Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2023-10-16 08:59:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 11277.47 | 994.02 | 994.02 |
Net Site Energy | 11277.47 | 994.02 | 994.02 |
Total Source Energy | 25003.94 | 2203.91 | 2203.91 |
Net Source Energy | 25003.94 | 2203.91 | 2203.91 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 447.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1642.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 767.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 242.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1745.01 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 651.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 584.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 142.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 206.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.75 | 2906.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 62.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 6134.98 | 5142.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 447.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1642.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 767.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 242.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 32.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 584.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 142.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 206.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 2906.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 447.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1642.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 767.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 242.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1745.01 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 651.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 584.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 142.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 206.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.75 | 2906.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 62.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 89.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 216.85 | 295.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 234.88 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 540.75 | 453.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 89.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 216.85 | 295.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 234.88 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 540.75 | 453.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 6134.982 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 6134.982 | 100.00 |
Total On-Site and Utility Electric Sources | 6134.982 | 100.00 |
Total Electricity End Uses | 6134.982 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 903.87 | 36.59 |
Air to Air Heat Recovery for Heating | 1566.19 | 63.41 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2470.06 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1.17 |
Time Setpoint Not Met During Occupied Cooling | 179.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8142.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 9.1389 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.3365 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.3365 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 9.2031 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 6.1031 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.8125 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.3656 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 8.7188 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.5531 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.5531 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 6.3938 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.5531 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.3656 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.3656 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7219 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 6.3938 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 6.8557 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 6.8557 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.1389 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.3365 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.3365 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 9.2031 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 6.1031 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.8125 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.3656 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 8.7188 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.5531 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.5531 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 6.3938 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.5531 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.5531 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.5531 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.3656 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.3656 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7219 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 6.3938 | 18.58 | 0.0000 | |
Total | 11345.29 | 6.8557 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 6.8557 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.4542 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 18-AUG-19:19 | 07-JAN-17:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-21:10 |
Heating | 0.00 | 187250.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 182872.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 88772.42 | 89612.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 32158.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 37611.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6653.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3989.38 | 245501.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1872.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 442211.49 | 522364.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 187250.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 182872.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58789.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 14636.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1855.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 37611.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 6653.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3989.38 | 245501.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 536.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1095.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 484.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5200.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2429.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 769.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5526.46 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2063.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1851.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 452.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 652.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.39 | 3150.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 197.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 19429.49 | 5574.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 42.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 458.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 67.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.11 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 163.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 39.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 57.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 277.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1712.56 | 491.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 42.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 458.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 214.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 67.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.11 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 163.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 39.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 57.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 277.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1712.56 | 491.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.56 | 0.589405 | 0.529000 | 1.35 | 1.00 | 0.500000 | 0.000646 | 0.000071 | 1.35 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.327311 | 0.156146 | 0.529000 | 0.173147 | 0.529000 | 0.500000 | 0.002440 | 0.000033 | 0.173147 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.249515 | 0.237195 | 0.529000 | 0.131993 | 0.632521 | 0.500000 | 0.001606 | 0.000015 | 0.131993 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.250098 | 0.500416 | 0.529000 | 0.132302 | 1.00 | 0.500000 | 0.000761 | 0.000022 | 0.132302 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.121289 | 0.595328 | 0.529000 | 0.064162 | 1.00 | 0.500000 | 0.000640 | 0.000013 | 0.064162 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.39 | 0.069610 | 0.529000 | 1.79 | 0.529000 | 0.500000 | 0.021719 | 0.000101 | 1.79 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.40 | 0.102938 | 0.529000 | 0.739567 | 0.529000 | 0.500000 | 0.003701 | 0.000098 | 0.739567 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.66 | 0.213819 | 0.529000 | 2.47 | 0.570183 | 0.500000 | 0.001782 | 0.000264 | 2.47 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.43 | 0.829881 | 0.529000 | 0.756582 | 1.00 | 0.500000 | 0.000459 | 0.000125 | 0.756582 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.24 | 0.112696 | 0.529000 | 1.19 | 0.529000 | 0.500000 | 0.003381 | 0.000110 | 1.19 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.35 | 0.107524 | 0.529000 | 1.24 | 0.529000 | 0.500000 | 0.003543 | 0.000114 | 1.24 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.31 | 0.061236 | 0.529000 | 1.22 | 0.529000 | 0.500000 | 0.011191 | 0.000075 | 1.22 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.748068 | 0.419800 | 0.529000 | 0.395728 | 1.00 | 0.500000 | 0.000908 | 0.000077 | 0.395728 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 8107.59 | 0.000071 | 170.63 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3821.33 | 0.000033 | 96.78 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1675.19 | 0.000015 | 37.89 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2541.28 | 0.000022 | 62.07 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1435.83 | 0.000013 | 36.51 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11555.24 | 0.000101 | 244.33 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 11149.29 | 0.000098 | 259.15 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 30230.88 | 0.000264 | 680.43 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 6543.14 | 0.000057 | 186.98 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 6555.57 | 0.000057 | 187.33 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 37521.80 | 0.000328 | 1072.22 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 37770.48 | 0.000330 | 1079.32 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 6517.57 | 0.000057 | 186.25 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 6530.00 | 0.000057 | 186.60 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14322.52 | 0.000125 | 348.61 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1994.61 | 0.000017 | 57.00 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1999.59 | 0.000017 | 57.14 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 9532.03 | 0.000083 | 272.38 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 12601.99 | 0.000110 | 278.56 |
DINING_FLR_6 VAV BOX REHEAT COIL | 13033.67 | 0.000114 | 287.66 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8590.10 | 0.000075 | 182.73 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8845.55 | 0.000077 | 224.84 |
VAV WITH REHEAT HEATING COIL | 176420.31 | 0.001543 | 2977.62 |
FLR_3_DOAS HEATING COIL | 16512.40 | 0.000144 | 278.70 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 0.983040 | 0.000057 | 0.000391 |
ROOM_2_FLR_3 FAN COIL | 0.971194 | 0.000057 | 0.000387 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.51 | 0.000328 | 0.002147 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.87 | 0.000330 | 0.002431 |
ROOM_5_FLR_3 FAN COIL | 0.881139 | 0.000057 | 0.000353 |
ROOM_6_FLR_3 FAN COIL | 0.873060 | 0.000057 | 0.000350 |
ROOM_1_FLR_6 FAN COIL | 0.258531 | 0.000017 | 0.000103 |
ROOM_2_FLR_6 FAN COIL | 0.255081 | 0.000017 | 0.000101 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.15 | 0.000083 | 0.000466 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 0.983040 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 0.971194 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.51 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.87 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.881139 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.873060 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.258531 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.255081 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.15 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008703 | 12.80 | 0.008500 | 0.000391 | 0.983040 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008705 | 12.80 | 0.008500 | 0.000387 | 0.971194 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008619 | 12.80 | 0.008500 | 0.002147 | 5.51 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008857 | 12.80 | 0.008500 | 0.002431 | 5.87 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008726 | 12.80 | 0.008500 | 0.000353 | 0.881139 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008729 | 12.80 | 0.008500 | 0.000350 | 0.873060 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008693 | 12.80 | 0.008500 | 0.000103 | 0.258531 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008695 | 12.80 | 0.008500 | 0.000101 | 0.255081 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008771 | 12.80 | 0.008500 | 0.000466 | 1.15 | |
VAV WITH REHEAT COOLING COIL | 29.53 | 6.70 | 0.012250 | 10.92 | 0.008500 | 0.025970 | 21.92 | 727095.27 |
FLR_3_DOAS COOLING COIL | 34.40 | 6.70 | 0.014473 | 11.91 | 0.008500 | 0.003256 | 2.05 | 91161.11 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.66 | 11.66 | 22.04 | 11.66 | 21.92 | 21.92 | 0.300000 | 0.531978 | 21.92 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 21.92 | 11.66 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 21.92 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.025970 | 0.000018 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001543 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.003256 | 0.000146 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000144 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.035956 | 7409.20 | |
HEATSYS1 PUMP | 0.003813 | 1148.20 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003813 | 0.457517 |
COOLSYS1 | 0.035956 | 4.31 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 435807.96 | 435807.96 | 0.003813 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.035956 | 5129.64 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.035956 | 1006672.42 | 1007279.73 | 114.83 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 9.139 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.519 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.336 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.096 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.336 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.096 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 9.203 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.583 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 6.103 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.793 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.813 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.343 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.366 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.746 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 8.719 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.789 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.366 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 78.186 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.366 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 78.186 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.722 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2946.209 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 18084.325 | 9.139 | 169.807 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18084.325 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 894.495 | 13.336 | 82.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 894.495 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1035.829 | 13.336 | 82.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1035.829 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 1511.551 | 9.203 | 569.967 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1511.551 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 578.329 | 6.103 | 283.494 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 578.329 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 453.605 | 5.813 | 54.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 453.605 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1957.673 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1957.673 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11405.759 | 8.719 | 27.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11405.759 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 111.660 | 4.553 | 74.440 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.660 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 111.691 | 4.553 | 74.460 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.691 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2489.757 | 6.394 | 118.803 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.757 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 111.691 | 4.553 | 74.460 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.691 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3437.839 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3437.839 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3437.839 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3437.839 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1210.923 | 11.722 | 54.453 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1210.923 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2635.024 | 6.394 | 118.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2635.024 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 1.067 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.370 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.442 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.217 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.286 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7702 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5624 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5260 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6546 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6103 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.55514967E-15 | 0.35055860E-16 | -0.14326465E-09 | 0.28783368E-17 |
29 | 8 | 0.20966873E-07 | 0.14258959E-12 | 0.36819155E-03 | -0.23840058E-09 |
30 | 7 | -0.11954852E-01 | 0.74774803E-08 | -0.22672946E-01 | 0.13593102E-03 |
31 | 6 | 0.39755982 | 0.26159305E-05 | 0.46545104 | -0.46559307E-02 |
32 | 5 | -5.1145337 | 0.98147117E-04 | -4.3902405 | 0.62241115E-01 |
33 | 4 | 32.666535 | 0.80637729E-03 | 21.240866 | -0.41765750 |
34 | 3 | -110.51061 | 0.17642800E-02 | -55.229641 | 1.5048560 |
35 | 2 | 196.42192 | 0.99585215E-03 | 77.513220 | -2.8894543 |
36 | 1 | -170.90254 | 0.10665179E-03 | -55.149704 | 2.7409959 |
37 | 0 | 57.057407 | 0.60929387E-06 | 15.576129 | |
38 | 9 | 0.10314710E-14 | 0.47183642E-16 | -0.12881513E-09 | -0.40099708E-17 |
39 | 8 | 0.18927665E-07 | 0.17950474E-12 | 0.34608657E-03 | -0.21521408E-09 |
40 | 7 | -0.11292911E-01 | 0.96443222E-08 | -0.21719088E-01 | 0.12840450E-03 |
41 | 6 | 0.37957032 | 0.34070209E-05 | 0.45007157 | -0.44438791E-02 |
42 | 5 | -4.9389364 | 0.12890179E-03 | -4.2718596 | 0.60063826E-01 |
43 | 4 | 31.889569 | 0.10670331E-02 | 20.777560 | -0.40734193 |
44 | 3 | -108.85680 | 0.23501275E-02 | -54.313423 | 1.4809641 |
45 | 2 | 194.78196 | 0.13343675E-02 | 76.673975 | -2.8634131 |
46 | 1 | -170.29645 | 0.14368413E-03 | -54.907648 | 2.7303734 |
47 | 0 | 57.057407 | 0.82565881E-06 | 15.617726 | |
48 | 9 | 0.86975537E-15 | 0.52023775E-16 | -0.12536948E-09 | -0.54620444E-17 |
49 | 8 | 0.18440443E-07 | 0.18784465E-12 | 0.34068694E-03 | -0.20967419E-09 |
50 | 7 | -0.11130813E-01 | 0.10155400E-07 | -0.21485363E-01 | 0.12656138E-03 |
51 | 6 | 0.37516444 | 0.35965268E-05 | 0.44629465 | -0.43919449E-02 |
52 | 5 | -4.8959230 | 0.13636263E-03 | -4.2427425 | 0.59530495E-01 |
53 | 4 | 31.699203 | 0.11309484E-02 | 20.663505 | -0.40481456 |
54 | 3 | -108.45147 | 0.24950915E-02 | -54.087828 | 1.4751087 |
55 | 2 | 194.37988 | 0.14187814E-02 | 76.467519 | -2.8570287 |
56 | 1 | -170.14779 | 0.15298304E-03 | -54.848449 | 2.7277680 |
57 | 0 | 57.057407 | 0.88039223E-06 | 15.628184 | |
58 | 9 | 0.12430042E-14 | 0.43603463E-16 | -0.13615479E-09 | -0.52742981E-17 |
59 | 8 | 0.19963588E-07 | 0.16114398E-12 | 0.35741204E-03 | -0.22699287E-09 |
60 | 7 | -0.11632381E-01 | 0.85488282E-08 | -0.22208377E-01 | 0.13226440E-03 |
61 | 6 | 0.38879653 | 0.30047059E-05 | 0.45796739 | -0.45526330E-02 |
62 | 5 | -5.0290001 | 0.11318598E-03 | -4.3326723 | 0.61180550E-01 |
63 | 4 | 32.288109 | 0.93328928E-03 | 21.015642 | -0.41263319 |
64 | 3 | -109.70522 | 0.20484795E-02 | -54.784283 | 1.4932205 |
65 | 2 | 195.62339 | 0.11595496E-02 | 77.105128 | -2.8767741 |
66 | 1 | -170.60747 | 0.12450863E-03 | -55.031726 | 2.7358244 |
67 | 0 | 57.057407 | 0.71328115E-06 | 15.596176 | |
68 | 9 | 0.10418955E-14 | 0.45554749E-16 | -0.13285794E-09 | -0.34221686E-17 |
69 | 8 | 0.19498290E-07 | 0.16949498E-12 | 0.35235048E-03 | -0.22170227E-09 |
70 | 7 | -0.11480752E-01 | 0.90423087E-08 | -0.21989859E-01 | 0.13054032E-03 |
71 | 6 | 0.38467563 | 0.31853038E-05 | 0.45444290 | -0.45040579E-02 |
72 | 5 | -4.9887746 | 0.12022067E-03 | -4.3055366 | 0.60681782E-01 |
73 | 4 | 32.110117 | 0.99300969E-03 | 20.909427 | -0.41027004 |
74 | 3 | -109.32633 | 0.21828955E-02 | -54.574228 | 1.4877470 |
75 | 2 | 195.24766 | 0.12373115E-02 | 76.912747 | -2.8708078 |
76 | 1 | -170.46860 | 0.13302463E-03 | -54.976289 | 2.7333905 |
77 | 0 | 57.057407 | 0.76310210E-06 | 15.605744 | |
78 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
79 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
80 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
81 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
82 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
83 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
84 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
85 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
86 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
87 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
88 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
89 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
90 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
91 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
92 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
93 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4711_SHGC_0.25 | 37 | 1 | VerySmooth | 2.678 | 2.678 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.4711_SHGC_0.25 | 38 | 1 | VerySmooth | 2.678 | 2.678 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.39142E-002 | 0.16139 | 0.61472 | 0.61472 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11798 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.39142E-002 | 0.16139 | 0.61472 | 0.61472 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11798 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 8.9580E-002 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.6657E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1002 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.9606E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 6.5426E-002 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.3594E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.6511E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.7811E-003 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 9.8153E-002 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.5023E-002 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1094 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.8621E-002 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.1825E-002 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.9872E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 2.9789E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.2036E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.1008E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.1943E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.6249E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.0557E-003 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.5728E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.2866E-003 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.6108E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.2309E-003 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.1008E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.1943E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.6249E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.0557E-003 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.5728E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.2866E-003 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.6108E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.2309E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 33947.35621 | 33947.35621 | 2.55829 | 2.55829 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 28.79500 | 1.44630E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1219.23086 | 1219.23086 | 5.42040E-002 | 0.85446 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30000 | 2.29779E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4342.58337 | 4342.58337 | 0.32731 | 0.32731 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 34.40000 | 1.44733E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2940.73444 | 2940.73444 | 0.13073 | 0.13073 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3310.50688 | 3310.50688 | 0.24951 | 0.24951 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.12000 | 1.44691E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1003.89303 | 1003.89303 | 4.46299E-002 | 9.17347E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3318.95743 | 3318.95743 | 0.25010 | 0.25010 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 30.17250 | 1.44655E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1868.55565 | 1868.55565 | 8.30698E-002 | 8.30698E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1609.56077 | 1609.56077 | 0.12129 | 0.12129 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 31.88250 | 1.44687E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1109.58039 | 1109.58039 | 4.93283E-002 | 5.77652E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44981.16306 | 44981.16306 | 3.38995 | 3.38995 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 33.92500 | 1.44724E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2438.19480 | 2438.19480 | 0.10839 | 0.10839 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 18533.14351 | 18533.14351 | 1.39805 | 1.39805 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 34.40000 | 1.44733E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 7387.54034 | 7387.54034 | 0.32842 | 0.67639 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 61837.79107 | 61837.79107 | 4.66207 | 4.66207 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 17687.28117 | 17687.28117 | 0.78632 | 1.89399 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 9679.84728 | 9679.84728 | 0.98304 | 0.98304 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 6543.23700 | 6543.23700 | 0.29259 | 0.29259 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 9563.20391 | 9563.20391 | 0.97119 | 0.97119 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 6555.66790 | 6555.66790 | 0.29315 | 0.29315 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 54291.92008 | 54291.92008 | 5.51317 | 5.51317 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 37522.06846 | 37522.06846 | 1.67790 | 1.67790 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 57772.66225 | 57772.66225 | 5.86709 | 5.86709 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 34.02000 | 1.44726E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 37770.75514 | 37770.75514 | 1.68902 | 1.68902 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 8676.42305 | 8676.42305 | 0.88114 | 0.88114 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.50250 | 1.44680E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 6517.66485 | 6517.66485 | 0.29145 | 0.29145 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 8596.86750 | 8596.86750 | 0.87306 | 0.87306 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 31.26500 | 1.44675E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 6530.10424 | 6530.10424 | 0.29200 | 0.29200 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 18978.54584 | 18978.54584 | 1.43021 | 1.43021 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 34.21000 | 1.44729E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 10473.59104 | 10473.59104 | 0.46563 | 0.47476 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2545.71824 | 2545.71824 | 0.25853 | 0.25853 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1994.63476 | 1994.63476 | 8.91928E-002 | 8.91928E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2511.74385 | 2511.74385 | 0.25508 | 0.25508 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1999.61997 | 1999.61997 | 8.94157E-002 | 8.94157E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 11320.15846 | 11320.15846 | 1.14964 | 1.14964 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 9532.14416 | 9532.14416 | 0.42625 | 0.42625 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29720.28818 | 29720.28818 | 2.24252 | 2.24252 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 6566.49128 | 6566.49128 | 0.29192 | 1.18780 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -6.30000 | 2.29779E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31150.22495 | 31150.22495 | 2.35038 | 2.35038 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 6707.97021 | 6707.97021 | 0.29821 | 1.18780 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -6.30000 | 2.29779E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30599.38930 | 30599.38930 | 2.31213 | 2.31213 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.54500 | 1.44717E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2381.73589 | 2381.73589 | 0.10587 | 0.36735 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -6.30000 | 2.29779E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 9926.69499 | 9926.69499 | 0.74807 | 0.74807 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 34.40000 | 1.44733E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6832.01659 | 6832.01659 | 0.30373 | 0.30373 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | -6.30000 | 2.29779E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 427712.54 | 21.91649 | 21.91649 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 199039.82 | 7.41795 | 7.41795 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 51689.19 | 16.15229 | 2.05125 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 55039.41 | 5.14095 | 2.05125 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.55829 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.58940 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.35334 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.46415E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.09288E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.35334 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8107.59371 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.09288E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 170.63488 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.32731 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15615 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17315 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52900 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.44002E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.34307E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17315 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3821.33282 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.34307E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 96.77720 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.24951 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23720 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13199 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63252 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.60627E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.46553E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13199 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1675.18947 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.46553E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 37.88863 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.25010 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.50042 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13230 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.61366E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.22322E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13230 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2541.27534 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.22322E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 62.06681 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.12129 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.59533 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.41617E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.39983E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.25613E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.41617E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1435.83422 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25613E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 36.50942 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.38995 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.96099E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.79328 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52900 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.17194E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.01090E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.79328 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11555.24206 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.01090E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 244.33469 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.39805 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10294 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.73957 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52900 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.70124E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.75389E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.73957 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11149.29265 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.75389E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 259.14593 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.66207 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21382 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.46623 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57018 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.78188E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.64473E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.46623 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30230.87981 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.64473E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 680.42976 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.98304 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.98304 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.72422E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.91411E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70361 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.70252E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.91411E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.98304 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6543.13728 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.72422E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 186.97831 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97119 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.97119 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.73510E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.86979E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70360 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.70530E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.86979E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.97119 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6555.56800 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.73510E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 187.33345 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.51317 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.51317 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.28257E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.14696E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70439 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61927E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.14696E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.51317 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 37521.79665 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.28257E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1072.21725 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.86709 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.86709 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.30433E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.43127E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70348 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.85656E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.43127E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.86709 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 37770.48163 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.30433E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1079.32209 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.88114 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.88114 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.70185E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.53053E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70356 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.72639E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.53053E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.88114 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6517.56551 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.70185E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 186.24775 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.87306 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.87306 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.71273E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.50016E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70356 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.72857E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.50016E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.87306 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6530.00471 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.71273E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 186.60312 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.43021 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.82988 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.75658 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.59102E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.25300E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.75658 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14322.52122 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25300E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 348.60799 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.25853 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.25853 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.74497E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.02675E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70362 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.69288E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.02675E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.25853 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1994.60515 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.74497E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 56.99581 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.25508 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.25508 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.74933E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.01369E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70362 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.69527E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.01369E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.25508 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1999.59029 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.74933E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 57.13823 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.14964 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.14964 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.33904E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.66045E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70342 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.77111E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.66045E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.14964 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9532.03163 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.33904E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 272.37605 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.24252 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11270 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.18629 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52900 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.38078E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.10248E-004 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.18629 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12601.98607 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.10248E-004 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 278.56060 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.35038 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10752 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.24335 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52900 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.54339E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.14024E-004 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.24335 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13033.66758 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14024E-004 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 287.66152 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.31213 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.12355E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.22311 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52900 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11908E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.51499E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.22311 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8590.10005 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.51499E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 182.73432 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74807 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.41980 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52900 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.39573 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.07575E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.73847E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39573 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8845.54849 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.73847E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 224.84304 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.65909 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65909 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.03987 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65909 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.91649 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 21.91649 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.53198 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 21.91649 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.91649 |
338 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 11.66146 |
339 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.52833 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.92190 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.22503E-002 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 727095.26874 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.59702E-002 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 21.91649 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 176420.31041 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54340E-003 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2977.62266 |
351 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 21.91649 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.59702E-002 |
353 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.83361E-005 |
354 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.54340E-003 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
356 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
357 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 34.40000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.90668 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.44733E-002 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 91161.10877 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.25606E-003 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 16512.40431 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.44458E-004 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 278.69642 |
369 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.25606E-003 |
371 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.46247E-004 |
372 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.44458E-004 |
373 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.59560E-002 |
374 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 7409.20028 |
375 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.81264E-003 |
376 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.45752 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.81264E-003 |
378 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1148.19918 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 435807.95908 |
381 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 435807.96000 |
382 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.81264E-003 |
383 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.59560E-002 |
384 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 4.31472 |
385 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.59560E-002 |
386 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 5129.63925 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.59560E-002 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1006672.42241 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1007279.73000 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 114.82989 |
391 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
392 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
393 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
394 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
395 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 8149.24 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3837.39 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1683.14 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2552.33 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1441.85 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11614.36 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 11200.86 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 30374.97 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 7047.88 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 7061.27 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 40416.10 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 40683.93 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 7020.34 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 7033.74 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14385.04 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2148.42 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2153.78 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 10267.05 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 12663.12 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 13096.99 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8633.81 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8882.60 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 131207.19 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 12280.59 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 16689.26 | 13202.77 | 3486.49 | 0.79 | 1981.59 | 20.10 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 16495.95 | 13047.29 | 3448.66 | 0.79 | 1958.45 | 19.86 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 92266.68 | 73427.20 | 18839.48 | 0.80 | 10988.79 | 111.45 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 102208.39 | 80011.66 | 22196.72 | 0.78 | 12083.02 | 122.55 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 15019.81 | 11862.25 | 3157.56 | 0.79 | 1781.88 | 18.07 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 14887.55 | 11756.01 | 3131.54 | 0.79 | 1766.06 | 17.91 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4381.94 | 3468.88 | 913.06 | 0.79 | 520.47 | 5.28 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4325.22 | 3423.40 | 901.82 | 0.79 | 513.69 | 5.21 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 19750.05 | 15549.76 | 4200.29 | 0.79 | 2341.26 | 23.75 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 650476.42 | 420559.44 | 229916.99 | 0.65 | 79024.20 | 801.51 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 64688.92 | 41041.02 | 23647.90 | 0.63 | 7608.06 | 77.17 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.370 | 1.137 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.370 | 1.137 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.370 | 1.137 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.370 | 1.137 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 3.3409215857E-002 | 4.8533391451E-002 | Fail | Pass | 9.9372905470E-002 | 0.3497102801 | Pass | Fail |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.5219224393E-003 | 4.0688718572E-002 | Pass | Pass | 0.3519671228 | 1.0411455217 | Fail | Fail |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.5981280339E-002 | 7.6567997150E-002 | Fail | Pass | 0.1970645426 | 0.9681087039 | Fail | Fail |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.5665059294E-002 | 3.7523920616E-002 | Fail | Pass | 0.1880930475 | 0.9562345008 | Pass | Fail |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.7985958576E-003 | 2.9412670905E-002 | Pass | Pass | 0.1136772803 | 0.4020485675 | Fail | Fail |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.2119287181 | 0.3791186320 | Fail | Fail | 8.0420348899E-002 | 0.1492098448 | Pass | Fail |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.3952341861E-002 | 0.1609278897 | Fail | Pass | 0.4824940260 | 4.1188235815 | Pass | Fail |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.2232661177E-002 | 9.4220743159E-002 | Fail | Pass | 0.1181110358 | 0.4219002239 | Fail | Fail |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.8902922958E-002 | 0.2345627372 | Pass | Pass | 0.1527344507 | 0.6819259386 | Fail | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.0749371171E-002 | 0.2405801961 | Pass | Pass | 0.1522262068 | 0.6664866137 | Fail | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.2957253218E-002 | 2.7990778351E-002 | Pass | Pass | 0.1084671808 | 0.3110336575 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.7143709242E-002 | 6.0056030789E-002 | Pass | Pass | 0.3415810118 | 1.7897630973 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.7538873415E-002 | 0.2294750279 | Pass | Pass | 0.1536740637 | 0.7081983022 | Fail | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.9349990999E-002 | 0.2354318383 | Pass | Pass | 0.1530958693 | 0.6902672130 | Fail | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.4465040658E-003 | 2.9363538112E-002 | Fail | Pass | 0.1188216755 | 0.4416782423 | Fail | Fail |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.4668275676E-002 | 0.2878973750 | Pass | Pass | 0.2087902402 | 0.9113836049 | Fail | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.5036724257E-002 | 0.2900622850 | Pass | Pass | 0.2398042741 | 0.9757043920 | Fail | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.0412775737E-002 | 0.1802106429 | Pass | Pass | 0.1019496530 | 0.3417413505 | Fail | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.3881958693E-002 | 0.1627548262 | Fail | Fail | 8.7298772826E-002 | 0.1926103683 | Pass | Fail |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.6004384892E-002 | 0.1736558897 | Fail | Fail | 9.3003475294E-002 | 0.2132847225 | Pass | Fail |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1409101539 | 0.3477429968 | Fail | Pass | 7.2953621424E-002 | 0.1429553018 | Pass | Fail |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.1669641200E-002 | 4.5514710831E-002 | Fail | Pass | 0.1383914009 | 0.3918570372 | Fail | Fail |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3040.67 | 49.88 | 593.26 | 2732.74 | 7348.30 | 13764.84 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.678 | 0.251 | 0.251 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.678 | 0.251 | 0.251 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.678 | 0.251 | 0.251 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.678 | 0.251 | 0.251 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.678 | 0.251 | 0.251 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.678 | 0.251 | 0.251 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.678 | 0.251 | 0.251 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.678 | 0.251 | 0.251 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.678 | 0.251 | 0.251 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.678 | 0.251 | 0.251 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.678 | 0.251 | 0.251 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.678 | 0.251 | 0.251 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.678 | 0.251 | 0.251 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.678 | 0.251 | 0.251 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.678 | 0.251 | 0.251 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.678 | 0.251 | 0.251 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.678 | 0.251 | 0.251 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.678 | 0.251 | 0.251 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.678 | 0.251 | 0.251 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.678 | 0.251 | 0.251 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.678 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.678 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.678 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.678 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 432.95 | 2.678 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.678 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.1389 | 1978.83 | 18084.33 | LightsWired | LTG_SCH_BASEMENT | 51.16 | 168.00 | 51.10 | 0.0000 | Y | 173.46 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.3365 | 67.07 | 894.50 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.61 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.3365 | 77.67 | 1035.83 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 9.97 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 9.2031 | 164.24 | 1511.55 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 16.63 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 6.1031 | 94.76 | 578.33 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 2.78 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.8125 | 78.04 | 453.60 | LightsWired | LTG_SCH_LAUNDRY | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 4.37 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.3656 | 188.86 | 1957.67 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.96 | 0.0000 | Y | 17.99 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 8.7188 | 1308.19 | 11405.76 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 56.98 | 0.0000 | Y | 122.00 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.5531 | 156.09 | 710.69 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.5531 | 156.07 | 710.61 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.5531 | 1863.81 | 8486.17 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 76.02 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.5531 | 1864.32 | 8488.49 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 76.04 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.5531 | 156.09 | 710.69 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.5531 | 156.07 | 710.61 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 6.3938 | 1557.62 | 9959.03 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 109.60 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.5531 | 39.02 | 177.67 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.59 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.5531 | 39.02 | 177.65 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.59 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.5531 | 220.77 | 1005.22 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 9.00 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.3656 | 331.66 | 3437.84 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 53.92 | 0.0000 | Y | 34.80 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.3656 | 331.66 | 3437.84 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 53.92 | 0.0000 | Y | 34.80 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7219 | 103.30 | 1210.92 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.33 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 6.3938 | 412.12 | 2635.02 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 29.00 |
Interior Lighting Total | 6.8557 | 11345.29 | 77780.02 | 507.69 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 11405.76 | 798.40 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 11405.76 | 0.00 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1957.67 | 763.49 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 1957.67 | 0.00 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3437.84 | 687.57 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3437.84 | 0.00 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3437.84 | 687.57 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3437.84 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 15448.40 | AstronomicalClock | - | 83.77 | 83.77 | 242.92 | |
Exterior Lighting Total | 15448.40 | 242.92 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 435807.96 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1007279.73 | 2.96 | 1007456.78 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10958.67 | 16689.26 | 13202.77 | 3486.49 | 0.79 | - | 1981.59 | 20.10 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10834.58 | 16495.95 | 13047.29 | 3448.66 | 0.79 | - | 1958.45 | 19.86 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 60110.40 | 92266.68 | 73427.20 | 18839.48 | 0.80 | - | 10988.79 | 111.45 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 68070.43 | 102208.39 | 80011.66 | 22196.72 | 0.78 | - | 12083.02 | 122.55 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9884.72 | 15019.81 | 11862.25 | 3157.56 | 0.79 | - | 1781.88 | 18.07 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9799.69 | 14887.55 | 11756.01 | 3131.54 | 0.79 | - | 1766.06 | 17.91 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2874.69 | 4381.94 | 3468.88 | 913.06 | 0.79 | - | 520.47 | 5.28 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2838.13 | 4325.22 | 3423.40 | 901.82 | 0.79 | - | 513.69 | 5.21 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 13048.25 | 19750.05 | 15549.76 | 4200.29 | 0.79 | - | 2341.26 | 23.75 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 727095.27 | 650476.42 | 420559.44 | 229916.99 | 0.65 | - | 79024.20 | 801.51 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 91161.11 | 64688.92 | 41041.02 | 23647.90 | 0.63 | - | 7608.06 | 77.17 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 8107.59 | 8149.24 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3821.33 | 3837.39 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1675.19 | 1683.14 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2541.28 | 2552.33 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1435.83 | 1441.85 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11555.24 | 11614.36 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11149.29 | 11200.86 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 30230.88 | 30374.97 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6543.14 | 7047.88 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6555.57 | 7061.27 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 37521.80 | 40416.10 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 37770.48 | 40683.93 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6517.57 | 7020.34 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6530.00 | 7033.74 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 14322.52 | 14385.04 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1994.61 | 2148.42 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1999.59 | 2153.78 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 9532.03 | 10267.05 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12601.99 | 12663.12 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 13033.67 | 13096.99 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8590.10 | 8633.81 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8845.55 | 8882.60 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 176420.31 | 131207.19 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 16512.40 | 12280.59 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.98 | 691.70 | 703.64 | 1.00 | 1.20 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.97 | 683.37 | 703.64 | 1.00 | 1.20 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.51 | 3879.26 | 703.64 | 1.00 | 0.96 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.87 | 4128.29 | 703.64 | 1.00 | 0.96 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.88 | 620.00 | 703.64 | 1.00 | 1.23 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.87 | 614.32 | 703.64 | 1.00 | 1.23 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.26 | 181.91 | 703.64 | 1.00 | 1.82 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.26 | 179.48 | 703.64 | 1.00 | 1.83 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.15 | 808.93 | 703.64 | 1.00 | 1.16 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 21.92 | 49106.94 | 2240.64 | 1.00 | 1.11 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.035956 | 7409.20 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003813 | 1148.20 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.035956 | 5129.64 | 142664.32 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 33947.36 | 33947.36 | 17.16 | 2.558 | 2.558 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00921 | 28.79 | 0.01446 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4342.58 | 4342.58 | 64.75 | 0.327 | 0.327 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00921 | 34.40 | 0.01447 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3310.51 | 3310.51 | 42.62 | 0.250 | 0.250 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.00 | 24.00 | 0.00943 | 32.12 | 0.01447 | 0.092 | 0.00 |
MECH_FLR_1 | 3318.96 | 3318.96 | 20.21 | 0.250 | 0.250 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 24.00 | 24.00 | 0.00887 | 30.17 | 0.01447 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1609.56 | 1609.56 | 16.99 | 0.121 | 0.121 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00901 | 31.88 | 0.01447 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44981.16 | 44981.16 | 576.39 | 3.390 | 3.390 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00856 | 33.92 | 0.01447 | 0.000 | 0.00 |
CAFE_FLR_1 | 18533.14 | 18533.14 | 98.13 | 1.398 | 1.398 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.99 | 0.01030 | 34.40 | 0.01447 | 0.676 | 0.00 |
LOBBY_FLR_1 | 61837.79 | 61837.79 | 47.27 | 4.662 | 4.662 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 23.99 | 0.01010 | 34.40 | 0.01447 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 9679.85 | 9679.85 | 248.06 | 0.983 | 0.983 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00870 | 32.91 | 0.01447 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9563.20 | 9563.20 | 245.10 | 0.971 | 0.971 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00871 | 32.75 | 0.01447 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 54291.92 | 54291.92 | 2213.84 | 5.513 | 5.513 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00862 | 34.40 | 0.01447 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 57772.66 | 57772.66 | 2355.13 | 5.867 | 5.867 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 21.11 | 21.11 | 0.00886 | 34.02 | 0.01447 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8676.42 | 8676.42 | 222.35 | 0.881 | 0.881 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 21.11 | 21.11 | 0.00873 | 31.50 | 0.01447 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8596.87 | 8596.87 | 220.33 | 0.873 | 0.873 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 21.11 | 21.11 | 0.00873 | 31.26 | 0.01447 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 18978.55 | 18978.55 | 48.74 | 1.430 | 1.430 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00959 | 34.21 | 0.01447 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2545.72 | 2545.72 | 65.24 | 0.259 | 0.259 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00869 | 32.91 | 0.01447 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2511.74 | 2511.74 | 64.37 | 0.255 | 0.255 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00870 | 32.91 | 0.01447 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11320.16 | 11320.16 | 461.47 | 1.150 | 1.150 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00877 | 34.40 | 0.01447 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29720.29 | 29720.29 | 89.61 | 2.243 | 2.243 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.98 | 0.01042 | 34.30 | 0.01447 | 1.188 | 0.00 |
DINING_FLR_6 | 31150.22 | 31150.22 | 93.92 | 2.350 | 2.350 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.98 | 0.01034 | 34.30 | 0.01447 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30599.39 | 30599.39 | 296.21 | 2.312 | 2.312 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01012 | 33.55 | 0.01447 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9926.69 | 9926.69 | 24.09 | 0.748 | 0.748 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00909 | 34.40 | 0.01447 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1219.23 | 1219.23 | 0.62 | 0.054 | 0.854 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00793 | -6.30 | 0.00230 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2940.73 | 2940.73 | 43.84 | 0.131 | 0.131 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00757 | -6.30 | 0.00230 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1003.89 | 1003.89 | 12.93 | 0.045 | 0.092 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00752 | -6.30 | 0.00230 | 0.092 | 0.00 |
MECH_FLR_1 | 1868.56 | 1868.56 | 11.38 | 0.083 | 0.083 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00740 | -6.30 | 0.00230 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1109.58 | 1109.58 | 11.71 | 0.049 | 0.058 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00741 | -6.30 | 0.00230 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2438.19 | 2438.19 | 31.24 | 0.108 | 0.108 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00737 | -6.30 | 0.00230 | 0.000 | 0.00 |
CAFE_FLR_1 | 7387.54 | 7387.54 | 39.12 | 0.328 | 0.676 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00762 | -6.30 | 0.00230 | 0.676 | 0.00 |
LOBBY_FLR_1 | 17687.28 | 17687.28 | 13.52 | 0.786 | 1.894 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00755 | -6.30 | 0.00230 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 6543.24 | 6543.24 | 167.68 | 0.293 | 0.293 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00755 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 6555.67 | 6555.67 | 168.02 | 0.293 | 0.293 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00755 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 37522.07 | 37522.07 | 1530.02 | 1.678 | 1.678 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00758 | -6.30 | 0.00230 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 37770.76 | 37770.76 | 1539.74 | 1.689 | 1.689 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00759 | -6.30 | 0.00230 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 6517.66 | 6517.66 | 167.03 | 0.291 | 0.291 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00755 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 6530.10 | 6530.10 | 167.36 | 0.292 | 0.292 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00755 | -6.30 | 0.00230 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 10473.59 | 10473.59 | 26.90 | 0.466 | 0.475 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00765 | -6.30 | 0.00230 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1994.63 | 1994.63 | 51.12 | 0.089 | 0.089 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00763 | -6.30 | 0.00230 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1999.62 | 1999.62 | 51.25 | 0.089 | 0.089 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00763 | -6.30 | 0.00230 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 9532.14 | 9532.14 | 388.58 | 0.426 | 0.426 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00764 | -6.30 | 0.00230 | 0.099 | 0.00 |
BANQUET_FLR_6 | 6566.49 | 6566.49 | 19.80 | 0.292 | 1.188 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.00 | 21.00 | 0.00772 | -6.30 | 0.00230 | 1.188 | 0.00 |
DINING_FLR_6 | 6707.97 | 6707.97 | 20.23 | 0.298 | 1.188 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00772 | -6.30 | 0.00230 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2381.74 | 2381.74 | 23.06 | 0.106 | 0.367 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00679 | -6.30 | 0.00230 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 6832.02 | 6832.02 | 16.58 | 0.304 | 0.304 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 21.00 | 21.00 | 0.00776 | -6.30 | 0.00230 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 21.92 | 21.92 | 7.42 | 7.42 | 21.9165 | 11.6591 | 21.9165 | 0.5320 | 0.3000 |
FLR_3_DOAS | 16.15 | 2.05 | 5.14 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 8107.594 | 8107.594 | 1.353335 | 0.00007093 | 170.635 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8107.59 | 8107.59 | 1.353335 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00792637 | 49.4093 | 1219.23 | 0.00 | 8153.01 | 8153.01 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3821.333 | 3821.333 | 0.173147 | 0.00003343 | 96.777 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 3821.33 | 3821.33 | 0.173147 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00756775 | 47.2025 | 2940.73 | 0.00 | 3840.96 | 3840.96 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1675.189 | 1675.189 | 0.131993 | 0.00001466 | 37.889 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1675.19 | 1675.19 | 0.131993 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00751602 | 46.8825 | 1003.89 | 0.00 | 1684.23 | 1684.23 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2541.275 | 2541.275 | 0.132302 | 0.00002223 | 62.067 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 2541.28 | 2541.28 | 0.132302 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00739920 | 46.1625 | 1868.56 | 0.00 | 2554.48 | 2554.48 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1435.834 | 1435.834 | 0.064162 | 0.00001256 | 36.509 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1435.83 | 1435.83 | 0.064162 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00741452 | 46.2569 | 1109.58 | 0.00 | 1443.20 | 1443.20 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11555.242 | 11555.242 | 1.793282 | 0.00010109 | 244.335 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 11555.24 | 11555.24 | 1.793282 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00737438 | 46.0106 | 2438.19 | 0.00 | 11619.87 | 11619.87 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 11149.293 | 11149.293 | 0.739567 | 0.00009754 | 259.146 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 11149.29 | 11149.29 | 0.739567 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00761615 | 47.5004 | 7387.54 | 0.00 | 11208.89 | 11208.89 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 30230.880 | 30230.880 | 2.466234 | 0.00026447 | 680.430 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 30230.88 | 30230.88 | 2.466234 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00754779 | 47.0783 | 17687.28 | 0.00 | 30394.28 | 30394.28 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 10958.670 | -999.000 | 0.983040 | 0.00039141 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 10958.67 | 10463.54 | 0.983040 | 21.70 | 15.37 | 0.00870252 | 12.80 | 11.77 | 0.00850000 | 32.91 | 0.01447054 | 23.14 | 0.0000 | 21.11 | 0.00870252 | 53.8156 | 9679.85 | 0.00 | 11341.29 | 10619.57 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 6543.137 | 6543.137 | 0.292589 | 0.00005724 | 186.978 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6543.14 | 6543.14 | 0.292589 | 21.11 | 14.13 | 0.00755287 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00755287 | 46.7910 | 6543.24 | 0.00 | 7053.65 | 7053.65 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 10834.584 | -999.000 | 0.971194 | 0.00038698 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 10834.58 | 10338.64 | 0.971194 | 21.70 | 15.38 | 0.00870530 | 12.80 | 11.77 | 0.00850000 | 32.75 | 0.01447025 | 23.10 | 0.0000 | 21.11 | 0.00870530 | 53.8326 | 9563.20 | 0.00 | 11212.74 | 10492.65 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 6555.568 | 6555.568 | 0.293145 | 0.00005735 | 187.333 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6555.57 | 6555.57 | 0.293145 | 21.11 | 14.13 | 0.00755368 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00755368 | 46.7959 | 6555.67 | 0.00 | 7067.05 | 7067.05 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 60110.399 | -999.000 | 5.513166 | 0.00214696 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 60110.40 | 58480.74 | 5.513166 | 21.70 | 15.30 | 0.00861927 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 0.0000 | 21.11 | 0.00861927 | 53.3056 | 54291.92 | 0.00 | 62231.67 | 59379.67 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 37521.797 | 37521.797 | 1.677898 | 0.00032826 | 1072.217 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 37521.80 | 37521.80 | 1.677898 | 21.11 | 14.16 | 0.00758418 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00758418 | 46.9814 | 37522.07 | 0.00 | 40449.61 | 40449.61 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 68070.430 | -999.000 | 5.867085 | 0.00243127 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | 7/21 15:40:00 | 68070.43 | 62835.30 | 5.867085 | 21.70 | 15.51 | 0.00885656 | 12.80 | 11.77 | 0.00850000 | 34.02 | 0.01447257 | 23.44 | 0.0000 | 21.11 | 0.00885656 | 54.7547 | 57772.66 | 0.00 | 70425.02 | 63742.27 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 37770.482 | 37770.482 | 1.689019 | 0.00033043 | 1079.322 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 37770.48 | 37770.48 | 1.689019 | 21.11 | 14.16 | 0.00758661 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00758661 | 46.9963 | 37770.76 | 0.00 | 40717.70 | 40717.70 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9884.717 | -999.000 | 0.881139 | 0.00035305 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | 7/21 10:30:00 | 9884.72 | 9388.11 | 0.881139 | 21.70 | 15.40 | 0.00872639 | 12.80 | 11.77 | 0.00850000 | 31.50 | 0.01446797 | 22.76 | 0.0000 | 21.11 | 0.00872639 | 53.9613 | 8676.42 | 0.00 | 10228.80 | 9526.90 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 6517.566 | 6517.566 | 0.291446 | 0.00005702 | 186.248 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6517.57 | 6517.57 | 0.291446 | 21.11 | 14.13 | 0.00755125 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00755125 | 46.7811 | 6517.66 | 0.00 | 7026.08 | 7026.08 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9799.693 | -999.000 | 0.873060 | 0.00035002 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | 7/21 10:20:00 | 9799.69 | 9302.86 | 0.873060 | 21.70 | 15.40 | 0.00872857 | 12.80 | 11.77 | 0.00850000 | 31.26 | 0.01446754 | 22.70 | 0.0000 | 21.11 | 0.00872857 | 53.9746 | 8596.87 | 0.00 | 10140.72 | 9440.29 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 6530.005 | 6530.005 | 0.292002 | 0.00005713 | 186.603 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6530.00 | 6530.00 | 0.292002 | 21.11 | 14.13 | 0.00755207 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00755207 | 46.7861 | 6530.10 | 0.00 | 7039.49 | 7039.49 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 14322.521 | 14322.521 | 0.756582 | 0.00012530 | 348.608 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 14322.52 | 14322.52 | 0.756582 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00765371 | 47.7306 | 10473.59 | 0.00 | 14397.01 | 14397.01 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2874.691 | -999.000 | 0.258531 | 0.00010268 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 2874.69 | 2750.72 | 0.258531 | 21.70 | 15.37 | 0.00869288 | 12.80 | 11.77 | 0.00850000 | 32.91 | 0.01447054 | 23.14 | 0.0000 | 21.11 | 0.00869288 | 53.7568 | 2545.72 | 0.00 | 2975.18 | 2791.88 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1994.605 | 1994.605 | 0.089193 | 0.00001745 | 56.996 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1994.61 | 1994.61 | 0.089193 | 21.11 | 14.20 | 0.00762799 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00762799 | 47.2507 | 1994.63 | 0.00 | 2150.23 | 2150.23 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2838.127 | -999.000 | 0.255081 | 0.00010137 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 2838.13 | 2714.28 | 0.255081 | 21.70 | 15.37 | 0.00869527 | 12.80 | 11.77 | 0.00850000 | 32.91 | 0.01447054 | 23.14 | 0.0000 | 21.11 | 0.00869527 | 53.7715 | 2511.74 | 0.00 | 2937.31 | 2754.86 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1999.590 | 1999.590 | 0.089416 | 0.00001749 | 57.138 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1999.59 | 1999.59 | 0.089416 | 21.11 | 14.20 | 0.00762888 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00762888 | 47.2561 | 1999.62 | 0.00 | 2155.60 | 2155.60 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13048.253 | -999.000 | 1.149637 | 0.00046604 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 13048.25 | 12270.92 | 1.149637 | 21.70 | 15.43 | 0.00877111 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 0.0000 | 21.11 | 0.00877111 | 54.2343 | 11320.16 | 0.00 | 13504.56 | 12453.40 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 9532.032 | 9532.032 | 0.426247 | 0.00008339 | 272.376 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 9532.03 | 9532.03 | 0.426247 | 21.11 | 14.21 | 0.00764069 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00764069 | 47.3280 | 9532.14 | 0.00 | 10275.77 | 10275.77 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12601.986 | 12601.986 | 1.186295 | 0.00011025 | 278.561 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 12601.99 | 12601.99 | 1.186295 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00771778 | 48.1257 | 6566.49 | 0.00 | 12670.59 | 12670.59 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 13033.668 | 13033.668 | 1.243352 | 0.00011402 | 287.662 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 13033.67 | 13033.67 | 1.243352 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00772344 | 48.1609 | 6707.97 | 0.00 | 13104.66 | 13104.66 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 8590.100 | 8590.100 | 1.223114 | 0.00007515 | 182.734 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 8590.10 | 8590.10 | 1.223114 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00678741 | 42.3938 | 2381.74 | 0.00 | 8638.05 | 8638.05 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 8845.548 | 8845.548 | 0.395728 | 0.00007738 | 224.843 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 8845.55 | 8845.55 | 0.395728 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00776046 | 48.3883 | 6832.02 | 0.00 | 8890.93 | 8890.93 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 727095.269 | -999.000 | 21.916495 | 0.02597016 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 727095.27 | 482104.89 | 21.916495 | 29.53 | 20.70 | 0.01225033 | 10.92 | 10.92 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 53.2086 | 23.99 | 0.00970219 | 50.2824 | 290623.29 | 0.00 | 741654.97 | 478930.53 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 176420.310 | 176420.310 | 6.574948 | 0.00154340 | 2977.623 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 176420.31 | 176420.31 | 6.574948 | -6.30 | -6.30 | 0.00229779 | 16.70 | 12.85 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 177.3620 | 21.01 | 0.00761557 | 47.4693 | 67640.21 | 0.00 | 158656.53 | 158656.53 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 91161.109 | -999.000 | 2.051317 | 0.00325606 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 91161.11 | 55491.40 | 2.051317 | 34.40 | 23.54 | 0.01447326 | 11.91 | 11.41 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 99.9965 | 21.11 | 0.00874297 | 54.0612 | 158520.69 | 0.00 | 92644.03 | 56011.80 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 16512.404 | 16512.404 | 0.615395 | 0.00014446 | 278.696 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 16512.40 | 16512.40 | 0.615395 | -6.30 | -6.30 | 0.00229779 | 16.70 | 12.85 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 333.3216 | 21.11 | 0.00758565 | 46.9904 | 114965.90 | 0.00 | 14849.77 | 14849.77 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 8107.594 | 8107.594 | 1.353335 | 0.00007093 | 170.635 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 1.8237 | 1.860359 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8107.59 | 8107.59 | 1.0000 | 1.57119046 | 1.353335 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.07092153 | 60.00 | 32.22 | 27.78 | 0.000 | 8107.59 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00792637 | 21.00 | 0.00792637 | 49.4093 | 1219.23 | 0.00 | 8153.01 | 8153.01 | 1.57119046 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.69 | 15.11 | 0.00800000 | 42123.8 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3821.333 | 3821.333 | 0.173147 | 0.00003343 | 96.777 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 0.8595 | 0.876839 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 3821.33 | 3821.33 | 1.0000 | 0.20101990 | 0.173147 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.03342728 | 60.00 | 32.22 | 27.78 | 0.000 | 3821.33 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00756775 | 21.00 | 0.00756775 | 47.2025 | 2940.73 | 0.00 | 3840.96 | 3840.96 | 0.20101990 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.34 | 19.76 | 0.00800000 | 56042.1 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1675.189 | 1675.189 | 0.131993 | 0.00001466 | 37.889 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 0.3768 | 0.384387 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 1675.19 | 1675.19 | 1.0000 | 0.15324102 | 0.131993 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01465379 | 60.00 | 32.22 | 27.78 | 0.000 | 1675.19 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00751602 | 21.00 | 0.00751602 | 46.8825 | 1003.89 | 0.00 | 1684.23 | 1684.23 | 0.15324102 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.38 | 17.15 | 0.00800000 | 47925.4 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2541.275 | 2541.275 | 0.132302 | 0.00002223 | 62.067 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 0.5716 | 0.583118 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 2541.28 | 2541.28 | 1.0000 | 0.15359962 | 0.132302 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.02222992 | 60.00 | 32.22 | 27.78 | 0.000 | 2541.28 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00739920 | 21.00 | 0.00739920 | 46.1625 | 1868.56 | 0.00 | 2554.48 | 2554.48 | 0.15359962 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.91 | 18.99 | 0.00800000 | 53565.5 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1435.834 | 1435.834 | 0.064162 | 0.00001256 | 36.509 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 0.3230 | 0.329465 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 1435.83 | 1435.83 | 1.0000 | 0.07449023 | 0.064162 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01256002 | 60.00 | 32.22 | 27.78 | 0.000 | 1435.83 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00741452 | 21.00 | 0.00741452 | 46.2569 | 1109.58 | 0.00 | 1443.20 | 1443.20 | 0.07449023 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.60 | 19.84 | 0.00800000 | 56309.1 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11555.242 | 11555.242 | 1.793282 | 0.00010109 | 244.335 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 2.5991 | 2.651453 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 11555.24 | 11555.24 | 1.0000 | 2.08195812 | 1.793282 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.10107999 | 60.00 | 32.22 | 27.78 | 0.000 | 11555.24 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00737438 | 21.00 | 0.00737438 | 46.0106 | 2438.19 | 0.00 | 11619.87 | 11619.87 | 2.08195812 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.07 | 15.25 | 0.00800000 | 42516.0 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11149.293 | 11149.293 | 0.739567 | 0.00009754 | 259.146 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 2.5078 | 2.558304 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 11149.29 | 11149.29 | 1.0000 | 0.85861939 | 0.739567 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.09752893 | 60.00 | 32.22 | 27.78 | 0.000 | 11149.29 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00761615 | 21.00 | 0.00761615 | 47.5004 | 7387.54 | 0.00 | 11208.89 | 11208.89 | 0.85861939 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.40 | 17.84 | 0.00800000 | 49989.3 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30230.880 | 30230.880 | 2.466234 | 0.00026447 | 680.430 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 6.7999 | 6.936743 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 30230.88 | 30230.88 | 1.0000 | 2.86324015 | 2.466234 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.26444595 | 60.00 | 32.22 | 27.78 | 0.000 | 30230.88 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00754779 | 21.00 | 0.00754779 | 47.0783 | 17687.28 | 0.00 | 30394.28 | 30394.28 | 2.86324015 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.01 | 17.02 | 0.00800000 | 47550.1 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10958.670 | -999.000 | 0.983040 | 0.00039141 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0175 | 1004.8586 | 1.1610 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.983040 | 1.14128622 | 4197.9300 | 999.8980 | 35.95233857 | 13.37 | 6.70 | 6.67 | 1006672.42 | 1.0886 | 1.088583 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 10958.67 | 10463.54 | 1.0000 | 1.14128622 | 0.983040 | 21.70 | 15.37 | 0.00870252 | 43924.2 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.39137107 | 6.70 | 13.37 | 6.67 | 0.000 | 10958.67 | 32.91 | 0.01447054 | 23.14 | 0.00000000 | 0.0000 | 21.11 | 0.00870252 | 21.11 | 0.00870252 | 53.8156 | 9679.85 | 0.00 | 11341.29 | 10619.57 | 1.14128622 | 21.70 | 15.74 | 0.00870252 | 43924.2 | 12.59 | 11.97 | 0.00845200 | 33986.9 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6543.137 | 6543.137 | 0.292589 | 0.00005724 | 186.978 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.983040 | 1.14128622 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 1.4718 | 1.501381 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 6543.14 | 6543.14 | 1.0000 | 0.33968937 | 0.292589 | 21.11 | 14.13 | 0.00755287 | 40398.1 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.05723638 | 60.00 | 32.22 | 27.78 | 0.000 | 6543.14 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00755287 | 21.11 | 0.00755287 | 46.7910 | 6543.24 | 0.00 | 7053.65 | 7053.65 | 0.33968937 | 16.60 | 12.71 | 0.00755287 | 35802.7 | 36.98 | 19.94 | 0.00755287 | 56567.7 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10834.584 | -999.000 | 0.971194 | 0.00038698 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0227 | 1004.8586 | 1.1610 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.971194 | 1.12753365 | 4197.9300 | 999.8980 | 35.95233857 | 13.37 | 6.70 | 6.67 | 1006672.42 | 1.0763 | 1.076257 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 10834.58 | 10338.64 | 1.0000 | 1.12753365 | 0.971194 | 21.70 | 15.38 | 0.00870530 | 43931.3 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.38693954 | 6.70 | 13.37 | 6.67 | 0.000 | 10834.58 | 32.75 | 0.01447025 | 23.10 | 0.00000000 | 0.0000 | 21.11 | 0.00870530 | 21.11 | 0.00870530 | 53.8326 | 9563.20 | 0.00 | 11212.74 | 10492.65 | 1.12753365 | 21.70 | 15.74 | 0.00870530 | 43931.3 | 12.59 | 11.97 | 0.00845230 | 33986.8 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6555.568 | 6555.568 | 0.293145 | 0.00005735 | 187.333 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.971194 | 1.12753365 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 1.4746 | 1.504233 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 6555.57 | 6555.57 | 1.0000 | 0.34033471 | 0.293145 | 21.11 | 14.13 | 0.00755368 | 40400.1 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.05734512 | 60.00 | 32.22 | 27.78 | 0.000 | 6555.57 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00755368 | 21.11 | 0.00755368 | 46.7959 | 6555.67 | 0.00 | 7067.05 | 7067.05 | 0.34033471 | 16.60 | 12.72 | 0.00755368 | 35804.7 | 36.98 | 19.94 | 0.00755368 | 56569.7 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 60110.399 | -999.000 | 5.513166 | 0.00214696 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8628 | 1004.8586 | 1.1610 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.513166 | 6.40065667 | 4197.9300 | 999.8980 | 35.95233857 | 13.37 | 6.70 | 6.67 | 1006672.42 | 5.9712 | 5.971086 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 60110.40 | 58480.74 | 1.0000 | 6.40065667 | 5.513166 | 21.70 | 15.30 | 0.00861927 | 43713.5 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 2.14674509 | 6.70 | 13.37 | 6.67 | 0.000 | 60110.40 | 34.40 | 0.01447326 | 23.54 | 0.00000000 | 0.0000 | 21.11 | 0.00861927 | 21.11 | 0.00861927 | 53.3056 | 54291.92 | 0.00 | 62231.67 | 59379.67 | 6.40065667 | 21.70 | 15.67 | 0.00861927 | 43713.5 | 12.62 | 11.97 | 0.00844276 | 33990.8 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 37521.797 | 37521.797 | 1.677898 | 0.00032826 | 1072.217 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.513166 | 6.40065667 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 8.4399 | 8.609709 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 37521.80 | 37521.80 | 1.0000 | 1.94800027 | 1.677898 | 21.11 | 14.16 | 0.00758418 | 40478.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.32822356 | 60.00 | 32.22 | 27.78 | 0.000 | 37521.80 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00758418 | 21.11 | 0.00758418 | 46.9814 | 37522.07 | 0.00 | 40449.61 | 40449.61 | 1.94800027 | 16.60 | 12.75 | 0.00758418 | 35882.0 | 36.98 | 19.96 | 0.00758418 | 56646.6 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 68070.430 | -999.000 | 5.867085 | 0.00243127 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3039 | 1004.8586 | 1.1610 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.867085 | 6.81154833 | 4197.9300 | 999.8980 | 35.95233857 | 13.37 | 6.70 | 6.67 | 1006672.42 | 6.7619 | 6.761798 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | unknown | unknown | 7/21 15:40:00 | Sensible | 68070.43 | 62835.30 | 1.0000 | 6.81154833 | 5.867085 | 21.70 | 15.51 | 0.00885656 | 44315.6 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 2.43102462 | 6.70 | 13.37 | 6.67 | 0.000 | 68070.43 | 34.02 | 0.01447257 | 23.44 | 0.00000000 | 0.0000 | 21.11 | 0.00885656 | 21.11 | 0.00885656 | 54.7547 | 57772.66 | 0.00 | 70425.02 | 63742.27 | 6.81154833 | 21.70 | 15.88 | 0.00885656 | 44315.6 | 12.54 | 11.96 | 0.00846790 | 33976.5 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 37770.482 | 37770.482 | 1.689019 | 0.00033043 | 1079.322 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.867085 | 6.81154833 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 8.4958 | 8.666772 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 37770.48 | 37770.48 | 1.0000 | 1.96091113 | 1.689019 | 21.11 | 14.16 | 0.00758661 | 40484.2 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.33039894 | 60.00 | 32.22 | 27.78 | 0.000 | 37770.48 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00758661 | 21.11 | 0.00758661 | 46.9963 | 37770.76 | 0.00 | 40717.70 | 40717.70 | 1.96091113 | 16.60 | 12.75 | 0.00758661 | 35888.1 | 36.98 | 19.96 | 0.00758661 | 56652.8 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9884.717 | -999.000 | 0.881139 | 0.00035305 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0619 | 1004.8586 | 1.1610 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.881139 | 1.02298144 | 4197.9300 | 999.8980 | 35.95233857 | 13.37 | 6.70 | 6.67 | 1006672.42 | 0.9819 | 0.981902 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | unknown | unknown | 7/21 10:30:00 | Sensible | 9884.72 | 9388.11 | 1.0000 | 1.02298144 | 0.881139 | 21.70 | 15.40 | 0.00872639 | 43984.9 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.35301658 | 6.70 | 13.37 | 6.67 | 0.000 | 9884.72 | 31.50 | 0.01446797 | 22.76 | 0.00000000 | 0.0000 | 21.11 | 0.00872639 | 21.11 | 0.00872639 | 53.9613 | 8676.42 | 0.00 | 10228.80 | 9526.90 | 1.02298144 | 21.70 | 15.76 | 0.00872639 | 43984.9 | 12.58 | 11.96 | 0.00845458 | 33985.8 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6517.566 | 6517.566 | 0.291446 | 0.00005702 | 186.248 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.881139 | 1.02298144 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 1.4660 | 1.495513 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 6517.57 | 6517.57 | 1.0000 | 0.33836180 | 0.291446 | 21.11 | 14.13 | 0.00755125 | 40394.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.05701269 | 60.00 | 32.22 | 27.78 | 0.000 | 6517.57 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00755125 | 21.11 | 0.00755125 | 46.7811 | 6517.66 | 0.00 | 7026.08 | 7026.08 | 0.33836180 | 16.60 | 12.71 | 0.00755125 | 35798.6 | 36.98 | 19.93 | 0.00755125 | 56563.6 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9799.693 | -999.000 | 0.873060 | 0.00035002 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0660 | 1004.8586 | 1.1610 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.873060 | 1.01360174 | 4197.9300 | 999.8980 | 35.95233857 | 13.37 | 6.70 | 6.67 | 1006672.42 | 0.9735 | 0.973456 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | unknown | unknown | 7/21 10:20:00 | Sensible | 9799.69 | 9302.86 | 1.0000 | 1.01360174 | 0.873060 | 21.70 | 15.40 | 0.00872857 | 43990.4 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.34998009 | 6.70 | 13.37 | 6.67 | 0.000 | 9799.69 | 31.26 | 0.01446754 | 22.70 | 0.00000000 | 0.0000 | 21.11 | 0.00872857 | 21.11 | 0.00872857 | 53.9746 | 8596.87 | 0.00 | 10140.72 | 9440.29 | 1.01360174 | 21.70 | 15.76 | 0.00872857 | 43990.4 | 12.58 | 11.96 | 0.00845482 | 33985.7 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6530.005 | 6530.005 | 0.292002 | 0.00005713 | 186.603 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.873060 | 1.01360174 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 1.4688 | 1.498367 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 6530.00 | 6530.00 | 1.0000 | 0.33900759 | 0.292002 | 21.11 | 14.13 | 0.00755207 | 40396.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.05712150 | 60.00 | 32.22 | 27.78 | 0.000 | 6530.00 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00755207 | 21.11 | 0.00755207 | 46.7861 | 6530.10 | 0.00 | 7039.49 | 7039.49 | 0.33900759 | 16.60 | 12.71 | 0.00755207 | 35800.7 | 36.98 | 19.93 | 0.00755207 | 56565.7 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14322.521 | 14322.521 | 0.756582 | 0.00012530 | 348.608 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 3.2216 | 3.286429 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 14322.52 | 14322.52 | 1.0000 | 0.87837422 | 0.756582 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.12528688 | 60.00 | 32.22 | 27.78 | 0.000 | 14322.52 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00765371 | 21.00 | 0.00765371 | 47.7306 | 10473.59 | 0.00 | 14397.01 | 14397.01 | 0.87837422 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.67 | 18.92 | 0.00800000 | 53325.3 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2874.691 | -999.000 | 0.258531 | 0.00010268 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9996 | 1004.8586 | 1.1610 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.258531 | 0.30014832 | 4197.9300 | 999.8980 | 35.95233857 | 13.37 | 6.70 | 6.67 | 1006672.42 | 0.2856 | 0.285558 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 2874.69 | 2750.72 | 1.0000 | 0.30014832 | 0.258531 | 21.70 | 15.37 | 0.00869288 | 43899.8 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.10266489 | 6.70 | 13.37 | 6.67 | 0.000 | 2874.69 | 32.91 | 0.01447054 | 23.14 | 0.00000000 | 0.0000 | 21.11 | 0.00869288 | 21.11 | 0.00869288 | 53.7568 | 2545.72 | 0.00 | 2975.18 | 2791.88 | 0.30014832 | 21.70 | 15.73 | 0.00869288 | 43899.8 | 12.59 | 11.97 | 0.00845095 | 33987.4 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1994.605 | 1994.605 | 0.089193 | 0.00001745 | 56.996 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.258531 | 0.30014832 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 0.4487 | 0.457680 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 1994.61 | 1994.61 | 1.0000 | 0.10355069 | 0.089193 | 21.11 | 14.20 | 0.00762799 | 40588.9 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01744790 | 60.00 | 32.22 | 27.78 | 0.000 | 1994.61 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00762799 | 21.11 | 0.00762799 | 47.2507 | 1994.63 | 0.00 | 2150.23 | 2150.23 | 0.10355069 | 16.60 | 12.79 | 0.00762799 | 35992.9 | 36.98 | 19.99 | 0.00762799 | 56757.9 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2838.127 | -999.000 | 0.255081 | 0.00010137 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0041 | 1004.8586 | 1.1610 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.255081 | 0.29614280 | 4197.9300 | 999.8980 | 35.95233857 | 13.37 | 6.70 | 6.67 | 1006672.42 | 0.2819 | 0.281926 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 2838.13 | 2714.28 | 1.0000 | 0.29614280 | 0.255081 | 21.70 | 15.37 | 0.00869527 | 43905.8 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.10135908 | 6.70 | 13.37 | 6.67 | 0.000 | 2838.13 | 32.91 | 0.01447054 | 23.14 | 0.00000000 | 0.0000 | 21.11 | 0.00869527 | 21.11 | 0.00869527 | 53.7715 | 2511.74 | 0.00 | 2937.31 | 2754.86 | 0.29614280 | 21.70 | 15.73 | 0.00869527 | 43905.8 | 12.59 | 11.97 | 0.00845121 | 33987.3 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1999.590 | 1999.590 | 0.089416 | 0.00001749 | 57.138 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.255081 | 0.29614280 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 0.4498 | 0.458824 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 1999.59 | 1999.59 | 1.0000 | 0.10380950 | 0.089416 | 21.11 | 14.20 | 0.00762888 | 40591.2 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01749150 | 60.00 | 32.22 | 27.78 | 0.000 | 1999.59 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00762888 | 21.11 | 0.00762888 | 47.2561 | 1999.62 | 0.00 | 2155.60 | 2155.60 | 0.10380950 | 16.60 | 12.79 | 0.00762888 | 35995.1 | 36.98 | 19.99 | 0.00762888 | 56760.1 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13048.253 | -999.000 | 1.149637 | 0.00046604 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1450 | 1004.8586 | 1.1610 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.149637 | 1.33470159 | 4197.9300 | 999.8980 | 35.95233857 | 13.37 | 6.70 | 6.67 | 1006672.42 | 1.2962 | 1.296152 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 13048.25 | 12270.92 | 1.0000 | 1.33470159 | 1.149637 | 21.70 | 15.43 | 0.00877111 | 44098.4 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.46599710 | 6.70 | 13.37 | 6.67 | 0.000 | 13048.25 | 34.40 | 0.01447326 | 23.54 | 0.00000000 | 0.0000 | 21.11 | 0.00877111 | 21.11 | 0.00877111 | 54.2343 | 11320.16 | 0.00 | 13504.56 | 12453.40 | 1.33470159 | 21.70 | 15.80 | 0.00877111 | 44098.4 | 12.57 | 11.96 | 0.00845912 | 33980.3 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9532.032 | 9532.032 | 0.426247 | 0.00008339 | 272.376 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.149637 | 1.33470159 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 2.1441 | 2.187209 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 9532.03 | 9532.03 | 1.0000 | 0.49486282 | 0.426247 | 21.11 | 14.21 | 0.00764069 | 40621.3 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.08338186 | 60.00 | 32.22 | 27.78 | 0.000 | 9532.03 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00764069 | 21.11 | 0.00764069 | 47.3280 | 9532.14 | 0.00 | 10275.77 | 10275.77 | 0.49486282 | 16.60 | 12.80 | 0.00764069 | 36025.0 | 36.98 | 20.00 | 0.00764069 | 56789.9 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12601.986 | 12601.986 | 1.186295 | 0.00011025 | 278.561 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 2.8346 | 2.891637 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 12601.99 | 12601.99 | 1.0000 | 1.37726065 | 1.186295 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.11023643 | 60.00 | 32.22 | 27.78 | 0.000 | 12601.99 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00771778 | 21.00 | 0.00771778 | 48.1257 | 6566.49 | 0.00 | 12670.59 | 12670.59 | 1.37726065 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.62 | 16.53 | 0.00800000 | 46134.6 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13033.668 | 13033.668 | 1.243352 | 0.00011402 | 287.662 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 2.9317 | 2.990691 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 13033.67 | 13033.67 | 1.0000 | 1.44350236 | 1.243352 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.11401258 | 60.00 | 32.22 | 27.78 | 0.000 | 13033.67 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00772344 | 21.00 | 0.00772344 | 48.1609 | 6707.97 | 0.00 | 13104.66 | 13104.66 | 1.44350236 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.50 | 16.49 | 0.00800000 | 46013.1 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8590.100 | 8590.100 | 1.223114 | 0.00007515 | 182.734 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 1.9322 | 1.971075 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 8590.10 | 8590.10 | 1.0000 | 1.42000703 | 1.223114 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.07514228 | 60.00 | 32.22 | 27.78 | 0.000 | 8590.10 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.57 | 0.00678741 | 21.00 | 0.00678741 | 42.3938 | 2381.74 | 0.00 | 8638.05 | 8638.05 | 1.42000703 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.57 | 15.43 | 0.00800000 | 43017.8 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8845.548 | 8845.548 | 0.395728 | 0.00007738 | 224.843 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 1.9896 | 2.029690 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | Sensible | 8845.55 | 8845.55 | 1.0000 | 0.45943110 | 0.395728 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.07737682 | 60.00 | 32.22 | 27.78 | 0.000 | 8845.55 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00776046 | 21.00 | 0.00776046 | 48.3883 | 6832.02 | 0.00 | 8890.93 | 8890.93 | 0.45943110 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.58 | 19.84 | 0.00800000 | 56286.8 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 727095.269 | -999.000 | 21.916495 | 0.02597016 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.6127 | 1004.8586 | 1.1610 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.916495 | 25.44453637 | 4197.9300 | 999.8980 | 35.95233857 | 13.37 | 6.70 | 6.67 | 1006672.42 | 72.2276 | 72.227594 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 727095.27 | 482104.89 | 1.0000 | 25.44453637 | 21.916495 | 29.53 | 20.70 | 0.01225033 | 60981.0 | 10.92 | 10.92 | 0.00850000 | 32405.3 | 25.96750909 | 6.70 | 13.37 | 6.67 | 49106.944 | 677988.32 | 34.40 | 0.01447326 | 23.54 | 11.66146000 | 53.2086 | 23.99 | 0.00972253 | 23.99 | 0.00970219 | 50.2824 | 290623.29 | 0.00 | 741654.97 | 478930.53 | 25.44453637 | 29.53 | 21.12 | 0.01225033 | 60981.0 | 11.21 | 11.08 | 0.00815585 | 31833.1 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 176420.310 | 176420.310 | 6.574948 | 0.00154340 | 2977.623 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.916495 | 25.44453637 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 39.6826 | 40.481204 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 176420.31 | 176420.31 | 1.0000 | 7.63336091 | 6.574948 | -6.30 | -6.30 | 0.00229779 | -610.8 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 1.54324439 | 60.00 | 32.22 | 27.78 | 0.000 | 176420.31 | -6.30 | 0.00229779 | -6.30 | 11.66146000 | 177.3620 | 20.97 | 0.00760315 | 21.01 | 0.00761557 | 47.4693 | 67640.21 | 0.00 | 158656.53 | 158656.53 | 7.63336091 | 2.80 | -0.72 | 0.00229779 | 8572.2 | 23.40 | 10.14 | 0.00229779 | 29356.8 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 91161.109 | -999.000 | 2.051317 | 0.00325606 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1031.7451 | 1004.8586 | 1.1610 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.38144746 | 4197.9300 | 999.8980 | 35.95233857 | 13.37 | 6.70 | 6.67 | 1006672.42 | 9.0557 | 9.055688 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 91161.11 | 55491.40 | 1.0000 | 2.38153119 | 2.051317 | 34.40 | 23.54 | 0.01447326 | 71688.8 | 11.91 | 11.41 | 0.00850000 | 33410.4 | 3.25573143 | 6.70 | 13.37 | 6.67 | 2195.006 | 88966.10 | 34.40 | 0.01447326 | 23.54 | 2.05124512 | 99.9965 | 21.11 | 0.00874518 | 21.11 | 0.00874297 | 54.0612 | 158520.69 | 0.00 | 92644.03 | 56011.80 | 2.38153119 | 34.40 | 23.99 | 0.01447326 | 71688.8 | 11.60 | 11.47 | 0.00837545 | 32787.8 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 16512.404 | 16512.404 | 0.615395 | 0.00014446 | 278.696 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.38144746 | 4197.9300 | 999.8980 | 3.81224921 | 54.44 | 82.22 | 27.78 | 444578.77 | 3.7142 | 3.788918 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | Sensible | 16512.40 | 16512.40 | 1.0000 | 0.71445936 | 0.615395 | -6.30 | -6.30 | 0.00229779 | -610.8 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 0.14444298 | 60.00 | 32.22 | 27.78 | 0.000 | 16512.40 | -6.30 | 0.00229779 | -6.30 | 2.05124512 | 333.3216 | 21.11 | 0.00758399 | 21.11 | 0.00758565 | 46.9904 | 114965.90 | 0.00 | 14849.77 | 14849.77 | 0.71445936 | 2.80 | -0.72 | 0.00229779 | 8572.2 | 23.40 | 10.14 | 0.00229779 | 29356.8 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 11.66 | 21.92 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1526.50 | 5688.17 | 23.17 |
RETAIL_1_FLR_1 | 2873.33 | 5706.17 | 597.83 |
RETAIL_2_FLR_1 | 2601.50 | 5899.50 | 759.83 |
MECH_FLR_1 | 1834.50 | 6282.00 | 406.67 |
STORAGE_FLR_1 | 1498.67 | 6715.33 | 560.17 |
LAUNDRY_FLR_1 | 7402.33 | 3489.17 | 2942.50 |
CAFE_FLR_1 | 4443.17 | 5441.33 | 1946.00 |
LOBBY_FLR_1 | 3785.67 | 5406.33 | 1596.33 |
ROOM_1_FLR_3 | 1568.67 | 8165.17 | 1515.50 |
ROOM_2_FLR_3 | 1965.17 | 8266.00 | 1930.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1392.83 | 8760.00 | 1392.83 |
ROOM_5_FLR_3 | 1468.67 | 8005.33 | 1456.17 |
ROOM_6_FLR_3 | 1842.50 | 8132.67 | 1833.67 |
CORRIDOR_FLR_3 | 2072.50 | 7153.00 | 1246.33 |
ROOM_1_FLR_6 | 2194.33 | 8083.00 | 2045.00 |
ROOM_2_FLR_6 | 2586.83 | 8184.50 | 2480.50 |
ROOM_3_MULT9_FLR_6 | 1039.17 | 8154.00 | 1032.00 |
BANQUET_FLR_6 | 5370.17 | 3680.00 | 1648.50 |
DINING_FLR_6 | 5922.83 | 2791.67 | 1486.50 |
KITCHEN_FLR_6 | 8305.33 | 6580.00 | 6405.67 |
CORRIDOR_FLR_6 | 2610.33 | 5902.67 | 469.17 |
Facility | 8743.17 | 8760.00 | 8142.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 77.67 | 0.00 | 77.67 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 1.67 | 0.00 | 1.67 |
ROOM_2_FLR_3 | 0.00 | 0.83 | 0.00 | 0.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1.17 | 6.50 | 1.17 | 6.50 |
ROOM_5_FLR_3 | 0.00 | 0.83 | 0.00 | 0.83 |
ROOM_6_FLR_3 | 0.00 | 1.00 | 0.00 | 1.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 4.33 | 0.00 | 4.33 |
ROOM_2_FLR_6 | 0.00 | 3.50 | 0.00 | 3.50 |
ROOM_3_MULT9_FLR_6 | 0.00 | 11.17 | 0.00 | 11.17 |
BANQUET_FLR_6 | 0.00 | 9.67 | 0.00 | 9.67 |
DINING_FLR_6 | 0.00 | 12.33 | 0.00 | 12.33 |
KITCHEN_FLR_6 | 0.00 | 141.83 | 0.00 | 141.83 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1.17 | 179.33 | 1.17 | 179.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 106.50 | 4826.41 | 0.988 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.26 | 10.83 | 265.76 | 2.223 | 0.135 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.25 | 12.54 | 307.76 | 1.473 | 0.045 | 0.000 | 0.000 |
MECH_FLR_1 | 1.53 | 2.65 | 650.80 | 0.688 | 0.050 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.573 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 22.213 | 0.145 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.31 | 142.30 | 748.35 | 3.485 | 0.107 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.35 | 422.44 | 5183.56 | 1.695 | 0.044 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.175 | 0.000 | 0.068 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.472 | 0.175 | 0.000 | 0.066 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.536 | 0.078 | 0.000 | 0.104 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.175 | 0.000 | 0.068 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.472 | 0.175 | 0.000 | 0.066 |
CORRIDOR_FLR_3 | 12.12 | 20.96 | 1186.91 | 0.537 | 0.021 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.473 | 0.175 | 0.000 | 0.081 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.472 | 0.175 | 0.000 | 0.079 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.537 | 0.142 | 0.000 | 0.129 |
BANQUET_FLR_6 | 144.55 | 249.90 | 1010.89 | 4.687 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 144.55 | 249.90 | 1010.89 | 5.029 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.86 | 22.24 | 314.87 | 20.653 | 0.146 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.83 | 22.18 | 1256.16 | 1.074 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 106.50 | 4826.41 | 0.578 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.26 | 10.83 | 265.76 | 1.322 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.25 | 12.54 | 307.76 | 0.875 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.53 | 2.65 | 650.80 | 0.412 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.346 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 12.273 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.31 | 142.30 | 748.35 | 2.083 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.35 | 422.44 | 5183.56 | 0.982 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.516 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.455 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.454 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.12 | 20.96 | 1186.91 | 0.323 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.516 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.55 | 249.90 | 1010.89 | 2.429 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.55 | 249.90 | 1010.89 | 2.546 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.86 | 22.24 | 314.87 | 8.107 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.83 | 22.18 | 1256.16 | 0.638 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.60 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.26 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.25 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.53 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.86 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.31 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.35 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.12 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.55 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.55 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.86 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.83 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 870.81 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 41034950.68 | 0.00 | 41034950.68 | 0.00 | 41034950.68 | 26946214.98 | 3.29 | 10.83 | 8745.88 | 0.00 |
RETAIL_1_FLR_1 | 5098440.88 | 0.00 | 5098440.88 | 310220.85 | 5408661.74 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3903484.02 | 0.00 | 3903484.02 | 119745.64 | 4023229.67 | 2892943.94 | 18.16 | 4.04 | 8737.80 | 0.00 |
MECH_FLR_1 | 3862298.02 | 0.00 | 3862298.02 | 283007.56 | 4145305.58 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1858772.92 | 0.00 | 1858772.92 | 163279.77 | 2022052.69 | 1821682.01 | 2716.87 | 549.90 | 5493.23 | 0.00 |
LAUNDRY_FLR_1 | 59160626.84 | 0.00 | 59160626.84 | 386432.37 | 59547059.21 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 22398066.78 | 0.00 | 22398066.78 | 685760.76 | 23083827.54 | 21330615.53 | 2220.67 | 1040.11 | 5499.22 | 0.00 |
LOBBY_FLR_1 | 75420630.75 | 0.00 | 75420630.75 | 1959375.13 | 77380005.88 | 59728886.00 | 73.45 | 44.25 | 8642.30 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 69621.73 | 2016497.35 | 180061.18 | 2196558.52 | 1946875.62 | 0.00 | 7631.17 | 1128.83 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 67658.72 | 2014306.23 | 180047.44 | 2194353.67 | 1946647.51 | 0.00 | 7631.17 | 1128.83 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 73722.75 | 26471610.02 | 50239.09 | 26521849.11 | 26397887.27 | 0.00 | 7681.67 | 1078.33 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 67490.83 | 26472596.56 | 50252.83 | 26522849.38 | 26405105.73 | 0.00 | 7693.63 | 1066.37 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 69698.68 | 2016574.30 | 180061.18 | 2196635.47 | 1946875.62 | 0.00 | 7631.17 | 1128.83 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 67718.71 | 2014366.23 | 180047.44 | 2194413.66 | 1946647.51 | 0.00 | 7631.17 | 1128.83 | 0.00 |
CORRIDOR_FLR_3 | 21993346.13 | 0.00 | 21993346.13 | 217730.19 | 22211076.32 | 14972100.18 | 4.84 | 3.88 | 8751.28 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 83403.01 | 570121.92 | 180098.20 | 750220.12 | 486718.90 | 0.00 | 7626.50 | 1133.50 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 80795.93 | 567457.81 | 180084.46 | 747542.27 | 486661.88 | 0.00 | 7626.50 | 1133.50 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 83445.49 | 3210365.91 | 92144.54 | 3302510.45 | 3126920.42 | 0.00 | 7626.50 | 1133.50 | 0.00 |
BANQUET_FLR_6 | 40599201.02 | 0.00 | 40599201.02 | 439754.55 | 41038955.57 | 37458366.31 | 2879.46 | 1483.19 | 4397.35 | 0.00 |
DINING_FLR_6 | 43548506.82 | 0.00 | 43548506.82 | 439754.55 | 43988261.37 | 37458366.31 | 1738.28 | 351.04 | 6670.69 | 0.00 |
KITCHEN_FLR_6 | 55741000.51 | 0.00 | 55741000.51 | 393682.28 | 56134682.78 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 11636997.80 | 0.00 | 11636997.80 | 385314.24 | 12022312.04 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.45E+10 | 12746231.66 | 0.45E+10 | 18144986.26 | 0.46E+10 | 0.43E+10 | 5002.83 | 7976.26 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3012 | 0.0000 | 1.3012 | 0.0000 | 1.3012 | 0.8545 | 3.29 | 10.83 | 8745.88 |
RETAIL_1_FLR_1 | 0.1617 | 0.0000 | 0.1617 | 0.0098 | 0.1715 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1238 | 0.0000 | 0.1238 | 0.0038 | 0.1276 | 0.0917 | 18.16 | 4.04 | 8737.80 |
MECH_FLR_1 | 0.1225 | 0.0000 | 0.1225 | 0.0090 | 0.1314 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0589 | 0.0000 | 0.0589 | 0.0052 | 0.0641 | 0.0578 | 2716.87 | 549.90 | 5493.23 |
LAUNDRY_FLR_1 | 1.8760 | 0.0000 | 1.8760 | 0.0123 | 1.8882 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7102 | 0.0000 | 0.7102 | 0.0217 | 0.7320 | 0.6764 | 2220.67 | 1040.11 | 5499.22 |
LOBBY_FLR_1 | 2.3916 | 0.0000 | 2.3916 | 0.0621 | 2.4537 | 1.8940 | 73.45 | 44.25 | 8642.30 |
ROOM_1_FLR_3 | 0.0617 | 0.0022 | 0.0639 | 0.0057 | 0.0697 | 0.0617 | 0.00 | 7631.17 | 1128.83 |
ROOM_2_FLR_3 | 0.0617 | 0.0021 | 0.0639 | 0.0057 | 0.0696 | 0.0617 | 0.00 | 7631.17 | 1128.83 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0021 | 0.8394 | 0.0016 | 0.8410 | 0.8373 | 0.00 | 7693.63 | 1066.37 |
ROOM_5_FLR_3 | 0.0617 | 0.0022 | 0.0639 | 0.0057 | 0.0697 | 0.0617 | 0.00 | 7631.17 | 1128.83 |
ROOM_6_FLR_3 | 0.0617 | 0.0021 | 0.0639 | 0.0057 | 0.0696 | 0.0617 | 0.00 | 7631.17 | 1128.83 |
CORRIDOR_FLR_3 | 0.6974 | 0.0000 | 0.6974 | 0.0069 | 0.7043 | 0.4748 | 4.84 | 3.88 | 8751.28 |
ROOM_1_FLR_6 | 0.0154 | 0.0026 | 0.0181 | 0.0057 | 0.0238 | 0.0154 | 0.00 | 7626.50 | 1133.50 |
ROOM_2_FLR_6 | 0.0154 | 0.0026 | 0.0180 | 0.0057 | 0.0237 | 0.0154 | 0.00 | 7626.50 | 1133.50 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0026 | 0.1018 | 0.0029 | 0.1047 | 0.0992 | 0.00 | 7626.50 | 1133.50 |
BANQUET_FLR_6 | 1.2874 | 0.0000 | 1.2874 | 0.0139 | 1.3013 | 1.1878 | 2879.46 | 1483.19 | 4397.35 |
DINING_FLR_6 | 1.3809 | 0.0000 | 1.3809 | 0.0139 | 1.3949 | 1.1878 | 1738.28 | 351.04 | 6670.69 |
KITCHEN_FLR_6 | 1.7675 | 0.0000 | 1.7675 | 0.0125 | 1.7800 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3690 | 0.0000 | 0.3690 | 0.0122 | 0.3812 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 79.8861 | 0.2265 | 80.1126 | 0.4543 | 80.5669 | 73.9670 | 5002.83 | 7976.26 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.52E+09 | 0.00 | 0.52E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 87193944.56 | 663555.85 | 87857500.41 | 64690340.46 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 16.5111 | 0.0000 | 16.5111 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 2.7649 | 0.0210 | 2.7859 | 2.0513 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 5459.33 | 3084.75 | 0.00 | 215.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 15.7190 | 17.9746 | 0.0000 | 15.7824 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 2.7649 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1318 |
Defaulted Fields | 1181 |
Fields with Defaults | 4005 |
Autosized Fields | 350 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 6134.98 | 75961.20 | 07-NOV-02:10 | 442211.49 | 18-AUG-19:20 |
Electricity:Building | 2519.17 | 32804.76 | 02-JAN-02:10 | 151906.32 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 323.72 | 3705.45 | 02-JAN-02:10 | 24299.15 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2512.08 | 32663.61 | 02-JAN-02:10 | 151664.99 | 02-JAN-20:10 |
InteriorLights:Electricity | 767.06 | 6971.81 | 02-JAN-02:10 | 62892.57 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 173.46 | 1576.23 | 02-JAN-02:10 | 14185.34 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 767.06 | 6971.81 | 02-JAN-02:10 | 62892.57 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 767.06 | 6971.81 | 02-JAN-02:10 | 62892.57 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 173.46 | 1576.23 | 02-JAN-02:10 | 14185.34 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 767.06 | 6971.81 | 02-JAN-02:10 | 62892.57 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.80 | 222.61 | 02-JAN-02:10 | 1390.02 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.61 | 78.27 | 02-JAN-02:10 | 704.41 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.61 | 78.27 | 02-JAN-02:10 | 704.41 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.77 | 257.78 | 02-JAN-02:10 | 1609.65 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.97 | 90.64 | 02-JAN-02:10 | 815.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.97 | 90.64 | 02-JAN-02:10 | 815.72 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 29.11 | 327.88 | 02-JAN-02:10 | 2199.84 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 16.64 | 151.16 | 02-JAN-02:10 | 1360.40 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 16.64 | 151.16 | 02-JAN-02:10 | 1360.40 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.38 | 76.28 | 02-JAN-02:10 | 469.87 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.78 | 25.30 | 02-JAN-02:10 | 227.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.78 | 25.30 | 02-JAN-02:10 | 227.72 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.30 | 1002.39 | 02-JAN-02:10 | 4930.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.37 | 39.69 | 02-JAN-02:10 | 357.21 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.37 | 39.69 | 02-JAN-02:10 | 357.21 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 32.33 | 398.98 | 02-JAN-02:10 | 2727.18 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 17.99 | 195.77 | 02-JAN-02:10 | 1761.91 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 17.99 | 195.77 | 02-JAN-02:10 | 1761.91 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 271.00 | 3251.99 | 02-JAN-02:10 | 20294.39 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 122.00 | 1140.58 | 02-JAN-02:10 | 10265.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 122.00 | 1140.58 | 02-JAN-02:10 | 10265.18 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 18.66 | 264.62 | 01-JAN-02:10 | 1227.54 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 18.66 | 264.59 | 01-JAN-02:10 | 1227.39 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 304.77 | 4565.05 | 01-JAN-02:10 | 20923.25 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 76.02 | 643.59 | 01-JAN-02:10 | 5851.22 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 76.02 | 643.59 | 01-JAN-02:10 | 5851.22 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 304.86 | 4566.30 | 01-JAN-02:10 | 20928.98 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 76.04 | 643.77 | 01-JAN-02:10 | 5852.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 76.04 | 643.77 | 01-JAN-02:10 | 5852.82 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 18.66 | 264.62 | 01-JAN-02:10 | 1227.54 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 18.66 | 264.59 | 01-JAN-02:10 | 1227.39 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.66 | 66.15 | 01-JAN-02:10 | 306.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.50 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.50 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.66 | 66.15 | 01-JAN-02:10 | 306.85 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.49 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.49 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.10 | 540.75 | 01-JAN-02:10 | 2478.43 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 9.00 | 76.24 | 01-JAN-02:10 | 693.10 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 9.00 | 76.24 | 01-JAN-02:10 | 693.10 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 210.65 | 2593.08 | 02-JAN-02:10 | 9841.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 34.80 | 343.78 | 02-JAN-02:10 | 3094.06 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 34.80 | 343.78 | 02-JAN-02:10 | 3094.06 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 210.65 | 2593.08 | 02-JAN-02:10 | 9841.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 34.80 | 343.78 | 02-JAN-02:10 | 3094.06 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 34.80 | 343.78 | 02-JAN-02:10 | 3094.06 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 454.16 | 6253.02 | 02-JAN-02:10 | 18944.06 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.33 | 121.09 | 02-JAN-02:10 | 1089.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.33 | 121.09 | 02-JAN-02:10 | 1089.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1745.01 | 25691.80 | 02-JAN-02:10 | 89475.41 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1745.01 | 25691.80 | 02-JAN-02:10 | 89475.41 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 62.27 | 1114.62 | 19-MAR-22:30 | 3428.00 | 13-OCT-06:30 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1930.86 | 2612.98 | 26-APR-01:30 | 211031.63 | 06-JUL-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.49 | 0.00 | 01-JAN-11:10 | 2024.65 | 30-DEC-23:40 |
MedTempRefrigeration:Refrigeration:Electricity | 34.69 | 934.23 | 12-FEB-04:10 | 1244.60 | 31-OCT-09:10 |
Fans:Electricity | 584.52 | 12840.46 | 09-APR-05:00 | 43378.57 | 18-AUG-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 823.00 | 13849.31 | 29-OCT-03:30 | 54534.21 | 18-AUG-21:10 |
ExteriorEquipment:Electricity | 651.48 | 9618.58 | 02-JAN-02:20 | 39726.11 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 32.45 | 553.78 | 23-FEB-02:30 | 1868.65 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 6134.98 | 75961.20 | 07-NOV-02:10 | 442211.49 | 18-AUG-19:20 |
ElectricityPurchased:Plant | 6134.98 | 75961.20 | 07-NOV-02:10 | 442211.49 | 18-AUG-19:20 |
Cogeneration:ElectricityPurchased | 6134.98 | 75961.20 | 07-NOV-02:10 | 442211.49 | 18-AUG-19:20 |
General:Cogeneration:ElectricityPurchased | 6134.98 | 75961.20 | 07-NOV-02:10 | 442211.49 | 18-AUG-19:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 6134.98 | 75961.20 | 07-NOV-02:10 | 442211.49 | 18-AUG-19:20 |
ElectricityNet:Plant | 6134.98 | 75961.20 | 07-NOV-02:10 | 442211.49 | 18-AUG-19:20 |
Cogeneration:ElectricityNet | 6134.98 | 75961.20 | 07-NOV-02:10 | 442211.49 | 18-AUG-19:20 |
General:Cogeneration:ElectricityNet | 6134.98 | 75961.20 | 07-NOV-02:10 | 442211.49 | 18-AUG-19:20 |
General:Fans:Electricity | 584.52 | 12840.46 | 09-APR-05:00 | 43378.57 | 18-AUG-21:10 |
ExteriorLights:Electricity | 242.92 | 0.00 | 01-JAN-07:50 | 15448.40 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 242.92 | 0.00 | 01-JAN-07:50 | 15448.40 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 206.03 | 0.00 | 19-JAN-10:20 | 9938.94 | 01-JAN-16:20 |
General:HeatRecovery:Electricity | 206.03 | 0.00 | 19-JAN-10:20 | 9938.94 | 01-JAN-16:20 |
WaterSystems:Electricity | 90.75 | 1086.56 | 18-JUL-00:50 | 4738.76 | 10-AUG-18:10 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.56 | 18-JUL-00:50 | 4738.76 | 10-AUG-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1642.20 | 0.00 | 01-JAN-00:10 | 199939.90 | 08-JUL-15:20 |
General:Cooling:Electricity | 1642.20 | 0.00 | 01-JAN-00:10 | 199939.90 | 08-JUL-15:20 |
Pumps:Electricity | 142.73 | 47.91 | 20-FEB-09:00 | 7723.29 | 23-AUG-21:00 |
General:Pumps:Electricity | 142.73 | 47.91 | 20-FEB-09:00 | 7723.29 | 23-AUG-21:00 |
WIRED_LTG_ELECTRICITY | 27.00 | 0.00 | 01-JAN-00:10 | 2213.82 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5142.49 | 29270.80 | 14-MAR-01:20 | 522364.03 | 07-JAN-17:10 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3353.65 | 15908.90 | 07-JUL-10:10 | 450856.34 | 11-FEB-24:00 |
WaterSystems:NaturalGas | 2906.61 | 15908.90 | 02-JAN-15:10 | 268914.08 | 14-FEB-22:00 |
Water Heater:WaterSystems:NaturalGas | 2906.61 | 15908.90 | 02-JAN-15:10 | 268914.08 | 14-FEB-22:00 |
Heating:NaturalGas | 447.03 | 0.00 | 20-JAN-12:50 | 257145.12 | 12-FEB-07:10 |
Boiler:Heating:NaturalGas | 447.03 | 0.00 | 20-JAN-12:50 | 257145.12 | 12-FEB-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 5250.90 | -64.34 | 04-DEC-20:30 | 735089.29 | 23-AUG-21:00 |
PlantLoopCoolingDemand:HVAC | 5250.90 | -64.34 | 04-DEC-20:30 | 735089.29 | 23-AUG-21:00 |
CoolingCoils:PlantLoopCoolingDemand | 5250.90 | -64.34 | 04-DEC-20:30 | 735089.29 | 23-AUG-21:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 23-FEB-02:30 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 23-FEB-02:30 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 31-JAN-07:30 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 31-JAN-07:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 26914.12 | 135149.25 | 23-MAR-13:10 | 2755547.58 | 23-AUG-20:50 |
EnergyTransfer:Building | 5409.50 | 59902.87 | 31-OCT-09:00 | 351789.81 | 07-JUL-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 723.08 | 8496.08 | 07-NOV-02:40 | 36216.23 | 08-JUL-10:50 |
Refrigeration:EnergyTransfer | 185.22 | 3999.87 | 12-FEB-04:00 | 10654.18 | 17-NOV-07:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.61 | 1999.93 | 12-FEB-04:00 | 5327.09 | 17-NOV-07:50 |
General:Refrigeration:EnergyTransfer | 92.61 | 1999.93 | 12-FEB-04:00 | 5327.09 | 17-NOV-07:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.61 | 1999.93 | 12-FEB-04:00 | 5327.09 | 17-NOV-07:50 |
EnergyTransfer:Plant | 13464.69 | 16236.42 | 04-MAR-04:00 | 1697135.45 | 23-AUG-21:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.66 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 70.95 | 1752.70 | 12-FEB-04:10 | 2683.79 | 31-OCT-09:10 |
EnergyTransfer:Zone:BASEMENT | 413.93 | 2459.52 | 28-JAN-23:00 | 26004.23 | 25-OCT-19:30 |
Heating:EnergyTransfer | 115.57 | 0.00 | 01-JAN-08:10 | 99741.86 | 07-JAN-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.03 | 0.00 | 01-JAN-00:10 | 997.71 | 10-APR-06:30 |
General:Heating:EnergyTransfer | 115.57 | 0.00 | 01-JAN-08:10 | 99741.86 | 07-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.03 | 0.00 | 01-JAN-00:10 | 997.71 | 10-APR-06:30 |
Cooling:EnergyTransfer | 5201.32 | 46063.43 | 28-JAN-23:00 | 349093.92 | 07-JUL-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 413.90 | 2166.56 | 28-JAN-23:00 | 26004.23 | 25-OCT-19:30 |
General:Cooling:EnergyTransfer | 5201.32 | 46063.43 | 28-JAN-23:00 | 349093.92 | 07-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 413.90 | 2166.56 | 28-JAN-23:00 | 26004.23 | 25-OCT-19:30 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 42.12 | 0.03 | 14-JAN-23:10 | 3230.34 | 10-OCT-13:30 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.81 | 0.00 | 01-JAN-00:10 | 1669.16 | 12-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.81 | 0.00 | 01-JAN-00:10 | 1669.16 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 41.32 | 0.00 | 01-JAN-16:00 | 3230.34 | 10-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 41.32 | 0.00 | 01-JAN-16:00 | 3230.34 | 10-OCT-13:30 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 38.52 | 26.86 | 31-OCT-09:00 | 2375.39 | 18-AUG-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 128.32 | 15-JAN-16:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 128.32 | 15-JAN-16:00 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 38.52 | 0.00 | 31-OCT-09:00 | 2375.39 | 18-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 38.52 | 0.00 | 31-OCT-09:00 | 2375.39 | 18-AUG-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 33.64 | 0.05 | 03-FEB-10:00 | 2411.94 | 07-JUL-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.14 | 0.00 | 01-JAN-00:10 | 457.18 | 04-FEB-16:40 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.14 | 0.00 | 01-JAN-00:10 | 457.18 | 04-FEB-16:40 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 33.50 | 0.00 | 06-JAN-02:10 | 2411.94 | 07-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 33.50 | 0.00 | 06-JAN-02:10 | 2411.94 | 07-JUL-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 15.44 | 0.02 | 18-JAN-14:40 | 946.17 | 07-JUL-21:00 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.25 | 0.00 | 01-JAN-00:10 | 377.54 | 12-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.25 | 0.00 | 01-JAN-00:10 | 377.54 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 15.19 | 0.00 | 03-JAN-10:10 | 946.17 | 07-JUL-21:00 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 15.19 | 0.00 | 03-JAN-10:10 | 946.17 | 07-JUL-21:00 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 604.00 | 6471.62 | 07-OCT-04:30 | 39296.52 | 07-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 556.51 | 21-OCT-03:20 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 556.51 | 21-OCT-03:20 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 604.00 | 6471.62 | 07-OCT-04:30 | 39296.52 | 07-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 604.00 | 6471.62 | 07-OCT-04:30 | 39296.52 | 07-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 227.15 | 24.85 | 10-JAN-09:30 | 12477.98 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.02 | 0.00 | 01-JAN-00:10 | 770.38 | 14-DEC-09:30 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.02 | 0.00 | 01-JAN-00:10 | 770.38 | 14-DEC-09:30 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 227.13 | 0.00 | 09-JAN-09:10 | 12477.98 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 227.13 | 0.00 | 09-JAN-09:10 | 12477.98 | 18-AUG-21:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 788.74 | 934.96 | 31-OCT-09:00 | 43944.65 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 2299.83 | 07-OCT-05:40 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 2299.83 | 07-OCT-05:40 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 788.71 | 934.96 | 31-OCT-09:00 | 43944.65 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 788.71 | 934.96 | 31-OCT-09:00 | 43944.65 | 18-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 69.09 | 0.08 | 01-MAR-22:30 | 10478.69 | 18-AUG-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 11.05 | 0.00 | 01-JAN-08:10 | 6395.40 | 07-JAN-19:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 11.05 | 0.00 | 01-JAN-08:10 | 6395.40 | 07-JAN-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 58.04 | 0.00 | 01-JAN-00:10 | 10478.69 | 18-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 58.04 | 0.00 | 01-JAN-00:10 | 10478.69 | 18-AUG-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 66.97 | 0.05 | 21-MAR-03:30 | 10420.66 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 14.59 | 0.00 | 01-JAN-08:10 | 7084.13 | 12-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 14.59 | 0.00 | 01-JAN-08:10 | 7084.13 | 12-FEB-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 52.37 | 0.00 | 01-JAN-00:10 | 10420.66 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 52.37 | 0.00 | 01-JAN-00:10 | 10420.66 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 404.67 | 0.87 | 26-JAN-05:40 | 45031.58 | 10-OCT-13:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 5.84 | 0.00 | 01-JAN-07:10 | 23041.99 | 12-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 5.84 | 0.00 | 01-JAN-07:10 | 23041.99 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 398.83 | 0.00 | 01-JAN-00:10 | 45031.58 | 10-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 398.83 | 0.00 | 01-JAN-00:10 | 45031.58 | 10-OCT-13:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 483.05 | 0.67 | 20-NOV-18:00 | 66626.76 | 08-JUL-15:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 35.65 | 0.00 | 01-JAN-00:10 | 44449.14 | 07-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 35.65 | 0.00 | 01-JAN-00:10 | 44449.14 | 07-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 447.40 | 0.00 | 01-JAN-16:30 | 66626.76 | 08-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 447.40 | 0.00 | 01-JAN-16:30 | 66626.76 | 08-JUL-15:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 69.12 | 0.11 | 29-NOV-21:50 | 9212.60 | 07-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 10.97 | 0.00 | 01-JAN-08:10 | 6501.20 | 07-JAN-19:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 10.97 | 0.00 | 01-JAN-08:10 | 6501.20 | 07-JAN-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 58.15 | 0.00 | 01-JAN-00:10 | 9212.60 | 07-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 58.15 | 0.00 | 01-JAN-00:10 | 9212.60 | 07-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 66.81 | 0.09 | 01-MAR-17:50 | 9338.51 | 07-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 14.43 | 0.00 | 01-JAN-08:10 | 6682.29 | 07-JAN-19:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 14.43 | 0.00 | 01-JAN-08:10 | 6682.29 | 07-JAN-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 52.37 | 0.00 | 01-JAN-00:10 | 9338.51 | 07-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 52.37 | 0.00 | 01-JAN-00:10 | 9338.51 | 07-JUL-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 194.44 | 0.76 | 04-FEB-09:40 | 12478.08 | 18-AUG-19:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.55 | 0.00 | 01-JAN-00:10 | 2880.62 | 07-JAN-17:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.55 | 0.00 | 01-JAN-00:10 | 2880.62 | 07-JAN-17:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 193.90 | 0.00 | 03-JAN-09:10 | 12478.08 | 18-AUG-19:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 193.90 | 0.00 | 03-JAN-09:10 | 12478.08 | 18-AUG-19:10 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 18.47 | 0.01 | 19-JAN-23:00 | 2850.79 | 18-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.50 | 0.00 | 01-JAN-08:10 | 2041.41 | 07-JAN-19:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.50 | 0.00 | 01-JAN-08:10 | 2041.41 | 07-JAN-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.97 | 0.00 | 01-JAN-00:10 | 2850.79 | 18-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.97 | 0.00 | 01-JAN-00:10 | 2850.79 | 18-AUG-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 18.31 | 0.00 | 05-OCT-01:40 | 2776.24 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.72 | 0.00 | 01-JAN-08:10 | 2272.95 | 12-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.72 | 0.00 | 01-JAN-08:10 | 2272.95 | 12-FEB-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 12.59 | 0.00 | 01-JAN-00:10 | 2776.24 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 12.59 | 0.00 | 01-JAN-00:10 | 2776.24 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 96.56 | 0.86 | 31-JAN-03:50 | 13561.39 | 25-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 9.95 | 0.00 | 01-JAN-08:10 | 9299.89 | 07-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 9.95 | 0.00 | 01-JAN-08:10 | 9299.89 | 07-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 86.61 | 0.00 | 01-JAN-00:10 | 13561.39 | 25-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 86.61 | 0.00 | 01-JAN-00:10 | 13561.39 | 25-SEP-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 449.08 | 3258.89 | 31-OCT-09:00 | 23978.93 | 07-JUL-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 241.02 | 14-NOV-23:40 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 241.02 | 14-NOV-23:40 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 449.07 | 3258.89 | 31-OCT-09:00 | 23978.93 | 07-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 449.07 | 3258.89 | 31-OCT-09:00 | 23978.93 | 07-JUL-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 486.44 | 4257.49 | 28-JAN-23:00 | 25154.35 | 07-JUL-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 228.25 | 14-NOV-23:40 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 228.25 | 14-NOV-23:40 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 486.44 | 4257.49 | 28-JAN-23:00 | 25154.35 | 07-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 486.44 | 4257.49 | 28-JAN-23:00 | 25154.35 | 07-JUL-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 49.93 | 13-OCT-03:00 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 49.93 | 13-OCT-03:00 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 630.47 | 6318.51 | 07-NOV-02:40 | 31151.59 | 08-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 630.47 | 6318.51 | 07-NOV-02:40 | 31151.59 | 08-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 99.87 | 0.21 | 17-JAN-15:50 | 7085.04 | 07-JUL-18:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.03 | 0.00 | 01-JAN-00:10 | 2946.16 | 12-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.03 | 0.00 | 01-JAN-00:10 | 2946.16 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 98.84 | 0.00 | 03-JAN-09:10 | 7085.04 | 07-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 98.84 | 0.00 | 03-JAN-09:10 | 7085.04 | 07-JUL-18:10 |
PlantLoopHeatingDemand:Facility | 990.56 | 7487.70 | 03-AUG-02:20 | 254688.61 | 12-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 671.59 | 7487.70 | 03-AUG-02:20 | 51939.98 | 02-FEB-08:00 |
WaterSystems:PlantLoopHeatingDemand | 671.59 | 7487.70 | 03-AUG-02:20 | 51939.98 | 02-FEB-08:00 |
General:WaterSystems:PlantLoopHeatingDemand | 671.59 | 7487.70 | 03-AUG-02:20 | 51939.98 | 02-FEB-08:00 |
EnergyTransfer:HVAC | 8039.93 | 11.84 | 13-MAY-07:20 | 839819.18 | 06-JUL-18:20 |
HeatingCoils:EnergyTransfer | 318.97 | 0.00 | 20-JAN-12:50 | 214593.96 | 12-FEB-07:10 |
PlantLoopHeatingDemand:HVAC | 318.97 | 0.00 | 20-JAN-12:50 | 214593.96 | 12-FEB-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 318.97 | 0.00 | 20-JAN-12:50 | 214593.96 | 12-FEB-07:10 |
CoolingCoils:EnergyTransfer | 5250.90 | -64.34 | 04-DEC-20:30 | 735089.29 | 23-AUG-21:00 |
HeatRecoveryForHeating:EnergyTransfer | 1566.19 | 0.00 | 19-JAN-10:20 | 452726.35 | 12-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 903.87 | 0.00 | 01-JAN-00:10 | 247655.20 | 07-JUL-12:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 671.59 | 7487.70 | 03-AUG-02:20 | 51939.98 | 02-FEB-08:00 |
WaterUse:WaterSystems:EnergyTransfer | 671.59 | 7487.70 | 03-AUG-02:20 | 51939.98 | 02-FEB-08:00 |
Boilers:EnergyTransfer | 315.15 | 0.00 | 20-JAN-12:50 | 210228.39 | 12-FEB-07:10 |
Chillers:EnergyTransfer | 5371.56 | 0.00 | 01-JAN-00:10 | 740848.06 | 23-AUG-21:00 |
HeatRejection:EnergyTransfer | 7013.77 | 0.00 | 01-JAN-00:10 | 923185.90 | 23-AUG-21:00 |
General:HeatRejection:EnergyTransfer | 7013.77 | 0.00 | 01-JAN-00:10 | 923185.90 | 23-AUG-21:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.031 | -413.906 | 0.000 | 0.000 | 141.438 | 173.462 | 150.255 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -51.280 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.807 | -41.318 | 0.000 | 0.000 | 15.110 | 8.614 | 10.186 | 18.649 | 0.000 | 0.349 | 0.001 | 0.000 | -8.874 | 0.000 | -2.536 | -0.986 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.006 | -38.519 | 0.000 | 0.000 | 16.732 | 9.975 | 11.795 | 0.000 | 0.000 | 0.140 | 0.936 | 0.000 | 0.000 | 0.000 | -1.064 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.141 | -33.500 | 0.000 | 0.000 | 3.655 | 16.635 | 12.471 | 0.000 | 0.000 | 0.336 | 2.627 | 0.000 | 0.000 | 0.000 | -2.365 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.247 | -15.192 | 0.000 | 0.000 | 2.835 | 2.785 | 3.598 | 0.000 | 0.000 | 0.197 | 6.874 | 0.000 | 0.000 | 0.000 | -1.343 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.004 | -604.003 | 0.000 | 0.000 | 11.268 | 4.368 | 658.131 | 0.000 | 0.000 | 0.508 | 0.000 | 0.000 | 0.000 | 0.000 | -3.545 | -66.732 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.024 | -227.130 | 0.000 | 0.000 | 187.041 | 17.992 | 14.341 | 51.485 | 0.000 | 0.760 | 0.000 | 0.000 | -27.407 | 0.000 | -6.249 | -10.856 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.031 | -788.717 | 0.000 | 0.000 | 548.828 | 121.998 | 148.998 | 68.421 | 0.000 | 2.215 | 0.000 | 0.000 | -36.886 | 0.000 | -18.292 | -46.596 |
ROOM_1_FLR_3 | 14.065 | -44.483 | 0.000 | -16.571 | 0.000 | 0.000 | 9.715 | 6.366 | 12.292 | 39.206 | 0.000 | 1.338 | 3.475 | 0.000 | -19.212 | 0.000 | -6.192 | -0.000 |
ROOM_2_FLR_3 | 18.161 | -39.617 | 0.000 | -16.324 | 0.000 | 0.000 | 9.739 | 6.366 | 12.291 | 30.535 | 0.000 | 1.342 | 3.677 | 0.000 | -20.087 | 0.000 | -6.084 | -0.001 |
ROOM_3_MULT19_FLR_3 | 9.610 | -145.574 | 0.000 | -257.015 | 0.000 | 0.000 | 0.000 | 76.021 | 228.754 | 225.135 | 0.000 | 4.646 | 23.172 | 0.000 | -110.929 | 0.000 | -53.819 | -0.004 |
ROOM_4_MULT19_FLR_3 | 64.933 | -256.561 | 0.000 | -220.115 | 0.000 | 0.000 | 185.241 | 76.042 | 228.817 | 94.867 | 0.000 | 9.453 | 0.000 | 0.000 | -111.763 | 0.000 | -40.723 | -30.189 |
ROOM_5_FLR_3 | 13.974 | -44.486 | 0.000 | -16.669 | 0.000 | 0.000 | 9.707 | 6.366 | 12.292 | 38.990 | 0.000 | 1.333 | 3.269 | 0.000 | -18.549 | 0.000 | -6.228 | -0.001 |
ROOM_6_FLR_3 | 17.994 | -39.506 | 0.000 | -16.427 | 0.000 | 0.000 | 9.731 | 6.366 | 12.291 | 29.810 | 0.000 | 1.335 | 3.446 | 0.000 | -18.922 | 0.000 | -6.116 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.546 | -193.898 | 0.000 | 0.000 | 115.222 | 109.603 | 0.000 | 34.546 | 0.000 | 0.988 | 0.000 | 0.000 | -26.048 | 0.000 | -7.333 | -33.625 |
ROOM_1_FLR_6 | 5.414 | -10.775 | 0.000 | -4.113 | 0.000 | 0.000 | 2.432 | 1.592 | 3.073 | 9.751 | 0.000 | 0.337 | 0.001 | 0.000 | -4.733 | 0.000 | -1.572 | -1.406 |
ROOM_2_FLR_6 | 6.771 | -9.593 | 0.000 | -4.054 | 0.000 | 0.000 | 2.438 | 1.591 | 3.073 | 7.608 | 0.000 | 0.338 | 0.000 | 0.000 | -4.947 | 0.000 | -1.545 | -1.680 |
ROOM_3_MULT9_FLR_6 | 13.743 | -63.392 | 0.000 | -27.003 | 0.000 | 0.000 | 21.807 | 9.005 | 27.097 | 49.701 | 0.000 | 1.730 | 0.002 | 0.000 | -22.002 | 0.000 | -8.257 | -2.429 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.001 | -449.079 | 0.000 | 0.000 | 317.017 | 34.796 | 175.857 | 8.740 | 0.000 | 0.440 | 0.000 | 0.000 | -16.941 | 0.000 | -4.333 | -66.499 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -486.441 | 0.000 | 0.000 | 315.796 | 34.796 | 175.857 | 8.500 | 0.000 | 0.436 | 0.000 | 0.000 | -17.520 | 0.000 | -4.382 | -27.043 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -630.453 | 0.000 | 0.000 | 28.305 | 13.327 | 550.372 | 17.748 | 0.000 | 0.387 | 36.272 | 0.000 | -12.014 | 0.000 | -3.944 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 1.025 | -98.842 | 0.000 | 0.000 | 30.654 | 28.999 | 0.000 | 16.398 | 0.000 | 0.409 | 36.277 | 0.000 | -11.704 | 0.000 | -3.217 | -0.000 |
Total Facility | 164.664 | -653.988 | 2.864 | -4599.289 | 0.000 | 0.000 | 1984.707 | 767.065 | 2451.839 | 750.092 | 0.000 | 29.017 | 120.028 | 0.000 | -488.537 | 0.000 | -189.137 | -339.329 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-OCT-05:32 | 0.00 | 0.00 | 0.00 | -37130.60 | 0.00 | 0.00 | 5160.69 | 6304.56 | 5323.05 | 0.00 | 0.00 | 0.00 | 20342.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 10-OCT-13:30 | 0.00 | 0.00 | 0.00 | -3230.78 | 0.00 | 0.00 | 150.60 | 195.67 | 252.59 | 4142.99 | 0.00 | 54.06 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1565.13 |
RETAIL_2_FLR_1 | 18-AUG-21:00 | 0.00 | 0.00 | 0.00 | -2375.42 | 0.00 | 0.00 | 697.61 | 725.08 | 752.15 | 0.00 | 0.00 | 30.30 | 170.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 07-JUL-20:00 | 0.00 | 0.00 | 0.00 | -2412.02 | 0.00 | 0.00 | 129.08 | 1360.40 | 839.45 | 0.00 | 0.00 | 71.61 | 11.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 14-DEC-08:48 | 0.00 | 0.00 | 0.00 | -1054.02 | 0.00 | 0.00 | 65.14 | 101.21 | 127.45 | 0.00 | 0.00 | 0.00 | 860.25 | 0.00 | -0.00 | 0.00 | -100.03 | 0.00 |
LAUNDRY_FLR_1 | 05-APR-20:47 | 0.00 | 0.00 | 0.00 | -52273.45 | 0.00 | 0.00 | 406.84 | 317.52 | 41967.83 | 0.00 | 0.00 | 0.00 | 9909.04 | 0.00 | -0.00 | 0.00 | -327.78 | 0.00 |
CAFE_FLR_1 | 24-NOV-00:53 | 0.00 | 0.00 | 0.00 | -19354.77 | 0.00 | 0.00 | 9056.56 | 391.53 | 304.82 | 0.00 | 0.00 | 0.00 | 12224.72 | 0.00 | -2258.81 | 0.00 | -364.05 | 0.00 |
LOBBY_FLR_1 | 24-NOV-00:53 | 0.00 | 0.00 | 0.00 | -68992.13 | 0.00 | 0.00 | 26758.08 | 2281.15 | 3167.12 | 0.00 | 0.00 | 0.00 | 40904.70 | 0.00 | -3017.86 | 0.00 | -1101.07 | 0.00 |
ROOM_1_FLR_3 | 10-APR-15:01 | 0.00 | -11417.14 | 0.00 | -719.50 | 0.00 | 0.00 | 235.28 | 137.21 | 273.93 | 7328.84 | 0.00 | 76.12 | 4085.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 10-APR-15:01 | 0.00 | -11188.87 | 0.00 | -713.39 | 0.00 | 0.00 | 235.29 | 137.19 | 273.90 | 6328.17 | 0.00 | 78.31 | 4849.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 10-OCT-13:30 | 0.00 | -34580.32 | 0.00 | -10453.73 | 0.00 | 0.00 | 0.00 | 1638.34 | 5097.90 | 50538.64 | 0.00 | 751.01 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -12991.84 |
ROOM_4_MULT19_FLR_3 | 10-JUN-18:02 | 0.00 | -70691.07 | 0.00 | -9796.41 | 0.00 | 0.00 | 5406.87 | 5852.82 | 9610.21 | 11927.20 | 0.00 | 804.20 | 46886.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 10-APR-15:01 | 0.00 | -10236.52 | 0.00 | -717.48 | 0.00 | 0.00 | 235.29 | 137.21 | 273.93 | 2530.66 | 0.00 | 76.87 | 7700.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 10-APR-15:01 | 0.00 | -10070.35 | 0.00 | -712.09 | 0.00 | 0.00 | 235.29 | 137.19 | 273.90 | 1528.46 | 0.00 | 78.79 | 8528.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 18-AUG-19:10 | 0.00 | 0.00 | 0.00 | -12478.25 | 0.00 | 0.00 | 4080.34 | 8963.13 | 0.00 | 1288.52 | 0.00 | 264.78 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2118.51 |
ROOM_1_FLR_6 | 10-APR-15:01 | 0.00 | -3002.68 | 0.00 | -180.10 | 0.00 | 0.00 | 58.82 | 34.30 | 68.48 | 1816.18 | 0.00 | 18.56 | 1186.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 10-APR-15:01 | 0.00 | -2936.37 | 0.00 | -178.44 | 0.00 | 0.00 | 58.82 | 34.30 | 68.48 | 1568.71 | 0.00 | 19.15 | 1365.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 26-FEB-16:02 | 0.00 | -13452.09 | 0.00 | -1167.14 | 0.00 | 0.00 | 294.11 | 228.73 | 673.54 | 5795.03 | 0.00 | 43.34 | 7584.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 07-DEC-23:41 | 0.00 | 0.00 | 0.00 | -33165.65 | 0.00 | 0.00 | 15318.99 | 1031.35 | 6747.90 | 0.00 | 0.00 | 0.00 | 11799.56 | 0.00 | -1423.37 | 0.00 | -308.79 | 0.00 |
DINING_FLR_6 | 25-APR-23:59 | 0.00 | 0.00 | 0.00 | -37260.34 | 0.00 | 0.00 | 15642.46 | 687.57 | 2249.30 | 0.00 | 0.00 | 0.00 | 20302.38 | 0.00 | -1357.05 | 0.00 | -264.32 | 0.00 |
KITCHEN_FLR_6 | 01-DEC-18:47 | 0.00 | 0.00 | 0.00 | -38453.75 | 0.00 | 0.00 | 751.12 | 726.55 | 26759.11 | 0.00 | 0.00 | 0.00 | 11547.08 | 0.00 | -1043.74 | 0.00 | -286.37 | 0.00 |
CORRIDOR_FLR_6 | 07-JUL-18:03 | 0.00 | 0.00 | 0.00 | -7091.83 | 0.00 | 0.00 | 1079.62 | 2108.02 | 0.00 | 1089.99 | 0.00 | 131.98 | 2682.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-AUG-18:02 | 0.00 | -150067.38 | 0.00 | -224929.45 | 0.00 | 0.00 | 73809.31 | 53571.31 | 122326.88 | 45696.69 | 0.00 | 6621.62 | 72971.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 14-NOV-23:39 | 0.00 | 0.00 | 3506.38 | 0.00 | 0.00 | 0.00 | 6664.85 | 4728.51 | 4258.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19158.18 |
RETAIL_1_FLR_1 | 14-DEC-08:49 | 0.00 | 0.00 | 1767.55 | 0.00 | 0.00 | 0.00 | 358.03 | 313.07 | 360.84 | 357.23 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -181.99 | -2974.74 |
RETAIL_2_FLR_1 | 30-NOV-18:17 | 0.00 | 0.00 | 297.98 | 0.00 | 0.00 | 0.00 | 500.55 | 543.81 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -70.23 | -1857.11 |
MECH_FLR_1 | 04-FEB-16:37 | 0.00 | 0.00 | 1371.54 | 0.00 | 0.00 | 0.00 | 65.77 | 377.89 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -153.52 | -1970.94 |
STORAGE_FLR_1 | 04-FEB-16:37 | 0.00 | 0.00 | 761.55 | 0.00 | 0.00 | 0.00 | 50.59 | 63.26 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -88.58 | -876.04 |
LAUNDRY_FLR_1 | 14-OCT-03:59 | 0.00 | 0.00 | 2313.07 | 0.00 | 0.00 | 0.00 | 608.17 | 39.69 | 9326.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -215.16 | -12071.96 |
CAFE_FLR_1 | 30-NOV-18:17 | 0.00 | 0.00 | 2080.52 | 0.00 | 0.00 | 0.00 | 5860.81 | 1174.60 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2150.21 | 0.00 | -389.82 | -7287.17 |
LOBBY_FLR_1 | 15-NOV-00:06 | 0.00 | 0.00 | 5518.46 | 0.00 | 0.00 | 0.00 | 26427.67 | 2281.15 | 3167.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3512.99 | 0.00 | -1298.57 | -32582.85 |
ROOM_1_FLR_3 | 12-FEB-09:01 | 10004.34 | 289.30 | 0.00 | -289.30 | 0.00 | 0.00 | 163.33 | 274.41 | 653.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1276.52 | 0.00 | -903.70 | -8915.08 |
ROOM_2_FLR_3 | 12-FEB-09:01 | 10069.12 | 284.66 | 0.00 | -284.66 | 0.00 | 0.00 | 163.33 | 274.38 | 653.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2901.67 | 0.00 | -901.70 | -7356.60 |
ROOM_3_MULT19_FLR_3 | 12-FEB-06:00 | 23041.79 | 3320.68 | 0.00 | -3320.68 | 0.00 | 0.00 | 0.00 | 643.59 | 3921.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20957.33 | 0.00 | -5030.65 | -1618.85 |
ROOM_4_MULT19_FLR_3 | 07-JAN-16:02 | 56970.71 | 3734.95 | 0.00 | -3734.95 | 0.00 | 0.00 | 3103.17 | 1931.47 | 5687.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -12085.61 | 0.00 | -3626.04 | -51981.37 |
ROOM_5_FLR_3 | 07-JAN-19:01 | 9725.12 | 286.75 | 0.00 | -286.75 | 0.00 | 0.00 | 353.87 | 490.02 | 516.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3054.02 | 0.00 | -736.04 | -7295.21 |
ROOM_6_FLR_3 | 07-JAN-19:01 | 9729.52 | 285.87 | 0.00 | -285.87 | 0.00 | 0.00 | 353.87 | 489.96 | 516.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3075.12 | 0.00 | -735.64 | -7278.78 |
CORRIDOR_FLR_3 | 04-FEB-16:37 | 0.00 | 0.00 | 5339.26 | 0.00 | 0.00 | 0.00 | 2078.69 | 2489.76 | 0.00 | 1459.01 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -473.94 | -10892.78 |
ROOM_1_FLR_6 | 12-FEB-09:01 | 2952.67 | 72.60 | 0.00 | -72.60 | 0.00 | 0.00 | 40.83 | 68.60 | 163.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -324.89 | 0.00 | -226.54 | -2673.99 |
ROOM_2_FLR_6 | 12-FEB-09:01 | 2968.70 | 71.43 | 0.00 | -71.43 | 0.00 | 0.00 | 40.83 | 68.59 | 163.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -731.17 | 0.00 | -226.03 | -2284.22 |
ROOM_3_MULT9_FLR_6 | 07-JAN-19:01 | 13702.80 | 465.21 | 0.00 | -465.21 | 0.00 | 0.00 | 796.23 | 693.10 | 1138.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3528.20 | 0.00 | -850.78 | -11951.20 |
BANQUET_FLR_6 | 14-NOV-23:39 | 0.00 | 0.00 | 1687.25 | 0.00 | 0.00 | 0.00 | 15642.24 | 1031.35 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1358.92 | 0.00 | -296.11 | -23453.70 |
DINING_FLR_6 | 14-NOV-23:39 | 0.00 | 0.00 | 1597.86 | 0.00 | 0.00 | 0.00 | 15642.14 | 1031.35 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1386.95 | 0.00 | -297.15 | -23335.14 |
KITCHEN_FLR_6 | 13-OCT-03:00 | 0.00 | 0.00 | 249.69 | 0.00 | 0.00 | 0.00 | 1516.11 | 121.09 | 5415.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1088.61 | 0.00 | -248.93 | -5965.34 |
CORRIDOR_FLR_6 | 12-FEB-06:00 | 0.00 | 0.00 | 2946.16 | 0.00 | 0.00 | 0.00 | 1283.30 | 527.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2323.63 | 0.00 | -543.12 | -1889.71 |
Total Facility | 07-JAN-16:02 | 53170.48 | 81650.16 | 5811.94 | -81650.16 | 0.00 | 0.00 | 36373.53 | 17498.58 | 78718.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -46670.89 | 0.00 | -17745.15 | -127156.74 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 22.0399 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 21.9165 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6591 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6591 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5583 | 2.5583 | 1.3533 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3273 | 0.3273 | 0.1731 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2495 | 0.2495 | 0.1320 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2501 | 0.2501 | 0.1323 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1213 | 0.1213 | 0.0642 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3899 | 3.3899 | 1.7933 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3980 | 1.3980 | 0.7396 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.6621 | 4.6621 | 2.4662 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4302 | 1.4302 | 0.7566 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2425 | 2.2425 | 1.1863 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3504 | 2.3504 | 1.2434 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3121 | 2.3121 | 1.2231 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7481 | 0.7481 | 0.3957 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 22.0399 | 21.9165 | 22.0399 | 11.6591 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3533 | 1.3533 | 1.3533 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1731 | 0.1731 | 0.1731 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1320 | 0.1320 | 0.1320 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1323 | 0.1323 | 0.1323 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0642 | 0.0642 | 0.0642 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7933 | 1.7933 | 1.7933 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7396 | 0.7396 | 0.7396 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4662 | 2.4662 | 2.4662 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7566 | 0.7566 | 0.7566 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1863 | 1.1863 | 1.1863 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2434 | 1.2434 | 1.2434 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2231 | 1.2231 | 1.2231 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3957 | 0.3957 | 0.3957 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6591 | 11.6591 | 11.6591 | 11.6591 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 1.17 |
Number of hours cooling loads not met | 179.33 |
Number of hours not met | 180.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 447.03 | 257145.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1642.20 | 199939.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 767.06 | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 242.92 | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.56 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 32.45 | 1868.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 584.52 | 43378.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 142.73 | 7723.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 206.03 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4738.76 | 2906.61 | 268914.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.49 | 2024.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.69 | 1244.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1807.29 | 6134.98 |
Natural Gas | 1788.84 | 5142.49 |
Additional | 0.00 | 0.00 |
Total | 3596.13 | 11277.47 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 67.61 |
Space Heating | 0.00 |
Space Cooling | 144.75 |
Fans (All) | 51.52 |
Service Water Heating | 8.00 |
Receptacle Equipment | 153.81 |
Miscellaneous (All) | 540.75 |
Subtotal | 540.75 |
Natural Gas [MJ/m2] | |
Space Heating | 39.40 |
Service Water Heating | 256.20 |
Miscellaneous (All) | 453.27 |
Subtotal | 453.27 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.80 |
Space Heating | 3.96 |
Space Cooling | 14.56 |
Fans (All) | 5.18 |
Service Water Heating | 26.58 |
Receptacle Equipment | 31.34 |
Miscellaneous | 11.58 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2667. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 2678. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 3061. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8759.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.33 | 0.00 | 0.00 | 0.00 |
Average | 8759.98 | 0.02 | 0.00 | 0.00 | 0.00 |
Sum | 192719.50 | 0.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37202.17 | 0.83 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108265.83 | 3.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 3.17 | 0.00 | 0.00 | 0.00 |
Average | 288886.86 | 0.18 | 0.00 | 0.00 | 0.00 |
Sum | 6355511.00 | 4.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8622.33 | 137.67 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 7324.83 | 1435.17 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 7492.50 | 1267.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8571.33 | 188.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 7422.83 | 1337.17 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 7569.00 | 1191.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8617.67 | 142.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7324.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1435.17 | 0.00 | 0.00 | 0.00 |
Average | 8499.89 | 260.11 | 0.00 | 0.00 | 0.00 |
Sum | 186997.67 | 5722.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 57671.17 | 1484.83 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 539572.33 | 170844.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1677674.50 | 437754.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 97084.00 | 3274.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 974218.83 | 271496.17 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1000526.83 | 245188.17 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 107234.33 | 1034.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1677674.50 | 437754.50 | 0.00 | 0.00 | 0.00 |
Average | 237474.45 | 51412.59 | 0.00 | 0.00 | 0.00 |
Sum | 5224438.00 | 1131077.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:42
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.325665E+11 | 32190.18 | 28-JAN-23:01 | 5.50 | 1.04 | 0.769741E+10 | 4840.13 | 12-JAN-22:30 | 5.50 | 1.04 |
February | 0.275303E+11 | 21252.33 | 04-FEB-16:33 | 7.07 | 1.24 | 0.660386E+10 | 4812.36 | 01-FEB-23:10 | 7.07 | 1.24 |
March | 0.283438E+11 | 20374.59 | 01-MAR-05:52 | 8.30 | 5.47 | 0.689557E+10 | 4483.22 | 01-MAR-22:10 | 11.02 | 10.13 |
April | 0.251525E+11 | 19486.03 | 25-APR-23:59 | 7.80 | 5.02 | 0.624748E+10 | 4124.24 | 05-APR-21:10 | 7.80 | 5.02 |
May | 0.287837E+11 | 20290.52 | 11-MAY-06:09 | 8.17 | 5.64 | 0.674682E+10 | 4244.17 | 26-MAY-21:19 | 18.30 | 17.97 |
June | 0.320676E+11 | 15838.03 | 10-JUN-18:02 | 28.62 | 13.87 | 0.713559E+10 | 4616.47 | 16-JUN-21:19 | 23.70 | 21.00 |
July | 0.357088E+11 | 16463.96 | 20-JUL-18:10 | 32.12 | 22.73 | 0.773198E+10 | 4837.02 | 27-JUL-21:19 | 20.60 | 20.26 |
August | 0.386988E+11 | 19989.16 | 31-AUG-21:00 | 21.70 | 20.13 | 0.809114E+10 | 4837.04 | 23-AUG-21:19 | 21.70 | 20.13 |
September | 0.409507E+11 | 23234.19 | 28-SEP-21:00 | 15.60 | 13.52 | 0.793824E+10 | 4843.54 | 29-SEP-03:20 | 12.03 | 11.21 |
October | 0.433743E+11 | 37132.39 | 06-OCT-05:32 | 7.20 | 7.20 | 0.821511E+10 | 5006.52 | 25-OCT-22:19 | 5.40 | 3.94 |
November | 0.420367E+11 | 36579.39 | 30-NOV-07:11 | 6.10 | 5.46 | 0.794987E+10 | 5003.32 | 13-NOV-23:49 | 6.10 | 5.46 |
December | 0.386900E+11 | 35728.93 | 09-DEC-22:47 | 6.70 | 2.82 | 0.817071E+10 | 4963.26 | 21-DEC-22:19 | 5.60 | 3.83 |
Annual Sum or Average | 0.413904E+12 | 0.894238E+11 | ||||||||
Minimum of Months | 0.251525E+11 | 15838.03 | 5.50 | 1.04 | 0.624748E+10 | 4124.24 | 5.40 | 1.04 | ||
Maximum of Months | 0.433743E+11 | 37132.39 | 32.12 | 22.73 | 0.821511E+10 | 5006.52 | 23.70 | 21.00 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131296E+10 | 2182.80 | 29-JAN-09:53 | 8.90 | 3.56 | 0.627263E+09 | 399.63 | 31-JAN-22:19 | 14.13 | 10.68 |
February | 0.176070E+10 | 2580.96 | 04-FEB-16:33 | 7.07 | 1.24 | 0.579368E+09 | 452.69 | 28-FEB-22:30 | 18.10 | 10.49 |
March | 0.319037E+10 | 2389.54 | 30-MAR-14:10 | 27.80 | 17.74 | 0.677588E+09 | 491.05 | 30-MAR-21:30 | 23.35 | 16.68 |
April | 0.352462E+10 | 2898.66 | 15-APR-13:23 | 27.25 | 14.96 | 0.674245E+09 | 483.85 | 17-APR-21:30 | 20.00 | 13.99 |
May | 0.408152E+10 | 2222.68 | 16-MAY-18:10 | 28.22 | 17.07 | 0.730341E+09 | 491.81 | 18-MAY-21:40 | 22.07 | 16.54 |
June | 0.447069E+10 | 2469.36 | 13-JUN-18:15 | 31.67 | 21.94 | 0.758627E+09 | 491.83 | 05-JUN-21:19 | 31.67 | 21.94 |
July | 0.490621E+10 | 2835.48 | 07-JUL-18:15 | 33.70 | 23.11 | 0.793986E+09 | 491.83 | 21-JUL-23:19 | 26.50 | 20.50 |
August | 0.521281E+10 | 3092.82 | 19-AUG-13:40 | 33.70 | 23.70 | 0.812846E+09 | 491.83 | 25-AUG-21:19 | 25.93 | 18.45 |
September | 0.437982E+10 | 3066.19 | 24-SEP-12:40 | 28.70 | 19.86 | 0.736004E+09 | 491.83 | 15-SEP-21:19 | 28.70 | 19.86 |
October | 0.370571E+10 | 3230.34 | 10-OCT-13:30 | 28.85 | 20.88 | 0.701220E+09 | 491.82 | 10-OCT-21:19 | 21.10 | 18.73 |
November | 0.288456E+10 | 2504.25 | 08-NOV-13:40 | 20.20 | 9.59 | 0.635981E+09 | 439.11 | 08-NOV-22:19 | 13.33 | 6.86 |
December | 0.188743E+10 | 2285.73 | 10-DEC-13:00 | 15.60 | 7.72 | 0.637406E+09 | 440.75 | 12-DEC-22:30 | 18.30 | 14.75 |
Annual Sum or Average | 0.413174E+11 | 0.836487E+10 | ||||||||
Minimum of Months | 0.131296E+10 | 2182.80 | 7.07 | 1.24 | 0.579368E+09 | 399.63 | 13.33 | 6.86 | ||
Maximum of Months | 0.521281E+10 | 3230.34 | 33.70 | 23.70 | 0.812846E+09 | 491.83 | 31.67 | 21.94 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237860E+10 | 1988.95 | 16-JAN-21:46 | 6.70 | 1.44 | 0.775668E+09 | 536.37 | 31-JAN-22:30 | 13.75 | 10.50 |
February | 0.235509E+10 | 1981.96 | 24-FEB-23:22 | 6.95 | 2.53 | 0.729826E+09 | 569.51 | 27-FEB-22:30 | 15.00 | 8.33 |
March | 0.304732E+10 | 2116.50 | 15-MAR-03:28 | 8.30 | 4.50 | 0.875410E+09 | 569.53 | 30-MAR-23:19 | 21.13 | 15.63 |
April | 0.315620E+10 | 2149.96 | 25-APR-23:59 | 7.80 | 5.02 | 0.869379E+09 | 569.53 | 19-APR-21:19 | 7.80 | 5.02 |
May | 0.349570E+10 | 2114.75 | 11-MAY-06:09 | 8.17 | 5.64 | 0.924150E+09 | 569.54 | 19-MAY-23:19 | 20.40 | 15.66 |
June | 0.373002E+10 | 2168.46 | 27-JUN-21:00 | 27.20 | 20.99 | 0.921296E+09 | 569.54 | 24-JUN-01:19 | 27.20 | 20.99 |
July | 0.398592E+10 | 2345.71 | 07-JUL-21:00 | 30.60 | 22.80 | 0.952263E+09 | 569.54 | 22-JUL-01:19 | 25.00 | 20.48 |
August | 0.407856E+10 | 2375.39 | 18-AUG-21:00 | 31.10 | 22.83 | 0.962956E+09 | 569.54 | 26-AUG-01:19 | 21.87 | 17.62 |
September | 0.354693E+10 | 2214.07 | 07-SEP-21:00 | 25.60 | 21.61 | 0.908493E+09 | 569.54 | 09-SEP-01:19 | 22.60 | 20.36 |
October | 0.323277E+10 | 2238.14 | 13-OCT-07:03 | 6.43 | 4.97 | 0.895173E+09 | 569.54 | 06-OCT-21:10 | 6.43 | 4.97 |
November | 0.285205E+10 | 2077.91 | 11-NOV-08:63 | 6.57 | 5.91 | 0.827725E+09 | 569.34 | 08-NOV-22:30 | 6.57 | 5.91 |
December | 0.265915E+10 | 2280.84 | 14-DEC-08:48 | 6.02 | 4.79 | 0.809339E+09 | 564.41 | 12-DEC-23:10 | 6.02 | 4.79 |
Annual Sum or Average | 0.385183E+11 | 0.104517E+11 | ||||||||
Minimum of Months | 0.235509E+10 | 1981.96 | 6.02 | 1.44 | 0.729826E+09 | 536.37 | 6.02 | 4.79 | ||
Maximum of Months | 0.407856E+10 | 2375.39 | 31.10 | 22.83 | 0.962956E+09 | 569.54 | 27.20 | 20.99 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112384E+10 | 1777.59 | 16-JAN-21:46 | 6.70 | 1.44 | 0.153170E+09 | 101.23 | 20-JAN-22:10 | 11.52 | 8.16 |
February | 0.153834E+10 | 1761.16 | 24-FEB-23:22 | 6.95 | 2.53 | 0.142351E+09 | 108.28 | 28-FEB-22:10 | 18.63 | 10.80 |
March | 0.264686E+10 | 1963.87 | 15-MAR-03:28 | 8.30 | 4.50 | 0.167403E+09 | 115.11 | 30-MAR-21:19 | 23.53 | 16.75 |
April | 0.286516E+10 | 2021.57 | 25-APR-23:59 | 7.80 | 5.02 | 0.170716E+09 | 116.91 | 19-APR-21:10 | 7.80 | 5.02 |
May | 0.327937E+10 | 2026.64 | 11-MAY-06:09 | 8.17 | 5.64 | 0.187193E+09 | 120.45 | 31-MAY-21:19 | 22.07 | 18.80 |
June | 0.359756E+10 | 2119.66 | 28-JUN-20:00 | 27.80 | 22.66 | 0.192531E+09 | 120.45 | 05-JUN-21:19 | 27.80 | 22.66 |
July | 0.390537E+10 | 2411.94 | 07-JUL-20:00 | 31.10 | 23.22 | 0.200656E+09 | 120.45 | 24-JUL-21:19 | 26.33 | 20.14 |
August | 0.393767E+10 | 2353.95 | 18-AUG-20:00 | 31.70 | 22.32 | 0.202537E+09 | 120.45 | 25-AUG-21:19 | 25.93 | 18.45 |
September | 0.333743E+10 | 1999.47 | 07-SEP-20:00 | 27.20 | 22.45 | 0.186858E+09 | 120.45 | 11-SEP-21:19 | 22.97 | 20.08 |
October | 0.293476E+10 | 2143.11 | 13-OCT-07:03 | 6.43 | 4.97 | 0.175895E+09 | 117.39 | 19-OCT-21:10 | 17.12 | 15.78 |
November | 0.245037E+10 | 1990.49 | 11-NOV-08:63 | 6.57 | 5.91 | 0.159031E+09 | 109.10 | 03-NOV-21:10 | 6.57 | 5.91 |
December | 0.188361E+10 | 2217.62 | 14-DEC-08:48 | 6.02 | 4.79 | 0.155741E+09 | 106.88 | 13-DEC-22:10 | 6.02 | 4.79 |
Annual Sum or Average | 0.335003E+11 | 0.209408E+10 | ||||||||
Minimum of Months | 0.112384E+10 | 1761.16 | 6.02 | 1.44 | 0.142351E+09 | 101.23 | 6.02 | 4.79 | ||
Maximum of Months | 0.393767E+10 | 2411.94 | 31.70 | 23.22 | 0.202537E+09 | 120.45 | 27.80 | 22.66 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.340963E+09 | 715.62 | 25-JAN-18:41 | 5.18 | 1.39 | 0.117111E+09 | 74.08 | 31-JAN-22:49 | 12.98 | 10.12 |
February | 0.619202E+09 | 828.62 | 24-FEB-23:22 | 6.95 | 2.53 | 0.108129E+09 | 79.86 | 28-FEB-22:49 | 17.57 | 10.18 |
March | 0.123003E+10 | 948.36 | 15-MAR-03:28 | 8.30 | 4.50 | 0.126223E+09 | 84.99 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.135231E+10 | 963.69 | 25-APR-23:59 | 7.80 | 5.02 | 0.128620E+09 | 85.86 | 19-APR-21:40 | 7.80 | 5.02 |
May | 0.155369E+10 | 962.27 | 11-MAY-06:09 | 8.17 | 5.64 | 0.141170E+09 | 89.50 | 31-MAY-22:10 | 21.73 | 18.83 |
June | 0.167049E+10 | 821.72 | 25-JUN-10:33 | 29.80 | 23.29 | 0.146283E+09 | 92.66 | 14-JUN-21:19 | 29.80 | 23.29 |
July | 0.180156E+10 | 946.17 | 07-JUL-21:00 | 30.60 | 22.80 | 0.153166E+09 | 92.66 | 24-JUL-21:40 | 25.97 | 20.04 |
August | 0.180829E+10 | 920.66 | 18-AUG-21:00 | 31.10 | 22.83 | 0.154854E+09 | 92.66 | 18-AUG-23:19 | 28.53 | 23.21 |
September | 0.157522E+10 | 802.65 | 09-SEP-10:33 | 30.03 | 23.84 | 0.141270E+09 | 92.60 | 07-SEP-21:49 | 30.03 | 23.84 |
October | 0.138617E+10 | 1012.62 | 13-OCT-07:03 | 6.43 | 4.97 | 0.132585E+09 | 86.51 | 18-OCT-22:10 | 22.80 | 22.03 |
November | 0.112273E+10 | 945.19 | 11-NOV-08:63 | 6.57 | 5.91 | 0.119919E+09 | 80.25 | 03-NOV-22:10 | 6.57 | 5.91 |
December | 0.731758E+09 | 1054.04 | 14-DEC-08:48 | 6.02 | 4.79 | 0.118291E+09 | 78.34 | 13-DEC-23:10 | 6.02 | 4.79 |
Annual Sum or Average | 0.151924E+11 | 0.158762E+10 | ||||||||
Minimum of Months | 0.340963E+09 | 715.62 | 5.18 | 1.39 | 0.108129E+09 | 74.08 | 6.02 | 4.79 | ||
Maximum of Months | 0.180829E+10 | 1054.04 | 31.10 | 23.84 | 0.154854E+09 | 92.66 | 30.03 | 23.84 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.474296E+11 | 50479.97 | 12-JAN-21:43 | 6.10 | 1.92 | 0.578898E+09 | 494.64 | 28-JAN-23:10 | 5.50 | 1.04 |
February | 0.438667E+11 | 50606.29 | 06-FEB-20:43 | 4.90 | 3.67 | 0.526694E+09 | 486.02 | 23-FEB-23:10 | 7.62 | 2.26 |
March | 0.505811E+11 | 50916.26 | 22-MAR-20:44 | 5.60 | 4.80 | 0.589847E+09 | 437.64 | 22-MAR-20:40 | 5.60 | 4.80 |
April | 0.498655E+11 | 52273.85 | 05-APR-20:47 | 4.18 | 1.21 | 0.571411E+09 | 486.12 | 05-APR-21:10 | 3.80 | 1.07 |
May | 0.527659E+11 | 40413.11 | 11-MAY-06:07 | 8.17 | 5.64 | 0.592183E+09 | 381.88 | 19-MAY-21:10 | 23.62 | 16.17 |
June | 0.521691E+11 | 39076.54 | 13-JUN-20:00 | 29.40 | 21.98 | 0.575425E+09 | 381.73 | 27-JUN-21:10 | 27.02 | 21.02 |
July | 0.540733E+11 | 39296.52 | 07-JUL-20:00 | 31.10 | 23.22 | 0.594200E+09 | 381.74 | 11-JUL-21:10 | 26.52 | 20.92 |
August | 0.543785E+11 | 39166.17 | 18-AUG-20:00 | 31.70 | 22.32 | 0.595934E+09 | 381.82 | 01-AUG-21:10 | 31.70 | 22.32 |
September | 0.511380E+11 | 38895.86 | 07-SEP-20:00 | 27.20 | 22.45 | 0.573162E+09 | 381.79 | 05-SEP-21:10 | 27.20 | 22.45 |
October | 0.510914E+11 | 47434.33 | 25-OCT-19:23 | 7.50 | 4.71 | 0.589793E+09 | 492.90 | 25-OCT-21:19 | 5.93 | 4.06 |
November | 0.482860E+11 | 49803.30 | 22-NOV-20:58 | 5.60 | 1.38 | 0.568537E+09 | 467.33 | 07-NOV-23:49 | 5.60 | 1.38 |
December | 0.483531E+11 | 51566.55 | 04-DEC-21:57 | 5.00 | 0.90 | 0.585179E+09 | 489.01 | 21-DEC-22:19 | 5.60 | 3.83 |
Annual Sum or Average | 0.603998E+12 | 0.694127E+10 | ||||||||
Minimum of Months | 0.438667E+11 | 38895.86 | 4.18 | 0.90 | 0.526694E+09 | 381.73 | 3.80 | 1.04 | ||
Maximum of Months | 0.543785E+11 | 52273.85 | 31.70 | 23.22 | 0.595934E+09 | 494.64 | 31.70 | 22.45 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140282E+11 | 12932.67 | 25-JAN-00:30 | 7.25 | 4.99 | 0.919689E+10 | 6504.12 | 25-JAN-00:40 | 7.07 | 4.97 |
February | 0.140741E+11 | 13358.07 | 24-FEB-22:36 | 6.87 | 2.51 | 0.865537E+10 | 6598.17 | 23-FEB-23:10 | 6.87 | 2.51 |
March | 0.181722E+11 | 13960.41 | 01-MAR-04:10 | 8.90 | 5.10 | 0.103105E+11 | 6658.44 | 16-MAR-03:49 | 8.98 | 4.96 |
April | 0.184425E+11 | 12823.50 | 15-APR-13:30 | 27.25 | 14.96 | 0.100874E+11 | 6470.15 | 12-APR-01:00 | 27.25 | 14.96 |
May | 0.202091E+11 | 11969.77 | 11-MAY-04:55 | 8.30 | 5.47 | 0.106551E+11 | 6513.72 | 10-MAY-23:19 | 8.30 | 5.47 |
June | 0.213705E+11 | 11562.97 | 13-JUN-21:10 | 28.12 | 21.63 | 0.104903E+11 | 6461.98 | 10-JUN-01:19 | 28.12 | 21.63 |
July | 0.229425E+11 | 12176.08 | 07-JUL-21:10 | 30.40 | 22.79 | 0.108395E+11 | 6461.99 | 28-JUL-23:19 | 17.20 | 16.88 |
August | 0.240112E+11 | 12477.98 | 18-AUG-21:10 | 30.82 | 22.88 | 0.109482E+11 | 6461.98 | 26-AUG-01:19 | 21.87 | 17.62 |
September | 0.211169E+11 | 12198.41 | 25-SEP-15:03 | 29.40 | 19.56 | 0.104174E+11 | 6462.03 | 17-SEP-23:19 | 29.40 | 19.56 |
October | 0.196509E+11 | 13068.73 | 06-OCT-05:01 | 7.20 | 7.20 | 0.104633E+11 | 6711.95 | 25-OCT-22:19 | 5.40 | 3.94 |
November | 0.172967E+11 | 19363.52 | 24-NOV-00:53 | 8.30 | 6.91 | 0.977762E+10 | 6910.87 | 07-NOV-23:49 | 8.30 | 6.91 |
December | 0.158123E+11 | 13174.17 | 07-DEC-22:57 | 6.70 | 3.39 | 0.958551E+10 | 6488.27 | 19-DEC-23:30 | 5.60 | 1.95 |
Annual Sum or Average | 0.227127E+12 | 0.121427E+12 | ||||||||
Minimum of Months | 0.140282E+11 | 11562.97 | 6.70 | 2.51 | 0.865537E+10 | 6461.98 | 5.40 | 1.95 | ||
Maximum of Months | 0.240112E+11 | 19363.52 | 30.82 | 22.88 | 0.109482E+11 | 6910.87 | 29.40 | 21.63 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.518132E+11 | 43180.22 | 12-JAN-22:35 | 6.10 | 1.97 | 0.283752E+11 | 19207.01 | 25-JAN-00:40 | 7.07 | 4.97 |
February | 0.502487E+11 | 54843.33 | 24-FEB-22:33 | 6.87 | 2.51 | 0.265217E+11 | 19606.10 | 23-FEB-23:10 | 6.87 | 2.51 |
March | 0.623900E+11 | 54811.69 | 01-MAR-04:10 | 8.90 | 5.10 | 0.311981E+11 | 19772.88 | 16-MAR-04:49 | 8.40 | 4.65 |
April | 0.637031E+11 | 53591.51 | 05-APR-20:47 | 4.18 | 1.21 | 0.305175E+11 | 19390.67 | 05-APR-21:10 | 3.80 | 1.07 |
May | 0.706274E+11 | 42162.62 | 10-MAY-03:40 | 9.27 | 4.65 | 0.319795E+11 | 19365.02 | 10-MAY-23:19 | 11.83 | 6.76 |
June | 0.748226E+11 | 41225.23 | 13-JUN-21:10 | 28.12 | 21.63 | 0.312844E+11 | 19185.34 | 08-JUN-04:19 | 28.12 | 21.63 |
July | 0.796067E+11 | 43294.64 | 07-JUL-21:10 | 30.40 | 22.79 | 0.322820E+11 | 19185.25 | 28-JUL-23:19 | 17.20 | 16.88 |
August | 0.816354E+11 | 43944.65 | 18-AUG-21:10 | 30.82 | 22.88 | 0.325264E+11 | 19185.19 | 26-AUG-01:19 | 21.87 | 17.62 |
September | 0.721765E+11 | 41797.96 | 07-SEP-21:10 | 25.40 | 21.43 | 0.311784E+11 | 19185.30 | 17-SEP-23:19 | 17.60 | 15.85 |
October | 0.665662E+11 | 60509.11 | 25-OCT-22:15 | 5.40 | 3.94 | 0.315987E+11 | 19932.84 | 25-OCT-22:19 | 5.40 | 3.94 |
November | 0.591343E+11 | 69005.85 | 24-NOV-00:53 | 8.30 | 6.91 | 0.298635E+11 | 20047.17 | 07-NOV-23:49 | 8.30 | 6.91 |
December | 0.559850E+11 | 49511.78 | 08-DEC-21:17 | 5.20 | 0.87 | 0.295733E+11 | 19532.45 | 14-DEC-02:20 | 8.70 | 8.13 |
Annual Sum or Average | 0.788709E+12 | 0.366899E+12 | ||||||||
Minimum of Months | 0.502487E+11 | 41225.23 | 4.18 | 0.87 | 0.265217E+11 | 19185.19 | 3.80 | 1.07 | ||
Maximum of Months | 0.816354E+11 | 69005.85 | 30.82 | 22.88 | 0.325264E+11 | 20047.17 | 28.12 | 21.63 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 85646971.07 | 2680.75 | 29-JAN-16:01 | 16.52 | 6.64 | 93711453.47 | 56.69 | 25-JAN-00:10 | 16.52 | 6.64 |
February | 0.225917E+09 | 2966.02 | 26-FEB-16:02 | 24.32 | 12.30 | 85578670.21 | 56.69 | 27-FEB-22:10 | 15.40 | 8.51 |
March | 0.697294E+09 | 2942.04 | 13-MAR-15:02 | 23.98 | 13.14 | 96976297.39 | 56.69 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.116227E+10 | 3034.15 | 10-APR-15:01 | 25.60 | 14.02 | 94716818.71 | 56.69 | 17-APR-22:49 | 18.58 | 13.56 |
May | 0.166902E+10 | 2928.54 | 09-MAY-15:02 | 22.80 | 12.60 | 98527058.39 | 56.70 | 15-MAY-21:00 | 22.20 | 15.21 |
June | 0.224495E+10 | 2966.19 | 26-JUN-15:02 | 30.73 | 23.72 | 95744200.15 | 56.70 | 29-JUN-00:40 | 24.80 | 20.69 |
July | 0.250991E+10 | 2965.64 | 05-JUL-18:02 | 31.52 | 22.95 | 98863095.06 | 56.70 | 07-JUL-21:49 | 29.60 | 22.72 |
August | 0.264424E+10 | 2963.94 | 22-AUG-15:02 | 30.00 | 23.93 | 99066397.08 | 56.70 | 18-AUG-21:00 | 30.00 | 23.93 |
September | 0.179612E+10 | 2930.58 | 22-SEP-15:02 | 26.70 | 17.53 | 95292054.51 | 56.70 | 09-SEP-01:10 | 26.70 | 17.53 |
October | 0.948732E+09 | 2900.36 | 08-OCT-15:02 | 27.20 | 18.90 | 97363931.84 | 56.69 | 10-OCT-22:10 | 21.02 | 18.59 |
November | 0.380412E+09 | 2911.46 | 11-NOV-16:01 | 21.32 | 11.45 | 93132855.56 | 56.69 | 01-NOV-21:40 | 21.32 | 11.45 |
December | 0.145164E+09 | 2750.62 | 10-DEC-16:02 | 18.62 | 9.23 | 94458290.95 | 56.69 | 12-DEC-23:19 | 18.13 | 14.84 |
Annual Sum or Average | 0.145097E+11 | 0.114343E+10 | ||||||||
Minimum of Months | 85646971.07 | 2680.75 | 16.52 | 6.64 | 85578670.21 | 56.69 | 15.40 | 6.64 | ||
Maximum of Months | 0.264424E+10 | 3034.15 | 31.52 | 23.93 | 99066397.08 | 56.70 | 30.00 | 23.93 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40258760.77 | 1083.39 | 29-JAN-16:01 | 16.52 | 6.64 | 92873376.55 | 56.69 | 12-JAN-23:49 | 16.52 | 6.64 |
February | 0.133328E+09 | 2884.91 | 26-FEB-16:02 | 24.32 | 12.30 | 84867375.44 | 56.69 | 28-FEB-22:10 | 18.63 | 10.80 |
March | 0.507887E+09 | 2871.32 | 30-MAR-18:02 | 26.02 | 17.62 | 96153388.34 | 56.69 | 29-MAR-21:10 | 26.02 | 17.62 |
April | 0.101318E+10 | 2975.55 | 10-APR-15:01 | 25.60 | 14.02 | 94396510.78 | 56.69 | 12-APR-21:10 | 19.13 | 13.60 |
May | 0.159987E+10 | 2894.54 | 30-MAY-15:02 | 30.13 | 21.49 | 98459681.92 | 56.69 | 04-MAY-21:10 | 30.13 | 21.49 |
June | 0.223128E+10 | 2922.92 | 12-JUN-18:02 | 31.60 | 21.71 | 95758869.94 | 56.70 | 22-JUN-00:49 | 24.08 | 20.55 |
July | 0.247920E+10 | 2931.51 | 05-JUL-18:02 | 31.52 | 22.95 | 98873115.48 | 56.70 | 20-JUL-21:10 | 28.22 | 22.43 |
August | 0.251569E+10 | 2934.67 | 16-AUG-15:02 | 32.80 | 24.24 | 99048058.13 | 56.70 | 02-AUG-21:10 | 32.80 | 24.24 |
September | 0.159357E+10 | 2932.98 | 07-SEP-15:02 | 31.70 | 23.05 | 95162358.13 | 56.70 | 06-SEP-23:40 | 31.70 | 23.05 |
October | 0.682878E+09 | 2808.51 | 13-OCT-15:02 | 21.78 | 12.23 | 96579048.85 | 56.69 | 19-OCT-22:10 | 16.70 | 15.65 |
November | 0.219647E+09 | 2836.62 | 11-NOV-16:01 | 21.32 | 11.45 | 92032920.38 | 56.69 | 05-NOV-23:19 | 21.32 | 11.45 |
December | 76610469.31 | 2450.87 | 10-DEC-16:02 | 18.62 | 9.23 | 93342776.31 | 56.69 | 06-DEC-04:19 | 18.62 | 9.23 |
Annual Sum or Average | 0.130934E+11 | 0.113755E+10 | ||||||||
Minimum of Months | 40258760.77 | 1083.39 | 16.52 | 6.64 | 84867375.44 | 56.69 | 16.52 | 6.64 | ||
Maximum of Months | 0.251569E+10 | 2975.55 | 32.80 | 24.24 | 99048058.13 | 56.70 | 32.80 | 24.24 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131544E+09 | 252.97 | 29-JAN-15:30 | 16.15 | 6.57 | 0.00 | 0.00 | 01-JAN-00:10 | 16.15 | 6.57 |
February | 0.190155E+09 | 442.52 | 26-FEB-14:50 | 24.90 | 12.71 | 0.00 | 0.00 | 01-FEB-00:10 | 24.90 | 12.71 |
March | 0.336113E+09 | 419.12 | 11-MAR-15:00 | 26.10 | 16.58 | 0.00 | 0.00 | 01-MAR-00:10 | 26.10 | 16.58 |
April | 0.387269E+09 | 425.98 | 15-APR-14:00 | 27.80 | 15.01 | 0.00 | 0.00 | 01-APR-00:10 | 27.80 | 15.01 |
May | 0.466434E+09 | 353.83 | 20-MAY-13:30 | 30.00 | 19.14 | 0.00 | 0.00 | 01-MAY-00:10 | 30.00 | 19.14 |
June | 0.609760E+09 | 398.31 | 24-JUN-17:15 | 32.60 | 22.26 | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 22.26 |
July | 0.697491E+09 | 443.15 | 08-JUL-17:12 | 34.40 | 23.36 | 0.00 | 0.00 | 01-JUL-00:10 | 34.40 | 23.36 |
August | 0.792063E+09 | 506.53 | 19-AUG-14:00 | 33.90 | 23.86 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 23.86 |
September | 0.615969E+09 | 551.03 | 24-SEP-12:50 | 28.80 | 19.88 | 0.00 | 0.00 | 01-SEP-00:10 | 28.80 | 19.88 |
October | 0.467376E+09 | 592.52 | 10-OCT-13:30 | 28.85 | 20.88 | 0.00 | 0.00 | 01-OCT-00:10 | 28.85 | 20.88 |
November | 0.328011E+09 | 486.18 | 08-NOV-14:30 | 21.15 | 9.87 | 0.00 | 0.00 | 01-NOV-00:10 | 21.15 | 9.87 |
December | 0.225536E+09 | 455.73 | 10-DEC-14:30 | 17.50 | 8.24 | 0.00 | 0.00 | 01-DEC-00:10 | 17.50 | 8.24 |
Annual Sum or Average | 0.524772E+10 | 0.00 | ||||||||
Minimum of Months | 0.131544E+09 | 252.97 | 16.15 | 6.57 | 0.00 | 0.00 | 16.15 | 6.57 | ||
Maximum of Months | 0.792063E+09 | 592.52 | 34.40 | 23.86 | 0.00 | 0.00 | 34.40 | 23.86 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73012826.28 | 675.67 | 01-JAN-09:02 | 11.78 | 10.88 | 93960568.37 | 56.69 | 24-JAN-23:40 | 7.97 | 5.03 |
February | 0.140261E+09 | 930.33 | 28-FEB-19:02 | 21.52 | 12.04 | 85500940.43 | 56.69 | 22-FEB-22:40 | 21.52 | 12.04 |
March | 0.309220E+09 | 991.46 | 30-MAR-18:02 | 26.02 | 17.62 | 95863325.79 | 56.69 | 29-MAR-21:00 | 26.02 | 17.62 |
April | 0.485730E+09 | 967.27 | 18-APR-15:02 | 25.60 | 16.92 | 93494030.76 | 56.69 | 19-APR-22:19 | 17.23 | 15.39 |
May | 0.693066E+09 | 1012.66 | 18-MAY-18:02 | 28.72 | 17.91 | 97388640.80 | 56.69 | 16-MAY-21:10 | 28.72 | 17.91 |
June | 0.878110E+09 | 1059.04 | 10-JUN-18:02 | 28.62 | 13.87 | 95054208.22 | 56.69 | 12-JUN-21:30 | 26.15 | 21.12 |
July | 0.957984E+09 | 1015.89 | 16-JUL-18:02 | 32.52 | 22.45 | 98230542.47 | 56.69 | 03-JUL-21:19 | 32.52 | 22.45 |
August | 0.952817E+09 | 1012.71 | 25-AUG-18:02 | 29.82 | 19.04 | 98324871.67 | 56.69 | 17-AUG-22:10 | 29.82 | 19.04 |
September | 0.683296E+09 | 996.15 | 07-SEP-18:02 | 29.72 | 22.85 | 94144590.84 | 56.69 | 08-SEP-21:10 | 25.50 | 21.60 |
October | 0.393319E+09 | 948.03 | 10-OCT-18:02 | 25.63 | 20.24 | 96080691.55 | 56.69 | 19-OCT-22:10 | 16.70 | 15.65 |
November | 0.216275E+09 | 863.14 | 05-NOV-15:02 | 23.98 | 18.38 | 92321908.91 | 56.69 | 03-NOV-22:40 | 23.98 | 18.38 |
December | 0.103805E+09 | 691.85 | 24-DEC-09:02 | 15.28 | 14.17 | 94491747.62 | 56.69 | 12-DEC-23:10 | 15.28 | 14.17 |
Annual Sum or Average | 0.588690E+10 | 0.113486E+10 | ||||||||
Minimum of Months | 73012826.28 | 675.67 | 11.78 | 10.88 | 85500940.43 | 56.69 | 7.97 | 5.03 | ||
Maximum of Months | 0.957984E+09 | 1059.04 | 32.52 | 22.85 | 98324871.67 | 56.69 | 32.52 | 22.45 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 79110307.86 | 2275.67 | 29-JAN-16:01 | 16.52 | 6.64 | 93809129.05 | 56.69 | 25-JAN-00:10 | 16.52 | 6.64 |
February | 0.238595E+09 | 2666.80 | 26-FEB-16:02 | 24.32 | 12.30 | 85806336.80 | 56.69 | 28-FEB-22:10 | 18.63 | 10.80 |
March | 0.630645E+09 | 2662.00 | 13-MAR-15:02 | 23.98 | 13.14 | 97242911.08 | 56.69 | 30-MAR-21:30 | 23.35 | 16.68 |
April | 0.112836E+10 | 2738.49 | 10-APR-15:01 | 25.60 | 14.02 | 95019805.58 | 56.69 | 18-APR-21:40 | 19.60 | 14.79 |
May | 0.170331E+10 | 2648.69 | 30-MAY-15:02 | 30.13 | 21.49 | 98808646.20 | 56.69 | 22-MAY-21:49 | 30.13 | 21.49 |
June | 0.228639E+10 | 2687.13 | 21-JUN-15:02 | 32.12 | 22.66 | 95954134.55 | 56.70 | 13-JUN-21:19 | 32.12 | 22.66 |
July | 0.258267E+10 | 2682.58 | 15-JUL-15:02 | 32.88 | 24.22 | 98989420.12 | 56.70 | 14-JUL-21:19 | 32.88 | 24.22 |
August | 0.265747E+10 | 2683.55 | 15-AUG-15:02 | 32.20 | 24.14 | 99159806.18 | 56.70 | 17-AUG-21:19 | 28.53 | 23.54 |
September | 0.180277E+10 | 2690.31 | 11-SEP-15:02 | 29.50 | 23.02 | 95432424.31 | 56.69 | 08-SEP-21:19 | 29.50 | 23.02 |
October | 0.930681E+09 | 2672.51 | 10-OCT-15:02 | 29.08 | 20.63 | 97523818.27 | 56.69 | 10-OCT-22:10 | 21.02 | 18.59 |
November | 0.357198E+09 | 2615.30 | 11-NOV-16:01 | 21.32 | 11.45 | 93310135.41 | 56.69 | 02-NOV-22:19 | 21.32 | 11.45 |
December | 0.140566E+09 | 2388.89 | 10-DEC-16:02 | 18.62 | 9.23 | 94544298.21 | 56.69 | 12-DEC-23:19 | 18.13 | 14.84 |
Annual Sum or Average | 0.145378E+11 | 0.114560E+10 | ||||||||
Minimum of Months | 79110307.86 | 2275.67 | 16.52 | 6.64 | 85806336.80 | 56.69 | 16.52 | 6.64 | ||
Maximum of Months | 0.265747E+10 | 2738.49 | 32.88 | 24.22 | 99159806.18 | 56.70 | 32.88 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 41272543.71 | 882.90 | 24-JAN-16:04 | 11.10 | 5.64 | 92921619.81 | 56.69 | 12-JAN-23:10 | 11.10 | 5.64 |
February | 0.140863E+09 | 2527.26 | 28-FEB-16:02 | 23.40 | 12.60 | 85038132.58 | 56.69 | 26-FEB-01:00 | 23.40 | 12.60 |
March | 0.439756E+09 | 2548.01 | 30-MAR-18:02 | 26.02 | 17.62 | 96362100.50 | 56.69 | 30-MAR-21:10 | 23.72 | 16.82 |
April | 0.970838E+09 | 2695.60 | 10-APR-15:01 | 25.60 | 14.02 | 94773711.12 | 56.69 | 18-APR-21:10 | 19.90 | 15.31 |
May | 0.162940E+10 | 2651.14 | 30-MAY-15:02 | 30.13 | 21.49 | 98777711.20 | 56.69 | 08-MAY-21:00 | 30.13 | 21.49 |
June | 0.227244E+10 | 2658.71 | 12-JUN-15:02 | 33.30 | 22.58 | 95959839.68 | 56.70 | 13-JUN-21:19 | 27.93 | 21.51 |
July | 0.255145E+10 | 2666.16 | 20-JUL-15:02 | 32.80 | 23.21 | 98988420.51 | 56.70 | 07-JUL-22:19 | 32.80 | 23.21 |
August | 0.252711E+10 | 2666.49 | 17-AUG-15:02 | 33.30 | 24.03 | 99152312.76 | 56.70 | 18-AUG-21:49 | 29.68 | 23.03 |
September | 0.159116E+10 | 2617.73 | 07-SEP-15:02 | 31.70 | 23.05 | 95368763.17 | 56.69 | 05-SEP-22:49 | 31.70 | 23.05 |
October | 0.657143E+09 | 2493.07 | 10-OCT-18:02 | 25.63 | 20.24 | 96829916.91 | 56.69 | 19-OCT-21:49 | 16.78 | 15.67 |
November | 0.197505E+09 | 2315.67 | 06-NOV-16:01 | 20.32 | 10.34 | 92055977.78 | 56.69 | 05-NOV-01:19 | 20.32 | 10.34 |
December | 74695379.21 | 1202.07 | 11-DEC-09:03 | 8.45 | 7.67 | 93375405.04 | 56.69 | 23-DEC-01:00 | 7.80 | 7.49 |
Annual Sum or Average | 0.130936E+11 | 0.113960E+10 | ||||||||
Minimum of Months | 41272543.71 | 882.90 | 8.45 | 5.64 | 85038132.58 | 56.69 | 7.80 | 5.64 | ||
Maximum of Months | 0.255145E+10 | 2695.60 | 33.30 | 24.03 | 99152312.76 | 56.70 | 32.80 | 23.21 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187546E+10 | 2560.80 | 16-JAN-21:46 | 6.70 | 1.44 | 0.120544E+10 | 761.76 | 31-JAN-22:40 | 13.37 | 10.31 |
February | 0.231873E+10 | 2536.69 | 24-FEB-23:22 | 6.95 | 2.53 | 0.112169E+10 | 840.64 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.391732E+10 | 2909.61 | 15-MAR-03:28 | 8.30 | 4.50 | 0.134373E+10 | 877.16 | 30-MAR-21:49 | 22.98 | 16.53 |
April | 0.423310E+10 | 2960.99 | 25-APR-23:59 | 7.80 | 5.02 | 0.137692E+10 | 912.46 | 19-APR-21:40 | 7.80 | 5.02 |
May | 0.474088E+10 | 2926.20 | 11-MAY-06:09 | 8.17 | 5.64 | 0.148765E+10 | 936.17 | 19-MAY-21:40 | 22.77 | 15.87 |
June | 0.506662E+10 | 2594.32 | 29-JUN-20:10 | 27.52 | 21.23 | 0.152692E+10 | 951.84 | 29-JUN-23:19 | 23.70 | 21.22 |
July | 0.549256E+10 | 3039.69 | 07-JUL-19:20 | 32.57 | 23.08 | 0.159080E+10 | 951.84 | 07-JUL-23:19 | 27.80 | 22.77 |
August | 0.555702E+10 | 3119.52 | 18-AUG-19:10 | 32.62 | 23.05 | 0.160894E+10 | 951.84 | 18-AUG-23:19 | 28.53 | 23.21 |
September | 0.480919E+10 | 2417.46 | 08-SEP-20:10 | 27.43 | 21.82 | 0.148877E+10 | 951.83 | 12-SEP-21:19 | 23.30 | 20.12 |
October | 0.425381E+10 | 3075.56 | 13-OCT-07:03 | 6.43 | 4.97 | 0.140140E+10 | 908.47 | 11-OCT-21:40 | 6.43 | 4.97 |
November | 0.351816E+10 | 2829.83 | 11-NOV-08:63 | 6.57 | 5.91 | 0.124866E+10 | 824.16 | 08-NOV-22:40 | 6.57 | 5.91 |
December | 0.269148E+10 | 3074.29 | 14-DEC-08:48 | 6.02 | 4.79 | 0.122282E+10 | 800.91 | 12-DEC-23:10 | 6.02 | 4.79 |
Annual Sum or Average | 0.484743E+11 | 0.166237E+11 | ||||||||
Minimum of Months | 0.187546E+10 | 2417.46 | 6.02 | 1.44 | 0.112169E+10 | 761.76 | 6.02 | 4.79 | ||
Maximum of Months | 0.555702E+10 | 3119.52 | 32.62 | 23.08 | 0.160894E+10 | 951.84 | 28.53 | 23.21 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 63110301.12 | 2778.51 | 29-JAN-16:01 | 16.52 | 6.64 | 93222452.35 | 56.69 | 12-JAN-23:49 | 16.52 | 6.64 |
February | 0.189362E+09 | 3100.93 | 26-FEB-16:02 | 24.32 | 12.30 | 85209105.74 | 56.70 | 28-FEB-01:00 | 12.80 | 7.01 |
March | 0.612960E+09 | 3075.02 | 13-MAR-15:02 | 23.98 | 13.14 | 96584495.72 | 56.69 | 30-MAR-21:30 | 23.35 | 16.68 |
April | 0.107603E+10 | 3182.77 | 10-APR-15:01 | 25.60 | 14.02 | 94471179.51 | 56.69 | 12-APR-21:19 | 18.87 | 13.55 |
May | 0.162592E+10 | 3062.78 | 09-MAY-15:02 | 22.80 | 12.60 | 98419066.12 | 56.70 | 19-MAY-22:30 | 21.40 | 15.73 |
June | 0.224238E+10 | 3073.41 | 21-JUN-18:02 | 30.50 | 21.69 | 95673213.14 | 56.70 | 26-JUN-00:10 | 24.40 | 21.65 |
July | 0.253648E+10 | 3088.62 | 19-JUL-15:02 | 30.78 | 23.68 | 98781961.07 | 56.70 | 07-JUL-21:30 | 30.78 | 23.68 |
August | 0.266992E+10 | 3099.94 | 04-AUG-18:02 | 28.80 | 23.56 | 99005434.57 | 56.70 | 18-AUG-21:30 | 30.25 | 22.97 |
September | 0.170631E+10 | 3086.46 | 07-SEP-18:02 | 29.72 | 22.85 | 95123577.99 | 56.70 | 05-SEP-22:49 | 29.72 | 22.85 |
October | 0.828388E+09 | 3024.51 | 02-OCT-15:02 | 26.70 | 20.27 | 96994685.77 | 56.69 | 10-OCT-21:10 | 21.10 | 18.77 |
November | 0.307882E+09 | 3041.20 | 11-NOV-16:01 | 21.32 | 11.45 | 92683418.91 | 56.69 | 06-NOV-22:00 | 21.32 | 11.45 |
December | 0.114219E+09 | 2868.97 | 10-DEC-16:02 | 18.62 | 9.23 | 93876366.75 | 56.69 | 06-DEC-04:40 | 18.62 | 9.23 |
Annual Sum or Average | 0.139730E+11 | 0.114004E+10 | ||||||||
Minimum of Months | 63110301.12 | 2778.51 | 16.52 | 6.64 | 85209105.74 | 56.69 | 12.80 | 6.64 | ||
Maximum of Months | 0.266992E+10 | 3182.77 | 30.78 | 23.68 | 99005434.57 | 56.70 | 30.78 | 23.68 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26839639.98 | 1435.67 | 25-JAN-16:03 | 8.03 | 2.16 | 92630461.58 | 56.69 | 25-JAN-00:10 | 8.03 | 2.16 |
February | 0.108426E+09 | 3002.55 | 26-FEB-16:02 | 24.32 | 12.30 | 84593882.38 | 56.69 | 28-FEB-22:10 | 18.63 | 10.80 |
March | 0.432866E+09 | 2995.34 | 29-MAR-18:02 | 25.50 | 17.73 | 95714676.84 | 56.69 | 30-MAR-21:10 | 23.72 | 16.82 |
April | 0.921409E+09 | 3114.79 | 10-APR-15:01 | 25.60 | 14.02 | 94153522.57 | 56.69 | 14-APR-21:10 | 19.53 | 13.39 |
May | 0.155102E+10 | 3028.90 | 05-MAY-15:02 | 27.80 | 19.38 | 98360998.18 | 56.70 | 18-MAY-22:19 | 21.87 | 16.46 |
June | 0.222735E+10 | 3039.20 | 23-JUN-15:02 | 30.60 | 22.97 | 95688227.01 | 56.70 | 27-JUN-21:10 | 27.02 | 21.02 |
July | 0.250438E+10 | 3049.05 | 21-JUL-18:02 | 33.03 | 22.93 | 98793944.19 | 56.70 | 07-JUL-21:30 | 33.03 | 22.93 |
August | 0.253550E+10 | 3065.00 | 14-AUG-18:02 | 29.90 | 23.13 | 98985898.91 | 56.70 | 18-AUG-21:19 | 30.53 | 22.93 |
September | 0.149154E+10 | 3032.49 | 08-SEP-18:02 | 28.80 | 21.95 | 94989276.03 | 56.70 | 25-SEP-22:10 | 23.03 | 19.17 |
October | 0.570816E+09 | 2926.97 | 10-OCT-15:02 | 29.08 | 20.63 | 96136424.83 | 56.69 | 02-OCT-22:10 | 29.08 | 20.63 |
November | 0.169651E+09 | 2950.65 | 11-NOV-16:01 | 21.32 | 11.45 | 91528201.02 | 56.69 | 02-NOV-22:40 | 21.32 | 11.45 |
December | 54917372.35 | 2057.27 | 11-DEC-16:02 | 21.02 | 15.88 | 92878993.85 | 56.69 | 06-DEC-04:40 | 21.02 | 15.88 |
Annual Sum or Average | 0.125947E+11 | 0.113445E+10 | ||||||||
Minimum of Months | 26839639.98 | 1435.67 | 8.03 | 2.16 | 84593882.38 | 56.69 | 8.03 | 2.16 | ||
Maximum of Months | 0.253550E+10 | 3114.79 | 33.03 | 23.13 | 98985898.91 | 56.70 | 33.03 | 22.93 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164981E+09 | 1474.81 | 29-JAN-16:01 | 16.52 | 6.64 | 95424750.41 | 56.69 | 25-JAN-00:10 | 16.52 | 6.64 |
February | 0.270621E+09 | 1624.36 | 26-FEB-16:02 | 24.32 | 12.30 | 86715104.60 | 56.69 | 21-FEB-22:10 | 24.32 | 12.30 |
March | 0.566407E+09 | 1619.39 | 13-MAR-15:02 | 23.98 | 13.14 | 97395075.74 | 56.69 | 30-MAR-21:10 | 23.72 | 16.82 |
April | 0.718298E+09 | 1571.06 | 09-APR-15:02 | 21.70 | 11.33 | 94689479.08 | 56.69 | 19-APR-22:10 | 17.52 | 15.55 |
May | 0.942054E+09 | 1588.72 | 05-MAY-15:02 | 27.80 | 19.38 | 98370146.41 | 56.69 | 23-MAY-21:49 | 20.78 | 16.98 |
June | 0.122478E+10 | 1599.29 | 25-JUN-15:02 | 31.47 | 23.23 | 95623909.95 | 56.70 | 14-JUN-21:10 | 31.47 | 23.23 |
July | 0.140614E+10 | 1596.94 | 04-JUL-15:02 | 31.28 | 22.90 | 98747435.07 | 56.70 | 10-JUL-21:10 | 26.52 | 21.24 |
August | 0.156402E+10 | 1604.36 | 10-AUG-15:02 | 31.20 | 24.31 | 98994722.87 | 56.70 | 25-AUG-21:10 | 26.02 | 18.49 |
September | 0.116330E+10 | 1579.66 | 24-SEP-15:02 | 28.90 | 20.59 | 95237828.22 | 56.70 | 15-SEP-21:10 | 28.90 | 20.59 |
October | 0.810566E+09 | 1603.70 | 10-OCT-15:02 | 29.08 | 20.63 | 97731400.52 | 56.69 | 11-OCT-00:30 | 19.70 | 17.85 |
November | 0.508755E+09 | 1594.21 | 08-NOV-16:01 | 21.60 | 10.05 | 94193493.15 | 56.69 | 08-NOV-22:10 | 13.62 | 6.96 |
December | 0.282933E+09 | 1524.28 | 10-DEC-16:02 | 18.62 | 9.23 | 96092979.49 | 56.69 | 11-DEC-22:10 | 15.60 | 13.95 |
Annual Sum or Average | 0.962285E+10 | 0.114922E+10 | ||||||||
Minimum of Months | 0.164981E+09 | 1474.81 | 16.52 | 6.64 | 86715104.60 | 56.69 | 13.62 | 6.64 | ||
Maximum of Months | 0.156402E+10 | 1624.36 | 31.47 | 24.31 | 98994722.87 | 56.70 | 31.47 | 23.23 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.298916E+11 | 32108.85 | 24-JAN-23:54 | 7.80 | 5.02 | 0.184410E+11 | 12343.17 | 21-JAN-01:30 | 7.80 | 5.02 |
February | 0.288897E+11 | 31250.28 | 23-FEB-23:37 | 7.07 | 2.01 | 0.169013E+11 | 12535.97 | 01-FEB-23:30 | 7.07 | 2.01 |
March | 0.358037E+11 | 30808.02 | 15-MAR-05:44 | 7.88 | 4.03 | 0.191610E+11 | 12656.62 | 16-MAR-03:49 | 8.98 | 4.96 |
April | 0.373067E+11 | 32060.20 | 25-APR-23:59 | 7.80 | 5.02 | 0.185989E+11 | 12019.51 | 05-APR-21:10 | 7.80 | 5.02 |
May | 0.415905E+11 | 30801.95 | 10-MAY-03:23 | 9.45 | 4.70 | 0.193010E+11 | 11641.60 | 10-MAY-03:30 | 9.45 | 4.70 |
June | 0.431197E+11 | 23473.17 | 13-JUN-21:20 | 27.93 | 21.51 | 0.187435E+11 | 11367.63 | 23-JUN-21:19 | 24.23 | 21.22 |
July | 0.452943E+11 | 23978.93 | 07-JUL-21:20 | 30.20 | 22.78 | 0.192961E+11 | 11366.36 | 13-JUL-21:19 | 23.30 | 21.29 |
August | 0.454439E+11 | 23732.92 | 18-AUG-21:20 | 30.53 | 22.93 | 0.193774E+11 | 11376.85 | 11-AUG-21:19 | 30.53 | 22.93 |
September | 0.403643E+11 | 22676.16 | 07-SEP-21:10 | 25.40 | 21.43 | 0.186613E+11 | 11347.75 | 17-SEP-23:19 | 17.60 | 15.85 |
October | 0.369789E+11 | 31799.28 | 04-OCT-04:40 | 7.97 | 7.65 | 0.191393E+11 | 12785.13 | 25-OCT-22:19 | 5.40 | 3.94 |
November | 0.329351E+11 | 31591.46 | 14-NOV-23:40 | 7.40 | 4.47 | 0.183286E+11 | 12778.47 | 13-NOV-23:49 | 7.40 | 4.47 |
December | 0.314558E+11 | 33171.68 | 07-DEC-23:41 | 6.20 | 3.09 | 0.187409E+11 | 12457.74 | 14-DEC-02:20 | 8.70 | 8.13 |
Annual Sum or Average | 0.449074E+12 | 0.224690E+12 | ||||||||
Minimum of Months | 0.288897E+11 | 22676.16 | 6.20 | 2.01 | 0.169013E+11 | 11347.75 | 5.40 | 2.01 | ||
Maximum of Months | 0.454439E+11 | 33171.68 | 30.53 | 22.93 | 0.193774E+11 | 12785.13 | 30.53 | 22.93 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.331443E+11 | 33791.60 | 24-JAN-23:54 | 7.80 | 5.02 | 0.187446E+11 | 12422.33 | 21-JAN-01:30 | 7.80 | 5.02 |
February | 0.319655E+11 | 33609.06 | 24-FEB-23:26 | 6.95 | 2.53 | 0.171052E+11 | 12591.09 | 01-FEB-23:30 | 6.95 | 2.53 |
March | 0.393022E+11 | 32674.40 | 15-MAR-05:44 | 7.88 | 4.03 | 0.192747E+11 | 12714.05 | 16-MAR-03:49 | 8.98 | 4.96 |
April | 0.405189E+11 | 37267.09 | 25-APR-23:59 | 7.80 | 5.02 | 0.186553E+11 | 12075.01 | 05-APR-21:10 | 7.80 | 5.02 |
May | 0.447013E+11 | 32308.60 | 10-MAY-03:23 | 9.45 | 4.70 | 0.193275E+11 | 11650.17 | 10-MAY-03:30 | 9.45 | 4.70 |
June | 0.458593E+11 | 24692.13 | 13-JUN-21:20 | 27.93 | 21.51 | 0.187534E+11 | 11378.16 | 23-JUN-21:19 | 24.23 | 21.22 |
July | 0.480812E+11 | 25154.35 | 07-JUL-21:20 | 30.20 | 22.78 | 0.193046E+11 | 11374.06 | 19-JUL-21:19 | 25.60 | 22.06 |
August | 0.481604E+11 | 24905.86 | 18-AUG-21:20 | 30.53 | 22.93 | 0.193861E+11 | 11386.30 | 11-AUG-21:19 | 30.53 | 22.93 |
September | 0.432001E+11 | 23872.89 | 05-SEP-21:20 | 26.50 | 21.19 | 0.186855E+11 | 11366.57 | 05-SEP-21:19 | 26.50 | 21.19 |
October | 0.403041E+11 | 33540.27 | 25-OCT-22:15 | 5.40 | 3.94 | 0.192214E+11 | 12900.98 | 25-OCT-22:19 | 5.40 | 3.94 |
November | 0.362997E+11 | 33370.56 | 17-NOV-24:00 | 6.70 | 3.54 | 0.184856E+11 | 12892.87 | 13-NOV-23:49 | 6.70 | 3.54 |
December | 0.348985E+11 | 34922.79 | 07-DEC-23:41 | 6.20 | 3.09 | 0.189682E+11 | 12518.44 | 14-DEC-02:20 | 8.70 | 8.13 |
Annual Sum or Average | 0.486435E+12 | 0.225912E+12 | ||||||||
Minimum of Months | 0.319655E+11 | 23872.89 | 5.40 | 2.53 | 0.171052E+11 | 11366.57 | 5.40 | 2.53 | ||
Maximum of Months | 0.481604E+11 | 37267.09 | 30.53 | 22.93 | 0.193861E+11 | 12900.98 | 30.53 | 22.93 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.470253E+11 | 36321.40 | 25-JAN-18:41 | 5.18 | 1.39 | 0.187947E+11 | 11491.83 | 21-JAN-18:19 | 5.18 | 1.39 |
February | 0.441521E+11 | 35525.11 | 08-FEB-18:31 | 6.47 | 1.20 | 0.169901E+11 | 11353.65 | 08-FEB-18:30 | 6.47 | 1.20 |
March | 0.520275E+11 | 34747.48 | 22-MAR-17:44 | 5.60 | 4.80 | 0.188391E+11 | 11342.20 | 18-MAR-17:40 | 5.60 | 4.80 |
April | 0.524111E+11 | 34233.60 | 06-APR-22:38 | 6.30 | 3.11 | 0.182387E+11 | 11393.16 | 15-APR-17:10 | 26.42 | 15.32 |
May | 0.562428E+11 | 31790.80 | 15-MAY-17:01 | 28.72 | 16.81 | 0.188567E+11 | 11320.54 | 20-MAY-17:10 | 26.02 | 17.45 |
June | 0.561826E+11 | 30725.59 | 25-JUN-10:33 | 29.80 | 23.29 | 0.182588E+11 | 11346.21 | 10-JUN-17:10 | 29.80 | 23.29 |
July | 0.586039E+11 | 31151.59 | 08-JUL-10:50 | 33.53 | 24.57 | 0.188630E+11 | 11319.68 | 15-JUL-17:19 | 33.30 | 24.04 |
August | 0.587073E+11 | 30991.36 | 27-AUG-10:50 | 30.03 | 22.67 | 0.188714E+11 | 11319.67 | 12-AUG-17:19 | 30.03 | 22.67 |
September | 0.545072E+11 | 30596.77 | 09-SEP-10:45 | 30.32 | 23.97 | 0.182496E+11 | 11319.65 | 23-SEP-17:19 | 27.23 | 18.81 |
October | 0.530511E+11 | 36018.61 | 13-OCT-07:03 | 6.43 | 4.97 | 0.188400E+11 | 11319.97 | 28-OCT-17:30 | 16.95 | 16.95 |
November | 0.490525E+11 | 35180.45 | 30-NOV-18:19 | 6.70 | 6.70 | 0.182145E+11 | 11319.96 | 04-NOV-17:30 | 6.70 | 6.70 |
December | 0.485017E+11 | 38455.57 | 01-DEC-18:47 | 6.05 | 0.79 | 0.188143E+11 | 11522.80 | 30-DEC-18:49 | 7.88 | 7.53 |
Annual Sum or Average | 0.630465E+12 | 0.221831E+12 | ||||||||
Minimum of Months | 0.441521E+11 | 30596.77 | 5.18 | 0.79 | 0.169901E+11 | 11319.65 | 5.18 | 1.20 | ||
Maximum of Months | 0.587073E+11 | 38455.57 | 33.53 | 24.57 | 0.188714E+11 | 11522.80 | 33.30 | 24.04 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286348E+10 | 4430.06 | 25-JAN-18:41 | 5.18 | 1.39 | 0.127407E+10 | 810.84 | 31-JAN-22:30 | 13.75 | 10.50 |
February | 0.424139E+10 | 5078.30 | 24-FEB-23:22 | 6.95 | 2.53 | 0.117873E+10 | 887.50 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.776191E+10 | 5806.26 | 15-MAR-03:28 | 8.30 | 4.50 | 0.139043E+10 | 958.66 | 30-MAR-21:40 | 23.17 | 16.60 |
April | 0.866488E+10 | 5884.28 | 25-APR-23:59 | 7.80 | 5.02 | 0.143420E+10 | 982.67 | 17-APR-21:30 | 7.80 | 5.02 |
May | 0.100344E+11 | 5781.20 | 11-MAY-06:09 | 8.17 | 5.64 | 0.157911E+10 | 1007.38 | 30-MAY-21:40 | 22.77 | 21.08 |
June | 0.110237E+11 | 6075.07 | 13-JUN-18:03 | 31.93 | 21.91 | 0.161796E+10 | 1007.40 | 05-JUN-21:19 | 31.93 | 21.91 |
July | 0.121314E+11 | 7091.79 | 07-JUL-18:03 | 33.80 | 23.16 | 0.167813E+10 | 1007.39 | 24-JUL-21:19 | 26.33 | 20.14 |
August | 0.123166E+11 | 6970.95 | 18-AUG-15:03 | 34.50 | 23.13 | 0.169919E+10 | 1007.39 | 02-AUG-21:19 | 34.50 | 23.13 |
September | 0.100298E+11 | 5921.94 | 07-SEP-15:25 | 31.70 | 23.32 | 0.155590E+10 | 1007.39 | 07-SEP-21:19 | 25.20 | 21.25 |
October | 0.851367E+10 | 6011.55 | 13-OCT-07:03 | 6.43 | 4.97 | 0.144112E+10 | 964.03 | 10-OCT-21:40 | 6.43 | 4.97 |
November | 0.667661E+10 | 5436.98 | 11-NOV-08:63 | 6.57 | 5.91 | 0.129213E+10 | 864.76 | 03-NOV-21:40 | 6.57 | 5.91 |
December | 0.458382E+10 | 6249.18 | 14-DEC-08:48 | 6.02 | 4.79 | 0.128552E+10 | 855.35 | 12-DEC-23:10 | 6.02 | 4.79 |
Annual Sum or Average | 0.988416E+11 | 0.174265E+11 | ||||||||
Minimum of Months | 0.286348E+10 | 4430.06 | 5.18 | 1.39 | 0.117873E+10 | 810.84 | 6.02 | 4.79 | ||
Maximum of Months | 0.123166E+11 | 7091.79 | 34.50 | 23.32 | 0.169919E+10 | 1007.40 | 34.50 | 23.13 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 505726.10 | 784.22 | 25-JAN-00:27 | 7.25 |
February | 1248896.52 | 1743.04 | 23-FEB-23:43 | 6.88 |
March | 16692415.39 | 2730.21 | 16-MAR-05:00 | 8.30 |
April | 8766281.86 | 2523.22 | 09-APR-04:12 | 8.53 |
May | 1455496.04 | 1772.91 | 10-MAY-05:35 | 9.23 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 1180725.10 | 1344.43 | 07-OCT-05:35 | 7.80 |
November | 1150384.54 | 3506.25 | 14-NOV-23:39 | 7.40 |
December | 59016.37 | 562.29 | 14-DEC-07:30 | 5.85 |
Annual Sum or Average | 31058941.92 | |||
Minimum of Months | 0.00 | 0.00 | 5.85 | |
Maximum of Months | 16692415.39 | 3506.25 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.445440E+09 | 1355.19 | 08-JAN-05:00 | -5.6 |
February | 0.224189E+09 | 1669.16 | 12-FEB-06:00 | -12.2 |
March | 9238411.91 | 533.15 | 16-MAR-05:00 | 8.30 |
April | 2068683.92 | 408.54 | 28-APR-05:47 | 8.40 |
May | 377266.07 | 401.44 | 10-MAY-05:35 | 9.23 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 9402119.35 | 1238.74 | 31-OCT-07:51 | 7.80 |
November | 27278948.74 | 752.73 | 29-NOV-00:23 | 6.95 |
December | 89455472.07 | 1767.59 | 14-DEC-08:49 | 6.02 |
Annual Sum or Average | 0.807450E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.445440E+09 | 1767.59 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 726651.27 | 257.09 | 13-JAN-12:23 | 6.95 |
February | 639471.33 | 284.57 | 04-FEB-15:03 | 6.88 |
March | 306291.93 | 249.01 | 23-MAR-08:10 | 6.97 |
April | 68624.62 | 95.58 | 07-APR-07:44 | 6.47 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 876179.63 | 243.71 | 07-OCT-05:35 | 7.80 |
November | 1028076.42 | 297.98 | 30-NOV-18:17 | 6.70 |
December | 1932036.86 | 290.16 | 21-DEC-15:33 | 7.03 |
Annual Sum or Average | 5577332.05 | |||
Minimum of Months | 0.00 | 0.00 | 6.47 | |
Maximum of Months | 1932036.86 | 297.98 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73132749.00 | 482.43 | 28-JAN-23:00 | 5.60 |
February | 50580865.88 | 1371.54 | 04-FEB-16:37 | 7.07 |
March | 3306564.72 | 340.18 | 23-MAR-08:10 | 6.97 |
April | 660188.47 | 227.22 | 07-APR-07:44 | 6.47 |
May | 55404.08 | 87.24 | 10-MAY-05:35 | 9.23 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 3165377.10 | 447.90 | 07-OCT-05:35 | 7.80 |
November | 4726565.74 | 525.22 | 14-NOV-23:39 | 7.40 |
December | 5559643.07 | 403.79 | 21-DEC-22:55 | 5.60 |
Annual Sum or Average | 0.141187E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.60 | |
Maximum of Months | 73132749.00 | 1371.54 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144550E+09 | 366.68 | 08-JAN-05:40 | -5.2 |
February | 85297858.52 | 761.56 | 04-FEB-16:37 | 7.07 |
March | 2024251.44 | 166.53 | 23-MAR-08:10 | 6.97 |
April | 433462.14 | 128.57 | 07-APR-07:44 | 6.47 |
May | 45495.73 | 60.33 | 10-MAY-05:35 | 9.23 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 2026891.72 | 231.91 | 07-OCT-05:35 | 7.80 |
November | 2685456.33 | 278.01 | 14-NOV-23:39 | 7.40 |
December | 10118923.66 | 228.51 | 21-DEC-22:55 | 5.60 |
Annual Sum or Average | 0.247182E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.2 | |
Maximum of Months | 0.144550E+09 | 761.56 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 572523.44 | 1513.79 | 13-MAR-01:14 | 8.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 173733.79 | 1254.27 | 10-MAY-03:54 | 8.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 2032281.42 | 2312.71 | 14-OCT-03:59 | 7.80 |
November | 919805.87 | 2246.59 | 17-NOV-03:37 | 8.50 |
December | 289828.67 | 2028.12 | 06-DEC-04:05 | 8.80 |
Annual Sum or Average | 3988173.19 | |||
Minimum of Months | 0.00 | 0.00 | 5.70 | |
Maximum of Months | 2032281.42 | 2312.71 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2146147.55 | 1121.70 | 21-JAN-10:53 | 6.70 |
February | 2117496.45 | 1491.56 | 11-FEB-09:34 | 7.60 |
March | 2865378.20 | 1807.68 | 23-MAR-08:10 | 6.97 |
April | 968286.86 | 1217.85 | 26-APR-07:31 | 6.67 |
May | 22692.56 | 173.52 | 11-MAY-06:02 | 8.17 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 5743270.09 | 1642.67 | 31-OCT-07:53 | 7.80 |
November | 2895488.09 | 2080.51 | 30-NOV-18:17 | 6.70 |
December | 7030870.88 | 1819.81 | 14-DEC-07:30 | 5.85 |
Annual Sum or Average | 23789630.68 | |||
Minimum of Months | 0.00 | 0.00 | 5.85 | |
Maximum of Months | 7030870.88 | 2080.51 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4393675.17 | 2604.65 | 25-JAN-18:35 | 5.37 |
February | 3971450.36 | 3811.02 | 01-FEB-15:43 | 7.12 |
March | 1369676.07 | 3545.40 | 23-MAR-08:10 | 6.97 |
April | 561996.08 | 993.74 | 06-APR-08:45 | 6.83 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 4584560.07 | 4599.65 | 07-OCT-05:35 | 7.80 |
November | 3798313.64 | 5518.39 | 15-NOV-00:06 | 7.12 |
December | 12117885.39 | 4296.19 | 21-DEC-15:33 | 7.03 |
Annual Sum or Average | 30797556.80 | |||
Minimum of Months | 0.00 | 0.00 | 5.37 | |
Maximum of Months | 12117885.39 | 5518.39 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106640E+10 | 2496.16 | 07-JAN-19:01 | -5.6 |
February | 0.621231E+09 | 2501.09 | 12-FEB-09:01 | -10.2 |
March | 0.101647E+09 | 2405.08 | 23-MAR-08:61 | 6.97 |
April | 28019545.72 | 2373.18 | 07-APR-08:61 | 7.95 |
May | 673732.90 | 450.23 | 13-MAY-08:03 | 17.67 |
June | 844464.69 | 644.37 | 04-JUN-08:05 | 22.57 |
July | 588274.59 | 584.21 | 02-JUL-08:05 | 22.67 |
August | 477618.74 | 654.11 | 26-AUG-08:05 | 23.07 |
September | 964459.40 | 638.32 | 14-SEP-08:03 | 15.55 |
October | 61816483.32 | 2353.20 | 26-OCT-08:61 | 5.05 |
November | 0.220351E+09 | 2417.27 | 21-NOV-09:01 | -0.1 |
December | 0.658868E+09 | 2438.09 | 18-DEC-09:01 | -1.7 |
Annual Sum or Average | 0.276188E+10 | |||
Minimum of Months | 477618.74 | 450.23 | -10.2 | |
Maximum of Months | 0.106640E+10 | 2501.09 | 23.07 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134588E+10 | 2496.51 | 07-JAN-19:01 | -5.6 |
February | 0.793060E+09 | 2517.29 | 12-FEB-09:01 | -10.2 |
March | 0.148152E+09 | 2404.70 | 23-MAR-08:61 | 6.97 |
April | 35616132.08 | 2381.58 | 07-APR-08:61 | 7.95 |
May | 676862.23 | 436.57 | 12-MAY-08:04 | 15.28 |
June | 696079.57 | 695.42 | 04-JUN-08:05 | 22.57 |
July | 491684.49 | 664.45 | 02-JUL-08:05 | 22.67 |
August | 516174.12 | 682.78 | 26-AUG-08:05 | 23.07 |
September | 1061674.80 | 642.40 | 10-SEP-08:05 | 22.97 |
October | 86395729.38 | 2377.93 | 26-OCT-08:61 | 5.05 |
November | 0.345159E+09 | 2434.95 | 21-NOV-09:01 | -0.1 |
December | 0.890350E+09 | 2457.30 | 18-DEC-09:01 | -1.7 |
Annual Sum or Average | 0.364805E+10 | |||
Minimum of Months | 491684.49 | 436.57 | -10.2 | |
Maximum of Months | 0.134588E+10 | 2517.29 | 23.07 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 56865556.30 | 279.02 | 08-JAN-05:10 | -5.5 |
February | 17773189.59 | 303.18 | 12-FEB-06:00 | -12.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 9.70 |
December | 2265411.34 | 103.63 | 26-DEC-05:00 | 3.90 |
Annual Sum or Average | 76904157.23 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 56865556.30 | 303.18 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.219803E+09 | 749.61 | 07-JAN-16:02 | -4.1 |
February | 0.122015E+09 | 749.39 | 03-FEB-09:01 | -6.8 |
March | 5765415.81 | 697.15 | 23-MAR-08:61 | 6.97 |
April | 1111931.37 | 697.68 | 07-APR-08:61 | 7.95 |
May | 230271.52 | 289.08 | 11-MAY-08:03 | 12.15 |
June | 57281.80 | 229.35 | 02-JUN-08:05 | 22.48 |
July | 38126.47 | 97.63 | 17-JUL-08:07 | 24.27 |
August | 31985.67 | 141.20 | 25-AUG-08:05 | 22.15 |
September | 293614.09 | 237.72 | 12-SEP-08:05 | 23.07 |
October | 2237470.43 | 699.60 | 26-OCT-08:61 | 5.05 |
November | 22771167.41 | 720.56 | 22-NOV-09:01 | 1.05 |
December | 94729668.96 | 731.67 | 18-DEC-09:01 | -1.7 |
Annual Sum or Average | 0.469085E+09 | |||
Minimum of Months | 31985.67 | 97.63 | -6.8 | |
Maximum of Months | 0.219803E+09 | 749.61 | 24.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107223E+10 | 2431.28 | 07-JAN-19:01 | -5.6 |
February | 0.611417E+09 | 2415.69 | 11-FEB-19:01 | -6.2 |
March | 0.105047E+09 | 2336.64 | 22-MAR-18:01 | 5.60 |
April | 26952890.09 | 724.22 | 07-APR-08:02 | 7.95 |
May | 286352.67 | 371.88 | 09-MAY-18:05 | 19.63 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 103640.38 | 283.51 | 30-JUL-08:06 | 22.48 |
August | 36926.96 | 185.79 | 24-AUG-08:05 | 23.80 |
September | 231505.93 | 403.06 | 16-SEP-08:05 | 22.30 |
October | 64017619.88 | 2268.51 | 31-OCT-08:61 | 7.80 |
November | 0.215226E+09 | 2306.32 | 30-NOV-19:01 | 6.70 |
December | 0.646498E+09 | 2357.92 | 31-DEC-19:01 | 5.50 |
Annual Sum or Average | 0.274204E+10 | |||
Minimum of Months | 0.00 | 0.00 | -6.2 | |
Maximum of Months | 0.107223E+10 | 2431.28 | 23.80 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135579E+10 | 2432.38 | 07-JAN-19:01 | -5.6 |
February | 0.773068E+09 | 2419.21 | 11-FEB-19:01 | -6.2 |
March | 0.146719E+09 | 2340.60 | 22-MAR-18:01 | 5.60 |
April | 33994423.94 | 727.54 | 25-APR-15:04 | 18.22 |
May | 351677.41 | 373.43 | 01-MAY-18:05 | 22.12 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 104499.23 | 290.68 | 30-JUL-08:06 | 22.48 |
August | 44684.93 | 207.85 | 24-AUG-08:05 | 23.80 |
September | 404278.48 | 590.20 | 16-SEP-08:05 | 22.30 |
October | 90920161.63 | 2268.00 | 31-OCT-08:61 | 7.80 |
November | 0.330698E+09 | 2323.28 | 21-NOV-16:01 | 9.03 |
December | 0.876186E+09 | 2358.91 | 26-DEC-19:01 | 6.52 |
Annual Sum or Average | 0.360828E+10 | |||
Minimum of Months | 0.00 | 0.00 | -6.2 | |
Maximum of Months | 0.135579E+10 | 2432.38 | 23.80 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 83389837.89 | 720.15 | 07-JAN-17:00 | -5.0 |
February | 26195016.47 | 1334.82 | 04-FEB-16:37 | 7.07 |
March | 4209660.59 | 491.64 | 23-MAR-08:10 | 6.97 |
April | 727128.95 | 274.31 | 07-APR-07:44 | 6.47 |
May | 40909.23 | 97.27 | 10-MAY-05:40 | 9.23 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 5205559.77 | 602.53 | 07-OCT-05:35 | 7.80 |
November | 7251391.54 | 760.78 | 29-NOV-00:23 | 6.95 |
December | 9584611.05 | 648.99 | 21-DEC-22:55 | 5.60 |
Annual Sum or Average | 0.136604E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 83389837.89 | 1334.82 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157788E+10 | 2942.15 | 07-JAN-19:01 | -5.6 |
February | 0.959384E+09 | 2952.67 | 12-FEB-09:01 | -10.2 |
March | 0.239973E+09 | 2841.26 | 22-MAR-18:01 | 5.60 |
April | 71733210.78 | 2824.20 | 07-APR-08:61 | 7.95 |
May | 2412524.18 | 1113.56 | 11-MAY-08:62 | 12.15 |
June | 876279.41 | 493.59 | 24-JUN-08:05 | 24.78 |
July | 912379.16 | 573.86 | 05-JUL-08:05 | 26.47 |
August | 1041160.33 | 580.31 | 26-AUG-08:05 | 23.07 |
September | 4247903.87 | 613.60 | 23-SEP-08:03 | 20.37 |
October | 0.157021E+09 | 2795.57 | 26-OCT-08:61 | 5.05 |
November | 0.432040E+09 | 2842.36 | 21-NOV-09:01 | -0.1 |
December | 0.105125E+10 | 2870.00 | 18-DEC-09:01 | -1.7 |
Annual Sum or Average | 0.449877E+10 | |||
Minimum of Months | 876279.41 | 493.59 | -10.2 | |
Maximum of Months | 0.157788E+10 | 2952.67 | 26.47 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.192711E+10 | 2941.78 | 07-JAN-19:01 | -5.6 |
February | 0.118128E+10 | 2968.70 | 12-FEB-09:01 | -10.2 |
March | 0.322758E+09 | 2839.91 | 22-MAR-18:01 | 5.60 |
April | 87163751.15 | 2832.85 | 07-APR-08:61 | 7.95 |
May | 2996620.20 | 1126.77 | 11-MAY-08:62 | 12.15 |
June | 973740.48 | 563.91 | 13-JUN-08:05 | 25.37 |
July | 776625.85 | 534.94 | 02-JUL-08:05 | 22.67 |
August | 1005470.86 | 576.51 | 27-AUG-08:05 | 23.17 |
September | 5021723.02 | 563.45 | 16-SEP-18:05 | 25.40 |
October | 0.216461E+09 | 2805.16 | 26-OCT-08:61 | 5.05 |
November | 0.624176E+09 | 2864.92 | 21-NOV-09:01 | -0.1 |
December | 0.134840E+10 | 2895.87 | 18-DEC-09:01 | -1.7 |
Annual Sum or Average | 0.571813E+10 | |||
Minimum of Months | 776625.85 | 534.94 | -10.2 | |
Maximum of Months | 0.192711E+10 | 2968.70 | 25.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.451676E+09 | 1522.54 | 07-JAN-19:01 | -5.6 |
February | 0.258218E+09 | 1514.46 | 12-FEB-09:01 | -10.2 |
March | 44969892.24 | 1460.39 | 23-MAR-08:61 | 6.97 |
April | 19477357.03 | 1447.17 | 07-APR-08:61 | 7.95 |
May | 389249.91 | 299.57 | 11-MAY-08:62 | 12.15 |
June | 426792.12 | 351.40 | 04-JUN-08:05 | 22.57 |
July | 312007.14 | 289.98 | 10-JUL-08:05 | 23.68 |
August | 187821.45 | 346.37 | 09-AUG-08:05 | 26.38 |
September | 652908.73 | 358.80 | 14-SEP-08:03 | 15.55 |
October | 25438530.90 | 1422.09 | 26-OCT-08:61 | 5.05 |
November | 68621596.11 | 1440.82 | 30-NOV-16:01 | 7.20 |
December | 0.235379E+09 | 1468.30 | 31-DEC-19:01 | 5.50 |
Annual Sum or Average | 0.110575E+10 | |||
Minimum of Months | 187821.45 | 289.98 | -10.2 | |
Maximum of Months | 0.451676E+09 | 1522.54 | 26.38 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 177591.25 | 317.33 | 15-JAN-16:00 | 7.20 |
February | 50359.66 | 251.80 | 04-FEB-15:03 | 6.88 |
March | 20311.35 | 208.69 | 23-MAR-08:10 | 6.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 24885.46 | 414.76 | 26-OCT-08:50 | 7.65 |
November | 426981.38 | 1687.14 | 14-NOV-23:39 | 7.40 |
December | 667987.59 | 1069.64 | 05-DEC-09:50 | 7.85 |
Annual Sum or Average | 1368116.69 | |||
Minimum of Months | 0.00 | 0.00 | 6.88 | |
Maximum of Months | 667987.59 | 1687.14 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 278708.48 | 1597.72 | 14-NOV-23:39 | 7.40 |
December | 85644.79 | 519.87 | 05-DEC-09:50 | 7.85 |
Annual Sum or Average | 364353.26 | |||
Minimum of Months | 0.00 | 0.00 | 5.70 | |
Maximum of Months | 278708.48 | 1597.72 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 29956.91 | 249.64 | 13-OCT-03:00 | 7.80 |
November | 12601.07 | 126.01 | 29-NOV-00:20 | 7.03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 42557.98 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 29956.91 | 249.64 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.574701E+09 | 2321.49 | 08-JAN-05:20 | -5.4 |
February | 0.300228E+09 | 2946.16 | 12-FEB-06:00 | -12.2 |
March | 13692333.44 | 1021.31 | 23-MAR-08:10 | 6.97 |
April | 2877884.33 | 915.92 | 27-APR-07:07 | 6.75 |
May | 363910.66 | 488.96 | 10-MAY-05:35 | 9.23 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 16439547.59 | 1538.29 | 07-OCT-05:35 | 7.80 |
November | 29321599.72 | 1715.46 | 14-NOV-23:39 | 7.40 |
December | 87552438.61 | 1407.27 | 21-DEC-22:55 | 5.60 |
Annual Sum or Average | 0.102518E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.574701E+09 | 2946.16 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.147273E+11 | 14185.34 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.132974E+11 | 14185.34 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.147727E+11 | 14185.34 | 01-MAR-20:10 | 0.127855E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.142280E+11 | 14185.34 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.147528E+11 | 14185.34 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.142932E+11 | 14185.34 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.146876E+11 | 14185.34 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.147784E+11 | 14185.34 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.142337E+11 | 14185.34 | 01-SEP-19:10 | 0.123352E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.147216E+11 | 14185.34 | 02-OCT-19:10 | 0.127549E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.142819E+11 | 14185.34 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.146876E+11 | 14185.34 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.173462E+12 | 0.150255E+12 | ||||
Minimum of Months | 0.132974E+11 | 14185.34 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.147784E+11 | 14185.34 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.731324E+09 | 704.41 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.660319E+09 | 704.41 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.733578E+09 | 704.41 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.706528E+09 | 704.41 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.732592E+09 | 704.41 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.709769E+09 | 704.41 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.729351E+09 | 704.41 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.733860E+09 | 704.41 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.706810E+09 | 704.41 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.731042E+09 | 704.41 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.709205E+09 | 704.41 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.729351E+09 | 704.41 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.861373E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.660319E+09 | 704.41 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.733860E+09 | 704.41 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.846876E+09 | 815.72 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.764651E+09 | 815.72 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.849486E+09 | 815.72 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.818162E+09 | 815.72 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.848344E+09 | 815.72 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.821915E+09 | 815.72 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.844592E+09 | 815.72 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.849812E+09 | 815.72 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.818489E+09 | 815.72 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.846549E+09 | 815.72 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.821262E+09 | 815.72 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.844592E+09 | 815.72 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.997473E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.764651E+09 | 815.72 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.849812E+09 | 815.72 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.141236E+10 | 1360.40 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.127524E+10 | 1360.40 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.141672E+10 | 1360.40 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.136448E+10 | 1360.40 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.141481E+10 | 1360.40 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.137074E+10 | 1360.40 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.140855E+10 | 1360.40 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.141726E+10 | 1360.40 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.136502E+10 | 1360.40 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.141182E+10 | 1360.40 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.136965E+10 | 1360.40 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.140855E+10 | 1360.40 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.166352E+11 | 0.124712E+11 | ||||
Minimum of Months | 0.127524E+10 | 1360.40 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.141726E+10 | 1360.40 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.236418E+09 | 227.72 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.213464E+09 | 227.72 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.237147E+09 | 227.72 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.228402E+09 | 227.72 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.236828E+09 | 227.72 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.229450E+09 | 227.72 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.235780E+09 | 227.72 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.237238E+09 | 227.72 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.228493E+09 | 227.72 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.236327E+09 | 227.72 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.229268E+09 | 227.72 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.235780E+09 | 227.72 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.278459E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.213464E+09 | 227.72 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.237238E+09 | 227.72 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.370859E+09 | 357.21 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.334852E+09 | 357.21 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.372002E+09 | 357.21 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.358285E+09 | 357.21 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.371502E+09 | 357.21 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.359929E+09 | 357.21 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.369859E+09 | 357.21 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.372145E+09 | 357.21 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.358428E+09 | 357.21 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.370717E+09 | 357.21 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.359643E+09 | 357.21 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.369859E+09 | 357.21 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.436808E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.334852E+09 | 357.21 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.372145E+09 | 357.21 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.160392E+10 | 1761.91 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.144265E+10 | 1761.91 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.154421E+10 | 1761.91 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.144233E+10 | 1761.91 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.145274E+10 | 1761.91 | 01-MAY-19:19 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.138958E+10 | 1761.91 | 01-JUN-19:30 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.143940E+10 | 1761.91 | 03-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.147645E+10 | 1761.91 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.148062E+10 | 1761.91 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.157538E+10 | 1761.91 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.154540E+10 | 1761.91 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.159911E+10 | 1761.91 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.179918E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.138958E+10 | 1761.91 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.160392E+10 | 1761.91 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104288E+11 | 10265.18 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.941318E+10 | 10265.18 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.104004E+11 | 10265.18 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.997788E+10 | 10265.18 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.103047E+11 | 10265.18 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.996426E+10 | 10265.18 | 01-JUN-19:19 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.102503E+11 | 10265.18 | 03-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.103381E+11 | 10265.18 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.100155E+11 | 10265.18 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.104010E+11 | 10265.18 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.101030E+11 | 10265.18 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.104007E+11 | 10265.18 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.121998E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.941318E+10 | 10265.18 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.104288E+11 | 10265.18 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85091918.49 | 76.99 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 76846309.13 | 76.99 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 84415649.14 | 76.99 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 82445007.08 | 76.99 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 84753783.81 | 76.99 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 81790910.76 | 76.99 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 85418966.65 | 76.99 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 84415649.14 | 76.99 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 82467180.11 | 76.99 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 85080831.98 | 76.99 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 82117958.92 | 76.99 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 85430053.17 | 76.99 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.100027E+10 | 0.300992E+10 | ||||
Minimum of Months | 76846309.13 | 76.99 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 85430053.17 | 76.99 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85115186.72 | 77.01 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 76867322.62 | 77.01 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 84438732.44 | 77.01 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 82467551.52 | 77.01 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 84776959.58 | 77.01 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 81813276.33 | 77.01 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 85442324.32 | 77.01 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 84438732.44 | 77.01 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 82489730.61 | 77.01 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 85104097.18 | 77.01 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 82140413.93 | 77.01 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 85453413.86 | 77.01 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.100055E+10 | 0.301074E+10 | ||||
Minimum of Months | 76867322.62 | 77.01 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 85453413.86 | 77.01 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.232638E+10 | 2240.78 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.210051E+10 | 2240.78 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.233355E+10 | 2240.78 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.224750E+10 | 2240.78 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.233041E+10 | 2240.78 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.225781E+10 | 2240.78 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.232011E+10 | 2240.78 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.233445E+10 | 2240.78 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.224840E+10 | 2240.78 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.232548E+10 | 2240.78 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.225602E+10 | 2240.78 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.232011E+10 | 2240.78 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.274007E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.210051E+10 | 2240.78 | 0.00 | 0.00 | |
Maximum of Months | 0.233445E+10 | 2240.78 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85115186.72 | 77.01 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 76867322.62 | 77.01 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 84438732.44 | 77.01 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 82467551.52 | 77.01 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 84776959.58 | 77.01 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 81813276.33 | 77.01 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 85442324.32 | 77.01 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 84438732.44 | 77.01 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 82489730.61 | 77.01 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 85104097.18 | 77.01 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 82140413.93 | 77.01 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 85453413.86 | 77.01 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.100055E+10 | 0.301074E+10 | ||||
Minimum of Months | 76867322.62 | 77.01 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 85453413.86 | 77.01 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.304304E+10 | 3094.06 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.274302E+10 | 3094.06 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.297793E+10 | 3094.06 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.281285E+10 | 3094.06 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.286852E+10 | 3094.06 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.275994E+10 | 3094.06 | 01-JUN-19:30 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.284771E+10 | 3094.06 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.289727E+10 | 3094.06 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.285480E+10 | 3094.06 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.302326E+10 | 3094.06 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.293382E+10 | 3094.06 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.303432E+10 | 3094.06 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.347965E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.274302E+10 | 3094.06 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.304304E+10 | 3094.06 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.304304E+10 | 3094.06 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.274302E+10 | 3094.06 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.297793E+10 | 3094.06 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.281285E+10 | 3094.06 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.286852E+10 | 3094.06 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.275994E+10 | 3094.06 | 01-JUN-19:30 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.284771E+10 | 3094.06 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.289727E+10 | 3094.06 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.285480E+10 | 3094.06 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.302326E+10 | 3094.06 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.293382E+10 | 3094.06 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.303432E+10 | 3094.06 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.347965E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.274302E+10 | 3094.06 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.304304E+10 | 3094.06 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113146E+10 | 1089.83 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.102161E+10 | 1089.83 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.113495E+10 | 1089.83 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.109310E+10 | 1089.83 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.113342E+10 | 1089.83 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.109811E+10 | 1089.83 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.112841E+10 | 1089.83 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.113539E+10 | 1089.83 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.109354E+10 | 1089.83 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.113103E+10 | 1089.83 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.109724E+10 | 1089.83 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.112841E+10 | 1089.83 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.133267E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.102161E+10 | 1089.83 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.113539E+10 | 1089.83 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.246211E+10 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.222306E+10 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.246970E+10 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.237864E+10 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.246638E+10 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.238954E+10 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.245547E+10 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.247065E+10 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.237958E+10 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.246116E+10 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.238765E+10 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.245547E+10 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.289994E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.222306E+10 | 2371.52 | 0.00 | 0.00 | |
Maximum of Months | 0.247065E+10 | 2371.52 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.147273E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.132974E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.147727E+11 | 0.127855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.142280E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.147528E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.142932E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.146876E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.147784E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.142337E+11 | 0.123352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.147216E+11 | 0.127549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.142819E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.146876E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.173462E+12 | 0.150255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.132974E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.147784E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.731324E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.569274E+09 |
February | 0.179968E+10 | 0.660319E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 205548.47 | 0.399157E+09 |
March | 0.199990E+10 | 0.733578E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2591021.89 | 0.261240E+09 |
April | 0.192973E+10 | 0.706528E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11857849.69 | 0.163321E+09 |
May | 0.199475E+10 | 0.732592E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30516043.99 | 85531641.75 |
June | 0.193394E+10 | 0.709769E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75809703.29 | 32682721.25 |
July | 0.199054E+10 | 0.729351E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 95333306.75 | 17480129.69 |
August | 0.199896E+10 | 0.733860E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92453473.59 | 6016750.19 |
September | 0.192879E+10 | 0.706810E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33640298.46 | 49117154.33 |
October | 0.199148E+10 | 0.731042E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5860100.37 | 0.203844E+09 |
November | 0.192552E+10 | 0.709205E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 419896.77 | 0.303094E+09 |
December | 0.199054E+10 | 0.729351E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445253E+09 |
Annual Sum or Average | 0.234744E+11 | 0.861373E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348687E+09 | 0.253601E+10 |
Minimum of Months | 0.179968E+10 | 0.660319E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6016750.19 |
Maximum of Months | 0.199990E+10 | 0.733860E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 95333306.75 | 0.569274E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.846876E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224521E+09 |
February | 0.208403E+10 | 0.764651E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 274100.99 | 0.160318E+09 |
March | 0.231589E+10 | 0.849486E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1260568.44 | 0.111059E+09 |
April | 0.223463E+10 | 0.818162E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429543.67 | 73978193.02 |
May | 0.230993E+10 | 0.848344E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12274941.82 | 42202801.69 |
June | 0.223950E+10 | 0.821915E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29850308.04 | 17380385.78 |
July | 0.230505E+10 | 0.844592E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37446581.47 | 10460745.45 |
August | 0.231480E+10 | 0.849812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36190138.65 | 4413132.08 |
September | 0.223354E+10 | 0.818489E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13933507.25 | 25698437.59 |
October | 0.230614E+10 | 0.846549E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2879415.64 | 88083147.78 |
November | 0.222975E+10 | 0.821262E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 200610.41 | 0.126925E+09 |
December | 0.230505E+10 | 0.844592E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6357.41 | 0.179151E+09 |
Annual Sum or Average | 0.271834E+11 | 0.997473E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139746E+09 | 0.106419E+10 |
Minimum of Months | 0.208403E+10 | 0.764651E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4413132.08 |
Maximum of Months | 0.231589E+10 | 0.849812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37446581.47 | 0.224521E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.141236E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515477E+09 |
February | 0.440737E+09 | 0.127524E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1224563.37 | 0.362518E+09 |
March | 0.489771E+09 | 0.141672E+10 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4295925.98 | 0.238399E+09 |
April | 0.472586E+09 | 0.136448E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15820508.68 | 0.160034E+09 |
May | 0.488511E+09 | 0.141481E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30600132.10 | 91534170.85 |
June | 0.473617E+09 | 0.137074E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69514397.59 | 38685633.68 |
July | 0.487480E+09 | 0.140855E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86634195.26 | 23696309.77 |
August | 0.489542E+09 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84410925.13 | 9352009.12 |
September | 0.472357E+09 | 0.136502E+10 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34118641.39 | 56070839.96 |
October | 0.487709E+09 | 0.141182E+10 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8404378.91 | 0.191286E+09 |
November | 0.471555E+09 | 0.136965E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 839638.01 | 0.276819E+09 |
December | 0.487480E+09 | 0.140855E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109366.93 | 0.400798E+09 |
Annual Sum or Average | 0.574883E+10 | 0.166352E+11 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335973E+09 | 0.236467E+10 |
Minimum of Months | 0.440737E+09 | 0.127524E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9352009.12 |
Maximum of Months | 0.489771E+09 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86634195.26 | 0.515477E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.236418E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74.95 | 0.296668E+09 |
February | 0.339028E+09 | 0.213464E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 711089.91 | 0.207644E+09 |
March | 0.376747E+09 | 0.237147E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2618987.52 | 0.134822E+09 |
April | 0.363528E+09 | 0.228402E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9367886.32 | 89651855.22 |
May | 0.375778E+09 | 0.236828E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18200950.47 | 50488346.80 |
June | 0.364321E+09 | 0.229450E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40872884.24 | 21209318.83 |
July | 0.374985E+09 | 0.235780E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50472040.51 | 12872279.53 |
August | 0.376571E+09 | 0.237238E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49305692.91 | 4924010.69 |
September | 0.363352E+09 | 0.228493E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20400216.03 | 30526332.60 |
October | 0.375161E+09 | 0.236327E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4976374.21 | 0.107469E+09 |
November | 0.362735E+09 | 0.229268E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 499629.97 | 0.157007E+09 |
December | 0.374985E+09 | 0.235780E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63954.12 | 0.229673E+09 |
Annual Sum or Average | 0.442217E+10 | 0.278459E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197490E+09 | 0.134296E+10 |
Minimum of Months | 0.339028E+09 | 0.213464E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74.95 | 4924010.69 |
Maximum of Months | 0.376747E+09 | 0.237238E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50472040.51 | 0.296668E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.370859E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774848E+09 |
February | 0.139600E+10 | 0.334852E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 912552.20 | 0.551504E+09 |
March | 0.155131E+10 | 0.372002E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 3862598.77 | 0.369887E+09 |
April | 0.149688E+10 | 0.358285E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 17551066.26 | 0.239592E+09 |
May | 0.154732E+10 | 0.371502E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 41883437.39 | 0.128094E+09 |
June | 0.150015E+10 | 0.359929E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.105800E+09 | 43948578.38 |
July | 0.154405E+10 | 0.369859E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.136233E+09 | 24904320.66 |
August | 0.155059E+10 | 0.372145E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.138308E+09 | 8200434.75 |
September | 0.149615E+10 | 0.358428E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 52122396.72 | 73007249.09 |
October | 0.154478E+10 | 0.370717E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 10813035.70 | 0.287137E+09 |
November | 0.149361E+10 | 0.359643E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 696836.44 | 0.427120E+09 |
December | 0.154405E+10 | 0.369859E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 3052.10 | 0.616506E+09 |
Annual Sum or Average | 0.182090E+11 | 0.436808E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.508185E+09 | 0.354475E+10 |
Minimum of Months | 0.139600E+10 | 0.334852E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8200434.75 |
Maximum of Months | 0.155131E+10 | 0.372145E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.138308E+09 | 0.774848E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.160392E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131754E+10 |
February | 0.236489E+11 | 0.144265E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 355468.22 | 0.944330E+09 |
March | 0.262800E+11 | 0.154421E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4462755.20 | 0.657963E+09 |
April | 0.253579E+11 | 0.144233E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23261760.18 | 0.428509E+09 |
May | 0.262123E+11 | 0.145274E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63724943.67 | 0.243009E+09 |
June | 0.254132E+11 | 0.138958E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168616E+09 | 97665543.05 |
July | 0.261570E+11 | 0.143940E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211852E+09 | 58351901.92 |
August | 0.262677E+11 | 0.147645E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203585E+09 | 23326189.08 |
September | 0.253456E+11 | 0.148062E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72426110.96 | 0.146301E+09 |
October | 0.261693E+11 | 0.157538E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11692841.88 | 0.520784E+09 |
November | 0.253025E+11 | 0.154540E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 391905.78 | 0.754090E+09 |
December | 0.261570E+11 | 0.159911E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105740E+10 |
Annual Sum or Average | 0.308468E+12 | 0.179918E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760369E+09 | 0.624927E+10 |
Minimum of Months | 0.236489E+11 | 0.138958E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23326189.08 |
Maximum of Months | 0.262800E+11 | 0.160392E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211852E+09 | 0.131754E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.104288E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381988E+10 |
February | 0.702046E+11 | 0.941318E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2758627.76 | 0.274483E+10 |
March | 0.780153E+11 | 0.104004E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15972131.74 | 0.191916E+10 |
April | 0.752779E+11 | 0.997788E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77636632.37 | 0.127507E+10 |
May | 0.778146E+11 | 0.103047E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188299E+09 | 0.729281E+09 |
June | 0.754422E+11 | 0.996426E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481909E+09 | 0.293394E+09 |
July | 0.776503E+11 | 0.102503E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607819E+09 | 0.179209E+09 |
August | 0.779788E+11 | 0.103381E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585904E+09 | 73062098.13 |
September | 0.752414E+11 | 0.100155E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214391E+09 | 0.444808E+09 |
October | 0.776868E+11 | 0.104010E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38610014.10 | 0.152648E+10 |
November | 0.751137E+11 | 0.101030E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1770525.80 | 0.220304E+10 |
December | 0.776503E+11 | 0.104007E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308379E+10 |
Annual Sum or Average | 0.915726E+12 | 0.121998E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221507E+10 | 0.182920E+11 |
Minimum of Months | 0.702046E+11 | 0.941318E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73062098.13 |
Maximum of Months | 0.780153E+11 | 0.104288E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607819E+09 | 0.381988E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323195E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 476713.72 | 0.225281E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2933174.93 | 0.144256E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10004570.30 | 88171251.88 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23580481.96 | 39828481.21 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61070260.22 | 10319137.53 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78699214.06 | 4042509.92 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83507876.40 | 495272.77 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32988469.99 | 19577646.56 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6242169.98 | 0.107101E+09 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 446369.28 | 0.168996E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18603.36 | 0.250968E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299968E+09 | 0.138223E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495272.77 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83507876.40 | 0.323195E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 326.38 | 0.319714E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 670217.19 | 0.222660E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3104851.68 | 0.141309E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10492738.50 | 87366052.20 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23745478.60 | 39695838.63 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61059403.69 | 10334355.87 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78685323.64 | 4046358.83 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83570649.90 | 485765.77 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33362135.74 | 19438876.24 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6700469.81 | 0.104598E+09 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 602590.69 | 0.165019E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67585.00 | 0.246487E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302062E+09 | 0.136115E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 326.38 | 485765.77 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83570649.90 | 0.319714E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 85091918.49 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86477936.82 |
February | 0.00 | 76846309.13 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52592.26 | 61718135.54 |
March | 0.00 | 84415649.14 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 398282.66 | 45901200.54 |
April | 0.00 | 82445007.08 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1831665.77 | 30277604.96 |
May | 0.00 | 84753783.81 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4598336.39 | 16643350.45 |
June | 0.00 | 81790910.76 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12756299.54 | 6165867.12 |
July | 0.00 | 85418966.65 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16479140.99 | 3501747.17 |
August | 0.00 | 84415649.14 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16444654.61 | 1163729.00 |
September | 0.00 | 82467180.11 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5860963.23 | 9665540.17 |
October | 0.00 | 85080831.98 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 991544.87 | 36030283.60 |
November | 0.00 | 82117958.92 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16093.82 | 53281155.01 |
December | 0.00 | 85430053.17 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71236557.17 |
Annual Sum or Average | 0.00 | 0.100027E+10 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59429574.16 | 0.422063E+09 |
Minimum of Months | 0.00 | 76846309.13 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1163729.00 |
Maximum of Months | 0.00 | 85430053.17 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16479140.99 | 86477936.82 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 85115186.72 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.49 | 90265424.47 |
February | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 261645.13 | 62836209.54 |
March | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1034028.55 | 39455587.94 |
April | 0.293479E+09 | 82467551.52 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3497288.83 | 24205893.06 |
May | 0.303504E+09 | 84776959.58 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7376523.98 | 10867887.45 |
June | 0.293842E+09 | 81813276.33 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17635153.54 | 2830966.11 |
July | 0.303141E+09 | 85442324.32 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22454623.63 | 1047761.14 |
August | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23954681.61 | 112971.55 |
September | 0.293479E+09 | 82489730.61 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10161529.23 | 5360707.91 |
October | 0.303322E+09 | 85104097.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2261063.23 | 29204172.67 |
November | 0.293661E+09 | 82140413.93 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 234428.76 | 46360805.93 |
December | 0.303141E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38936.95 | 69894094.88 |
Annual Sum or Average | 0.357224E+10 | 0.100055E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88910259.91 | 0.382442E+09 |
Minimum of Months | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.49 | 112971.55 |
Maximum of Months | 0.303685E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23954681.61 | 90265424.47 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323746E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 459918.56 | 0.226267E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2983051.34 | 0.145844E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9936439.87 | 89532259.99 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23337862.41 | 40576523.17 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60839651.49 | 10705202.53 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78447805.29 | 4167488.36 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83285511.37 | 551320.07 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32883375.49 | 19913788.00 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6217996.39 | 0.107971E+09 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 483345.64 | 0.169734E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18671.75 | 0.251433E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298894E+09 | 0.139044E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551320.07 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83285511.37 | 0.323746E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.59 | 0.319992E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 619606.92 | 0.223419E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3208626.89 | 0.142957E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10057212.09 | 88800441.58 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23359200.01 | 40492722.69 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60829826.08 | 10716714.85 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78440964.14 | 4163561.72 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83309984.61 | 544393.88 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32979445.33 | 19825071.14 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6429420.06 | 0.105815E+09 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 688878.05 | 0.165334E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 97928.70 | 0.246764E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300021E+09 | 0.136882E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.59 | 544393.88 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83309984.61 | 0.319992E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.232638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396881E+09 |
February | 0.348285E+10 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 680803.08 | 0.279232E+09 |
March | 0.387034E+10 | 0.233355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2928266.47 | 0.187669E+09 |
April | 0.373454E+10 | 0.224750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10190709.68 | 0.126813E+09 |
May | 0.386038E+10 | 0.233041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21945837.88 | 71485133.82 |
June | 0.374269E+10 | 0.225781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52105716.81 | 30222246.52 |
July | 0.385223E+10 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65298100.22 | 18628532.61 |
August | 0.386853E+10 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63170661.83 | 7580037.03 |
September | 0.373273E+10 | 0.224840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24414268.94 | 44224422.46 |
October | 0.385404E+10 | 0.232548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5545214.93 | 0.149279E+09 |
November | 0.372639E+10 | 0.225602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619988.13 | 0.212959E+09 |
December | 0.385223E+10 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65366.27 | 0.308331E+09 |
Annual Sum or Average | 0.454292E+11 | 0.274007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246965E+09 | 0.183330E+10 |
Minimum of Months | 0.348285E+10 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7580037.03 |
Maximum of Months | 0.387034E+10 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65298100.22 | 0.396881E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322451E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 467221.23 | 0.224910E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2857318.80 | 0.143891E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9782828.22 | 88210642.76 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23137151.58 | 40164935.25 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60387621.20 | 10481079.95 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77883652.81 | 4071300.48 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82601612.81 | 484031.89 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32456579.73 | 19578912.77 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6112512.37 | 0.106793E+09 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 436068.99 | 0.168505E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16916.52 | 0.249982E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296139E+09 | 0.137952E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484031.89 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82601612.81 | 0.322451E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4698.96 | 0.320011E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 692148.62 | 0.222742E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3057384.76 | 0.140786E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10223170.55 | 87377960.60 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23254583.99 | 40025166.56 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60370041.48 | 10493001.05 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77862085.68 | 4072733.68 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82668846.11 | 474401.51 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32845804.18 | 19436754.86 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6623739.48 | 0.104064E+09 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 622061.80 | 0.164325E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85709.90 | 0.245938E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298310E+09 | 0.135975E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4698.96 | 474401.51 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82668846.11 | 0.320011E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 85115186.72 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169361E+09 |
February | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 221545.96 | 0.117998E+09 |
March | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1453992.70 | 75312868.47 |
April | 0.293479E+09 | 82467551.52 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973565.34 | 45644567.46 |
May | 0.303504E+09 | 84776959.58 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11894823.87 | 20561470.65 |
June | 0.293842E+09 | 81813276.33 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31002690.03 | 5356543.29 |
July | 0.303141E+09 | 85442324.32 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39924813.85 | 2077917.29 |
August | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42295028.03 | 248400.66 |
September | 0.293479E+09 | 82489730.61 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16558126.99 | 10149905.19 |
October | 0.303322E+09 | 85104097.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3051038.16 | 55973327.84 |
November | 0.293661E+09 | 82140413.93 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 185917.07 | 88861291.63 |
December | 0.303141E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8342.07 | 0.132063E+09 |
Annual Sum or Average | 0.357224E+10 | 0.100055E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151570E+09 | 0.723608E+09 |
Minimum of Months | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248400.66 |
Maximum of Months | 0.303685E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42295028.03 | 0.169361E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.304304E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904027E+09 |
February | 0.415303E+11 | 0.274302E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 372436.73 | 0.652021E+09 |
March | 0.461508E+11 | 0.297793E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2266947.44 | 0.455443E+09 |
April | 0.445315E+11 | 0.281285E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11985084.48 | 0.304313E+09 |
May | 0.460320E+11 | 0.286852E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32463465.05 | 0.174606E+09 |
June | 0.446286E+11 | 0.275994E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96535321.13 | 69538947.86 |
July | 0.459349E+11 | 0.284771E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125916E+09 | 43651580.98 |
August | 0.461292E+11 | 0.289727E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122138E+09 | 18380470.40 |
September | 0.445099E+11 | 0.285480E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41511199.44 | 0.106852E+09 |
October | 0.459565E+11 | 0.302326E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6656116.40 | 0.358958E+09 |
November | 0.444343E+11 | 0.293382E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117523.71 | 0.516639E+09 |
December | 0.459349E+11 | 0.303432E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728564E+09 |
Annual Sum or Average | 0.541708E+12 | 0.347965E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439962E+09 | 0.433299E+10 |
Minimum of Months | 0.415303E+11 | 0.274302E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18380470.40 |
Maximum of Months | 0.461508E+11 | 0.304304E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125916E+09 | 0.904027E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.304304E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.915108E+09 |
February | 0.415303E+11 | 0.274302E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 250798.36 | 0.659907E+09 |
March | 0.461508E+11 | 0.297793E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2157804.84 | 0.460842E+09 |
April | 0.445315E+11 | 0.281285E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11521521.71 | 0.306943E+09 |
May | 0.460320E+11 | 0.286852E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31886138.98 | 0.175699E+09 |
June | 0.446286E+11 | 0.275994E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96050551.15 | 69698414.14 |
July | 0.459349E+11 | 0.284771E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125537E+09 | 43806141.49 |
August | 0.461292E+11 | 0.289727E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121661E+09 | 18469680.66 |
September | 0.445099E+11 | 0.285480E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40809702.87 | 0.107630E+09 |
October | 0.459565E+11 | 0.302326E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6173575.56 | 0.362669E+09 |
November | 0.444343E+11 | 0.293382E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57276.96 | 0.523291E+09 |
December | 0.459349E+11 | 0.303432E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737604E+09 |
Annual Sum or Average | 0.541708E+12 | 0.347965E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436105E+09 | 0.438167E+10 |
Minimum of Months | 0.415303E+11 | 0.274302E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18469680.66 |
Maximum of Months | 0.461508E+11 | 0.304304E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125537E+09 | 0.915108E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113146E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829785E+09 |
February | 0.369574E+10 | 0.102161E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 140754.04 | 0.596629E+09 |
March | 0.410691E+10 | 0.113495E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1784125.59 | 0.413868E+09 |
April | 0.396281E+10 | 0.109310E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 9057978.78 | 0.273569E+09 |
May | 0.409635E+10 | 0.113342E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 27949400.58 | 0.155584E+09 |
June | 0.397146E+10 | 0.109811E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 85621919.63 | 61213986.52 |
July | 0.408770E+10 | 0.112841E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.112291E+09 | 38455013.97 |
August | 0.410499E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.108850E+09 | 16035630.17 |
September | 0.396089E+10 | 0.109354E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 36003139.36 | 95222480.53 |
October | 0.408962E+10 | 0.113103E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 5229583.56 | 0.325498E+09 |
November | 0.395417E+10 | 0.109724E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 12507.49 | 0.470594E+09 |
December | 0.408770E+10 | 0.112841E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667169E+09 |
Annual Sum or Average | 0.482060E+11 | 0.133267E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.386941E+09 | 0.394362E+10 |
Minimum of Months | 0.369574E+10 | 0.102161E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16035630.17 |
Maximum of Months | 0.410691E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.112291E+09 | 0.829785E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.246211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704698E+09 |
February | 0.368610E+10 | 0.222306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 928758.50 | 0.494656E+09 |
March | 0.409620E+10 | 0.246970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4263976.00 | 0.326616E+09 |
April | 0.395248E+10 | 0.237864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14927204.42 | 0.219196E+09 |
May | 0.408566E+10 | 0.246638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32994291.75 | 0.126023E+09 |
June | 0.396110E+10 | 0.238954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86645871.19 | 52468685.17 |
July | 0.407704E+10 | 0.245547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111594E+09 | 31474737.49 |
August | 0.409429E+10 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108149E+09 | 12526843.22 |
September | 0.395056E+10 | 0.237958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39987196.05 | 73993276.91 |
October | 0.407896E+10 | 0.246116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8627004.03 | 0.255970E+09 |
November | 0.394385E+10 | 0.238765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 760277.37 | 0.372554E+09 |
December | 0.407704E+10 | 0.245547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50287.75 | 0.546626E+09 |
Annual Sum or Average | 0.480803E+11 | 0.289994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408928E+09 | 0.321680E+10 |
Minimum of Months | 0.368610E+10 | 0.222306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12526843.22 |
Maximum of Months | 0.409620E+10 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111594E+09 | 0.704698E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 14185.34 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 14185.34 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 14185.34 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 14185.34 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 14185.34 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 14185.34 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 14185.34 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 14185.34 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 14185.34 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 14185.34 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 14185.34 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 14185.34 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 14185.34 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 14185.34 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 704.41 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 354.85 | 27-JAN-08:00 |
February | 1169.53 | 01-FEB-00:10 | 704.41 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.70 | 28-FEB-14:30 | 445.23 | 12-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 704.41 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.40 | 30-MAR-14:30 | 246.25 | 19-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 704.41 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.24 | 12-APR-14:00 | 259.87 | 06-APR-05:00 |
May | 1169.53 | 01-MAY-00:10 | 704.41 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.22 | 19-MAY-17:00 | 160.60 | 11-MAY-05:25 |
June | 1169.53 | 01-JUN-00:10 | 704.41 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.65 | 06-JUN-15:00 | 123.56 | 10-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 704.41 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.14 | 08-JUL-15:00 | 60.74 | 28-JUL-23:00 |
August | 1169.53 | 01-AUG-00:10 | 704.41 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.79 | 02-AUG-16:00 | 51.13 | 25-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 704.41 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.81 | 07-SEP-16:00 | 114.27 | 14-SEP-05:10 |
October | 1169.53 | 01-OCT-23:10 | 704.41 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.53 | 10-OCT-16:00 | 230.88 | 26-OCT-07:00 |
November | 1169.53 | 01-NOV-00:10 | 704.41 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.60 | 19-NOV-15:40 | 303.45 | 22-NOV-07:00 |
December | 1169.53 | 01-DEC-00:10 | 704.41 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 338.32 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 704.41 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.13 | |||||
Maximum of Months | 1169.53 | 704.41 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 138.14 | 445.23 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 815.72 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 138.81 | 27-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 815.72 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.01 | 26-FEB-15:00 | 171.87 | 12-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 815.72 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.69 | 30-MAR-14:00 | 100.73 | 19-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 815.72 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.98 | 12-APR-14:00 | 106.59 | 06-APR-05:00 |
May | 1354.32 | 01-MAY-00:10 | 815.72 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.29 | 30-MAY-14:00 | 71.22 | 11-MAY-05:30 |
June | 1354.32 | 01-JUN-00:10 | 815.72 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.12 | 06-JUN-15:00 | 56.26 | 10-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 815.72 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.99 | 08-JUL-16:00 | 29.89 | 28-JUL-23:00 |
August | 1354.32 | 01-AUG-00:10 | 815.72 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.73 | 01-AUG-15:00 | 25.34 | 25-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 815.72 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.41 | 07-SEP-15:00 | 52.01 | 14-SEP-05:10 |
October | 1354.32 | 01-OCT-23:10 | 815.72 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.19 | 10-OCT-16:00 | 95.64 | 26-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 815.72 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.16 | 19-NOV-15:00 | 120.59 | 22-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 815.72 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 | 12-DEC-14:00 | 131.88 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 815.72 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 | |||||
Maximum of Months | 1354.32 | 815.72 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 54.99 | 171.87 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 1360.40 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 323.69 | 27-JAN-08:00 |
February | 286.42 | 01-FEB-00:10 | 1360.40 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.07 | 26-FEB-15:00 | 406.17 | 12-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 1360.40 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.07 | 30-MAR-15:50 | 224.62 | 19-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 1360.40 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.94 | 12-APR-14:00 | 241.69 | 06-APR-05:00 |
May | 286.42 | 01-MAY-00:10 | 1360.40 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.87 | 19-MAY-16:50 | 159.15 | 11-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 1360.40 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.58 | 06-JUN-15:00 | 128.01 | 10-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 1360.40 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.91 | 08-JUL-16:00 | 67.59 | 28-JUL-23:00 |
August | 286.42 | 01-AUG-00:10 | 1360.40 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.60 | 01-AUG-16:40 | 57.27 | 25-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 1360.40 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.79 | 07-SEP-16:00 | 117.99 | 14-SEP-05:43 |
October | 286.42 | 01-OCT-23:10 | 1360.40 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.22 | 10-OCT-16:00 | 215.75 | 26-OCT-07:00 |
November | 286.42 | 01-NOV-00:10 | 1360.40 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.26 | 19-NOV-15:00 | 276.79 | 22-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 1360.40 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.68 | 12-DEC-14:00 | 308.64 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.27 | |||||
Maximum of Months | 286.42 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 127.91 | 406.17 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 227.72 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 | 31-JAN-15:00 | 186.76 | 27-JAN-08:00 |
February | 220.32 | 01-FEB-00:10 | 227.72 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.66 | 26-FEB-15:00 | 234.35 | 12-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 227.72 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.32 | 30-MAR-14:00 | 129.59 | 19-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 227.72 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.82 | 12-APR-14:00 | 138.22 | 06-APR-05:00 |
May | 220.32 | 01-MAY-00:10 | 227.72 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.43 | 19-MAY-16:40 | 90.34 | 11-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 227.72 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.83 | 06-JUN-15:00 | 73.19 | 10-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 227.72 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.43 | 08-JUL-16:00 | 37.29 | 28-JUL-23:00 |
August | 220.32 | 01-AUG-00:10 | 227.72 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.46 | 01-AUG-16:50 | 31.82 | 25-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 227.72 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.64 | 07-SEP-16:00 | 67.40 | 29-SEP-04:00 |
October | 220.32 | 01-OCT-23:10 | 227.72 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.06 | 10-OCT-16:00 | 122.34 | 26-OCT-05:40 |
November | 220.32 | 01-NOV-00:10 | 227.72 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.55 | 19-NOV-15:00 | 159.69 | 22-NOV-06:00 |
December | 220.32 | 01-DEC-00:10 | 227.72 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.38 | 12-DEC-14:00 | 178.07 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 227.72 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 | 31.82 | |||||
Maximum of Months | 220.32 | 227.72 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 73.43 | 234.35 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 357.21 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 489.82 | 27-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 357.21 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 37.91 | 26-FEB-15:00 | 593.24 | 12-FEB-07:10 |
March | 907.20 | 01-MAR-00:10 | 357.21 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 77.43 | 30-MAR-15:50 | 352.86 | 19-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 357.21 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 92.39 | 17-APR-16:20 | 360.37 | 06-APR-05:10 |
May | 907.20 | 01-MAY-00:10 | 357.21 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 121.89 | 29-MAY-17:00 | 260.29 | 11-MAY-05:40 |
June | 907.20 | 01-JUN-00:10 | 357.21 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 162.36 | 06-JUN-17:00 | 178.17 | 08-JUN-06:00 |
July | 907.20 | 01-JUL-00:10 | 357.21 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 199.93 | 08-JUL-16:00 | 98.95 | 28-JUL-23:00 |
August | 907.20 | 01-AUG-00:10 | 357.21 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 180.10 | 01-AUG-17:00 | 81.81 | 25-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 357.21 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 131.79 | 07-SEP-16:00 | 172.93 | 14-SEP-05:43 |
October | 907.20 | 01-OCT-23:10 | 357.21 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 108.72 | 10-OCT-16:00 | 333.44 | 26-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 357.21 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 39.77 | 05-NOV-16:00 | 422.88 | 22-NOV-07:10 |
December | 907.20 | 01-DEC-00:10 | 357.21 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.79 | 12-DEC-14:00 | 468.90 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 81.81 | ||||||
Maximum of Months | 907.20 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 199.93 | 593.24 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1761.91 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 801.80 | 14-JAN-06:00 |
February | 15368.40 | 01-FEB-00:10 | 1761.91 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.62 | 28-FEB-14:30 | 984.40 | 12-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1761.91 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.76 | 30-MAR-14:30 | 568.13 | 19-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1761.91 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.13 | 12-APR-14:00 | 614.71 | 06-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1761.91 | 01-MAY-19:19 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.03 | 30-MAY-14:00 | 412.64 | 11-MAY-05:30 |
June | 15368.40 | 01-JUN-00:10 | 1761.91 | 01-JUN-19:30 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.06 | 06-JUN-15:00 | 331.19 | 10-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1761.91 | 03-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 306.10 | 08-JUL-16:00 | 175.55 | 28-JUL-23:10 |
August | 15368.40 | 01-AUG-00:10 | 1761.91 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.06 | 02-AUG-16:00 | 143.20 | 25-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 1761.91 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.53 | 07-SEP-16:00 | 310.53 | 29-SEP-04:15 |
October | 15368.40 | 01-OCT-23:10 | 1761.91 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.11 | 10-OCT-16:00 | 557.70 | 26-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1761.91 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.97 | 19-NOV-15:40 | 699.74 | 22-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1761.91 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 752.89 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1761.91 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.20 | |||||
Maximum of Months | 15368.40 | 1761.91 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 306.10 | 984.40 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 10265.18 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2351.26 | 14-JAN-06:00 |
February | 45622.98 | 01-FEB-00:10 | 10265.18 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.19 | 28-FEB-14:30 | 2846.42 | 12-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 10265.18 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 308.35 | 30-MAR-14:00 | 1698.05 | 19-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 10265.18 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 404.99 | 12-APR-14:00 | 1817.38 | 06-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 10265.18 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 517.12 | 30-MAY-14:00 | 1206.69 | 11-MAY-05:30 |
June | 45622.98 | 01-JUN-00:10 | 10265.18 | 01-JUN-19:19 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 750.26 | 06-JUN-15:00 | 966.59 | 10-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 10265.18 | 03-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 903.52 | 08-JUL-16:00 | 501.67 | 28-JUL-23:07 |
August | 45622.98 | 01-AUG-00:10 | 10265.18 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 786.40 | 01-AUG-15:00 | 415.06 | 25-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 10265.18 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 547.33 | 07-SEP-15:00 | 912.51 | 29-SEP-04:10 |
October | 45622.98 | 01-OCT-23:10 | 10265.18 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 427.48 | 10-OCT-16:00 | 1640.14 | 26-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 10265.18 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.04 | 19-NOV-15:00 | 2060.03 | 22-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 10265.18 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 2210.32 | 18-DEC-05:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 10265.18 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.06 | |||||
Maximum of Months | 45622.98 | 10265.18 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 903.52 | 2846.42 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 207.09 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 26-FEB-16:10 | 259.59 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 30-MAR-16:00 | 144.02 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 17-APR-15:10 | 151.93 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.90 | 19-MAY-16:00 | 93.01 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.77 | 06-JUN-15:10 | 69.24 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.13 | 08-JUL-15:10 | 28.71 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.25 | 02-AUG-16:00 | 19.11 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 07-SEP-16:00 | 64.93 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 10-OCT-16:00 | 135.09 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 05-NOV-16:00 | 177.21 | 22-NOV-06:06 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.39 | 12-DEC-16:07 | 197.49 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.11 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 98.13 | 259.59 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 | 31-JAN-15:00 | 207.07 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 26-FEB-16:08 | 259.58 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.04 | 30-MAR-16:00 | 144.00 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 17-APR-15:08 | 151.92 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.89 | 19-MAY-16:00 | 93.00 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.76 | 06-JUN-15:10 | 69.24 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.12 | 08-JUL-15:10 | 28.67 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.24 | 02-AUG-16:00 | 19.11 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 07-SEP-16:00 | 64.93 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.92 | 10-OCT-16:00 | 135.07 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.28 | 05-NOV-16:00 | 177.20 | 22-NOV-06:06 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 | 12-DEC-14:00 | 197.48 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 | 19.11 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 98.12 | 259.58 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 76.99 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 54.01 | 27-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 76.99 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.97 | 26-FEB-15:00 | 67.69 | 12-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 76.99 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 30-MAR-14:00 | 40.12 | 19-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 76.99 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.09 | 12-APR-14:00 | 41.70 | 06-APR-05:10 |
May | 0.00 | 01-MAY-00:10 | 76.99 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 19-MAY-14:00 | 28.21 | 11-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 76.99 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 | 06-JUN-15:00 | 22.22 | 10-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 76.99 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 | 08-JUL-15:00 | 11.10 | 28-JUL-23:00 |
August | 0.00 | 01-AUG-00:10 | 76.99 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 02-AUG-16:00 | 9.15 | 25-AUG-06:10 |
September | 0.00 | 01-SEP-00:10 | 76.99 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.85 | 07-SEP-16:00 | 21.16 | 14-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 76.99 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.89 | 10-OCT-16:00 | 38.46 | 26-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 76.99 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 | 05-NOV-16:00 | 47.38 | 22-NOV-07:20 |
December | 0.00 | 01-DEC-00:10 | 76.99 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 53.05 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 76.99 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.15 | |||||
Maximum of Months | 0.00 | 76.99 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 | 67.69 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 77.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 | 31-JAN-15:00 | 57.80 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 77.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.64 | 26-FEB-15:00 | 72.45 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 77.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 | 30-MAR-15:55 | 40.19 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 77.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 17-APR-15:10 | 42.40 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 77.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 19-MAY-16:00 | 25.96 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 77.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | 06-JUN-15:10 | 19.32 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 77.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.39 | 08-JUL-15:10 | 8.12 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 77.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.63 | 02-AUG-16:00 | 5.33 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 77.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.82 | 07-SEP-16:00 | 18.12 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 77.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 | 10-OCT-16:00 | 37.70 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 77.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 | 05-NOV-16:00 | 49.46 | 22-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 77.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 | 12-DEC-14:00 | 55.12 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 | 5.33 | |||||
Maximum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 27.39 | 72.45 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 207.08 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 26-FEB-16:08 | 259.60 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 30-MAR-16:00 | 144.02 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 17-APR-15:10 | 151.94 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.89 | 19-MAY-16:00 | 93.01 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.77 | 06-JUN-15:10 | 69.24 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.13 | 08-JUL-15:10 | 28.59 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.25 | 02-AUG-16:00 | 19.11 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 07-SEP-16:00 | 64.93 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 10-OCT-16:00 | 135.09 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 05-NOV-16:00 | 177.22 | 22-NOV-06:06 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.39 | 12-DEC-16:07 | 197.49 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.11 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 98.13 | 259.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 | 31-JAN-15:00 | 207.07 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 26-FEB-16:08 | 259.58 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 30-MAR-15:55 | 144.01 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 17-APR-15:10 | 151.92 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.89 | 19-MAY-16:00 | 93.00 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.76 | 06-JUN-15:10 | 69.24 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.13 | 08-JUL-15:10 | 28.54 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.24 | 02-AUG-16:00 | 19.11 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 07-SEP-16:00 | 64.93 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 10-OCT-16:00 | 135.07 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 05-NOV-16:00 | 177.20 | 22-NOV-06:06 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 | 12-DEC-14:00 | 197.47 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 | 19.11 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 98.13 | 259.58 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 2240.78 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 249.43 | 27-JAN-08:00 |
February | 2263.36 | 01-FEB-00:10 | 2240.78 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 26-FEB-15:00 | 312.89 | 12-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 2240.78 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.16 | 30-MAR-14:00 | 176.19 | 19-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 2240.78 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.75 | 12-APR-14:00 | 189.24 | 06-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 2240.78 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.11 | 30-MAY-14:00 | 124.59 | 11-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 2240.78 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.46 | 06-JUN-15:00 | 100.77 | 10-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 2240.78 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.91 | 08-JUL-16:00 | 52.19 | 28-JUL-23:00 |
August | 2263.36 | 01-AUG-00:10 | 2240.78 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.23 | 01-AUG-17:00 | 43.82 | 25-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 2240.78 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.95 | 07-SEP-16:00 | 92.89 | 29-SEP-04:00 |
October | 2263.36 | 01-OCT-23:10 | 2240.78 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.27 | 10-OCT-16:00 | 166.80 | 26-OCT-05:00 |
November | 2263.36 | 01-NOV-00:10 | 2240.78 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.27 | 19-NOV-15:00 | 213.33 | 22-NOV-06:50 |
December | 2263.36 | 01-DEC-00:10 | 2240.78 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.30 | 12-DEC-15:00 | 237.82 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.82 | ||||
Maximum of Months | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.91 | 312.89 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 207.57 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 | 26-FEB-16:10 | 260.11 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 | 30-MAR-16:00 | 144.47 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 | 17-APR-15:10 | 152.39 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.52 | 19-MAY-16:00 | 93.44 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.41 | 06-JUN-15:10 | 69.66 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.70 | 08-JUL-15:10 | 27.22 | 28-JUL-23:07 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.88 | 02-AUG-16:00 | 19.51 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.05 | 07-SEP-16:00 | 65.35 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.56 | 10-OCT-16:00 | 135.54 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 05-NOV-16:00 | 177.68 | 22-NOV-06:06 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 12-DEC-16:08 | 197.96 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 97.70 | 260.11 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 | 31-JAN-15:00 | 207.56 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 | 26-FEB-16:08 | 260.10 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 | 30-MAR-16:00 | 144.46 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 | 17-APR-15:10 | 152.38 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.52 | 19-MAY-16:00 | 93.43 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.40 | 06-JUN-15:10 | 69.66 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.69 | 08-JUL-15:50 | 27.22 | 28-JUL-23:07 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.88 | 02-AUG-16:00 | 19.51 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.05 | 07-SEP-16:00 | 65.35 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.55 | 10-OCT-16:00 | 135.52 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 05-NOV-16:00 | 177.67 | 22-NOV-06:06 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.12 | 12-DEC-14:00 | 197.96 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 | 19.51 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 97.69 | 260.10 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 77.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 106.20 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 77.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 | 26-FEB-16:10 | 133.08 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 77.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 30-MAR-16:00 | 73.92 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 77.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.47 | 17-APR-15:10 | 77.97 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 77.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.97 | 19-MAY-16:00 | 47.81 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 77.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.16 | 06-JUN-15:10 | 35.64 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 77.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.02 | 08-JUL-15:10 | 14.38 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 77.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.96 | 02-AUG-16:00 | 9.98 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 77.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.30 | 07-SEP-16:00 | 33.44 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 77.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.91 | 10-OCT-16:00 | 69.35 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 77.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 05-NOV-16:00 | 90.91 | 22-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 77.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 | 12-DEC-16:10 | 101.29 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.98 | |||||
Maximum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 50.02 | 133.08 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3094.06 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 549.96 | 14-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 3094.06 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.32 | 26-FEB-15:00 | 670.36 | 12-FEB-07:10 |
March | 26988.77 | 01-MAR-00:10 | 3094.06 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.27 | 30-MAR-14:00 | 403.36 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3094.06 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.55 | 12-APR-14:00 | 422.68 | 06-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 3094.06 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.39 | 19-MAY-14:00 | 284.69 | 11-MAY-05:25 |
June | 26988.77 | 01-JUN-00:10 | 3094.06 | 01-JUN-19:30 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.15 | 06-JUN-15:00 | 218.60 | 10-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3094.06 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.27 | 08-JUL-15:00 | 114.26 | 28-JUL-23:07 |
August | 26988.77 | 01-AUG-00:10 | 3094.06 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.68 | 02-AUG-16:00 | 94.78 | 25-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 3094.06 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.68 | 07-SEP-16:00 | 207.94 | 29-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 3094.06 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.74 | 10-OCT-16:00 | 380.82 | 26-OCT-05:10 |
November | 26988.77 | 01-NOV-00:10 | 3094.06 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 19-NOV-15:00 | 480.86 | 22-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 3094.06 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 515.95 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.78 | |||||
Maximum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 194.27 | 670.36 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3094.06 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 553.50 | 14-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 3094.06 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.36 | 28-FEB-14:00 | 674.70 | 12-FEB-07:10 |
March | 26988.77 | 01-MAR-00:10 | 3094.06 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.52 | 30-MAR-14:30 | 403.36 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3094.06 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.69 | 12-APR-14:00 | 422.69 | 06-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 3094.06 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.39 | 19-MAY-14:00 | 285.59 | 11-MAY-05:25 |
June | 26988.77 | 01-JUN-00:10 | 3094.06 | 01-JUN-19:30 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.15 | 06-JUN-15:00 | 218.60 | 10-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3094.06 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.27 | 08-JUL-15:00 | 114.26 | 28-JUL-23:07 |
August | 26988.77 | 01-AUG-00:10 | 3094.06 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.68 | 02-AUG-16:00 | 94.78 | 25-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 3094.06 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.68 | 07-SEP-16:00 | 207.95 | 29-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 3094.06 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.74 | 10-OCT-16:00 | 380.82 | 26-OCT-05:10 |
November | 26988.77 | 01-NOV-00:10 | 3094.06 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.59 | 19-NOV-15:00 | 484.00 | 22-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 3094.06 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 519.47 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.78 | |||||
Maximum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 194.27 | 674.70 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1089.83 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 500.52 | 27-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1089.83 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 13.86 | 26-FEB-15:00 | 616.12 | 12-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1089.83 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 51.89 | 30-MAR-15:50 | 361.00 | 19-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1089.83 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 68.71 | 12-APR-14:00 | 374.68 | 06-APR-05:10 |
May | 2401.70 | 01-MAY-00:10 | 1089.83 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 91.79 | 19-MAY-15:40 | 268.68 | 11-MAY-05:25 |
June | 2401.70 | 01-JUN-00:10 | 1089.83 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 141.70 | 06-JUN-15:00 | 193.63 | 10-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1089.83 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 174.05 | 08-JUL-15:00 | 102.29 | 28-JUL-23:10 |
August | 2401.70 | 01-AUG-00:10 | 1089.83 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 152.07 | 02-AUG-16:00 | 84.80 | 25-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1089.83 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 106.41 | 07-SEP-16:00 | 185.90 | 29-SEP-04:00 |
October | 2401.70 | 01-OCT-23:10 | 1089.83 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 83.19 | 10-OCT-16:00 | 341.13 | 26-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 1089.83 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 4.44 | 05-NOV-16:00 | 434.01 | 22-NOV-07:00 |
December | 2401.70 | 01-DEC-00:10 | 1089.83 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 479.20 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1089.83 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 84.80 | ||||||
Maximum of Months | 2401.70 | 1089.83 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 174.05 | 616.12 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 442.38 | 27-JAN-08:00 |
February | 2395.44 | 01-FEB-00:10 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.89 | 28-FEB-14:00 | 554.71 | 12-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.80 | 30-MAR-14:00 | 307.42 | 19-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.78 | 12-APR-14:00 | 324.34 | 06-APR-05:00 |
May | 2395.44 | 01-MAY-00:10 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.18 | 19-MAY-17:00 | 210.81 | 11-MAY-05:30 |
June | 2395.44 | 01-JUN-00:10 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.54 | 06-JUN-15:00 | 170.37 | 10-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.20 | 08-JUL-15:00 | 88.43 | 28-JUL-23:00 |
August | 2395.44 | 01-AUG-00:10 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.63 | 02-AUG-16:00 | 74.07 | 25-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.94 | 07-SEP-16:00 | 155.05 | 29-SEP-04:10 |
October | 2395.44 | 01-OCT-23:10 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.13 | 10-OCT-16:00 | 288.31 | 26-OCT-07:00 |
November | 2395.44 | 01-NOV-00:10 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.63 | 19-NOV-15:00 | 378.45 | 22-NOV-06:30 |
December | 2395.44 | 01-DEC-00:10 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.30 | 12-DEC-15:00 | 421.84 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.07 | ||||
Maximum of Months | 2395.44 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.20 | 554.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 32190.18 | 28-JAN-23:01 | 89459.16 | 47285.09 | 42584.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21252.33 | 04-FEB-16:33 | 11501.89 | 11821.18 | 11178.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20374.59 | 01-MAR-05:52 | 115018.92 | 31522.79 | 31938.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19486.03 | 25-APR-23:59 | 80513.24 | 22065.95 | 22356.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20290.52 | 11-MAY-06:09 | 51119.52 | 78807.87 | 63876.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15838.03 | 10-JUN-18:02 | 46007.57 | 66198.40 | 51101.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16463.96 | 20-JUL-18:10 | 53675.50 | 75655.77 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19989.16 | 31-AUG-21:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23234.19 | 28-SEP-21:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 37132.39 | 06-OCT-05:32 | 53675.50 | 37827.34 | 31938.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36579.39 | 30-NOV-07:11 | 35783.66 | 55165.51 | 44713.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 35728.93 | 09-DEC-22:47 | 26837.75 | 28371.05 | 22356.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15838.03 | 10223.90 | 11821.18 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37132.39 | 115018.92 | 78807.87 | 63876.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2182.80 | 29-JAN-09:53 | 6497.40 | 2348.05 | 2886.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.07 |
February | 2580.96 | 04-FEB-16:33 | 1169.53 | 587.01 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.03 |
March | 2389.54 | 30-MAR-14:10 | 389.84 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 42.40 | 0.00 |
April | 2898.66 | 15-APR-13:23 | 1169.53 | 587.01 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 36.18 | 0.00 |
May | 2222.68 | 16-MAY-18:10 | 5457.82 | 3756.88 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 51.10 | 0.00 |
June | 2469.36 | 13-JUN-18:15 | 1819.27 | 1252.29 | 1299.04 | 0.00 | 0.00 | 0.00 | 0.00 | 84.60 | 0.00 |
July | 2835.48 | 07-JUL-18:15 | 1819.27 | 1252.29 | 1299.04 | 0.00 | 0.00 | 0.00 | 0.00 | 106.32 | 0.00 |
August | 3092.82 | 19-AUG-13:40 | 389.84 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 106.27 | 0.00 |
September | 3066.19 | 24-SEP-12:40 | 259.90 | 156.54 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 52.55 | 0.00 |
October | 3230.34 | 10-OCT-13:30 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 54.06 | 0.00 |
November | 2504.25 | 08-NOV-13:40 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.78 |
December | 2285.73 | 10-DEC-13:00 | 389.84 | 234.80 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2182.80 | 259.90 | 156.54 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3230.34 | 6497.40 | 3756.88 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 106.32 | 175.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1988.95 | 16-JAN-21:46 | 12038.40 | 5438.10 | 5850.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.79 |
February | 1981.96 | 24-FEB-23:22 | 13543.20 | 2719.05 | 3342.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.84 |
March | 2116.50 | 15-MAR-03:28 | 13543.20 | 906.35 | 1671.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.66 |
April | 2149.96 | 25-APR-23:59 | 9480.24 | 1268.89 | 1755.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.74 |
May | 2114.75 | 11-MAY-06:09 | 6019.20 | 4531.75 | 5014.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.59 |
June | 2168.46 | 27-JUN-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 13.85 | 0.00 |
July | 2345.71 | 07-JUL-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 28.21 | 0.00 |
August | 2375.39 | 18-AUG-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 30.30 | 0.00 |
September | 2214.07 | 07-SEP-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.94 | 0.00 |
October | 2238.14 | 13-OCT-07:03 | 1805.76 | 1087.62 | 1253.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.16 |
November | 2077.91 | 11-NOV-08:63 | 2257.20 | 1087.62 | 1253.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.54 |
December | 2280.84 | 14-DEC-08:48 | 6019.20 | 3625.40 | 4178.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1981.96 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2375.39 | 13543.20 | 5438.10 | 5850.02 | 0.00 | 0.00 | 0.00 | 0.00 | 30.30 | 78.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1777.59 | 16-JAN-21:46 | 2545.92 | 9069.31 | 6185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.23 |
February | 1761.16 | 24-FEB-23:22 | 2864.16 | 4534.65 | 3534.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.65 |
March | 1963.87 | 15-MAR-03:28 | 2864.16 | 1511.55 | 1767.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.08 |
April | 2021.57 | 25-APR-23:59 | 2004.91 | 2116.17 | 1855.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.21 |
May | 2026.64 | 11-MAY-06:09 | 1272.96 | 7557.76 | 5301.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.84 |
June | 2119.66 | 28-JUN-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 38.82 | 0.00 |
July | 2411.94 | 07-JUL-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 71.61 | 0.00 |
August | 2353.95 | 18-AUG-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 77.48 | 0.00 |
September | 1999.47 | 07-SEP-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 32.65 | 0.00 |
October | 2143.11 | 13-OCT-07:03 | 381.89 | 1813.86 | 1325.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.78 |
November | 1990.49 | 11-NOV-08:63 | 477.36 | 1813.86 | 1325.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.50 |
December | 2217.62 | 14-DEC-08:48 | 1272.96 | 6046.21 | 4418.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1761.16 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2411.94 | 2864.16 | 9069.31 | 6185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 77.48 | 177.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 715.62 | 25-JAN-18:41 | 856.80 | 1062.68 | 1249.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.60 |
February | 828.62 | 24-FEB-23:22 | 2203.20 | 759.06 | 1019.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.27 |
March | 948.36 | 15-MAR-03:28 | 2203.20 | 253.02 | 509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.65 |
April | 963.69 | 25-APR-23:59 | 1542.24 | 354.23 | 535.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.88 |
May | 962.27 | 11-MAY-06:09 | 979.20 | 1265.09 | 1529.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.18 |
June | 821.72 | 25-JUN-10:33 | 220.32 | 227.72 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 36.53 | 0.00 |
July | 946.17 | 07-JUL-21:00 | 195.84 | 202.41 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 38.46 | 0.00 |
August | 920.66 | 18-AUG-21:00 | 195.84 | 202.41 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 41.31 | 0.00 |
September | 802.65 | 09-SEP-10:33 | 220.32 | 189.77 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 38.88 | 0.00 |
October | 1012.62 | 13-OCT-07:03 | 293.76 | 303.62 | 382.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.31 |
November | 945.19 | 11-NOV-08:63 | 367.20 | 303.62 | 382.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.94 |
December | 1054.04 | 14-DEC-08:48 | 979.20 | 1012.07 | 1274.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 715.62 | 195.84 | 189.77 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1054.04 | 2203.20 | 1265.09 | 1529.41 | 0.00 | 0.00 | 0.00 | 0.00 | 41.31 | 100.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 50479.97 | 12-JAN-21:43 | 8064.00 | 3175.23 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 291.22 |
February | 50606.29 | 06-FEB-20:43 | 7056.00 | 3572.14 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 309.78 |
March | 50916.26 | 22-MAR-20:44 | 8064.00 | 3175.23 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 294.81 |
April | 52273.85 | 05-APR-20:47 | 4838.40 | 1905.14 | 25992.76 | 225814.22 | 0.00 | 0.00 | 0.00 | 0.00 | 327.78 |
May | 40413.11 | 11-MAY-06:07 | 4032.00 | 1984.52 | 28880.85 | 250904.69 | 0.00 | 0.00 | 0.00 | 0.00 | 240.71 |
June | 39076.54 | 13-JUN-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 74.92 | 0.00 |
July | 39296.52 | 07-JUL-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 97.78 | 0.00 |
August | 39166.17 | 18-AUG-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 105.81 | 0.00 |
September | 38895.86 | 07-SEP-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 44.59 | 0.00 |
October | 47434.33 | 25-OCT-19:23 | 2116.80 | 1071.64 | 13718.40 | 119179.73 | 0.00 | 0.00 | 0.00 | 0.00 | 259.67 |
November | 49803.30 | 22-NOV-20:58 | 6350.40 | 3214.92 | 41155.21 | 357539.19 | 0.00 | 0.00 | 0.00 | 0.00 | 294.26 |
December | 51566.55 | 04-DEC-21:57 | 8064.00 | 3175.23 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 316.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 38895.86 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52273.85 | 8064.00 | 3572.14 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 105.81 | 327.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12932.67 | 25-JAN-00:30 | 46105.20 | 1174.60 | 914.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.60 |
February | 13358.07 | 24-FEB-22:36 | 153684.00 | 11746.04 | 7112.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.86 |
March | 13960.41 | 01-MAR-04:10 | 153684.00 | 1957.67 | 2032.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.45 |
April | 12823.50 | 15-APR-13:30 | 15368.40 | 895.64 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 78.92 | 0.00 |
May | 11969.77 | 11-MAY-04:55 | 153684.00 | 3915.35 | 3048.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.34 |
June | 11562.97 | 13-JUN-21:10 | 15368.40 | 1174.60 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 101.87 | 0.00 |
July | 12176.08 | 07-JUL-21:10 | 15368.40 | 1174.60 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 156.88 | 0.00 |
August | 12477.98 | 18-AUG-21:10 | 15368.40 | 1174.60 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 166.86 | 0.00 |
September | 12198.41 | 25-SEP-15:03 | 51228.00 | 1791.27 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 132.84 | 0.00 |
October | 13068.73 | 06-OCT-05:01 | 95625.60 | 6264.55 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.72 |
November | 19363.52 | 24-NOV-00:53 | 46105.20 | 1174.60 | 914.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.05 |
December | 13174.17 | 07-DEC-22:57 | 153684.00 | 11746.04 | 7112.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11562.97 | 15368.40 | 895.64 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19363.52 | 153684.00 | 11746.04 | 7112.54 | 0.00 | 0.00 | 0.00 | 0.00 | 166.86 | 455.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 43180.22 | 12-JAN-22:35 | 91245.96 | 13686.91 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1313.95 |
February | 54843.33 | 24-FEB-22:33 | 456229.80 | 68434.56 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1302.40 |
March | 54811.69 | 01-MAR-04:10 | 456229.80 | 11405.76 | 21114.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1141.09 |
April | 53591.51 | 05-APR-20:47 | 243322.56 | 54747.65 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1520.94 |
May | 42162.62 | 10-MAY-03:40 | 91245.96 | 2281.15 | 4222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1107.00 |
June | 41225.23 | 13-JUN-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 290.90 | 0.00 |
July | 43294.64 | 07-JUL-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 448.08 | 0.00 |
August | 43944.65 | 18-AUG-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 476.59 | 0.00 |
September | 41797.96 | 07-SEP-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 99.47 | 0.00 |
October | 60509.11 | 25-OCT-22:15 | 182491.92 | 13686.91 | 16891.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1424.96 |
November | 69005.85 | 24-NOV-00:53 | 136868.94 | 6843.46 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1101.07 |
December | 49511.78 | 08-DEC-21:17 | 405537.60 | 91246.08 | 95013.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 41225.23 | 45622.98 | 2281.15 | 4222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 69005.85 | 456229.80 | 91246.08 | 95013.56 | 0.00 | 0.00 | 0.00 | 0.00 | 476.59 | 1520.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2680.75 | 29-JAN-16:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.20 |
February | 2966.02 | 26-FEB-16:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 11.18 | 0.00 |
March | 2942.04 | 13-MAR-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 9.21 | 0.00 |
April | 3034.15 | 10-APR-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 0.00 |
May | 2928.54 | 09-MAY-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 | 0.00 |
June | 2966.19 | 26-JUN-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 51.32 | 0.00 |
July | 2965.64 | 05-JUL-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 56.47 | 0.00 |
August | 2963.94 | 22-AUG-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 46.91 | 0.00 |
September | 2930.58 | 22-SEP-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 26.31 | 0.00 |
October | 2900.36 | 08-OCT-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 29.10 | 0.00 |
November | 2911.46 | 11-NOV-16:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 |
December | 2750.62 | 10-DEC-16:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2680.75 | 324.00 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3034.15 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 56.47 | 41.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1083.39 | 29-JAN-16:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.84 |
February | 2884.91 | 26-FEB-16:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 | 0.00 |
March | 2871.32 | 30-MAR-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 22.26 | 0.00 |
April | 2975.55 | 10-APR-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 19.58 | 0.00 |
May | 2894.54 | 30-MAY-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 47.78 | 0.00 |
June | 2922.92 | 12-JUN-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 56.25 | 0.00 |
July | 2931.51 | 05-JUL-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 56.35 | 0.00 |
August | 2934.67 | 16-AUG-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 64.34 | 0.00 |
September | 2932.98 | 07-SEP-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 57.19 | 0.00 |
October | 2808.51 | 13-OCT-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.38 |
November | 2836.62 | 11-NOV-16:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 |
December | 2450.87 | 10-DEC-16:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1083.39 | 324.00 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2975.55 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 64.34 | 31.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 252.97 | 29-JAN-15:30 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 |
February | 442.52 | 26-FEB-14:50 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 2.79 | 0.00 |
March | 419.12 | 11-MAR-15:00 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 4.95 | 0.00 |
April | 425.98 | 15-APR-14:00 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 8.02 | 0.00 |
May | 353.83 | 20-MAY-13:30 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 11.94 | 0.00 |
June | 398.31 | 24-JUN-17:15 | 0.00 | 261.77 | 526.30 | 0.00 | 0.00 | 0.00 | 0.00 | 16.48 | 0.00 |
July | 443.15 | 08-JUL-17:12 | 0.00 | 261.77 | 526.30 | 0.00 | 0.00 | 0.00 | 0.00 | 19.53 | 0.00 |
August | 506.53 | 19-AUG-14:00 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 18.65 | 0.00 |
September | 551.03 | 24-SEP-12:50 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 | 0.00 |
October | 592.52 | 10-OCT-13:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 9.88 | 0.00 |
November | 486.18 | 08-NOV-14:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.14 |
December | 455.73 | 10-DEC-14:30 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 252.97 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 592.52 | 0.00 | 261.77 | 526.30 | 0.00 | 0.00 | 0.00 | 0.00 | 19.53 | 13.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 675.67 | 01-JAN-09:02 | 270.00 | 215.63 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.16 |
February | 930.33 | 28-FEB-19:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
March | 991.46 | 30-MAR-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 6.66 | 0.00 |
April | 967.27 | 18-APR-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 6.26 | 0.00 |
May | 1012.66 | 18-MAY-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 10.66 | 0.00 |
June | 1059.04 | 10-JUN-18:02 | 702.00 | 462.06 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 10.58 | 0.00 |
July | 1015.89 | 16-JUL-18:02 | 702.00 | 462.06 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 17.18 | 0.00 |
August | 1012.71 | 25-AUG-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 12.45 | 0.00 |
September | 996.15 | 07-SEP-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 12.28 | 0.00 |
October | 948.03 | 10-OCT-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 6.36 | 0.00 |
November | 863.14 | 05-NOV-15:02 | 324.00 | 152.48 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 0.00 |
December | 691.85 | 24-DEC-09:02 | 216.00 | 172.50 | 639.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 675.67 | 216.00 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1059.04 | 831.60 | 462.06 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 17.18 | 18.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2275.67 | 29-JAN-16:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.49 |
February | 2666.80 | 26-FEB-16:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 11.61 | 0.00 |
March | 2662.00 | 13-MAR-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 9.24 | 0.00 |
April | 2738.49 | 10-APR-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 19.22 | 0.00 |
May | 2648.69 | 30-MAY-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 47.53 | 0.00 |
June | 2687.13 | 21-JUN-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 60.17 | 0.00 |
July | 2682.58 | 15-JUL-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 64.89 | 0.00 |
August | 2683.55 | 15-AUG-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 60.39 | 0.00 |
September | 2690.31 | 11-SEP-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 43.43 | 0.00 |
October | 2672.51 | 10-OCT-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 41.11 | 0.00 |
November | 2615.30 | 11-NOV-16:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 |
December | 2388.89 | 10-DEC-16:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2275.67 | 324.00 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2738.49 | 680.40 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 64.89 | 35.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 882.90 | 24-JAN-16:04 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.04 |
February | 2527.26 | 28-FEB-16:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 8.77 | 0.00 |
March | 2548.01 | 30-MAR-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 22.63 | 0.00 |
April | 2695.60 | 10-APR-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 | 0.00 |
May | 2651.14 | 30-MAY-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 47.63 | 0.00 |
June | 2658.71 | 12-JUN-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 67.08 | 0.00 |
July | 2666.16 | 20-JUL-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 64.35 | 0.00 |
August | 2666.49 | 17-AUG-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 67.32 | 0.00 |
September | 2617.73 | 07-SEP-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 57.17 | 0.00 |
October | 2493.07 | 10-OCT-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 20.10 | 0.00 |
November | 2315.67 | 06-NOV-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.47 |
December | 1202.07 | 11-DEC-09:03 | 360.00 | 538.96 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 882.90 | 360.00 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2695.60 | 831.60 | 654.11 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 67.32 | 89.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2560.80 | 16-JAN-21:46 | 20118.72 | 14938.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.50 |
February | 2536.69 | 24-FEB-23:22 | 22633.56 | 7469.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.82 |
March | 2909.61 | 15-MAR-03:28 | 22633.56 | 2489.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.64 |
April | 2960.99 | 25-APR-23:59 | 15843.49 | 3485.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.51 |
May | 2926.20 | 11-MAY-06:09 | 10059.36 | 12448.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.13 |
June | 2594.32 | 29-JUN-20:10 | 2011.87 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.34 | 0.00 |
July | 3039.69 | 07-JUL-19:20 | 1760.39 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.82 | 0.00 |
August | 3119.52 | 18-AUG-19:10 | 1760.39 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.19 | 0.00 |
September | 2417.46 | 08-SEP-20:10 | 2011.87 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.60 | 0.00 |
October | 3075.56 | 13-OCT-07:03 | 3017.81 | 2987.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.38 |
November | 2829.83 | 11-NOV-08:63 | 3772.26 | 2987.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.46 |
December | 3074.29 | 14-DEC-08:48 | 10059.36 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2417.46 | 1760.39 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3119.52 | 22633.56 | 14938.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.19 | 137.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2778.51 | 29-JAN-16:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.77 |
February | 3100.93 | 26-FEB-16:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 10.92 | 0.00 |
March | 3075.02 | 13-MAR-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 8.96 | 0.00 |
April | 3182.77 | 10-APR-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 | 0.00 |
May | 3062.78 | 09-MAY-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 0.00 |
June | 3073.41 | 21-JUN-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 49.76 | 0.00 |
July | 3088.62 | 19-JUL-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 51.55 | 0.00 |
August | 3099.94 | 04-AUG-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 38.94 | 0.00 |
September | 3086.46 | 07-SEP-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 44.73 | 0.00 |
October | 3024.51 | 02-OCT-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 25.87 | 0.00 |
November | 3041.20 | 11-NOV-16:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.35 |
December | 2868.97 | 10-DEC-16:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2778.51 | 324.00 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3182.77 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 51.55 | 40.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1435.67 | 25-JAN-16:03 | 972.00 | 342.97 | 684.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.95 |
February | 3002.55 | 26-FEB-16:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.16 | 0.00 |
March | 2995.34 | 29-MAR-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 18.43 | 0.00 |
April | 3114.79 | 10-APR-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 19.15 | 0.00 |
May | 3028.90 | 05-MAY-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 32.80 | 0.00 |
June | 3039.20 | 23-JUN-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 50.62 | 0.00 |
July | 3049.05 | 21-JUL-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 64.55 | 0.00 |
August | 3065.00 | 14-AUG-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 45.90 | 0.00 |
September | 3032.49 | 08-SEP-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 38.64 | 0.00 |
October | 2926.97 | 10-OCT-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 41.12 | 0.00 |
November | 2950.65 | 11-NOV-16:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.24 |
December | 2057.27 | 11-DEC-16:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1435.67 | 324.00 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3114.79 | 972.00 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 64.55 | 90.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1474.81 | 29-JAN-16:01 | 378.00 | 177.90 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.20 |
February | 1624.36 | 26-FEB-16:02 | 324.00 | 152.48 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 4.82 | 0.00 |
March | 1619.39 | 13-MAR-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 3.65 | 0.00 |
April | 1571.06 | 09-APR-15:02 | 324.00 | 152.48 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 |
May | 1588.72 | 05-MAY-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 16.52 | 0.00 |
June | 1599.29 | 25-JUN-15:02 | 324.00 | 152.48 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 28.27 | 0.00 |
July | 1596.94 | 04-JUL-15:02 | 324.00 | 152.48 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 27.85 | 0.00 |
August | 1604.36 | 10-AUG-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 27.43 | 0.00 |
September | 1579.66 | 24-SEP-15:02 | 324.00 | 152.48 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 19.62 | 0.00 |
October | 1603.70 | 10-OCT-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 19.95 | 0.00 |
November | 1594.21 | 08-NOV-16:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.61 |
December | 1524.28 | 10-DEC-16:02 | 324.00 | 152.48 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1474.81 | 324.00 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1624.36 | 680.40 | 177.90 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 28.27 | 22.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 32108.85 | 24-JAN-23:54 | 269887.68 | 10313.52 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.45 |
February | 31250.28 | 23-FEB-23:37 | 80966.30 | 3094.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.62 |
March | 30808.02 | 15-MAR-05:44 | 104956.32 | 6875.68 | 28116.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.69 |
April | 32060.20 | 25-APR-23:59 | 188921.38 | 4812.98 | 15745.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.74 |
May | 30801.95 | 10-MAY-03:23 | 161932.61 | 2062.70 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.84 |
June | 23473.17 | 13-JUN-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 60.80 | 0.00 |
July | 23978.93 | 07-JUL-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 95.90 | 0.00 |
August | 23732.92 | 18-AUG-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 101.02 | 0.00 |
September | 22676.16 | 07-SEP-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 20.74 | 0.00 |
October | 31799.28 | 04-OCT-04:40 | 269887.68 | 6875.68 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.12 |
November | 31591.46 | 14-NOV-23:40 | 188921.38 | 7219.46 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.93 |
December | 33171.68 | 07-DEC-23:41 | 188921.38 | 7219.46 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22676.16 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33171.68 | 269887.68 | 10313.52 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 101.02 | 308.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33791.60 | 24-JAN-23:54 | 269887.68 | 10313.52 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.38 |
February | 33609.06 | 24-FEB-23:26 | 269887.68 | 10313.52 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.94 |
March | 32674.40 | 15-MAR-05:44 | 104956.32 | 6875.68 | 28116.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.37 |
April | 37267.09 | 25-APR-23:59 | 188921.38 | 4812.98 | 15745.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.32 |
May | 32308.60 | 10-MAY-03:23 | 161932.61 | 2062.70 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.04 |
June | 24692.13 | 13-JUN-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 60.76 | 0.00 |
July | 25154.35 | 07-JUL-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 95.89 | 0.00 |
August | 24905.86 | 18-AUG-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 101.00 | 0.00 |
September | 23872.89 | 05-SEP-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 38.02 | 0.00 |
October | 33540.27 | 25-OCT-22:15 | 107955.07 | 4125.41 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.24 |
November | 33370.56 | 17-NOV-24:00 | 53977.54 | 2062.70 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.24 |
December | 34922.79 | 07-DEC-23:41 | 188921.38 | 7219.46 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 23872.89 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37267.09 | 269887.68 | 10313.52 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 101.00 | 330.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36321.40 | 25-JAN-18:41 | 9339.96 | 5085.88 | 104389.99 | 157449.82 | 0.00 | 0.00 | 0.00 | 0.00 | 302.51 |
February | 35525.11 | 08-FEB-18:31 | 9339.96 | 5085.88 | 104389.99 | 157449.82 | 0.00 | 0.00 | 0.00 | 0.00 | 282.35 |
March | 34747.48 | 22-MAR-17:44 | 13342.80 | 7265.54 | 149128.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 286.71 |
April | 34233.60 | 06-APR-22:38 | 24017.04 | 3632.77 | 149128.56 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 285.17 |
May | 31790.80 | 15-MAY-17:01 | 9339.96 | 5085.88 | 104389.99 | 157449.82 | 0.00 | 0.00 | 0.00 | 60.97 | 0.00 |
June | 30725.59 | 25-JUN-10:33 | 2401.70 | 1089.83 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 80.75 | 0.00 |
July | 31151.59 | 08-JUL-10:50 | 800.57 | 302.73 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 130.02 | 0.00 |
August | 30991.36 | 27-AUG-10:50 | 800.57 | 363.28 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 82.74 | 0.00 |
September | 30596.77 | 09-SEP-10:45 | 1601.14 | 605.46 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 87.72 | 0.00 |
October | 36018.61 | 13-OCT-07:03 | 3202.27 | 1453.11 | 44738.57 | 44985.66 | 0.00 | 0.00 | 0.00 | 0.00 | 276.98 |
November | 35180.45 | 30-NOV-18:19 | 10674.24 | 5812.43 | 119302.85 | 179942.65 | 0.00 | 0.00 | 0.00 | 0.00 | 288.18 |
December | 38455.57 | 01-DEC-18:47 | 13342.80 | 7265.54 | 149128.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 286.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 30596.77 | 800.57 | 302.73 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38455.57 | 24017.04 | 7265.54 | 149128.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 130.02 | 302.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4430.06 | 25-JAN-18:41 | 9315.60 | 11067.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.43 |
February | 5078.30 | 24-FEB-23:22 | 23954.40 | 7905.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.09 |
March | 5806.26 | 15-MAR-03:28 | 23954.40 | 2635.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.23 |
April | 5884.28 | 25-APR-23:59 | 16768.08 | 3689.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.56 |
May | 5781.20 | 11-MAY-06:09 | 10646.40 | 13175.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.59 |
June | 6075.07 | 13-JUN-18:03 | 11178.72 | 12648.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.21 | 0.00 |
July | 7091.79 | 07-JUL-18:03 | 11178.72 | 12648.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.98 | 0.00 |
August | 6970.95 | 18-AUG-15:03 | 7984.80 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.29 | 0.00 |
September | 5921.94 | 07-SEP-15:25 | 2661.60 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.92 | 0.00 |
October | 6011.55 | 13-OCT-07:03 | 3193.92 | 3162.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.67 |
November | 5436.98 | 11-NOV-08:63 | 3992.40 | 3162.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.07 |
December | 6249.18 | 14-DEC-08:48 | 10646.40 | 10540.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4430.06 | 2661.60 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7091.79 | 23954.40 | 13175.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.29 | 239.43 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.384185E+12 | 284032.75 | 19-JAN-20:00 | 0.568443E+12 | 522364.03 | 07-JAN-17:10 |
February | 0.356192E+12 | 300986.43 | 28-FEB-20:19 | 0.474923E+12 | 494673.10 | 11-FEB-19:10 |
March | 0.420738E+12 | 342079.37 | 30-MAR-19:10 | 0.449709E+12 | 406321.74 | 22-MAR-18:10 |
April | 0.456131E+12 | 347215.92 | 04-APR-19:00 | 0.406012E+12 | 422369.39 | 05-APR-20:00 |
May | 0.550080E+12 | 382514.40 | 30-MAY-19:40 | 0.395882E+12 | 348291.66 | 01-MAY-17:10 |
June | 0.640018E+12 | 408942.80 | 13-JUN-19:49 | 0.370174E+12 | 339130.35 | 02-JUN-17:10 |
July | 0.722509E+12 | 437368.82 | 07-JUL-19:49 | 0.374571E+12 | 318169.82 | 05-JUL-17:19 |
August | 0.745339E+12 | 442211.49 | 18-AUG-19:19 | 0.374278E+12 | 318129.46 | 31-AUG-17:19 |
September | 0.596436E+12 | 412205.42 | 07-SEP-19:10 | 0.368582E+12 | 334305.65 | 29-SEP-17:19 |
October | 0.472880E+12 | 410832.55 | 18-OCT-19:49 | 0.417430E+12 | 412263.18 | 25-OCT-20:19 |
November | 0.401209E+12 | 329995.73 | 27-NOV-20:10 | 0.435794E+12 | 450421.30 | 30-NOV-19:10 |
December | 0.389266E+12 | 283552.82 | 12-DEC-20:10 | 0.506690E+12 | 452341.91 | 18-DEC-18:49 |
Annual Sum or Average | 0.613498E+13 | 0.514249E+13 | ||||
Minimum of Months | 0.356192E+12 | 283552.82 | 0.368582E+12 | 318129.46 | ||
Maximum of Months | 0.745339E+12 | 442211.49 | 0.568443E+12 | 522364.03 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.654818E+11 | 0.240439E+11 | 0.148212E+12 | 0.553310E+11 | 0.433653E+11 | 0.576737E+10 | 0.00 | 0.546492E+10 | 0.00 | 0.00 | 0.236229E+11 | 0.770509E+10 | 0.00 |
February | 0.591094E+11 | 0.205217E+11 | 0.133859E+12 | 0.499765E+11 | 0.396436E+11 | 0.713521E+10 | 0.00 | 0.172414E+11 | 0.00 | 0.00 | 0.170428E+11 | 0.696251E+10 | 0.00 |
March | 0.652314E+11 | 0.209851E+11 | 0.148223E+12 | 0.553338E+11 | 0.453966E+11 | 0.112624E+11 | 0.00 | 0.490703E+11 | 0.00 | 0.00 | 0.122852E+11 | 0.770327E+10 | 0.00 |
April | 0.628483E+11 | 0.185752E+11 | 0.143397E+12 | 0.535455E+11 | 0.458753E+11 | 0.130041E+11 | 0.00 | 0.969259E+11 | 0.00 | 0.00 | 0.937981E+10 | 0.746514E+10 | 0.00 |
May | 0.648475E+11 | 0.176853E+11 | 0.148223E+12 | 0.553319E+11 | 0.504844E+11 | 0.144940E+11 | 0.00 | 0.174903E+12 | 0.00 | 0.00 | 0.110635E+11 | 0.770458E+10 | 0.00 |
June | 0.626904E+11 | 0.164525E+11 | 0.143446E+12 | 0.535481E+11 | 0.536881E+11 | 0.147606E+11 | 0.00 | 0.263352E+12 | 0.00 | 0.00 | 0.194404E+11 | 0.745677E+10 | 0.00 |
July | 0.647260E+11 | 0.172497E+11 | 0.148174E+12 | 0.553290E+11 | 0.571679E+11 | 0.157504E+11 | 0.00 | 0.326602E+12 | 0.00 | 0.00 | 0.244549E+11 | 0.771254E+10 | 0.00 |
August | 0.649521E+11 | 0.185103E+11 | 0.148234E+12 | 0.553336E+11 | 0.589513E+11 | 0.159870E+11 | 0.00 | 0.344554E+12 | 0.00 | 0.00 | 0.257438E+11 | 0.770430E+10 | 0.00 |
September | 0.630243E+11 | 0.195577E+11 | 0.143408E+12 | 0.535457E+11 | 0.519282E+11 | 0.145016E+11 | 0.00 | 0.222424E+12 | 0.00 | 0.00 | 0.153905E+11 | 0.746640E+10 | 0.00 |
October | 0.653718E+11 | 0.220047E+11 | 0.148201E+12 | 0.553308E+11 | 0.489337E+11 | 0.126406E+11 | 0.00 | 0.943958E+11 | 0.00 | 0.00 | 0.129908E+11 | 0.770314E+10 | 0.00 |
November | 0.633707E+11 | 0.228667E+11 | 0.143462E+12 | 0.535469E+11 | 0.448132E+11 | 0.101292E+11 | 0.00 | 0.370684E+11 | 0.00 | 0.00 | 0.134354E+11 | 0.744931E+10 | 0.00 |
December | 0.654113E+11 | 0.244703E+11 | 0.148174E+12 | 0.553297E+11 | 0.442680E+11 | 0.729593E+10 | 0.00 | 0.102029E+11 | 0.00 | 0.00 | 0.211807E+11 | 0.771297E+10 | 0.00 |
Annual Sum or Average | 0.767065E+12 | 0.242923E+12 | 0.174501E+13 | 0.651482E+12 | 0.584516E+12 | 0.142729E+12 | 0.00 | 0.164220E+13 | 0.00 | 0.00 | 0.206031E+12 | 0.907460E+11 | 0.00 |
Minimum of Months | 0.591094E+11 | 0.164525E+11 | 0.133859E+12 | 0.499765E+11 | 0.396436E+11 | 0.576737E+10 | 0.00 | 0.546492E+10 | 0.00 | 0.00 | 0.937981E+10 | 0.696251E+10 | 0.00 |
Maximum of Months | 0.654818E+11 | 0.244703E+11 | 0.148234E+12 | 0.553338E+11 | 0.589513E+11 | 0.159870E+11 | 0.00 | 0.344554E+12 | 0.00 | 0.00 | 0.257438E+11 | 0.771297E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.145368E+12 | 0.00 | 0.271156E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.924062E+11 | 0.00 | 0.245313E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.319460E+11 | 0.00 | 0.265739E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.125867E+11 | 0.00 | 0.246470E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.236516E+10 | 0.00 | 0.241538E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.630111E+09 | 0.00 | 0.222430E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 56359064.25 | 0.00 | 0.222694E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 41805850.38 | 0.00 | 0.222198E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.632939E+09 | 0.00 | 0.220978E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.260568E+11 | 0.00 | 0.239470E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.442387E+11 | 0.00 | 0.244464E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.907056E+11 | 0.00 | 0.264164E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.447034E+12 | 0.00 | 0.290661E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 41805850.38 | 0.00 | 0.220978E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.145368E+12 | 0.00 | 0.271156E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 62892.57 | 02-JAN-20:10 | 15448.40 | 01-JAN-00:10 | 89475.41 | 02-JAN-07:10 | 39726.11 | 02-JAN-07:19 | 36172.77 | 23-JAN-21:19 | 5819.62 | 28-JAN-22:00 | 0.00 | 01-JAN-00:10 |
February | 62892.57 | 01-FEB-20:10 | 15448.40 | 01-FEB-00:10 | 89475.41 | 01-FEB-07:10 | 39726.11 | 01-FEB-07:19 | 31327.45 | 23-FEB-22:49 | 5736.45 | 24-FEB-23:10 | 0.00 | 01-FEB-00:10 |
March | 62892.57 | 01-MAR-20:10 | 15448.40 | 01-MAR-00:10 | 89475.41 | 01-MAR-07:10 | 39726.11 | 01-MAR-07:19 | 33808.55 | 30-MAR-21:10 | 5937.70 | 13-MAR-18:10 | 0.00 | 01-MAR-00:10 |
April | 62892.57 | 03-APR-19:10 | 15448.40 | 01-APR-00:10 | 89475.41 | 03-APR-06:10 | 39726.11 | 03-APR-06:19 | 33282.74 | 17-APR-21:10 | 6123.62 | 15-APR-16:49 | 0.00 | 01-APR-00:10 |
May | 62892.57 | 01-MAY-19:19 | 15448.40 | 01-MAY-00:10 | 89475.41 | 01-MAY-06:10 | 39726.11 | 08-MAY-06:19 | 35121.95 | 19-MAY-21:10 | 6307.40 | 30-MAY-21:40 | 0.00 | 01-MAY-00:10 |
June | 62892.57 | 01-JUN-19:30 | 15448.40 | 01-JUN-00:10 | 89475.41 | 01-JUN-06:10 | 39725.67 | 23-JUN-06:19 | 38283.85 | 29-JUN-21:10 | 7225.61 | 26-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 62892.57 | 03-JUL-19:30 | 15448.40 | 01-JUL-00:10 | 89475.41 | 03-JUL-06:10 | 39726.11 | 28-JUL-06:19 | 40553.21 | 07-JUL-21:10 | 7315.03 | 01-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 62892.57 | 01-AUG-19:10 | 15448.40 | 01-AUG-00:10 | 89475.41 | 01-AUG-06:10 | 39726.11 | 14-AUG-06:19 | 43378.57 | 18-AUG-21:10 | 7723.29 | 23-AUG-20:00 | 0.00 | 01-AUG-00:10 |
September | 62892.57 | 01-SEP-19:10 | 15448.40 | 01-SEP-00:10 | 89475.41 | 01-SEP-06:10 | 39726.11 | 01-SEP-06:19 | 42073.23 | 07-SEP-21:10 | 6833.72 | 27-SEP-18:10 | 0.00 | 01-SEP-00:10 |
October | 62892.57 | 02-OCT-19:10 | 15448.40 | 01-OCT-00:10 | 89475.41 | 02-OCT-06:10 | 39726.11 | 02-OCT-06:19 | 38408.60 | 10-OCT-21:10 | 7108.73 | 18-OCT-19:00 | 0.00 | 01-OCT-00:10 |
November | 62892.57 | 01-NOV-19:10 | 15448.40 | 01-NOV-00:10 | 89475.41 | 01-NOV-06:10 | 39726.11 | 01-NOV-06:19 | 42720.29 | 14-NOV-22:30 | 5746.92 | 23-NOV-09:20 | 0.00 | 01-NOV-00:10 |
December | 62892.57 | 01-DEC-20:10 | 15448.40 | 01-DEC-00:10 | 89475.41 | 01-DEC-07:10 | 39726.11 | 01-DEC-07:19 | 32983.25 | 09-DEC-21:49 | 5759.27 | 09-DEC-10:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 62892.57 | 15448.40 | 89475.41 | 39725.67 | 31327.45 | 5736.45 | 0.00 | |||||||
Maximum of Months | 62892.57 | 15448.40 | 89475.41 | 39726.11 | 43378.57 | 7723.29 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 53550.55 | 19-JAN-21:00 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4738.25 | 25-JAN-07:10 | 0.00 |
February | 83690.99 | 26-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 4738.28 | 13-FEB-19:10 | 0.00 |
March | 110814.73 | 30-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-01:10 | 4738.56 | 03-MAR-07:00 | 0.00 |
April | 114092.55 | 17-APR-15:20 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4738.53 | 24-APR-06:10 | 0.00 |
May | 146934.13 | 30-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-16:30 | 4738.27 | 08-MAY-06:10 | 0.00 |
June | 178040.20 | 28-JUN-18:19 | 0.00 | 0.00 | 9938.94 | 01-JUN-08:20 | 4738.15 | 05-JUN-06:10 | 0.00 |
July | 199939.90 | 08-JUL-15:20 | 0.00 | 0.00 | 9938.94 | 01-JUL-00:10 | 4738.02 | 10-JUL-06:10 | 0.00 |
August | 197939.87 | 18-AUG-18:19 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 4738.76 | 10-AUG-18:10 | 0.00 |
September | 172852.28 | 07-SEP-18:10 | 0.00 | 0.00 | 9938.94 | 01-SEP-10:50 | 4738.22 | 18-SEP-06:10 | 0.00 |
October | 161459.40 | 18-OCT-20:40 | 0.00 | 0.00 | 9938.94 | 01-OCT-12:00 | 4738.49 | 16-OCT-18:10 | 0.00 |
November | 92990.06 | 27-NOV-19:10 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:49 | 4738.41 | 29-NOV-07:00 | 0.00 |
December | 71179.92 | 13-DEC-11:39 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 4738.56 | 20-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 53550.55 | 0.00 | 0.00 | 9938.94 | 4738.02 | 0.00 | |||
Maximum of Months | 199939.90 | 0.00 | 0.00 | 9938.94 | 4738.76 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 284032.75 | 19-JAN-20:00 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 21309.08 | 5362.37 | 0.00 | 51676.95 | 0.00 |
February | 300986.43 | 28-FEB-20:19 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 24157.82 | 5358.79 | 0.00 | 66289.89 | 0.00 |
March | 342079.37 | 30-MAR-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 26260.69 | 5808.19 | 0.00 | 103219.30 | 0.00 |
April | 347215.92 | 04-APR-19:00 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 25890.46 | 5731.36 | 0.00 | 100778.44 | 0.00 |
May | 382514.40 | 30-MAY-19:40 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 29543.67 | 6217.16 | 0.00 | 131799.91 | 0.00 |
June | 408942.80 | 13-JUN-19:49 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 32805.05 | 6305.38 | 0.00 | 154878.43 | 0.00 |
July | 437368.82 | 07-JUL-19:49 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 36087.11 | 6681.33 | 0.00 | 179907.64 | 0.00 |
August | 442211.49 | 18-AUG-19:19 | 62892.57 | 88772.42 | 15448.40 | 32158.99 | 37611.66 | 6653.24 | 0.00 | 182872.92 | 0.00 |
September | 412205.42 | 07-SEP-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 31743.56 | 6614.56 | 0.00 | 158564.14 | 0.00 |
October | 410832.55 | 18-OCT-19:49 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 29630.00 | 7092.63 | 0.00 | 158440.47 | 0.00 |
November | 329995.73 | 27-NOV-20:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 24031.72 | 5606.60 | 0.00 | 86462.32 | 0.00 |
December | 283552.82 | 12-DEC-20:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 24381.97 | 5310.24 | 0.00 | 49145.85 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 283552.82 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 21309.08 | 5310.24 | 0.00 | 49145.85 | 0.00 | |
Maximum of Months | 442211.49 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 37611.66 | 7092.63 | 0.00 | 182872.92 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 217257.51 | 07-JAN-16:10 | 0.00 | 268312.54 | 26-JAN-21:10 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 257145.12 | 12-FEB-07:10 | 0.00 | 268914.08 | 14-FEB-21:00 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 145105.00 | 23-MAR-07:00 | 0.00 | 250316.82 | 08-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 100625.13 | 05-APR-20:00 | 0.00 | 248148.35 | 18-APR-17:10 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 65528.34 | 11-MAY-05:19 | 0.00 | 244537.12 | 02-MAY-20:00 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 48165.39 | 08-JUN-05:00 | 0.00 | 234868.75 | 02-JUN-20:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 5339.91 | 28-JUL-08:09 | 0.00 | 214474.69 | 03-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 4299.23 | 25-AUG-08:09 | 0.00 | 214345.58 | 31-AUG-20:00 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 35522.60 | 29-SEP-03:49 | 0.00 | 230057.33 | 29-SEP-17:19 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 149516.36 | 25-OCT-22:10 | 0.00 | 245082.78 | 30-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 150498.80 | 30-NOV-16:00 | 0.00 | 246991.45 | 25-NOV-22:19 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 167999.76 | 29-DEC-00:30 | 0.00 | 259591.12 | 22-DEC-21:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 4299.23 | 0.00 | 214345.58 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 257145.12 | 0.00 | 268914.08 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 25.27 | 11.00 | 25.27 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 25.10 | 11.00 | 25.10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 25.22 | 9.00 | 25.22 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 25.21 | 2.67 | 25.21 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.73 | 0.67 | 24.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 25.21 | 10.00 | 25.21 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 25.10 | 8.00 | 25.10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 25.20 | 25.33 | 25.20 |
Annual Sum or Average | 0.00 | 0.00 | 77.67 | 25.19 | 77.67 | 25.19 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 25.27 | 25.33 | 25.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.74 | 0.33 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.69 | 0.50 | 21.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.70 | 0.83 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.67 | 21.70 | 1.67 | 21.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.74 | 0.83 | 21.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.75 | 0.50 | 21.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.83 | 21.73 | 0.83 | 21.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.75 | 0.50 | 21.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.52 | 0.83 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
February | 0.33 | 20.50 | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.69 | 1.00 | 21.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.70 | 4.00 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.70 | 1.50 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 20.51 | 1.17 | 20.51 | 6.50 | 21.39 | 6.50 | 21.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.52 | 0.83 | 20.52 | 4.00 | 21.70 | 4.00 | 21.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.79 | 0.33 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.83 | 21.72 | 0.83 | 21.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.79 | 0.33 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.85 | 0.33 | 21.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.69 | 0.67 | 21.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 21.75 | 1.00 | 21.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.85 | 0.67 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.73 | 1.67 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.75 | 1.50 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.33 | 21.73 | 4.33 | 21.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.75 | 1.67 | 21.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.73 | 0.67 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.72 | 1.83 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.70 | 1.00 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.50 | 21.72 | 3.50 | 21.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.73 | 1.83 | 21.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.69 | 0.50 | 21.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.76 | 1.50 | 21.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.70 | 0.83 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.80 | 2.50 | 21.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.83 | 2.33 | 21.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.89 | 3.33 | 21.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.17 | 21.82 | 11.17 | 21.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.89 | 3.33 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.96 | 1.17 | 24.96 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.81 | 1.00 | 24.81 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.69 | 1.83 | 24.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.60 | 0.33 | 24.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.66 | 0.17 | 24.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.76 | 1.67 | 24.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.69 | 1.33 | 24.69 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.73 | 2.17 | 24.73 |
Annual Sum or Average | 0.00 | 0.00 | 9.67 | 24.75 | 9.67 | 24.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.96 | 2.17 | 24.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.06 | 1.17 | 25.06 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.81 | 1.33 | 24.81 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.71 | 2.50 | 24.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.65 | 0.33 | 24.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.69 | 0.17 | 24.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.79 | 2.00 | 24.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.71 | 1.83 | 24.71 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.76 | 3.00 | 24.76 |
Annual Sum or Average | 0.00 | 0.00 | 12.33 | 24.78 | 12.33 | 24.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 25.06 | 3.00 | 25.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 25.13 | 15.67 | 25.13 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 24.99 | 11.67 | 24.99 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 25.00 | 21.83 | 25.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 24.95 | 17.83 | 24.95 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.72 | 4.00 | 24.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.79 | 0.67 | 24.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.69 | 0.33 | 24.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 25.13 | 20.50 | 25.13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 25.05 | 14.67 | 25.05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 25.09 | 34.67 | 25.09 |
Annual Sum or Average | 0.00 | 0.00 | 141.83 | 25.04 | 141.83 | 25.04 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 25.13 | 34.67 | 25.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 737.00 | 23.18 | 0.67 | 23.18 | 0.33 | 23.18 |
February | 671.67 | 22.65 | 0.00 | 22.65 | 0.00 | 22.65 |
March | 744.00 | 22.02 | 0.00 | 22.02 | 0.00 | 22.02 |
April | 720.00 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
May | 744.00 | 21.83 | 0.00 | 21.83 | 0.00 | 21.83 |
June | 720.00 | 22.69 | 0.00 | 22.69 | 0.00 | 22.69 |
July | 453.50 | 23.01 | 22.00 | 23.05 | 0.00 | 23.05 |
August | 122.33 | 23.28 | 429.33 | 23.75 | 9.17 | 23.75 |
September | 14.00 | 23.93 | 565.33 | 23.95 | 10.50 | 23.95 |
October | 51.17 | 23.87 | 308.33 | 23.94 | 3.17 | 23.94 |
November | 230.33 | 23.93 | 148.50 | 23.94 | 0.00 | 23.94 |
December | 480.17 | 23.84 | 52.33 | 23.85 | 0.00 | 23.85 |
Annual Sum or Average | 5688.17 | 22.59 | 1526.50 | 22.87 | 23.17 | 22.88 |
Minimum of Months | 14.00 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
Maximum of Months | 744.00 | 23.93 | 565.33 | 23.95 | 10.50 | 23.95 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 739.67 | 21.18 | 277.50 | 21.13 | 277.50 | 21.11 |
February | 641.50 | 21.29 | 172.83 | 21.24 | 171.33 | 21.20 |
March | 668.67 | 21.68 | 39.50 | 21.76 | 8.33 | 21.75 |
April | 595.83 | 21.82 | 57.67 | 21.99 | 1.33 | 21.99 |
May | 499.17 | 22.15 | 149.17 | 22.48 | 0.00 | 22.48 |
June | 201.83 | 22.51 | 408.67 | 23.30 | 0.00 | 23.30 |
July | 107.33 | 22.41 | 531.33 | 23.51 | 4.33 | 23.50 |
August | 27.17 | 22.99 | 645.50 | 23.71 | 12.83 | 23.71 |
September | 299.00 | 22.19 | 308.83 | 22.98 | 0.00 | 22.98 |
October | 554.83 | 21.79 | 133.00 | 22.18 | 2.00 | 22.18 |
November | 654.67 | 21.49 | 43.50 | 21.55 | 21.00 | 21.54 |
December | 716.50 | 21.30 | 105.83 | 21.28 | 99.17 | 21.25 |
Annual Sum or Average | 5706.17 | 21.65 | 2873.33 | 22.16 | 597.83 | 22.09 |
Minimum of Months | 27.17 | 21.18 | 39.50 | 21.13 | 0.00 | 21.11 |
Maximum of Months | 739.67 | 22.99 | 645.50 | 23.71 | 277.50 | 23.71 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.58 | 9.00 | 21.58 | 9.00 | 21.57 |
February | 664.67 | 21.93 | 16.83 | 21.90 | 16.83 | 21.88 |
March | 672.00 | 22.57 | 27.00 | 22.62 | 0.00 | 22.62 |
April | 544.67 | 22.75 | 82.33 | 22.89 | 16.33 | 22.90 |
May | 422.50 | 22.99 | 289.67 | 23.28 | 105.17 | 23.31 |
June | 230.33 | 23.51 | 436.67 | 23.74 | 122.00 | 23.76 |
July | 186.33 | 23.65 | 565.83 | 23.80 | 145.67 | 23.81 |
August | 164.83 | 23.97 | 634.50 | 23.88 | 162.67 | 23.90 |
September | 276.50 | 23.27 | 414.67 | 23.59 | 129.67 | 23.62 |
October | 571.83 | 22.77 | 102.00 | 22.91 | 41.33 | 22.95 |
November | 690.33 | 22.48 | 21.17 | 22.51 | 11.17 | 22.52 |
December | 731.50 | 21.94 | 1.83 | 21.95 | 0.00 | 21.95 |
Annual Sum or Average | 5899.50 | 22.49 | 2601.50 | 22.89 | 759.83 | 22.96 |
Minimum of Months | 164.83 | 21.58 | 1.83 | 21.58 | 0.00 | 21.57 |
Maximum of Months | 744.00 | 23.97 | 634.50 | 23.88 | 162.67 | 23.90 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.07 | 203.17 | 21.05 | 203.17 | 21.04 |
February | 672.00 | 21.30 | 141.83 | 21.25 | 141.83 | 21.21 |
March | 743.67 | 21.80 | 5.33 | 21.79 | 5.33 | 21.79 |
April | 711.33 | 22.32 | 0.00 | 22.32 | 0.00 | 22.32 |
May | 626.83 | 22.81 | 14.00 | 22.84 | 0.00 | 22.84 |
June | 168.67 | 23.17 | 287.33 | 23.60 | 0.00 | 23.60 |
July | 55.33 | 23.07 | 481.50 | 23.79 | 0.00 | 23.79 |
August | 1.83 | 23.29 | 543.50 | 23.86 | 0.00 | 23.86 |
September | 367.33 | 22.99 | 101.50 | 23.17 | 0.00 | 23.17 |
October | 727.00 | 22.31 | 0.00 | 22.31 | 0.00 | 22.31 |
November | 720.00 | 21.69 | 3.17 | 21.68 | 3.17 | 21.68 |
December | 744.00 | 21.20 | 53.17 | 21.19 | 53.17 | 21.17 |
Annual Sum or Average | 6282.00 | 21.91 | 1834.50 | 22.21 | 406.67 | 22.15 |
Minimum of Months | 1.83 | 21.07 | 0.00 | 21.05 | 0.00 | 21.04 |
Maximum of Months | 744.00 | 23.29 | 543.50 | 23.86 | 203.17 | 23.86 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.03 | 274.83 | 21.02 | 274.83 | 21.01 |
February | 672.00 | 21.20 | 174.50 | 21.16 | 174.50 | 21.13 |
March | 744.00 | 21.63 | 8.00 | 21.62 | 8.00 | 21.62 |
April | 720.00 | 22.16 | 0.00 | 22.16 | 0.00 | 22.16 |
May | 728.50 | 22.74 | 0.00 | 22.74 | 0.00 | 22.74 |
June | 250.33 | 23.13 | 146.50 | 23.38 | 0.00 | 23.38 |
July | 99.33 | 23.09 | 356.67 | 23.69 | 0.00 | 23.69 |
August | 17.83 | 23.28 | 418.00 | 23.81 | 0.00 | 23.81 |
September | 531.33 | 22.98 | 17.33 | 23.00 | 0.00 | 23.00 |
October | 744.00 | 22.15 | 0.00 | 22.15 | 0.00 | 22.15 |
November | 720.00 | 21.52 | 5.00 | 21.51 | 5.00 | 21.51 |
December | 744.00 | 21.11 | 97.83 | 21.09 | 97.83 | 21.08 |
Annual Sum or Average | 6715.33 | 21.87 | 1498.67 | 22.04 | 560.17 | 21.97 |
Minimum of Months | 17.83 | 21.03 | 0.00 | 21.02 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 23.28 | 418.00 | 23.81 | 274.83 | 23.81 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 283.67 | 22.72 | 415.17 | 23.24 | 142.83 | 23.39 |
February | 249.50 | 22.90 | 440.50 | 23.27 | 145.00 | 23.41 |
March | 275.83 | 23.38 | 588.67 | 23.35 | 212.33 | 23.49 |
April | 279.67 | 23.67 | 635.33 | 23.36 | 247.83 | 23.50 |
May | 308.50 | 23.92 | 712.67 | 23.34 | 301.83 | 23.48 |
June | 308.00 | 23.93 | 706.33 | 23.32 | 304.67 | 23.47 |
July | 329.67 | 23.94 | 742.33 | 23.32 | 329.67 | 23.47 |
August | 328.17 | 23.95 | 744.00 | 23.32 | 328.17 | 23.47 |
September | 305.50 | 23.95 | 701.17 | 23.34 | 304.17 | 23.49 |
October | 300.17 | 23.70 | 671.50 | 23.35 | 266.17 | 23.50 |
November | 251.17 | 23.41 | 562.33 | 23.37 | 195.33 | 23.50 |
December | 269.33 | 23.05 | 482.33 | 23.37 | 164.50 | 23.52 |
Annual Sum or Average | 3489.17 | 23.57 | 7402.33 | 23.33 | 2942.50 | 23.48 |
Minimum of Months | 249.50 | 22.72 | 415.17 | 23.24 | 142.83 | 23.39 |
Maximum of Months | 329.67 | 23.95 | 744.00 | 23.37 | 329.67 | 23.52 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 708.50 | 21.94 | 70.00 | 21.90 | 66.33 | 21.87 |
February | 574.50 | 22.13 | 78.50 | 22.21 | 46.67 | 22.20 |
March | 483.67 | 22.68 | 164.33 | 22.97 | 40.33 | 23.02 |
April | 398.83 | 22.82 | 327.50 | 23.24 | 105.83 | 23.30 |
May | 376.00 | 23.37 | 513.33 | 23.56 | 247.50 | 23.62 |
June | 295.33 | 23.76 | 615.83 | 23.73 | 258.50 | 23.78 |
July | 354.17 | 23.84 | 710.00 | 23.79 | 341.83 | 23.81 |
August | 334.00 | 23.93 | 736.50 | 23.85 | 333.67 | 23.87 |
September | 349.17 | 23.59 | 617.83 | 23.71 | 291.67 | 23.74 |
October | 370.83 | 22.84 | 394.50 | 23.33 | 126.50 | 23.38 |
November | 540.00 | 22.68 | 157.50 | 22.93 | 66.83 | 23.00 |
December | 656.33 | 22.24 | 57.33 | 22.37 | 20.33 | 22.41 |
Annual Sum or Average | 5441.33 | 22.81 | 4443.17 | 23.22 | 1946.00 | 23.30 |
Minimum of Months | 295.33 | 21.94 | 57.33 | 21.90 | 20.33 | 21.87 |
Maximum of Months | 708.50 | 23.93 | 736.50 | 23.85 | 341.83 | 23.87 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 731.33 | 22.26 | 7.33 | 22.27 | 7.33 | 22.28 |
February | 621.50 | 22.51 | 22.17 | 22.55 | 20.33 | 22.58 |
March | 543.00 | 23.00 | 108.67 | 23.15 | 29.00 | 23.18 |
April | 402.50 | 23.11 | 233.00 | 23.40 | 90.33 | 23.47 |
May | 342.83 | 23.51 | 439.50 | 23.70 | 212.83 | 23.75 |
June | 255.00 | 23.84 | 562.50 | 23.82 | 216.67 | 23.85 |
July | 307.67 | 23.96 | 679.67 | 23.86 | 302.83 | 23.89 |
August | 298.17 | 23.99 | 724.17 | 23.88 | 298.17 | 23.90 |
September | 286.33 | 23.83 | 595.17 | 23.83 | 255.00 | 23.86 |
October | 344.17 | 23.17 | 293.83 | 23.47 | 102.33 | 23.52 |
November | 568.50 | 23.03 | 85.33 | 23.13 | 49.50 | 23.19 |
December | 705.33 | 22.66 | 34.33 | 22.72 | 12.00 | 22.74 |
Annual Sum or Average | 5406.33 | 23.05 | 3785.67 | 23.37 | 1596.33 | 23.46 |
Minimum of Months | 255.00 | 22.26 | 7.33 | 22.27 | 7.33 | 22.28 |
Maximum of Months | 731.33 | 23.99 | 724.17 | 23.88 | 302.83 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.77 | 564.33 | 20.73 | 564.33 | 20.71 |
February | 672.00 | 20.96 | 319.17 | 20.85 | 319.17 | 20.79 |
March | 736.33 | 21.32 | 52.33 | 21.28 | 52.33 | 21.24 |
April | 699.00 | 21.47 | 11.00 | 21.46 | 11.00 | 21.45 |
May | 682.67 | 21.48 | 0.83 | 21.48 | 0.67 | 21.49 |
June | 607.83 | 21.40 | 6.67 | 21.42 | 2.17 | 21.43 |
July | 610.50 | 21.36 | 25.17 | 21.43 | 7.17 | 21.44 |
August | 597.50 | 21.33 | 27.83 | 21.42 | 3.83 | 21.43 |
September | 633.17 | 21.41 | 8.67 | 21.43 | 2.50 | 21.44 |
October | 719.50 | 21.38 | 28.67 | 21.35 | 28.33 | 21.33 |
November | 718.67 | 21.25 | 112.33 | 21.18 | 112.33 | 21.13 |
December | 744.00 | 20.94 | 411.67 | 20.86 | 411.67 | 20.82 |
Annual Sum or Average | 8165.17 | 21.25 | 1568.67 | 21.17 | 1515.50 | 21.11 |
Minimum of Months | 597.50 | 20.77 | 0.83 | 20.73 | 0.67 | 20.71 |
Maximum of Months | 744.00 | 21.48 | 564.33 | 21.48 | 564.33 | 21.49 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.59 | 627.17 | 20.56 | 627.17 | 20.54 |
February | 672.00 | 20.79 | 363.33 | 20.69 | 363.33 | 20.64 |
March | 741.17 | 21.16 | 103.83 | 21.10 | 103.83 | 21.04 |
April | 710.50 | 21.43 | 22.33 | 21.40 | 22.33 | 21.38 |
May | 695.67 | 21.50 | 1.00 | 21.50 | 1.00 | 21.50 |
June | 612.33 | 21.42 | 6.50 | 21.44 | 2.17 | 21.44 |
July | 615.33 | 21.37 | 23.17 | 21.43 | 7.00 | 21.45 |
August | 609.00 | 21.36 | 17.83 | 21.42 | 4.83 | 21.43 |
September | 663.67 | 21.47 | 3.83 | 21.47 | 2.67 | 21.48 |
October | 738.33 | 21.26 | 45.33 | 21.22 | 45.33 | 21.18 |
November | 720.00 | 21.02 | 211.67 | 20.93 | 211.67 | 20.87 |
December | 744.00 | 20.70 | 539.17 | 20.64 | 539.17 | 20.61 |
Annual Sum or Average | 8266.00 | 21.16 | 1965.17 | 21.06 | 1930.50 | 20.98 |
Minimum of Months | 609.00 | 20.59 | 1.00 | 20.56 | 1.00 | 20.54 |
Maximum of Months | 744.00 | 21.50 | 627.17 | 21.50 | 627.17 | 21.50 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.79 | 531.00 | 20.74 | 531.00 | 20.72 |
February | 672.00 | 20.92 | 276.83 | 20.84 | 276.83 | 20.79 |
March | 744.00 | 21.14 | 75.33 | 21.12 | 75.33 | 21.10 |
April | 720.00 | 21.29 | 6.17 | 21.29 | 6.17 | 21.28 |
May | 744.00 | 21.42 | 0.33 | 21.42 | 0.33 | 21.42 |
June | 720.00 | 21.57 | 3.50 | 21.57 | 3.50 | 21.58 |
July | 744.00 | 21.59 | 11.33 | 21.60 | 11.33 | 21.61 |
August | 744.00 | 21.59 | 11.67 | 21.60 | 11.67 | 21.60 |
September | 720.00 | 21.42 | 4.00 | 21.42 | 4.00 | 21.43 |
October | 744.00 | 21.20 | 14.17 | 21.19 | 14.17 | 21.19 |
November | 720.00 | 21.06 | 104.83 | 21.02 | 104.83 | 20.99 |
December | 744.00 | 20.91 | 353.67 | 20.85 | 353.67 | 20.82 |
Annual Sum or Average | 8760.00 | 21.24 | 1392.83 | 21.17 | 1392.83 | 21.12 |
Minimum of Months | 672.00 | 20.79 | 0.33 | 20.74 | 0.33 | 20.72 |
Maximum of Months | 744.00 | 21.59 | 531.00 | 21.60 | 531.00 | 21.61 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.80 | 549.17 | 20.76 | 549.17 | 20.74 |
February | 672.00 | 21.02 | 309.67 | 20.90 | 309.67 | 20.84 |
March | 738.83 | 21.41 | 46.00 | 21.38 | 46.00 | 21.34 |
April | 688.00 | 21.53 | 8.83 | 21.52 | 8.83 | 21.52 |
May | 655.17 | 21.47 | 0.50 | 21.47 | 0.50 | 21.47 |
June | 578.67 | 21.35 | 1.83 | 21.36 | 0.83 | 21.36 |
July | 574.17 | 21.26 | 11.17 | 21.29 | 5.50 | 21.30 |
August | 570.50 | 21.26 | 8.50 | 21.29 | 3.17 | 21.30 |
September | 606.33 | 21.36 | 2.83 | 21.36 | 2.33 | 21.37 |
October | 713.67 | 21.41 | 32.17 | 21.38 | 32.17 | 21.36 |
November | 720.00 | 21.29 | 98.50 | 21.23 | 98.50 | 21.19 |
December | 744.00 | 20.97 | 399.50 | 20.90 | 399.50 | 20.86 |
Annual Sum or Average | 8005.33 | 21.25 | 1468.67 | 21.18 | 1456.17 | 21.12 |
Minimum of Months | 570.50 | 20.80 | 0.50 | 20.76 | 0.50 | 20.74 |
Maximum of Months | 744.00 | 21.53 | 549.17 | 21.52 | 549.17 | 21.52 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.61 | 616.00 | 20.57 | 616.00 | 20.55 |
February | 672.00 | 20.84 | 342.83 | 20.73 | 342.83 | 20.68 |
March | 744.00 | 21.26 | 84.67 | 21.22 | 84.67 | 21.19 |
April | 719.50 | 21.56 | 13.67 | 21.55 | 13.67 | 21.54 |
May | 666.67 | 21.49 | 0.83 | 21.50 | 0.83 | 21.50 |
June | 579.00 | 21.35 | 2.17 | 21.36 | 0.67 | 21.36 |
July | 574.00 | 21.26 | 10.67 | 21.29 | 4.83 | 21.30 |
August | 574.67 | 21.27 | 4.83 | 21.28 | 3.50 | 21.29 |
September | 652.33 | 21.48 | 2.83 | 21.49 | 2.67 | 21.49 |
October | 742.50 | 21.35 | 42.00 | 21.32 | 42.00 | 21.29 |
November | 720.00 | 21.03 | 196.00 | 20.96 | 196.00 | 20.92 |
December | 744.00 | 20.71 | 526.00 | 20.65 | 526.00 | 20.63 |
Annual Sum or Average | 8132.67 | 21.17 | 1842.50 | 21.07 | 1833.67 | 21.00 |
Minimum of Months | 574.00 | 20.61 | 0.83 | 20.57 | 0.67 | 20.55 |
Maximum of Months | 744.00 | 21.56 | 616.00 | 21.55 | 616.00 | 21.54 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.04 | 142.17 | 21.03 | 142.17 | 21.03 |
February | 672.00 | 21.29 | 118.67 | 21.25 | 118.67 | 21.21 |
March | 744.00 | 21.97 | 0.00 | 21.97 | 0.00 | 21.97 |
April | 719.17 | 22.56 | 21.67 | 22.57 | 21.67 | 22.57 |
May | 698.33 | 22.98 | 113.17 | 22.99 | 113.17 | 22.99 |
June | 346.83 | 23.49 | 290.67 | 23.63 | 158.00 | 23.65 |
July | 265.50 | 23.64 | 516.50 | 23.78 | 216.00 | 23.77 |
August | 231.50 | 23.83 | 574.00 | 23.87 | 228.00 | 23.87 |
September | 523.67 | 23.27 | 211.50 | 23.35 | 164.50 | 23.38 |
October | 744.00 | 22.43 | 47.33 | 22.46 | 47.33 | 22.48 |
November | 720.00 | 21.64 | 6.67 | 21.65 | 6.67 | 21.65 |
December | 744.00 | 21.16 | 30.17 | 21.15 | 30.17 | 21.15 |
Annual Sum or Average | 7153.00 | 22.19 | 2072.50 | 22.45 | 1246.33 | 22.51 |
Minimum of Months | 231.50 | 21.04 | 0.00 | 21.03 | 0.00 | 21.03 |
Maximum of Months | 744.00 | 23.83 | 574.00 | 23.87 | 228.00 | 23.87 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.67 | 614.33 | 20.63 | 614.33 | 20.62 |
February | 672.00 | 20.88 | 376.00 | 20.77 | 376.00 | 20.72 |
March | 735.50 | 21.24 | 128.33 | 21.16 | 128.33 | 21.10 |
April | 685.50 | 21.39 | 36.00 | 21.36 | 36.00 | 21.34 |
May | 662.17 | 21.41 | 27.50 | 21.42 | 23.17 | 21.41 |
June | 594.33 | 21.35 | 31.50 | 21.44 | 8.33 | 21.45 |
July | 600.33 | 21.32 | 68.33 | 21.47 | 22.17 | 21.49 |
August | 589.50 | 21.30 | 73.33 | 21.50 | 14.33 | 21.52 |
September | 622.67 | 21.35 | 25.67 | 21.40 | 11.67 | 21.41 |
October | 714.67 | 21.29 | 66.17 | 21.25 | 63.50 | 21.20 |
November | 718.33 | 21.16 | 220.33 | 21.07 | 220.33 | 21.01 |
December | 744.00 | 20.83 | 526.83 | 20.76 | 526.83 | 20.73 |
Annual Sum or Average | 8083.00 | 21.17 | 2194.33 | 21.10 | 2045.00 | 21.03 |
Minimum of Months | 589.50 | 20.67 | 25.67 | 20.63 | 8.33 | 20.62 |
Maximum of Months | 744.00 | 21.41 | 614.33 | 21.50 | 614.33 | 21.52 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.54 | 652.00 | 20.52 | 652.00 | 20.51 |
February | 672.00 | 20.73 | 428.17 | 20.65 | 428.17 | 20.61 |
March | 740.33 | 21.07 | 207.67 | 20.98 | 207.67 | 20.91 |
April | 702.17 | 21.36 | 49.50 | 21.32 | 49.50 | 21.29 |
May | 675.50 | 21.43 | 27.33 | 21.43 | 25.33 | 21.43 |
June | 597.00 | 21.36 | 28.33 | 21.44 | 7.83 | 21.45 |
July | 603.67 | 21.33 | 60.83 | 21.46 | 22.00 | 21.47 |
August | 598.33 | 21.32 | 53.67 | 21.47 | 14.17 | 21.49 |
September | 651.00 | 21.40 | 18.17 | 21.42 | 12.67 | 21.43 |
October | 736.50 | 21.17 | 92.00 | 21.09 | 92.00 | 21.03 |
November | 720.00 | 20.91 | 351.67 | 20.83 | 351.67 | 20.79 |
December | 744.00 | 20.61 | 617.50 | 20.56 | 617.50 | 20.55 |
Annual Sum or Average | 8184.50 | 21.09 | 2586.83 | 20.99 | 2480.50 | 20.92 |
Minimum of Months | 597.00 | 20.54 | 18.17 | 20.52 | 7.83 | 20.51 |
Maximum of Months | 744.00 | 21.43 | 652.00 | 21.47 | 652.00 | 21.49 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.13 | 382.67 | 21.01 | 382.67 | 20.95 |
February | 668.67 | 21.21 | 237.33 | 21.09 | 237.33 | 21.03 |
March | 727.33 | 21.40 | 39.17 | 21.37 | 39.17 | 21.33 |
April | 686.17 | 21.45 | 15.50 | 21.44 | 15.50 | 21.43 |
May | 691.33 | 21.48 | 3.83 | 21.48 | 3.83 | 21.49 |
June | 635.67 | 21.46 | 7.67 | 21.47 | 7.67 | 21.48 |
July | 633.67 | 21.40 | 20.67 | 21.42 | 20.67 | 21.44 |
August | 618.50 | 21.39 | 15.83 | 21.41 | 15.83 | 21.43 |
September | 629.00 | 21.39 | 11.00 | 21.41 | 7.83 | 21.42 |
October | 682.33 | 21.36 | 36.17 | 21.34 | 32.17 | 21.32 |
November | 699.33 | 21.40 | 53.33 | 21.36 | 53.33 | 21.32 |
December | 738.00 | 21.25 | 216.00 | 21.15 | 216.00 | 21.08 |
Annual Sum or Average | 8154.00 | 21.36 | 1039.17 | 21.30 | 1032.00 | 21.26 |
Minimum of Months | 618.50 | 21.13 | 3.83 | 21.01 | 3.83 | 20.95 |
Maximum of Months | 744.00 | 21.48 | 382.67 | 21.48 | 382.67 | 21.49 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 598.33 | 23.00 | 52.00 | 23.08 | 15.83 | 23.10 |
February | 409.00 | 23.04 | 104.17 | 23.22 | 31.50 | 23.27 |
March | 244.33 | 23.26 | 272.50 | 23.61 | 33.17 | 23.63 |
April | 153.83 | 23.62 | 510.83 | 23.85 | 91.67 | 23.87 |
May | 224.33 | 23.98 | 693.17 | 23.95 | 219.33 | 23.96 |
June | 211.00 | 24.00 | 711.17 | 23.98 | 211.00 | 23.98 |
July | 291.83 | 24.00 | 744.00 | 23.98 | 291.83 | 23.98 |
August | 290.67 | 24.00 | 744.00 | 23.98 | 290.67 | 23.98 |
September | 270.67 | 23.99 | 711.17 | 23.95 | 270.67 | 23.96 |
October | 199.67 | 23.54 | 530.83 | 23.81 | 114.00 | 23.84 |
November | 333.33 | 23.27 | 199.83 | 23.50 | 59.50 | 23.55 |
December | 453.00 | 23.09 | 96.50 | 23.24 | 19.33 | 23.26 |
Annual Sum or Average | 3680.00 | 23.46 | 5370.17 | 23.75 | 1648.50 | 23.79 |
Minimum of Months | 153.83 | 23.00 | 52.00 | 23.08 | 15.83 | 23.10 |
Maximum of Months | 598.33 | 24.00 | 744.00 | 23.98 | 291.83 | 23.98 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 449.17 | 23.10 | 109.00 | 23.26 | 11.17 | 23.27 |
February | 299.50 | 23.17 | 174.50 | 23.46 | 28.00 | 23.49 |
March | 125.00 | 23.37 | 352.67 | 23.80 | 23.00 | 23.81 |
April | 110.50 | 23.77 | 586.50 | 23.93 | 81.00 | 23.93 |
May | 197.83 | 23.99 | 720.83 | 23.97 | 197.50 | 23.98 |
June | 197.17 | 24.00 | 719.17 | 23.99 | 197.17 | 23.99 |
July | 271.67 | 24.00 | 744.00 | 23.99 | 271.67 | 23.99 |
August | 269.50 | 24.00 | 744.00 | 23.99 | 269.50 | 23.99 |
September | 243.33 | 24.00 | 719.83 | 23.97 | 243.33 | 23.97 |
October | 137.17 | 23.75 | 610.83 | 23.91 | 103.67 | 23.92 |
November | 191.17 | 23.36 | 275.50 | 23.71 | 48.17 | 23.73 |
December | 299.67 | 23.16 | 166.00 | 23.44 | 12.33 | 23.45 |
Annual Sum or Average | 2791.67 | 23.58 | 5922.83 | 23.84 | 1486.50 | 23.87 |
Minimum of Months | 110.50 | 23.10 | 109.00 | 23.26 | 11.17 | 23.27 |
Maximum of Months | 449.17 | 24.00 | 744.00 | 23.99 | 271.67 | 23.99 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 529.33 | 23.75 | 611.17 | 23.87 | 448.67 | 23.92 |
February | 472.17 | 23.87 | 588.83 | 23.90 | 431.00 | 23.94 |
March | 523.33 | 24.04 | 695.83 | 23.98 | 520.33 | 24.00 |
April | 526.83 | 24.04 | 705.00 | 23.98 | 525.83 | 24.00 |
May | 573.00 | 24.00 | 742.67 | 23.96 | 573.00 | 23.98 |
June | 575.50 | 24.00 | 720.00 | 23.98 | 575.50 | 23.98 |
July | 614.33 | 23.99 | 744.00 | 23.98 | 614.33 | 23.98 |
August | 617.17 | 23.99 | 744.00 | 23.98 | 617.17 | 23.99 |
September | 565.50 | 23.99 | 720.00 | 23.96 | 565.50 | 23.97 |
October | 547.67 | 24.05 | 735.67 | 23.97 | 547.50 | 23.99 |
November | 510.50 | 24.00 | 657.17 | 23.96 | 500.17 | 23.99 |
December | 524.67 | 23.96 | 641.00 | 23.98 | 486.67 | 24.01 |
Annual Sum or Average | 6580.00 | 23.98 | 8305.33 | 23.96 | 6405.67 | 23.98 |
Minimum of Months | 472.17 | 23.75 | 588.83 | 23.87 | 431.00 | 23.92 |
Maximum of Months | 617.17 | 24.05 | 744.00 | 23.98 | 617.17 | 24.01 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.04 | 232.00 | 21.03 | 232.00 | 21.02 |
February | 672.00 | 21.25 | 167.67 | 21.20 | 167.67 | 21.17 |
March | 737.33 | 21.78 | 0.00 | 21.78 | 0.00 | 21.78 |
April | 658.83 | 22.35 | 2.33 | 22.35 | 0.00 | 22.35 |
May | 450.00 | 22.79 | 115.17 | 23.00 | 0.00 | 23.00 |
June | 113.33 | 23.13 | 488.33 | 23.73 | 0.00 | 23.73 |
July | 53.83 | 22.96 | 626.00 | 23.80 | 0.00 | 23.80 |
August | 0.00 | 0.00 | 699.50 | 23.88 | 0.00 | 23.88 |
September | 292.00 | 22.84 | 203.50 | 23.24 | 0.00 | 23.24 |
October | 717.33 | 22.15 | 6.33 | 22.16 | 0.00 | 22.16 |
November | 720.00 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
December | 744.00 | 21.12 | 69.50 | 21.11 | 69.50 | 21.10 |
Annual Sum or Average | 5902.67 | 21.78 | 2610.33 | 22.26 | 469.17 | 22.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.03 | 0.00 | 21.02 |
Maximum of Months | 744.00 | 23.13 | 699.50 | 23.88 | 232.00 | 23.88 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.18693 | 29.32202 | 0.05837 | 5.26973 |
February | 672.00000 | 22.64626 | 32.10642 | -0.0610 | 5.35488 |
March | 744.00000 | 22.02483 | 39.17135 | -0.1740 | 5.91374 |
April | 720.00000 | 21.42002 | 50.47066 | -0.2622 | 6.69286 |
May | 744.00000 | 21.82971 | 59.87316 | -1.2238 | 36.58459 |
June | 720.00000 | 22.69320 | 58.14748 | -0.9165 | 23.05533 |
July | 744.00000 | 23.22445 | 59.87204 | -0.7077 | 15.79107 |
August | 744.00000 | 23.67985 | 58.26261 | -0.5453 | 11.40468 |
September | 720.00000 | 23.90397 | 56.18801 | -0.4653 | 9.61824 |
October | 744.00000 | 23.94807 | 46.43888 | 0.39386 | 8.33767 |
November | 720.00000 | 23.96297 | 35.60187 | 0.32265 | 7.33574 |
December | 744.00000 | 23.86988 | 31.49024 | 0.25858 | 6.55745 |
Annual Sum or Average | 8760.00000 | 23.03610 | 46.48921 | -0.2781 | 11.88117 |
Minimum of Months | 672.00000 | 21.42002 | 29.32202 | -1.2238 | 5.26973 |
Maximum of Months | 744.00000 | 23.96297 | 59.87316 | 0.39386 | 36.58459 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.19896 | 31.05430 | -0.4534 | 10.10265 |
February | 672.00000 | 21.40805 | 33.07085 | -0.3522 | 8.95340 |
March | 744.00000 | 21.87413 | 38.32279 | -0.1338 | 6.98022 |
April | 720.00000 | 22.12909 | 47.62991 | 0.00533 | 6.50955 |
May | 744.00000 | 22.55947 | 56.78629 | -0.8186 | 20.83167 |
June | 720.00000 | 23.25665 | 56.05702 | -0.5494 | 12.74764 |
July | 744.00000 | 23.42938 | 59.46744 | -0.4507 | 10.27630 |
August | 744.00000 | 23.64052 | 58.83869 | -0.3631 | 8.33023 |
September | 720.00000 | 22.99591 | 59.24839 | -0.6254 | 15.34387 |
October | 744.00000 | 22.26493 | 50.62401 | 0.05883 | 7.04706 |
November | 720.00000 | 21.69935 | 39.72067 | -0.1803 | 7.22291 |
December | 744.00000 | 21.39057 | 34.83206 | -0.3414 | 8.66124 |
Annual Sum or Average | 8760.00000 | 22.32590 | 47.21467 | -0.3505 | 10.25897 |
Minimum of Months | 672.00000 | 21.19896 | 31.05430 | -0.8186 | 6.50955 |
Maximum of Months | 744.00000 | 23.64052 | 59.46744 | 0.05883 | 20.83167 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.57796 | 32.06300 | -0.2984 | 7.38867 |
February | 672.00000 | 21.94576 | 33.63213 | -0.1900 | 6.71678 |
March | 744.00000 | 22.68288 | 38.38434 | 0.03886 | 5.78477 |
April | 720.00000 | 22.98245 | 47.02737 | 0.17659 | 6.32665 |
May | 744.00000 | 23.28121 | 56.01386 | -0.6398 | 14.29885 |
June | 720.00000 | 23.61618 | 56.05662 | -0.5027 | 10.78477 |
July | 744.00000 | 23.68375 | 59.35249 | -0.4497 | 9.56020 |
August | 744.00000 | 23.77169 | 59.05452 | -0.4156 | 8.81439 |
September | 720.00000 | 23.49439 | 58.74383 | -0.5361 | 11.55278 |
October | 744.00000 | 22.97978 | 50.17598 | 0.19608 | 6.42978 |
November | 720.00000 | 22.52547 | 39.53883 | 0.00301 | 5.64447 |
December | 744.00000 | 21.97058 | 35.34640 | -0.1714 | 6.28350 |
Annual Sum or Average | 8760.00000 | 22.88060 | 47.19125 | -0.2330 | 8.30875 |
Minimum of Months | 672.00000 | 21.57796 | 32.06300 | -0.6398 | 5.64447 |
Maximum of Months | 744.00000 | 23.77169 | 59.35249 | 0.19608 | 14.29885 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.80741 | 26.21142 | 0.53650 | 14.15473 |
February | 672.00000 | 22.87676 | 28.02467 | 0.59042 | 15.47410 |
March | 744.00000 | 22.97881 | 33.60796 | 0.69469 | 17.99077 |
April | 720.00000 | 23.00507 | 42.82063 | 0.78290 | 20.55578 |
May | 744.00000 | 23.01221 | 52.57044 | 0.16218 | 10.65947 |
June | 720.00000 | 23.02710 | 53.60081 | 0.20720 | 10.89458 |
July | 744.00000 | 23.04130 | 57.03658 | 0.24261 | 10.97635 |
August | 744.00000 | 23.03913 | 57.01526 | 0.24720 | 11.10145 |
September | 720.00000 | 23.02944 | 55.89328 | 0.19319 | 10.72659 |
October | 744.00000 | 23.01131 | 45.81775 | 0.79402 | 20.82671 |
November | 720.00000 | 22.98085 | 34.51131 | 0.68560 | 17.63584 |
December | 744.00000 | 22.92420 | 29.67476 | 0.60912 | 15.90525 |
Annual Sum or Average | 8760.00000 | 22.97827 | 43.14913 | 0.47801 | 14.73347 |
Minimum of Months | 672.00000 | 22.80741 | 26.21142 | 0.16218 | 10.65947 |
Maximum of Months | 744.00000 | 23.04130 | 57.03658 | 0.79402 | 20.82671 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.01932 | 35.97214 | -0.1680 | 6.88227 |
February | 672.00000 | 22.37723 | 37.53754 | -0.0408 | 6.78601 |
March | 744.00000 | 23.04165 | 42.27183 | 0.20515 | 7.14801 |
April | 720.00000 | 23.17646 | 51.03451 | 0.31211 | 8.07882 |
May | 744.00000 | 23.39936 | 59.98282 | -0.4693 | 10.58102 |
June | 720.00000 | 23.62511 | 60.05890 | -0.3463 | 8.16871 |
July | 744.00000 | 23.70128 | 63.20207 | -0.2782 | 7.06598 |
August | 744.00000 | 23.79981 | 62.63780 | -0.2241 | 6.38644 |
September | 720.00000 | 23.59630 | 62.42597 | -0.3473 | 8.54934 |
October | 744.00000 | 23.28991 | 53.69402 | 0.36634 | 9.04680 |
November | 720.00000 | 22.94296 | 43.26299 | 0.17994 | 6.96986 |
December | 744.00000 | 22.41474 | 39.24704 | -0.0170 | 6.42276 |
Annual Sum or Average | 8760.00000 | 23.11900 | 51.01852 | -0.0694 | 7.67820 |
Minimum of Months | 672.00000 | 22.01932 | 35.97214 | -0.4693 | 6.38644 |
Maximum of Months | 744.00000 | 23.79981 | 63.20207 | 0.36634 | 10.58102 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.28385 | 34.65991 | -0.1091 | 6.01067 |
February | 672.00000 | 22.61559 | 36.17794 | -0.0057 | 6.11406 |
March | 744.00000 | 23.21663 | 40.95906 | 0.19623 | 6.50979 |
April | 720.00000 | 23.37839 | 49.50712 | 0.30394 | 7.54818 |
May | 744.00000 | 23.54408 | 58.38764 | -0.5065 | 10.98001 |
June | 720.00000 | 23.69950 | 58.61166 | -0.4230 | 9.14501 |
July | 744.00000 | 23.75104 | 61.82746 | -0.3733 | 8.15463 |
August | 744.00000 | 23.80953 | 61.50960 | -0.3468 | 7.67170 |
September | 720.00000 | 23.69688 | 60.97549 | -0.4175 | 9.01509 |
October | 744.00000 | 23.45264 | 52.28869 | 0.34415 | 7.96543 |
November | 720.00000 | 23.18336 | 41.87127 | 0.19014 | 6.41412 |
December | 744.00000 | 22.71720 | 37.77499 | 0.03057 | 5.75283 |
Annual Sum or Average | 8760.00000 | 23.28220 | 49.62076 | -0.0939 | 7.61442 |
Minimum of Months | 672.00000 | 22.28385 | 34.65991 | -0.5065 | 5.75283 |
Maximum of Months | 744.00000 | 23.80953 | 61.82746 | 0.34415 | 10.98001 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.77492 | 34.45712 | -0.6252 | 13.83862 |
February | 672.00000 | 20.96124 | 37.35230 | -0.5200 | 11.73002 |
March | 744.00000 | 21.34338 | 42.27860 | -0.3075 | 7.83211 |
April | 720.00000 | 21.52475 | 50.73198 | -0.1678 | 6.49446 |
May | 744.00000 | 21.63563 | 55.89995 | -1.1767 | 35.33605 |
June | 720.00000 | 21.70404 | 54.28545 | -1.1001 | 31.96512 |
July | 744.00000 | 21.70992 | 56.70896 | -1.0665 | 30.47842 |
August | 744.00000 | 21.72486 | 55.97823 | -1.0521 | 29.89243 |
September | 720.00000 | 21.64278 | 57.76703 | -1.1450 | 33.95303 |
October | 744.00000 | 21.43996 | 54.47728 | -0.1912 | 6.63787 |
November | 720.00000 | 21.25133 | 43.92348 | -0.3602 | 8.53069 |
December | 744.00000 | 20.94370 | 39.12712 | -0.5252 | 11.42878 |
Annual Sum or Average | 8760.00000 | 21.38999 | 48.64068 | -0.6877 | 19.05620 |
Minimum of Months | 672.00000 | 20.77492 | 34.45712 | -1.1767 | 6.49446 |
Maximum of Months | 744.00000 | 21.72486 | 57.76703 | -0.1678 | 35.33605 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.59077 | 34.77739 | -0.6966 | 15.96193 |
February | 672.00000 | 20.79265 | 37.65617 | -0.5858 | 13.25684 |
March | 744.00000 | 21.17236 | 42.80540 | -0.3688 | 8.59020 |
April | 720.00000 | 21.45066 | 51.10630 | -0.1972 | 6.64290 |
May | 744.00000 | 21.61889 | 56.16229 | -1.1884 | 35.80598 |
June | 720.00000 | 21.70531 | 54.31219 | -1.1009 | 31.97239 |
July | 744.00000 | 21.71060 | 56.79866 | -1.0687 | 30.54743 |
August | 744.00000 | 21.72035 | 56.36352 | -1.0641 | 30.33899 |
September | 720.00000 | 21.61269 | 58.61520 | -1.1729 | 35.07445 |
October | 744.00000 | 21.27577 | 55.44745 | -0.2521 | 7.01401 |
November | 720.00000 | 21.01657 | 44.60854 | -0.4445 | 9.82767 |
December | 744.00000 | 20.69971 | 39.64193 | -0.6100 | 13.49981 |
Annual Sum or Average | 8760.00000 | 21.28272 | 49.08366 | -0.7303 | 19.92116 |
Minimum of Months | 672.00000 | 20.59077 | 34.77739 | -1.1884 | 6.64290 |
Maximum of Months | 744.00000 | 21.72035 | 58.61520 | -0.1972 | 35.80598 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.78574 | 33.18999 | -0.5980 | 13.05434 |
February | 672.00000 | 20.92089 | 35.90121 | -0.5248 | 11.39329 |
March | 744.00000 | 21.13905 | 41.39425 | -0.3964 | 8.58872 |
April | 720.00000 | 21.29370 | 49.92535 | -0.2823 | 6.98834 |
May | 744.00000 | 21.42340 | 56.19392 | -1.3395 | 42.58958 |
June | 720.00000 | 21.56794 | 55.08112 | -1.2650 | 39.07212 |
July | 744.00000 | 21.59293 | 57.73098 | -1.2333 | 37.54668 |
August | 744.00000 | 21.58632 | 57.49676 | -1.2388 | 37.78474 |
September | 720.00000 | 21.41913 | 58.52164 | -1.3267 | 41.93784 |
October | 744.00000 | 21.19627 | 54.05822 | -0.2974 | 7.04329 |
November | 720.00000 | 21.06139 | 42.69414 | -0.4274 | 9.15233 |
December | 744.00000 | 20.90584 | 37.88016 | -0.5247 | 11.17482 |
Annual Sum or Average | 8760.00000 | 21.24265 | 48.40596 | -0.7896 | 22.25967 |
Minimum of Months | 672.00000 | 20.78574 | 33.18999 | -1.3395 | 6.98834 |
Maximum of Months | 744.00000 | 21.59293 | 58.52164 | -0.2823 | 42.58958 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.80352 | 34.39359 | -0.6192 | 13.66840 |
February | 672.00000 | 21.02080 | 37.25604 | -0.5033 | 11.43064 |
March | 744.00000 | 21.42662 | 42.07521 | -0.2931 | 7.67218 |
April | 720.00000 | 21.60587 | 50.40733 | -0.1508 | 6.43875 |
May | 744.00000 | 21.69089 | 55.40133 | -1.1543 | 34.44458 |
June | 720.00000 | 21.73995 | 53.93425 | -1.0829 | 31.32073 |
July | 744.00000 | 21.73119 | 56.15537 | -1.0532 | 30.02557 |
August | 744.00000 | 21.74063 | 55.69159 | -1.0454 | 29.70359 |
September | 720.00000 | 21.66837 | 57.45260 | -1.1356 | 33.62482 |
October | 744.00000 | 21.48890 | 54.13243 | -0.1813 | 6.63574 |
November | 720.00000 | 21.29020 | 43.82301 | -0.3524 | 8.36218 |
December | 744.00000 | 20.96787 | 39.05244 | -0.5185 | 11.21794 |
Annual Sum or Average | 8760.00000 | 21.43302 | 48.37163 | -0.6755 | 18.75852 |
Minimum of Months | 672.00000 | 20.80352 | 34.39359 | -1.1543 | 6.43875 |
Maximum of Months | 744.00000 | 21.74063 | 57.45260 | -0.1508 | 34.44458 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.60528 | 34.73261 | -0.6937 | 15.87526 |
February | 672.00000 | 20.84127 | 37.56216 | -0.5709 | 12.90055 |
March | 744.00000 | 21.25580 | 42.63701 | -0.3544 | 8.26495 |
April | 720.00000 | 21.55735 | 50.62669 | -0.1758 | 6.52039 |
May | 744.00000 | 21.68506 | 55.66025 | -1.1628 | 34.77988 |
June | 720.00000 | 21.74097 | 53.98954 | -1.0836 | 31.33129 |
July | 744.00000 | 21.73104 | 56.27429 | -1.0556 | 30.10232 |
August | 744.00000 | 21.73847 | 56.09411 | -1.0565 | 30.11190 |
September | 720.00000 | 21.65752 | 58.06796 | -1.1589 | 34.55587 |
October | 744.00000 | 21.35807 | 54.85585 | -0.2366 | 6.90936 |
November | 720.00000 | 21.02815 | 44.59074 | -0.4420 | 9.66709 |
December | 744.00000 | 20.71225 | 39.58441 | -0.6058 | 13.36117 |
Annual Sum or Average | 8760.00000 | 21.32806 | 48.78078 | -0.7176 | 19.57535 |
Minimum of Months | 672.00000 | 20.60528 | 34.73261 | -1.1628 | 6.52039 |
Maximum of Months | 744.00000 | 21.74097 | 58.06796 | -0.1758 | 34.77988 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.67161 | 34.99924 | -0.6903 | 15.75257 |
February | 672.00000 | 20.87715 | 37.92895 | -0.5736 | 13.16674 |
March | 744.00000 | 21.26690 | 42.98427 | -0.3468 | 8.58615 |
April | 720.00000 | 21.47960 | 51.89936 | -0.1876 | 6.85779 |
May | 744.00000 | 21.61995 | 57.26729 | -1.1813 | 35.75891 |
June | 720.00000 | 21.69492 | 55.18591 | -1.0984 | 32.08836 |
July | 744.00000 | 21.69957 | 57.72802 | -1.0613 | 30.43940 |
August | 744.00000 | 21.71756 | 56.79093 | -1.0467 | 29.84262 |
September | 720.00000 | 21.61490 | 59.43733 | -1.1583 | 34.73894 |
October | 744.00000 | 21.36986 | 55.75724 | -0.2253 | 7.13729 |
November | 720.00000 | 21.16268 | 44.78246 | -0.4086 | 9.49143 |
December | 744.00000 | 20.82803 | 39.83899 | -0.5869 | 13.00849 |
Annual Sum or Average | 8760.00000 | 21.33562 | 49.60961 | -0.7149 | 19.78152 |
Minimum of Months | 672.00000 | 20.67161 | 34.99924 | -1.1813 | 6.85779 |
Maximum of Months | 744.00000 | 21.71756 | 59.43733 | -0.1876 | 35.75891 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.54207 | 35.25725 | -0.7525 | 17.74298 |
February | 672.00000 | 20.73273 | 38.20814 | -0.6366 | 14.68137 |
March | 744.00000 | 21.08550 | 43.53610 | -0.4129 | 9.52122 |
April | 720.00000 | 21.40677 | 52.30082 | -0.2179 | 7.04982 |
May | 744.00000 | 21.60552 | 57.55096 | -1.1928 | 36.21741 |
June | 720.00000 | 21.69640 | 55.21187 | -1.0991 | 32.09101 |
July | 744.00000 | 21.70054 | 57.80453 | -1.0635 | 30.50443 |
August | 744.00000 | 21.71279 | 57.22542 | -1.0589 | 30.27914 |
September | 720.00000 | 21.58372 | 60.42181 | -1.1875 | 35.91036 |
October | 744.00000 | 21.19022 | 56.81430 | -0.2924 | 7.67863 |
November | 720.00000 | 20.91422 | 45.48733 | -0.4989 | 11.06303 |
December | 744.00000 | 20.60580 | 40.32001 | -0.6694 | 15.23006 |
Annual Sum or Average | 8760.00000 | 21.23360 | 50.07191 | -0.7579 | 20.70382 |
Minimum of Months | 672.00000 | 20.54207 | 35.25725 | -1.1928 | 7.04982 |
Maximum of Months | 744.00000 | 21.71279 | 60.42181 | -0.2179 | 36.21741 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.12537 | 35.24153 | -0.5056 | 11.48628 |
February | 672.00000 | 21.21694 | 38.00924 | -0.4318 | 10.08067 |
March | 744.00000 | 21.44812 | 42.57340 | -0.2805 | 7.69031 |
April | 720.00000 | 21.54003 | 51.12024 | -0.1859 | 6.72184 |
May | 744.00000 | 21.61480 | 56.79902 | -1.2259 | 37.71667 |
June | 720.00000 | 21.68190 | 55.36552 | -1.1629 | 34.81578 |
July | 744.00000 | 21.69038 | 57.73361 | -1.1245 | 33.03749 |
August | 744.00000 | 21.71395 | 56.52480 | -1.1001 | 32.04595 |
September | 720.00000 | 21.63534 | 57.78098 | -1.1731 | 35.39639 |
October | 744.00000 | 21.52134 | 54.20272 | -0.1651 | 6.64951 |
November | 720.00000 | 21.45881 | 43.93420 | -0.2802 | 7.73127 |
December | 744.00000 | 21.26512 | 39.66807 | -0.4083 | 9.56125 |
Annual Sum or Average | 8760.00000 | 21.49400 | 49.13788 | -0.6720 | 19.46857 |
Minimum of Months | 672.00000 | 21.12537 | 35.24153 | -1.2259 | 6.64951 |
Maximum of Months | 744.00000 | 21.71395 | 57.78098 | -0.1651 | 37.71667 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.18525 | 35.06707 | 0.11567 | 6.29169 |
February | 672.00000 | 23.38626 | 36.30292 | 0.20045 | 6.94283 |
March | 744.00000 | 23.69649 | 40.80243 | 0.35461 | 8.18008 |
April | 720.00000 | 23.82907 | 48.90499 | 0.47569 | 10.15610 |
May | 744.00000 | 23.92065 | 57.44804 | -0.2637 | 6.69025 |
June | 720.00000 | 23.96848 | 57.94853 | -0.1998 | 5.98498 |
July | 744.00000 | 23.97503 | 61.18274 | -0.1634 | 5.60034 |
August | 744.00000 | 23.97369 | 61.12327 | -0.1631 | 5.59084 |
September | 720.00000 | 23.92114 | 60.62333 | -0.2397 | 6.36621 |
October | 744.00000 | 23.76446 | 52.15500 | 0.46351 | 9.90221 |
November | 720.00000 | 23.59696 | 42.04120 | 0.31696 | 7.76212 |
December | 744.00000 | 23.41051 | 38.04977 | 0.21144 | 6.75668 |
Annual Sum or Average | 8760.00000 | 23.72053 | 49.37726 | 0.09154 | 7.18317 |
Minimum of Months | 672.00000 | 23.18525 | 35.06707 | -0.2637 | 5.59084 |
Maximum of Months | 744.00000 | 23.97503 | 61.18274 | 0.47569 | 10.15610 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.42352 | 34.07551 | 0.21125 | 6.73613 |
February | 672.00000 | 23.57929 | 35.33073 | 0.28437 | 7.56683 |
March | 744.00000 | 23.81970 | 39.89747 | 0.41907 | 9.08951 |
April | 720.00000 | 23.90155 | 48.12847 | 0.52512 | 11.10899 |
May | 744.00000 | 23.95907 | 56.81438 | -0.2085 | 6.09105 |
June | 720.00000 | 23.98407 | 57.47125 | -0.1572 | 5.64825 |
July | 744.00000 | 23.98746 | 60.72052 | -0.1228 | 5.34809 |
August | 744.00000 | 23.98693 | 60.67255 | -0.1233 | 5.34422 |
September | 720.00000 | 23.95652 | 60.01897 | -0.1880 | 5.85644 |
October | 744.00000 | 23.85929 | 51.26788 | 0.51886 | 10.94583 |
November | 720.00000 | 23.75198 | 41.05838 | 0.39034 | 8.69727 |
December | 744.00000 | 23.60858 | 37.00931 | 0.29721 | 7.47821 |
Annual Sum or Average | 8760.00000 | 23.81925 | 48.61304 | 0.15292 | 7.48828 |
Minimum of Months | 672.00000 | 23.42352 | 34.07551 | -0.2085 | 5.34422 |
Maximum of Months | 744.00000 | 23.98746 | 60.72052 | 0.52512 | 11.10899 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.67991 | 32.64743 | 0.87658 | 24.36906 |
February | 672.00000 | 23.74047 | 34.10276 | 0.93950 | 26.57967 |
March | 744.00000 | 23.85781 | 38.94919 | 1.06512 | 31.20736 |
April | 720.00000 | 23.90543 | 47.16605 | 1.17372 | 35.86453 |
May | 744.00000 | 23.93181 | 55.85955 | 0.72105 | 20.03346 |
June | 720.00000 | 23.96289 | 56.67412 | 0.78795 | 21.74972 |
July | 744.00000 | 23.97037 | 59.86852 | 0.82865 | 22.77948 |
August | 744.00000 | 23.97578 | 59.80263 | 0.83112 | 22.75083 |
September | 720.00000 | 23.94125 | 58.91490 | 0.74549 | 20.27018 |
October | 744.00000 | 23.88839 | 50.08310 | 1.16556 | 35.37230 |
November | 720.00000 | 23.81134 | 39.95108 | 1.03243 | 29.89856 |
December | 744.00000 | 23.78017 | 35.76386 | 0.95263 | 26.98691 |
Annual Sum or Average | 8760.00000 | 23.87116 | 47.55689 | 0.92645 | 26.48275 |
Minimum of Months | 672.00000 | 23.67991 | 32.64743 | 0.72105 | 20.03346 |
Maximum of Months | 744.00000 | 23.97578 | 59.86852 | 1.17372 | 35.86453 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.02517 | 29.77131 | -0.4930 | 10.27375 |
February | 672.00000 | 21.20117 | 31.83269 | -0.4230 | 9.13755 |
March | 744.00000 | 21.62863 | 37.30955 | -0.2600 | 7.02633 |
April | 720.00000 | 22.15560 | 45.96621 | -0.0733 | 5.77147 |
May | 744.00000 | 22.75740 | 54.84212 | -0.8908 | 22.19276 |
June | 720.00000 | 23.44638 | 54.40411 | -0.6475 | 14.21139 |
July | 744.00000 | 23.63544 | 57.91358 | -0.5551 | 11.63393 |
August | 744.00000 | 23.70676 | 57.94936 | -0.5297 | 10.94936 |
September | 720.00000 | 23.11550 | 57.69806 | -0.7438 | 16.97763 |
October | 744.00000 | 22.15052 | 49.58680 | -0.0518 | 5.58723 |
November | 720.00000 | 21.51799 | 38.45277 | -0.2823 | 7.18396 |
December | 744.00000 | 21.10644 | 33.77318 | -0.4265 | 9.13977 |
Annual Sum or Average | 8760.00000 | 22.29320 | 45.86979 | -0.4484 | 10.85228 |
Minimum of Months | 672.00000 | 21.02517 | 29.77131 | -0.8908 | 5.58723 |
Maximum of Months | 744.00000 | 23.70676 | 57.94936 | -0.0518 | 22.19276 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.03823 | 33.56888 | -0.4733 | 9.83285 |
February | 672.00000 | 21.28845 | 35.49489 | -0.3930 | 8.60555 |
March | 744.00000 | 21.96769 | 40.47748 | -0.1813 | 6.16913 |
April | 720.00000 | 22.56464 | 48.70598 | 0.02075 | 5.54537 |
May | 744.00000 | 23.01542 | 57.63946 | -0.8191 | 19.49394 |
June | 720.00000 | 23.61468 | 57.16040 | -0.6060 | 12.99806 |
July | 744.00000 | 23.75608 | 60.30501 | -0.5318 | 11.04617 |
August | 744.00000 | 23.83417 | 60.13133 | -0.5048 | 10.37139 |
September | 720.00000 | 23.37751 | 60.14090 | -0.6718 | 14.75759 |
October | 744.00000 | 22.43047 | 52.49342 | 0.01071 | 5.54493 |
November | 720.00000 | 21.64452 | 41.99060 | -0.2543 | 6.74387 |
December | 744.00000 | 21.15631 | 37.44982 | -0.4106 | 8.81638 |
Annual Sum or Average | 8760.00000 | 22.48018 | 48.87074 | -0.4015 | 10.00499 |
Minimum of Months | 672.00000 | 21.03823 | 33.56888 | -0.8191 | 5.54493 |
Maximum of Months | 744.00000 | 23.83417 | 60.30501 | 0.02075 | 19.49394 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.03650 | 31.17218 | -0.4826 | 10.08647 |
February | 672.00000 | 21.25127 | 33.10696 | -0.3983 | 8.81736 |
March | 744.00000 | 21.79594 | 38.21749 | -0.2001 | 6.62344 |
April | 720.00000 | 22.45498 | 46.39301 | 0.02337 | 5.99236 |
May | 744.00000 | 23.10107 | 54.73206 | -0.7353 | 17.20740 |
June | 720.00000 | 23.68339 | 54.14963 | -0.5194 | 11.18821 |
July | 744.00000 | 23.76453 | 57.47358 | -0.4600 | 9.67238 |
August | 744.00000 | 23.84958 | 57.24720 | -0.4296 | 8.95314 |
September | 720.00000 | 23.29294 | 57.72449 | -0.6449 | 14.37043 |
October | 744.00000 | 22.19498 | 50.45566 | -0.0202 | 5.84154 |
November | 720.00000 | 21.48365 | 39.80462 | -0.2761 | 7.18848 |
December | 744.00000 | 21.12354 | 35.07758 | -0.4156 | 8.97193 |
Annual Sum or Average | 8760.00000 | 22.42557 | 46.36930 | -0.3800 | 9.58114 |
Minimum of Months | 672.00000 | 21.03650 | 31.17218 | -0.7353 | 5.84154 |
Maximum of Months | 744.00000 | 23.84958 | 57.72449 | 0.02337 | 17.20740 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.06863 | 29.26434 | -0.4698 | 9.84977 |
February | 672.00000 | 21.30173 | 31.16786 | -0.3892 | 8.66978 |
March | 744.00000 | 21.80095 | 36.46711 | -0.2130 | 6.62347 |
April | 720.00000 | 22.33871 | 44.99054 | -0.0229 | 5.71068 |
May | 744.00000 | 22.93418 | 53.72117 | -0.8185 | 19.68729 |
June | 720.00000 | 23.56738 | 53.31427 | -0.5899 | 12.70846 |
July | 744.00000 | 23.71552 | 56.79616 | -0.5099 | 10.61803 |
August | 744.00000 | 23.77415 | 56.79692 | -0.4887 | 10.08824 |
September | 720.00000 | 23.27825 | 56.48287 | -0.6757 | 14.97572 |
October | 744.00000 | 22.33320 | 48.52076 | -0.0023 | 5.54979 |
November | 720.00000 | 21.68598 | 37.62331 | -0.2364 | 6.74809 |
December | 744.00000 | 21.19913 | 33.14550 | -0.3953 | 8.66928 |
Annual Sum or Average | 8760.00000 | 22.42235 | 44.93452 | -0.4013 | 10.00193 |
Minimum of Months | 672.00000 | 21.06863 | 29.26434 | -0.8185 | 5.54979 |
Maximum of Months | 744.00000 | 23.77415 | 56.79692 | -0.0023 | 19.68729 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.546492E+10 | 71446.65 | 19-JAN-19:04 | 263.87 | 0.164197E+11 | 0.00 | 0.218847E+11 | 1.12 | 3.35 | 19-JAN-19:04 | 0.00 | 0.00 |
February | 0.172414E+11 | 95189.84 | 28-FEB-16:02 | 352.63 | 0.496079E+11 | 0.00 | 0.668494E+11 | 1.62 | 3.50 | 28-FEB-19:02 | 0.00 | 0.00 |
March | 0.490703E+11 | 121332.78 | 30-MAR-18:03 | 585.29 | 0.143169E+12 | 0.00 | 0.192240E+12 | 2.39 | 3.55 | 28-MAR-18:02 | 0.00 | 0.00 |
April | 0.969259E+11 | 123854.53 | 12-APR-15:03 | 674.57 | 0.287586E+12 | 0.00 | 0.384512E+12 | 2.83 | 3.95 | 22-APR-18:02 | 0.00 | 0.00 |
May | 0.174903E+12 | 156143.07 | 30-MAY-18:03 | 740.81 | 0.543640E+12 | 0.00 | 0.718542E+12 | 3.06 | 4.07 | 25-MAY-18:03 | 0.00 | 0.00 |
June | 0.263352E+12 | 186202.86 | 28-JUN-18:05 | 719.75 | 0.863653E+12 | 0.00 | 0.112700E+13 | 3.25 | 4.19 | 22-JUN-21:00 | 0.00 | 0.00 |
July | 0.326602E+12 | 205786.48 | 06-JUL-18:03 | 744.00 | 0.110229E+13 | 0.00 | 0.142889E+13 | 3.40 | 4.20 | 29-JUL-18:04 | 0.00 | 0.00 |
August | 0.344554E+12 | 206666.67 | 18-AUG-18:03 | 744.00 | 0.117991E+13 | 0.00 | 0.152446E+13 | 3.43 | 4.11 | 07-AUG-21:00 | 0.00 | 0.00 |
September | 0.222424E+12 | 182210.05 | 07-SEP-18:03 | 718.67 | 0.743298E+12 | 0.00 | 0.965721E+12 | 3.26 | 4.16 | 21-SEP-18:02 | 0.00 | 0.00 |
October | 0.943958E+11 | 161459.40 | 18-OCT-20:40 | 649.95 | 0.302595E+12 | 0.00 | 0.396991E+12 | 2.73 | 4.08 | 18-OCT-20:40 | 0.00 | 0.00 |
November | 0.370684E+11 | 106369.33 | 27-NOV-19:03 | 522.91 | 0.109335E+12 | 0.00 | 0.146404E+12 | 2.23 | 3.92 | 05-NOV-18:02 | 0.00 | 0.00 |
December | 0.102029E+11 | 72823.41 | 12-DEC-16:02 | 358.81 | 0.300636E+11 | 0.00 | 0.402666E+11 | 1.51 | 3.19 | 15-DEC-16:04 | 0.00 | 0.00 |
Annual Sum or Average | 0.164220E+13 | 7075.24 | 0.537156E+13 | 0.00 | 0.701377E+13 | 2.57 | 0.00 | 0.00 | ||||
Minimum of Months | 0.546492E+10 | 71446.65 | 263.87 | 0.164197E+11 | 0.00 | 0.218847E+11 | 1.12 | 3.19 | 0.00 | 0.00 | ||
Maximum of Months | 0.344554E+12 | 206666.67 | 744.00 | 0.117991E+13 | 0.00 | 0.152446E+13 | 3.43 | 4.20 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.106050E+12 | 0.00 | 735.58 | 208794.71 | 25-JAN-19:01 | 0.00 | 54.18 | 80.30 | 0.35 | 0.00 | 0.09 | 0.48 | 25-JAN-19:01 |
February | 0.665836E+11 | 0.00 | 595.84 | 223861.49 | 12-FEB-09:03 | 0.00 | 54.50 | 77.21 | 0.24 | 0.00 | 0.06 | 0.51 | 12-FEB-09:03 |
March | 0.213846E+11 | 0.00 | 465.73 | 200243.14 | 23-MAR-08:02 | 0.00 | 54.62 | 70.21 | 0.08 | 0.00 | 0.02 | 0.46 | 23-MAR-08:02 |
April | 0.836295E+10 | 0.00 | 337.48 | 108487.67 | 06-APR-22:05 | 0.00 | 45.91 | 61.19 | 0.03 | 0.00 | 0.01 | 0.25 | 06-APR-22:05 |
May | 0.156495E+10 | 0.00 | 67.73 | 88352.35 | 11-MAY-06:02 | 0.00 | 49.31 | 52.56 | 0.00 | 0.00 | 0.00 | 0.20 | 11-MAY-06:02 |
June | 0.412372E+09 | 0.00 | 15.44 | 36165.73 | 09-JUN-08:05 | 0.00 | 50.22 | 51.01 | 0.00 | 0.00 | 0.00 | 0.08 | 09-JUN-08:05 |
July | 35100318.32 | 0.00 | 3.25 | 18581.63 | 28-JUL-15:05 | 0.00 | 61.42 | 61.49 | 0.00 | 0.00 | 0.00 | 0.04 | 28-JUL-15:05 |
August | 26026245.15 | 0.00 | 1.37 | 16058.92 | 25-AUG-08:05 | 0.00 | 64.59 | 64.62 | 0.00 | 0.00 | 0.00 | 0.04 | 25-AUG-08:05 |
September | 0.396066E+09 | 0.00 | 47.21 | 41724.88 | 15-SEP-08:03 | 0.00 | 58.19 | 59.44 | 0.00 | 0.00 | 0.00 | 0.10 | 15-SEP-08:03 |
October | 0.178823E+11 | 0.00 | 362.61 | 203632.69 | 25-OCT-08:61 | 0.00 | 52.77 | 65.73 | 0.06 | 0.00 | 0.02 | 0.47 | 25-OCT-08:61 |
November | 0.300090E+11 | 0.00 | 558.45 | 161893.31 | 22-NOV-19:03 | 0.00 | 59.48 | 75.90 | 0.12 | 0.00 | 0.03 | 0.37 | 22-NOV-19:03 |
December | 0.624388E+11 | 0.00 | 716.54 | 180991.54 | 22-DEC-19:01 | 0.00 | 55.11 | 79.39 | 0.23 | 0.00 | 0.05 | 0.42 | 22-DEC-19:01 |
Annual Sum or Average | 0.315145E+12 | 0.00 | 3907.23 | 0.00 | 55.05 | 66.55 | 0.09 | 0.00 | 0.02 | ||||
Minimum of Months | 26026245.15 | 0.00 | 1.37 | 16058.92 | 0.00 | 45.91 | 51.01 | 0.00 | 0.00 | 0.00 | 0.04 | ||
Maximum of Months | 0.106050E+12 | 0.00 | 735.58 | 223861.49 | 0.00 | 64.59 | 80.30 | 0.35 | 0.00 | 0.09 | 0.51 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.856553E+10 | 0.00 | 175.57 | 0.724078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 126977.00 | 19-JAN-21:00 | 92889.83 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.293440E+11 | 0.00 | 220.76 | 0.290339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153415.09 | 26-FEB-14:50 | 153415.09 | 26-FEB-14:50 | 0.00 | 0.00 | 0.00 |
March | 0.889674E+11 | 0.00 | 404.48 | 0.863600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 238677.08 | 30-MAR-18:05 | 231124.80 | 30-MAR-18:40 | 0.00 | 0.00 | 0.00 |
April | 0.187632E+12 | 0.00 | 527.86 | 0.163441E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 264903.03 | 04-APR-10:33 | 251743.71 | 15-APR-13:33 | 0.00 | 0.00 | 0.00 |
May | 0.371113E+12 | 0.00 | 690.02 | 0.271948E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 385224.23 | 30-MAY-21:10 | 289802.84 | 16-MAY-18:27 | 0.00 | 0.00 | 0.00 |
June | 0.614128E+12 | 0.00 | 704.28 | 0.395019E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 449776.27 | 22-JUN-20:30 | 268705.78 | 03-JUN-18:40 | 0.00 | 0.00 | 0.00 |
July | 0.800726E+12 | 0.00 | 744.00 | 0.450366E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 463954.09 | 26-JUL-22:40 | 281501.58 | 07-JUL-19:10 | 0.00 | 0.00 | 0.00 |
August | 0.864641E+12 | 0.00 | 744.00 | 0.478682E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 550314.01 | 23-AUG-21:00 | 286573.92 | 18-AUG-20:10 | 0.00 | 0.00 | 0.00 |
September | 0.531446E+12 | 0.00 | 699.08 | 0.331229E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 443011.79 | 27-SEP-18:03 | 253450.19 | 08-SEP-20:10 | 0.00 | 0.00 | 0.00 |
October | 0.203562E+12 | 0.00 | 463.03 | 0.137455E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 487642.06 | 18-OCT-21:00 | 217839.54 | 10-OCT-18:05 | 0.00 | 0.00 | 0.00 |
November | 0.678571E+11 | 0.00 | 334.47 | 0.554719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 245934.55 | 27-NOV-19:05 | 158468.56 | 05-NOV-16:00 | 0.00 | 0.00 | 0.00 |
December | 0.150454E+11 | 0.00 | 210.25 | 0.128715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 175771.21 | 13-DEC-11:40 | 122231.43 | 12-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378303E+13 | 0.00 | 5917.80 | 0.241912E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.856553E+10 | 0.00 | 175.57 | 0.724078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 126977.00 | 92889.83 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.864641E+12 | 0.00 | 744.00 | 0.478682E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 550314.01 | 289802.84 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.176252E+10 | 0.00 | 46.33 | 0.137197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23359.34 | 19-JAN-16:00 | 22284.96 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.552120E+10 | 0.00 | 130.72 | 0.546661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27394.32 | 28-FEB-15:00 | 27394.32 | 28-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.174097E+11 | 0.00 | 332.33 | 0.157248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42240.29 | 31-MAR-11:00 | 29870.13 | 30-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.353659E+11 | 0.00 | 498.42 | 0.289004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49920.11 | 04-APR-10:20 | 30476.97 | 16-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.702690E+11 | 0.00 | 686.67 | 0.480235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61735.64 | 23-MAY-14:00 | 32382.04 | 30-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.102265E+12 | 0.00 | 702.83 | 0.649232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71662.75 | 26-JUN-18:00 | 34790.95 | 06-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.128587E+12 | 0.00 | 744.00 | 0.723841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78472.77 | 26-JUL-07:20 | 36308.02 | 08-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.130771E+12 | 0.00 | 744.00 | 0.751358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77870.35 | 21-AUG-07:40 | 35278.04 | 01-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.917847E+11 | 0.00 | 699.00 | 0.565505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68652.23 | 28-SEP-12:20 | 33148.43 | 07-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.380799E+11 | 0.00 | 416.42 | 0.248282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73445.65 | 19-OCT-02:40 | 30735.54 | 10-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.147380E+11 | 0.00 | 246.33 | 0.110135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46083.55 | 19-NOV-24:00 | 27175.19 | 05-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.325392E+10 | 0.00 | 74.17 | 0.253842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35336.55 | 13-DEC-13:00 | 25608.46 | 12-DEC-14:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.639807E+12 | 0.00 | 5321.22 | 0.406861E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.176252E+10 | 0.00 | 46.33 | 0.137197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23359.34 | 22284.96 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.130771E+12 | 0.00 | 744.00 | 0.751358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78472.77 | 36308.02 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 72154832.25 | 0.00 | 22.53 | 67102294.79 | 0.00 | 0.00 | 0.00 | 0.00 | 11844.56 | 29-JAN-16:01 | 11844.56 | 29-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.501092E+09 | 0.00 | 101.38 | 0.485696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12727.58 | 26-FEB-16:02 | 12727.58 | 26-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.207386E+10 | 0.00 | 323.48 | 0.150706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13162.28 | 29-MAR-15:02 | 12673.09 | 13-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.391830E+10 | 0.00 | 504.00 | 0.246589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14062.63 | 04-APR-15:02 | 12869.44 | 10-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.636614E+10 | 0.00 | 636.94 | 0.367505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13859.76 | 28-MAY-08:62 | 12559.45 | 09-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.918022E+10 | 0.00 | 657.55 | 0.568499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15983.15 | 29-JUN-08:62 | 12565.04 | 26-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.106850E+11 | 0.00 | 683.14 | 0.659762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15961.22 | 23-JUL-08:62 | 12570.87 | 05-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.113913E+11 | 0.00 | 694.43 | 0.706438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15972.85 | 29-AUG-08:62 | 12571.41 | 22-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.715719E+10 | 0.00 | 622.29 | 0.404939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15675.68 | 17-SEP-08:62 | 12534.34 | 22-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.319390E+10 | 0.00 | 431.82 | 0.189426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15052.81 | 18-OCT-15:02 | 12436.56 | 13-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.892386E+09 | 0.00 | 211.66 | 0.640229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13354.32 | 19-NOV-16:02 | 12416.52 | 11-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.206467E+09 | 0.00 | 58.71 | 0.141236E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12222.71 | 12-DEC-16:02 | 12092.79 | 10-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.556379E+11 | 0.00 | 4947.94 | 0.342729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 72154832.25 | 0.00 | 22.53 | 67102294.79 | 0.00 | 0.00 | 0.00 | 0.00 | 11844.56 | 11844.56 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.113913E+11 | 0.00 | 694.43 | 0.706438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15983.15 | 12869.44 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 8795731.55 | 0.00 | 2.58 | 7000801.09 | 0.00 | 0.00 | 0.00 | 0.00 | 5101.67 | 19-JAN-19:04 | 4225.76 | 29-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.227134E+09 | 0.00 | 50.55 | 0.220822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12577.64 | 26-FEB-16:02 | 12577.64 | 26-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.136610E+10 | 0.00 | 251.45 | 0.924887E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13258.84 | 29-MAR-15:02 | 12422.83 | 13-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.329050E+10 | 0.00 | 463.73 | 0.197212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13822.10 | 04-APR-15:02 | 12718.17 | 10-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.606379E+10 | 0.00 | 618.85 | 0.347273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13883.10 | 23-MAY-15:02 | 12411.70 | 09-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.911916E+10 | 0.00 | 656.61 | 0.568158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15755.68 | 29-JUN-08:62 | 12346.77 | 02-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.105421E+11 | 0.00 | 683.58 | 0.651963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15927.95 | 23-JUL-08:62 | 12396.63 | 05-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.108146E+11 | 0.00 | 690.54 | 0.661194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15393.89 | 24-AUG-08:62 | 12419.13 | 16-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.622704E+10 | 0.00 | 593.95 | 0.334804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15499.22 | 17-SEP-08:62 | 12409.02 | 07-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.209916E+10 | 0.00 | 330.65 | 0.113824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14886.55 | 18-OCT-15:02 | 12286.28 | 13-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.352430E+09 | 0.00 | 112.91 | 0.212393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13501.55 | 05-NOV-15:02 | 12270.26 | 11-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 38825595.99 | 0.00 | 19.35 | 20792521.50 | 0.00 | 0.00 | 0.00 | 0.00 | 11136.02 | 11-DEC-16:02 | 10932.28 | 10-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.501497E+11 | 0.00 | 4474.74 | 0.301302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8795731.55 | 0.00 | 2.58 | 7000801.09 | 0.00 | 0.00 | 0.00 | 0.00 | 5101.67 | 4225.76 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.108146E+11 | 0.00 | 690.54 | 0.661194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15927.95 | 12718.17 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.153981E+09 | 0.00 | 6.97 | 0.153981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11869.75 | 29-JAN-15:30 | 11869.75 | 29-JAN-15:30 | 0.00 | 0.00 | 0.00 |
February | 0.254889E+10 | 0.00 | 73.97 | 0.254889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24299.70 | 26-FEB-14:50 | 24299.70 | 26-FEB-14:50 | 0.00 | 0.00 | 0.00 |
March | 0.568513E+10 | 0.00 | 175.04 | 0.413708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25288.89 | 30-MAR-13:40 | 21097.02 | 13-MAR-16:10 | 0.00 | 0.00 | 0.00 |
April | 0.807771E+10 | 0.00 | 264.33 | 0.445067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23017.06 | 15-APR-14:00 | 18964.95 | 15-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.116683E+11 | 0.00 | 380.13 | 0.457581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19423.06 | 06-MAY-13:30 | 10433.26 | 06-MAY-13:40 | 0.00 | 0.00 | 0.00 |
June | 0.241100E+11 | 0.00 | 573.36 | 0.107137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24373.23 | 25-JUN-08:00 | 14741.88 | 24-JUN-17:15 | 0.00 | 0.00 | 0.00 |
July | 0.312998E+11 | 0.00 | 650.43 | 0.146075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29454.75 | 13-JUL-21:00 | 19785.61 | 08-JUL-17:20 | 0.00 | 0.00 | 0.00 |
August | 0.398904E+11 | 0.00 | 729.69 | 0.207619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33708.05 | 19-AUG-13:40 | 28086.48 | 19-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.252646E+11 | 0.00 | 530.96 | 0.133684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37432.29 | 24-SEP-14:50 | 30652.90 | 24-SEP-12:00 | 0.00 | 0.00 | 0.00 |
October | 0.151589E+11 | 0.00 | 321.57 | 0.105504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37630.95 | 11-OCT-15:50 | 30398.89 | 10-OCT-12:00 | 0.00 | 0.00 | 0.00 |
November | 0.613173E+10 | 0.00 | 150.00 | 0.578961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28523.32 | 12-NOV-14:00 | 28523.32 | 12-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.235737E+10 | 0.00 | 65.54 | 0.203853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27187.69 | 10-DEC-14:20 | 27187.69 | 10-DEC-14:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172347E+12 | 0.00 | 3922.01 | 0.936965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.153981E+09 | 0.00 | 6.97 | 0.153981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11869.75 | 10433.26 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.398904E+11 | 0.00 | 729.69 | 0.207619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37630.95 | 30652.90 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.593221E+09 | 0.00 | 40.97 | 0.284930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52293.68 | 01-JAN-09:02 | 48066.84 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.306235E+10 | 0.00 | 159.55 | 0.215929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73668.17 | 18-FEB-09:03 | 69419.45 | 28-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.104793E+11 | 0.00 | 344.47 | 0.662781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76241.52 | 30-MAR-15:02 | 73525.15 | 30-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.241584E+11 | 0.00 | 467.51 | 0.143704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83025.40 | 21-APR-18:02 | 71677.84 | 18-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.421049E+11 | 0.00 | 525.36 | 0.246392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84766.15 | 28-MAY-18:02 | 74681.24 | 18-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.582592E+11 | 0.00 | 531.27 | 0.384010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98863.35 | 29-JUN-08:62 | 78567.87 | 10-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.669330E+11 | 0.00 | 564.73 | 0.431303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100437.37 | 23-JUL-08:62 | 74518.46 | 13-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.664676E+11 | 0.00 | 554.18 | 0.423226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96732.99 | 24-AUG-08:62 | 74660.69 | 25-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.422094E+11 | 0.00 | 504.68 | 0.233504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96775.07 | 17-SEP-08:62 | 73307.20 | 06-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.169080E+11 | 0.00 | 439.98 | 0.832514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85827.04 | 01-OCT-18:02 | 70257.71 | 10-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.592999E+10 | 0.00 | 239.86 | 0.294281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77613.74 | 27-NOV-19:03 | 64172.41 | 06-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.122335E+10 | 0.00 | 79.24 | 0.515030E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65842.40 | 24-DEC-09:02 | 52444.65 | 24-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.338329E+12 | 0.00 | 4451.80 | 0.207069E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.593221E+09 | 0.00 | 40.97 | 0.284930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52293.68 | 48066.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.669330E+11 | 0.00 | 564.73 | 0.431303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100437.37 | 78567.87 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 42686247.45 | 0.00 | 20.45 | 35971623.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9980.75 | 29-JAN-16:01 | 9980.75 | 29-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.537738E+09 | 0.00 | 108.72 | 0.520641E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11439.37 | 26-FEB-16:02 | 11439.37 | 26-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.176465E+10 | 0.00 | 340.68 | 0.123326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12093.47 | 29-MAR-15:02 | 11390.85 | 13-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.377355E+10 | 0.00 | 513.52 | 0.234145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12604.88 | 04-APR-15:02 | 11567.01 | 10-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.656250E+10 | 0.00 | 667.19 | 0.381013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12742.13 | 28-MAY-08:62 | 11288.31 | 09-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.940591E+10 | 0.00 | 687.42 | 0.587970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14127.10 | 23-JUN-08:62 | 11303.79 | 21-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.110831E+11 | 0.00 | 704.40 | 0.701049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14298.76 | 30-JUL-08:62 | 11276.03 | 04-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.115102E+11 | 0.00 | 712.13 | 0.729498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14012.30 | 24-AUG-08:62 | 11240.50 | 15-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.722929E+10 | 0.00 | 637.43 | 0.414342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14115.59 | 17-SEP-08:62 | 11298.90 | 11-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.313949E+10 | 0.00 | 455.62 | 0.183056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13538.51 | 18-OCT-15:02 | 11277.18 | 10-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.776826E+09 | 0.00 | 205.32 | 0.545884E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12301.63 | 05-NOV-15:02 | 11159.77 | 11-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.171408E+09 | 0.00 | 60.69 | 0.105991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10886.32 | 12-DEC-16:02 | 10469.27 | 10-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.559974E+11 | 0.00 | 5113.55 | 0.347525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 42686247.45 | 0.00 | 20.45 | 35971623.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9980.75 | 9980.75 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.115102E+11 | 0.00 | 712.13 | 0.729498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14298.76 | 11567.01 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 8212107.58 | 0.00 | 2.98 | 6498959.59 | 0.00 | 0.00 | 0.00 | 0.00 | 5391.16 | 19-JAN-19:04 | 3286.11 | 24-JAN-16:04 | 0.00 | 0.00 | 0.00 |
February | 0.235910E+09 | 0.00 | 58.63 | 0.223942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10909.34 | 28-FEB-16:02 | 10909.34 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.103946E+10 | 0.00 | 247.01 | 0.633076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11868.94 | 29-MAR-15:02 | 10963.36 | 30-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.311625E+10 | 0.00 | 474.24 | 0.185861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12419.60 | 04-APR-15:02 | 11463.86 | 10-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.623306E+10 | 0.00 | 656.74 | 0.358953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12658.65 | 28-MAY-08:62 | 11193.52 | 16-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.934123E+10 | 0.00 | 687.92 | 0.585638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14006.74 | 23-JUN-08:62 | 11190.09 | 09-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.109342E+11 | 0.00 | 704.29 | 0.689657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14171.16 | 30-JUL-08:62 | 11199.41 | 24-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.109205E+11 | 0.00 | 709.88 | 0.674658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13890.44 | 24-AUG-08:62 | 11172.08 | 17-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.626960E+10 | 0.00 | 628.14 | 0.342361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13996.77 | 17-SEP-08:62 | 11115.74 | 23-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.201023E+10 | 0.00 | 330.52 | 0.105399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13426.11 | 18-OCT-15:02 | 10726.86 | 10-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.246906E+09 | 0.00 | 102.91 | 0.121868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11707.96 | 05-NOV-15:02 | 9989.31 | 06-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 29487626.09 | 0.00 | 15.99 | 13778627.97 | 0.00 | 0.00 | 0.00 | 0.00 | 5267.42 | 12-DEC-16:02 | 3988.35 | 11-DEC-09:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.503850E+11 | 0.00 | 4619.25 | 0.304244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8212107.58 | 0.00 | 2.98 | 6498959.59 | 0.00 | 0.00 | 0.00 | 0.00 | 5267.42 | 3286.11 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.109342E+11 | 0.00 | 709.88 | 0.689657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14171.16 | 11463.86 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 13064503.11 | 0.00 | 13.83 | 12256847.28 | 0.00 | 0.00 | 0.00 | 0.00 | 3093.88 | 29-JAN-16:01 | 3093.88 | 29-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.107288E+09 | 0.00 | 71.53 | 0.105557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3343.50 | 26-FEB-16:02 | 3343.50 | 26-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.456704E+09 | 0.00 | 267.32 | 0.335114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3445.38 | 29-MAR-15:02 | 3329.20 | 13-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.903451E+09 | 0.00 | 441.61 | 0.581472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3726.13 | 21-APR-18:02 | 3380.69 | 10-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.153915E+10 | 0.00 | 615.20 | 0.889767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3780.04 | 28-MAY-08:62 | 3299.35 | 09-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.229437E+10 | 0.00 | 656.92 | 0.138626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4336.36 | 29-JUN-08:62 | 3299.66 | 28-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.270496E+10 | 0.00 | 679.75 | 0.165526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4382.04 | 30-JUL-08:62 | 3291.97 | 30-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.288477E+10 | 0.00 | 691.73 | 0.176134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4353.75 | 29-AUG-08:62 | 3295.33 | 04-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.168677E+10 | 0.00 | 598.13 | 0.935835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4311.72 | 17-SEP-08:62 | 3302.26 | 06-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.695882E+09 | 0.00 | 344.57 | 0.421512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3960.29 | 18-OCT-15:02 | 3266.93 | 13-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.177174E+09 | 0.00 | 142.63 | 0.131724E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3498.23 | 19-NOV-16:02 | 3261.80 | 11-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 37237538.82 | 0.00 | 37.31 | 27331989.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3227.91 | 12-DEC-16:02 | 3176.76 | 10-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135008E+11 | 0.00 | 4560.54 | 0.824343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 13064503.11 | 0.00 | 13.83 | 12256847.28 | 0.00 | 0.00 | 0.00 | 0.00 | 3093.88 | 3093.88 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.288477E+10 | 0.00 | 691.73 | 0.176134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4382.04 | 3380.69 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2950383.74 | 0.00 | 1.60 | 2403511.54 | 0.00 | 0.00 | 0.00 | 0.00 | 1493.28 | 19-JAN-19:04 | 1416.17 | 25-JAN-16:03 | 0.00 | 0.00 | 0.00 |
February | 48357845.15 | 0.00 | 35.75 | 47192772.29 | 0.00 | 0.00 | 0.00 | 0.00 | 3299.65 | 26-FEB-16:02 | 3299.65 | 26-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.286593E+09 | 0.00 | 193.24 | 0.195135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3478.46 | 29-MAR-15:02 | 3234.91 | 13-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.741791E+09 | 0.00 | 399.42 | 0.460627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3642.84 | 21-APR-18:02 | 3336.52 | 10-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.145758E+10 | 0.00 | 600.01 | 0.837949E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3736.95 | 28-MAY-08:62 | 3256.14 | 09-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.227778E+10 | 0.00 | 655.72 | 0.138115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4285.41 | 29-JUN-08:62 | 3240.68 | 23-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.266778E+10 | 0.00 | 680.13 | 0.163222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4369.11 | 23-JUL-08:62 | 3254.35 | 30-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.273306E+10 | 0.00 | 688.33 | 0.163384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4213.23 | 12-AUG-08:62 | 3258.80 | 07-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.143836E+10 | 0.00 | 570.66 | 0.753893E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4257.65 | 17-SEP-08:62 | 3259.71 | 15-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.437665E+09 | 0.00 | 247.32 | 0.243293E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3911.63 | 18-OCT-15:02 | 3191.84 | 12-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 62574977.23 | 0.00 | 66.19 | 39613090.18 | 0.00 | 0.00 | 0.00 | 0.00 | 3553.41 | 05-NOV-15:02 | 3218.48 | 11-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 6635476.29 | 0.00 | 10.25 | 4329182.20 | 0.00 | 0.00 | 0.00 | 0.00 | 2219.30 | 11-DEC-16:02 | 1805.82 | 11-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121611E+11 | 0.00 | 4148.62 | 0.723165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2950383.74 | 0.00 | 1.60 | 2403511.54 | 0.00 | 0.00 | 0.00 | 0.00 | 1493.28 | 1416.17 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.273306E+10 | 0.00 | 688.33 | 0.163384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4369.11 | 3336.52 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.802700E+09 | 0.00 | 114.43 | 0.758064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13969.49 | 29-JAN-16:01 | 13969.49 | 29-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.161011E+10 | 0.00 | 181.41 | 0.155264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15009.41 | 26-FEB-16:02 | 15009.41 | 26-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.383565E+10 | 0.00 | 415.06 | 0.294313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15437.69 | 29-MAR-15:02 | 14945.36 | 13-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.522361E+10 | 0.00 | 499.03 | 0.333147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16871.70 | 21-APR-18:02 | 14651.25 | 09-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.764970E+10 | 0.00 | 619.28 | 0.426485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17070.28 | 28-MAY-18:02 | 14791.68 | 16-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.108127E+11 | 0.00 | 645.95 | 0.645559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19907.56 | 29-JUN-08:62 | 14821.89 | 25-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.130887E+11 | 0.00 | 671.02 | 0.792589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19847.81 | 23-JUL-08:62 | 14798.66 | 04-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.147792E+11 | 0.00 | 684.89 | 0.942110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19719.14 | 29-AUG-08:62 | 14830.15 | 10-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.102269E+11 | 0.00 | 617.95 | 0.618360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19459.98 | 17-SEP-08:62 | 14599.88 | 17-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.634073E+10 | 0.00 | 504.87 | 0.429420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17252.04 | 18-OCT-15:02 | 14666.39 | 13-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.345081E+10 | 0.00 | 378.74 | 0.275000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15940.74 | 27-NOV-19:03 | 14642.82 | 11-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.173393E+10 | 0.00 | 205.33 | 0.147682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14460.26 | 13-DEC-16:03 | 14261.91 | 10-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.795547E+11 | 0.00 | 5537.97 | 0.513574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.802700E+09 | 0.00 | 114.43 | 0.758064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13969.49 | 13969.49 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.147792E+11 | 0.00 | 684.89 | 0.942110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19907.56 | 15009.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 527.26 | 366.27 | 160.99 | 595.59 | 607.53 | 0.00 | 0.00 | 0.00 |
February | 491.15 | 327.66 | 163.48 | 605.86 | 505.79 | 0.00 | 0.00 | 0.00 |
March | 449.12 | 235.68 | 213.44 | 619.31 | 326.48 | 0.00 | 0.00 | 0.00 |
April | 338.00 | 112.77 | 225.23 | 527.85 | 257.89 | 0.00 | 0.00 | 0.00 |
May | 271.69 | 33.25 | 238.45 | 457.37 | 160.74 | 0.00 | 0.00 | 0.00 |
June | 249.47 | 13.93 | 235.54 | 490.51 | 97.79 | 0.00 | 0.00 | 0.00 |
July | 250.25 | 16.88 | 233.37 | 516.85 | 62.41 | 0.00 | 0.00 | 0.00 |
August | 301.54 | 56.67 | 244.87 | 622.49 | 51.34 | 0.00 | 0.00 | 0.00 |
September | 340.43 | 132.46 | 207.97 | 600.53 | 129.68 | 0.00 | 0.00 | 0.00 |
October | 478.03 | 308.97 | 169.06 | 719.80 | 292.36 | 0.00 | 0.00 | 0.00 |
November | 522.27 | 348.52 | 173.76 | 704.22 | 394.01 | 0.00 | 0.00 | 0.00 |
December | 523.54 | 368.30 | 155.25 | 635.78 | 504.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 394.80 | 192.80 | 202.00 | 591.34 | 281.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 249.47 | 13.93 | 155.25 | 457.37 | 51.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 527.26 | 368.30 | 244.87 | 719.80 | 607.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1484.72 | 1031.40 | 453.32 | 1639.67 | 1809.59 | 0.00 | 0.00 | 0.00 |
February | 1383.03 | 922.68 | 460.35 | 1667.81 | 1535.83 | 0.00 | 0.00 | 0.00 |
March | 1264.70 | 663.66 | 601.04 | 1697.97 | 1030.33 | 0.00 | 0.00 | 0.00 |
April | 951.78 | 317.55 | 634.23 | 1444.30 | 815.71 | 0.00 | 0.00 | 0.00 |
May | 765.07 | 93.63 | 671.45 | 1250.61 | 518.11 | 0.00 | 0.00 | 0.00 |
June | 702.49 | 39.22 | 663.27 | 1364.18 | 302.70 | 0.00 | 0.00 | 0.00 |
July | 704.68 | 47.53 | 657.15 | 1442.64 | 195.56 | 0.00 | 0.00 | 0.00 |
August | 849.11 | 159.58 | 689.52 | 1743.63 | 156.07 | 0.00 | 0.00 | 0.00 |
September | 958.64 | 373.00 | 585.64 | 1665.25 | 414.75 | 0.00 | 0.00 | 0.00 |
October | 1346.11 | 870.05 | 476.06 | 1989.33 | 922.48 | 0.00 | 0.00 | 0.00 |
November | 1470.69 | 981.40 | 489.29 | 1935.64 | 1232.64 | 0.00 | 0.00 | 0.00 |
December | 1474.27 | 1037.10 | 437.17 | 1749.28 | 1536.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1111.73 | 542.91 | 568.82 | 1632.57 | 869.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 702.49 | 39.22 | 437.17 | 1250.61 | 156.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1484.72 | 1037.10 | 689.52 | 1989.33 | 1809.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1928.74 | 1339.84 | 588.89 | 2168.74 | 2456.99 | 0.00 | 0.00 | 0.00 |
February | 1796.64 | 1198.62 | 598.02 | 2210.99 | 2080.97 | 0.00 | 0.00 | 0.00 |
March | 1642.92 | 862.13 | 780.79 | 2255.45 | 1382.92 | 0.00 | 0.00 | 0.00 |
April | 1236.41 | 412.51 | 823.90 | 1917.69 | 1097.32 | 0.00 | 0.00 | 0.00 |
May | 993.87 | 121.63 | 872.25 | 1663.94 | 691.29 | 0.00 | 0.00 | 0.00 |
June | 912.57 | 50.95 | 861.62 | 1822.23 | 397.71 | 0.00 | 0.00 | 0.00 |
July | 915.42 | 61.75 | 853.67 | 1930.83 | 254.17 | 0.00 | 0.00 | 0.00 |
August | 1103.04 | 207.31 | 895.73 | 2334.79 | 197.00 | 0.00 | 0.00 | 0.00 |
September | 1245.33 | 484.54 | 760.78 | 2214.13 | 547.44 | 0.00 | 0.00 | 0.00 |
October | 1748.68 | 1130.24 | 618.43 | 2640.68 | 1237.82 | 0.00 | 0.00 | 0.00 |
November | 1910.51 | 1274.89 | 635.62 | 2561.90 | 1660.87 | 0.00 | 0.00 | 0.00 |
December | 1915.16 | 1347.25 | 567.91 | 2312.94 | 2088.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1444.20 | 705.27 | 738.93 | 2169.63 | 1169.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 912.57 | 50.95 | 567.91 | 1663.94 | 197.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1928.74 | 1347.25 | 895.73 | 2640.68 | 2456.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.25 | 72.42 | 31.83 | 119.11 | 122.13 | 0.00 | 0.00 | 0.00 |
February | 97.11 | 64.78 | 32.32 | 121.00 | 100.51 | 0.00 | 0.00 | 0.00 |
March | 88.80 | 46.60 | 42.20 | 123.45 | 62.25 | 0.00 | 0.00 | 0.00 |
April | 66.83 | 22.30 | 44.53 | 105.51 | 48.06 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 6.57 | 47.15 | 93.17 | 26.65 | 0.00 | 0.00 | 0.00 |
June | 49.32 | 2.75 | 46.57 | 104.95 | 12.51 | 0.00 | 0.00 | 0.00 |
July | 49.48 | 3.34 | 46.14 | 112.33 | 6.00 | 0.00 | 0.00 | 0.00 |
August | 59.62 | 11.20 | 48.41 | 134.59 | 3.07 | 0.00 | 0.00 | 0.00 |
September | 67.31 | 26.19 | 41.12 | 124.31 | 18.35 | 0.00 | 0.00 | 0.00 |
October | 94.52 | 61.09 | 33.43 | 145.26 | 53.33 | 0.00 | 0.00 | 0.00 |
November | 103.26 | 68.91 | 34.36 | 141.45 | 75.89 | 0.00 | 0.00 | 0.00 |
December | 103.51 | 72.82 | 30.70 | 127.63 | 99.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.06 | 38.12 | 39.94 | 121.09 | 52.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.32 | 2.75 | 30.70 | 93.17 | 3.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.25 | 72.82 | 48.41 | 145.26 | 122.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.12 | 38.65 | 44.47 | 63.68 | 258.09 | 0.00 | 0.00 | 0.00 |
February | 95.23 | 44.63 | 50.60 | 96.61 | 208.78 | 0.00 | 0.00 | 0.00 |
March | 139.71 | 67.38 | 72.33 | 178.15 | 120.71 | 0.00 | 0.00 | 0.00 |
April | 157.43 | 72.01 | 85.43 | 235.71 | 88.49 | 0.00 | 0.00 | 0.00 |
May | 158.41 | 60.12 | 98.28 | 265.61 | 49.31 | 0.00 | 0.00 | 0.00 |
June | 166.42 | 64.08 | 102.34 | 320.09 | 23.19 | 0.00 | 0.00 | 0.00 |
July | 156.65 | 57.94 | 98.71 | 317.41 | 11.09 | 0.00 | 0.00 | 0.00 |
August | 153.87 | 57.55 | 96.32 | 313.76 | 5.71 | 0.00 | 0.00 | 0.00 |
September | 125.70 | 52.55 | 73.15 | 219.88 | 34.37 | 0.00 | 0.00 | 0.00 |
October | 111.85 | 58.15 | 53.69 | 158.96 | 105.17 | 0.00 | 0.00 | 0.00 |
November | 88.83 | 39.72 | 49.11 | 102.09 | 156.59 | 0.00 | 0.00 | 0.00 |
December | 73.57 | 32.23 | 41.35 | 62.39 | 210.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.06 | 53.79 | 72.27 | 195.06 | 105.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.57 | 32.23 | 41.35 | 62.39 | 5.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.42 | 72.01 | 102.34 | 320.09 | 258.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 0.00 | 19.63 | 2.95 | 146.03 | 0.00 | 0.00 | 0.00 |
February | 21.76 | 0.00 | 21.76 | 10.32 | 116.30 | 0.00 | 0.00 | 0.00 |
March | 30.56 | 0.00 | 30.56 | 23.97 | 65.52 | 0.00 | 0.00 | 0.00 |
April | 37.06 | 0.22 | 36.84 | 46.24 | 47.13 | 0.00 | 0.00 | 0.00 |
May | 44.21 | 1.39 | 42.83 | 70.86 | 24.98 | 0.00 | 0.00 | 0.00 |
June | 48.63 | 3.19 | 45.44 | 101.61 | 11.59 | 0.00 | 0.00 | 0.00 |
July | 46.05 | 2.36 | 43.69 | 104.09 | 5.80 | 0.00 | 0.00 | 0.00 |
August | 40.90 | 0.48 | 40.42 | 95.81 | 2.97 | 0.00 | 0.00 | 0.00 |
September | 30.88 | 0.01 | 30.86 | 55.24 | 18.17 | 0.00 | 0.00 | 0.00 |
October | 23.46 | 0.00 | 23.46 | 25.02 | 56.01 | 0.00 | 0.00 | 0.00 |
November | 21.00 | 0.00 | 21.00 | 13.30 | 83.90 | 0.00 | 0.00 | 0.00 |
December | 18.15 | 0.00 | 18.15 | 3.85 | 115.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.91 | 0.64 | 31.27 | 46.31 | 57.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.15 | 0.00 | 18.15 | 2.95 | 2.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.63 | 3.19 | 45.44 | 104.09 | 146.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.12 | 38.65 | 44.47 | 67.13 | 254.03 | 0.00 | 0.00 | 0.00 |
February | 95.23 | 44.63 | 50.60 | 100.41 | 205.44 | 0.00 | 0.00 | 0.00 |
March | 139.71 | 67.38 | 72.33 | 182.43 | 118.33 | 0.00 | 0.00 | 0.00 |
April | 157.43 | 72.01 | 85.43 | 238.13 | 87.59 | 0.00 | 0.00 | 0.00 |
May | 158.41 | 60.12 | 98.28 | 266.41 | 49.05 | 0.00 | 0.00 | 0.00 |
June | 166.42 | 64.08 | 102.34 | 320.20 | 23.16 | 0.00 | 0.00 | 0.00 |
July | 156.65 | 57.94 | 98.71 | 317.65 | 11.03 | 0.00 | 0.00 | 0.00 |
August | 153.87 | 57.55 | 96.32 | 314.89 | 5.55 | 0.00 | 0.00 | 0.00 |
September | 125.70 | 52.55 | 73.15 | 221.95 | 33.67 | 0.00 | 0.00 | 0.00 |
October | 111.85 | 58.15 | 53.69 | 163.41 | 102.78 | 0.00 | 0.00 | 0.00 |
November | 88.83 | 39.72 | 49.11 | 107.15 | 152.80 | 0.00 | 0.00 | 0.00 |
December | 73.57 | 32.23 | 41.35 | 66.68 | 206.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.06 | 53.79 | 72.27 | 197.73 | 103.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.57 | 32.23 | 41.35 | 66.68 | 5.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.42 | 72.01 | 102.34 | 320.20 | 254.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.38 | 57.92 | 25.46 | 94.04 | 96.10 | 0.00 | 0.00 | 0.00 |
February | 77.67 | 51.82 | 25.85 | 95.17 | 81.04 | 0.00 | 0.00 | 0.00 |
March | 71.03 | 37.27 | 33.75 | 95.38 | 56.65 | 0.00 | 0.00 | 0.00 |
April | 53.45 | 17.83 | 35.62 | 81.85 | 44.67 | 0.00 | 0.00 | 0.00 |
May | 42.97 | 5.26 | 37.71 | 72.15 | 27.01 | 0.00 | 0.00 | 0.00 |
June | 39.45 | 2.20 | 37.25 | 81.15 | 14.30 | 0.00 | 0.00 | 0.00 |
July | 39.57 | 2.67 | 36.91 | 86.52 | 8.35 | 0.00 | 0.00 | 0.00 |
August | 47.69 | 8.96 | 38.72 | 103.89 | 5.76 | 0.00 | 0.00 | 0.00 |
September | 53.84 | 20.95 | 32.89 | 96.36 | 20.52 | 0.00 | 0.00 | 0.00 |
October | 75.60 | 48.86 | 26.74 | 112.78 | 50.29 | 0.00 | 0.00 | 0.00 |
November | 82.59 | 55.11 | 27.48 | 108.79 | 69.30 | 0.00 | 0.00 | 0.00 |
December | 82.79 | 58.24 | 24.55 | 99.00 | 83.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.43 | 30.49 | 31.95 | 93.93 | 46.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.45 | 2.20 | 24.55 | 72.15 | 5.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.38 | 58.24 | 38.72 | 112.78 | 96.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.71 | 0.00 | 15.71 | 2.15 | 122.04 | 0.00 | 0.00 | 0.00 |
February | 17.41 | 0.00 | 17.41 | 8.30 | 96.58 | 0.00 | 0.00 | 0.00 |
March | 24.45 | 0.00 | 24.45 | 20.39 | 52.44 | 0.00 | 0.00 | 0.00 |
April | 29.65 | 0.17 | 29.48 | 39.81 | 36.61 | 0.00 | 0.00 | 0.00 |
May | 35.37 | 1.11 | 34.27 | 60.67 | 18.56 | 0.00 | 0.00 | 0.00 |
June | 38.91 | 2.55 | 36.35 | 86.43 | 7.86 | 0.00 | 0.00 | 0.00 |
July | 36.85 | 1.89 | 34.96 | 88.76 | 3.54 | 0.00 | 0.00 | 0.00 |
August | 32.73 | 0.38 | 32.34 | 82.78 | 1.52 | 0.00 | 0.00 | 0.00 |
September | 24.70 | 0.01 | 24.69 | 48.31 | 13.11 | 0.00 | 0.00 | 0.00 |
October | 18.77 | 0.00 | 18.77 | 21.66 | 44.58 | 0.00 | 0.00 | 0.00 |
November | 16.80 | 0.00 | 16.80 | 10.87 | 68.81 | 0.00 | 0.00 | 0.00 |
December | 14.52 | 0.00 | 14.52 | 2.70 | 96.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.53 | 0.51 | 25.02 | 39.58 | 46.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.52 | 0.00 | 14.52 | 2.15 | 1.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.91 | 2.55 | 36.35 | 88.76 | 122.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.12 | 36.93 | 44.18 | 53.45 | 250.39 | 0.00 | 0.00 | 0.00 |
February | 101.81 | 54.80 | 47.00 | 96.20 | 197.31 | 0.00 | 0.00 | 0.00 |
March | 128.09 | 58.43 | 69.66 | 149.39 | 111.97 | 0.00 | 0.00 | 0.00 |
April | 154.84 | 70.67 | 84.16 | 224.20 | 81.54 | 0.00 | 0.00 | 0.00 |
May | 169.62 | 71.73 | 97.89 | 279.33 | 45.40 | 0.00 | 0.00 | 0.00 |
June | 175.44 | 73.48 | 101.96 | 333.25 | 21.05 | 0.00 | 0.00 | 0.00 |
July | 171.00 | 71.74 | 99.26 | 340.46 | 10.64 | 0.00 | 0.00 | 0.00 |
August | 156.73 | 62.17 | 94.56 | 319.06 | 5.36 | 0.00 | 0.00 | 0.00 |
September | 128.45 | 56.76 | 71.69 | 223.28 | 32.67 | 0.00 | 0.00 | 0.00 |
October | 109.86 | 57.18 | 52.68 | 147.72 | 97.96 | 0.00 | 0.00 | 0.00 |
November | 87.50 | 39.47 | 48.03 | 87.74 | 144.22 | 0.00 | 0.00 | 0.00 |
December | 75.93 | 34.56 | 41.37 | 53.98 | 198.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.49 | 57.32 | 71.17 | 192.86 | 99.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.93 | 34.56 | 41.37 | 53.45 | 5.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 175.44 | 73.48 | 101.96 | 340.46 | 250.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.25 | 72.42 | 31.83 | 118.54 | 121.84 | 0.00 | 0.00 | 0.00 |
February | 97.11 | 64.78 | 32.32 | 119.94 | 100.32 | 0.00 | 0.00 | 0.00 |
March | 88.80 | 46.60 | 42.20 | 122.40 | 61.75 | 0.00 | 0.00 | 0.00 |
April | 66.83 | 22.30 | 44.53 | 104.41 | 47.74 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 6.57 | 47.15 | 92.11 | 26.48 | 0.00 | 0.00 | 0.00 |
June | 49.32 | 2.75 | 46.57 | 104.06 | 12.34 | 0.00 | 0.00 | 0.00 |
July | 49.48 | 3.34 | 46.14 | 111.59 | 5.91 | 0.00 | 0.00 | 0.00 |
August | 59.62 | 11.20 | 48.41 | 134.22 | 2.96 | 0.00 | 0.00 | 0.00 |
September | 67.31 | 26.19 | 41.12 | 123.75 | 18.14 | 0.00 | 0.00 | 0.00 |
October | 94.52 | 61.09 | 33.43 | 144.37 | 52.94 | 0.00 | 0.00 | 0.00 |
November | 103.26 | 68.91 | 34.36 | 140.79 | 75.56 | 0.00 | 0.00 | 0.00 |
December | 103.51 | 72.82 | 30.70 | 127.06 | 99.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.06 | 38.12 | 39.94 | 120.30 | 51.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.32 | 2.75 | 30.70 | 92.11 | 2.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.25 | 72.82 | 48.41 | 144.37 | 121.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 0.00 | 19.63 | 2.81 | 146.05 | 0.00 | 0.00 | 0.00 |
February | 21.76 | 0.00 | 21.76 | 9.87 | 116.63 | 0.00 | 0.00 | 0.00 |
March | 30.56 | 0.00 | 30.56 | 23.35 | 65.39 | 0.00 | 0.00 | 0.00 |
April | 37.06 | 0.22 | 36.84 | 45.09 | 46.96 | 0.00 | 0.00 | 0.00 |
May | 44.21 | 1.39 | 42.83 | 69.66 | 24.80 | 0.00 | 0.00 | 0.00 |
June | 48.63 | 3.19 | 45.44 | 100.67 | 11.38 | 0.00 | 0.00 | 0.00 |
July | 46.05 | 2.36 | 43.69 | 103.34 | 5.72 | 0.00 | 0.00 | 0.00 |
August | 40.90 | 0.48 | 40.42 | 95.39 | 2.86 | 0.00 | 0.00 | 0.00 |
September | 30.88 | 0.01 | 30.86 | 54.53 | 18.02 | 0.00 | 0.00 | 0.00 |
October | 23.46 | 0.00 | 23.46 | 24.12 | 55.88 | 0.00 | 0.00 | 0.00 |
November | 21.00 | 0.00 | 21.00 | 13.05 | 83.73 | 0.00 | 0.00 | 0.00 |
December | 18.15 | 0.00 | 18.15 | 3.68 | 115.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.91 | 0.64 | 31.27 | 45.67 | 57.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.15 | 0.00 | 18.15 | 2.81 | 2.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.63 | 3.19 | 45.44 | 103.34 | 146.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.12 | 36.93 | 44.18 | 55.42 | 244.66 | 0.00 | 0.00 | 0.00 |
February | 101.81 | 54.80 | 47.00 | 99.55 | 193.41 | 0.00 | 0.00 | 0.00 |
March | 128.09 | 58.43 | 69.66 | 153.59 | 109.47 | 0.00 | 0.00 | 0.00 |
April | 154.84 | 70.67 | 84.16 | 226.26 | 80.63 | 0.00 | 0.00 | 0.00 |
May | 169.62 | 71.73 | 97.89 | 279.98 | 45.15 | 0.00 | 0.00 | 0.00 |
June | 175.44 | 73.48 | 101.96 | 333.37 | 21.02 | 0.00 | 0.00 | 0.00 |
July | 171.00 | 71.74 | 99.26 | 340.72 | 10.59 | 0.00 | 0.00 | 0.00 |
August | 156.73 | 62.17 | 94.56 | 320.16 | 5.21 | 0.00 | 0.00 | 0.00 |
September | 128.45 | 56.76 | 71.69 | 225.09 | 32.02 | 0.00 | 0.00 | 0.00 |
October | 109.86 | 57.18 | 52.68 | 151.74 | 95.59 | 0.00 | 0.00 | 0.00 |
November | 87.50 | 39.47 | 48.03 | 92.67 | 139.93 | 0.00 | 0.00 | 0.00 |
December | 75.93 | 34.56 | 41.37 | 57.04 | 192.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.49 | 57.32 | 71.17 | 195.14 | 97.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.93 | 34.56 | 41.37 | 55.42 | 5.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 175.44 | 73.48 | 101.96 | 340.72 | 244.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.87 | 0.00 | 24.87 | 3.09 | 201.50 | 0.00 | 0.00 | 0.00 |
February | 27.56 | 0.00 | 27.56 | 11.84 | 160.55 | 0.00 | 0.00 | 0.00 |
March | 38.70 | 0.00 | 38.70 | 28.74 | 92.28 | 0.00 | 0.00 | 0.00 |
April | 46.93 | 0.27 | 46.65 | 57.23 | 68.55 | 0.00 | 0.00 | 0.00 |
May | 55.99 | 1.76 | 54.24 | 87.92 | 39.76 | 0.00 | 0.00 | 0.00 |
June | 61.58 | 4.04 | 57.54 | 123.40 | 22.19 | 0.00 | 0.00 | 0.00 |
July | 58.32 | 2.99 | 55.33 | 124.63 | 14.00 | 0.00 | 0.00 | 0.00 |
August | 51.80 | 0.61 | 51.19 | 113.39 | 10.29 | 0.00 | 0.00 | 0.00 |
September | 39.10 | 0.02 | 39.09 | 65.66 | 33.21 | 0.00 | 0.00 | 0.00 |
October | 29.71 | 0.00 | 29.71 | 29.03 | 82.65 | 0.00 | 0.00 | 0.00 |
November | 26.59 | 0.00 | 26.59 | 14.84 | 117.42 | 0.00 | 0.00 | 0.00 |
December | 22.99 | 0.00 | 22.99 | 3.38 | 160.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.42 | 0.81 | 39.60 | 55.51 | 83.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.99 | 0.00 | 22.99 | 3.09 | 10.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.58 | 4.04 | 57.54 | 124.63 | 201.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.17 | 0.00 | 9.17 | 1.14 | 74.28 | 0.00 | 0.00 | 0.00 |
February | 10.16 | 0.00 | 10.16 | 4.37 | 59.19 | 0.00 | 0.00 | 0.00 |
March | 14.27 | 0.00 | 14.27 | 10.60 | 34.02 | 0.00 | 0.00 | 0.00 |
April | 17.30 | 0.10 | 17.20 | 21.10 | 25.27 | 0.00 | 0.00 | 0.00 |
May | 20.64 | 0.65 | 19.99 | 32.41 | 14.66 | 0.00 | 0.00 | 0.00 |
June | 22.70 | 1.49 | 21.21 | 45.49 | 8.18 | 0.00 | 0.00 | 0.00 |
July | 21.50 | 1.10 | 20.40 | 45.94 | 5.16 | 0.00 | 0.00 | 0.00 |
August | 19.10 | 0.22 | 18.87 | 41.80 | 3.79 | 0.00 | 0.00 | 0.00 |
September | 14.41 | 0.01 | 14.41 | 24.21 | 12.24 | 0.00 | 0.00 | 0.00 |
October | 10.95 | 0.00 | 10.95 | 10.70 | 30.47 | 0.00 | 0.00 | 0.00 |
November | 9.80 | 0.00 | 9.80 | 5.47 | 43.29 | 0.00 | 0.00 | 0.00 |
December | 8.47 | 0.00 | 8.47 | 1.24 | 59.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14.90 | 0.30 | 14.60 | 20.46 | 30.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.47 | 0.00 | 8.47 | 1.14 | 3.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.70 | 1.49 | 21.21 | 45.94 | 74.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 48.64 | 33.79 | 14.85 | 54.66 | 60.38 | 0.00 | 0.00 | 0.00 |
February | 45.31 | 30.23 | 15.08 | 55.97 | 49.94 | 0.00 | 0.00 | 0.00 |
March | 41.43 | 21.74 | 19.69 | 57.71 | 31.62 | 0.00 | 0.00 | 0.00 |
April | 31.18 | 10.40 | 20.78 | 49.21 | 25.42 | 0.00 | 0.00 | 0.00 |
May | 25.07 | 3.07 | 22.00 | 43.14 | 15.53 | 0.00 | 0.00 | 0.00 |
June | 23.01 | 1.28 | 21.73 | 47.28 | 8.84 | 0.00 | 0.00 | 0.00 |
July | 23.09 | 1.56 | 21.53 | 49.99 | 5.42 | 0.00 | 0.00 | 0.00 |
August | 27.82 | 5.23 | 22.59 | 60.16 | 3.88 | 0.00 | 0.00 | 0.00 |
September | 31.41 | 12.22 | 19.19 | 56.80 | 12.13 | 0.00 | 0.00 | 0.00 |
October | 44.10 | 28.50 | 15.60 | 67.50 | 28.29 | 0.00 | 0.00 | 0.00 |
November | 48.18 | 32.15 | 16.03 | 66.00 | 37.98 | 0.00 | 0.00 | 0.00 |
December | 48.30 | 33.98 | 14.32 | 58.94 | 49.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.42 | 17.79 | 18.64 | 55.62 | 27.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.01 | 1.28 | 14.32 | 43.14 | 3.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.64 | 33.98 | 22.59 | 67.50 | 60.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.02 | 91.71 | 40.31 | 148.36 | 163.89 | 0.00 | 0.00 | 0.00 |
February | 122.98 | 82.05 | 40.94 | 151.91 | 135.55 | 0.00 | 0.00 | 0.00 |
March | 112.46 | 59.01 | 53.45 | 156.64 | 85.82 | 0.00 | 0.00 | 0.00 |
April | 84.63 | 28.24 | 56.40 | 133.56 | 68.99 | 0.00 | 0.00 | 0.00 |
May | 68.03 | 8.33 | 59.71 | 117.09 | 42.15 | 0.00 | 0.00 | 0.00 |
June | 62.47 | 3.49 | 58.98 | 128.32 | 23.99 | 0.00 | 0.00 | 0.00 |
July | 62.66 | 4.23 | 58.43 | 135.69 | 14.72 | 0.00 | 0.00 | 0.00 |
August | 75.50 | 14.19 | 61.31 | 163.30 | 10.53 | 0.00 | 0.00 | 0.00 |
September | 85.24 | 33.17 | 52.08 | 154.17 | 32.92 | 0.00 | 0.00 | 0.00 |
October | 119.70 | 77.37 | 42.33 | 183.22 | 76.78 | 0.00 | 0.00 | 0.00 |
November | 130.78 | 87.27 | 43.51 | 179.15 | 103.08 | 0.00 | 0.00 | 0.00 |
December | 131.09 | 92.22 | 38.87 | 159.97 | 133.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.86 | 48.28 | 50.58 | 150.96 | 74.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.47 | 3.49 | 38.87 | 117.09 | 10.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.02 | 92.22 | 61.31 | 183.22 | 163.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.25 | 72.42 | 31.83 | 118.70 | 121.49 | 0.00 | 0.00 | 0.00 |
February | 97.11 | 64.78 | 32.32 | 120.39 | 99.78 | 0.00 | 0.00 | 0.00 |
March | 88.80 | 46.60 | 42.20 | 122.64 | 61.26 | 0.00 | 0.00 | 0.00 |
April | 66.83 | 22.30 | 44.53 | 104.70 | 47.27 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 6.57 | 47.15 | 92.24 | 26.05 | 0.00 | 0.00 | 0.00 |
June | 49.32 | 2.75 | 46.57 | 104.45 | 11.92 | 0.00 | 0.00 | 0.00 |
July | 49.48 | 3.34 | 46.14 | 111.86 | 5.52 | 0.00 | 0.00 | 0.00 |
August | 59.62 | 11.20 | 48.41 | 134.03 | 2.69 | 0.00 | 0.00 | 0.00 |
September | 67.31 | 26.19 | 41.12 | 123.72 | 17.53 | 0.00 | 0.00 | 0.00 |
October | 94.52 | 61.09 | 33.43 | 144.58 | 52.18 | 0.00 | 0.00 | 0.00 |
November | 103.26 | 68.91 | 34.36 | 141.04 | 74.73 | 0.00 | 0.00 | 0.00 |
December | 103.51 | 72.82 | 30.70 | 127.24 | 98.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.06 | 38.12 | 39.94 | 120.49 | 51.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.32 | 2.75 | 30.70 | 92.24 | 2.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.25 | 72.82 | 48.41 | 144.58 | 121.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.12 | 38.65 | 44.47 | 63.67 | 256.94 | 0.00 | 0.00 | 0.00 |
February | 95.23 | 44.63 | 50.60 | 96.16 | 207.16 | 0.00 | 0.00 | 0.00 |
March | 139.71 | 67.38 | 72.33 | 176.80 | 118.61 | 0.00 | 0.00 | 0.00 |
April | 157.43 | 72.01 | 85.43 | 233.84 | 86.97 | 0.00 | 0.00 | 0.00 |
May | 158.41 | 60.12 | 98.28 | 263.21 | 48.15 | 0.00 | 0.00 | 0.00 |
June | 166.42 | 64.08 | 102.34 | 317.94 | 22.02 | 0.00 | 0.00 | 0.00 |
July | 156.65 | 57.94 | 98.71 | 315.74 | 10.18 | 0.00 | 0.00 | 0.00 |
August | 153.87 | 57.55 | 96.32 | 312.22 | 5.00 | 0.00 | 0.00 | 0.00 |
September | 125.70 | 52.55 | 73.15 | 218.84 | 32.76 | 0.00 | 0.00 | 0.00 |
October | 111.85 | 58.15 | 53.69 | 158.17 | 102.74 | 0.00 | 0.00 | 0.00 |
November | 88.83 | 39.72 | 49.11 | 101.90 | 154.16 | 0.00 | 0.00 | 0.00 |
December | 73.57 | 32.23 | 41.35 | 62.55 | 208.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.06 | 53.79 | 72.27 | 193.95 | 103.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.57 | 32.23 | 41.35 | 62.55 | 5.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.42 | 72.01 | 102.34 | 317.94 | 256.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 0.00 | 19.63 | 3.07 | 145.56 | 0.00 | 0.00 | 0.00 |
February | 21.76 | 0.00 | 21.76 | 10.58 | 115.50 | 0.00 | 0.00 | 0.00 |
March | 30.56 | 0.00 | 30.56 | 24.25 | 64.30 | 0.00 | 0.00 | 0.00 |
April | 37.06 | 0.22 | 36.84 | 46.09 | 46.28 | 0.00 | 0.00 | 0.00 |
May | 44.21 | 1.39 | 42.83 | 70.21 | 24.43 | 0.00 | 0.00 | 0.00 |
June | 48.63 | 3.19 | 45.44 | 101.19 | 11.04 | 0.00 | 0.00 | 0.00 |
July | 46.05 | 2.36 | 43.69 | 103.70 | 5.37 | 0.00 | 0.00 | 0.00 |
August | 40.90 | 0.48 | 40.42 | 95.61 | 2.60 | 0.00 | 0.00 | 0.00 |
September | 30.88 | 0.01 | 30.86 | 55.30 | 17.29 | 0.00 | 0.00 | 0.00 |
October | 23.46 | 0.00 | 23.46 | 25.50 | 54.56 | 0.00 | 0.00 | 0.00 |
November | 21.00 | 0.00 | 21.00 | 13.85 | 82.42 | 0.00 | 0.00 | 0.00 |
December | 18.15 | 0.00 | 18.15 | 4.19 | 114.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.91 | 0.64 | 31.27 | 46.33 | 56.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.15 | 0.00 | 18.15 | 3.07 | 2.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.63 | 3.19 | 45.44 | 103.70 | 145.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.12 | 38.65 | 44.47 | 67.01 | 253.24 | 0.00 | 0.00 | 0.00 |
February | 95.23 | 44.63 | 50.60 | 100.06 | 203.87 | 0.00 | 0.00 | 0.00 |
March | 139.71 | 67.38 | 72.33 | 181.55 | 116.00 | 0.00 | 0.00 | 0.00 |
April | 157.43 | 72.01 | 85.43 | 236.41 | 85.99 | 0.00 | 0.00 | 0.00 |
May | 158.41 | 60.12 | 98.28 | 264.02 | 47.86 | 0.00 | 0.00 | 0.00 |
June | 166.42 | 64.08 | 102.34 | 318.05 | 21.98 | 0.00 | 0.00 | 0.00 |
July | 156.65 | 57.94 | 98.71 | 315.98 | 10.13 | 0.00 | 0.00 | 0.00 |
August | 153.87 | 57.55 | 96.32 | 313.41 | 4.84 | 0.00 | 0.00 | 0.00 |
September | 125.70 | 52.55 | 73.15 | 221.07 | 32.00 | 0.00 | 0.00 | 0.00 |
October | 111.85 | 58.15 | 53.69 | 163.19 | 100.06 | 0.00 | 0.00 | 0.00 |
November | 88.83 | 39.72 | 49.11 | 107.53 | 150.11 | 0.00 | 0.00 | 0.00 |
December | 73.57 | 32.23 | 41.35 | 67.09 | 204.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.06 | 53.79 | 72.27 | 196.80 | 102.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.57 | 32.23 | 41.35 | 67.01 | 4.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.42 | 72.01 | 102.34 | 318.05 | 253.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.89 | 106.21 | 46.68 | 165.81 | 186.01 | 0.00 | 0.00 | 0.00 |
February | 142.42 | 95.01 | 47.41 | 170.23 | 152.57 | 0.00 | 0.00 | 0.00 |
March | 130.23 | 68.34 | 61.89 | 176.44 | 92.06 | 0.00 | 0.00 | 0.00 |
April | 98.01 | 32.70 | 65.31 | 153.44 | 69.01 | 0.00 | 0.00 | 0.00 |
May | 78.78 | 9.64 | 69.14 | 137.67 | 37.01 | 0.00 | 0.00 | 0.00 |
June | 72.34 | 4.04 | 68.30 | 157.42 | 16.16 | 0.00 | 0.00 | 0.00 |
July | 72.57 | 4.89 | 67.67 | 168.59 | 7.21 | 0.00 | 0.00 | 0.00 |
August | 87.44 | 16.43 | 71.00 | 200.77 | 3.34 | 0.00 | 0.00 | 0.00 |
September | 98.72 | 38.41 | 60.31 | 182.32 | 25.35 | 0.00 | 0.00 | 0.00 |
October | 138.62 | 89.59 | 49.02 | 208.84 | 78.98 | 0.00 | 0.00 | 0.00 |
November | 151.44 | 101.06 | 50.39 | 200.70 | 114.92 | 0.00 | 0.00 | 0.00 |
December | 151.81 | 106.80 | 45.02 | 178.42 | 152.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 114.48 | 55.91 | 58.58 | 175.11 | 77.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.34 | 4.04 | 45.02 | 137.67 | 3.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.89 | 106.80 | 71.00 | 208.84 | 186.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.44 | 0.00 | 137.44 | 10.34 | 1267.10 | 0.00 | 0.00 | 0.00 |
February | 152.33 | 0.00 | 152.33 | 48.14 | 1030.44 | 0.00 | 0.00 | 0.00 |
March | 213.92 | 0.00 | 213.92 | 119.99 | 608.57 | 0.00 | 0.00 | 0.00 |
April | 259.38 | 1.51 | 257.87 | 269.92 | 440.65 | 0.00 | 0.00 | 0.00 |
May | 309.48 | 9.71 | 299.77 | 434.05 | 260.15 | 0.00 | 0.00 | 0.00 |
June | 340.37 | 22.32 | 318.05 | 642.33 | 142.34 | 0.00 | 0.00 | 0.00 |
July | 322.35 | 16.52 | 305.83 | 655.88 | 93.10 | 0.00 | 0.00 | 0.00 |
August | 286.31 | 3.36 | 282.94 | 598.61 | 71.02 | 0.00 | 0.00 | 0.00 |
September | 216.12 | 0.08 | 216.03 | 332.03 | 213.85 | 0.00 | 0.00 | 0.00 |
October | 164.21 | 0.00 | 164.21 | 133.15 | 536.12 | 0.00 | 0.00 | 0.00 |
November | 146.96 | 0.00 | 146.96 | 55.36 | 766.11 | 0.00 | 0.00 | 0.00 |
December | 127.05 | 0.00 | 127.05 | 9.86 | 1045.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 223.38 | 4.48 | 218.90 | 277.14 | 537.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.05 | 0.00 | 127.05 | 9.86 | 71.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 340.37 | 22.32 | 318.05 | 655.88 | 1267.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.44 | 0.00 | 137.44 | 8.73 | 1307.04 | 0.00 | 0.00 | 0.00 |
February | 152.33 | 0.00 | 152.33 | 43.70 | 1063.89 | 0.00 | 0.00 | 0.00 |
March | 213.92 | 0.00 | 213.92 | 110.32 | 629.27 | 0.00 | 0.00 | 0.00 |
April | 259.38 | 1.51 | 257.87 | 259.02 | 453.65 | 0.00 | 0.00 | 0.00 |
May | 309.48 | 9.71 | 299.77 | 423.35 | 268.55 | 0.00 | 0.00 | 0.00 |
June | 340.37 | 22.32 | 318.05 | 632.67 | 147.87 | 0.00 | 0.00 | 0.00 |
July | 322.35 | 16.52 | 305.83 | 646.43 | 97.96 | 0.00 | 0.00 | 0.00 |
August | 286.31 | 3.36 | 282.94 | 589.44 | 75.82 | 0.00 | 0.00 | 0.00 |
September | 216.12 | 0.08 | 216.03 | 323.16 | 222.92 | 0.00 | 0.00 | 0.00 |
October | 164.21 | 0.00 | 164.21 | 125.30 | 554.70 | 0.00 | 0.00 | 0.00 |
November | 146.96 | 0.00 | 146.96 | 48.28 | 792.35 | 0.00 | 0.00 | 0.00 |
December | 127.05 | 0.00 | 127.05 | 8.16 | 1082.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 223.38 | 4.48 | 218.90 | 269.54 | 555.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.05 | 0.00 | 127.05 | 8.16 | 75.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 340.37 | 22.32 | 318.05 | 646.43 | 1307.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 0.00 | 19.63 | 2.09 | 174.59 | 0.00 | 0.00 | 0.00 |
February | 21.76 | 0.00 | 21.76 | 8.81 | 142.04 | 0.00 | 0.00 | 0.00 |
March | 30.56 | 0.00 | 30.56 | 22.94 | 83.51 | 0.00 | 0.00 | 0.00 |
April | 37.06 | 0.22 | 36.84 | 49.41 | 60.96 | 0.00 | 0.00 | 0.00 |
May | 44.21 | 1.39 | 42.83 | 77.61 | 37.59 | 0.00 | 0.00 | 0.00 |
June | 48.63 | 3.19 | 45.44 | 109.78 | 22.28 | 0.00 | 0.00 | 0.00 |
July | 46.05 | 2.36 | 43.69 | 113.08 | 15.07 | 0.00 | 0.00 | 0.00 |
August | 40.90 | 0.48 | 40.42 | 104.60 | 11.83 | 0.00 | 0.00 | 0.00 |
September | 30.88 | 0.01 | 30.86 | 61.40 | 29.23 | 0.00 | 0.00 | 0.00 |
October | 23.46 | 0.00 | 23.46 | 26.01 | 72.56 | 0.00 | 0.00 | 0.00 |
November | 21.00 | 0.00 | 21.00 | 11.89 | 103.68 | 0.00 | 0.00 | 0.00 |
December | 18.15 | 0.00 | 18.15 | 2.25 | 142.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.91 | 0.64 | 31.27 | 49.39 | 74.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.15 | 0.00 | 18.15 | 2.09 | 11.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.63 | 3.19 | 45.44 | 113.08 | 174.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 162.23 | 73.86 | 88.36 | 101.31 | 587.02 | 0.00 | 0.00 | 0.00 |
February | 203.60 | 109.60 | 94.00 | 190.15 | 475.76 | 0.00 | 0.00 | 0.00 |
March | 256.16 | 116.85 | 139.31 | 304.95 | 283.93 | 0.00 | 0.00 | 0.00 |
April | 309.65 | 141.33 | 168.31 | 469.78 | 213.50 | 0.00 | 0.00 | 0.00 |
May | 339.21 | 143.45 | 195.76 | 589.32 | 138.35 | 0.00 | 0.00 | 0.00 |
June | 350.85 | 146.95 | 203.90 | 702.34 | 82.89 | 0.00 | 0.00 | 0.00 |
July | 341.97 | 143.47 | 198.50 | 716.41 | 56.74 | 0.00 | 0.00 | 0.00 |
August | 313.43 | 124.33 | 189.10 | 672.74 | 44.54 | 0.00 | 0.00 | 0.00 |
September | 256.88 | 113.51 | 143.37 | 477.00 | 106.97 | 0.00 | 0.00 | 0.00 |
October | 219.71 | 114.36 | 105.35 | 310.74 | 251.39 | 0.00 | 0.00 | 0.00 |
November | 174.98 | 78.93 | 96.05 | 178.33 | 347.78 | 0.00 | 0.00 | 0.00 |
December | 151.85 | 69.12 | 82.73 | 102.08 | 476.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 256.97 | 114.63 | 142.34 | 402.39 | 254.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 151.85 | 69.12 | 82.73 | 101.31 | 44.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 350.85 | 146.95 | 203.90 | 716.41 | 587.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.25 | 72.42 | 31.83 | 115.61 | 141.70 | 0.00 | 0.00 | 0.00 |
February | 97.11 | 64.78 | 32.32 | 118.83 | 120.05 | 0.00 | 0.00 | 0.00 |
March | 88.80 | 46.60 | 42.20 | 124.56 | 77.67 | 0.00 | 0.00 | 0.00 |
April | 66.83 | 22.30 | 44.53 | 110.02 | 61.10 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 6.57 | 47.15 | 100.67 | 38.94 | 0.00 | 0.00 | 0.00 |
June | 49.32 | 2.75 | 46.57 | 113.67 | 23.29 | 0.00 | 0.00 | 0.00 |
July | 49.48 | 3.34 | 46.14 | 121.33 | 15.33 | 0.00 | 0.00 | 0.00 |
August | 59.62 | 11.20 | 48.41 | 143.87 | 11.88 | 0.00 | 0.00 | 0.00 |
September | 67.31 | 26.19 | 41.12 | 132.25 | 28.85 | 0.00 | 0.00 | 0.00 |
October | 94.52 | 61.09 | 33.43 | 149.25 | 67.54 | 0.00 | 0.00 | 0.00 |
November | 103.26 | 68.91 | 34.36 | 142.63 | 91.03 | 0.00 | 0.00 | 0.00 |
December | 103.51 | 72.82 | 30.70 | 124.97 | 118.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.06 | 38.12 | 39.94 | 124.86 | 66.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.32 | 2.75 | 30.70 | 100.67 | 11.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.25 | 72.82 | 48.41 | 149.25 | 141.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.87 | 0.00 | 24.87 | 2.74 | 206.07 | 0.00 | 0.00 | 0.00 |
February | 27.56 | 0.00 | 27.56 | 10.83 | 164.08 | 0.00 | 0.00 | 0.00 |
March | 38.70 | 0.00 | 38.70 | 26.52 | 93.18 | 0.00 | 0.00 | 0.00 |
April | 46.93 | 0.27 | 46.65 | 54.12 | 69.46 | 0.00 | 0.00 | 0.00 |
May | 55.99 | 1.76 | 54.24 | 83.05 | 41.80 | 0.00 | 0.00 | 0.00 |
June | 61.58 | 4.04 | 57.54 | 118.31 | 23.82 | 0.00 | 0.00 | 0.00 |
July | 58.32 | 2.99 | 55.33 | 119.86 | 15.33 | 0.00 | 0.00 | 0.00 |
August | 51.80 | 0.61 | 51.19 | 108.74 | 11.78 | 0.00 | 0.00 | 0.00 |
September | 39.10 | 0.02 | 39.09 | 62.53 | 34.29 | 0.00 | 0.00 | 0.00 |
October | 29.71 | 0.00 | 29.71 | 27.26 | 83.02 | 0.00 | 0.00 | 0.00 |
November | 26.59 | 0.00 | 26.59 | 13.42 | 118.85 | 0.00 | 0.00 | 0.00 |
December | 22.99 | 0.00 | 22.99 | 2.78 | 164.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.42 | 0.81 | 39.60 | 52.75 | 85.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.99 | 0.00 | 22.99 | 2.74 | 11.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.58 | 4.04 | 57.54 | 119.86 | 206.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.25 | 0.00 | 22.25 | 2.45 | 184.37 | 0.00 | 0.00 | 0.00 |
February | 24.66 | 0.00 | 24.66 | 9.69 | 146.81 | 0.00 | 0.00 | 0.00 |
March | 34.63 | 0.00 | 34.63 | 23.73 | 83.37 | 0.00 | 0.00 | 0.00 |
April | 41.99 | 0.25 | 41.74 | 48.42 | 62.14 | 0.00 | 0.00 | 0.00 |
May | 50.10 | 1.57 | 48.53 | 74.30 | 37.40 | 0.00 | 0.00 | 0.00 |
June | 55.10 | 3.61 | 51.48 | 105.85 | 21.31 | 0.00 | 0.00 | 0.00 |
July | 52.18 | 2.67 | 49.51 | 107.24 | 13.71 | 0.00 | 0.00 | 0.00 |
August | 46.35 | 0.54 | 45.80 | 97.29 | 10.54 | 0.00 | 0.00 | 0.00 |
September | 34.98 | 0.01 | 34.97 | 55.94 | 30.68 | 0.00 | 0.00 | 0.00 |
October | 26.58 | 0.00 | 26.58 | 24.39 | 74.28 | 0.00 | 0.00 | 0.00 |
November | 23.79 | 0.00 | 23.79 | 12.01 | 106.34 | 0.00 | 0.00 | 0.00 |
December | 20.57 | 0.00 | 20.57 | 2.49 | 147.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.16 | 0.73 | 35.43 | 47.20 | 76.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.57 | 0.00 | 20.57 | 2.45 | 10.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.10 | 3.61 | 51.48 | 107.24 | 184.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 389.19 | 270.36 | 118.83 | 428.01 | 491.66 | 0.00 | 0.00 | 0.00 |
February | 362.53 | 241.86 | 120.67 | 438.18 | 407.75 | 0.00 | 0.00 | 0.00 |
March | 331.52 | 173.96 | 157.55 | 450.80 | 255.50 | 0.00 | 0.00 | 0.00 |
April | 249.49 | 83.24 | 166.25 | 382.19 | 206.59 | 0.00 | 0.00 | 0.00 |
May | 200.55 | 24.54 | 176.01 | 330.14 | 130.84 | 0.00 | 0.00 | 0.00 |
June | 184.14 | 10.28 | 173.86 | 363.20 | 75.98 | 0.00 | 0.00 | 0.00 |
July | 184.72 | 12.46 | 172.26 | 385.66 | 47.61 | 0.00 | 0.00 | 0.00 |
August | 222.58 | 41.83 | 180.75 | 466.46 | 35.70 | 0.00 | 0.00 | 0.00 |
September | 251.29 | 97.77 | 153.51 | 443.15 | 100.50 | 0.00 | 0.00 | 0.00 |
October | 352.86 | 228.06 | 124.79 | 530.89 | 227.49 | 0.00 | 0.00 | 0.00 |
November | 385.51 | 257.25 | 128.26 | 518.88 | 306.80 | 0.00 | 0.00 | 0.00 |
December | 386.45 | 271.85 | 114.60 | 461.58 | 401.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 291.42 | 142.31 | 149.11 | 433.29 | 223.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 184.14 | 10.28 | 114.60 | 330.14 | 35.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 389.19 | 271.85 | 180.75 | 530.89 | 491.66 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141220E+10 | 0.981020E+09 | 0.431183E+09 | 0.159523E+10 | 0.162720E+10 |
February | 0.118818E+10 | 0.792686E+09 | 0.395494E+09 | 0.146571E+10 | 0.122361E+10 |
March | 0.120293E+10 | 0.631243E+09 | 0.571687E+09 | 0.165876E+10 | 0.874446E+09 |
April | 0.876087E+09 | 0.292293E+09 | 0.583795E+09 | 0.136820E+10 | 0.668454E+09 |
May | 0.727706E+09 | 89053889.35 | 0.638652E+09 | 0.122501E+10 | 0.430524E+09 |
June | 0.646621E+09 | 36100811.87 | 0.610520E+09 | 0.127140E+10 | 0.253467E+09 |
July | 0.670261E+09 | 45210453.17 | 0.625050E+09 | 0.138432E+10 | 0.167172E+09 |
August | 0.807634E+09 | 0.151787E+09 | 0.655847E+09 | 0.166727E+10 | 0.137518E+09 |
September | 0.882405E+09 | 0.343335E+09 | 0.539070E+09 | 0.155656E+10 | 0.336136E+09 |
October | 0.128037E+10 | 0.827554E+09 | 0.452812E+09 | 0.192790E+10 | 0.783062E+09 |
November | 0.135373E+10 | 0.903351E+09 | 0.450383E+09 | 0.182534E+10 | 0.102127E+10 |
December | 0.140226E+10 | 0.986443E+09 | 0.415820E+09 | 0.170288E+10 | 0.135100E+10 |
Annual Sum or Average | 0.124504E+11 | 0.608008E+10 | 0.637031E+10 | 0.186486E+11 | 0.887386E+10 |
Minimum of Months | 0.646621E+09 | 36100811.87 | 0.395494E+09 | 0.122501E+10 | 0.137518E+09 |
Maximum of Months | 0.141220E+10 | 0.986443E+09 | 0.655847E+09 | 0.192790E+10 | 0.162720E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.397667E+10 | 0.276249E+10 | 0.121418E+10 | 0.439168E+10 | 0.484680E+10 |
February | 0.334584E+10 | 0.223215E+10 | 0.111368E+10 | 0.403476E+10 | 0.371549E+10 |
March | 0.338737E+10 | 0.177754E+10 | 0.160983E+10 | 0.454785E+10 | 0.275963E+10 |
April | 0.246700E+10 | 0.823077E+09 | 0.164393E+10 | 0.374362E+10 | 0.211433E+10 |
May | 0.204917E+10 | 0.250770E+09 | 0.179840E+10 | 0.334963E+10 | 0.138770E+10 |
June | 0.182084E+10 | 0.101658E+09 | 0.171918E+10 | 0.353595E+10 | 0.784587E+09 |
July | 0.188741E+10 | 0.127310E+09 | 0.176010E+10 | 0.386398E+10 | 0.523795E+09 |
August | 0.227424E+10 | 0.427422E+09 | 0.184682E+10 | 0.467013E+10 | 0.418008E+09 |
September | 0.248479E+10 | 0.966809E+09 | 0.151798E+10 | 0.431634E+10 | 0.107502E+10 |
October | 0.360543E+10 | 0.233034E+10 | 0.127509E+10 | 0.532823E+10 | 0.247078E+10 |
November | 0.381203E+10 | 0.254378E+10 | 0.126825E+10 | 0.501717E+10 | 0.319500E+10 |
December | 0.394868E+10 | 0.277776E+10 | 0.117092E+10 | 0.468528E+10 | 0.411608E+10 |
Annual Sum or Average | 0.350595E+11 | 0.171211E+11 | 0.179384E+11 | 0.514846E+11 | 0.274072E+11 |
Minimum of Months | 0.182084E+10 | 0.101658E+09 | 0.111368E+10 | 0.334963E+10 | 0.418008E+09 |
Maximum of Months | 0.397667E+10 | 0.277776E+10 | 0.184682E+10 | 0.532823E+10 | 0.484680E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.516592E+10 | 0.358863E+10 | 0.157729E+10 | 0.580875E+10 | 0.658079E+10 |
February | 0.434643E+10 | 0.289969E+10 | 0.144674E+10 | 0.534884E+10 | 0.503429E+10 |
March | 0.440039E+10 | 0.230912E+10 | 0.209126E+10 | 0.604099E+10 | 0.370400E+10 |
April | 0.320478E+10 | 0.106922E+10 | 0.213555E+10 | 0.497065E+10 | 0.284424E+10 |
May | 0.266199E+10 | 0.325764E+09 | 0.233623E+10 | 0.445670E+10 | 0.185155E+10 |
June | 0.236538E+10 | 0.132059E+09 | 0.223332E+10 | 0.472322E+10 | 0.103088E+10 |
July | 0.245185E+10 | 0.165382E+09 | 0.228647E+10 | 0.517154E+10 | 0.680782E+09 |
August | 0.295437E+10 | 0.555246E+09 | 0.239913E+10 | 0.625351E+10 | 0.527634E+09 |
September | 0.322789E+10 | 0.125594E+10 | 0.197195E+10 | 0.573902E+10 | 0.141897E+10 |
October | 0.468365E+10 | 0.302724E+10 | 0.165641E+10 | 0.707281E+10 | 0.331538E+10 |
November | 0.495204E+10 | 0.330451E+10 | 0.164753E+10 | 0.664044E+10 | 0.430496E+10 |
December | 0.512956E+10 | 0.360846E+10 | 0.152109E+10 | 0.619497E+10 | 0.559263E+10 |
Annual Sum or Average | 0.455443E+11 | 0.222413E+11 | 0.233030E+11 | 0.684214E+11 | 0.368861E+11 |
Minimum of Months | 0.236538E+10 | 0.132059E+09 | 0.144674E+10 | 0.445670E+10 | 0.527634E+09 |
Maximum of Months | 0.516592E+10 | 0.360846E+10 | 0.239913E+10 | 0.707281E+10 | 0.658079E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279218E+09 | 0.193965E+09 | 85252967.91 | 0.319035E+09 | 0.327112E+09 |
February | 0.234924E+09 | 0.156728E+09 | 78196598.94 | 0.292732E+09 | 0.243155E+09 |
March | 0.237841E+09 | 0.124808E+09 | 0.113033E+09 | 0.330645E+09 | 0.166739E+09 |
April | 0.173219E+09 | 57791307.85 | 0.115427E+09 | 0.273495E+09 | 0.124571E+09 |
May | 0.143881E+09 | 17607483.41 | 0.126274E+09 | 0.249549E+09 | 71376555.13 |
June | 0.127849E+09 | 7137750.53 | 0.120712E+09 | 0.272028E+09 | 32414402.94 |
July | 0.132523E+09 | 8938883.07 | 0.123585E+09 | 0.300876E+09 | 16058720.93 |
August | 0.159684E+09 | 30010917.68 | 0.129673E+09 | 0.360496E+09 | 8221444.91 |
September | 0.174468E+09 | 67883271.16 | 0.106584E+09 | 0.322206E+09 | 47555552.36 |
October | 0.253151E+09 | 0.163622E+09 | 89529587.28 | 0.389062E+09 | 0.142828E+09 |
November | 0.267657E+09 | 0.178608E+09 | 89049108.36 | 0.366634E+09 | 0.196703E+09 |
December | 0.277252E+09 | 0.195037E+09 | 82215273.99 | 0.341849E+09 | 0.266848E+09 |
Annual Sum or Average | 0.246167E+10 | 0.120214E+10 | 0.125953E+10 | 0.381861E+10 | 0.164358E+10 |
Minimum of Months | 0.127849E+09 | 7137750.53 | 78196598.94 | 0.249549E+09 | 8221444.91 |
Maximum of Months | 0.279218E+09 | 0.195037E+09 | 0.129673E+09 | 0.389062E+09 | 0.327112E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222627E+09 | 0.103516E+09 | 0.119111E+09 | 0.170554E+09 | 0.691269E+09 |
February | 0.230374E+09 | 0.107973E+09 | 0.122401E+09 | 0.233714E+09 | 0.505079E+09 |
March | 0.374198E+09 | 0.180474E+09 | 0.193725E+09 | 0.477148E+09 | 0.323313E+09 |
April | 0.408065E+09 | 0.186640E+09 | 0.221425E+09 | 0.610968E+09 | 0.229371E+09 |
May | 0.424277E+09 | 0.161030E+09 | 0.263246E+09 | 0.711402E+09 | 0.132085E+09 |
June | 0.431370E+09 | 0.166096E+09 | 0.265273E+09 | 0.829671E+09 | 60103871.66 |
July | 0.419570E+09 | 0.155192E+09 | 0.264378E+09 | 0.850138E+09 | 29694109.46 |
August | 0.412124E+09 | 0.154141E+09 | 0.257983E+09 | 0.840375E+09 | 15288136.47 |
September | 0.325820E+09 | 0.136209E+09 | 0.189611E+09 | 0.569933E+09 | 89077928.89 |
October | 0.299566E+09 | 0.155754E+09 | 0.143812E+09 | 0.425745E+09 | 0.281680E+09 |
November | 0.230249E+09 | 0.102964E+09 | 0.127285E+09 | 0.264626E+09 | 0.405892E+09 |
December | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.167100E+09 | 0.564838E+09 |
Annual Sum or Average | 0.397530E+10 | 0.169631E+10 | 0.227899E+10 | 0.615137E+10 | 0.332769E+10 |
Minimum of Months | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.167100E+09 | 15288136.47 |
Maximum of Months | 0.431370E+09 | 0.186640E+09 | 0.265273E+09 | 0.850138E+09 | 0.691269E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52588594.07 | 0.00 | 52588594.07 | 7908542.94 | 0.391136E+09 |
February | 52648446.06 | 0.00 | 52648446.06 | 24973849.64 | 0.281360E+09 |
March | 81855013.60 | 1648.52 | 81853365.08 | 64188794.87 | 0.175480E+09 |
April | 96048332.89 | 560963.03 | 95487369.87 | 0.119850E+09 | 0.122160E+09 |
May | 0.118419E+09 | 3714011.78 | 0.114705E+09 | 0.189781E+09 | 66915798.98 |
June | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.263381E+09 | 30031972.83 |
July | 0.123345E+09 | 6320378.90 | 0.117025E+09 | 0.278807E+09 | 15521699.45 |
August | 0.109554E+09 | 1287040.28 | 0.108267E+09 | 0.256610E+09 | 7960956.20 |
September | 80028430.11 | 31459.51 | 79996970.60 | 0.143180E+09 | 47102484.82 |
October | 62833545.17 | 0.00 | 62833545.17 | 67017804.75 | 0.150010E+09 |
November | 54419711.70 | 0.00 | 54419711.70 | 34482980.94 | 0.217473E+09 |
December | 48614241.33 | 0.00 | 48614241.33 | 10306190.49 | 0.309795E+09 |
Annual Sum or Average | 0.100639E+10 | 20181056.73 | 0.986211E+09 | 0.146049E+10 | 0.181495E+10 |
Minimum of Months | 48614241.33 | 0.00 | 48614241.33 | 7908542.94 | 7960956.20 |
Maximum of Months | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.278807E+09 | 0.391136E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222627E+09 | 0.103516E+09 | 0.119111E+09 | 0.179795E+09 | 0.680407E+09 |
February | 0.230374E+09 | 0.107973E+09 | 0.122401E+09 | 0.242900E+09 | 0.496991E+09 |
March | 0.374198E+09 | 0.180474E+09 | 0.193725E+09 | 0.488628E+09 | 0.316937E+09 |
April | 0.408065E+09 | 0.186640E+09 | 0.221425E+09 | 0.617231E+09 | 0.227036E+09 |
May | 0.424277E+09 | 0.161030E+09 | 0.263246E+09 | 0.713542E+09 | 0.131366E+09 |
June | 0.431370E+09 | 0.166096E+09 | 0.265273E+09 | 0.829957E+09 | 60026299.12 |
July | 0.419570E+09 | 0.155192E+09 | 0.264378E+09 | 0.850786E+09 | 29544626.08 |
August | 0.412124E+09 | 0.154141E+09 | 0.257983E+09 | 0.843410E+09 | 14860948.35 |
September | 0.325820E+09 | 0.136209E+09 | 0.189611E+09 | 0.575304E+09 | 87284258.05 |
October | 0.299566E+09 | 0.155754E+09 | 0.143812E+09 | 0.437668E+09 | 0.275296E+09 |
November | 0.230249E+09 | 0.102964E+09 | 0.127285E+09 | 0.277726E+09 | 0.396059E+09 |
December | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.178588E+09 | 0.553125E+09 |
Annual Sum or Average | 0.397530E+10 | 0.169631E+10 | 0.227899E+10 | 0.623554E+10 | 0.326893E+10 |
Minimum of Months | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.178588E+09 | 14860948.35 |
Maximum of Months | 0.431370E+09 | 0.186640E+09 | 0.265273E+09 | 0.850786E+09 | 0.680407E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223330E+09 | 0.155141E+09 | 68188813.41 | 0.251886E+09 | 0.257402E+09 |
February | 0.187902E+09 | 0.125357E+09 | 62544840.67 | 0.230227E+09 | 0.196058E+09 |
March | 0.190235E+09 | 99826196.68 | 90408627.06 | 0.255465E+09 | 0.151722E+09 |
April | 0.138547E+09 | 46223853.60 | 92323562.43 | 0.212153E+09 | 0.115779E+09 |
May | 0.115082E+09 | 14083185.96 | 0.100999E+09 | 0.193238E+09 | 72348624.61 |
June | 0.102259E+09 | 5709065.05 | 96550134.41 | 0.210339E+09 | 37070486.12 |
July | 0.105998E+09 | 7149684.58 | 98847981.78 | 0.231739E+09 | 22368475.53 |
August | 0.127722E+09 | 24003960.40 | 0.103718E+09 | 0.278271E+09 | 15438210.65 |
September | 0.139546E+09 | 54295818.95 | 85250458.26 | 0.249769E+09 | 53196295.33 |
October | 0.202481E+09 | 0.130871E+09 | 71609428.64 | 0.302078E+09 | 0.134692E+09 |
November | 0.214083E+09 | 0.142858E+09 | 71225121.93 | 0.281993E+09 | 0.179620E+09 |
December | 0.221757E+09 | 0.155998E+09 | 65759141.47 | 0.265149E+09 | 0.223896E+09 |
Annual Sum or Average | 0.196894E+10 | 0.961517E+09 | 0.100743E+10 | 0.296231E+10 | 0.145959E+10 |
Minimum of Months | 0.102259E+09 | 5709065.05 | 62544840.67 | 0.193238E+09 | 15438210.65 |
Maximum of Months | 0.223330E+09 | 0.155998E+09 | 0.103718E+09 | 0.302078E+09 | 0.257402E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42076451.99 | 0.00 | 42076451.99 | 5754330.72 | 0.326874E+09 |
February | 42124339.93 | 0.00 | 42124339.93 | 20078982.61 | 0.233649E+09 |
March | 65492691.15 | 1318.99 | 65491372.16 | 54617022.22 | 0.140452E+09 |
April | 76848851.72 | 448829.91 | 76400021.81 | 0.103194E+09 | 94889871.74 |
May | 94747450.04 | 2971603.27 | 91775846.77 | 0.162503E+09 | 49707948.09 |
June | 0.100844E+09 | 6613320.29 | 94230889.24 | 0.224020E+09 | 20381395.01 |
July | 98689421.90 | 5056973.36 | 93632448.53 | 0.237736E+09 | 9492159.73 |
August | 87654522.95 | 1029768.70 | 86624754.24 | 0.221709E+09 | 4061988.70 |
September | 64031230.67 | 25170.94 | 64006059.72 | 0.125213E+09 | 33990735.78 |
October | 50273499.29 | 0.00 | 50273499.29 | 58022804.25 | 0.119391E+09 |
November | 43541540.27 | 0.00 | 43541540.27 | 28178591.38 | 0.178357E+09 |
December | 38896548.34 | 0.00 | 38896548.34 | 7219455.35 | 0.259316E+09 |
Annual Sum or Average | 0.805221E+09 | 16146985.47 | 0.789074E+09 | 0.124825E+10 | 0.147056E+10 |
Minimum of Months | 38896548.34 | 0.00 | 38896548.34 | 5754330.72 | 4061988.70 |
Maximum of Months | 0.100844E+09 | 6613320.29 | 94230889.24 | 0.237736E+09 | 0.326874E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217269E+09 | 98926312.94 | 0.118343E+09 | 0.143160E+09 | 0.670657E+09 |
February | 0.246295E+09 | 0.132584E+09 | 0.113711E+09 | 0.232720E+09 | 0.477320E+09 |
March | 0.343073E+09 | 0.156492E+09 | 0.186581E+09 | 0.400121E+09 | 0.299892E+09 |
April | 0.401332E+09 | 0.183183E+09 | 0.218149E+09 | 0.581129E+09 | 0.211359E+09 |
May | 0.454306E+09 | 0.192122E+09 | 0.262184E+09 | 0.748148E+09 | 0.121612E+09 |
June | 0.454739E+09 | 0.190467E+09 | 0.264272E+09 | 0.863772E+09 | 54562761.80 |
July | 0.458002E+09 | 0.192153E+09 | 0.265848E+09 | 0.911884E+09 | 28500929.89 |
August | 0.419782E+09 | 0.166515E+09 | 0.253266E+09 | 0.854575E+09 | 14345546.09 |
September | 0.332940E+09 | 0.147113E+09 | 0.185827E+09 | 0.578748E+09 | 84678284.60 |
October | 0.294256E+09 | 0.153163E+09 | 0.141093E+09 | 0.395645E+09 | 0.262389E+09 |
November | 0.226791E+09 | 0.102303E+09 | 0.124488E+09 | 0.227410E+09 | 0.373806E+09 |
December | 0.203367E+09 | 92572432.32 | 0.110794E+09 | 0.144575E+09 | 0.530353E+09 |
Annual Sum or Average | 0.405215E+10 | 0.180759E+10 | 0.224456E+10 | 0.608189E+10 | 0.312948E+10 |
Minimum of Months | 0.203367E+09 | 92572432.32 | 0.110794E+09 | 0.143160E+09 | 14345546.09 |
Maximum of Months | 0.458002E+09 | 0.192153E+09 | 0.265848E+09 | 0.911884E+09 | 0.670657E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279218E+09 | 0.193965E+09 | 85252967.91 | 0.317501E+09 | 0.326328E+09 |
February | 0.234924E+09 | 0.156728E+09 | 78196598.94 | 0.290162E+09 | 0.242702E+09 |
March | 0.237841E+09 | 0.124808E+09 | 0.113033E+09 | 0.327836E+09 | 0.165387E+09 |
April | 0.173219E+09 | 57791307.85 | 0.115427E+09 | 0.270635E+09 | 0.123744E+09 |
May | 0.143881E+09 | 17607483.41 | 0.126274E+09 | 0.246707E+09 | 70933546.76 |
June | 0.127849E+09 | 7137750.53 | 0.120712E+09 | 0.269732E+09 | 31991719.77 |
July | 0.132523E+09 | 8938883.07 | 0.123585E+09 | 0.298874E+09 | 15817738.31 |
August | 0.159684E+09 | 30010917.68 | 0.129673E+09 | 0.359493E+09 | 7921103.49 |
September | 0.174468E+09 | 67883271.16 | 0.106584E+09 | 0.320751E+09 | 47022695.28 |
October | 0.253151E+09 | 0.163622E+09 | 89529587.28 | 0.386689E+09 | 0.141802E+09 |
November | 0.267657E+09 | 0.178608E+09 | 89049108.36 | 0.364936E+09 | 0.195854E+09 |
December | 0.277252E+09 | 0.195037E+09 | 82215273.99 | 0.340327E+09 | 0.266283E+09 |
Annual Sum or Average | 0.246167E+10 | 0.120214E+10 | 0.125953E+10 | 0.379364E+10 | 0.163579E+10 |
Minimum of Months | 0.127849E+09 | 7137750.53 | 78196598.94 | 0.246707E+09 | 7921103.49 |
Maximum of Months | 0.279218E+09 | 0.195037E+09 | 0.129673E+09 | 0.386689E+09 | 0.326328E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52588594.07 | 0.00 | 52588594.07 | 7521538.93 | 0.391174E+09 |
February | 52648446.06 | 0.00 | 52648446.06 | 23876899.18 | 0.282142E+09 |
March | 81855013.60 | 1648.52 | 81853365.08 | 62542080.40 | 0.175128E+09 |
April | 96048332.89 | 560963.03 | 95487369.87 | 0.116881E+09 | 0.121718E+09 |
May | 0.118419E+09 | 3714011.78 | 0.114705E+09 | 0.186590E+09 | 66424619.05 |
June | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.260944E+09 | 29507571.83 |
July | 0.123345E+09 | 6320378.90 | 0.117025E+09 | 0.276779E+09 | 15308598.74 |
August | 0.109554E+09 | 1287040.28 | 0.108267E+09 | 0.255484E+09 | 7661762.98 |
September | 80028430.11 | 31459.51 | 79996970.60 | 0.141339E+09 | 46709634.86 |
October | 62833545.17 | 0.00 | 62833545.17 | 64606357.11 | 0.149681E+09 |
November | 54419711.70 | 0.00 | 54419711.70 | 33827545.92 | 0.217031E+09 |
December | 48614241.33 | 0.00 | 48614241.33 | 9863966.68 | 0.309994E+09 |
Annual Sum or Average | 0.100639E+10 | 20181056.73 | 0.986211E+09 | 0.144026E+10 | 0.181248E+10 |
Minimum of Months | 48614241.33 | 0.00 | 48614241.33 | 7521538.93 | 7661762.98 |
Maximum of Months | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.276779E+09 | 0.391174E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217269E+09 | 98926312.94 | 0.118343E+09 | 0.148432E+09 | 0.655308E+09 |
February | 0.246295E+09 | 0.132584E+09 | 0.113711E+09 | 0.240839E+09 | 0.467888E+09 |
March | 0.343073E+09 | 0.156492E+09 | 0.186581E+09 | 0.411387E+09 | 0.293204E+09 |
April | 0.401332E+09 | 0.183183E+09 | 0.218149E+09 | 0.586464E+09 | 0.208980E+09 |
May | 0.454306E+09 | 0.192122E+09 | 0.262184E+09 | 0.749911E+09 | 0.120931E+09 |
June | 0.454739E+09 | 0.190467E+09 | 0.264272E+09 | 0.864095E+09 | 54490741.56 |
July | 0.458002E+09 | 0.192153E+09 | 0.265848E+09 | 0.912592E+09 | 28370353.78 |
August | 0.419782E+09 | 0.166515E+09 | 0.253266E+09 | 0.857515E+09 | 13941682.71 |
September | 0.332940E+09 | 0.147113E+09 | 0.185827E+09 | 0.583427E+09 | 82999459.53 |
October | 0.294256E+09 | 0.153163E+09 | 0.141093E+09 | 0.406409E+09 | 0.256024E+09 |
November | 0.226791E+09 | 0.102303E+09 | 0.124488E+09 | 0.240193E+09 | 0.362704E+09 |
December | 0.203367E+09 | 92572432.32 | 0.110794E+09 | 0.152785E+09 | 0.514852E+09 |
Annual Sum or Average | 0.405215E+10 | 0.180759E+10 | 0.224456E+10 | 0.615405E+10 | 0.305969E+10 |
Minimum of Months | 0.203367E+09 | 92572432.32 | 0.110794E+09 | 0.148432E+09 | 13941682.71 |
Maximum of Months | 0.458002E+09 | 0.192153E+09 | 0.265848E+09 | 0.912592E+09 | 0.655308E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66600136.23 | 0.00 | 66600136.23 | 8286397.93 | 0.539700E+09 |
February | 66675935.00 | 0.00 | 66675935.00 | 28652335.66 | 0.388402E+09 |
March | 0.103664E+09 | 2087.74 | 0.103662E+09 | 76984980.31 | 0.247171E+09 |
April | 0.121639E+09 | 710424.28 | 0.120929E+09 | 0.148330E+09 | 0.177686E+09 |
May | 0.149970E+09 | 4703561.58 | 0.145266E+09 | 0.235472E+09 | 0.106486E+09 |
June | 0.159620E+09 | 10467803.52 | 0.149152E+09 | 0.319849E+09 | 57514328.53 |
July | 0.156209E+09 | 8004361.08 | 0.148205E+09 | 0.333802E+09 | 37491518.85 |
August | 0.138743E+09 | 1629955.30 | 0.137113E+09 | 0.303711E+09 | 27572698.30 |
September | 0.101351E+09 | 39841.48 | 0.101311E+09 | 0.170202E+09 | 86080969.80 |
October | 79574720.39 | 0.00 | 79574720.39 | 77755836.01 | 0.221370E+09 |
November | 68919131.17 | 0.00 | 68919131.17 | 38474736.58 | 0.304355E+09 |
December | 61566869.25 | 0.00 | 61566869.25 | 9040366.88 | 0.430120E+09 |
Annual Sum or Average | 0.127453E+10 | 25558034.99 | 0.124897E+10 | 0.175056E+10 | 0.262395E+10 |
Minimum of Months | 61566869.25 | 0.00 | 61566869.25 | 8286397.93 | 27572698.30 |
Maximum of Months | 0.159620E+09 | 10467803.52 | 0.149152E+09 | 0.333802E+09 | 0.539700E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 24551567.91 | 0.00 | 24551567.91 | 3054709.39 | 0.198956E+09 |
February | 24579510.47 | 0.00 | 24579510.47 | 10562437.33 | 0.143181E+09 |
March | 38214920.19 | 769.63 | 38214150.56 | 28379851.44 | 91117547.10 |
April | 44841228.59 | 261891.81 | 44579336.78 | 54680459.39 | 65502517.62 |
May | 55285042.92 | 1733927.56 | 53551115.36 | 86804577.38 | 39255115.20 |
June | 58842496.02 | 3858865.82 | 54983630.20 | 0.117910E+09 | 21202162.98 |
July | 57585179.58 | 2950738.93 | 54634440.65 | 0.123053E+09 | 13820926.25 |
August | 51146327.01 | 600869.02 | 50545457.99 | 0.111961E+09 | 10164438.29 |
September | 37362159.44 | 14687.22 | 37347472.22 | 62743349.88 | 31733009.80 |
October | 29334536.86 | 0.00 | 29334536.86 | 28664020.77 | 81606141.86 |
November | 25406445.47 | 0.00 | 25406445.47 | 14183381.02 | 0.112198E+09 |
December | 22696097.29 | 0.00 | 22696097.29 | 3332653.57 | 0.158560E+09 |
Annual Sum or Average | 0.469846E+09 | 9421749.97 | 0.460424E+09 | 0.645329E+09 | 0.967297E+09 |
Minimum of Months | 22696097.29 | 0.00 | 22696097.29 | 3054709.39 | 10164438.29 |
Maximum of Months | 58842496.02 | 3858865.82 | 54983630.20 | 0.123053E+09 | 0.198956E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130282E+09 | 90503082.87 | 39778691.28 | 0.146400E+09 | 0.161728E+09 |
February | 0.109615E+09 | 73128454.63 | 36486217.96 | 0.135395E+09 | 0.120813E+09 |
March | 0.110976E+09 | 58234705.39 | 52740862.99 | 0.154573E+09 | 84691283.44 |
April | 80823152.87 | 26965191.36 | 53857961.51 | 0.127551E+09 | 65883066.24 |
May | 67134435.80 | 8215580.81 | 58918854.99 | 0.115544E+09 | 41591133.10 |
June | 59654024.21 | 3330445.64 | 56323578.57 | 0.122544E+09 | 22913488.14 |
July | 61834899.83 | 4170846.82 | 57664053.01 | 0.133899E+09 | 14522916.49 |
August | 74508055.00 | 14002973.25 | 60505081.75 | 0.161142E+09 | 10394802.40 |
September | 81405849.48 | 31674060.78 | 49731788.71 | 0.147229E+09 | 31433562.73 |
October | 0.118119E+09 | 76345167.07 | 41774144.65 | 0.180804E+09 | 75764853.57 |
November | 0.124888E+09 | 83337782.51 | 41549955.12 | 0.171080E+09 | 98437557.04 |
December | 0.129365E+09 | 91003310.47 | 38361315.54 | 0.157860E+09 | 0.132019E+09 |
Annual Sum or Average | 0.114860E+10 | 0.560912E+09 | 0.587693E+09 | 0.175402E+10 | 0.860193E+09 |
Minimum of Months | 59654024.21 | 3330445.64 | 36486217.96 | 0.115544E+09 | 10394802.40 |
Maximum of Months | 0.130282E+09 | 91003310.47 | 60505081.75 | 0.180804E+09 | 0.161728E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353611E+09 | 0.245644E+09 | 0.107968E+09 | 0.397360E+09 | 0.438964E+09 |
February | 0.297517E+09 | 0.198486E+09 | 99031058.63 | 0.367490E+09 | 0.327910E+09 |
March | 0.301210E+09 | 0.158061E+09 | 0.143149E+09 | 0.419544E+09 | 0.229869E+09 |
April | 0.219371E+09 | 73189044.97 | 0.146182E+09 | 0.346200E+09 | 0.178820E+09 |
May | 0.182217E+09 | 22298766.77 | 0.159918E+09 | 0.313609E+09 | 0.112887E+09 |
June | 0.161913E+09 | 9039510.68 | 0.152874E+09 | 0.332610E+09 | 62191893.67 |
July | 0.167833E+09 | 11320531.40 | 0.156512E+09 | 0.363429E+09 | 39418165.94 |
August | 0.202230E+09 | 38006933.66 | 0.164223E+09 | 0.437373E+09 | 28213617.48 |
September | 0.220952E+09 | 85969879.73 | 0.134982E+09 | 0.399610E+09 | 85317118.84 |
October | 0.320600E+09 | 0.207216E+09 | 0.113384E+09 | 0.490739E+09 | 0.205641E+09 |
November | 0.338971E+09 | 0.226196E+09 | 0.112775E+09 | 0.464346E+09 | 0.267180E+09 |
December | 0.351122E+09 | 0.247002E+09 | 0.104120E+09 | 0.428463E+09 | 0.358328E+09 |
Annual Sum or Average | 0.311755E+10 | 0.152243E+10 | 0.159512E+10 | 0.476077E+10 | 0.233474E+10 |
Minimum of Months | 0.161913E+09 | 9039510.68 | 99031058.63 | 0.313609E+09 | 28213617.48 |
Maximum of Months | 0.353611E+09 | 0.247002E+09 | 0.164223E+09 | 0.490739E+09 | 0.438964E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279218E+09 | 0.193965E+09 | 85252967.91 | 0.317934E+09 | 0.325398E+09 |
February | 0.234924E+09 | 0.156728E+09 | 78196598.94 | 0.291257E+09 | 0.241394E+09 |
March | 0.237841E+09 | 0.124808E+09 | 0.113033E+09 | 0.328474E+09 | 0.164068E+09 |
April | 0.173219E+09 | 57791307.85 | 0.115427E+09 | 0.271371E+09 | 0.122514E+09 |
May | 0.143881E+09 | 17607483.41 | 0.126274E+09 | 0.247065E+09 | 69759983.88 |
June | 0.127849E+09 | 7137750.53 | 0.120712E+09 | 0.270733E+09 | 30891949.54 |
July | 0.132523E+09 | 8938883.07 | 0.123585E+09 | 0.299594E+09 | 14790504.75 |
August | 0.159684E+09 | 30010917.68 | 0.129673E+09 | 0.358994E+09 | 7204478.15 |
September | 0.174468E+09 | 67883271.16 | 0.106584E+09 | 0.320677E+09 | 45450411.79 |
October | 0.253151E+09 | 0.163622E+09 | 89529587.28 | 0.387231E+09 | 0.139762E+09 |
November | 0.267657E+09 | 0.178608E+09 | 89049108.36 | 0.365580E+09 | 0.193695E+09 |
December | 0.277252E+09 | 0.195037E+09 | 82215273.99 | 0.340794E+09 | 0.264327E+09 |
Annual Sum or Average | 0.246167E+10 | 0.120214E+10 | 0.125953E+10 | 0.379970E+10 | 0.161926E+10 |
Minimum of Months | 0.127849E+09 | 7137750.53 | 78196598.94 | 0.247065E+09 | 7204478.15 |
Maximum of Months | 0.279218E+09 | 0.195037E+09 | 0.129673E+09 | 0.387231E+09 | 0.325398E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222627E+09 | 0.103516E+09 | 0.119111E+09 | 0.170547E+09 | 0.688179E+09 |
February | 0.230374E+09 | 0.107973E+09 | 0.122401E+09 | 0.232629E+09 | 0.501163E+09 |
March | 0.374198E+09 | 0.180474E+09 | 0.193725E+09 | 0.473537E+09 | 0.317674E+09 |
April | 0.408065E+09 | 0.186640E+09 | 0.221425E+09 | 0.606117E+09 | 0.225436E+09 |
May | 0.424277E+09 | 0.161030E+09 | 0.263246E+09 | 0.704973E+09 | 0.128969E+09 |
June | 0.431370E+09 | 0.166096E+09 | 0.265273E+09 | 0.824110E+09 | 57065885.10 |
July | 0.419570E+09 | 0.155192E+09 | 0.264378E+09 | 0.845670E+09 | 27276406.37 |
August | 0.412124E+09 | 0.154141E+09 | 0.257983E+09 | 0.836243E+09 | 13393754.94 |
September | 0.325820E+09 | 0.136209E+09 | 0.189611E+09 | 0.567225E+09 | 84919736.96 |
October | 0.299566E+09 | 0.155754E+09 | 0.143812E+09 | 0.423635E+09 | 0.275187E+09 |
November | 0.230249E+09 | 0.102964E+09 | 0.127285E+09 | 0.264135E+09 | 0.399594E+09 |
December | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.167521E+09 | 0.559376E+09 |
Annual Sum or Average | 0.397530E+10 | 0.169631E+10 | 0.227899E+10 | 0.611634E+10 | 0.327823E+10 |
Minimum of Months | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.167521E+09 | 13393754.94 |
Maximum of Months | 0.431370E+09 | 0.186640E+09 | 0.265273E+09 | 0.845670E+09 | 0.688179E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52588594.07 | 0.00 | 52588594.07 | 8224126.63 | 0.389872E+09 |
February | 52648446.06 | 0.00 | 52648446.06 | 25601129.03 | 0.279414E+09 |
March | 81855013.60 | 1648.52 | 81853365.08 | 64939348.77 | 0.172223E+09 |
April | 96048332.89 | 560963.03 | 95487369.87 | 0.119468E+09 | 0.119966E+09 |
May | 0.118419E+09 | 3714011.78 | 0.114705E+09 | 0.188043E+09 | 65433502.72 |
June | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.262296E+09 | 28626374.40 |
July | 0.123345E+09 | 6320378.90 | 0.117025E+09 | 0.277737E+09 | 14382431.53 |
August | 0.109554E+09 | 1287040.28 | 0.108267E+09 | 0.256080E+09 | 6951638.13 |
September | 80028430.11 | 31459.51 | 79996970.60 | 0.143336E+09 | 44818415.74 |
October | 62833545.17 | 0.00 | 62833545.17 | 68299192.58 | 0.146125E+09 |
November | 54419711.70 | 0.00 | 54419711.70 | 35906027.30 | 0.213628E+09 |
December | 48614241.33 | 0.00 | 48614241.33 | 11225342.85 | 0.306654E+09 |
Annual Sum or Average | 0.100639E+10 | 20181056.73 | 0.986211E+09 | 0.146115E+10 | 0.178809E+10 |
Minimum of Months | 48614241.33 | 0.00 | 48614241.33 | 8224126.63 | 6951638.13 |
Maximum of Months | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.277737E+09 | 0.389872E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222627E+09 | 0.103516E+09 | 0.119111E+09 | 0.179469E+09 | 0.678285E+09 |
February | 0.230374E+09 | 0.107973E+09 | 0.122401E+09 | 0.242073E+09 | 0.493211E+09 |
March | 0.374198E+09 | 0.180474E+09 | 0.193725E+09 | 0.486272E+09 | 0.310702E+09 |
April | 0.408065E+09 | 0.186640E+09 | 0.221425E+09 | 0.612777E+09 | 0.222881E+09 |
May | 0.424277E+09 | 0.161030E+09 | 0.263246E+09 | 0.707158E+09 | 0.128185E+09 |
June | 0.431370E+09 | 0.166096E+09 | 0.265273E+09 | 0.824398E+09 | 56983129.59 |
July | 0.419570E+09 | 0.155192E+09 | 0.264378E+09 | 0.846332E+09 | 27131646.65 |
August | 0.412124E+09 | 0.154141E+09 | 0.257983E+09 | 0.839437E+09 | 12968039.84 |
September | 0.325820E+09 | 0.136209E+09 | 0.189611E+09 | 0.573016E+09 | 82950776.18 |
October | 0.299566E+09 | 0.155754E+09 | 0.143812E+09 | 0.437077E+09 | 0.268008E+09 |
November | 0.230249E+09 | 0.102964E+09 | 0.127285E+09 | 0.278709E+09 | 0.389094E+09 |
December | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.179703E+09 | 0.548137E+09 |
Annual Sum or Average | 0.397530E+10 | 0.169631E+10 | 0.227899E+10 | 0.620642E+10 | 0.321854E+10 |
Minimum of Months | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.179469E+09 | 12968039.84 |
Maximum of Months | 0.431370E+09 | 0.186640E+09 | 0.265273E+09 | 0.846332E+09 | 0.678285E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.409499E+09 | 0.284468E+09 | 0.125032E+09 | 0.444117E+09 | 0.498220E+09 |
February | 0.344539E+09 | 0.229856E+09 | 0.114683E+09 | 0.411814E+09 | 0.369101E+09 |
March | 0.348816E+09 | 0.183042E+09 | 0.165774E+09 | 0.472586E+09 | 0.246566E+09 |
April | 0.254042E+09 | 84756499.22 | 0.169285E+09 | 0.397720E+09 | 0.178864E+09 |
May | 0.211016E+09 | 25823064.22 | 0.185193E+09 | 0.368748E+09 | 99139845.60 |
June | 0.187503E+09 | 10468196.17 | 0.177035E+09 | 0.408027E+09 | 41874073.95 |
July | 0.194358E+09 | 13109729.90 | 0.181249E+09 | 0.451562E+09 | 19311208.03 |
August | 0.234192E+09 | 44013890.93 | 0.190178E+09 | 0.537745E+09 | 8942510.81 |
September | 0.255873E+09 | 99557331.94 | 0.156316E+09 | 0.472571E+09 | 65697847.46 |
October | 0.371270E+09 | 0.239967E+09 | 0.131304E+09 | 0.559348E+09 | 0.211529E+09 |
November | 0.392545E+09 | 0.261946E+09 | 0.130599E+09 | 0.520218E+09 | 0.297885E+09 |
December | 0.406617E+09 | 0.286040E+09 | 0.120577E+09 | 0.477894E+09 | 0.407539E+09 |
Annual Sum or Average | 0.361027E+10 | 0.176305E+10 | 0.184722E+10 | 0.552235E+10 | 0.244467E+10 |
Minimum of Months | 0.187503E+09 | 10468196.17 | 0.114683E+09 | 0.368748E+09 | 8942510.81 |
Maximum of Months | 0.409499E+09 | 0.286040E+09 | 0.190178E+09 | 0.559348E+09 | 0.498220E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.368106E+09 | 0.00 | 0.368106E+09 | 27685160.83 | 0.339379E+10 |
February | 0.368525E+09 | 0.00 | 0.368525E+09 | 0.116456E+09 | 0.249284E+10 |
March | 0.572963E+09 | 11539.19 | 0.572952E+09 | 0.321380E+09 | 0.163000E+10 |
April | 0.672313E+09 | 3926592.47 | 0.668386E+09 | 0.699643E+09 | 0.114215E+10 |
May | 0.828899E+09 | 25997097.83 | 0.802902E+09 | 0.116257E+10 | 0.696789E+09 |
June | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.166493E+10 | 0.368941E+09 |
July | 0.863385E+09 | 44240976.70 | 0.819144E+09 | 0.175671E+10 | 0.249355E+09 |
August | 0.766846E+09 | 9008940.72 | 0.757837E+09 | 0.160331E+10 | 0.190217E+09 |
September | 0.560178E+09 | 220208.23 | 0.559958E+09 | 0.860622E+09 | 0.554307E+09 |
October | 0.439818E+09 | 0.00 | 0.439818E+09 | 0.356637E+09 | 0.143595E+10 |
November | 0.380924E+09 | 0.00 | 0.380924E+09 | 0.143489E+09 | 0.198575E+10 |
December | 0.340287E+09 | 0.00 | 0.340287E+09 | 26418006.39 | 0.280088E+10 |
Annual Sum or Average | 0.704448E+10 | 0.141262E+09 | 0.690322E+10 | 0.873986E+10 | 0.169410E+11 |
Minimum of Months | 0.340287E+09 | 0.00 | 0.340287E+09 | 26418006.39 | 0.190217E+09 |
Maximum of Months | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.175671E+10 | 0.339379E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.368106E+09 | 0.00 | 0.368106E+09 | 23380341.22 | 0.350078E+10 |
February | 0.368525E+09 | 0.00 | 0.368525E+09 | 0.105707E+09 | 0.257376E+10 |
March | 0.572963E+09 | 11539.19 | 0.572952E+09 | 0.295472E+09 | 0.168543E+10 |
April | 0.672313E+09 | 3926592.47 | 0.668386E+09 | 0.671383E+09 | 0.117586E+10 |
May | 0.828899E+09 | 25997097.83 | 0.802902E+09 | 0.113390E+10 | 0.719291E+09 |
June | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.163988E+10 | 0.383269E+09 |
July | 0.863385E+09 | 44240976.70 | 0.819144E+09 | 0.173141E+10 | 0.262387E+09 |
August | 0.766846E+09 | 9008940.72 | 0.757837E+09 | 0.157876E+10 | 0.203078E+09 |
September | 0.560178E+09 | 220208.23 | 0.559958E+09 | 0.837623E+09 | 0.577801E+09 |
October | 0.439818E+09 | 0.00 | 0.439818E+09 | 0.335593E+09 | 0.148570E+10 |
November | 0.380924E+09 | 0.00 | 0.380924E+09 | 0.125134E+09 | 0.205378E+10 |
December | 0.340287E+09 | 0.00 | 0.340287E+09 | 21849634.67 | 0.289903E+10 |
Annual Sum or Average | 0.704448E+10 | 0.141262E+09 | 0.690322E+10 | 0.850009E+10 | 0.175202E+11 |
Minimum of Months | 0.340287E+09 | 0.00 | 0.340287E+09 | 21849634.67 | 0.203078E+09 |
Maximum of Months | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.173141E+10 | 0.350078E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52588594.07 | 0.00 | 52588594.07 | 5601087.82 | 0.467612E+09 |
February | 52648446.06 | 0.00 | 52648446.06 | 21302805.61 | 0.343622E+09 |
March | 81855013.60 | 1648.52 | 81853365.08 | 61431239.99 | 0.223665E+09 |
April | 96048332.89 | 560963.03 | 95487369.87 | 0.128077E+09 | 0.158019E+09 |
May | 0.118419E+09 | 3714011.78 | 0.114705E+09 | 0.207858E+09 | 0.100687E+09 |
June | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.284553E+09 | 57741587.42 |
July | 0.123345E+09 | 6320378.90 | 0.117025E+09 | 0.302882E+09 | 40367861.52 |
August | 0.109554E+09 | 1287040.28 | 0.108267E+09 | 0.280163E+09 | 31695512.18 |
September | 80028430.11 | 31459.51 | 79996970.60 | 0.159156E+09 | 75756236.87 |
October | 62833545.17 | 0.00 | 62833545.17 | 69678484.83 | 0.194344E+09 |
November | 54419711.70 | 0.00 | 54419711.70 | 30818899.06 | 0.268736E+09 |
December | 48614241.33 | 0.00 | 48614241.33 | 6038979.41 | 0.382800E+09 |
Annual Sum or Average | 0.100639E+10 | 20181056.73 | 0.986211E+09 | 0.155756E+10 | 0.234505E+10 |
Minimum of Months | 48614241.33 | 0.00 | 48614241.33 | 5601087.82 | 31695512.18 |
Maximum of Months | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.302882E+09 | 0.467612E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.434507E+09 | 0.197839E+09 | 0.236668E+09 | 0.271343E+09 | 0.157226E+10 |
February | 0.492555E+09 | 0.265149E+09 | 0.227406E+09 | 0.460019E+09 | 0.115095E+10 |
March | 0.686097E+09 | 0.312962E+09 | 0.373136E+09 | 0.816776E+09 | 0.760490E+09 |
April | 0.802608E+09 | 0.366340E+09 | 0.436268E+09 | 0.121767E+10 | 0.553381E+09 |
May | 0.908547E+09 | 0.384217E+09 | 0.524331E+09 | 0.157844E+10 | 0.370553E+09 |
June | 0.909412E+09 | 0.380907E+09 | 0.528506E+09 | 0.182045E+10 | 0.214855E+09 |
July | 0.915938E+09 | 0.384279E+09 | 0.531659E+09 | 0.191883E+10 | 0.151982E+09 |
August | 0.839504E+09 | 0.333007E+09 | 0.506497E+09 | 0.180187E+10 | 0.119291E+09 |
September | 0.665833E+09 | 0.294206E+09 | 0.371628E+09 | 0.123638E+10 | 0.277269E+09 |
October | 0.588469E+09 | 0.306304E+09 | 0.282165E+09 | 0.832288E+09 | 0.673331E+09 |
November | 0.453550E+09 | 0.204592E+09 | 0.248958E+09 | 0.462220E+09 | 0.901439E+09 |
December | 0.406705E+09 | 0.185132E+09 | 0.221573E+09 | 0.273408E+09 | 0.127608E+10 |
Annual Sum or Average | 0.810373E+10 | 0.361493E+10 | 0.448879E+10 | 0.126897E+11 | 0.802189E+10 |
Minimum of Months | 0.406705E+09 | 0.185132E+09 | 0.221573E+09 | 0.271343E+09 | 0.119291E+09 |
Maximum of Months | 0.915938E+09 | 0.384279E+09 | 0.531659E+09 | 0.191883E+10 | 0.157226E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279218E+09 | 0.193965E+09 | 85252967.91 | 0.309646E+09 | 0.379519E+09 |
February | 0.234924E+09 | 0.156728E+09 | 78196598.94 | 0.287480E+09 | 0.290435E+09 |
March | 0.237841E+09 | 0.124808E+09 | 0.113033E+09 | 0.333617E+09 | 0.208030E+09 |
April | 0.173219E+09 | 57791307.85 | 0.115427E+09 | 0.285163E+09 | 0.158380E+09 |
May | 0.143881E+09 | 17607483.41 | 0.126274E+09 | 0.269636E+09 | 0.104298E+09 |
June | 0.127849E+09 | 7137750.53 | 0.120712E+09 | 0.294633E+09 | 60362513.11 |
July | 0.132523E+09 | 8938883.07 | 0.123585E+09 | 0.324967E+09 | 41058626.03 |
August | 0.159684E+09 | 30010917.68 | 0.129673E+09 | 0.385336E+09 | 31808647.66 |
September | 0.174468E+09 | 67883271.16 | 0.106584E+09 | 0.342795E+09 | 74776923.17 |
October | 0.253151E+09 | 0.163622E+09 | 89529587.28 | 0.399742E+09 | 0.180891E+09 |
November | 0.267657E+09 | 0.178608E+09 | 89049108.36 | 0.369710E+09 | 0.235953E+09 |
December | 0.277252E+09 | 0.195037E+09 | 82215273.99 | 0.334720E+09 | 0.317762E+09 |
Annual Sum or Average | 0.246167E+10 | 0.120214E+10 | 0.125953E+10 | 0.393745E+10 | 0.208328E+10 |
Minimum of Months | 0.127849E+09 | 7137750.53 | 78196598.94 | 0.269636E+09 | 31808647.66 |
Maximum of Months | 0.279218E+09 | 0.195037E+09 | 0.129673E+09 | 0.399742E+09 | 0.379519E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66600136.23 | 0.00 | 66600136.23 | 7329313.58 | 0.551938E+09 |
February | 66675935.00 | 0.00 | 66675935.00 | 26191174.51 | 0.396953E+09 |
March | 0.103664E+09 | 2087.74 | 0.103662E+09 | 71036612.16 | 0.249567E+09 |
April | 0.121639E+09 | 710424.28 | 0.120929E+09 | 0.140274E+09 | 0.180030E+09 |
May | 0.149970E+09 | 4703561.58 | 0.145266E+09 | 0.222428E+09 | 0.111964E+09 |
June | 0.159620E+09 | 10467803.52 | 0.149152E+09 | 0.306647E+09 | 61746966.57 |
July | 0.156209E+09 | 8004361.08 | 0.148205E+09 | 0.321038E+09 | 41049105.53 |
August | 0.138743E+09 | 1629955.30 | 0.137113E+09 | 0.291252E+09 | 31548067.82 |
September | 0.101351E+09 | 39841.48 | 0.101311E+09 | 0.162069E+09 | 88890277.06 |
October | 79574720.39 | 0.00 | 79574720.39 | 73009823.29 | 0.222372E+09 |
November | 68919131.17 | 0.00 | 68919131.17 | 34790008.44 | 0.308071E+09 |
December | 61566869.25 | 0.00 | 61566869.25 | 7446731.16 | 0.440478E+09 |
Annual Sum or Average | 0.127453E+10 | 25558034.99 | 0.124897E+10 | 0.166351E+10 | 0.268461E+10 |
Minimum of Months | 61566869.25 | 0.00 | 61566869.25 | 7329313.58 | 31548067.82 |
Maximum of Months | 0.159620E+09 | 10467803.52 | 0.149152E+09 | 0.321038E+09 | 0.551938E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59587394.23 | 0.00 | 59587394.23 | 6557564.63 | 0.493812E+09 |
February | 59655211.68 | 0.00 | 59655211.68 | 23433343.07 | 0.355156E+09 |
March | 92748761.43 | 1867.91 | 92746893.52 | 63556726.06 | 0.223289E+09 |
April | 0.108831E+09 | 635619.29 | 0.108195E+09 | 0.125504E+09 | 0.161073E+09 |
May | 0.134178E+09 | 4208294.36 | 0.129970E+09 | 0.199007E+09 | 0.100175E+09 |
June | 0.142813E+09 | 9365583.47 | 0.133447E+09 | 0.274358E+09 | 55245244.95 |
July | 0.139761E+09 | 7161532.19 | 0.132599E+09 | 0.287234E+09 | 36726790.25 |
August | 0.124134E+09 | 1458327.18 | 0.122675E+09 | 0.260584E+09 | 28226175.82 |
September | 90679085.44 | 35646.33 | 90643439.12 | 0.145003E+09 | 79530467.69 |
October | 71195803.84 | 0.00 | 71195803.84 | 65322165.53 | 0.198957E+09 |
November | 61662207.79 | 0.00 | 61662207.79 | 31126752.37 | 0.275630E+09 |
December | 55084111.20 | 0.00 | 55084111.20 | 6662618.58 | 0.394082E+09 |
Annual Sum or Average | 0.114033E+10 | 22866870.75 | 0.111746E+10 | 0.148835E+10 | 0.240190E+10 |
Minimum of Months | 55084111.20 | 0.00 | 55084111.20 | 6557564.63 | 28226175.82 |
Maximum of Months | 0.142813E+09 | 9365583.47 | 0.133447E+09 | 0.287234E+09 | 0.493812E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104240E+10 | 0.724128E+09 | 0.318275E+09 | 0.114639E+10 | 0.131687E+10 |
February | 0.877042E+09 | 0.585111E+09 | 0.291931E+09 | 0.106006E+10 | 0.986437E+09 |
March | 0.887931E+09 | 0.465944E+09 | 0.421987E+09 | 0.120742E+10 | 0.684334E+09 |
April | 0.646677E+09 | 0.215752E+09 | 0.430925E+09 | 0.990648E+09 | 0.535474E+09 |
May | 0.537152E+09 | 65733982.34 | 0.471418E+09 | 0.884242E+09 | 0.350439E+09 |
June | 0.477300E+09 | 26647349.68 | 0.450653E+09 | 0.941412E+09 | 0.196947E+09 |
July | 0.494749E+09 | 33371514.17 | 0.461378E+09 | 0.103295E+10 | 0.127521E+09 |
August | 0.596149E+09 | 0.112040E+09 | 0.484109E+09 | 0.124938E+10 | 95627099.20 |
September | 0.651339E+09 | 0.253428E+09 | 0.397911E+09 | 0.114863E+10 | 0.260494E+09 |
October | 0.945089E+09 | 0.610848E+09 | 0.334241E+09 | 0.142194E+10 | 0.609297E+09 |
November | 0.999244E+09 | 0.666797E+09 | 0.332447E+09 | 0.134493E+10 | 0.795223E+09 |
December | 0.103506E+10 | 0.728130E+09 | 0.306934E+09 | 0.123630E+10 | 0.107643E+10 |
Annual Sum or Average | 0.919014E+10 | 0.448793E+10 | 0.470221E+10 | 0.136643E+11 | 0.703509E+10 |
Minimum of Months | 0.477300E+09 | 26647349.68 | 0.291931E+09 | 0.884242E+09 | 95627099.20 |
Maximum of Months | 0.104240E+10 | 0.728130E+09 | 0.484109E+09 | 0.142194E+10 | 0.131687E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 595.59 | 607.53 | 527.26 | 366.27 | 160.99 | 0.00 | 0.00 |
February | 605.86 | 505.79 | 491.15 | 327.66 | 163.48 | 0.00 | 0.00 |
March | 619.31 | 326.48 | 449.12 | 235.68 | 213.44 | 0.00 | 0.00 |
April | 527.85 | 257.89 | 338.00 | 112.77 | 225.23 | 0.00 | 0.00 |
May | 457.37 | 160.74 | 271.69 | 33.25 | 238.45 | 0.00 | 0.00 |
June | 490.51 | 97.79 | 249.47 | 13.93 | 235.54 | 0.00 | 0.00 |
July | 516.85 | 62.41 | 250.25 | 16.88 | 233.37 | 0.00 | 0.00 |
August | 622.49 | 51.34 | 301.54 | 56.67 | 244.87 | 0.00 | 0.00 |
September | 600.53 | 129.68 | 340.43 | 132.46 | 207.97 | 0.00 | 0.00 |
October | 719.80 | 292.36 | 478.03 | 308.97 | 169.06 | 0.00 | 0.00 |
November | 704.22 | 394.01 | 522.27 | 348.52 | 173.76 | 0.00 | 0.00 |
December | 635.78 | 504.41 | 523.54 | 368.30 | 155.25 | 0.00 | 0.00 |
Annual Sum or Average | 591.34 | 281.39 | 394.80 | 192.80 | 202.00 | 0.00 | 0.00 |
Minimum of Months | 457.37 | 51.34 | 249.47 | 13.93 | 155.25 | 0.00 | 0.00 |
Maximum of Months | 719.80 | 607.53 | 527.26 | 368.30 | 244.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1639.67 | 1809.59 | 1484.72 | 1031.40 | 453.32 | 0.00 | 0.00 |
February | 1667.81 | 1535.83 | 1383.03 | 922.68 | 460.35 | 0.00 | 0.00 |
March | 1697.97 | 1030.33 | 1264.70 | 663.66 | 601.04 | 0.00 | 0.00 |
April | 1444.30 | 815.71 | 951.78 | 317.55 | 634.23 | 0.00 | 0.00 |
May | 1250.61 | 518.11 | 765.07 | 93.63 | 671.45 | 0.00 | 0.00 |
June | 1364.18 | 302.70 | 702.49 | 39.22 | 663.27 | 0.00 | 0.00 |
July | 1442.64 | 195.56 | 704.68 | 47.53 | 657.15 | 0.00 | 0.00 |
August | 1743.63 | 156.07 | 849.11 | 159.58 | 689.52 | 0.00 | 0.00 |
September | 1665.25 | 414.75 | 958.64 | 373.00 | 585.64 | 0.00 | 0.00 |
October | 1989.33 | 922.48 | 1346.11 | 870.05 | 476.06 | 0.00 | 0.00 |
November | 1935.64 | 1232.64 | 1470.69 | 981.40 | 489.29 | 0.00 | 0.00 |
December | 1749.28 | 1536.77 | 1474.27 | 1037.10 | 437.17 | 0.00 | 0.00 |
Annual Sum or Average | 1632.57 | 869.08 | 1111.73 | 542.91 | 568.82 | 0.00 | 0.00 |
Minimum of Months | 1250.61 | 156.07 | 702.49 | 39.22 | 437.17 | 0.00 | 0.00 |
Maximum of Months | 1989.33 | 1809.59 | 1484.72 | 1037.10 | 689.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2168.74 | 2456.99 | 1928.74 | 1339.84 | 588.89 | 0.00 | 0.00 |
February | 2210.99 | 2080.97 | 1796.64 | 1198.62 | 598.02 | 0.00 | 0.00 |
March | 2255.45 | 1382.92 | 1642.92 | 862.13 | 780.79 | 0.00 | 0.00 |
April | 1917.69 | 1097.32 | 1236.41 | 412.51 | 823.90 | 0.00 | 0.00 |
May | 1663.94 | 691.29 | 993.87 | 121.63 | 872.25 | 0.00 | 0.00 |
June | 1822.23 | 397.71 | 912.57 | 50.95 | 861.62 | 0.00 | 0.00 |
July | 1930.83 | 254.17 | 915.42 | 61.75 | 853.67 | 0.00 | 0.00 |
August | 2334.79 | 197.00 | 1103.04 | 207.31 | 895.73 | 0.00 | 0.00 |
September | 2214.13 | 547.44 | 1245.33 | 484.54 | 760.78 | 0.00 | 0.00 |
October | 2640.68 | 1237.82 | 1748.68 | 1130.24 | 618.43 | 0.00 | 0.00 |
November | 2561.90 | 1660.87 | 1910.51 | 1274.89 | 635.62 | 0.00 | 0.00 |
December | 2312.94 | 2088.05 | 1915.16 | 1347.25 | 567.91 | 0.00 | 0.00 |
Annual Sum or Average | 2169.63 | 1169.65 | 1444.20 | 705.27 | 738.93 | 0.00 | 0.00 |
Minimum of Months | 1663.94 | 197.00 | 912.57 | 50.95 | 567.91 | 0.00 | 0.00 |
Maximum of Months | 2640.68 | 2456.99 | 1928.74 | 1347.25 | 895.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 164.09 | 361.52 | 187.37 | 111.07 | 76.30 | 0.00 | 0.00 |
February | 203.69 | 295.37 | 192.34 | 109.42 | 82.92 | 0.00 | 0.00 |
March | 297.85 | 179.22 | 228.51 | 113.98 | 114.53 | 0.00 | 0.00 |
April | 339.93 | 135.25 | 224.26 | 94.30 | 129.96 | 0.00 | 0.00 |
May | 358.59 | 75.78 | 212.13 | 66.70 | 145.43 | 0.00 | 0.00 |
June | 425.01 | 35.66 | 215.75 | 66.83 | 148.91 | 0.00 | 0.00 |
July | 429.73 | 17.07 | 206.13 | 61.28 | 144.85 | 0.00 | 0.00 |
August | 448.35 | 8.78 | 213.49 | 68.75 | 144.73 | 0.00 | 0.00 |
September | 344.06 | 52.59 | 193.01 | 78.74 | 114.27 | 0.00 | 0.00 |
October | 301.21 | 155.49 | 206.36 | 119.24 | 87.12 | 0.00 | 0.00 |
November | 235.42 | 224.36 | 192.09 | 108.63 | 83.46 | 0.00 | 0.00 |
December | 174.65 | 295.15 | 177.09 | 105.05 | 72.04 | 0.00 | 0.00 |
Annual Sum or Average | 310.81 | 152.30 | 204.11 | 91.91 | 112.21 | 0.00 | 0.00 |
Minimum of Months | 164.09 | 8.78 | 177.09 | 61.28 | 72.04 | 0.00 | 0.00 |
Maximum of Months | 448.35 | 361.52 | 228.51 | 119.24 | 148.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 62.16 | 392.15 | 102.75 | 38.65 | 64.11 | 0.00 | 0.00 |
February | 105.28 | 316.29 | 116.99 | 44.63 | 72.36 | 0.00 | 0.00 |
March | 204.71 | 182.15 | 170.27 | 67.38 | 102.89 | 0.00 | 0.00 |
April | 283.57 | 133.92 | 194.49 | 72.22 | 122.27 | 0.00 | 0.00 |
May | 336.74 | 73.51 | 202.62 | 61.51 | 141.11 | 0.00 | 0.00 |
June | 421.14 | 34.07 | 215.05 | 67.27 | 147.78 | 0.00 | 0.00 |
July | 421.51 | 16.60 | 202.70 | 60.30 | 142.40 | 0.00 | 0.00 |
August | 410.67 | 8.49 | 194.77 | 58.03 | 136.74 | 0.00 | 0.00 |
September | 277.12 | 51.78 | 156.58 | 52.56 | 104.02 | 0.00 | 0.00 |
October | 187.49 | 157.86 | 135.30 | 58.15 | 77.15 | 0.00 | 0.00 |
November | 118.84 | 235.09 | 109.83 | 39.72 | 70.10 | 0.00 | 0.00 |
December | 66.61 | 318.26 | 91.72 | 32.23 | 59.50 | 0.00 | 0.00 |
Annual Sum or Average | 242.07 | 159.24 | 157.97 | 54.43 | 103.54 | 0.00 | 0.00 |
Minimum of Months | 62.16 | 8.49 | 91.72 | 32.23 | 59.50 | 0.00 | 0.00 |
Maximum of Months | 421.51 | 392.15 | 215.05 | 72.22 | 147.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 94.04 | 96.10 | 83.38 | 57.92 | 25.46 | 0.00 | 0.00 |
February | 95.17 | 81.04 | 77.67 | 51.82 | 25.85 | 0.00 | 0.00 |
March | 95.38 | 56.65 | 71.03 | 37.27 | 33.75 | 0.00 | 0.00 |
April | 81.85 | 44.67 | 53.45 | 17.83 | 35.62 | 0.00 | 0.00 |
May | 72.15 | 27.01 | 42.97 | 5.26 | 37.71 | 0.00 | 0.00 |
June | 81.15 | 14.30 | 39.45 | 2.20 | 37.25 | 0.00 | 0.00 |
July | 86.52 | 8.35 | 39.57 | 2.67 | 36.91 | 0.00 | 0.00 |
August | 103.89 | 5.76 | 47.69 | 8.96 | 38.72 | 0.00 | 0.00 |
September | 96.36 | 20.52 | 53.84 | 20.95 | 32.89 | 0.00 | 0.00 |
October | 112.78 | 50.29 | 75.60 | 48.86 | 26.74 | 0.00 | 0.00 |
November | 108.79 | 69.30 | 82.59 | 55.11 | 27.48 | 0.00 | 0.00 |
December | 99.00 | 83.59 | 82.79 | 58.24 | 24.55 | 0.00 | 0.00 |
Annual Sum or Average | 93.93 | 46.28 | 62.43 | 30.49 | 31.95 | 0.00 | 0.00 |
Minimum of Months | 72.15 | 5.76 | 39.45 | 2.20 | 24.55 | 0.00 | 0.00 |
Maximum of Months | 112.78 | 96.10 | 83.38 | 58.24 | 38.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.15 | 122.04 | 15.71 | 0.00 | 15.71 | 0.00 | 0.00 |
February | 8.30 | 96.58 | 17.41 | 0.00 | 17.41 | 0.00 | 0.00 |
March | 20.39 | 52.44 | 24.45 | 0.00 | 24.45 | 0.00 | 0.00 |
April | 39.81 | 36.61 | 29.65 | 0.17 | 29.48 | 0.00 | 0.00 |
May | 60.67 | 18.56 | 35.37 | 1.11 | 34.27 | 0.00 | 0.00 |
June | 86.43 | 7.86 | 38.91 | 2.55 | 36.35 | 0.00 | 0.00 |
July | 88.76 | 3.54 | 36.85 | 1.89 | 34.96 | 0.00 | 0.00 |
August | 82.78 | 1.52 | 32.73 | 0.38 | 32.34 | 0.00 | 0.00 |
September | 48.31 | 13.11 | 24.70 | 0.01 | 24.69 | 0.00 | 0.00 |
October | 21.66 | 44.58 | 18.77 | 0.00 | 18.77 | 0.00 | 0.00 |
November | 10.87 | 68.81 | 16.80 | 0.00 | 16.80 | 0.00 | 0.00 |
December | 2.70 | 96.82 | 14.52 | 0.00 | 14.52 | 0.00 | 0.00 |
Annual Sum or Average | 39.58 | 46.63 | 25.53 | 0.51 | 25.02 | 0.00 | 0.00 |
Minimum of Months | 2.15 | 1.52 | 14.52 | 0.00 | 14.52 | 0.00 | 0.00 |
Maximum of Months | 88.76 | 122.04 | 38.91 | 2.55 | 36.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 156.01 | 356.25 | 185.37 | 109.35 | 76.01 | 0.00 | 0.00 |
February | 207.19 | 288.68 | 198.92 | 119.59 | 79.33 | 0.00 | 0.00 |
March | 268.70 | 170.63 | 216.89 | 105.03 | 111.86 | 0.00 | 0.00 |
April | 325.05 | 125.72 | 221.66 | 92.97 | 128.69 | 0.00 | 0.00 |
May | 369.66 | 70.11 | 223.34 | 78.30 | 145.03 | 0.00 | 0.00 |
June | 436.38 | 32.46 | 224.76 | 76.24 | 148.53 | 0.00 | 0.00 |
July | 451.87 | 16.37 | 220.48 | 75.08 | 145.40 | 0.00 | 0.00 |
August | 453.22 | 8.25 | 216.35 | 73.37 | 142.97 | 0.00 | 0.00 |
September | 346.47 | 50.25 | 195.76 | 82.95 | 112.81 | 0.00 | 0.00 |
October | 290.32 | 149.14 | 204.38 | 118.27 | 86.10 | 0.00 | 0.00 |
November | 225.44 | 216.69 | 190.76 | 108.38 | 82.38 | 0.00 | 0.00 |
December | 172.07 | 288.46 | 179.44 | 107.38 | 72.06 | 0.00 | 0.00 |
Annual Sum or Average | 309.09 | 147.05 | 206.55 | 95.44 | 111.11 | 0.00 | 0.00 |
Minimum of Months | 156.01 | 8.25 | 179.44 | 73.37 | 72.06 | 0.00 | 0.00 |
Maximum of Months | 453.22 | 356.25 | 224.76 | 119.59 | 148.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 46.93 | 379.41 | 100.75 | 36.93 | 63.82 | 0.00 | 0.00 |
February | 98.37 | 298.98 | 123.57 | 54.80 | 68.77 | 0.00 | 0.00 |
March | 171.18 | 169.09 | 158.65 | 58.43 | 100.22 | 0.00 | 0.00 |
April | 267.84 | 124.08 | 191.89 | 70.89 | 121.00 | 0.00 | 0.00 |
May | 349.03 | 69.33 | 213.83 | 73.12 | 140.71 | 0.00 | 0.00 |
June | 433.94 | 32.30 | 224.07 | 76.67 | 147.39 | 0.00 | 0.00 |
July | 444.05 | 16.30 | 217.05 | 74.10 | 142.95 | 0.00 | 0.00 |
August | 415.54 | 8.06 | 197.63 | 62.65 | 134.98 | 0.00 | 0.00 |
September | 278.93 | 49.35 | 159.32 | 56.77 | 102.56 | 0.00 | 0.00 |
October | 171.60 | 147.21 | 133.32 | 57.18 | 76.14 | 0.00 | 0.00 |
November | 98.77 | 216.72 | 108.49 | 39.47 | 69.02 | 0.00 | 0.00 |
December | 50.65 | 297.89 | 94.08 | 34.56 | 59.52 | 0.00 | 0.00 |
Annual Sum or Average | 236.32 | 150.00 | 160.41 | 57.96 | 102.45 | 0.00 | 0.00 |
Minimum of Months | 46.93 | 8.06 | 94.08 | 34.56 | 59.52 | 0.00 | 0.00 |
Maximum of Months | 444.05 | 379.41 | 224.07 | 76.67 | 147.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 172.80 | 465.61 | 214.70 | 125.50 | 89.19 | 0.00 | 0.00 |
February | 201.73 | 382.86 | 206.01 | 112.27 | 93.74 | 0.00 | 0.00 |
March | 249.40 | 239.46 | 206.86 | 80.76 | 126.11 | 0.00 | 0.00 |
April | 260.57 | 187.70 | 180.04 | 39.01 | 141.03 | 0.00 | 0.00 |
May | 279.70 | 111.23 | 169.73 | 13.80 | 155.93 | 0.00 | 0.00 |
June | 343.32 | 62.04 | 169.76 | 10.30 | 159.46 | 0.00 | 0.00 |
July | 355.67 | 38.71 | 165.57 | 9.87 | 155.70 | 0.00 | 0.00 |
August | 378.49 | 28.34 | 174.22 | 20.25 | 153.97 | 0.00 | 0.00 |
September | 300.73 | 90.39 | 170.17 | 45.41 | 124.76 | 0.00 | 0.00 |
October | 286.09 | 213.82 | 204.46 | 105.87 | 98.59 | 0.00 | 0.00 |
November | 253.72 | 290.02 | 215.35 | 119.42 | 95.93 | 0.00 | 0.00 |
December | 199.19 | 378.53 | 210.85 | 126.20 | 84.66 | 0.00 | 0.00 |
Annual Sum or Average | 273.86 | 206.50 | 190.59 | 67.17 | 123.42 | 0.00 | 0.00 |
Minimum of Months | 172.80 | 28.34 | 165.57 | 9.87 | 84.66 | 0.00 | 0.00 |
Maximum of Months | 378.49 | 465.61 | 215.35 | 126.20 | 159.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 163.95 | 360.00 | 187.37 | 111.07 | 76.30 | 0.00 | 0.00 |
February | 202.87 | 293.26 | 192.34 | 109.42 | 82.92 | 0.00 | 0.00 |
March | 295.82 | 176.24 | 228.51 | 113.98 | 114.53 | 0.00 | 0.00 |
April | 337.24 | 132.94 | 224.26 | 94.30 | 129.96 | 0.00 | 0.00 |
May | 355.25 | 74.00 | 212.13 | 66.70 | 145.43 | 0.00 | 0.00 |
June | 422.36 | 33.90 | 215.75 | 66.83 | 148.91 | 0.00 | 0.00 |
July | 427.58 | 15.69 | 206.13 | 61.28 | 144.85 | 0.00 | 0.00 |
August | 446.25 | 7.69 | 213.49 | 68.75 | 144.73 | 0.00 | 0.00 |
September | 342.44 | 50.18 | 193.01 | 78.74 | 114.27 | 0.00 | 0.00 |
October | 299.87 | 152.05 | 206.36 | 119.24 | 87.12 | 0.00 | 0.00 |
November | 235.12 | 221.06 | 192.09 | 108.63 | 83.46 | 0.00 | 0.00 |
December | 174.77 | 292.52 | 177.09 | 105.05 | 72.04 | 0.00 | 0.00 |
Annual Sum or Average | 309.21 | 150.08 | 204.11 | 91.91 | 112.21 | 0.00 | 0.00 |
Minimum of Months | 163.95 | 7.69 | 177.09 | 61.28 | 72.04 | 0.00 | 0.00 |
Maximum of Months | 446.25 | 360.00 | 228.51 | 119.24 | 148.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 62.37 | 391.10 | 102.75 | 38.65 | 64.11 | 0.00 | 0.00 |
February | 105.29 | 314.02 | 116.99 | 44.63 | 72.36 | 0.00 | 0.00 |
March | 204.15 | 178.65 | 170.27 | 67.38 | 102.89 | 0.00 | 0.00 |
April | 281.71 | 131.47 | 194.49 | 72.22 | 122.27 | 0.00 | 0.00 |
May | 333.73 | 71.79 | 202.62 | 61.51 | 141.11 | 0.00 | 0.00 |
June | 418.62 | 32.40 | 215.05 | 67.27 | 147.78 | 0.00 | 0.00 |
July | 419.48 | 15.30 | 202.70 | 60.30 | 142.40 | 0.00 | 0.00 |
August | 409.00 | 7.42 | 194.77 | 58.03 | 136.74 | 0.00 | 0.00 |
September | 276.30 | 49.23 | 156.58 | 52.56 | 104.02 | 0.00 | 0.00 |
October | 187.79 | 153.72 | 135.30 | 58.15 | 77.15 | 0.00 | 0.00 |
November | 119.88 | 231.03 | 109.83 | 39.72 | 70.10 | 0.00 | 0.00 |
December | 67.61 | 315.47 | 91.72 | 32.23 | 59.50 | 0.00 | 0.00 |
Annual Sum or Average | 241.24 | 156.86 | 157.97 | 54.43 | 103.54 | 0.00 | 0.00 |
Minimum of Months | 62.37 | 7.42 | 91.72 | 32.23 | 59.50 | 0.00 | 0.00 |
Maximum of Months | 419.48 | 391.10 | 215.05 | 72.22 | 147.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 165.81 | 186.01 | 152.89 | 106.21 | 46.68 | 0.00 | 0.00 |
February | 170.23 | 152.57 | 142.42 | 95.01 | 47.41 | 0.00 | 0.00 |
March | 176.44 | 92.06 | 130.23 | 68.34 | 61.89 | 0.00 | 0.00 |
April | 153.44 | 69.01 | 98.01 | 32.70 | 65.31 | 0.00 | 0.00 |
May | 137.67 | 37.01 | 78.78 | 9.64 | 69.14 | 0.00 | 0.00 |
June | 157.42 | 16.16 | 72.34 | 4.04 | 68.30 | 0.00 | 0.00 |
July | 168.59 | 7.21 | 72.57 | 4.89 | 67.67 | 0.00 | 0.00 |
August | 200.77 | 3.34 | 87.44 | 16.43 | 71.00 | 0.00 | 0.00 |
September | 182.32 | 25.35 | 98.72 | 38.41 | 60.31 | 0.00 | 0.00 |
October | 208.84 | 78.98 | 138.62 | 89.59 | 49.02 | 0.00 | 0.00 |
November | 200.70 | 114.92 | 151.44 | 101.06 | 50.39 | 0.00 | 0.00 |
December | 178.42 | 152.16 | 151.81 | 106.80 | 45.02 | 0.00 | 0.00 |
Annual Sum or Average | 175.11 | 77.52 | 114.48 | 55.91 | 58.58 | 0.00 | 0.00 |
Minimum of Months | 137.67 | 3.34 | 72.34 | 4.04 | 45.02 | 0.00 | 0.00 |
Maximum of Months | 208.84 | 186.01 | 152.89 | 106.80 | 71.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.34 | 1267.10 | 137.44 | 0.00 | 137.44 | 0.00 | 0.00 |
February | 48.14 | 1030.44 | 152.33 | 0.00 | 152.33 | 0.00 | 0.00 |
March | 119.99 | 608.57 | 213.92 | 0.00 | 213.92 | 0.00 | 0.00 |
April | 269.92 | 440.65 | 259.38 | 1.51 | 257.87 | 0.00 | 0.00 |
May | 434.05 | 260.15 | 309.48 | 9.71 | 299.77 | 0.00 | 0.00 |
June | 642.33 | 142.34 | 340.37 | 22.32 | 318.05 | 0.00 | 0.00 |
July | 655.88 | 93.10 | 322.35 | 16.52 | 305.83 | 0.00 | 0.00 |
August | 598.61 | 71.02 | 286.31 | 3.36 | 282.94 | 0.00 | 0.00 |
September | 332.03 | 213.85 | 216.12 | 0.08 | 216.03 | 0.00 | 0.00 |
October | 133.15 | 536.12 | 164.21 | 0.00 | 164.21 | 0.00 | 0.00 |
November | 55.36 | 766.11 | 146.96 | 0.00 | 146.96 | 0.00 | 0.00 |
December | 9.86 | 1045.73 | 127.05 | 0.00 | 127.05 | 0.00 | 0.00 |
Annual Sum or Average | 277.14 | 537.19 | 223.38 | 4.48 | 218.90 | 0.00 | 0.00 |
Minimum of Months | 9.86 | 71.02 | 127.05 | 0.00 | 127.05 | 0.00 | 0.00 |
Maximum of Months | 655.88 | 1267.10 | 340.37 | 22.32 | 318.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 8.73 | 1307.04 | 137.44 | 0.00 | 137.44 | 0.00 | 0.00 |
February | 43.70 | 1063.89 | 152.33 | 0.00 | 152.33 | 0.00 | 0.00 |
March | 110.32 | 629.27 | 213.92 | 0.00 | 213.92 | 0.00 | 0.00 |
April | 259.02 | 453.65 | 259.38 | 1.51 | 257.87 | 0.00 | 0.00 |
May | 423.35 | 268.55 | 309.48 | 9.71 | 299.77 | 0.00 | 0.00 |
June | 632.67 | 147.87 | 340.37 | 22.32 | 318.05 | 0.00 | 0.00 |
July | 646.43 | 97.96 | 322.35 | 16.52 | 305.83 | 0.00 | 0.00 |
August | 589.44 | 75.82 | 286.31 | 3.36 | 282.94 | 0.00 | 0.00 |
September | 323.16 | 222.92 | 216.12 | 0.08 | 216.03 | 0.00 | 0.00 |
October | 125.30 | 554.70 | 164.21 | 0.00 | 164.21 | 0.00 | 0.00 |
November | 48.28 | 792.35 | 146.96 | 0.00 | 146.96 | 0.00 | 0.00 |
December | 8.16 | 1082.37 | 127.05 | 0.00 | 127.05 | 0.00 | 0.00 |
Annual Sum or Average | 269.54 | 555.56 | 223.38 | 4.48 | 218.90 | 0.00 | 0.00 |
Minimum of Months | 8.16 | 75.82 | 127.05 | 0.00 | 127.05 | 0.00 | 0.00 |
Maximum of Months | 646.43 | 1307.04 | 340.37 | 22.32 | 318.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 165.72 | 850.01 | 286.11 | 146.28 | 139.83 | 0.00 | 0.00 |
February | 283.66 | 703.71 | 322.47 | 174.39 | 148.09 | 0.00 | 0.00 |
March | 441.76 | 434.43 | 375.52 | 163.44 | 212.08 | 0.00 | 0.00 |
April | 621.84 | 328.19 | 413.53 | 163.85 | 249.68 | 0.00 | 0.00 |
May | 765.18 | 212.46 | 437.14 | 151.41 | 285.73 | 0.00 | 0.00 |
June | 924.61 | 127.28 | 448.80 | 152.90 | 295.91 | 0.00 | 0.00 |
July | 950.58 | 86.90 | 437.50 | 149.17 | 288.33 | 0.00 | 0.00 |
August | 921.14 | 68.18 | 413.96 | 136.02 | 277.94 | 0.00 | 0.00 |
September | 669.63 | 164.03 | 355.07 | 139.71 | 215.36 | 0.00 | 0.00 |
October | 478.71 | 384.20 | 337.68 | 175.45 | 162.23 | 0.00 | 0.00 |
November | 318.46 | 528.10 | 299.24 | 147.84 | 151.40 | 0.00 | 0.00 |
December | 194.39 | 703.08 | 273.51 | 141.94 | 131.57 | 0.00 | 0.00 |
Annual Sum or Average | 562.80 | 380.96 | 366.94 | 153.39 | 213.55 | 0.00 | 0.00 |
Minimum of Months | 165.72 | 68.18 | 273.51 | 136.02 | 131.57 | 0.00 | 0.00 |
Maximum of Months | 950.58 | 850.01 | 448.80 | 175.45 | 295.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 381.24 | 830.14 | 436.30 | 270.36 | 165.94 | 0.00 | 0.00 |
February | 424.89 | 684.84 | 414.75 | 241.86 | 172.89 | 0.00 | 0.00 |
March | 494.47 | 425.47 | 404.85 | 173.96 | 230.88 | 0.00 | 0.00 |
April | 483.91 | 337.36 | 338.41 | 83.76 | 254.65 | 0.00 | 0.00 |
May | 485.93 | 208.49 | 306.64 | 27.87 | 278.77 | 0.00 | 0.00 |
June | 585.25 | 119.01 | 300.82 | 17.93 | 282.89 | 0.00 | 0.00 |
July | 611.65 | 75.54 | 295.22 | 18.12 | 277.10 | 0.00 | 0.00 |
August | 672.16 | 57.69 | 320.72 | 42.98 | 277.74 | 0.00 | 0.00 |
September | 561.44 | 165.31 | 325.37 | 97.80 | 227.57 | 0.00 | 0.00 |
October | 575.96 | 378.22 | 409.15 | 228.06 | 181.08 | 0.00 | 0.00 |
November | 526.42 | 514.11 | 435.89 | 257.25 | 178.64 | 0.00 | 0.00 |
December | 429.81 | 676.44 | 430.00 | 271.85 | 158.15 | 0.00 | 0.00 |
Annual Sum or Average | 519.99 | 371.12 | 367.99 | 143.85 | 224.15 | 0.00 | 0.00 |
Minimum of Months | 381.24 | 57.69 | 295.22 | 17.93 | 158.15 | 0.00 | 0.00 |
Maximum of Months | 672.16 | 830.14 | 436.30 | 271.85 | 282.89 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.159523E+10 | 0.162720E+10 | 0.141220E+10 | 0.981020E+09 | 0.431183E+09 | 0.00 | 0.00 |
February | 0.146571E+10 | 0.122361E+10 | 0.118818E+10 | 0.792686E+09 | 0.395494E+09 | 0.00 | 0.00 |
March | 0.165876E+10 | 0.874446E+09 | 0.120293E+10 | 0.631243E+09 | 0.571687E+09 | 0.00 | 0.00 |
April | 0.136820E+10 | 0.668454E+09 | 0.876087E+09 | 0.292293E+09 | 0.583795E+09 | 0.00 | 0.00 |
May | 0.122501E+10 | 0.430524E+09 | 0.727706E+09 | 89053889.35 | 0.638652E+09 | 0.00 | 0.00 |
June | 0.127140E+10 | 0.253467E+09 | 0.646621E+09 | 36100811.87 | 0.610520E+09 | 0.00 | 0.00 |
July | 0.138432E+10 | 0.167172E+09 | 0.670261E+09 | 45210453.17 | 0.625050E+09 | 0.00 | 0.00 |
August | 0.166727E+10 | 0.137518E+09 | 0.807634E+09 | 0.151787E+09 | 0.655847E+09 | 0.00 | 0.00 |
September | 0.155656E+10 | 0.336136E+09 | 0.882405E+09 | 0.343335E+09 | 0.539070E+09 | 0.00 | 0.00 |
October | 0.192790E+10 | 0.783062E+09 | 0.128037E+10 | 0.827554E+09 | 0.452812E+09 | 0.00 | 0.00 |
November | 0.182534E+10 | 0.102127E+10 | 0.135373E+10 | 0.903351E+09 | 0.450383E+09 | 0.00 | 0.00 |
December | 0.170288E+10 | 0.135100E+10 | 0.140226E+10 | 0.986443E+09 | 0.415820E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.186486E+11 | 0.887386E+10 | 0.124504E+11 | 0.608008E+10 | 0.637031E+10 | 0.00 | 0.00 |
Minimum of Months | 0.122501E+10 | 0.137518E+09 | 0.646621E+09 | 36100811.87 | 0.395494E+09 | 0.00 | 0.00 |
Maximum of Months | 0.192790E+10 | 0.162720E+10 | 0.141220E+10 | 0.986443E+09 | 0.655847E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.439168E+10 | 0.484680E+10 | 0.397667E+10 | 0.276249E+10 | 0.121418E+10 | 0.00 | 0.00 |
February | 0.403476E+10 | 0.371549E+10 | 0.334584E+10 | 0.223215E+10 | 0.111368E+10 | 0.00 | 0.00 |
March | 0.454785E+10 | 0.275963E+10 | 0.338737E+10 | 0.177754E+10 | 0.160983E+10 | 0.00 | 0.00 |
April | 0.374362E+10 | 0.211433E+10 | 0.246700E+10 | 0.823077E+09 | 0.164393E+10 | 0.00 | 0.00 |
May | 0.334963E+10 | 0.138770E+10 | 0.204917E+10 | 0.250770E+09 | 0.179840E+10 | 0.00 | 0.00 |
June | 0.353595E+10 | 0.784587E+09 | 0.182084E+10 | 0.101658E+09 | 0.171918E+10 | 0.00 | 0.00 |
July | 0.386398E+10 | 0.523795E+09 | 0.188741E+10 | 0.127310E+09 | 0.176010E+10 | 0.00 | 0.00 |
August | 0.467013E+10 | 0.418008E+09 | 0.227424E+10 | 0.427422E+09 | 0.184682E+10 | 0.00 | 0.00 |
September | 0.431634E+10 | 0.107502E+10 | 0.248479E+10 | 0.966809E+09 | 0.151798E+10 | 0.00 | 0.00 |
October | 0.532823E+10 | 0.247078E+10 | 0.360543E+10 | 0.233034E+10 | 0.127509E+10 | 0.00 | 0.00 |
November | 0.501717E+10 | 0.319500E+10 | 0.381203E+10 | 0.254378E+10 | 0.126825E+10 | 0.00 | 0.00 |
December | 0.468528E+10 | 0.411608E+10 | 0.394868E+10 | 0.277776E+10 | 0.117092E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.514846E+11 | 0.274072E+11 | 0.350595E+11 | 0.171211E+11 | 0.179384E+11 | 0.00 | 0.00 |
Minimum of Months | 0.334963E+10 | 0.418008E+09 | 0.182084E+10 | 0.101658E+09 | 0.111368E+10 | 0.00 | 0.00 |
Maximum of Months | 0.532823E+10 | 0.484680E+10 | 0.397667E+10 | 0.277776E+10 | 0.184682E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.580875E+10 | 0.658079E+10 | 0.516592E+10 | 0.358863E+10 | 0.157729E+10 | 0.00 | 0.00 |
February | 0.534884E+10 | 0.503429E+10 | 0.434643E+10 | 0.289969E+10 | 0.144674E+10 | 0.00 | 0.00 |
March | 0.604099E+10 | 0.370400E+10 | 0.440039E+10 | 0.230912E+10 | 0.209126E+10 | 0.00 | 0.00 |
April | 0.497065E+10 | 0.284424E+10 | 0.320478E+10 | 0.106922E+10 | 0.213555E+10 | 0.00 | 0.00 |
May | 0.445670E+10 | 0.185155E+10 | 0.266199E+10 | 0.325764E+09 | 0.233623E+10 | 0.00 | 0.00 |
June | 0.472322E+10 | 0.103088E+10 | 0.236538E+10 | 0.132059E+09 | 0.223332E+10 | 0.00 | 0.00 |
July | 0.517154E+10 | 0.680782E+09 | 0.245185E+10 | 0.165382E+09 | 0.228647E+10 | 0.00 | 0.00 |
August | 0.625351E+10 | 0.527634E+09 | 0.295437E+10 | 0.555246E+09 | 0.239913E+10 | 0.00 | 0.00 |
September | 0.573902E+10 | 0.141897E+10 | 0.322789E+10 | 0.125594E+10 | 0.197195E+10 | 0.00 | 0.00 |
October | 0.707281E+10 | 0.331538E+10 | 0.468365E+10 | 0.302724E+10 | 0.165641E+10 | 0.00 | 0.00 |
November | 0.664044E+10 | 0.430496E+10 | 0.495204E+10 | 0.330451E+10 | 0.164753E+10 | 0.00 | 0.00 |
December | 0.619497E+10 | 0.559263E+10 | 0.512956E+10 | 0.360846E+10 | 0.152109E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.684214E+11 | 0.368861E+11 | 0.455443E+11 | 0.222413E+11 | 0.233030E+11 | 0.00 | 0.00 |
Minimum of Months | 0.445670E+10 | 0.527634E+09 | 0.236538E+10 | 0.132059E+09 | 0.144674E+10 | 0.00 | 0.00 |
Maximum of Months | 0.707281E+10 | 0.658079E+10 | 0.516592E+10 | 0.360846E+10 | 0.239913E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.439492E+09 | 0.968284E+09 | 0.501844E+09 | 0.297480E+09 | 0.204364E+09 | 0.00 | 0.00 |
February | 0.492768E+09 | 0.714557E+09 | 0.465298E+09 | 0.264700E+09 | 0.200598E+09 | 0.00 | 0.00 |
March | 0.797758E+09 | 0.480017E+09 | 0.612039E+09 | 0.305281E+09 | 0.306758E+09 | 0.00 | 0.00 |
April | 0.881097E+09 | 0.350576E+09 | 0.581284E+09 | 0.244432E+09 | 0.336852E+09 | 0.00 | 0.00 |
May | 0.960446E+09 | 0.202956E+09 | 0.568158E+09 | 0.178638E+09 | 0.389520E+09 | 0.00 | 0.00 |
June | 0.110162E+10 | 92438226.72 | 0.559219E+09 | 0.173234E+09 | 0.385985E+09 | 0.00 | 0.00 |
July | 0.115098E+10 | 45719452.88 | 0.552093E+09 | 0.164131E+09 | 0.387962E+09 | 0.00 | 0.00 |
August | 0.120087E+10 | 23507592.76 | 0.571808E+09 | 0.184152E+09 | 0.387656E+09 | 0.00 | 0.00 |
September | 0.891806E+09 | 0.136301E+09 | 0.500287E+09 | 0.204092E+09 | 0.296195E+09 | 0.00 | 0.00 |
October | 0.806758E+09 | 0.416459E+09 | 0.552717E+09 | 0.319376E+09 | 0.233342E+09 | 0.00 | 0.00 |
November | 0.610215E+09 | 0.581549E+09 | 0.497906E+09 | 0.281572E+09 | 0.216334E+09 | 0.00 | 0.00 |
December | 0.467789E+09 | 0.790526E+09 | 0.474312E+09 | 0.281358E+09 | 0.192954E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.980160E+10 | 0.480289E+10 | 0.643697E+10 | 0.289845E+10 | 0.353852E+10 | 0.00 | 0.00 |
Minimum of Months | 0.439492E+09 | 23507592.76 | 0.465298E+09 | 0.164131E+09 | 0.192954E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120087E+10 | 0.968284E+09 | 0.612039E+09 | 0.319376E+09 | 0.389520E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.166489E+09 | 0.105033E+10 | 0.275215E+09 | 0.103516E+09 | 0.171700E+09 | 0.00 | 0.00 |
February | 0.254696E+09 | 0.765173E+09 | 0.283022E+09 | 0.107973E+09 | 0.175050E+09 | 0.00 | 0.00 |
March | 0.548282E+09 | 0.487882E+09 | 0.456053E+09 | 0.180475E+09 | 0.275578E+09 | 0.00 | 0.00 |
April | 0.735010E+09 | 0.347125E+09 | 0.504114E+09 | 0.187201E+09 | 0.316912E+09 | 0.00 | 0.00 |
May | 0.901921E+09 | 0.196881E+09 | 0.542695E+09 | 0.164744E+09 | 0.377951E+09 | 0.00 | 0.00 |
June | 0.109158E+10 | 88304934.23 | 0.557408E+09 | 0.174362E+09 | 0.383046E+09 | 0.00 | 0.00 |
July | 0.112898E+10 | 44456849.43 | 0.542915E+09 | 0.161512E+09 | 0.381403E+09 | 0.00 | 0.00 |
August | 0.109995E+10 | 22746471.57 | 0.521677E+09 | 0.155428E+09 | 0.366249E+09 | 0.00 | 0.00 |
September | 0.718304E+09 | 0.134207E+09 | 0.405848E+09 | 0.136240E+09 | 0.269608E+09 | 0.00 | 0.00 |
October | 0.502185E+09 | 0.422806E+09 | 0.362400E+09 | 0.155754E+09 | 0.206646E+09 | 0.00 | 0.00 |
November | 0.308031E+09 | 0.609354E+09 | 0.284668E+09 | 0.102964E+09 | 0.181704E+09 | 0.00 | 0.00 |
December | 0.178410E+09 | 0.852435E+09 | 0.245674E+09 | 86321527.55 | 0.159353E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.763384E+10 | 0.502170E+10 | 0.498169E+10 | 0.171649E+10 | 0.326520E+10 | 0.00 | 0.00 |
Minimum of Months | 0.166489E+09 | 22746471.57 | 0.245674E+09 | 86321527.55 | 0.159353E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112898E+10 | 0.105033E+10 | 0.557408E+09 | 0.187201E+09 | 0.383046E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.251886E+09 | 0.257402E+09 | 0.223330E+09 | 0.155141E+09 | 68188813.41 | 0.00 | 0.00 |
February | 0.230227E+09 | 0.196058E+09 | 0.187902E+09 | 0.125357E+09 | 62544840.67 | 0.00 | 0.00 |
March | 0.255465E+09 | 0.151722E+09 | 0.190235E+09 | 99826196.68 | 90408627.06 | 0.00 | 0.00 |
April | 0.212153E+09 | 0.115779E+09 | 0.138547E+09 | 46223853.60 | 92323562.43 | 0.00 | 0.00 |
May | 0.193238E+09 | 72348624.61 | 0.115082E+09 | 14083185.96 | 0.100999E+09 | 0.00 | 0.00 |
June | 0.210339E+09 | 37070486.12 | 0.102259E+09 | 5709065.05 | 96550134.41 | 0.00 | 0.00 |
July | 0.231739E+09 | 22368475.53 | 0.105998E+09 | 7149684.58 | 98847981.78 | 0.00 | 0.00 |
August | 0.278271E+09 | 15438210.65 | 0.127722E+09 | 24003960.40 | 0.103718E+09 | 0.00 | 0.00 |
September | 0.249769E+09 | 53196295.33 | 0.139546E+09 | 54295818.95 | 85250458.26 | 0.00 | 0.00 |
October | 0.302078E+09 | 0.134692E+09 | 0.202481E+09 | 0.130871E+09 | 71609428.64 | 0.00 | 0.00 |
November | 0.281993E+09 | 0.179620E+09 | 0.214083E+09 | 0.142858E+09 | 71225121.93 | 0.00 | 0.00 |
December | 0.265149E+09 | 0.223896E+09 | 0.221757E+09 | 0.155998E+09 | 65759141.47 | 0.00 | 0.00 |
Annual Sum or Average | 0.296231E+10 | 0.145959E+10 | 0.196894E+10 | 0.961517E+09 | 0.100743E+10 | 0.00 | 0.00 |
Minimum of Months | 0.193238E+09 | 15438210.65 | 0.102259E+09 | 5709065.05 | 62544840.67 | 0.00 | 0.00 |
Maximum of Months | 0.302078E+09 | 0.257402E+09 | 0.223330E+09 | 0.155998E+09 | 0.103718E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5754330.72 | 0.326874E+09 | 42076451.99 | 0.00 | 42076451.99 | 0.00 | 0.00 |
February | 20078982.61 | 0.233649E+09 | 42124339.93 | 0.00 | 42124339.93 | 0.00 | 0.00 |
March | 54617022.22 | 0.140452E+09 | 65492691.15 | 1318.99 | 65491372.16 | 0.00 | 0.00 |
April | 0.103194E+09 | 94889871.74 | 76848851.72 | 448829.91 | 76400021.81 | 0.00 | 0.00 |
May | 0.162503E+09 | 49707948.09 | 94747450.04 | 2971603.27 | 91775846.77 | 0.00 | 0.00 |
June | 0.224020E+09 | 20381395.01 | 0.100844E+09 | 6613320.29 | 94230889.24 | 0.00 | 0.00 |
July | 0.237736E+09 | 9492159.73 | 98689421.90 | 5056973.36 | 93632448.53 | 0.00 | 0.00 |
August | 0.221709E+09 | 4061988.70 | 87654522.95 | 1029768.70 | 86624754.24 | 0.00 | 0.00 |
September | 0.125213E+09 | 33990735.78 | 64031230.67 | 25170.94 | 64006059.72 | 0.00 | 0.00 |
October | 58022804.25 | 0.119391E+09 | 50273499.29 | 0.00 | 50273499.29 | 0.00 | 0.00 |
November | 28178591.38 | 0.178357E+09 | 43541540.27 | 0.00 | 43541540.27 | 0.00 | 0.00 |
December | 7219455.35 | 0.259316E+09 | 38896548.34 | 0.00 | 38896548.34 | 0.00 | 0.00 |
Annual Sum or Average | 0.124825E+10 | 0.147056E+10 | 0.805221E+09 | 16146985.47 | 0.789074E+09 | 0.00 | 0.00 |
Minimum of Months | 5754330.72 | 4061988.70 | 38896548.34 | 0.00 | 38896548.34 | 0.00 | 0.00 |
Maximum of Months | 0.237736E+09 | 0.326874E+09 | 0.100844E+09 | 6613320.29 | 94230889.24 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.417864E+09 | 0.954188E+09 | 0.496486E+09 | 0.292891E+09 | 0.203596E+09 | 0.00 | 0.00 |
February | 0.501243E+09 | 0.698383E+09 | 0.481219E+09 | 0.289311E+09 | 0.191908E+09 | 0.00 | 0.00 |
March | 0.719687E+09 | 0.457010E+09 | 0.580914E+09 | 0.281299E+09 | 0.299614E+09 | 0.00 | 0.00 |
April | 0.842525E+09 | 0.325864E+09 | 0.574551E+09 | 0.240974E+09 | 0.333577E+09 | 0.00 | 0.00 |
May | 0.990098E+09 | 0.187789E+09 | 0.598187E+09 | 0.209729E+09 | 0.388458E+09 | 0.00 | 0.00 |
June | 0.113109E+10 | 84141251.36 | 0.582588E+09 | 0.197605E+09 | 0.384983E+09 | 0.00 | 0.00 |
July | 0.121029E+10 | 43849703.94 | 0.590525E+09 | 0.201092E+09 | 0.389433E+09 | 0.00 | 0.00 |
August | 0.121390E+10 | 22092959.33 | 0.579466E+09 | 0.196526E+09 | 0.382940E+09 | 0.00 | 0.00 |
September | 0.898042E+09 | 0.130245E+09 | 0.507408E+09 | 0.214997E+09 | 0.292411E+09 | 0.00 | 0.00 |
October | 0.777592E+09 | 0.399449E+09 | 0.547407E+09 | 0.316785E+09 | 0.230622E+09 | 0.00 | 0.00 |
November | 0.584349E+09 | 0.561663E+09 | 0.494448E+09 | 0.280911E+09 | 0.213537E+09 | 0.00 | 0.00 |
December | 0.460879E+09 | 0.772615E+09 | 0.480619E+09 | 0.287609E+09 | 0.193010E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.974755E+10 | 0.463729E+10 | 0.651382E+10 | 0.300973E+10 | 0.350409E+10 | 0.00 | 0.00 |
Minimum of Months | 0.417864E+09 | 22092959.33 | 0.480619E+09 | 0.196526E+09 | 0.191908E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121390E+10 | 0.954188E+09 | 0.598187E+09 | 0.316785E+09 | 0.389433E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.125690E+09 | 0.101622E+10 | 0.269858E+09 | 98926312.94 | 0.170931E+09 | 0.00 | 0.00 |
February | 0.237982E+09 | 0.723296E+09 | 0.298943E+09 | 0.132584E+09 | 0.166359E+09 | 0.00 | 0.00 |
March | 0.458497E+09 | 0.452900E+09 | 0.424928E+09 | 0.156494E+09 | 0.268435E+09 | 0.00 | 0.00 |
April | 0.694253E+09 | 0.321605E+09 | 0.497381E+09 | 0.183744E+09 | 0.313637E+09 | 0.00 | 0.00 |
May | 0.934849E+09 | 0.185704E+09 | 0.572725E+09 | 0.195836E+09 | 0.376889E+09 | 0.00 | 0.00 |
June | 0.112476E+10 | 83720673.23 | 0.580777E+09 | 0.198732E+09 | 0.382045E+09 | 0.00 | 0.00 |
July | 0.118935E+10 | 43659663.72 | 0.581347E+09 | 0.198474E+09 | 0.382873E+09 | 0.00 | 0.00 |
August | 0.111297E+10 | 21579530.52 | 0.529335E+09 | 0.167803E+09 | 0.361533E+09 | 0.00 | 0.00 |
September | 0.722977E+09 | 0.127920E+09 | 0.412969E+09 | 0.147145E+09 | 0.265824E+09 | 0.00 | 0.00 |
October | 0.459603E+09 | 0.394293E+09 | 0.357089E+09 | 0.153163E+09 | 0.203926E+09 | 0.00 | 0.00 |
November | 0.256021E+09 | 0.561736E+09 | 0.281211E+09 | 0.102303E+09 | 0.178908E+09 | 0.00 | 0.00 |
December | 0.135661E+09 | 0.797858E+09 | 0.251981E+09 | 92572432.32 | 0.159409E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.745262E+10 | 0.473049E+10 | 0.505854E+10 | 0.182778E+10 | 0.323077E+10 | 0.00 | 0.00 |
Minimum of Months | 0.125690E+09 | 21579530.52 | 0.251981E+09 | 92572432.32 | 0.159409E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118935E+10 | 0.101622E+10 | 0.581347E+09 | 0.198732E+09 | 0.382873E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.462835E+09 | 0.124708E+10 | 0.575045E+09 | 0.336147E+09 | 0.238898E+09 | 0.00 | 0.00 |
February | 0.488017E+09 | 0.926224E+09 | 0.498387E+09 | 0.271614E+09 | 0.226773E+09 | 0.00 | 0.00 |
March | 0.667993E+09 | 0.641360E+09 | 0.554065E+09 | 0.216298E+09 | 0.337767E+09 | 0.00 | 0.00 |
April | 0.675396E+09 | 0.486527E+09 | 0.466674E+09 | 0.101127E+09 | 0.365548E+09 | 0.00 | 0.00 |
May | 0.749140E+09 | 0.297930E+09 | 0.454606E+09 | 36951836.71 | 0.417654E+09 | 0.00 | 0.00 |
June | 0.889895E+09 | 0.160805E+09 | 0.440030E+09 | 26696625.66 | 0.413333E+09 | 0.00 | 0.00 |
July | 0.952618E+09 | 0.103689E+09 | 0.443462E+09 | 26446478.24 | 0.417015E+09 | 0.00 | 0.00 |
August | 0.101374E+10 | 75896598.12 | 0.466627E+09 | 54240731.23 | 0.412387E+09 | 0.00 | 0.00 |
September | 0.779499E+09 | 0.234279E+09 | 0.441071E+09 | 0.117698E+09 | 0.323373E+09 | 0.00 | 0.00 |
October | 0.766275E+09 | 0.572695E+09 | 0.547629E+09 | 0.283562E+09 | 0.264067E+09 | 0.00 | 0.00 |
November | 0.657650E+09 | 0.751735E+09 | 0.558184E+09 | 0.309534E+09 | 0.248651E+09 | 0.00 | 0.00 |
December | 0.533513E+09 | 0.101384E+10 | 0.564750E+09 | 0.338005E+09 | 0.226745E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.863657E+10 | 0.651207E+10 | 0.601053E+10 | 0.211832E+10 | 0.389221E+10 | 0.00 | 0.00 |
Minimum of Months | 0.462835E+09 | 75896598.12 | 0.440030E+09 | 26446478.24 | 0.226745E+09 | 0.00 | 0.00 |
Maximum of Months | 0.101374E+10 | 0.124708E+10 | 0.575045E+09 | 0.338005E+09 | 0.417654E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.439119E+09 | 0.964215E+09 | 0.501844E+09 | 0.297480E+09 | 0.204364E+09 | 0.00 | 0.00 |
February | 0.490793E+09 | 0.709463E+09 | 0.465298E+09 | 0.264700E+09 | 0.200598E+09 | 0.00 | 0.00 |
March | 0.792313E+09 | 0.472043E+09 | 0.612039E+09 | 0.305281E+09 | 0.306758E+09 | 0.00 | 0.00 |
April | 0.874126E+09 | 0.344589E+09 | 0.581284E+09 | 0.244432E+09 | 0.336852E+09 | 0.00 | 0.00 |
May | 0.951515E+09 | 0.198205E+09 | 0.568158E+09 | 0.178638E+09 | 0.389520E+09 | 0.00 | 0.00 |
June | 0.109476E+10 | 87875475.56 | 0.559219E+09 | 0.173234E+09 | 0.385985E+09 | 0.00 | 0.00 |
July | 0.114523E+10 | 42034622.04 | 0.552093E+09 | 0.164131E+09 | 0.387962E+09 | 0.00 | 0.00 |
August | 0.119524E+10 | 20597070.62 | 0.571808E+09 | 0.184152E+09 | 0.387656E+09 | 0.00 | 0.00 |
September | 0.887592E+09 | 0.130061E+09 | 0.500287E+09 | 0.204092E+09 | 0.296195E+09 | 0.00 | 0.00 |
October | 0.803173E+09 | 0.407256E+09 | 0.552717E+09 | 0.319376E+09 | 0.233342E+09 | 0.00 | 0.00 |
November | 0.609427E+09 | 0.573000E+09 | 0.497906E+09 | 0.281572E+09 | 0.216334E+09 | 0.00 | 0.00 |
December | 0.468106E+09 | 0.783494E+09 | 0.474312E+09 | 0.281358E+09 | 0.192954E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.975139E+10 | 0.473283E+10 | 0.643697E+10 | 0.289845E+10 | 0.353852E+10 | 0.00 | 0.00 |
Minimum of Months | 0.439119E+09 | 20597070.62 | 0.465298E+09 | 0.164131E+09 | 0.192954E+09 | 0.00 | 0.00 |
Maximum of Months | 0.119524E+10 | 0.964215E+09 | 0.612039E+09 | 0.319376E+09 | 0.389520E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.167051E+09 | 0.104751E+10 | 0.275215E+09 | 0.103516E+09 | 0.171700E+09 | 0.00 | 0.00 |
February | 0.254726E+09 | 0.759677E+09 | 0.283022E+09 | 0.107973E+09 | 0.175050E+09 | 0.00 | 0.00 |
March | 0.546792E+09 | 0.478505E+09 | 0.456053E+09 | 0.180475E+09 | 0.275578E+09 | 0.00 | 0.00 |
April | 0.730181E+09 | 0.340782E+09 | 0.504114E+09 | 0.187201E+09 | 0.316912E+09 | 0.00 | 0.00 |
May | 0.893860E+09 | 0.192277E+09 | 0.542695E+09 | 0.164744E+09 | 0.377951E+09 | 0.00 | 0.00 |
June | 0.108506E+10 | 83976833.61 | 0.557408E+09 | 0.174362E+09 | 0.383046E+09 | 0.00 | 0.00 |
July | 0.112354E+10 | 40987946.29 | 0.542915E+09 | 0.161512E+09 | 0.381403E+09 | 0.00 | 0.00 |
August | 0.109546E+10 | 19864471.16 | 0.521677E+09 | 0.155428E+09 | 0.366249E+09 | 0.00 | 0.00 |
September | 0.716176E+09 | 0.127594E+09 | 0.405848E+09 | 0.136240E+09 | 0.269608E+09 | 0.00 | 0.00 |
October | 0.502978E+09 | 0.411734E+09 | 0.362400E+09 | 0.155754E+09 | 0.206646E+09 | 0.00 | 0.00 |
November | 0.310716E+09 | 0.598823E+09 | 0.284668E+09 | 0.102964E+09 | 0.181704E+09 | 0.00 | 0.00 |
December | 0.181086E+09 | 0.844950E+09 | 0.245674E+09 | 86321527.55 | 0.159353E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.760763E+10 | 0.494668E+10 | 0.498169E+10 | 0.171649E+10 | 0.326520E+10 | 0.00 | 0.00 |
Minimum of Months | 0.167051E+09 | 19864471.16 | 0.245674E+09 | 86321527.55 | 0.159353E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112354E+10 | 0.104751E+10 | 0.557408E+09 | 0.187201E+09 | 0.383046E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.444117E+09 | 0.498220E+09 | 0.409499E+09 | 0.284468E+09 | 0.125032E+09 | 0.00 | 0.00 |
February | 0.411814E+09 | 0.369101E+09 | 0.344539E+09 | 0.229856E+09 | 0.114683E+09 | 0.00 | 0.00 |
March | 0.472586E+09 | 0.246566E+09 | 0.348816E+09 | 0.183042E+09 | 0.165774E+09 | 0.00 | 0.00 |
April | 0.397720E+09 | 0.178864E+09 | 0.254042E+09 | 84756499.22 | 0.169285E+09 | 0.00 | 0.00 |
May | 0.368748E+09 | 99139845.60 | 0.211016E+09 | 25823064.22 | 0.185193E+09 | 0.00 | 0.00 |
June | 0.408027E+09 | 41874073.95 | 0.187503E+09 | 10468196.17 | 0.177035E+09 | 0.00 | 0.00 |
July | 0.451562E+09 | 19311208.03 | 0.194358E+09 | 13109729.90 | 0.181249E+09 | 0.00 | 0.00 |
August | 0.537745E+09 | 8942510.81 | 0.234192E+09 | 44013890.93 | 0.190178E+09 | 0.00 | 0.00 |
September | 0.472571E+09 | 65697847.46 | 0.255873E+09 | 99557331.94 | 0.156316E+09 | 0.00 | 0.00 |
October | 0.559348E+09 | 0.211529E+09 | 0.371270E+09 | 0.239967E+09 | 0.131304E+09 | 0.00 | 0.00 |
November | 0.520218E+09 | 0.297885E+09 | 0.392545E+09 | 0.261946E+09 | 0.130599E+09 | 0.00 | 0.00 |
December | 0.477894E+09 | 0.407539E+09 | 0.406617E+09 | 0.286040E+09 | 0.120577E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.552235E+10 | 0.244467E+10 | 0.361027E+10 | 0.176305E+10 | 0.184722E+10 | 0.00 | 0.00 |
Minimum of Months | 0.368748E+09 | 8942510.81 | 0.187503E+09 | 10468196.17 | 0.114683E+09 | 0.00 | 0.00 |
Maximum of Months | 0.559348E+09 | 0.498220E+09 | 0.409499E+09 | 0.286040E+09 | 0.190178E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 27685160.83 | 0.339379E+10 | 0.368106E+09 | 0.00 | 0.368106E+09 | 0.00 | 0.00 |
February | 0.116456E+09 | 0.249284E+10 | 0.368525E+09 | 0.00 | 0.368525E+09 | 0.00 | 0.00 |
March | 0.321380E+09 | 0.163000E+10 | 0.572963E+09 | 11539.19 | 0.572952E+09 | 0.00 | 0.00 |
April | 0.699643E+09 | 0.114215E+10 | 0.672313E+09 | 3926592.47 | 0.668386E+09 | 0.00 | 0.00 |
May | 0.116257E+10 | 0.696789E+09 | 0.828899E+09 | 25997097.83 | 0.802902E+09 | 0.00 | 0.00 |
June | 0.166493E+10 | 0.368941E+09 | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.00 | 0.00 |
July | 0.175671E+10 | 0.249355E+09 | 0.863385E+09 | 44240976.70 | 0.819144E+09 | 0.00 | 0.00 |
August | 0.160331E+10 | 0.190217E+09 | 0.766846E+09 | 9008940.72 | 0.757837E+09 | 0.00 | 0.00 |
September | 0.860622E+09 | 0.554307E+09 | 0.560178E+09 | 220208.23 | 0.559958E+09 | 0.00 | 0.00 |
October | 0.356637E+09 | 0.143595E+10 | 0.439818E+09 | 0.00 | 0.439818E+09 | 0.00 | 0.00 |
November | 0.143489E+09 | 0.198575E+10 | 0.380924E+09 | 0.00 | 0.380924E+09 | 0.00 | 0.00 |
December | 26418006.39 | 0.280088E+10 | 0.340287E+09 | 0.00 | 0.340287E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.873986E+10 | 0.169410E+11 | 0.704448E+10 | 0.141262E+09 | 0.690322E+10 | 0.00 | 0.00 |
Minimum of Months | 26418006.39 | 0.190217E+09 | 0.340287E+09 | 0.00 | 0.340287E+09 | 0.00 | 0.00 |
Maximum of Months | 0.175671E+10 | 0.339379E+10 | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 23380341.22 | 0.350078E+10 | 0.368106E+09 | 0.00 | 0.368106E+09 | 0.00 | 0.00 |
February | 0.105707E+09 | 0.257376E+10 | 0.368525E+09 | 0.00 | 0.368525E+09 | 0.00 | 0.00 |
March | 0.295472E+09 | 0.168543E+10 | 0.572963E+09 | 11539.19 | 0.572952E+09 | 0.00 | 0.00 |
April | 0.671383E+09 | 0.117586E+10 | 0.672313E+09 | 3926592.47 | 0.668386E+09 | 0.00 | 0.00 |
May | 0.113390E+10 | 0.719291E+09 | 0.828899E+09 | 25997097.83 | 0.802902E+09 | 0.00 | 0.00 |
June | 0.163988E+10 | 0.383269E+09 | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.00 | 0.00 |
July | 0.173141E+10 | 0.262387E+09 | 0.863385E+09 | 44240976.70 | 0.819144E+09 | 0.00 | 0.00 |
August | 0.157876E+10 | 0.203078E+09 | 0.766846E+09 | 9008940.72 | 0.757837E+09 | 0.00 | 0.00 |
September | 0.837623E+09 | 0.577801E+09 | 0.560178E+09 | 220208.23 | 0.559958E+09 | 0.00 | 0.00 |
October | 0.335593E+09 | 0.148570E+10 | 0.439818E+09 | 0.00 | 0.439818E+09 | 0.00 | 0.00 |
November | 0.125134E+09 | 0.205378E+10 | 0.380924E+09 | 0.00 | 0.380924E+09 | 0.00 | 0.00 |
December | 21849634.67 | 0.289903E+10 | 0.340287E+09 | 0.00 | 0.340287E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.850009E+10 | 0.175202E+11 | 0.704448E+10 | 0.141262E+09 | 0.690322E+10 | 0.00 | 0.00 |
Minimum of Months | 21849634.67 | 0.203078E+09 | 0.340287E+09 | 0.00 | 0.340287E+09 | 0.00 | 0.00 |
Maximum of Months | 0.173141E+10 | 0.350078E+10 | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.443853E+09 | 0.227666E+10 | 0.766313E+09 | 0.391803E+09 | 0.374510E+09 | 0.00 | 0.00 |
February | 0.686220E+09 | 0.170242E+10 | 0.780127E+09 | 0.421877E+09 | 0.358251E+09 | 0.00 | 0.00 |
March | 0.118322E+10 | 0.116358E+10 | 0.100579E+10 | 0.437771E+09 | 0.568023E+09 | 0.00 | 0.00 |
April | 0.161180E+10 | 0.850672E+09 | 0.107188E+10 | 0.424692E+09 | 0.647183E+09 | 0.00 | 0.00 |
May | 0.204945E+10 | 0.569056E+09 | 0.117085E+10 | 0.405538E+09 | 0.765309E+09 | 0.00 | 0.00 |
June | 0.239660E+10 | 0.329918E+09 | 0.116330E+10 | 0.396310E+09 | 0.766990E+09 | 0.00 | 0.00 |
July | 0.254602E+10 | 0.232750E+09 | 0.117181E+10 | 0.399539E+09 | 0.772269E+09 | 0.00 | 0.00 |
August | 0.246719E+10 | 0.182612E+09 | 0.110874E+10 | 0.364305E+09 | 0.744437E+09 | 0.00 | 0.00 |
September | 0.173569E+10 | 0.425164E+09 | 0.920329E+09 | 0.362120E+09 | 0.558209E+09 | 0.00 | 0.00 |
October | 0.128217E+10 | 0.102903E+10 | 0.904454E+09 | 0.469926E+09 | 0.434528E+09 | 0.00 | 0.00 |
November | 0.825448E+09 | 0.136883E+10 | 0.775627E+09 | 0.383200E+09 | 0.392427E+09 | 0.00 | 0.00 |
December | 0.520649E+09 | 0.188313E+10 | 0.732571E+09 | 0.380168E+09 | 0.352403E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.177483E+11 | 0.120138E+11 | 0.115718E+11 | 0.483725E+10 | 0.673454E+10 | 0.00 | 0.00 |
Minimum of Months | 0.443853E+09 | 0.182612E+09 | 0.732571E+09 | 0.362120E+09 | 0.352403E+09 | 0.00 | 0.00 |
Maximum of Months | 0.254602E+10 | 0.227666E+10 | 0.117181E+10 | 0.469926E+09 | 0.772269E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.102111E+10 | 0.222345E+10 | 0.116859E+10 | 0.724128E+09 | 0.444462E+09 | 0.00 | 0.00 |
February | 0.102789E+10 | 0.165676E+10 | 0.100337E+10 | 0.585111E+09 | 0.418262E+09 | 0.00 | 0.00 |
March | 0.132439E+10 | 0.113957E+10 | 0.108434E+10 | 0.465948E+09 | 0.618396E+09 | 0.00 | 0.00 |
April | 0.125429E+10 | 0.874438E+09 | 0.877147E+09 | 0.217098E+09 | 0.660049E+09 | 0.00 | 0.00 |
May | 0.130152E+10 | 0.558423E+09 | 0.821300E+09 | 74645838.28 | 0.746654E+09 | 0.00 | 0.00 |
June | 0.151696E+10 | 0.308483E+09 | 0.779732E+09 | 46480736.68 | 0.733252E+09 | 0.00 | 0.00 |
July | 0.163824E+10 | 0.202317E+09 | 0.790720E+09 | 48537407.44 | 0.742182E+09 | 0.00 | 0.00 |
August | 0.180032E+10 | 0.154510E+09 | 0.859026E+09 | 0.115128E+09 | 0.743898E+09 | 0.00 | 0.00 |
September | 0.145526E+10 | 0.428473E+09 | 0.843369E+09 | 0.253504E+09 | 0.589865E+09 | 0.00 | 0.00 |
October | 0.154266E+10 | 0.101301E+10 | 0.109586E+10 | 0.610848E+09 | 0.485011E+09 | 0.00 | 0.00 |
November | 0.136449E+10 | 0.133257E+10 | 0.112983E+10 | 0.666797E+09 | 0.463028E+09 | 0.00 | 0.00 |
December | 0.115120E+10 | 0.181178E+10 | 0.115171E+10 | 0.728130E+09 | 0.423585E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.163983E+11 | 0.117038E+11 | 0.116050E+11 | 0.453636E+10 | 0.706864E+10 | 0.00 | 0.00 |
Minimum of Months | 0.102111E+10 | 0.154510E+09 | 0.779732E+09 | 46480736.68 | 0.418262E+09 | 0.00 | 0.00 |
Maximum of Months | 0.180032E+10 | 0.222345E+10 | 0.116859E+10 | 0.728130E+09 | 0.746654E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770506E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162263928.3 | 81.21 | 0.00 | 0.00 |
February | 0.696238E+10 | -0.681597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146410019.0 | 81.21 | 0.00 | 0.00 |
March | 0.770324E+10 | -0.754147E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161766521.4 | 81.21 | 0.00 | 0.00 |
April | 0.746501E+10 | -0.730858E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156427031.2 | 81.21 | 0.00 | 0.00 |
May | 0.770436E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161573542.0 | 81.21 | 0.00 | 0.00 |
June | 0.745681E+10 | -0.730052E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156283042.4 | 81.21 | 0.00 | 0.00 |
July | 0.771232E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161471634.1 | 81.21 | 0.00 | 0.00 |
August | 0.770426E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161457212.7 | 81.21 | 0.00 | 0.00 |
September | 0.746626E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156338268.8 | 81.21 | 0.00 | 0.00 |
October | 0.770313E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161692447.7 | 81.21 | 0.00 | 0.00 |
November | 0.744910E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156676921.1 | 81.21 | 0.00 | 0.00 |
December | 0.771285E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161985400.5 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907448E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190435E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696238E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162263928.3 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771285E+10 | -0.681597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146410019.0 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.116057E+12 | -0.114307E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175041E+10 | 81.26 | 0.00 | 0.00 |
February | 0.104979E+12 | -0.103383E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.159575E+10 | 81.26 | 0.00 | 0.00 |
March | 0.113662E+12 | -0.111877E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178551E+10 | 81.26 | 0.00 | 0.00 |
April | 0.105398E+12 | -0.103652E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.174539E+10 | 81.25 | 0.00 | 0.00 |
May | 0.103239E+12 | -0.101448E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179113E+10 | 81.25 | 0.00 | 0.00 |
June | 0.950184E+11 | -0.933104E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170802E+10 | 81.25 | 0.00 | 0.00 |
July | 0.951363E+11 | -0.933875E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174884E+10 | 81.24 | 0.00 | 0.00 |
August | 0.949078E+11 | -0.931728E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173503E+10 | 81.24 | 0.00 | 0.00 |
September | 0.944204E+11 | -0.927478E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167255E+10 | 81.24 | 0.00 | 0.00 |
October | 0.102385E+12 | -0.100658E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172695E+10 | 81.24 | 0.00 | 0.00 |
November | 0.104561E+12 | -0.102890E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167096E+10 | 81.25 | 0.00 | 0.00 |
December | 0.113034E+12 | -0.111304E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172974E+10 | 81.26 | 0.00 | 0.00 |
Annual Sum or Average | 0.124280E+13 | -0.122214E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206603E+11 | 81.25 | 0.00 | 0.00 |
Minimum of Months | 0.944204E+11 | -0.114307E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.179113E+10 | 81.24 | 0.00 | 0.00 |
Maximum of Months | 0.116057E+12 | -0.927478E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.159575E+10 | 81.26 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.675915E+11 | -0.660958E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149569E+10 | 58.98 | 0.00 | 0.00 |
February | 0.612071E+11 | -0.598358E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.137137E+10 | 58.98 | 0.00 | 0.00 |
March | 0.656127E+11 | -0.640684E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154427E+10 | 58.98 | 0.00 | 0.00 |
April | 0.595100E+11 | -0.579912E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.151886E+10 | 58.98 | 0.00 | 0.00 |
May | 0.566029E+11 | -0.550506E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.155229E+10 | 58.98 | 0.00 | 0.00 |
June | 0.505616E+11 | -0.490943E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146728E+10 | 58.98 | 0.00 | 0.00 |
July | 0.495594E+11 | -0.480655E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149393E+10 | 58.98 | 0.00 | 0.00 |
August | 0.494042E+11 | -0.479293E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147490E+10 | 58.98 | 0.00 | 0.00 |
September | 0.500040E+11 | -0.485857E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141830E+10 | 58.98 | 0.00 | 0.00 |
October | 0.558005E+11 | -0.543367E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146383E+10 | 58.98 | 0.00 | 0.00 |
November | 0.587288E+11 | -0.573128E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141607E+10 | 58.98 | 0.00 | 0.00 |
December | 0.649805E+11 | -0.635133E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146719E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.689563E+12 | -0.671879E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.176840E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.494042E+11 | -0.660958E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.155229E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.675915E+11 | -0.479293E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.137137E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.93 | 0.93 | 01-JAN-08:50 | 4810.38 | 33.78 | 269.00 | 273.50 | 741.71 | 25.18 | 151.33 | 241.67 |
February | 263.00 | 0.93 | 0.93 | 01-FEB-09:00 | 4266.88 | 30.58 | 190.67 | 246.83 | 522.58 | 21.54 | 97.50 | 198.00 |
March | 351.67 | 0.93 | 0.93 | 01-MAR-08:09 | 1056.89 | 19.19 | 10.83 | 318.00 | 406.47 | 20.61 | 139.17 | 246.00 |
April | 369.33 | 0.94 | 0.93 | 01-APR-07:00 | 845.23 | 18.68 | 0.00 | 322.50 | 334.92 | 20.43 | 116.33 | 236.00 |
May | 407.00 | 0.94 | 0.93 | 01-MAY-06:00 | 800.66 | 18.64 | 0.00 | 357.17 | 317.53 | 20.38 | 152.83 | 259.83 |
June | 411.67 | 0.94 | 0.93 | 01-JUN-06:40 | 739.11 | 18.40 | 0.00 | 356.83 | 297.30 | 20.16 | 141.67 | 241.50 |
July | 411.00 | 0.94 | 0.93 | 01-JUL-06:49 | 782.10 | 18.50 | 0.00 | 361.50 | 311.90 | 20.24 | 172.50 | 260.67 |
August | 390.50 | 0.93 | 0.93 | 01-AUG-06:00 | 968.53 | 19.17 | 0.00 | 350.17 | 378.70 | 20.89 | 213.33 | 279.33 |
September | 298.50 | 0.94 | 0.93 | 01-SEP-07:10 | 1018.70 | 19.11 | 0.00 | 308.17 | 402.18 | 20.85 | 149.67 | 223.17 |
October | 293.50 | 0.93 | 0.93 | 01-OCT-07:40 | 2457.31 | 24.40 | 105.00 | 289.50 | 415.76 | 20.68 | 95.83 | 209.50 |
November | 299.00 | 0.93 | 0.93 | 01-NOV-07:00 | 4784.52 | 34.53 | 285.17 | 273.17 | 601.17 | 24.85 | 156.33 | 239.83 |
December | 285.17 | 0.93 | 0.93 | 01-DEC-07:49 | 4501.80 | 34.28 | 269.67 | 268.00 | 831.29 | 26.35 | 158.83 | 232.67 |
Annual Sum or Average | 4071.00 | 0.93 | 2032.35 | 23.27 | 1130.33 | 3725.33 | 443.69 | 21.64 | 1745.33 | 2868.17 | ||
Minimum of Months | 263.00 | 0.93 | 0.93 | 739.11 | 18.40 | 0.00 | 246.83 | 297.30 | 20.16 | 95.83 | 198.00 | |
Maximum of Months | 411.67 | 0.94 | 0.93 | 4810.38 | 34.53 | 285.17 | 361.50 | 831.29 | 26.35 | 213.33 | 279.33 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.62 | 0.61 | 01-JAN-08:39 | 5101.01 | 33.90 | 271.67 | 281.50 | 1031.72 | 25.14 | 165.83 | 262.17 |
February | 263.00 | 0.63 | 0.61 | 01-FEB-09:50 | 4543.25 | 30.69 | 191.83 | 258.33 | 798.39 | 21.67 | 101.83 | 222.00 |
March | 351.67 | 0.63 | 0.61 | 01-MAR-07:00 | 1281.88 | 19.69 | 18.33 | 331.83 | 630.73 | 20.95 | 161.17 | 296.83 |
April | 369.33 | 0.63 | 0.61 | 01-APR-07:40 | 1011.06 | 19.41 | 0.83 | 340.83 | 500.21 | 20.93 | 167.50 | 297.50 |
May | 407.00 | 0.63 | 0.61 | 01-MAY-06:49 | 934.53 | 19.51 | 1.33 | 379.50 | 450.90 | 21.02 | 223.00 | 327.33 |
June | 411.67 | 0.63 | 0.61 | 01-JUN-06:19 | 861.61 | 19.31 | 0.33 | 378.67 | 419.36 | 20.84 | 209.83 | 330.00 |
July | 411.00 | 0.63 | 0.61 | 01-JUL-06:19 | 908.39 | 19.40 | 0.33 | 382.33 | 437.70 | 20.90 | 234.00 | 330.33 |
August | 390.50 | 0.62 | 0.61 | 01-AUG-06:40 | 1124.13 | 19.95 | 16.00 | 365.17 | 533.70 | 21.45 | 255.33 | 326.17 |
September | 298.50 | 0.63 | 0.61 | 01-SEP-06:00 | 1211.51 | 19.74 | 9.00 | 322.17 | 594.37 | 21.28 | 175.17 | 285.00 |
October | 293.50 | 0.63 | 0.61 | 01-OCT-07:19 | 2727.60 | 24.56 | 108.50 | 304.00 | 683.42 | 20.80 | 103.00 | 261.83 |
November | 299.00 | 0.63 | 0.61 | 01-NOV-07:49 | 5063.09 | 34.62 | 286.17 | 281.33 | 877.87 | 24.86 | 167.67 | 264.00 |
December | 285.17 | 0.62 | 0.61 | 01-DEC-07:49 | 4797.33 | 34.39 | 271.00 | 278.00 | 1124.77 | 26.31 | 167.50 | 256.67 |
Annual Sum or Average | 4071.00 | 0.63 | 2233.66 | 23.81 | 1175.33 | 3903.67 | 644.09 | 22.01 | 2131.83 | 3459.83 | ||
Minimum of Months | 263.00 | 0.62 | 0.61 | 861.61 | 19.31 | 0.33 | 258.33 | 419.36 | 20.80 | 101.83 | 222.00 | |
Maximum of Months | 411.67 | 0.63 | 0.61 | 5101.01 | 34.62 | 286.17 | 382.33 | 1124.77 | 26.31 | 255.33 | 330.33 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.83 | 0.80 | 01-JAN-08:00 | 301.69 | 13.68 | 0.00 | 195.50 | 139.89 | 17.11 | 0.00 | 33.83 |
February | 263.00 | 0.84 | 0.80 | 01-FEB-10:09 | 311.13 | 13.86 | 0.00 | 183.17 | 147.54 | 17.25 | 0.00 | 59.67 |
March | 351.67 | 0.82 | 0.80 | 01-MAR-08:20 | 402.95 | 15.41 | 0.00 | 306.33 | 188.03 | 18.66 | 0.00 | 149.33 |
April | 369.33 | 0.81 | 0.80 | 01-APR-07:49 | 489.90 | 16.33 | 0.00 | 336.83 | 223.06 | 19.53 | 0.17 | 205.00 |
May | 407.00 | 0.81 | 0.80 | 01-MAY-06:49 | 623.77 | 17.85 | 17.83 | 388.00 | 284.43 | 21.38 | 69.33 | 334.50 |
June | 411.67 | 0.81 | 0.80 | 01-JUN-06:10 | 693.74 | 19.46 | 55.17 | 391.33 | 318.45 | 22.88 | 153.00 | 353.83 |
July | 411.00 | 0.81 | 0.80 | 01-JUL-05:00 | 704.97 | 18.37 | 27.33 | 393.00 | 308.00 | 22.24 | 140.67 | 345.00 |
August | 390.50 | 0.81 | 0.80 | 01-AUG-06:19 | 619.03 | 17.23 | 0.00 | 368.00 | 280.36 | 20.41 | 32.33 | 314.17 |
September | 298.50 | 0.81 | 0.80 | 01-SEP-06:00 | 453.58 | 16.15 | 0.00 | 311.83 | 213.19 | 19.34 | 0.00 | 171.00 |
October | 293.50 | 0.84 | 0.80 | 01-OCT-07:40 | 316.48 | 14.32 | 0.00 | 213.33 | 155.11 | 17.73 | 0.00 | 74.50 |
November | 299.00 | 0.83 | 0.80 | 01-NOV-07:00 | 312.14 | 13.94 | 0.00 | 231.17 | 147.05 | 17.32 | 0.00 | 26.00 |
December | 285.17 | 0.83 | 0.80 | 01-DEC-08:50 | 292.19 | 13.72 | 0.00 | 194.17 | 137.44 | 17.19 | 0.00 | 7.67 |
Annual Sum or Average | 4071.00 | 0.82 | 483.43 | 16.15 | 100.33 | 3512.67 | 221.87 | 19.55 | 395.50 | 2074.50 | ||
Minimum of Months | 263.00 | 0.81 | 0.80 | 292.19 | 13.68 | 0.00 | 183.17 | 137.44 | 17.11 | 0.00 | 7.67 | |
Maximum of Months | 411.67 | 0.84 | 0.80 | 704.97 | 19.46 | 55.17 | 393.00 | 318.45 | 22.88 | 153.00 | 353.83 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.83 | 0.80 | 01-JAN-08:00 | 301.69 | 13.68 | 0.00 | 195.50 | 139.89 | 17.11 | 0.00 | 33.83 |
February | 263.00 | 0.84 | 0.80 | 01-FEB-10:09 | 311.13 | 13.86 | 0.00 | 183.17 | 147.54 | 17.25 | 0.00 | 59.67 |
March | 351.67 | 0.82 | 0.80 | 01-MAR-08:20 | 402.95 | 15.41 | 0.00 | 306.33 | 188.03 | 18.66 | 0.00 | 149.33 |
April | 369.33 | 0.81 | 0.80 | 01-APR-07:49 | 489.90 | 16.33 | 0.00 | 336.83 | 223.06 | 19.53 | 0.17 | 205.00 |
May | 407.00 | 0.81 | 0.80 | 01-MAY-06:49 | 623.77 | 17.85 | 17.83 | 388.00 | 284.43 | 21.38 | 69.33 | 334.50 |
June | 411.67 | 0.81 | 0.80 | 01-JUN-06:10 | 693.74 | 19.46 | 55.17 | 391.33 | 318.45 | 22.88 | 153.00 | 353.83 |
July | 411.00 | 0.81 | 0.80 | 01-JUL-05:00 | 704.97 | 18.37 | 27.33 | 393.00 | 308.00 | 22.24 | 140.67 | 345.00 |
August | 390.50 | 0.81 | 0.80 | 01-AUG-06:19 | 619.03 | 17.23 | 0.00 | 368.00 | 280.36 | 20.41 | 32.33 | 314.17 |
September | 298.50 | 0.81 | 0.80 | 01-SEP-06:00 | 453.58 | 16.15 | 0.00 | 311.83 | 213.19 | 19.34 | 0.00 | 171.00 |
October | 293.50 | 0.84 | 0.80 | 01-OCT-07:40 | 316.48 | 14.32 | 0.00 | 213.33 | 155.11 | 17.73 | 0.00 | 74.50 |
November | 299.00 | 0.83 | 0.80 | 01-NOV-07:00 | 312.14 | 13.94 | 0.00 | 231.17 | 147.05 | 17.32 | 0.00 | 26.00 |
December | 285.17 | 0.83 | 0.80 | 01-DEC-08:50 | 292.19 | 13.72 | 0.00 | 194.17 | 137.44 | 17.19 | 0.00 | 7.67 |
Annual Sum or Average | 4071.00 | 0.82 | 483.43 | 16.15 | 100.33 | 3512.67 | 221.87 | 19.55 | 395.50 | 2074.50 | ||
Minimum of Months | 263.00 | 0.81 | 0.80 | 292.19 | 13.68 | 0.00 | 183.17 | 137.44 | 17.11 | 0.00 | 7.67 | |
Maximum of Months | 411.67 | 0.84 | 0.80 | 704.97 | 19.46 | 55.17 | 393.00 | 318.45 | 22.88 | 153.00 | 353.83 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.263181E+11 | 129944.10 | 12-JAN-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.215404E+11 | 124522.59 | 14-FEB-23:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139245E+11 | 121681.35 | 13-MAR-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.594075E+10 | 123957.21 | 07-APR-07:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141680E+10 | 93279.96 | 11-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.384825E+09 | 34394.71 | 08-JUN-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 491.46 | 1.64 | 25-AUG-10:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.205837E+09 | 26844.31 | 29-SEP-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136648E+11 | 121316.00 | 07-OCT-04:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152253E+11 | 128057.00 | 30-NOV-08:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203939E+11 | 131748.11 | 07-DEC-23:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119015E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.263181E+11 | 131748.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.362415E+09 | 4305.71 | 18-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6847218.49 | 2822.29 | 01-MAY-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.369263E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.362415E+09 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.220725E+10 | 2453.05 | 08-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138121E+10 | 2763.39 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.373545E+09 | 2147.97 | 08-MAR-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147541E+09 | 1824.83 | 06-APR-09:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7800492.38 | 1785.32 | 11-MAY-06:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7262497.86 | 360.17 | 30-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.229924E+09 | 2598.56 | 31-OCT-07:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.494009E+09 | 1947.63 | 30-NOV-18:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139048E+10 | 2877.89 | 14-DEC-08:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.623902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.220725E+10 | 2877.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.126440E+09 | 716.58 | 02-JAN-11:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 67966785.18 | 596.81 | 04-FEB-16:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 223699.54 | 151.29 | 23-MAR-10:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17333.98 | 67.26 | 22-NOV-11:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11547484.48 | 404.54 | 22-DEC-11:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.126440E+09 | 716.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.124399E+10 | 1318.67 | 23-JAN-11:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.693712E+09 | 2150.31 | 04-FEB-16:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29921444.51 | 740.66 | 23-MAR-09:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 297436.33 | 327.45 | 07-APR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 68903661.20 | 1177.00 | 22-NOV-11:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.471568E+09 | 1186.19 | 18-DEC-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.124399E+10 | 2150.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.907609E+09 | 773.93 | 08-JAN-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.505660E+09 | 1139.24 | 04-FEB-16:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33778856.45 | 444.24 | 23-MAR-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1622844.58 | 189.28 | 07-APR-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 637327.85 | 181.80 | 31-OCT-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 66602079.47 | 661.45 | 22-NOV-11:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.399105E+09 | 720.52 | 18-DEC-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.907609E+09 | 1139.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.357181E+09 | 3473.51 | 31-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.233791E+09 | 5841.73 | 28-FEB-04:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145871E+09 | 11413.97 | 10-MAR-04:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 67876711.74 | 10413.51 | 10-APR-03:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10804562.59 | 9442.49 | 11-MAY-03:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 57766.81 | 288.83 | 08-JUN-04:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 247991.24 | 154.21 | 29-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5159922.02 | 1933.58 | 29-SEP-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164368E+09 | 11533.72 | 04-OCT-03:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174200E+09 | 10118.82 | 20-NOV-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.250249E+09 | 8446.71 | 14-DEC-02:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.357181E+09 | 11533.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108934E+10 | 5123.85 | 09-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.588936E+09 | 3937.12 | 07-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 75316418.33 | 4445.92 | 23-MAR-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15560312.80 | 5013.82 | 06-APR-09:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76643.04 | 127.74 | 29-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 58136920.78 | 5110.94 | 31-OCT-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 67075938.17 | 3331.46 | 30-NOV-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.348898E+09 | 4224.20 | 22-DEC-11:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108934E+10 | 5123.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.581509E+09 | 8565.61 | 08-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124451E+09 | 4522.29 | 07-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6704100.32 | 2422.85 | 22-DEC-14:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.712664E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.581509E+09 | 8565.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.589030E+10 | 7672.01 | 07-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.328685E+10 | 9789.81 | 04-FEB-16:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 54647246.37 | 5776.53 | 23-MAR-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26245356.92 | 5303.76 | 31-OCT-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.256992E+09 | 4146.78 | 30-NOV-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261956E+10 | 6864.73 | 22-DEC-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.589030E+10 | 9789.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.453566E+10 | 4832.20 | 08-JAN-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.252832E+10 | 5449.18 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.246168E+09 | 3114.86 | 23-MAR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52753565.59 | 3617.93 | 06-APR-09:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101992E+09 | 3660.99 | 31-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.632155E+09 | 3308.20 | 22-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243910E+10 | 3862.20 | 18-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.453566E+10 | 5449.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 769843.95 | 2655.88 | 01-MAR-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 817487.47 | 1621.49 | 14-OCT-02:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 451314.12 | 786.72 | 13-NOV-01:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2038645.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 817487.47 | 2655.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.263393E+10 | 7165.15 | 07-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168949E+10 | 10951.96 | 12-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10800.41 | 0.49 | 11-MAR-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11145.87 | 0.50 | 21-APR-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19846.51 | 0.50 | 02-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9866.33 | 0.49 | 30-JUN-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9226.96 | 0.50 | 29-JUL-18:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10492.27 | 0.50 | 24-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17363.33 | 0.49 | 13-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8698.40 | 0.49 | 11-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106521E+09 | 2908.81 | 22-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.400333E+09 | 4936.91 | 18-DEC-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.483037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8698.40 | 0.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.263393E+10 | 10951.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.481018E+10 | 10266.28 | 07-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.291047E+10 | 10299.75 | 03-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.656033E+09 | 9903.97 | 18-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180930E+09 | 9935.82 | 06-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5580859.55 | 2205.85 | 20-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4652360.03 | 3030.74 | 04-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3739237.71 | 2794.57 | 02-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3135848.14 | 3057.71 | 26-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10310628.12 | 2911.51 | 10-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.419253E+09 | 9925.86 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122548E+10 | 10135.41 | 21-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.315654E+10 | 10178.36 | 18-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3135848.14 | 2205.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.481018E+10 | 10299.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.597447E+10 | 10253.28 | 07-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.365505E+10 | 10286.69 | 03-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.910840E+09 | 9946.09 | 19-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.226539E+09 | 9946.17 | 06-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6630705.70 | 2203.63 | 30-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4046526.96 | 3220.52 | 04-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3045791.47 | 3102.64 | 02-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3154238.19 | 3170.16 | 26-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12289944.61 | 3016.38 | 10-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.575135E+09 | 9984.83 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182142E+10 | 10122.70 | 21-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.412762E+10 | 10165.54 | 18-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3045791.47 | 2203.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.597447E+10 | 10286.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.636042E+10 | 23632.35 | 08-JAN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.228262E+10 | 25418.35 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.453660E+09 | 10665.29 | 26-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.909670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.636042E+10 | 25418.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.246163E+11 | 59488.62 | 07-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141119E+11 | 59516.51 | 03-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.220251E+10 | 56635.15 | 22-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.533724E+09 | 56719.97 | 06-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 48955382.26 | 26402.91 | 11-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17313944.45 | 24604.61 | 02-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14110267.83 | 14919.97 | 17-JUL-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13553425.50 | 18134.21 | 25-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86420084.50 | 25258.51 | 12-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.896807E+09 | 56839.92 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.505451E+10 | 57905.51 | 22-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140847E+11 | 58498.81 | 18-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.616808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 13553425.50 | 14919.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.246163E+11 | 59516.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.485229E+10 | 9976.91 | 07-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.287660E+10 | 10004.67 | 12-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.667839E+09 | 9622.06 | 22-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.181615E+09 | 3170.09 | 07-APR-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6241682.40 | 1977.74 | 01-MAY-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 848847.85 | 1651.49 | 30-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 375954.11 | 1257.43 | 24-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6811851.78 | 2093.74 | 16-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.434571E+09 | 9521.33 | 31-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120714E+10 | 9634.92 | 22-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.311012E+10 | 9784.18 | 17-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.485229E+10 | 10004.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.602918E+10 | 9968.81 | 07-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.357631E+10 | 10001.21 | 03-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.903171E+09 | 9639.66 | 22-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.227323E+09 | 3264.05 | 25-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8275317.28 | 1996.52 | 01-MAY-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 861712.45 | 1679.61 | 30-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 413759.87 | 1343.57 | 24-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9511535.06 | 2832.06 | 16-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.599206E+09 | 9559.34 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177350E+10 | 9738.81 | 22-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.408759E+10 | 9867.78 | 18-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.602918E+10 | 10001.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171355E+10 | 3021.58 | 07-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107178E+10 | 3031.45 | 03-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.322087E+09 | 2953.67 | 19-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107100E+09 | 2951.51 | 06-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8598174.84 | 1203.20 | 11-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1256735.69 | 608.71 | 24-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1406900.42 | 687.89 | 05-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1368953.30 | 696.83 | 26-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11863121.66 | 723.82 | 23-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.222101E+09 | 2947.88 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.538096E+09 | 2983.30 | 21-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118311E+10 | 2995.84 | 18-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.518232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1256735.69 | 608.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171355E+10 | 3031.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.207194E+10 | 3016.94 | 07-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130507E+10 | 3026.82 | 03-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.417619E+09 | 2951.43 | 19-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127732E+09 | 2947.03 | 06-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10301196.32 | 1216.73 | 11-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1349557.06 | 678.61 | 13-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1245720.46 | 654.43 | 02-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1334711.97 | 693.95 | 27-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13583156.44 | 678.85 | 16-SEP-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.301064E+09 | 2943.43 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.748502E+09 | 2978.75 | 21-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149170E+10 | 2991.25 | 18-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.649145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1245720.46 | 654.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.207194E+10 | 3026.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.489944E+10 | 14174.37 | 07-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.294343E+10 | 14218.81 | 12-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.708207E+09 | 13643.60 | 22-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.302325E+09 | 13703.11 | 06-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20447152.07 | 3259.75 | 11-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5733547.79 | 3953.57 | 04-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4913773.32 | 3421.83 | 10-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3390671.93 | 3906.63 | 09-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25602241.22 | 3723.21 | 14-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.424320E+09 | 13588.20 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.965624E+09 | 13757.50 | 21-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.282486E+10 | 13898.75 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3390671.93 | 3259.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.489944E+10 | 14218.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.856553E+10 | 0.724078E+10 | 126977.00 | 19-JAN-21:00 | 70492.74 | 0.04 |
February | 0.00 | 0.00 | 0.293440E+11 | 0.290339E+11 | 153415.09 | 26-FEB-14:50 | 153415.09 | 0.08 |
March | 0.00 | 0.00 | 0.889674E+11 | 0.863600E+11 | 238677.08 | 30-MAR-18:05 | 228081.30 | 0.26 |
April | 0.00 | 0.00 | 0.187632E+12 | 0.163441E+12 | 264903.03 | 04-APR-10:33 | 137924.16 | 0.55 |
May | 0.00 | 0.00 | 0.371113E+12 | 0.271948E+12 | 385224.23 | 30-MAY-21:10 | 202580.31 | 0.87 |
June | 0.00 | 0.00 | 0.614128E+12 | 0.395019E+12 | 449776.27 | 22-JUN-20:30 | 221820.55 | 0.89 |
July | 0.00 | 0.00 | 0.800726E+12 | 0.450366E+12 | 463954.09 | 26-JUL-22:40 | 185356.34 | 1.00 |
August | 0.00 | 0.00 | 0.864641E+12 | 0.478682E+12 | 550314.01 | 23-AUG-21:00 | 225341.94 | 1.00 |
September | 0.00 | 0.00 | 0.531446E+12 | 0.331229E+12 | 443011.79 | 27-SEP-18:03 | 185941.48 | 0.97 |
October | 0.00 | 0.00 | 0.203562E+12 | 0.137455E+12 | 487642.06 | 18-OCT-21:00 | 208989.92 | 0.45 |
November | 0.00 | 0.00 | 0.678571E+11 | 0.554719E+11 | 245934.55 | 27-NOV-19:05 | 146319.96 | 0.21 |
December | 0.00 | 0.00 | 0.150454E+11 | 0.128715E+11 | 175771.21 | 13-DEC-11:40 | 97744.49 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.378303E+13 | 0.241912E+13 | 0.54 | |||
Minimum of Months | 0.00 | 0.00 | 0.856553E+10 | 0.724078E+10 | 126977.00 | 70492.74 | 0.04 | |
Maximum of Months | 0.00 | 0.00 | 0.864641E+12 | 0.478682E+12 | 550314.01 | 228081.30 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.176252E+10 | 0.137197E+10 | 23359.34 | 19-JAN-16:00 | 14579.82 | 0.04 |
February | 0.00 | 0.00 | 0.552120E+10 | 0.546661E+10 | 27394.32 | 28-FEB-15:00 | 27394.32 | 0.06 |
March | 0.00 | 0.00 | 0.174097E+11 | 0.157248E+11 | 42240.29 | 31-MAR-11:00 | 23978.21 | 0.25 |
April | 0.00 | 0.00 | 0.353659E+11 | 0.289004E+11 | 49920.11 | 04-APR-10:20 | 23954.48 | 0.55 |
May | 0.00 | 0.00 | 0.702690E+11 | 0.480235E+11 | 61735.64 | 23-MAY-14:00 | 26801.33 | 0.88 |
June | 0.00 | 0.00 | 0.102265E+12 | 0.649232E+11 | 71662.75 | 26-JUN-18:00 | 28106.37 | 0.90 |
July | 0.00 | 0.00 | 0.128587E+12 | 0.723841E+11 | 78472.77 | 26-JUL-07:20 | 26367.60 | 1.00 |
August | 0.00 | 0.00 | 0.130771E+12 | 0.751358E+11 | 77870.35 | 21-AUG-07:40 | 26445.45 | 1.00 |
September | 0.00 | 0.00 | 0.917847E+11 | 0.565505E+11 | 68652.23 | 28-SEP-12:20 | 25963.48 | 0.97 |
October | 0.00 | 0.00 | 0.380799E+11 | 0.248282E+11 | 73445.65 | 19-OCT-02:40 | 24614.96 | 0.43 |
November | 0.00 | 0.00 | 0.147380E+11 | 0.110135E+11 | 46083.55 | 19-NOV-24:00 | 22548.36 | 0.21 |
December | 0.00 | 0.00 | 0.325392E+10 | 0.253842E+10 | 35336.55 | 13-DEC-13:00 | 20784.95 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.639807E+12 | 0.406861E+12 | 0.53 | |||
Minimum of Months | 0.00 | 0.00 | 0.176252E+10 | 0.137197E+10 | 23359.34 | 14579.82 | 0.04 | |
Maximum of Months | 0.00 | 0.00 | 0.130771E+12 | 0.751358E+11 | 78472.77 | 28106.37 | 1.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 72154832.25 | 67102294.79 | 11844.56 | 29-JAN-16:01 | 11844.56 | 0.01 |
February | 0.00 | 0.00 | 0.501092E+09 | 0.485696E+09 | 12727.58 | 26-FEB-16:02 | 12727.58 | 0.02 |
March | 0.00 | 0.00 | 0.207386E+10 | 0.150706E+10 | 13162.28 | 29-MAR-15:02 | 11929.61 | 0.24 |
April | 0.00 | 0.00 | 0.391830E+10 | 0.246589E+10 | 14062.63 | 04-APR-15:02 | 11316.58 | 0.60 |
May | 0.00 | 0.00 | 0.636614E+10 | 0.367505E+10 | 13859.76 | 28-MAY-08:62 | 9716.34 | 0.81 |
June | 0.00 | 0.00 | 0.918022E+10 | 0.568499E+10 | 15983.15 | 29-JUN-08:62 | 9918.48 | 0.90 |
July | 0.00 | 0.00 | 0.106850E+11 | 0.659762E+10 | 15961.22 | 23-JUL-08:62 | 10038.06 | 0.92 |
August | 0.00 | 0.00 | 0.113913E+11 | 0.706438E+10 | 15972.85 | 29-AUG-08:62 | 9923.60 | 0.93 |
September | 0.00 | 0.00 | 0.715719E+10 | 0.404939E+10 | 15675.68 | 17-SEP-08:62 | 9654.62 | 0.86 |
October | 0.00 | 0.00 | 0.319390E+10 | 0.189426E+10 | 15052.81 | 18-OCT-15:02 | 10737.43 | 0.52 |
November | 0.00 | 0.00 | 0.892386E+09 | 0.640229E+09 | 13354.32 | 19-NOV-16:02 | 11076.08 | 0.15 |
December | 0.00 | 0.00 | 0.206467E+09 | 0.141236E+09 | 12222.71 | 12-DEC-16:02 | 11024.97 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.556379E+11 | 0.342729E+11 | 0.50 | |||
Minimum of Months | 0.00 | 0.00 | 72154832.25 | 67102294.79 | 11844.56 | 9654.62 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.113913E+11 | 0.706438E+10 | 15983.15 | 12727.58 | 0.93 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8795731.55 | 7000801.09 | 5101.67 | 19-JAN-19:04 | 2399.85 | 0.00 |
February | 0.00 | 0.00 | 0.227134E+09 | 0.220822E+09 | 12577.64 | 26-FEB-16:02 | 12577.64 | 0.01 |
March | 0.00 | 0.00 | 0.136610E+10 | 0.924887E+09 | 13258.84 | 29-MAR-15:02 | 11649.27 | 0.21 |
April | 0.00 | 0.00 | 0.329050E+10 | 0.197212E+10 | 13822.10 | 04-APR-15:02 | 11056.26 | 0.56 |
May | 0.00 | 0.00 | 0.606379E+10 | 0.347273E+10 | 13883.10 | 23-MAY-15:02 | 11470.60 | 0.79 |
June | 0.00 | 0.00 | 0.911916E+10 | 0.568158E+10 | 15755.68 | 29-JUN-08:62 | 9830.07 | 0.90 |
July | 0.00 | 0.00 | 0.105421E+11 | 0.651963E+10 | 15927.95 | 23-JUL-08:62 | 9829.43 | 0.92 |
August | 0.00 | 0.00 | 0.108146E+11 | 0.661194E+10 | 15393.89 | 24-AUG-08:62 | 9734.38 | 0.93 |
September | 0.00 | 0.00 | 0.622704E+10 | 0.334804E+10 | 15499.22 | 17-SEP-08:62 | 9502.37 | 0.82 |
October | 0.00 | 0.00 | 0.209916E+10 | 0.113824E+10 | 14886.55 | 18-OCT-15:02 | 10606.37 | 0.40 |
November | 0.00 | 0.00 | 0.352430E+09 | 0.212393E+09 | 13501.55 | 05-NOV-15:02 | 11217.87 | 0.10 |
December | 0.00 | 0.00 | 38825595.99 | 20792521.50 | 11136.02 | 11-DEC-16:02 | 10672.55 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.501497E+11 | 0.301302E+11 | 0.47 | |||
Minimum of Months | 0.00 | 0.00 | 8795731.55 | 7000801.09 | 5101.67 | 2399.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.108146E+11 | 0.661194E+10 | 15927.95 | 12577.64 | 0.93 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.153981E+09 | 0.153981E+09 | 11869.75 | 29-JAN-15:30 | 11869.75 | 0.00 |
February | 0.00 | 0.00 | 0.254889E+10 | 0.254889E+10 | 24299.70 | 26-FEB-14:50 | 24299.70 | 0.00 |
March | 0.00 | 0.00 | 0.568513E+10 | 0.413708E+10 | 25288.89 | 30-MAR-13:40 | 16160.68 | 0.12 |
April | 0.00 | 0.00 | 0.807771E+10 | 0.445067E+10 | 23017.06 | 15-APR-14:00 | 18964.95 | 0.31 |
May | 0.00 | 0.00 | 0.116683E+11 | 0.457581E+10 | 19423.06 | 06-MAY-13:30 | 10404.59 | 0.49 |
June | 0.00 | 0.00 | 0.241100E+11 | 0.107137E+11 | 24373.23 | 25-JUN-08:00 | 9390.75 | 0.76 |
July | 0.00 | 0.00 | 0.312998E+11 | 0.146075E+11 | 29454.75 | 13-JUL-21:00 | 12157.09 | 0.87 |
August | 0.00 | 0.00 | 0.398904E+11 | 0.207619E+11 | 33708.05 | 19-AUG-13:40 | 28071.76 | 0.98 |
September | 0.00 | 0.00 | 0.252646E+11 | 0.133684E+11 | 37432.29 | 24-SEP-14:50 | 29324.49 | 0.74 |
October | 0.00 | 0.00 | 0.151589E+11 | 0.105504E+11 | 37630.95 | 11-OCT-15:50 | 29421.20 | 0.30 |
November | 0.00 | 0.00 | 0.613173E+10 | 0.578961E+10 | 28523.32 | 12-NOV-14:00 | 28523.32 | 0.03 |
December | 0.00 | 0.00 | 0.235737E+10 | 0.203853E+10 | 27187.69 | 10-DEC-14:20 | 27187.69 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.172347E+12 | 0.936965E+11 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 0.153981E+09 | 0.153981E+09 | 11869.75 | 9390.75 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.398904E+11 | 0.207619E+11 | 37630.95 | 29421.20 | 0.98 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.593221E+09 | 0.284930E+09 | 52293.68 | 01-JAN-09:02 | 48066.84 | 0.04 |
February | 0.00 | 0.00 | 0.306235E+10 | 0.215929E+10 | 73668.17 | 18-FEB-09:03 | 56578.59 | 0.11 |
March | 0.00 | 0.00 | 0.104793E+11 | 0.662781E+10 | 76241.52 | 30-MAR-15:02 | 69606.20 | 0.25 |
April | 0.00 | 0.00 | 0.241584E+11 | 0.143704E+11 | 83025.40 | 21-APR-18:02 | 60708.64 | 0.54 |
May | 0.00 | 0.00 | 0.421049E+11 | 0.246392E+11 | 84766.15 | 28-MAY-18:02 | 63180.27 | 0.66 |
June | 0.00 | 0.00 | 0.582592E+11 | 0.384010E+11 | 98863.35 | 29-JUN-08:62 | 56238.86 | 0.72 |
July | 0.00 | 0.00 | 0.669330E+11 | 0.431303E+11 | 100437.37 | 23-JUL-08:62 | 59146.74 | 0.76 |
August | 0.00 | 0.00 | 0.664676E+11 | 0.423226E+11 | 96732.99 | 24-AUG-08:62 | 55750.29 | 0.74 |
September | 0.00 | 0.00 | 0.422094E+11 | 0.233504E+11 | 96775.07 | 17-SEP-08:62 | 57489.06 | 0.70 |
October | 0.00 | 0.00 | 0.169080E+11 | 0.832514E+10 | 85827.04 | 01-OCT-18:02 | 59996.58 | 0.52 |
November | 0.00 | 0.00 | 0.592999E+10 | 0.294281E+10 | 77613.74 | 27-NOV-19:03 | 53567.38 | 0.21 |
December | 0.00 | 0.00 | 0.122335E+10 | 0.515030E+09 | 65842.40 | 24-DEC-09:02 | 52444.65 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.338329E+12 | 0.207069E+12 | 0.45 | |||
Minimum of Months | 0.00 | 0.00 | 0.593221E+09 | 0.284930E+09 | 52293.68 | 48066.84 | 0.04 | |
Maximum of Months | 0.00 | 0.00 | 0.669330E+11 | 0.431303E+11 | 100437.37 | 69606.20 | 0.76 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 42686247.45 | 35971623.15 | 9980.75 | 29-JAN-16:01 | 9980.75 | 0.01 |
February | 0.00 | 0.00 | 0.537738E+09 | 0.520641E+09 | 11439.37 | 26-FEB-16:02 | 11439.37 | 0.01 |
March | 0.00 | 0.00 | 0.176465E+10 | 0.123326E+10 | 12093.47 | 29-MAR-15:02 | 10577.71 | 0.25 |
April | 0.00 | 0.00 | 0.377355E+10 | 0.234145E+10 | 12604.88 | 04-APR-15:02 | 10160.10 | 0.61 |
May | 0.00 | 0.00 | 0.656250E+10 | 0.381013E+10 | 12742.13 | 28-MAY-08:62 | 9140.11 | 0.86 |
June | 0.00 | 0.00 | 0.940591E+10 | 0.587970E+10 | 14127.10 | 23-JUN-08:62 | 9047.74 | 0.94 |
July | 0.00 | 0.00 | 0.110831E+11 | 0.701049E+10 | 14298.76 | 30-JUL-08:62 | 8173.45 | 0.95 |
August | 0.00 | 0.00 | 0.115102E+11 | 0.729498E+10 | 14012.30 | 24-AUG-08:62 | 8805.32 | 0.96 |
September | 0.00 | 0.00 | 0.722929E+10 | 0.414342E+10 | 14115.59 | 17-SEP-08:62 | 8698.25 | 0.89 |
October | 0.00 | 0.00 | 0.313949E+10 | 0.183056E+10 | 13538.51 | 18-OCT-15:02 | 9654.18 | 0.54 |
November | 0.00 | 0.00 | 0.776826E+09 | 0.545884E+09 | 12301.63 | 05-NOV-15:02 | 10194.74 | 0.15 |
December | 0.00 | 0.00 | 0.171408E+09 | 0.105991E+09 | 10886.32 | 12-DEC-16:02 | 9781.35 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.559974E+11 | 0.347525E+11 | 0.52 | |||
Minimum of Months | 0.00 | 0.00 | 42686247.45 | 35971623.15 | 9980.75 | 8173.45 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.115102E+11 | 0.729498E+10 | 14298.76 | 11439.37 | 0.96 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8212107.58 | 6498959.59 | 5391.16 | 19-JAN-19:04 | 2836.64 | 0.00 |
February | 0.00 | 0.00 | 0.235910E+09 | 0.223942E+09 | 10909.34 | 28-FEB-16:02 | 10909.34 | 0.01 |
March | 0.00 | 0.00 | 0.103946E+10 | 0.633076E+09 | 11868.94 | 29-MAR-15:02 | 10295.03 | 0.20 |
April | 0.00 | 0.00 | 0.311625E+10 | 0.185861E+10 | 12419.60 | 04-APR-15:02 | 9951.05 | 0.58 |
May | 0.00 | 0.00 | 0.623306E+10 | 0.358953E+10 | 12658.65 | 28-MAY-08:62 | 9050.63 | 0.85 |
June | 0.00 | 0.00 | 0.934123E+10 | 0.585638E+10 | 14006.74 | 23-JUN-08:62 | 8981.09 | 0.95 |
July | 0.00 | 0.00 | 0.109342E+11 | 0.689657E+10 | 14171.16 | 30-JUL-08:62 | 8101.14 | 0.95 |
August | 0.00 | 0.00 | 0.109205E+11 | 0.674658E+10 | 13890.44 | 24-AUG-08:62 | 8697.69 | 0.95 |
September | 0.00 | 0.00 | 0.626960E+10 | 0.342361E+10 | 13996.77 | 17-SEP-08:62 | 8587.03 | 0.87 |
October | 0.00 | 0.00 | 0.201023E+10 | 0.105399E+10 | 13426.11 | 18-OCT-15:02 | 9563.82 | 0.41 |
November | 0.00 | 0.00 | 0.246906E+09 | 0.121868E+09 | 11707.96 | 05-NOV-15:02 | 9368.30 | 0.10 |
December | 0.00 | 0.00 | 29487626.09 | 13778627.97 | 5267.42 | 12-DEC-16:02 | 3453.48 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.503850E+11 | 0.304244E+11 | 0.49 | |||
Minimum of Months | 0.00 | 0.00 | 8212107.58 | 6498959.59 | 5267.42 | 2836.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109342E+11 | 0.689657E+10 | 14171.16 | 10909.34 | 0.95 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 13064503.11 | 12256847.28 | 3093.88 | 29-JAN-16:01 | 3093.88 | 0.00 |
February | 0.00 | 0.00 | 0.107288E+09 | 0.105557E+09 | 3343.50 | 26-FEB-16:02 | 3343.50 | 0.01 |
March | 0.00 | 0.00 | 0.456704E+09 | 0.335114E+09 | 3445.38 | 29-MAR-15:02 | 3140.51 | 0.21 |
April | 0.00 | 0.00 | 0.903451E+09 | 0.581472E+09 | 3726.13 | 21-APR-18:02 | 2647.35 | 0.54 |
May | 0.00 | 0.00 | 0.153915E+10 | 0.889767E+09 | 3780.04 | 28-MAY-08:62 | 2377.71 | 0.80 |
June | 0.00 | 0.00 | 0.229437E+10 | 0.138626E+10 | 4336.36 | 29-JUN-08:62 | 2457.06 | 0.90 |
July | 0.00 | 0.00 | 0.270496E+10 | 0.165526E+10 | 4382.04 | 30-JUL-08:62 | 2165.78 | 0.91 |
August | 0.00 | 0.00 | 0.288477E+10 | 0.176134E+10 | 4353.75 | 29-AUG-08:62 | 2438.13 | 0.93 |
September | 0.00 | 0.00 | 0.168677E+10 | 0.935835E+09 | 4311.72 | 17-SEP-08:62 | 2354.64 | 0.83 |
October | 0.00 | 0.00 | 0.695882E+09 | 0.421512E+09 | 3960.29 | 18-OCT-15:02 | 2816.19 | 0.41 |
November | 0.00 | 0.00 | 0.177174E+09 | 0.131724E+09 | 3498.23 | 19-NOV-16:02 | 2891.93 | 0.09 |
December | 0.00 | 0.00 | 37237538.82 | 27331989.35 | 3227.91 | 12-DEC-16:02 | 2911.50 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.135008E+11 | 0.824343E+10 | 0.47 | |||
Minimum of Months | 0.00 | 0.00 | 13064503.11 | 12256847.28 | 3093.88 | 2165.78 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.288477E+10 | 0.176134E+10 | 4382.04 | 3343.50 | 0.93 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2950383.74 | 2403511.54 | 1493.28 | 19-JAN-19:04 | 727.00 | 0.00 |
February | 0.00 | 0.00 | 48357845.15 | 47192772.29 | 3299.65 | 26-FEB-16:02 | 3299.65 | 0.00 |
March | 0.00 | 0.00 | 0.286593E+09 | 0.195135E+09 | 3478.46 | 29-MAR-15:02 | 3055.67 | 0.17 |
April | 0.00 | 0.00 | 0.741791E+09 | 0.460627E+09 | 3642.84 | 21-APR-18:02 | 2625.14 | 0.50 |
May | 0.00 | 0.00 | 0.145758E+10 | 0.837949E+09 | 3736.95 | 28-MAY-08:62 | 2346.14 | 0.78 |
June | 0.00 | 0.00 | 0.227778E+10 | 0.138115E+10 | 4285.41 | 29-JUN-08:62 | 2452.90 | 0.90 |
July | 0.00 | 0.00 | 0.266778E+10 | 0.163222E+10 | 4369.11 | 23-JUL-08:62 | 2460.56 | 0.91 |
August | 0.00 | 0.00 | 0.273306E+10 | 0.163384E+10 | 4213.23 | 12-AUG-08:62 | 2524.63 | 0.93 |
September | 0.00 | 0.00 | 0.143836E+10 | 0.753893E+09 | 4257.65 | 17-SEP-08:62 | 2311.93 | 0.79 |
October | 0.00 | 0.00 | 0.437665E+09 | 0.243293E+09 | 3911.63 | 18-OCT-15:02 | 2777.78 | 0.30 |
November | 0.00 | 0.00 | 62574977.23 | 39613090.18 | 3553.41 | 05-NOV-15:02 | 2936.20 | 0.06 |
December | 0.00 | 0.00 | 6635476.29 | 4329182.20 | 2219.30 | 11-DEC-16:02 | 1805.82 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.121611E+11 | 0.723165E+10 | 0.45 | |||
Minimum of Months | 0.00 | 0.00 | 2950383.74 | 2403511.54 | 1493.28 | 727.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.273306E+10 | 0.163384E+10 | 4369.11 | 3299.65 | 0.93 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.802700E+09 | 0.758064E+09 | 13969.49 | 29-JAN-16:01 | 13969.49 | 0.02 |
February | 0.00 | 0.00 | 0.161011E+10 | 0.155264E+10 | 15009.41 | 26-FEB-16:02 | 15009.41 | 0.03 |
March | 0.00 | 0.00 | 0.383565E+10 | 0.294313E+10 | 15437.69 | 29-MAR-15:02 | 14117.30 | 0.28 |
April | 0.00 | 0.00 | 0.522361E+10 | 0.333147E+10 | 16871.70 | 21-APR-18:02 | 11769.46 | 0.60 |
May | 0.00 | 0.00 | 0.764970E+10 | 0.426485E+10 | 17070.28 | 28-MAY-18:02 | 12533.84 | 0.80 |
June | 0.00 | 0.00 | 0.108127E+11 | 0.645559E+10 | 19907.56 | 29-JUN-08:62 | 10692.96 | 0.89 |
July | 0.00 | 0.00 | 0.130887E+11 | 0.792589E+10 | 19847.81 | 23-JUL-08:62 | 11267.19 | 0.90 |
August | 0.00 | 0.00 | 0.147792E+11 | 0.942110E+10 | 19719.14 | 29-AUG-08:62 | 10867.47 | 0.92 |
September | 0.00 | 0.00 | 0.102269E+11 | 0.618360E+10 | 19459.98 | 17-SEP-08:62 | 11036.74 | 0.86 |
October | 0.00 | 0.00 | 0.634073E+10 | 0.429420E+10 | 17252.04 | 18-OCT-15:02 | 12975.43 | 0.59 |
November | 0.00 | 0.00 | 0.345081E+10 | 0.275000E+10 | 15940.74 | 27-NOV-19:03 | 11326.36 | 0.24 |
December | 0.00 | 0.00 | 0.173393E+10 | 0.147682E+10 | 14460.26 | 13-DEC-16:03 | 11482.31 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.795547E+11 | 0.513574E+11 | 0.52 | |||
Minimum of Months | 0.00 | 0.00 | 0.802700E+09 | 0.758064E+09 | 13969.49 | 10692.96 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.147792E+11 | 0.942110E+10 | 19907.56 | 15009.41 | 0.92 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 39594.39 | 208794.71 | 25-JAN-19:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 27522.99 | 223861.49 | 12-FEB-09:03 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7984.08 | 200243.14 | 23-MAR-08:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3226.45 | 108487.67 | 06-APR-22:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 584.29 | 88352.35 | 11-MAY-06:02 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 159.10 | 36165.73 | 09-JUN-08:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 13.11 | 18581.63 | 28-JUL-15:05 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 9.72 | 16058.92 | 25-AUG-08:05 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 152.80 | 41724.88 | 15-SEP-08:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 6676.49 | 203632.69 | 25-OCT-08:61 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 11577.56 | 161893.31 | 22-NOV-19:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23311.98 | 180991.54 | 22-DEC-19:01 |
Annual Sum or Average | 0.00 | 9993.20 | ||||
Minimum of Months | 0.00 | 0.00 | 9.72 | 16058.92 | ||
Maximum of Months | 0.00 | 0.00 | 39594.39 | 223861.49 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 6130.43 | 239330.89 | 19-JAN-19:04 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 20505.92 | 323560.96 | 28-FEB-16:02 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 53453.35 | 420441.99 | 30-MAR-18:03 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 110951.33 | 454059.53 | 21-APR-18:02 | 0.00 | 0.00 | 01-APR-00:10 |
May | 202971.84 | 554222.50 | 30-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 333199.29 | 682439.11 | 26-JUN-18:02 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 411548.86 | 726692.52 | 01-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 440526.25 | 740848.06 | 23-AUG-21:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 286766.03 | 672849.23 | 27-SEP-18:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 112976.17 | 657977.47 | 18-OCT-20:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 42181.76 | 414306.66 | 27-NOV-19:03 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 11224.48 | 225864.70 | 13-DEC-11:33 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 170331.21 | 0.00 | ||||
Minimum of Months | 6130.43 | 225864.70 | 0.00 | 0.00 | ||
Maximum of Months | 440526.25 | 740848.06 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 26226.13 | 61409.64 | 31-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26276.70 | 61094.97 | 01-FEB-21:11 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25460.51 | 64159.09 | 08-MAR-07:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23923.63 | 57692.77 | 25-APR-06:21 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22126.97 | 55376.93 | 11-MAY-06:01 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20521.61 | 44749.12 | 07-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19532.11 | 39605.88 | 03-JUL-06:15 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 19481.19 | 39465.08 | 31-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 20323.71 | 44995.33 | 29-SEP-06:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21822.03 | 51713.40 | 21-OCT-07:30 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 23647.59 | 56742.41 | 20-NOV-07:19 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 25247.76 | 60198.98 | 28-DEC-21:01 |
Annual Sum or Average | 0.00 | 22863.13 | ||||
Minimum of Months | 0.00 | 0.00 | 19481.19 | 39465.08 | ||
Maximum of Months | 0.00 | 0.00 | 26276.70 | 64159.09 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 0.91 | 2194.93 | 01-JAN-00:10 | 0.91 |
February | 0.530997E+10 | 0.91 | 2194.93 | 01-FEB-00:03 | 0.91 |
March | 0.587890E+10 | 0.91 | 2194.93 | 01-MAR-00:03 | 0.91 |
April | 0.568926E+10 | 0.90 | 2194.93 | 01-APR-00:10 | 0.91 |
May | 0.587890E+10 | 0.90 | 2194.93 | 01-MAY-00:05 | 0.90 |
June | 0.568926E+10 | 0.90 | 2194.93 | 01-JUN-00:05 | 0.90 |
July | 0.587890E+10 | 0.90 | 2194.93 | 01-JUL-00:10 | 0.90 |
August | 0.587890E+10 | 0.90 | 2194.93 | 01-AUG-00:05 | 0.90 |
September | 0.568926E+10 | 0.90 | 2194.93 | 01-SEP-00:05 | 0.90 |
October | 0.587890E+10 | 0.90 | 2194.93 | 01-OCT-00:10 | 0.90 |
November | 0.568926E+10 | 0.91 | 2194.93 | 01-NOV-00:03 | 0.91 |
December | 0.587890E+10 | 0.91 | 2194.93 | 01-DEC-00:03 | 0.91 |
Annual Sum or Average | 0.692193E+11 | 0.91 | |||
Minimum of Months | 0.530997E+10 | 0.90 | 2194.93 | 0.90 | |
Maximum of Months | 0.587890E+10 | 0.91 | 2194.93 | 0.91 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.330999E+11 | 0.82 | 41205.93 | 23-JAN-21:15 | 1.71 |
February | 0.308429E+11 | 0.84 | 34982.13 | 01-FEB-23:45 | 1.53 |
March | 0.361371E+11 | 0.86 | 34982.13 | 16-MAR-04:40 | 1.53 |
April | 0.359256E+11 | 0.87 | 34982.13 | 06-APR-22:05 | 1.54 |
May | 0.388979E+11 | 0.89 | 28883.45 | 19-MAY-21:10 | 1.35 |
June | 0.403829E+11 | 0.93 | 31394.51 | 29-JUN-21:10 | 1.42 |
July | 0.427556E+11 | 0.94 | 32770.74 | 07-JUL-21:10 | 1.46 |
August | 0.441842E+11 | 0.96 | 35626.65 | 18-AUG-21:10 | 1.54 |
September | 0.400507E+11 | 0.92 | 35241.95 | 07-SEP-21:10 | 1.53 |
October | 0.388498E+11 | 0.89 | 41205.93 | 25-OCT-21:10 | 1.70 |
November | 0.359654E+11 | 0.87 | 41205.93 | 07-NOV-23:40 | 1.70 |
December | 0.348544E+11 | 0.85 | 41205.93 | 09-DEC-21:45 | 1.70 |
Annual Sum or Average | 0.451947E+12 | 0.89 | |||
Minimum of Months | 0.308429E+11 | 0.82 | 28883.45 | 1.35 | |
Maximum of Months | 0.441842E+11 | 0.96 | 41205.93 | 1.71 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:10 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:03 | 0.28 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.28 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:05 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:05 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:05 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:05 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:03 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:03 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:03 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:03 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.28 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:05 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:03 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.233344E+09 | 0.46 | 691.70 | 01-JAN-09:02 | 0.59 |
February | 0.178493E+09 | 0.46 | 691.70 | 01-FEB-09:01 | 0.60 |
March | 0.168161E+09 | 0.45 | 691.70 | 03-MAR-16:02 | 0.60 |
April | 0.231276E+09 | 0.48 | 691.70 | 02-APR-15:02 | 0.59 |
May | 0.318629E+09 | 0.51 | 691.70 | 01-MAY-15:02 | 0.59 |
June | 0.440734E+09 | 0.54 | 691.70 | 01-JUN-08:62 | 0.59 |
July | 0.495677E+09 | 0.55 | 691.70 | 01-JUL-08:62 | 0.59 |
August | 0.521581E+09 | 0.55 | 691.70 | 01-AUG-08:62 | 0.59 |
September | 0.340023E+09 | 0.52 | 691.70 | 01-SEP-08:62 | 0.59 |
October | 0.206904E+09 | 0.47 | 691.70 | 01-OCT-15:02 | 0.59 |
November | 0.132050E+09 | 0.44 | 691.70 | 01-NOV-08:62 | 0.59 |
December | 0.181042E+09 | 0.43 | 691.70 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.344791E+10 | 0.49 | |||
Minimum of Months | 0.132050E+09 | 0.43 | 691.70 | 0.59 | |
Maximum of Months | 0.521581E+09 | 0.55 | 691.70 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.273058E+09 | 0.51 | 683.37 | 01-JAN-09:02 | 0.59 |
February | 0.191595E+09 | 0.48 | 683.37 | 01-FEB-09:01 | 0.60 |
March | 0.141338E+09 | 0.43 | 683.37 | 03-MAR-09:02 | 0.60 |
April | 0.200178E+09 | 0.46 | 683.37 | 02-APR-15:02 | 0.59 |
May | 0.302975E+09 | 0.50 | 683.37 | 01-MAY-15:02 | 0.59 |
June | 0.438521E+09 | 0.54 | 683.37 | 01-JUN-08:62 | 0.59 |
July | 0.489834E+09 | 0.55 | 683.37 | 01-JUL-08:62 | 0.59 |
August | 0.491741E+09 | 0.55 | 683.37 | 01-AUG-08:62 | 0.59 |
September | 0.295156E+09 | 0.50 | 683.37 | 01-SEP-08:62 | 0.59 |
October | 0.154840E+09 | 0.44 | 683.37 | 01-OCT-15:02 | 0.59 |
November | 0.129157E+09 | 0.43 | 683.37 | 01-NOV-08:62 | 0.59 |
December | 0.209354E+09 | 0.46 | 683.37 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.331775E+10 | 0.49 | |||
Minimum of Months | 0.129157E+09 | 0.43 | 683.37 | 0.59 | |
Maximum of Months | 0.491741E+09 | 0.55 | 683.37 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.352827E+09 | 0.18 | 902.11 | 08-JAN-05:10 | 0.60 |
February | 0.272123E+09 | 0.16 | 1046.84 | 26-FEB-14:50 | 0.60 |
March | 0.301091E+09 | 0.14 | 1059.77 | 11-MAR-12:30 | 0.60 |
April | 0.419882E+09 | 0.22 | 1054.79 | 15-APR-14:00 | 0.60 |
May | 0.563620E+09 | 0.30 | 776.06 | 06-MAY-13:40 | 0.59 |
June | 0.104416E+10 | 0.47 | 910.29 | 24-JUN-17:20 | 0.59 |
July | 0.128649E+10 | 0.52 | 1043.38 | 08-JUL-17:20 | 0.59 |
August | 0.159919E+10 | 0.58 | 1227.98 | 19-AUG-13:50 | 0.59 |
September | 0.107739E+10 | 0.44 | 1762.01 | 24-SEP-12:30 | 0.59 |
October | 0.725622E+09 | 0.26 | 1868.16 | 10-OCT-13:40 | 0.59 |
November | 0.316730E+09 | 0.12 | 1253.35 | 06-NOV-14:20 | 0.60 |
December | 0.158951E+09 | 0.08 | 1216.15 | 10-DEC-14:00 | 0.60 |
Annual Sum or Average | 0.811807E+10 | 0.29 | |||
Minimum of Months | 0.158951E+09 | 0.08 | 776.06 | 0.59 | |
Maximum of Months | 0.159919E+10 | 0.58 | 1868.16 | 0.60 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.126852E+10 | 0.43 | 4128.29 | 01-JAN-16:01 | 0.59 |
February | 0.925507E+09 | 0.43 | 4128.29 | 01-FEB-09:01 | 0.60 |
March | 0.790998E+09 | 0.42 | 4128.29 | 04-MAR-09:03 | 0.59 |
April | 0.127751E+10 | 0.42 | 4128.29 | 01-APR-08:62 | 0.60 |
May | 0.199049E+10 | 0.42 | 4128.29 | 01-MAY-15:02 | 0.59 |
June | 0.274019E+10 | 0.44 | 4128.29 | 01-JUN-08:62 | 0.59 |
July | 0.303559E+10 | 0.45 | 4128.29 | 01-JUL-08:62 | 0.59 |
August | 0.296966E+10 | 0.44 | 4128.29 | 01-AUG-08:62 | 0.59 |
September | 0.188818E+10 | 0.42 | 4128.29 | 01-SEP-08:62 | 0.59 |
October | 0.950493E+09 | 0.42 | 4128.29 | 01-OCT-15:02 | 0.59 |
November | 0.696107E+09 | 0.42 | 4128.29 | 02-NOV-15:02 | 0.59 |
December | 0.897620E+09 | 0.42 | 4128.29 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.194309E+11 | 0.43 | |||
Minimum of Months | 0.696107E+09 | 0.42 | 4128.29 | 0.59 | |
Maximum of Months | 0.303559E+10 | 0.45 | 4128.29 | 0.60 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.216243E+09 | 0.46 | 620.00 | 01-JAN-09:02 | 0.59 |
February | 0.167446E+09 | 0.46 | 620.00 | 01-FEB-09:01 | 0.60 |
March | 0.145882E+09 | 0.46 | 620.00 | 02-MAR-16:02 | 0.60 |
April | 0.217567E+09 | 0.49 | 620.00 | 02-APR-15:02 | 0.59 |
May | 0.324492E+09 | 0.54 | 620.00 | 01-MAY-15:02 | 0.59 |
June | 0.450263E+09 | 0.57 | 620.00 | 01-JUN-08:62 | 0.59 |
July | 0.510608E+09 | 0.56 | 620.00 | 01-JUL-08:62 | 0.59 |
August | 0.521985E+09 | 0.57 | 620.00 | 01-AUG-08:62 | 0.59 |
September | 0.340070E+09 | 0.53 | 620.00 | 01-SEP-08:62 | 0.59 |
October | 0.197270E+09 | 0.49 | 620.00 | 01-OCT-15:02 | 0.59 |
November | 0.118292E+09 | 0.44 | 620.00 | 01-NOV-08:62 | 0.59 |
December | 0.164443E+09 | 0.43 | 620.00 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.337456E+10 | 0.50 | |||
Minimum of Months | 0.118292E+09 | 0.43 | 620.00 | 0.59 | |
Maximum of Months | 0.521985E+09 | 0.57 | 620.00 | 0.60 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.255403E+09 | 0.50 | 614.32 | 01-JAN-09:02 | 0.59 |
February | 0.176596E+09 | 0.47 | 614.32 | 01-FEB-09:01 | 0.60 |
March | 0.118044E+09 | 0.43 | 614.32 | 03-MAR-09:02 | 0.60 |
April | 0.183977E+09 | 0.47 | 614.32 | 02-APR-15:02 | 0.59 |
May | 0.308547E+09 | 0.53 | 614.32 | 01-MAY-15:02 | 0.59 |
June | 0.448763E+09 | 0.57 | 614.32 | 01-JUN-08:62 | 0.59 |
July | 0.505285E+09 | 0.56 | 614.32 | 01-JUL-08:62 | 0.59 |
August | 0.493771E+09 | 0.57 | 614.32 | 01-AUG-08:62 | 0.59 |
September | 0.292164E+09 | 0.53 | 614.32 | 01-SEP-08:62 | 0.59 |
October | 0.142579E+09 | 0.44 | 614.32 | 01-OCT-15:02 | 0.59 |
November | 0.114167E+09 | 0.42 | 614.32 | 01-NOV-08:62 | 0.59 |
December | 0.192840E+09 | 0.45 | 614.32 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.323214E+10 | 0.49 | |||
Minimum of Months | 0.114167E+09 | 0.42 | 614.32 | 0.59 | |
Maximum of Months | 0.505285E+09 | 0.57 | 614.32 | 0.60 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 72103839.53 | 0.48 | 181.91 | 01-JAN-09:02 | 0.59 |
February | 54205869.76 | 0.47 | 181.91 | 01-FEB-09:01 | 0.60 |
March | 45564908.17 | 0.45 | 181.91 | 02-MAR-09:02 | 0.59 |
April | 57730107.33 | 0.48 | 181.91 | 02-APR-15:02 | 0.59 |
May | 78797525.47 | 0.52 | 181.91 | 01-MAY-15:02 | 0.59 |
June | 0.111498E+09 | 0.54 | 181.91 | 01-JUN-08:62 | 0.59 |
July | 0.126315E+09 | 0.54 | 181.91 | 01-JUL-08:62 | 0.59 |
August | 0.132637E+09 | 0.55 | 181.91 | 01-AUG-08:62 | 0.59 |
September | 81808362.34 | 0.52 | 181.91 | 01-SEP-15:02 | 0.59 |
October | 51919639.56 | 0.47 | 181.91 | 01-OCT-15:02 | 0.59 |
November | 39447925.00 | 0.44 | 181.91 | 01-NOV-08:62 | 0.59 |
December | 56575854.05 | 0.45 | 181.91 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.908604E+09 | 0.49 | |||
Minimum of Months | 39447925.00 | 0.44 | 181.91 | 0.59 | |
Maximum of Months | 0.132637E+09 | 0.55 | 181.91 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 83677595.70 | 0.54 | 179.48 | 01-JAN-09:02 | 0.59 |
February | 59339040.76 | 0.49 | 179.48 | 01-FEB-09:01 | 0.60 |
March | 39964139.94 | 0.44 | 179.48 | 02-MAR-09:02 | 0.59 |
April | 49523584.40 | 0.46 | 179.48 | 02-APR-15:02 | 0.59 |
May | 74558128.01 | 0.51 | 179.48 | 01-MAY-15:02 | 0.59 |
June | 0.111012E+09 | 0.54 | 179.48 | 01-JUN-08:62 | 0.59 |
July | 0.124801E+09 | 0.54 | 179.48 | 01-JUL-08:62 | 0.59 |
August | 0.125148E+09 | 0.55 | 179.48 | 01-AUG-08:62 | 0.59 |
September | 70072146.82 | 0.50 | 179.48 | 01-SEP-15:02 | 0.59 |
October | 41207944.23 | 0.44 | 179.48 | 01-OCT-15:02 | 0.59 |
November | 41393690.91 | 0.44 | 179.48 | 01-NOV-08:62 | 0.59 |
December | 65766767.83 | 0.49 | 179.48 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.886464E+09 | 0.49 | |||
Minimum of Months | 39964139.94 | 0.44 | 179.48 | 0.59 | |
Maximum of Months | 0.125148E+09 | 0.55 | 179.48 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.263264E+09 | 0.47 | 808.93 | 01-JAN-16:01 | 0.59 |
February | 0.229785E+09 | 0.47 | 808.93 | 01-FEB-09:01 | 0.60 |
March | 0.261518E+09 | 0.48 | 808.93 | 02-MAR-16:02 | 0.60 |
April | 0.298926E+09 | 0.48 | 808.93 | 01-APR-15:02 | 0.60 |
May | 0.377464E+09 | 0.51 | 808.93 | 01-MAY-15:02 | 0.59 |
June | 0.506882E+09 | 0.53 | 808.93 | 01-JUN-08:62 | 0.59 |
July | 0.590705E+09 | 0.54 | 808.93 | 01-JUL-08:62 | 0.59 |
August | 0.664410E+09 | 0.55 | 808.93 | 01-AUG-08:62 | 0.59 |
September | 0.479455E+09 | 0.52 | 808.93 | 01-SEP-15:02 | 0.59 |
October | 0.366036E+09 | 0.50 | 808.93 | 01-OCT-15:02 | 0.59 |
November | 0.247360E+09 | 0.48 | 808.93 | 01-NOV-15:02 | 0.59 |
December | 0.240115E+09 | 0.47 | 808.93 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.452592E+10 | 0.50 | |||
Minimum of Months | 0.229785E+09 | 0.47 | 808.93 | 0.59 | |
Maximum of Months | 0.664410E+09 | 0.55 | 808.93 | 0.60 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.759209E+09 | 0.683288E+09 | 724.58 | 07-JAN-16:02 | 652.12 | 652.12 | 45.50 | 1.19 |
February | 0.478047E+09 | 0.430243E+09 | 789.91 | 12-FEB-07:03 | 710.92 | 710.92 | 47.47 | 1.43 |
March | 0.191712E+09 | 0.172541E+09 | 721.91 | 23-MAR-08:02 | 649.72 | 649.72 | 39.36 | 1.18 |
April | 65452564.84 | 58907308.36 | 561.52 | 06-APR-08:45 | 505.37 | 505.37 | 54.58 | 0.77 |
May | 10162088.24 | 9145879.41 | 465.33 | 10-MAY-03:45 | 418.80 | 418.80 | 44.49 | 0.60 |
June | 2449220.79 | 2204298.71 | 265.38 | 02-JUN-08:05 | 238.84 | 238.84 | 61.80 | 0.30 |
July | 455951.21 | 410356.09 | 248.02 | 28-JUL-15:05 | 223.22 | 223.22 | 63.42 | 0.28 |
August | 396594.94 | 356935.44 | 230.32 | 25-AUG-08:05 | 207.29 | 207.29 | 64.39 | 0.26 |
September | 4632553.34 | 4169298.00 | 294.78 | 12-SEP-08:05 | 265.30 | 265.30 | 62.21 | 0.34 |
October | 0.136338E+09 | 0.122704E+09 | 736.57 | 25-OCT-08:61 | 662.91 | 662.91 | 40.23 | 1.23 |
November | 0.271532E+09 | 0.244379E+09 | 675.63 | 30-NOV-16:01 | 608.07 | 608.07 | 50.40 | 1.04 |
December | 0.525485E+09 | 0.472937E+09 | 763.43 | 21-DEC-19:01 | 687.09 | 687.09 | 65.19 | 1.31 |
Annual Sum or Average | 0.244587E+10 | 0.220129E+10 | ||||||
Minimum of Months | 396594.94 | 356935.44 | 230.32 | 207.29 | 207.29 | 39.36 | 0.26 | |
Maximum of Months | 0.759209E+09 | 0.683288E+09 | 789.91 | 710.92 | 710.92 | 65.19 | 1.43 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 7041353.89 | 6337218.50 | 277.84 | 19-JAN-19:04 | 250.05 | 250.05 | 8.15 | 8.74 |
February | 29396892.32 | 26457203.09 | 344.31 | 28-FEB-16:02 | 309.88 | 309.88 | 7.24 | 9.68 |
March | 0.133910E+09 | 0.120519E+09 | 865.64 | 13-MAR-18:02 | 779.08 | 779.08 | 7.16 | 14.73 |
April | 0.357516E+09 | 0.321765E+09 | 1110.38 | 17-APR-18:02 | 999.34 | 999.34 | 6.75 | 16.43 |
May | 0.675287E+09 | 0.607758E+09 | 1172.37 | 30-MAY-18:03 | 1055.14 | 1055.14 | 6.73 | 16.82 |
June | 0.134260E+10 | 0.120834E+10 | 2265.51 | 26-JUN-18:02 | 2038.96 | 2038.96 | 7.25 | 22.24 |
July | 0.188241E+10 | 0.169417E+10 | 2264.31 | 01-JUL-18:03 | 2037.88 | 2037.88 | 7.23 | 22.23 |
August | 0.211909E+10 | 0.190718E+10 | 2545.75 | 23-AUG-21:00 | 2291.17 | 2291.17 | 7.15 | 23.34 |
September | 0.110137E+10 | 0.991230E+09 | 1908.62 | 27-SEP-18:02 | 1717.76 | 1717.76 | 7.25 | 20.70 |
October | 0.373572E+09 | 0.336215E+09 | 1931.18 | 18-OCT-20:00 | 1738.07 | 1738.07 | 7.24 | 20.80 |
November | 77165414.16 | 69448872.74 | 700.86 | 27-NOV-19:03 | 630.77 | 630.77 | 7.58 | 13.41 |
December | 16126096.81 | 14513487.13 | 231.06 | 12-DEC-19:02 | 207.95 | 207.95 | 7.83 | 8.00 |
Annual Sum or Average | 0.811548E+10 | 0.730393E+10 | ||||||
Minimum of Months | 7041353.89 | 6337218.50 | 231.06 | 207.95 | 207.95 | 6.73 | 8.00 | |
Maximum of Months | 0.211909E+10 | 0.190718E+10 | 2545.75 | 2291.17 | 2291.17 | 8.15 | 23.34 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.487280E+10 | 0.438552E+10 | 5129.64 | 01-JAN-07:35 | 4616.68 | 4616.68 | 8.41 | 35.95 |
February | 0.651187E+10 | 0.586069E+10 | 5129.64 | 01-FEB-00:03 | 4616.68 | 4616.68 | 8.41 | 35.95 |
March | 0.108085E+11 | 0.972761E+10 | 5129.64 | 01-MAR-00:03 | 4616.68 | 4616.68 | 8.60 | 35.95 |
April | 0.124570E+11 | 0.112113E+11 | 5129.64 | 01-APR-00:10 | 4616.68 | 4616.68 | 8.45 | 35.95 |
May | 0.136802E+11 | 0.123122E+11 | 5129.64 | 01-MAY-00:05 | 4616.68 | 4616.68 | 9.04 | 35.95 |
June | 0.132914E+11 | 0.119623E+11 | 5129.64 | 01-JUN-00:05 | 4616.68 | 4616.68 | 9.39 | 35.95 |
July | 0.137392E+11 | 0.123653E+11 | 5129.64 | 01-JUL-00:10 | 4616.68 | 4616.68 | 10.18 | 35.95 |
August | 0.137392E+11 | 0.123653E+11 | 5129.64 | 01-AUG-00:05 | 4616.68 | 4616.68 | 9.42 | 35.95 |
September | 0.132714E+11 | 0.119443E+11 | 5129.64 | 01-SEP-00:05 | 4616.68 | 4616.68 | 9.23 | 35.95 |
October | 0.120024E+11 | 0.108021E+11 | 5129.64 | 01-OCT-00:10 | 4616.68 | 4616.68 | 8.66 | 35.95 |
November | 0.965637E+10 | 0.869073E+10 | 5129.64 | 01-NOV-05:01 | 4616.68 | 4616.68 | 8.41 | 35.95 |
December | 0.662600E+10 | 0.596340E+10 | 5129.64 | 01-DEC-00:03 | 4616.68 | 4616.68 | 8.40 | 35.95 |
Annual Sum or Average | 0.130656E+12 | 0.117591E+12 | ||||||
Minimum of Months | 0.487280E+10 | 0.438552E+10 | 5129.64 | 4616.68 | 4616.68 | 8.40 | 35.95 | |
Maximum of Months | 0.137392E+11 | 0.123653E+11 | 5129.64 | 4616.68 | 4616.68 | 10.18 | 35.95 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 49.24 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 40.12 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 49.13 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.38 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 52.50 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 53.43 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.99 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 54.09 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 53.47 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 52.45 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:03 | 14.37 | 14.37 | 46.50 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 49.82 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 40.12 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.09 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 61.03 | 80.12 | 39594.39 | 208794.71 | 25-JAN-19:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 60.48 | 79.41 | 27522.99 | 223861.49 | 12-FEB-09:03 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 44.56 | 44.56 | 7984.08 | 200243.14 | 23-MAR-08:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 48.93 | 79.40 | 3226.45 | 108487.67 | 06-APR-22:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 34.48 | 34.48 | 584.29 | 88352.35 | 11-MAY-06:02 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 61.85 | 61.85 | 159.10 | 36165.73 | 09-JUN-08:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 59.02 | 59.02 | 13.11 | 18581.63 | 28-JUL-15:05 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 64.43 | 64.43 | 9.72 | 16058.92 | 25-AUG-08:05 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 64.14 | 64.14 | 152.80 | 41724.88 | 15-SEP-08:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 71.45 | 79.40 | 6676.49 | 203632.69 | 25-OCT-08:61 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 64.46 | 79.45 | 11577.56 | 161893.31 | 22-NOV-19:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 59.83 | 80.78 | 23311.98 | 180991.54 | 22-DEC-19:01 |
Annual Sum or Average | 0.00 | 9993.20 | ||||||
Minimum of Months | 0.00 | 0.00 | 34.48 | 34.48 | 9.72 | 16058.92 | ||
Maximum of Months | 0.00 | 0.00 | 71.45 | 80.78 | 39594.39 | 223861.49 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 6130.43 | 239330.89 | 19-JAN-19:04 | 9.70 | 8.11 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 20505.92 | 323560.96 | 28-FEB-16:02 | 9.34 | 7.20 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 53453.35 | 420441.99 | 30-MAR-18:03 | 9.59 | 6.80 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 110951.33 | 454059.53 | 21-APR-18:02 | 10.47 | 7.45 | 0.00 | 0.00 | 01-APR-00:10 |
May | 202971.84 | 554222.50 | 30-MAY-18:03 | 10.38 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 333199.29 | 682439.11 | 26-JUN-18:02 | 11.76 | 7.22 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 411548.86 | 726692.52 | 01-JUL-18:03 | 12.02 | 7.20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 440526.25 | 740848.06 | 23-AUG-21:00 | 12.04 | 7.12 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 286766.03 | 672849.23 | 27-SEP-18:02 | 11.69 | 7.22 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 112976.17 | 657977.47 | 18-OCT-20:40 | 11.58 | 7.21 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 42181.76 | 414306.66 | 27-NOV-19:03 | 10.30 | 7.56 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 11224.48 | 225864.70 | 13-DEC-11:33 | 9.24 | 7.74 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 170331.21 | 0.00 | ||||||
Minimum of Months | 6130.43 | 225864.70 | 9.24 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 440526.25 | 740848.06 | 12.04 | 8.11 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 49.24 | 59.46 | 26226.13 | 61409.64 | 31-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 40.12 | 58.72 | 26276.70 | 61094.97 | 01-FEB-21:11 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 49.13 | 58.32 | 25460.51 | 64159.09 | 08-MAR-07:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.38 | 58.84 | 23923.63 | 57692.77 | 25-APR-06:21 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 52.50 | 58.55 | 22126.97 | 55376.93 | 11-MAY-06:01 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 53.43 | 59.66 | 20521.61 | 44749.12 | 07-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.99 | 59.21 | 19532.11 | 39605.88 | 03-JUL-06:15 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 54.09 | 59.74 | 19481.19 | 39465.08 | 31-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 53.47 | 58.58 | 20323.71 | 44995.33 | 29-SEP-06:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 52.45 | 58.41 | 21822.03 | 51713.40 | 21-OCT-07:30 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 46.50 | 58.19 | 23647.59 | 56742.41 | 20-NOV-07:19 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 49.82 | 58.49 | 25247.76 | 60198.98 | 28-DEC-21:01 |
Annual Sum or Average | 0.00 | 22863.13 | ||||||
Minimum of Months | 0.00 | 0.00 | 40.12 | 58.19 | 19481.19 | 39465.08 | ||
Maximum of Months | 0.00 | 0.00 | 54.09 | 59.74 | 26276.70 | 64159.09 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.432573E+11 | 0.00 | 0.856553E+10 | 0.330999E+11 | 0.00 | 0.00 |
February | 0.309513E+11 | 0.00 | 0.293440E+11 | 0.308429E+11 | 0.00 | 0.00 |
March | 0.148847E+11 | 0.00 | 0.889674E+11 | 0.361371E+11 | 0.00 | 0.00 |
April | 0.658882E+10 | 0.00 | 0.187632E+12 | 0.359256E+11 | 0.00 | 0.00 |
May | 0.144226E+10 | 0.00 | 0.371113E+12 | 0.388979E+11 | 0.00 | 0.00 |
June | 0.384883E+09 | 0.00 | 0.614128E+12 | 0.403829E+11 | 0.00 | 0.00 |
July | 247991.24 | 0.00 | 0.800726E+12 | 0.427556E+11 | 0.00 | 0.00 |
August | 491.46 | 0.00 | 0.864641E+12 | 0.441842E+11 | 0.00 | 0.00 |
September | 0.218336E+09 | 0.00 | 0.531446E+12 | 0.400507E+11 | 0.00 | 0.00 |
October | 0.142469E+11 | 0.00 | 0.203562E+12 | 0.388498E+11 | 0.00 | 0.00 |
November | 0.169857E+11 | 0.00 | 0.678571E+11 | 0.359654E+11 | 0.00 | 0.00 |
December | 0.283311E+11 | 0.00 | 0.150454E+11 | 0.348544E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.157292E+12 | 0.00 | 0.378303E+13 | 0.451947E+12 | 0.00 | 0.00 |
Minimum of Months | 491.46 | 0.00 | 0.856553E+10 | 0.308429E+11 | 0.00 | 0.00 |
Maximum of Months | 0.432573E+11 | 0.00 | 0.864641E+12 | 0.441842E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.263393E+10 | 0.00 | 0.176252E+10 | 0.587890E+10 | 0.00 | 0.00 |
February | 0.168949E+10 | 0.00 | 0.552120E+10 | 0.530997E+10 | 0.00 | 0.00 |
March | 10800.41 | 0.00 | 0.174097E+11 | 0.587890E+10 | 0.00 | 0.00 |
April | 11145.87 | 0.00 | 0.353659E+11 | 0.568926E+10 | 0.00 | 0.00 |
May | 19846.51 | 0.00 | 0.702690E+11 | 0.587890E+10 | 0.00 | 0.00 |
June | 9866.33 | 0.00 | 0.102265E+12 | 0.568926E+10 | 0.00 | 0.00 |
July | 9226.96 | 0.00 | 0.128587E+12 | 0.587890E+10 | 0.00 | 0.00 |
August | 10492.27 | 0.00 | 0.130771E+12 | 0.587890E+10 | 0.00 | 0.00 |
September | 17363.33 | 0.00 | 0.917847E+11 | 0.568926E+10 | 0.00 | 0.00 |
October | 8698.40 | 0.00 | 0.380799E+11 | 0.587890E+10 | 0.00 | 0.00 |
November | 0.106521E+09 | 0.00 | 0.147380E+11 | 0.568926E+10 | 0.00 | 0.00 |
December | 0.400333E+09 | 0.00 | 0.325392E+10 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.483037E+10 | 0.00 | 0.639807E+12 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 8698.40 | 0.00 | 0.176252E+10 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 0.263393E+10 | 0.00 | 0.130771E+12 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.330999E+11 | 0.856564E+10 | 0.432573E+11 | 0.437639E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308429E+11 | 0.293446E+11 | 0.309513E+11 | 0.261707E+12 | 27007660.45 | 0.00 | 0.00 | 0.00 |
March | 0.361371E+11 | 0.889674E+11 | 0.148847E+11 | 0.973275E+11 | 0.414864E+09 | 0.00 | 0.00 | 0.00 |
April | 0.359256E+11 | 0.187632E+12 | 0.658882E+10 | 0.424057E+11 | 0.444440E+10 | 0.00 | 0.00 | 0.00 |
May | 0.388979E+11 | 0.371113E+12 | 0.144226E+10 | 0.593625E+10 | 0.289548E+11 | 0.00 | 0.00 | 0.00 |
June | 0.403829E+11 | 0.614128E+12 | 0.384883E+09 | 0.944749E+09 | 0.118188E+12 | 0.00 | 0.00 | 0.00 |
July | 0.427556E+11 | 0.800726E+12 | 247991.24 | 0.00 | 0.190735E+12 | 0.00 | 0.00 | 0.00 |
August | 0.441842E+11 | 0.864641E+12 | 491.46 | 0.00 | 0.238201E+12 | 0.00 | 0.00 | 0.00 |
September | 0.400507E+11 | 0.531446E+12 | 0.218336E+09 | 0.853036E+09 | 0.710188E+11 | 0.00 | 0.00 | 0.00 |
October | 0.388498E+11 | 0.203562E+12 | 0.142469E+11 | 0.445022E+11 | 0.122659E+11 | 0.00 | 0.00 | 0.00 |
November | 0.359654E+11 | 0.678571E+11 | 0.169857E+11 | 0.135381E+12 | 0.177806E+09 | 0.00 | 0.00 | 0.00 |
December | 0.348544E+11 | 0.150493E+11 | 0.283311E+11 | 0.282766E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.451947E+12 | 0.378303E+13 | 0.157292E+12 | 0.130946E+13 | 0.664427E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.308429E+11 | 0.856564E+10 | 491.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.441842E+11 | 0.864641E+12 | 0.432573E+11 | 0.437639E+12 | 0.238201E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.176252E+10 | 0.263393E+10 | 0.778553E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.552120E+10 | 0.168949E+10 | 0.485872E+11 | 53444276.06 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.174097E+11 | 10800.41 | 0.213263E+11 | 0.107487E+10 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.353659E+11 | 11145.87 | 0.942991E+10 | 0.286232E+10 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.702690E+11 | 19846.51 | 0.163075E+10 | 0.125521E+11 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.102265E+12 | 9866.33 | 0.422124E+09 | 0.414474E+11 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.128587E+12 | 9226.96 | 0.00 | 0.634411E+11 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.130771E+12 | 10492.27 | 0.00 | 0.805632E+11 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.917847E+11 | 17363.33 | 0.344037E+09 | 0.308419E+11 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.380799E+11 | 8698.40 | 0.130335E+11 | 0.621312E+10 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.147380E+11 | 0.106521E+09 | 0.292802E+11 | 0.375782E+09 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.325392E+10 | 0.400333E+09 | 0.548210E+11 | 18646205.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.639807E+12 | 0.483037E+10 | 0.256730E+12 | 0.239444E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.176252E+10 | 8698.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.130771E+12 | 0.263393E+10 | 0.778553E+11 | 0.805632E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.330999E+11 | 0.432573E+11 | 0.856553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308429E+11 | 0.309513E+11 | 0.293440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.361371E+11 | 0.148847E+11 | 0.889674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.359256E+11 | 0.658882E+10 | 0.187632E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.388979E+11 | 0.144226E+10 | 0.371113E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.403829E+11 | 0.384883E+09 | 0.614128E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.427556E+11 | 247991.24 | 0.800726E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.441842E+11 | 491.46 | 0.864641E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.400507E+11 | 0.218336E+09 | 0.531446E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.388498E+11 | 0.142469E+11 | 0.203562E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.359654E+11 | 0.169857E+11 | 0.678571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.348544E+11 | 0.283311E+11 | 0.150454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.451947E+12 | 0.157292E+12 | 0.378303E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.308429E+11 | 491.46 | 0.856553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.441842E+11 | 0.432573E+11 | 0.864641E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 0.263393E+10 | 0.176252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.168949E+10 | 0.552120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 10800.41 | 0.174097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 11145.87 | 0.353659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 19846.51 | 0.702690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 9866.33 | 0.102265E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 9226.96 | 0.128587E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 10492.27 | 0.130771E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 17363.33 | 0.917847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 8698.40 | 0.380799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.106521E+09 | 0.147380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.400333E+09 | 0.325392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.483037E+10 | 0.639807E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 8698.40 | 0.176252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.263393E+10 | 0.130771E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.397724E+11 | 0.00 | 0.00 | 5060528.46 | 0.00 | 0.00 | 0.758059E+10 | 0.00 | 0.95 |
February | 0.404687E+11 | 0.00 | 0.00 | 224541.88 | 2736330.85 | 0.00 | 0.600193E+09 | 0.00 | 0.96 |
March | 0.407001E+11 | 0.00 | 0.00 | 0.00 | 35123218.19 | 0.00 | 0.00 | 0.00 | 0.98 |
April | 0.298269E+11 | 0.00 | 0.00 | 0.00 | 0.548965E+09 | 0.00 | 0.00 | 0.00 | 0.98 |
May | 0.174056E+11 | 0.00 | 0.00 | 0.00 | 0.326521E+10 | 0.00 | 0.00 | 0.00 | 0.98 |
June | 0.597875E+10 | 0.126505E+09 | 0.00 | 1244.22 | 0.142212E+11 | 0.00 | 30263753.17 | 0.00 | 0.91 |
July | 0.596542E+09 | 0.433857E+10 | 0.00 | 377133.56 | 0.198519E+11 | 0.00 | 0.147804E+09 | 0.00 | 0.87 |
August | 9659806.75 | 0.169297E+11 | 0.00 | 1252934.78 | 0.121849E+11 | 0.00 | 0.311349E+09 | 0.00 | 0.88 |
September | 72661399.85 | 0.119429E+11 | 0.00 | 30910732.25 | 0.573051E+09 | 0.00 | 0.121125E+11 | 0.00 | 1.05 |
October | 0.159851E+09 | 0.316073E+10 | 0.00 | 89316432.77 | 55444071.31 | 0.00 | 0.413916E+11 | 0.00 | 1.13 |
November | 0.158716E+09 | 44985986.06 | 0.00 | 0.108348E+09 | 713069.84 | 0.00 | 0.506279E+11 | 0.00 | 1.14 |
December | 0.445297E+10 | 0.00 | 0.00 | 83252493.89 | 0.00 | 0.00 | 0.476791E+11 | 0.00 | 1.03 |
Annual Sum or Average | 0.179603E+12 | 0.365434E+11 | 0.00 | 0.318744E+09 | 0.507392E+11 | 0.00 | 0.160481E+12 | 0.00 | 0.99 |
Minimum of Months | 9659806.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Maximum of Months | 0.407001E+11 | 0.169297E+11 | 0.00 | 0.108348E+09 | 0.198519E+11 | 0.00 | 0.506279E+11 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.370140E+10 | 0.00 | 0.00 | 62774.67 | 0.00 | 0.228479E+10 | 67067791.67 | 0.00 | 2.20 |
February | 0.386153E+10 | 397040.82 | 0.00 | 327581.79 | 0.00 | 0.124681E+10 | 0.147109E+09 | 0.00 | 2.24 |
March | 0.482758E+10 | 3683065.71 | 0.00 | 475798.37 | 1338511.45 | 65790481.16 | 0.314497E+09 | 0.00 | 2.27 |
April | 0.356346E+10 | 16591719.86 | 0.00 | 427473.78 | 55152537.68 | 13611246.65 | 0.238724E+09 | 0.00 | 2.31 |
May | 0.204451E+10 | 0.220498E+09 | 0.00 | 312115.77 | 0.197617E+09 | 0.00 | 0.182241E+09 | 0.00 | 2.27 |
June | 0.639168E+09 | 0.143299E+10 | 0.00 | 211757.06 | 0.439510E+09 | 0.00 | 0.129467E+09 | 0.00 | 2.13 |
July | 77691361.65 | 0.250500E+10 | 0.00 | 33332.23 | 0.739991E+09 | 0.00 | 17377920.71 | 0.00 | 2.11 |
August | 27289997.52 | 0.353119E+10 | 0.00 | 31880.30 | 0.420186E+09 | 0.00 | 13779338.71 | 0.00 | 2.16 |
September | 0.111431E+10 | 0.934174E+09 | 0.00 | 747555.50 | 0.612927E+09 | 0.00 | 0.231355E+09 | 0.00 | 2.27 |
October | 0.382231E+10 | 0.160889E+09 | 0.00 | 1136318.07 | 0.218753E+09 | 13702834.61 | 0.596097E+09 | 0.00 | 2.29 |
November | 0.479189E+10 | 1266156.91 | 0.00 | 740451.84 | 4335869.05 | 0.214682E+09 | 0.357195E+09 | 0.00 | 2.25 |
December | 0.499810E+10 | 0.00 | 0.00 | 321379.95 | 0.00 | 0.831256E+09 | 0.242974E+09 | 0.00 | 2.19 |
Annual Sum or Average | 0.334693E+11 | 0.880668E+10 | 0.00 | 4828419.31 | 0.268981E+10 | 0.467064E+10 | 0.253788E+10 | 0.00 | 2.22 |
Minimum of Months | 27289997.52 | 0.00 | 0.00 | 31880.30 | 0.00 | 0.00 | 13779338.71 | 0.00 | 2.11 |
Maximum of Months | 0.499810E+10 | 0.353119E+10 | 0.00 | 1136318.07 | 0.739991E+09 | 0.228479E+10 | 0.596097E+09 | 0.00 | 2.31 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.460390E+10 | 0.00 | 0.00 | 1510.16 | 0.00 | 0.00 | 10107517.29 | 0.00 | 1.45 |
February | 0.381671E+10 | 0.00 | 0.00 | 117230.35 | 266879.24 | 0.00 | 0.189368E+09 | 0.00 | 1.47 |
March | 0.328953E+10 | 63757.09 | 0.00 | 543037.69 | 3361873.22 | 0.00 | 0.684218E+09 | 0.00 | 1.50 |
April | 0.187622E+10 | 2419614.12 | 0.00 | 1055222.89 | 51121891.53 | 0.00 | 0.105715E+10 | 0.00 | 1.53 |
May | 0.664444E+09 | 80369482.53 | 0.00 | 1517815.95 | 0.242846E+09 | 0.00 | 0.105718E+10 | 0.00 | 1.53 |
June | 0.105191E+09 | 0.103116E+10 | 0.00 | 915063.68 | 0.446242E+09 | 0.00 | 0.498690E+09 | 0.00 | 1.47 |
July | 11580586.21 | 0.194625E+10 | 0.00 | 229241.19 | 0.566206E+09 | 0.00 | 61951912.39 | 0.00 | 1.43 |
August | 887628.50 | 0.265976E+10 | 0.00 | 144454.72 | 0.344586E+09 | 0.00 | 31118316.70 | 0.00 | 1.43 |
September | 0.348121E+09 | 0.729335E+09 | 0.00 | 1115696.34 | 0.430952E+09 | 0.00 | 0.700991E+09 | 0.00 | 1.49 |
October | 0.239643E+10 | 0.117889E+09 | 0.00 | 877092.04 | 0.161011E+09 | 0.00 | 0.985580E+09 | 0.00 | 1.48 |
November | 0.363297E+10 | 0.00 | 0.00 | 238987.59 | 4266683.58 | 0.00 | 0.430945E+09 | 0.00 | 1.47 |
December | 0.451103E+10 | 0.00 | 0.00 | 50326.53 | 0.00 | 0.00 | 0.112324E+09 | 0.00 | 1.44 |
Annual Sum or Average | 0.252570E+11 | 0.656725E+10 | 0.00 | 6805679.13 | 0.225086E+10 | 0.00 | 0.581963E+10 | 0.00 | 1.47 |
Minimum of Months | 887628.50 | 0.00 | 0.00 | 1510.16 | 0.00 | 0.00 | 10107517.29 | 0.00 | 1.43 |
Maximum of Months | 0.460390E+10 | 0.265976E+10 | 0.00 | 1517815.95 | 0.566206E+09 | 0.00 | 0.105718E+10 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.381974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.805068E+09 | 0.00 | 0.00 | 0.69 |
February | 0.347506E+10 | 0.00 | 0.00 | 0.00 | 267503.77 | 0.539547E+09 | 0.00 | 0.00 | 0.70 |
March | 0.397884E+10 | 0.00 | 0.00 | 0.00 | 3433646.61 | 0.00 | 0.00 | 0.00 | 0.71 |
April | 0.290341E+10 | 0.00 | 0.00 | 3062.38 | 53666797.96 | 0.00 | 12466007.03 | 0.00 | 0.72 |
May | 0.164749E+10 | 23361255.54 | 0.00 | 116007.56 | 0.296222E+09 | 0.00 | 54199221.55 | 0.00 | 0.71 |
June | 0.483820E+09 | 0.641781E+09 | 0.00 | 211787.09 | 0.806987E+09 | 0.00 | 0.104970E+09 | 0.00 | 0.67 |
July | 54814599.92 | 0.156927E+10 | 0.00 | 64401.63 | 0.904261E+09 | 0.00 | 17828019.99 | 0.00 | 0.66 |
August | 17943426.32 | 0.212854E+10 | 0.00 | 31778.86 | 0.793636E+09 | 0.00 | 13458303.73 | 0.00 | 0.65 |
September | 0.931535E+09 | 0.244488E+09 | 0.00 | 79108.58 | 0.885639E+09 | 0.00 | 96122173.28 | 0.00 | 0.68 |
October | 0.335131E+10 | 13073777.89 | 0.00 | 5060.13 | 0.261921E+09 | 0.00 | 18282370.94 | 0.00 | 0.70 |
November | 0.407366E+10 | 0.00 | 0.00 | 0.00 | 4276668.03 | 0.00 | 0.00 | 0.00 | 0.69 |
December | 0.462624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7977810.98 | 0.00 | 0.00 | 0.68 |
Annual Sum or Average | 0.293639E+11 | 0.462051E+10 | 0.00 | 511206.21 | 0.401031E+10 | 0.135259E+10 | 0.317326E+09 | 0.00 | 0.69 |
Minimum of Months | 17943426.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
Maximum of Months | 0.462624E+10 | 0.212854E+10 | 0.00 | 211787.09 | 0.904261E+09 | 0.805068E+09 | 0.104970E+09 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895892E+09 | 0.00 | 0.00 | 0.58 |
February | 0.144050E+10 | 0.00 | 0.00 | 0.00 | 129729.59 | 0.506441E+09 | 0.00 | 0.00 | 0.58 |
March | 0.192959E+10 | 0.00 | 0.00 | 0.00 | 1665193.68 | 0.00 | 0.00 | 0.00 | 0.59 |
April | 0.141410E+10 | 0.00 | 0.00 | 0.00 | 26026444.45 | 0.00 | 0.00 | 0.00 | 0.60 |
May | 0.825201E+09 | 0.00 | 0.00 | 0.00 | 0.154804E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
June | 0.281003E+09 | 0.159667E+09 | 0.00 | 6043.54 | 0.521226E+09 | 0.00 | 3879010.34 | 0.00 | 0.55 |
July | 33155277.81 | 0.523053E+09 | 0.00 | 4036.68 | 0.636370E+09 | 0.00 | 2082047.15 | 0.00 | 0.54 |
August | 13283633.45 | 0.703796E+09 | 0.00 | 5658.24 | 0.657532E+09 | 0.00 | 1939244.30 | 0.00 | 0.53 |
September | 0.498313E+09 | 32703406.53 | 0.00 | 0.00 | 0.510321E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.163413E+10 | 0.00 | 0.00 | 0.00 | 0.133362E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
November | 0.197558E+10 | 0.00 | 0.00 | 0.00 | 2074028.40 | 0.00 | 0.00 | 0.00 | 0.58 |
December | 0.213791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109519E+09 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.135297E+11 | 0.141922E+10 | 0.00 | 15738.47 | 0.264351E+10 | 0.151185E+10 | 7900301.78 | 0.00 | 0.57 |
Minimum of Months | 13283633.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.213791E+10 | 0.703796E+09 | 0.00 | 6043.54 | 0.657532E+09 | 0.895892E+09 | 3879010.34 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.104479E+10 | 0.00 | 0.00 | 0.112218E+09 | 0.00 | 0.00 | 0.706812E+11 | 0.00 | 22.23 |
February | 0.605392E+09 | 3625866.11 | 0.00 | 0.101873E+09 | 0.00 | 0.00 | 0.621330E+11 | 0.00 | 22.72 |
March | 0.936102E+09 | 48143503.21 | 0.00 | 0.111995E+09 | 0.00 | 0.00 | 0.615001E+11 | 0.00 | 23.35 |
April | 0.384491E+09 | 0.763905E+09 | 0.00 | 90841118.61 | 5158786.55 | 0.00 | 0.447902E+11 | 0.00 | 23.54 |
May | 0.255682E+09 | 0.483697E+10 | 0.00 | 62645960.99 | 9080531.22 | 0.00 | 0.254321E+11 | 0.00 | 23.25 |
June | 12726541.12 | 0.216785E+11 | 0.00 | 22608877.07 | 24292628.53 | 0.00 | 0.876242E+10 | 0.00 | 21.37 |
July | 1055475.67 | 0.363464E+11 | 0.00 | 4308120.29 | 49682598.56 | 0.00 | 0.103271E+10 | 0.00 | 20.32 |
August | 1423908.95 | 0.430410E+11 | 0.00 | 2239970.96 | 32619912.01 | 0.00 | 0.440362E+09 | 0.00 | 20.13 |
September | 22337263.19 | 0.172207E+11 | 0.00 | 37614968.22 | 26567683.91 | 0.00 | 0.159184E+11 | 0.00 | 22.09 |
October | 0.977836E+09 | 0.434725E+10 | 0.00 | 95728450.86 | 6959328.50 | 0.00 | 0.516951E+11 | 0.00 | 22.81 |
November | 0.938866E+09 | 61829673.46 | 0.00 | 0.111775E+09 | 944876.88 | 0.00 | 0.630670E+11 | 0.00 | 22.71 |
December | 0.820018E+09 | 0.00 | 0.00 | 0.133630E+09 | 0.00 | 0.00 | 0.715338E+11 | 0.00 | 22.11 |
Annual Sum or Average | 0.600072E+10 | 0.128348E+12 | 0.00 | 0.887478E+09 | 0.155306E+09 | 0.00 | 0.476986E+12 | 0.00 | 22.21 |
Minimum of Months | 1055475.67 | 0.00 | 0.00 | 2239970.96 | 0.00 | 0.00 | 0.440362E+09 | 0.00 | 20.13 |
Maximum of Months | 0.104479E+10 | 0.430410E+11 | 0.00 | 0.133630E+09 | 49682598.56 | 0.00 | 0.715338E+11 | 0.00 | 23.54 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.194279E+11 | 0.00 | 0.00 | 3806505.51 | 0.00 | 47528189.87 | 0.643210E+10 | 0.00 | 3.36 |
February | 0.136448E+11 | 1687285.18 | 0.00 | 8206252.76 | 0.00 | 0.00 | 0.893041E+10 | 0.00 | 3.43 |
March | 0.794204E+10 | 17820054.39 | 0.00 | 17852425.59 | 3585513.47 | 0.00 | 0.145786E+11 | 0.00 | 3.52 |
April | 0.478747E+10 | 0.195795E+09 | 0.00 | 16461494.94 | 0.111097E+09 | 0.00 | 0.118409E+11 | 0.00 | 3.59 |
May | 0.153809E+10 | 0.150043E+10 | 0.00 | 16749074.87 | 0.323793E+09 | 0.00 | 0.833305E+10 | 0.00 | 3.59 |
June | 0.407740E+09 | 0.767643E+10 | 0.00 | 6776878.56 | 0.715127E+09 | 0.00 | 0.305642E+10 | 0.00 | 3.46 |
July | 13955627.79 | 0.133034E+11 | 0.00 | 1907848.33 | 0.107043E+10 | 0.00 | 0.422957E+09 | 0.00 | 3.39 |
August | 9260106.42 | 0.168757E+11 | 0.00 | 913057.87 | 0.721928E+09 | 0.00 | 0.188780E+09 | 0.00 | 3.47 |
September | 0.891766E+09 | 0.605540E+10 | 0.00 | 12632470.60 | 0.687505E+09 | 0.00 | 0.518159E+10 | 0.00 | 3.61 |
October | 0.537279E+10 | 0.131856E+10 | 0.00 | 20554183.08 | 0.356882E+09 | 0.00 | 0.139751E+11 | 0.00 | 3.57 |
November | 0.893857E+10 | 16081719.17 | 0.00 | 16324325.69 | 8034396.84 | 0.00 | 0.142009E+11 | 0.00 | 3.47 |
December | 0.155157E+11 | 0.00 | 0.00 | 8571917.71 | 0.00 | 0.00 | 0.105580E+11 | 0.00 | 3.36 |
Annual Sum or Average | 0.784901E+11 | 0.469613E+11 | 0.00 | 0.130756E+09 | 0.399838E+10 | 47528189.87 | 0.976988E+11 | 0.00 | 3.48 |
Minimum of Months | 9260106.42 | 0.00 | 0.00 | 913057.87 | 0.00 | 0.00 | 0.188780E+09 | 0.00 | 3.36 |
Maximum of Months | 0.194279E+11 | 0.168757E+11 | 0.00 | 20554183.08 | 0.107043E+10 | 47528189.87 | 0.145786E+11 | 0.00 | 3.61 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.765169E+11 | 0.00 | 0.00 | 4943026.13 | 0.00 | 0.00 | 0.977730E+10 | 0.00 | 1.62 |
February | 0.537573E+11 | 0.00 | 0.00 | 17960728.11 | 4986519.82 | 0.00 | 0.215760E+11 | 0.00 | 1.65 |
March | 0.348247E+11 | 29676702.96 | 0.00 | 48634813.86 | 34333414.13 | 0.00 | 0.408598E+11 | 0.00 | 1.70 |
April | 0.162831E+11 | 0.195273E+09 | 0.00 | 57562156.34 | 0.806178E+09 | 0.00 | 0.402101E+11 | 0.00 | 1.74 |
May | 0.441185E+10 | 0.301801E+10 | 0.00 | 64374284.78 | 0.313831E+10 | 0.00 | 0.296999E+11 | 0.00 | 1.78 |
June | 0.863854E+09 | 0.241863E+11 | 0.00 | 26989059.96 | 0.464980E+10 | 0.00 | 0.113799E+11 | 0.00 | 1.73 |
July | 12596857.69 | 0.432888E+11 | 0.00 | 7486941.68 | 0.587011E+10 | 0.00 | 0.154274E+10 | 0.00 | 1.69 |
August | 8886462.33 | 0.557259E+11 | 0.00 | 3679938.55 | 0.381093E+10 | 0.00 | 0.682082E+09 | 0.00 | 1.70 |
September | 0.244985E+10 | 0.186376E+11 | 0.00 | 41970362.80 | 0.398439E+10 | 0.00 | 0.187178E+11 | 0.00 | 1.76 |
October | 0.205112E+11 | 0.366078E+10 | 0.00 | 57580240.74 | 0.187930E+10 | 0.00 | 0.448687E+11 | 0.00 | 1.71 |
November | 0.363940E+11 | 5141025.64 | 0.00 | 41797370.91 | 74580056.91 | 0.00 | 0.406307E+11 | 0.00 | 1.65 |
December | 0.642301E+11 | 0.00 | 0.00 | 16587322.56 | 0.00 | 0.00 | 0.225069E+11 | 0.00 | 1.61 |
Annual Sum or Average | 0.310264E+12 | 0.148747E+12 | 0.00 | 0.389566E+09 | 0.242529E+11 | 0.00 | 0.282452E+12 | 0.00 | 1.69 |
Minimum of Months | 8886462.33 | 0.00 | 0.00 | 3679938.55 | 0.00 | 0.00 | 0.682082E+09 | 0.00 | 1.61 |
Maximum of Months | 0.765169E+11 | 0.557259E+11 | 0.00 | 64374284.78 | 0.587011E+10 | 0.00 | 0.448687E+11 | 0.00 | 1.78 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.320968E+09 | 0.00 | 0.00 | 515907.25 | 16609.21 | 0.107974E+10 | 86452042.91 | 2491.65 | 0.47 |
February | 0.268903E+09 | 287159.88 | 0.00 | 1657856.58 | 205576.43 | 0.786328E+09 | 0.245363E+09 | 7981.77 | 0.47 |
March | 0.302847E+09 | 15724284.28 | 19849.84 | 4898818.97 | 5818143.64 | 0.356996E+09 | 0.634654E+09 | 3851.20 | 0.47 |
April | 0.153710E+09 | 68867272.50 | 148981.05 | 6094918.53 | 20423428.70 | 91435698.16 | 0.643885E+09 | 8738.90 | 0.47 |
May | 38114500.50 | 0.327698E+09 | 244487.87 | 4146988.10 | 36407077.81 | 570964.42 | 0.297259E+09 | 12693.13 | 0.47 |
June | 11936923.31 | 0.967341E+09 | 514101.38 | 2184625.11 | 58071915.68 | 109491.34 | 0.119696E+09 | 29199.12 | 0.48 |
July | 437832.38 | 0.140707E+10 | 794098.90 | 97523.91 | 99770281.88 | 17800.73 | 385025.89 | 21240.62 | 0.47 |
August | 744.51 | 0.151297E+10 | 689207.12 | 4406.85 | 79460078.21 | 0.00 | 0.00 | 18461.69 | 0.47 |
September | 23476170.47 | 0.745021E+09 | 852808.51 | 2070485.05 | 80290641.27 | 264982.42 | 0.182510E+09 | 28376.06 | 0.48 |
October | 0.207527E+09 | 0.196841E+09 | 320979.54 | 5218324.87 | 35230513.42 | 0.243377E+09 | 0.591470E+09 | 14413.73 | 0.47 |
November | 0.298094E+09 | 15388419.82 | 124066.81 | 2809201.68 | 10969222.86 | 0.547894E+09 | 0.485621E+09 | 9002.70 | 0.47 |
December | 0.391231E+09 | 759369.85 | 3242.50 | 985516.24 | 1779413.51 | 0.951264E+09 | 0.161892E+09 | 2049.45 | 0.47 |
Annual Sum or Average | 0.201725E+10 | 0.525797E+10 | 3711823.54 | 30684573.14 | 0.428443E+09 | 0.405799E+10 | 0.344919E+10 | 158500.01 | 0.47 |
Minimum of Months | 744.51 | 0.00 | 0.00 | 4406.85 | 16609.21 | 0.00 | 0.00 | 2049.45 | 0.47 |
Maximum of Months | 0.391231E+09 | 0.151297E+10 | 852808.51 | 6094918.53 | 99770281.88 | 0.107974E+10 | 0.643885E+09 | 29199.12 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.224907E+09 | 0.00 | 0.00 | 122296.83 | 16607.26 | 0.123245E+10 | 30018470.30 | 2491.36 | 0.47 |
February | 0.217768E+09 | 103519.17 | 415.58 | 809741.11 | 387301.85 | 0.930264E+09 | 0.153256E+09 | 9422.81 | 0.47 |
March | 0.333258E+09 | 13820147.43 | 30461.58 | 3091798.33 | 7710705.97 | 0.497322E+09 | 0.465571E+09 | 2287.20 | 0.47 |
April | 0.159296E+09 | 64105958.08 | 192347.12 | 5134172.31 | 25130326.18 | 0.111017E+09 | 0.619574E+09 | 9309.58 | 0.47 |
May | 39461340.35 | 0.321647E+09 | 239560.95 | 3953955.83 | 42419476.92 | 549902.56 | 0.296086E+09 | 12825.70 | 0.47 |
June | 12236405.07 | 0.967256E+09 | 480882.03 | 2194739.40 | 58074769.67 | 158523.78 | 0.119322E+09 | 24095.30 | 0.48 |
July | 437781.08 | 0.140606E+10 | 622664.18 | 97470.16 | 0.100783E+09 | 17798.64 | 385023.11 | 17634.81 | 0.47 |
August | 744.42 | 0.150629E+10 | 672165.23 | 4406.33 | 85966291.41 | 0.00 | 0.00 | 20047.55 | 0.48 |
September | 24536803.19 | 0.729055E+09 | 813905.72 | 1762542.33 | 96197364.95 | 238332.81 | 0.181760E+09 | 30192.05 | 0.48 |
October | 0.232467E+09 | 0.178123E+09 | 455402.67 | 3213921.08 | 53785025.02 | 0.331894E+09 | 0.479894E+09 | 15995.53 | 0.47 |
November | 0.313371E+09 | 13374826.22 | 92420.49 | 1251468.13 | 13014172.30 | 0.736830E+09 | 0.282810E+09 | 6189.39 | 0.47 |
December | 0.341406E+09 | 296514.06 | 2159.12 | 287718.68 | 2241935.97 | 0.109797E+10 | 65529228.29 | 3168.09 | 0.47 |
Annual Sum or Average | 0.189915E+10 | 0.520013E+10 | 3602384.67 | 21924230.53 | 0.485727E+09 | 0.493872E+10 | 0.269421E+10 | 153659.38 | 0.47 |
Minimum of Months | 744.42 | 0.00 | 0.00 | 4406.33 | 16607.26 | 0.00 | 0.00 | 2287.20 | 0.47 |
Maximum of Months | 0.341406E+09 | 0.150629E+10 | 813905.72 | 5134172.31 | 0.100783E+09 | 0.123245E+10 | 0.619574E+09 | 30192.05 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.146972E+11 | 0.00 | 0.00 | 1014619.93 | 258990.49 | 0.504721E+10 | 0.426076E+09 | 0.00 | 0.53 |
February | 0.136681E+11 | 3899376.66 | 0.00 | 10479080.77 | 2889911.33 | 0.211924E+10 | 0.185953E+10 | 0.00 | 0.53 |
March | 0.135921E+11 | 0.269255E+09 | 0.00 | 16652677.63 | 23161874.13 | 0.00 | 0.400991E+10 | 0.00 | 0.54 |
April | 0.870709E+10 | 0.911617E+09 | 0.00 | 19521862.16 | 0.301223E+09 | 0.00 | 0.341050E+10 | 0.00 | 0.54 |
May | 0.326137E+10 | 0.462918E+10 | 0.00 | 9062326.75 | 0.311238E+09 | 0.00 | 0.134091E+10 | 0.00 | 0.54 |
June | 0.978757E+09 | 0.137627E+11 | 0.00 | 7337566.53 | 0.148304E+09 | 0.00 | 0.829834E+09 | 0.00 | 0.54 |
July | 10809303.64 | 0.199157E+11 | 0.00 | 15672.22 | 0.526799E+09 | 0.00 | 1895942.89 | 0.00 | 0.54 |
August | 0.00 | 0.215999E+11 | 0.00 | 39697.92 | 1652874.21 | 0.00 | 30149.85 | 0.00 | 0.54 |
September | 0.143983E+10 | 0.107591E+11 | 0.00 | 10103652.70 | 0.443368E+09 | 0.00 | 0.137472E+10 | 0.00 | 0.54 |
October | 0.873238E+10 | 0.248521E+10 | 0.00 | 33011116.93 | 0.666010E+09 | 0.00 | 0.543901E+10 | 0.00 | 0.54 |
November | 0.135596E+11 | 0.209038E+09 | 0.00 | 23019820.53 | 0.150152E+09 | 0.00 | 0.451095E+10 | 0.00 | 0.54 |
December | 0.179918E+11 | 34495379.56 | 0.00 | 9815493.34 | 0.00 | 0.321773E+09 | 0.208808E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.966390E+11 | 0.745800E+11 | 0.00 | 0.140074E+09 | 0.257506E+10 | 0.748822E+10 | 0.252914E+11 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 15672.22 | 0.00 | 0.00 | 30149.85 | 0.00 | 0.53 |
Maximum of Months | 0.179918E+11 | 0.215999E+11 | 0.00 | 33011116.93 | 0.666010E+09 | 0.504721E+10 | 0.543901E+10 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.533123E+10 | 0.00 | 10246.38 | 6497617.96 | 225267.55 | 0.118112E+11 | 0.302808E+10 | 23547.38 | 0.53 |
February | 0.429885E+10 | 1093088.63 | 49559.10 | 17453833.63 | 5567787.13 | 0.674864E+10 | 0.659723E+10 | 80709.65 | 0.53 |
March | 0.459128E+10 | 0.146776E+09 | 509327.37 | 40183782.42 | 0.145176E+09 | 0.116060E+10 | 0.118314E+11 | 35513.00 | 0.53 |
April | 0.223960E+10 | 0.659536E+09 | 1523090.82 | 51813342.32 | 0.552046E+09 | 0.294846E+09 | 0.955417E+10 | 67704.71 | 0.54 |
May | 0.604036E+09 | 0.329405E+10 | 3626008.35 | 37825837.53 | 0.164404E+10 | 4479297.23 | 0.396626E+10 | 60345.39 | 0.54 |
June | 0.186539E+09 | 0.113491E+11 | 3752999.69 | 17992958.75 | 0.256196E+10 | 126221.44 | 0.161177E+10 | 21476.88 | 0.54 |
July | 5938237.69 | 0.168098E+11 | 5162790.84 | 1075231.34 | 0.363309E+10 | 0.00 | 5710928.24 | 28605.80 | 0.54 |
August | 10097.59 | 0.175962E+11 | 3448712.93 | 55484.41 | 0.400777E+10 | 0.00 | 4284.87 | 23242.82 | 0.54 |
September | 0.347554E+09 | 0.794597E+10 | 10861743.82 | 18107783.54 | 0.324854E+10 | 4172857.76 | 0.245559E+10 | 126359.06 | 0.54 |
October | 0.323030E+10 | 0.207883E+10 | 5074636.10 | 40983563.15 | 0.106807E+10 | 0.332417E+09 | 0.106046E+11 | 102443.76 | 0.54 |
November | 0.442285E+10 | 0.174525E+09 | 1281663.44 | 27439854.14 | 0.183431E+09 | 0.287480E+10 | 0.107734E+11 | 50698.33 | 0.54 |
December | 0.547986E+10 | 3958102.41 | 80754.05 | 12173806.23 | 30410516.52 | 0.896726E+10 | 0.595780E+10 | 55439.28 | 0.53 |
Annual Sum or Average | 0.307380E+11 | 0.600598E+11 | 35381532.89 | 0.271603E+09 | 0.170803E+11 | 0.321986E+11 | 0.663860E+11 | 676086.05 | 0.54 |
Minimum of Months | 10097.59 | 0.00 | 10246.38 | 55484.41 | 225267.55 | 0.00 | 4284.87 | 21476.88 | 0.53 |
Maximum of Months | 0.547986E+10 | 0.175962E+11 | 10861743.82 | 51813342.32 | 0.400777E+10 | 0.118112E+11 | 0.118314E+11 | 126359.06 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.328308E+09 | 0.00 | 0.00 | 380731.45 | 16609.21 | 0.108092E+10 | 78060814.13 | 2491.65 | 0.47 |
February | 0.269261E+09 | 287583.67 | 0.00 | 1974712.50 | 205152.64 | 0.766232E+09 | 0.264783E+09 | 7981.77 | 0.47 |
March | 0.281388E+09 | 16096528.00 | 28474.45 | 4814432.93 | 5436042.32 | 0.357207E+09 | 0.655986E+09 | 5084.19 | 0.47 |
April | 0.130862E+09 | 70962261.17 | 165923.53 | 6659772.64 | 18311866.99 | 87173063.02 | 0.670431E+09 | 8369.46 | 0.47 |
May | 27576015.44 | 0.339070E+09 | 158787.89 | 4613839.79 | 25127147.23 | 953309.24 | 0.306948E+09 | 6360.51 | 0.47 |
June | 4638784.32 | 0.991054E+09 | 0.00 | 2439963.79 | 34901650.57 | 0.00 | 0.126848E+09 | 0.00 | 0.48 |
July | 437832.38 | 0.143940E+10 | 263116.55 | 95885.35 | 67987104.76 | 17800.73 | 386664.45 | 2343.95 | 0.47 |
August | 744.51 | 0.153965E+10 | 112667.79 | 4406.85 | 53369281.46 | 0.00 | 0.00 | 1278.06 | 0.47 |
September | 20991469.97 | 0.757764E+09 | 372785.65 | 2383588.42 | 68048882.44 | 47313.18 | 0.184899E+09 | 6757.33 | 0.48 |
October | 0.181092E+09 | 0.201149E+09 | 300601.87 | 5307925.47 | 30947059.88 | 0.261318E+09 | 0.599874E+09 | 9929.09 | 0.47 |
November | 0.293200E+09 | 14767479.22 | 72023.31 | 2796695.57 | 11646208.87 | 0.537537E+09 | 0.500886E+09 | 5000.78 | 0.47 |
December | 0.396913E+09 | 549661.89 | 4398.07 | 871732.53 | 1989121.47 | 0.934877E+09 | 0.172712E+09 | 893.88 | 0.47 |
Annual Sum or Average | 0.193467E+10 | 0.537076E+10 | 1478779.11 | 32343687.28 | 0.317986E+09 | 0.402629E+10 | 0.356181E+10 | 56490.66 | 0.47 |
Minimum of Months | 744.51 | 0.00 | 0.00 | 4406.85 | 16609.21 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.396913E+09 | 0.153965E+10 | 372785.65 | 6659772.64 | 68048882.44 | 0.108092E+10 | 0.670431E+09 | 9929.09 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.237126E+09 | 0.00 | 0.00 | 113540.84 | 16607.26 | 0.122178E+10 | 28481589.46 | 2491.36 | 0.47 |
February | 0.224937E+09 | 80350.44 | 1329.12 | 946377.39 | 410470.58 | 0.902291E+09 | 0.173924E+09 | 8509.27 | 0.47 |
March | 0.336781E+09 | 12812631.66 | 72933.18 | 2769024.03 | 8665752.58 | 0.475856E+09 | 0.483837E+09 | 12284.76 | 0.47 |
April | 0.151713E+09 | 64733706.12 | 162677.69 | 5591303.44 | 24530172.10 | 0.111945E+09 | 0.625773E+09 | 11385.06 | 0.47 |
May | 29650479.58 | 0.336334E+09 | 157908.73 | 4399119.23 | 27820234.77 | 2386307.65 | 0.303616E+09 | 7220.32 | 0.47 |
June | 4555275.58 | 0.991289E+09 | 0.00 | 2458467.67 | 34546463.85 | 0.00 | 0.126897E+09 | 0.00 | 0.48 |
July | 437781.08 | 0.143804E+10 | 262944.28 | 95806.91 | 69176198.14 | 17798.64 | 386686.35 | 2485.12 | 0.47 |
August | 744.42 | 0.153608E+10 | 112335.57 | 4406.33 | 56757060.33 | 0.00 | 0.00 | 1596.93 | 0.47 |
September | 22120152.84 | 0.749354E+09 | 411470.17 | 2046132.78 | 76317706.90 | 513252.19 | 0.183618E+09 | 12620.73 | 0.48 |
October | 0.235659E+09 | 0.190808E+09 | 466387.03 | 3080799.79 | 41085251.60 | 0.336899E+09 | 0.471829E+09 | 19320.01 | 0.47 |
November | 0.324532E+09 | 12840222.15 | 118224.29 | 965672.01 | 13522966.74 | 0.718409E+09 | 0.290356E+09 | 6195.22 | 0.47 |
December | 0.351060E+09 | 295817.51 | 3605.59 | 260085.52 | 2241935.97 | 0.109535E+10 | 58524955.83 | 2418.16 | 0.47 |
Annual Sum or Average | 0.191857E+10 | 0.533267E+10 | 1769815.65 | 22730735.96 | 0.355091E+09 | 0.486545E+10 | 0.274724E+10 | 86526.93 | 0.47 |
Minimum of Months | 744.42 | 0.00 | 0.00 | 4406.33 | 16607.26 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.351060E+09 | 0.153608E+10 | 466387.03 | 5591303.44 | 76317706.90 | 0.122178E+10 | 0.625773E+09 | 19320.01 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.234042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304322E+10 | 0.00 | 0.00 | 0.54 |
February | 0.216890E+11 | 0.00 | 0.00 | 0.00 | 1529746.10 | 0.126890E+10 | 0.00 | 0.00 | 0.55 |
March | 0.227534E+11 | 0.00 | 0.00 | 0.00 | 19635639.41 | 0.00 | 0.00 | 0.00 | 0.55 |
April | 0.166748E+11 | 0.00 | 0.00 | 0.00 | 0.306899E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
May | 0.968745E+10 | 3615137.74 | 0.00 | 37187.33 | 0.182180E+10 | 0.00 | 43129097.46 | 0.00 | 0.56 |
June | 0.302958E+10 | 0.350033E+10 | 0.00 | 368305.48 | 0.460151E+10 | 0.00 | 0.329471E+09 | 0.00 | 0.52 |
July | 0.327134E+09 | 0.851756E+10 | 0.00 | 261512.75 | 0.536134E+10 | 0.00 | 88175212.07 | 0.00 | 0.51 |
August | 78057517.99 | 0.122192E+11 | 0.00 | 235056.69 | 0.419225E+10 | 0.00 | 0.101646E+09 | 0.00 | 0.50 |
September | 0.565525E+10 | 0.121973E+10 | 0.00 | 189417.07 | 0.519577E+10 | 0.00 | 0.220563E+09 | 0.00 | 0.53 |
October | 0.192694E+11 | 0.00 | 0.00 | 0.00 | 0.157258E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
November | 0.232956E+11 | 0.00 | 0.00 | 0.00 | 24456538.71 | 0.00 | 0.00 | 0.00 | 0.54 |
December | 0.264420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59274994.85 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.172306E+12 | 0.254604E+11 | 0.00 | 1091479.32 | 0.230978E+11 | 0.437140E+10 | 0.782984E+09 | 0.00 | 0.54 |
Minimum of Months | 78057517.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.264420E+11 | 0.122192E+11 | 0.00 | 368305.48 | 0.536134E+10 | 0.304322E+10 | 0.329471E+09 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 68310522.60 | 0.00 | 0.00 | 96053.33 | 4152.30 | 0.290934E+09 | 12577978.73 | 622.91 | 0.47 |
February | 58336307.71 | 71789.97 | 0.00 | 339634.30 | 51394.11 | 0.227028E+09 | 39858514.32 | 1995.44 | 0.47 |
March | 75122294.54 | 3909649.15 | 5072.51 | 992321.89 | 1475957.83 | 0.142807E+09 | 0.105927E+09 | 852.76 | 0.47 |
April | 38571527.93 | 16952658.49 | 38308.40 | 1238645.36 | 5368795.65 | 51026198.30 | 0.132945E+09 | 2342.75 | 0.47 |
May | 9448458.38 | 82098506.68 | 60717.82 | 846885.72 | 8928514.66 | 5091876.69 | 69635664.49 | 2745.22 | 0.47 |
June | 2967690.16 | 0.241341E+09 | 162493.54 | 477343.95 | 14977872.58 | 27196.90 | 30009489.27 | 7724.04 | 0.48 |
July | 109458.09 | 0.350014E+09 | 285963.87 | 17628.97 | 26605122.22 | 4450.18 | 103008.48 | 8832.48 | 0.47 |
August | 186.13 | 0.376960E+09 | 280756.21 | 1040.69 | 21033246.17 | 0.00 | 61.03 | 10243.45 | 0.48 |
September | 5947626.62 | 0.184335E+09 | 191971.71 | 386401.85 | 22014622.02 | 5856477.21 | 39889897.35 | 6652.97 | 0.48 |
October | 52902332.06 | 48788896.65 | 98372.14 | 1028151.52 | 9210896.66 | 0.101007E+09 | 0.106961E+09 | 3442.92 | 0.47 |
November | 72771926.63 | 3799486.11 | 31275.79 | 549534.59 | 2789924.56 | 0.185794E+09 | 74488842.88 | 1991.58 | 0.47 |
December | 87324494.78 | 165189.21 | 798.43 | 187194.69 | 469506.63 | 0.264307E+09 | 24524932.69 | 524.56 | 0.47 |
Annual Sum or Average | 0.471813E+09 | 0.130844E+10 | 1155730.41 | 6160836.86 | 0.112930E+09 | 0.127388E+10 | 0.636921E+09 | 47971.08 | 0.47 |
Minimum of Months | 186.13 | 0.00 | 0.00 | 1040.69 | 4152.30 | 0.00 | 61.03 | 524.56 | 0.47 |
Maximum of Months | 87324494.78 | 0.376960E+09 | 285963.87 | 1238645.36 | 26605122.22 | 0.290934E+09 | 0.132945E+09 | 10243.45 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 36548140.14 | 0.00 | 0.00 | 33155.91 | 4151.82 | 0.333715E+09 | 1578199.54 | 622.84 | 0.47 |
February | 44263630.96 | 25879.79 | 180.64 | 164719.24 | 96825.46 | 0.262407E+09 | 18689465.62 | 2278.96 | 0.47 |
March | 81035899.81 | 3474801.37 | 7499.93 | 593984.51 | 1908396.83 | 0.165485E+09 | 77695610.11 | 202.41 | 0.47 |
April | 39773889.55 | 16074958.21 | 38846.86 | 1020999.89 | 6243184.15 | 57431485.60 | 0.125529E+09 | 2496.02 | 0.47 |
May | 9765085.38 | 81160769.69 | 60732.07 | 797429.87 | 9855586.50 | 6114543.31 | 68335865.04 | 2723.53 | 0.47 |
June | 3023985.17 | 0.241326E+09 | 147007.49 | 478861.75 | 14977689.67 | 27193.71 | 29947756.78 | 8620.17 | 0.48 |
July | 109445.27 | 0.350103E+09 | 271029.32 | 17577.29 | 26488183.77 | 4449.66 | 103046.02 | 7502.69 | 0.47 |
August | 186.10 | 0.375448E+09 | 269783.48 | 1026.47 | 22510505.07 | 0.00 | 75.11 | 9890.06 | 0.48 |
September | 6252503.26 | 0.181228E+09 | 202033.25 | 308336.29 | 25086330.78 | 6466758.93 | 39046702.57 | 7483.50 | 0.48 |
October | 57282730.09 | 44465439.65 | 146955.56 | 586459.67 | 13477661.82 | 0.132711E+09 | 71286960.08 | 4743.88 | 0.47 |
November | 73601115.84 | 3342530.61 | 24366.08 | 217118.38 | 3253543.07 | 0.229022E+09 | 30725531.10 | 1462.34 | 0.47 |
December | 68827363.89 | 74128.52 | 499.78 | 60073.99 | 560483.99 | 0.298924E+09 | 8487654.55 | 832.02 | 0.47 |
Annual Sum or Average | 0.420484E+09 | 0.129672E+10 | 1168934.47 | 4279743.28 | 0.124463E+09 | 0.149231E+10 | 0.471426E+09 | 48858.42 | 0.47 |
Minimum of Months | 186.10 | 0.00 | 0.00 | 1026.47 | 4151.82 | 0.00 | 75.11 | 202.41 | 0.47 |
Maximum of Months | 81035899.81 | 0.375448E+09 | 271029.32 | 1020999.89 | 26488183.77 | 0.333715E+09 | 0.125529E+09 | 9890.06 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.449406E+09 | 0.00 | 493.95 | 4313562.51 | 26676.42 | 0.142100E+10 | 0.514666E+09 | 3507.94 | 0.53 |
February | 0.406472E+09 | 461894.56 | 0.00 | 5405776.09 | 329500.23 | 0.100034E+10 | 0.679359E+09 | 12819.69 | 0.53 |
March | 0.388887E+09 | 26918361.55 | 18325.35 | 9479335.86 | 7697898.23 | 0.403241E+09 | 0.128538E+10 | 3256.29 | 0.54 |
April | 0.235212E+09 | 0.111885E+09 | 198882.75 | 8006907.17 | 31574968.60 | 0.151092E+09 | 0.104337E+10 | 5809.02 | 0.54 |
May | 62062353.27 | 0.519138E+09 | 221035.28 | 4788179.43 | 65836754.23 | 4892393.38 | 0.474486E+09 | 14347.29 | 0.54 |
June | 19378160.29 | 0.152692E+10 | 762179.21 | 2231189.38 | 0.120098E+09 | 15828.92 | 0.193478E+09 | 36200.65 | 0.54 |
July | 703212.36 | 0.222401E+10 | 1194200.18 | 118480.38 | 0.196249E+09 | 28590.15 | 656553.63 | 26121.95 | 0.54 |
August | 1195.77 | 0.240259E+10 | 1108846.73 | 6766.77 | 0.155061E+09 | 0.00 | 311.17 | 16129.21 | 0.54 |
September | 37361442.03 | 0.118718E+10 | 779486.39 | 2971147.90 | 0.138990E+09 | 5112724.20 | 0.289145E+09 | 20848.90 | 0.54 |
October | 0.254910E+09 | 0.323866E+09 | 369793.91 | 10793585.04 | 49030774.15 | 0.230883E+09 | 0.118597E+10 | 6430.47 | 0.54 |
November | 0.351076E+09 | 28504313.40 | 95288.41 | 10436041.58 | 13946825.01 | 0.482764E+09 | 0.129896E+10 | 897.69 | 0.54 |
December | 0.453419E+09 | 2076190.14 | 0.00 | 6978658.74 | 2009906.05 | 0.110962E+10 | 0.847793E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.265889E+10 | 0.835354E+10 | 4748532.14 | 65529630.86 | 0.780851E+09 | 0.480899E+10 | 0.781327E+10 | 146369.11 | 0.54 |
Minimum of Months | 1195.77 | 0.00 | 0.00 | 6766.77 | 26676.42 | 0.00 | 311.17 | 0.00 | 0.53 |
Maximum of Months | 0.453419E+09 | 0.240259E+10 | 1194200.18 | 10793585.04 | 0.196249E+09 | 0.142100E+10 | 0.129896E+10 | 36200.65 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111375E+11 | 0.00 | 0.00 | 42187557.71 | 0.00 | 0.00 | 0.322116E+11 | 0.00 | 4.16 |
February | 0.664236E+10 | 2398589.42 | 0.00 | 49102545.00 | 0.00 | 0.00 | 0.324777E+11 | 0.00 | 4.36 |
March | 0.238383E+10 | 33363007.96 | 0.00 | 74027309.50 | 0.00 | 0.00 | 0.389962E+11 | 0.00 | 4.71 |
April | 0.737601E+09 | 0.511359E+09 | 0.00 | 67332498.23 | 1491971.17 | 0.00 | 0.313830E+11 | 0.00 | 4.98 |
May | 44727514.97 | 0.328152E+10 | 0.00 | 56060465.84 | 501868.98 | 0.00 | 0.200762E+11 | 0.00 | 5.17 |
June | 648768.41 | 0.158773E+11 | 0.00 | 21415655.91 | 0.00 | 0.00 | 0.714277E+10 | 0.00 | 4.99 |
July | 0.00 | 0.271401E+11 | 0.00 | 4830782.89 | 0.00 | 0.00 | 0.916794E+09 | 0.00 | 4.81 |
August | 0.00 | 0.325588E+11 | 0.00 | 2443142.56 | 0.00 | 0.00 | 0.390321E+09 | 0.00 | 4.76 |
September | 14390457.47 | 0.122012E+11 | 0.00 | 33064549.68 | 1605986.80 | 0.00 | 0.119214E+11 | 0.00 | 4.93 |
October | 0.150438E+10 | 0.296615E+10 | 0.00 | 66106447.66 | 13685094.48 | 0.00 | 0.339430E+11 | 0.00 | 4.68 |
November | 0.316600E+10 | 38649612.87 | 0.00 | 65181415.27 | 384624.19 | 0.00 | 0.378556E+11 | 0.00 | 4.47 |
December | 0.723260E+10 | 0.00 | 0.00 | 58696658.34 | 0.00 | 0.00 | 0.372977E+11 | 0.00 | 4.22 |
Annual Sum or Average | 0.328640E+11 | 0.946108E+11 | 0.00 | 0.540449E+09 | 17669545.63 | 0.00 | 0.284612E+12 | 0.00 | 4.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2443142.56 | 0.00 | 0.00 | 0.390321E+09 | 0.00 | 4.16 |
Maximum of Months | 0.111375E+11 | 0.325588E+11 | 0.00 | 74027309.50 | 13685094.48 | 0.00 | 0.389962E+11 | 0.00 | 5.17 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.678858E+10 | 0.00 | 0.00 | 57360097.75 | 0.00 | 0.00 | 0.398572E+11 | 0.00 | 4.47 |
February | 0.370572E+10 | 2513953.69 | 0.00 | 62938276.35 | 0.00 | 0.00 | 0.386302E+11 | 0.00 | 4.72 |
March | 0.924197E+09 | 36571587.29 | 0.00 | 90048225.82 | 0.00 | 0.00 | 0.439260E+11 | 0.00 | 5.10 |
April | 0.346818E+09 | 0.555263E+09 | 0.00 | 77399058.45 | 0.00 | 0.00 | 0.342474E+11 | 0.00 | 5.36 |
May | 4103362.93 | 0.352716E+10 | 0.00 | 61562828.63 | 0.00 | 0.00 | 0.214686E+11 | 0.00 | 5.54 |
June | 0.00 | 0.168911E+11 | 0.00 | 23095573.89 | 0.00 | 0.00 | 0.757014E+10 | 0.00 | 5.30 |
July | 0.00 | 0.288499E+11 | 0.00 | 5120024.18 | 0.00 | 0.00 | 0.967956E+09 | 0.00 | 5.10 |
August | 0.00 | 0.344991E+11 | 0.00 | 2598400.70 | 0.00 | 0.00 | 0.410615E+09 | 0.00 | 5.04 |
September | 0.00 | 0.130313E+11 | 0.00 | 36464073.01 | 0.00 | 0.00 | 0.127373E+11 | 0.00 | 5.26 |
October | 0.735398E+09 | 0.319191E+10 | 0.00 | 78677006.10 | 0.00 | 0.00 | 0.375967E+11 | 0.00 | 5.05 |
November | 0.130346E+10 | 41888511.21 | 0.00 | 82331049.91 | 74882.50 | 0.00 | 0.431786E+11 | 0.00 | 4.84 |
December | 0.372714E+10 | 0.00 | 0.00 | 77210401.63 | 0.00 | 0.00 | 0.445719E+11 | 0.00 | 4.57 |
Annual Sum or Average | 0.175354E+11 | 0.100627E+12 | 0.00 | 0.654805E+09 | 74882.50 | 0.00 | 0.325163E+12 | 0.00 | 5.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2598400.70 | 0.00 | 0.00 | 0.410615E+09 | 0.00 | 4.47 |
Maximum of Months | 0.678858E+10 | 0.344991E+11 | 0.00 | 90048225.82 | 74882.50 | 0.00 | 0.445719E+11 | 0.00 | 5.54 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 19890412.22 | 0.00 | 0.00 | 0.138947E+09 | 0.00 | 0.00 | 0.621384E+11 | 0.00 | 19.41 |
February | 28342640.32 | 4608283.49 | 0.00 | 0.119701E+09 | 0.00 | 0.00 | 0.543426E+11 | 0.00 | 20.28 |
March | 72701932.28 | 59907407.80 | 0.00 | 0.136808E+09 | 0.00 | 0.00 | 0.549790E+11 | 0.00 | 21.37 |
April | 8537124.18 | 0.927833E+09 | 0.00 | 0.105892E+09 | 0.00 | 0.00 | 0.386971E+11 | 0.00 | 21.98 |
May | 13313974.59 | 0.547251E+10 | 0.00 | 70712495.83 | 0.00 | 0.00 | 0.213863E+11 | 0.00 | 21.99 |
June | 0.00 | 0.226683E+11 | 0.00 | 25973378.98 | 0.00 | 0.00 | 0.731452E+10 | 0.00 | 20.66 |
July | 0.00 | 0.375215E+11 | 0.00 | 4669836.27 | 0.00 | 0.00 | 0.816812E+09 | 0.00 | 19.86 |
August | 0.00 | 0.433736E+11 | 0.00 | 2744650.81 | 0.00 | 0.00 | 0.389813E+09 | 0.00 | 19.69 |
September | 0.00 | 0.178748E+11 | 0.00 | 45119814.57 | 0.00 | 0.00 | 0.134405E+11 | 0.00 | 21.10 |
October | 0.126454E+09 | 0.434345E+10 | 0.00 | 0.116778E+09 | 0.00 | 0.00 | 0.456456E+11 | 0.00 | 21.13 |
November | 0.136462E+09 | 72199433.90 | 0.00 | 0.132427E+09 | 0.00 | 0.00 | 0.557387E+11 | 0.00 | 20.70 |
December | 53107801.21 | 0.00 | 0.00 | 0.155162E+09 | 0.00 | 0.00 | 0.633636E+11 | 0.00 | 19.70 |
Annual Sum or Average | 0.458810E+09 | 0.132319E+12 | 0.00 | 0.105493E+10 | 0.00 | 0.00 | 0.418253E+12 | 0.00 | 20.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2744650.81 | 0.00 | 0.00 | 0.389813E+09 | 0.00 | 19.41 |
Maximum of Months | 0.136462E+09 | 0.433736E+11 | 0.00 | 0.155162E+09 | 0.00 | 0.00 | 0.633636E+11 | 0.00 | 21.99 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.979951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403373E+10 | 0.00 | 0.00 | 1.06 |
February | 0.100987E+11 | 0.00 | 0.00 | 0.00 | 800129.28 | 0.190939E+10 | 0.00 | 0.00 | 1.08 |
March | 0.118999E+11 | 516038.03 | 0.00 | 0.00 | 9754326.41 | 1157836.72 | 0.00 | 0.00 | 1.09 |
April | 0.854215E+10 | 17303493.76 | 0.00 | 166131.03 | 0.143219E+09 | 0.00 | 0.179364E+09 | 0.00 | 1.11 |
May | 0.478368E+10 | 0.456838E+09 | 0.00 | 563445.07 | 0.500996E+09 | 0.00 | 0.306008E+09 | 0.00 | 1.10 |
June | 0.137114E+10 | 0.381255E+10 | 0.00 | 712544.91 | 0.626749E+09 | 0.00 | 0.386061E+09 | 0.00 | 1.06 |
July | 0.167010E+09 | 0.658955E+10 | 0.00 | 146653.90 | 0.115830E+10 | 0.00 | 50231221.27 | 0.00 | 1.06 |
August | 57749702.77 | 0.841715E+10 | 0.00 | 89572.34 | 0.720763E+09 | 0.00 | 36161479.71 | 0.00 | 1.05 |
September | 0.287695E+10 | 0.169962E+10 | 0.00 | 295055.97 | 0.171044E+10 | 0.00 | 0.196178E+09 | 0.00 | 1.06 |
October | 0.100667E+11 | 50855365.25 | 0.00 | 13520.30 | 0.771680E+09 | 372965.35 | 11667235.79 | 0.00 | 1.08 |
November | 0.119565E+11 | 0.00 | 0.00 | 0.00 | 12791921.90 | 0.228193E+09 | 0.00 | 0.00 | 1.07 |
December | 0.130493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812086E+09 | 0.00 | 0.00 | 1.06 |
Annual Sum or Average | 0.846694E+11 | 0.210444E+11 | 0.00 | 1986923.53 | 0.565550E+10 | 0.698493E+10 | 0.116567E+10 | 0.00 | 1.07 |
Minimum of Months | 57749702.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
Maximum of Months | 0.130493E+11 | 0.841715E+10 | 0.00 | 712544.91 | 0.171044E+10 | 0.403373E+10 | 0.386061E+09 | 0.00 | 1.11 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:59:42
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.184730E+12 | 0.174136E+11 | 0.215188E+12 | 0.896893E+12 | 0.794852E+11 |
February | 0.191074E+12 | 0.127660E+11 | 0.155255E+12 | 0.663973E+12 | 0.108390E+12 |
March | 0.280087E+12 | 0.942490E+10 | 0.113118E+12 | 0.497993E+12 | 0.221160E+12 |
April | 0.314871E+12 | 0.585844E+10 | 0.677297E+11 | 0.326421E+12 | 0.405030E+12 |
May | 0.345593E+12 | 0.149195E+10 | 0.157362E+11 | 0.102343E+12 | 0.735192E+12 |
June | 0.351550E+12 | -0.472576E+10 | -0.627280E+11 | -0.234786E+12 | 0.114264E+13 |
July | 0.326655E+12 | -0.920656E+10 | -0.116316E+12 | -0.476267E+12 | 0.144466E+13 |
August | 0.301397E+12 | -0.110404E+11 | -0.135634E+12 | -0.585234E+12 | 0.154032E+13 |
September | 0.227070E+12 | -0.249698E+10 | -0.307296E+11 | -0.109171E+12 | 0.980926E+12 |
October | 0.217944E+12 | 0.603937E+10 | 0.733955E+11 | 0.344718E+12 | 0.423680E+12 |
November | 0.152652E+12 | 0.101645E+11 | 0.122858E+12 | 0.554373E+12 | 0.178561E+12 |
December | 0.147044E+12 | 0.141929E+11 | 0.175388E+12 | 0.751268E+12 | 0.882470E+11 |
Annual Sum or Average | 0.304067E+13 | 0.498820E+11 | 0.593261E+12 | 0.273252E+13 | 0.734829E+13 |
Minimum of Months | 0.147044E+12 | -0.110404E+11 | -0.135634E+12 | -0.585234E+12 | 0.794852E+11 |
Maximum of Months | 0.351550E+12 | 0.174136E+11 | 0.215188E+12 | 0.896893E+12 | 0.154032E+13 |