02 | 6.02 |
June | 37444.65 | 124.82 | 09-JUN-05:00 | 7.80 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 5020380.92 | 400.79 | 28-OCT-04:10 | 4.22 |
November | 13545428.86 | 429.48 | 29-NOV-01:35 | 4.60 |
December | 14257967.25 | 710.61 | 15-DEC-15:08 | 4.40 |
Annual Sum or Average | 76708854.02 | |||
Minimum of Months | 0.00 | 0.00 | 1.70 | |
Maximum of Months | 19077206.30 | 867.26 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 2.30 |
February | 176237.60 | 1754.61 | 16-FEB-01:15 | 3.87 |
March | 2384354.50 | 3690.49 | 07-MAR-01:19 | 4.80 |
April | 1710508.37 | 3411.75 | 07-APR-03:59 | 4.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 2166654.38 | 3763.19 | 27-OCT-01:06 | 3.80 |
November | 2946548.78 | 3242.47 | 10-NOV-04:59 | 5.00 |
December | 257655.26 | 2373.52 | 01-DEC-02:18 | 4.13 |
Annual Sum or Average | 9641958.90 | |||
Minimum of Months | 0.00 | 0.00 | 2.30 | |
Maximum of Months | 2946548.78 | 3763.19 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12413488.72 | 3296.16 | 07-JAN-21:33 | 2.43 |
February | 13177755.05 | 2228.30 | 16-FEB-01:15 | 3.87 |
March | 28607578.19 | 2756.85 | 03-MAR-04:30 | 4.40 |
April | 23239778.47 | 2961.60 | 20-APR-05:53 | 4.40 |
May | 3049809.09 | 1934.13 | 04-MAY-04:02 | 6.02 |
June | 21914.77 | 73.05 | 09-JUN-05:00 | 7.80 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 16035851.41 | 2608.09 | 25-OCT-13:33 | 4.67 |
November | 27783744.79 | 3157.23 | 05-NOV-02:12 | 4.23 |
December | 18319581.08 | 3279.21 | 25-DEC-22:49 | 2.15 |
Annual Sum or Average | 0.142650E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.15 | |
Maximum of Months | 28607578.19 | 3296.16 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32799184.53 | 9474.71 | 10-JAN-23:57 | 3.90 |
February | 26826916.04 | 8882.45 | 25-FEB-23:30 | 1.95 |
March | 55433699.81 | 10274.21 | 07-MAR-01:19 | 4.80 |
April | 51061640.45 | 10659.45 | 07-APR-03:59 | 4.40 |
May | 1541439.60 | 4885.00 | 04-MAY-04:02 | 6.02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 26605277.57 | 9623.35 | 13-OCT-00:49 | 4.18 |
November | 58501651.75 | 11642.16 | 20-NOV-01:26 | 5.00 |
December | 32016224.29 | 7197.72 | 08-DEC-14:23 | 5.00 |
Annual Sum or Average | 0.284786E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.95 | |
Maximum of Months | 58501651.75 | 11642.16 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.481526E+09 | 2375.38 | 17-JAN-09:01 | -2.5 |
February | 0.303035E+09 | 2381.51 | 16-FEB-19:01 | 1.70 |
March | 0.107122E+09 | 2206.41 | 22-MAR-08:62 | 4.87 |
April | 11021039.28 | 1010.66 | 22-APR-08:03 | 13.77 |
May | 4948361.57 | 1067.63 | 17-MAY-08:03 | 15.97 |
June | 872722.98 | 1032.64 | 11-JUN-08:03 | 18.58 |
July | 274285.77 | 452.61 | 08-JUL-08:04 | 21.38 |
August | 386788.71 | 487.74 | 28-AUG-08:03 | 19.08 |
September | 628922.66 | 886.53 | 09-SEP-08:03 | 15.18 |
October | 49304165.07 | 2311.63 | 25-OCT-08:61 | 0.22 |
November | 0.137841E+09 | 2293.89 | 10-NOV-19:01 | 6.10 |
December | 0.487031E+09 | 2359.03 | 25-DEC-19:01 | 1.93 |
Annual Sum or Average | 0.158399E+10 | |||
Minimum of Months | 274285.77 | 452.61 | -2.5 | |
Maximum of Months | 0.487031E+09 | 2381.51 | 21.38 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.815151E+09 | 2395.44 | 25-JAN-09:01 | 2.67 |
February | 0.523724E+09 | 2390.70 | 16-FEB-19:01 | 1.70 |
March | 0.184814E+09 | 2298.25 | 04-MAR-09:01 | 2.15 |
April | 18598586.04 | 1145.62 | 29-APR-08:03 | 15.37 |
May | 5584292.59 | 1082.81 | 04-MAY-15:03 | 12.20 |
June | 752967.58 | 727.13 | 06-JUN-08:03 | 19.27 |
July | 256219.37 | 388.80 | 08-JUL-08:04 | 21.38 |
August | 599833.76 | 667.60 | 28-AUG-08:03 | 19.08 |
September | 1174000.30 | 1070.61 | 27-SEP-08:03 | 16.05 |
October | 82466037.99 | 2345.92 | 26-OCT-08:61 | 1.97 |
November | 0.303987E+09 | 2351.25 | 27-NOV-09:01 | -1.2 |
December | 0.896484E+09 | 2408.98 | 15-DEC-09:01 | -6.5 |
Annual Sum or Average | 0.283359E+10 | |||
Minimum of Months | 256219.37 | 388.80 | -6.5 | |
Maximum of Months | 0.896484E+09 | 2408.98 | 21.38 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 832743.75 | 59.40 | 19-JAN-05:00 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 832743.75 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 832743.75 | 59.40 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118751E+09 | 690.50 | 19-JAN-16:01 | 3.62 |
February | 69673084.81 | 688.26 | 05-FEB-16:01 | 3.48 |
March | 6456744.90 | 536.50 | 06-MAR-09:01 | 5.83 |
April | 1031840.55 | 371.96 | 18-APR-08:03 | 8.48 |
May | 811864.64 | 325.92 | 02-MAY-08:03 | 9.87 |
June | 217950.89 | 368.41 | 10-JUN-15:04 | 25.60 |
July | 148554.66 | 248.61 | 28-JUL-08:05 | 22.57 |
August | 226828.09 | 313.46 | 09-AUG-08:04 | 22.07 |
September | 497558.16 | 371.54 | 21-SEP-15:04 | 30.00 |
October | 5142845.25 | 675.28 | 26-OCT-08:61 | 1.97 |
November | 25806839.06 | 682.75 | 27-NOV-09:01 | -1.2 |
December | 0.150087E+09 | 701.74 | 15-DEC-09:01 | -6.5 |
Annual Sum or Average | 0.378852E+09 | |||
Minimum of Months | 148554.66 | 248.61 | -6.5 | |
Maximum of Months | 0.150087E+09 | 701.74 | 30.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.509339E+09 | 2327.93 | 20-JAN-09:01 | -3.2 |
February | 0.327491E+09 | 2332.85 | 16-FEB-19:01 | 1.70 |
March | 0.105241E+09 | 2232.90 | 03-MAR-19:01 | 5.32 |
April | 10389081.49 | 905.18 | 07-APR-18:03 | 10.92 |
May | 1995232.26 | 730.86 | 06-MAY-18:03 | 16.52 |
June | 233216.05 | 545.54 | 08-JUN-18:04 | 11.60 |
July | 17140.40 | 192.71 | 10-JUL-08:04 | 21.88 |
August | 6959.21 | 69.22 | 29-AUG-18:04 | 21.83 |
September | 212241.31 | 441.04 | 24-SEP-08:04 | 15.28 |
October | 49712676.04 | 2262.16 | 25-OCT-08:61 | 0.22 |
November | 0.148805E+09 | 2238.24 | 10-NOV-19:01 | 6.10 |
December | 0.510667E+09 | 2317.66 | 25-DEC-19:01 | 1.93 |
Annual Sum or Average | 0.166411E+10 | |||
Minimum of Months | 6959.21 | 69.22 | -3.2 | |
Maximum of Months | 0.510667E+09 | 2332.85 | 21.88 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.831063E+09 | 2334.46 | 19-JAN-16:01 | 3.62 |
February | 0.541789E+09 | 2343.00 | 16-FEB-19:01 | 1.70 |
March | 0.167143E+09 | 2243.11 | 03-MAR-19:01 | 5.32 |
April | 18788726.93 | 836.09 | 04-APR-18:03 | 15.92 |
May | 2669467.45 | 825.30 | 06-MAY-18:03 | 16.52 |
June | 227420.66 | 583.03 | 08-JUN-18:04 | 11.60 |
July | 21207.82 | 209.35 | 10-JUL-08:04 | 21.88 |
August | 25395.74 | 154.48 | 29-AUG-18:04 | 21.83 |
September | 409122.44 | 511.24 | 24-SEP-08:04 | 15.28 |
October | 78039445.27 | 2265.24 | 25-OCT-08:61 | 0.22 |
November | 0.301659E+09 | 2238.21 | 10-NOV-19:01 | 6.10 |
December | 0.900790E+09 | 2327.70 | 25-DEC-19:01 | 1.93 |
Annual Sum or Average | 0.284262E+10 | |||
Minimum of Months | 21207.82 | 154.48 | 0.22 | |
Maximum of Months | 0.900790E+09 | 2343.00 | 21.88 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11405413.66 | 655.79 | 11-JAN-03:12 | 3.70 |
February | 10294928.96 | 703.98 | 28-FEB-23:50 | 2.73 |
March | 9819772.98 | 666.39 | 02-MAR-04:38 | 4.60 |
April | 5900390.00 | 556.13 | 09-APR-03:52 | 4.40 |
May | 729816.07 | 381.87 | 04-MAY-04:02 | 6.02 |
June | 20519.18 | 68.40 | 09-JUN-05:00 | 7.80 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 4556010.94 | 590.77 | 28-OCT-04:10 | 4.22 |
November | 12610351.15 | 625.88 | 29-NOV-01:35 | 4.60 |
December | 15621120.62 | 773.11 | 25-DEC-22:49 | 2.15 |
Annual Sum or Average | 70958323.56 | |||
Minimum of Months | 0.00 | 0.00 | 2.15 | |
Maximum of Months | 15621120.62 | 773.11 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.873238E+09 | 2820.05 | 25-JAN-09:01 | 2.67 |
February | 0.590903E+09 | 2840.47 | 16-FEB-19:01 | 1.70 |
March | 0.305823E+09 | 2724.66 | 03-MAR-19:01 | 5.32 |
April | 65170534.34 | 2202.84 | 08-APR-08:61 | 4.60 |
May | 24603016.17 | 2174.19 | 05-MAY-08:62 | 8.07 |
June | 3512210.49 | 935.31 | 20-JUN-08:03 | 21.05 |
July | 248221.22 | 591.19 | 28-JUL-08:03 | 22.57 |
August | 723144.60 | 762.16 | 27-AUG-08:03 | 20.28 |
September | 1538085.45 | 1136.90 | 27-SEP-08:03 | 16.05 |
October | 0.132425E+09 | 2766.49 | 25-OCT-08:61 | 0.22 |
November | 0.362751E+09 | 2749.22 | 10-NOV-19:01 | 6.10 |
December | 0.881075E+09 | 2816.13 | 25-DEC-19:01 | 1.93 |
Annual Sum or Average | 0.324201E+10 | |||
Minimum of Months | 248221.22 | 591.19 | 0.22 | |
Maximum of Months | 0.881075E+09 | 2840.47 | 22.57 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134203E+10 | 2854.79 | 25-JAN-09:01 | 2.67 |
February | 0.911261E+09 | 2838.11 | 16-FEB-19:01 | 1.70 |
March | 0.455235E+09 | 2745.26 | 04-MAR-09:01 | 2.15 |
April | 90097626.23 | 2716.15 | 08-APR-08:61 | 4.60 |
May | 27209879.42 | 2251.54 | 05-MAY-08:62 | 8.07 |
June | 3328692.80 | 991.46 | 20-JUN-08:03 | 21.05 |
July | 282804.58 | 495.81 | 28-JUL-08:03 | 22.57 |
August | 747759.90 | 769.32 | 27-AUG-08:03 | 20.28 |
September | 1716742.86 | 917.07 | 24-SEP-08:03 | 15.28 |
October | 0.216263E+09 | 2783.33 | 26-OCT-08:61 | 1.97 |
November | 0.680723E+09 | 2809.21 | 13-NOV-09:01 | 2.67 |
December | 0.144334E+10 | 2863.51 | 15-DEC-09:01 | -6.5 |
Annual Sum or Average | 0.517223E+10 | |||
Minimum of Months | 282804.58 | 495.81 | -6.5 | |
Maximum of Months | 0.144334E+10 | 2863.51 | 22.57 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160796E+09 | 1441.56 | 17-JAN-09:01 | -2.5 |
February | 0.104968E+09 | 1438.62 | 16-FEB-19:01 | 1.70 |
March | 47829117.10 | 1359.18 | 22-MAR-08:62 | 4.87 |
April | 11412158.17 | 504.80 | 26-APR-08:03 | 13.68 |
May | 5198289.34 | 578.05 | 10-MAY-08:03 | 15.97 |
June | 810022.13 | 504.38 | 11-JUN-08:03 | 18.58 |
July | 878917.72 | 417.43 | 05-JUL-08:04 | 25.87 |
August | 621454.87 | 400.09 | 02-AUG-08:04 | 24.78 |
September | 219791.34 | 308.63 | 02-SEP-08:04 | 20.87 |
October | 24435501.15 | 1410.99 | 25-OCT-08:61 | 0.22 |
November | 43594269.01 | 1386.50 | 10-NOV-19:01 | 6.10 |
December | 0.152592E+09 | 1428.57 | 08-DEC-09:01 | -0.5 |
Annual Sum or Average | 0.553356E+09 | |||
Minimum of Months | 219791.34 | 308.63 | -2.5 | |
Maximum of Months | 0.160796E+09 | 1441.56 | 25.87 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28170783.00 | 4242.50 | 20-JAN-14:35 | 4.47 |
February | 20717630.07 | 3727.35 | 16-FEB-01:15 | 3.87 |
March | 14203307.84 | 4162.71 | 29-MAR-01:43 | 4.82 |
April | 11012826.26 | 4393.84 | 20-APR-05:53 | 4.40 |
May | 225524.01 | 1183.99 | 04-MAY-04:02 | 6.02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 12102915.23 | 3881.43 | 29-OCT-03:18 | 4.07 |
November | 29547875.04 | 4942.15 | 16-NOV-08:54 | 2.20 |
December | 40680388.83 | 5308.83 | 14-DEC-15:44 | 2.30 |
Annual Sum or Average | 0.156661E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.20 | |
Maximum of Months | 40680388.83 | 5308.83 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15395866.75 | 3398.77 | 07-JAN-21:33 | 2.43 |
February | 10074206.65 | 3677.46 | 16-FEB-01:15 | 3.87 |
March | 9478862.75 | 4538.39 | 07-MAR-01:19 | 4.80 |
April | 8180687.81 | 4374.10 | 07-APR-03:59 | 4.40 |
May | 124999.61 | 840.58 | 04-MAY-04:02 | 6.02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 8433077.40 | 4238.06 | 13-OCT-00:49 | 4.18 |
November | 18371903.45 | 4591.82 | 10-NOV-04:59 | 5.00 |
December | 21333998.89 | 4577.26 | 14-DEC-15:44 | 2.30 |
Annual Sum or Average | 91393603.30 | |||
Minimum of Months | 0.00 | 0.00 | 2.30 | |
Maximum of Months | 21333998.89 | 4591.82 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16401.76 | 133.03 | 07-JAN-21:33 | 2.43 |
February | 258414.14 | 2588.62 | 16-FEB-01:15 | 3.87 |
March | 419116.19 | 1031.95 | 07-MAR-01:19 | 4.80 |
April | 327001.07 | 903.75 | 06-APR-00:19 | 4.03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 977423.75 | 2252.00 | 29-OCT-03:18 | 4.07 |
November | 1027186.96 | 1814.32 | 23-NOV-03:15 | 5.20 |
December | 104585.66 | 548.06 | 01-DEC-02:18 | 4.13 |
Annual Sum or Average | 3130129.53 | |||
Minimum of Months | 0.00 | 0.00 | 2.43 | |
Maximum of Months | 1027186.96 | 2588.62 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 56156611.83 | 1194.37 | 11-JAN-03:12 | 3.70 |
February | 22178660.72 | 1160.48 | 28-FEB-23:50 | 2.73 |
March | 17944491.00 | 1134.86 | 03-MAR-04:30 | 4.40 |
April | 11634969.95 | 953.96 | 24-APR-02:20 | 4.60 |
May | 1675820.26 | 702.13 | 04-MAY-04:02 | 6.02 |
June | 54539.20 | 181.80 | 09-JUN-05:00 | 7.80 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 9728521.88 | 1058.30 | 27-OCT-01:06 | 3.80 |
November | 25705523.75 | 1120.53 | 29-NOV-01:35 | 4.60 |
December | 43269721.31 | 1355.68 | 25-DEC-22:49 | 2.15 |
Annual Sum or Average | 0.188349E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.15 | |
Maximum of Months | 56156611.83 | 1355.68 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.147273E+11 | 14185.34 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.132974E+11 | 14185.34 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.147727E+11 | 14185.34 | 01-MAR-20:10 | 0.127855E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.142280E+11 | 14185.34 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.147528E+11 | 14185.34 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.142932E+11 | 14185.34 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.146876E+11 | 14185.34 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.147784E+11 | 14185.34 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.142337E+11 | 14185.34 | 01-SEP-19:10 | 0.123352E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.147216E+11 | 14185.34 | 02-OCT-19:10 | 0.127549E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.142819E+11 | 14185.34 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.146876E+11 | 14185.34 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.173462E+12 | 0.150255E+12 | ||||
Minimum of Months | 0.132974E+11 | 14185.34 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.147784E+11 | 14185.34 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.731324E+09 | 704.41 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.660319E+09 | 704.41 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.733578E+09 | 704.41 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.706528E+09 | 704.41 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.732592E+09 | 704.41 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.709769E+09 | 704.41 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.729351E+09 | 704.41 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.733860E+09 | 704.41 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.706810E+09 | 704.41 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.731042E+09 | 704.41 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.709205E+09 | 704.41 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.729351E+09 | 704.41 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.861373E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.660319E+09 | 704.41 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.733860E+09 | 704.41 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.846876E+09 | 815.72 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.764651E+09 | 815.72 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.849486E+09 | 815.72 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.818162E+09 | 815.72 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.848344E+09 | 815.72 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.821915E+09 | 815.72 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.844592E+09 | 815.72 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.849812E+09 | 815.72 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.818489E+09 | 815.72 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.846549E+09 | 815.72 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.821262E+09 | 815.72 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.844592E+09 | 815.72 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.997473E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.764651E+09 | 815.72 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.849812E+09 | 815.72 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.141236E+10 | 1360.40 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.127524E+10 | 1360.40 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.141672E+10 | 1360.40 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.136448E+10 | 1360.40 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.141481E+10 | 1360.40 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.137074E+10 | 1360.40 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.140855E+10 | 1360.40 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.141726E+10 | 1360.40 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.136502E+10 | 1360.40 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.141182E+10 | 1360.40 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.136965E+10 | 1360.40 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.140855E+10 | 1360.40 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.166352E+11 | 0.124712E+11 | ||||
Minimum of Months | 0.127524E+10 | 1360.40 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.141726E+10 | 1360.40 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.236418E+09 | 227.72 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.213464E+09 | 227.72 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.237147E+09 | 227.72 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.228402E+09 | 227.72 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.236828E+09 | 227.72 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.229450E+09 | 227.72 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.235780E+09 | 227.72 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.237238E+09 | 227.72 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.228493E+09 | 227.72 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.236327E+09 | 227.72 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.229268E+09 | 227.72 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.235780E+09 | 227.72 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.278459E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.213464E+09 | 227.72 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.237238E+09 | 227.72 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.370859E+09 | 357.21 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.334852E+09 | 357.21 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.372002E+09 | 357.21 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.358285E+09 | 357.21 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.371502E+09 | 357.21 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.359929E+09 | 357.21 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.369859E+09 | 357.21 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.372145E+09 | 357.21 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.358428E+09 | 357.21 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.370717E+09 | 357.21 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.359643E+09 | 357.21 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.369859E+09 | 357.21 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.436808E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.334852E+09 | 357.21 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.372145E+09 | 357.21 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.158776E+10 | 1761.91 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.141759E+10 | 1761.91 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.153779E+10 | 1761.91 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.143709E+10 | 1761.91 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.146517E+10 | 1761.91 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.138307E+10 | 1761.91 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.144456E+10 | 1761.91 | 03-JUL-19:19 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.147241E+10 | 1761.91 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.146468E+10 | 1761.91 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.156129E+10 | 1761.91 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.153104E+10 | 1761.91 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.159999E+10 | 1761.91 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.179025E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.138307E+10 | 1761.91 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.159999E+10 | 1761.91 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104091E+11 | 10265.18 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.938257E+10 | 10265.18 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.103889E+11 | 10265.18 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.996007E+10 | 10265.18 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.103049E+11 | 10265.18 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.995274E+10 | 10265.18 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.102456E+11 | 10265.18 | 03-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.103257E+11 | 10265.18 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.999390E+10 | 10265.18 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.103790E+11 | 10265.18 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.100847E+11 | 10265.18 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.103968E+11 | 10265.18 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.121824E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.938257E+10 | 10265.18 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.104091E+11 | 10265.18 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85091918.49 | 76.99 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 76846309.13 | 76.99 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 84415649.14 | 76.99 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 82445007.08 | 76.99 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 84753783.81 | 76.99 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 81790910.76 | 76.99 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 85418966.65 | 76.99 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 84415649.14 | 76.99 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 82467180.11 | 76.99 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 85080831.98 | 76.99 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 82117958.92 | 76.99 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 85430053.17 | 76.99 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.100027E+10 | 0.300992E+10 | ||||
Minimum of Months | 76846309.13 | 76.99 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 85430053.17 | 76.99 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85115186.72 | 77.01 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 76867322.62 | 77.01 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 84438732.44 | 77.01 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 82467551.52 | 77.01 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 84776959.58 | 77.01 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 81813276.33 | 77.01 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 85442324.32 | 77.01 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 84438732.44 | 77.01 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 82489730.61 | 77.01 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 85104097.18 | 77.01 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 82140413.93 | 77.01 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 85453413.86 | 77.01 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.100055E+10 | 0.301074E+10 | ||||
Minimum of Months | 76867322.62 | 77.01 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 85453413.86 | 77.01 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.232638E+10 | 2240.78 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.210051E+10 | 2240.78 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.233355E+10 | 2240.78 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.224750E+10 | 2240.78 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.233041E+10 | 2240.78 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.225781E+10 | 2240.78 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.232011E+10 | 2240.78 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.233445E+10 | 2240.78 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.224840E+10 | 2240.78 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.232548E+10 | 2240.78 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.225602E+10 | 2240.78 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.232011E+10 | 2240.78 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.274007E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.210051E+10 | 2240.78 | 0.00 | 0.00 | |
Maximum of Months | 0.233445E+10 | 2240.78 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85115186.72 | 77.01 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 76867322.62 | 77.01 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 84438732.44 | 77.01 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 82467551.52 | 77.01 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 84776959.58 | 77.01 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 81813276.33 | 77.01 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 85442324.32 | 77.01 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 84438732.44 | 77.01 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 82489730.61 | 77.01 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 85104097.18 | 77.01 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 82140413.93 | 77.01 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 85453413.86 | 77.01 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.100055E+10 | 0.301074E+10 | ||||
Minimum of Months | 76867322.62 | 77.01 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 85453413.86 | 77.01 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.301611E+10 | 3094.06 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.270167E+10 | 3094.06 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.296265E+10 | 3094.06 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.280409E+10 | 3094.06 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.287761E+10 | 3094.06 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.275691E+10 | 3094.06 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.285457E+10 | 3094.06 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.289360E+10 | 3094.06 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.283736E+10 | 3094.06 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.299144E+10 | 3094.06 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.290891E+10 | 3094.06 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.302375E+10 | 3094.06 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.346287E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.270167E+10 | 3094.06 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.302375E+10 | 3094.06 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.301611E+10 | 3094.06 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.270167E+10 | 3094.06 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.296265E+10 | 3094.06 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.280409E+10 | 3094.06 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.287761E+10 | 3094.06 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.275691E+10 | 3094.06 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.285457E+10 | 3094.06 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.289360E+10 | 3094.06 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.283736E+10 | 3094.06 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.299144E+10 | 3094.06 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.290891E+10 | 3094.06 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.302375E+10 | 3094.06 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.346287E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.270167E+10 | 3094.06 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.302375E+10 | 3094.06 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113146E+10 | 1089.83 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.102161E+10 | 1089.83 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.113495E+10 | 1089.83 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.109310E+10 | 1089.83 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.113342E+10 | 1089.83 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.109811E+10 | 1089.83 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.112841E+10 | 1089.83 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.113539E+10 | 1089.83 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.109354E+10 | 1089.83 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.113103E+10 | 1089.83 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.109724E+10 | 1089.83 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.112841E+10 | 1089.83 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.133267E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.102161E+10 | 1089.83 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.113539E+10 | 1089.83 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.246211E+10 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.222306E+10 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.246970E+10 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.237864E+10 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.246638E+10 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.238954E+10 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.245547E+10 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.247065E+10 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.237958E+10 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.246116E+10 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.238765E+10 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.245547E+10 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.289994E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.222306E+10 | 2371.52 | 0.00 | 0.00 | |
Maximum of Months | 0.247065E+10 | 2371.52 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.147273E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.132974E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.147727E+11 | 0.127855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.142280E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.147528E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.142932E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.146876E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.147784E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.142337E+11 | 0.123352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.147216E+11 | 0.127549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.142819E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.146876E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.173462E+12 | 0.150255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.132974E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.147784E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.731324E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558019E+09 |
February | 0.179968E+10 | 0.660319E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463146E+09 |
March | 0.199990E+10 | 0.733578E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386150E+09 |
April | 0.192973E+10 | 0.706528E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1006932.15 | 0.248155E+09 |
May | 0.199475E+10 | 0.732592E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10439045.00 | 0.161811E+09 |
June | 0.193394E+10 | 0.709769E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59267996.09 | 77774370.83 |
July | 0.199054E+10 | 0.729351E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 76703123.44 | 36287879.66 |
August | 0.199896E+10 | 0.733860E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53440399.53 | 52765406.06 |
September | 0.192879E+10 | 0.706810E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19247485.31 | 0.107670E+09 |
October | 0.199148E+10 | 0.731042E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3233772.37 | 0.270011E+09 |
November | 0.192552E+10 | 0.709205E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430209E+09 |
December | 0.199054E+10 | 0.729351E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573705E+09 |
Annual Sum or Average | 0.234744E+11 | 0.861373E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223339E+09 | 0.336570E+10 |
Minimum of Months | 0.179968E+10 | 0.660319E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36287879.66 |
Maximum of Months | 0.199990E+10 | 0.733860E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 76703123.44 | 0.573705E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.846876E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218960E+09 |
February | 0.208403E+10 | 0.764651E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181789E+09 |
March | 0.231589E+10 | 0.849486E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153081E+09 |
April | 0.223463E+10 | 0.818162E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 651128.98 | 97682055.28 |
May | 0.230993E+10 | 0.848344E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4911403.92 | 64703143.86 |
June | 0.223950E+10 | 0.821915E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23905265.05 | 31019965.61 |
July | 0.230505E+10 | 0.844592E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30569077.95 | 14196273.66 |
August | 0.231480E+10 | 0.849812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21344477.00 | 20457157.61 |
September | 0.223354E+10 | 0.818489E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8025693.27 | 42024295.47 |
October | 0.230614E+10 | 0.846549E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1441158.25 | 0.105520E+09 |
November | 0.222975E+10 | 0.821262E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168708E+09 |
December | 0.230505E+10 | 0.844592E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224671E+09 |
Annual Sum or Average | 0.271834E+11 | 0.997473E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90848204.42 | 0.132281E+10 |
Minimum of Months | 0.208403E+10 | 0.764651E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14196273.66 |
Maximum of Months | 0.231589E+10 | 0.849812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30569077.95 | 0.224671E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.141236E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493243E+09 |
February | 0.440737E+09 | 0.127524E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408779E+09 |
March | 0.489771E+09 | 0.141672E+10 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2222.73 | 0.348643E+09 |
April | 0.472586E+09 | 0.136448E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1671764.38 | 0.226895E+09 |
May | 0.488511E+09 | 0.141481E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10305436.83 | 0.154755E+09 |
June | 0.473617E+09 | 0.137074E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54275852.34 | 74981833.34 |
July | 0.487480E+09 | 0.140855E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69970280.56 | 33813024.54 |
August | 0.489542E+09 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48762145.78 | 49005204.96 |
September | 0.472357E+09 | 0.136502E+10 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17822355.60 | 0.100710E+09 |
October | 0.487709E+09 | 0.141182E+10 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3170091.01 | 0.244135E+09 |
November | 0.471555E+09 | 0.136965E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381628E+09 |
December | 0.487480E+09 | 0.140855E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504205E+09 |
Annual Sum or Average | 0.574883E+10 | 0.166352E+11 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205980E+09 | 0.302079E+10 |
Minimum of Months | 0.440737E+09 | 0.127524E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33813024.54 |
Maximum of Months | 0.489771E+09 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69970280.56 | 0.504205E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.236418E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273943E+09 |
February | 0.339028E+09 | 0.213464E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19111.08 | 0.224329E+09 |
March | 0.376747E+09 | 0.237147E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53936.25 | 0.183832E+09 |
April | 0.363528E+09 | 0.228402E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2304632.54 | 0.114506E+09 |
May | 0.375778E+09 | 0.236828E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9672261.27 | 75474572.00 |
June | 0.364321E+09 | 0.229450E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35974846.39 | 36159264.41 |
July | 0.374985E+09 | 0.235780E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45277488.60 | 15645803.78 |
August | 0.376571E+09 | 0.237238E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33018757.76 | 22765315.30 |
September | 0.363352E+09 | 0.228493E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14653839.18 | 47827053.27 |
October | 0.375161E+09 | 0.236327E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3294510.87 | 0.124819E+09 |
November | 0.362735E+09 | 0.229268E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203738E+09 |
December | 0.374985E+09 | 0.235780E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281165E+09 |
Annual Sum or Average | 0.442217E+10 | 0.278459E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144269E+09 | 0.160420E+10 |
Minimum of Months | 0.339028E+09 | 0.213464E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15645803.78 |
Maximum of Months | 0.376747E+09 | 0.237238E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45277488.60 | 0.281165E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.370859E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753899E+09 |
February | 0.139600E+10 | 0.334852E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623182E+09 |
March | 0.155131E+10 | 0.372002E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523914E+09 |
April | 0.149688E+10 | 0.358285E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 1253653.49 | 0.332312E+09 |
May | 0.154732E+10 | 0.371502E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 12889225.96 | 0.220024E+09 |
June | 0.150015E+10 | 0.359929E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 73798971.83 | 0.103506E+09 |
July | 0.154405E+10 | 0.369859E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 95517298.04 | 46173284.35 |
August | 0.155059E+10 | 0.372145E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 66540861.80 | 66975553.14 |
September | 0.149615E+10 | 0.358428E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 23977802.82 | 0.138383E+09 |
October | 0.154478E+10 | 0.370717E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 4033986.45 | 0.355048E+09 |
November | 0.149361E+10 | 0.359643E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572958E+09 |
December | 0.154405E+10 | 0.369859E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771471E+09 |
Annual Sum or Average | 0.182090E+11 | 0.436808E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.278012E+09 | 0.450784E+10 |
Minimum of Months | 0.139600E+10 | 0.334852E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46173284.35 |
Maximum of Months | 0.155131E+10 | 0.372145E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 95517298.04 | 0.771471E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.158776E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125653E+10 |
February | 0.236489E+11 | 0.141759E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104230E+10 |
March | 0.262800E+11 | 0.153779E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.863260E+09 |
April | 0.253579E+11 | 0.143709E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3319988.80 | 0.540218E+09 |
May | 0.262123E+11 | 0.146517E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31984354.31 | 0.342082E+09 |
June | 0.254132E+11 | 0.138307E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148208E+09 | 0.160573E+09 |
July | 0.261570E+11 | 0.144456E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184793E+09 | 73523953.09 |
August | 0.262677E+11 | 0.147241E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124503E+09 | 0.107981E+09 |
September | 0.253456E+11 | 0.146468E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43820572.67 | 0.228989E+09 |
October | 0.261693E+11 | 0.156129E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7542953.35 | 0.598179E+09 |
November | 0.253025E+11 | 0.153104E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.964556E+09 |
December | 0.261570E+11 | 0.159999E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129410E+10 |
Annual Sum or Average | 0.308468E+12 | 0.179025E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544172E+09 | 0.747229E+10 |
Minimum of Months | 0.236489E+11 | 0.138307E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73523953.09 |
Maximum of Months | 0.262800E+11 | 0.159999E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184793E+09 | 0.129410E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.104091E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368239E+10 |
February | 0.702046E+11 | 0.938257E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305457E+10 |
March | 0.780153E+11 | 0.103889E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256518E+10 |
April | 0.752779E+11 | 0.996007E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9736422.42 | 0.161991E+10 |
May | 0.778146E+11 | 0.103049E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82029938.67 | 0.106727E+10 |
June | 0.754422E+11 | 0.995274E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398927E+09 | 0.507597E+09 |
July | 0.776503E+11 | 0.102456E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507208E+09 | 0.231299E+09 |
August | 0.779788E+11 | 0.103257E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350088E+09 | 0.332414E+09 |
September | 0.752414E+11 | 0.999390E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125972E+09 | 0.689092E+09 |
October | 0.776868E+11 | 0.103790E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21377524.65 | 0.176174E+10 |
November | 0.751137E+11 | 0.100847E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283186E+10 |
December | 0.776503E+11 | 0.103968E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378472E+10 |
Annual Sum or Average | 0.915726E+12 | 0.121824E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149534E+10 | 0.221280E+11 |
Minimum of Months | 0.702046E+11 | 0.938257E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231299E+09 |
Maximum of Months | 0.780153E+11 | 0.104091E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507208E+09 | 0.378472E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306977E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9201.39 | 0.252082E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30593.30 | 0.204474E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2597817.92 | 0.121413E+09 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11830356.40 | 72915752.09 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48278104.01 | 29044097.75 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63155785.10 | 6629797.59 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46458306.32 | 12847480.78 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18346057.82 | 38236449.97 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3764411.16 | 0.130371E+09 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227650E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315213E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194471E+09 | 0.171785E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6629797.59 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63155785.10 | 0.315213E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300433E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9355.71 | 0.246873E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30809.92 | 0.201254E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2601392.25 | 0.120123E+09 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11848987.85 | 72566860.01 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48264145.85 | 29037434.43 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63162814.24 | 6644018.65 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46545717.56 | 12813233.47 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18487835.24 | 37927369.46 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3812352.99 | 0.127784E+09 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222701E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307468E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194763E+09 | 0.168563E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6644018.65 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63162814.24 | 0.307468E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 85091918.49 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90716053.35 |
February | 0.00 | 76846309.13 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75649982.95 |
March | 0.00 | 84415649.14 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63115478.16 |
April | 0.00 | 82445007.08 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 320249.77 | 39682744.70 |
May | 0.00 | 84753783.81 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2188467.89 | 25665258.98 |
June | 0.00 | 81790910.76 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10732765.59 | 11806994.63 |
July | 0.00 | 85418966.65 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13876711.16 | 4814495.33 |
August | 0.00 | 84415649.14 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9895164.06 | 7284997.92 |
September | 0.00 | 82467180.11 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3825171.50 | 16053700.78 |
October | 0.00 | 85080831.98 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 713616.30 | 42741277.47 |
November | 0.00 | 82117958.92 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69824293.96 |
December | 0.00 | 85430053.17 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93790610.01 |
Annual Sum or Average | 0.00 | 0.100027E+10 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41552146.27 | 0.541146E+09 |
Minimum of Months | 0.00 | 76846309.13 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4814495.33 |
Maximum of Months | 0.00 | 85430053.17 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13876711.16 | 93790610.01 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 85115186.72 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83877422.30 |
February | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13361.94 | 68631324.74 |
March | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25472.96 | 55576254.40 |
April | 0.293479E+09 | 82467551.52 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 888431.04 | 32792717.40 |
May | 0.303504E+09 | 84776959.58 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3670735.25 | 19837207.93 |
June | 0.293842E+09 | 81813276.33 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13758404.48 | 7950048.02 |
July | 0.303141E+09 | 85442324.32 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17922159.08 | 1812851.20 |
August | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13387081.10 | 3469365.33 |
September | 0.293479E+09 | 82489730.61 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5759624.12 | 10363101.53 |
October | 0.303322E+09 | 85104097.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1348983.39 | 35070144.85 |
November | 0.293661E+09 | 82140413.93 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61518853.12 |
December | 0.303141E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85899126.93 |
Annual Sum or Average | 0.357224E+10 | 0.100055E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56774253.36 | 0.466798E+09 |
Minimum of Months | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1812851.20 |
Maximum of Months | 0.303685E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17922159.08 | 85899126.93 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307800E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9345.92 | 0.252888E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30780.77 | 0.205903E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2618895.61 | 0.122744E+09 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11819309.62 | 74082392.66 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48144134.56 | 29472316.90 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63036538.50 | 6786675.07 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46421323.50 | 13163250.40 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18359811.14 | 38746814.77 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3789547.71 | 0.131219E+09 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228539E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316154E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194230E+09 | 0.172750E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6786675.07 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63036538.50 | 0.316154E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300456E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9938.61 | 0.247073E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30994.93 | 0.203878E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2634196.01 | 0.122503E+09 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11824884.89 | 74027976.33 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48132252.63 | 29466683.25 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63032306.07 | 6786199.71 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46438337.72 | 13153487.86 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18427245.31 | 38672057.64 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3821965.41 | 0.129817E+09 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222833E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306940E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194352E+09 | 0.169561E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6786199.71 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63032306.07 | 0.306940E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.232638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384569E+09 |
February | 0.348285E+10 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318781E+09 |
March | 0.387034E+10 | 0.233355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271161E+09 |
April | 0.373454E+10 | 0.224750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 903362.95 | 0.177002E+09 |
May | 0.386038E+10 | 0.233041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7632236.61 | 0.119113E+09 |
June | 0.374269E+10 | 0.225781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41489615.06 | 57499535.94 |
July | 0.385223E+10 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53454619.11 | 26295008.52 |
August | 0.386853E+10 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37176133.82 | 37936436.42 |
September | 0.373273E+10 | 0.224840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13321669.79 | 77595309.82 |
October | 0.385404E+10 | 0.232548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2226568.58 | 0.192118E+09 |
November | 0.372639E+10 | 0.225602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299627E+09 |
December | 0.385223E+10 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392316E+09 |
Annual Sum or Average | 0.454292E+11 | 0.274007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156204E+09 | 0.235401E+10 |
Minimum of Months | 0.348285E+10 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26295008.52 |
Maximum of Months | 0.387034E+10 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53454619.11 | 0.392316E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306445E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7848.68 | 0.251809E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28473.35 | 0.204295E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2514875.53 | 0.121690E+09 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11600882.24 | 73160775.11 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47788703.76 | 29286548.07 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62483091.82 | 6812446.59 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45869495.06 | 13067496.36 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18027025.57 | 38535854.31 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3670542.61 | 0.130467E+09 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227370E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314683E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191991E+09 | 0.171762E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6812446.59 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62483091.82 | 0.314683E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299331E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8028.03 | 0.246154E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28710.66 | 0.200657E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2518247.21 | 0.120331E+09 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11616060.77 | 72815542.83 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47766033.37 | 29277357.71 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62483007.35 | 6828612.22 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45959964.28 | 13029853.99 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18169888.77 | 38220446.78 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3731220.90 | 0.127493E+09 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221413E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306488E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192281E+09 | 0.168204E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6828612.22 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62483007.35 | 0.306488E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 85115186.72 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159401E+09 |
February | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3136.65 | 0.130691E+09 |
March | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14256.95 | 0.105688E+09 |
April | 0.293479E+09 | 82467551.52 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1296566.02 | 62565888.78 |
May | 0.303504E+09 | 84776959.58 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5962726.56 | 37502302.40 |
June | 0.293842E+09 | 81813276.33 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24520238.14 | 14968702.43 |
July | 0.303141E+09 | 85442324.32 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32043877.51 | 3481254.08 |
August | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23491176.49 | 6674091.96 |
September | 0.293479E+09 | 82489730.61 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9168442.02 | 19814456.10 |
October | 0.303322E+09 | 85104097.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1821903.15 | 67489902.64 |
November | 0.293661E+09 | 82140413.93 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117915E+09 |
December | 0.303141E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163634E+09 |
Annual Sum or Average | 0.357224E+10 | 0.100055E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98322323.47 | 0.889826E+09 |
Minimum of Months | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3481254.08 |
Maximum of Months | 0.303685E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32043877.51 | 0.163634E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.301611E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.804744E+09 |
February | 0.415303E+11 | 0.270167E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3100.72 | 0.667196E+09 |
March | 0.461508E+11 | 0.296265E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16940.75 | 0.564322E+09 |
April | 0.445315E+11 | 0.280409E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2719209.23 | 0.359282E+09 |
May | 0.460320E+11 | 0.287761E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18506605.94 | 0.239960E+09 |
June | 0.446286E+11 | 0.275691E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89327170.89 | 0.115066E+09 |
July | 0.459349E+11 | 0.285457E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115526E+09 | 52815182.73 |
August | 0.461292E+11 | 0.289360E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82856239.97 | 74701374.89 |
September | 0.445099E+11 | 0.283736E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35541238.24 | 0.152215E+09 |
October | 0.459565E+11 | 0.299144E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7930574.19 | 0.380525E+09 |
November | 0.444343E+11 | 0.290891E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612305E+09 |
December | 0.459349E+11 | 0.302375E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823639E+09 |
Annual Sum or Average | 0.541708E+12 | 0.346287E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352428E+09 | 0.484677E+10 |
Minimum of Months | 0.415303E+11 | 0.270167E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52815182.73 |
Maximum of Months | 0.461508E+11 | 0.302375E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115526E+09 | 0.823639E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.301611E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820334E+09 |
February | 0.415303E+11 | 0.270167E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680371E+09 |
March | 0.461508E+11 | 0.296265E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4341.25 | 0.576449E+09 |
April | 0.445315E+11 | 0.280409E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1951603.87 | 0.366721E+09 |
May | 0.460320E+11 | 0.287761E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16331538.41 | 0.244745E+09 |
June | 0.446286E+11 | 0.275691E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86171749.14 | 0.116927E+09 |
July | 0.459349E+11 | 0.285457E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111534E+09 | 53663994.65 |
August | 0.461292E+11 | 0.289360E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79035307.34 | 76096967.01 |
September | 0.445099E+11 | 0.283736E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32550066.48 | 0.154947E+09 |
October | 0.459565E+11 | 0.299144E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6971166.19 | 0.388021E+09 |
November | 0.444343E+11 | 0.290891E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624217E+09 |
December | 0.459349E+11 | 0.302375E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839465E+09 |
Annual Sum or Average | 0.541708E+12 | 0.346287E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334550E+09 | 0.494196E+10 |
Minimum of Months | 0.415303E+11 | 0.270167E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53663994.65 |
Maximum of Months | 0.461508E+11 | 0.302375E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111534E+09 | 0.839465E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113146E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774957E+09 |
February | 0.369574E+10 | 0.102161E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641133E+09 |
March | 0.410691E+10 | 0.113495E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539679E+09 |
April | 0.396281E+10 | 0.109310E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 1132144.84 | 0.343142E+09 |
May | 0.409635E+10 | 0.113342E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 12597703.93 | 0.227331E+09 |
June | 0.397146E+10 | 0.109811E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 73917488.44 | 0.107312E+09 |
July | 0.408770E+10 | 0.112841E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 95666193.79 | 48522049.54 |
August | 0.410499E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 66417045.75 | 69989756.29 |
September | 0.396089E+10 | 0.109354E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 23675721.28 | 0.143306E+09 |
October | 0.408962E+10 | 0.113103E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3927180.39 | 0.366327E+09 |
November | 0.395417E+10 | 0.109724E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590097E+09 |
December | 0.408770E+10 | 0.112841E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794032E+09 |
Annual Sum or Average | 0.482060E+11 | 0.133267E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.277333E+09 | 0.464583E+10 |
Minimum of Months | 0.369574E+10 | 0.102161E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48522049.54 |
Maximum of Months | 0.410691E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 95666193.79 | 0.794032E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.246211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674371E+09 |
February | 0.368610E+10 | 0.222306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562247E+09 |
March | 0.409620E+10 | 0.246970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482486E+09 |
April | 0.395248E+10 | 0.237864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1091607.91 | 0.318191E+09 |
May | 0.408566E+10 | 0.246638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12275408.47 | 0.213906E+09 |
June | 0.396110E+10 | 0.238954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72237293.67 | 0.103653E+09 |
July | 0.407704E+10 | 0.245547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93509850.26 | 47504042.68 |
August | 0.409429E+10 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64903128.74 | 68416468.87 |
September | 0.395056E+10 | 0.237958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23078476.32 | 0.138636E+09 |
October | 0.407896E+10 | 0.246116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3817720.06 | 0.338906E+09 |
November | 0.394385E+10 | 0.238765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526430E+09 |
December | 0.407704E+10 | 0.245547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688991E+09 |
Annual Sum or Average | 0.480803E+11 | 0.289994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270913E+09 | 0.416374E+10 |
Minimum of Months | 0.368610E+10 | 0.222306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47504042.68 |
Maximum of Months | 0.409620E+10 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93509850.26 | 0.688991E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 14185.34 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 14185.34 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 14185.34 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 14185.34 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 14185.34 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 14185.34 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 14185.34 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 14185.34 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 14185.34 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 14185.34 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 14185.34 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 14185.34 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 14185.34 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 14185.34 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 704.41 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 320.67 | 21-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 704.41 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 299.53 | 04-FEB-06:40 |
March | 1169.53 | 01-MAR-00:10 | 704.41 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 268.36 | 05-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 704.41 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.10 | 13-APR-17:00 | 204.55 | 06-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 704.41 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.92 | 22-MAY-13:00 | 177.91 | 07-MAY-05:00 |
June | 1169.53 | 01-JUN-00:10 | 704.41 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.70 | 28-JUN-16:00 | 147.10 | 09-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 704.41 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.05 | 22-JUL-15:00 | 73.46 | 08-JUL-03:00 |
August | 1169.53 | 01-AUG-00:10 | 704.41 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.15 | 20-AUG-15:00 | 107.48 | 31-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 704.41 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.68 | 03-SEP-14:00 | 129.08 | 20-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 704.41 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.80 | 01-OCT-16:00 | 255.01 | 27-OCT-07:00 |
November | 1169.53 | 01-NOV-00:10 | 704.41 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 278.71 | 28-NOV-08:00 |
December | 1169.53 | 01-DEC-00:10 | 704.41 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 334.74 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 704.41 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.46 | |||||
Maximum of Months | 1169.53 | 704.41 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 137.70 | 334.74 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 815.72 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 127.32 | 26-JAN-04:00 |
February | 1354.32 | 01-FEB-00:10 | 815.72 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 121.10 | 05-FEB-08:00 |
March | 1354.32 | 01-MAR-00:10 | 815.72 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 109.66 | 05-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 815.72 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 13-APR-17:00 | 86.68 | 08-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 815.72 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.03 | 22-MAY-13:00 | 75.24 | 07-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 815.72 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.15 | 28-JUN-16:00 | 63.09 | 09-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 815.72 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.97 | 22-JUL-15:00 | 30.44 | 08-JUL-03:00 |
August | 1354.32 | 01-AUG-00:10 | 815.72 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.98 | 20-AUG-16:00 | 43.63 | 31-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 815.72 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.36 | 03-SEP-14:00 | 52.64 | 20-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 815.72 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.86 | 01-OCT-16:00 | 104.82 | 27-OCT-07:00 |
November | 1354.32 | 01-NOV-00:10 | 815.72 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 112.22 | 27-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 815.72 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 134.86 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 815.72 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.44 | |||||
Maximum of Months | 1354.32 | 815.72 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 53.15 | 134.86 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 1360.40 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 292.51 | 21-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 1360.40 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 275.37 | 04-FEB-06:40 |
March | 286.42 | 01-MAR-00:10 | 1360.40 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 | 08-MAR-14:00 | 251.98 | 05-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 1360.40 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.61 | 13-APR-17:00 | 200.29 | 06-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 1360.40 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.94 | 22-MAY-13:00 | 174.32 | 07-MAY-05:00 |
June | 286.42 | 01-JUN-00:10 | 1360.40 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.62 | 28-JUN-16:00 | 148.46 | 09-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 1360.40 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.46 | 22-JUL-15:00 | 71.98 | 08-JUL-04:00 |
August | 286.42 | 01-AUG-00:10 | 1360.40 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.09 | 20-AUG-15:00 | 103.13 | 31-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 1360.40 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.49 | 03-SEP-14:00 | 124.35 | 20-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 1360.40 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.69 | 01-OCT-16:00 | 243.30 | 27-OCT-07:00 |
November | 286.42 | 01-NOV-00:10 | 1360.40 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 257.12 | 27-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 1360.40 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 305.94 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.98 | |||||
Maximum of Months | 286.42 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 125.62 | 305.94 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 227.72 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 168.77 | 21-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 227.72 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 | 14-FEB-16:00 | 157.64 | 04-FEB-06:50 |
March | 220.32 | 01-MAR-00:10 | 227.72 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.61 | 08-MAR-14:00 | 141.25 | 05-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 227.72 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 | 13-APR-17:00 | 108.77 | 08-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 227.72 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 | 22-MAY-13:00 | 93.99 | 07-MAY-05:00 |
June | 220.32 | 01-JUN-00:10 | 227.72 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 28-JUN-16:00 | 79.50 | 09-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 227.72 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.40 | 22-JUL-15:00 | 37.18 | 08-JUL-03:00 |
August | 220.32 | 01-AUG-00:10 | 227.72 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.78 | 01-AUG-15:50 | 53.76 | 31-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 227.72 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.96 | 03-SEP-14:00 | 64.51 | 20-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 227.72 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.24 | 01-OCT-16:00 | 134.01 | 26-OCT-07:00 |
November | 220.32 | 01-NOV-00:10 | 227.72 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 143.66 | 27-NOV-07:00 |
December | 220.32 | 01-DEC-00:10 | 227.72 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 176.19 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 227.72 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.18 | |||||
Maximum of Months | 220.32 | 227.72 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 176.19 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 357.21 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 440.28 | 21-JAN-07:00 |
February | 907.20 | 01-FEB-00:10 | 357.21 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 413.43 | 04-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 357.21 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 374.56 | 05-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 357.21 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 25.03 | 13-APR-17:00 | 325.79 | 07-APR-05:55 |
May | 907.20 | 01-MAY-00:10 | 357.21 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 71.51 | 22-MAY-13:00 | 285.03 | 07-MAY-05:35 |
June | 907.20 | 01-JUN-00:10 | 357.21 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 171.53 | 28-JUN-16:00 | 230.40 | 09-JUN-05:00 |
July | 907.20 | 01-JUL-00:10 | 357.21 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 164.50 | 22-JUL-15:00 | 98.27 | 08-JUL-03:40 |
August | 907.20 | 01-AUG-00:10 | 357.21 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 128.50 | 20-AUG-15:00 | 140.82 | 31-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 357.21 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 103.09 | 03-SEP-14:00 | 171.06 | 09-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 357.21 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 58.29 | 01-OCT-16:00 | 357.10 | 26-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 357.21 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 385.37 | 27-NOV-21:53 |
December | 907.20 | 01-DEC-00:10 | 357.21 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 452.20 | 15-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 98.27 | ||||||
Maximum of Months | 907.20 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 171.53 | 452.20 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1761.91 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 722.40 | 26-JAN-04:00 |
February | 15368.40 | 01-FEB-00:10 | 1761.91 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 687.12 | 04-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 1761.91 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 613.14 | 06-MAR-06:00 |
April | 15368.40 | 01-APR-00:10 | 1761.91 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.92 | 29-APR-16:00 | 483.15 | 16-APR-05:05 |
May | 15368.40 | 01-MAY-00:10 | 1761.91 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.84 | 22-MAY-13:00 | 426.43 | 07-MAY-05:35 |
June | 15368.40 | 01-JUN-00:10 | 1761.91 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 304.96 | 28-JUN-16:00 | 364.60 | 09-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1761.91 | 03-JUL-19:19 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 291.93 | 22-JUL-15:00 | 169.83 | 08-JUL-03:00 |
August | 15368.40 | 01-AUG-00:10 | 1761.91 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.03 | 20-AUG-15:00 | 234.89 | 31-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 1761.91 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.95 | 03-SEP-14:00 | 292.53 | 25-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 1761.91 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.47 | 01-OCT-16:00 | 582.28 | 26-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1761.91 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 635.90 | 27-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1761.91 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 767.81 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1761.91 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.83 | |||||
Maximum of Months | 15368.40 | 1761.91 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 304.96 | 767.81 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 10265.18 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2133.70 | 20-JAN-02:00 |
February | 45622.98 | 01-FEB-00:10 | 10265.18 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2037.97 | 04-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 10265.18 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1832.19 | 05-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 10265.18 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.88 | 13-APR-17:00 | 1444.49 | 08-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 10265.18 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 424.53 | 22-MAY-13:00 | 1254.04 | 07-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 10265.18 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 870.47 | 28-JUN-16:00 | 1078.90 | 09-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 10265.18 | 03-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 835.07 | 22-JUL-15:00 | 498.18 | 08-JUL-03:50 |
August | 45622.98 | 01-AUG-00:10 | 10265.18 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 660.68 | 20-AUG-16:00 | 713.92 | 31-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 10265.18 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 522.72 | 03-SEP-14:00 | 861.63 | 25-SEP-05:00 |
October | 45622.98 | 01-OCT-23:10 | 10265.18 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 301.31 | 01-OCT-16:00 | 1753.41 | 26-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 10265.18 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1891.56 | 27-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 10265.18 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2267.32 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 10265.18 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.18 | |||||
Maximum of Months | 45622.98 | 10265.18 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 870.47 | 2267.32 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 187.08 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 14-FEB-16:10 | 174.80 | 04-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 08-MAR-16:09 | 156.72 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 13-APR-17:00 | 119.24 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.74 | 19-MAY-15:10 | 100.83 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 28-JUN-16:00 | 79.75 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.42 | 21-JUL-17:00 | 32.18 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.17 | 01-AUG-16:00 | 48.95 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.06 | 02-SEP-15:10 | 62.68 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.94 | 01-OCT-16:00 | 148.72 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 159.38 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 195.27 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.18 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 195.27 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 187.07 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 14-FEB-16:10 | 174.79 | 04-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 08-MAR-16:10 | 156.71 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.49 | 13-APR-17:00 | 119.23 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.74 | 19-MAY-15:10 | 100.83 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 28-JUN-16:00 | 79.75 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.41 | 21-JUL-17:00 | 32.18 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.25 | 01-AUG-15:10 | 48.94 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.10 | 02-SEP-15:10 | 62.68 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.94 | 01-OCT-16:00 | 148.71 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 159.36 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 195.26 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.18 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 195.26 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 76.99 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 51.89 | 26-JAN-04:00 |
February | 0.00 | 01-FEB-00:10 | 76.99 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 49.42 | 05-FEB-08:10 |
March | 0.00 | 01-MAR-00:10 | 76.99 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 44.09 | 05-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 76.99 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 | 13-APR-17:00 | 34.56 | 06-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 76.99 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.26 | 22-MAY-13:00 | 29.27 | 07-MAY-05:00 |
June | 0.00 | 01-JUN-00:10 | 76.99 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.23 | 28-JUN-16:00 | 24.10 | 09-JUN-04:03 |
July | 0.00 | 01-JUL-00:10 | 76.99 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.32 | 22-JUL-15:00 | 11.70 | 08-JUL-03:00 |
August | 0.00 | 01-AUG-00:10 | 76.99 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.65 | 20-AUG-15:00 | 17.29 | 31-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 76.99 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 | 03-SEP-14:00 | 21.06 | 20-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 76.99 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 | 01-OCT-16:00 | 43.70 | 27-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 76.99 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 45.76 | 27-NOV-07:10 |
December | 0.00 | 01-DEC-00:10 | 76.99 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 54.75 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 76.99 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.70 | |||||
Maximum of Months | 0.00 | 76.99 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 23.23 | 54.75 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 77.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 52.21 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 77.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 | 14-FEB-16:00 | 48.79 | 04-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 77.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 | 08-MAR-16:04 | 43.74 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 77.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 13-APR-17:00 | 33.28 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 77.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.60 | 19-MAY-15:20 | 28.14 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 77.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.57 | 28-JUN-16:00 | 22.26 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 77.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.27 | 22-JUL-15:10 | 8.18 | 08-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 77.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.03 | 20-AUG-15:10 | 13.66 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 77.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.94 | 02-SEP-15:08 | 17.49 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 77.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.99 | 01-OCT-16:00 | 41.51 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 77.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 44.48 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 77.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 54.50 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.18 | |||||
Maximum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 26.57 | 54.50 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 187.08 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 14-FEB-16:07 | 174.80 | 04-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 08-MAR-16:10 | 156.72 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 13-APR-17:00 | 124.90 | 08-APR-07:20 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.74 | 19-MAY-15:20 | 100.83 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 28-JUN-16:00 | 79.76 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.54 | 22-JUL-15:10 | 32.19 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.34 | 20-AUG-15:10 | 48.95 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.10 | 02-SEP-15:10 | 62.68 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 | 01-OCT-16:00 | 148.72 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 159.38 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 195.27 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.19 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 195.27 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 187.06 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 14-FEB-16:07 | 174.79 | 04-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 08-MAR-16:09 | 156.71 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 13-APR-17:00 | 123.93 | 08-APR-07:20 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.74 | 19-MAY-15:20 | 100.83 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.18 | 28-JUN-16:00 | 79.75 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.54 | 22-JUL-15:10 | 32.19 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.34 | 20-AUG-15:10 | 48.94 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.10 | 02-SEP-15:10 | 62.68 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 | 01-OCT-16:00 | 148.71 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 159.36 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 195.26 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.19 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 95.18 | 195.26 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 2240.78 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 225.37 | 21-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 2240.78 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 213.54 | 04-FEB-06:00 |
March | 2263.36 | 01-MAR-00:10 | 2240.78 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 194.56 | 05-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 2240.78 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.36 | 13-APR-17:00 | 155.47 | 08-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 2240.78 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.91 | 22-MAY-13:00 | 134.78 | 07-MAY-05:00 |
June | 2263.36 | 01-JUN-00:10 | 2240.78 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.37 | 28-JUN-16:00 | 113.85 | 09-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 2240.78 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.40 | 22-JUL-15:00 | 55.47 | 08-JUL-03:00 |
August | 2263.36 | 01-AUG-00:10 | 2240.78 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.11 | 20-AUG-15:00 | 78.81 | 31-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 2240.78 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.80 | 03-SEP-14:00 | 94.59 | 20-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 2240.78 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.56 | 01-OCT-16:00 | 187.23 | 27-OCT-07:00 |
November | 2263.36 | 01-NOV-00:10 | 2240.78 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 201.08 | 27-NOV-06:00 |
December | 2263.36 | 01-DEC-00:10 | 2240.78 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 238.95 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.47 | ||||
Maximum of Months | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.37 | 238.95 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 187.50 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 14-FEB-16:10 | 175.22 | 04-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.30 | 08-MAR-16:09 | 157.13 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 13-APR-17:00 | 119.63 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.43 | 19-MAY-15:10 | 101.21 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.88 | 28-JUN-16:00 | 80.12 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.11 | 21-JUL-17:00 | 30.88 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.19 | 01-AUG-16:00 | 49.30 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.02 | 02-SEP-15:10 | 63.04 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.59 | 01-OCT-16:00 | 149.12 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 159.78 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 195.70 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.88 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 94.88 | 195.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 187.49 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 14-FEB-16:10 | 175.20 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.30 | 08-MAR-16:10 | 157.12 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 13-APR-17:00 | 119.62 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.42 | 19-MAY-15:10 | 101.20 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.88 | 28-JUN-16:00 | 80.12 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.11 | 21-JUL-17:00 | 31.18 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.77 | 01-AUG-16:00 | 49.30 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.78 | 02-SEP-15:10 | 63.04 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.62 | 01-OCT-16:00 | 149.11 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 159.77 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 195.68 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.18 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 94.88 | 195.68 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 77.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 95.93 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 77.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 | 14-FEB-16:10 | 89.65 | 04-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 77.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 | 08-MAR-16:09 | 80.39 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 77.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 | 13-APR-17:00 | 61.21 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 77.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.78 | 19-MAY-15:08 | 51.78 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 77.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.55 | 28-JUN-16:00 | 40.99 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 77.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.15 | 22-JUL-15:10 | 15.32 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 77.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.35 | 01-AUG-15:10 | 25.23 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 77.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.36 | 02-SEP-15:10 | 32.26 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 77.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 | 01-OCT-16:00 | 76.30 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 77.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 81.75 | 27-NOV-06:50 |
December | 180.00 | 01-DEC-00:10 | 77.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 100.12 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 | |||||
Maximum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 48.55 | 100.12 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3094.06 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 482.00 | 21-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 3094.06 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.02 | 14-FEB-15:00 | 455.22 | 04-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 3094.06 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.72 | 08-MAR-14:00 | 410.64 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3094.06 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.34 | 29-APR-16:00 | 334.66 | 16-APR-05:05 |
May | 26988.77 | 01-MAY-00:10 | 3094.06 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.30 | 22-MAY-13:00 | 301.04 | 07-MAY-05:35 |
June | 26988.77 | 01-JUN-00:10 | 3094.06 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.90 | 28-JUN-16:00 | 254.19 | 09-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3094.06 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.70 | 22-JUL-15:00 | 113.20 | 08-JUL-03:30 |
August | 26988.77 | 01-AUG-00:10 | 3094.06 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.69 | 20-AUG-16:00 | 161.65 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 3094.06 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.70 | 03-SEP-14:00 | 194.80 | 25-SEP-05:00 |
October | 26988.77 | 01-OCT-23:10 | 3094.06 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.32 | 01-OCT-16:00 | 394.97 | 26-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 3094.06 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 419.65 | 27-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 3094.06 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 503.57 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.20 | |||||
Maximum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 193.90 | 503.57 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3094.06 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 488.56 | 21-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 3094.06 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 460.68 | 04-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 3094.06 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.79 | 08-MAR-14:00 | 416.46 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3094.06 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.56 | 29-APR-16:00 | 337.11 | 16-APR-05:05 |
May | 26988.77 | 01-MAY-00:10 | 3094.06 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.08 | 22-MAY-13:00 | 301.16 | 07-MAY-05:35 |
June | 26988.77 | 01-JUN-00:10 | 3094.06 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.90 | 28-JUN-16:00 | 254.41 | 09-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3094.06 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.87 | 22-JUL-15:00 | 113.20 | 08-JUL-03:30 |
August | 26988.77 | 01-AUG-00:10 | 3094.06 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.25 | 20-AUG-16:00 | 161.65 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 3094.06 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.59 | 03-SEP-14:00 | 195.79 | 09-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 3094.06 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.15 | 01-OCT-16:00 | 400.06 | 26-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 3094.06 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 424.49 | 27-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 3094.06 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 508.84 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.20 | |||||
Maximum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 193.90 | 508.84 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1089.83 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 449.85 | 21-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 1089.83 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 422.57 | 04-FEB-06:05 |
March | 2401.70 | 01-MAR-00:10 | 1089.83 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 382.86 | 05-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1089.83 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 24.46 | 13-APR-17:00 | 342.49 | 07-APR-05:55 |
May | 2401.70 | 01-MAY-00:10 | 1089.83 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 71.74 | 22-MAY-13:00 | 300.33 | 07-MAY-05:35 |
June | 2401.70 | 01-JUN-00:10 | 1089.83 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 173.75 | 28-JUN-16:00 | 244.35 | 09-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1089.83 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 166.53 | 22-JUL-15:00 | 101.36 | 08-JUL-03:00 |
August | 2401.70 | 01-AUG-00:10 | 1089.83 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 129.84 | 20-AUG-15:00 | 144.66 | 31-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1089.83 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 103.94 | 03-SEP-14:00 | 175.45 | 09-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1089.83 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 58.35 | 01-OCT-16:00 | 365.04 | 26-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 1089.83 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 388.57 | 27-NOV-06:00 |
December | 2401.70 | 01-DEC-00:10 | 1089.83 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 468.08 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1089.83 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 101.36 | ||||||
Maximum of Months | 2401.70 | 1089.83 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 173.75 | 468.08 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 399.66 | 21-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 373.40 | 04-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 335.04 | 05-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.75 | 13-APR-17:00 | 269.24 | 08-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.07 | 22-MAY-13:00 | 233.47 | 07-MAY-05:00 |
June | 2395.44 | 01-JUN-00:10 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.85 | 28-JUN-16:00 | 198.99 | 09-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.83 | 22-JUL-15:00 | 98.97 | 08-JUL-03:00 |
August | 2395.44 | 01-AUG-00:10 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.92 | 20-AUG-15:00 | 139.14 | 31-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.59 | 03-SEP-14:00 | 165.73 | 20-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.91 | 01-OCT-16:00 | 322.42 | 27-OCT-07:00 |
November | 2395.44 | 01-NOV-00:10 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 342.39 | 27-NOV-06:00 |
December | 2395.44 | 01-DEC-00:10 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 417.18 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.97 | ||||
Maximum of Months | 2395.44 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.85 | 417.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 37258.42 | 28-JAN-21:21 | 62621.41 | 77231.46 | 59618.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 36875.47 | 24-FEB-20:17 | 26837.75 | 42556.03 | 30341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 36384.95 | 03-MAR-21:50 | 30671.71 | 37827.89 | 28744.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34126.58 | 23-APR-04:47 | 62621.41 | 22065.95 | 22356.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28452.34 | 07-MAY-05:41 | 71567.33 | 37828.07 | 34067.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19359.10 | 08-JUN-21:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20927.99 | 27-JUL-21:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22320.57 | 23-AUG-21:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23796.27 | 15-SEP-21:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 41251.01 | 29-OCT-04:29 | 89459.16 | 31522.79 | 31938.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 45138.72 | 25-NOV-23:30 | 89459.16 | 47285.09 | 42584.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 44775.32 | 01-DEC-02:15 | 69011.35 | 9457.38 | 12775.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 19359.10 | 10223.90 | 9457.38 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45138.72 | 89459.16 | 77231.46 | 59618.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5338.59 | 27-JAN-10:47 | 779.69 | 587.01 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.42 |
February | 5442.77 | 04-FEB-11:38 | 3898.44 | 1956.71 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.18 |
March | 4427.77 | 08-MAR-13:30 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.25 |
April | 3491.59 | 13-APR-12:50 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 |
May | 2775.03 | 13-MAY-13:00 | 389.84 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 41.03 | 0.00 |
June | 3073.79 | 29-JUN-14:30 | 389.84 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 123.25 | 0.00 |
July | 3294.55 | 22-JUL-13:30 | 389.84 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 120.37 | 0.00 |
August | 4069.11 | 22-AUG-13:20 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 67.74 | 0.00 |
September | 4910.88 | 28-SEP-13:10 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 48.66 | 0.00 |
October | 4945.10 | 19-OCT-12:30 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.47 |
November | 5881.06 | 19-NOV-09:07 | 4548.18 | 1643.63 | 2020.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.12 |
December | 6218.53 | 23-DEC-12:41 | 2728.91 | 1369.70 | 1768.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2775.03 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6218.53 | 4548.18 | 1956.71 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 123.25 | 226.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3297.33 | 03-JAN-21:50 | 9630.72 | 5800.64 | 6017.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.48 |
February | 3072.38 | 25-FEB-23:11 | 8426.88 | 2175.24 | 2674.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.69 |
March | 3759.13 | 27-MAR-06:02 | 3611.52 | 2719.05 | 3008.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.02 |
April | 2733.93 | 05-APR-23:12 | 5417.28 | 725.08 | 1002.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.46 |
May | 2088.13 | 19-MAY-20:50 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 |
June | 2363.15 | 28-JUN-20:10 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 21.40 | 0.00 |
July | 2431.40 | 21-JUL-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 22.02 | 0.00 |
August | 2365.88 | 18-AUG-20:10 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 11.23 | 0.00 |
September | 2186.72 | 13-SEP-20:10 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 |
October | 2879.35 | 24-OCT-21:14 | 6771.60 | 2719.05 | 2925.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.21 |
November | 3119.71 | 24-NOV-22:48 | 6771.60 | 2719.05 | 2925.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.16 |
December | 3010.47 | 18-DEC-22:51 | 13543.20 | 5438.10 | 5850.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2088.13 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3759.13 | 13543.20 | 5800.64 | 6017.16 | 0.00 | 0.00 | 0.00 | 0.00 | 22.02 | 95.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1246.30 | 29-JAN-20:00 | 572.83 | 3174.26 | 2120.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.51 |
February | 1247.34 | 08-FEB-22:05 | 1718.50 | 5441.59 | 3711.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.81 |
March | 1305.82 | 09-MAR-05:17 | 2864.16 | 3023.10 | 2650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.58 |
April | 1525.82 | 28-APR-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.99 |
May | 1900.64 | 19-MAY-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 0.00 |
June | 2389.76 | 29-JUN-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 23.75 | 0.00 |
July | 2417.45 | 21-JUL-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 57.03 | 0.00 |
August | 2286.19 | 18-AUG-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 28.14 | 0.00 |
September | 1979.40 | 01-SEP-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 |
October | 1802.03 | 02-OCT-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.86 |
November | 1301.23 | 25-NOV-23:26 | 2227.68 | 4534.65 | 3534.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.28 |
December | 1182.06 | 04-DEC-11:33 | 572.83 | 3400.99 | 2783.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1182.06 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2417.45 | 2864.16 | 5441.59 | 3711.24 | 0.00 | 0.00 | 0.00 | 0.00 | 57.03 | 201.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1144.50 | 11-JAN-17:51 | 856.80 | 442.80 | 624.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.05 |
February | 1160.47 | 08-FEB-22:05 | 1321.92 | 910.87 | 1070.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.94 |
March | 1242.27 | 09-MAR-05:17 | 2203.20 | 506.04 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.66 |
April | 1335.35 | 24-APR-00:33 | 660.96 | 113.87 | 191.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.92 |
May | 1135.27 | 02-MAY-00:07 | 1321.92 | 227.73 | 382.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.62 |
June | 933.08 | 29-JUN-10:35 | 97.92 | 126.52 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 46.07 | 0.00 |
July | 936.44 | 23-JUL-10:35 | 146.88 | 151.81 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 41.98 | 0.00 |
August | 920.37 | 19-AUG-10:35 | 146.88 | 126.52 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 29.24 | 0.00 |
September | 896.79 | 03-SEP-10:35 | 146.88 | 151.81 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 27.97 | 0.00 |
October | 1278.96 | 12-OCT-03:53 | 660.96 | 75.91 | 152.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.23 |
November | 1222.62 | 25-NOV-23:26 | 1713.60 | 759.06 | 1019.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.29 |
December | 1055.86 | 20-DEC-18:05 | 1224.00 | 1518.11 | 1784.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 896.79 | 97.92 | 75.91 | 152.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1335.35 | 2203.20 | 1518.11 | 1784.32 | 0.00 | 0.00 | 0.00 | 0.00 | 46.07 | 108.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 53436.15 | 03-JAN-21:39 | 8064.00 | 3175.23 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 335.48 |
February | 52860.24 | 01-FEB-21:30 | 8064.00 | 3175.23 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 333.32 |
March | 51649.42 | 02-MAR-21:58 | 8064.00 | 3175.23 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 269.75 |
April | 48827.73 | 23-APR-21:46 | 8064.00 | 1984.52 | 28880.85 | 250904.69 | 0.00 | 0.00 | 0.00 | 0.00 | 263.83 |
May | 40982.72 | 04-MAY-06:10 | 4032.00 | 1984.52 | 28880.85 | 250904.69 | 0.00 | 0.00 | 0.00 | 0.00 | 234.78 |
June | 39613.86 | 28-JUN-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 71.15 | 0.00 |
July | 39637.68 | 21-JUL-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 77.88 | 0.00 |
August | 39462.99 | 17-AUG-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 51.34 | 0.00 |
September | 39040.49 | 13-SEP-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.30 |
October | 52155.04 | 24-OCT-19:09 | 7056.00 | 3572.14 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 300.98 |
November | 51038.12 | 27-NOV-21:49 | 8064.00 | 3175.23 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 337.43 |
December | 54234.20 | 04-DEC-20:57 | 7056.00 | 3572.14 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 325.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 39040.49 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 54234.20 | 8064.00 | 3572.14 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 77.88 | 337.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22123.99 | 01-JAN-10:00 | 17076.00 | 716.51 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.84 |
February | 22025.27 | 04-FEB-13:00 | 15368.40 | 895.64 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.88 |
March | 19547.64 | 05-MAR-23:30 | 27321.60 | 1174.60 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.22 |
April | 16810.31 | 23-APR-23:41 | 138315.60 | 3523.81 | 2743.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.40 |
May | 13682.71 | 02-MAY-00:07 | 92210.40 | 1761.91 | 1524.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.80 |
June | 11808.91 | 28-JUN-21:10 | 15368.40 | 1174.60 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 97.85 | 0.00 |
July | 12112.50 | 21-JUL-21:10 | 15368.40 | 1174.60 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 120.33 | 0.00 |
August | 13385.32 | 20-AUG-12:00 | 5122.80 | 358.25 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 184.29 | 0.00 |
September | 15573.25 | 28-SEP-13:10 | 3415.20 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 107.58 | 0.00 |
October | 20130.61 | 28-OCT-04:35 | 153684.00 | 1957.67 | 2032.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467.42 |
November | 25664.03 | 19-NOV-09:07 | 59766.00 | 2507.78 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.41 |
December | 25541.39 | 23-DEC-12:41 | 35859.60 | 2089.82 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11808.91 | 3415.20 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25664.03 | 153684.00 | 3523.81 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 184.29 | 500.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 66062.70 | 15-JAN-22:37 | 121661.28 | 17108.64 | 19002.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1486.01 |
February | 63849.34 | 16-FEB-00:43 | 456229.80 | 22811.52 | 31671.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1279.36 |
March | 64900.80 | 17-MAR-23:00 | 319360.86 | 23952.09 | 29559.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1432.61 |
April | 65137.38 | 23-APR-23:40 | 91245.96 | 4562.30 | 6334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1269.67 |
May | 71921.87 | 04-MAY-05:47 | 106453.62 | 13048.19 | 15835.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1103.85 |
June | 43055.22 | 28-JUN-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 279.42 | 0.00 |
July | 43769.54 | 21-JUL-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 343.69 | 0.00 |
August | 43338.01 | 18-AUG-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 106.09 | 0.00 |
September | 41620.28 | 13-SEP-20:10 | 40553.76 | 9124.61 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.56 |
October | 63570.44 | 28-OCT-04:35 | 456229.80 | 11405.76 | 21114.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1341.51 |
November | 64995.01 | 24-NOV-23:13 | 410606.82 | 30795.55 | 38005.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1296.39 |
December | 65024.57 | 29-DEC-23:07 | 136868.94 | 10265.18 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1458.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 41620.28 | 40553.76 | 4562.30 | 6334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 71921.87 | 456229.80 | 30795.55 | 38005.42 | 0.00 | 0.00 | 0.00 | 0.00 | 343.69 | 1486.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4007.49 | 20-JAN-16:01 | 972.00 | 343.01 | 684.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.79 |
February | 4319.82 | 13-FEB-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.14 |
March | 4355.85 | 08-MAR-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 0.00 |
April | 4492.00 | 26-APR-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 17.21 | 0.00 |
May | 4530.57 | 09-MAY-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 23.86 | 0.00 |
June | 4587.06 | 28-JUN-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 85.42 | 0.00 |
July | 4559.55 | 21-JUL-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 72.36 | 0.00 |
August | 3803.62 | 17-AUG-08:61 | 252.00 | 377.32 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 20.44 | 0.00 |
September | 4602.46 | 20-SEP-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 43.71 | 0.00 |
October | 4597.82 | 05-OCT-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 23.15 | 0.00 |
November | 4115.71 | 02-NOV-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.64 |
December | 4030.89 | 04-DEC-16:01 | 972.00 | 343.01 | 684.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3803.62 | 252.00 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4602.46 | 972.00 | 654.18 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 85.42 | 102.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3851.54 | 01-JAN-16:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.71 |
February | 4180.90 | 13-FEB-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 |
March | 4244.45 | 08-MAR-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 | 0.00 |
April | 4416.99 | 26-APR-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 17.57 | 0.00 |
May | 4485.26 | 20-MAY-18:01 | 819.00 | 857.43 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 21.31 | 0.00 |
June | 4551.43 | 13-JUN-18:01 | 970.20 | 763.12 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 50.95 | 0.00 |
July | 4521.15 | 21-JUL-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 72.15 | 0.00 |
August | 3757.99 | 17-AUG-08:61 | 252.00 | 377.27 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 20.43 | 0.00 |
September | 4495.10 | 21-SEP-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 41.89 | 0.00 |
October | 4478.13 | 05-OCT-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 24.15 | 0.00 |
November | 3986.87 | 02-NOV-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.38 |
December | 3834.31 | 29-DEC-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3757.99 | 252.00 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4551.43 | 970.20 | 857.43 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 72.15 | 62.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 847.23 | 03-JAN-12:40 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.73 |
February | 871.58 | 14-FEB-13:00 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.31 |
March | 744.66 | 08-MAR-13:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 |
April | 573.51 | 13-APR-13:20 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 0.00 |
May | 422.39 | 13-MAY-13:10 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 7.76 | 0.00 |
June | 469.87 | 29-JUN-14:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 0.00 |
July | 515.72 | 23-JUL-13:30 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 19.28 | 0.00 |
August | 649.19 | 22-AUG-13:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 0.00 |
September | 820.19 | 28-SEP-13:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 9.40 | 0.00 |
October | 877.14 | 19-OCT-12:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 |
November | 854.81 | 20-NOV-13:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 |
December | 861.84 | 31-DEC-13:40 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 422.39 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 877.14 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 23.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 456.07 | 22-JAN-19:03 | 1170.00 | 770.11 | 1264.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.73 |
February | 899.31 | 15-FEB-19:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.25 |
March | 1071.61 | 27-MAR-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 |
April | 1236.50 | 29-APR-15:01 | 378.00 | 177.90 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 5.11 | 0.00 |
May | 1286.76 | 19-MAY-18:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.72 | 0.00 |
June | 1295.88 | 16-JUN-18:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 11.95 | 0.00 |
July | 1287.94 | 21-JUL-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 19.76 | 0.00 |
August | 1154.90 | 21-AUG-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 14.69 | 0.00 |
September | 1247.06 | 20-SEP-18:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 7.71 | 0.00 |
October | 1219.18 | 11-OCT-18:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 | 0.00 |
November | 1013.26 | 02-NOV-18:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 |
December | 435.33 | 23-DEC-19:04 | 936.00 | 616.09 | 1011.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 435.33 | 378.00 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1295.88 | 1170.00 | 770.11 | 1264.50 | 0.00 | 0.00 | 0.00 | 0.00 | 19.76 | 31.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3513.11 | 01-JAN-09:01 | 378.00 | 480.22 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.32 |
February | 3752.68 | 13-FEB-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.30 |
March | 3802.86 | 08-MAR-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 2.35 | 0.00 |
April | 3922.13 | 29-APR-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 18.29 | 0.00 |
May | 3964.81 | 21-MAY-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 33.02 | 0.00 |
June | 4006.71 | 28-JUN-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 85.89 | 0.00 |
July | 3961.25 | 04-JUL-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 72.13 | 0.00 |
August | 3353.77 | 25-AUG-18:01 | 970.20 | 763.21 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 0.00 |
September | 4004.24 | 21-SEP-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 41.83 | 0.00 |
October | 3999.24 | 06-OCT-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 29.86 | 0.00 |
November | 3586.93 | 13-NOV-09:01 | 360.00 | 539.02 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.21 |
December | 3515.99 | 31-DEC-09:01 | 378.00 | 480.22 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3353.77 | 324.00 | 240.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4006.71 | 970.20 | 763.21 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 85.89 | 138.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3277.11 | 01-JAN-09:01 | 378.00 | 480.16 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.81 |
February | 3494.40 | 14-FEB-16:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 3.27 | 0.00 |
March | 3711.79 | 08-MAR-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 | 0.00 |
April | 3876.50 | 29-APR-15:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 18.45 | 0.00 |
May | 3926.30 | 21-MAY-15:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 33.06 | 0.00 |
June | 3969.99 | 28-JUN-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 85.89 | 0.00 |
July | 3915.49 | 21-JUL-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 73.33 | 0.00 |
August | 3372.63 | 23-AUG-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 13.82 | 0.00 |
September | 3917.48 | 21-SEP-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 | 0.00 |
October | 3899.67 | 06-OCT-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 30.90 | 0.00 |
November | 3458.42 | 07-NOV-09:01 | 252.00 | 377.27 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.33 |
December | 3283.71 | 30-DEC-09:01 | 378.00 | 480.16 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3277.11 | 252.00 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3969.99 | 831.60 | 654.11 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 85.89 | 124.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2611.10 | 29-JAN-20:00 | 4526.71 | 5228.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.74 |
February | 2586.41 | 08-FEB-22:05 | 13580.14 | 8963.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.78 |
March | 2796.59 | 09-MAR-05:17 | 22633.56 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.11 |
April | 2995.24 | 24-APR-00:33 | 6790.07 | 1120.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.37 |
May | 2936.26 | 19-MAY-18:30 | 1760.39 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.46 | 0.00 |
June | 3523.09 | 16-JUN-18:30 | 1760.39 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 0.00 |
July | 3661.40 | 21-JUL-18:30 | 1760.39 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.40 | 0.00 |
August | 3441.04 | 18-AUG-18:15 | 3520.78 | 3983.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.79 | 0.00 |
September | 2909.10 | 13-SEP-18:15 | 3520.78 | 3983.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.66 | 0.00 |
October | 2864.79 | 12-OCT-03:53 | 6790.07 | 746.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.71 |
November | 2768.92 | 25-NOV-23:26 | 17603.88 | 7469.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.36 |
December | 2542.44 | 04-DEC-11:33 | 4526.71 | 5601.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2542.44 | 1760.39 | 746.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3661.40 | 22633.56 | 8963.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.40 | 154.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4217.73 | 09-JAN-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.23 |
February | 4566.58 | 13-FEB-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.36 |
March | 4596.59 | 08-MAR-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 1.73 | 0.00 |
April | 4748.26 | 13-APR-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 14.49 | 0.00 |
May | 4793.36 | 20-MAY-18:01 | 819.00 | 857.53 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 21.15 | 0.00 |
June | 4867.36 | 28-JUN-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 85.00 | 0.00 |
July | 4838.39 | 21-JUL-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 71.92 | 0.00 |
August | 3948.90 | 18-AUG-08:61 | 252.00 | 377.32 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 13.51 | 0.00 |
September | 4872.10 | 20-SEP-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 43.43 | 0.00 |
October | 4866.59 | 05-OCT-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 22.87 | 0.00 |
November | 4338.03 | 02-NOV-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 |
December | 4252.27 | 04-DEC-16:01 | 972.00 | 343.01 | 684.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3948.90 | 252.00 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4872.10 | 972.00 | 857.53 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 85.00 | 102.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4046.78 | 05-JAN-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.87 |
February | 4394.13 | 13-FEB-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.74 |
March | 4462.21 | 08-MAR-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 2.78 | 0.00 |
April | 4655.28 | 26-APR-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 17.45 | 0.00 |
May | 4741.48 | 20-MAY-18:01 | 819.00 | 857.43 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 20.99 | 0.00 |
June | 4814.73 | 13-JUN-18:01 | 970.20 | 763.12 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 50.59 | 0.00 |
July | 4790.53 | 21-JUL-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 71.70 | 0.00 |
August | 3898.76 | 18-AUG-08:61 | 252.00 | 377.27 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 0.00 |
September | 4746.30 | 21-SEP-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 41.65 | 0.00 |
October | 4723.65 | 05-OCT-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 23.97 | 0.00 |
November | 4177.83 | 02-NOV-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.18 |
December | 4012.61 | 02-DEC-16:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3898.76 | 252.00 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4814.73 | 970.20 | 857.43 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 71.70 | 63.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2000.33 | 03-JAN-16:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.05 |
February | 2144.47 | 14-FEB-16:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.32 |
March | 2143.32 | 08-MAR-16:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
April | 2183.21 | 13-APR-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 6.88 | 0.00 |
May | 2188.09 | 31-MAY-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 13.88 | 0.00 |
June | 2208.78 | 28-JUN-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 43.40 | 0.00 |
July | 2172.75 | 21-JUL-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 37.06 | 0.00 |
August | 1901.96 | 11-AUG-18:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 15.16 | 0.00 |
September | 2252.76 | 27-SEP-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 18.31 | 0.00 |
October | 2203.32 | 31-OCT-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 2.46 | 0.00 |
November | 2027.99 | 02-NOV-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.80 |
December | 1999.78 | 31-DEC-16:01 | 378.00 | 177.90 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1901.96 | 378.00 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2252.76 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 43.40 | 39.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 32229.98 | 23-JAN-23:15 | 107955.07 | 4125.41 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.64 |
February | 31077.12 | 23-FEB-22:53 | 242898.91 | 18564.33 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.48 |
March | 38416.08 | 17-MAR-22:54 | 188921.38 | 7219.46 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.19 |
April | 34421.42 | 07-APR-06:00 | 41982.53 | 2200.22 | 11246.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.24 |
May | 31253.53 | 04-MAY-04:04 | 134943.84 | 3437.84 | 11246.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.32 |
June | 23453.36 | 28-JUN-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 57.52 | 0.00 |
July | 23573.84 | 21-JUL-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 71.92 | 0.00 |
August | 22737.17 | 17-AUG-22:00 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 42.36 | 0.00 |
September | 21581.51 | 01-SEP-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.16 |
October | 31651.41 | 25-OCT-22:37 | 80966.30 | 3094.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.86 |
November | 33245.10 | 15-NOV-23:30 | 134943.84 | 5156.76 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.00 |
December | 33601.87 | 13-DEC-23:58 | 161932.61 | 6188.11 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 21581.51 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38416.08 | 242898.91 | 18564.33 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 71.92 | 345.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 34072.17 | 23-JAN-23:15 | 107955.07 | 4125.41 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.23 |
February | 33296.25 | 20-FEB-22:31 | 191920.13 | 13751.36 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.24 |
March | 42370.64 | 17-MAR-22:54 | 188921.38 | 7219.46 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.42 |
April | 36513.93 | 07-APR-06:00 | 41982.53 | 2200.22 | 11246.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.19 |
May | 33076.99 | 04-MAY-04:04 | 134943.84 | 3437.84 | 11246.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.95 |
June | 24804.48 | 28-JUN-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 57.42 | 0.00 |
July | 24943.20 | 21-JUL-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 71.81 | 0.00 |
August | 24087.07 | 07-AUG-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 30.46 | 0.00 |
September | 22927.03 | 01-SEP-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.16 |
October | 34131.60 | 30-OCT-03:58 | 269887.68 | 3437.84 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.41 |
November | 36202.51 | 15-NOV-23:30 | 134943.84 | 5156.76 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.72 |
December | 36855.76 | 13-DEC-23:58 | 161932.61 | 6188.11 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22927.03 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42370.64 | 269887.68 | 13751.36 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 71.81 | 341.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37798.68 | 31-JAN-12:51 | 4803.41 | 2724.58 | 134215.70 | 168696.24 | 0.00 | 0.00 | 0.00 | 0.00 | 269.59 |
February | 39788.84 | 06-FEB-17:01 | 13342.80 | 3027.31 | 149128.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 290.10 |
March | 36794.87 | 22-MAR-07:57 | 10674.24 | 4843.69 | 149128.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 270.85 |
April | 36239.88 | 09-APR-05:22 | 18679.92 | 3632.77 | 125511.30 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 265.03 |
May | 33221.12 | 04-MAY-06:10 | 10674.24 | 6054.62 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 241.74 |
June | 31720.83 | 29-JUN-10:40 | 1067.42 | 605.46 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 100.99 | 0.00 |
July | 32013.48 | 23-JUL-10:40 | 1601.14 | 726.55 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 90.57 | 0.00 |
August | 31964.77 | 20-AUG-10:40 | 1601.14 | 726.55 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 71.51 | 0.00 |
September | 31792.73 | 03-SEP-10:40 | 1601.14 | 726.55 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 52.33 | 0.00 |
October | 36970.14 | 24-OCT-16:58 | 13342.80 | 3027.31 | 149128.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 295.07 |
November | 42462.57 | 29-NOV-08:41 | 10674.24 | 4843.69 | 149128.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 310.13 |
December | 37773.06 | 16-DEC-10:37 | 7205.11 | 3269.49 | 134215.70 | 168696.24 | 0.00 | 0.00 | 0.00 | 0.00 | 290.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 31720.83 | 1067.42 | 605.46 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42462.57 | 18679.92 | 6054.62 | 149128.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 100.99 | 310.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4074.44 | 29-JAN-20:00 | 4790.88 | 5533.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.15 |
February | 4098.59 | 08-FEB-22:05 | 14372.64 | 9486.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.36 |
March | 4368.31 | 09-MAR-05:17 | 23954.40 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.39 |
April | 5622.33 | 13-APR-14:10 | 798.48 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 | 0.00 |
May | 5960.19 | 30-MAY-14:30 | 798.48 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.11 | 0.00 |
June | 7450.79 | 28-JUN-15:03 | 9315.60 | 4611.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.55 | 0.00 |
July | 7542.23 | 22-JUL-13:30 | 798.48 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.32 | 0.00 |
August | 7696.74 | 20-AUG-13:10 | 532.32 | 527.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.22 | 0.00 |
September | 7704.56 | 03-SEP-13:30 | 532.32 | 527.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.92 | 0.00 |
October | 7007.70 | 01-OCT-12:00 | 798.48 | 790.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.99 | 0.00 |
November | 4301.31 | 25-NOV-23:26 | 18631.20 | 7905.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.90 |
December | 4031.73 | 04-DEC-11:33 | 4790.88 | 5928.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4031.73 | 532.32 | 527.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7704.56 | 23954.40 | 9486.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.55 | 272.36 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.402867E+12 | 257151.41 | 03-JAN-20:10 | 0.520163E+12 | 495560.61 | 15-JAN-22:30 |
February | 0.364801E+12 | 259105.63 | 07-FEB-20:00 | 0.456683E+12 | 480673.93 | 01-FEB-19:49 |
March | 0.404982E+12 | 270123.38 | 08-MAR-20:19 | 0.469082E+12 | 473730.63 | 03-MAR-22:40 |
April | 0.426715E+12 | 326307.39 | 28-APR-19:10 | 0.429120E+12 | 383234.38 | 23-APR-17:19 |
May | 0.477094E+12 | 357609.44 | 19-MAY-19:10 | 0.414305E+12 | 350592.14 | 01-MAY-17:19 |
June | 0.543851E+12 | 393270.25 | 27-JUN-19:19 | 0.384159E+12 | 348436.56 | 01-JUN-17:30 |
July | 0.617743E+12 | 407587.22 | 21-JUL-19:19 | 0.388206E+12 | 343789.69 | 01-JUL-17:00 |
August | 0.596578E+12 | 389722.09 | 18-AUG-19:10 | 0.386842E+12 | 342095.10 | 29-AUG-17:49 |
September | 0.515137E+12 | 358135.47 | 13-SEP-19:19 | 0.379200E+12 | 347412.15 | 29-SEP-17:30 |
October | 0.459516E+12 | 323543.20 | 05-OCT-18:10 | 0.425726E+12 | 423624.85 | 24-OCT-17:30 |
November | 0.397509E+12 | 264303.52 | 02-NOV-19:10 | 0.459471E+12 | 455789.25 | 26-NOV-19:40 |
December | 0.406121E+12 | 265383.96 | 29-DEC-20:10 | 0.524250E+12 | 469859.22 | 16-DEC-22:19 |
Annual Sum or Average | 0.561291E+13 | 0.523721E+13 | ||||
Minimum of Months | 0.364801E+12 | 257151.41 | 0.379200E+12 | 342095.10 | ||
Maximum of Months | 0.617743E+12 | 407587.22 | 0.524250E+12 | 495560.61 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.653921E+11 | 0.241922E+11 | 0.148212E+12 | 0.553309E+11 | 0.506401E+11 | 0.859886E+10 | 0.00 | 0.141236E+11 | 0.00 | 0.00 | 0.234636E+11 | 0.770383E+10 | 0.00 |
February | 0.589710E+11 | 0.206051E+11 | 0.133859E+12 | 0.499764E+11 | 0.451519E+11 | 0.857403E+10 | 0.00 | 0.162602E+11 | 0.00 | 0.00 | 0.197329E+11 | 0.696139E+10 | 0.00 |
March | 0.651830E+11 | 0.210129E+11 | 0.148223E+12 | 0.553337E+11 | 0.491318E+11 | 0.106039E+11 | 0.00 | 0.259639E+11 | 0.00 | 0.00 | 0.166231E+11 | 0.770256E+10 | 0.00 |
April | 0.628077E+11 | 0.184917E+11 | 0.143397E+12 | 0.535454E+11 | 0.497745E+11 | 0.134413E+11 | 0.00 | 0.618914E+11 | 0.00 | 0.00 | 0.108905E+11 | 0.746469E+10 | 0.00 |
May | 0.648783E+11 | 0.175370E+11 | 0.148223E+12 | 0.553319E+11 | 0.530546E+11 | 0.156539E+11 | 0.00 | 0.994842E+11 | 0.00 | 0.00 | 0.100096E+11 | 0.770421E+10 | 0.00 |
June | 0.626663E+11 | 0.161374E+11 | 0.143446E+12 | 0.535481E+11 | 0.581735E+11 | 0.174127E+11 | 0.00 | 0.167029E+12 | 0.00 | 0.00 | 0.128887E+11 | 0.745688E+10 | 0.00 |
July | 0.647401E+11 | 0.171106E+11 | 0.148174E+12 | 0.553290E+11 | 0.639384E+11 | 0.196531E+11 | 0.00 | 0.220584E+12 | 0.00 | 0.00 | 0.151957E+11 | 0.771239E+10 | 0.00 |
August | 0.649283E+11 | 0.183990E+11 | 0.148234E+12 | 0.553335E+11 | 0.647216E+11 | 0.194761E+11 | 0.00 | 0.199584E+12 | 0.00 | 0.00 | 0.128719E+11 | 0.770434E+10 | 0.00 |
September | 0.629519E+11 | 0.195577E+11 | 0.143408E+12 | 0.535457E+11 | 0.597025E+11 | 0.173617E+11 | 0.00 | 0.137979E+12 | 0.00 | 0.00 | 0.804394E+10 | 0.746624E+10 | 0.00 |
October | 0.652720E+11 | 0.220789E+11 | 0.148201E+12 | 0.553307E+11 | 0.571943E+11 | 0.143283E+11 | 0.00 | 0.731515E+11 | 0.00 | 0.00 | 0.110302E+11 | 0.770274E+10 | 0.00 |
November | 0.632882E+11 | 0.229780E+11 | 0.143462E+12 | 0.535468E+11 | 0.516985E+11 | 0.103319E+11 | 0.00 | 0.213597E+11 | 0.00 | 0.00 | 0.183597E+11 | 0.744816E+10 | 0.00 |
December | 0.653872E+11 | 0.246371E+11 | 0.148174E+12 | 0.553296E+11 | 0.520332E+11 | 0.860867E+10 | 0.00 | 0.144577E+11 | 0.00 | 0.00 | 0.245720E+11 | 0.771196E+10 | 0.00 |
Annual Sum or Average | 0.766466E+12 | 0.242738E+12 | 0.174501E+13 | 0.651482E+12 | 0.655215E+12 | 0.164045E+12 | 0.00 | 0.105187E+13 | 0.00 | 0.00 | 0.183682E+12 | 0.907394E+11 | 0.00 |
Minimum of Months | 0.589710E+11 | 0.161374E+11 | 0.133859E+12 | 0.499764E+11 | 0.451519E+11 | 0.857403E+10 | 0.00 | 0.141236E+11 | 0.00 | 0.00 | 0.804394E+10 | 0.696139E+10 | 0.00 |
Maximum of Months | 0.653921E+11 | 0.246371E+11 | 0.148234E+12 | 0.553337E+11 | 0.647216E+11 | 0.196531E+11 | 0.00 | 0.220584E+12 | 0.00 | 0.00 | 0.245720E+11 | 0.771239E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.874257E+11 | 0.00 | 0.280819E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.644706E+11 | 0.00 | 0.255008E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.393593E+11 | 0.00 | 0.277699E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.229627E+11 | 0.00 | 0.259202E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.682739E+10 | 0.00 | 0.255499E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.959320E+09 | 0.00 | 0.236086E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 79925950.05 | 0.00 | 0.236306E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 78513961.79 | 0.00 | 0.234725E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.427473E+09 | 0.00 | 0.231802E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.243773E+11 | 0.00 | 0.249445E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.590222E+11 | 0.00 | 0.253357E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.991679E+11 | 0.00 | 0.273261E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.405158E+12 | 0.00 | 0.304321E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 78513961.79 | 0.00 | 0.231802E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.991679E+11 | 0.00 | 0.280819E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 62892.57 | 02-JAN-20:10 | 15448.40 | 01-JAN-00:10 | 89475.41 | 02-JAN-07:10 | 39726.11 | 02-JAN-07:19 | 50173.79 | 04-JAN-22:30 | 6169.11 | 01-JAN-13:00 | 0.00 | 01-JAN-00:10 |
February | 62892.57 | 01-FEB-20:10 | 15448.40 | 01-FEB-00:10 | 89475.41 | 01-FEB-07:10 | 39726.11 | 01-FEB-07:19 | 48383.04 | 24-FEB-21:19 | 7043.24 | 14-FEB-16:49 | 0.00 | 01-FEB-00:10 |
March | 62892.57 | 01-MAR-20:10 | 15448.40 | 01-MAR-00:10 | 89475.41 | 01-MAR-07:10 | 39726.11 | 13-MAR-06:19 | 44104.36 | 17-MAR-20:30 | 7217.20 | 08-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 62892.57 | 03-APR-19:10 | 15448.40 | 01-APR-00:10 | 89475.41 | 03-APR-06:10 | 39724.49 | 03-APR-06:19 | 41557.42 | 13-APR-21:10 | 7548.22 | 13-APR-18:30 | 0.00 | 01-APR-00:10 |
May | 62892.57 | 01-MAY-19:10 | 15448.40 | 01-MAY-00:10 | 89475.41 | 01-MAY-06:10 | 39725.36 | 22-MAY-06:19 | 44860.44 | 19-MAY-21:10 | 7981.80 | 21-MAY-20:19 | 0.00 | 01-MAY-00:10 |
June | 62892.57 | 01-JUN-19:10 | 15448.40 | 01-JUN-00:10 | 89475.41 | 01-JUN-06:10 | 39724.64 | 08-JUN-06:19 | 49571.14 | 27-JUN-21:10 | 8181.19 | 26-JUN-18:30 | 0.00 | 01-JUN-00:10 |
July | 62892.57 | 03-JUL-19:19 | 15448.40 | 01-JUL-00:10 | 89475.41 | 03-JUL-06:10 | 39725.12 | 28-JUL-06:19 | 51758.71 | 21-JUL-21:10 | 8150.92 | 21-JUL-20:00 | 0.00 | 01-JUL-00:10 |
August | 62892.57 | 01-AUG-19:10 | 15448.40 | 01-AUG-00:10 | 89475.41 | 01-AUG-06:10 | 39724.49 | 02-AUG-06:19 | 52674.29 | 18-AUG-21:10 | 8143.54 | 15-AUG-18:19 | 0.00 | 01-AUG-00:10 |
September | 62892.57 | 01-SEP-19:10 | 15448.40 | 01-SEP-00:10 | 89475.41 | 01-SEP-06:10 | 39726.11 | 08-SEP-06:19 | 51472.53 | 13-SEP-21:10 | 8115.08 | 02-SEP-20:49 | 0.00 | 01-SEP-00:10 |
October | 62892.57 | 02-OCT-19:10 | 15448.40 | 01-OCT-00:10 | 89475.41 | 02-OCT-06:10 | 39726.11 | 02-OCT-06:19 | 48454.73 | 06-OCT-21:10 | 8022.38 | 10-OCT-18:30 | 0.00 | 01-OCT-00:10 |
November | 62892.57 | 01-NOV-19:10 | 15448.40 | 01-NOV-00:10 | 89475.41 | 01-NOV-06:10 | 39726.11 | 01-NOV-06:19 | 49237.97 | 03-NOV-21:40 | 6639.99 | 02-NOV-15:09 | 0.00 | 01-NOV-00:10 |
December | 62892.57 | 01-DEC-20:10 | 15448.40 | 01-DEC-00:10 | 89475.41 | 01-DEC-07:10 | 39726.11 | 01-DEC-07:19 | 50128.26 | 13-DEC-23:30 | 6184.19 | 12-DEC-10:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 62892.57 | 15448.40 | 89475.41 | 39724.49 | 41557.42 | 6169.11 | 0.00 | |||||||
Maximum of Months | 62892.57 | 15448.40 | 89475.41 | 39726.11 | 52674.29 | 8181.19 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 41888.44 | 01-JAN-14:09 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:20 | 4738.23 | 06-JAN-19:30 | 0.00 |
February | 71984.58 | 14-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:10 | 4738.20 | 22-FEB-19:00 | 0.00 |
March | 73122.85 | 08-MAR-16:10 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:10 | 4738.45 | 20-MAR-06:40 | 0.00 |
April | 91719.71 | 13-APR-18:10 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4738.31 | 20-APR-18:10 | 0.00 |
May | 113448.20 | 19-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-01:30 | 4738.52 | 25-MAY-18:10 | 0.00 |
June | 162271.04 | 28-JUN-15:09 | 0.00 | 0.00 | 9938.94 | 02-JUN-01:00 | 4738.63 | 15-JUN-18:10 | 0.00 |
July | 166185.81 | 21-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 02-JUL-09:20 | 4738.77 | 13-JUL-18:10 | 0.00 |
August | 147284.68 | 20-AUG-15:20 | 0.00 | 0.00 | 9938.94 | 01-AUG-07:40 | 4737.68 | 01-AUG-06:30 | 0.00 |
September | 121035.89 | 02-SEP-15:20 | 0.00 | 0.00 | 9938.94 | 01-SEP-09:30 | 4738.74 | 07-SEP-18:10 | 0.00 |
October | 108909.52 | 06-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-10:00 | 4738.80 | 17-OCT-06:30 | 0.00 |
November | 47627.02 | 02-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:30 | 4738.41 | 27-NOV-19:40 | 0.00 |
December | 29729.45 | 31-DEC-16:10 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:10 | 4738.44 | 11-DEC-19:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 29729.45 | 0.00 | 0.00 | 9938.94 | 4737.68 | 0.00 | |||
Maximum of Months | 166185.81 | 0.00 | 0.00 | 9938.94 | 4738.80 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 257151.41 | 03-JAN-20:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 30170.79 | 4851.79 | 0.00 | 7486.16 | 0.00 |
February | 259105.63 | 07-FEB-20:00 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 38014.31 | 4368.05 | 0.00 | 2105.68 | 0.00 |
March | 270123.38 | 08-MAR-20:19 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 27113.91 | 6368.38 | 0.00 | 30965.74 | 0.00 |
April | 326307.39 | 28-APR-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 30408.54 | 7502.87 | 0.00 | 82188.33 | 0.00 |
May | 357609.44 | 19-MAY-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 34818.98 | 7497.24 | 0.00 | 100704.88 | 0.00 |
June | 393270.25 | 27-JUN-19:19 | 62892.57 | 88772.42 | 15448.40 | 32159.27 | 39502.07 | 7674.28 | 0.00 | 131191.91 | 0.00 |
July | 407587.22 | 21-JUL-19:19 | 62892.57 | 88772.42 | 15448.40 | 32159.27 | 42761.55 | 7664.93 | 0.00 | 142141.55 | 0.00 |
August | 389722.09 | 18-AUG-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 42462.74 | 8015.27 | 0.00 | 124607.86 | 0.00 |
September | 358135.47 | 13-SEP-19:19 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 37658.44 | 8076.31 | 0.00 | 96912.99 | 0.00 |
October | 323543.20 | 05-OCT-18:10 | 55920.94 | 79417.81 | 15448.40 | 31837.63 | 32022.93 | 7541.12 | 0.00 | 92725.16 | 0.00 |
November | 264303.52 | 02-NOV-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 29437.70 | 6062.48 | 0.00 | 23318.26 | 0.00 |
December | 265383.96 | 29-DEC-20:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 39779.54 | 4857.26 | 0.00 | 5917.35 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 257151.41 | 55920.94 | 79417.81 | 15448.40 | 31837.63 | 27113.91 | 4368.05 | 0.00 | 2105.68 | 0.00 | |
Maximum of Months | 407587.22 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 42761.55 | 8076.31 | 0.00 | 142141.55 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 181318.90 | 15-JAN-22:30 | 0.00 | 284693.62 | 30-JAN-21:19 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 168374.52 | 09-FEB-23:40 | 0.00 | 284573.64 | 13-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 196757.96 | 31-MAR-03:49 | 0.00 | 283086.30 | 21-MAR-20:49 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 158650.74 | 19-APR-04:49 | 0.00 | 266543.84 | 01-APR-19:10 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 100111.23 | 06-MAY-04:10 | 0.00 | 247021.69 | 01-MAY-20:40 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 77500.98 | 09-JUN-03:00 | 0.00 | 244805.32 | 01-JUN-20:00 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 6039.70 | 10-JUL-08:09 | 0.00 | 241901.80 | 02-JUL-21:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 5785.91 | 09-AUG-08:09 | 0.00 | 238711.97 | 29-AUG-20:30 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 12611.52 | 09-SEP-05:00 | 0.00 | 243722.27 | 28-SEP-20:00 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 167755.19 | 13-OCT-02:30 | 0.00 | 246664.73 | 24-OCT-17:49 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 183150.55 | 11-NOV-23:49 | 0.00 | 261009.30 | 30-NOV-21:00 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 199884.92 | 01-DEC-03:20 | 0.00 | 277449.68 | 18-DEC-21:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 5785.91 | 0.00 | 238711.97 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 199884.92 | 0.00 | 284693.62 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.69 | 1.33 | 24.69 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.63 | 0.17 | 24.63 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.70 | 1.83 | 24.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.72 | 2.67 | 24.72 |
Annual Sum or Average | 0.00 | 0.00 | 6.00 | 24.70 | 6.00 | 24.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.72 | 2.67 | 24.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 64.50 | 25.24 | 64.50 | 25.24 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 57.00 | 25.36 | 57.00 | 25.36 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 25.26 | 35.17 | 25.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 25.34 | 23.33 | 25.34 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 25.28 | 3.17 | 25.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.89 | 0.17 | 24.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 25.25 | 21.17 | 25.25 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 52.67 | 25.21 | 52.67 | 25.21 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 68.50 | 25.17 | 68.50 | 25.17 |
Annual Sum or Average | 0.00 | 0.00 | 325.67 | 25.25 | 325.67 | 25.25 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 68.50 | 25.36 | 68.50 | 25.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.88 | 2.17 | 24.88 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.70 | 1.67 | 24.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.69 | 0.33 | 24.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.67 | 0.33 | 24.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.73 | 0.17 | 24.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.72 | 4.33 | 24.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.79 | 4.67 | 24.79 |
Annual Sum or Average | 0.00 | 0.00 | 13.67 | 24.76 | 13.67 | 24.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.88 | 4.67 | 24.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.83 | 0.17 | 24.83 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.64 | 0.17 | 24.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.74 | 0.33 | 24.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.83 | 0.17 | 24.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.78 | 1.00 | 21.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.82 | 2.67 | 21.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.82 | 1.67 | 21.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.75 | 1.17 | 21.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.81 | 0.67 | 21.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.17 | 21.80 | 7.17 | 21.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.82 | 2.67 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.80 | 1.00 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.81 | 2.33 | 21.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.77 | 0.33 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.67 | 21.81 | 3.67 | 21.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.81 | 2.33 | 21.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.74 | 1.33 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.73 | 0.67 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.17 | 21.74 | 2.17 | 21.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.74 | 1.33 | 21.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.72 | 1.33 | 21.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.74 | 0.67 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.87 | 1.50 | 21.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.84 | 0.17 | 21.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.67 | 21.77 | 4.67 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.87 | 1.50 | 21.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.73 | 0.50 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.76 | 1.50 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.76 | 0.67 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.74 | 0.83 | 21.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.83 | 21.75 | 3.83 | 21.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.76 | 1.50 | 21.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.90 | 1.50 | 21.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.91 | 4.33 | 21.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.82 | 3.83 | 21.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.78 | 1.50 | 21.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.92 | 0.50 | 21.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.67 | 21.86 | 11.67 | 21.86 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.92 | 4.33 | 21.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.91 | 1.50 | 21.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.90 | 4.17 | 21.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.76 | 1.67 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.33 | 21.87 | 7.33 | 21.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.91 | 4.17 | 21.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.74 | 0.50 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.77 | 0.67 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.79 | 2.83 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 21.97 | 6.00 | 21.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 22.07 | 5.83 | 22.07 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.00 | 21.96 | 16.00 | 21.96 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 22.07 | 6.00 | 22.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.84 | 1.83 | 24.84 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.86 | 4.17 | 24.86 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.85 | 5.00 | 24.85 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.94 | 3.83 | 24.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.92 | 0.67 | 24.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.79 | 2.17 | 24.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.79 | 4.33 | 24.79 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.79 | 1.50 | 24.79 |
Annual Sum or Average | 0.00 | 0.00 | 23.50 | 24.85 | 23.50 | 24.85 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.94 | 5.00 | 24.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.79 | 3.83 | 24.79 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 24.82 | 7.50 | 24.82 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 24.91 | 6.33 | 24.91 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.97 | 5.00 | 24.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.00 | 0.67 | 25.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.79 | 3.33 | 24.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 24.84 | 6.00 | 24.84 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.80 | 3.33 | 24.80 |
Annual Sum or Average | 0.00 | 0.00 | 36.00 | 24.85 | 36.00 | 24.85 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 25.00 | 7.50 | 25.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 80.17 | 25.19 | 80.17 | 25.19 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 74.00 | 25.27 | 74.00 | 25.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 51.33 | 25.21 | 51.33 | 25.21 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 | 25.26 | 34.00 | 25.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 25.27 | 4.67 | 25.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.20 | 0.17 | 25.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 25.26 | 31.00 | 25.26 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 79.33 | 25.21 | 79.33 | 25.21 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 94.33 | 25.24 | 94.33 | 25.24 |
Annual Sum or Average | 0.00 | 0.00 | 449.00 | 25.23 | 449.00 | 25.23 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 94.33 | 25.27 | 94.33 | 25.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 662.67 | 23.94 | 0.00 | 23.94 | 0.00 | 23.94 |
February | 617.00 | 23.87 | 0.00 | 23.87 | 0.00 | 23.87 |
March | 728.17 | 23.74 | 0.00 | 23.74 | 0.00 | 23.74 |
April | 719.33 | 23.70 | 0.00 | 23.70 | 0.00 | 23.70 |
May | 584.33 | 23.70 | 20.17 | 23.71 | 0.00 | 23.71 |
June | 330.50 | 23.73 | 106.50 | 23.79 | 20.00 | 23.79 |
July | 280.00 | 23.92 | 557.17 | 23.93 | 263.17 | 23.93 |
August | 167.50 | 23.97 | 569.67 | 23.96 | 167.17 | 23.96 |
September | 56.00 | 23.97 | 316.00 | 23.99 | 48.83 | 23.99 |
October | 336.50 | 23.99 | 81.83 | 23.99 | 0.00 | 23.99 |
November | 486.83 | 23.99 | 0.00 | 23.99 | 0.00 | 23.99 |
December | 631.00 | 23.99 | 0.00 | 23.99 | 0.00 | 23.99 |
Annual Sum or Average | 5599.83 | 23.85 | 1651.33 | 23.88 | 499.17 | 23.88 |
Minimum of Months | 56.00 | 23.70 | 0.00 | 23.70 | 0.00 | 23.70 |
Maximum of Months | 728.17 | 23.99 | 569.67 | 23.99 | 263.17 | 23.99 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 572.67 | 21.93 | 139.50 | 22.17 | 40.17 | 22.11 |
February | 478.67 | 22.06 | 107.67 | 22.38 | 7.83 | 22.36 |
March | 550.17 | 22.38 | 73.83 | 22.57 | 1.50 | 22.56 |
April | 458.00 | 22.94 | 37.33 | 23.02 | 0.00 | 23.02 |
May | 378.33 | 22.97 | 106.67 | 23.19 | 0.83 | 23.19 |
June | 146.17 | 23.18 | 392.17 | 23.76 | 16.50 | 23.76 |
July | 225.67 | 23.92 | 734.67 | 23.96 | 225.67 | 23.95 |
August | 149.00 | 23.92 | 724.17 | 23.96 | 149.00 | 23.96 |
September | 118.33 | 23.44 | 536.00 | 23.87 | 52.67 | 23.86 |
October | 290.83 | 22.70 | 286.00 | 23.32 | 4.00 | 23.31 |
November | 484.50 | 22.47 | 137.17 | 22.82 | 0.00 | 22.82 |
December | 554.33 | 21.92 | 149.00 | 22.21 | 37.67 | 22.15 |
Annual Sum or Average | 4406.67 | 22.56 | 3424.17 | 23.14 | 535.83 | 23.16 |
Minimum of Months | 118.33 | 21.92 | 37.33 | 22.17 | 0.00 | 22.11 |
Maximum of Months | 572.67 | 23.92 | 734.67 | 23.96 | 225.67 | 23.96 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 740.83 | 22.72 | 0.00 | 22.72 | 0.00 | 22.72 |
February | 660.33 | 22.90 | 0.00 | 22.90 | 0.00 | 22.90 |
March | 712.00 | 23.13 | 0.00 | 23.13 | 0.00 | 23.13 |
April | 646.33 | 23.42 | 0.00 | 23.42 | 0.00 | 23.42 |
May | 471.50 | 23.39 | 55.50 | 23.45 | 2.00 | 23.44 |
June | 146.00 | 23.43 | 245.17 | 23.76 | 22.33 | 23.77 |
July | 274.83 | 23.91 | 709.00 | 23.90 | 274.83 | 23.90 |
August | 186.67 | 23.92 | 710.00 | 23.92 | 186.67 | 23.92 |
September | 85.33 | 23.73 | 445.33 | 23.88 | 63.83 | 23.88 |
October | 430.17 | 23.34 | 108.33 | 23.46 | 1.33 | 23.46 |
November | 670.17 | 23.18 | 0.00 | 23.18 | 0.00 | 23.18 |
December | 744.00 | 22.75 | 0.00 | 22.75 | 0.00 | 22.75 |
Annual Sum or Average | 5768.17 | 23.16 | 2273.33 | 23.37 | 551.00 | 23.40 |
Minimum of Months | 85.33 | 22.72 | 0.00 | 22.72 | 0.00 | 22.72 |
Maximum of Months | 744.00 | 23.92 | 710.00 | 23.92 | 274.83 | 23.92 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.77 | 0.00 | 21.77 | 0.00 | 21.77 |
February | 672.00 | 22.01 | 0.00 | 22.01 | 0.00 | 22.01 |
March | 744.00 | 22.64 | 0.00 | 22.64 | 0.00 | 22.64 |
April | 717.33 | 23.30 | 0.00 | 23.30 | 0.00 | 23.30 |
May | 566.50 | 23.63 | 12.00 | 23.64 | 0.00 | 23.64 |
June | 212.50 | 23.90 | 124.17 | 23.93 | 3.00 | 23.93 |
July | 130.83 | 24.00 | 640.50 | 24.00 | 130.83 | 24.00 |
August | 81.33 | 24.00 | 577.83 | 24.00 | 81.33 | 24.00 |
September | 121.83 | 23.93 | 199.50 | 23.96 | 29.83 | 23.96 |
October | 582.17 | 23.21 | 25.50 | 23.24 | 0.00 | 23.24 |
November | 720.00 | 22.53 | 0.00 | 22.53 | 0.00 | 22.53 |
December | 744.00 | 21.70 | 0.00 | 21.70 | 0.00 | 21.70 |
Annual Sum or Average | 6036.50 | 22.68 | 1579.50 | 22.95 | 245.00 | 22.98 |
Minimum of Months | 81.33 | 21.70 | 0.00 | 21.70 | 0.00 | 21.70 |
Maximum of Months | 744.00 | 24.00 | 640.50 | 24.00 | 130.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.05 | 24.17 | 21.05 | 24.17 | 21.05 |
February | 672.00 | 21.13 | 13.50 | 21.13 | 13.50 | 21.13 |
March | 744.00 | 21.43 | 2.00 | 21.43 | 2.00 | 21.43 |
April | 720.00 | 22.01 | 0.00 | 22.01 | 0.00 | 22.01 |
May | 744.00 | 22.44 | 0.00 | 22.44 | 0.00 | 22.44 |
June | 643.33 | 23.00 | 15.33 | 23.02 | 3.67 | 23.02 |
July | 431.83 | 23.26 | 171.33 | 23.29 | 128.33 | 23.29 |
August | 538.33 | 23.15 | 94.83 | 23.16 | 79.17 | 23.16 |
September | 715.83 | 22.87 | 25.83 | 22.87 | 25.83 | 22.87 |
October | 744.00 | 22.14 | 0.00 | 22.14 | 0.00 | 22.14 |
November | 720.00 | 21.36 | 0.00 | 21.36 | 0.00 | 21.36 |
December | 744.00 | 21.04 | 76.83 | 21.04 | 76.83 | 21.04 |
Annual Sum or Average | 8161.33 | 22.00 | 423.83 | 22.03 | 353.50 | 22.05 |
Minimum of Months | 431.83 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
Maximum of Months | 744.00 | 23.26 | 171.33 | 23.29 | 128.33 | 23.29 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 173.67 | 24.48 | 735.50 | 24.16 | 173.67 | 24.21 |
February | 180.67 | 24.46 | 667.50 | 24.17 | 180.67 | 24.22 |
March | 223.67 | 24.23 | 743.67 | 24.09 | 223.67 | 24.12 |
April | 211.67 | 24.13 | 714.50 | 24.06 | 211.67 | 24.07 |
May | 286.67 | 24.01 | 742.33 | 24.00 | 286.67 | 24.00 |
June | 427.00 | 24.00 | 720.00 | 24.00 | 427.00 | 24.00 |
July | 657.33 | 24.00 | 744.00 | 24.00 | 657.33 | 24.00 |
August | 642.83 | 24.00 | 744.00 | 24.00 | 642.83 | 24.00 |
September | 524.33 | 24.00 | 720.00 | 24.00 | 524.33 | 24.00 |
October | 292.67 | 24.09 | 743.17 | 24.04 | 292.67 | 24.05 |
November | 217.33 | 24.31 | 718.50 | 24.14 | 217.33 | 24.17 |
December | 165.33 | 24.47 | 733.67 | 24.16 | 165.33 | 24.21 |
Annual Sum or Average | 4003.17 | 24.11 | 8726.83 | 24.06 | 4003.17 | 24.07 |
Minimum of Months | 165.33 | 24.00 | 667.50 | 24.00 | 165.33 | 24.00 |
Maximum of Months | 657.33 | 24.48 | 744.00 | 24.17 | 657.33 | 24.22 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 550.83 | 22.37 | 137.33 | 22.70 | 0.00 | 22.70 |
February | 453.17 | 22.50 | 141.00 | 22.86 | 0.00 | 22.86 |
March | 533.17 | 22.61 | 112.33 | 22.85 | 0.00 | 22.85 |
April | 463.67 | 22.85 | 79.67 | 23.01 | 0.00 | 23.01 |
May | 397.17 | 22.62 | 96.33 | 22.80 | 7.83 | 22.80 |
June | 227.50 | 22.77 | 347.83 | 23.32 | 46.67 | 23.35 |
July | 405.83 | 23.62 | 723.33 | 23.61 | 405.17 | 23.61 |
August | 306.33 | 23.70 | 718.50 | 23.73 | 303.83 | 23.72 |
September | 142.67 | 23.31 | 620.33 | 23.70 | 108.67 | 23.69 |
October | 240.33 | 22.76 | 351.50 | 23.45 | 15.00 | 23.46 |
November | 428.17 | 22.74 | 184.00 | 23.12 | 0.00 | 23.12 |
December | 539.00 | 22.46 | 159.50 | 22.82 | 0.00 | 22.82 |
Annual Sum or Average | 4687.83 | 22.78 | 3671.67 | 23.23 | 887.17 | 23.27 |
Minimum of Months | 142.67 | 22.37 | 79.67 | 22.70 | 0.00 | 22.70 |
Maximum of Months | 550.83 | 23.70 | 723.33 | 23.73 | 405.17 | 23.72 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 648.17 | 23.19 | 0.00 | 23.19 | 0.00 | 23.19 |
February | 516.17 | 23.27 | 0.00 | 23.27 | 0.00 | 23.27 |
March | 521.50 | 23.33 | 0.17 | 23.33 | 0.00 | 23.33 |
April | 477.67 | 23.43 | 1.83 | 23.44 | 0.00 | 23.44 |
May | 338.17 | 23.29 | 137.33 | 23.47 | 9.67 | 23.48 |
June | 137.50 | 23.40 | 339.50 | 23.77 | 45.00 | 23.78 |
July | 391.83 | 23.88 | 728.00 | 23.86 | 391.83 | 23.86 |
August | 292.00 | 23.90 | 738.33 | 23.89 | 292.00 | 23.89 |
September | 114.33 | 23.86 | 602.00 | 23.90 | 110.83 | 23.90 |
October | 183.83 | 23.43 | 211.33 | 23.70 | 12.00 | 23.71 |
November | 391.67 | 23.43 | 9.83 | 23.44 | 0.00 | 23.44 |
December | 675.83 | 23.30 | 0.00 | 23.30 | 0.00 | 23.30 |
Annual Sum or Average | 4688.67 | 23.42 | 2768.33 | 23.59 | 861.33 | 23.62 |
Minimum of Months | 114.33 | 23.19 | 0.00 | 23.19 | 0.00 | 23.19 |
Maximum of Months | 675.83 | 23.90 | 738.33 | 23.90 | 391.83 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 741.33 | 21.31 | 293.67 | 21.19 | 293.67 | 21.13 |
February | 661.17 | 21.39 | 131.50 | 21.31 | 131.50 | 21.25 |
March | 731.17 | 21.48 | 27.50 | 21.46 | 27.50 | 21.44 |
April | 700.33 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
May | 698.33 | 21.55 | 1.33 | 21.55 | 0.00 | 21.55 |
June | 613.83 | 21.43 | 24.67 | 21.51 | 0.00 | 21.51 |
July | 577.00 | 21.30 | 77.67 | 21.54 | 1.83 | 21.54 |
August | 571.67 | 21.27 | 86.00 | 21.54 | 1.33 | 21.54 |
September | 568.17 | 21.29 | 64.33 | 21.50 | 1.33 | 21.50 |
October | 672.17 | 21.44 | 45.33 | 21.47 | 26.83 | 21.44 |
November | 704.33 | 21.47 | 53.67 | 21.44 | 53.17 | 21.40 |
December | 744.00 | 21.32 | 344.33 | 21.19 | 344.33 | 21.12 |
Annual Sum or Average | 7983.50 | 21.41 | 1150.00 | 21.42 | 881.50 | 21.37 |
Minimum of Months | 568.17 | 21.27 | 0.00 | 21.19 | 0.00 | 21.12 |
Maximum of Months | 744.00 | 21.59 | 344.33 | 21.59 | 344.33 | 21.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.91 | 608.67 | 20.85 | 608.67 | 20.83 |
February | 672.00 | 21.06 | 324.17 | 20.96 | 324.17 | 20.91 |
March | 744.00 | 21.30 | 89.17 | 21.26 | 89.17 | 21.22 |
April | 715.00 | 21.54 | 8.67 | 21.54 | 8.67 | 21.53 |
May | 709.33 | 21.55 | 2.50 | 21.55 | 1.83 | 21.55 |
June | 621.17 | 21.46 | 23.00 | 21.52 | 0.00 | 21.52 |
July | 585.67 | 21.32 | 66.83 | 21.53 | 1.67 | 21.53 |
August | 597.17 | 21.34 | 60.50 | 21.52 | 1.50 | 21.52 |
September | 625.00 | 21.43 | 29.33 | 21.51 | 1.67 | 21.51 |
October | 721.00 | 21.39 | 60.50 | 21.36 | 56.50 | 21.31 |
November | 719.83 | 21.19 | 238.00 | 21.11 | 238.00 | 21.06 |
December | 744.00 | 20.84 | 644.17 | 20.80 | 644.17 | 20.78 |
Annual Sum or Average | 8198.17 | 21.27 | 2155.50 | 21.21 | 1976.00 | 21.15 |
Minimum of Months | 585.67 | 20.84 | 2.50 | 20.80 | 0.00 | 20.78 |
Maximum of Months | 744.00 | 21.55 | 644.17 | 21.55 | 644.17 | 21.55 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.91 | 575.50 | 20.88 | 575.50 | 20.87 |
February | 672.00 | 20.99 | 299.33 | 20.94 | 299.33 | 20.92 |
March | 744.00 | 21.16 | 68.83 | 21.15 | 68.83 | 21.14 |
April | 720.00 | 21.34 | 9.00 | 21.34 | 9.00 | 21.33 |
May | 744.00 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
June | 720.00 | 21.60 | 0.00 | 21.60 | 0.00 | 21.60 |
July | 744.00 | 21.66 | 2.17 | 21.66 | 2.17 | 21.66 |
August | 744.00 | 21.60 | 2.33 | 21.60 | 2.33 | 21.60 |
September | 720.00 | 21.48 | 0.50 | 21.48 | 0.50 | 21.48 |
October | 744.00 | 21.25 | 40.67 | 21.23 | 40.67 | 21.21 |
November | 720.00 | 21.04 | 281.67 | 21.01 | 281.67 | 20.99 |
December | 744.00 | 20.86 | 636.67 | 20.84 | 636.67 | 20.83 |
Annual Sum or Average | 8760.00 | 21.28 | 1916.67 | 21.20 | 1916.67 | 21.15 |
Minimum of Months | 672.00 | 20.86 | 0.00 | 20.84 | 0.00 | 20.83 |
Maximum of Months | 744.00 | 21.66 | 636.67 | 21.66 | 636.67 | 21.66 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.37 | 285.83 | 21.24 | 285.83 | 21.17 |
February | 671.67 | 21.48 | 156.67 | 21.38 | 156.67 | 21.31 |
March | 742.67 | 21.60 | 29.67 | 21.57 | 29.67 | 21.55 |
April | 704.83 | 21.69 | 2.33 | 21.69 | 2.33 | 21.69 |
May | 673.17 | 21.56 | 6.00 | 21.57 | 1.83 | 21.57 |
June | 565.67 | 21.32 | 26.50 | 21.41 | 0.00 | 21.41 |
July | 536.83 | 21.16 | 125.17 | 21.57 | 1.17 | 21.58 |
August | 540.50 | 21.17 | 136.17 | 21.61 | 0.00 | 21.61 |
September | 552.83 | 21.27 | 74.50 | 21.51 | 0.33 | 21.52 |
October | 670.50 | 21.49 | 47.50 | 21.52 | 29.00 | 21.49 |
November | 714.67 | 21.56 | 63.67 | 21.51 | 63.67 | 21.46 |
December | 744.00 | 21.38 | 345.00 | 21.25 | 345.00 | 21.18 |
Annual Sum or Average | 7861.33 | 21.44 | 1299.00 | 21.47 | 915.50 | 21.42 |
Minimum of Months | 536.83 | 21.16 | 2.33 | 21.24 | 0.00 | 21.17 |
Maximum of Months | 744.00 | 21.69 | 345.00 | 21.69 | 345.00 | 21.69 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.91 | 585.33 | 20.88 | 585.33 | 20.87 |
February | 672.00 | 21.07 | 348.67 | 21.00 | 348.67 | 20.97 |
March | 744.00 | 21.47 | 80.67 | 21.43 | 80.67 | 21.40 |
April | 713.00 | 21.69 | 11.17 | 21.69 | 11.17 | 21.68 |
May | 689.67 | 21.60 | 7.33 | 21.61 | 2.83 | 21.61 |
June | 573.17 | 21.35 | 21.50 | 21.42 | 0.00 | 21.42 |
July | 537.50 | 21.17 | 67.00 | 21.41 | 1.17 | 21.41 |
August | 544.67 | 21.19 | 43.50 | 21.35 | 0.00 | 21.35 |
September | 580.17 | 21.35 | 6.67 | 21.37 | 0.50 | 21.37 |
October | 713.50 | 21.51 | 55.33 | 21.47 | 54.33 | 21.43 |
November | 720.00 | 21.20 | 241.17 | 21.15 | 241.17 | 21.11 |
December | 744.00 | 20.81 | 641.00 | 20.79 | 641.00 | 20.78 |
Annual Sum or Average | 7975.67 | 21.28 | 2109.33 | 21.22 | 1966.83 | 21.16 |
Minimum of Months | 537.50 | 20.81 | 6.67 | 20.79 | 0.00 | 20.78 |
Maximum of Months | 744.00 | 21.69 | 641.00 | 21.69 | 641.00 | 21.68 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.99 | 0.00 | 21.99 | 0.00 | 21.99 |
February | 672.00 | 22.21 | 0.00 | 22.21 | 0.00 | 22.21 |
March | 744.00 | 22.75 | 0.00 | 22.75 | 0.00 | 22.75 |
April | 719.67 | 23.42 | 0.00 | 23.42 | 0.00 | 23.42 |
May | 599.33 | 23.64 | 8.00 | 23.64 | 0.33 | 23.64 |
June | 263.50 | 23.87 | 99.17 | 23.90 | 27.17 | 23.90 |
July | 330.17 | 23.99 | 647.67 | 23.99 | 330.17 | 23.99 |
August | 229.33 | 23.98 | 595.67 | 23.98 | 229.33 | 23.98 |
September | 156.00 | 23.90 | 232.17 | 23.93 | 77.67 | 23.93 |
October | 547.33 | 23.43 | 59.00 | 23.48 | 6.00 | 23.49 |
November | 720.00 | 22.81 | 0.00 | 22.81 | 0.00 | 22.81 |
December | 744.00 | 21.89 | 0.00 | 21.89 | 0.00 | 21.89 |
Annual Sum or Average | 6469.33 | 22.91 | 1641.67 | 23.13 | 670.67 | 23.19 |
Minimum of Months | 156.00 | 21.89 | 0.00 | 21.89 | 0.00 | 21.89 |
Maximum of Months | 744.00 | 23.99 | 647.67 | 23.99 | 330.17 | 23.99 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 739.50 | 21.21 | 462.83 | 21.08 | 462.83 | 21.03 |
February | 657.50 | 21.30 | 294.83 | 21.18 | 294.83 | 21.11 |
March | 727.50 | 21.39 | 175.33 | 21.30 | 175.33 | 21.24 |
April | 690.83 | 21.53 | 58.00 | 21.49 | 58.00 | 21.46 |
May | 682.67 | 21.47 | 24.17 | 21.48 | 17.50 | 21.47 |
June | 594.17 | 21.37 | 43.83 | 21.50 | 1.33 | 21.50 |
July | 562.50 | 21.27 | 123.83 | 21.60 | 12.67 | 21.61 |
August | 557.17 | 21.24 | 130.17 | 21.60 | 11.83 | 21.60 |
September | 562.83 | 21.26 | 94.17 | 21.53 | 9.00 | 21.52 |
October | 667.83 | 21.38 | 98.00 | 21.39 | 74.33 | 21.34 |
November | 701.67 | 21.38 | 222.50 | 21.28 | 221.67 | 21.22 |
December | 742.33 | 21.22 | 466.50 | 21.09 | 466.50 | 21.03 |
Annual Sum or Average | 7886.50 | 21.34 | 2194.17 | 21.34 | 1805.83 | 21.27 |
Minimum of Months | 557.17 | 21.21 | 24.17 | 21.08 | 1.33 | 21.03 |
Maximum of Months | 742.33 | 21.53 | 466.50 | 21.60 | 466.50 | 21.61 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.77 | 670.67 | 20.73 | 670.67 | 20.72 |
February | 672.00 | 20.95 | 488.50 | 20.87 | 488.50 | 20.83 |
March | 744.00 | 21.20 | 289.83 | 21.12 | 289.83 | 21.07 |
April | 710.83 | 21.49 | 76.50 | 21.45 | 76.50 | 21.41 |
May | 698.50 | 21.49 | 25.17 | 21.49 | 21.17 | 21.47 |
June | 600.17 | 21.40 | 38.83 | 21.51 | 1.67 | 21.51 |
July | 567.00 | 21.28 | 102.33 | 21.57 | 11.33 | 21.57 |
August | 579.00 | 21.28 | 97.83 | 21.54 | 13.17 | 21.54 |
September | 611.33 | 21.37 | 55.17 | 21.49 | 14.17 | 21.48 |
October | 718.17 | 21.31 | 137.67 | 21.25 | 131.17 | 21.18 |
November | 720.00 | 21.05 | 461.83 | 20.97 | 461.83 | 20.93 |
December | 744.00 | 20.72 | 688.67 | 20.69 | 688.67 | 20.68 |
Annual Sum or Average | 8109.00 | 21.18 | 3133.00 | 21.13 | 2868.67 | 21.05 |
Minimum of Months | 567.00 | 20.72 | 25.17 | 20.69 | 1.67 | 20.68 |
Maximum of Months | 744.00 | 21.49 | 688.67 | 21.57 | 688.67 | 21.57 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 662.17 | 21.31 | 139.50 | 21.25 | 137.50 | 21.20 |
February | 596.33 | 21.37 | 68.50 | 21.32 | 68.50 | 21.29 |
March | 683.17 | 21.42 | 25.17 | 21.41 | 25.00 | 21.39 |
April | 703.50 | 21.60 | 5.67 | 21.60 | 5.67 | 21.59 |
May | 718.17 | 21.57 | 6.83 | 21.57 | 6.83 | 21.56 |
June | 650.00 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
July | 599.83 | 21.34 | 28.67 | 21.42 | 7.83 | 21.42 |
August | 585.83 | 21.29 | 94.00 | 21.56 | 4.00 | 21.56 |
September | 573.33 | 21.31 | 108.50 | 21.63 | 1.17 | 21.63 |
October | 618.50 | 21.34 | 83.50 | 21.48 | 26.67 | 21.46 |
November | 622.33 | 21.37 | 32.33 | 21.37 | 24.67 | 21.35 |
December | 647.00 | 21.27 | 180.17 | 21.21 | 179.00 | 21.17 |
Annual Sum or Average | 7660.17 | 21.40 | 772.83 | 21.44 | 486.83 | 21.41 |
Minimum of Months | 573.33 | 21.27 | 0.00 | 21.21 | 0.00 | 21.17 |
Maximum of Months | 718.17 | 21.60 | 180.17 | 21.63 | 179.00 | 21.63 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 717.67 | 22.57 | 0.17 | 22.57 | 0.00 | 22.57 |
February | 603.83 | 22.66 | 2.00 | 22.67 | 0.00 | 22.67 |
March | 539.50 | 22.82 | 15.67 | 22.86 | 0.00 | 22.86 |
April | 385.33 | 22.95 | 24.17 | 23.01 | 0.00 | 23.01 |
May | 180.00 | 22.91 | 244.67 | 23.43 | 8.83 | 23.44 |
June | 65.00 | 23.57 | 551.83 | 23.77 | 47.83 | 23.78 |
July | 400.17 | 23.81 | 742.67 | 23.75 | 400.17 | 23.76 |
August | 298.17 | 23.76 | 735.83 | 23.70 | 298.00 | 23.71 |
September | 153.00 | 23.32 | 574.17 | 23.62 | 109.67 | 23.63 |
October | 395.33 | 22.77 | 177.50 | 23.10 | 16.50 | 23.12 |
November | 604.17 | 22.74 | 12.67 | 22.77 | 0.00 | 22.77 |
December | 728.83 | 22.58 | 0.00 | 22.58 | 0.00 | 22.58 |
Annual Sum or Average | 5071.00 | 22.89 | 3081.33 | 23.21 | 881.00 | 23.27 |
Minimum of Months | 65.00 | 22.57 | 0.00 | 22.57 | 0.00 | 22.57 |
Maximum of Months | 728.83 | 23.81 | 742.67 | 23.77 | 400.17 | 23.78 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 608.00 | 22.81 | 1.67 | 22.82 | 0.00 | 22.82 |
February | 468.00 | 22.85 | 13.83 | 22.90 | 0.00 | 22.90 |
March | 364.00 | 22.94 | 49.67 | 23.08 | 0.00 | 23.08 |
April | 204.67 | 23.01 | 69.00 | 23.26 | 0.00 | 23.26 |
May | 91.67 | 23.05 | 363.17 | 23.69 | 7.83 | 23.69 |
June | 49.17 | 23.83 | 650.67 | 23.85 | 44.33 | 23.85 |
July | 392.17 | 23.90 | 744.00 | 23.87 | 392.17 | 23.88 |
August | 291.50 | 23.86 | 743.67 | 23.82 | 291.50 | 23.83 |
September | 113.83 | 23.71 | 644.50 | 23.77 | 105.67 | 23.77 |
October | 257.00 | 22.83 | 242.00 | 23.31 | 13.33 | 23.33 |
November | 446.67 | 22.85 | 44.33 | 22.95 | 0.00 | 22.95 |
December | 638.83 | 22.85 | 0.50 | 22.85 | 0.00 | 22.85 |
Annual Sum or Average | 3925.50 | 23.08 | 3567.00 | 23.44 | 854.83 | 23.49 |
Minimum of Months | 49.17 | 22.81 | 0.50 | 22.82 | 0.00 | 22.82 |
Maximum of Months | 638.83 | 23.90 | 744.00 | 23.87 | 392.17 | 23.88 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 486.17 | 24.25 | 744.00 | 24.20 | 486.17 | 24.21 |
February | 457.83 | 24.26 | 672.00 | 24.21 | 457.83 | 24.22 |
March | 521.00 | 24.14 | 744.00 | 24.12 | 521.00 | 24.13 |
April | 512.67 | 24.08 | 718.17 | 24.07 | 512.67 | 24.07 |
May | 539.50 | 24.00 | 743.33 | 24.00 | 539.50 | 24.00 |
June | 556.50 | 23.99 | 720.00 | 23.99 | 556.50 | 23.99 |
July | 663.00 | 23.99 | 744.00 | 23.99 | 663.00 | 23.99 |
August | 631.50 | 23.99 | 744.00 | 23.99 | 631.50 | 23.99 |
September | 558.17 | 23.99 | 720.00 | 23.99 | 558.17 | 23.99 |
October | 529.17 | 24.07 | 743.83 | 24.06 | 529.17 | 24.07 |
November | 498.50 | 24.21 | 720.00 | 24.19 | 498.50 | 24.19 |
December | 480.00 | 24.31 | 742.17 | 24.25 | 480.00 | 24.26 |
Annual Sum or Average | 6434.00 | 24.10 | 8755.50 | 24.09 | 6434.00 | 24.09 |
Minimum of Months | 457.83 | 23.99 | 672.00 | 23.99 | 457.83 | 23.99 |
Maximum of Months | 663.00 | 24.31 | 744.00 | 24.25 | 663.00 | 24.26 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.76 | 0.00 | 21.76 | 0.00 | 21.76 |
February | 672.00 | 22.10 | 0.00 | 22.10 | 0.00 | 22.10 |
March | 742.50 | 22.78 | 0.00 | 22.78 | 0.00 | 22.78 |
April | 654.00 | 23.49 | 0.00 | 23.49 | 0.00 | 23.49 |
May | 409.00 | 23.58 | 46.83 | 23.62 | 0.00 | 23.62 |
June | 113.67 | 23.81 | 252.17 | 23.93 | 15.00 | 23.93 |
July | 197.50 | 23.99 | 691.33 | 24.00 | 197.50 | 24.00 |
August | 132.50 | 23.99 | 687.17 | 23.99 | 132.50 | 23.99 |
September | 111.50 | 23.82 | 377.83 | 23.95 | 48.83 | 23.95 |
October | 478.17 | 23.21 | 83.50 | 23.33 | 0.00 | 23.33 |
November | 709.50 | 22.62 | 0.00 | 22.62 | 0.00 | 22.62 |
December | 744.00 | 21.68 | 5.50 | 21.67 | 5.50 | 21.67 |
Annual Sum or Average | 5708.33 | 22.69 | 2144.33 | 23.04 | 399.33 | 23.09 |
Minimum of Months | 111.50 | 21.68 | 0.00 | 21.67 | 0.00 | 21.67 |
Maximum of Months | 744.00 | 23.99 | 691.33 | 24.00 | 197.50 | 24.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.95101 | 21.24001 | 0.19797 | 5.86348 |
February | 672.00000 | 23.88319 | 22.74551 | 0.18211 | 5.77253 |
March | 744.00000 | 23.74196 | 21.85861 | 0.13555 | 5.49913 |
April | 720.00000 | 23.70269 | 18.70218 | 0.10454 | 5.35281 |
May | 744.00000 | 23.73914 | 26.94173 | -0.7699 | 17.73246 |
June | 720.00000 | 23.83789 | 36.49029 | -0.6599 | 14.33541 |
July | 744.00000 | 23.90081 | 50.56385 | -0.5287 | 10.94776 |
August | 744.00000 | 23.94434 | 48.87195 | -0.5155 | 10.61731 |
September | 720.00000 | 23.98280 | 41.02075 | -0.5444 | 11.29481 |
October | 744.00000 | 23.99088 | 26.72570 | 0.26701 | 6.58248 |
November | 720.00000 | 24.00166 | 20.93440 | 0.22619 | 6.10229 |
December | 744.00000 | 23.99630 | 19.09281 | 0.20550 | 5.90781 |
Annual Sum or Average | 8760.00000 | 23.88953 | 29.65873 | -0.1434 | 8.85439 |
Minimum of Months | 672.00000 | 23.70269 | 18.70218 | -0.7699 | 5.35281 |
Maximum of Months | 744.00000 | 24.00166 | 50.56385 | 0.26701 | 17.73246 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.40918 | 22.73465 | -0.1085 | 8.14775 |
February | 672.00000 | 22.62262 | 23.70694 | -0.0369 | 7.65612 |
March | 744.00000 | 22.80100 | 22.41045 | -0.0025 | 6.82284 |
April | 720.00000 | 23.32552 | 18.53496 | 0.11095 | 6.39588 |
May | 744.00000 | 23.44227 | 26.85650 | -0.7409 | 18.24363 |
June | 720.00000 | 23.79250 | 35.86673 | -0.5161 | 11.47297 |
July | 744.00000 | 23.97052 | 49.66818 | -0.3170 | 7.37182 |
August | 744.00000 | 23.96264 | 48.27723 | -0.3084 | 7.44840 |
September | 720.00000 | 23.86789 | 41.25066 | -0.3885 | 9.27635 |
October | 744.00000 | 23.47785 | 27.50901 | 0.26005 | 8.33552 |
November | 720.00000 | 22.97955 | 22.41831 | 0.06563 | 7.34897 |
December | 744.00000 | 22.46204 | 20.68401 | -0.1020 | 8.26743 |
Annual Sum or Average | 8760.00000 | 23.26216 | 30.05001 | -0.1747 | 8.91221 |
Minimum of Months | 672.00000 | 22.40918 | 18.53496 | -0.7409 | 6.39588 |
Maximum of Months | 744.00000 | 23.97052 | 49.66818 | 0.26005 | 18.24363 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.72065 | 23.36180 | -0.0649 | 5.49597 |
February | 672.00000 | 22.91650 | 24.28632 | -0.0074 | 5.34611 |
March | 744.00000 | 23.16658 | 22.79367 | 0.04870 | 5.34536 |
April | 720.00000 | 23.47665 | 19.12112 | 0.11075 | 5.50071 |
May | 744.00000 | 23.56641 | 27.34964 | -0.7402 | 17.08206 |
June | 720.00000 | 23.78309 | 36.63304 | -0.5811 | 12.40517 |
July | 744.00000 | 23.89153 | 50.74606 | -0.4355 | 9.06136 |
August | 744.00000 | 23.89883 | 49.36378 | -0.4420 | 9.17664 |
September | 720.00000 | 23.85082 | 42.19879 | -0.5180 | 10.76955 |
October | 744.00000 | 23.57373 | 28.41280 | 0.20474 | 6.34364 |
November | 720.00000 | 23.22840 | 23.09444 | 0.06643 | 5.35731 |
December | 744.00000 | 22.75054 | 21.41307 | -0.0703 | 5.41271 |
Annual Sum or Average | 8760.00000 | 23.40396 | 30.78933 | -0.2037 | 8.12636 |
Minimum of Months | 672.00000 | 22.72065 | 19.12112 | -0.7402 | 5.34536 |
Maximum of Months | 744.00000 | 23.89883 | 50.74606 | 0.20474 | 17.08206 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 24.07336 | 17.86721 | 0.79094 | 19.32501 |
February | 672.00000 | 24.08289 | 18.94560 | 0.81240 | 20.06454 |
March | 744.00000 | 24.04596 | 17.72068 | 0.82224 | 20.17108 |
April | 720.00000 | 24.02949 | 14.58219 | 0.82598 | 20.21787 |
May | 744.00000 | 23.99553 | 22.84572 | 0.26373 | 8.20634 |
June | 720.00000 | 23.99770 | 32.58518 | 0.37455 | 9.72872 |
July | 744.00000 | 24.00074 | 46.96653 | 0.49014 | 11.61311 |
August | 744.00000 | 24.00097 | 45.58661 | 0.47622 | 11.39382 |
September | 720.00000 | 23.99881 | 38.17016 | 0.39455 | 9.81603 |
October | 744.00000 | 24.02053 | 23.91666 | 0.88592 | 22.44564 |
November | 720.00000 | 24.08324 | 18.05088 | 0.82218 | 20.19333 |
December | 744.00000 | 24.07874 | 16.12721 | 0.77876 | 18.90979 |
Annual Sum or Average | 8760.00000 | 24.03367 | 26.17556 | 0.64387 | 15.98492 |
Minimum of Months | 672.00000 | 23.99553 | 14.58219 | 0.26373 | 8.20634 |
Maximum of Months | 744.00000 | 24.08324 | 46.96653 | 0.88592 | 22.44564 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.77282 | 25.58069 | 0.06789 | 7.18179 |
February | 672.00000 | 22.94678 | 26.58184 | 0.12887 | 7.07885 |
March | 744.00000 | 22.95095 | 25.39694 | 0.12001 | 6.51621 |
April | 720.00000 | 23.15435 | 21.94006 | 0.15936 | 6.26058 |
May | 744.00000 | 23.01763 | 30.79270 | -0.7629 | 18.38024 |
June | 720.00000 | 23.27782 | 40.43777 | -0.5714 | 12.84541 |
July | 744.00000 | 23.58750 | 54.42833 | -0.3327 | 7.75673 |
August | 744.00000 | 23.70288 | 52.62273 | -0.2843 | 7.37329 |
September | 720.00000 | 23.68597 | 45.17089 | -0.3354 | 8.63856 |
October | 744.00000 | 23.48810 | 30.88430 | 0.35112 | 9.09492 |
November | 720.00000 | 23.20285 | 25.38527 | 0.20751 | 7.49262 |
December | 744.00000 | 22.87470 | 23.55081 | 0.08649 | 7.28107 |
Annual Sum or Average | 8760.00000 | 23.22294 | 33.62538 | -0.0986 | 8.83955 |
Minimum of Months | 672.00000 | 22.77282 | 21.94006 | -0.7629 | 6.26058 |
Maximum of Months | 744.00000 | 23.70288 | 54.42833 | 0.35112 | 18.38024 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.28341 | 25.49934 | 0.10474 | 5.62655 |
February | 672.00000 | 23.42002 | 26.43395 | 0.14954 | 5.71811 |
March | 744.00000 | 23.51550 | 25.09361 | 0.16941 | 5.83945 |
April | 720.00000 | 23.61253 | 21.56922 | 0.18235 | 5.88101 |
May | 744.00000 | 23.60575 | 29.80840 | -0.6771 | 15.13968 |
June | 720.00000 | 23.73304 | 39.11475 | -0.5434 | 11.53417 |
July | 744.00000 | 23.84217 | 53.14901 | -0.3921 | 8.32893 |
August | 744.00000 | 23.87988 | 51.65735 | -0.3860 | 8.20179 |
September | 720.00000 | 23.89362 | 44.34062 | -0.4390 | 9.15849 |
October | 744.00000 | 23.79169 | 30.53152 | 0.30377 | 7.23325 |
November | 720.00000 | 23.64943 | 25.23862 | 0.20860 | 6.11353 |
December | 744.00000 | 23.36210 | 23.60095 | 0.11154 | 5.54726 |
Annual Sum or Average | 8760.00000 | 23.63319 | 33.06190 | -0.1022 | 7.87438 |
Minimum of Months | 672.00000 | 23.28341 | 21.56922 | -0.6771 | 5.54726 |
Maximum of Months | 744.00000 | 23.89362 | 53.14901 | 0.30377 | 15.13968 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.31762 | 25.91036 | -0.4636 | 10.63572 |
February | 672.00000 | 21.42190 | 27.31058 | -0.4009 | 9.53119 |
March | 744.00000 | 21.50940 | 26.67307 | -0.3453 | 8.46602 |
April | 720.00000 | 21.64080 | 23.47382 | -0.2691 | 7.61141 |
May | 744.00000 | 21.65574 | 32.36488 | -1.2897 | 41.02108 |
June | 720.00000 | 21.70925 | 40.93820 | -1.1478 | 34.37241 |
July | 744.00000 | 21.73788 | 47.78774 | -1.0692 | 30.92514 |
August | 744.00000 | 21.73140 | 47.90319 | -1.0695 | 31.01919 |
September | 720.00000 | 21.71041 | 45.81972 | -1.1239 | 33.60292 |
October | 744.00000 | 21.62252 | 33.51021 | -0.2064 | 7.32016 |
November | 720.00000 | 21.51348 | 27.62921 | -0.3479 | 8.64513 |
December | 744.00000 | 21.32210 | 24.12311 | -0.4772 | 10.93534 |
Annual Sum or Average | 8760.00000 | 21.57487 | 33.66294 | -0.6861 | 19.57214 |
Minimum of Months | 672.00000 | 21.31762 | 23.47382 | -1.2897 | 7.32016 |
Maximum of Months | 744.00000 | 21.73788 | 47.90319 | -0.2064 | 41.02108 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.90836 | 26.41091 | -0.6190 | 13.51793 |
February | 672.00000 | 21.06059 | 27.77278 | -0.5419 | 11.81176 |
March | 744.00000 | 21.30449 | 26.92758 | -0.4328 | 9.48331 |
April | 720.00000 | 21.55555 | 23.57897 | -0.3137 | 7.93481 |
May | 744.00000 | 21.63218 | 32.39031 | -1.3098 | 41.90279 |
June | 720.00000 | 21.70964 | 40.93945 | -1.1473 | 34.28715 |
July | 744.00000 | 21.73803 | 47.92724 | -1.0755 | 31.11132 |
August | 744.00000 | 21.72314 | 48.41697 | -1.0933 | 31.86798 |
September | 720.00000 | 21.68006 | 46.52613 | -1.1805 | 35.81759 |
October | 744.00000 | 21.45465 | 33.95043 | -0.2982 | 7.96587 |
November | 720.00000 | 21.19412 | 28.02506 | -0.4867 | 10.49654 |
December | 744.00000 | 20.84301 | 24.68269 | -0.6540 | 14.47402 |
Annual Sum or Average | 8760.00000 | 21.40164 | 34.00443 | -0.7643 | 20.95022 |
Minimum of Months | 672.00000 | 20.84301 | 23.57897 | -1.3098 | 7.93481 |
Maximum of Months | 744.00000 | 21.73803 | 48.41697 | -0.2982 | 41.90279 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.90855 | 25.36504 | -0.6075 | 12.82968 |
February | 672.00000 | 20.98511 | 26.75770 | -0.5682 | 11.85919 |
March | 744.00000 | 21.16056 | 25.70727 | -0.4983 | 10.24242 |
April | 720.00000 | 21.33840 | 22.32182 | -0.4404 | 9.25650 |
May | 744.00000 | 21.44812 | 31.08480 | -1.4912 | 50.59878 |
June | 720.00000 | 21.60099 | 40.28270 | -1.3413 | 42.94550 |
July | 744.00000 | 21.65782 | 49.35182 | -1.2559 | 38.78065 |
August | 744.00000 | 21.60337 | 49.74401 | -1.2865 | 40.17887 |
September | 720.00000 | 21.47859 | 46.25365 | -1.3830 | 44.94361 |
October | 744.00000 | 21.24707 | 32.96933 | -0.4124 | 8.88626 |
November | 720.00000 | 21.04292 | 26.97735 | -0.5412 | 11.23024 |
December | 744.00000 | 20.85842 | 23.74657 | -0.6336 | 13.58539 |
Annual Sum or Average | 8760.00000 | 21.27894 | 33.42826 | -0.8735 | 24.68903 |
Minimum of Months | 672.00000 | 20.85842 | 22.32182 | -1.4912 | 8.88626 |
Maximum of Months | 744.00000 | 21.65782 | 49.74401 | -0.4124 | 50.59878 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.36762 | 25.84217 | -0.4542 | 10.48400 |
February | 672.00000 | 21.47617 | 27.22066 | -0.3943 | 9.40107 |
March | 744.00000 | 21.59869 | 26.56974 | -0.3156 | 8.21084 |
April | 720.00000 | 21.72641 | 23.44019 | -0.2299 | 7.41797 |
May | 744.00000 | 21.73143 | 32.10442 | -1.2405 | 38.84866 |
June | 720.00000 | 21.74702 | 40.70609 | -1.1109 | 32.87245 |
July | 744.00000 | 21.75590 | 47.31194 | -1.0378 | 29.72026 |
August | 744.00000 | 21.75427 | 47.53925 | -1.0428 | 30.00100 |
September | 720.00000 | 21.74345 | 45.57019 | -1.1053 | 32.84410 |
October | 744.00000 | 21.67390 | 33.40937 | -0.1912 | 7.27553 |
November | 720.00000 | 21.56995 | 27.55280 | -0.3350 | 8.52178 |
December | 744.00000 | 21.37888 | 24.05093 | -0.4668 | 10.64973 |
Annual Sum or Average | 8760.00000 | 21.62745 | 33.48471 | -0.6622 | 18.91455 |
Minimum of Months | 672.00000 | 21.36762 | 23.44019 | -1.2405 | 7.27553 |
Maximum of Months | 744.00000 | 21.75590 | 47.53925 | -0.1912 | 38.84866 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.90670 | 26.35400 | -0.6201 | 13.38872 |
February | 672.00000 | 21.07185 | 27.68943 | -0.5448 | 11.66933 |
March | 744.00000 | 21.47009 | 26.68077 | -0.3874 | 8.85094 |
April | 720.00000 | 21.71006 | 23.45239 | -0.2602 | 7.57100 |
May | 744.00000 | 21.72784 | 32.12438 | -1.2549 | 39.43654 |
June | 720.00000 | 21.74736 | 40.74481 | -1.1109 | 32.81599 |
July | 744.00000 | 21.75586 | 47.47888 | -1.0441 | 29.90853 |
August | 744.00000 | 21.75232 | 47.89970 | -1.0651 | 30.77566 |
September | 720.00000 | 21.73391 | 46.15934 | -1.1553 | 34.74568 |
October | 744.00000 | 21.58284 | 33.64533 | -0.2674 | 7.69200 |
November | 720.00000 | 21.20045 | 27.95202 | -0.4833 | 10.31446 |
December | 744.00000 | 20.80770 | 24.63798 | -0.6615 | 14.52051 |
Annual Sum or Average | 8760.00000 | 21.45717 | 33.77538 | -0.7393 | 20.19703 |
Minimum of Months | 672.00000 | 20.80770 | 23.45239 | -1.2549 | 7.57100 |
Maximum of Months | 744.00000 | 21.75586 | 47.89970 | -0.2602 | 39.43654 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.22069 | 26.23453 | -0.5282 | 12.16839 |
February | 672.00000 | 21.33984 | 27.64804 | -0.4568 | 10.80285 |
March | 744.00000 | 21.43581 | 26.91522 | -0.3951 | 9.47449 |
April | 720.00000 | 21.60403 | 23.54811 | -0.2974 | 8.20453 |
May | 744.00000 | 21.62660 | 32.70988 | -1.3147 | 42.52975 |
June | 720.00000 | 21.70025 | 41.38472 | -1.1475 | 34.72029 |
July | 744.00000 | 21.73619 | 48.34732 | -1.0581 | 30.77683 |
August | 744.00000 | 21.72607 | 48.55774 | -1.0626 | 31.07179 |
September | 720.00000 | 21.69266 | 46.58939 | -1.1367 | 34.53660 |
October | 744.00000 | 21.57423 | 33.88194 | -0.2418 | 8.00770 |
November | 720.00000 | 21.43274 | 27.88023 | -0.4071 | 9.80397 |
December | 744.00000 | 21.22556 | 24.38893 | -0.5422 | 12.53490 |
Annual Sum or Average | 8760.00000 | 21.52686 | 34.05019 | -0.7175 | 20.44910 |
Minimum of Months | 672.00000 | 21.22069 | 23.54811 | -1.3147 | 8.00770 |
Maximum of Months | 744.00000 | 21.73619 | 48.55774 | -0.2418 | 42.52975 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.77460 | 26.78784 | -0.6956 | 15.69457 |
February | 672.00000 | 20.94688 | 28.16251 | -0.6097 | 13.57215 |
March | 744.00000 | 21.20401 | 27.21437 | -0.4925 | 10.79184 |
April | 720.00000 | 21.51427 | 23.66402 | -0.3451 | 8.59810 |
May | 744.00000 | 21.60355 | 32.73936 | -1.3357 | 43.43541 |
June | 720.00000 | 21.70108 | 41.38621 | -1.1470 | 34.62651 |
July | 744.00000 | 21.73695 | 48.47141 | -1.0644 | 30.94852 |
August | 744.00000 | 21.71737 | 49.06755 | -1.0875 | 31.91950 |
September | 720.00000 | 21.66181 | 47.35697 | -1.1961 | 36.82985 |
October | 744.00000 | 21.38056 | 34.40373 | -0.3445 | 8.89006 |
November | 720.00000 | 21.04762 | 28.35506 | -0.5671 | 12.36368 |
December | 744.00000 | 20.71771 | 24.99215 | -0.7300 | 16.72612 |
Annual Sum or Average | 8760.00000 | 21.33543 | 34.42572 | -0.8027 | 22.09082 |
Minimum of Months | 672.00000 | 20.71771 | 23.66402 | -1.3357 | 8.59810 |
Maximum of Months | 744.00000 | 21.73695 | 49.06755 | -0.3445 | 43.43541 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.53660 | 27.69042 | -0.3378 | 9.30483 |
February | 672.00000 | 21.58982 | 29.06843 | -0.3029 | 8.71361 |
March | 744.00000 | 21.57983 | 28.17322 | -0.3118 | 8.39341 |
April | 720.00000 | 21.64165 | 24.70393 | -0.2951 | 8.08414 |
May | 744.00000 | 21.63173 | 33.14378 | -1.3677 | 44.92311 |
June | 720.00000 | 21.68869 | 41.60970 | -1.2446 | 38.85026 |
July | 744.00000 | 21.72565 | 48.61398 | -1.1411 | 34.09377 |
August | 744.00000 | 21.72153 | 48.55536 | -1.1251 | 33.60302 |
September | 720.00000 | 21.71288 | 46.16683 | -1.1417 | 34.85049 |
October | 744.00000 | 21.67264 | 34.46961 | -0.1709 | 7.45907 |
November | 720.00000 | 21.63227 | 29.51330 | -0.2569 | 8.14739 |
December | 744.00000 | 21.54198 | 26.08367 | -0.3357 | 9.34761 |
Annual Sum or Average | 8760.00000 | 21.63969 | 34.85578 | -0.6716 | 20.55567 |
Minimum of Months | 672.00000 | 21.53660 | 24.70393 | -1.3677 | 7.45907 |
Maximum of Months | 744.00000 | 21.72565 | 48.61398 | -0.1709 | 44.92311 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.62546 | 25.88350 | -0.0371 | 5.61877 |
February | 672.00000 | 22.79562 | 26.83887 | 0.02501 | 5.59416 |
March | 744.00000 | 23.11472 | 25.19551 | 0.12193 | 5.76910 |
April | 720.00000 | 23.37820 | 21.59351 | 0.19956 | 6.18496 |
May | 744.00000 | 23.51232 | 29.81082 | -0.5792 | 12.70971 |
June | 720.00000 | 23.66826 | 39.31097 | -0.4133 | 8.97720 |
July | 744.00000 | 23.71769 | 53.71537 | -0.2813 | 6.85452 |
August | 744.00000 | 23.66263 | 52.55774 | -0.3206 | 7.41278 |
September | 720.00000 | 23.51897 | 45.57059 | -0.4548 | 9.81502 |
October | 744.00000 | 23.21248 | 31.45077 | 0.21746 | 6.70631 |
November | 720.00000 | 22.93090 | 25.75439 | 0.06458 | 5.68650 |
December | 744.00000 | 22.60733 | 23.99580 | -0.0584 | 5.68972 |
Annual Sum or Average | 8760.00000 | 23.23068 | 33.53224 | -0.1273 | 7.26064 |
Minimum of Months | 672.00000 | 22.60733 | 21.59351 | -0.5792 | 5.59416 |
Maximum of Months | 744.00000 | 23.71769 | 53.71537 | 0.21746 | 12.70971 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.01790 | 25.44827 | 0.08506 | 5.66445 |
February | 672.00000 | 23.16607 | 26.39048 | 0.14076 | 5.89247 |
March | 744.00000 | 23.42900 | 24.78376 | 0.22208 | 6.37122 |
April | 720.00000 | 23.60179 | 21.22326 | 0.27551 | 6.82927 |
May | 744.00000 | 23.69833 | 29.34065 | -0.4847 | 10.40308 |
June | 720.00000 | 23.80952 | 38.79272 | -0.3339 | 7.61246 |
July | 744.00000 | 23.85073 | 53.09977 | -0.2052 | 6.00176 |
August | 744.00000 | 23.80504 | 51.92904 | -0.2421 | 6.39442 |
September | 720.00000 | 23.67838 | 44.96128 | -0.3718 | 8.25240 |
October | 744.00000 | 23.43394 | 30.99499 | 0.29130 | 7.33046 |
November | 720.00000 | 23.24521 | 25.35450 | 0.16398 | 6.06629 |
December | 744.00000 | 23.00534 | 23.59751 | 0.06552 | 5.64307 |
Annual Sum or Average | 8760.00000 | 23.47985 | 33.05178 | -0.0338 | 6.87634 |
Minimum of Months | 672.00000 | 23.00534 | 21.22326 | -0.4847 | 5.64307 |
Maximum of Months | 744.00000 | 23.85073 | 53.09977 | 0.29130 | 10.40308 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 24.16487 | 24.70859 | 0.98443 | 27.25886 |
February | 672.00000 | 24.17633 | 25.62400 | 1.01582 | 28.55970 |
March | 744.00000 | 24.11412 | 24.10454 | 1.03675 | 29.24590 |
April | 720.00000 | 24.07034 | 20.85197 | 1.06368 | 30.56171 |
May | 744.00000 | 24.00340 | 28.70596 | 0.58532 | 16.15897 |
June | 720.00000 | 23.99307 | 38.12285 | 0.71525 | 19.73427 |
July | 744.00000 | 23.99367 | 52.15586 | 0.83649 | 23.45880 |
August | 744.00000 | 23.99352 | 50.83041 | 0.81335 | 22.77099 |
September | 720.00000 | 23.99171 | 43.68462 | 0.70948 | 19.55080 |
October | 744.00000 | 24.05774 | 30.11322 | 1.10664 | 32.42212 |
November | 720.00000 | 24.16859 | 24.74709 | 1.02874 | 28.96274 |
December | 744.00000 | 24.20331 | 23.12088 | 0.97935 | 27.15405 |
Annual Sum or Average | 8760.00000 | 24.07698 | 32.28929 | 0.90567 | 25.46991 |
Minimum of Months | 672.00000 | 23.99171 | 20.85197 | 0.58532 | 16.15897 |
Maximum of Months | 744.00000 | 24.20331 | 52.15586 | 1.10664 | 32.42212 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.05033 | 21.85391 | -0.5010 | 10.27143 |
February | 672.00000 | 21.13296 | 23.08792 | -0.4674 | 9.62915 |
March | 744.00000 | 21.43167 | 21.38656 | -0.3957 | 8.35754 |
April | 720.00000 | 22.00638 | 17.23148 | -0.2794 | 6.84613 |
May | 744.00000 | 22.44086 | 25.75854 | -1.1718 | 34.28153 |
June | 720.00000 | 23.07145 | 35.12912 | -0.8918 | 22.22869 |
July | 744.00000 | 23.35708 | 49.58581 | -0.6952 | 15.24444 |
August | 744.00000 | 23.24081 | 48.53551 | -0.7433 | 16.74661 |
September | 720.00000 | 22.87095 | 41.64993 | -0.9177 | 22.96971 |
October | 744.00000 | 22.13800 | 27.31809 | -0.1816 | 6.37096 |
November | 720.00000 | 21.36138 | 21.86330 | -0.4098 | 8.63775 |
December | 744.00000 | 21.04362 | 19.77388 | -0.5153 | 10.57931 |
Annual Sum or Average | 8760.00000 | 22.10083 | 29.48838 | -0.5983 | 14.37669 |
Minimum of Months | 672.00000 | 21.04362 | 17.23148 | -1.1718 | 6.37096 |
Maximum of Months | 744.00000 | 23.35708 | 49.58581 | -0.1816 | 34.28153 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.99229 | 25.24507 | -0.2781 | 6.88253 |
February | 672.00000 | 22.21116 | 26.24047 | -0.2177 | 6.23158 |
March | 744.00000 | 22.75325 | 24.49795 | -0.0968 | 5.34943 |
April | 720.00000 | 23.41941 | 20.57377 | 0.04020 | 5.20859 |
May | 744.00000 | 23.67460 | 28.47145 | -0.7934 | 18.65086 |
June | 720.00000 | 23.91554 | 37.40726 | -0.6371 | 13.64730 |
July | 744.00000 | 23.99356 | 51.30404 | -0.5071 | 10.41054 |
August | 744.00000 | 23.98680 | 50.01850 | -0.5183 | 10.65023 |
September | 720.00000 | 23.94671 | 43.03770 | -0.5867 | 12.31027 |
October | 744.00000 | 23.56962 | 29.64413 | 0.14364 | 5.94774 |
November | 720.00000 | 22.80847 | 24.82240 | -0.0806 | 5.29346 |
December | 744.00000 | 21.88714 | 23.36424 | -0.3146 | 7.20119 |
Annual Sum or Average | 8760.00000 | 23.18409 | 32.10650 | -0.3215 | 9.00313 |
Minimum of Months | 672.00000 | 21.88714 | 20.57377 | -0.7934 | 5.20859 |
Maximum of Months | 744.00000 | 23.99356 | 51.30404 | 0.14364 | 18.65086 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.76014 | 23.68765 | -0.3328 | 7.73442 |
February | 672.00000 | 22.09799 | 24.57223 | -0.2404 | 6.83400 |
March | 744.00000 | 22.77791 | 22.60354 | -0.0828 | 5.57821 |
April | 720.00000 | 23.53325 | 18.42447 | 0.08410 | 5.47320 |
May | 744.00000 | 23.74913 | 26.17615 | -0.7265 | 16.75063 |
June | 720.00000 | 23.95436 | 35.15572 | -0.5606 | 11.77512 |
July | 744.00000 | 23.99799 | 49.11425 | -0.4296 | 8.91221 |
August | 744.00000 | 23.99422 | 47.88577 | -0.4436 | 9.18501 |
September | 720.00000 | 23.94478 | 41.02467 | -0.5313 | 11.11560 |
October | 744.00000 | 23.48605 | 27.75721 | 0.14263 | 6.27012 |
November | 720.00000 | 22.63875 | 23.08923 | -0.1143 | 5.73312 |
December | 744.00000 | 21.67915 | 21.72528 | -0.3641 | 8.12659 |
Annual Sum or Average | 8760.00000 | 23.13880 | 30.15422 | -0.3006 | 8.63983 |
Minimum of Months | 672.00000 | 21.67915 | 18.42447 | -0.7265 | 5.47320 |
Maximum of Months | 744.00000 | 23.99799 | 49.11425 | 0.14263 | 16.75063 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.77238 | 21.07546 | -0.3437 | 7.65878 |
February | 672.00000 | 22.00773 | 22.07422 | -0.2804 | 6.93030 |
March | 744.00000 | 22.64032 | 20.16515 | -0.1412 | 5.60313 |
April | 720.00000 | 23.30602 | 16.24751 | -0.0049 | 5.27118 |
May | 744.00000 | 23.69782 | 24.04255 | -0.7936 | 18.82496 |
June | 720.00000 | 23.95285 | 33.37450 | -0.6160 | 13.10560 |
July | 744.00000 | 23.99990 | 47.64098 | -0.4871 | 9.99736 |
August | 744.00000 | 23.99782 | 46.31781 | -0.5039 | 10.34222 |
September | 720.00000 | 23.96036 | 39.03587 | -0.5866 | 12.32485 |
October | 744.00000 | 23.37308 | 25.66427 | 0.07979 | 5.82339 |
November | 720.00000 | 22.52986 | 20.64435 | -0.1635 | 5.79461 |
December | 744.00000 | 21.70482 | 19.16023 | -0.3701 | 8.03066 |
Annual Sum or Average | 8760.00000 | 23.08345 | 28.00878 | -0.3516 | 9.16063 |
Minimum of Months | 672.00000 | 21.70482 | 16.24751 | -0.7936 | 5.27118 |
Maximum of Months | 744.00000 | 23.99990 | 47.64098 | 0.07979 | 18.82496 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.141236E+11 | 41991.26 | 01-JAN-16:03 | 502.01 | 0.447426E+11 | 0.00 | 0.588662E+11 | 2.15 | 3.19 | 13-JAN-21:03 | 0.00 | 0.00 |
February | 0.162602E+11 | 75723.09 | 13-FEB-16:03 | 495.27 | 0.518794E+11 | 0.00 | 0.681396E+11 | 2.35 | 3.81 | 15-FEB-16:01 | 0.00 | 0.00 |
March | 0.259639E+11 | 85977.29 | 08-MAR-16:01 | 602.05 | 0.804433E+11 | 0.00 | 0.106407E+12 | 2.55 | 3.83 | 12-MAR-15:02 | 0.00 | 0.00 |
April | 0.618914E+11 | 109260.07 | 28-APR-18:01 | 682.36 | 0.196396E+12 | 0.00 | 0.258287E+12 | 2.99 | 4.05 | 10-APR-18:01 | 0.00 | 0.00 |
May | 0.994842E+11 | 128013.73 | 19-MAY-18:03 | 737.56 | 0.317598E+12 | 0.00 | 0.417082E+12 | 3.12 | 4.01 | 25-MAY-18:02 | 0.00 | 0.00 |
June | 0.167029E+12 | 180669.20 | 28-JUN-15:03 | 719.93 | 0.523225E+12 | 0.00 | 0.690254E+12 | 3.12 | 3.97 | 09-JUN-18:01 | 0.00 | 0.00 |
July | 0.220584E+12 | 183260.19 | 21-JUL-18:03 | 744.00 | 0.711417E+12 | 0.00 | 0.932001E+12 | 3.22 | 4.37 | 31-JUL-18:02 | 0.00 | 0.00 |
August | 0.199584E+12 | 156282.87 | 20-AUG-15:13 | 744.00 | 0.651954E+12 | 0.00 | 0.851538E+12 | 3.24 | 4.20 | 29-AUG-18:01 | 0.00 | 0.00 |
September | 0.137979E+12 | 138612.79 | 20-SEP-15:01 | 719.93 | 0.454179E+12 | 0.00 | 0.592158E+12 | 3.21 | 3.99 | 26-SEP-18:01 | 0.00 | 0.00 |
October | 0.731515E+11 | 126235.60 | 06-OCT-15:01 | 699.05 | 0.240130E+12 | 0.00 | 0.313281E+12 | 3.00 | 4.14 | 02-OCT-18:01 | 0.00 | 0.00 |
November | 0.213597E+11 | 60068.77 | 02-NOV-15:01 | 589.49 | 0.675306E+11 | 0.00 | 0.888903E+11 | 2.60 | 3.76 | 02-NOV-15:01 | 0.00 | 0.00 |
December | 0.144577E+11 | 36761.77 | 29-DEC-16:04 | 493.43 | 0.460677E+11 | 0.00 | 0.605254E+11 | 2.11 | 3.19 | 23-DEC-17:47 | 0.00 | 0.00 |
Annual Sum or Average | 0.105187E+13 | 7729.08 | 0.338556E+13 | 0.00 | 0.443743E+13 | 2.81 | 0.00 | 0.00 | ||||
Minimum of Months | 0.141236E+11 | 36761.77 | 493.43 | 0.447426E+11 | 0.00 | 0.588662E+11 | 2.11 | 3.19 | 0.00 | 0.00 | ||
Maximum of Months | 0.220584E+12 | 183260.19 | 744.00 | 0.711417E+12 | 0.00 | 0.932001E+12 | 3.24 | 4.37 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.597341E+11 | 0.00 | 724.17 | 191774.38 | 22-JAN-19:02 | 0.00 | 54.13 | 79.95 | 0.21 | 0.00 | 0.05 | 0.45 | 22-JAN-19:02 |
February | 0.439857E+11 | 0.00 | 606.05 | 154213.39 | 09-FEB-23:43 | 0.00 | 54.43 | 77.84 | 0.17 | 0.00 | 0.04 | 0.36 | 09-FEB-23:43 |
March | 0.270379E+11 | 0.00 | 522.84 | 178089.02 | 22-MAR-08:62 | 0.00 | 51.94 | 70.71 | 0.10 | 0.00 | 0.02 | 0.42 | 22-MAR-08:62 |
April | 0.163124E+11 | 0.00 | 284.01 | 159267.09 | 04-APR-04:55 | 0.00 | 39.46 | 54.11 | 0.05 | 0.00 | 0.01 | 0.37 | 04-APR-04:55 |
May | 0.468376E+10 | 0.00 | 137.99 | 114393.96 | 05-MAY-03:43 | 0.00 | 40.99 | 47.84 | 0.01 | 0.00 | 0.00 | 0.27 | 05-MAY-03:43 |
June | 0.650353E+09 | 0.00 | 30.68 | 75887.48 | 09-JUN-05:00 | 0.00 | 47.23 | 48.65 | 0.00 | 0.00 | 0.00 | 0.18 | 09-JUN-05:00 |
July | 49925562.60 | 0.00 | 1.66 | 28275.87 | 10-JUL-08:04 | 0.00 | 57.56 | 57.61 | 0.00 | 0.00 | 0.00 | 0.07 | 10-JUL-08:04 |
August | 49186633.92 | 0.00 | 1.62 | 26727.58 | 09-AUG-08:04 | 0.00 | 60.10 | 60.14 | 0.00 | 0.00 | 0.00 | 0.06 | 09-AUG-08:04 |
September | 0.275334E+09 | 0.00 | 20.59 | 45429.34 | 27-SEP-18:04 | 0.00 | 53.08 | 53.85 | 0.00 | 0.00 | 0.00 | 0.11 | 27-SEP-18:04 |
October | 0.169919E+11 | 0.00 | 299.95 | 209280.07 | 25-OCT-15:01 | 0.00 | 47.24 | 59.54 | 0.05 | 0.00 | 0.01 | 0.49 | 25-OCT-15:01 |
November | 0.409056E+11 | 0.00 | 608.82 | 154563.99 | 05-NOV-08:03 | 0.00 | 52.95 | 75.39 | 0.15 | 0.00 | 0.04 | 0.36 | 05-NOV-08:03 |
December | 0.684509E+11 | 0.00 | 737.38 | 186518.85 | 15-DEC-16:03 | 0.00 | 53.77 | 80.43 | 0.24 | 0.00 | 0.06 | 0.44 | 15-DEC-16:03 |
Annual Sum or Average | 0.279127E+12 | 0.00 | 3975.75 | 0.00 | 51.08 | 63.79 | 0.08 | 0.00 | 0.02 | ||||
Minimum of Months | 49186633.92 | 0.00 | 1.62 | 26727.58 | 0.00 | 39.46 | 47.84 | 0.00 | 0.00 | 0.00 | 0.06 | ||
Maximum of Months | 0.684509E+11 | 0.00 | 737.38 | 209280.07 | 0.00 | 60.10 | 80.43 | 0.24 | 0.00 | 0.06 | 0.49 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.216634E+10 | 0.00 | 200.83 | 0.216634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55944.96 | 08-JAN-21:53 | 55944.96 | 08-JAN-21:53 | 0.00 | 0.00 | 0.00 |
February | 0.779789E+10 | 0.00 | 188.95 | 0.779789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 130423.66 | 14-FEB-15:10 | 130423.66 | 14-FEB-15:10 | 0.00 | 0.00 | 0.00 |
March | 0.252991E+11 | 0.00 | 234.79 | 0.252991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143110.82 | 08-MAR-14:00 | 143110.82 | 08-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.100748E+12 | 0.00 | 378.41 | 0.100748E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 200622.03 | 13-APR-18:04 | 200622.03 | 13-APR-18:04 | 0.00 | 0.00 | 0.00 |
May | 0.188588E+12 | 0.00 | 533.26 | 0.188588E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 234336.51 | 19-MAY-18:20 | 234336.51 | 19-MAY-18:20 | 0.00 | 0.00 | 0.00 |
June | 0.330153E+12 | 0.00 | 653.67 | 0.329888E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 276082.49 | 27-JUN-18:20 | 276082.49 | 27-JUN-18:20 | 0.00 | 0.00 | 0.00 |
July | 0.453353E+12 | 0.00 | 744.00 | 0.429361E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 352550.25 | 31-JUL-20:00 | 291723.87 | 21-JUL-18:20 | 0.00 | 0.00 | 0.00 |
August | 0.406181E+12 | 0.00 | 742.17 | 0.393532E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 296474.82 | 14-AUG-21:00 | 271441.33 | 18-AUG-18:20 | 0.00 | 0.00 | 0.00 |
September | 0.265232E+12 | 0.00 | 658.00 | 0.264216E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 237792.62 | 13-SEP-19:20 | 237792.62 | 13-SEP-19:20 | 0.00 | 0.00 | 0.00 |
October | 0.115092E+12 | 0.00 | 408.04 | 0.115009E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 208843.48 | 05-OCT-18:06 | 208843.48 | 05-OCT-18:06 | 0.00 | 0.00 | 0.00 |
November | 0.452953E+10 | 0.00 | 171.74 | 0.452953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69253.24 | 09-NOV-14:00 | 69253.24 | 09-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.810365E+09 | 0.00 | 185.73 | 0.810365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48091.30 | 16-DEC-21:40 | 48091.30 | 16-DEC-21:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189995E+13 | 0.00 | 5099.58 | 0.186195E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.810365E+09 | 0.00 | 171.74 | 0.810365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48091.30 | 48091.30 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.453353E+12 | 0.00 | 744.00 | 0.429361E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 352550.25 | 291723.87 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.119195E+09 | 0.00 | 17.18 | 0.119195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4034.29 | 05-JAN-14:10 | 4034.29 | 05-JAN-14:10 | 0.00 | 0.00 | 0.00 |
February | 0.100811E+10 | 0.00 | 33.80 | 0.100811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21463.31 | 14-FEB-16:00 | 21463.31 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.393816E+10 | 0.00 | 136.89 | 0.393816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22412.19 | 08-MAR-16:00 | 22412.19 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.151227E+11 | 0.00 | 322.17 | 0.151227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24753.83 | 29-APR-15:01 | 24753.83 | 29-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.280797E+11 | 0.00 | 507.06 | 0.280784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27279.39 | 19-MAY-15:02 | 27279.39 | 19-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.457900E+11 | 0.00 | 649.83 | 0.457331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31625.44 | 28-JUN-15:01 | 31625.44 | 28-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.671160E+11 | 0.00 | 744.00 | 0.596909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42112.97 | 01-JUL-14:00 | 31720.09 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.589319E+11 | 0.00 | 742.50 | 0.544729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39938.51 | 26-AUG-10:00 | 30025.95 | 01-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.381063E+11 | 0.00 | 657.83 | 0.371919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37647.88 | 05-SEP-12:20 | 28944.75 | 03-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.160914E+11 | 0.00 | 350.31 | 0.159762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28113.26 | 11-OCT-10:10 | 26337.70 | 01-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.450045E+09 | 0.00 | 41.21 | 0.450045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14180.69 | 09-NOV-14:00 | 14180.69 | 09-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 35543.17 | 0.00 | 0.28 | 35543.17 | 0.00 | 0.00 | 0.00 | 0.00 | 38.55 | 11-DEC-19:45 | 38.55 | 11-DEC-19:45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274753E+12 | 0.00 | 4203.06 | 0.261782E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 35543.17 | 0.00 | 0.28 | 35543.17 | 0.00 | 0.00 | 0.00 | 0.00 | 38.55 | 38.55 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.671160E+11 | 0.00 | 744.00 | 0.596909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42112.97 | 31720.09 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.122701E+10 | 0.00 | 179.20 | 0.122701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18123.17 | 05-JAN-16:01 | 18123.17 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.179103E+10 | 0.00 | 225.72 | 0.179103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19165.72 | 14-FEB-16:02 | 19165.72 | 14-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.283690E+10 | 0.00 | 361.87 | 0.283681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19303.04 | 08-MAR-16:01 | 19303.04 | 08-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.535200E+10 | 0.00 | 569.06 | 0.534452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19785.77 | 29-APR-15:01 | 19785.77 | 29-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.664787E+10 | 0.00 | 633.11 | 0.592818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20024.60 | 21-MAY-15:01 | 20024.60 | 21-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.956647E+10 | 0.00 | 664.62 | 0.743913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20025.51 | 12-JUN-15:01 | 20025.51 | 12-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.117871E+11 | 0.00 | 708.81 | 0.733095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20025.83 | 20-JUL-18:02 | 20025.83 | 20-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.116954E+11 | 0.00 | 706.78 | 0.726270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18927.70 | 26-AUG-08:61 | 17441.38 | 17-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.928140E+10 | 0.00 | 671.75 | 0.626483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20027.45 | 21-SEP-15:01 | 20027.45 | 21-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.623777E+10 | 0.00 | 580.33 | 0.540343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20027.43 | 06-OCT-15:01 | 20027.43 | 06-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.239731E+10 | 0.00 | 345.02 | 0.239528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18376.44 | 02-NOV-15:01 | 18376.44 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.101744E+10 | 0.00 | 180.57 | 0.101744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18070.74 | 26-DEC-16:02 | 18070.74 | 26-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.698377E+11 | 0.00 | 5826.85 | 0.542413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.101744E+10 | 0.00 | 179.20 | 0.101744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18070.74 | 17441.38 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.117871E+11 | 0.00 | 708.81 | 0.743913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20027.45 | 20027.45 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.228196E+09 | 0.00 | 37.81 | 0.228196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17909.82 | 05-JAN-16:01 | 17909.82 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.589752E+09 | 0.00 | 85.41 | 0.589752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18937.89 | 14-FEB-16:02 | 18937.89 | 14-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.144492E+10 | 0.00 | 220.33 | 0.144492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19074.61 | 08-MAR-16:01 | 19074.61 | 08-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.418754E+10 | 0.00 | 499.33 | 0.418037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19552.61 | 29-APR-15:01 | 19552.61 | 29-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.617879E+10 | 0.00 | 611.54 | 0.548690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19788.96 | 21-MAY-15:01 | 19788.96 | 21-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.957723E+10 | 0.00 | 662.69 | 0.748923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19789.45 | 12-JUN-15:01 | 19789.45 | 12-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.114663E+11 | 0.00 | 708.30 | 0.710480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19791.62 | 21-JUL-18:02 | 19791.62 | 21-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.106131E+11 | 0.00 | 700.88 | 0.632814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18724.50 | 26-AUG-08:61 | 17225.75 | 17-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.721841E+10 | 0.00 | 649.42 | 0.446861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19791.20 | 21-SEP-15:01 | 19791.20 | 21-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.364875E+10 | 0.00 | 453.57 | 0.295302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19790.09 | 06-OCT-15:01 | 19790.09 | 06-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.582113E+09 | 0.00 | 125.35 | 0.581197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18158.81 | 02-NOV-15:01 | 18158.81 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.134518E+09 | 0.00 | 25.09 | 0.134518E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17844.07 | 29-DEC-16:01 | 17844.07 | 29-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.558696E+11 | 0.00 | 4779.72 | 0.409896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.134518E+09 | 0.00 | 25.09 | 0.134518E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17844.07 | 17225.75 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.114663E+11 | 0.00 | 708.30 | 0.748923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19791.62 | 19791.62 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.254109E+11 | 0.00 | 302.64 | 0.254109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60879.93 | 03-JAN-12:40 | 60879.93 | 03-JAN-12:40 | 0.00 | 0.00 | 0.00 |
February | 0.235775E+11 | 0.00 | 308.09 | 0.235775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61055.44 | 14-FEB-13:00 | 61055.44 | 14-FEB-13:00 | 0.00 | 0.00 | 0.00 |
March | 0.200189E+11 | 0.00 | 338.89 | 0.200189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50213.46 | 08-MAR-13:30 | 50213.46 | 08-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.192122E+11 | 0.00 | 432.98 | 0.192122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36326.33 | 13-APR-13:20 | 36326.33 | 13-APR-13:20 | 0.00 | 0.00 | 0.00 |
May | 0.161567E+11 | 0.00 | 448.92 | 0.149656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24301.67 | 13-MAY-13:10 | 24301.67 | 13-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.248551E+11 | 0.00 | 576.62 | 0.195963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28507.35 | 29-JUN-13:20 | 27620.45 | 29-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.392866E+11 | 0.00 | 714.67 | 0.202654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32816.71 | 23-JUL-13:30 | 26960.49 | 23-JUL-13:40 | 0.00 | 0.00 | 0.00 |
August | 0.450847E+11 | 0.00 | 709.12 | 0.268243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45934.19 | 21-AUG-14:20 | 38405.98 | 18-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.466698E+11 | 0.00 | 662.02 | 0.363064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57050.99 | 28-SEP-13:30 | 54956.38 | 28-SEP-13:30 | 0.00 | 0.00 | 0.00 |
October | 0.460067E+11 | 0.00 | 569.20 | 0.434236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60953.53 | 19-OCT-12:30 | 60953.53 | 19-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 0.361897E+11 | 0.00 | 419.00 | 0.361897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61502.65 | 20-NOV-13:30 | 61502.65 | 20-NOV-13:30 | 0.00 | 0.00 | 0.00 |
December | 0.282426E+11 | 0.00 | 333.35 | 0.282426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62061.53 | 31-DEC-13:40 | 62061.53 | 31-DEC-13:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370711E+12 | 0.00 | 5815.50 | 0.314033E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.161567E+11 | 0.00 | 302.64 | 0.149656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24301.67 | 24301.67 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.466698E+11 | 0.00 | 714.67 | 0.434236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62061.53 | 62061.53 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.198099E+09 | 0.00 | 20.62 | 0.198099E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31934.17 | 22-JAN-19:03 | 31934.17 | 22-JAN-19:03 | 0.00 | 0.00 | 0.00 |
February | 0.104394E+10 | 0.00 | 88.72 | 0.104394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71234.16 | 15-FEB-19:01 | 71234.16 | 15-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.616401E+10 | 0.00 | 303.27 | 0.614972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84587.32 | 27-MAR-15:01 | 84587.32 | 27-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.201620E+11 | 0.00 | 466.75 | 0.201620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95717.64 | 29-APR-15:01 | 95717.64 | 29-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.340266E+11 | 0.00 | 523.60 | 0.302975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99221.45 | 21-MAY-15:01 | 99221.45 | 21-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.528072E+11 | 0.00 | 565.52 | 0.435558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99253.25 | 27-JUN-15:01 | 99253.25 | 27-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.660158E+11 | 0.00 | 610.03 | 0.440627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99270.58 | 03-JUL-18:02 | 99270.58 | 03-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.579996E+11 | 0.00 | 573.32 | 0.369897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92237.94 | 26-AUG-08:61 | 88988.65 | 21-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.377071E+11 | 0.00 | 510.86 | 0.254218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96807.81 | 21-SEP-18:02 | 96807.81 | 21-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.162585E+11 | 0.00 | 426.42 | 0.132752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94228.26 | 06-OCT-15:01 | 94228.26 | 06-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.226960E+10 | 0.00 | 157.74 | 0.226718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80935.52 | 02-NOV-18:01 | 80935.52 | 02-NOV-18:01 | 0.00 | 0.00 | 0.00 |
December | 0.195689E+09 | 0.00 | 12.48 | 0.195689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29960.08 | 23-DEC-19:04 | 29960.08 | 23-DEC-19:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.294848E+12 | 0.00 | 4259.31 | 0.223619E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.195689E+09 | 0.00 | 12.48 | 0.195689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29960.08 | 29960.08 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.660158E+11 | 0.00 | 610.03 | 0.440627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99270.58 | 99270.58 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.119095E+10 | 0.00 | 191.68 | 0.119095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15873.82 | 05-JAN-16:01 | 15873.82 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.157270E+10 | 0.00 | 225.89 | 0.157270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16785.67 | 14-FEB-16:02 | 16785.67 | 14-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.313696E+10 | 0.00 | 402.36 | 0.313688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16907.03 | 08-MAR-16:01 | 16907.03 | 08-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.618244E+10 | 0.00 | 616.33 | 0.617310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17328.53 | 29-APR-15:01 | 17328.53 | 29-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.748878E+10 | 0.00 | 684.79 | 0.666962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17537.28 | 21-MAY-15:01 | 17537.28 | 21-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.104860E+11 | 0.00 | 698.86 | 0.845980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17541.19 | 27-JUN-15:01 | 17541.19 | 27-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.129831E+11 | 0.00 | 732.20 | 0.856222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17541.57 | 04-JUL-15:02 | 17541.57 | 04-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.125727E+11 | 0.00 | 730.18 | 0.825173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15290.37 | 29-AUG-18:01 | 14892.17 | 25-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.958314E+10 | 0.00 | 694.90 | 0.672737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17540.14 | 21-SEP-15:01 | 17540.14 | 21-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.631516E+10 | 0.00 | 601.28 | 0.550009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17539.77 | 06-OCT-15:01 | 17539.77 | 06-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.242829E+10 | 0.00 | 361.98 | 0.242250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16094.19 | 02-NOV-15:01 | 16094.19 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.970312E+09 | 0.00 | 154.54 | 0.970312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15841.57 | 29-DEC-09:01 | 15841.57 | 29-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.749104E+11 | 0.00 | 6095.00 | 0.596373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.970312E+09 | 0.00 | 154.54 | 0.970312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15290.37 | 14892.17 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.129831E+11 | 0.00 | 732.20 | 0.856222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17541.57 | 17541.57 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.197410E+09 | 0.00 | 40.21 | 0.197410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15029.72 | 01-JAN-09:01 | 15029.72 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.395348E+09 | 0.00 | 76.08 | 0.395348E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16065.60 | 14-FEB-16:02 | 16065.60 | 14-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.152725E+10 | 0.00 | 262.52 | 0.152725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16745.05 | 08-MAR-16:01 | 16745.05 | 08-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.489567E+10 | 0.00 | 576.17 | 0.488751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17164.50 | 29-APR-15:01 | 17164.50 | 29-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.697870E+10 | 0.00 | 675.21 | 0.618049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17371.12 | 21-MAY-15:01 | 17371.12 | 21-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.104814E+11 | 0.00 | 698.53 | 0.848586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17374.94 | 27-JUN-15:01 | 17374.94 | 27-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.126456E+11 | 0.00 | 731.97 | 0.824371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17371.15 | 20-JUL-18:02 | 17371.15 | 20-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.114836E+11 | 0.00 | 728.26 | 0.719298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15203.92 | 29-AUG-18:01 | 15194.11 | 23-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.746255E+10 | 0.00 | 685.89 | 0.480520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17374.74 | 21-SEP-15:01 | 17374.74 | 21-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.355335E+10 | 0.00 | 490.39 | 0.283836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17373.20 | 06-OCT-15:01 | 17373.20 | 06-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.605213E+09 | 0.00 | 124.21 | 0.602163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15699.47 | 12-NOV-09:01 | 15699.47 | 12-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 0.113419E+09 | 0.00 | 35.49 | 0.113419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15082.13 | 30-DEC-09:01 | 15082.13 | 30-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.603395E+11 | 0.00 | 5124.92 | 0.454697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.113419E+09 | 0.00 | 35.49 | 0.113419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15029.72 | 15029.72 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.126456E+11 | 0.00 | 731.97 | 0.848586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17374.94 | 17374.94 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.273670E+09 | 0.00 | 124.83 | 0.273670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4807.87 | 05-JAN-16:01 | 4807.87 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.412701E+09 | 0.00 | 170.57 | 0.412701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5084.52 | 14-FEB-16:02 | 5084.52 | 14-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.634213E+09 | 0.00 | 267.88 | 0.634213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5120.94 | 08-MAR-16:01 | 5120.94 | 08-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.123583E+10 | 0.00 | 496.05 | 0.123364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5248.97 | 29-APR-15:01 | 5248.97 | 29-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.157712E+10 | 0.00 | 593.37 | 0.141973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5312.30 | 21-MAY-15:01 | 5312.30 | 21-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.242564E+10 | 0.00 | 655.52 | 0.189698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5312.67 | 12-JUN-15:01 | 5312.67 | 12-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.303970E+10 | 0.00 | 706.80 | 0.189538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5313.32 | 20-JUL-18:02 | 5313.32 | 20-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.298274E+10 | 0.00 | 704.26 | 0.185823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5147.54 | 26-AUG-08:61 | 4573.83 | 16-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.223969E+10 | 0.00 | 661.53 | 0.151641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5313.73 | 21-SEP-15:01 | 5313.73 | 21-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.140980E+10 | 0.00 | 499.37 | 0.120938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5313.25 | 06-OCT-15:01 | 5313.25 | 06-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.479967E+09 | 0.00 | 246.38 | 0.478770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4875.07 | 02-NOV-15:01 | 4875.07 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.221513E+09 | 0.00 | 121.09 | 0.221513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4794.00 | 26-DEC-16:02 | 4794.00 | 26-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169326E+11 | 0.00 | 5247.65 | 0.130506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.221513E+09 | 0.00 | 121.09 | 0.221513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4794.00 | 4573.83 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.303970E+10 | 0.00 | 706.80 | 0.189698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5313.73 | 5313.73 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 47650949.08 | 0.00 | 28.91 | 47650949.08 | 0.00 | 0.00 | 0.00 | 0.00 | 4742.51 | 05-JAN-16:01 | 4742.51 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.130309E+09 | 0.00 | 62.71 | 0.130309E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5014.85 | 14-FEB-16:02 | 5014.85 | 14-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.312764E+09 | 0.00 | 150.35 | 0.312764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5051.04 | 08-MAR-16:01 | 5051.04 | 08-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.942409E+09 | 0.00 | 419.37 | 0.940592E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5177.59 | 29-APR-15:01 | 5177.59 | 29-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.145346E+10 | 0.00 | 574.27 | 0.130325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5240.05 | 21-MAY-15:01 | 5240.05 | 21-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.242546E+10 | 0.00 | 655.66 | 0.190312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5240.41 | 12-JUN-15:01 | 5240.41 | 12-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.295424E+10 | 0.00 | 706.65 | 0.183040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5241.00 | 20-JUL-18:02 | 5241.00 | 20-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.269711E+10 | 0.00 | 699.31 | 0.161330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5082.83 | 26-AUG-08:61 | 4510.98 | 16-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.169353E+10 | 0.00 | 642.17 | 0.105175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5240.81 | 21-SEP-15:01 | 5240.81 | 21-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.769476E+09 | 0.00 | 362.14 | 0.616082E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5240.53 | 06-OCT-15:01 | 5240.53 | 06-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.106228E+09 | 0.00 | 61.04 | 0.106172E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4808.44 | 02-NOV-15:01 | 4808.44 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 24375444.03 | 0.00 | 19.22 | 24375444.03 | 0.00 | 0.00 | 0.00 | 0.00 | 4719.10 | 02-DEC-16:01 | 4719.10 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135570E+11 | 0.00 | 4381.80 | 0.987977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 24375444.03 | 0.00 | 19.22 | 24375444.03 | 0.00 | 0.00 | 0.00 | 0.00 | 4719.10 | 4510.98 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.295424E+10 | 0.00 | 706.65 | 0.190312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5241.00 | 5241.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.653010E+10 | 0.00 | 341.21 | 0.653010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19221.95 | 05-JAN-16:01 | 19221.95 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.630126E+10 | 0.00 | 365.22 | 0.630126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20326.81 | 14-FEB-16:02 | 20326.81 | 14-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.594339E+10 | 0.00 | 427.91 | 0.594313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20470.14 | 08-MAR-16:01 | 20470.14 | 08-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.657052E+10 | 0.00 | 550.77 | 0.655208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20981.20 | 29-APR-15:01 | 20981.20 | 29-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.666128E+10 | 0.00 | 612.40 | 0.587849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21222.82 | 18-MAY-18:01 | 21222.82 | 18-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.949314E+10 | 0.00 | 652.81 | 0.713920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21230.67 | 11-JUN-15:01 | 21230.67 | 11-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.138029E+11 | 0.00 | 698.93 | 0.855009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21231.02 | 21-JUL-18:02 | 21231.02 | 21-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.148147E+11 | 0.00 | 701.83 | 0.971788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20215.38 | 26-AUG-08:61 | 18488.46 | 17-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.137884E+11 | 0.00 | 674.18 | 0.102644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21229.66 | 20-SEP-18:01 | 21229.66 | 20-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.122102E+11 | 0.00 | 622.66 | 0.112064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20762.35 | 05-OCT-18:01 | 20762.35 | 05-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.864628E+10 | 0.00 | 483.19 | 0.862306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19487.55 | 02-NOV-15:01 | 19487.55 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.723107E+10 | 0.00 | 360.34 | 0.723107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19175.51 | 29-DEC-09:01 | 19175.51 | 29-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111993E+12 | 0.00 | 6491.47 | 0.939371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.594339E+10 | 0.00 | 341.21 | 0.587849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19175.51 | 18488.46 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.148147E+11 | 0.00 | 701.83 | 0.112064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21231.02 | 21231.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1365.45 | 1061.86 | 303.59 | 1535.64 | 590.30 | 0.00 | 0.00 | 0.00 |
February | 1345.94 | 985.04 | 360.90 | 1542.12 | 545.59 | 0.00 | 0.00 | 0.00 |
March | 1000.83 | 610.71 | 390.12 | 1173.13 | 436.96 | 0.00 | 0.00 | 0.00 |
April | 768.64 | 315.00 | 453.64 | 933.58 | 307.18 | 0.00 | 0.00 | 0.00 |
May | 517.30 | 117.03 | 400.27 | 637.97 | 218.76 | 0.00 | 0.00 | 0.00 |
June | 432.45 | 51.93 | 380.52 | 619.59 | 141.59 | 0.00 | 0.00 | 0.00 |
July | 478.69 | 75.11 | 403.58 | 744.72 | 87.45 | 0.00 | 0.00 | 0.00 |
August | 651.18 | 205.38 | 445.80 | 967.53 | 105.85 | 0.00 | 0.00 | 0.00 |
September | 924.44 | 520.38 | 404.06 | 1276.51 | 192.27 | 0.00 | 0.00 | 0.00 |
October | 1245.45 | 916.13 | 329.32 | 1553.77 | 332.40 | 0.00 | 0.00 | 0.00 |
November | 1404.90 | 1081.24 | 323.66 | 1623.80 | 476.87 | 0.00 | 0.00 | 0.00 |
December | 1489.03 | 1229.18 | 259.85 | 1682.33 | 605.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 966.54 | 595.38 | 371.15 | 1188.85 | 335.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 432.45 | 51.93 | 259.85 | 619.59 | 87.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1489.03 | 1229.18 | 453.64 | 1682.33 | 605.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3845.01 | 2990.13 | 854.88 | 4301.34 | 1699.15 | 0.00 | 0.00 | 0.00 |
February | 3790.08 | 2773.82 | 1016.26 | 4320.68 | 1568.61 | 0.00 | 0.00 | 0.00 |
March | 2818.28 | 1719.73 | 1098.54 | 3291.72 | 1249.95 | 0.00 | 0.00 | 0.00 |
April | 2164.44 | 887.02 | 1277.42 | 2633.52 | 861.86 | 0.00 | 0.00 | 0.00 |
May | 1456.68 | 329.54 | 1127.14 | 1821.63 | 603.73 | 0.00 | 0.00 | 0.00 |
June | 1217.75 | 146.22 | 1071.52 | 1778.25 | 381.10 | 0.00 | 0.00 | 0.00 |
July | 1347.97 | 211.51 | 1136.46 | 2120.23 | 232.64 | 0.00 | 0.00 | 0.00 |
August | 1833.69 | 578.34 | 1255.35 | 2735.54 | 287.13 | 0.00 | 0.00 | 0.00 |
September | 2603.16 | 1465.35 | 1137.81 | 3594.98 | 530.73 | 0.00 | 0.00 | 0.00 |
October | 3507.10 | 2579.76 | 927.34 | 4364.71 | 939.27 | 0.00 | 0.00 | 0.00 |
November | 3956.12 | 3044.70 | 911.42 | 4551.79 | 1363.63 | 0.00 | 0.00 | 0.00 |
December | 4193.02 | 3461.29 | 731.73 | 4713.64 | 1747.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2721.70 | 1676.56 | 1045.14 | 3346.71 | 952.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1217.75 | 146.22 | 731.73 | 1778.25 | 232.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4193.02 | 3461.29 | 1277.42 | 4713.64 | 1747.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4994.88 | 3884.35 | 1110.53 | 5673.75 | 2293.68 | 0.00 | 0.00 | 0.00 |
February | 4923.53 | 3603.35 | 1320.18 | 5706.04 | 2116.98 | 0.00 | 0.00 | 0.00 |
March | 3661.10 | 2234.03 | 1427.07 | 4342.74 | 1700.92 | 0.00 | 0.00 | 0.00 |
April | 2811.73 | 1152.28 | 1659.44 | 3481.79 | 1174.04 | 0.00 | 0.00 | 0.00 |
May | 1892.31 | 428.09 | 1464.22 | 2390.87 | 835.22 | 0.00 | 0.00 | 0.00 |
June | 1581.92 | 189.95 | 1391.97 | 2338.59 | 523.86 | 0.00 | 0.00 | 0.00 |
July | 1751.09 | 274.76 | 1476.33 | 2806.40 | 309.18 | 0.00 | 0.00 | 0.00 |
August | 2382.07 | 751.30 | 1630.78 | 3625.16 | 374.02 | 0.00 | 0.00 | 0.00 |
September | 3381.65 | 1903.57 | 1478.08 | 4753.50 | 697.20 | 0.00 | 0.00 | 0.00 |
October | 4555.93 | 3351.26 | 1204.67 | 5763.36 | 1250.98 | 0.00 | 0.00 | 0.00 |
November | 5139.22 | 3955.24 | 1183.98 | 6006.31 | 1834.22 | 0.00 | 0.00 | 0.00 |
December | 5446.97 | 4496.41 | 950.56 | 6220.48 | 2357.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3535.64 | 2177.95 | 1357.69 | 4418.30 | 1284.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1581.92 | 189.95 | 950.56 | 2338.59 | 309.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5446.97 | 4496.41 | 1659.44 | 6220.48 | 2357.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 269.97 | 209.95 | 60.02 | 308.98 | 113.58 | 0.00 | 0.00 | 0.00 |
February | 266.12 | 194.76 | 71.36 | 309.81 | 104.26 | 0.00 | 0.00 | 0.00 |
March | 197.88 | 120.75 | 77.13 | 235.65 | 82.16 | 0.00 | 0.00 | 0.00 |
April | 151.97 | 62.28 | 89.69 | 188.51 | 54.44 | 0.00 | 0.00 | 0.00 |
May | 102.28 | 23.14 | 79.14 | 130.77 | 36.44 | 0.00 | 0.00 | 0.00 |
June | 85.50 | 10.27 | 75.24 | 130.44 | 20.77 | 0.00 | 0.00 | 0.00 |
July | 94.65 | 14.85 | 79.80 | 156.61 | 9.64 | 0.00 | 0.00 | 0.00 |
August | 128.75 | 40.61 | 88.14 | 199.61 | 12.58 | 0.00 | 0.00 | 0.00 |
September | 182.78 | 102.89 | 79.89 | 258.95 | 28.51 | 0.00 | 0.00 | 0.00 |
October | 246.25 | 181.13 | 65.11 | 313.82 | 57.73 | 0.00 | 0.00 | 0.00 |
November | 277.77 | 213.78 | 63.99 | 327.10 | 88.19 | 0.00 | 0.00 | 0.00 |
December | 294.41 | 243.03 | 51.38 | 338.82 | 115.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.10 | 117.72 | 73.38 | 241.20 | 60.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.50 | 10.27 | 51.38 | 130.44 | 9.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 294.41 | 243.03 | 89.69 | 338.82 | 115.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 195.30 | 111.38 | 83.92 | 181.68 | 231.57 | 0.00 | 0.00 | 0.00 |
February | 250.90 | 144.77 | 106.13 | 250.54 | 208.04 | 0.00 | 0.00 | 0.00 |
March | 279.96 | 148.71 | 131.25 | 300.11 | 158.18 | 0.00 | 0.00 | 0.00 |
April | 358.17 | 190.62 | 167.55 | 416.86 | 99.30 | 0.00 | 0.00 | 0.00 |
May | 340.60 | 175.98 | 164.62 | 424.29 | 66.91 | 0.00 | 0.00 | 0.00 |
June | 362.93 | 202.12 | 160.81 | 508.91 | 38.68 | 0.00 | 0.00 | 0.00 |
July | 327.68 | 160.12 | 167.56 | 483.54 | 17.96 | 0.00 | 0.00 | 0.00 |
August | 335.18 | 154.81 | 180.38 | 475.22 | 23.46 | 0.00 | 0.00 | 0.00 |
September | 304.12 | 160.57 | 143.55 | 404.36 | 53.65 | 0.00 | 0.00 | 0.00 |
October | 278.31 | 173.36 | 104.96 | 327.81 | 115.54 | 0.00 | 0.00 | 0.00 |
November | 217.48 | 127.93 | 89.54 | 214.89 | 177.48 | 0.00 | 0.00 | 0.00 |
December | 186.74 | 116.61 | 70.13 | 169.25 | 237.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 286.48 | 155.51 | 130.97 | 346.81 | 118.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.74 | 111.38 | 70.13 | 169.25 | 17.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.93 | 202.12 | 180.38 | 508.91 | 237.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.58 | 0.00 | 36.58 | 10.28 | 124.97 | 0.00 | 0.00 | 0.00 |
February | 45.72 | 0.00 | 45.72 | 19.15 | 112.09 | 0.00 | 0.00 | 0.00 |
March | 57.68 | 0.00 | 57.68 | 39.09 | 85.06 | 0.00 | 0.00 | 0.00 |
April | 73.57 | 0.99 | 72.59 | 63.75 | 51.97 | 0.00 | 0.00 | 0.00 |
May | 79.63 | 5.17 | 74.46 | 87.61 | 34.14 | 0.00 | 0.00 | 0.00 |
June | 90.67 | 15.08 | 75.59 | 133.34 | 19.37 | 0.00 | 0.00 | 0.00 |
July | 83.14 | 7.09 | 76.05 | 133.22 | 9.32 | 0.00 | 0.00 | 0.00 |
August | 77.16 | 1.89 | 75.27 | 113.00 | 11.94 | 0.00 | 0.00 | 0.00 |
September | 61.59 | 0.04 | 61.55 | 76.74 | 28.05 | 0.00 | 0.00 | 0.00 |
October | 45.92 | 0.00 | 45.92 | 36.74 | 61.35 | 0.00 | 0.00 | 0.00 |
November | 38.99 | 0.00 | 38.99 | 14.53 | 95.57 | 0.00 | 0.00 | 0.00 |
December | 31.14 | 0.00 | 31.14 | 4.02 | 128.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.20 | 2.53 | 57.68 | 61.18 | 63.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.14 | 0.00 | 31.14 | 4.02 | 9.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.67 | 15.08 | 76.05 | 133.34 | 128.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 195.30 | 111.38 | 83.92 | 189.72 | 226.33 | 0.00 | 0.00 | 0.00 |
February | 250.90 | 144.77 | 106.13 | 258.62 | 203.36 | 0.00 | 0.00 | 0.00 |
March | 279.96 | 148.71 | 131.25 | 305.85 | 155.51 | 0.00 | 0.00 | 0.00 |
April | 358.17 | 190.62 | 167.55 | 420.31 | 98.23 | 0.00 | 0.00 | 0.00 |
May | 340.60 | 175.98 | 164.62 | 425.49 | 66.57 | 0.00 | 0.00 | 0.00 |
June | 362.93 | 202.12 | 160.81 | 508.97 | 38.56 | 0.00 | 0.00 | 0.00 |
July | 327.68 | 160.12 | 167.56 | 484.06 | 17.81 | 0.00 | 0.00 | 0.00 |
August | 335.18 | 154.81 | 180.38 | 476.99 | 23.03 | 0.00 | 0.00 | 0.00 |
September | 304.12 | 160.57 | 143.55 | 407.92 | 52.34 | 0.00 | 0.00 | 0.00 |
October | 278.31 | 173.36 | 104.96 | 333.94 | 112.60 | 0.00 | 0.00 | 0.00 |
November | 217.48 | 127.93 | 89.54 | 222.44 | 172.75 | 0.00 | 0.00 | 0.00 |
December | 186.74 | 116.61 | 70.13 | 177.26 | 230.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 286.48 | 155.51 | 130.97 | 351.30 | 116.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.74 | 111.38 | 70.13 | 177.26 | 17.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.93 | 202.12 | 180.38 | 508.97 | 230.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 215.94 | 167.92 | 48.01 | 243.32 | 98.63 | 0.00 | 0.00 | 0.00 |
February | 212.85 | 155.78 | 57.07 | 244.29 | 91.52 | 0.00 | 0.00 | 0.00 |
March | 158.27 | 96.58 | 61.69 | 185.65 | 72.62 | 0.00 | 0.00 | 0.00 |
April | 121.56 | 49.81 | 71.74 | 149.16 | 48.95 | 0.00 | 0.00 | 0.00 |
May | 81.81 | 18.51 | 63.30 | 103.35 | 33.77 | 0.00 | 0.00 | 0.00 |
June | 68.39 | 8.21 | 60.18 | 103.42 | 20.33 | 0.00 | 0.00 | 0.00 |
July | 75.70 | 11.88 | 63.82 | 124.04 | 11.08 | 0.00 | 0.00 | 0.00 |
August | 102.98 | 32.48 | 70.50 | 158.45 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 146.19 | 82.29 | 63.90 | 205.73 | 28.13 | 0.00 | 0.00 | 0.00 |
October | 196.96 | 144.88 | 52.08 | 248.45 | 52.77 | 0.00 | 0.00 | 0.00 |
November | 222.18 | 170.99 | 51.19 | 258.05 | 78.86 | 0.00 | 0.00 | 0.00 |
December | 235.48 | 194.39 | 41.09 | 266.96 | 101.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.85 | 94.16 | 58.70 | 190.60 | 54.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.39 | 8.21 | 41.09 | 103.35 | 11.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.48 | 194.39 | 71.74 | 266.96 | 101.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.27 | 0.00 | 29.27 | 8.19 | 101.47 | 0.00 | 0.00 | 0.00 |
February | 36.58 | 0.00 | 36.58 | 16.17 | 90.08 | 0.00 | 0.00 | 0.00 |
March | 46.15 | 0.00 | 46.15 | 33.31 | 67.39 | 0.00 | 0.00 | 0.00 |
April | 58.87 | 0.79 | 58.08 | 54.98 | 39.91 | 0.00 | 0.00 | 0.00 |
May | 63.72 | 4.14 | 59.58 | 74.55 | 25.83 | 0.00 | 0.00 | 0.00 |
June | 72.54 | 12.06 | 60.48 | 111.99 | 14.03 | 0.00 | 0.00 | 0.00 |
July | 66.52 | 5.67 | 60.85 | 112.03 | 6.05 | 0.00 | 0.00 | 0.00 |
August | 61.73 | 1.51 | 60.22 | 95.87 | 7.93 | 0.00 | 0.00 | 0.00 |
September | 49.28 | 0.04 | 49.25 | 65.89 | 20.26 | 0.00 | 0.00 | 0.00 |
October | 36.74 | 0.00 | 36.74 | 32.18 | 47.31 | 0.00 | 0.00 | 0.00 |
November | 31.20 | 0.00 | 31.20 | 12.41 | 76.14 | 0.00 | 0.00 | 0.00 |
December | 24.91 | 0.00 | 24.91 | 3.05 | 104.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.17 | 2.02 | 46.15 | 51.90 | 49.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.91 | 0.00 | 24.91 | 3.05 | 6.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 72.54 | 12.06 | 60.85 | 112.03 | 104.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 189.37 | 105.99 | 83.38 | 160.11 | 219.13 | 0.00 | 0.00 | 0.00 |
February | 229.33 | 123.28 | 106.05 | 212.94 | 197.67 | 0.00 | 0.00 | 0.00 |
March | 304.76 | 173.62 | 131.14 | 323.17 | 148.65 | 0.00 | 0.00 | 0.00 |
April | 413.42 | 235.26 | 178.16 | 487.50 | 93.94 | 0.00 | 0.00 | 0.00 |
May | 394.96 | 224.96 | 169.99 | 494.82 | 64.18 | 0.00 | 0.00 | 0.00 |
June | 425.94 | 262.36 | 163.58 | 590.40 | 35.71 | 0.00 | 0.00 | 0.00 |
July | 393.93 | 225.19 | 168.74 | 572.55 | 17.26 | 0.00 | 0.00 | 0.00 |
August | 389.89 | 214.90 | 174.99 | 546.68 | 22.17 | 0.00 | 0.00 | 0.00 |
September | 325.12 | 181.92 | 143.20 | 428.81 | 50.63 | 0.00 | 0.00 | 0.00 |
October | 283.26 | 179.87 | 103.38 | 326.35 | 107.65 | 0.00 | 0.00 | 0.00 |
November | 220.30 | 129.24 | 91.06 | 211.36 | 170.83 | 0.00 | 0.00 | 0.00 |
December | 179.45 | 109.46 | 69.99 | 153.15 | 230.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 312.79 | 180.74 | 132.05 | 376.40 | 112.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 179.45 | 105.99 | 69.99 | 153.15 | 17.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 425.94 | 262.36 | 178.16 | 590.40 | 230.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 269.97 | 209.95 | 60.02 | 308.21 | 113.08 | 0.00 | 0.00 | 0.00 |
February | 266.12 | 194.76 | 71.36 | 309.02 | 103.50 | 0.00 | 0.00 | 0.00 |
March | 197.88 | 120.75 | 77.13 | 233.93 | 81.77 | 0.00 | 0.00 | 0.00 |
April | 151.97 | 62.28 | 89.69 | 186.39 | 54.19 | 0.00 | 0.00 | 0.00 |
May | 102.28 | 23.14 | 79.14 | 128.67 | 36.24 | 0.00 | 0.00 | 0.00 |
June | 85.50 | 10.27 | 75.24 | 128.73 | 20.41 | 0.00 | 0.00 | 0.00 |
July | 94.65 | 14.85 | 79.80 | 155.16 | 9.54 | 0.00 | 0.00 | 0.00 |
August | 128.75 | 40.61 | 88.14 | 198.33 | 12.39 | 0.00 | 0.00 | 0.00 |
September | 182.78 | 102.89 | 79.89 | 258.00 | 28.15 | 0.00 | 0.00 | 0.00 |
October | 246.25 | 181.13 | 65.11 | 312.70 | 57.20 | 0.00 | 0.00 | 0.00 |
November | 277.77 | 213.78 | 63.99 | 326.13 | 87.67 | 0.00 | 0.00 | 0.00 |
December | 294.41 | 243.03 | 51.38 | 338.04 | 115.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.10 | 117.72 | 73.38 | 239.88 | 59.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.50 | 10.27 | 51.38 | 128.67 | 9.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 294.41 | 243.03 | 89.69 | 338.04 | 115.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.58 | 0.00 | 36.58 | 9.64 | 124.33 | 0.00 | 0.00 | 0.00 |
February | 45.72 | 0.00 | 45.72 | 18.56 | 111.31 | 0.00 | 0.00 | 0.00 |
March | 57.68 | 0.00 | 57.68 | 37.46 | 85.34 | 0.00 | 0.00 | 0.00 |
April | 73.57 | 0.99 | 72.59 | 61.12 | 51.84 | 0.00 | 0.00 | 0.00 |
May | 79.63 | 5.17 | 74.46 | 85.36 | 33.91 | 0.00 | 0.00 | 0.00 |
June | 90.67 | 15.08 | 75.59 | 131.62 | 19.11 | 0.00 | 0.00 | 0.00 |
July | 83.14 | 7.09 | 76.05 | 131.77 | 9.26 | 0.00 | 0.00 | 0.00 |
August | 77.16 | 1.89 | 75.27 | 111.57 | 11.74 | 0.00 | 0.00 | 0.00 |
September | 61.59 | 0.04 | 61.55 | 75.59 | 27.77 | 0.00 | 0.00 | 0.00 |
October | 45.92 | 0.00 | 45.92 | 35.41 | 61.13 | 0.00 | 0.00 | 0.00 |
November | 38.99 | 0.00 | 38.99 | 13.70 | 94.95 | 0.00 | 0.00 | 0.00 |
December | 31.14 | 0.00 | 31.14 | 3.53 | 128.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.20 | 2.53 | 57.68 | 59.83 | 63.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.14 | 0.00 | 31.14 | 3.53 | 9.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.67 | 15.08 | 76.05 | 131.77 | 128.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 189.37 | 105.99 | 83.38 | 167.57 | 212.61 | 0.00 | 0.00 | 0.00 |
February | 229.33 | 123.28 | 106.05 | 220.77 | 192.08 | 0.00 | 0.00 | 0.00 |
March | 304.76 | 173.62 | 131.14 | 328.09 | 146.07 | 0.00 | 0.00 | 0.00 |
April | 413.42 | 235.26 | 178.16 | 490.09 | 92.89 | 0.00 | 0.00 | 0.00 |
May | 394.96 | 224.96 | 169.99 | 495.81 | 63.86 | 0.00 | 0.00 | 0.00 |
June | 425.94 | 262.36 | 163.58 | 590.57 | 35.69 | 0.00 | 0.00 | 0.00 |
July | 393.93 | 225.19 | 168.74 | 573.13 | 17.14 | 0.00 | 0.00 | 0.00 |
August | 389.89 | 214.90 | 174.99 | 548.36 | 21.77 | 0.00 | 0.00 | 0.00 |
September | 325.12 | 181.92 | 143.20 | 432.09 | 49.36 | 0.00 | 0.00 | 0.00 |
October | 283.26 | 179.87 | 103.38 | 331.64 | 104.69 | 0.00 | 0.00 | 0.00 |
November | 220.30 | 129.24 | 91.06 | 218.27 | 164.84 | 0.00 | 0.00 | 0.00 |
December | 179.45 | 109.46 | 69.99 | 159.09 | 220.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 312.79 | 180.74 | 132.05 | 380.35 | 109.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 179.45 | 105.99 | 69.99 | 159.09 | 17.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 425.94 | 262.36 | 178.16 | 590.57 | 220.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 46.33 | 0.00 | 46.33 | 9.01 | 174.27 | 0.00 | 0.00 | 0.00 |
February | 57.90 | 0.00 | 57.90 | 20.61 | 156.11 | 0.00 | 0.00 | 0.00 |
March | 73.05 | 0.00 | 73.05 | 46.19 | 120.45 | 0.00 | 0.00 | 0.00 |
April | 93.17 | 1.25 | 91.93 | 77.52 | 76.71 | 0.00 | 0.00 | 0.00 |
May | 100.85 | 6.55 | 94.30 | 107.07 | 52.96 | 0.00 | 0.00 | 0.00 |
June | 114.82 | 19.10 | 95.73 | 164.64 | 32.07 | 0.00 | 0.00 | 0.00 |
July | 105.29 | 8.97 | 96.32 | 164.14 | 18.80 | 0.00 | 0.00 | 0.00 |
August | 97.72 | 2.39 | 95.32 | 138.56 | 22.93 | 0.00 | 0.00 | 0.00 |
September | 78.01 | 0.06 | 77.95 | 93.41 | 47.02 | 0.00 | 0.00 | 0.00 |
October | 58.15 | 0.00 | 58.15 | 41.99 | 92.98 | 0.00 | 0.00 | 0.00 |
November | 49.38 | 0.00 | 49.38 | 13.97 | 138.66 | 0.00 | 0.00 | 0.00 |
December | 39.43 | 0.00 | 39.43 | 2.66 | 181.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 76.24 | 3.20 | 73.04 | 73.59 | 92.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.43 | 0.00 | 39.43 | 2.66 | 18.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 114.82 | 19.10 | 96.32 | 164.64 | 181.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.08 | 0.00 | 17.08 | 3.32 | 64.24 | 0.00 | 0.00 | 0.00 |
February | 21.35 | 0.00 | 21.35 | 7.60 | 57.55 | 0.00 | 0.00 | 0.00 |
March | 26.93 | 0.00 | 26.93 | 17.03 | 44.40 | 0.00 | 0.00 | 0.00 |
April | 34.35 | 0.46 | 33.89 | 28.58 | 28.28 | 0.00 | 0.00 | 0.00 |
May | 37.18 | 2.42 | 34.76 | 39.47 | 19.52 | 0.00 | 0.00 | 0.00 |
June | 42.33 | 7.04 | 35.29 | 60.69 | 11.82 | 0.00 | 0.00 | 0.00 |
July | 38.81 | 3.31 | 35.51 | 60.51 | 6.93 | 0.00 | 0.00 | 0.00 |
August | 36.02 | 0.88 | 35.14 | 51.08 | 8.45 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 0.02 | 28.74 | 34.44 | 17.33 | 0.00 | 0.00 | 0.00 |
October | 21.44 | 0.00 | 21.44 | 15.48 | 34.28 | 0.00 | 0.00 | 0.00 |
November | 18.20 | 0.00 | 18.20 | 5.15 | 51.12 | 0.00 | 0.00 | 0.00 |
December | 14.54 | 0.00 | 14.54 | 0.98 | 66.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.11 | 1.18 | 26.93 | 27.13 | 34.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.54 | 0.00 | 14.54 | 0.98 | 6.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.33 | 7.04 | 35.51 | 60.69 | 66.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 125.97 | 97.96 | 28.01 | 144.21 | 56.36 | 0.00 | 0.00 | 0.00 |
February | 124.17 | 90.87 | 33.29 | 144.92 | 52.01 | 0.00 | 0.00 | 0.00 |
March | 92.33 | 56.34 | 35.99 | 109.78 | 42.06 | 0.00 | 0.00 | 0.00 |
April | 70.91 | 29.06 | 41.85 | 87.55 | 29.22 | 0.00 | 0.00 | 0.00 |
May | 47.72 | 10.80 | 36.93 | 60.03 | 20.81 | 0.00 | 0.00 | 0.00 |
June | 39.90 | 4.79 | 35.11 | 59.53 | 12.81 | 0.00 | 0.00 | 0.00 |
July | 44.16 | 6.93 | 37.23 | 71.57 | 7.18 | 0.00 | 0.00 | 0.00 |
August | 60.07 | 18.95 | 41.13 | 91.97 | 8.83 | 0.00 | 0.00 | 0.00 |
September | 85.28 | 48.01 | 37.28 | 120.08 | 17.18 | 0.00 | 0.00 | 0.00 |
October | 114.90 | 84.52 | 30.38 | 145.74 | 31.26 | 0.00 | 0.00 | 0.00 |
November | 129.61 | 99.75 | 29.86 | 152.39 | 45.30 | 0.00 | 0.00 | 0.00 |
December | 137.37 | 113.40 | 23.97 | 158.47 | 57.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.17 | 54.93 | 34.24 | 112.00 | 31.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.90 | 4.79 | 23.97 | 59.53 | 7.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.37 | 113.40 | 41.85 | 158.47 | 57.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 341.90 | 265.89 | 76.02 | 391.41 | 152.96 | 0.00 | 0.00 | 0.00 |
February | 337.02 | 246.65 | 90.37 | 393.34 | 141.18 | 0.00 | 0.00 | 0.00 |
March | 250.61 | 152.92 | 97.68 | 297.97 | 114.17 | 0.00 | 0.00 | 0.00 |
April | 192.47 | 78.87 | 113.59 | 237.62 | 79.31 | 0.00 | 0.00 | 0.00 |
May | 129.53 | 29.30 | 100.23 | 162.94 | 56.47 | 0.00 | 0.00 | 0.00 |
June | 108.29 | 13.00 | 95.28 | 161.58 | 34.77 | 0.00 | 0.00 | 0.00 |
July | 119.86 | 18.81 | 101.06 | 194.27 | 19.49 | 0.00 | 0.00 | 0.00 |
August | 163.06 | 51.43 | 111.63 | 249.63 | 23.98 | 0.00 | 0.00 | 0.00 |
September | 231.48 | 130.30 | 101.18 | 325.92 | 46.63 | 0.00 | 0.00 | 0.00 |
October | 311.86 | 229.40 | 82.46 | 395.57 | 84.83 | 0.00 | 0.00 | 0.00 |
November | 351.78 | 270.74 | 81.05 | 413.62 | 122.95 | 0.00 | 0.00 | 0.00 |
December | 372.85 | 307.78 | 65.07 | 430.11 | 155.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.02 | 149.08 | 92.94 | 303.99 | 85.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 108.29 | 13.00 | 65.07 | 161.58 | 19.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 372.85 | 307.78 | 113.59 | 430.11 | 155.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 269.97 | 209.95 | 60.02 | 308.38 | 112.54 | 0.00 | 0.00 | 0.00 |
February | 266.12 | 194.76 | 71.36 | 308.92 | 103.32 | 0.00 | 0.00 | 0.00 |
March | 197.88 | 120.75 | 77.13 | 234.89 | 81.14 | 0.00 | 0.00 | 0.00 |
April | 151.97 | 62.28 | 89.69 | 187.53 | 53.47 | 0.00 | 0.00 | 0.00 |
May | 102.28 | 23.14 | 79.14 | 130.08 | 35.53 | 0.00 | 0.00 | 0.00 |
June | 85.50 | 10.27 | 75.24 | 129.94 | 20.07 | 0.00 | 0.00 | 0.00 |
July | 94.65 | 14.85 | 79.80 | 155.83 | 9.11 | 0.00 | 0.00 | 0.00 |
August | 128.75 | 40.61 | 88.14 | 198.50 | 12.03 | 0.00 | 0.00 | 0.00 |
September | 182.78 | 102.89 | 79.89 | 257.69 | 27.70 | 0.00 | 0.00 | 0.00 |
October | 246.25 | 181.13 | 65.11 | 313.05 | 56.64 | 0.00 | 0.00 | 0.00 |
November | 277.77 | 213.78 | 63.99 | 326.60 | 86.78 | 0.00 | 0.00 | 0.00 |
December | 294.41 | 243.03 | 51.38 | 338.33 | 114.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.10 | 117.72 | 73.38 | 240.42 | 59.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.50 | 10.27 | 51.38 | 129.94 | 9.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 294.41 | 243.03 | 89.69 | 338.33 | 114.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 195.30 | 111.38 | 83.92 | 181.14 | 228.99 | 0.00 | 0.00 | 0.00 |
February | 250.90 | 144.77 | 106.13 | 249.29 | 205.99 | 0.00 | 0.00 | 0.00 |
March | 279.96 | 148.71 | 131.25 | 298.88 | 155.98 | 0.00 | 0.00 | 0.00 |
April | 358.17 | 190.62 | 167.55 | 414.65 | 97.38 | 0.00 | 0.00 | 0.00 |
May | 340.60 | 175.98 | 164.62 | 422.24 | 65.21 | 0.00 | 0.00 | 0.00 |
June | 362.93 | 202.12 | 160.81 | 506.87 | 37.44 | 0.00 | 0.00 | 0.00 |
July | 327.68 | 160.12 | 167.56 | 481.35 | 16.98 | 0.00 | 0.00 | 0.00 |
August | 335.18 | 154.81 | 180.38 | 472.98 | 22.45 | 0.00 | 0.00 | 0.00 |
September | 304.12 | 160.57 | 143.55 | 402.52 | 52.09 | 0.00 | 0.00 | 0.00 |
October | 278.31 | 173.36 | 104.96 | 326.70 | 113.03 | 0.00 | 0.00 | 0.00 |
November | 217.48 | 127.93 | 89.54 | 214.30 | 174.18 | 0.00 | 0.00 | 0.00 |
December | 186.74 | 116.61 | 70.13 | 168.62 | 234.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 286.48 | 155.51 | 130.97 | 345.31 | 116.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.74 | 111.38 | 70.13 | 168.62 | 16.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.93 | 202.12 | 180.38 | 506.87 | 234.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.58 | 0.00 | 36.58 | 10.87 | 123.41 | 0.00 | 0.00 | 0.00 |
February | 45.72 | 0.00 | 45.72 | 19.62 | 110.85 | 0.00 | 0.00 | 0.00 |
March | 57.68 | 0.00 | 57.68 | 39.58 | 83.72 | 0.00 | 0.00 | 0.00 |
April | 73.57 | 0.99 | 72.59 | 63.71 | 50.95 | 0.00 | 0.00 | 0.00 |
May | 79.63 | 5.17 | 74.46 | 87.35 | 33.28 | 0.00 | 0.00 | 0.00 |
June | 90.67 | 15.08 | 75.59 | 132.84 | 18.81 | 0.00 | 0.00 | 0.00 |
July | 83.14 | 7.09 | 76.05 | 132.67 | 8.81 | 0.00 | 0.00 | 0.00 |
August | 77.16 | 1.89 | 75.27 | 112.48 | 11.41 | 0.00 | 0.00 | 0.00 |
September | 61.59 | 0.04 | 61.55 | 76.53 | 27.17 | 0.00 | 0.00 | 0.00 |
October | 45.92 | 0.00 | 45.92 | 37.14 | 59.78 | 0.00 | 0.00 | 0.00 |
November | 38.99 | 0.00 | 38.99 | 15.27 | 93.45 | 0.00 | 0.00 | 0.00 |
December | 31.14 | 0.00 | 31.14 | 4.39 | 126.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.20 | 2.53 | 57.68 | 61.26 | 62.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.14 | 0.00 | 31.14 | 4.39 | 8.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.67 | 15.08 | 76.05 | 132.84 | 126.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 195.30 | 111.38 | 83.92 | 190.17 | 223.53 | 0.00 | 0.00 | 0.00 |
February | 250.90 | 144.77 | 106.13 | 258.31 | 200.98 | 0.00 | 0.00 | 0.00 |
March | 279.96 | 148.71 | 131.25 | 305.34 | 152.97 | 0.00 | 0.00 | 0.00 |
April | 358.17 | 190.62 | 167.55 | 418.39 | 96.17 | 0.00 | 0.00 | 0.00 |
May | 340.60 | 175.98 | 164.62 | 423.50 | 64.85 | 0.00 | 0.00 | 0.00 |
June | 362.93 | 202.12 | 160.81 | 506.93 | 37.32 | 0.00 | 0.00 | 0.00 |
July | 327.68 | 160.12 | 167.56 | 481.88 | 16.83 | 0.00 | 0.00 | 0.00 |
August | 335.18 | 154.81 | 180.38 | 474.83 | 21.99 | 0.00 | 0.00 | 0.00 |
September | 304.12 | 160.57 | 143.55 | 406.29 | 50.67 | 0.00 | 0.00 | 0.00 |
October | 278.31 | 173.36 | 104.96 | 333.57 | 109.68 | 0.00 | 0.00 | 0.00 |
November | 217.48 | 127.93 | 89.54 | 223.16 | 168.78 | 0.00 | 0.00 | 0.00 |
December | 186.74 | 116.61 | 70.13 | 177.71 | 227.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 286.48 | 155.51 | 130.97 | 350.34 | 113.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.74 | 111.38 | 70.13 | 177.71 | 16.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.93 | 202.12 | 180.38 | 506.93 | 227.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 395.94 | 307.91 | 88.03 | 444.38 | 171.51 | 0.00 | 0.00 | 0.00 |
February | 390.28 | 285.63 | 104.65 | 446.54 | 156.60 | 0.00 | 0.00 | 0.00 |
March | 290.21 | 177.09 | 113.12 | 340.85 | 121.24 | 0.00 | 0.00 | 0.00 |
April | 222.88 | 91.34 | 131.54 | 275.31 | 77.50 | 0.00 | 0.00 | 0.00 |
May | 150.00 | 33.93 | 116.07 | 193.37 | 50.60 | 0.00 | 0.00 | 0.00 |
June | 125.40 | 15.06 | 110.34 | 195.79 | 27.78 | 0.00 | 0.00 | 0.00 |
July | 138.81 | 21.78 | 117.03 | 233.51 | 12.11 | 0.00 | 0.00 | 0.00 |
August | 188.83 | 59.55 | 129.27 | 294.75 | 16.41 | 0.00 | 0.00 | 0.00 |
September | 268.06 | 150.89 | 117.17 | 378.32 | 39.95 | 0.00 | 0.00 | 0.00 |
October | 361.15 | 265.65 | 95.49 | 455.81 | 84.71 | 0.00 | 0.00 | 0.00 |
November | 407.38 | 313.53 | 93.85 | 472.56 | 132.13 | 0.00 | 0.00 | 0.00 |
December | 431.78 | 356.43 | 75.35 | 487.82 | 175.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 280.27 | 172.64 | 107.62 | 351.04 | 88.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 125.40 | 15.06 | 75.35 | 193.37 | 12.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 431.78 | 356.43 | 131.54 | 487.82 | 175.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 256.06 | 0.00 | 256.06 | 50.65 | 981.45 | 0.00 | 0.00 | 0.00 |
February | 320.04 | 0.00 | 320.04 | 112.26 | 883.75 | 0.00 | 0.00 | 0.00 |
March | 403.77 | 0.01 | 403.75 | 251.22 | 681.30 | 0.00 | 0.00 | 0.00 |
April | 514.99 | 6.90 | 508.09 | 427.28 | 426.68 | 0.00 | 0.00 | 0.00 |
May | 557.42 | 36.22 | 521.20 | 589.20 | 293.82 | 0.00 | 0.00 | 0.00 |
June | 634.64 | 105.54 | 529.10 | 909.23 | 178.25 | 0.00 | 0.00 | 0.00 |
July | 581.96 | 49.60 | 532.35 | 908.77 | 106.20 | 0.00 | 0.00 | 0.00 |
August | 540.08 | 13.22 | 526.86 | 770.88 | 128.08 | 0.00 | 0.00 | 0.00 |
September | 431.15 | 0.31 | 430.84 | 528.13 | 253.88 | 0.00 | 0.00 | 0.00 |
October | 321.40 | 0.00 | 321.40 | 245.76 | 502.71 | 0.00 | 0.00 | 0.00 |
November | 272.95 | 0.00 | 272.95 | 82.13 | 763.81 | 0.00 | 0.00 | 0.00 |
December | 217.95 | 0.00 | 217.95 | 14.71 | 1020.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 421.40 | 17.68 | 403.72 | 409.08 | 516.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 217.95 | 0.00 | 217.95 | 14.71 | 106.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 634.64 | 105.54 | 532.35 | 909.23 | 1020.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 256.06 | 0.00 | 256.06 | 43.79 | 1013.26 | 0.00 | 0.00 | 0.00 |
February | 320.04 | 0.00 | 320.04 | 103.19 | 911.78 | 0.00 | 0.00 | 0.00 |
March | 403.77 | 0.01 | 403.75 | 239.41 | 702.11 | 0.00 | 0.00 | 0.00 |
April | 514.99 | 6.90 | 508.09 | 413.70 | 438.39 | 0.00 | 0.00 | 0.00 |
May | 557.42 | 36.22 | 521.20 | 574.67 | 302.03 | 0.00 | 0.00 | 0.00 |
June | 634.64 | 105.54 | 529.10 | 895.67 | 184.04 | 0.00 | 0.00 | 0.00 |
July | 581.96 | 49.60 | 532.35 | 895.35 | 111.43 | 0.00 | 0.00 | 0.00 |
August | 540.08 | 13.22 | 526.86 | 757.58 | 133.82 | 0.00 | 0.00 | 0.00 |
September | 431.15 | 0.31 | 430.84 | 516.82 | 262.39 | 0.00 | 0.00 | 0.00 |
October | 321.40 | 0.00 | 321.40 | 236.92 | 517.95 | 0.00 | 0.00 | 0.00 |
November | 272.95 | 0.00 | 272.95 | 75.12 | 788.40 | 0.00 | 0.00 | 0.00 |
December | 217.95 | 0.00 | 217.95 | 11.63 | 1056.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 421.40 | 17.68 | 403.72 | 398.54 | 533.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 217.95 | 0.00 | 217.95 | 11.63 | 111.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 634.64 | 105.54 | 532.35 | 895.67 | 1056.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.58 | 0.00 | 36.58 | 11.35 | 131.96 | 0.00 | 0.00 | 0.00 |
February | 45.72 | 0.00 | 45.72 | 21.71 | 119.71 | 0.00 | 0.00 | 0.00 |
March | 57.68 | 0.00 | 57.68 | 45.44 | 92.34 | 0.00 | 0.00 | 0.00 |
April | 73.57 | 0.99 | 72.59 | 76.22 | 58.28 | 0.00 | 0.00 | 0.00 |
May | 79.63 | 5.17 | 74.46 | 103.50 | 40.85 | 0.00 | 0.00 | 0.00 |
June | 90.67 | 15.08 | 75.59 | 153.68 | 25.67 | 0.00 | 0.00 | 0.00 |
July | 83.14 | 7.09 | 76.05 | 154.86 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 77.16 | 1.89 | 75.27 | 134.08 | 18.47 | 0.00 | 0.00 | 0.00 |
September | 61.59 | 0.04 | 61.55 | 94.35 | 32.96 | 0.00 | 0.00 | 0.00 |
October | 45.92 | 0.00 | 45.92 | 46.82 | 65.67 | 0.00 | 0.00 | 0.00 |
November | 38.99 | 0.00 | 38.99 | 17.32 | 100.37 | 0.00 | 0.00 | 0.00 |
December | 31.14 | 0.00 | 31.14 | 4.33 | 136.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.20 | 2.53 | 57.68 | 72.24 | 69.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.14 | 0.00 | 31.14 | 4.33 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.67 | 15.08 | 76.05 | 154.86 | 136.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 378.72 | 211.97 | 166.75 | 347.01 | 455.76 | 0.00 | 0.00 | 0.00 |
February | 458.63 | 246.53 | 212.09 | 459.51 | 416.24 | 0.00 | 0.00 | 0.00 |
March | 609.47 | 347.21 | 262.26 | 692.67 | 321.49 | 0.00 | 0.00 | 0.00 |
April | 826.77 | 470.48 | 356.29 | 1041.31 | 211.89 | 0.00 | 0.00 | 0.00 |
May | 789.86 | 449.90 | 339.96 | 1060.53 | 153.52 | 0.00 | 0.00 | 0.00 |
June | 851.82 | 524.69 | 327.13 | 1262.22 | 96.22 | 0.00 | 0.00 | 0.00 |
July | 787.80 | 450.35 | 337.45 | 1232.04 | 59.06 | 0.00 | 0.00 | 0.00 |
August | 779.72 | 429.77 | 349.95 | 1180.33 | 69.48 | 0.00 | 0.00 | 0.00 |
September | 650.19 | 363.81 | 286.38 | 936.65 | 121.07 | 0.00 | 0.00 | 0.00 |
October | 566.48 | 359.72 | 206.75 | 713.60 | 230.36 | 0.00 | 0.00 | 0.00 |
November | 440.57 | 258.46 | 182.12 | 456.59 | 351.55 | 0.00 | 0.00 | 0.00 |
December | 358.87 | 218.90 | 139.97 | 328.25 | 473.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 625.54 | 361.45 | 264.09 | 810.84 | 245.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 358.87 | 211.97 | 139.97 | 328.25 | 59.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 851.82 | 524.69 | 356.29 | 1262.22 | 473.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 269.97 | 209.95 | 60.02 | 318.83 | 119.05 | 0.00 | 0.00 | 0.00 |
February | 266.12 | 194.76 | 71.36 | 320.75 | 109.94 | 0.00 | 0.00 | 0.00 |
March | 197.88 | 120.75 | 77.13 | 246.86 | 88.13 | 0.00 | 0.00 | 0.00 |
April | 151.97 | 62.28 | 89.69 | 202.98 | 59.95 | 0.00 | 0.00 | 0.00 |
May | 102.28 | 23.14 | 79.14 | 146.99 | 42.63 | 0.00 | 0.00 | 0.00 |
June | 85.50 | 10.27 | 75.24 | 150.16 | 26.95 | 0.00 | 0.00 | 0.00 |
July | 94.65 | 14.85 | 79.80 | 178.16 | 15.90 | 0.00 | 0.00 | 0.00 |
August | 128.75 | 40.61 | 88.14 | 221.50 | 18.83 | 0.00 | 0.00 | 0.00 |
September | 182.78 | 102.89 | 79.89 | 278.80 | 32.91 | 0.00 | 0.00 | 0.00 |
October | 246.25 | 181.13 | 65.11 | 330.13 | 61.48 | 0.00 | 0.00 | 0.00 |
November | 277.77 | 213.78 | 63.99 | 339.08 | 91.96 | 0.00 | 0.00 | 0.00 |
December | 294.41 | 243.03 | 51.38 | 348.86 | 120.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.10 | 117.72 | 73.38 | 256.56 | 65.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.50 | 10.27 | 51.38 | 146.99 | 15.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 294.41 | 243.03 | 89.69 | 348.86 | 120.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 46.33 | 0.00 | 46.33 | 7.85 | 174.17 | 0.00 | 0.00 | 0.00 |
February | 57.90 | 0.00 | 57.90 | 18.49 | 156.86 | 0.00 | 0.00 | 0.00 |
March | 73.05 | 0.00 | 73.05 | 43.29 | 121.76 | 0.00 | 0.00 | 0.00 |
April | 93.17 | 1.25 | 91.93 | 73.75 | 78.08 | 0.00 | 0.00 | 0.00 |
May | 100.85 | 6.55 | 94.30 | 103.26 | 54.19 | 0.00 | 0.00 | 0.00 |
June | 114.82 | 19.10 | 95.73 | 160.83 | 33.35 | 0.00 | 0.00 | 0.00 |
July | 105.29 | 8.97 | 96.32 | 160.44 | 20.14 | 0.00 | 0.00 | 0.00 |
August | 97.72 | 2.39 | 95.32 | 134.90 | 24.42 | 0.00 | 0.00 | 0.00 |
September | 78.01 | 0.06 | 77.95 | 90.38 | 48.49 | 0.00 | 0.00 | 0.00 |
October | 58.15 | 0.00 | 58.15 | 39.61 | 93.60 | 0.00 | 0.00 | 0.00 |
November | 49.38 | 0.00 | 49.38 | 12.29 | 138.83 | 0.00 | 0.00 | 0.00 |
December | 39.43 | 0.00 | 39.43 | 2.05 | 181.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 76.24 | 3.20 | 73.04 | 70.87 | 93.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.43 | 0.00 | 39.43 | 2.05 | 20.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 114.82 | 19.10 | 96.32 | 160.83 | 181.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 41.45 | 0.00 | 41.45 | 7.02 | 155.80 | 0.00 | 0.00 | 0.00 |
February | 51.81 | 0.00 | 51.81 | 16.54 | 140.35 | 0.00 | 0.00 | 0.00 |
March | 65.36 | 0.00 | 65.36 | 38.73 | 108.94 | 0.00 | 0.00 | 0.00 |
April | 83.36 | 1.12 | 82.25 | 65.98 | 69.86 | 0.00 | 0.00 | 0.00 |
May | 90.23 | 5.86 | 84.37 | 92.39 | 48.48 | 0.00 | 0.00 | 0.00 |
June | 102.73 | 17.08 | 85.65 | 143.90 | 29.84 | 0.00 | 0.00 | 0.00 |
July | 94.20 | 8.03 | 86.17 | 143.54 | 18.02 | 0.00 | 0.00 | 0.00 |
August | 87.43 | 2.14 | 85.29 | 120.69 | 21.85 | 0.00 | 0.00 | 0.00 |
September | 69.79 | 0.05 | 69.74 | 80.86 | 43.39 | 0.00 | 0.00 | 0.00 |
October | 52.03 | 0.00 | 52.03 | 35.44 | 83.75 | 0.00 | 0.00 | 0.00 |
November | 44.18 | 0.00 | 44.18 | 10.99 | 124.20 | 0.00 | 0.00 | 0.00 |
December | 35.28 | 0.00 | 35.28 | 1.83 | 162.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 68.21 | 2.86 | 65.35 | 63.41 | 83.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.28 | 0.00 | 35.28 | 1.83 | 18.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.73 | 17.08 | 86.17 | 143.90 | 162.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1007.89 | 783.80 | 224.09 | 1144.38 | 449.16 | 0.00 | 0.00 | 0.00 |
February | 993.49 | 727.10 | 266.39 | 1147.61 | 416.87 | 0.00 | 0.00 | 0.00 |
March | 738.75 | 450.79 | 287.96 | 865.52 | 340.28 | 0.00 | 0.00 | 0.00 |
April | 567.37 | 232.51 | 334.85 | 686.52 | 238.25 | 0.00 | 0.00 | 0.00 |
May | 381.84 | 86.38 | 295.46 | 468.14 | 170.66 | 0.00 | 0.00 | 0.00 |
June | 319.21 | 38.33 | 280.88 | 465.49 | 106.59 | 0.00 | 0.00 | 0.00 |
July | 353.35 | 55.44 | 297.90 | 561.14 | 61.77 | 0.00 | 0.00 | 0.00 |
August | 480.67 | 151.60 | 329.07 | 723.51 | 75.47 | 0.00 | 0.00 | 0.00 |
September | 682.37 | 384.11 | 298.26 | 948.57 | 141.97 | 0.00 | 0.00 | 0.00 |
October | 919.32 | 676.23 | 243.09 | 1155.30 | 251.77 | 0.00 | 0.00 | 0.00 |
November | 1037.01 | 798.10 | 238.91 | 1209.25 | 361.44 | 0.00 | 0.00 | 0.00 |
December | 1099.11 | 907.30 | 191.81 | 1258.53 | 457.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 713.44 | 439.47 | 273.96 | 884.66 | 255.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 319.21 | 38.33 | 191.81 | 465.49 | 61.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1099.11 | 907.30 | 334.85 | 1258.53 | 457.09 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365721E+10 | 0.284409E+10 | 0.813124E+09 | 0.411307E+10 | 0.158105E+10 |
February | 0.325610E+10 | 0.238302E+10 | 0.873079E+09 | 0.373070E+10 | 0.131988E+10 |
March | 0.268063E+10 | 0.163574E+10 | 0.104489E+10 | 0.314210E+10 | 0.117034E+10 |
April | 0.199231E+10 | 0.816477E+09 | 0.117584E+10 | 0.241983E+10 | 0.796212E+09 |
May | 0.138554E+10 | 0.313445E+09 | 0.107209E+10 | 0.170873E+10 | 0.585930E+09 |
June | 0.112091E+10 | 0.134596E+09 | 0.986310E+09 | 0.160599E+10 | 0.367001E+09 |
July | 0.128213E+10 | 0.201175E+09 | 0.108095E+10 | 0.199466E+10 | 0.234228E+09 |
August | 0.174413E+10 | 0.550093E+09 | 0.119404E+10 | 0.259144E+10 | 0.283503E+09 |
September | 0.239615E+10 | 0.134882E+10 | 0.104733E+10 | 0.330871E+10 | 0.498372E+09 |
October | 0.333581E+10 | 0.245376E+10 | 0.882050E+09 | 0.416161E+10 | 0.890309E+09 |
November | 0.364151E+10 | 0.280257E+10 | 0.838938E+09 | 0.420889E+10 | 0.123604E+10 |
December | 0.398823E+10 | 0.329223E+10 | 0.695993E+09 | 0.450595E+10 | 0.162245E+10 |
Annual Sum or Average | 0.304806E+11 | 0.187760E+11 | 0.117046E+11 | 0.374917E+11 | 0.105853E+11 |
Minimum of Months | 0.112091E+10 | 0.134596E+09 | 0.695993E+09 | 0.160599E+10 | 0.234228E+09 |
Maximum of Months | 0.398823E+10 | 0.329223E+10 | 0.119404E+10 | 0.450595E+10 | 0.162245E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102985E+11 | 0.800876E+10 | 0.228970E+10 | 0.115207E+11 | 0.455100E+10 |
February | 0.916896E+10 | 0.671042E+10 | 0.245853E+10 | 0.104526E+11 | 0.379477E+10 |
March | 0.754847E+10 | 0.460613E+10 | 0.294234E+10 | 0.881654E+10 | 0.334787E+10 |
April | 0.561022E+10 | 0.229915E+10 | 0.331108E+10 | 0.682608E+10 | 0.223395E+10 |
May | 0.390158E+10 | 0.882641E+09 | 0.301894E+10 | 0.487906E+10 | 0.161702E+10 |
June | 0.315640E+10 | 0.379014E+09 | 0.277738E+10 | 0.460923E+10 | 0.987823E+09 |
July | 0.361039E+10 | 0.566496E+09 | 0.304390E+10 | 0.567883E+10 | 0.623116E+09 |
August | 0.491137E+10 | 0.154903E+10 | 0.336234E+10 | 0.732687E+10 | 0.769053E+09 |
September | 0.674739E+10 | 0.379819E+10 | 0.294920E+10 | 0.931819E+10 | 0.137566E+10 |
October | 0.939343E+10 | 0.690963E+10 | 0.248379E+10 | 0.116904E+11 | 0.251574E+10 |
November | 0.102543E+11 | 0.789186E+10 | 0.236239E+10 | 0.117982E+11 | 0.353454E+10 |
December | 0.112306E+11 | 0.927071E+10 | 0.195987E+10 | 0.126250E+11 | 0.468182E+10 |
Annual Sum or Average | 0.858315E+11 | 0.528720E+11 | 0.329595E+11 | 0.105542E+12 | 0.300324E+11 |
Minimum of Months | 0.315640E+10 | 0.379014E+09 | 0.195987E+10 | 0.460923E+10 | 0.623116E+09 |
Maximum of Months | 0.112306E+11 | 0.927071E+10 | 0.336234E+10 | 0.126250E+11 | 0.468182E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133783E+11 | 0.104038E+11 | 0.297446E+10 | 0.151966E+11 | 0.614340E+10 |
February | 0.119110E+11 | 0.871722E+10 | 0.319378E+10 | 0.138041E+11 | 0.512140E+10 |
March | 0.980589E+10 | 0.598362E+10 | 0.382227E+10 | 0.116316E+11 | 0.455574E+10 |
April | 0.728800E+10 | 0.298672E+10 | 0.430128E+10 | 0.902480E+10 | 0.304311E+10 |
May | 0.506838E+10 | 0.114660E+10 | 0.392177E+10 | 0.640372E+10 | 0.223705E+10 |
June | 0.410034E+10 | 0.492361E+09 | 0.360798E+10 | 0.606163E+10 | 0.135784E+10 |
July | 0.469011E+10 | 0.735911E+09 | 0.395420E+10 | 0.751665E+10 | 0.828111E+09 |
August | 0.638014E+10 | 0.201227E+10 | 0.436787E+10 | 0.970964E+10 | 0.100177E+10 |
September | 0.876524E+10 | 0.493407E+10 | 0.383118E+10 | 0.123211E+11 | 0.180714E+10 |
October | 0.122026E+11 | 0.897601E+10 | 0.322659E+10 | 0.154366E+11 | 0.335064E+10 |
November | 0.133209E+11 | 0.102520E+11 | 0.306888E+10 | 0.155684E+11 | 0.475430E+10 |
December | 0.145892E+11 | 0.120432E+11 | 0.254598E+10 | 0.166609E+11 | 0.631377E+10 |
Annual Sum or Average | 0.111500E+12 | 0.686838E+11 | 0.428162E+11 | 0.139336E+12 | 0.405143E+11 |
Minimum of Months | 0.410034E+10 | 0.492361E+09 | 0.254598E+10 | 0.606163E+10 | 0.828111E+09 |
Maximum of Months | 0.145892E+11 | 0.120432E+11 | 0.436787E+10 | 0.166609E+11 | 0.631377E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723095E+09 | 0.562325E+09 | 0.160770E+09 | 0.827570E+09 | 0.304206E+09 |
February | 0.643788E+09 | 0.471164E+09 | 0.172624E+09 | 0.749499E+09 | 0.252236E+09 |
March | 0.530008E+09 | 0.323413E+09 | 0.206595E+09 | 0.631158E+09 | 0.220070E+09 |
April | 0.393917E+09 | 0.161432E+09 | 0.232486E+09 | 0.488625E+09 | 0.141106E+09 |
May | 0.273947E+09 | 61973527.69 | 0.211974E+09 | 0.350259E+09 | 97606165.08 |
June | 0.221626E+09 | 26612006.93 | 0.195014E+09 | 0.338109E+09 | 53825416.05 |
July | 0.253502E+09 | 39775788.64 | 0.213726E+09 | 0.419468E+09 | 25818115.34 |
August | 0.344848E+09 | 0.108763E+09 | 0.236085E+09 | 0.534640E+09 | 33682827.21 |
September | 0.473762E+09 | 0.266685E+09 | 0.207077E+09 | 0.671206E+09 | 73910490.41 |
October | 0.659549E+09 | 0.485151E+09 | 0.174398E+09 | 0.840534E+09 | 0.154637E+09 |
November | 0.719990E+09 | 0.554116E+09 | 0.165874E+09 | 0.847853E+09 | 0.228586E+09 |
December | 0.788542E+09 | 0.650931E+09 | 0.137611E+09 | 0.907493E+09 | 0.310120E+09 |
Annual Sum or Average | 0.602657E+10 | 0.371234E+10 | 0.231423E+10 | 0.760641E+10 | 0.189580E+10 |
Minimum of Months | 0.221626E+09 | 26612006.93 | 0.137611E+09 | 0.338109E+09 | 25818115.34 |
Maximum of Months | 0.788542E+09 | 0.650931E+09 | 0.236085E+09 | 0.907493E+09 | 0.310120E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.523089E+09 | 0.298319E+09 | 0.224770E+09 | 0.486619E+09 | 0.620237E+09 |
February | 0.606983E+09 | 0.350236E+09 | 0.256747E+09 | 0.606103E+09 | 0.503300E+09 |
March | 0.749847E+09 | 0.398315E+09 | 0.351532E+09 | 0.803813E+09 | 0.423673E+09 |
April | 0.928389E+09 | 0.494100E+09 | 0.434289E+09 | 0.108051E+10 | 0.257397E+09 |
May | 0.912271E+09 | 0.471357E+09 | 0.440913E+09 | 0.113643E+10 | 0.179207E+09 |
June | 0.940717E+09 | 0.523906E+09 | 0.416811E+09 | 0.131909E+10 | 0.100251E+09 |
July | 0.877654E+09 | 0.428858E+09 | 0.448795E+09 | 0.129510E+10 | 48109483.73 |
August | 0.897753E+09 | 0.414634E+09 | 0.483120E+09 | 0.127283E+10 | 62828455.79 |
September | 0.788271E+09 | 0.416188E+09 | 0.372084E+09 | 0.104809E+10 | 0.139062E+09 |
October | 0.745436E+09 | 0.464315E+09 | 0.281121E+09 | 0.878009E+09 | 0.309468E+09 |
November | 0.563698E+09 | 0.331600E+09 | 0.232098E+09 | 0.557004E+09 | 0.460034E+09 |
December | 0.500176E+09 | 0.312337E+09 | 0.187839E+09 | 0.453315E+09 | 0.635974E+09 |
Annual Sum or Average | 0.903428E+10 | 0.490416E+10 | 0.413012E+10 | 0.109369E+11 | 0.373954E+10 |
Minimum of Months | 0.500176E+09 | 0.298319E+09 | 0.187839E+09 | 0.453315E+09 | 48109483.73 |
Maximum of Months | 0.940717E+09 | 0.523906E+09 | 0.483120E+09 | 0.131909E+10 | 0.635974E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 97981004.79 | 0.00 | 97981004.79 | 27547156.91 | 0.334722E+09 |
February | 0.110609E+09 | 0.00 | 0.110609E+09 | 46336162.43 | 0.271174E+09 |
March | 0.154499E+09 | 5370.55 | 0.154493E+09 | 0.104688E+09 | 0.227824E+09 |
April | 0.190699E+09 | 2554501.35 | 0.188145E+09 | 0.165240E+09 | 0.134707E+09 |
May | 0.213292E+09 | 13858268.08 | 0.199434E+09 | 0.234666E+09 | 91427927.08 |
June | 0.235007E+09 | 39082164.48 | 0.195925E+09 | 0.345627E+09 | 50213555.43 |
July | 0.222682E+09 | 18980349.87 | 0.203701E+09 | 0.356809E+09 | 24967592.70 |
August | 0.206659E+09 | 5057538.87 | 0.201601E+09 | 0.302662E+09 | 31978975.11 |
September | 0.159653E+09 | 113768.03 | 0.159539E+09 | 0.198899E+09 | 72709429.88 |
October | 0.122983E+09 | 0.00 | 0.122983E+09 | 98394459.33 | 0.164308E+09 |
November | 0.101073E+09 | 0.00 | 0.101073E+09 | 37662263.36 | 0.247718E+09 |
December | 83396664.10 | 0.00 | 83396664.10 | 10772122.40 | 0.344578E+09 |
Annual Sum or Average | 0.189853E+10 | 79651961.22 | 0.181888E+10 | 0.192930E+10 | 0.199633E+10 |
Minimum of Months | 83396664.10 | 0.00 | 83396664.10 | 10772122.40 | 24967592.70 |
Maximum of Months | 0.235007E+09 | 39082164.48 | 0.203701E+09 | 0.356809E+09 | 0.344578E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.523089E+09 | 0.298319E+09 | 0.224770E+09 | 0.508151E+09 | 0.606193E+09 |
February | 0.606983E+09 | 0.350236E+09 | 0.256747E+09 | 0.625659E+09 | 0.491975E+09 |
March | 0.749847E+09 | 0.398315E+09 | 0.351532E+09 | 0.819199E+09 | 0.416517E+09 |
April | 0.928389E+09 | 0.494100E+09 | 0.434289E+09 | 0.108944E+10 | 0.254611E+09 |
May | 0.912271E+09 | 0.471357E+09 | 0.440913E+09 | 0.113962E+10 | 0.178312E+09 |
June | 0.940717E+09 | 0.523906E+09 | 0.416811E+09 | 0.131924E+10 | 99938382.07 |
July | 0.877654E+09 | 0.428858E+09 | 0.448795E+09 | 0.129650E+10 | 47705380.28 |
August | 0.897753E+09 | 0.414634E+09 | 0.483120E+09 | 0.127757E+10 | 61675511.59 |
September | 0.788271E+09 | 0.416188E+09 | 0.372084E+09 | 0.105732E+10 | 0.135670E+09 |
October | 0.745436E+09 | 0.464315E+09 | 0.281121E+09 | 0.894417E+09 | 0.301587E+09 |
November | 0.563698E+09 | 0.331600E+09 | 0.232098E+09 | 0.576566E+09 | 0.447757E+09 |
December | 0.500176E+09 | 0.312337E+09 | 0.187839E+09 | 0.474767E+09 | 0.617630E+09 |
Annual Sum or Average | 0.903428E+10 | 0.490416E+10 | 0.413012E+10 | 0.110785E+11 | 0.365957E+10 |
Minimum of Months | 0.500176E+09 | 0.298319E+09 | 0.187839E+09 | 0.474767E+09 | 47705380.28 |
Maximum of Months | 0.940717E+09 | 0.523906E+09 | 0.483120E+09 | 0.131924E+10 | 0.617630E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.578361E+09 | 0.449770E+09 | 0.128590E+09 | 0.651719E+09 | 0.264178E+09 |
February | 0.514928E+09 | 0.376856E+09 | 0.138072E+09 | 0.590998E+09 | 0.221395E+09 |
March | 0.423922E+09 | 0.258679E+09 | 0.165243E+09 | 0.497252E+09 | 0.194503E+09 |
April | 0.315071E+09 | 0.129120E+09 | 0.185952E+09 | 0.386624E+09 | 0.126872E+09 |
May | 0.219114E+09 | 49568964.22 | 0.169545E+09 | 0.276814E+09 | 90455274.07 |
June | 0.177265E+09 | 21285372.45 | 0.155980E+09 | 0.268072E+09 | 52704460.44 |
July | 0.202761E+09 | 31814303.90 | 0.170947E+09 | 0.332237E+09 | 29686035.25 |
August | 0.275824E+09 | 86993003.94 | 0.188831E+09 | 0.424391E+09 | 37232546.56 |
September | 0.378934E+09 | 0.213306E+09 | 0.165628E+09 | 0.533246E+09 | 72901039.60 |
October | 0.527535E+09 | 0.388044E+09 | 0.139491E+09 | 0.665450E+09 | 0.141337E+09 |
November | 0.575878E+09 | 0.443205E+09 | 0.132673E+09 | 0.668874E+09 | 0.204414E+09 |
December | 0.630708E+09 | 0.520641E+09 | 0.110067E+09 | 0.715014E+09 | 0.272640E+09 |
Annual Sum or Average | 0.482030E+10 | 0.296928E+10 | 0.185102E+10 | 0.601069E+10 | 0.170832E+10 |
Minimum of Months | 0.177265E+09 | 21285372.45 | 0.110067E+09 | 0.268072E+09 | 29686035.25 |
Maximum of Months | 0.630708E+09 | 0.520641E+09 | 0.188831E+09 | 0.715014E+09 | 0.272640E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78395194.18 | 0.00 | 78395194.18 | 21938556.71 | 0.271784E+09 |
February | 88498821.31 | 0.00 | 88498821.31 | 39110960.12 | 0.217932E+09 |
March | 0.123615E+09 | 4297.01 | 0.123611E+09 | 89222696.38 | 0.180505E+09 |
April | 0.152580E+09 | 2043871.97 | 0.150536E+09 | 0.142515E+09 | 0.103458E+09 |
May | 0.170657E+09 | 11088084.06 | 0.159568E+09 | 0.199671E+09 | 69176447.67 |
June | 0.188031E+09 | 31269876.03 | 0.156761E+09 | 0.290284E+09 | 36364356.86 |
July | 0.178169E+09 | 15186292.66 | 0.162983E+09 | 0.300061E+09 | 16193343.01 |
August | 0.165349E+09 | 4046567.42 | 0.161302E+09 | 0.256780E+09 | 21252983.01 |
September | 0.127739E+09 | 91026.49 | 0.127648E+09 | 0.170781E+09 | 52509472.69 |
October | 98399454.57 | 0.00 | 98399454.57 | 86177677.24 | 0.126704E+09 |
November | 80868758.46 | 0.00 | 80868758.46 | 32154928.73 | 0.197362E+09 |
December | 66726175.04 | 0.00 | 66726175.04 | 8156449.71 | 0.281022E+09 |
Annual Sum or Average | 0.151903E+10 | 63730015.63 | 0.145530E+10 | 0.163685E+10 | 0.157426E+10 |
Minimum of Months | 66726175.04 | 0.00 | 66726175.04 | 8156449.71 | 16193343.01 |
Maximum of Months | 0.188031E+09 | 31269876.03 | 0.162983E+09 | 0.300061E+09 | 0.281022E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.507216E+09 | 0.283893E+09 | 0.223323E+09 | 0.428851E+09 | 0.586912E+09 |
February | 0.554793E+09 | 0.298227E+09 | 0.256566E+09 | 0.515155E+09 | 0.478200E+09 |
March | 0.816260E+09 | 0.465022E+09 | 0.351239E+09 | 0.865581E+09 | 0.398147E+09 |
April | 0.107158E+10 | 0.609786E+09 | 0.461789E+09 | 0.126360E+10 | 0.243484E+09 |
May | 0.105785E+10 | 0.602543E+09 | 0.455309E+09 | 0.132532E+10 | 0.171901E+09 |
June | 0.110403E+10 | 0.680041E+09 | 0.423991E+09 | 0.153031E+10 | 92557758.71 |
July | 0.105510E+10 | 0.603154E+09 | 0.451944E+09 | 0.153351E+10 | 46230153.17 |
August | 0.104428E+10 | 0.575590E+09 | 0.468689E+09 | 0.146422E+10 | 59390576.31 |
September | 0.842711E+09 | 0.471538E+09 | 0.371174E+09 | 0.111148E+10 | 0.131224E+09 |
October | 0.758679E+09 | 0.481775E+09 | 0.276904E+09 | 0.874100E+09 | 0.288327E+09 |
November | 0.571024E+09 | 0.334984E+09 | 0.236040E+09 | 0.547833E+09 | 0.442801E+09 |
December | 0.480632E+09 | 0.293171E+09 | 0.187461E+09 | 0.410196E+09 | 0.617515E+09 |
Annual Sum or Average | 0.986415E+10 | 0.569972E+10 | 0.416443E+10 | 0.118702E+11 | 0.355669E+10 |
Minimum of Months | 0.480632E+09 | 0.283893E+09 | 0.187461E+09 | 0.410196E+09 | 46230153.17 |
Maximum of Months | 0.110403E+10 | 0.680041E+09 | 0.468689E+09 | 0.153351E+10 | 0.617515E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723095E+09 | 0.562325E+09 | 0.160770E+09 | 0.825497E+09 | 0.302878E+09 |
February | 0.643788E+09 | 0.471164E+09 | 0.172624E+09 | 0.747578E+09 | 0.250377E+09 |
March | 0.530008E+09 | 0.323413E+09 | 0.206595E+09 | 0.626562E+09 | 0.219011E+09 |
April | 0.393917E+09 | 0.161432E+09 | 0.232486E+09 | 0.483113E+09 | 0.140457E+09 |
May | 0.273947E+09 | 61973527.69 | 0.211974E+09 | 0.344621E+09 | 97052492.90 |
June | 0.221626E+09 | 26612006.93 | 0.195014E+09 | 0.333661E+09 | 52890603.71 |
July | 0.253502E+09 | 39775788.64 | 0.213726E+09 | 0.415581E+09 | 25556713.42 |
August | 0.344848E+09 | 0.108763E+09 | 0.236085E+09 | 0.531209E+09 | 33175814.30 |
September | 0.473762E+09 | 0.266685E+09 | 0.207077E+09 | 0.668746E+09 | 72972731.60 |
October | 0.659549E+09 | 0.485151E+09 | 0.174398E+09 | 0.837532E+09 | 0.153209E+09 |
November | 0.719990E+09 | 0.554116E+09 | 0.165874E+09 | 0.845335E+09 | 0.227248E+09 |
December | 0.788542E+09 | 0.650931E+09 | 0.137611E+09 | 0.905397E+09 | 0.308795E+09 |
Annual Sum or Average | 0.602657E+10 | 0.371234E+10 | 0.231423E+10 | 0.756483E+10 | 0.188362E+10 |
Minimum of Months | 0.221626E+09 | 26612006.93 | 0.137611E+09 | 0.333661E+09 | 25556713.42 |
Maximum of Months | 0.788542E+09 | 0.650931E+09 | 0.236085E+09 | 0.905397E+09 | 0.308795E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 97981004.79 | 0.00 | 97981004.79 | 25816896.88 | 0.332998E+09 |
February | 0.110609E+09 | 0.00 | 0.110609E+09 | 44911421.16 | 0.269276E+09 |
March | 0.154499E+09 | 5370.55 | 0.154493E+09 | 0.100336E+09 | 0.228568E+09 |
April | 0.190699E+09 | 2554501.35 | 0.188145E+09 | 0.158424E+09 | 0.134359E+09 |
May | 0.213292E+09 | 13858268.08 | 0.199434E+09 | 0.228620E+09 | 90821585.20 |
June | 0.235007E+09 | 39082164.48 | 0.195925E+09 | 0.341157E+09 | 49545618.37 |
July | 0.222682E+09 | 18980349.87 | 0.203701E+09 | 0.352928E+09 | 24808948.20 |
August | 0.206659E+09 | 5057538.87 | 0.201601E+09 | 0.298827E+09 | 31449213.89 |
September | 0.159653E+09 | 113768.03 | 0.159539E+09 | 0.195925E+09 | 71973236.83 |
October | 0.122983E+09 | 0.00 | 0.122983E+09 | 94844544.75 | 0.163718E+09 |
November | 0.101073E+09 | 0.00 | 0.101073E+09 | 35509458.81 | 0.246111E+09 |
December | 83396664.10 | 0.00 | 83396664.10 | 9458141.56 | 0.343264E+09 |
Annual Sum or Average | 0.189853E+10 | 79651961.22 | 0.181888E+10 | 0.188676E+10 | 0.198689E+10 |
Minimum of Months | 83396664.10 | 0.00 | 83396664.10 | 9458141.56 | 24808948.20 |
Maximum of Months | 0.235007E+09 | 39082164.48 | 0.203701E+09 | 0.352928E+09 | 0.343264E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.507216E+09 | 0.283893E+09 | 0.223323E+09 | 0.448806E+09 | 0.569467E+09 |
February | 0.554793E+09 | 0.298227E+09 | 0.256566E+09 | 0.534080E+09 | 0.464669E+09 |
March | 0.816260E+09 | 0.465022E+09 | 0.351239E+09 | 0.878752E+09 | 0.391247E+09 |
April | 0.107158E+10 | 0.609786E+09 | 0.461789E+09 | 0.127030E+10 | 0.240776E+09 |
May | 0.105785E+10 | 0.602543E+09 | 0.455309E+09 | 0.132797E+10 | 0.171039E+09 |
June | 0.110403E+10 | 0.680041E+09 | 0.423991E+09 | 0.153076E+10 | 92498597.33 |
July | 0.105510E+10 | 0.603154E+09 | 0.451944E+09 | 0.153506E+10 | 45910081.69 |
August | 0.104428E+10 | 0.575590E+09 | 0.468689E+09 | 0.146872E+10 | 58311010.97 |
September | 0.842711E+09 | 0.471538E+09 | 0.371174E+09 | 0.111997E+10 | 0.127943E+09 |
October | 0.758679E+09 | 0.481775E+09 | 0.276904E+09 | 0.888266E+09 | 0.280409E+09 |
November | 0.571024E+09 | 0.334984E+09 | 0.236040E+09 | 0.565767E+09 | 0.427259E+09 |
December | 0.480632E+09 | 0.293171E+09 | 0.187461E+09 | 0.426115E+09 | 0.590985E+09 |
Annual Sum or Average | 0.986415E+10 | 0.569972E+10 | 0.416443E+10 | 0.119946E+11 | 0.346051E+10 |
Minimum of Months | 0.480632E+09 | 0.283893E+09 | 0.187461E+09 | 0.426115E+09 | 45910081.69 |
Maximum of Months | 0.110403E+10 | 0.680041E+09 | 0.468689E+09 | 0.153506E+10 | 0.590985E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.124087E+09 | 0.00 | 0.124087E+09 | 24140601.02 | 0.466774E+09 |
February | 0.140079E+09 | 0.00 | 0.140079E+09 | 49862868.70 | 0.377669E+09 |
March | 0.195663E+09 | 6801.46 | 0.195656E+09 | 0.123727E+09 | 0.322616E+09 |
April | 0.241509E+09 | 3235114.78 | 0.238274E+09 | 0.200934E+09 | 0.198839E+09 |
May | 0.270121E+09 | 17550622.12 | 0.252571E+09 | 0.286769E+09 | 0.141860E+09 |
June | 0.297622E+09 | 49495095.36 | 0.248127E+09 | 0.426760E+09 | 83121524.80 |
July | 0.282012E+09 | 24037415.51 | 0.257975E+09 | 0.439628E+09 | 50361772.91 |
August | 0.261720E+09 | 6405053.86 | 0.255315E+09 | 0.371106E+09 | 61426237.57 |
September | 0.202191E+09 | 144080.03 | 0.202047E+09 | 0.242131E+09 | 0.121866E+09 |
October | 0.155750E+09 | 0.00 | 0.155750E+09 | 0.112468E+09 | 0.249045E+09 |
November | 0.128002E+09 | 0.00 | 0.128002E+09 | 36205716.31 | 0.359410E+09 |
December | 0.105617E+09 | 0.00 | 0.105617E+09 | 7123174.13 | 0.485448E+09 |
Annual Sum or Average | 0.240437E+10 | 0.100874E+09 | 0.230350E+10 | 0.232086E+10 | 0.291844E+10 |
Minimum of Months | 0.105617E+09 | 0.00 | 0.105617E+09 | 7123174.13 | 50361772.91 |
Maximum of Months | 0.297622E+09 | 49495095.36 | 0.257975E+09 | 0.439628E+09 | 0.485448E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45743517.88 | 0.00 | 45743517.88 | 8899225.12 | 0.172072E+09 |
February | 51638974.26 | 0.00 | 51638974.26 | 18381518.06 | 0.139224E+09 |
March | 72129348.61 | 2507.30 | 72126841.31 | 45610779.41 | 0.118930E+09 |
April | 89030149.10 | 1192597.26 | 87837551.84 | 74072507.54 | 73300467.31 |
May | 99577941.81 | 6469886.03 | 93108055.78 | 0.105715E+09 | 52295387.93 |
June | 0.109716E+09 | 18245941.58 | 91469732.72 | 0.157321E+09 | 30642035.83 |
July | 0.103961E+09 | 8861186.67 | 95100166.05 | 0.162065E+09 | 18565434.81 |
August | 96480877.97 | 2361168.07 | 94119709.91 | 0.136805E+09 | 22644254.63 |
September | 74535836.68 | 53113.86 | 74482722.82 | 89259476.80 | 44924964.61 |
October | 57415983.93 | 0.00 | 57415983.93 | 41460539.87 | 91808183.53 |
November | 47186840.17 | 0.00 | 47186840.17 | 13346926.19 | 0.132494E+09 |
December | 38934656.81 | 0.00 | 38934656.81 | 2625896.93 | 0.178956E+09 |
Annual Sum or Average | 0.886351E+09 | 37186400.77 | 0.849165E+09 | 0.855563E+09 | 0.107586E+10 |
Minimum of Months | 38934656.81 | 0.00 | 38934656.81 | 2625896.93 | 18565434.81 |
Maximum of Months | 0.109716E+09 | 18245941.58 | 95100166.05 | 0.162065E+09 | 0.178956E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.337393E+09 | 0.262378E+09 | 75014586.89 | 0.386251E+09 | 0.150944E+09 |
February | 0.300389E+09 | 0.219843E+09 | 80545831.06 | 0.350588E+09 | 0.125834E+09 |
March | 0.247300E+09 | 0.150903E+09 | 96396323.39 | 0.294044E+09 | 0.112661E+09 |
April | 0.183800E+09 | 75323316.63 | 0.108477E+09 | 0.226922E+09 | 75734400.02 |
May | 0.127823E+09 | 28916598.29 | 98906174.13 | 0.160786E+09 | 55728819.91 |
June | 0.103410E+09 | 12417055.19 | 90992515.30 | 0.154304E+09 | 33200255.75 |
July | 0.118283E+09 | 18559222.69 | 99723891.11 | 0.191704E+09 | 19236511.60 |
August | 0.160905E+09 | 50748321.82 | 0.110156E+09 | 0.246338E+09 | 23663661.62 |
September | 0.221055E+09 | 0.124434E+09 | 96621084.81 | 0.311243E+09 | 44530716.67 |
October | 0.307743E+09 | 0.226370E+09 | 81373553.20 | 0.390357E+09 | 83715229.74 |
November | 0.335945E+09 | 0.258549E+09 | 77396069.05 | 0.395000E+09 | 0.117411E+09 |
December | 0.367930E+09 | 0.303722E+09 | 64208705.21 | 0.424435E+09 | 0.153656E+09 |
Annual Sum or Average | 0.281198E+10 | 0.173216E+10 | 0.107981E+10 | 0.353197E+10 | 0.996315E+09 |
Minimum of Months | 0.103410E+09 | 12417055.19 | 64208705.21 | 0.154304E+09 | 19236511.60 |
Maximum of Months | 0.367930E+09 | 0.303722E+09 | 0.110156E+09 | 0.424435E+09 | 0.153656E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.915754E+09 | 0.712149E+09 | 0.203605E+09 | 0.104836E+10 | 0.409693E+09 |
February | 0.815317E+09 | 0.596699E+09 | 0.218618E+09 | 0.951567E+09 | 0.341540E+09 |
March | 0.671222E+09 | 0.409583E+09 | 0.261639E+09 | 0.798096E+09 | 0.305784E+09 |
April | 0.498871E+09 | 0.204443E+09 | 0.294428E+09 | 0.615912E+09 | 0.205559E+09 |
May | 0.346937E+09 | 78485562.51 | 0.268452E+09 | 0.436406E+09 | 0.151259E+09 |
June | 0.280675E+09 | 33702427.65 | 0.246972E+09 | 0.418813E+09 | 90112285.06 |
July | 0.321045E+09 | 50373526.60 | 0.270671E+09 | 0.520324E+09 | 52211827.24 |
August | 0.436728E+09 | 0.137741E+09 | 0.298987E+09 | 0.668611E+09 | 64227776.17 |
September | 0.599989E+09 | 0.337740E+09 | 0.262249E+09 | 0.844776E+09 | 0.120865E+09 |
October | 0.835278E+09 | 0.614413E+09 | 0.220864E+09 | 0.105951E+10 | 0.227220E+09 |
November | 0.911822E+09 | 0.701754E+09 | 0.210069E+09 | 0.107211E+10 | 0.318676E+09 |
December | 0.998639E+09 | 0.824363E+09 | 0.174276E+09 | 0.115200E+10 | 0.417055E+09 |
Annual Sum or Average | 0.763228E+10 | 0.470145E+10 | 0.293083E+10 | 0.958649E+10 | 0.270420E+10 |
Minimum of Months | 0.280675E+09 | 33702427.65 | 0.174276E+09 | 0.418813E+09 | 52211827.24 |
Maximum of Months | 0.998639E+09 | 0.824363E+09 | 0.298987E+09 | 0.115200E+10 | 0.417055E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723095E+09 | 0.562325E+09 | 0.160770E+09 | 0.825973E+09 | 0.301421E+09 |
February | 0.643788E+09 | 0.471164E+09 | 0.172624E+09 | 0.747335E+09 | 0.249945E+09 |
March | 0.530008E+09 | 0.323413E+09 | 0.206595E+09 | 0.629131E+09 | 0.217338E+09 |
April | 0.393917E+09 | 0.161432E+09 | 0.232486E+09 | 0.486070E+09 | 0.138585E+09 |
May | 0.273947E+09 | 61973527.69 | 0.211974E+09 | 0.348409E+09 | 95158183.79 |
June | 0.221626E+09 | 26612006.93 | 0.195014E+09 | 0.336814E+09 | 52027468.18 |
July | 0.253502E+09 | 39775788.64 | 0.213726E+09 | 0.417384E+09 | 24399553.92 |
August | 0.344848E+09 | 0.108763E+09 | 0.236085E+09 | 0.531663E+09 | 32217146.34 |
September | 0.473762E+09 | 0.266685E+09 | 0.207077E+09 | 0.667945E+09 | 71790000.33 |
October | 0.659549E+09 | 0.485151E+09 | 0.174398E+09 | 0.838466E+09 | 0.151710E+09 |
November | 0.719990E+09 | 0.554116E+09 | 0.165874E+09 | 0.846541E+09 | 0.224941E+09 |
December | 0.788542E+09 | 0.650931E+09 | 0.137611E+09 | 0.906176E+09 | 0.306865E+09 |
Annual Sum or Average | 0.602657E+10 | 0.371234E+10 | 0.231423E+10 | 0.758191E+10 | 0.186640E+10 |
Minimum of Months | 0.221626E+09 | 26612006.93 | 0.137611E+09 | 0.336814E+09 | 24399553.92 |
Maximum of Months | 0.788542E+09 | 0.650931E+09 | 0.236085E+09 | 0.906176E+09 | 0.306865E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.523089E+09 | 0.298319E+09 | 0.224770E+09 | 0.485153E+09 | 0.613330E+09 |
February | 0.606983E+09 | 0.350236E+09 | 0.256747E+09 | 0.603084E+09 | 0.498330E+09 |
March | 0.749847E+09 | 0.398315E+09 | 0.351532E+09 | 0.800519E+09 | 0.417777E+09 |
April | 0.928389E+09 | 0.494100E+09 | 0.434289E+09 | 0.107477E+10 | 0.252406E+09 |
May | 0.912271E+09 | 0.471357E+09 | 0.440913E+09 | 0.113093E+10 | 0.174657E+09 |
June | 0.940717E+09 | 0.523906E+09 | 0.416811E+09 | 0.131380E+10 | 97033346.02 |
July | 0.877654E+09 | 0.428858E+09 | 0.448795E+09 | 0.128924E+10 | 45484229.93 |
August | 0.897753E+09 | 0.414634E+09 | 0.483120E+09 | 0.126682E+10 | 60123376.72 |
September | 0.788271E+09 | 0.416188E+09 | 0.372084E+09 | 0.104334E+10 | 0.135027E+09 |
October | 0.745436E+09 | 0.464315E+09 | 0.281121E+09 | 0.875028E+09 | 0.302751E+09 |
November | 0.563698E+09 | 0.331600E+09 | 0.232098E+09 | 0.555459E+09 | 0.451478E+09 |
December | 0.500176E+09 | 0.312337E+09 | 0.187839E+09 | 0.451622E+09 | 0.627778E+09 |
Annual Sum or Average | 0.903428E+10 | 0.490416E+10 | 0.413012E+10 | 0.108898E+11 | 0.367618E+10 |
Minimum of Months | 0.500176E+09 | 0.298319E+09 | 0.187839E+09 | 0.451622E+09 | 45484229.93 |
Maximum of Months | 0.940717E+09 | 0.523906E+09 | 0.483120E+09 | 0.131380E+10 | 0.627778E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 97981004.79 | 0.00 | 97981004.79 | 29112829.76 | 0.330539E+09 |
February | 0.110609E+09 | 0.00 | 0.110609E+09 | 47455204.51 | 0.268157E+09 |
March | 0.154499E+09 | 5370.55 | 0.154493E+09 | 0.106020E+09 | 0.224238E+09 |
April | 0.190699E+09 | 2554501.35 | 0.188145E+09 | 0.165132E+09 | 0.132074E+09 |
May | 0.213292E+09 | 13858268.08 | 0.199434E+09 | 0.233956E+09 | 89143994.90 |
June | 0.235007E+09 | 39082164.48 | 0.195925E+09 | 0.344332E+09 | 48749891.74 |
July | 0.222682E+09 | 18980349.87 | 0.203701E+09 | 0.355331E+09 | 23608594.38 |
August | 0.206659E+09 | 5057538.87 | 0.201601E+09 | 0.301263E+09 | 30562565.00 |
September | 0.159653E+09 | 113768.03 | 0.159539E+09 | 0.198374E+09 | 70416901.11 |
October | 0.122983E+09 | 0.00 | 0.122983E+09 | 99464037.43 | 0.160126E+09 |
November | 0.101073E+09 | 0.00 | 0.101073E+09 | 39572052.85 | 0.242225E+09 |
December | 83396664.10 | 0.00 | 83396664.10 | 11754128.58 | 0.339604E+09 |
Annual Sum or Average | 0.189853E+10 | 79651961.22 | 0.181888E+10 | 0.193177E+10 | 0.195945E+10 |
Minimum of Months | 83396664.10 | 0.00 | 83396664.10 | 11754128.58 | 23608594.38 |
Maximum of Months | 0.235007E+09 | 39082164.48 | 0.203701E+09 | 0.355331E+09 | 0.339604E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.523089E+09 | 0.298319E+09 | 0.224770E+09 | 0.509339E+09 | 0.598709E+09 |
February | 0.606983E+09 | 0.350236E+09 | 0.256747E+09 | 0.624911E+09 | 0.486200E+09 |
March | 0.749847E+09 | 0.398315E+09 | 0.351532E+09 | 0.817836E+09 | 0.409725E+09 |
April | 0.928389E+09 | 0.494100E+09 | 0.434289E+09 | 0.108446E+10 | 0.249277E+09 |
May | 0.912271E+09 | 0.471357E+09 | 0.440913E+09 | 0.113431E+10 | 0.173687E+09 |
June | 0.940717E+09 | 0.523906E+09 | 0.416811E+09 | 0.131396E+10 | 96727860.51 |
July | 0.877654E+09 | 0.428858E+09 | 0.448795E+09 | 0.129068E+10 | 45083663.46 |
August | 0.897753E+09 | 0.414634E+09 | 0.483120E+09 | 0.127179E+10 | 58906240.88 |
September | 0.788271E+09 | 0.416188E+09 | 0.372084E+09 | 0.105310E+10 | 0.131341E+09 |
October | 0.745436E+09 | 0.464315E+09 | 0.281121E+09 | 0.893441E+09 | 0.293768E+09 |
November | 0.563698E+09 | 0.331600E+09 | 0.232098E+09 | 0.578440E+09 | 0.437482E+09 |
December | 0.500176E+09 | 0.312337E+09 | 0.187839E+09 | 0.475986E+09 | 0.609262E+09 |
Annual Sum or Average | 0.903428E+10 | 0.490416E+10 | 0.413012E+10 | 0.110482E+11 | 0.359017E+10 |
Minimum of Months | 0.500176E+09 | 0.298319E+09 | 0.187839E+09 | 0.475986E+09 | 45083663.46 |
Maximum of Months | 0.940717E+09 | 0.523906E+09 | 0.483120E+09 | 0.131396E+10 | 0.609262E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106049E+10 | 0.824703E+09 | 0.235784E+09 | 0.119022E+10 | 0.459368E+09 |
February | 0.944177E+09 | 0.691007E+09 | 0.253170E+09 | 0.108027E+10 | 0.378841E+09 |
March | 0.777308E+09 | 0.474317E+09 | 0.302991E+09 | 0.912940E+09 | 0.324733E+09 |
April | 0.577717E+09 | 0.236755E+09 | 0.340963E+09 | 0.713604E+09 | 0.200873E+09 |
May | 0.401770E+09 | 90890125.98 | 0.310880E+09 | 0.517935E+09 | 0.135524E+09 |
June | 0.325035E+09 | 39029062.12 | 0.286006E+09 | 0.507487E+09 | 72010808.88 |
July | 0.371785E+09 | 58335011.33 | 0.313450E+09 | 0.625443E+09 | 32423758.58 |
August | 0.505753E+09 | 0.159511E+09 | 0.346242E+09 | 0.789452E+09 | 43942666.22 |
September | 0.694817E+09 | 0.391119E+09 | 0.303698E+09 | 0.980597E+09 | 0.103538E+09 |
October | 0.967293E+09 | 0.711521E+09 | 0.255772E+09 | 0.122085E+10 | 0.226879E+09 |
November | 0.105593E+10 | 0.812665E+09 | 0.243270E+09 | 0.122487E+10 | 0.342481E+09 |
December | 0.115647E+10 | 0.954653E+09 | 0.201820E+09 | 0.130657E+10 | 0.469485E+09 |
Annual Sum or Average | 0.883855E+10 | 0.544450E+10 | 0.339405E+10 | 0.110702E+11 | 0.279010E+10 |
Minimum of Months | 0.325035E+09 | 39029062.12 | 0.201820E+09 | 0.507487E+09 | 32423758.58 |
Maximum of Months | 0.115647E+10 | 0.954653E+09 | 0.346242E+09 | 0.130657E+10 | 0.469485E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.685841E+09 | 0.00 | 0.685841E+09 | 0.135664E+09 | 0.262871E+10 |
February | 0.774233E+09 | 0.00 | 0.774233E+09 | 0.271573E+09 | 0.213798E+10 |
March | 0.108145E+10 | 37592.41 | 0.108141E+10 | 0.672881E+09 | 0.182478E+10 |
April | 0.133485E+10 | 17880832.21 | 0.131696E+10 | 0.110750E+10 | 0.110595E+10 |
May | 0.149299E+10 | 97004202.60 | 0.139599E+10 | 0.157813E+10 | 0.786980E+09 |
June | 0.164499E+10 | 0.273565E+09 | 0.137142E+10 | 0.235672E+10 | 0.462019E+09 |
July | 0.155871E+10 | 0.132857E+09 | 0.142585E+10 | 0.243406E+10 | 0.284453E+09 |
August | 0.144656E+10 | 35401431.26 | 0.141115E+10 | 0.206473E+10 | 0.343043E+09 |
September | 0.111753E+10 | 796346.02 | 0.111673E+10 | 0.136891E+10 | 0.658050E+09 |
October | 0.860849E+09 | 0.00 | 0.860849E+09 | 0.658250E+09 | 0.134645E+10 |
November | 0.707481E+09 | 0.00 | 0.707481E+09 | 0.212888E+09 | 0.197980E+10 |
December | 0.583755E+09 | 0.00 | 0.583755E+09 | 39387775.06 | 0.273252E+10 |
Annual Sum or Average | 0.132892E+11 | 0.557543E+09 | 0.127317E+11 | 0.129007E+11 | 0.162907E+11 |
Minimum of Months | 0.583755E+09 | 0.00 | 0.583755E+09 | 39387775.06 | 0.284453E+09 |
Maximum of Months | 0.164499E+10 | 0.273565E+09 | 0.142585E+10 | 0.243406E+10 | 0.273252E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.685841E+09 | 0.00 | 0.685841E+09 | 0.117299E+09 | 0.271392E+10 |
February | 0.774233E+09 | 0.00 | 0.774233E+09 | 0.249630E+09 | 0.220578E+10 |
March | 0.108145E+10 | 37592.41 | 0.108141E+10 | 0.641234E+09 | 0.188052E+10 |
April | 0.133485E+10 | 17880832.21 | 0.131696E+10 | 0.107230E+10 | 0.113629E+10 |
May | 0.149299E+10 | 97004202.60 | 0.139599E+10 | 0.153920E+10 | 0.808946E+09 |
June | 0.164499E+10 | 0.273565E+09 | 0.137142E+10 | 0.232157E+10 | 0.477039E+09 |
July | 0.155871E+10 | 0.132857E+09 | 0.142585E+10 | 0.239810E+10 | 0.298442E+09 |
August | 0.144656E+10 | 35401431.26 | 0.141115E+10 | 0.202910E+10 | 0.358412E+09 |
September | 0.111753E+10 | 796346.02 | 0.111673E+10 | 0.133960E+10 | 0.680126E+09 |
October | 0.860849E+09 | 0.00 | 0.860849E+09 | 0.634576E+09 | 0.138728E+10 |
November | 0.707481E+09 | 0.00 | 0.707481E+09 | 0.194724E+09 | 0.204354E+10 |
December | 0.583755E+09 | 0.00 | 0.583755E+09 | 31153301.05 | 0.282888E+10 |
Annual Sum or Average | 0.132892E+11 | 0.557543E+09 | 0.127317E+11 | 0.125685E+11 | 0.168192E+11 |
Minimum of Months | 0.583755E+09 | 0.00 | 0.583755E+09 | 31153301.05 | 0.298442E+09 |
Maximum of Months | 0.164499E+10 | 0.273565E+09 | 0.142585E+10 | 0.239810E+10 | 0.282888E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 97981004.79 | 0.00 | 97981004.79 | 30390255.72 | 0.353444E+09 |
February | 0.110609E+09 | 0.00 | 0.110609E+09 | 52524733.62 | 0.289593E+09 |
March | 0.154499E+09 | 5370.55 | 0.154493E+09 | 0.121700E+09 | 0.247323E+09 |
April | 0.190699E+09 | 2554501.35 | 0.188145E+09 | 0.197552E+09 | 0.151066E+09 |
May | 0.213292E+09 | 13858268.08 | 0.199434E+09 | 0.277218E+09 | 0.109401E+09 |
June | 0.235007E+09 | 39082164.48 | 0.195925E+09 | 0.398351E+09 | 66545677.53 |
July | 0.222682E+09 | 18980349.87 | 0.203701E+09 | 0.414771E+09 | 42194490.77 |
August | 0.206659E+09 | 5057538.87 | 0.201601E+09 | 0.359114E+09 | 49474862.16 |
September | 0.159653E+09 | 113768.03 | 0.159539E+09 | 0.244561E+09 | 85438832.13 |
October | 0.122983E+09 | 0.00 | 0.122983E+09 | 0.125407E+09 | 0.175889E+09 |
November | 0.101073E+09 | 0.00 | 0.101073E+09 | 44882514.48 | 0.260158E+09 |
December | 83396664.10 | 0.00 | 83396664.10 | 11609110.84 | 0.364341E+09 |
Annual Sum or Average | 0.189853E+10 | 79651961.22 | 0.181888E+10 | 0.227808E+10 | 0.219487E+10 |
Minimum of Months | 83396664.10 | 0.00 | 83396664.10 | 11609110.84 | 42194490.77 |
Maximum of Months | 0.235007E+09 | 39082164.48 | 0.203701E+09 | 0.414771E+09 | 0.364341E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101436E+10 | 0.567746E+09 | 0.446614E+09 | 0.929443E+09 | 0.122070E+10 |
February | 0.110951E+10 | 0.596411E+09 | 0.513096E+09 | 0.111164E+10 | 0.100696E+10 |
March | 0.163240E+10 | 0.929977E+09 | 0.702427E+09 | 0.185524E+10 | 0.861090E+09 |
April | 0.214300E+10 | 0.121949E+10 | 0.923513E+09 | 0.269907E+10 | 0.549228E+09 |
May | 0.211555E+10 | 0.120500E+10 | 0.910554E+09 | 0.284051E+10 | 0.411188E+09 |
June | 0.220791E+10 | 0.135999E+10 | 0.847922E+09 | 0.327167E+10 | 0.249394E+09 |
July | 0.211005E+10 | 0.120622E+10 | 0.903823E+09 | 0.329989E+10 | 0.158196E+09 |
August | 0.208841E+10 | 0.115110E+10 | 0.937312E+09 | 0.316141E+10 | 0.186095E+09 |
September | 0.168530E+10 | 0.943008E+09 | 0.742295E+09 | 0.242781E+10 | 0.313818E+09 |
October | 0.151725E+10 | 0.963481E+09 | 0.553769E+09 | 0.191130E+10 | 0.616987E+09 |
November | 0.114197E+10 | 0.669921E+09 | 0.472046E+09 | 0.118349E+10 | 0.911223E+09 |
December | 0.961196E+09 | 0.586300E+09 | 0.374896E+09 | 0.879186E+09 | 0.126752E+10 |
Annual Sum or Average | 0.197269E+11 | 0.113986E+11 | 0.832827E+10 | 0.255707E+11 | 0.775240E+10 |
Minimum of Months | 0.961196E+09 | 0.567746E+09 | 0.374896E+09 | 0.879186E+09 | 0.158196E+09 |
Maximum of Months | 0.220791E+10 | 0.135999E+10 | 0.937312E+09 | 0.329989E+10 | 0.126752E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723095E+09 | 0.562325E+09 | 0.160770E+09 | 0.853965E+09 | 0.318867E+09 |
February | 0.643788E+09 | 0.471164E+09 | 0.172624E+09 | 0.775948E+09 | 0.265979E+09 |
March | 0.530008E+09 | 0.323413E+09 | 0.206595E+09 | 0.661198E+09 | 0.236037E+09 |
April | 0.393917E+09 | 0.161432E+09 | 0.232486E+09 | 0.526116E+09 | 0.155386E+09 |
May | 0.273947E+09 | 61973527.69 | 0.211974E+09 | 0.393690E+09 | 0.114182E+09 |
June | 0.221626E+09 | 26612006.93 | 0.195014E+09 | 0.389213E+09 | 69841958.49 |
July | 0.253502E+09 | 39775788.64 | 0.213726E+09 | 0.477186E+09 | 42576508.56 |
August | 0.344848E+09 | 0.108763E+09 | 0.236085E+09 | 0.593275E+09 | 50426504.39 |
September | 0.473762E+09 | 0.266685E+09 | 0.207077E+09 | 0.722662E+09 | 85308201.56 |
October | 0.659549E+09 | 0.485151E+09 | 0.174398E+09 | 0.884223E+09 | 0.164662E+09 |
November | 0.719990E+09 | 0.554116E+09 | 0.165874E+09 | 0.878907E+09 | 0.238365E+09 |
December | 0.788542E+09 | 0.650931E+09 | 0.137611E+09 | 0.934385E+09 | 0.323920E+09 |
Annual Sum or Average | 0.602657E+10 | 0.371234E+10 | 0.231423E+10 | 0.809077E+10 | 0.206555E+10 |
Minimum of Months | 0.221626E+09 | 26612006.93 | 0.137611E+09 | 0.389213E+09 | 42576508.56 |
Maximum of Months | 0.788542E+09 | 0.650931E+09 | 0.236085E+09 | 0.934385E+09 | 0.323920E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.124087E+09 | 0.00 | 0.124087E+09 | 21014759.83 | 0.466495E+09 |
February | 0.140079E+09 | 0.00 | 0.140079E+09 | 44727857.89 | 0.379487E+09 |
March | 0.195663E+09 | 6801.46 | 0.195656E+09 | 0.115947E+09 | 0.326113E+09 |
April | 0.241509E+09 | 3235114.78 | 0.238274E+09 | 0.191154E+09 | 0.202384E+09 |
May | 0.270121E+09 | 17550622.12 | 0.252571E+09 | 0.276573E+09 | 0.145136E+09 |
June | 0.297622E+09 | 49495095.36 | 0.248127E+09 | 0.416880E+09 | 86437089.65 |
July | 0.282012E+09 | 24037415.51 | 0.257975E+09 | 0.429711E+09 | 53948773.57 |
August | 0.261720E+09 | 6405053.86 | 0.255315E+09 | 0.361307E+09 | 65417135.98 |
September | 0.202191E+09 | 144080.03 | 0.202047E+09 | 0.234264E+09 | 0.125690E+09 |
October | 0.155750E+09 | 0.00 | 0.155750E+09 | 0.106086E+09 | 0.250707E+09 |
November | 0.128002E+09 | 0.00 | 0.128002E+09 | 31852404.53 | 0.359838E+09 |
December | 0.105617E+09 | 0.00 | 0.105617E+09 | 5479423.46 | 0.487052E+09 |
Annual Sum or Average | 0.240437E+10 | 0.100874E+09 | 0.230350E+10 | 0.223500E+10 | 0.294871E+10 |
Minimum of Months | 0.105617E+09 | 0.00 | 0.105617E+09 | 5479423.46 | 53948773.57 |
Maximum of Months | 0.297622E+09 | 49495095.36 | 0.257975E+09 | 0.429711E+09 | 0.487052E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111021E+09 | 0.00 | 0.111021E+09 | 18801985.24 | 0.417300E+09 |
February | 0.125329E+09 | 0.00 | 0.125329E+09 | 40018183.93 | 0.339532E+09 |
March | 0.175060E+09 | 6085.29 | 0.175054E+09 | 0.103738E+09 | 0.291775E+09 |
April | 0.216079E+09 | 2894469.45 | 0.213184E+09 | 0.171026E+09 | 0.181073E+09 |
May | 0.241679E+09 | 15702608.11 | 0.225976E+09 | 0.247451E+09 | 0.129854E+09 |
June | 0.266283E+09 | 44283449.36 | 0.222000E+09 | 0.372984E+09 | 77335591.62 |
July | 0.252317E+09 | 21506366.74 | 0.230811E+09 | 0.384464E+09 | 48268172.12 |
August | 0.234162E+09 | 5730625.96 | 0.228431E+09 | 0.323263E+09 | 58528959.43 |
September | 0.180901E+09 | 128908.95 | 0.180772E+09 | 0.209597E+09 | 0.112455E+09 |
October | 0.139350E+09 | 0.00 | 0.139350E+09 | 94915842.78 | 0.224309E+09 |
November | 0.114524E+09 | 0.00 | 0.114524E+09 | 28498467.02 | 0.321929E+09 |
December | 94495583.87 | 0.00 | 94495583.87 | 4902460.93 | 0.435732E+09 |
Annual Sum or Average | 0.215120E+10 | 90252513.85 | 0.206095E+10 | 0.199966E+10 | 0.263809E+10 |
Minimum of Months | 94495583.87 | 0.00 | 94495583.87 | 4902460.93 | 48268172.12 |
Maximum of Months | 0.266283E+09 | 44283449.36 | 0.230811E+09 | 0.384464E+09 | 0.435732E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.269953E+10 | 0.209933E+10 | 0.600202E+09 | 0.306511E+10 | 0.120304E+10 |
February | 0.240345E+10 | 0.175899E+10 | 0.644458E+09 | 0.277629E+10 | 0.100850E+10 |
March | 0.197868E+10 | 0.120740E+10 | 0.771280E+09 | 0.231821E+10 | 0.911394E+09 |
April | 0.147061E+10 | 0.602672E+09 | 0.867938E+09 | 0.177945E+10 | 0.617551E+09 |
May | 0.102273E+10 | 0.231366E+09 | 0.791362E+09 | 0.125388E+10 | 0.457094E+09 |
June | 0.827394E+09 | 99350551.84 | 0.728044E+09 | 0.120655E+10 | 0.276292E+09 |
July | 0.946399E+09 | 0.148495E+09 | 0.797904E+09 | 0.150295E+10 | 0.165445E+09 |
August | 0.128742E+10 | 0.406044E+09 | 0.881376E+09 | 0.193785E+10 | 0.202136E+09 |
September | 0.176869E+10 | 0.995615E+09 | 0.773078E+09 | 0.245870E+10 | 0.367980E+09 |
October | 0.246229E+10 | 0.181121E+10 | 0.651081E+09 | 0.309436E+10 | 0.674335E+09 |
November | 0.268794E+10 | 0.206868E+10 | 0.619257E+09 | 0.313437E+10 | 0.936855E+09 |
December | 0.294386E+10 | 0.243012E+10 | 0.513743E+09 | 0.337085E+10 | 0.122426E+10 |
Annual Sum or Average | 0.224990E+11 | 0.138593E+11 | 0.863972E+10 | 0.278986E+11 | 0.804488E+10 |
Minimum of Months | 0.827394E+09 | 99350551.84 | 0.513743E+09 | 0.120655E+10 | 0.165445E+09 |
Maximum of Months | 0.294386E+10 | 0.243012E+10 | 0.881376E+09 | 0.337085E+10 | 0.122426E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1535.64 | 590.30 | 1365.45 | 1061.86 | 303.59 | 0.00 | 0.00 |
February | 1542.12 | 545.59 | 1345.94 | 985.04 | 360.90 | 0.00 | 0.00 |
March | 1173.13 | 436.96 | 1000.83 | 610.71 | 390.12 | 0.00 | 0.00 |
April | 933.58 | 307.18 | 768.64 | 315.00 | 453.64 | 0.00 | 0.00 |
May | 637.97 | 218.76 | 517.30 | 117.03 | 400.27 | 0.00 | 0.00 |
June | 619.59 | 141.59 | 432.45 | 51.93 | 380.52 | 0.00 | 0.00 |
July | 744.72 | 87.45 | 478.69 | 75.11 | 403.58 | 0.00 | 0.00 |
August | 967.53 | 105.85 | 651.18 | 205.38 | 445.80 | 0.00 | 0.00 |
September | 1276.51 | 192.27 | 924.44 | 520.38 | 404.06 | 0.00 | 0.00 |
October | 1553.77 | 332.40 | 1245.45 | 916.13 | 329.32 | 0.00 | 0.00 |
November | 1623.80 | 476.87 | 1404.90 | 1081.24 | 323.66 | 0.00 | 0.00 |
December | 1682.33 | 605.75 | 1489.03 | 1229.18 | 259.85 | 0.00 | 0.00 |
Annual Sum or Average | 1188.85 | 335.66 | 966.54 | 595.38 | 371.15 | 0.00 | 0.00 |
Minimum of Months | 619.59 | 87.45 | 432.45 | 51.93 | 259.85 | 0.00 | 0.00 |
Maximum of Months | 1682.33 | 605.75 | 1489.03 | 1229.18 | 453.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4301.34 | 1699.15 | 3845.01 | 2990.13 | 854.88 | 0.00 | 0.00 |
February | 4320.68 | 1568.61 | 3790.08 | 2773.82 | 1016.26 | 0.00 | 0.00 |
March | 3291.72 | 1249.95 | 2818.28 | 1719.73 | 1098.54 | 0.00 | 0.00 |
April | 2633.52 | 861.86 | 2164.44 | 887.02 | 1277.42 | 0.00 | 0.00 |
May | 1821.63 | 603.73 | 1456.68 | 329.54 | 1127.14 | 0.00 | 0.00 |
June | 1778.25 | 381.10 | 1217.75 | 146.22 | 1071.52 | 0.00 | 0.00 |
July | 2120.23 | 232.64 | 1347.97 | 211.51 | 1136.46 | 0.00 | 0.00 |
August | 2735.54 | 287.13 | 1833.69 | 578.34 | 1255.35 | 0.00 | 0.00 |
September | 3594.98 | 530.73 | 2603.16 | 1465.35 | 1137.81 | 0.00 | 0.00 |
October | 4364.71 | 939.27 | 3507.10 | 2579.76 | 927.34 | 0.00 | 0.00 |
November | 4551.79 | 1363.63 | 3956.12 | 3044.70 | 911.42 | 0.00 | 0.00 |
December | 4713.64 | 1747.99 | 4193.02 | 3461.29 | 731.73 | 0.00 | 0.00 |
Annual Sum or Average | 3346.71 | 952.32 | 2721.70 | 1676.56 | 1045.14 | 0.00 | 0.00 |
Minimum of Months | 1778.25 | 232.64 | 1217.75 | 146.22 | 731.73 | 0.00 | 0.00 |
Maximum of Months | 4713.64 | 1747.99 | 4193.02 | 3461.29 | 1277.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5673.75 | 2293.68 | 4994.88 | 3884.35 | 1110.53 | 0.00 | 0.00 |
February | 5706.04 | 2116.98 | 4923.53 | 3603.35 | 1320.18 | 0.00 | 0.00 |
March | 4342.74 | 1700.92 | 3661.10 | 2234.03 | 1427.07 | 0.00 | 0.00 |
April | 3481.79 | 1174.04 | 2811.73 | 1152.28 | 1659.44 | 0.00 | 0.00 |
May | 2390.87 | 835.22 | 1892.31 | 428.09 | 1464.22 | 0.00 | 0.00 |
June | 2338.59 | 523.86 | 1581.92 | 189.95 | 1391.97 | 0.00 | 0.00 |
July | 2806.40 | 309.18 | 1751.09 | 274.76 | 1476.33 | 0.00 | 0.00 |
August | 3625.16 | 374.02 | 2382.07 | 751.30 | 1630.78 | 0.00 | 0.00 |
September | 4753.50 | 697.20 | 3381.65 | 1903.57 | 1478.08 | 0.00 | 0.00 |
October | 5763.36 | 1250.98 | 4555.93 | 3351.26 | 1204.67 | 0.00 | 0.00 |
November | 6006.31 | 1834.22 | 5139.22 | 3955.24 | 1183.98 | 0.00 | 0.00 |
December | 6220.48 | 2357.29 | 5446.97 | 4496.41 | 950.56 | 0.00 | 0.00 |
Annual Sum or Average | 4418.30 | 1284.70 | 3535.64 | 2177.95 | 1357.69 | 0.00 | 0.00 |
Minimum of Months | 2338.59 | 309.18 | 1581.92 | 189.95 | 950.56 | 0.00 | 0.00 |
Maximum of Months | 6220.48 | 2357.29 | 5446.97 | 4496.41 | 1659.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 477.78 | 332.27 | 465.27 | 321.33 | 143.94 | 0.00 | 0.00 |
February | 552.21 | 304.17 | 517.02 | 339.53 | 177.48 | 0.00 | 0.00 |
March | 531.76 | 236.35 | 477.84 | 269.46 | 208.38 | 0.00 | 0.00 |
April | 603.83 | 152.20 | 510.15 | 252.91 | 257.24 | 0.00 | 0.00 |
May | 554.39 | 102.68 | 442.88 | 199.12 | 243.76 | 0.00 | 0.00 |
June | 639.32 | 59.41 | 448.43 | 212.39 | 236.04 | 0.00 | 0.00 |
July | 640.14 | 27.60 | 422.33 | 174.97 | 247.36 | 0.00 | 0.00 |
August | 674.82 | 36.02 | 463.93 | 195.41 | 268.52 | 0.00 | 0.00 |
September | 663.06 | 81.92 | 486.90 | 263.45 | 223.44 | 0.00 | 0.00 |
October | 637.18 | 168.82 | 524.56 | 354.49 | 170.07 | 0.00 | 0.00 |
November | 532.75 | 256.42 | 495.25 | 341.71 | 153.54 | 0.00 | 0.00 |
December | 491.59 | 336.75 | 481.15 | 359.64 | 121.51 | 0.00 | 0.00 |
Annual Sum or Average | 583.20 | 173.89 | 477.58 | 273.23 | 204.35 | 0.00 | 0.00 |
Minimum of Months | 477.78 | 27.60 | 422.33 | 174.97 | 121.51 | 0.00 | 0.00 |
Maximum of Months | 674.82 | 336.75 | 524.56 | 359.64 | 268.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 196.71 | 348.00 | 231.88 | 111.38 | 120.50 | 0.00 | 0.00 |
February | 274.60 | 312.28 | 296.62 | 144.77 | 151.85 | 0.00 | 0.00 |
March | 343.11 | 238.74 | 337.64 | 148.72 | 188.93 | 0.00 | 0.00 |
April | 482.74 | 148.88 | 431.75 | 191.61 | 240.14 | 0.00 | 0.00 |
May | 511.95 | 99.56 | 420.24 | 181.16 | 239.08 | 0.00 | 0.00 |
June | 640.22 | 55.84 | 453.60 | 217.20 | 236.39 | 0.00 | 0.00 |
July | 616.96 | 26.82 | 410.82 | 167.20 | 243.61 | 0.00 | 0.00 |
August | 589.58 | 34.56 | 412.34 | 156.69 | 255.65 | 0.00 | 0.00 |
September | 484.57 | 80.30 | 365.71 | 160.61 | 205.10 | 0.00 | 0.00 |
October | 369.59 | 172.86 | 324.23 | 173.36 | 150.88 | 0.00 | 0.00 |
November | 233.92 | 265.26 | 256.47 | 127.93 | 128.54 | 0.00 | 0.00 |
December | 175.91 | 353.87 | 217.88 | 116.61 | 101.27 | 0.00 | 0.00 |
Annual Sum or Average | 410.55 | 177.42 | 346.68 | 158.04 | 188.64 | 0.00 | 0.00 |
Minimum of Months | 175.91 | 26.82 | 217.88 | 111.38 | 101.27 | 0.00 | 0.00 |
Maximum of Months | 640.22 | 353.87 | 453.60 | 217.20 | 255.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 243.32 | 98.63 | 215.94 | 167.92 | 48.01 | 0.00 | 0.00 |
February | 244.29 | 91.52 | 212.85 | 155.78 | 57.07 | 0.00 | 0.00 |
March | 185.65 | 72.62 | 158.27 | 96.58 | 61.69 | 0.00 | 0.00 |
April | 149.16 | 48.95 | 121.56 | 49.81 | 71.74 | 0.00 | 0.00 |
May | 103.35 | 33.77 | 81.81 | 18.51 | 63.30 | 0.00 | 0.00 |
June | 103.42 | 20.33 | 68.39 | 8.21 | 60.18 | 0.00 | 0.00 |
July | 124.04 | 11.08 | 75.70 | 11.88 | 63.82 | 0.00 | 0.00 |
August | 158.45 | 13.90 | 102.98 | 32.48 | 70.50 | 0.00 | 0.00 |
September | 205.73 | 28.13 | 146.19 | 82.29 | 63.90 | 0.00 | 0.00 |
October | 248.45 | 52.77 | 196.96 | 144.88 | 52.08 | 0.00 | 0.00 |
November | 258.05 | 78.86 | 222.18 | 170.99 | 51.19 | 0.00 | 0.00 |
December | 266.96 | 101.79 | 235.48 | 194.39 | 41.09 | 0.00 | 0.00 |
Annual Sum or Average | 190.60 | 54.17 | 152.85 | 94.16 | 58.70 | 0.00 | 0.00 |
Minimum of Months | 103.35 | 11.08 | 68.39 | 8.21 | 41.09 | 0.00 | 0.00 |
Maximum of Months | 266.96 | 101.79 | 235.48 | 194.39 | 71.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 8.19 | 101.47 | 29.27 | 0.00 | 29.27 | 0.00 | 0.00 |
February | 16.17 | 90.08 | 36.58 | 0.00 | 36.58 | 0.00 | 0.00 |
March | 33.31 | 67.39 | 46.15 | 0.00 | 46.15 | 0.00 | 0.00 |
April | 54.98 | 39.91 | 58.87 | 0.79 | 58.08 | 0.00 | 0.00 |
May | 74.55 | 25.83 | 63.72 | 4.14 | 59.58 | 0.00 | 0.00 |
June | 111.99 | 14.03 | 72.54 | 12.06 | 60.48 | 0.00 | 0.00 |
July | 112.03 | 6.05 | 66.52 | 5.67 | 60.85 | 0.00 | 0.00 |
August | 95.87 | 7.93 | 61.73 | 1.51 | 60.22 | 0.00 | 0.00 |
September | 65.89 | 20.26 | 49.28 | 0.04 | 49.25 | 0.00 | 0.00 |
October | 32.18 | 47.31 | 36.74 | 0.00 | 36.74 | 0.00 | 0.00 |
November | 12.41 | 76.14 | 31.20 | 0.00 | 31.20 | 0.00 | 0.00 |
December | 3.05 | 104.92 | 24.91 | 0.00 | 24.91 | 0.00 | 0.00 |
Annual Sum or Average | 51.90 | 49.92 | 48.17 | 2.02 | 46.15 | 0.00 | 0.00 |
Minimum of Months | 3.05 | 6.05 | 24.91 | 0.00 | 24.91 | 0.00 | 0.00 |
Maximum of Months | 112.03 | 104.92 | 72.54 | 12.06 | 60.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 462.07 | 325.96 | 459.35 | 315.94 | 143.40 | 0.00 | 0.00 |
February | 517.31 | 296.51 | 495.45 | 318.04 | 177.41 | 0.00 | 0.00 |
March | 553.87 | 227.19 | 502.64 | 294.37 | 208.27 | 0.00 | 0.00 |
April | 669.86 | 144.10 | 565.39 | 297.54 | 267.85 | 0.00 | 0.00 |
May | 621.60 | 98.54 | 497.24 | 248.10 | 249.13 | 0.00 | 0.00 |
June | 717.84 | 54.83 | 511.44 | 272.63 | 238.81 | 0.00 | 0.00 |
July | 727.50 | 26.60 | 488.58 | 240.04 | 248.53 | 0.00 | 0.00 |
August | 744.52 | 34.08 | 518.64 | 255.51 | 263.13 | 0.00 | 0.00 |
September | 685.75 | 77.71 | 507.90 | 284.81 | 223.09 | 0.00 | 0.00 |
October | 637.33 | 163.13 | 529.51 | 361.01 | 168.50 | 0.00 | 0.00 |
November | 531.67 | 252.69 | 498.08 | 343.02 | 155.06 | 0.00 | 0.00 |
December | 478.26 | 332.91 | 473.86 | 352.49 | 121.37 | 0.00 | 0.00 |
Annual Sum or Average | 612.65 | 168.88 | 503.89 | 298.45 | 205.44 | 0.00 | 0.00 |
Minimum of Months | 462.07 | 26.60 | 459.35 | 240.04 | 121.37 | 0.00 | 0.00 |
Maximum of Months | 744.52 | 332.91 | 565.39 | 361.01 | 267.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 167.88 | 327.62 | 225.95 | 105.99 | 119.96 | 0.00 | 0.00 |
February | 231.82 | 295.88 | 275.05 | 123.28 | 151.78 | 0.00 | 0.00 |
March | 358.85 | 224.71 | 362.44 | 173.62 | 188.82 | 0.00 | 0.00 |
April | 548.55 | 142.08 | 486.99 | 236.24 | 250.75 | 0.00 | 0.00 |
May | 580.37 | 96.98 | 474.59 | 230.14 | 244.45 | 0.00 | 0.00 |
June | 722.13 | 54.75 | 516.60 | 277.44 | 239.17 | 0.00 | 0.00 |
July | 704.88 | 26.39 | 477.07 | 232.28 | 244.79 | 0.00 | 0.00 |
August | 659.88 | 33.47 | 467.05 | 216.79 | 250.26 | 0.00 | 0.00 |
September | 506.39 | 75.84 | 386.71 | 181.96 | 204.75 | 0.00 | 0.00 |
October | 362.06 | 160.83 | 329.17 | 179.87 | 149.30 | 0.00 | 0.00 |
November | 225.38 | 253.20 | 259.30 | 129.24 | 130.06 | 0.00 | 0.00 |
December | 152.97 | 339.16 | 210.58 | 109.46 | 101.13 | 0.00 | 0.00 |
Annual Sum or Average | 436.05 | 168.61 | 372.99 | 183.26 | 189.73 | 0.00 | 0.00 |
Minimum of Months | 152.97 | 26.39 | 210.58 | 105.99 | 101.13 | 0.00 | 0.00 |
Maximum of Months | 722.13 | 339.16 | 516.60 | 277.44 | 250.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 526.48 | 426.35 | 531.28 | 363.85 | 167.43 | 0.00 | 0.00 |
February | 553.15 | 393.54 | 540.44 | 337.53 | 202.91 | 0.00 | 0.00 |
March | 466.52 | 316.62 | 442.92 | 209.26 | 233.65 | 0.00 | 0.00 |
April | 430.55 | 212.80 | 390.90 | 109.64 | 281.26 | 0.00 | 0.00 |
May | 367.17 | 147.44 | 315.28 | 49.07 | 266.22 | 0.00 | 0.00 |
June | 443.15 | 88.16 | 305.33 | 43.93 | 261.40 | 0.00 | 0.00 |
July | 489.71 | 51.63 | 308.13 | 38.02 | 270.11 | 0.00 | 0.00 |
August | 530.43 | 63.40 | 356.87 | 73.65 | 283.22 | 0.00 | 0.00 |
September | 573.57 | 127.88 | 423.52 | 178.38 | 245.14 | 0.00 | 0.00 |
October | 591.72 | 236.28 | 506.34 | 313.91 | 192.43 | 0.00 | 0.00 |
November | 567.78 | 340.67 | 548.98 | 370.49 | 178.49 | 0.00 | 0.00 |
December | 561.85 | 430.77 | 564.19 | 421.18 | 143.01 | 0.00 | 0.00 |
Annual Sum or Average | 508.19 | 235.48 | 435.53 | 208.39 | 227.15 | 0.00 | 0.00 |
Minimum of Months | 367.17 | 51.63 | 305.33 | 38.02 | 143.01 | 0.00 | 0.00 |
Maximum of Months | 591.72 | 430.77 | 564.19 | 421.18 | 283.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 477.13 | 329.14 | 465.27 | 321.33 | 143.94 | 0.00 | 0.00 |
February | 550.36 | 301.46 | 517.02 | 339.53 | 177.48 | 0.00 | 0.00 |
March | 529.92 | 233.28 | 477.84 | 269.46 | 208.38 | 0.00 | 0.00 |
April | 600.62 | 149.29 | 510.15 | 252.91 | 257.24 | 0.00 | 0.00 |
May | 551.65 | 100.07 | 442.88 | 199.12 | 243.76 | 0.00 | 0.00 |
June | 636.78 | 57.48 | 448.43 | 212.39 | 236.04 | 0.00 | 0.00 |
July | 637.18 | 26.09 | 422.33 | 174.97 | 247.36 | 0.00 | 0.00 |
August | 671.46 | 34.46 | 463.93 | 195.41 | 268.52 | 0.00 | 0.00 |
September | 659.98 | 79.56 | 486.90 | 263.45 | 223.44 | 0.00 | 0.00 |
October | 635.59 | 165.52 | 524.56 | 354.49 | 170.07 | 0.00 | 0.00 |
November | 532.16 | 252.23 | 495.25 | 341.71 | 153.54 | 0.00 | 0.00 |
December | 491.12 | 333.13 | 481.15 | 359.64 | 121.51 | 0.00 | 0.00 |
Annual Sum or Average | 581.13 | 171.15 | 477.58 | 273.23 | 204.35 | 0.00 | 0.00 |
Minimum of Months | 477.13 | 26.09 | 422.33 | 174.97 | 121.51 | 0.00 | 0.00 |
Maximum of Months | 671.46 | 333.13 | 524.56 | 359.64 | 268.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 197.88 | 343.78 | 231.88 | 111.38 | 120.50 | 0.00 | 0.00 |
February | 274.79 | 308.68 | 296.62 | 144.77 | 151.85 | 0.00 | 0.00 |
March | 343.08 | 234.85 | 337.64 | 148.72 | 188.93 | 0.00 | 0.00 |
April | 480.74 | 145.77 | 431.75 | 191.61 | 240.14 | 0.00 | 0.00 |
May | 509.75 | 97.03 | 420.24 | 181.16 | 239.08 | 0.00 | 0.00 |
June | 637.80 | 54.15 | 453.60 | 217.20 | 236.39 | 0.00 | 0.00 |
July | 614.28 | 25.37 | 410.82 | 167.20 | 243.61 | 0.00 | 0.00 |
August | 586.94 | 33.03 | 412.34 | 156.69 | 255.65 | 0.00 | 0.00 |
September | 482.73 | 77.74 | 365.71 | 160.61 | 205.10 | 0.00 | 0.00 |
October | 369.63 | 168.38 | 324.23 | 173.36 | 150.88 | 0.00 | 0.00 |
November | 235.47 | 259.27 | 256.47 | 127.93 | 128.54 | 0.00 | 0.00 |
December | 177.01 | 349.18 | 217.88 | 116.61 | 101.27 | 0.00 | 0.00 |
Annual Sum or Average | 409.73 | 174.11 | 346.68 | 158.04 | 188.64 | 0.00 | 0.00 |
Minimum of Months | 177.01 | 25.37 | 217.88 | 111.38 | 101.27 | 0.00 | 0.00 |
Maximum of Months | 637.80 | 349.18 | 453.60 | 217.20 | 255.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 444.38 | 171.51 | 395.94 | 307.91 | 88.03 | 0.00 | 0.00 |
February | 446.54 | 156.60 | 390.28 | 285.63 | 104.65 | 0.00 | 0.00 |
March | 340.85 | 121.24 | 290.21 | 177.09 | 113.12 | 0.00 | 0.00 |
April | 275.31 | 77.50 | 222.88 | 91.34 | 131.54 | 0.00 | 0.00 |
May | 193.37 | 50.60 | 150.00 | 33.93 | 116.07 | 0.00 | 0.00 |
June | 195.79 | 27.78 | 125.40 | 15.06 | 110.34 | 0.00 | 0.00 |
July | 233.51 | 12.11 | 138.81 | 21.78 | 117.03 | 0.00 | 0.00 |
August | 294.75 | 16.41 | 188.83 | 59.55 | 129.27 | 0.00 | 0.00 |
September | 378.32 | 39.95 | 268.06 | 150.89 | 117.17 | 0.00 | 0.00 |
October | 455.81 | 84.71 | 361.15 | 265.65 | 95.49 | 0.00 | 0.00 |
November | 472.56 | 132.13 | 407.38 | 313.53 | 93.85 | 0.00 | 0.00 |
December | 487.82 | 175.29 | 431.78 | 356.43 | 75.35 | 0.00 | 0.00 |
Annual Sum or Average | 351.04 | 88.47 | 280.27 | 172.64 | 107.62 | 0.00 | 0.00 |
Minimum of Months | 193.37 | 12.11 | 125.40 | 15.06 | 75.35 | 0.00 | 0.00 |
Maximum of Months | 487.82 | 175.29 | 431.78 | 356.43 | 131.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 50.65 | 981.45 | 256.06 | 0.00 | 256.06 | 0.00 | 0.00 |
February | 112.26 | 883.75 | 320.04 | 0.00 | 320.04 | 0.00 | 0.00 |
March | 251.22 | 681.30 | 403.77 | 0.01 | 403.75 | 0.00 | 0.00 |
April | 427.28 | 426.68 | 514.99 | 6.90 | 508.09 | 0.00 | 0.00 |
May | 589.20 | 293.82 | 557.42 | 36.22 | 521.20 | 0.00 | 0.00 |
June | 909.23 | 178.25 | 634.64 | 105.54 | 529.10 | 0.00 | 0.00 |
July | 908.77 | 106.20 | 581.96 | 49.60 | 532.35 | 0.00 | 0.00 |
August | 770.88 | 128.08 | 540.08 | 13.22 | 526.86 | 0.00 | 0.00 |
September | 528.13 | 253.88 | 431.15 | 0.31 | 430.84 | 0.00 | 0.00 |
October | 245.76 | 502.71 | 321.40 | 0.00 | 321.40 | 0.00 | 0.00 |
November | 82.13 | 763.81 | 272.95 | 0.00 | 272.95 | 0.00 | 0.00 |
December | 14.71 | 1020.21 | 217.95 | 0.00 | 217.95 | 0.00 | 0.00 |
Annual Sum or Average | 409.08 | 516.58 | 421.40 | 17.68 | 403.72 | 0.00 | 0.00 |
Minimum of Months | 14.71 | 106.20 | 217.95 | 0.00 | 217.95 | 0.00 | 0.00 |
Maximum of Months | 909.23 | 1020.21 | 634.64 | 105.54 | 532.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 43.79 | 1013.26 | 256.06 | 0.00 | 256.06 | 0.00 | 0.00 |
February | 103.19 | 911.78 | 320.04 | 0.00 | 320.04 | 0.00 | 0.00 |
March | 239.41 | 702.11 | 403.77 | 0.01 | 403.75 | 0.00 | 0.00 |
April | 413.70 | 438.39 | 514.99 | 6.90 | 508.09 | 0.00 | 0.00 |
May | 574.67 | 302.03 | 557.42 | 36.22 | 521.20 | 0.00 | 0.00 |
June | 895.67 | 184.04 | 634.64 | 105.54 | 529.10 | 0.00 | 0.00 |
July | 895.35 | 111.43 | 581.96 | 49.60 | 532.35 | 0.00 | 0.00 |
August | 757.58 | 133.82 | 540.08 | 13.22 | 526.86 | 0.00 | 0.00 |
September | 516.82 | 262.39 | 431.15 | 0.31 | 430.84 | 0.00 | 0.00 |
October | 236.92 | 517.95 | 321.40 | 0.00 | 321.40 | 0.00 | 0.00 |
November | 75.12 | 788.40 | 272.95 | 0.00 | 272.95 | 0.00 | 0.00 |
December | 11.63 | 1056.18 | 217.95 | 0.00 | 217.95 | 0.00 | 0.00 |
Annual Sum or Average | 398.54 | 533.33 | 421.40 | 17.68 | 403.72 | 0.00 | 0.00 |
Minimum of Months | 11.63 | 111.43 | 217.95 | 0.00 | 217.95 | 0.00 | 0.00 |
Maximum of Months | 895.67 | 1056.18 | 634.64 | 105.54 | 532.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 660.44 | 690.01 | 685.27 | 421.92 | 263.35 | 0.00 | 0.00 |
February | 789.83 | 633.75 | 770.46 | 441.29 | 329.17 | 0.00 | 0.00 |
March | 976.31 | 493.30 | 865.04 | 467.96 | 397.07 | 0.00 | 0.00 |
April | 1315.08 | 324.70 | 1052.32 | 533.75 | 518.57 | 0.00 | 0.00 |
May | 1308.61 | 234.59 | 971.77 | 478.21 | 493.56 | 0.00 | 0.00 |
June | 1564.71 | 147.48 | 1027.99 | 550.03 | 477.96 | 0.00 | 0.00 |
July | 1564.90 | 90.56 | 965.59 | 472.29 | 493.30 | 0.00 | 0.00 |
August | 1535.53 | 106.39 | 985.63 | 472.27 | 513.37 | 0.00 | 0.00 |
September | 1308.39 | 185.52 | 894.57 | 466.75 | 427.82 | 0.00 | 0.00 |
October | 1085.37 | 352.32 | 858.64 | 540.86 | 317.78 | 0.00 | 0.00 |
November | 800.51 | 531.40 | 757.34 | 472.24 | 285.11 | 0.00 | 0.00 |
December | 653.63 | 702.39 | 684.41 | 461.93 | 222.48 | 0.00 | 0.00 |
Annual Sum or Average | 1131.79 | 373.08 | 876.84 | 481.69 | 395.15 | 0.00 | 0.00 |
Minimum of Months | 653.63 | 90.56 | 684.41 | 421.92 | 222.48 | 0.00 | 0.00 |
Maximum of Months | 1564.90 | 702.39 | 1052.32 | 550.03 | 518.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1127.13 | 747.02 | 1095.67 | 783.80 | 311.87 | 0.00 | 0.00 |
February | 1162.34 | 693.79 | 1103.20 | 727.10 | 376.10 | 0.00 | 0.00 |
March | 940.74 | 564.17 | 877.17 | 450.80 | 426.37 | 0.00 | 0.00 |
April | 825.06 | 385.01 | 743.90 | 234.88 | 509.03 | 0.00 | 0.00 |
May | 659.46 | 268.99 | 572.93 | 98.80 | 474.13 | 0.00 | 0.00 |
June | 763.44 | 162.99 | 536.77 | 74.51 | 462.26 | 0.00 | 0.00 |
July | 863.38 | 98.20 | 552.84 | 72.45 | 480.40 | 0.00 | 0.00 |
August | 977.47 | 120.12 | 665.81 | 156.13 | 509.68 | 0.00 | 0.00 |
September | 1119.39 | 233.41 | 830.16 | 384.22 | 445.95 | 0.00 | 0.00 |
October | 1219.74 | 418.51 | 1029.49 | 676.23 | 353.26 | 0.00 | 0.00 |
November | 1206.57 | 598.51 | 1130.58 | 798.10 | 332.48 | 0.00 | 0.00 |
December | 1216.67 | 755.88 | 1173.83 | 907.30 | 266.52 | 0.00 | 0.00 |
Annual Sum or Average | 1005.81 | 419.13 | 857.89 | 445.54 | 412.36 | 0.00 | 0.00 |
Minimum of Months | 659.46 | 98.20 | 536.77 | 72.45 | 266.52 | 0.00 | 0.00 |
Maximum of Months | 1219.74 | 755.88 | 1173.83 | 907.30 | 509.68 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.411307E+10 | 0.158105E+10 | 0.365721E+10 | 0.284409E+10 | 0.813124E+09 | 0.00 | 0.00 |
February | 0.373070E+10 | 0.131988E+10 | 0.325610E+10 | 0.238302E+10 | 0.873079E+09 | 0.00 | 0.00 |
March | 0.314210E+10 | 0.117034E+10 | 0.268063E+10 | 0.163574E+10 | 0.104489E+10 | 0.00 | 0.00 |
April | 0.241983E+10 | 0.796212E+09 | 0.199231E+10 | 0.816477E+09 | 0.117584E+10 | 0.00 | 0.00 |
May | 0.170873E+10 | 0.585930E+09 | 0.138554E+10 | 0.313445E+09 | 0.107209E+10 | 0.00 | 0.00 |
June | 0.160599E+10 | 0.367001E+09 | 0.112091E+10 | 0.134596E+09 | 0.986310E+09 | 0.00 | 0.00 |
July | 0.199466E+10 | 0.234228E+09 | 0.128213E+10 | 0.201175E+09 | 0.108095E+10 | 0.00 | 0.00 |
August | 0.259144E+10 | 0.283503E+09 | 0.174413E+10 | 0.550093E+09 | 0.119404E+10 | 0.00 | 0.00 |
September | 0.330871E+10 | 0.498372E+09 | 0.239615E+10 | 0.134882E+10 | 0.104733E+10 | 0.00 | 0.00 |
October | 0.416161E+10 | 0.890309E+09 | 0.333581E+10 | 0.245376E+10 | 0.882050E+09 | 0.00 | 0.00 |
November | 0.420889E+10 | 0.123604E+10 | 0.364151E+10 | 0.280257E+10 | 0.838938E+09 | 0.00 | 0.00 |
December | 0.450595E+10 | 0.162245E+10 | 0.398823E+10 | 0.329223E+10 | 0.695993E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.374917E+11 | 0.105853E+11 | 0.304806E+11 | 0.187760E+11 | 0.117046E+11 | 0.00 | 0.00 |
Minimum of Months | 0.160599E+10 | 0.234228E+09 | 0.112091E+10 | 0.134596E+09 | 0.695993E+09 | 0.00 | 0.00 |
Maximum of Months | 0.450595E+10 | 0.162245E+10 | 0.398823E+10 | 0.329223E+10 | 0.119404E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115207E+11 | 0.455100E+10 | 0.102985E+11 | 0.800876E+10 | 0.228970E+10 | 0.00 | 0.00 |
February | 0.104526E+11 | 0.379477E+10 | 0.916896E+10 | 0.671042E+10 | 0.245853E+10 | 0.00 | 0.00 |
March | 0.881654E+10 | 0.334787E+10 | 0.754847E+10 | 0.460613E+10 | 0.294234E+10 | 0.00 | 0.00 |
April | 0.682608E+10 | 0.223395E+10 | 0.561022E+10 | 0.229915E+10 | 0.331108E+10 | 0.00 | 0.00 |
May | 0.487906E+10 | 0.161702E+10 | 0.390158E+10 | 0.882641E+09 | 0.301894E+10 | 0.00 | 0.00 |
June | 0.460923E+10 | 0.987823E+09 | 0.315640E+10 | 0.379014E+09 | 0.277738E+10 | 0.00 | 0.00 |
July | 0.567883E+10 | 0.623116E+09 | 0.361039E+10 | 0.566496E+09 | 0.304390E+10 | 0.00 | 0.00 |
August | 0.732687E+10 | 0.769053E+09 | 0.491137E+10 | 0.154903E+10 | 0.336234E+10 | 0.00 | 0.00 |
September | 0.931819E+10 | 0.137566E+10 | 0.674739E+10 | 0.379819E+10 | 0.294920E+10 | 0.00 | 0.00 |
October | 0.116904E+11 | 0.251574E+10 | 0.939343E+10 | 0.690963E+10 | 0.248379E+10 | 0.00 | 0.00 |
November | 0.117982E+11 | 0.353454E+10 | 0.102543E+11 | 0.789186E+10 | 0.236239E+10 | 0.00 | 0.00 |
December | 0.126250E+11 | 0.468182E+10 | 0.112306E+11 | 0.927071E+10 | 0.195987E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.105542E+12 | 0.300324E+11 | 0.858315E+11 | 0.528720E+11 | 0.329595E+11 | 0.00 | 0.00 |
Minimum of Months | 0.460923E+10 | 0.623116E+09 | 0.315640E+10 | 0.379014E+09 | 0.195987E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126250E+11 | 0.468182E+10 | 0.112306E+11 | 0.927071E+10 | 0.336234E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.151966E+11 | 0.614340E+10 | 0.133783E+11 | 0.104038E+11 | 0.297446E+10 | 0.00 | 0.00 |
February | 0.138041E+11 | 0.512140E+10 | 0.119110E+11 | 0.871722E+10 | 0.319378E+10 | 0.00 | 0.00 |
March | 0.116316E+11 | 0.455574E+10 | 0.980589E+10 | 0.598362E+10 | 0.382227E+10 | 0.00 | 0.00 |
April | 0.902480E+10 | 0.304311E+10 | 0.728800E+10 | 0.298672E+10 | 0.430128E+10 | 0.00 | 0.00 |
May | 0.640372E+10 | 0.223705E+10 | 0.506838E+10 | 0.114660E+10 | 0.392177E+10 | 0.00 | 0.00 |
June | 0.606163E+10 | 0.135784E+10 | 0.410034E+10 | 0.492361E+09 | 0.360798E+10 | 0.00 | 0.00 |
July | 0.751665E+10 | 0.828111E+09 | 0.469011E+10 | 0.735911E+09 | 0.395420E+10 | 0.00 | 0.00 |
August | 0.970964E+10 | 0.100177E+10 | 0.638014E+10 | 0.201227E+10 | 0.436787E+10 | 0.00 | 0.00 |
September | 0.123211E+11 | 0.180714E+10 | 0.876524E+10 | 0.493407E+10 | 0.383118E+10 | 0.00 | 0.00 |
October | 0.154366E+11 | 0.335064E+10 | 0.122026E+11 | 0.897601E+10 | 0.322659E+10 | 0.00 | 0.00 |
November | 0.155684E+11 | 0.475430E+10 | 0.133209E+11 | 0.102520E+11 | 0.306888E+10 | 0.00 | 0.00 |
December | 0.166609E+11 | 0.631377E+10 | 0.145892E+11 | 0.120432E+11 | 0.254598E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.139336E+12 | 0.405143E+11 | 0.111500E+12 | 0.686838E+11 | 0.428162E+11 | 0.00 | 0.00 |
Minimum of Months | 0.606163E+10 | 0.828111E+09 | 0.410034E+10 | 0.492361E+09 | 0.254598E+10 | 0.00 | 0.00 |
Maximum of Months | 0.166609E+11 | 0.631377E+10 | 0.145892E+11 | 0.120432E+11 | 0.436787E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.127969E+10 | 0.889939E+09 | 0.124618E+10 | 0.860644E+09 | 0.385540E+09 | 0.00 | 0.00 |
February | 0.133592E+10 | 0.735849E+09 | 0.125077E+10 | 0.821399E+09 | 0.429371E+09 | 0.00 | 0.00 |
March | 0.142426E+10 | 0.633034E+09 | 0.127985E+10 | 0.721728E+09 | 0.558127E+09 | 0.00 | 0.00 |
April | 0.156513E+10 | 0.394502E+09 | 0.132231E+10 | 0.655531E+09 | 0.666775E+09 | 0.00 | 0.00 |
May | 0.148489E+10 | 0.275010E+09 | 0.118622E+10 | 0.533331E+09 | 0.652887E+09 | 0.00 | 0.00 |
June | 0.165712E+10 | 0.153995E+09 | 0.116234E+10 | 0.550518E+09 | 0.611824E+09 | 0.00 | 0.00 |
July | 0.171456E+10 | 73919486.42 | 0.113116E+10 | 0.468634E+09 | 0.662522E+09 | 0.00 | 0.00 |
August | 0.180744E+10 | 96480343.29 | 0.124260E+10 | 0.523397E+09 | 0.719205E+09 | 0.00 | 0.00 |
September | 0.171866E+10 | 0.212337E+09 | 0.126203E+10 | 0.682873E+09 | 0.579160E+09 | 0.00 | 0.00 |
October | 0.170661E+10 | 0.452175E+09 | 0.140499E+10 | 0.949466E+09 | 0.455520E+09 | 0.00 | 0.00 |
November | 0.138088E+10 | 0.664641E+09 | 0.128369E+10 | 0.885716E+09 | 0.397972E+09 | 0.00 | 0.00 |
December | 0.131667E+10 | 0.901960E+09 | 0.128872E+10 | 0.963268E+09 | 0.325450E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.183918E+11 | 0.548384E+10 | 0.150609E+11 | 0.861650E+10 | 0.644435E+10 | 0.00 | 0.00 |
Minimum of Months | 0.127969E+10 | 73919486.42 | 0.113116E+10 | 0.468634E+09 | 0.325450E+09 | 0.00 | 0.00 |
Maximum of Months | 0.180744E+10 | 0.901960E+09 | 0.140499E+10 | 0.963268E+09 | 0.719205E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.526878E+09 | 0.932095E+09 | 0.621070E+09 | 0.298319E+09 | 0.322751E+09 | 0.00 | 0.00 |
February | 0.664319E+09 | 0.755473E+09 | 0.717592E+09 | 0.350236E+09 | 0.367356E+09 | 0.00 | 0.00 |
March | 0.918990E+09 | 0.639444E+09 | 0.904345E+09 | 0.398320E+09 | 0.506025E+09 | 0.00 | 0.00 |
April | 0.125126E+10 | 0.385902E+09 | 0.111909E+10 | 0.496654E+09 | 0.622434E+09 | 0.00 | 0.00 |
May | 0.137122E+10 | 0.266670E+09 | 0.112556E+10 | 0.485216E+09 | 0.640348E+09 | 0.00 | 0.00 |
June | 0.165946E+10 | 0.144737E+09 | 0.117572E+10 | 0.562988E+09 | 0.612736E+09 | 0.00 | 0.00 |
July | 0.165247E+10 | 71830998.70 | 0.110034E+10 | 0.447839E+09 | 0.652497E+09 | 0.00 | 0.00 |
August | 0.157914E+10 | 92556260.76 | 0.110441E+10 | 0.419691E+09 | 0.684721E+09 | 0.00 | 0.00 |
September | 0.125599E+10 | 0.208148E+09 | 0.947924E+09 | 0.416301E+09 | 0.531623E+09 | 0.00 | 0.00 |
October | 0.989905E+09 | 0.462988E+09 | 0.868419E+09 | 0.464315E+09 | 0.404104E+09 | 0.00 | 0.00 |
November | 0.606318E+09 | 0.687565E+09 | 0.664771E+09 | 0.331600E+09 | 0.333171E+09 | 0.00 | 0.00 |
December | 0.471146E+09 | 0.947816E+09 | 0.583573E+09 | 0.312337E+09 | 0.271236E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.129471E+11 | 0.559522E+10 | 0.109328E+11 | 0.498382E+10 | 0.594900E+10 | 0.00 | 0.00 |
Minimum of Months | 0.471146E+09 | 71830998.70 | 0.583573E+09 | 0.298319E+09 | 0.271236E+09 | 0.00 | 0.00 |
Maximum of Months | 0.165946E+10 | 0.947816E+09 | 0.117572E+10 | 0.562988E+09 | 0.684721E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.651719E+09 | 0.264178E+09 | 0.578361E+09 | 0.449770E+09 | 0.128590E+09 | 0.00 | 0.00 |
February | 0.590998E+09 | 0.221395E+09 | 0.514928E+09 | 0.376856E+09 | 0.138072E+09 | 0.00 | 0.00 |
March | 0.497252E+09 | 0.194503E+09 | 0.423922E+09 | 0.258679E+09 | 0.165243E+09 | 0.00 | 0.00 |
April | 0.386624E+09 | 0.126872E+09 | 0.315071E+09 | 0.129120E+09 | 0.185952E+09 | 0.00 | 0.00 |
May | 0.276814E+09 | 90455274.07 | 0.219114E+09 | 49568964.22 | 0.169545E+09 | 0.00 | 0.00 |
June | 0.268072E+09 | 52704460.44 | 0.177265E+09 | 21285372.45 | 0.155980E+09 | 0.00 | 0.00 |
July | 0.332237E+09 | 29686035.25 | 0.202761E+09 | 31814303.90 | 0.170947E+09 | 0.00 | 0.00 |
August | 0.424391E+09 | 37232546.56 | 0.275824E+09 | 86993003.94 | 0.188831E+09 | 0.00 | 0.00 |
September | 0.533246E+09 | 72901039.60 | 0.378934E+09 | 0.213306E+09 | 0.165628E+09 | 0.00 | 0.00 |
October | 0.665450E+09 | 0.141337E+09 | 0.527535E+09 | 0.388044E+09 | 0.139491E+09 | 0.00 | 0.00 |
November | 0.668874E+09 | 0.204414E+09 | 0.575878E+09 | 0.443205E+09 | 0.132673E+09 | 0.00 | 0.00 |
December | 0.715014E+09 | 0.272640E+09 | 0.630708E+09 | 0.520641E+09 | 0.110067E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.601069E+10 | 0.170832E+10 | 0.482030E+10 | 0.296928E+10 | 0.185102E+10 | 0.00 | 0.00 |
Minimum of Months | 0.268072E+09 | 29686035.25 | 0.177265E+09 | 21285372.45 | 0.110067E+09 | 0.00 | 0.00 |
Maximum of Months | 0.715014E+09 | 0.272640E+09 | 0.630708E+09 | 0.520641E+09 | 0.188831E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 21938556.71 | 0.271784E+09 | 78395194.18 | 0.00 | 78395194.18 | 0.00 | 0.00 |
February | 39110960.12 | 0.217932E+09 | 88498821.31 | 0.00 | 88498821.31 | 0.00 | 0.00 |
March | 89222696.38 | 0.180505E+09 | 0.123615E+09 | 4297.01 | 0.123611E+09 | 0.00 | 0.00 |
April | 0.142515E+09 | 0.103458E+09 | 0.152580E+09 | 2043871.97 | 0.150536E+09 | 0.00 | 0.00 |
May | 0.199671E+09 | 69176447.67 | 0.170657E+09 | 11088084.06 | 0.159568E+09 | 0.00 | 0.00 |
June | 0.290284E+09 | 36364356.86 | 0.188031E+09 | 31269876.03 | 0.156761E+09 | 0.00 | 0.00 |
July | 0.300061E+09 | 16193343.01 | 0.178169E+09 | 15186292.66 | 0.162983E+09 | 0.00 | 0.00 |
August | 0.256780E+09 | 21252983.01 | 0.165349E+09 | 4046567.42 | 0.161302E+09 | 0.00 | 0.00 |
September | 0.170781E+09 | 52509472.69 | 0.127739E+09 | 91026.49 | 0.127648E+09 | 0.00 | 0.00 |
October | 86177677.24 | 0.126704E+09 | 98399454.57 | 0.00 | 98399454.57 | 0.00 | 0.00 |
November | 32154928.73 | 0.197362E+09 | 80868758.46 | 0.00 | 80868758.46 | 0.00 | 0.00 |
December | 8156449.71 | 0.281022E+09 | 66726175.04 | 0.00 | 66726175.04 | 0.00 | 0.00 |
Annual Sum or Average | 0.163685E+10 | 0.157426E+10 | 0.151903E+10 | 63730015.63 | 0.145530E+10 | 0.00 | 0.00 |
Minimum of Months | 8156449.71 | 16193343.01 | 66726175.04 | 0.00 | 66726175.04 | 0.00 | 0.00 |
Maximum of Months | 0.300061E+09 | 0.281022E+09 | 0.188031E+09 | 31269876.03 | 0.162983E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.123761E+10 | 0.873050E+09 | 0.123031E+10 | 0.846218E+09 | 0.384093E+09 | 0.00 | 0.00 |
February | 0.125147E+10 | 0.717313E+09 | 0.119858E+10 | 0.769391E+09 | 0.429191E+09 | 0.00 | 0.00 |
March | 0.148349E+10 | 0.608504E+09 | 0.134627E+10 | 0.788435E+09 | 0.557833E+09 | 0.00 | 0.00 |
April | 0.173628E+10 | 0.373511E+09 | 0.146549E+10 | 0.771218E+09 | 0.694275E+09 | 0.00 | 0.00 |
May | 0.166491E+10 | 0.263922E+09 | 0.133180E+10 | 0.664517E+09 | 0.667283E+09 | 0.00 | 0.00 |
June | 0.186064E+10 | 0.142119E+09 | 0.132566E+10 | 0.706653E+09 | 0.619005E+09 | 0.00 | 0.00 |
July | 0.194854E+10 | 71235298.67 | 0.130860E+10 | 0.642930E+09 | 0.665670E+09 | 0.00 | 0.00 |
August | 0.199413E+10 | 91267645.87 | 0.138913E+10 | 0.684353E+09 | 0.704775E+09 | 0.00 | 0.00 |
September | 0.177746E+10 | 0.201423E+09 | 0.131647E+10 | 0.738223E+09 | 0.578250E+09 | 0.00 | 0.00 |
October | 0.170702E+10 | 0.436918E+09 | 0.141823E+10 | 0.966926E+09 | 0.451303E+09 | 0.00 | 0.00 |
November | 0.137808E+10 | 0.654960E+09 | 0.129101E+10 | 0.889101E+09 | 0.401914E+09 | 0.00 | 0.00 |
December | 0.128096E+10 | 0.891679E+09 | 0.126917E+10 | 0.944102E+09 | 0.325072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.193206E+11 | 0.532590E+10 | 0.158907E+11 | 0.941206E+10 | 0.647866E+10 | 0.00 | 0.00 |
Minimum of Months | 0.123761E+10 | 71235298.67 | 0.119858E+10 | 0.642930E+09 | 0.325072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.199413E+10 | 0.891679E+09 | 0.146549E+10 | 0.966926E+09 | 0.704775E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.449649E+09 | 0.877491E+09 | 0.605197E+09 | 0.283893E+09 | 0.321304E+09 | 0.00 | 0.00 |
February | 0.560831E+09 | 0.715784E+09 | 0.665402E+09 | 0.298227E+09 | 0.367175E+09 | 0.00 | 0.00 |
March | 0.961143E+09 | 0.601870E+09 | 0.970759E+09 | 0.465027E+09 | 0.505732E+09 | 0.00 | 0.00 |
April | 0.142185E+10 | 0.368261E+09 | 0.126228E+10 | 0.612341E+09 | 0.649934E+09 | 0.00 | 0.00 |
May | 0.155447E+10 | 0.259750E+09 | 0.127114E+10 | 0.616401E+09 | 0.654743E+09 | 0.00 | 0.00 |
June | 0.187177E+10 | 0.141901E+09 | 0.133904E+10 | 0.719123E+09 | 0.619916E+09 | 0.00 | 0.00 |
July | 0.188795E+10 | 70676761.56 | 0.127778E+10 | 0.622134E+09 | 0.655645E+09 | 0.00 | 0.00 |
August | 0.176743E+10 | 89639121.45 | 0.125094E+10 | 0.580648E+09 | 0.670290E+09 | 0.00 | 0.00 |
September | 0.131257E+10 | 0.196585E+09 | 0.100236E+10 | 0.471651E+09 | 0.530713E+09 | 0.00 | 0.00 |
October | 0.969753E+09 | 0.430770E+09 | 0.881662E+09 | 0.481775E+09 | 0.399887E+09 | 0.00 | 0.00 |
November | 0.584193E+09 | 0.656287E+09 | 0.672096E+09 | 0.334984E+09 | 0.337112E+09 | 0.00 | 0.00 |
December | 0.409724E+09 | 0.908401E+09 | 0.564029E+09 | 0.293171E+09 | 0.270858E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.137513E+11 | 0.531741E+10 | 0.117627E+11 | 0.577938E+10 | 0.598331E+10 | 0.00 | 0.00 |
Minimum of Months | 0.409724E+09 | 70676761.56 | 0.564029E+09 | 0.283893E+09 | 0.270858E+09 | 0.00 | 0.00 |
Maximum of Months | 0.188795E+10 | 0.908401E+09 | 0.133904E+10 | 0.719123E+09 | 0.670290E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.141012E+10 | 0.114195E+10 | 0.142298E+10 | 0.974527E+09 | 0.448450E+09 | 0.00 | 0.00 |
February | 0.133818E+10 | 0.952043E+09 | 0.130742E+10 | 0.816542E+09 | 0.490882E+09 | 0.00 | 0.00 |
March | 0.124953E+10 | 0.848039E+09 | 0.118631E+10 | 0.560495E+09 | 0.625818E+09 | 0.00 | 0.00 |
April | 0.111598E+10 | 0.551575E+09 | 0.101321E+10 | 0.284194E+09 | 0.729017E+09 | 0.00 | 0.00 |
May | 0.983438E+09 | 0.394906E+09 | 0.844459E+09 | 0.131423E+09 | 0.713037E+09 | 0.00 | 0.00 |
June | 0.114864E+10 | 0.228521E+09 | 0.791422E+09 | 0.113861E+09 | 0.677561E+09 | 0.00 | 0.00 |
July | 0.131164E+10 | 0.138292E+09 | 0.825301E+09 | 0.101831E+09 | 0.723470E+09 | 0.00 | 0.00 |
August | 0.142070E+10 | 0.169805E+09 | 0.955834E+09 | 0.197256E+09 | 0.758578E+09 | 0.00 | 0.00 |
September | 0.148669E+10 | 0.331465E+09 | 0.109777E+10 | 0.462371E+09 | 0.635400E+09 | 0.00 | 0.00 |
October | 0.158486E+10 | 0.632856E+09 | 0.135619E+10 | 0.840783E+09 | 0.515404E+09 | 0.00 | 0.00 |
November | 0.147169E+10 | 0.883017E+09 | 0.142296E+10 | 0.960302E+09 | 0.462654E+09 | 0.00 | 0.00 |
December | 0.150485E+10 | 0.115378E+10 | 0.151112E+10 | 0.112808E+10 | 0.383036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.160263E+11 | 0.742625E+10 | 0.137350E+11 | 0.657167E+10 | 0.716331E+10 | 0.00 | 0.00 |
Minimum of Months | 0.983438E+09 | 0.138292E+09 | 0.791422E+09 | 0.101831E+09 | 0.383036E+09 | 0.00 | 0.00 |
Maximum of Months | 0.158486E+10 | 0.115378E+10 | 0.151112E+10 | 0.112808E+10 | 0.758578E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.127794E+10 | 0.881566E+09 | 0.124618E+10 | 0.860644E+09 | 0.385540E+09 | 0.00 | 0.00 |
February | 0.133144E+10 | 0.729296E+09 | 0.125077E+10 | 0.821399E+09 | 0.429371E+09 | 0.00 | 0.00 |
March | 0.141935E+10 | 0.624813E+09 | 0.127985E+10 | 0.721728E+09 | 0.558127E+09 | 0.00 | 0.00 |
April | 0.155680E+10 | 0.386951E+09 | 0.132231E+10 | 0.655531E+09 | 0.666775E+09 | 0.00 | 0.00 |
May | 0.147755E+10 | 0.268022E+09 | 0.118622E+10 | 0.533331E+09 | 0.652887E+09 | 0.00 | 0.00 |
June | 0.165053E+10 | 0.148977E+09 | 0.116234E+10 | 0.550518E+09 | 0.611824E+09 | 0.00 | 0.00 |
July | 0.170662E+10 | 69874539.25 | 0.113116E+10 | 0.468634E+09 | 0.662522E+09 | 0.00 | 0.00 |
August | 0.179845E+10 | 92308867.63 | 0.124260E+10 | 0.523397E+09 | 0.719205E+09 | 0.00 | 0.00 |
September | 0.171068E+10 | 0.206208E+09 | 0.126203E+10 | 0.682873E+09 | 0.579160E+09 | 0.00 | 0.00 |
October | 0.170236E+10 | 0.443331E+09 | 0.140499E+10 | 0.949466E+09 | 0.455520E+09 | 0.00 | 0.00 |
November | 0.137936E+10 | 0.653781E+09 | 0.128369E+10 | 0.885716E+09 | 0.397972E+09 | 0.00 | 0.00 |
December | 0.131542E+10 | 0.892268E+09 | 0.128872E+10 | 0.963268E+09 | 0.325450E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.183265E+11 | 0.539740E+10 | 0.150609E+11 | 0.861650E+10 | 0.644435E+10 | 0.00 | 0.00 |
Minimum of Months | 0.127794E+10 | 69874539.25 | 0.113116E+10 | 0.468634E+09 | 0.325450E+09 | 0.00 | 0.00 |
Maximum of Months | 0.179845E+10 | 0.892268E+09 | 0.140499E+10 | 0.963268E+09 | 0.719205E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.529992E+09 | 0.920788E+09 | 0.621070E+09 | 0.298319E+09 | 0.322751E+09 | 0.00 | 0.00 |
February | 0.664763E+09 | 0.746754E+09 | 0.717592E+09 | 0.350236E+09 | 0.367356E+09 | 0.00 | 0.00 |
March | 0.918917E+09 | 0.629024E+09 | 0.904345E+09 | 0.398320E+09 | 0.506025E+09 | 0.00 | 0.00 |
April | 0.124609E+10 | 0.377848E+09 | 0.111909E+10 | 0.496654E+09 | 0.622434E+09 | 0.00 | 0.00 |
May | 0.136532E+10 | 0.259893E+09 | 0.112556E+10 | 0.485216E+09 | 0.640348E+09 | 0.00 | 0.00 |
June | 0.165318E+10 | 0.140368E+09 | 0.117572E+10 | 0.562988E+09 | 0.612736E+09 | 0.00 | 0.00 |
July | 0.164528E+10 | 67958112.28 | 0.110034E+10 | 0.447839E+09 | 0.652497E+09 | 0.00 | 0.00 |
August | 0.157205E+10 | 88467581.18 | 0.110441E+10 | 0.419691E+09 | 0.684721E+09 | 0.00 | 0.00 |
September | 0.125123E+10 | 0.201514E+09 | 0.947924E+09 | 0.416301E+09 | 0.531623E+09 | 0.00 | 0.00 |
October | 0.990013E+09 | 0.451002E+09 | 0.868419E+09 | 0.464315E+09 | 0.404104E+09 | 0.00 | 0.00 |
November | 0.610336E+09 | 0.672031E+09 | 0.664771E+09 | 0.331600E+09 | 0.333171E+09 | 0.00 | 0.00 |
December | 0.474109E+09 | 0.935236E+09 | 0.583573E+09 | 0.312337E+09 | 0.271236E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.129213E+11 | 0.549089E+10 | 0.109328E+11 | 0.498382E+10 | 0.594900E+10 | 0.00 | 0.00 |
Minimum of Months | 0.474109E+09 | 67958112.28 | 0.583573E+09 | 0.298319E+09 | 0.271236E+09 | 0.00 | 0.00 |
Maximum of Months | 0.165318E+10 | 0.935236E+09 | 0.117572E+10 | 0.562988E+09 | 0.684721E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119022E+10 | 0.459368E+09 | 0.106049E+10 | 0.824703E+09 | 0.235784E+09 | 0.00 | 0.00 |
February | 0.108027E+10 | 0.378841E+09 | 0.944177E+09 | 0.691007E+09 | 0.253170E+09 | 0.00 | 0.00 |
March | 0.912940E+09 | 0.324733E+09 | 0.777308E+09 | 0.474317E+09 | 0.302991E+09 | 0.00 | 0.00 |
April | 0.713604E+09 | 0.200873E+09 | 0.577717E+09 | 0.236755E+09 | 0.340963E+09 | 0.00 | 0.00 |
May | 0.517935E+09 | 0.135524E+09 | 0.401770E+09 | 90890125.98 | 0.310880E+09 | 0.00 | 0.00 |
June | 0.507487E+09 | 72010808.88 | 0.325035E+09 | 39029062.12 | 0.286006E+09 | 0.00 | 0.00 |
July | 0.625443E+09 | 32423758.58 | 0.371785E+09 | 58335011.33 | 0.313450E+09 | 0.00 | 0.00 |
August | 0.789452E+09 | 43942666.22 | 0.505753E+09 | 0.159511E+09 | 0.346242E+09 | 0.00 | 0.00 |
September | 0.980597E+09 | 0.103538E+09 | 0.694817E+09 | 0.391119E+09 | 0.303698E+09 | 0.00 | 0.00 |
October | 0.122085E+10 | 0.226879E+09 | 0.967293E+09 | 0.711521E+09 | 0.255772E+09 | 0.00 | 0.00 |
November | 0.122487E+10 | 0.342481E+09 | 0.105593E+10 | 0.812665E+09 | 0.243270E+09 | 0.00 | 0.00 |
December | 0.130657E+10 | 0.469485E+09 | 0.115647E+10 | 0.954653E+09 | 0.201820E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110702E+11 | 0.279010E+10 | 0.883855E+10 | 0.544450E+10 | 0.339405E+10 | 0.00 | 0.00 |
Minimum of Months | 0.507487E+09 | 32423758.58 | 0.325035E+09 | 39029062.12 | 0.201820E+09 | 0.00 | 0.00 |
Maximum of Months | 0.130657E+10 | 0.469485E+09 | 0.115647E+10 | 0.954653E+09 | 0.346242E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.135664E+09 | 0.262871E+10 | 0.685841E+09 | 0.00 | 0.685841E+09 | 0.00 | 0.00 |
February | 0.271573E+09 | 0.213798E+10 | 0.774233E+09 | 0.00 | 0.774233E+09 | 0.00 | 0.00 |
March | 0.672881E+09 | 0.182478E+10 | 0.108145E+10 | 37592.41 | 0.108141E+10 | 0.00 | 0.00 |
April | 0.110750E+10 | 0.110595E+10 | 0.133485E+10 | 17880832.21 | 0.131696E+10 | 0.00 | 0.00 |
May | 0.157813E+10 | 0.786980E+09 | 0.149299E+10 | 97004202.60 | 0.139599E+10 | 0.00 | 0.00 |
June | 0.235672E+10 | 0.462019E+09 | 0.164499E+10 | 0.273565E+09 | 0.137142E+10 | 0.00 | 0.00 |
July | 0.243406E+10 | 0.284453E+09 | 0.155871E+10 | 0.132857E+09 | 0.142585E+10 | 0.00 | 0.00 |
August | 0.206473E+10 | 0.343043E+09 | 0.144656E+10 | 35401431.26 | 0.141115E+10 | 0.00 | 0.00 |
September | 0.136891E+10 | 0.658050E+09 | 0.111753E+10 | 796346.02 | 0.111673E+10 | 0.00 | 0.00 |
October | 0.658250E+09 | 0.134645E+10 | 0.860849E+09 | 0.00 | 0.860849E+09 | 0.00 | 0.00 |
November | 0.212888E+09 | 0.197980E+10 | 0.707481E+09 | 0.00 | 0.707481E+09 | 0.00 | 0.00 |
December | 39387775.06 | 0.273252E+10 | 0.583755E+09 | 0.00 | 0.583755E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.129007E+11 | 0.162907E+11 | 0.132892E+11 | 0.557543E+09 | 0.127317E+11 | 0.00 | 0.00 |
Minimum of Months | 39387775.06 | 0.284453E+09 | 0.583755E+09 | 0.00 | 0.583755E+09 | 0.00 | 0.00 |
Maximum of Months | 0.243406E+10 | 0.273252E+10 | 0.164499E+10 | 0.273565E+09 | 0.142585E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117299E+09 | 0.271392E+10 | 0.685841E+09 | 0.00 | 0.685841E+09 | 0.00 | 0.00 |
February | 0.249630E+09 | 0.220578E+10 | 0.774233E+09 | 0.00 | 0.774233E+09 | 0.00 | 0.00 |
March | 0.641234E+09 | 0.188052E+10 | 0.108145E+10 | 37592.41 | 0.108141E+10 | 0.00 | 0.00 |
April | 0.107230E+10 | 0.113629E+10 | 0.133485E+10 | 17880832.21 | 0.131696E+10 | 0.00 | 0.00 |
May | 0.153920E+10 | 0.808946E+09 | 0.149299E+10 | 97004202.60 | 0.139599E+10 | 0.00 | 0.00 |
June | 0.232157E+10 | 0.477039E+09 | 0.164499E+10 | 0.273565E+09 | 0.137142E+10 | 0.00 | 0.00 |
July | 0.239810E+10 | 0.298442E+09 | 0.155871E+10 | 0.132857E+09 | 0.142585E+10 | 0.00 | 0.00 |
August | 0.202910E+10 | 0.358412E+09 | 0.144656E+10 | 35401431.26 | 0.141115E+10 | 0.00 | 0.00 |
September | 0.133960E+10 | 0.680126E+09 | 0.111753E+10 | 796346.02 | 0.111673E+10 | 0.00 | 0.00 |
October | 0.634576E+09 | 0.138728E+10 | 0.860849E+09 | 0.00 | 0.860849E+09 | 0.00 | 0.00 |
November | 0.194724E+09 | 0.204354E+10 | 0.707481E+09 | 0.00 | 0.707481E+09 | 0.00 | 0.00 |
December | 31153301.05 | 0.282888E+10 | 0.583755E+09 | 0.00 | 0.583755E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.125685E+11 | 0.168192E+11 | 0.132892E+11 | 0.557543E+09 | 0.127317E+11 | 0.00 | 0.00 |
Minimum of Months | 31153301.05 | 0.298442E+09 | 0.583755E+09 | 0.00 | 0.583755E+09 | 0.00 | 0.00 |
Maximum of Months | 0.239810E+10 | 0.282888E+10 | 0.164499E+10 | 0.273565E+09 | 0.142585E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.176892E+10 | 0.184813E+10 | 0.183544E+10 | 0.113007E+10 | 0.705365E+09 | 0.00 | 0.00 |
February | 0.191075E+10 | 0.153317E+10 | 0.186390E+10 | 0.106758E+10 | 0.796329E+09 | 0.00 | 0.00 |
March | 0.261494E+10 | 0.132126E+10 | 0.231691E+10 | 0.125340E+10 | 0.106352E+10 | 0.00 | 0.00 |
April | 0.340868E+10 | 0.841622E+09 | 0.272762E+10 | 0.138347E+10 | 0.134414E+10 | 0.00 | 0.00 |
May | 0.350499E+10 | 0.628338E+09 | 0.260279E+10 | 0.128083E+10 | 0.132196E+10 | 0.00 | 0.00 |
June | 0.405574E+10 | 0.382281E+09 | 0.266454E+10 | 0.142568E+10 | 0.123886E+10 | 0.00 | 0.00 |
July | 0.419144E+10 | 0.242554E+09 | 0.258623E+10 | 0.126498E+10 | 0.132125E+10 | 0.00 | 0.00 |
August | 0.411276E+10 | 0.284965E+09 | 0.263992E+10 | 0.126492E+10 | 0.137500E+10 | 0.00 | 0.00 |
September | 0.339135E+10 | 0.480878E+09 | 0.231872E+10 | 0.120981E+10 | 0.110891E+10 | 0.00 | 0.00 |
October | 0.290706E+10 | 0.943662E+09 | 0.229978E+10 | 0.144863E+10 | 0.851151E+09 | 0.00 | 0.00 |
November | 0.207491E+10 | 0.137738E+10 | 0.196303E+10 | 0.122404E+10 | 0.738993E+09 | 0.00 | 0.00 |
December | 0.175069E+10 | 0.188129E+10 | 0.183313E+10 | 0.123723E+10 | 0.595904E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.356922E+11 | 0.117655E+11 | 0.276520E+11 | 0.151906E+11 | 0.124614E+11 | 0.00 | 0.00 |
Minimum of Months | 0.175069E+10 | 0.242554E+09 | 0.183313E+10 | 0.106758E+10 | 0.595904E+09 | 0.00 | 0.00 |
Maximum of Months | 0.419144E+10 | 0.188129E+10 | 0.272762E+10 | 0.144863E+10 | 0.137500E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.301890E+10 | 0.200082E+10 | 0.293464E+10 | 0.209933E+10 | 0.835310E+09 | 0.00 | 0.00 |
February | 0.281194E+10 | 0.167842E+10 | 0.266886E+10 | 0.175899E+10 | 0.909867E+09 | 0.00 | 0.00 |
March | 0.251969E+10 | 0.151108E+10 | 0.234940E+10 | 0.120741E+10 | 0.114199E+10 | 0.00 | 0.00 |
April | 0.213856E+10 | 0.997935E+09 | 0.192820E+10 | 0.608802E+09 | 0.131940E+10 | 0.00 | 0.00 |
May | 0.176629E+10 | 0.720468E+09 | 0.153453E+10 | 0.264619E+09 | 0.126991E+10 | 0.00 | 0.00 |
June | 0.197883E+10 | 0.422479E+09 | 0.139130E+10 | 0.193129E+09 | 0.119817E+10 | 0.00 | 0.00 |
July | 0.231248E+10 | 0.263020E+09 | 0.148073E+10 | 0.194039E+09 | 0.128669E+10 | 0.00 | 0.00 |
August | 0.261806E+10 | 0.321724E+09 | 0.178330E+10 | 0.418180E+09 | 0.136512E+10 | 0.00 | 0.00 |
September | 0.290145E+10 | 0.605006E+09 | 0.215178E+10 | 0.995888E+09 | 0.115590E+10 | 0.00 | 0.00 |
October | 0.326695E+10 | 0.112094E+10 | 0.275740E+10 | 0.181121E+10 | 0.946181E+09 | 0.00 | 0.00 |
November | 0.312742E+10 | 0.155133E+10 | 0.293046E+10 | 0.206868E+10 | 0.861782E+09 | 0.00 | 0.00 |
December | 0.325874E+10 | 0.202455E+10 | 0.314397E+10 | 0.243012E+10 | 0.713855E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.317193E+11 | 0.132178E+11 | 0.270546E+11 | 0.140504E+11 | 0.130042E+11 | 0.00 | 0.00 |
Minimum of Months | 0.176629E+10 | 0.263020E+09 | 0.139130E+10 | 0.193129E+09 | 0.713855E+09 | 0.00 | 0.00 |
Maximum of Months | 0.326695E+10 | 0.202455E+10 | 0.314397E+10 | 0.243012E+10 | 0.136512E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770368E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160890951.7 | 81.21 | 0.00 | 0.00 |
February | 0.696127E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -145302430.5 | 81.21 | 0.00 | 0.00 |
March | 0.770252E+10 | -0.754147E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161050601.8 | 81.21 | 0.00 | 0.00 |
April | 0.746458E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -155982302.4 | 81.21 | 0.00 | 0.00 |
May | 0.770417E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161377168.1 | 81.21 | 0.00 | 0.00 |
June | 0.745674E+10 | -0.730054E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156201473.3 | 81.21 | 0.00 | 0.00 |
July | 0.771226E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161406060.5 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161406562.7 | 81.21 | 0.00 | 0.00 |
September | 0.746614E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156205119.4 | 81.21 | 0.00 | 0.00 |
October | 0.770265E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161217324.0 | 81.21 | 0.00 | 0.00 |
November | 0.744813E+10 | -0.729242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -155700813.6 | 81.21 | 0.00 | 0.00 |
December | 0.771165E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160785441.2 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907380E+11 | -0.888405E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.189753E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696127E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161406562.7 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771226E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -145302430.5 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.120246E+12 | -0.118519E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172738E+10 | 81.26 | 0.00 | 0.00 |
February | 0.109177E+12 | -0.107615E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.156217E+10 | 81.26 | 0.00 | 0.00 |
March | 0.118853E+12 | -0.117120E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173365E+10 | 81.26 | 0.00 | 0.00 |
April | 0.110907E+12 | -0.109228E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167868E+10 | 81.25 | 0.00 | 0.00 |
May | 0.109273E+12 | -0.107539E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173353E+10 | 81.25 | 0.00 | 0.00 |
June | 0.100928E+12 | -0.992538E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167466E+10 | 81.25 | 0.00 | 0.00 |
July | 0.101011E+12 | -0.992825E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172855E+10 | 81.25 | 0.00 | 0.00 |
August | 0.100306E+12 | -0.985789E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172725E+10 | 81.25 | 0.00 | 0.00 |
September | 0.990855E+11 | -0.974151E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167041E+10 | 81.25 | 0.00 | 0.00 |
October | 0.106681E+12 | -0.104955E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172589E+10 | 81.25 | 0.00 | 0.00 |
November | 0.108402E+12 | -0.106732E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.166995E+10 | 81.25 | 0.00 | 0.00 |
December | 0.116966E+12 | -0.115240E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172591E+10 | 81.25 | 0.00 | 0.00 |
Annual Sum or Average | 0.130184E+13 | -0.128148E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203580E+11 | 81.25 | 0.00 | 0.00 |
Minimum of Months | 0.990855E+11 | -0.118519E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.173365E+10 | 81.25 | 0.00 | 0.00 |
Maximum of Months | 0.120246E+12 | -0.974151E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156217E+10 | 81.26 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.711712E+11 | -0.697074E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146381E+10 | 58.98 | 0.00 | 0.00 |
February | 0.647830E+11 | -0.634582E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.132475E+10 | 58.98 | 0.00 | 0.00 |
March | 0.700446E+11 | -0.685721E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147255E+10 | 58.98 | 0.00 | 0.00 |
April | 0.642191E+11 | -0.627925E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142658E+10 | 58.98 | 0.00 | 0.00 |
May | 0.617785E+11 | -0.603060E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147258E+10 | 58.98 | 0.00 | 0.00 |
June | 0.556471E+11 | -0.542261E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142101E+10 | 58.98 | 0.00 | 0.00 |
July | 0.546171E+11 | -0.531514E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146573E+10 | 58.98 | 0.00 | 0.00 |
August | 0.540627E+11 | -0.525988E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146390E+10 | 58.98 | 0.00 | 0.00 |
September | 0.540297E+11 | -0.526145E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141519E+10 | 58.98 | 0.00 | 0.00 |
October | 0.595062E+11 | -0.580441E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146208E+10 | 58.98 | 0.00 | 0.00 |
November | 0.620354E+11 | -0.606208E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141459E+10 | 58.98 | 0.00 | 0.00 |
December | 0.683570E+11 | -0.668950E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146200E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.740252E+12 | -0.722987E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.172648E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.540297E+11 | -0.697074E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.147258E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.711712E+11 | -0.525988E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.132475E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.93 | 0.93 | 01-JAN-07:40 | 9466.57 | 38.08 | 292.50 | 289.33 | 1602.92 | 28.59 | 225.67 | 276.33 |
February | 282.00 | 0.93 | 0.93 | 01-FEB-07:40 | 11056.86 | 36.94 | 265.17 | 276.00 | 935.53 | 25.04 | 198.83 | 256.00 |
March | 351.33 | 0.93 | 0.93 | 01-MAR-06:00 | 1748.12 | 21.59 | 106.00 | 332.67 | 592.74 | 21.98 | 212.33 | 282.50 |
April | 381.83 | 0.93 | 0.93 | 01-APR-06:40 | 1265.24 | 20.65 | 116.83 | 355.33 | 530.97 | 22.37 | 313.17 | 314.50 |
May | 378.00 | 0.93 | 0.93 | 01-MAY-05:00 | 960.63 | 20.18 | 38.17 | 378.83 | 414.44 | 21.94 | 291.17 | 312.83 |
June | 412.83 | 0.93 | 0.93 | 01-JUN-05:40 | 747.66 | 19.39 | 23.67 | 376.17 | 321.85 | 21.20 | 157.83 | 206.33 |
July | 395.33 | 0.93 | 0.93 | 01-JUL-06:19 | 926.03 | 19.90 | 48.00 | 379.67 | 394.96 | 21.68 | 254.00 | 294.67 |
August | 408.83 | 0.93 | 0.93 | 01-AUG-05:00 | 1185.06 | 20.37 | 120.67 | 376.17 | 495.40 | 22.10 | 298.33 | 323.33 |
September | 359.33 | 0.93 | 0.93 | 01-SEP-06:10 | 1308.83 | 20.34 | 94.17 | 332.00 | 549.30 | 22.12 | 241.17 | 288.00 |
October | 329.00 | 0.93 | 0.93 | 01-OCT-06:40 | 5954.79 | 29.37 | 199.00 | 321.50 | 681.02 | 22.74 | 196.00 | 294.33 |
November | 284.17 | 0.93 | 0.93 | 01-NOV-06:49 | 10793.39 | 38.80 | 278.67 | 285.00 | 1462.62 | 28.19 | 235.33 | 272.33 |
December | 265.67 | 0.93 | 0.93 | 01-DEC-07:40 | 10793.84 | 40.22 | 263.83 | 271.17 | 2665.77 | 31.78 | 210.00 | 259.17 |
Annual Sum or Average | 4149.83 | 0.93 | 4085.94 | 26.00 | 1846.67 | 3973.83 | 807.64 | 23.73 | 2833.83 | 3380.33 | ||
Minimum of Months | 265.67 | 0.93 | 0.93 | 747.66 | 19.39 | 23.67 | 271.17 | 321.85 | 21.20 | 157.83 | 206.33 | |
Maximum of Months | 412.83 | 0.93 | 0.93 | 11056.86 | 40.22 | 292.50 | 379.67 | 2665.77 | 31.78 | 313.17 | 323.33 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.62 | 0.61 | 01-JAN-07:40 | 10037.32 | 38.16 | 292.50 | 295.33 | 2172.14 | 28.04 | 205.17 | 285.33 |
February | 282.00 | 0.62 | 0.61 | 01-FEB-07:30 | 11626.04 | 36.99 | 261.50 | 283.00 | 1503.03 | 24.50 | 176.67 | 268.33 |
March | 351.33 | 0.62 | 0.61 | 01-MAR-06:49 | 2145.64 | 21.56 | 116.83 | 342.67 | 989.43 | 21.86 | 195.67 | 315.83 |
April | 381.83 | 0.63 | 0.61 | 01-APR-06:30 | 1557.24 | 20.96 | 139.00 | 363.83 | 822.26 | 22.52 | 307.33 | 343.17 |
May | 378.00 | 0.62 | 0.61 | 01-MAY-05:00 | 1173.88 | 20.72 | 96.50 | 388.33 | 627.17 | 22.29 | 304.17 | 357.17 |
June | 412.83 | 0.62 | 0.61 | 01-JUN-05:30 | 914.12 | 20.11 | 58.33 | 396.00 | 487.88 | 21.71 | 215.50 | 351.50 |
July | 395.33 | 0.62 | 0.61 | 01-JUL-05:00 | 1122.13 | 20.52 | 96.00 | 393.17 | 590.54 | 22.11 | 292.00 | 358.00 |
August | 408.83 | 0.62 | 0.61 | 01-AUG-05:49 | 1435.44 | 20.81 | 166.00 | 385.67 | 745.16 | 22.37 | 309.50 | 362.00 |
September | 359.33 | 0.62 | 0.61 | 01-SEP-05:00 | 1666.30 | 20.44 | 108.17 | 344.00 | 905.98 | 22.08 | 215.83 | 318.50 |
October | 329.00 | 0.62 | 0.61 | 01-OCT-06:30 | 6456.51 | 29.23 | 191.33 | 326.50 | 1181.45 | 22.28 | 154.33 | 312.50 |
November | 284.17 | 0.62 | 0.61 | 01-NOV-06:49 | 11400.13 | 38.87 | 278.67 | 290.33 | 2070.37 | 27.60 | 191.33 | 279.67 |
December | 265.67 | 0.62 | 0.61 | 01-DEC-07:40 | 11478.07 | 40.27 | 264.00 | 276.00 | 3352.68 | 31.14 | 179.00 | 269.00 |
Annual Sum or Average | 4149.83 | 0.62 | 4462.02 | 26.26 | 2068.83 | 4084.83 | 1183.23 | 23.69 | 2746.50 | 3821.00 | ||
Minimum of Months | 265.67 | 0.62 | 0.61 | 914.12 | 20.11 | 58.33 | 276.00 | 487.88 | 21.71 | 154.33 | 268.33 | |
Maximum of Months | 412.83 | 0.63 | 0.61 | 11626.04 | 40.27 | 292.50 | 396.00 | 3352.68 | 31.14 | 309.50 | 362.00 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.82 | 0.80 | 01-JAN-08:20 | 406.29 | 15.04 | 0.00 | 248.00 | 202.03 | 18.63 | 0.00 | 120.50 |
February | 282.00 | 0.81 | 0.80 | 01-FEB-07:49 | 462.65 | 15.79 | 0.00 | 261.17 | 237.21 | 19.30 | 3.67 | 142.33 |
March | 351.33 | 0.81 | 0.80 | 01-MAR-06:00 | 571.39 | 16.61 | 0.00 | 329.83 | 270.68 | 19.93 | 40.83 | 195.83 |
April | 381.83 | 0.81 | 0.80 | 01-APR-06:40 | 724.35 | 18.14 | 0.00 | 366.17 | 344.45 | 21.36 | 172.67 | 337.67 |
May | 378.00 | 0.80 | 0.80 | 01-MAY-05:49 | 876.03 | 18.50 | 4.33 | 398.67 | 371.26 | 21.64 | 170.50 | 361.00 |
June | 412.83 | 0.80 | 0.80 | 01-JUN-05:19 | 920.03 | 20.40 | 74.00 | 409.67 | 353.01 | 21.93 | 167.00 | 339.00 |
July | 395.33 | 0.80 | 0.80 | 01-JUL-05:00 | 889.73 | 19.20 | 27.17 | 401.83 | 383.19 | 21.72 | 191.67 | 368.83 |
August | 408.83 | 0.81 | 0.80 | 01-AUG-05:40 | 784.35 | 18.19 | 0.00 | 389.67 | 381.27 | 21.45 | 207.50 | 365.17 |
September | 359.33 | 0.81 | 0.80 | 01-SEP-05:00 | 592.50 | 17.10 | 0.00 | 336.33 | 290.30 | 20.41 | 83.83 | 259.67 |
October | 329.00 | 0.82 | 0.80 | 01-OCT-06:00 | 404.30 | 15.57 | 0.00 | 295.00 | 213.61 | 19.07 | 1.17 | 152.17 |
November | 284.17 | 0.82 | 0.80 | 01-NOV-06:00 | 418.79 | 15.52 | 0.00 | 263.83 | 220.44 | 19.10 | 0.00 | 165.00 |
December | 265.67 | 0.83 | 0.80 | 01-DEC-07:00 | 336.41 | 14.28 | 0.00 | 235.67 | 185.35 | 18.02 | 0.00 | 101.33 |
Annual Sum or Average | 4149.83 | 0.81 | 642.91 | 17.27 | 105.50 | 3935.83 | 297.44 | 20.40 | 1038.83 | 2908.50 | ||
Minimum of Months | 265.67 | 0.80 | 0.80 | 336.41 | 14.28 | 0.00 | 235.67 | 185.35 | 18.02 | 0.00 | 101.33 | |
Maximum of Months | 412.83 | 0.83 | 0.80 | 920.03 | 20.40 | 74.00 | 409.67 | 383.19 | 21.93 | 207.50 | 368.83 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.82 | 0.80 | 01-JAN-08:20 | 406.29 | 15.04 | 0.00 | 248.00 | 202.03 | 18.63 | 0.00 | 120.50 |
February | 282.00 | 0.81 | 0.80 | 01-FEB-07:49 | 462.65 | 15.79 | 0.00 | 261.17 | 237.21 | 19.30 | 3.67 | 142.33 |
March | 351.33 | 0.81 | 0.80 | 01-MAR-06:00 | 571.39 | 16.61 | 0.00 | 329.83 | 270.68 | 19.93 | 40.83 | 195.83 |
April | 381.83 | 0.81 | 0.80 | 01-APR-06:40 | 724.35 | 18.14 | 0.00 | 366.17 | 344.45 | 21.36 | 172.67 | 337.67 |
May | 378.00 | 0.80 | 0.80 | 01-MAY-05:49 | 876.03 | 18.50 | 4.33 | 398.67 | 371.26 | 21.64 | 170.50 | 361.00 |
June | 412.83 | 0.80 | 0.80 | 01-JUN-05:19 | 920.03 | 20.40 | 74.00 | 409.67 | 353.01 | 21.93 | 167.00 | 339.00 |
July | 395.33 | 0.80 | 0.80 | 01-JUL-05:00 | 889.73 | 19.20 | 27.17 | 401.83 | 383.19 | 21.72 | 191.67 | 368.83 |
August | 408.83 | 0.81 | 0.80 | 01-AUG-05:40 | 784.35 | 18.19 | 0.00 | 389.67 | 381.27 | 21.45 | 207.50 | 365.17 |
September | 359.33 | 0.81 | 0.80 | 01-SEP-05:00 | 592.50 | 17.10 | 0.00 | 336.33 | 290.30 | 20.41 | 83.83 | 259.67 |
October | 329.00 | 0.82 | 0.80 | 01-OCT-06:00 | 404.30 | 15.57 | 0.00 | 295.00 | 213.61 | 19.07 | 1.17 | 152.17 |
November | 284.17 | 0.82 | 0.80 | 01-NOV-06:00 | 418.79 | 15.52 | 0.00 | 263.83 | 220.44 | 19.10 | 0.00 | 165.00 |
December | 265.67 | 0.83 | 0.80 | 01-DEC-07:00 | 336.41 | 14.28 | 0.00 | 235.67 | 185.35 | 18.02 | 0.00 | 101.33 |
Annual Sum or Average | 4149.83 | 0.81 | 642.91 | 17.27 | 105.50 | 3935.83 | 297.44 | 20.40 | 1038.83 | 2908.50 | ||
Minimum of Months | 265.67 | 0.80 | 0.80 | 336.41 | 14.28 | 0.00 | 235.67 | 185.35 | 18.02 | 0.00 | 101.33 | |
Maximum of Months | 412.83 | 0.83 | 0.80 | 920.03 | 20.40 | 74.00 | 409.67 | 383.19 | 21.93 | 207.50 | 368.83 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.253255E+11 | 147393.52 | 26-JAN-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.224559E+11 | 147623.59 | 16-FEB-23:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.199335E+11 | 172170.12 | 08-MAR-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153048E+11 | 173850.95 | 04-APR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.430992E+10 | 133181.47 | 04-MAY-04:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.577650E+09 | 92157.45 | 09-JUN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.206320E+09 | 18361.25 | 09-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136228E+11 | 172020.27 | 30-OCT-02:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.288194E+11 | 172081.42 | 20-NOV-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.319167E+11 | 148727.59 | 14-DEC-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162473E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.319167E+11 | 173850.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.336708E+09 | 1236.59 | 19-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164402E+09 | 1041.45 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 39461582.02 | 779.56 | 04-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 825696.94 | 226.58 | 24-APR-03:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 459391.08 | 332.97 | 05-MAY-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38936035.64 | 976.20 | 26-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 46508480.25 | 927.85 | 11-NOV-07:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.295424E+09 | 1309.31 | 09-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.922726E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.336708E+09 | 1309.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2598045.35 | 224.17 | 19-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2598045.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2598045.35 | 224.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 46631466.79 | 474.23 | 20-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4904315.04 | 263.80 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3192680.85 | 240.22 | 08-DEC-12:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54728462.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46631466.79 | 474.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.395640E+09 | 952.75 | 26-JAN-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.216003E+09 | 1399.02 | 01-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16450531.63 | 508.18 | 04-MAR-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7299348.38 | 337.57 | 26-OCT-08:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20591777.48 | 356.69 | 27-NOV-12:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.410300E+09 | 1258.50 | 04-DEC-11:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.410300E+09 | 1399.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2196876.76 | 3293.41 | 16-APR-02:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1267862.29 | 1603.72 | 13-OCT-00:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 811019.94 | 2703.40 | 24-NOV-01:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4275758.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2196876.76 | 3293.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.279451E+09 | 3641.55 | 19-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 78867973.11 | 2748.94 | 22-FEB-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 25109478.96 | 3471.79 | 22-MAR-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 221213.46 | 604.53 | 16-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3782303.42 | 4278.39 | 05-MAY-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 48058138.36 | 4437.91 | 25-OCT-13:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 39340571.04 | 3152.93 | 04-NOV-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180236E+09 | 6681.38 | 08-DEC-11:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.655066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.279451E+09 | 6681.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.292996E+09 | 3747.95 | 20-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2550247.73 | 1507.04 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19049179.32 | 2030.72 | 09-DEC-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.314596E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.292996E+09 | 3747.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.507982E+09 | 2500.85 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182193E+09 | 2126.46 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2615111.44 | 554.14 | 26-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 891174.29 | 220.22 | 12-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.454022E+09 | 2640.51 | 08-DEC-11:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.507982E+09 | 2640.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 14123131.29 | 2890.09 | 13-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4562043.01 | 3416.54 | 03-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1242885.25 | 1708.59 | 27-NOV-12:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14280503.31 | 4360.60 | 20-DEC-13:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 34208562.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14280503.31 | 4360.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 181606.52 | 605.36 | 02-FEB-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 145410.92 | 1118.88 | 20-DEC-13:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 327017.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 181606.52 | 1118.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 131352.36 | 656.76 | 24-APR-00:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 131352.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 131352.36 | 656.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100514E+10 | 5656.91 | 21-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.417676E+09 | 3602.47 | 04-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17460099.59 | 1587.74 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 26563.20 | 0.57 | 16-APR-17:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 46050.77 | 0.57 | 30-MAY-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 57664.23 | 0.57 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 38491.95 | 0.57 | 05-JUL-03:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 38897.02 | 0.57 | 13-AUG-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 50305.88 | 0.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18787445.26 | 1746.64 | 26-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27948913.65 | 1821.90 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.725283E+09 | 4952.93 | 15-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 26563.20 | 0.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100514E+10 | 5656.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.224907E+10 | 9900.96 | 20-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147287E+10 | 9887.11 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.640766E+09 | 9492.85 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97028649.04 | 4096.01 | 22-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38676761.60 | 4373.21 | 19-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6777589.58 | 4250.87 | 11-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2009538.56 | 2166.42 | 08-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2421569.91 | 2194.55 | 28-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3099387.06 | 3607.63 | 09-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.266201E+09 | 9738.21 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.766394E+09 | 9449.32 | 10-NOV-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227175E+10 | 9900.22 | 22-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.781706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2009538.56 | 2166.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.227175E+10 | 9900.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.363322E+10 | 9918.79 | 26-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.241600E+10 | 9952.32 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103144E+10 | 9663.67 | 04-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149788E+09 | 4585.23 | 29-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43604073.71 | 4364.85 | 04-MAY-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6289351.81 | 3130.83 | 06-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1924772.03 | 1923.03 | 08-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3425898.80 | 2894.21 | 28-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5423695.94 | 4356.59 | 27-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.444328E+09 | 9825.24 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155724E+10 | 9851.27 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.395690E+10 | 9972.53 | 15-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1924772.03 | 1923.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.395690E+10 | 9972.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136330E+09 | 6822.41 | 19-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136330E+09 | 6822.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.159097E+11 | 54485.47 | 26-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101917E+11 | 54378.27 | 06-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252877E+10 | 43853.50 | 06-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.279915E+09 | 31410.05 | 18-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95046435.85 | 29151.22 | 10-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30197074.49 | 33346.95 | 10-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 26995468.82 | 24621.62 | 28-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33871670.26 | 29298.39 | 09-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 65933943.06 | 33575.67 | 21-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134660E+10 | 53722.94 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.597891E+10 | 54130.52 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184544E+11 | 55136.82 | 15-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.549421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 26995468.82 | 24621.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.184544E+11 | 55136.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.237287E+10 | 9662.67 | 20-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157409E+10 | 9479.36 | 16-FEB-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.627229E+09 | 9267.60 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96280475.08 | 3708.46 | 07-APR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24346404.91 | 3067.44 | 06-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2002214.91 | 2334.00 | 08-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 182207.46 | 1182.34 | 10-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 138705.54 | 697.98 | 29-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1197736.40 | 1963.89 | 24-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.269103E+09 | 9481.76 | 25-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.820963E+09 | 9239.63 | 04-NOV-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.238055E+10 | 9603.71 | 08-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.816895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 138705.54 | 697.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.238055E+10 | 9662.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.371140E+10 | 9644.33 | 20-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.248813E+10 | 9645.02 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.931019E+09 | 9264.61 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144991E+09 | 3484.18 | 04-APR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29997532.60 | 3442.59 | 06-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2082198.92 | 2481.96 | 08-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 221935.12 | 1245.87 | 10-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 282979.07 | 1019.56 | 29-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2422526.85 | 2386.62 | 24-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.420960E+09 | 9483.91 | 25-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154134E+10 | 9370.18 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.397841E+10 | 9585.50 | 08-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 221935.12 | 1019.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.397841E+10 | 9645.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.954218E+09 | 2952.81 | 20-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.658728E+09 | 2974.31 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.375215E+09 | 2873.67 | 04-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 93729449.66 | 2272.97 | 08-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 37496267.41 | 2311.61 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5851512.11 | 991.31 | 20-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 462792.90 | 655.30 | 28-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 923637.79 | 822.66 | 27-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2886638.66 | 1152.26 | 27-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164374E+09 | 2936.41 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.432033E+09 | 2919.56 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.964177E+09 | 2980.28 | 15-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.369010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 462792.90 | 655.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.964177E+09 | 2980.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142184E+10 | 2959.26 | 15-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.986644E+09 | 2967.64 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.538251E+09 | 2912.90 | 04-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125907E+09 | 2825.41 | 08-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41244623.74 | 2396.59 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5498769.21 | 1043.05 | 20-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 493464.11 | 564.31 | 28-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 981548.14 | 831.62 | 27-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3482265.39 | 944.63 | 24-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.263301E+09 | 2929.84 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.769845E+09 | 2943.89 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152454E+10 | 2973.58 | 15-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.568203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 493464.11 | 564.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.152454E+10 | 2973.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.189235E+10 | 13564.70 | 17-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128917E+10 | 13297.64 | 16-FEB-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.720606E+09 | 13077.84 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.224919E+09 | 4825.22 | 26-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108276E+09 | 5472.60 | 10-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14577368.33 | 4966.57 | 11-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9626017.69 | 4342.00 | 05-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7042104.34 | 4180.87 | 02-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3094476.10 | 3386.17 | 02-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.301701E+09 | 13334.44 | 25-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.631836E+09 | 12940.93 | 10-NOV-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180828E+10 | 13464.47 | 08-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.701147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3094476.10 | 3386.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.189235E+10 | 13564.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.216634E+10 | 0.216634E+10 | 55944.96 | 08-JAN-21:53 | 55944.96 | 0.00 |
February | 0.00 | 0.00 | 0.779789E+10 | 0.779789E+10 | 130423.66 | 14-FEB-15:10 | 130423.66 | 0.00 |
March | 0.00 | 0.00 | 0.252991E+11 | 0.252991E+11 | 143110.82 | 08-MAR-14:00 | 143110.82 | 0.00 |
April | 0.00 | 0.00 | 0.100748E+12 | 0.100748E+12 | 200622.03 | 13-APR-18:04 | 200622.03 | 0.00 |
May | 0.00 | 0.00 | 0.188588E+12 | 0.188588E+12 | 234336.51 | 19-MAY-18:20 | 234336.51 | 0.13 |
June | 0.00 | 0.00 | 0.330153E+12 | 0.329888E+12 | 276082.49 | 27-JUN-18:20 | 276082.49 | 0.39 |
July | 0.00 | 0.00 | 0.453353E+12 | 0.429361E+12 | 352550.25 | 31-JUL-20:00 | 192067.97 | 0.94 |
August | 0.00 | 0.00 | 0.406181E+12 | 0.393532E+12 | 296474.82 | 14-AUG-21:00 | 246386.82 | 0.97 |
September | 0.00 | 0.00 | 0.265232E+12 | 0.264216E+12 | 237792.62 | 13-SEP-19:20 | 237792.62 | 0.60 |
October | 0.00 | 0.00 | 0.115092E+12 | 0.115009E+12 | 208843.48 | 05-OCT-18:06 | 208843.48 | 0.13 |
November | 0.00 | 0.00 | 0.452953E+10 | 0.452953E+10 | 69253.24 | 09-NOV-14:00 | 69253.24 | 0.00 |
December | 0.00 | 0.00 | 0.810365E+09 | 0.810365E+09 | 48091.30 | 16-DEC-21:40 | 48091.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.189995E+13 | 0.186195E+13 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 0.810365E+09 | 0.810365E+09 | 48091.30 | 48091.30 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.453353E+12 | 0.429361E+12 | 352550.25 | 276082.49 | 0.97 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.119195E+09 | 0.119195E+09 | 4034.29 | 05-JAN-14:10 | 4034.29 | 0.00 |
February | 0.00 | 0.00 | 0.100811E+10 | 0.100811E+10 | 21463.31 | 14-FEB-16:00 | 21463.31 | 0.00 |
March | 0.00 | 0.00 | 0.393816E+10 | 0.393816E+10 | 22412.19 | 08-MAR-16:00 | 22412.19 | 0.00 |
April | 0.00 | 0.00 | 0.151227E+11 | 0.151227E+11 | 24753.83 | 29-APR-15:01 | 24753.83 | 0.00 |
May | 0.00 | 0.00 | 0.280797E+11 | 0.280784E+11 | 27279.39 | 19-MAY-15:02 | 27279.39 | 0.12 |
June | 0.00 | 0.00 | 0.457900E+11 | 0.457331E+11 | 31625.44 | 28-JUN-15:01 | 31625.44 | 0.34 |
July | 0.00 | 0.00 | 0.671160E+11 | 0.596909E+11 | 42112.97 | 01-JUL-14:00 | 19529.61 | 0.92 |
August | 0.00 | 0.00 | 0.589319E+11 | 0.544729E+11 | 39938.51 | 26-AUG-10:00 | 18960.68 | 0.95 |
September | 0.00 | 0.00 | 0.381063E+11 | 0.371919E+11 | 37647.88 | 05-SEP-12:20 | 22115.77 | 0.58 |
October | 0.00 | 0.00 | 0.160914E+11 | 0.159762E+11 | 28113.26 | 11-OCT-10:10 | 22376.22 | 0.13 |
November | 0.00 | 0.00 | 0.450045E+09 | 0.450045E+09 | 14180.69 | 09-NOV-14:00 | 14180.69 | 0.00 |
December | 0.00 | 0.00 | 35543.17 | 35543.17 | 38.55 | 11-DEC-19:45 | 38.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.274753E+12 | 0.261782E+12 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 35543.17 | 35543.17 | 38.55 | 38.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.671160E+11 | 0.596909E+11 | 42112.97 | 31625.44 | 0.95 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.122701E+10 | 0.122701E+10 | 18123.17 | 05-JAN-16:01 | 18123.17 | 0.00 |
February | 0.00 | 0.00 | 0.179103E+10 | 0.179103E+10 | 19165.72 | 14-FEB-16:02 | 19165.72 | 0.00 |
March | 0.00 | 0.00 | 0.283690E+10 | 0.283681E+10 | 19303.04 | 08-MAR-16:01 | 19303.04 | 0.00 |
April | 0.00 | 0.00 | 0.535200E+10 | 0.534452E+10 | 19785.77 | 29-APR-15:01 | 19785.77 | 0.00 |
May | 0.00 | 0.00 | 0.664787E+10 | 0.592818E+10 | 20024.60 | 21-MAY-15:01 | 20024.60 | 0.23 |
June | 0.00 | 0.00 | 0.956647E+10 | 0.743913E+10 | 20025.51 | 12-JUN-15:01 | 20025.51 | 0.58 |
July | 0.00 | 0.00 | 0.117871E+11 | 0.733095E+10 | 20025.83 | 20-JUL-18:02 | 20025.83 | 0.93 |
August | 0.00 | 0.00 | 0.116954E+11 | 0.726270E+10 | 18927.70 | 26-AUG-08:61 | 15190.29 | 0.95 |
September | 0.00 | 0.00 | 0.928140E+10 | 0.626483E+10 | 20027.45 | 21-SEP-15:01 | 20027.45 | 0.77 |
October | 0.00 | 0.00 | 0.623777E+10 | 0.540343E+10 | 20027.43 | 06-OCT-15:01 | 20027.43 | 0.23 |
November | 0.00 | 0.00 | 0.239731E+10 | 0.239528E+10 | 18376.44 | 02-NOV-15:01 | 18376.44 | 0.00 |
December | 0.00 | 0.00 | 0.101744E+10 | 0.101744E+10 | 18070.74 | 26-DEC-16:02 | 18070.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.698377E+11 | 0.542413E+11 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.101744E+10 | 0.101744E+10 | 18070.74 | 15190.29 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.117871E+11 | 0.743913E+10 | 20027.45 | 20027.45 | 0.95 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.228196E+09 | 0.228196E+09 | 17909.82 | 05-JAN-16:01 | 17909.82 | 0.00 |
February | 0.00 | 0.00 | 0.589752E+09 | 0.589752E+09 | 18937.89 | 14-FEB-16:02 | 18937.89 | 0.00 |
March | 0.00 | 0.00 | 0.144492E+10 | 0.144492E+10 | 19074.61 | 08-MAR-16:01 | 19074.61 | 0.00 |
April | 0.00 | 0.00 | 0.418754E+10 | 0.418037E+10 | 19552.61 | 29-APR-15:01 | 19552.61 | 0.00 |
May | 0.00 | 0.00 | 0.617879E+10 | 0.548690E+10 | 19788.96 | 21-MAY-15:01 | 19788.96 | 0.23 |
June | 0.00 | 0.00 | 0.957723E+10 | 0.748923E+10 | 19789.45 | 12-JUN-15:01 | 19789.45 | 0.58 |
July | 0.00 | 0.00 | 0.114663E+11 | 0.710480E+10 | 19791.62 | 21-JUL-18:02 | 19791.62 | 0.93 |
August | 0.00 | 0.00 | 0.106131E+11 | 0.632814E+10 | 18724.50 | 26-AUG-08:61 | 14982.05 | 0.94 |
September | 0.00 | 0.00 | 0.721841E+10 | 0.446861E+10 | 19791.20 | 21-SEP-15:01 | 19791.20 | 0.75 |
October | 0.00 | 0.00 | 0.364875E+10 | 0.295302E+10 | 19790.09 | 06-OCT-15:01 | 19790.09 | 0.21 |
November | 0.00 | 0.00 | 0.582113E+09 | 0.581197E+09 | 18158.81 | 02-NOV-15:01 | 18158.81 | 0.00 |
December | 0.00 | 0.00 | 0.134518E+09 | 0.134518E+09 | 17844.07 | 29-DEC-16:01 | 17844.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.558696E+11 | 0.409896E+11 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.134518E+09 | 0.134518E+09 | 17844.07 | 14982.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.114663E+11 | 0.748923E+10 | 19791.62 | 19791.62 | 0.94 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.254109E+11 | 0.254109E+11 | 60879.93 | 03-JAN-12:40 | 60879.93 | 0.00 |
February | 0.00 | 0.00 | 0.235775E+11 | 0.235775E+11 | 61055.44 | 14-FEB-13:00 | 61055.44 | 0.00 |
March | 0.00 | 0.00 | 0.200189E+11 | 0.200189E+11 | 50213.46 | 08-MAR-13:30 | 50213.46 | 0.00 |
April | 0.00 | 0.00 | 0.192122E+11 | 0.192122E+11 | 36326.33 | 13-APR-13:20 | 36326.33 | 0.00 |
May | 0.00 | 0.00 | 0.161567E+11 | 0.149656E+11 | 24301.67 | 13-MAY-13:10 | 24301.67 | 0.09 |
June | 0.00 | 0.00 | 0.248551E+11 | 0.195963E+11 | 28507.35 | 29-JUN-13:20 | 21109.64 | 0.30 |
July | 0.00 | 0.00 | 0.392866E+11 | 0.202654E+11 | 32816.71 | 23-JUL-13:30 | 26939.87 | 0.89 |
August | 0.00 | 0.00 | 0.450847E+11 | 0.268243E+11 | 45934.19 | 21-AUG-14:20 | 37812.93 | 0.92 |
September | 0.00 | 0.00 | 0.466698E+11 | 0.363064E+11 | 57050.99 | 28-SEP-13:30 | 54956.38 | 0.57 |
October | 0.00 | 0.00 | 0.460067E+11 | 0.434236E+11 | 60953.53 | 19-OCT-12:30 | 60953.53 | 0.13 |
November | 0.00 | 0.00 | 0.361897E+11 | 0.361897E+11 | 61502.65 | 20-NOV-13:30 | 61502.65 | 0.00 |
December | 0.00 | 0.00 | 0.282426E+11 | 0.282426E+11 | 62061.53 | 31-DEC-13:40 | 62061.53 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.370711E+12 | 0.314033E+12 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 0.161567E+11 | 0.149656E+11 | 24301.67 | 21109.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.466698E+11 | 0.434236E+11 | 62061.53 | 62061.53 | 0.92 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.198099E+09 | 0.198099E+09 | 31934.17 | 22-JAN-19:03 | 31934.17 | 0.00 |
February | 0.00 | 0.00 | 0.104394E+10 | 0.104394E+10 | 71234.16 | 15-FEB-19:01 | 71234.16 | 0.00 |
March | 0.00 | 0.00 | 0.616401E+10 | 0.614972E+10 | 84587.32 | 27-MAR-15:01 | 84587.32 | 0.00 |
April | 0.00 | 0.00 | 0.201620E+11 | 0.201620E+11 | 95717.64 | 29-APR-15:01 | 95717.64 | 0.00 |
May | 0.00 | 0.00 | 0.340266E+11 | 0.302975E+11 | 99221.45 | 21-MAY-15:01 | 99221.45 | 0.18 |
June | 0.00 | 0.00 | 0.528072E+11 | 0.435558E+11 | 99253.25 | 27-JUN-15:01 | 99253.25 | 0.48 |
July | 0.00 | 0.00 | 0.660158E+11 | 0.440627E+11 | 99270.58 | 03-JUL-18:02 | 99270.58 | 0.80 |
August | 0.00 | 0.00 | 0.579996E+11 | 0.369897E+11 | 92237.94 | 26-AUG-08:61 | 73751.84 | 0.77 |
September | 0.00 | 0.00 | 0.377071E+11 | 0.254218E+11 | 96807.81 | 21-SEP-18:02 | 96807.81 | 0.56 |
October | 0.00 | 0.00 | 0.162585E+11 | 0.132752E+11 | 94228.26 | 06-OCT-15:01 | 94228.26 | 0.16 |
November | 0.00 | 0.00 | 0.226960E+10 | 0.226718E+10 | 80935.52 | 02-NOV-18:01 | 80935.52 | 0.00 |
December | 0.00 | 0.00 | 0.195689E+09 | 0.195689E+09 | 29960.08 | 23-DEC-19:04 | 29960.08 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.294848E+12 | 0.223619E+12 | 0.25 | |||
Minimum of Months | 0.00 | 0.00 | 0.195689E+09 | 0.195689E+09 | 29960.08 | 29960.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.660158E+11 | 0.440627E+11 | 99270.58 | 99270.58 | 0.80 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.119095E+10 | 0.119095E+10 | 15873.82 | 05-JAN-16:01 | 15873.82 | 0.00 |
February | 0.00 | 0.00 | 0.157270E+10 | 0.157270E+10 | 16785.67 | 14-FEB-16:02 | 16785.67 | 0.00 |
March | 0.00 | 0.00 | 0.313696E+10 | 0.313688E+10 | 16907.03 | 08-MAR-16:01 | 16907.03 | 0.00 |
April | 0.00 | 0.00 | 0.618244E+10 | 0.617310E+10 | 17328.53 | 29-APR-15:01 | 17328.53 | 0.00 |
May | 0.00 | 0.00 | 0.748878E+10 | 0.666962E+10 | 17537.28 | 21-MAY-15:01 | 17537.28 | 0.26 |
June | 0.00 | 0.00 | 0.104860E+11 | 0.845980E+10 | 17541.19 | 27-JUN-15:01 | 17541.19 | 0.61 |
July | 0.00 | 0.00 | 0.129831E+11 | 0.856222E+10 | 17541.57 | 04-JUL-15:02 | 17541.57 | 0.96 |
August | 0.00 | 0.00 | 0.125727E+11 | 0.825173E+10 | 15290.37 | 29-AUG-18:01 | 14624.87 | 0.98 |
September | 0.00 | 0.00 | 0.958314E+10 | 0.672737E+10 | 17540.14 | 21-SEP-15:01 | 17540.14 | 0.80 |
October | 0.00 | 0.00 | 0.631516E+10 | 0.550009E+10 | 17539.77 | 06-OCT-15:01 | 17539.77 | 0.24 |
November | 0.00 | 0.00 | 0.242829E+10 | 0.242250E+10 | 16094.19 | 02-NOV-15:01 | 16094.19 | 0.00 |
December | 0.00 | 0.00 | 0.970312E+09 | 0.970312E+09 | 15841.57 | 29-DEC-09:01 | 15841.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.749104E+11 | 0.596373E+11 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 0.970312E+09 | 0.970312E+09 | 15290.37 | 14624.87 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.129831E+11 | 0.856222E+10 | 17541.57 | 17541.57 | 0.98 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.197410E+09 | 0.197410E+09 | 15029.72 | 01-JAN-09:01 | 15029.72 | 0.00 |
February | 0.00 | 0.00 | 0.395348E+09 | 0.395348E+09 | 16065.60 | 14-FEB-16:02 | 16065.60 | 0.00 |
March | 0.00 | 0.00 | 0.152725E+10 | 0.152725E+10 | 16745.05 | 08-MAR-16:01 | 16745.05 | 0.00 |
April | 0.00 | 0.00 | 0.489567E+10 | 0.488751E+10 | 17164.50 | 29-APR-15:01 | 17164.50 | 0.00 |
May | 0.00 | 0.00 | 0.697870E+10 | 0.618049E+10 | 17371.12 | 21-MAY-15:01 | 17371.12 | 0.26 |
June | 0.00 | 0.00 | 0.104814E+11 | 0.848586E+10 | 17374.94 | 27-JUN-15:01 | 17374.94 | 0.61 |
July | 0.00 | 0.00 | 0.126456E+11 | 0.824371E+10 | 17371.15 | 20-JUL-18:02 | 17371.15 | 0.96 |
August | 0.00 | 0.00 | 0.114836E+11 | 0.719298E+10 | 15203.92 | 29-AUG-18:01 | 14453.27 | 0.98 |
September | 0.00 | 0.00 | 0.746255E+10 | 0.480520E+10 | 17374.74 | 21-SEP-15:01 | 17374.74 | 0.79 |
October | 0.00 | 0.00 | 0.355335E+10 | 0.283836E+10 | 17373.20 | 06-OCT-15:01 | 17373.20 | 0.23 |
November | 0.00 | 0.00 | 0.605213E+09 | 0.602163E+09 | 15699.47 | 12-NOV-09:01 | 15699.47 | 0.00 |
December | 0.00 | 0.00 | 0.113419E+09 | 0.113419E+09 | 15082.13 | 30-DEC-09:01 | 15082.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.603395E+11 | 0.454697E+11 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 0.113419E+09 | 0.113419E+09 | 15029.72 | 14453.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.126456E+11 | 0.848586E+10 | 17374.94 | 17374.94 | 0.98 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.273670E+09 | 0.273670E+09 | 4807.87 | 05-JAN-16:01 | 4807.87 | 0.00 |
February | 0.00 | 0.00 | 0.412701E+09 | 0.412701E+09 | 5084.52 | 14-FEB-16:02 | 5084.52 | 0.00 |
March | 0.00 | 0.00 | 0.634213E+09 | 0.634213E+09 | 5120.94 | 08-MAR-16:01 | 5120.94 | 0.00 |
April | 0.00 | 0.00 | 0.123583E+10 | 0.123364E+10 | 5248.97 | 29-APR-15:01 | 5248.97 | 0.00 |
May | 0.00 | 0.00 | 0.157712E+10 | 0.141973E+10 | 5312.30 | 21-MAY-15:01 | 5312.30 | 0.22 |
June | 0.00 | 0.00 | 0.242564E+10 | 0.189698E+10 | 5312.67 | 12-JUN-15:01 | 5312.67 | 0.57 |
July | 0.00 | 0.00 | 0.303970E+10 | 0.189538E+10 | 5313.32 | 20-JUL-18:02 | 5313.32 | 0.93 |
August | 0.00 | 0.00 | 0.298274E+10 | 0.185823E+10 | 5147.54 | 26-AUG-08:61 | 3840.33 | 0.95 |
September | 0.00 | 0.00 | 0.223969E+10 | 0.151641E+10 | 5313.73 | 21-SEP-15:01 | 5313.73 | 0.76 |
October | 0.00 | 0.00 | 0.140980E+10 | 0.120938E+10 | 5313.25 | 06-OCT-15:01 | 5313.25 | 0.23 |
November | 0.00 | 0.00 | 0.479967E+09 | 0.478770E+09 | 4875.07 | 02-NOV-15:01 | 4875.07 | 0.00 |
December | 0.00 | 0.00 | 0.221513E+09 | 0.221513E+09 | 4794.00 | 26-DEC-16:02 | 4794.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.169326E+11 | 0.130506E+11 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.221513E+09 | 0.221513E+09 | 4794.00 | 3840.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.303970E+10 | 0.189698E+10 | 5313.73 | 5313.73 | 0.95 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 47650949.08 | 47650949.08 | 4742.51 | 05-JAN-16:01 | 4742.51 | 0.00 |
February | 0.00 | 0.00 | 0.130309E+09 | 0.130309E+09 | 5014.85 | 14-FEB-16:02 | 5014.85 | 0.00 |
March | 0.00 | 0.00 | 0.312764E+09 | 0.312764E+09 | 5051.04 | 08-MAR-16:01 | 5051.04 | 0.00 |
April | 0.00 | 0.00 | 0.942409E+09 | 0.940592E+09 | 5177.59 | 29-APR-15:01 | 5177.59 | 0.00 |
May | 0.00 | 0.00 | 0.145346E+10 | 0.130325E+10 | 5240.05 | 21-MAY-15:01 | 5240.05 | 0.22 |
June | 0.00 | 0.00 | 0.242546E+10 | 0.190312E+10 | 5240.41 | 12-JUN-15:01 | 5240.41 | 0.57 |
July | 0.00 | 0.00 | 0.295424E+10 | 0.183040E+10 | 5241.00 | 20-JUL-18:02 | 5241.00 | 0.93 |
August | 0.00 | 0.00 | 0.269711E+10 | 0.161330E+10 | 5082.83 | 26-AUG-08:61 | 3757.72 | 0.94 |
September | 0.00 | 0.00 | 0.169353E+10 | 0.105175E+10 | 5240.81 | 21-SEP-15:01 | 5240.81 | 0.74 |
October | 0.00 | 0.00 | 0.769476E+09 | 0.616082E+09 | 5240.53 | 06-OCT-15:01 | 5240.53 | 0.20 |
November | 0.00 | 0.00 | 0.106228E+09 | 0.106172E+09 | 4808.44 | 02-NOV-15:01 | 4808.44 | 0.00 |
December | 0.00 | 0.00 | 24375444.03 | 24375444.03 | 4719.10 | 02-DEC-16:01 | 4719.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.135570E+11 | 0.987977E+10 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 24375444.03 | 24375444.03 | 4719.10 | 3757.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.295424E+10 | 0.190312E+10 | 5241.00 | 5241.00 | 0.94 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.653010E+10 | 0.653010E+10 | 19221.95 | 05-JAN-16:01 | 19221.95 | 0.00 |
February | 0.00 | 0.00 | 0.630126E+10 | 0.630126E+10 | 20326.81 | 14-FEB-16:02 | 20326.81 | 0.00 |
March | 0.00 | 0.00 | 0.594339E+10 | 0.594313E+10 | 20470.14 | 08-MAR-16:01 | 20470.14 | 0.00 |
April | 0.00 | 0.00 | 0.657052E+10 | 0.655208E+10 | 20981.20 | 29-APR-15:01 | 20981.20 | 0.01 |
May | 0.00 | 0.00 | 0.666128E+10 | 0.587849E+10 | 21222.82 | 18-MAY-18:01 | 21222.82 | 0.23 |
June | 0.00 | 0.00 | 0.949314E+10 | 0.713920E+10 | 21230.67 | 11-JUN-15:01 | 21230.67 | 0.58 |
July | 0.00 | 0.00 | 0.138029E+11 | 0.855009E+10 | 21231.02 | 21-JUL-18:02 | 21231.02 | 0.93 |
August | 0.00 | 0.00 | 0.148147E+11 | 0.971788E+10 | 20215.38 | 26-AUG-08:61 | 15827.94 | 0.94 |
September | 0.00 | 0.00 | 0.137884E+11 | 0.102644E+11 | 21229.66 | 20-SEP-18:01 | 21229.66 | 0.78 |
October | 0.00 | 0.00 | 0.122102E+11 | 0.112064E+11 | 20762.35 | 05-OCT-18:01 | 20762.35 | 0.25 |
November | 0.00 | 0.00 | 0.864628E+10 | 0.862306E+10 | 19487.55 | 02-NOV-15:01 | 19487.55 | 0.01 |
December | 0.00 | 0.00 | 0.723107E+10 | 0.723107E+10 | 19175.51 | 29-DEC-09:01 | 19175.51 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.111993E+12 | 0.939371E+11 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.594339E+10 | 0.587849E+10 | 19175.51 | 15827.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.148147E+11 | 0.112064E+11 | 21231.02 | 21231.02 | 0.94 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 22302.15 | 191774.38 | 22-JAN-19:02 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18181.91 | 154213.39 | 09-FEB-23:43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 10094.81 | 178089.02 | 22-MAR-08:62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 6293.39 | 159267.09 | 04-APR-04:55 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1748.73 | 114393.96 | 05-MAY-03:43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 250.92 | 75887.48 | 09-JUN-05:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.64 | 28275.87 | 10-JUL-08:04 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.37 | 26727.58 | 09-AUG-08:04 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 106.23 | 45429.34 | 27-SEP-18:04 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 6344.05 | 209280.07 | 25-OCT-15:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15781.47 | 154563.99 | 05-NOV-08:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 25556.64 | 186518.85 | 15-DEC-16:03 |
Annual Sum or Average | 0.00 | 8851.06 | ||||
Minimum of Months | 0.00 | 0.00 | 18.37 | 26727.58 | ||
Maximum of Months | 0.00 | 0.00 | 25556.64 | 209280.07 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16704.97 | 129940.26 | 01-JAN-16:03 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 21444.86 | 285904.02 | 13-FEB-16:03 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 30034.07 | 329266.09 | 08-MAR-16:01 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 75769.93 | 417947.59 | 28-APR-18:01 | 0.00 | 0.00 | 01-APR-00:10 |
May | 118577.53 | 446008.96 | 18-MAY-18:01 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 201861.54 | 499821.88 | 28-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 265612.73 | 558874.51 | 31-JUL-18:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 243411.64 | 483815.43 | 17-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 175223.53 | 469176.45 | 20-SEP-18:01 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 89654.16 | 450609.82 | 06-OCT-15:01 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 26053.49 | 225661.09 | 02-NOV-15:01 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 17199.71 | 117139.02 | 29-DEC-16:04 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 107355.48 | 0.00 | ||||
Minimum of Months | 16704.97 | 117139.02 | 0.00 | 0.00 | ||
Maximum of Months | 265612.73 | 558874.51 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 27539.22 | 64498.28 | 10-JAN-21:11 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 27730.80 | 62602.47 | 15-FEB-07:25 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 27113.01 | 68024.28 | 14-MAR-06:51 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25751.18 | 63722.89 | 07-APR-06:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 24065.14 | 56924.43 | 06-MAY-07:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22494.37 | 46670.33 | 01-JUN-06:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21425.86 | 43654.91 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 21220.61 | 42906.88 | 31-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21875.63 | 47873.43 | 25-SEP-06:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 23204.43 | 57764.88 | 18-OCT-06:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 24866.37 | 60521.50 | 20-NOV-07:41 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 26465.54 | 63490.73 | 03-DEC-08:61 |
Annual Sum or Average | 0.00 | 24460.65 | ||||
Minimum of Months | 0.00 | 0.00 | 21220.61 | 42906.88 | ||
Maximum of Months | 0.00 | 0.00 | 27730.80 | 68024.28 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 1.07 | 2194.93 | 01-JAN-00:03 | 1.07 |
February | 0.530997E+10 | 1.07 | 2194.93 | 01-FEB-00:05 | 1.07 |
March | 0.587890E+10 | 1.07 | 2194.93 | 01-MAR-00:05 | 1.07 |
April | 0.568926E+10 | 1.07 | 2194.93 | 01-APR-00:10 | 1.07 |
May | 0.587890E+10 | 1.07 | 2194.93 | 01-MAY-00:10 | 1.07 |
June | 0.568926E+10 | 1.06 | 2194.93 | 01-JUN-00:10 | 1.07 |
July | 0.587890E+10 | 1.06 | 2194.93 | 01-JUL-00:10 | 1.06 |
August | 0.587890E+10 | 1.06 | 2194.93 | 01-AUG-00:10 | 1.06 |
September | 0.568926E+10 | 1.06 | 2194.93 | 01-SEP-00:10 | 1.06 |
October | 0.587890E+10 | 1.06 | 2194.93 | 01-OCT-00:10 | 1.06 |
November | 0.568926E+10 | 1.07 | 2194.93 | 01-NOV-00:10 | 1.07 |
December | 0.587890E+10 | 1.07 | 2194.93 | 01-DEC-00:10 | 1.07 |
Annual Sum or Average | 0.692193E+11 | 1.06 | |||
Minimum of Months | 0.530997E+10 | 1.06 | 2194.93 | 1.06 | |
Maximum of Months | 0.587890E+10 | 1.07 | 2194.93 | 1.07 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.392352E+11 | 0.95 | 47259.78 | 02-JAN-21:35 | 1.93 |
February | 0.351372E+11 | 0.95 | 48749.67 | 10-FEB-22:10 | 1.97 |
March | 0.388414E+11 | 0.95 | 47129.27 | 05-MAR-22:25 | 1.93 |
April | 0.388405E+11 | 0.97 | 46322.04 | 04-APR-04:55 | 1.92 |
May | 0.410282E+11 | 0.98 | 38758.25 | 19-MAY-21:10 | 1.71 |
June | 0.441623E+11 | 1.03 | 42179.03 | 23-JUN-21:10 | 1.78 |
July | 0.483117E+11 | 1.06 | 44004.66 | 21-JUL-21:10 | 1.84 |
August | 0.492660E+11 | 1.07 | 45309.69 | 18-AUG-21:10 | 1.86 |
September | 0.456950E+11 | 1.05 | 45135.12 | 13-SEP-21:10 | 1.87 |
October | 0.444518E+11 | 1.02 | 47129.27 | 24-OCT-20:15 | 1.92 |
November | 0.406959E+11 | 0.99 | 48749.67 | 24-NOV-23:05 | 1.97 |
December | 0.403389E+11 | 0.97 | 48514.24 | 19-DEC-20:05 | 1.97 |
Annual Sum or Average | 0.506004E+12 | 1.00 | |||
Minimum of Months | 0.351372E+11 | 0.95 | 38758.25 | 1.71 | |
Maximum of Months | 0.492660E+11 | 1.07 | 48749.67 | 1.97 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.32 | 76.61 | 01-JAN-00:03 | 0.32 |
February | 0.185347E+09 | 0.32 | 76.61 | 01-FEB-00:05 | 0.32 |
March | 0.205205E+09 | 0.32 | 76.61 | 01-MAR-00:05 | 0.32 |
April | 0.198586E+09 | 0.32 | 76.61 | 01-APR-00:10 | 0.32 |
May | 0.205205E+09 | 0.32 | 76.61 | 01-MAY-00:10 | 0.33 |
June | 0.198586E+09 | 0.32 | 76.61 | 01-JUN-00:10 | 0.32 |
July | 0.205205E+09 | 0.32 | 76.61 | 01-JUL-00:10 | 0.32 |
August | 0.205205E+09 | 0.32 | 76.61 | 01-AUG-00:10 | 0.32 |
September | 0.198586E+09 | 0.32 | 76.61 | 01-SEP-00:10 | 0.32 |
October | 0.205205E+09 | 0.32 | 76.61 | 01-OCT-00:10 | 0.32 |
November | 0.198586E+09 | 0.32 | 76.61 | 01-NOV-00:10 | 0.32 |
December | 0.205205E+09 | 0.32 | 76.61 | 01-DEC-00:10 | 0.32 |
Annual Sum or Average | 0.241613E+10 | 0.32 | |||
Minimum of Months | 0.185347E+09 | 0.32 | 76.61 | 0.32 | |
Maximum of Months | 0.205205E+09 | 0.32 | 76.61 | 0.33 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.23 | 612.92 | 01-JAN-07:10 | 0.32 |
February | 0.105030E+10 | 0.23 | 612.92 | 01-FEB-07:05 | 0.32 |
March | 0.116283E+10 | 0.23 | 612.92 | 01-MAR-07:05 | 0.32 |
April | 0.112532E+10 | 0.23 | 612.92 | 01-APR-06:05 | 0.32 |
May | 0.116283E+10 | 0.23 | 612.92 | 01-MAY-06:05 | 0.32 |
June | 0.112532E+10 | 0.23 | 612.92 | 01-JUN-06:05 | 0.32 |
July | 0.116283E+10 | 0.23 | 612.92 | 01-JUL-06:05 | 0.32 |
August | 0.116283E+10 | 0.23 | 612.92 | 01-AUG-06:05 | 0.32 |
September | 0.112532E+10 | 0.23 | 612.92 | 01-SEP-06:05 | 0.32 |
October | 0.116283E+10 | 0.23 | 612.92 | 01-OCT-06:10 | 0.32 |
November | 0.112532E+10 | 0.23 | 612.92 | 01-NOV-06:10 | 0.32 |
December | 0.116283E+10 | 0.23 | 612.92 | 01-DEC-07:03 | 0.32 |
Annual Sum or Average | 0.136914E+11 | 0.23 | |||
Minimum of Months | 0.105030E+10 | 0.23 | 612.92 | 0.32 | |
Maximum of Months | 0.116283E+10 | 0.23 | 612.92 | 0.32 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.249667E+09 | 0.56 | 1014.41 | 01-JAN-16:01 | 0.70 |
February | 0.227678E+09 | 0.57 | 1014.41 | 01-FEB-09:01 | 0.70 |
March | 0.234740E+09 | 0.58 | 1014.41 | 04-MAR-16:01 | 0.70 |
April | 0.318721E+09 | 0.62 | 1014.41 | 01-APR-15:01 | 0.70 |
May | 0.372463E+09 | 0.62 | 1014.41 | 01-MAY-15:01 | 0.70 |
June | 0.509130E+09 | 0.65 | 1014.41 | 01-JUN-08:62 | 0.70 |
July | 0.585442E+09 | 0.66 | 1014.41 | 01-JUL-08:61 | 0.69 |
August | 0.593432E+09 | 0.66 | 1014.41 | 01-AUG-08:61 | 0.69 |
September | 0.495566E+09 | 0.65 | 1014.41 | 01-SEP-08:62 | 0.69 |
October | 0.377259E+09 | 0.62 | 1014.41 | 01-OCT-08:61 | 0.69 |
November | 0.217953E+09 | 0.59 | 1014.41 | 01-NOV-15:02 | 0.70 |
December | 0.239996E+09 | 0.56 | 1014.41 | 01-DEC-16:01 | 0.70 |
Annual Sum or Average | 0.442205E+10 | 0.61 | |||
Minimum of Months | 0.217953E+09 | 0.56 | 1014.41 | 0.69 | |
Maximum of Months | 0.593432E+09 | 0.66 | 1014.41 | 0.70 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.277015E+09 | 0.52 | 1002.45 | 01-JAN-09:01 | 0.70 |
February | 0.220277E+09 | 0.52 | 1002.45 | 01-FEB-09:01 | 0.70 |
March | 0.188186E+09 | 0.53 | 1002.45 | 03-MAR-09:02 | 0.70 |
April | 0.262917E+09 | 0.58 | 1002.45 | 01-APR-15:01 | 0.70 |
May | 0.349447E+09 | 0.60 | 1002.45 | 01-MAY-15:01 | 0.70 |
June | 0.510363E+09 | 0.65 | 1002.45 | 01-JUN-08:62 | 0.70 |
July | 0.570383E+09 | 0.66 | 1002.45 | 01-JUL-08:61 | 0.69 |
August | 0.537929E+09 | 0.66 | 1002.45 | 01-AUG-08:61 | 0.69 |
September | 0.388557E+09 | 0.63 | 1002.45 | 01-SEP-08:62 | 0.69 |
October | 0.255233E+09 | 0.56 | 1002.45 | 01-OCT-08:61 | 0.69 |
November | 0.177052E+09 | 0.52 | 1002.45 | 01-NOV-15:02 | 0.70 |
December | 0.289820E+09 | 0.52 | 1002.45 | 02-DEC-09:02 | 0.70 |
Annual Sum or Average | 0.402718E+10 | 0.58 | |||
Minimum of Months | 0.177052E+09 | 0.52 | 1002.45 | 0.69 | |
Maximum of Months | 0.570383E+09 | 0.66 | 1002.45 | 0.70 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.131596E+10 | 0.30 | 3065.06 | 03-JAN-12:40 | 0.70 |
February | 0.118780E+10 | 0.32 | 2986.68 | 14-FEB-12:50 | 0.70 |
March | 0.101320E+10 | 0.32 | 2486.90 | 08-MAR-13:00 | 0.70 |
April | 0.947715E+09 | 0.42 | 1555.43 | 13-APR-13:20 | 0.70 |
May | 0.807790E+09 | 0.42 | 1047.02 | 13-MAY-13:10 | 0.70 |
June | 0.118194E+10 | 0.56 | 1292.78 | 29-JUN-14:40 | 0.70 |
July | 0.169697E+10 | 0.67 | 1388.98 | 23-JUL-13:40 | 0.70 |
August | 0.196494E+10 | 0.66 | 2322.52 | 20-AUG-12:40 | 0.70 |
September | 0.227190E+10 | 0.64 | 3206.96 | 28-SEP-13:30 | 0.70 |
October | 0.228777E+10 | 0.54 | 3234.43 | 01-OCT-11:40 | 0.70 |
November | 0.185060E+10 | 0.41 | 3097.03 | 20-NOV-13:30 | 0.70 |
December | 0.144597E+10 | 0.31 | 3122.07 | 31-DEC-13:40 | 0.70 |
Annual Sum or Average | 0.179725E+11 | 0.47 | |||
Minimum of Months | 0.807790E+09 | 0.30 | 1047.02 | 0.70 | |
Maximum of Months | 0.228777E+10 | 0.67 | 3234.43 | 0.70 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116055E+10 | 0.50 | 4990.47 | 01-JAN-16:01 | 0.70 |
February | 0.846559E+09 | 0.50 | 4990.47 | 01-FEB-09:01 | 0.70 |
March | 0.670949E+09 | 0.50 | 4990.47 | 09-MAR-16:01 | 0.70 |
April | 0.120623E+10 | 0.50 | 4990.47 | 01-APR-08:62 | 0.70 |
May | 0.188706E+10 | 0.50 | 4990.47 | 01-MAY-08:62 | 0.70 |
June | 0.289782E+10 | 0.55 | 4990.47 | 01-JUN-08:62 | 0.70 |
July | 0.328848E+10 | 0.57 | 4990.47 | 01-JUL-08:61 | 0.69 |
August | 0.288582E+10 | 0.54 | 4990.47 | 01-AUG-08:61 | 0.70 |
September | 0.196137E+10 | 0.50 | 4990.47 | 01-SEP-08:62 | 0.69 |
October | 0.107549E+10 | 0.49 | 4990.47 | 01-OCT-08:61 | 0.70 |
November | 0.696244E+09 | 0.50 | 4990.47 | 02-NOV-18:01 | 0.70 |
December | 0.128738E+10 | 0.50 | 4990.47 | 03-DEC-16:01 | 0.70 |
Annual Sum or Average | 0.198640E+11 | 0.51 | |||
Minimum of Months | 0.670949E+09 | 0.49 | 4990.47 | 0.69 | |
Maximum of Months | 0.328848E+10 | 0.57 | 4990.47 | 0.70 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.237430E+09 | 0.57 | 888.39 | 01-JAN-09:01 | 0.70 |
February | 0.209685E+09 | 0.57 | 888.39 | 01-FEB-19:01 | 0.70 |
March | 0.242835E+09 | 0.60 | 888.39 | 02-MAR-09:01 | 0.70 |
April | 0.359190E+09 | 0.66 | 888.39 | 01-APR-08:62 | 0.70 |
May | 0.417687E+09 | 0.66 | 888.39 | 01-MAY-08:62 | 0.70 |
June | 0.565178E+09 | 0.68 | 888.39 | 01-JUN-08:62 | 0.70 |
July | 0.643358E+09 | 0.68 | 888.39 | 01-JUL-08:61 | 0.69 |
August | 0.629588E+09 | 0.68 | 888.39 | 01-AUG-08:61 | 0.69 |
September | 0.513130E+09 | 0.67 | 888.39 | 01-SEP-08:62 | 0.69 |
October | 0.381097E+09 | 0.65 | 888.39 | 01-OCT-08:61 | 0.70 |
November | 0.217877E+09 | 0.60 | 888.39 | 01-NOV-08:62 | 0.70 |
December | 0.225706E+09 | 0.54 | 888.39 | 01-DEC-16:01 | 0.70 |
Annual Sum or Average | 0.464276E+10 | 0.63 | |||
Minimum of Months | 0.209685E+09 | 0.54 | 888.39 | 0.69 | |
Maximum of Months | 0.643358E+09 | 0.68 | 888.39 | 0.70 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.253479E+09 | 0.52 | 879.96 | 01-JAN-09:01 | 0.70 |
February | 0.194078E+09 | 0.50 | 879.96 | 01-FEB-09:01 | 0.70 |
March | 0.174347E+09 | 0.53 | 879.96 | 02-MAR-09:01 | 0.70 |
April | 0.298010E+09 | 0.64 | 879.96 | 01-APR-08:62 | 0.70 |
May | 0.394285E+09 | 0.66 | 879.96 | 01-MAY-08:62 | 0.70 |
June | 0.571386E+09 | 0.68 | 879.96 | 01-JUN-08:62 | 0.70 |
July | 0.630270E+09 | 0.68 | 879.96 | 01-JUL-08:61 | 0.69 |
August | 0.575480E+09 | 0.68 | 879.96 | 01-AUG-08:61 | 0.69 |
September | 0.401441E+09 | 0.66 | 879.96 | 01-SEP-08:62 | 0.69 |
October | 0.244482E+09 | 0.59 | 879.96 | 01-OCT-08:61 | 0.70 |
November | 0.161669E+09 | 0.50 | 879.96 | 01-NOV-08:62 | 0.70 |
December | 0.261061E+09 | 0.51 | 879.96 | 03-DEC-16:01 | 0.70 |
Annual Sum or Average | 0.415999E+10 | 0.60 | |||
Minimum of Months | 0.161669E+09 | 0.50 | 879.96 | 0.69 | |
Maximum of Months | 0.630270E+09 | 0.68 | 879.96 | 0.70 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 79141391.16 | 0.56 | 269.12 | 01-JAN-16:01 | 0.70 |
February | 69424450.20 | 0.56 | 269.12 | 01-FEB-09:01 | 0.70 |
March | 67996964.79 | 0.57 | 269.12 | 03-MAR-09:02 | 0.70 |
April | 79425514.59 | 0.62 | 269.12 | 01-APR-15:01 | 0.70 |
May | 91048991.71 | 0.62 | 269.12 | 01-MAY-15:01 | 0.70 |
June | 0.130284E+09 | 0.65 | 269.12 | 01-JUN-15:01 | 0.70 |
July | 0.153390E+09 | 0.66 | 269.12 | 01-JUL-08:61 | 0.69 |
August | 0.153474E+09 | 0.66 | 269.12 | 01-AUG-08:61 | 0.69 |
September | 0.121376E+09 | 0.65 | 269.12 | 01-SEP-08:62 | 0.69 |
October | 93348961.62 | 0.62 | 269.12 | 01-OCT-08:61 | 0.69 |
November | 62291089.69 | 0.58 | 269.12 | 01-NOV-15:02 | 0.70 |
December | 77025855.90 | 0.57 | 269.12 | 01-DEC-16:01 | 0.70 |
Annual Sum or Average | 0.117823E+10 | 0.61 | |||
Minimum of Months | 62291089.69 | 0.56 | 269.12 | 0.69 | |
Maximum of Months | 0.153474E+09 | 0.66 | 269.12 | 0.70 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 89587479.63 | 0.54 | 265.46 | 01-JAN-09:01 | 0.70 |
February | 71028984.84 | 0.53 | 265.46 | 01-FEB-09:01 | 0.70 |
March | 60084974.99 | 0.52 | 265.46 | 03-MAR-09:02 | 0.70 |
April | 66273130.95 | 0.58 | 265.46 | 01-APR-15:01 | 0.70 |
May | 85118211.62 | 0.61 | 265.46 | 01-MAY-15:01 | 0.70 |
June | 0.130582E+09 | 0.65 | 265.46 | 01-JUN-15:01 | 0.70 |
July | 0.149248E+09 | 0.66 | 265.46 | 01-JUL-08:61 | 0.69 |
August | 0.139063E+09 | 0.65 | 265.46 | 01-AUG-08:61 | 0.69 |
September | 92443897.25 | 0.63 | 265.46 | 01-SEP-15:02 | 0.70 |
October | 65927815.22 | 0.56 | 265.46 | 01-OCT-08:61 | 0.69 |
November | 61661995.68 | 0.51 | 265.46 | 01-NOV-15:02 | 0.70 |
December | 93607689.14 | 0.56 | 265.46 | 01-DEC-09:02 | 0.70 |
Annual Sum or Average | 0.110463E+10 | 0.58 | |||
Minimum of Months | 60084974.99 | 0.51 | 265.46 | 0.69 | |
Maximum of Months | 0.149248E+09 | 0.66 | 265.46 | 0.70 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.495165E+09 | 0.61 | 1072.53 | 01-JAN-09:01 | 0.70 |
February | 0.442562E+09 | 0.62 | 1072.53 | 01-FEB-16:01 | 0.70 |
March | 0.391161E+09 | 0.60 | 1072.53 | 01-MAR-16:02 | 0.70 |
April | 0.382364E+09 | 0.62 | 1072.53 | 01-APR-15:01 | 0.70 |
May | 0.374605E+09 | 0.62 | 1072.53 | 01-MAY-15:01 | 0.70 |
June | 0.501388E+09 | 0.64 | 1072.53 | 01-JUN-15:01 | 0.69 |
July | 0.662193E+09 | 0.65 | 1072.53 | 01-JUL-08:61 | 0.69 |
August | 0.728931E+09 | 0.66 | 1072.53 | 01-AUG-08:61 | 0.69 |
September | 0.748594E+09 | 0.65 | 1072.53 | 01-SEP-08:62 | 0.69 |
October | 0.715026E+09 | 0.64 | 1072.53 | 01-OCT-08:61 | 0.70 |
November | 0.544167E+09 | 0.63 | 1072.53 | 01-NOV-08:62 | 0.70 |
December | 0.526814E+09 | 0.62 | 1072.53 | 01-DEC-16:01 | 0.70 |
Annual Sum or Average | 0.651297E+10 | 0.63 | |||
Minimum of Months | 0.374605E+09 | 0.60 | 1072.53 | 0.69 | |
Maximum of Months | 0.748594E+09 | 0.66 | 1072.53 | 0.70 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.482595E+09 | 0.434336E+09 | 694.63 | 09-JAN-09:01 | 625.17 | 625.17 | 66.50 | 1.10 |
February | 0.361998E+09 | 0.325799E+09 | 684.73 | 16-FEB-23:15 | 616.25 | 616.25 | 53.47 | 1.08 |
March | 0.227417E+09 | 0.204675E+09 | 691.84 | 22-MAR-08:62 | 622.66 | 622.66 | 41.69 | 1.10 |
April | 0.106498E+09 | 95848361.10 | 658.85 | 16-APR-04:45 | 592.97 | 592.97 | 60.08 | 1.00 |
May | 29860648.63 | 26874583.77 | 599.50 | 04-MAY-04:57 | 539.55 | 539.55 | 50.10 | 0.86 |
June | 3941906.84 | 3547716.16 | 441.17 | 09-JUN-05:00 | 397.05 | 397.05 | 47.32 | 0.56 |
July | 516492.73 | 464843.45 | 262.74 | 10-JUL-08:04 | 236.46 | 236.46 | 56.73 | 0.30 |
August | 567693.62 | 510924.26 | 283.96 | 09-AUG-08:04 | 255.56 | 255.56 | 59.77 | 0.33 |
September | 2293798.32 | 2064418.49 | 258.51 | 21-SEP-08:03 | 232.66 | 232.66 | 47.85 | 0.29 |
October | 0.121449E+09 | 0.109304E+09 | 718.08 | 25-OCT-15:01 | 646.27 | 646.27 | 38.24 | 1.19 |
November | 0.323970E+09 | 0.291573E+09 | 693.04 | 18-NOV-04:33 | 623.74 | 623.74 | 48.16 | 1.11 |
December | 0.540119E+09 | 0.486107E+09 | 702.09 | 01-DEC-03:20 | 631.88 | 631.88 | 48.53 | 1.13 |
Annual Sum or Average | 0.220123E+10 | 0.198110E+10 | ||||||
Minimum of Months | 516492.73 | 464843.45 | 258.51 | 232.66 | 232.66 | 38.24 | 0.29 | |
Maximum of Months | 0.540119E+09 | 0.486107E+09 | 718.08 | 646.27 | 646.27 | 66.50 | 1.19 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.116099E+10 | 0.104489E+10 | 2524.58 | 24-JAN-16:03 | 2272.13 | 2272.13 | 8.40 | 5.02 |
February | 0.136076E+10 | 0.122468E+10 | 3496.86 | 15-FEB-16:01 | 3147.17 | 3147.17 | 8.16 | 8.59 |
March | 0.206072E+10 | 0.185465E+10 | 3723.81 | 08-MAR-16:01 | 3351.43 | 3351.43 | 7.32 | 9.86 |
April | 0.393103E+10 | 0.353793E+10 | 3808.34 | 13-APR-18:01 | 3427.50 | 3427.50 | 7.02 | 10.42 |
May | 0.546539E+10 | 0.491885E+10 | 4174.66 | 27-MAY-18:02 | 3757.19 | 3757.19 | 7.08 | 13.99 |
June | 0.749404E+10 | 0.674464E+10 | 4361.02 | 26-JUN-18:25 | 3924.92 | 3924.92 | 6.73 | 16.98 |
July | 0.940633E+10 | 0.846569E+10 | 4325.42 | 21-JUL-21:00 | 3892.88 | 3892.88 | 6.73 | 16.37 |
August | 0.922927E+10 | 0.830634E+10 | 4343.89 | 15-AUG-18:13 | 3909.51 | 3909.51 | 6.73 | 16.69 |
September | 0.744464E+10 | 0.670018E+10 | 4319.57 | 18-SEP-18:03 | 3887.61 | 3887.61 | 7.29 | 16.27 |
October | 0.457191E+10 | 0.411472E+10 | 4255.93 | 10-OCT-18:01 | 3830.33 | 3830.33 | 7.17 | 15.21 |
November | 0.186709E+10 | 0.168038E+10 | 3409.53 | 02-NOV-15:01 | 3068.57 | 3068.57 | 8.16 | 8.17 |
December | 0.122990E+10 | 0.110691E+10 | 2713.06 | 02-DEC-16:03 | 2441.75 | 2441.75 | 8.40 | 5.57 |
Annual Sum or Average | 0.552221E+11 | 0.496999E+11 | ||||||
Minimum of Months | 0.116099E+10 | 0.104489E+10 | 2524.58 | 2272.13 | 2272.13 | 6.73 | 5.02 | |
Maximum of Months | 0.940633E+10 | 0.846569E+10 | 4361.02 | 3924.92 | 3924.92 | 8.40 | 16.98 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.682696E+10 | 0.614427E+10 | 3777.60 | 01-JAN-00:03 | 3399.84 | 3399.84 | 8.42 | 26.48 |
February | 0.673538E+10 | 0.606184E+10 | 3777.60 | 01-FEB-00:05 | 3399.84 | 3399.84 | 8.40 | 26.48 |
March | 0.818744E+10 | 0.736870E+10 | 3777.60 | 01-MAR-00:05 | 3399.84 | 3399.84 | 8.41 | 26.48 |
April | 0.927960E+10 | 0.835164E+10 | 3777.60 | 01-APR-00:10 | 3399.84 | 3399.84 | 8.40 | 26.48 |
May | 0.100304E+11 | 0.902733E+10 | 3777.60 | 01-MAY-00:10 | 3399.84 | 3399.84 | 8.61 | 26.48 |
June | 0.979056E+10 | 0.881150E+10 | 3777.60 | 01-JUN-00:10 | 3399.84 | 3399.84 | 8.90 | 26.48 |
July | 0.101179E+11 | 0.910612E+10 | 3777.60 | 01-JUL-00:10 | 3399.84 | 3399.84 | 9.19 | 26.48 |
August | 0.101179E+11 | 0.910612E+10 | 3777.60 | 01-AUG-00:10 | 3399.84 | 3399.84 | 9.42 | 26.48 |
September | 0.979062E+10 | 0.881156E+10 | 3777.60 | 01-SEP-00:10 | 3399.84 | 3399.84 | 9.15 | 26.48 |
October | 0.950663E+10 | 0.855597E+10 | 3777.60 | 01-OCT-00:10 | 3399.84 | 3399.84 | 8.94 | 26.48 |
November | 0.801670E+10 | 0.721503E+10 | 3777.60 | 01-NOV-00:10 | 3399.84 | 3399.84 | 8.56 | 26.48 |
December | 0.671033E+10 | 0.603930E+10 | 3777.60 | 01-DEC-00:10 | 3399.84 | 3399.84 | 8.40 | 26.48 |
Annual Sum or Average | 0.105110E+12 | 0.945994E+11 | ||||||
Minimum of Months | 0.671033E+10 | 0.603930E+10 | 3777.60 | 3399.84 | 3399.84 | 8.40 | 26.48 | |
Maximum of Months | 0.101179E+11 | 0.910612E+10 | 3777.60 | 3399.84 | 3399.84 | 9.42 | 26.48 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:03 | 14.37 | 14.37 | 47.82 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 48.77 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 49.09 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.07 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 52.72 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 52.97 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.57 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 53.06 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 52.97 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 52.10 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 52.63 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:10 | 14.37 | 14.37 | 49.93 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 47.82 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.57 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 58.05 | 80.69 | 22302.15 | 191774.38 | 22-JAN-19:02 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 59.58 | 81.63 | 18181.91 | 154213.39 | 09-FEB-23:43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 55.72 | 80.67 | 10094.81 | 178089.02 | 22-MAR-08:62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 55.84 | 79.90 | 6293.39 | 159267.09 | 04-APR-04:55 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 39.59 | 39.59 | 1748.73 | 114393.96 | 05-MAY-03:43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 44.84 | 44.84 | 250.92 | 75887.48 | 09-JUN-05:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 51.11 | 51.11 | 18.64 | 28275.87 | 10-JUL-08:04 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 60.24 | 60.24 | 18.37 | 26727.58 | 09-AUG-08:04 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 61.02 | 61.02 | 106.23 | 45429.34 | 27-SEP-18:04 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 44.78 | 44.78 | 6344.05 | 209280.07 | 25-OCT-15:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 53.05 | 79.40 | 15781.47 | 154563.99 | 05-NOV-08:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 62.33 | 80.22 | 25556.64 | 186518.85 | 15-DEC-16:03 |
Annual Sum or Average | 0.00 | 8851.06 | ||||||
Minimum of Months | 0.00 | 0.00 | 39.59 | 39.59 | 18.37 | 26727.58 | ||
Maximum of Months | 0.00 | 0.00 | 62.33 | 81.63 | 25556.64 | 209280.07 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16704.97 | 129940.26 | 01-JAN-16:03 | 9.54 | 8.37 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 21444.86 | 285904.02 | 13-FEB-16:03 | 10.06 | 7.48 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 30034.07 | 329266.09 | 08-MAR-16:01 | 10.27 | 7.30 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 75769.93 | 417947.59 | 28-APR-18:01 | 10.75 | 6.98 | 0.00 | 0.00 | 01-APR-00:10 |
May | 118577.53 | 446008.96 | 18-MAY-18:01 | 10.72 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 201861.54 | 499821.88 | 28-JUN-18:03 | 11.21 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 265612.73 | 558874.51 | 31-JUL-18:02 | 12.57 | 7.53 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 243411.64 | 483815.43 | 17-AUG-18:03 | 11.06 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 175223.53 | 469176.45 | 20-SEP-18:01 | 10.93 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 89654.16 | 450609.82 | 06-OCT-15:01 | 10.76 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 26053.49 | 225661.09 | 02-NOV-15:01 | 10.18 | 8.14 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 17199.71 | 117139.02 | 29-DEC-16:04 | 9.43 | 8.37 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 107355.48 | 0.00 | ||||||
Minimum of Months | 16704.97 | 117139.02 | 9.43 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 265612.73 | 558874.51 | 12.57 | 8.37 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 47.82 | 59.79 | 27539.22 | 64498.28 | 10-JAN-21:11 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 48.77 | 58.87 | 27730.80 | 62602.47 | 15-FEB-07:25 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 49.09 | 59.03 | 27113.01 | 68024.28 | 14-MAR-06:51 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.07 | 59.31 | 25751.18 | 63722.89 | 07-APR-06:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 52.72 | 59.65 | 24065.14 | 56924.43 | 06-MAY-07:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 52.97 | 59.10 | 22494.37 | 46670.33 | 01-JUN-06:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.57 | 59.60 | 21425.86 | 43654.91 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 53.06 | 58.43 | 21220.61 | 42906.88 | 31-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 52.97 | 58.45 | 21875.63 | 47873.43 | 25-SEP-06:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 52.10 | 58.55 | 23204.43 | 57764.88 | 18-OCT-06:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 52.63 | 58.94 | 24866.37 | 60521.50 | 20-NOV-07:41 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 49.93 | 59.09 | 26465.54 | 63490.73 | 03-DEC-08:61 |
Annual Sum or Average | 0.00 | 24460.65 | ||||||
Minimum of Months | 0.00 | 0.00 | 47.82 | 58.43 | 21220.61 | 42906.88 | ||
Maximum of Months | 0.00 | 0.00 | 53.57 | 59.79 | 27730.80 | 68024.28 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.272016E+11 | 0.00 | 0.216634E+10 | 0.392352E+11 | 0.00 | 0.00 |
February | 0.231096E+11 | 0.00 | 0.779789E+10 | 0.351372E+11 | 0.00 | 0.00 |
March | 0.200145E+11 | 0.00 | 0.252991E+11 | 0.388414E+11 | 0.00 | 0.00 |
April | 0.153082E+11 | 0.00 | 0.100748E+12 | 0.388405E+11 | 0.00 | 0.00 |
May | 0.431416E+10 | 0.00 | 0.188588E+12 | 0.410282E+11 | 0.00 | 0.00 |
June | 0.577650E+09 | 0.00 | 0.330153E+12 | 0.441623E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.453353E+12 | 0.483117E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.406181E+12 | 0.492660E+11 | 0.00 | 0.00 |
September | 0.206320E+09 | 0.00 | 0.265232E+12 | 0.456950E+11 | 0.00 | 0.00 |
October | 0.137209E+11 | 0.00 | 0.115092E+12 | 0.444518E+11 | 0.00 | 0.00 |
November | 0.289288E+11 | 0.00 | 0.452953E+10 | 0.406959E+11 | 0.00 | 0.00 |
December | 0.332934E+11 | 0.00 | 0.810365E+09 | 0.403389E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.166675E+12 | 0.00 | 0.189995E+13 | 0.506004E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.810365E+09 | 0.351372E+11 | 0.00 | 0.00 |
Maximum of Months | 0.332934E+11 | 0.00 | 0.453353E+12 | 0.492660E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.100514E+10 | 0.00 | 0.119195E+09 | 0.587890E+10 | 0.00 | 0.00 |
February | 0.417676E+09 | 0.00 | 0.100811E+10 | 0.530997E+10 | 0.00 | 0.00 |
March | 17460099.59 | 0.00 | 0.393816E+10 | 0.587890E+10 | 0.00 | 0.00 |
April | 26563.20 | 0.00 | 0.151227E+11 | 0.568926E+10 | 0.00 | 0.00 |
May | 46050.77 | 0.00 | 0.280797E+11 | 0.587890E+10 | 0.00 | 0.00 |
June | 57664.23 | 0.00 | 0.457900E+11 | 0.568926E+10 | 0.00 | 0.00 |
July | 38491.95 | 0.00 | 0.671160E+11 | 0.587890E+10 | 0.00 | 0.00 |
August | 38897.02 | 0.00 | 0.589319E+11 | 0.587890E+10 | 0.00 | 0.00 |
September | 50305.88 | 0.00 | 0.381063E+11 | 0.568926E+10 | 0.00 | 0.00 |
October | 18787445.26 | 0.00 | 0.160914E+11 | 0.587890E+10 | 0.00 | 0.00 |
November | 27948913.65 | 0.00 | 0.450045E+09 | 0.568926E+10 | 0.00 | 0.00 |
December | 0.725283E+09 | 0.00 | 35543.17 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.221255E+10 | 0.00 | 0.274753E+12 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 26563.20 | 0.00 | 35543.17 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 0.100514E+10 | 0.00 | 0.671160E+11 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.392352E+11 | 0.216839E+10 | 0.272016E+11 | 0.358268E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.351372E+11 | 0.779946E+10 | 0.231096E+11 | 0.277079E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388414E+11 | 0.253014E+11 | 0.200145E+11 | 0.167095E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.388405E+11 | 0.100751E+12 | 0.153082E+11 | 0.594306E+11 | 2003956.43 | 0.00 | 0.00 | 0.00 |
May | 0.410282E+11 | 0.188588E+12 | 0.431416E+10 | 0.249321E+11 | 0.561394E+09 | 0.00 | 0.00 | 0.00 |
June | 0.441623E+11 | 0.330153E+12 | 0.577650E+09 | 0.117110E+11 | 0.179943E+11 | 0.00 | 0.00 | 0.00 |
July | 0.483117E+11 | 0.453353E+12 | 0.00 | 0.958854E+10 | 0.256626E+11 | 0.00 | 0.00 | 0.00 |
August | 0.492660E+11 | 0.406181E+12 | 0.00 | 0.920269E+10 | 0.129886E+11 | 0.00 | 0.00 | 0.00 |
September | 0.456950E+11 | 0.265232E+12 | 0.206320E+09 | 0.802446E+10 | 0.218385E+10 | 0.00 | 0.00 | 0.00 |
October | 0.444518E+11 | 0.115096E+12 | 0.137209E+11 | 0.689217E+11 | 25505914.21 | 0.00 | 0.00 | 0.00 |
November | 0.406959E+11 | 0.453218E+10 | 0.289288E+11 | 0.168305E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.403389E+11 | 0.811685E+09 | 0.332934E+11 | 0.359905E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.506004E+12 | 0.189997E+13 | 0.166675E+12 | 0.152246E+13 | 0.594182E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.351372E+11 | 0.811685E+09 | 0.00 | 0.802446E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.492660E+11 | 0.453353E+12 | 0.332934E+11 | 0.359905E+12 | 0.256626E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.119195E+09 | 0.100514E+10 | 0.758311E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.100811E+10 | 0.417676E+09 | 0.600604E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.393816E+10 | 17460099.59 | 0.409856E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.151227E+11 | 26563.20 | 0.181916E+11 | 0.169953E+09 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.280797E+11 | 46050.77 | 0.752642E+10 | 0.844101E+09 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.457900E+11 | 57664.23 | 0.169619E+10 | 0.802583E+10 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.671160E+11 | 38491.95 | 99548660.49 | 0.178384E+11 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.589319E+11 | 38897.02 | 0.135210E+09 | 0.121180E+11 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.381063E+11 | 50305.88 | 0.110454E+10 | 0.307905E+10 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.160914E+11 | 18787445.26 | 0.209277E+11 | 0.327834E+09 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.450045E+09 | 27948913.65 | 0.484863E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 35543.17 | 0.725283E+09 | 0.797943E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.274753E+12 | 0.221255E+10 | 0.354839E+12 | 0.424032E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 35543.17 | 26563.20 | 99548660.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.671160E+11 | 0.100514E+10 | 0.797943E+11 | 0.178384E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.392352E+11 | 0.272016E+11 | 0.216634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.351372E+11 | 0.231096E+11 | 0.779789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388414E+11 | 0.200145E+11 | 0.252991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.388405E+11 | 0.153082E+11 | 0.100748E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.410282E+11 | 0.431416E+10 | 0.188588E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.441623E+11 | 0.577650E+09 | 0.330153E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.483117E+11 | 0.00 | 0.453353E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.492660E+11 | 0.00 | 0.406181E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.456950E+11 | 0.206320E+09 | 0.265232E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.444518E+11 | 0.137209E+11 | 0.115092E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.406959E+11 | 0.289288E+11 | 0.452953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.403389E+11 | 0.332934E+11 | 0.810365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.506004E+12 | 0.166675E+12 | 0.189995E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.351372E+11 | 0.00 | 0.810365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.492660E+11 | 0.332934E+11 | 0.453353E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 0.100514E+10 | 0.119195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.417676E+09 | 0.100811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 17460099.59 | 0.393816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 26563.20 | 0.151227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 46050.77 | 0.280797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 57664.23 | 0.457900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 38491.95 | 0.671160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 38897.02 | 0.589319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 50305.88 | 0.381063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 18787445.26 | 0.160914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 27948913.65 | 0.450045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.725283E+09 | 35543.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.221255E+10 | 0.274753E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 26563.20 | 35543.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.100514E+10 | 0.671160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.905390E+09 | 0.00 | 0.00 | 0.114802E+09 | 0.00 | 0.00 | 0.519089E+11 | 0.00 | 0.96 |
February | 0.426136E+10 | 0.00 | 0.00 | 76223558.90 | 0.00 | 0.00 | 0.394485E+11 | 0.00 | 0.89 |
March | 0.121581E+11 | 0.00 | 0.00 | 45259198.98 | 0.00 | 0.00 | 0.320574E+11 | 0.00 | 0.88 |
April | 0.998732E+10 | 0.00 | 0.00 | 32267844.76 | 18542.02 | 0.00 | 0.265777E+11 | 0.00 | 0.92 |
May | 0.517891E+10 | 0.00 | 0.00 | 31545306.81 | 1423164.50 | 0.00 | 0.247717E+11 | 0.00 | 0.93 |
June | 0.437297E+09 | 0.262593E+09 | 0.00 | 42427391.69 | 0.116328E+09 | 0.00 | 0.185519E+11 | 0.00 | 0.92 |
July | 16702390.33 | 0.701350E+09 | 0.00 | 52306773.66 | 49762290.82 | 0.00 | 0.119506E+11 | 0.00 | 0.96 |
August | 19993868.96 | 0.250909E+09 | 0.00 | 68400324.23 | 8882976.52 | 0.00 | 0.175579E+11 | 0.00 | 1.05 |
September | 639134.01 | 31855508.94 | 0.00 | 85085502.45 | 39486.76 | 0.00 | 0.315894E+11 | 0.00 | 1.22 |
October | 25544690.36 | 0.00 | 0.00 | 0.123907E+09 | 0.00 | 0.00 | 0.515902E+11 | 0.00 | 1.22 |
November | 24541672.87 | 0.00 | 0.00 | 0.148847E+09 | 0.00 | 0.00 | 0.609046E+11 | 0.00 | 1.10 |
December | 0.197689E+09 | 0.00 | 0.00 | 0.157769E+09 | 0.00 | 0.00 | 0.590097E+11 | 0.00 | 1.04 |
Annual Sum or Average | 0.332135E+11 | 0.124671E+10 | 0.00 | 0.978842E+09 | 0.176454E+09 | 0.00 | 0.425919E+12 | 0.00 | 1.01 |
Minimum of Months | 639134.01 | 0.00 | 0.00 | 31545306.81 | 0.00 | 0.00 | 0.119506E+11 | 0.00 | 0.88 |
Maximum of Months | 0.121581E+11 | 0.701350E+09 | 0.00 | 0.157769E+09 | 0.116328E+09 | 0.00 | 0.609046E+11 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.273651E+10 | 0.00 | 0.00 | 6157090.57 | 0.00 | 0.262652E+09 | 0.265903E+10 | 0.00 | 1.95 |
February | 0.244778E+10 | 0.00 | 0.00 | 6557230.45 | 0.00 | 59122867.94 | 0.257680E+10 | 0.00 | 2.01 |
March | 0.268491E+10 | 0.00 | 0.00 | 4517663.23 | 0.00 | 8054893.83 | 0.234064E+10 | 0.00 | 2.00 |
April | 0.181064E+10 | 4103.85 | 0.00 | 5398664.62 | 0.00 | 0.00 | 0.216268E+10 | 0.00 | 2.04 |
May | 0.148195E+10 | 193874.45 | 0.00 | 5181089.57 | 0.00 | 0.00 | 0.159642E+10 | 0.00 | 1.95 |
June | 0.464769E+09 | 76887879.97 | 0.00 | 6023761.07 | 0.00 | 0.00 | 0.143666E+10 | 0.00 | 2.05 |
July | 7709300.84 | 0.146242E+09 | 0.00 | 6808167.86 | 0.00 | 0.00 | 0.117481E+10 | 0.00 | 2.27 |
August | 12550201.88 | 63482577.96 | 0.00 | 9815020.87 | 0.00 | 0.00 | 0.166419E+10 | 0.00 | 2.49 |
September | 0.274941E+09 | 10362745.30 | 0.00 | 10634771.39 | 0.00 | 0.00 | 0.255370E+10 | 0.00 | 2.71 |
October | 0.128996E+10 | 0.00 | 0.00 | 9827924.28 | 0.00 | 27106341.47 | 0.368036E+10 | 0.00 | 2.63 |
November | 0.232030E+10 | 0.00 | 0.00 | 8767984.95 | 0.00 | 1374249.56 | 0.381592E+10 | 0.00 | 2.12 |
December | 0.282333E+10 | 0.00 | 0.00 | 9183303.28 | 0.00 | 0.196956E+09 | 0.293395E+10 | 0.00 | 1.94 |
Annual Sum or Average | 0.183554E+11 | 0.297173E+09 | 0.00 | 88872672.13 | 0.00 | 0.555266E+09 | 0.285952E+11 | 0.00 | 2.18 |
Minimum of Months | 7709300.84 | 0.00 | 0.00 | 4517663.23 | 0.00 | 0.00 | 0.117481E+10 | 0.00 | 1.94 |
Maximum of Months | 0.282333E+10 | 0.146242E+09 | 0.00 | 10634771.39 | 0.00 | 0.262652E+09 | 0.381592E+10 | 0.00 | 2.71 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.383729E+10 | 0.00 | 0.00 | 905559.59 | 0.00 | 0.00 | 0.686059E+09 | 0.00 | 1.31 |
February | 0.312573E+10 | 0.00 | 0.00 | 1046134.09 | 0.00 | 0.00 | 0.978487E+09 | 0.00 | 1.34 |
March | 0.281103E+10 | 0.00 | 0.00 | 1495789.42 | 0.00 | 0.00 | 0.166608E+10 | 0.00 | 1.42 |
April | 0.149988E+10 | 0.00 | 0.00 | 2536284.96 | 1991.25 | 0.00 | 0.236099E+10 | 0.00 | 1.54 |
May | 0.799195E+09 | 145813.74 | 0.00 | 3398344.76 | 7021.52 | 0.00 | 0.241464E+10 | 0.00 | 1.59 |
June | 0.184800E+09 | 41183294.09 | 0.00 | 4755478.26 | 810873.50 | 0.00 | 0.188981E+10 | 0.00 | 1.60 |
July | 3068843.31 | 79840226.73 | 0.00 | 5551470.51 | 1836399.51 | 0.00 | 0.127386E+10 | 0.00 | 1.62 |
August | 14838349.20 | 26836034.93 | 0.00 | 6599010.26 | 1272899.57 | 0.00 | 0.170161E+10 | 0.00 | 1.67 |
September | 76182782.03 | 3421114.17 | 0.00 | 5930462.00 | 0.00 | 0.00 | 0.262421E+10 | 0.00 | 1.71 |
October | 0.124828E+10 | 0.00 | 0.00 | 3779368.08 | 0.00 | 0.00 | 0.275855E+10 | 0.00 | 1.56 |
November | 0.297571E+10 | 0.00 | 0.00 | 1594051.31 | 0.00 | 0.00 | 0.159898E+10 | 0.00 | 1.32 |
December | 0.391435E+10 | 0.00 | 0.00 | 772695.66 | 0.00 | 0.00 | 0.658182E+09 | 0.00 | 1.28 |
Annual Sum or Average | 0.204904E+11 | 0.151426E+09 | 0.00 | 38364648.91 | 3929185.36 | 0.00 | 0.206115E+11 | 0.00 | 1.50 |
Minimum of Months | 3068843.31 | 0.00 | 0.00 | 772695.66 | 0.00 | 0.00 | 0.658182E+09 | 0.00 | 1.28 |
Maximum of Months | 0.391435E+10 | 79840226.73 | 0.00 | 6599010.26 | 1836399.51 | 0.00 | 0.275855E+10 | 0.00 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.276672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
February | 0.249637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
March | 0.269833E+10 | 0.00 | 0.00 | 1923.06 | 0.00 | 0.00 | 12694576.29 | 0.00 | 0.41 |
April | 0.185209E+10 | 0.00 | 0.00 | 607367.95 | 1225.80 | 0.00 | 0.483689E+09 | 0.00 | 0.44 |
May | 0.933087E+09 | 94084.35 | 0.00 | 2381497.25 | 0.00 | 0.00 | 0.113775E+10 | 0.00 | 0.49 |
June | 0.137976E+09 | 37051307.62 | 0.00 | 4829895.56 | 14014.32 | 0.00 | 0.140169E+10 | 0.00 | 0.60 |
July | 0.00 | 70062990.80 | 0.00 | 5657143.70 | 0.00 | 0.00 | 0.106520E+10 | 0.00 | 0.66 |
August | 227776.63 | 22239529.58 | 0.00 | 6448934.35 | 0.00 | 0.00 | 0.134373E+10 | 0.00 | 0.64 |
September | 51012623.36 | 2232448.97 | 0.00 | 4847924.19 | 0.00 | 0.00 | 0.180930E+10 | 0.00 | 0.57 |
October | 0.165270E+10 | 0.00 | 0.00 | 1542571.38 | 0.00 | 0.00 | 0.802276E+09 | 0.00 | 0.46 |
November | 0.274314E+10 | 0.00 | 0.00 | 12267.85 | 0.00 | 0.00 | 29589705.43 | 0.00 | 0.38 |
December | 0.280160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.181332E+11 | 0.131680E+09 | 0.00 | 26329525.29 | 15240.11 | 0.00 | 0.808593E+10 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.280160E+10 | 70062990.80 | 0.00 | 6448934.35 | 14014.32 | 0.00 | 0.180930E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.266275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171181E+09 | 0.00 | 0.00 | 0.67 |
February | 0.254239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14618757.19 | 0.00 | 0.00 | 0.68 |
March | 0.277688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 |
April | 0.233337E+10 | 0.00 | 0.00 | 0.00 | 1255.58 | 0.00 | 0.00 | 0.00 | 0.76 |
May | 0.192020E+10 | 0.00 | 0.00 | 0.00 | 96369.79 | 0.00 | 0.00 | 0.00 | 0.77 |
June | 0.111067E+10 | 2569767.52 | 0.00 | 103640.68 | 22612826.78 | 0.00 | 55728680.50 | 0.00 | 0.73 |
July | 0.589741E+09 | 2981053.04 | 0.00 | 166240.82 | 45928783.60 | 0.00 | 83477775.70 | 0.00 | 0.72 |
August | 0.849833E+09 | 0.00 | 0.00 | 78033.54 | 17432390.68 | 0.00 | 59302898.44 | 0.00 | 0.73 |
September | 0.149295E+10 | 0.00 | 0.00 | 0.00 | 2157157.48 | 0.00 | 0.00 | 0.00 | 0.78 |
October | 0.237443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 |
November | 0.284009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
December | 0.285820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11452922.82 | 0.00 | 0.00 | 0.66 |
Annual Sum or Average | 0.243515E+11 | 5550820.56 | 0.00 | 347915.04 | 88228783.90 | 0.197252E+09 | 0.198509E+09 | 0.00 | 0.72 |
Minimum of Months | 0.589741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.285820E+10 | 2981053.04 | 0.00 | 166240.82 | 45928783.60 | 0.171181E+09 | 83477775.70 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.195997E+09 | 0.00 | 0.00 | 0.687413E+11 | 0.00 | 19.11 |
February | 1319715.73 | 0.00 | 0.00 | 0.173478E+09 | 0.00 | 0.00 | 0.625518E+11 | 0.00 | 19.65 |
March | 11032939.33 | 0.00 | 0.00 | 0.160917E+09 | 0.00 | 0.00 | 0.688775E+11 | 0.00 | 21.09 |
April | 11432183.43 | 26217.25 | 0.00 | 0.141810E+09 | 0.00 | 0.00 | 0.568836E+11 | 0.00 | 22.79 |
May | 6086778.56 | 1700107.45 | 0.00 | 0.121619E+09 | 0.00 | 0.00 | 0.461876E+11 | 0.00 | 23.03 |
June | 0.00 | 0.544265E+09 | 0.00 | 0.100652E+09 | 0.00 | 0.00 | 0.272195E+11 | 0.00 | 21.50 |
July | 0.00 | 0.105211E+10 | 0.00 | 89723670.13 | 0.00 | 0.00 | 0.151891E+11 | 0.00 | 20.92 |
August | 0.00 | 0.344589E+09 | 0.00 | 0.110042E+09 | 0.00 | 0.00 | 0.213713E+11 | 0.00 | 21.63 |
September | 0.00 | 39255911.73 | 0.00 | 0.113445E+09 | 0.00 | 0.00 | 0.364690E+11 | 0.00 | 23.41 |
October | 20394777.33 | 0.00 | 0.00 | 0.148197E+09 | 0.00 | 0.00 | 0.583922E+11 | 0.00 | 22.26 |
November | 15843188.58 | 0.00 | 0.00 | 0.177129E+09 | 0.00 | 0.00 | 0.695869E+11 | 0.00 | 19.48 |
December | 3200434.59 | 0.00 | 0.00 | 0.215560E+09 | 0.00 | 0.00 | 0.696628E+11 | 0.00 | 18.86 |
Annual Sum or Average | 69310017.54 | 0.198195E+10 | 0.00 | 0.174857E+10 | 0.00 | 0.00 | 0.601133E+12 | 0.00 | 21.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 89723670.13 | 0.00 | 0.00 | 0.151891E+11 | 0.00 | 18.86 |
Maximum of Months | 20394777.33 | 0.105211E+10 | 0.00 | 0.215560E+09 | 0.00 | 0.00 | 0.696628E+11 | 0.00 | 23.41 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126968E+11 | 0.00 | 0.00 | 31069142.34 | 0.00 | 0.00 | 0.228849E+11 | 0.00 | 4.28 |
February | 0.887510E+10 | 0.00 | 0.00 | 31736382.65 | 0.00 | 0.00 | 0.229802E+11 | 0.00 | 4.35 |
March | 0.942465E+10 | 0.00 | 0.00 | 23732488.32 | 0.00 | 0.00 | 0.240600E+11 | 0.00 | 4.43 |
April | 0.674872E+10 | 14682.15 | 0.00 | 22989354.60 | 0.00 | 0.00 | 0.207350E+11 | 0.00 | 4.52 |
May | 0.513431E+10 | 1077227.38 | 0.00 | 19574090.46 | 49678.70 | 0.00 | 0.173649E+11 | 0.00 | 4.53 |
June | 0.178217E+10 | 0.289875E+09 | 0.00 | 20759452.70 | 6089795.11 | 0.00 | 0.120231E+11 | 0.00 | 4.36 |
July | 0.204304E+09 | 0.565509E+09 | 0.00 | 24783998.63 | 14847052.67 | 0.00 | 0.797298E+10 | 0.00 | 4.35 |
August | 0.399539E+09 | 0.219832E+09 | 0.00 | 36169967.78 | 2859511.31 | 0.00 | 0.107195E+11 | 0.00 | 4.57 |
September | 0.938816E+09 | 33123957.11 | 0.00 | 42596716.90 | 0.00 | 0.00 | 0.172470E+11 | 0.00 | 4.95 |
October | 0.486119E+10 | 0.00 | 0.00 | 43328163.09 | 0.00 | 0.00 | 0.248141E+11 | 0.00 | 4.88 |
November | 0.737261E+10 | 0.00 | 0.00 | 43937791.19 | 0.00 | 0.00 | 0.288929E+11 | 0.00 | 4.35 |
December | 0.118312E+11 | 0.00 | 0.00 | 42773865.18 | 0.00 | 0.00 | 0.246459E+11 | 0.00 | 4.21 |
Annual Sum or Average | 0.702694E+11 | 0.110943E+10 | 0.00 | 0.383451E+09 | 23846037.79 | 0.00 | 0.234341E+12 | 0.00 | 4.48 |
Minimum of Months | 0.204304E+09 | 0.00 | 0.00 | 19574090.46 | 0.00 | 0.00 | 0.797298E+10 | 0.00 | 4.21 |
Maximum of Months | 0.126968E+11 | 0.565509E+09 | 0.00 | 43937791.19 | 14847052.67 | 0.00 | 0.288929E+11 | 0.00 | 4.95 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.358752E+11 | 0.00 | 0.00 | 73385051.43 | 0.00 | 0.00 | 0.592270E+11 | 0.00 | 1.64 |
February | 0.266660E+11 | 0.00 | 0.00 | 73917343.48 | 0.00 | 0.00 | 0.597758E+11 | 0.00 | 1.68 |
March | 0.252169E+11 | 0.00 | 0.00 | 85412608.36 | 0.00 | 0.00 | 0.694012E+11 | 0.00 | 1.77 |
April | 0.159025E+11 | 41119.98 | 0.00 | 87143371.07 | 0.00 | 0.00 | 0.659544E+11 | 0.00 | 1.93 |
May | 0.111237E+11 | 3040895.59 | 0.00 | 83853956.38 | 115204.86 | 0.00 | 0.571029E+11 | 0.00 | 1.98 |
June | 0.272293E+10 | 0.818571E+09 | 0.00 | 93132309.30 | 26730448.31 | 0.00 | 0.415636E+11 | 0.00 | 1.97 |
July | 0.109987E+09 | 0.160456E+10 | 0.00 | 0.106928E+09 | 51350575.24 | 0.00 | 0.275135E+11 | 0.00 | 2.00 |
August | 0.396202E+09 | 0.558007E+09 | 0.00 | 0.131454E+09 | 21584811.24 | 0.00 | 0.365943E+11 | 0.00 | 2.07 |
September | 0.109742E+10 | 71043857.01 | 0.00 | 0.135017E+09 | 0.00 | 0.00 | 0.572823E+11 | 0.00 | 2.16 |
October | 0.897687E+10 | 0.00 | 0.00 | 0.133301E+09 | 0.00 | 0.00 | 0.771593E+11 | 0.00 | 1.98 |
November | 0.175170E+11 | 0.00 | 0.00 | 0.115339E+09 | 0.00 | 0.00 | 0.804677E+11 | 0.00 | 1.68 |
December | 0.331458E+11 | 0.00 | 0.00 | 74897416.14 | 0.00 | 0.00 | 0.628043E+11 | 0.00 | 1.60 |
Annual Sum or Average | 0.178751E+12 | 0.305526E+10 | 0.00 | 0.119378E+10 | 99781039.65 | 0.00 | 0.694846E+12 | 0.00 | 1.87 |
Minimum of Months | 0.109987E+09 | 0.00 | 0.00 | 73385051.43 | 0.00 | 0.00 | 0.275135E+11 | 0.00 | 1.60 |
Maximum of Months | 0.358752E+11 | 0.160456E+10 | 0.00 | 0.135017E+09 | 51350575.24 | 0.00 | 0.804677E+11 | 0.00 | 2.16 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.290217E+09 | 0.00 | 0.00 | 5344396.59 | 0.00 | 0.794848E+09 | 0.448520E+09 | 0.00 | 0.47 |
February | 0.248952E+09 | 0.00 | 0.00 | 6961106.63 | 0.00 | 0.599549E+09 | 0.528170E+09 | 0.00 | 0.47 |
March | 0.259085E+09 | 0.00 | 0.00 | 9009161.01 | 0.00 | 0.385842E+09 | 0.826538E+09 | 0.00 | 0.47 |
April | 0.159398E+09 | 381535.13 | 0.00 | 12984256.39 | 2717.17 | 76436364.56 | 0.953701E+09 | 0.00 | 0.47 |
May | 0.121634E+09 | 3168853.91 | 4340.14 | 13394961.51 | 197305.58 | 24044827.29 | 0.768576E+09 | 217.33 | 0.47 |
June | 37827558.55 | 49244158.01 | 8131.80 | 10177497.95 | 1456358.71 | 3504069.22 | 0.422197E+09 | 1725.74 | 0.47 |
July | 402215.52 | 0.285249E+09 | 123045.28 | 2718123.29 | 14015131.27 | 16084.11 | 44968484.13 | 11404.44 | 0.47 |
August | 9865504.38 | 0.175021E+09 | 55681.12 | 5109168.74 | 7346862.70 | 129410.35 | 0.128925E+09 | 5990.20 | 0.47 |
September | 44150392.19 | 34817939.06 | 0.00 | 13042083.86 | 1669886.71 | 583415.80 | 0.517525E+09 | 0.00 | 0.47 |
October | 0.140941E+09 | 2946211.90 | 0.00 | 14336561.60 | 321078.80 | 0.130991E+09 | 0.921056E+09 | 0.00 | 0.47 |
November | 0.236722E+09 | 0.00 | 0.00 | 8908456.18 | 0.00 | 0.436426E+09 | 0.841231E+09 | 0.00 | 0.47 |
December | 0.288635E+09 | 0.00 | 0.00 | 5726173.02 | 0.00 | 0.801920E+09 | 0.450824E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.183783E+10 | 0.550829E+09 | 191198.34 | 0.107712E+09 | 25009340.94 | 0.325429E+10 | 0.685223E+10 | 19337.70 | 0.47 |
Minimum of Months | 402215.52 | 0.00 | 0.00 | 2718123.29 | 0.00 | 16084.11 | 44968484.13 | 0.00 | 0.47 |
Maximum of Months | 0.290217E+09 | 0.285249E+09 | 123045.28 | 14336561.60 | 14015131.27 | 0.801920E+09 | 0.953701E+09 | 11404.44 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.401227E+09 | 0.00 | 0.00 | 1341492.55 | 0.00 | 0.103905E+10 | 97129504.66 | 0.00 | 0.47 |
February | 0.363189E+09 | 0.00 | 0.00 | 2483278.54 | 0.00 | 0.800606E+09 | 0.217191E+09 | 0.00 | 0.47 |
March | 0.360258E+09 | 0.00 | 0.00 | 5095716.19 | 0.00 | 0.587642E+09 | 0.527304E+09 | 0.00 | 0.47 |
April | 0.227177E+09 | 380482.78 | 0.00 | 10473267.44 | 3724.49 | 0.119999E+09 | 0.844730E+09 | 0.00 | 0.47 |
May | 0.140305E+09 | 3142671.43 | 4099.81 | 12600005.89 | 223093.66 | 28131332.77 | 0.746505E+09 | 457.13 | 0.47 |
June | 38506305.17 | 49250988.20 | 8514.98 | 10264206.81 | 1443588.21 | 3533260.16 | 0.421346E+09 | 1341.40 | 0.47 |
July | 399335.74 | 0.284316E+09 | 116032.30 | 2720028.25 | 14921431.79 | 16082.22 | 44963824.63 | 10370.81 | 0.47 |
August | 9902233.87 | 0.172531E+09 | 57404.40 | 4888306.51 | 9810707.40 | 180552.36 | 0.129041E+09 | 8253.33 | 0.47 |
September | 49051783.54 | 33242062.11 | 0.00 | 10814532.13 | 3241488.58 | 785297.04 | 0.514581E+09 | 0.00 | 0.47 |
October | 0.245804E+09 | 2642755.66 | 308.67 | 8861062.35 | 623629.65 | 0.225297E+09 | 0.727221E+09 | 213.92 | 0.47 |
November | 0.394381E+09 | 0.00 | 0.00 | 2665631.77 | 0.00 | 0.752006E+09 | 0.374057E+09 | 0.00 | 0.47 |
December | 0.401584E+09 | 0.00 | 0.00 | 1032406.44 | 0.00 | 0.107121E+10 | 73102684.74 | 0.00 | 0.47 |
Annual Sum or Average | 0.263178E+10 | 0.545507E+09 | 186360.16 | 73239934.89 | 30267663.77 | 0.462845E+10 | 0.471717E+10 | 20636.58 | 0.47 |
Minimum of Months | 399335.74 | 0.00 | 0.00 | 1032406.44 | 0.00 | 16082.22 | 44963824.63 | 0.00 | 0.47 |
Maximum of Months | 0.401584E+09 | 0.284316E+09 | 116032.30 | 12600005.89 | 14921431.79 | 0.107121E+10 | 0.844730E+09 | 10370.81 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114342E+11 | 0.00 | 0.00 | 0.110144E+09 | 0.00 | 0.153976E+09 | 0.916822E+10 | 0.00 | 0.53 |
February | 0.908547E+10 | 0.00 | 0.00 | 0.102796E+09 | 0.00 | 0.00 | 0.957255E+10 | 0.00 | 0.54 |
March | 0.989969E+10 | 0.00 | 0.00 | 68741557.29 | 0.00 | 0.00 | 0.101055E+11 | 0.00 | 0.54 |
April | 0.605323E+10 | 5210116.49 | 0.00 | 69841515.87 | 0.00 | 0.00 | 0.101820E+11 | 0.00 | 0.54 |
May | 0.507873E+10 | 45703898.76 | 0.00 | 60564399.75 | 0.00 | 0.00 | 0.743881E+10 | 0.00 | 0.54 |
June | 0.194652E+10 | 0.687587E+09 | 0.00 | 47290841.53 | 0.00 | 0.00 | 0.442921E+10 | 0.00 | 0.54 |
July | 25706491.75 | 0.405699E+10 | 0.00 | 11771009.89 | 2596403.26 | 0.00 | 0.614782E+09 | 0.00 | 0.54 |
August | 0.105262E+09 | 0.247338E+10 | 0.00 | 26978377.13 | 193724.82 | 0.00 | 0.182067E+10 | 0.00 | 0.54 |
September | 0.524032E+09 | 0.494742E+09 | 0.00 | 92395021.48 | 0.00 | 0.00 | 0.718413E+10 | 0.00 | 0.54 |
October | 0.376302E+10 | 44301531.58 | 0.00 | 0.131941E+09 | 0.00 | 0.00 | 0.124753E+11 | 0.00 | 0.54 |
November | 0.751220E+10 | 0.00 | 0.00 | 0.146712E+09 | 0.00 | 0.00 | 0.129955E+11 | 0.00 | 0.53 |
December | 0.109398E+11 | 0.00 | 0.00 | 0.150482E+09 | 0.00 | 0.00 | 0.988712E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.663678E+11 | 0.780791E+10 | 0.00 | 0.101966E+10 | 2790128.08 | 0.153976E+09 | 0.958737E+11 | 0.00 | 0.54 |
Minimum of Months | 25706491.75 | 0.00 | 0.00 | 11771009.89 | 0.00 | 0.00 | 0.614782E+09 | 0.00 | 0.53 |
Maximum of Months | 0.114342E+11 | 0.405699E+10 | 0.00 | 0.150482E+09 | 2596403.26 | 0.153976E+09 | 0.129955E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.594607E+10 | 0.00 | 0.00 | 6419747.91 | 0.00 | 0.120141E+11 | 0.290559E+10 | 0.00 | 0.53 |
February | 0.546433E+10 | 0.00 | 0.00 | 13431153.32 | 0.00 | 0.753194E+10 | 0.575624E+10 | 0.00 | 0.53 |
March | 0.574446E+10 | 0.00 | 0.00 | 38786788.81 | 0.00 | 0.132913E+10 | 0.129670E+11 | 0.00 | 0.53 |
April | 0.411001E+10 | 3532139.31 | 11289.37 | 72640108.36 | 1635912.49 | 35171033.76 | 0.120917E+11 | 32200.01 | 0.53 |
May | 0.252305E+10 | 37654869.30 | 113135.31 | 87857022.45 | 7856158.48 | 22220257.89 | 0.994841E+10 | 92233.31 | 0.54 |
June | 0.743980E+09 | 0.593286E+09 | 357779.21 | 77284439.28 | 94070685.69 | 5253416.93 | 0.559826E+10 | 60496.15 | 0.54 |
July | 9555878.61 | 0.340944E+10 | 2200071.23 | 22313294.69 | 0.648923E+09 | 46390.88 | 0.620522E+09 | 125774.59 | 0.54 |
August | 0.146977E+09 | 0.183376E+10 | 2123834.63 | 40319129.73 | 0.638220E+09 | 347381.04 | 0.176580E+10 | 151255.88 | 0.54 |
September | 0.841713E+09 | 0.220175E+09 | 317290.92 | 77530801.30 | 0.274294E+09 | 8107690.12 | 0.687534E+10 | 91065.09 | 0.54 |
October | 0.402863E+10 | 24078859.18 | 0.00 | 56992115.84 | 20227698.04 | 0.931423E+09 | 0.113577E+11 | 7088.54 | 0.53 |
November | 0.611769E+10 | 0.00 | 0.00 | 20124564.55 | 0.00 | 0.511023E+10 | 0.941201E+10 | 0.00 | 0.53 |
December | 0.591937E+10 | 0.00 | 0.00 | 5094106.60 | 0.00 | 0.127644E+11 | 0.229420E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.415958E+11 | 0.612193E+10 | 5123400.67 | 0.518793E+09 | 0.168523E+10 | 0.397525E+11 | 0.815928E+11 | 560113.56 | 0.53 |
Minimum of Months | 9555878.61 | 0.00 | 0.00 | 5094106.60 | 0.00 | 46390.88 | 0.620522E+09 | 0.00 | 0.53 |
Maximum of Months | 0.611769E+10 | 0.340944E+10 | 2200071.23 | 87857022.45 | 0.648923E+09 | 0.127644E+11 | 0.129670E+11 | 151255.88 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.268245E+09 | 0.00 | 0.00 | 6680821.95 | 0.00 | 0.799175E+09 | 0.464828E+09 | 0.00 | 0.47 |
February | 0.258269E+09 | 0.00 | 0.00 | 7013170.72 | 0.00 | 0.599025E+09 | 0.519325E+09 | 0.00 | 0.47 |
March | 0.188755E+09 | 0.00 | 0.00 | 11243151.15 | 0.00 | 0.371729E+09 | 0.908746E+09 | 0.00 | 0.47 |
April | 52702693.02 | 377939.16 | 0.00 | 17279288.41 | 6313.13 | 85344705.03 | 0.104719E+10 | 0.00 | 0.47 |
May | 33045311.44 | 3215144.95 | 0.00 | 17352257.70 | 155572.00 | 19521756.11 | 0.857731E+09 | 0.00 | 0.47 |
June | 14598787.15 | 50116680.32 | 0.00 | 13020301.58 | 593693.93 | 265830.65 | 0.445821E+09 | 0.00 | 0.47 |
July | 116936.89 | 0.293948E+09 | 13496.42 | 2949087.20 | 5436784.23 | 10143.63 | 45028739.32 | 756.12 | 0.47 |
August | 3475411.21 | 0.179460E+09 | 26107.75 | 6376737.05 | 2942903.59 | 0.00 | 0.134177E+09 | 293.81 | 0.47 |
September | 18058890.27 | 35539303.18 | 8272.20 | 15167785.27 | 938423.28 | 210881.32 | 0.541863E+09 | 1827.11 | 0.47 |
October | 91439246.42 | 2984716.86 | 0.00 | 16460696.92 | 282573.85 | 0.126870E+09 | 0.972554E+09 | 0.00 | 0.47 |
November | 0.184987E+09 | 0.00 | 0.00 | 11648754.63 | 0.00 | 0.449168E+09 | 0.877484E+09 | 0.00 | 0.47 |
December | 0.323205E+09 | 0.00 | 0.00 | 5360757.80 | 0.00 | 0.813711E+09 | 0.404829E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.143690E+10 | 0.565642E+09 | 47876.37 | 0.130553E+09 | 10356264.02 | 0.326503E+10 | 0.721958E+10 | 2877.03 | 0.47 |
Minimum of Months | 116936.89 | 0.00 | 0.00 | 2949087.20 | 0.00 | 0.00 | 45028739.32 | 0.00 | 0.47 |
Maximum of Months | 0.323205E+09 | 0.293948E+09 | 26107.75 | 17352257.70 | 5436784.23 | 0.813711E+09 | 0.104719E+10 | 1827.11 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.404598E+09 | 0.00 | 0.00 | 1531073.09 | 0.00 | 0.102451E+10 | 0.108110E+09 | 0.00 | 0.47 |
February | 0.398399E+09 | 0.00 | 0.00 | 2186333.44 | 0.00 | 0.776241E+09 | 0.206644E+09 | 0.00 | 0.47 |
March | 0.341021E+09 | 0.00 | 0.00 | 6311728.10 | 0.00 | 0.506072E+09 | 0.626895E+09 | 0.00 | 0.47 |
April | 88110622.56 | 376807.55 | 0.00 | 14310460.93 | 7399.72 | 0.116654E+09 | 0.983304E+09 | 0.00 | 0.47 |
May | 36681126.62 | 3202802.83 | 0.00 | 16459187.40 | 167519.19 | 24883239.25 | 0.849518E+09 | 0.00 | 0.47 |
June | 14614745.29 | 50104122.28 | 0.00 | 13101738.83 | 600310.52 | 255352.86 | 0.445678E+09 | 0.00 | 0.47 |
July | 116923.19 | 0.293739E+09 | 13427.88 | 2947563.27 | 5610229.16 | 10142.44 | 45024641.95 | 822.98 | 0.47 |
August | 3826848.71 | 0.178821E+09 | 33764.65 | 6135910.00 | 3551810.46 | 176.27 | 0.134049E+09 | 957.98 | 0.47 |
September | 22086143.55 | 35162516.40 | 13011.35 | 12564995.34 | 1303772.09 | 233086.33 | 0.540349E+09 | 4250.84 | 0.47 |
October | 0.186075E+09 | 2807952.49 | 0.00 | 9918828.59 | 458432.82 | 0.205089E+09 | 0.806100E+09 | 522.58 | 0.47 |
November | 0.436606E+09 | 0.00 | 0.00 | 3882852.64 | 0.00 | 0.701294E+09 | 0.381326E+09 | 0.00 | 0.47 |
December | 0.419557E+09 | 0.00 | 0.00 | 874073.09 | 0.00 | 0.102808E+10 | 98415661.15 | 0.00 | 0.47 |
Annual Sum or Average | 0.235169E+10 | 0.564215E+09 | 60203.88 | 90224744.70 | 11699473.98 | 0.438332E+10 | 0.522541E+10 | 6554.39 | 0.47 |
Minimum of Months | 116923.19 | 0.00 | 0.00 | 874073.09 | 0.00 | 176.27 | 45024641.95 | 0.00 | 0.47 |
Maximum of Months | 0.436606E+09 | 0.293739E+09 | 33764.65 | 16459187.40 | 5610229.16 | 0.102808E+10 | 0.983304E+09 | 4250.84 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.232903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
February | 0.210145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
March | 0.228214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
April | 0.163779E+11 | 0.00 | 0.00 | 4251596.16 | 10318.79 | 0.00 | 0.291236E+10 | 0.00 | 0.50 |
May | 0.947470E+10 | 797303.39 | 0.00 | 12329930.64 | 12443.56 | 0.00 | 0.665439E+10 | 0.00 | 0.52 |
June | 0.238478E+10 | 0.276989E+09 | 0.00 | 26997335.46 | 239966.26 | 0.00 | 0.810785E+10 | 0.00 | 0.56 |
July | 5848796.33 | 0.517790E+09 | 0.00 | 33421848.40 | 255537.95 | 0.00 | 0.660294E+10 | 0.00 | 0.59 |
August | 0.111099E+09 | 0.188866E+09 | 0.00 | 40914003.94 | 0.00 | 0.00 | 0.873048E+10 | 0.00 | 0.60 |
September | 0.139339E+10 | 23586828.51 | 0.00 | 34866545.70 | 0.00 | 0.00 | 0.123071E+11 | 0.00 | 0.60 |
October | 0.117476E+11 | 0.00 | 0.00 | 17032055.84 | 0.00 | 0.00 | 0.846570E+10 | 0.00 | 0.52 |
November | 0.233204E+11 | 0.00 | 0.00 | 3132.30 | 0.00 | 0.00 | 20508782.87 | 0.00 | 0.44 |
December | 0.235839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 0.155526E+12 | 0.100803E+10 | 0.00 | 0.169816E+09 | 518266.57 | 0.00 | 0.538013E+11 | 0.00 | 0.51 |
Minimum of Months | 5848796.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.235839E+11 | 0.517790E+09 | 0.00 | 40914003.94 | 255537.95 | 0.00 | 0.123071E+11 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 72973525.48 | 0.00 | 0.00 | 1077540.72 | 0.00 | 0.233555E+09 | 77126085.14 | 0.00 | 0.47 |
February | 65539526.31 | 0.00 | 0.00 | 1502704.70 | 0.00 | 0.181582E+09 | 97283687.27 | 0.00 | 0.47 |
March | 68811102.75 | 0.00 | 0.00 | 1946678.29 | 0.00 | 0.154645E+09 | 0.144716E+09 | 0.00 | 0.47 |
April | 42424473.22 | 95383.78 | 0.00 | 2885576.52 | 679.29 | 55560394.15 | 0.199760E+09 | 0.00 | 0.47 |
May | 30647460.73 | 786992.06 | 996.14 | 3092388.60 | 54547.81 | 23230981.83 | 0.174942E+09 | 143.22 | 0.47 |
June | 9681877.29 | 12370760.74 | 428.77 | 2381085.27 | 306123.71 | 4298794.15 | 0.102065E+09 | 280.35 | 0.47 |
July | 147388.29 | 71443844.96 | 27675.68 | 617835.35 | 3375726.85 | 1485.12 | 11259518.00 | 2499.86 | 0.47 |
August | 2562029.21 | 43807246.55 | 12702.04 | 1139519.09 | 1786262.49 | 45139.00 | 32260624.11 | 1096.71 | 0.47 |
September | 11537704.24 | 8673493.81 | 0.00 | 2994566.02 | 448462.64 | 749796.50 | 0.128543E+09 | 0.00 | 0.47 |
October | 38310418.75 | 730251.72 | 0.00 | 3154562.67 | 86570.95 | 66894863.96 | 0.193471E+09 | 0.00 | 0.47 |
November | 64407520.02 | 0.00 | 0.00 | 1682957.93 | 0.00 | 0.163382E+09 | 0.151350E+09 | 0.00 | 0.47 |
December | 71539670.44 | 0.00 | 0.00 | 1200625.65 | 0.00 | 0.239212E+09 | 74823867.33 | 0.00 | 0.47 |
Annual Sum or Average | 0.478583E+09 | 0.137908E+09 | 41802.62 | 23676040.82 | 6058373.75 | 0.112316E+10 | 0.138760E+10 | 4020.14 | 0.47 |
Minimum of Months | 147388.29 | 0.00 | 0.00 | 617835.35 | 0.00 | 1485.12 | 11259518.00 | 0.00 | 0.47 |
Maximum of Months | 72973525.48 | 71443844.96 | 27675.68 | 3154562.67 | 3375726.85 | 0.239212E+09 | 0.199760E+09 | 2499.86 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 91118001.91 | 0.00 | 0.00 | 285177.99 | 0.00 | 0.275876E+09 | 17408002.36 | 0.00 | 0.47 |
February | 84102358.75 | 0.00 | 0.00 | 528925.91 | 0.00 | 0.226384E+09 | 34852591.85 | 0.00 | 0.47 |
March | 92973317.76 | 0.00 | 0.00 | 1093339.53 | 0.00 | 0.198838E+09 | 77170206.79 | 0.00 | 0.47 |
April | 57388859.37 | 95372.61 | 0.00 | 2291833.36 | 679.21 | 70285260.68 | 0.170629E+09 | 0.00 | 0.47 |
May | 34732444.89 | 780634.84 | 932.98 | 2887614.89 | 60806.43 | 24676076.80 | 0.169589E+09 | 206.25 | 0.47 |
June | 9909139.15 | 12348239.06 | 0.00 | 2398725.56 | 327650.56 | 4002601.86 | 0.102102E+09 | 218.57 | 0.47 |
July | 145402.41 | 71192774.79 | 25222.94 | 617259.57 | 3620038.53 | 1484.95 | 11260670.78 | 2941.35 | 0.47 |
August | 2579611.52 | 43220645.54 | 15082.52 | 1080964.18 | 2364964.64 | 45133.71 | 32297383.21 | 1271.52 | 0.47 |
September | 12460601.68 | 8327333.15 | 0.00 | 2428998.87 | 793554.52 | 939365.58 | 0.127979E+09 | 0.00 | 0.47 |
October | 61075929.74 | 619632.10 | 129.32 | 1852520.23 | 196964.23 | 0.105563E+09 | 0.133304E+09 | 1.33 | 0.47 |
November | 0.103048E+09 | 0.00 | 0.00 | 487024.93 | 0.00 | 0.233536E+09 | 43706658.01 | 0.00 | 0.47 |
December | 82766055.57 | 0.00 | 0.00 | 192227.40 | 0.00 | 0.291809E+09 | 11963804.31 | 0.00 | 0.47 |
Annual Sum or Average | 0.632300E+09 | 0.136585E+09 | 41367.76 | 16144612.41 | 7364658.12 | 0.143196E+10 | 0.932263E+09 | 4639.02 | 0.47 |
Minimum of Months | 145402.41 | 0.00 | 0.00 | 192227.40 | 0.00 | 1484.95 | 11260670.78 | 0.00 | 0.47 |
Maximum of Months | 0.103048E+09 | 71192774.79 | 25222.94 | 2887614.89 | 3620038.53 | 0.291809E+09 | 0.170629E+09 | 2941.35 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.288615E+09 | 0.00 | 0.00 | 27527653.26 | 0.00 | 0.877332E+09 | 0.127823E+10 | 0.00 | 0.53 |
February | 0.223706E+09 | 0.00 | 0.00 | 25295443.09 | 0.00 | 0.652802E+09 | 0.132048E+10 | 0.00 | 0.53 |
March | 0.299838E+09 | 0.00 | 0.00 | 18236835.30 | 0.00 | 0.461442E+09 | 0.159831E+10 | 0.00 | 0.54 |
April | 0.224687E+09 | 607811.71 | 0.00 | 16216484.52 | 9344.48 | 0.179978E+09 | 0.151051E+10 | 0.00 | 0.54 |
May | 0.185293E+09 | 4981989.23 | 0.00 | 14584429.13 | 431713.81 | 79049538.91 | 0.121099E+10 | 80.75 | 0.54 |
June | 62430590.56 | 78068037.24 | 32188.12 | 10974063.98 | 3323888.46 | 7023503.62 | 0.680401E+09 | 22950.92 | 0.54 |
July | 1131617.20 | 0.454510E+09 | 272117.68 | 3178955.07 | 26005049.06 | 25833.05 | 72925960.34 | 84106.58 | 0.54 |
August | 16461177.05 | 0.281334E+09 | 104151.69 | 6375262.69 | 11522790.21 | 165175.90 | 0.208327E+09 | 42416.29 | 0.54 |
September | 70781688.04 | 56530936.81 | 0.00 | 19621209.72 | 2072975.14 | 730242.46 | 0.832870E+09 | 0.00 | 0.54 |
October | 0.162964E+09 | 4929038.38 | 0.00 | 28995340.18 | 318630.19 | 0.132757E+09 | 0.161439E+10 | 0.00 | 0.54 |
November | 0.214069E+09 | 0.00 | 0.00 | 32443774.20 | 0.00 | 0.395991E+09 | 0.180408E+10 | 0.00 | 0.53 |
December | 0.272964E+09 | 0.00 | 0.00 | 34852930.69 | 0.00 | 0.864989E+09 | 0.131204E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.202294E+10 | 0.880962E+09 | 408457.49 | 0.238302E+09 | 43684391.35 | 0.365229E+10 | 0.134436E+11 | 149554.53 | 0.54 |
Minimum of Months | 1131617.20 | 0.00 | 0.00 | 3178955.07 | 0.00 | 25833.05 | 72925960.34 | 0.00 | 0.53 |
Maximum of Months | 0.299838E+09 | 0.454510E+09 | 272117.68 | 34852930.69 | 26005049.06 | 0.877332E+09 | 0.180408E+10 | 84106.58 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.196112E+11 | 0.00 | 0.00 | 36006827.42 | 0.00 | 0.00 | 0.391039E+11 | 0.00 | 5.19 |
February | 0.137469E+11 | 0.00 | 0.00 | 40174959.93 | 0.00 | 0.00 | 0.395044E+11 | 0.00 | 5.31 |
March | 0.723111E+10 | 0.00 | 0.00 | 55872299.25 | 0.00 | 0.00 | 0.510523E+11 | 0.00 | 5.61 |
April | 0.356010E+10 | 25814.45 | 0.00 | 64430847.34 | 0.00 | 0.00 | 0.463833E+11 | 0.00 | 6.03 |
May | 0.123468E+10 | 1981348.15 | 0.00 | 67230912.65 | 0.00 | 0.00 | 0.404766E+11 | 0.00 | 6.21 |
June | 0.226050E+09 | 0.520194E+09 | 0.00 | 65805055.47 | 2863080.22 | 0.00 | 0.261325E+11 | 0.00 | 6.06 |
July | 36873663.73 | 0.101055E+10 | 0.00 | 62809263.71 | 7668307.33 | 0.00 | 0.156630E+11 | 0.00 | 5.99 |
August | 0.172947E+09 | 0.348744E+09 | 0.00 | 70970309.43 | 9972714.63 | 0.00 | 0.206742E+11 | 0.00 | 6.10 |
September | 0.441361E+09 | 44068245.71 | 0.00 | 62604262.92 | 282583.36 | 0.00 | 0.323995E+11 | 0.00 | 6.30 |
October | 0.510348E+10 | 0.00 | 0.00 | 56401437.88 | 0.00 | 0.00 | 0.451731E+11 | 0.00 | 5.90 |
November | 0.140992E+11 | 0.00 | 0.00 | 48195367.87 | 0.00 | 0.00 | 0.451568E+11 | 0.00 | 5.21 |
December | 0.226075E+11 | 0.00 | 0.00 | 34335456.12 | 0.00 | 0.00 | 0.367140E+11 | 0.00 | 5.06 |
Annual Sum or Average | 0.880713E+11 | 0.192556E+10 | 0.00 | 0.664837E+09 | 20786685.54 | 0.00 | 0.438434E+12 | 0.00 | 5.75 |
Minimum of Months | 36873663.73 | 0.00 | 0.00 | 34335456.12 | 0.00 | 0.00 | 0.156630E+11 | 0.00 | 5.06 |
Maximum of Months | 0.226075E+11 | 0.101055E+10 | 0.00 | 70970309.43 | 9972714.63 | 0.00 | 0.510523E+11 | 0.00 | 6.30 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114342E+11 | 0.00 | 0.00 | 56238677.25 | 0.00 | 0.00 | 0.478615E+11 | 0.00 | 5.24 |
February | 0.741503E+10 | 0.00 | 0.00 | 60095595.47 | 0.00 | 0.00 | 0.464869E+11 | 0.00 | 5.37 |
March | 0.340473E+10 | 0.00 | 0.00 | 78250853.88 | 0.00 | 0.00 | 0.559634E+11 | 0.00 | 5.70 |
April | 0.156467E+10 | 25796.11 | 0.00 | 84307405.04 | 0.00 | 0.00 | 0.498445E+11 | 0.00 | 6.19 |
May | 0.595426E+09 | 1979940.96 | 0.00 | 83266328.41 | 0.00 | 0.00 | 0.426254E+11 | 0.00 | 6.40 |
June | 82915900.28 | 0.532508E+09 | 0.00 | 77060519.66 | 1990657.64 | 0.00 | 0.274312E+11 | 0.00 | 6.28 |
July | 3974796.55 | 0.102848E+10 | 0.00 | 71746061.73 | 4843148.15 | 0.00 | 0.164255E+11 | 0.00 | 6.21 |
August | 56047433.82 | 0.356052E+09 | 0.00 | 83361057.59 | 4449485.02 | 0.00 | 0.217105E+11 | 0.00 | 6.32 |
September | 0.193051E+09 | 44319330.37 | 0.00 | 76404284.73 | 0.00 | 0.00 | 0.339799E+11 | 0.00 | 6.50 |
October | 0.239974E+10 | 0.00 | 0.00 | 74043100.38 | 0.00 | 0.00 | 0.491746E+11 | 0.00 | 6.03 |
November | 0.707120E+10 | 0.00 | 0.00 | 68739796.78 | 0.00 | 0.00 | 0.530846E+11 | 0.00 | 5.28 |
December | 0.149765E+11 | 0.00 | 0.00 | 56337399.66 | 0.00 | 0.00 | 0.449446E+11 | 0.00 | 5.11 |
Annual Sum or Average | 0.491976E+11 | 0.196337E+10 | 0.00 | 0.869851E+09 | 11283290.81 | 0.00 | 0.489533E+12 | 0.00 | 5.89 |
Minimum of Months | 3974796.55 | 0.00 | 0.00 | 56238677.25 | 0.00 | 0.00 | 0.164255E+11 | 0.00 | 5.11 |
Maximum of Months | 0.149765E+11 | 0.102848E+10 | 0.00 | 84307405.04 | 4843148.15 | 0.00 | 0.559634E+11 | 0.00 | 6.50 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.203503E+09 | 0.00 | 0.00 | 0.682766E+11 | 0.00 | 19.30 |
February | 918613.42 | 0.00 | 0.00 | 0.182756E+09 | 0.00 | 0.00 | 0.624854E+11 | 0.00 | 20.03 |
March | 0.00 | 0.00 | 0.00 | 0.170930E+09 | 0.00 | 0.00 | 0.692509E+11 | 0.00 | 22.09 |
April | 4904116.99 | 38575.85 | 0.00 | 0.157358E+09 | 0.00 | 0.00 | 0.577362E+11 | 0.00 | 24.11 |
May | 932871.24 | 3051326.25 | 0.00 | 0.136123E+09 | 0.00 | 0.00 | 0.465667E+11 | 0.00 | 24.59 |
June | 0.00 | 0.797851E+09 | 0.00 | 0.109908E+09 | 0.00 | 0.00 | 0.270156E+11 | 0.00 | 23.51 |
July | 0.00 | 0.153943E+10 | 0.00 | 93708448.84 | 0.00 | 0.00 | 0.147659E+11 | 0.00 | 23.02 |
August | 0.00 | 0.552217E+09 | 0.00 | 0.120943E+09 | 0.00 | 0.00 | 0.210099E+11 | 0.00 | 23.56 |
September | 0.00 | 62842745.78 | 0.00 | 0.127128E+09 | 0.00 | 0.00 | 0.354836E+11 | 0.00 | 24.72 |
October | 4999132.23 | 0.00 | 0.00 | 0.162075E+09 | 0.00 | 0.00 | 0.583239E+11 | 0.00 | 23.23 |
November | 2834924.04 | 0.00 | 0.00 | 0.190922E+09 | 0.00 | 0.00 | 0.699497E+11 | 0.00 | 19.94 |
December | 740456.67 | 0.00 | 0.00 | 0.231177E+09 | 0.00 | 0.00 | 0.690283E+11 | 0.00 | 18.79 |
Annual Sum or Average | 15330114.58 | 0.295543E+10 | 0.00 | 0.188653E+10 | 0.00 | 0.00 | 0.599893E+12 | 0.00 | 22.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 93708448.84 | 0.00 | 0.00 | 0.147659E+11 | 0.00 | 18.79 |
Maximum of Months | 4999132.23 | 0.153943E+10 | 0.00 | 0.231177E+09 | 0.00 | 0.00 | 0.699497E+11 | 0.00 | 24.72 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.884439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414741E+09 | 0.00 | 0.00 | 0.66 |
February | 0.813236E+10 | 0.00 | 0.00 | 320464.42 | 0.00 | 72332294.23 | 0.158979E+09 | 0.00 | 0.67 |
March | 0.822198E+10 | 0.00 | 0.00 | 1193145.02 | 0.00 | 0.00 | 0.891134E+09 | 0.00 | 0.71 |
April | 0.469147E+10 | 5777.87 | 0.00 | 7464812.14 | 0.00 | 0.00 | 0.327172E+10 | 0.00 | 0.83 |
May | 0.263889E+10 | 485380.61 | 0.00 | 13353774.83 | 0.00 | 0.00 | 0.424333E+10 | 0.00 | 0.94 |
June | 0.475999E+09 | 0.193112E+09 | 0.00 | 17438757.21 | 0.00 | 0.00 | 0.409963E+10 | 0.00 | 1.09 |
July | 0.00 | 0.348289E+09 | 0.00 | 17861620.61 | 0.00 | 0.00 | 0.301657E+10 | 0.00 | 1.20 |
August | 11919542.07 | 0.130339E+09 | 0.00 | 23039174.07 | 0.00 | 0.00 | 0.399884E+10 | 0.00 | 1.20 |
September | 0.522395E+09 | 16170530.94 | 0.00 | 19903804.65 | 0.00 | 0.00 | 0.540372E+10 | 0.00 | 1.10 |
October | 0.436304E+10 | 0.00 | 0.00 | 10554049.98 | 0.00 | 0.00 | 0.402227E+10 | 0.00 | 0.87 |
November | 0.871252E+10 | 0.00 | 0.00 | 466896.34 | 0.00 | 0.00 | 0.579157E+09 | 0.00 | 0.66 |
December | 0.913855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237313E+09 | 0.00 | 0.00 | 0.64 |
Annual Sum or Average | 0.557535E+11 | 0.688401E+09 | 0.00 | 0.111596E+09 | 0.00 | 0.724386E+09 | 0.296854E+11 | 0.00 | 0.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
Maximum of Months | 0.913855E+10 | 0.348289E+09 | 0.00 | 23039174.07 | 0.00 | 0.414741E+09 | 0.540372E+10 | 0.00 | 1.20 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:59:47
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.257045E+12 | 0.166066E+11 | 0.189824E+12 | 0.871627E+12 | 0.108407E+12 |
February | 0.326434E+12 | 0.138626E+11 | 0.156955E+12 | 0.737265E+12 | 0.108236E+12 |
March | 0.450211E+12 | 0.120922E+11 | 0.132211E+12 | 0.662940E+12 | 0.138426E+12 |
April | 0.564361E+12 | 0.825861E+10 | 0.889486E+11 | 0.473477E+12 | 0.282751E+12 |
May | 0.610082E+12 | 0.601781E+10 | 0.639772E+11 | 0.361274E+12 | 0.434352E+12 |
June | 0.570019E+12 | 0.287212E+10 | 0.275601E+11 | 0.191930E+12 | 0.704905E+12 |
July | 0.572457E+12 | 0.428058E+09 | 0.925313E+10 | 0.709567E+11 | 0.947107E+12 |
August | 0.545846E+12 | 0.157048E+10 | 0.228932E+11 | 0.139763E+12 | 0.866644E+12 |
September | 0.435210E+12 | 0.402253E+10 | 0.437758E+11 | 0.275869E+12 | 0.606414E+12 |
October | 0.347245E+12 | 0.867306E+10 | 0.957664E+11 | 0.508332E+12 | 0.338967E+12 |
November | 0.275006E+12 | 0.128484E+11 | 0.148408E+12 | 0.692648E+12 | 0.128640E+12 |
December | 0.233429E+12 | 0.169646E+11 | 0.197385E+12 | 0.886077E+12 | 0.115789E+12 |
Annual Sum or Average | 0.518734E+13 | 0.104217E+12 | 0.117696E+13 | 0.587216E+13 | 0.478064E+13 |
Minimum of Months | 0.233429E+12 | 0.428058E+09 | 0.925313E+10 | 0.709567E+11 | 0.108236E+12 |
Maximum of Months | 0.610082E+12 | 0.169646E+11 | 0.197385E+12 | 0.886077E+12 | 0.947107E+12 |