Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:59

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020

Simulation Timestamp: 2023-10-16 08:59:32


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 12553.54 1106.50 1106.50
Net Site Energy 12553.54 1106.50 1106.50
Total Source Energy 30728.77 2708.51 2708.51
Net Source Energy 30728.77 2708.51 2708.51


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 4.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 3526.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 767.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 243.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1745.01 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 651.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 630.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 198.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 304.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.74 2540.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 63.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 8219.26 4334.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 4.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 3526.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 767.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 243.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 959.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 14.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 8.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 32.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 630.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 198.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 304.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.74 2540.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 20.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 35.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 4.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 3526.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 767.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 243.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1745.01 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 651.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 630.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 198.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 304.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 90.74 2540.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 63.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 89.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 391.82 224.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 243.62 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 724.47 382.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 89.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 391.82 224.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 243.62 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 724.47 382.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 8219.265 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 8219.265 100.00
     
Total On-Site and Utility Electric Sources 8219.265 100.00
Total Electricity End Uses 8219.265 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 3329.61 98.13
Air to Air Heat Recovery for Heating 63.54 1.87
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 3393.15 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 83.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 8444.83


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:59
RunPeriod RUNPERIOD 1
Weather File Miami Intl Ap FL USA TMY3 WMO#=722020
Latitude [deg] 25.82
Longitude [deg] -80.3
Elevation [m] 11.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 9.1389 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 13.3365 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 13.3365 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 9.2031 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 6.1031 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.8125 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 10.3656 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 8.7188 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 4.5531 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 4.5531 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 6.3938 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 4.5531 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.3656 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.3656 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 11.7219 4.65 2934.4875
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 6.3938 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 6.8557 7.07 41.0709
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 6.8557 7.07 41.0709
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 9.1389 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 13.3365 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 13.3365 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 9.2031 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 6.1031 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.8125 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 10.3656 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 8.7188 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 4.5531 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 4.5531 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 4.5531 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 4.5531 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 4.5531 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 4.5531 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 6.3938 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 4.5531 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 4.5531 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 4.5531 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 10.3656 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 10.3656 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 11.7219 4.65 2934.4875  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 6.3938 18.58 0.0000  
Total 11345.29             6.8557 3.54 41.0709  
Conditioned Total 11345.29             6.8557 3.54 41.0709  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 4.4542 8.82 37.1989
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 27-JUL-19:10 26-DEC-18:10 - - - - - - - - - - 02-JAN-21:10
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 198228.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 88772.42 104248.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 32150.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 30541.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 7774.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 3788.35 217103.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 2396.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 451931.94 321351.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 198228.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 58789.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 29272.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1846.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 30153.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 150.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 30541.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 7774.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 3788.35 217103.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 241.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 1061.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 1093.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 5.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 11167.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2429.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 769.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5526.46 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2063.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1995.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 627.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 963.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 287.39 2754.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 199.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 26030.41 4698.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 984.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 214.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 67.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 487.11 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 175.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 55.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 84.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 242.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2294.38 414.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 984.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 214.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 67.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 487.11 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 175.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 55.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 84.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 242.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2294.38 414.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.71 0.556421 0.547000 1.48 1.00 0.500000 0.000685 0.000068 1.48 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.289413 0.176593 0.547000 0.158309 0.547000 0.500000 0.002158 0.000020 0.158309 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.241751 0.244813 0.547000 0.132238 0.652834 0.500000 0.001556 0.000010 0.132238 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.249083 0.502457 0.547000 0.136248 1.00 0.500000 0.000758 0.000014 0.136248 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.120650 0.598479 0.547000 0.065996 1.00 0.500000 0.000637 0.000007 0.065996 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.26 0.072391 0.547000 1.78 0.547000 0.500000 0.020885 0.000093 1.78 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.27 0.113422 0.547000 0.694045 0.547000 0.500000 0.003359 0.000064 0.694045 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 4.41 0.226014 0.547000 2.41 0.602704 0.500000 0.001686 0.000183 2.41 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.36 0.872299 0.547000 0.744283 1.00 0.500000 0.000437 0.000083 0.744283 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.18 0.115816 0.547000 1.19 0.547000 0.500000 0.003290 0.000086 1.19 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.29 0.110557 0.547000 1.25 0.547000 0.500000 0.003446 0.000089 1.25 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.21 0.064027 0.547000 1.21 0.547000 0.500000 0.010703 0.000056 1.21 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.725299 0.432979 0.547000 0.396738 1.00 0.500000 0.000880 0.000051 0.396738 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 7817.43 0.000068 163.02
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 2308.46 0.000020 53.04
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1167.56 0.000010 25.23
MECH_FLR_1 VAV BOX REHEAT COIL 1567.01 0.000014 34.82
STORAGE_FLR_1 VAV BOX REHEAT COIL 843.94 0.000007 19.01
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 10601.94 0.000093 222.56
CAFE_FLR_1 VAV BOX REHEAT COIL 7355.27 0.000064 161.89
LOBBY_FLR_1 VAV BOX REHEAT COIL 20973.23 0.000183 452.63
ROOM_1_FLR_3 FAN COIL HEATING COIL 3428.08 0.000030 97.94
ROOM_2_FLR_3 FAN COIL HEATING COIL 3428.35 0.000030 97.95
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 20112.85 0.000176 574.65
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 20130.65 0.000176 575.15
ROOM_5_FLR_3 FAN COIL HEATING COIL 3427.07 0.000030 97.92
ROOM_6_FLR_3 FAN COIL HEATING COIL 3427.34 0.000030 97.92
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 9454.18 0.000083 212.80
ROOM_1_FLR_6 FAN COIL HEATING COIL 1040.92 0.000009 29.74
ROOM_2_FLR_6 FAN COIL HEATING COIL 1041.18 0.000009 29.75
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 5021.24 0.000044 143.46
BANQUET_FLR_6 VAV BOX REHEAT COIL 9863.92 0.000086 211.94
DINING_FLR_6 VAV BOX REHEAT COIL 10160.16 0.000089 218.00
KITCHEN_FLR_6 VAV BOX REHEAT COIL 6379.10 0.000056 133.03
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 5863.13 0.000051 135.01
VAV WITH REHEAT HEATING COIL 61474.18 0.000538 1140.74
FLR_3_DOAS HEATING COIL 5950.05 0.000052 110.41
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ZoneExhaust

User-Specified Maximum Flow Rate [m3/s]
LOBBY_FLR_1 EXHAUST FAN 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 0.962384 0.000030 0.000402
ROOM_2_FLR_3 FAN COIL 0.972991 0.000030 0.000406
ROOM_3_MULT19_FLR_3 FAN COIL 4.87 0.000176 0.002001
ROOM_4_MULT19_FLR_3 FAN COIL 5.88 0.000176 0.002547
ROOM_5_FLR_3 FAN COIL 0.859888 0.000030 0.000362
ROOM_6_FLR_3 FAN COIL 0.867992 0.000030 0.000366
ROOM_1_FLR_6 FAN COIL 0.252518 0.000009 0.000105
ROOM_2_FLR_6 FAN COIL 0.254993 0.000009 0.000106
ROOM_3_MULT9_FLR_6 FAN COIL 1.00 0.000044 0.000432
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 0.962384
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 0.972991
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 4.87
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 5.88
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 0.859888
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 0.867992
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.252518
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.254993
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008762 12.80 0.008500 0.000402 0.962384  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008759 12.80 0.008500 0.000406 0.972991  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008695 12.80 0.008500 0.002001 4.87  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008898 12.80 0.008500 0.002547 5.88  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008794 12.80 0.008500 0.000362 0.859888  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008792 12.80 0.008500 0.000366 0.867992  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008750 12.80 0.008500 0.000105 0.252518  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008747 12.80 0.008500 0.000106 0.254993  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008868 12.80 0.008500 0.000432 1.00  
VAV WITH REHEAT COOLING COIL 29.06 6.70 0.013829 11.09 0.008500 0.029093 21.19 814519.63
FLR_3_DOAS COOLING COIL 33.20 6.70 0.017167 11.94 0.008500 0.003869 2.05 108329.82
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 11.66 11.66 21.32 11.66 21.19 21.19 0.300000 0.550138 21.19
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 21.19 11.66
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 11.66
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 21.19
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.029093 0.000016
VAV WITH REHEAT_HEATC_CONTROLLER 0.000538  
FLR_3_DOAS_COOLC_CONTROLLER 0.003869 0.000123
FLR_3_DOAS_HEATC_CONTROLLER 0.000052  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.039690 8178.60  
HEATSYS1 PUMP 0.001949 587.10 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.001949 0.233937
COOLSYS1 0.039690 4.76
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 222837.22 222837.22 0.001949
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.039690 5662.32
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.039690 1111209.45 1114329.22 127.03
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 26.30 23.60 20.30 19.40 20.90 21.60 24.10 26.40 27.70 28.10 28.00 27.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Miami Intl Ap FL USA TMY3 WMO#=722020 25.82 -80.30 -5.00 11.00 101193 1.2027


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 24.49 8.70 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 9.139 5.380 0.000 0.000 0.000 0.000 14.519 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 13.336 10.760 0.000 0.000 0.000 0.000 24.096 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 13.336 10.760 0.000 0.000 0.000 0.000 24.096 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 9.203 5.380 0.000 0.000 0.000 0.000 14.583 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 6.103 2.690 0.000 0.000 0.000 0.000 8.793 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.813 61.680 535.850 0.000 0.000 0.000 603.343 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 10.366 5.380 0.000 0.000 0.000 0.000 15.746 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 8.719 8.070 0.000 0.000 0.000 0.000 16.789 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 6.394 0.000 0.000 0.000 0.000 0.000 6.394 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 10.366 67.820 0.000 0.000 0.000 0.000 78.186 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 10.366 67.820 0.000 0.000 0.000 0.000 78.186 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 11.722 515.227 2419.260 0.000 0.000 0.000 2946.209 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 6.394 0.000 0.000 0.000 0.000 0.000 6.394 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 18084.325 9.139 169.807 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 18084.325
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 894.495 13.336 82.602 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 894.495
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 1035.829 13.336 82.602 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1035.829
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 1511.551 9.203 569.967 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1511.551
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 578.329 6.103 283.494 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 578.329
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 453.605 5.813 54.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 453.605
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1957.673 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1957.673
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 11405.759 8.719 27.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 11405.759
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 111.660 4.553 74.440 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.660
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 111.691 4.553 74.460 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.691
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 2489.757 6.394 118.803 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2489.757
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 111.691 4.553 74.460 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.691
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 3437.839 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3437.839
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 3437.839 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3437.839
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1210.923 11.722 54.453 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1210.923
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 2635.024 6.394 118.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2635.024


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 457.500 4.429 20.573 0.000 0.250 0.000 0.750 ReachInFreezer 457.500 457.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 285.000 2.759 12.816 0.000 0.250 0.000 0.750 ReachInRefrigerator 285.000 285.000


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.464 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.198 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.2832 0.750 0.900 0.450 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 1.287 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.608 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.684 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.608 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.684 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.4124 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.4124 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2887
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.8346
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 3.472
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.6100
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.4545
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.4264
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.4545
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.4264
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 2.165
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 2.165
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.4637404 3.4637404 3.4637404  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.1981135 1.1981135 1.1981135  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.61927053E-06 0.12767249E-08 -0.37968499E-05 0.16832131E-17
21 2 0.77611055 0.17315568E-02 1.0534842 -0.72792597E-06
22 1 -21.915918 0.11588205 -6.3286394 0.20197014
23 0 21.365777 0.10835518 5.5011278  
24 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
25 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
26 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
27 0 21.361010 0.87247630E-01 5.4456762  
28 9 0.16691074E-14 0.45207920E-16 -0.13282787E-09 -0.59403108E-17
29 8 0.19494068E-07 0.16957001E-12 0.35230437E-03 -0.22165426E-09
30 7 -0.11479370E-01 0.90467759E-08 -0.21987867E-01 0.13052461E-03
31 6 0.38463807 0.31869432E-05 0.45441076 -0.45036152E-02
32 5 -4.9884079 0.12028467E-03 -4.3052891 0.60677235E-01
33 4 32.108494 0.99355415E-03 20.908458 -0.41024850
34 3 -109.32288 0.21841230E-02 -54.572312 1.4876971
35 2 195.24423 0.12380226E-02 76.910992 -2.8707534
36 1 -170.46733 0.13310261E-03 -54.975783 2.7333683
37 0 57.057407 0.76355891E-06 15.605832  
38 9 0.14115123E-14 0.53960859E-16 -0.11739578E-09 -0.22900007E-17
39 8 0.17311930E-07 0.20639465E-12 0.32798840E-03 -0.19684260E-09
40 7 -0.10748946E-01 0.11327704E-07 -0.20934514E-01 0.12221941E-03
41 6 0.36478417 0.40360747E-05 0.43737925 -0.42695883E-02
42 5 -4.7945715 0.15382307E-03 -4.1739388 0.58273831E-01
43 4 31.250576 0.12816568E-02 20.393829 -0.39885853
44 3 -107.49604 0.28390629E-02 -53.554356 1.4613070
45 2 193.43186 0.16201491E-02 75.979619 -2.8419759
46 1 -169.79719 0.17527083E-03 -54.709122 2.7216233
47 0 57.057407 0.10123612E-05 15.653272  
48 9 0.65135446E-15 0.56204292E-16 -0.11372497E-09 -0.53489081E-17
49 8 0.16791160E-07 0.21454591E-12 0.32203280E-03 -0.19092129E-09
50 7 -0.10569524E-01 0.11862766E-07 -0.20675571E-01 0.12017931E-03
51 6 0.35990649 0.42391557E-05 0.43318136 -0.42120931E-02
52 5 -4.7469406 0.16196889E-03 -4.1415055 0.57683257E-01
53 4 31.039704 0.13525358E-02 20.266625 -0.39605902
54 3 -107.04684 0.30019179E-02 -53.302690 1.4548183
55 2 192.98603 0.17160237E-02 75.749609 -2.8348971
56 1 -169.63227 0.18593554E-03 -54.643729 2.7187328
57 0 57.057407 0.10758168E-05 15.665287  
58 9 0.14115123E-14 0.53960859E-16 -0.11739578E-09 -0.22900007E-17
59 8 0.17311930E-07 0.20639465E-12 0.32798840E-03 -0.19684260E-09
60 7 -0.10748946E-01 0.11327704E-07 -0.20934514E-01 0.12221941E-03
61 6 0.36478417 0.40360747E-05 0.43737925 -0.42695883E-02
62 5 -4.7945715 0.15382307E-03 -4.1739388 0.58273831E-01
63 4 31.250576 0.12816568E-02 20.393829 -0.39885853
64 3 -107.49604 0.28390629E-02 -53.554356 1.4613070
65 2 193.43186 0.16201491E-02 75.979619 -2.8419759
66 1 -169.79719 0.17527083E-03 -54.709122 2.7216233
67 0 57.057407 0.10123612E-05 15.653272  
68 9 0.65135446E-15 0.56204292E-16 -0.11372497E-09 -0.53489081E-17
69 8 0.16791160E-07 0.21454591E-12 0.32203280E-03 -0.19092129E-09
70 7 -0.10569524E-01 0.11862766E-07 -0.20675571E-01 0.12017931E-03
71 6 0.35990649 0.42391557E-05 0.43318136 -0.42120931E-02
72 5 -4.7469406 0.16196889E-03 -4.1415055 0.57683257E-01
73 4 31.039704 0.13525358E-02 20.266625 -0.39605902
74 3 -107.04684 0.30019179E-02 -53.302690 1.4548183
75 2 192.98603 0.17160237E-02 75.749609 -2.8348971
76 1 -169.63227 0.18593554E-03 -54.643729 2.7187328
77 0 57.057407 0.10758168E-05 15.665287  
78 7 -0.10696287E-14 0.39031946E-16 -0.22096194E-13 0.53014468E-15
79 6 0.18597363E-10 0.52355087E-11 0.51921923E-09 -0.18483703E-10
80 5 -0.10208356E-06 0.25520809E-07 -0.21786771E-05 0.17041956E-06
81 4 0.13587196E-03 0.96408156E-05 0.17589348E-02 -0.28090751E-03
82 3 -0.20124247E-01 0.34048350E-03 -0.21477792 0.43172268E-01
83 2 0.28586126 0.14813331E-02 2.8938873 -0.61762740
84 1 -0.72340799 0.92453067E-03 -7.1302655 1.5680075
85 0 0.46030979 0.18706506E-04 4.4521723  
86 7 -0.22096194E-13 0.39031946E-16 -0.10696287E-14 0.53014468E-15
87 6 0.51921923E-09 0.52355087E-11 0.18597363E-10 -0.18483703E-10
88 5 -0.21786771E-05 0.25520809E-07 -0.10208356E-06 0.17041956E-06
89 4 0.17589348E-02 0.96408156E-05 0.13587196E-03 -0.28090751E-03
90 3 -0.21477792 0.34048350E-03 -0.20124247E-01 0.43172268E-01
91 2 2.8938873 0.14813331E-02 0.28586126 -0.61762740
92 1 -7.1302655 0.92453067E-03 -0.72340799 1.5680075
93 0 4.4521723 0.18706506E-04 0.46030979  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
103 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
104 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
105 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
106 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
107 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
108 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
109 0 1.0055995 0.48413807E-04 60.838472  
110 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
111 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
112 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
113 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
114 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
115 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
116 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
117 0 1.0055995 0.48413807E-04 60.838472  
118 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
119 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
120 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
121 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
122 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
123 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
124 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
125 0 1.0055995 0.48413807E-04 60.838472  
126 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
127 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
128 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
129 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
130 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
131 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
132 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
133 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.5119_SHGC_0.25 37 1 VerySmooth 2.910 2.910 1.000 0.251    
2 RESWINDOW_U_0.5119_SHGC_0.25 38 1 VerySmooth 2.910 2.910 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   1.79780E-002 0.16139 0.60964 0.60964 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10364 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   1.79780E-002 0.16139 0.60964 0.60964 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10364 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 1.500
2 RACK2 1 0 Zone Air-Cooled 3.000


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 0.576 0.5074
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 0.263 2.9576E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 3.921E-002 5.846E-004 2.885E-004 0.531 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 1.513E-002 1.949E-004 5.306E-004 0.177 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 3.577E-002 2.178E-004 5.696E-004 0.198 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 2.064E-002 2.178E-004 4.726E-004 0.198 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 4.884E-002 6.258E-004 5.569E-004 0.569 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 8.667E-002 4.589E-004 2.527E-004 0.417 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.248 1.893E-004 3.620E-004 0.172 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 6.349E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 6.350E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 2.751E-002 7.066E-005 5.696E-004 8.345E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.164E-002 4.746E-004 2.589E-004 0.561 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 4.974E-002 4.815E-004 2.609E-004 0.569 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 4.868E-002 1.181E-004 9.784E-005 0.140 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 7.4607E-002
2 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 2.9204E-002
3 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 8.0785E-002
4 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 3.0178E-002
5 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 6.0528E-002
6 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 2.0974E-002
7 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 2.6511E-002
8 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 8.7811E-003
9 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 8.3109E-002
10 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 3.6615E-002
11 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 8.9976E-002
12 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 3.7980E-002
13 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 6.6905E-002
14 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 2.6957E-002
15 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 2.9789E-002
16 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 1.2036E-002
17 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.9812E-002
18 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.1108E-002
19 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.5442E-002
20 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 8.4786E-003
21 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.4441E-002
22 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 5.7580E-003
23 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.6108E-002
24 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 9.2309E-003
25 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.9812E-002
26 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.1108E-002
27 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.5442E-002
28 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 8.4786E-003
29 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.4441E-002
30 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 5.7580E-003
31 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.6108E-002
32 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 9.2309E-003


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 37253.40731 37253.40731 2.70994 2.70994 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 29.24700 1.71597E-002 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 0.85446   00:10:00 8.70000 6.99286E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 3977.79264 3977.79264 0.28941 0.28941 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 33.20000 1.71672E-002 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 1473.81668 1473.81668 6.32467E-002 7.92179E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 8.70000 6.99286E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3322.85955 3322.85955 0.24175 0.24175 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59200 1.71642E-002 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 470.38968 470.38968 2.01862E-002 9.17347E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 8.70000 6.99286E-003 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 3424.33768 3424.33768 0.24908 0.24908 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 20:00:00 29.85000 1.71608E-002 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 848.74836 848.74836 3.64230E-002 3.64230E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 8.70000 6.99286E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1658.65969 1658.65969 0.12065 0.12065 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 31.70367 1.71644E-002 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 496.03216 496.03216 2.12866E-002 5.77652E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 8.70000 6.99286E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 44807.78717 44807.78717 3.25971 3.25971 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 32.99900 1.71668E-002 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 1202.26721 1202.26721 5.15936E-002 5.15936E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 8.70000 6.99286E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 17424.90390 17424.90390 1.26882 1.26882 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 33.20000 1.71672E-002 188.86188 142.30000 0.67639 0.00000
14 CAFE_FLR_1 Heating 3695.99264 3695.99264 0.15861 0.67639 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 8.70000 6.99286E-003 188.86188 142.30000 0.67639 0.00000
15 LOBBY_FLR_1 Cooling 60605.55122 60605.55122 4.41052 4.41052 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 33.20000 1.71672E-002 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 8253.80744 8253.80744 0.35420 1.89399 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 8.70000 6.99286E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 9816.99822 9816.99822 0.96238 0.96238 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26200 1.71654E-002 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 3428.08138 3428.08138 0.14798 0.14798 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 9925.20037 9925.20037 0.97299 0.97299 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 32.15033 1.71652E-002 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 3428.34773 3428.34773 0.14799 0.14799 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 49677.99198 49677.99198 4.86956 4.86956 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 33.20000 1.71672E-002 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 20112.85260 20112.85260 0.86819 0.86819 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 60021.24302 60021.24302 5.88388 5.88388 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 31.70367 1.71644E-002 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 20130.65851 20130.65851 0.86896 0.86896 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 8771.44330 8771.44330 0.85989 0.85989 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 30.65400 1.71624E-002 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 3427.07310 3427.07310 0.14793 0.14793 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 8854.10952 8854.10952 0.86799 0.86799 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 30.65400 1.71624E-002 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 3427.33947 3427.33947 0.14794 0.14794 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 18705.09247 18705.09247 1.36066 1.36066 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 32.15033 1.71652E-002 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 5529.82604 5529.82604 0.23731 0.47476 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 2575.86031 2575.86031 0.25252 0.25252 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26200 1.71654E-002 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 1040.92476 1040.92476 4.49322E-002 4.49322E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2601.11439 2601.11439 0.25499 0.25499 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26200 1.71654E-002 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 1041.18113 1041.18113 4.49433E-002 4.49433E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 10246.74503 10246.74503 1.00452 1.00452 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 33.20000 1.71672E-002 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 5021.23701 5021.23701 0.21675 0.21675 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 29960.29758 29960.29758 2.18210 2.18210 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 33.20000 1.71672E-002 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 3570.27808 3570.27808 0.15321 1.18780 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 20:00:00 8.70000 6.99286E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 31385.98971 31385.98971 2.28590 2.28590 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 33.20000 1.71672E-002 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 3567.06475 3567.06475 0.15308 1.18780 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 8.70000 6.99286E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 30318.66368 30318.66368 2.21134 2.21134 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 32.59700 1.71661E-002 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 0.00000 0.00000 0.00000 0.36735   00:10:00 8.70000 6.99286E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 9970.69828 9970.69828 0.72530 0.72530 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 33.20000 1.71672E-002 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 3771.13969 3771.13969 0.16183 0.16183 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 8.70000 6.99286E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 416411.51 21.19362 21.19362 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 68851.61 7.12111 7.12111 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00
3 FLR_3_DOAS Cooling Sensible 50573.62 15.48898 2.05125 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 FLR_3_DOAS Heating Sensible 19832.79 2.63561 2.05125 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.70994
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.55642
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.48234
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.84733E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.83903E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.48234
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7817.43259
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.83903E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 163.01908
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.28941
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17659
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.15831
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54700
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.15750E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.01954E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.15831
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2308.45622
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.01954E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 53.03936
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.24175
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24481
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13224
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.65283
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.55629E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.02143E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13224
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1167.55970
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.02143E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 25.23264
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.24908
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.50246
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13625
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.58274E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.37089E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13625
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1567.00841
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.37089E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 34.82035
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.12065
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.59848
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 6.59956E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.36613E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.38318E-006
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.59956E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 843.94256
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.38318E-006
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 19.01354
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.25971
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.23910E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.78306
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54700
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.08850E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.27504E-005
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.78306
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10601.93687
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.27504E-005
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 222.55588
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.26882
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11342
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.69405
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54700
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.35913E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.43471E-005
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.69405
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7355.26721
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.43471E-005
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 161.88872
99 Fan:ZoneExhaust LOBBY_FLR_1 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.41052
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22601
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.41255
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.60270
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.68574E-003
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.83483E-004
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.41255
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
110 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 20973.22502
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.83483E-004
113 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 452.62986
114 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
115 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.96238
116 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.96238
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.99903E-005
118 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.02331E-004
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68264
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.76196E-003
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.02331E-004
125 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.96238
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3428.07988
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.99903E-005
128 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 97.94448
129 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
130 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.97299
131 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.97299
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.99927E-005
133 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.06449E-004
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68265
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.75898E-003
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.06449E-004
140 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.97299
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3428.34624
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.99927E-005
143 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 97.95209
144 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
145 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 4.86956
146 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 4.86956
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.75956E-004
148 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.00061E-003
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68355
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.69549E-003
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.00061E-003
155 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 4.86956
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 20112.84813
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.75956E-004
158 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 574.64551
159 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
160 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.88388
161 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 5.88388
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.76112E-004
163 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.54727E-003
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68271
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.89812E-003
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.54727E-003
170 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.88388
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 20130.65403
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.76112E-004
173 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 575.15422
174 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
175 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.85989
176 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.85989
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.99815E-005
178 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.62493E-004
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68259
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.79406E-003
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.62493E-004
185 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.85989
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3427.07160
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.99815E-005
188 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 97.91568
189 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
190 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.86799
191 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.86799
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.99838E-005
193 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.65671E-004
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68260
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.79154E-003
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.65671E-004
200 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.86799
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3427.33798
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.99838E-005
203 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 97.92329
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.36066
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.87230
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.74428
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.36777E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.27093E-005
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.74428
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
214 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9454.17977
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.27093E-005
217 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 212.80069
218 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
219 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.25252
220 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.25252
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 9.10646E-006
222 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.05238E-004
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68267
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.75004E-003
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.05238E-004
229 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.25252
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1040.92433
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.10646E-006
232 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 29.74012
233 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
234 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.25499
235 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.25499
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 9.10870E-006
237 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.06196E-004
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68267
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.74737E-003
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.06196E-004
244 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.25499
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1041.18070
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.10870E-006
247 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 29.74744
248 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
249 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.00452
250 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.00452
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.39280E-005
252 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.31523E-004
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68247
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.86760E-003
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.31523E-004
259 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.00452
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5021.23536
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.39280E-005
262 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 143.46074
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.18210
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11582
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.19361
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54700
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.28969E-003
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.62939E-005
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.19361
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
273 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9863.91751
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.62939E-005
276 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 211.94359
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.28590
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11056
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.25039
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54700
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.44618E-003
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.88855E-005
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.25039
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
287 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10160.16041
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.88855E-005
290 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 218.00139
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.21134
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.40265E-002
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.20960
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54700
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.07030E-002
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.58071E-005
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.20960
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
301 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6379.09961
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.58071E-005
304 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 133.02513
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.72530
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.43298
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54700
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.39674
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.79951E-004
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.12933E-005
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.39674
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
315 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5863.13449
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.12933E-005
318 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 135.00590
319 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 11.65941
320 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 11.65941
321 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 21.31519
322 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 11.65941
323 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 21.19362
324 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 21.19362
325 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
326 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.55014
327 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
328 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
329 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
333 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
334 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
335 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 21.19362
336 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
337 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.19362
338 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 11.66146
339 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 11.66146
340 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 29.05703
341 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.08946
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.38291E-002
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 814519.63365
346 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.90928E-002
347 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 21.19362
348 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 61474.17713
349 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.37803E-004
350 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1140.73609
351 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 21.19362
352 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 2.90928E-002
353 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 1.63680E-005
354 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 5.37803E-004
355 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
356 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
357 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
358 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 33.20000
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.94186
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.71672E-002
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 108329.82081
364 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.86929E-003
365 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
366 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 5950.04693
367 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.20536E-005
368 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 110.41113
369 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
370 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 3.86929E-003
371 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.23069E-004
372 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 5.20536E-005
373 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 3.96898E-002
374 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 8178.60225
375 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 1.94948E-003
376 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.23394
377 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 1.94948E-003
378 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 587.09693
379 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
380 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 222837.22266
381 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 222837.22000
382 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 1.94948E-003
383 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 3.96898E-002
384 PlantLoop COOLSYS1 Plant Loop Volume [m3] 4.76278
385 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 3.96898E-002
386 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 5662.32219
387 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 3.96898E-002
388 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1111209.44633
389 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1114329.22000
390 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 127.03353
391 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
392 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
393 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
394 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
395 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 7857.81
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 2319.15
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1173.39
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 1574.52
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 847.93
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 10656.35
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 7390.88
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 21078.12
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 3691.90
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 3692.18
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 21660.62
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 21679.80
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 3690.81
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 3691.10
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 9498.89
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 1121.02
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 1121.30
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 5407.61
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 9913.45
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 10211.25
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 6412.05
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 5890.23
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 55036.30
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 5326.93


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 16425.12 13138.06 3287.06 0.80 1838.29 18.64
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 16597.85 13278.72 3319.13 0.80 1857.72 18.84
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 82180.53 66013.42 16167.12 0.80 9208.89 93.40
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 102686.67 81451.75 21234.92 0.79 11467.14 116.31
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 14754.60 11778.10 2976.50 0.80 1650.40 16.74
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 14887.43 11886.00 3001.44 0.80 1665.33 16.89
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 4301.12 3442.96 858.16 0.80 481.48 4.88
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 4341.33 3475.74 865.59 0.80 486.01 4.93
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 17445.04 13863.04 3582.01 0.79 1949.01 19.77
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 654034.83 427987.02 226047.81 0.65 78228.37 793.44
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 67803.65 43510.62 24293.03 0.64 8145.92 82.62


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 3.93 13.40


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.940 0.824   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.198 1.198   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.608 1.296   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.608 1.296   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.608 1.296   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.608 1.296   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.608 1.296   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.608 1.296   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.608 1.296   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.608 1.296   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.608 1.296   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.608 1.296   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.608 1.296   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.608 1.296   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.608 1.296   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.608 1.296   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.684 1.345   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.684 1.345   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.684 1.345   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.684 1.345   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.684 1.345   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.3731853046E-002 2.2317357548E-002 Pass Pass 1.0817758828E-002 2.2573127482E-002 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 3.1484018537E-002 4.2914711067E-002 Pass Pass 1.6336106745E-002 1.9298754148E-002 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 2.2403195573E-002 2.8570129719E-002 Pass Pass 9.4377903077E-003 2.0066091744E-002 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 1.6349165318E-002 1.7552025836E-002 Pass Pass 9.2692114142E-003 2.0515471706E-002 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 1.1024058322E-002 1.0725714877E-002 Pass Pass 9.0880322321E-003 2.0666778455E-002 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 8.4217762455E-002 0.2238625312 Pass Pass 1.9034197558E-002 4.7599379078E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 1.3511699329E-002 3.6748195218E-002 Pass Pass 1.7566330960E-002 2.5279571090E-002 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 1.6755710410E-002 3.5059420218E-002 Pass Pass 1.4032611459E-002 2.5362931910E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 9.2591140281E-002 0.3149180550 Pass Pass 0.1380564170 0.5849797670 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 8.2083600347E-002 0.2741194256 Pass Pass 0.1045610120 0.4096796525 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 4.7313583379E-003 2.1529544784E-002 Pass Pass 2.5534521059E-002 3.5830599875E-002 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 6.2608626448E-002 0.1956663977 Pass Pass 7.6698435527E-002 0.2509254458 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 9.2612816134E-002 0.3258875362 Pass Pass 0.1172688561 0.4470704396 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 9.2611782887E-002 0.3130404806 Pass Pass 0.1495367495 0.6039366164 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 1.2244423423E-002 1.0827794717E-002 Pass Pass 8.9426755295E-003 1.9809591198E-002 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 9.0637610263E-002 0.3095324061 Pass Pass 0.1360544351 0.5679298610 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 7.5867317256E-002 0.2590922619 Pass Pass 0.1026052806 0.3877818781 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 9.2635042096E-002 0.3045378545 Pass Pass 0.1188814627 0.4774862400 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 1.7282832206E-002 4.8157883964E-002 Pass Pass 1.4430507215E-002 3.7704180488E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 1.3737878963E-002 3.9242010023E-002 Pass Pass 1.3884375612E-002 3.5390567980E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 1.4218339938E-002 3.9836977717E-002 Pass Pass 1.9623770722E-002 3.8601011609E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 2.3175972075E-002 1.7468558711E-002 Pass Pass 9.4530641787E-003 1.8557581177E-002 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3205.98 -90.6 -1101.3 -4964.1 15363.94 12413.97



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
MIAMI INTL AP ANN HTG 99.6% CONDNS DB 8.70 0.00 8.70 Wetbulb [C] 3.80 340.00
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 33.20 6.70 25.30 Wetbulb [C] 4.50 140.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 65.00 29      
Feb 0.00 0      
Mar 0.00 0      
Apr 38.00 14      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 391.00 83      
Sep 0.00 0      
Oct 225.00 40      
Nov 0.00 0      
Dec 5.00 10      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.845 0.940 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.079 1.287 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.55 0.273 0.283 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.079 1.287 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.079 1.287 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.079 1.287 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.55 0.273 0.283 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 1.079 1.287 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.55 0.273 0.283 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.296 1.608 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.296 1.608 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.296 1.608 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.296 1.608 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.296 1.608 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.296 1.608 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.296 1.608 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.296 1.608 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.296 1.608 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.296 1.608 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 1.296 1.608 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 1.296 1.608 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 1.296 1.608 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 1.296 1.608 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.345 1.684 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.345 1.684 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 1.345 1.684 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.345 1.684 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.345 1.684 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.55 0.273 0.283 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.55 0.273 0.283 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.345 1.684 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.55 0.273 0.283 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.55 0.273 0.283 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.55 0.273 0.283 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.371 0.412 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.371 0.412 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.371 0.412 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.371 0.412 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.371 0.412 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.371 0.412 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.371 0.412 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.371 0.412 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.371 0.412 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.371 0.412 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.379 0.412 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.371 0.412 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.379 0.412 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.371 0.412 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.379 0.412 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.371 0.412 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.379 0.412 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.371 0.412 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.371 0.412 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.371 0.412 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.379 0.412 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.364 0.412 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.379 0.412 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.364 0.412 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.379 0.412 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.364 0.412 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.379 0.412 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.364 0.412 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.379 0.412 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.364 0.412 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.379 0.412 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.364 0.412 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.379 0.412 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.364 0.412 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.364 0.412 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.364 0.412 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.379 0.412 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.379 0.412 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.379 0.412 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.364 0.412 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.364 0.412 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.364 0.412 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.364 0.412 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.364 0.412 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.364 0.412 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.364 0.412 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   23.26 0.00 0.00 23.26 23.26 2.910 0.251 0.251             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   65.50 0.00 0.00 65.50 65.50 2.910 0.251 0.251             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   85.08 0.00 0.00 85.08 85.08 2.910 0.251 0.251             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.910 0.251 0.251             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.910 0.251 0.251             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.910 0.251 0.251             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.910 0.251 0.251             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   3.68 0.00 0.00 3.68 279.56 2.910 0.251 0.251             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   3.68 0.00 0.00 3.68 279.65 2.910 0.251 0.251             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.910 0.251 0.251             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.910 0.251 0.251             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.910 0.251 0.251             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.910 0.251 0.251             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.910 0.251 0.251             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   2.15 0.00 0.00 2.15 8.59 2.910 0.251 0.251             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   2.15 0.00 0.00 2.15 8.58 2.910 0.251 0.251             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.910 0.251 0.251             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.910 0.251 0.251             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.910 0.251 0.251             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.910 0.251 0.251             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.910 0.251 0.251             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   6.74 0.00 0.00 6.74 60.70 2.910 0.251 0.251             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.910 0.251 0.251             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.910 0.251 0.251             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.910 0.251 0.251             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.910 0.251 0.251             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.910 0.251 0.251             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   5.82 0.00 0.00 5.82 5.82 2.910 0.251 0.251             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   5.21 0.00 0.00 5.21 5.21 2.910 0.251 0.251             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.910 0.251 0.251             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.910 0.251 0.251                      
North Total or Average             432.95 2.910 0.251 0.251                      
Non-North Total or Average             780.84 2.910 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.016 1.198 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 9.1389 1978.83 18084.33 LightsWired LTG_SCH_BASEMENT 51.16 168.00 51.10 0.0000 Y 173.46
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 13.3365 67.07 894.50 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 8.61
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 13.3365 77.67 1035.83 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 9.97
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 9.2031 164.24 1511.55 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 16.63
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 6.1031 94.76 578.33 LightsWired LTG_SCH_STORAGE 25.68 168.00 25.65 0.0000 Y 2.78
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.8125 78.04 453.60 LightsWired LTG_SCH_LAUNDRY 51.36 168.00 51.30 0.0000 Y 4.37
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 10.3656 188.86 1957.67 LightsWired LTG_SCH_DINING 58.69 168.00 49.09 0.0000 Y 18.04
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 8.7188 1308.19 11405.76 LightsWired LTG_SCH_LOBBY 58.69 168.00 56.99 0.0000 Y 122.01
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 4.5531 156.09 710.69 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 4.5531 156.07 710.61 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 4.5531 1863.81 8486.17 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 76.02
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 4.5531 1864.32 8488.49 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 76.04
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 4.5531 156.09 710.69 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 4.5531 156.07 710.61 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 6.3938 1557.62 9959.03 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 109.60
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 4.5531 39.02 177.67 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.59
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 4.5531 39.02 177.65 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.59
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 4.5531 220.77 1005.22 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 9.00
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 10.3656 331.66 3437.84 LightsWired LTG_SCH_DINING 58.69 168.00 53.85 0.0000 Y 34.75
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 10.3656 331.66 3437.84 LightsWired LTG_SCH_DINING 58.69 168.00 53.85 0.0000 Y 34.75
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 11.7219 103.30 1210.92 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 13.33
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 6.3938 412.12 2635.02 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 29.00
Interior Lighting Total       6.8557 11345.29 77780.02               507.66


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.07 11405.76 798.40
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.00 11405.76 0.00
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.39 1957.67 763.49
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.00 1957.67 0.00
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3437.84 687.57
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.00 3437.84 0.00
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3437.84 687.57
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.00 3437.84 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 15448.40 AstronomicalClock -   83.82 83.82 243.08
Exterior Lighting Total 15448.40           243.08



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 222837.22 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 1114329.22 2.96 1114525.09 2.96 3.93 13.40


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11264.40 16425.12 13138.06 3287.06 0.80 - 1838.29 18.64
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11379.70 16597.85 13278.72 3319.13 0.80 - 1857.72 18.84
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 56012.81 82180.53 66013.42 16167.12 0.80 - 9208.89 93.40
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 71318.16 102686.67 81451.75 21234.92 0.79 - 11467.14 116.31
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10149.02 14754.60 11778.10 2976.50 0.80 - 1650.40 16.74
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10238.00 14887.43 11886.00 3001.44 0.80 - 1665.33 16.89
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2946.44 4301.12 3442.96 858.16 0.80 - 481.48 4.88
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2973.25 4341.33 3475.74 865.59 0.80 - 486.01 4.93
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 12081.72 17445.04 13863.04 3582.01 0.79 - 1949.01 19.77
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 814519.63 654034.83 427987.02 226047.81 0.65 - 78228.37 793.44
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 108329.82 67803.65 43510.62 24293.03 0.64 - 8145.92 82.62
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 7817.43 7857.81 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2308.46 2319.15 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1167.56 1173.39 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1567.01 1574.52 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 843.94 847.93 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 10601.94 10656.35 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 7355.27 7390.88 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 20973.23 21078.12 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 3428.08 3691.90 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 3428.35 3692.18 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 20112.85 21660.62 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 20130.65 21679.80 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 3427.07 3690.81 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 3427.34 3691.10 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 9454.18 9498.89 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1040.92 1121.02 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1041.18 1121.30 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 5021.24 5407.61 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 9863.92 9913.45 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 10160.16 10211.25 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 6379.10 6412.05 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 5863.13 5890.23 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 61474.18 55036.30 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 5950.05 5326.93 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.96 677.17 703.64 1.00 1.21 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.97 684.63 703.64 1.00 1.20 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 4.87 3426.40 703.64 1.00 0.97 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 5.88 4140.11 703.64 1.00 0.96 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.86 605.05 703.64 1.00 1.24 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.87 610.75 703.64 1.00 1.23 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.25 177.68 703.64 1.00 1.84 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.25 179.42 703.64 1.00 1.84 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.00 706.82 703.64 1.00 1.20 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1314.72 21.19 44934.17 2120.17 1.00 1.12 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.039690 8178.60 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.001949 587.10 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.039690 5662.32 142664.32 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.80 0.58 0.51
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.80 0.26 0.03



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 37253.41 37253.41 18.83 2.710 2.710 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 24.00 24.00 0.00915 29.25 0.01716 0.854 0.00
RETAIL_1_FLR_1 3977.79 3977.79 59.31 0.289 0.289 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 24.00 24.00 0.00936 33.20 0.01717 0.079 0.00
RETAIL_2_FLR_1 3322.86 3322.86 42.78 0.242 0.242 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 24.00 24.00 0.00947 31.59 0.01716 0.092 0.00
MECH_FLR_1 3424.34 3424.34 20.85 0.249 0.249 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 20:00:00 24.00 24.00 0.00895 29.85 0.01716 0.000 0.00
STORAGE_FLR_1 1658.66 1658.66 17.50 0.121 0.121 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 24.00 24.00 0.00910 31.70 0.01716 0.058 0.00
LAUNDRY_FLR_1 44807.79 44807.79 574.17 3.260 3.260 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 24.00 24.00 0.00857 33.00 0.01717 0.000 0.00
CAFE_FLR_1 17424.90 17424.90 92.26 1.269 1.269 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 24.00 23.99 0.01045 33.20 0.01717 0.676 0.00
LOBBY_FLR_1 60605.55 60605.55 46.33 4.411 4.411 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 23.99 0.01017 33.20 0.01717 1.894 0.00
ROOM_1_FLR_3 9817.00 9817.00 251.58 0.962 0.962 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 21.11 21.11 0.00876 32.26 0.01717 0.062 0.00
ROOM_2_FLR_3 9925.20 9925.20 254.38 0.973 0.973 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 21.11 21.11 0.00876 32.15 0.01717 0.062 0.00
ROOM_3_MULT19_FLR_3 49677.99 49677.99 2025.70 4.870 4.870 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 21.11 21.11 0.00870 33.20 0.01717 0.837 0.00
ROOM_4_MULT19_FLR_3 60021.24 60021.24 2446.80 5.884 5.884 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 21.11 21.11 0.00890 31.70 0.01716 0.837 0.00
ROOM_5_FLR_3 8771.44 8771.44 224.78 0.860 0.860 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 21.11 21.11 0.00879 30.65 0.01716 0.062 0.00
ROOM_6_FLR_3 8854.11 8854.11 226.93 0.868 0.868 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 21.11 21.11 0.00879 30.65 0.01716 0.062 0.00
CORRIDOR_FLR_3 18705.09 18705.09 48.04 1.361 1.361 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 24.00 24.00 0.00966 32.15 0.01717 0.475 0.00
ROOM_1_FLR_6 2575.86 2575.86 66.01 0.253 0.253 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 21.11 21.11 0.00875 32.26 0.01717 0.015 0.00
ROOM_2_FLR_6 2601.11 2601.11 66.67 0.255 0.255 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 21.11 21.11 0.00875 32.26 0.01717 0.015 0.00
ROOM_3_MULT9_FLR_6 10246.75 10246.75 417.71 1.005 1.005 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 21.11 21.11 0.00887 33.20 0.01717 0.099 0.00
BANQUET_FLR_6 29960.30 29960.30 90.34 2.182 2.182 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 23.98 0.01042 33.20 0.01717 1.188 0.00
DINING_FLR_6 31385.99 31385.99 94.63 2.286 2.286 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 23.98 0.01034 33.20 0.01717 1.188 0.00
KITCHEN_FLR_6 30318.66 30318.66 293.49 2.211 2.211 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 24.00 23.97 0.01015 32.60 0.01717 0.367 0.00
CORRIDOR_FLR_6 9970.70 9970.70 24.19 0.725 0.725 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 24.00 0.00913 33.20 0.01717 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 0.854   00:10:00 21.00 23.64 0.00699 8.70 0.00699 0.854 0.00
RETAIL_1_FLR_1 1473.82 1473.82 21.97 0.063 0.079 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.00 21.00 0.00786 8.70 0.00699 0.079 0.00
RETAIL_2_FLR_1 470.39 470.39 6.06 0.020 0.092 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.00 21.00 0.00784 8.70 0.00699 0.092 0.00
MECH_FLR_1 848.75 848.75 5.17 0.036 0.036 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.00 21.00 0.00780 8.70 0.00699 0.000 0.00
STORAGE_FLR_1 496.03 496.03 5.23 0.021 0.058 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.00 21.00 0.00780 8.70 0.00699 0.058 0.00
LAUNDRY_FLR_1 1202.27 1202.27 15.41 0.052 0.052 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.00 21.00 0.00780 8.70 0.00699 0.000 0.00
CAFE_FLR_1 3695.99 3695.99 19.57 0.159 0.676 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.00 21.00 0.00788 8.70 0.00699 0.676 0.00
LOBBY_FLR_1 8253.81 8253.81 6.31 0.354 1.894 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.00 21.00 0.00785 8.70 0.00699 1.894 0.00
ROOM_1_FLR_3 3428.08 3428.08 87.85 0.148 0.148 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00786 8.70 0.00699 0.062 0.00
ROOM_2_FLR_3 3428.35 3428.35 87.87 0.148 0.148 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00786 8.70 0.00699 0.062 0.00
ROOM_3_MULT19_FLR_3 20112.85 20112.85 820.13 0.868 0.868 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00787 8.70 0.00699 0.837 0.00
ROOM_4_MULT19_FLR_3 20130.66 20130.66 820.64 0.869 0.869 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00787 8.70 0.00699 0.837 0.00
ROOM_5_FLR_3 3427.07 3427.07 87.82 0.148 0.148 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00786 8.70 0.00699 0.062 0.00
ROOM_6_FLR_3 3427.34 3427.34 87.84 0.148 0.148 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00786 8.70 0.00699 0.062 0.00
CORRIDOR_FLR_3 5529.83 5529.83 14.20 0.237 0.475 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00789 8.70 0.00699 0.475 0.00
ROOM_1_FLR_6 1040.92 1040.92 26.68 0.045 0.045 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00788 8.70 0.00699 0.015 0.00
ROOM_2_FLR_6 1041.18 1041.18 26.69 0.045 0.045 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00788 8.70 0.00699 0.015 0.00
ROOM_3_MULT9_FLR_6 5021.24 5021.24 204.69 0.217 0.217 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00789 8.70 0.00699 0.099 0.00
BANQUET_FLR_6 3570.28 3570.28 10.76 0.153 1.188 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 20:00:00 21.00 21.00 0.00791 8.70 0.00699 1.188 0.00
DINING_FLR_6 3567.06 3567.06 10.76 0.153 1.188 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 21.00 21.00 0.00791 8.70 0.00699 1.188 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.000 0.367   00:10:00 21.00 22.21 0.00541 8.70 0.00699 0.367 0.00
CORRIDOR_FLR_6 3771.14 3771.14 9.15 0.162 0.162 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 21.00 21.00 0.00793 8.70 0.00699 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 21.19 21.19 7.12 7.12 21.1936 11.6594 21.1936 0.5501 0.3000
FLR_3_DOAS 15.49 2.05 2.64 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 7817.433 7817.433 1.482337 0.00006839 163.019   1/21 00:10:00   1/21 00:10:00 7817.43 7817.43 1.482337 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00800000 51.6560 0.00 0.00 7861.37 7861.37
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 2308.456 2308.456 0.158309 0.00002020 53.039 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 2308.46 2308.46 0.158309 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00786152 50.7735 1473.82 0.00 2320.84 2320.84
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1167.560 1167.560 0.132238 0.00001021 25.233 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 1167.56 1167.56 0.132238 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00783721 50.6182 470.39 0.00 1174.04 1174.04
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 1567.008 1567.008 0.136248 0.00001371 34.820 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 1567.01 1567.01 0.136248 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00779694 50.3613 848.75 0.00 1575.52 1575.52
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 843.943 843.943 0.065996 0.00000738 19.014 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 843.94 843.94 0.065996 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00779902 50.3746 496.03 0.00 848.50 848.50
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10601.937 10601.937 1.783061 0.00009275 222.556 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 10601.94 10601.94 1.783061 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00780283 50.3991 1202.27 0.00 10661.38 10661.38
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 7355.267 7355.267 0.694045 0.00006435 161.889 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 7355.27 7355.27 0.694045 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00787591 50.8652 3695.99 0.00 7395.38 7395.38
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 20973.225 20973.225 2.412552 0.00018348 452.630 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 20973.23 20973.23 2.412552 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00784652 50.6775 8253.81 0.00 21089.77 21089.77
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 11264.396 -999.000 0.962384 0.00040233 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown 7/21 17:00:00 11264.40 10581.23 0.962384 21.68 15.77 0.00876196 12.80 12.09 0.00850000 32.26 0.01716543 25.09 0.0000 21.11 0.00876196 56.1280 9817.00 0.00 11287.27 10453.62
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 3428.080 3428.080 0.147976 0.00002999 97.944 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 3428.08 3428.08 0.147976 21.11 14.75 0.00786244 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00786244 50.4342 3428.08 0.00 3695.59 3695.59
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 11379.699 -999.000 0.972991 0.00040645 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 unknown 7/21 17:10:00 11379.70 10696.92 0.972991 21.68 15.77 0.00875898 12.80 12.09 0.00850000 32.15 0.01716522 25.06 0.0000 21.11 0.00875898 56.1092 9925.20 0.00 11402.82 10567.51
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 3428.346 3428.346 0.147987 0.00002999 97.952 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 3428.35 3428.35 0.147987 21.11 14.75 0.00786246 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00786246 50.4343 3428.35 0.00 3695.87 3695.87
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 56012.813 -999.000 4.869558 0.00200061 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 unknown 7/21 14:50:00 56012.81 53438.24 4.869558 21.68 15.71 0.00869549 12.80 12.09 0.00850000 33.20 0.01716721 25.32 0.0000 21.11 0.00869549 55.7052 49677.99 0.00 56128.38 52748.35
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 20112.848 20112.848 0.868189 0.00017596 574.646 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 20112.85 20112.85 0.868189 21.11 14.77 0.00787405 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00787405 50.5075 20112.85 0.00 21682.35 21682.35
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 71318.163 -999.000 5.883877 0.00254727 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 unknown 7/21 17:50:00 71318.16 64945.43 5.883877 21.68 15.89 0.00889812 12.80 12.09 0.00850000 31.70 0.01716436 24.94 0.0000 21.11 0.00889812 56.9872 60021.24 0.00 71458.52 64269.96
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 20130.654 20130.654 0.868958 0.00017611 575.154 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 20130.65 20130.65 0.868958 21.11 14.77 0.00787412 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00787412 50.5079 20130.66 0.00 21701.55 21701.55
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 10149.024 -999.000 0.859888 0.00036249 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown 7/21 10:00:00 10149.02 9463.17 0.859888 21.68 15.80 0.00879406 12.80 12.09 0.00850000 30.65 0.01716236 24.67 0.0000 21.11 0.00879406 56.3308 8771.44 0.00 10169.48 9352.84
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 3427.072 3427.072 0.147932 0.00002998 97.916 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 3427.07 3427.07 0.147932 21.11 14.75 0.00786241 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00786241 50.4340 3427.07 0.00 3694.50 3694.50
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 10237.998 -999.000 0.867992 0.00036567 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown 7/21 10:00:00 10238.00 9551.66 0.867992 21.68 15.80 0.00879154 12.80 12.09 0.00850000 30.65 0.01716236 24.67 0.0000 21.11 0.00879154 56.3149 8854.11 0.00 10258.64 9439.99
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 3427.338 3427.338 0.147944 0.00002998 97.923 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 3427.34 3427.34 0.147944 21.11 14.75 0.00786242 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00786242 50.4341 3427.34 0.00 3694.79 3694.79
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 9454.180 9454.180 0.744283 0.00008271 212.801 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 9454.18 9454.18 0.744283 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00789265 50.9716 5529.83 0.00 9505.28 9505.28
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 2946.444 -999.000 0.252518 0.00010524 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown 7/21 17:00:00 2946.44 2775.41 0.252518 21.68 15.76 0.00875004 12.80 12.09 0.00850000 32.26 0.01716543 25.09 0.0000 21.11 0.00875004 56.0527 2575.86 0.00 2952.44 2741.52
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 1040.924 1040.924 0.044932 0.00000911 29.740 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1040.92 1040.92 0.044932 21.11 14.77 0.00788392 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00788392 50.5703 1040.92 0.00 1122.15 1122.15
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2973.251 -999.000 0.254993 0.00010620 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown 7/21 17:00:00 2973.25 2802.40 0.254993 21.68 15.76 0.00874737 12.80 12.09 0.00850000 32.26 0.01716543 25.09 0.0000 21.11 0.00874737 56.0358 2601.11 0.00 2979.31 2768.08
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 1041.181 1041.181 0.044943 0.00000911 29.747 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1041.18 1041.18 0.044943 21.11 14.77 0.00788396 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00788396 50.5705 1041.18 0.00 1122.43 1122.43
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 12081.721 -999.000 1.004521 0.00043152 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 unknown 7/21 14:40:00 12081.72 11078.02 1.004521 21.68 15.86 0.00886760 12.80 12.09 0.00850000 33.20 0.01716721 25.32 0.0000 21.11 0.00886760 56.7954 10246.75 0.00 12105.66 10958.78
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 5021.235 5021.235 0.216746 0.00004393 143.461 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5021.24 5021.24 0.216746 21.11 14.78 0.00788861 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00788861 50.5999 5021.24 0.00 5413.06 5413.06
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 9863.918 9863.918 1.193609 0.00008629 211.944 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 20:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 20:00:00 9863.92 9863.92 1.193609 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00791406 51.1084 3570.28 0.00 9918.80 9918.80
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10160.160 10160.160 1.250390 0.00008889 218.001 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 10160.16 10160.16 1.250390 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00791387 51.1070 3567.06 0.00 10216.72 10216.72
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 6379.100 6379.100 1.209601 0.00005581 133.025   1/21 00:10:00   1/21 00:10:00 6379.10 6379.10 1.209601 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00800000 51.6560 0.00 0.00 6414.95 6414.95
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 5863.134 5863.134 0.396738 0.00005129 135.006 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 5863.13 5863.13 0.396738 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00792758 51.1944 3771.14 0.00 5894.57 5894.57
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 814519.634 -999.000 21.193621 0.02909275 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 814519.63 461923.55 21.193621 29.06 22.07 0.01382907 11.09 11.09 0.00850000 33.20 0.01716721 25.32 55.0234 23.99 0.00973439 52.2613 291148.95 0.00 815823.06 462079.98
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 61474.177 61474.177 6.358086 0.00053780 1140.736 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 61474.18 61474.18 6.358086 8.70 8.70 0.00699286 16.70 13.18 0.00800000 8.70 0.00699286 8.70 183.4115 22.02 0.00706926 42.9375 32873.62 0.00 66639.85 66639.85
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 108329.821 -999.000 2.051317 0.00386929 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 108329.82 53987.08 2.051317 33.20 25.32 0.01716721 11.94 11.73 0.00850000 33.20 0.01716721 25.32 99.9965 21.11 0.00880983 56.4288 157400.03 0.00 108457.34 54776.98
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 5950.047 5950.047 0.615395 0.00005205 110.411 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5950.05 5950.05 0.615395 8.70 8.70 0.00699286 16.70 13.18 0.00800000 8.70 0.00699286 8.70 333.3216 21.11 0.00787409 50.5078 61057.70 0.00 6450.03 6450.03



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 7817.433 7817.433 1.482337 0.00006839 163.019 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 3.4389 3.508136   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 7817.43 7817.43 1.0000 1.78286447 1.482337 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.06838333 60.00 32.22 27.78 0.000 7817.43 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 51.6560 0.00 0.00 7861.37 7861.37 1.78286447 16.60 13.15 0.00800000 36934.7 20.92 14.82 0.00800000 41344.1
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 2308.456 2308.456 0.158309 0.00002020 53.039 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 1.0155 1.035938 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 2308.46 2308.46 1.0000 0.19040450 0.158309 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.02019332 60.00 32.22 27.78 0.000 2308.46 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00786152 21.00 0.00786152 50.7735 1473.82 0.00 2320.84 2320.84 0.19040450 16.60 13.15 0.00800000 36934.7 28.55 17.55 0.00800000 49123.7
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1167.560 1167.560 0.132238 0.00001021 25.233 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 0.5136 0.523952 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 1167.56 1167.56 1.0000 0.15904750 0.132238 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.01021328 60.00 32.22 27.78 0.000 1167.56 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00783721 21.00 0.00783721 50.6182 470.39 0.00 1174.04 1174.04 0.15904750 16.60 13.15 0.00800000 36934.7 23.84 15.90 0.00800000 44316.5
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 1567.008 1567.008 0.136248 0.00001371 34.820 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 0.6893 0.703208 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 1567.01 1567.01 1.0000 0.16387104 0.136248 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.01370747 60.00 32.22 27.78 0.000 1567.01 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00779694 21.00 0.00779694 50.3613 848.75 0.00 1575.52 1575.52 0.16387104 16.60 13.15 0.00800000 36934.7 26.03 16.68 0.00800000 46549.1
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 843.943 843.943 0.065996 0.00000738 19.014 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 0.3713 0.378726 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 843.94 843.94 1.0000 0.07937546 0.065996 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.00738242 60.00 32.22 27.78 0.000 843.94 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00779902 21.00 0.00779902 50.3746 496.03 0.00 848.50 848.50 0.07937546 16.60 13.15 0.00800000 36934.7 27.08 17.05 0.00800000 47624.5
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 10601.937 10601.937 1.783061 0.00009275 222.556 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 4.6638 4.757705 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 10601.94 10601.94 1.0000 2.14455691 1.783061 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.09274091 60.00 32.22 27.78 0.000 10601.94 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00780283 21.00 0.00780283 50.3991 1202.27 0.00 10661.38 10661.38 2.14455691 16.60 13.15 0.00800000 36934.7 21.48 15.03 0.00800000 41906.1
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 7355.267 7355.267 0.694045 0.00006435 161.889 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 3.2356 3.300735 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 7355.27 7355.27 1.0000 0.83475531 0.694045 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.06434052 60.00 32.22 27.78 0.000 7355.27 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00787591 21.00 0.00787591 50.8652 3695.99 0.00 7395.38 7395.38 0.83475531 16.60 13.15 0.00800000 36934.7 25.29 16.42 0.00800000 45794.1
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 20973.225 20973.225 2.412552 0.00018348 452.630 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 9.2262 9.411904 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 20973.23 20973.23 1.0000 2.90167028 2.412552 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.18346420 60.00 32.22 27.78 0.000 20973.23 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00784652 21.00 0.00784652 50.6775 8253.81 0.00 21089.77 21089.77 2.90167028 16.60 13.15 0.00800000 36934.7 23.73 15.86 0.00800000 44202.9
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 11264.396 -999.000 0.962384 0.00040233 -999.000 -999.0000 1.00000 1.00000 1021.1280 1004.8586 1.2027 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.962384 1.15749712   4197.9300 999.8980 39.68577796 13.37 6.70 6.67 1111209.45 1.0137 1.013687 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown unknown unknown 7/21 17:00:00 Sensible 11264.40 10581.23 1.0000 1.15749712 0.962384 21.68 15.77 0.00876196 44053.9 12.80 12.09 0.00850000 34322.2 0.40228958 6.70 13.37 6.67 0.000 11264.40 32.26 0.01716543 25.09 0.00000000 0.0000 21.11 0.00876196 21.11 0.00876196 56.1280 9817.00 0.00 11287.27 10453.62 1.15749712 21.68 15.79 0.00876196 44053.9 12.84 12.09 0.00847670 34302.4
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 3428.080 3428.080 0.147976 0.00002999 97.944 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.962384 1.15749712   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 1.5080 1.538378 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 3428.08 3428.08 1.0000 0.17797596 0.147976 21.11 14.75 0.00786244 41185.1 40.00 21.17 0.00800000 60796.0 0.02998728 60.00 32.22 27.78 0.000 3428.08 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00786244 21.11 0.00786244 50.4342 3428.08 0.00 3695.59 3695.59 0.17797596 16.60 13.02 0.00786244 36586.5 36.97 20.17 0.00786244 57351.0
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 11379.699 -999.000 0.972991 0.00040645 -999.000 -999.0000 1.00000 1.00000 1021.1225 1004.8586 1.2027 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.972991 1.17025452   4197.9300 999.8980 39.68577796 13.37 6.70 6.67 1111209.45 1.0241 1.024063 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 unknown unknown unknown 7/21 17:10:00 Sensible 11379.70 10696.92 1.0000 1.17025452 0.972991 21.68 15.77 0.00875898 44046.3 12.80 12.09 0.00850000 34322.2 0.40640741 6.70 13.37 6.67 0.000 11379.70 32.15 0.01716522 25.06 0.00000000 0.0000 21.11 0.00875898 21.11 0.00875898 56.1092 9925.20 0.00 11402.82 10567.51 1.17025452 21.68 15.78 0.00875898 44046.3 12.84 12.09 0.00847627 34302.4
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 3428.346 3428.346 0.147987 0.00002999 97.952 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.972991 1.17025452   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 1.5081 1.538498 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 3428.35 3428.35 1.0000 0.17798978 0.147987 21.11 14.75 0.00786246 41185.1 40.00 21.17 0.00800000 60796.0 0.02998961 60.00 32.22 27.78 0.000 3428.35 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00786246 21.11 0.00786246 50.4343 3428.35 0.00 3695.87 3695.87 0.17798978 16.60 13.02 0.00786246 36586.5 36.97 20.17 0.00786246 57351.0
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 56012.813 -999.000 4.869558 0.00200061 -999.000 -999.0000 1.00000 1.00000 1021.0045 1004.8586 1.2027 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 4.869558 5.85680706   4197.9300 999.8980 39.68577796 13.37 6.70 6.67 1111209.45 5.0407 5.040613 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 unknown unknown unknown 7/21 14:50:00 Sensible 56012.81 53438.24 1.0000 5.85680706 4.869558 21.68 15.71 0.00869549 43885.9 12.80 12.09 0.00850000 34322.2 2.00040646 6.70 13.37 6.67 0.000 56012.81 33.20 0.01716721 25.32 0.00000000 0.0000 21.11 0.00869549 21.11 0.00869549 55.7052 49677.99 0.00 56128.38 52748.35 5.85680706 21.68 15.73 0.00869549 43885.9 12.86 12.09 0.00846692 34302.5
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 20112.848 20112.848 0.868189 0.00017596 574.646 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 4.869558 5.85680706   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 8.8477 9.025803 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 20112.85 20112.85 1.0000 1.04420490 0.868189 21.11 14.77 0.00787405 41214.6 40.00 21.17 0.00800000 60796.0 0.17593802 60.00 32.22 27.78 0.000 20112.85 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00787405 21.11 0.00787405 50.5075 20112.85 0.00 21682.35 21682.35 1.04420490 16.60 13.03 0.00787405 36615.8 36.97 20.17 0.00787405 57380.3
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 71318.163 -999.000 5.883877 0.00254727 -999.000 -999.0000 1.00000 1.00000 1021.3812 1004.8586 1.2027 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.883877 7.07676782   4197.9300 999.8980 39.68577796 13.37 6.70 6.67 1111209.45 6.4181 6.417947 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 unknown unknown unknown 7/21 17:50:00 Sensible 71318.16 64945.43 1.0000 7.07676782 5.883877 21.68 15.89 0.00889812 44400.0 12.80 12.09 0.00850000 34322.2 2.54701213 6.70 13.37 6.67 0.000 71318.16 31.70 0.01716436 24.94 0.00000000 0.0000 21.11 0.00889812 21.11 0.00889812 56.9872 60021.24 0.00 71458.52 64269.96 7.07676782 21.68 15.90 0.00889812 44400.0 12.79 12.09 0.00849578 34302.4
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 20130.654 20130.654 0.868958 0.00017611 575.154 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.883877 7.07676782   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 8.8556 9.033793 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 20130.65 20130.65 1.0000 1.04512934 0.868958 21.11 14.77 0.00787412 41214.8 40.00 21.17 0.00800000 60796.0 0.17609378 60.00 32.22 27.78 0.000 20130.65 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00787412 21.11 0.00787412 50.5079 20130.66 0.00 21701.55 21701.55 1.04512934 16.60 13.03 0.00787412 36616.0 36.97 20.17 0.00787412 57380.5
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 10149.024 -999.000 0.859888 0.00036249 -999.000 -999.0000 1.00000 1.00000 1021.1877 1004.8586 1.2027 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.859888 1.03422117   4197.9300 999.8980 39.68577796 13.37 6.70 6.67 1111209.45 0.9133 0.913314 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown unknown unknown 7/21 10:00:00 Sensible 10149.02 9463.17 1.0000 1.03422117 0.859888 21.68 15.80 0.00879406 44135.4 12.80 12.09 0.00850000 34322.2 0.36245588 6.70 13.37 6.67 0.000 10149.02 30.65 0.01716236 24.67 0.00000000 0.0000 21.11 0.00879406 21.11 0.00879406 56.3308 8771.44 0.00 10169.48 9352.84 1.03422117 21.68 15.81 0.00879406 44135.4 12.83 12.09 0.00848131 34302.4
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 3427.072 3427.072 0.147932 0.00002998 97.916 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.859888 1.03422117   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 1.5076 1.537926 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 3427.07 3427.07 1.0000 0.17792361 0.147932 21.11 14.75 0.00786241 41185.0 40.00 21.17 0.00800000 60796.0 0.02997846 60.00 32.22 27.78 0.000 3427.07 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00786241 21.11 0.00786241 50.4340 3427.07 0.00 3694.50 3694.50 0.17792361 16.60 13.02 0.00786241 36586.4 36.97 20.17 0.00786241 57350.9
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 10237.998 -999.000 0.867992 0.00036567 -999.000 -999.0000 1.00000 1.00000 1021.1830 1004.8586 1.2027 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.867992 1.04396754   4197.9300 999.8980 39.68577796 13.37 6.70 6.67 1111209.45 0.9213 0.921321 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown unknown unknown 7/21 10:00:00 Sensible 10238.00 9551.66 1.0000 1.04396754 0.867992 21.68 15.80 0.00879154 44129.0 12.80 12.09 0.00850000 34322.2 0.36563344 6.70 13.37 6.67 0.000 10238.00 30.65 0.01716236 24.67 0.00000000 0.0000 21.11 0.00879154 21.11 0.00879154 56.3149 8854.11 0.00 10258.64 9439.99 1.04396754 21.68 15.81 0.00879154 44129.0 12.83 12.09 0.00848095 34302.4
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 3427.338 3427.338 0.147944 0.00002998 97.923 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.867992 1.04396754   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 1.5077 1.538046 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 3427.34 3427.34 1.0000 0.17793744 0.147944 21.11 14.75 0.00786242 41185.0 40.00 21.17 0.00800000 60796.0 0.02998079 60.00 32.22 27.78 0.000 3427.34 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00786242 21.11 0.00786242 50.4341 3427.34 0.00 3694.79 3694.79 0.17793744 16.60 13.02 0.00786242 36586.4 36.97 20.17 0.00786242 57350.9
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 9454.180 9454.180 0.744283 0.00008271 212.801 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 4.1589 4.242639 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 9454.18 9454.18 1.0000 0.89517790 0.744283 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.08270085 60.00 32.22 27.78 0.000 9454.18 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00789265 21.00 0.00789265 50.9716 5529.83 0.00 9505.28 9505.28 0.89517790 16.60 13.15 0.00800000 36934.7 27.01 17.02 0.00800000 47553.0
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 2946.444 -999.000 0.252518 0.00010524 -999.000 -999.0000 1.00000 1.00000 1021.1059 1004.8586 1.2027 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.252518 0.30371268   4197.9300 999.8980 39.68577796 13.37 6.70 6.67 1111209.45 0.2652 0.265152 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown unknown unknown 7/21 17:00:00 Sensible 2946.44 2775.41 1.0000 0.30371268 0.252518 21.68 15.76 0.00875004 44023.6 12.80 12.09 0.00850000 34322.2 0.10522745 6.70 13.37 6.67 0.000 2946.44 32.26 0.01716543 25.09 0.00000000 0.0000 21.11 0.00875004 21.11 0.00875004 56.0527 2575.86 0.00 2952.44 2741.52 0.30371268 21.68 15.77 0.00875004 44023.6 12.84 12.09 0.00847497 34302.4
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 1040.924 1040.924 0.044932 0.00000911 29.740 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.252518 0.30371268   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 0.4579 0.467123 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1040.92 1040.92 1.0000 0.05404177 0.044932 21.11 14.77 0.00788392 41239.6 40.00 21.17 0.00800000 60796.0 0.00910553 60.00 32.22 27.78 0.000 1040.92 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00788392 21.11 0.00788392 50.5703 1040.92 0.00 1122.15 1122.15 0.05404177 16.60 13.04 0.00788392 36640.8 36.97 20.18 0.00788392 57405.4
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2973.251 -999.000 0.254993 0.00010620 -999.000 -999.0000 1.00000 1.00000 1021.1009 1004.8586 1.2027 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.254993 0.30669039   4197.9300 999.8980 39.68577796 13.37 6.70 6.67 1111209.45 0.2676 0.267564 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown unknown unknown 7/21 17:00:00 Sensible 2973.25 2802.40 1.0000 0.30669039 0.254993 21.68 15.76 0.00874737 44016.8 12.80 12.09 0.00850000 34322.2 0.10618484 6.70 13.37 6.67 0.000 2973.25 32.26 0.01716543 25.09 0.00000000 0.0000 21.11 0.00874737 21.11 0.00874737 56.0358 2601.11 0.00 2979.31 2768.08 0.30669039 21.68 15.77 0.00874737 44016.8 12.84 12.09 0.00847458 34302.4
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 1041.181 1041.181 0.044943 0.00000911 29.747 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.254993 0.30669039   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 0.4580 0.467238 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1041.18 1041.18 1.0000 0.05405508 0.044943 21.11 14.77 0.00788396 41239.7 40.00 21.17 0.00800000 60796.0 0.00910777 60.00 32.22 27.78 0.000 1041.18 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00788396 21.11 0.00788396 50.5705 1041.18 0.00 1122.43 1122.43 0.05405508 16.60 13.04 0.00788396 36640.9 36.97 20.18 0.00788396 57405.5
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 12081.721 -999.000 1.004521 0.00043152 -999.000 -999.0000 1.00000 1.00000 1021.3244 1004.8586 1.2027 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.004521 1.20817621   4197.9300 999.8980 39.68577796 13.37 6.70 6.67 1111209.45 1.0873 1.087238 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 unknown unknown unknown 7/21 14:40:00 Sensible 12081.72 11078.02 1.0000 1.20817621 1.004521 21.68 15.86 0.00886760 44322.2 12.80 12.09 0.00850000 34322.2 0.43147899 6.70 13.37 6.67 0.000 12081.72 33.20 0.01716721 25.32 0.00000000 0.0000 21.11 0.00886760 21.11 0.00886760 56.7954 10246.75 0.00 12105.66 10958.78 1.20817621 21.68 15.88 0.00886760 44322.2 12.80 12.09 0.00849161 34302.4
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 5021.235 5021.235 0.216746 0.00004393 143.461 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.004521 1.20817621   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 2.2089 2.253320 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5021.24 5021.24 1.0000 0.26068832 0.216746 21.11 14.78 0.00788861 41251.6 40.00 21.17 0.00800000 60796.0 0.04392348 60.00 32.22 27.78 0.000 5021.24 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00788861 21.11 0.00788861 50.5999 5021.24 0.00 5413.06 5413.06 0.26068832 16.60 13.04 0.00788861 36652.7 36.97 20.18 0.00788861 57417.2
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 9863.918 9863.918 1.193609 0.00008629 211.944 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 4.3392 4.426512 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 20:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 20:00:00 Sensible 9863.92 9863.92 1.0000 1.43560055 1.193609 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.08628505 60.00 32.22 27.78 0.000 9863.92 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00791406 21.00 0.00791406 51.1084 3570.28 0.00 9918.80 9918.80 1.43560055 16.60 13.15 0.00800000 36934.7 23.38 15.73 0.00800000 43843.9
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 10160.160 10160.160 1.250390 0.00008889 218.001 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 4.4695 4.559454 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 Sensible 10160.16 10160.16 1.0000 1.50389253 1.250390 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.08887645 60.00 32.22 27.78 0.000 10160.16 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00791387 21.00 0.00791387 51.1070 3567.06 0.00 10216.72 10216.72 1.50389253 16.60 13.15 0.00800000 36934.7 23.26 15.69 0.00800000 43728.2
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 6379.100 6379.100 1.209601 0.00005581 133.025 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 2.8062 2.862672   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 6379.10 6379.10 1.0000 1.45483442 1.209601 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.05580145 60.00 32.22 27.78 0.000 6379.10 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 51.6560 0.00 0.00 6414.95 6414.95 1.45483442 16.60 13.15 0.00800000 36934.7 20.92 14.82 0.00800000 41344.1
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 5863.134 5863.134 0.396738 0.00005129 135.006 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 2.5792 2.631129 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 Sensible 5863.13 5863.13 1.0000 0.47717280 0.396738 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.05128803 60.00 32.22 27.78 0.000 5863.13 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00792758 21.00 0.00792758 51.1944 3771.14 0.00 5894.57 5894.57 0.47717280 16.60 13.15 0.00800000 36934.7 28.71 17.60 0.00800000 49287.8
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 814519.634 -999.000 21.193621 0.02909275 -999.000 -999.0000 1.00000 1.00000 1030.5476 1004.8586 1.2027 VAV WITH REHEAT FAN Fan:VariableVolume 21.193621 25.49039312   4197.9300 999.8980 39.68577796 13.37 6.70 6.67 1111209.45 73.3003 73.300280 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 Sensible 814519.63 461923.55 1.0000 25.49039312 21.193621 29.06 22.07 0.01382907 64530.3 11.09 11.09 0.00850000 32576.4 29.08978630 6.70 13.37 6.67 44934.168 769585.47 33.20 0.01716721 25.32 11.66146000 55.0234 23.99 0.00974526 23.99 0.00973439 52.2613 291148.95 0.00 815823.06 462079.98 25.49039312 29.06 22.09 0.01382907 64530.3 11.47 11.37 0.00832705 32525.2
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 61474.177 61474.177 6.358086 0.00053780 1140.736 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 VAV WITH REHEAT FAN Fan:VariableVolume 21.193621 25.49039312   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 27.0428 27.587033 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 Sensible 61474.18 61474.18 1.0000 7.64711793 6.358086 8.70 8.70 0.00699286 26343.9 16.70 13.18 0.00800000 37036.7 0.53774806 60.00 32.22 27.78 0.000 61474.18 8.70 0.00699286 8.70 11.66146000 183.4115 17.40 0.00763789 22.02 0.00706926 42.9375 32873.62 0.00 66639.85 66639.85 7.64711793 2.80 2.80 0.00699286 20338.7 11.36 9.92 0.00699286 29053.0
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 108329.821 -999.000 2.051317 0.00386929 -999.000 -999.0000 1.00000 1.00000 1036.7530 1004.8586 1.2027 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.46711237   4197.9300 999.8980 39.68577796 13.37 6.70 6.67 1111209.45 9.7488 9.748821 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 Sensible 108329.82 53987.08 1.0000 2.46719911 2.051317 33.20 25.32 0.01716721 77354.4 11.94 11.73 0.00850000 33446.3 3.86889549 6.70 13.37 6.67 2195.006 106134.81 33.20 0.01716721 25.32 2.05124512 99.9965 21.11 0.00881409 21.11 0.00880983 56.4288 157400.03 0.00 108457.34 54776.98 2.46719911 33.20 25.34 0.01716721 77354.4 11.78 11.72 0.00854298 33394.7
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 5950.047 5950.047 0.615395 0.00005205 110.411 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.46711237   4197.9300 999.8980 1.94927837 54.44 82.22 27.78 227321.91 2.6175 2.670132 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5950.05 5950.05 1.0000 0.74015973 0.615395 8.70 8.70 0.00699286 26343.9 16.70 13.18 0.00800000 37036.7 0.05204830 60.00 32.22 27.78 0.000 5950.05 8.70 0.00699286 8.70 2.05124512 333.3216 21.11 0.00787300 21.11 0.00787409 50.5078 61057.70 0.00 6450.03 6450.03 0.74015973 2.80 2.80 0.00699286 20338.7 11.36 9.92 0.00699286 29053.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 3697.17 1934.83 0.00
RETAIL_1_FLR_1 6206.00 1660.67 0.00
RETAIL_2_FLR_1 5288.00 1501.00 31.83
MECH_FLR_1 3014.17 3443.83 0.00
STORAGE_FLR_1 2034.17 4211.50 0.00
LAUNDRY_FLR_1 8433.00 3627.00 3539.50
CAFE_FLR_1 8080.33 3347.67 3050.17
LOBBY_FLR_1 7382.17 2896.50 2505.50
ROOM_1_FLR_3 136.00 7461.67 10.67
ROOM_2_FLR_3 79.50 7686.67 15.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 20.33 8760.00 20.33
ROOM_5_FLR_3 12.17 7219.83 9.00
ROOM_6_FLR_3 13.50 7478.33 11.50
CORRIDOR_FLR_3 3570.17 3871.50 886.00
ROOM_1_FLR_6 380.50 7367.83 54.50
ROOM_2_FLR_6 300.67 7581.00 91.33
ROOM_3_MULT9_FLR_6 220.67 7453.33 34.67
BANQUET_FLR_6 8274.17 2562.17 2418.67
DINING_FLR_6 8465.17 2289.33 2237.83
KITCHEN_FLR_6 8738.17 6919.67 6919.17
CORRIDOR_FLR_6 4715.00 2654.17 0.00
Facility 8750.00 8760.00 8444.83
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 5.67 0.00 5.67
ROOM_2_FLR_3 0.00 0.67 0.00 0.67
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 24.17 0.00 24.17
ROOM_5_FLR_3 0.00 2.17 0.00 2.17
ROOM_6_FLR_3 0.00 1.67 0.00 1.67
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 8.67 0.00 8.67
ROOM_2_FLR_6 0.00 2.50 0.00 2.50
ROOM_3_MULT9_FLR_6 0.00 73.83 0.00 73.83
BANQUET_FLR_6 0.00 0.00 0.00 0.00
DINING_FLR_6 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 0.00 83.00 0.00 83.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.80 106.50 4826.41 1.003 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 2.036 0.131 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 1.412 0.044 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.672 0.049 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.556 0.049 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 20.217 0.140 0.000 0.000
CAFE_FLR_1 82.58 142.30 748.35 3.324 0.103 0.000 0.000
LOBBY_FLR_1 245.14 422.44 5183.56 1.637 0.043 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.474 0.169 0.000 0.065
ROOM_2_FLR_3 0.95 1.50 118.93 0.474 0.169 0.000 0.066
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.538 0.075 0.000 0.105
ROOM_5_FLR_3 0.95 1.50 118.94 0.474 0.169 0.000 0.065
ROOM_6_FLR_3 0.95 1.50 118.93 0.474 0.169 0.000 0.066
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.502 0.021 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.474 0.169 0.000 0.078
ROOM_2_FLR_6 0.95 1.50 118.93 0.474 0.169 0.000 0.080
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.538 0.138 0.000 0.125
BANQUET_FLR_6 145.01 249.90 1010.89 4.580 0.049 0.000 0.000
DINING_FLR_6 145.01 249.90 1010.89 4.863 0.049 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 19.232 0.141 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 1.032 0.035 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.80 106.50 4826.41 0.724 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 1.407 0.003 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 1.084 0.001 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.486 0.001 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.393 0.001 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 14.974 0.003 0.000 0.000
CAFE_FLR_1 82.58 142.30 748.35 2.417 0.002 0.000 0.000
LOBBY_FLR_1 245.14 422.44 5183.56 1.290 0.001 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.462 0.003 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.462 0.003 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.525 0.001 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.463 0.003 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.462 0.003 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.364 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.461 0.003 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.461 0.003 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.525 0.003 0.000 0.000
BANQUET_FLR_6 145.01 249.90 1010.89 3.376 0.001 0.000 0.000
DINING_FLR_6 145.01 249.90 1010.89 3.711 0.001 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 11.262 0.003 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 0.725 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.80 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.28 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.58 142.30 748.35 188.86 0.0000 0.676
LOBBY_FLR_1 VAV WITH REHEAT 245.14 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 145.01 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 145.01 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.39 1604.23 35184.81 11345.29 0.0000 137.584


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 41483626.59 0.00 41483626.59 0.00 41483626.59 26946214.98 0.00 0.00 8760.00 0.00
RETAIL_1_FLR_1 4637018.32 0.00 4637018.32 299317.48 4936335.80 2498216.28 0.00 0.00 8760.00 0.00
RETAIL_2_FLR_1 3721260.39 0.00 3721260.39 115536.93 3836797.31 2892943.94 0.00 2.00 8758.00 0.00
MECH_FLR_1 3750623.83 0.00 3750623.83 273060.66 4023684.49 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 1790082.85 0.00 1790082.85 157540.96 1947623.81 1821682.01 3433.61 1045.65 4280.74 0.00
LAUNDRY_FLR_1 53720539.95 0.00 53720539.95 372850.38 54093390.33 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 21259440.55 0.00 21259440.55 661658.24 21921098.78 21330615.53 5270.93 384.59 3104.48 0.00
LOBBY_FLR_1 72536398.20 0.00 72536398.20 1890508.72 74426906.92 59728886.00 3.67 9.44 8746.89 0.00
ROOM_1_FLR_3 1946875.62 66602.60 2013478.22 173731.82 2187210.04 1946875.62 0.00 7650.83 1109.17 0.00
ROOM_2_FLR_3 1946647.51 67782.32 2014429.83 173718.57 2188148.40 1946647.51 0.00 7650.83 1109.17 0.00
ROOM_3_MULT19_FLR_3 26397887.27 68641.37 26466528.65 48473.13 26515001.77 26397887.27 0.00 7744.00 1016.00 8760.00
ROOM_4_MULT19_FLR_3 26405105.73 67760.04 26472865.77 48486.38 26521352.15 26405105.73 0.00 7728.96 1031.04 0.00
ROOM_5_FLR_3 1946875.62 66700.10 2013575.71 173731.82 2187307.54 1946875.62 0.00 7650.83 1109.17 0.00
ROOM_6_FLR_3 1946647.51 67871.87 2014519.38 173718.57 2188237.95 1946647.51 0.00 7650.83 1109.17 0.00
CORRIDOR_FLR_3 20403036.56 0.00 20403036.56 210076.73 20613113.29 14972100.18 0.33 3.83 8755.83 0.00
ROOM_1_FLR_6 486718.90 80711.40 567430.30 173766.55 741196.85 486718.90 0.00 7637.17 1122.83 0.00
ROOM_2_FLR_6 486661.88 82319.09 568980.97 173753.29 742734.26 486661.88 0.00 7637.17 1122.83 0.00
ROOM_3_MULT9_FLR_6 3126920.42 80879.75 3207800.17 88905.05 3296705.21 3126920.42 0.00 7637.50 1122.50 0.00
BANQUET_FLR_6 39559927.64 0.00 39559927.64 424294.23 39984221.87 37458366.31 3551.35 432.58 4776.06 0.00
DINING_FLR_6 42005784.69 0.00 42005784.69 424294.23 42430078.92 37458366.31 1967.37 359.68 6432.95 0.00
KITCHEN_FLR_6 51777900.86 0.00 51777900.86 379841.71 52157742.57 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 11110107.55 0.00 11110107.55 371767.87 11481875.41 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.45E+10 12333283.59 0.45E+10 17507169.38 0.45E+10 0.43E+10 7672.59 8044.36 8760.00 8760.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.3154 0.0000 1.3154 0.0000 1.3154 0.8545 0.00 0.00 8760.00
RETAIL_1_FLR_1 0.1470 0.0000 0.1470 0.0095 0.1565 0.0792 0.00 0.00 8760.00
RETAIL_2_FLR_1 0.1180 0.0000 0.1180 0.0037 0.1217 0.0917 0.00 2.00 8758.00
MECH_FLR_1 0.1189 0.0000 0.1189 0.0087 0.1276 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0568 0.0000 0.0568 0.0050 0.0618 0.0578 3433.61 1045.65 4280.74
LAUNDRY_FLR_1 1.7035 0.0000 1.7035 0.0118 1.7153 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.6741 0.0000 0.6741 0.0210 0.6951 0.6764 5270.93 384.59 3104.48
LOBBY_FLR_1 2.3001 0.0000 2.3001 0.0599 2.3601 1.8940 3.67 9.44 8746.89
ROOM_1_FLR_3 0.0617 0.0021 0.0638 0.0055 0.0694 0.0617 0.00 7650.83 1109.17
ROOM_2_FLR_3 0.0617 0.0021 0.0639 0.0055 0.0694 0.0617 0.00 7650.83 1109.17
ROOM_4_MULT19_FLR_3 0.8373 0.0021 0.8394 0.0015 0.8410 0.8373 0.00 7728.96 1031.04
ROOM_5_FLR_3 0.0617 0.0021 0.0639 0.0055 0.0694 0.0617 0.00 7650.83 1109.17
ROOM_6_FLR_3 0.0617 0.0022 0.0639 0.0055 0.0694 0.0617 0.00 7650.83 1109.17
CORRIDOR_FLR_3 0.6470 0.0000 0.6470 0.0067 0.6536 0.4748 0.33 3.83 8755.83
ROOM_1_FLR_6 0.0154 0.0026 0.0180 0.0055 0.0235 0.0154 0.00 7637.17 1122.83
ROOM_2_FLR_6 0.0154 0.0026 0.0180 0.0055 0.0236 0.0154 0.00 7637.17 1122.83
ROOM_3_MULT9_FLR_6 0.0992 0.0026 0.1017 0.0028 0.1045 0.0992 0.00 7637.50 1122.50
BANQUET_FLR_6 1.2544 0.0000 1.2544 0.0135 1.2679 1.1878 3551.35 432.58 4776.06
DINING_FLR_6 1.3320 0.0000 1.3320 0.0135 1.3454 1.1878 1967.37 359.68 6432.95
KITCHEN_FLR_6 1.6419 0.0000 1.6419 0.0120 1.6539 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.3523 0.0000 0.3523 0.0118 0.3641 0.1256 0.00 0.00 8760.00
Total Facility 79.1482 0.2257 79.3738 0.4383 79.8122 73.9670 7672.59 8044.36 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.53E+09 0.00 0.53E+09 0.22E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 93579813.88 649268.54 94229082.42 64690340.46 0.00 0.00 8760.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 16.8692 0.0000 16.8692 6.9969 0.00 0.00 8760.00
FLR_3_DOAS 2.9674 0.0206 2.9880 2.0513 0.00 0.00 8760.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 8752.61 0.00 0.00 7.39 0.00 0.00 0.00 0.00 0.00
FLR_3_DOAS 0.00 7874.96 885.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 16.8704 0.0000 0.0000 17.8033 0.0000 0.0000 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 2.9678 2.9675 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1318
Defaulted Fields 1181
Fields with Defaults 4005
Autosized Fields 350
Autosizable Fields 402
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 8219.26 83801.69 16-MAR-01:50 451931.94 27-JUL-19:10
Electricity:Building 2519.14 32804.76 02-JAN-02:10 151906.32 02-JAN-20:10
Electricity:Zone:BASEMENT 323.72 3705.45 02-JAN-02:10 24299.15 02-JAN-20:10
Electricity:SpaceType:GENERAL 2512.05 32663.61 02-JAN-02:10 151664.99 02-JAN-20:10
InteriorLights:Electricity 767.04 6971.81 02-JAN-02:10 62892.57 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 173.46 1576.23 02-JAN-02:10 14185.34 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 767.04 6971.81 02-JAN-02:10 62892.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity 767.04 6971.81 02-JAN-02:10 62892.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 173.46 1576.23 02-JAN-02:10 14185.34 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 767.04 6971.81 02-JAN-02:10 62892.57 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 18.80 222.61 02-JAN-02:10 1390.02 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.61 78.27 02-JAN-02:10 704.41 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.61 78.27 02-JAN-02:10 704.41 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 21.77 257.78 02-JAN-02:10 1609.65 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.97 90.64 02-JAN-02:10 815.72 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.97 90.64 02-JAN-02:10 815.72 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 29.11 327.88 02-JAN-02:10 2199.84 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 16.64 151.16 02-JAN-02:10 1360.40 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 16.64 151.16 02-JAN-02:10 1360.40 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 6.38 76.28 02-JAN-02:10 469.87 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.78 25.30 02-JAN-02:10 227.72 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.78 25.30 02-JAN-02:10 227.72 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 72.30 1002.39 02-JAN-02:10 4930.01 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.37 39.69 02-JAN-02:10 357.21 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.37 39.69 02-JAN-02:10 357.21 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 32.38 398.98 02-JAN-02:10 2727.18 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 18.04 195.77 02-JAN-02:10 1761.91 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 18.04 195.77 02-JAN-02:10 1761.91 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 271.01 3251.99 02-JAN-02:10 20294.39 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 122.01 1140.58 02-JAN-02:10 10265.18 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 122.01 1140.58 02-JAN-02:10 10265.18 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 18.66 264.62 01-JAN-02:10 1227.54 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 18.66 264.59 01-JAN-02:10 1227.39 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 304.77 4565.05 01-JAN-02:10 20923.25 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 76.02 643.59 01-JAN-02:10 5851.22 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 76.02 643.59 01-JAN-02:10 5851.22 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 304.86 4566.30 01-JAN-02:10 20928.98 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 76.04 643.77 01-JAN-02:10 5852.82 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 76.04 643.77 01-JAN-02:10 5852.82 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 18.66 264.62 01-JAN-02:10 1227.54 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 18.66 264.59 01-JAN-02:10 1227.39 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 4.66 66.15 01-JAN-02:10 306.88 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.59 13.47 01-JAN-02:10 122.50 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.59 13.47 01-JAN-02:10 122.50 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 4.66 66.15 01-JAN-02:10 306.85 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.59 13.47 01-JAN-02:10 122.49 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.59 13.47 01-JAN-02:10 122.49 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 36.10 540.75 01-JAN-02:10 2478.43 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 9.00 76.24 01-JAN-02:10 693.10 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 9.00 76.24 01-JAN-02:10 693.10 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 210.61 2593.08 02-JAN-02:10 9841.96 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 34.75 343.78 02-JAN-02:10 3094.06 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 34.75 343.78 02-JAN-02:10 3094.06 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 210.61 2593.08 02-JAN-02:10 9841.96 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 34.75 343.78 02-JAN-02:10 3094.06 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 34.75 343.78 02-JAN-02:10 3094.06 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 454.16 6253.02 02-JAN-02:10 18944.06 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.33 121.09 02-JAN-02:10 1089.83 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.33 121.09 02-JAN-02:10 1089.83 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
InteriorEquipment:Electricity 1745.01 25691.80 02-JAN-02:10 89475.41 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1745.01 25691.80 02-JAN-02:10 89475.41 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 433.74 5990.78 01-JAN-00:10 16487.34 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
Refrigeration:Electricity 63.05 1133.51 16-MAR-22:30 3264.61 22-DEC-07:30
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 3871.04 2559.85 16-MAR-01:50 233587.09 27-JUL-18:10
LowTempRefrigeration:Refrigeration:Electricity 20.59 0.00 01-JAN-11:10 1895.05 29-JUL-10:50
MedTempRefrigeration:Refrigeration:Electricity 35.37 984.22 25-JAN-04:10 1204.76 28-AUG-13:10
Fans:Electricity 630.18 12660.70 05-FEB-01:10 42569.67 21-SEP-21:10
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 966.97 21925.65 17-DEC-06:00 53725.31 21-SEP-21:10
ExteriorEquipment:Electricity 651.48 9618.58 02-JAN-02:20 39726.11 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 32.45 553.78 02-JAN-02:20 1868.65 02-JAN-21:10
ElectricityPurchased:Facility 8219.26 83801.69 16-MAR-01:50 451931.94 27-JUL-19:10
ElectricityPurchased:Plant 8219.26 83801.69 16-MAR-01:50 451931.94 27-JUL-19:10
Cogeneration:ElectricityPurchased 8219.26 83801.69 16-MAR-01:50 451931.94 27-JUL-19:10
General:Cogeneration:ElectricityPurchased 8219.26 83801.69 16-MAR-01:50 451931.94 27-JUL-19:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 8219.26 83801.69 16-MAR-01:50 451931.94 27-JUL-19:10
ElectricityNet:Plant 8219.26 83801.69 16-MAR-01:50 451931.94 27-JUL-19:10
Cogeneration:ElectricityNet 8219.26 83801.69 16-MAR-01:50 451931.94 27-JUL-19:10
General:Cogeneration:ElectricityNet 8219.26 83801.69 16-MAR-01:50 451931.94 27-JUL-19:10
General:Fans:Electricity 630.18 12660.70 05-FEB-01:10 42569.67 21-SEP-21:10
ExteriorLights:Electricity 243.08 0.00 01-JAN-07:20 15448.40 01-JAN-00:10
General:ExteriorLights:Electricity 243.08 0.00 01-JAN-07:20 15448.40 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.91 18.80 01-JAN-00:10 188.00 01-JAN-07:10
HeatRecovery:Electricity 304.34 8417.13 01-JAN-02:10 9938.94 01-JAN-09:30
General:HeatRecovery:Electricity 304.34 8417.13 01-JAN-02:10 9938.94 01-JAN-09:30
WaterSystems:Electricity 90.74 1086.56 18-FEB-01:20 4738.72 08-NOV-19:10
Water Heater:WaterSystems:Electricity 90.74 1086.56 18-FEB-01:20 4738.72 08-NOV-19:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 3526.25 0.00 25-JAN-04:20 218650.81 27-JUL-18:10
General:Cooling:Electricity 3526.25 0.00 25-JAN-04:20 218650.81 27-JUL-18:10
Pumps:Electricity 198.09 48.37 15-DEC-08:30 8018.71 27-JUL-18:10
General:Pumps:Electricity 198.09 48.37 15-DEC-08:30 8018.71 27-JUL-18:10
WIRED_LTG_ELECTRICITY 27.00 0.00 01-JAN-00:10 2213.82 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 4334.28 29270.80 02-JAN-02:10 321351.58 26-DEC-18:10
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 2545.44 15908.90 02-JAN-11:10 233904.16 03-FEB-23:10
WaterSystems:NaturalGas 2540.69 15908.90 02-JAN-11:10 219704.57 17-JAN-21:20
Water Heater:WaterSystems:NaturalGas 2540.69 15908.90 02-JAN-11:10 219704.57 17-JAN-21:20
Heating:NaturalGas 4.75 0.00 01-JAN-00:10 24733.76 04-FEB-06:00
Boiler:Heating:NaturalGas 4.75 0.00 01-JAN-00:10 24733.76 04-FEB-06:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 11482.27 0.00 25-JAN-04:20 721622.03 25-SEP-21:00
PlantLoopCoolingDemand:HVAC 11482.27 0.00 25-JAN-04:20 721622.03 25-SEP-21:00
CoolingCoils:PlantLoopCoolingDemand 11482.27 0.00 25-JAN-04:20 721622.03 25-SEP-21:00


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
Water Heater:WaterSystems:Water 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:20
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
Water Heater:WaterSystems:MainsWater 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:20
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 02-JAN-07:10
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 02-JAN-07:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 49054.85 160297.97 20-MAR-10:10 2967798.56 27-JUL-18:10
EnergyTransfer:Building 6718.21 119964.28 05-FEB-04:00 353448.27 27-JUL-18:20
EnergyTransfer:Zone:KITCHEN_FLR_6 764.06 11895.17 04-FEB-04:00 36013.64 23-JUL-10:50
Refrigeration:EnergyTransfer 189.53 4130.56 16-MAR-22:30 10377.53 22-DEC-07:30
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 94.76 2065.28 16-MAR-22:30 5188.77 22-DEC-07:30
General:Refrigeration:EnergyTransfer 94.76 2065.28 16-MAR-22:30 5188.77 22-DEC-07:30
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 94.76 2065.28 16-MAR-22:30 5188.77 22-DEC-07:30
EnergyTransfer:Plant 27458.27 13128.31 16-MAR-01:30 1667475.19 25-SEP-21:00
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.76 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 73.00 1902.67 25-JAN-04:10 2564.29 28-AUG-13:10
EnergyTransfer:Zone:BASEMENT 515.04 13111.04 24-APR-14:00 24569.48 31-OCT-21:00
Heating:EnergyTransfer 0.89 0.00 01-JAN-00:10 13001.99 04-FEB-19:10
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 0.89 0.00 01-JAN-00:10 13001.99 04-FEB-19:10
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 6622.56 110519.79 04-FEB-06:00 349839.11 27-JUL-18:20
Cooling:EnergyTransfer:Zone:BASEMENT 515.04 13111.04 24-APR-14:00 24569.48 31-OCT-21:00
General:Cooling:EnergyTransfer 6622.56 110519.79 04-FEB-06:00 349839.11 27-JUL-18:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 515.04 13111.04 24-APR-14:00 24569.48 31-OCT-21:00
EnergyTransfer:Zone:RETAIL_1_FLR_1 56.47 301.71 04-FEB-07:10 3941.00 09-DEC-12:30
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 56.47 301.71 04-FEB-07:10 3941.00 09-DEC-12:30
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 56.47 301.71 04-FEB-07:10 3941.00 09-DEC-12:30
EnergyTransfer:Zone:RETAIL_2_FLR_1 45.94 1040.45 20-MAR-12:20 2337.81 28-JUL-21:00
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 45.94 1040.45 20-MAR-12:20 2337.81 28-JUL-21:00
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 45.94 1040.45 20-MAR-12:20 2337.81 28-JUL-21:00
EnergyTransfer:Zone:MECH_FLR_1 44.95 1019.93 05-FEB-06:00 2494.54 28-JUL-20:00
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:MECH_FLR_1 44.95 1019.93 05-FEB-06:00 2494.54 28-JUL-20:00
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 44.95 1019.93 05-FEB-06:00 2494.54 28-JUL-20:00
EnergyTransfer:Zone:STORAGE_FLR_1 21.11 487.25 04-FEB-08:00 986.60 28-JUL-21:00
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 21.11 487.25 04-FEB-08:00 986.60 28-JUL-21:00
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 21.11 487.25 04-FEB-08:00 986.60 28-JUL-21:00
EnergyTransfer:Zone:LAUNDRY_FLR_1 626.89 10265.37 04-FEB-06:00 38927.86 28-JUL-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 626.89 10265.37 04-FEB-06:00 38927.86 28-JUL-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 626.89 10265.37 04-FEB-06:00 38927.86 28-JUL-20:00
EnergyTransfer:Zone:CAFE_FLR_1 268.86 4903.53 16-MAR-08:30 13485.03 09-DEC-12:30
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 268.86 4903.53 16-MAR-08:30 13485.03 09-DEC-12:30
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 268.86 4903.53 16-MAR-08:30 13485.03 09-DEC-12:30
EnergyTransfer:Zone:LOBBY_FLR_1 915.83 20109.12 16-MAR-09:30 43747.03 18-SEP-21:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 915.83 20109.12 16-MAR-09:30 43747.03 18-SEP-21:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 915.83 20109.12 16-MAR-09:30 43747.03 18-SEP-21:10
EnergyTransfer:Zone:ROOM_1_FLR_3 105.37 1.04 13-NOV-04:40 10895.10 30-SEP-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 0.06 0.00 01-JAN-00:10 1272.70 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 0.06 0.00 01-JAN-00:10 1272.70 04-FEB-07:00
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 105.30 0.00 25-JAN-04:40 10895.10 30-SEP-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 105.30 0.00 25-JAN-04:40 10895.10 30-SEP-15:10
EnergyTransfer:Zone:ROOM_2_FLR_3 96.44 0.07 27-NOV-06:00 10663.89 28-JUL-15:20
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 0.15 0.00 01-JAN-00:10 1512.45 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 0.15 0.00 01-JAN-00:10 1512.45 04-FEB-07:00
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 96.29 0.00 25-JAN-01:10 10663.89 28-JUL-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 96.29 0.00 25-JAN-01:10 10663.89 28-JUL-15:20
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 666.59 6178.73 04-FEB-07:00 52678.59 03-DEC-14:00
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 666.59 6178.73 04-FEB-07:00 52678.59 03-DEC-14:00
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 666.59 6178.73 04-FEB-07:00 52678.59 03-DEC-14:00
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 750.45 95.21 04-FEB-07:00 68405.60 29-JUL-15:20
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 0.25 0.00 01-JAN-00:10 10976.32 04-FEB-19:10
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 0.25 0.00 01-JAN-00:10 10976.32 04-FEB-19:10
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 750.20 0.00 03-FEB-16:20 68405.60 29-JUL-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 750.20 0.00 03-FEB-16:20 68405.60 29-JUL-15:20
EnergyTransfer:Zone:ROOM_5_FLR_3 106.44 0.63 23-JAN-05:10 9189.86 29-JUL-15:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 0.05 0.00 01-JAN-00:10 1340.02 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 0.05 0.00 01-JAN-00:10 1340.02 04-FEB-07:00
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 106.40 0.00 23-JAN-04:50 9189.86 29-JUL-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 106.40 0.00 23-JAN-04:50 9189.86 29-JUL-15:10
EnergyTransfer:Zone:ROOM_6_FLR_3 97.35 0.02 13-DEC-02:30 9310.80 23-JUL-08:10
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 0.13 0.00 01-JAN-00:10 1593.91 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 0.13 0.00 01-JAN-00:10 1593.91 04-FEB-07:00
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 97.22 0.00 23-JAN-01:50 9310.80 23-JUL-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 97.22 0.00 23-JAN-01:50 9310.80 23-JUL-08:10
EnergyTransfer:Zone:CORRIDOR_FLR_3 249.43 5817.86 04-FEB-07:30 12119.84 21-SEP-20:10
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 249.43 5817.86 04-FEB-07:30 12119.84 21-SEP-20:10
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 249.43 5817.86 04-FEB-07:30 12119.84 21-SEP-20:10
EnergyTransfer:Zone:ROOM_1_FLR_6 25.80 0.10 27-JAN-05:30 2871.62 28-JUL-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 0.07 0.00 01-JAN-00:10 607.26 16-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 0.07 0.00 01-JAN-00:10 607.26 16-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 25.73 0.00 08-JAN-06:10 2871.62 28-JUL-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 25.73 0.00 08-JAN-06:10 2871.62 28-JUL-15:10
EnergyTransfer:Zone:ROOM_2_FLR_6 23.58 0.11 14-DEC-03:10 2884.25 28-JUL-15:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 0.15 0.00 01-JAN-00:10 806.37 04-FEB-09:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 0.15 0.00 01-JAN-00:10 806.37 04-FEB-09:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 23.43 0.00 08-JAN-06:10 2884.25 28-JUL-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 23.43 0.00 08-JAN-06:10 2884.25 28-JUL-15:10
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 152.28 6.21 05-FEB-06:30 12706.22 25-OCT-15:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 0.03 0.00 01-JAN-00:10 1451.12 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 0.03 0.00 01-JAN-00:10 1451.12 04-FEB-07:00
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 152.25 0.00 08-JAN-06:50 12706.22 25-OCT-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 152.25 0.00 08-JAN-06:50 12706.22 25-OCT-15:10
EnergyTransfer:Zone:BANQUET_FLR_6 508.91 10239.04 16-MAR-09:30 23745.11 27-JUL-21:20
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 508.91 10239.04 16-MAR-09:30 23745.11 27-JUL-21:20
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 508.91 10239.04 16-MAR-09:30 23745.11 27-JUL-21:20
EnergyTransfer:Zone:DINING_FLR_6 542.11 11148.25 16-MAR-09:20 24912.27 27-JUL-21:20
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 542.11 11148.25 16-MAR-09:20 24912.27 27-JUL-21:20
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 542.11 11148.25 16-MAR-09:20 24912.27 27-JUL-21:20
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 669.30 9742.88 04-FEB-04:00 30940.07 23-JUL-10:50
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 669.30 9742.88 04-FEB-04:00 30940.07 23-JUL-10:50
EnergyTransfer:Zone:CORRIDOR_FLR_6 134.33 2156.89 04-FEB-07:10 7279.13 28-JUL-15:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 134.33 2156.89 04-FEB-07:10 7279.13 28-JUL-15:40
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 134.33 2156.89 04-FEB-07:10 7279.13 28-JUL-15:40
PlantLoopHeatingDemand:Facility 538.75 6417.41 18-JUL-01:30 43616.87 04-FEB-07:10
PlantLoopHeatingDemand:Plant 535.81 6417.41 18-JUL-01:30 39062.66 19-JAN-07:30
WaterSystems:PlantLoopHeatingDemand 535.81 6417.41 18-JUL-01:30 39062.66 19-JAN-07:30
General:WaterSystems:PlantLoopHeatingDemand 535.81 6417.41 18-JUL-01:30 39062.66 19-JAN-07:30
EnergyTransfer:HVAC 14878.37 1573.31 20-MAR-10:10 969562.51 27-JUL-18:10
HeatingCoils:EnergyTransfer 2.94 0.00 01-JAN-00:10 23756.63 20-DEC-23:10
PlantLoopHeatingDemand:HVAC 2.94 0.00 01-JAN-00:10 23756.63 20-DEC-23:10
HeatingCoils:PlantLoopHeatingDemand 2.94 0.00 01-JAN-00:10 23756.63 20-DEC-23:10
CoolingCoils:EnergyTransfer 11482.27 0.00 25-JAN-04:20 721622.03 25-SEP-21:00
HeatRecoveryForHeating:EnergyTransfer 63.54 0.00 01-JAN-00:10 213380.66 04-FEB-06:10
HeatRecoveryForCooling:EnergyTransfer 3329.61 0.00 01-JAN-00:10 290217.06 14-JUL-11:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 535.81 6417.41 18-JUL-01:30 39062.66 19-JAN-07:30
WaterUse:WaterSystems:EnergyTransfer 535.81 6417.41 18-JUL-01:30 39062.66 19-JAN-07:30
Boilers:EnergyTransfer 2.90 0.00 01-JAN-00:10 16120.77 04-FEB-07:00
Chillers:EnergyTransfer 11649.28 0.00 25-JAN-04:20 727706.31 25-SEP-21:00
HeatRejection:EnergyTransfer 15175.53 0.00 25-JAN-04:20 921736.40 27-JUL-18:10
General:HeatRejection:EnergyTransfer 15175.53 0.00 25-JAN-04:20 921736.40 27-JUL-18:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -515.047 0.000 0.000 136.196 173.462 150.255 0.000 0.000 0.000 55.133 0.000 0.000 0.000 0.000 0.000
RETAIL_1_FLR_1 0.000 0.000 0.000 -56.469 0.000 0.000 14.121 8.614 10.186 20.546 0.000 0.793 5.445 0.000 -2.801 0.000 -0.434 -0.000
RETAIL_2_FLR_1 0.000 0.000 0.000 -45.936 0.000 0.000 16.071 9.975 11.795 0.000 0.000 0.319 7.971 0.000 0.000 0.000 -0.195 0.000
MECH_FLR_1 0.000 0.000 0.000 -44.953 0.000 0.000 3.460 16.635 12.471 0.000 0.000 0.768 12.021 0.000 0.000 0.000 -0.402 0.000
STORAGE_FLR_1 0.000 0.000 0.000 -21.108 0.000 0.000 2.679 2.785 3.598 0.000 0.000 0.452 11.817 0.000 0.000 0.000 -0.222 0.000
LAUNDRY_FLR_1 0.000 0.000 0.000 -626.892 0.000 0.000 11.290 4.368 658.131 0.000 0.000 1.269 0.000 0.000 0.000 0.000 -0.569 -47.597
CAFE_FLR_1 0.000 0.000 0.000 -268.860 0.000 0.000 180.327 18.040 14.341 57.280 0.000 1.730 7.177 0.000 -8.840 0.000 -1.195 -0.000
LOBBY_FLR_1 0.000 0.000 0.000 -915.836 0.000 0.000 535.469 122.013 148.998 76.918 0.000 5.062 42.148 0.000 -11.322 0.000 -3.450 -0.002
ROOM_1_FLR_3 0.180 -84.819 0.000 -20.598 0.000 0.000 9.635 6.366 12.292 48.701 0.000 3.349 30.026 0.000 -4.093 0.000 -1.040 0.000
ROOM_2_FLR_3 0.377 -76.018 0.000 -20.505 0.000 0.000 9.645 6.366 12.291 40.755 0.000 3.363 28.819 0.000 -4.072 0.000 -1.022 0.000
ROOM_3_MULT19_FLR_3 0.000 -335.426 0.000 -331.156 0.000 0.000 0.000 76.021 228.754 257.812 0.000 11.308 143.931 0.000 -31.254 0.000 -19.990 0.000
ROOM_4_MULT19_FLR_3 1.114 -478.075 0.000 -272.969 0.000 0.000 184.040 76.042 228.817 157.485 0.000 22.870 109.922 0.000 -19.760 0.000 -9.485 -0.008
ROOM_5_FLR_3 0.163 -85.853 0.000 -20.655 0.000 0.000 9.629 6.366 12.292 49.848 0.000 3.335 29.860 0.000 -3.924 0.000 -1.062 0.000
ROOM_6_FLR_3 0.347 -76.854 0.000 -20.575 0.000 0.000 9.638 6.366 12.291 41.787 0.000 3.341 28.509 0.000 -3.808 0.000 -1.042 0.000
CORRIDOR_FLR_3 0.000 0.000 0.000 -249.427 0.000 0.000 108.272 109.603 0.000 44.324 0.000 2.225 0.001 0.000 -7.083 0.000 -1.327 -6.588
ROOM_1_FLR_6 0.156 -20.670 0.000 -5.142 0.000 0.000 2.410 1.592 3.073 12.125 0.000 0.845 6.859 0.000 -0.977 0.000 -0.271 -0.000
ROOM_2_FLR_6 0.299 -18.460 0.000 -5.116 0.000 0.000 2.413 1.591 3.073 10.168 0.000 0.848 6.416 0.000 -0.965 0.000 -0.267 -0.000
ROOM_3_MULT9_FLR_6 0.110 -119.190 0.000 -33.142 0.000 0.000 21.673 9.005 27.097 58.979 0.000 4.269 37.383 0.000 -4.470 0.000 -1.713 -0.000
BANQUET_FLR_6 0.000 0.000 0.000 -508.911 0.000 0.000 314.752 34.752 175.857 13.926 0.000 1.038 0.000 0.000 -4.630 0.000 -0.816 -25.969
DINING_FLR_6 0.000 0.000 0.000 -542.118 0.000 0.000 314.417 34.752 175.857 13.597 0.000 1.028 8.174 0.000 -4.883 0.000 -0.825 -0.000
KITCHEN_FLR_6 0.000 0.000 0.000 -669.283 0.000 0.000 28.122 13.327 550.372 22.723 0.000 0.916 58.410 0.000 -3.860 0.000 -0.727 0.000
CORRIDOR_FLR_6 0.000 0.000 0.000 -134.330 0.000 0.000 28.918 28.999 0.000 20.285 0.000 0.956 58.919 0.000 -3.210 0.000 -0.539 0.000
Total Facility 2.747 -1295.365 0.000 -5329.030 0.000 0.000 1943.179 767.039 2451.839 947.258 0.000 70.085 688.943 0.000 -119.950 0.000 -46.593 -80.164


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 31-OCT-21:00 0.00 0.00 0.00 -24569.86 0.00 0.00 5924.42 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -3545.35
RETAIL_1_FLR_1 09-DEC-12:30 0.00 0.00 0.00 -3940.37 0.00 0.00 225.91 195.67 252.59 4590.65 0.00 37.30 0.00 0.00 -0.00 0.00 0.00 -1361.75
RETAIL_2_FLR_1 28-JUL-21:00 0.00 0.00 0.00 -2337.83 0.00 0.00 697.61 725.08 752.15 0.00 0.00 23.99 139.00 0.00 -0.00 0.00 0.00 0.00
MECH_FLR_1 28-JUL-20:00 0.00 0.00 0.00 -2494.57 0.00 0.00 129.09 1360.40 839.45 0.00 0.00 45.30 120.34 0.00 -0.00 0.00 0.00 0.00
STORAGE_FLR_1 28-JUL-21:00 0.00 0.00 0.00 -986.62 0.00 0.00 113.48 202.41 229.41 0.00 0.00 32.71 408.61 0.00 -0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 28-JUL-20:00 0.00 0.00 0.00 -38927.07 0.00 0.00 408.80 357.21 44299.38 0.00 0.00 61.84 0.00 0.00 -0.00 0.00 0.00 -6200.16
CAFE_FLR_1 09-DEC-12:30 0.00 0.00 0.00 -13482.90 0.00 0.00 2968.89 298.55 355.63 12881.53 0.00 82.48 0.00 0.00 -0.00 0.00 0.00 -3104.18
LOBBY_FLR_1 18-SEP-21:10 0.00 0.00 0.00 -43755.52 0.00 0.00 26440.01 6843.46 7389.94 540.68 0.00 315.74 2225.69 0.00 -0.00 0.00 0.00 0.00
ROOM_1_FLR_3 24-FEB-16:02 0.00 -11155.65 0.00 -746.44 0.00 0.00 235.29 137.21 273.93 7392.72 0.00 61.16 3801.79 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_3 21-AUG-15:02 0.00 -11196.61 0.00 -755.11 0.00 0.00 235.28 137.19 273.90 5758.32 0.00 202.28 5344.75 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 03-DEC-14:00 0.00 -41856.13 0.00 -10820.76 0.00 0.00 0.00 1930.94 5686.12 51681.15 0.00 147.68 0.00 0.00 -0.00 0.00 0.00 -6769.00
ROOM_4_MULT19_FLR_3 17-APR-18:02 0.00 -68138.41 0.00 -10334.98 0.00 0.00 6374.71 5209.05 9610.21 6695.67 0.00 1009.08 49574.67 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 10-SEP-15:02 0.00 -9952.09 0.00 -757.61 0.00 0.00 130.71 161.71 305.54 3100.11 0.00 220.32 6791.30 0.00 -0.00 0.00 0.00 0.00
ROOM_6_FLR_3 27-JUL-15:02 0.00 -10059.21 0.00 -756.04 0.00 0.00 235.29 137.19 273.90 3098.31 0.00 307.29 6763.27 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 21-SEP-20:10 0.00 0.00 0.00 -12120.26 0.00 0.00 4663.27 7967.22 0.00 464.54 0.00 158.03 0.00 0.00 -0.00 0.00 0.00 -1132.80
ROOM_1_FLR_6 17-SEP-15:02 0.00 -2919.77 0.00 -190.51 0.00 0.00 32.68 40.43 76.39 1824.79 0.00 54.29 1081.71 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_6 02-AUG-15:02 0.00 -2921.69 0.00 -188.57 0.00 0.00 58.82 34.30 68.48 1477.85 0.00 55.09 1415.73 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 24-OCT-15:02 0.00 -12054.72 0.00 -1247.81 0.00 0.00 529.38 194.07 603.86 6472.74 0.00 189.95 5312.54 0.00 -0.00 0.00 0.00 0.00
BANQUET_FLR_6 27-JUL-21:20 0.00 0.00 0.00 -23751.17 0.00 0.00 15627.77 2062.70 6747.90 181.61 0.00 80.66 0.00 0.00 -0.00 0.00 0.00 -949.47
DINING_FLR_6 27-JUL-21:20 0.00 0.00 0.00 -24918.75 0.00 0.00 15623.04 2062.70 6747.90 167.09 0.00 80.63 237.38 0.00 -0.00 0.00 0.00 0.00
KITCHEN_FLR_6 23-JUL-10:50 0.00 0.00 0.00 -30941.70 0.00 0.00 459.46 363.28 24259.91 2803.21 0.00 123.44 2932.41 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 28-JUL-15:40 0.00 0.00 0.00 -7278.50 0.00 0.00 771.15 658.76 0.00 1531.53 0.00 152.79 4164.26 0.00 -0.00 0.00 0.00 0.00
Total Facility 28-JUL-18:02 0.00 -145829.36 0.00 -227066.19 0.00 0.00 73842.98 53571.31 122326.88 36339.61 0.00 5835.80 80978.97 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MECH_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 16-MAR-08:62 4358.04 420.54 0.00 -420.54 0.00 0.00 101.10 215.61 453.05 0.00 0.00 0.00 0.00 0.00 -531.13 0.00 -359.71 -4236.95
ROOM_2_FLR_3 25-JAN-09:02 5333.05 406.96 0.00 -406.96 0.00 0.00 101.97 215.58 452.99 0.00 0.00 0.00 0.00 0.00 -510.80 0.00 -269.55 -5323.24
ROOM_3_MULT19_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 03-FEB-16:03 29974.94 6181.96 0.00 -6181.96 0.00 0.00 4979.41 1638.79 5099.29 73.25 0.00 0.00 0.00 0.00 -0.00 0.00 -14154.26 -27611.42
ROOM_5_FLR_3 03-FEB-16:04 2795.58 456.13 0.00 -456.13 0.00 0.00 244.24 137.21 273.93 868.90 0.00 0.00 0.00 0.00 -0.00 0.00 -661.54 -3658.32
ROOM_6_FLR_3 03-FEB-16:03 3352.03 456.02 0.00 -456.02 0.00 0.00 258.77 137.19 273.90 0.00 0.00 0.00 0.00 0.00 -37.32 0.00 -842.14 -3142.43
CORRIDOR_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 16-MAR-08:62 1582.34 93.85 0.00 -93.85 0.00 0.00 26.20 53.90 113.26 0.00 0.00 0.00 0.00 0.00 -113.02 0.00 -86.03 -1576.66
ROOM_2_FLR_6 25-JAN-09:02 1606.93 89.92 0.00 -89.92 0.00 0.00 26.32 53.90 113.25 0.00 0.00 0.00 0.00 0.00 -108.12 0.00 -63.31 -1628.97
ROOM_3_MULT9_FLR_6 16-MAR-08:62 5671.68 676.48 0.00 -676.48 0.00 0.00 227.07 304.96 998.70 407.57 0.00 0.00 0.00 0.00 -0.00 0.00 -416.50 -7193.48
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 19-MAR-15:05 -86013.20 132679.70 0.00 -132679.70 0.00 0.00 33529.78 14962.59 75140.94 28910.45 0.00 0.00 0.00 0.00 0.00 0.00 -32124.90 -34405.64



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 21.3152 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 21.1936 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 11.6594 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.6594 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.000000 142.3000 0.003581 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.001045 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.7099 2.7099 1.4823 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2894 0.2894 0.1583 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2418 0.2418 0.1322 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2491 0.2491 0.1362 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1207 0.1207 0.0660 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.2597 3.2597 1.7831 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2688 1.2688 0.6940 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.4105 4.4105 2.4126 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3607 1.3607 0.7443 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1821 2.1821 1.1936 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2859 2.2859 1.2504 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2113 2.2113 1.2096 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7253 0.7253 0.3967 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 21.3152 21.1936 21.3152 11.6594 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4823 1.4823 1.4823 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1583 0.1583 0.1583 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1322 0.1322 0.1322 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1362 0.1362 0.1362 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0660 0.0660 0.0660 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7831 1.7831 1.7831 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6940 0.6940 0.6940 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4126 2.4126 2.4126 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7443 0.7443 0.7443 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1936 1.1936 1.1936 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2504 1.2504 1.2504 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2096 1.2096 1.2096 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3967 0.3967 0.3967 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 11.6594 11.6594 11.6594 11.6594 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 83.00
Number of hours not met 83.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 4.75 24733.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 3526.25 218650.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 767.04 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 243.08 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 959.56 59492.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 14.43 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 8.99 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 32.45 1868.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.91 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 630.18 42569.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 198.09 8018.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 304.34 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.74 4738.72 2540.69 219704.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 20.59 1895.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 35.37 1204.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1808.06 8219.26
Natural Gas 1788.84 4334.28
Additional 0.00 0.00
Total 3596.90 12553.54


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 67.61
Space Heating 0.00
Space Cooling 310.81
Fans (All) 55.55
Service Water Heating 8.00
Receptacle Equipment 153.81
Miscellaneous (All) 724.47
Subtotal 724.47


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.42
Service Water Heating 223.94
Miscellaneous (All) 382.03
Subtotal 382.03


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 6.11
Space Heating 0.04
Space Cooling 28.09
Fans (All) 5.02
Service Water Heating 20.96
Receptacle Equipment 28.15
Miscellaneous 11.63


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2667. 8760.
LTG_SCH_LOBBY 3061. 8760.
LTG_SCH_STORAGE 1339. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 2678. 8760.
LTG_SCH_GUESTROOM 2482. 8760.
LTG_SCH_CORRIDOR 3061. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3924. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 18.89 365 18.89 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 23.33 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8760.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 8760.00 0.00 0.00 0.00 0.00
Sum 192720.00 0.00 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 0.00 0.00 0.00 0.00
Average 288887.05 0.00 0.00 0.00 0.00
Sum 6355515.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8750.83 9.17 0.00 0.00 0.00
RETAIL_2_FLR_1 8127.50 632.50 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 5497.67 3262.33 0.00 0.00 0.00
LOBBY_FLR_1 5862.50 2897.50 0.00 0.00 0.00
ROOM_1_FLR_3 8758.67 1.33 0.00 0.00 0.00
ROOM_2_FLR_3 8758.83 1.17 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8734.33 25.67 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8758.33 1.67 0.00 0.00 0.00
ROOM_5_FLR_3 8758.50 1.50 0.00 0.00 0.00
ROOM_6_FLR_3 8758.50 1.50 0.00 0.00 0.00
CORRIDOR_FLR_3 7873.33 886.67 0.00 0.00 0.00
ROOM_1_FLR_6 8756.50 3.50 0.00 0.00 0.00
ROOM_2_FLR_6 8757.33 2.67 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8753.33 6.67 0.00 0.00 0.00
BANQUET_FLR_6 5801.83 2958.17 0.00 0.00 0.00
DINING_FLR_6 6010.33 2749.67 0.00 0.00 0.00
KITCHEN_FLR_6 8309.83 450.17 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 5497.67 0.00 0.00 0.00 0.00
Max 8760.00 3262.33 0.00 0.00 0.00
Average 8128.55 631.45 0.00 0.00 0.00
Sum 178828.17 13891.83 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50096.50 82.50 0.00 0.00 0.00
RETAIL_2_FLR_1 52367.00 6789.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 333495.67 376921.33 0.00 0.00 0.00
LOBBY_FLR_1 1134091.83 981337.17 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 85435.33 14922.67 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 649019.00 596696.00 0.00 0.00 0.00
DINING_FLR_6 684377.17 561337.83 0.00 0.00 0.00
KITCHEN_FLR_6 104609.17 3659.83 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 1134091.83 981337.17 0.00 0.00 0.00
Average 173353.12 115533.92 0.00 0.00 0.00
Sum 3813768.67 2541746.33 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:32

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

For: Environment

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A

For: Environment

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI

For: Environment

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.444810E+11 23272.03 04-JAN-22:00 18.90 17.12 0.816293E+10 4837.23 25-JAN-23:10 12.20 8.81
February 0.382190E+11 21870.21 01-FEB-22:00 22.20 18.84 0.728506E+10 4837.12 24-FEB-22:10 16.02 11.81
March 0.400042E+11 19483.82 01-MAR-22:00 17.80 14.81 0.786402E+10 4837.04 09-MAR-22:19 23.30 22.07
April 0.384314E+11 18385.70 16-APR-10:33 28.67 21.62 0.746361E+10 4786.82 06-APR-22:10 28.67 21.62
May 0.407969E+11 18658.85 14-MAY-10:33 29.23 23.78 0.782443E+10 4837.03 25-MAY-21:19 23.90 22.53
June 0.402434E+11 18849.78 11-JUN-10:33 30.93 23.60 0.764551E+10 4837.03 15-JUN-21:19 28.30 23.49
July 0.434846E+11 21036.68 13-JUL-21:00 27.80 24.87 0.802563E+10 4837.05 12-JUL-21:19 27.80 24.87
August 0.454776E+11 23279.64 25-AUG-21:00 26.70 24.27 0.817771E+10 4837.05 10-AUG-23:19 26.70 24.27
September 0.453892E+11 24192.14 22-SEP-21:00 28.30 25.04 0.792006E+10 4837.06 14-SEP-21:19 28.30 25.04
October 0.472787E+11 24569.48 31-OCT-21:00 24.40 22.88 0.818681E+10 4837.07 23-OCT-21:30 24.40 22.88
November 0.453684E+11 24567.19 21-NOV-22:00 24.40 22.49 0.792234E+10 4837.11 15-NOV-00:10 24.40 22.49
December 0.458701E+11 24379.78 12-DEC-22:00 15.00 10.83 0.818685E+10 4837.19 14-DEC-01:39 15.93 15.40
                     
Annual Sum or Average 0.515044E+12         0.946649E+11        
Minimum of Months 0.382190E+11 18385.70   15.00 10.83 0.728506E+10 4786.82   12.20 8.81
Maximum of Months 0.472787E+11 24569.48   30.93 25.04 0.818685E+10 4837.23   28.67 25.04



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.436465E+10 3617.49 02-JAN-14:30 28.90 24.11 0.747197E+09 491.82 02-JAN-22:19 21.67 19.71
February 0.400333E+10 3540.56 11-FEB-14:10 29.22 24.12 0.688103E+09 491.83 27-FEB-22:19 21.33 15.04
March 0.431632E+10 2801.89 04-MAR-11:33 27.03 22.82 0.772471E+09 491.83 31-MAR-21:19 23.23 18.15
April 0.437807E+10 2589.75 13-APR-13:10 29.32 23.85 0.763564E+09 491.83 17-APR-21:30 23.05 17.57
May 0.463463E+10 2386.76 22-MAY-18:03 30.40 23.74 0.806770E+09 491.82 22-MAY-23:19 25.20 22.38
June 0.468282E+10 2552.32 29-JUN-18:13 30.00 24.84 0.794500E+09 491.82 16-JUN-23:19 30.00 24.84
July 0.509044E+10 2775.54 29-JUL-17:02 34.22 24.14 0.822728E+09 491.82 30-JUL-23:19 27.03 24.30
August 0.501681E+10 2781.78 20-AUG-12:00 32.20 26.10 0.821435E+09 491.83 14-AUG-23:19 32.20 26.10
September 0.521120E+10 3528.51 30-SEP-13:10 30.68 24.82 0.797048E+09 491.83 12-SEP-23:19 30.68 24.82
October 0.541800E+10 3739.75 25-OCT-12:30 30.00 22.10 0.817539E+09 491.83 17-OCT-23:19 30.00 22.10
November 0.481442E+10 3808.04 07-NOV-13:20 27.97 21.09 0.765195E+09 491.83 09-NOV-00:20 24.80 21.07
December 0.453798E+10 3941.00 09-DEC-12:30 27.20 22.50 0.756870E+09 491.82 09-DEC-00:20 27.20 22.50
                     
Annual Sum or Average 0.564687E+11         0.935342E+10        
Minimum of Months 0.400333E+10 2386.76   27.03 21.09 0.688103E+09 491.82   21.33 15.04
Maximum of Months 0.541800E+10 3941.00   34.22 26.10 0.822728E+09 491.83   32.20 26.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.351945E+10 1960.68 13-JAN-22:00 24.40 20.99 0.916267E+09 569.54 03-JAN-00:20 24.40 20.99
February 0.326491E+10 1938.10 22-FEB-22:00 19.40 14.76 0.834962E+09 569.54 23-FEB-00:20 17.77 15.47
March 0.367885E+10 2084.98 28-MAR-21:00 24.40 21.00 0.934091E+09 569.54 31-MAR-23:19 22.73 18.09
April 0.374234E+10 2227.53 13-APR-21:00 25.60 22.81 0.913664E+09 569.54 20-APR-22:10 22.20 16.88
May 0.400067E+10 2235.10 17-MAY-21:00 26.10 22.56 0.951875E+09 569.54 08-MAY-23:19 26.10 22.56
June 0.397443E+10 2305.33 09-JUN-21:00 29.40 24.96 0.927554E+09 569.54 19-JUN-23:19 26.70 23.65
July 0.422630E+10 2337.81 28-JUL-21:00 29.40 24.13 0.958419E+09 569.54 14-JUL-23:19 29.40 24.13
August 0.412854E+10 2323.47 17-AUG-21:00 27.80 24.58 0.958990E+09 569.54 07-AUG-23:19 27.80 24.58
September 0.403972E+10 2307.56 01-SEP-21:00 28.90 24.03 0.928171E+09 569.54 26-SEP-23:19 24.23 22.15
October 0.405526E+10 2268.07 06-OCT-21:00 26.70 23.40 0.955548E+09 569.54 17-OCT-23:19 24.40 18.65
November 0.369959E+10 2122.62 08-NOV-22:00 25.60 21.66 0.910239E+09 569.54 01-NOV-23:19 25.60 21.66
December 0.360585E+10 2075.82 08-DEC-22:00 23.90 22.40 0.922736E+09 569.54 04-DEC-00:20 23.90 22.40
                     
Annual Sum or Average 0.459359E+11         0.111125E+11        
Minimum of Months 0.326491E+10 1938.10   19.40 14.76 0.834962E+09 569.54   17.77 15.47
Maximum of Months 0.422630E+10 2337.81   29.40 24.96 0.958990E+09 569.54   29.40 24.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.332233E+10 1635.92 01-JAN-11:33 26.30 21.34 0.181777E+09 118.82 03-JAN-22:19 22.03 20.47
February 0.308434E+10 1666.95 11-FEB-11:33 27.60 23.74 0.166970E+09 120.22 17-FEB-22:19 23.90 20.81
March 0.346900E+10 1668.11 05-MAR-11:33 27.77 23.38 0.187146E+09 120.45 30-MAR-21:19 23.90 19.93
April 0.357873E+10 1919.85 14-APR-20:00 26.10 23.27 0.186862E+09 120.45 17-APR-21:30 23.05 17.57
May 0.396873E+10 2218.40 31-MAY-20:00 27.80 24.12 0.199157E+09 120.45 08-MAY-21:19 27.80 24.12
June 0.408791E+10 2454.10 29-JUN-20:00 28.90 25.14 0.196396E+09 120.45 14-JUN-21:19 28.90 25.14
July 0.435040E+10 2494.54 28-JUL-20:00 28.30 23.96 0.203116E+09 120.45 06-JUL-21:19 28.30 23.96
August 0.413257E+10 2399.69 21-AUG-20:00 28.30 24.58 0.201826E+09 120.45 23-AUG-21:30 26.70 22.51
September 0.404050E+10 2396.65 22-SEP-20:00 28.30 25.04 0.195491E+09 120.45 14-SEP-21:30 28.30 25.04
October 0.393402E+10 2093.93 03-OCT-20:00 27.80 25.31 0.198794E+09 120.45 19-OCT-21:19 24.23 19.31
November 0.356062E+10 1853.40 03-NOV-21:00 26.70 24.27 0.186614E+09 120.45 01-NOV-21:19 26.70 24.27
December 0.342354E+10 1707.14 09-DEC-12:30 27.20 22.50 0.185020E+09 120.45 01-DEC-22:19 27.20 22.50
                     
Annual Sum or Average 0.449527E+11         0.228917E+10        
Minimum of Months 0.308434E+10 1635.92   26.10 21.34 0.166970E+09 118.82   22.03 17.57
Maximum of Months 0.435040E+10 2494.54   28.90 25.31 0.203116E+09 120.45   28.90 25.14



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.158319E+10 792.56 01-JAN-11:33 26.30 21.34 0.137865E+09 87.98 03-JAN-22:40 21.87 20.31
February 0.146945E+10 807.65 11-FEB-11:33 27.60 23.74 0.126566E+09 89.00 17-FEB-23:10 23.90 20.81
March 0.165137E+10 806.37 05-MAR-11:33 27.77 23.38 0.141790E+09 89.17 30-MAR-22:10 23.80 20.03
April 0.170054E+10 851.13 16-APR-10:33 28.67 21.62 0.141628E+09 91.66 14-APR-21:00 28.67 21.62
May 0.185608E+10 872.81 31-MAY-10:33 32.23 24.19 0.151662E+09 92.66 22-MAY-21:19 32.23 24.19
June 0.188334E+10 956.43 29-JUN-21:00 28.90 24.82 0.150414E+09 92.65 14-JUN-21:19 28.90 24.82
July 0.199832E+10 986.60 28-JUL-21:00 29.40 24.13 0.155883E+09 92.66 12-JUL-23:19 29.40 24.13
August 0.191962E+10 933.49 21-AUG-21:00 28.30 25.04 0.154432E+09 92.66 23-AUG-21:30 26.70 22.51
September 0.187051E+10 937.91 22-SEP-21:00 28.30 25.04 0.149680E+09 92.66 24-SEP-23:19 26.70 23.55
October 0.185332E+10 874.52 09-OCT-10:33 31.27 23.88 0.151485E+09 92.65 06-OCT-21:40 31.27 23.88
November 0.169156E+10 828.35 04-NOV-10:33 28.13 24.58 0.141618E+09 91.55 03-NOV-22:10 28.13 24.58
December 0.163023E+10 831.23 09-DEC-12:30 27.20 22.50 0.140268E+09 90.02 08-DEC-23:10 27.20 22.50
                     
Annual Sum or Average 0.211075E+11         0.174329E+10        
Minimum of Months 0.146945E+10 792.56   26.30 21.34 0.126566E+09 87.98   21.87 20.03
Maximum of Months 0.199832E+10 986.60   32.23 25.04 0.155883E+09 92.66   32.23 24.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.516621E+11 37960.95 13-JAN-21:00 24.40 20.99 0.584283E+09 381.74 09-JAN-22:10 24.40 20.99
February 0.470243E+11 37968.68 17-FEB-21:00 23.90 20.81 0.528433E+09 381.76 24-FEB-22:10 16.02 11.81
March 0.525295E+11 38234.70 27-MAR-20:00 24.40 20.99 0.587195E+09 381.71 14-MAR-21:10 24.40 20.99
April 0.514735E+11 38560.68 14-APR-20:00 26.10 23.27 0.568248E+09 381.69 14-APR-21:10 25.50 22.67
May 0.538686E+11 38682.63 31-MAY-20:00 27.80 24.12 0.589032E+09 381.71 19-MAY-21:10 27.80 24.12
June 0.526770E+11 38828.79 09-JUN-20:00 29.40 24.96 0.571960E+09 381.74 16-JUN-21:10 28.30 22.46
July 0.545174E+11 38927.86 28-JUL-20:00 28.30 23.96 0.589656E+09 381.73 07-JUL-21:10 28.30 23.96
August 0.541388E+11 38764.14 31-AUG-20:00 27.80 24.58 0.590027E+09 381.76 11-AUG-21:10 27.80 24.58
September 0.524688E+11 38735.58 08-SEP-20:00 30.60 24.86 0.570558E+09 381.76 12-SEP-21:10 26.60 23.14
October 0.536343E+11 38577.73 06-OCT-20:00 26.70 23.40 0.588005E+09 381.76 24-OCT-21:10 25.92 21.45
November 0.511542E+11 38264.06 03-NOV-20:00 26.10 24.52 0.567704E+09 381.76 03-NOV-21:10 26.70 24.27
December 0.517371E+11 38072.77 08-DEC-21:00 24.40 22.09 0.584039E+09 381.72 20-DEC-22:10 10.50 8.09
                     
Annual Sum or Average 0.626886E+12         0.691914E+10        
Minimum of Months 0.470243E+11 37960.95   23.90 20.81 0.528433E+09 381.69   10.50 8.09
Maximum of Months 0.545174E+11 38927.86   30.60 24.96 0.590027E+09 381.76   28.30 24.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.215328E+11 13132.58 01-JAN-10:30 25.85 21.37 0.107801E+11 6462.08 27-JAN-04:19 14.23 8.41
February 0.196295E+11 12441.87 11-FEB-14:00 29.40 24.15 0.977622E+10 6462.09 23-FEB-00:20 17.77 15.47
March 0.213122E+11 11089.15 13-MAR-21:10 25.00 22.24 0.108569E+11 6462.10 03-MAR-05:19 25.00 22.24
April 0.211020E+11 11273.60 14-APR-21:10 25.50 22.67 0.105033E+11 6462.11 21-APR-04:19 22.20 17.20
May 0.223646E+11 11538.47 22-MAY-21:10 27.70 22.63 0.108794E+11 6462.06 08-MAY-23:19 27.70 22.63
June 0.224315E+11 11691.76 02-JUN-21:10 28.90 24.83 0.105671E+11 6462.00 04-JUN-23:19 25.60 23.09
July 0.236338E+11 11926.40 27-JUL-21:10 29.22 25.45 0.109197E+11 6462.01 23-JUL-23:19 29.22 25.45
August 0.235709E+11 11881.88 31-AUG-21:10 27.77 24.60 0.109500E+11 6462.01 11-AUG-23:19 27.77 24.60
September 0.238327E+11 12480.12 08-SEP-21:10 29.90 24.64 0.106076E+11 6462.02 26-SEP-23:19 24.23 22.15
October 0.248057E+11 13076.04 25-OCT-15:03 29.22 22.14 0.109550E+11 6462.07 17-OCT-23:19 29.22 22.14
November 0.226978E+11 12668.18 19-NOV-11:00 26.70 21.75 0.105372E+11 6462.14 15-NOV-00:20 26.70 21.75
December 0.219433E+11 13485.03 09-DEC-12:30 27.20 22.50 0.108090E+11 6462.15 14-DEC-00:20 15.60 13.77
                     
Annual Sum or Average 0.268857E+12         0.128141E+12        
Minimum of Months 0.196295E+11 11089.15   25.00 21.37 0.977622E+10 6462.00   14.23 8.41
Maximum of Months 0.248057E+11 13485.03   29.90 25.45 0.109550E+11 6462.15   29.22 25.45



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.712586E+11 39896.53 13-JAN-22:10 24.32 21.03 0.320750E+11 19185.35 26-JAN-00:20 12.20 8.71
February 0.656300E+11 39057.68 17-FEB-22:10 23.90 20.81 0.290287E+11 19185.45 23-FEB-00:20 17.77 15.47
March 0.730617E+11 39155.06 27-MAR-21:10 24.90 21.81 0.322089E+11 19185.44 03-MAR-05:19 24.90 21.81
April 0.733323E+11 40563.34 14-APR-21:10 25.50 22.67 0.311625E+11 19185.52 21-APR-04:19 22.20 17.20
May 0.788568E+11 41407.52 22-MAY-21:10 27.70 22.63 0.322956E+11 19185.33 08-MAY-23:19 27.70 22.63
June 0.789605E+11 42637.11 29-JUN-21:10 28.90 24.82 0.313744E+11 19185.26 04-JUN-23:19 28.90 24.82
July 0.829441E+11 43196.96 28-JUL-21:10 29.32 24.20 0.323571E+11 19185.27 23-JUL-23:19 29.32 24.20
August 0.817161E+11 42890.99 21-AUG-21:10 28.22 25.01 0.324675E+11 19185.27 23-AUG-23:19 25.93 23.26
September 0.805070E+11 43747.03 18-SEP-21:10 28.30 25.12 0.314184E+11 19185.29 26-SEP-23:19 24.23 22.15
October 0.816410E+11 42638.67 06-OCT-21:10 26.70 23.48 0.324556E+11 19185.34 17-OCT-23:19 24.40 18.65
November 0.750275E+11 41777.69 03-NOV-21:10 26.70 24.27 0.312698E+11 19185.59 15-NOV-00:20 18.13 15.20
December 0.728917E+11 40864.19 08-DEC-22:10 23.98 22.48 0.321433E+11 19185.54 14-DEC-00:20 15.60 13.77
                     
Annual Sum or Average 0.915827E+12         0.380257E+12        
Minimum of Months 0.656300E+11 39057.68   23.90 20.81 0.290287E+11 19185.26   12.20 8.71
Maximum of Months 0.829441E+11 43747.03   29.32 25.12 0.324675E+11 19185.59   29.32 24.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.136542E+10 2880.81 02-JAN-16:02 25.50 20.58 98227064.20 56.69 02-JAN-22:49 20.87 19.79
February 0.148715E+10 2975.51 24-FEB-16:02 25.00 13.11 88921113.17 56.69 27-FEB-22:40 20.97 15.02
March 0.184854E+10 2940.06 27-MAR-15:02 27.70 22.36 98656923.79 56.70 30-MAR-23:49 23.30 19.34
April 0.222276E+10 2938.93 14-APR-15:02 30.40 24.46 95679555.32 56.70 13-APR-02:49 30.40 24.46
May 0.252083E+10 2948.49 29-MAY-15:02 32.88 24.35 99049509.72 56.70 23-MAY-02:09 32.88 24.35
June 0.255357E+10 2957.27 28-JUN-15:02 30.50 24.49 95922333.46 56.70 09-JUN-21:19 30.50 24.49
July 0.284269E+10 2953.13 21-JUL-15:02 31.52 25.08 99063754.11 56.70 07-JUL-21:10 31.52 25.08
August 0.271662E+10 2945.26 18-AUG-15:02 31.60 25.09 99124559.12 56.70 31-AUG-21:10 27.77 24.60
September 0.265697E+10 2957.48 30-SEP-15:02 31.10 24.59 95850694.39 56.70 21-SEP-21:10 31.10 24.59
October 0.258306E+10 2932.30 20-OCT-15:02 27.20 21.57 99026078.63 56.70 31-OCT-00:10 26.10 24.11
November 0.197929E+10 2935.27 25-NOV-16:02 27.12 22.15 95610147.84 56.70 02-NOV-23:00 27.12 22.15
December 0.154895E+10 2874.64 01-DEC-16:02 26.42 19.90 98260135.15 56.70 26-DEC-22:00 11.70 10.17
                     
Annual Sum or Average 0.263258E+11         0.116339E+10        
Minimum of Months 0.136542E+10 2874.64   25.00 13.11 88921113.17 56.69   11.70 10.17
Maximum of Months 0.284269E+10 2975.51   32.88 25.09 99124559.12 56.70   32.88 25.08



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.970155E+09 2824.51 03-JAN-16:02 26.42 20.44 97484644.47 56.69 27-JAN-22:19 19.40 15.40
February 0.118669E+10 2963.22 24-FEB-16:02 25.00 13.11 88497787.71 56.69 21-FEB-01:39 25.00 13.11
March 0.161471E+10 2921.61 28-MAR-15:02 26.60 20.66 98383734.39 56.70 30-MAR-22:40 23.50 19.75
April 0.209995E+10 2955.46 12-APR-15:02 27.98 22.83 95637705.72 56.70 12-APR-00:40 27.98 22.83
May 0.251918E+10 2977.76 13-MAY-15:02 30.00 23.99 99058422.13 56.70 22-MAY-21:40 27.40 22.36
June 0.259472E+10 2982.40 28-JUN-15:02 30.50 24.49 95942684.29 56.70 29-JUN-21:10 28.90 24.82
July 0.286896E+10 2985.68 07-JUL-15:02 31.20 24.86 99076605.17 56.70 20-JUL-21:10 28.30 24.59
August 0.266333E+10 2987.73 21-AUG-15:02 30.37 25.25 99122040.36 56.70 02-AUG-21:10 30.37 25.25
September 0.248711E+10 2982.85 10-SEP-15:02 31.10 25.25 95822517.52 56.70 24-SEP-03:30 27.20 24.02
October 0.226285E+10 2958.57 14-OCT-15:02 30.78 23.18 98939402.99 56.70 16-OCT-22:30 25.60 20.84
November 0.163239E+10 2927.74 07-NOV-16:02 28.22 22.20 95326019.41 56.70 22-NOV-22:00 26.10 23.70
December 0.117359E+10 2883.00 02-DEC-16:02 25.50 20.22 97680125.88 56.69 01-DEC-22:10 25.50 20.22
                     
Annual Sum or Average 0.240736E+11         0.116097E+10        
Minimum of Months 0.970155E+09 2824.51   25.00 13.11 88497787.71 56.69   19.40 13.11
Maximum of Months 0.286896E+10 2987.73   31.20 25.25 99122040.36 56.70   30.37 25.25



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.663171E+09 685.38 02-JAN-14:30 28.90 24.11 0.00 0.00 01-JAN-00:10 28.90 24.11
February 0.600553E+09 615.62 11-FEB-14:30 28.85 24.07 0.00 0.00 01-FEB-00:10 28.85 24.07
March 0.617604E+09 511.21 02-MAR-14:30 25.00 17.17 0.00 0.00 01-MAR-00:10 25.00 17.17
April 0.634286E+09 426.87 15-APR-14:30 30.85 22.80 0.00 0.00 01-APR-00:10 30.85 22.80
May 0.691790E+09 397.26 22-MAY-17:12 31.33 23.80 0.00 0.00 01-MAY-00:10 31.33 23.80
June 0.719583E+09 401.00 29-JUN-17:12 30.40 24.80 0.00 0.00 01-JUN-00:10 30.40 24.80
July 0.786230E+09 445.75 29-JUL-17:12 34.03 24.14 0.00 0.00 01-JUL-00:10 34.03 24.14
August 0.786173E+09 449.98 20-AUG-13:50 32.20 25.08 0.00 0.00 01-AUG-00:10 32.20 25.08
September 0.859678E+09 586.12 30-SEP-13:40 30.93 24.69 0.00 0.00 01-SEP-00:10 30.93 24.69
October 0.924935E+09 652.89 25-OCT-12:40 30.00 22.13 0.00 0.00 01-OCT-00:10 30.00 22.13
November 0.795115E+09 688.80 07-NOV-13:40 28.13 20.93 0.00 0.00 01-NOV-00:10 28.13 20.93
December 0.691741E+09 693.14 03-DEC-14:00 24.40 18.35 0.00 0.00 01-DEC-00:10 24.40 18.35
                     
Annual Sum or Average 0.877086E+10         0.00        
Minimum of Months 0.600553E+09 397.26   24.40 17.17 0.00 0.00   24.40 17.17
Maximum of Months 0.924935E+09 693.14   34.03 25.08 0.00 0.00   34.03 25.08



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.517529E+09 944.71 06-JAN-19:02 24.40 21.75 96518336.14 56.69 30-JAN-22:10 15.00 13.89
February 0.556410E+09 964.08 17-FEB-19:02 24.32 20.61 87509754.20 56.69 27-FEB-22:19 21.33 15.04
March 0.685221E+09 983.12 13-MAR-18:02 27.93 22.26 97207713.34 56.69 28-MAR-22:00 23.30 19.98
April 0.812516E+09 1032.55 17-APR-18:02 30.03 18.67 94561054.39 56.69 12-APR-21:10 30.03 18.67
May 0.982455E+09 1024.00 20-MAY-08:62 27.88 22.09 98343446.43 56.69 15-MAY-21:30 27.88 22.09
June 0.103871E+10 1023.09 17-JUN-08:62 26.88 22.12 95419056.06 56.69 20-JUN-21:30 26.40 23.77
July 0.109759E+10 1022.22 02-JUL-08:62 27.98 23.54 98599148.04 56.69 24-JUL-21:00 25.60 23.64
August 0.102229E+10 1016.04 19-AUG-18:02 29.40 24.22 98465317.22 56.69 14-AUG-21:30 29.40 24.22
September 0.970283E+09 1015.76 01-SEP-18:02 29.90 23.26 95164296.73 56.69 13-SEP-21:19 26.50 23.17
October 0.893616E+09 1000.30 03-OCT-18:02 29.22 24.97 97939961.84 56.69 04-OCT-21:10 26.60 23.14
November 0.721747E+09 986.51 20-NOV-19:02 26.02 20.73 94241856.52 56.69 20-NOV-23:00 25.60 21.37
December 0.572674E+09 976.33 09-DEC-09:02 26.20 22.58 96683033.40 56.69 06-DEC-22:10 26.20 22.58
                     
Annual Sum or Average 0.987104E+10         0.115065E+10        
Minimum of Months 0.517529E+09 944.71   24.32 18.67 87509754.20 56.69   15.00 13.89
Maximum of Months 0.109759E+10 1032.55   30.03 24.97 98599148.04 56.69   30.03 24.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.141390E+10 2602.60 03-JAN-16:02 26.42 20.44 98467978.05 56.69 13-JAN-23:40 23.90 21.21
February 0.148624E+10 2665.01 24-FEB-16:02 25.00 13.11 89125700.97 56.69 22-FEB-23:10 25.00 13.11
March 0.181762E+10 2617.31 31-MAR-15:02 25.78 18.38 98907499.59 56.69 28-MAR-22:00 25.78 18.38
April 0.220291E+10 2647.32 10-APR-15:02 27.20 18.73 95848452.95 56.69 12-APR-00:40 25.00 22.84
May 0.252626E+10 2655.95 20-MAY-15:02 30.00 21.38 99142210.35 56.70 22-MAY-21:10 27.70 22.63
June 0.268988E+10 2656.09 01-JUN-15:02 30.00 23.17 96006618.29 56.70 14-JUN-21:10 28.30 23.17
July 0.292621E+10 2676.73 27-JUL-15:02 34.50 25.05 99125078.24 56.70 25-JUL-21:30 34.50 25.05
August 0.272072E+10 2674.89 20-AUG-15:02 31.93 25.29 99175872.55 56.70 31-AUG-21:19 27.73 24.61
September 0.275158E+10 2677.29 10-SEP-15:02 31.10 25.25 95923465.44 56.70 21-SEP-21:40 28.90 25.14
October 0.261779E+10 2665.00 20-OCT-15:02 27.20 21.57 99108917.96 56.70 25-OCT-21:10 26.60 21.10
November 0.199004E+10 2645.89 06-NOV-16:02 27.80 20.07 95735963.76 56.69 28-NOV-22:30 25.00 22.46
December 0.145593E+10 2599.90 08-DEC-16:02 26.93 23.20 98316487.70 56.69 09-DEC-00:00 24.40 22.88
                     
Annual Sum or Average 0.265991E+11         0.116488E+10        
Minimum of Months 0.141390E+10 2599.90   25.00 13.11 89125700.97 56.69   23.90 13.11
Maximum of Months 0.292621E+10 2677.29   34.50 25.29 99175872.55 56.70   34.50 25.14



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.101507E+10 2480.36 15-JAN-16:02 24.72 16.69 97768518.74 56.69 13-JAN-22:10 24.72 16.69
February 0.117295E+10 2649.72 24-FEB-16:02 25.00 13.11 88797378.07 56.69 23-FEB-00:40 25.00 13.11
March 0.157399E+10 2572.03 01-MAR-16:02 24.90 15.69 98699997.83 56.69 30-MAR-22:30 23.60 19.84
April 0.207652E+10 2689.81 15-APR-15:02 31.20 22.93 95830541.90 56.69 13-APR-23:40 31.20 22.93
May 0.252443E+10 2682.05 20-MAY-15:02 30.00 21.38 99144433.94 56.70 22-MAY-21:10 27.70 22.63
June 0.273102E+10 2675.70 01-JUN-15:02 30.00 23.17 96009679.54 56.70 02-JUN-21:19 28.90 24.83
July 0.295244E+10 2703.68 27-JUL-15:02 34.50 25.05 99127508.28 56.70 24-JUL-21:10 34.50 25.05
August 0.266693E+10 2667.22 19-AUG-15:02 31.70 24.44 99174322.09 56.70 22-AUG-21:10 27.80 24.20
September 0.257980E+10 2652.16 13-SEP-15:02 31.32 24.14 95915417.14 56.70 22-SEP-21:10 28.30 25.17
October 0.229135E+10 2606.33 24-OCT-15:02 29.32 21.23 99069133.39 56.69 18-OCT-22:30 29.32 21.23
November 0.163627E+10 2553.08 21-NOV-09:02 26.70 21.80 95519203.52 56.69 02-NOV-22:40 26.70 21.80
December 0.108360E+10 2512.72 09-DEC-09:02 26.20 22.58 97653219.28 56.69 08-DEC-22:00 26.20 22.58
                     
Annual Sum or Average 0.243044E+11         0.116271E+10        
Minimum of Months 0.101507E+10 2480.36   24.72 13.11 88797378.07 56.69   23.60 13.11
Maximum of Months 0.295244E+10 2703.68   34.50 25.05 99174322.09 56.70   34.50 25.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.472504E+10 2340.38 01-JAN-11:33 26.30 21.34 0.147506E+10 942.42 03-JAN-22:40 21.87 20.31
February 0.433582E+10 2321.40 11-FEB-11:33 27.60 23.74 0.134345E+10 932.71 17-FEB-23:10 23.90 20.81
March 0.489552E+10 2345.13 04-MAR-11:33 27.03 22.82 0.151168E+10 946.96 30-MAR-21:49 23.90 20.07
April 0.503305E+10 2479.50 16-APR-10:33 28.67 21.62 0.150799E+10 951.84 17-APR-21:30 23.05 17.57
May 0.539652E+10 2621.07 22-MAY-20:10 28.22 22.81 0.158503E+10 951.84 23-MAY-23:19 22.80 21.59
June 0.548146E+10 2947.48 29-JUN-20:10 28.90 25.09 0.155887E+10 951.84 05-JUN-23:19 28.90 25.09
July 0.580951E+10 2986.71 28-JUL-20:10 28.48 23.99 0.161009E+10 951.84 05-JUL-23:19 28.48 23.99
August 0.567029E+10 2989.48 21-AUG-20:10 28.30 24.66 0.160957E+10 951.84 23-AUG-23:19 25.93 23.26
September 0.558086E+10 3029.96 21-SEP-20:10 28.90 24.88 0.155783E+10 951.84 26-SEP-23:19 24.23 22.15
October 0.558504E+10 2836.17 25-OCT-20:10 26.70 21.87 0.160406E+10 951.84 19-OCT-23:19 26.70 21.87
November 0.502333E+10 2553.98 10-NOV-21:10 24.22 21.58 0.150598E+10 951.84 09-NOV-00:20 24.22 21.58
December 0.482009E+10 2481.96 09-DEC-12:30 27.20 22.50 0.149146E+10 951.83 08-DEC-22:19 27.20 22.50
                     
Annual Sum or Average 0.623565E+11         0.183611E+11        
Minimum of Months 0.433582E+10 2321.40   24.22 21.34 0.134345E+10 932.71   21.87 17.57
Maximum of Months 0.580951E+10 3029.96   28.90 25.09 0.161009E+10 951.84   28.90 25.09



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.119399E+10 2997.75 23-JAN-16:02 26.70 20.30 98008745.83 56.69 13-JAN-22:10 26.70 20.30
February 0.137950E+10 3102.00 24-FEB-16:02 25.00 13.11 88775847.97 56.70 06-FEB-05:49 25.00 13.11
March 0.175840E+10 3040.97 25-MAR-15:02 26.52 20.85 98522138.34 56.70 13-MAR-22:19 26.52 20.85
April 0.219161E+10 3072.91 01-APR-15:02 27.88 24.57 95607057.42 56.70 13-APR-00:40 25.60 23.64
May 0.252931E+10 3065.75 16-MAY-18:02 28.12 22.30 99010830.23 56.70 20-MAY-01:10 26.10 22.63
June 0.257972E+10 3067.84 25-JUN-15:02 29.82 24.57 95892859.29 56.70 09-JUN-21:10 29.82 24.57
July 0.289775E+10 3084.27 28-JUL-18:02 32.15 24.42 99040706.94 56.70 28-JUL-21:10 29.32 24.20
August 0.273994E+10 3073.81 02-AUG-15:02 31.10 25.63 99082352.77 56.70 25-AUG-00:00 26.70 24.27
September 0.266138E+10 3110.24 17-SEP-15:02 31.10 24.65 95807775.09 56.70 08-SEP-21:10 31.10 24.65
October 0.253150E+10 3042.70 28-OCT-15:02 28.40 23.19 98961069.07 56.70 08-OCT-00:40 28.40 23.19
November 0.186797E+10 3067.46 07-NOV-16:02 28.22 22.20 95483812.88 56.70 20-NOV-23:10 25.60 21.12
December 0.139944E+10 2962.80 25-DEC-16:02 25.92 23.57 98047460.69 56.69 08-DEC-23:10 25.92 23.57
                     
Annual Sum or Average 0.257305E+11         0.116224E+10        
Minimum of Months 0.119399E+10 2962.80   25.00 13.11 88775847.97 56.69   25.00 13.11
Maximum of Months 0.289775E+10 3110.24   32.15 25.63 99082352.77 56.70   31.10 24.65



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.797025E+09 2957.54 03-JAN-16:02 26.42 20.44 97181574.84 56.69 14-JAN-01:30 23.90 21.21
February 0.106974E+10 3080.40 24-FEB-16:02 25.00 13.11 88322143.03 56.69 22-FEB-23:19 25.00 13.11
March 0.151907E+10 3075.93 28-MAR-15:02 26.60 20.66 98228149.64 56.70 27-MAR-21:00 26.60 20.66
April 0.206500E+10 3089.71 07-APR-15:02 27.12 20.72 95566506.80 56.70 14-APR-23:49 25.00 22.59
May 0.252821E+10 3098.07 29-MAY-18:02 30.82 24.67 99021193.71 56.70 18-MAY-00:00 30.82 24.67
June 0.262210E+10 3100.44 09-JUN-18:02 30.00 25.09 95914362.09 56.70 09-JUN-21:10 29.32 24.94
July 0.292523E+10 3107.24 28-JUL-18:02 32.15 24.42 99054936.71 56.70 08-JUL-01:00 32.15 24.42
August 0.268532E+10 3110.06 02-AUG-15:02 31.10 25.63 99079862.67 56.70 27-AUG-01:10 26.70 24.97
September 0.248599E+10 3099.19 26-SEP-15:02 31.02 23.54 95777997.22 56.70 24-SEP-01:49 31.02 23.54
October 0.219925E+10 3103.66 05-OCT-15:02 30.92 23.76 98867522.15 56.70 20-OCT-21:49 25.18 20.89
November 0.151054E+10 3041.90 08-NOV-16:02 28.12 21.75 95165226.94 56.70 03-NOV-21:30 28.12 21.75
December 0.102052E+10 3033.43 01-DEC-16:02 26.42 19.90 97392571.11 56.69 19-DEC-05:49 17.30 16.14
                     
Annual Sum or Average 0.234280E+11         0.115957E+10        
Minimum of Months 0.797025E+09 2957.54   25.00 13.11 88322143.03 56.69   17.30 13.11
Maximum of Months 0.292523E+10 3110.06   32.15 25.63 99079862.67 56.70   32.15 24.97



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.121859E+10 1444.02 03-JAN-16:02 26.42 20.44 98612486.31 56.70 13-JAN-22:00 23.90 21.21
February 0.113348E+10 1475.66 24-FEB-16:02 25.00 13.11 89137746.32 56.70 22-FEB-22:30 25.00 13.11
March 0.119016E+10 1438.80 04-MAR-16:02 27.52 22.31 98673033.58 56.69 12-MAR-23:10 21.70 19.15
April 0.125176E+10 1455.94 14-APR-15:02 30.40 24.46 95572539.81 56.70 14-APR-21:30 25.30 22.39
May 0.137582E+10 1423.48 01-MAY-15:02 29.90 20.98 98941872.36 56.70 09-MAY-21:10 26.02 22.55
June 0.143908E+10 1433.52 01-JUN-15:02 30.00 23.17 95834564.24 56.70 16-JUN-21:40 28.30 22.29
July 0.157456E+10 1458.54 27-JUL-15:02 34.50 25.05 98989835.26 56.70 18-JUL-21:30 34.50 25.05
August 0.155340E+10 1459.22 21-AUG-15:02 30.37 25.25 99044078.41 56.70 14-AUG-21:49 30.37 25.25
September 0.166646E+10 1449.54 21-SEP-15:02 31.10 25.31 95863008.50 56.70 29-SEP-22:49 28.30 23.57
October 0.175019E+10 1478.01 24-OCT-15:02 29.32 21.23 99136389.11 56.70 16-OCT-22:10 29.32 21.23
November 0.148464E+10 1475.35 07-NOV-16:02 28.22 22.20 95778802.72 56.70 08-NOV-23:30 25.00 21.33
December 0.127902E+10 1448.11 08-DEC-16:02 26.93 23.20 98576992.43 56.69 04-DEC-23:10 26.93 23.20
                     
Annual Sum or Average 0.169172E+11         0.116416E+10        
Minimum of Months 0.113348E+10 1423.48   25.00 13.11 89137746.32 56.69   21.70 13.11
Maximum of Months 0.175019E+10 1478.01   34.50 25.31 99136389.11 56.70   34.50 25.25



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.386269E+11 21488.81 13-JAN-23:00 23.90 21.21 0.191468E+11 11347.80 02-JAN-00:20 23.90 21.21
February 0.359767E+11 21788.66 17-FEB-23:00 23.90 20.81 0.173446E+11 11347.81 23-FEB-00:20 17.77 15.47
March 0.409179E+11 22110.53 27-MAR-22:00 24.40 21.69 0.192937E+11 11347.79 12-MAR-23:19 24.40 21.69
April 0.417968E+11 22739.85 14-APR-21:10 25.50 22.67 0.186771E+11 11347.82 02-APR-23:19 25.50 22.67
May 0.451846E+11 23424.39 22-MAY-21:20 27.60 22.54 0.193293E+11 11355.41 31-MAY-22:00 26.90 24.88
June 0.450266E+11 23731.22 28-JUN-21:20 28.90 24.83 0.187483E+11 11367.22 29-JUN-21:19 28.90 24.82
July 0.469237E+11 23745.11 27-JUL-21:20 29.03 25.15 0.193016E+11 11361.00 27-JUL-21:19 29.03 25.15
August 0.459846E+11 23602.90 02-AUG-21:20 29.23 24.60 0.193735E+11 11363.16 31-AUG-22:00 27.30 24.40
September 0.442770E+11 23655.00 08-SEP-21:10 29.90 24.64 0.186931E+11 11361.72 20-SEP-22:00 27.80 25.31
October 0.442035E+11 22961.42 03-OCT-21:10 27.80 25.31 0.192826E+11 11347.80 15-OCT-23:19 22.60 19.33
November 0.405482E+11 22622.70 03-NOV-22:00 26.70 24.27 0.186033E+11 11347.95 27-NOV-00:20 11.50 9.02
December 0.394392E+11 21872.39 08-DEC-23:00 24.40 22.88 0.191618E+11 11348.05 15-DEC-04:19 8.13 5.63
                     
Annual Sum or Average 0.508906E+12         0.226956E+12        
Minimum of Months 0.359767E+11 21488.81   23.90 20.81 0.173446E+11 11347.79   8.13 5.63
Maximum of Months 0.469237E+11 23745.11   29.90 25.31 0.193735E+11 11367.22   29.03 25.31



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.416870E+11 22795.01 13-JAN-22:10 24.32 21.03 0.192164E+11 11347.81 02-JAN-00:20 24.32 21.03
February 0.387195E+11 23044.12 17-FEB-22:10 23.90 20.81 0.173949E+11 11347.81 23-FEB-00:20 17.77 15.47
March 0.439293E+11 23344.45 27-MAR-21:10 24.90 21.81 0.193394E+11 11347.80 12-MAR-23:19 24.90 21.81
April 0.445414E+11 23912.32 14-APR-21:10 25.50 22.67 0.186976E+11 11347.83 02-APR-23:19 25.50 22.67
May 0.479431E+11 24612.89 22-MAY-21:20 27.60 22.54 0.193408E+11 11359.38 22-MAY-21:19 27.60 22.54
June 0.476368E+11 24890.30 28-JUN-21:20 28.90 24.83 0.187554E+11 11371.44 15-JUN-21:19 28.90 24.83
July 0.496202E+11 24912.27 27-JUL-21:20 29.03 25.15 0.193066E+11 11365.73 27-JUL-21:19 29.03 25.15
August 0.486692E+11 24764.22 02-AUG-21:20 29.23 24.60 0.193831E+11 11363.88 31-AUG-22:00 27.30 24.40
September 0.468497E+11 24835.39 08-SEP-21:10 29.90 24.64 0.187018E+11 11359.86 20-SEP-22:00 27.80 25.31
October 0.468375E+11 24130.34 03-OCT-21:10 27.80 25.31 0.192978E+11 11347.88 03-OCT-22:30 27.50 25.45
November 0.432477E+11 23770.19 03-NOV-22:00 26.70 24.27 0.186332E+11 11347.96 27-NOV-00:20 11.50 9.02
December 0.424315E+11 23037.49 08-DEC-23:00 24.40 22.88 0.192235E+11 11348.06 15-DEC-04:19 8.13 5.63
                     
Annual Sum or Average 0.542113E+12         0.227290E+12        
Minimum of Months 0.387195E+11 22795.01   23.90 20.81 0.173949E+11 11347.80   8.13 5.63
Maximum of Months 0.496202E+11 24912.27   29.90 25.31 0.193831E+11 11371.44   29.03 25.45



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.540912E+11 29389.92 01-JAN-11:50 26.20 21.28 0.188375E+11 11319.65 14-JAN-18:19 18.87 16.84
February 0.494797E+11 29619.84 11-FEB-11:33 27.60 23.74 0.170189E+11 11319.67 04-FEB-18:19 27.60 23.74
March 0.554532E+11 29851.45 27-MAR-10:33 26.13 21.70 0.188534E+11 11319.66 25-MAR-17:19 26.13 21.70
April 0.551178E+11 30569.37 15-APR-10:37 29.27 22.89 0.182490E+11 11319.68 01-APR-17:19 29.27 22.89
May 0.579528E+11 30545.75 31-MAY-10:33 32.23 24.19 0.188631E+11 11319.68 20-MAY-17:19 32.23 24.19
June 0.568699E+11 30758.29 11-JUN-10:50 31.02 23.55 0.182612E+11 11319.67 10-JUN-17:19 31.02 23.55
July 0.591383E+11 30940.07 23-JUL-10:50 32.75 24.78 0.188634E+11 11319.67 01-JUL-17:19 32.75 24.78
August 0.584096E+11 30722.99 19-AUG-10:40 31.50 24.70 0.188695E+11 11319.71 19-AUG-17:19 30.53 24.22
September 0.566832E+11 30665.49 10-SEP-10:40 30.40 24.57 0.182561E+11 11319.65 16-SEP-17:19 30.20 23.69
October 0.576012E+11 30617.63 07-OCT-10:37 31.13 24.14 0.188601E+11 11319.66 21-OCT-17:19 26.67 19.93
November 0.541662E+11 29578.37 03-NOV-10:33 28.13 24.02 0.182415E+11 11319.57 04-NOV-17:19 27.03 24.72
December 0.543320E+11 29583.86 09-DEC-11:50 27.20 22.50 0.188401E+11 11319.63 16-DEC-18:19 19.40 15.49
                     
Annual Sum or Average 0.669295E+12         0.222014E+12        
Minimum of Months 0.494797E+11 29389.92   26.13 21.28 0.170189E+11 11319.57   18.87 15.49
Maximum of Months 0.591383E+11 30940.07   32.75 24.78 0.188695E+11 11319.71   32.75 24.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.961355E+10 5074.42 01-JAN-11:33 26.30 21.34 0.149817E+10 982.62 03-JAN-22:30 21.95 20.39
February 0.898674E+10 5146.66 11-FEB-11:33 27.60 23.74 0.138335E+10 982.53 17-FEB-22:40 23.90 20.81
March 0.102016E+11 5071.64 04-MAR-11:33 27.03 22.82 0.156517E+10 1001.35 30-MAR-21:40 23.90 20.02
April 0.107857E+11 5790.30 14-APR-15:13 30.20 24.40 0.158115E+10 1007.40 17-APR-21:30 23.05 17.57
May 0.118451E+11 5947.22 18-MAY-15:03 30.92 22.77 0.167833E+10 1007.39 23-MAY-23:19 22.80 21.59
June 0.122603E+11 6471.57 28-JUN-15:40 30.20 24.40 0.165007E+10 1007.39 22-JUN-23:19 30.20 24.40
July 0.132323E+11 7279.13 28-JUL-15:40 35.00 24.98 0.170005E+10 1007.39 12-JUL-21:19 35.00 24.98
August 0.125827E+11 6576.83 31-AUG-15:03 32.12 24.95 0.169969E+10 1007.39 14-AUG-23:19 32.12 24.95
September 0.123884E+11 7206.43 09-SEP-13:00 31.70 25.11 0.164210E+10 1007.39 12-SEP-23:19 25.00 23.33
October 0.120125E+11 6852.91 06-OCT-12:40 30.20 23.69 0.168050E+10 1007.39 19-OCT-21:19 24.23 19.31
November 0.105196E+11 6020.01 10-NOV-13:40 28.33 24.04 0.155953E+10 1007.39 03-NOV-23:19 28.33 24.04
December 0.990060E+10 5528.80 09-DEC-12:40 27.20 22.50 0.152382E+10 1005.27 08-DEC-22:40 27.20 22.50
                     
Annual Sum or Average 0.134329E+12         0.191619E+11        
Minimum of Months 0.898674E+10 5071.64   26.30 21.34 0.138335E+10 982.53   21.95 17.57
Maximum of Months 0.132323E+11 7279.13   35.00 25.11 0.170005E+10 1007.40   35.00 24.98



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:05 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:05 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:05 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:05 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:05 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:05 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:05 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:05 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:05 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:05 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:05 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:05 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:05 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:05 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:05 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:05 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:05 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:05 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:05 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:05 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:05 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:05 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:05 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:05 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1820273.68 632.91 09-JAN-09:03 15.28
February 6938206.67 599.65 16-FEB-09:05 24.08
March 1625370.04 1089.52 16-MAR-08:62 8.68
April 891475.12 659.65 30-APR-08:05 23.12
May 519746.25 621.64 02-MAY-08:05 26.28
June 243860.43 550.69 19-JUN-08:05 26.60
July 19718.57 173.68 03-JUL-08:05 26.88
August 281043.64 512.89 29-AUG-08:05 27.38
September 302804.19 475.15 26-SEP-08:05 24.78
October 440983.76 705.28 02-OCT-08:05 27.57
November 737658.26 626.91 30-NOV-09:05 26.20
December 1807559.95 641.55 23-DEC-09:05 23.98
         
Annual Sum or Average 15628700.55      
Minimum of Months 19718.57 173.68   8.68
Maximum of Months 6938206.67 1089.52   27.57



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 5745464.16 1333.27 25-JAN-09:02 11.57
February 12824400.91 1332.86 04-FEB-09:02 10.47
March 3885651.89 1326.61 16-MAR-08:62 8.68
April 1038966.21 737.83 09-APR-08:05 23.90
May 532670.19 632.74 08-MAY-08:05 25.18
June 147368.74 509.03 19-JUN-08:05 26.60
July 12575.35 125.75 03-JUL-08:05 26.88
August 344610.18 562.19 13-AUG-08:05 27.07
September 466547.30 476.53 05-SEP-08:05 24.50
October 1201751.51 680.46 14-OCT-08:05 26.38
November 1570905.49 661.09 19-NOV-09:05 25.18
December 8654850.24 1260.98 27-DEC-09:02 11.47
         
Annual Sum or Average 36425762.16      
Minimum of Months 12575.35 125.75   8.68
Maximum of Months 12824400.91 1333.27   27.07



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:05 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:05 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:05 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 502099.13 342.63 27-JAN-09:02 16.47
February 575262.55 394.42 03-FEB-16:03 16.42
March 459277.95 357.30 15-MAR-15:03 17.30
April 278004.61 325.66 21-APR-08:05 24.60
May 71536.94 144.39 01-MAY-08:05 24.78
June 51919.68 96.16 12-JUN-08:07 28.48
July 91287.23 91.73 21-JUL-08:07 28.48
August 57828.36 70.91 18-AUG-08:07 29.60
September 11218.50 99.56 25-SEP-18:07 24.40
October 334480.40 290.71 18-OCT-08:05 26.20
November 368559.35 309.42 29-NOV-09:05 25.68
December 452684.78 292.88 06-DEC-09:05 25.18
         
Annual Sum or Average 3254159.50      
Minimum of Months 11218.50 70.91   16.42
Maximum of Months 575262.55 394.42   29.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1297651.65 600.53 25-JAN-16:05 17.80
February 6552014.57 698.91 03-FEB-16:04 16.42
March 1245941.48 554.12 19-MAR-15:05 16.78
April 64254.37 642.54 30-APR-08:05 23.12
May 17281.57 159.02 25-MAY-08:05 25.40
June 0.00 0.00 01-JUN-00:05 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 51064.99 510.65 28-AUG-08:05 23.72
September 0.00 0.00 01-SEP-00:05 27.05
October 24657.18 246.57 18-OCT-08:05 26.20
November 283828.30 541.22 12-NOV-09:05 14.68
December 2300228.68 552.40 20-DEC-19:03 12.62
         
Annual Sum or Average 11836922.78      
Minimum of Months 0.00 0.00   12.62
Maximum of Months 6552014.57 698.91   27.05



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 6796759.30 640.89 25-JAN-16:03 17.80
February 11666893.64 838.03 03-FEB-16:03 16.42
March 2869614.78 624.84 15-MAR-15:04 17.30
April 68146.42 681.46 30-APR-08:05 23.12
May 27039.78 234.77 25-MAY-08:05 25.40
June 0.00 0.00 01-JUN-00:05 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 54005.25 540.05 28-AUG-08:05 23.72
September 0.00 0.00 01-SEP-00:05 27.05
October 55394.05 530.70 18-OCT-08:05 26.20
November 800326.71 486.06 29-NOV-09:05 25.68
December 10658246.02 675.52 27-DEC-16:03 20.00
         
Annual Sum or Average 32996425.95      
Minimum of Months 0.00 0.00   16.42
Maximum of Months 11666893.64 838.03   27.05



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:05 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:05 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:05 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 13526623.64 1233.74 25-JAN-09:02 11.57
February 20219534.35 1573.16 04-FEB-09:02 10.47
March 11068274.76 1582.35 16-MAR-08:62 8.68
April 1003486.70 599.49 29-APR-08:05 23.40
May 947081.61 630.11 24-MAY-08:05 26.10
June 644779.25 655.70 18-JUN-08:05 25.40
July 212197.02 578.78 03-JUL-08:05 26.88
August 685960.15 642.30 03-AUG-08:05 23.98
September 617356.25 575.60 07-SEP-08:05 25.18
October 1125693.60 688.56 15-OCT-08:05 24.60
November 4944929.91 637.77 28-NOV-19:05 25.00
December 18331489.26 1233.59 15-DEC-09:02 10.97
         
Annual Sum or Average 73327406.50      
Minimum of Months 212197.02 575.60   8.68
Maximum of Months 20219534.35 1582.35   26.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 39430684.99 1606.93 25-JAN-09:02 11.57
February 33268369.56 1606.15 04-FEB-09:02 10.47
March 18671785.44 1601.05 16-MAR-08:62 8.68
April 1043987.46 657.62 08-APR-08:05 25.10
May 917809.67 616.81 24-MAY-08:05 26.10
June 581013.56 684.00 19-JUN-08:05 26.60
July 126785.31 607.09 03-JUL-08:05 26.88
August 721349.13 637.54 13-AUG-08:05 27.07
September 706032.25 556.28 14-SEP-08:05 26.88
October 1379823.22 646.20 09-OCT-08:05 27.38
November 9660483.44 1559.58 13-NOV-09:02 16.65
December 43359986.09 1600.16 27-DEC-09:02 11.47
         
Annual Sum or Average 0.149868E+09      
Minimum of Months 126785.31 556.28   8.68
Maximum of Months 43359986.09 1606.93   27.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 79825.60 186.57 31-JAN-09:05 13.90
February 1854244.57 260.78 04-FEB-09:04 10.47
March 565898.56 630.19 16-MAR-08:62 8.68
April 276914.45 347.82 27-APR-08:05 23.40
May 63323.28 274.08 01-MAY-08:05 24.78
June 0.00 0.00 01-JUN-00:05 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 49800.30 291.96 28-AUG-08:05 23.72
September 1099.54 11.00 06-SEP-08:05 25.47
October 0.00 0.00 01-OCT-00:10 27.93
November 48606.21 156.78 25-NOV-09:06 20.78
December 121253.83 118.16 27-DEC-09:05 11.47
         
Annual Sum or Average 3060966.35      
Minimum of Months 0.00 0.00   8.68
Maximum of Months 1854244.57 630.19   27.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:05 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:05 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:05 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:05 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:05 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:05 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:05 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:05 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:05 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:05 22.05
June 0.00 0.00 01-JUN-00:05 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:05 28.60
September 0.00 0.00 01-SEP-00:05 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:05 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.147273E+11 14185.34 02-JAN-20:10 0.127587E+11 10113.80 02-JAN-20:10
February 0.132974E+11 14185.34 01-FEB-20:10 0.115208E+11 10113.80 01-FEB-20:10
March 0.147727E+11 14185.34 01-MAR-20:10 0.127855E+11 10113.80 01-MAR-20:10
April 0.142280E+11 14185.34 03-APR-19:10 0.123314E+11 10113.80 03-APR-19:10
May 0.147528E+11 14185.34 01-MAY-19:10 0.127741E+11 10113.80 01-MAY-19:10
June 0.142932E+11 14185.34 01-JUN-19:10 0.123716E+11 10113.80 01-JUN-19:10
July 0.146876E+11 14185.34 03-JUL-19:10 0.127338E+11 10113.80 03-JUL-19:10
August 0.147784E+11 14185.34 01-AUG-19:10 0.127894E+11 10113.80 01-AUG-19:10
September 0.142337E+11 14185.34 01-SEP-19:10 0.123352E+11 10113.80 01-SEP-19:10
October 0.147216E+11 14185.34 02-OCT-19:10 0.127549E+11 10113.80 02-OCT-19:10
November 0.142819E+11 14185.34 01-NOV-19:10 0.123659E+11 10113.80 01-NOV-19:10
December 0.146876E+11 14185.34 01-DEC-20:10 0.127338E+11 10113.80 01-DEC-20:10
             
Annual Sum or Average 0.173462E+12     0.150255E+12    
Minimum of Months 0.132974E+11 14185.34   0.115208E+11 10113.80  
Maximum of Months 0.147784E+11 14185.34   0.127894E+11 10113.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.731324E+09 704.41 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.660319E+09 704.41 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.733578E+09 704.41 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.706528E+09 704.41 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.732592E+09 704.41 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.709769E+09 704.41 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.729351E+09 704.41 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.733860E+09 704.41 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.706810E+09 704.41 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.731042E+09 704.41 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.709205E+09 704.41 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.729351E+09 704.41 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.861373E+10     0.101856E+11    
Minimum of Months 0.660319E+09 704.41   0.780982E+09 685.60  
Maximum of Months 0.733860E+09 704.41   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.846876E+09 815.72 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.764651E+09 815.72 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.849486E+09 815.72 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.818162E+09 815.72 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.848344E+09 815.72 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.821915E+09 815.72 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.844592E+09 815.72 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.849812E+09 815.72 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.818489E+09 815.72 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.846549E+09 815.72 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.821262E+09 815.72 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.844592E+09 815.72 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.997473E+10     0.117950E+11    
Minimum of Months 0.764651E+09 815.72   0.904380E+09 793.93  
Maximum of Months 0.849812E+09 815.72   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.141236E+10 1360.40 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.127524E+10 1360.40 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.141672E+10 1360.40 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.136448E+10 1360.40 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.141481E+10 1360.40 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.137074E+10 1360.40 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.140855E+10 1360.40 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.141726E+10 1360.40 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.136502E+10 1360.40 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.141182E+10 1360.40 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.136965E+10 1360.40 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.140855E+10 1360.40 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.166352E+11     0.124712E+11    
Minimum of Months 0.127524E+10 1360.40   0.956227E+09 839.45  
Maximum of Months 0.141726E+10 1360.40   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.236418E+09 227.72 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.213464E+09 227.72 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.237147E+09 227.72 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.228402E+09 227.72 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.236828E+09 227.72 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.229450E+09 227.72 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.235780E+09 227.72 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.237238E+09 227.72 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.228493E+09 227.72 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.236327E+09 227.72 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.229268E+09 227.72 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.235780E+09 227.72 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.278459E+10     0.359760E+10    
Minimum of Months 0.213464E+09 227.72   0.275845E+09 242.16  
Maximum of Months 0.237238E+09 227.72   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.370859E+09 357.21 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.334852E+09 357.21 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.372002E+09 357.21 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.358285E+09 357.21 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.371502E+09 357.21 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.359929E+09 357.21 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.369859E+09 357.21 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.372145E+09 357.21 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.358428E+09 357.21 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.370717E+09 357.21 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.359643E+09 357.21 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.369859E+09 357.21 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.436808E+10     0.679355E+11    
Minimum of Months 0.334852E+09 357.21   0.520895E+10 4572.80  
Maximum of Months 0.372145E+09 357.21   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.158558E+10 1761.91 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.141366E+10 1761.91 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.153412E+10 1761.91 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.145996E+10 1761.91 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.149054E+10 1761.91 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.144519E+10 1761.91 01-JUN-19:10 0.118076E+10 965.27 01-JUN-19:10
July 0.146137E+10 1761.91 03-JUL-19:10 0.121533E+10 965.27 03-JUL-19:10
August 0.150479E+10 1761.91 01-AUG-19:10 0.122063E+10 965.27 01-AUG-19:10
September 0.147887E+10 1761.91 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.155970E+10 1761.91 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.152070E+10 1761.91 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.158530E+10 1761.91 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.180398E+11     0.143405E+11    
Minimum of Months 0.141366E+10 1761.91   0.109956E+10 965.27  
Maximum of Months 0.158558E+10 1761.91   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104070E+11 10265.18 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.937927E+10 10265.18 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.103889E+11 10265.18 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.998862E+10 10265.18 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.103373E+11 10265.18 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.100216E+11 10265.18 01-JUN-19:10 0.122682E+11 10029.21 01-JUN-19:10
July 0.102714E+11 10265.18 03-JUL-19:10 0.126273E+11 10029.21 03-JUL-19:10
August 0.103638E+11 10265.18 01-AUG-19:10 0.126824E+11 10029.21 01-AUG-19:10
September 0.100123E+11 10265.18 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.103803E+11 10265.18 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.100767E+11 10265.18 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.103854E+11 10265.18 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.122013E+12     0.148998E+12    
Minimum of Months 0.937927E+10 10265.18   0.114244E+11 10029.21  
Maximum of Months 0.104070E+11 10265.18   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85091918.49 76.99 01-JAN-19:10 0.255708E+09 232.19 01-JAN-08:09
February 76846309.13 76.99 01-FEB-20:10 0.230956E+09 232.19 01-FEB-07:10
March 84415649.14 76.99 01-MAR-20:10 0.255355E+09 232.19 01-MAR-07:10
April 82445007.08 76.99 01-APR-18:10 0.247516E+09 232.19 01-APR-07:10
May 84753783.81 76.99 01-MAY-19:10 0.255532E+09 232.19 01-MAY-06:10
June 81790910.76 76.99 01-JUN-19:10 0.247163E+09 232.19 01-JUN-06:10
July 85418966.65 76.99 01-JUL-18:10 0.255885E+09 232.19 01-JUL-07:10
August 84415649.14 76.99 01-AUG-19:10 0.255355E+09 232.19 01-AUG-06:10
September 82467180.11 76.99 01-SEP-19:10 0.247516E+09 232.19 01-SEP-06:10
October 85080831.98 76.99 01-OCT-18:10 0.255708E+09 232.19 01-OCT-07:10
November 82117958.92 76.99 01-NOV-19:10 0.247340E+09 232.19 01-NOV-06:10
December 85430053.17 76.99 01-DEC-20:10 0.255885E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.100027E+10     0.300992E+10    
Minimum of Months 76846309.13 76.99   0.230956E+09 232.19  
Maximum of Months 85430053.17 76.99   0.255885E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85115186.72 77.01 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 76867322.62 77.01 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 84438732.44 77.01 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 82467551.52 77.01 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 84776959.58 77.01 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 81813276.33 77.01 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 85442324.32 77.01 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 84438732.44 77.01 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 82489730.61 77.01 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 85104097.18 77.01 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 82140413.93 77.01 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 85453413.86 77.01 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.100055E+10     0.301074E+10    
Minimum of Months 76867322.62 77.01   0.231020E+09 232.26  
Maximum of Months 85453413.86 77.01   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.232638E+10 2240.78 02-JAN-20:10 0.00 0.00
February 0.210051E+10 2240.78 01-FEB-20:10 0.00 0.00
March 0.233355E+10 2240.78 01-MAR-20:10 0.00 0.00
April 0.224750E+10 2240.78 03-APR-19:10 0.00 0.00
May 0.233041E+10 2240.78 01-MAY-19:10 0.00 0.00
June 0.225781E+10 2240.78 01-JUN-19:10 0.00 0.00
July 0.232011E+10 2240.78 03-JUL-19:10 0.00 0.00
August 0.233445E+10 2240.78 01-AUG-19:10 0.00 0.00
September 0.224840E+10 2240.78 01-SEP-19:10 0.00 0.00
October 0.232548E+10 2240.78 02-OCT-19:10 0.00 0.00
November 0.225602E+10 2240.78 01-NOV-19:10 0.00 0.00
December 0.232011E+10 2240.78 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.274007E+11     0.00 0.00
Minimum of Months 0.210051E+10 2240.78   0.00 0.00
Maximum of Months 0.233445E+10 2240.78   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85115186.72 77.01 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 76867322.62 77.01 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 84438732.44 77.01 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 82467551.52 77.01 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 84776959.58 77.01 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 81813276.33 77.01 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 85442324.32 77.01 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 84438732.44 77.01 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 82489730.61 77.01 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 85104097.18 77.01 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 82140413.93 77.01 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 85453413.86 77.01 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.100055E+10     0.301074E+10    
Minimum of Months 76867322.62 77.01   0.231020E+09 232.26  
Maximum of Months 85453413.86 77.01   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.301722E+10 3094.06 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.270132E+10 3094.06 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.296389E+10 3094.06 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.282776E+10 3094.06 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.290316E+10 3094.06 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.280132E+10 3094.06 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.286862E+10 3094.06 03-JUL-19:19 0.149358E+11 6747.90 01-JUL-06:10
August 0.292425E+10 3094.06 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.285020E+10 3094.06 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.298382E+10 3094.06 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.290521E+10 3094.06 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.300552E+10 3094.06 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.347523E+11     0.175857E+12    
Minimum of Months 0.270132E+10 3094.06   0.134904E+11 6747.90  
Maximum of Months 0.301722E+10 3094.06   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.301722E+10 3094.06 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.270132E+10 3094.06 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.296389E+10 3094.06 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.282776E+10 3094.06 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.290316E+10 3094.06 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.280132E+10 3094.06 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.286862E+10 3094.06 03-JUL-19:19 0.149358E+11 6747.90 01-JUL-06:10
August 0.292425E+10 3094.06 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.285020E+10 3094.06 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.298382E+10 3094.06 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.290521E+10 3094.06 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.300552E+10 3094.06 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.347523E+11     0.175857E+12    
Minimum of Months 0.270132E+10 3094.06   0.134904E+11 6747.90  
Maximum of Months 0.301722E+10 3094.06   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.113146E+10 1089.83 02-JAN-20:10 0.368383E+11 16487.34 01-JAN-07:10
February 0.102161E+10 1089.83 01-FEB-20:10 0.332733E+11 16487.34 01-FEB-07:10
March 0.113495E+10 1089.83 01-MAR-20:10 0.368383E+11 16487.34 01-MAR-07:10
April 0.109310E+10 1089.83 03-APR-19:10 0.356500E+11 16487.34 01-APR-06:10
May 0.113342E+10 1089.83 01-MAY-19:10 0.368383E+11 16487.34 01-MAY-06:10
June 0.109811E+10 1089.83 01-JUN-19:10 0.356500E+11 16487.34 01-JUN-06:10
July 0.112841E+10 1089.83 03-JUL-19:10 0.368383E+11 16487.34 01-JUL-06:10
August 0.113539E+10 1089.83 01-AUG-19:10 0.368383E+11 16487.34 01-AUG-06:10
September 0.109354E+10 1089.83 01-SEP-19:10 0.356500E+11 16487.34 01-SEP-06:10
October 0.113103E+10 1089.83 02-OCT-19:10 0.368383E+11 16487.34 01-OCT-06:10
November 0.109724E+10 1089.83 01-NOV-19:10 0.356500E+11 16487.34 01-NOV-06:10
December 0.112841E+10 1089.83 01-DEC-20:10 0.368383E+11 16487.34 01-DEC-07:10
             
Annual Sum or Average 0.133267E+11     0.433742E+12    
Minimum of Months 0.102161E+10 1089.83   0.332733E+11 16487.34  
Maximum of Months 0.113539E+10 1089.83   0.368383E+11 16487.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.246211E+10 2371.52 02-JAN-20:10 0.00 0.00
February 0.222306E+10 2371.52 01-FEB-20:10 0.00 0.00
March 0.246970E+10 2371.52 01-MAR-20:10 0.00 0.00
April 0.237864E+10 2371.52 03-APR-19:10 0.00 0.00
May 0.246638E+10 2371.52 01-MAY-19:10 0.00 0.00
June 0.238954E+10 2371.52 01-JUN-19:10 0.00 0.00
July 0.245547E+10 2371.52 03-JUL-19:10 0.00 0.00
August 0.247065E+10 2371.52 01-AUG-19:10 0.00 0.00
September 0.237958E+10 2371.52 01-SEP-19:10 0.00 0.00
October 0.246116E+10 2371.52 02-OCT-19:10 0.00 0.00
November 0.238765E+10 2371.52 01-NOV-19:10 0.00 0.00
December 0.245547E+10 2371.52 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.289994E+11     0.00 0.00
Minimum of Months 0.222306E+10 2371.52   0.00 0.00
Maximum of Months 0.247065E+10 2371.52   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.147273E+11 0.127587E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.132974E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.147727E+11 0.127855E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.142280E+11 0.123314E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.147528E+11 0.127741E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.142932E+11 0.123716E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.146876E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.147784E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.142337E+11 0.123352E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.147216E+11 0.127549E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.142819E+11 0.123659E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.146876E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.173462E+12 0.150255E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.132974E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.147784E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.731324E+09 0.864900E+09 0.00 0.00 0.00 0.00 8091695.06 0.123491E+09
February 0.179968E+10 0.660319E+09 0.780982E+09 0.00 0.00 0.00 0.00 12229336.61 79082235.87
March 0.199990E+10 0.733578E+09 0.866718E+09 0.00 0.00 0.00 0.00 15757538.87 67984101.81
April 0.192973E+10 0.706528E+09 0.835931E+09 0.00 0.00 0.00 0.00 40033231.35 18221777.64
May 0.199475E+10 0.732592E+09 0.865939E+09 0.00 0.00 0.00 0.00 89524894.41 1820171.30
June 0.193394E+10 0.709769E+09 0.838659E+09 0.00 0.00 0.00 0.00 0.118506E+09 42965.28
July 0.199054E+10 0.729351E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.133570E+09 488069.19
August 0.199896E+10 0.733860E+09 0.866978E+09 0.00 0.00 0.00 0.00 0.131174E+09 135990.41
September 0.192879E+10 0.706810E+09 0.836191E+09 0.00 0.00 0.00 0.00 0.110007E+09 182537.31
October 0.199148E+10 0.731042E+09 0.864640E+09 0.00 0.00 0.00 0.00 82076249.74 2231823.11
November 0.192552E+10 0.709205E+09 0.838269E+09 0.00 0.00 0.00 0.00 40355328.95 38342416.77
December 0.199054E+10 0.729351E+09 0.863211E+09 0.00 0.00 0.00 0.00 11595763.39 0.102143E+09
                   
Annual Sum or Average 0.234744E+11 0.861373E+10 0.101856E+11 0.00 0.00 0.00 0.00 0.792921E+09 0.434166E+09
Minimum of Months 0.179968E+10 0.660319E+09 0.780982E+09 0.00 0.00 0.00 0.00 8091695.06 42965.28
Maximum of Months 0.199990E+10 0.733860E+09 0.866978E+09 0.00 0.00 0.00 0.00 0.133570E+09 0.123491E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.846876E+09 0.100156E+10 0.00 0.00 0.00 0.00 4394431.71 52690051.70
February 0.208403E+10 0.764651E+09 0.904380E+09 0.00 0.00 0.00 0.00 6661936.31 35026143.56
March 0.231589E+10 0.849486E+09 0.100366E+10 0.00 0.00 0.00 0.00 7672706.96 30875365.02
April 0.223463E+10 0.818162E+09 0.968011E+09 0.00 0.00 0.00 0.00 16693626.02 10410302.81
May 0.230993E+10 0.848344E+09 0.100276E+10 0.00 0.00 0.00 0.00 34646558.70 1497596.04
June 0.223950E+10 0.821915E+09 0.971170E+09 0.00 0.00 0.00 0.00 46169739.22 48562.13
July 0.230505E+10 0.844592E+09 0.999601E+09 0.00 0.00 0.00 0.00 52482928.63 415208.20
August 0.231480E+10 0.849812E+09 0.100396E+10 0.00 0.00 0.00 0.00 51116600.56 180687.33
September 0.223354E+10 0.818489E+09 0.968312E+09 0.00 0.00 0.00 0.00 43390274.40 305146.41
October 0.230614E+10 0.846549E+09 0.100126E+10 0.00 0.00 0.00 0.00 32937710.86 1629471.44
November 0.222975E+10 0.821262E+09 0.970719E+09 0.00 0.00 0.00 0.00 17337460.57 17618781.61
December 0.230505E+10 0.844592E+09 0.999601E+09 0.00 0.00 0.00 0.00 5804192.99 44310039.10
                   
Annual Sum or Average 0.271834E+11 0.997473E+10 0.117950E+11 0.00 0.00 0.00 0.00 0.319308E+09 0.195007E+09
Minimum of Months 0.208403E+10 0.764651E+09 0.904380E+09 0.00 0.00 0.00 0.00 4394431.71 48562.13
Maximum of Months 0.231589E+10 0.849812E+09 0.100396E+10 0.00 0.00 0.00 0.00 52482928.63 52690051.70



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.141236E+10 0.105898E+10 0.00 0.00 0.00 0.00 12853284.17 0.110077E+09
February 0.440737E+09 0.127524E+10 0.956227E+09 0.00 0.00 0.00 0.00 18695695.95 72396655.07
March 0.489771E+09 0.141672E+10 0.106120E+10 0.00 0.00 0.00 0.00 21403104.68 62365601.20
April 0.472586E+09 0.136448E+10 0.102351E+10 0.00 0.00 0.00 0.00 41893520.23 19274899.73
May 0.488511E+09 0.141481E+10 0.106025E+10 0.00 0.00 0.00 0.00 82342076.52 2828703.24
June 0.473617E+09 0.137074E+10 0.102685E+10 0.00 0.00 0.00 0.00 0.106540E+09 108762.60
July 0.487480E+09 0.140855E+10 0.105691E+10 0.00 0.00 0.00 0.00 0.121365E+09 913890.11
August 0.489542E+09 0.141726E+10 0.106152E+10 0.00 0.00 0.00 0.00 0.120397E+09 439637.95
September 0.472357E+09 0.136502E+10 0.102382E+10 0.00 0.00 0.00 0.00 0.102005E+09 502912.17
October 0.487709E+09 0.141182E+10 0.105866E+10 0.00 0.00 0.00 0.00 80222258.16 2724956.79
November 0.471555E+09 0.136965E+10 0.102637E+10 0.00 0.00 0.00 0.00 44205143.48 37300205.23
December 0.487480E+09 0.140855E+10 0.105691E+10 0.00 0.00 0.00 0.00 15933401.43 92893136.17
                   
Annual Sum or Average 0.574883E+10 0.166352E+11 0.124712E+11 0.00 0.00 0.00 0.00 0.767856E+09 0.401826E+09
Minimum of Months 0.440737E+09 0.127524E+10 0.956227E+09 0.00 0.00 0.00 0.00 12853284.17 108762.60
Maximum of Months 0.489771E+09 0.141726E+10 0.106152E+10 0.00 0.00 0.00 0.00 0.121365E+09 0.110077E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.236418E+09 0.305485E+09 0.00 0.00 0.00 0.00 7618130.17 61653601.75
February 0.339028E+09 0.213464E+09 0.275845E+09 0.00 0.00 0.00 0.00 11096920.28 40149114.58
March 0.376747E+09 0.237147E+09 0.306128E+09 0.00 0.00 0.00 0.00 13033297.46 34399604.99
April 0.363528E+09 0.228402E+09 0.295253E+09 0.00 0.00 0.00 0.00 25213859.45 10022042.54
May 0.375778E+09 0.236828E+09 0.305852E+09 0.00 0.00 0.00 0.00 48943054.22 1469375.18
June 0.364321E+09 0.229450E+09 0.296217E+09 0.00 0.00 0.00 0.00 62225395.53 40135.44
July 0.374985E+09 0.235780E+09 0.304889E+09 0.00 0.00 0.00 0.00 70384729.88 474165.62
August 0.376571E+09 0.237238E+09 0.306219E+09 0.00 0.00 0.00 0.00 70317839.42 207334.06
September 0.363352E+09 0.228493E+09 0.295345E+09 0.00 0.00 0.00 0.00 59561808.07 220788.97
October 0.375161E+09 0.236327E+09 0.305393E+09 0.00 0.00 0.00 0.00 47553923.40 1398753.40
November 0.362735E+09 0.229268E+09 0.296079E+09 0.00 0.00 0.00 0.00 26512487.24 20574551.64
December 0.374985E+09 0.235780E+09 0.304889E+09 0.00 0.00 0.00 0.00 9545929.81 51796622.93
                   
Annual Sum or Average 0.442217E+10 0.278459E+10 0.359760E+10 0.00 0.00 0.00 0.00 0.452007E+09 0.222406E+09
Minimum of Months 0.339028E+09 0.213464E+09 0.275845E+09 0.00 0.00 0.00 0.00 7618130.17 40135.44
Maximum of Months 0.376747E+09 0.237238E+09 0.306219E+09 0.00 0.00 0.00 0.00 70384729.88 61653601.75



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.370859E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 18945350.22 0.160641E+09
February 0.139600E+10 0.334852E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 29600438.21 0.105413E+09
March 0.155131E+10 0.372002E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 34844429.47 90572489.06
April 0.149688E+10 0.358285E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 68249772.67 23617219.80
May 0.154732E+10 0.371502E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 0.137182E+09 2245877.45
June 0.150015E+10 0.359929E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 0.177875E+09 107628.17
July 0.154405E+10 0.369859E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.201076E+09 576497.05
August 0.155059E+10 0.372145E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.195891E+09 464808.06
September 0.149615E+10 0.358428E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 0.170911E+09 560336.38
October 0.154478E+10 0.370717E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 0.134767E+09 2145088.15
November 0.149361E+10 0.359643E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 71693194.03 48376125.49
December 0.154405E+10 0.369859E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 27705317.25 0.134016E+09
                   
Annual Sum or Average 0.182090E+11 0.436808E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 0.126874E+10 0.568736E+09
Minimum of Months 0.139600E+10 0.334852E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 18945350.22 107628.17
Maximum of Months 0.155131E+10 0.372145E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.201076E+09 0.160641E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.158558E+10 0.121771E+10 0.00 0.00 0.00 0.00 16962201.75 0.325877E+09
February 0.236489E+11 0.141366E+10 0.109956E+10 0.00 0.00 0.00 0.00 26042016.10 0.214321E+09
March 0.262800E+11 0.153412E+10 0.122027E+10 0.00 0.00 0.00 0.00 33992787.55 0.187121E+09
April 0.253579E+11 0.145996E+10 0.117692E+10 0.00 0.00 0.00 0.00 87490200.51 62182659.41
May 0.262123E+11 0.149054E+10 0.121917E+10 0.00 0.00 0.00 0.00 0.194084E+09 9566370.31
June 0.254132E+11 0.144519E+10 0.118076E+10 0.00 0.00 0.00 0.00 0.261778E+09 357286.91
July 0.261570E+11 0.146137E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.296184E+09 2373814.30
August 0.262677E+11 0.150479E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.286532E+09 875947.20
September 0.253456E+11 0.147887E+10 0.117729E+10 0.00 0.00 0.00 0.00 0.239857E+09 1927028.58
October 0.261693E+11 0.155970E+10 0.121734E+10 0.00 0.00 0.00 0.00 0.176480E+09 9698285.15
November 0.253025E+11 0.152070E+10 0.118021E+10 0.00 0.00 0.00 0.00 85689744.40 0.106886E+09
December 0.261570E+11 0.158530E+10 0.121533E+10 0.00 0.00 0.00 0.00 24979499.76 0.273368E+09
                   
Annual Sum or Average 0.308468E+12 0.180398E+11 0.143405E+11 0.00 0.00 0.00 0.00 0.173007E+10 0.119456E+10
Minimum of Months 0.236489E+11 0.141366E+10 0.109956E+10 0.00 0.00 0.00 0.00 16962201.75 357286.91
Maximum of Months 0.262800E+11 0.158558E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.296184E+09 0.325877E+09



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.104070E+11 0.126520E+11 0.00 0.00 0.00 0.00 57735581.03 0.932618E+09
February 0.702046E+11 0.937927E+10 0.114244E+11 0.00 0.00 0.00 0.00 90768022.27 0.617968E+09
March 0.780153E+11 0.103889E+11 0.126786E+11 0.00 0.00 0.00 0.00 0.112140E+09 0.541312E+09
April 0.752779E+11 0.998862E+10 0.122282E+11 0.00 0.00 0.00 0.00 0.263364E+09 0.185438E+09
May 0.778146E+11 0.103373E+11 0.126672E+11 0.00 0.00 0.00 0.00 0.556715E+09 28881811.43
June 0.754422E+11 0.100216E+11 0.122682E+11 0.00 0.00 0.00 0.00 0.746910E+09 1160883.82
July 0.776503E+11 0.102714E+11 0.126273E+11 0.00 0.00 0.00 0.00 0.854012E+09 7215505.21
August 0.779788E+11 0.103638E+11 0.126824E+11 0.00 0.00 0.00 0.00 0.825409E+09 3725188.74
September 0.752414E+11 0.100123E+11 0.122320E+11 0.00 0.00 0.00 0.00 0.697042E+09 6021485.40
October 0.776868E+11 0.103803E+11 0.126482E+11 0.00 0.00 0.00 0.00 0.517022E+09 29185985.81
November 0.751137E+11 0.100767E+11 0.122624E+11 0.00 0.00 0.00 0.00 0.260719E+09 0.311634E+09
December 0.776503E+11 0.103854E+11 0.126273E+11 0.00 0.00 0.00 0.00 80371282.18 0.784868E+09
                   
Annual Sum or Average 0.915726E+12 0.122013E+12 0.148998E+12 0.00 0.00 0.00 0.00 0.506221E+10 0.345003E+10
Minimum of Months 0.702046E+11 0.937927E+10 0.114244E+11 0.00 0.00 0.00 0.00 57735581.03 1160883.82
Maximum of Months 0.780153E+11 0.104070E+11 0.126824E+11 0.00 0.00 0.00 0.00 0.854012E+09 0.932618E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 11962316.31 54684120.31
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 18298631.33 33102029.19
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 25970053.98 29376833.14
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 45241992.65 3782840.72
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 84223720.82 164262.83
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.103364E+09 9771.91
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.114433E+09 19752.78
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.111959E+09 69235.47
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 99745101.15 0.00
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 82695400.91 45258.14
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 45548601.27 13462129.52
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 17754913.59 44447494.68
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.761197E+09 0.179164E+09
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 11962316.31 0.00
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.114433E+09 54684120.31



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 12689348.47 52742652.47
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 19028940.97 32381600.52
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 26351531.25 28673793.70
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 45379365.38 3754648.62
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 84204115.73 164631.51
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.103308E+09 9771.52
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.114397E+09 19983.74
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.111973E+09 67379.34
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 99854832.61 0.00
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 82999191.53 40958.15
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 46137086.38 13148087.60
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 18319134.56 42924010.11
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.764641E+09 0.173928E+09
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 12689348.47 0.00
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.114397E+09 52742652.47



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 85091918.49 0.255708E+09 0.00 0.00 0.00 0.00 1645418.20 22019669.97
February 0.00 76846309.13 0.230956E+09 0.00 0.00 0.00 0.00 2502490.13 14090877.88
March 0.00 84415649.14 0.255355E+09 0.00 0.00 0.00 0.00 3046153.14 12197604.17
April 0.00 82445007.08 0.247516E+09 0.00 0.00 0.00 0.00 7041507.93 3387652.65
May 0.00 84753783.81 0.255532E+09 0.00 0.00 0.00 0.00 15739145.46 415437.45
June 0.00 81790910.76 0.247163E+09 0.00 0.00 0.00 0.00 20992503.42 3904.60
July 0.00 85418966.65 0.255885E+09 0.00 0.00 0.00 0.00 23914076.47 62924.72
August 0.00 84415649.14 0.255355E+09 0.00 0.00 0.00 0.00 23192199.54 65666.08
September 0.00 82467180.11 0.247516E+09 0.00 0.00 0.00 0.00 20028652.15 28041.80
October 0.00 85080831.98 0.255708E+09 0.00 0.00 0.00 0.00 15316010.12 381986.73
November 0.00 82117958.92 0.247340E+09 0.00 0.00 0.00 0.00 7822396.86 6840979.66
December 0.00 85430053.17 0.255885E+09 0.00 0.00 0.00 0.00 2436180.42 18190189.96
                   
Annual Sum or Average 0.00 0.100027E+10 0.300992E+10 0.00 0.00 0.00 0.00 0.143677E+09 77684935.67
Minimum of Months 0.00 76846309.13 0.230956E+09 0.00 0.00 0.00 0.00 1645418.20 3904.60
Maximum of Months 0.00 85430053.17 0.255885E+09 0.00 0.00 0.00 0.00 23914076.47 22019669.97



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 85115186.72 0.255778E+09 0.00 0.00 0.00 0.00 4169761.01 14378878.31
February 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 6164566.87 8932637.43
March 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 8208547.08 7796343.07
April 0.293479E+09 82467551.52 0.247584E+09 0.00 0.00 0.00 0.00 13598109.19 988522.90
May 0.303504E+09 84776959.58 0.255602E+09 0.00 0.00 0.00 0.00 24120389.82 26713.57
June 0.293842E+09 81813276.33 0.247231E+09 0.00 0.00 0.00 0.00 29282635.43 925.25
July 0.303141E+09 85442324.32 0.255955E+09 0.00 0.00 0.00 0.00 32317257.28 2440.26
August 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 31809218.78 1716.58
September 0.293479E+09 82489730.61 0.247584E+09 0.00 0.00 0.00 0.00 28433317.73 0.00
October 0.303322E+09 85104097.18 0.255778E+09 0.00 0.00 0.00 0.00 24034258.76 5206.61
November 0.293661E+09 82140413.93 0.247408E+09 0.00 0.00 0.00 0.00 13781929.78 3551704.56
December 0.303141E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 5777795.80 11674987.09
                   
Annual Sum or Average 0.357224E+10 0.100055E+10 0.301074E+10 0.00 0.00 0.00 0.00 0.221698E+09 47360075.63
Minimum of Months 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 4169761.01 0.00
Maximum of Months 0.303685E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 32317257.28 14378878.31



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 11831749.86 55370162.29
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 18152006.85 33623026.31
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 25764251.39 30225331.24
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 44910303.96 3970653.17
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 83935939.61 170211.86
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.103063E+09 9772.21
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.114197E+09 20891.79
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.111769E+09 71955.61
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 99492005.36 0.00
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 82457769.86 58922.12
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 45384891.07 13703954.68
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 17683221.72 44651703.30
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.758642E+09 0.181877E+09
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 11831749.86 0.00
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.114197E+09 55370162.29



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 12237976.25 53346701.02
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 18439832.26 32879125.63
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 25876515.08 29645477.37
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 44952635.50 3955210.00
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 83923366.28 170809.78
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.103035E+09 9775.21
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.114176E+09 21107.93
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.111776E+09 70074.71
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 99543239.84 0.00
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 82605854.56 55093.82
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 45783977.48 13422271.11
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 18195063.31 42809229.99
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.760545E+09 0.176385E+09
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 12237976.25 0.00
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.114176E+09 53346701.02



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.232638E+10 0.00 0.00 0.00 0.00 0.00 7828454.41 90245860.65
February 0.348285E+10 0.210051E+10 0.00 0.00 0.00 0.00 0.00 11977422.44 58464829.49
March 0.387034E+10 0.233355E+10 0.00 0.00 0.00 0.00 0.00 13766532.19 51775875.38
April 0.373454E+10 0.224750E+10 0.00 0.00 0.00 0.00 0.00 28517512.52 17184257.09
May 0.386038E+10 0.233041E+10 0.00 0.00 0.00 0.00 0.00 60858128.80 2480134.07
June 0.374269E+10 0.225781E+10 0.00 0.00 0.00 0.00 0.00 80069486.51 102599.05
July 0.385223E+10 0.232011E+10 0.00 0.00 0.00 0.00 0.00 91731795.99 794255.84
August 0.386853E+10 0.233445E+10 0.00 0.00 0.00 0.00 0.00 89443333.68 430949.78
September 0.373273E+10 0.224840E+10 0.00 0.00 0.00 0.00 0.00 75500116.09 528714.98
October 0.385404E+10 0.232548E+10 0.00 0.00 0.00 0.00 0.00 56154055.14 2929250.98
November 0.372639E+10 0.225602E+10 0.00 0.00 0.00 0.00 0.00 30271923.36 31229894.16
December 0.385223E+10 0.232011E+10 0.00 0.00 0.00 0.00 0.00 10246843.64 75513879.41
                   
Annual Sum or Average 0.454292E+11 0.274007E+11 0.00 0.00 0.00 0.00 0.00 0.556366E+09 0.331681E+09
Minimum of Months 0.348285E+10 0.210051E+10 0.00 0.00 0.00 0.00 0.00 7828454.41 102599.05
Maximum of Months 0.387034E+10 0.233445E+10 0.00 0.00 0.00 0.00 0.00 91731795.99 90245860.65



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 11681207.78 54889052.06
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 17868293.09 33252465.16
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 25365127.94 29434589.96
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 44439035.70 3853850.54
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 83248075.94 174176.90
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.102396E+09 11554.59
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.113408E+09 22158.53
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.110987E+09 54901.74
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 98810189.29 0.00
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 81782738.95 44200.08
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 44896213.77 13515244.39
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 17363938.32 44528901.77
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.752246E+09 0.179781E+09
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 11681207.78 0.00
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.113408E+09 54889052.06



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 12504229.38 52714490.01
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 18651805.42 32463678.84
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 25754537.54 28659559.09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 44575469.70 3827397.20
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 83224878.19 174813.40
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.102334E+09 11649.41
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.113368E+09 22400.71
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.111001E+09 52855.07
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 98926820.38 0.00
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 82111074.39 40784.25
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 45566469.71 13161126.87
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 18013838.46 42792688.77
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.756032E+09 0.173921E+09
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 12504229.38 0.00
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.113368E+09 52714490.01



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 85115186.72 0.255778E+09 0.00 0.00 0.00 0.00 5782962.68 28836728.77
February 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 8946649.89 17422159.21
March 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 12899937.02 15376477.39
April 0.293479E+09 82467551.52 0.247584E+09 0.00 0.00 0.00 0.00 22778333.91 1963009.57
May 0.303504E+09 84776959.58 0.255602E+09 0.00 0.00 0.00 0.00 42697682.93 84154.40
June 0.293842E+09 81813276.33 0.247231E+09 0.00 0.00 0.00 0.00 52472782.73 5712.02
July 0.303141E+09 85442324.32 0.255955E+09 0.00 0.00 0.00 0.00 58093463.66 10026.95
August 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 56839511.21 23745.51
September 0.293479E+09 82489730.61 0.247584E+09 0.00 0.00 0.00 0.00 50459754.47 0.00
October 0.303322E+09 85104097.18 0.255778E+09 0.00 0.00 0.00 0.00 41592497.50 27745.64
November 0.293661E+09 82140413.93 0.247408E+09 0.00 0.00 0.00 0.00 22720201.39 7134847.59
December 0.303141E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 8702598.84 23466607.65
                   
Annual Sum or Average 0.357224E+10 0.100055E+10 0.301074E+10 0.00 0.00 0.00 0.00 0.383986E+09 94351214.69
Minimum of Months 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 5782962.68 0.00
Maximum of Months 0.303685E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 58093463.66 28836728.77



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.301722E+10 0.149358E+11 0.00 0.00 0.00 0.00 11122075.54 0.217242E+09
February 0.415303E+11 0.270132E+10 0.134904E+11 0.00 0.00 0.00 0.00 17171929.72 0.145746E+09
March 0.461508E+11 0.296389E+10 0.149358E+11 0.00 0.00 0.00 0.00 19042848.58 0.129607E+09
April 0.445315E+11 0.282776E+10 0.144540E+11 0.00 0.00 0.00 0.00 48075133.46 45960483.33
May 0.460320E+11 0.290316E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.110784E+09 7614346.33
June 0.446286E+11 0.280132E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.154160E+09 535731.24
July 0.459349E+11 0.286862E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.179476E+09 2073188.73
August 0.461292E+11 0.292425E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.173019E+09 1398900.11
September 0.445099E+11 0.285020E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.147183E+09 1803911.68
October 0.459565E+11 0.298382E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.108498E+09 7395354.44
November 0.444343E+11 0.290521E+10 0.144540E+11 0.00 0.00 0.00 0.00 53844929.29 73508239.17
December 0.459349E+11 0.300552E+10 0.149358E+11 0.00 0.00 0.00 0.00 16031323.58 0.183320E+09
                   
Annual Sum or Average 0.541708E+12 0.347523E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.103841E+10 0.816205E+09
Minimum of Months 0.415303E+11 0.270132E+10 0.134904E+11 0.00 0.00 0.00 0.00 11122075.54 535731.24
Maximum of Months 0.461508E+11 0.301722E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.179476E+09 0.217242E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.301722E+10 0.149358E+11 0.00 0.00 0.00 0.00 10215276.81 0.219922E+09
February 0.415303E+11 0.270132E+10 0.134904E+11 0.00 0.00 0.00 0.00 15840703.93 0.147075E+09
March 0.461508E+11 0.296389E+10 0.149358E+11 0.00 0.00 0.00 0.00 17982503.66 0.131189E+09
April 0.445315E+11 0.282776E+10 0.144540E+11 0.00 0.00 0.00 0.00 46991580.92 46174031.71
May 0.460320E+11 0.290316E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.110037E+09 7633879.90
June 0.446286E+11 0.280132E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.153684E+09 537115.23
July 0.459349E+11 0.286862E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.179152E+09 2076340.74
August 0.461292E+11 0.292425E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.172468E+09 1478077.79
September 0.445099E+11 0.285020E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.146602E+09 1805802.00
October 0.459565E+11 0.298382E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.107521E+09 7408426.45
November 0.444343E+11 0.290521E+10 0.144540E+11 0.00 0.00 0.00 0.00 52658380.33 74088136.99
December 0.459349E+11 0.300552E+10 0.149358E+11 0.00 0.00 0.00 0.00 15128303.27 0.185597E+09
                   
Annual Sum or Average 0.541708E+12 0.347523E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.102828E+10 0.824985E+09
Minimum of Months 0.415303E+11 0.270132E+10 0.134904E+11 0.00 0.00 0.00 0.00 10215276.81 537115.23
Maximum of Months 0.461508E+11 0.301722E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.179152E+09 0.219922E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.113146E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 8108544.53 0.195520E+09
February 0.369574E+10 0.102161E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 12661979.82 0.129091E+09
March 0.410691E+10 0.113495E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 15018291.81 0.115952E+09
April 0.396281E+10 0.109310E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 41220992.02 39394787.56
May 0.409635E+10 0.113342E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 98862283.55 6180440.43
June 0.397146E+10 0.109811E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.138150E+09 438872.94
July 0.408770E+10 0.112841E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.160904E+09 1663069.53
August 0.410499E+10 0.113539E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.155076E+09 1387261.57
September 0.396089E+10 0.109354E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.131513E+09 1370096.62
October 0.408962E+10 0.113103E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 95976974.86 5990580.78
November 0.395417E+10 0.109724E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 46015054.45 64700195.89
December 0.408770E+10 0.112841E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 12427861.09 0.164847E+09
                   
Annual Sum or Average 0.482060E+11 0.133267E+11 0.392709E+12 0.359593E+12 0.00 0.00 0.00 0.915934E+09 0.726535E+09
Minimum of Months 0.369574E+10 0.102161E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 8108544.53 438872.94
Maximum of Months 0.410691E+10 0.113539E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.160904E+09 0.195520E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.246211E+10 0.00 0.00 0.00 0.00 0.00 13415857.91 0.147689E+09
February 0.368610E+10 0.222306E+10 0.00 0.00 0.00 0.00 0.00 19427975.43 96044363.52
March 0.409620E+10 0.246970E+10 0.00 0.00 0.00 0.00 0.00 22238176.83 84781450.87
April 0.395248E+10 0.237864E+10 0.00 0.00 0.00 0.00 0.00 46838791.03 27536172.71
May 0.408566E+10 0.246638E+10 0.00 0.00 0.00 0.00 0.00 0.102546E+09 3888195.12
June 0.396110E+10 0.238954E+10 0.00 0.00 0.00 0.00 0.00 0.137701E+09 195314.24
July 0.407704E+10 0.245547E+10 0.00 0.00 0.00 0.00 0.00 0.159284E+09 1300424.53
August 0.409429E+10 0.247065E+10 0.00 0.00 0.00 0.00 0.00 0.155263E+09 643610.64
September 0.395056E+10 0.237958E+10 0.00 0.00 0.00 0.00 0.00 0.131388E+09 615282.01
October 0.407896E+10 0.246116E+10 0.00 0.00 0.00 0.00 0.00 98469701.96 3883052.48
November 0.394385E+10 0.238765E+10 0.00 0.00 0.00 0.00 0.00 52229809.02 49534612.92
December 0.407704E+10 0.245547E+10 0.00 0.00 0.00 0.00 0.00 16956303.13 0.123012E+09
                   
Annual Sum or Average 0.480803E+11 0.289994E+11 0.00 0.00 0.00 0.00 0.00 0.955758E+09 0.539124E+09
Minimum of Months 0.368610E+10 0.222306E+10 0.00 0.00 0.00 0.00 0.00 13415857.91 195314.24
Maximum of Months 0.409620E+10 0.247065E+10 0.00 0.00 0.00 0.00 0.00 0.159284E+09 0.147689E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 14185.34 02-JAN-20:10 10113.80 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 14185.34 01-FEB-20:10 10113.80 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 14185.34 01-MAR-20:10 10113.80 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 14185.34 03-APR-19:10 10113.80 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 14185.34 01-MAY-19:10 10113.80 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 14185.34 01-JUN-19:10 10113.80 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 14185.34 03-JUL-19:10 10113.80 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 14185.34 01-AUG-19:10 10113.80 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 14185.34 01-SEP-19:10 10113.80 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 14185.34 02-OCT-19:10 10113.80 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 14185.34 01-NOV-19:10 10113.80 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 14185.34 01-DEC-20:10 10113.80 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   14185.34   10113.80   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   14185.34   10113.80   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 704.41 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 56.95 02-JAN-14:00 146.81 25-JAN-05:20
February 1169.53 01-FEB-00:10 704.41 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 62.70 11-FEB-14:00 202.93 04-FEB-07:00
March 1169.53 01-MAR-00:10 704.41 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 62.11 13-MAR-16:00 179.45 16-MAR-07:00
April 1169.53 01-APR-00:10 704.41 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 93.44 17-APR-15:00 95.64 02-APR-05:20
May 1169.53 01-MAY-00:10 704.41 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 117.90 22-MAY-13:00 26.43 07-MAY-06:00
June 1169.53 01-JUN-00:10 704.41 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 94.13 11-JUN-13:00 8.30 05-JUN-22:00
July 1169.53 01-JUL-00:10 704.41 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 130.79 29-JUL-16:00 14.27 14-JUL-22:00
August 1169.53 01-AUG-00:10 704.41 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 112.96 23-AUG-13:00 8.10 05-AUG-18:00
September 1169.53 01-SEP-00:10 704.41 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 93.86 13-SEP-13:00 14.24 02-SEP-22:00
October 1169.53 01-OCT-23:10 704.41 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 93.85 09-OCT-10:55 27.28 26-OCT-14:00
November 1169.53 01-NOV-00:10 704.41 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 69.12 17-NOV-15:00 145.62 27-NOV-03:00
December 1169.53 01-DEC-00:10 704.41 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 56.46 10-DEC-14:00 168.20 15-DEC-05:20
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   704.41   685.60   0.00 0.00 0.00 0.00 56.46   8.10  
Maximum of Months 1169.53   704.41   685.60   0.00 0.00 0.00 0.00 130.79   202.93  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 815.72 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 26.39 02-JAN-14:30 65.60 25-JAN-07:00
February 1354.32 01-FEB-00:10 815.72 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 27.47 11-FEB-14:00 85.79 04-FEB-07:00
March 1354.32 01-MAR-00:10 815.72 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 27.19 13-MAR-16:00 78.92 16-MAR-05:50
April 1354.32 01-APR-00:10 815.72 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 39.08 17-APR-15:00 43.16 02-APR-05:30
May 1354.32 01-MAY-00:10 815.72 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 49.08 22-MAY-13:00 14.58 07-MAY-06:00
June 1354.32 01-JUN-00:10 815.72 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 39.08 11-JUN-13:00 3.21 05-JUN-22:00
July 1354.32 01-JUL-00:10 815.72 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 52.45 29-JUL-16:00 5.51 14-JUL-23:07
August 1354.32 01-AUG-00:10 815.72 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 46.10 23-AUG-13:00 6.36 12-AUG-07:00
September 1354.32 01-SEP-00:10 815.72 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 39.11 13-SEP-13:00 7.94 05-SEP-06:00
October 1354.32 01-OCT-23:10 815.72 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 38.94 14-OCT-13:00 11.62 28-OCT-03:00
November 1354.32 01-NOV-00:10 815.72 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 29.14 17-NOV-15:00 63.53 27-NOV-03:00
December 1354.32 01-DEC-00:10 815.72 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 24.78 10-DEC-14:40 74.07 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   815.72   793.93   0.00 0.00 0.00 0.00 24.78   3.21  
Maximum of Months 1354.32   815.72   793.93   0.00 0.00 0.00 0.00 52.45   85.79  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 1360.40 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 64.75 02-JAN-14:30 144.36 25-JAN-07:00
February 286.42 01-FEB-00:10 1360.40 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 67.71 11-FEB-14:00 195.29 04-FEB-07:00
March 286.42 01-MAR-00:10 1360.40 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 69.75 13-MAR-16:00 178.19 16-MAR-06:40
April 286.42 01-APR-00:10 1360.40 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 92.78 17-APR-15:00 96.26 02-APR-05:40
May 286.42 01-MAY-00:10 1360.40 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 113.01 22-MAY-13:00 31.65 07-MAY-05:40
June 286.42 01-JUN-00:10 1360.40 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 88.57 11-JUN-13:00 8.64 05-JUN-15:00
July 286.42 01-JUL-00:10 1360.40 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 121.37 29-JUL-16:00 13.03 14-JUL-22:00
August 286.42 01-AUG-00:10 1360.40 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 105.81 23-AUG-13:00 15.11 12-AUG-09:00
September 286.42 01-SEP-00:10 1360.40 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 90.36 08-SEP-16:00 16.74 05-SEP-06:00
October 286.42 01-OCT-23:10 1360.40 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 92.43 14-OCT-13:00 23.71 28-OCT-03:00
November 286.42 01-NOV-00:10 1360.40 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 71.79 17-NOV-15:00 142.96 27-NOV-07:00
December 286.42 01-DEC-00:10 1360.40 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 59.71 10-DEC-14:40 166.14 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   1360.40   839.45   0.00 0.00 0.00 0.00 59.71   8.64  
Maximum of Months 286.42   1360.40   839.45   0.00 0.00 0.00 0.00 121.37   195.29  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 227.72 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 37.01 02-JAN-14:30 82.16 25-JAN-07:00
February 220.32 01-FEB-00:10 227.72 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 38.77 11-FEB-14:00 111.65 04-FEB-07:00
March 220.32 01-MAR-00:10 227.72 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 39.97 13-MAR-16:00 101.09 16-MAR-05:40
April 220.32 01-APR-00:10 227.72 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 53.41 17-APR-15:00 54.52 02-APR-05:20
May 220.32 01-MAY-00:10 227.72 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 65.12 22-MAY-13:00 17.36 07-MAY-06:00
June 220.32 01-JUN-00:10 227.72 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 51.01 11-JUN-13:00 4.58 05-JUN-15:00
July 220.32 01-JUL-00:10 227.72 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 69.58 29-JUL-16:00 7.52 14-JUL-22:00
August 220.32 01-AUG-00:10 227.72 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 60.95 23-AUG-13:00 8.00 12-AUG-07:00
September 220.32 01-SEP-00:10 227.72 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 51.96 13-SEP-13:00 8.67 05-SEP-06:00
October 220.32 01-OCT-23:10 227.72 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 52.95 14-OCT-13:00 13.51 28-OCT-03:00
November 220.32 01-NOV-00:10 227.72 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 41.36 17-NOV-15:00 81.87 27-NOV-03:00
December 220.32 01-DEC-00:10 227.72 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 34.20 10-DEC-14:40 94.63 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   227.72   242.16   0.00 0.00 0.00 0.00 34.20   4.58  
Maximum of Months 220.32   227.72   242.16   0.00 0.00 0.00 0.00 69.58   111.65  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 357.21 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 105.20 02-JAN-14:30 226.22 25-JAN-07:00
February 907.20 01-FEB-00:10 357.21 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 110.00 11-FEB-14:00 279.78 04-FEB-07:00
March 907.20 01-MAR-00:10 357.21 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 107.59 13-MAR-16:00 270.39 16-MAR-07:00
April 907.20 01-APR-00:10 357.21 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 143.51 16-APR-17:00 139.41 02-APR-06:10
May 907.20 01-MAY-00:10 357.21 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 170.81 29-MAY-16:00 50.41 01-MAY-06:00
June 907.20 01-JUN-00:10 357.21 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 146.74 11-JUN-13:00 10.36 15-JUN-08:00
July 907.20 01-JUL-00:10 357.21 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 195.33 29-JUL-16:00 17.92 14-JUL-19:20
August 907.20 01-AUG-00:10 357.21 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 163.89 06-AUG-13:00 26.67 12-AUG-09:00
September 907.20 01-SEP-00:10 357.21 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 147.67 08-SEP-16:00 26.42 05-SEP-06:00
October 907.20 01-OCT-23:10 357.21 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 146.60 07-OCT-10:50 33.96 20-OCT-06:00
November 907.20 01-NOV-00:10 357.21 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 105.22 17-NOV-15:00 215.56 27-NOV-07:00
December 907.20 01-DEC-00:10 357.21 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 105.88 10-DEC-14:40 252.60 15-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   357.21   4572.80   39726.58   0.00 0.00 0.00 105.20   10.36  
Maximum of Months 907.20   357.21   4572.80   39726.58   0.00 0.00 0.00 195.33   279.78  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 1761.91 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 125.90 02-JAN-14:00 391.90 25-JAN-05:20
February 15368.40 01-FEB-00:10 1761.91 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 138.63 11-FEB-14:00 487.54 04-FEB-06:03
March 15368.40 01-MAR-00:10 1761.91 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 137.35 13-MAR-16:00 460.26 16-MAR-05:00
April 15368.40 01-APR-00:10 1761.91 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 206.59 17-APR-15:00 245.17 02-APR-05:20
May 15368.40 01-MAY-00:10 1761.91 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 267.21 22-MAY-13:00 89.55 01-MAY-05:00
June 15368.40 01-JUN-00:10 1761.91 01-JUN-19:10 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 218.38 11-JUN-13:00 18.28 06-JUN-03:10
July 15368.40 01-JUL-00:10 1761.91 03-JUL-19:10 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 289.14 29-JUL-16:00 31.52 14-JUL-23:10
August 15368.40 01-AUG-00:10 1761.91 01-AUG-19:10 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 249.71 23-AUG-13:00 34.27 12-AUG-07:00
September 15368.40 01-SEP-00:10 1761.91 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 207.51 13-SEP-13:00 46.99 05-SEP-06:00
October 15368.40 01-OCT-23:10 1761.91 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 207.48 09-OCT-10:55 76.01 28-OCT-03:10
November 15368.40 01-NOV-00:10 1761.91 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 152.83 17-NOV-15:00 378.80 27-NOV-03:00
December 15368.40 01-DEC-00:10 1761.91 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 124.83 10-DEC-14:00 437.68 15-DEC-05:20
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   1761.91   965.27   0.00 0.00 0.00 0.00 124.83   18.28  
Maximum of Months 15368.40   1761.91   965.27   0.00 0.00 0.00 0.00 289.14   487.54  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 10265.18 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 392.18 02-JAN-14:30 1137.44 25-JAN-05:40
February 45622.98 01-FEB-00:10 10265.18 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 408.52 11-FEB-14:00 1460.26 04-FEB-07:00
March 45622.98 01-MAR-00:10 10265.18 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 419.03 13-MAR-16:00 1348.03 16-MAR-05:00
April 45622.98 01-APR-00:10 10265.18 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 629.63 17-APR-15:00 732.46 02-APR-05:40
May 45622.98 01-MAY-00:10 10265.18 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 796.78 22-MAY-13:00 256.33 01-MAY-06:00
June 45622.98 01-JUN-00:10 10265.18 01-JUN-19:10 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 641.41 11-JUN-13:00 52.38 05-JUN-22:00
July 45622.98 01-JUL-00:10 10265.18 03-JUL-19:10 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 859.28 29-JUL-16:00 90.14 14-JUL-23:07
August 45622.98 01-AUG-00:10 10265.18 01-AUG-19:10 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 746.38 23-AUG-13:00 123.11 12-AUG-07:00
September 45622.98 01-SEP-00:10 10265.18 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 629.54 13-SEP-13:00 134.41 05-SEP-06:00
October 45622.98 01-OCT-23:10 10265.18 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 614.86 09-OCT-10:55 217.30 28-OCT-03:10
November 45622.98 01-NOV-00:10 10265.18 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 453.18 17-NOV-15:00 1093.91 27-NOV-05:50
December 45622.98 01-DEC-00:10 10265.18 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 376.51 10-DEC-14:40 1274.52 15-DEC-05:40
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   10265.18   10029.21   0.00 0.00 0.00 0.00 376.51   52.38  
Maximum of Months 45622.98   10265.18   10029.21   0.00 0.00 0.00 0.00 859.28   1460.26  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 37.72 01-JAN-11:00 85.02 25-JAN-07:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 44.37 11-FEB-16:10 118.92 04-FEB-07:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 55.05 13-MAR-16:00 105.27 16-MAR-07:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 72.53 17-APR-15:10 47.71 02-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 80.02 29-MAY-16:00 11.55 10-MAY-15:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 70.33 10-JUN-16:00 3.97 05-JUN-15:00
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 94.53 29-JUL-16:00 3.98 14-JUL-17:40
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 73.38 21-AUG-16:00 7.33 28-AUG-13:00
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 73.36 20-SEP-16:00 0.00 01-SEP-00:05
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 69.90 14-OCT-16:00 11.54 26-OCT-14:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 53.53 17-NOV-16:10 80.18 27-NOV-07:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 46.69 10-DEC-16:10 97.18 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 37.72   0.00  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 94.53   118.92  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 37.72 01-JAN-11:00 85.02 25-JAN-07:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 44.37 11-FEB-16:10 118.91 04-FEB-07:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 55.05 13-MAR-16:00 105.26 16-MAR-07:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 72.52 17-APR-15:10 47.70 02-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 80.01 29-MAY-16:00 11.55 10-MAY-15:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 70.33 10-JUN-16:00 3.97 05-JUN-15:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 94.53 29-JUL-16:00 3.98 14-JUL-17:40
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 73.38 21-AUG-16:00 7.16 28-AUG-13:00
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 73.35 20-SEP-16:00 0.00 01-SEP-00:05
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 69.89 14-OCT-16:00 11.54 26-OCT-14:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 53.53 17-NOV-16:08 80.17 27-NOV-07:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 46.69 10-DEC-16:08 97.17 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 37.72   0.00  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 94.53   118.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 76.99 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 10.40 02-JAN-14:00 27.36 25-JAN-07:30
February 0.00 01-FEB-00:10 76.99 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 11.33 11-FEB-14:00 34.11 04-FEB-07:00
March 0.00 01-MAR-00:10 76.99 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 11.22 13-MAR-16:00 32.58 16-MAR-07:00
April 0.00 01-APR-00:10 76.99 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 16.28 17-APR-15:00 17.43 02-APR-05:30
May 0.00 01-MAY-00:10 76.99 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 20.24 22-MAY-13:00 5.01 07-MAY-05:00
June 0.00 01-JUN-00:10 76.99 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 16.40 11-JUN-13:00 1.11 05-JUN-15:00
July 0.00 01-JUL-00:10 76.99 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 22.32 29-JUL-16:00 1.11 14-JUL-23:10
August 0.00 01-AUG-00:10 76.99 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 19.45 23-AUG-13:00 2.27 28-AUG-12:00
September 0.00 01-SEP-00:10 76.99 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 16.36 13-SEP-13:00 2.25 05-SEP-06:00
October 0.00 01-OCT-00:10 76.99 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 16.36 09-OCT-11:00 4.12 28-OCT-03:00
November 0.00 01-NOV-00:10 76.99 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 12.36 17-NOV-15:00 26.29 27-NOV-07:00
December 0.00 01-DEC-00:10 76.99 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 10.31 10-DEC-14:00 30.78 15-DEC-07:20
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   76.99   232.19   0.00 0.00 0.00 0.00 10.31   1.11  
Maximum of Months 0.00   76.99   232.19   0.00 0.00 0.00 0.00 22.32   34.11  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 77.01 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 12.49 02-JAN-14:00 23.73 25-JAN-07:00
February 180.00 01-FEB-00:10 77.01 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 12.38 11-FEB-16:08 33.19 04-FEB-07:00
March 180.00 01-MAR-00:10 77.01 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 15.37 13-MAR-16:00 29.38 16-MAR-07:00
April 180.00 01-APR-00:10 77.01 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 20.24 17-APR-15:10 13.31 02-APR-06:00
May 180.00 01-MAY-00:10 77.01 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 22.33 29-MAY-16:00 2.86 10-MAY-15:00
June 180.00 01-JUN-00:10 77.01 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 19.63 10-JUN-15:50 0.65 05-JUN-15:00
July 180.00 01-JUL-00:10 77.01 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 26.38 29-JUL-16:00 0.91 14-JUL-18:00
August 180.00 01-AUG-00:10 77.01 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 20.48 21-AUG-16:00 0.73 05-AUG-18:00
September 180.00 01-SEP-00:10 77.01 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 20.47 20-SEP-16:00 0.00 01-SEP-00:05
October 180.00 01-OCT-00:10 77.01 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 19.51 14-OCT-16:00 1.84 01-OCT-08:00
November 180.00 01-NOV-00:10 77.01 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 14.94 17-NOV-16:10 22.38 27-NOV-07:00
December 180.00 01-DEC-00:10 77.01 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 13.03 10-DEC-16:08 27.12 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 12.38   0.00  
Maximum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 26.38   33.19  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 37.72 01-JAN-11:00 86.33 25-JAN-09:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 44.37 11-FEB-16:10 118.91 04-FEB-07:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 55.05 13-MAR-16:00 105.27 16-MAR-07:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 72.53 17-APR-15:10 47.71 02-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 80.02 29-MAY-16:00 11.55 10-MAY-15:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 70.33 10-JUN-16:00 3.97 05-JUN-15:00
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 94.54 29-JUL-16:00 3.98 14-JUL-17:40
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 73.39 21-AUG-16:00 7.52 28-AUG-13:00
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 73.36 20-SEP-16:00 0.00 01-SEP-00:05
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 69.90 14-OCT-16:00 11.54 26-OCT-14:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 53.53 17-NOV-16:10 80.18 27-NOV-07:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 46.69 10-DEC-16:10 97.18 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 37.72   0.00  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 94.54   118.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 37.72 01-JAN-11:00 85.02 25-JAN-07:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 44.37 11-FEB-16:10 118.91 04-FEB-07:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 55.05 13-MAR-16:00 105.26 16-MAR-07:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 72.52 17-APR-15:10 47.70 02-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 80.01 29-MAY-16:00 11.55 10-MAY-15:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 70.33 10-JUN-16:00 3.97 05-JUN-15:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 94.53 29-JUL-16:00 3.98 14-JUL-17:40
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 73.38 21-AUG-16:00 7.35 28-AUG-13:00
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 73.35 20-SEP-16:00 0.00 01-SEP-00:05
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 69.89 14-OCT-16:00 11.54 26-OCT-14:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 53.53 17-NOV-16:10 80.17 27-NOV-07:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 46.69 10-DEC-16:10 97.17 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 37.72   0.00  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 94.53   118.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 2240.78 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 43.89 02-JAN-14:00 114.26 25-JAN-05:20
February 2263.36 01-FEB-00:10 2240.78 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 48.70 11-FEB-14:00 152.49 04-FEB-07:00
March 2263.36 01-MAR-00:10 2240.78 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 48.56 13-MAR-16:00 140.99 16-MAR-05:00
April 2263.36 01-APR-00:10 2240.78 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 67.23 17-APR-15:00 76.39 02-APR-05:20
May 2263.36 01-MAY-00:10 2240.78 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 84.54 22-MAY-13:00 25.04 07-MAY-06:00
June 2263.36 01-JUN-00:10 2240.78 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 67.16 11-JUN-13:00 7.91 05-JUN-15:00
July 2263.36 01-JUL-00:10 2240.78 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 91.65 29-JUL-16:00 10.38 14-JUL-22:00
August 2263.36 01-AUG-00:10 2240.78 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 79.40 23-AUG-13:00 12.30 12-AUG-07:00
September 2263.36 01-SEP-00:10 2240.78 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 66.52 13-SEP-13:00 13.05 05-SEP-06:00
October 2263.36 01-OCT-23:10 2240.78 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 66.84 09-OCT-10:55 21.82 28-OCT-03:00
November 2263.36 01-NOV-00:10 2240.78 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 51.63 17-NOV-15:00 114.28 27-NOV-03:00
December 2263.36 01-DEC-00:10 2240.78 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 40.78 10-DEC-14:00 132.32 15-DEC-05:20
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   2240.78   0.00 0.00 0.00 0.00 0.00 40.78   7.91  
Maximum of Months 2263.36   2240.78   0.00 0.00 0.00 0.00 0.00 91.65   152.49  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 37.32 01-JAN-11:00 85.47 25-JAN-07:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 43.97 11-FEB-16:10 119.38 04-FEB-07:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 54.67 13-MAR-16:00 105.72 16-MAR-07:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 72.15 17-APR-15:10 48.13 02-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 79.64 29-MAY-16:00 11.96 10-MAY-15:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 69.95 10-JUN-16:00 4.38 05-JUN-15:00
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 94.16 29-JUL-16:00 4.39 14-JUL-17:40
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 73.00 21-AUG-16:00 6.42 28-AUG-13:00
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 72.98 20-SEP-16:00 0.00 01-SEP-00:05
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 69.52 14-OCT-16:00 11.95 26-OCT-14:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 53.14 17-NOV-16:10 80.62 27-NOV-07:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 46.30 10-DEC-16:10 97.63 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 37.32   0.00  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 94.16   119.38  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 37.32 01-JAN-11:00 85.46 25-JAN-07:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 43.97 11-FEB-16:10 119.37 04-FEB-07:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 54.66 13-MAR-16:00 105.71 16-MAR-07:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 72.14 17-APR-15:10 48.13 02-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 79.64 29-MAY-16:00 11.96 10-MAY-15:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 69.94 10-JUN-16:00 4.38 05-JUN-15:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 94.15 29-JUL-16:00 4.39 14-JUL-17:40
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 73.00 21-AUG-16:00 6.24 28-AUG-13:00
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 72.97 20-SEP-16:00 0.00 01-SEP-00:05
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 69.51 14-OCT-16:00 11.95 26-OCT-14:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 53.14 17-NOV-16:08 80.62 27-NOV-07:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 46.30 10-DEC-16:08 97.63 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 37.32   0.00  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 94.15   119.37  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 77.01 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 19.10 01-JAN-11:00 43.73 25-JAN-07:00
February 180.00 01-FEB-00:10 77.01 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 20.84 11-FEB-11:00 61.08 04-FEB-07:00
March 180.00 01-MAR-00:10 77.01 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 27.97 13-MAR-16:00 54.09 16-MAR-07:00
April 180.00 01-APR-00:10 77.01 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 36.90 17-APR-15:10 24.63 02-APR-06:00
May 180.00 01-MAY-00:10 77.01 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 40.75 29-MAY-16:00 6.12 10-MAY-15:00
June 180.00 01-JUN-00:10 77.01 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 35.79 10-JUN-16:00 2.24 05-JUN-15:00
July 180.00 01-JUL-00:10 77.01 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 48.16 29-JUL-16:00 2.24 14-JUL-17:40
August 180.00 01-AUG-00:10 77.01 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 37.35 21-AUG-16:00 2.75 28-AUG-13:00
September 180.00 01-SEP-00:10 77.01 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 37.24 08-SEP-16:00 0.00 01-SEP-00:05
October 180.00 01-OCT-00:10 77.01 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 35.33 14-OCT-16:00 6.12 26-OCT-14:00
November 180.00 01-NOV-00:10 77.01 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 25.53 17-NOV-16:10 41.25 27-NOV-07:00
December 180.00 01-DEC-00:10 77.01 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 21.80 10-DEC-16:10 49.95 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 19.10   0.00  
Maximum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 48.16   61.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3094.06 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 91.84 02-JAN-14:30 259.65 25-JAN-07:00
February 26988.77 01-FEB-00:10 3094.06 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 88.46 11-FEB-14:00 343.35 04-FEB-07:00
March 26988.77 01-MAR-00:10 3094.06 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 86.43 13-MAR-16:00 309.17 16-MAR-06:00
April 26988.77 01-APR-00:10 3094.06 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 130.84 17-APR-15:00 167.31 02-APR-05:10
May 26988.77 01-MAY-00:10 3094.06 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 165.51 22-MAY-13:00 59.21 01-MAY-06:00
June 26988.77 01-JUN-00:10 3094.06 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 131.78 11-JUN-13:00 21.84 05-JUN-15:00
July 26988.77 01-JUL-00:10 3094.06 03-JUL-19:19 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 183.79 29-JUL-16:00 21.92 14-JUL-23:07
August 26988.77 01-AUG-00:10 3094.06 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 158.48 23-AUG-13:00 32.04 12-AUG-09:00
September 26988.77 01-SEP-00:10 3094.06 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 131.93 13-SEP-13:00 31.83 05-SEP-06:00
October 26988.77 01-OCT-23:10 3094.06 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 134.15 09-OCT-10:55 50.45 28-OCT-03:10
November 26988.77 01-NOV-00:10 3094.06 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 98.64 17-NOV-15:00 247.50 27-NOV-07:00
December 26988.77 01-DEC-00:10 3094.06 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 85.85 10-DEC-14:40 289.66 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 85.85   21.84  
Maximum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 183.79   343.35  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3094.06 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 89.64 02-JAN-14:30 259.66 25-JAN-07:00
February 26988.77 01-FEB-00:10 3094.06 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 87.22 11-FEB-14:00 343.36 04-FEB-07:00
March 26988.77 01-MAR-00:10 3094.06 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 86.43 13-MAR-16:00 309.17 16-MAR-06:00
April 26988.77 01-APR-00:10 3094.06 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 130.84 17-APR-15:00 167.31 02-APR-05:10
May 26988.77 01-MAY-00:10 3094.06 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 165.50 22-MAY-13:00 59.21 01-MAY-06:00
June 26988.77 01-JUN-00:10 3094.06 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 131.78 11-JUN-13:00 21.84 05-JUN-15:00
July 26988.77 01-JUL-00:10 3094.06 03-JUL-19:19 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 183.79 29-JUL-16:00 21.92 14-JUL-18:03
August 26988.77 01-AUG-00:10 3094.06 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 158.48 23-AUG-13:00 32.04 12-AUG-09:00
September 26988.77 01-SEP-00:10 3094.06 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 131.41 13-SEP-13:00 31.83 05-SEP-06:00
October 26988.77 01-OCT-23:10 3094.06 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 132.84 09-OCT-10:55 50.45 28-OCT-03:10
November 26988.77 01-NOV-00:10 3094.06 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 96.56 17-NOV-15:00 247.50 27-NOV-07:00
December 26988.77 01-DEC-00:10 3094.06 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 84.10 10-DEC-14:40 289.67 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 84.10   21.84  
Maximum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 183.79   343.36  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1089.83 02-JAN-20:10 14912.86 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 70.93 02-JAN-14:00 232.37 25-JAN-07:00
February 2401.70 01-FEB-00:10 1089.83 01-FEB-20:10 14912.86 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 78.23 11-FEB-14:00 307.30 04-FEB-07:00
March 2401.70 01-MAR-00:10 1089.83 01-MAR-20:10 14912.86 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 77.55 13-MAR-16:00 276.94 16-MAR-07:00
April 2401.70 01-APR-00:10 1089.83 03-APR-19:10 14912.86 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 117.26 17-APR-15:00 149.70 02-APR-06:00
May 2401.70 01-MAY-00:10 1089.83 01-MAY-19:10 14912.86 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 148.30 22-MAY-13:00 52.98 01-MAY-05:10
June 2401.70 01-JUN-00:10 1089.83 01-JUN-19:10 14912.86 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 118.11 11-JUN-13:00 19.42 05-JUN-15:00
July 2401.70 01-JUL-00:10 1089.83 03-JUL-19:10 14912.86 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 164.72 29-JUL-16:00 19.83 14-JUL-18:07
August 2401.70 01-AUG-00:10 1089.83 01-AUG-19:10 14912.86 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 142.02 23-AUG-13:00 28.60 28-AUG-12:30
September 2401.70 01-SEP-00:10 1089.83 01-SEP-19:10 14912.86 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 117.80 20-SEP-16:00 28.44 05-SEP-06:00
October 2401.70 01-OCT-23:10 1089.83 02-OCT-19:10 14912.86 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 117.72 09-OCT-11:00 43.01 28-OCT-03:30
November 2401.70 01-NOV-00:10 1089.83 01-NOV-19:10 14912.86 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 86.35 17-NOV-15:00 221.50 27-NOV-07:00
December 2401.70 01-DEC-00:10 1089.83 01-DEC-20:10 14912.86 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 70.31 10-DEC-14:00 259.25 15-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1089.83   14912.86   22492.83   0.00 0.00 0.00 70.31   19.42  
Maximum of Months 2401.70   1089.83   14912.86   22492.83   0.00 0.00 0.00 164.72   307.30  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 2371.52 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 71.02 02-JAN-14:00 187.01 25-JAN-05:05
February 2395.44 01-FEB-00:10 2371.52 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 76.40 11-FEB-14:00 253.68 04-FEB-07:00
March 2395.44 01-MAR-00:10 2371.52 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 81.26 13-MAR-16:00 233.01 16-MAR-05:00
April 2395.44 01-APR-00:10 2371.52 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 114.62 17-APR-15:00 127.85 02-APR-05:00
May 2395.44 01-MAY-00:10 2371.52 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 145.00 22-MAY-13:00 40.75 07-MAY-06:00
June 2395.44 01-JUN-00:10 2371.52 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 115.45 11-JUN-13:00 17.86 05-JUN-15:00
July 2395.44 01-JUL-00:10 2371.52 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 161.01 29-JUL-16:00 19.24 14-JUL-22:00
August 2395.44 01-AUG-00:10 2371.52 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 138.84 23-AUG-13:00 20.37 12-AUG-07:00
September 2395.44 01-SEP-00:10 2371.52 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 115.13 13-SEP-13:00 19.19 02-SEP-22:00
October 2395.44 01-OCT-23:10 2371.52 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 115.11 09-OCT-10:55 33.13 26-OCT-14:00
November 2395.44 01-NOV-00:10 2371.52 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 84.40 17-NOV-15:00 189.23 27-NOV-03:00
December 2395.44 01-DEC-00:10 2371.52 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 68.66 10-DEC-14:00 217.85 15-DEC-05:05
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   2371.52   0.00 0.00 0.00 0.00 0.00 68.66   17.86  
Maximum of Months 2395.44   2371.52   0.00 0.00 0.00 0.00 0.00 161.01   253.68  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 23272.03 04-JAN-22:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
February 21870.21 01-FEB-22:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
March 19483.82 01-MAR-22:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
April 18385.70 16-APR-10:33 11501.89 14185.53 12775.33 0.00 0.00 0.00 0.00 0.00 0.00
May 18658.85 14-MAY-10:33 11501.89 14185.53 12775.33 0.00 0.00 0.00 0.00 0.00 0.00
June 18849.78 11-JUN-10:33 11501.89 14185.53 12775.33 0.00 0.00 0.00 0.00 0.00 0.00
July 21036.68 13-JUL-21:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
August 23279.64 25-AUG-21:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
September 24192.14 22-SEP-21:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
October 24569.48 31-OCT-21:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
November 24567.19 21-NOV-22:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
December 24379.78 12-DEC-22:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 18385.70   10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24569.48   11501.89 14185.53 12775.33 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3617.49 02-JAN-14:30 259.90 195.67 252.59 0.00 0.00 0.00 0.00 56.93 0.00
February 3540.56 11-FEB-14:10 389.84 195.67 252.59 0.00 0.00 0.00 0.00 60.61 0.00
March 2801.89 04-MAR-11:33 1169.53 587.01 757.77 0.00 0.00 0.00 0.00 35.49 0.00
April 2589.75 13-APR-13:10 259.90 195.67 252.59 0.00 0.00 0.00 0.00 61.78 0.00
May 2386.76 22-MAY-18:03 5457.82 3756.88 3897.11 0.00 0.00 0.00 0.00 73.48 0.00
June 2552.32 29-JUN-18:13 2728.91 1878.44 1948.56 0.00 0.00 0.00 0.00 69.20 0.00
July 2775.54 29-JUL-17:02 6237.50 3756.88 4041.45 0.00 0.00 0.00 0.00 115.72 0.00
August 2781.78 20-AUG-12:00 389.84 234.80 288.68 0.00 0.00 0.00 0.00 94.12 0.00
September 3528.51 30-SEP-13:10 389.84 195.67 252.59 0.00 0.00 0.00 0.00 76.91 0.00
October 3739.75 25-OCT-12:30 259.90 195.67 252.59 0.00 0.00 0.00 0.00 69.04 0.00
November 3808.04 07-NOV-13:20 259.90 195.67 252.59 0.00 0.00 0.00 0.00 45.89 0.00
December 3941.00 09-DEC-12:30 389.84 195.67 252.59 0.00 0.00 0.00 0.00 37.30 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2386.76   259.90 195.67 252.59 0.00 0.00 0.00 0.00 35.49 0.00
Maximum of Months 3941.00   6237.50 3756.88 4041.45 0.00 0.00 0.00 0.00 115.72 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1960.68 13-JAN-22:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 1.80 0.00
February 1938.10 22-FEB-22:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 0.00 21.18
March 2084.98 28-MAR-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 1.82 0.00
April 2227.53 13-APR-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 7.25 0.00
May 2235.10 17-MAY-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 9.50 0.00
June 2305.33 09-JUN-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 24.14 0.00
July 2337.81 28-JUL-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 23.99 0.00
August 2323.47 17-AUG-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 17.11 0.00
September 2307.56 01-SEP-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 21.93 0.00
October 2268.07 06-OCT-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 12.15 0.00
November 2122.62 08-NOV-22:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 7.22 0.00
December 2075.82 08-DEC-22:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 0.00 0.47
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1938.10   1203.84 725.08 752.15 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2337.81   1203.84 725.08 752.15 0.00 0.00 0.00 0.00 24.14 21.18



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1635.92 01-JAN-11:33 286.42 1360.40 1060.35 0.00 0.00 0.00 0.00 35.75 0.00
February 1666.95 11-FEB-11:33 286.42 1133.66 927.81 0.00 0.00 0.00 0.00 48.68 0.00
March 1668.11 05-MAR-11:33 286.42 1360.40 1060.35 0.00 0.00 0.00 0.00 49.20 0.00
April 1919.85 14-APR-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 22.36 0.00
May 2218.40 31-MAY-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 40.34 0.00
June 2454.10 29-JUN-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 51.80 0.00
July 2494.54 28-JUL-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 45.30 0.00
August 2399.69 21-AUG-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 45.45 0.00
September 2396.65 22-SEP-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 45.63 0.00
October 2093.93 03-OCT-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 40.12 0.00
November 1853.40 03-NOV-21:00 254.59 1209.24 795.27 0.00 0.00 0.00 0.00 28.68 0.00
December 1707.14 09-DEC-12:30 95.47 377.89 309.27 0.00 0.00 0.00 0.00 43.62 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1635.92   95.47 377.89 309.27 0.00 0.00 0.00 0.00 22.36 0.00
Maximum of Months 2494.54   286.42 1360.40 1060.35 0.00 0.00 0.00 0.00 51.80 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 792.56 01-JAN-11:33 220.32 227.72 305.88 0.00 0.00 0.00 0.00 20.63 0.00
February 807.65 11-FEB-11:33 220.32 189.77 267.65 0.00 0.00 0.00 0.00 28.09 0.00
March 806.37 05-MAR-11:33 220.32 227.72 305.88 0.00 0.00 0.00 0.00 28.53 0.00
April 851.13 16-APR-10:33 220.32 227.72 305.88 0.00 0.00 0.00 0.00 32.87 0.00
May 872.81 31-MAY-10:33 146.88 189.77 267.65 0.00 0.00 0.00 0.00 52.57 0.00
June 956.43 29-JUN-21:00 195.84 202.41 229.41 0.00 0.00 0.00 0.00 29.88 0.00
July 986.60 28-JUL-21:00 195.84 202.41 229.41 0.00 0.00 0.00 0.00 32.71 0.00
August 933.49 21-AUG-21:00 195.84 202.41 229.41 0.00 0.00 0.00 0.00 26.25 0.00
September 937.91 22-SEP-21:00 195.84 202.41 229.41 0.00 0.00 0.00 0.00 26.35 0.00
October 874.52 09-OCT-10:33 220.32 227.72 305.88 0.00 0.00 0.00 0.00 46.60 0.00
November 828.35 04-NOV-10:33 220.32 189.77 267.65 0.00 0.00 0.00 0.00 28.76 0.00
December 831.23 09-DEC-12:30 73.44 63.26 89.22 0.00 0.00 0.00 0.00 24.86 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 792.56   73.44 63.26 89.22 0.00 0.00 0.00 0.00 20.63 0.00
Maximum of Months 986.60   220.32 227.72 305.88 0.00 0.00 0.00 0.00 52.57 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 37960.95 13-JAN-21:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 5.80 0.00
February 37968.68 17-FEB-21:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 1.51
March 38234.70 27-MAR-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 5.84 0.00
April 38560.68 14-APR-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 30.53 0.00
May 38682.63 31-MAY-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 55.09 0.00
June 38828.79 09-JUN-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 77.89 0.00
July 38927.86 28-JUL-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 61.84 0.00
August 38764.14 31-AUG-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 55.21 0.00
September 38735.58 08-SEP-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 94.49 0.00
October 38577.73 06-OCT-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 39.13 0.00
November 38264.06 03-NOV-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 30.48 0.00
December 38072.77 08-DEC-21:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 5.83 0.00
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 37960.95   705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38927.86   705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 94.49 1.51



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 13132.58 01-JAN-10:30 8538.00 358.25 406.43 0.00 0.00 0.00 0.00 48.09 0.00
February 12441.87 11-FEB-14:00 5122.80 298.55 355.63 0.00 0.00 0.00 0.00 138.63 0.00
March 11089.15 13-MAR-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 25.87 0.00
April 11273.60 14-APR-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 38.85 0.00
May 11538.47 22-MAY-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 94.97 0.00
June 11691.76 02-JUN-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 125.85 0.00
July 11926.40 27-JUL-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 133.08 0.00
August 11881.88 31-AUG-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 97.22 0.00
September 12480.12 08-SEP-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 150.56 0.00
October 13076.04 25-OCT-15:03 51228.00 1791.27 2133.76 0.00 0.00 0.00 0.00 132.83 0.00
November 12668.18 19-NOV-11:00 8538.00 358.25 406.43 0.00 0.00 0.00 0.00 69.98 0.00
December 13485.03 09-DEC-12:30 5122.80 298.55 355.63 0.00 0.00 0.00 0.00 82.48 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 11089.15   5122.80 298.55 355.63 0.00 0.00 0.00 0.00 25.87 0.00
Maximum of Months 13485.03   51228.00 1791.27 2133.76 0.00 0.00 0.00 0.00 150.56 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 39896.53 13-JAN-22:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 23.31 0.00
February 39057.68 17-FEB-22:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 7.58
March 39155.06 27-MAR-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 66.95 0.00
April 40563.34 14-APR-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 110.84 0.00
May 41407.52 22-MAY-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 271.18 0.00
June 42637.11 29-JUN-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 358.75 0.00
July 43196.96 28-JUL-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 386.73 0.00
August 42890.99 21-AUG-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 309.14 0.00
September 43747.03 18-SEP-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 315.74 0.00
October 42638.67 06-OCT-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 198.80 0.00
November 41777.69 03-NOV-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 198.66 0.00
December 40864.19 08-DEC-22:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 1.36
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 39057.68   45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 43747.03   45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 386.73 7.58



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2880.81 02-JAN-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 18.76 0.00
February 2975.51 24-FEB-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 15.29 0.00
March 2940.06 27-MAR-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 33.08 0.00
April 2938.93 14-APR-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 50.63 0.00
May 2948.49 29-MAY-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 66.55 0.00
June 2957.27 28-JUN-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 51.46 0.00
July 2953.13 21-JUL-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 58.11 0.00
August 2945.26 18-AUG-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 58.85 0.00
September 2957.48 30-SEP-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 54.51 0.00
October 2932.30 20-OCT-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 29.72 0.00
November 2935.27 25-NOV-16:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 29.51 0.00
December 2874.64 01-DEC-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 24.71 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2874.64   324.00 205.81 410.90 0.00 0.00 0.00 0.00 15.29 0.00
Maximum of Months 2975.51   583.20 242.57 458.31 0.00 0.00 0.00 0.00 66.55 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2824.51 03-JAN-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 25.56 0.00
February 2963.22 24-FEB-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 16.19 0.00
March 2921.61 28-MAR-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 26.26 0.00
April 2955.46 12-APR-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 35.10 0.00
May 2977.76 13-MAY-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 48.41 0.00
June 2982.40 28-JUN-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 51.48 0.00
July 2985.68 07-JUL-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 56.06 0.00
August 2987.73 21-AUG-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 50.57 0.00
September 2982.85 10-SEP-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 55.19 0.00
October 2958.57 14-OCT-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 53.70 0.00
November 2927.74 07-NOV-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 36.71 0.00
December 2883.00 02-DEC-16:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 19.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2824.51   324.00 205.78 410.85 0.00 0.00 0.00 0.00 16.19 0.00
Maximum of Months 2987.73   583.20 242.54 458.26 0.00 0.00 0.00 0.00 56.06 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 685.38 02-JAN-14:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 10.39 0.00
February 615.62 11-FEB-14:30 0.00 25.41 74.82 0.00 0.00 0.00 0.00 10.31 0.00
March 511.21 02-MAR-14:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 3.09 0.00
April 426.87 15-APR-14:30 0.00 25.41 74.82 0.00 0.00 0.00 0.00 13.88 0.00
May 397.26 22-MAY-17:12 0.00 206.33 526.30 0.00 0.00 0.00 0.00 14.75 0.00
June 401.00 29-JUN-17:12 0.00 206.33 526.30 0.00 0.00 0.00 0.00 13.10 0.00
July 445.75 29-JUL-17:12 0.00 261.77 526.30 0.00 0.00 0.00 0.00 19.56 0.00
August 449.98 20-AUG-13:50 0.00 25.41 74.82 0.00 0.00 0.00 0.00 16.38 0.00
September 586.12 30-SEP-13:40 0.00 25.41 74.82 0.00 0.00 0.00 0.00 14.07 0.00
October 652.89 25-OCT-12:40 0.00 21.56 67.08 0.00 0.00 0.00 0.00 12.34 0.00
November 688.80 07-NOV-13:40 0.00 21.56 67.08 0.00 0.00 0.00 0.00 8.91 0.00
December 693.14 03-DEC-14:00 0.00 25.41 74.82 0.00 0.00 0.00 0.00 1.94 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 397.26   0.00 21.56 67.08 0.00 0.00 0.00 0.00 1.94 0.00
Maximum of Months 693.14   0.00 261.77 526.30 0.00 0.00 0.00 0.00 19.56 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 944.71 06-JAN-19:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 4.21 0.00
February 964.08 17-FEB-19:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 3.93 0.00
March 983.12 13-MAR-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 10.09 0.00
April 1032.55 17-APR-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 13.28 0.00
May 1024.00 20-MAY-08:62 324.00 258.76 959.99 0.00 0.00 0.00 0.00 9.43 0.00
June 1023.09 17-JUN-08:62 324.00 258.76 959.99 0.00 0.00 0.00 0.00 7.58 0.00
July 1022.22 02-JUL-08:62 324.00 258.76 959.99 0.00 0.00 0.00 0.00 9.62 0.00
August 1016.04 19-AUG-18:02 702.00 462.06 758.70 0.00 0.00 0.00 0.00 12.15 0.00
September 1015.76 01-SEP-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 13.07 0.00
October 1000.30 03-OCT-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 11.78 0.00
November 986.51 20-NOV-19:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 6.88 0.00
December 976.33 09-DEC-09:02 324.00 258.76 959.99 0.00 0.00 0.00 0.00 6.85 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 944.71   324.00 258.76 758.70 0.00 0.00 0.00 0.00 3.93 0.00
Maximum of Months 1032.55   831.60 462.06 959.99 0.00 0.00 0.00 0.00 13.28 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2602.60 03-JAN-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 24.99 0.00
February 2665.01 24-FEB-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 15.88 0.00
March 2617.31 31-MAR-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 20.63 0.00
April 2647.32 10-APR-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 30.02 0.00
May 2655.95 20-MAY-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 48.37 0.00
June 2656.09 01-JUN-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 47.94 0.00
July 2676.73 27-JUL-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 76.75 0.00
August 2674.89 20-AUG-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 60.62 0.00
September 2677.29 10-SEP-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 55.08 0.00
October 2665.00 20-OCT-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 29.74 0.00
November 2645.89 06-NOV-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 34.06 0.00
December 2599.90 08-DEC-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 28.20 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2599.90   324.00 205.81 410.90 0.00 0.00 0.00 0.00 15.88 0.00
Maximum of Months 2677.29   583.20 242.57 458.31 0.00 0.00 0.00 0.00 76.75 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2480.36 15-JAN-16:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 14.47 0.00
February 2649.72 24-FEB-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 16.78 0.00
March 2572.03 01-MAR-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 15.70 0.00
April 2689.81 15-APR-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 55.98 0.00
May 2682.05 20-MAY-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 48.43 0.00
June 2675.70 01-JUN-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 47.96 0.00
July 2703.68 27-JUL-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 76.82 0.00
August 2667.22 19-AUG-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 59.19 0.00
September 2652.16 13-SEP-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 56.75 0.00
October 2606.33 24-OCT-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 44.05 0.00
November 2553.08 21-NOV-09:02 216.00 323.38 679.49 0.00 0.00 0.00 0.00 27.00 0.00
December 2512.72 09-DEC-09:02 324.00 411.57 979.73 0.00 0.00 0.00 0.00 23.23 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2480.36   216.00 205.78 410.85 0.00 0.00 0.00 0.00 14.47 0.00
Maximum of Months 2703.68   583.20 411.57 979.73 0.00 0.00 0.00 0.00 76.82 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2340.38 01-JAN-11:33 2263.36 2240.78 0.00 0.00 0.00 0.00 0.00 23.44 0.00
February 2321.40 11-FEB-11:33 2263.36 1867.32 0.00 0.00 0.00 0.00 0.00 35.56 0.00
March 2345.13 04-MAR-11:33 2263.36 1867.32 0.00 0.00 0.00 0.00 0.00 29.93 0.00
April 2479.50 16-APR-10:33 2263.36 2240.78 0.00 0.00 0.00 0.00 0.00 40.75 0.00
May 2621.07 22-MAY-20:10 2011.87 1991.81 0.00 0.00 0.00 0.00 0.00 33.93 0.00
June 2947.48 29-JUN-20:10 2011.87 1991.81 0.00 0.00 0.00 0.00 0.00 39.50 0.00
July 2986.71 28-JUL-20:10 2011.87 1991.81 0.00 0.00 0.00 0.00 0.00 35.97 0.00
August 2989.48 21-AUG-20:10 2011.87 1991.81 0.00 0.00 0.00 0.00 0.00 34.63 0.00
September 3029.96 21-SEP-20:10 2011.87 1991.81 0.00 0.00 0.00 0.00 0.00 39.51 0.00
October 2836.17 25-OCT-20:10 2011.87 1991.81 0.00 0.00 0.00 0.00 0.00 21.70 0.00
November 2553.98 10-NOV-21:10 2011.87 1991.81 0.00 0.00 0.00 0.00 0.00 1.42 0.00
December 2481.96 09-DEC-12:30 754.45 622.44 0.00 0.00 0.00 0.00 0.00 27.92 0.00
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2321.40   754.45 622.44 0.00 0.00 0.00 0.00 0.00 1.42 0.00
Maximum of Months 3029.96   2263.36 2240.78 0.00 0.00 0.00 0.00 0.00 40.75 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2997.75 23-JAN-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 26.85 0.00
February 3102.00 24-FEB-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 15.03 0.00
March 3040.97 25-MAR-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 24.94 0.00
April 3072.91 01-APR-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 33.81 0.00
May 3065.75 16-MAY-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 35.62 0.00
June 3067.84 25-JUN-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 47.06 0.00
July 3084.27 28-JUL-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 61.76 0.00
August 3073.81 02-AUG-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 54.97 0.00
September 3110.24 17-SEP-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 54.29 0.00
October 3042.70 28-OCT-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 37.67 0.00
November 3067.46 07-NOV-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 35.32 0.00
December 2962.80 25-DEC-16:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 21.24 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2962.80   324.00 205.81 410.90 0.00 0.00 0.00 0.00 15.03 0.00
Maximum of Months 3110.24   831.60 654.18 774.39 0.00 0.00 0.00 0.00 61.76 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2957.54 03-JAN-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 25.32 0.00
February 3080.40 24-FEB-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 16.04 0.00
March 3075.93 28-MAR-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 25.94 0.00
April 3089.71 07-APR-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 29.23 0.00
May 3098.07 29-MAY-18:02 702.00 734.94 774.30 0.00 0.00 0.00 0.00 53.36 0.00
June 3100.44 09-JUN-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 47.83 0.00
July 3107.24 28-JUL-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 61.78 0.00
August 3110.06 02-AUG-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 55.09 0.00
September 3099.19 26-SEP-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 54.71 0.00
October 3103.66 05-OCT-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 53.90 0.00
November 3041.90 08-NOV-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 36.12 0.00
December 3033.43 01-DEC-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 24.96 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2957.54   583.20 205.78 410.85 0.00 0.00 0.00 0.00 16.04 0.00
Maximum of Months 3110.06   831.60 734.94 774.30 0.00 0.00 0.00 0.00 61.78 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1444.02 03-JAN-16:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 11.58 0.00
February 1475.66 24-FEB-16:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 6.92 0.00
March 1438.80 04-MAR-16:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 15.74 0.00
April 1455.94 14-APR-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 25.31 0.00
May 1423.48 01-MAY-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 23.90 0.00
June 1433.52 01-JUN-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 24.03 0.00
July 1458.54 27-JUL-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 38.73 0.00
August 1459.22 21-AUG-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 25.19 0.00
September 1449.54 21-SEP-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 27.42 0.00
October 1478.01 24-OCT-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 21.11 0.00
November 1475.35 07-NOV-16:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 17.35 0.00
December 1448.11 08-DEC-16:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 13.19 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1423.48   324.00 129.38 402.58 0.00 0.00 0.00 0.00 6.92 0.00
Maximum of Months 1478.01   583.20 152.48 449.03 0.00 0.00 0.00 0.00 38.73 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 21488.81 13-JAN-23:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 3.32
February 21788.66 17-FEB-23:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 3.35
March 22110.53 27-MAR-22:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 5.03 0.00
April 22739.85 14-APR-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 23.23 0.00
May 23424.39 22-MAY-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 57.58 0.00
June 23731.22 28-JUN-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 78.94 0.00
July 23745.11 27-JUL-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 80.66 0.00
August 23602.90 02-AUG-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 84.28 0.00
September 23655.00 08-SEP-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 94.89 0.00
October 22961.42 03-OCT-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 60.80 0.00
November 22622.70 03-NOV-22:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 42.96 0.00
December 21872.39 08-DEC-23:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 5.02 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 21488.81   26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23745.11   26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 94.89 3.35



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 22795.01 13-JAN-22:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 3.59 0.00
February 23044.12 17-FEB-22:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 3.37
March 23344.45 27-MAR-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 13.37 0.00
April 23912.32 14-APR-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 23.23 0.00
May 24612.89 22-MAY-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 57.54 0.00
June 24890.30 28-JUN-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 78.91 0.00
July 24912.27 27-JUL-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 80.63 0.00
August 24764.22 02-AUG-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 84.25 0.00
September 24835.39 08-SEP-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 94.89 0.00
October 24130.34 03-OCT-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 60.80 0.00
November 23770.19 03-NOV-22:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 42.96 0.00
December 23037.49 08-DEC-23:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 5.02 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 22795.01   26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24912.27   26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 94.89 3.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 29389.92 01-JAN-11:50 800.57 363.28 14912.86 18744.03 0.00 0.00 0.00 31.39 0.00
February 29619.84 11-FEB-11:33 2401.70 908.19 44738.57 56232.08 0.00 0.00 0.00 52.12 0.00
March 29851.45 27-MAR-10:33 1601.14 908.19 44738.57 56232.08 0.00 0.00 0.00 30.43 0.00
April 30569.37 15-APR-10:37 2401.70 908.19 44738.57 56232.08 0.00 0.00 0.00 75.55 0.00
May 30545.75 31-MAY-10:33 1601.14 908.19 44738.57 56232.08 0.00 0.00 0.00 118.55 0.00
June 30758.29 11-JUN-10:50 800.57 363.28 14912.86 18744.03 0.00 0.00 0.00 99.79 0.00
July 30940.07 23-JUL-10:50 800.57 363.28 14912.86 18744.03 0.00 0.00 0.00 123.44 0.00
August 30722.99 19-AUG-10:40 2401.70 908.19 44738.57 56232.08 0.00 0.00 0.00 106.91 0.00
September 30665.49 10-SEP-10:40 2401.70 1089.83 44738.57 56232.08 0.00 0.00 0.00 91.33 0.00
October 30617.63 07-OCT-10:37 2401.70 908.19 44738.57 56232.08 0.00 0.00 0.00 102.26 0.00
November 29578.37 03-NOV-10:33 1601.14 908.19 44738.57 56232.08 0.00 0.00 0.00 59.47 0.00
December 29583.86 09-DEC-11:50 800.57 302.73 14912.86 18744.03 0.00 0.00 0.00 46.00 0.00
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 29389.92   800.57 302.73 14912.86 18744.03 0.00 0.00 0.00 30.43 0.00
Maximum of Months 30940.07   2401.70 1089.83 44738.57 56232.08 0.00 0.00 0.00 123.44 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5074.42 01-JAN-11:33 2395.44 2371.52 0.00 0.00 0.00 0.00 0.00 37.93 0.00
February 5146.66 11-FEB-11:33 2395.44 1976.27 0.00 0.00 0.00 0.00 0.00 56.06 0.00
March 5071.64 04-MAR-11:33 2395.44 1976.27 0.00 0.00 0.00 0.00 0.00 49.82 0.00
April 5790.30 14-APR-15:13 3992.40 1976.27 0.00 0.00 0.00 0.00 0.00 87.25 0.00
May 5947.22 18-MAY-15:03 7984.80 3952.54 0.00 0.00 0.00 0.00 0.00 97.52 0.00
June 6471.57 28-JUN-15:40 1330.80 658.76 0.00 0.00 0.00 0.00 0.00 87.45 0.00
July 7279.13 28-JUL-15:40 1330.80 658.76 0.00 0.00 0.00 0.00 0.00 152.79 0.00
August 6576.83 31-AUG-15:03 7984.80 3952.54 0.00 0.00 0.00 0.00 0.00 114.43 0.00
September 7206.43 09-SEP-13:00 798.48 658.76 0.00 0.00 0.00 0.00 0.00 108.13 0.00
October 6852.91 06-OCT-12:40 532.32 658.76 0.00 0.00 0.00 0.00 0.00 87.17 0.00
November 6020.01 10-NOV-13:40 532.32 658.76 0.00 0.00 0.00 0.00 0.00 60.99 0.00
December 5528.80 09-DEC-12:40 798.48 658.76 0.00 0.00 0.00 0.00 0.00 44.84 0.00
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 5071.64   532.32 658.76 0.00 0.00 0.00 0.00 0.00 37.93 0.00
Maximum of Months 7279.13   7984.80 3952.54 0.00 0.00 0.00 0.00 0.00 152.79 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.560445E+12 386850.80 03-JAN-20:49 0.380928E+12 319315.38 17-JAN-18:10
February 0.536586E+12 407798.00 10-FEB-20:30 0.343073E+12 319181.81 02-FEB-18:10
March 0.614363E+12 410353.87 09-MAR-20:00 0.375255E+12 318154.27 03-MAR-18:00
April 0.647143E+12 406186.44 14-APR-19:19 0.356685E+12 316556.86 04-APR-17:10
May 0.736000E+12 421812.14 22-MAY-19:10 0.362426E+12 314708.39 01-MAY-17:10
June 0.756839E+12 445950.11 29-JUN-19:19 0.346199E+12 312642.39 01-JUN-17:40
July 0.797224E+12 451931.94 27-JUL-19:10 0.355454E+12 311463.77 05-JUL-17:19
August 0.793972E+12 442515.92 21-AUG-19:10 0.357051E+12 312228.34 28-AUG-17:30
September 0.763588E+12 451001.99 08-SEP-19:00 0.349448E+12 314103.90 29-SEP-17:19
October 0.753433E+12 438145.75 03-OCT-19:19 0.367180E+12 316334.20 31-OCT-17:10
November 0.661584E+12 423180.71 21-NOV-20:30 0.361598E+12 318047.33 30-NOV-18:19
December 0.598088E+12 408314.82 07-DEC-20:00 0.378982E+12 321351.58 26-DEC-18:10
             
Annual Sum or Average 0.821926E+13     0.433428E+13    
Minimum of Months 0.536586E+12 386850.80   0.343073E+12 311463.77  
Maximum of Months 0.797224E+12 451931.94   0.380928E+12 321351.58  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.653901E+11 0.231911E+11 0.148212E+12 0.553309E+11 0.482469E+11 0.159055E+11 0.00 0.166788E+12 0.00 0.00 0.243455E+11 0.770461E+10 0.00
February 0.589631E+11 0.200119E+11 0.133859E+12 0.499764E+11 0.443060E+11 0.143513E+11 0.00 0.180856E+12 0.00 0.00 0.224841E+11 0.696213E+10 0.00
March 0.651817E+11 0.208924E+11 0.148223E+12 0.553337E+11 0.494514E+11 0.161932E+11 0.00 0.220638E+12 0.00 0.00 0.254035E+11 0.770313E+10 0.00
April 0.629064E+11 0.189830E+11 0.143397E+12 0.535455E+11 0.499648E+11 0.159798E+11 0.00 0.264677E+12 0.00 0.00 0.250429E+11 0.746505E+10 0.00
May 0.649871E+11 0.185010E+11 0.148223E+12 0.553321E+11 0.542715E+11 0.170106E+11 0.00 0.338097E+12 0.00 0.00 0.265029E+11 0.770436E+10 0.00
June 0.628861E+11 0.173980E+11 0.143446E+12 0.535483E+11 0.548292E+11 0.168980E+11 0.00 0.369417E+12 0.00 0.00 0.257570E+11 0.745691E+10 0.00
July 0.648108E+11 0.181395E+11 0.148174E+12 0.553291E+11 0.577378E+11 0.176265E+11 0.00 0.395738E+12 0.00 0.00 0.266108E+11 0.771249E+10 0.00
August 0.650601E+11 0.191220E+11 0.148234E+12 0.553337E+11 0.571841E+11 0.175584E+11 0.00 0.391804E+12 0.00 0.00 0.265987E+11 0.770437E+10 0.00
September 0.630102E+11 0.196967E+11 0.143408E+12 0.535457E+11 0.564496E+11 0.170200E+11 0.00 0.372030E+12 0.00 0.00 0.257617E+11 0.746634E+10 0.00
October 0.652565E+11 0.216339E+11 0.148201E+12 0.553307E+11 0.567879E+11 0.172078E+11 0.00 0.349417E+12 0.00 0.00 0.265247E+11 0.770295E+10 0.00
November 0.632625E+11 0.220789E+11 0.143462E+12 0.535468E+11 0.515355E+11 0.162147E+11 0.00 0.274185E+12 0.00 0.00 0.246736E+11 0.744901E+10 0.00
December 0.653247E+11 0.234321E+11 0.148174E+12 0.553296E+11 0.494112E+11 0.161250E+11 0.00 0.202601E+12 0.00 0.00 0.246328E+11 0.771263E+10 0.00
                           
Annual Sum or Average 0.767039E+12 0.243081E+12 0.174501E+13 0.651482E+12 0.630176E+12 0.198091E+12 0.00 0.352625E+13 0.00 0.00 0.304338E+12 0.907440E+11 0.00
Minimum of Months 0.589631E+11 0.173980E+11 0.133859E+12 0.499764E+11 0.443060E+11 0.143513E+11 0.00 0.166788E+12 0.00 0.00 0.224841E+11 0.696213E+10 0.00
Maximum of Months 0.653901E+11 0.234321E+11 0.148234E+12 0.553337E+11 0.577378E+11 0.176265E+11 0.00 0.395738E+12 0.00 0.00 0.266108E+11 0.771263E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.109856E+10 0.00 0.227912E+12 0.00 0.00
February 0.137204E+12 0.00 0.116679E+10 0.00 0.204702E+12 0.00 0.00
March 0.152024E+12 0.00 0.634443E+09 0.00 0.222597E+12 0.00 0.00
April 0.146956E+12 0.00 0.103501E+09 0.00 0.209625E+12 0.00 0.00
May 0.151978E+12 0.00 45795078.00 0.00 0.210402E+12 0.00 0.00
June 0.147114E+12 0.00 34393398.07 0.00 0.199050E+12 0.00 0.00
July 0.151820E+12 0.00 35557885.43 0.00 0.203598E+12 0.00 0.00
August 0.152039E+12 0.00 41631344.82 0.00 0.204971E+12 0.00 0.00
September 0.146971E+12 0.00 27258380.60 0.00 0.202450E+12 0.00 0.00
October 0.151903E+12 0.00 0.116322E+09 0.00 0.215160E+12 0.00 0.00
November 0.147091E+12 0.00 0.298483E+09 0.00 0.214208E+12 0.00 0.00
December 0.151820E+12 0.00 0.115098E+10 0.00 0.226011E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.475371E+10 0.00 0.254069E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 27258380.60 0.00 0.199050E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.116679E+10 0.00 0.227912E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 62892.57 02-JAN-20:10 15448.40 01-JAN-00:10 89475.41 02-JAN-07:10 39726.11 02-JAN-07:19 36457.25 13-JAN-22:10 7061.45 03-JAN-21:00 0.00 01-JAN-00:10
February 62892.57 01-FEB-20:10 15448.40 01-FEB-00:10 89475.41 01-FEB-07:10 39726.11 01-FEB-07:19 35017.49 17-FEB-22:10 7297.00 11-FEB-19:00 0.00 01-FEB-00:10
March 62892.57 01-MAR-20:10 15448.40 01-MAR-00:10 89475.41 01-MAR-07:10 39726.11 13-MAR-06:19 33132.51 30-MAR-21:10 7441.55 09-MAR-20:00 0.00 01-MAR-00:10
April 62892.57 03-APR-19:10 15448.40 01-APR-00:10 89475.41 03-APR-06:10 39726.11 03-APR-06:19 35751.81 14-APR-21:10 7109.29 13-APR-18:19 0.00 01-APR-00:10
May 62892.57 01-MAY-19:10 15448.40 01-MAY-00:10 89475.41 01-MAY-06:10 39725.51 25-MAY-06:19 36935.89 22-MAY-21:10 7686.18 24-MAY-19:10 0.00 01-MAY-00:10
June 62892.57 01-JUN-19:10 15448.40 01-JUN-00:10 89475.41 01-JUN-06:10 39725.83 15-JUN-06:19 38770.73 29-JUN-21:10 7692.57 21-JUN-19:10 0.00 01-JUN-00:10
July 62892.57 03-JUL-19:19 15448.40 01-JUL-00:10 89475.41 03-JUL-06:10 39725.51 13-JUL-06:19 40229.04 27-JUL-21:10 8018.71 27-JUL-18:10 0.00 01-JUL-00:10
August 62892.57 01-AUG-19:10 15448.40 01-AUG-00:10 89475.41 01-AUG-06:10 39726.11 21-AUG-06:19 41161.64 21-AUG-21:10 7637.95 21-AUG-18:19 0.00 01-AUG-00:10
September 62892.57 01-SEP-19:10 15448.40 01-SEP-00:10 89475.41 01-SEP-06:10 39726.11 01-SEP-06:19 42569.67 21-SEP-21:10 8011.23 25-SEP-20:00 0.00 01-SEP-00:10
October 62892.57 02-OCT-19:10 15448.40 01-OCT-00:10 89475.41 02-OCT-06:10 39726.11 02-OCT-06:19 41316.38 06-OCT-21:19 7446.01 03-OCT-19:00 0.00 01-OCT-00:10
November 62892.57 01-NOV-19:10 15448.40 01-NOV-00:10 89475.41 01-NOV-06:10 39726.11 01-NOV-06:19 39664.60 03-NOV-21:10 7705.92 21-NOV-20:49 0.00 01-NOV-00:10
December 62892.57 01-DEC-20:10 15448.40 01-DEC-00:10 89475.41 01-DEC-07:10 39726.11 05-DEC-07:19 38036.40 08-DEC-22:10 7542.01 25-DEC-20:00 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 62892.57   15448.40   89475.41   39725.51   33132.51   7061.45   0.00  
Maximum of Months 62892.57   15448.40   89475.41   39726.11   42569.67   8018.71   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 149938.87 02-JAN-13:00 0.00 0.00 9938.94 01-JAN-09:30 4738.64 23-JAN-19:10 0.00
February 158728.01 10-FEB-21:00 0.00 0.00 9938.94 01-FEB-09:20 4738.58 22-FEB-19:10 0.00
March 160452.94 09-MAR-20:00 0.00 0.00 9938.94 01-MAR-02:49 4738.54 16-MAR-18:10 0.00
April 177036.45 14-APR-15:20 0.00 0.00 9938.94 01-APR-00:10 4738.24 03-APR-06:10 0.00
May 186637.28 29-MAY-18:10 0.00 0.00 9938.94 01-MAY-00:10 4738.24 01-MAY-06:10 0.00
June 198506.34 08-JUN-18:10 0.00 0.00 9938.94 01-JUN-00:10 4738.37 29-JUN-18:10 0.00
July 218650.81 27-JUL-18:10 0.00 0.00 9938.94 01-JUL-00:10 4737.69 21-JUL-18:00 0.00
August 203467.63 21-AUG-15:00 0.00 0.00 9938.94 01-AUG-00:10 4737.79 24-AUG-18:10 0.00
September 208865.10 18-SEP-18:10 0.00 0.00 9938.94 01-SEP-00:10 4737.66 22-SEP-18:00 0.00
October 191232.53 03-OCT-15:20 0.00 0.00 9938.94 01-OCT-00:10 4738.30 11-OCT-18:19 0.00
November 171275.86 21-NOV-21:30 0.00 0.00 9938.94 01-NOV-00:10 4738.72 08-NOV-19:10 0.00
December 167438.37 25-DEC-21:00 0.00 0.00 9938.94 01-DEC-00:20 4738.31 20-DEC-07:10 0.00
                   
Annual Sum or Average     0.00 0.00         0.00
Minimum of Months 149938.87   0.00 0.00 9938.94   4737.66   0.00
Maximum of Months 218650.81   0.00 0.00 9938.94   4738.72   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 386850.80 03-JAN-20:49 62892.57 88772.42 15448.40 32159.77 29097.03 7057.55 0.00 135820.99 0.00
February 407798.00 10-FEB-20:30 62892.57 88772.42 15448.40 32159.77 28342.90 7243.58 0.00 157211.85 0.00
March 410353.87 09-MAR-20:00 62892.57 88772.42 15448.40 32159.77 27207.20 7441.55 0.00 160452.94 0.00
April 406186.44 14-APR-19:19 62892.57 88772.42 15448.40 32159.77 30775.40 6881.64 0.00 153400.33 0.00
May 421812.14 22-MAY-19:10 62892.57 88772.42 15448.40 32151.31 28722.96 7135.73 0.00 170358.87 0.00
June 445950.11 29-JUN-19:19 62892.57 88772.42 15448.40 32159.27 31129.23 7552.68 0.00 191911.69 0.00
July 451931.94 27-JUL-19:10 62892.57 88772.42 15448.40 32150.62 30541.28 7774.12 0.00 198228.76 0.00
August 442515.92 21-AUG-19:10 62892.57 88772.42 15448.40 32151.31 31189.58 7566.38 0.00 188133.93 0.00
September 451001.99 08-SEP-19:00 62892.57 88772.42 15448.40 32159.77 35249.30 7413.89 0.00 193318.65 0.00
October 438145.75 03-OCT-19:19 62892.57 88772.42 15448.40 32159.77 34310.04 7373.86 0.00 181479.85 0.00
November 423180.71 21-NOV-20:30 62892.57 88772.42 15448.40 32159.77 31498.75 7670.21 0.00 169155.48 0.00
December 408314.82 07-DEC-20:00 62892.57 88772.42 15448.40 32159.77 29281.14 7442.88 0.00 156339.45 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 386850.80   62892.57 88772.42 15448.40 32150.62 27207.20 6881.64 0.00 135820.99 0.00
Maximum of Months 451931.94   62892.57 88772.42 15448.40 32159.77 35249.30 7774.12 0.00 198228.76 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 20647.24 24-JAN-23:10 0.00 219704.57 17-JAN-21:19 0.00
February 104248.32 01-FEB-18:10 0.00 24733.76 04-FEB-05:00 0.00 218926.52 01-FEB-21:49 0.00
March 104248.32 01-MAR-18:10 0.00 15747.56 16-MAR-08:09 0.00 214555.86 01-MAR-21:30 0.00
April 104248.32 01-APR-17:10 0.00 6801.44 21-APR-08:09 0.00 212757.39 03-APR-20:19 0.00
May 104248.32 01-MAY-17:10 0.00 5373.06 01-MAY-08:09 0.00 210816.77 01-MAY-20:49 0.00
June 104248.32 01-JUN-17:10 0.00 4654.59 13-JUN-08:09 0.00 208780.95 01-JUN-20:30 0.00
July 104248.32 01-JUL-17:10 0.00 3418.04 07-JUL-08:09 0.00 207537.40 03-JUL-20:30 0.00
August 104248.32 01-AUG-17:10 0.00 5487.30 28-AUG-08:09 0.00 208482.99 31-AUG-20:00 0.00
September 104248.32 01-SEP-17:10 0.00 3684.53 15-SEP-08:09 0.00 210255.44 29-SEP-20:19 0.00
October 104248.32 02-OCT-17:10 0.00 6795.65 18-OCT-08:09 0.00 212463.63 31-OCT-20:00 0.00
November 104248.32 01-NOV-17:10 0.00 5968.04 12-NOV-09:09 0.00 214280.75 30-NOV-21:30 0.00
December 104248.32 01-DEC-18:10 0.00 21675.73 20-DEC-23:10 0.00 217456.75 31-DEC-22:19 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 3418.04   0.00 207537.40   0.00
Maximum of Months 104248.32   0.00 24733.76   0.00 219704.57   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.83 21.86 0.83 21.86
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 21.70 0.33 21.70
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.50 21.75 0.50 21.75
August 0.00 0.00 0.00 0.00 0.83 21.69 0.83 21.69
September 0.00 0.00 0.00 0.00 1.17 21.73 1.17 21.73
October 0.00 0.00 0.00 0.00 1.33 21.75 1.33 21.75
November 0.00 0.00 0.00 0.00 0.33 21.80 0.33 21.80
December 0.00 0.00 0.00 0.00 0.33 21.69 0.33 21.69
                 
Annual Sum or Average 0.00   0.00   5.67 21.75 5.67 21.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.33 21.86 1.33 21.86



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.50 21.72 0.50 21.72
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.67 21.71 0.67 21.71
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.50 21.72 0.50 21.72



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 2.50 21.70 2.50 21.70
June 0.00 0.00 0.00 0.00 5.83 21.72 5.83 21.72
July 0.00 0.00 0.00 0.00 8.50 21.73 8.50 21.73
August 0.00 0.00 0.00 0.00 4.00 21.72 4.00 21.72
September 0.00 0.00 0.00 0.00 3.17 21.71 3.17 21.71
October 0.00 0.00 0.00 0.00 0.17 21.67 0.17 21.67
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   24.17 21.72 24.17 21.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 8.50 21.73 8.50 21.73



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
February 0.00 0.00 0.00 0.00 0.33 21.78 0.33 21.78
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 21.70 0.33 21.70
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.33 21.68 0.33 21.68
July 0.00 0.00 0.00 0.00 0.50 21.70 0.50 21.70
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.17 21.67 0.17 21.67
November 0.00 0.00 0.00 0.00 0.33 21.70 0.33 21.70
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.17 21.70 2.17 21.70
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.50 21.78 0.50 21.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 21.68 0.33 21.68
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.50 21.69 0.50 21.69
July 0.00 0.00 0.00 0.00 0.67 21.69 0.67 21.69
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1.67 21.69 1.67 21.69
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.67 21.69 0.67 21.69



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 1.00 21.86 1.00 21.86
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 21.73 0.67 21.73
May 0.00 0.00 0.00 0.00 0.67 21.68 0.67 21.68
June 0.00 0.00 0.00 0.00 0.33 21.70 0.33 21.70
July 0.00 0.00 0.00 0.00 1.00 21.76 1.00 21.76
August 0.00 0.00 0.00 0.00 1.17 21.74 1.17 21.74
September 0.00 0.00 0.00 0.00 1.33 21.78 1.33 21.78
October 0.00 0.00 0.00 0.00 1.50 21.77 1.50 21.77
November 0.00 0.00 0.00 0.00 0.33 21.75 0.33 21.75
December 0.00 0.00 0.00 0.00 0.67 21.70 0.67 21.70
                 
Annual Sum or Average 0.00   0.00   8.67 21.76 8.67 21.76
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.50 21.86 1.50 21.86



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
May 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
June 0.00 0.00 0.00 0.00 0.33 21.70 0.33 21.70
July 0.00 0.00 0.00 0.00 0.83 21.75 0.83 21.75
August 0.00 0.00 0.00 0.00 0.67 21.69 0.67 21.69
September 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.50 21.71 2.50 21.71
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.83 21.75 0.83 21.75



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 6.50 21.91 6.50 21.91
February 0.00 0.00 0.00 0.00 6.50 21.93 6.50 21.93
March 0.00 0.00 0.00 0.00 3.83 21.78 3.83 21.78
April 0.00 0.00 0.00 0.00 2.83 21.76 2.83 21.76
May 0.00 0.00 0.00 0.00 1.83 21.69 1.83 21.69
June 0.00 0.00 0.00 0.00 3.00 21.71 3.00 21.71
July 0.00 0.00 0.00 0.00 5.33 21.75 5.33 21.75
August 0.00 0.00 0.00 0.00 5.83 21.76 5.83 21.76
September 0.00 0.00 0.00 0.00 9.83 21.86 9.83 21.86
October 0.00 0.00 0.00 0.00 13.00 21.95 13.00 21.95
November 0.00 0.00 0.00 0.00 7.50 21.91 7.50 21.91
December 0.00 0.00 0.00 0.00 7.83 21.92 7.83 21.92
                 
Annual Sum or Average 0.00   0.00   73.83 21.86 73.83 21.86
Minimum of Months 0.00 0.00 0.00 0.00 1.83 21.69 1.83 21.69
Maximum of Months 0.00 0.00 0.00 0.00 13.00 21.95 13.00 21.95



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 75.83 23.71 355.33 23.91 0.00 23.91
February 155.50 23.50 249.67 23.72 0.00 23.72
March 397.83 23.16 39.83 23.23 0.00 23.23
April 526.33 23.05 3.50 23.06 0.00 23.06
May 322.50 23.02 42.00 23.13 0.00 23.13
June 270.83 23.07 85.33 23.26 0.00 23.26
July 161.50 23.23 398.17 23.67 0.00 23.67
August 0.83 23.30 488.83 23.95 0.00 23.95
September 0.00 0.00 500.67 23.97 0.00 23.97
October 0.00 0.00 559.17 23.96 0.00 23.96
November 6.50 23.68 518.00 23.95 0.00 23.95
December 17.17 23.77 456.67 23.95 0.00 23.95
             
Annual Sum or Average 1934.83 23.16 3697.17 23.67 0.00 23.67
Minimum of Months 0.00 0.00 3.50 23.06 0.00 23.06
Maximum of Months 526.33 23.77 559.17 23.97 0.00 23.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 383.33 22.29 267.33 22.92 0.00 22.92
February 279.83 22.36 285.17 23.10 0.00 23.10
March 269.17 22.34 344.50 23.15 0.00 23.15
April 179.67 22.68 402.00 23.43 0.00 23.43
May 40.00 22.70 607.00 23.67 0.00 23.67
June 1.33 22.76 686.83 23.78 0.00 23.78
July 0.00 0.00 723.50 23.85 0.00 23.85
August 28.17 22.70 687.00 23.78 0.00 23.78
September 0.50 22.81 683.33 23.87 0.00 23.87
October 9.17 22.74 681.83 23.82 0.00 23.82
November 140.33 22.41 502.50 23.52 0.00 23.52
December 329.17 22.23 335.00 23.04 0.00 23.04
             
Annual Sum or Average 1660.67 22.37 6206.00 23.51 0.00 23.51
Minimum of Months 0.00 0.00 267.33 22.92 0.00 22.92
Maximum of Months 383.33 22.81 723.50 23.87 0.00 23.87



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 362.00 22.92 198.17 23.22 0.00 23.22
February 260.00 22.93 227.33 23.33 0.00 23.33
March 239.50 22.87 306.17 23.40 0.00 23.40
April 118.50 22.91 410.50 23.63 0.00 23.63
May 46.67 22.94 504.17 23.78 0.50 23.78
June 19.33 23.30 523.00 23.86 7.00 23.86
July 4.17 23.55 615.33 23.87 2.67 23.87
August 28.17 23.14 579.00 23.83 6.33 23.83
September 5.33 23.40 606.50 23.85 2.83 23.85
October 18.83 23.54 596.17 23.83 11.83 23.83
November 113.67 22.96 439.33 23.63 0.67 23.63
December 284.83 22.87 282.33 23.33 0.00 23.33
             
Annual Sum or Average 1501.00 22.93 5288.00 23.64 31.83 23.64
Minimum of Months 4.17 22.87 198.17 23.22 0.00 23.22
Maximum of Months 362.00 23.55 615.33 23.87 11.83 23.87



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 709.17 22.64 1.50 22.64 0.00 22.64
February 596.17 22.75 5.67 22.76 0.00 22.76
March 604.17 22.77 18.67 22.80 0.00 22.80
April 438.50 23.07 57.33 23.16 0.00 23.16
May 85.17 23.15 315.50 23.71 0.00 23.71
June 0.00 0.00 544.00 23.88 0.00 23.88
July 0.00 0.00 640.00 23.90 0.00 23.90
August 29.00 23.18 486.17 23.84 0.00 23.84
September 0.00 0.00 517.33 23.87 0.00 23.87
October 53.17 23.23 296.00 23.76 0.00 23.76
November 333.67 22.97 106.17 23.19 0.00 23.19
December 594.83 22.69 25.83 22.74 0.00 22.74
             
Annual Sum or Average 3443.83 22.80 3014.17 23.30 0.00 23.30
Minimum of Months 0.00 0.00 1.50 22.64 0.00 22.64
Maximum of Months 709.17 23.23 640.00 23.90 0.00 23.90



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 743.00 22.56 0.00 22.56 0.00 22.56
February 664.00 22.70 0.00 22.70 0.00 22.70
March 717.17 22.75 0.00 22.75 0.00 22.75
April 600.67 23.06 2.83 23.07 0.00 23.07
May 163.33 23.19 145.50 23.48 0.00 23.48
June 1.83 23.29 438.33 23.86 0.00 23.86
July 0.00 0.00 581.50 23.89 0.00 23.89
August 55.00 23.21 358.67 23.78 0.00 23.78
September 3.33 23.29 402.33 23.85 0.00 23.85
October 120.50 23.27 99.50 23.51 0.00 23.51
November 467.83 22.99 5.50 23.00 0.00 23.00
December 674.83 22.66 0.00 22.66 0.00 22.66
             
Annual Sum or Average 4211.50 22.81 2034.17 23.15 0.00 23.15
Minimum of Months 0.00 0.00 0.00 22.56 0.00 22.56
Maximum of Months 743.00 23.29 581.50 23.89 0.00 23.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 301.17 23.71 670.83 23.28 274.00 23.43
February 270.50 23.78 614.67 23.29 253.17 23.44
March 301.33 23.80 685.17 23.28 283.33 23.43
April 294.67 23.95 697.50 23.26 292.83 23.42
May 313.50 23.96 737.67 23.25 313.50 23.41
June 305.00 23.96 719.00 23.24 305.00 23.41
July 317.17 23.95 743.83 23.24 317.17 23.40
August 313.17 23.96 739.67 23.24 313.17 23.40
September 304.33 23.96 719.33 23.24 304.33 23.40
October 311.00 23.96 734.50 23.24 311.00 23.41
November 293.00 23.91 686.50 23.28 287.33 23.43
December 302.17 23.80 684.33 23.27 284.67 23.43
             
Annual Sum or Average 3627.00 23.89 8433.00 23.26 3539.50 23.42
Minimum of Months 270.50 23.71 614.67 23.24 253.17 23.40
Maximum of Months 317.17 23.96 743.83 23.29 317.17 23.44



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 265.33 23.62 577.67 23.79 193.50 23.81
February 221.17 23.72 564.00 23.82 172.00 23.84
March 276.33 23.64 605.50 23.76 209.50 23.80
April 274.00 23.90 664.67 23.82 263.33 23.85
May 305.67 23.97 731.83 23.81 305.17 23.84
June 279.00 23.98 716.33 23.82 278.83 23.85
July 285.83 23.98 743.33 23.88 285.83 23.90
August 297.67 23.94 726.50 23.87 290.50 23.89
September 273.00 23.98 720.00 23.92 273.00 23.94
October 292.67 23.98 736.67 23.94 292.67 23.95
November 278.33 23.86 668.00 23.89 247.83 23.91
December 298.67 23.65 625.83 23.80 238.00 23.82
             
Annual Sum or Average 3347.67 23.85 8080.33 23.84 3050.17 23.87
Minimum of Months 221.17 23.62 564.00 23.76 172.00 23.80
Maximum of Months 305.67 23.98 743.33 23.94 305.17 23.95



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 257.67 23.66 478.67 23.78 159.33 23.81
February 212.33 23.69 466.33 23.79 141.00 23.82
March 262.00 23.62 510.83 23.76 173.67 23.80
April 244.00 23.85 577.67 23.83 214.17 23.86
May 254.33 23.98 645.00 23.86 252.33 23.89
June 229.50 24.00 662.17 23.86 229.50 23.89
July 232.33 24.00 714.17 23.87 232.33 23.89
August 241.83 23.99 700.83 23.86 239.83 23.89
September 222.67 24.00 711.00 23.89 222.67 23.91
October 239.67 23.99 730.33 23.90 239.67 23.92
November 228.33 23.90 630.83 23.87 203.33 23.89
December 271.83 23.70 554.33 23.80 197.67 23.83
             
Annual Sum or Average 2896.50 23.86 7382.17 23.84 2505.50 23.87
Minimum of Months 212.33 23.62 466.33 23.76 141.00 23.80
Maximum of Months 271.83 24.00 730.33 23.90 252.33 23.92



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 698.33 21.50 1.50 21.50 1.17 21.51
February 616.17 21.49 5.67 21.50 2.83 21.50
March 666.83 21.46 3.83 21.46 3.17 21.47
April 622.50 21.45 7.83 21.48 0.00 21.48
May 613.83 21.38 7.50 21.41 0.33 21.41
June 584.83 21.36 9.17 21.39 0.00 21.39
July 589.17 21.32 18.50 21.38 0.00 21.38
August 600.17 21.35 20.67 21.41 0.50 21.42
September 573.00 21.32 21.17 21.40 0.00 21.40
October 601.00 21.35 22.00 21.42 0.67 21.42
November 620.00 21.43 7.17 21.45 0.50 21.45
December 675.83 21.45 11.00 21.48 1.50 21.48
             
Annual Sum or Average 7461.67 21.41 136.00 21.44 10.67 21.44
Minimum of Months 573.00 21.32 1.50 21.38 0.00 21.38
Maximum of Months 698.33 21.50 22.00 21.50 3.17 21.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 730.50 21.44 2.33 21.44 2.33 21.44
February 645.33 21.48 5.83 21.48 5.83 21.48
March 691.00 21.46 3.17 21.46 3.17 21.46
April 639.67 21.49 4.17 21.50 0.00 21.50
May 616.50 21.39 8.17 21.42 0.83 21.42
June 582.17 21.36 10.50 21.39 0.00 21.39
July 588.33 21.32 20.17 21.39 0.00 21.39
August 605.17 21.36 14.50 21.41 0.50 21.41
September 586.00 21.36 7.50 21.38 0.00 21.38
October 638.83 21.45 1.17 21.45 0.33 21.45
November 655.67 21.47 0.67 21.47 0.67 21.48
December 707.50 21.42 1.33 21.42 1.33 21.42
             
Annual Sum or Average 7686.67 21.42 79.50 21.44 15.00 21.44
Minimum of Months 582.17 21.32 0.67 21.38 0.00 21.38
Maximum of Months 730.50 21.49 20.17 21.50 5.83 21.50



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.28 2.50 21.28 2.50 21.29
February 672.00 21.35 2.50 21.35 2.50 21.36
March 744.00 21.38 7.33 21.39 7.33 21.39
April 720.00 21.50 0.00 21.50 0.00 21.50
May 744.00 21.60 1.50 21.60 1.50 21.60
June 720.00 21.64 1.50 21.64 1.50 21.64
July 744.00 21.66 0.17 21.66 0.17 21.66
August 744.00 21.62 0.67 21.62 0.67 21.62
September 720.00 21.61 0.00 21.61 0.00 21.61
October 744.00 21.54 1.00 21.54 1.00 21.54
November 720.00 21.43 0.83 21.43 0.83 21.43
December 744.00 21.32 2.33 21.32 2.33 21.32
             
Annual Sum or Average 8760.00 21.49 20.33 21.50 20.33 21.50
Minimum of Months 672.00 21.28 0.00 21.28 0.00 21.29
Maximum of Months 744.00 21.66 7.33 21.66 7.33 21.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 694.17 21.54 1.00 21.54 0.83 21.54
February 603.50 21.50 2.33 21.50 2.33 21.50
March 647.83 21.46 2.67 21.47 2.33 21.47
April 590.17 21.39 0.50 21.39 0.00 21.39
May 580.17 21.29 0.83 21.29 0.83 21.30
June 549.00 21.25 0.00 21.25 0.00 21.25
July 558.17 21.23 0.67 21.23 0.00 21.23
August 577.33 21.28 0.50 21.28 0.50 21.29
September 549.33 21.26 0.67 21.26 0.00 21.26
October 582.00 21.30 0.50 21.30 0.33 21.30
November 609.17 21.42 1.17 21.42 0.50 21.42
December 679.00 21.47 1.33 21.48 1.33 21.48
             
Annual Sum or Average 7219.83 21.37 12.17 21.38 9.00 21.38
Minimum of Months 549.00 21.23 0.00 21.23 0.00 21.23
Maximum of Months 694.17 21.54 2.67 21.54 2.33 21.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 737.83 21.51 1.50 21.51 1.50 21.52
February 663.17 21.60 4.17 21.60 4.17 21.60
March 683.83 21.52 2.17 21.53 2.17 21.53
April 597.17 21.40 0.33 21.40 0.00 21.40
May 579.50 21.29 1.00 21.29 1.00 21.30
June 546.17 21.25 0.67 21.25 0.00 21.25
July 556.00 21.22 1.00 21.22 0.00 21.22
August 579.00 21.29 0.50 21.29 0.50 21.29
September 555.50 21.27 0.00 21.27 0.00 21.27
October 602.17 21.36 0.17 21.36 0.17 21.36
November 652.17 21.50 0.67 21.50 0.67 21.50
December 725.83 21.46 1.33 21.47 1.33 21.47
             
Annual Sum or Average 7478.33 21.40 13.50 21.40 11.50 21.40
Minimum of Months 546.17 21.22 0.00 21.22 0.00 21.22
Maximum of Months 737.83 21.60 4.17 21.60 4.17 21.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 682.83 22.93 26.33 22.94 24.50 22.95
February 644.83 23.03 14.17 23.03 14.17 23.04
March 606.67 23.07 45.17 23.09 37.67 23.11
April 365.50 23.37 115.67 23.46 56.83 23.47
May 159.83 23.56 307.83 23.75 100.67 23.75
June 116.50 23.88 490.50 23.91 116.50 23.90
July 107.67 23.92 604.67 23.93 107.67 23.93
August 120.00 23.87 528.17 23.91 119.33 23.90
September 102.17 23.89 583.00 23.92 102.17 23.92
October 97.67 23.84 558.00 23.89 97.67 23.88
November 325.00 23.31 219.67 23.51 72.00 23.53
December 542.83 22.87 77.00 22.97 36.83 23.00
             
Annual Sum or Average 3871.50 23.19 3570.17 23.52 886.00 23.55
Minimum of Months 97.67 22.87 14.17 22.94 14.17 22.95
Maximum of Months 682.83 23.92 604.67 23.93 119.33 23.93



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 690.67 21.45 10.50 21.45 8.33 21.46
February 608.50 21.44 19.83 21.47 12.33 21.47
March 660.50 21.41 20.00 21.44 11.67 21.45
April 606.00 21.39 20.83 21.46 1.17 21.46
May 602.17 21.34 28.50 21.43 1.00 21.43
June 575.00 21.32 29.50 21.42 0.00 21.42
July 579.33 21.29 55.17 21.47 0.00 21.47
August 594.17 21.33 47.00 21.47 1.17 21.47
September 567.17 21.30 46.00 21.45 0.33 21.45
October 596.00 21.32 46.67 21.47 2.50 21.47
November 616.33 21.39 25.67 21.47 2.67 21.47
December 672.00 21.40 30.83 21.45 13.33 21.45
             
Annual Sum or Average 7367.83 21.37 380.50 21.45 54.50 21.46
Minimum of Months 567.17 21.29 10.50 21.42 0.00 21.42
Maximum of Months 690.67 21.45 55.17 21.47 13.33 21.47



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 727.17 21.38 17.00 21.37 17.00 21.37
February 639.17 21.43 23.17 21.43 21.83 21.42
March 682.17 21.40 19.50 21.40 18.83 21.40
April 623.00 21.43 13.33 21.47 1.50 21.48
May 603.33 21.35 27.83 21.43 1.33 21.44
June 573.00 21.32 31.67 21.43 0.00 21.43
July 578.83 21.29 55.50 21.47 0.00 21.47
August 597.33 21.33 40.00 21.46 1.17 21.46
September 578.00 21.33 30.00 21.42 0.83 21.43
October 625.50 21.39 16.50 21.44 2.83 21.44
November 650.50 21.43 7.33 21.43 7.17 21.43
December 703.00 21.35 18.83 21.35 18.83 21.35
             
Annual Sum or Average 7581.00 21.37 300.67 21.42 91.33 21.42
Minimum of Months 573.00 21.29 7.33 21.35 0.00 21.35
Maximum of Months 727.17 21.43 55.50 21.47 21.83 21.48



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 641.33 21.42 31.00 21.50 4.50 21.50
February 584.50 21.44 15.33 21.49 5.50 21.50
March 663.83 21.47 12.17 21.47 12.17 21.48
April 642.50 21.49 1.50 21.50 1.50 21.50
May 650.17 21.47 1.50 21.48 1.50 21.48
June 616.33 21.45 0.00 21.45 0.00 21.45
July 617.33 21.40 0.17 21.40 0.17 21.40
August 625.33 21.41 1.17 21.42 1.17 21.42
September 582.00 21.36 24.00 21.44 0.00 21.44
October 597.33 21.37 58.17 21.54 2.33 21.54
November 595.83 21.39 39.67 21.51 1.33 21.51
December 636.83 21.40 36.00 21.50 4.50 21.51
             
Annual Sum or Average 7453.33 21.42 220.67 21.47 34.67 21.48
Minimum of Months 582.00 21.36 0.00 21.40 0.00 21.40
Maximum of Months 663.83 21.49 58.17 21.54 12.17 21.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 215.50 23.78 592.33 23.85 165.67 23.87
February 168.00 23.87 567.00 23.88 141.50 23.90
March 203.33 23.83 656.00 23.89 170.50 23.90
April 204.00 24.00 713.33 23.95 204.00 23.96
May 229.67 24.00 744.00 23.97 229.67 23.98
June 214.50 24.00 720.00 23.98 214.50 23.98
July 219.67 24.00 744.00 23.99 219.67 23.99
August 222.83 24.00 744.00 23.97 222.83 23.98
September 216.50 24.00 720.00 23.97 216.50 23.98
October 230.50 24.00 744.00 23.95 230.50 23.96
November 203.67 23.99 679.00 23.92 202.00 23.94
December 234.00 23.86 650.50 23.88 201.33 23.90
             
Annual Sum or Average 2562.17 23.94 8274.17 23.94 2418.67 23.95
Minimum of Months 168.00 23.78 567.00 23.85 141.50 23.87
Maximum of Months 234.00 24.00 744.00 23.99 230.50 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 161.33 23.91 657.00 23.91 145.83 23.92
February 136.50 23.95 606.33 23.93 127.83 23.94
March 167.17 23.90 685.33 23.93 148.83 23.94
April 185.50 24.00 719.50 23.97 185.50 23.97
May 217.83 24.00 744.00 23.98 217.83 23.99
June 203.50 24.00 720.00 23.99 203.50 23.99
July 209.50 24.00 744.00 23.99 209.50 23.99
August 211.17 24.00 744.00 23.99 211.17 23.99
September 205.83 24.00 720.00 23.98 205.83 23.99
October 219.83 24.00 744.00 23.97 219.83 23.98
November 183.33 24.00 693.67 23.95 183.33 23.96
December 187.83 23.95 687.33 23.92 178.83 23.93
             
Annual Sum or Average 2289.33 23.98 8465.17 23.96 2237.83 23.97
Minimum of Months 136.50 23.90 606.33 23.91 127.83 23.92
Maximum of Months 219.83 24.00 744.00 23.99 219.83 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 553.67 23.99 736.50 23.92 553.67 23.94
February 504.83 23.99 664.33 23.93 504.33 23.95
March 567.00 23.99 741.00 23.94 567.00 23.96
April 564.33 23.99 720.00 23.96 564.33 23.97
May 598.50 23.99 744.00 23.97 598.50 23.98
June 594.83 23.99 720.00 23.98 594.83 23.98
July 616.00 23.99 744.00 23.98 616.00 23.99
August 609.67 23.99 744.00 23.98 609.67 23.98
September 592.33 23.99 720.00 23.98 592.33 23.98
October 597.17 23.99 744.00 23.97 597.17 23.98
November 559.33 23.99 718.00 23.95 559.33 23.96
December 562.00 23.99 742.33 23.93 562.00 23.95
             
Annual Sum or Average 6919.67 23.99 8738.17 23.96 6919.17 23.97
Minimum of Months 504.83 23.99 664.33 23.92 504.33 23.94
Maximum of Months 616.00 23.99 744.00 23.98 616.00 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 651.00 22.51 18.33 22.54 0.00 22.54
February 533.00 22.67 23.83 22.72 0.00 22.72
March 452.83 22.66 81.67 22.83 0.00 22.83
April 212.67 23.08 253.83 23.50 0.00 23.50
May 20.33 22.97 570.83 23.83 0.00 23.83
June 0.00 0.00 697.50 23.91 0.00 23.91
July 0.00 0.00 731.83 23.93 0.00 23.93
August 6.33 23.15 677.50 23.90 0.00 23.90
September 0.00 0.00 665.67 23.91 0.00 23.91
October 7.67 23.13 607.83 23.86 0.00 23.86
November 255.33 22.81 291.00 23.35 0.00 23.35
December 515.00 22.45 95.17 22.66 0.00 22.66
             
Annual Sum or Average 2654.17 22.64 4715.00 23.44 0.00 23.44
Minimum of Months 0.00 0.00 18.33 22.54 0.00 22.54
Maximum of Months 651.00 23.15 731.83 23.93 0.00 23.93



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.85154 51.80427 0.41000 8.64536
February 672.00000 23.69002 52.87190 0.37080 8.02107
March 744.00000 23.36207 54.88874 0.29469 6.99270
April 720.00000 23.18517 59.25887 0.27675 6.73391
May 744.00000 23.33101 59.65750 -0.6500 14.08181
June 720.00000 23.41394 59.16309 -0.6210 13.29024
July 744.00000 23.63410 58.20171 -0.5425 11.33433
August 744.00000 23.81078 57.82091 -0.4762 9.85068
September 720.00000 23.86220 57.33415 -0.4550 9.43879
October 744.00000 23.88043 57.41401 0.46338 9.52998
November 720.00000 23.89502 55.71346 0.45418 9.37764
December 744.00000 23.89071 54.28849 0.44061 9.14063
           
Annual Sum or Average 8760.00000 23.65093 56.55026 -0.0050 9.71684
Minimum of Months 672.00000 23.18517 51.80427 -0.6500 6.73391
Maximum of Months 744.00000 23.89502 59.65750 0.46338 14.08181



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.96343 54.43326 0.28750 8.19417
February 672.00000 23.12304 54.50318 0.33155 8.62298
March 744.00000 23.15067 55.57116 0.34250 8.74132
April 720.00000 23.37194 59.03525 0.42709 9.34416
May 744.00000 23.59027 59.97496 -0.4071 8.92840
June 720.00000 23.74516 59.73713 -0.3425 7.69834
July 744.00000 23.83191 59.17062 -0.3013 7.11752
August 744.00000 23.75261 59.80343 -0.3304 7.70741
September 720.00000 23.83033 58.99554 -0.2855 7.10692
October 744.00000 23.77201 59.03587 0.56527 11.95849
November 720.00000 23.47673 57.84823 0.46503 10.53038
December 744.00000 23.06035 57.28642 0.33744 8.84237
           
Annual Sum or Average 8760.00000 23.47378 57.96746 0.08909 8.73429
Minimum of Months 672.00000 22.96343 54.43326 -0.4071 7.10692
Maximum of Months 744.00000 23.83191 59.97496 0.56527 11.95849



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.25835 54.77139 0.30895 7.40546
February 672.00000 23.34304 55.02028 0.33560 7.78812
March 744.00000 23.39013 55.90273 0.35608 8.16550
April 720.00000 23.54822 59.29607 0.42409 9.00718
May 744.00000 23.64548 60.13358 -0.4572 9.68170
June 720.00000 23.70923 59.91595 -0.4307 9.13173
July 744.00000 23.77113 59.44236 -0.4053 8.62770
August 744.00000 23.72052 59.98719 -0.4253 9.03344
September 720.00000 23.76830 59.50073 -0.4071 8.67265
October 744.00000 23.72875 59.73024 0.48168 9.96170
November 720.00000 23.56002 58.44793 0.42152 9.00857
December 744.00000 23.33932 57.46043 0.35053 7.95769
           
Annual Sum or Average 8760.00000 23.56614 58.31686 0.04417 8.70822
Minimum of Months 672.00000 23.25835 54.77139 -0.4572 7.40546
Maximum of Months 744.00000 23.77113 60.13358 0.48168 9.96170



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.90320 51.53216 0.81570 21.60924
February 672.00000 22.90479 52.06403 0.82802 22.03651
March 744.00000 22.90675 53.09367 0.84408 22.60572
April 720.00000 22.90857 57.03835 0.88478 23.84961
May 744.00000 22.92884 57.95341 0.19847 10.90357
June 720.00000 22.94039 57.74197 0.21803 11.01267
July 744.00000 22.93504 57.55195 0.22108 10.96011
August 744.00000 22.92084 57.91937 0.20141 10.94056
September 720.00000 22.93465 57.62064 0.21202 10.92843
October 744.00000 22.91696 57.85857 0.90146 24.39075
November 720.00000 22.92282 56.05499 0.87398 23.49591
December 744.00000 22.88693 54.54388 0.83320 22.13051
           
Annual Sum or Average 8760.00000 22.91749 55.93291 0.58446 17.87774
Minimum of Months 672.00000 22.88693 51.53216 0.19847 10.90357
Maximum of Months 744.00000 22.94039 57.95341 0.90146 24.39075



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.71525 57.98427 0.53556 11.57059
February 672.00000 23.74977 58.33136 0.55118 11.87806
March 744.00000 23.67852 59.56486 0.53647 11.64012
April 720.00000 23.70750 63.18527 0.57543 12.21366
May 744.00000 23.72318 64.13746 -0.2767 6.83408
June 720.00000 23.75039 63.85557 -0.2513 6.52367
July 744.00000 23.83567 63.35211 -0.2137 6.08802
August 744.00000 23.80938 63.71441 -0.2238 6.31540
September 720.00000 23.90177 62.87428 -0.1719 5.82374
October 744.00000 23.91142 62.84017 0.67205 14.62584
November 720.00000 23.85034 61.55255 0.62631 13.62159
December 744.00000 23.73356 60.69805 0.56567 12.24324
           
Annual Sum or Average 8760.00000 23.78058 61.85846 0.24178 9.93672
Minimum of Months 672.00000 23.67852 57.98427 -0.2767 5.82374
Maximum of Months 744.00000 23.91142 64.13746 0.67205 14.62584



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.67513 56.93382 0.44702 9.48487
February 672.00000 23.68782 57.31826 0.45683 9.66364
March 744.00000 23.63456 58.43927 0.45197 9.67207
April 720.00000 23.67673 61.96810 0.49313 10.30204
May 744.00000 23.71915 62.73642 -0.3820 8.31138
June 720.00000 23.75600 62.43481 -0.3603 7.93663
July 744.00000 23.79756 62.05711 -0.3421 7.61475
August 744.00000 23.78030 62.48407 -0.3513 7.77565
September 720.00000 23.84202 61.89993 -0.3252 7.35035
October 744.00000 23.85326 61.99906 0.55684 11.55909
November 720.00000 23.79869 60.62502 0.52201 10.88483
December 744.00000 23.70592 59.57991 0.47769 10.03934
           
Annual Sum or Average 8760.00000 23.74412 60.72292 0.13502 9.21361
Minimum of Months 672.00000 23.63456 56.93382 -0.3820 7.35035
Maximum of Months 744.00000 23.85326 62.73642 0.55684 11.55909



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.61447 55.87816 -0.0976 6.01827
February 672.00000 21.64472 55.31627 -0.0747 6.03026
March 744.00000 21.64962 55.10365 -0.0591 5.97827
April 720.00000 21.70702 56.09123 -0.0097 5.88253
May 744.00000 21.72470 56.03937 -1.0638 30.34642
June 720.00000 21.73028 56.10378 -1.0504 29.74200
July 744.00000 21.73862 55.70602 -1.0311 28.97721
August 744.00000 21.73139 56.15612 -1.0431 29.48365
September 720.00000 21.73321 55.86720 -1.0391 29.36962
October 744.00000 21.72919 55.71554 0.01506 5.87981
November 720.00000 21.69082 56.03145 -0.0290 5.92866
December 744.00000 21.62128 57.72143 -0.0721 5.95500
           
Annual Sum or Average 8760.00000 21.69309 55.98245 -0.4653 15.85844
Minimum of Months 672.00000 21.61447 55.10365 -1.0638 5.87981
Maximum of Months 744.00000 21.73862 57.72143 0.01506 30.34642



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.47094 57.80973 -0.1557 6.13869
February 672.00000 21.55802 56.73929 -0.1153 6.07868
March 744.00000 21.59134 55.87610 -0.0873 6.01761
April 720.00000 21.69749 56.44414 -0.0192 5.84349
May 744.00000 21.72544 56.04380 -1.0637 30.32930
June 720.00000 21.73302 56.00440 -1.0457 29.55053
July 744.00000 21.74016 55.66855 -1.0281 28.85246
August 744.00000 21.73005 56.27525 -1.0480 29.66068
September 720.00000 21.72650 56.34074 -1.0556 29.99627
October 744.00000 21.71181 56.73542 -0.0056 5.80406
November 720.00000 21.63995 57.61686 -0.0594 5.87036
December 744.00000 21.50918 59.57602 -0.1204 6.00522
           
Annual Sum or Average 8760.00000 21.65310 56.76278 -0.4860 15.90430
Minimum of Months 672.00000 21.47094 55.66855 -1.0637 5.80406
Maximum of Months 744.00000 21.74016 59.57602 -0.0056 30.32930



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.28151 56.91733 -0.2414 6.43937
February 672.00000 21.34985 56.64998 -0.2148 6.23507
March 744.00000 21.38415 56.43282 -0.1989 6.15988
April 720.00000 21.49612 57.53408 -0.1478 5.79852
May 744.00000 21.59912 56.54047 -1.2344 37.59147
June 720.00000 21.64080 56.31931 -1.2068 36.37149
July 744.00000 21.66229 56.29623 -1.1962 35.93784
August 744.00000 21.61626 56.60475 -1.2222 37.06567
September 720.00000 21.61085 56.65396 -1.2256 37.23478
October 744.00000 21.53801 57.28947 -0.1304 5.70766
November 720.00000 21.43184 57.54689 -0.1723 5.88069
December 744.00000 21.31963 59.08560 -0.2120 6.16033
           
Annual Sum or Average 8760.00000 21.49483 56.99176 -0.6194 18.95911
Minimum of Months 672.00000 21.28151 56.29623 -1.2344 5.70766
Maximum of Months 744.00000 21.66229 59.08560 -0.1304 37.59147



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.65807 55.46273 -0.0847 6.03184
February 672.00000 21.68429 55.11675 -0.0650 6.02200
March 744.00000 21.70571 54.94097 -0.0470 5.97404
April 720.00000 21.73617 55.84488 -0.0040 5.94149
May 744.00000 21.74085 55.96257 -1.0566 30.11116
June 720.00000 21.74745 55.84957 -1.0312 29.01279
July 744.00000 21.75172 55.53844 -1.0185 28.53092
August 744.00000 21.74201 56.11578 -1.0384 29.35023
September 720.00000 21.74762 55.60287 -1.0254 28.85606
October 744.00000 21.74301 55.70128 0.02122 5.92105
November 720.00000 21.71342 56.11256 -0.0216 5.93083
December 744.00000 21.63597 57.94737 -0.0740 5.93718
           
Annual Sum or Average 8760.00000 21.71725 55.85564 -0.4562 15.69425
Minimum of Months 672.00000 21.63597 54.94097 -1.0566 5.92105
Maximum of Months 744.00000 21.75172 57.94737 0.02122 30.11116



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.52760 56.94928 -0.1420 6.07783
February 672.00000 21.62297 56.15793 -0.1022 6.03863
March 744.00000 21.66862 55.52139 -0.0717 5.96660
April 720.00000 21.73273 56.24701 -0.0117 5.91543
May 744.00000 21.74122 55.99448 -1.0565 30.09650
June 720.00000 21.74859 55.77284 -1.0272 28.84941
July 744.00000 21.75243 55.50603 -1.0159 28.42252
August 744.00000 21.74109 56.32374 -1.0426 29.50024
September 720.00000 21.74425 56.05682 -1.0408 29.42928
October 744.00000 21.73427 56.62026 0.00223 5.84926
November 720.00000 21.67507 57.30322 -0.0514 5.85915
December 744.00000 21.50960 59.68202 -0.1267 5.97964
           
Annual Sum or Average 8760.00000 21.68324 56.51598 -0.4763 15.72425
Minimum of Months 672.00000 21.50960 55.50603 -1.0565 5.84926
Maximum of Months 744.00000 21.75243 59.68202 0.00223 30.09650



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.58082 57.70965 -0.1143 6.20412
February 672.00000 21.61999 56.83686 -0.0854 6.19733
March 744.00000 21.62625 56.38746 -0.0672 6.12761
April 720.00000 21.69736 57.13689 -0.0088 5.96854
May 744.00000 21.72046 56.75863 -1.0594 30.30658
June 720.00000 21.72737 56.58422 -1.0443 29.63040
July 744.00000 21.73720 56.07017 -1.0224 28.80772
August 744.00000 21.72615 56.66905 -1.0385 29.43971
September 720.00000 21.72836 56.44566 -1.0359 29.40266
October 744.00000 21.72097 56.58912 0.01443 5.95125
November 720.00000 21.67165 57.39158 -0.0363 6.02523
December 744.00000 21.58723 59.49216 -0.0871 6.11190
           
Annual Sum or Average 8760.00000 21.67883 57.00862 -0.4678 15.90615
Minimum of Months 672.00000 21.58082 56.07017 -1.0594 5.95125
Maximum of Months 744.00000 21.73720 59.49216 0.01443 30.30658



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.41961 59.83577 -0.1794 6.41801
February 672.00000 21.52607 58.42974 -0.1289 6.29173
March 744.00000 21.56370 57.26725 -0.0970 6.19683
April 720.00000 21.68799 57.59041 -0.0179 5.92640
May 744.00000 21.72141 56.75390 -1.0591 30.28313
June 720.00000 21.73044 56.47717 -1.0395 29.43503
July 744.00000 21.73898 56.00817 -1.0194 28.68217
August 744.00000 21.72477 56.82190 -1.0432 29.60270
September 720.00000 21.72125 57.01302 -1.0524 30.00728
October 744.00000 21.70229 57.88051 -0.0058 5.85890
November 720.00000 21.61395 59.27456 -0.0684 5.97169
December 744.00000 21.45913 61.49136 -0.1418 6.25488
           
Annual Sum or Average 8760.00000 21.63443 57.90277 -0.4900 15.96870
Minimum of Months 672.00000 21.41961 56.00817 -1.0591 5.85890
Maximum of Months 744.00000 21.73898 61.49136 -0.0058 30.28313



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.68007 55.07457 -0.0664 6.17948
February 672.00000 21.69017 55.15242 -0.0613 6.13042
March 744.00000 21.66731 55.46145 -0.0725 6.06152
April 720.00000 21.69178 56.94655 -0.0481 5.92530
May 744.00000 21.70858 56.96309 -1.1276 33.12374
June 720.00000 21.71804 56.88126 -1.1078 32.23082
July 744.00000 21.72952 56.57481 -1.0929 31.65125
August 744.00000 21.71981 56.68754 -1.0993 31.92250
September 720.00000 21.73904 56.21322 -1.0688 30.77090
October 744.00000 21.74863 55.97512 0.01065 6.01783
November 720.00000 21.72317 55.87950 -0.0183 6.07522
December 744.00000 21.67786 57.06354 -0.0488 6.10773
           
Annual Sum or Average 8760.00000 21.70787 56.24572 -0.4860 16.91700
Minimum of Months 672.00000 21.66731 55.07457 -1.1276 5.92530
Maximum of Months 744.00000 21.74863 57.06354 0.01065 33.12374



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.78822 57.27204 0.52361 11.10162
February 672.00000 23.83626 57.48471 0.55092 11.66092
March 744.00000 23.84812 58.22430 0.57105 12.18659
April 720.00000 23.93075 61.39294 0.63845 13.64809
May 744.00000 23.96332 61.94138 -0.1645 5.60273
June 720.00000 23.97598 61.61492 -0.1434 5.45590
July 744.00000 23.98306 61.38892 -0.1358 5.40348
August 744.00000 23.96845 61.81483 -0.1532 5.52723
September 720.00000 23.96768 61.60749 -0.1561 5.56315
October 744.00000 23.94102 62.00916 0.65696 14.10161
November 720.00000 23.88655 60.81137 0.60973 12.96604
December 744.00000 23.80600 59.87332 0.55515 11.75981
           
Annual Sum or Average 8760.00000 23.90819 60.46744 0.27764 9.56624
Minimum of Months 672.00000 23.78822 57.27204 -0.1645 5.40348
Maximum of Months 744.00000 23.98306 62.00916 0.65696 14.10161



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.86737 56.47404 0.57189 12.13665
February 672.00000 23.90149 56.74401 0.59536 12.67431
March 744.00000 23.90646 57.52883 0.61322 13.17093
April 720.00000 23.96079 60.82577 0.67153 14.54823
May 744.00000 23.98068 61.45263 -0.1227 5.34004
June 720.00000 23.98716 61.17007 -0.1049 5.25123
July 744.00000 23.99052 60.95892 -0.0987 5.22169
August 744.00000 23.98273 61.35235 -0.1136 5.29737
September 720.00000 23.98139 61.14784 -0.1171 5.33122
October 744.00000 23.96350 61.50666 0.68606 14.91851
November 720.00000 23.92735 60.19597 0.64536 13.87650
December 744.00000 23.87613 59.10920 0.60047 12.79399
           
Annual Sum or Average 8760.00000 23.94392 59.88735 0.31713 10.02836
Minimum of Months 672.00000 23.86737 56.47404 -0.1227 5.22169
Maximum of Months 744.00000 23.99052 61.50666 0.68606 14.91851



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.86124 55.13737 1.21159 37.41268
February 672.00000 23.87481 55.56761 1.23177 38.36413
March 744.00000 23.89704 56.42714 1.25696 39.44721
April 720.00000 23.93319 59.86780 1.31820 42.23489
May 744.00000 23.95562 60.63918 0.80644 21.93583
June 720.00000 23.97139 60.41135 0.83354 22.68572
July 744.00000 23.97261 60.22914 0.84531 23.21205
August 744.00000 23.96736 60.53852 0.82220 22.33866
September 720.00000 23.96814 60.29065 0.82666 22.51461
October 744.00000 23.95480 60.53174 1.34109 43.22173
November 720.00000 23.91577 59.08736 1.28978 40.90187
December 744.00000 23.87314 57.80516 1.23682 38.47757
           
Annual Sum or Average 8760.00000 23.92900 58.89360 1.08402 32.68966
Minimum of Months 672.00000 23.86124 55.13737 0.80644 21.93583
Maximum of Months 744.00000 23.97261 60.63918 1.34109 43.22173



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.56052 54.11854 0.08617 5.57396
February 672.00000 22.71193 54.20525 0.12597 5.76924
March 744.00000 22.78033 55.25984 0.15078 5.97108
April 720.00000 23.13801 58.38359 0.26220 6.55310
May 744.00000 23.50871 59.00575 -0.5893 12.40400
June 720.00000 23.75432 58.66430 -0.5016 10.32195
July 744.00000 23.83857 58.20942 -0.4726 9.70316
August 744.00000 23.68145 59.14729 -0.5255 10.89459
September 720.00000 23.73187 58.56327 -0.5092 10.51616
October 744.00000 23.51906 58.99743 0.36690 7.84021
November 720.00000 23.16921 57.74774 0.26751 6.75532
December 744.00000 22.73369 56.89722 0.14870 5.86995
           
Annual Sum or Average 8760.00000 23.26309 57.44990 -0.1008 8.19699
Minimum of Months 672.00000 22.56052 54.11854 -0.5893 5.57396
Maximum of Months 744.00000 23.83857 59.14729 0.36690 12.40400



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.97824 56.50585 0.17904 6.02859
February 672.00000 23.05157 56.84293 0.19999 6.15879
March 744.00000 23.16236 57.63675 0.23446 6.51006
April 720.00000 23.51144 60.58706 0.34362 7.56192
May 744.00000 23.69049 61.31594 -0.5495 11.41869
June 720.00000 23.85122 60.82429 -0.4925 10.10514
July 744.00000 23.90064 60.41423 -0.4758 9.75055
August 744.00000 23.84345 60.97606 -0.4943 10.15828
September 720.00000 23.88603 60.45720 -0.4801 9.87104
October 744.00000 23.85630 60.59600 0.43656 8.99155
November 720.00000 23.53970 59.68883 0.34620 7.70024
December 744.00000 23.08775 59.25157 0.22496 6.43305
           
Annual Sum or Average 8760.00000 23.53203 59.60524 -0.0457 8.40441
Minimum of Months 672.00000 22.97824 56.50585 -0.5495 6.02859
Maximum of Months 744.00000 23.90064 61.31594 0.43656 11.41869



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.63191 54.74318 0.12677 6.02793
February 672.00000 22.83902 54.67360 0.18186 6.37964
March 744.00000 22.98769 55.30522 0.22653 6.80289
April 720.00000 23.47393 57.86288 0.37284 8.10932
May 744.00000 23.75199 58.18503 -0.4627 9.63251
June 720.00000 23.89931 57.65942 -0.4044 8.46833
July 744.00000 23.91810 57.34467 -0.3932 8.27978
August 744.00000 23.85984 57.94282 -0.4180 8.75787
September 720.00000 23.87820 57.55564 -0.4104 8.63398
October 744.00000 23.78774 57.97095 0.46160 9.50592
November 720.00000 23.36813 57.36815 0.34120 7.91229
December 744.00000 22.79545 57.38272 0.18714 6.46848
           
Annual Sum or Average 8760.00000 23.43505 57.01193 -0.0174 7.92352
Minimum of Months 672.00000 22.63191 54.67360 -0.4627 6.02793
Maximum of Months 744.00000 23.91810 58.18503 0.46160 9.63251



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.68193 53.15740 0.12280 5.76803
February 672.00000 22.83840 53.22597 0.16418 6.04635
March 744.00000 22.91503 54.20657 0.19085 6.29428
April 720.00000 23.27073 57.26274 0.30273 7.06464
May 744.00000 23.60554 57.81379 -0.5396 11.25752
June 720.00000 23.80326 57.47327 -0.4655 9.60207
July 744.00000 23.86377 57.09193 -0.4431 9.15077
August 744.00000 23.73614 57.92873 -0.4892 10.13112
September 720.00000 23.78076 57.39069 -0.4739 9.80244
October 744.00000 23.60657 57.81759 0.39724 8.34962
November 720.00000 23.29018 56.59250 0.30465 7.22820
December 744.00000 22.86077 55.85228 0.18677 6.16516
           
Annual Sum or Average 8760.00000 23.35667 56.33376 -0.0635 8.08447
Minimum of Months 672.00000 22.68193 53.15740 -0.5396 5.76803
Maximum of Months 744.00000 23.86377 57.92873 0.39724 11.25752



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.166788E+12 152118.03 01-JAN-19:03 741.25 0.532692E+12 0.00 0.699481E+12 3.11 4.05 07-JAN-19:02 0.00 0.00
February 0.180856E+12 167440.99 11-FEB-16:03 661.31 0.576614E+12 0.00 0.757470E+12 3.07 4.03 12-FEB-19:03 0.00 0.00
March 0.220638E+12 165485.17 13-MAR-18:03 739.62 0.722224E+12 0.00 0.942863E+12 3.17 4.05 19-MAR-08:62 0.00 0.00
April 0.264677E+12 183063.98 14-APR-15:03 720.00 0.854492E+12 0.00 0.111917E+13 3.19 4.04 25-APR-18:03 0.00 0.00
May 0.338097E+12 194793.02 29-MAY-18:03 744.00 0.111937E+13 0.00 0.145747E+13 3.30 4.06 24-MAY-18:03 0.00 0.00
June 0.369417E+12 207677.20 08-JUN-18:05 720.00 0.122689E+13 0.00 0.159631E+13 3.32 3.99 18-JUN-20:20 0.00 0.00
July 0.395738E+12 225612.96 27-JUL-18:03 744.00 0.130794E+13 0.00 0.170368E+13 3.31 4.10 02-JUL-18:03 0.00 0.00
August 0.391804E+12 203467.63 21-AUG-16:00 744.00 0.129852E+13 0.00 0.169032E+13 3.32 4.05 12-AUG-08:03 0.00 0.00
September 0.372030E+12 218878.17 18-SEP-18:03 720.00 0.124412E+13 0.00 0.161615E+13 3.35 4.01 25-SEP-21:00 0.00 0.00
October 0.349417E+12 197796.19 03-OCT-15:03 744.00 0.117372E+13 0.00 0.152314E+13 3.35 4.07 01-OCT-08:03 0.00 0.00
November 0.274185E+12 182645.52 03-NOV-18:03 719.89 0.920696E+12 0.00 0.119488E+13 3.29 4.04 24-NOV-09:02 0.00 0.00
December 0.202601E+12 176776.48 23-DEC-19:03 738.58 0.671988E+12 0.00 0.874590E+12 3.18 4.08 23-DEC-19:03 0.00 0.00
                         
Annual Sum or Average 0.352625E+13     8736.65 0.116493E+14 0.00 0.151755E+14 3.25     0.00 0.00
Minimum of Months 0.166788E+12 152118.03   661.31 0.532692E+12 0.00 0.699481E+12 3.07 3.99   0.00 0.00
Maximum of Months 0.395738E+12 225612.96   744.00 0.130794E+13 0.00 0.170368E+13 3.35 4.10   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.663055E+09 0.00 178.34 20925.20 19-JAN-09:05 0.00 59.38 63.84 0.00 0.00 0.00 0.09 19-JAN-09:05
February 0.715689E+09 0.00 99.04 23516.82 23-FEB-19:05 0.00 56.09 59.25 0.00 0.00 0.00 0.11 23-FEB-19:05
March 0.387163E+09 0.00 82.68 29026.89 19-MAR-15:05 0.00 54.70 57.11 0.00 0.00 0.00 0.13 19-MAR-15:05
April 67227647.23 0.00 5.76 29865.53 21-APR-08:05 0.00 52.29 52.50 0.00 0.00 0.00 0.13 21-APR-08:05
May 28445128.72 0.00 3.56 22657.49 01-MAY-08:05 0.00 53.67 53.80 0.00 0.00 0.00 0.10 01-MAY-08:05
June 20785283.01 0.00 2.00 12519.64 12-JUN-08:07 0.00 53.98 54.05 0.00 0.00 0.00 0.06 12-JUN-08:07
July 21522939.75 0.00 0.97 12677.63 21-JUL-08:07 0.00 54.51 54.55 0.00 0.00 0.00 0.06 21-JUL-08:07
August 25615855.29 0.00 1.58 23233.95 28-AUG-08:05 0.00 54.14 54.20 0.00 0.00 0.00 0.10 28-AUG-08:05
September 16496509.00 0.00 1.14 14136.58 15-SEP-08:05 0.00 55.66 55.70 0.00 0.00 0.00 0.06 15-SEP-08:05
October 74169597.16 0.00 3.83 29836.36 18-OCT-08:05 0.00 52.90 53.04 0.00 0.00 0.00 0.13 18-OCT-08:05
November 0.183694E+09 0.00 42.00 24739.39 29-NOV-09:05 0.00 54.74 55.98 0.00 0.00 0.00 0.11 29-NOV-09:05
December 0.695834E+09 0.00 160.46 25376.47 06-DEC-09:05 0.00 57.00 61.10 0.00 0.00 0.00 0.11 06-DEC-09:05
                           
Annual Sum or Average 0.289970E+10 0.00 581.37     0.00 54.92 56.25 0.00 0.00 0.00    
Minimum of Months 16496509.00 0.00 0.97 12519.64   0.00 52.29 52.50 0.00 0.00 0.00 0.06  
Maximum of Months 0.715689E+09 0.00 178.34 29865.53   0.00 59.38 63.84 0.00 0.00 0.00 0.13  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.366951E+12 0.00 692.32 0.243432E+12 0.00 0.00 0.00 0.00 448145.34 06-JAN-23:00 223501.62 13-JAN-22:00 0.00 0.00 0.00
February 0.401368E+12 0.00 637.06 0.270618E+12 0.00 0.00 0.00 0.00 444408.36 10-FEB-22:00 215785.05 17-FEB-22:00 0.00 0.00 0.00
March 0.513478E+12 0.00 708.91 0.326309E+12 0.00 0.00 0.00 0.00 460281.68 09-MAR-21:00 225694.59 13-MAR-18:10 0.00 0.00 0.00
April 0.609081E+12 0.00 719.67 0.395661E+12 0.00 0.00 0.00 0.00 399804.01 14-APR-20:00 242598.26 17-APR-18:08 0.00 0.00 0.00
May 0.818786E+12 0.00 744.00 0.473531E+12 0.00 0.00 0.00 0.00 486570.12 28-MAY-20:00 251375.38 22-MAY-20:10 0.00 0.00 0.00
June 0.902818E+12 0.00 720.00 0.489816E+12 0.00 0.00 0.00 0.00 486661.69 21-JUN-19:10 264425.96 09-JUN-21:00 0.00 0.00 0.00
July 0.961076E+12 0.00 744.00 0.519890E+12 0.00 0.00 0.00 0.00 497593.42 27-JUL-21:00 271832.74 27-JUL-21:00 0.00 0.00 0.00
August 0.960372E+12 0.00 744.00 0.513207E+12 0.00 0.00 0.00 0.00 493841.75 06-AUG-21:00 271235.90 02-AUG-21:00 0.00 0.00 0.00
September 0.912906E+12 0.00 720.00 0.495387E+12 0.00 0.00 0.00 0.00 549866.27 25-SEP-21:00 280958.40 08-SEP-20:10 0.00 0.00 0.00
October 0.855511E+12 0.00 744.00 0.484368E+12 0.00 0.00 0.00 0.00 489926.99 01-OCT-20:00 260521.04 03-OCT-20:10 0.00 0.00 0.00
November 0.665263E+12 0.00 707.14 0.382345E+12 0.00 0.00 0.00 0.00 486518.01 21-NOV-20:50 249211.82 03-NOV-21:00 0.00 0.00 0.00
December 0.478519E+12 0.00 705.00 0.283279E+12 0.00 0.00 0.00 0.00 497113.07 25-DEC-22:00 227756.03 08-DEC-21:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.844613E+13 0.00 8586.10 0.487784E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.366951E+12 0.00 637.06 0.243432E+12 0.00 0.00 0.00 0.00 399804.01   215785.05   0.00 0.00 0.00
Maximum of Months 0.961076E+12 0.00 744.00 0.519890E+12 0.00 0.00 0.00 0.00 549866.27   280958.40   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.677718E+11 0.00 629.83 0.425099E+11 0.00 0.00 0.00 0.00 69237.46 07-JAN-03:30 31776.10 02-JAN-14:30 0.00 0.00 0.00
February 0.730596E+11 0.00 607.50 0.480295E+11 0.00 0.00 0.00 0.00 66420.60 19-FEB-11:08 32472.50 11-FEB-14:00 0.00 0.00 0.00
March 0.884565E+11 0.00 672.00 0.575723E+11 0.00 0.00 0.00 0.00 71113.53 19-MAR-07:30 32169.79 13-MAR-15:02 0.00 0.00 0.00
April 0.104449E+12 0.00 718.83 0.688285E+11 0.00 0.00 0.00 0.00 71667.21 01-APR-02:40 34329.10 17-APR-15:00 0.00 0.00 0.00
May 0.130143E+12 0.00 744.00 0.775898E+11 0.00 0.00 0.00 0.00 75328.85 27-MAY-13:50 35993.18 22-MAY-13:00 0.00 0.00 0.00
June 0.140044E+12 0.00 720.00 0.776376E+11 0.00 0.00 0.00 0.00 65096.78 05-JUN-14:20 34669.20 11-JUN-13:00 0.00 0.00 0.00
July 0.146006E+12 0.00 744.00 0.810793E+11 0.00 0.00 0.00 0.00 78320.77 02-JUL-17:10 36585.84 28-JUL-15:00 0.00 0.00 0.00
August 0.147946E+12 0.00 744.00 0.807202E+11 0.00 0.00 0.00 0.00 77733.94 12-AUG-08:00 35860.24 23-AUG-13:00 0.00 0.00 0.00
September 0.138211E+12 0.00 720.00 0.772421E+11 0.00 0.00 0.00 0.00 62991.20 06-SEP-11:00 34792.19 20-SEP-14:00 0.00 0.00 0.00
October 0.132898E+12 0.00 744.00 0.774799E+11 0.00 0.00 0.00 0.00 75152.59 01-OCT-07:20 34478.78 14-OCT-13:00 0.00 0.00 0.00
November 0.111112E+12 0.00 692.67 0.643230E+11 0.00 0.00 0.00 0.00 78941.54 08-NOV-09:00 32641.04 17-NOV-15:00 0.00 0.00 0.00
December 0.838727E+11 0.00 655.33 0.496187E+11 0.00 0.00 0.00 0.00 74613.04 24-DEC-07:30 32117.16 10-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.136397E+13 0.00 8392.17 0.802631E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.677718E+11 0.00 607.50 0.425099E+11 0.00 0.00 0.00 0.00 62991.20   31776.10   0.00 0.00 0.00
Maximum of Months 0.147946E+12 0.00 744.00 0.810793E+11 0.00 0.00 0.00 0.00 78941.54   36585.84   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.500101E+10 0.00 598.23 0.266567E+10 0.00 0.00 0.00 0.00 16578.72 07-JAN-09:02 12319.63 19-JAN-16:02 0.00 0.00 0.00
February 0.571887E+10 0.00 561.98 0.324315E+10 0.00 0.00 0.00 0.00 15875.85 02-FEB-09:02 12571.38 24-FEB-16:02 0.00 0.00 0.00
March 0.734195E+10 0.00 627.63 0.427425E+10 0.00 0.00 0.00 0.00 16061.03 06-MAR-09:02 12407.84 26-MAR-15:02 0.00 0.00 0.00
April 0.904973E+10 0.00 658.17 0.549608E+10 0.00 0.00 0.00 0.00 15062.95 16-APR-08:62 12346.03 16-APR-18:02 0.00 0.00 0.00
May 0.106748E+11 0.00 693.71 0.656577E+10 0.00 0.00 0.00 0.00 15686.34 24-MAY-18:02 12417.03 19-MAY-18:02 0.00 0.00 0.00
June 0.110679E+11 0.00 677.33 0.684062E+10 0.00 0.00 0.00 0.00 14746.76 13-JUN-08:62 12414.10 28-JUN-15:02 0.00 0.00 0.00
July 0.123581E+11 0.00 708.24 0.786367E+10 0.00 0.00 0.00 0.00 14422.62 02-JUL-18:02 12383.52 21-JUL-15:02 0.00 0.00 0.00
August 0.118050E+11 0.00 696.42 0.739586E+10 0.00 0.00 0.00 0.00 15960.84 12-AUG-08:62 12404.93 06-AUG-15:02 0.00 0.00 0.00
September 0.115127E+11 0.00 679.24 0.720758E+10 0.00 0.00 0.00 0.00 14706.98 16-SEP-08:62 12402.11 04-SEP-15:02 0.00 0.00 0.00
October 0.109973E+11 0.00 697.24 0.680684E+10 0.00 0.00 0.00 0.00 15330.20 01-OCT-08:62 12338.49 16-OCT-15:02 0.00 0.00 0.00
November 0.813575E+10 0.00 641.38 0.467872E+10 0.00 0.00 0.00 0.00 15331.05 24-NOV-09:02 12443.01 25-NOV-16:02 0.00 0.00 0.00
December 0.598794E+10 0.00 610.91 0.326474E+10 0.00 0.00 0.00 0.00 16297.40 23-DEC-09:02 12138.72 01-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.109651E+12 0.00 7850.49 0.663029E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.500101E+10 0.00 561.98 0.266567E+10 0.00 0.00 0.00 0.00 14422.62   12138.72   0.00 0.00 0.00
Maximum of Months 0.123581E+11 0.00 708.24 0.786367E+10 0.00 0.00 0.00 0.00 16578.72   12571.38   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.319531E+10 0.00 497.91 0.142379E+10 0.00 0.00 0.00 0.00 16699.65 07-JAN-09:02 12215.45 26-JAN-16:02 0.00 0.00 0.00
February 0.434242E+10 0.00 507.77 0.218656E+10 0.00 0.00 0.00 0.00 15714.46 18-FEB-09:02 12705.22 24-FEB-16:02 0.00 0.00 0.00
March 0.627573E+10 0.00 590.12 0.346590E+10 0.00 0.00 0.00 0.00 16119.30 19-MAR-08:62 12383.31 28-MAR-15:02 0.00 0.00 0.00
April 0.850603E+10 0.00 647.23 0.506243E+10 0.00 0.00 0.00 0.00 15256.09 16-APR-08:62 12576.92 16-APR-18:02 0.00 0.00 0.00
May 0.106673E+11 0.00 694.39 0.654828E+10 0.00 0.00 0.00 0.00 16227.09 24-MAY-18:02 12555.61 13-MAY-15:02 0.00 0.00 0.00
June 0.112557E+11 0.00 680.16 0.698094E+10 0.00 0.00 0.00 0.00 14883.05 13-JUN-08:62 12533.41 28-JUN-15:02 0.00 0.00 0.00
July 0.124756E+11 0.00 710.20 0.793818E+10 0.00 0.00 0.00 0.00 14802.89 02-JUL-18:02 12550.25 07-JUL-15:02 0.00 0.00 0.00
August 0.115705E+11 0.00 696.05 0.716999E+10 0.00 0.00 0.00 0.00 16026.41 12-AUG-08:62 12565.57 21-AUG-15:02 0.00 0.00 0.00
September 0.107490E+11 0.00 673.53 0.651833E+10 0.00 0.00 0.00 0.00 14904.84 16-SEP-08:62 12526.35 10-SEP-15:02 0.00 0.00 0.00
October 0.954384E+10 0.00 681.98 0.554791E+10 0.00 0.00 0.00 0.00 15427.95 01-OCT-08:62 12573.73 14-OCT-15:02 0.00 0.00 0.00
November 0.652278E+10 0.00 603.95 0.336794E+10 0.00 0.00 0.00 0.00 15451.00 24-NOV-09:02 12406.46 07-NOV-16:02 0.00 0.00 0.00
December 0.424860E+10 0.00 528.92 0.201748E+10 0.00 0.00 0.00 0.00 16166.26 23-DEC-09:02 12319.31 04-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.993529E+11 0.00 7512.21 0.582277E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.319531E+10 0.00 497.91 0.142379E+10 0.00 0.00 0.00 0.00 14802.89   12215.45   0.00 0.00 0.00
Maximum of Months 0.124756E+11 0.00 710.20 0.793818E+10 0.00 0.00 0.00 0.00 16699.65   12705.22   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.286437E+11 0.00 527.28 0.188831E+11 0.00 0.00 0.00 0.00 46999.76 02-JAN-14:30 41049.21 02-JAN-14:30 0.00 0.00 0.00
February 0.254304E+11 0.00 481.31 0.158029E+11 0.00 0.00 0.00 0.00 40914.99 11-FEB-14:30 32692.26 22-FEB-14:40 0.00 0.00 0.00
March 0.244281E+11 0.00 534.76 0.128676E+11 0.00 0.00 0.00 0.00 33815.14 04-MAR-11:33 27009.48 03-MAR-14:40 0.00 0.00 0.00
April 0.248458E+11 0.00 581.98 0.120424E+11 0.00 0.00 0.00 0.00 26188.09 15-APR-14:30 19109.79 15-APR-14:30 0.00 0.00 0.00
May 0.287785E+11 0.00 689.24 0.128948E+11 0.00 0.00 0.00 0.00 25432.48 25-MAY-20:20 15642.21 22-MAY-17:17 0.00 0.00 0.00
June 0.327046E+11 0.00 710.17 0.152151E+11 0.00 0.00 0.00 0.00 28392.23 18-JUN-20:20 16096.41 29-JUN-17:17 0.00 0.00 0.00
July 0.379278E+11 0.00 738.67 0.192087E+11 0.00 0.00 0.00 0.00 28013.39 29-JUL-17:20 21540.98 29-JUL-17:20 0.00 0.00 0.00
August 0.379063E+11 0.00 727.22 0.197557E+11 0.00 0.00 0.00 0.00 28960.85 20-AUG-13:40 22117.94 20-AUG-13:50 0.00 0.00 0.00
September 0.455575E+11 0.00 716.83 0.270677E+11 0.00 0.00 0.00 0.00 38334.99 30-SEP-13:30 28370.53 30-SEP-13:40 0.00 0.00 0.00
October 0.494258E+11 0.00 736.72 0.304108E+11 0.00 0.00 0.00 0.00 43594.04 25-OCT-12:30 36590.31 25-OCT-12:40 0.00 0.00 0.00
November 0.397908E+11 0.00 631.96 0.247835E+11 0.00 0.00 0.00 0.00 46352.72 07-NOV-13:30 41426.49 07-NOV-13:40 0.00 0.00 0.00
December 0.310511E+11 0.00 513.79 0.200608E+11 0.00 0.00 0.00 0.00 46857.70 09-DEC-12:30 42641.88 03-DEC-14:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.406490E+12 0.00 7589.92 0.228993E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.244281E+11 0.00 481.31 0.120424E+11 0.00 0.00 0.00 0.00 25432.48   15642.21   0.00 0.00 0.00
Maximum of Months 0.494258E+11 0.00 738.67 0.304108E+11 0.00 0.00 0.00 0.00 46999.76   42641.88   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.263369E+11 0.00 502.62 0.124269E+11 0.00 0.00 0.00 0.00 105420.79 07-JAN-09:02 69616.70 06-JAN-19:02 0.00 0.00 0.00
February 0.319487E+11 0.00 455.37 0.168913E+11 0.00 0.00 0.00 0.00 98025.82 18-FEB-09:02 71120.63 17-FEB-19:02 0.00 0.00 0.00
March 0.412194E+11 0.00 515.93 0.227272E+11 0.00 0.00 0.00 0.00 101305.16 19-MAR-08:62 72332.66 13-MAR-18:02 0.00 0.00 0.00
April 0.520612E+11 0.00 511.78 0.310587E+11 0.00 0.00 0.00 0.00 94143.87 16-APR-08:62 75774.19 17-APR-18:02 0.00 0.00 0.00
May 0.667253E+11 0.00 554.72 0.436780E+11 0.00 0.00 0.00 0.00 104447.62 24-MAY-18:02 75218.29 20-MAY-08:62 0.00 0.00 0.00
June 0.724628E+11 0.00 563.94 0.495608E+11 0.00 0.00 0.00 0.00 88504.89 04-JUN-15:02 75139.48 17-JUN-08:62 0.00 0.00 0.00
July 0.769342E+11 0.00 608.64 0.530499E+11 0.00 0.00 0.00 0.00 94781.61 02-JUL-18:02 75094.31 02-JUL-08:62 0.00 0.00 0.00
August 0.706164E+11 0.00 570.72 0.470911E+11 0.00 0.00 0.00 0.00 100949.95 12-AUG-08:62 74320.14 19-AUG-18:02 0.00 0.00 0.00
September 0.667773E+11 0.00 544.67 0.441662E+11 0.00 0.00 0.00 0.00 88738.83 16-SEP-08:62 74540.97 23-SEP-08:62 0.00 0.00 0.00
October 0.588472E+11 0.00 527.00 0.359543E+11 0.00 0.00 0.00 0.00 96311.77 01-OCT-08:62 73254.64 03-OCT-18:02 0.00 0.00 0.00
November 0.444458E+11 0.00 507.71 0.251661E+11 0.00 0.00 0.00 0.00 95628.14 24-NOV-09:02 72733.87 20-NOV-19:02 0.00 0.00 0.00
December 0.313812E+11 0.00 501.13 0.156215E+11 0.00 0.00 0.00 0.00 101121.16 23-DEC-09:02 71865.77 09-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.639756E+12 0.00 6364.23 0.397392E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.263369E+11 0.00 455.37 0.124269E+11 0.00 0.00 0.00 0.00 88504.89   69616.70   0.00 0.00 0.00
Maximum of Months 0.769342E+11 0.00 608.64 0.530499E+11 0.00 0.00 0.00 0.00 105420.79   75774.19   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.526302E+10 0.00 616.41 0.295623E+10 0.00 0.00 0.00 0.00 14771.08 07-JAN-09:02 10944.04 15-JAN-16:02 0.00 0.00 0.00
February 0.573911E+10 0.00 576.98 0.330895E+10 0.00 0.00 0.00 0.00 14046.97 18-FEB-09:02 11276.50 24-FEB-16:02 0.00 0.00 0.00
March 0.722392E+10 0.00 659.76 0.421747E+10 0.00 0.00 0.00 0.00 14434.73 06-MAR-09:02 10981.52 31-MAR-15:02 0.00 0.00 0.00
April 0.900595E+10 0.00 683.14 0.546953E+10 0.00 0.00 0.00 0.00 13311.97 29-APR-08:62 11106.68 10-APR-15:02 0.00 0.00 0.00
May 0.107187E+11 0.00 709.69 0.666010E+10 0.00 0.00 0.00 0.00 14303.63 24-MAY-18:02 11112.15 20-MAY-15:02 0.00 0.00 0.00
June 0.116841E+11 0.00 694.40 0.748296E+10 0.00 0.00 0.00 0.00 12665.82 05-JUN-08:62 11045.88 01-JUN-15:02 0.00 0.00 0.00
July 0.127495E+11 0.00 722.26 0.837447E+10 0.00 0.00 0.00 0.00 12905.95 02-JUL-18:02 11135.82 27-JUL-15:02 0.00 0.00 0.00
August 0.118439E+11 0.00 708.00 0.757387E+10 0.00 0.00 0.00 0.00 14330.02 12-AUG-08:62 11125.45 20-AUG-15:02 0.00 0.00 0.00
September 0.119613E+11 0.00 694.85 0.779832E+10 0.00 0.00 0.00 0.00 13129.69 05-SEP-08:62 11127.84 10-SEP-15:02 0.00 0.00 0.00
October 0.111757E+11 0.00 712.01 0.707219E+10 0.00 0.00 0.00 0.00 13777.94 01-OCT-08:62 11125.00 20-OCT-15:02 0.00 0.00 0.00
November 0.818562E+10 0.00 652.62 0.481309E+10 0.00 0.00 0.00 0.00 13760.35 24-NOV-09:02 11131.20 06-NOV-16:02 0.00 0.00 0.00
December 0.557567E+10 0.00 606.74 0.302921E+10 0.00 0.00 0.00 0.00 14620.03 23-DEC-09:02 10914.87 04-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.111127E+12 0.00 8036.85 0.687564E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.526302E+10 0.00 576.98 0.295623E+10 0.00 0.00 0.00 0.00 12665.82   10914.87   0.00 0.00 0.00
Maximum of Months 0.127495E+11 0.00 722.26 0.837447E+10 0.00 0.00 0.00 0.00 14771.08   11276.50   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.347252E+10 0.00 499.83 0.167858E+10 0.00 0.00 0.00 0.00 14984.63 07-JAN-09:02 10646.65 15-JAN-16:02 0.00 0.00 0.00
February 0.432641E+10 0.00 531.25 0.227103E+10 0.00 0.00 0.00 0.00 14076.56 18-FEB-09:02 11378.99 24-FEB-16:02 0.00 0.00 0.00
March 0.611205E+10 0.00 616.75 0.340665E+10 0.00 0.00 0.00 0.00 14462.17 19-MAR-08:62 10991.14 01-MAR-16:02 0.00 0.00 0.00
April 0.843822E+10 0.00 679.52 0.498556E+10 0.00 0.00 0.00 0.00 13458.44 29-APR-08:62 11261.87 15-APR-15:02 0.00 0.00 0.00
May 0.107068E+11 0.00 710.57 0.662745E+10 0.00 0.00 0.00 0.00 14727.84 24-MAY-18:02 11239.77 20-MAY-15:02 0.00 0.00 0.00
June 0.118698E+11 0.00 695.98 0.763341E+10 0.00 0.00 0.00 0.00 12779.64 05-JUN-08:62 11138.97 01-JUN-15:02 0.00 0.00 0.00
July 0.128658E+11 0.00 723.44 0.845300E+10 0.00 0.00 0.00 0.00 13169.68 02-JUL-18:02 11267.39 27-JUL-15:02 0.00 0.00 0.00
August 0.115972E+11 0.00 707.22 0.728335E+10 0.00 0.00 0.00 0.00 14367.03 12-AUG-08:62 11121.28 19-AUG-15:02 0.00 0.00 0.00
September 0.111919E+11 0.00 690.72 0.701609E+10 0.00 0.00 0.00 0.00 13308.59 05-SEP-08:62 11089.65 13-SEP-15:02 0.00 0.00 0.00
October 0.969784E+10 0.00 703.01 0.572553E+10 0.00 0.00 0.00 0.00 13840.55 01-OCT-08:62 10974.81 24-OCT-15:02 0.00 0.00 0.00
November 0.657385E+10 0.00 612.38 0.359810E+10 0.00 0.00 0.00 0.00 13848.60 24-NOV-09:02 10763.79 14-NOV-16:02 0.00 0.00 0.00
December 0.385308E+10 0.00 522.05 0.185164E+10 0.00 0.00 0.00 0.00 14477.52 23-DEC-09:02 10609.29 04-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.100705E+12 0.00 7692.72 0.605304E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.347252E+10 0.00 499.83 0.167858E+10 0.00 0.00 0.00 0.00 12779.64   10609.29   0.00 0.00 0.00
Maximum of Months 0.128658E+11 0.00 723.44 0.845300E+10 0.00 0.00 0.00 0.00 14984.63   11378.99   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.107075E+10 0.00 530.77 0.549195E+09 0.00 0.00 0.00 0.00 4524.37 07-JAN-09:02 3209.93 23-JAN-16:02 0.00 0.00 0.00
February 0.131670E+10 0.00 534.15 0.721285E+09 0.00 0.00 0.00 0.00 4312.16 02-FEB-09:02 3293.77 24-FEB-16:02 0.00 0.00 0.00
March 0.175212E+10 0.00 600.37 0.983624E+09 0.00 0.00 0.00 0.00 4362.80 06-MAR-09:02 3233.04 04-MAR-16:02 0.00 0.00 0.00
April 0.223362E+10 0.00 656.35 0.132047E+10 0.00 0.00 0.00 0.00 4124.66 22-APR-08:62 3242.45 01-APR-15:02 0.00 0.00 0.00
May 0.268910E+10 0.00 691.98 0.161326E+10 0.00 0.00 0.00 0.00 4248.11 24-MAY-18:02 3237.52 16-MAY-18:02 0.00 0.00 0.00
June 0.280890E+10 0.00 675.35 0.169593E+10 0.00 0.00 0.00 0.00 3969.55 13-JUN-08:62 3259.90 25-JUN-15:02 0.00 0.00 0.00
July 0.316332E+10 0.00 707.14 0.198347E+10 0.00 0.00 0.00 0.00 3905.80 15-JUL-08:62 3266.81 28-JUL-18:02 0.00 0.00 0.00
August 0.298911E+10 0.00 694.01 0.183892E+10 0.00 0.00 0.00 0.00 4358.92 12-AUG-08:62 3237.94 02-AUG-15:02 0.00 0.00 0.00
September 0.289397E+10 0.00 677.13 0.177817E+10 0.00 0.00 0.00 0.00 4063.56 16-SEP-08:62 3246.80 17-SEP-15:02 0.00 0.00 0.00
October 0.270088E+10 0.00 692.71 0.162740E+10 0.00 0.00 0.00 0.00 4199.08 01-OCT-08:62 3234.86 28-OCT-15:02 0.00 0.00 0.00
November 0.191459E+10 0.00 621.07 0.105680E+10 0.00 0.00 0.00 0.00 4172.76 24-NOV-09:02 3253.48 09-NOV-16:02 0.00 0.00 0.00
December 0.134061E+10 0.00 551.82 0.709742E+09 0.00 0.00 0.00 0.00 4466.14 23-DEC-09:02 3160.52 25-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.268737E+11 0.00 7632.84 0.158783E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.107075E+10 0.00 530.77 0.549195E+09 0.00 0.00 0.00 0.00 3905.80   3160.52   0.00 0.00 0.00
Maximum of Months 0.316332E+10 0.00 707.14 0.198347E+10 0.00 0.00 0.00 0.00 4524.37   3293.77   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.629069E+09 0.00 407.01 0.270507E+09 0.00 0.00 0.00 0.00 4552.18 07-JAN-09:02 3196.75 26-JAN-16:02 0.00 0.00 0.00
February 0.966108E+09 0.00 461.31 0.469573E+09 0.00 0.00 0.00 0.00 4263.40 18-FEB-09:02 3324.96 24-FEB-16:02 0.00 0.00 0.00
March 0.147781E+10 0.00 555.88 0.782288E+09 0.00 0.00 0.00 0.00 4358.57 19-MAR-08:62 3271.34 28-MAR-15:02 0.00 0.00 0.00
April 0.209171E+10 0.00 647.62 0.120157E+10 0.00 0.00 0.00 0.00 4171.29 16-APR-08:62 3280.47 02-APR-15:02 0.00 0.00 0.00
May 0.268796E+10 0.00 692.67 0.160902E+10 0.00 0.00 0.00 0.00 4398.81 24-MAY-18:02 3293.52 29-MAY-18:02 0.00 0.00 0.00
June 0.285770E+10 0.00 678.16 0.173223E+10 0.00 0.00 0.00 0.00 4005.83 13-JUN-08:62 3284.29 25-JUN-15:02 0.00 0.00 0.00
July 0.319455E+10 0.00 709.01 0.200395E+10 0.00 0.00 0.00 0.00 3939.46 15-JUL-08:62 3294.69 28-JUL-18:02 0.00 0.00 0.00
August 0.292814E+10 0.00 693.08 0.177512E+10 0.00 0.00 0.00 0.00 4374.85 12-AUG-08:62 3283.77 02-AUG-15:02 0.00 0.00 0.00
September 0.269541E+10 0.00 672.22 0.158985E+10 0.00 0.00 0.00 0.00 4107.51 16-SEP-08:62 3291.44 26-SEP-15:02 0.00 0.00 0.00
October 0.231758E+10 0.00 679.52 0.128244E+10 0.00 0.00 0.00 0.00 4206.95 01-OCT-08:62 3295.00 05-OCT-15:02 0.00 0.00 0.00
November 0.149552E+10 0.00 583.00 0.728129E+09 0.00 0.00 0.00 0.00 4201.89 24-NOV-09:02 3252.48 08-NOV-16:02 0.00 0.00 0.00
December 0.913153E+09 0.00 444.67 0.416036E+09 0.00 0.00 0.00 0.00 4428.59 23-DEC-09:02 3246.06 01-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.242547E+11 0.00 7224.16 0.138607E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.629069E+09 0.00 407.01 0.270507E+09 0.00 0.00 0.00 0.00 3939.46   3196.75   0.00 0.00 0.00
Maximum of Months 0.319455E+10 0.00 709.01 0.200395E+10 0.00 0.00 0.00 0.00 4552.18   3324.96   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.104754E+11 0.00 654.41 0.711038E+10 0.00 0.00 0.00 0.00 18395.96 07-JAN-09:02 12892.60 03-JAN-16:02 0.00 0.00 0.00
February 0.994665E+10 0.00 587.81 0.660558E+10 0.00 0.00 0.00 0.00 17852.57 02-FEB-09:02 13290.60 24-FEB-16:02 0.00 0.00 0.00
March 0.104982E+11 0.00 639.33 0.665039E+10 0.00 0.00 0.00 0.00 18054.47 06-MAR-09:02 13004.53 04-MAR-16:02 0.00 0.00 0.00
April 0.110701E+11 0.00 643.86 0.689127E+10 0.00 0.00 0.00 0.00 16719.43 16-APR-08:62 13127.05 01-APR-15:02 0.00 0.00 0.00
May 0.125400E+11 0.00 675.69 0.780094E+10 0.00 0.00 0.00 0.00 17915.67 24-MAY-18:02 12928.58 01-MAY-15:02 0.00 0.00 0.00
June 0.133892E+11 0.00 660.92 0.859009E+10 0.00 0.00 0.00 0.00 15466.31 13-JUN-08:62 12944.51 01-JUN-15:02 0.00 0.00 0.00
July 0.147289E+11 0.00 692.45 0.964710E+10 0.00 0.00 0.00 0.00 16299.44 02-JUL-18:02 13155.25 27-JUL-15:02 0.00 0.00 0.00
August 0.145227E+11 0.00 680.01 0.954368E+10 0.00 0.00 0.00 0.00 18033.31 12-AUG-08:62 13141.91 21-AUG-15:02 0.00 0.00 0.00
September 0.156604E+11 0.00 674.27 0.107223E+11 0.00 0.00 0.00 0.00 15829.60 16-SEP-08:62 13049.44 04-SEP-15:02 0.00 0.00 0.00
October 0.162947E+11 0.00 699.48 0.113605E+11 0.00 0.00 0.00 0.00 17188.73 01-OCT-08:62 13113.41 24-OCT-15:02 0.00 0.00 0.00
November 0.135124E+11 0.00 657.64 0.915361E+10 0.00 0.00 0.00 0.00 17053.94 24-NOV-09:02 13080.60 07-NOV-16:02 0.00 0.00 0.00
December 0.113263E+11 0.00 653.59 0.752651E+10 0.00 0.00 0.00 0.00 18335.68 23-DEC-09:02 12889.69 25-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.153965E+12 0.00 7919.46 0.101602E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.994665E+10 0.00 587.81 0.660558E+10 0.00 0.00 0.00 0.00 15466.31   12889.69   0.00 0.00 0.00
Maximum of Months 0.162947E+11 0.00 699.48 0.113605E+11 0.00 0.00 0.00 0.00 18395.96   13290.60   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 555.54 361.23 194.31 862.05 214.35 0.00 0.00 0.00
February 490.42 278.92 211.50 799.33 179.44 0.00 0.00 0.00
March 379.01 156.70 222.31 628.86 144.94 0.00 0.00 0.00
April 271.75 55.67 216.09 502.66 90.17 0.00 0.00 0.00
May 212.18 6.74 205.44 431.43 33.68 0.00 0.00 0.00
June 200.14 0.42 199.72 437.25 11.05 0.00 0.00 0.00
July 214.16 1.80 212.36 482.78 20.08 0.00 0.00 0.00
August 240.75 18.00 222.75 521.74 9.86 0.00 0.00 0.00
September 312.20 77.13 235.07 666.26 28.15 0.00 0.00 0.00
October 433.29 206.02 227.26 814.22 48.97 0.00 0.00 0.00
November 490.86 275.48 215.37 831.38 103.79 0.00 0.00 0.00
December 535.60 338.19 197.42 848.85 186.10 0.00 0.00 0.00
                 
Annual Sum or Average 360.73 147.45 213.28 651.49 88.81 0.00 0.00 0.00
Minimum of Months 200.14 0.42 194.31 431.43 9.86 0.00 0.00 0.00
Maximum of Months 555.54 361.23 235.07 862.05 214.35 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1564.36 1017.20 547.16 2390.29 676.42 0.00 0.00 0.00
February 1380.98 785.42 595.57 2214.74 565.42 0.00 0.00 0.00
March 1067.25 441.25 626.01 1742.10 458.91 0.00 0.00 0.00
April 765.24 156.76 608.48 1396.75 283.47 0.00 0.00 0.00
May 597.48 18.97 578.52 1206.32 108.64 0.00 0.00 0.00
June 563.58 1.17 562.41 1231.63 37.34 0.00 0.00 0.00
July 603.05 5.06 597.99 1359.90 59.54 0.00 0.00 0.00
August 677.95 50.70 627.25 1462.08 34.92 0.00 0.00 0.00
September 879.14 217.19 661.95 1867.48 86.65 0.00 0.00 0.00
October 1220.12 580.15 639.96 2276.36 150.75 0.00 0.00 0.00
November 1382.22 775.75 606.47 2313.73 326.42 0.00 0.00 0.00
December 1508.22 952.31 555.91 2358.37 590.30 0.00 0.00 0.00
                 
Annual Sum or Average 1015.79 415.21 600.58 1816.32 280.31 0.00 0.00 0.00
Minimum of Months 563.58 1.17 547.16 1206.32 34.92 0.00 0.00 0.00
Maximum of Months 1564.36 1017.20 661.95 2390.29 676.42 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2032.19 1321.40 710.79 3189.63 881.35 0.00 0.00 0.00
February 1793.98 1020.30 773.67 2963.34 731.38 0.00 0.00 0.00
March 1386.42 573.21 813.22 2338.68 592.42 0.00 0.00 0.00
April 994.09 203.64 790.45 1882.63 361.35 0.00 0.00 0.00
May 776.16 24.64 751.52 1629.21 135.37 0.00 0.00 0.00
June 732.13 1.52 730.60 1666.11 46.53 0.00 0.00 0.00
July 783.39 6.58 776.82 1842.88 74.00 0.00 0.00 0.00
August 880.69 65.86 814.83 1978.55 41.68 0.00 0.00 0.00
September 1142.06 282.14 859.91 2521.71 107.63 0.00 0.00 0.00
October 1585.00 753.65 831.35 3051.79 179.34 0.00 0.00 0.00
November 1795.58 1007.74 787.84 3093.86 413.31 0.00 0.00 0.00
December 1959.26 1237.10 722.16 3141.88 763.61 0.00 0.00 0.00
                 
Annual Sum or Average 1319.57 539.38 780.19 2439.05 359.02 0.00 0.00 0.00
Minimum of Months 732.13 1.52 710.79 1629.21 41.68 0.00 0.00 0.00
Maximum of Months 2032.19 1321.40 859.91 3189.63 881.35 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.84 71.42 38.42 176.25 34.22 0.00 0.00 0.00
February 96.96 55.15 41.82 163.98 26.69 0.00 0.00 0.00
March 74.94 30.98 43.95 129.54 19.57 0.00 0.00 0.00
April 53.73 11.01 42.72 106.18 8.56 0.00 0.00 0.00
May 41.95 1.33 40.62 99.95 1.37 0.00 0.00 0.00
June 39.57 0.08 39.49 105.92 0.11 0.00 0.00 0.00
July 42.34 0.36 41.99 113.68 0.51 0.00 0.00 0.00
August 47.60 3.56 44.04 123.02 0.05 0.00 0.00 0.00
September 61.73 15.25 46.48 149.08 0.80 0.00 0.00 0.00
October 85.67 40.73 44.93 175.23 2.12 0.00 0.00 0.00
November 97.05 54.47 42.58 175.08 12.48 0.00 0.00 0.00
December 105.90 66.86 39.03 173.22 27.88 0.00 0.00 0.00
                 
Annual Sum or Average 71.32 29.15 42.17 140.81 11.13 0.00 0.00 0.00
Minimum of Months 39.57 0.08 38.42 99.95 0.05 0.00 0.00 0.00
Maximum of Months 109.84 71.42 46.48 176.25 34.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 94.49 40.86 53.63 141.87 68.35 0.00 0.00 0.00
February 118.59 54.01 64.58 194.38 53.09 0.00 0.00 0.00
March 146.90 67.15 79.75 240.63 38.31 0.00 0.00 0.00
April 161.24 74.56 86.68 290.47 15.79 0.00 0.00 0.00
May 147.47 56.94 90.54 304.11 2.55 0.00 0.00 0.00
June 124.86 35.04 89.82 288.48 0.21 0.00 0.00 0.00
July 139.32 43.06 96.27 319.68 0.95 0.00 0.00 0.00
August 139.00 45.18 93.82 311.77 0.08 0.00 0.00 0.00
September 118.61 34.96 83.66 273.22 1.55 0.00 0.00 0.00
October 118.21 46.17 72.04 244.84 4.04 0.00 0.00 0.00
November 97.25 35.62 61.63 182.10 24.90 0.00 0.00 0.00
December 97.50 43.57 53.92 154.91 54.22 0.00 0.00 0.00
                 
Annual Sum or Average 125.34 48.08 77.26 245.81 21.87 0.00 0.00 0.00
Minimum of Months 94.49 34.96 53.63 141.87 0.08 0.00 0.00 0.00
Maximum of Months 161.24 74.56 96.27 319.68 68.35 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.33 0.00 23.33 30.79 35.77 0.00 0.00 0.00
February 27.61 0.00 27.61 43.82 27.63 0.00 0.00 0.00
March 32.94 0.00 32.94 51.37 20.23 0.00 0.00 0.00
April 37.01 0.21 36.79 70.32 8.22 0.00 0.00 0.00
May 42.02 1.72 40.30 99.44 1.32 0.00 0.00 0.00
June 45.04 3.24 41.80 117.59 0.12 0.00 0.00 0.00
July 45.63 2.27 43.35 120.57 0.52 0.00 0.00 0.00
August 40.41 0.42 39.98 107.53 0.05 0.00 0.00 0.00
September 35.78 0.01 35.77 97.80 0.80 0.00 0.00 0.00
October 29.96 0.00 29.96 74.00 1.99 0.00 0.00 0.00
November 26.05 0.00 26.05 53.38 12.80 0.00 0.00 0.00
December 23.07 0.00 23.07 34.18 28.29 0.00 0.00 0.00
                 
Annual Sum or Average 34.10 0.66 33.44 75.22 11.41 0.00 0.00 0.00
Minimum of Months 23.07 0.00 23.07 30.79 0.05 0.00 0.00 0.00
Maximum of Months 45.63 3.24 43.35 120.57 35.77 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 94.49 40.86 53.63 146.96 65.61 0.00 0.00 0.00
February 118.59 54.01 64.58 198.45 51.14 0.00 0.00 0.00
March 146.90 67.15 79.75 243.50 37.11 0.00 0.00 0.00
April 161.24 74.56 86.68 291.65 15.39 0.00 0.00 0.00
May 147.47 56.94 90.54 304.11 2.54 0.00 0.00 0.00
June 124.86 35.04 89.82 288.04 0.22 0.00 0.00 0.00
July 139.32 43.06 96.27 319.42 0.96 0.00 0.00 0.00
August 139.00 45.18 93.82 312.31 0.07 0.00 0.00 0.00
September 118.61 34.96 83.66 274.97 1.45 0.00 0.00 0.00
October 118.21 46.17 72.04 248.11 3.66 0.00 0.00 0.00
November 97.25 35.62 61.63 186.11 23.85 0.00 0.00 0.00
December 97.50 43.57 53.92 159.50 51.84 0.00 0.00 0.00
                 
Annual Sum or Average 125.34 48.08 77.26 248.03 21.03 0.00 0.00 0.00
Minimum of Months 94.49 34.96 53.63 146.96 0.07 0.00 0.00 0.00
Maximum of Months 161.24 74.56 96.27 319.42 65.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 87.85 57.13 30.73 136.60 35.73 0.00 0.00 0.00
February 77.56 44.11 33.45 126.96 28.68 0.00 0.00 0.00
March 59.94 24.78 35.16 100.05 22.11 0.00 0.00 0.00
April 42.98 8.80 34.17 82.12 11.98 0.00 0.00 0.00
May 33.55 1.07 32.49 74.28 2.97 0.00 0.00 0.00
June 31.65 0.07 31.59 77.94 0.74 0.00 0.00 0.00
July 33.87 0.28 33.58 85.32 1.47 0.00 0.00 0.00
August 38.07 2.85 35.23 91.52 0.68 0.00 0.00 0.00
September 49.37 12.20 37.18 113.57 2.84 0.00 0.00 0.00
October 68.52 32.58 35.94 134.46 4.85 0.00 0.00 0.00
November 77.63 43.57 34.06 134.48 14.97 0.00 0.00 0.00
December 84.70 53.48 31.22 134.68 30.29 0.00 0.00 0.00
                 
Annual Sum or Average 57.05 23.32 33.73 107.57 13.04 0.00 0.00 0.00
Minimum of Months 31.65 0.07 30.73 74.28 0.68 0.00 0.00 0.00
Maximum of Months 87.85 57.13 37.18 136.60 35.73 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 18.66 0.00 18.66 27.11 27.22 0.00 0.00 0.00
February 22.09 0.00 22.09 38.68 20.48 0.00 0.00 0.00
March 26.35 0.00 26.35 45.68 14.36 0.00 0.00 0.00
April 29.61 0.17 29.44 62.17 4.83 0.00 0.00 0.00
May 33.62 1.38 32.24 86.60 0.75 0.00 0.00 0.00
June 36.04 2.59 33.45 100.92 0.03 0.00 0.00 0.00
July 36.50 1.82 34.69 103.49 0.21 0.00 0.00 0.00
August 32.33 0.34 31.99 93.48 0.01 0.00 0.00 0.00
September 28.63 0.01 28.62 85.01 0.24 0.00 0.00 0.00
October 23.97 0.00 23.97 65.85 0.95 0.00 0.00 0.00
November 20.84 0.00 20.84 47.60 9.17 0.00 0.00 0.00
December 18.46 0.00 18.46 30.34 21.27 0.00 0.00 0.00
                 
Annual Sum or Average 27.29 0.53 26.76 65.71 8.24 0.00 0.00 0.00
Minimum of Months 18.46 0.00 18.46 27.11 0.01 0.00 0.00 0.00
Maximum of Months 36.50 2.59 34.69 103.49 27.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 104.88 50.26 54.62 156.09 65.04 0.00 0.00 0.00
February 121.65 56.52 65.13 194.89 48.90 0.00 0.00 0.00
March 148.18 70.06 78.12 236.60 34.05 0.00 0.00 0.00
April 161.02 71.88 89.14 290.07 14.72 0.00 0.00 0.00
May 152.34 60.91 91.43 313.11 2.33 0.00 0.00 0.00
June 149.72 57.46 92.26 331.52 0.23 0.00 0.00 0.00
July 154.05 55.59 98.46 346.03 0.90 0.00 0.00 0.00
August 140.80 47.14 93.66 316.21 0.07 0.00 0.00 0.00
September 135.65 48.98 86.67 303.53 1.48 0.00 0.00 0.00
October 124.71 53.52 71.19 257.08 3.82 0.00 0.00 0.00
November 101.55 40.44 61.11 187.52 22.98 0.00 0.00 0.00
December 82.13 29.10 53.03 127.54 52.40 0.00 0.00 0.00
                 
Annual Sum or Average 131.41 53.45 77.96 255.26 20.46 0.00 0.00 0.00
Minimum of Months 82.13 29.10 53.03 127.54 0.07 0.00 0.00 0.00
Maximum of Months 161.02 71.88 98.46 346.03 65.04 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.84 71.42 38.42 175.27 34.06 0.00 0.00 0.00
February 96.96 55.15 41.82 163.14 26.35 0.00 0.00 0.00
March 74.94 30.98 43.95 128.53 19.12 0.00 0.00 0.00
April 53.73 11.01 42.72 105.50 8.16 0.00 0.00 0.00
May 41.95 1.33 40.62 99.64 1.32 0.00 0.00 0.00
June 39.57 0.08 39.49 104.99 0.13 0.00 0.00 0.00
July 42.34 0.36 41.99 113.10 0.50 0.00 0.00 0.00
August 47.60 3.56 44.04 122.86 0.04 0.00 0.00 0.00
September 61.73 15.25 46.48 148.43 0.81 0.00 0.00 0.00
October 85.67 40.73 44.93 174.83 2.05 0.00 0.00 0.00
November 97.05 54.47 42.58 174.60 12.33 0.00 0.00 0.00
December 105.90 66.86 39.03 173.16 27.42 0.00 0.00 0.00
                 
Annual Sum or Average 71.32 29.15 42.17 140.23 10.96 0.00 0.00 0.00
Minimum of Months 39.57 0.08 38.42 99.64 0.04 0.00 0.00 0.00
Maximum of Months 109.84 71.42 46.48 175.27 34.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.33 0.00 23.33 29.73 35.67 0.00 0.00 0.00
February 27.61 0.00 27.61 42.85 27.42 0.00 0.00 0.00
March 32.94 0.00 32.94 50.37 20.00 0.00 0.00 0.00
April 37.01 0.21 36.79 69.58 7.83 0.00 0.00 0.00
May 42.02 1.72 40.30 99.12 1.27 0.00 0.00 0.00
June 45.04 3.24 41.80 116.68 0.14 0.00 0.00 0.00
July 45.63 2.27 43.35 119.99 0.51 0.00 0.00 0.00
August 40.41 0.42 39.98 107.36 0.04 0.00 0.00 0.00
September 35.78 0.01 35.77 97.09 0.81 0.00 0.00 0.00
October 29.96 0.00 29.96 73.50 1.93 0.00 0.00 0.00
November 26.05 0.00 26.05 52.80 12.68 0.00 0.00 0.00
December 23.07 0.00 23.07 34.05 27.74 0.00 0.00 0.00
                 
Annual Sum or Average 34.10 0.66 33.44 74.58 11.27 0.00 0.00 0.00
Minimum of Months 23.07 0.00 23.07 29.73 0.04 0.00 0.00 0.00
Maximum of Months 45.63 3.24 43.35 119.99 35.67 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 104.88 50.26 54.62 160.80 62.18 0.00 0.00 0.00
February 121.65 56.52 65.13 198.65 47.00 0.00 0.00 0.00
March 148.18 70.06 78.12 239.23 32.89 0.00 0.00 0.00
April 161.02 71.88 89.14 291.18 14.32 0.00 0.00 0.00
May 152.34 60.91 91.43 313.13 2.32 0.00 0.00 0.00
June 149.72 57.46 92.26 331.11 0.23 0.00 0.00 0.00
July 154.05 55.59 98.46 345.79 0.90 0.00 0.00 0.00
August 140.80 47.14 93.66 316.76 0.07 0.00 0.00 0.00
September 135.65 48.98 86.67 305.21 1.38 0.00 0.00 0.00
October 124.71 53.52 71.19 260.23 3.47 0.00 0.00 0.00
November 101.55 40.44 61.11 191.42 21.97 0.00 0.00 0.00
December 82.13 29.10 53.03 132.06 49.72 0.00 0.00 0.00
                 
Annual Sum or Average 131.41 53.45 77.96 257.36 19.59 0.00 0.00 0.00
Minimum of Months 82.13 29.10 53.03 132.06 0.07 0.00 0.00 0.00
Maximum of Months 161.02 71.88 98.46 345.79 62.18 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 29.54 0.00 29.54 34.75 58.22 0.00 0.00 0.00
February 34.97 0.00 34.97 51.58 46.03 0.00 0.00 0.00
March 41.71 0.00 41.71 61.74 35.76 0.00 0.00 0.00
April 46.86 0.27 46.60 84.85 19.27 0.00 0.00 0.00
May 53.22 2.18 51.04 115.85 5.35 0.00 0.00 0.00
June 57.04 4.10 52.94 135.06 1.68 0.00 0.00 0.00
July 57.78 2.88 54.91 140.59 3.16 0.00 0.00 0.00
August 51.17 0.54 50.63 122.18 1.59 0.00 0.00 0.00
September 45.31 0.01 45.30 111.98 5.45 0.00 0.00 0.00
October 37.94 0.00 37.94 82.37 8.96 0.00 0.00 0.00
November 32.99 0.00 32.99 58.74 25.41 0.00 0.00 0.00
December 29.22 0.00 29.22 38.76 48.16 0.00 0.00 0.00
                 
Annual Sum or Average 43.19 0.84 42.35 86.70 21.48 0.00 0.00 0.00
Minimum of Months 29.22 0.00 29.22 34.75 1.59 0.00 0.00 0.00
Maximum of Months 57.78 4.10 54.91 140.59 58.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.89 0.00 10.89 12.81 21.46 0.00 0.00 0.00
February 12.89 0.00 12.89 19.02 16.97 0.00 0.00 0.00
March 15.38 0.00 15.38 22.76 13.18 0.00 0.00 0.00
April 17.28 0.10 17.18 31.28 7.10 0.00 0.00 0.00
May 19.62 0.80 18.81 42.71 1.97 0.00 0.00 0.00
June 21.03 1.51 19.52 49.79 0.62 0.00 0.00 0.00
July 21.30 1.06 20.24 51.83 1.17 0.00 0.00 0.00
August 18.86 0.20 18.67 45.04 0.59 0.00 0.00 0.00
September 16.70 0.00 16.70 41.28 2.01 0.00 0.00 0.00
October 13.99 0.00 13.99 30.36 3.30 0.00 0.00 0.00
November 12.16 0.00 12.16 21.65 9.37 0.00 0.00 0.00
December 10.77 0.00 10.77 14.29 17.75 0.00 0.00 0.00
                 
Annual Sum or Average 15.92 0.31 15.61 31.96 7.92 0.00 0.00 0.00
Minimum of Months 10.77 0.00 10.77 12.81 0.59 0.00 0.00 0.00
Maximum of Months 21.30 1.51 20.24 51.83 21.46 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 51.25 33.32 17.93 81.44 19.63 0.00 0.00 0.00
February 45.24 25.73 19.51 75.70 15.77 0.00 0.00 0.00
March 34.96 14.46 20.51 59.63 12.42 0.00 0.00 0.00
April 25.07 5.14 19.93 48.28 7.22 0.00 0.00 0.00
May 19.57 0.62 18.95 42.90 2.00 0.00 0.00 0.00
June 18.46 0.04 18.43 44.25 0.63 0.00 0.00 0.00
July 19.76 0.17 19.59 48.54 1.17 0.00 0.00 0.00
August 22.21 1.66 20.55 52.33 0.58 0.00 0.00 0.00
September 28.80 7.12 21.69 65.50 1.98 0.00 0.00 0.00
October 39.97 19.01 20.97 78.18 3.23 0.00 0.00 0.00
November 45.28 25.41 19.87 79.10 8.73 0.00 0.00 0.00
December 49.41 31.20 18.21 79.99 16.70 0.00 0.00 0.00
                 
Annual Sum or Average 33.28 13.60 19.68 62.92 7.47 0.00 0.00 0.00
Minimum of Months 18.46 0.04 17.93 42.90 0.58 0.00 0.00 0.00
Maximum of Months 51.25 33.32 21.69 81.44 19.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 139.10 90.45 48.65 221.04 53.27 0.00 0.00 0.00
February 122.80 69.84 52.96 205.46 42.81 0.00 0.00 0.00
March 94.90 39.24 55.67 161.85 33.72 0.00 0.00 0.00
April 68.05 13.94 54.11 131.03 19.60 0.00 0.00 0.00
May 53.13 1.69 51.44 116.44 5.43 0.00 0.00 0.00
June 50.12 0.10 50.01 120.11 1.71 0.00 0.00 0.00
July 53.62 0.45 53.17 131.73 3.18 0.00 0.00 0.00
August 60.28 4.51 55.78 142.03 1.57 0.00 0.00 0.00
September 78.17 19.31 58.86 177.79 5.38 0.00 0.00 0.00
October 108.49 51.59 56.91 212.19 8.78 0.00 0.00 0.00
November 122.91 68.98 53.93 214.70 23.70 0.00 0.00 0.00
December 134.11 84.68 49.43 217.10 45.32 0.00 0.00 0.00
                 
Annual Sum or Average 90.33 36.92 53.40 170.78 20.27 0.00 0.00 0.00
Minimum of Months 50.12 0.10 48.65 116.44 1.57 0.00 0.00 0.00
Maximum of Months 139.10 90.45 58.86 221.04 53.27 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.84 71.42 38.42 175.18 33.11 0.00 0.00 0.00
February 96.96 55.15 41.82 162.72 25.78 0.00 0.00 0.00
March 74.94 30.98 43.95 128.37 18.69 0.00 0.00 0.00
April 53.73 11.01 42.72 105.29 7.90 0.00 0.00 0.00
May 41.95 1.33 40.62 100.03 1.20 0.00 0.00 0.00
June 39.57 0.08 39.49 106.11 0.07 0.00 0.00 0.00
July 42.34 0.36 41.99 113.60 0.41 0.00 0.00 0.00
August 47.60 3.56 44.04 123.09 0.03 0.00 0.00 0.00
September 61.73 15.25 46.48 148.64 0.59 0.00 0.00 0.00
October 85.67 40.73 44.93 174.70 1.78 0.00 0.00 0.00
November 97.05 54.47 42.58 174.27 11.74 0.00 0.00 0.00
December 105.90 66.86 39.03 172.05 26.87 0.00 0.00 0.00
                 
Annual Sum or Average 71.32 29.15 42.17 140.23 10.62 0.00 0.00 0.00
Minimum of Months 39.57 0.08 38.42 100.03 0.03 0.00 0.00 0.00
Maximum of Months 109.84 71.42 46.48 175.18 33.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 94.49 40.86 53.63 141.02 66.02 0.00 0.00 0.00
February 118.59 54.01 64.58 193.09 51.29 0.00 0.00 0.00
March 146.90 67.15 79.75 238.62 36.71 0.00 0.00 0.00
April 161.24 74.56 86.68 288.28 14.60 0.00 0.00 0.00
May 147.47 56.94 90.54 302.93 2.22 0.00 0.00 0.00
June 124.86 35.04 89.82 287.75 0.14 0.00 0.00 0.00
July 139.32 43.06 96.27 318.55 0.76 0.00 0.00 0.00
August 139.00 45.18 93.82 311.02 0.05 0.00 0.00 0.00
September 118.61 34.96 83.66 272.49 1.12 0.00 0.00 0.00
October 118.21 46.17 72.04 244.64 3.34 0.00 0.00 0.00
November 97.25 35.62 61.63 181.71 23.38 0.00 0.00 0.00
December 97.50 43.57 53.92 153.97 52.26 0.00 0.00 0.00
                 
Annual Sum or Average 125.34 48.08 77.26 244.78 20.87 0.00 0.00 0.00
Minimum of Months 94.49 34.96 53.63 141.02 0.05 0.00 0.00 0.00
Maximum of Months 161.24 74.56 96.27 318.55 66.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.33 0.00 23.33 31.15 34.31 0.00 0.00 0.00
February 27.61 0.00 27.61 43.98 26.54 0.00 0.00 0.00
March 32.94 0.00 32.94 51.21 19.28 0.00 0.00 0.00
April 37.01 0.21 36.79 69.94 7.57 0.00 0.00 0.00
May 42.02 1.72 40.30 99.36 1.16 0.00 0.00 0.00
June 45.04 3.24 41.80 117.52 0.08 0.00 0.00 0.00
July 45.63 2.27 43.35 120.38 0.42 0.00 0.00 0.00
August 40.41 0.42 39.98 107.70 0.03 0.00 0.00 0.00
September 35.78 0.01 35.77 98.00 0.58 0.00 0.00 0.00
October 29.96 0.00 29.96 74.62 1.63 0.00 0.00 0.00
November 26.05 0.00 26.05 53.91 11.94 0.00 0.00 0.00
December 23.07 0.00 23.07 34.50 27.05 0.00 0.00 0.00
                 
Annual Sum or Average 34.10 0.66 33.44 75.34 10.82 0.00 0.00 0.00
Minimum of Months 23.07 0.00 23.07 31.15 0.03 0.00 0.00 0.00
Maximum of Months 45.63 3.24 43.35 120.38 34.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 94.49 40.86 53.63 146.80 62.87 0.00 0.00 0.00
February 118.59 54.01 64.58 197.59 49.14 0.00 0.00 0.00
March 146.90 67.15 79.75 241.76 35.42 0.00 0.00 0.00
April 161.24 74.56 86.68 289.50 14.20 0.00 0.00 0.00
May 147.47 56.94 90.54 302.92 2.21 0.00 0.00 0.00
June 124.86 35.04 89.82 287.29 0.14 0.00 0.00 0.00
July 139.32 43.06 96.27 318.27 0.77 0.00 0.00 0.00
August 139.00 45.18 93.82 311.57 0.04 0.00 0.00 0.00
September 118.61 34.96 83.66 274.33 1.03 0.00 0.00 0.00
October 118.21 46.17 72.04 248.15 2.99 0.00 0.00 0.00
November 97.25 35.62 61.63 186.13 22.25 0.00 0.00 0.00
December 97.50 43.57 53.92 159.20 49.54 0.00 0.00 0.00
                 
Annual Sum or Average 125.34 48.08 77.26 247.23 19.93 0.00 0.00 0.00
Minimum of Months 94.49 34.96 53.63 146.80 0.04 0.00 0.00 0.00
Maximum of Months 161.24 74.56 96.27 318.27 62.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 161.09 104.75 56.34 253.46 50.62 0.00 0.00 0.00
February 142.21 80.88 61.33 236.88 38.61 0.00 0.00 0.00
March 109.90 45.44 64.46 188.81 26.82 0.00 0.00 0.00
April 78.80 16.14 62.66 158.24 10.10 0.00 0.00 0.00
May 61.53 1.95 59.57 153.10 1.50 0.00 0.00 0.00
June 58.04 0.12 57.92 161.78 0.07 0.00 0.00 0.00
July 62.10 0.52 61.58 173.25 0.44 0.00 0.00 0.00
August 69.81 5.22 64.59 186.49 0.02 0.00 0.00 0.00
September 90.53 22.37 68.17 221.60 0.65 0.00 0.00 0.00
October 125.64 59.74 65.90 257.53 2.43 0.00 0.00 0.00
November 142.33 79.88 62.45 254.40 17.67 0.00 0.00 0.00
December 155.31 98.06 57.25 249.73 41.18 0.00 0.00 0.00
                 
Annual Sum or Average 104.60 42.76 61.85 207.80 15.75 0.00 0.00 0.00
Minimum of Months 58.04 0.12 56.34 153.10 0.02 0.00 0.00 0.00
Maximum of Months 161.09 104.75 68.17 257.53 50.62 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 163.29 0.00 163.29 166.29 375.76 0.00 0.00 0.00
February 193.28 0.00 193.28 248.21 309.82 0.00 0.00 0.00
March 230.56 0.00 230.56 299.71 246.59 0.00 0.00 0.00
April 259.03 1.48 257.55 425.67 138.39 0.00 0.00 0.00
May 294.14 12.05 282.09 592.37 49.52 0.00 0.00 0.00
June 315.27 22.68 292.60 698.73 16.64 0.00 0.00 0.00
July 319.36 15.90 303.47 736.96 26.36 0.00 0.00 0.00
August 282.83 2.96 279.86 629.78 16.82 0.00 0.00 0.00
September 250.44 0.06 250.38 582.89 39.76 0.00 0.00 0.00
October 209.71 0.00 209.71 426.89 64.82 0.00 0.00 0.00
November 182.34 0.00 182.34 293.36 168.01 0.00 0.00 0.00
December 161.51 0.00 161.51 186.94 317.68 0.00 0.00 0.00
                 
Annual Sum or Average 238.71 4.62 234.09 441.58 146.80 0.00 0.00 0.00
Minimum of Months 161.51 0.00 161.51 166.29 16.64 0.00 0.00 0.00
Maximum of Months 319.36 22.68 303.47 736.96 375.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 163.29 0.00 163.29 157.57 391.54 0.00 0.00 0.00
February 193.28 0.00 193.28 237.92 323.42 0.00 0.00 0.00
March 230.56 0.00 230.56 288.97 258.62 0.00 0.00 0.00
April 259.03 1.48 257.55 415.49 146.54 0.00 0.00 0.00
May 294.14 12.05 282.09 581.91 55.06 0.00 0.00 0.00
June 315.27 22.68 292.60 686.66 19.01 0.00 0.00 0.00
July 319.36 15.90 303.47 726.37 29.50 0.00 0.00 0.00
August 282.83 2.96 279.86 617.38 19.41 0.00 0.00 0.00
September 250.44 0.06 250.38 571.64 43.06 0.00 0.00 0.00
October 209.71 0.00 209.71 416.86 70.73 0.00 0.00 0.00
November 182.34 0.00 182.34 283.58 177.45 0.00 0.00 0.00
December 161.51 0.00 161.51 178.43 332.55 0.00 0.00 0.00
                 
Annual Sum or Average 238.71 4.62 234.09 431.17 154.84 0.00 0.00 0.00
Minimum of Months 161.51 0.00 161.51 157.57 19.01 0.00 0.00 0.00
Maximum of Months 319.36 22.68 303.47 726.37 391.54 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.33 0.00 23.33 29.61 52.34 0.00 0.00 0.00
February 27.61 0.00 27.61 41.54 45.07 0.00 0.00 0.00
March 32.94 0.00 32.94 50.01 36.90 0.00 0.00 0.00
April 37.01 0.21 36.79 71.21 21.91 0.00 0.00 0.00
May 42.02 1.72 40.30 97.96 10.20 0.00 0.00 0.00
June 45.04 3.24 41.80 113.95 4.35 0.00 0.00 0.00
July 45.63 2.27 43.35 121.74 6.21 0.00 0.00 0.00
August 40.41 0.42 39.98 102.74 4.45 0.00 0.00 0.00
September 35.78 0.01 35.77 96.47 6.76 0.00 0.00 0.00
October 29.96 0.00 29.96 72.70 11.25 0.00 0.00 0.00
November 26.05 0.00 26.05 51.64 25.23 0.00 0.00 0.00
December 23.07 0.00 23.07 33.39 44.14 0.00 0.00 0.00
                 
Annual Sum or Average 34.10 0.66 33.44 73.74 22.30 0.00 0.00 0.00
Minimum of Months 23.07 0.00 23.07 29.61 4.35 0.00 0.00 0.00
Maximum of Months 45.63 3.24 43.35 121.74 52.34 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 209.74 100.51 109.23 319.85 184.56 0.00 0.00 0.00
February 243.28 113.02 130.26 388.96 158.49 0.00 0.00 0.00
March 296.35 140.11 156.24 473.12 128.46 0.00 0.00 0.00
April 322.01 143.75 178.26 584.78 82.69 0.00 0.00 0.00
May 304.66 121.80 182.86 613.86 38.88 0.00 0.00 0.00
June 299.42 114.92 184.51 647.07 16.50 0.00 0.00 0.00
July 308.07 111.17 196.90 694.20 23.43 0.00 0.00 0.00
August 281.59 94.28 187.31 610.61 16.89 0.00 0.00 0.00
September 271.28 97.96 173.32 604.76 25.47 0.00 0.00 0.00
October 249.41 107.04 142.37 514.57 42.26 0.00 0.00 0.00
November 203.09 80.88 122.21 376.05 89.65 0.00 0.00 0.00
December 164.25 58.20 106.06 259.60 159.27 0.00 0.00 0.00
                 
Annual Sum or Average 262.80 106.89 155.91 507.76 80.20 0.00 0.00 0.00
Minimum of Months 164.25 58.20 106.06 259.60 16.50 0.00 0.00 0.00
Maximum of Months 322.01 143.75 196.90 694.20 184.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.84 71.42 38.42 178.11 48.57 0.00 0.00 0.00
February 96.96 55.15 41.82 164.23 41.99 0.00 0.00 0.00
March 74.94 30.98 43.95 129.55 35.06 0.00 0.00 0.00
April 53.73 11.01 42.72 107.88 21.95 0.00 0.00 0.00
May 41.95 1.33 40.62 97.08 10.33 0.00 0.00 0.00
June 39.57 0.08 39.49 101.80 4.35 0.00 0.00 0.00
July 42.34 0.36 41.99 114.28 6.23 0.00 0.00 0.00
August 47.60 3.56 44.04 117.77 4.48 0.00 0.00 0.00
September 61.73 15.25 46.48 148.74 6.75 0.00 0.00 0.00
October 85.67 40.73 44.93 175.74 11.13 0.00 0.00 0.00
November 97.05 54.47 42.58 176.04 23.81 0.00 0.00 0.00
December 105.90 66.86 39.03 175.39 41.72 0.00 0.00 0.00
                 
Annual Sum or Average 71.32 29.15 42.17 140.43 21.27 0.00 0.00 0.00
Minimum of Months 39.57 0.08 38.42 97.08 4.35 0.00 0.00 0.00
Maximum of Months 109.84 71.42 46.48 178.11 48.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 29.54 0.00 29.54 33.11 57.34 0.00 0.00 0.00
February 34.97 0.00 34.97 48.97 46.29 0.00 0.00 0.00
March 41.71 0.00 41.71 58.60 36.25 0.00 0.00 0.00
April 46.86 0.27 46.60 80.52 20.72 0.00 0.00 0.00
May 53.22 2.18 51.04 109.90 6.74 0.00 0.00 0.00
June 57.04 4.10 52.94 128.39 2.30 0.00 0.00 0.00
July 57.78 2.88 54.91 134.56 3.99 0.00 0.00 0.00
August 51.17 0.54 50.63 116.18 2.21 0.00 0.00 0.00
September 45.31 0.01 45.30 106.56 6.24 0.00 0.00 0.00
October 37.94 0.00 37.94 78.30 9.85 0.00 0.00 0.00
November 32.99 0.00 32.99 55.54 25.54 0.00 0.00 0.00
December 29.22 0.00 29.22 36.73 47.95 0.00 0.00 0.00
                 
Annual Sum or Average 43.19 0.84 42.35 82.44 22.01 0.00 0.00 0.00
Minimum of Months 29.22 0.00 29.22 33.11 2.21 0.00 0.00 0.00
Maximum of Months 57.78 4.10 54.91 134.56 57.34 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.43 0.00 26.43 29.62 51.30 0.00 0.00 0.00
February 31.29 0.00 31.29 43.81 41.41 0.00 0.00 0.00
March 37.32 0.00 37.32 52.43 32.43 0.00 0.00 0.00
April 41.93 0.24 41.69 72.04 18.53 0.00 0.00 0.00
May 47.61 1.95 45.66 98.33 6.03 0.00 0.00 0.00
June 51.04 3.67 47.36 114.87 2.06 0.00 0.00 0.00
July 51.70 2.57 49.12 120.39 3.57 0.00 0.00 0.00
August 45.78 0.48 45.30 103.94 1.98 0.00 0.00 0.00
September 40.54 0.01 40.53 95.34 5.58 0.00 0.00 0.00
October 33.95 0.00 33.95 70.06 8.82 0.00 0.00 0.00
November 29.52 0.00 29.52 49.69 22.85 0.00 0.00 0.00
December 26.14 0.00 26.14 32.86 42.90 0.00 0.00 0.00
                 
Annual Sum or Average 38.64 0.75 37.89 73.76 19.69 0.00 0.00 0.00
Minimum of Months 26.14 0.00 26.14 29.62 1.98 0.00 0.00 0.00
Maximum of Months 51.70 3.67 49.12 120.39 51.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 410.06 266.64 143.43 642.71 154.88 0.00 0.00 0.00
February 362.00 205.88 156.12 593.58 127.36 0.00 0.00 0.00
March 279.76 115.66 164.10 464.49 101.18 0.00 0.00 0.00
April 200.59 41.09 159.50 371.68 62.36 0.00 0.00 0.00
May 156.62 4.97 151.65 325.34 20.00 0.00 0.00 0.00
June 147.73 0.31 147.43 334.95 7.08 0.00 0.00 0.00
July 158.08 1.33 156.75 370.55 11.92 0.00 0.00 0.00
August 177.71 13.29 164.42 400.23 6.58 0.00 0.00 0.00
September 230.45 56.93 173.52 506.02 18.38 0.00 0.00 0.00
October 319.83 152.07 167.75 610.06 28.85 0.00 0.00 0.00
November 362.32 203.35 158.97 619.64 70.71 0.00 0.00 0.00
December 395.35 249.63 145.72 629.58 133.11 0.00 0.00 0.00
                 
Annual Sum or Average 266.27 108.84 157.43 488.55 61.57 0.00 0.00 0.00
Minimum of Months 147.73 0.31 143.43 325.34 6.58 0.00 0.00 0.00
Maximum of Months 410.06 266.64 173.52 642.71 154.88 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.148795E+10 0.967519E+09 0.520433E+09 0.230891E+10 0.574116E+09
February 0.118642E+10 0.674762E+09 0.511657E+09 0.193375E+10 0.434100E+09
March 0.101513E+10 0.419697E+09 0.595431E+09 0.168435E+10 0.388197E+09
April 0.704385E+09 0.144292E+09 0.560093E+09 0.130289E+10 0.233724E+09
May 0.568300E+09 18039893.06 0.550260E+09 0.115554E+10 90221223.26
June 0.518766E+09 1079877.92 0.517686E+09 0.113334E+10 28652061.34
July 0.573595E+09 4816469.25 0.568779E+09 0.129308E+10 53790041.21
August 0.644834E+09 48222350.38 0.596611E+09 0.139744E+10 26413013.69
September 0.809229E+09 0.199919E+09 0.609311E+09 0.172694E+10 72958145.06
October 0.116052E+10 0.551817E+09 0.608706E+09 0.218081E+10 0.131174E+09
November 0.127230E+10 0.714056E+09 0.558244E+09 0.215493E+10 0.269037E+09
December 0.143456E+10 0.905795E+09 0.528761E+09 0.227357E+10 0.498442E+09
           
Annual Sum or Average 0.113760E+11 0.465001E+10 0.672597E+10 0.205455E+11 0.280082E+10
Minimum of Months 0.518766E+09 1079877.92 0.511657E+09 0.113334E+10 26413013.69
Maximum of Months 0.148795E+10 0.967519E+09 0.609311E+09 0.230891E+10 0.574116E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.418997E+10 0.272447E+10 0.146550E+10 0.640217E+10 0.181174E+10
February 0.334088E+10 0.190008E+10 0.144079E+10 0.535791E+10 0.136785E+10
March 0.285853E+10 0.118184E+10 0.167669E+10 0.466605E+10 0.122915E+10
April 0.198350E+10 0.406316E+09 0.157718E+10 0.362039E+10 0.734747E+09
May 0.160030E+10 50799149.42 0.154950E+10 0.323100E+10 0.290987E+09
June 0.146081E+10 3040865.03 0.145777E+10 0.319239E+10 96793987.11
July 0.161521E+10 13562859.83 0.160164E+10 0.364235E+10 0.159463E+09
August 0.181581E+10 0.135791E+09 0.168002E+10 0.391602E+10 93519271.87
September 0.227874E+10 0.562957E+09 0.171578E+10 0.484050E+10 0.224590E+09
October 0.326796E+10 0.155388E+10 0.171408E+10 0.609700E+10 0.403782E+09
November 0.358271E+10 0.201074E+10 0.157198E+10 0.599718E+10 0.846088E+09
December 0.403962E+10 0.255066E+10 0.148896E+10 0.631666E+10 0.158106E+10
           
Annual Sum or Average 0.320340E+11 0.130941E+11 0.189399E+11 0.572796E+11 0.883977E+10
Minimum of Months 0.146081E+10 3040865.03 0.144079E+10 0.319239E+10 93519271.87
Maximum of Months 0.418997E+10 0.272447E+10 0.171578E+10 0.640217E+10 0.181174E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.544302E+10 0.353924E+10 0.190377E+10 0.854309E+10 0.236061E+10
February 0.433999E+10 0.246832E+10 0.187167E+10 0.716890E+10 0.176934E+10
March 0.371340E+10 0.153528E+10 0.217812E+10 0.626391E+10 0.158674E+10
April 0.257668E+10 0.527828E+09 0.204885E+10 0.487977E+10 0.936620E+09
May 0.207888E+10 65990986.10 0.201288E+10 0.436369E+10 0.362566E+09
June 0.189768E+10 3950256.73 0.189373E+10 0.431855E+10 0.120612E+09
July 0.209825E+10 17618926.79 0.208063E+10 0.493597E+10 0.198196E+09
August 0.235884E+10 0.176400E+09 0.218244E+10 0.529936E+10 0.111624E+09
September 0.296021E+10 0.731314E+09 0.222890E+10 0.653628E+10 0.278988E+09
October 0.424526E+10 0.201858E+10 0.222668E+10 0.817393E+10 0.480343E+09
November 0.465415E+10 0.261206E+10 0.204209E+10 0.801928E+10 0.107129E+10
December 0.524769E+10 0.331345E+10 0.193424E+10 0.841521E+10 0.204526E+10
           
Annual Sum or Average 0.416140E+11 0.170100E+11 0.246040E+11 0.769179E+11 0.113222E+11
Minimum of Months 0.189768E+10 3950256.73 0.187167E+10 0.431855E+10 0.111624E+09
Maximum of Months 0.544302E+10 0.353924E+10 0.222890E+10 0.854309E+10 0.236061E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.294194E+09 0.191295E+09 0.102899E+09 0.472075E+09 91648994.01
February 0.234576E+09 0.133412E+09 0.101164E+09 0.396708E+09 64558790.36
March 0.200709E+09 82981349.66 0.117728E+09 0.346960E+09 52409925.21
April 0.139270E+09 28528948.73 0.110741E+09 0.275221E+09 22178269.43
May 0.112364E+09 3566796.69 0.108797E+09 0.267700E+09 3669624.86
June 0.102570E+09 213510.41 0.102357E+09 0.274541E+09 286791.80
July 0.113411E+09 952298.69 0.112459E+09 0.304475E+09 1353160.77
August 0.127496E+09 9534386.88 0.117961E+09 0.329491E+09 121100.44
September 0.160000E+09 39527329.16 0.120472E+09 0.386404E+09 2065721.33
October 0.229456E+09 0.109104E+09 0.120353E+09 0.469326E+09 5676719.74
November 0.251556E+09 0.141181E+09 0.110375E+09 0.453807E+09 32346128.85
December 0.283637E+09 0.179091E+09 0.104546E+09 0.463956E+09 74676675.33
           
Annual Sum or Average 0.224924E+10 0.919388E+09 0.132985E+10 0.444066E+10 0.350992E+09
Minimum of Months 0.102570E+09 213510.41 0.101164E+09 0.267700E+09 121100.44
Maximum of Months 0.294194E+09 0.191295E+09 0.120472E+09 0.472075E+09 91648994.01



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.253088E+09 0.109438E+09 0.143650E+09 0.379983E+09 0.183066E+09
February 0.286903E+09 0.130669E+09 0.156234E+09 0.470233E+09 0.128435E+09
March 0.393465E+09 0.179864E+09 0.213602E+09 0.644492E+09 0.102610E+09
April 0.417943E+09 0.193256E+09 0.224687E+09 0.752890E+09 40918098.13
May 0.394988E+09 0.152497E+09 0.242491E+09 0.814524E+09 6834188.61
June 0.323637E+09 90811701.15 0.232825E+09 0.747752E+09 552453.00
July 0.373167E+09 0.115324E+09 0.257843E+09 0.856223E+09 2548953.51
August 0.372297E+09 0.121012E+09 0.251286E+09 0.835032E+09 204614.80
September 0.307449E+09 90604734.42 0.216844E+09 0.708175E+09 4023953.86
October 0.316622E+09 0.123668E+09 0.192954E+09 0.655773E+09 10813923.65
November 0.252061E+09 92323391.94 0.159737E+09 0.471998E+09 64540202.11
December 0.261142E+09 0.116710E+09 0.144432E+09 0.414910E+09 0.145216E+09
           
Annual Sum or Average 0.395276E+10 0.151618E+10 0.243658E+10 0.775198E+10 0.689763E+09
Minimum of Months 0.252061E+09 90604734.42 0.143650E+09 0.379983E+09 204614.80
Maximum of Months 0.417943E+09 0.193256E+09 0.257843E+09 0.856223E+09 0.183066E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62480615.07 0.00 62480615.07 82468667.48 95793629.15
February 66798791.70 0.00 66798791.70 0.106011E+09 66846623.19
March 88222215.26 1556.86 88220658.39 0.137590E+09 54188455.77
April 95917903.38 547620.98 95370282.40 0.182262E+09 21293538.38
May 0.112552E+09 4610857.06 0.107941E+09 0.266328E+09 3534460.83
June 0.116746E+09 8396627.57 0.108349E+09 0.304790E+09 318873.53
July 0.122202E+09 6082373.67 0.116120E+09 0.322922E+09 1395797.77
August 0.108221E+09 1134477.74 0.107087E+09 0.288015E+09 127728.38
September 92738767.59 21425.30 92717342.29 0.253511E+09 2073280.83
October 80243081.80 0.00 80243081.80 0.198211E+09 5335027.09
November 67521071.96 0.00 67521071.96 0.138365E+09 33180928.03
December 61801109.67 0.00 61801109.67 91548775.68 75781786.47
           
Annual Sum or Average 0.107544E+10 20794939.18 0.105465E+10 0.237202E+10 0.359870E+09
Minimum of Months 61801109.67 0.00 61801109.67 82468667.48 127728.38
Maximum of Months 0.122202E+09 8396627.57 0.116120E+09 0.322922E+09 95793629.15



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.253088E+09 0.109438E+09 0.143650E+09 0.393605E+09 0.175719E+09
February 0.286903E+09 0.130669E+09 0.156234E+09 0.480097E+09 0.123714E+09
March 0.393465E+09 0.179864E+09 0.213602E+09 0.652178E+09 99384358.73
April 0.417943E+09 0.193256E+09 0.224687E+09 0.755949E+09 39888797.31
May 0.394988E+09 0.152497E+09 0.242491E+09 0.814535E+09 6806701.88
June 0.323637E+09 90811701.15 0.232825E+09 0.746597E+09 566244.60
July 0.373167E+09 0.115324E+09 0.257843E+09 0.855525E+09 2571725.06
August 0.372297E+09 0.121012E+09 0.251286E+09 0.836498E+09 195046.20
September 0.307449E+09 90604734.42 0.216844E+09 0.712724E+09 3750943.08
October 0.316622E+09 0.123668E+09 0.192954E+09 0.664535E+09 9801432.03
November 0.252061E+09 92323391.94 0.159737E+09 0.482403E+09 61826162.38
December 0.261142E+09 0.116710E+09 0.144432E+09 0.427192E+09 0.138852E+09
           
Annual Sum or Average 0.395276E+10 0.151618E+10 0.243658E+10 0.782184E+10 0.663077E+09
Minimum of Months 0.252061E+09 90604734.42 0.143650E+09 0.393605E+09 195046.20
Maximum of Months 0.417943E+09 0.193256E+09 0.257843E+09 0.855525E+09 0.175719E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.235309E+09 0.153006E+09 82302997.65 0.365865E+09 95702438.21
February 0.187624E+09 0.106708E+09 80915277.26 0.307146E+09 69370674.81
March 0.160536E+09 66371880.15 94163689.54 0.267978E+09 59212983.44
April 0.111394E+09 22818620.98 88575365.15 0.212859E+09 31056013.24
May 89873280.16 2852869.99 87020410.17 0.198939E+09 7942251.36
June 82039774.92 170774.37 81869000.56 0.202033E+09 1910163.57
July 90710703.00 761687.47 89949015.53 0.228522E+09 3941853.63
August 0.101976E+09 7625992.90 94350425.71 0.245128E+09 1828535.59
September 0.127974E+09 31615575.84 96358645.11 0.294361E+09 7351939.88
October 0.183529E+09 87265587.65 96262912.52 0.360129E+09 12987908.77
November 0.201205E+09 0.112922E+09 88282536.13 0.348578E+09 38814906.48
December 0.226865E+09 0.143244E+09 83620064.08 0.360727E+09 81118141.37
           
Annual Sum or Average 0.179903E+10 0.735364E+09 0.106367E+10 0.339227E+10 0.411238E+09
Minimum of Months 82039774.92 170774.37 80915277.26 0.198939E+09 1828535.59
Maximum of Months 0.235309E+09 0.153006E+09 96358645.11 0.365865E+09 95702438.21



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 49991117.79 0.00 49991117.79 72623828.99 72894281.58
February 53446117.01 0.00 53446117.01 93584513.85 49552786.42
March 70587127.69 1245.66 70585882.03 0.122354E+09 38460930.42
April 76744494.28 438154.86 76306339.42 0.161156E+09 12506453.85
May 90053455.50 3689174.61 86364280.90 0.231954E+09 2020812.78
June 93409270.91 6718192.47 86691078.44 0.261572E+09 80722.59
July 97774596.35 4866543.94 92908052.41 0.277175E+09 553955.90
August 86588371.69 907702.50 85680669.19 0.250385E+09 17972.23
September 74200848.51 17142.51 74183706.00 0.220343E+09 625669.03
October 64202974.78 0.00 64202974.78 0.176382E+09 2544748.31
November 54024017.81 0.00 54024017.81 0.123382E+09 23772698.52
December 49447441.40 0.00 49447441.40 81255813.38 56971782.65
           
Annual Sum or Average 0.860470E+09 16638156.53 0.843832E+09 0.207217E+10 0.260003E+09
Minimum of Months 49447441.40 0.00 49447441.40 72623828.99 17972.23
Maximum of Months 97774596.35 6718192.47 92908052.41 0.277175E+09 72894281.58



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.280909E+09 0.134618E+09 0.146291E+09 0.418063E+09 0.174216E+09
February 0.294295E+09 0.136722E+09 0.157574E+09 0.471480E+09 0.118302E+09
March 0.396895E+09 0.187649E+09 0.209246E+09 0.633713E+09 91199684.67
April 0.417353E+09 0.186314E+09 0.231039E+09 0.751869E+09 38141820.46
May 0.408027E+09 0.163129E+09 0.244897E+09 0.838646E+09 6248344.57
June 0.388079E+09 0.148941E+09 0.239138E+09 0.859296E+09 594982.71
July 0.412596E+09 0.148889E+09 0.263707E+09 0.926800E+09 2400817.58
August 0.377126E+09 0.126265E+09 0.250860E+09 0.846945E+09 185950.61
September 0.351604E+09 0.126961E+09 0.224643E+09 0.786738E+09 3844204.96
October 0.334034E+09 0.143355E+09 0.190679E+09 0.688565E+09 10222638.13
November 0.263220E+09 0.104823E+09 0.158397E+09 0.486055E+09 59559345.79
December 0.219983E+09 77942147.70 0.142041E+09 0.341602E+09 0.140347E+09
           
Annual Sum or Average 0.414412E+10 0.168561E+10 0.245851E+10 0.804977E+10 0.645263E+09
Minimum of Months 0.219983E+09 77942147.70 0.142041E+09 0.341602E+09 185950.61
Maximum of Months 0.417353E+09 0.187649E+09 0.263707E+09 0.926800E+09 0.174216E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.294194E+09 0.191295E+09 0.102899E+09 0.469437E+09 91216204.13
February 0.234576E+09 0.133412E+09 0.101164E+09 0.394675E+09 63749880.62
March 0.200709E+09 82981349.66 0.117728E+09 0.344253E+09 51213585.40
April 0.139270E+09 28528948.73 0.110741E+09 0.273446E+09 21140044.04
May 0.112364E+09 3566796.69 0.108797E+09 0.266881E+09 3536433.81
June 0.102570E+09 213510.41 0.102357E+09 0.272145E+09 324656.75
July 0.113411E+09 952298.69 0.112459E+09 0.302922E+09 1332836.13
August 0.127496E+09 9534386.88 0.117961E+09 0.329073E+09 98581.02
September 0.160000E+09 39527329.16 0.120472E+09 0.384722E+09 2098830.19
October 0.229456E+09 0.109104E+09 0.120353E+09 0.468278E+09 5486608.00
November 0.251556E+09 0.141181E+09 0.110375E+09 0.452569E+09 31955724.33
December 0.283637E+09 0.179091E+09 0.104546E+09 0.463797E+09 73454502.44
           
Annual Sum or Average 0.224924E+10 0.919388E+09 0.132985E+10 0.442220E+10 0.345608E+09
Minimum of Months 0.102570E+09 213510.41 0.101164E+09 0.266881E+09 98581.02
Maximum of Months 0.294194E+09 0.191295E+09 0.120472E+09 0.469437E+09 91216204.13



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62480615.07 0.00 62480615.07 79622748.92 95549613.36
February 66798791.70 0.00 66798791.70 0.103662E+09 66337150.09
March 88222215.26 1556.86 88220658.39 0.134919E+09 53557688.19
April 95917903.38 547620.98 95370282.40 0.180344E+09 20302490.28
May 0.112552E+09 4610857.06 0.107941E+09 0.265485E+09 3398706.11
June 0.116746E+09 8396627.57 0.108349E+09 0.302424E+09 357787.75
July 0.122202E+09 6082373.67 0.116120E+09 0.321373E+09 1375678.44
August 0.108221E+09 1134477.74 0.107087E+09 0.287564E+09 105877.33
September 92738767.59 21425.30 92717342.29 0.251654E+09 2112421.09
October 80243081.80 0.00 80243081.80 0.196874E+09 5170897.16
November 67521071.96 0.00 67521071.96 0.136866E+09 32864725.88
December 61801109.67 0.00 61801109.67 91187762.00 74288032.70
           
Annual Sum or Average 0.107544E+10 20794939.18 0.105465E+10 0.235198E+10 0.355421E+09
Minimum of Months 61801109.67 0.00 61801109.67 79622748.92 105877.33
Maximum of Months 0.122202E+09 8396627.57 0.116120E+09 0.321373E+09 95549613.36



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.280909E+09 0.134618E+09 0.146291E+09 0.430700E+09 0.166541E+09
February 0.294295E+09 0.136722E+09 0.157574E+09 0.480585E+09 0.113700E+09
March 0.396895E+09 0.187649E+09 0.209246E+09 0.640745E+09 88101046.16
April 0.417353E+09 0.186314E+09 0.231039E+09 0.754727E+09 37127293.46
May 0.408027E+09 0.163129E+09 0.244897E+09 0.838701E+09 6223987.22
June 0.388079E+09 0.148941E+09 0.239138E+09 0.858248E+09 608325.89
July 0.412596E+09 0.148889E+09 0.263707E+09 0.926160E+09 2421559.27
August 0.377126E+09 0.126265E+09 0.250860E+09 0.848408E+09 176722.61
September 0.351604E+09 0.126961E+09 0.224643E+09 0.791100E+09 3582218.10
October 0.334034E+09 0.143355E+09 0.190679E+09 0.697006E+09 9288276.03
November 0.263220E+09 0.104823E+09 0.158397E+09 0.496148E+09 56955654.93
December 0.219983E+09 77942147.70 0.142041E+09 0.353721E+09 0.133183E+09
           
Annual Sum or Average 0.414412E+10 0.168561E+10 0.245851E+10 0.811625E+10 0.617909E+09
Minimum of Months 0.219983E+09 77942147.70 0.142041E+09 0.353721E+09 176722.61
Maximum of Months 0.417353E+09 0.187649E+09 0.263707E+09 0.926160E+09 0.166541E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 79127756.68 0.00 79127756.68 93070444.12 0.155947E+09
February 84596454.92 0.00 84596454.92 0.124787E+09 0.111364E+09
March 0.111728E+09 1971.67 0.111726E+09 0.165377E+09 95780722.97
April 0.121474E+09 693527.42 0.120780E+09 0.219935E+09 49949696.38
May 0.142540E+09 5839359.54 0.136701E+09 0.310293E+09 14336340.13
June 0.147852E+09 10633799.02 0.137218E+09 0.350072E+09 4355940.64
July 0.154761E+09 7702942.47 0.147058E+09 0.376545E+09 8464859.01
August 0.137055E+09 1436744.47 0.135618E+09 0.327252E+09 4262949.93
September 0.117448E+09 27133.79 0.117421E+09 0.290259E+09 14124147.47
October 0.101623E+09 0.00 0.101623E+09 0.220610E+09 23998506.11
November 85511177.30 0.00 85511177.30 0.152261E+09 65870257.16
December 78267205.96 0.00 78267205.96 0.103821E+09 0.128997E+09
           
Annual Sum or Average 0.136198E+10 26335478.38 0.133565E+10 0.273428E+10 0.677452E+09
Minimum of Months 78267205.96 0.00 78267205.96 93070444.12 4262949.93
Maximum of Months 0.154761E+09 10633799.02 0.147058E+09 0.376545E+09 0.155947E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 29169767.54 0.00 29169767.54 34309619.45 57488418.97
February 31185756.15 0.00 31185756.15 46001702.39 41053506.61
March 41187518.84 726.84 41186792.00 60964977.73 35308740.45
April 44780336.12 255662.92 44524673.20 81077135.92 18413526.34
May 52546101.77 2152629.72 50393472.05 0.114387E+09 5284968.59
June 54504216.72 3920058.63 50584158.09 0.129051E+09 1605780.08
July 57051379.78 2839623.55 54211756.23 0.138810E+09 3120497.53
August 50524228.81 529643.50 49994585.30 0.120639E+09 1571499.86
September 43296121.35 10002.64 43286118.71 0.107001E+09 5206745.59
October 37462371.96 0.00 37462371.96 81326021.63 8847127.79
November 31522960.69 0.00 31522960.69 56129725.49 24282504.26
December 28852532.91 0.00 28852532.91 38272741.94 47553650.26
           
Annual Sum or Average 0.502083E+09 9708347.80 0.492375E+09 0.100797E+10 0.249737E+09
Minimum of Months 28852532.91 0.00 28852532.91 34309619.45 1571499.86
Maximum of Months 57051379.78 3920058.63 54211756.23 0.138810E+09 57488418.97



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.137270E+09 89257568.62 48012355.27 0.218128E+09 52565398.75
February 0.109452E+09 62249486.00 47202813.38 0.183132E+09 38161011.78
March 93650183.18 38718763.36 54931419.82 0.159716E+09 33274404.20
April 64982902.08 13311492.51 51671409.57 0.125135E+09 18721910.72
May 52428562.51 1664252.96 50764309.54 0.114904E+09 5358498.81
June 47858801.41 99623.10 47759178.32 0.114703E+09 1637607.21
July 52917082.30 444338.73 52472743.56 0.129996E+09 3134727.84
August 59489060.90 4448706.50 55040354.41 0.140156E+09 1549981.24
September 74655163.70 18443292.50 56211871.19 0.169785E+09 5139120.06
October 0.107063E+09 50907336.51 56156024.54 0.209394E+09 8664524.32
November 0.117375E+09 65874561.67 51500584.55 0.205036E+09 22636358.61
December 0.132344E+09 83563227.84 48780680.41 0.214235E+09 44726519.66
           
Annual Sum or Average 0.104949E+10 0.428983E+09 0.620504E+09 0.198432E+10 0.235570E+09
Minimum of Months 47858801.41 99623.10 47202813.38 0.114703E+09 1549981.24
Maximum of Months 0.137270E+09 89257568.62 56211871.19 0.218128E+09 52565398.75



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.372579E+09 0.242263E+09 0.130315E+09 0.592045E+09 0.142673E+09
February 0.297076E+09 0.168958E+09 0.128118E+09 0.497056E+09 0.103577E+09
March 0.254186E+09 0.105091E+09 0.149095E+09 0.433502E+09 90313539.12
April 0.176377E+09 36130113.49 0.140247E+09 0.339641E+09 50815095.19
May 0.142302E+09 4517122.96 0.137785E+09 0.311874E+09 14544061.82
June 0.129899E+09 270397.47 0.129628E+09 0.311328E+09 4444800.92
July 0.143628E+09 1206026.21 0.142422E+09 0.352836E+09 8508292.55
August 0.161465E+09 12074699.40 0.149391E+09 0.380412E+09 4206966.13
September 0.202629E+09 50058868.35 0.152571E+09 0.460832E+09 13948623.01
October 0.290592E+09 0.138173E+09 0.152419E+09 0.568337E+09 23517291.30
November 0.318580E+09 0.178797E+09 0.139783E+09 0.556510E+09 61439707.44
December 0.359208E+09 0.226808E+09 0.132401E+09 0.581477E+09 0.121397E+09
           
Annual Sum or Average 0.284852E+10 0.116435E+10 0.168417E+10 0.538585E+10 0.639385E+09
Minimum of Months 0.129899E+09 270397.47 0.128118E+09 0.311328E+09 4206966.13
Maximum of Months 0.372579E+09 0.242263E+09 0.152571E+09 0.592045E+09 0.142673E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.294194E+09 0.191295E+09 0.102899E+09 0.469205E+09 88672031.04
February 0.234576E+09 0.133412E+09 0.101164E+09 0.393655E+09 62376027.20
March 0.200709E+09 82981349.66 0.117728E+09 0.343817E+09 50069264.33
April 0.139270E+09 28528948.73 0.110741E+09 0.272917E+09 20479019.54
May 0.112364E+09 3566796.69 0.108797E+09 0.267929E+09 3203845.50
June 0.102570E+09 213510.41 0.102357E+09 0.275030E+09 192742.54
July 0.113411E+09 952298.69 0.112459E+09 0.304264E+09 1097696.90
August 0.127496E+09 9534386.88 0.117961E+09 0.329676E+09 86215.22
September 0.160000E+09 39527329.16 0.120472E+09 0.385287E+09 1524071.27
October 0.229456E+09 0.109104E+09 0.120353E+09 0.467907E+09 4771479.78
November 0.251556E+09 0.141181E+09 0.110375E+09 0.451697E+09 30425734.14
December 0.283637E+09 0.179091E+09 0.104546E+09 0.460825E+09 71975585.93
           
Annual Sum or Average 0.224924E+10 0.919388E+09 0.132985E+10 0.442221E+10 0.334874E+09
Minimum of Months 0.102570E+09 213510.41 0.101164E+09 0.267929E+09 86215.22
Maximum of Months 0.294194E+09 0.191295E+09 0.120472E+09 0.469205E+09 88672031.04



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.253088E+09 0.109438E+09 0.143650E+09 0.377698E+09 0.176836E+09
February 0.286903E+09 0.130669E+09 0.156234E+09 0.467115E+09 0.124086E+09
March 0.393465E+09 0.179864E+09 0.213602E+09 0.639129E+09 98332448.71
April 0.417943E+09 0.193256E+09 0.224687E+09 0.747210E+09 37840801.28
May 0.394988E+09 0.152497E+09 0.242491E+09 0.811365E+09 5952956.01
June 0.323637E+09 90811701.15 0.232825E+09 0.745859E+09 362428.11
July 0.373167E+09 0.115324E+09 0.257843E+09 0.853202E+09 2045247.68
August 0.372297E+09 0.121012E+09 0.251286E+09 0.833028E+09 127438.79
September 0.307449E+09 90604734.42 0.216844E+09 0.706292E+09 2904367.10
October 0.316622E+09 0.123668E+09 0.192954E+09 0.655250E+09 8955694.99
November 0.252061E+09 92323391.94 0.159737E+09 0.470981E+09 60601723.42
December 0.261142E+09 0.116710E+09 0.144432E+09 0.412380E+09 0.139968E+09
           
Annual Sum or Average 0.395276E+10 0.151618E+10 0.243658E+10 0.771951E+10 0.658013E+09
Minimum of Months 0.252061E+09 90604734.42 0.143650E+09 0.377698E+09 127438.79
Maximum of Months 0.417943E+09 0.193256E+09 0.257843E+09 0.853202E+09 0.176836E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62480615.07 0.00 62480615.07 83438395.44 91883329.59
February 66798791.70 0.00 66798791.70 0.106404E+09 64205444.70
March 88222215.26 1556.86 88220658.39 0.137166E+09 51641669.63
April 95917903.38 547620.98 95370282.40 0.181279E+09 19608857.09
May 0.112552E+09 4610857.06 0.107941E+09 0.266130E+09 3114741.00
June 0.116746E+09 8396627.57 0.108349E+09 0.304623E+09 215839.11
July 0.122202E+09 6082373.67 0.116120E+09 0.322428E+09 1128481.22
August 0.108221E+09 1134477.74 0.107087E+09 0.288453E+09 85497.56
September 92738767.59 21425.30 92717342.29 0.254016E+09 1490768.90
October 80243081.80 0.00 80243081.80 0.199866E+09 4365170.63
November 67521071.96 0.00 67521071.96 0.139735E+09 30944767.01
December 61801109.67 0.00 61801109.67 92410198.63 72442898.26
           
Annual Sum or Average 0.107544E+10 20794939.18 0.105465E+10 0.237595E+10 0.341127E+09
Minimum of Months 61801109.67 0.00 61801109.67 83438395.44 85497.56
Maximum of Months 0.122202E+09 8396627.57 0.116120E+09 0.322428E+09 91883329.59



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.253088E+09 0.109438E+09 0.143650E+09 0.393189E+09 0.168399E+09
February 0.286903E+09 0.130669E+09 0.156234E+09 0.478012E+09 0.118875E+09
March 0.393465E+09 0.179864E+09 0.213602E+09 0.647535E+09 94875180.63
April 0.417943E+09 0.193256E+09 0.224687E+09 0.750394E+09 36795615.45
May 0.394988E+09 0.152497E+09 0.242491E+09 0.811336E+09 5926826.75
June 0.323637E+09 90811701.15 0.232825E+09 0.744645E+09 373782.98
July 0.373167E+09 0.115324E+09 0.257843E+09 0.852454E+09 2066996.07
August 0.372297E+09 0.121012E+09 0.251286E+09 0.834522E+09 119817.03
September 0.307449E+09 90604734.42 0.216844E+09 0.711069E+09 2661661.68
October 0.316622E+09 0.123668E+09 0.192954E+09 0.664645E+09 8017375.62
November 0.252061E+09 92323391.94 0.159737E+09 0.482461E+09 57660371.17
December 0.261142E+09 0.116710E+09 0.144432E+09 0.426393E+09 0.132684E+09
           
Annual Sum or Average 0.395276E+10 0.151618E+10 0.243658E+10 0.779666E+10 0.628456E+09
Minimum of Months 0.252061E+09 90604734.42 0.143650E+09 0.393189E+09 119817.03
Maximum of Months 0.417943E+09 0.193256E+09 0.257843E+09 0.852454E+09 0.168399E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.431464E+09 0.280553E+09 0.150912E+09 0.678872E+09 0.135585E+09
February 0.344028E+09 0.195661E+09 0.148367E+09 0.573063E+09 93398643.00
March 0.294360E+09 0.121700E+09 0.172659E+09 0.505720E+09 71829294.80
April 0.204253E+09 41840441.24 0.162413E+09 0.410148E+09 26177259.58
May 0.164793E+09 5231049.65 0.159561E+09 0.410056E+09 4007677.76
June 0.150429E+09 313133.51 0.150116E+09 0.419337E+09 177792.69
July 0.166328E+09 1396637.42 0.164931E+09 0.464043E+09 1176259.01
August 0.186985E+09 13983093.38 0.173002E+09 0.499495E+09 43224.04
September 0.234655E+09 57970621.67 0.176684E+09 0.574378E+09 1675444.67
October 0.336520E+09 0.160011E+09 0.176509E+09 0.689779E+09 6507944.51
November 0.368931E+09 0.207056E+09 0.161876E+09 0.659399E+09 45791258.90
December 0.415981E+09 0.262654E+09 0.153327E+09 0.668877E+09 0.110294E+09
           
Annual Sum or Average 0.329873E+10 0.134837E+10 0.195036E+10 0.655317E+10 0.496665E+09
Minimum of Months 0.150429E+09 313133.51 0.148367E+09 0.410056E+09 43224.04
Maximum of Months 0.431464E+09 0.280553E+09 0.176684E+09 0.689779E+09 0.135585E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.437348E+09 0.00 0.437348E+09 0.445386E+09 0.100644E+10
February 0.467574E+09 0.00 0.467574E+09 0.600462E+09 0.749526E+09
March 0.617532E+09 10897.63 0.617521E+09 0.802731E+09 0.660464E+09
April 0.671400E+09 3833201.69 0.667567E+09 0.110334E+10 0.358710E+09
May 0.787833E+09 32274777.04 0.755559E+09 0.158659E+10 0.132631E+09
June 0.817192E+09 58774166.93 0.758418E+09 0.181112E+10 43139888.22
July 0.855382E+09 42575003.16 0.812807E+09 0.197388E+10 70597042.81
August 0.757519E+09 7941043.40 0.749578E+09 0.168680E+10 45049338.50
September 0.649147E+09 149971.41 0.648997E+09 0.151084E+10 0.103061E+09
October 0.561680E+09 0.00 0.561680E+09 0.114340E+10 0.173620E+09
November 0.472630E+09 0.00 0.472630E+09 0.760383E+09 0.435483E+09
December 0.432591E+09 0.00 0.432591E+09 0.500694E+09 0.850883E+09
           
Annual Sum or Average 0.752783E+10 0.145559E+09 0.738227E+10 0.139256E+11 0.462961E+10
Minimum of Months 0.432591E+09 0.00 0.432591E+09 0.445386E+09 43139888.22
Maximum of Months 0.855382E+09 58774166.93 0.812807E+09 0.197388E+10 0.100644E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.437348E+09 0.00 0.437348E+09 0.422048E+09 0.104870E+10
February 0.467574E+09 0.00 0.467574E+09 0.575564E+09 0.782412E+09
March 0.617532E+09 10897.63 0.617521E+09 0.773983E+09 0.692678E+09
April 0.671400E+09 3833201.69 0.667567E+09 0.107695E+10 0.379841E+09
May 0.787833E+09 32274777.04 0.755559E+09 0.155859E+10 0.147460E+09
June 0.817192E+09 58774166.93 0.758418E+09 0.177983E+10 49285753.33
July 0.855382E+09 42575003.16 0.812807E+09 0.194550E+10 79000250.39
August 0.757519E+09 7941043.40 0.749578E+09 0.165360E+10 51997997.79
September 0.649147E+09 149971.41 0.648997E+09 0.148168E+10 0.111615E+09
October 0.561680E+09 0.00 0.561680E+09 0.111653E+10 0.189435E+09
November 0.472630E+09 0.00 0.472630E+09 0.735052E+09 0.459942E+09
December 0.432591E+09 0.00 0.432591E+09 0.477907E+09 0.890699E+09
           
Annual Sum or Average 0.752783E+10 0.145559E+09 0.738227E+10 0.135972E+11 0.488306E+10
Minimum of Months 0.432591E+09 0.00 0.432591E+09 0.422048E+09 49285753.33
Maximum of Months 0.855382E+09 58774166.93 0.812807E+09 0.194550E+10 0.104870E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62480615.07 0.00 62480615.07 79318295.96 0.140182E+09
February 66798791.70 0.00 66798791.70 0.100498E+09 0.109029E+09
March 88222215.26 1556.86 88220658.39 0.133950E+09 98825449.58
April 95917903.38 547620.98 95370282.40 0.184566E+09 56782526.02
May 0.112552E+09 4610857.06 0.107941E+09 0.262372E+09 27321383.74
June 0.116746E+09 8396627.57 0.108349E+09 0.295359E+09 11286925.24
July 0.122202E+09 6082373.67 0.116120E+09 0.326068E+09 16630482.00
August 0.108221E+09 1134477.74 0.107087E+09 0.275191E+09 11920236.50
September 92738767.59 21425.30 92717342.29 0.250057E+09 17514949.04
October 80243081.80 0.00 80243081.80 0.194709E+09 30137399.73
November 67521071.96 0.00 67521071.96 0.133843E+09 65406905.42
December 61801109.67 0.00 61801109.67 89430336.68 0.118217E+09
           
Annual Sum or Average 0.107544E+10 20794939.18 0.105465E+10 0.232536E+10 0.703254E+09
Minimum of Months 61801109.67 0.00 61801109.67 79318295.96 11286925.24
Maximum of Months 0.122202E+09 8396627.57 0.116120E+09 0.326068E+09 0.140182E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.561778E+09 0.269218E+09 0.292561E+09 0.856688E+09 0.494336E+09
February 0.588549E+09 0.273424E+09 0.315125E+09 0.940977E+09 0.383422E+09
March 0.793733E+09 0.375272E+09 0.418462E+09 0.126721E+10 0.344078E+09
April 0.834647E+09 0.372602E+09 0.462045E+09 0.151574E+10 0.214343E+09
May 0.815995E+09 0.326235E+09 0.489760E+09 0.164417E+10 0.104123E+09
June 0.776103E+09 0.297862E+09 0.478241E+09 0.167720E+10 42758164.16
July 0.825133E+09 0.297756E+09 0.527377E+09 0.185933E+10 62746536.84
August 0.754198E+09 0.252513E+09 0.501685E+09 0.163546E+10 45242600.64
September 0.703159E+09 0.253905E+09 0.449254E+09 0.156753E+10 66023479.72
October 0.668020E+09 0.286690E+09 0.381330E+09 0.137823E+10 0.113180E+09
November 0.526403E+09 0.209630E+09 0.316772E+09 0.974734E+09 0.232365E+09
December 0.439935E+09 0.155873E+09 0.284062E+09 0.695306E+09 0.426600E+09
           
Annual Sum or Average 0.828765E+10 0.337098E+10 0.491667E+10 0.160126E+11 0.252922E+10
Minimum of Months 0.439935E+09 0.155873E+09 0.284062E+09 0.695306E+09 42758164.16
Maximum of Months 0.834647E+09 0.375272E+09 0.527377E+09 0.185933E+10 0.494336E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.294194E+09 0.191295E+09 0.102899E+09 0.477042E+09 0.130080E+09
February 0.234576E+09 0.133412E+09 0.101164E+09 0.397315E+09 0.101587E+09
March 0.200709E+09 82981349.66 0.117728E+09 0.346982E+09 93891343.32
April 0.139270E+09 28528948.73 0.110741E+09 0.279617E+09 56898835.68
May 0.112364E+09 3566796.69 0.108797E+09 0.260029E+09 27671472.17
June 0.102570E+09 213510.41 0.102357E+09 0.263867E+09 11264458.47
July 0.113411E+09 952298.69 0.112459E+09 0.306075E+09 16698021.96
August 0.127496E+09 9534386.88 0.117961E+09 0.315431E+09 11986263.42
September 0.160000E+09 39527329.16 0.120472E+09 0.385538E+09 17500724.49
October 0.229456E+09 0.109104E+09 0.120353E+09 0.470711E+09 29811299.50
November 0.251556E+09 0.141181E+09 0.110375E+09 0.456300E+09 61721718.53
December 0.283637E+09 0.179091E+09 0.104546E+09 0.469777E+09 0.111756E+09
           
Annual Sum or Average 0.224924E+10 0.919388E+09 0.132985E+10 0.442868E+10 0.670867E+09
Minimum of Months 0.102570E+09 213510.41 0.101164E+09 0.260029E+09 11264458.47
Maximum of Months 0.294194E+09 0.191295E+09 0.120472E+09 0.477042E+09 0.130080E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 79127756.68 0.00 79127756.68 88672455.80 0.153584E+09
February 84596454.92 0.00 84596454.92 0.118464E+09 0.111980E+09
March 0.111728E+09 1971.67 0.111726E+09 0.156965E+09 97082261.23
April 0.121474E+09 693527.42 0.120780E+09 0.208709E+09 53695847.34
May 0.142540E+09 5839359.54 0.136701E+09 0.294352E+09 18056356.08
June 0.147852E+09 10633799.02 0.137218E+09 0.332793E+09 5957796.07
July 0.154761E+09 7702942.47 0.147058E+09 0.360397E+09 10683892.01
August 0.137055E+09 1436744.47 0.135618E+09 0.311167E+09 5929828.92
September 0.117448E+09 27133.79 0.117421E+09 0.276197E+09 16165585.75
October 0.101623E+09 0.00 0.101623E+09 0.209723E+09 26389427.49
November 85511177.30 0.00 85511177.30 0.143951E+09 66193852.75
December 78267205.96 0.00 78267205.96 98381981.83 0.128433E+09
           
Annual Sum or Average 0.136198E+10 26335478.38 0.133565E+10 0.259977E+10 0.694152E+09
Minimum of Months 78267205.96 0.00 78267205.96 88672455.80 5929828.92
Maximum of Months 0.154761E+09 10633799.02 0.147058E+09 0.360397E+09 0.153584E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70795903.72 0.00 70795903.72 79335582.05 0.137410E+09
February 75688768.75 0.00 75688768.75 0.105990E+09 0.100189E+09
March 99963347.83 1764.06 99961583.77 0.140437E+09 86859866.96
April 0.108683E+09 620501.61 0.108063E+09 0.186733E+09 48041878.07
May 0.127531E+09 5224497.11 0.122306E+09 0.263358E+09 16155090.20
June 0.132283E+09 9514100.27 0.122769E+09 0.297751E+09 5330462.72
July 0.138465E+09 6891851.82 0.131574E+09 0.322449E+09 9558918.66
August 0.122624E+09 1285460.72 0.121338E+09 0.278403E+09 5305440.40
September 0.105081E+09 24276.70 0.105057E+09 0.247115E+09 14463410.82
October 90922304.24 0.00 90922304.24 0.187640E+09 23611229.27
November 76507174.33 0.00 76507174.33 0.128794E+09 59223806.26
December 70025965.73 0.00 70025965.73 88022726.99 0.114908E+09
           
Annual Sum or Average 0.121857E+10 23562452.29 0.119501E+10 0.232603E+10 0.621057E+09
Minimum of Months 70025965.73 0.00 70025965.73 79335582.05 5305440.40
Maximum of Months 0.138465E+09 9514100.27 0.131574E+09 0.322449E+09 0.137410E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.109832E+10 0.714162E+09 0.384153E+09 0.172144E+10 0.414824E+09
February 0.875743E+09 0.498067E+09 0.377676E+09 0.143599E+10 0.308118E+09
March 0.749308E+09 0.309794E+09 0.439514E+09 0.124408E+10 0.270993E+09
April 0.519937E+09 0.106507E+09 0.413430E+09 0.963384E+09 0.161642E+09
May 0.419488E+09 13315914.90 0.406172E+09 0.871384E+09 53581197.08
June 0.382925E+09 797097.99 0.382128E+09 0.868181E+09 18349786.64
July 0.423397E+09 3555214.79 0.419842E+09 0.992469E+09 31925607.32
August 0.475980E+09 35594707.33 0.440385E+09 0.107199E+10 17619203.59
September 0.597326E+09 0.147567E+09 0.449759E+09 0.131161E+10 47644667.37
October 0.856629E+09 0.407317E+09 0.449312E+09 0.163398E+10 77263334.22
November 0.939135E+09 0.527071E+09 0.412063E+09 0.160611E+10 0.183292E+09
December 0.105890E+10 0.668601E+09 0.390301E+09 0.168626E+10 0.356510E+09
           
Annual Sum or Average 0.839708E+10 0.343235E+10 0.496474E+10 0.154069E+11 0.194176E+10
Minimum of Months 0.382925E+09 797097.99 0.377676E+09 0.868181E+09 17619203.59
Maximum of Months 0.109832E+10 0.714162E+09 0.449759E+09 0.172144E+10 0.414824E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 862.05 214.35 555.54 361.23 194.31 0.00 0.00
February 799.33 179.44 490.42 278.92 211.50 0.00 0.00
March 628.86 144.94 379.01 156.70 222.31 0.00 0.00
April 502.66 90.17 271.75 55.67 216.09 0.00 0.00
May 431.43 33.68 212.18 6.74 205.44 0.00 0.00
June 437.25 11.05 200.14 0.42 199.72 0.00 0.00
July 482.78 20.08 214.16 1.80 212.36 0.00 0.00
August 521.74 9.86 240.75 18.00 222.75 0.00 0.00
September 666.26 28.15 312.20 77.13 235.07 0.00 0.00
October 814.22 48.97 433.29 206.02 227.26 0.00 0.00
November 831.38 103.79 490.86 275.48 215.37 0.00 0.00
December 848.85 186.10 535.60 338.19 197.42 0.00 0.00
               
Annual Sum or Average 651.49 88.81 360.73 147.45 213.28 0.00 0.00
Minimum of Months 431.43 9.86 200.14 0.42 194.31 0.00 0.00
Maximum of Months 862.05 214.35 555.54 361.23 235.07 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2390.29 676.42 1564.36 1017.20 547.16 0.00 0.00
February 2214.74 565.42 1380.98 785.42 595.57 0.00 0.00
March 1742.10 458.91 1067.25 441.25 626.01 0.00 0.00
April 1396.75 283.47 765.24 156.76 608.48 0.00 0.00
May 1206.32 108.64 597.48 18.97 578.52 0.00 0.00
June 1231.63 37.34 563.58 1.17 562.41 0.00 0.00
July 1359.90 59.54 603.05 5.06 597.99 0.00 0.00
August 1462.08 34.92 677.95 50.70 627.25 0.00 0.00
September 1867.48 86.65 879.14 217.19 661.95 0.00 0.00
October 2276.36 150.75 1220.12 580.15 639.96 0.00 0.00
November 2313.73 326.42 1382.22 775.75 606.47 0.00 0.00
December 2358.37 590.30 1508.22 952.31 555.91 0.00 0.00
               
Annual Sum or Average 1816.32 280.31 1015.79 415.21 600.58 0.00 0.00
Minimum of Months 1206.32 34.92 563.58 1.17 547.16 0.00 0.00
Maximum of Months 2390.29 676.42 1564.36 1017.20 661.95 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3189.63 881.35 2032.19 1321.40 710.79 0.00 0.00
February 2963.34 731.38 1793.98 1020.30 773.67 0.00 0.00
March 2338.68 592.42 1386.42 573.21 813.22 0.00 0.00
April 1882.63 361.35 994.09 203.64 790.45 0.00 0.00
May 1629.21 135.37 776.16 24.64 751.52 0.00 0.00
June 1666.11 46.53 732.13 1.52 730.60 0.00 0.00
July 1842.88 74.00 783.39 6.58 776.82 0.00 0.00
August 1978.55 41.68 880.69 65.86 814.83 0.00 0.00
September 2521.71 107.63 1142.06 282.14 859.91 0.00 0.00
October 3051.79 179.34 1585.00 753.65 831.35 0.00 0.00
November 3093.86 413.31 1795.58 1007.74 787.84 0.00 0.00
December 3141.88 763.61 1959.26 1237.10 722.16 0.00 0.00
               
Annual Sum or Average 2439.05 359.02 1319.57 539.38 780.19 0.00 0.00
Minimum of Months 1629.21 41.68 732.13 1.52 710.79 0.00 0.00
Maximum of Months 3189.63 881.35 2032.19 1321.40 859.91 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 315.58 100.02 204.33 112.28 92.05 0.00 0.00
February 357.10 78.52 215.56 109.16 106.40 0.00 0.00
March 369.22 56.94 221.84 98.14 123.70 0.00 0.00
April 396.55 24.25 214.97 85.57 129.41 0.00 0.00
May 404.06 3.92 189.42 58.27 131.16 0.00 0.00
June 394.40 0.32 164.43 35.12 129.31 0.00 0.00
July 433.35 1.46 181.67 43.41 138.25 0.00 0.00
August 434.78 0.12 186.60 48.74 137.86 0.00 0.00
September 422.29 2.35 180.34 50.21 130.14 0.00 0.00
October 420.04 6.13 203.88 86.91 116.98 0.00 0.00
November 356.46 36.66 194.30 90.09 104.21 0.00 0.00
December 327.04 81.00 203.40 110.44 92.96 0.00 0.00
               
Annual Sum or Average 386.07 32.45 196.66 77.23 119.43 0.00 0.00
Minimum of Months 315.58 0.12 164.43 35.12 92.05 0.00 0.00
Maximum of Months 434.78 100.02 221.84 112.28 138.25 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 177.14 100.77 117.82 40.86 76.96 0.00 0.00
February 242.02 78.51 146.21 54.01 92.19 0.00 0.00
March 294.50 56.97 179.84 67.15 112.69 0.00 0.00
April 361.90 23.54 198.25 74.77 123.48 0.00 0.00
May 403.49 3.81 189.49 58.66 130.84 0.00 0.00
June 405.63 0.34 169.90 38.27 131.63 0.00 0.00
July 439.98 1.47 184.95 45.33 139.62 0.00 0.00
August 419.84 0.12 179.40 45.60 133.80 0.00 0.00
September 372.77 2.25 154.39 34.96 119.43 0.00 0.00
October 322.11 5.65 148.17 46.17 102.00 0.00 0.00
November 239.46 36.62 123.30 35.62 87.68 0.00 0.00
December 193.17 79.63 120.57 43.57 77.00 0.00 0.00
               
Annual Sum or Average 323.09 32.28 159.44 48.74 110.71 0.00 0.00
Minimum of Months 177.14 0.12 117.82 34.96 76.96 0.00 0.00
Maximum of Months 439.98 100.77 198.25 74.77 139.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 136.60 35.73 87.85 57.13 30.73 0.00 0.00
February 126.96 28.68 77.56 44.11 33.45 0.00 0.00
March 100.05 22.11 59.94 24.78 35.16 0.00 0.00
April 82.12 11.98 42.98 8.80 34.17 0.00 0.00
May 74.28 2.97 33.55 1.07 32.49 0.00 0.00
June 77.94 0.74 31.65 0.07 31.59 0.00 0.00
July 85.32 1.47 33.87 0.28 33.58 0.00 0.00
August 91.52 0.68 38.07 2.85 35.23 0.00 0.00
September 113.57 2.84 49.37 12.20 37.18 0.00 0.00
October 134.46 4.85 68.52 32.58 35.94 0.00 0.00
November 134.48 14.97 77.63 43.57 34.06 0.00 0.00
December 134.68 30.29 84.70 53.48 31.22 0.00 0.00
               
Annual Sum or Average 107.57 13.04 57.05 23.32 33.73 0.00 0.00
Minimum of Months 74.28 0.68 31.65 0.07 30.73 0.00 0.00
Maximum of Months 136.60 35.73 87.85 57.13 37.18 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 27.11 27.22 18.66 0.00 18.66 0.00 0.00
February 38.68 20.48 22.09 0.00 22.09 0.00 0.00
March 45.68 14.36 26.35 0.00 26.35 0.00 0.00
April 62.17 4.83 29.61 0.17 29.44 0.00 0.00
May 86.60 0.75 33.62 1.38 32.24 0.00 0.00
June 100.92 0.03 36.04 2.59 33.45 0.00 0.00
July 103.49 0.21 36.50 1.82 34.69 0.00 0.00
August 93.48 0.01 32.33 0.34 31.99 0.00 0.00
September 85.01 0.24 28.63 0.01 28.62 0.00 0.00
October 65.85 0.95 23.97 0.00 23.97 0.00 0.00
November 47.60 9.17 20.84 0.00 20.84 0.00 0.00
December 30.34 21.27 18.46 0.00 18.46 0.00 0.00
               
Annual Sum or Average 65.71 8.24 27.29 0.53 26.76 0.00 0.00
Minimum of Months 27.11 0.01 18.46 0.00 18.46 0.00 0.00
Maximum of Months 103.49 27.22 36.50 2.59 34.69 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 330.28 98.03 214.72 121.68 93.04 0.00 0.00
February 357.48 74.70 218.61 111.66 106.95 0.00 0.00
March 364.08 52.12 223.12 101.04 122.08 0.00 0.00
April 395.42 22.72 214.75 82.89 131.86 0.00 0.00
May 412.71 3.61 194.29 62.24 132.05 0.00 0.00
June 436.51 0.35 189.29 57.54 131.75 0.00 0.00
July 459.12 1.39 196.39 55.94 140.44 0.00 0.00
August 439.07 0.11 188.40 50.70 137.70 0.00 0.00
September 451.95 2.29 197.38 64.23 133.15 0.00 0.00
October 431.91 5.86 210.38 94.26 116.13 0.00 0.00
November 362.02 35.20 198.60 94.91 103.69 0.00 0.00
December 299.93 79.05 188.03 95.97 92.06 0.00 0.00
               
Annual Sum or Average 395.17 31.11 202.73 82.60 120.13 0.00 0.00
Minimum of Months 299.93 0.11 188.03 50.70 92.06 0.00 0.00
Maximum of Months 459.12 98.03 223.12 121.68 140.44 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 188.23 95.55 128.21 50.26 77.95 0.00 0.00
February 239.50 72.42 149.26 56.52 92.75 0.00 0.00
March 287.43 50.72 181.12 70.06 111.06 0.00 0.00
April 360.65 22.06 198.02 72.09 125.93 0.00 0.00
May 412.25 3.59 194.36 62.63 131.73 0.00 0.00
June 447.79 0.37 194.76 60.70 134.06 0.00 0.00
July 465.77 1.42 199.67 57.86 141.81 0.00 0.00
August 424.12 0.10 181.21 47.57 133.64 0.00 0.00
September 402.29 2.19 171.43 48.99 122.44 0.00 0.00
October 333.72 5.38 154.67 53.52 101.15 0.00 0.00
November 243.44 33.88 127.60 40.44 87.16 0.00 0.00
December 165.27 76.62 105.21 29.10 76.11 0.00 0.00
               
Annual Sum or Average 331.27 30.19 165.51 54.11 111.40 0.00 0.00
Minimum of Months 165.27 0.10 105.21 29.10 76.11 0.00 0.00
Maximum of Months 465.77 95.55 199.67 72.09 141.81 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 345.48 148.02 230.79 123.78 107.01 0.00 0.00
February 349.77 119.60 215.90 95.57 120.33 0.00 0.00
March 304.84 93.94 186.96 53.69 133.27 0.00 0.00
April 295.32 53.07 157.26 19.44 137.82 0.00 0.00
May 317.75 14.61 145.54 5.29 140.25 0.00 0.00
June 349.13 4.57 146.65 5.76 140.89 0.00 0.00
July 372.62 8.61 152.46 4.55 147.91 0.00 0.00
August 361.58 4.32 152.53 6.90 145.63 0.00 0.00
September 396.55 14.81 168.99 26.44 142.55 0.00 0.00
October 402.96 24.14 200.40 70.59 129.80 0.00 0.00
November 372.91 65.93 213.34 94.39 118.95 0.00 0.00
December 347.71 125.51 223.52 115.88 107.64 0.00 0.00
               
Annual Sum or Average 351.38 56.15 182.71 51.67 131.05 0.00 0.00
Minimum of Months 295.32 4.32 145.54 4.55 107.01 0.00 0.00
Maximum of Months 402.96 148.02 230.79 123.78 147.91 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 313.82 96.76 204.33 112.28 92.05 0.00 0.00
February 354.64 75.91 215.56 109.16 106.40 0.00 0.00
March 366.07 54.49 221.84 98.14 123.70 0.00 0.00
April 393.46 22.39 214.97 85.57 129.41 0.00 0.00
May 402.96 3.42 189.42 58.27 131.16 0.00 0.00
June 393.86 0.21 164.43 35.12 129.31 0.00 0.00
July 432.15 1.17 181.67 43.41 138.25 0.00 0.00
August 434.10 0.08 186.60 48.74 137.86 0.00 0.00
September 421.13 1.71 180.34 50.21 130.14 0.00 0.00
October 419.32 5.11 203.88 86.91 116.98 0.00 0.00
November 355.32 34.47 194.30 90.09 104.21 0.00 0.00
December 325.02 78.14 203.40 110.44 92.96 0.00 0.00
               
Annual Sum or Average 384.49 30.97 196.66 77.23 119.43 0.00 0.00
Minimum of Months 313.82 0.08 164.43 35.12 92.05 0.00 0.00
Maximum of Months 434.10 96.76 221.84 112.28 138.25 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 177.37 96.59 117.82 40.86 76.96 0.00 0.00
February 241.32 75.43 146.21 54.01 92.19 0.00 0.00
March 292.61 54.34 179.84 67.15 112.69 0.00 0.00
April 359.37 21.69 198.25 74.77 123.48 0.00 0.00
May 402.23 3.33 189.49 58.66 130.84 0.00 0.00
June 404.81 0.23 169.90 38.27 131.63 0.00 0.00
July 438.65 1.19 184.95 45.33 139.62 0.00 0.00
August 419.27 0.08 179.40 45.60 133.80 0.00 0.00
September 372.33 1.60 154.39 34.96 119.43 0.00 0.00
October 322.77 4.62 148.17 46.17 102.00 0.00 0.00
November 240.01 34.15 123.30 35.62 87.68 0.00 0.00
December 193.21 76.10 120.57 43.57 77.00 0.00 0.00
               
Annual Sum or Average 322.42 30.59 159.44 48.74 110.71 0.00 0.00
Minimum of Months 177.37 0.08 117.82 34.96 76.96 0.00 0.00
Maximum of Months 438.65 96.59 198.25 74.77 139.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 253.46 50.62 161.09 104.75 56.34 0.00 0.00
February 236.88 38.61 142.21 80.88 61.33 0.00 0.00
March 188.81 26.82 109.90 45.44 64.46 0.00 0.00
April 158.24 10.10 78.80 16.14 62.66 0.00 0.00
May 153.10 1.50 61.53 1.95 59.57 0.00 0.00
June 161.78 0.07 58.04 0.12 57.92 0.00 0.00
July 173.25 0.44 62.10 0.52 61.58 0.00 0.00
August 186.49 0.02 69.81 5.22 64.59 0.00 0.00
September 221.60 0.65 90.53 22.37 68.17 0.00 0.00
October 257.53 2.43 125.64 59.74 65.90 0.00 0.00
November 254.40 17.67 142.33 79.88 62.45 0.00 0.00
December 249.73 41.18 155.31 98.06 57.25 0.00 0.00
               
Annual Sum or Average 207.80 15.75 104.60 42.76 61.85 0.00 0.00
Minimum of Months 153.10 0.02 58.04 0.12 56.34 0.00 0.00
Maximum of Months 257.53 50.62 161.09 104.75 68.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 166.29 375.76 163.29 0.00 163.29 0.00 0.00
February 248.21 309.82 193.28 0.00 193.28 0.00 0.00
March 299.71 246.59 230.56 0.00 230.56 0.00 0.00
April 425.67 138.39 259.03 1.48 257.55 0.00 0.00
May 592.37 49.52 294.14 12.05 282.09 0.00 0.00
June 698.73 16.64 315.27 22.68 292.60 0.00 0.00
July 736.96 26.36 319.36 15.90 303.47 0.00 0.00
August 629.78 16.82 282.83 2.96 279.86 0.00 0.00
September 582.89 39.76 250.44 0.06 250.38 0.00 0.00
October 426.89 64.82 209.71 0.00 209.71 0.00 0.00
November 293.36 168.01 182.34 0.00 182.34 0.00 0.00
December 186.94 317.68 161.51 0.00 161.51 0.00 0.00
               
Annual Sum or Average 441.58 146.80 238.71 4.62 234.09 0.00 0.00
Minimum of Months 166.29 16.64 161.51 0.00 161.51 0.00 0.00
Maximum of Months 736.96 375.76 319.36 22.68 303.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 157.57 391.54 163.29 0.00 163.29 0.00 0.00
February 237.92 323.42 193.28 0.00 193.28 0.00 0.00
March 288.97 258.62 230.56 0.00 230.56 0.00 0.00
April 415.49 146.54 259.03 1.48 257.55 0.00 0.00
May 581.91 55.06 294.14 12.05 282.09 0.00 0.00
June 686.66 19.01 315.27 22.68 292.60 0.00 0.00
July 726.37 29.50 319.36 15.90 303.47 0.00 0.00
August 617.38 19.41 282.83 2.96 279.86 0.00 0.00
September 571.64 43.06 250.44 0.06 250.38 0.00 0.00
October 416.86 70.73 209.71 0.00 209.71 0.00 0.00
November 283.58 177.45 182.34 0.00 182.34 0.00 0.00
December 178.43 332.55 161.51 0.00 161.51 0.00 0.00
               
Annual Sum or Average 431.17 154.84 238.71 4.62 234.09 0.00 0.00
Minimum of Months 157.57 19.01 161.51 0.00 161.51 0.00 0.00
Maximum of Months 726.37 391.54 319.36 22.68 303.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 522.81 280.71 342.91 171.94 170.98 0.00 0.00
February 591.31 242.12 367.86 168.17 199.69 0.00 0.00
March 648.69 196.43 404.22 171.09 233.13 0.00 0.00
April 763.49 126.18 412.74 154.97 257.78 0.00 0.00
May 808.81 59.31 388.63 124.86 263.78 0.00 0.00
June 862.81 25.19 384.04 118.24 265.80 0.00 0.00
July 930.20 35.86 396.04 113.80 282.24 0.00 0.00
August 831.11 25.81 369.59 98.26 271.33 0.00 0.00
September 849.96 38.97 368.79 113.22 255.57 0.00 0.00
October 762.96 64.58 365.04 147.77 217.27 0.00 0.00
November 602.50 137.46 326.19 135.34 190.84 0.00 0.00
December 465.71 242.46 293.22 125.06 168.16 0.00 0.00
               
Annual Sum or Average 720.54 122.39 368.22 136.71 231.52 0.00 0.00
Minimum of Months 465.71 25.19 293.22 98.26 168.16 0.00 0.00
Maximum of Months 930.20 280.71 412.74 171.94 282.24 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 698.74 256.82 466.04 266.64 199.40 0.00 0.00
February 683.38 212.09 428.25 205.88 222.37 0.00 0.00
March 573.83 168.16 358.80 115.67 243.13 0.00 0.00
April 524.00 101.37 289.39 41.60 247.79 0.00 0.00
May 533.25 32.47 257.45 9.10 248.35 0.00 0.00
June 577.97 11.20 255.81 8.08 247.73 0.00 0.00
July 625.37 19.35 267.56 6.78 260.78 0.00 0.00
August 620.35 10.77 274.66 14.31 260.36 0.00 0.00
September 707.90 30.18 316.30 56.95 259.35 0.00 0.00
October 758.21 47.30 391.72 152.07 239.64 0.00 0.00
November 722.98 117.22 424.83 203.35 221.48 0.00 0.00
December 695.58 220.37 450.71 249.63 201.09 0.00 0.00
               
Annual Sum or Average 643.25 101.78 348.10 110.42 237.68 0.00 0.00
Minimum of Months 524.00 10.77 255.81 6.78 199.40 0.00 0.00
Maximum of Months 758.21 256.82 466.04 266.64 260.78 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.230891E+10 0.574116E+09 0.148795E+10 0.967519E+09 0.520433E+09 0.00 0.00
February 0.193375E+10 0.434100E+09 0.118642E+10 0.674762E+09 0.511657E+09 0.00 0.00
March 0.168435E+10 0.388197E+09 0.101513E+10 0.419697E+09 0.595431E+09 0.00 0.00
April 0.130289E+10 0.233724E+09 0.704385E+09 0.144292E+09 0.560093E+09 0.00 0.00
May 0.115554E+10 90221223.26 0.568300E+09 18039893.06 0.550260E+09 0.00 0.00
June 0.113334E+10 28652061.34 0.518766E+09 1079877.92 0.517686E+09 0.00 0.00
July 0.129308E+10 53790041.21 0.573595E+09 4816469.25 0.568779E+09 0.00 0.00
August 0.139744E+10 26413013.69 0.644834E+09 48222350.38 0.596611E+09 0.00 0.00
September 0.172694E+10 72958145.06 0.809229E+09 0.199919E+09 0.609311E+09 0.00 0.00
October 0.218081E+10 0.131174E+09 0.116052E+10 0.551817E+09 0.608706E+09 0.00 0.00
November 0.215493E+10 0.269037E+09 0.127230E+10 0.714056E+09 0.558244E+09 0.00 0.00
December 0.227357E+10 0.498442E+09 0.143456E+10 0.905795E+09 0.528761E+09 0.00 0.00
               
Annual Sum or Average 0.205455E+11 0.280082E+10 0.113760E+11 0.465001E+10 0.672597E+10 0.00 0.00
Minimum of Months 0.113334E+10 26413013.69 0.518766E+09 1079877.92 0.511657E+09 0.00 0.00
Maximum of Months 0.230891E+10 0.574116E+09 0.148795E+10 0.967519E+09 0.609311E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.640217E+10 0.181174E+10 0.418997E+10 0.272447E+10 0.146550E+10 0.00 0.00
February 0.535791E+10 0.136785E+10 0.334088E+10 0.190008E+10 0.144079E+10 0.00 0.00
March 0.466605E+10 0.122915E+10 0.285853E+10 0.118184E+10 0.167669E+10 0.00 0.00
April 0.362039E+10 0.734747E+09 0.198350E+10 0.406316E+09 0.157718E+10 0.00 0.00
May 0.323100E+10 0.290987E+09 0.160030E+10 50799149.42 0.154950E+10 0.00 0.00
June 0.319239E+10 96793987.11 0.146081E+10 3040865.03 0.145777E+10 0.00 0.00
July 0.364235E+10 0.159463E+09 0.161521E+10 13562859.83 0.160164E+10 0.00 0.00
August 0.391602E+10 93519271.87 0.181581E+10 0.135791E+09 0.168002E+10 0.00 0.00
September 0.484050E+10 0.224590E+09 0.227874E+10 0.562957E+09 0.171578E+10 0.00 0.00
October 0.609700E+10 0.403782E+09 0.326796E+10 0.155388E+10 0.171408E+10 0.00 0.00
November 0.599718E+10 0.846088E+09 0.358271E+10 0.201074E+10 0.157198E+10 0.00 0.00
December 0.631666E+10 0.158106E+10 0.403962E+10 0.255066E+10 0.148896E+10 0.00 0.00
               
Annual Sum or Average 0.572796E+11 0.883977E+10 0.320340E+11 0.130941E+11 0.189399E+11 0.00 0.00
Minimum of Months 0.319239E+10 93519271.87 0.146081E+10 3040865.03 0.144079E+10 0.00 0.00
Maximum of Months 0.640217E+10 0.181174E+10 0.418997E+10 0.272447E+10 0.171578E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.854309E+10 0.236061E+10 0.544302E+10 0.353924E+10 0.190377E+10 0.00 0.00
February 0.716890E+10 0.176934E+10 0.433999E+10 0.246832E+10 0.187167E+10 0.00 0.00
March 0.626391E+10 0.158674E+10 0.371340E+10 0.153528E+10 0.217812E+10 0.00 0.00
April 0.487977E+10 0.936620E+09 0.257668E+10 0.527828E+09 0.204885E+10 0.00 0.00
May 0.436369E+10 0.362566E+09 0.207888E+10 65990986.10 0.201288E+10 0.00 0.00
June 0.431855E+10 0.120612E+09 0.189768E+10 3950256.73 0.189373E+10 0.00 0.00
July 0.493597E+10 0.198196E+09 0.209825E+10 17618926.79 0.208063E+10 0.00 0.00
August 0.529936E+10 0.111624E+09 0.235884E+10 0.176400E+09 0.218244E+10 0.00 0.00
September 0.653628E+10 0.278988E+09 0.296021E+10 0.731314E+09 0.222890E+10 0.00 0.00
October 0.817393E+10 0.480343E+09 0.424526E+10 0.201858E+10 0.222668E+10 0.00 0.00
November 0.801928E+10 0.107129E+10 0.465415E+10 0.261206E+10 0.204209E+10 0.00 0.00
December 0.841521E+10 0.204526E+10 0.524769E+10 0.331345E+10 0.193424E+10 0.00 0.00
               
Annual Sum or Average 0.769179E+11 0.113222E+11 0.416140E+11 0.170100E+11 0.246040E+11 0.00 0.00
Minimum of Months 0.431855E+10 0.111624E+09 0.189768E+10 3950256.73 0.187167E+10 0.00 0.00
Maximum of Months 0.854309E+10 0.236061E+10 0.544302E+10 0.353924E+10 0.222890E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.845238E+09 0.267895E+09 0.547283E+09 0.300734E+09 0.246549E+09 0.00 0.00
February 0.863903E+09 0.189955E+09 0.521479E+09 0.264081E+09 0.257398E+09 0.00 0.00
March 0.988930E+09 0.152497E+09 0.594175E+09 0.262845E+09 0.331330E+09 0.00 0.00
April 0.102786E+10 62843958.11 0.557213E+09 0.221785E+09 0.335428E+09 0.00 0.00
May 0.108222E+10 10503038.70 0.507352E+09 0.156063E+09 0.351288E+09 0.00 0.00
June 0.102229E+10 839216.55 0.426207E+09 91025211.56 0.335181E+09 0.00 0.00
July 0.116070E+10 3901194.28 0.486578E+09 0.116277E+09 0.370301E+09 0.00 0.00
August 0.116451E+10 317111.18 0.499793E+09 0.130546E+09 0.369247E+09 0.00 0.00
September 0.109457E+10 6079418.83 0.467448E+09 0.130132E+09 0.337316E+09 0.00 0.00
October 0.112504E+10 16427612.03 0.546079E+09 0.232772E+09 0.313307E+09 0.00 0.00
November 0.923937E+09 95018370.71 0.503617E+09 0.233505E+09 0.270113E+09 0.00 0.00
December 0.875931E+09 0.216958E+09 0.544779E+09 0.295801E+09 0.248978E+09 0.00 0.00
               
Annual Sum or Average 0.121751E+11 0.102324E+10 0.620200E+10 0.243557E+10 0.376644E+10 0.00 0.00
Minimum of Months 0.845238E+09 317111.18 0.426207E+09 91025211.56 0.246549E+09 0.00 0.00
Maximum of Months 0.116451E+10 0.267895E+09 0.594175E+09 0.300734E+09 0.370301E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.474464E+09 0.269903E+09 0.315569E+09 0.109438E+09 0.206131E+09 0.00 0.00
February 0.585485E+09 0.189938E+09 0.353702E+09 0.130669E+09 0.223033E+09 0.00 0.00
March 0.788779E+09 0.152582E+09 0.481688E+09 0.179865E+09 0.301822E+09 0.00 0.00
April 0.938042E+09 61012496.79 0.513861E+09 0.193804E+09 0.320057E+09 0.00 0.00
May 0.108072E+10 10198936.37 0.507540E+09 0.157107E+09 0.350432E+09 0.00 0.00
June 0.105139E+10 884225.29 0.440383E+09 99208328.72 0.341174E+09 0.00 0.00
July 0.117843E+10 3950446.63 0.495369E+09 0.121407E+09 0.373962E+09 0.00 0.00
August 0.112451E+10 317411.59 0.480518E+09 0.122146E+09 0.358372E+09 0.00 0.00
September 0.966232E+09 5822507.12 0.400187E+09 90626159.72 0.309561E+09 0.00 0.00
October 0.862742E+09 15132996.06 0.396866E+09 0.123668E+09 0.273197E+09 0.00 0.00
November 0.620686E+09 94924737.48 0.319582E+09 92323391.94 0.227259E+09 0.00 0.00
December 0.517386E+09 0.213279E+09 0.322943E+09 0.116710E+09 0.206233E+09 0.00 0.00
               
Annual Sum or Average 0.101889E+11 0.101795E+10 0.502821E+10 0.153697E+10 0.349123E+10 0.00 0.00
Minimum of Months 0.474464E+09 317411.59 0.315569E+09 90626159.72 0.206131E+09 0.00 0.00
Maximum of Months 0.117843E+10 0.269903E+09 0.513861E+09 0.193804E+09 0.373962E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.365865E+09 95702438.21 0.235309E+09 0.153006E+09 82302997.65 0.00 0.00
February 0.307146E+09 69370674.81 0.187624E+09 0.106708E+09 80915277.26 0.00 0.00
March 0.267978E+09 59212983.44 0.160536E+09 66371880.15 94163689.54 0.00 0.00
April 0.212859E+09 31056013.24 0.111394E+09 22818620.98 88575365.15 0.00 0.00
May 0.198939E+09 7942251.36 89873280.16 2852869.99 87020410.17 0.00 0.00
June 0.202033E+09 1910163.57 82039774.92 170774.37 81869000.56 0.00 0.00
July 0.228522E+09 3941853.63 90710703.00 761687.47 89949015.53 0.00 0.00
August 0.245128E+09 1828535.59 0.101976E+09 7625992.90 94350425.71 0.00 0.00
September 0.294361E+09 7351939.88 0.127974E+09 31615575.84 96358645.11 0.00 0.00
October 0.360129E+09 12987908.77 0.183529E+09 87265587.65 96262912.52 0.00 0.00
November 0.348578E+09 38814906.48 0.201205E+09 0.112922E+09 88282536.13 0.00 0.00
December 0.360727E+09 81118141.37 0.226865E+09 0.143244E+09 83620064.08 0.00 0.00
               
Annual Sum or Average 0.339227E+10 0.411238E+09 0.179903E+10 0.735364E+09 0.106367E+10 0.00 0.00
Minimum of Months 0.198939E+09 1828535.59 82039774.92 170774.37 80915277.26 0.00 0.00
Maximum of Months 0.365865E+09 95702438.21 0.235309E+09 0.153006E+09 96358645.11 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 72623828.99 72894281.58 49991117.79 0.00 49991117.79 0.00 0.00
February 93584513.85 49552786.42 53446117.01 0.00 53446117.01 0.00 0.00
March 0.122354E+09 38460930.42 70587127.69 1245.66 70585882.03 0.00 0.00
April 0.161156E+09 12506453.85 76744494.28 438154.86 76306339.42 0.00 0.00
May 0.231954E+09 2020812.78 90053455.50 3689174.61 86364280.90 0.00 0.00
June 0.261572E+09 80722.59 93409270.91 6718192.47 86691078.44 0.00 0.00
July 0.277175E+09 553955.90 97774596.35 4866543.94 92908052.41 0.00 0.00
August 0.250385E+09 17972.23 86588371.69 907702.50 85680669.19 0.00 0.00
September 0.220343E+09 625669.03 74200848.51 17142.51 74183706.00 0.00 0.00
October 0.176382E+09 2544748.31 64202974.78 0.00 64202974.78 0.00 0.00
November 0.123382E+09 23772698.52 54024017.81 0.00 54024017.81 0.00 0.00
December 81255813.38 56971782.65 49447441.40 0.00 49447441.40 0.00 0.00
               
Annual Sum or Average 0.207217E+10 0.260003E+09 0.860470E+09 16638156.53 0.843832E+09 0.00 0.00
Minimum of Months 72623828.99 17972.23 49447441.40 0.00 49447441.40 0.00 0.00
Maximum of Months 0.277175E+09 72894281.58 97774596.35 6718192.47 92908052.41 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.884627E+09 0.262559E+09 0.575104E+09 0.325914E+09 0.249190E+09 0.00 0.00
February 0.864810E+09 0.180707E+09 0.528872E+09 0.270134E+09 0.258738E+09 0.00 0.00
March 0.975148E+09 0.139594E+09 0.597604E+09 0.270631E+09 0.326974E+09 0.00 0.00
April 0.102492E+10 58883325.21 0.556623E+09 0.214843E+09 0.341780E+09 0.00 0.00
May 0.110541E+10 9669021.19 0.520390E+09 0.166696E+09 0.353695E+09 0.00 0.00
June 0.113144E+10 918910.23 0.490649E+09 0.149155E+09 0.341494E+09 0.00 0.00
July 0.122971E+10 3724899.95 0.526007E+09 0.149841E+09 0.376166E+09 0.00 0.00
August 0.117602E+10 284474.20 0.504622E+09 0.135800E+09 0.368822E+09 0.00 0.00
September 0.117145E+10 5931735.88 0.511604E+09 0.166489E+09 0.345115E+09 0.00 0.00
October 0.115684E+10 15702172.42 0.563490E+09 0.252459E+09 0.311031E+09 0.00 0.00
November 0.938351E+09 91242313.68 0.514776E+09 0.246004E+09 0.268773E+09 0.00 0.00
December 0.803323E+09 0.211726E+09 0.503620E+09 0.257033E+09 0.246587E+09 0.00 0.00
               
Annual Sum or Average 0.124620E+11 0.980943E+09 0.639336E+10 0.260500E+10 0.378836E+10 0.00 0.00
Minimum of Months 0.803323E+09 284474.20 0.490649E+09 0.135800E+09 0.246587E+09 0.00 0.00
Maximum of Months 0.122971E+10 0.262559E+09 0.597604E+09 0.325914E+09 0.376166E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.504157E+09 0.255924E+09 0.343390E+09 0.134618E+09 0.208771E+09 0.00 0.00
February 0.579410E+09 0.175200E+09 0.361094E+09 0.136722E+09 0.224373E+09 0.00 0.00
March 0.769861E+09 0.135856E+09 0.485117E+09 0.187651E+09 0.297466E+09 0.00 0.00
April 0.934815E+09 57174179.67 0.513271E+09 0.186862E+09 0.326409E+09 0.00 0.00
May 0.110418E+10 9621136.49 0.520578E+09 0.167740E+09 0.352838E+09 0.00 0.00
June 0.116067E+10 965681.60 0.504825E+09 0.157338E+09 0.347487E+09 0.00 0.00
July 0.124753E+10 3795568.07 0.534798E+09 0.154971E+09 0.379827E+09 0.00 0.00
August 0.113597E+10 279085.98 0.485347E+09 0.127400E+09 0.357947E+09 0.00 0.00
September 0.104273E+10 5673456.76 0.444343E+09 0.126983E+09 0.317360E+09 0.00 0.00
October 0.893825E+09 14403337.71 0.414277E+09 0.143355E+09 0.270922E+09 0.00 0.00
November 0.631007E+09 87813151.42 0.330741E+09 0.104823E+09 0.225919E+09 0.00 0.00
December 0.442665E+09 0.205228E+09 0.281784E+09 77942147.70 0.203842E+09 0.00 0.00
               
Annual Sum or Average 0.104468E+11 0.951934E+09 0.521957E+10 0.170640E+10 0.351316E+10 0.00 0.00
Minimum of Months 0.442665E+09 279085.98 0.281784E+09 77942147.70 0.203842E+09 0.00 0.00
Maximum of Months 0.124753E+10 0.255924E+09 0.534798E+09 0.187651E+09 0.379827E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.925327E+09 0.396448E+09 0.618146E+09 0.331521E+09 0.286625E+09 0.00 0.00
February 0.846166E+09 0.289345E+09 0.522310E+09 0.231207E+09 0.291103E+09 0.00 0.00
March 0.816482E+09 0.251599E+09 0.500751E+09 0.143812E+09 0.356939E+09 0.00 0.00
April 0.765457E+09 0.137570E+09 0.407614E+09 50390796.35 0.357223E+09 0.00 0.00
May 0.851071E+09 39136392.86 0.389816E+09 14173365.17 0.375643E+09 0.00 0.00
June 0.904943E+09 11833182.06 0.380113E+09 14923878.21 0.365189E+09 0.00 0.00
July 0.998029E+09 23069637.46 0.408357E+09 12192930.96 0.396164E+09 0.00 0.00
August 0.968450E+09 11582834.69 0.408534E+09 18489793.87 0.390044E+09 0.00 0.00
September 0.102785E+10 38391727.10 0.438028E+09 68539297.28 0.369489E+09 0.00 0.00
October 0.107930E+10 64657112.42 0.536740E+09 0.189080E+09 0.347660E+09 0.00 0.00
November 0.966586E+09 0.170878E+09 0.552989E+09 0.244672E+09 0.308318E+09 0.00 0.00
December 0.931303E+09 0.336171E+09 0.598672E+09 0.310371E+09 0.288301E+09 0.00 0.00
               
Annual Sum or Average 0.110810E+11 0.177068E+10 0.576207E+10 0.162937E+10 0.413270E+10 0.00 0.00
Minimum of Months 0.765457E+09 11582834.69 0.380113E+09 12192930.96 0.286625E+09 0.00 0.00
Maximum of Months 0.107930E+10 0.396448E+09 0.618146E+09 0.331521E+09 0.396164E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.840545E+09 0.259149E+09 0.547283E+09 0.300734E+09 0.246549E+09 0.00 0.00
February 0.857955E+09 0.183647E+09 0.521479E+09 0.264081E+09 0.257398E+09 0.00 0.00
March 0.980492E+09 0.145947E+09 0.594175E+09 0.262845E+09 0.331330E+09 0.00 0.00
April 0.101985E+10 58043927.74 0.557213E+09 0.221785E+09 0.335428E+09 0.00 0.00
May 0.107929E+10 9156036.61 0.507352E+09 0.156063E+09 0.351288E+09 0.00 0.00
June 0.102089E+10 554938.70 0.426207E+09 91025211.56 0.335181E+09 0.00 0.00
July 0.115747E+10 3142699.65 0.486578E+09 0.116277E+09 0.370301E+09 0.00 0.00
August 0.116270E+10 207529.39 0.499793E+09 0.130546E+09 0.369247E+09 0.00 0.00
September 0.109158E+10 4424646.49 0.467448E+09 0.130132E+09 0.337316E+09 0.00 0.00
October 0.112311E+10 13682808.89 0.546079E+09 0.232772E+09 0.313307E+09 0.00 0.00
November 0.920988E+09 89337402.97 0.503617E+09 0.233505E+09 0.270113E+09 0.00 0.00
December 0.870544E+09 0.209282E+09 0.544779E+09 0.295801E+09 0.248978E+09 0.00 0.00
               
Annual Sum or Average 0.121254E+11 0.976576E+09 0.620200E+10 0.243557E+10 0.376644E+10 0.00 0.00
Minimum of Months 0.840545E+09 207529.39 0.426207E+09 91025211.56 0.246549E+09 0.00 0.00
Maximum of Months 0.116270E+10 0.259149E+09 0.594175E+09 0.300734E+09 0.370301E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.475062E+09 0.258717E+09 0.315569E+09 0.109438E+09 0.206131E+09 0.00 0.00
February 0.583813E+09 0.182476E+09 0.353702E+09 0.130669E+09 0.223033E+09 0.00 0.00
March 0.783728E+09 0.145544E+09 0.481688E+09 0.179865E+09 0.301822E+09 0.00 0.00
April 0.931497E+09 56228184.69 0.513861E+09 0.193804E+09 0.320057E+09 0.00 0.00
May 0.107733E+10 8910036.57 0.507540E+09 0.157107E+09 0.350432E+09 0.00 0.00
June 0.104927E+10 589203.70 0.440383E+09 99208328.72 0.341174E+09 0.00 0.00
July 0.117487E+10 3185303.60 0.495369E+09 0.121407E+09 0.373962E+09 0.00 0.00
August 0.112297E+10 202182.38 0.480518E+09 0.122146E+09 0.358372E+09 0.00 0.00
September 0.965083E+09 4150131.45 0.400187E+09 90626159.72 0.309561E+09 0.00 0.00
October 0.864507E+09 12378666.17 0.396866E+09 0.123668E+09 0.273197E+09 0.00 0.00
November 0.622115E+09 88524834.49 0.319582E+09 92323391.94 0.227259E+09 0.00 0.00
December 0.517493E+09 0.203817E+09 0.322943E+09 0.116710E+09 0.206233E+09 0.00 0.00
               
Annual Sum or Average 0.101677E+11 0.964723E+09 0.502821E+10 0.153697E+10 0.349123E+10 0.00 0.00
Minimum of Months 0.475062E+09 202182.38 0.315569E+09 90626159.72 0.206131E+09 0.00 0.00
Maximum of Months 0.117487E+10 0.258717E+09 0.513861E+09 0.193804E+09 0.373962E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.678872E+09 0.135585E+09 0.431464E+09 0.280553E+09 0.150912E+09 0.00 0.00
February 0.573063E+09 93398643.00 0.344028E+09 0.195661E+09 0.148367E+09 0.00 0.00
March 0.505720E+09 71829294.80 0.294360E+09 0.121700E+09 0.172659E+09 0.00 0.00
April 0.410148E+09 26177259.58 0.204253E+09 41840441.24 0.162413E+09 0.00 0.00
May 0.410056E+09 4007677.76 0.164793E+09 5231049.65 0.159561E+09 0.00 0.00
June 0.419337E+09 177792.69 0.150429E+09 313133.51 0.150116E+09 0.00 0.00
July 0.464043E+09 1176259.01 0.166328E+09 1396637.42 0.164931E+09 0.00 0.00
August 0.499495E+09 43224.04 0.186985E+09 13983093.38 0.173002E+09 0.00 0.00
September 0.574378E+09 1675444.67 0.234655E+09 57970621.67 0.176684E+09 0.00 0.00
October 0.689779E+09 6507944.51 0.336520E+09 0.160011E+09 0.176509E+09 0.00 0.00
November 0.659399E+09 45791258.90 0.368931E+09 0.207056E+09 0.161876E+09 0.00 0.00
December 0.668877E+09 0.110294E+09 0.415981E+09 0.262654E+09 0.153327E+09 0.00 0.00
               
Annual Sum or Average 0.655317E+10 0.496665E+09 0.329873E+10 0.134837E+10 0.195036E+10 0.00 0.00
Minimum of Months 0.410056E+09 43224.04 0.150429E+09 313133.51 0.148367E+09 0.00 0.00
Maximum of Months 0.689779E+09 0.135585E+09 0.431464E+09 0.280553E+09 0.176684E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.445386E+09 0.100644E+10 0.437348E+09 0.00 0.437348E+09 0.00 0.00
February 0.600462E+09 0.749526E+09 0.467574E+09 0.00 0.467574E+09 0.00 0.00
March 0.802731E+09 0.660464E+09 0.617532E+09 10897.63 0.617521E+09 0.00 0.00
April 0.110334E+10 0.358710E+09 0.671400E+09 3833201.69 0.667567E+09 0.00 0.00
May 0.158659E+10 0.132631E+09 0.787833E+09 32274777.04 0.755559E+09 0.00 0.00
June 0.181112E+10 43139888.22 0.817192E+09 58774166.93 0.758418E+09 0.00 0.00
July 0.197388E+10 70597042.81 0.855382E+09 42575003.16 0.812807E+09 0.00 0.00
August 0.168680E+10 45049338.50 0.757519E+09 7941043.40 0.749578E+09 0.00 0.00
September 0.151084E+10 0.103061E+09 0.649147E+09 149971.41 0.648997E+09 0.00 0.00
October 0.114340E+10 0.173620E+09 0.561680E+09 0.00 0.561680E+09 0.00 0.00
November 0.760383E+09 0.435483E+09 0.472630E+09 0.00 0.472630E+09 0.00 0.00
December 0.500694E+09 0.850883E+09 0.432591E+09 0.00 0.432591E+09 0.00 0.00
               
Annual Sum or Average 0.139256E+11 0.462961E+10 0.752783E+10 0.145559E+09 0.738227E+10 0.00 0.00
Minimum of Months 0.445386E+09 43139888.22 0.432591E+09 0.00 0.432591E+09 0.00 0.00
Maximum of Months 0.197388E+10 0.100644E+10 0.855382E+09 58774166.93 0.812807E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.422048E+09 0.104870E+10 0.437348E+09 0.00 0.437348E+09 0.00 0.00
February 0.575564E+09 0.782412E+09 0.467574E+09 0.00 0.467574E+09 0.00 0.00
March 0.773983E+09 0.692678E+09 0.617532E+09 10897.63 0.617521E+09 0.00 0.00
April 0.107695E+10 0.379841E+09 0.671400E+09 3833201.69 0.667567E+09 0.00 0.00
May 0.155859E+10 0.147460E+09 0.787833E+09 32274777.04 0.755559E+09 0.00 0.00
June 0.177983E+10 49285753.33 0.817192E+09 58774166.93 0.758418E+09 0.00 0.00
July 0.194550E+10 79000250.39 0.855382E+09 42575003.16 0.812807E+09 0.00 0.00
August 0.165360E+10 51997997.79 0.757519E+09 7941043.40 0.749578E+09 0.00 0.00
September 0.148168E+10 0.111615E+09 0.649147E+09 149971.41 0.648997E+09 0.00 0.00
October 0.111653E+10 0.189435E+09 0.561680E+09 0.00 0.561680E+09 0.00 0.00
November 0.735052E+09 0.459942E+09 0.472630E+09 0.00 0.472630E+09 0.00 0.00
December 0.477907E+09 0.890699E+09 0.432591E+09 0.00 0.432591E+09 0.00 0.00
               
Annual Sum or Average 0.135972E+11 0.488306E+10 0.752783E+10 0.145559E+09 0.738227E+10 0.00 0.00
Minimum of Months 0.422048E+09 49285753.33 0.432591E+09 0.00 0.432591E+09 0.00 0.00
Maximum of Months 0.194550E+10 0.104870E+10 0.855382E+09 58774166.93 0.812807E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.140030E+10 0.751848E+09 0.918453E+09 0.460513E+09 0.457941E+09 0.00 0.00
February 0.143049E+10 0.585741E+09 0.889924E+09 0.406836E+09 0.483088E+09 0.00 0.00
March 0.173746E+10 0.526105E+09 0.108266E+10 0.458255E+09 0.624410E+09 0.00 0.00
April 0.197897E+10 0.327063E+09 0.106984E+10 0.401679E+09 0.668156E+09 0.00 0.00
May 0.216632E+10 0.158867E+09 0.104091E+10 0.334413E+09 0.706498E+09 0.00 0.00
June 0.223641E+10 65288642.96 0.995419E+09 0.306472E+09 0.688947E+09 0.00 0.00
July 0.249145E+10 96047408.31 0.106075E+10 0.304791E+09 0.755955E+09 0.00 0.00
August 0.222605E+10 69124783.87 0.989915E+09 0.263182E+09 0.726733E+09 0.00 0.00
September 0.220310E+10 0.101008E+09 0.955897E+09 0.293453E+09 0.662444E+09 0.00 0.00
October 0.204350E+10 0.172981E+09 0.977720E+09 0.395794E+09 0.581926E+09 0.00 0.00
November 0.156167E+10 0.356285E+09 0.845480E+09 0.350811E+09 0.494669E+09 0.00 0.00
December 0.124736E+10 0.649418E+09 0.785373E+09 0.334964E+09 0.450409E+09 0.00 0.00
               
Annual Sum or Average 0.227231E+11 0.385978E+10 0.116123E+11 0.431116E+10 0.730118E+10 0.00 0.00
Minimum of Months 0.124736E+10 65288642.96 0.785373E+09 0.263182E+09 0.450409E+09 0.00 0.00
Maximum of Months 0.249145E+10 0.751848E+09 0.108266E+10 0.460513E+09 0.755955E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.187150E+10 0.687878E+09 0.124824E+10 0.714162E+09 0.534077E+09 0.00 0.00
February 0.165324E+10 0.513085E+09 0.103603E+10 0.498067E+09 0.537961E+09 0.00 0.00
March 0.153695E+10 0.450402E+09 0.960999E+09 0.309798E+09 0.651201E+09 0.00 0.00
April 0.135821E+10 0.262761E+09 0.750094E+09 0.107821E+09 0.642273E+09 0.00 0.00
May 0.142826E+10 86960216.81 0.689559E+09 24379771.54 0.665179E+09 0.00 0.00
June 0.149811E+10 29019877.90 0.663060E+09 20944997.28 0.642115E+09 0.00 0.00
July 0.167498E+10 51832586.22 0.716623E+09 18150009.08 0.698473E+09 0.00 0.00
August 0.166154E+10 28838070.76 0.735659E+09 38316912.53 0.697342E+09 0.00 0.00
September 0.183487E+10 78222680.14 0.819855E+09 0.147619E+09 0.672236E+09 0.00 0.00
October 0.203078E+10 0.126701E+09 0.104917E+10 0.407317E+09 0.641857E+09 0.00 0.00
November 0.187397E+10 0.303825E+09 0.110115E+10 0.527071E+09 0.574082E+09 0.00 0.00
December 0.186305E+10 0.590233E+09 0.120719E+10 0.668601E+09 0.538594E+09 0.00 0.00
               
Annual Sum or Average 0.202855E+11 0.320976E+10 0.109776E+11 0.348225E+10 0.749539E+10 0.00 0.00
Minimum of Months 0.135821E+10 28838070.76 0.663060E+09 18150009.08 0.534077E+09 0.00 0.00
Maximum of Months 0.203078E+10 0.687878E+09 0.124824E+10 0.714162E+09 0.698473E+09 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 19.42 15.96 13.59 3.30 9.49 57.21 169.93 0.03
February 20.87 16.70 13.89 5.53 11.19 68.99 182.59 0.00
March 21.57 17.63 15.09 5.59 12.13 85.97 199.13 0.00
April 24.11 19.68 17.40 4.69 15.31 97.05 212.67 0.01
May 26.41 22.40 20.67 5.05 18.50 110.67 177.92 0.00
June 27.68 24.06 22.67 3.87 20.33 120.35 147.07 0.00
July 28.13 24.25 22.77 2.86 20.30 124.71 163.26 0.00
August 27.97 24.38 23.03 3.45 20.36 120.27 145.14 0.08
September 27.49 23.91 22.56 3.39 20.13 107.67 134.94 0.00
October 26.35 22.68 21.10 3.72 17.49 81.44 160.40 0.04
November 23.59 20.24 18.46 4.39 14.74 70.67 140.11 0.00
December 20.30 17.47 15.75 3.70 12.21 59.50 147.31 0.00
                 
Annual Sum or Average 24.51 20.80 18.94 4.12 16.04 92.16 164.97 0.01
Minimum of Months 19.42 15.96 13.59 2.86 9.49 57.21 134.94 0.00
Maximum of Months 28.13 24.38 23.03 5.59 20.36 124.71 212.67 0.08



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 28.90 02-JAN-14:20 24.35 22.57 2.37 19.46 142.33 666.50
February 29.40 11-FEB-13:00 24.15 22.20 4.60 20.75 178.50 682.00
March 29.40 13-MAR-15:00 22.41 19.40 6.20 21.27 178.00 499.00
April 32.20 17-APR-14:00 19.76 12.80 5.20 21.27 367.00 219.50
May 34.40 22-MAY-12:00 23.24 18.30 5.70 25.99 382.50 457.50
June 32.20 11-JUN-12:00 23.83 20.60 3.60 23.15 181.50 762.50
July 35.60 29-JUL-15:00 24.39 20.00 3.60 25.66 281.50 374.50
August 33.90 23-AUG-12:00 25.44 22.20 5.70 24.50 261.50 640.00
September 32.20 08-SEP-14:00 23.42 20.00 2.10 21.61 221.50 576.00
October 32.20 09-OCT-10:00 23.83 20.60 3.10 25.16 286.50 457.50
November 30.00 17-NOV-14:00 22.20 18.90 4.10 19.35 178.50 412.50
December 28.90 10-DEC-14:20 22.91 20.40 7.87 19.82 162.67 585.17
                 
Annual Sum or Average                
Minimum of Months 28.90   19.76 12.80 2.10 19.35 142.33 219.50
Maximum of Months 35.60   25.44 22.57 7.87 25.99 382.50 762.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 9.40 25-JAN-04:00 4.59 -1.7 3.10 -7.3 0.00 0.00
February 5.00 04-FEB-06:00 1.99 -2.8 5.70 -11.9 0.00 0.00
March 6.70 16-MAR-04:00 4.49 1.70 4.60 -9.2 0.00 0.00
April 14.40 02-APR-05:49 13.38 12.70 1.60 0.69 0.00 0.00
May 20.60 01-MAY-04:00 19.45 18.90 1.00 7.95 0.00 0.00
June 22.80 05-JUN-14:00 20.57 19.40 2.10 18.46 245.00 55.00
July 22.80 02-JUL-15:00 21.59 21.10 4.60 20.92 155.00 8.50
August 22.20 12-AUG-06:00 21.85 21.70 2.60 20.40 65.50 0.00
September 22.20 05-SEP-05:00 21.37 21.10 2.60 13.54 0.00 0.00
October 21.10 28-OCT-02:00 20.29 20.00 2.60 8.54 0.00 0.00
November 10.00 27-NOV-02:00 8.82 7.80 3.10 -4.6 0.00 0.00
December 7.80 15-DEC-05:40 5.61 3.13 6.37 -7.8 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 5.00   1.99 -2.8 1.00 -11.9 0.00 0.00
Maximum of Months 22.80   21.85 21.70 6.37 20.92 245.00 55.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 24.83 02-JAN-13:00 28.90 23.30 1.50 19.87 151.00 613.50
February 24.15 11-FEB-13:00 29.40 22.20 4.60 20.75 178.50 682.00
March 23.83 14-MAR-09:00 26.70 22.80 11.30 19.52 243.50 478.00
April 24.58 01-APR-15:00 28.30 23.30 3.60 16.30 93.50 759.50
May 26.05 28-MAY-14:00 28.90 25.00 5.20 25.66 289.00 98.50
June 26.06 28-JUN-11:00 28.90 25.00 1.50 22.98 404.50 373.50
July 26.39 12-JUL-10:00 30.60 25.00 4.60 23.82 287.50 574.00
August 26.46 21-AUG-15:00 32.20 24.40 3.60 24.50 205.50 366.00
September 26.31 22-SEP-16:00 30.00 25.00 6.20 28.91 54.00 21.00
October 26.52 01-OCT-11:00 29.40 25.60 6.20 28.43 283.50 0.00
November 25.31 04-NOV-13:00 27.80 24.40 2.10 26.48 199.00 3.00
December 24.31 24-DEC-14:00 27.20 23.30 2.10 23.66 201.50 114.50
                 
Annual Sum or Average                
Minimum of Months 23.83   26.70 22.20 1.50 16.30 54.00 0.00
Maximum of Months 26.52   32.20 25.60 11.30 28.91 404.50 759.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 23.30 02-JAN-13:00 28.90 24.83 1.50 19.87 151.00 613.50
February 22.80 11-FEB-16:19 27.60 24.09 5.70 18.94 101.33 565.33
March 22.80 14-MAR-09:20 25.57 23.60 9.63 22.18 176.17 527.17
April 23.30 01-APR-14:00 27.80 24.57 5.70 15.76 108.00 831.00
May 25.00 28-MAY-12:00 27.80 25.74 6.70 22.98 249.50 244.50
June 25.00 06-JUN-18:00 27.20 25.59 3.60 23.99 17.50 0.00
July 25.00 12-JUL-03:00 27.20 25.59 1.50 19.70 0.00 0.00
August 25.60 21-AUG-11:00 28.90 26.35 2.60 23.15 567.00 173.50
September 25.00 22-SEP-00:00 27.80 25.31 3.60 20.92 0.00 0.00
October 25.60 01-OCT-11:00 29.40 26.52 6.20 28.43 283.50 0.00
November 24.40 05-NOV-01:19 26.10 24.93 2.03 16.37 0.00 0.00
December 23.90 24-DEC-08:00 23.90 23.90 2.60 17.75 168.50 167.00
                 
Annual Sum or Average                
Minimum of Months 22.80   23.90 23.60 1.50 15.76 0.00 0.00
Maximum of Months 25.60   29.40 26.52 9.63 28.43 567.00 831.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 24.73 28.77 0.00
February 18.00 13.00 16.00 25.06 35.04 0.00
March 18.00 13.00 16.00 26.11 42.49 0.00
April 18.00 13.00 16.00 27.63 49.05 0.00
May 18.00 13.00 16.00 29.20 48.15 0.00
June 18.00 13.00 16.00 30.41 45.99 0.00
July 18.00 13.00 16.00 30.92 49.88 0.00
August 18.00 13.00 16.00 30.58 45.60 0.00
September 18.00 13.00 16.00 29.50 40.49 0.00
October 18.00 13.00 16.00 27.97 35.89 0.00
November 18.00 13.00 16.00 26.40 29.31 0.00
December 18.00 13.00 16.00 25.21 26.63 0.00
             
Annual Sum or Average 18.00 13.00 16.00 27.83 39.80 0.00
Minimum of Months 18.00 13.00 16.00 24.73 26.63 0.00
Maximum of Months 18.00 13.00 16.00 30.92 49.88 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770456E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -161771515.9 81.21 0.00 0.00
February 0.696205E+10 -0.681597E+10 0.00 0.00 672.00 0.00 -146082330.2 81.21 0.00 0.00
March 0.770312E+10 -0.754145E+10 0.00 0.00 744.00 0.00 -161672391.7 81.21 0.00 0.00
April 0.746494E+10 -0.730858E+10 0.00 0.00 720.00 0.00 -156360599.1 81.21 0.00 0.00
May 0.770430E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -161511896.0 81.21 0.00 0.00
June 0.745679E+10 -0.730053E+10 0.00 0.00 720.00 0.00 -156260603.8 81.21 0.00 0.00
July 0.771231E+10 -0.755085E+10 0.00 0.00 744.00 0.00 -161465847.8 81.21 0.00 0.00
August 0.770428E+10 -0.754280E+10 0.00 0.00 744.00 0.00 -161480006.9 81.21 0.00 0.00
September 0.746620E+10 -0.730993E+10 0.00 0.00 720.00 0.00 -156268665.4 81.21 0.00 0.00
October 0.770294E+10 -0.754143E+10 0.00 0.00 744.00 0.00 -161513247.5 81.21 0.00 0.00
November 0.744883E+10 -0.729242E+10 0.00 0.00 720.00 0.00 -156407346.2 81.21 0.00 0.00
December 0.771259E+10 -0.755085E+10 0.00 0.00 744.00 0.00 -161738864.8 81.21 0.00 0.00
                     
Annual Sum or Average 0.907429E+11 -0.888404E+11 0.00 0.00 8760.00 0.00 -0.190253E+10 81.21 0.00 0.00
Minimum of Months 0.696205E+10 -0.755085E+10 0.00 0.00 672.00 0.00 -161771515.9 81.21 0.00 0.00
Maximum of Months 0.771259E+10 -0.681597E+10 0.00 0.00 744.00 0.00 -146082330.2 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.973973E+11 -0.956671E+11 0.00 0.00 744.00 0.00 -0.173014E+10 81.25 0.00 0.00
February 0.874644E+11 -0.858973E+11 0.00 0.00 672.00 0.00 -0.156701E+10 81.25 0.00 0.00
March 0.950770E+11 -0.933323E+11 0.00 0.00 744.00 0.00 -0.174473E+10 81.24 0.00 0.00
April 0.895181E+11 -0.878245E+11 0.00 0.00 720.00 0.00 -0.169363E+10 81.24 0.00 0.00
May 0.898266E+11 -0.880808E+11 0.00 0.00 744.00 0.00 -0.174575E+10 81.25 0.00 0.00
June 0.849480E+11 -0.832611E+11 0.00 0.00 720.00 0.00 -0.168693E+10 81.24 0.00 0.00
July 0.869152E+11 -0.851792E+11 0.00 0.00 744.00 0.00 -0.173604E+10 81.23 0.00 0.00
August 0.874772E+11 -0.857461E+11 0.00 0.00 744.00 0.00 -0.173106E+10 81.24 0.00 0.00
September 0.864223E+11 -0.847485E+11 0.00 0.00 720.00 0.00 -0.167374E+10 81.24 0.00 0.00
October 0.918994E+11 -0.901705E+11 0.00 0.00 744.00 0.00 -0.172888E+10 81.24 0.00 0.00
November 0.915117E+11 -0.898390E+11 0.00 0.00 720.00 0.00 -0.167264E+10 81.24 0.00 0.00
December 0.965739E+11 -0.948452E+11 0.00 0.00 744.00 0.00 -0.172870E+10 81.24 0.00 0.00
                     
Annual Sum or Average 0.108503E+13 -0.106459E+13 0.00 0.00 8760.00 0.00 -0.204393E+11 81.24 0.00 0.00
Minimum of Months 0.849480E+11 -0.956671E+11 0.00 0.00 672.00 0.00 -0.174575E+10 81.23 0.00 0.00
Maximum of Months 0.973973E+11 -0.832611E+11 0.00 0.00 744.00 0.00 -0.156701E+10 81.25 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.515032E+11 -0.500354E+11 0.00 0.00 744.00 0.00 -0.146777E+10 58.98 0.00 0.00
February 0.460918E+11 -0.447600E+11 0.00 0.00 672.00 0.00 -0.133181E+10 58.98 0.00 0.00
March 0.495522E+11 -0.480641E+11 0.00 0.00 744.00 0.00 -0.148818E+10 58.98 0.00 0.00
April 0.457789E+11 -0.443317E+11 0.00 0.00 720.00 0.00 -0.144730E+10 58.98 0.00 0.00
May 0.449990E+11 -0.435096E+11 0.00 0.00 744.00 0.00 -0.148940E+10 58.98 0.00 0.00
June 0.418507E+11 -0.404127E+11 0.00 0.00 720.00 0.00 -0.143797E+10 58.97 0.00 0.00
July 0.424551E+11 -0.409784E+11 0.00 0.00 744.00 0.00 -0.147670E+10 58.97 0.00 0.00
August 0.429815E+11 -0.415122E+11 0.00 0.00 744.00 0.00 -0.146930E+10 58.97 0.00 0.00
September 0.430984E+11 -0.416785E+11 0.00 0.00 720.00 0.00 -0.141987E+10 58.98 0.00 0.00
October 0.467549E+11 -0.452884E+11 0.00 0.00 744.00 0.00 -0.146650E+10 58.98 0.00 0.00
November 0.474707E+11 -0.460521E+11 0.00 0.00 720.00 0.00 -0.141859E+10 58.98 0.00 0.00
December 0.507885E+11 -0.493223E+11 0.00 0.00 744.00 0.00 -0.146614E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.553325E+12 -0.535945E+12 0.00 0.00 8760.00 0.00 -0.173795E+11 58.98 0.00 0.00
Minimum of Months 0.418507E+11 -0.500354E+11 0.00 0.00 672.00 0.00 -0.148940E+10 58.97 0.00 0.00
Maximum of Months 0.515032E+11 -0.404127E+11 0.00 0.00 744.00 0.00 -0.133181E+10 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.93 0.93 01-JAN-07:40 5394.00 35.44 267.50 294.00 652.58 25.33 209.17 267.33
February 304.33 0.93 0.93 01-FEB-07:49 1634.55 24.75 114.50 281.83 473.66 21.30 151.33 238.83
March 362.67 0.93 0.93 01-MAR-07:19 1003.72 19.33 0.00 329.00 393.02 21.09 173.83 262.17
April 357.50 0.93 0.93 01-APR-06:00 814.46 19.17 0.00 330.17 329.73 20.88 156.17 247.00
May 389.00 0.93 0.93 01-MAY-06:40 708.17 18.42 0.00 347.50 283.86 20.14 119.83 224.50
June 388.17 0.94 0.93 01-JUN-06:49 666.53 17.72 0.00 323.33 264.09 19.48 87.33 206.33
July 403.83 0.93 0.93 01-JUL-06:40 749.72 18.51 0.00 355.33 300.51 20.25 159.67 257.17
August 348.33 0.93 0.93 01-AUG-06:49 890.06 18.88 0.00 344.33 350.59 20.59 180.17 267.67
September 349.67 0.93 0.93 01-SEP-06:00 1090.33 19.03 0.17 316.17 416.64 20.76 191.17 254.33
October 323.50 0.93 0.93 02-OCT-07:10 1401.34 21.23 40.33 316.83 503.84 21.64 215.83 270.67
November 314.83 0.93 0.93 01-NOV-06:00 3243.30 30.94 238.00 293.33 571.41 23.83 222.17 264.33
December 282.67 0.93 0.93 01-DEC-08:39 5541.75 36.21 278.67 282.33 674.55 24.92 201.00 255.00
                         
Annual Sum or Average 4111.50 0.93     1768.18 22.66 939.17 3814.17 420.17 21.51 2067.67 3015.33
Minimum of Months 282.67 0.93 0.93   666.53 17.72 0.00 281.83 264.09 19.48 87.33 206.33
Maximum of Months 403.83 0.94 0.93   5541.75 36.21 278.67 355.33 674.55 25.33 222.17 270.67



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.63 0.61 01-JAN-07:40 5708.63 35.48 267.67 299.17 965.21 25.23 202.00 288.00
February 304.33 0.62 0.61 01-FEB-07:49 1886.44 24.90 116.50 289.33 724.81 21.58 161.33 266.50
March 362.67 0.62 0.61 01-MAR-07:10 1196.89 19.95 15.67 342.83 585.00 21.51 208.33 307.67
April 357.50 0.63 0.61 01-APR-06:00 960.77 19.95 6.33 341.33 475.56 21.44 221.67 310.17
May 389.00 0.63 0.61 01-MAY-06:19 822.84 19.34 0.67 366.00 398.09 20.83 186.83 319.50
June 388.17 0.64 0.61 01-JUN-06:40 772.41 18.71 0.00 343.67 369.56 20.22 159.00 293.50
July 403.83 0.63 0.61 01-JUL-06:19 867.07 19.44 0.33 373.17 417.41 20.95 226.50 325.50
August 348.33 0.63 0.61 01-AUG-06:30 1027.11 19.73 6.83 356.17 487.13 21.22 231.17 320.83
September 349.67 0.63 0.61 01-SEP-06:49 1260.08 19.80 29.33 328.33 585.71 21.32 229.83 296.67
October 323.50 0.63 0.61 02-OCT-06:00 1636.57 21.67 53.50 324.17 738.09 21.99 233.83 303.67
November 314.83 0.62 0.61 01-NOV-06:00 3504.84 31.01 239.50 302.33 831.46 24.00 232.50 282.33
December 282.67 0.62 0.61 01-DEC-08:39 5858.46 36.27 279.00 290.00 988.65 24.92 204.17 271.50
                         
Annual Sum or Average 4111.50 0.63     1957.28 23.25 1015.33 3956.50 608.33 21.95 2497.17 3585.83
Minimum of Months 282.67 0.62 0.61   772.41 18.71 0.00 289.33 369.56 20.22 159.00 266.50
Maximum of Months 403.83 0.64 0.61   5858.46 36.27 279.00 373.17 988.65 25.23 233.83 325.50



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.83 0.80 01-JAN-08:00 325.89 14.28 0.00 249.83 162.58 17.73 0.00 79.00
February 304.33 0.82 0.80 01-FEB-07:00 380.09 15.23 0.00 259.50 181.91 18.54 0.00 116.50
March 362.67 0.81 0.80 01-MAR-09:09 460.30 16.20 0.00 322.17 214.72 19.42 0.00 203.67
April 357.50 0.81 0.80 01-APR-06:00 559.45 17.08 0.00 340.67 257.20 20.24 18.17 268.67
May 389.00 0.81 0.80 01-MAY-06:19 686.77 17.70 12.17 373.50 295.67 20.83 83.17 320.83
June 388.17 0.81 0.80 01-JUN-05:00 750.52 19.46 58.83 364.83 317.17 21.51 108.83 307.33
July 403.83 0.81 0.80 01-JUL-06:10 782.07 17.49 1.33 381.50 333.04 21.38 130.67 334.83
August 348.33 0.81 0.80 01-AUG-06:30 694.28 17.23 0.00 357.67 305.46 20.40 55.67 311.33
September 349.67 0.81 0.80 01-SEP-06:49 577.13 16.53 0.00 322.67 256.22 19.68 1.83 250.33
October 323.50 0.82 0.80 02-OCT-07:10 441.20 15.86 0.00 304.17 211.74 19.12 0.00 191.83
November 314.83 0.82 0.80 01-NOV-07:19 393.70 15.20 0.00 264.17 184.36 18.51 0.00 127.50
December 282.67 0.82 0.80 01-DEC-08:39 367.38 14.96 0.00 255.17 177.82 18.36 0.00 92.00
                         
Annual Sum or Average 4111.50 0.81     550.80 16.57 72.33 3795.83 247.42 19.77 398.33 2603.83
Minimum of Months 282.67 0.81 0.80   325.89 14.28 0.00 249.83 162.58 17.73 0.00 79.00
Maximum of Months 403.83 0.83 0.80   782.07 19.46 58.83 381.50 333.04 21.51 130.67 334.83



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 287.00 0.83 0.80 01-JAN-08:00 325.89 14.28 0.00 249.83 162.58 17.73 0.00 79.00
February 304.33 0.82 0.80 01-FEB-07:00 380.09 15.23 0.00 259.50 181.91 18.54 0.00 116.50
March 362.67 0.81 0.80 01-MAR-09:09 460.30 16.20 0.00 322.17 214.72 19.42 0.00 203.67
April 357.50 0.81 0.80 01-APR-06:00 559.45 17.08 0.00 340.67 257.20 20.24 18.17 268.67
May 389.00 0.81 0.80 01-MAY-06:19 686.77 17.70 12.17 373.50 295.67 20.83 83.17 320.83
June 388.17 0.81 0.80 01-JUN-05:00 750.52 19.46 58.83 364.83 317.17 21.51 108.83 307.33
July 403.83 0.81 0.80 01-JUL-06:10 782.07 17.49 1.33 381.50 333.04 21.38 130.67 334.83
August 348.33 0.81 0.80 01-AUG-06:30 694.28 17.23 0.00 357.67 305.46 20.40 55.67 311.33
September 349.67 0.81 0.80 01-SEP-06:49 577.13 16.53 0.00 322.67 256.22 19.68 1.83 250.33
October 323.50 0.82 0.80 02-OCT-07:10 441.20 15.86 0.00 304.17 211.74 19.12 0.00 191.83
November 314.83 0.82 0.80 01-NOV-07:19 393.70 15.20 0.00 264.17 184.36 18.51 0.00 127.50
December 282.67 0.82 0.80 01-DEC-08:39 367.38 14.96 0.00 255.17 177.82 18.36 0.00 92.00
                         
Annual Sum or Average 4111.50 0.81     550.80 16.57 72.33 3795.83 247.42 19.77 398.33 2603.83
Minimum of Months 282.67 0.81 0.80   325.89 14.28 0.00 249.83 162.58 17.73 0.00 79.00
Maximum of Months 403.83 0.83 0.80   782.07 19.46 58.83 381.50 333.04 21.51 130.67 334.83



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 61853170.00 22875.41 24-JAN-23:10 0.00 0.00 0.00 0.00 0.00
February 61168964.81 21495.64 03-FEB-23:10 0.00 0.00 0.00 0.00 0.00
March 27768944.00 3842.92 15-MAR-23:00 0.00 0.00 0.00 0.00 0.00
April 138124.67 115.93 02-APR-04:50 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 13106681.47 3905.72 26-NOV-24:00 0.00 0.00 0.00 0.00 0.00
December 71781553.48 22422.50 20-DEC-23:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.235817E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 71781553.48 22875.41   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 1709856.57 214.31 31-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 13752759.09 740.86 04-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 9335262.57 393.14 21-MAR-07:20 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 1493847.73 167.90 13-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 1211476.03 168.34 27-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 27503201.99     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 13752759.09 740.86   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 51893262.94 1129.56 23-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 33109609.38 1464.09 04-FEB-06:00 0.00 0.00 0.00 0.00 0.00
March 25142080.18 889.48 16-MAR-04:00 0.00 0.00 0.00 0.00 0.00
April 1247493.01 187.45 01-APR-05:00 0.00 0.00 0.00 0.00 0.00
May 1114406.90 368.12 01-MAY-04:00 0.00 0.00 0.00 0.00 0.00
June 118207.10 49.27 25-JUN-16:40 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 115318.74 98.98 07-AUG-10:50 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 399433.24 94.88 14-OCT-05:00 0.00 0.00 0.00 0.00 0.00
November 14873073.35 966.63 13-NOV-04:50 0.00 0.00 0.00 0.00 0.00
December 53969946.83 1169.79 16-DEC-06:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.181983E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 53969946.83 1464.09   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 1686479.37 456.57 04-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1686479.37     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1686479.37 456.57   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 8846.22 0.55 04-JAN-04:05 0.00 0.00 0.00 0.00 0.00
February 16572.22 0.54 19-FEB-09:06 0.00 0.00 0.00 0.00 0.00
March 46080.99 68.77 02-MAR-12:00 0.00 0.00 0.00 0.00 0.00
April 10685.13 0.54 01-APR-17:01 0.00 0.00 0.00 0.00 0.00
May 10400.63 0.54 27-MAY-03:05 0.00 0.00 0.00 0.00 0.00
June 10554.82 0.55 14-JUN-09:20 0.00 0.00 0.00 0.00 0.00
July 6697.04 0.54 20-JUL-14:30 0.00 0.00 0.00 0.00 0.00
August 10193.91 0.55 24-AUG-20:50 0.00 0.00 0.00 0.00 0.00
September 6153.07 0.54 06-SEP-17:02 0.00 0.00 0.00 0.00 0.00
October 10045.73 0.55 19-OCT-02:30 0.00 0.00 0.00 0.00 0.00
November 14378.76 0.55 19-NOV-08:10 0.00 0.00 0.00 0.00 0.00
December 14980.82 0.55 03-DEC-04:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 165589.34     0.00 0.00 0.00 0.00 0.00
Minimum of Months 6153.07 0.54   0.00 0.00 0.00 0.00 0.00
Maximum of Months 46080.99 68.77   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 28130311.24 2765.87 09-JAN-09:03 0.00 0.00 0.00 0.00 0.00
February 51152227.10 2832.30 16-FEB-09:05 0.00 0.00 0.00 0.00 0.00
March 22787718.29 4704.09 16-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 4859560.02 3074.60 30-APR-08:05 0.00 0.00 0.00 0.00 0.00
May 2869823.94 2912.76 08-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 1425325.94 2631.96 19-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 198361.16 1194.08 03-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 1698657.12 2503.40 29-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 1725353.29 2357.69 26-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 2536652.92 3233.39 02-OCT-08:05 0.00 0.00 0.00 0.00 0.00
November 9661038.31 2933.69 30-NOV-09:05 0.00 0.00 0.00 0.00 0.00
December 34813350.74 2998.35 23-DEC-09:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.161858E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 198361.16 1194.08   0.00 0.00 0.00 0.00 0.00
Maximum of Months 51152227.10 4704.09   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 79262510.07 5626.82 25-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 85635933.57 5698.44 04-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 43157222.47 5687.10 16-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 5487380.47 3353.25 09-APR-08:05 0.00 0.00 0.00 0.00 0.00
May 2934335.28 2955.91 08-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 1016734.98 2471.55 19-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 101374.67 1013.75 03-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 2011995.94 2671.72 13-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 2569268.99 2361.41 05-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 6231811.51 3134.92 14-OCT-08:05 0.00 0.00 0.00 0.00 0.00
November 19618763.68 3066.58 19-NOV-09:05 0.00 0.00 0.00 0.00 0.00
December 92590302.40 5331.66 27-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.340618E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 101374.67 1013.75   0.00 0.00 0.00 0.00 0.00
Maximum of Months 92590302.40 5698.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.201207E+09 30893.51 27-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.233857E+09 33026.53 04-FEB-19:03 0.00 0.00 0.00 0.00 0.00
March 0.132820E+09 29795.91 15-MAR-15:03 0.00 0.00 0.00 0.00 0.00
April 49079326.48 30336.05 21-APR-08:05 0.00 0.00 0.00 0.00 0.00
May 17566407.51 18246.42 01-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 15916118.00 14852.60 12-JUN-08:07 0.00 0.00 0.00 0.00 0.00
July 21605857.99 14548.73 21-JUL-08:07 0.00 0.00 0.00 0.00 0.00
August 18150165.61 13039.68 18-AUG-08:07 0.00 0.00 0.00 0.00 0.00
September 9134144.49 15079.39 25-SEP-18:07 0.00 0.00 0.00 0.00 0.00
October 63088499.87 27918.37 18-OCT-08:05 0.00 0.00 0.00 0.00 0.00
November 69664498.76 29249.03 29-NOV-09:05 0.00 0.00 0.00 0.00 0.00
December 0.179711E+09 28107.08 06-DEC-09:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.101180E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 9134144.49 13039.68   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.233857E+09 33026.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 31163091.81 2734.64 25-JAN-16:05 0.00 0.00 0.00 0.00 0.00
February 48126507.12 3075.34 03-FEB-16:04 0.00 0.00 0.00 0.00 0.00
March 17700780.59 2531.17 19-MAR-15:05 0.00 0.00 0.00 0.00 0.00
April 301333.56 3013.34 30-APR-08:05 0.00 0.00 0.00 0.00 0.00
May 230490.21 1151.58 25-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 253001.70 2507.55 28-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 148062.12 1480.37 18-OCT-08:05 0.00 0.00 0.00 0.00 0.00
November 7325908.76 2419.43 12-NOV-09:05 0.00 0.00 0.00 0.00 0.00
December 41773622.76 2468.64 20-DEC-19:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.147023E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 48126507.12 3075.34   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 88118804.83 2901.57 25-JAN-16:03 0.00 0.00 0.00 0.00 0.00
February 76242260.28 3616.49 03-FEB-16:03 0.00 0.00 0.00 0.00 0.00
March 31332280.43 2823.14 15-MAR-15:04 0.00 0.00 0.00 0.00 0.00
April 325443.23 3164.41 30-APR-08:05 0.00 0.00 0.00 0.00 0.00
May 307016.74 1439.40 25-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 290823.60 2621.96 28-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 374498.89 2584.25 18-OCT-08:05 0.00 0.00 0.00 0.00 0.00
November 15799407.88 2402.79 29-NOV-09:05 0.00 0.00 0.00 0.00 0.00
December 0.103322E+09 3114.69 27-DEC-16:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.316113E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.103322E+09 3616.49   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 35001179.46 1317.76 25-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 31708093.38 1697.06 04-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 21915686.74 1703.05 16-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 1372367.39 711.20 29-APR-08:05 0.00 0.00 0.00 0.00 0.00
May 1277577.68 737.89 24-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 834683.15 762.51 18-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 288039.99 689.54 03-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 891441.42 749.76 03-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 814214.25 686.79 07-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 1497445.34 793.97 15-OCT-08:05 0.00 0.00 0.00 0.00 0.00
November 10761808.27 746.46 28-NOV-19:05 0.00 0.00 0.00 0.00 0.00
December 36618986.68 1353.56 15-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.142982E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 288039.99 686.79   0.00 0.00 0.00 0.00 0.00
Maximum of Months 36618986.68 1703.05   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 81022244.11 1694.65 25-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 53608919.01 1716.88 04-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 34308124.83 1715.03 16-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 1432775.26 764.19 08-APR-08:05 0.00 0.00 0.00 0.00 0.00
May 1236955.85 724.90 24-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 747322.90 790.60 19-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 201127.94 715.81 03-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 930761.26 745.11 13-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 990256.94 667.71 14-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 1800599.03 752.12 09-OCT-08:05 0.00 0.00 0.00 0.00 0.00
November 18589925.16 1679.40 13-NOV-09:02 0.00 0.00 0.00 0.00 0.00
December 79763671.24 1700.73 15-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.274633E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 201127.94 667.71   0.00 0.00 0.00 0.00 0.00
Maximum of Months 81022244.11 1716.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 11769463.72 2226.45 31-JAN-09:05 0.00 0.00 0.00 0.00 0.00
February 41247548.75 2866.11 04-FEB-09:04 0.00 0.00 0.00 0.00 0.00
March 24688953.36 6250.94 16-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 4437227.38 3942.68 27-APR-08:05 0.00 0.00 0.00 0.00 0.00
May 1402838.69 3306.31 01-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 216402.50 331.99 25-JUN-08:07 0.00 0.00 0.00 0.00 0.00
July 189308.07 319.13 20-JUL-08:07 0.00 0.00 0.00 0.00 0.00
August 1026690.63 3436.20 28-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 396871.13 1008.43 06-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 207049.73 796.81 16-OCT-08:07 0.00 0.00 0.00 0.00 0.00
November 5219060.17 2272.22 25-NOV-09:06 0.00 0.00 0.00 0.00 0.00
December 9465003.02 1752.60 28-DEC-16:06 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.100266E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 189308.07 319.13   0.00 0.00 0.00 0.00 0.00
Maximum of Months 41247548.75 6250.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.366951E+12 0.243432E+12 448145.34 06-JAN-23:00 207648.36 0.81
February 0.00 0.00 0.401368E+12 0.270618E+12 444408.36 10-FEB-22:00 212090.03 0.84
March 0.00 0.00 0.513478E+12 0.326309E+12 460281.68 09-MAR-21:00 206427.62 0.85
April 0.00 0.00 0.609081E+12 0.395661E+12 399804.01 14-APR-20:00 229260.16 1.00
May 0.00 0.00 0.818786E+12 0.473531E+12 486570.12 28-MAY-20:00 192756.62 1.00
June 0.00 0.00 0.902818E+12 0.489816E+12 486661.69 21-JUN-19:10 210922.05 1.00
July 0.00 0.00 0.961076E+12 0.519890E+12 497593.42 27-JUL-21:00 271832.74 1.00
August 0.00 0.00 0.960372E+12 0.513207E+12 493841.75 06-AUG-21:00 204017.05 1.00
September 0.00 0.00 0.912906E+12 0.495387E+12 549866.27 25-SEP-21:00 227490.35 1.00
October 0.00 0.00 0.855511E+12 0.484368E+12 489926.99 01-OCT-20:00 198792.49 1.00
November 0.00 0.00 0.665263E+12 0.382345E+12 486518.01 21-NOV-20:50 211242.40 0.94
December 0.00 0.00 0.478519E+12 0.283279E+12 497113.07 25-DEC-22:00 192411.11 0.90
                 
Annual Sum or Average 0.00 0.00 0.844613E+13 0.487784E+13       0.95
Minimum of Months 0.00 0.00 0.366951E+12 0.243432E+12 399804.01   192411.11 0.81
Maximum of Months 0.00 0.00 0.961076E+12 0.519890E+12 549866.27   271832.74 1.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.677718E+11 0.425099E+11 69237.46 07-JAN-03:30 25566.96 0.77
February 0.00 0.00 0.730596E+11 0.480295E+11 66420.60 19-FEB-11:08 26052.04 0.83
March 0.00 0.00 0.884565E+11 0.575723E+11 71113.53 19-MAR-07:30 26973.69 0.84
April 0.00 0.00 0.104449E+12 0.688285E+11 71667.21 01-APR-02:40 25712.06 1.00
May 0.00 0.00 0.130143E+12 0.775898E+11 75328.85 27-MAY-13:50 28357.52 1.00
June 0.00 0.00 0.140044E+12 0.776376E+11 65096.78 05-JUN-14:20 28525.83 1.00
July 0.00 0.00 0.146006E+12 0.810793E+11 78320.77 02-JUL-17:10 27791.27 1.00
August 0.00 0.00 0.147946E+12 0.807202E+11 77733.94 12-AUG-08:00 27786.08 1.00
September 0.00 0.00 0.138211E+12 0.772421E+11 62991.20 06-SEP-11:00 33073.01 1.00
October 0.00 0.00 0.132898E+12 0.774799E+11 75152.59 01-OCT-07:20 27258.97 1.00
November 0.00 0.00 0.111112E+12 0.643230E+11 78941.54 08-NOV-09:00 27796.03 0.93
December 0.00 0.00 0.838727E+11 0.496187E+11 74613.04 24-DEC-07:30 25606.80 0.86
                 
Annual Sum or Average 0.00 0.00 0.136397E+13 0.802631E+12       0.94
Minimum of Months 0.00 0.00 0.677718E+11 0.425099E+11 62991.20   25566.96 0.77
Maximum of Months 0.00 0.00 0.147946E+12 0.810793E+11 78941.54   33073.01 1.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.500101E+10 0.266567E+10 16578.72 07-JAN-09:02 9469.95 0.74
February 0.00 0.00 0.571887E+10 0.324315E+10 15875.85 02-FEB-09:02 9604.87 0.79
March 0.00 0.00 0.734195E+10 0.427425E+10 16061.03 06-MAR-09:02 9583.96 0.80
April 0.00 0.00 0.904973E+10 0.549608E+10 15062.95 16-APR-08:62 10374.90 0.91
May 0.00 0.00 0.106748E+11 0.656577E+10 15686.34 24-MAY-18:02 9903.32 0.93
June 0.00 0.00 0.110679E+11 0.684062E+10 14746.76 13-JUN-08:62 10678.28 0.94
July 0.00 0.00 0.123581E+11 0.786367E+10 14422.62 02-JUL-18:02 10561.54 0.95
August 0.00 0.00 0.118050E+11 0.739586E+10 15960.84 12-AUG-08:62 9468.31 0.94
September 0.00 0.00 0.115127E+11 0.720758E+10 14706.98 16-SEP-08:62 10676.13 0.94
October 0.00 0.00 0.109973E+11 0.680684E+10 15330.20 01-OCT-08:62 9940.10 0.94
November 0.00 0.00 0.813575E+10 0.467872E+10 15331.05 24-NOV-09:02 9064.95 0.88
December 0.00 0.00 0.598794E+10 0.326474E+10 16297.40 23-DEC-09:02 9173.53 0.80
                 
Annual Sum or Average 0.00 0.00 0.109651E+12 0.663029E+11       0.88
Minimum of Months 0.00 0.00 0.500101E+10 0.266567E+10 14422.62   9064.95 0.74
Maximum of Months 0.00 0.00 0.123581E+11 0.786367E+10 16578.72   10678.28 0.95



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.319531E+10 0.142379E+10 16699.65 07-JAN-09:02 9392.06 0.63
February 0.00 0.00 0.434242E+10 0.218656E+10 15714.46 18-FEB-09:02 10243.05 0.72
March 0.00 0.00 0.627573E+10 0.346590E+10 16119.30 19-MAR-08:62 8568.26 0.76
April 0.00 0.00 0.850603E+10 0.506243E+10 15256.09 16-APR-08:62 10465.44 0.90
May 0.00 0.00 0.106673E+11 0.654828E+10 16227.09 24-MAY-18:02 9786.57 0.93
June 0.00 0.00 0.112557E+11 0.698094E+10 14883.05 13-JUN-08:62 10989.21 0.94
July 0.00 0.00 0.124756E+11 0.793818E+10 14802.89 02-JUL-18:02 10543.33 0.95
August 0.00 0.00 0.115705E+11 0.716999E+10 16026.41 12-AUG-08:62 9635.45 0.94
September 0.00 0.00 0.107490E+11 0.651833E+10 14904.84 16-SEP-08:62 10763.60 0.94
October 0.00 0.00 0.954384E+10 0.554791E+10 15427.95 01-OCT-08:62 10082.99 0.92
November 0.00 0.00 0.652278E+10 0.336794E+10 15451.00 24-NOV-09:02 9080.33 0.83
December 0.00 0.00 0.424860E+10 0.201748E+10 16166.26 23-DEC-09:02 9260.74 0.70
                 
Annual Sum or Average 0.00 0.00 0.993529E+11 0.582277E+11       0.85
Minimum of Months 0.00 0.00 0.319531E+10 0.142379E+10 14802.89   8568.26 0.63
Maximum of Months 0.00 0.00 0.124756E+11 0.793818E+10 16699.65   10989.21 0.95



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.286437E+11 0.188831E+11 46999.76 02-JAN-14:30 41049.21 0.61
February 0.00 0.00 0.254304E+11 0.158029E+11 40914.99 11-FEB-14:30 31860.21 0.63
March 0.00 0.00 0.244281E+11 0.128676E+11 33815.14 04-MAR-11:33 26810.79 0.68
April 0.00 0.00 0.248458E+11 0.120424E+11 26188.09 15-APR-14:30 19109.79 0.81
May 0.00 0.00 0.287785E+11 0.128948E+11 25432.48 25-MAY-20:20 8189.66 0.93
June 0.00 0.00 0.327046E+11 0.152151E+11 28392.23 18-JUN-20:20 9890.71 0.99
July 0.00 0.00 0.379278E+11 0.192087E+11 28013.39 29-JUL-17:20 21540.98 0.99
August 0.00 0.00 0.379063E+11 0.197557E+11 28960.85 20-AUG-13:40 22056.05 0.98
September 0.00 0.00 0.455575E+11 0.270677E+11 38334.99 30-SEP-13:30 28361.50 1.00
October 0.00 0.00 0.494258E+11 0.304108E+11 43594.04 25-OCT-12:30 36520.26 0.99
November 0.00 0.00 0.397908E+11 0.247835E+11 46352.72 07-NOV-13:30 41382.59 0.85
December 0.00 0.00 0.310511E+11 0.200608E+11 46857.70 09-DEC-12:30 40386.09 0.64
                 
Annual Sum or Average 0.00 0.00 0.406490E+12 0.228993E+12       0.84
Minimum of Months 0.00 0.00 0.244281E+11 0.120424E+11 25432.48   8189.66 0.61
Maximum of Months 0.00 0.00 0.494258E+11 0.304108E+11 46999.76   41382.59 1.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.263369E+11 0.124269E+11 105420.79 07-JAN-09:02 55776.65 0.63
February 0.00 0.00 0.319487E+11 0.168913E+11 98025.82 18-FEB-09:02 60874.22 0.62
March 0.00 0.00 0.412194E+11 0.227272E+11 101305.16 19-MAR-08:62 51264.94 0.65
April 0.00 0.00 0.520612E+11 0.310587E+11 94143.87 16-APR-08:62 62902.42 0.71
May 0.00 0.00 0.667253E+11 0.436780E+11 104447.62 24-MAY-18:02 55721.08 0.75
June 0.00 0.00 0.724628E+11 0.495608E+11 88504.89 04-JUN-15:02 70463.17 0.78
July 0.00 0.00 0.769342E+11 0.530499E+11 94781.61 02-JUL-18:02 62123.63 0.82
August 0.00 0.00 0.706164E+11 0.470911E+11 100949.95 12-AUG-08:62 56832.12 0.77
September 0.00 0.00 0.667773E+11 0.441662E+11 88738.83 16-SEP-08:62 66297.93 0.76
October 0.00 0.00 0.588472E+11 0.359543E+11 96311.77 01-OCT-08:62 59984.38 0.71
November 0.00 0.00 0.444458E+11 0.251661E+11 95628.14 24-NOV-09:02 52919.66 0.69
December 0.00 0.00 0.313812E+11 0.156215E+11 101121.16 23-DEC-09:02 56287.40 0.65
                 
Annual Sum or Average 0.00 0.00 0.639756E+12 0.397392E+12       0.71
Minimum of Months 0.00 0.00 0.263369E+11 0.124269E+11 88504.89   51264.94 0.62
Maximum of Months 0.00 0.00 0.769342E+11 0.530499E+11 105420.79   70463.17 0.82



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.526302E+10 0.295623E+10 14771.08 07-JAN-09:02 8614.05 0.77
February 0.00 0.00 0.573911E+10 0.330895E+10 14046.97 18-FEB-09:02 9048.09 0.81
March 0.00 0.00 0.722392E+10 0.421747E+10 14434.73 06-MAR-09:02 8742.46 0.83
April 0.00 0.00 0.900595E+10 0.546953E+10 13311.97 29-APR-08:62 9331.07 0.95
May 0.00 0.00 0.107187E+11 0.666010E+10 14303.63 24-MAY-18:02 8759.07 0.95
June 0.00 0.00 0.116841E+11 0.748296E+10 12665.82 05-JUN-08:62 10228.80 0.96
July 0.00 0.00 0.127495E+11 0.837447E+10 12905.95 02-JUL-18:02 9498.82 0.97
August 0.00 0.00 0.118439E+11 0.757387E+10 14330.02 12-AUG-08:62 8506.96 0.95
September 0.00 0.00 0.119613E+11 0.779832E+10 13129.69 05-SEP-08:62 9588.11 0.97
October 0.00 0.00 0.111757E+11 0.707219E+10 13777.94 01-OCT-08:62 8912.02 0.96
November 0.00 0.00 0.818562E+10 0.481309E+10 13760.35 24-NOV-09:02 8124.97 0.90
December 0.00 0.00 0.557567E+10 0.302921E+10 14620.03 23-DEC-09:02 8232.35 0.80
                 
Annual Sum or Average 0.00 0.00 0.111127E+12 0.687564E+11       0.90
Minimum of Months 0.00 0.00 0.526302E+10 0.295623E+10 12665.82   8124.97 0.77
Maximum of Months 0.00 0.00 0.127495E+11 0.837447E+10 14771.08   10228.80 0.97



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.347252E+10 0.167858E+10 14984.63 07-JAN-09:02 8640.88 0.64
February 0.00 0.00 0.432641E+10 0.227103E+10 14076.56 18-FEB-09:02 9184.28 0.75
March 0.00 0.00 0.611205E+10 0.340665E+10 14462.17 19-MAR-08:62 7695.19 0.79
April 0.00 0.00 0.843822E+10 0.498556E+10 13458.44 29-APR-08:62 9392.34 0.94
May 0.00 0.00 0.107068E+11 0.662745E+10 14727.84 24-MAY-18:02 8664.73 0.96
June 0.00 0.00 0.118698E+11 0.763341E+10 12779.64 05-JUN-08:62 10322.60 0.97
July 0.00 0.00 0.128658E+11 0.845300E+10 13169.68 02-JUL-18:02 9501.88 0.97
August 0.00 0.00 0.115972E+11 0.728335E+10 14367.03 12-AUG-08:62 8643.83 0.95
September 0.00 0.00 0.111919E+11 0.701609E+10 13308.59 05-SEP-08:62 9640.13 0.96
October 0.00 0.00 0.969784E+10 0.572553E+10 13840.55 01-OCT-08:62 9028.77 0.94
November 0.00 0.00 0.657385E+10 0.359810E+10 13848.60 24-NOV-09:02 8127.99 0.84
December 0.00 0.00 0.385308E+10 0.185164E+10 14477.52 23-DEC-09:02 8298.67 0.70
                 
Annual Sum or Average 0.00 0.00 0.100705E+12 0.605304E+11       0.87
Minimum of Months 0.00 0.00 0.347252E+10 0.167858E+10 12779.64   7695.19 0.64
Maximum of Months 0.00 0.00 0.128658E+11 0.845300E+10 14984.63   10322.60 0.97



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.107075E+10 0.549195E+09 4524.37 07-JAN-09:02 2320.97 0.67
February 0.00 0.00 0.131670E+10 0.721285E+09 4312.16 02-FEB-09:02 2385.71 0.76
March 0.00 0.00 0.175212E+10 0.983624E+09 4362.80 06-MAR-09:02 2369.36 0.77
April 0.00 0.00 0.223362E+10 0.132047E+10 4124.66 22-APR-08:62 2646.01 0.91
May 0.00 0.00 0.268910E+10 0.161326E+10 4248.11 24-MAY-18:02 2511.28 0.93
June 0.00 0.00 0.280890E+10 0.169593E+10 3969.55 13-JUN-08:62 2671.65 0.94
July 0.00 0.00 0.316332E+10 0.198347E+10 3905.80 15-JUL-08:62 2873.21 0.95
August 0.00 0.00 0.298911E+10 0.183892E+10 4358.92 12-AUG-08:62 2303.48 0.93
September 0.00 0.00 0.289397E+10 0.177817E+10 4063.56 16-SEP-08:62 2663.14 0.94
October 0.00 0.00 0.270088E+10 0.162740E+10 4199.08 01-OCT-08:62 2495.31 0.93
November 0.00 0.00 0.191459E+10 0.105680E+10 4172.76 24-NOV-09:02 2192.84 0.86
December 0.00 0.00 0.134061E+10 0.709742E+09 4466.14 23-DEC-09:02 2239.37 0.73
                 
Annual Sum or Average 0.00 0.00 0.268737E+11 0.158783E+11       0.86
Minimum of Months 0.00 0.00 0.107075E+10 0.549195E+09 3905.80   2192.84 0.67
Maximum of Months 0.00 0.00 0.316332E+10 0.198347E+10 4524.37   2873.21 0.95



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.629069E+09 0.270507E+09 4552.18 07-JAN-09:02 2298.18 0.53
February 0.00 0.00 0.966108E+09 0.469573E+09 4263.40 18-FEB-09:02 2545.30 0.67
March 0.00 0.00 0.147781E+10 0.782288E+09 4358.57 19-MAR-08:62 2093.99 0.73
April 0.00 0.00 0.209171E+10 0.120157E+10 4171.29 16-APR-08:62 2632.00 0.90
May 0.00 0.00 0.268796E+10 0.160902E+10 4398.81 24-MAY-18:02 2468.47 0.93
June 0.00 0.00 0.285770E+10 0.173223E+10 4005.83 13-JUN-08:62 2760.33 0.94
July 0.00 0.00 0.319455E+10 0.200395E+10 3939.46 15-JUL-08:62 2902.18 0.95
August 0.00 0.00 0.292814E+10 0.177512E+10 4374.85 12-AUG-08:62 2341.19 0.93
September 0.00 0.00 0.269541E+10 0.158985E+10 4107.51 16-SEP-08:62 2670.73 0.93
October 0.00 0.00 0.231758E+10 0.128244E+10 4206.95 01-OCT-08:62 2537.50 0.91
November 0.00 0.00 0.149552E+10 0.728129E+09 4201.89 24-NOV-09:02 2192.08 0.81
December 0.00 0.00 0.913153E+09 0.416036E+09 4428.59 23-DEC-09:02 2257.07 0.59
                 
Annual Sum or Average 0.00 0.00 0.242547E+11 0.138607E+11       0.82
Minimum of Months 0.00 0.00 0.629069E+09 0.270507E+09 3939.46   2093.99 0.53
Maximum of Months 0.00 0.00 0.319455E+10 0.200395E+10 4552.18   2902.18 0.95



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.104754E+11 0.711038E+10 18395.96 07-JAN-09:02 9609.76 0.81
February 0.00 0.00 0.994665E+10 0.660558E+10 17852.57 02-FEB-09:02 9926.24 0.82
March 0.00 0.00 0.104982E+11 0.665039E+10 18054.47 06-MAR-09:02 9516.72 0.81
April 0.00 0.00 0.110701E+11 0.689127E+10 16719.43 16-APR-08:62 10548.91 0.89
May 0.00 0.00 0.125400E+11 0.780094E+10 17915.67 24-MAY-18:02 9739.77 0.91
June 0.00 0.00 0.133892E+11 0.859009E+10 15466.31 13-JUN-08:62 11081.66 0.92
July 0.00 0.00 0.147289E+11 0.964710E+10 16299.44 02-JUL-18:02 10598.86 0.93
August 0.00 0.00 0.145227E+11 0.954368E+10 18033.31 12-AUG-08:62 9329.09 0.91
September 0.00 0.00 0.156604E+11 0.107223E+11 15829.60 16-SEP-08:62 11157.45 0.94
October 0.00 0.00 0.162947E+11 0.113605E+11 17188.73 01-OCT-08:62 9984.80 0.94
November 0.00 0.00 0.135124E+11 0.915361E+10 17053.94 24-NOV-09:02 8954.16 0.90
December 0.00 0.00 0.113263E+11 0.752651E+10 18335.68 23-DEC-09:02 9525.50 0.85
                 
Annual Sum or Average 0.00 0.00 0.153965E+12 0.101602E+12       0.89
Minimum of Months 0.00 0.00 0.994665E+10 0.660558E+10 15466.31   8954.16 0.81
Maximum of Months 0.00 0.00 0.162947E+11 0.113605E+11 18395.96   11157.45 0.94



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 247.56 20925.20 19-JAN-09:05
February 0.00 0.00 01-FEB-00:03 295.84 23516.82 23-FEB-19:05
March 0.00 0.00 01-MAR-00:03 144.55 29026.89 19-MAR-15:05
April 0.00 0.00 01-APR-00:10 25.94 29865.53 21-APR-08:05
May 0.00 0.00 01-MAY-00:05 10.62 22657.49 01-MAY-08:05
June 0.00 0.00 01-JUN-00:05 8.02 12519.64 12-JUN-08:07
July 0.00 0.00 01-JUL-00:10 8.04 12677.63 21-JUL-08:07
August 0.00 0.00 01-AUG-00:05 9.57 23233.95 28-AUG-08:05
September 0.00 0.00 01-SEP-00:05 6.37 14136.58 15-SEP-08:05
October 0.00 0.00 01-OCT-00:10 27.69 29836.36 18-OCT-08:05
November 0.00 0.00 01-NOV-00:05 70.87 24739.39 29-NOV-09:05
December 0.00 0.00 01-DEC-00:03 259.80 25376.47 06-DEC-09:05
             
Annual Sum or Average 0.00     91.95    
Minimum of Months 0.00 0.00   6.37 12519.64  
Maximum of Months 0.00 0.00   295.84 29865.53  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 198884.53 602087.16 01-JAN-19:03 0.00 0.00 01-JAN-00:10
February 238348.94 635095.90 11-FEB-19:03 0.00 0.00 01-FEB-00:03
March 269647.72 629189.87 09-MAR-21:00 0.00 0.00 01-MAR-00:03
April 329665.05 610870.17 14-APR-18:05 0.00 0.00 01-APR-00:10
May 417926.50 726161.86 24-MAY-18:03 0.00 0.00 01-MAY-00:05
June 473336.96 704454.26 08-JUN-18:05 0.00 0.00 01-JUN-00:05
July 488330.10 728194.23 27-JUL-18:03 0.00 0.00 01-JUL-00:10
August 484811.15 696768.01 21-AUG-18:03 0.00 0.00 01-AUG-00:05
September 479984.98 735783.78 18-SEP-18:03 0.00 0.00 01-SEP-00:05
October 438218.00 679314.75 03-OCT-18:03 0.00 0.00 01-OCT-00:10
November 355206.73 681473.79 21-NOV-21:30 0.00 0.00 01-NOV-00:05
December 250891.65 721059.92 23-DEC-19:03 0.00 0.00 01-DEC-00:03
             
Annual Sum or Average 369396.11     0.00    
Minimum of Months 198884.53 602087.16   0.00 0.00  
Maximum of Months 488330.10 735783.78   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 20264.86 40654.70 19-JAN-07:15
February 0.00 0.00 01-FEB-00:03 20086.29 40516.43 03-FEB-07:15
March 0.00 0.00 01-MAR-00:03 19531.37 39687.24 01-MAR-08:00
April 0.00 0.00 01-APR-00:10 18692.10 38061.90 03-APR-06:10
May 0.00 0.00 01-MAY-00:05 17836.35 36388.57 01-MAY-06:15
June 0.00 0.00 01-JUN-00:05 17184.86 34664.81 01-JUN-06:20
July 0.00 0.00 01-JUL-00:10 16893.71 33634.53 03-JUL-06:40
August 0.00 0.00 01-AUG-00:05 17092.84 34410.08 31-AUG-06:30
September 0.00 0.00 01-SEP-00:05 17671.22 35864.03 29-SEP-06:50
October 0.00 0.00 01-OCT-00:10 18497.10 37783.44 31-OCT-06:40
November 0.00 0.00 01-NOV-00:05 19354.86 39377.96 30-NOV-08:00
December 0.00 0.00 01-DEC-00:03 19998.76 40396.48 27-DEC-07:15
             
Annual Sum or Average 0.00     18583.76    
Minimum of Months 0.00 0.00   16893.71 33634.53  
Maximum of Months 0.00 0.00   20264.86 40654.70  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.587890E+10 0.87 2194.93 01-JAN-00:10 0.87
February 0.530997E+10 0.87 2194.93 01-FEB-00:03 0.87
March 0.587890E+10 0.87 2194.93 01-MAR-00:03 0.87
April 0.568926E+10 0.87 2194.93 01-APR-00:10 0.87
May 0.587890E+10 0.87 2194.93 01-MAY-00:05 0.87
June 0.568926E+10 0.87 2194.93 01-JUN-00:05 0.87
July 0.587890E+10 0.87 2194.93 01-JUL-00:10 0.87
August 0.587890E+10 0.87 2194.93 01-AUG-00:05 0.87
September 0.568926E+10 0.87 2194.93 01-SEP-00:05 0.87
October 0.587890E+10 0.87 2194.93 01-OCT-00:10 0.87
November 0.568926E+10 0.87 2194.93 01-NOV-00:05 0.87
December 0.587890E+10 0.87 2194.93 01-DEC-00:03 0.87
           
Annual Sum or Average 0.692193E+11 0.87      
Minimum of Months 0.530997E+10 0.87 2194.93   0.87
Maximum of Months 0.587890E+10 0.87 2194.93   0.87



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.369580E+11 0.83 30675.11 13-JAN-22:10 1.35
February 0.335976E+11 0.84 29143.39 17-FEB-22:10 1.31
March 0.374031E+11 0.84 27211.40 03-MAR-22:10 1.25
April 0.372295E+11 0.85 28858.10 13-APR-21:10 1.30
May 0.400984E+11 0.87 29590.68 22-MAY-21:10 1.32
June 0.402857E+11 0.89 31173.86 29-JUN-21:10 1.37
July 0.422262E+11 0.90 32528.99 27-JUL-21:10 1.40
August 0.423097E+11 0.90 33633.48 21-AUG-21:10 1.43
September 0.416779E+11 0.91 34980.22 21-SEP-21:10 1.47
October 0.420748E+11 0.89 34604.24 25-OCT-21:20 1.46
November 0.387887E+11 0.87 33030.45 10-NOV-22:10 1.42
December 0.377557E+11 0.84 31960.88 08-DEC-22:10 1.39
           
Annual Sum or Average 0.470405E+12 0.87      
Minimum of Months 0.335976E+11 0.83 27211.40   1.25
Maximum of Months 0.423097E+11 0.91 34980.22   1.47



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.26 76.61 01-JAN-00:10 0.26
February 0.185347E+09 0.26 76.61 01-FEB-00:03 0.26
March 0.205205E+09 0.26 76.61 01-MAR-00:03 0.26
April 0.198586E+09 0.26 76.61 01-APR-00:10 0.26
May 0.205205E+09 0.26 76.61 01-MAY-00:05 0.26
June 0.198586E+09 0.26 76.61 01-JUN-00:05 0.26
July 0.205205E+09 0.26 76.61 01-JUL-00:10 0.26
August 0.205205E+09 0.26 76.61 01-AUG-00:05 0.26
September 0.198586E+09 0.26 76.61 01-SEP-00:05 0.26
October 0.205205E+09 0.26 76.61 01-OCT-00:10 0.26
November 0.198586E+09 0.26 76.61 01-NOV-00:05 0.26
December 0.205205E+09 0.26 76.61 01-DEC-00:03 0.26
           
Annual Sum or Average 0.241613E+10 0.26      
Minimum of Months 0.185347E+09 0.26 76.61   0.26
Maximum of Months 0.205205E+09 0.26 76.61   0.26



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:10 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:10 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:05 0.00
June 0.00 -0.0 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:10 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 -0.0 0.00 01-MAR-00:03 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.19 612.92 01-JAN-07:05 0.26
February 0.105030E+10 0.19 612.92 01-FEB-07:05 0.26
March 0.116283E+10 0.19 612.92 01-MAR-07:05 0.26
April 0.112532E+10 0.19 612.92 01-APR-06:10 0.26
May 0.116283E+10 0.19 612.92 01-MAY-06:05 0.26
June 0.112532E+10 0.19 612.92 01-JUN-06:10 0.26
July 0.116283E+10 0.19 612.92 01-JUL-06:10 0.26
August 0.116283E+10 0.19 612.92 01-AUG-06:10 0.26
September 0.112532E+10 0.19 612.92 01-SEP-06:10 0.26
October 0.116283E+10 0.19 612.92 01-OCT-06:10 0.26
November 0.112532E+10 0.19 612.92 01-NOV-06:05 0.26
December 0.116283E+10 0.19 612.92 01-DEC-07:10 0.26
           
Annual Sum or Average 0.136914E+11 0.19      
Minimum of Months 0.105030E+10 0.19 612.92   0.26
Maximum of Months 0.116283E+10 0.19 612.92   0.26



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.249585E+09 0.48 677.17 01-JAN-09:02 0.57
February 0.279900E+09 0.50 677.17 01-FEB-09:02 0.57
March 0.349844E+09 0.50 677.17 01-MAR-09:02 0.57
April 0.426253E+09 0.52 677.17 01-APR-08:62 0.57
May 0.480401E+09 0.53 677.17 01-MAY-08:62 0.57
June 0.486388E+09 0.54 677.17 01-JUN-08:62 0.57
July 0.552838E+09 0.55 677.17 01-JUL-08:62 0.57
August 0.521556E+09 0.54 677.17 01-AUG-08:62 0.57
September 0.512076E+09 0.54 677.17 01-SEP-08:62 0.57
October 0.489256E+09 0.54 677.17 01-OCT-08:62 0.57
November 0.362247E+09 0.52 677.17 01-NOV-08:62 0.57
December 0.284309E+09 0.49 677.17 01-DEC-09:02 0.57
           
Annual Sum or Average 0.499465E+10 0.52      
Minimum of Months 0.249585E+09 0.48 677.17   0.57
Maximum of Months 0.552838E+09 0.55 677.17   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.169088E+09 0.44 684.63 01-JAN-09:02 0.57
February 0.216879E+09 0.46 684.63 01-FEB-16:02 0.57
March 0.297574E+09 0.48 684.63 01-MAR-16:02 0.57
April 0.395819E+09 0.52 684.63 01-APR-08:62 0.57
May 0.479762E+09 0.53 684.63 01-MAY-08:62 0.57
June 0.496023E+09 0.54 684.63 01-JUN-08:62 0.57
July 0.559159E+09 0.55 684.63 01-JUL-08:62 0.57
August 0.508485E+09 0.54 684.63 01-AUG-08:62 0.57
September 0.472215E+09 0.54 684.63 01-SEP-08:62 0.57
October 0.416006E+09 0.53 684.63 01-OCT-08:62 0.57
November 0.290074E+09 0.49 684.63 01-NOV-08:62 0.57
December 0.208984E+09 0.46 684.63 01-DEC-09:02 0.57
           
Annual Sum or Average 0.451007E+10 0.51      
Minimum of Months 0.169088E+09 0.44 684.63   0.57
Maximum of Months 0.559159E+09 0.55 684.63   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.131908E+10 0.41 2138.75 02-JAN-14:30 0.57
February 0.111982E+10 0.41 2077.28 22-FEB-15:00 0.58
March 0.100918E+10 0.41 1605.03 02-MAR-14:30 0.57
April 0.103790E+10 0.46 956.89 15-APR-14:30 0.57
May 0.119527E+10 0.53 873.79 22-MAY-17:20 0.57
June 0.132582E+10 0.56 886.27 29-JUN-17:20 0.57
July 0.149998E+10 0.57 1011.85 29-JUL-17:20 0.57
August 0.149378E+10 0.56 1024.79 20-AUG-13:50 0.57
September 0.179840E+10 0.57 1806.14 30-SEP-13:40 0.57
October 0.205663E+10 0.57 2026.95 25-OCT-12:40 0.57
November 0.167544E+10 0.50 2145.10 07-NOV-13:40 0.57
December 0.137337E+10 0.40 2191.24 03-DEC-13:40 0.57
           
Annual Sum or Average 0.169047E+11 0.50      
Minimum of Months 0.100918E+10 0.40 873.79   0.57
Maximum of Months 0.205663E+10 0.57 2191.24   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.124087E+10 0.41 4140.11 01-JAN-09:02 0.57
February 0.145334E+10 0.41 4140.11 01-FEB-09:02 0.57
March 0.186933E+10 0.41 4140.11 01-MAR-16:02 0.57
April 0.233980E+10 0.41 4140.11 01-APR-08:62 0.57
May 0.299986E+10 0.43 4140.11 01-MAY-08:62 0.57
June 0.331085E+10 0.45 4140.11 01-JUN-08:62 0.57
July 0.353978E+10 0.47 4140.11 01-JUL-08:62 0.57
August 0.315093E+10 0.44 4140.11 01-AUG-08:62 0.57
September 0.296414E+10 0.43 4140.11 01-SEP-08:62 0.57
October 0.258648E+10 0.41 4140.11 01-OCT-08:62 0.57
November 0.194308E+10 0.41 4140.11 01-NOV-08:62 0.57
December 0.142184E+10 0.41 4140.11 01-DEC-09:02 0.57
           
Annual Sum or Average 0.288203E+11 0.42      
Minimum of Months 0.124087E+10 0.41 4140.11   0.57
Maximum of Months 0.353978E+10 0.47 4140.11   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.262570E+09 0.50 605.05 01-JAN-09:02 0.57
February 0.279067E+09 0.51 605.05 01-FEB-09:02 0.57
March 0.341505E+09 0.52 605.05 01-MAR-09:02 0.57
April 0.419357E+09 0.54 605.05 01-APR-08:62 0.57
May 0.483334E+09 0.55 605.05 01-MAY-08:62 0.57
June 0.525589E+09 0.55 605.05 01-JUN-08:62 0.57
July 0.576346E+09 0.56 605.05 01-JUL-08:62 0.57
August 0.524806E+09 0.54 605.05 01-AUG-08:62 0.57
September 0.538277E+09 0.55 605.05 01-SEP-08:62 0.57
October 0.502935E+09 0.55 605.05 01-OCT-08:62 0.57
November 0.372633E+09 0.53 605.05 01-NOV-08:62 0.57
December 0.265522E+09 0.49 605.05 01-DEC-09:02 0.57
           
Annual Sum or Average 0.509194E+10 0.53      
Minimum of Months 0.262570E+09 0.49 605.05   0.57
Maximum of Months 0.576346E+09 0.56 605.05   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.175826E+09 0.44 610.75 01-JAN-09:02 0.57
February 0.209269E+09 0.48 610.75 01-FEB-09:02 0.57
March 0.284580E+09 0.49 610.75 01-MAR-09:02 0.57
April 0.390769E+09 0.54 610.75 01-APR-08:62 0.57
May 0.483554E+09 0.55 610.75 01-MAY-08:62 0.57
June 0.535490E+09 0.55 610.75 01-JUN-08:62 0.57
July 0.582835E+09 0.56 610.75 01-JUL-08:62 0.57
August 0.513933E+09 0.54 610.75 01-AUG-08:62 0.57
September 0.498422E+09 0.55 610.75 01-SEP-08:62 0.57
October 0.428060E+09 0.54 610.75 01-OCT-08:62 0.57
November 0.290577E+09 0.50 610.75 01-NOV-08:62 0.57
December 0.186466E+09 0.45 610.75 01-DEC-09:02 0.57
           
Annual Sum or Average 0.457978E+10 0.52      
Minimum of Months 0.175826E+09 0.44 610.75   0.57
Maximum of Months 0.582835E+09 0.56 610.75   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 56413636.47 0.48 177.68 01-JAN-09:02 0.57
February 66109990.77 0.49 177.68 01-FEB-16:02 0.57
March 84814537.64 0.50 177.68 01-MAR-16:02 0.57
April 0.105788E+09 0.52 177.68 01-APR-08:62 0.57
May 0.121260E+09 0.53 177.68 01-MAY-08:62 0.57
June 0.123321E+09 0.54 177.68 01-JUN-08:62 0.57
July 0.141471E+09 0.54 177.68 01-JUL-08:62 0.57
August 0.131909E+09 0.53 177.68 01-AUG-08:62 0.57
September 0.128157E+09 0.54 177.68 01-SEP-08:62 0.57
October 0.119518E+09 0.53 177.68 01-OCT-08:62 0.57
November 85745243.56 0.51 177.68 01-NOV-08:62 0.57
December 65839988.02 0.49 177.68 01-DEC-09:02 0.57
           
Annual Sum or Average 0.123035E+10 0.52      
Minimum of Months 56413636.47 0.48 177.68   0.57
Maximum of Months 0.141471E+09 0.54 177.68   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 38929724.92 0.44 179.42 01-JAN-09:02 0.57
February 51109042.64 0.46 179.42 01-FEB-16:02 0.57
March 72326006.73 0.48 179.42 01-MAR-16:02 0.57
April 98487207.16 0.52 179.42 01-APR-08:62 0.57
May 0.121179E+09 0.53 179.42 01-MAY-08:62 0.57
June 0.125855E+09 0.54 179.42 01-JUN-08:62 0.57
July 0.143133E+09 0.55 179.42 01-JUL-08:62 0.57
August 0.128831E+09 0.53 179.42 01-AUG-08:62 0.57
September 0.118368E+09 0.54 179.42 01-SEP-08:62 0.57
October 0.101556E+09 0.52 179.42 01-OCT-08:62 0.57
November 68038144.17 0.49 179.42 01-NOV-15:02 0.57
December 49553399.27 0.45 179.42 01-DEC-09:02 0.57
           
Annual Sum or Average 0.111737E+10 0.50      
Minimum of Months 38929724.92 0.44 179.42   0.57
Maximum of Months 0.143133E+09 0.55 179.42   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.529549E+09 0.51 706.82 01-JAN-09:02 0.57
February 0.487281E+09 0.51 706.82 01-FEB-09:02 0.57
March 0.492178E+09 0.51 706.82 01-MAR-09:02 0.57
April 0.507904E+09 0.51 706.82 01-APR-08:62 0.57
May 0.561492E+09 0.52 706.82 01-MAY-08:62 0.57
June 0.600934E+09 0.53 706.82 01-JUN-08:62 0.57
July 0.669104E+09 0.53 706.82 01-JUL-08:62 0.57
August 0.653309E+09 0.52 706.82 01-AUG-08:62 0.57
September 0.728541E+09 0.54 706.82 01-SEP-08:62 0.57
October 0.765753E+09 0.54 706.82 01-OCT-08:62 0.57
November 0.645836E+09 0.53 706.82 01-NOV-08:62 0.57
December 0.552698E+09 0.51 706.82 01-DEC-09:02 0.57
           
Annual Sum or Average 0.719458E+10 0.52      
Minimum of Months 0.487281E+09 0.51 706.82   0.57
Maximum of Months 0.765753E+09 0.54 706.82   0.57



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 8598252.49 7738427.24 173.25 19-JAN-09:05 155.93 155.93 54.95 0.20
February 7638347.64 6874512.88 182.69 04-FEB-19:03 164.42 164.42 55.53 0.22
March 4549930.17 4094937.16 226.42 19-MAR-15:05 203.78 203.78 55.05 0.28
April 529475.04 476527.54 198.62 21-APR-08:05 178.75 178.75 49.89 0.24
May 244057.65 219651.89 171.92 26-MAY-08:05 154.73 154.73 54.85 0.20
June 182785.62 164507.05 106.69 12-JUN-08:07 96.02 96.02 53.98 0.12
July 190763.67 171687.30 109.68 21-JUL-08:07 98.71 98.71 54.42 0.12
August 223505.09 201154.58 184.82 28-AUG-08:05 166.34 166.34 54.28 0.22
September 154895.31 139405.78 125.55 15-SEP-08:05 113.00 113.00 55.43 0.14
October 593993.88 534594.50 207.74 18-OCT-08:05 186.97 186.97 51.50 0.26
November 1978034.71 1780231.23 201.67 29-NOV-09:05 181.50 181.50 55.36 0.25
December 8633202.47 7769882.22 184.69 28-DEC-16:04 166.22 166.22 62.54 0.22
                 
Annual Sum or Average 33517243.73 30165519.36            
Minimum of Months 154895.31 139405.78 106.69   96.02 96.02 49.89 0.12
Maximum of Months 8633202.47 7769882.22 226.42   203.78 203.78 62.54 0.28



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.658676E+09 0.592808E+09 1404.80 01-JAN-19:03 1264.32 1264.32 7.25 19.23
February 0.747471E+09 0.672724E+09 1669.86 11-FEB-19:03 1502.88 1502.88 7.23 20.71
March 0.983580E+09 0.885222E+09 1731.32 09-MAR-21:00 1558.19 1558.19 7.15 21.03
April 0.117833E+10 0.106050E+10 1461.41 13-APR-18:05 1315.27 1315.27 6.76 19.56
May 0.171603E+10 0.154443E+10 2024.98 24-MAY-18:03 1822.48 1822.48 7.23 22.47
June 0.209695E+10 0.188725E+10 2076.64 08-JUN-18:05 1868.97 1868.97 6.73 22.71
July 0.233208E+10 0.209887E+10 2382.97 27-JUL-18:03 2144.68 2144.68 6.73 24.06
August 0.226387E+10 0.203748E+10 2072.19 21-AUG-18:03 1864.97 1864.97 6.73 22.69
September 0.221892E+10 0.199702E+10 2331.13 18-SEP-18:03 2098.02 2098.02 6.73 23.84
October 0.191292E+10 0.172162E+10 1783.38 30-OCT-18:03 1605.04 1605.04 6.73 21.30
November 0.141404E+10 0.127263E+10 1995.69 21-NOV-20:50 1796.12 1796.12 7.22 22.33
December 0.932487E+09 0.839239E+09 1965.90 23-DEC-19:03 1769.31 1769.31 7.25 22.19
                 
Annual Sum or Average 0.184553E+11 0.166098E+11            
Minimum of Months 0.658676E+09 0.592808E+09 1404.80   1264.32 1264.32 6.73 19.23
Maximum of Months 0.233208E+10 0.209887E+10 2382.97   2144.68 2144.68 7.25 24.06



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.151099E+11 0.135989E+11 5662.32 01-JAN-00:10 5096.09 5096.09 9.47 39.69
February 0.134803E+11 0.121323E+11 5662.32 01-FEB-00:03 5096.09 5096.09 8.59 39.69
March 0.150768E+11 0.135691E+11 5662.32 01-MAR-00:03 5096.09 5096.09 8.73 39.69
April 0.146767E+11 0.132091E+11 5662.32 01-APR-00:10 5096.09 5096.09 8.94 39.69
May 0.151660E+11 0.136494E+11 5662.32 01-MAY-00:05 5096.09 5096.09 9.35 39.69
June 0.146767E+11 0.132091E+11 5662.32 01-JUN-00:05 5096.09 5096.09 9.43 39.69
July 0.151660E+11 0.136494E+11 5662.32 01-JUL-00:10 5096.09 5096.09 9.36 39.69
August 0.151660E+11 0.136494E+11 5662.32 01-AUG-00:05 5096.09 5096.09 9.78 39.69
September 0.146767E+11 0.132091E+11 5662.32 01-SEP-00:05 5096.09 5096.09 9.41 39.69
October 0.151660E+11 0.136494E+11 5662.32 01-OCT-00:10 5096.09 5096.09 9.35 39.69
November 0.146745E+11 0.132070E+11 5662.32 01-NOV-00:05 5096.09 5096.09 9.71 39.69
December 0.150555E+11 0.135500E+11 5662.32 01-DEC-00:03 5096.09 5096.09 9.28 39.69
                 
Annual Sum or Average 0.178091E+12 0.160282E+12            
Minimum of Months 0.134803E+11 0.121323E+11 5662.32   5096.09 5096.09 8.59 39.69
Maximum of Months 0.151660E+11 0.136494E+11 5662.32   5096.09 5096.09 9.78 39.69



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:10 14.37 14.37 51.59 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:03 14.37 14.37 51.85 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:03 14.37 14.37 52.00 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 53.56 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:05 14.37 14.37 54.18 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:05 14.37 14.37 54.21 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 54.91 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:05 14.37 14.37 54.64 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:05 14.37 14.37 54.01 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 54.14 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:05 14.37 14.37 53.98 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:03 14.37 14.37 52.03 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 51.59 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 54.91 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 60.40 60.40 247.56 20925.20 19-JAN-09:05
February 0.00 0.00 01-FEB-00:03 64.14 79.40 295.84 23516.82 23-FEB-19:05
March 0.00 0.00 01-MAR-00:03 51.68 51.68 144.55 29026.89 19-MAR-15:05
April 0.00 0.00 01-APR-00:10 54.98 54.98 25.94 29865.53 21-APR-08:05
May 0.00 0.00 01-MAY-00:05 53.55 53.55 10.62 22657.49 01-MAY-08:05
June 0.00 0.00 01-JUN-00:05 53.21 53.21 8.02 12519.64 12-JUN-08:07
July 0.00 0.00 01-JUL-00:10 54.74 54.74 8.04 12677.63 21-JUL-08:07
August 0.00 0.00 01-AUG-00:05 53.09 53.09 9.57 23233.95 28-AUG-08:05
September 0.00 0.00 01-SEP-00:05 54.19 54.19 6.37 14136.58 15-SEP-08:05
October 0.00 0.00 01-OCT-00:10 56.36 56.36 27.69 29836.36 18-OCT-08:05
November 0.00 0.00 01-NOV-00:05 53.76 53.76 70.87 24739.39 29-NOV-09:05
December 0.00 0.00 01-DEC-00:03 53.81 53.81 259.80 25376.47 06-DEC-09:05
                 
Annual Sum or Average 0.00         91.95    
Minimum of Months 0.00 0.00   51.68 51.68 6.37 12519.64  
Maximum of Months 0.00 0.00   64.14 79.40 295.84 29865.53  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 198884.53 602087.16 01-JAN-19:03 10.84 7.22 0.00 0.00 01-JAN-00:10
February 238348.94 635095.90 11-FEB-19:03 11.02 7.20 0.00 0.00 01-FEB-00:03
March 269647.72 629189.87 09-MAR-21:00 10.91 7.12 0.00 0.00 01-MAR-00:03
April 329665.05 610870.17 14-APR-18:05 10.37 6.70 0.00 0.00 01-APR-00:10
May 417926.50 726161.86 24-MAY-18:03 11.56 7.20 0.00 0.00 01-MAY-00:05
June 473336.96 704454.26 08-JUN-18:05 10.94 6.70 0.00 0.00 01-JUN-00:05
July 488330.10 728194.23 27-JUL-18:03 11.08 6.70 0.00 0.00 01-JUL-00:10
August 484811.15 696768.01 21-AUG-18:03 10.89 6.70 0.00 0.00 01-AUG-00:05
September 479984.98 735783.78 18-SEP-18:03 11.13 6.70 0.00 0.00 01-SEP-00:05
October 438218.00 679314.75 03-OCT-18:03 10.79 6.70 0.00 0.00 01-OCT-00:10
November 355206.73 681473.79 21-NOV-21:30 11.23 7.13 0.00 0.00 01-NOV-00:05
December 250891.65 721059.92 23-DEC-19:03 11.56 7.22 0.00 0.00 01-DEC-00:03
                 
Annual Sum or Average 369396.11         0.00    
Minimum of Months 198884.53 602087.16   10.37 6.70 0.00 0.00  
Maximum of Months 488330.10 735783.78   11.56 7.22 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 51.59 59.57 20264.86 40654.70 19-JAN-07:15
February 0.00 0.00 01-FEB-00:03 51.85 59.43 20086.29 40516.43 03-FEB-07:15
March 0.00 0.00 01-MAR-00:03 52.00 59.45 19531.37 39687.24 01-MAR-08:00
April 0.00 0.00 01-APR-00:10 53.56 58.38 18692.10 38061.90 03-APR-06:10
May 0.00 0.00 01-MAY-00:05 54.18 58.92 17836.35 36388.57 01-MAY-06:15
June 0.00 0.00 01-JUN-00:05 54.21 58.66 17184.86 34664.81 01-JUN-06:20
July 0.00 0.00 01-JUL-00:10 54.91 59.35 16893.71 33634.53 03-JUL-06:40
August 0.00 0.00 01-AUG-00:05 54.64 59.61 17092.84 34410.08 31-AUG-06:30
September 0.00 0.00 01-SEP-00:05 54.01 58.61 17671.22 35864.03 29-SEP-06:50
October 0.00 0.00 01-OCT-00:10 54.14 59.70 18497.10 37783.44 31-OCT-06:40
November 0.00 0.00 01-NOV-00:05 53.98 58.92 19354.86 39377.96 30-NOV-08:00
December 0.00 0.00 01-DEC-00:03 52.03 59.75 19998.76 40396.48 27-DEC-07:15
                 
Annual Sum or Average 0.00         18583.76    
Minimum of Months 0.00 0.00   51.59 58.38 16893.71 33634.53  
Maximum of Months 0.00 0.00   54.91 59.75 20264.86 40654.70  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.115456E+09 0.00 0.366951E+12 0.369580E+11 0.00 0.00
February 0.109718E+09 0.00 0.401368E+12 0.335976E+11 0.00 0.00
March 62246286.75 0.00 0.513478E+12 0.374031E+11 0.00 0.00
April 1385617.69 0.00 0.609081E+12 0.372295E+11 0.00 0.00
May 1114406.90 0.00 0.818786E+12 0.400984E+11 0.00 0.00
June 118207.10 0.00 0.902818E+12 0.402857E+11 0.00 0.00
July 0.00 0.00 0.961076E+12 0.422262E+11 0.00 0.00
August 115318.74 0.00 0.960372E+12 0.423097E+11 0.00 0.00
September 0.00 0.00 0.912906E+12 0.416779E+11 0.00 0.00
October 399433.24 0.00 0.855511E+12 0.420748E+11 0.00 0.00
November 29473602.55 0.00 0.665263E+12 0.387887E+11 0.00 0.00
December 0.126963E+09 0.00 0.478519E+12 0.377557E+11 0.00 0.00
             
Annual Sum or Average 0.446990E+09 0.00 0.844613E+13 0.470405E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.366951E+12 0.335976E+11 0.00 0.00
Maximum of Months 0.126963E+09 0.00 0.961076E+12 0.423097E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 8846.22 0.00 0.677718E+11 0.587890E+10 0.00 0.00
February 16572.22 0.00 0.730596E+11 0.530997E+10 0.00 0.00
March 46080.99 0.00 0.884565E+11 0.587890E+10 0.00 0.00
April 10685.13 0.00 0.104449E+12 0.568926E+10 0.00 0.00
May 10400.63 0.00 0.130143E+12 0.587890E+10 0.00 0.00
June 10554.82 0.00 0.140044E+12 0.568926E+10 0.00 0.00
July 6697.04 0.00 0.146006E+12 0.587890E+10 0.00 0.00
August 10193.91 0.00 0.147946E+12 0.587890E+10 0.00 0.00
September 6153.07 0.00 0.138211E+12 0.568926E+10 0.00 0.00
October 10045.73 0.00 0.132898E+12 0.587890E+10 0.00 0.00
November 14378.76 0.00 0.111112E+12 0.568926E+10 0.00 0.00
December 14980.82 0.00 0.838727E+11 0.587890E+10 0.00 0.00
             
Annual Sum or Average 165589.34 0.00 0.136397E+13 0.692193E+11 0.00 0.00
Minimum of Months 6153.07 0.00 0.677718E+11 0.530997E+10 0.00 0.00
Maximum of Months 46080.99 0.00 0.147946E+12 0.587890E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.369580E+11 0.366951E+12 0.115456E+09 0.106216E+11 0.298742E+11 0.00 0.00 0.00
February 0.335976E+11 0.401368E+12 0.109718E+09 0.136746E+11 0.301475E+11 0.00 0.00 0.00
March 0.374031E+11 0.513478E+12 62246286.75 0.106092E+11 0.565630E+11 0.00 0.00 0.00
April 0.372295E+11 0.609081E+12 1385617.69 0.486576E+09 0.936574E+11 0.00 0.00 0.00
May 0.400984E+11 0.818786E+12 1114406.90 0.173023E+09 0.259590E+12 0.00 0.00 0.00
June 0.402857E+11 0.902818E+12 118207.10 0.00 0.387685E+12 0.00 0.00 0.00
July 0.422262E+11 0.961076E+12 0.00 0.00 0.410487E+12 0.00 0.00 0.00
August 0.423097E+11 0.960372E+12 115318.74 0.00 0.421034E+12 0.00 0.00 0.00
September 0.416779E+11 0.912906E+12 0.00 0.00 0.366909E+12 0.00 0.00 0.00
October 0.420748E+11 0.855511E+12 399433.24 0.263169E+09 0.281172E+12 0.00 0.00 0.00
November 0.387887E+11 0.665263E+12 29473602.55 0.385269E+10 0.154107E+12 0.00 0.00 0.00
December 0.377557E+11 0.478519E+12 0.126963E+09 0.139573E+11 0.535612E+11 0.00 0.00 0.00
                 
Annual Sum or Average 0.470405E+12 0.844613E+13 0.446990E+09 0.536382E+11 0.254479E+13 0.00 0.00 0.00
Minimum of Months 0.335976E+11 0.366951E+12 0.00 0.00 0.298742E+11 0.00 0.00 0.00
Maximum of Months 0.423097E+11 0.961076E+12 0.126963E+09 0.139573E+11 0.421034E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.587890E+10 0.677718E+11 8846.22 0.213883E+10 0.138667E+11 0.00 0.00 0.00
February 0.530997E+10 0.730596E+11 16572.22 0.234738E+10 0.169047E+11 0.00 0.00 0.00
March 0.587890E+10 0.884565E+11 46080.99 0.192777E+10 0.300050E+11 0.00 0.00 0.00
April 0.568926E+10 0.104449E+12 10685.13 79156343.97 0.412983E+11 0.00 0.00 0.00
May 0.587890E+10 0.130143E+12 10400.63 0.00 0.819787E+11 0.00 0.00 0.00
June 0.568926E+10 0.140044E+12 10554.82 0.00 0.105506E+12 0.00 0.00 0.00
July 0.587890E+10 0.146006E+12 6697.04 0.00 0.112692E+12 0.00 0.00 0.00
August 0.587890E+10 0.147946E+12 10193.91 0.00 0.114050E+12 0.00 0.00 0.00
September 0.568926E+10 0.138211E+12 6153.07 0.00 0.104223E+12 0.00 0.00 0.00
October 0.587890E+10 0.132898E+12 10045.73 0.00 0.875100E+11 0.00 0.00 0.00
November 0.568926E+10 0.111112E+12 14378.76 0.585831E+09 0.517993E+11 0.00 0.00 0.00
December 0.587890E+10 0.838727E+11 14980.82 0.282090E+10 0.249907E+11 0.00 0.00 0.00
                 
Annual Sum or Average 0.692193E+11 0.136397E+13 165589.34 0.989986E+10 0.784825E+12 0.00 0.00 0.00
Minimum of Months 0.530997E+10 0.677718E+11 6153.07 0.00 0.138667E+11 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.147946E+12 46080.99 0.282090E+10 0.114050E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.369580E+11 0.115456E+09 0.366951E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.335976E+11 0.109718E+09 0.401368E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.374031E+11 62246286.75 0.513478E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.372295E+11 1385617.69 0.609081E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.400984E+11 1114406.90 0.818786E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.402857E+11 118207.10 0.902818E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.422262E+11 0.00 0.961076E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.423097E+11 115318.74 0.960372E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.416779E+11 0.00 0.912906E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.420748E+11 399433.24 0.855511E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.387887E+11 29473602.55 0.665263E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.377557E+11 0.126963E+09 0.478519E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.470405E+12 0.446990E+09 0.844613E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.335976E+11 0.00 0.366951E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.423097E+11 0.126963E+09 0.961076E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.587890E+10 8846.22 0.677718E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.530997E+10 16572.22 0.730596E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.587890E+10 46080.99 0.884565E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.568926E+10 10685.13 0.104449E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.587890E+10 10400.63 0.130143E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.568926E+10 10554.82 0.140044E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.587890E+10 6697.04 0.146006E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.587890E+10 10193.91 0.147946E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.568926E+10 6153.07 0.138211E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.587890E+10 10045.73 0.132898E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.568926E+10 14378.76 0.111112E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.587890E+10 14980.82 0.838727E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.692193E+11 165589.34 0.136397E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.530997E+10 6153.07 0.677718E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 46080.99 0.147946E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.687445E+09 0.564227E+10 0.00 45886821.82 0.659272E+09 0.00 0.242010E+11 0.00 1.05
February 0.166338E+10 0.398948E+10 0.00 20076042.33 0.313453E+10 0.00 0.139059E+11 0.00 1.01
March 0.808475E+10 0.375343E+10 0.00 5873430.71 0.825010E+10 0.00 0.578311E+10 0.00 0.99
April 0.344907E+10 0.210136E+10 0.00 1064943.27 0.114390E+11 0.00 0.742434E+09 0.00 0.98
May 25485080.64 0.820486E+10 0.00 93720.68 0.199916E+11 0.00 16861797.77 0.00 0.97
June 0.00 0.146839E+11 0.00 0.00 0.222848E+11 0.00 0.00 0.00 0.95
July 0.00 0.217093E+11 0.00 0.00 0.190356E+11 0.00 0.00 0.00 0.96
August 0.00 0.374933E+11 0.00 0.00 0.474967E+10 0.00 0.00 0.00 0.99
September 0.00 0.364625E+11 0.00 0.00 0.260079E+10 0.00 0.00 0.00 1.01
October 0.00 0.306825E+11 0.00 2108689.42 0.175817E+10 0.00 62129580.37 0.00 1.03
November 65349844.36 0.208535E+11 0.00 19603225.54 0.101798E+10 0.00 0.693774E+10 0.00 1.05
December 0.297620E+09 0.121266E+11 0.00 42783016.20 0.566999E+09 0.00 0.191917E+11 0.00 1.06
                   
Annual Sum or Average 0.142731E+11 0.197703E+12 0.00 0.137490E+09 0.954886E+11 0.00 0.708408E+11 0.00 1.00
Minimum of Months 0.00 0.210136E+10 0.00 0.00 0.566999E+09 0.00 0.00 0.00 0.95
Maximum of Months 0.808475E+10 0.374933E+11 0.00 45886821.82 0.222848E+11 0.00 0.242010E+11 0.00 1.06



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.193675E+10 0.520039E+09 0.00 1908636.45 0.200070E+09 0.00 0.634200E+09 0.00 2.08
February 0.124852E+10 0.551346E+09 0.00 1915396.82 0.257300E+09 0.00 0.395679E+09 0.00 2.06
March 0.119161E+10 0.963756E+09 0.00 1065746.73 0.375173E+09 0.00 0.292523E+09 0.00 1.98
April 0.321747E+09 0.117269E+10 0.00 352050.69 0.367021E+09 0.00 0.125987E+09 0.00 1.97
May 2194544.75 0.260529E+10 0.00 23018.15 0.501363E+09 0.00 2315287.51 0.00 1.93
June 0.00 0.388040E+10 0.00 0.00 0.255924E+09 0.00 0.00 0.00 1.93
July 0.00 0.455344E+10 0.00 0.00 0.129581E+09 0.00 0.00 0.00 1.98
August 0.00 0.434845E+10 0.00 0.00 0.397368E+09 0.00 0.00 0.00 1.99
September 0.00 0.440857E+10 0.00 0.00 0.183242E+09 0.00 0.00 0.00 2.11
October 787872.29 0.358088E+10 0.00 103920.39 0.240313E+09 0.00 5363393.57 0.00 2.18
November 0.510868E+09 0.227563E+10 0.00 712646.16 0.230378E+09 0.00 0.190794E+09 0.00 2.13
December 0.143593E+10 0.118094E+10 0.00 1301981.91 0.252576E+09 0.00 0.503905E+09 0.00 2.10
                   
Annual Sum or Average 0.664840E+10 0.300414E+11 0.00 7383397.30 0.339031E+10 0.00 0.215077E+10 0.00 2.04
Minimum of Months 0.00 0.520039E+09 0.00 0.00 0.129581E+09 0.00 0.00 0.00 1.93
Maximum of Months 0.193675E+10 0.455344E+10 0.00 1915396.82 0.501363E+09 0.00 0.634200E+09 0.00 2.18



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.133619E+10 0.269190E+09 0.00 879918.40 0.278017E+09 0.00 0.762949E+09 0.00 1.40
February 0.626965E+09 0.348243E+09 0.00 1017357.11 0.288247E+09 0.00 0.751951E+09 0.00 1.41
March 0.667146E+09 0.722265E+09 0.00 872374.10 0.382217E+09 0.00 0.581804E+09 0.00 1.41
April 59218828.46 0.853036E+09 0.00 859561.38 0.407847E+09 0.00 0.323241E+09 0.00 1.42
May 80985.43 0.190096E+10 0.00 80034.03 0.733997E+09 0.00 3708412.87 0.00 1.42
June 0.00 0.277731E+10 0.00 0.00 0.717242E+09 0.00 0.00 0.00 1.41
July 0.00 0.340866E+10 0.00 0.00 0.435740E+09 0.00 0.00 0.00 1.43
August 0.00 0.315673E+10 0.00 0.00 0.695580E+09 0.00 0.00 0.00 1.42
September 0.00 0.309459E+10 0.00 0.00 0.407210E+09 0.00 0.00 0.00 1.42
October 61222.44 0.239338E+10 0.00 149991.29 0.436234E+09 0.00 5074498.21 0.00 1.41
November 0.293182E+09 0.146550E+10 0.00 378757.87 0.409301E+09 0.00 0.276893E+09 0.00 1.40
December 0.956644E+09 0.748682E+09 0.00 807557.75 0.337156E+09 0.00 0.636079E+09 0.00 1.40
                   
Annual Sum or Average 0.393949E+10 0.211385E+11 0.00 5045551.93 0.552879E+10 0.00 0.334170E+10 0.00 1.41
Minimum of Months 0.00 0.269190E+09 0.00 0.00 0.278017E+09 0.00 0.00 0.00 1.40
Maximum of Months 0.133619E+10 0.340866E+10 0.00 1017357.11 0.733997E+09 0.00 0.762949E+09 0.00 1.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.215200E+10 28942105.40 0.00 1621.64 0.523651E+09 0.00 2856406.25 0.00 0.68
February 0.139996E+10 67042594.01 0.00 1331.08 0.574143E+09 0.00 182785.35 0.00 0.67
March 0.124439E+10 0.140413E+09 0.00 43364.94 0.962267E+09 0.00 27725531.01 0.00 0.67
April 0.351671E+09 0.228597E+09 0.00 55899.12 0.102111E+10 0.00 33817023.01 0.00 0.67
May 2755931.02 0.111974E+10 0.00 12098.98 0.152822E+10 0.00 1134081.85 0.00 0.67
June 0.00 0.278912E+10 0.00 0.00 0.781785E+09 0.00 0.00 0.00 0.68
July 0.00 0.353606E+10 0.00 0.00 0.398828E+09 0.00 0.00 0.00 0.69
August 0.00 0.252691E+10 0.00 0.00 0.134944E+10 0.00 0.00 0.00 0.67
September 0.00 0.257509E+10 0.00 0.00 0.944360E+09 0.00 0.00 0.00 0.67
October 3513406.75 0.108683E+10 0.00 21158.26 0.172906E+10 0.00 1816345.53 0.00 0.66
November 0.580490E+09 0.438880E+09 0.00 3072.61 0.142217E+10 0.00 4398629.77 0.00 0.66
December 0.160697E+10 0.124953E+09 0.00 22359.54 0.961433E+09 0.00 20762957.53 0.00 0.67
                   
Annual Sum or Average 0.734174E+10 0.146626E+11 0.00 160906.17 0.121965E+11 0.00 92693760.29 0.00 0.67
Minimum of Months 0.00 28942105.40 0.00 0.00 0.398828E+09 0.00 0.00 0.00 0.66
Maximum of Months 0.215200E+10 0.353606E+10 0.00 55899.12 0.172906E+10 0.00 33817023.01 0.00 0.69



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.104376E+10 0.00 0.00 0.00 0.267664E+09 0.00 0.00 0.00 0.57
February 0.678198E+09 0.00 0.00 0.00 0.310576E+09 0.00 0.00 0.00 0.57
March 0.616204E+09 0.00 0.00 0.00 0.534113E+09 0.00 0.00 0.00 0.56
April 0.185295E+09 25981548.87 0.00 2386.15 0.576854E+09 0.00 1361163.77 0.00 0.56
May 1844938.91 0.268078E+09 0.00 399.07 0.987801E+09 0.00 44173.00 0.00 0.55
June 0.00 0.996870E+09 0.00 0.00 0.664568E+09 0.00 0.00 0.00 0.55
July 0.00 0.147827E+10 0.00 0.00 0.348987E+09 0.00 0.00 0.00 0.55
August 0.00 0.887571E+09 0.00 0.00 0.934628E+09 0.00 0.00 0.00 0.55
September 0.00 0.918415E+09 0.00 0.00 0.727949E+09 0.00 0.00 0.00 0.55
October 2519933.37 0.252780E+09 0.00 2270.13 0.109177E+10 0.00 63747.55 0.00 0.55
November 0.283308E+09 57609988.47 0.00 0.00 0.838815E+09 0.00 0.00 0.00 0.55
December 0.788447E+09 2435183.50 0.00 0.00 0.523429E+09 0.00 0.00 0.00 0.56
                   
Annual Sum or Average 0.359958E+10 0.488801E+10 0.00 5055.36 0.780716E+10 0.00 1469084.32 0.00 0.56
Minimum of Months 0.00 0.00 0.00 0.00 0.267664E+09 0.00 0.00 0.00 0.55
Maximum of Months 0.104376E+10 0.147827E+10 0.00 2386.15 0.109177E+10 0.00 1361163.77 0.00 0.57



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.104102E+09 0.820260E+10 0.00 62165390.91 18647600.40 0.00 0.314015E+11 0.00 20.79
February 65789789.19 0.957637E+10 0.00 49063954.26 9109453.03 0.00 0.203869E+11 0.00 20.70
March 48472671.66 0.164133E+11 0.00 42964203.88 18927260.72 0.00 0.185851E+11 0.00 20.70
April 165334.67 0.182860E+11 0.00 20281480.43 24086570.19 0.00 0.553919E+10 0.00 20.44
May 0.00 0.380163E+11 0.00 889057.02 58350223.58 0.00 50513805.21 0.00 20.19
June 0.00 0.500897E+11 0.00 0.00 56332023.85 0.00 0.00 0.00 19.90
July 0.00 0.540021E+11 0.00 0.00 84175793.17 0.00 0.00 0.00 19.71
August 0.00 0.546565E+11 0.00 0.00 65197592.79 0.00 0.00 0.00 19.81
September 0.00 0.495862E+11 0.00 0.00 70276962.26 0.00 0.00 0.00 19.70
October 0.00 0.404787E+11 0.00 1873547.63 70823399.58 0.00 71889515.14 0.00 19.89
November 13588355.61 0.275416E+11 0.00 22040678.37 32659746.30 0.00 0.842860E+10 0.00 20.22
December 50197493.98 0.160548E+11 0.00 48434356.20 45885015.45 0.00 0.240400E+11 0.00 20.58
                   
Annual Sum or Average 0.282316E+09 0.382904E+12 0.00 0.247713E+09 0.554472E+09 0.00 0.108504E+12 0.00 20.22
Minimum of Months 0.00 0.820260E+10 0.00 0.00 9109453.03 0.00 0.00 0.00 19.70
Maximum of Months 0.104102E+09 0.546565E+11 0.00 62165390.91 84175793.17 0.00 0.314015E+11 0.00 20.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.922427E+09 0.304566E+10 0.00 23443106.71 0.165910E+09 0.00 0.107079E+11 0.00 3.34
February 0.541759E+09 0.344370E+10 0.00 19792729.98 0.183791E+09 0.00 0.704071E+10 0.00 3.32
March 0.117822E+10 0.589348E+10 0.00 14347215.57 0.321660E+09 0.00 0.559078E+10 0.00 3.25
April 0.161312E+09 0.654566E+10 0.00 7528456.57 0.397275E+09 0.00 0.196700E+10 0.00 3.24
May 0.00 0.136027E+11 0.00 689604.81 0.808665E+09 0.00 24346874.75 0.00 3.24
June 0.00 0.184452E+11 0.00 0.00 0.905026E+09 0.00 0.00 0.00 3.27
July 0.00 0.205486E+11 0.00 0.00 0.585323E+09 0.00 0.00 0.00 3.27
August 0.00 0.206034E+11 0.00 0.00 0.901070E+09 0.00 0.00 0.00 3.31
September 0.00 0.199267E+11 0.00 0.00 0.277131E+09 0.00 0.00 0.00 3.40
October 204448.54 0.166007E+11 0.00 1003657.50 0.242645E+09 0.00 32160022.65 0.00 3.49
November 0.233870E+09 0.108909E+11 0.00 8433421.33 0.231301E+09 0.00 0.292922E+10 0.00 3.42
December 0.805573E+09 0.636067E+10 0.00 17308485.19 0.114707E+09 0.00 0.796393E+10 0.00 3.34
                   
Annual Sum or Average 0.384337E+10 0.145907E+12 0.00 92546677.66 0.513450E+10 0.00 0.362561E+11 0.00 3.32
Minimum of Months 0.00 0.304566E+10 0.00 0.00 0.114707E+09 0.00 0.00 0.00 3.24
Maximum of Months 0.117822E+10 0.206034E+11 0.00 23443106.71 0.905026E+09 0.00 0.107079E+11 0.00 3.49



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.587682E+10 0.878051E+10 0.00 57401221.59 0.174233E+10 0.00 0.339983E+11 0.00 1.60
February 0.332226E+10 0.100476E+11 0.00 50316577.11 0.217545E+10 0.00 0.231040E+11 0.00 1.61
March 0.551314E+10 0.180572E+11 0.00 37520627.27 0.335532E+10 0.00 0.181953E+11 0.00 1.61
April 0.523333E+09 0.196410E+11 0.00 26138011.73 0.440126E+10 0.00 0.702009E+10 0.00 1.63
May 0.00 0.431287E+11 0.00 2384245.85 0.766124E+10 0.00 83510607.73 0.00 1.65
June 0.00 0.611871E+11 0.00 0.00 0.684928E+10 0.00 0.00 0.00 1.66
July 0.00 0.691476E+11 0.00 0.00 0.504949E+10 0.00 0.00 0.00 1.66
August 0.00 0.676311E+11 0.00 0.00 0.694193E+10 0.00 0.00 0.00 1.65
September 0.00 0.647773E+11 0.00 0.00 0.346604E+10 0.00 0.00 0.00 1.66
October 441252.20 0.523028E+11 0.00 3458812.12 0.320698E+10 0.00 0.111715E+09 0.00 1.66
November 0.967685E+09 0.343663E+11 0.00 23411527.86 0.237710E+10 0.00 0.994975E+10 0.00 1.63
December 0.427631E+10 0.197572E+11 0.00 47378786.09 0.152004E+10 0.00 0.261991E+11 0.00 1.61
                   
Annual Sum or Average 0.204800E+11 0.468825E+12 0.00 0.248010E+09 0.487465E+11 0.00 0.118662E+12 0.00 1.64
Minimum of Months 0.00 0.878051E+10 0.00 0.00 0.152004E+10 0.00 0.00 0.00 1.60
Maximum of Months 0.587682E+10 0.691476E+11 0.00 57401221.59 0.766124E+10 0.00 0.339983E+11 0.00 1.66



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 94412827.79 0.426280E+09 650410.46 4906153.50 50562440.06 11334918.95 0.533699E+09 26979.96 0.47
February 43639342.43 0.418351E+09 417742.04 3866987.41 49843210.34 34972891.89 0.292108E+09 20401.44 0.47
March 63735875.24 0.622075E+09 399585.79 3193269.58 49648073.13 10239639.72 0.283197E+09 24133.73 0.47
April 4974043.57 0.839421E+09 574227.32 1217525.29 52559878.56 40080.00 49370887.40 32996.85 0.47
May 0.00 0.146154E+10 743395.46 0.00 83623129.42 0.00 0.00 20088.68 0.47
June 0.00 0.183570E+10 573796.08 0.00 93398795.34 0.00 0.00 9267.15 0.47
July 0.00 0.196417E+10 130536.52 0.00 87867135.17 0.00 0.00 689.74 0.47
August 0.00 0.199523E+10 583116.45 0.00 0.103528E+09 0.00 0.00 10817.02 0.47
September 0.00 0.181865E+10 677278.33 0.00 89443696.35 0.00 0.00 11669.51 0.47
October 0.00 0.157525E+10 627954.46 0.00 82189032.58 0.00 0.00 17042.01 0.48
November 16547747.75 0.115526E+10 642851.68 1391195.38 80131273.83 4328320.52 0.129068E+09 17404.56 0.47
December 63940848.14 0.628588E+09 527736.39 3397072.41 54763728.72 22689901.80 0.356837E+09 20156.98 0.47
                   
Annual Sum or Average 0.287251E+09 0.147405E+11 6548630.99 17972203.58 0.877559E+09 83605752.87 0.164428E+10 211647.62 0.47
Minimum of Months 0.00 0.418351E+09 130536.52 0.00 49648073.13 0.00 0.00 689.74 0.47
Maximum of Months 94412827.79 0.199523E+10 743395.46 4906153.50 0.103528E+09 34972891.89 0.533699E+09 32996.85 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.122319E+09 0.395916E+09 854027.98 2874720.18 80659275.38 46185255.32 0.472898E+09 35339.18 0.47
February 51355175.03 0.403175E+09 591953.50 2676289.03 64784425.05 50182861.04 0.270329E+09 25878.30 0.47
March 69988014.06 0.608087E+09 613199.66 2479540.26 63334901.36 26164450.91 0.261692E+09 32603.78 0.47
April 5645065.80 0.832997E+09 623696.08 1133175.58 58823655.41 40075.30 48777704.93 38411.73 0.47
May 0.00 0.146187E+10 811101.42 0.00 83040195.96 0.00 0.00 20589.91 0.47
June 0.00 0.183949E+10 514868.68 0.00 89449604.69 0.00 0.00 5467.48 0.47
July 0.00 0.196737E+10 80795.29 0.00 84482790.98 0.00 0.00 452.15 0.47
August 0.00 0.199123E+10 755890.82 0.00 0.107111E+09 0.00 0.00 13202.26 0.47
September 0.00 0.180512E+10 964765.87 0.00 0.102454E+09 0.00 0.00 18061.35 0.47
October 0.00 0.154504E+10 1672234.90 0.00 0.111124E+09 0.00 0.00 46916.06 0.48
November 18874507.18 0.111925E+10 1430872.60 956594.40 0.115191E+09 7851773.95 0.123635E+09 40130.32 0.47
December 86510958.65 0.599890E+09 870036.86 2058353.29 83020432.50 68478745.79 0.289765E+09 38634.98 0.47
                   
Annual Sum or Average 0.354693E+09 0.145694E+11 9783443.67 12178672.74 0.104348E+10 0.198903E+09 0.146710E+10 315687.50 0.47
Minimum of Months 0.00 0.395916E+09 80795.29 0.00 58823655.41 0.00 0.00 452.15 0.47
Maximum of Months 0.122319E+09 0.199123E+10 1672234.90 2874720.18 0.115191E+09 68478745.79 0.472898E+09 46916.06 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.284891E+10 0.621768E+10 0.00 39271893.30 0.257064E+09 0.00 0.584866E+10 0.00 0.54
February 0.189855E+10 0.587161E+10 0.00 25970882.18 0.482625E+09 0.00 0.315455E+10 0.00 0.54
March 0.276068E+10 0.893920E+10 0.00 13125224.44 0.174508E+09 0.00 0.211243E+10 0.00 0.54
April 0.319421E+09 0.118520E+11 0.00 4254882.19 0.250690E+09 0.00 0.430245E+09 0.00 0.54
May 0.00 0.207894E+11 0.00 0.00 0.171982E+09 0.00 0.00 0.00 0.54
June 0.00 0.261648E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.54
July 0.00 0.278256E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.54
August 0.00 0.284509E+11 0.00 0.00 14491037.62 0.00 0.00 0.00 0.54
September 0.00 0.258814E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.54
October 0.00 0.224672E+11 0.00 0.00 14845686.59 0.00 0.00 0.00 0.54
November 0.801268E+09 0.165394E+11 0.00 9997409.83 0.220375E+09 0.00 0.124071E+10 0.00 0.54
December 0.214773E+10 0.888491E+10 0.00 25291869.10 0.388150E+09 0.00 0.388607E+10 0.00 0.54
                   
Annual Sum or Average 0.107766E+11 0.209884E+12 0.00 0.117912E+09 0.197473E+10 0.00 0.166727E+11 0.00 0.54
Minimum of Months 0.00 0.587161E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.54
Maximum of Months 0.284891E+10 0.284509E+11 0.00 39271893.30 0.482625E+09 0.00 0.584866E+10 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.176740E+10 0.453007E+10 6703770.96 28919375.68 0.193960E+10 22328907.30 0.692059E+10 132348.16 0.54
February 0.738501E+09 0.432268E+10 5249377.85 24635894.05 0.202792E+10 26550897.23 0.429077E+10 126690.64 0.54
March 0.997606E+09 0.652725E+10 10488793.38 20482694.85 0.257830E+10 10873145.29 0.385861E+10 153595.61 0.54
April 0.101842E+09 0.903141E+10 8479092.58 8793381.79 0.306593E+10 543597.45 0.642948E+09 184843.58 0.54
May 0.00 0.169893E+11 9099432.46 0.00 0.396864E+10 0.00 0.00 53134.54 0.54
June 0.00 0.224563E+11 8727258.53 0.00 0.370689E+10 0.00 0.00 39022.29 0.54
July 0.00 0.243688E+11 16322440.52 0.00 0.344801E+10 0.00 0.00 68321.18 0.54
August 0.00 0.238074E+11 14069919.62 0.00 0.465159E+10 0.00 0.00 42565.59 0.54
September 0.00 0.214917E+11 3019569.90 0.00 0.439367E+10 0.00 0.00 7973.80 0.54
October 0.00 0.170909E+11 30268078.37 0.00 0.536677E+10 0.00 0.00 246852.34 0.54
November 0.311608E+09 0.121460E+11 19605118.94 10258411.62 0.459855E+10 2675233.10 0.172800E+10 226324.49 0.54
December 0.124568E+10 0.654832E+10 8903297.44 22790062.68 0.271824E+10 12403184.23 0.477988E+10 128086.44 0.54
                   
Annual Sum or Average 0.516263E+10 0.169310E+12 0.140936E+09 0.115880E+09 0.424641E+11 75374964.59 0.222208E+11 1409758.65 0.54
Minimum of Months 0.00 0.432268E+10 3019569.90 0.00 0.193960E+10 0.00 0.00 7973.80 0.54
Maximum of Months 0.176740E+10 0.243688E+11 30268078.37 28919375.68 0.536677E+10 26550897.23 0.692059E+10 246852.34 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 72904048.02 0.436720E+09 123914.24 5270292.08 40667979.83 18012706.46 0.548165E+09 7899.44 0.47
February 40457742.48 0.427880E+09 185273.37 4381499.93 40563730.97 35054811.56 0.294694E+09 3560.80 0.47
March 36389460.51 0.635871E+09 78147.73 3509157.40 36194688.79 10500329.84 0.309967E+09 2902.40 0.47
April 2932999.76 0.859314E+09 16230.75 1347844.47 33255116.45 0.00 51321692.03 2533.29 0.47
May 0.00 0.148728E+10 107581.45 0.00 58542515.10 0.00 0.00 597.15 0.47
June 0.00 0.187472E+10 0.00 0.00 54969604.99 0.00 0.00 0.00 0.47
July 0.00 0.199890E+10 0.00 0.00 53275999.68 0.00 0.00 0.00 0.47
August 0.00 0.202626E+10 44032.04 0.00 73050402.02 0.00 0.00 2011.28 0.47
September 0.00 0.185445E+10 0.00 0.00 54328280.53 0.00 0.00 0.00 0.47
October 0.00 0.160197E+10 17452.46 0.00 56090348.36 0.00 0.00 933.42 0.48
November 13903127.57 0.117005E+10 245152.60 1577315.17 65754169.60 2378334.42 0.133477E+09 5502.95 0.47
December 59514881.96 0.634172E+09 215852.39 3280239.91 49503357.67 32801599.43 0.351269E+09 8386.07 0.47
                   
Annual Sum or Average 0.226102E+09 0.150076E+11 1033637.01 19366348.95 0.616196E+09 98747781.70 0.168889E+10 34326.81 0.47
Minimum of Months 0.00 0.427880E+09 0.00 0.00 33255116.45 0.00 0.00 0.00 0.47
Maximum of Months 72904048.02 0.202626E+10 245152.60 5270292.08 73050402.02 35054811.56 0.548165E+09 8386.07 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.130283E+09 0.410176E+09 492131.61 2968787.38 66771970.41 53242570.22 0.457782E+09 23948.10 0.47
February 46376976.21 0.415701E+09 352939.48 3089777.11 52513215.97 45719927.16 0.279357E+09 10365.22 0.47
March 67505558.02 0.626325E+09 141981.84 2632250.42 45593850.28 15266897.27 0.274919E+09 6825.48 0.47
April 2987386.78 0.856674E+09 16070.33 1260588.72 35790352.79 0.00 51348046.10 2691.51 0.47
May 0.00 0.148799E+10 107226.72 0.00 57651684.76 0.00 0.00 939.21 0.47
June 0.00 0.187729E+10 0.00 0.00 52174480.32 0.00 0.00 0.00 0.47
July 0.00 0.200047E+10 0.00 0.00 51461400.29 0.00 0.00 0.00 0.47
August 0.00 0.202378E+10 43906.52 0.00 75283977.43 0.00 0.00 2131.40 0.47
September 0.00 0.184664E+10 0.00 0.00 61919902.93 0.00 0.00 0.00 0.47
October 0.00 0.158377E+10 51524.10 0.00 74057379.97 0.00 0.00 2148.21 0.48
November 18660827.78 0.114192E+10 475674.63 1096365.40 93496668.91 10449406.13 0.121111E+09 13021.85 0.47
December 91667452.60 0.598341E+09 549112.69 1858343.10 84910114.57 77637109.23 0.275650E+09 19655.94 0.47
                   
Annual Sum or Average 0.357482E+09 0.148691E+11 2230567.93 12906112.13 0.751625E+09 0.202316E+09 0.146017E+10 81726.92 0.47
Minimum of Months 0.00 0.410176E+09 0.00 0.00 35790352.79 0.00 0.00 0.00 0.47
Maximum of Months 0.130283E+09 0.202378E+10 549112.69 3089777.11 93496668.91 77637109.23 0.457782E+09 23948.10 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.117713E+11 96036153.73 0.00 0.00 0.292261E+10 0.00 0.00 0.00 0.51
February 0.764856E+10 33100945.00 0.00 0.00 0.346950E+10 0.00 0.00 0.00 0.51
March 0.691566E+10 0.243775E+09 0.00 85364.56 0.577983E+10 0.00 33655884.17 0.00 0.50
April 0.184410E+10 0.169781E+10 0.00 379154.32 0.512076E+10 0.00 0.261798E+09 0.00 0.50
May 11878672.53 0.610498E+10 0.00 66426.99 0.816364E+10 0.00 9364364.61 0.00 0.50
June 0.00 0.144461E+11 0.00 0.00 0.462052E+10 0.00 0.00 0.00 0.50
July 0.00 0.182388E+11 0.00 0.00 0.276784E+10 0.00 0.00 0.00 0.50
August 0.00 0.153887E+11 0.00 0.00 0.564250E+10 0.00 0.00 0.00 0.50
September 0.00 0.158677E+11 0.00 0.00 0.334782E+10 0.00 0.00 0.00 0.50
October 4970733.55 0.118702E+11 0.00 390263.57 0.360458E+10 0.00 23977146.45 0.00 0.50
November 0.313432E+10 0.443312E+10 0.00 48364.03 0.574058E+10 0.00 60717103.53 0.00 0.50
December 0.872576E+10 0.139316E+10 0.00 136790.10 0.454158E+10 0.00 0.166022E+09 0.00 0.50
                   
Annual Sum or Average 0.400566E+11 0.898135E+11 0.00 1106363.57 0.557218E+11 0.00 0.555534E+09 0.00 0.50
Minimum of Months 0.00 33100945.00 0.00 0.00 0.276784E+10 0.00 0.00 0.00 0.50
Maximum of Months 0.117713E+11 0.182388E+11 0.00 390263.57 0.816364E+10 0.00 0.261798E+09 0.00 0.51



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 25001751.46 0.105530E+09 177776.61 954834.07 13665078.90 26267015.24 0.108865E+09 6790.14 0.47
February 11114038.69 0.104344E+09 107394.72 788893.09 12700848.23 17174671.15 64569299.18 5468.38 0.47
March 16491750.33 0.154650E+09 135636.83 661555.13 13244195.37 14354596.89 58583610.49 6878.43 0.47
April 1249655.60 0.208953E+09 185537.88 265910.25 13999568.76 17267.45 12367800.77 9139.02 0.47
May 0.00 0.363635E+09 325796.52 0.00 22511760.85 0.00 0.00 9221.08 0.47
June 0.00 0.457730E+09 243811.81 0.00 24441358.82 0.00 0.00 6290.56 0.47
July 0.00 0.490802E+09 107275.23 0.00 22132082.52 0.00 0.00 2047.76 0.47
August 0.00 0.495612E+09 226392.79 0.00 28993065.85 0.00 0.00 6722.38 0.47
September 0.00 0.453758E+09 276478.98 0.00 23154799.68 0.00 0.00 6037.48 0.47
October 0.00 0.390862E+09 427304.92 0.00 23220004.94 0.00 0.00 10977.41 0.48
November 4218272.95 0.286406E+09 265204.41 266259.35 22336620.19 7973156.78 25376245.48 5722.96 0.47
December 16944778.27 0.156170E+09 129520.32 619990.29 14667847.61 23533411.55 70618140.68 7383.11 0.47
                   
Annual Sum or Average 75020247.30 0.366845E+10 2608131.00 3557442.18 0.235067E+09 89320119.06 0.340380E+09 82678.71 0.47
Minimum of Months 0.00 0.104344E+09 107275.23 0.00 12700848.23 0.00 0.00 2047.76 0.47
Maximum of Months 25001751.46 0.495612E+09 427304.92 954834.07 28993065.85 26267015.24 0.108865E+09 10977.41 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 31234052.82 98225971.92 235501.60 482120.90 20894500.80 58293088.10 71059982.03 10069.68 0.47
February 12914586.28 0.100315E+09 135785.80 498813.46 16686928.69 25894434.33 54328095.93 6646.46 0.47
March 17722432.13 0.151805E+09 170060.45 487823.23 16032928.70 21683260.77 50187441.17 9209.94 0.47
April 1403175.58 0.207630E+09 203258.09 244579.08 15278351.22 21870.10 12229380.64 9309.35 0.47
May 0.00 0.364122E+09 296215.91 0.00 22009577.63 0.00 0.00 8951.65 0.47
June 0.00 0.459323E+09 212419.30 0.00 22823369.17 0.00 0.00 5660.54 0.47
July 0.00 0.491968E+09 87275.25 0.00 20926895.04 0.00 0.00 1207.87 0.47
August 0.00 0.494747E+09 287306.54 0.00 29735283.29 0.00 0.00 7054.36 0.47
September 0.00 0.449727E+09 371583.57 0.00 27033900.20 0.00 0.00 6887.17 0.47
October 0.00 0.384164E+09 488958.87 0.00 29805239.10 0.00 0.00 13585.28 0.48
November 4800817.91 0.277648E+09 460887.77 165676.90 30854535.60 11718462.23 21144544.72 13626.44 0.47
December 21901935.96 0.149322E+09 244260.88 320247.25 21378933.54 42454943.76 47026104.61 9903.82 0.47
                   
Annual Sum or Average 89977000.67 0.362900E+10 3193514.02 2199260.84 0.273460E+09 0.160066E+09 0.255976E+09 102112.55 0.47
Minimum of Months 0.00 98225971.92 87275.25 0.00 15278351.22 0.00 0.00 1207.87 0.47
Maximum of Months 31234052.82 0.494747E+09 488958.87 498813.46 30854535.60 58293088.10 71059982.03 13626.44 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.107084E+09 0.706807E+09 91940.34 11234616.49 60056749.83 1287497.58 0.915302E+09 443.44 0.54
February 54804349.13 0.691115E+09 339614.17 7208238.63 61224722.95 28943609.59 0.510677E+09 2434.60 0.54
March 80577620.05 0.996416E+09 343983.50 4766756.40 82781680.15 13498258.81 0.479949E+09 8688.31 0.54
April 8743246.23 0.132797E+10 474202.84 1417479.26 0.105142E+09 64373.38 79079376.52 22417.97 0.54
May 0.00 0.229164E+10 452254.71 0.00 0.190848E+09 0.00 0.00 5398.47 0.54
June 0.00 0.289542E+10 0.00 0.00 0.203889E+09 0.00 0.00 0.00 0.54
July 0.00 0.310214E+10 0.00 0.00 0.193902E+09 0.00 0.00 0.00 0.54
August 0.00 0.313525E+10 332756.17 0.00 0.236229E+09 0.00 0.00 4307.40 0.54
September 0.00 0.291010E+10 102077.95 0.00 0.155539E+09 0.00 0.00 44.82 0.54
October 0.00 0.253823E+10 0.00 0.00 0.124847E+09 0.00 0.00 0.00 0.54
November 23467490.68 0.187945E+10 244383.30 2792440.74 0.105555E+09 56701.39 0.216747E+09 2360.94 0.54
December 69175671.79 0.103453E+10 34803.63 7714792.79 63861451.19 948726.96 0.639881E+09 815.05 0.54
                   
Annual Sum or Average 0.343853E+09 0.235091E+11 2416016.61 35134324.31 0.158388E+10 44799167.71 0.284164E+10 46911.00 0.54
Minimum of Months 0.00 0.691115E+09 0.00 0.00 60056749.83 0.00 0.00 0.00 0.54
Maximum of Months 0.107084E+09 0.313525E+10 474202.84 11234616.49 0.236229E+09 28943609.59 0.915302E+09 22417.97 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.394991E+09 0.553837E+10 0.00 46232795.75 20112028.22 0.00 0.212821E+11 0.00 4.38
February 0.143628E+09 0.652501E+10 0.00 39438731.74 15060820.97 0.00 0.143311E+11 0.00 4.44
March 0.337471E+09 0.116875E+11 0.00 33879828.78 8113557.64 0.00 0.128499E+11 0.00 4.52
April 3271504.75 0.131861E+11 0.00 19897985.83 2089462.43 0.00 0.432897E+10 0.00 4.62
May 0.00 0.281578E+11 0.00 1408803.49 0.00 0.00 49406496.63 0.00 4.72
June 0.00 0.377899E+11 0.00 0.00 0.00 0.00 0.00 0.00 4.75
July 0.00 0.411043E+11 0.00 0.00 0.00 0.00 0.00 0.00 4.73
August 0.00 0.409839E+11 0.00 0.00 0.00 0.00 0.00 0.00 4.69
September 0.00 0.369602E+11 0.00 0.00 0.00 0.00 0.00 0.00 4.64
October 0.00 0.297390E+11 0.00 2034860.28 2618758.51 0.00 61985034.32 0.00 4.57
November 33453093.52 0.194979E+11 0.00 17741555.23 16981599.75 0.00 0.598126E+10 0.00 4.49
December 0.352001E+09 0.113495E+11 0.00 37028743.93 13033187.43 0.00 0.161649E+11 0.00 4.40
                   
Annual Sum or Average 0.126482E+10 0.282520E+12 0.00 0.197663E+09 78009414.96 0.00 0.750496E+11 0.00 4.58
Minimum of Months 0.00 0.553837E+10 0.00 0.00 0.00 0.00 0.00 0.00 4.38
Maximum of Months 0.394991E+09 0.411043E+11 0.00 46232795.75 20112028.22 0.00 0.212821E+11 0.00 4.75



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.179913E+09 0.593348E+10 0.00 53709458.10 2329505.45 0.00 0.230994E+11 0.00 4.69
February 14561947.14 0.698819E+10 0.00 45071604.66 0.00 0.00 0.154919E+11 0.00 4.75
March 0.191263E+09 0.124685E+11 0.00 38641516.79 0.00 0.00 0.139231E+11 0.00 4.83
April 0.00 0.140186E+11 0.00 21519271.72 0.00 0.00 0.459253E+10 0.00 4.91
May 0.00 0.298832E+11 0.00 1480387.05 0.00 0.00 51889790.28 0.00 5.00
June 0.00 0.400099E+11 0.00 0.00 0.00 0.00 0.00 0.00 5.02
July 0.00 0.435218E+11 0.00 0.00 0.00 0.00 0.00 0.00 5.00
August 0.00 0.433977E+11 0.00 0.00 0.00 0.00 0.00 0.00 4.95
September 0.00 0.391180E+11 0.00 0.00 0.00 0.00 0.00 0.00 4.90
October 0.00 0.314830E+11 0.00 2162336.75 0.00 0.00 64941056.91 0.00 4.83
November 10366291.34 0.207216E+11 0.00 20173569.15 0.00 0.00 0.642185E+10 0.00 4.77
December 0.135494E+09 0.121133E+11 0.00 42560424.77 1300730.16 0.00 0.175661E+11 0.00 4.70
                   
Annual Sum or Average 0.531598E+09 0.299657E+12 0.00 0.225319E+09 3630235.61 0.00 0.812118E+11 0.00 4.86
Minimum of Months 0.00 0.593348E+10 0.00 0.00 0.00 0.00 0.00 0.00 4.69
Maximum of Months 0.191263E+09 0.435218E+11 0.00 53709458.10 2329505.45 0.00 0.230994E+11 0.00 5.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.830796E+10 0.00 76998303.45 0.00 0.00 0.273462E+11 0.00 19.37
February 0.00 0.951821E+10 0.00 60933664.79 0.00 0.00 0.172042E+11 0.00 19.39
March 0.00 0.158192E+11 0.00 54034315.38 0.00 0.00 0.160473E+11 0.00 19.46
April 0.00 0.183808E+11 0.00 23746195.83 0.00 0.00 0.456421E+10 0.00 19.45
May 0.00 0.380861E+11 0.00 1079834.50 0.00 0.00 37869117.18 0.00 19.37
June 0.00 0.501328E+11 0.00 0.00 0.00 0.00 0.00 0.00 19.21
July 0.00 0.547828E+11 0.00 0.00 0.00 0.00 0.00 0.00 19.08
August 0.00 0.550305E+11 0.00 0.00 0.00 0.00 0.00 0.00 19.09
September 0.00 0.497359E+11 0.00 0.00 0.00 0.00 0.00 0.00 19.02
October 0.00 0.404132E+11 0.00 2161462.94 0.00 0.00 61287544.85 0.00 19.05
November 0.00 0.271851E+11 0.00 27927458.49 0.00 0.00 0.728905E+10 0.00 19.11
December 0.00 0.155391E+11 0.00 59231734.38 0.00 0.00 0.206741E+11 0.00 19.19
                   
Annual Sum or Average 0.00 0.382932E+12 0.00 0.306113E+09 0.00 0.00 0.932242E+11 0.00 19.23
Minimum of Months 0.00 0.830796E+10 0.00 0.00 0.00 0.00 0.00 0.00 19.02
Maximum of Months 0.00 0.550305E+11 0.00 76998303.45 0.00 0.00 0.273462E+11 0.00 19.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.627206E+10 0.282231E+09 0.00 1951.65 0.132693E+10 0.00 2622436.84 0.00 1.02
February 0.405206E+10 0.346892E+09 0.00 135996.54 0.152236E+10 0.00 24854033.55 0.00 1.02
March 0.365255E+10 0.101665E+10 0.00 123728.91 0.219452E+10 0.00 51693693.85 0.00 1.01
April 0.948655E+09 0.228024E+10 0.00 317056.50 0.142768E+10 0.00 0.173463E+09 0.00 1.02
May 5413134.69 0.641900E+10 0.00 57692.53 0.140081E+10 0.00 5888140.17 0.00 1.02
June 0.00 0.102463E+11 0.00 0.00 0.465788E+09 0.00 0.00 0.00 1.05
July 0.00 0.118259E+11 0.00 0.00 0.315957E+09 0.00 0.00 0.00 1.08
August 0.00 0.107100E+11 0.00 0.00 0.107804E+10 0.00 0.00 0.00 1.05
September 0.00 0.997954E+10 0.00 0.00 0.829220E+09 0.00 0.00 0.00 1.06
October 3247433.88 0.713539E+10 0.00 140249.95 0.133715E+10 0.00 12173509.05 0.00 1.02
November 0.165120E+10 0.350206E+10 0.00 31321.08 0.195907E+10 0.00 51902595.08 0.00 1.00
December 0.469714E+10 0.109361E+10 0.00 95293.93 0.207969E+10 0.00 42585663.08 0.00 1.01
                   
Annual Sum or Average 0.212823E+11 0.648379E+11 0.00 903291.10 0.159372E+11 0.00 0.365183E+09 0.00 1.03
Minimum of Months 0.00 0.282231E+09 0.00 0.00 0.315957E+09 0.00 0.00 0.00 1.00
Maximum of Months 0.627206E+10 0.118259E+11 0.00 317056.50 0.219452E+10 0.00 0.173463E+09 0.00 1.08



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:59:32

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.195658E+12 0.199311E+10 0.290041E+11 0.115960E+12 0.715028E+12
February 0.225641E+12 0.124749E+09 0.930727E+10 0.367898E+11 0.771970E+12
March 0.314181E+12 -0.171674E+10 -0.864194E+10 -0.611224E+11 0.958884E+12
April 0.337240E+12 -0.449400E+10 -0.454934E+11 -0.217329E+12 0.113475E+13
May 0.333211E+12 -0.104692E+11 -0.128428E+12 -0.575014E+12 0.147354E+13
June 0.292615E+12 -0.141097E+11 -0.177884E+12 -0.798489E+12 0.161190E+13
July 0.306711E+12 -0.151255E+11 -0.196126E+12 -0.854604E+12 0.171977E+13
August 0.336131E+12 -0.153343E+11 -0.195667E+12 -0.870709E+12 0.170634E+13
September 0.251385E+12 -0.138080E+11 -0.176188E+12 -0.778272E+12 0.163168E+13
October 0.240626E+12 -0.111864E+11 -0.137399E+12 -0.623413E+12 0.153923E+13
November 0.179143E+12 -0.597504E+10 -0.734618E+11 -0.322810E+12 0.121027E+13
December 0.193436E+12 -452500822.2 -336516804.1 -0.150498E+11 0.890361E+12
           
Annual Sum or Average 0.320598E+13 -0.905536E+11 -0.110131E+13 -0.496406E+13 0.153637E+14
Minimum of Months 0.179143E+12 -0.153343E+11 -0.196126E+12 -0.870709E+12 0.715028E+12
Maximum of Months 0.337240E+12 0.199311E+10 0.290041E+11 0.115960E+12 0.171977E+13