Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:59
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 09:01:04
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10487.12 | 924.36 | 924.36 |
Net Site Energy | 10487.12 | 924.36 | 924.36 |
Total Source Energy | 21458.26 | 1891.38 | 1891.38 |
Net Source Energy | 21458.26 | 1891.38 | 1891.38 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 698.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 425.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 766.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 242.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1745.01 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 651.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 543.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 122.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 194.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 3155.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 62.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4844.08 | 5643.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 698.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 425.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 766.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 242.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 32.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 543.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 122.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 194.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 3155.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 698.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 425.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 766.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 242.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1745.01 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 651.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 543.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 122.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 194.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 3155.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 62.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 88.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 104.23 | 339.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 233.81 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 426.97 | 497.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 88.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 104.23 | 339.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 233.81 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 426.97 | 497.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 4844.084 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4844.084 | 100.00 |
Total On-Site and Utility Electric Sources | 4844.084 | 100.00 |
Total Electricity End Uses | 4844.084 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 18.04 | 0.77 |
Air to Air Heat Recovery for Heating | 2317.58 | 99.23 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2335.62 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 474.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7332.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:59 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 9.1389 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.3365 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.3365 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 9.2031 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 6.1031 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.8125 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.3656 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 8.7188 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.5531 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.5531 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 6.3938 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.5531 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.3656 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.3656 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7219 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 6.3938 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 6.8557 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 6.8557 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.1389 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.3365 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.3365 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 9.2031 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 6.1031 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.8125 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.3656 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 8.7188 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.5531 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.5531 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 6.3938 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.5531 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.5531 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.5531 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.3656 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.3656 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7219 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 6.3938 | 18.58 | 0.0000 | |
Total | 11345.29 | 6.8557 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 6.8557 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.4542 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-19:30 | 22-JAN-18:49 | - | - | - | - | - | - | - | - | - | - | 03-JAN-21:30 |
Heating | 0.00 | 186463.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 117286.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 88772.42 | 100066.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 32159.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 29138.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 8118.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3897.07 | 244830.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2396.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 370048.64 | 531360.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 186463.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 117286.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58789.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 25090.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1855.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 29138.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 8118.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3897.07 | 244830.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1061.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1093.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 757.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1347.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2428.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 767.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5526.46 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2063.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1720.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 388.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 614.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.39 | 3420.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 196.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 15341.21 | 6117.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 66.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 118.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 214.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 67.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.11 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 151.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 34.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 54.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 301.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1352.21 | 539.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 66.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 118.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 214.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 67.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.11 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 151.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 34.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 54.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 301.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1352.21 | 539.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.59 | 0.582734 | 0.509000 | 1.32 | 1.00 | 0.500000 | 0.000654 | 0.000060 | 1.32 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.478973 | 0.106704 | 0.509000 | 0.243797 | 0.509000 | 0.500000 | 0.003571 | 0.000031 | 0.243797 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.241620 | 0.244946 | 0.509000 | 0.122984 | 0.653188 | 0.500000 | 0.001555 | 0.000012 | 0.122984 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.219990 | 0.568906 | 0.509000 | 0.111975 | 1.00 | 0.500000 | 0.000670 | 0.000018 | 0.111975 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.105999 | 0.681199 | 0.509000 | 0.053954 | 1.00 | 0.500000 | 0.000559 | 0.000010 | 0.053954 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.30 | 0.071537 | 0.509000 | 1.68 | 0.509000 | 0.500000 | 0.021134 | 0.000093 | 1.68 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.85 | 0.077922 | 0.509000 | 0.940067 | 0.509000 | 0.500000 | 0.004890 | 0.000094 | 0.940067 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.09 | 0.195979 | 0.509000 | 2.59 | 0.522611 | 0.500000 | 0.001944 | 0.000237 | 2.59 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.57 | 0.753754 | 0.509000 | 0.801502 | 1.00 | 0.500000 | 0.000505 | 0.000110 | 0.801502 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.13 | 0.118419 | 0.509000 | 1.09 | 0.509000 | 0.500000 | 0.003217 | 0.000095 | 1.09 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.24 | 0.113042 | 0.509000 | 1.14 | 0.509000 | 0.500000 | 0.003370 | 0.000098 | 1.14 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.29 | 0.061899 | 0.509000 | 1.16 | 0.509000 | 0.500000 | 0.011071 | 0.000066 | 1.16 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.810785 | 0.387327 | 0.509000 | 0.412690 | 1.00 | 0.500000 | 0.000984 | 0.000066 | 0.412690 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 6854.95 | 0.000060 | 142.95 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3585.89 | 0.000031 | 82.68 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1408.91 | 0.000012 | 31.34 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2014.09 | 0.000018 | 48.23 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1159.54 | 0.000010 | 28.97 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10616.37 | 0.000093 | 223.88 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 10711.65 | 0.000094 | 238.14 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 27139.73 | 0.000237 | 597.49 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5287.97 | 0.000046 | 151.12 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5291.52 | 0.000046 | 151.22 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 30397.66 | 0.000266 | 868.67 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 30479.30 | 0.000267 | 871.00 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5295.72 | 0.000046 | 151.34 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5299.27 | 0.000046 | 151.44 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12534.72 | 0.000110 | 292.10 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1612.10 | 0.000014 | 46.07 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1613.93 | 0.000014 | 46.12 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 7727.53 | 0.000068 | 220.82 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 10868.62 | 0.000095 | 238.09 |
DINING_FLR_6 VAV BOX REHEAT COIL | 11250.60 | 0.000098 | 246.15 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7546.41 | 0.000066 | 159.40 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7589.30 | 0.000066 | 182.60 |
VAV WITH REHEAT HEATING COIL | 170401.39 | 0.001491 | 2909.13 |
FLR_3_DOAS HEATING COIL | 15340.96 | 0.000134 | 261.90 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.22 | 0.000046 | 0.000477 |
ROOM_2_FLR_3 FAN COIL | 1.09 | 0.000046 | 0.000430 |
ROOM_3_MULT19_FLR_3 FAN COIL | 8.15 | 0.000266 | 0.003139 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.05 | 0.000267 | 0.002098 |
ROOM_5_FLR_3 FAN COIL | 1.09 | 0.000046 | 0.000427 |
ROOM_6_FLR_3 FAN COIL | 0.985723 | 0.000046 | 0.000388 |
ROOM_1_FLR_6 FAN COIL | 0.317627 | 0.000014 | 0.000124 |
ROOM_2_FLR_6 FAN COIL | 0.283286 | 0.000014 | 0.000111 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.72 | 0.000068 | 0.000680 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.22 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.09 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 8.15 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.05 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.09 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.985723 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.317627 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.283286 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.72 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008566 | 12.80 | 0.008500 | 0.000477 | 1.22 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008573 | 12.80 | 0.008500 | 0.000430 | 1.09 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008504 | 12.80 | 0.008500 | 0.003139 | 8.15 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008784 | 12.80 | 0.008500 | 0.002098 | 5.05 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008574 | 12.80 | 0.008500 | 0.000427 | 1.09 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008581 | 12.80 | 0.008500 | 0.000388 | 0.985723 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008563 | 12.80 | 0.008500 | 0.000124 | 0.317627 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008571 | 12.80 | 0.008500 | 0.000111 | 0.283286 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008602 | 12.80 | 0.008500 | 0.000680 | 1.72 | |
VAV WITH REHEAT COOLING COIL | 26.76 | 6.70 | 0.009204 | 10.95 | 0.008500 | 0.017321 | 22.79 | 484932.30 |
FLR_3_DOAS COOLING COIL | 29.40 | 6.70 | 0.008822 | 11.92 | 0.008500 | 0.001623 | 2.05 | 45447.84 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.66 | 11.66 | 22.91 | 11.66 | 22.79 | 22.79 | 0.300000 | 0.511759 | 22.79 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 22.79 | 11.66 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 22.79 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.017321 | 0.000027 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001491 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001623 | 0.000293 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000134 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.026817 | 5526.09 | |
HEATSYS1 PUMP | 0.003430 | 1032.85 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003430 | 0.411556 |
COOLSYS1 | 0.026817 | 3.22 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 392028.15 | 392028.15 | 0.003430 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.026817 | 3825.90 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.026817 | 750817.87 | 751446.35 | 85.66 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 9.139 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.519 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.336 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.096 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.336 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.096 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 9.203 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.583 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 6.103 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.793 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.813 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.343 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.366 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.746 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 8.719 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.789 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.366 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 78.186 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.366 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 78.186 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.722 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2946.209 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 18084.325 | 9.139 | 169.807 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18084.325 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 894.495 | 13.336 | 82.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 894.495 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1035.829 | 13.336 | 82.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1035.829 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 1511.551 | 9.203 | 569.967 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1511.551 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 578.329 | 6.103 | 283.494 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 578.329 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 453.605 | 5.813 | 54.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 453.605 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1957.673 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1957.673 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11405.759 | 8.719 | 27.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11405.759 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 111.660 | 4.553 | 74.440 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.660 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 111.691 | 4.553 | 74.460 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.691 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2489.757 | 6.394 | 118.803 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.757 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 111.691 | 4.553 | 74.460 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.691 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3437.839 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3437.839 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3437.839 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3437.839 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1210.923 | 11.722 | 54.453 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1210.923 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2635.024 | 6.394 | 118.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2635.024 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.8226 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.107 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.174 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.031 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.097 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.048 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7359 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6841 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8028 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7445 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.17638513E-14 | 0.32473881E-16 | -0.15472737E-09 | 0.39084990E-16 |
29 | 8 | 0.22578286E-07 | 0.11136169E-12 | 0.38514655E-03 | -0.25672286E-09 |
30 | 7 | -0.12460867E-01 | 0.57383191E-08 | -0.23401545E-01 | 0.14168460E-03 |
31 | 6 | 0.41130930 | 0.19934685E-05 | 0.47716306 | -0.48180040E-02 |
32 | 5 | -5.2487139 | 0.74343025E-04 | -4.4802041 | 0.63904887E-01 |
33 | 4 | 33.260058 | 0.60748543E-03 | 21.592533 | -0.42553784 |
34 | 3 | -111.77343 | 0.13226915E-02 | -55.924898 | 1.5231004 |
35 | 2 | 197.67353 | 0.74337769E-03 | 78.150831 | -2.9093300 |
36 | 1 | -171.36487 | 0.79295509E-04 | -55.335031 | 2.7490988 |
37 | 0 | 57.057407 | 0.45097929E-06 | 15.545453 | |
38 | 9 | -0.19728226E-15 | 0.38070760E-16 | -0.14134637E-09 | 0.10329039E-17 |
39 | 8 | 0.20696804E-07 | 0.14765672E-12 | 0.36530744E-03 | -0.23532978E-09 |
40 | 7 | -0.11868633E-01 | 0.77667999E-08 | -0.22548754E-01 | 0.13495068E-03 |
41 | 6 | 0.39521686 | 0.27204939E-05 | 0.46345169 | -0.46283129E-02 |
42 | 5 | -5.0916664 | 0.10217830E-03 | -4.3748670 | 0.61957574E-01 |
43 | 4 | 32.565369 | 0.84029717E-03 | 21.180735 | -0.41631434 |
44 | 3 | -110.29532 | 0.18400486E-02 | -55.110745 | 1.5017457 |
45 | 2 | 196.20849 | 0.10394005E-02 | 77.404245 | -2.8860650 |
46 | 1 | -170.82368 | 0.11139293E-03 | -55.118150 | 2.7396138 |
47 | 0 | 57.057407 | 0.63685742E-06 | 15.581450 | |
48 | 9 | 0.13059652E-14 | 0.41030072E-16 | -0.13816519E-09 | -0.47111965E-17 |
49 | 8 | 0.20247126E-07 | 0.15597406E-12 | 0.36047671E-03 | -0.23021680E-09 |
50 | 7 | -0.11724123E-01 | 0.82470298E-08 | -0.22340566E-01 | 0.13330755E-03 |
51 | 6 | 0.39128975 | 0.28947446E-05 | 0.46009809 | -0.45820219E-02 |
52 | 5 | -5.0533361 | 0.10891817E-03 | -4.3490697 | 0.61482301E-01 |
53 | 4 | 32.395785 | 0.89717001E-03 | 21.079809 | -0.41406279 |
54 | 3 | -109.93440 | 0.19673976E-02 | -54.911173 | 1.4965315 |
55 | 2 | 195.85064 | 0.11127485E-02 | 77.221372 | -2.8803827 |
56 | 1 | -170.69145 | 0.11939355E-03 | -55.065279 | 2.7372963 |
57 | 0 | 57.057407 | 0.68346468E-06 | 15.590432 | |
58 | 9 | -0.20590843E-15 | 0.37601014E-16 | -0.14495918E-09 | 0.53749011E-17 |
59 | 8 | 0.21205398E-07 | 0.13808064E-12 | 0.37072834E-03 | -0.24111267E-09 |
60 | 7 | -0.12030653E-01 | 0.72214098E-08 | -0.22782120E-01 | 0.13679291E-03 |
61 | 6 | 0.39961963 | 0.25236359E-05 | 0.46720788 | -0.46802108E-02 |
62 | 5 | -5.1346368 | 0.94596970E-04 | -4.4037454 | 0.62490383E-01 |
63 | 4 | 32.755467 | 0.77656360E-03 | 21.293679 | -0.41883826 |
64 | 3 | -110.69986 | 0.16977958E-02 | -55.334066 | 1.5075900 |
65 | 2 | 196.60952 | 0.95769584E-03 | 77.608945 | -2.8924333 |
66 | 1 | -170.97185 | 0.10250317E-03 | -55.177451 | 2.7422106 |
67 | 0 | 57.057407 | 0.58520576E-06 | 15.571474 | |
68 | 9 | -0.13316196E-15 | 0.35962645E-16 | -0.14184186E-09 | 0.33595795E-17 |
69 | 8 | 0.20766565E-07 | 0.14634888E-12 | 0.36605364E-03 | -0.23612300E-09 |
70 | 7 | -0.11890945E-01 | 0.76921302E-08 | -0.22580893E-01 | 0.13520437E-03 |
71 | 6 | 0.39582317 | 0.26934781E-05 | 0.46396918 | -0.46354598E-02 |
72 | 5 | -5.0975841 | 0.10113583E-03 | -4.3788466 | 0.62030949E-01 |
73 | 4 | 32.591550 | 0.83151862E-03 | 21.196301 | -0.41666193 |
74 | 3 | -110.35104 | 0.18204263E-02 | -55.141525 | 1.5025506 |
75 | 2 | 196.26372 | 0.10281160E-02 | 77.432455 | -2.8869422 |
76 | 1 | -170.84409 | 0.11016374E-03 | -55.126315 | 2.7399715 |
77 | 0 | 57.057407 | 0.62970739E-06 | 15.580070 | |
78 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
79 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
80 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
81 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
82 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
83 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
84 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
85 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
86 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
87 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
88 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
89 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
90 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
91 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
92 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
93 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3856_SHGC_0.4 | 37 | 1 | VerySmooth | 2.191 | 2.191 | 1.000 | 0.401 | ||
2 | RESWINDOW_U_0.3856_SHGC_0.4 | 38 | 1 | VerySmooth | 2.191 | 2.191 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.40174E-002 | 0.31435 | 0.47878 | 0.47878 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11969 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.40174E-002 | 0.31435 | 0.47878 | 0.47878 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11969 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1505 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.9294E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1718 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 0.1044 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1000 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.0976E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.2077E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.3979E-002 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1725 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1069 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1978 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1245 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1107 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.1062E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 4.7248E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.9114E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.9527E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.2854E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.0432E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.7306E-002 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8856E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.1489E-002 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.1419E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.4687E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.9527E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.2854E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.0432E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.7306E-002 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8856E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.1489E-002 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.1419E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.4687E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 35105.47130 | 35105.47130 | 2.58758 | 2.58758 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 26.12400 | 8.81626E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 6497.64608 | 6497.64608 | 0.47897 | 0.47897 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.82094E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2318.34601 | 2318.34601 | 0.10080 | 0.10080 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3277.67745 | 3277.67745 | 0.24162 | 0.24162 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 29.29600 | 8.82133E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 769.51877 | 769.51877 | 3.34606E-002 | 9.17347E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2984.89200 | 2984.89200 | 0.21999 | 0.21999 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 29.19200 | 8.82116E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1432.08484 | 1432.08484 | 6.22704E-002 | 6.22704E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1438.22015 | 1438.22015 | 0.10600 | 0.10600 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.82150E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 879.09236 | 879.09236 | 3.82250E-002 | 5.77652E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44752.70101 | 44752.70101 | 3.29863 | 3.29863 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1890.62156 | 1890.62156 | 8.22061E-002 | 8.22061E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 25034.65568 | 25034.65568 | 1.84689 | 1.84689 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.82094E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 5823.45042 | 5823.45042 | 0.25321 | 0.67639 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 68981.24283 | 68981.24283 | 5.08645 | 5.08645 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.82122E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 13678.68023 | 13678.68023 | 0.59478 | 1.89399 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 12249.78776 | 12249.78776 | 1.21668 | 1.21668 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 28.36000 | 8.81983E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5288.08678 | 5288.08678 | 0.23128 | 0.23128 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11017.88221 | 11017.88221 | 1.09432 | 1.09432 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 28.08267 | 8.81938E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5291.63389 | 5291.63389 | 0.23144 | 0.23144 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 82035.79616 | 82035.79616 | 8.14762 | 8.14762 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 30397.98497 | 30397.98497 | 1.32953 | 1.32953 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 50871.94353 | 50871.94353 | 5.05289 | 5.05289 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.82150E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 30479.61972 | 30479.61972 | 1.33310 | 1.33310 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10948.80272 | 10948.80272 | 1.08746 | 1.08746 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5295.83755 | 5295.83755 | 0.23162 | 0.23162 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9924.47087 | 9924.47087 | 0.98572 | 0.98572 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5299.38347 | 5299.38347 | 0.23178 | 0.23178 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 21363.81466 | 21363.81466 | 1.57466 | 1.57466 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 29.40000 | 8.82150E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 8366.32729 | 8366.32729 | 0.36379 | 0.47476 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3197.94297 | 3197.94297 | 0.31763 | 0.31763 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 28.36000 | 8.81983E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1612.13003 | 1612.13003 | 7.05085E-002 | 7.05085E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2852.18311 | 2852.18311 | 0.28329 | 0.28329 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1613.96726 | 1613.96726 | 7.05889E-002 | 7.05889E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 17290.84334 | 17290.84334 | 1.71741 | 1.71741 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.82122E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 7727.66243 | 7727.66243 | 0.33798 | 0.33798 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 28918.70850 | 28918.70850 | 2.13415 | 2.13415 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5218.57896 | 5218.57896 | 0.22692 | 1.18780 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30294.69545 | 30294.69545 | 2.23566 | 2.23566 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5332.14830 | 5332.14830 | 0.23185 | 1.18780 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | -4.20000 | 2.69032E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30952.69610 | 30952.69610 | 2.28735 | 2.28735 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 28.46400 | 8.82000E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1515.68164 | 1515.68164 | 6.58950E-002 | 0.36735 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -4.20000 | 2.69032E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 11000.21624 | 11000.21624 | 0.81078 | 0.81078 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 29.40000 | 8.82150E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 5442.67036 | 5442.67036 | 0.23666 | 0.23666 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | -4.20000 | 2.69032E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 379208.27 | 22.78522 | 22.78522 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 181330.16 | 7.27397 | 7.27397 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 40614.20 | 18.54363 | 2.05125 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 51134.75 | 4.06783 | 2.05125 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.58758 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.58273 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50900 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.31708 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.53815E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.99701E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.31708 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6854.95244 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.99701E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 142.94822 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.47897 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10670 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50900 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24380 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50900 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.57062E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.13710E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24380 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3585.89367 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.13710E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 82.68476 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.24162 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24495 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50900 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12298 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65319 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.55545E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.23257E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12298 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1408.90608 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.23257E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 31.34275 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.21999 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.56891 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50900 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11197 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.69707E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.76201E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11197 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2014.08622 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.76201E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 48.22862 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.10600 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.68120 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50900 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.39536E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.59308E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.01442E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.39536E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1159.54158 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.01442E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 28.97237 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.29863 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.15369E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50900 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.67900 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50900 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.11344E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.28766E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.67900 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10616.36998 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.28766E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 223.88168 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.84689 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.79217E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50900 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.94007 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50900 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.88952E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.37102E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.94007 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10711.65227 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.37102E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 238.13551 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.08645 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19598 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50900 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.58900 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52261 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.94408E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.37430E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.58900 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27139.73327 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.37430E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 597.49408 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.21668 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.21668 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.62615E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.76761E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69134 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56608E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.76761E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.21668 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5287.97220 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.62615E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 151.11637 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.09432 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.09432 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.62925E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.29647E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69133 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57313E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.29647E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.09432 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5291.51924 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.62925E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 151.21771 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.14762 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 8.14762 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.65932E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.13877E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69178 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50448E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.13877E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.14762 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 30397.66291 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.65932E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 868.67039 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.05289 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.05289 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.66646E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.09835E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69083 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.78368E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.09835E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.05289 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 30479.29684 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.66646E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 871.00269 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.08746 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.08746 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.63293E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.27047E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69133 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57394E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.27047E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.08746 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5295.72282 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.63293E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 151.33780 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.98572 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.98572 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.63603E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.87884E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69132 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58138E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.87884E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.98572 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5299.26867 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.63603E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 151.43910 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.57466 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.75375 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50900 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80150 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.05470E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.09659E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.80150 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12534.72289 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.09659E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 292.09949 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.31763 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.31763 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.41033E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.24370E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69135 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56333E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.24370E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.31763 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1612.09624 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.41033E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 46.06718 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.28329 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.28329 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.41194E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.11161E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69134 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57113E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.11161E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.28329 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1613.93343 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.41194E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 46.11967 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.71741 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.71741 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.76038E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 6.79536E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69111 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60163E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.79536E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.71741 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7727.53216 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.76038E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 220.81986 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.13415 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11842 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50900 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.08628 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50900 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.21740E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.50834E-005 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.08628 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10868.62105 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.50834E-005 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 238.09312 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.23566 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11304 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50900 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.13795 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50900 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.37044E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.84251E-005 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.13795 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11250.59670 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.84251E-005 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 246.15173 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.28735 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.18987E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50900 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.16426 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50900 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10709E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.60193E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.16426 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7546.41144 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.60193E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 159.39670 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81078 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38733 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50900 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41269 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.83665E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.63945E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41269 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7589.30441 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.63945E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 182.60068 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.66055 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.66055 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.90874 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.66055 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.78522 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 22.78522 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.51176 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 22.78522 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.78522 |
338 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 11.66146 |
339 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.75983 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.95288 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.20444E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 484932.30241 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.73207E-002 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 22.78522 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 170401.38827 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49075E-003 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2909.13105 |
351 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 22.78522 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.73207E-002 |
353 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.74926E-005 |
354 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.49075E-003 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
356 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
357 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.40000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.91727 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.82150E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 45447.83718 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.62329E-003 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 15340.96456 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.34209E-004 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 261.90442 |
369 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.62329E-003 |
371 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.93349E-004 |
372 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.34209E-004 |
373 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.68175E-002 |
374 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 5526.08761 |
375 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.42963E-003 |
376 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.41156 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.42963E-003 |
378 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1032.85493 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 392028.14934 |
381 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 392028.15000 |
382 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.42963E-003 |
383 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.68175E-002 |
384 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.21810 |
385 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.68175E-002 |
386 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3825.89684 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.68175E-002 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 750817.87420 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 751446.35000 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 85.66488 |
391 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
392 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
393 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
394 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
395 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 6890.40 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3602.50 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1415.67 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2022.96 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1164.43 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10670.69 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 10763.10 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 27271.39 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 5695.76 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 5699.58 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 32741.61 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 32829.53 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 5704.11 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 5707.93 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12592.19 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1736.36 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1738.34 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8323.18 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 10922.38 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 11306.31 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7584.97 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7622.56 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 129793.51 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 11685.10 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 20101.76 | 16216.41 | 3885.35 | 0.81 | 2304.78 | 23.38 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 18103.16 | 14596.81 | 3506.35 | 0.81 | 2075.21 | 21.05 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 133116.15 | 107862.70 | 25253.44 | 0.81 | 15290.37 | 155.08 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 86680.27 | 68904.48 | 17775.78 | 0.79 | 9883.47 | 100.24 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 17992.25 | 14506.55 | 3485.70 | 0.81 | 2062.45 | 20.92 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 16330.72 | 13160.00 | 3170.72 | 0.81 | 1871.59 | 18.98 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5245.20 | 4232.21 | 1012.99 | 0.81 | 601.44 | 6.10 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4684.66 | 3777.83 | 906.83 | 0.81 | 537.04 | 5.45 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 28555.22 | 22978.47 | 5576.75 | 0.80 | 3270.74 | 33.17 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 564736.83 | 393930.71 | 170806.12 | 0.70 | 67754.50 | 687.20 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 49660.04 | 34741.99 | 14918.05 | 0.70 | 5487.20 | 55.65 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.107 | 0.950 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.107 | 0.950 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.107 | 0.950 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.107 | 0.950 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 4.1123275330E-002 | 5.4830907302E-002 | Pass | Pass | 0.1798428160 | 0.5019573521 | Fail | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.5352113464E-002 | 4.3666210377E-002 | Pass | Pass | 0.7218030519 | 2.0762663513 | Fail | Fail |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.9452083119E-002 | 9.0933808365E-002 | Fail | Pass | 0.3340585306 | 1.0907716220 | Fail | Fail |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.3065469047E-002 | 4.2107845142E-002 | Pass | Pass | 0.3730168843 | 1.5827395286 | Fail | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.8115916466E-003 | 2.4021409378E-002 | Pass | Pass | 0.5323456356 | 1.4075677788 | Fail | Fail |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.2915345998 | 0.5854183237 | Fail | Pass | 0.1133388078 | 0.1859829449 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.6090619699E-002 | 0.2233351616 | Pass | Pass | 0.3692736017 | 1.4712085478 | Fail | Fail |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.7516558155E-002 | 0.1177471529 | Fail | Pass | 0.3755386433 | 1.5616514111 | Fail | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.6075712921E-002 | 0.2955614783 | Pass | Pass | 0.2603090844 | 0.9053068675 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.6186875922E-002 | 0.2960410767 | Pass | Pass | 0.4527276256 | 1.8358502002 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.5838893067E-003 | 1.0221744774E-002 | Pass | Pass | 0.7727228165 | 3.1513602429 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.4535654034E-002 | 9.5821157305E-002 | Pass | Pass | 1.0885348933 | 10.5404083543 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.5796129468E-002 | 0.2941461152 | Pass | Pass | 0.2578367068 | 0.8874627227 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.5910841400E-002 | 0.2944820514 | Pass | Pass | 0.3285987715 | 1.1195874939 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.0020579568E-002 | 2.7081599133E-002 | Pass | Pass | 0.5450773951 | 1.5342547214 | Fail | Fail |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2584893008E-002 | 0.3322936141 | Pass | Pass | 0.3333081383 | 1.3889649502 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2611470874E-002 | 0.3321331018 | Pass | Pass | 0.2987667375 | 1.1747087133 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.4212473659E-002 | 0.2602181338 | Pass | Pass | 0.1832041503 | 0.6583140336 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1059081673 | 0.1985906349 | Pass | Pass | 0.1454274845 | 0.2653621272 | Pass | Fail |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1004551873 | 0.2248000085 | Fail | Pass | 0.1394628087 | 0.2701254248 | Pass | Fail |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.2552857248 | 0.5278026225 | Fail | Pass | 0.1207320165 | 0.1976485340 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.7647351137E-002 | 4.8467937038E-002 | Pass | Pass | 0.4775855913 | 2.5149484716 | Fail | Fail |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3545.01 | 132.86 | 1716.91 | 7242.80 | 2239.93 | 14877.52 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.191 | 0.401 | 0.402 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.191 | 0.401 | 0.402 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.191 | 0.401 | 0.402 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.191 | 0.401 | 0.402 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.191 | 0.401 | 0.402 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.191 | 0.401 | 0.402 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.191 | 0.401 | 0.402 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.191 | 0.401 | 0.402 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.191 | 0.401 | 0.402 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.191 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 432.95 | 2.191 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.191 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.1389 | 1978.83 | 18084.33 | LightsWired | LTG_SCH_BASEMENT | 51.16 | 168.00 | 51.10 | 0.0000 | Y | 173.46 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.3365 | 67.07 | 894.50 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.61 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.3365 | 77.67 | 1035.83 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 9.97 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 9.2031 | 164.24 | 1511.55 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 16.63 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 6.1031 | 94.76 | 578.33 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 2.78 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.8125 | 78.04 | 453.60 | LightsWired | LTG_SCH_LAUNDRY | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 4.37 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.3656 | 188.86 | 1957.67 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.84 | 0.0000 | Y | 17.95 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 8.7188 | 1308.19 | 11405.76 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 56.94 | 0.0000 | Y | 121.92 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.5531 | 156.09 | 710.69 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.5531 | 156.07 | 710.61 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.5531 | 1863.81 | 8486.17 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 76.02 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.5531 | 1864.32 | 8488.49 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 76.04 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.5531 | 156.09 | 710.69 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.5531 | 156.07 | 710.61 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 6.3938 | 1557.62 | 9959.03 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 109.60 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.5531 | 39.02 | 177.67 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.59 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.5531 | 39.02 | 177.65 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.59 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.5531 | 220.77 | 1005.22 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 9.00 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.3656 | 331.66 | 3437.84 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 53.70 | 0.0000 | Y | 34.65 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.3656 | 331.66 | 3437.84 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 53.70 | 0.0000 | Y | 34.65 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7219 | 103.30 | 1210.92 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.33 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 6.3938 | 412.12 | 2635.02 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 29.00 |
Interior Lighting Total | 6.8557 | 11345.29 | 77780.02 | 507.28 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 11405.76 | 798.40 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 11405.76 | 0.00 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1957.67 | 763.49 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 1957.67 | 0.00 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3437.84 | 687.57 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3437.84 | 0.00 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3437.84 | 687.57 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3437.84 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 15448.40 | AstronomicalClock | - | 83.55 | 83.55 | 242.27 | |
Exterior Lighting Total | 15448.40 | 242.27 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 392028.15 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 751446.35 | 2.96 | 751578.43 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13348.29 | 20101.76 | 16216.41 | 3885.35 | 0.81 | - | 2304.78 | 23.38 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12029.20 | 18103.16 | 14596.81 | 3506.35 | 0.81 | - | 2075.21 | 21.05 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 87878.75 | 133116.15 | 107862.70 | 25253.44 | 0.81 | - | 15290.37 | 155.08 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 58749.36 | 86680.27 | 68904.48 | 17775.78 | 0.79 | - | 9883.47 | 100.24 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11956.41 | 17992.25 | 14506.55 | 3485.70 | 0.81 | - | 2062.45 | 20.92 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10859.93 | 16330.72 | 13160.00 | 3170.72 | 0.81 | - | 1871.59 | 18.98 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3482.09 | 5245.20 | 4232.21 | 1012.99 | 0.81 | - | 601.44 | 6.10 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3112.28 | 4684.66 | 3777.83 | 906.83 | 0.81 | - | 537.04 | 5.45 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 19025.55 | 28555.22 | 22978.47 | 5576.75 | 0.80 | - | 3270.74 | 33.17 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 484932.30 | 564736.83 | 393930.71 | 170806.12 | 0.70 | - | 67754.50 | 687.20 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 45447.84 | 49660.04 | 34741.99 | 14918.05 | 0.70 | - | 5487.20 | 55.65 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 6854.95 | 6890.40 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3585.89 | 3602.50 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1408.91 | 1415.67 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2014.09 | 2022.96 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1159.54 | 1164.43 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10616.37 | 10670.69 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10711.65 | 10763.10 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 27139.73 | 27271.39 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5287.97 | 5695.76 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5291.52 | 5699.58 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 30397.66 | 32741.61 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 30479.30 | 32829.53 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5295.72 | 5704.11 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5299.27 | 5707.93 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12534.72 | 12592.19 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1612.10 | 1736.36 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1613.93 | 1738.34 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 7727.53 | 8323.18 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10868.62 | 10922.38 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11250.60 | 11306.31 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7546.41 | 7584.97 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7589.30 | 7622.56 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 170401.39 | 129793.51 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 15340.96 | 11685.10 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.22 | 856.10 | 703.64 | 1.00 | 1.15 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.09 | 770.01 | 703.64 | 1.00 | 1.18 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 8.15 | 5732.96 | 703.64 | 1.00 | 0.94 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.05 | 3555.40 | 703.64 | 1.00 | 0.97 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.09 | 765.18 | 703.64 | 1.00 | 1.18 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.99 | 693.59 | 703.64 | 1.00 | 1.20 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.32 | 223.49 | 703.64 | 1.00 | 1.67 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.28 | 199.33 | 703.64 | 1.00 | 1.75 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.72 | 1208.43 | 703.64 | 1.00 | 1.09 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 22.79 | 51053.45 | 2240.64 | 1.00 | 1.11 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.026817 | 5526.09 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003430 | 1032.85 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.026817 | 3825.90 | 142664.32 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 35105.47 | 35105.47 | 17.74 | 2.588 | 2.588 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 24.00 | 24.00 | 0.00919 | 26.12 | 0.00882 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 6497.65 | 6497.65 | 96.88 | 0.479 | 0.479 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00888 | 29.05 | 0.00882 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3277.68 | 3277.68 | 42.20 | 0.242 | 0.242 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00936 | 29.30 | 0.00882 | 0.092 | 0.00 |
MECH_FLR_1 | 2984.89 | 2984.89 | 18.17 | 0.220 | 0.220 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00871 | 29.19 | 0.00882 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1438.22 | 1438.22 | 15.18 | 0.106 | 0.106 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00882 | 29.40 | 0.00882 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44752.70 | 44752.70 | 573.46 | 3.299 | 3.299 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00854 | 29.40 | 0.00882 | 0.000 | 0.00 |
CAFE_FLR_1 | 25034.66 | 25034.66 | 132.56 | 1.847 | 1.847 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 23.99 | 0.00977 | 29.05 | 0.00882 | 0.676 | 0.00 |
LOBBY_FLR_1 | 68981.24 | 68981.24 | 52.73 | 5.086 | 5.086 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 23.99 | 0.00987 | 29.23 | 0.00882 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 12249.79 | 12249.79 | 313.92 | 1.217 | 1.217 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00857 | 28.36 | 0.00882 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11017.88 | 11017.88 | 282.38 | 1.094 | 1.094 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 21.11 | 21.11 | 0.00857 | 28.08 | 0.00882 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 82035.80 | 82035.80 | 3345.14 | 8.148 | 8.148 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 21.11 | 21.11 | 0.00850 | 29.14 | 0.00882 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 50871.94 | 50871.94 | 2073.82 | 5.053 | 5.053 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 21.11 | 21.11 | 0.00878 | 29.40 | 0.00882 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10948.80 | 10948.80 | 280.58 | 1.087 | 1.087 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 21.11 | 21.11 | 0.00857 | 25.45 | 0.00882 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9924.47 | 9924.47 | 254.36 | 0.986 | 0.986 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.11 | 21.11 | 0.00858 | 23.68 | 0.00881 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 21363.81 | 21363.81 | 54.86 | 1.575 | 1.575 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00939 | 29.40 | 0.00882 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3197.94 | 3197.94 | 81.95 | 0.318 | 0.318 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00856 | 28.36 | 0.00882 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2852.18 | 2852.18 | 73.10 | 0.283 | 0.283 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 21.11 | 21.11 | 0.00857 | 27.94 | 0.00882 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 17290.84 | 17290.84 | 704.87 | 1.717 | 1.717 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 21.11 | 21.11 | 0.00860 | 29.23 | 0.00882 | 0.099 | 0.00 |
BANQUET_FLR_6 | 28918.71 | 28918.71 | 87.19 | 2.134 | 2.134 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 23.98 | 0.01044 | 29.40 | 0.00882 | 1.188 | 0.00 |
DINING_FLR_6 | 30294.70 | 30294.70 | 91.34 | 2.236 | 2.236 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 23.99 | 0.01035 | 29.40 | 0.00882 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30952.70 | 30952.70 | 299.63 | 2.287 | 2.287 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 24.00 | 23.97 | 0.01007 | 28.46 | 0.00882 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 11000.22 | 11000.22 | 26.69 | 0.811 | 0.811 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00896 | 29.40 | 0.00882 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.99 | 0.00269 | -4.20 | 0.00269 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2318.35 | 2318.35 | 34.57 | 0.101 | 0.101 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00749 | -4.20 | 0.00269 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 769.52 | 769.52 | 9.91 | 0.033 | 0.092 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00742 | -4.20 | 0.00269 | 0.092 | 0.00 |
MECH_FLR_1 | 1432.08 | 1432.08 | 8.72 | 0.062 | 0.062 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00728 | -4.20 | 0.00269 | 0.000 | 0.00 |
STORAGE_FLR_1 | 879.09 | 879.09 | 9.28 | 0.038 | 0.058 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00732 | -4.20 | 0.00269 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1890.62 | 1890.62 | 24.23 | 0.082 | 0.082 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00726 | -4.20 | 0.00269 | 0.000 | 0.00 |
CAFE_FLR_1 | 5823.45 | 5823.45 | 30.83 | 0.253 | 0.676 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00755 | -4.20 | 0.00269 | 0.676 | 0.00 |
LOBBY_FLR_1 | 13678.68 | 13678.68 | 10.46 | 0.595 | 1.894 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00746 | -4.20 | 0.00269 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5288.09 | 5288.09 | 135.52 | 0.231 | 0.231 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00749 | -4.20 | 0.00269 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5291.63 | 5291.63 | 135.62 | 0.231 | 0.231 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00749 | -4.20 | 0.00269 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 30397.98 | 30397.98 | 1239.53 | 1.330 | 1.330 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00752 | -4.20 | 0.00269 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 30479.62 | 30479.62 | 1242.52 | 1.333 | 1.333 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00752 | -4.20 | 0.00269 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5295.84 | 5295.84 | 135.71 | 0.232 | 0.232 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00749 | -4.20 | 0.00269 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5299.38 | 5299.38 | 135.82 | 0.232 | 0.232 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00749 | -4.20 | 0.00269 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 8366.33 | 8366.33 | 21.48 | 0.364 | 0.475 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00760 | -4.20 | 0.00269 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1612.13 | 1612.13 | 41.31 | 0.071 | 0.071 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00757 | -4.20 | 0.00269 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1613.97 | 1613.97 | 41.37 | 0.071 | 0.071 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00757 | -4.20 | 0.00269 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 7727.66 | 7727.66 | 315.02 | 0.338 | 0.338 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00759 | -4.20 | 0.00269 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5218.58 | 5218.58 | 15.73 | 0.227 | 1.188 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00767 | -4.20 | 0.00269 | 1.188 | 0.00 |
DINING_FLR_6 | 5332.15 | 5332.15 | 16.08 | 0.232 | 1.188 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 21.00 | 21.00 | 0.00768 | -4.20 | 0.00269 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1515.68 | 1515.68 | 14.67 | 0.066 | 0.367 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00585 | -4.20 | 0.00269 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 5442.67 | 5442.67 | 13.21 | 0.237 | 0.237 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | 21.00 | 21.00 | 0.00772 | -4.20 | 0.00269 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 22.79 | 22.79 | 7.27 | 7.27 | 22.7852 | 11.6605 | 22.7852 | 0.5118 | 0.3000 |
FLR_3_DOAS | 18.54 | 2.05 | 4.07 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 6854.952 | 6854.952 | 1.317077 | 0.00005997 | 142.948 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6854.95 | 6854.95 | 1.317077 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 6893.48 | 6893.48 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3585.894 | 3585.894 | 0.243797 | 0.00003137 | 82.685 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3585.89 | 3585.89 | 0.243797 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00749309 | 47.7895 | 2318.35 | 0.00 | 3605.11 | 3605.11 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1408.906 | 1408.906 | 0.122984 | 0.00001233 | 31.343 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1408.91 | 1408.91 | 0.122984 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00741935 | 47.3237 | 769.52 | 0.00 | 1416.56 | 1416.56 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2014.086 | 2014.086 | 0.111975 | 0.00001762 | 48.229 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2014.09 | 2014.09 | 0.111975 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00728366 | 46.4683 | 1432.08 | 0.00 | 2024.63 | 2024.63 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1159.542 | 1159.542 | 0.053954 | 0.00001014 | 28.972 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1159.54 | 1159.54 | 0.053954 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00732126 | 46.7054 | 879.09 | 0.00 | 1165.52 | 1165.52 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10616.370 | 10616.370 | 1.679003 | 0.00009288 | 223.882 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10616.37 | 10616.37 | 1.679003 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00726278 | 46.3376 | 1890.62 | 0.00 | 10675.80 | 10675.80 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 10711.652 | 10711.652 | 0.940067 | 0.00009371 | 238.136 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10711.65 | 10711.65 | 0.940067 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00754874 | 48.1398 | 5823.45 | 0.00 | 10769.83 | 10769.83 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 27139.733 | 27139.733 | 2.589003 | 0.00023743 | 597.494 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 27139.73 | 27139.73 | 2.589003 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00746084 | 47.5852 | 13678.68 | 0.00 | 27287.71 | 27287.71 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 13348.290 | -999.000 | 1.216678 | 0.00047676 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 13348.29 | 13138.63 | 1.216678 | 21.69 | 15.47 | 0.00856608 | 12.80 | 11.97 | 0.00850000 | 28.36 | 0.00881983 | 18.00 | 0.0000 | 21.11 | 0.00856608 | 54.1686 | 12249.79 | 0.00 | 13533.71 | 13087.78 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5287.972 | 5287.972 | 0.231281 | 0.00004626 | 151.116 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5287.97 | 5287.97 | 0.231281 | 21.11 | 14.28 | 0.00748764 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00748764 | 47.4309 | 5288.09 | 0.00 | 5700.56 | 5700.56 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12029.196 | -999.000 | 1.094323 | 0.00042965 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | unknown | 8/21 16:50:00 | 12029.20 | 11820.43 | 1.094323 | 21.69 | 15.48 | 0.00857313 | 12.80 | 11.97 | 0.00850000 | 28.08 | 0.00881938 | 17.91 | 0.0000 | 21.11 | 0.00857313 | 54.2126 | 11017.88 | 0.00 | 12196.13 | 11775.23 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5291.519 | 5291.519 | 0.231436 | 0.00004629 | 151.218 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5291.52 | 5291.52 | 0.231436 | 21.11 | 14.28 | 0.00748799 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00748799 | 47.4331 | 5291.63 | 0.00 | 5704.38 | 5704.38 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 87878.746 | -999.000 | 8.147616 | 0.00313877 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | 8/21 13:30:00 | 87878.75 | 87783.83 | 8.147616 | 21.69 | 15.42 | 0.00850448 | 12.80 | 11.97 | 0.00850000 | 29.14 | 0.00882108 | 18.26 | 0.0000 | 21.11 | 0.00850448 | 53.7831 | 82035.80 | 0.00 | 89110.13 | 87408.23 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 30397.663 | 30397.663 | 1.329534 | 0.00026593 | 868.670 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 30397.66 | 30397.66 | 1.329534 | 21.11 | 14.32 | 0.00752391 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00752391 | 47.6569 | 30397.98 | 0.00 | 32769.60 | 32769.60 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 58749.357 | -999.000 | 5.052889 | 0.00209835 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | unknown | 8/21 15:00:00 | 58749.36 | 54982.31 | 5.052889 | 21.69 | 15.66 | 0.00878368 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 0.0000 | 21.11 | 0.00878368 | 55.5264 | 50871.94 | 0.00 | 59541.70 | 54844.74 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 30479.297 | 30479.297 | 1.333104 | 0.00026665 | 871.003 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 30479.30 | 30479.30 | 1.333104 | 21.11 | 14.32 | 0.00752496 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00752496 | 47.6634 | 30479.62 | 0.00 | 32857.61 | 32857.61 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11956.415 | -999.000 | 1.087461 | 0.00042705 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | 8/21 10:00:00 | 11956.41 | 11746.66 | 1.087461 | 21.69 | 15.48 | 0.00857394 | 12.80 | 11.97 | 0.00850000 | 25.45 | 0.00881519 | 17.01 | 0.0000 | 21.11 | 0.00857394 | 54.2176 | 10948.80 | 0.00 | 12122.32 | 11701.80 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5295.723 | 5295.723 | 0.231620 | 0.00004633 | 151.338 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5295.72 | 5295.72 | 0.231620 | 21.11 | 14.28 | 0.00748832 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00748832 | 47.4352 | 5295.84 | 0.00 | 5708.92 | 5708.92 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10859.931 | -999.000 | 0.985723 | 0.00038788 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | unknown | 8/21 09:00:00 | 10859.93 | 10650.62 | 0.985723 | 21.69 | 15.49 | 0.00858138 | 12.80 | 11.97 | 0.00850000 | 23.68 | 0.00881240 | 16.40 | 0.0000 | 21.11 | 0.00858138 | 54.2641 | 9924.47 | 0.00 | 11010.47 | 10610.46 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5299.269 | 5299.269 | 0.231775 | 0.00004636 | 151.439 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5299.27 | 5299.27 | 0.231775 | 21.11 | 14.28 | 0.00748866 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00748866 | 47.4373 | 5299.38 | 0.00 | 5712.74 | 5712.74 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 12534.723 | 12534.723 | 0.801502 | 0.00010966 | 292.099 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 12534.72 | 12534.72 | 0.801502 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00759695 | 48.4425 | 8366.33 | 0.00 | 12601.67 | 12601.67 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3482.092 | -999.000 | 0.317627 | 0.00012437 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 3482.09 | 3429.64 | 0.317627 | 21.69 | 15.47 | 0.00856333 | 12.80 | 11.97 | 0.00850000 | 28.36 | 0.00881983 | 18.00 | 0.0000 | 21.11 | 0.00856333 | 54.1515 | 3197.94 | 0.00 | 3530.48 | 3416.30 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1612.096 | 1612.096 | 0.070509 | 0.00001410 | 46.067 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1612.10 | 1612.10 | 0.070509 | 21.11 | 14.36 | 0.00757234 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00757234 | 47.9610 | 1612.13 | 0.00 | 1737.88 | 1737.88 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3112.276 | -999.000 | 0.283286 | 0.00011116 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | 8/21 17:00:00 | 3112.28 | 3059.71 | 0.283286 | 21.69 | 15.48 | 0.00857113 | 12.80 | 11.97 | 0.00850000 | 27.94 | 0.00881916 | 17.86 | 0.0000 | 21.11 | 0.00857113 | 54.2001 | 2852.18 | 0.00 | 3155.48 | 3047.97 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1613.933 | 1613.933 | 0.070589 | 0.00001412 | 46.120 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1613.93 | 1613.93 | 0.070589 | 21.11 | 14.36 | 0.00757282 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00757282 | 47.9640 | 1613.97 | 0.00 | 1739.86 | 1739.86 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 19025.548 | -999.000 | 1.717406 | 0.00067954 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | 8/21 13:40:00 | 19025.55 | 18569.76 | 1.717406 | 21.69 | 15.50 | 0.00860163 | 12.80 | 11.97 | 0.00850000 | 29.23 | 0.00882122 | 18.29 | 0.0000 | 21.11 | 0.00860163 | 54.3910 | 17290.84 | 0.00 | 19288.53 | 18502.19 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 7727.532 | 7727.532 | 0.337983 | 0.00006760 | 220.820 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 7727.53 | 7727.53 | 0.337983 | 21.11 | 14.38 | 0.00758787 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00758787 | 48.0578 | 7727.66 | 0.00 | 8330.48 | 8330.48 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10868.621 | 10868.621 | 1.086282 | 0.00009508 | 238.093 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10868.62 | 10868.62 | 1.086282 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00766908 | 48.8972 | 5218.58 | 0.00 | 10928.77 | 10928.77 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11250.597 | 11250.597 | 1.137952 | 0.00009843 | 246.152 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 11250.60 | 11250.60 | 1.137952 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00767570 | 48.9398 | 5332.15 | 0.00 | 11312.88 | 11312.88 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7546.411 | 7546.411 | 1.164263 | 0.00006602 | 159.397 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 7546.41 | 7546.41 | 1.164263 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00584870 | 37.4067 | 1515.68 | 0.00 | 7588.63 | 7588.63 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7589.304 | 7589.304 | 0.412690 | 0.00006639 | 182.601 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | 7589.30 | 7589.30 | 0.412690 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00771919 | 49.2132 | 5442.67 | 0.00 | 7628.95 | 7628.95 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 484932.302 | -999.000 | 22.785223 | 0.01732066 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 484932.30 | 435121.29 | 22.785223 | 26.76 | 17.78 | 0.00920444 | 10.95 | 10.95 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 51.1799 | 23.99 | 0.00956873 | 50.7107 | 308783.50 | 0.00 | 490131.37 | 419384.14 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 170401.388 | 170401.388 | 6.835567 | 0.00149075 | 2909.131 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 170401.39 | 170401.39 | 6.835567 | -4.20 | -4.20 | 0.00269032 | 16.70 | 13.06 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 170.5997 | 21.22 | 0.00652056 | 41.1005 | 52122.17 | 0.00 | 156987.14 | 156987.14 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 45447.837 | -999.000 | 2.051317 | 0.00162329 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 45447.84 | 43504.21 | 2.051317 | 29.40 | 18.34 | 0.00882150 | 11.92 | 11.61 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 99.9965 | 21.11 | 0.00861245 | 54.4574 | 186702.93 | 0.00 | 45923.42 | 42707.30 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 15340.965 | 15340.965 | 0.615395 | 0.00013421 | 261.904 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 15340.96 | 15340.96 | 0.615395 | -4.20 | -4.20 | 0.00269032 | 16.70 | 13.06 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 333.3216 | 21.11 | 0.00752475 | 47.6621 | 93006.31 | 0.00 | 14133.30 | 14133.30 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 6854.952 | 6854.952 | 1.317077 | 0.00005997 | 142.948 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 1.7141 | 1.748587 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6854.95 | 6854.95 | 1.0000 | 1.56335869 | 1.317077 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.05996400 | 60.00 | 32.22 | 27.78 | 0.000 | 6854.95 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 6893.48 | 6893.48 | 1.56335869 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3585.894 | 3585.894 | 0.243797 | 0.00003137 | 82.685 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 0.8967 | 0.914703 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3585.89 | 3585.89 | 1.0000 | 0.28938505 | 0.243797 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.03136776 | 60.00 | 32.22 | 27.78 | 0.000 | 3585.89 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00749309 | 21.00 | 0.00749309 | 47.7895 | 2318.35 | 0.00 | 3605.11 | 3605.11 | 0.28938505 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.82 | 17.64 | 0.00800000 | 49392.6 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1408.906 | 1408.906 | 0.122984 | 0.00001233 | 31.343 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 0.3523 | 0.359389 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1408.91 | 1408.91 | 1.0000 | 0.14598145 | 0.122984 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01232447 | 60.00 | 32.22 | 27.78 | 0.000 | 1408.91 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00741935 | 21.00 | 0.00741935 | 47.3237 | 769.52 | 0.00 | 1416.56 | 1416.56 | 0.14598145 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.12 | 16.71 | 0.00800000 | 46638.4 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2014.086 | 2014.086 | 0.111975 | 0.00001762 | 48.229 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 0.5036 | 0.513761 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2014.09 | 2014.09 | 1.0000 | 0.13291296 | 0.111975 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01761831 | 60.00 | 32.22 | 27.78 | 0.000 | 2014.09 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00728366 | 21.00 | 0.00728366 | 46.4683 | 1432.08 | 0.00 | 2024.63 | 2024.63 | 0.13291296 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.54 | 18.55 | 0.00800000 | 52167.5 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1159.542 | 1159.542 | 0.053954 | 0.00001014 | 28.972 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 0.2899 | 0.295780 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1159.54 | 1159.54 | 1.0000 | 0.06404242 | 0.053954 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01014314 | 60.00 | 32.22 | 27.78 | 0.000 | 1159.54 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00732126 | 21.00 | 0.00732126 | 46.7054 | 879.09 | 0.00 | 1165.52 | 1165.52 | 0.06404242 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.45 | 19.48 | 0.00800000 | 55133.9 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10616.370 | 10616.370 | 1.679003 | 0.00009288 | 223.882 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 2.6546 | 2.708063 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10616.37 | 10616.37 | 1.0000 | 1.99296164 | 1.679003 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09286716 | 60.00 | 32.22 | 27.78 | 0.000 | 10616.37 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00726278 | 21.00 | 0.00726278 | 46.3376 | 1890.62 | 0.00 | 10675.80 | 10675.80 | 1.99296164 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.85 | 15.17 | 0.00800000 | 42291.5 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10711.652 | 10711.652 | 0.940067 | 0.00009371 | 238.136 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 2.6785 | 2.732368 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10711.65 | 10711.65 | 1.0000 | 1.11585050 | 0.940067 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09370065 | 60.00 | 32.22 | 27.78 | 0.000 | 10711.65 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00754874 | 21.00 | 0.00754874 | 48.1398 | 5823.45 | 0.00 | 10769.83 | 10769.83 | 1.11585050 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.07 | 16.69 | 0.00800000 | 46586.4 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 27139.733 | 27139.733 | 2.589003 | 0.00023743 | 597.494 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 6.7863 | 6.922904 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 27139.73 | 27139.73 | 1.0000 | 3.07312256 | 2.589003 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.23740601 | 60.00 | 32.22 | 27.78 | 0.000 | 27139.73 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00746084 | 21.00 | 0.00746084 | 47.5852 | 13678.68 | 0.00 | 27287.71 | 27287.71 | 3.07312256 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.31 | 16.42 | 0.00800000 | 45814.2 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13348.290 | -999.000 | 1.216678 | 0.00047676 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7639 | 1004.8586 | 1.1870 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.216678 | 1.44418548 | 4197.9300 | 999.8980 | 26.81473915 | 13.37 | 6.70 | 6.67 | 750817.87 | 1.7778 | 1.777800 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 13348.29 | 13138.63 | 1.0000 | 1.44418548 | 1.216678 | 21.69 | 15.47 | 0.00856608 | 43565.0 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.47671244 | 6.70 | 13.37 | 6.67 | 0.000 | 13348.29 | 28.36 | 0.00881983 | 18.00 | 0.00000000 | 0.0000 | 21.11 | 0.00856608 | 21.11 | 0.00856608 | 54.1686 | 12249.79 | 0.00 | 13533.71 | 13087.78 | 1.44418548 | 21.69 | 15.62 | 0.00856608 | 43565.0 | 12.81 | 12.05 | 0.00844377 | 34193.8 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5287.972 | 5287.972 | 0.231281 | 0.00004626 | 151.116 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.216678 | 1.44418548 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 1.3223 | 1.348876 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5287.97 | 5287.97 | 1.0000 | 0.27452838 | 0.231281 | 21.11 | 14.28 | 0.00748764 | 40232.5 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04625677 | 60.00 | 32.22 | 27.78 | 0.000 | 5287.97 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00748764 | 21.11 | 0.00748764 | 47.4309 | 5288.09 | 0.00 | 5700.56 | 5700.56 | 0.27452838 | 16.60 | 12.65 | 0.00748764 | 35637.5 | 36.98 | 19.89 | 0.00748764 | 56402.5 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12029.196 | -999.000 | 1.094323 | 0.00042965 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7770 | 1004.8586 | 1.1870 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.094323 | 1.29895158 | 4197.9300 | 999.8980 | 26.81473915 | 13.37 | 6.70 | 6.67 | 750817.87 | 1.6021 | 1.602116 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | unknown | unknown | unknown | 8/21 16:50:00 | Sensible | 12029.20 | 11820.43 | 1.0000 | 1.29895158 | 1.094323 | 21.69 | 15.48 | 0.00857313 | 43582.9 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.42960316 | 6.70 | 13.37 | 6.67 | 0.000 | 12029.20 | 28.08 | 0.00881938 | 17.91 | 0.00000000 | 0.0000 | 21.11 | 0.00857313 | 21.11 | 0.00857313 | 54.2126 | 11017.88 | 0.00 | 12196.13 | 11775.23 | 1.29895158 | 21.69 | 15.62 | 0.00857313 | 43582.9 | 12.81 | 12.05 | 0.00844479 | 34193.7 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5291.519 | 5291.519 | 0.231436 | 0.00004629 | 151.218 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.094323 | 1.29895158 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 1.3232 | 1.349780 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5291.52 | 5291.52 | 1.0000 | 0.27471253 | 0.231436 | 21.11 | 14.28 | 0.00748799 | 40233.4 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04628780 | 60.00 | 32.22 | 27.78 | 0.000 | 5291.52 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00748799 | 21.11 | 0.00748799 | 47.4331 | 5291.63 | 0.00 | 5704.38 | 5704.38 | 0.27471253 | 16.60 | 12.65 | 0.00748799 | 35638.4 | 36.98 | 19.89 | 0.00748799 | 56403.3 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 87878.746 | -999.000 | 8.147616 | 0.00313877 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6494 | 1004.8586 | 1.1870 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.147616 | 9.67114501 | 4197.9300 | 999.8980 | 26.81473915 | 13.37 | 6.70 | 6.67 | 750817.87 | 11.7044 | 11.704184 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | unknown | unknown | 8/21 13:30:00 | Sensible | 87878.75 | 87783.83 | 1.0000 | 9.67114501 | 8.147616 | 21.69 | 15.42 | 0.00850448 | 43408.9 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 3.13844638 | 6.70 | 13.37 | 6.67 | 0.000 | 87878.75 | 29.14 | 0.00882108 | 18.26 | 0.00000000 | 0.0000 | 21.11 | 0.00850448 | 21.11 | 0.00850448 | 53.7831 | 82035.80 | 0.00 | 89110.13 | 87408.23 | 9.67114501 | 21.69 | 15.56 | 0.00850448 | 43408.9 | 12.84 | 12.05 | 0.00843478 | 34194.9 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30397.663 | 30397.663 | 1.329534 | 0.00026593 | 868.670 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.147616 | 9.67114501 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 7.6010 | 7.753949 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 30397.66 | 30397.66 | 1.0000 | 1.57814422 | 1.329534 | 21.11 | 14.32 | 0.00752391 | 40325.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.26590489 | 60.00 | 32.22 | 27.78 | 0.000 | 30397.66 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00752391 | 21.11 | 0.00752391 | 47.6569 | 30397.98 | 0.00 | 32769.60 | 32769.60 | 1.57814422 | 16.60 | 12.69 | 0.00752391 | 35729.4 | 36.98 | 19.91 | 0.00752391 | 56494.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 58749.357 | -999.000 | 5.052889 | 0.00209835 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1684 | 1004.8586 | 1.1870 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.052889 | 5.99773249 | 4197.9300 | 999.8980 | 26.81473915 | 13.37 | 6.70 | 6.67 | 750817.87 | 7.8247 | 7.824569 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | unknown | unknown | unknown | 8/21 15:00:00 | Sensible | 58749.36 | 54982.31 | 1.0000 | 5.99773249 | 5.052889 | 21.69 | 15.66 | 0.00878368 | 44117.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 2.09813766 | 6.70 | 13.37 | 6.67 | 0.000 | 58749.36 | 29.40 | 0.00882150 | 18.34 | 0.00000000 | 0.0000 | 21.11 | 0.00878368 | 21.11 | 0.00878368 | 55.5264 | 50871.94 | 0.00 | 59541.70 | 54844.74 | 5.99773249 | 21.69 | 15.81 | 0.00878368 | 44117.5 | 12.74 | 12.05 | 0.00847349 | 34190.1 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30479.297 | 30479.297 | 1.333104 | 0.00026665 | 871.003 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.052889 | 5.99773249 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 7.6214 | 7.774773 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 30479.30 | 30479.30 | 1.0000 | 1.58238238 | 1.333104 | 21.11 | 14.32 | 0.00752496 | 40327.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.26661898 | 60.00 | 32.22 | 27.78 | 0.000 | 30479.30 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00752496 | 21.11 | 0.00752496 | 47.6634 | 30479.62 | 0.00 | 32857.61 | 32857.61 | 1.58238238 | 16.60 | 12.69 | 0.00752496 | 35732.0 | 36.98 | 19.91 | 0.00752496 | 56496.7 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11956.415 | -999.000 | 1.087461 | 0.00042705 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7785 | 1004.8586 | 1.1870 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.087461 | 1.29080631 | 4197.9300 | 999.8980 | 26.81473915 | 13.37 | 6.70 | 6.67 | 750817.87 | 1.5925 | 1.592422 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | unknown | unknown | 8/21 10:00:00 | Sensible | 11956.41 | 11746.66 | 1.0000 | 1.29080631 | 1.087461 | 21.69 | 15.48 | 0.00857394 | 43584.9 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.42700390 | 6.70 | 13.37 | 6.67 | 0.000 | 11956.41 | 25.45 | 0.00881519 | 17.01 | 0.00000000 | 0.0000 | 21.11 | 0.00857394 | 21.11 | 0.00857394 | 54.2176 | 10948.80 | 0.00 | 12122.32 | 11701.80 | 1.29080631 | 21.69 | 15.62 | 0.00857394 | 43584.9 | 12.81 | 12.05 | 0.00844490 | 34193.7 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5295.723 | 5295.723 | 0.231620 | 0.00004633 | 151.338 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.087461 | 1.29080631 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 1.3242 | 1.350853 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5295.72 | 5295.72 | 1.0000 | 0.27493076 | 0.231620 | 21.11 | 14.28 | 0.00748832 | 40234.2 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04632457 | 60.00 | 32.22 | 27.78 | 0.000 | 5295.72 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00748832 | 21.11 | 0.00748832 | 47.4352 | 5295.84 | 0.00 | 5708.92 | 5708.92 | 0.27493076 | 16.60 | 12.65 | 0.00748832 | 35639.3 | 36.98 | 19.89 | 0.00748832 | 56404.2 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10859.931 | -999.000 | 0.985723 | 0.00038788 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7924 | 1004.8586 | 1.1870 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.985723 | 1.17004415 | 4197.9300 | 999.8980 | 26.81473915 | 13.37 | 6.70 | 6.67 | 750817.87 | 1.4464 | 1.446387 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | unknown | unknown | unknown | 8/21 09:00:00 | Sensible | 10859.93 | 10650.62 | 1.0000 | 1.17004415 | 0.985723 | 21.69 | 15.49 | 0.00858138 | 43603.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.38784477 | 6.70 | 13.37 | 6.67 | 0.000 | 10859.93 | 23.68 | 0.00881240 | 16.40 | 0.00000000 | 0.0000 | 21.11 | 0.00858138 | 21.11 | 0.00858138 | 54.2641 | 9924.47 | 0.00 | 11010.47 | 10610.46 | 1.17004415 | 21.69 | 15.63 | 0.00858138 | 43603.8 | 12.81 | 12.05 | 0.00844597 | 34193.5 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5299.269 | 5299.269 | 0.231775 | 0.00004636 | 151.439 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.985723 | 1.17004415 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 1.3251 | 1.351757 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5299.27 | 5299.27 | 1.0000 | 0.27511484 | 0.231775 | 21.11 | 14.28 | 0.00748866 | 40235.1 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04635558 | 60.00 | 32.22 | 27.78 | 0.000 | 5299.27 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00748866 | 21.11 | 0.00748866 | 47.4373 | 5299.38 | 0.00 | 5712.74 | 5712.74 | 0.27511484 | 16.60 | 12.65 | 0.00748866 | 35640.1 | 36.98 | 19.89 | 0.00748866 | 56405.1 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12534.723 | 12534.723 | 0.801502 | 0.00010966 | 292.099 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 3.1343 | 3.197404 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 12534.72 | 12534.72 | 1.0000 | 0.95137512 | 0.801502 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.10964804 | 60.00 | 32.22 | 27.78 | 0.000 | 12534.72 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00759695 | 21.00 | 0.00759695 | 48.4425 | 8366.33 | 0.00 | 12601.67 | 12601.67 | 0.95137512 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.59 | 17.90 | 0.00800000 | 50180.5 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3482.092 | -999.000 | 0.317627 | 0.00012437 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7588 | 1004.8586 | 1.1870 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.317627 | 0.37702051 | 4197.9300 | 999.8980 | 26.81473915 | 13.37 | 6.70 | 6.67 | 750817.87 | 0.4638 | 0.463765 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 3482.09 | 3429.64 | 1.0000 | 0.37702051 | 0.317627 | 21.69 | 15.47 | 0.00856333 | 43558.0 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.12435726 | 6.70 | 13.37 | 6.67 | 0.000 | 3482.09 | 28.36 | 0.00881983 | 18.00 | 0.00000000 | 0.0000 | 21.11 | 0.00856333 | 21.11 | 0.00856333 | 54.1515 | 3197.94 | 0.00 | 3530.48 | 3416.30 | 0.37702051 | 21.69 | 15.61 | 0.00856333 | 43558.0 | 12.81 | 12.05 | 0.00844338 | 34193.9 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1612.096 | 1612.096 | 0.070509 | 0.00001410 | 46.067 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.317627 | 0.37702051 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 0.4031 | 0.411220 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1612.10 | 1612.10 | 1.0000 | 0.08369298 | 0.070509 | 21.11 | 14.36 | 0.00757234 | 40447.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01410188 | 60.00 | 32.22 | 27.78 | 0.000 | 1612.10 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00757234 | 21.11 | 0.00757234 | 47.9610 | 1612.13 | 0.00 | 1737.88 | 1737.88 | 0.08369298 | 16.60 | 12.73 | 0.00757234 | 35852.0 | 36.98 | 19.95 | 0.00757234 | 56616.9 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3112.276 | -999.000 | 0.283286 | 0.00011116 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7733 | 1004.8586 | 1.1870 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.283286 | 0.33625748 | 4197.9300 | 999.8980 | 26.81473915 | 13.37 | 6.70 | 6.67 | 750817.87 | 0.4145 | 0.414510 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | unknown | unknown | 8/21 17:00:00 | Sensible | 3112.28 | 3059.71 | 1.0000 | 0.33625748 | 0.283286 | 21.69 | 15.48 | 0.00857113 | 43577.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.11114987 | 6.70 | 13.37 | 6.67 | 0.000 | 3112.28 | 27.94 | 0.00881916 | 17.86 | 0.00000000 | 0.0000 | 21.11 | 0.00857113 | 21.11 | 0.00857113 | 54.2001 | 2852.18 | 0.00 | 3155.48 | 3047.97 | 0.33625748 | 21.69 | 15.62 | 0.00857113 | 43577.8 | 12.81 | 12.05 | 0.00844450 | 34193.7 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1613.933 | 1613.933 | 0.070589 | 0.00001412 | 46.120 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.283286 | 0.33625748 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 0.4036 | 0.411688 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1613.93 | 1613.93 | 1.0000 | 0.08378836 | 0.070589 | 21.11 | 14.36 | 0.00757282 | 40448.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01411795 | 60.00 | 32.22 | 27.78 | 0.000 | 1613.93 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00757282 | 21.11 | 0.00757282 | 47.9640 | 1613.97 | 0.00 | 1739.86 | 1739.86 | 0.08378836 | 16.60 | 12.73 | 0.00757282 | 35853.2 | 36.98 | 19.95 | 0.00757282 | 56618.1 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19025.548 | -999.000 | 1.717406 | 0.00067954 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8300 | 1004.8586 | 1.1870 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.717406 | 2.03854549 | 4197.9300 | 999.8980 | 26.81473915 | 13.37 | 6.70 | 6.67 | 750817.87 | 2.5340 | 2.533929 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | unknown | unknown | 8/21 13:40:00 | Sensible | 19025.55 | 18569.76 | 1.0000 | 2.03854549 | 1.717406 | 21.69 | 15.50 | 0.00860163 | 43655.1 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.67946649 | 6.70 | 13.37 | 6.67 | 0.000 | 19025.55 | 29.23 | 0.00882122 | 18.29 | 0.00000000 | 0.0000 | 21.11 | 0.00860163 | 21.11 | 0.00860163 | 54.3910 | 17290.84 | 0.00 | 19288.53 | 18502.19 | 2.03854549 | 21.69 | 15.65 | 0.00860163 | 43655.1 | 12.80 | 12.05 | 0.00844885 | 34193.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7727.532 | 7727.532 | 0.337983 | 0.00006760 | 220.820 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.717406 | 2.03854549 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 1.9323 | 1.971168 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 7727.53 | 7727.53 | 1.0000 | 0.40118236 | 0.337983 | 21.11 | 14.38 | 0.00758787 | 40487.2 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06759693 | 60.00 | 32.22 | 27.78 | 0.000 | 7727.53 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00758787 | 21.11 | 0.00758787 | 48.0578 | 7727.66 | 0.00 | 8330.48 | 8330.48 | 0.40118236 | 16.60 | 12.75 | 0.00758787 | 35891.3 | 36.98 | 19.96 | 0.00758787 | 56656.1 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10868.621 | 10868.621 | 1.086282 | 0.00009508 | 238.093 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 2.7177 | 2.772408 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10868.62 | 10868.62 | 1.0000 | 1.28940708 | 1.086282 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09507374 | 60.00 | 32.22 | 27.78 | 0.000 | 10868.62 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00766908 | 21.00 | 0.00766908 | 48.8972 | 5218.58 | 0.00 | 10928.77 | 10928.77 | 1.28940708 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.91 | 16.28 | 0.00800000 | 45410.5 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11250.597 | 11250.597 | 1.137952 | 0.00009843 | 246.152 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 2.8132 | 2.869844 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 11250.60 | 11250.60 | 1.0000 | 1.35073840 | 1.137952 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09841509 | 60.00 | 32.22 | 27.78 | 0.000 | 11250.60 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00767570 | 21.00 | 0.00767570 | 48.9398 | 5332.15 | 0.00 | 11312.88 | 11312.88 | 1.35073840 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.81 | 16.25 | 0.00800000 | 45310.1 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7546.411 | 7546.411 | 1.164263 | 0.00006602 | 159.397 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 1.8870 | 1.924967 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 7546.41 | 7546.41 | 1.0000 | 1.38196946 | 1.164263 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06601256 | 60.00 | 32.22 | 27.78 | 0.000 | 7546.41 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.32 | 0.00584870 | 21.00 | 0.00584870 | 37.4067 | 1515.68 | 0.00 | 7588.63 | 7588.63 | 1.38196946 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.99 | 15.22 | 0.00800000 | 42425.9 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7589.304 | 7589.304 | 0.412690 | 0.00006639 | 182.601 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 1.8977 | 1.935908 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | Sensible | 7589.30 | 7589.30 | 1.0000 | 0.48985867 | 0.412690 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06638777 | 60.00 | 32.22 | 27.78 | 0.000 | 7589.30 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00771919 | 21.00 | 0.00771919 | 49.2132 | 5442.67 | 0.00 | 7628.95 | 7628.95 | 0.48985867 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.87 | 18.66 | 0.00800000 | 52508.5 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 484932.302 | -999.000 | 22.785223 | 0.01732066 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9506 | 1004.8586 | 1.1870 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.785223 | 27.04585022 | 4197.9300 | 999.8980 | 26.81473915 | 13.37 | 6.70 | 6.67 | 750817.87 | 64.5872 | 64.587208 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 484932.30 | 435121.29 | 1.0000 | 27.04585022 | 22.785223 | 26.76 | 17.78 | 0.00920444 | 50367.0 | 10.95 | 10.95 | 0.00850000 | 32437.0 | 17.31889136 | 6.70 | 13.37 | 6.67 | 51053.451 | 433878.85 | 29.40 | 0.00882150 | 18.34 | 11.66146000 | 51.1799 | 23.99 | 0.00960627 | 23.99 | 0.00956873 | 50.7107 | 308783.50 | 0.00 | 490131.37 | 419384.14 | 27.04585022 | 26.76 | 17.93 | 0.00920444 | 50367.0 | 11.59 | 11.25 | 0.00816743 | 32244.7 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 170401.388 | 170401.388 | 6.835567 | 0.00149075 | 2909.131 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.785223 | 27.04585022 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 42.6091 | 43.466621 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 170401.39 | 170401.39 | 1.0000 | 8.11375507 | 6.835567 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 1.49059361 | 60.00 | 32.22 | 27.78 | 0.000 | 170401.39 | -4.20 | 0.00269032 | -4.20 | 11.66146000 | 170.5997 | 18.50 | 0.00690725 | 21.22 | 0.00652056 | 41.1005 | 52122.17 | 0.00 | 156987.14 | 156987.14 | 8.11375507 | 2.80 | 0.07 | 0.00269032 | 9555.9 | 21.96 | 9.93 | 0.00269032 | 28904.2 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 45447.837 | -999.000 | 2.051317 | 0.00162329 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2387 | 1004.8586 | 1.1870 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.43480905 | 4197.9300 | 999.8980 | 26.81473915 | 13.37 | 6.70 | 6.67 | 750817.87 | 6.0531 | 6.053111 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | Sensible | 45447.84 | 43504.21 | 1.0000 | 2.43489466 | 2.051317 | 29.40 | 18.34 | 0.00882150 | 52086.5 | 11.92 | 11.61 | 0.00850000 | 33421.2 | 1.62312585 | 6.70 | 13.37 | 6.67 | 2195.006 | 43252.83 | 29.40 | 0.00882150 | 18.34 | 2.05124512 | 99.9965 | 21.11 | 0.00860799 | 21.11 | 0.00861245 | 54.4574 | 186702.93 | 0.00 | 45923.42 | 42707.30 | 2.43489466 | 29.40 | 18.50 | 0.00882150 | 52086.5 | 12.23 | 11.66 | 0.00829812 | 33225.9 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15340.965 | 15340.965 | 0.615395 | 0.00013421 | 261.904 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.43480905 | 4197.9300 | 999.8980 | 3.42928341 | 54.44 | 82.22 | 27.78 | 399917.87 | 3.8360 | 3.913230 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 15340.96 | 15340.96 | 1.0000 | 0.73046840 | 0.615395 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 0.13419576 | 60.00 | 32.22 | 27.78 | 0.000 | 15340.96 | -4.20 | 0.00269032 | -4.20 | 2.05124512 | 333.3216 | 21.11 | 0.00752312 | 21.11 | 0.00752475 | 47.6621 | 93006.31 | 0.00 | 14133.30 | 14133.30 | 0.73046840 | 2.80 | 0.07 | 0.00269032 | 9555.9 | 21.96 | 9.93 | 0.00269032 | 28904.2 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 11.66 | 22.79 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 147.67 | 6729.17 | 0.00 |
RETAIL_1_FLR_1 | 920.17 | 7946.67 | 414.50 |
RETAIL_2_FLR_1 | 444.33 | 7470.33 | 0.00 |
MECH_FLR_1 | 46.33 | 8504.17 | 14.33 |
STORAGE_FLR_1 | 34.17 | 8718.83 | 34.17 |
LAUNDRY_FLR_1 | 7425.50 | 3314.33 | 2746.67 |
CAFE_FLR_1 | 1269.50 | 6725.50 | 35.00 |
LOBBY_FLR_1 | 1469.17 | 5879.17 | 37.83 |
ROOM_1_FLR_3 | 1983.83 | 8396.50 | 1892.50 |
ROOM_2_FLR_3 | 2439.83 | 8573.00 | 2410.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 943.17 | 8760.00 | 943.17 |
ROOM_5_FLR_3 | 1914.83 | 8343.50 | 1882.83 |
ROOM_6_FLR_3 | 2328.33 | 8562.50 | 2321.00 |
CORRIDOR_FLR_3 | 20.00 | 8579.33 | 16.00 |
ROOM_1_FLR_6 | 2704.50 | 8319.83 | 2556.50 |
ROOM_2_FLR_6 | 3101.00 | 8524.17 | 3045.67 |
ROOM_3_MULT9_FLR_6 | 1352.00 | 8201.83 | 1204.83 |
BANQUET_FLR_6 | 4652.17 | 1692.33 | 40.33 |
DINING_FLR_6 | 5975.67 | 773.67 | 24.83 |
KITCHEN_FLR_6 | 8477.67 | 6280.33 | 6248.67 |
CORRIDOR_FLR_6 | 254.00 | 8160.83 | 36.50 |
Facility | 8755.50 | 8760.00 | 7332.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 256.17 | 0.00 | 256.17 |
CAFE_FLR_1 | 0.00 | 0.33 | 0.00 | 0.33 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 5.83 | 0.00 | 5.83 |
ROOM_2_FLR_3 | 0.00 | 4.33 | 0.00 | 4.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.17 | 0.00 | 0.17 |
ROOM_5_FLR_3 | 0.00 | 4.83 | 0.00 | 4.83 |
ROOM_6_FLR_3 | 0.00 | 5.17 | 0.00 | 5.17 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 11.17 | 0.00 | 11.17 |
ROOM_2_FLR_6 | 0.00 | 8.50 | 0.00 | 8.50 |
ROOM_3_MULT9_FLR_6 | 0.00 | 2.50 | 0.00 | 2.50 |
BANQUET_FLR_6 | 0.00 | 36.67 | 0.00 | 36.67 |
DINING_FLR_6 | 0.00 | 51.67 | 0.00 | 51.67 |
KITCHEN_FLR_6 | 0.00 | 384.33 | 0.00 | 384.33 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 474.33 | 0.00 | 474.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 106.50 | 4826.41 | 0.950 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.26 | 10.83 | 265.76 | 3.123 | 0.138 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.25 | 12.54 | 307.76 | 1.367 | 0.046 | 0.000 | 0.000 |
MECH_FLR_1 | 1.53 | 2.65 | 650.80 | 0.583 | 0.051 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.486 | 0.051 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 21.559 | 0.148 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.31 | 142.30 | 748.35 | 4.294 | 0.108 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.35 | 422.44 | 5183.56 | 1.726 | 0.045 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.179 | 0.000 | 0.042 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.473 | 0.178 | 0.000 | 0.044 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.537 | 0.079 | 0.000 | 0.070 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.179 | 0.000 | 0.042 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.473 | 0.178 | 0.000 | 0.044 |
CORRIDOR_FLR_3 | 12.12 | 20.96 | 1186.91 | 0.572 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.473 | 0.179 | 0.000 | 0.049 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.473 | 0.178 | 0.000 | 0.052 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.537 | 0.145 | 0.000 | 0.078 |
BANQUET_FLR_6 | 144.55 | 249.90 | 1010.89 | 4.448 | 0.052 | 0.000 | 0.000 |
DINING_FLR_6 | 144.55 | 249.90 | 1010.89 | 4.837 | 0.052 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.86 | 22.24 | 314.87 | 20.376 | 0.149 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.83 | 22.18 | 1256.16 | 1.114 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 106.50 | 4826.41 | 0.576 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.26 | 10.83 | 265.76 | 1.819 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.25 | 12.54 | 307.76 | 0.797 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.53 | 2.65 | 650.80 | 0.341 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.284 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 11.972 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.31 | 142.30 | 748.35 | 2.604 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.35 | 422.44 | 5183.56 | 1.125 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.457 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.457 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.521 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.457 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.457 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.12 | 20.96 | 1186.91 | 0.334 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.457 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.457 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.519 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.55 | 249.90 | 1010.89 | 2.437 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.55 | 249.90 | 1010.89 | 2.553 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.86 | 22.24 | 314.87 | 8.392 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.83 | 22.18 | 1256.16 | 0.651 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.60 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.26 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.25 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.53 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.86 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.31 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.35 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.12 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.55 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.55 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.86 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.83 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 870.81 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 39370954.07 | 0.00 | 39370954.07 | 0.00 | 39370954.07 | 26946214.98 | 4.16 | 0.83 | 8755.00 | 0.00 |
RETAIL_1_FLR_1 | 7180330.78 | 0.00 | 7180330.78 | 316459.92 | 7496790.69 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3623117.49 | 0.00 | 3623117.49 | 122153.93 | 3745271.41 | 2892943.94 | 169.42 | 64.62 | 8525.96 | 0.00 |
MECH_FLR_1 | 3277192.47 | 0.00 | 3277192.47 | 288699.32 | 3565891.78 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1578060.25 | 0.00 | 1578060.25 | 166563.60 | 1744623.85 | 1821682.01 | 8760.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 57347697.70 | 0.00 | 57347697.70 | 394204.17 | 57741901.87 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 27689624.85 | 0.00 | 27689624.85 | 699552.56 | 28389177.41 | 21330615.53 | 120.48 | 27.31 | 8612.20 | 0.00 |
LOBBY_FLR_1 | 76869761.60 | 0.00 | 76869761.60 | 1998781.45 | 78868543.05 | 59728886.00 | 120.64 | 23.74 | 8615.62 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 43454.58 | 1990330.19 | 183682.98 | 2174013.18 | 1946875.62 | 0.00 | 8064.33 | 695.67 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 45579.52 | 1992227.03 | 183668.97 | 2175896.00 | 1946647.51 | 0.00 | 8064.33 | 695.67 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 47524.69 | 26445411.96 | 51249.61 | 26496661.57 | 26397887.27 | 0.00 | 8081.00 | 679.00 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 45109.91 | 26450215.64 | 51263.63 | 26501479.26 | 26405105.73 | 0.00 | 8082.74 | 677.26 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 43413.08 | 1990288.70 | 183682.98 | 2173971.68 | 1946875.62 | 0.00 | 8064.33 | 695.67 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 45486.87 | 1992134.38 | 183668.97 | 2175803.35 | 1946647.51 | 0.00 | 8064.33 | 695.67 | 0.00 |
CORRIDOR_FLR_3 | 23442973.82 | 0.00 | 23442973.82 | 222109.68 | 23665083.51 | 14972100.18 | 1.96 | 0.39 | 8757.65 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 50743.43 | 537462.34 | 183721.42 | 721183.76 | 486718.90 | 0.00 | 8062.67 | 697.33 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 53684.82 | 540346.70 | 183707.41 | 724054.10 | 486661.88 | 0.00 | 8062.67 | 697.33 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 50631.63 | 3177552.04 | 93998.31 | 3271550.35 | 3126920.42 | 0.00 | 8062.83 | 697.17 | 0.00 |
BANQUET_FLR_6 | 38501713.57 | 0.00 | 38501713.57 | 448601.54 | 38950315.11 | 37458366.31 | 4544.13 | 328.06 | 3887.81 | 0.00 |
DINING_FLR_6 | 41858611.98 | 0.00 | 41858611.98 | 448601.54 | 42307213.52 | 37458366.31 | 3187.98 | 233.42 | 5338.60 | 0.00 |
KITCHEN_FLR_6 | 54947845.65 | 0.00 | 54947845.65 | 401602.39 | 55349448.04 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12086103.84 | 0.00 | 12086103.84 | 393066.01 | 12479169.85 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.45E+10 | 8312078.39 | 0.45E+10 | 18509960.64 | 0.46E+10 | 0.43E+10 | 8760.00 | 8128.32 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.2484 | 0.0000 | 1.2484 | 0.0000 | 1.2484 | 0.8545 | 4.16 | 0.83 | 8755.00 |
RETAIL_1_FLR_1 | 0.2277 | 0.0000 | 0.2277 | 0.0100 | 0.2377 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1149 | 0.0000 | 0.1149 | 0.0039 | 0.1188 | 0.0917 | 169.42 | 64.62 | 8525.96 |
MECH_FLR_1 | 0.1039 | 0.0000 | 0.1039 | 0.0092 | 0.1131 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0500 | 0.0000 | 0.0500 | 0.0053 | 0.0553 | 0.0578 | 8760.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 1.8185 | 0.0000 | 1.8185 | 0.0125 | 1.8310 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.8780 | 0.0000 | 0.8780 | 0.0222 | 0.9002 | 0.6764 | 120.48 | 27.31 | 8612.20 |
LOBBY_FLR_1 | 2.4375 | 0.0000 | 2.4375 | 0.0634 | 2.5009 | 1.8940 | 120.64 | 23.74 | 8615.62 |
ROOM_1_FLR_3 | 0.0617 | 0.0014 | 0.0631 | 0.0058 | 0.0689 | 0.0617 | 0.00 | 8064.33 | 695.67 |
ROOM_2_FLR_3 | 0.0617 | 0.0014 | 0.0632 | 0.0058 | 0.0690 | 0.0617 | 0.00 | 8064.33 | 695.67 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0014 | 0.8387 | 0.0016 | 0.8404 | 0.8373 | 0.00 | 8082.74 | 677.26 |
ROOM_5_FLR_3 | 0.0617 | 0.0014 | 0.0631 | 0.0058 | 0.0689 | 0.0617 | 0.00 | 8064.33 | 695.67 |
ROOM_6_FLR_3 | 0.0617 | 0.0014 | 0.0632 | 0.0058 | 0.0690 | 0.0617 | 0.00 | 8064.33 | 695.67 |
CORRIDOR_FLR_3 | 0.7434 | 0.0000 | 0.7434 | 0.0070 | 0.7504 | 0.4748 | 1.96 | 0.39 | 8757.65 |
ROOM_1_FLR_6 | 0.0154 | 0.0016 | 0.0170 | 0.0058 | 0.0229 | 0.0154 | 0.00 | 8062.67 | 697.33 |
ROOM_2_FLR_6 | 0.0154 | 0.0017 | 0.0171 | 0.0058 | 0.0230 | 0.0154 | 0.00 | 8062.67 | 697.33 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0016 | 0.1008 | 0.0030 | 0.1037 | 0.0992 | 0.00 | 8062.83 | 697.17 |
BANQUET_FLR_6 | 1.2209 | 0.0000 | 1.2209 | 0.0142 | 1.2351 | 1.1878 | 4544.13 | 328.06 | 3887.81 |
DINING_FLR_6 | 1.3273 | 0.0000 | 1.3273 | 0.0142 | 1.3416 | 1.1878 | 3187.98 | 233.42 | 5338.60 |
KITCHEN_FLR_6 | 1.7424 | 0.0000 | 1.7424 | 0.0127 | 1.7551 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3832 | 0.0000 | 0.3832 | 0.0125 | 0.3957 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 80.0721 | 0.1490 | 80.2212 | 0.4634 | 80.6846 | 73.9670 | 8760.00 | 8128.32 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.55E+09 | 0.00 | 0.55E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 91145268.87 | 425628.52 | 91570897.38 | 64690340.46 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 17.3310 | 0.0000 | 17.3310 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 2.8902 | 0.0135 | 2.9037 | 2.0513 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 5048.63 | 3587.86 | 0.00 | 123.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 7343.21 | 1416.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 16.4324 | 18.6337 | 0.0000 | 16.4979 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 2.8903 | 2.8918 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1318 |
Defaulted Fields | 1181 |
Fields with Defaults | 4005 |
Autosized Fields | 350 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4844.08 | 75844.81 | 20-NOV-03:20 | 370048.64 | 10-AUG-19:30 |
Electricity:Building | 2518.76 | 32511.05 | 01-JUL-05:00 | 151906.32 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 323.72 | 3705.45 | 02-JAN-02:10 | 24299.15 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2511.67 | 32369.91 | 01-JUL-05:00 | 151664.99 | 02-JAN-20:10 |
InteriorLights:Electricity | 766.66 | 6678.11 | 01-JUL-05:00 | 62892.57 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 173.46 | 1576.23 | 02-JAN-02:10 | 14185.34 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 766.66 | 6678.11 | 01-JUL-05:00 | 62892.57 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 766.66 | 6678.11 | 01-JUL-05:00 | 62892.57 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 173.46 | 1576.23 | 02-JAN-02:10 | 14185.34 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 766.66 | 6678.11 | 01-JUL-05:00 | 62892.57 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.80 | 222.61 | 02-JAN-02:10 | 1390.02 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.61 | 78.27 | 02-JAN-02:10 | 704.41 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.61 | 78.27 | 02-JAN-02:10 | 704.41 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.77 | 257.78 | 02-JAN-02:10 | 1609.65 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.97 | 90.64 | 02-JAN-02:10 | 815.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.97 | 90.64 | 02-JAN-02:10 | 815.72 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 29.11 | 327.88 | 02-JAN-02:10 | 2199.84 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 16.64 | 151.16 | 02-JAN-02:10 | 1360.40 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 16.64 | 151.16 | 02-JAN-02:10 | 1360.40 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.38 | 76.28 | 02-JAN-02:10 | 469.87 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.78 | 25.30 | 02-JAN-02:10 | 227.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.78 | 25.30 | 02-JAN-02:10 | 227.72 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.30 | 1002.39 | 02-JAN-02:10 | 4930.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.37 | 39.69 | 02-JAN-02:10 | 357.21 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.37 | 39.69 | 02-JAN-02:10 | 357.21 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 32.29 | 322.63 | 03-JUN-05:00 | 2727.18 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 17.95 | 119.42 | 03-JUN-05:00 | 1761.91 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 17.95 | 119.42 | 03-JUN-05:00 | 1761.91 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 270.92 | 3172.15 | 01-JUL-05:00 | 20294.39 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 121.92 | 1060.74 | 01-JUL-05:00 | 10265.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 121.92 | 1060.74 | 01-JUL-05:00 | 10265.18 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 18.66 | 264.62 | 01-JAN-02:10 | 1227.54 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 18.66 | 264.59 | 01-JAN-02:10 | 1227.39 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 304.77 | 4565.05 | 01-JAN-02:10 | 20923.25 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 76.02 | 643.59 | 01-JAN-02:10 | 5851.22 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 76.02 | 643.59 | 01-JAN-02:10 | 5851.22 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 304.86 | 4566.30 | 01-JAN-02:10 | 20928.98 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 76.04 | 643.77 | 01-JAN-02:10 | 5852.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 76.04 | 643.77 | 01-JAN-02:10 | 5852.82 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 18.66 | 264.62 | 01-JAN-02:10 | 1227.54 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 18.66 | 264.59 | 01-JAN-02:10 | 1227.39 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.66 | 66.15 | 01-JAN-02:10 | 306.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.50 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.50 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.66 | 66.15 | 01-JAN-02:10 | 306.85 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.49 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.49 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.10 | 540.75 | 01-JAN-02:10 | 2478.43 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 9.00 | 76.24 | 01-JAN-02:10 | 693.10 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 9.00 | 76.24 | 01-JAN-02:10 | 693.10 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 210.51 | 2524.33 | 13-MAY-05:00 | 9841.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 34.65 | 275.03 | 13-MAY-05:00 | 3094.06 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 34.65 | 275.03 | 13-MAY-05:00 | 3094.06 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 210.51 | 2524.33 | 13-MAY-05:00 | 9841.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 34.65 | 275.03 | 13-MAY-05:00 | 3094.06 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 34.65 | 275.03 | 13-MAY-05:00 | 3094.06 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 454.16 | 6253.02 | 02-JAN-02:10 | 18944.06 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.33 | 121.09 | 02-JAN-02:10 | 1089.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.33 | 121.09 | 02-JAN-02:10 | 1089.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1745.01 | 25691.80 | 02-JAN-02:10 | 89475.41 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1745.01 | 25691.80 | 02-JAN-02:10 | 89475.41 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 62.09 | 1116.23 | 11-FEB-23:30 | 3445.44 | 31-MAR-06:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 694.17 | 2595.49 | 26-APR-02:30 | 157723.56 | 10-AUG-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.50 | 0.00 | 01-JAN-11:10 | 2034.09 | 15-NOV-11:40 |
MedTempRefrigeration:Refrigeration:Electricity | 34.50 | 973.22 | 19-FEB-04:10 | 1245.48 | 06-MAR-09:10 |
Fans:Electricity | 543.37 | 12463.13 | 08-OCT-04:50 | 41298.23 | 31-JAN-22:50 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 769.85 | 13745.78 | 01-OCT-05:00 | 48340.39 | 07-FEB-20:40 |
ExteriorEquipment:Electricity | 651.48 | 9618.58 | 02-JAN-02:20 | 39726.11 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 32.45 | 553.72 | 03-JUN-05:00 | 1868.65 | 25-JAN-21:10 |
ElectricityPurchased:Facility | 4844.08 | 75844.81 | 20-NOV-03:20 | 370048.64 | 10-AUG-19:30 |
ElectricityPurchased:Plant | 4844.08 | 75844.81 | 20-NOV-03:20 | 370048.64 | 10-AUG-19:30 |
Cogeneration:ElectricityPurchased | 4844.08 | 75844.81 | 20-NOV-03:20 | 370048.64 | 10-AUG-19:30 |
General:Cogeneration:ElectricityPurchased | 4844.08 | 75844.81 | 20-NOV-03:20 | 370048.64 | 10-AUG-19:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4844.08 | 75844.81 | 20-NOV-03:20 | 370048.64 | 10-AUG-19:30 |
ElectricityNet:Plant | 4844.08 | 75844.81 | 20-NOV-03:20 | 370048.64 | 10-AUG-19:30 |
Cogeneration:ElectricityNet | 4844.08 | 75844.81 | 20-NOV-03:20 | 370048.64 | 10-AUG-19:30 |
General:Cogeneration:ElectricityNet | 4844.08 | 75844.81 | 20-NOV-03:20 | 370048.64 | 10-AUG-19:30 |
General:Fans:Electricity | 543.37 | 12463.13 | 08-OCT-04:50 | 41298.23 | 31-JAN-22:50 |
ExteriorLights:Electricity | 242.27 | 0.00 | 01-JAN-08:10 | 15448.40 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 242.27 | 0.00 | 01-JAN-08:10 | 15448.40 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 194.02 | 0.00 | 25-FEB-11:40 | 9938.94 | 01-JAN-10:10 |
General:HeatRecovery:Electricity | 194.02 | 0.00 | 25-FEB-11:40 | 9938.94 | 01-JAN-10:10 |
WaterSystems:Electricity | 90.74 | 1086.57 | 13-SEP-00:30 | 4738.61 | 31-MAY-18:10 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.57 | 13-SEP-00:30 | 4738.61 | 31-MAY-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 425.63 | 0.00 | 01-JAN-00:20 | 142582.39 | 10-AUG-18:10 |
General:Cooling:Electricity | 425.63 | 0.00 | 01-JAN-00:20 | 142582.39 | 10-AUG-18:10 |
Pumps:Electricity | 122.81 | 47.91 | 20-APR-10:10 | 8225.48 | 10-AUG-18:10 |
General:Pumps:Electricity | 122.81 | 47.91 | 20-APR-10:10 | 8225.48 | 10-AUG-18:10 |
WIRED_LTG_ELECTRICITY | 26.99 | 0.00 | 01-JAN-00:10 | 2213.82 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5643.03 | 29270.80 | 28-APR-01:10 | 531360.57 | 22-JAN-18:50 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3854.20 | 15908.90 | 14-MAY-10:10 | 440859.39 | 09-FEB-21:10 |
WaterSystems:NaturalGas | 3155.64 | 15908.90 | 02-JAN-16:10 | 286457.09 | 20-APR-20:40 |
Water Heater:WaterSystems:NaturalGas | 3155.64 | 15908.90 | 02-JAN-16:10 | 286457.09 | 20-APR-20:40 |
Heating:NaturalGas | 698.56 | 0.00 | 06-FEB-13:30 | 186550.53 | 23-NOV-11:50 |
Boiler:Heating:NaturalGas | 698.56 | 0.00 | 06-FEB-13:30 | 186550.53 | 23-NOV-11:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 1263.41 | 0.00 | 01-JAN-00:20 | 467046.88 | 10-AUG-18:10 |
PlantLoopCoolingDemand:HVAC | 1263.41 | 0.00 | 01-JAN-00:20 | 467046.88 | 10-AUG-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 1263.41 | 0.00 | 01-JAN-00:20 | 467046.88 | 10-AUG-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-21:30 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-21:30 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-21:30 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 03-JAN-01:50 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-21:30 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-21:30 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-21:30 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 03-JAN-01:50 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:30 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 13559.56 | 142647.47 | 11-JAN-14:40 | 2007522.18 | 10-AUG-18:10 |
EnergyTransfer:Building | 4954.08 | 48904.71 | 16-MAR-09:40 | 343619.54 | 10-AUG-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 711.05 | 8188.30 | 22-APR-01:10 | 36359.89 | 13-AUG-10:40 |
Refrigeration:EnergyTransfer | 184.02 | 4025.83 | 11-FEB-23:20 | 10656.68 | 31-MAR-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.01 | 2012.91 | 11-FEB-23:20 | 5328.34 | 31-MAR-06:20 |
General:Refrigeration:EnergyTransfer | 92.01 | 2012.91 | 11-FEB-23:20 | 5328.34 | 31-MAR-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.01 | 2012.91 | 11-FEB-23:20 | 5328.34 | 31-MAR-06:20 |
EnergyTransfer:Plant | 4509.93 | 14373.39 | 28-SEP-02:40 | 1126005.84 | 10-AUG-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.63 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 70.38 | 1869.65 | 19-FEB-04:10 | 2686.44 | 06-MAR-09:10 |
EnergyTransfer:Zone:BASEMENT | 413.74 | 1701.82 | 16-MAR-09:40 | 23902.51 | 10-NOV-22:40 |
Heating:EnergyTransfer | 122.91 | 0.00 | 01-JAN-08:50 | 74256.57 | 26-DEC-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.02 | 0.00 | 01-JAN-00:10 | 634.67 | 17-APR-07:50 |
General:Heating:EnergyTransfer | 122.91 | 0.00 | 01-JAN-08:50 | 74256.57 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.02 | 0.00 | 01-JAN-00:10 | 634.67 | 17-APR-07:50 |
Cooling:EnergyTransfer | 4739.16 | 38468.48 | 16-MAR-09:40 | 340013.54 | 10-AUG-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 413.72 | 1701.82 | 16-MAR-09:40 | 23902.51 | 10-NOV-22:40 |
General:Cooling:EnergyTransfer | 4739.16 | 38468.48 | 16-MAR-09:40 | 340013.54 | 10-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 413.72 | 1701.82 | 16-MAR-09:40 | 23902.51 | 10-NOV-22:40 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 40.44 | 0.02 | 19-DEC-06:50 | 4487.61 | 04-OCT-12:50 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.54 | 0.00 | 01-JAN-00:10 | 761.16 | 19-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.54 | 0.00 | 01-JAN-00:10 | 761.16 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 39.91 | 0.00 | 01-JAN-02:10 | 4487.61 | 04-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 39.91 | 0.00 | 01-JAN-02:10 | 4487.61 | 04-OCT-12:50 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 33.90 | 22.51 | 16-MAR-09:40 | 2121.77 | 10-AUG-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.02 | 0.00 | 01-JAN-00:10 | 176.94 | 23-NOV-18:30 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.02 | 0.00 | 01-JAN-00:10 | 176.94 | 23-NOV-18:30 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 33.87 | 18.36 | 04-DEC-09:40 | 2121.77 | 10-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 33.87 | 18.36 | 04-DEC-09:40 | 2121.77 | 10-AUG-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 27.18 | 0.43 | 26-DEC-14:00 | 1738.30 | 10-AUG-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 191.74 | 23-NOV-18:30 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 191.74 | 23-NOV-18:30 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 27.12 | 0.00 | 01-JAN-09:30 | 1738.30 | 10-AUG-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 27.12 | 0.00 | 01-JAN-09:30 | 1738.30 | 10-AUG-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 11.88 | 0.03 | 14-FEB-15:20 | 676.97 | 10-AUG-10:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.07 | 0.00 | 01-JAN-00:10 | 166.69 | 16-JAN-17:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.07 | 0.00 | 01-JAN-00:10 | 166.69 | 16-JAN-17:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 11.81 | 0.00 | 01-JAN-09:30 | 676.97 | 10-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 11.81 | 0.00 | 01-JAN-09:30 | 676.97 | 10-AUG-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 589.94 | 6147.27 | 20-MAY-03:40 | 38867.68 | 08-FEB-21:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 529.67 | 13-OCT-01:50 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 529.67 | 13-OCT-01:50 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 589.93 | 6147.27 | 20-MAY-03:40 | 38867.68 | 08-FEB-21:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 589.93 | 6147.27 | 20-MAY-03:40 | 38867.68 | 08-FEB-21:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 237.69 | 284.77 | 04-DEC-09:40 | 15597.68 | 04-OCT-12:50 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.20 | 0.00 | 01-JAN-00:10 | 1223.24 | 17-APR-07:50 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.20 | 0.00 | 01-JAN-00:10 | 1223.24 | 17-APR-07:50 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 237.49 | 0.00 | 16-MAR-09:40 | 15597.68 | 04-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 237.49 | 0.00 | 16-MAR-09:40 | 15597.68 | 04-OCT-12:50 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 758.64 | 919.35 | 16-MAR-09:40 | 40992.29 | 10-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.19 | 0.00 | 01-JAN-00:10 | 3245.13 | 23-NOV-18:30 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.19 | 0.00 | 01-JAN-00:10 | 3245.13 | 23-NOV-18:30 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 758.45 | 919.35 | 16-MAR-09:40 | 40992.29 | 10-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 758.45 | 919.35 | 16-MAR-09:40 | 40992.29 | 10-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 53.47 | 0.00 | 08-FEB-21:10 | 12740.30 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 14.59 | 0.00 | 01-JAN-08:10 | 5154.96 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 14.59 | 0.00 | 01-JAN-08:10 | 5154.96 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 38.88 | 0.00 | 01-JAN-00:10 | 12740.30 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 38.88 | 0.00 | 01-JAN-00:10 | 12740.30 | 10-AUG-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 49.08 | 0.03 | 21-OCT-19:00 | 11970.38 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 17.81 | 0.00 | 01-JAN-08:10 | 5223.79 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 17.81 | 0.00 | 01-JAN-08:10 | 5223.79 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 31.27 | 0.00 | 01-JAN-00:10 | 11970.38 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 31.27 | 0.00 | 01-JAN-00:10 | 11970.38 | 10-AUG-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 335.98 | 0.69 | 22-FEB-03:30 | 63432.77 | 04-OCT-12:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 7.76 | 0.00 | 01-JAN-07:50 | 12428.21 | 19-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 7.76 | 0.00 | 01-JAN-07:50 | 12428.21 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 328.23 | 0.00 | 01-JAN-00:10 | 63432.77 | 04-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 328.23 | 0.00 | 01-JAN-00:10 | 63432.77 | 04-OCT-12:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 321.87 | 0.95 | 10-NOV-23:40 | 57332.03 | 24-JUL-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 22.43 | 0.00 | 01-JAN-07:10 | 33434.37 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 22.43 | 0.00 | 01-JAN-07:10 | 33434.37 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 299.44 | 0.00 | 01-JAN-00:10 | 57332.03 | 24-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 299.44 | 0.00 | 01-JAN-00:10 | 57332.03 | 24-JUL-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 51.85 | 0.04 | 07-DEC-15:20 | 10817.29 | 10-AUG-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 14.64 | 0.00 | 01-JAN-08:10 | 5147.71 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 14.64 | 0.00 | 01-JAN-08:10 | 5147.71 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 37.22 | 0.00 | 01-JAN-00:10 | 10817.29 | 10-AUG-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 37.22 | 0.00 | 01-JAN-00:10 | 10817.29 | 10-AUG-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 46.93 | 0.09 | 31-DEC-13:30 | 10263.25 | 10-AUG-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 17.75 | 0.00 | 01-JAN-08:10 | 5220.19 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 17.75 | 0.00 | 01-JAN-08:10 | 5220.19 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 29.18 | 0.00 | 01-JAN-00:10 | 10263.25 | 10-AUG-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 29.18 | 0.00 | 01-JAN-00:10 | 10263.25 | 10-AUG-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 182.07 | 0.37 | 30-NOV-15:40 | 10325.62 | 13-AUG-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.56 | 0.00 | 01-JAN-00:10 | 1608.22 | 04-DEC-09:40 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.56 | 0.00 | 01-JAN-00:10 | 1608.22 | 04-DEC-09:40 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 181.51 | 0.00 | 01-JAN-09:30 | 10325.62 | 13-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 181.51 | 0.00 | 01-JAN-09:30 | 10325.62 | 13-AUG-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 15.10 | 0.00 | 13-MAR-19:40 | 3449.97 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.84 | 0.00 | 01-JAN-08:10 | 1672.36 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.84 | 0.00 | 01-JAN-08:10 | 1672.36 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 9.26 | 0.00 | 01-JAN-00:10 | 3449.97 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 9.26 | 0.00 | 01-JAN-00:10 | 3449.97 | 10-AUG-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 14.24 | 0.01 | 29-JAN-15:00 | 3150.65 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.96 | 0.00 | 01-JAN-08:10 | 1684.35 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.96 | 0.00 | 01-JAN-08:10 | 1684.35 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.28 | 0.00 | 01-JAN-00:10 | 3150.65 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.28 | 0.00 | 01-JAN-00:10 | 3150.65 | 10-AUG-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 78.89 | 0.11 | 16-NOV-00:40 | 18355.28 | 14-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 13.17 | 0.00 | 01-JAN-08:10 | 7512.25 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 13.17 | 0.00 | 01-JAN-08:10 | 7512.25 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 65.72 | 0.00 | 01-JAN-00:10 | 18355.28 | 14-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 65.72 | 0.00 | 01-JAN-00:10 | 18355.28 | 14-SEP-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 423.27 | 2131.20 | 04-DEC-09:40 | 22656.86 | 17-APR-22:00 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 166.40 | 03-MAR-01:00 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 166.40 | 03-MAR-01:00 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 423.27 | 2131.20 | 04-DEC-09:40 | 22656.86 | 17-APR-22:00 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 423.27 | 2131.20 | 04-DEC-09:40 | 22656.86 | 17-APR-22:00 |
EnergyTransfer:Zone:DINING_FLR_6 | 465.41 | 3047.92 | 04-DEC-09:40 | 23704.66 | 24-JUL-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 58.67 | 03-MAR-01:00 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 58.67 | 03-MAR-01:00 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 465.41 | 3047.92 | 04-DEC-09:40 | 23704.66 | 24-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 465.41 | 3047.92 | 04-DEC-09:40 | 23704.66 | 24-JUL-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 17.15 | 13-OCT-01:50 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 17.15 | 13-OCT-01:50 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 619.04 | 6005.18 | 22-APR-01:10 | 31272.16 | 13-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 619.04 | 6005.18 | 22-APR-01:10 | 31272.16 | 13-AUG-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 91.45 | 2.24 | 08-JAN-03:20 | 6834.73 | 10-AUG-14:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.31 | 0.00 | 01-JAN-00:10 | 763.54 | 19-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.31 | 0.00 | 01-JAN-00:10 | 763.54 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 91.14 | 0.00 | 01-JAN-09:30 | 6834.73 | 10-AUG-14:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 91.14 | 0.00 | 01-JAN-09:30 | 6834.73 | 10-AUG-14:20 |
PlantLoopHeatingDemand:Facility | 1260.77 | 9491.03 | 11-AUG-01:50 | 191112.97 | 24-JAN-07:20 |
PlantLoopHeatingDemand:Plant | 764.25 | 9491.03 | 11-AUG-01:50 | 54598.14 | 09-FEB-07:40 |
WaterSystems:PlantLoopHeatingDemand | 764.25 | 9491.03 | 11-AUG-01:50 | 54598.14 | 09-FEB-07:40 |
General:WaterSystems:PlantLoopHeatingDemand | 764.25 | 9491.03 | 11-AUG-01:50 | 54598.14 | 09-FEB-07:40 |
EnergyTransfer:HVAC | 4095.55 | 130.15 | 21-OCT-13:40 | 539197.22 | 10-AUG-18:10 |
HeatingCoils:EnergyTransfer | 496.52 | 0.00 | 07-FEB-15:10 | 154696.00 | 26-JAN-16:20 |
PlantLoopHeatingDemand:HVAC | 496.52 | 0.00 | 07-FEB-15:10 | 154696.00 | 26-JAN-16:20 |
HeatingCoils:PlantLoopHeatingDemand | 496.52 | 0.00 | 07-FEB-15:10 | 154696.00 | 26-JAN-16:20 |
CoolingCoils:EnergyTransfer | 1263.41 | 0.00 | 01-JAN-00:20 | 467046.88 | 10-AUG-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 2317.58 | 0.00 | 25-FEB-11:40 | 384704.88 | 19-FEB-06:30 |
HeatRecoveryForCooling:EnergyTransfer | 18.04 | 0.00 | 01-JAN-00:10 | 85760.12 | 29-AUG-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 764.25 | 9491.03 | 11-AUG-01:50 | 54598.14 | 09-FEB-07:40 |
WaterUse:WaterSystems:EnergyTransfer | 764.25 | 9491.03 | 11-AUG-01:50 | 54598.14 | 09-FEB-07:40 |
Boilers:EnergyTransfer | 490.58 | 0.00 | 06-FEB-13:30 | 146683.08 | 26-JAN-16:20 |
Chillers:EnergyTransfer | 1368.73 | 0.00 | 01-JAN-00:20 | 474720.90 | 10-AUG-18:10 |
HeatRejection:EnergyTransfer | 1794.36 | 0.00 | 01-JAN-00:20 | 617303.29 | 10-AUG-18:10 |
General:HeatRejection:EnergyTransfer | 1794.36 | 0.00 | 01-JAN-00:20 | 617303.29 | 10-AUG-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.017 | -413.724 | 0.000 | 0.000 | 137.851 | 173.462 | 150.255 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -47.860 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.539 | -39.906 | 0.000 | 0.000 | 15.894 | 8.614 | 10.186 | 23.204 | 0.000 | 0.030 | 0.000 | 0.000 | -10.068 | 0.000 | -3.972 | -4.520 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.021 | -33.875 | 0.000 | 0.000 | 17.033 | 9.975 | 11.795 | 0.000 | 0.000 | 0.011 | 0.000 | 0.000 | 0.000 | 0.000 | -1.700 | -3.260 |
MECH_FLR_1 | 0.000 | 0.000 | 0.054 | -27.123 | 0.000 | 0.000 | 3.731 | 16.635 | 12.471 | 0.000 | 0.000 | 0.029 | 0.000 | 0.000 | 0.000 | 0.000 | -3.839 | -1.958 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.069 | -11.815 | 0.000 | 0.000 | 2.907 | 2.785 | 3.598 | 0.000 | 0.000 | 0.018 | 4.612 | 0.000 | 0.000 | 0.000 | -2.174 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.009 | -589.931 | 0.000 | 0.000 | 11.193 | 4.368 | 658.131 | 0.000 | 0.000 | 0.042 | 0.000 | 0.000 | 0.000 | 0.000 | -5.747 | -78.065 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.201 | -237.491 | 0.000 | 0.000 | 197.654 | 17.947 | 14.341 | 64.408 | 0.000 | 0.058 | 0.000 | 0.000 | -30.235 | 0.000 | -9.434 | -17.448 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.191 | -758.456 | 0.000 | 0.000 | 558.948 | 121.918 | 148.998 | 84.531 | 0.000 | 0.165 | 0.000 | 0.000 | -42.309 | 0.000 | -28.721 | -85.266 |
ROOM_1_FLR_3 | 19.208 | -29.077 | 0.000 | -14.422 | 0.000 | 0.000 | 9.749 | 6.366 | 12.292 | 44.048 | 0.000 | 0.153 | 0.000 | 0.000 | -22.885 | 0.000 | -9.748 | -15.683 |
ROOM_2_FLR_3 | 22.939 | -22.264 | 0.000 | -14.126 | 0.000 | 0.000 | 9.776 | 6.366 | 12.291 | 31.020 | 0.000 | 0.157 | 0.000 | 0.000 | -23.117 | 0.000 | -9.660 | -13.381 |
ROOM_3_MULT19_FLR_3 | 16.434 | -120.006 | 0.000 | -216.893 | 0.000 | 0.000 | 0.000 | 76.021 | 228.754 | 275.756 | 0.000 | 0.375 | 0.000 | 0.000 | -129.135 | 0.000 | -70.946 | -60.359 |
ROOM_4_MULT19_FLR_3 | 58.597 | -143.496 | 0.000 | -192.114 | 0.000 | 0.000 | 185.677 | 76.042 | 228.817 | 77.377 | 0.000 | 1.709 | 0.000 | 0.000 | -127.783 | 0.000 | -59.223 | -105.601 |
ROOM_5_FLR_3 | 19.256 | -27.359 | 0.000 | -14.478 | 0.000 | 0.000 | 9.745 | 6.366 | 12.292 | 42.079 | 0.000 | 0.155 | 0.000 | 0.000 | -22.422 | 0.000 | -9.762 | -15.871 |
ROOM_6_FLR_3 | 22.914 | -20.122 | 0.000 | -14.217 | 0.000 | 0.000 | 9.770 | 6.366 | 12.291 | 28.889 | 0.000 | 0.159 | 0.000 | 0.000 | -22.527 | 0.000 | -9.685 | -13.837 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.561 | -181.509 | 0.000 | 0.000 | 119.067 | 109.603 | 0.000 | 39.539 | 0.000 | 0.081 | 0.000 | 0.000 | -29.975 | 0.000 | -11.695 | -45.672 |
ROOM_1_FLR_6 | 7.195 | -7.042 | 0.000 | -3.573 | 0.000 | 0.000 | 2.441 | 1.592 | 3.073 | 10.953 | 0.000 | 0.039 | 0.000 | 0.000 | -5.662 | 0.000 | -2.461 | -6.554 |
ROOM_2_FLR_6 | 8.447 | -5.271 | 0.000 | -3.501 | 0.000 | 0.000 | 2.447 | 1.591 | 3.073 | 7.719 | 0.000 | 0.040 | 0.000 | 0.000 | -5.709 | 0.000 | -2.443 | -6.396 |
ROOM_3_MULT9_FLR_6 | 19.205 | -48.157 | 0.000 | -23.594 | 0.000 | 0.000 | 21.877 | 9.005 | 27.097 | 59.866 | 0.000 | 0.247 | 0.000 | 0.000 | -26.732 | 0.000 | -12.245 | -26.570 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -423.276 | 0.000 | 0.000 | 315.907 | 34.655 | 175.857 | 7.390 | 0.000 | 0.029 | 0.000 | 0.000 | -18.264 | 0.000 | -6.946 | -85.352 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -465.412 | 0.000 | 0.000 | 314.763 | 34.655 | 175.857 | 7.179 | 0.000 | 0.029 | 0.000 | 0.000 | -18.818 | 0.000 | -7.002 | -41.250 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -619.031 | 0.000 | 0.000 | 28.235 | 13.327 | 550.372 | 19.553 | 0.000 | 0.026 | 26.240 | 0.000 | -12.444 | 0.000 | -6.279 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.307 | -91.140 | 0.000 | 0.000 | 31.643 | 28.999 | 0.000 | 19.335 | 0.000 | 0.028 | 29.530 | 0.000 | -13.522 | 0.000 | -5.180 | -0.000 |
Total Facility | 194.194 | -422.794 | 1.969 | -4389.605 | 0.000 | 0.000 | 2006.308 | 766.657 | 2451.839 | 842.846 | 0.000 | 3.579 | 60.382 | 0.000 | -561.608 | 0.000 | -278.863 | -674.906 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 29-NOV-21:48 | 0.00 | 0.00 | 0.00 | -37074.43 | 0.00 | 0.00 | 5924.42 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 8959.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 12-FEB-12:55 | 0.00 | 0.00 | 0.00 | -6214.05 | 0.00 | 0.00 | 212.49 | 234.80 | 288.68 | 7147.62 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -219.13 | -1450.40 |
RETAIL_2_FLR_1 | 24-APR-23:34 | 0.00 | 0.00 | 0.00 | -2175.35 | 0.00 | 0.00 | 809.79 | 181.27 | 250.72 | 0.00 | 0.00 | 0.00 | 1009.39 | 0.00 | -0.00 | 0.00 | -75.82 | 0.00 |
MECH_FLR_1 | 18-MAY-06:25 | 0.00 | 0.00 | 0.00 | -1910.37 | 0.00 | 0.00 | 81.13 | 755.78 | 530.18 | 0.00 | 0.00 | 0.00 | 727.68 | 0.00 | -0.00 | 0.00 | -184.38 | 0.00 |
STORAGE_FLR_1 | 18-MAY-06:25 | 0.00 | 0.00 | 0.00 | -894.05 | 0.00 | 0.00 | 63.96 | 126.51 | 152.94 | 0.00 | 0.00 | 0.00 | 654.37 | 0.00 | -0.00 | 0.00 | -103.73 | 0.00 |
LAUNDRY_FLR_1 | 07-FEB-20:01 | 0.00 | 0.00 | 0.00 | -52365.77 | 0.00 | 0.00 | 337.87 | 357.21 | 44299.38 | 0.00 | 0.00 | 0.00 | 7692.81 | 0.00 | -0.00 | 0.00 | -321.50 | 0.00 |
CAFE_FLR_1 | 12-FEB-12:39 | 0.00 | 0.00 | 0.00 | -25065.04 | 0.00 | 0.00 | 2968.95 | 358.25 | 406.43 | 20490.14 | 0.00 | 0.00 | 1329.40 | 0.00 | -0.00 | 0.00 | -488.13 | 0.00 |
LOBBY_FLR_1 | 10-MAY-21:54 | 0.00 | 0.00 | 0.00 | -60203.61 | 0.00 | 0.00 | 26625.48 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 23566.18 | 0.00 | -2877.99 | 0.00 | -1343.46 | 0.00 |
ROOM_1_FLR_3 | 14-MAY-15:02 | 0.00 | -13482.39 | 0.00 | -735.78 | 0.00 | 0.00 | 130.71 | 161.71 | 305.54 | 11467.07 | 0.00 | 64.75 | 2088.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 10-AUG-18:02 | 0.00 | -12301.78 | 0.00 | -751.45 | 0.00 | 0.00 | 335.50 | 436.07 | 516.20 | 9465.22 | 0.00 | 200.55 | 2099.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 04-OCT-12:30 | 0.00 | -53002.45 | 0.00 | -10424.69 | 0.00 | 0.00 | 0.00 | 1638.34 | 5097.90 | 87514.45 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -398.78 | -30424.78 |
ROOM_4_MULT19_FLR_3 | 24-JUL-18:02 | 0.00 | -58746.57 | 0.00 | -10256.30 | 0.00 | 0.00 | 6375.30 | 5209.05 | 9610.21 | 15117.80 | 0.00 | 807.03 | 31883.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 14-MAY-15:02 | 0.00 | -11874.46 | 0.00 | -724.97 | 0.00 | 0.00 | 130.72 | 161.71 | 305.54 | 3208.98 | 0.00 | 81.08 | 8711.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 30-JUL-15:02 | 0.00 | -10868.41 | 0.00 | -729.18 | 0.00 | 0.00 | 130.72 | 161.69 | 305.51 | 1829.07 | 0.00 | 125.97 | 9044.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 18-MAY-06:25 | 0.00 | 0.00 | 0.00 | -13363.23 | 0.00 | 0.00 | 2614.81 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 7634.90 | 0.00 | -1308.97 | 0.00 | -557.03 | 0.00 |
ROOM_1_FLR_6 | 10-AUG-18:02 | 0.00 | -3542.36 | 0.00 | -187.68 | 0.00 | 0.00 | 83.87 | 109.03 | 129.07 | 2254.67 | 0.00 | 49.83 | 1103.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 31-JUL-18:02 | 0.00 | -3188.08 | 0.00 | -187.82 | 0.00 | 0.00 | 83.88 | 109.02 | 129.05 | 2364.61 | 0.00 | 23.20 | 666.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 04-OCT-15:02 | 0.00 | -18953.77 | 0.00 | -1189.35 | 0.00 | 0.00 | 529.40 | 194.07 | 603.86 | 10410.09 | 0.00 | 0.00 | 8716.01 | 0.00 | -0.00 | 0.00 | -310.31 | 0.00 |
BANQUET_FLR_6 | 31-OCT-03:59 | 0.00 | 0.00 | 0.00 | -31685.76 | 0.00 | 0.00 | 15763.17 | 343.78 | 2249.30 | 0.00 | 0.00 | 0.00 | 14903.74 | 0.00 | -1283.60 | 0.00 | -290.63 | 0.00 |
DINING_FLR_6 | 07-APR-23:14 | 0.00 | 0.00 | 0.00 | -34087.76 | 0.00 | 0.00 | 16252.14 | 687.57 | 2249.30 | 0.00 | 0.00 | 0.00 | 16247.63 | 0.00 | -1067.31 | 0.00 | -281.57 | 0.00 |
KITCHEN_FLR_6 | 29-MAR-11:16 | 0.00 | 0.00 | 0.00 | -39542.32 | 0.00 | 0.00 | 308.87 | 302.73 | 24259.91 | 1473.34 | 0.00 | 0.00 | 13445.49 | 0.00 | -0.00 | 0.00 | -248.02 | 0.00 |
CORRIDOR_FLR_6 | 10-AUG-14:20 | 0.00 | 0.00 | 0.00 | -6834.50 | 0.00 | 0.00 | 462.68 | 658.76 | 0.00 | 3529.79 | 0.00 | 78.05 | 2105.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-18:02 | 0.00 | -156018.03 | 0.00 | -216391.56 | 0.00 | 0.00 | 74608.10 | 53571.31 | 122326.88 | 53479.82 | 0.00 | 4793.14 | 63630.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 30-OCT-05:03 | 0.00 | 0.00 | 1940.26 | 0.00 | 0.00 | 0.00 | 5187.65 | 6304.56 | 5323.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18755.52 |
RETAIL_1_FLR_1 | 23-APR-07:06 | 0.00 | 0.00 | 1918.35 | 0.00 | 0.00 | 0.00 | 447.56 | 313.07 | 360.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -67.11 | 0.00 | -151.86 | -2820.86 |
RETAIL_2_FLR_1 | 23-NOV-18:25 | 0.00 | 0.00 | 353.89 | 0.00 | 0.00 | 0.00 | 406.46 | 453.18 | 501.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -77.18 | -1637.78 |
MECH_FLR_1 | 02-DEC-07:16 | 0.00 | 0.00 | 435.54 | 0.00 | 0.00 | 0.00 | 109.60 | 453.47 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -167.42 | -1184.63 |
STORAGE_FLR_1 | 10-DEC-19:47 | 0.00 | 0.00 | 258.86 | 0.00 | 0.00 | 0.00 | 101.17 | 177.11 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -93.62 | -647.43 |
LAUNDRY_FLR_1 | 13-OCT-01:49 | 0.00 | 0.00 | 2757.28 | 0.00 | 0.00 | 0.00 | 605.03 | 39.69 | 9326.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -245.00 | -12483.18 |
CAFE_FLR_1 | 02-DEC-07:16 | 0.00 | 0.00 | 3311.12 | 0.00 | 0.00 | 0.00 | 5862.67 | 587.30 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2019.80 | 0.00 | -413.99 | -7733.74 |
LOBBY_FLR_1 | 23-NOV-18:25 | 0.00 | 0.00 | 6490.51 | 0.00 | 0.00 | 0.00 | 13528.22 | 5702.88 | 6334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2539.27 | 0.00 | -1287.11 | -28229.46 |
ROOM_1_FLR_3 | 13-DEC-19:01 | 8692.39 | 293.24 | 0.00 | -293.24 | 0.00 | 0.00 | 417.94 | 436.12 | 516.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1519.49 | 0.00 | -413.83 | -8129.39 |
ROOM_2_FLR_3 | 19-FEB-09:01 | 8538.83 | 294.71 | 0.00 | -294.71 | 0.00 | 0.00 | 163.33 | 274.38 | 653.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1383.93 | 0.00 | -664.10 | -7581.65 |
ROOM_3_MULT19_FLR_3 | 19-FEB-06:00 | 12427.95 | 3404.35 | 0.00 | -3404.35 | 0.00 | 0.00 | 0.00 | 643.59 | 3921.46 | 0.00 | 0.00 | 0.00 | 580.12 | 0.00 | -13724.83 | 0.00 | -3848.30 | 0.00 |
ROOM_4_MULT19_FLR_3 | 15-JAN-16:01 | 45213.73 | 4172.94 | 0.00 | -4172.94 | 0.00 | 0.00 | 3045.63 | 1931.47 | 5687.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8578.28 | 0.00 | -2832.17 | -44468.05 |
ROOM_5_FLR_3 | 13-DEC-19:01 | 8525.28 | 293.51 | 0.00 | -293.51 | 0.00 | 0.00 | 417.73 | 436.12 | 516.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1517.38 | 0.00 | -413.93 | -7964.08 |
ROOM_6_FLR_3 | 15-JAN-09:01 | 8344.53 | 296.24 | 0.00 | -296.24 | 0.00 | 0.00 | 163.33 | 274.38 | 653.15 | 565.85 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -661.88 | -9339.36 |
CORRIDOR_FLR_3 | 01-DEC-18:20 | 0.00 | 0.00 | 4500.19 | 0.00 | 0.00 | 0.00 | 3457.18 | 5975.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2006.35 | 0.00 | -518.18 | -11408.26 |
ROOM_1_FLR_6 | 15-JAN-09:01 | 2553.44 | 75.39 | 0.00 | -75.39 | 0.00 | 0.00 | 40.83 | 68.60 | 163.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -87.08 | 0.00 | -166.49 | -2572.60 |
ROOM_2_FLR_6 | 07-JAN-09:01 | 2524.07 | 74.60 | 0.00 | -74.60 | 0.00 | 0.00 | 40.83 | 68.59 | 163.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -419.41 | 0.00 | -169.51 | -2207.87 |
ROOM_3_MULT9_FLR_6 | 19-DEC-19:01 | 12414.83 | 488.50 | 0.00 | -488.50 | 0.00 | 0.00 | 935.66 | 616.86 | 1138.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1475.87 | 0.00 | -464.62 | -13164.91 |
BANQUET_FLR_6 | 03-MAR-00:55 | 0.00 | 0.00 | 665.58 | 0.00 | 0.00 | 0.00 | 15501.78 | 687.57 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1080.74 | 0.00 | -313.94 | -17709.55 |
DINING_FLR_6 | 03-MAR-00:55 | 0.00 | 0.00 | 234.66 | 0.00 | 0.00 | 0.00 | 15397.99 | 687.57 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1104.73 | 0.00 | -316.90 | -17147.90 |
KITCHEN_FLR_6 | 13-OCT-01:49 | 0.00 | 0.00 | 171.54 | 0.00 | 0.00 | 0.00 | 1456.79 | 121.09 | 5415.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -956.00 | 0.00 | -271.47 | -5937.93 |
CORRIDOR_FLR_6 | 10-DEC-19:47 | 0.00 | 0.00 | 1943.61 | 0.00 | 0.00 | 0.00 | 1099.79 | 1844.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -821.85 | 0.00 | -222.52 | -3843.55 |
Total Facility | 10-NOV-09:01 | 74269.04 | 24129.60 | 14756.71 | -24129.60 | 0.00 | 0.00 | 22324.84 | 26712.50 | 88432.23 | 38024.67 | 0.00 | 0.00 | 0.00 | 0.00 | -2929.58 | 0.00 | -10971.84 | -250618.57 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 22.9087 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.7852 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6605 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6605 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5876 | 2.5876 | 1.3171 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4790 | 0.4790 | 0.2438 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2416 | 0.2416 | 0.1230 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2200 | 0.2200 | 0.1120 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1060 | 0.1060 | 0.0540 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2986 | 3.2986 | 1.6790 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8469 | 1.8469 | 0.9401 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.0864 | 5.0864 | 2.5890 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5747 | 1.5747 | 0.8015 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1341 | 2.1341 | 1.0863 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2357 | 2.2357 | 1.1380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2874 | 2.2874 | 1.1643 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8108 | 0.8108 | 0.4127 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 22.9087 | 22.7852 | 22.9087 | 11.6605 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3171 | 1.3171 | 1.3171 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2438 | 0.2438 | 0.2438 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1230 | 0.1230 | 0.1230 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1120 | 0.1120 | 0.1120 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0540 | 0.0540 | 0.0540 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6790 | 1.6790 | 1.6790 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9401 | 0.9401 | 0.9401 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5890 | 2.5890 | 2.5890 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8015 | 0.8015 | 0.8015 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0863 | 1.0863 | 1.0863 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1380 | 1.1380 | 1.1380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1643 | 1.1643 | 1.1643 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4127 | 0.4127 | 0.4127 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6605 | 11.6605 | 11.6605 | 11.6605 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 474.33 |
Number of hours not met | 474.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 698.56 | 186550.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 425.63 | 142582.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 766.66 | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 242.27 | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.56 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 32.45 | 1868.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 543.37 | 41298.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 122.81 | 8225.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 194.02 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.61 | 3155.64 | 286457.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.50 | 2034.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.50 | 1245.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1807.10 | 4844.08 |
Natural Gas | 1788.84 | 5643.03 |
Additional | 0.00 | 0.00 |
Total | 3595.94 | 10487.12 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 67.57 |
Space Heating | 0.00 |
Space Cooling | 37.52 |
Fans (All) | 47.89 |
Service Water Heating | 8.00 |
Receptacle Equipment | 153.81 |
Miscellaneous (All) | 426.97 |
Subtotal | 426.97 |
Natural Gas [MJ/m2] | |
Space Heating | 61.57 |
Service Water Heating | 278.15 |
Miscellaneous (All) | 497.39 |
Subtotal | 497.39 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.31 |
Space Heating | 6.66 |
Space Cooling | 4.06 |
Fans (All) | 5.18 |
Service Water Heating | 30.96 |
Receptacle Equipment | 33.70 |
Miscellaneous | 12.14 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2667. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 2678. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 3061. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8758.17 | 1.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8758.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1.83 | 0.00 | 0.00 | 0.00 |
Average | 8759.91 | 0.09 | 0.00 | 0.00 | 0.00 |
Sum | 192718.00 | 2.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37202.17 | 0.83 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108250.83 | 18.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 18.17 | 0.00 | 0.00 | 0.00 |
Average | 288886.18 | 0.86 | 0.00 | 0.00 | 0.00 |
Sum | 6355496.00 | 19.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8728.67 | 31.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8716.67 | 43.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8755.00 | 5.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8716.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 43.33 | 0.00 | 0.00 | 0.00 |
Average | 8754.79 | 5.21 | 0.00 | 0.00 | 0.00 |
Sum | 192605.33 | 114.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 709051.67 | 1365.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2103707.00 | 11722.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1236212.50 | 9502.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1240381.00 | 5334.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108237.67 | 31.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2103707.00 | 11722.00 | 0.00 | 0.00 | 0.00 |
Average | 287616.36 | 1270.69 | 0.00 | 0.00 | 0.00 |
Sum | 6327559.83 | 27955.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:04
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.339302E+11 | 34483.24 | 09-JAN-22:01 | 5.60 | 1.64 | 0.792619E+10 | 4946.35 | 30-JAN-22:19 | 5.60 | 3.84 |
February | 0.299838E+11 | 32768.76 | 08-FEB-20:21 | 3.85 | 1.80 | 0.705755E+10 | 4947.76 | 01-FEB-22:30 | 3.85 | 1.80 |
March | 0.325873E+11 | 26821.85 | 24-MAR-20:45 | 5.10 | -0.5 | 0.773932E+10 | 4885.51 | 23-MAR-21:30 | 5.10 | -0.5 |
April | 0.315628E+11 | 23289.15 | 24-APR-23:34 | 7.40 | 5.44 | 0.736923E+10 | 4822.42 | 17-APR-21:19 | 7.40 | 5.44 |
May | 0.333016E+11 | 24364.77 | 18-MAY-06:25 | 5.85 | 5.34 | 0.765864E+10 | 4821.39 | 10-MAY-21:40 | 5.85 | 5.34 |
June | 0.333390E+11 | 20551.20 | 15-JUN-05:27 | 9.15 | 8.12 | 0.750694E+10 | 4829.57 | 23-JUN-21:19 | 14.23 | 10.54 |
July | 0.356489E+11 | 17230.41 | 04-JUL-05:27 | 11.40 | 8.70 | 0.787441E+10 | 4837.03 | 26-JUL-21:19 | 19.67 | 16.34 |
August | 0.367012E+11 | 18109.33 | 18-AUG-21:00 | 15.00 | 12.34 | 0.800509E+10 | 4837.06 | 08-AUG-21:19 | 15.00 | 12.34 |
September | 0.362515E+11 | 26862.61 | 28-SEP-05:50 | 8.30 | 7.54 | 0.782420E+10 | 4891.74 | 27-SEP-04:49 | 8.30 | 7.54 |
October | 0.379654E+11 | 35593.24 | 16-OCT-06:23 | 6.40 | 5.43 | 0.812122E+10 | 4931.14 | 11-OCT-02:49 | 6.40 | 5.43 |
November | 0.365797E+11 | 37074.87 | 29-NOV-21:48 | 5.00 | 3.42 | 0.787220E+10 | 4961.49 | 10-NOV-22:40 | 5.00 | 3.42 |
December | 0.358718E+11 | 36814.45 | 01-DEC-20:45 | 5.10 | 5.05 | 0.805576E+10 | 4959.93 | 20-DEC-23:10 | 4.82 | 3.63 |
Annual Sum or Average | 0.413723E+12 | 0.930107E+11 | ||||||||
Minimum of Months | 0.299838E+11 | 17230.41 | 3.85 | -0.5 | 0.705755E+10 | 4821.39 | 3.85 | -0.5 | ||
Maximum of Months | 0.379654E+11 | 37074.87 | 15.00 | 12.34 | 0.812122E+10 | 4961.49 | 19.67 | 16.34 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.964753E+09 | 4050.99 | 20-JAN-12:48 | 6.52 | 4.54 | 0.621474E+09 | 384.04 | 10-JAN-00:10 | 6.52 | 4.54 |
February | 0.178757E+10 | 6214.52 | 12-FEB-12:55 | 6.10 | 0.89 | 0.566379E+09 | 389.14 | 03-FEB-23:00 | 6.10 | 0.89 |
March | 0.285153E+10 | 3975.74 | 02-MAR-13:20 | 12.57 | 7.60 | 0.635085E+09 | 405.73 | 14-MAR-21:30 | 12.50 | 8.53 |
April | 0.361726E+10 | 3609.41 | 27-APR-13:10 | 26.10 | 16.37 | 0.620214E+09 | 434.93 | 27-APR-21:30 | 15.80 | 11.30 |
May | 0.425327E+10 | 3475.43 | 04-MAY-13:20 | 22.77 | 15.31 | 0.646141E+09 | 432.26 | 04-MAY-21:30 | 18.35 | 12.20 |
June | 0.449033E+10 | 2759.95 | 28-JUN-10:33 | 21.50 | 14.65 | 0.629144E+09 | 428.70 | 28-JUN-21:30 | 17.50 | 13.87 |
July | 0.523210E+10 | 3354.37 | 31-JUL-13:20 | 27.57 | 18.47 | 0.670266E+09 | 449.80 | 24-JUL-21:30 | 27.57 | 18.47 |
August | 0.544785E+10 | 4256.89 | 24-AUG-13:10 | 28.93 | 19.36 | 0.683535E+09 | 462.94 | 10-AUG-21:30 | 28.93 | 19.36 |
September | 0.470944E+10 | 4397.98 | 14-SEP-13:20 | 23.17 | 17.52 | 0.642403E+09 | 449.39 | 12-SEP-21:30 | 23.17 | 17.52 |
October | 0.358510E+10 | 4487.61 | 04-OCT-12:50 | 20.60 | 11.27 | 0.639159E+09 | 432.32 | 04-OCT-21:30 | 15.00 | 9.56 |
November | 0.175721E+10 | 5509.88 | 11-NOV-12:35 | 6.13 | 4.87 | 0.603245E+09 | 387.84 | 10-NOV-22:40 | 6.13 | 4.87 |
December | 0.120924E+10 | 3568.21 | 05-DEC-11:20 | 8.87 | 5.64 | 0.623266E+09 | 378.83 | 07-DEC-22:30 | 6.10 | 5.21 |
Annual Sum or Average | 0.399057E+11 | 0.758031E+10 | ||||||||
Minimum of Months | 0.964753E+09 | 2759.95 | 6.10 | 0.89 | 0.566379E+09 | 378.83 | 6.10 | 0.89 | ||
Maximum of Months | 0.544785E+10 | 6214.52 | 28.93 | 19.36 | 0.683535E+09 | 462.94 | 28.93 | 19.36 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235816E+10 | 1750.60 | 03-JAN-06:34 | 7.80 | 6.88 | 0.785371E+09 | 537.82 | 09-JAN-22:10 | 5.60 | 1.64 |
February | 0.228363E+10 | 1929.01 | 08-FEB-20:27 | 3.85 | 1.80 | 0.730711E+09 | 553.11 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.271364E+10 | 2153.07 | 15-MAR-06:07 | 6.88 | 5.85 | 0.846657E+09 | 566.21 | 02-MAR-23:10 | 6.88 | 5.85 |
April | 0.280278E+10 | 2175.35 | 24-APR-23:34 | 7.40 | 5.44 | 0.840578E+09 | 569.52 | 26-APR-21:00 | 12.80 | 10.12 |
May | 0.304832E+10 | 2154.21 | 18-MAY-06:25 | 5.85 | 5.34 | 0.891405E+09 | 569.54 | 15-MAY-21:30 | 5.85 | 5.34 |
June | 0.306368E+10 | 1812.69 | 15-JUN-05:27 | 9.15 | 8.12 | 0.874079E+09 | 569.52 | 26-JUN-21:10 | 15.82 | 13.04 |
July | 0.334853E+10 | 1972.80 | 24-JUL-21:00 | 22.80 | 16.50 | 0.922695E+09 | 569.54 | 30-JUL-23:19 | 19.80 | 15.74 |
August | 0.340518E+10 | 2121.77 | 10-AUG-21:00 | 23.00 | 16.96 | 0.929839E+09 | 569.55 | 08-AUG-21:19 | 23.00 | 16.96 |
September | 0.308749E+10 | 1909.36 | 14-SEP-21:00 | 18.30 | 14.89 | 0.878266E+09 | 569.54 | 12-SEP-23:19 | 18.30 | 14.89 |
October | 0.286817E+10 | 2025.00 | 12-OCT-23:32 | 7.43 | 6.58 | 0.866158E+09 | 569.53 | 04-OCT-22:00 | 7.43 | 6.58 |
November | 0.248993E+10 | 1869.58 | 28-NOV-23:25 | 7.25 | 6.32 | 0.789075E+09 | 547.97 | 10-NOV-22:40 | 7.25 | 6.32 |
December | 0.240533E+10 | 1854.28 | 01-DEC-18:17 | 6.10 | 5.39 | 0.795198E+09 | 550.66 | 04-DEC-22:10 | 4.85 | 3.28 |
Annual Sum or Average | 0.338748E+11 | 0.101500E+11 | ||||||||
Minimum of Months | 0.228363E+10 | 1750.60 | 3.85 | 1.80 | 0.730711E+09 | 537.82 | 4.85 | 1.64 | ||
Maximum of Months | 0.340518E+10 | 2175.35 | 23.00 | 16.96 | 0.929839E+09 | 569.55 | 23.00 | 16.96 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142437E+10 | 1494.15 | 01-JAN-20:15 | 5.93 | 5.23 | 0.154024E+09 | 98.94 | 30-JAN-22:19 | 5.60 | 3.84 |
February | 0.155866E+10 | 1610.48 | 26-FEB-01:32 | 8.87 | 8.22 | 0.141380E+09 | 104.67 | 28-FEB-22:10 | 8.12 | 7.00 |
March | 0.217220E+10 | 1813.17 | 15-MAR-06:07 | 6.88 | 5.85 | 0.163092E+09 | 104.47 | 20-MAR-21:49 | 8.22 | 6.10 |
April | 0.230232E+10 | 1829.91 | 24-APR-23:34 | 7.40 | 5.44 | 0.164080E+09 | 113.80 | 27-APR-21:19 | 16.27 | 11.36 |
May | 0.259112E+10 | 1910.42 | 18-MAY-06:25 | 5.85 | 5.34 | 0.178180E+09 | 116.78 | 05-MAY-21:19 | 5.85 | 5.34 |
June | 0.266623E+10 | 1591.73 | 13-JUN-23:40 | 10.00 | 8.89 | 0.178048E+09 | 119.59 | 28-JUN-21:10 | 16.97 | 13.74 |
July | 0.290701E+10 | 1598.25 | 24-JUL-21:00 | 22.80 | 16.50 | 0.189857E+09 | 120.45 | 26-JUL-21:19 | 19.67 | 16.34 |
August | 0.296204E+10 | 1738.30 | 10-AUG-20:00 | 25.60 | 17.66 | 0.192387E+09 | 120.45 | 15-AUG-22:10 | 18.18 | 14.52 |
September | 0.262834E+10 | 1656.42 | 27-SEP-06:30 | 8.60 | 8.44 | 0.177320E+09 | 120.10 | 14-SEP-21:10 | 8.60 | 8.44 |
October | 0.239098E+10 | 1712.76 | 12-OCT-23:32 | 7.43 | 6.58 | 0.170751E+09 | 113.38 | 04-OCT-21:10 | 7.43 | 6.58 |
November | 0.192883E+10 | 1569.10 | 17-NOV-08:35 | 7.03 | 6.50 | 0.154152E+09 | 106.15 | 06-NOV-22:10 | 7.03 | 6.50 |
December | 0.159049E+10 | 1550.11 | 04-DEC-16:10 | 8.03 | 4.89 | 0.154662E+09 | 101.20 | 04-DEC-22:10 | 4.85 | 3.28 |
Annual Sum or Average | 0.271226E+11 | 0.201793E+10 | ||||||||
Minimum of Months | 0.142437E+10 | 1494.15 | 5.85 | 4.89 | 0.141380E+09 | 98.94 | 4.85 | 3.28 | ||
Maximum of Months | 0.296204E+10 | 1910.42 | 25.60 | 17.66 | 0.192387E+09 | 120.45 | 19.67 | 16.34 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.397994E+09 | 643.73 | 12-JAN-07:10 | 6.70 | 6.17 | 0.116987E+09 | 72.13 | 11-JAN-23:10 | 6.70 | 6.17 |
February | 0.566064E+09 | 755.64 | 26-FEB-01:32 | 8.87 | 8.22 | 0.106799E+09 | 76.44 | 28-FEB-23:40 | 6.47 | 5.27 |
March | 0.978533E+09 | 853.54 | 15-MAR-06:07 | 6.88 | 5.85 | 0.121699E+09 | 76.09 | 20-MAR-22:19 | 7.93 | 5.90 |
April | 0.106620E+10 | 862.16 | 24-APR-23:34 | 7.40 | 5.44 | 0.122596E+09 | 83.47 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.120556E+10 | 894.07 | 18-MAY-06:25 | 5.85 | 5.34 | 0.133319E+09 | 85.58 | 05-MAY-22:10 | 5.85 | 5.34 |
June | 0.124477E+10 | 750.34 | 13-JUN-23:40 | 10.00 | 8.89 | 0.133479E+09 | 87.73 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.135894E+10 | 669.20 | 24-JUL-18:10 | 28.72 | 17.86 | 0.142574E+09 | 90.77 | 24-JUL-21:40 | 21.33 | 16.04 |
August | 0.138054E+10 | 681.60 | 10-AUG-18:08 | 30.57 | 19.31 | 0.144671E+09 | 91.91 | 10-AUG-21:40 | 22.67 | 16.07 |
September | 0.122591E+10 | 778.12 | 27-SEP-05:14 | 7.57 | 7.21 | 0.132917E+09 | 88.06 | 14-SEP-21:40 | 7.57 | 7.21 |
October | 0.110552E+10 | 807.70 | 12-OCT-23:32 | 7.43 | 6.58 | 0.127504E+09 | 83.25 | 04-OCT-22:10 | 7.43 | 6.58 |
November | 0.774351E+09 | 724.33 | 20-NOV-06:13 | 7.80 | 6.22 | 0.115726E+09 | 77.37 | 06-NOV-23:10 | 7.80 | 6.22 |
December | 0.510128E+09 | 718.19 | 03-DEC-09:07 | 7.98 | 3.60 | 0.117136E+09 | 72.80 | 04-DEC-22:10 | 4.85 | 3.28 |
Annual Sum or Average | 0.118145E+11 | 0.151541E+10 | ||||||||
Minimum of Months | 0.397994E+09 | 643.73 | 5.85 | 3.60 | 0.106799E+09 | 72.13 | 4.85 | 3.28 | ||
Maximum of Months | 0.138054E+10 | 894.07 | 30.57 | 19.31 | 0.144671E+09 | 91.91 | 22.67 | 16.07 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.477958E+11 | 50428.00 | 23-JAN-21:40 | 4.40 | 2.93 | 0.592551E+09 | 489.73 | 30-JAN-22:19 | 5.60 | 3.84 |
February | 0.437722E+11 | 52379.02 | 07-FEB-20:01 | 4.82 | 2.07 | 0.535035E+09 | 508.33 | 01-FEB-22:30 | 4.82 | 2.07 |
March | 0.494526E+11 | 51226.88 | 24-MAR-20:45 | 5.10 | -0.5 | 0.597159E+09 | 508.23 | 23-MAR-21:30 | 5.10 | -0.5 |
April | 0.485980E+11 | 49727.30 | 17-APR-19:00 | 5.60 | 4.36 | 0.577552E+09 | 484.48 | 07-APR-21:30 | 5.60 | 4.36 |
May | 0.509700E+11 | 49684.70 | 10-MAY-22:00 | 6.70 | 5.64 | 0.597547E+09 | 470.82 | 10-MAY-21:40 | 6.70 | 5.64 |
June | 0.500619E+11 | 38426.82 | 28-JUN-20:00 | 21.70 | 15.30 | 0.576532E+09 | 389.22 | 06-JUN-21:10 | 21.70 | 15.30 |
July | 0.520262E+11 | 38712.28 | 24-JUL-20:00 | 23.90 | 16.63 | 0.596452E+09 | 382.01 | 04-JUL-23:10 | 23.90 | 16.63 |
August | 0.524473E+11 | 38783.54 | 10-AUG-20:00 | 25.60 | 17.66 | 0.598494E+09 | 381.90 | 08-AUG-21:10 | 25.60 | 17.66 |
September | 0.496470E+11 | 43398.20 | 27-SEP-06:59 | 8.90 | 8.58 | 0.576927E+09 | 426.25 | 27-SEP-04:49 | 8.90 | 8.58 |
October | 0.499847E+11 | 49333.63 | 31-OCT-20:29 | 7.20 | 6.43 | 0.596376E+09 | 477.75 | 31-OCT-21:10 | 7.30 | 6.51 |
November | 0.472546E+11 | 50329.27 | 29-NOV-21:48 | 5.00 | 3.42 | 0.576966E+09 | 513.21 | 10-NOV-22:40 | 5.00 | 3.42 |
December | 0.479215E+11 | 52305.45 | 04-DEC-21:40 | 5.00 | 3.43 | 0.594456E+09 | 503.41 | 26-DEC-22:10 | 4.90 | 4.13 |
Annual Sum or Average | 0.589932E+12 | 0.701605E+10 | ||||||||
Minimum of Months | 0.437722E+11 | 38426.82 | 4.40 | -0.5 | 0.535035E+09 | 381.90 | 4.82 | -0.5 | ||
Maximum of Months | 0.524473E+11 | 52379.02 | 25.60 | 17.66 | 0.598494E+09 | 513.21 | 25.60 | 17.66 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149587E+11 | 19794.98 | 20-JAN-12:48 | 6.52 | 4.54 | 0.862580E+10 | 6191.64 | 30-JAN-22:19 | 5.60 | 3.84 |
February | 0.157902E+11 | 25066.42 | 12-FEB-12:39 | 5.93 | 0.82 | 0.804746E+10 | 6490.36 | 03-FEB-23:00 | 5.93 | 0.82 |
March | 0.192820E+11 | 15356.16 | 01-MAR-13:17 | 10.97 | 5.87 | 0.927766E+10 | 6625.59 | 03-MAR-00:49 | 6.70 | 5.87 |
April | 0.203233E+11 | 15994.73 | 24-APR-23:34 | 7.40 | 5.44 | 0.917838E+10 | 6466.45 | 07-APR-23:40 | 7.40 | 5.44 |
May | 0.218038E+11 | 14531.93 | 27-MAY-04:27 | 7.80 | 7.25 | 0.964391E+10 | 6460.28 | 04-MAY-22:10 | 7.80 | 7.25 |
June | 0.218533E+11 | 12889.20 | 15-JUN-02:29 | 8.60 | 7.75 | 0.946956E+10 | 6460.27 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.237655E+11 | 12204.95 | 31-JUL-15:03 | 28.40 | 18.96 | 0.100270E+11 | 6461.57 | 24-JUL-23:19 | 28.40 | 18.96 |
August | 0.245244E+11 | 14417.16 | 24-AUG-14:10 | 29.18 | 19.32 | 0.101775E+11 | 6461.66 | 10-AUG-23:19 | 29.18 | 19.32 |
September | 0.226561E+11 | 15450.25 | 23-SEP-13:20 | 22.57 | 17.43 | 0.959193E+10 | 6461.67 | 12-SEP-23:19 | 22.57 | 17.43 |
October | 0.207141E+11 | 15597.68 | 04-OCT-12:50 | 20.60 | 11.27 | 0.947199E+10 | 6537.95 | 13-OCT-02:00 | 6.70 | 5.33 |
November | 0.163709E+11 | 24423.79 | 11-NOV-12:03 | 5.28 | 4.39 | 0.859339E+10 | 6225.90 | 10-NOV-22:40 | 5.28 | 4.39 |
December | 0.154476E+11 | 13989.18 | 05-DEC-11:20 | 8.87 | 5.64 | 0.870947E+10 | 6156.78 | 20-DEC-23:10 | 4.82 | 3.63 |
Annual Sum or Average | 0.237490E+12 | 0.110814E+12 | ||||||||
Minimum of Months | 0.149587E+11 | 12204.95 | 5.28 | 0.82 | 0.804746E+10 | 6156.78 | 4.82 | 0.82 | ||
Maximum of Months | 0.245244E+11 | 25066.42 | 29.18 | 19.32 | 0.101775E+11 | 6625.59 | 29.18 | 19.32 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.541567E+11 | 39305.93 | 09-JAN-22:20 | 5.60 | 1.67 | 0.280760E+11 | 19245.90 | 30-JAN-22:19 | 5.60 | 3.84 |
February | 0.521404E+11 | 46873.94 | 28-FEB-23:30 | 6.65 | 5.48 | 0.260807E+11 | 19523.64 | 03-FEB-23:00 | 6.65 | 5.48 |
March | 0.612692E+11 | 58831.08 | 21-MAR-21:18 | 7.03 | 6.14 | 0.300532E+11 | 19740.57 | 03-MAR-00:49 | 7.03 | 6.14 |
April | 0.626827E+11 | 52477.42 | 11-APR-22:00 | 6.70 | 5.41 | 0.296029E+11 | 19610.08 | 21-APR-23:30 | 8.30 | 6.94 |
May | 0.676471E+11 | 60204.86 | 10-MAY-21:54 | 6.70 | 5.64 | 0.311203E+11 | 19641.67 | 10-MAY-21:40 | 6.70 | 5.64 |
June | 0.678339E+11 | 39862.88 | 15-JUN-05:27 | 9.15 | 8.12 | 0.304481E+11 | 19189.33 | 22-JUN-01:39 | 12.97 | 11.68 |
July | 0.733042E+11 | 39587.72 | 24-JUL-21:10 | 22.43 | 16.40 | 0.317809E+11 | 19202.00 | 19-JUL-04:49 | 22.43 | 16.40 |
August | 0.749767E+11 | 40992.29 | 10-AUG-21:10 | 22.92 | 16.74 | 0.320038E+11 | 19225.48 | 11-AUG-04:30 | 12.85 | 11.96 |
September | 0.684981E+11 | 41913.69 | 27-SEP-05:14 | 7.57 | 7.21 | 0.305302E+11 | 19244.43 | 12-SEP-02:49 | 7.57 | 7.21 |
October | 0.645578E+11 | 59903.72 | 13-OCT-00:55 | 7.20 | 6.12 | 0.305941E+11 | 19700.95 | 13-OCT-02:00 | 6.70 | 5.33 |
November | 0.562971E+11 | 46414.07 | 28-NOV-23:05 | 7.62 | 6.40 | 0.281092E+11 | 19544.93 | 10-NOV-22:40 | 7.62 | 6.40 |
December | 0.550881E+11 | 40018.21 | 03-DEC-09:07 | 7.98 | 3.60 | 0.283786E+11 | 19176.07 | 07-DEC-23:19 | 6.10 | 5.28 |
Annual Sum or Average | 0.758452E+12 | 0.356778E+12 | ||||||||
Minimum of Months | 0.521404E+11 | 39305.93 | 5.60 | 1.67 | 0.260807E+11 | 19176.07 | 5.60 | 3.84 | ||
Maximum of Months | 0.749767E+11 | 60204.86 | 22.92 | 16.74 | 0.320038E+11 | 19740.57 | 22.43 | 16.40 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55344550.57 | 2107.97 | 20-JAN-16:02 | 5.40 | 3.78 | 93220246.76 | 56.69 | 03-JAN-05:30 | 5.40 | 3.78 |
February | 0.123455E+09 | 3124.92 | 08-FEB-16:02 | 7.12 | 3.76 | 85376362.34 | 56.69 | 08-FEB-22:10 | 3.22 | 1.67 |
March | 0.295326E+09 | 3350.19 | 18-MAR-15:02 | 20.10 | 10.35 | 95889341.79 | 56.69 | 18-MAR-23:30 | 10.00 | 8.01 |
April | 0.696646E+09 | 3483.65 | 01-APR-18:02 | 25.13 | 11.98 | 94044038.16 | 56.69 | 26-APR-21:00 | 12.80 | 10.12 |
May | 0.118115E+10 | 3554.62 | 14-MAY-15:02 | 23.30 | 12.38 | 98053290.50 | 56.69 | 03-MAY-21:00 | 23.30 | 12.38 |
June | 0.137157E+10 | 3300.56 | 02-JUN-18:01 | 19.45 | 12.43 | 95235484.29 | 56.70 | 28-JUN-21:40 | 17.77 | 13.93 |
July | 0.202354E+10 | 3310.12 | 25-JUL-18:02 | 22.02 | 16.61 | 98597802.45 | 56.70 | 27-JUL-21:40 | 18.17 | 14.77 |
August | 0.197294E+10 | 3543.45 | 10-AUG-18:02 | 30.57 | 19.31 | 98638756.47 | 56.70 | 24-AUG-22:40 | 20.77 | 16.72 |
September | 0.133524E+10 | 3267.73 | 13-SEP-18:02 | 22.43 | 16.15 | 94777491.20 | 56.69 | 14-SEP-02:20 | 14.63 | 13.65 |
October | 0.492622E+09 | 3497.16 | 04-OCT-15:02 | 21.60 | 11.48 | 96392968.52 | 56.69 | 04-OCT-21:40 | 15.37 | 9.73 |
November | 0.111414E+09 | 3181.66 | 04-NOV-15:02 | 20.92 | 15.94 | 91239878.14 | 56.69 | 16-NOV-22:30 | 5.00 | 4.37 |
December | 61378294.74 | 2918.11 | 05-DEC-16:02 | 6.10 | 4.53 | 93541750.99 | 56.69 | 28-DEC-04:30 | 8.60 | 7.35 |
Annual Sum or Average | 0.972063E+10 | 0.113501E+10 | ||||||||
Minimum of Months | 55344550.57 | 2107.97 | 5.40 | 3.76 | 85376362.34 | 56.69 | 3.22 | 1.67 | ||
Maximum of Months | 0.202354E+10 | 3554.62 | 30.57 | 19.31 | 98638756.47 | 56.70 | 23.30 | 16.72 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 37623399.94 | 1010.78 | 24-JAN-16:03 | 6.60 | 5.12 | 92673850.06 | 56.69 | 03-JAN-05:30 | 6.60 | 5.12 |
February | 68654442.80 | 2966.21 | 27-FEB-16:02 | 19.32 | 12.38 | 84497378.55 | 56.69 | 01-FEB-03:49 | 19.32 | 12.38 |
March | 0.163487E+09 | 2994.18 | 18-MAR-15:02 | 20.10 | 10.35 | 94903312.02 | 56.69 | 18-MAR-23:10 | 10.40 | 8.02 |
April | 0.493810E+09 | 3162.17 | 01-APR-18:02 | 25.13 | 11.98 | 93338745.82 | 56.69 | 26-APR-21:30 | 14.20 | 10.54 |
May | 0.987151E+09 | 3217.53 | 14-MAY-15:02 | 23.30 | 12.38 | 97714869.87 | 56.69 | 15-MAY-21:49 | 12.98 | 11.14 |
June | 0.122490E+10 | 3007.49 | 24-JUN-18:02 | 18.72 | 11.75 | 94995663.30 | 56.69 | 28-JUN-21:00 | 18.30 | 14.03 |
July | 0.180304E+10 | 3084.31 | 20-JUL-15:02 | 26.88 | 16.80 | 98438522.73 | 56.70 | 26-JUL-21:40 | 17.63 | 15.37 |
August | 0.167413E+10 | 3263.26 | 10-AUG-18:02 | 30.57 | 19.31 | 98425790.90 | 56.70 | 24-AUG-22:19 | 21.33 | 16.95 |
September | 0.973192E+09 | 3092.85 | 22-SEP-15:02 | 23.58 | 17.29 | 94329509.33 | 56.69 | 22-SEP-21:00 | 16.70 | 14.57 |
October | 0.273215E+09 | 3123.07 | 04-OCT-15:02 | 21.60 | 11.48 | 95426587.90 | 56.69 | 04-OCT-23:19 | 13.70 | 9.84 |
November | 74340134.85 | 2874.86 | 04-NOV-15:02 | 20.92 | 15.94 | 90600499.48 | 56.69 | 14-NOV-22:19 | 5.60 | 5.10 |
December | 42920083.80 | 959.82 | 03-DEC-19:03 | 8.72 | 3.46 | 92825105.36 | 56.69 | 28-DEC-04:30 | 8.60 | 7.35 |
Annual Sum or Average | 0.781647E+10 | 0.112817E+10 | ||||||||
Minimum of Months | 37623399.94 | 959.82 | 6.60 | 3.46 | 84497378.55 | 56.69 | 5.60 | 5.10 | ||
Maximum of Months | 0.180304E+10 | 3263.26 | 30.57 | 19.31 | 98438522.73 | 56.70 | 21.33 | 16.95 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 91606507.14 | 158.87 | 08-JAN-14:40 | 5.40 | 2.66 | 0.00 | 0.00 | 01-JAN-00:10 | 5.40 | 2.66 |
February | 0.180277E+09 | 536.60 | 08-FEB-14:00 | 6.70 | 3.83 | 0.00 | 0.00 | 01-FEB-00:10 | 6.70 | 3.83 |
March | 0.298585E+09 | 684.17 | 02-MAR-13:30 | 12.75 | 7.74 | 0.00 | 0.00 | 01-MAR-00:10 | 12.75 | 7.74 |
April | 0.368416E+09 | 663.51 | 27-APR-13:10 | 26.10 | 16.37 | 0.00 | 0.00 | 01-APR-00:10 | 26.10 | 16.37 |
May | 0.427320E+09 | 638.43 | 04-MAY-13:20 | 22.77 | 15.31 | 0.00 | 0.00 | 01-MAY-00:10 | 22.77 | 15.31 |
June | 0.443342E+09 | 500.61 | 28-JUN-13:20 | 24.60 | 15.70 | 0.00 | 0.00 | 01-JUN-00:10 | 24.60 | 15.70 |
July | 0.578871E+09 | 618.63 | 31-JUL-13:20 | 27.57 | 18.47 | 0.00 | 0.00 | 01-JUL-00:10 | 27.57 | 18.47 |
August | 0.647355E+09 | 761.86 | 24-AUG-13:10 | 28.93 | 19.36 | 0.00 | 0.00 | 01-AUG-00:10 | 28.93 | 19.36 |
September | 0.569253E+09 | 810.42 | 14-SEP-13:30 | 23.35 | 17.43 | 0.00 | 0.00 | 01-SEP-00:10 | 23.35 | 17.43 |
October | 0.407557E+09 | 834.64 | 04-OCT-12:30 | 20.60 | 11.38 | 0.00 | 0.00 | 01-OCT-00:10 | 20.60 | 11.38 |
November | 0.179585E+09 | 548.58 | 04-NOV-13:50 | 21.02 | 15.96 | 0.00 | 0.00 | 01-NOV-00:10 | 21.02 | 15.96 |
December | 0.126592E+09 | 484.60 | 05-DEC-12:25 | 10.30 | 6.13 | 0.00 | 0.00 | 01-DEC-00:10 | 10.30 | 6.13 |
Annual Sum or Average | 0.431876E+10 | 0.00 | ||||||||
Minimum of Months | 91606507.14 | 158.87 | 5.40 | 2.66 | 0.00 | 0.00 | 5.40 | 2.66 | ||
Maximum of Months | 0.647355E+09 | 834.64 | 28.93 | 19.36 | 0.00 | 0.00 | 28.93 | 19.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 74097795.96 | 449.13 | 09-JAN-19:04 | 5.60 | 1.78 | 94277827.16 | 56.69 | 30-JAN-22:10 | 5.60 | 3.84 |
February | 0.104489E+09 | 684.06 | 25-FEB-09:03 | 11.88 | 10.94 | 85550882.33 | 56.69 | 08-FEB-22:10 | 11.88 | 10.94 |
March | 0.193084E+09 | 706.16 | 17-MAR-18:01 | 10.82 | 7.32 | 95536634.98 | 56.69 | 18-MAR-23:19 | 10.20 | 8.02 |
April | 0.324505E+09 | 844.53 | 01-APR-18:02 | 25.13 | 11.98 | 93100621.18 | 56.69 | 27-APR-21:49 | 14.87 | 11.14 |
May | 0.474942E+09 | 855.37 | 14-MAY-18:02 | 21.83 | 11.88 | 96859236.62 | 56.69 | 15-MAY-21:00 | 12.80 | 11.20 |
June | 0.561590E+09 | 872.45 | 09-JUN-18:02 | 22.70 | 13.21 | 94019040.09 | 56.69 | 08-JUN-22:10 | 22.70 | 13.21 |
July | 0.650461E+09 | 907.93 | 24-JUL-18:02 | 28.72 | 17.86 | 97186242.78 | 56.69 | 24-JUL-21:40 | 21.33 | 16.04 |
August | 0.633259E+09 | 897.11 | 10-AUG-18:02 | 30.57 | 19.31 | 97211327.17 | 56.69 | 28-AUG-22:30 | 18.45 | 15.09 |
September | 0.437822E+09 | 819.11 | 13-SEP-18:02 | 22.43 | 16.15 | 93398212.05 | 56.69 | 25-SEP-21:10 | 13.90 | 13.52 |
October | 0.267636E+09 | 749.42 | 04-OCT-15:02 | 21.60 | 11.48 | 95745871.31 | 56.69 | 06-OCT-21:10 | 12.70 | 10.58 |
November | 0.144609E+09 | 686.71 | 04-NOV-08:63 | 13.07 | 11.67 | 91917085.44 | 56.69 | 06-NOV-23:10 | 15.40 | 14.28 |
December | 73519259.12 | 483.75 | 05-DEC-19:03 | 5.37 | 3.27 | 94318567.43 | 56.69 | 15-DEC-22:10 | 5.68 | 5.47 |
Annual Sum or Average | 0.394001E+10 | 0.112912E+10 | ||||||||
Minimum of Months | 73519259.12 | 449.13 | 5.37 | 1.78 | 85550882.33 | 56.69 | 5.60 | 3.84 | ||
Maximum of Months | 0.650461E+09 | 907.93 | 30.57 | 19.31 | 97211327.17 | 56.69 | 22.70 | 16.04 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55019209.09 | 926.77 | 10-JAN-09:03 | 5.78 | 3.12 | 93143830.16 | 56.69 | 03-JAN-05:30 | 5.78 | 3.12 |
February | 0.120246E+09 | 2591.79 | 08-FEB-16:02 | 7.12 | 3.76 | 85384449.00 | 56.69 | 04-FEB-01:30 | 7.12 | 3.76 |
March | 0.288624E+09 | 2990.94 | 18-MAR-15:02 | 20.10 | 10.35 | 96082357.98 | 56.69 | 18-MAR-23:10 | 10.40 | 8.02 |
April | 0.715203E+09 | 3098.80 | 01-APR-18:02 | 25.13 | 11.98 | 94417611.12 | 56.69 | 26-APR-21:30 | 14.20 | 10.54 |
May | 0.104755E+10 | 3149.93 | 14-MAY-15:02 | 23.30 | 12.38 | 98112444.13 | 56.69 | 06-MAY-23:30 | 23.30 | 12.38 |
June | 0.145340E+10 | 3006.83 | 02-JUN-18:01 | 19.45 | 12.43 | 95490524.94 | 56.69 | 28-JUN-21:19 | 17.23 | 13.81 |
July | 0.178284E+10 | 3124.78 | 24-JUL-18:02 | 28.72 | 17.86 | 98698784.78 | 56.70 | 31-JUL-22:10 | 20.05 | 15.96 |
August | 0.194157E+10 | 3141.64 | 10-AUG-18:02 | 30.57 | 19.31 | 98815638.52 | 56.70 | 23-AUG-21:49 | 21.27 | 16.17 |
September | 0.122719E+10 | 3042.27 | 22-SEP-15:02 | 23.58 | 17.29 | 94741911.45 | 56.70 | 14-SEP-21:19 | 23.58 | 17.29 |
October | 0.487072E+09 | 3097.86 | 04-OCT-15:02 | 21.60 | 11.48 | 96531676.75 | 56.69 | 04-OCT-21:10 | 14.27 | 9.23 |
November | 0.115523E+09 | 2866.27 | 04-NOV-15:02 | 20.92 | 15.94 | 91202976.51 | 56.69 | 16-NOV-22:30 | 5.00 | 4.37 |
December | 70397613.90 | 967.03 | 30-DEC-09:03 | 4.18 | 3.83 | 93460705.43 | 56.69 | 28-DEC-04:30 | 4.18 | 3.83 |
Annual Sum or Average | 0.930464E+10 | 0.113608E+10 | ||||||||
Minimum of Months | 55019209.09 | 926.77 | 4.18 | 3.12 | 85384449.00 | 56.69 | 4.18 | 3.12 | ||
Maximum of Months | 0.194157E+10 | 3149.93 | 30.57 | 19.31 | 98815638.52 | 56.70 | 23.58 | 17.29 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34011566.35 | 788.26 | 05-JAN-09:04 | -0.0 | -0.1 | 92640978.49 | 56.69 | 03-JAN-05:30 | -0.0 | -0.1 |
February | 64283743.57 | 1090.96 | 27-FEB-09:01 | 8.77 | 7.22 | 84448023.48 | 56.69 | 01-FEB-03:49 | 8.77 | 7.22 |
March | 0.146134E+09 | 2522.42 | 02-MAR-09:01 | 4.78 | 3.27 | 95080013.79 | 56.69 | 21-MAR-21:49 | 6.78 | 5.71 |
April | 0.499095E+09 | 2776.38 | 27-APR-15:02 | 27.20 | 17.22 | 93797057.79 | 56.69 | 26-APR-21:10 | 27.20 | 17.22 |
May | 0.846698E+09 | 2871.31 | 14-MAY-15:02 | 23.30 | 12.38 | 97862195.75 | 56.69 | 15-MAY-21:49 | 12.98 | 11.14 |
June | 0.129252E+10 | 2818.92 | 28-JUN-18:02 | 25.40 | 16.48 | 95390390.57 | 56.69 | 28-JUN-21:19 | 17.23 | 13.81 |
July | 0.155360E+10 | 2899.38 | 30-JUL-15:02 | 27.30 | 18.11 | 98626292.91 | 56.70 | 31-JUL-21:00 | 20.30 | 16.18 |
August | 0.163063E+10 | 2892.51 | 23-AUG-15:02 | 28.95 | 18.68 | 98707683.83 | 56.70 | 24-AUG-21:00 | 21.90 | 17.18 |
September | 0.854036E+09 | 2777.66 | 12-SEP-15:02 | 24.40 | 16.76 | 94367609.42 | 56.69 | 15-SEP-00:30 | 15.55 | 14.02 |
October | 0.262007E+09 | 2736.98 | 04-OCT-15:02 | 21.60 | 11.48 | 95575816.81 | 56.69 | 04-OCT-21:10 | 14.27 | 9.23 |
November | 70315336.13 | 1445.16 | 04-NOV-15:02 | 20.92 | 15.94 | 90559121.96 | 56.69 | 14-NOV-22:19 | 5.60 | 5.10 |
December | 40698941.98 | 765.24 | 03-DEC-09:03 | 7.98 | 3.60 | 92757622.05 | 56.69 | 16-DEC-03:39 | 9.80 | 8.72 |
Annual Sum or Average | 0.729402E+10 | 0.112981E+10 | ||||||||
Minimum of Months | 34011566.35 | 765.24 | -0.0 | -0.1 | 84448023.48 | 56.69 | -0.0 | -0.1 | ||
Maximum of Months | 0.163063E+10 | 2899.38 | 28.95 | 18.68 | 98707683.83 | 56.70 | 27.20 | 17.22 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194250E+10 | 2352.63 | 12-JAN-07:10 | 6.70 | 6.17 | 0.120156E+10 | 736.61 | 09-JAN-22:30 | 6.70 | 6.17 |
February | 0.247482E+10 | 2771.06 | 08-FEB-15:02 | 7.70 | 3.86 | 0.109659E+10 | 771.97 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.365395E+10 | 3147.70 | 15-MAR-06:07 | 6.88 | 5.85 | 0.125566E+10 | 794.60 | 02-MAR-23:10 | 6.88 | 5.85 |
April | 0.404001E+10 | 3251.67 | 24-APR-23:34 | 7.40 | 5.44 | 0.127423E+10 | 871.57 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.460323E+10 | 3340.92 | 18-MAY-06:25 | 5.85 | 5.34 | 0.139444E+10 | 887.17 | 15-MAY-21:40 | 5.85 | 5.34 |
June | 0.470318E+10 | 2810.79 | 13-JUN-23:40 | 10.00 | 8.89 | 0.138610E+10 | 908.67 | 28-JUN-21:40 | 17.77 | 13.93 |
July | 0.512489E+10 | 2547.20 | 24-JUL-18:10 | 28.72 | 17.86 | 0.147919E+10 | 940.53 | 24-JUL-21:40 | 21.33 | 16.04 |
August | 0.523105E+10 | 2597.21 | 10-AUG-18:08 | 30.57 | 19.31 | 0.150609E+10 | 951.83 | 10-AUG-21:10 | 22.92 | 16.74 |
September | 0.465022E+10 | 2879.38 | 27-SEP-05:14 | 7.57 | 7.21 | 0.138429E+10 | 934.09 | 14-SEP-21:40 | 7.57 | 7.21 |
October | 0.404735E+10 | 3034.38 | 12-OCT-23:32 | 7.43 | 6.58 | 0.130416E+10 | 867.06 | 04-OCT-22:10 | 7.43 | 6.58 |
November | 0.275128E+10 | 2678.33 | 28-NOV-23:25 | 7.25 | 6.32 | 0.117606E+10 | 763.43 | 05-NOV-23:10 | 7.25 | 6.32 |
December | 0.215449E+10 | 2657.79 | 10-DEC-19:46 | 6.78 | 5.97 | 0.120395E+10 | 745.37 | 05-DEC-22:40 | 6.78 | 5.97 |
Annual Sum or Average | 0.453770E+11 | 0.156623E+11 | ||||||||
Minimum of Months | 0.194250E+10 | 2352.63 | 5.85 | 3.86 | 0.109659E+10 | 736.61 | 5.85 | 5.34 | ||
Maximum of Months | 0.523105E+10 | 3340.92 | 30.57 | 19.31 | 0.150609E+10 | 951.83 | 22.92 | 16.74 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35818937.20 | 1787.89 | 20-JAN-16:02 | 5.40 | 3.78 | 92797360.51 | 56.69 | 03-JAN-05:30 | 5.40 | 3.78 |
February | 0.106778E+09 | 3247.32 | 08-FEB-16:02 | 7.12 | 3.76 | 84946990.88 | 56.69 | 01-FEB-03:49 | 7.12 | 3.76 |
March | 0.273396E+09 | 3485.52 | 18-MAR-15:02 | 20.10 | 10.35 | 95472738.81 | 56.69 | 18-MAR-23:19 | 10.20 | 8.02 |
April | 0.659540E+09 | 3635.58 | 01-APR-18:02 | 25.13 | 11.98 | 93779861.42 | 56.69 | 26-APR-21:30 | 14.20 | 10.54 |
May | 0.112784E+10 | 3708.26 | 14-MAY-15:02 | 23.30 | 12.38 | 97887419.56 | 56.69 | 15-MAY-21:40 | 13.17 | 11.09 |
June | 0.132285E+10 | 3427.18 | 02-JUN-18:01 | 19.45 | 12.43 | 95130644.17 | 56.70 | 22-JUN-21:30 | 16.70 | 13.38 |
July | 0.201123E+10 | 3691.26 | 31-JUL-18:02 | 26.42 | 18.31 | 98499949.47 | 56.70 | 26-JUL-21:10 | 26.42 | 18.31 |
August | 0.192163E+10 | 3729.93 | 10-AUG-18:02 | 30.57 | 19.31 | 98512319.56 | 56.70 | 09-AUG-21:00 | 30.57 | 19.31 |
September | 0.124614E+10 | 3382.75 | 13-SEP-18:02 | 22.43 | 16.15 | 94569435.55 | 56.69 | 13-SEP-00:10 | 22.43 | 16.15 |
October | 0.417946E+09 | 3642.92 | 04-OCT-15:02 | 21.60 | 11.48 | 95981966.87 | 56.69 | 09-OCT-00:40 | 12.40 | 10.53 |
November | 94219801.43 | 3251.04 | 04-NOV-15:02 | 20.92 | 15.94 | 90765168.27 | 56.69 | 14-NOV-22:19 | 5.60 | 5.10 |
December | 44937269.52 | 3041.96 | 05-DEC-16:02 | 6.10 | 4.53 | 93143924.06 | 56.69 | 20-DEC-22:10 | 5.00 | 4.14 |
Annual Sum or Average | 0.926233E+10 | 0.113149E+10 | ||||||||
Minimum of Months | 35818937.20 | 1787.89 | 5.40 | 3.76 | 84946990.88 | 56.69 | 5.00 | 3.76 | ||
Maximum of Months | 0.201123E+10 | 3729.93 | 30.57 | 19.31 | 98512319.56 | 56.70 | 30.57 | 19.31 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 17910978.04 | 780.03 | 11-JAN-16:05 | 14.03 | 10.30 | 92424451.84 | 56.69 | 11-JAN-04:30 | 14.03 | 10.30 |
February | 50790464.58 | 3061.62 | 27-FEB-16:02 | 19.32 | 12.38 | 84114510.67 | 56.69 | 03-FEB-03:49 | 19.32 | 12.38 |
March | 0.143102E+09 | 3080.57 | 18-MAR-15:02 | 20.10 | 10.35 | 94432650.86 | 56.69 | 03-MAR-05:19 | 20.10 | 10.35 |
April | 0.455685E+09 | 3274.98 | 01-APR-18:02 | 25.13 | 11.98 | 93040976.71 | 56.69 | 27-APR-03:09 | 11.10 | 8.33 |
May | 0.922857E+09 | 3330.22 | 14-MAY-15:02 | 23.30 | 12.38 | 97554726.07 | 56.69 | 15-MAY-21:30 | 13.35 | 11.02 |
June | 0.116249E+10 | 3103.48 | 24-JUN-18:02 | 18.72 | 11.75 | 94927148.38 | 56.69 | 28-JUN-21:30 | 17.50 | 13.87 |
July | 0.177330E+10 | 3375.83 | 31-JUL-18:02 | 26.42 | 18.31 | 98375884.35 | 56.70 | 24-JUL-21:00 | 26.42 | 18.31 |
August | 0.160105E+10 | 3355.12 | 10-AUG-18:02 | 30.57 | 19.31 | 98306819.36 | 56.70 | 09-AUG-21:00 | 30.57 | 19.31 |
September | 0.857426E+09 | 3147.93 | 22-SEP-15:02 | 23.58 | 17.29 | 94113066.37 | 56.70 | 06-SEP-23:00 | 23.58 | 17.29 |
October | 0.214983E+09 | 3217.72 | 04-OCT-15:02 | 21.60 | 11.48 | 94916364.82 | 56.69 | 05-OCT-00:20 | 12.57 | 9.63 |
November | 54977700.60 | 2960.32 | 04-NOV-15:02 | 20.92 | 15.94 | 90168525.03 | 56.69 | 16-NOV-22:30 | 5.00 | 4.37 |
December | 26310987.14 | 907.75 | 10-DEC-16:03 | 9.72 | 8.43 | 92497180.42 | 56.69 | 26-DEC-22:40 | 4.60 | 3.84 |
Annual Sum or Average | 0.728087E+10 | 0.112487E+10 | ||||||||
Minimum of Months | 17910978.04 | 780.03 | 9.72 | 8.43 | 84114510.67 | 56.69 | 4.60 | 3.84 | ||
Maximum of Months | 0.177330E+10 | 3375.83 | 30.57 | 19.31 | 98375884.35 | 56.70 | 30.57 | 19.31 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 99960886.34 | 1985.77 | 05-JAN-16:01 | 5.73 | 4.38 | 94473010.90 | 56.69 | 26-JAN-22:19 | 7.60 | 7.14 |
February | 0.252473E+09 | 2040.44 | 10-FEB-16:01 | 6.52 | 4.10 | 86535251.65 | 56.69 | 08-FEB-22:10 | 6.52 | 4.10 |
March | 0.415549E+09 | 2156.25 | 18-MAR-15:02 | 20.10 | 10.35 | 96790380.85 | 56.69 | 14-MAR-21:30 | 20.10 | 10.35 |
April | 0.602928E+09 | 2173.03 | 02-APR-15:02 | 20.60 | 11.87 | 94486912.12 | 56.69 | 26-APR-21:00 | 12.80 | 10.12 |
May | 0.745590E+09 | 2224.97 | 14-MAY-15:02 | 23.30 | 12.38 | 98021801.47 | 56.69 | 15-MAY-21:00 | 12.80 | 11.20 |
June | 0.841227E+09 | 2156.88 | 09-JUN-18:02 | 22.70 | 13.21 | 95166382.13 | 56.69 | 09-JUN-21:10 | 16.70 | 11.79 |
July | 0.112554E+10 | 2175.87 | 24-JUL-18:02 | 28.72 | 17.86 | 98448198.19 | 56.70 | 24-JUL-21:40 | 21.33 | 16.04 |
August | 0.123961E+10 | 2209.47 | 24-AUG-15:02 | 29.62 | 19.18 | 98518582.98 | 56.70 | 09-AUG-21:49 | 29.62 | 19.18 |
September | 0.102186E+10 | 2193.70 | 14-SEP-15:02 | 23.98 | 16.97 | 94822247.91 | 56.70 | 14-SEP-21:00 | 17.20 | 14.47 |
October | 0.606249E+09 | 2238.19 | 04-OCT-15:02 | 21.60 | 11.48 | 97173908.28 | 56.69 | 04-OCT-22:00 | 13.90 | 9.72 |
November | 0.191806E+09 | 1989.68 | 10-NOV-16:01 | 8.53 | 6.27 | 92272943.70 | 56.69 | 04-NOV-23:10 | 8.53 | 6.27 |
December | 0.159016E+09 | 1987.83 | 05-DEC-16:02 | 6.10 | 4.53 | 94716110.19 | 56.69 | 26-DEC-22:40 | 4.60 | 3.84 |
Annual Sum or Average | 0.730180E+10 | 0.114143E+10 | ||||||||
Minimum of Months | 99960886.34 | 1985.77 | 5.73 | 4.10 | 86535251.65 | 56.69 | 4.60 | 3.84 | ||
Maximum of Months | 0.123961E+10 | 2238.19 | 29.62 | 19.18 | 98518582.98 | 56.70 | 29.62 | 19.18 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.308825E+11 | 31352.01 | 30-JAN-23:31 | 5.93 | 4.15 | 0.189080E+11 | 12722.25 | 30-JAN-22:19 | 5.93 | 4.15 |
February | 0.288338E+11 | 31633.24 | 04-FEB-00:37 | 7.03 | 6.37 | 0.171591E+11 | 12777.81 | 03-FEB-23:00 | 7.03 | 6.37 |
March | 0.338671E+11 | 31550.20 | 03-MAR-05:08 | 7.12 | 6.62 | 0.192408E+11 | 13092.26 | 18-MAR-00:20 | 7.03 | 5.73 |
April | 0.348917E+11 | 31539.07 | 07-APR-23:14 | 7.93 | 7.28 | 0.186312E+11 | 13075.42 | 07-APR-23:40 | 7.57 | 6.58 |
May | 0.383270E+11 | 31151.59 | 12-MAY-05:38 | 7.40 | 7.02 | 0.193105E+11 | 13071.94 | 20-MAY-03:49 | 7.80 | 6.22 |
June | 0.387886E+11 | 29781.33 | 15-JUN-01:37 | 9.07 | 8.19 | 0.187229E+11 | 12421.38 | 15-JUN-01:30 | 9.07 | 8.19 |
July | 0.413285E+11 | 22509.39 | 24-JUL-21:10 | 22.43 | 16.40 | 0.192903E+11 | 11616.20 | 05-JUL-02:00 | 22.43 | 16.40 |
August | 0.412739E+11 | 22437.89 | 10-AUG-21:20 | 22.83 | 16.52 | 0.193657E+11 | 11654.50 | 03-AUG-03:20 | 22.83 | 16.52 |
September | 0.372108E+11 | 29862.59 | 28-SEP-05:32 | 8.30 | 7.58 | 0.186498E+11 | 12650.13 | 27-SEP-03:00 | 8.30 | 7.58 |
October | 0.350621E+11 | 31689.90 | 31-OCT-03:59 | 7.20 | 6.66 | 0.191697E+11 | 12888.27 | 11-OCT-02:49 | 7.20 | 6.66 |
November | 0.316791E+11 | 31282.57 | 20-NOV-03:42 | 7.88 | 6.22 | 0.184119E+11 | 12824.95 | 09-NOV-05:00 | 7.88 | 6.22 |
December | 0.311276E+11 | 30392.50 | 04-DEC-21:34 | 5.00 | 3.43 | 0.189414E+11 | 12529.96 | 07-DEC-23:19 | 6.10 | 5.28 |
Annual Sum or Average | 0.423273E+12 | 0.225801E+12 | ||||||||
Minimum of Months | 0.288338E+11 | 22437.89 | 5.00 | 3.43 | 0.171591E+11 | 11616.20 | 5.93 | 4.15 | ||
Maximum of Months | 0.413285E+11 | 31689.90 | 22.83 | 16.52 | 0.193657E+11 | 13092.26 | 22.83 | 16.52 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345970E+11 | 33105.66 | 30-JAN-23:31 | 5.93 | 4.15 | 0.191143E+11 | 12877.18 | 30-JAN-22:19 | 5.93 | 4.15 |
February | 0.322192E+11 | 33312.46 | 04-FEB-02:25 | 7.20 | 6.36 | 0.173205E+11 | 12894.05 | 03-FEB-23:00 | 7.20 | 6.36 |
March | 0.377000E+11 | 33196.19 | 03-MAR-05:08 | 7.12 | 6.62 | 0.193545E+11 | 13218.84 | 18-MAR-00:20 | 7.03 | 5.73 |
April | 0.385259E+11 | 34092.76 | 07-APR-23:14 | 7.93 | 7.28 | 0.187041E+11 | 13170.76 | 07-APR-23:40 | 7.57 | 6.58 |
May | 0.418709E+11 | 33648.57 | 12-MAY-05:45 | 7.30 | 6.96 | 0.193554E+11 | 13198.73 | 20-MAY-03:49 | 7.80 | 6.22 |
June | 0.420863E+11 | 31623.19 | 15-JUN-05:10 | 8.98 | 8.04 | 0.187460E+11 | 12491.53 | 15-JUN-01:30 | 8.98 | 8.04 |
July | 0.445243E+11 | 23704.66 | 24-JUL-21:20 | 22.07 | 16.28 | 0.193037E+11 | 11626.58 | 05-JUL-02:00 | 22.07 | 16.28 |
August | 0.444186E+11 | 23650.32 | 10-AUG-21:20 | 22.83 | 16.52 | 0.193833E+11 | 11667.65 | 03-AUG-03:20 | 22.83 | 16.52 |
September | 0.404713E+11 | 31728.24 | 28-SEP-05:20 | 8.30 | 7.66 | 0.186850E+11 | 12712.63 | 27-SEP-03:00 | 8.30 | 7.66 |
October | 0.387622E+11 | 33547.20 | 24-OCT-02:20 | 7.07 | 6.69 | 0.192680E+11 | 12973.00 | 11-OCT-02:49 | 7.07 | 6.69 |
November | 0.353794E+11 | 32890.02 | 20-NOV-03:42 | 7.88 | 6.22 | 0.185684E+11 | 12911.43 | 09-NOV-05:00 | 7.88 | 6.22 |
December | 0.348541E+11 | 32360.57 | 30-DEC-18:37 | 4.80 | 4.22 | 0.191417E+11 | 12648.59 | 20-DEC-23:10 | 4.80 | 4.22 |
Annual Sum or Average | 0.465409E+12 | 0.226945E+12 | ||||||||
Minimum of Months | 0.322192E+11 | 23650.32 | 4.80 | 4.15 | 0.173205E+11 | 11626.58 | 4.80 | 4.15 | ||
Maximum of Months | 0.445243E+11 | 34092.76 | 22.83 | 16.52 | 0.193833E+11 | 13218.84 | 22.83 | 16.52 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.482150E+11 | 37287.85 | 30-JAN-18:51 | 5.60 | 4.81 | 0.188307E+11 | 11516.54 | 28-JAN-18:40 | 5.60 | 4.81 |
February | 0.446695E+11 | 36821.63 | 08-FEB-17:21 | 6.15 | 3.07 | 0.170083E+11 | 11520.84 | 11-FEB-18:40 | 5.97 | 0.97 |
March | 0.510404E+11 | 39543.45 | 29-MAR-11:16 | 7.97 | 5.28 | 0.188527E+11 | 11406.05 | 04-MAR-18:49 | 7.97 | 5.28 |
April | 0.513588E+11 | 37908.16 | 11-APR-11:23 | 8.60 | 6.96 | 0.182413E+11 | 11382.34 | 08-APR-17:00 | 8.60 | 6.96 |
May | 0.544196E+11 | 38156.54 | 12-MAY-05:45 | 7.30 | 6.96 | 0.188499E+11 | 11319.66 | 20-MAY-17:19 | 16.87 | 9.98 |
June | 0.540695E+11 | 31669.09 | 15-JUN-05:50 | 9.32 | 8.19 | 0.182454E+11 | 11319.62 | 24-JUN-17:19 | 19.23 | 11.83 |
July | 0.565844E+11 | 31245.32 | 24-JUL-10:37 | 25.93 | 17.48 | 0.188536E+11 | 11319.69 | 15-JUL-17:19 | 25.93 | 17.48 |
August | 0.568717E+11 | 31285.32 | 13-AUG-10:40 | 24.17 | 17.28 | 0.188634E+11 | 11319.69 | 12-AUG-17:19 | 24.17 | 17.28 |
September | 0.531092E+11 | 33206.85 | 28-SEP-06:44 | 8.80 | 7.92 | 0.182432E+11 | 11319.66 | 23-SEP-17:19 | 8.80 | 7.92 |
October | 0.520377E+11 | 34742.99 | 24-OCT-06:20 | 6.47 | 6.47 | 0.188438E+11 | 11357.89 | 28-OCT-17:30 | 10.55 | 7.51 |
November | 0.481774E+11 | 37041.01 | 23-NOV-18:36 | 5.60 | 4.52 | 0.182328E+11 | 11524.10 | 25-NOV-18:49 | 7.70 | 6.65 |
December | 0.484905E+11 | 36356.03 | 13-DEC-18:19 | 6.47 | 2.58 | 0.188354E+11 | 11419.99 | 30-DEC-18:00 | 4.40 | 3.92 |
Annual Sum or Average | 0.619044E+12 | 0.221900E+12 | ||||||||
Minimum of Months | 0.446695E+11 | 31245.32 | 5.60 | 2.58 | 0.170083E+11 | 11319.62 | 4.40 | 0.97 | ||
Maximum of Months | 0.568717E+11 | 39543.45 | 25.93 | 17.48 | 0.188634E+11 | 11524.10 | 25.93 | 17.48 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362216E+10 | 4728.93 | 05-JAN-15:03 | 6.60 | 5.08 | 0.127063E+10 | 778.00 | 30-JAN-22:19 | 5.60 | 3.84 |
February | 0.464713E+10 | 5869.36 | 08-FEB-15:02 | 7.70 | 3.86 | 0.115907E+10 | 831.03 | 27-FEB-22:40 | 12.20 | 10.25 |
March | 0.716678E+10 | 6436.29 | 15-MAR-06:07 | 6.88 | 5.85 | 0.131768E+10 | 845.01 | 14-MAR-21:40 | 6.88 | 5.85 |
April | 0.815759E+10 | 6582.45 | 24-APR-23:34 | 7.40 | 5.44 | 0.133255E+10 | 939.82 | 27-APR-21:30 | 15.80 | 11.30 |
May | 0.938277E+10 | 6536.01 | 18-MAY-06:25 | 5.85 | 5.34 | 0.145286E+10 | 945.96 | 15-MAY-21:30 | 5.85 | 5.34 |
June | 0.973335E+10 | 5561.11 | 13-JUN-23:40 | 10.00 | 8.89 | 0.146159E+10 | 979.25 | 28-JUN-21:30 | 17.50 | 13.87 |
July | 0.106692E+11 | 5838.08 | 24-JUL-15:03 | 30.32 | 18.75 | 0.156339E+10 | 1007.37 | 24-JUL-21:40 | 21.33 | 16.04 |
August | 0.108213E+11 | 6834.73 | 10-AUG-14:20 | 29.67 | 19.07 | 0.157561E+10 | 1007.38 | 10-AUG-21:10 | 22.92 | 16.74 |
September | 0.942356E+10 | 5595.24 | 27-SEP-05:14 | 7.57 | 7.21 | 0.143613E+10 | 976.35 | 14-SEP-21:30 | 7.57 | 7.21 |
October | 0.803386E+10 | 6030.03 | 12-OCT-23:32 | 7.43 | 6.58 | 0.135202E+10 | 905.42 | 04-OCT-21:40 | 7.43 | 6.58 |
November | 0.548261E+10 | 5456.03 | 28-NOV-23:25 | 7.25 | 6.32 | 0.124298E+10 | 815.62 | 05-NOV-23:10 | 7.25 | 6.32 |
December | 0.399921E+10 | 5086.88 | 05-DEC-11:20 | 8.87 | 5.64 | 0.127244E+10 | 778.74 | 04-DEC-22:10 | 8.87 | 5.64 |
Annual Sum or Average | 0.911395E+11 | 0.164370E+11 | ||||||||
Minimum of Months | 0.362216E+10 | 4728.93 | 5.85 | 3.86 | 0.115907E+10 | 778.00 | 5.60 | 3.84 | ||
Maximum of Months | 0.108213E+11 | 6834.73 | 30.32 | 19.07 | 0.157561E+10 | 1007.38 | 22.92 | 16.74 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 284636.27 | 541.58 | 28-JAN-23:23 | 6.10 |
February | 1054906.61 | 1055.13 | 22-FEB-06:07 | 7.62 |
March | 5053534.72 | 1822.39 | 03-MAR-00:55 | 6.70 |
April | 4750217.52 | 1269.34 | 17-APR-07:50 | 5.68 |
May | 3516801.16 | 1109.00 | 10-MAY-03:23 | 7.50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 4515.52 | 75.26 | 27-SEP-05:07 | 7.38 |
October | 1524911.85 | 1940.24 | 30-OCT-05:03 | 7.20 |
November | 153729.09 | 1049.32 | 29-NOV-00:02 | 7.35 |
December | 323707.93 | 655.16 | 10-DEC-08:33 | 6.70 |
Annual Sum or Average | 16666960.68 | |||
Minimum of Months | 0.00 | 0.00 | 5.68 | |
Maximum of Months | 5053534.72 | 1940.24 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160812E+09 | 896.97 | 30-JAN-22:39 | 5.60 |
February | 68468790.61 | 930.33 | 04-FEB-00:17 | 6.87 |
March | 26647060.47 | 1911.73 | 19-MAR-07:50 | 8.22 |
April | 23164059.31 | 1918.39 | 23-APR-07:06 | 8.48 |
May | 22614921.81 | 826.24 | 10-MAY-21:59 | 6.70 |
June | 1219659.41 | 582.30 | 14-JUN-06:20 | 10.20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 2560388.18 | 853.50 | 27-SEP-05:07 | 7.38 |
October | 33018667.15 | 1902.42 | 25-OCT-07:20 | 8.17 |
November | 40527904.31 | 946.73 | 29-NOV-00:02 | 7.35 |
December | 0.160096E+09 | 1765.51 | 10-DEC-19:47 | 6.78 |
Annual Sum or Average | 0.539130E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.60 | |
Maximum of Months | 0.160812E+09 | 1918.39 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4510388.25 | 317.88 | 22-JAN-10:57 | 6.10 |
February | 1481977.86 | 322.41 | 22-FEB-06:07 | 7.62 |
March | 2188804.99 | 256.81 | 04-MAR-07:13 | 5.97 |
April | 1202033.87 | 227.02 | 17-APR-07:50 | 5.68 |
May | 701957.53 | 145.86 | 19-MAY-05:09 | 7.88 |
June | 1994.40 | 16.58 | 15-JUN-03:37 | 8.30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 93153.57 | 165.55 | 27-SEP-05:07 | 7.38 |
October | 2913732.07 | 240.47 | 30-OCT-05:03 | 7.20 |
November | 3364758.17 | 353.88 | 23-NOV-18:25 | 5.60 |
December | 4051958.68 | 353.76 | 02-DEC-07:16 | 6.10 |
Annual Sum or Average | 20510759.39 | |||
Minimum of Months | 0.00 | 0.00 | 5.60 | |
Maximum of Months | 4510388.25 | 353.88 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9080819.55 | 377.31 | 29-JAN-07:13 | 6.50 |
February | 4704880.27 | 387.60 | 22-FEB-06:07 | 7.62 |
March | 7465452.83 | 382.74 | 03-MAR-00:55 | 6.70 |
April | 4821394.55 | 343.42 | 01-APR-05:24 | 7.75 |
May | 3066262.94 | 255.49 | 20-MAY-03:40 | 7.80 |
June | 81464.78 | 104.38 | 15-JUN-03:37 | 8.30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 348507.46 | 251.97 | 27-SEP-04:43 | 7.20 |
October | 8262826.76 | 402.95 | 30-OCT-05:03 | 7.20 |
November | 7548961.06 | 384.07 | 29-NOV-00:02 | 7.35 |
December | 8280796.90 | 435.55 | 02-DEC-07:16 | 6.10 |
Annual Sum or Average | 53661367.10 | |||
Minimum of Months | 0.00 | 0.00 | 6.10 | |
Maximum of Months | 9080819.55 | 435.55 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22922098.77 | 197.10 | 28-JAN-23:23 | 6.10 |
February | 10976113.75 | 187.79 | 22-FEB-06:07 | 7.62 |
March | 4883999.73 | 201.58 | 03-MAR-00:55 | 6.70 |
April | 3246688.41 | 178.73 | 01-APR-05:24 | 7.75 |
May | 2169613.51 | 135.27 | 20-MAY-03:40 | 7.80 |
June | 65945.70 | 61.07 | 15-JUN-03:37 | 8.30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 254109.21 | 137.93 | 27-SEP-05:07 | 7.38 |
October | 5030132.80 | 206.79 | 30-OCT-05:03 | 7.20 |
November | 4597206.77 | 205.34 | 29-NOV-00:02 | 7.35 |
December | 15306019.07 | 258.86 | 10-DEC-19:47 | 6.78 |
Annual Sum or Average | 69451927.73 | |||
Minimum of Months | 0.00 | 0.00 | 6.10 | |
Maximum of Months | 22922098.77 | 258.86 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 412067.96 | 1441.02 | 27-JAN-02:15 | 7.60 |
February | 254703.32 | 1268.53 | 03-FEB-03:38 | 7.57 |
March | 573447.35 | 1525.10 | 03-MAR-03:52 | 7.20 |
April | 1741890.48 | 1794.26 | 06-APR-02:24 | 7.20 |
May | 2075152.00 | 1958.72 | 20-MAY-03:04 | 7.80 |
June | 235134.15 | 1605.85 | 15-JUN-03:37 | 8.30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 117304.53 | 1071.34 | 27-SEP-01:55 | 8.30 |
October | 3625792.25 | 2756.83 | 13-OCT-01:49 | 6.78 |
November | 212248.73 | 1215.31 | 09-NOV-05:37 | 7.03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 9247740.77 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 3625792.25 | 2756.83 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35892544.34 | 2590.22 | 29-JAN-07:13 | 6.50 |
February | 11610605.94 | 3015.23 | 27-FEB-07:27 | 7.50 |
March | 27182561.27 | 2843.55 | 04-MAR-07:13 | 5.97 |
April | 18563466.06 | 2750.26 | 17-APR-06:27 | 6.10 |
May | 9596669.08 | 2027.55 | 10-MAY-05:46 | 7.80 |
June | 145452.47 | 444.58 | 15-JUN-03:03 | 8.30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 2474412.89 | 1715.92 | 27-SEP-05:07 | 7.38 |
October | 28054306.80 | 2755.61 | 24-OCT-06:18 | 6.47 |
November | 30564366.68 | 3043.39 | 17-NOV-08:11 | 6.87 |
December | 36585365.69 | 3311.28 | 02-DEC-07:16 | 6.10 |
Annual Sum or Average | 0.200670E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.97 | |
Maximum of Months | 36585365.69 | 3311.28 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52715231.20 | 4992.15 | 23-JAN-18:10 | 6.02 |
February | 12058431.06 | 4365.03 | 20-FEB-12:55 | 6.70 |
March | 19412998.65 | 5068.23 | 03-MAR-00:55 | 6.70 |
April | 9672410.11 | 3510.98 | 17-APR-07:50 | 5.68 |
May | 1494254.04 | 1402.43 | 18-MAY-06:10 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 156085.98 | 1268.92 | 27-SEP-05:07 | 7.38 |
October | 14792887.66 | 3964.27 | 30-OCT-05:03 | 7.20 |
November | 35753426.73 | 6490.26 | 23-NOV-18:25 | 5.60 |
December | 45215875.13 | 5754.40 | 02-DEC-07:16 | 6.10 |
Annual Sum or Average | 0.191272E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.60 | |
Maximum of Months | 52715231.20 | 6490.26 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100331E+10 | 2155.79 | 15-JAN-09:01 | -2.5 |
February | 0.597776E+09 | 2138.34 | 19-FEB-09:01 | -3.1 |
March | 0.297823E+09 | 2093.93 | 22-MAR-15:01 | 6.70 |
April | 99630321.85 | 2059.07 | 18-APR-08:61 | 4.50 |
May | 17498146.66 | 1840.14 | 18-MAY-08:62 | 6.28 |
June | 1979255.50 | 777.28 | 18-JUN-08:03 | 12.57 |
July | 1129302.65 | 825.74 | 16-JUL-15:04 | 17.80 |
August | 1149720.02 | 739.32 | 27-AUG-15:04 | 18.42 |
September | 6811244.45 | 927.30 | 27-SEP-08:62 | 9.08 |
October | 0.138582E+09 | 2081.38 | 28-OCT-08:61 | 8.07 |
November | 0.562939E+09 | 2156.53 | 14-NOV-19:01 | 5.68 |
December | 0.918910E+09 | 2173.20 | 13-DEC-19:01 | 5.00 |
Annual Sum or Average | 0.364754E+10 | |||
Minimum of Months | 1129302.65 | 739.32 | -3.1 | |
Maximum of Months | 0.100331E+10 | 2173.20 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115381E+10 | 2134.26 | 07-JAN-09:01 | -3.1 |
February | 0.761850E+09 | 2134.71 | 19-FEB-09:01 | -3.1 |
March | 0.405804E+09 | 2075.45 | 28-MAR-08:61 | 6.78 |
April | 0.136220E+09 | 2030.65 | 18-APR-08:61 | 4.50 |
May | 21561519.22 | 1877.47 | 18-MAY-08:62 | 6.28 |
June | 2173729.89 | 749.90 | 18-JUN-08:03 | 12.57 |
July | 959978.30 | 719.82 | 04-JUL-18:04 | 14.08 |
August | 1285922.76 | 671.57 | 27-AUG-15:04 | 18.42 |
September | 9057900.11 | 1427.39 | 28-SEP-08:62 | 10.28 |
October | 0.204720E+09 | 2050.38 | 28-OCT-08:61 | 8.07 |
November | 0.678759E+09 | 2115.34 | 14-NOV-19:01 | 5.68 |
December | 0.107739E+10 | 2124.80 | 16-DEC-19:01 | 7.20 |
Annual Sum or Average | 0.445359E+10 | |||
Minimum of Months | 959978.30 | 671.57 | -3.1 | |
Maximum of Months | 0.115381E+10 | 2134.71 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40488576.37 | 134.17 | 05-JAN-06:00 | -1.1 |
February | 11759313.24 | 163.53 | 19-FEB-06:00 | -5.6 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:05 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 5757096.89 | 81.06 | 30-NOV-24:00 | 4.40 |
December | 44084253.84 | 148.33 | 26-DEC-04:03 | -1.0 |
Annual Sum or Average | 0.102089E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 44084253.84 | 163.53 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106213E+09 | 594.92 | 15-JAN-16:01 | 1.60 |
February | 65363729.90 | 589.00 | 13-FEB-16:01 | 0.60 |
March | 4939130.07 | 565.95 | 05-MAR-16:01 | 6.02 |
April | 635379.45 | 383.03 | 25-APR-15:03 | 16.20 |
May | 441378.79 | 302.83 | 12-MAY-15:05 | 16.78 |
June | 230703.05 | 282.45 | 07-JUN-15:05 | 15.92 |
July | 192508.31 | 238.00 | 25-JUL-08:06 | 15.18 |
August | 178573.14 | 258.23 | 21-AUG-08:05 | 15.53 |
September | 489146.89 | 233.35 | 24-SEP-15:05 | 16.20 |
October | 1289144.60 | 548.72 | 31-OCT-15:01 | 10.82 |
November | 30853068.15 | 580.96 | 30-NOV-16:01 | 4.50 |
December | 84265552.09 | 590.40 | 26-DEC-16:02 | 3.27 |
Annual Sum or Average | 0.295092E+09 | |||
Minimum of Months | 178573.14 | 233.35 | 0.60 | |
Maximum of Months | 0.106213E+09 | 594.92 | 16.78 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100795E+10 | 2110.59 | 16-JAN-09:01 | -0.5 |
February | 0.600555E+09 | 2101.98 | 18-FEB-19:01 | -0.8 |
March | 0.287779E+09 | 2062.94 | 22-MAR-15:01 | 6.70 |
April | 93177833.11 | 2023.84 | 18-APR-08:61 | 4.50 |
May | 22745097.13 | 1806.77 | 18-MAY-08:62 | 6.28 |
June | 2665606.26 | 608.73 | 02-JUN-18:04 | 19.45 |
July | 1042865.97 | 739.66 | 16-JUL-15:04 | 17.80 |
August | 939426.18 | 715.96 | 27-AUG-15:04 | 18.42 |
September | 8934064.42 | 612.30 | 06-SEP-15:05 | 16.02 |
October | 0.142011E+09 | 2042.13 | 31-OCT-18:01 | 8.80 |
November | 0.565539E+09 | 2115.86 | 14-NOV-19:01 | 5.68 |
December | 0.925772E+09 | 2131.42 | 13-DEC-19:01 | 5.00 |
Annual Sum or Average | 0.365911E+10 | |||
Minimum of Months | 939426.18 | 608.73 | -0.8 | |
Maximum of Months | 0.100795E+10 | 2131.42 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116078E+10 | 2086.15 | 15-JAN-09:01 | -2.5 |
February | 0.762144E+09 | 2077.10 | 19-FEB-19:01 | -1.1 |
March | 0.385025E+09 | 2039.18 | 22-MAR-15:01 | 6.70 |
April | 0.125466E+09 | 1994.61 | 18-APR-08:61 | 4.50 |
May | 28571720.01 | 1840.69 | 18-MAY-08:62 | 6.28 |
June | 3086911.26 | 529.21 | 29-JUN-15:05 | 17.30 |
July | 920896.04 | 675.73 | 16-JUL-15:04 | 17.80 |
August | 945325.67 | 692.58 | 27-AUG-15:04 | 18.42 |
September | 11917282.19 | 987.39 | 26-SEP-15:02 | 11.97 |
October | 0.207820E+09 | 2011.65 | 31-OCT-18:01 | 8.80 |
November | 0.673786E+09 | 2077.17 | 14-NOV-19:01 | 5.68 |
December | 0.107714E+10 | 2084.15 | 18-DEC-19:01 | 4.72 |
Annual Sum or Average | 0.443760E+10 | |||
Minimum of Months | 920896.04 | 529.21 | -2.5 | |
Maximum of Months | 0.116078E+10 | 2086.15 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 23531824.53 | 748.42 | 28-JAN-23:23 | 6.10 |
February | 10825246.90 | 712.46 | 27-FEB-07:27 | 7.50 |
March | 18072796.95 | 699.20 | 22-MAR-00:03 | 7.12 |
April | 11534493.23 | 661.56 | 01-APR-05:24 | 7.75 |
May | 6477641.86 | 452.29 | 20-MAY-03:40 | 7.80 |
June | 183607.38 | 185.04 | 15-JUN-03:37 | 8.30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 992741.97 | 518.35 | 27-SEP-05:07 | 7.38 |
October | 20212261.96 | 776.88 | 30-OCT-05:03 | 7.20 |
November | 18109774.86 | 770.26 | 29-NOV-00:02 | 7.35 |
December | 30255852.81 | 1125.03 | 01-DEC-18:20 | 6.10 |
Annual Sum or Average | 0.140196E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.10 | |
Maximum of Months | 30255852.81 | 1125.03 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146684E+10 | 2553.44 | 15-JAN-09:01 | -2.5 |
February | 0.926414E+09 | 2537.29 | 19-FEB-09:01 | -3.1 |
March | 0.543364E+09 | 2507.76 | 22-MAR-15:01 | 6.70 |
April | 0.225777E+09 | 2455.46 | 18-APR-08:61 | 4.50 |
May | 72470261.77 | 2319.78 | 18-MAY-08:62 | 6.28 |
June | 12975557.04 | 900.17 | 11-JUN-08:03 | 14.08 |
July | 1534704.90 | 791.82 | 16-JUL-15:04 | 17.80 |
August | 1534123.75 | 890.40 | 19-AUG-08:03 | 15.08 |
September | 30640566.71 | 1896.92 | 27-SEP-08:62 | 9.08 |
October | 0.303020E+09 | 2480.39 | 28-OCT-08:61 | 8.07 |
November | 0.893988E+09 | 2542.82 | 14-NOV-19:01 | 5.68 |
December | 0.136329E+10 | 2548.65 | 17-DEC-19:01 | 5.50 |
Annual Sum or Average | 0.584185E+10 | |||
Minimum of Months | 1534123.75 | 791.82 | -3.1 | |
Maximum of Months | 0.146684E+10 | 2553.44 | 17.80 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165702E+10 | 2524.08 | 07-JAN-09:01 | -3.1 |
February | 0.113656E+10 | 2523.85 | 19-FEB-09:01 | -3.1 |
March | 0.696340E+09 | 2472.12 | 22-MAR-15:01 | 6.70 |
April | 0.290905E+09 | 2416.98 | 18-APR-08:61 | 4.50 |
May | 85429347.05 | 2292.73 | 27-MAY-08:61 | 8.48 |
June | 15103484.29 | 708.62 | 11-JUN-08:03 | 14.08 |
July | 1387940.36 | 902.63 | 16-JUL-15:04 | 17.80 |
August | 1770262.47 | 785.83 | 19-AUG-08:03 | 15.08 |
September | 42251695.14 | 2242.94 | 28-SEP-08:62 | 10.28 |
October | 0.425740E+09 | 2437.59 | 28-OCT-08:61 | 8.07 |
November | 0.104126E+10 | 2493.95 | 14-NOV-19:01 | 5.68 |
December | 0.156304E+10 | 2506.61 | 25-DEC-19:01 | -0.7 |
Annual Sum or Average | 0.695681E+10 | |||
Minimum of Months | 1387940.36 | 708.62 | -3.1 | |
Maximum of Months | 0.165702E+10 | 2524.08 | 17.80 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.439315E+09 | 1366.75 | 02-JAN-16:11 | 8.17 |
February | 0.229948E+09 | 1352.78 | 17-FEB-09:01 | 1.02 |
March | 93322242.35 | 1332.71 | 22-MAR-15:01 | 6.70 |
April | 34290780.52 | 1313.07 | 18-APR-08:61 | 4.50 |
May | 8827105.08 | 1160.82 | 18-MAY-08:62 | 6.28 |
June | 1383768.60 | 564.24 | 23-JUN-15:04 | 16.88 |
July | 786269.75 | 558.35 | 16-JUL-15:04 | 17.80 |
August | 762519.03 | 440.84 | 21-AUG-08:03 | 15.53 |
September | 3332202.08 | 485.45 | 21-SEP-15:04 | 17.30 |
October | 33321703.46 | 1315.29 | 28-OCT-08:61 | 8.07 |
November | 0.210849E+09 | 1367.82 | 14-NOV-19:01 | 5.68 |
December | 0.407177E+09 | 1379.57 | 19-DEC-19:01 | 5.60 |
Annual Sum or Average | 0.146332E+10 | |||
Minimum of Months | 762519.03 | 440.84 | 1.02 | |
Maximum of Months | 0.439315E+09 | 1379.57 | 17.80 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 116219.33 | 665.61 | 03-MAR-00:55 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:05 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 58812.62 | 411.57 | 13-OCT-01:09 | 7.12 |
November | 37455.74 | 190.92 | 17-NOV-08:11 | 6.87 |
December | 24948.66 | 415.81 | 02-DEC-07:16 | 6.10 |
Annual Sum or Average | 237436.35 | |||
Minimum of Months | 0.00 | 0.00 | 5.92 | |
Maximum of Months | 116219.33 | 665.61 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 42720.37 | 234.67 | 03-MAR-00:55 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:05 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 4300.36 | 50.17 | 13-OCT-01:09 | 7.12 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 9.22 |
December | 8086.64 | 134.78 | 02-DEC-07:16 | 6.10 |
Annual Sum or Average | 55107.37 | |||
Minimum of Months | 0.00 | 0.00 | 5.92 | |
Maximum of Months | 42720.37 | 234.67 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:05 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 27301.00 | 171.54 | 13-OCT-01:49 | 6.78 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 27301.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 27301.00 | 171.54 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 49313738.59 | 1524.52 | 30-JAN-22:39 | 5.60 |
February | 33139515.70 | 1449.94 | 27-FEB-07:27 | 7.50 |
March | 37932742.77 | 1471.86 | 03-MAR-00:55 | 6.70 |
April | 29117099.72 | 1435.48 | 17-APR-07:50 | 5.68 |
May | 22240481.74 | 1215.39 | 19-MAY-05:09 | 7.88 |
June | 910142.47 | 646.86 | 15-JUN-03:37 | 8.30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 3311869.10 | 1347.18 | 27-SEP-05:07 | 7.38 |
October | 47994232.77 | 1672.56 | 30-OCT-05:03 | 7.20 |
November | 34563475.23 | 1626.67 | 29-NOV-00:02 | 7.35 |
December | 48656667.91 | 1943.64 | 10-DEC-19:47 | 6.78 |
Annual Sum or Average | 0.307180E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.60 | |
Maximum of Months | 49313738.59 | 1943.64 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.147273E+11 | 14185.34 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.132974E+11 | 14185.34 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.147727E+11 | 14185.34 | 01-MAR-20:10 | 0.127855E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.142280E+11 | 14185.34 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.147528E+11 | 14185.34 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.142932E+11 | 14185.34 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.146876E+11 | 14185.34 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.147784E+11 | 14185.34 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.142337E+11 | 14185.34 | 01-SEP-19:10 | 0.123352E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.147216E+11 | 14185.34 | 02-OCT-19:10 | 0.127549E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.142819E+11 | 14185.34 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.146876E+11 | 14185.34 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.173462E+12 | 0.150255E+12 | ||||
Minimum of Months | 0.132974E+11 | 14185.34 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.147784E+11 | 14185.34 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.731324E+09 | 704.41 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.660319E+09 | 704.41 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.733578E+09 | 704.41 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.706528E+09 | 704.41 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.732592E+09 | 704.41 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.709769E+09 | 704.41 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.729351E+09 | 704.41 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.733860E+09 | 704.41 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.706810E+09 | 704.41 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.731042E+09 | 704.41 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.709205E+09 | 704.41 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.729351E+09 | 704.41 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.861373E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.660319E+09 | 704.41 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.733860E+09 | 704.41 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.846876E+09 | 815.72 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.764651E+09 | 815.72 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.849486E+09 | 815.72 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.818162E+09 | 815.72 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.848344E+09 | 815.72 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.821915E+09 | 815.72 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.844592E+09 | 815.72 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.849812E+09 | 815.72 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.818489E+09 | 815.72 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.846549E+09 | 815.72 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.821262E+09 | 815.72 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.844592E+09 | 815.72 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.997473E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.764651E+09 | 815.72 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.849812E+09 | 815.72 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.141236E+10 | 1360.40 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.127524E+10 | 1360.40 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.141672E+10 | 1360.40 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.136448E+10 | 1360.40 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.141481E+10 | 1360.40 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.137074E+10 | 1360.40 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.140855E+10 | 1360.40 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.141726E+10 | 1360.40 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.136502E+10 | 1360.40 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.141182E+10 | 1360.40 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.136965E+10 | 1360.40 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.140855E+10 | 1360.40 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.166352E+11 | 0.124712E+11 | ||||
Minimum of Months | 0.127524E+10 | 1360.40 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.141726E+10 | 1360.40 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.236418E+09 | 227.72 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.213464E+09 | 227.72 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.237147E+09 | 227.72 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.228402E+09 | 227.72 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.236828E+09 | 227.72 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.229450E+09 | 227.72 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.235780E+09 | 227.72 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.237238E+09 | 227.72 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.228493E+09 | 227.72 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.236327E+09 | 227.72 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.229268E+09 | 227.72 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.235780E+09 | 227.72 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.278459E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.213464E+09 | 227.72 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.237238E+09 | 227.72 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.370859E+09 | 357.21 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.334852E+09 | 357.21 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.372002E+09 | 357.21 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.358285E+09 | 357.21 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.371502E+09 | 357.21 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.359929E+09 | 357.21 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.369859E+09 | 357.21 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.372145E+09 | 357.21 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.358428E+09 | 357.21 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.370717E+09 | 357.21 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.359643E+09 | 357.21 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.369859E+09 | 357.21 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.436808E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.334852E+09 | 357.21 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.372145E+09 | 357.21 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.163951E+10 | 1761.91 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.144231E+10 | 1761.91 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.154951E+10 | 1761.91 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.142806E+10 | 1761.91 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.143166E+10 | 1761.91 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.133627E+10 | 1761.91 | 01-JUN-19:40 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.139613E+10 | 1761.91 | 03-JUL-19:00 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.144637E+10 | 1761.91 | 01-AUG-19:19 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.147816E+10 | 1761.91 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.158607E+10 | 1761.91 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.157370E+10 | 1761.91 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.163911E+10 | 1761.91 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.179469E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.133627E+10 | 1761.91 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.163951E+10 | 1761.91 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104669E+11 | 10265.18 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.941056E+10 | 10265.18 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.104030E+11 | 10265.18 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.995618E+10 | 10265.18 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.102736E+11 | 10265.18 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.990700E+10 | 10265.18 | 01-JUN-19:30 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.102020E+11 | 10265.18 | 03-JUL-19:49 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.103054E+11 | 10265.18 | 01-AUG-19:19 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.100074E+11 | 10265.18 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.104087E+11 | 10265.18 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.101340E+11 | 10265.18 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.104437E+11 | 10265.18 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.121918E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.941056E+10 | 10265.18 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.104669E+11 | 10265.18 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85091918.49 | 76.99 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 76846309.13 | 76.99 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 84415649.14 | 76.99 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 82445007.08 | 76.99 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 84753783.81 | 76.99 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 81790910.76 | 76.99 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 85418966.65 | 76.99 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 84415649.14 | 76.99 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 82467180.11 | 76.99 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 85080831.98 | 76.99 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 82117958.92 | 76.99 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 85430053.17 | 76.99 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.100027E+10 | 0.300992E+10 | ||||
Minimum of Months | 76846309.13 | 76.99 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 85430053.17 | 76.99 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85115186.72 | 77.01 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 76867322.62 | 77.01 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 84438732.44 | 77.01 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 82467551.52 | 77.01 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 84776959.58 | 77.01 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 81813276.33 | 77.01 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 85442324.32 | 77.01 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 84438732.44 | 77.01 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 82489730.61 | 77.01 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 85104097.18 | 77.01 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 82140413.93 | 77.01 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 85453413.86 | 77.01 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.100055E+10 | 0.301074E+10 | ||||
Minimum of Months | 76867322.62 | 77.01 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 85453413.86 | 77.01 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.232638E+10 | 2240.78 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.210051E+10 | 2240.78 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.233355E+10 | 2240.78 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.224750E+10 | 2240.78 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.233041E+10 | 2240.78 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.225781E+10 | 2240.78 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.232011E+10 | 2240.78 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.233445E+10 | 2240.78 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.224840E+10 | 2240.78 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.232548E+10 | 2240.78 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.225602E+10 | 2240.78 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.232011E+10 | 2240.78 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.274007E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.210051E+10 | 2240.78 | 0.00 | 0.00 | |
Maximum of Months | 0.233445E+10 | 2240.78 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85115186.72 | 77.01 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 76867322.62 | 77.01 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 84438732.44 | 77.01 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 82467551.52 | 77.01 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 84776959.58 | 77.01 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 81813276.33 | 77.01 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 85442324.32 | 77.01 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 84438732.44 | 77.01 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 82489730.61 | 77.01 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 85104097.18 | 77.01 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 82140413.93 | 77.01 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 85453413.86 | 77.01 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.100055E+10 | 0.301074E+10 | ||||
Minimum of Months | 76867322.62 | 77.01 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 85453413.86 | 77.01 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.305847E+10 | 3094.06 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.272414E+10 | 3094.06 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.297416E+10 | 3094.06 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.279895E+10 | 3094.06 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.285332E+10 | 3094.06 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.271329E+10 | 3094.06 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.280106E+10 | 3094.06 | 10-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.286712E+10 | 3094.06 | 01-AUG-19:19 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.285021E+10 | 3094.06 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.300644E+10 | 3094.06 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.294968E+10 | 3094.06 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.305788E+10 | 3094.06 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.346547E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.271329E+10 | 3094.06 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.305847E+10 | 3094.06 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.305847E+10 | 3094.06 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.272414E+10 | 3094.06 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.297416E+10 | 3094.06 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.279895E+10 | 3094.06 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.285332E+10 | 3094.06 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.271329E+10 | 3094.06 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.280106E+10 | 3094.06 | 10-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.286712E+10 | 3094.06 | 01-AUG-19:19 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.285021E+10 | 3094.06 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.300644E+10 | 3094.06 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.294968E+10 | 3094.06 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.305788E+10 | 3094.06 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.346547E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.271329E+10 | 3094.06 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.305847E+10 | 3094.06 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113146E+10 | 1089.83 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.102161E+10 | 1089.83 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.113495E+10 | 1089.83 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.109310E+10 | 1089.83 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.113342E+10 | 1089.83 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.109811E+10 | 1089.83 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.112841E+10 | 1089.83 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.113539E+10 | 1089.83 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.109354E+10 | 1089.83 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.113103E+10 | 1089.83 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.109724E+10 | 1089.83 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.112841E+10 | 1089.83 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.133267E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.102161E+10 | 1089.83 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.113539E+10 | 1089.83 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.246211E+10 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.222306E+10 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.246970E+10 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.237864E+10 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.246638E+10 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.238954E+10 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.245547E+10 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.247065E+10 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.237958E+10 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.246116E+10 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.238765E+10 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.245547E+10 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.289994E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.222306E+10 | 2371.52 | 0.00 | 0.00 | |
Maximum of Months | 0.247065E+10 | 2371.52 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.147273E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.132974E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.147727E+11 | 0.127855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.142280E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.147528E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.142932E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.146876E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.147784E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.142337E+11 | 0.123352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.147216E+11 | 0.127549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.142819E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.146876E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.173462E+12 | 0.150255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.132974E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.147784E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.731324E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552174E+09 |
February | 0.179968E+10 | 0.660319E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458411E+09 |
March | 0.199990E+10 | 0.733578E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426248E+09 |
April | 0.192973E+10 | 0.706528E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1507342.39 | 0.335918E+09 |
May | 0.199475E+10 | 0.732592E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 567217.13 | 0.277382E+09 |
June | 0.193394E+10 | 0.709769E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2028503.61 | 0.186826E+09 |
July | 0.199054E+10 | 0.729351E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8749374.86 | 0.144174E+09 |
August | 0.199896E+10 | 0.733860E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16577804.44 | 0.119928E+09 |
September | 0.192879E+10 | 0.706810E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 177249.10 | 0.208666E+09 |
October | 0.199148E+10 | 0.731042E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324523E+09 |
November | 0.192552E+10 | 0.709205E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416150E+09 |
December | 0.199054E+10 | 0.729351E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521793E+09 |
Annual Sum or Average | 0.234744E+11 | 0.861373E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29607491.52 | 0.397219E+10 |
Minimum of Months | 0.179968E+10 | 0.660319E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119928E+09 |
Maximum of Months | 0.199990E+10 | 0.733860E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16577804.44 | 0.552174E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.846876E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221075E+09 |
February | 0.208403E+10 | 0.764651E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185667E+09 |
March | 0.231589E+10 | 0.849486E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178005E+09 |
April | 0.223463E+10 | 0.818162E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 693627.97 | 0.144784E+09 |
May | 0.230993E+10 | 0.848344E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 198787.33 | 0.124728E+09 |
June | 0.223950E+10 | 0.821915E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 580727.24 | 89956306.54 |
July | 0.230505E+10 | 0.844592E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3116861.03 | 73028324.99 |
August | 0.231480E+10 | 0.849812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6381287.68 | 62762288.96 |
September | 0.223354E+10 | 0.818489E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 113413.63 | 96775535.48 |
October | 0.230614E+10 | 0.846549E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140537E+09 |
November | 0.222975E+10 | 0.821262E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172017E+09 |
December | 0.230505E+10 | 0.844592E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210293E+09 |
Annual Sum or Average | 0.271834E+11 | 0.997473E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11084704.88 | 0.169963E+10 |
Minimum of Months | 0.208403E+10 | 0.764651E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62762288.96 |
Maximum of Months | 0.231589E+10 | 0.849812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6381287.68 | 0.221075E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.141236E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505112E+09 |
February | 0.440737E+09 | 0.127524E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419026E+09 |
March | 0.489771E+09 | 0.141672E+10 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396646E+09 |
April | 0.472586E+09 | 0.136448E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2265437.36 | 0.322818E+09 |
May | 0.488511E+09 | 0.141481E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 832855.19 | 0.281232E+09 |
June | 0.473617E+09 | 0.137074E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1733102.48 | 0.205017E+09 |
July | 0.487480E+09 | 0.140855E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7807777.55 | 0.167323E+09 |
August | 0.489542E+09 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15755070.58 | 0.144847E+09 |
September | 0.472357E+09 | 0.136502E+10 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 678324.80 | 0.218267E+09 |
October | 0.487709E+09 | 0.141182E+10 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314355E+09 |
November | 0.471555E+09 | 0.136965E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387872E+09 |
December | 0.487480E+09 | 0.140855E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476767E+09 |
Annual Sum or Average | 0.574883E+10 | 0.166352E+11 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29072567.96 | 0.383928E+10 |
Minimum of Months | 0.440737E+09 | 0.127524E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144847E+09 |
Maximum of Months | 0.489771E+09 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15755070.58 | 0.505112E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.236418E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289883E+09 |
February | 0.339028E+09 | 0.213464E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239562E+09 |
March | 0.376747E+09 | 0.237147E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224260E+09 |
April | 0.363528E+09 | 0.228402E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1345363.78 | 0.181970E+09 |
May | 0.375778E+09 | 0.236828E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 516299.79 | 0.158021E+09 |
June | 0.364321E+09 | 0.229450E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1098878.63 | 0.114514E+09 |
July | 0.374985E+09 | 0.235780E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4719138.45 | 92977003.79 |
August | 0.376571E+09 | 0.237238E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9429318.51 | 80308877.51 |
September | 0.363352E+09 | 0.228493E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 412721.50 | 0.122011E+09 |
October | 0.375161E+09 | 0.236327E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176734E+09 |
November | 0.362735E+09 | 0.229268E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220472E+09 |
December | 0.374985E+09 | 0.235780E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273098E+09 |
Annual Sum or Average | 0.442217E+10 | 0.278459E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17521720.66 | 0.217381E+10 |
Minimum of Months | 0.339028E+09 | 0.213464E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80308877.51 |
Maximum of Months | 0.376747E+09 | 0.237238E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9429318.51 | 0.289883E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.370859E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770533E+09 |
February | 0.139600E+10 | 0.334852E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639778E+09 |
March | 0.155131E+10 | 0.372002E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605114E+09 |
April | 0.149688E+10 | 0.358285E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 2215368.69 | 0.485693E+09 |
May | 0.154732E+10 | 0.371502E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 1074452.33 | 0.411354E+09 |
June | 0.150015E+10 | 0.359929E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 2208660.35 | 0.292676E+09 |
July | 0.154405E+10 | 0.369859E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 11725381.15 | 0.229684E+09 |
August | 0.155059E+10 | 0.372145E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 23353835.62 | 0.196229E+09 |
September | 0.149615E+10 | 0.358428E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 1268195.75 | 0.312947E+09 |
October | 0.154478E+10 | 0.370717E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473375E+09 |
November | 0.149361E+10 | 0.359643E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597833E+09 |
December | 0.154405E+10 | 0.369859E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731739E+09 |
Annual Sum or Average | 0.182090E+11 | 0.436808E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 41845893.88 | 0.574696E+10 |
Minimum of Months | 0.139600E+10 | 0.334852E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196229E+09 |
Maximum of Months | 0.155131E+10 | 0.372145E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 23353835.62 | 0.770533E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.163951E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124752E+10 |
February | 0.236489E+11 | 0.144231E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104950E+10 |
March | 0.262800E+11 | 0.154951E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998007E+09 |
April | 0.253579E+11 | 0.142806E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2858530.66 | 0.804653E+09 |
May | 0.262123E+11 | 0.143166E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 770295.64 | 0.681724E+09 |
June | 0.254132E+11 | 0.133627E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3111627.92 | 0.482730E+09 |
July | 0.261570E+11 | 0.139613E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17210401.98 | 0.387386E+09 |
August | 0.262677E+11 | 0.144637E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33901988.95 | 0.330096E+09 |
September | 0.253456E+11 | 0.147816E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 277574.98 | 0.527575E+09 |
October | 0.261693E+11 | 0.158607E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.781365E+09 |
November | 0.253025E+11 | 0.157370E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.958494E+09 |
December | 0.261570E+11 | 0.163911E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118466E+10 |
Annual Sum or Average | 0.308468E+12 | 0.179469E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58130420.13 | 0.943371E+10 |
Minimum of Months | 0.236489E+11 | 0.133627E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330096E+09 |
Maximum of Months | 0.262800E+11 | 0.163951E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33901988.95 | 0.124752E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.104669E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371768E+10 |
February | 0.702046E+11 | 0.941056E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313208E+10 |
March | 0.780153E+11 | 0.104030E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300923E+10 |
April | 0.752779E+11 | 0.995618E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9486330.06 | 0.244882E+10 |
May | 0.778146E+11 | 0.102736E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2277806.46 | 0.210720E+10 |
June | 0.754422E+11 | 0.990700E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7894664.33 | 0.153067E+10 |
July | 0.776503E+11 | 0.102020E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47959382.77 | 0.123506E+10 |
August | 0.779788E+11 | 0.103054E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96653089.38 | 0.106202E+10 |
September | 0.752414E+11 | 0.100074E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 950265.33 | 0.164243E+10 |
October | 0.776868E+11 | 0.104087E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238885E+10 |
November | 0.751137E+11 | 0.101340E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290768E+10 |
December | 0.776503E+11 | 0.104437E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353926E+10 |
Annual Sum or Average | 0.915726E+12 | 0.121918E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165222E+09 | 0.287210E+11 |
Minimum of Months | 0.702046E+11 | 0.941056E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106202E+10 |
Maximum of Months | 0.780153E+11 | 0.104669E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96653089.38 | 0.371768E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313975E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262319E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245503E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1324402.25 | 0.196041E+09 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 764531.18 | 0.163321E+09 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1825824.17 | 0.111518E+09 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7274405.44 | 82909699.23 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13812637.84 | 68322560.28 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1046698.68 | 0.118721E+09 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4042.57 | 0.186401E+09 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237926E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296757E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26052542.12 | 0.228371E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68322560.28 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13812637.84 | 0.313975E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311521E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258612E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241507E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1380422.05 | 0.193245E+09 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 769727.71 | 0.161931E+09 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1823218.39 | 0.110548E+09 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7319392.84 | 82329602.63 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13982538.09 | 67660013.54 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1073638.62 | 0.117017E+09 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4177.68 | 0.182629E+09 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235264E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293713E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26353115.37 | 0.225598E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67660013.54 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13982538.09 | 0.311521E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 85091918.49 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80962146.16 |
February | 0.00 | 76846309.13 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71374084.53 |
March | 0.00 | 84415649.14 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72463549.39 |
April | 0.00 | 82445007.08 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 237966.67 | 61109732.01 |
May | 0.00 | 84753783.81 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51798.44 | 52637666.91 |
June | 0.00 | 81790910.76 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 187473.92 | 38335808.44 |
July | 0.00 | 85418966.65 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1246166.61 | 30312928.63 |
August | 0.00 | 84415649.14 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2647843.49 | 25863012.76 |
September | 0.00 | 82467180.11 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58417.66 | 40663145.29 |
October | 0.00 | 85080831.98 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58486402.74 |
November | 0.00 | 82117958.92 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64963067.30 |
December | 0.00 | 85430053.17 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78172028.81 |
Annual Sum or Average | 0.00 | 0.100027E+10 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4429666.79 | 0.675344E+09 |
Minimum of Months | 0.00 | 76846309.13 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25863012.76 |
Maximum of Months | 0.00 | 85430053.17 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2647843.49 | 80962146.16 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 85115186.72 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88560578.47 |
February | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73190807.50 |
March | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68060137.78 |
April | 0.293479E+09 | 82467551.52 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 481540.14 | 53849727.09 |
May | 0.303504E+09 | 84776959.58 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 297317.48 | 44502602.24 |
June | 0.293842E+09 | 81813276.33 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 621096.22 | 30078599.13 |
July | 0.303141E+09 | 85442324.32 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2358865.07 | 22153413.64 |
August | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4433044.29 | 18290868.33 |
September | 0.293479E+09 | 82489730.61 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 411927.24 | 31961090.44 |
October | 0.303322E+09 | 85104097.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1673.21 | 51263508.14 |
November | 0.293661E+09 | 82140413.93 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66951575.47 |
December | 0.303141E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83438339.27 |
Annual Sum or Average | 0.357224E+10 | 0.100055E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8605463.65 | 0.632301E+09 |
Minimum of Months | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18290868.33 |
Maximum of Months | 0.303685E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4433044.29 | 88560578.47 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313712E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262418E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246613E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1351119.12 | 0.197696E+09 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 795772.48 | 0.163808E+09 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1857633.08 | 0.112498E+09 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7355134.34 | 83375856.19 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13844669.30 | 68926902.05 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1082766.50 | 0.118844E+09 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4256.10 | 0.187077E+09 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237799E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296430E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26291350.92 | 0.228920E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68926902.05 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13844669.30 | 0.313712E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311395E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258508E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242739E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1408227.88 | 0.195471E+09 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 802270.19 | 0.162902E+09 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1862559.57 | 0.112146E+09 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7375192.20 | 83182333.42 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13883097.23 | 68603295.79 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1103274.59 | 0.117609E+09 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4529.56 | 0.183552E+09 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235105E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293396E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26439151.22 | 0.226461E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68603295.79 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13883097.23 | 0.311395E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.232638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387517E+09 |
February | 0.348285E+10 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320328E+09 |
March | 0.387034E+10 | 0.233355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301106E+09 |
April | 0.373454E+10 | 0.224750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1571465.23 | 0.246078E+09 |
May | 0.386038E+10 | 0.233041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443229.79 | 0.215709E+09 |
June | 0.374269E+10 | 0.225781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1122858.36 | 0.155875E+09 |
July | 0.385223E+10 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5545241.74 | 0.126648E+09 |
August | 0.386853E+10 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11288907.95 | 0.110049E+09 |
September | 0.373273E+10 | 0.224840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245353.47 | 0.166485E+09 |
October | 0.385404E+10 | 0.232548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235811E+09 |
November | 0.372639E+10 | 0.225602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292906E+09 |
December | 0.385223E+10 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365330E+09 |
Annual Sum or Average | 0.454292E+11 | 0.274007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20217056.53 | 0.292384E+10 |
Minimum of Months | 0.348285E+10 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110049E+09 |
Maximum of Months | 0.387034E+10 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11288907.95 | 0.387517E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313538E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261792E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245111E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1290481.89 | 0.196230E+09 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 710116.92 | 0.163881E+09 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1756820.24 | 0.112224E+09 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7092876.09 | 83581357.26 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13528207.03 | 68763207.19 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 996948.50 | 0.119052E+09 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2863.31 | 0.186086E+09 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237274E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296482E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25378313.99 | 0.228401E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68763207.19 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13528207.03 | 0.313538E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311790E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258234E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240871E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1336809.37 | 0.193289E+09 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 717891.28 | 0.162529E+09 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1750999.57 | 0.111401E+09 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7109079.14 | 83103471.69 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13658161.68 | 68097668.42 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1034784.32 | 0.117320E+09 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3126.25 | 0.181899E+09 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234755E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293688E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25610851.61 | 0.225698E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68097668.42 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13658161.68 | 0.311790E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 85115186.72 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163776E+09 |
February | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136940E+09 |
March | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127960E+09 |
April | 0.293479E+09 | 82467551.52 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 666953.35 | 0.101786E+09 |
May | 0.303504E+09 | 84776959.58 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 386340.43 | 84215640.36 |
June | 0.293842E+09 | 81813276.33 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 918692.01 | 57588381.59 |
July | 0.303141E+09 | 85442324.32 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3676191.37 | 42756741.37 |
August | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6946393.46 | 35263233.09 |
September | 0.293479E+09 | 82489730.61 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 523280.67 | 61455113.81 |
October | 0.303322E+09 | 85104097.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1135.56 | 97335296.41 |
November | 0.293661E+09 | 82140413.93 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124328E+09 |
December | 0.303141E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154712E+09 |
Annual Sum or Average | 0.357224E+10 | 0.100055E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13118986.87 | 0.118812E+10 |
Minimum of Months | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35263233.09 |
Maximum of Months | 0.303685E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6946393.46 | 0.163776E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.305847E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904023E+09 |
February | 0.415303E+11 | 0.272414E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.755530E+09 |
March | 0.461508E+11 | 0.297416E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723306E+09 |
April | 0.445315E+11 | 0.279895E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1440644.59 | 0.588573E+09 |
May | 0.460320E+11 | 0.285332E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83899.06 | 0.508209E+09 |
June | 0.446286E+11 | 0.271329E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 766984.11 | 0.373584E+09 |
July | 0.459349E+11 | 0.280106E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8132988.82 | 0.299212E+09 |
August | 0.461292E+11 | 0.286712E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18258841.99 | 0.257240E+09 |
September | 0.445099E+11 | 0.285021E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116020.65 | 0.394129E+09 |
October | 0.459565E+11 | 0.300644E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573223E+09 |
November | 0.444343E+11 | 0.294968E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708933E+09 |
December | 0.459349E+11 | 0.305788E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.859626E+09 |
Annual Sum or Average | 0.541708E+12 | 0.346547E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 28799379.21 | 0.694559E+10 |
Minimum of Months | 0.415303E+11 | 0.271329E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257240E+09 |
Maximum of Months | 0.461508E+11 | 0.305847E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18258841.99 | 0.904023E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.305847E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913268E+09 |
February | 0.415303E+11 | 0.272414E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762891E+09 |
March | 0.461508E+11 | 0.297416E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729236E+09 |
April | 0.445315E+11 | 0.279895E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1426117.70 | 0.592539E+09 |
May | 0.460320E+11 | 0.285332E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83890.63 | 0.510674E+09 |
June | 0.446286E+11 | 0.271329E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 766947.94 | 0.375152E+09 |
July | 0.459349E+11 | 0.280106E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8100348.25 | 0.300096E+09 |
August | 0.461292E+11 | 0.286712E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18130003.44 | 0.258312E+09 |
September | 0.445099E+11 | 0.285021E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116008.38 | 0.396418E+09 |
October | 0.459565E+11 | 0.300644E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578364E+09 |
November | 0.444343E+11 | 0.294968E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716261E+09 |
December | 0.459349E+11 | 0.305788E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.868627E+09 |
Annual Sum or Average | 0.541708E+12 | 0.346547E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 28623316.35 | 0.700184E+10 |
Minimum of Months | 0.415303E+11 | 0.271329E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258312E+09 |
Maximum of Months | 0.461508E+11 | 0.305847E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18130003.44 | 0.913268E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113146E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823142E+09 |
February | 0.369574E+10 | 0.102161E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685330E+09 |
March | 0.410691E+10 | 0.113495E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655398E+09 |
April | 0.396281E+10 | 0.109310E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 1283727.94 | 0.530190E+09 |
May | 0.409635E+10 | 0.113342E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 77256.76 | 0.454785E+09 |
June | 0.397146E+10 | 0.109811E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 694429.66 | 0.332975E+09 |
July | 0.408770E+10 | 0.112841E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 7265200.08 | 0.266236E+09 |
August | 0.410499E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 16221786.92 | 0.229549E+09 |
September | 0.396089E+10 | 0.109354E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 106706.07 | 0.353285E+09 |
October | 0.408962E+10 | 0.113103E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518686E+09 |
November | 0.395417E+10 | 0.109724E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645159E+09 |
December | 0.408770E+10 | 0.112841E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.783907E+09 |
Annual Sum or Average | 0.482060E+11 | 0.133267E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 25649107.42 | 0.627864E+10 |
Minimum of Months | 0.369574E+10 | 0.102161E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229549E+09 |
Maximum of Months | 0.410691E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 16221786.92 | 0.823142E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.246211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688190E+09 |
February | 0.368610E+10 | 0.222306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.569728E+09 |
March | 0.409620E+10 | 0.246970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534413E+09 |
April | 0.395248E+10 | 0.237864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2029053.84 | 0.435185E+09 |
May | 0.408566E+10 | 0.246638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245387.31 | 0.380416E+09 |
June | 0.396110E+10 | 0.238954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 965927.56 | 0.278554E+09 |
July | 0.407704E+10 | 0.245547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7634111.87 | 0.226596E+09 |
August | 0.409429E+10 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16928434.14 | 0.191638E+09 |
September | 0.395056E+10 | 0.237958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155413.21 | 0.291386E+09 |
October | 0.407896E+10 | 0.246116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414119E+09 |
November | 0.394385E+10 | 0.238765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521116E+09 |
December | 0.407704E+10 | 0.245547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649032E+09 |
Annual Sum or Average | 0.480803E+11 | 0.289994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27958327.93 | 0.518037E+10 |
Minimum of Months | 0.368610E+10 | 0.222306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191638E+09 |
Maximum of Months | 0.409620E+10 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16928434.14 | 0.688190E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 14185.34 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 14185.34 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 14185.34 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 14185.34 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 14185.34 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 14185.34 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 14185.34 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 14185.34 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 14185.34 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 14185.34 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 14185.34 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 14185.34 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 14185.34 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 14185.34 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 704.41 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 323.33 | 15-JAN-08:00 |
February | 1169.53 | 01-FEB-00:10 | 704.41 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 339.03 | 19-FEB-06:00 |
March | 1169.53 | 01-MAR-00:10 | 704.41 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 275.51 | 01-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 704.41 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.77 | 01-APR-17:00 | 243.94 | 19-APR-05:00 |
May | 1169.53 | 01-MAY-00:10 | 704.41 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.35 | 05-MAY-16:00 | 206.21 | 11-MAY-03:30 |
June | 1169.53 | 01-JUN-00:10 | 704.41 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.70 | 28-JUN-17:00 | 159.09 | 15-JUN-03:43 |
July | 1169.53 | 01-JUL-00:10 | 704.41 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.55 | 24-JUL-15:00 | 120.51 | 07-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 704.41 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.50 | 10-AUG-17:00 | 123.62 | 01-AUG-05:20 |
September | 1169.53 | 01-SEP-00:10 | 704.41 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.71 | 14-SEP-17:00 | 176.59 | 27-SEP-04:43 |
October | 1169.53 | 01-OCT-23:10 | 704.41 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 190.35 | 13-OCT-07:00 |
November | 1169.53 | 01-NOV-00:10 | 704.41 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 264.95 | 11-NOV-08:00 |
December | 1169.53 | 01-DEC-00:10 | 704.41 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 291.33 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 704.41 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.51 | |||||
Maximum of Months | 1169.53 | 704.41 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 94.50 | 339.03 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 815.72 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 127.49 | 15-JAN-08:00 |
February | 1354.32 | 01-FEB-00:10 | 815.72 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 131.39 | 19-FEB-05:00 |
March | 1354.32 | 01-MAR-00:10 | 815.72 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 113.56 | 01-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 815.72 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.08 | 01-APR-16:00 | 100.39 | 19-APR-05:00 |
May | 1354.32 | 01-MAY-00:10 | 815.72 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.75 | 05-MAY-16:00 | 88.02 | 11-MAY-03:00 |
June | 1354.32 | 01-JUN-00:10 | 815.72 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.79 | 28-JUN-17:00 | 69.42 | 15-JUN-03:43 |
July | 1354.32 | 01-JUL-00:10 | 815.72 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.21 | 24-JUL-15:00 | 57.91 | 07-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 815.72 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.49 | 29-AUG-16:00 | 58.65 | 01-AUG-05:25 |
September | 1354.32 | 01-SEP-00:10 | 815.72 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.97 | 22-SEP-16:00 | 75.46 | 27-SEP-04:43 |
October | 1354.32 | 01-OCT-23:10 | 815.72 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 82.87 | 13-OCT-05:00 |
November | 1354.32 | 01-NOV-00:10 | 815.72 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 107.80 | 11-NOV-08:00 |
December | 1354.32 | 01-DEC-00:10 | 815.72 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 114.52 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 815.72 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.91 | |||||
Maximum of Months | 1354.32 | 815.72 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 35.49 | 131.39 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 1360.40 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 294.95 | 15-JAN-08:00 |
February | 286.42 | 01-FEB-00:10 | 1360.40 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 309.29 | 19-FEB-06:00 |
March | 286.42 | 01-MAR-00:10 | 1360.40 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 259.23 | 01-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 1360.40 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.86 | 01-APR-16:00 | 225.72 | 19-APR-05:00 |
May | 286.42 | 01-MAY-00:10 | 1360.40 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.64 | 05-MAY-16:00 | 200.86 | 11-MAY-03:00 |
June | 286.42 | 01-JUN-00:10 | 1360.40 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.03 | 28-JUN-17:00 | 155.62 | 15-JUN-03:47 |
July | 286.42 | 01-JUL-00:10 | 1360.40 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.21 | 24-JUL-15:00 | 130.03 | 19-JUL-05:00 |
August | 286.42 | 01-AUG-00:10 | 1360.40 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.72 | 10-AUG-17:00 | 134.21 | 01-AUG-06:10 |
September | 286.42 | 01-SEP-00:10 | 1360.40 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.57 | 22-SEP-16:00 | 168.41 | 27-SEP-04:43 |
October | 286.42 | 01-OCT-23:10 | 1360.40 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 185.58 | 12-OCT-06:57 |
November | 286.42 | 01-NOV-00:10 | 1360.40 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 244.35 | 11-NOV-08:00 |
December | 286.42 | 01-DEC-00:10 | 1360.40 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 265.74 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.03 | |||||
Maximum of Months | 286.42 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 85.72 | 309.29 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 227.72 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 170.17 | 15-JAN-08:00 |
February | 220.32 | 01-FEB-00:10 | 227.72 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 178.45 | 19-FEB-06:00 |
March | 220.32 | 01-MAR-00:10 | 227.72 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 147.13 | 01-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 227.72 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.94 | 01-APR-16:00 | 128.80 | 19-APR-05:00 |
May | 220.32 | 01-MAY-00:10 | 227.72 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.53 | 05-MAY-16:00 | 114.68 | 11-MAY-03:00 |
June | 220.32 | 01-JUN-00:10 | 227.72 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.32 | 28-JUN-17:00 | 88.64 | 15-JUN-03:47 |
July | 220.32 | 01-JUL-00:10 | 227.72 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.50 | 24-JUL-15:00 | 74.25 | 19-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 227.72 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.45 | 10-AUG-17:00 | 75.76 | 01-AUG-05:40 |
September | 220.32 | 01-SEP-00:10 | 227.72 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.96 | 22-SEP-16:00 | 95.68 | 27-SEP-04:43 |
October | 220.32 | 01-OCT-23:10 | 227.72 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 105.78 | 13-OCT-05:00 |
November | 220.32 | 01-NOV-00:10 | 227.72 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 139.44 | 11-NOV-07:50 |
December | 220.32 | 01-DEC-00:10 | 227.72 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 153.31 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 227.72 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.25 | |||||
Maximum of Months | 220.32 | 227.72 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 49.45 | 178.45 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 357.21 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 451.17 | 15-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 357.21 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 459.77 | 19-FEB-08:00 |
March | 907.20 | 01-MAR-00:10 | 357.21 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 390.68 | 01-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 357.21 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 69.90 | 01-APR-16:00 | 347.81 | 19-APR-05:10 |
May | 907.20 | 01-MAY-00:10 | 357.21 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 37.46 | 05-MAY-16:00 | 323.61 | 18-MAY-06:10 |
June | 907.20 | 01-JUN-00:10 | 357.21 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 65.81 | 28-JUN-17:00 | 258.30 | 15-JUN-05:07 |
July | 907.20 | 01-JUL-00:10 | 357.21 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 108.60 | 24-JUL-15:00 | 186.57 | 04-JUL-05:55 |
August | 907.20 | 01-AUG-00:10 | 357.21 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 135.38 | 10-AUG-17:00 | 191.91 | 01-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 357.21 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 40.24 | 14-SEP-17:00 | 279.45 | 28-SEP-06:55 |
October | 907.20 | 01-OCT-23:10 | 357.21 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 321.14 | 16-OCT-06:45 |
November | 907.20 | 01-NOV-00:10 | 357.21 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 377.34 | 13-NOV-20:43 |
December | 907.20 | 01-DEC-00:10 | 357.21 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 410.42 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 186.57 | ||||||
Maximum of Months | 907.20 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 135.38 | 459.77 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1761.91 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 714.87 | 15-JAN-08:00 |
February | 15368.40 | 01-FEB-00:10 | 1761.91 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 749.52 | 19-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 1761.91 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 620.61 | 01-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1761.91 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.95 | 01-APR-16:00 | 566.83 | 19-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1761.91 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.05 | 05-MAY-16:00 | 493.13 | 11-MAY-03:00 |
June | 15368.40 | 01-JUN-00:10 | 1761.91 | 01-JUN-19:40 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.03 | 28-JUN-17:00 | 405.34 | 15-JUN-03:43 |
July | 15368.40 | 01-JUL-00:10 | 1761.91 | 03-JUL-19:00 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.81 | 24-JUL-15:00 | 322.07 | 07-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 1761.91 | 01-AUG-19:19 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.81 | 10-AUG-17:00 | 321.06 | 01-AUG-05:20 |
September | 15368.40 | 01-SEP-00:10 | 1761.91 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.82 | 14-SEP-17:00 | 442.49 | 27-SEP-04:43 |
October | 15368.40 | 01-OCT-23:10 | 1761.91 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 480.83 | 13-OCT-01:55 |
November | 15368.40 | 01-NOV-00:10 | 1761.91 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 595.82 | 11-NOV-08:00 |
December | 15368.40 | 01-DEC-00:10 | 1761.91 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 644.03 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1761.91 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.06 | |||||
Maximum of Months | 15368.40 | 1761.91 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 203.81 | 749.52 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 10265.18 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2134.97 | 15-JAN-08:00 |
February | 45622.98 | 01-FEB-00:10 | 10265.18 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2199.86 | 19-FEB-05:00 |
March | 45622.98 | 01-MAR-00:10 | 10265.18 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1898.21 | 01-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 10265.18 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.27 | 01-APR-16:00 | 1707.75 | 19-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 10265.18 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.66 | 05-MAY-16:00 | 1494.07 | 11-MAY-03:00 |
June | 45622.98 | 01-JUN-00:10 | 10265.18 | 01-JUN-19:30 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.09 | 28-JUN-17:00 | 1201.02 | 15-JUN-03:47 |
July | 45622.98 | 01-JUL-00:10 | 10265.18 | 03-JUL-19:49 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 501.20 | 24-JUL-15:00 | 990.68 | 07-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 10265.18 | 01-AUG-19:19 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 577.31 | 10-AUG-17:00 | 970.22 | 01-AUG-05:20 |
September | 45622.98 | 01-SEP-00:10 | 10265.18 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.46 | 14-SEP-17:00 | 1302.85 | 27-SEP-04:43 |
October | 45622.98 | 01-OCT-23:10 | 10265.18 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1410.54 | 13-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 10265.18 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 1810.49 | 11-NOV-08:00 |
December | 45622.98 | 01-DEC-00:10 | 10265.18 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1925.85 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 10265.18 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 970.22 | |||||
Maximum of Months | 45622.98 | 10265.18 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 577.31 | 2199.86 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 188.81 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 197.91 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 161.03 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.05 | 27-APR-15:40 | 142.70 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 05-MAY-16:00 | 120.77 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.97 | 28-JUN-17:00 | 91.04 | 15-JUN-03:58 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 24-JUL-15:10 | 71.02 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 10-AUG-17:00 | 77.11 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 | 14-SEP-17:00 | 99.71 | 27-SEP-04:53 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 04-OCT-15:10 | 111.52 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 154.89 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 170.21 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.02 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 197.91 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 188.80 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 197.90 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 161.01 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 | 27-APR-15:10 | 142.69 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 05-MAY-16:00 | 120.76 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.97 | 28-JUN-17:00 | 91.04 | 15-JUN-03:58 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 24-JUL-15:10 | 71.01 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 10-AUG-17:00 | 76.28 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 | 14-SEP-17:00 | 99.70 | 27-SEP-04:53 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 04-OCT-15:10 | 111.51 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 154.87 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 170.20 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.01 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 197.90 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 76.99 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 48.01 | 15-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 76.99 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 50.64 | 19-FEB-06:00 |
March | 0.00 | 01-MAR-00:10 | 76.99 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 44.87 | 01-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 76.99 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 | 27-APR-15:13 | 38.87 | 19-APR-05:10 |
May | 0.00 | 01-MAY-00:10 | 76.99 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.03 | 05-MAY-16:00 | 35.22 | 11-MAY-03:00 |
June | 0.00 | 01-JUN-00:10 | 76.99 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 | 28-JUN-17:00 | 27.21 | 01-JUN-03:53 |
July | 0.00 | 01-JUL-00:10 | 76.99 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.21 | 24-JUL-15:00 | 23.12 | 19-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 76.99 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 | 10-AUG-17:00 | 23.67 | 01-AUG-05:55 |
September | 0.00 | 01-SEP-00:10 | 76.99 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.03 | 14-SEP-17:00 | 28.23 | 27-SEP-03:53 |
October | 0.00 | 01-OCT-00:10 | 76.99 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 33.93 | 13-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 76.99 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 42.79 | 11-NOV-23:00 |
December | 0.00 | 01-DEC-00:10 | 76.99 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 45.43 | 06-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 76.99 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.12 | |||||
Maximum of Months | 0.00 | 76.99 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 | 50.64 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 77.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 52.69 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 77.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 55.24 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 77.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 44.94 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 77.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27-APR-15:10 | 39.83 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 77.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 05-MAY-16:00 | 33.70 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 77.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.32 | 28-JUN-17:00 | 25.41 | 15-JUN-03:55 |
July | 180.00 | 01-JUL-00:10 | 77.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 | 24-JUL-15:10 | 19.82 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 77.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.31 | 10-AUG-17:00 | 20.51 | 01-AUG-07:30 |
September | 180.00 | 01-SEP-00:10 | 77.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.20 | 14-SEP-17:00 | 27.83 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 77.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 04-OCT-15:05 | 31.12 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 77.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 43.23 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 77.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 47.50 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.82 | |||||
Maximum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 19.31 | 55.24 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 188.81 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 197.91 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 161.03 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 | 27-APR-15:10 | 142.70 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 05-MAY-16:00 | 120.76 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.97 | 28-JUN-17:00 | 91.04 | 15-JUN-03:58 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.14 | 24-JUL-15:10 | 71.02 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 10-AUG-17:00 | 81.63 | 01-AUG-07:50 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 | 14-SEP-17:00 | 99.71 | 27-SEP-04:53 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 04-OCT-15:10 | 111.52 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 154.89 | 11-NOV-07:20 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 170.21 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.02 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 197.91 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 188.80 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 197.90 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 161.01 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 | 27-APR-15:10 | 142.69 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 05-MAY-16:00 | 120.76 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.97 | 28-JUN-17:00 | 91.04 | 15-JUN-03:58 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 24-JUL-15:10 | 71.01 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.16 | 10-AUG-17:00 | 81.21 | 01-AUG-07:50 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 | 14-SEP-17:00 | 99.70 | 27-SEP-04:53 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 04-OCT-15:08 | 111.51 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 154.88 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 170.20 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.01 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 69.16 | 197.90 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 2240.78 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 227.31 | 15-JAN-08:00 |
February | 2263.36 | 01-FEB-00:10 | 2240.78 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 238.34 | 19-FEB-06:00 |
March | 2263.36 | 01-MAR-00:10 | 2240.78 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 195.32 | 01-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 2240.78 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.27 | 01-APR-16:00 | 173.36 | 19-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 2240.78 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.42 | 05-MAY-16:00 | 155.45 | 11-MAY-03:00 |
June | 2263.36 | 01-JUN-00:10 | 2240.78 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.86 | 28-JUN-17:00 | 120.13 | 15-JUN-03:43 |
July | 2263.36 | 01-JUL-00:10 | 2240.78 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.35 | 24-JUL-15:00 | 99.95 | 07-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 2240.78 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.22 | 29-AUG-16:00 | 102.39 | 01-AUG-05:25 |
September | 2263.36 | 01-SEP-00:10 | 2240.78 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.51 | 22-SEP-16:00 | 128.32 | 27-SEP-04:43 |
October | 2263.36 | 01-OCT-23:10 | 2240.78 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 142.66 | 13-OCT-05:00 |
November | 2263.36 | 01-NOV-00:10 | 2240.78 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 186.32 | 11-NOV-07:50 |
December | 2263.36 | 01-DEC-00:10 | 2240.78 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 204.84 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.95 | ||||
Maximum of Months | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.22 | 238.34 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 189.30 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 198.40 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 161.50 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.65 | 27-APR-16:00 | 143.17 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 | 05-MAY-16:00 | 121.22 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.58 | 28-JUN-17:00 | 91.48 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.74 | 24-JUL-15:10 | 71.45 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.80 | 10-AUG-17:00 | 75.10 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.39 | 14-SEP-17:00 | 100.15 | 27-SEP-04:53 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 04-OCT-15:10 | 111.97 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 155.36 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 170.69 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.45 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 68.80 | 198.40 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 189.28 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 198.38 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 161.49 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.65 | 27-APR-15:50 | 143.15 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 | 05-MAY-16:00 | 121.21 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.57 | 28-JUN-17:00 | 91.48 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.75 | 24-JUL-15:10 | 71.45 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.80 | 10-AUG-17:00 | 74.25 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.38 | 14-SEP-17:00 | 100.14 | 27-SEP-04:53 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 04-OCT-15:10 | 111.96 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 155.34 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 170.67 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.45 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 68.80 | 198.38 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 77.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 96.85 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 77.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 101.51 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 77.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 82.63 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 77.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.29 | 27-APR-15:50 | 73.25 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 77.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.97 | 05-MAY-16:00 | 62.02 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 77.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.72 | 28-JUN-17:00 | 46.81 | 15-JUN-03:55 |
July | 180.00 | 01-JUL-00:10 | 77.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 | 24-JUL-15:10 | 36.56 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 77.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.20 | 10-AUG-17:00 | 38.40 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 77.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.99 | 14-SEP-17:00 | 51.24 | 27-SEP-04:53 |
October | 180.00 | 01-OCT-00:10 | 77.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 | 04-OCT-15:10 | 57.29 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 77.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 79.49 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 77.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 87.33 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.56 | |||||
Maximum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 35.20 | 101.51 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3094.06 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 515.30 | 15-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 3094.06 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 528.95 | 19-FEB-06:10 |
March | 26988.77 | 01-MAR-00:10 | 3094.06 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 446.49 | 01-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3094.06 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.59 | 01-APR-16:00 | 401.22 | 19-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 3094.06 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.69 | 05-MAY-16:00 | 346.78 | 11-MAY-03:10 |
June | 26988.77 | 01-JUN-00:10 | 3094.06 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.32 | 28-JUN-17:00 | 286.83 | 15-JUN-03:43 |
July | 26988.77 | 01-JUL-00:10 | 3094.06 | 10-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.06 | 24-JUL-15:00 | 227.85 | 05-JUL-02:50 |
August | 26988.77 | 01-AUG-00:10 | 3094.06 | 01-AUG-19:19 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.20 | 10-AUG-17:00 | 228.96 | 06-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 3094.06 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.72 | 14-SEP-17:00 | 314.93 | 27-SEP-04:43 |
October | 26988.77 | 01-OCT-23:10 | 3094.06 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 327.59 | 13-OCT-01:55 |
November | 26988.77 | 01-NOV-00:10 | 3094.06 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 430.94 | 11-NOV-07:10 |
December | 26988.77 | 01-DEC-00:10 | 3094.06 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 469.25 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.85 | |||||
Maximum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 122.20 | 528.95 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3094.06 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 515.31 | 15-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 3094.06 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 533.04 | 19-FEB-06:10 |
March | 26988.77 | 01-MAR-00:10 | 3094.06 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 446.49 | 01-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3094.06 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.13 | 27-APR-16:00 | 401.23 | 19-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 3094.06 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.69 | 05-MAY-16:00 | 346.78 | 11-MAY-03:10 |
June | 26988.77 | 01-JUN-00:10 | 3094.06 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.32 | 28-JUN-17:00 | 287.82 | 15-JUN-03:43 |
July | 26988.77 | 01-JUL-00:10 | 3094.06 | 10-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.06 | 24-JUL-15:00 | 228.02 | 05-JUL-02:50 |
August | 26988.77 | 01-AUG-00:10 | 3094.06 | 01-AUG-19:19 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.20 | 10-AUG-17:00 | 229.09 | 06-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 3094.06 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.72 | 14-SEP-17:00 | 316.16 | 27-SEP-04:43 |
October | 26988.77 | 01-OCT-23:10 | 3094.06 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 329.95 | 16-OCT-06:45 |
November | 26988.77 | 01-NOV-00:10 | 3094.06 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 430.95 | 11-NOV-07:10 |
December | 26988.77 | 01-DEC-00:10 | 3094.06 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 469.25 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.02 | |||||
Maximum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 122.20 | 533.04 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1089.83 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 461.22 | 15-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1089.83 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 476.25 | 19-FEB-06:10 |
March | 2401.70 | 01-MAR-00:10 | 1089.83 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 399.63 | 01-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1089.83 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 45.06 | 27-APR-15:40 | 357.80 | 19-APR-05:10 |
May | 2401.70 | 01-MAY-00:10 | 1089.83 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 13.32 | 05-MAY-16:00 | 327.26 | 18-MAY-06:15 |
June | 2401.70 | 01-JUN-00:10 | 1089.83 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 38.05 | 28-JUN-17:00 | 267.27 | 15-JUN-05:07 |
July | 2401.70 | 01-JUL-00:10 | 1089.83 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 93.28 | 24-JUL-15:00 | 201.76 | 19-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1089.83 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 109.57 | 10-AUG-17:00 | 207.96 | 01-AUG-06:15 |
September | 2401.70 | 01-SEP-00:10 | 1089.83 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 13.35 | 14-SEP-17:00 | 290.52 | 27-SEP-04:43 |
October | 2401.70 | 01-OCT-23:10 | 1089.83 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 332.00 | 13-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 1089.83 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 385.73 | 11-NOV-07:10 |
December | 2401.70 | 01-DEC-00:10 | 1089.83 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 420.01 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1089.83 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 201.76 | ||||||
Maximum of Months | 2401.70 | 1089.83 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 109.57 | 476.25 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 403.24 | 15-JAN-08:00 |
February | 2395.44 | 01-FEB-00:10 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 422.74 | 19-FEB-06:00 |
March | 2395.44 | 01-MAR-00:10 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 343.79 | 01-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.51 | 01-APR-16:00 | 304.59 | 19-APR-05:00 |
May | 2395.44 | 01-MAY-00:10 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | 05-MAY-16:00 | 265.58 | 11-MAY-03:00 |
June | 2395.44 | 01-JUN-00:10 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.74 | 28-JUN-17:00 | 206.40 | 15-JUN-03:43 |
July | 2395.44 | 01-JUL-00:10 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.16 | 24-JUL-15:00 | 173.30 | 19-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.02 | 10-AUG-17:00 | 177.21 | 01-AUG-05:25 |
September | 2395.44 | 01-SEP-00:10 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.35 | 22-SEP-16:00 | 220.59 | 27-SEP-04:43 |
October | 2395.44 | 01-OCT-23:10 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 243.66 | 13-OCT-05:00 |
November | 2395.44 | 01-NOV-00:10 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 330.68 | 11-NOV-07:50 |
December | 2395.44 | 01-DEC-00:10 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 363.43 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.30 | ||||
Maximum of Months | 2395.44 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.02 | 422.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 34483.24 | 09-JAN-22:01 | 92015.14 | 75656.14 | 59618.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 32768.76 | 08-FEB-20:21 | 71567.33 | 113482.76 | 80910.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26821.85 | 24-MAR-20:45 | 40895.62 | 50437.18 | 38325.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23289.15 | 24-APR-23:34 | 92015.14 | 25218.23 | 25550.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24364.77 | 18-MAY-06:25 | 40895.62 | 63046.30 | 51101.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20551.20 | 15-JUN-05:27 | 26837.75 | 18913.67 | 15969.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17230.41 | 04-JUL-05:27 | 26837.75 | 14185.53 | 12775.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18109.33 | 18-AUG-21:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26862.61 | 28-SEP-05:50 | 89459.16 | 63045.57 | 53230.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35593.24 | 16-OCT-06:23 | 30671.71 | 47284.72 | 38325.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37074.87 | 29-NOV-21:48 | 102239.04 | 126092.96 | 95814.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36814.45 | 01-DEC-20:45 | 89459.16 | 141853.45 | 101138.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17230.41 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37074.87 | 102239.04 | 141853.45 | 101138.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4050.99 | 20-JAN-12:48 | 2598.96 | 1956.71 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.42 |
February | 6214.52 | 12-FEB-12:55 | 1559.38 | 939.22 | 1154.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.13 |
March | 3975.74 | 02-MAR-13:20 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.29 |
April | 3609.41 | 27-APR-13:10 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 | 0.00 |
May | 3475.43 | 04-MAY-13:20 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.41 |
June | 2759.95 | 28-JUN-10:33 | 779.69 | 587.01 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.27 |
July | 3354.37 | 31-JUL-13:20 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 40.93 | 0.00 |
August | 4256.89 | 24-AUG-13:10 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 56.08 | 0.00 |
September | 4397.98 | 14-SEP-13:20 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.74 |
October | 4487.61 | 04-OCT-12:50 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.65 |
November | 5509.88 | 11-NOV-12:35 | 779.69 | 469.61 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.86 |
December | 3568.21 | 05-DEC-11:20 | 779.69 | 587.01 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2759.95 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6214.52 | 2598.96 | 1956.71 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 56.08 | 219.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1750.60 | 03-JAN-06:34 | 10533.60 | 3625.40 | 4178.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.47 |
February | 1929.01 | 08-FEB-20:27 | 8426.88 | 6525.72 | 6351.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.01 |
March | 2153.07 | 15-MAR-06:07 | 4213.44 | 3172.23 | 3510.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.23 |
April | 2175.35 | 24-APR-23:34 | 10834.56 | 1450.16 | 2005.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.82 |
May | 2154.21 | 18-MAY-06:25 | 4815.36 | 3625.40 | 4011.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.71 |
June | 1812.69 | 15-JUN-05:27 | 3160.08 | 1087.62 | 1253.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.82 |
July | 1972.80 | 24-JUL-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 |
August | 2121.77 | 10-AUG-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.46 |
September | 1909.36 | 14-SEP-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 |
October | 2025.00 | 12-OCT-23:32 | 12188.88 | 1631.43 | 2256.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.51 |
November | 1869.58 | 28-NOV-23:25 | 2708.64 | 543.81 | 668.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.95 |
December | 1854.28 | 01-DEC-18:17 | 2257.20 | 1631.43 | 1755.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1750.60 | 1203.84 | 543.81 | 668.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.46 | |
Maximum of Months | 2175.35 | 12188.88 | 6525.72 | 6351.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1494.15 | 01-JAN-20:15 | 1145.66 | 7255.45 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.23 |
February | 1610.48 | 26-FEB-01:32 | 2004.91 | 4081.19 | 3181.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.30 |
March | 1813.17 | 15-MAR-06:07 | 891.07 | 5290.43 | 3711.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.49 |
April | 1829.91 | 24-APR-23:34 | 2291.33 | 2418.48 | 2120.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.04 |
May | 1910.42 | 18-MAY-06:25 | 1018.37 | 6046.21 | 4241.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.38 |
June | 1591.73 | 13-JUN-23:40 | 572.83 | 604.62 | 530.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.00 |
July | 1598.25 | 24-JUL-21:00 | 254.59 | 1209.24 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.74 |
August | 1738.30 | 10-AUG-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 | 0.00 |
September | 1656.42 | 27-SEP-06:30 | 1145.66 | 6801.98 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.52 |
October | 1712.76 | 12-OCT-23:32 | 2577.74 | 2720.79 | 2385.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.98 |
November | 1569.10 | 17-NOV-08:35 | 254.59 | 1209.24 | 883.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.26 |
December | 1550.11 | 04-DEC-16:10 | 1591.20 | 3778.88 | 3092.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1494.15 | 222.77 | 604.62 | 530.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1910.42 | 2577.74 | 7255.45 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 | 184.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 643.73 | 12-JAN-07:10 | 195.84 | 253.02 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.31 |
February | 755.64 | 26-FEB-01:32 | 1542.24 | 683.15 | 917.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.64 |
March | 853.54 | 15-MAR-06:07 | 685.44 | 885.57 | 1070.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.34 |
April | 862.16 | 24-APR-23:34 | 1762.56 | 404.83 | 611.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.40 |
May | 894.07 | 18-MAY-06:25 | 783.36 | 1012.07 | 1223.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.73 |
June | 750.34 | 13-JUN-23:40 | 440.64 | 101.21 | 152.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.99 |
July | 669.20 | 24-JUL-18:10 | 1028.16 | 1214.49 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 31.75 | 0.00 |
August | 681.60 | 10-AUG-18:08 | 1028.16 | 1214.49 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 41.32 | 0.00 |
September | 778.12 | 27-SEP-05:14 | 1713.60 | 1012.07 | 1274.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.49 |
October | 807.70 | 12-OCT-23:32 | 1982.88 | 455.43 | 688.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.16 |
November | 724.33 | 20-NOV-06:13 | 514.08 | 303.62 | 382.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.72 |
December | 718.19 | 03-DEC-09:07 | 734.40 | 455.43 | 611.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 643.73 | 195.84 | 101.21 | 152.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 894.07 | 1982.88 | 1214.49 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 41.32 | 103.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 50428.00 | 23-JAN-21:40 | 8064.00 | 3175.23 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 310.97 |
February | 52379.02 | 07-FEB-20:01 | 5644.80 | 2857.71 | 36582.41 | 317812.61 | 0.00 | 0.00 | 0.00 | 0.00 | 321.50 |
March | 51226.88 | 24-MAR-20:45 | 3225.60 | 1270.09 | 17328.51 | 150542.82 | 0.00 | 0.00 | 0.00 | 0.00 | 320.78 |
April | 49727.30 | 17-APR-19:00 | 7056.00 | 3175.23 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 295.60 |
May | 49684.70 | 10-MAY-22:00 | 9072.00 | 2381.43 | 33694.32 | 292722.14 | 0.00 | 0.00 | 0.00 | 0.00 | 286.25 |
June | 38426.82 | 28-JUN-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 33.52 |
July | 38712.28 | 24-JUL-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 |
August | 38783.54 | 10-AUG-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 22.74 | 0.00 |
September | 43398.20 | 27-SEP-06:59 | 4032.00 | 1984.52 | 28880.85 | 250904.69 | 0.00 | 0.00 | 0.00 | 0.00 | 234.65 |
October | 49333.63 | 31-OCT-20:29 | 7257.60 | 2857.71 | 38989.14 | 338721.34 | 0.00 | 0.00 | 0.00 | 0.00 | 271.77 |
November | 50329.27 | 29-NOV-21:48 | 8064.00 | 3175.23 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 301.34 |
December | 52305.45 | 04-DEC-21:40 | 8064.00 | 3175.23 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 322.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 38426.82 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52379.02 | 9072.00 | 3175.23 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 22.74 | 322.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19794.98 | 20-JAN-12:48 | 34152.00 | 2985.45 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.91 |
February | 25066.42 | 12-FEB-12:39 | 51228.00 | 3582.54 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.13 |
March | 15356.16 | 01-MAR-13:17 | 10245.60 | 895.64 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.27 |
April | 15994.73 | 24-APR-23:34 | 122947.20 | 3132.28 | 2438.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.55 |
May | 14531.93 | 27-MAY-04:27 | 122947.20 | 1566.14 | 1625.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.56 |
June | 12889.20 | 15-JUN-02:29 | 153684.00 | 1957.67 | 2032.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.83 |
July | 12204.95 | 31-JUL-15:03 | 51228.00 | 1791.27 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 111.23 | 0.00 |
August | 14417.16 | 24-AUG-14:10 | 5122.80 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 130.05 | 0.00 |
September | 15450.25 | 23-SEP-13:20 | 5122.80 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.80 |
October | 15597.68 | 04-OCT-12:50 | 3415.20 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.64 |
November | 24423.79 | 11-NOV-12:03 | 51228.00 | 3582.54 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 513.29 |
December | 13989.18 | 05-DEC-11:20 | 10245.60 | 895.64 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12204.95 | 3415.20 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25066.42 | 153684.00 | 3582.54 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 130.05 | 513.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 39305.93 | 09-JAN-22:20 | 91245.96 | 13686.91 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1448.58 |
February | 46873.94 | 28-FEB-23:30 | 91245.96 | 6843.46 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1347.13 |
March | 58831.08 | 21-MAR-21:18 | 228114.90 | 34217.28 | 36949.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1307.50 |
April | 52477.42 | 11-APR-22:00 | 456229.80 | 68434.56 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1347.35 |
May | 60204.86 | 10-MAY-21:54 | 456229.80 | 68434.56 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.46 |
June | 39862.88 | 15-JUN-05:27 | 106453.62 | 13048.19 | 15835.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.62 |
July | 39587.72 | 24-JUL-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.12 |
August | 40992.29 | 10-AUG-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.01 |
September | 41913.69 | 27-SEP-05:14 | 354845.40 | 45623.04 | 52785.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1220.38 |
October | 59903.72 | 13-OCT-00:55 | 182491.92 | 6843.46 | 10557.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1306.15 |
November | 46414.07 | 28-NOV-23:05 | 91245.96 | 6843.46 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1189.74 |
December | 40018.21 | 03-DEC-09:07 | 152076.60 | 19093.24 | 25336.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1147.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 39305.93 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.01 | |
Maximum of Months | 60204.86 | 456229.80 | 68434.56 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1448.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2107.97 | 20-JAN-16:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.46 |
February | 3124.92 | 08-FEB-16:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.43 |
March | 3350.19 | 18-MAR-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.37 |
April | 3483.65 | 01-APR-18:02 | 702.00 | 735.03 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 | 0.00 |
May | 3554.62 | 14-MAY-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 | 0.00 |
June | 3300.56 | 02-JUN-18:01 | 970.20 | 763.21 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.09 |
July | 3310.12 | 25-JUL-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 |
August | 3543.45 | 10-AUG-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 50.47 | 0.00 |
September | 3267.73 | 13-SEP-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
October | 3497.16 | 04-OCT-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.56 |
November | 3181.66 | 04-NOV-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.48 |
December | 2918.11 | 05-DEC-16:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2107.97 | 324.00 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3554.62 | 970.20 | 763.21 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 50.47 | 114.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1010.78 | 24-JAN-16:03 | 972.00 | 342.97 | 684.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.05 |
February | 2966.21 | 27-FEB-16:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 |
March | 2994.18 | 18-MAR-15:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.61 |
April | 3162.17 | 01-APR-18:02 | 702.00 | 734.94 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 18.36 | 0.00 |
May | 3217.53 | 14-MAY-15:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3.88 | 0.00 |
June | 3007.49 | 24-JUN-18:02 | 702.00 | 734.94 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.41 |
July | 3084.31 | 20-JUL-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 27.91 | 0.00 |
August | 3263.26 | 10-AUG-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 50.14 | 0.00 |
September | 3092.85 | 22-SEP-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 0.00 |
October | 3123.07 | 04-OCT-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 |
November | 2874.86 | 04-NOV-15:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 |
December | 959.82 | 03-DEC-19:03 | 1053.00 | 1102.42 | 1161.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 959.82 | 324.00 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3263.26 | 1053.00 | 1102.42 | 1161.45 | 0.00 | 0.00 | 0.00 | 0.00 | 50.14 | 103.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 158.87 | 08-JAN-14:40 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.21 |
February | 536.60 | 08-FEB-14:00 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.32 |
March | 684.17 | 02-MAR-13:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.74 |
April | 663.51 | 27-APR-13:10 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 5.05 | 0.00 |
May | 638.43 | 04-MAY-13:20 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
June | 500.61 | 28-JUN-13:20 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 2.29 | 0.00 |
July | 618.63 | 31-JUL-13:20 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 7.79 | 0.00 |
August | 761.86 | 24-AUG-13:10 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 10.23 | 0.00 |
September | 810.42 | 14-SEP-13:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
October | 834.64 | 04-OCT-12:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.25 |
November | 548.58 | 04-NOV-13:50 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.49 |
December | 484.60 | 05-DEC-12:25 | 0.00 | 43.11 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 158.87 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 834.64 | 0.00 | 43.11 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 10.23 | 36.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 449.13 | 09-JAN-19:04 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.39 |
February | 684.06 | 25-FEB-09:03 | 162.00 | 129.38 | 479.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.57 |
March | 706.16 | 17-MAR-18:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.60 |
April | 844.53 | 01-APR-18:02 | 702.00 | 462.06 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 | 0.00 |
May | 855.37 | 14-MAY-18:02 | 702.00 | 462.06 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 |
June | 872.45 | 09-JUN-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 | 0.00 |
July | 907.93 | 24-JUL-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 10.62 | 0.00 |
August | 897.11 | 10-AUG-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 14.05 | 0.00 |
September | 819.11 | 13-SEP-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 | 0.00 |
October | 749.42 | 04-OCT-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 | 0.00 |
November | 686.71 | 04-NOV-08:63 | 162.00 | 129.38 | 479.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.19 |
December | 483.75 | 05-DEC-19:03 | 1386.00 | 685.40 | 1264.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 449.13 | 162.00 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 907.93 | 1386.00 | 685.40 | 1264.50 | 0.00 | 0.00 | 0.00 | 0.00 | 14.05 | 31.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 926.77 | 10-JAN-09:03 | 252.00 | 377.32 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.86 |
February | 2591.79 | 08-FEB-16:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.25 |
March | 2990.94 | 18-MAR-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.88 |
April | 3098.80 | 01-APR-18:02 | 702.00 | 735.03 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 19.45 | 0.00 |
May | 3149.93 | 14-MAY-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 0.00 |
June | 3006.83 | 02-JUN-18:01 | 970.20 | 763.21 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.84 |
July | 3124.78 | 24-JUL-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 40.33 | 0.00 |
August | 3141.64 | 10-AUG-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 52.14 | 0.00 |
September | 3042.27 | 22-SEP-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 6.85 | 0.00 |
October | 3097.86 | 04-OCT-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.57 |
November | 2866.27 | 04-NOV-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.68 |
December | 967.03 | 30-DEC-09:03 | 378.00 | 480.22 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 926.77 | 252.00 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3149.93 | 970.20 | 763.21 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 52.14 | 123.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 788.26 | 05-JAN-09:04 | 252.00 | 377.27 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.39 |
February | 1090.96 | 27-FEB-09:01 | 360.00 | 538.96 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.80 |
March | 2522.42 | 02-MAR-09:01 | 252.00 | 377.27 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.91 |
April | 2776.38 | 27-APR-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 30.41 | 0.00 |
May | 2871.31 | 14-MAY-15:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 | 0.00 |
June | 2818.92 | 28-JUN-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 18.68 | 0.00 |
July | 2899.38 | 30-JUL-15:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 31.49 | 0.00 |
August | 2892.51 | 23-AUG-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 41.89 | 0.00 |
September | 2777.66 | 12-SEP-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 12.06 | 0.00 |
October | 2736.98 | 04-OCT-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 |
November | 1445.16 | 04-NOV-15:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 |
December | 765.24 | 03-DEC-09:03 | 324.00 | 411.57 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 765.24 | 252.00 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2899.38 | 831.60 | 654.11 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 41.89 | 154.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2352.63 | 12-JAN-07:10 | 2011.87 | 2489.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.33 |
February | 2771.06 | 08-FEB-15:02 | 3017.81 | 2489.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.16 |
March | 3147.70 | 15-MAR-06:07 | 7041.55 | 8714.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.88 |
April | 3251.67 | 24-APR-23:34 | 18106.85 | 3983.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.86 |
May | 3340.92 | 18-MAY-06:25 | 8047.49 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.26 |
June | 2810.79 | 13-JUN-23:40 | 4526.71 | 995.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.04 |
July | 2547.20 | 24-JUL-18:10 | 10562.33 | 11950.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 | 0.00 |
August | 2597.21 | 10-AUG-18:08 | 10562.33 | 11950.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.70 | 0.00 |
September | 2879.38 | 27-SEP-05:14 | 17603.88 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.18 |
October | 3034.38 | 12-OCT-23:32 | 20370.20 | 4481.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.33 |
November | 2678.33 | 28-NOV-23:25 | 4526.71 | 1493.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.47 |
December | 2657.79 | 10-DEC-19:46 | 15089.04 | 17428.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2352.63 | 2011.87 | 995.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3340.92 | 20370.20 | 17428.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.70 | 139.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1787.89 | 20-JAN-16:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.81 |
February | 3247.32 | 08-FEB-16:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.72 |
March | 3485.52 | 18-MAR-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 |
April | 3635.58 | 01-APR-18:02 | 702.00 | 735.03 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 0.00 |
May | 3708.26 | 14-MAY-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 3.36 | 0.00 |
June | 3427.18 | 02-JUN-18:01 | 970.20 | 763.21 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.36 |
July | 3691.26 | 31-JUL-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 23.65 | 0.00 |
August | 3729.93 | 10-AUG-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 49.83 | 0.00 |
September | 3382.75 | 13-SEP-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 |
October | 3642.92 | 04-OCT-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.97 |
November | 3251.04 | 04-NOV-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.18 |
December | 3041.96 | 05-DEC-16:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1787.89 | 324.00 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3729.93 | 970.20 | 763.21 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 49.83 | 114.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 780.03 | 11-JAN-16:05 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 |
February | 3061.62 | 27-FEB-16:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.32 |
March | 3080.57 | 18-MAR-15:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.77 |
April | 3274.98 | 01-APR-18:02 | 702.00 | 734.94 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 17.82 | 0.00 |
May | 3330.22 | 14-MAY-15:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3.37 | 0.00 |
June | 3103.48 | 24-JUN-18:02 | 702.00 | 734.94 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.75 |
July | 3375.83 | 31-JUL-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 23.20 | 0.00 |
August | 3355.12 | 10-AUG-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 49.33 | 0.00 |
September | 3147.93 | 22-SEP-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 0.00 |
October | 3217.72 | 04-OCT-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.95 |
November | 2960.32 | 04-NOV-15:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 |
December | 907.75 | 10-DEC-16:03 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 780.03 | 324.00 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3375.83 | 831.60 | 734.94 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 49.33 | 82.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1985.77 | 05-JAN-16:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.28 |
February | 2040.44 | 10-FEB-16:01 | 972.00 | 215.63 | 670.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.13 |
March | 2156.25 | 18-MAR-15:02 | 324.00 | 152.48 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.99 |
April | 2173.03 | 02-APR-15:02 | 324.00 | 152.48 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.21 |
May | 2224.97 | 14-MAY-15:02 | 324.00 | 152.48 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 2.22 | 0.00 |
June | 2156.88 | 09-JUN-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 | 0.00 |
July | 2175.87 | 24-JUL-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 20.81 | 0.00 |
August | 2209.47 | 24-AUG-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 22.70 | 0.00 |
September | 2193.70 | 14-SEP-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 0.00 |
October | 2238.19 | 04-OCT-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.32 |
November | 1989.68 | 10-NOV-16:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.85 |
December | 1987.83 | 05-DEC-16:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1985.77 | 324.00 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2238.19 | 972.00 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 22.70 | 61.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 31352.01 | 30-JAN-23:31 | 242898.91 | 9282.17 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.67 |
February | 31633.24 | 04-FEB-00:37 | 269887.68 | 6875.68 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.59 |
March | 31550.20 | 03-MAR-05:08 | 269887.68 | 6875.68 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.44 |
April | 31539.07 | 07-APR-23:14 | 269887.68 | 6875.68 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.92 |
May | 31151.59 | 12-MAY-05:38 | 209912.64 | 11001.09 | 56232.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.13 |
June | 29781.33 | 15-JUN-01:37 | 242898.91 | 3094.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.43 |
July | 22509.39 | 24-JUL-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.46 |
August | 22437.89 | 10-AUG-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.73 |
September | 29862.59 | 28-SEP-05:32 | 167930.11 | 11001.09 | 44986.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.70 |
October | 31689.90 | 31-OCT-03:59 | 269887.68 | 3437.84 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.63 |
November | 31282.57 | 20-NOV-03:42 | 161932.61 | 2062.70 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.75 |
December | 30392.50 | 04-DEC-21:34 | 239900.16 | 27502.72 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22437.89 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.73 | |
Maximum of Months | 31689.90 | 269887.68 | 27502.72 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33105.66 | 30-JAN-23:31 | 242898.91 | 9282.17 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.42 |
February | 33312.46 | 04-FEB-02:25 | 107955.07 | 1375.14 | 8997.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.46 |
March | 33196.19 | 03-MAR-05:08 | 269887.68 | 6875.68 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.43 |
April | 34092.76 | 07-APR-23:14 | 269887.68 | 6875.68 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.57 |
May | 33648.57 | 12-MAY-05:45 | 209912.64 | 11001.09 | 56232.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.66 |
June | 31623.19 | 15-JUN-05:10 | 62973.79 | 3575.35 | 16869.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.12 |
July | 23704.66 | 24-JUL-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.61 |
August | 23650.32 | 10-AUG-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 |
September | 31728.24 | 28-SEP-05:20 | 104956.32 | 6875.68 | 28116.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.21 |
October | 33547.20 | 24-OCT-02:20 | 269887.68 | 3437.84 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.40 |
November | 32890.02 | 20-NOV-03:42 | 161932.61 | 2062.70 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.59 |
December | 32360.57 | 30-DEC-18:37 | 179925.12 | 20627.04 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 23650.32 | 26988.77 | 1375.14 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 | |
Maximum of Months | 34092.76 | 269887.68 | 20627.04 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37287.85 | 30-JAN-18:51 | 9339.96 | 5085.88 | 104389.99 | 157449.82 | 0.00 | 0.00 | 0.00 | 0.00 | 307.31 |
February | 36821.63 | 08-FEB-17:21 | 9339.96 | 2119.12 | 104389.99 | 157449.82 | 0.00 | 0.00 | 0.00 | 0.00 | 296.68 |
March | 39543.45 | 29-MAR-11:16 | 5337.12 | 3027.31 | 149128.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 0.00 | 248.02 |
April | 37908.16 | 11-APR-11:23 | 3735.98 | 2119.12 | 104389.99 | 131208.19 | 0.00 | 0.00 | 0.00 | 0.00 | 239.16 |
May | 38156.54 | 12-MAY-05:45 | 18679.92 | 4843.69 | 125511.30 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 265.35 |
June | 31669.09 | 15-JUN-05:50 | 18679.92 | 4843.69 | 125511.30 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 232.02 |
July | 31245.32 | 24-JUL-10:37 | 1601.14 | 908.19 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 26.26 | 0.00 |
August | 31285.32 | 13-AUG-10:40 | 2401.70 | 1089.83 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.15 | 0.00 |
September | 33206.85 | 28-SEP-06:44 | 10674.24 | 6054.62 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 244.74 |
October | 34742.99 | 24-OCT-06:20 | 6404.54 | 3632.77 | 89477.13 | 67478.50 | 0.00 | 0.00 | 0.00 | 0.00 | 292.12 |
November | 37041.01 | 23-NOV-18:36 | 7471.97 | 4238.23 | 104389.99 | 157449.82 | 0.00 | 0.00 | 0.00 | 0.00 | 307.20 |
December | 36356.03 | 13-DEC-18:19 | 13342.80 | 7265.54 | 149128.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 288.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 31245.32 | 1601.14 | 908.19 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39543.45 | 18679.92 | 7265.54 | 149128.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 26.26 | 307.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4728.93 | 05-JAN-15:03 | 7984.80 | 6587.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.96 |
February | 5869.36 | 08-FEB-15:02 | 3193.92 | 2635.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.07 |
March | 6436.29 | 15-MAR-06:07 | 7452.48 | 9222.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.02 |
April | 6582.45 | 24-APR-23:34 | 19163.52 | 4216.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.78 |
May | 6536.01 | 18-MAY-06:25 | 8517.12 | 10540.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.01 |
June | 5561.11 | 13-JUN-23:40 | 4790.88 | 1054.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.11 |
July | 5838.08 | 24-JUL-15:03 | 7984.80 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.26 | 0.00 |
August | 6834.73 | 10-AUG-14:20 | 798.48 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.05 | 0.00 |
September | 5595.24 | 27-SEP-05:14 | 18631.20 | 10540.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.89 |
October | 6030.03 | 12-OCT-23:32 | 21558.96 | 4743.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.45 |
November | 5456.03 | 28-NOV-23:25 | 4790.88 | 1581.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.81 |
December | 5086.88 | 05-DEC-11:20 | 1596.96 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4728.93 | 798.48 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6834.73 | 21558.96 | 10540.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.26 | 237.01 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.382706E+12 | 242728.45 | 02-JAN-20:00 | 0.564618E+12 | 531360.57 | 22-JAN-18:49 |
February | 0.345646E+12 | 257645.88 | 08-FEB-20:19 | 0.482936E+12 | 515983.14 | 09-FEB-21:10 |
March | 0.384814E+12 | 249027.48 | 14-MAR-19:10 | 0.502461E+12 | 472878.38 | 04-MAR-20:30 |
April | 0.385287E+12 | 315838.28 | 27-APR-19:10 | 0.461481E+12 | 427822.76 | 03-APR-17:40 |
May | 0.411449E+12 | 306811.02 | 04-MAY-19:19 | 0.457469E+12 | 401507.38 | 23-MAY-17:10 |
June | 0.417652E+12 | 322838.52 | 28-JUN-19:10 | 0.412990E+12 | 364591.16 | 06-JUN-17:00 |
July | 0.464559E+12 | 350275.09 | 24-JUL-19:49 | 0.411734E+12 | 349882.59 | 03-JUL-17:19 |
August | 0.487084E+12 | 370048.64 | 10-AUG-19:30 | 0.410322E+12 | 349546.23 | 31-AUG-17:10 |
September | 0.415844E+12 | 306372.06 | 13-SEP-19:10 | 0.410682E+12 | 351829.87 | 26-SEP-17:00 |
October | 0.393180E+12 | 275854.22 | 04-OCT-19:00 | 0.473026E+12 | 458732.72 | 29-OCT-21:49 |
November | 0.370868E+12 | 248207.81 | 21-NOV-20:40 | 0.501041E+12 | 487303.59 | 29-NOV-19:00 |
December | 0.384992E+12 | 250059.21 | 12-DEC-20:10 | 0.554273E+12 | 503183.79 | 27-DEC-18:49 |
Annual Sum or Average | 0.484408E+13 | 0.564303E+13 | ||||
Minimum of Months | 0.345646E+12 | 242728.45 | 0.410322E+12 | 349546.23 | ||
Maximum of Months | 0.487084E+12 | 370048.64 | 0.564618E+12 | 531360.57 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.655864E+11 | 0.263426E+11 | 0.148212E+12 | 0.553311E+11 | 0.438311E+11 | 0.409869E+10 | 0.00 | 0.123787E+10 | 0.00 | 0.00 | 0.251287E+11 | 0.770465E+10 | 0.00 |
February | 0.590687E+11 | 0.217174E+11 | 0.133859E+12 | 0.499765E+11 | 0.391046E+11 | 0.509453E+10 | 0.00 | 0.389249E+10 | 0.00 | 0.00 | 0.212434E+11 | 0.696225E+10 | 0.00 |
March | 0.652318E+11 | 0.211983E+11 | 0.148223E+12 | 0.553338E+11 | 0.439875E+11 | 0.776932E+10 | 0.00 | 0.807595E+10 | 0.00 | 0.00 | 0.220406E+11 | 0.770293E+10 | 0.00 |
April | 0.627845E+11 | 0.176575E+11 | 0.143397E+12 | 0.535454E+11 | 0.437748E+11 | 0.104089E+11 | 0.00 | 0.235895E+11 | 0.00 | 0.00 | 0.175788E+11 | 0.746508E+10 | 0.00 |
May | 0.647649E+11 | 0.156832E+11 | 0.148223E+12 | 0.553318E+11 | 0.469917E+11 | 0.133957E+11 | 0.00 | 0.409289E+11 | 0.00 | 0.00 | 0.131434E+11 | 0.770458E+10 | 0.00 |
June | 0.624865E+11 | 0.138016E+11 | 0.143446E+12 | 0.535479E+11 | 0.464254E+11 | 0.148506E+11 | 0.00 | 0.621002E+11 | 0.00 | 0.00 | 0.841274E+10 | 0.745696E+10 | 0.00 |
July | 0.645411E+11 | 0.148953E+11 | 0.148174E+12 | 0.553288E+11 | 0.498713E+11 | 0.167524E+11 | 0.00 | 0.951961E+11 | 0.00 | 0.00 | 0.680073E+10 | 0.771264E+10 | 0.00 |
August | 0.648290E+11 | 0.171014E+11 | 0.148234E+12 | 0.553334E+11 | 0.503864E+11 | 0.171879E+11 | 0.00 | 0.113050E+12 | 0.00 | 0.00 | 0.792341E+10 | 0.770440E+10 | 0.00 |
September | 0.630045E+11 | 0.192703E+11 | 0.143408E+12 | 0.535457E+11 | 0.464131E+11 | 0.138643E+11 | 0.00 | 0.542762E+11 | 0.00 | 0.00 | 0.944745E+10 | 0.746644E+10 | 0.00 |
October | 0.653565E+11 | 0.228667E+11 | 0.148201E+12 | 0.553308E+11 | 0.456018E+11 | 0.933078E+10 | 0.00 | 0.170713E+11 | 0.00 | 0.00 | 0.164398E+11 | 0.770306E+10 | 0.00 |
November | 0.634616E+11 | 0.247205E+11 | 0.143462E+12 | 0.535470E+11 | 0.426848E+11 | 0.521918E+10 | 0.00 | 0.423611E+10 | 0.00 | 0.00 | 0.209976E+11 | 0.744903E+10 | 0.00 |
December | 0.655415E+11 | 0.270193E+11 | 0.148174E+12 | 0.553298E+11 | 0.442974E+11 | 0.483631E+10 | 0.00 | 0.197046E+10 | 0.00 | 0.00 | 0.248662E+11 | 0.771264E+10 | 0.00 |
Annual Sum or Average | 0.766657E+12 | 0.242274E+12 | 0.174501E+13 | 0.651482E+12 | 0.543370E+12 | 0.122809E+12 | 0.00 | 0.425625E+12 | 0.00 | 0.00 | 0.194023E+12 | 0.907447E+11 | 0.00 |
Minimum of Months | 0.590687E+11 | 0.138016E+11 | 0.133859E+12 | 0.499765E+11 | 0.391046E+11 | 0.409869E+10 | 0.00 | 0.123787E+10 | 0.00 | 0.00 | 0.680073E+10 | 0.696225E+10 | 0.00 |
Maximum of Months | 0.655864E+11 | 0.270193E+11 | 0.148234E+12 | 0.553338E+11 | 0.503864E+11 | 0.171879E+11 | 0.00 | 0.113050E+12 | 0.00 | 0.00 | 0.251287E+11 | 0.771264E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.132621E+12 | 0.00 | 0.280079E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.915097E+11 | 0.00 | 0.254223E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.710507E+11 | 0.00 | 0.279386E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.491919E+11 | 0.00 | 0.265333E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.381083E+11 | 0.00 | 0.267382E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.135053E+11 | 0.00 | 0.252371E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.387149E+10 | 0.00 | 0.256043E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.361550E+10 | 0.00 | 0.254668E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.151773E+11 | 0.00 | 0.248534E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.590992E+11 | 0.00 | 0.262024E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.937745E+11 | 0.00 | 0.260176E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.127031E+12 | 0.00 | 0.275421E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.698555E+12 | 0.00 | 0.315564E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.361550E+10 | 0.00 | 0.248534E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.132621E+12 | 0.00 | 0.280079E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 62892.57 | 02-JAN-20:10 | 15448.40 | 01-JAN-00:10 | 89475.41 | 02-JAN-07:10 | 39726.11 | 02-JAN-07:19 | 41298.23 | 31-JAN-22:49 | 4803.74 | 25-JAN-21:00 | 0.00 | 01-JAN-00:10 |
February | 62892.57 | 01-FEB-20:10 | 15448.40 | 01-FEB-00:10 | 89475.41 | 01-FEB-07:10 | 39726.11 | 01-FEB-07:19 | 36545.43 | 07-FEB-20:40 | 6470.48 | 27-FEB-15:09 | 0.00 | 01-FEB-00:10 |
March | 62892.57 | 01-MAR-20:10 | 15448.40 | 01-MAR-00:10 | 89475.41 | 01-MAR-07:10 | 39726.11 | 13-MAR-06:19 | 31054.70 | 17-MAR-21:10 | 7047.85 | 18-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 62892.57 | 03-APR-19:10 | 15448.40 | 01-APR-00:10 | 89475.41 | 03-APR-06:10 | 39725.67 | 04-APR-06:19 | 35006.83 | 05-APR-02:30 | 8106.29 | 26-APR-15:09 | 0.00 | 01-APR-00:10 |
May | 62892.57 | 01-MAY-19:10 | 15448.40 | 01-MAY-00:10 | 89475.41 | 01-MAY-06:10 | 39725.51 | 01-MAY-06:19 | 30020.36 | 04-MAY-21:10 | 8195.07 | 04-MAY-18:10 | 0.00 | 01-MAY-00:10 |
June | 62892.57 | 01-JUN-19:40 | 15448.40 | 01-JUN-00:10 | 89475.41 | 01-JUN-06:10 | 39724.49 | 14-JUN-06:19 | 30700.89 | 28-JUN-21:10 | 8215.59 | 27-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 62892.57 | 10-JUL-19:30 | 15448.40 | 01-JUL-00:10 | 89475.41 | 03-JUL-06:10 | 39724.49 | 10-JUL-06:19 | 32006.43 | 31-JUL-21:10 | 8187.26 | 19-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 62892.57 | 01-AUG-19:19 | 15448.40 | 01-AUG-00:10 | 89475.41 | 01-AUG-06:10 | 39725.08 | 16-AUG-06:19 | 34279.93 | 10-AUG-21:10 | 8225.48 | 10-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 62892.57 | 01-SEP-19:10 | 15448.40 | 01-SEP-00:10 | 89475.41 | 01-SEP-06:10 | 39726.11 | 06-SEP-06:19 | 33768.95 | 14-SEP-21:10 | 8185.35 | 08-SEP-16:30 | 0.00 | 01-SEP-00:10 |
October | 62892.57 | 02-OCT-19:10 | 15448.40 | 01-OCT-00:10 | 89475.41 | 02-OCT-06:10 | 39726.11 | 02-OCT-06:19 | 33225.42 | 12-OCT-21:10 | 7701.32 | 04-OCT-15:09 | 0.00 | 01-OCT-00:10 |
November | 62892.57 | 01-NOV-19:10 | 15448.40 | 01-NOV-00:10 | 89475.41 | 01-NOV-06:10 | 39726.11 | 01-NOV-06:19 | 33769.78 | 29-NOV-22:00 | 7465.98 | 04-NOV-15:09 | 0.00 | 01-NOV-00:10 |
December | 62892.57 | 01-DEC-20:10 | 15448.40 | 01-DEC-00:10 | 89475.41 | 01-DEC-07:10 | 39726.11 | 01-DEC-07:19 | 33366.00 | 14-DEC-22:00 | 5778.63 | 05-DEC-12:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 62892.57 | 15448.40 | 89475.41 | 39724.49 | 30020.36 | 4803.74 | 0.00 | |||||||
Maximum of Months | 62892.57 | 15448.40 | 89475.41 | 39726.11 | 41298.23 | 8225.48 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 4523.89 | 08-JAN-14:30 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4738.51 | 02-JAN-07:30 | 0.00 |
February | 48063.84 | 27-FEB-14:00 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 4738.28 | 10-FEB-07:10 | 0.00 |
March | 55779.43 | 18-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:20 | 4738.30 | 27-MAR-18:40 | 0.00 |
April | 99451.79 | 27-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4738.37 | 11-APR-06:19 | 0.00 |
May | 88139.13 | 04-MAY-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:10 | 4738.61 | 31-MAY-18:10 | 0.00 |
June | 101021.37 | 28-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-00:10 | 4738.35 | 26-JUN-06:10 | 0.00 |
July | 124230.06 | 24-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUL-03:39 | 4738.31 | 21-JUL-18:30 | 0.00 |
August | 142582.39 | 10-AUG-18:10 | 0.00 | 0.00 | 9938.94 | 01-AUG-02:49 | 4738.53 | 21-AUG-06:10 | 0.00 |
September | 98914.43 | 14-SEP-15:30 | 0.00 | 0.00 | 9938.94 | 02-SEP-01:30 | 4738.54 | 20-SEP-06:40 | 0.00 |
October | 74864.05 | 04-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:10 | 4738.52 | 11-OCT-18:10 | 0.00 |
November | 62746.68 | 04-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4738.59 | 02-NOV-06:49 | 0.00 |
December | 13588.40 | 05-DEC-12:30 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 4738.30 | 15-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4523.89 | 0.00 | 0.00 | 9938.94 | 4738.28 | 0.00 | |||
Maximum of Months | 142582.39 | 0.00 | 0.00 | 9938.94 | 4738.61 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 242728.45 | 02-JAN-20:00 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 22213.30 | 4192.49 | 0.00 | 1217.33 | 0.00 |
February | 257645.88 | 08-FEB-20:19 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 35730.63 | 4512.19 | 0.00 | 2115.40 | 0.00 |
March | 249027.48 | 14-MAR-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 22194.79 | 5884.19 | 0.00 | 16236.72 | 0.00 |
April | 315838.28 | 27-APR-19:10 | 62892.57 | 88772.42 | 15448.40 | 32149.92 | 25522.88 | 7994.02 | 0.00 | 75504.12 | 0.00 |
May | 306811.02 | 04-MAY-19:19 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 25375.13 | 8087.74 | 0.00 | 67794.08 | 0.00 |
June | 322838.52 | 28-JUN-19:10 | 60488.76 | 88772.42 | 0.00 | 32148.47 | 26748.73 | 8006.73 | 0.00 | 90355.92 | 0.00 |
July | 350275.09 | 24-JUL-19:49 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 28106.07 | 8076.30 | 0.00 | 98482.52 | 0.00 |
August | 370048.64 | 10-AUG-19:30 | 62892.57 | 88772.42 | 15448.40 | 32159.27 | 29138.05 | 8118.19 | 0.00 | 117286.87 | 0.00 |
September | 306372.06 | 13-SEP-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 26363.69 | 7817.25 | 0.00 | 66443.13 | 0.00 |
October | 275854.22 | 04-OCT-19:00 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 25289.05 | 6627.70 | 0.00 | 38715.61 | 0.00 |
November | 248207.81 | 21-NOV-20:40 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 27140.78 | 4392.31 | 0.00 | 1725.64 | 0.00 |
December | 250059.21 | 12-DEC-20:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 29855.31 | 4278.81 | 0.00 | 1292.95 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 242728.45 | 60488.76 | 88772.42 | 0.00 | 32148.47 | 22194.79 | 4192.49 | 0.00 | 1217.33 | 0.00 | |
Maximum of Months | 370048.64 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 35730.63 | 8118.19 | 0.00 | 117286.87 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 186463.87 | 22-JAN-18:49 | 0.00 | 282769.04 | 18-JAN-21:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 183030.78 | 12-FEB-11:30 | 0.00 | 278166.04 | 10-FEB-21:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 178116.24 | 23-MAR-08:39 | 0.00 | 283177.66 | 30-MAR-17:30 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 182289.03 | 09-APR-06:49 | 0.00 | 286457.09 | 20-APR-20:40 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 171470.59 | 23-MAY-04:40 | 0.00 | 261949.09 | 10-MAY-20:49 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 99830.61 | 15-JUN-02:00 | 0.00 | 249428.17 | 06-JUN-20:00 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 51276.26 | 03-JUL-03:00 | 0.00 | 246321.32 | 03-JUL-20:40 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 54598.88 | 21-AUG-04:00 | 0.00 | 245882.77 | 31-AUG-20:19 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 130869.37 | 27-SEP-04:40 | 0.00 | 246508.93 | 29-SEP-20:30 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 182055.50 | 29-OCT-00:20 | 0.00 | 257418.31 | 31-OCT-20:49 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 186550.53 | 23-NOV-11:50 | 0.00 | 265476.66 | 30-NOV-21:19 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 176240.50 | 15-DEC-09:00 | 0.00 | 273215.29 | 28-DEC-21:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 51276.26 | 0.00 | 245882.77 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 186550.53 | 0.00 | 286457.09 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 25.23 | 37.50 | 25.23 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 25.29 | 19.67 | 25.29 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 35.50 | 25.14 | 35.50 | 25.14 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 25.11 | 24.17 | 25.11 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 25.10 | 14.00 | 25.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.11 | 0.33 | 25.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.03 | 1.33 | 25.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 25.09 | 20.33 | 25.09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 25.15 | 45.83 | 25.15 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 57.50 | 25.25 | 57.50 | 25.25 |
Annual Sum or Average | 0.00 | 0.00 | 256.17 | 25.18 | 256.17 | 25.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 57.50 | 25.29 | 57.50 | 25.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.62 | 0.17 | 24.62 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.65 | 0.17 | 24.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.64 | 0.33 | 24.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.65 | 0.17 | 24.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.77 | 0.17 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.83 | 1.00 | 21.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.74 | 0.33 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.73 | 1.17 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.78 | 1.83 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.87 | 1.17 | 21.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.83 | 21.79 | 5.83 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.87 | 1.83 | 21.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.91 | 0.33 | 21.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.76 | 1.00 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.79 | 1.83 | 21.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.72 | 1.17 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.33 | 21.77 | 4.33 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.91 | 1.83 | 21.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.74 | 0.50 | 21.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.77 | 0.67 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.69 | 0.83 | 21.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.74 | 1.33 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.71 | 1.17 | 21.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.67 | 0.33 | 21.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.83 | 21.72 | 4.83 | 21.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.77 | 1.33 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.77 | 0.50 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.85 | 0.67 | 21.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.78 | 1.17 | 21.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.84 | 1.67 | 21.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.78 | 1.17 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.17 | 21.80 | 5.17 | 21.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.85 | 1.67 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.82 | 0.33 | 21.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.87 | 2.33 | 21.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.74 | 1.00 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.76 | 2.33 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.80 | 3.00 | 21.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.83 | 2.17 | 21.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.17 | 21.81 | 11.17 | 21.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.87 | 3.00 | 21.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.83 | 1.83 | 21.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.79 | 1.67 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.81 | 3.00 | 21.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.80 | 1.83 | 21.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.50 | 21.81 | 8.50 | 21.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.83 | 3.00 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.70 | 0.67 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.75 | 1.17 | 21.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.78 | 0.17 | 21.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.50 | 21.73 | 2.50 | 21.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.78 | 1.17 | 21.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.72 | 3.67 | 24.72 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.71 | 2.83 | 24.71 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 24.76 | 6.33 | 24.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.73 | 3.67 | 24.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 24.73 | 6.00 | 24.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.62 | 0.33 | 24.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.70 | 0.17 | 24.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 24.69 | 6.33 | 24.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.73 | 3.00 | 24.73 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.78 | 4.33 | 24.78 |
Annual Sum or Average | 0.00 | 0.00 | 36.67 | 24.73 | 36.67 | 24.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 24.78 | 6.33 | 24.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.78 | 5.17 | 24.78 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.74 | 4.17 | 24.74 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 24.81 | 8.00 | 24.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.75 | 4.67 | 24.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 24.75 | 7.50 | 24.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.64 | 0.50 | 24.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.74 | 0.17 | 24.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 24.72 | 8.67 | 24.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 24.71 | 5.67 | 24.71 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 24.77 | 7.17 | 24.77 |
Annual Sum or Average | 0.00 | 0.00 | 51.67 | 24.75 | 51.67 | 24.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 24.81 | 8.67 | 24.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 50.67 | 25.17 | 50.67 | 25.17 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 | 25.14 | 33.00 | 25.14 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 61.17 | 25.09 | 61.17 | 25.09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 25.06 | 37.17 | 25.06 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 25.09 | 25.83 | 25.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.77 | 3.83 | 24.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.85 | 3.17 | 24.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 41.50 | 24.95 | 41.50 | 24.95 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 57.50 | 25.05 | 57.50 | 25.05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 70.50 | 25.11 | 70.50 | 25.11 |
Annual Sum or Average | 0.00 | 0.00 | 384.33 | 25.08 | 384.33 | 25.08 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 70.50 | 25.17 | 70.50 | 25.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 726.33 | 23.49 | 0.00 | 23.49 | 0.00 | 23.49 |
February | 663.17 | 23.33 | 0.00 | 23.33 | 0.00 | 23.33 |
March | 739.67 | 23.19 | 0.00 | 23.19 | 0.00 | 23.19 |
April | 718.83 | 23.06 | 0.00 | 23.06 | 0.00 | 23.06 |
May | 741.33 | 23.11 | 0.00 | 23.11 | 0.00 | 23.11 |
June | 679.67 | 23.18 | 0.00 | 23.18 | 0.00 | 23.18 |
July | 566.00 | 23.31 | 14.50 | 23.32 | 0.00 | 23.32 |
August | 337.83 | 23.29 | 36.67 | 23.36 | 0.00 | 23.36 |
September | 236.50 | 23.43 | 69.67 | 23.55 | 0.00 | 23.55 |
October | 327.17 | 23.60 | 3.00 | 23.61 | 0.00 | 23.61 |
November | 352.17 | 23.69 | 23.83 | 23.71 | 0.00 | 23.71 |
December | 640.50 | 23.65 | 0.00 | 23.65 | 0.00 | 23.65 |
Annual Sum or Average | 6729.17 | 23.33 | 147.67 | 23.34 | 0.00 | 23.34 |
Minimum of Months | 236.50 | 23.06 | 0.00 | 23.06 | 0.00 | 23.06 |
Maximum of Months | 741.33 | 23.69 | 69.67 | 23.71 | 0.00 | 23.71 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 738.83 | 21.04 | 167.17 | 21.04 | 165.83 | 21.03 |
February | 646.17 | 21.10 | 106.33 | 21.13 | 95.67 | 21.12 |
March | 705.00 | 21.17 | 26.00 | 21.24 | 6.83 | 21.24 |
April | 666.83 | 21.26 | 30.67 | 21.37 | 0.00 | 21.37 |
May | 677.00 | 21.32 | 37.33 | 21.44 | 0.00 | 21.44 |
June | 666.50 | 21.39 | 21.00 | 21.45 | 0.00 | 21.45 |
July | 606.00 | 21.55 | 88.67 | 21.81 | 0.00 | 21.81 |
August | 555.67 | 21.53 | 132.83 | 21.94 | 0.00 | 21.94 |
September | 577.17 | 21.34 | 100.83 | 21.71 | 0.00 | 21.71 |
October | 673.67 | 21.20 | 48.67 | 21.38 | 0.00 | 21.38 |
November | 705.33 | 21.06 | 28.50 | 21.10 | 17.83 | 21.10 |
December | 728.50 | 21.07 | 132.17 | 21.07 | 128.33 | 21.06 |
Annual Sum or Average | 7946.67 | 21.24 | 920.17 | 21.37 | 414.50 | 21.36 |
Minimum of Months | 555.67 | 21.04 | 21.00 | 21.04 | 0.00 | 21.03 |
Maximum of Months | 738.83 | 21.55 | 167.17 | 21.94 | 165.83 | 21.94 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
February | 671.67 | 21.96 | 0.00 | 21.96 | 0.00 | 21.96 |
March | 743.50 | 22.37 | 0.00 | 22.37 | 0.00 | 22.37 |
April | 682.33 | 22.60 | 3.50 | 22.61 | 0.00 | 22.61 |
May | 659.00 | 22.80 | 13.17 | 22.83 | 0.00 | 22.83 |
June | 576.50 | 22.84 | 25.83 | 22.89 | 0.00 | 22.89 |
July | 417.83 | 22.98 | 120.67 | 23.20 | 0.00 | 23.20 |
August | 329.17 | 22.89 | 195.00 | 23.27 | 0.00 | 23.27 |
September | 474.67 | 22.82 | 86.17 | 22.99 | 0.00 | 22.99 |
October | 710.33 | 22.60 | 0.00 | 22.60 | 0.00 | 22.60 |
November | 717.33 | 22.04 | 0.00 | 22.04 | 0.00 | 22.04 |
December | 744.00 | 21.81 | 0.00 | 21.81 | 0.00 | 21.81 |
Annual Sum or Average | 7470.33 | 22.38 | 444.33 | 22.47 | 0.00 | 22.47 |
Minimum of Months | 329.17 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
Maximum of Months | 744.00 | 22.98 | 195.00 | 23.27 | 0.00 | 23.27 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.11 | 9.33 | 21.10 | 9.33 | 21.10 |
February | 672.00 | 21.24 | 5.00 | 21.23 | 5.00 | 21.23 |
March | 744.00 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
April | 720.00 | 21.96 | 0.00 | 21.96 | 0.00 | 21.96 |
May | 742.50 | 22.44 | 0.00 | 22.44 | 0.00 | 22.44 |
June | 710.33 | 22.73 | 0.00 | 22.73 | 0.00 | 22.73 |
July | 667.17 | 23.03 | 11.33 | 23.05 | 0.00 | 23.05 |
August | 596.17 | 23.07 | 20.67 | 23.10 | 0.00 | 23.10 |
September | 700.00 | 22.71 | 0.00 | 22.71 | 0.00 | 22.71 |
October | 744.00 | 22.05 | 0.00 | 22.05 | 0.00 | 22.05 |
November | 720.00 | 21.40 | 0.00 | 21.40 | 0.00 | 21.40 |
December | 744.00 | 21.14 | 0.00 | 21.14 | 0.00 | 21.14 |
Annual Sum or Average | 8504.17 | 22.01 | 46.33 | 22.02 | 14.33 | 22.02 |
Minimum of Months | 596.17 | 21.11 | 0.00 | 21.10 | 0.00 | 21.10 |
Maximum of Months | 744.00 | 23.07 | 20.67 | 23.10 | 9.33 | 23.10 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.02 | 17.67 | 21.02 | 17.67 | 21.02 |
February | 672.00 | 21.09 | 16.50 | 21.09 | 16.50 | 21.09 |
March | 744.00 | 21.30 | 0.00 | 21.30 | 0.00 | 21.30 |
April | 720.00 | 21.70 | 0.00 | 21.70 | 0.00 | 21.70 |
May | 744.00 | 22.20 | 0.00 | 22.20 | 0.00 | 22.20 |
June | 720.00 | 22.51 | 0.00 | 22.51 | 0.00 | 22.51 |
July | 733.17 | 22.87 | 0.00 | 22.87 | 0.00 | 22.87 |
August | 713.67 | 22.96 | 0.00 | 22.96 | 0.00 | 22.96 |
September | 720.00 | 22.50 | 0.00 | 22.50 | 0.00 | 22.50 |
October | 744.00 | 21.78 | 0.00 | 21.78 | 0.00 | 21.78 |
November | 720.00 | 21.20 | 0.00 | 21.20 | 0.00 | 21.20 |
December | 744.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
Annual Sum or Average | 8718.83 | 21.85 | 34.17 | 21.84 | 34.17 | 21.84 |
Minimum of Months | 672.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
Maximum of Months | 744.00 | 22.96 | 17.67 | 22.96 | 17.67 | 22.96 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 260.50 | 23.15 | 545.00 | 23.43 | 162.50 | 23.58 |
February | 233.67 | 23.23 | 499.00 | 23.43 | 159.33 | 23.57 |
March | 275.33 | 23.41 | 600.17 | 23.48 | 201.33 | 23.62 |
April | 267.83 | 23.61 | 617.00 | 23.47 | 219.17 | 23.61 |
May | 292.83 | 23.75 | 659.50 | 23.47 | 260.67 | 23.60 |
June | 285.83 | 23.81 | 641.67 | 23.45 | 267.67 | 23.57 |
July | 297.67 | 23.91 | 685.17 | 23.46 | 289.00 | 23.58 |
August | 305.83 | 23.95 | 702.33 | 23.44 | 302.50 | 23.57 |
September | 288.00 | 23.89 | 660.50 | 23.46 | 277.33 | 23.58 |
October | 291.00 | 23.63 | 649.33 | 23.47 | 244.00 | 23.61 |
November | 265.33 | 23.50 | 590.83 | 23.49 | 198.33 | 23.64 |
December | 250.50 | 23.34 | 575.00 | 23.48 | 164.83 | 23.65 |
Annual Sum or Average | 3314.33 | 23.62 | 7425.50 | 23.46 | 2746.67 | 23.60 |
Minimum of Months | 233.67 | 23.15 | 499.00 | 23.43 | 159.33 | 23.57 |
Maximum of Months | 305.83 | 23.95 | 702.33 | 23.49 | 302.50 | 23.65 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 732.67 | 21.39 | 10.00 | 21.41 | 4.50 | 21.41 |
February | 625.00 | 21.62 | 25.83 | 21.71 | 0.17 | 21.71 |
March | 667.83 | 21.90 | 38.17 | 22.01 | 0.00 | 22.01 |
April | 595.67 | 22.10 | 63.67 | 22.25 | 0.00 | 22.25 |
May | 568.17 | 22.22 | 88.83 | 22.40 | 0.00 | 22.40 |
June | 494.50 | 22.26 | 94.17 | 22.45 | 0.00 | 22.45 |
July | 326.00 | 22.33 | 264.50 | 22.85 | 0.83 | 22.85 |
August | 312.17 | 22.32 | 332.83 | 23.00 | 21.83 | 23.02 |
September | 394.83 | 22.11 | 230.67 | 22.69 | 0.00 | 22.69 |
October | 599.00 | 22.03 | 82.67 | 22.25 | 0.00 | 22.25 |
November | 690.83 | 21.59 | 16.83 | 21.64 | 1.17 | 21.64 |
December | 718.83 | 21.47 | 21.33 | 21.52 | 6.50 | 21.51 |
Annual Sum or Average | 6725.50 | 21.88 | 1269.50 | 22.15 | 35.00 | 22.15 |
Minimum of Months | 312.17 | 21.39 | 10.00 | 21.41 | 0.00 | 21.41 |
Maximum of Months | 732.67 | 22.33 | 332.83 | 23.00 | 21.83 | 23.02 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.33 | 22.16 | 0.00 | 22.16 | 0.00 | 22.16 |
February | 651.50 | 22.42 | 1.83 | 22.43 | 0.00 | 22.43 |
March | 683.50 | 22.75 | 0.83 | 22.75 | 0.00 | 22.75 |
April | 553.17 | 22.87 | 36.17 | 22.93 | 0.00 | 22.93 |
May | 423.00 | 22.87 | 90.33 | 23.06 | 0.00 | 23.06 |
June | 327.83 | 22.83 | 170.17 | 23.21 | 0.00 | 23.21 |
July | 176.83 | 22.92 | 330.83 | 23.54 | 2.67 | 23.54 |
August | 149.67 | 22.99 | 472.50 | 23.65 | 24.83 | 23.66 |
September | 233.17 | 22.77 | 313.00 | 23.40 | 8.50 | 23.41 |
October | 517.67 | 22.80 | 37.67 | 22.88 | 0.00 | 22.88 |
November | 675.83 | 22.43 | 15.83 | 22.46 | 1.83 | 22.47 |
December | 743.67 | 22.28 | 0.00 | 22.28 | 0.00 | 22.28 |
Annual Sum or Average | 5879.17 | 22.58 | 1469.17 | 22.84 | 37.83 | 22.85 |
Minimum of Months | 149.67 | 22.16 | 0.00 | 22.16 | 0.00 | 22.16 |
Maximum of Months | 743.67 | 22.99 | 472.50 | 23.65 | 24.83 | 23.66 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.68 | 616.50 | 20.63 | 616.50 | 20.62 |
February | 670.67 | 20.94 | 319.33 | 20.83 | 319.33 | 20.78 |
March | 742.17 | 21.16 | 108.00 | 21.07 | 108.00 | 21.00 |
April | 704.33 | 21.38 | 7.83 | 21.37 | 5.50 | 21.37 |
May | 703.33 | 21.46 | 6.50 | 21.48 | 0.00 | 21.48 |
June | 679.83 | 21.51 | 5.17 | 21.53 | 0.00 | 21.53 |
July | 650.67 | 21.44 | 25.17 | 21.51 | 0.00 | 21.51 |
August | 651.83 | 21.43 | 32.17 | 21.52 | 0.00 | 21.52 |
September | 655.00 | 21.37 | 20.00 | 21.43 | 0.00 | 21.43 |
October | 732.83 | 21.25 | 16.00 | 21.23 | 16.00 | 21.20 |
November | 717.83 | 20.87 | 299.67 | 20.77 | 299.67 | 20.71 |
December | 744.00 | 20.76 | 527.50 | 20.67 | 527.50 | 20.64 |
Annual Sum or Average | 8396.50 | 21.18 | 1983.83 | 21.08 | 1892.50 | 21.00 |
Minimum of Months | 650.67 | 20.68 | 5.17 | 20.63 | 0.00 | 20.62 |
Maximum of Months | 744.00 | 21.51 | 616.50 | 21.53 | 616.50 | 21.53 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.55 | 677.00 | 20.52 | 677.00 | 20.52 |
February | 672.00 | 20.73 | 436.50 | 20.65 | 436.50 | 20.62 |
March | 744.00 | 20.95 | 200.50 | 20.85 | 200.50 | 20.79 |
April | 713.67 | 21.24 | 17.67 | 21.22 | 17.67 | 21.21 |
May | 722.50 | 21.43 | 1.00 | 21.44 | 0.17 | 21.43 |
June | 696.17 | 21.50 | 2.50 | 21.51 | 0.00 | 21.51 |
July | 684.50 | 21.49 | 13.00 | 21.53 | 0.00 | 21.53 |
August | 692.50 | 21.49 | 12.33 | 21.52 | 0.00 | 21.52 |
September | 695.67 | 21.38 | 1.00 | 21.39 | 0.00 | 21.39 |
October | 744.00 | 21.08 | 37.67 | 21.03 | 37.67 | 20.98 |
November | 720.00 | 20.73 | 381.83 | 20.64 | 381.83 | 20.59 |
December | 744.00 | 20.60 | 658.83 | 20.57 | 658.83 | 20.56 |
Annual Sum or Average | 8573.00 | 21.09 | 2439.83 | 20.97 | 2410.17 | 20.88 |
Minimum of Months | 672.00 | 20.55 | 1.00 | 20.52 | 0.00 | 20.52 |
Maximum of Months | 744.00 | 21.50 | 677.00 | 21.53 | 677.00 | 21.53 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.85 | 313.50 | 20.76 | 313.50 | 20.71 |
February | 672.00 | 20.94 | 241.17 | 20.87 | 241.17 | 20.83 |
March | 744.00 | 21.07 | 56.50 | 21.06 | 56.50 | 21.05 |
April | 720.00 | 21.22 | 0.00 | 21.22 | 0.00 | 21.22 |
May | 744.00 | 21.34 | 0.00 | 21.34 | 0.00 | 21.34 |
June | 720.00 | 21.38 | 0.00 | 21.38 | 0.00 | 21.38 |
July | 744.00 | 21.41 | 0.00 | 21.41 | 0.00 | 21.41 |
August | 744.00 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
September | 720.00 | 21.28 | 0.00 | 21.28 | 0.00 | 21.28 |
October | 744.00 | 21.14 | 0.00 | 21.14 | 0.00 | 21.14 |
November | 720.00 | 20.98 | 99.83 | 20.90 | 99.83 | 20.84 |
December | 744.00 | 20.87 | 232.17 | 20.76 | 232.17 | 20.69 |
Annual Sum or Average | 8760.00 | 21.16 | 943.17 | 21.10 | 943.17 | 21.05 |
Minimum of Months | 672.00 | 20.85 | 0.00 | 20.76 | 0.00 | 20.69 |
Maximum of Months | 744.00 | 21.41 | 313.50 | 21.41 | 313.50 | 21.41 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.66 | 620.00 | 20.62 | 620.00 | 20.61 |
February | 672.00 | 20.95 | 314.17 | 20.85 | 314.17 | 20.80 |
March | 744.00 | 21.22 | 87.83 | 21.14 | 87.83 | 21.08 |
April | 703.67 | 21.46 | 3.50 | 21.46 | 3.50 | 21.45 |
May | 699.50 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
June | 656.50 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
July | 639.33 | 21.43 | 5.00 | 21.44 | 0.00 | 21.44 |
August | 630.83 | 21.40 | 18.17 | 21.45 | 0.00 | 21.45 |
September | 652.67 | 21.37 | 8.83 | 21.39 | 0.00 | 21.39 |
October | 737.00 | 21.30 | 15.00 | 21.27 | 15.00 | 21.25 |
November | 720.00 | 20.87 | 303.67 | 20.77 | 303.67 | 20.71 |
December | 744.00 | 20.74 | 538.67 | 20.67 | 538.67 | 20.64 |
Annual Sum or Average | 8343.50 | 21.19 | 1914.83 | 21.08 | 1882.83 | 21.00 |
Minimum of Months | 630.83 | 20.66 | 0.00 | 20.62 | 0.00 | 20.61 |
Maximum of Months | 744.00 | 21.51 | 620.00 | 21.51 | 620.00 | 21.51 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.54 | 668.17 | 20.51 | 668.17 | 20.50 |
February | 672.00 | 20.72 | 438.00 | 20.65 | 438.00 | 20.62 |
March | 744.00 | 21.02 | 138.83 | 20.94 | 138.83 | 20.89 |
April | 719.50 | 21.38 | 8.50 | 21.37 | 8.50 | 21.37 |
May | 734.83 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
June | 688.33 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
July | 685.67 | 21.54 | 2.83 | 21.55 | 0.00 | 21.55 |
August | 670.33 | 21.49 | 4.50 | 21.50 | 0.00 | 21.50 |
September | 695.83 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
October | 744.00 | 21.13 | 32.00 | 21.09 | 32.00 | 21.04 |
November | 720.00 | 20.72 | 386.50 | 20.63 | 386.50 | 20.58 |
December | 744.00 | 20.58 | 649.00 | 20.55 | 649.00 | 20.53 |
Annual Sum or Average | 8562.50 | 21.13 | 2328.33 | 20.99 | 2321.00 | 20.91 |
Minimum of Months | 670.33 | 20.54 | 0.00 | 20.51 | 0.00 | 20.50 |
Maximum of Months | 744.00 | 21.57 | 668.17 | 21.57 | 668.17 | 21.57 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.02 | 11.50 | 21.02 | 11.50 | 21.02 |
February | 672.00 | 21.09 | 4.50 | 21.09 | 4.50 | 21.09 |
March | 744.00 | 21.34 | 0.00 | 21.34 | 0.00 | 21.34 |
April | 720.00 | 21.83 | 0.00 | 21.83 | 0.00 | 21.83 |
May | 744.00 | 22.39 | 0.00 | 22.39 | 0.00 | 22.39 |
June | 720.00 | 22.63 | 0.00 | 22.63 | 0.00 | 22.63 |
July | 711.33 | 22.97 | 0.00 | 22.97 | 0.00 | 22.97 |
August | 629.17 | 23.04 | 4.00 | 23.04 | 0.00 | 23.04 |
September | 686.83 | 22.60 | 0.00 | 22.60 | 0.00 | 22.60 |
October | 744.00 | 21.74 | 0.00 | 21.74 | 0.00 | 21.74 |
November | 720.00 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
December | 744.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
Annual Sum or Average | 8579.33 | 21.88 | 20.00 | 21.88 | 16.00 | 21.88 |
Minimum of Months | 629.17 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
Maximum of Months | 744.00 | 23.04 | 11.50 | 23.04 | 11.50 | 23.04 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.59 | 702.50 | 20.57 | 702.50 | 20.57 |
February | 670.33 | 20.84 | 423.50 | 20.75 | 423.50 | 20.71 |
March | 740.67 | 21.07 | 249.33 | 20.96 | 249.33 | 20.90 |
April | 699.00 | 21.31 | 54.50 | 21.29 | 49.33 | 21.26 |
May | 692.50 | 21.40 | 14.67 | 21.44 | 1.00 | 21.44 |
June | 664.67 | 21.46 | 12.33 | 21.49 | 0.00 | 21.49 |
July | 630.50 | 21.37 | 41.83 | 21.49 | 0.00 | 21.49 |
August | 638.67 | 21.38 | 45.67 | 21.51 | 0.00 | 21.51 |
September | 647.33 | 21.31 | 28.83 | 21.39 | 0.50 | 21.39 |
October | 730.50 | 21.17 | 56.83 | 21.08 | 56.83 | 21.00 |
November | 717.67 | 20.77 | 426.83 | 20.67 | 425.83 | 20.63 |
December | 744.00 | 20.68 | 647.67 | 20.63 | 647.67 | 20.62 |
Annual Sum or Average | 8319.83 | 21.10 | 2704.50 | 21.01 | 2556.50 | 20.92 |
Minimum of Months | 630.50 | 20.59 | 12.33 | 20.57 | 0.00 | 20.57 |
Maximum of Months | 744.00 | 21.46 | 702.50 | 21.51 | 702.50 | 21.51 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.50 | 728.83 | 20.50 | 728.83 | 20.49 |
February | 672.00 | 20.64 | 516.67 | 20.59 | 516.67 | 20.57 |
March | 744.00 | 20.85 | 392.67 | 20.77 | 392.67 | 20.73 |
April | 712.33 | 21.18 | 78.67 | 21.13 | 78.00 | 21.09 |
May | 715.00 | 21.39 | 5.50 | 21.40 | 1.00 | 21.40 |
June | 686.67 | 21.47 | 5.00 | 21.48 | 0.00 | 21.48 |
July | 669.83 | 21.45 | 21.00 | 21.51 | 0.00 | 21.51 |
August | 682.50 | 21.45 | 20.67 | 21.50 | 0.00 | 21.50 |
September | 689.83 | 21.32 | 5.00 | 21.33 | 1.50 | 21.33 |
October | 744.00 | 20.98 | 116.50 | 20.86 | 116.50 | 20.77 |
November | 720.00 | 20.64 | 493.50 | 20.56 | 493.50 | 20.52 |
December | 744.00 | 20.53 | 717.00 | 20.52 | 717.00 | 20.52 |
Annual Sum or Average | 8524.17 | 21.03 | 3101.00 | 20.90 | 3045.67 | 20.81 |
Minimum of Months | 669.83 | 20.50 | 5.00 | 20.50 | 0.00 | 20.49 |
Maximum of Months | 744.00 | 21.47 | 728.83 | 21.51 | 728.83 | 21.51 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 739.67 | 20.92 | 426.00 | 20.81 | 426.00 | 20.76 |
February | 651.67 | 21.12 | 202.17 | 21.02 | 202.17 | 20.96 |
March | 720.67 | 21.28 | 50.83 | 21.23 | 47.67 | 21.19 |
April | 683.83 | 21.42 | 8.50 | 21.43 | 2.67 | 21.43 |
May | 687.50 | 21.43 | 7.50 | 21.44 | 0.50 | 21.44 |
June | 662.17 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
July | 644.17 | 21.39 | 12.67 | 21.43 | 0.00 | 21.43 |
August | 645.17 | 21.39 | 48.83 | 21.53 | 0.00 | 21.53 |
September | 639.17 | 21.34 | 52.33 | 21.49 | 0.00 | 21.49 |
October | 688.50 | 21.27 | 16.83 | 21.31 | 3.50 | 21.30 |
November | 706.67 | 21.04 | 161.00 | 20.95 | 157.00 | 20.88 |
December | 732.67 | 20.95 | 365.33 | 20.83 | 365.33 | 20.77 |
Annual Sum or Average | 8201.83 | 21.25 | 1352.00 | 21.20 | 1204.83 | 21.13 |
Minimum of Months | 639.17 | 20.92 | 0.00 | 20.81 | 0.00 | 20.76 |
Maximum of Months | 739.67 | 21.46 | 426.00 | 21.53 | 426.00 | 21.53 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 386.83 | 23.11 | 33.50 | 23.19 | 0.00 | 23.19 |
February | 287.50 | 23.16 | 111.33 | 23.40 | 0.00 | 23.40 |
March | 194.83 | 23.21 | 160.83 | 23.59 | 0.00 | 23.59 |
April | 68.50 | 23.17 | 316.33 | 23.86 | 0.00 | 23.86 |
May | 5.83 | 23.13 | 603.00 | 23.98 | 0.00 | 23.98 |
June | 0.00 | 0.00 | 667.83 | 23.97 | 0.00 | 23.97 |
July | 1.67 | 23.99 | 736.17 | 23.97 | 1.67 | 23.97 |
August | 26.33 | 23.99 | 743.67 | 23.96 | 26.33 | 23.96 |
September | 12.83 | 23.82 | 655.83 | 23.95 | 10.50 | 23.95 |
October | 111.67 | 23.09 | 390.00 | 23.81 | 0.00 | 23.81 |
November | 253.50 | 23.10 | 195.67 | 23.49 | 1.83 | 23.49 |
December | 342.83 | 23.06 | 38.00 | 23.17 | 0.00 | 23.17 |
Annual Sum or Average | 1692.33 | 23.14 | 4652.17 | 23.76 | 40.33 | 23.76 |
Minimum of Months | 0.00 | 0.00 | 33.50 | 23.17 | 0.00 | 23.17 |
Maximum of Months | 386.83 | 23.99 | 743.67 | 23.98 | 26.33 | 23.98 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 232.33 | 23.18 | 160.83 | 23.55 | 0.00 | 23.55 |
February | 156.67 | 23.25 | 218.83 | 23.69 | 0.00 | 23.69 |
March | 56.50 | 23.28 | 364.33 | 23.93 | 0.00 | 23.93 |
April | 2.50 | 23.23 | 527.83 | 24.00 | 0.00 | 24.00 |
May | 0.00 | 0.00 | 713.17 | 24.00 | 0.00 | 24.00 |
June | 0.00 | 0.00 | 717.83 | 23.98 | 0.00 | 23.98 |
July | 0.00 | 0.00 | 743.67 | 23.99 | 0.00 | 23.99 |
August | 18.50 | 23.99 | 744.00 | 23.99 | 18.50 | 23.99 |
September | 5.17 | 24.00 | 712.17 | 23.96 | 5.17 | 23.96 |
October | 7.33 | 23.14 | 558.50 | 23.99 | 0.00 | 23.99 |
November | 105.50 | 23.15 | 341.83 | 23.81 | 1.17 | 23.81 |
December | 189.17 | 23.13 | 172.67 | 23.57 | 0.00 | 23.57 |
Annual Sum or Average | 773.67 | 23.21 | 5975.67 | 23.91 | 24.83 | 23.91 |
Minimum of Months | 0.00 | 0.00 | 160.83 | 23.55 | 0.00 | 23.55 |
Maximum of Months | 232.33 | 24.00 | 744.00 | 24.00 | 18.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 508.67 | 24.09 | 666.17 | 24.05 | 492.00 | 24.08 |
February | 465.17 | 24.06 | 612.50 | 24.01 | 452.17 | 24.04 |
March | 522.50 | 24.18 | 719.50 | 24.08 | 522.33 | 24.11 |
April | 517.17 | 24.12 | 713.00 | 24.02 | 517.17 | 24.05 |
May | 542.50 | 24.06 | 740.83 | 23.99 | 542.50 | 24.01 |
June | 532.00 | 24.01 | 719.33 | 23.95 | 532.00 | 23.97 |
July | 557.67 | 23.99 | 744.00 | 23.95 | 557.67 | 23.97 |
August | 564.67 | 23.99 | 744.00 | 23.97 | 564.67 | 23.97 |
September | 530.17 | 24.01 | 719.50 | 23.96 | 530.17 | 23.97 |
October | 535.00 | 24.11 | 740.17 | 24.01 | 535.00 | 24.04 |
November | 503.33 | 24.15 | 686.17 | 24.05 | 503.33 | 24.08 |
December | 501.50 | 24.20 | 672.50 | 24.11 | 499.67 | 24.14 |
Annual Sum or Average | 6280.33 | 24.08 | 8477.67 | 24.01 | 6248.67 | 24.03 |
Minimum of Months | 465.17 | 23.99 | 612.50 | 23.95 | 452.17 | 23.97 |
Maximum of Months | 564.67 | 24.20 | 744.00 | 24.11 | 564.67 | 24.14 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 18.33 | 21.01 | 18.33 | 21.01 |
February | 672.00 | 21.11 | 18.17 | 21.11 | 18.17 | 21.11 |
March | 744.00 | 21.33 | 0.00 | 21.33 | 0.00 | 21.33 |
April | 712.33 | 21.76 | 0.00 | 21.76 | 0.00 | 21.76 |
May | 719.17 | 22.27 | 0.00 | 22.27 | 0.00 | 22.27 |
June | 673.00 | 22.60 | 2.00 | 22.61 | 0.00 | 22.61 |
July | 540.67 | 22.82 | 66.83 | 22.94 | 0.00 | 22.94 |
August | 517.50 | 22.79 | 119.17 | 23.00 | 0.00 | 23.00 |
September | 630.17 | 22.34 | 29.50 | 22.41 | 0.00 | 22.41 |
October | 744.00 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
November | 720.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
December | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
Annual Sum or Average | 8160.83 | 21.76 | 254.00 | 21.81 | 36.50 | 21.81 |
Minimum of Months | 517.50 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 22.82 | 119.17 | 23.00 | 18.33 | 23.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.50438 | 32.90716 | 0.16403 | 5.67808 |
February | 672.00000 | 23.33554 | 34.33200 | 0.12975 | 5.51133 |
March | 744.00000 | 23.19678 | 35.06948 | 0.09846 | 5.36711 |
April | 720.00000 | 23.05683 | 38.80920 | 0.08763 | 5.32747 |
May | 744.00000 | 23.10950 | 42.79239 | -0.8717 | 21.26380 |
June | 720.00000 | 23.21929 | 45.07495 | -0.8132 | 19.19960 |
July | 744.00000 | 23.42172 | 48.66384 | -0.7137 | 15.94791 |
August | 744.00000 | 23.55559 | 52.30749 | -0.6383 | 13.72903 |
September | 720.00000 | 23.71269 | 48.84834 | -0.6018 | 12.77804 |
October | 744.00000 | 23.78709 | 40.34666 | 0.29668 | 6.91360 |
November | 720.00000 | 23.81721 | 38.21870 | 0.28910 | 6.82409 |
December | 744.00000 | 23.69440 | 33.98267 | 0.22394 | 6.12973 |
Annual Sum or Average | 8760.00000 | 23.45186 | 40.98080 | -0.1977 | 10.42219 |
Minimum of Months | 672.00000 | 23.05683 | 32.90716 | -0.8717 | 5.32747 |
Maximum of Months | 744.00000 | 23.81721 | 52.30749 | 0.29668 | 21.26380 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.05929 | 35.25952 | -0.4705 | 9.95670 |
February | 672.00000 | 21.20417 | 36.29156 | -0.3723 | 8.90312 |
March | 744.00000 | 21.30537 | 36.72374 | -0.3003 | 7.95072 |
April | 720.00000 | 21.42984 | 40.32015 | -0.2068 | 7.19478 |
May | 744.00000 | 21.50630 | 44.67185 | -1.2434 | 39.17790 |
June | 720.00000 | 21.52334 | 47.51949 | -1.1962 | 36.41641 |
July | 744.00000 | 21.87928 | 50.98477 | -1.0180 | 29.43590 |
August | 744.00000 | 22.00779 | 55.08378 | -0.9401 | 27.03871 |
September | 720.00000 | 21.77818 | 52.48800 | -1.0681 | 32.86822 |
October | 744.00000 | 21.43314 | 44.13382 | -0.1940 | 7.21040 |
November | 720.00000 | 21.11259 | 42.31776 | -0.3683 | 8.51135 |
December | 744.00000 | 21.11757 | 36.92985 | -0.4367 | 9.57915 |
Annual Sum or Average | 8760.00000 | 21.44824 | 43.59708 | -0.6529 | 18.73930 |
Minimum of Months | 672.00000 | 21.05929 | 35.25952 | -1.2434 | 7.19478 |
Maximum of Months | 744.00000 | 22.00779 | 55.08378 | -0.1940 | 39.17790 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.67953 | 36.74481 | -0.2480 | 6.60517 |
February | 672.00000 | 21.96384 | 37.40432 | -0.1661 | 6.09740 |
March | 744.00000 | 22.36755 | 37.32862 | -0.0606 | 5.45897 |
April | 720.00000 | 22.66037 | 40.34638 | 0.03821 | 5.51214 |
May | 744.00000 | 22.91914 | 44.02035 | -0.8688 | 21.60502 |
June | 720.00000 | 23.02856 | 46.34793 | -0.8091 | 19.46705 |
July | 744.00000 | 23.30717 | 49.72380 | -0.6794 | 15.30218 |
August | 744.00000 | 23.34754 | 53.68527 | -0.6371 | 14.14685 |
September | 720.00000 | 23.12261 | 51.32663 | -0.7408 | 17.40045 |
October | 744.00000 | 22.65252 | 43.91814 | 0.05758 | 5.47387 |
November | 720.00000 | 22.04209 | 42.84186 | -0.1127 | 5.74870 |
December | 744.00000 | 21.81068 | 38.26591 | -0.2055 | 6.22076 |
Annual Sum or Average | 8760.00000 | 22.57864 | 43.52739 | -0.3706 | 10.77746 |
Minimum of Months | 672.00000 | 21.67953 | 36.74481 | -0.8688 | 5.45897 |
Maximum of Months | 744.00000 | 23.34754 | 53.68527 | 0.05758 | 21.60502 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.06016 | 29.98946 | 0.63297 | 16.34601 |
February | 672.00000 | 23.06211 | 31.08438 | 0.65574 | 16.85854 |
March | 744.00000 | 23.12123 | 31.48785 | 0.69268 | 17.86355 |
April | 720.00000 | 23.13176 | 34.92841 | 0.73615 | 18.98244 |
May | 744.00000 | 23.12860 | 38.98789 | 0.06138 | 10.02679 |
June | 720.00000 | 23.08343 | 41.68086 | 0.08689 | 10.13126 |
July | 744.00000 | 23.11485 | 45.78191 | 0.13589 | 10.13170 |
August | 744.00000 | 23.11699 | 49.90131 | 0.17213 | 10.39022 |
September | 720.00000 | 23.11441 | 46.84751 | 0.12098 | 10.11472 |
October | 744.00000 | 23.14434 | 38.23392 | 0.75464 | 19.44506 |
November | 720.00000 | 23.11830 | 36.20196 | 0.70960 | 18.49174 |
December | 744.00000 | 23.09603 | 31.50405 | 0.65449 | 17.03951 |
Annual Sum or Average | 8760.00000 | 23.10801 | 38.08932 | 0.44986 | 14.63609 |
Minimum of Months | 672.00000 | 23.06016 | 29.98946 | 0.06138 | 10.02679 |
Maximum of Months | 744.00000 | 23.14434 | 49.90131 | 0.75464 | 19.44506 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.42697 | 39.47110 | -0.2816 | 7.21027 |
February | 672.00000 | 21.75429 | 40.11045 | -0.1498 | 6.73423 |
March | 744.00000 | 22.07390 | 40.24100 | -0.0384 | 6.17908 |
April | 720.00000 | 22.32763 | 43.40938 | 0.07527 | 6.22641 |
May | 744.00000 | 22.47077 | 47.40637 | -0.8481 | 21.93031 |
June | 720.00000 | 22.55960 | 49.88825 | -0.7822 | 19.11946 |
July | 744.00000 | 22.88102 | 53.30986 | -0.6199 | 14.64906 |
August | 744.00000 | 22.97033 | 57.23965 | -0.5500 | 13.52590 |
September | 720.00000 | 22.74352 | 54.72200 | -0.6714 | 17.69446 |
October | 744.00000 | 22.32614 | 46.96254 | 0.08929 | 6.51125 |
November | 720.00000 | 21.66302 | 45.94671 | -0.1478 | 6.41886 |
December | 744.00000 | 21.54400 | 41.05117 | -0.2366 | 6.97260 |
Annual Sum or Average | 8760.00000 | 22.23129 | 46.68004 | -0.3480 | 11.11964 |
Minimum of Months | 672.00000 | 21.42697 | 39.47110 | -0.8481 | 6.17908 |
Maximum of Months | 744.00000 | 22.97033 | 57.23965 | 0.08929 | 21.93031 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.15673 | 38.83584 | -0.1077 | 5.78875 |
February | 672.00000 | 22.46441 | 39.44561 | -0.0148 | 5.69852 |
March | 744.00000 | 22.83379 | 39.43933 | 0.08792 | 5.66380 |
April | 720.00000 | 23.07031 | 42.49654 | 0.17789 | 6.12613 |
May | 744.00000 | 23.24826 | 46.18883 | -0.7022 | 16.04375 |
June | 720.00000 | 23.33654 | 48.51043 | -0.6452 | 14.37083 |
July | 744.00000 | 23.52133 | 51.98781 | -0.5432 | 11.64767 |
August | 744.00000 | 23.56126 | 55.78506 | -0.4983 | 10.68219 |
September | 720.00000 | 23.42763 | 53.34732 | -0.5770 | 12.81978 |
October | 744.00000 | 23.08891 | 45.87016 | 0.20365 | 6.36578 |
November | 720.00000 | 22.50493 | 44.81313 | 0.02980 | 5.72975 |
December | 744.00000 | 22.27944 | 40.34047 | -0.0657 | 5.67941 |
Annual Sum or Average | 8760.00000 | 22.96046 | 45.62020 | -0.2226 | 8.90127 |
Minimum of Months | 672.00000 | 22.15673 | 38.83584 | -0.7022 | 5.66380 |
Maximum of Months | 744.00000 | 23.56126 | 55.78506 | 0.20365 | 16.04375 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.67676 | 40.04326 | -0.6214 | 13.50922 |
February | 672.00000 | 20.94283 | 40.91623 | -0.5130 | 11.25848 |
March | 744.00000 | 21.16163 | 41.78989 | -0.4089 | 9.09073 |
April | 720.00000 | 21.41804 | 45.15864 | -0.2701 | 7.38892 |
May | 744.00000 | 21.56245 | 48.98587 | -1.2909 | 41.08050 |
June | 720.00000 | 21.61489 | 51.35774 | -1.2306 | 38.00665 |
July | 744.00000 | 21.67155 | 52.63407 | -1.1418 | 34.13211 |
August | 744.00000 | 21.65992 | 55.28294 | -1.1378 | 33.92253 |
September | 720.00000 | 21.54444 | 55.71464 | -1.2354 | 38.44690 |
October | 744.00000 | 21.28440 | 49.94061 | -0.3013 | 7.61518 |
November | 720.00000 | 20.87401 | 47.74756 | -0.4925 | 10.69588 |
December | 744.00000 | 20.75602 | 41.83357 | -0.5855 | 12.74119 |
Annual Sum or Average | 8760.00000 | 21.26547 | 47.64611 | -0.7708 | 21.55130 |
Minimum of Months | 672.00000 | 20.67676 | 40.04326 | -1.2909 | 7.38892 |
Maximum of Months | 744.00000 | 21.67155 | 55.71464 | -0.2701 | 41.08050 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.55088 | 40.31640 | -0.6650 | 14.75992 |
February | 672.00000 | 20.72843 | 41.36422 | -0.5865 | 12.80714 |
March | 744.00000 | 20.95081 | 42.22009 | -0.4827 | 10.18108 |
April | 720.00000 | 21.26138 | 45.58034 | -0.3289 | 7.85392 |
May | 744.00000 | 21.48808 | 49.23795 | -1.3378 | 43.12689 |
June | 720.00000 | 21.56112 | 51.55369 | -1.2651 | 39.43636 |
July | 744.00000 | 21.63779 | 53.02526 | -1.1744 | 35.35912 |
August | 744.00000 | 21.61455 | 56.02120 | -1.1804 | 35.55379 |
September | 720.00000 | 21.44826 | 56.76854 | -1.3049 | 41.38301 |
October | 744.00000 | 21.08296 | 50.47527 | -0.3766 | 8.31448 |
November | 720.00000 | 20.73045 | 48.15595 | -0.5414 | 11.66308 |
December | 744.00000 | 20.59730 | 42.19158 | -0.6390 | 14.00354 |
Annual Sum or Average | 8760.00000 | 21.13980 | 48.10431 | -0.8251 | 22.92864 |
Minimum of Months | 672.00000 | 20.55088 | 40.31640 | -1.3378 | 7.85392 |
Maximum of Months | 744.00000 | 21.63779 | 56.76854 | -0.3289 | 43.12689 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.85192 | 38.56990 | -0.5397 | 11.30779 |
February | 672.00000 | 20.93879 | 39.75822 | -0.4994 | 10.50181 |
March | 744.00000 | 21.07367 | 40.63970 | -0.4366 | 9.06840 |
April | 720.00000 | 21.22274 | 44.23023 | -0.3549 | 7.77372 |
May | 744.00000 | 21.33660 | 48.14375 | -1.4527 | 48.43294 |
June | 720.00000 | 21.38142 | 50.26564 | -1.4043 | 45.86725 |
July | 744.00000 | 21.41337 | 52.64959 | -1.3671 | 43.96238 |
August | 744.00000 | 21.39214 | 55.68805 | -1.3608 | 43.61079 |
September | 720.00000 | 21.28383 | 55.60527 | -1.4320 | 47.30904 |
October | 744.00000 | 21.13696 | 48.87595 | -0.3605 | 7.75964 |
November | 720.00000 | 20.98035 | 46.29307 | -0.4416 | 9.28729 |
December | 744.00000 | 20.86980 | 40.50339 | -0.5227 | 10.88553 |
Annual Sum or Average | 8760.00000 | 21.15793 | 46.80065 | -0.8499 | 24.73157 |
Minimum of Months | 672.00000 | 20.85192 | 38.56990 | -1.4527 | 7.75964 |
Maximum of Months | 744.00000 | 21.41337 | 55.68805 | -0.3549 | 48.43294 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.66314 | 40.06443 | -0.6245 | 13.56960 |
February | 672.00000 | 20.94810 | 40.90101 | -0.5122 | 11.14377 |
March | 744.00000 | 21.21969 | 41.68128 | -0.3943 | 8.87264 |
April | 720.00000 | 21.50666 | 44.96972 | -0.2452 | 7.22833 |
May | 744.00000 | 21.58649 | 48.90964 | -1.2968 | 41.39657 |
June | 720.00000 | 21.66751 | 50.95292 | -1.2035 | 36.88772 |
July | 744.00000 | 21.69221 | 52.70519 | -1.1562 | 34.82377 |
August | 744.00000 | 21.69075 | 54.94823 | -1.1298 | 33.64465 |
September | 720.00000 | 21.54900 | 55.79500 | -1.2461 | 39.00304 |
October | 744.00000 | 21.32035 | 49.81756 | -0.2937 | 7.59632 |
November | 720.00000 | 20.86709 | 47.75728 | -0.4934 | 10.68910 |
December | 744.00000 | 20.73873 | 41.86666 | -0.5892 | 12.76825 |
Annual Sum or Average | 8760.00000 | 21.28906 | 47.55961 | -0.7671 | 21.53177 |
Minimum of Months | 672.00000 | 20.66314 | 40.06443 | -1.2968 | 7.22833 |
Maximum of Months | 744.00000 | 21.69221 | 55.79500 | -0.2452 | 41.39657 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.54431 | 40.32897 | -0.6674 | 14.85889 |
February | 672.00000 | 20.72171 | 41.36423 | -0.5882 | 12.78429 |
March | 744.00000 | 21.01526 | 42.07585 | -0.4671 | 9.79017 |
April | 720.00000 | 21.38164 | 45.26670 | -0.2978 | 7.51570 |
May | 744.00000 | 21.53821 | 49.08563 | -1.3367 | 43.10390 |
June | 720.00000 | 21.64804 | 51.08467 | -1.2280 | 37.86062 |
July | 744.00000 | 21.68092 | 53.01226 | -1.1828 | 35.81968 |
August | 744.00000 | 21.67120 | 55.53313 | -1.1651 | 34.97043 |
September | 720.00000 | 21.47950 | 56.57231 | -1.3098 | 41.72112 |
October | 744.00000 | 21.13207 | 50.31238 | -0.3665 | 8.17947 |
November | 720.00000 | 20.72175 | 48.18712 | -0.5427 | 11.70427 |
December | 744.00000 | 20.58055 | 42.22760 | -0.6428 | 14.12563 |
Annual Sum or Average | 8760.00000 | 21.17856 | 47.94897 | -0.8178 | 22.76248 |
Minimum of Months | 672.00000 | 20.54431 | 40.32897 | -1.3367 | 7.51570 |
Maximum of Months | 744.00000 | 21.68092 | 56.57231 | -0.2978 | 43.10390 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.59082 | 40.62667 | -0.6791 | 15.16650 |
February | 672.00000 | 20.84928 | 41.56446 | -0.5666 | 12.61146 |
March | 744.00000 | 21.07866 | 42.39432 | -0.4537 | 10.06000 |
April | 720.00000 | 21.36866 | 45.67905 | -0.2997 | 7.93952 |
May | 744.00000 | 21.53420 | 49.53458 | -1.3179 | 42.69016 |
June | 720.00000 | 21.59754 | 52.07209 | -1.2442 | 38.91583 |
July | 744.00000 | 21.65770 | 53.50932 | -1.1463 | 34.63219 |
August | 744.00000 | 21.63964 | 56.45503 | -1.1478 | 34.64146 |
September | 720.00000 | 21.50509 | 56.96602 | -1.2632 | 40.07255 |
October | 744.00000 | 21.20609 | 50.68699 | -0.3437 | 8.33397 |
November | 720.00000 | 20.77636 | 48.59200 | -0.5446 | 11.98573 |
December | 744.00000 | 20.67856 | 42.42431 | -0.6406 | 14.22547 |
Annual Sum or Average | 8760.00000 | 21.20867 | 48.40451 | -0.8055 | 22.66513 |
Minimum of Months | 672.00000 | 20.59082 | 40.62667 | -1.3179 | 7.93952 |
Maximum of Months | 744.00000 | 21.65770 | 56.96602 | -0.2997 | 42.69016 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.50146 | 40.83410 | -0.7171 | 16.34722 |
February | 672.00000 | 20.64344 | 42.01909 | -0.6405 | 14.31159 |
March | 744.00000 | 20.85488 | 42.86209 | -0.5328 | 11.36648 |
April | 720.00000 | 21.20466 | 46.12791 | -0.3628 | 8.50162 |
May | 744.00000 | 21.46183 | 49.79701 | -1.3666 | 44.80399 |
June | 720.00000 | 21.55228 | 52.25346 | -1.2778 | 40.29368 |
July | 744.00000 | 21.63114 | 53.91037 | -1.1780 | 35.79804 |
August | 744.00000 | 21.59635 | 57.23258 | -1.1917 | 36.30128 |
September | 720.00000 | 21.40681 | 58.06270 | -1.3382 | 43.25426 |
October | 744.00000 | 20.98230 | 51.29363 | -0.4272 | 9.26399 |
November | 720.00000 | 20.64039 | 48.99924 | -0.5935 | 13.02964 |
December | 744.00000 | 20.53274 | 42.76691 | -0.6931 | 15.58510 |
Annual Sum or Average | 8760.00000 | 21.08636 | 48.87515 | -0.8614 | 24.12753 |
Minimum of Months | 672.00000 | 20.50146 | 40.83410 | -1.3666 | 8.50162 |
Maximum of Months | 744.00000 | 21.63114 | 58.06270 | -0.3628 | 44.80399 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.93138 | 40.97912 | -0.5347 | 11.73444 |
February | 672.00000 | 21.18980 | 41.72275 | -0.4172 | 9.84291 |
March | 744.00000 | 21.34234 | 42.90052 | -0.3348 | 8.37273 |
April | 720.00000 | 21.51650 | 46.03994 | -0.2368 | 7.30657 |
May | 744.00000 | 21.56994 | 49.72830 | -1.3152 | 42.48372 |
June | 720.00000 | 21.61380 | 51.68857 | -1.2626 | 39.74236 |
July | 744.00000 | 21.65180 | 53.16456 | -1.1992 | 36.95154 |
August | 744.00000 | 21.64543 | 55.43837 | -1.1735 | 35.77750 |
September | 720.00000 | 21.56235 | 55.68697 | -1.2337 | 38.80042 |
October | 744.00000 | 21.42797 | 50.50864 | -0.2377 | 7.27986 |
November | 720.00000 | 21.08661 | 48.35222 | -0.4153 | 9.49422 |
December | 744.00000 | 20.98672 | 42.84468 | -0.4989 | 11.27470 |
Annual Sum or Average | 8760.00000 | 21.37785 | 48.28427 | -0.7404 | 21.66032 |
Minimum of Months | 672.00000 | 20.93138 | 40.97912 | -1.3152 | 7.27986 |
Maximum of Months | 744.00000 | 21.65180 | 55.68697 | -0.2368 | 42.48372 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.53380 | 38.75285 | 0.24180 | 6.69629 |
February | 672.00000 | 23.61248 | 39.49443 | 0.27975 | 7.11329 |
March | 744.00000 | 23.76483 | 39.38451 | 0.34029 | 7.68817 |
April | 720.00000 | 23.85853 | 42.21749 | 0.40943 | 8.69431 |
May | 744.00000 | 23.92834 | 45.57155 | -0.3924 | 8.38417 |
June | 720.00000 | 23.94495 | 47.79626 | -0.3429 | 7.56448 |
July | 744.00000 | 23.96835 | 51.44968 | -0.2893 | 6.86028 |
August | 744.00000 | 23.95805 | 55.40208 | -0.2688 | 6.59738 |
September | 720.00000 | 23.90735 | 53.05698 | -0.3454 | 7.67817 |
October | 744.00000 | 23.79547 | 45.63672 | 0.40499 | 8.63174 |
November | 720.00000 | 23.65242 | 44.29306 | 0.33189 | 7.71707 |
December | 744.00000 | 23.56431 | 40.18649 | 0.26115 | 6.84496 |
Annual Sum or Average | 8760.00000 | 23.79166 | 45.30043 | 0.05110 | 7.53859 |
Minimum of Months | 672.00000 | 23.53380 | 38.75285 | -0.3924 | 6.59738 |
Maximum of Months | 744.00000 | 23.96835 | 55.40208 | 0.40943 | 8.69431 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.73023 | 37.57585 | 0.32974 | 7.57078 |
February | 672.00000 | 23.78769 | 38.36015 | 0.36188 | 8.05186 |
March | 744.00000 | 23.89296 | 38.32727 | 0.41008 | 8.67818 |
April | 720.00000 | 23.94801 | 41.27332 | 0.46780 | 9.69797 |
May | 744.00000 | 23.98231 | 44.77868 | -0.3241 | 7.30187 |
June | 720.00000 | 23.98077 | 47.09250 | -0.2840 | 6.75470 |
July | 744.00000 | 23.98874 | 50.83874 | -0.2391 | 6.29256 |
August | 744.00000 | 23.98488 | 54.77516 | -0.2170 | 6.04998 |
September | 720.00000 | 23.95943 | 52.26752 | -0.2805 | 6.75647 |
October | 744.00000 | 23.90790 | 44.62746 | 0.46905 | 9.71523 |
November | 720.00000 | 23.81499 | 43.12364 | 0.41110 | 8.79893 |
December | 744.00000 | 23.75621 | 38.99224 | 0.34791 | 7.78795 |
Annual Sum or Average | 8760.00000 | 23.89504 | 44.36759 | 0.11956 | 7.78353 |
Minimum of Months | 672.00000 | 23.73023 | 37.57585 | -0.3241 | 6.04998 |
Maximum of Months | 744.00000 | 23.98874 | 54.77516 | 0.46905 | 9.71523 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.86517 | 36.33681 | 0.97611 | 27.56151 |
February | 672.00000 | 23.85252 | 37.18631 | 1.00381 | 28.74255 |
March | 744.00000 | 23.95632 | 37.48223 | 1.06305 | 31.00059 |
April | 720.00000 | 23.94218 | 40.54981 | 1.12092 | 33.52189 |
May | 744.00000 | 23.92495 | 44.16362 | 0.59608 | 17.27504 |
June | 720.00000 | 23.90833 | 46.29391 | 0.64552 | 18.19701 |
July | 744.00000 | 23.92920 | 50.02587 | 0.69816 | 19.59510 |
August | 744.00000 | 23.94335 | 53.77119 | 0.73194 | 20.40868 |
September | 720.00000 | 23.91930 | 51.16763 | 0.65159 | 18.20432 |
October | 744.00000 | 23.93084 | 43.73243 | 1.11675 | 33.14452 |
November | 720.00000 | 23.91308 | 42.03418 | 1.05790 | 30.82536 |
December | 744.00000 | 23.90812 | 37.81780 | 1.00101 | 28.58719 |
Annual Sum or Average | 8760.00000 | 23.91658 | 43.41318 | 0.88784 | 25.56712 |
Minimum of Months | 672.00000 | 23.85252 | 36.33681 | 0.59608 | 17.27504 |
Maximum of Months | 744.00000 | 23.95632 | 53.77119 | 1.12092 | 33.52189 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.01715 | 34.68750 | -0.4573 | 9.40844 |
February | 672.00000 | 21.09459 | 35.82113 | -0.4215 | 8.87313 |
March | 744.00000 | 21.29761 | 36.10005 | -0.3564 | 7.77452 |
April | 720.00000 | 21.70348 | 39.06521 | -0.2371 | 6.47754 |
May | 744.00000 | 22.19610 | 42.42130 | -1.1777 | 34.43049 |
June | 720.00000 | 22.51049 | 44.43359 | -1.0546 | 28.72266 |
July | 744.00000 | 22.88571 | 47.72565 | -0.9017 | 22.45172 |
August | 744.00000 | 22.98818 | 51.66035 | -0.8410 | 20.24122 |
September | 720.00000 | 22.49747 | 49.93747 | -1.0243 | 27.54470 |
October | 744.00000 | 21.77853 | 42.78736 | -0.1961 | 6.00416 |
November | 720.00000 | 21.20104 | 41.52214 | -0.3553 | 7.88653 |
December | 744.00000 | 21.02766 | 36.45997 | -0.4397 | 9.06017 |
Annual Sum or Average | 8760.00000 | 21.85464 | 41.91466 | -0.6230 | 15.77502 |
Minimum of Months | 672.00000 | 21.01715 | 34.68750 | -1.1777 | 6.00416 |
Maximum of Months | 744.00000 | 22.98818 | 51.66035 | -0.1961 | 34.43049 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.01574 | 38.03027 | -0.4516 | 9.28718 |
February | 672.00000 | 21.09344 | 39.16049 | -0.4153 | 8.71071 |
March | 744.00000 | 21.34469 | 39.36030 | -0.3425 | 7.53982 |
April | 720.00000 | 21.82705 | 42.11683 | -0.2034 | 6.17468 |
May | 744.00000 | 22.38561 | 45.31679 | -1.1154 | 31.46631 |
June | 720.00000 | 22.63067 | 47.42929 | -1.0144 | 26.96644 |
July | 744.00000 | 22.99731 | 50.69926 | -0.8629 | 21.06479 |
August | 744.00000 | 23.13795 | 54.51713 | -0.7884 | 18.46812 |
September | 720.00000 | 22.64438 | 52.78697 | -0.9749 | 25.69792 |
October | 744.00000 | 21.74286 | 46.13738 | -0.2010 | 6.17564 |
November | 720.00000 | 21.10785 | 45.01070 | -0.3773 | 8.11119 |
December | 744.00000 | 21.03487 | 39.76966 | -0.4348 | 8.96817 |
Annual Sum or Average | 8760.00000 | 21.91875 | 45.05633 | -0.5995 | 14.91638 |
Minimum of Months | 672.00000 | 21.01574 | 38.03027 | -1.1154 | 6.17468 |
Maximum of Months | 744.00000 | 23.13795 | 54.51713 | -0.2010 | 31.46631 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.01446 | 35.84631 | -0.4473 | 9.21581 |
February | 672.00000 | 21.11194 | 36.89841 | -0.4010 | 8.54531 |
March | 744.00000 | 21.32503 | 37.13436 | -0.3278 | 7.42401 |
April | 720.00000 | 21.78310 | 39.93140 | -0.1874 | 6.25988 |
May | 744.00000 | 22.31090 | 43.12268 | -1.0897 | 30.77756 |
June | 720.00000 | 22.67184 | 44.96040 | -0.9452 | 24.52535 |
July | 744.00000 | 23.05951 | 48.12502 | -0.7830 | 18.75023 |
August | 744.00000 | 23.08124 | 52.24966 | -0.7480 | 17.66343 |
September | 720.00000 | 22.51134 | 50.77899 | -0.9673 | 25.90461 |
October | 744.00000 | 21.60516 | 44.14255 | -0.2099 | 6.27156 |
November | 720.00000 | 21.11888 | 42.74823 | -0.3605 | 7.93600 |
December | 744.00000 | 21.03655 | 37.57523 | -0.4287 | 8.87342 |
Annual Sum or Average | 8760.00000 | 21.89071 | 42.82136 | -0.5756 | 14.37343 |
Minimum of Months | 672.00000 | 21.01446 | 35.84631 | -1.0897 | 6.25988 |
Maximum of Months | 744.00000 | 23.08124 | 52.24966 | -0.1874 | 30.77756 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.10589 | 34.02409 | -0.4232 | 8.82805 |
February | 672.00000 | 21.23532 | 35.01123 | -0.3787 | 8.24781 |
March | 744.00000 | 21.56332 | 35.02639 | -0.2899 | 6.93554 |
April | 720.00000 | 21.96383 | 37.94520 | -0.1716 | 5.95620 |
May | 744.00000 | 22.44718 | 41.24286 | -1.0853 | 30.21960 |
June | 720.00000 | 22.74800 | 43.23739 | -0.9654 | 25.05599 |
July | 744.00000 | 23.11099 | 46.51530 | -0.8154 | 19.40028 |
August | 744.00000 | 23.20401 | 50.40730 | -0.7574 | 17.46716 |
September | 720.00000 | 22.73845 | 48.65321 | -0.9343 | 23.91349 |
October | 744.00000 | 22.05030 | 41.55084 | -0.1282 | 5.57416 |
November | 720.00000 | 21.39968 | 40.51303 | -0.3007 | 7.23095 |
December | 744.00000 | 21.14091 | 35.74797 | -0.4012 | 8.42467 |
Annual Sum or Average | 8760.00000 | 22.06408 | 40.85133 | -0.5553 | 13.96704 |
Minimum of Months | 672.00000 | 21.10589 | 34.02409 | -1.0853 | 5.57416 |
Maximum of Months | 744.00000 | 23.20401 | 50.40730 | -0.1282 | 30.21960 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.123787E+10 | 12841.72 | 17-JAN-19:04 | 234.35 | 0.394424E+10 | 0.00 | 0.518211E+10 | 1.00 | 3.19 | 01-JAN-05:40 | 0.00 | 0.00 |
February | 0.389249E+10 | 54909.44 | 27-FEB-16:02 | 298.15 | 0.121305E+11 | 0.00 | 0.160230E+11 | 1.41 | 3.24 | 27-FEB-16:02 | 0.00 | 0.00 |
March | 0.807595E+10 | 64043.30 | 18-MAR-15:02 | 458.31 | 0.253348E+11 | 0.00 | 0.334108E+11 | 1.96 | 3.57 | 18-MAR-18:01 | 0.00 | 0.00 |
April | 0.235895E+11 | 108438.62 | 27-APR-15:03 | 565.95 | 0.746966E+11 | 0.00 | 0.982861E+11 | 2.49 | 3.84 | 26-APR-18:02 | 0.00 | 0.00 |
May | 0.409289E+11 | 96349.39 | 05-MAY-18:02 | 684.31 | 0.130480E+12 | 0.00 | 0.171409E+12 | 2.91 | 3.94 | 15-MAY-18:03 | 0.00 | 0.00 |
June | 0.621002E+11 | 109522.67 | 28-JUN-18:03 | 703.52 | 0.195900E+12 | 0.00 | 0.258000E+12 | 3.06 | 4.06 | 17-JUN-18:02 | 0.00 | 0.00 |
July | 0.951961E+11 | 132736.77 | 24-JUL-18:03 | 738.37 | 0.309052E+12 | 0.00 | 0.404248E+12 | 3.13 | 4.08 | 15-JUL-18:03 | 0.00 | 0.00 |
August | 0.113050E+12 | 150424.66 | 10-AUG-18:03 | 737.89 | 0.368524E+12 | 0.00 | 0.481574E+12 | 3.14 | 4.15 | 26-AUG-18:02 | 0.00 | 0.00 |
September | 0.542762E+11 | 105544.80 | 14-SEP-15:03 | 675.18 | 0.176132E+12 | 0.00 | 0.230408E+12 | 2.97 | 4.08 | 23-SEP-18:02 | 0.00 | 0.00 |
October | 0.170713E+11 | 86220.95 | 04-OCT-15:02 | 512.36 | 0.529883E+11 | 0.00 | 0.700596E+11 | 2.17 | 3.95 | 04-OCT-15:02 | 0.00 | 0.00 |
November | 0.423611E+10 | 69154.08 | 04-NOV-15:02 | 306.52 | 0.132698E+11 | 0.00 | 0.175059E+11 | 1.35 | 3.65 | 04-NOV-15:02 | 0.00 | 0.00 |
December | 0.197046E+10 | 15506.38 | 19-DEC-19:03 | 283.22 | 0.627874E+10 | 0.00 | 0.824919E+10 | 1.21 | 3.19 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.425625E+12 | 6198.14 | 0.136873E+13 | 0.00 | 0.179436E+13 | 2.24 | 0.00 | 0.00 | ||||
Minimum of Months | 0.123787E+10 | 12841.72 | 234.35 | 0.394424E+10 | 0.00 | 0.518211E+10 | 1.00 | 3.19 | 0.00 | 0.00 | ||
Maximum of Months | 0.113050E+12 | 150424.66 | 738.37 | 0.368524E+12 | 0.00 | 0.481574E+12 | 3.14 | 4.15 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.950203E+11 | 0.00 | 744.00 | 219323.84 | 12-JAN-09:01 | 0.00 | 52.29 | 80.33 | 0.31 | 0.00 | 0.09 | 0.56 | 12-JAN-09:01 |
February | 0.638863E+11 | 0.00 | 660.03 | 155691.01 | 20-FEB-19:15 | 0.00 | 51.48 | 79.60 | 0.23 | 0.00 | 0.07 | 0.40 | 20-FEB-19:15 |
March | 0.488672E+11 | 0.00 | 717.95 | 220140.61 | 03-MAR-09:02 | 0.00 | 49.88 | 78.73 | 0.15 | 0.00 | 0.05 | 0.56 | 03-MAR-09:02 |
April | 0.342318E+11 | 0.00 | 560.97 | 128779.20 | 17-APR-07:50 | 0.00 | 42.28 | 69.80 | 0.10 | 0.00 | 0.03 | 0.33 | 17-APR-07:50 |
May | 0.269895E+11 | 0.00 | 444.16 | 173204.07 | 18-MAY-08:62 | 0.00 | 37.91 | 61.49 | 0.07 | 0.00 | 0.03 | 0.44 | 18-MAY-08:62 |
June | 0.919490E+10 | 0.00 | 310.46 | 107998.78 | 15-JUN-03:03 | 0.00 | 32.93 | 51.94 | 0.02 | 0.00 | 0.01 | 0.28 | 15-JUN-03:03 |
July | 0.252943E+10 | 0.00 | 185.61 | 44791.88 | 13-JUL-08:05 | 0.00 | 37.22 | 47.97 | 0.01 | 0.00 | 0.00 | 0.11 | 13-JUL-08:05 |
August | 0.237103E+10 | 0.00 | 161.58 | 44140.32 | 21-AUG-08:05 | 0.00 | 36.02 | 45.53 | 0.00 | 0.00 | 0.00 | 0.11 | 21-AUG-08:05 |
September | 0.101352E+11 | 0.00 | 362.04 | 115435.05 | 27-SEP-04:53 | 0.00 | 39.43 | 58.95 | 0.03 | 0.00 | 0.01 | 0.29 | 27-SEP-04:53 |
October | 0.412105E+11 | 0.00 | 627.97 | 158106.80 | 16-OCT-08:62 | 0.00 | 47.83 | 73.99 | 0.12 | 0.00 | 0.04 | 0.40 | 16-OCT-08:62 |
November | 0.653994E+11 | 0.00 | 703.34 | 194358.47 | 24-NOV-16:01 | 0.00 | 51.17 | 79.13 | 0.21 | 0.00 | 0.06 | 0.50 | 24-NOV-16:01 |
December | 0.907476E+11 | 0.00 | 742.85 | 221560.93 | 07-DEC-19:03 | 0.00 | 51.93 | 80.12 | 0.29 | 0.00 | 0.09 | 0.57 | 07-DEC-19:03 |
Annual Sum or Average | 0.490583E+12 | 0.00 | 6220.97 | 0.00 | 44.17 | 67.22 | 0.13 | 0.00 | 0.04 | ||||
Minimum of Months | 0.237103E+10 | 0.00 | 161.58 | 44140.32 | 0.00 | 32.93 | 45.53 | 0.00 | 0.00 | 0.00 | 0.11 | ||
Maximum of Months | 0.950203E+11 | 0.00 | 744.00 | 221560.93 | 0.00 | 52.29 | 80.33 | 0.31 | 0.00 | 0.09 | 0.57 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.305234E+09 | 0.00 | 179.14 | 0.305234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40263.44 | 04-JAN-21:14 | 40263.44 | 04-JAN-21:14 | 0.00 | 0.00 | 0.00 |
February | 0.205599E+10 | 0.00 | 144.16 | 0.205599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79742.69 | 27-FEB-15:00 | 79742.69 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.420411E+10 | 0.00 | 169.48 | 0.420411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102908.53 | 18-MAR-16:10 | 102908.53 | 18-MAR-16:10 | 0.00 | 0.00 | 0.00 |
April | 0.286744E+11 | 0.00 | 217.32 | 0.286744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 205582.09 | 27-APR-18:10 | 205582.09 | 27-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.552908E+11 | 0.00 | 314.17 | 0.548583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 205273.59 | 05-MAY-18:00 | 177065.19 | 04-MAY-18:03 | 0.00 | 0.00 | 0.00 |
June | 0.985683E+11 | 0.00 | 436.29 | 0.984298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 221214.23 | 28-JUN-18:10 | 210065.17 | 28-JUN-18:10 | 0.00 | 0.00 | 0.00 |
July | 0.167844E+12 | 0.00 | 556.76 | 0.162029E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 271313.52 | 27-JUL-18:40 | 237611.13 | 24-JUL-18:20 | 0.00 | 0.00 | 0.00 |
August | 0.212712E+12 | 0.00 | 605.01 | 0.203226E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 298764.55 | 10-AUG-18:07 | 253018.07 | 10-AUG-18:07 | 0.00 | 0.00 | 0.00 |
September | 0.808736E+11 | 0.00 | 383.75 | 0.786906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 206178.88 | 14-SEP-17:15 | 181446.27 | 14-SEP-17:15 | 0.00 | 0.00 | 0.00 |
October | 0.149364E+11 | 0.00 | 190.78 | 0.149215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 126558.28 | 04-OCT-15:03 | 126558.28 | 04-OCT-15:03 | 0.00 | 0.00 | 0.00 |
November | 0.365309E+10 | 0.00 | 158.27 | 0.365309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103185.90 | 04-NOV-14:20 | 103185.90 | 04-NOV-14:20 | 0.00 | 0.00 | 0.00 |
December | 0.377485E+09 | 0.00 | 200.14 | 0.377485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34606.16 | 12-DEC-22:37 | 34606.16 | 12-DEC-22:37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.669495E+12 | 0.00 | 3555.27 | 0.651425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.305234E+09 | 0.00 | 144.16 | 0.305234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34606.16 | 34606.16 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.212712E+12 | 0.00 | 605.01 | 0.203226E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 298764.55 | 253018.07 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.332455E+09 | 0.00 | 10.50 | 0.332455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18783.31 | 27-FEB-15:00 | 18783.31 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.656272E+09 | 0.00 | 31.22 | 0.656272E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20929.09 | 18-MAR-16:00 | 20929.09 | 18-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.473027E+10 | 0.00 | 108.42 | 0.473027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29946.00 | 27-APR-15:02 | 29946.00 | 27-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.970367E+10 | 0.00 | 217.97 | 0.924311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36235.69 | 05-MAY-18:02 | 28414.14 | 05-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.167744E+11 | 0.00 | 379.13 | 0.167571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29532.74 | 28-JUN-15:02 | 29532.74 | 28-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.301164E+11 | 0.00 | 540.17 | 0.278837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39786.10 | 15-JUL-18:00 | 32735.79 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.384432E+11 | 0.00 | 594.67 | 0.348388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40345.78 | 30-AUG-12:40 | 32850.62 | 10-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.144140E+11 | 0.00 | 332.04 | 0.132626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38717.43 | 23-SEP-13:30 | 28194.70 | 12-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.254416E+10 | 0.00 | 106.42 | 0.253791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24147.99 | 04-OCT-15:00 | 24147.99 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.658452E+09 | 0.00 | 21.53 | 0.579607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28029.94 | 04-NOV-13:50 | 22855.52 | 04-NOV-14:20 | 0.00 | 0.00 | 0.00 |
December | 7193.64 | 0.00 | 0.06 | 7193.64 | 0.00 | 0.00 | 0.00 | 0.00 | 35.97 | 05-DEC-11:57 | 35.97 | 05-DEC-11:57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118373E+12 | 0.00 | 2342.12 | 0.110822E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.384432E+11 | 0.00 | 594.67 | 0.348388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40345.78 | 32850.62 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 9090484.77 | 0.00 | 2.22 | 8412275.13 | 0.00 | 0.00 | 0.00 | 0.00 | 9196.44 | 20-JAN-16:02 | 9196.44 | 20-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.184356E+09 | 0.00 | 40.49 | 0.151650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14246.83 | 06-FEB-16:02 | 14246.83 | 06-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.706842E+09 | 0.00 | 116.32 | 0.682674E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14850.72 | 18-MAR-15:02 | 14850.72 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.210869E+10 | 0.00 | 304.50 | 0.167351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15584.30 | 01-APR-18:02 | 15584.30 | 01-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.393075E+10 | 0.00 | 490.67 | 0.281115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15297.92 | 14-MAY-15:02 | 15297.92 | 14-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.461639E+10 | 0.00 | 572.45 | 0.292829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15148.59 | 12-JUN-15:01 | 14844.45 | 08-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.752916E+10 | 0.00 | 666.21 | 0.482540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15301.64 | 16-JUL-15:01 | 14695.40 | 25-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.737773E+10 | 0.00 | 655.54 | 0.459268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15313.72 | 28-AUG-15:02 | 15083.45 | 10-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.469678E+10 | 0.00 | 537.37 | 0.283501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14676.51 | 22-SEP-18:02 | 14656.85 | 15-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.133658E+10 | 0.00 | 241.80 | 0.954022E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15070.28 | 04-OCT-15:02 | 15070.28 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.136637E+09 | 0.00 | 32.17 | 71965650.56 | 0.00 | 0.00 | 0.00 | 0.00 | 14006.37 | 11-NOV-16:02 | 14006.37 | 11-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 18616092.82 | 0.00 | 5.81 | 17696927.63 | 0.00 | 0.00 | 0.00 | 0.00 | 13563.44 | 05-DEC-16:02 | 13563.44 | 05-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.326516E+11 | 0.00 | 3665.54 | 0.215524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9090484.77 | 0.00 | 2.22 | 8412275.13 | 0.00 | 0.00 | 0.00 | 0.00 | 9196.44 | 9196.44 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.752916E+10 | 0.00 | 666.21 | 0.482540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15584.30 | 15584.30 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2590396.11 | 0.00 | 1.44 | 2153419.97 | 0.00 | 0.00 | 0.00 | 0.00 | 3817.89 | 24-JAN-16:03 | 3817.89 | 24-JAN-16:03 | 0.00 | 0.00 | 0.00 |
February | 45560293.78 | 0.00 | 15.30 | 30837153.53 | 0.00 | 0.00 | 0.00 | 0.00 | 13295.11 | 27-FEB-16:02 | 13295.11 | 27-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.274759E+09 | 0.00 | 50.96 | 0.270011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13367.92 | 18-MAR-15:02 | 13367.92 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.135267E+10 | 0.00 | 215.29 | 0.106109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14029.59 | 01-APR-18:02 | 14029.59 | 01-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.313273E+10 | 0.00 | 434.90 | 0.226434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13771.06 | 14-MAY-15:02 | 13771.06 | 14-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.400232E+10 | 0.00 | 527.16 | 0.258256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13583.18 | 12-JUN-15:01 | 13371.71 | 02-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.656449E+10 | 0.00 | 626.39 | 0.425716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13737.19 | 16-JUL-15:01 | 13295.24 | 20-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.604914E+10 | 0.00 | 614.61 | 0.369354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13830.87 | 28-AUG-15:02 | 13726.49 | 29-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.311054E+10 | 0.00 | 464.27 | 0.176382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13480.98 | 24-SEP-15:02 | 13351.61 | 22-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.556651E+09 | 0.00 | 130.18 | 0.405752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13565.85 | 04-OCT-15:02 | 13565.85 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 44752227.89 | 0.00 | 11.49 | 23170043.01 | 0.00 | 0.00 | 0.00 | 0.00 | 13492.55 | 04-NOV-15:02 | 12753.31 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 4296991.80 | 0.00 | 1.48 | 3535860.94 | 0.00 | 0.00 | 0.00 | 0.00 | 3601.22 | 03-DEC-19:03 | 3601.22 | 03-DEC-19:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.251405E+11 | 0.00 | 3093.47 | 0.163580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2590396.11 | 0.00 | 1.44 | 2153419.97 | 0.00 | 0.00 | 0.00 | 0.00 | 3601.22 | 3601.22 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.656449E+10 | 0.00 | 626.39 | 0.425716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14029.59 | 14029.59 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 20465098.89 | 0.00 | 2.00 | 20465098.89 | 0.00 | 0.00 | 0.00 | 0.00 | 4582.63 | 08-JAN-14:40 | 4582.63 | 08-JAN-14:40 | 0.00 | 0.00 | 0.00 |
February | 0.231332E+10 | 0.00 | 44.10 | 0.231332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34513.54 | 08-FEB-14:00 | 34513.54 | 08-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.565474E+10 | 0.00 | 136.38 | 0.565474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46834.27 | 02-MAR-13:30 | 46834.27 | 02-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.924778E+10 | 0.00 | 246.68 | 0.776762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42082.96 | 27-APR-13:20 | 38095.76 | 27-APR-13:10 | 0.00 | 0.00 | 0.00 |
May | 0.121638E+11 | 0.00 | 322.21 | 0.925114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41461.31 | 04-MAY-13:20 | 36089.88 | 04-MAY-13:20 | 0.00 | 0.00 | 0.00 |
June | 0.127592E+11 | 0.00 | 379.77 | 0.688043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29319.41 | 28-JUN-13:10 | 23963.40 | 09-JUN-12:40 | 0.00 | 0.00 | 0.00 |
July | 0.218399E+11 | 0.00 | 480.19 | 0.117487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41009.86 | 31-JUL-13:00 | 32491.03 | 31-JUL-13:20 | 0.00 | 0.00 | 0.00 |
August | 0.271512E+11 | 0.00 | 500.00 | 0.155193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52861.44 | 24-AUG-14:50 | 45353.47 | 23-AUG-12:30 | 0.00 | 0.00 | 0.00 |
September | 0.238370E+11 | 0.00 | 390.32 | 0.148896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54484.41 | 14-SEP-13:30 | 44040.90 | 10-SEP-15:03 | 0.00 | 0.00 | 0.00 |
October | 0.124482E+11 | 0.00 | 220.09 | 0.109426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56017.09 | 04-OCT-12:30 | 56017.09 | 04-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 0.112967E+10 | 0.00 | 26.62 | 0.739222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35295.01 | 04-NOV-13:30 | 25309.18 | 04-NOV-13:40 | 0.00 | 0.00 | 0.00 |
December | 0.110088E+10 | 0.00 | 23.42 | 0.110088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30395.72 | 05-DEC-12:25 | 30395.72 | 05-DEC-12:25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129666E+12 | 0.00 | 2771.79 | 0.868281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 20465098.89 | 0.00 | 2.00 | 20465098.89 | 0.00 | 0.00 | 0.00 | 0.00 | 4582.63 | 4582.63 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.271512E+11 | 0.00 | 500.00 | 0.155193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56017.09 | 56017.09 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.239592E+09 | 0.00 | 28.46 | 0.154160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30315.95 | 09-JAN-19:04 | 30315.95 | 09-JAN-19:04 | 0.00 | 0.00 | 0.00 |
February | 0.132398E+10 | 0.00 | 90.02 | 0.640198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53766.71 | 25-FEB-09:03 | 53766.71 | 25-FEB-09:03 | 0.00 | 0.00 | 0.00 |
March | 0.346448E+10 | 0.00 | 231.72 | 0.262306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53956.08 | 21-MAR-18:02 | 53956.08 | 21-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.110374E+11 | 0.00 | 395.85 | 0.828232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61385.87 | 01-APR-18:02 | 61385.87 | 01-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.215298E+11 | 0.00 | 512.83 | 0.152820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63956.87 | 05-MAY-18:02 | 61647.79 | 14-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.286246E+11 | 0.00 | 508.21 | 0.202742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62771.73 | 09-JUN-18:02 | 62771.73 | 09-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.359726E+11 | 0.00 | 525.41 | 0.246532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66065.56 | 15-JUL-18:02 | 64908.93 | 24-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.350617E+11 | 0.00 | 525.50 | 0.219150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65521.64 | 13-AUG-15:02 | 64219.08 | 10-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.201181E+11 | 0.00 | 497.31 | 0.107798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61476.70 | 23-SEP-15:02 | 58758.54 | 13-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.668501E+10 | 0.00 | 347.54 | 0.367824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58788.80 | 01-OCT-08:62 | 55233.57 | 02-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.225679E+10 | 0.00 | 147.55 | 0.863824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56772.97 | 05-NOV-08:62 | 53943.92 | 04-NOV-08:63 | 0.00 | 0.00 | 0.00 |
December | 0.178853E+09 | 0.00 | 19.99 | 0.118246E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33120.92 | 05-DEC-19:03 | 33120.92 | 05-DEC-19:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166493E+12 | 0.00 | 3830.41 | 0.109264E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.178853E+09 | 0.00 | 19.99 | 0.118246E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30315.95 | 30315.95 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.359726E+11 | 0.00 | 525.50 | 0.246532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66065.56 | 64908.93 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 7737990.56 | 0.00 | 3.20 | 7125174.14 | 0.00 | 0.00 | 0.00 | 0.00 | 3455.22 | 10-JAN-09:03 | 3455.22 | 10-JAN-09:03 | 0.00 | 0.00 | 0.00 |
February | 0.165255E+09 | 0.00 | 39.83 | 0.128869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11822.93 | 08-FEB-16:02 | 11822.93 | 08-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.649575E+09 | 0.00 | 135.89 | 0.605980E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13286.59 | 18-MAR-15:02 | 13286.59 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.216076E+10 | 0.00 | 340.67 | 0.168078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13860.31 | 01-APR-18:02 | 13860.31 | 01-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.338929E+10 | 0.00 | 475.80 | 0.233345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13686.58 | 14-MAY-15:02 | 13686.58 | 14-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.499394E+10 | 0.00 | 606.15 | 0.320699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13641.55 | 12-JUN-15:01 | 13281.76 | 08-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.649394E+10 | 0.00 | 678.58 | 0.399044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13917.32 | 31-JUL-18:02 | 13553.48 | 24-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.729568E+10 | 0.00 | 665.50 | 0.452899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14054.40 | 30-AUG-08:62 | 13678.86 | 07-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.424362E+10 | 0.00 | 524.11 | 0.253838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13492.26 | 24-SEP-15:02 | 13279.12 | 22-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.131169E+10 | 0.00 | 250.05 | 0.921696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13482.95 | 04-OCT-15:02 | 13482.95 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.141153E+09 | 0.00 | 41.47 | 70111800.17 | 0.00 | 0.00 | 0.00 | 0.00 | 13388.00 | 04-NOV-15:02 | 12686.75 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 51142684.37 | 0.00 | 14.38 | 48100787.87 | 0.00 | 0.00 | 0.00 | 0.00 | 4002.10 | 29-DEC-09:03 | 3646.41 | 02-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.309038E+11 | 0.00 | 3775.63 | 0.200609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7737990.56 | 0.00 | 3.20 | 7125174.14 | 0.00 | 0.00 | 0.00 | 0.00 | 3455.22 | 3455.22 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.729568E+10 | 0.00 | 678.58 | 0.452899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14054.40 | 13860.31 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3462527.96 | 0.00 | 1.63 | 3002464.10 | 0.00 | 0.00 | 0.00 | 0.00 | 2886.72 | 05-JAN-09:04 | 2886.72 | 05-JAN-09:04 | 0.00 | 0.00 | 0.00 |
February | 20347280.71 | 0.00 | 12.83 | 12919202.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4381.11 | 27-FEB-09:01 | 3875.98 | 27-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.176982E+09 | 0.00 | 49.40 | 0.159658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11149.89 | 02-MAR-09:01 | 11149.89 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 |
April | 0.131762E+10 | 0.00 | 248.51 | 0.989489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12120.61 | 02-APR-15:02 | 12120.61 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.256288E+10 | 0.00 | 422.32 | 0.175166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12417.60 | 14-MAY-15:02 | 12417.60 | 14-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.431044E+10 | 0.00 | 578.29 | 0.282612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12391.01 | 12-JUN-15:01 | 12158.84 | 28-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.548881E+10 | 0.00 | 666.79 | 0.340620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12764.01 | 31-JUL-18:02 | 12506.92 | 30-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.592044E+10 | 0.00 | 639.32 | 0.355157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12710.68 | 09-AUG-18:02 | 12449.66 | 23-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.263955E+10 | 0.00 | 443.50 | 0.148058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12770.89 | 23-SEP-15:02 | 12028.63 | 11-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.496829E+09 | 0.00 | 126.34 | 0.324312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12019.92 | 04-OCT-15:02 | 12019.92 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 23197726.62 | 0.00 | 13.42 | 8691963.98 | 0.00 | 0.00 | 0.00 | 0.00 | 6951.11 | 04-NOV-15:02 | 4622.58 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 4934408.93 | 0.00 | 1.76 | 4362900.04 | 0.00 | 0.00 | 0.00 | 0.00 | 2777.56 | 03-DEC-09:03 | 2777.56 | 03-DEC-09:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229655E+11 | 0.00 | 3204.11 | 0.145186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3462527.96 | 0.00 | 1.63 | 3002464.10 | 0.00 | 0.00 | 0.00 | 0.00 | 2777.56 | 2777.56 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.592044E+10 | 0.00 | 666.79 | 0.355157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12770.89 | 12506.92 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1394549.60 | 0.00 | 1.21 | 1281811.31 | 0.00 | 0.00 | 0.00 | 0.00 | 1924.55 | 20-JAN-16:02 | 1924.55 | 20-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 45850530.62 | 0.00 | 30.17 | 39190490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 3717.99 | 06-FEB-16:02 | 3717.99 | 06-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.173221E+09 | 0.00 | 91.51 | 0.169062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3875.77 | 18-MAR-15:02 | 3875.77 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.517273E+09 | 0.00 | 245.15 | 0.425556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4067.07 | 01-APR-18:02 | 4067.07 | 01-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.959932E+09 | 0.00 | 421.23 | 0.719541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3992.28 | 14-MAY-15:02 | 3992.28 | 14-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.112154E+10 | 0.00 | 512.89 | 0.737563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3966.87 | 12-JUN-15:01 | 3874.00 | 08-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.186964E+10 | 0.00 | 648.34 | 0.122968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3999.67 | 16-JUL-15:01 | 3944.68 | 31-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.178891E+10 | 0.00 | 621.89 | 0.114610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4043.53 | 25-AUG-08:62 | 3960.21 | 10-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.109975E+10 | 0.00 | 459.75 | 0.695738E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3946.61 | 23-SEP-08:62 | 3767.01 | 23-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.288514E+09 | 0.00 | 176.31 | 0.218301E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3932.84 | 04-OCT-15:02 | 3932.84 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 32375897.35 | 0.00 | 22.53 | 18660115.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3684.11 | 11-NOV-16:02 | 3684.11 | 11-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 3514156.28 | 0.00 | 2.24 | 3235718.86 | 0.00 | 0.00 | 0.00 | 0.00 | 3559.63 | 05-DEC-16:02 | 3559.63 | 05-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.790192E+10 | 0.00 | 3233.21 | 0.540391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1394549.60 | 0.00 | 1.21 | 1281811.31 | 0.00 | 0.00 | 0.00 | 0.00 | 1924.55 | 1924.55 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.186964E+10 | 0.00 | 648.34 | 0.122968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4067.07 | 4067.07 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 482531.01 | 0.00 | 0.32 | 381086.20 | 0.00 | 0.00 | 0.00 | 0.00 | 718.59 | 11-JAN-16:05 | 624.44 | 25-JAN-16:04 | 0.00 | 0.00 | 0.00 |
February | 8682963.43 | 0.00 | 11.78 | 6483379.46 | 0.00 | 0.00 | 0.00 | 0.00 | 3440.80 | 27-FEB-16:02 | 3440.80 | 27-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 61697128.26 | 0.00 | 39.81 | 60746426.64 | 0.00 | 0.00 | 0.00 | 0.00 | 3459.64 | 18-MAR-15:02 | 3459.64 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.324437E+09 | 0.00 | 170.74 | 0.263920E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3630.91 | 01-APR-18:02 | 3630.91 | 01-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.749187E+09 | 0.00 | 356.51 | 0.571375E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3564.28 | 14-MAY-15:02 | 3564.28 | 14-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.954531E+09 | 0.00 | 468.44 | 0.646638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3526.15 | 12-JUN-15:01 | 3460.67 | 02-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.160963E+10 | 0.00 | 614.51 | 0.107611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3566.36 | 16-JUL-15:01 | 3557.38 | 31-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.143384E+10 | 0.00 | 575.66 | 0.907873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3585.64 | 28-AUG-15:02 | 3527.33 | 29-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.684310E+09 | 0.00 | 362.05 | 0.417465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3510.56 | 24-SEP-15:02 | 3418.59 | 13-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.107667E+09 | 0.00 | 78.34 | 83883771.99 | 0.00 | 0.00 | 0.00 | 0.00 | 3510.88 | 04-OCT-15:02 | 3510.88 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 10803747.32 | 0.00 | 7.16 | 6213853.23 | 0.00 | 0.00 | 0.00 | 0.00 | 3499.38 | 04-NOV-15:02 | 3296.36 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 1112348.84 | 0.00 | 0.66 | 948988.11 | 0.00 | 0.00 | 0.00 | 0.00 | 847.81 | 10-DEC-16:03 | 778.89 | 05-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.594638E+10 | 0.00 | 2685.96 | 0.404204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 482531.01 | 0.00 | 0.32 | 381086.20 | 0.00 | 0.00 | 0.00 | 0.00 | 718.59 | 624.44 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.160963E+10 | 0.00 | 614.51 | 0.107611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3630.91 | 3630.91 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.386361E+09 | 0.00 | 47.78 | 0.381536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20203.47 | 20-JAN-16:02 | 20203.47 | 20-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.158324E+10 | 0.00 | 151.39 | 0.139618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20215.56 | 01-FEB-16:02 | 20215.56 | 01-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.276938E+10 | 0.00 | 259.42 | 0.255054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21062.24 | 18-MAR-15:02 | 21062.24 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.421691E+10 | 0.00 | 401.24 | 0.332985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21240.23 | 27-APR-18:02 | 21240.23 | 27-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.533718E+10 | 0.00 | 505.19 | 0.357817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21702.17 | 05-MAY-18:02 | 21694.31 | 14-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.605830E+10 | 0.00 | 584.13 | 0.350253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21739.53 | 12-JUN-15:01 | 21589.28 | 09-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.894587E+10 | 0.00 | 661.30 | 0.517717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22173.38 | 15-JUL-18:02 | 21474.74 | 24-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.101841E+11 | 0.00 | 653.03 | 0.621749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21810.28 | 09-AUG-18:02 | 21669.23 | 29-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.818835E+10 | 0.00 | 563.78 | 0.523116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21059.13 | 22-SEP-18:02 | 20829.81 | 14-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.427554E+10 | 0.00 | 387.98 | 0.312743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21373.06 | 04-OCT-15:02 | 21373.06 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.104780E+10 | 0.00 | 115.17 | 0.752556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20211.29 | 10-NOV-16:01 | 20211.29 | 10-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.879794E+09 | 0.00 | 91.54 | 0.853483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20208.16 | 06-DEC-16:02 | 20208.16 | 06-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.538728E+11 | 0.00 | 4421.96 | 0.360981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.386361E+09 | 0.00 | 47.78 | 0.381536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20203.47 | 20203.47 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.101841E+11 | 0.00 | 661.30 | 0.621749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22173.38 | 21694.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 438.55 | 260.88 | 177.67 | 386.54 | 513.67 | 0.00 | 0.00 | 0.00 |
February | 674.87 | 418.72 | 256.15 | 676.06 | 451.92 | 0.00 | 0.00 | 0.00 |
March | 715.89 | 378.50 | 337.40 | 755.36 | 375.57 | 0.00 | 0.00 | 0.00 |
April | 756.46 | 324.65 | 431.81 | 851.19 | 302.22 | 0.00 | 0.00 | 0.00 |
May | 704.79 | 214.87 | 489.92 | 813.57 | 240.13 | 0.00 | 0.00 | 0.00 |
June | 637.68 | 170.67 | 467.01 | 760.58 | 177.27 | 0.00 | 0.00 | 0.00 |
July | 692.81 | 251.56 | 441.25 | 894.13 | 157.10 | 0.00 | 0.00 | 0.00 |
August | 738.59 | 339.38 | 399.21 | 973.19 | 152.17 | 0.00 | 0.00 | 0.00 |
September | 819.19 | 448.04 | 371.15 | 1008.76 | 226.59 | 0.00 | 0.00 | 0.00 |
October | 741.03 | 453.68 | 287.34 | 835.07 | 318.65 | 0.00 | 0.00 | 0.00 |
November | 443.48 | 253.85 | 189.63 | 424.24 | 406.85 | 0.00 | 0.00 | 0.00 |
December | 464.15 | 300.16 | 163.99 | 448.39 | 516.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 651.97 | 317.29 | 334.69 | 735.80 | 319.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 438.55 | 170.67 | 163.99 | 386.54 | 152.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 819.19 | 453.68 | 489.92 | 1008.76 | 516.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1234.93 | 734.63 | 500.29 | 1072.69 | 1490.99 | 0.00 | 0.00 | 0.00 |
February | 1900.38 | 1179.08 | 721.29 | 1879.61 | 1324.18 | 0.00 | 0.00 | 0.00 |
March | 2015.91 | 1065.82 | 950.09 | 2099.72 | 1123.78 | 0.00 | 0.00 | 0.00 |
April | 2130.15 | 914.20 | 1215.94 | 2362.19 | 917.07 | 0.00 | 0.00 | 0.00 |
May | 1984.66 | 605.06 | 1379.59 | 2252.86 | 738.88 | 0.00 | 0.00 | 0.00 |
June | 1795.66 | 480.59 | 1315.07 | 2097.26 | 561.49 | 0.00 | 0.00 | 0.00 |
July | 1950.90 | 708.37 | 1242.53 | 2477.93 | 500.24 | 0.00 | 0.00 | 0.00 |
August | 2079.83 | 955.67 | 1124.16 | 2704.05 | 488.26 | 0.00 | 0.00 | 0.00 |
September | 2306.78 | 1261.66 | 1045.13 | 2809.12 | 703.94 | 0.00 | 0.00 | 0.00 |
October | 2086.69 | 1277.54 | 809.14 | 2322.79 | 971.45 | 0.00 | 0.00 | 0.00 |
November | 1248.82 | 714.83 | 533.99 | 1176.37 | 1201.29 | 0.00 | 0.00 | 0.00 |
December | 1307.01 | 845.22 | 461.79 | 1246.81 | 1504.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1835.92 | 893.47 | 942.45 | 2042.35 | 958.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1234.93 | 480.59 | 461.79 | 1072.69 | 488.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2306.78 | 1277.54 | 1379.59 | 2809.12 | 1504.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1604.24 | 954.33 | 649.91 | 1401.79 | 2080.88 | 0.00 | 0.00 | 0.00 |
February | 2468.70 | 1531.69 | 937.00 | 2467.40 | 1838.59 | 0.00 | 0.00 | 0.00 |
March | 2618.78 | 1384.56 | 1234.22 | 2759.72 | 1570.14 | 0.00 | 0.00 | 0.00 |
April | 2767.18 | 1187.60 | 1579.58 | 3106.03 | 1280.75 | 0.00 | 0.00 | 0.00 |
May | 2578.18 | 786.01 | 1792.17 | 2956.50 | 1041.04 | 0.00 | 0.00 | 0.00 |
June | 2332.66 | 624.32 | 1708.35 | 2745.51 | 795.73 | 0.00 | 0.00 | 0.00 |
July | 2534.33 | 920.22 | 1614.12 | 3256.87 | 702.02 | 0.00 | 0.00 | 0.00 |
August | 2701.82 | 1241.47 | 1460.35 | 3555.05 | 679.35 | 0.00 | 0.00 | 0.00 |
September | 2996.64 | 1638.96 | 1357.68 | 3691.43 | 982.13 | 0.00 | 0.00 | 0.00 |
October | 2710.73 | 1659.60 | 1051.12 | 3050.12 | 1361.95 | 0.00 | 0.00 | 0.00 |
November | 1622.29 | 928.61 | 693.68 | 1533.41 | 1695.13 | 0.00 | 0.00 | 0.00 |
December | 1697.88 | 1097.99 | 599.89 | 1632.40 | 2099.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2384.96 | 1160.66 | 1224.30 | 2680.45 | 1341.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1604.24 | 624.32 | 599.89 | 1401.79 | 679.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2996.64 | 1659.60 | 1792.17 | 3691.43 | 2099.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.71 | 51.58 | 35.13 | 77.90 | 102.27 | 0.00 | 0.00 | 0.00 |
February | 133.43 | 82.79 | 50.64 | 135.28 | 89.93 | 0.00 | 0.00 | 0.00 |
March | 141.54 | 74.84 | 66.71 | 150.58 | 74.86 | 0.00 | 0.00 | 0.00 |
April | 149.57 | 64.19 | 85.38 | 168.05 | 60.93 | 0.00 | 0.00 | 0.00 |
May | 139.35 | 42.48 | 96.87 | 159.31 | 48.46 | 0.00 | 0.00 | 0.00 |
June | 126.08 | 33.74 | 92.34 | 148.63 | 35.18 | 0.00 | 0.00 | 0.00 |
July | 136.98 | 49.74 | 87.24 | 176.12 | 30.16 | 0.00 | 0.00 | 0.00 |
August | 146.03 | 67.10 | 78.93 | 193.10 | 28.16 | 0.00 | 0.00 | 0.00 |
September | 161.97 | 88.59 | 73.38 | 201.04 | 43.84 | 0.00 | 0.00 | 0.00 |
October | 146.51 | 89.70 | 56.81 | 166.48 | 62.53 | 0.00 | 0.00 | 0.00 |
November | 87.68 | 50.19 | 37.49 | 85.28 | 80.24 | 0.00 | 0.00 | 0.00 |
December | 91.77 | 59.35 | 32.42 | 90.23 | 101.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.91 | 62.73 | 66.17 | 146.04 | 63.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.71 | 33.74 | 32.42 | 77.90 | 28.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 161.97 | 89.70 | 96.87 | 201.04 | 102.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.25 | 18.52 | 43.73 | 27.29 | 205.51 | 0.00 | 0.00 | 0.00 |
February | 111.04 | 41.69 | 69.36 | 77.41 | 178.31 | 0.00 | 0.00 | 0.00 |
March | 155.56 | 52.59 | 102.96 | 131.96 | 142.37 | 0.00 | 0.00 | 0.00 |
April | 236.38 | 90.26 | 146.12 | 240.18 | 111.04 | 0.00 | 0.00 | 0.00 |
May | 304.75 | 124.07 | 180.68 | 339.09 | 87.81 | 0.00 | 0.00 | 0.00 |
June | 292.45 | 113.33 | 179.11 | 334.96 | 63.73 | 0.00 | 0.00 | 0.00 |
July | 361.52 | 189.97 | 171.55 | 448.61 | 54.77 | 0.00 | 0.00 | 0.00 |
August | 299.20 | 152.61 | 146.59 | 376.37 | 51.82 | 0.00 | 0.00 | 0.00 |
September | 244.45 | 117.59 | 126.86 | 284.51 | 81.73 | 0.00 | 0.00 | 0.00 |
October | 139.79 | 57.47 | 82.32 | 130.82 | 120.25 | 0.00 | 0.00 | 0.00 |
November | 69.23 | 19.68 | 49.55 | 40.62 | 158.13 | 0.00 | 0.00 | 0.00 |
December | 58.44 | 20.29 | 38.15 | 31.69 | 203.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 195.10 | 83.49 | 111.61 | 206.13 | 121.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 58.44 | 18.52 | 38.15 | 27.29 | 51.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.52 | 189.97 | 180.68 | 448.61 | 205.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.55 | 0.00 | 19.55 | 1.07 | 113.30 | 0.00 | 0.00 | 0.00 |
February | 30.42 | 0.00 | 30.42 | 7.36 | 98.04 | 0.00 | 0.00 | 0.00 |
March | 44.83 | 0.00 | 44.83 | 21.97 | 77.11 | 0.00 | 0.00 | 0.00 |
April | 63.66 | 0.39 | 63.27 | 45.01 | 58.99 | 0.00 | 0.00 | 0.00 |
May | 81.67 | 2.45 | 79.22 | 70.66 | 45.42 | 0.00 | 0.00 | 0.00 |
June | 85.95 | 5.75 | 80.20 | 83.11 | 32.26 | 0.00 | 0.00 | 0.00 |
July | 81.81 | 6.59 | 75.22 | 88.09 | 27.54 | 0.00 | 0.00 | 0.00 |
August | 66.31 | 1.99 | 64.32 | 73.66 | 26.04 | 0.00 | 0.00 | 0.00 |
September | 51.33 | 0.04 | 51.29 | 44.01 | 43.57 | 0.00 | 0.00 | 0.00 |
October | 35.14 | 0.00 | 35.14 | 19.35 | 64.57 | 0.00 | 0.00 | 0.00 |
November | 22.14 | 0.00 | 22.14 | 4.63 | 85.87 | 0.00 | 0.00 | 0.00 |
December | 16.61 | 0.00 | 16.61 | 0.65 | 110.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.05 | 1.44 | 48.60 | 38.49 | 65.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.61 | 0.00 | 16.61 | 0.65 | 26.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.95 | 6.59 | 80.20 | 88.09 | 113.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.25 | 18.52 | 43.73 | 28.98 | 203.68 | 0.00 | 0.00 | 0.00 |
February | 111.04 | 41.69 | 69.36 | 80.94 | 175.65 | 0.00 | 0.00 | 0.00 |
March | 155.56 | 52.59 | 102.96 | 136.33 | 140.17 | 0.00 | 0.00 | 0.00 |
April | 236.38 | 90.26 | 146.12 | 244.31 | 109.66 | 0.00 | 0.00 | 0.00 |
May | 304.75 | 124.07 | 180.68 | 341.68 | 87.11 | 0.00 | 0.00 | 0.00 |
June | 292.45 | 113.33 | 179.11 | 336.97 | 63.24 | 0.00 | 0.00 | 0.00 |
July | 361.52 | 189.97 | 171.55 | 450.75 | 54.23 | 0.00 | 0.00 | 0.00 |
August | 299.20 | 152.61 | 146.59 | 379.13 | 51.06 | 0.00 | 0.00 | 0.00 |
September | 244.45 | 117.59 | 126.86 | 288.18 | 80.30 | 0.00 | 0.00 | 0.00 |
October | 139.79 | 57.47 | 82.32 | 135.24 | 117.95 | 0.00 | 0.00 | 0.00 |
November | 69.23 | 19.68 | 49.55 | 42.73 | 156.25 | 0.00 | 0.00 | 0.00 |
December | 58.44 | 20.29 | 38.15 | 33.73 | 201.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 195.10 | 83.49 | 111.61 | 209.08 | 119.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 58.44 | 18.52 | 38.15 | 28.98 | 51.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.52 | 189.97 | 180.68 | 450.75 | 203.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.35 | 41.26 | 28.10 | 62.42 | 77.58 | 0.00 | 0.00 | 0.00 |
February | 106.72 | 66.22 | 40.51 | 107.43 | 72.12 | 0.00 | 0.00 | 0.00 |
March | 113.21 | 59.86 | 53.36 | 118.08 | 65.22 | 0.00 | 0.00 | 0.00 |
April | 119.63 | 51.34 | 68.29 | 131.55 | 55.00 | 0.00 | 0.00 | 0.00 |
May | 111.46 | 33.98 | 77.48 | 125.30 | 44.32 | 0.00 | 0.00 | 0.00 |
June | 100.84 | 26.99 | 73.85 | 116.37 | 33.45 | 0.00 | 0.00 | 0.00 |
July | 109.56 | 39.78 | 69.78 | 139.26 | 29.07 | 0.00 | 0.00 | 0.00 |
August | 116.80 | 53.67 | 63.13 | 152.49 | 27.82 | 0.00 | 0.00 | 0.00 |
September | 129.55 | 70.85 | 58.69 | 158.35 | 41.39 | 0.00 | 0.00 | 0.00 |
October | 117.19 | 71.75 | 45.44 | 130.11 | 57.34 | 0.00 | 0.00 | 0.00 |
November | 70.13 | 40.14 | 29.99 | 67.22 | 65.03 | 0.00 | 0.00 | 0.00 |
December | 73.40 | 47.47 | 25.93 | 71.77 | 79.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.11 | 50.18 | 52.93 | 115.05 | 53.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.35 | 26.99 | 25.93 | 62.42 | 27.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 129.55 | 71.75 | 77.48 | 158.35 | 79.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.64 | 0.00 | 15.64 | 0.58 | 95.73 | 0.00 | 0.00 | 0.00 |
February | 24.34 | 0.00 | 24.34 | 5.28 | 81.71 | 0.00 | 0.00 | 0.00 |
March | 35.87 | 0.00 | 35.87 | 17.33 | 63.41 | 0.00 | 0.00 | 0.00 |
April | 50.93 | 0.31 | 50.62 | 37.37 | 47.46 | 0.00 | 0.00 | 0.00 |
May | 65.34 | 1.96 | 63.38 | 59.54 | 35.79 | 0.00 | 0.00 | 0.00 |
June | 68.77 | 4.60 | 64.17 | 69.95 | 25.03 | 0.00 | 0.00 | 0.00 |
July | 65.45 | 5.27 | 60.19 | 75.23 | 20.63 | 0.00 | 0.00 | 0.00 |
August | 53.06 | 1.59 | 51.46 | 63.24 | 19.41 | 0.00 | 0.00 | 0.00 |
September | 41.07 | 0.03 | 41.04 | 37.71 | 33.68 | 0.00 | 0.00 | 0.00 |
October | 28.12 | 0.00 | 28.12 | 15.64 | 52.78 | 0.00 | 0.00 | 0.00 |
November | 17.71 | 0.00 | 17.71 | 3.19 | 72.45 | 0.00 | 0.00 | 0.00 |
December | 13.29 | 0.00 | 13.29 | 0.33 | 93.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.04 | 1.16 | 38.89 | 32.28 | 53.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.29 | 0.00 | 13.29 | 0.33 | 19.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.77 | 5.27 | 64.17 | 75.23 | 95.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 58.42 | 14.64 | 43.78 | 20.64 | 203.24 | 0.00 | 0.00 | 0.00 |
February | 107.62 | 38.12 | 69.50 | 69.79 | 174.86 | 0.00 | 0.00 | 0.00 |
March | 161.29 | 58.49 | 102.80 | 134.71 | 137.82 | 0.00 | 0.00 | 0.00 |
April | 249.11 | 103.37 | 145.74 | 252.00 | 106.83 | 0.00 | 0.00 | 0.00 |
May | 265.24 | 92.35 | 172.89 | 284.93 | 85.21 | 0.00 | 0.00 | 0.00 |
June | 317.46 | 138.17 | 179.29 | 366.61 | 61.30 | 0.00 | 0.00 | 0.00 |
July | 296.07 | 133.11 | 162.96 | 358.55 | 50.37 | 0.00 | 0.00 | 0.00 |
August | 290.63 | 145.38 | 145.25 | 361.82 | 48.45 | 0.00 | 0.00 | 0.00 |
September | 215.23 | 99.44 | 115.79 | 240.97 | 78.25 | 0.00 | 0.00 | 0.00 |
October | 140.73 | 60.13 | 80.60 | 129.70 | 117.34 | 0.00 | 0.00 | 0.00 |
November | 68.87 | 19.50 | 49.37 | 38.23 | 155.71 | 0.00 | 0.00 | 0.00 |
December | 56.34 | 18.11 | 38.23 | 25.98 | 199.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 185.93 | 76.91 | 109.02 | 190.94 | 118.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.34 | 14.64 | 38.23 | 20.64 | 48.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 317.46 | 145.38 | 179.29 | 366.61 | 203.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.71 | 51.58 | 35.13 | 77.87 | 102.13 | 0.00 | 0.00 | 0.00 |
February | 133.43 | 82.79 | 50.64 | 135.02 | 89.68 | 0.00 | 0.00 | 0.00 |
March | 141.54 | 74.84 | 66.71 | 149.76 | 74.63 | 0.00 | 0.00 | 0.00 |
April | 149.57 | 64.19 | 85.38 | 166.76 | 60.69 | 0.00 | 0.00 | 0.00 |
May | 139.35 | 42.48 | 96.87 | 159.11 | 47.80 | 0.00 | 0.00 | 0.00 |
June | 126.08 | 33.74 | 92.34 | 147.35 | 34.87 | 0.00 | 0.00 | 0.00 |
July | 136.98 | 49.74 | 87.24 | 176.11 | 29.33 | 0.00 | 0.00 | 0.00 |
August | 146.03 | 67.10 | 78.93 | 192.48 | 27.72 | 0.00 | 0.00 | 0.00 |
September | 161.97 | 88.59 | 73.38 | 200.85 | 43.08 | 0.00 | 0.00 | 0.00 |
October | 146.51 | 89.70 | 56.81 | 165.91 | 62.23 | 0.00 | 0.00 | 0.00 |
November | 87.68 | 50.19 | 37.49 | 85.15 | 80.10 | 0.00 | 0.00 | 0.00 |
December | 91.77 | 59.35 | 32.42 | 90.19 | 101.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.91 | 62.73 | 66.17 | 145.58 | 62.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.71 | 33.74 | 32.42 | 77.87 | 27.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 161.97 | 89.70 | 96.87 | 200.85 | 102.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.55 | 0.00 | 19.55 | 1.04 | 113.24 | 0.00 | 0.00 | 0.00 |
February | 30.42 | 0.00 | 30.42 | 7.22 | 97.84 | 0.00 | 0.00 | 0.00 |
March | 44.83 | 0.00 | 44.83 | 21.23 | 76.98 | 0.00 | 0.00 | 0.00 |
April | 63.66 | 0.39 | 63.27 | 43.71 | 59.01 | 0.00 | 0.00 | 0.00 |
May | 81.67 | 2.45 | 79.22 | 70.35 | 44.84 | 0.00 | 0.00 | 0.00 |
June | 85.95 | 5.75 | 80.20 | 81.57 | 32.00 | 0.00 | 0.00 | 0.00 |
July | 81.81 | 6.59 | 75.22 | 88.06 | 26.80 | 0.00 | 0.00 | 0.00 |
August | 66.31 | 1.99 | 64.32 | 72.78 | 25.60 | 0.00 | 0.00 | 0.00 |
September | 51.33 | 0.04 | 51.29 | 43.66 | 42.88 | 0.00 | 0.00 | 0.00 |
October | 35.14 | 0.00 | 35.14 | 18.73 | 64.29 | 0.00 | 0.00 | 0.00 |
November | 22.14 | 0.00 | 22.14 | 4.46 | 85.67 | 0.00 | 0.00 | 0.00 |
December | 16.61 | 0.00 | 16.61 | 0.59 | 110.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.05 | 1.44 | 48.60 | 37.97 | 64.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.61 | 0.00 | 16.61 | 0.59 | 25.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.95 | 6.59 | 80.20 | 88.06 | 113.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 58.42 | 14.64 | 43.78 | 21.46 | 200.65 | 0.00 | 0.00 | 0.00 |
February | 107.62 | 38.12 | 69.50 | 72.21 | 170.89 | 0.00 | 0.00 | 0.00 |
March | 161.29 | 58.49 | 102.80 | 138.75 | 135.34 | 0.00 | 0.00 | 0.00 |
April | 249.11 | 103.37 | 145.74 | 255.63 | 105.36 | 0.00 | 0.00 | 0.00 |
May | 265.24 | 92.35 | 172.89 | 287.20 | 84.47 | 0.00 | 0.00 | 0.00 |
June | 317.46 | 138.17 | 179.29 | 368.22 | 60.85 | 0.00 | 0.00 | 0.00 |
July | 296.07 | 133.11 | 162.96 | 360.49 | 49.82 | 0.00 | 0.00 | 0.00 |
August | 290.63 | 145.38 | 145.25 | 364.26 | 47.72 | 0.00 | 0.00 | 0.00 |
September | 215.23 | 99.44 | 115.79 | 244.30 | 76.71 | 0.00 | 0.00 | 0.00 |
October | 140.73 | 60.13 | 80.60 | 133.79 | 114.80 | 0.00 | 0.00 | 0.00 |
November | 68.87 | 19.50 | 49.37 | 39.73 | 153.14 | 0.00 | 0.00 | 0.00 |
December | 56.34 | 18.11 | 38.23 | 27.10 | 196.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 185.93 | 76.91 | 109.02 | 193.38 | 116.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.34 | 14.64 | 38.23 | 21.46 | 47.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 317.46 | 145.38 | 179.29 | 368.22 | 200.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.76 | 0.00 | 24.76 | 0.71 | 156.98 | 0.00 | 0.00 | 0.00 |
February | 38.53 | 0.00 | 38.53 | 7.68 | 134.21 | 0.00 | 0.00 | 0.00 |
March | 56.77 | 0.00 | 56.77 | 25.99 | 104.79 | 0.00 | 0.00 | 0.00 |
April | 80.62 | 0.50 | 80.12 | 56.58 | 80.61 | 0.00 | 0.00 | 0.00 |
May | 103.43 | 3.11 | 100.32 | 89.72 | 63.74 | 0.00 | 0.00 | 0.00 |
June | 108.85 | 7.28 | 101.57 | 104.78 | 46.66 | 0.00 | 0.00 | 0.00 |
July | 103.60 | 8.34 | 95.26 | 111.27 | 41.11 | 0.00 | 0.00 | 0.00 |
August | 83.98 | 2.52 | 81.46 | 91.45 | 40.52 | 0.00 | 0.00 | 0.00 |
September | 65.00 | 0.05 | 64.95 | 54.37 | 63.22 | 0.00 | 0.00 | 0.00 |
October | 44.51 | 0.00 | 44.51 | 22.34 | 90.17 | 0.00 | 0.00 | 0.00 |
November | 28.03 | 0.00 | 28.03 | 4.63 | 118.81 | 0.00 | 0.00 | 0.00 |
December | 21.04 | 0.00 | 21.04 | 0.34 | 153.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.38 | 1.83 | 61.55 | 47.73 | 90.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.04 | 0.00 | 21.04 | 0.34 | 40.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.85 | 8.34 | 101.57 | 111.27 | 156.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.13 | 0.00 | 9.13 | 0.26 | 57.87 | 0.00 | 0.00 | 0.00 |
February | 14.20 | 0.00 | 14.20 | 2.83 | 49.47 | 0.00 | 0.00 | 0.00 |
March | 20.93 | 0.00 | 20.93 | 9.58 | 38.63 | 0.00 | 0.00 | 0.00 |
April | 29.72 | 0.18 | 29.54 | 20.86 | 29.72 | 0.00 | 0.00 | 0.00 |
May | 38.13 | 1.14 | 36.98 | 33.07 | 23.50 | 0.00 | 0.00 | 0.00 |
June | 40.13 | 2.68 | 37.44 | 38.63 | 17.20 | 0.00 | 0.00 | 0.00 |
July | 38.19 | 3.07 | 35.12 | 41.02 | 15.15 | 0.00 | 0.00 | 0.00 |
August | 30.96 | 0.93 | 30.03 | 33.71 | 14.94 | 0.00 | 0.00 | 0.00 |
September | 23.96 | 0.02 | 23.94 | 20.04 | 23.31 | 0.00 | 0.00 | 0.00 |
October | 16.41 | 0.00 | 16.41 | 8.23 | 33.24 | 0.00 | 0.00 | 0.00 |
November | 10.33 | 0.00 | 10.33 | 1.71 | 43.80 | 0.00 | 0.00 | 0.00 |
December | 7.76 | 0.00 | 7.76 | 0.12 | 56.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.37 | 0.67 | 22.69 | 17.60 | 33.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 7.76 | 0.00 | 7.76 | 0.12 | 14.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.13 | 3.07 | 37.44 | 41.02 | 57.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.46 | 24.07 | 16.39 | 35.57 | 51.01 | 0.00 | 0.00 | 0.00 |
February | 62.26 | 38.63 | 23.63 | 62.92 | 44.24 | 0.00 | 0.00 | 0.00 |
March | 66.04 | 34.92 | 31.13 | 70.56 | 36.84 | 0.00 | 0.00 | 0.00 |
April | 69.79 | 29.95 | 39.84 | 79.13 | 30.18 | 0.00 | 0.00 | 0.00 |
May | 65.02 | 19.82 | 45.20 | 75.04 | 24.83 | 0.00 | 0.00 | 0.00 |
June | 58.83 | 15.74 | 43.08 | 69.76 | 18.68 | 0.00 | 0.00 | 0.00 |
July | 63.91 | 23.21 | 40.71 | 82.66 | 16.51 | 0.00 | 0.00 | 0.00 |
August | 68.14 | 31.31 | 36.83 | 90.16 | 15.94 | 0.00 | 0.00 | 0.00 |
September | 75.57 | 41.33 | 34.24 | 94.07 | 23.00 | 0.00 | 0.00 | 0.00 |
October | 68.36 | 41.85 | 26.51 | 77.89 | 31.46 | 0.00 | 0.00 | 0.00 |
November | 40.91 | 23.42 | 17.49 | 39.45 | 40.07 | 0.00 | 0.00 | 0.00 |
December | 42.82 | 27.69 | 15.13 | 41.74 | 50.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.15 | 29.27 | 30.88 | 68.26 | 31.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 40.46 | 15.74 | 15.13 | 35.57 | 15.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.57 | 41.85 | 45.20 | 94.07 | 51.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.81 | 65.32 | 44.49 | 96.54 | 138.45 | 0.00 | 0.00 | 0.00 |
February | 168.98 | 104.85 | 64.14 | 170.77 | 120.07 | 0.00 | 0.00 | 0.00 |
March | 179.26 | 94.77 | 84.48 | 191.50 | 99.99 | 0.00 | 0.00 | 0.00 |
April | 189.42 | 81.29 | 108.12 | 214.78 | 81.93 | 0.00 | 0.00 | 0.00 |
May | 176.48 | 53.80 | 122.68 | 203.67 | 67.40 | 0.00 | 0.00 | 0.00 |
June | 159.67 | 42.73 | 116.94 | 189.35 | 50.69 | 0.00 | 0.00 | 0.00 |
July | 173.48 | 62.99 | 110.49 | 224.36 | 44.80 | 0.00 | 0.00 | 0.00 |
August | 184.94 | 84.98 | 99.96 | 244.72 | 43.26 | 0.00 | 0.00 | 0.00 |
September | 205.12 | 112.19 | 92.93 | 255.33 | 62.43 | 0.00 | 0.00 | 0.00 |
October | 185.55 | 113.60 | 71.95 | 211.40 | 85.38 | 0.00 | 0.00 | 0.00 |
November | 111.05 | 63.56 | 47.48 | 107.08 | 108.76 | 0.00 | 0.00 | 0.00 |
December | 116.22 | 75.16 | 41.06 | 113.30 | 138.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.25 | 79.45 | 83.80 | 185.28 | 86.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.81 | 42.73 | 41.06 | 96.54 | 43.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 205.12 | 113.60 | 122.68 | 255.33 | 138.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.71 | 51.58 | 35.13 | 77.96 | 101.61 | 0.00 | 0.00 | 0.00 |
February | 133.43 | 82.79 | 50.64 | 135.07 | 89.32 | 0.00 | 0.00 | 0.00 |
March | 141.54 | 74.84 | 66.71 | 150.07 | 74.26 | 0.00 | 0.00 | 0.00 |
April | 149.57 | 64.19 | 85.38 | 166.98 | 60.60 | 0.00 | 0.00 | 0.00 |
May | 139.35 | 42.48 | 96.87 | 157.97 | 48.13 | 0.00 | 0.00 | 0.00 |
June | 126.08 | 33.74 | 92.34 | 147.24 | 34.86 | 0.00 | 0.00 | 0.00 |
July | 136.98 | 49.74 | 87.24 | 174.61 | 29.86 | 0.00 | 0.00 | 0.00 |
August | 146.03 | 67.10 | 78.93 | 191.94 | 27.67 | 0.00 | 0.00 | 0.00 |
September | 161.97 | 88.59 | 73.38 | 200.29 | 43.19 | 0.00 | 0.00 | 0.00 |
October | 146.51 | 89.70 | 56.81 | 165.99 | 61.67 | 0.00 | 0.00 | 0.00 |
November | 87.68 | 50.19 | 37.49 | 85.32 | 79.40 | 0.00 | 0.00 | 0.00 |
December | 91.77 | 59.35 | 32.42 | 90.29 | 101.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.91 | 62.73 | 66.17 | 145.34 | 62.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.71 | 33.74 | 32.42 | 77.96 | 27.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 161.97 | 89.70 | 96.87 | 200.29 | 101.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.25 | 18.52 | 43.73 | 27.58 | 203.80 | 0.00 | 0.00 | 0.00 |
February | 111.04 | 41.69 | 69.36 | 77.37 | 176.72 | 0.00 | 0.00 | 0.00 |
March | 155.56 | 52.59 | 102.96 | 131.42 | 140.91 | 0.00 | 0.00 | 0.00 |
April | 236.38 | 90.26 | 146.12 | 238.28 | 110.29 | 0.00 | 0.00 | 0.00 |
May | 304.75 | 124.07 | 180.68 | 336.25 | 87.07 | 0.00 | 0.00 | 0.00 |
June | 292.45 | 113.33 | 179.11 | 332.01 | 63.01 | 0.00 | 0.00 | 0.00 |
July | 361.52 | 189.97 | 171.55 | 445.21 | 54.09 | 0.00 | 0.00 | 0.00 |
August | 299.20 | 152.61 | 146.59 | 374.06 | 50.81 | 0.00 | 0.00 | 0.00 |
September | 244.45 | 117.59 | 126.86 | 283.13 | 80.35 | 0.00 | 0.00 | 0.00 |
October | 139.79 | 57.47 | 82.32 | 130.42 | 118.29 | 0.00 | 0.00 | 0.00 |
November | 69.23 | 19.68 | 49.55 | 40.91 | 156.05 | 0.00 | 0.00 | 0.00 |
December | 58.44 | 20.29 | 38.15 | 31.90 | 201.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 195.10 | 83.49 | 111.61 | 204.87 | 119.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 58.44 | 18.52 | 38.15 | 27.58 | 50.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.52 | 189.97 | 180.68 | 445.21 | 203.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.55 | 0.00 | 19.55 | 1.15 | 112.22 | 0.00 | 0.00 | 0.00 |
February | 30.42 | 0.00 | 30.42 | 7.56 | 97.12 | 0.00 | 0.00 | 0.00 |
March | 44.83 | 0.00 | 44.83 | 22.22 | 76.22 | 0.00 | 0.00 | 0.00 |
April | 63.66 | 0.39 | 63.27 | 44.89 | 58.41 | 0.00 | 0.00 | 0.00 |
May | 81.67 | 2.45 | 79.22 | 70.04 | 44.96 | 0.00 | 0.00 | 0.00 |
June | 85.95 | 5.75 | 80.20 | 82.31 | 31.87 | 0.00 | 0.00 | 0.00 |
July | 81.81 | 6.59 | 75.22 | 87.25 | 27.18 | 0.00 | 0.00 | 0.00 |
August | 66.31 | 1.99 | 64.32 | 73.34 | 25.49 | 0.00 | 0.00 | 0.00 |
September | 51.33 | 0.04 | 51.29 | 43.95 | 42.75 | 0.00 | 0.00 | 0.00 |
October | 35.14 | 0.00 | 35.14 | 19.81 | 63.30 | 0.00 | 0.00 | 0.00 |
November | 22.14 | 0.00 | 22.14 | 4.84 | 84.62 | 0.00 | 0.00 | 0.00 |
December | 16.61 | 0.00 | 16.61 | 0.76 | 109.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.05 | 1.44 | 48.60 | 38.36 | 64.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.61 | 0.00 | 16.61 | 0.76 | 25.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.95 | 6.59 | 80.20 | 87.25 | 112.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.25 | 18.52 | 43.73 | 29.20 | 202.15 | 0.00 | 0.00 | 0.00 |
February | 111.04 | 41.69 | 69.36 | 81.15 | 174.10 | 0.00 | 0.00 | 0.00 |
March | 155.56 | 52.59 | 102.96 | 136.20 | 138.54 | 0.00 | 0.00 | 0.00 |
April | 236.38 | 90.26 | 146.12 | 242.78 | 108.74 | 0.00 | 0.00 | 0.00 |
May | 304.75 | 124.07 | 180.68 | 338.99 | 86.30 | 0.00 | 0.00 | 0.00 |
June | 292.45 | 113.33 | 179.11 | 334.05 | 62.49 | 0.00 | 0.00 | 0.00 |
July | 361.52 | 189.97 | 171.55 | 447.38 | 53.53 | 0.00 | 0.00 | 0.00 |
August | 299.20 | 152.61 | 146.59 | 376.97 | 49.99 | 0.00 | 0.00 | 0.00 |
September | 244.45 | 117.59 | 126.86 | 287.10 | 78.70 | 0.00 | 0.00 | 0.00 |
October | 139.79 | 57.47 | 82.32 | 135.40 | 115.69 | 0.00 | 0.00 | 0.00 |
November | 69.23 | 19.68 | 49.55 | 43.15 | 154.18 | 0.00 | 0.00 | 0.00 |
December | 58.44 | 20.29 | 38.15 | 34.09 | 199.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 195.10 | 83.49 | 111.61 | 208.03 | 118.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 58.44 | 18.52 | 38.15 | 29.20 | 49.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.52 | 189.97 | 180.68 | 447.38 | 202.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.17 | 75.65 | 51.52 | 109.81 | 155.04 | 0.00 | 0.00 | 0.00 |
February | 195.69 | 121.42 | 74.28 | 192.51 | 136.47 | 0.00 | 0.00 | 0.00 |
March | 207.59 | 109.75 | 97.84 | 215.56 | 113.04 | 0.00 | 0.00 | 0.00 |
April | 219.35 | 94.14 | 125.21 | 242.13 | 90.55 | 0.00 | 0.00 | 0.00 |
May | 204.37 | 62.31 | 142.06 | 231.77 | 70.47 | 0.00 | 0.00 | 0.00 |
June | 184.91 | 49.49 | 135.42 | 216.74 | 50.68 | 0.00 | 0.00 | 0.00 |
July | 200.90 | 72.94 | 127.95 | 258.24 | 42.48 | 0.00 | 0.00 | 0.00 |
August | 214.17 | 98.41 | 115.76 | 282.45 | 39.76 | 0.00 | 0.00 | 0.00 |
September | 237.54 | 129.92 | 107.62 | 292.52 | 63.67 | 0.00 | 0.00 | 0.00 |
October | 214.88 | 131.56 | 83.32 | 239.15 | 94.19 | 0.00 | 0.00 | 0.00 |
November | 128.60 | 73.61 | 54.99 | 121.19 | 121.99 | 0.00 | 0.00 | 0.00 |
December | 134.59 | 87.04 | 47.55 | 128.23 | 154.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 189.05 | 92.00 | 97.05 | 210.93 | 94.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.17 | 49.49 | 47.55 | 109.81 | 39.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.54 | 131.56 | 142.06 | 292.52 | 155.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.86 | 0.00 | 136.86 | 1.34 | 1000.22 | 0.00 | 0.00 | 0.00 |
February | 212.96 | 0.00 | 212.96 | 26.44 | 862.52 | 0.00 | 0.00 | 0.00 |
March | 313.79 | 0.00 | 313.79 | 109.65 | 679.15 | 0.00 | 0.00 | 0.00 |
April | 445.58 | 2.74 | 442.84 | 264.77 | 515.57 | 0.00 | 0.00 | 0.00 |
May | 571.66 | 17.16 | 554.50 | 443.48 | 394.50 | 0.00 | 0.00 | 0.00 |
June | 601.63 | 40.25 | 561.38 | 524.55 | 289.60 | 0.00 | 0.00 | 0.00 |
July | 572.63 | 46.10 | 526.53 | 572.51 | 250.66 | 0.00 | 0.00 | 0.00 |
August | 464.18 | 13.94 | 450.24 | 472.83 | 244.90 | 0.00 | 0.00 | 0.00 |
September | 359.27 | 0.27 | 359.00 | 270.55 | 385.23 | 0.00 | 0.00 | 0.00 |
October | 245.99 | 0.00 | 245.99 | 95.87 | 582.96 | 0.00 | 0.00 | 0.00 |
November | 154.95 | 0.00 | 154.95 | 14.12 | 782.42 | 0.00 | 0.00 | 0.00 |
December | 116.30 | 0.00 | 116.30 | 0.41 | 978.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 350.33 | 10.11 | 340.21 | 234.35 | 579.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.30 | 0.00 | 116.30 | 0.41 | 244.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 601.63 | 46.10 | 561.38 | 572.51 | 1000.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.86 | 0.00 | 136.86 | 0.83 | 1032.51 | 0.00 | 0.00 | 0.00 |
February | 212.96 | 0.00 | 212.96 | 23.13 | 890.46 | 0.00 | 0.00 | 0.00 |
March | 313.79 | 0.00 | 313.79 | 101.24 | 698.36 | 0.00 | 0.00 | 0.00 |
April | 445.58 | 2.74 | 442.84 | 254.06 | 528.92 | 0.00 | 0.00 | 0.00 |
May | 571.66 | 17.16 | 554.50 | 432.69 | 403.67 | 0.00 | 0.00 | 0.00 |
June | 601.63 | 40.25 | 561.38 | 513.77 | 296.63 | 0.00 | 0.00 | 0.00 |
July | 572.63 | 46.10 | 526.53 | 563.42 | 256.98 | 0.00 | 0.00 | 0.00 |
August | 464.18 | 13.94 | 450.24 | 464.01 | 251.86 | 0.00 | 0.00 | 0.00 |
September | 359.27 | 0.27 | 359.00 | 262.34 | 395.54 | 0.00 | 0.00 | 0.00 |
October | 245.99 | 0.00 | 245.99 | 88.41 | 601.34 | 0.00 | 0.00 | 0.00 |
November | 154.95 | 0.00 | 154.95 | 11.87 | 810.36 | 0.00 | 0.00 | 0.00 |
December | 116.30 | 0.00 | 116.30 | 0.25 | 1010.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 350.33 | 10.11 | 340.21 | 227.63 | 596.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.30 | 0.00 | 116.30 | 0.25 | 251.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 601.63 | 46.10 | 561.38 | 563.42 | 1032.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.55 | 0.00 | 19.55 | 1.30 | 121.09 | 0.00 | 0.00 | 0.00 |
February | 30.42 | 0.00 | 30.42 | 8.71 | 105.36 | 0.00 | 0.00 | 0.00 |
March | 44.83 | 0.00 | 44.83 | 25.55 | 83.93 | 0.00 | 0.00 | 0.00 |
April | 63.66 | 0.39 | 63.27 | 53.68 | 65.68 | 0.00 | 0.00 | 0.00 |
May | 81.67 | 2.45 | 79.22 | 84.73 | 51.62 | 0.00 | 0.00 | 0.00 |
June | 85.95 | 5.75 | 80.20 | 99.15 | 39.33 | 0.00 | 0.00 | 0.00 |
July | 81.81 | 6.59 | 75.22 | 107.08 | 33.84 | 0.00 | 0.00 | 0.00 |
August | 66.31 | 1.99 | 64.32 | 91.47 | 32.48 | 0.00 | 0.00 | 0.00 |
September | 51.33 | 0.04 | 51.29 | 57.60 | 46.52 | 0.00 | 0.00 | 0.00 |
October | 35.14 | 0.00 | 35.14 | 24.03 | 70.41 | 0.00 | 0.00 | 0.00 |
November | 22.14 | 0.00 | 22.14 | 6.39 | 92.61 | 0.00 | 0.00 | 0.00 |
December | 16.61 | 0.00 | 16.61 | 1.04 | 118.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.05 | 1.44 | 48.60 | 46.96 | 71.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.61 | 0.00 | 16.61 | 1.04 | 32.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.95 | 6.59 | 80.20 | 107.08 | 121.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.83 | 29.28 | 87.55 | 46.08 | 435.10 | 0.00 | 0.00 | 0.00 |
February | 215.22 | 76.23 | 138.99 | 152.83 | 373.28 | 0.00 | 0.00 | 0.00 |
March | 322.56 | 116.96 | 205.59 | 296.89 | 299.91 | 0.00 | 0.00 | 0.00 |
April | 498.18 | 206.73 | 291.45 | 552.54 | 238.18 | 0.00 | 0.00 | 0.00 |
May | 530.45 | 184.69 | 345.75 | 628.85 | 194.08 | 0.00 | 0.00 | 0.00 |
June | 634.88 | 276.32 | 358.55 | 802.05 | 148.48 | 0.00 | 0.00 | 0.00 |
July | 592.09 | 266.20 | 325.89 | 791.82 | 125.62 | 0.00 | 0.00 | 0.00 |
August | 581.22 | 290.74 | 290.48 | 799.24 | 121.43 | 0.00 | 0.00 | 0.00 |
September | 430.43 | 198.86 | 231.56 | 544.26 | 170.24 | 0.00 | 0.00 | 0.00 |
October | 281.45 | 120.26 | 161.19 | 291.43 | 255.76 | 0.00 | 0.00 | 0.00 |
November | 137.73 | 39.00 | 98.73 | 88.68 | 337.10 | 0.00 | 0.00 | 0.00 |
December | 112.67 | 36.21 | 76.46 | 58.84 | 427.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 371.83 | 153.80 | 218.03 | 422.50 | 260.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 112.67 | 29.28 | 76.46 | 46.08 | 121.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 634.88 | 290.74 | 358.55 | 802.05 | 435.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.71 | 51.58 | 35.13 | 79.88 | 110.11 | 0.00 | 0.00 | 0.00 |
February | 133.43 | 82.79 | 50.64 | 140.24 | 96.55 | 0.00 | 0.00 | 0.00 |
March | 141.54 | 74.84 | 66.71 | 158.13 | 81.24 | 0.00 | 0.00 | 0.00 |
April | 149.57 | 64.19 | 85.38 | 179.38 | 67.17 | 0.00 | 0.00 | 0.00 |
May | 139.35 | 42.48 | 96.87 | 174.45 | 53.93 | 0.00 | 0.00 | 0.00 |
June | 126.08 | 33.74 | 92.34 | 165.33 | 41.82 | 0.00 | 0.00 | 0.00 |
July | 136.98 | 49.74 | 87.24 | 195.65 | 35.70 | 0.00 | 0.00 | 0.00 |
August | 146.03 | 67.10 | 78.93 | 212.26 | 33.84 | 0.00 | 0.00 | 0.00 |
September | 161.97 | 88.59 | 73.38 | 217.76 | 46.23 | 0.00 | 0.00 | 0.00 |
October | 146.51 | 89.70 | 56.81 | 175.57 | 68.39 | 0.00 | 0.00 | 0.00 |
November | 87.68 | 50.19 | 37.49 | 89.20 | 87.24 | 0.00 | 0.00 | 0.00 |
December | 91.77 | 59.35 | 32.42 | 93.28 | 109.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.91 | 62.73 | 66.17 | 156.83 | 69.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.71 | 33.74 | 32.42 | 79.88 | 33.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 161.97 | 89.70 | 96.87 | 217.76 | 110.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.76 | 0.00 | 24.76 | 0.57 | 160.64 | 0.00 | 0.00 | 0.00 |
February | 38.53 | 0.00 | 38.53 | 6.69 | 137.79 | 0.00 | 0.00 | 0.00 |
March | 56.77 | 0.00 | 56.77 | 23.76 | 107.07 | 0.00 | 0.00 | 0.00 |
April | 80.62 | 0.50 | 80.12 | 53.38 | 82.08 | 0.00 | 0.00 | 0.00 |
May | 103.43 | 3.11 | 100.32 | 85.96 | 64.61 | 0.00 | 0.00 | 0.00 |
June | 108.85 | 7.28 | 101.57 | 100.16 | 47.99 | 0.00 | 0.00 | 0.00 |
July | 103.60 | 8.34 | 95.26 | 106.54 | 42.50 | 0.00 | 0.00 | 0.00 |
August | 83.98 | 2.52 | 81.46 | 87.94 | 41.45 | 0.00 | 0.00 | 0.00 |
September | 65.00 | 0.05 | 64.95 | 51.67 | 63.79 | 0.00 | 0.00 | 0.00 |
October | 44.51 | 0.00 | 44.51 | 20.59 | 91.36 | 0.00 | 0.00 | 0.00 |
November | 28.03 | 0.00 | 28.03 | 3.93 | 122.27 | 0.00 | 0.00 | 0.00 |
December | 21.04 | 0.00 | 21.04 | 0.23 | 156.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.38 | 1.83 | 61.55 | 45.36 | 92.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.04 | 0.00 | 21.04 | 0.23 | 41.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.85 | 8.34 | 101.57 | 106.54 | 160.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.15 | 0.00 | 22.15 | 0.51 | 143.72 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 0.00 | 34.47 | 5.98 | 123.28 | 0.00 | 0.00 | 0.00 |
March | 50.79 | 0.00 | 50.79 | 21.26 | 95.80 | 0.00 | 0.00 | 0.00 |
April | 72.13 | 0.44 | 71.69 | 47.76 | 73.44 | 0.00 | 0.00 | 0.00 |
May | 92.54 | 2.78 | 89.76 | 76.91 | 57.81 | 0.00 | 0.00 | 0.00 |
June | 97.39 | 6.52 | 90.87 | 89.62 | 42.94 | 0.00 | 0.00 | 0.00 |
July | 92.70 | 7.46 | 85.23 | 95.32 | 38.02 | 0.00 | 0.00 | 0.00 |
August | 75.14 | 2.26 | 72.88 | 78.68 | 37.09 | 0.00 | 0.00 | 0.00 |
September | 58.16 | 0.04 | 58.11 | 46.23 | 57.08 | 0.00 | 0.00 | 0.00 |
October | 39.82 | 0.00 | 39.82 | 18.42 | 81.74 | 0.00 | 0.00 | 0.00 |
November | 25.08 | 0.00 | 25.08 | 3.52 | 109.39 | 0.00 | 0.00 | 0.00 |
December | 18.83 | 0.00 | 18.83 | 0.20 | 140.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.71 | 1.64 | 55.07 | 40.58 | 83.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.83 | 0.00 | 18.83 | 0.20 | 37.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.39 | 7.46 | 90.87 | 95.32 | 143.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 323.71 | 192.57 | 131.14 | 279.68 | 417.99 | 0.00 | 0.00 | 0.00 |
February | 498.14 | 309.07 | 189.07 | 494.83 | 362.26 | 0.00 | 0.00 | 0.00 |
March | 528.43 | 279.38 | 249.05 | 554.50 | 301.73 | 0.00 | 0.00 | 0.00 |
April | 558.37 | 239.64 | 318.74 | 620.54 | 246.97 | 0.00 | 0.00 | 0.00 |
May | 520.24 | 158.60 | 361.63 | 587.10 | 202.34 | 0.00 | 0.00 | 0.00 |
June | 470.70 | 125.98 | 344.72 | 542.86 | 154.54 | 0.00 | 0.00 | 0.00 |
July | 511.39 | 185.68 | 325.71 | 645.52 | 137.25 | 0.00 | 0.00 | 0.00 |
August | 545.19 | 250.51 | 294.68 | 708.59 | 130.99 | 0.00 | 0.00 | 0.00 |
September | 604.68 | 330.72 | 273.96 | 742.66 | 186.22 | 0.00 | 0.00 | 0.00 |
October | 546.98 | 334.88 | 212.10 | 614.27 | 255.66 | 0.00 | 0.00 | 0.00 |
November | 327.35 | 187.38 | 139.97 | 309.64 | 330.12 | 0.00 | 0.00 | 0.00 |
December | 342.61 | 221.56 | 121.05 | 329.29 | 416.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 481.25 | 234.20 | 247.05 | 535.93 | 261.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 323.71 | 125.98 | 121.05 | 279.68 | 130.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 604.68 | 334.88 | 361.63 | 742.66 | 417.99 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117461E+10 | 0.698752E+09 | 0.475859E+09 | 0.103531E+10 | 0.137583E+10 |
February | 0.163263E+10 | 0.101296E+10 | 0.619672E+09 | 0.163551E+10 | 0.109329E+10 |
March | 0.191745E+10 | 0.101376E+10 | 0.903689E+09 | 0.202315E+10 | 0.100594E+10 |
April | 0.196075E+10 | 0.841503E+09 | 0.111925E+10 | 0.220628E+10 | 0.783345E+09 |
May | 0.188772E+10 | 0.575512E+09 | 0.131221E+10 | 0.217907E+10 | 0.643170E+09 |
June | 0.165286E+10 | 0.442373E+09 | 0.121049E+10 | 0.197142E+10 | 0.459488E+09 |
July | 0.185562E+10 | 0.673775E+09 | 0.118184E+10 | 0.239484E+10 | 0.420782E+09 |
August | 0.197825E+10 | 0.908995E+09 | 0.106925E+10 | 0.260659E+10 | 0.407567E+09 |
September | 0.212334E+10 | 0.116132E+10 | 0.962015E+09 | 0.261469E+10 | 0.587313E+09 |
October | 0.198477E+10 | 0.121515E+10 | 0.769624E+09 | 0.223666E+10 | 0.853468E+09 |
November | 0.114951E+10 | 0.657987E+09 | 0.491521E+09 | 0.109962E+10 | 0.105455E+10 |
December | 0.124317E+10 | 0.803942E+09 | 0.439232E+09 | 0.120097E+10 | 0.138314E+10 |
Annual Sum or Average | 0.205607E+11 | 0.100060E+11 | 0.105547E+11 | 0.232041E+11 | 0.100679E+11 |
Minimum of Months | 0.114951E+10 | 0.442373E+09 | 0.439232E+09 | 0.103531E+10 | 0.407567E+09 |
Maximum of Months | 0.212334E+10 | 0.121515E+10 | 0.131221E+10 | 0.261469E+10 | 0.138314E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.330763E+10 | 0.196764E+10 | 0.133999E+10 | 0.287309E+10 | 0.399346E+10 |
February | 0.459739E+10 | 0.285244E+10 | 0.174495E+10 | 0.454715E+10 | 0.320347E+10 |
March | 0.539941E+10 | 0.285469E+10 | 0.254473E+10 | 0.562388E+10 | 0.300993E+10 |
April | 0.552134E+10 | 0.236962E+10 | 0.315172E+10 | 0.612279E+10 | 0.237704E+10 |
May | 0.531570E+10 | 0.162060E+10 | 0.369510E+10 | 0.603405E+10 | 0.197901E+10 |
June | 0.465435E+10 | 0.124569E+10 | 0.340866E+10 | 0.543610E+10 | 0.145539E+10 |
July | 0.522529E+10 | 0.189731E+10 | 0.332799E+10 | 0.663689E+10 | 0.133983E+10 |
August | 0.557061E+10 | 0.255967E+10 | 0.301095E+10 | 0.724252E+10 | 0.130775E+10 |
September | 0.597918E+10 | 0.327021E+10 | 0.270897E+10 | 0.728124E+10 | 0.182462E+10 |
October | 0.558898E+10 | 0.342177E+10 | 0.216721E+10 | 0.622137E+10 | 0.260192E+10 |
November | 0.323694E+10 | 0.185285E+10 | 0.138409E+10 | 0.304916E+10 | 0.311375E+10 |
December | 0.350069E+10 | 0.226385E+10 | 0.123685E+10 | 0.333944E+10 | 0.402886E+10 |
Annual Sum or Average | 0.578975E+11 | 0.281763E+11 | 0.297212E+11 | 0.644077E+11 | 0.302350E+11 |
Minimum of Months | 0.323694E+10 | 0.124569E+10 | 0.123685E+10 | 0.287309E+10 | 0.130775E+10 |
Maximum of Months | 0.597918E+10 | 0.342177E+10 | 0.369510E+10 | 0.728124E+10 | 0.402886E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.429680E+10 | 0.255608E+10 | 0.174072E+10 | 0.375454E+10 | 0.557344E+10 |
February | 0.597227E+10 | 0.370548E+10 | 0.226679E+10 | 0.596913E+10 | 0.444792E+10 |
March | 0.701415E+10 | 0.370840E+10 | 0.330575E+10 | 0.739163E+10 | 0.420547E+10 |
April | 0.717253E+10 | 0.307827E+10 | 0.409427E+10 | 0.805084E+10 | 0.331971E+10 |
May | 0.690540E+10 | 0.210526E+10 | 0.480014E+10 | 0.791870E+10 | 0.278832E+10 |
June | 0.604627E+10 | 0.161823E+10 | 0.442804E+10 | 0.711635E+10 | 0.206252E+10 |
July | 0.678795E+10 | 0.246471E+10 | 0.432325E+10 | 0.872319E+10 | 0.188029E+10 |
August | 0.723654E+10 | 0.332516E+10 | 0.391139E+10 | 0.952185E+10 | 0.181956E+10 |
September | 0.776730E+10 | 0.424819E+10 | 0.351911E+10 | 0.956819E+10 | 0.254569E+10 |
October | 0.726041E+10 | 0.444508E+10 | 0.281533E+10 | 0.816943E+10 | 0.364785E+10 |
November | 0.420497E+10 | 0.240696E+10 | 0.179801E+10 | 0.397460E+10 | 0.439378E+10 |
December | 0.454760E+10 | 0.294087E+10 | 0.160674E+10 | 0.437221E+10 | 0.562460E+10 |
Annual Sum or Average | 0.752122E+11 | 0.366027E+11 | 0.386095E+11 | 0.845307E+11 | 0.423092E+11 |
Minimum of Months | 0.420497E+10 | 0.161823E+10 | 0.160674E+10 | 0.375454E+10 | 0.181956E+10 |
Maximum of Months | 0.776730E+10 | 0.444508E+10 | 0.480014E+10 | 0.956819E+10 | 0.562460E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232241E+09 | 0.138155E+09 | 94085984.75 | 0.208636E+09 | 0.273922E+09 |
February | 0.322800E+09 | 0.200280E+09 | 0.122520E+09 | 0.327281E+09 | 0.217562E+09 |
March | 0.379114E+09 | 0.200438E+09 | 0.178676E+09 | 0.403317E+09 | 0.200498E+09 |
April | 0.387675E+09 | 0.166380E+09 | 0.221296E+09 | 0.435596E+09 | 0.157929E+09 |
May | 0.373237E+09 | 0.113789E+09 | 0.259449E+09 | 0.426690E+09 | 0.129789E+09 |
June | 0.326802E+09 | 87464675.02 | 0.239337E+09 | 0.385248E+09 | 91196169.23 |
July | 0.366890E+09 | 0.133217E+09 | 0.233673E+09 | 0.471712E+09 | 80775145.47 |
August | 0.391136E+09 | 0.179724E+09 | 0.211412E+09 | 0.517203E+09 | 75432498.34 |
September | 0.419822E+09 | 0.229614E+09 | 0.190208E+09 | 0.521085E+09 | 0.113639E+09 |
October | 0.392424E+09 | 0.240255E+09 | 0.152169E+09 | 0.445889E+09 | 0.167490E+09 |
November | 0.227278E+09 | 0.130095E+09 | 97182520.67 | 0.221049E+09 | 0.207985E+09 |
December | 0.245797E+09 | 0.158953E+09 | 86844037.59 | 0.241672E+09 | 0.272932E+09 |
Annual Sum or Average | 0.406522E+10 | 0.197836E+10 | 0.208685E+10 | 0.460538E+10 | 0.198915E+10 |
Minimum of Months | 0.227278E+09 | 87464675.02 | 86844037.59 | 0.208636E+09 | 75432498.34 |
Maximum of Months | 0.419822E+09 | 0.240255E+09 | 0.259449E+09 | 0.521085E+09 | 0.273922E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.166731E+09 | 49599010.86 | 0.117132E+09 | 73089345.22 | 0.550425E+09 |
February | 0.268637E+09 | 0.100850E+09 | 0.167787E+09 | 0.187275E+09 | 0.431360E+09 |
March | 0.416644E+09 | 0.140864E+09 | 0.275781E+09 | 0.353452E+09 | 0.381314E+09 |
April | 0.612687E+09 | 0.233947E+09 | 0.378739E+09 | 0.622559E+09 | 0.287817E+09 |
May | 0.816233E+09 | 0.332303E+09 | 0.483930E+09 | 0.908215E+09 | 0.235180E+09 |
June | 0.758024E+09 | 0.293758E+09 | 0.464266E+09 | 0.868221E+09 | 0.165176E+09 |
July | 0.968308E+09 | 0.508828E+09 | 0.459480E+09 | 0.120157E+10 | 0.146690E+09 |
August | 0.801373E+09 | 0.408746E+09 | 0.392627E+09 | 0.100807E+10 | 0.138805E+09 |
September | 0.633602E+09 | 0.304787E+09 | 0.328815E+09 | 0.737440E+09 | 0.211857E+09 |
October | 0.374415E+09 | 0.153917E+09 | 0.220498E+09 | 0.350388E+09 | 0.322065E+09 |
November | 0.179442E+09 | 51011659.85 | 0.128430E+09 | 0.105295E+09 | 0.409876E+09 |
December | 0.156513E+09 | 54332932.01 | 0.102180E+09 | 84869690.62 | 0.545439E+09 |
Annual Sum or Average | 0.615261E+10 | 0.263294E+10 | 0.351966E+10 | 0.650044E+10 | 0.382600E+10 |
Minimum of Months | 0.156513E+09 | 49599010.86 | 0.102180E+09 | 73089345.22 | 0.138805E+09 |
Maximum of Months | 0.968308E+09 | 0.508828E+09 | 0.483930E+09 | 0.120157E+10 | 0.550425E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52368466.14 | 0.00 | 52368466.14 | 2875034.45 | 0.303469E+09 |
February | 73600977.77 | 0.00 | 73600977.77 | 17802553.23 | 0.237172E+09 |
March | 0.120069E+09 | 391.48 | 0.120069E+09 | 58841781.79 | 0.206523E+09 |
April | 0.164999E+09 | 1015143.42 | 0.163984E+09 | 0.116669E+09 | 0.152903E+09 |
May | 0.218743E+09 | 6567927.74 | 0.212175E+09 | 0.189263E+09 | 0.121650E+09 |
June | 0.222782E+09 | 14903905.08 | 0.207878E+09 | 0.215417E+09 | 83609515.06 |
July | 0.219114E+09 | 17639237.34 | 0.201475E+09 | 0.235931E+09 | 73757573.56 |
August | 0.177614E+09 | 5334198.86 | 0.172280E+09 | 0.197301E+09 | 69752864.78 |
September | 0.133037E+09 | 99658.47 | 0.132938E+09 | 0.114065E+09 | 0.112943E+09 |
October | 94124964.10 | 0.00 | 94124964.10 | 51822607.15 | 0.172940E+09 |
November | 57376818.73 | 0.00 | 57376818.73 | 11999165.57 | 0.222574E+09 |
December | 44499694.93 | 0.00 | 44499694.93 | 1752338.36 | 0.296040E+09 |
Annual Sum or Average | 0.157833E+10 | 45560462.39 | 0.153277E+10 | 0.121374E+10 | 0.205333E+10 |
Minimum of Months | 44499694.93 | 0.00 | 44499694.93 | 1752338.36 | 69752864.78 |
Maximum of Months | 0.222782E+09 | 17639237.34 | 0.212175E+09 | 0.235931E+09 | 0.303469E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.166731E+09 | 49599010.86 | 0.117132E+09 | 77627707.14 | 0.545544E+09 |
February | 0.268637E+09 | 0.100850E+09 | 0.167787E+09 | 0.195809E+09 | 0.424938E+09 |
March | 0.416644E+09 | 0.140864E+09 | 0.275781E+09 | 0.365134E+09 | 0.375441E+09 |
April | 0.612687E+09 | 0.233947E+09 | 0.378739E+09 | 0.633261E+09 | 0.284227E+09 |
May | 0.816233E+09 | 0.332303E+09 | 0.483930E+09 | 0.915144E+09 | 0.233328E+09 |
June | 0.758024E+09 | 0.293758E+09 | 0.464266E+09 | 0.873428E+09 | 0.163909E+09 |
July | 0.968308E+09 | 0.508828E+09 | 0.459480E+09 | 0.120729E+10 | 0.145249E+09 |
August | 0.801373E+09 | 0.408746E+09 | 0.392627E+09 | 0.101547E+10 | 0.136769E+09 |
September | 0.633602E+09 | 0.304787E+09 | 0.328815E+09 | 0.746953E+09 | 0.208131E+09 |
October | 0.374415E+09 | 0.153917E+09 | 0.220498E+09 | 0.362234E+09 | 0.315918E+09 |
November | 0.179442E+09 | 51011659.85 | 0.128430E+09 | 0.110769E+09 | 0.404988E+09 |
December | 0.156513E+09 | 54332932.01 | 0.102180E+09 | 90341940.19 | 0.539743E+09 |
Annual Sum or Average | 0.615261E+10 | 0.263294E+10 | 0.351966E+10 | 0.659346E+10 | 0.377818E+10 |
Minimum of Months | 0.156513E+09 | 49599010.86 | 0.102180E+09 | 77627707.14 | 0.136769E+09 |
Maximum of Months | 0.968308E+09 | 0.508828E+09 | 0.483930E+09 | 0.120729E+10 | 0.545544E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185756E+09 | 0.110502E+09 | 75253821.84 | 0.167193E+09 | 0.207802E+09 |
February | 0.258189E+09 | 0.160192E+09 | 97996810.64 | 0.259886E+09 | 0.174476E+09 |
March | 0.303231E+09 | 0.160319E+09 | 0.142912E+09 | 0.316258E+09 | 0.174673E+09 |
April | 0.310079E+09 | 0.133077E+09 | 0.177001E+09 | 0.340972E+09 | 0.142549E+09 |
May | 0.298531E+09 | 91012766.08 | 0.207518E+09 | 0.335612E+09 | 0.118704E+09 |
June | 0.261389E+09 | 69957827.29 | 0.191432E+09 | 0.301636E+09 | 86702668.08 |
July | 0.293453E+09 | 0.106552E+09 | 0.186901E+09 | 0.372993E+09 | 77864247.90 |
August | 0.312846E+09 | 0.143750E+09 | 0.169096E+09 | 0.408430E+09 | 74510772.35 |
September | 0.335791E+09 | 0.183654E+09 | 0.152136E+09 | 0.410448E+09 | 0.107283E+09 |
October | 0.313877E+09 | 0.192166E+09 | 0.121711E+09 | 0.348483E+09 | 0.153570E+09 |
November | 0.181786E+09 | 0.104056E+09 | 77730558.02 | 0.174230E+09 | 0.168569E+09 |
December | 0.196599E+09 | 0.127137E+09 | 69461416.07 | 0.192232E+09 | 0.212447E+09 |
Annual Sum or Average | 0.325153E+10 | 0.158238E+10 | 0.166915E+10 | 0.362837E+10 | 0.169915E+10 |
Minimum of Months | 0.181786E+09 | 69957827.29 | 69461416.07 | 0.167193E+09 | 74510772.35 |
Maximum of Months | 0.335791E+09 | 0.192166E+09 | 0.207518E+09 | 0.410448E+09 | 0.212447E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41900326.30 | 0.00 | 41900326.30 | 1555799.76 | 0.256393E+09 |
February | 58888587.20 | 0.00 | 58888587.20 | 12777256.57 | 0.197670E+09 |
March | 96068061.79 | 313.23 | 96067748.57 | 46404376.91 | 0.169845E+09 |
April | 0.132017E+09 | 812222.38 | 0.131204E+09 | 96868844.55 | 0.123006E+09 |
May | 0.175017E+09 | 5255038.69 | 0.169762E+09 | 0.159484E+09 | 95849072.38 |
June | 0.178249E+09 | 11924704.54 | 0.166324E+09 | 0.181314E+09 | 64868075.65 |
July | 0.175314E+09 | 14113260.42 | 0.161201E+09 | 0.201509E+09 | 55244769.76 |
August | 0.142110E+09 | 4267924.75 | 0.137842E+09 | 0.169389E+09 | 51982203.16 |
September | 0.106444E+09 | 79737.34 | 0.106364E+09 | 97742540.14 | 87309432.59 |
October | 75309952.72 | 0.00 | 75309952.72 | 41899247.52 | 0.141372E+09 |
November | 45907539.48 | 0.00 | 45907539.48 | 8279606.33 | 0.187801E+09 |
December | 35604474.90 | 0.00 | 35604474.90 | 890258.19 | 0.250013E+09 |
Annual Sum or Average | 0.126283E+10 | 36453201.35 | 0.122638E+10 | 0.101811E+10 | 0.168135E+10 |
Minimum of Months | 35604474.90 | 0.00 | 35604474.90 | 890258.19 | 51982203.16 |
Maximum of Months | 0.178249E+09 | 14113260.42 | 0.169762E+09 | 0.201509E+09 | 0.256393E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.156474E+09 | 39212816.39 | 0.117262E+09 | 55283314.80 | 0.544362E+09 |
February | 0.260353E+09 | 92217704.15 | 0.168135E+09 | 0.168843E+09 | 0.423010E+09 |
March | 0.431998E+09 | 0.156650E+09 | 0.275348E+09 | 0.360795E+09 | 0.369150E+09 |
April | 0.645692E+09 | 0.267941E+09 | 0.377750E+09 | 0.653172E+09 | 0.276899E+09 |
May | 0.710424E+09 | 0.247357E+09 | 0.463067E+09 | 0.763149E+09 | 0.228222E+09 |
June | 0.822858E+09 | 0.358142E+09 | 0.464716E+09 | 0.950261E+09 | 0.158892E+09 |
July | 0.792984E+09 | 0.356523E+09 | 0.436461E+09 | 0.960333E+09 | 0.134915E+09 |
August | 0.778426E+09 | 0.389384E+09 | 0.389042E+09 | 0.969102E+09 | 0.129780E+09 |
September | 0.557872E+09 | 0.257746E+09 | 0.300126E+09 | 0.624591E+09 | 0.202815E+09 |
October | 0.376944E+09 | 0.161062E+09 | 0.215882E+09 | 0.347396E+09 | 0.314274E+09 |
November | 0.178516E+09 | 50551984.52 | 0.127964E+09 | 99095637.53 | 0.403612E+09 |
December | 0.150900E+09 | 48501623.07 | 0.102398E+09 | 69577649.94 | 0.535297E+09 |
Annual Sum or Average | 0.586344E+10 | 0.242529E+10 | 0.343815E+10 | 0.602160E+10 | 0.372123E+10 |
Minimum of Months | 0.150900E+09 | 39212816.39 | 0.102398E+09 | 55283314.80 | 0.129780E+09 |
Maximum of Months | 0.822858E+09 | 0.389384E+09 | 0.464716E+09 | 0.969102E+09 | 0.544362E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232241E+09 | 0.138155E+09 | 94085984.75 | 0.208560E+09 | 0.273534E+09 |
February | 0.322800E+09 | 0.200280E+09 | 0.122520E+09 | 0.326652E+09 | 0.216962E+09 |
March | 0.379114E+09 | 0.200438E+09 | 0.178676E+09 | 0.401113E+09 | 0.199878E+09 |
April | 0.387675E+09 | 0.166380E+09 | 0.221296E+09 | 0.432248E+09 | 0.157300E+09 |
May | 0.373237E+09 | 0.113789E+09 | 0.259449E+09 | 0.426162E+09 | 0.128018E+09 |
June | 0.326802E+09 | 87464675.02 | 0.239337E+09 | 0.381921E+09 | 90386308.21 |
July | 0.366890E+09 | 0.133217E+09 | 0.233673E+09 | 0.471703E+09 | 78554452.93 |
August | 0.391136E+09 | 0.179724E+09 | 0.211412E+09 | 0.515551E+09 | 74245611.12 |
September | 0.419822E+09 | 0.229614E+09 | 0.190208E+09 | 0.520596E+09 | 0.111658E+09 |
October | 0.392424E+09 | 0.240255E+09 | 0.152169E+09 | 0.444368E+09 | 0.166664E+09 |
November | 0.227278E+09 | 0.130095E+09 | 97182520.67 | 0.220715E+09 | 0.207622E+09 |
December | 0.245797E+09 | 0.158953E+09 | 86844037.59 | 0.241559E+09 | 0.272468E+09 |
Annual Sum or Average | 0.406522E+10 | 0.197836E+10 | 0.208685E+10 | 0.459115E+10 | 0.197729E+10 |
Minimum of Months | 0.227278E+09 | 87464675.02 | 86844037.59 | 0.208560E+09 | 74245611.12 |
Maximum of Months | 0.419822E+09 | 0.240255E+09 | 0.259449E+09 | 0.520596E+09 | 0.273534E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52368466.14 | 0.00 | 52368466.14 | 2782171.88 | 0.303300E+09 |
February | 73600977.77 | 0.00 | 73600977.77 | 17464333.09 | 0.236683E+09 |
March | 0.120069E+09 | 391.48 | 0.120069E+09 | 56868370.71 | 0.206172E+09 |
April | 0.164999E+09 | 1015143.42 | 0.163984E+09 | 0.113304E+09 | 0.152951E+09 |
May | 0.218743E+09 | 6567927.74 | 0.212175E+09 | 0.188429E+09 | 0.120109E+09 |
June | 0.222782E+09 | 14903905.08 | 0.207878E+09 | 0.211441E+09 | 82955734.20 |
July | 0.219114E+09 | 17639237.34 | 0.201475E+09 | 0.235871E+09 | 71768281.60 |
August | 0.177614E+09 | 5334198.86 | 0.172280E+09 | 0.194927E+09 | 68567874.87 |
September | 0.133037E+09 | 99658.47 | 0.132938E+09 | 0.113176E+09 | 0.111139E+09 |
October | 94124964.10 | 0.00 | 94124964.10 | 50166541.52 | 0.172187E+09 |
November | 57376818.73 | 0.00 | 57376818.73 | 11565950.73 | 0.222050E+09 |
December | 44499694.93 | 0.00 | 44499694.93 | 1570125.44 | 0.295611E+09 |
Annual Sum or Average | 0.157833E+10 | 45560462.39 | 0.153277E+10 | 0.119757E+10 | 0.204349E+10 |
Minimum of Months | 44499694.93 | 0.00 | 44499694.93 | 1570125.44 | 68567874.87 |
Maximum of Months | 0.222782E+09 | 17639237.34 | 0.212175E+09 | 0.235871E+09 | 0.303300E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.156474E+09 | 39212816.39 | 0.117262E+09 | 57483302.96 | 0.537409E+09 |
February | 0.260353E+09 | 92217704.15 | 0.168135E+09 | 0.174689E+09 | 0.413418E+09 |
March | 0.431998E+09 | 0.156650E+09 | 0.275348E+09 | 0.371615E+09 | 0.362487E+09 |
April | 0.645692E+09 | 0.267941E+09 | 0.377750E+09 | 0.662599E+09 | 0.273097E+09 |
May | 0.710424E+09 | 0.247357E+09 | 0.463067E+09 | 0.769235E+09 | 0.226242E+09 |
June | 0.822858E+09 | 0.358142E+09 | 0.464716E+09 | 0.954437E+09 | 0.157712E+09 |
July | 0.792984E+09 | 0.356523E+09 | 0.436461E+09 | 0.965527E+09 | 0.133443E+09 |
August | 0.778426E+09 | 0.389384E+09 | 0.389042E+09 | 0.975621E+09 | 0.127815E+09 |
September | 0.557872E+09 | 0.257746E+09 | 0.300126E+09 | 0.633227E+09 | 0.198823E+09 |
October | 0.376944E+09 | 0.161062E+09 | 0.215882E+09 | 0.358334E+09 | 0.307484E+09 |
November | 0.178516E+09 | 50551984.52 | 0.127964E+09 | 0.102985E+09 | 0.396949E+09 |
December | 0.150900E+09 | 48501623.07 | 0.102398E+09 | 72573696.43 | 0.527048E+09 |
Annual Sum or Average | 0.586344E+10 | 0.242529E+10 | 0.343815E+10 | 0.609832E+10 | 0.366193E+10 |
Minimum of Months | 0.150900E+09 | 39212816.39 | 0.102398E+09 | 57483302.96 | 0.127815E+09 |
Maximum of Months | 0.822858E+09 | 0.389384E+09 | 0.464716E+09 | 0.975621E+09 | 0.537409E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66321358.09 | 0.00 | 66321358.09 | 1909299.81 | 0.420466E+09 |
February | 93210994.38 | 0.00 | 93210994.38 | 18580301.54 | 0.324677E+09 |
March | 0.152060E+09 | 495.79 | 0.152060E+09 | 69604519.89 | 0.280676E+09 |
April | 0.208961E+09 | 1285615.09 | 0.207675E+09 | 0.146645E+09 | 0.208946E+09 |
May | 0.277024E+09 | 8317866.07 | 0.268706E+09 | 0.240307E+09 | 0.170731E+09 |
June | 0.282139E+09 | 18874855.40 | 0.263264E+09 | 0.271594E+09 | 0.120939E+09 |
July | 0.277494E+09 | 22338981.12 | 0.255155E+09 | 0.298024E+09 | 0.110107E+09 |
August | 0.224937E+09 | 6755426.29 | 0.218182E+09 | 0.244932E+09 | 0.108540E+09 |
September | 0.168483E+09 | 126211.16 | 0.168357E+09 | 0.140918E+09 | 0.163867E+09 |
October | 0.119203E+09 | 0.00 | 0.119203E+09 | 59824641.38 | 0.241498E+09 |
November | 72664120.65 | 0.00 | 72664120.65 | 12006188.11 | 0.307958E+09 |
December | 56356055.86 | 0.00 | 56356055.86 | 901988.90 | 0.410736E+09 |
Annual Sum or Average | 0.199885E+10 | 57699450.91 | 0.194115E+10 | 0.150525E+10 | 0.286914E+10 |
Minimum of Months | 56356055.86 | 0.00 | 56356055.86 | 901988.90 | 0.108540E+09 |
Maximum of Months | 0.282139E+09 | 22338981.12 | 0.268706E+09 | 0.298024E+09 | 0.420466E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 24448798.74 | 0.00 | 24448798.74 | 703846.97 | 0.155001E+09 |
February | 34361432.09 | 0.00 | 34361432.09 | 6849468.50 | 0.119690E+09 |
March | 56055618.56 | 182.77 | 56055435.79 | 25659108.13 | 0.103469E+09 |
April | 77031535.71 | 473930.95 | 76557604.76 | 54059405.98 | 77026178.68 |
May | 0.102122E+09 | 3066309.85 | 99056130.07 | 88587040.61 | 62938639.97 |
June | 0.104008E+09 | 6958053.25 | 97050039.40 | 0.100121E+09 | 44583228.90 |
July | 0.102296E+09 | 8235073.42 | 94060683.56 | 0.109864E+09 | 40589830.01 |
August | 82921087.56 | 2490329.85 | 80430757.71 | 90291952.41 | 40012359.05 |
September | 62109917.75 | 46526.66 | 62063391.09 | 51948292.58 | 60408161.38 |
October | 43943282.55 | 0.00 | 43943282.55 | 22053839.96 | 89026232.31 |
November | 26787003.65 | 0.00 | 26787003.65 | 4425978.07 | 0.113526E+09 |
December | 20775175.71 | 0.00 | 20775175.71 | 332510.46 | 0.151414E+09 |
Annual Sum or Average | 0.736860E+09 | 21270406.75 | 0.715590E+09 | 0.554896E+09 | 0.105768E+10 |
Minimum of Months | 20775175.71 | 0.00 | 20775175.71 | 332510.46 | 40012359.05 |
Maximum of Months | 0.104008E+09 | 8235073.42 | 99056130.07 | 0.109864E+09 | 0.155001E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108363E+09 | 64462737.30 | 43900141.34 | 95268863.23 | 0.136629E+09 |
February | 0.150617E+09 | 93449879.22 | 57167513.00 | 0.152205E+09 | 0.107017E+09 |
March | 0.176893E+09 | 93523610.87 | 83369497.89 | 0.188976E+09 | 98671897.83 |
April | 0.180888E+09 | 77632025.32 | 0.103256E+09 | 0.205110E+09 | 78237169.37 |
May | 0.174151E+09 | 53093294.10 | 0.121058E+09 | 0.200987E+09 | 66514300.29 |
June | 0.152484E+09 | 40810664.91 | 0.111674E+09 | 0.180825E+09 | 48410577.85 |
July | 0.171189E+09 | 62158441.70 | 0.109031E+09 | 0.221400E+09 | 44211930.65 |
August | 0.182502E+09 | 83858412.51 | 98643882.84 | 0.241493E+09 | 42692090.40 |
September | 0.195887E+09 | 0.107137E+09 | 88750420.26 | 0.243835E+09 | 59618166.87 |
October | 0.183104E+09 | 0.112102E+09 | 71001357.22 | 0.208615E+09 | 84250671.89 |
November | 0.106047E+09 | 60701964.75 | 45344972.53 | 0.102255E+09 | 0.103865E+09 |
December | 0.114688E+09 | 74166869.16 | 40521077.98 | 0.111803E+09 | 0.136358E+09 |
Annual Sum or Average | 0.189681E+10 | 0.923097E+09 | 0.973717E+09 | 0.215277E+10 | 0.100648E+10 |
Minimum of Months | 0.106047E+09 | 40810664.91 | 40521077.98 | 95268863.23 | 42692090.40 |
Maximum of Months | 0.195887E+09 | 0.112102E+09 | 0.121058E+09 | 0.243835E+09 | 0.136629E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294119E+09 | 0.174965E+09 | 0.119154E+09 | 0.258579E+09 | 0.370838E+09 |
February | 0.408806E+09 | 0.253642E+09 | 0.155164E+09 | 0.413116E+09 | 0.290465E+09 |
March | 0.480124E+09 | 0.253842E+09 | 0.226282E+09 | 0.512920E+09 | 0.267816E+09 |
April | 0.490966E+09 | 0.210709E+09 | 0.280257E+09 | 0.556711E+09 | 0.212352E+09 |
May | 0.472682E+09 | 0.144106E+09 | 0.328576E+09 | 0.545519E+09 | 0.180533E+09 |
June | 0.413874E+09 | 0.110768E+09 | 0.303105E+09 | 0.490797E+09 | 0.131396E+09 |
July | 0.464643E+09 | 0.168711E+09 | 0.295932E+09 | 0.600925E+09 | 0.120000E+09 |
August | 0.495349E+09 | 0.227609E+09 | 0.267740E+09 | 0.655463E+09 | 0.115875E+09 |
September | 0.531678E+09 | 0.290791E+09 | 0.240887E+09 | 0.661817E+09 | 0.161816E+09 |
October | 0.496980E+09 | 0.304268E+09 | 0.192712E+09 | 0.566223E+09 | 0.228674E+09 |
November | 0.287833E+09 | 0.164758E+09 | 0.123076E+09 | 0.277540E+09 | 0.281912E+09 |
December | 0.311287E+09 | 0.201304E+09 | 0.109982E+09 | 0.303456E+09 | 0.370104E+09 |
Annual Sum or Average | 0.514834E+10 | 0.250547E+10 | 0.264287E+10 | 0.584307E+10 | 0.273178E+10 |
Minimum of Months | 0.287833E+09 | 0.110768E+09 | 0.109982E+09 | 0.258579E+09 | 0.115875E+09 |
Maximum of Months | 0.531678E+09 | 0.304268E+09 | 0.328576E+09 | 0.661817E+09 | 0.370838E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232241E+09 | 0.138155E+09 | 94085984.75 | 0.208814E+09 | 0.272162E+09 |
February | 0.322800E+09 | 0.200280E+09 | 0.122520E+09 | 0.326757E+09 | 0.216071E+09 |
March | 0.379114E+09 | 0.200438E+09 | 0.178676E+09 | 0.401953E+09 | 0.198896E+09 |
April | 0.387675E+09 | 0.166380E+09 | 0.221296E+09 | 0.432802E+09 | 0.157086E+09 |
May | 0.373237E+09 | 0.113789E+09 | 0.259449E+09 | 0.423112E+09 | 0.128901E+09 |
June | 0.326802E+09 | 87464675.02 | 0.239337E+09 | 0.381647E+09 | 90351599.22 |
July | 0.366890E+09 | 0.133217E+09 | 0.233673E+09 | 0.467684E+09 | 79984008.52 |
August | 0.391136E+09 | 0.179724E+09 | 0.211412E+09 | 0.514101E+09 | 74119136.77 |
September | 0.419822E+09 | 0.229614E+09 | 0.190208E+09 | 0.519155E+09 | 0.111943E+09 |
October | 0.392424E+09 | 0.240255E+09 | 0.152169E+09 | 0.444589E+09 | 0.165189E+09 |
November | 0.227278E+09 | 0.130095E+09 | 97182520.67 | 0.221156E+09 | 0.205807E+09 |
December | 0.245797E+09 | 0.158953E+09 | 86844037.59 | 0.241822E+09 | 0.270522E+09 |
Annual Sum or Average | 0.406522E+10 | 0.197836E+10 | 0.208685E+10 | 0.458359E+10 | 0.197103E+10 |
Minimum of Months | 0.227278E+09 | 87464675.02 | 86844037.59 | 0.208814E+09 | 74119136.77 |
Maximum of Months | 0.419822E+09 | 0.240255E+09 | 0.259449E+09 | 0.519155E+09 | 0.272162E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.166731E+09 | 49599010.86 | 0.117132E+09 | 73866539.92 | 0.545855E+09 |
February | 0.268637E+09 | 0.100850E+09 | 0.167787E+09 | 0.187166E+09 | 0.427529E+09 |
March | 0.416644E+09 | 0.140864E+09 | 0.275781E+09 | 0.352004E+09 | 0.377407E+09 |
April | 0.612687E+09 | 0.233947E+09 | 0.378739E+09 | 0.617623E+09 | 0.285865E+09 |
May | 0.816233E+09 | 0.332303E+09 | 0.483930E+09 | 0.900600E+09 | 0.233199E+09 |
June | 0.758024E+09 | 0.293758E+09 | 0.464266E+09 | 0.860582E+09 | 0.163315E+09 |
July | 0.968308E+09 | 0.508828E+09 | 0.459480E+09 | 0.119246E+10 | 0.144862E+09 |
August | 0.801373E+09 | 0.408746E+09 | 0.392627E+09 | 0.100189E+10 | 0.136101E+09 |
September | 0.633602E+09 | 0.304787E+09 | 0.328815E+09 | 0.733877E+09 | 0.208257E+09 |
October | 0.374415E+09 | 0.153917E+09 | 0.220498E+09 | 0.349322E+09 | 0.316840E+09 |
November | 0.179442E+09 | 51011659.85 | 0.128430E+09 | 0.106044E+09 | 0.404487E+09 |
December | 0.156513E+09 | 54332932.01 | 0.102180E+09 | 85427923.75 | 0.538938E+09 |
Annual Sum or Average | 0.615261E+10 | 0.263294E+10 | 0.351966E+10 | 0.646087E+10 | 0.378266E+10 |
Minimum of Months | 0.156513E+09 | 49599010.86 | 0.102180E+09 | 73866539.92 | 0.136101E+09 |
Maximum of Months | 0.968308E+09 | 0.508828E+09 | 0.483930E+09 | 0.119246E+10 | 0.545855E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52368466.14 | 0.00 | 52368466.14 | 3077966.81 | 0.300564E+09 |
February | 73600977.77 | 0.00 | 73600977.77 | 18300827.45 | 0.234952E+09 |
March | 0.120069E+09 | 391.48 | 0.120069E+09 | 59501450.19 | 0.204157E+09 |
April | 0.164999E+09 | 1015143.42 | 0.163984E+09 | 0.116348E+09 | 0.151410E+09 |
May | 0.218743E+09 | 6567927.74 | 0.212175E+09 | 0.187591E+09 | 0.120419E+09 |
June | 0.222782E+09 | 14903905.08 | 0.207878E+09 | 0.213338E+09 | 82600487.15 |
July | 0.219114E+09 | 17639237.34 | 0.201475E+09 | 0.233696E+09 | 72809956.40 |
August | 0.177614E+09 | 5334198.86 | 0.172280E+09 | 0.196433E+09 | 68267822.21 |
September | 0.133037E+09 | 99658.47 | 0.132938E+09 | 0.113907E+09 | 0.110819E+09 |
October | 94124964.10 | 0.00 | 94124964.10 | 53052440.07 | 0.169535E+09 |
November | 57376818.73 | 0.00 | 57376818.73 | 12556348.92 | 0.219338E+09 |
December | 44499694.93 | 0.00 | 44499694.93 | 2039751.87 | 0.292086E+09 |
Annual Sum or Average | 0.157833E+10 | 45560462.39 | 0.153277E+10 | 0.120984E+10 | 0.202696E+10 |
Minimum of Months | 44499694.93 | 0.00 | 44499694.93 | 2039751.87 | 68267822.21 |
Maximum of Months | 0.222782E+09 | 17639237.34 | 0.212175E+09 | 0.233696E+09 | 0.300564E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.166731E+09 | 49599010.86 | 0.117132E+09 | 78216517.65 | 0.541441E+09 |
February | 0.268637E+09 | 0.100850E+09 | 0.167787E+09 | 0.196321E+09 | 0.421192E+09 |
March | 0.416644E+09 | 0.140864E+09 | 0.275781E+09 | 0.364799E+09 | 0.371054E+09 |
April | 0.612687E+09 | 0.233947E+09 | 0.378739E+09 | 0.629295E+09 | 0.281852E+09 |
May | 0.816233E+09 | 0.332303E+09 | 0.483930E+09 | 0.907955E+09 | 0.231142E+09 |
June | 0.758024E+09 | 0.293758E+09 | 0.464266E+09 | 0.865869E+09 | 0.161965E+09 |
July | 0.968308E+09 | 0.508828E+09 | 0.459480E+09 | 0.119826E+10 | 0.143366E+09 |
August | 0.801373E+09 | 0.408746E+09 | 0.392627E+09 | 0.100968E+10 | 0.133890E+09 |
September | 0.633602E+09 | 0.304787E+09 | 0.328815E+09 | 0.744171E+09 | 0.203996E+09 |
October | 0.374415E+09 | 0.153917E+09 | 0.220498E+09 | 0.362663E+09 | 0.309861E+09 |
November | 0.179442E+09 | 51011659.85 | 0.128430E+09 | 0.111856E+09 | 0.399629E+09 |
December | 0.156513E+09 | 54332932.01 | 0.102180E+09 | 91303342.48 | 0.533500E+09 |
Annual Sum or Average | 0.615261E+10 | 0.263294E+10 | 0.351966E+10 | 0.656039E+10 | 0.373289E+10 |
Minimum of Months | 0.156513E+09 | 49599010.86 | 0.102180E+09 | 78216517.65 | 0.133890E+09 |
Maximum of Months | 0.968308E+09 | 0.508828E+09 | 0.483930E+09 | 0.119826E+10 | 0.541441E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340604E+09 | 0.202618E+09 | 0.137986E+09 | 0.294105E+09 | 0.415268E+09 |
February | 0.473418E+09 | 0.293730E+09 | 0.179688E+09 | 0.465710E+09 | 0.330155E+09 |
March | 0.556007E+09 | 0.293962E+09 | 0.262045E+09 | 0.577355E+09 | 0.302779E+09 |
April | 0.568563E+09 | 0.244012E+09 | 0.324552E+09 | 0.627598E+09 | 0.234700E+09 |
May | 0.547388E+09 | 0.166882E+09 | 0.380507E+09 | 0.620770E+09 | 0.188740E+09 |
June | 0.479286E+09 | 0.128275E+09 | 0.351011E+09 | 0.561797E+09 | 0.131357E+09 |
July | 0.538079E+09 | 0.195375E+09 | 0.342704E+09 | 0.691661E+09 | 0.113774E+09 |
August | 0.573638E+09 | 0.263582E+09 | 0.310056E+09 | 0.756522E+09 | 0.106486E+09 |
September | 0.615709E+09 | 0.336751E+09 | 0.278959E+09 | 0.758219E+09 | 0.165026E+09 |
October | 0.575528E+09 | 0.352358E+09 | 0.223170E+09 | 0.640534E+09 | 0.252291E+09 |
November | 0.333325E+09 | 0.190797E+09 | 0.142527E+09 | 0.314121E+09 | 0.316208E+09 |
December | 0.360485E+09 | 0.233120E+09 | 0.127365E+09 | 0.343439E+09 | 0.413417E+09 |
Annual Sum or Average | 0.596203E+10 | 0.290146E+10 | 0.306057E+10 | 0.665183E+10 | 0.297020E+10 |
Minimum of Months | 0.333325E+09 | 0.128275E+09 | 0.127365E+09 | 0.294105E+09 | 0.106486E+09 |
Maximum of Months | 0.615709E+09 | 0.352358E+09 | 0.380507E+09 | 0.758219E+09 | 0.415268E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.366565E+09 | 0.00 | 0.366565E+09 | 3577324.80 | 0.267900E+10 |
February | 0.515187E+09 | 0.00 | 0.515187E+09 | 63952774.15 | 0.208660E+10 |
March | 0.840452E+09 | 2740.29 | 0.840450E+09 | 0.293688E+09 | 0.181902E+10 |
April | 0.115495E+10 | 7105734.80 | 0.114784E+10 | 0.686272E+09 | 0.133635E+10 |
May | 0.153114E+10 | 45973752.97 | 0.148517E+10 | 0.118780E+10 | 0.105663E+10 |
June | 0.155941E+10 | 0.104323E+09 | 0.145509E+10 | 0.135962E+10 | 0.750649E+09 |
July | 0.153374E+10 | 0.123470E+09 | 0.141027E+10 | 0.153341E+10 | 0.671359E+09 |
August | 0.124325E+10 | 37337977.86 | 0.120591E+10 | 0.126643E+10 | 0.655939E+09 |
September | 0.931226E+09 | 697582.85 | 0.930528E+09 | 0.701271E+09 | 0.998509E+09 |
October | 0.658850E+09 | 0.00 | 0.658850E+09 | 0.256768E+09 | 0.156141E+10 |
November | 0.401623E+09 | 0.00 | 0.401623E+09 | 36596906.24 | 0.202803E+10 |
December | 0.311486E+09 | 0.00 | 0.311486E+09 | 1092167.38 | 0.262098E+10 |
Annual Sum or Average | 0.110479E+11 | 0.318911E+09 | 0.107290E+11 | 0.739049E+10 | 0.182645E+11 |
Minimum of Months | 0.311486E+09 | 0.00 | 0.311486E+09 | 1092167.38 | 0.655939E+09 |
Maximum of Months | 0.155941E+10 | 0.123470E+09 | 0.148517E+10 | 0.153341E+10 | 0.267900E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.366565E+09 | 0.00 | 0.366565E+09 | 2234891.62 | 0.276547E+10 |
February | 0.515187E+09 | 0.00 | 0.515187E+09 | 55961551.98 | 0.215421E+10 |
March | 0.840452E+09 | 2740.29 | 0.840450E+09 | 0.271154E+09 | 0.187050E+10 |
April | 0.115495E+10 | 7105734.80 | 0.114784E+10 | 0.658522E+09 | 0.137095E+10 |
May | 0.153114E+10 | 45973752.97 | 0.148517E+10 | 0.115892E+10 | 0.108120E+10 |
June | 0.155941E+10 | 0.104323E+09 | 0.145509E+10 | 0.133170E+10 | 0.768873E+09 |
July | 0.153374E+10 | 0.123470E+09 | 0.141027E+10 | 0.150908E+10 | 0.688291E+09 |
August | 0.124325E+10 | 37337977.86 | 0.120591E+10 | 0.124281E+10 | 0.674575E+09 |
September | 0.931226E+09 | 697582.85 | 0.930528E+09 | 0.679986E+09 | 0.102524E+10 |
October | 0.658850E+09 | 0.00 | 0.658850E+09 | 0.236803E+09 | 0.161062E+10 |
November | 0.401623E+09 | 0.00 | 0.401623E+09 | 30766388.63 | 0.210046E+10 |
December | 0.311486E+09 | 0.00 | 0.311486E+09 | 668539.84 | 0.270744E+10 |
Annual Sum or Average | 0.110479E+11 | 0.318911E+09 | 0.107290E+11 | 0.717860E+10 | 0.188178E+11 |
Minimum of Months | 0.311486E+09 | 0.00 | 0.311486E+09 | 668539.84 | 0.674575E+09 |
Maximum of Months | 0.155941E+10 | 0.123470E+09 | 0.148517E+10 | 0.150908E+10 | 0.276547E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52368466.14 | 0.00 | 52368466.14 | 3483470.62 | 0.324334E+09 |
February | 73600977.77 | 0.00 | 73600977.77 | 21062372.66 | 0.254898E+09 |
March | 0.120069E+09 | 391.48 | 0.120069E+09 | 68424122.38 | 0.224810E+09 |
April | 0.164999E+09 | 1015143.42 | 0.163984E+09 | 0.139142E+09 | 0.170233E+09 |
May | 0.218743E+09 | 6567927.74 | 0.212175E+09 | 0.226951E+09 | 0.138266E+09 |
June | 0.222782E+09 | 14903905.08 | 0.207878E+09 | 0.256990E+09 | 0.101948E+09 |
July | 0.219114E+09 | 17639237.34 | 0.201475E+09 | 0.286812E+09 | 90636512.37 |
August | 0.177614E+09 | 5334198.86 | 0.172280E+09 | 0.244988E+09 | 86994549.32 |
September | 0.133037E+09 | 99658.47 | 0.132938E+09 | 0.149307E+09 | 0.120582E+09 |
October | 94124964.10 | 0.00 | 94124964.10 | 64361884.09 | 0.188582E+09 |
November | 57376818.73 | 0.00 | 57376818.73 | 16550896.51 | 0.240047E+09 |
December | 44499694.93 | 0.00 | 44499694.93 | 2794605.86 | 0.316251E+09 |
Annual Sum or Average | 0.157833E+10 | 45560462.39 | 0.153277E+10 | 0.148087E+10 | 0.225758E+10 |
Minimum of Months | 44499694.93 | 0.00 | 44499694.93 | 2794605.86 | 86994549.32 |
Maximum of Months | 0.222782E+09 | 17639237.34 | 0.212175E+09 | 0.286812E+09 | 0.324334E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.312927E+09 | 78420063.57 | 0.234506E+09 | 0.123431E+09 | 0.116537E+10 |
February | 0.520668E+09 | 0.184422E+09 | 0.336246E+09 | 0.369724E+09 | 0.903027E+09 |
March | 0.863935E+09 | 0.313278E+09 | 0.550657E+09 | 0.795185E+09 | 0.803266E+09 |
April | 0.129129E+10 | 0.535845E+09 | 0.755447E+09 | 0.143218E+10 | 0.617354E+09 |
May | 0.142075E+10 | 0.494678E+09 | 0.926068E+09 | 0.168431E+10 | 0.519812E+09 |
June | 0.164560E+10 | 0.716233E+09 | 0.929366E+09 | 0.207891E+10 | 0.384861E+09 |
July | 0.158586E+10 | 0.712996E+09 | 0.872859E+09 | 0.212080E+10 | 0.336451E+09 |
August | 0.155674E+10 | 0.778713E+09 | 0.778028E+09 | 0.214069E+10 | 0.325225E+09 |
September | 0.111566E+10 | 0.515455E+09 | 0.600209E+09 | 0.141072E+10 | 0.441259E+09 |
October | 0.753835E+09 | 0.322102E+09 | 0.431733E+09 | 0.780559E+09 | 0.685022E+09 |
November | 0.357007E+09 | 0.101097E+09 | 0.255910E+09 | 0.229850E+09 | 0.873775E+09 |
December | 0.301778E+09 | 96996357.68 | 0.204782E+09 | 0.157589E+09 | 0.114545E+10 |
Annual Sum or Average | 0.117260E+11 | 0.485024E+10 | 0.687581E+10 | 0.133240E+11 | 0.820087E+10 |
Minimum of Months | 0.301778E+09 | 78420063.57 | 0.204782E+09 | 0.123431E+09 | 0.325225E+09 |
Maximum of Months | 0.164560E+10 | 0.778713E+09 | 0.929366E+09 | 0.214069E+10 | 0.116537E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232241E+09 | 0.138155E+09 | 94085984.75 | 0.213940E+09 | 0.294928E+09 |
February | 0.322800E+09 | 0.200280E+09 | 0.122520E+09 | 0.339259E+09 | 0.233580E+09 |
March | 0.379114E+09 | 0.200438E+09 | 0.178676E+09 | 0.423531E+09 | 0.217606E+09 |
April | 0.387675E+09 | 0.166380E+09 | 0.221296E+09 | 0.464951E+09 | 0.174103E+09 |
May | 0.373237E+09 | 0.113789E+09 | 0.259449E+09 | 0.467252E+09 | 0.144458E+09 |
June | 0.326802E+09 | 87464675.02 | 0.239337E+09 | 0.428528E+09 | 0.108406E+09 |
July | 0.366890E+09 | 0.133217E+09 | 0.233673E+09 | 0.524017E+09 | 95609740.63 |
August | 0.391136E+09 | 0.179724E+09 | 0.211412E+09 | 0.568521E+09 | 90633864.32 |
September | 0.419822E+09 | 0.229614E+09 | 0.190208E+09 | 0.564442E+09 | 0.119837E+09 |
October | 0.392424E+09 | 0.240255E+09 | 0.152169E+09 | 0.470247E+09 | 0.183179E+09 |
November | 0.227278E+09 | 0.130095E+09 | 97182520.67 | 0.231209E+09 | 0.226129E+09 |
December | 0.245797E+09 | 0.158953E+09 | 86844037.59 | 0.249854E+09 | 0.293932E+09 |
Annual Sum or Average | 0.406522E+10 | 0.197836E+10 | 0.208685E+10 | 0.494575E+10 | 0.218240E+10 |
Minimum of Months | 0.227278E+09 | 87464675.02 | 86844037.59 | 0.213940E+09 | 90633864.32 |
Maximum of Months | 0.419822E+09 | 0.240255E+09 | 0.259449E+09 | 0.568521E+09 | 0.294928E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66321358.09 | 0.00 | 66321358.09 | 1522850.89 | 0.430258E+09 |
February | 93210994.38 | 0.00 | 93210994.38 | 16181341.93 | 0.333344E+09 |
March | 0.152060E+09 | 495.79 | 0.152060E+09 | 63649488.56 | 0.286789E+09 |
April | 0.208961E+09 | 1285615.09 | 0.207675E+09 | 0.138361E+09 | 0.212758E+09 |
May | 0.277024E+09 | 8317866.07 | 0.268706E+09 | 0.230243E+09 | 0.173063E+09 |
June | 0.282139E+09 | 18874855.40 | 0.263264E+09 | 0.259620E+09 | 0.124397E+09 |
July | 0.277494E+09 | 22338981.12 | 0.255155E+09 | 0.285359E+09 | 0.113830E+09 |
August | 0.224937E+09 | 6755426.29 | 0.218182E+09 | 0.235530E+09 | 0.111019E+09 |
September | 0.168483E+09 | 126211.16 | 0.168357E+09 | 0.133928E+09 | 0.165356E+09 |
October | 0.119203E+09 | 0.00 | 0.119203E+09 | 55135951.75 | 0.244688E+09 |
November | 72664120.65 | 0.00 | 72664120.65 | 10189892.76 | 0.316913E+09 |
December | 56356055.86 | 0.00 | 56356055.86 | 609528.60 | 0.419586E+09 |
Annual Sum or Average | 0.199885E+10 | 57699450.91 | 0.194115E+10 | 0.143033E+10 | 0.293200E+10 |
Minimum of Months | 56356055.86 | 0.00 | 56356055.86 | 609528.60 | 0.111019E+09 |
Maximum of Months | 0.282139E+09 | 22338981.12 | 0.268706E+09 | 0.285359E+09 | 0.430258E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59337970.38 | 0.00 | 59337970.38 | 1362500.46 | 0.384929E+09 |
February | 83396229.85 | 0.00 | 83396229.85 | 14477507.94 | 0.298242E+09 |
March | 0.136049E+09 | 443.59 | 0.136048E+09 | 56947438.58 | 0.256591E+09 |
April | 0.186958E+09 | 1150244.69 | 0.185808E+09 | 0.123792E+09 | 0.190356E+09 |
May | 0.247854E+09 | 7442026.29 | 0.240412E+09 | 0.205999E+09 | 0.154840E+09 |
June | 0.252431E+09 | 16887404.64 | 0.235543E+09 | 0.232283E+09 | 0.111298E+09 |
July | 0.248275E+09 | 19986771.05 | 0.228288E+09 | 0.255312E+09 | 0.101845E+09 |
August | 0.201252E+09 | 6044105.50 | 0.195208E+09 | 0.210729E+09 | 99328938.44 |
September | 0.150743E+09 | 112921.60 | 0.150630E+09 | 0.119826E+09 | 0.147944E+09 |
October | 0.106652E+09 | 0.00 | 0.106652E+09 | 49330344.94 | 0.218924E+09 |
November | 65012864.06 | 0.00 | 65012864.06 | 9116935.66 | 0.283533E+09 |
December | 50421976.71 | 0.00 | 50421976.71 | 545347.54 | 0.375355E+09 |
Annual Sum or Average | 0.178838E+10 | 51623917.35 | 0.173676E+10 | 0.127972E+10 | 0.262319E+10 |
Minimum of Months | 50421976.71 | 0.00 | 50421976.71 | 545347.54 | 99328938.44 |
Maximum of Months | 0.252431E+09 | 19986771.05 | 0.240412E+09 | 0.255312E+09 | 0.384929E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.867026E+09 | 0.515775E+09 | 0.351251E+09 | 0.749092E+09 | 0.111955E+10 |
February | 0.120511E+10 | 0.747705E+09 | 0.457405E+09 | 0.119710E+10 | 0.876372E+09 |
March | 0.141535E+10 | 0.748295E+09 | 0.667051E+09 | 0.148516E+10 | 0.808143E+09 |
April | 0.144731E+10 | 0.621144E+09 | 0.826163E+09 | 0.160845E+10 | 0.640134E+09 |
May | 0.139341E+10 | 0.424807E+09 | 0.968600E+09 | 0.157249E+10 | 0.541943E+09 |
June | 0.122005E+10 | 0.326532E+09 | 0.893516E+09 | 0.140710E+10 | 0.400567E+09 |
July | 0.136971E+10 | 0.497338E+09 | 0.872371E+09 | 0.172895E+10 | 0.367602E+09 |
August | 0.146023E+10 | 0.670963E+09 | 0.789263E+09 | 0.189787E+10 | 0.350846E+09 |
September | 0.156732E+10 | 0.857216E+09 | 0.710104E+09 | 0.192499E+10 | 0.482672E+09 |
October | 0.146504E+10 | 0.896945E+09 | 0.568092E+09 | 0.164527E+10 | 0.684766E+09 |
November | 0.848496E+09 | 0.485685E+09 | 0.362811E+09 | 0.802579E+09 | 0.855667E+09 |
December | 0.917634E+09 | 0.593419E+09 | 0.324215E+09 | 0.881976E+09 | 0.111499E+10 |
Annual Sum or Average | 0.151767E+11 | 0.738582E+10 | 0.779084E+10 | 0.169010E+11 | 0.824325E+10 |
Minimum of Months | 0.848496E+09 | 0.326532E+09 | 0.324215E+09 | 0.749092E+09 | 0.350846E+09 |
Maximum of Months | 0.156732E+10 | 0.896945E+09 | 0.968600E+09 | 0.192499E+10 | 0.111955E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 386.54 | 513.67 | 438.55 | 260.88 | 177.67 | 0.00 | 0.00 |
February | 676.06 | 451.92 | 674.87 | 418.72 | 256.15 | 0.00 | 0.00 |
March | 755.36 | 375.57 | 715.89 | 378.50 | 337.40 | 0.00 | 0.00 |
April | 851.19 | 302.22 | 756.46 | 324.65 | 431.81 | 0.00 | 0.00 |
May | 813.57 | 240.13 | 704.79 | 214.87 | 489.92 | 0.00 | 0.00 |
June | 760.58 | 177.27 | 637.68 | 170.67 | 467.01 | 0.00 | 0.00 |
July | 894.13 | 157.10 | 692.81 | 251.56 | 441.25 | 0.00 | 0.00 |
August | 973.19 | 152.17 | 738.59 | 339.38 | 399.21 | 0.00 | 0.00 |
September | 1008.76 | 226.59 | 819.19 | 448.04 | 371.15 | 0.00 | 0.00 |
October | 835.07 | 318.65 | 741.03 | 453.68 | 287.34 | 0.00 | 0.00 |
November | 424.24 | 406.85 | 443.48 | 253.85 | 189.63 | 0.00 | 0.00 |
December | 448.39 | 516.41 | 464.15 | 300.16 | 163.99 | 0.00 | 0.00 |
Annual Sum or Average | 735.80 | 319.25 | 651.97 | 317.29 | 334.69 | 0.00 | 0.00 |
Minimum of Months | 386.54 | 152.17 | 438.55 | 170.67 | 163.99 | 0.00 | 0.00 |
Maximum of Months | 1008.76 | 516.41 | 819.19 | 453.68 | 489.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1072.69 | 1490.99 | 1234.93 | 734.63 | 500.29 | 0.00 | 0.00 |
February | 1879.61 | 1324.18 | 1900.38 | 1179.08 | 721.29 | 0.00 | 0.00 |
March | 2099.72 | 1123.78 | 2015.91 | 1065.82 | 950.09 | 0.00 | 0.00 |
April | 2362.19 | 917.07 | 2130.15 | 914.20 | 1215.94 | 0.00 | 0.00 |
May | 2252.86 | 738.88 | 1984.66 | 605.06 | 1379.59 | 0.00 | 0.00 |
June | 2097.26 | 561.49 | 1795.66 | 480.59 | 1315.07 | 0.00 | 0.00 |
July | 2477.93 | 500.24 | 1950.90 | 708.37 | 1242.53 | 0.00 | 0.00 |
August | 2704.05 | 488.26 | 2079.83 | 955.67 | 1124.16 | 0.00 | 0.00 |
September | 2809.12 | 703.94 | 2306.78 | 1261.66 | 1045.13 | 0.00 | 0.00 |
October | 2322.79 | 971.45 | 2086.69 | 1277.54 | 809.14 | 0.00 | 0.00 |
November | 1176.37 | 1201.29 | 1248.82 | 714.83 | 533.99 | 0.00 | 0.00 |
December | 1246.81 | 1504.20 | 1307.01 | 845.22 | 461.79 | 0.00 | 0.00 |
Annual Sum or Average | 2042.35 | 958.75 | 1835.92 | 893.47 | 942.45 | 0.00 | 0.00 |
Minimum of Months | 1072.69 | 488.26 | 1234.93 | 480.59 | 461.79 | 0.00 | 0.00 |
Maximum of Months | 2809.12 | 1504.20 | 2306.78 | 1277.54 | 1379.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1401.79 | 2080.88 | 1604.24 | 954.33 | 649.91 | 0.00 | 0.00 |
February | 2467.40 | 1838.59 | 2468.70 | 1531.69 | 937.00 | 0.00 | 0.00 |
March | 2759.72 | 1570.14 | 2618.78 | 1384.56 | 1234.22 | 0.00 | 0.00 |
April | 3106.03 | 1280.75 | 2767.18 | 1187.60 | 1579.58 | 0.00 | 0.00 |
May | 2956.50 | 1041.04 | 2578.18 | 786.01 | 1792.17 | 0.00 | 0.00 |
June | 2745.51 | 795.73 | 2332.66 | 624.32 | 1708.35 | 0.00 | 0.00 |
July | 3256.87 | 702.02 | 2534.33 | 920.22 | 1614.12 | 0.00 | 0.00 |
August | 3555.05 | 679.35 | 2701.82 | 1241.47 | 1460.35 | 0.00 | 0.00 |
September | 3691.43 | 982.13 | 2996.64 | 1638.96 | 1357.68 | 0.00 | 0.00 |
October | 3050.12 | 1361.95 | 2710.73 | 1659.60 | 1051.12 | 0.00 | 0.00 |
November | 1533.41 | 1695.13 | 1622.29 | 928.61 | 693.68 | 0.00 | 0.00 |
December | 1632.40 | 2099.99 | 1697.88 | 1097.99 | 599.89 | 0.00 | 0.00 |
Annual Sum or Average | 2680.45 | 1341.61 | 2384.96 | 1160.66 | 1224.30 | 0.00 | 0.00 |
Minimum of Months | 1401.79 | 679.35 | 1604.24 | 624.32 | 599.89 | 0.00 | 0.00 |
Maximum of Months | 3691.43 | 2099.99 | 2996.64 | 1659.60 | 1792.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 97.21 | 299.80 | 148.96 | 70.10 | 78.86 | 0.00 | 0.00 |
February | 205.91 | 261.46 | 244.48 | 124.48 | 120.00 | 0.00 | 0.00 |
March | 279.92 | 214.60 | 297.10 | 127.43 | 169.67 | 0.00 | 0.00 |
April | 406.69 | 170.42 | 385.94 | 154.45 | 231.50 | 0.00 | 0.00 |
May | 497.30 | 135.17 | 444.10 | 166.55 | 277.55 | 0.00 | 0.00 |
June | 482.86 | 98.18 | 418.53 | 147.08 | 271.45 | 0.00 | 0.00 |
July | 624.10 | 84.29 | 498.51 | 239.71 | 258.79 | 0.00 | 0.00 |
August | 569.10 | 79.62 | 445.23 | 219.71 | 225.52 | 0.00 | 0.00 |
September | 484.66 | 124.69 | 406.41 | 206.17 | 200.24 | 0.00 | 0.00 |
October | 295.06 | 180.54 | 286.30 | 147.17 | 139.14 | 0.00 | 0.00 |
November | 121.98 | 234.45 | 156.91 | 69.87 | 87.04 | 0.00 | 0.00 |
December | 114.80 | 298.43 | 150.21 | 79.63 | 70.57 | 0.00 | 0.00 |
Annual Sum or Average | 349.19 | 181.42 | 324.01 | 146.22 | 177.78 | 0.00 | 0.00 |
Minimum of Months | 97.21 | 79.62 | 148.96 | 69.87 | 70.57 | 0.00 | 0.00 |
Maximum of Months | 624.10 | 299.80 | 498.51 | 239.71 | 277.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 26.83 | 313.76 | 81.80 | 18.52 | 63.28 | 0.00 | 0.00 |
February | 85.21 | 270.60 | 141.47 | 41.69 | 99.78 | 0.00 | 0.00 |
March | 156.57 | 215.55 | 200.39 | 52.59 | 147.79 | 0.00 | 0.00 |
April | 288.42 | 167.74 | 300.03 | 90.65 | 209.38 | 0.00 | 0.00 |
May | 411.22 | 131.42 | 386.42 | 126.52 | 259.90 | 0.00 | 0.00 |
June | 418.50 | 93.91 | 378.40 | 119.08 | 259.31 | 0.00 | 0.00 |
July | 537.49 | 80.43 | 443.33 | 196.56 | 246.77 | 0.00 | 0.00 |
August | 451.89 | 76.21 | 365.51 | 154.60 | 210.91 | 0.00 | 0.00 |
September | 331.54 | 123.23 | 295.77 | 117.63 | 178.15 | 0.00 | 0.00 |
October | 153.29 | 181.22 | 174.93 | 57.47 | 117.47 | 0.00 | 0.00 |
November | 45.67 | 240.42 | 91.37 | 19.68 | 71.68 | 0.00 | 0.00 |
December | 31.95 | 309.61 | 75.05 | 20.29 | 54.76 | 0.00 | 0.00 |
Annual Sum or Average | 245.91 | 183.26 | 245.15 | 84.93 | 160.21 | 0.00 | 0.00 |
Minimum of Months | 26.83 | 76.21 | 75.05 | 18.52 | 54.76 | 0.00 | 0.00 |
Maximum of Months | 537.49 | 313.76 | 443.33 | 196.56 | 259.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 62.42 | 77.58 | 69.35 | 41.26 | 28.10 | 0.00 | 0.00 |
February | 107.43 | 72.12 | 106.72 | 66.22 | 40.51 | 0.00 | 0.00 |
March | 118.08 | 65.22 | 113.21 | 59.86 | 53.36 | 0.00 | 0.00 |
April | 131.55 | 55.00 | 119.63 | 51.34 | 68.29 | 0.00 | 0.00 |
May | 125.30 | 44.32 | 111.46 | 33.98 | 77.48 | 0.00 | 0.00 |
June | 116.37 | 33.45 | 100.84 | 26.99 | 73.85 | 0.00 | 0.00 |
July | 139.26 | 29.07 | 109.56 | 39.78 | 69.78 | 0.00 | 0.00 |
August | 152.49 | 27.82 | 116.80 | 53.67 | 63.13 | 0.00 | 0.00 |
September | 158.35 | 41.39 | 129.55 | 70.85 | 58.69 | 0.00 | 0.00 |
October | 130.11 | 57.34 | 117.19 | 71.75 | 45.44 | 0.00 | 0.00 |
November | 67.22 | 65.03 | 70.13 | 40.14 | 29.99 | 0.00 | 0.00 |
December | 71.77 | 79.32 | 73.40 | 47.47 | 25.93 | 0.00 | 0.00 |
Annual Sum or Average | 115.05 | 53.88 | 103.11 | 50.18 | 52.93 | 0.00 | 0.00 |
Minimum of Months | 62.42 | 27.82 | 69.35 | 26.99 | 25.93 | 0.00 | 0.00 |
Maximum of Months | 158.35 | 79.32 | 129.55 | 71.75 | 77.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.58 | 95.73 | 15.64 | 0.00 | 15.64 | 0.00 | 0.00 |
February | 5.28 | 81.71 | 24.34 | 0.00 | 24.34 | 0.00 | 0.00 |
March | 17.33 | 63.41 | 35.87 | 0.00 | 35.87 | 0.00 | 0.00 |
April | 37.37 | 47.46 | 50.93 | 0.31 | 50.62 | 0.00 | 0.00 |
May | 59.54 | 35.79 | 65.34 | 1.96 | 63.38 | 0.00 | 0.00 |
June | 69.95 | 25.03 | 68.77 | 4.60 | 64.17 | 0.00 | 0.00 |
July | 75.23 | 20.63 | 65.45 | 5.27 | 60.19 | 0.00 | 0.00 |
August | 63.24 | 19.41 | 53.06 | 1.59 | 51.46 | 0.00 | 0.00 |
September | 37.71 | 33.68 | 41.07 | 0.03 | 41.04 | 0.00 | 0.00 |
October | 15.64 | 52.78 | 28.12 | 0.00 | 28.12 | 0.00 | 0.00 |
November | 3.19 | 72.45 | 17.71 | 0.00 | 17.71 | 0.00 | 0.00 |
December | 0.33 | 93.34 | 13.29 | 0.00 | 13.29 | 0.00 | 0.00 |
Annual Sum or Average | 32.28 | 53.32 | 40.04 | 1.16 | 38.89 | 0.00 | 0.00 |
Minimum of Months | 0.33 | 19.41 | 13.29 | 0.00 | 13.29 | 0.00 | 0.00 |
Maximum of Months | 75.23 | 95.73 | 68.77 | 5.27 | 64.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 91.30 | 298.16 | 145.13 | 66.22 | 78.91 | 0.00 | 0.00 |
February | 199.50 | 259.22 | 241.05 | 120.91 | 120.15 | 0.00 | 0.00 |
March | 282.41 | 210.40 | 302.83 | 133.32 | 169.51 | 0.00 | 0.00 |
April | 415.94 | 164.69 | 398.68 | 167.56 | 231.11 | 0.00 | 0.00 |
May | 442.43 | 131.40 | 404.59 | 134.84 | 269.76 | 0.00 | 0.00 |
June | 512.47 | 94.68 | 443.54 | 171.92 | 271.63 | 0.00 | 0.00 |
July | 533.26 | 78.30 | 433.05 | 182.85 | 250.20 | 0.00 | 0.00 |
August | 552.68 | 74.54 | 436.66 | 212.48 | 224.18 | 0.00 | 0.00 |
September | 440.38 | 119.89 | 377.20 | 188.02 | 189.17 | 0.00 | 0.00 |
October | 294.14 | 178.09 | 287.25 | 149.83 | 137.41 | 0.00 | 0.00 |
November | 120.16 | 232.59 | 156.56 | 69.69 | 86.86 | 0.00 | 0.00 |
December | 110.32 | 295.73 | 148.11 | 77.45 | 70.65 | 0.00 | 0.00 |
Annual Sum or Average | 333.58 | 177.75 | 314.84 | 139.64 | 175.20 | 0.00 | 0.00 |
Minimum of Months | 91.30 | 74.54 | 145.13 | 66.22 | 70.65 | 0.00 | 0.00 |
Maximum of Months | 552.68 | 298.16 | 443.54 | 212.48 | 271.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 18.70 | 310.08 | 77.97 | 14.64 | 63.33 | 0.00 | 0.00 |
February | 74.64 | 263.93 | 138.04 | 38.12 | 99.92 | 0.00 | 0.00 |
March | 156.35 | 208.69 | 206.12 | 58.49 | 147.63 | 0.00 | 0.00 |
April | 296.77 | 161.79 | 312.77 | 103.76 | 209.00 | 0.00 | 0.00 |
May | 356.73 | 128.49 | 346.91 | 94.80 | 252.11 | 0.00 | 0.00 |
June | 449.17 | 92.22 | 403.41 | 143.92 | 259.49 | 0.00 | 0.00 |
July | 447.70 | 75.77 | 377.87 | 139.70 | 238.18 | 0.00 | 0.00 |
August | 436.61 | 72.90 | 356.94 | 147.37 | 209.57 | 0.00 | 0.00 |
September | 286.12 | 117.74 | 266.55 | 99.48 | 167.08 | 0.00 | 0.00 |
October | 149.93 | 176.51 | 175.88 | 60.13 | 115.74 | 0.00 | 0.00 |
November | 41.72 | 236.34 | 91.01 | 19.50 | 71.51 | 0.00 | 0.00 |
December | 23.89 | 303.36 | 72.95 | 18.11 | 54.85 | 0.00 | 0.00 |
Annual Sum or Average | 229.02 | 178.58 | 235.98 | 78.35 | 157.63 | 0.00 | 0.00 |
Minimum of Months | 18.70 | 72.90 | 72.95 | 14.64 | 54.85 | 0.00 | 0.00 |
Maximum of Months | 449.17 | 310.08 | 403.41 | 147.37 | 259.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 117.37 | 388.61 | 184.16 | 89.39 | 94.77 | 0.00 | 0.00 |
February | 232.17 | 335.97 | 283.98 | 143.47 | 140.50 | 0.00 | 0.00 |
March | 294.86 | 277.49 | 323.00 | 129.69 | 193.31 | 0.00 | 0.00 |
April | 370.93 | 222.02 | 369.54 | 111.92 | 257.62 | 0.00 | 0.00 |
May | 399.54 | 177.51 | 383.06 | 77.88 | 305.18 | 0.00 | 0.00 |
June | 399.86 | 130.57 | 367.48 | 68.45 | 299.03 | 0.00 | 0.00 |
July | 456.57 | 114.83 | 379.19 | 97.61 | 281.58 | 0.00 | 0.00 |
August | 458.68 | 113.30 | 368.02 | 119.74 | 248.28 | 0.00 | 0.00 |
September | 423.31 | 171.46 | 369.66 | 153.59 | 216.07 | 0.00 | 0.00 |
October | 316.43 | 236.80 | 314.83 | 155.45 | 159.37 | 0.00 | 0.00 |
November | 145.02 | 303.59 | 190.33 | 86.98 | 103.35 | 0.00 | 0.00 |
December | 141.48 | 384.95 | 187.84 | 102.85 | 84.99 | 0.00 | 0.00 |
Annual Sum or Average | 313.44 | 237.63 | 310.15 | 111.22 | 198.93 | 0.00 | 0.00 |
Minimum of Months | 117.37 | 113.30 | 184.16 | 68.45 | 84.99 | 0.00 | 0.00 |
Maximum of Months | 458.68 | 388.61 | 383.06 | 155.45 | 305.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 97.74 | 297.61 | 148.96 | 70.10 | 78.86 | 0.00 | 0.00 |
February | 205.84 | 259.44 | 244.48 | 124.48 | 120.00 | 0.00 | 0.00 |
March | 278.92 | 212.59 | 297.10 | 127.43 | 169.67 | 0.00 | 0.00 |
April | 403.68 | 169.32 | 385.94 | 154.45 | 231.50 | 0.00 | 0.00 |
May | 493.07 | 134.05 | 444.10 | 166.55 | 277.55 | 0.00 | 0.00 |
June | 478.49 | 97.10 | 418.53 | 147.08 | 271.45 | 0.00 | 0.00 |
July | 619.16 | 83.28 | 498.51 | 239.71 | 258.79 | 0.00 | 0.00 |
August | 565.61 | 78.09 | 445.23 | 219.71 | 225.52 | 0.00 | 0.00 |
September | 482.53 | 122.64 | 406.41 | 206.17 | 200.24 | 0.00 | 0.00 |
October | 294.29 | 177.85 | 286.30 | 147.17 | 139.14 | 0.00 | 0.00 |
November | 122.46 | 231.67 | 156.91 | 69.87 | 87.04 | 0.00 | 0.00 |
December | 115.34 | 295.37 | 150.21 | 79.63 | 70.57 | 0.00 | 0.00 |
Annual Sum or Average | 347.31 | 179.54 | 324.01 | 146.22 | 177.78 | 0.00 | 0.00 |
Minimum of Months | 97.74 | 78.09 | 148.96 | 69.87 | 70.57 | 0.00 | 0.00 |
Maximum of Months | 619.16 | 297.61 | 498.51 | 239.71 | 277.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 27.24 | 311.26 | 81.80 | 18.52 | 63.28 | 0.00 | 0.00 |
February | 85.76 | 268.26 | 141.47 | 41.69 | 99.78 | 0.00 | 0.00 |
March | 156.68 | 213.02 | 200.39 | 52.59 | 147.79 | 0.00 | 0.00 |
April | 286.73 | 166.21 | 300.03 | 90.65 | 209.38 | 0.00 | 0.00 |
May | 407.92 | 130.14 | 386.42 | 126.52 | 259.90 | 0.00 | 0.00 |
June | 414.83 | 92.82 | 378.40 | 119.08 | 259.31 | 0.00 | 0.00 |
July | 533.33 | 79.41 | 443.33 | 196.56 | 246.77 | 0.00 | 0.00 |
August | 449.41 | 74.58 | 365.51 | 154.60 | 210.91 | 0.00 | 0.00 |
September | 330.38 | 120.79 | 295.77 | 117.63 | 178.15 | 0.00 | 0.00 |
October | 153.92 | 177.70 | 174.93 | 57.47 | 117.47 | 0.00 | 0.00 |
November | 46.40 | 237.20 | 91.37 | 19.68 | 71.68 | 0.00 | 0.00 |
December | 32.56 | 305.95 | 75.05 | 20.29 | 54.76 | 0.00 | 0.00 |
Annual Sum or Average | 244.78 | 181.03 | 245.15 | 84.93 | 160.21 | 0.00 | 0.00 |
Minimum of Months | 27.24 | 74.58 | 75.05 | 18.52 | 54.76 | 0.00 | 0.00 |
Maximum of Months | 533.33 | 311.26 | 443.33 | 196.56 | 259.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 109.81 | 155.04 | 127.17 | 75.65 | 51.52 | 0.00 | 0.00 |
February | 192.51 | 136.47 | 195.69 | 121.42 | 74.28 | 0.00 | 0.00 |
March | 215.56 | 113.04 | 207.59 | 109.75 | 97.84 | 0.00 | 0.00 |
April | 242.13 | 90.55 | 219.35 | 94.14 | 125.21 | 0.00 | 0.00 |
May | 231.77 | 70.47 | 204.37 | 62.31 | 142.06 | 0.00 | 0.00 |
June | 216.74 | 50.68 | 184.91 | 49.49 | 135.42 | 0.00 | 0.00 |
July | 258.24 | 42.48 | 200.90 | 72.94 | 127.95 | 0.00 | 0.00 |
August | 282.45 | 39.76 | 214.17 | 98.41 | 115.76 | 0.00 | 0.00 |
September | 292.52 | 63.67 | 237.54 | 129.92 | 107.62 | 0.00 | 0.00 |
October | 239.15 | 94.19 | 214.88 | 131.56 | 83.32 | 0.00 | 0.00 |
November | 121.19 | 121.99 | 128.60 | 73.61 | 54.99 | 0.00 | 0.00 |
December | 128.23 | 154.35 | 134.59 | 87.04 | 47.55 | 0.00 | 0.00 |
Annual Sum or Average | 210.93 | 94.18 | 189.05 | 92.00 | 97.05 | 0.00 | 0.00 |
Minimum of Months | 109.81 | 39.76 | 127.17 | 49.49 | 47.55 | 0.00 | 0.00 |
Maximum of Months | 292.52 | 155.04 | 237.54 | 131.56 | 142.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.34 | 1000.22 | 136.86 | 0.00 | 136.86 | 0.00 | 0.00 |
February | 26.44 | 862.52 | 212.96 | 0.00 | 212.96 | 0.00 | 0.00 |
March | 109.65 | 679.15 | 313.79 | 0.00 | 313.79 | 0.00 | 0.00 |
April | 264.77 | 515.57 | 445.58 | 2.74 | 442.84 | 0.00 | 0.00 |
May | 443.48 | 394.50 | 571.66 | 17.16 | 554.50 | 0.00 | 0.00 |
June | 524.55 | 289.60 | 601.63 | 40.25 | 561.38 | 0.00 | 0.00 |
July | 572.51 | 250.66 | 572.63 | 46.10 | 526.53 | 0.00 | 0.00 |
August | 472.83 | 244.90 | 464.18 | 13.94 | 450.24 | 0.00 | 0.00 |
September | 270.55 | 385.23 | 359.27 | 0.27 | 359.00 | 0.00 | 0.00 |
October | 95.87 | 582.96 | 245.99 | 0.00 | 245.99 | 0.00 | 0.00 |
November | 14.12 | 782.42 | 154.95 | 0.00 | 154.95 | 0.00 | 0.00 |
December | 0.41 | 978.56 | 116.30 | 0.00 | 116.30 | 0.00 | 0.00 |
Annual Sum or Average | 234.35 | 579.16 | 350.33 | 10.11 | 340.21 | 0.00 | 0.00 |
Minimum of Months | 0.41 | 244.90 | 116.30 | 0.00 | 116.30 | 0.00 | 0.00 |
Maximum of Months | 572.51 | 1000.22 | 601.63 | 46.10 | 561.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.83 | 1032.51 | 136.86 | 0.00 | 136.86 | 0.00 | 0.00 |
February | 23.13 | 890.46 | 212.96 | 0.00 | 212.96 | 0.00 | 0.00 |
March | 101.24 | 698.36 | 313.79 | 0.00 | 313.79 | 0.00 | 0.00 |
April | 254.06 | 528.92 | 445.58 | 2.74 | 442.84 | 0.00 | 0.00 |
May | 432.69 | 403.67 | 571.66 | 17.16 | 554.50 | 0.00 | 0.00 |
June | 513.77 | 296.63 | 601.63 | 40.25 | 561.38 | 0.00 | 0.00 |
July | 563.42 | 256.98 | 572.63 | 46.10 | 526.53 | 0.00 | 0.00 |
August | 464.01 | 251.86 | 464.18 | 13.94 | 450.24 | 0.00 | 0.00 |
September | 262.34 | 395.54 | 359.27 | 0.27 | 359.00 | 0.00 | 0.00 |
October | 88.41 | 601.34 | 245.99 | 0.00 | 245.99 | 0.00 | 0.00 |
November | 11.87 | 810.36 | 154.95 | 0.00 | 154.95 | 0.00 | 0.00 |
December | 0.25 | 1010.84 | 116.30 | 0.00 | 116.30 | 0.00 | 0.00 |
Annual Sum or Average | 227.63 | 596.71 | 350.33 | 10.11 | 340.21 | 0.00 | 0.00 |
Minimum of Months | 0.25 | 251.86 | 116.30 | 0.00 | 116.30 | 0.00 | 0.00 |
Maximum of Months | 563.42 | 1032.51 | 601.63 | 46.10 | 561.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 109.82 | 648.86 | 223.09 | 80.86 | 142.23 | 0.00 | 0.00 |
February | 288.30 | 561.72 | 379.08 | 159.02 | 220.06 | 0.00 | 0.00 |
March | 475.63 | 460.15 | 508.93 | 191.80 | 317.13 | 0.00 | 0.00 |
April | 781.03 | 366.46 | 711.41 | 271.31 | 440.10 | 0.00 | 0.00 |
May | 885.71 | 297.31 | 751.47 | 229.63 | 521.84 | 0.00 | 0.00 |
June | 1064.34 | 227.45 | 846.91 | 315.82 | 531.09 | 0.00 | 0.00 |
July | 1092.52 | 193.12 | 810.88 | 322.53 | 488.35 | 0.00 | 0.00 |
August | 1101.26 | 186.03 | 793.57 | 359.83 | 433.74 | 0.00 | 0.00 |
September | 817.37 | 260.74 | 643.72 | 287.49 | 356.23 | 0.00 | 0.00 |
October | 487.77 | 391.30 | 463.11 | 209.96 | 253.15 | 0.00 | 0.00 |
November | 176.90 | 509.59 | 247.55 | 89.19 | 158.36 | 0.00 | 0.00 |
December | 139.26 | 641.57 | 221.06 | 95.56 | 125.49 | 0.00 | 0.00 |
Annual Sum or Average | 620.04 | 394.59 | 550.79 | 217.98 | 332.81 | 0.00 | 0.00 |
Minimum of Months | 109.82 | 186.03 | 221.06 | 80.86 | 125.49 | 0.00 | 0.00 |
Maximum of Months | 1101.26 | 648.86 | 846.91 | 359.83 | 531.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 256.79 | 698.38 | 370.63 | 192.57 | 178.06 | 0.00 | 0.00 |
February | 488.49 | 604.31 | 571.15 | 309.07 | 262.08 | 0.00 | 0.00 |
March | 595.10 | 500.18 | 636.00 | 279.38 | 356.62 | 0.00 | 0.00 |
April | 721.03 | 401.84 | 711.12 | 240.58 | 470.54 | 0.00 | 0.00 |
May | 746.38 | 321.17 | 716.21 | 164.49 | 551.72 | 0.00 | 0.00 |
June | 727.27 | 240.10 | 676.94 | 139.77 | 537.16 | 0.00 | 0.00 |
July | 841.68 | 212.07 | 707.69 | 201.49 | 506.20 | 0.00 | 0.00 |
August | 872.80 | 207.12 | 704.31 | 255.29 | 449.02 | 0.00 | 0.00 |
September | 839.79 | 306.31 | 727.83 | 330.81 | 397.03 | 0.00 | 0.00 |
October | 647.89 | 423.36 | 631.31 | 334.88 | 296.43 | 0.00 | 0.00 |
November | 304.54 | 549.22 | 380.47 | 187.38 | 193.09 | 0.00 | 0.00 |
December | 307.99 | 691.35 | 382.47 | 221.56 | 160.91 | 0.00 | 0.00 |
Annual Sum or Average | 613.11 | 428.79 | 601.34 | 237.67 | 363.67 | 0.00 | 0.00 |
Minimum of Months | 256.79 | 207.12 | 370.63 | 139.77 | 160.91 | 0.00 | 0.00 |
Maximum of Months | 872.80 | 698.38 | 727.83 | 334.88 | 551.72 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.103531E+10 | 0.137583E+10 | 0.117461E+10 | 0.698752E+09 | 0.475859E+09 | 0.00 | 0.00 |
February | 0.163551E+10 | 0.109329E+10 | 0.163263E+10 | 0.101296E+10 | 0.619672E+09 | 0.00 | 0.00 |
March | 0.202315E+10 | 0.100594E+10 | 0.191745E+10 | 0.101376E+10 | 0.903689E+09 | 0.00 | 0.00 |
April | 0.220628E+10 | 0.783345E+09 | 0.196075E+10 | 0.841503E+09 | 0.111925E+10 | 0.00 | 0.00 |
May | 0.217907E+10 | 0.643170E+09 | 0.188772E+10 | 0.575512E+09 | 0.131221E+10 | 0.00 | 0.00 |
June | 0.197142E+10 | 0.459488E+09 | 0.165286E+10 | 0.442373E+09 | 0.121049E+10 | 0.00 | 0.00 |
July | 0.239484E+10 | 0.420782E+09 | 0.185562E+10 | 0.673775E+09 | 0.118184E+10 | 0.00 | 0.00 |
August | 0.260659E+10 | 0.407567E+09 | 0.197825E+10 | 0.908995E+09 | 0.106925E+10 | 0.00 | 0.00 |
September | 0.261469E+10 | 0.587313E+09 | 0.212334E+10 | 0.116132E+10 | 0.962015E+09 | 0.00 | 0.00 |
October | 0.223666E+10 | 0.853468E+09 | 0.198477E+10 | 0.121515E+10 | 0.769624E+09 | 0.00 | 0.00 |
November | 0.109962E+10 | 0.105455E+10 | 0.114951E+10 | 0.657987E+09 | 0.491521E+09 | 0.00 | 0.00 |
December | 0.120097E+10 | 0.138314E+10 | 0.124317E+10 | 0.803942E+09 | 0.439232E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.232041E+11 | 0.100679E+11 | 0.205607E+11 | 0.100060E+11 | 0.105547E+11 | 0.00 | 0.00 |
Minimum of Months | 0.103531E+10 | 0.407567E+09 | 0.114951E+10 | 0.442373E+09 | 0.439232E+09 | 0.00 | 0.00 |
Maximum of Months | 0.261469E+10 | 0.138314E+10 | 0.212334E+10 | 0.121515E+10 | 0.131221E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.287309E+10 | 0.399346E+10 | 0.330763E+10 | 0.196764E+10 | 0.133999E+10 | 0.00 | 0.00 |
February | 0.454715E+10 | 0.320347E+10 | 0.459739E+10 | 0.285244E+10 | 0.174495E+10 | 0.00 | 0.00 |
March | 0.562388E+10 | 0.300993E+10 | 0.539941E+10 | 0.285469E+10 | 0.254473E+10 | 0.00 | 0.00 |
April | 0.612279E+10 | 0.237704E+10 | 0.552134E+10 | 0.236962E+10 | 0.315172E+10 | 0.00 | 0.00 |
May | 0.603405E+10 | 0.197901E+10 | 0.531570E+10 | 0.162060E+10 | 0.369510E+10 | 0.00 | 0.00 |
June | 0.543610E+10 | 0.145539E+10 | 0.465435E+10 | 0.124569E+10 | 0.340866E+10 | 0.00 | 0.00 |
July | 0.663689E+10 | 0.133983E+10 | 0.522529E+10 | 0.189731E+10 | 0.332799E+10 | 0.00 | 0.00 |
August | 0.724252E+10 | 0.130775E+10 | 0.557061E+10 | 0.255967E+10 | 0.301095E+10 | 0.00 | 0.00 |
September | 0.728124E+10 | 0.182462E+10 | 0.597918E+10 | 0.327021E+10 | 0.270897E+10 | 0.00 | 0.00 |
October | 0.622137E+10 | 0.260192E+10 | 0.558898E+10 | 0.342177E+10 | 0.216721E+10 | 0.00 | 0.00 |
November | 0.304916E+10 | 0.311375E+10 | 0.323694E+10 | 0.185285E+10 | 0.138409E+10 | 0.00 | 0.00 |
December | 0.333944E+10 | 0.402886E+10 | 0.350069E+10 | 0.226385E+10 | 0.123685E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.644077E+11 | 0.302350E+11 | 0.578975E+11 | 0.281763E+11 | 0.297212E+11 | 0.00 | 0.00 |
Minimum of Months | 0.287309E+10 | 0.130775E+10 | 0.323694E+10 | 0.124569E+10 | 0.123685E+10 | 0.00 | 0.00 |
Maximum of Months | 0.728124E+10 | 0.402886E+10 | 0.597918E+10 | 0.342177E+10 | 0.369510E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.375454E+10 | 0.557344E+10 | 0.429680E+10 | 0.255608E+10 | 0.174072E+10 | 0.00 | 0.00 |
February | 0.596913E+10 | 0.444792E+10 | 0.597227E+10 | 0.370548E+10 | 0.226679E+10 | 0.00 | 0.00 |
March | 0.739163E+10 | 0.420547E+10 | 0.701415E+10 | 0.370840E+10 | 0.330575E+10 | 0.00 | 0.00 |
April | 0.805084E+10 | 0.331971E+10 | 0.717253E+10 | 0.307827E+10 | 0.409427E+10 | 0.00 | 0.00 |
May | 0.791870E+10 | 0.278832E+10 | 0.690540E+10 | 0.210526E+10 | 0.480014E+10 | 0.00 | 0.00 |
June | 0.711635E+10 | 0.206252E+10 | 0.604627E+10 | 0.161823E+10 | 0.442804E+10 | 0.00 | 0.00 |
July | 0.872319E+10 | 0.188029E+10 | 0.678795E+10 | 0.246471E+10 | 0.432325E+10 | 0.00 | 0.00 |
August | 0.952185E+10 | 0.181956E+10 | 0.723654E+10 | 0.332516E+10 | 0.391139E+10 | 0.00 | 0.00 |
September | 0.956819E+10 | 0.254569E+10 | 0.776730E+10 | 0.424819E+10 | 0.351911E+10 | 0.00 | 0.00 |
October | 0.816943E+10 | 0.364785E+10 | 0.726041E+10 | 0.444508E+10 | 0.281533E+10 | 0.00 | 0.00 |
November | 0.397460E+10 | 0.439378E+10 | 0.420497E+10 | 0.240696E+10 | 0.179801E+10 | 0.00 | 0.00 |
December | 0.437221E+10 | 0.562460E+10 | 0.454760E+10 | 0.294087E+10 | 0.160674E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.845307E+11 | 0.423092E+11 | 0.752122E+11 | 0.366027E+11 | 0.386095E+11 | 0.00 | 0.00 |
Minimum of Months | 0.375454E+10 | 0.181956E+10 | 0.420497E+10 | 0.161823E+10 | 0.160674E+10 | 0.00 | 0.00 |
Maximum of Months | 0.956819E+10 | 0.562460E+10 | 0.776730E+10 | 0.444508E+10 | 0.480014E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.260365E+09 | 0.802986E+09 | 0.398972E+09 | 0.187754E+09 | 0.211218E+09 | 0.00 | 0.00 |
February | 0.498148E+09 | 0.632514E+09 | 0.591438E+09 | 0.301130E+09 | 0.290308E+09 | 0.00 | 0.00 |
March | 0.749730E+09 | 0.574773E+09 | 0.795758E+09 | 0.341302E+09 | 0.454457E+09 | 0.00 | 0.00 |
April | 0.105413E+10 | 0.441720E+09 | 0.100036E+10 | 0.400327E+09 | 0.600035E+09 | 0.00 | 0.00 |
May | 0.133197E+10 | 0.362032E+09 | 0.118947E+10 | 0.446091E+09 | 0.743379E+09 | 0.00 | 0.00 |
June | 0.125157E+10 | 0.254473E+09 | 0.108483E+10 | 0.381223E+09 | 0.703603E+09 | 0.00 | 0.00 |
July | 0.167158E+10 | 0.225769E+09 | 0.133520E+10 | 0.642045E+09 | 0.693153E+09 | 0.00 | 0.00 |
August | 0.152428E+10 | 0.213249E+09 | 0.119251E+10 | 0.588470E+09 | 0.604039E+09 | 0.00 | 0.00 |
September | 0.125623E+10 | 0.323205E+09 | 0.105342E+10 | 0.534400E+09 | 0.519023E+09 | 0.00 | 0.00 |
October | 0.790287E+09 | 0.483565E+09 | 0.766839E+09 | 0.394173E+09 | 0.372666E+09 | 0.00 | 0.00 |
November | 0.316177E+09 | 0.607695E+09 | 0.406719E+09 | 0.181107E+09 | 0.225612E+09 | 0.00 | 0.00 |
December | 0.307480E+09 | 0.799309E+09 | 0.402310E+09 | 0.213286E+09 | 0.189024E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110120E+11 | 0.572129E+10 | 0.102178E+11 | 0.461131E+10 | 0.560652E+10 | 0.00 | 0.00 |
Minimum of Months | 0.260365E+09 | 0.213249E+09 | 0.398972E+09 | 0.181107E+09 | 0.189024E+09 | 0.00 | 0.00 |
Maximum of Months | 0.167158E+10 | 0.802986E+09 | 0.133520E+10 | 0.642045E+09 | 0.743379E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 71868377.36 | 0.840379E+09 | 0.219099E+09 | 49599010.86 | 0.169500E+09 | 0.00 | 0.00 |
February | 0.206139E+09 | 0.654637E+09 | 0.342238E+09 | 0.100850E+09 | 0.241388E+09 | 0.00 | 0.00 |
March | 0.419348E+09 | 0.577337E+09 | 0.536713E+09 | 0.140864E+09 | 0.395849E+09 | 0.00 | 0.00 |
April | 0.747580E+09 | 0.434779E+09 | 0.777685E+09 | 0.234962E+09 | 0.542723E+09 | 0.00 | 0.00 |
May | 0.110142E+10 | 0.351994E+09 | 0.103498E+10 | 0.338871E+09 | 0.696105E+09 | 0.00 | 0.00 |
June | 0.108475E+10 | 0.243425E+09 | 0.980806E+09 | 0.308662E+09 | 0.672144E+09 | 0.00 | 0.00 |
July | 0.143963E+10 | 0.215411E+09 | 0.118742E+10 | 0.526467E+09 | 0.660954E+09 | 0.00 | 0.00 |
August | 0.121035E+10 | 0.204108E+09 | 0.978987E+09 | 0.414081E+09 | 0.564907E+09 | 0.00 | 0.00 |
September | 0.859364E+09 | 0.319418E+09 | 0.766639E+09 | 0.304886E+09 | 0.461753E+09 | 0.00 | 0.00 |
October | 0.410583E+09 | 0.485386E+09 | 0.468540E+09 | 0.153917E+09 | 0.314622E+09 | 0.00 | 0.00 |
November | 0.118368E+09 | 0.623162E+09 | 0.236818E+09 | 51011659.85 | 0.185807E+09 | 0.00 | 0.00 |
December | 85565422.92 | 0.829254E+09 | 0.201013E+09 | 54332932.01 | 0.146680E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.775497E+10 | 0.577929E+10 | 0.773094E+10 | 0.267850E+10 | 0.505243E+10 | 0.00 | 0.00 |
Minimum of Months | 71868377.36 | 0.204108E+09 | 0.201013E+09 | 49599010.86 | 0.146680E+09 | 0.00 | 0.00 |
Maximum of Months | 0.143963E+10 | 0.840379E+09 | 0.118742E+10 | 0.526467E+09 | 0.696105E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.167193E+09 | 0.207802E+09 | 0.185756E+09 | 0.110502E+09 | 75253821.84 | 0.00 | 0.00 |
February | 0.259886E+09 | 0.174476E+09 | 0.258189E+09 | 0.160192E+09 | 97996810.64 | 0.00 | 0.00 |
March | 0.316258E+09 | 0.174673E+09 | 0.303231E+09 | 0.160319E+09 | 0.142912E+09 | 0.00 | 0.00 |
April | 0.340972E+09 | 0.142549E+09 | 0.310079E+09 | 0.133077E+09 | 0.177001E+09 | 0.00 | 0.00 |
May | 0.335612E+09 | 0.118704E+09 | 0.298531E+09 | 91012766.08 | 0.207518E+09 | 0.00 | 0.00 |
June | 0.301636E+09 | 86702668.08 | 0.261389E+09 | 69957827.29 | 0.191432E+09 | 0.00 | 0.00 |
July | 0.372993E+09 | 77864247.90 | 0.293453E+09 | 0.106552E+09 | 0.186901E+09 | 0.00 | 0.00 |
August | 0.408430E+09 | 74510772.35 | 0.312846E+09 | 0.143750E+09 | 0.169096E+09 | 0.00 | 0.00 |
September | 0.410448E+09 | 0.107283E+09 | 0.335791E+09 | 0.183654E+09 | 0.152136E+09 | 0.00 | 0.00 |
October | 0.348483E+09 | 0.153570E+09 | 0.313877E+09 | 0.192166E+09 | 0.121711E+09 | 0.00 | 0.00 |
November | 0.174230E+09 | 0.168569E+09 | 0.181786E+09 | 0.104056E+09 | 77730558.02 | 0.00 | 0.00 |
December | 0.192232E+09 | 0.212447E+09 | 0.196599E+09 | 0.127137E+09 | 69461416.07 | 0.00 | 0.00 |
Annual Sum or Average | 0.362837E+10 | 0.169915E+10 | 0.325153E+10 | 0.158238E+10 | 0.166915E+10 | 0.00 | 0.00 |
Minimum of Months | 0.167193E+09 | 74510772.35 | 0.181786E+09 | 69957827.29 | 69461416.07 | 0.00 | 0.00 |
Maximum of Months | 0.410448E+09 | 0.212447E+09 | 0.335791E+09 | 0.192166E+09 | 0.207518E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1555799.76 | 0.256393E+09 | 41900326.30 | 0.00 | 41900326.30 | 0.00 | 0.00 |
February | 12777256.57 | 0.197670E+09 | 58888587.20 | 0.00 | 58888587.20 | 0.00 | 0.00 |
March | 46404376.91 | 0.169845E+09 | 96068061.79 | 313.23 | 96067748.57 | 0.00 | 0.00 |
April | 96868844.55 | 0.123006E+09 | 0.132017E+09 | 812222.38 | 0.131204E+09 | 0.00 | 0.00 |
May | 0.159484E+09 | 95849072.38 | 0.175017E+09 | 5255038.69 | 0.169762E+09 | 0.00 | 0.00 |
June | 0.181314E+09 | 64868075.65 | 0.178249E+09 | 11924704.54 | 0.166324E+09 | 0.00 | 0.00 |
July | 0.201509E+09 | 55244769.76 | 0.175314E+09 | 14113260.42 | 0.161201E+09 | 0.00 | 0.00 |
August | 0.169389E+09 | 51982203.16 | 0.142110E+09 | 4267924.75 | 0.137842E+09 | 0.00 | 0.00 |
September | 97742540.14 | 87309432.59 | 0.106444E+09 | 79737.34 | 0.106364E+09 | 0.00 | 0.00 |
October | 41899247.52 | 0.141372E+09 | 75309952.72 | 0.00 | 75309952.72 | 0.00 | 0.00 |
November | 8279606.33 | 0.187801E+09 | 45907539.48 | 0.00 | 45907539.48 | 0.00 | 0.00 |
December | 890258.19 | 0.250013E+09 | 35604474.90 | 0.00 | 35604474.90 | 0.00 | 0.00 |
Annual Sum or Average | 0.101811E+10 | 0.168135E+10 | 0.126283E+10 | 36453201.35 | 0.122638E+10 | 0.00 | 0.00 |
Minimum of Months | 890258.19 | 51982203.16 | 35604474.90 | 0.00 | 35604474.90 | 0.00 | 0.00 |
Maximum of Months | 0.201509E+09 | 0.256393E+09 | 0.178249E+09 | 14113260.42 | 0.169762E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.244543E+09 | 0.798595E+09 | 0.388716E+09 | 0.177368E+09 | 0.211348E+09 | 0.00 | 0.00 |
February | 0.482629E+09 | 0.627107E+09 | 0.583153E+09 | 0.292498E+09 | 0.290655E+09 | 0.00 | 0.00 |
March | 0.756406E+09 | 0.563526E+09 | 0.811112E+09 | 0.357088E+09 | 0.454024E+09 | 0.00 | 0.00 |
April | 0.107811E+10 | 0.426887E+09 | 0.103337E+10 | 0.434321E+09 | 0.599046E+09 | 0.00 | 0.00 |
May | 0.118501E+10 | 0.351938E+09 | 0.108366E+10 | 0.361145E+09 | 0.722516E+09 | 0.00 | 0.00 |
June | 0.132832E+10 | 0.245416E+09 | 0.114966E+10 | 0.445607E+09 | 0.704053E+09 | 0.00 | 0.00 |
July | 0.142827E+10 | 0.209706E+09 | 0.115987E+10 | 0.489740E+09 | 0.670134E+09 | 0.00 | 0.00 |
August | 0.148029E+10 | 0.199659E+09 | 0.116956E+10 | 0.569108E+09 | 0.600453E+09 | 0.00 | 0.00 |
September | 0.114148E+10 | 0.310763E+09 | 0.977694E+09 | 0.487360E+09 | 0.490334E+09 | 0.00 | 0.00 |
October | 0.787829E+09 | 0.477002E+09 | 0.769368E+09 | 0.401318E+09 | 0.368051E+09 | 0.00 | 0.00 |
November | 0.311443E+09 | 0.602866E+09 | 0.405794E+09 | 0.180647E+09 | 0.225147E+09 | 0.00 | 0.00 |
December | 0.295468E+09 | 0.792096E+09 | 0.396697E+09 | 0.207455E+09 | 0.189242E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105198E+11 | 0.560556E+10 | 0.992866E+10 | 0.440365E+10 | 0.552500E+10 | 0.00 | 0.00 |
Minimum of Months | 0.244543E+09 | 0.199659E+09 | 0.388716E+09 | 0.177368E+09 | 0.189242E+09 | 0.00 | 0.00 |
Maximum of Months | 0.148029E+10 | 0.798595E+09 | 0.116956E+10 | 0.569108E+09 | 0.722516E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 50086460.34 | 0.830530E+09 | 0.208843E+09 | 39212816.39 | 0.169630E+09 | 0.00 | 0.00 |
February | 0.180563E+09 | 0.638509E+09 | 0.333954E+09 | 92217704.15 | 0.241736E+09 | 0.00 | 0.00 |
March | 0.418774E+09 | 0.558951E+09 | 0.552067E+09 | 0.156651E+09 | 0.395417E+09 | 0.00 | 0.00 |
April | 0.769224E+09 | 0.419369E+09 | 0.810690E+09 | 0.268956E+09 | 0.541734E+09 | 0.00 | 0.00 |
May | 0.955455E+09 | 0.344142E+09 | 0.929166E+09 | 0.253925E+09 | 0.675242E+09 | 0.00 | 0.00 |
June | 0.116425E+10 | 0.239036E+09 | 0.104564E+10 | 0.373046E+09 | 0.672594E+09 | 0.00 | 0.00 |
July | 0.119912E+10 | 0.202933E+09 | 0.101210E+10 | 0.374162E+09 | 0.637935E+09 | 0.00 | 0.00 |
August | 0.116941E+10 | 0.195249E+09 | 0.956040E+09 | 0.394718E+09 | 0.561321E+09 | 0.00 | 0.00 |
September | 0.741627E+09 | 0.305185E+09 | 0.690909E+09 | 0.257846E+09 | 0.433063E+09 | 0.00 | 0.00 |
October | 0.401583E+09 | 0.472754E+09 | 0.471069E+09 | 0.161062E+09 | 0.310007E+09 | 0.00 | 0.00 |
November | 0.108141E+09 | 0.612590E+09 | 0.235893E+09 | 50551984.52 | 0.185341E+09 | 0.00 | 0.00 |
December | 63992017.26 | 0.812508E+09 | 0.195400E+09 | 48501623.07 | 0.146898E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.722223E+10 | 0.563176E+10 | 0.744177E+10 | 0.247085E+10 | 0.497092E+10 | 0.00 | 0.00 |
Minimum of Months | 50086460.34 | 0.195249E+09 | 0.195400E+09 | 39212816.39 | 0.146898E+09 | 0.00 | 0.00 |
Maximum of Months | 0.119912E+10 | 0.830530E+09 | 0.104564E+10 | 0.394718E+09 | 0.675242E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.314373E+09 | 0.104084E+10 | 0.493252E+09 | 0.239428E+09 | 0.253824E+09 | 0.00 | 0.00 |
February | 0.561674E+09 | 0.812771E+09 | 0.686996E+09 | 0.347092E+09 | 0.339904E+09 | 0.00 | 0.00 |
March | 0.789756E+09 | 0.743228E+09 | 0.865133E+09 | 0.347366E+09 | 0.517766E+09 | 0.00 | 0.00 |
April | 0.961448E+09 | 0.575484E+09 | 0.957846E+09 | 0.290101E+09 | 0.667746E+09 | 0.00 | 0.00 |
May | 0.107012E+10 | 0.475435E+09 | 0.102598E+10 | 0.208584E+09 | 0.817395E+09 | 0.00 | 0.00 |
June | 0.103644E+10 | 0.338437E+09 | 0.952505E+09 | 0.177412E+09 | 0.775093E+09 | 0.00 | 0.00 |
July | 0.122288E+10 | 0.307571E+09 | 0.101562E+10 | 0.261443E+09 | 0.754179E+09 | 0.00 | 0.00 |
August | 0.122852E+10 | 0.303456E+09 | 0.985709E+09 | 0.320713E+09 | 0.664996E+09 | 0.00 | 0.00 |
September | 0.109723E+10 | 0.444421E+09 | 0.958159E+09 | 0.398101E+09 | 0.560058E+09 | 0.00 | 0.00 |
October | 0.847519E+09 | 0.634252E+09 | 0.843231E+09 | 0.416370E+09 | 0.426860E+09 | 0.00 | 0.00 |
November | 0.375884E+09 | 0.786917E+09 | 0.493331E+09 | 0.225460E+09 | 0.267872E+09 | 0.00 | 0.00 |
December | 0.378932E+09 | 0.103105E+10 | 0.503106E+09 | 0.275471E+09 | 0.227635E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.988477E+10 | 0.749387E+10 | 0.978087E+10 | 0.350754E+10 | 0.627333E+10 | 0.00 | 0.00 |
Minimum of Months | 0.314373E+09 | 0.303456E+09 | 0.493252E+09 | 0.177412E+09 | 0.227635E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122852E+10 | 0.104084E+10 | 0.102598E+10 | 0.416370E+09 | 0.817395E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.261787E+09 | 0.797124E+09 | 0.398972E+09 | 0.187754E+09 | 0.211218E+09 | 0.00 | 0.00 |
February | 0.497969E+09 | 0.627646E+09 | 0.591438E+09 | 0.301130E+09 | 0.290308E+09 | 0.00 | 0.00 |
March | 0.747050E+09 | 0.569396E+09 | 0.795758E+09 | 0.341302E+09 | 0.454457E+09 | 0.00 | 0.00 |
April | 0.104635E+10 | 0.438874E+09 | 0.100036E+10 | 0.400327E+09 | 0.600035E+09 | 0.00 | 0.00 |
May | 0.132064E+10 | 0.359031E+09 | 0.118947E+10 | 0.446091E+09 | 0.743379E+09 | 0.00 | 0.00 |
June | 0.124025E+10 | 0.251690E+09 | 0.108483E+10 | 0.381223E+09 | 0.703603E+09 | 0.00 | 0.00 |
July | 0.165835E+10 | 0.223053E+09 | 0.133520E+10 | 0.642045E+09 | 0.693153E+09 | 0.00 | 0.00 |
August | 0.151494E+10 | 0.209167E+09 | 0.119251E+10 | 0.588470E+09 | 0.604039E+09 | 0.00 | 0.00 |
September | 0.125073E+10 | 0.317894E+09 | 0.105342E+10 | 0.534400E+09 | 0.519023E+09 | 0.00 | 0.00 |
October | 0.788228E+09 | 0.476344E+09 | 0.766839E+09 | 0.394173E+09 | 0.372666E+09 | 0.00 | 0.00 |
November | 0.317405E+09 | 0.600499E+09 | 0.406719E+09 | 0.181107E+09 | 0.225612E+09 | 0.00 | 0.00 |
December | 0.308918E+09 | 0.791128E+09 | 0.402310E+09 | 0.213286E+09 | 0.189024E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109526E+11 | 0.566185E+10 | 0.102178E+11 | 0.461131E+10 | 0.560652E+10 | 0.00 | 0.00 |
Minimum of Months | 0.261787E+09 | 0.209167E+09 | 0.398972E+09 | 0.181107E+09 | 0.189024E+09 | 0.00 | 0.00 |
Maximum of Months | 0.165835E+10 | 0.797124E+09 | 0.133520E+10 | 0.642045E+09 | 0.743379E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 72968316.51 | 0.833679E+09 | 0.219099E+09 | 49599010.86 | 0.169500E+09 | 0.00 | 0.00 |
February | 0.207463E+09 | 0.648985E+09 | 0.342238E+09 | 0.100850E+09 | 0.241388E+09 | 0.00 | 0.00 |
March | 0.419651E+09 | 0.570563E+09 | 0.536713E+09 | 0.140864E+09 | 0.395849E+09 | 0.00 | 0.00 |
April | 0.743196E+09 | 0.430816E+09 | 0.777685E+09 | 0.234962E+09 | 0.542723E+09 | 0.00 | 0.00 |
May | 0.109256E+10 | 0.348580E+09 | 0.103498E+10 | 0.338871E+09 | 0.696105E+09 | 0.00 | 0.00 |
June | 0.107524E+10 | 0.240595E+09 | 0.980806E+09 | 0.308662E+09 | 0.672144E+09 | 0.00 | 0.00 |
July | 0.142846E+10 | 0.212680E+09 | 0.118742E+10 | 0.526467E+09 | 0.660954E+09 | 0.00 | 0.00 |
August | 0.120369E+10 | 0.199743E+09 | 0.978987E+09 | 0.414081E+09 | 0.564907E+09 | 0.00 | 0.00 |
September | 0.856357E+09 | 0.313095E+09 | 0.766639E+09 | 0.304886E+09 | 0.461753E+09 | 0.00 | 0.00 |
October | 0.412262E+09 | 0.475943E+09 | 0.468540E+09 | 0.153917E+09 | 0.314622E+09 | 0.00 | 0.00 |
November | 0.120272E+09 | 0.614827E+09 | 0.236818E+09 | 51011659.85 | 0.185807E+09 | 0.00 | 0.00 |
December | 87202517.29 | 0.819445E+09 | 0.201013E+09 | 54332932.01 | 0.146680E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.771933E+10 | 0.570895E+10 | 0.773094E+10 | 0.267850E+10 | 0.505243E+10 | 0.00 | 0.00 |
Minimum of Months | 72968316.51 | 0.199743E+09 | 0.201013E+09 | 49599010.86 | 0.146680E+09 | 0.00 | 0.00 |
Maximum of Months | 0.142846E+10 | 0.833679E+09 | 0.118742E+10 | 0.526467E+09 | 0.696105E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.294105E+09 | 0.415268E+09 | 0.340604E+09 | 0.202618E+09 | 0.137986E+09 | 0.00 | 0.00 |
February | 0.465710E+09 | 0.330155E+09 | 0.473418E+09 | 0.293730E+09 | 0.179688E+09 | 0.00 | 0.00 |
March | 0.577355E+09 | 0.302779E+09 | 0.556007E+09 | 0.293962E+09 | 0.262045E+09 | 0.00 | 0.00 |
April | 0.627598E+09 | 0.234700E+09 | 0.568563E+09 | 0.244012E+09 | 0.324552E+09 | 0.00 | 0.00 |
May | 0.620770E+09 | 0.188740E+09 | 0.547388E+09 | 0.166882E+09 | 0.380507E+09 | 0.00 | 0.00 |
June | 0.561797E+09 | 0.131357E+09 | 0.479286E+09 | 0.128275E+09 | 0.351011E+09 | 0.00 | 0.00 |
July | 0.691661E+09 | 0.113774E+09 | 0.538079E+09 | 0.195375E+09 | 0.342704E+09 | 0.00 | 0.00 |
August | 0.756522E+09 | 0.106486E+09 | 0.573638E+09 | 0.263582E+09 | 0.310056E+09 | 0.00 | 0.00 |
September | 0.758219E+09 | 0.165026E+09 | 0.615709E+09 | 0.336751E+09 | 0.278959E+09 | 0.00 | 0.00 |
October | 0.640534E+09 | 0.252291E+09 | 0.575528E+09 | 0.352358E+09 | 0.223170E+09 | 0.00 | 0.00 |
November | 0.314121E+09 | 0.316208E+09 | 0.333325E+09 | 0.190797E+09 | 0.142527E+09 | 0.00 | 0.00 |
December | 0.343439E+09 | 0.413417E+09 | 0.360485E+09 | 0.233120E+09 | 0.127365E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.665183E+10 | 0.297020E+10 | 0.596203E+10 | 0.290146E+10 | 0.306057E+10 | 0.00 | 0.00 |
Minimum of Months | 0.294105E+09 | 0.106486E+09 | 0.333325E+09 | 0.128275E+09 | 0.127365E+09 | 0.00 | 0.00 |
Maximum of Months | 0.758219E+09 | 0.415268E+09 | 0.615709E+09 | 0.352358E+09 | 0.380507E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 3577324.80 | 0.267900E+10 | 0.366565E+09 | 0.00 | 0.366565E+09 | 0.00 | 0.00 |
February | 63952774.15 | 0.208660E+10 | 0.515187E+09 | 0.00 | 0.515187E+09 | 0.00 | 0.00 |
March | 0.293688E+09 | 0.181902E+10 | 0.840452E+09 | 2740.29 | 0.840450E+09 | 0.00 | 0.00 |
April | 0.686272E+09 | 0.133635E+10 | 0.115495E+10 | 7105734.80 | 0.114784E+10 | 0.00 | 0.00 |
May | 0.118780E+10 | 0.105663E+10 | 0.153114E+10 | 45973752.97 | 0.148517E+10 | 0.00 | 0.00 |
June | 0.135962E+10 | 0.750649E+09 | 0.155941E+10 | 0.104323E+09 | 0.145509E+10 | 0.00 | 0.00 |
July | 0.153341E+10 | 0.671359E+09 | 0.153374E+10 | 0.123470E+09 | 0.141027E+10 | 0.00 | 0.00 |
August | 0.126643E+10 | 0.655939E+09 | 0.124325E+10 | 37337977.86 | 0.120591E+10 | 0.00 | 0.00 |
September | 0.701271E+09 | 0.998509E+09 | 0.931226E+09 | 697582.85 | 0.930528E+09 | 0.00 | 0.00 |
October | 0.256768E+09 | 0.156141E+10 | 0.658850E+09 | 0.00 | 0.658850E+09 | 0.00 | 0.00 |
November | 36596906.24 | 0.202803E+10 | 0.401623E+09 | 0.00 | 0.401623E+09 | 0.00 | 0.00 |
December | 1092167.38 | 0.262098E+10 | 0.311486E+09 | 0.00 | 0.311486E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.739049E+10 | 0.182645E+11 | 0.110479E+11 | 0.318911E+09 | 0.107290E+11 | 0.00 | 0.00 |
Minimum of Months | 1092167.38 | 0.655939E+09 | 0.311486E+09 | 0.00 | 0.311486E+09 | 0.00 | 0.00 |
Maximum of Months | 0.153341E+10 | 0.267900E+10 | 0.155941E+10 | 0.123470E+09 | 0.148517E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 2234891.62 | 0.276547E+10 | 0.366565E+09 | 0.00 | 0.366565E+09 | 0.00 | 0.00 |
February | 55961551.98 | 0.215421E+10 | 0.515187E+09 | 0.00 | 0.515187E+09 | 0.00 | 0.00 |
March | 0.271154E+09 | 0.187050E+10 | 0.840452E+09 | 2740.29 | 0.840450E+09 | 0.00 | 0.00 |
April | 0.658522E+09 | 0.137095E+10 | 0.115495E+10 | 7105734.80 | 0.114784E+10 | 0.00 | 0.00 |
May | 0.115892E+10 | 0.108120E+10 | 0.153114E+10 | 45973752.97 | 0.148517E+10 | 0.00 | 0.00 |
June | 0.133170E+10 | 0.768873E+09 | 0.155941E+10 | 0.104323E+09 | 0.145509E+10 | 0.00 | 0.00 |
July | 0.150908E+10 | 0.688291E+09 | 0.153374E+10 | 0.123470E+09 | 0.141027E+10 | 0.00 | 0.00 |
August | 0.124281E+10 | 0.674575E+09 | 0.124325E+10 | 37337977.86 | 0.120591E+10 | 0.00 | 0.00 |
September | 0.679986E+09 | 0.102524E+10 | 0.931226E+09 | 697582.85 | 0.930528E+09 | 0.00 | 0.00 |
October | 0.236803E+09 | 0.161062E+10 | 0.658850E+09 | 0.00 | 0.658850E+09 | 0.00 | 0.00 |
November | 30766388.63 | 0.210046E+10 | 0.401623E+09 | 0.00 | 0.401623E+09 | 0.00 | 0.00 |
December | 668539.84 | 0.270744E+10 | 0.311486E+09 | 0.00 | 0.311486E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.717860E+10 | 0.188178E+11 | 0.110479E+11 | 0.318911E+09 | 0.107290E+11 | 0.00 | 0.00 |
Minimum of Months | 668539.84 | 0.674575E+09 | 0.311486E+09 | 0.00 | 0.311486E+09 | 0.00 | 0.00 |
Maximum of Months | 0.150908E+10 | 0.276547E+10 | 0.155941E+10 | 0.123470E+09 | 0.148517E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.294135E+09 | 0.173791E+10 | 0.597536E+09 | 0.216575E+09 | 0.380961E+09 | 0.00 | 0.00 |
February | 0.697456E+09 | 0.135892E+10 | 0.917070E+09 | 0.384702E+09 | 0.532367E+09 | 0.00 | 0.00 |
March | 0.127394E+10 | 0.123248E+10 | 0.136312E+10 | 0.513717E+09 | 0.849402E+09 | 0.00 | 0.00 |
April | 0.202444E+10 | 0.949860E+09 | 0.184397E+10 | 0.703239E+09 | 0.114073E+10 | 0.00 | 0.00 |
May | 0.237228E+10 | 0.796308E+09 | 0.201273E+10 | 0.615035E+09 | 0.139769E+10 | 0.00 | 0.00 |
June | 0.275877E+10 | 0.589557E+09 | 0.219518E+10 | 0.818602E+09 | 0.137658E+10 | 0.00 | 0.00 |
July | 0.292619E+10 | 0.517257E+09 | 0.217186E+10 | 0.863852E+09 | 0.130801E+10 | 0.00 | 0.00 |
August | 0.294962E+10 | 0.498270E+09 | 0.212549E+10 | 0.963771E+09 | 0.116172E+10 | 0.00 | 0.00 |
September | 0.211863E+10 | 0.675836E+09 | 0.166852E+10 | 0.745168E+09 | 0.923355E+09 | 0.00 | 0.00 |
October | 0.130645E+10 | 0.104806E+10 | 0.124038E+10 | 0.562357E+09 | 0.678027E+09 | 0.00 | 0.00 |
November | 0.458527E+09 | 0.132087E+10 | 0.641662E+09 | 0.231192E+09 | 0.410470E+09 | 0.00 | 0.00 |
December | 0.372997E+09 | 0.171839E+10 | 0.592075E+09 | 0.255949E+09 | 0.336126E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.195534E+11 | 0.124437E+11 | 0.173696E+11 | 0.687416E+10 | 0.104954E+11 | 0.00 | 0.00 |
Minimum of Months | 0.294135E+09 | 0.498270E+09 | 0.592075E+09 | 0.216575E+09 | 0.336126E+09 | 0.00 | 0.00 |
Maximum of Months | 0.294962E+10 | 0.173791E+10 | 0.219518E+10 | 0.963771E+09 | 0.139769E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.687792E+09 | 0.187055E+10 | 0.992685E+09 | 0.515775E+09 | 0.476910E+09 | 0.00 | 0.00 |
February | 0.118176E+10 | 0.146196E+10 | 0.138172E+10 | 0.747705E+09 | 0.634012E+09 | 0.00 | 0.00 |
March | 0.159393E+10 | 0.133969E+10 | 0.170345E+10 | 0.748296E+09 | 0.955158E+09 | 0.00 | 0.00 |
April | 0.186892E+10 | 0.104156E+10 | 0.184323E+10 | 0.623580E+09 | 0.121965E+10 | 0.00 | 0.00 |
May | 0.199911E+10 | 0.860229E+09 | 0.191828E+10 | 0.440567E+09 | 0.147772E+10 | 0.00 | 0.00 |
June | 0.188508E+10 | 0.622338E+09 | 0.175462E+10 | 0.362294E+09 | 0.139232E+10 | 0.00 | 0.00 |
July | 0.225436E+10 | 0.568015E+09 | 0.189548E+10 | 0.539664E+09 | 0.135581E+10 | 0.00 | 0.00 |
August | 0.233770E+10 | 0.554758E+09 | 0.188641E+10 | 0.683762E+09 | 0.120265E+10 | 0.00 | 0.00 |
September | 0.217673E+10 | 0.793967E+09 | 0.188655E+10 | 0.857456E+09 | 0.102909E+10 | 0.00 | 0.00 |
October | 0.173530E+10 | 0.113393E+10 | 0.169089E+10 | 0.896945E+09 | 0.793947E+09 | 0.00 | 0.00 |
November | 0.789361E+09 | 0.142359E+10 | 0.986173E+09 | 0.485685E+09 | 0.500488E+09 | 0.00 | 0.00 |
December | 0.824922E+09 | 0.185172E+10 | 0.102441E+10 | 0.593419E+09 | 0.430993E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.193350E+11 | 0.135223E+11 | 0.189639E+11 | 0.749515E+10 | 0.114688E+11 | 0.00 | 0.00 |
Minimum of Months | 0.687792E+09 | 0.554758E+09 | 0.986173E+09 | 0.362294E+09 | 0.430993E+09 | 0.00 | 0.00 |
Maximum of Months | 0.233770E+10 | 0.187055E+10 | 0.191828E+10 | 0.896945E+09 | 0.147772E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770454E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161747520.4 | 81.21 | 0.00 | 0.00 |
February | 0.696210E+10 | -0.681598E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146125333.0 | 81.21 | 0.00 | 0.00 |
March | 0.770293E+10 | -0.754145E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161481800.9 | 81.21 | 0.00 | 0.00 |
April | 0.746488E+10 | -0.730858E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156303825.7 | 81.21 | 0.00 | 0.00 |
May | 0.770436E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161576234.4 | 81.21 | 0.00 | 0.00 |
June | 0.745695E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156422948.1 | 81.21 | 0.00 | 0.00 |
July | 0.771243E+10 | -0.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161584127.6 | 81.21 | 0.00 | 0.00 |
August | 0.770434E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161543930.1 | 81.21 | 0.00 | 0.00 |
September | 0.746632E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156394914.9 | 81.21 | 0.00 | 0.00 |
October | 0.770298E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161552461.4 | 81.21 | 0.00 | 0.00 |
November | 0.744881E+10 | -0.729242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156383624.2 | 81.21 | 0.00 | 0.00 |
December | 0.771248E+10 | -0.755087E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161613397.7 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907431E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190273E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696210E+10 | -0.755087E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161747520.4 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771248E+10 | -0.681598E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146125333.0 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.119920E+12 | -0.118179E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174095E+10 | 81.26 | 0.00 | 0.00 |
February | 0.108835E+12 | -0.107258E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.157708E+10 | 81.26 | 0.00 | 0.00 |
March | 0.119570E+12 | -0.117820E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175020E+10 | 81.26 | 0.00 | 0.00 |
April | 0.113558E+12 | -0.111860E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169778E+10 | 81.26 | 0.00 | 0.00 |
May | 0.114398E+12 | -0.112645E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175273E+10 | 81.26 | 0.00 | 0.00 |
June | 0.107938E+12 | -0.106245E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169290E+10 | 81.25 | 0.00 | 0.00 |
July | 0.109524E+12 | -0.107781E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174303E+10 | 81.25 | 0.00 | 0.00 |
August | 0.108901E+12 | -0.107162E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173912E+10 | 81.25 | 0.00 | 0.00 |
September | 0.106308E+12 | -0.104630E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167842E+10 | 81.25 | 0.00 | 0.00 |
October | 0.112106E+12 | -0.110374E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173215E+10 | 81.25 | 0.00 | 0.00 |
November | 0.111341E+12 | -0.109665E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167542E+10 | 81.25 | 0.00 | 0.00 |
December | 0.117904E+12 | -0.116168E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173516E+10 | 81.26 | 0.00 | 0.00 |
Annual Sum or Average | 0.135030E+13 | -0.132979E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205150E+11 | 81.26 | 0.00 | 0.00 |
Minimum of Months | 0.106308E+12 | -0.118179E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.175273E+10 | 81.25 | 0.00 | 0.00 |
Maximum of Months | 0.119920E+12 | -0.104630E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157708E+10 | 81.26 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.709010E+11 | -0.694184E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148253E+10 | 58.99 | 0.00 | 0.00 |
February | 0.644948E+11 | -0.631493E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.134543E+10 | 58.99 | 0.00 | 0.00 |
March | 0.706687E+11 | -0.691733E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149536E+10 | 58.98 | 0.00 | 0.00 |
April | 0.665076E+11 | -0.650548E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145277E+10 | 58.98 | 0.00 | 0.00 |
May | 0.662035E+11 | -0.647045E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149899E+10 | 58.98 | 0.00 | 0.00 |
June | 0.617044E+11 | -0.602583E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.144613E+10 | 58.98 | 0.00 | 0.00 |
July | 0.619657E+11 | -0.604799E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148585E+10 | 58.98 | 0.00 | 0.00 |
August | 0.614894E+11 | -0.600091E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148025E+10 | 58.98 | 0.00 | 0.00 |
September | 0.602628E+11 | -0.588367E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142615E+10 | 58.98 | 0.00 | 0.00 |
October | 0.641850E+11 | -0.627143E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147070E+10 | 58.98 | 0.00 | 0.00 |
November | 0.645664E+11 | -0.631443E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142205E+10 | 58.99 | 0.00 | 0.00 |
December | 0.691667E+11 | -0.676921E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147451E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.782116E+12 | -0.764635E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.174807E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.602628E+11 | -0.694184E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.149899E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.709010E+11 | -0.588367E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.134543E+10 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.93 | 0.93 | 01-JAN-09:09 | 2337.27 | 32.55 | 223.50 | 222.17 | 1771.36 | 33.51 | 226.67 | 178.00 |
February | 259.50 | 0.93 | 0.93 | 01-FEB-08:20 | 4113.94 | 33.20 | 241.33 | 246.17 | 1773.37 | 29.22 | 210.67 | 213.17 |
March | 247.00 | 0.93 | 0.93 | 01-MAR-07:19 | 6052.74 | 30.55 | 185.33 | 316.00 | 761.34 | 22.34 | 172.50 | 255.17 |
April | 379.50 | 0.93 | 0.93 | 01-APR-06:49 | 1580.24 | 19.80 | 111.50 | 350.00 | 611.66 | 21.53 | 245.83 | 290.17 |
May | 427.83 | 0.93 | 0.93 | 01-MAY-06:49 | 1456.92 | 19.62 | 116.17 | 389.83 | 557.83 | 21.32 | 261.83 | 318.67 |
June | 375.17 | 0.93 | 0.93 | 01-JUN-05:30 | 1234.60 | 19.62 | 61.50 | 400.17 | 494.97 | 21.36 | 258.50 | 319.67 |
July | 471.00 | 0.94 | 0.93 | 01-JUL-04:00 | 1064.01 | 18.59 | 73.50 | 399.67 | 426.33 | 20.35 | 213.33 | 291.50 |
August | 366.67 | 0.94 | 0.93 | 01-AUG-05:40 | 1230.42 | 19.66 | 56.83 | 378.67 | 500.76 | 21.41 | 244.83 | 303.33 |
September | 301.17 | 0.93 | 0.93 | 01-SEP-07:40 | 3447.48 | 24.86 | 151.83 | 322.33 | 690.00 | 22.39 | 226.33 | 269.83 |
October | 245.33 | 0.93 | 0.93 | 01-OCT-07:19 | 6425.91 | 34.80 | 221.33 | 287.50 | 922.42 | 24.27 | 190.17 | 245.50 |
November | 242.67 | 0.93 | 0.93 | 01-NOV-07:49 | 2638.98 | 32.27 | 226.33 | 229.00 | 1750.20 | 32.57 | 225.00 | 186.50 |
December | 160.33 | 0.93 | 0.93 | 01-DEC-09:39 | 3133.25 | 35.79 | 150.33 | 211.50 | 2555.88 | 36.85 | 150.33 | 154.83 |
Annual Sum or Average | 3714.00 | 0.93 | 2561.79 | 24.97 | 1819.50 | 3753.00 | 909.81 | 24.32 | 2626.00 | 3026.33 | ||
Minimum of Months | 160.33 | 0.93 | 0.93 | 1064.01 | 18.59 | 56.83 | 211.50 | 426.33 | 20.35 | 150.33 | 154.83 | |
Maximum of Months | 471.00 | 0.94 | 0.93 | 6425.91 | 35.79 | 241.33 | 400.17 | 2555.88 | 36.85 | 261.83 | 319.67 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.63 | 0.61 | 01-JAN-09:09 | 2563.36 | 32.65 | 224.33 | 234.17 | 1995.62 | 33.60 | 227.67 | 206.50 |
February | 259.50 | 0.62 | 0.61 | 01-FEB-08:09 | 4422.58 | 33.32 | 242.33 | 254.33 | 2079.62 | 29.33 | 218.00 | 233.00 |
March | 247.00 | 0.62 | 0.61 | 01-MAR-07:10 | 6432.72 | 30.80 | 184.83 | 328.67 | 1138.95 | 22.42 | 177.50 | 291.17 |
April | 379.50 | 0.62 | 0.61 | 01-APR-06:40 | 1869.23 | 20.26 | 116.33 | 362.17 | 899.53 | 21.83 | 257.50 | 328.33 |
May | 427.83 | 0.62 | 0.61 | 01-MAY-06:40 | 1709.19 | 20.19 | 138.83 | 405.00 | 809.09 | 21.72 | 291.00 | 366.50 |
June | 375.17 | 0.63 | 0.61 | 01-JUN-05:10 | 1468.57 | 20.16 | 118.83 | 418.50 | 728.20 | 21.73 | 293.83 | 371.50 |
July | 471.00 | 0.64 | 0.61 | 01-JUL-04:00 | 1287.41 | 19.16 | 106.33 | 419.00 | 649.09 | 20.74 | 236.00 | 368.00 |
August | 366.67 | 0.63 | 0.61 | 01-AUG-05:40 | 1512.61 | 20.01 | 87.33 | 394.33 | 782.18 | 21.59 | 247.83 | 352.67 |
September | 301.17 | 0.62 | 0.61 | 01-SEP-07:40 | 3813.41 | 25.05 | 158.33 | 332.17 | 1054.95 | 22.47 | 226.33 | 304.50 |
October | 245.33 | 0.63 | 0.61 | 01-OCT-07:10 | 6811.70 | 34.96 | 221.33 | 300.33 | 1308.51 | 24.26 | 186.83 | 270.17 |
November | 242.67 | 0.62 | 0.61 | 01-NOV-07:49 | 2864.71 | 32.38 | 227.83 | 240.33 | 1974.86 | 32.66 | 224.83 | 213.83 |
December | 160.33 | 0.62 | 0.61 | 01-DEC-09:39 | 3442.21 | 35.93 | 150.33 | 223.83 | 2862.97 | 36.95 | 150.33 | 192.67 |
Annual Sum or Average | 3714.00 | 0.63 | 2844.76 | 25.31 | 1977.00 | 3912.83 | 1191.67 | 24.54 | 2737.67 | 3498.83 | ||
Minimum of Months | 160.33 | 0.62 | 0.61 | 1287.41 | 19.16 | 87.33 | 223.83 | 649.09 | 20.74 | 150.33 | 192.67 | |
Maximum of Months | 471.00 | 0.64 | 0.61 | 6811.70 | 35.93 | 242.33 | 419.00 | 2862.97 | 36.95 | 293.83 | 371.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.82 | 0.80 | 01-JAN-09:30 | 353.73 | 13.79 | 0.00 | 200.17 | 151.23 | 17.04 | 0.00 | 39.33 |
February | 259.50 | 0.81 | 0.80 | 01-FEB-08:39 | 438.80 | 15.06 | 0.00 | 232.17 | 193.94 | 18.34 | 0.00 | 112.83 |
March | 247.00 | 0.81 | 0.80 | 01-MAR-07:40 | 568.80 | 16.42 | 0.00 | 315.00 | 262.57 | 19.68 | 3.17 | 209.83 |
April | 379.50 | 0.81 | 0.80 | 01-APR-06:49 | 681.39 | 17.20 | 0.00 | 361.17 | 304.39 | 20.36 | 55.83 | 305.67 |
May | 427.83 | 0.81 | 0.80 | 01-MAY-06:49 | 851.55 | 18.38 | 17.67 | 409.17 | 376.86 | 21.98 | 199.67 | 367.83 |
June | 375.17 | 0.81 | 0.80 | 01-JUN-04:00 | 885.23 | 19.66 | 40.17 | 427.17 | 412.85 | 23.59 | 229.50 | 392.17 |
July | 471.00 | 0.81 | 0.80 | 01-JUL-04:49 | 742.76 | 18.64 | 48.00 | 435.17 | 347.64 | 22.71 | 212.33 | 341.83 |
August | 366.67 | 0.81 | 0.80 | 01-AUG-05:10 | 633.49 | 17.90 | 13.17 | 400.50 | 296.67 | 21.09 | 89.00 | 336.00 |
September | 301.17 | 0.81 | 0.80 | 01-SEP-07:40 | 606.97 | 17.24 | 0.00 | 325.50 | 288.63 | 20.45 | 28.33 | 256.33 |
October | 245.33 | 0.82 | 0.80 | 01-OCT-07:19 | 456.41 | 15.64 | 0.00 | 276.17 | 218.02 | 18.97 | 0.17 | 150.00 |
November | 242.67 | 0.82 | 0.80 | 01-NOV-07:49 | 382.63 | 14.25 | 0.00 | 212.33 | 162.53 | 17.47 | 0.00 | 54.83 |
December | 160.33 | 0.83 | 0.80 | 01-DEC-09:39 | 320.01 | 13.93 | 0.00 | 180.00 | 151.06 | 17.40 | 0.00 | 28.00 |
Annual Sum or Average | 3714.00 | 0.81 | 623.20 | 16.98 | 119.00 | 3774.50 | 285.24 | 20.44 | 818.00 | 2594.67 | ||
Minimum of Months | 160.33 | 0.81 | 0.80 | 320.01 | 13.79 | 0.00 | 180.00 | 151.06 | 17.04 | 0.00 | 28.00 | |
Maximum of Months | 471.00 | 0.83 | 0.80 | 885.23 | 19.66 | 48.00 | 435.17 | 412.85 | 23.59 | 229.50 | 392.17 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.82 | 0.80 | 01-JAN-09:30 | 353.73 | 13.79 | 0.00 | 200.17 | 151.23 | 17.04 | 0.00 | 39.33 |
February | 259.50 | 0.81 | 0.80 | 01-FEB-08:39 | 438.80 | 15.06 | 0.00 | 232.17 | 193.94 | 18.34 | 0.00 | 112.83 |
March | 247.00 | 0.81 | 0.80 | 01-MAR-07:40 | 568.80 | 16.42 | 0.00 | 315.00 | 262.57 | 19.68 | 3.17 | 209.83 |
April | 379.50 | 0.81 | 0.80 | 01-APR-06:49 | 681.39 | 17.20 | 0.00 | 361.17 | 304.39 | 20.36 | 55.83 | 305.67 |
May | 427.83 | 0.81 | 0.80 | 01-MAY-06:49 | 851.55 | 18.38 | 17.67 | 409.17 | 376.86 | 21.98 | 199.67 | 367.83 |
June | 375.17 | 0.81 | 0.80 | 01-JUN-04:00 | 885.23 | 19.66 | 40.17 | 427.17 | 412.85 | 23.59 | 229.50 | 392.17 |
July | 471.00 | 0.81 | 0.80 | 01-JUL-04:49 | 742.76 | 18.64 | 48.00 | 435.17 | 347.64 | 22.71 | 212.33 | 341.83 |
August | 366.67 | 0.81 | 0.80 | 01-AUG-05:10 | 633.49 | 17.90 | 13.17 | 400.50 | 296.67 | 21.09 | 89.00 | 336.00 |
September | 301.17 | 0.81 | 0.80 | 01-SEP-07:40 | 606.97 | 17.24 | 0.00 | 325.50 | 288.63 | 20.45 | 28.33 | 256.33 |
October | 245.33 | 0.82 | 0.80 | 01-OCT-07:19 | 456.41 | 15.64 | 0.00 | 276.17 | 218.02 | 18.97 | 0.17 | 150.00 |
November | 242.67 | 0.82 | 0.80 | 01-NOV-07:49 | 382.63 | 14.25 | 0.00 | 212.33 | 162.53 | 17.47 | 0.00 | 54.83 |
December | 160.33 | 0.83 | 0.80 | 01-DEC-09:39 | 320.01 | 13.93 | 0.00 | 180.00 | 151.06 | 17.40 | 0.00 | 28.00 |
Annual Sum or Average | 3714.00 | 0.81 | 623.20 | 16.98 | 119.00 | 3774.50 | 285.24 | 20.44 | 818.00 | 2594.67 | ||
Minimum of Months | 160.33 | 0.81 | 0.80 | 320.01 | 13.79 | 0.00 | 180.00 | 151.06 | 17.04 | 0.00 | 28.00 | |
Maximum of Months | 471.00 | 0.83 | 0.80 | 885.23 | 19.66 | 48.00 | 435.17 | 412.85 | 23.59 | 229.50 | 392.17 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.276946E+11 | 127714.88 | 04-JAN-07:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.241989E+11 | 129819.43 | 06-FEB-18:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.315996E+11 | 126750.38 | 03-MAR-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.280330E+11 | 129234.07 | 17-APR-07:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.247354E+11 | 127703.18 | 18-MAY-06:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.847673E+10 | 98891.95 | 15-JUN-03:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.230985E+10 | 38599.78 | 04-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.212188E+10 | 41142.37 | 21-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.879305E+10 | 118111.99 | 28-SEP-05:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.321285E+11 | 125822.33 | 29-OCT-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.314002E+11 | 129085.35 | 22-NOV-23:29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.289281E+11 | 131054.51 | 09-DEC-23:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250420E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.212188E+10 | 38599.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.321285E+11 | 131054.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.344441E+10 | 3167.20 | 23-JAN-18:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.230585E+10 | 3240.13 | 22-FEB-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174886E+10 | 3503.12 | 19-MAR-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102601E+10 | 3501.01 | 23-APR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.678761E+09 | 3292.06 | 18-MAY-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.380445E+09 | 2337.46 | 15-JUN-05:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133412E+09 | 1421.75 | 04-JUL-05:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157734E+09 | 1446.10 | 21-AUG-04:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.473504E+09 | 2721.60 | 27-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122968E+10 | 3554.85 | 18-OCT-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252211E+10 | 3194.74 | 17-NOV-08:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.324743E+10 | 3388.05 | 10-DEC-19:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.133412E+09 | 1421.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.344441E+10 | 3554.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 38637955.13 | 624.57 | 23-JAN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14161598.18 | 324.82 | 15-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 69836.23 | 74.80 | 12-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5819262.45 | 348.58 | 26-NOV-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 43087151.46 | 522.79 | 27-DEC-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43087151.46 | 624.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.552859E+09 | 887.06 | 23-JAN-13:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.296325E+09 | 1040.04 | 20-FEB-18:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10246669.30 | 278.79 | 05-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120182E+09 | 772.13 | 26-NOV-17:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.398522E+09 | 860.25 | 27-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.552859E+09 | 1040.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.557795E+09 | 602.07 | 23-JAN-18:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.314342E+09 | 693.43 | 20-FEB-18:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28196538.72 | 367.02 | 05-MAR-18:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 309292.66 | 190.05 | 18-APR-10:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 327332.84 | 74.88 | 31-OCT-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180446E+09 | 514.29 | 23-NOV-18:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.439873E+09 | 629.14 | 01-DEC-18:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.557795E+09 | 693.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.119192E+09 | 5213.48 | 03-JAN-04:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113104E+09 | 6962.85 | 25-FEB-03:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 94763343.95 | 8160.85 | 15-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107519E+09 | 10760.91 | 29-APR-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.188197E+09 | 11119.84 | 03-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 80018406.21 | 8980.30 | 15-JUN-02:29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12752695.71 | 1665.32 | 03-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10855240.67 | 3300.88 | 22-AUG-03:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 47549436.85 | 7564.33 | 20-SEP-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184510E+09 | 9240.48 | 19-OCT-03:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131142E+09 | 5605.58 | 21-NOV-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122448E+09 | 3656.30 | 28-DEC-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 10855240.67 | 1665.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.188197E+09 | 11119.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.261002E+10 | 7850.07 | 23-JAN-18:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130192E+10 | 7063.91 | 01-FEB-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.781140E+09 | 6732.26 | 21-MAR-09:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.201751E+09 | 7754.81 | 04-APR-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116237E+09 | 5525.84 | 18-MAY-06:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18421055.41 | 3610.19 | 14-JUN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5786985.31 | 1833.42 | 12-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2801322.73 | 1055.50 | 01-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130366E+09 | 5530.79 | 27-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.515123E+09 | 9209.21 | 18-OCT-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167187E+10 | 7538.12 | 21-NOV-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.250335E+10 | 7063.13 | 17-DEC-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.985879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2801322.73 | 1055.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.261002E+10 | 9209.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.316507E+09 | 10857.98 | 23-JAN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 94527512.40 | 5683.44 | 15-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 53986646.09 | 3863.63 | 27-NOV-11:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.419398E+09 | 6785.47 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.884419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.419398E+09 | 10857.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.618682E+10 | 8331.37 | 23-JAN-18:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.306673E+10 | 7629.68 | 04-FEB-09:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.474552E+09 | 7269.09 | 06-MAR-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6832603.37 | 7511.64 | 01-APR-06:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167412E+09 | 3541.44 | 22-OCT-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.295899E+10 | 7785.48 | 21-NOV-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.541585E+10 | 8241.48 | 10-DEC-19:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.618682E+10 | 8331.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.356030E+10 | 4180.78 | 23-JAN-18:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.205834E+10 | 4434.34 | 22-FEB-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.572150E+09 | 3918.29 | 06-MAR-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109184E+09 | 3636.47 | 01-APR-06:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 100783.07 | 335.94 | 27-SEP-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.204348E+09 | 4657.25 | 18-OCT-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171494E+10 | 4334.51 | 17-NOV-08:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.321193E+10 | 4692.03 | 10-DEC-19:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.356030E+10 | 4692.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 448821.33 | 722.52 | 19-MAY-02:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 448821.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 448821.33 | 722.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.757373E+09 | 4621.92 | 07-JAN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.440027E+09 | 5280.68 | 19-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 43850.61 | 66.09 | 01-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10297.38 | 0.72 | 27-APR-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20408.65 | 0.72 | 14-MAY-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39911.50 | 0.72 | 17-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 46517.19 | 0.73 | 05-JUL-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 52882.47 | 0.73 | 26-AUG-01:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 36426.23 | 0.71 | 08-SEP-10:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20022.12 | 0.73 | 01-OCT-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4380454.05 | 581.01 | 11-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229519E+09 | 3441.38 | 26-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 10297.38 | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.757373E+09 | 5280.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.456544E+10 | 8971.41 | 07-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.286690E+10 | 8965.63 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166740E+10 | 8731.97 | 05-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.667621E+09 | 8675.25 | 18-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.186661E+09 | 8044.23 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34676054.99 | 3315.80 | 18-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5647562.44 | 3574.58 | 16-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6767544.63 | 3269.11 | 27-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80109480.90 | 4102.05 | 27-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.906602E+09 | 8534.76 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.278283E+10 | 8794.18 | 13-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.423912E+10 | 8909.85 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5647562.44 | 3269.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.456544E+10 | 8971.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.520019E+10 | 8822.92 | 07-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.355942E+10 | 8827.40 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.216792E+10 | 8616.98 | 24-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.887072E+09 | 8537.61 | 18-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.227164E+09 | 8192.66 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41546205.78 | 3229.56 | 18-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4926397.18 | 3102.81 | 04-JUL-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7417098.72 | 3031.14 | 27-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111305E+09 | 6154.89 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126997E+10 | 8433.49 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.327723E+10 | 8701.90 | 13-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.489437E+10 | 8762.41 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4926397.18 | 3031.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.520019E+10 | 8827.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.618548E+10 | 12741.02 | 05-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161188E+10 | 14878.95 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113513E+10 | 8876.70 | 30-NOV-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.609807E+10 | 13769.80 | 26-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.150306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.618548E+10 | 14878.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.162664E+11 | 47772.53 | 06-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109521E+11 | 47626.83 | 13-FEB-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.370272E+10 | 46743.17 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.833546E+09 | 33024.25 | 25-APR-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108455E+09 | 28183.39 | 12-MAY-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41998868.06 | 26296.04 | 07-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41945229.68 | 22786.71 | 25-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 36856210.73 | 24314.82 | 21-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107068E+09 | 22832.46 | 24-SEP-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125514E+10 | 45543.80 | 31-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.729734E+10 | 47046.93 | 30-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146862E+11 | 47621.61 | 26-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.553298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 36856210.73 | 22786.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.162664E+11 | 47772.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.460209E+10 | 8794.85 | 07-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288877E+10 | 8744.93 | 18-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162520E+10 | 8569.18 | 05-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.636604E+09 | 8518.41 | 18-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.237318E+09 | 7867.92 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40804787.14 | 2807.67 | 02-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5529868.83 | 3279.01 | 16-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6897764.19 | 3190.72 | 27-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101663E+09 | 2719.46 | 06-SEP-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.928745E+09 | 8396.46 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279546E+10 | 8613.11 | 29-NOV-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.427715E+10 | 8758.79 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5529868.83 | 2719.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.460209E+10 | 8794.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.525909E+10 | 8670.88 | 07-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.356929E+10 | 8601.09 | 19-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209056E+10 | 8447.73 | 05-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.816876E+09 | 8380.97 | 18-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.288151E+09 | 8003.79 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 48451711.56 | 2457.70 | 29-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5371160.10 | 3043.91 | 16-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8306331.20 | 3125.13 | 27-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151321E+09 | 4331.45 | 26-SEP-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128720E+10 | 8294.92 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.326964E+10 | 8505.95 | 13-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.491798E+10 | 8611.50 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5371160.10 | 2457.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.525909E+10 | 8670.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160411E+10 | 2665.43 | 07-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104640E+10 | 2666.79 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.667209E+09 | 2618.45 | 05-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.311461E+09 | 2602.04 | 18-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126022E+09 | 2560.59 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34302673.82 | 945.35 | 11-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3935237.25 | 864.38 | 16-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6938661.32 | 936.98 | 19-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 63147690.20 | 2097.56 | 27-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.410802E+09 | 2555.77 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102624E+10 | 2630.40 | 11-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150119E+10 | 2647.19 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.680176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3935237.25 | 864.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.160411E+10 | 2666.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.180514E+10 | 2611.81 | 07-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126479E+10 | 2613.11 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.832176E+09 | 2572.86 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.391825E+09 | 2551.33 | 18-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146201E+09 | 2509.52 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40052726.81 | 777.46 | 12-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4894219.90 | 974.68 | 16-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9358496.51 | 841.19 | 19-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 89011726.37 | 2470.10 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.553313E+09 | 2516.53 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118474E+10 | 2583.31 | 11-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170839E+10 | 2593.95 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.802988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4894219.90 | 777.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.180514E+10 | 2613.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.485306E+10 | 12886.83 | 15-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.274191E+10 | 12840.52 | 17-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143927E+10 | 12575.09 | 05-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.634622E+09 | 12563.92 | 18-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.256116E+09 | 11389.19 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 49920188.94 | 5485.93 | 23-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9992027.01 | 5517.87 | 16-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10877758.84 | 4468.58 | 03-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 90917962.49 | 4828.45 | 21-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.665762E+09 | 12297.19 | 27-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.266544E+10 | 12729.95 | 30-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.452977E+10 | 12948.96 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9992027.01 | 4468.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.485306E+10 | 12948.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.305234E+09 | 0.305234E+09 | 40263.44 | 04-JAN-21:14 | 40263.44 | 0.00 |
February | 0.00 | 0.00 | 0.205599E+10 | 0.205599E+10 | 79742.69 | 27-FEB-15:00 | 79742.69 | 0.02 |
March | 0.00 | 0.00 | 0.420411E+10 | 0.420411E+10 | 102908.53 | 18-MAR-16:10 | 102908.53 | 0.03 |
April | 0.00 | 0.00 | 0.286744E+11 | 0.286744E+11 | 205582.09 | 27-APR-18:10 | 205582.09 | 0.09 |
May | 0.00 | 0.00 | 0.552908E+11 | 0.548583E+11 | 205273.59 | 05-MAY-18:00 | 171688.90 | 0.22 |
June | 0.00 | 0.00 | 0.985683E+11 | 0.984298E+11 | 221214.23 | 28-JUN-18:10 | 210065.17 | 0.42 |
July | 0.00 | 0.00 | 0.167844E+12 | 0.162029E+12 | 271313.52 | 27-JUL-18:40 | 196191.62 | 0.62 |
August | 0.00 | 0.00 | 0.212712E+12 | 0.203226E+12 | 298764.55 | 10-AUG-18:07 | 253018.07 | 0.81 |
September | 0.00 | 0.00 | 0.808736E+11 | 0.786906E+11 | 206178.88 | 14-SEP-17:15 | 181446.27 | 0.50 |
October | 0.00 | 0.00 | 0.149364E+11 | 0.149215E+11 | 126558.28 | 04-OCT-15:03 | 126558.28 | 0.11 |
November | 0.00 | 0.00 | 0.365309E+10 | 0.365309E+10 | 103185.90 | 04-NOV-14:20 | 103185.90 | 0.06 |
December | 0.00 | 0.00 | 0.377485E+09 | 0.377485E+09 | 34606.16 | 12-DEC-22:37 | 34606.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.669495E+12 | 0.651425E+12 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 0.305234E+09 | 0.305234E+09 | 34606.16 | 34606.16 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.212712E+12 | 0.203226E+12 | 298764.55 | 253018.07 | 0.81 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.332455E+09 | 0.332455E+09 | 18783.31 | 27-FEB-15:00 | 18783.31 | 0.01 |
March | 0.00 | 0.00 | 0.656272E+09 | 0.656272E+09 | 20929.09 | 18-MAR-16:00 | 20929.09 | 0.01 |
April | 0.00 | 0.00 | 0.473027E+10 | 0.473027E+10 | 29946.00 | 27-APR-15:02 | 29946.00 | 0.05 |
May | 0.00 | 0.00 | 0.970367E+10 | 0.924311E+10 | 36235.69 | 05-MAY-18:02 | 27242.31 | 0.17 |
June | 0.00 | 0.00 | 0.167744E+11 | 0.167571E+11 | 29532.74 | 28-JUN-15:02 | 29532.74 | 0.36 |
July | 0.00 | 0.00 | 0.301164E+11 | 0.278837E+11 | 39786.10 | 15-JUL-18:00 | 26404.20 | 0.61 |
August | 0.00 | 0.00 | 0.384432E+11 | 0.348388E+11 | 40345.78 | 30-AUG-12:40 | 25816.40 | 0.79 |
September | 0.00 | 0.00 | 0.144140E+11 | 0.132626E+11 | 38717.43 | 23-SEP-13:30 | 26575.57 | 0.44 |
October | 0.00 | 0.00 | 0.254416E+10 | 0.253791E+10 | 24147.99 | 04-OCT-15:00 | 24147.99 | 0.06 |
November | 0.00 | 0.00 | 0.658452E+09 | 0.579607E+09 | 28029.94 | 04-NOV-13:50 | 22649.60 | 0.03 |
December | 0.00 | 0.00 | 7193.64 | 7193.64 | 35.97 | 05-DEC-11:57 | 35.97 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.118373E+12 | 0.110822E+12 | 0.21 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.384432E+11 | 0.348388E+11 | 40345.78 | 29946.00 | 0.79 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 9090484.77 | 8412275.13 | 9196.44 | 20-JAN-16:02 | 9196.44 | 0.00 |
February | 0.00 | 0.00 | 0.184356E+09 | 0.151650E+09 | 14246.83 | 06-FEB-16:02 | 14246.83 | 0.03 |
March | 0.00 | 0.00 | 0.706842E+09 | 0.682674E+09 | 14850.72 | 18-MAR-15:02 | 14850.72 | 0.02 |
April | 0.00 | 0.00 | 0.210869E+10 | 0.167351E+10 | 15584.30 | 01-APR-18:02 | 15584.30 | 0.23 |
May | 0.00 | 0.00 | 0.393075E+10 | 0.281115E+10 | 15297.92 | 14-MAY-15:02 | 15297.92 | 0.52 |
June | 0.00 | 0.00 | 0.461639E+10 | 0.292829E+10 | 15148.59 | 12-JUN-15:01 | 12844.72 | 0.75 |
July | 0.00 | 0.00 | 0.752916E+10 | 0.482540E+10 | 15301.64 | 16-JUL-15:01 | 13313.40 | 0.89 |
August | 0.00 | 0.00 | 0.737773E+10 | 0.459268E+10 | 15313.72 | 28-AUG-15:02 | 14701.94 | 0.88 |
September | 0.00 | 0.00 | 0.469678E+10 | 0.283501E+10 | 14676.51 | 22-SEP-18:02 | 14235.06 | 0.75 |
October | 0.00 | 0.00 | 0.133658E+10 | 0.954022E+09 | 15070.28 | 04-OCT-15:02 | 15070.28 | 0.23 |
November | 0.00 | 0.00 | 0.136637E+09 | 71965650.56 | 14006.37 | 11-NOV-16:02 | 14006.37 | 0.04 |
December | 0.00 | 0.00 | 18616092.82 | 17696927.63 | 13563.44 | 05-DEC-16:02 | 13563.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.326516E+11 | 0.215524E+11 | 0.36 | |||
Minimum of Months | 0.00 | 0.00 | 9090484.77 | 8412275.13 | 9196.44 | 9196.44 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.752916E+10 | 0.482540E+10 | 15584.30 | 15584.30 | 0.89 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2590396.11 | 2153419.97 | 3817.89 | 24-JAN-16:03 | 3817.89 | 0.00 |
February | 0.00 | 0.00 | 45560293.78 | 30837153.53 | 13295.11 | 27-FEB-16:02 | 13295.11 | 0.01 |
March | 0.00 | 0.00 | 0.274759E+09 | 0.270011E+09 | 13367.92 | 18-MAR-15:02 | 13367.92 | 0.00 |
April | 0.00 | 0.00 | 0.135267E+10 | 0.106109E+10 | 14029.59 | 01-APR-18:02 | 14029.59 | 0.16 |
May | 0.00 | 0.00 | 0.313273E+10 | 0.226434E+10 | 13771.06 | 14-MAY-15:02 | 13771.06 | 0.46 |
June | 0.00 | 0.00 | 0.400232E+10 | 0.258256E+10 | 13583.18 | 12-JUN-15:01 | 11462.20 | 0.69 |
July | 0.00 | 0.00 | 0.656449E+10 | 0.425716E+10 | 13737.19 | 16-JUL-15:01 | 11903.50 | 0.84 |
August | 0.00 | 0.00 | 0.604914E+10 | 0.369354E+10 | 13830.87 | 28-AUG-15:02 | 13209.77 | 0.83 |
September | 0.00 | 0.00 | 0.311054E+10 | 0.176382E+10 | 13480.98 | 24-SEP-15:02 | 11840.92 | 0.64 |
October | 0.00 | 0.00 | 0.556651E+09 | 0.405752E+09 | 13565.85 | 04-OCT-15:02 | 13565.85 | 0.12 |
November | 0.00 | 0.00 | 44752227.89 | 23170043.01 | 13492.55 | 04-NOV-15:02 | 12753.31 | 0.01 |
December | 0.00 | 0.00 | 4296991.80 | 3535860.94 | 3601.22 | 03-DEC-19:03 | 3601.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.251405E+11 | 0.163580E+11 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 2590396.11 | 2153419.97 | 3601.22 | 3601.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.656449E+10 | 0.425716E+10 | 14029.59 | 14029.59 | 0.84 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 20465098.89 | 20465098.89 | 4582.63 | 08-JAN-14:40 | 4582.63 | 0.00 |
February | 0.00 | 0.00 | 0.231332E+10 | 0.231332E+10 | 34513.54 | 08-FEB-14:00 | 34513.54 | 0.00 |
March | 0.00 | 0.00 | 0.565474E+10 | 0.565474E+10 | 46834.27 | 02-MAR-13:30 | 46834.27 | 0.00 |
April | 0.00 | 0.00 | 0.924778E+10 | 0.776762E+10 | 42082.96 | 27-APR-13:20 | 38029.60 | 0.11 |
May | 0.00 | 0.00 | 0.121638E+11 | 0.925114E+10 | 41461.31 | 04-MAY-13:20 | 36089.88 | 0.21 |
June | 0.00 | 0.00 | 0.127592E+11 | 0.688043E+10 | 29319.41 | 28-JUN-13:10 | 19316.03 | 0.42 |
July | 0.00 | 0.00 | 0.218399E+11 | 0.117487E+11 | 41009.86 | 31-JUL-13:00 | 32300.97 | 0.55 |
August | 0.00 | 0.00 | 0.271512E+11 | 0.155193E+11 | 52861.44 | 24-AUG-14:50 | 43765.82 | 0.67 |
September | 0.00 | 0.00 | 0.238370E+11 | 0.148896E+11 | 54484.41 | 14-SEP-13:30 | 40438.62 | 0.52 |
October | 0.00 | 0.00 | 0.124482E+11 | 0.109426E+11 | 56017.09 | 04-OCT-12:30 | 56017.09 | 0.11 |
November | 0.00 | 0.00 | 0.112967E+10 | 0.739222E+09 | 35295.01 | 04-NOV-13:30 | 25140.67 | 0.02 |
December | 0.00 | 0.00 | 0.110088E+10 | 0.110088E+10 | 30395.72 | 05-DEC-12:25 | 30395.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.129666E+12 | 0.868281E+11 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 20465098.89 | 20465098.89 | 4582.63 | 4582.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.271512E+11 | 0.155193E+11 | 56017.09 | 56017.09 | 0.67 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.239592E+09 | 0.154160E+09 | 30315.95 | 09-JAN-19:04 | 30315.95 | 0.02 |
February | 0.00 | 0.00 | 0.132398E+10 | 0.640198E+09 | 53766.71 | 25-FEB-09:03 | 53766.71 | 0.11 |
March | 0.00 | 0.00 | 0.346448E+10 | 0.262306E+10 | 53956.08 | 21-MAR-18:02 | 53956.08 | 0.13 |
April | 0.00 | 0.00 | 0.110374E+11 | 0.828232E+10 | 61385.87 | 01-APR-18:02 | 61385.87 | 0.31 |
May | 0.00 | 0.00 | 0.215298E+11 | 0.152820E+11 | 63956.87 | 05-MAY-18:02 | 58385.76 | 0.56 |
June | 0.00 | 0.00 | 0.286246E+11 | 0.202742E+11 | 62771.73 | 09-JUN-18:02 | 62771.73 | 0.66 |
July | 0.00 | 0.00 | 0.359726E+11 | 0.246532E+11 | 66065.56 | 15-JUL-18:02 | 58381.65 | 0.68 |
August | 0.00 | 0.00 | 0.350617E+11 | 0.219150E+11 | 65521.64 | 13-AUG-15:02 | 61683.26 | 0.71 |
September | 0.00 | 0.00 | 0.201181E+11 | 0.107798E+11 | 61476.70 | 23-SEP-15:02 | 56562.30 | 0.69 |
October | 0.00 | 0.00 | 0.668501E+10 | 0.367824E+10 | 58788.80 | 01-OCT-08:62 | 52582.89 | 0.38 |
November | 0.00 | 0.00 | 0.225679E+10 | 0.863824E+09 | 56772.97 | 05-NOV-08:62 | 52182.81 | 0.19 |
December | 0.00 | 0.00 | 0.178853E+09 | 0.118246E+09 | 33120.92 | 05-DEC-19:03 | 33120.92 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.166493E+12 | 0.109264E+12 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 0.178853E+09 | 0.118246E+09 | 30315.95 | 30315.95 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.359726E+11 | 0.246532E+11 | 66065.56 | 62771.73 | 0.71 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7737990.56 | 7125174.14 | 3455.22 | 10-JAN-09:03 | 3455.22 | 0.00 |
February | 0.00 | 0.00 | 0.165255E+09 | 0.128869E+09 | 11822.93 | 08-FEB-16:02 | 11822.93 | 0.03 |
March | 0.00 | 0.00 | 0.649575E+09 | 0.605980E+09 | 13286.59 | 18-MAR-15:02 | 13286.59 | 0.03 |
April | 0.00 | 0.00 | 0.216076E+10 | 0.168078E+10 | 13860.31 | 01-APR-18:02 | 13860.31 | 0.26 |
May | 0.00 | 0.00 | 0.338929E+10 | 0.233345E+10 | 13686.58 | 14-MAY-15:02 | 13686.58 | 0.51 |
June | 0.00 | 0.00 | 0.499394E+10 | 0.320699E+10 | 13641.55 | 12-JUN-15:01 | 11735.27 | 0.80 |
July | 0.00 | 0.00 | 0.649394E+10 | 0.399044E+10 | 13917.32 | 31-JUL-18:02 | 13426.62 | 0.91 |
August | 0.00 | 0.00 | 0.729568E+10 | 0.452899E+10 | 14054.40 | 30-AUG-08:62 | 10302.27 | 0.89 |
September | 0.00 | 0.00 | 0.424362E+10 | 0.253838E+10 | 13492.26 | 24-SEP-15:02 | 11714.11 | 0.73 |
October | 0.00 | 0.00 | 0.131169E+10 | 0.921696E+09 | 13482.95 | 04-OCT-15:02 | 13482.95 | 0.25 |
November | 0.00 | 0.00 | 0.141153E+09 | 70111800.17 | 13388.00 | 04-NOV-15:02 | 12686.75 | 0.05 |
December | 0.00 | 0.00 | 51142684.37 | 48100787.87 | 4002.10 | 29-DEC-09:03 | 2897.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.309038E+11 | 0.200609E+11 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 7737990.56 | 7125174.14 | 3455.22 | 2897.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.729568E+10 | 0.452899E+10 | 14054.40 | 13860.31 | 0.91 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3462527.96 | 3002464.10 | 2886.72 | 05-JAN-09:04 | 2886.72 | 0.00 |
February | 0.00 | 0.00 | 20347280.71 | 12919202.77 | 4381.11 | 27-FEB-09:01 | 3289.11 | 0.01 |
March | 0.00 | 0.00 | 0.176982E+09 | 0.159658E+09 | 11149.89 | 02-MAR-09:01 | 11149.89 | 0.02 |
April | 0.00 | 0.00 | 0.131762E+10 | 0.989489E+09 | 12120.61 | 02-APR-15:02 | 12120.61 | 0.21 |
May | 0.00 | 0.00 | 0.256288E+10 | 0.175166E+10 | 12417.60 | 14-MAY-15:02 | 12417.60 | 0.45 |
June | 0.00 | 0.00 | 0.431044E+10 | 0.282612E+10 | 12391.01 | 12-JUN-15:01 | 10640.46 | 0.77 |
July | 0.00 | 0.00 | 0.548881E+10 | 0.340620E+10 | 12764.01 | 31-JUL-18:02 | 12103.83 | 0.89 |
August | 0.00 | 0.00 | 0.592044E+10 | 0.355157E+10 | 12710.68 | 09-AUG-18:02 | 12152.14 | 0.86 |
September | 0.00 | 0.00 | 0.263955E+10 | 0.148058E+10 | 12770.89 | 23-SEP-15:02 | 11538.58 | 0.62 |
October | 0.00 | 0.00 | 0.496829E+09 | 0.324312E+09 | 12019.92 | 04-OCT-15:02 | 12019.92 | 0.13 |
November | 0.00 | 0.00 | 23197726.62 | 8691963.98 | 6951.11 | 04-NOV-15:02 | 4622.58 | 0.02 |
December | 0.00 | 0.00 | 4934408.93 | 4362900.04 | 2777.56 | 03-DEC-09:03 | 2777.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.229655E+11 | 0.145186E+11 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 3462527.96 | 3002464.10 | 2777.56 | 2777.56 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.592044E+10 | 0.355157E+10 | 12770.89 | 12417.60 | 0.89 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1394549.60 | 1281811.31 | 1924.55 | 20-JAN-16:02 | 1924.55 | 0.00 |
February | 0.00 | 0.00 | 45850530.62 | 39190490.32 | 3717.99 | 06-FEB-16:02 | 3717.99 | 0.02 |
March | 0.00 | 0.00 | 0.173221E+09 | 0.169062E+09 | 3875.77 | 18-MAR-15:02 | 3875.77 | 0.01 |
April | 0.00 | 0.00 | 0.517273E+09 | 0.425556E+09 | 4067.07 | 01-APR-18:02 | 4067.07 | 0.18 |
May | 0.00 | 0.00 | 0.959932E+09 | 0.719541E+09 | 3992.28 | 14-MAY-15:02 | 3992.28 | 0.43 |
June | 0.00 | 0.00 | 0.112154E+10 | 0.737563E+09 | 3966.87 | 12-JUN-15:01 | 3369.85 | 0.67 |
July | 0.00 | 0.00 | 0.186964E+10 | 0.122968E+10 | 3999.67 | 16-JUL-15:01 | 3470.64 | 0.86 |
August | 0.00 | 0.00 | 0.178891E+10 | 0.114610E+10 | 4043.53 | 25-AUG-08:62 | 3314.65 | 0.84 |
September | 0.00 | 0.00 | 0.109975E+10 | 0.695738E+09 | 3946.61 | 23-SEP-08:62 | 3003.01 | 0.64 |
October | 0.00 | 0.00 | 0.288514E+09 | 0.218301E+09 | 3932.84 | 04-OCT-15:02 | 3932.84 | 0.16 |
November | 0.00 | 0.00 | 32375897.35 | 18660115.35 | 3684.11 | 11-NOV-16:02 | 3684.11 | 0.03 |
December | 0.00 | 0.00 | 3514156.28 | 3235718.86 | 3559.63 | 05-DEC-16:02 | 3559.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.790192E+10 | 0.540391E+10 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 1394549.60 | 1281811.31 | 1924.55 | 1924.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.186964E+10 | 0.122968E+10 | 4067.07 | 4067.07 | 0.86 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 482531.01 | 381086.20 | 718.59 | 11-JAN-16:05 | 510.85 | 0.00 |
February | 0.00 | 0.00 | 8682963.43 | 6483379.46 | 3440.80 | 27-FEB-16:02 | 3440.80 | 0.01 |
March | 0.00 | 0.00 | 61697128.26 | 60746426.64 | 3459.64 | 18-MAR-15:02 | 3459.64 | 0.00 |
April | 0.00 | 0.00 | 0.324437E+09 | 0.263920E+09 | 3630.91 | 01-APR-18:02 | 3630.91 | 0.13 |
May | 0.00 | 0.00 | 0.749187E+09 | 0.571375E+09 | 3564.28 | 14-MAY-15:02 | 3564.28 | 0.36 |
June | 0.00 | 0.00 | 0.954531E+09 | 0.646638E+09 | 3526.15 | 12-JUN-15:01 | 2979.57 | 0.61 |
July | 0.00 | 0.00 | 0.160963E+10 | 0.107611E+10 | 3566.36 | 16-JUL-15:01 | 3085.35 | 0.82 |
August | 0.00 | 0.00 | 0.143384E+10 | 0.907873E+09 | 3585.64 | 28-AUG-15:02 | 3415.22 | 0.77 |
September | 0.00 | 0.00 | 0.684310E+09 | 0.417465E+09 | 3510.56 | 24-SEP-15:02 | 3052.08 | 0.50 |
October | 0.00 | 0.00 | 0.107667E+09 | 83883771.99 | 3510.88 | 04-OCT-15:02 | 3510.88 | 0.06 |
November | 0.00 | 0.00 | 10803747.32 | 6213853.23 | 3499.38 | 04-NOV-15:02 | 3296.36 | 0.01 |
December | 0.00 | 0.00 | 1112348.84 | 948988.11 | 847.81 | 10-DEC-16:03 | 647.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.594638E+10 | 0.404204E+10 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 482531.01 | 381086.20 | 718.59 | 510.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.160963E+10 | 0.107611E+10 | 3630.91 | 3630.91 | 0.82 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.386361E+09 | 0.381536E+09 | 20203.47 | 20-JAN-16:02 | 20203.47 | 0.01 |
February | 0.00 | 0.00 | 0.158324E+10 | 0.139618E+10 | 20215.56 | 01-FEB-16:02 | 20215.56 | 0.09 |
March | 0.00 | 0.00 | 0.276938E+10 | 0.255054E+10 | 21062.24 | 18-MAR-15:02 | 21062.24 | 0.11 |
April | 0.00 | 0.00 | 0.421691E+10 | 0.332985E+10 | 21240.23 | 27-APR-18:02 | 21240.23 | 0.32 |
May | 0.00 | 0.00 | 0.533718E+10 | 0.357817E+10 | 21702.17 | 05-MAY-18:02 | 20451.92 | 0.56 |
June | 0.00 | 0.00 | 0.605830E+10 | 0.350253E+10 | 21739.53 | 12-JUN-15:01 | 18457.43 | 0.77 |
July | 0.00 | 0.00 | 0.894587E+10 | 0.517717E+10 | 22173.38 | 15-JUL-18:02 | 20069.75 | 0.87 |
August | 0.00 | 0.00 | 0.101841E+11 | 0.621749E+10 | 21810.28 | 09-AUG-18:02 | 21448.82 | 0.88 |
September | 0.00 | 0.00 | 0.818835E+10 | 0.523116E+10 | 21059.13 | 22-SEP-18:02 | 20045.06 | 0.78 |
October | 0.00 | 0.00 | 0.427554E+10 | 0.312743E+10 | 21373.06 | 04-OCT-15:02 | 21373.06 | 0.43 |
November | 0.00 | 0.00 | 0.104780E+10 | 0.752556E+09 | 20211.29 | 10-NOV-16:01 | 20211.29 | 0.11 |
December | 0.00 | 0.00 | 0.879794E+09 | 0.853483E+09 | 20208.16 | 06-DEC-16:02 | 20208.16 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.538728E+11 | 0.360981E+11 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 0.386361E+09 | 0.381536E+09 | 20203.47 | 18457.43 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.101841E+11 | 0.621749E+10 | 22173.38 | 21448.82 | 0.88 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 35476.51 | 219323.84 | 12-JAN-09:01 |
February | 0.12 | 382.71 | 06-FEB-13:40 | 26408.01 | 155691.01 | 20-FEB-19:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 18244.94 | 220140.61 | 03-MAR-09:02 |
April | 0.00 | 0.00 | 01-APR-00:05 | 13206.73 | 128779.20 | 17-APR-07:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10076.73 | 173204.07 | 18-MAY-08:62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 3547.43 | 107998.78 | 15-JUN-03:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 944.39 | 44791.88 | 13-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 885.25 | 44140.32 | 21-AUG-08:05 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 3910.19 | 115435.05 | 27-SEP-04:53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 15386.22 | 158106.80 | 16-OCT-08:62 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25231.25 | 194358.47 | 24-NOV-16:01 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 33881.28 | 221560.93 | 07-DEC-19:03 |
Annual Sum or Average | 0.01 | 15556.29 | ||||
Minimum of Months | 0.00 | 0.00 | 885.25 | 44140.32 | ||
Maximum of Months | 0.12 | 382.71 | 35476.51 | 221560.93 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1472.61 | 40919.30 | 17-JAN-19:04 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 5014.28 | 177851.70 | 27-FEB-16:02 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 9458.93 | 228614.86 | 18-MAR-15:02 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 28818.14 | 389660.76 | 27-APR-18:03 | 0.00 | 0.00 | 01-APR-00:05 |
May | 48715.51 | 379435.57 | 05-MAY-18:02 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 75578.72 | 410038.20 | 28-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 115386.77 | 468774.74 | 31-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 137591.27 | 504116.44 | 10-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 67952.27 | 410456.17 | 14-SEP-15:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 19783.57 | 340741.13 | 04-OCT-15:02 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5119.50 | 252242.78 | 04-NOV-15:02 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 2344.21 | 49410.07 | 19-DEC-19:03 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 43402.19 | 0.00 | ||||
Minimum of Months | 1472.61 | 40919.30 | 0.00 | 0.00 | ||
Maximum of Months | 137591.27 | 504116.44 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 27446.20 | 68449.74 | 11-JAN-07:11 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 27623.55 | 68465.66 | 01-FEB-07:51 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 27328.96 | 68642.19 | 07-MAR-07:51 |
April | 0.00 | 0.00 | 01-APR-00:05 | 26606.49 | 66047.25 | 01-APR-07:11 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 25674.46 | 60849.28 | 19-MAY-06:14 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24795.16 | 58820.16 | 15-JUN-06:38 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 24143.78 | 52501.01 | 03-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23968.35 | 53374.20 | 18-AUG-06:37 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24246.92 | 58025.01 | 27-SEP-06:55 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 24908.02 | 61489.80 | 13-OCT-06:11 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25872.58 | 60478.41 | 19-NOV-07:51 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 26800.76 | 67787.61 | 28-DEC-07:01 |
Annual Sum or Average | 0.00 | 25773.92 | ||||
Minimum of Months | 0.00 | 0.00 | 23968.35 | 52501.01 | ||
Maximum of Months | 0.00 | 0.00 | 27623.55 | 68642.19 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 0.89 | 2194.93 | 01-JAN-00:05 | 0.89 |
February | 0.530997E+10 | 0.89 | 2194.93 | 01-FEB-00:03 | 0.89 |
March | 0.587890E+10 | 0.89 | 2194.93 | 01-MAR-00:03 | 0.89 |
April | 0.568926E+10 | 0.89 | 2194.93 | 01-APR-00:05 | 0.89 |
May | 0.587890E+10 | 0.89 | 2194.93 | 01-MAY-00:05 | 0.89 |
June | 0.568926E+10 | 0.89 | 2194.93 | 01-JUN-00:05 | 0.89 |
July | 0.587890E+10 | 0.88 | 2194.93 | 01-JUL-00:10 | 0.88 |
August | 0.587890E+10 | 0.88 | 2194.93 | 01-AUG-00:05 | 0.88 |
September | 0.568926E+10 | 0.88 | 2194.93 | 01-SEP-00:05 | 0.88 |
October | 0.587890E+10 | 0.89 | 2194.93 | 01-OCT-00:10 | 0.88 |
November | 0.568926E+10 | 0.89 | 2194.93 | 01-NOV-00:03 | 0.89 |
December | 0.587890E+10 | 0.89 | 2194.93 | 01-DEC-00:03 | 0.89 |
Annual Sum or Average | 0.692193E+11 | 0.89 | |||
Minimum of Months | 0.530997E+10 | 0.88 | 2194.93 | 0.88 | |
Maximum of Months | 0.587890E+10 | 0.89 | 2194.93 | 0.89 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.334175E+11 | 0.79 | 37285.71 | 09-JAN-21:55 | 1.53 |
February | 0.303218E+11 | 0.79 | 41975.18 | 07-FEB-20:35 | 1.64 |
March | 0.347687E+11 | 0.81 | 37285.71 | 17-MAR-21:05 | 1.52 |
April | 0.342965E+11 | 0.82 | 35517.42 | 21-APR-23:55 | 1.47 |
May | 0.363308E+11 | 0.83 | 35517.42 | 24-MAY-04:45 | 1.47 |
June | 0.353395E+11 | 0.83 | 24425.23 | 28-JUN-21:10 | 1.17 |
July | 0.372988E+11 | 0.84 | 25639.02 | 31-JUL-21:10 | 1.20 |
August | 0.378723E+11 | 0.84 | 27628.34 | 10-AUG-21:10 | 1.25 |
September | 0.355130E+11 | 0.83 | 28072.14 | 12-SEP-21:10 | 1.27 |
October | 0.360095E+11 | 0.82 | 41975.18 | 24-OCT-01:15 | 1.64 |
November | 0.336614E+11 | 0.81 | 38530.42 | 15-NOV-22:50 | 1.56 |
December | 0.339541E+11 | 0.80 | 37285.71 | 04-DEC-21:55 | 1.52 |
Annual Sum or Average | 0.418784E+12 | 0.82 | |||
Minimum of Months | 0.303218E+11 | 0.79 | 24425.23 | 1.17 | |
Maximum of Months | 0.378723E+11 | 0.84 | 41975.18 | 1.64 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:05 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:03 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:05 | 0.27 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:05 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:05 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:05 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:05 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:03 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:03 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:05 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:03 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:03 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:03 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:10 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.287404E+09 | 0.45 | 856.10 | 01-JAN-09:01 | 0.58 |
February | 0.206213E+09 | 0.43 | 856.10 | 01-FEB-09:02 | 0.58 |
March | 0.182386E+09 | 0.43 | 856.10 | 01-MAR-16:02 | 0.58 |
April | 0.199474E+09 | 0.45 | 856.10 | 01-APR-15:02 | 0.58 |
May | 0.272537E+09 | 0.48 | 856.10 | 01-MAY-15:02 | 0.58 |
June | 0.294311E+09 | 0.49 | 856.10 | 01-JUN-08:62 | 0.58 |
July | 0.439880E+09 | 0.52 | 856.10 | 01-JUL-08:62 | 0.58 |
August | 0.407649E+09 | 0.51 | 856.10 | 01-AUG-08:62 | 0.58 |
September | 0.288245E+09 | 0.48 | 856.10 | 01-SEP-15:02 | 0.58 |
October | 0.174188E+09 | 0.44 | 856.10 | 01-OCT-15:02 | 0.58 |
November | 0.206954E+09 | 0.43 | 856.10 | 01-NOV-08:62 | 0.58 |
December | 0.274650E+09 | 0.45 | 856.10 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.323389E+10 | 0.46 | |||
Minimum of Months | 0.174188E+09 | 0.43 | 856.10 | 0.58 | |
Maximum of Months | 0.439880E+09 | 0.52 | 856.10 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.294637E+09 | 0.48 | 770.01 | 01-JAN-09:01 | 0.58 |
February | 0.215548E+09 | 0.44 | 770.01 | 01-FEB-09:02 | 0.58 |
March | 0.171976E+09 | 0.41 | 770.01 | 01-MAR-09:01 | 0.58 |
April | 0.161222E+09 | 0.43 | 770.01 | 01-APR-15:02 | 0.58 |
May | 0.225555E+09 | 0.45 | 770.01 | 01-MAY-15:02 | 0.58 |
June | 0.260393E+09 | 0.46 | 770.01 | 01-JUN-08:62 | 0.58 |
July | 0.390186E+09 | 0.49 | 770.01 | 01-JUL-08:62 | 0.58 |
August | 0.337963E+09 | 0.48 | 770.01 | 01-AUG-08:62 | 0.58 |
September | 0.201558E+09 | 0.44 | 770.01 | 01-SEP-15:02 | 0.58 |
October | 0.142037E+09 | 0.42 | 770.01 | 01-OCT-15:02 | 0.58 |
November | 0.210255E+09 | 0.43 | 770.01 | 01-NOV-08:62 | 0.58 |
December | 0.283040E+09 | 0.47 | 770.01 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.289437E+10 | 0.45 | |||
Minimum of Months | 0.142037E+09 | 0.41 | 770.01 | 0.58 | |
Maximum of Months | 0.390186E+09 | 0.49 | 770.01 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.589716E+09 | 0.28 | 871.54 | 05-JAN-06:00 | 0.58 |
February | 0.274734E+09 | 0.12 | 1615.24 | 08-FEB-14:00 | 0.59 |
March | 0.337561E+09 | 0.11 | 2729.15 | 02-MAR-13:30 | 0.58 |
April | 0.549445E+09 | 0.20 | 1736.45 | 27-APR-13:10 | 0.58 |
May | 0.714689E+09 | 0.25 | 1726.14 | 04-MAY-13:10 | 0.58 |
June | 0.791445E+09 | 0.31 | 1276.27 | 28-JUN-13:10 | 0.58 |
July | 0.115865E+10 | 0.38 | 1618.92 | 31-JUL-13:20 | 0.58 |
August | 0.133159E+10 | 0.39 | 2711.15 | 24-AUG-13:00 | 0.58 |
September | 0.128629E+10 | 0.32 | 3097.42 | 10-SEP-12:40 | 0.58 |
October | 0.714622E+09 | 0.17 | 3517.14 | 07-OCT-12:30 | 0.58 |
November | 0.179923E+09 | 0.09 | 1474.09 | 04-NOV-13:40 | 0.58 |
December | 0.615642E+09 | 0.26 | 1461.71 | 05-DEC-12:25 | 0.58 |
Annual Sum or Average | 0.854431E+10 | 0.24 | |||
Minimum of Months | 0.179923E+09 | 0.09 | 871.54 | 0.58 | |
Maximum of Months | 0.133159E+10 | 0.39 | 3517.14 | 0.59 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.932200E+09 | 0.41 | 3555.40 | 01-JAN-16:01 | 0.58 |
February | 0.732129E+09 | 0.41 | 3555.40 | 01-FEB-16:02 | 0.58 |
March | 0.554119E+09 | 0.41 | 3555.40 | 02-MAR-09:01 | 0.58 |
April | 0.782833E+09 | 0.41 | 3555.40 | 01-APR-08:62 | 0.58 |
May | 0.128392E+10 | 0.41 | 3555.40 | 01-MAY-15:02 | 0.58 |
June | 0.163692E+10 | 0.41 | 3555.40 | 01-JUN-08:62 | 0.58 |
July | 0.194972E+10 | 0.41 | 3555.40 | 01-JUL-08:62 | 0.58 |
August | 0.176454E+10 | 0.41 | 3555.40 | 01-AUG-08:62 | 0.58 |
September | 0.108236E+10 | 0.41 | 3555.40 | 01-SEP-15:02 | 0.58 |
October | 0.588931E+09 | 0.41 | 3555.40 | 01-OCT-08:62 | 0.58 |
November | 0.634629E+09 | 0.41 | 3555.40 | 04-NOV-08:63 | 0.58 |
December | 0.878431E+09 | 0.41 | 3555.40 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.128207E+11 | 0.41 | |||
Minimum of Months | 0.554119E+09 | 0.41 | 3555.40 | 0.58 | |
Maximum of Months | 0.194972E+10 | 0.41 | 3555.40 | 0.58 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.265467E+09 | 0.45 | 765.18 | 01-JAN-09:01 | 0.58 |
February | 0.189975E+09 | 0.43 | 765.18 | 01-FEB-09:02 | 0.58 |
March | 0.165802E+09 | 0.43 | 765.18 | 01-MAR-09:01 | 0.58 |
April | 0.196042E+09 | 0.47 | 765.18 | 01-APR-08:62 | 0.58 |
May | 0.238342E+09 | 0.49 | 765.18 | 01-MAY-15:02 | 0.58 |
June | 0.307076E+09 | 0.52 | 765.18 | 01-JUN-08:62 | 0.58 |
July | 0.367620E+09 | 0.53 | 765.18 | 01-JUL-08:62 | 0.58 |
August | 0.391482E+09 | 0.52 | 765.18 | 01-AUG-08:62 | 0.58 |
September | 0.258042E+09 | 0.49 | 765.18 | 01-SEP-15:02 | 0.58 |
October | 0.166736E+09 | 0.45 | 765.18 | 01-OCT-15:02 | 0.58 |
November | 0.191124E+09 | 0.43 | 765.18 | 01-NOV-08:62 | 0.58 |
December | 0.256017E+09 | 0.45 | 765.18 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.299372E+10 | 0.47 | |||
Minimum of Months | 0.165802E+09 | 0.43 | 765.18 | 0.58 | |
Maximum of Months | 0.391482E+09 | 0.53 | 765.18 | 0.58 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.276785E+09 | 0.49 | 693.59 | 01-JAN-09:01 | 0.58 |
February | 0.197992E+09 | 0.44 | 693.59 | 01-FEB-09:02 | 0.58 |
March | 0.150930E+09 | 0.41 | 693.59 | 01-MAR-09:01 | 0.58 |
April | 0.150277E+09 | 0.43 | 693.59 | 01-APR-08:62 | 0.58 |
May | 0.192796E+09 | 0.47 | 693.59 | 01-MAY-15:02 | 0.58 |
June | 0.271018E+09 | 0.50 | 693.59 | 01-JUN-08:62 | 0.58 |
July | 0.316556E+09 | 0.52 | 693.59 | 01-JUL-08:62 | 0.58 |
August | 0.322247E+09 | 0.51 | 693.59 | 01-AUG-08:62 | 0.58 |
September | 0.172916E+09 | 0.46 | 693.59 | 01-SEP-15:02 | 0.58 |
October | 0.130771E+09 | 0.41 | 693.59 | 02-OCT-15:02 | 0.58 |
November | 0.193170E+09 | 0.43 | 693.59 | 01-NOV-08:62 | 0.58 |
December | 0.263902E+09 | 0.48 | 693.59 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.263936E+10 | 0.46 | |||
Minimum of Months | 0.130771E+09 | 0.41 | 693.59 | 0.58 | |
Maximum of Months | 0.322247E+09 | 0.52 | 693.59 | 0.58 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 87849408.13 | 0.49 | 223.49 | 01-JAN-09:01 | 0.58 |
February | 63677169.45 | 0.45 | 223.49 | 01-FEB-09:02 | 0.58 |
March | 55969249.45 | 0.43 | 223.49 | 01-MAR-09:01 | 0.58 |
April | 56714123.38 | 0.45 | 223.49 | 01-APR-15:02 | 0.58 |
May | 72070665.94 | 0.48 | 223.49 | 01-MAY-15:02 | 0.58 |
June | 75039619.94 | 0.49 | 223.49 | 01-JUN-15:02 | 0.58 |
July | 0.111236E+09 | 0.52 | 223.49 | 01-JUL-15:02 | 0.58 |
August | 0.100631E+09 | 0.51 | 223.49 | 01-AUG-08:62 | 0.58 |
September | 72170794.88 | 0.48 | 223.49 | 01-SEP-15:02 | 0.58 |
October | 50102548.77 | 0.44 | 223.49 | 01-OCT-15:02 | 0.58 |
November | 64212234.84 | 0.45 | 223.49 | 01-NOV-08:62 | 0.58 |
December | 83977818.57 | 0.48 | 223.49 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.893651E+09 | 0.47 | |||
Minimum of Months | 50102548.77 | 0.43 | 223.49 | 0.58 | |
Maximum of Months | 0.111236E+09 | 0.52 | 223.49 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 89393003.22 | 0.54 | 199.33 | 01-JAN-09:01 | 0.58 |
February | 65693632.77 | 0.48 | 199.33 | 01-FEB-09:02 | 0.58 |
March | 52934715.65 | 0.42 | 199.33 | 01-MAR-09:01 | 0.58 |
April | 47246991.46 | 0.43 | 199.33 | 01-APR-15:02 | 0.58 |
May | 59876357.41 | 0.46 | 199.33 | 02-MAY-15:02 | 0.58 |
June | 65547205.17 | 0.47 | 199.33 | 01-JUN-15:02 | 0.58 |
July | 97815230.93 | 0.50 | 199.33 | 01-JUL-15:02 | 0.58 |
August | 82287710.03 | 0.48 | 199.33 | 01-AUG-08:62 | 0.58 |
September | 49838787.53 | 0.45 | 199.33 | 01-SEP-15:02 | 0.58 |
October | 43714880.19 | 0.41 | 199.33 | 01-OCT-15:02 | 0.58 |
November | 65054113.71 | 0.47 | 199.33 | 01-NOV-08:62 | 0.58 |
December | 85739126.69 | 0.51 | 199.33 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.805142E+09 | 0.47 | |||
Minimum of Months | 43714880.19 | 0.41 | 199.33 | 0.58 | |
Maximum of Months | 97815230.93 | 0.54 | 199.33 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.343225E+09 | 0.44 | 1208.43 | 01-JAN-09:01 | 0.58 |
February | 0.291223E+09 | 0.45 | 1208.43 | 01-FEB-09:02 | 0.58 |
March | 0.300199E+09 | 0.47 | 1208.43 | 01-MAR-16:02 | 0.58 |
April | 0.321850E+09 | 0.48 | 1208.43 | 01-APR-15:02 | 0.58 |
May | 0.354140E+09 | 0.49 | 1208.43 | 01-MAY-15:02 | 0.58 |
June | 0.370990E+09 | 0.50 | 1208.43 | 01-JUN-15:02 | 0.58 |
July | 0.493923E+09 | 0.52 | 1208.43 | 01-JUL-08:62 | 0.58 |
August | 0.528873E+09 | 0.51 | 1208.43 | 01-AUG-08:62 | 0.58 |
September | 0.475558E+09 | 0.49 | 1208.43 | 01-SEP-15:02 | 0.58 |
October | 0.334291E+09 | 0.47 | 1208.43 | 01-OCT-15:02 | 0.58 |
November | 0.264879E+09 | 0.44 | 1208.43 | 02-NOV-15:02 | 0.58 |
December | 0.354937E+09 | 0.46 | 1208.43 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.443409E+10 | 0.48 | |||
Minimum of Months | 0.264879E+09 | 0.44 | 1208.43 | 0.58 | |
Maximum of Months | 0.528873E+09 | 0.52 | 1208.43 | 0.58 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.679935E+09 | 0.611942E+09 | 687.37 | 12-JAN-09:01 | 618.64 | 618.64 | 36.15 | 1.20 |
February | 0.463956E+09 | 0.417561E+09 | 681.01 | 11-FEB-16:01 | 612.91 | 612.91 | 53.24 | 1.17 |
March | 0.356540E+09 | 0.320886E+09 | 703.09 | 03-MAR-09:02 | 632.78 | 632.78 | 38.34 | 1.26 |
April | 0.224559E+09 | 0.202103E+09 | 573.90 | 11-APR-09:17 | 516.51 | 516.51 | 65.70 | 0.84 |
May | 0.155786E+09 | 0.140207E+09 | 579.05 | 18-MAY-08:62 | 521.14 | 521.14 | 32.23 | 0.87 |
June | 48770197.73 | 43893177.96 | 476.18 | 15-JUN-03:37 | 428.56 | 428.56 | 47.99 | 0.64 |
July | 14112122.85 | 12700910.57 | 206.55 | 12-JUL-08:07 | 185.90 | 185.90 | 34.12 | 0.23 |
August | 11975302.84 | 10777772.56 | 232.72 | 03-AUG-08:05 | 209.45 | 209.45 | 44.80 | 0.26 |
September | 61626148.35 | 55463533.52 | 549.54 | 27-SEP-04:40 | 494.58 | 494.58 | 46.56 | 0.79 |
October | 0.281366E+09 | 0.253230E+09 | 589.99 | 31-OCT-03:05 | 530.99 | 530.99 | 48.17 | 0.89 |
November | 0.473867E+09 | 0.426480E+09 | 704.49 | 10-NOV-09:01 | 634.04 | 634.04 | 43.98 | 1.26 |
December | 0.653735E+09 | 0.588361E+09 | 704.93 | 20-DEC-09:03 | 634.43 | 634.43 | 40.95 | 1.27 |
Annual Sum or Average | 0.342623E+10 | 0.308360E+10 | ||||||
Minimum of Months | 11975302.84 | 10777772.56 | 206.55 | 185.90 | 185.90 | 32.23 | 0.23 | |
Maximum of Months | 0.679935E+09 | 0.611942E+09 | 704.93 | 634.43 | 634.43 | 65.70 | 1.27 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 62705627.04 | 56435064.33 | 1463.68 | 20-JAN-19:04 | 1317.31 | 1317.31 | 8.40 | 2.51 |
February | 0.408255E+09 | 0.367430E+09 | 3125.57 | 27-FEB-16:02 | 2813.02 | 2813.02 | 7.83 | 6.91 |
March | 0.972102E+09 | 0.874892E+09 | 3594.57 | 18-MAR-15:02 | 3235.11 | 3235.11 | 7.73 | 8.97 |
April | 0.226512E+10 | 0.203861E+10 | 4285.87 | 26-APR-15:02 | 3857.28 | 3857.28 | 6.99 | 15.02 |
May | 0.368635E+10 | 0.331772E+10 | 4368.73 | 04-MAY-18:03 | 3931.86 | 3931.86 | 7.33 | 16.37 |
June | 0.498786E+10 | 0.448908E+10 | 4366.39 | 27-JUN-18:03 | 3929.75 | 3929.75 | 7.27 | 16.33 |
July | 0.644019E+10 | 0.579617E+10 | 4363.02 | 19-JUL-18:03 | 3926.72 | 3926.72 | 7.34 | 16.28 |
August | 0.688449E+10 | 0.619605E+10 | 4383.35 | 10-AUG-18:03 | 3945.02 | 3945.02 | 6.73 | 16.62 |
September | 0.437907E+10 | 0.394116E+10 | 4327.83 | 08-SEP-15:02 | 3895.05 | 3895.05 | 7.32 | 15.69 |
October | 0.186423E+10 | 0.167780E+10 | 3983.94 | 04-OCT-15:02 | 3585.55 | 3585.55 | 7.49 | 11.54 |
November | 0.399323E+09 | 0.359391E+09 | 3835.87 | 04-NOV-15:02 | 3452.29 | 3452.29 | 7.58 | 10.41 |
December | 0.153372E+09 | 0.138035E+09 | 1721.73 | 05-DEC-12:30 | 1549.56 | 1549.56 | 8.40 | 3.05 |
Annual Sum or Average | 0.325031E+11 | 0.292528E+11 | ||||||
Minimum of Months | 62705627.04 | 56435064.33 | 1463.68 | 1317.31 | 1317.31 | 6.73 | 2.51 | |
Maximum of Months | 0.688449E+10 | 0.619605E+10 | 4383.35 | 3945.02 | 3945.02 | 8.40 | 16.62 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.322773E+10 | 0.290496E+10 | 3825.90 | 01-JAN-00:05 | 3443.31 | 3443.31 | 8.41 | 26.81 |
February | 0.410642E+10 | 0.369578E+10 | 3825.90 | 01-FEB-06:20 | 3443.31 | 3443.31 | 8.41 | 26.81 |
March | 0.631237E+10 | 0.568113E+10 | 3825.90 | 01-MAR-00:03 | 3443.31 | 3443.31 | 8.41 | 26.81 |
April | 0.779502E+10 | 0.701552E+10 | 3825.90 | 01-APR-02:30 | 3443.31 | 3443.31 | 8.40 | 26.81 |
May | 0.942521E+10 | 0.848269E+10 | 3825.90 | 01-MAY-00:05 | 3443.31 | 3443.31 | 8.45 | 26.81 |
June | 0.968977E+10 | 0.872080E+10 | 3825.90 | 01-JUN-00:05 | 3443.31 | 3443.31 | 8.58 | 26.81 |
July | 0.101698E+11 | 0.915283E+10 | 3825.90 | 01-JUL-00:10 | 3443.31 | 3443.31 | 8.73 | 26.81 |
August | 0.101631E+11 | 0.914680E+10 | 3825.90 | 01-AUG-00:05 | 3443.31 | 3443.31 | 8.95 | 26.81 |
September | 0.929942E+10 | 0.836947E+10 | 3825.90 | 01-SEP-00:05 | 3443.31 | 3443.31 | 8.74 | 26.81 |
October | 0.705688E+10 | 0.635119E+10 | 3825.90 | 01-OCT-00:10 | 3443.31 | 3443.31 | 8.48 | 26.81 |
November | 0.422182E+10 | 0.379964E+10 | 3825.90 | 01-NOV-05:02 | 3443.31 | 3443.31 | 8.42 | 26.81 |
December | 0.390089E+10 | 0.351080E+10 | 3825.90 | 01-DEC-00:03 | 3443.31 | 3443.31 | 8.40 | 26.81 |
Annual Sum or Average | 0.853684E+11 | 0.768316E+11 | ||||||
Minimum of Months | 0.322773E+10 | 0.290496E+10 | 3825.90 | 3443.31 | 3443.31 | 8.40 | 26.81 | |
Maximum of Months | 0.101698E+11 | 0.915283E+10 | 3825.90 | 3443.31 | 3443.31 | 8.95 | 26.81 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 48.50 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 37.55 | 0.08 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 49.08 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:05 | 14.37 | 14.37 | 51.90 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 51.91 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 52.22 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.88 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 52.68 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 52.66 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 51.55 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:03 | 14.37 | 14.37 | 51.56 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 49.37 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 37.55 | 0.08 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 52.88 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 54.38 | 80.09 | 35476.51 | 219323.84 | 12-JAN-09:01 |
February | 0.12 | 382.71 | 06-FEB-13:40 | 79.88 | 79.88 | 26408.01 | 155691.01 | 20-FEB-19:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 45.25 | 80.09 | 18244.94 | 220140.61 | 03-MAR-09:02 |
April | 0.00 | 0.00 | 01-APR-00:05 | 54.58 | 79.75 | 13206.73 | 128779.20 | 17-APR-07:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 46.49 | 79.40 | 10076.73 | 173204.07 | 18-MAY-08:62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 36.02 | 36.02 | 3547.43 | 107998.78 | 15-JUN-03:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 29.74 | 29.74 | 944.39 | 44791.88 | 13-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 41.17 | 41.17 | 885.25 | 44140.32 | 21-AUG-08:05 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 48.42 | 48.42 | 3910.19 | 115435.05 | 27-SEP-04:53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 48.75 | 79.40 | 15386.22 | 158106.80 | 16-OCT-08:62 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 52.79 | 79.53 | 25231.25 | 194358.47 | 24-NOV-16:01 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 56.21 | 80.34 | 33881.28 | 221560.93 | 07-DEC-19:03 |
Annual Sum or Average | 0.01 | 15556.29 | ||||||
Minimum of Months | 0.00 | 0.00 | 29.74 | 29.74 | 885.25 | 44140.32 | ||
Maximum of Months | 0.12 | 382.71 | 79.88 | 80.34 | 35476.51 | 221560.93 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1472.61 | 40919.30 | 17-JAN-19:04 | 8.73 | 8.37 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 5014.28 | 177851.70 | 27-FEB-16:02 | 9.39 | 7.81 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 9458.93 | 228614.86 | 18-MAR-15:02 | 9.73 | 7.69 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 28818.14 | 389660.76 | 27-APR-18:03 | 10.34 | 6.87 | 0.00 | 0.00 | 01-APR-00:05 |
May | 48715.51 | 379435.57 | 05-MAY-18:02 | 10.66 | 7.28 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 75578.72 | 410038.20 | 28-JUN-18:03 | 10.54 | 6.90 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 115386.77 | 468774.74 | 31-JUL-18:03 | 10.92 | 6.74 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 137591.27 | 504116.44 | 10-AUG-18:03 | 11.19 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 67952.27 | 410456.17 | 14-SEP-15:03 | 10.76 | 7.11 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 19783.57 | 340741.13 | 04-OCT-15:02 | 10.50 | 7.47 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5119.50 | 252242.78 | 04-NOV-15:02 | 9.81 | 7.57 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 2344.21 | 49410.07 | 19-DEC-19:03 | 8.81 | 8.37 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 43402.19 | 0.00 | ||||||
Minimum of Months | 1472.61 | 40919.30 | 8.73 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 137591.27 | 504116.44 | 11.19 | 8.37 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 48.50 | 59.71 | 27446.20 | 68449.74 | 11-JAN-07:11 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 37.55 | 58.74 | 27623.55 | 68465.66 | 01-FEB-07:51 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 49.08 | 59.24 | 27328.96 | 68642.19 | 07-MAR-07:51 |
April | 0.00 | 0.00 | 01-APR-00:05 | 51.90 | 59.73 | 26606.49 | 66047.25 | 01-APR-07:11 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 51.91 | 58.99 | 25674.46 | 60849.28 | 19-MAY-06:14 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 52.22 | 59.02 | 24795.16 | 58820.16 | 15-JUN-06:38 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.88 | 59.66 | 24143.78 | 52501.01 | 03-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 52.68 | 59.50 | 23968.35 | 53374.20 | 18-AUG-06:37 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 52.66 | 59.49 | 24246.92 | 58025.01 | 27-SEP-06:55 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 51.55 | 58.83 | 24908.02 | 61489.80 | 13-OCT-06:11 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 51.56 | 58.69 | 25872.58 | 60478.41 | 19-NOV-07:51 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 49.37 | 59.42 | 26800.76 | 67787.61 | 28-DEC-07:01 |
Annual Sum or Average | 0.00 | 25773.92 | ||||||
Minimum of Months | 0.00 | 0.00 | 37.55 | 58.69 | 23968.35 | 52501.01 | ||
Maximum of Months | 0.00 | 0.00 | 52.88 | 59.73 | 27623.55 | 68642.19 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.450811E+11 | 0.00 | 0.305234E+09 | 0.334175E+11 | 0.00 | 0.00 |
February | 0.337642E+11 | 0.00 | 0.205599E+10 | 0.303218E+11 | 0.00 | 0.00 |
March | 0.353096E+11 | 0.00 | 0.420411E+10 | 0.347687E+11 | 0.00 | 0.00 |
April | 0.294846E+11 | 0.00 | 0.286744E+11 | 0.342965E+11 | 0.00 | 0.00 |
May | 0.257190E+11 | 0.00 | 0.552908E+11 | 0.363308E+11 | 0.00 | 0.00 |
June | 0.895561E+10 | 0.00 | 0.985683E+11 | 0.353395E+11 | 0.00 | 0.00 |
July | 0.246180E+10 | 0.00 | 0.167844E+12 | 0.372988E+11 | 0.00 | 0.00 |
August | 0.229327E+10 | 0.00 | 0.212712E+12 | 0.378723E+11 | 0.00 | 0.00 |
September | 0.944457E+10 | 0.00 | 0.808736E+11 | 0.355130E+11 | 0.00 | 0.00 |
October | 0.344299E+11 | 0.00 | 0.149364E+11 | 0.360095E+11 | 0.00 | 0.00 |
November | 0.407597E+11 | 0.00 | 0.365309E+10 | 0.336614E+11 | 0.00 | 0.00 |
December | 0.447300E+11 | 0.00 | 0.377485E+09 | 0.339541E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.312433E+12 | 0.00 | 0.669495E+12 | 0.418784E+12 | 0.00 | 0.00 |
Minimum of Months | 0.229327E+10 | 0.00 | 0.305234E+09 | 0.303218E+11 | 0.00 | 0.00 |
Maximum of Months | 0.450811E+11 | 0.00 | 0.212712E+12 | 0.378723E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.757373E+09 | 0.00 | 0.00 | 0.587890E+10 | 0.00 | 0.00 |
February | 0.440027E+09 | 0.00 | 0.332455E+09 | 0.530997E+10 | 0.00 | 0.00 |
March | 43850.61 | 0.00 | 0.656272E+09 | 0.587890E+10 | 0.00 | 0.00 |
April | 10297.38 | 0.00 | 0.473027E+10 | 0.568926E+10 | 0.00 | 0.00 |
May | 20408.65 | 0.00 | 0.970367E+10 | 0.587890E+10 | 0.00 | 0.00 |
June | 39911.50 | 0.00 | 0.167744E+11 | 0.568926E+10 | 0.00 | 0.00 |
July | 46517.19 | 0.00 | 0.301164E+11 | 0.587890E+10 | 0.00 | 0.00 |
August | 52882.47 | 0.00 | 0.384432E+11 | 0.587890E+10 | 0.00 | 0.00 |
September | 36426.23 | 0.00 | 0.144140E+11 | 0.568926E+10 | 0.00 | 0.00 |
October | 20022.12 | 0.00 | 0.254416E+10 | 0.587890E+10 | 0.00 | 0.00 |
November | 4380454.05 | 0.00 | 0.658452E+09 | 0.568926E+10 | 0.00 | 0.00 |
December | 0.229519E+09 | 0.00 | 7193.64 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.143157E+10 | 0.00 | 0.118373E+12 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 10297.38 | 0.00 | 0.00 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 0.757373E+09 | 0.00 | 0.384432E+11 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.334175E+11 | 0.305234E+09 | 0.450811E+11 | 0.408859E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.303218E+11 | 0.205599E+10 | 0.337642E+11 | 0.313363E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.347687E+11 | 0.420596E+10 | 0.353096E+11 | 0.226039E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.342965E+11 | 0.286744E+11 | 0.294846E+11 | 0.133169E+12 | 0.185321E+09 | 0.00 | 0.00 | 0.00 |
May | 0.363308E+11 | 0.552908E+11 | 0.257190E+11 | 0.717191E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.353395E+11 | 0.985683E+11 | 0.895561E+10 | 0.232756E+11 | 1444913.24 | 0.00 | 0.00 | 0.00 |
July | 0.372988E+11 | 0.167844E+12 | 0.246180E+10 | 0.841061E+10 | 0.237138E+10 | 0.00 | 0.00 | 0.00 |
August | 0.378723E+11 | 0.212712E+12 | 0.229327E+10 | 0.762315E+10 | 0.687223E+10 | 0.00 | 0.00 | 0.00 |
September | 0.355130E+11 | 0.808736E+11 | 0.944457E+10 | 0.250346E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.360095E+11 | 0.149367E+11 | 0.344299E+11 | 0.914248E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.336614E+11 | 0.365316E+10 | 0.407597E+11 | 0.227999E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.339541E+11 | 0.377488E+09 | 0.447300E+11 | 0.364912E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.418784E+12 | 0.669497E+12 | 0.312433E+12 | 0.190183E+13 | 0.943038E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.303218E+11 | 0.305234E+09 | 0.229327E+10 | 0.762315E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.378723E+11 | 0.212712E+12 | 0.450811E+11 | 0.408859E+12 | 0.687223E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.00 | 0.757373E+09 | 0.778261E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.332455E+09 | 0.440027E+09 | 0.613938E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.656272E+09 | 43850.61 | 0.500948E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.473027E+10 | 10297.38 | 0.335072E+11 | 0.236875E+09 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.970367E+10 | 20408.65 | 0.215303E+11 | 0.164330E+09 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.167744E+11 | 39911.50 | 0.805486E+10 | 0.180189E+09 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.301164E+11 | 46517.19 | 0.279146E+10 | 0.238681E+10 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.384432E+11 | 52882.47 | 0.207611E+10 | 0.517852E+10 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.144140E+11 | 36426.23 | 0.850301E+10 | 0.466123E+09 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.254416E+10 | 20022.12 | 0.278872E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.658452E+09 | 4380454.05 | 0.504869E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 7193.64 | 0.229519E+09 | 0.715974E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.118373E+12 | 0.143157E+10 | 0.415749E+12 | 0.861285E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.00 | 10297.38 | 0.207611E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.384432E+11 | 0.757373E+09 | 0.778261E+11 | 0.517852E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.334175E+11 | 0.450811E+11 | 0.305234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.303218E+11 | 0.337642E+11 | 0.205599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.347687E+11 | 0.353096E+11 | 0.420411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.342965E+11 | 0.294846E+11 | 0.286744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.363308E+11 | 0.257190E+11 | 0.552908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.353395E+11 | 0.895561E+10 | 0.985683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.372988E+11 | 0.246180E+10 | 0.167844E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.378723E+11 | 0.229327E+10 | 0.212712E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.355130E+11 | 0.944457E+10 | 0.808736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.360095E+11 | 0.344299E+11 | 0.149364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.336614E+11 | 0.407597E+11 | 0.365309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.339541E+11 | 0.447300E+11 | 0.377485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.418784E+12 | 0.312433E+12 | 0.669495E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.303218E+11 | 0.229327E+10 | 0.305234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.378723E+11 | 0.450811E+11 | 0.212712E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 0.757373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.440027E+09 | 0.332455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 43850.61 | 0.656272E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 10297.38 | 0.473027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 20408.65 | 0.970367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 39911.50 | 0.167744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 46517.19 | 0.301164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 52882.47 | 0.384432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 36426.23 | 0.144140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 20022.12 | 0.254416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 4380454.05 | 0.658452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.229519E+09 | 7193.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.143157E+10 | 0.118373E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 10297.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.757373E+09 | 0.384432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.278285E+11 | 0.00 | 0.00 | 24216832.50 | 0.00 | 0.00 | 0.199923E+11 | 0.00 | 0.92 |
February | 0.328880E+11 | 0.00 | 0.00 | 10248514.80 | 0.00 | 0.00 | 0.102834E+11 | 0.00 | 0.92 |
March | 0.420264E+11 | 0.00 | 0.00 | 4520974.64 | 0.00 | 0.00 | 0.683387E+10 | 0.00 | 0.90 |
April | 0.416558E+11 | 0.00 | 0.00 | 1678834.00 | 5884248.33 | 0.00 | 0.420263E+10 | 0.00 | 0.91 |
May | 0.394766E+11 | 0.00 | 0.00 | 2787745.37 | 0.00 | 0.00 | 0.606874E+10 | 0.00 | 0.93 |
June | 0.316327E+11 | 0.00 | 0.00 | 5206330.09 | 0.00 | 0.00 | 0.760050E+10 | 0.00 | 0.96 |
July | 0.191139E+11 | 4879029.82 | 0.00 | 11120146.43 | 89021532.71 | 0.00 | 0.156264E+11 | 0.00 | 0.97 |
August | 0.861715E+10 | 11508702.24 | 0.00 | 19456551.18 | 0.318966E+09 | 0.00 | 0.228217E+11 | 0.00 | 0.98 |
September | 0.107218E+11 | 0.00 | 0.00 | 33470451.07 | 0.00 | 0.00 | 0.317965E+11 | 0.00 | 0.99 |
October | 0.116694E+11 | 0.00 | 0.00 | 61599146.78 | 0.00 | 0.00 | 0.415248E+11 | 0.00 | 0.99 |
November | 0.860977E+10 | 0.00 | 0.00 | 76757564.38 | 0.00 | 0.00 | 0.421849E+11 | 0.00 | 0.97 |
December | 0.170941E+11 | 0.00 | 0.00 | 58230408.01 | 0.00 | 0.00 | 0.330875E+11 | 0.00 | 0.95 |
Annual Sum or Average | 0.291334E+12 | 16387732.06 | 0.00 | 0.309293E+09 | 0.413872E+09 | 0.00 | 0.242023E+12 | 0.00 | 0.95 |
Minimum of Months | 0.860977E+10 | 0.00 | 0.00 | 1678834.00 | 0.00 | 0.00 | 0.420263E+10 | 0.00 | 0.90 |
Maximum of Months | 0.420264E+11 | 11508702.24 | 0.00 | 76757564.38 | 0.318966E+09 | 0.00 | 0.421849E+11 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.630337E+10 | 0.00 | 0.00 | 77443.48 | 0.00 | 0.228825E+10 | 70887461.48 | 0.00 | 3.03 |
February | 0.674917E+10 | 0.00 | 0.00 | 494184.90 | 0.00 | 0.920675E+09 | 0.301215E+09 | 0.00 | 3.06 |
March | 0.852400E+10 | 0.00 | 0.00 | 715454.32 | 0.00 | 66318957.62 | 0.493292E+09 | 0.00 | 3.03 |
April | 0.807530E+10 | 1449072.41 | 0.00 | 615995.52 | 0.00 | 29576558.70 | 0.388978E+09 | 0.00 | 3.05 |
May | 0.803696E+10 | 0.00 | 0.00 | 662963.42 | 0.00 | 12895102.30 | 0.385159E+09 | 0.00 | 3.12 |
June | 0.703120E+10 | 0.00 | 0.00 | 346090.61 | 0.00 | 2057521.75 | 0.229612E+09 | 0.00 | 3.20 |
July | 0.605222E+10 | 15228749.05 | 0.00 | 908175.48 | 2888366.22 | 0.00 | 0.349146E+09 | 0.00 | 3.25 |
August | 0.533133E+10 | 66408907.00 | 0.00 | 1183388.71 | 4727780.27 | 0.00 | 0.403964E+09 | 0.00 | 3.29 |
September | 0.680974E+10 | 0.00 | 0.00 | 2283495.46 | 0.00 | 7898411.62 | 0.835072E+09 | 0.00 | 3.29 |
October | 0.838821E+10 | 0.00 | 0.00 | 1115644.83 | 0.00 | 50792618.24 | 0.729230E+09 | 0.00 | 3.11 |
November | 0.799134E+10 | 0.00 | 0.00 | 258029.96 | 0.00 | 0.536329E+09 | 0.128805E+09 | 0.00 | 3.03 |
December | 0.638956E+10 | 0.00 | 0.00 | 260581.84 | 0.00 | 0.218195E+10 | 0.190784E+09 | 0.00 | 3.02 |
Annual Sum or Average | 0.856824E+11 | 83086728.46 | 0.00 | 8921448.54 | 7616146.49 | 0.609674E+10 | 0.450615E+10 | 0.00 | 3.12 |
Minimum of Months | 0.533133E+10 | 0.00 | 0.00 | 77443.48 | 0.00 | 0.00 | 70887461.48 | 0.00 | 3.02 |
Maximum of Months | 0.852400E+10 | 66408907.00 | 0.00 | 2283495.46 | 4727780.27 | 0.228825E+10 | 0.835072E+09 | 0.00 | 3.29 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.436961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 |
February | 0.394219E+10 | 0.00 | 0.00 | 22267.59 | 0.00 | 0.00 | 67035690.07 | 0.00 | 1.33 |
March | 0.436816E+10 | 0.00 | 0.00 | 81241.99 | 0.00 | 0.00 | 0.190270E+09 | 0.00 | 1.32 |
April | 0.376015E+10 | 0.00 | 0.00 | 338699.93 | 549452.37 | 0.00 | 0.529717E+09 | 0.00 | 1.33 |
May | 0.327102E+10 | 0.00 | 0.00 | 716613.51 | 0.00 | 0.00 | 0.996759E+09 | 0.00 | 1.37 |
June | 0.248697E+10 | 0.00 | 0.00 | 944471.96 | 0.00 | 0.00 | 0.119903E+10 | 0.00 | 1.41 |
July | 0.150461E+10 | 5039040.11 | 0.00 | 1741253.47 | 3766296.38 | 0.00 | 0.178891E+10 | 0.00 | 1.45 |
August | 0.131278E+10 | 16637716.05 | 0.00 | 2083307.45 | 14507581.88 | 0.00 | 0.164169E+10 | 0.00 | 1.46 |
September | 0.245683E+10 | 0.00 | 0.00 | 1268533.95 | 0.00 | 0.00 | 0.141682E+10 | 0.00 | 1.42 |
October | 0.404546E+10 | 0.00 | 0.00 | 332961.79 | 0.00 | 0.00 | 0.552974E+09 | 0.00 | 1.34 |
November | 0.430412E+10 | 0.00 | 0.00 | 11997.75 | 0.00 | 0.00 | 57025155.57 | 0.00 | 1.32 |
December | 0.440756E+10 | 0.00 | 0.00 | 3552.09 | 0.00 | 0.00 | 10817232.79 | 0.00 | 1.32 |
Annual Sum or Average | 0.402295E+11 | 21676756.16 | 0.00 | 7544901.48 | 18823330.63 | 0.00 | 0.845105E+10 | 0.00 | 1.37 |
Minimum of Months | 0.131278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 |
Maximum of Months | 0.440756E+10 | 16637716.05 | 0.00 | 2083307.45 | 14507581.88 | 0.00 | 0.178891E+10 | 0.00 | 1.46 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.395423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24211429.09 | 0.00 | 0.00 | 0.57 |
February | 0.365004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 297734.64 | 0.00 | 0.00 | 0.57 |
March | 0.415043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
April | 0.389891E+10 | 0.00 | 0.00 | 0.00 | 500264.50 | 0.00 | 0.00 | 0.00 | 0.57 |
May | 0.387010E+10 | 0.00 | 0.00 | 193.32 | 0.00 | 0.00 | 2016815.10 | 0.00 | 0.59 |
June | 0.327181E+10 | 0.00 | 0.00 | 32153.76 | 0.00 | 0.00 | 64106008.95 | 0.00 | 0.60 |
July | 0.268869E+10 | 198182.47 | 0.00 | 261364.80 | 7785015.30 | 0.00 | 0.254134E+09 | 0.00 | 0.61 |
August | 0.235173E+10 | 1325944.77 | 0.00 | 447449.99 | 26803627.52 | 0.00 | 0.288602E+09 | 0.00 | 0.61 |
September | 0.341022E+10 | 0.00 | 0.00 | 58666.37 | 0.00 | 0.00 | 73479776.93 | 0.00 | 0.60 |
October | 0.418127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
November | 0.397074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
December | 0.401544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7397102.98 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.434136E+11 | 1524127.25 | 0.00 | 799828.25 | 35088907.32 | 31906266.71 | 0.682338E+09 | 0.00 | 0.58 |
Minimum of Months | 0.235173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.418127E+10 | 1325944.77 | 0.00 | 447449.99 | 26803627.52 | 24211429.09 | 0.288602E+09 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.166667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250288E+09 | 0.00 | 0.00 | 0.47 |
February | 0.161067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148193E+09 | 0.00 | 0.00 | 0.48 |
March | 0.199960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 231611.26 | 0.00 | 0.00 | 0.47 |
April | 0.187864E+10 | 0.00 | 0.00 | 0.00 | 241046.08 | 0.00 | 0.00 | 0.00 | 0.48 |
May | 0.186573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 0.160739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
July | 0.141439E+10 | 0.00 | 0.00 | 1315.39 | 3846602.20 | 0.00 | 2274173.98 | 0.00 | 0.51 |
August | 0.126097E+10 | 140826.55 | 0.00 | 8197.41 | 13396253.96 | 0.00 | 7256559.66 | 0.00 | 0.51 |
September | 0.167860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
October | 0.201469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
November | 0.191218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1066599.57 | 0.00 | 0.00 | 0.47 |
December | 0.179832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140038E+09 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.207079E+11 | 140826.55 | 0.00 | 9512.80 | 17483902.25 | 0.539818E+09 | 9530733.63 | 0.00 | 0.49 |
Minimum of Months | 0.126097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.201469E+10 | 140826.55 | 0.00 | 8197.41 | 13396253.96 | 0.250288E+09 | 7256559.66 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112713E+10 | 0.00 | 0.00 | 0.148702E+09 | 0.00 | 0.00 | 0.693350E+11 | 0.00 | 20.83 |
February | 0.934178E+09 | 0.00 | 0.00 | 0.122034E+09 | 0.00 | 0.00 | 0.635408E+11 | 0.00 | 21.00 |
March | 0.856175E+09 | 0.00 | 0.00 | 0.156337E+09 | 0.00 | 0.00 | 0.733778E+11 | 0.00 | 21.01 |
April | 0.175768E+10 | 7501209.62 | 0.00 | 0.139303E+09 | 0.00 | 0.00 | 0.674688E+11 | 0.00 | 21.15 |
May | 0.201856E+10 | 0.00 | 0.00 | 0.125779E+09 | 0.00 | 0.00 | 0.669759E+11 | 0.00 | 21.79 |
June | 0.614667E+09 | 0.00 | 0.00 | 0.101550E+09 | 0.00 | 0.00 | 0.582137E+11 | 0.00 | 22.42 |
July | 85965541.42 | 0.130517E+09 | 0.00 | 99742781.43 | 29059.38 | 0.00 | 0.513480E+11 | 0.00 | 22.60 |
August | 0.129136E+09 | 0.445219E+09 | 0.00 | 93888751.52 | 891167.52 | 0.00 | 0.460542E+11 | 0.00 | 22.59 |
September | 0.530094E+09 | 0.00 | 0.00 | 0.101090E+09 | 0.00 | 0.00 | 0.611063E+11 | 0.00 | 22.39 |
October | 0.183400E+10 | 0.00 | 0.00 | 0.134606E+09 | 0.00 | 0.00 | 0.724991E+11 | 0.00 | 21.38 |
November | 0.793437E+09 | 0.00 | 0.00 | 0.155391E+09 | 0.00 | 0.00 | 0.695757E+11 | 0.00 | 20.84 |
December | 0.763487E+09 | 0.00 | 0.00 | 0.177737E+09 | 0.00 | 0.00 | 0.705051E+11 | 0.00 | 20.67 |
Annual Sum or Average | 0.114445E+11 | 0.583237E+09 | 0.00 | 0.155616E+10 | 920226.91 | 0.00 | 0.770000E+12 | 0.00 | 21.56 |
Minimum of Months | 85965541.42 | 0.00 | 0.00 | 93888751.52 | 0.00 | 0.00 | 0.460542E+11 | 0.00 | 20.67 |
Maximum of Months | 0.201856E+10 | 0.445219E+09 | 0.00 | 0.177737E+09 | 891167.52 | 0.00 | 0.733778E+11 | 0.00 | 22.60 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.315899E+11 | 0.00 | 0.00 | 934795.53 | 0.00 | 4458069.02 | 0.181418E+10 | 0.00 | 4.16 |
February | 0.244500E+11 | 0.00 | 0.00 | 4483345.59 | 0.00 | 0.00 | 0.632584E+10 | 0.00 | 4.21 |
March | 0.235352E+11 | 0.00 | 0.00 | 7195816.03 | 0.00 | 703715.05 | 0.115537E+11 | 0.00 | 4.18 |
April | 0.196128E+11 | 5228754.32 | 0.00 | 8560363.35 | 0.00 | 0.00 | 0.131643E+11 | 0.00 | 4.20 |
May | 0.167679E+11 | 0.00 | 0.00 | 10785073.66 | 0.00 | 0.00 | 0.157674E+11 | 0.00 | 4.29 |
June | 0.109870E+11 | 0.00 | 0.00 | 11702806.21 | 0.00 | 0.00 | 0.170080E+11 | 0.00 | 4.41 |
July | 0.708281E+10 | 63183057.40 | 0.00 | 17513479.61 | 5591042.57 | 0.00 | 0.175953E+11 | 0.00 | 4.47 |
August | 0.579374E+10 | 0.255101E+09 | 0.00 | 18971333.63 | 7814214.90 | 0.00 | 0.163523E+11 | 0.00 | 4.51 |
September | 0.108513E+11 | 0.00 | 0.00 | 20373610.40 | 0.00 | 0.00 | 0.186483E+11 | 0.00 | 4.52 |
October | 0.205117E+11 | 0.00 | 0.00 | 11121507.88 | 0.00 | 3681669.12 | 0.148643E+11 | 0.00 | 4.27 |
November | 0.277040E+11 | 0.00 | 0.00 | 2638886.40 | 0.00 | 593961.86 | 0.569540E+10 | 0.00 | 4.17 |
December | 0.306853E+11 | 0.00 | 0.00 | 2240099.72 | 0.00 | 4108273.72 | 0.312589E+10 | 0.00 | 4.14 |
Annual Sum or Average | 0.229572E+12 | 0.323513E+09 | 0.00 | 0.116521E+09 | 13405257.47 | 13545688.77 | 0.141915E+12 | 0.00 | 4.29 |
Minimum of Months | 0.579374E+10 | 0.00 | 0.00 | 934795.53 | 0.00 | 0.00 | 0.181418E+10 | 0.00 | 4.14 |
Maximum of Months | 0.315899E+11 | 0.255101E+09 | 0.00 | 20373610.40 | 7814214.90 | 4458069.02 | 0.186483E+11 | 0.00 | 4.52 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.869305E+11 | 0.00 | 0.00 | 1842226.89 | 0.00 | 0.00 | 0.508479E+10 | 0.00 | 1.66 |
February | 0.708882E+11 | 0.00 | 0.00 | 7669304.86 | 0.00 | 0.00 | 0.136403E+11 | 0.00 | 1.67 |
March | 0.631478E+11 | 0.00 | 0.00 | 25069901.01 | 0.00 | 0.00 | 0.333634E+11 | 0.00 | 1.66 |
April | 0.525332E+11 | 11470501.58 | 0.00 | 33085253.88 | 96272.23 | 0.00 | 0.383422E+11 | 0.00 | 1.68 |
May | 0.417517E+11 | 0.00 | 0.00 | 50833255.74 | 0.00 | 0.00 | 0.492758E+11 | 0.00 | 1.73 |
June | 0.282185E+11 | 0.00 | 0.00 | 54363765.28 | 0.00 | 0.00 | 0.503697E+11 | 0.00 | 1.79 |
July | 0.144021E+11 | 0.155686E+09 | 0.00 | 73006468.57 | 29400442.10 | 0.00 | 0.562536E+11 | 0.00 | 1.84 |
August | 0.123544E+11 | 0.581085E+09 | 0.00 | 77374640.93 | 73309776.87 | 0.00 | 0.517192E+11 | 0.00 | 1.86 |
September | 0.251224E+11 | 0.00 | 0.00 | 69679478.02 | 0.00 | 0.00 | 0.576965E+11 | 0.00 | 1.81 |
October | 0.532651E+11 | 0.00 | 0.00 | 38371332.00 | 0.00 | 0.00 | 0.443555E+11 | 0.00 | 1.70 |
November | 0.746678E+11 | 0.00 | 0.00 | 8683778.66 | 0.00 | 0.00 | 0.172306E+11 | 0.00 | 1.66 |
December | 0.844294E+11 | 0.00 | 0.00 | 4486352.15 | 0.00 | 0.00 | 0.864591E+10 | 0.00 | 1.65 |
Annual Sum or Average | 0.607711E+12 | 0.748241E+09 | 0.00 | 0.444466E+09 | 0.102806E+09 | 0.00 | 0.425978E+12 | 0.00 | 1.73 |
Minimum of Months | 0.123544E+11 | 0.00 | 0.00 | 1842226.89 | 0.00 | 0.00 | 0.508479E+10 | 0.00 | 1.65 |
Maximum of Months | 0.869305E+11 | 0.581085E+09 | 0.00 | 77374640.93 | 73309776.87 | 0.00 | 0.576965E+11 | 0.00 | 1.86 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.338508E+09 | 0.00 | 0.00 | 125366.84 | 0.00 | 0.110231E+10 | 6685546.12 | 0.00 | 0.47 |
February | 0.350488E+09 | 0.00 | 0.00 | 1274270.94 | 0.00 | 0.899590E+09 | 0.147441E+09 | 0.00 | 0.47 |
March | 0.426061E+09 | 0.00 | 0.00 | 3361642.29 | 0.00 | 0.839564E+09 | 0.404125E+09 | 0.00 | 0.47 |
April | 0.363840E+09 | 2081360.56 | 0.00 | 6603529.87 | 20255.75 | 0.432550E+09 | 0.799940E+09 | 0.00 | 0.47 |
May | 0.265821E+09 | 3777161.81 | 5444.62 | 11535756.29 | 157281.01 | 0.143696E+09 | 0.114016E+10 | 126.61 | 0.47 |
June | 0.207474E+09 | 1637055.62 | 0.00 | 12239501.53 | 149824.94 | 22841098.01 | 0.108717E+10 | 0.00 | 0.47 |
July | 0.114544E+09 | 37858400.61 | 2514.80 | 12626766.58 | 791369.48 | 1779943.99 | 0.921644E+09 | 604.94 | 0.47 |
August | 0.100853E+09 | 77010235.28 | 40563.97 | 9505630.28 | 2913716.93 | 1621325.61 | 0.728269E+09 | 4200.84 | 0.48 |
September | 0.236873E+09 | 13923012.25 | 2200.10 | 10434610.78 | 439011.56 | 52183175.07 | 0.104348E+10 | 406.48 | 0.47 |
October | 0.383704E+09 | 0.00 | 0.00 | 4875793.15 | 0.00 | 0.579811E+09 | 0.724700E+09 | 0.00 | 0.47 |
November | 0.371695E+09 | 66290.29 | 0.00 | 571647.52 | 0.00 | 0.984795E+09 | 0.127147E+09 | 0.00 | 0.47 |
December | 0.333441E+09 | 0.00 | 0.00 | 253553.51 | 0.00 | 0.111346E+10 | 31431577.34 | 0.00 | 0.47 |
Annual Sum or Average | 0.349330E+10 | 0.136354E+09 | 50723.48 | 73408069.58 | 4471459.66 | 0.617421E+10 | 0.716219E+10 | 5338.87 | 0.47 |
Minimum of Months | 0.100853E+09 | 0.00 | 0.00 | 125366.84 | 0.00 | 1621325.61 | 6685546.12 | 0.00 | 0.47 |
Maximum of Months | 0.426061E+09 | 77010235.28 | 40563.97 | 12626766.58 | 2913716.93 | 0.111346E+10 | 0.114016E+10 | 4200.84 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.279547E+09 | 0.00 | 0.00 | 59151.86 | 0.00 | 0.116359E+10 | 4262535.20 | 0.00 | 0.47 |
February | 0.346252E+09 | 0.00 | 0.00 | 383978.84 | 0.00 | 0.995421E+09 | 56572476.86 | 0.00 | 0.47 |
March | 0.474016E+09 | 0.00 | 0.00 | 1465853.33 | 0.00 | 0.995831E+09 | 0.201603E+09 | 0.00 | 0.47 |
April | 0.426413E+09 | 2029608.76 | 0.00 | 4424671.80 | 71761.31 | 0.549324E+09 | 0.622585E+09 | 0.00 | 0.47 |
May | 0.341994E+09 | 3701862.71 | 4600.26 | 9686340.83 | 232119.13 | 0.174785E+09 | 0.103456E+10 | 970.31 | 0.47 |
June | 0.258255E+09 | 1611062.42 | 0.00 | 10997858.04 | 175608.77 | 26645789.61 | 0.103367E+10 | 0.00 | 0.47 |
July | 0.139745E+09 | 37242365.10 | 2365.21 | 11413984.41 | 1402876.60 | 1648939.40 | 0.897663E+09 | 754.17 | 0.47 |
August | 0.122809E+09 | 73573651.18 | 37041.81 | 8326970.00 | 6340936.77 | 1763973.79 | 0.707251E+09 | 7717.76 | 0.48 |
September | 0.287567E+09 | 11753781.37 | 11067.41 | 7614650.78 | 2593774.29 | 67593908.11 | 0.980034E+09 | 4324.29 | 0.47 |
October | 0.457796E+09 | 0.00 | 0.00 | 2346338.28 | 0.00 | 0.753246E+09 | 0.479504E+09 | 0.00 | 0.47 |
November | 0.371672E+09 | 63269.15 | 1842.40 | 196353.94 | 0.00 | 0.104173E+10 | 70439710.59 | 1170.98 | 0.47 |
December | 0.304963E+09 | 0.00 | 0.00 | 76267.48 | 0.00 | 0.116967E+10 | 3708636.40 | 0.00 | 0.47 |
Annual Sum or Average | 0.381103E+10 | 0.129976E+09 | 56917.09 | 56992419.60 | 10817076.87 | 0.694125E+10 | 0.609186E+10 | 14937.51 | 0.47 |
Minimum of Months | 0.122809E+09 | 0.00 | 0.00 | 59151.86 | 0.00 | 1648939.40 | 3708636.40 | 0.00 | 0.47 |
Maximum of Months | 0.474016E+09 | 73573651.18 | 37041.81 | 11413984.41 | 6340936.77 | 0.116967E+10 | 0.103456E+10 | 7717.76 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132855E+11 | 0.00 | 0.00 | 143781.54 | 0.00 | 0.626596E+10 | 76921191.19 | 0.00 | 0.53 |
February | 0.158452E+11 | 0.00 | 0.00 | 14268637.40 | 0.00 | 0.148639E+10 | 0.162048E+10 | 0.00 | 0.54 |
March | 0.175300E+11 | 0.00 | 0.00 | 28588424.06 | 0.00 | 0.00 | 0.512733E+10 | 0.00 | 0.54 |
April | 0.134440E+11 | 28496032.19 | 0.00 | 36443433.60 | 0.00 | 0.00 | 0.825389E+10 | 0.00 | 0.54 |
May | 0.111198E+11 | 53423056.81 | 0.00 | 48196230.80 | 0.00 | 0.00 | 0.100006E+11 | 0.00 | 0.54 |
June | 0.774582E+10 | 24228497.68 | 0.00 | 55884508.53 | 0.00 | 0.00 | 0.102282E+11 | 0.00 | 0.54 |
July | 0.494462E+10 | 0.524099E+09 | 0.00 | 58529920.98 | 0.00 | 0.00 | 0.924197E+10 | 0.00 | 0.54 |
August | 0.402009E+10 | 0.108430E+10 | 0.00 | 45152334.45 | 0.00 | 0.00 | 0.732778E+10 | 0.00 | 0.54 |
September | 0.761580E+10 | 0.194772E+09 | 0.00 | 67129338.95 | 0.00 | 0.00 | 0.105265E+11 | 0.00 | 0.54 |
October | 0.151110E+11 | 0.00 | 0.00 | 46127328.49 | 0.00 | 0.00 | 0.779968E+10 | 0.00 | 0.54 |
November | 0.180170E+11 | 898836.90 | 0.00 | 4440882.73 | 0.00 | 0.122160E+10 | 0.881482E+09 | 0.00 | 0.53 |
December | 0.135053E+11 | 0.00 | 0.00 | 6109085.01 | 0.00 | 0.569383E+10 | 0.843094E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.142184E+12 | 0.191022E+10 | 0.00 | 0.411014E+09 | 0.00 | 0.146678E+11 | 0.719279E+11 | 0.00 | 0.54 |
Minimum of Months | 0.402009E+10 | 0.00 | 0.00 | 143781.54 | 0.00 | 0.00 | 76921191.19 | 0.00 | 0.53 |
Maximum of Months | 0.180170E+11 | 0.108430E+10 | 0.00 | 67129338.95 | 0.00 | 0.626596E+10 | 0.105265E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.518774E+10 | 0.00 | 0.00 | 9457203.74 | 0.00 | 0.104333E+11 | 0.400344E+10 | 0.00 | 0.53 |
February | 0.520814E+10 | 0.00 | 0.00 | 15409191.59 | 0.00 | 0.741428E+10 | 0.633374E+10 | 0.00 | 0.54 |
March | 0.649696E+10 | 0.00 | 0.00 | 37754347.05 | 0.00 | 0.167570E+10 | 0.144817E+11 | 0.00 | 0.54 |
April | 0.614902E+10 | 12017307.95 | 51149.59 | 68986776.89 | 16430197.62 | 98883855.51 | 0.154234E+11 | 5169.22 | 0.54 |
May | 0.569640E+10 | 25683752.59 | 80434.64 | 98682378.87 | 27671858.75 | 49240175.06 | 0.153301E+11 | 1619.27 | 0.54 |
June | 0.444812E+10 | 15974212.24 | 0.00 | 96536845.77 | 8260910.68 | 25226720.72 | 0.134650E+11 | 0.00 | 0.54 |
July | 0.269848E+10 | 0.294521E+09 | 259419.80 | 86245864.43 | 0.229450E+09 | 16239205.69 | 0.114480E+11 | 11007.30 | 0.54 |
August | 0.208712E+10 | 0.528874E+09 | 508108.66 | 69632087.92 | 0.555203E+09 | 12968265.98 | 0.922641E+10 | 15950.61 | 0.54 |
September | 0.445460E+10 | 68656075.36 | 313292.98 | 65833864.75 | 0.125831E+09 | 47360971.52 | 0.136466E+11 | 24585.83 | 0.54 |
October | 0.640889E+10 | 0.00 | 0.00 | 50764033.78 | 0.00 | 0.159034E+09 | 0.163444E+11 | 0.00 | 0.54 |
November | 0.535592E+10 | 866972.57 | 22832.29 | 23092511.03 | 5531.78 | 0.499436E+10 | 0.975668E+10 | 3746.05 | 0.54 |
December | 0.537785E+10 | 0.00 | 0.00 | 10039270.03 | 0.00 | 0.999670E+10 | 0.466925E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.595692E+11 | 0.946594E+09 | 1235237.97 | 0.632434E+09 | 0.962852E+09 | 0.349233E+11 | 0.134129E+12 | 62078.27 | 0.54 |
Minimum of Months | 0.208712E+10 | 0.00 | 0.00 | 9457203.74 | 0.00 | 12968265.98 | 0.400344E+10 | 0.00 | 0.53 |
Maximum of Months | 0.649696E+10 | 0.528874E+09 | 508108.66 | 98682378.87 | 0.555203E+09 | 0.104333E+11 | 0.163444E+11 | 24585.83 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.341156E+09 | 0.00 | 0.00 | 97375.98 | 0.00 | 0.109309E+10 | 13280431.80 | 0.00 | 0.47 |
February | 0.369246E+09 | 0.00 | 0.00 | 850494.71 | 0.00 | 0.901384E+09 | 0.127313E+09 | 0.00 | 0.47 |
March | 0.408207E+09 | 0.00 | 0.00 | 3602187.90 | 0.00 | 0.826954E+09 | 0.434348E+09 | 0.00 | 0.47 |
April | 0.298720E+09 | 2022647.20 | 0.00 | 8008355.33 | 78969.10 | 0.417261E+09 | 0.878944E+09 | 0.00 | 0.47 |
May | 0.231001E+09 | 3715024.24 | 4314.53 | 11067881.98 | 219418.58 | 0.180468E+09 | 0.113867E+10 | 1256.69 | 0.47 |
June | 0.145879E+09 | 1555457.94 | 0.00 | 14269813.41 | 231422.61 | 32036421.21 | 0.113754E+10 | 0.00 | 0.47 |
July | 91421405.79 | 37078062.21 | 14710.70 | 12922431.28 | 1556473.52 | 1606414.36 | 0.944644E+09 | 3643.41 | 0.47 |
August | 74329540.88 | 77538201.29 | 18331.05 | 10957295.61 | 2409532.17 | 1352403.86 | 0.753610E+09 | 2652.52 | 0.48 |
September | 0.222326E+09 | 13182114.84 | 13187.87 | 10564002.99 | 1167122.03 | 59237460.75 | 0.105084E+10 | 2205.63 | 0.47 |
October | 0.350780E+09 | 0.00 | 0.00 | 5261900.89 | 0.00 | 0.593694E+09 | 0.743355E+09 | 0.00 | 0.47 |
November | 0.376617E+09 | 63276.56 | 2112.22 | 615583.89 | 0.00 | 0.973621E+09 | 0.133356E+09 | 901.52 | 0.47 |
December | 0.332455E+09 | 0.00 | 0.00 | 405802.38 | 0.00 | 0.110693E+10 | 38795516.75 | 0.00 | 0.47 |
Annual Sum or Average | 0.324214E+10 | 0.135155E+09 | 52656.37 | 78623126.34 | 5662938.02 | 0.618764E+10 | 0.739470E+10 | 10659.77 | 0.47 |
Minimum of Months | 74329540.88 | 0.00 | 0.00 | 97375.98 | 0.00 | 1352403.86 | 13280431.80 | 0.00 | 0.47 |
Maximum of Months | 0.408207E+09 | 77538201.29 | 18331.05 | 14269813.41 | 2409532.17 | 0.110693E+10 | 0.113867E+10 | 3643.41 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.248980E+09 | 0.00 | 0.00 | 68446.23 | 0.00 | 0.119358E+10 | 4826466.61 | 0.00 | 0.47 |
February | 0.354708E+09 | 0.00 | 0.00 | 228598.62 | 0.00 | 0.982744E+09 | 60949741.57 | 0.00 | 0.47 |
March | 0.478971E+09 | 0.00 | 0.00 | 1273334.64 | 0.00 | 0.966324E+09 | 0.226347E+09 | 0.00 | 0.47 |
April | 0.424024E+09 | 1976030.38 | 0.00 | 5355365.10 | 124714.46 | 0.508232E+09 | 0.665134E+09 | 625.23 | 0.47 |
May | 0.303196E+09 | 3661172.48 | 3667.22 | 9025580.81 | 272809.37 | 0.223788E+09 | 0.102502E+10 | 1903.35 | 0.47 |
June | 0.174996E+09 | 1505821.55 | 0.00 | 12886083.81 | 280849.64 | 36794056.82 | 0.110490E+10 | 0.00 | 0.47 |
July | 0.102758E+09 | 36678535.20 | 14800.07 | 11594972.87 | 1951473.93 | 1674511.72 | 0.934444E+09 | 3551.89 | 0.47 |
August | 93455659.69 | 76357186.97 | 6550.51 | 9638778.19 | 3592119.68 | 1377998.56 | 0.735678E+09 | 3490.37 | 0.48 |
September | 0.271466E+09 | 11765980.73 | 32927.13 | 7360977.89 | 2559170.84 | 94025695.75 | 0.969957E+09 | 4868.65 | 0.47 |
October | 0.465448E+09 | 0.00 | 0.00 | 2348284.83 | 0.00 | 0.750091E+09 | 0.475004E+09 | 0.00 | 0.47 |
November | 0.367595E+09 | 63915.29 | 255.71 | 193785.72 | 407.82 | 0.103875E+10 | 77497668.97 | 1703.71 | 0.47 |
December | 0.291757E+09 | 0.00 | 0.00 | 88589.03 | 0.00 | 0.117665E+10 | 9918754.86 | 0.00 | 0.47 |
Annual Sum or Average | 0.357735E+10 | 0.132009E+09 | 58200.63 | 60062797.73 | 8781545.74 | 0.697404E+10 | 0.628967E+10 | 16143.20 | 0.47 |
Minimum of Months | 93455659.69 | 0.00 | 0.00 | 68446.23 | 0.00 | 1377998.56 | 4826466.61 | 0.00 | 0.47 |
Maximum of Months | 0.478971E+09 | 76357186.97 | 32927.13 | 12886083.81 | 3592119.68 | 0.119358E+10 | 0.110490E+10 | 4868.65 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.279094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567767E+09 | 0.00 | 0.00 | 0.56 |
February | 0.260816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47108484.22 | 0.00 | 0.00 | 0.56 |
March | 0.297054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2904589.62 | 0.00 | 0.00 | 0.55 |
April | 0.279079E+11 | 0.00 | 0.00 | 0.00 | 3580833.68 | 0.00 | 0.00 | 0.00 | 0.56 |
May | 0.277162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.238784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.208554E+11 | 711570.59 | 0.00 | 183661.68 | 56431207.64 | 0.00 | 0.189479E+09 | 0.00 | 0.60 |
August | 0.179511E+11 | 23252528.29 | 0.00 | 1042804.25 | 0.177867E+09 | 0.00 | 0.889103E+09 | 0.00 | 0.60 |
September | 0.247062E+11 | 0.00 | 0.00 | 46847.90 | 0.00 | 0.00 | 0.230074E+09 | 0.00 | 0.59 |
October | 0.299291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
November | 0.283078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114268E+09 | 0.00 | 0.00 | 0.56 |
December | 0.279987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.796258E+09 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.312947E+12 | 23964098.88 | 0.00 | 1273313.83 | 0.237879E+09 | 0.152831E+10 | 0.130866E+10 | 0.00 | 0.57 |
Minimum of Months | 0.179511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.299291E+11 | 23252528.29 | 0.00 | 1042804.25 | 0.177867E+09 | 0.796258E+09 | 0.889103E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 58828780.71 | 0.00 | 0.00 | 19405.39 | 0.00 | 0.302209E+09 | 850270.87 | 0.00 | 0.47 |
February | 78032861.88 | 0.00 | 0.00 | 295334.52 | 0.00 | 0.247922E+09 | 23448226.46 | 0.00 | 0.47 |
March | 0.106554E+09 | 0.00 | 0.00 | 761203.32 | 0.00 | 0.241162E+09 | 69800106.52 | 0.00 | 0.47 |
April | 90244381.26 | 520340.14 | 0.00 | 1479116.14 | 5063.94 | 0.153831E+09 | 0.155179E+09 | 0.00 | 0.47 |
May | 66313470.80 | 945683.26 | 0.00 | 2648566.04 | 39320.25 | 86005870.87 | 0.235334E+09 | 0.00 | 0.47 |
June | 51422077.74 | 417789.98 | 0.00 | 2888687.86 | 28930.16 | 25909312.39 | 0.252212E+09 | 0.00 | 0.47 |
July | 29039273.98 | 9472429.22 | 743.28 | 2973465.59 | 190013.30 | 538156.89 | 0.230098E+09 | 36.66 | 0.47 |
August | 26318850.67 | 19271401.00 | 5191.41 | 2090345.11 | 714654.51 | 2241392.58 | 0.179412E+09 | 932.33 | 0.48 |
September | 59510215.04 | 3504617.68 | 1426.36 | 2352745.72 | 85091.00 | 42869065.24 | 0.231010E+09 | 22.55 | 0.47 |
October | 97805299.39 | 0.00 | 0.00 | 1008991.05 | 0.00 | 0.197445E+09 | 0.127014E+09 | 0.00 | 0.47 |
November | 85222012.00 | 16572.57 | 0.00 | 118847.04 | 0.00 | 0.265153E+09 | 20558692.30 | 0.00 | 0.47 |
December | 66007707.57 | 0.00 | 0.00 | 48697.11 | 0.00 | 0.300129E+09 | 3461821.48 | 0.00 | 0.47 |
Annual Sum or Average | 0.815299E+09 | 34148833.86 | 7361.05 | 16685404.89 | 1063073.16 | 0.186542E+10 | 0.152838E+10 | 991.54 | 0.47 |
Minimum of Months | 26318850.67 | 0.00 | 0.00 | 19405.39 | 0.00 | 538156.89 | 850270.87 | 0.00 | 0.47 |
Maximum of Months | 0.106554E+09 | 19271401.00 | 5191.41 | 2973465.59 | 714654.51 | 0.302209E+09 | 0.252212E+09 | 932.33 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 34897940.62 | 0.00 | 0.00 | 6974.40 | 0.00 | 0.326808E+09 | 151880.60 | 0.00 | 0.47 |
February | 68880497.05 | 0.00 | 0.00 | 67607.77 | 0.00 | 0.271922E+09 | 8786885.19 | 0.00 | 0.47 |
March | 0.116265E+09 | 0.00 | 0.00 | 306097.74 | 0.00 | 0.268871E+09 | 32786704.23 | 0.00 | 0.47 |
April | 0.106522E+09 | 515302.89 | 0.00 | 970536.20 | 10039.63 | 0.183398E+09 | 0.109796E+09 | 0.00 | 0.47 |
May | 83590735.33 | 926530.92 | 1243.43 | 2186882.38 | 56964.54 | 95789637.68 | 0.208689E+09 | 149.21 | 0.47 |
June | 62382827.11 | 404849.87 | 0.00 | 2564939.70 | 41817.93 | 29931419.76 | 0.237514E+09 | 0.00 | 0.47 |
July | 34075829.61 | 9380250.77 | 656.99 | 2660946.23 | 281059.66 | 524799.55 | 0.225356E+09 | 122.86 | 0.47 |
August | 31038444.67 | 18582463.46 | 7348.01 | 1783719.94 | 1398515.34 | 3547441.67 | 0.173668E+09 | 1510.07 | 0.48 |
September | 71764058.39 | 3137782.78 | 2783.74 | 1619823.87 | 449106.13 | 59101915.25 | 0.203217E+09 | 1064.19 | 0.47 |
October | 0.115483E+09 | 0.00 | 0.00 | 446080.54 | 0.00 | 0.241728E+09 | 65566146.42 | 0.00 | 0.47 |
November | 74900994.23 | 15817.29 | 544.90 | 36998.81 | 0.00 | 0.289374E+09 | 6696513.42 | 208.45 | 0.47 |
December | 49644131.35 | 0.00 | 0.00 | 15085.83 | 0.00 | 0.319581E+09 | 364518.14 | 0.00 | 0.47 |
Annual Sum or Average | 0.849446E+09 | 32962997.97 | 12577.07 | 12665693.42 | 2237503.23 | 0.209058E+10 | 0.127259E+10 | 3054.77 | 0.47 |
Minimum of Months | 31038444.67 | 0.00 | 0.00 | 6974.40 | 0.00 | 524799.55 | 151880.60 | 0.00 | 0.47 |
Maximum of Months | 0.116265E+09 | 18582463.46 | 7348.01 | 2660946.23 | 1398515.34 | 0.326808E+09 | 0.237514E+09 | 1510.07 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.521486E+09 | 0.00 | 0.00 | 1982181.56 | 0.00 | 0.158173E+10 | 0.219870E+09 | 0.00 | 0.54 |
February | 0.436706E+09 | 0.00 | 0.00 | 7770712.17 | 0.00 | 0.112708E+10 | 0.675073E+09 | 0.00 | 0.54 |
March | 0.497565E+09 | 0.00 | 0.00 | 12055850.96 | 0.00 | 0.913069E+09 | 0.126453E+10 | 0.00 | 0.54 |
April | 0.435090E+09 | 3291239.25 | 0.00 | 13383779.84 | 84213.63 | 0.449666E+09 | 0.167637E+10 | 0.00 | 0.54 |
May | 0.372454E+09 | 6011284.20 | 0.00 | 15765939.34 | 316860.37 | 0.183805E+09 | 0.193547E+10 | 0.00 | 0.54 |
June | 0.306655E+09 | 2515763.78 | 0.00 | 16513735.72 | 354184.99 | 27994518.80 | 0.178454E+10 | 0.00 | 0.54 |
July | 0.187745E+09 | 59823178.78 | 6613.96 | 15763475.74 | 2250987.35 | 3377278.89 | 0.148050E+10 | 489.60 | 0.54 |
August | 0.163233E+09 | 0.124153E+09 | 25027.26 | 12875652.60 | 4260055.05 | 2998095.83 | 0.117044E+10 | 1874.72 | 0.54 |
September | 0.357536E+09 | 22295190.15 | 0.00 | 17567514.65 | 776163.54 | 60162834.52 | 0.172170E+10 | 0.00 | 0.54 |
October | 0.467579E+09 | 0.00 | 0.00 | 14494482.65 | 0.00 | 0.506560E+09 | 0.173068E+10 | 0.00 | 0.54 |
November | 0.531265E+09 | 106470.32 | 0.00 | 4011828.08 | 0.00 | 0.121127E+10 | 0.637275E+09 | 0.00 | 0.54 |
December | 0.458551E+09 | 0.00 | 0.00 | 5025260.39 | 0.00 | 0.150597E+10 | 0.405249E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.473587E+10 | 0.218196E+09 | 31641.22 | 0.137210E+09 | 8042464.93 | 0.757369E+10 | 0.147017E+11 | 2364.32 | 0.54 |
Minimum of Months | 0.163233E+09 | 0.00 | 0.00 | 1982181.56 | 0.00 | 2998095.83 | 0.219870E+09 | 0.00 | 0.53 |
Maximum of Months | 0.531265E+09 | 0.124153E+09 | 25027.26 | 17567514.65 | 4260055.05 | 0.158173E+10 | 0.193547E+10 | 1874.72 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.552889E+10 | 0.00 | 0.00 | 70727977.39 | 0.00 | 0.00 | 0.379321E+11 | 0.00 | 3.98 |
February | 0.337938E+10 | 0.00 | 0.00 | 65107170.76 | 0.00 | 0.00 | 0.368919E+11 | 0.00 | 4.05 |
March | 0.242363E+10 | 0.00 | 0.00 | 96331457.34 | 0.00 | 0.00 | 0.453570E+11 | 0.00 | 4.16 |
April | 0.877730E+09 | 5309846.66 | 0.00 | 0.105925E+09 | 0.00 | 0.00 | 0.457490E+11 | 0.00 | 4.35 |
May | 0.155560E+09 | 0.00 | 0.00 | 0.114610E+09 | 0.00 | 0.00 | 0.483176E+11 | 0.00 | 4.64 |
June | 8742374.31 | 0.00 | 0.00 | 90304936.24 | 0.00 | 0.00 | 0.429297E+11 | 0.00 | 4.90 |
July | 0.00 | 93587377.34 | 0.00 | 88604750.26 | 0.00 | 0.00 | 0.392427E+11 | 0.00 | 5.08 |
August | 3582311.44 | 0.315464E+09 | 0.00 | 81103561.96 | 0.00 | 0.00 | 0.351977E+11 | 0.00 | 5.05 |
September | 0.103542E+09 | 0.00 | 0.00 | 83893229.08 | 0.00 | 0.00 | 0.434621E+11 | 0.00 | 4.76 |
October | 0.161032E+10 | 0.00 | 0.00 | 99971007.37 | 0.00 | 0.00 | 0.476130E+11 | 0.00 | 4.32 |
November | 0.324288E+10 | 0.00 | 0.00 | 81208677.15 | 0.00 | 0.00 | 0.415983E+11 | 0.00 | 4.10 |
December | 0.507745E+10 | 0.00 | 0.00 | 79969067.76 | 0.00 | 0.00 | 0.390706E+11 | 0.00 | 3.97 |
Annual Sum or Average | 0.224117E+11 | 0.414362E+09 | 0.00 | 0.105776E+10 | 0.00 | 0.00 | 0.503362E+12 | 0.00 | 4.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 65107170.76 | 0.00 | 0.00 | 0.351977E+11 | 0.00 | 3.97 |
Maximum of Months | 0.552889E+10 | 0.315464E+09 | 0.00 | 0.114610E+09 | 0.00 | 0.00 | 0.483176E+11 | 0.00 | 5.08 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.182445E+10 | 0.00 | 0.00 | 96814261.71 | 0.00 | 0.00 | 0.458382E+11 | 0.00 | 4.35 |
February | 0.112874E+10 | 0.00 | 0.00 | 86453009.27 | 0.00 | 0.00 | 0.430267E+11 | 0.00 | 4.43 |
March | 0.783110E+09 | 0.00 | 0.00 | 0.120427E+09 | 0.00 | 0.00 | 0.516783E+11 | 0.00 | 4.56 |
April | 0.170710E+09 | 5916832.47 | 0.00 | 0.126568E+09 | 0.00 | 0.00 | 0.508134E+11 | 0.00 | 4.76 |
May | 42841976.70 | 0.00 | 0.00 | 0.131037E+09 | 0.00 | 0.00 | 0.525515E+11 | 0.00 | 5.04 |
June | 956779.35 | 0.00 | 0.00 | 0.100963E+09 | 0.00 | 0.00 | 0.463374E+11 | 0.00 | 5.29 |
July | 0.00 | 0.100577E+09 | 0.00 | 97453816.20 | 0.00 | 0.00 | 0.420830E+11 | 0.00 | 5.46 |
August | 0.00 | 0.340407E+09 | 0.00 | 89430808.24 | 0.00 | 0.00 | 0.377003E+11 | 0.00 | 5.42 |
September | 4519197.25 | 0.00 | 0.00 | 95130248.55 | 0.00 | 0.00 | 0.471151E+11 | 0.00 | 5.15 |
October | 0.341509E+09 | 0.00 | 0.00 | 0.121837E+09 | 0.00 | 0.00 | 0.534165E+11 | 0.00 | 4.71 |
November | 0.107650E+10 | 0.00 | 0.00 | 0.106189E+09 | 0.00 | 0.00 | 0.482003E+11 | 0.00 | 4.49 |
December | 0.167822E+10 | 0.00 | 0.00 | 0.107663E+09 | 0.00 | 0.00 | 0.467433E+11 | 0.00 | 4.34 |
Annual Sum or Average | 0.705155E+10 | 0.446901E+09 | 0.00 | 0.127997E+10 | 0.00 | 0.00 | 0.565504E+12 | 0.00 | 4.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 86453009.27 | 0.00 | 0.00 | 0.377003E+11 | 0.00 | 4.34 |
Maximum of Months | 0.182445E+10 | 0.340407E+09 | 0.00 | 0.131037E+09 | 0.00 | 0.00 | 0.534165E+11 | 0.00 | 5.46 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 69663291.40 | 0.00 | 0.00 | 0.177519E+09 | 0.00 | 0.00 | 0.631058E+11 | 0.00 | 18.88 |
February | 0.102874E+09 | 0.00 | 0.00 | 0.150162E+09 | 0.00 | 0.00 | 0.584842E+11 | 0.00 | 19.31 |
March | 28344815.75 | 0.00 | 0.00 | 0.192699E+09 | 0.00 | 0.00 | 0.677830E+11 | 0.00 | 19.44 |
April | 0.151321E+09 | 10208208.42 | 0.00 | 0.172596E+09 | 0.00 | 0.00 | 0.639972E+11 | 0.00 | 20.14 |
May | 0.225361E+09 | 0.00 | 0.00 | 0.160574E+09 | 0.00 | 0.00 | 0.636072E+11 | 0.00 | 20.99 |
June | 54638667.27 | 0.00 | 0.00 | 0.131048E+09 | 0.00 | 0.00 | 0.544687E+11 | 0.00 | 21.83 |
July | 0.00 | 0.162854E+09 | 0.00 | 0.127314E+09 | 0.00 | 0.00 | 0.470467E+11 | 0.00 | 22.13 |
August | 0.00 | 0.573190E+09 | 0.00 | 0.116778E+09 | 0.00 | 0.00 | 0.416751E+11 | 0.00 | 22.01 |
September | 21928695.42 | 0.00 | 0.00 | 0.128699E+09 | 0.00 | 0.00 | 0.570882E+11 | 0.00 | 21.63 |
October | 0.181910E+09 | 0.00 | 0.00 | 0.167281E+09 | 0.00 | 0.00 | 0.681701E+11 | 0.00 | 20.13 |
November | 30050477.18 | 0.00 | 0.00 | 0.178241E+09 | 0.00 | 0.00 | 0.636655E+11 | 0.00 | 19.18 |
December | 22913155.91 | 0.00 | 0.00 | 0.198687E+09 | 0.00 | 0.00 | 0.639684E+11 | 0.00 | 18.79 |
Annual Sum or Average | 0.889005E+09 | 0.746253E+09 | 0.00 | 0.190160E+10 | 0.00 | 0.00 | 0.713060E+12 | 0.00 | 20.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.116778E+09 | 0.00 | 0.00 | 0.416751E+11 | 0.00 | 18.79 |
Maximum of Months | 0.225361E+09 | 0.573190E+09 | 0.00 | 0.198687E+09 | 0.00 | 0.00 | 0.681701E+11 | 0.00 | 22.13 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.141629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499882E+09 | 0.00 | 0.00 | 1.08 |
February | 0.131979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255591E+09 | 0.00 | 0.00 | 1.09 |
March | 0.152966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 |
April | 0.143589E+11 | 1806519.61 | 0.00 | 13350.43 | 37235.18 | 0.00 | 10774560.73 | 0.00 | 1.09 |
May | 0.141858E+11 | 0.00 | 0.00 | 153803.90 | 0.00 | 0.00 | 85023619.89 | 0.00 | 1.12 |
June | 0.119685E+11 | 0.00 | 0.00 | 560679.83 | 0.00 | 0.00 | 0.325859E+09 | 0.00 | 1.15 |
July | 0.968306E+10 | 28505354.27 | 0.00 | 2162823.26 | 2704586.94 | 0.00 | 0.115192E+10 | 0.00 | 1.17 |
August | 0.880118E+10 | 0.104686E+09 | 0.00 | 2289828.26 | 8841300.76 | 0.00 | 0.900496E+09 | 0.00 | 1.17 |
September | 0.122584E+11 | 0.00 | 0.00 | 1337871.11 | 0.00 | 0.00 | 0.585207E+09 | 0.00 | 1.15 |
October | 0.154012E+11 | 0.00 | 0.00 | 688.85 | 0.00 | 3244618.76 | 5866964.80 | 0.00 | 1.10 |
November | 0.146325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1899674.52 | 0.00 | 0.00 | 1.08 |
December | 0.146345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191960E+09 | 0.00 | 0.00 | 1.08 |
Annual Sum or Average | 0.158581E+12 | 0.134997E+09 | 0.00 | 6519045.64 | 11583122.88 | 0.952577E+09 | 0.306515E+10 | 0.00 | 1.11 |
Minimum of Months | 0.880118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 |
Maximum of Months | 0.154012E+11 | 0.104686E+09 | 0.00 | 2289828.26 | 8841300.76 | 0.499882E+09 | 0.115192E+10 | 0.00 | 1.17 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:01:04
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.619817E+11 | 0.168566E+11 | 0.221951E+12 | 0.884905E+12 | 0.646852E+11 |
February | 0.133658E+12 | 0.141656E+11 | 0.185500E+12 | 0.752287E+12 | 0.625105E+11 |
March | 0.253043E+12 | 0.136736E+11 | 0.176699E+12 | 0.733521E+12 | 0.787474E+11 |
April | 0.406263E+12 | 0.112791E+11 | 0.142796E+12 | 0.611976E+12 | 0.135231E+12 |
May | 0.532504E+12 | 0.993078E+10 | 0.123091E+12 | 0.549293E+12 | 0.203694E+12 |
June | 0.547979E+12 | 0.764947E+10 | 0.938580E+11 | 0.431512E+12 | 0.278222E+12 |
July | 0.570002E+12 | 0.612995E+10 | 0.744953E+11 | 0.360714E+12 | 0.421175E+12 |
August | 0.449510E+12 | 0.516891E+10 | 0.637408E+11 | 0.310658E+12 | 0.498482E+12 |
September | 0.286194E+12 | 0.780249E+10 | 0.997234E+11 | 0.448078E+12 | 0.251429E+12 |
October | 0.191557E+12 | 0.109457E+11 | 0.143946E+12 | 0.603650E+12 | 0.110428E+12 |
November | 0.720157E+11 | 0.131848E+11 | 0.178722E+12 | 0.707304E+12 | 0.673413E+11 |
December | 0.403005E+11 | 0.160702E+11 | 0.212391E+12 | 0.848794E+12 | 0.679758E+11 |
Annual Sum or Average | 0.354501E+13 | 0.132857E+12 | 0.171691E+13 | 0.724269E+13 | 0.223992E+13 |
Minimum of Months | 0.403005E+11 | 0.516891E+10 | 0.637408E+11 | 0.310658E+12 | 0.625105E+11 |
Maximum of Months | 0.570002E+12 | 0.168566E+11 | 0.221951E+12 | 0.884905E+12 | 0.498482E+12 |