Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:59
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2023-10-16 08:59:53
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10797.40 | 951.71 | 951.71 |
Net Site Energy | 10797.40 | 951.71 | 951.71 |
Total Source Energy | 22452.34 | 1979.00 | 1979.00 |
Net Source Energy | 22452.34 | 1979.00 | 1979.00 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 914.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 878.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 767.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 242.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1745.01 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 651.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 561.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 160.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.75 | 2934.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 62.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5159.85 | 5637.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 914.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 878.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 767.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 242.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 32.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 561.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 160.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 2934.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 914.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 878.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 767.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 242.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1745.01 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 651.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 561.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 160.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.75 | 2934.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 62.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 89.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 149.04 | 339.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 216.73 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 454.80 | 496.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 89.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 149.04 | 339.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 216.73 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 454.80 | 496.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5159.849 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5159.849 | 100.00 |
Total On-Site and Utility Electric Sources | 5159.849 | 100.00 |
Total Electricity End Uses | 5159.849 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 22.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7353.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:59 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 9.1389 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.3365 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.3365 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 9.2031 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 6.1031 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.8125 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.3656 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 8.7188 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.5531 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.5531 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 6.3938 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.5531 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.3656 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.3656 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7219 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 6.3938 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 6.8557 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 6.8557 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.1389 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.3365 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.3365 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 9.2031 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 6.1031 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.8125 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.3656 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 8.7188 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.5531 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.5531 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 6.3938 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.5531 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.5531 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.5531 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.3656 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.3656 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7219 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 6.3938 | 18.58 | 0.0000 | |
Total | 11345.29 | 6.8557 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 6.8557 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.4542 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-SEP-19:10 | 02-JAN-20:00 | - | - | - | - | - | - | - | - | - | - | 02-JAN-21:10 |
Heating | 0.00 | 185003.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 118286.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 88772.42 | 89710.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 32151.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 29864.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 7344.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3873.13 | 242839.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1829.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 360462.95 | 517553.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 185003.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 118286.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58789.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1847.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 29864.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 7344.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3873.13 | 242839.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 530.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1058.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 991.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2781.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2430.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 769.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5526.46 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2063.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1777.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 508.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.40 | 3180.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 197.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 16341.24 | 6111.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 87.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 245.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 214.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 67.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.11 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 156.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 44.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 280.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1440.36 | 538.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 87.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 245.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 214.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 67.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.11 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 156.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 44.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 280.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1440.36 | 538.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.46 | 0.612567 | 0.549000 | 1.35 | 1.00 | 0.500000 | 0.000622 | 0.000061 | 1.35 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.325467 | 0.157031 | 0.549000 | 0.178681 | 0.549000 | 0.500000 | 0.002426 | 0.000025 | 0.178681 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.239258 | 0.247364 | 0.549000 | 0.131353 | 0.659636 | 0.500000 | 0.001540 | 0.000012 | 0.131353 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.226852 | 0.551695 | 0.549000 | 0.124542 | 1.00 | 0.500000 | 0.000691 | 0.000016 | 0.124542 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.107900 | 0.669199 | 0.549000 | 0.059237 | 1.00 | 0.500000 | 0.000569 | 0.000009 | 0.059237 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.31 | 0.071262 | 0.549000 | 1.82 | 0.549000 | 0.500000 | 0.021216 | 0.000096 | 1.82 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.40 | 0.103139 | 0.549000 | 0.766035 | 0.549000 | 0.500000 | 0.003694 | 0.000076 | 0.766035 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.53 | 0.220069 | 0.549000 | 2.49 | 0.586852 | 0.500000 | 0.001731 | 0.000211 | 2.49 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.35 | 0.878542 | 0.549000 | 0.741696 | 1.00 | 0.500000 | 0.000434 | 0.000093 | 0.741696 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.13 | 0.118637 | 0.549000 | 1.17 | 0.549000 | 0.500000 | 0.003211 | 0.000090 | 1.17 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.23 | 0.113102 | 0.549000 | 1.23 | 0.549000 | 0.500000 | 0.003369 | 0.000094 | 1.23 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.23 | 0.063627 | 0.549000 | 1.22 | 0.549000 | 0.500000 | 0.010770 | 0.000060 | 1.22 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.692564 | 0.453444 | 0.549000 | 0.380217 | 1.00 | 0.500000 | 0.000840 | 0.000057 | 0.380217 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 7002.68 | 0.000061 | 146.03 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 2809.35 | 0.000025 | 65.58 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1326.93 | 0.000012 | 29.11 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1826.68 | 0.000016 | 42.13 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1010.38 | 0.000009 | 23.95 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10967.84 | 0.000096 | 230.68 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 8715.34 | 0.000076 | 193.82 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 24162.54 | 0.000211 | 527.94 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 4141.15 | 0.000036 | 118.33 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 4141.31 | 0.000036 | 118.34 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 24034.76 | 0.000210 | 686.77 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 24049.92 | 0.000210 | 687.21 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 4140.33 | 0.000036 | 118.31 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 4140.48 | 0.000036 | 118.31 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 10588.30 | 0.000093 | 243.14 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1278.80 | 0.000011 | 36.54 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1278.34 | 0.000011 | 36.53 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 6171.36 | 0.000054 | 176.34 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 10341.95 | 0.000090 | 223.90 |
DINING_FLR_6 VAV BOX REHEAT COIL | 10722.38 | 0.000094 | 231.88 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6853.18 | 0.000060 | 143.53 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 6495.13 | 0.000057 | 154.04 |
VAV WITH REHEAT HEATING COIL | 97025.27 | 0.000849 | 1739.02 |
FLR_3_DOAS HEATING COIL | 9427.25 | 0.000082 | 168.97 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 0.950535 | 0.000036 | 0.000371 |
ROOM_2_FLR_3 FAN COIL | 0.911701 | 0.000036 | 0.000357 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.55 | 0.000210 | 0.002125 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.17 | 0.000210 | 0.002127 |
ROOM_5_FLR_3 FAN COIL | 0.831655 | 0.000036 | 0.000326 |
ROOM_6_FLR_3 FAN COIL | 0.797561 | 0.000036 | 0.000313 |
ROOM_1_FLR_6 FAN COIL | 0.246072 | 0.000011 | 0.000096 |
ROOM_2_FLR_6 FAN COIL | 0.235326 | 0.000011 | 0.000092 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.14 | 0.000054 | 0.000453 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 0.950535 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 0.911701 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.55 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.17 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.831655 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.797561 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.246072 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.235326 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.14 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008571 | 12.80 | 0.008500 | 0.000371 | 0.950535 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008574 | 12.80 | 0.008500 | 0.000357 | 0.911701 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008495 | 12.80 | 0.008495 | 0.002125 | 5.55 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008766 | 12.80 | 0.008500 | 0.002127 | 5.17 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008581 | 12.80 | 0.008500 | 0.000326 | 0.831655 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008585 | 12.80 | 0.008500 | 0.000313 | 0.797561 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008569 | 12.80 | 0.008500 | 0.000096 | 0.246072 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008572 | 12.80 | 0.008500 | 0.000092 | 0.235326 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008640 | 12.80 | 0.008500 | 0.000453 | 1.14 | |
VAV WITH REHEAT COOLING COIL | 28.03 | 6.70 | 0.008886 | 10.94 | 0.008500 | 0.016418 | 21.11 | 459657.95 |
FLR_3_DOAS COOLING COIL | 31.30 | 6.70 | 0.008233 | 11.91 | 0.008233 | 0.001713 | 2.05 | 47946.25 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.66 | 11.66 | 21.23 | 11.66 | 21.11 | 21.11 | 0.300000 | 0.552086 | 21.11 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 21.11 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 21.11 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.016418 | 0.000029 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.000849 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001713 | 0.000278 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000082 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.024390 | 5025.84 | |
HEATSYS1 PUMP | 0.002473 | 744.69 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.002473 | 0.296731 |
COOLSYS1 | 0.024390 | 2.93 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 282651.66 | 282651.66 | 0.002473 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.024390 | 3479.56 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.024390 | 682850.76 | 683446.96 | 77.91 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 9.139 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.519 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.336 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.096 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.336 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.096 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 9.203 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.583 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 6.103 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.793 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.813 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.343 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.366 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.746 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 8.719 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.789 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.366 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 78.186 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.366 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 78.186 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.722 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2946.209 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 18084.325 | 9.139 | 169.807 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18084.325 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 894.495 | 13.336 | 82.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 894.495 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1035.829 | 13.336 | 82.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1035.829 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 1511.551 | 9.203 | 569.967 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1511.551 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 578.329 | 6.103 | 283.494 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 578.329 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 453.605 | 5.813 | 54.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 453.605 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1957.673 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1957.673 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11405.759 | 8.719 | 27.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11405.759 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 111.660 | 4.553 | 74.440 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.660 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 111.691 | 4.553 | 74.460 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.691 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2489.757 | 6.394 | 118.803 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.757 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 111.691 | 4.553 | 74.460 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.691 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3437.839 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3437.839 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3437.839 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3437.839 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1210.923 | 11.722 | 54.453 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1210.923 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2635.024 | 6.394 | 118.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2635.024 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 1.067 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.370 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.442 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.217 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.286 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7702 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5624 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5260 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6546 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6103 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.55514967E-15 | 0.35055860E-16 | -0.14326465E-09 | 0.28783368E-17 |
29 | 8 | 0.20966873E-07 | 0.14258959E-12 | 0.36819155E-03 | -0.23840058E-09 |
30 | 7 | -0.11954852E-01 | 0.74774803E-08 | -0.22672946E-01 | 0.13593102E-03 |
31 | 6 | 0.39755982 | 0.26159305E-05 | 0.46545104 | -0.46559307E-02 |
32 | 5 | -5.1145337 | 0.98147117E-04 | -4.3902405 | 0.62241115E-01 |
33 | 4 | 32.666535 | 0.80637729E-03 | 21.240866 | -0.41765750 |
34 | 3 | -110.51061 | 0.17642800E-02 | -55.229641 | 1.5048560 |
35 | 2 | 196.42192 | 0.99585215E-03 | 77.513220 | -2.8894543 |
36 | 1 | -170.90254 | 0.10665179E-03 | -55.149704 | 2.7409959 |
37 | 0 | 57.057407 | 0.60929387E-06 | 15.576129 | |
38 | 9 | 0.10314710E-14 | 0.47183642E-16 | -0.12881513E-09 | -0.40099708E-17 |
39 | 8 | 0.18927665E-07 | 0.17950474E-12 | 0.34608657E-03 | -0.21521408E-09 |
40 | 7 | -0.11292911E-01 | 0.96443222E-08 | -0.21719088E-01 | 0.12840450E-03 |
41 | 6 | 0.37957032 | 0.34070209E-05 | 0.45007157 | -0.44438791E-02 |
42 | 5 | -4.9389364 | 0.12890179E-03 | -4.2718596 | 0.60063826E-01 |
43 | 4 | 31.889569 | 0.10670331E-02 | 20.777560 | -0.40734193 |
44 | 3 | -108.85680 | 0.23501275E-02 | -54.313423 | 1.4809641 |
45 | 2 | 194.78196 | 0.13343675E-02 | 76.673975 | -2.8634131 |
46 | 1 | -170.29645 | 0.14368413E-03 | -54.907648 | 2.7303734 |
47 | 0 | 57.057407 | 0.82565881E-06 | 15.617726 | |
48 | 9 | 0.86975537E-15 | 0.52023775E-16 | -0.12536948E-09 | -0.54620444E-17 |
49 | 8 | 0.18440443E-07 | 0.18784465E-12 | 0.34068694E-03 | -0.20967419E-09 |
50 | 7 | -0.11130813E-01 | 0.10155400E-07 | -0.21485363E-01 | 0.12656138E-03 |
51 | 6 | 0.37516444 | 0.35965268E-05 | 0.44629465 | -0.43919449E-02 |
52 | 5 | -4.8959230 | 0.13636263E-03 | -4.2427425 | 0.59530495E-01 |
53 | 4 | 31.699203 | 0.11309484E-02 | 20.663505 | -0.40481456 |
54 | 3 | -108.45147 | 0.24950915E-02 | -54.087828 | 1.4751087 |
55 | 2 | 194.37988 | 0.14187814E-02 | 76.467519 | -2.8570287 |
56 | 1 | -170.14779 | 0.15298304E-03 | -54.848449 | 2.7277680 |
57 | 0 | 57.057407 | 0.88039223E-06 | 15.628184 | |
58 | 9 | 0.12430042E-14 | 0.43603463E-16 | -0.13615479E-09 | -0.52742981E-17 |
59 | 8 | 0.19963588E-07 | 0.16114398E-12 | 0.35741204E-03 | -0.22699287E-09 |
60 | 7 | -0.11632381E-01 | 0.85488282E-08 | -0.22208377E-01 | 0.13226440E-03 |
61 | 6 | 0.38879653 | 0.30047059E-05 | 0.45796739 | -0.45526330E-02 |
62 | 5 | -5.0290001 | 0.11318598E-03 | -4.3326723 | 0.61180550E-01 |
63 | 4 | 32.288109 | 0.93328928E-03 | 21.015642 | -0.41263319 |
64 | 3 | -109.70522 | 0.20484795E-02 | -54.784283 | 1.4932205 |
65 | 2 | 195.62339 | 0.11595496E-02 | 77.105128 | -2.8767741 |
66 | 1 | -170.60747 | 0.12450863E-03 | -55.031726 | 2.7358244 |
67 | 0 | 57.057407 | 0.71328115E-06 | 15.596176 | |
68 | 9 | 0.10418955E-14 | 0.45554749E-16 | -0.13285794E-09 | -0.34221686E-17 |
69 | 8 | 0.19498290E-07 | 0.16949498E-12 | 0.35235048E-03 | -0.22170227E-09 |
70 | 7 | -0.11480752E-01 | 0.90423087E-08 | -0.21989859E-01 | 0.13054032E-03 |
71 | 6 | 0.38467563 | 0.31853038E-05 | 0.45444290 | -0.45040579E-02 |
72 | 5 | -4.9887746 | 0.12022067E-03 | -4.3055366 | 0.60681782E-01 |
73 | 4 | 32.110117 | 0.99300969E-03 | 20.909427 | -0.41027004 |
74 | 3 | -109.32633 | 0.21828955E-02 | -54.574228 | 1.4877470 |
75 | 2 | 195.24766 | 0.12373115E-02 | 76.912747 | -2.8708078 |
76 | 1 | -170.46860 | 0.13302463E-03 | -54.976289 | 2.7333905 |
77 | 0 | 57.057407 | 0.76310210E-06 | 15.605744 | |
78 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
79 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
80 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
81 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
82 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
83 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
84 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
85 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
86 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
87 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
88 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
89 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
90 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
91 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
92 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
93 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4711_SHGC_0.25 | 37 | 1 | VerySmooth | 2.678 | 2.678 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.4711_SHGC_0.25 | 38 | 1 | VerySmooth | 2.678 | 2.678 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.39142E-002 | 0.16139 | 0.61472 | 0.61472 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11798 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.39142E-002 | 0.16139 | 0.61472 | 0.61472 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11798 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 8.7013E-002 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.9098E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.6674E-002 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.2679E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 6.5685E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.4415E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.6511E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.7811E-003 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 9.8305E-002 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.7836E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1095 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.2162E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.2719E-002 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.0822E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 2.9789E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.2036E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.1172E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.2102E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.6312E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.1416E-003 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.5604E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.2330E-003 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.6108E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.2309E-003 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.1172E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.2102E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.6312E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.1416E-003 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.5604E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.2330E-003 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.6108E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.2309E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 33249.06263 | 33249.06263 | 2.46156 | 2.46156 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:30:00 | 27.33950 | 8.22721E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | 00:10:00 | 3.80000 | 5.05843E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 4395.80487 | 4395.80487 | 0.32547 | 0.32547 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.92917 | 8.23290E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 1884.07006 | 1884.07006 | 8.22847E-002 | 8.22847E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3231.38937 | 3231.38937 | 0.23926 | 0.23926 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 30.05400 | 8.23151E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 646.75392 | 646.75392 | 2.82467E-002 | 9.17347E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3064.49973 | 3064.49973 | 0.22685 | 0.22685 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 29.16400 | 8.23009E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1181.87653 | 1181.87653 | 5.16179E-002 | 5.16179E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1457.58689 | 1457.58689 | 0.10790 | 0.10790 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 31.03300 | 8.23307E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 703.67493 | 703.67493 | 3.07327E-002 | 5.77652E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44727.99419 | 44727.99419 | 3.31133 | 3.31133 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 31.30000 | 8.23349E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1556.31490 | 1556.31490 | 6.79703E-002 | 6.79703E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 18829.82543 | 18829.82543 | 1.39533 | 1.39533 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.92917 | 8.23290E-003 | 188.86188 | 142.30000 | 0.67638 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 4748.18961 | 4748.18961 | 0.20737 | 0.67638 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 188.86188 | 142.30000 | 0.67638 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 61159.89549 | 61159.89549 | 4.52965 | 4.52965 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.07750 | 8.23314E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 11284.83873 | 11284.83873 | 0.49286 | 1.89399 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 9528.23709 | 9528.23709 | 0.95054 | 0.95054 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 30.52867 | 8.23226E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 4141.20192 | 4141.20192 | 0.18192 | 0.18192 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 9138.95646 | 9138.95646 | 0.91170 | 0.91170 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 4141.35643 | 4141.35643 | 0.18193 | 0.18193 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 55588.18086 | 55588.18086 | 5.54523 | 5.54523 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.07750 | 8.23314E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 24034.90505 | 24034.90505 | 1.05588 | 1.05588 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 51784.34227 | 51784.34227 | 5.16618 | 5.16618 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 31.30000 | 8.23349E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 24050.06627 | 24050.06627 | 1.05654 | 1.05654 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 8336.56893 | 8336.56893 | 0.83165 | 0.83165 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 27.16150 | 8.22694E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 4140.37938 | 4140.37938 | 0.18189 | 0.18189 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 7994.80962 | 7994.80962 | 0.79756 | 0.79756 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 26.65717 | 8.22614E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 4140.53389 | 4140.53389 | 0.18190 | 0.18190 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 18248.79246 | 18248.79246 | 1.35099 | 1.35099 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30000 | 8.23349E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 6746.85422 | 6746.85422 | 0.29467 | 0.47476 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2466.64007 | 2466.64007 | 0.24607 | 0.24607 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 30.52867 | 8.23226E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1278.81174 | 1278.81174 | 5.61787E-002 | 5.61787E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2358.92700 | 2358.92700 | 0.23533 | 0.23533 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1278.35738 | 1278.35738 | 5.61587E-002 | 5.61587E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 11401.65860 | 11401.65860 | 1.13746 | 1.13746 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.07750 | 8.23314E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 6171.41618 | 6171.41618 | 0.27111 | 0.27111 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 28738.68261 | 28738.68261 | 2.13023 | 2.13023 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30000 | 8.23349E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 4284.35023 | 4284.35023 | 0.18712 | 1.18780 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30145.60093 | 30145.60093 | 2.23448 | 2.23448 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30000 | 8.23349E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 4368.38133 | 4368.38133 | 0.19079 | 1.18780 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 3.80000 | 5.05843E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29978.97688 | 29978.97688 | 2.22523 | 2.22523 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 30.49900 | 8.23222E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 562.44009 | 562.44009 | 2.45622E-002 | 0.36735 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 3.80000 | 5.05843E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 9355.00460 | 9355.00460 | 0.69256 | 0.69256 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 31.30000 | 8.23349E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 4525.60994 | 4525.60994 | 0.19765 | 0.19765 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 3.80000 | 5.05843E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 381714.54 | 21.11217 | 21.11217 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 110165.83 | 7.19144 | 7.19144 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 45064.07 | 15.11240 | 2.05125 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 31423.05 | 3.22351 | 2.05125 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.46156 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.61257 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.35140 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.21973E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.12625E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.35140 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7002.68251 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.12625E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 146.02887 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.32547 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15703 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17868 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54900 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.42627E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.45775E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17868 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2809.35365 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.45775E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 65.58172 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23926 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24736 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13135 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65964 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.54024E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.16086E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13135 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1326.93407 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.16086E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 29.11200 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22685 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.55170 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12454 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.90599E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.59806E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12454 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1826.68157 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.59806E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 42.13136 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.10790 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.66920 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.92371E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.69338E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.83922E-006 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.92371E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1010.37681 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.83922E-006 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 23.95464 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.31133 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.12625E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.81792 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54900 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.12158E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.59514E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.81792 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10967.83701 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.59514E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 230.68082 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.39533 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10314 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76603 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54900 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.69404E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.62456E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.76603 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8715.33939 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.62456E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 193.82311 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.52965 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22007 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.48678 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58685 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.73127E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.11384E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.48678 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24162.54279 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.11384E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 527.94094 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.95054 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.95054 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.62286E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.71493E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69394 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57148E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.71493E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.95054 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4141.15101 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.62286E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 118.33178 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.91170 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.91170 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.62299E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.56602E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69394 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57440E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.56602E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.91170 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4141.30551 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.62299E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 118.33619 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.54523 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.54523 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.10267E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.12479E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69438 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49458E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49458E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.12479E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.54523 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 24034.76091 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.10267E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 686.77459 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.16618 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.16618 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.10399E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.12676E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69344 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.76599E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.12676E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.16618 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 24049.92204 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.10399E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 687.20777 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.83165 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.83165 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.62214E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.25904E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69393 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58126E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.25904E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.83165 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4140.32848 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.62214E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 118.30828 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.79756 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.79756 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.62228E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.12832E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69392 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58462E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.12832E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.79756 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4140.48298 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.62228E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 118.31269 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.35099 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.87854 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.74170 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.33673E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.26311E-005 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.74170 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10588.30396 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.26311E-005 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 243.13548 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.24607 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.24607 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.11875E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.61089E-005 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69395 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56912E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.61089E-005 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.24607 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1278.79645 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.11875E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 36.53985 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.23533 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.23533 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.11835E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.19887E-005 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69394 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57216E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.19887E-005 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.23533 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1278.34210 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.11835E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 36.52686 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.13746 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.13746 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.39897E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.52930E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69365 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64030E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.52930E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.13746 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6171.35682 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.39897E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 176.33691 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.13023 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11864 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.16949 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54900 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.21148E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.04759E-005 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.16949 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10341.95293 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.04759E-005 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 223.89711 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.23448 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11310 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.22673 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54900 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.36865E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.38040E-005 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.22673 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10722.37911 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.38040E-005 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 231.88419 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.22523 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.36268E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.22165 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54900 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07703E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.99546E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.22165 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6853.18138 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.99546E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 143.52567 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69256 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.45344 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38022 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.40236E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.68222E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38022 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6495.12887 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.68222E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 154.03790 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.65573 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65573 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.23084 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65573 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.11217 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 21.11217 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.55209 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 21.11217 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.11217 |
338 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.02796 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.94366 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.88632E-003 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 459657.94592 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.64179E-002 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 21.11217 |
346 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 97025.27081 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.48819E-004 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1739.01847 |
349 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 21.11217 |
350 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.64179E-002 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.90043E-005 |
352 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.48819E-004 |
353 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
355 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 31.30000 |
356 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.91243 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.23349E-003 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.23349E-003 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 47946.24805 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.71253E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
363 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 9427.24706 |
364 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.24737E-005 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 168.96790 |
366 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
367 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.71253E-003 |
368 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.78063E-004 |
369 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.24737E-005 |
370 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.43898E-002 |
371 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 5025.84349 |
372 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.47276E-003 |
373 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.29673 |
374 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.47276E-003 |
375 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 744.68672 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
377 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 282651.65822 |
378 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 282651.66000 |
379 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.47276E-003 |
380 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.43898E-002 |
381 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.92678 |
382 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.43898E-002 |
383 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3479.56096 |
384 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.43898E-002 |
385 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 682850.76018 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 683446.96000 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 77.91295 |
388 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
389 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
390 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
391 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
392 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 7038.90 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 2822.23 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1333.49 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 1835.15 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1014.94 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11024.12 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 8757.22 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 24282.41 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 4460.31 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 4460.47 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 25886.94 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 25903.27 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 4459.42 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 4459.59 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 10637.59 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1377.32 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1376.83 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 6646.82 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 10393.66 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 10776.04 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6888.49 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 6524.47 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 81423.36 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 7911.32 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 15730.56 | 12659.45 | 3071.12 | 0.80 | 1816.63 | 18.43 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 15095.79 | 12146.06 | 2949.72 | 0.80 | 1743.17 | 17.68 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 90618.53 | 73305.78 | 17312.75 | 0.81 | 10497.08 | 106.47 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 88419.50 | 70215.28 | 18204.22 | 0.79 | 10156.28 | 103.01 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 13787.30 | 11087.83 | 2699.47 | 0.80 | 1591.74 | 16.14 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 13230.05 | 10637.13 | 2592.91 | 0.80 | 1527.25 | 15.49 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4070.56 | 3276.40 | 794.15 | 0.80 | 470.12 | 4.77 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 3894.93 | 3134.36 | 760.57 | 0.80 | 449.79 | 4.56 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 19054.42 | 15260.31 | 3794.11 | 0.80 | 2196.02 | 22.27 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 526583.54 | 365115.68 | 161467.85 | 0.69 | 62561.83 | 634.54 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 51527.24 | 35531.42 | 15995.82 | 0.69 | 5813.13 | 58.96 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.370 | 1.137 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.370 | 1.137 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.370 | 1.137 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.370 | 1.137 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.9330096377E-002 | 2.3999274279E-002 | Pass | Pass | 5.6420342345E-003 | 1.7225031033E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.7037736591E-002 | 4.2608514548E-002 | Pass | Pass | 5.0736795029E-002 | 6.2109563814E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.9243092201E-002 | 3.0898379369E-002 | Pass | Pass | 7.8344425634E-003 | 2.0689982595E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.2620056967E-002 | 1.6055975051E-002 | Pass | Pass | 1.0253781398E-002 | 2.8396126962E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.5058277555E-003 | 7.0100878455E-003 | Pass | Pass | 1.5606816831E-002 | 2.5277417543E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.1791577161E-002 | 0.2273228279 | Pass | Pass | 1.9318097533E-002 | 4.9301029782E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.4939206729E-002 | 7.9038065784E-002 | Pass | Pass | 1.3892685237E-002 | 2.5454676411E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.1352291482E-002 | 4.4872286514E-002 | Pass | Pass | 8.3685954528E-003 | 1.9337937788E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.0897671313E-002 | 8.4360594238E-002 | Pass | Pass | 0.2356684303 | 1.2986967943 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.4693241318E-002 | 0.1425003749 | Pass | Pass | 0.1125958531 | 0.2858003915 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.5508076606E-002 | 5.6694836536E-002 | Pass | Pass | 9.7618932452E-003 | 1.0088286694E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.3541056371E-002 | 5.5911831861E-002 | Pass | Pass | 0.1304364220 | 0.3828743630 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.3445083626E-002 | 0.1611854435 | Pass | Pass | 0.7430953737 | 6.1633148562 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.0533839968E-002 | 0.1380539500 | Pass | Pass | 0.2435923034 | 0.7794268697 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.0662895423E-002 | 1.1346697438E-002 | Pass | Pass | 1.2857545873E-002 | 2.4584687824E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.4494669654E-002 | 0.1321541353 | Pass | Pass | 2.6209547608 | 27.4466324297 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.2384980425E-002 | 0.2065337032 | Pass | Pass | 0.2320364715 | 0.9150408177 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.2331157257E-002 | 0.1579011661 | Pass | Pass | 0.1756647377 | 0.4013961946 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.6003431501E-002 | 7.1181055514E-002 | Pass | Pass | 1.2202916974E-002 | 3.5753075197E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.5691172703E-002 | 5.8915262557E-002 | Pass | Pass | 1.3392390645E-002 | 3.7652741314E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.4219974133E-002 | 7.3986255943E-002 | Pass | Pass | 2.1121439556E-002 | 4.0971496408E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.1455868118E-002 | 1.5257389060E-002 | Pass | Pass | 1.6754472378E-002 | 2.4768742863E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3561.99 | 78.30 | 973.24 | 4503.31 | 4288.33 | 13405.17 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.678 | 0.251 | 0.251 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.678 | 0.251 | 0.251 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.678 | 0.251 | 0.251 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.678 | 0.251 | 0.251 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.678 | 0.251 | 0.251 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.678 | 0.251 | 0.251 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.678 | 0.251 | 0.251 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.678 | 0.251 | 0.251 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.678 | 0.251 | 0.251 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.678 | 0.251 | 0.251 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.678 | 0.251 | 0.251 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.678 | 0.251 | 0.251 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.678 | 0.251 | 0.251 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.678 | 0.251 | 0.251 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.678 | 0.251 | 0.251 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.678 | 0.251 | 0.251 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.678 | 0.251 | 0.251 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.678 | 0.251 | 0.251 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.678 | 0.251 | 0.251 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.678 | 0.251 | 0.251 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.678 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.678 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.678 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.678 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 432.95 | 2.678 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.678 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.1389 | 1978.83 | 18084.33 | LightsWired | LTG_SCH_BASEMENT | 51.16 | 168.00 | 51.10 | 0.0000 | Y | 173.46 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.3365 | 67.07 | 894.50 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.61 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.3365 | 77.67 | 1035.83 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 9.97 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 9.2031 | 164.24 | 1511.55 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 16.63 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 6.1031 | 94.76 | 578.33 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 2.78 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.8125 | 78.04 | 453.60 | LightsWired | LTG_SCH_LAUNDRY | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 4.37 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.3656 | 188.86 | 1957.67 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.25 | 0.0000 | Y | 18.10 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 8.7188 | 1308.19 | 11405.76 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 57.00 | 0.0000 | Y | 122.03 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.5531 | 156.09 | 710.69 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.5531 | 156.07 | 710.61 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.5531 | 1863.81 | 8486.17 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 76.02 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.5531 | 1864.32 | 8488.49 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 76.04 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.5531 | 156.09 | 710.69 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.5531 | 156.07 | 710.61 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 6.3938 | 1557.62 | 9959.03 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 109.60 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.5531 | 39.02 | 177.67 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.59 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.5531 | 39.02 | 177.65 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.59 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.5531 | 220.77 | 1005.22 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 9.00 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.3656 | 331.66 | 3437.84 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 53.98 | 0.0000 | Y | 34.83 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.3656 | 331.66 | 3437.84 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 53.98 | 0.0000 | Y | 34.83 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7219 | 103.30 | 1210.92 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.33 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 6.3938 | 412.12 | 2635.02 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 29.00 |
Interior Lighting Total | 6.8557 | 11345.29 | 77780.02 | 507.91 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 11405.76 | 798.40 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 11405.76 | 0.00 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1957.67 | 763.49 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 1957.67 | 0.00 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3437.84 | 687.57 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3437.84 | 0.00 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3437.84 | 687.57 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3437.84 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 15448.40 | AstronomicalClock | - | 83.75 | 83.75 | 242.88 | |
Exterior Lighting Total | 15448.40 | 242.88 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 282651.66 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 683446.96 | 2.96 | 683567.09 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10401.02 | 15730.56 | 12659.45 | 3071.12 | 0.80 | - | 1816.63 | 18.43 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9984.08 | 15095.79 | 12146.06 | 2949.72 | 0.80 | - | 1743.17 | 17.68 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 59489.45 | 90618.53 | 73305.78 | 17312.75 | 0.81 | - | 10497.08 | 106.47 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 59544.64 | 88419.50 | 70215.28 | 18204.22 | 0.79 | - | 10156.28 | 103.01 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9124.62 | 13787.30 | 11087.83 | 2699.47 | 0.80 | - | 1591.74 | 16.14 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 8758.62 | 13230.05 | 10637.13 | 2592.91 | 0.80 | - | 1527.25 | 15.49 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2690.84 | 4070.56 | 3276.40 | 794.15 | 0.80 | - | 470.12 | 4.77 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2575.49 | 3894.93 | 3134.36 | 760.57 | 0.80 | - | 449.79 | 4.56 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 12681.08 | 19054.42 | 15260.31 | 3794.11 | 0.80 | - | 2196.02 | 22.27 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 459657.95 | 526583.54 | 365115.68 | 161467.85 | 0.69 | - | 62561.83 | 634.54 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 47946.25 | 51527.24 | 35531.42 | 15995.82 | 0.69 | - | 5813.13 | 58.96 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 7002.68 | 7038.90 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2809.35 | 2822.23 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1326.93 | 1333.49 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1826.68 | 1835.15 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1010.38 | 1014.94 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10967.84 | 11024.12 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 8715.34 | 8757.22 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 24162.54 | 24282.41 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4141.15 | 4460.31 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4141.31 | 4460.47 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 24034.76 | 25886.94 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 24049.92 | 25903.27 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4140.33 | 4459.42 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4140.48 | 4459.59 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 10588.30 | 10637.59 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1278.80 | 1377.32 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1278.34 | 1376.83 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 6171.36 | 6646.82 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10341.95 | 10393.66 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10722.38 | 10776.04 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 6853.18 | 6888.49 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 6495.13 | 6524.47 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 97025.27 | 81423.36 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 9427.25 | 7911.32 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.95 | 668.83 | 703.64 | 1.00 | 1.21 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.91 | 641.51 | 703.64 | 1.00 | 1.22 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.55 | 3901.82 | 703.64 | 1.00 | 0.96 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.17 | 3635.11 | 703.64 | 1.00 | 0.97 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.83 | 585.18 | 703.64 | 1.00 | 1.25 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.80 | 561.19 | 703.64 | 1.00 | 1.26 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.25 | 173.14 | 703.64 | 1.00 | 1.86 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.24 | 165.58 | 703.64 | 1.00 | 1.90 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.14 | 800.36 | 703.64 | 1.00 | 1.17 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 21.11 | 47304.74 | 2240.64 | 1.00 | 1.11 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.024390 | 5025.84 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002473 | 744.69 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.024390 | 3479.56 | 142664.32 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 33249.06 | 33249.06 | 16.80 | 2.462 | 2.462 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:30:00 | 24.00 | 24.00 | 0.00923 | 27.34 | 0.00823 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4395.80 | 4395.80 | 65.54 | 0.325 | 0.325 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00903 | 30.93 | 0.00823 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3231.39 | 3231.39 | 41.60 | 0.239 | 0.239 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00936 | 30.05 | 0.00823 | 0.092 | 0.00 |
MECH_FLR_1 | 3064.50 | 3064.50 | 18.66 | 0.227 | 0.227 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.00 | 24.00 | 0.00868 | 29.16 | 0.00823 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1457.59 | 1457.59 | 15.38 | 0.108 | 0.108 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 24.00 | 24.00 | 0.00879 | 31.03 | 0.00823 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44727.99 | 44727.99 | 573.15 | 3.311 | 3.311 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00854 | 31.30 | 0.00823 | 0.000 | 0.00 |
CAFE_FLR_1 | 18829.83 | 18829.83 | 99.70 | 1.395 | 1.395 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 23.99 | 0.01018 | 30.93 | 0.00823 | 0.676 | 0.00 |
LOBBY_FLR_1 | 61159.90 | 61159.90 | 46.75 | 4.530 | 4.530 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 23.99 | 0.01004 | 31.08 | 0.00823 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 9528.24 | 9528.24 | 244.18 | 0.951 | 0.951 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 21.11 | 21.11 | 0.00857 | 30.53 | 0.00823 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9138.96 | 9138.96 | 234.23 | 0.912 | 0.912 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00857 | 30.41 | 0.00823 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 55588.18 | 55588.18 | 2266.70 | 5.545 | 5.545 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 21.11 | 21.11 | 0.00849 | 31.08 | 0.00823 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 51784.34 | 51784.34 | 2111.01 | 5.166 | 5.166 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 21.11 | 21.11 | 0.00877 | 31.30 | 0.00823 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8336.57 | 8336.57 | 213.64 | 0.832 | 0.832 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 21.11 | 21.11 | 0.00858 | 27.16 | 0.00823 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 7994.81 | 7994.81 | 204.90 | 0.798 | 0.798 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 21.11 | 21.11 | 0.00858 | 26.66 | 0.00823 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 18248.79 | 18248.79 | 46.86 | 1.351 | 1.351 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00952 | 31.30 | 0.00823 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2466.64 | 2466.64 | 63.21 | 0.246 | 0.246 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 21.11 | 21.11 | 0.00857 | 30.53 | 0.00823 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2358.93 | 2358.93 | 60.46 | 0.235 | 0.235 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00857 | 30.41 | 0.00823 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11401.66 | 11401.66 | 464.79 | 1.137 | 1.137 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 21.11 | 21.11 | 0.00864 | 31.08 | 0.00823 | 0.099 | 0.00 |
BANQUET_FLR_6 | 28738.68 | 28738.68 | 86.65 | 2.130 | 2.130 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 23.98 | 0.01045 | 31.30 | 0.00823 | 1.188 | 0.00 |
DINING_FLR_6 | 30145.60 | 30145.60 | 90.89 | 2.234 | 2.234 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 23.99 | 0.01036 | 31.30 | 0.00823 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 29978.98 | 29978.98 | 290.20 | 2.225 | 2.225 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 24.00 | 23.97 | 0.01011 | 30.50 | 0.00823 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9355.00 | 9355.00 | 22.70 | 0.693 | 0.693 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00903 | 31.30 | 0.00823 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | 00:10:00 | 21.00 | 22.01 | 0.00506 | 3.80 | 0.00506 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 1884.07 | 1884.07 | 28.09 | 0.082 | 0.082 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00767 | 3.80 | 0.00506 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 646.75 | 646.75 | 8.33 | 0.028 | 0.092 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00764 | 3.80 | 0.00506 | 0.092 | 0.00 |
MECH_FLR_1 | 1181.88 | 1181.88 | 7.20 | 0.052 | 0.052 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00755 | 3.80 | 0.00506 | 0.000 | 0.00 |
STORAGE_FLR_1 | 703.67 | 703.67 | 7.43 | 0.031 | 0.058 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00756 | 3.80 | 0.00506 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1556.31 | 1556.31 | 19.94 | 0.068 | 0.068 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00753 | 3.80 | 0.00506 | 0.000 | 0.00 |
CAFE_FLR_1 | 4748.19 | 4748.19 | 25.14 | 0.207 | 0.676 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00771 | 3.80 | 0.00506 | 0.676 | 0.00 |
LOBBY_FLR_1 | 11284.84 | 11284.84 | 8.63 | 0.493 | 1.894 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00766 | 3.80 | 0.00506 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 4141.20 | 4141.20 | 106.12 | 0.182 | 0.182 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00766 | 3.80 | 0.00506 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 4141.36 | 4141.36 | 106.14 | 0.182 | 0.182 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00766 | 3.80 | 0.00506 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 24034.91 | 24034.91 | 980.06 | 1.056 | 1.056 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00768 | 3.80 | 0.00506 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24050.07 | 24050.07 | 980.41 | 1.057 | 1.057 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00768 | 3.80 | 0.00506 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 4140.38 | 4140.38 | 106.10 | 0.182 | 0.182 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00766 | 3.80 | 0.00506 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 4140.53 | 4140.53 | 106.12 | 0.182 | 0.182 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00766 | 3.80 | 0.00506 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 6746.85 | 6746.85 | 17.33 | 0.295 | 0.475 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00774 | 3.80 | 0.00506 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1278.81 | 1278.81 | 32.77 | 0.056 | 0.056 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00772 | 3.80 | 0.00506 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1278.36 | 1278.36 | 32.76 | 0.056 | 0.056 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00772 | 3.80 | 0.00506 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 6171.42 | 6171.42 | 251.58 | 0.271 | 0.271 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00773 | 3.80 | 0.00506 | 0.099 | 0.00 |
BANQUET_FLR_6 | 4284.35 | 4284.35 | 12.92 | 0.187 | 1.188 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00779 | 3.80 | 0.00506 | 1.188 | 0.00 |
DINING_FLR_6 | 4368.38 | 4368.38 | 13.17 | 0.191 | 1.188 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 21.00 | 21.00 | 0.00779 | 3.80 | 0.00506 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 562.44 | 562.44 | 5.44 | 0.025 | 0.367 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00491 | 3.80 | 0.00506 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 4525.61 | 4525.61 | 10.98 | 0.198 | 0.198 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 21.00 | 21.00 | 0.00782 | 3.80 | 0.00506 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 21.11 | 21.11 | 7.19 | 7.19 | 21.1122 | 11.6557 | 21.1122 | 0.5521 | 0.3000 |
FLR_3_DOAS | 15.11 | 2.05 | 3.22 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 7002.683 | 7002.683 | 1.351396 | 0.00006126 | 146.029 | 12/21 00:10:00 | 12/21 00:10:00 | 7002.68 | 7002.68 | 1.351396 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 7042.04 | 7042.04 | ||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 2809.354 | 2809.354 | 0.178681 | 0.00002458 | 65.582 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2809.35 | 2809.35 | 0.178681 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00767295 | 48.7070 | 1884.07 | 0.00 | 2824.35 | 2824.35 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1326.934 | 1326.934 | 0.131353 | 0.00001161 | 29.112 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1326.93 | 1326.93 | 0.131353 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00763711 | 48.4817 | 646.75 | 0.00 | 1334.27 | 1334.27 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1826.682 | 1826.682 | 0.124542 | 0.00001598 | 42.131 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1826.68 | 1826.68 | 0.124542 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00754698 | 47.9164 | 1181.88 | 0.00 | 1836.47 | 1836.47 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1010.377 | 1010.377 | 0.059237 | 0.00000884 | 23.955 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1010.38 | 1010.38 | 0.059237 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00755893 | 47.9913 | 703.67 | 0.00 | 1015.75 | 1015.75 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10967.837 | 10967.837 | 1.817922 | 0.00009595 | 230.681 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10967.84 | 10967.84 | 1.817922 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00753315 | 47.8301 | 1556.31 | 0.00 | 11029.29 | 11029.29 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 8715.339 | 8715.339 | 0.766035 | 0.00007625 | 193.823 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 8715.34 | 8715.34 | 0.766035 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00770916 | 48.9338 | 4748.19 | 0.00 | 8762.67 | 8762.67 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 24162.543 | 24162.543 | 2.486780 | 0.00021138 | 527.941 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 24162.54 | 24162.54 | 2.486780 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00765707 | 48.6068 | 11284.84 | 0.00 | 24296.34 | 24296.34 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 10401.022 | -999.000 | 0.950535 | 0.00037149 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | 8/21 16:20:00 | 10401.02 | 10225.69 | 0.950535 | 21.69 | 15.43 | 0.00857148 | 12.80 | 11.93 | 0.00850000 | 30.53 | 0.00823226 | 18.20 | 0.0000 | 21.11 | 0.00857148 | 53.9641 | 9528.24 | 0.00 | 10588.55 | 10225.00 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 4141.151 | 4141.151 | 0.181924 | 0.00003623 | 118.332 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4141.15 | 4141.15 | 0.181924 | 21.11 | 14.40 | 0.00765847 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00765847 | 48.2859 | 4141.20 | 0.00 | 4464.29 | 4464.29 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 9984.080 | -999.000 | 0.911701 | 0.00035660 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 9984.08 | 9809.01 | 0.911701 | 21.69 | 15.44 | 0.00857440 | 12.80 | 11.93 | 0.00850000 | 30.41 | 0.00823207 | 18.16 | 0.0000 | 21.11 | 0.00857440 | 53.9822 | 9138.96 | 0.00 | 10164.02 | 9808.47 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 4141.306 | 4141.306 | 0.181931 | 0.00003623 | 118.336 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4141.31 | 4141.31 | 0.181931 | 21.11 | 14.40 | 0.00765851 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00765851 | 48.2861 | 4141.36 | 0.00 | 4464.45 | 4464.45 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 59489.454 | -999.000 | 5.545226 | 0.00212479 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | 8/21 13:30:00 | 59489.45 | 59489.45 | 5.545226 | 21.69 | 15.37 | 0.00849458 | 12.80 | 11.93 | 0.00849458 | 31.08 | 0.00823314 | 18.38 | 0.0000 | 21.11 | 0.00849458 | 53.4853 | 55588.18 | 0.00 | 60562.58 | 59508.29 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 24034.761 | 24034.761 | 1.055878 | 0.00021027 | 686.775 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 24034.76 | 24034.76 | 1.055878 | 21.11 | 14.42 | 0.00768487 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00768487 | 48.4498 | 24034.91 | 0.00 | 25910.27 | 25910.27 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 59544.639 | -999.000 | 5.166180 | 0.00212676 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | unknown | 8/21 15:00:00 | 59544.64 | 55972.76 | 5.166180 | 21.69 | 15.60 | 0.00876599 | 12.80 | 11.93 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 0.0000 | 21.11 | 0.00876599 | 55.1727 | 51784.34 | 0.00 | 60590.69 | 56012.06 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 24049.922 | 24049.922 | 1.056544 | 0.00021040 | 687.208 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 24049.92 | 24049.92 | 1.056544 | 21.11 | 14.42 | 0.00768497 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00768497 | 48.4504 | 24050.07 | 0.00 | 25926.62 | 25926.62 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9124.617 | -999.000 | 0.831655 | 0.00032590 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | unknown | 8/21 09:30:00 | 9124.62 | 8950.15 | 0.831655 | 21.69 | 15.44 | 0.00858126 | 12.80 | 11.93 | 0.00850000 | 27.16 | 0.00822694 | 17.07 | 0.0000 | 21.11 | 0.00858126 | 54.0249 | 8336.57 | 0.00 | 9288.91 | 8949.90 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 4140.328 | 4140.328 | 0.181888 | 0.00003622 | 118.308 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4140.33 | 4140.33 | 0.181888 | 21.11 | 14.40 | 0.00765841 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00765841 | 48.2855 | 4140.38 | 0.00 | 4463.40 | 4463.40 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 8758.617 | -999.000 | 0.797561 | 0.00031283 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | unknown | 8/21 09:10:00 | 8758.62 | 8584.34 | 0.797561 | 21.69 | 15.44 | 0.00858462 | 12.80 | 11.93 | 0.00850000 | 26.66 | 0.00822614 | 16.89 | 0.0000 | 21.11 | 0.00858462 | 54.0458 | 7994.81 | 0.00 | 8916.25 | 8584.22 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 4140.483 | 4140.483 | 0.181895 | 0.00003622 | 118.313 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4140.48 | 4140.48 | 0.181895 | 21.11 | 14.40 | 0.00765845 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00765845 | 48.2857 | 4140.53 | 0.00 | 4463.57 | 4463.57 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 10588.304 | 10588.304 | 0.741696 | 0.00009263 | 243.135 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10588.30 | 10588.30 | 0.741696 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00773711 | 49.1085 | 6746.85 | 0.00 | 10645.12 | 10645.12 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2690.844 | -999.000 | 0.246072 | 0.00009611 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | 8/21 16:20:00 | 2690.84 | 2646.95 | 0.246072 | 21.69 | 15.43 | 0.00856912 | 12.80 | 11.93 | 0.00850000 | 30.53 | 0.00823226 | 18.20 | 0.0000 | 21.11 | 0.00856912 | 53.9495 | 2466.64 | 0.00 | 2739.38 | 2646.75 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1278.796 | 1278.796 | 0.056179 | 0.00001119 | 36.540 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1278.80 | 1278.80 | 0.056179 | 21.11 | 14.45 | 0.00771720 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00771720 | 48.6517 | 1278.81 | 0.00 | 1378.58 | 1378.58 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2575.487 | -999.000 | 0.235326 | 0.00009199 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 2575.49 | 2531.66 | 0.235326 | 21.69 | 15.43 | 0.00857216 | 12.80 | 11.93 | 0.00850000 | 30.41 | 0.00823207 | 18.16 | 0.0000 | 21.11 | 0.00857216 | 53.9683 | 2358.93 | 0.00 | 2621.92 | 2531.50 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1278.342 | 1278.342 | 0.056159 | 0.00001118 | 36.527 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1278.34 | 1278.34 | 0.056159 | 21.11 | 14.45 | 0.00771713 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00771713 | 48.6512 | 1278.36 | 0.00 | 1378.09 | 1378.09 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 12681.079 | -999.000 | 1.137458 | 0.00045293 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | 8/21 13:30:00 | 12681.08 | 12268.15 | 1.137458 | 21.69 | 15.49 | 0.00864030 | 12.80 | 11.93 | 0.00850000 | 31.08 | 0.00823314 | 18.38 | 0.0000 | 21.11 | 0.00864030 | 54.3922 | 11401.66 | 0.00 | 12907.59 | 12270.73 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 6171.357 | 6171.357 | 0.271114 | 0.00005399 | 176.337 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6171.36 | 6171.36 | 0.271114 | 21.11 | 14.46 | 0.00772897 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00772897 | 48.7248 | 6171.42 | 0.00 | 6652.92 | 6652.92 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10341.953 | 10341.953 | 1.169494 | 0.00009048 | 223.897 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10341.95 | 10341.95 | 1.169494 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00778721 | 49.4228 | 4284.35 | 0.00 | 10399.37 | 10399.37 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10722.379 | 10722.379 | 1.226728 | 0.00009380 | 231.884 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 10722.38 | 10722.38 | 1.226728 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00779092 | 49.4462 | 4368.38 | 0.00 | 10781.92 | 10781.92 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 6853.181 | 6853.181 | 1.221652 | 0.00005995 | 143.526 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 6853.18 | 6853.18 | 1.221652 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00490514 | 31.2793 | 562.44 | 0.00 | 6891.64 | 6891.64 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 6495.129 | 6495.129 | 0.380217 | 0.00005682 | 154.038 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 6495.13 | 6495.13 | 0.380217 | 16.70 | 13.02 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00782122 | 49.6360 | 4525.61 | 0.00 | 6529.65 | 6529.65 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 459657.946 | -999.000 | 21.112167 | 0.01641792 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 459657.95 | 434532.88 | 21.112167 | 28.03 | 17.90 | 0.00888632 | 10.94 | 10.94 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 55.2357 | 23.99 | 0.00966535 | 50.9909 | 284934.11 | 0.00 | 465887.15 | 418616.82 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 97025.271 | 97025.271 | 6.333650 | 0.00084882 | 1739.018 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 97025.27 | 97025.27 | 6.333650 | 3.80 | 3.80 | 0.00505843 | 16.70 | 13.02 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 184.1191 | 21.22 | 0.00705317 | 44.2087 | 42135.47 | 0.00 | 98560.12 | 98560.12 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 47946.248 | -999.000 | 2.051317 | 0.00171253 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 47946.25 | 47946.25 | 2.051317 | 31.30 | 18.45 | 0.00823349 | 11.91 | 11.29 | 0.00823349 | 31.30 | 0.00823349 | 18.45 | 99.9965 | 21.11 | 0.00862658 | 54.3062 | 151487.96 | 0.00 | 48572.77 | 47970.12 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 9427.247 | 9427.247 | 0.615395 | 0.00008247 | 168.968 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9427.25 | 9427.25 | 0.615395 | 3.80 | 3.80 | 0.00505843 | 16.70 | 13.02 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 333.3216 | 21.11 | 0.00768513 | 48.4514 | 73377.03 | 0.00 | 9576.38 | 9576.38 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 7002.683 | 7002.683 | 1.351396 | 0.00006126 | 146.029 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 2.4286 | 2.477496 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 7002.68 | 7002.68 | 1.0000 | 1.59705040 | 1.351396 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.06125627 | 60.00 | 32.22 | 27.78 | 0.000 | 7002.68 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 7042.04 | 7042.04 | 1.59705040 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2809.354 | 2809.354 | 0.178681 | 0.00002458 | 65.582 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 0.9743 | 0.993928 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2809.35 | 2809.35 | 1.0000 | 0.21116155 | 0.178681 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.02457494 | 60.00 | 32.22 | 27.78 | 0.000 | 2809.35 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00767295 | 21.00 | 0.00767295 | 48.7070 | 1884.07 | 0.00 | 2824.35 | 2824.35 | 0.21116155 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.72 | 17.94 | 0.00800000 | 50310.0 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1326.934 | 1326.934 | 0.131353 | 0.00001161 | 29.112 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 0.4602 | 0.469459 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1326.93 | 1326.93 | 1.0000 | 0.15522968 | 0.131353 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.01160741 | 60.00 | 32.22 | 27.78 | 0.000 | 1326.93 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00763711 | 21.00 | 0.00763711 | 48.4817 | 646.75 | 0.00 | 1334.27 | 1334.27 | 0.15522968 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.03 | 16.32 | 0.00800000 | 45530.2 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1826.682 | 1826.682 | 0.124542 | 0.00001598 | 42.131 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 0.6335 | 0.646266 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1826.68 | 1826.68 | 1.0000 | 0.14718093 | 0.124542 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.01597898 | 60.00 | 32.22 | 27.78 | 0.000 | 1826.68 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00754698 | 21.00 | 0.00754698 | 47.9164 | 1181.88 | 0.00 | 1836.47 | 1836.47 | 0.14718093 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.84 | 17.65 | 0.00800000 | 49412.4 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1010.377 | 1010.377 | 0.059237 | 0.00000884 | 23.955 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 0.3504 | 0.357464 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1010.38 | 1010.38 | 1.0000 | 0.07000516 | 0.059237 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.00883832 | 60.00 | 32.22 | 27.78 | 0.000 | 1010.38 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00755893 | 21.00 | 0.00755893 | 47.9913 | 703.67 | 0.00 | 1015.75 | 1015.75 | 0.07000516 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.83 | 18.31 | 0.00800000 | 51444.3 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10967.837 | 10967.837 | 1.817922 | 0.00009595 | 230.681 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 3.8038 | 3.880337 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10967.84 | 10967.84 | 1.0000 | 2.14838088 | 1.817922 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.09594163 | 60.00 | 32.22 | 27.78 | 0.000 | 10967.84 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00753315 | 21.00 | 0.00753315 | 47.8301 | 1556.31 | 0.00 | 11029.29 | 11029.29 | 2.14838088 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.63 | 15.09 | 0.00800000 | 42068.5 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8715.339 | 8715.339 | 0.766035 | 0.00007625 | 193.823 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 3.0226 | 3.083421 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 8715.34 | 8715.34 | 1.0000 | 0.90528376 | 0.766035 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.07623781 | 60.00 | 32.22 | 27.78 | 0.000 | 8715.34 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00770916 | 21.00 | 0.00770916 | 48.9338 | 4748.19 | 0.00 | 8762.67 | 8762.67 | 0.90528376 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.09 | 16.70 | 0.00800000 | 46614.2 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24162.543 | 24162.543 | 2.486780 | 0.00021138 | 527.941 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 8.3799 | 8.548523 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 24162.54 | 24162.54 | 1.0000 | 2.93882303 | 2.486780 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.21136290 | 60.00 | 32.22 | 27.78 | 0.000 | 24162.54 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00765707 | 21.00 | 0.00765707 | 48.6068 | 11284.84 | 0.00 | 24296.34 | 24296.34 | 2.93882303 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.71 | 16.21 | 0.00800000 | 45202.1 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10401.022 | -999.000 | 0.950535 | 0.00037149 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7739 | 1004.8586 | 1.1818 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.950535 | 1.12332230 | 4197.9300 | 999.8980 | 24.38735896 | 13.37 | 6.70 | 6.67 | 682850.76 | 1.5232 | 1.523148 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | unknown | unknown | 8/21 16:20:00 | Sensible | 10401.02 | 10225.69 | 1.0000 | 1.12332230 | 0.950535 | 21.69 | 15.43 | 0.00857148 | 43581.4 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.37145558 | 6.70 | 13.37 | 6.67 | 0.000 | 10401.02 | 30.53 | 0.00823226 | 18.20 | 0.00000000 | 0.0000 | 21.11 | 0.00857148 | 21.11 | 0.00857148 | 53.9641 | 9528.24 | 0.00 | 10588.55 | 10225.00 | 1.12332230 | 21.69 | 15.62 | 0.00857148 | 43581.4 | 12.78 | 12.03 | 0.00844328 | 34155.3 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4141.151 | 4141.151 | 0.181924 | 0.00003623 | 118.332 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.950535 | 1.12332230 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 1.4362 | 1.465108 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4141.15 | 4141.15 | 1.0000 | 0.21499445 | 0.181924 | 21.11 | 14.40 | 0.00765847 | 40666.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.03622490 | 60.00 | 32.22 | 27.78 | 0.000 | 4141.15 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00765847 | 21.11 | 0.00765847 | 48.2859 | 4141.20 | 0.00 | 4464.29 | 4464.29 | 0.21499445 | 16.60 | 12.82 | 0.00765847 | 36070.1 | 36.98 | 20.01 | 0.00765847 | 56834.7 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9984.080 | -999.000 | 0.911701 | 0.00035660 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7794 | 1004.8586 | 1.1818 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.911701 | 1.07742879 | 4197.9300 | 999.8980 | 24.38735896 | 13.37 | 6.70 | 6.67 | 682850.76 | 1.4621 | 1.462090 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 9984.08 | 9809.01 | 1.0000 | 1.07742879 | 0.911701 | 21.69 | 15.44 | 0.00857440 | 43588.8 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.35656517 | 6.70 | 13.37 | 6.67 | 0.000 | 9984.08 | 30.41 | 0.00823207 | 18.16 | 0.00000000 | 0.0000 | 21.11 | 0.00857440 | 21.11 | 0.00857440 | 53.9822 | 9138.96 | 0.00 | 10164.02 | 9808.47 | 1.07742879 | 21.69 | 15.62 | 0.00857440 | 43588.8 | 12.78 | 12.03 | 0.00844369 | 34155.2 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4141.306 | 4141.306 | 0.181931 | 0.00003623 | 118.336 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.911701 | 1.07742879 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 1.4363 | 1.465162 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4141.31 | 4141.31 | 1.0000 | 0.21500247 | 0.181931 | 21.11 | 14.40 | 0.00765851 | 40666.9 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.03622625 | 60.00 | 32.22 | 27.78 | 0.000 | 4141.31 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00765851 | 21.11 | 0.00765851 | 48.2861 | 4141.36 | 0.00 | 4464.45 | 4464.45 | 0.21500247 | 16.60 | 12.82 | 0.00765851 | 36070.1 | 36.98 | 20.01 | 0.00765851 | 56834.8 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 59489.454 | -999.000 | 5.545226 | 0.00212479 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6310 | 1004.8586 | 1.1818 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.545226 | 6.55323009 | 4197.9300 | 999.8980 | 24.38735896 | 13.37 | 6.70 | 6.67 | 682850.76 | 8.7119 | 8.711763 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | unknown | unknown | 8/21 13:30:00 | Sensible | 59489.45 | 59489.45 | 1.0000 | 6.55323009 | 5.545226 | 21.69 | 15.37 | 0.00849458 | 43386.4 | 12.80 | 11.93 | 0.00849458 | 34308.5 | 2.12456903 | 6.70 | 13.37 | 6.67 | 0.000 | 59489.45 | 31.08 | 0.00823314 | 18.38 | 0.00000000 | 0.0000 | 21.11 | 0.00849458 | 21.11 | 0.00849458 | 53.4853 | 55588.18 | 0.00 | 60562.58 | 59508.29 | 6.55323009 | 21.69 | 15.55 | 0.00849458 | 43386.4 | 12.80 | 12.03 | 0.00843086 | 34144.8 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24034.761 | 24034.761 | 1.055878 | 0.00021027 | 686.775 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.545226 | 6.55323009 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 8.3356 | 8.503315 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 24034.76 | 24034.76 | 1.0000 | 1.24781453 | 1.055878 | 21.11 | 14.42 | 0.00768487 | 40734.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.21024512 | 60.00 | 32.22 | 27.78 | 0.000 | 24034.76 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00768487 | 21.11 | 0.00768487 | 48.4498 | 24034.91 | 0.00 | 25910.27 | 25910.27 | 1.24781453 | 16.60 | 12.84 | 0.00768487 | 36136.9 | 36.97 | 20.03 | 0.00768487 | 56901.4 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 59544.639 | -999.000 | 5.166180 | 0.00212676 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1355 | 1004.8586 | 1.1818 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.166180 | 6.10528117 | 4197.9300 | 999.8980 | 24.38735896 | 13.37 | 6.70 | 6.67 | 682850.76 | 8.7200 | 8.719845 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | unknown | unknown | unknown | 8/21 15:00:00 | Sensible | 59544.64 | 55972.76 | 1.0000 | 6.10528117 | 5.166180 | 21.69 | 15.60 | 0.00876599 | 44075.2 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 2.12653988 | 6.70 | 13.37 | 6.67 | 0.000 | 59544.64 | 31.30 | 0.00823349 | 18.45 | 0.00000000 | 0.0000 | 21.11 | 0.00876599 | 21.11 | 0.00876599 | 55.1727 | 51784.34 | 0.00 | 60590.69 | 56012.06 | 6.10528117 | 21.69 | 15.79 | 0.00876599 | 44075.2 | 12.71 | 12.03 | 0.00846893 | 34150.9 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24049.922 | 24049.922 | 1.056544 | 0.00021040 | 687.208 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.166180 | 6.10528117 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 8.3408 | 8.508679 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 24049.92 | 24049.92 | 1.0000 | 1.24860165 | 1.056544 | 21.11 | 14.42 | 0.00768497 | 40734.3 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.21037775 | 60.00 | 32.22 | 27.78 | 0.000 | 24049.92 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00768497 | 21.11 | 0.00768497 | 48.4504 | 24050.07 | 0.00 | 25926.62 | 25926.62 | 1.24860165 | 16.60 | 12.84 | 0.00768497 | 36137.1 | 36.97 | 20.03 | 0.00768497 | 56901.7 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9124.617 | -999.000 | 0.831655 | 0.00032590 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7921 | 1004.8586 | 1.1818 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.831655 | 0.98283208 | 4197.9300 | 999.8980 | 24.38735896 | 13.37 | 6.70 | 6.67 | 682850.76 | 1.3363 | 1.336229 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | unknown | unknown | unknown | 8/21 09:30:00 | Sensible | 9124.62 | 8950.15 | 1.0000 | 0.98283208 | 0.831655 | 21.69 | 15.44 | 0.00858126 | 43606.2 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.32587085 | 6.70 | 13.37 | 6.67 | 0.000 | 9124.62 | 27.16 | 0.00822694 | 17.07 | 0.00000000 | 0.0000 | 21.11 | 0.00858126 | 21.11 | 0.00858126 | 54.0249 | 8336.57 | 0.00 | 9288.91 | 8949.90 | 0.98283208 | 21.69 | 15.63 | 0.00858126 | 43606.2 | 12.77 | 12.03 | 0.00844463 | 34155.0 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4140.328 | 4140.328 | 0.181888 | 0.00003622 | 118.308 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.831655 | 0.98283208 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 1.4359 | 1.464817 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4140.33 | 4140.33 | 1.0000 | 0.21495174 | 0.181888 | 21.11 | 14.40 | 0.00765841 | 40666.6 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.03621770 | 60.00 | 32.22 | 27.78 | 0.000 | 4140.33 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00765841 | 21.11 | 0.00765841 | 48.2855 | 4140.38 | 0.00 | 4463.40 | 4463.40 | 0.21495174 | 16.60 | 12.82 | 0.00765841 | 36069.9 | 36.98 | 20.01 | 0.00765841 | 56834.6 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8758.617 | -999.000 | 0.797561 | 0.00031283 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7984 | 1004.8586 | 1.1818 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.797561 | 0.94254084 | 4197.9300 | 999.8980 | 24.38735896 | 13.37 | 6.70 | 6.67 | 682850.76 | 1.2827 | 1.282631 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | unknown | unknown | unknown | 8/21 09:10:00 | Sensible | 8758.62 | 8584.34 | 1.0000 | 0.94254084 | 0.797561 | 21.69 | 15.44 | 0.00858462 | 43614.8 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.31279974 | 6.70 | 13.37 | 6.67 | 0.000 | 8758.62 | 26.66 | 0.00822614 | 16.89 | 0.00000000 | 0.0000 | 21.11 | 0.00858462 | 21.11 | 0.00858462 | 54.0458 | 7994.81 | 0.00 | 8916.25 | 8584.22 | 0.94254084 | 21.69 | 15.63 | 0.00858462 | 43614.8 | 12.77 | 12.03 | 0.00844509 | 34155.0 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4140.483 | 4140.483 | 0.181895 | 0.00003622 | 118.313 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.797561 | 0.94254084 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 1.4360 | 1.464871 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4140.48 | 4140.48 | 1.0000 | 0.21495977 | 0.181895 | 21.11 | 14.40 | 0.00765845 | 40666.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.03621906 | 60.00 | 32.22 | 27.78 | 0.000 | 4140.48 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00765845 | 21.11 | 0.00765845 | 48.2857 | 4140.53 | 0.00 | 4463.57 | 4463.57 | 0.21495977 | 16.60 | 12.82 | 0.00765845 | 36070.0 | 36.98 | 20.01 | 0.00765845 | 56834.6 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10588.304 | 10588.304 | 0.741696 | 0.00009263 | 243.135 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 3.6722 | 3.746061 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10588.30 | 10588.30 | 1.0000 | 0.87652038 | 0.741696 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.09262165 | 60.00 | 32.22 | 27.78 | 0.000 | 10588.30 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00773711 | 21.00 | 0.00773711 | 49.1085 | 6746.85 | 0.00 | 10645.12 | 10645.12 | 0.87652038 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.51 | 17.54 | 0.00800000 | 49079.5 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2690.844 | -999.000 | 0.246072 | 0.00009611 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7696 | 1004.8586 | 1.1818 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.246072 | 0.29080206 | 4197.9300 | 999.8980 | 24.38735896 | 13.37 | 6.70 | 6.67 | 682850.76 | 0.3941 | 0.394053 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | unknown | unknown | 8/21 16:20:00 | Sensible | 2690.84 | 2646.95 | 1.0000 | 0.29080206 | 0.246072 | 21.69 | 15.43 | 0.00856912 | 43575.4 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.09609913 | 6.70 | 13.37 | 6.67 | 0.000 | 2690.84 | 30.53 | 0.00823226 | 18.20 | 0.00000000 | 0.0000 | 21.11 | 0.00856912 | 21.11 | 0.00856912 | 53.9495 | 2466.64 | 0.00 | 2739.38 | 2646.75 | 0.29080206 | 21.69 | 15.62 | 0.00856912 | 43575.4 | 12.78 | 12.03 | 0.00844296 | 34155.3 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1278.796 | 1278.796 | 0.056179 | 0.00001119 | 36.540 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.246072 | 0.29080206 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 0.4435 | 0.452428 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1278.80 | 1278.80 | 1.0000 | 0.06639074 | 0.056179 | 21.11 | 14.45 | 0.00771720 | 40816.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.01118633 | 60.00 | 32.22 | 27.78 | 0.000 | 1278.80 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00771720 | 21.11 | 0.00771720 | 48.6517 | 1278.81 | 0.00 | 1378.58 | 1378.58 | 0.06639074 | 16.60 | 12.88 | 0.00771720 | 36218.8 | 36.97 | 20.06 | 0.00771720 | 56983.4 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2575.487 | -999.000 | 0.235326 | 0.00009199 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7752 | 1004.8586 | 1.1818 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.235326 | 0.27810343 | 4197.9300 | 999.8980 | 24.38735896 | 13.37 | 6.70 | 6.67 | 682850.76 | 0.3772 | 0.377160 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 2575.49 | 2531.66 | 1.0000 | 0.27810343 | 0.235326 | 21.69 | 15.43 | 0.00857216 | 43583.1 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.09197931 | 6.70 | 13.37 | 6.67 | 0.000 | 2575.49 | 30.41 | 0.00823207 | 18.16 | 0.00000000 | 0.0000 | 21.11 | 0.00857216 | 21.11 | 0.00857216 | 53.9683 | 2358.93 | 0.00 | 2621.92 | 2531.50 | 0.27810343 | 21.69 | 15.62 | 0.00857216 | 43583.1 | 12.78 | 12.03 | 0.00844338 | 34155.2 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1278.342 | 1278.342 | 0.056159 | 0.00001118 | 36.527 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.235326 | 0.27810343 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 0.4433 | 0.452268 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1278.34 | 1278.34 | 1.0000 | 0.06636716 | 0.056159 | 21.11 | 14.45 | 0.00771713 | 40815.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.01118235 | 60.00 | 32.22 | 27.78 | 0.000 | 1278.34 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00771713 | 21.11 | 0.00771713 | 48.6512 | 1278.36 | 0.00 | 1378.09 | 1378.09 | 0.06636716 | 16.60 | 12.88 | 0.00771713 | 36218.6 | 36.97 | 20.06 | 0.00771713 | 56983.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12681.079 | -999.000 | 1.137458 | 0.00045293 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9019 | 1004.8586 | 1.1818 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.137458 | 1.34422388 | 4197.9300 | 999.8980 | 24.38735896 | 13.37 | 6.70 | 6.67 | 682850.76 | 1.8571 | 1.857044 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | unknown | unknown | 8/21 13:30:00 | Sensible | 12681.08 | 12268.15 | 1.0000 | 1.34422388 | 1.137458 | 21.69 | 15.49 | 0.00864030 | 43756.0 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.45288409 | 6.70 | 13.37 | 6.67 | 0.000 | 12681.08 | 31.08 | 0.00823314 | 18.38 | 0.00000000 | 0.0000 | 21.11 | 0.00864030 | 21.11 | 0.00864030 | 54.3922 | 11401.66 | 0.00 | 12907.59 | 12270.73 | 1.34422388 | 21.69 | 15.68 | 0.00864030 | 43756.0 | 12.75 | 12.03 | 0.00845264 | 34153.7 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6171.357 | 6171.357 | 0.271114 | 0.00005399 | 176.337 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.137458 | 1.34422388 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 2.1403 | 2.183379 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6171.36 | 6171.36 | 1.0000 | 0.32039681 | 0.271114 | 21.11 | 14.46 | 0.00772897 | 40845.9 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.05398421 | 60.00 | 32.22 | 27.78 | 0.000 | 6171.36 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00772897 | 21.11 | 0.00772897 | 48.7248 | 6171.42 | 0.00 | 6652.92 | 6652.92 | 0.32039681 | 16.60 | 12.89 | 0.00772897 | 36248.5 | 36.97 | 20.07 | 0.00772897 | 57013.2 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10341.953 | 10341.953 | 1.169494 | 0.00009048 | 223.897 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 3.5867 | 3.658904 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10341.95 | 10341.95 | 1.0000 | 1.38208281 | 1.169494 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.09046669 | 60.00 | 32.22 | 27.78 | 0.000 | 10341.95 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00778721 | 21.00 | 0.00778721 | 49.4228 | 4284.35 | 0.00 | 10399.37 | 10399.37 | 1.38208281 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.98 | 15.95 | 0.00800000 | 44459.1 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10722.379 | 10722.379 | 1.226728 | 0.00009380 | 231.884 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 3.7187 | 3.793496 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 10722.38 | 10722.38 | 1.0000 | 1.44972072 | 1.226728 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.09379448 | 60.00 | 32.22 | 27.78 | 0.000 | 10722.38 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00779092 | 21.00 | 0.00779092 | 49.4462 | 4368.38 | 0.00 | 10781.92 | 10781.92 | 1.44972072 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.89 | 15.92 | 0.00800000 | 44372.0 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6853.181 | 6853.181 | 1.221652 | 0.00005995 | 143.526 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 2.3768 | 2.424603 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 6853.18 | 6853.18 | 1.0000 | 1.44372168 | 1.221652 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.05994850 | 60.00 | 32.22 | 27.78 | 0.000 | 6853.18 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 18.06 | 0.00490514 | 21.00 | 0.00490514 | 31.2793 | 562.44 | 0.00 | 6891.64 | 6891.64 | 1.44372168 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.28 | 14.96 | 0.00800000 | 41708.3 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6495.129 | 6495.129 | 0.380217 | 0.00005682 | 154.038 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 2.2526 | 2.297927 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 6495.13 | 6495.13 | 1.0000 | 0.44933287 | 0.380217 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.05681642 | 60.00 | 32.22 | 27.78 | 0.000 | 6495.13 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00782122 | 21.00 | 0.00782122 | 49.6360 | 4525.61 | 0.00 | 6529.65 | 6529.65 | 0.44933287 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.85 | 18.32 | 0.00800000 | 51466.6 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 459657.946 | -999.000 | 21.112167 | 0.01641792 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3592 | 1004.8586 | 1.1818 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.112167 | 24.94990805 | 4197.9300 | 999.8980 | 24.38735896 | 13.37 | 6.70 | 6.67 | 682850.76 | 67.3146 | 67.314554 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 459657.95 | 434532.88 | 1.0000 | 24.94990805 | 21.112167 | 28.03 | 17.90 | 0.00888632 | 50850.8 | 10.94 | 10.94 | 0.00850000 | 32427.5 | 16.41624200 | 6.70 | 13.37 | 6.67 | 47304.736 | 412353.21 | 31.30 | 0.00823349 | 18.45 | 11.66146000 | 55.2357 | 23.99 | 0.00969219 | 23.99 | 0.00966535 | 50.9909 | 284934.11 | 0.00 | 465887.15 | 418616.82 | 24.94990805 | 28.03 | 18.10 | 0.00888632 | 50850.8 | 11.60 | 11.23 | 0.00813524 | 32177.9 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 97025.271 | 97025.271 | 6.333650 | 0.00084882 | 1739.018 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.112167 | 24.94990805 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 33.6496 | 34.326800 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 97025.27 | 97025.27 | 1.0000 | 7.48497241 | 6.333650 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 0.84873281 | 60.00 | 32.22 | 27.78 | 0.000 | 97025.27 | 3.80 | 0.00505843 | 3.80 | 11.66146000 | 184.1191 | 18.36 | 0.00726635 | 21.22 | 0.00705317 | 44.2087 | 42135.47 | 0.00 | 98560.12 | 98560.12 | 7.48497241 | 2.80 | 2.80 | 0.00505843 | 15490.7 | 15.78 | 9.78 | 0.00505843 | 28658.4 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 47946.248 | -999.000 | 2.051317 | 0.00171253 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1456 | 1004.8586 | 1.1818 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.42411771 | 4197.9300 | 999.8980 | 24.38735896 | 13.37 | 6.70 | 6.67 | 682850.76 | 7.0215 | 7.021483 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | Sensible | 47946.25 | 47946.25 | 1.0000 | 2.42420295 | 2.051317 | 31.30 | 18.45 | 0.00823349 | 52522.0 | 11.91 | 11.29 | 0.00823349 | 32743.9 | 1.71235419 | 6.70 | 13.37 | 6.67 | 2195.006 | 45751.24 | 31.30 | 0.00823349 | 18.45 | 2.05124512 | 99.9965 | 21.11 | 0.00861962 | 21.11 | 0.00862658 | 54.3062 | 151487.96 | 0.00 | 48572.77 | 47970.12 | 2.42420295 | 31.30 | 18.65 | 0.00823349 | 52522.0 | 11.90 | 11.35 | 0.00813496 | 32485.4 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 9427.247 | 9427.247 | 0.615395 | 0.00008247 | 168.968 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.42411771 | 4197.9300 | 999.8980 | 2.47250776 | 54.44 | 82.22 | 27.78 | 288340.14 | 3.2695 | 3.335288 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 9427.25 | 9427.25 | 1.0000 | 0.72726088 | 0.615395 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 16.70 | 13.02 | 0.00800000 | 37036.7 | 0.08246526 | 60.00 | 32.22 | 27.78 | 0.000 | 9427.25 | 3.80 | 0.00505843 | 3.80 | 2.05124512 | 333.3216 | 21.11 | 0.00768378 | 21.11 | 0.00768513 | 48.4514 | 73377.03 | 0.00 | 9576.38 | 9576.38 | 0.72726088 | 2.80 | 2.80 | 0.00505843 | 15490.7 | 15.78 | 9.78 | 0.00505843 | 28658.4 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 21.11 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.003540 | 0.000914 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.003540 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 141.00 | 7679.67 | 0.00 |
RETAIL_1_FLR_1 | 802.83 | 7350.33 | 13.67 |
RETAIL_2_FLR_1 | 1098.33 | 6711.67 | 181.17 |
MECH_FLR_1 | 5.00 | 8502.83 | 0.00 |
STORAGE_FLR_1 | 0.00 | 8753.83 | 0.00 |
LAUNDRY_FLR_1 | 7537.17 | 3462.00 | 2912.00 |
CAFE_FLR_1 | 3378.00 | 4923.50 | 1133.33 |
LOBBY_FLR_1 | 2702.50 | 4832.50 | 906.33 |
ROOM_1_FLR_3 | 75.33 | 8288.33 | 71.83 |
ROOM_2_FLR_3 | 246.50 | 8491.17 | 246.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 233.17 | 8760.00 | 233.17 |
ROOM_5_FLR_3 | 76.33 | 8468.83 | 76.33 |
ROOM_6_FLR_3 | 202.17 | 8643.67 | 202.17 |
CORRIDOR_FLR_3 | 243.17 | 8714.83 | 242.17 |
ROOM_1_FLR_6 | 302.17 | 8184.50 | 268.83 |
ROOM_2_FLR_6 | 595.17 | 8412.50 | 589.00 |
ROOM_3_MULT9_FLR_6 | 53.83 | 8106.83 | 32.17 |
BANQUET_FLR_6 | 6151.17 | 1790.67 | 898.67 |
DINING_FLR_6 | 7054.00 | 1063.67 | 791.83 |
KITCHEN_FLR_6 | 8514.50 | 6415.33 | 6378.17 |
CORRIDOR_FLR_6 | 42.67 | 8191.33 | 2.67 |
Facility | 8720.50 | 8760.00 | 7353.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 3.67 | 0.00 | 3.67 |
ROOM_2_FLR_3 | 0.00 | 1.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.33 | 0.00 | 0.33 |
ROOM_5_FLR_3 | 0.00 | 3.50 | 0.00 | 3.50 |
ROOM_6_FLR_3 | 0.00 | 2.50 | 0.00 | 2.50 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 5.00 | 0.00 | 5.00 |
ROOM_2_FLR_6 | 0.00 | 1.33 | 0.00 | 1.33 |
ROOM_3_MULT9_FLR_6 | 0.00 | 18.00 | 0.00 | 18.00 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 22.50 | 0.00 | 22.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 1.025 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.487 | 0.136 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.563 | 0.045 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.695 | 0.051 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.573 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 24.150 | 0.145 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.55 | 142.30 | 748.35 | 3.813 | 0.107 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.05 | 422.44 | 5183.56 | 1.791 | 0.044 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.475 | 0.176 | 0.000 | 0.092 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.474 | 0.175 | 0.000 | 0.091 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.538 | 0.078 | 0.000 | 0.143 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.475 | 0.176 | 0.000 | 0.093 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.475 | 0.175 | 0.000 | 0.091 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.568 | 0.021 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.475 | 0.176 | 0.000 | 0.104 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.475 | 0.176 | 0.000 | 0.102 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.539 | 0.143 | 0.000 | 0.165 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.909 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 5.289 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 22.153 | 0.146 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.100 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 0.965 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.317 | 0.003 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.474 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.660 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.544 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 20.261 | 0.003 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.55 | 142.30 | 748.35 | 3.541 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.05 | 422.44 | 5183.56 | 1.657 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.463 | 0.004 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.462 | 0.004 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.526 | 0.002 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.464 | 0.004 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.463 | 0.004 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.539 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.463 | 0.004 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.462 | 0.004 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.526 | 0.003 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.153 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.361 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 13.534 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.046 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.78 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.55 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.173 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.05 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 0.399 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.96 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.96 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.11 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 135.585 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 42428738.66 | 0.00 | 42428738.66 | 0.00 | 42428738.66 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 5689291.46 | 0.00 | 5689291.46 | 310101.36 | 5999392.81 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 4125288.72 | 0.00 | 4125288.72 | 119699.52 | 4244988.24 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 3892113.81 | 0.00 | 3892113.81 | 282898.54 | 4175012.35 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1851209.97 | 0.00 | 1851209.97 | 163216.88 | 2014426.85 | 1821682.01 | 1145.94 | 1101.61 | 6512.45 | 0.00 |
LAUNDRY_FLR_1 | 64130195.81 | 0.00 | 64130195.81 | 386283.51 | 64516479.33 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 24434692.83 | 0.00 | 24434692.83 | 685496.60 | 25120189.43 | 14544917.54 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 79433436.34 | 0.00 | 79433436.34 | 1958620.37 | 81392056.71 | 39585427.43 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 94539.83 | 2041415.45 | 179991.83 | 2221407.27 | 1946875.62 | 0.00 | 7138.83 | 1621.17 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 93368.59 | 2040016.11 | 179978.09 | 2219994.20 | 1946647.51 | 0.00 | 7138.83 | 1621.17 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 105375.58 | 26503262.85 | 50219.74 | 26553482.59 | 26397887.27 | 0.00 | 7150.67 | 1609.33 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 92216.18 | 26497321.91 | 50233.47 | 26547555.38 | 26405105.73 | 0.00 | 7175.80 | 1584.20 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 94797.57 | 2041673.19 | 179991.83 | 2221665.02 | 1946875.62 | 0.00 | 7138.83 | 1621.17 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 93614.96 | 2040262.47 | 179978.09 | 2220240.57 | 1946647.51 | 0.00 | 7138.83 | 1621.17 | 0.00 |
CORRIDOR_FLR_3 | 23178623.16 | 0.00 | 23178623.16 | 217646.33 | 23396269.49 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 106408.24 | 593127.14 | 180028.86 | 773156.00 | 486718.90 | 0.00 | 7138.83 | 1621.17 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 104937.98 | 591599.86 | 180015.12 | 771614.98 | 486661.88 | 0.00 | 7138.83 | 1621.17 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 106148.55 | 3233068.97 | 92109.06 | 3325178.03 | 3126920.42 | 0.00 | 7139.00 | 1621.00 | 0.00 |
BANQUET_FLR_6 | 42376069.74 | 0.00 | 42376069.74 | 439585.22 | 42815654.96 | 37458366.31 | 3543.83 | 299.35 | 4916.82 | 0.00 |
DINING_FLR_6 | 45658373.76 | 0.00 | 45658373.76 | 439585.22 | 46097958.99 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
KITCHEN_FLR_6 | 59603430.71 | 0.00 | 59603430.71 | 393530.69 | 59996961.40 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 11887088.77 | 0.00 | 11887088.77 | 385165.88 | 12272254.65 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.46E+10 | 17688941.13 | 0.46E+10 | 18137997.94 | 0.46E+10 | 0.43E+10 | 4659.09 | 7261.15 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3454 | 0.0000 | 1.3454 | 0.0000 | 1.3454 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.1804 | 0.0000 | 0.1804 | 0.0098 | 0.1902 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1308 | 0.0000 | 0.1308 | 0.0038 | 0.1346 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.1234 | 0.0000 | 0.1234 | 0.0090 | 0.1324 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0587 | 0.0000 | 0.0587 | 0.0052 | 0.0639 | 0.0578 | 1145.94 | 1101.61 | 6512.45 |
LAUNDRY_FLR_1 | 2.0336 | 0.0000 | 2.0336 | 0.0122 | 2.0458 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7748 | 0.0000 | 0.7748 | 0.0217 | 0.7966 | 0.4612 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 2.5188 | 0.0000 | 2.5188 | 0.0621 | 2.5809 | 1.2552 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0617 | 0.0030 | 0.0647 | 0.0057 | 0.0704 | 0.0617 | 0.00 | 7138.83 | 1621.17 |
ROOM_2_FLR_3 | 0.0617 | 0.0030 | 0.0647 | 0.0057 | 0.0704 | 0.0617 | 0.00 | 7138.83 | 1621.17 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0029 | 0.8402 | 0.0016 | 0.8418 | 0.8373 | 0.00 | 7175.80 | 1584.20 |
ROOM_5_FLR_3 | 0.0617 | 0.0030 | 0.0647 | 0.0057 | 0.0704 | 0.0617 | 0.00 | 7138.83 | 1621.17 |
ROOM_6_FLR_3 | 0.0617 | 0.0030 | 0.0647 | 0.0057 | 0.0704 | 0.0617 | 0.00 | 7138.83 | 1621.17 |
CORRIDOR_FLR_3 | 0.7350 | 0.0000 | 0.7350 | 0.0069 | 0.7419 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0154 | 0.0034 | 0.0188 | 0.0057 | 0.0245 | 0.0154 | 0.00 | 7138.83 | 1621.17 |
ROOM_2_FLR_6 | 0.0154 | 0.0033 | 0.0188 | 0.0057 | 0.0245 | 0.0154 | 0.00 | 7138.83 | 1621.17 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0034 | 0.1025 | 0.0029 | 0.1054 | 0.0992 | 0.00 | 7139.00 | 1621.00 |
BANQUET_FLR_6 | 1.3437 | 0.0000 | 1.3437 | 0.0139 | 1.3577 | 1.1878 | 3543.83 | 299.35 | 4916.82 |
DINING_FLR_6 | 1.4478 | 0.0000 | 1.4478 | 0.0139 | 1.4618 | 1.1878 | 0.00 | 0.00 | 8760.00 |
KITCHEN_FLR_6 | 1.8900 | 0.0000 | 1.8900 | 0.0125 | 1.9025 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3769 | 0.0000 | 0.3769 | 0.0122 | 0.3892 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 80.7102 | 0.3070 | 81.0171 | 0.4541 | 81.4713 | 73.1130 | 4659.09 | 7261.15 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.57E+09 | 0.00 | 0.57E+09 | 0.19E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 90346581.89 | 891407.49 | 91237989.37 | 64690340.46 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 18.0991 | 0.0000 | 18.0991 | 6.1430 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 2.8649 | 0.0283 | 2.8931 | 2.0513 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 7724.90 | 0.00 | 0.00 | 0.00 | 1035.10 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 18.1620 | 0.0000 | 0.0000 | 0.0000 | 17.6479 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 2.8649 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1314 |
Defaulted Fields | 1179 |
Fields with Defaults | 3965 |
Autosized Fields | 347 |
Autosizable Fields | 400 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5159.85 | 72090.71 | 13-MAY-05:00 | 360462.95 | 29-SEP-19:10 |
Electricity:Building | 2519.39 | 32661.02 | 03-JUN-05:00 | 151906.32 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 323.72 | 3705.45 | 02-JAN-02:10 | 24299.15 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2512.30 | 32519.87 | 03-JUN-05:00 | 151664.99 | 02-JAN-20:10 |
InteriorLights:Electricity | 767.29 | 6828.07 | 03-JUN-05:00 | 62892.57 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 173.46 | 1576.23 | 02-JAN-02:10 | 14185.34 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 767.29 | 6828.07 | 03-JUN-05:00 | 62892.57 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 767.29 | 6828.07 | 03-JUN-05:00 | 62892.57 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 173.46 | 1576.23 | 02-JAN-02:10 | 14185.34 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 767.29 | 6828.07 | 03-JUN-05:00 | 62892.57 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.80 | 222.61 | 02-JAN-02:10 | 1390.02 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.61 | 78.27 | 02-JAN-02:10 | 704.41 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.61 | 78.27 | 02-JAN-02:10 | 704.41 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.77 | 257.78 | 02-JAN-02:10 | 1609.65 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.97 | 90.64 | 02-JAN-02:10 | 815.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.97 | 90.64 | 02-JAN-02:10 | 815.72 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 29.11 | 327.88 | 02-JAN-02:10 | 2199.84 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 16.64 | 151.16 | 02-JAN-02:10 | 1360.40 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 16.64 | 151.16 | 02-JAN-02:10 | 1360.40 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.38 | 76.28 | 02-JAN-02:10 | 469.87 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.78 | 25.30 | 02-JAN-02:10 | 227.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.78 | 25.30 | 02-JAN-02:10 | 227.72 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.30 | 1002.39 | 02-JAN-02:10 | 4930.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.37 | 39.69 | 02-JAN-02:10 | 357.21 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.37 | 39.69 | 02-JAN-02:10 | 357.21 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 32.44 | 373.53 | 13-MAY-05:00 | 2727.18 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 18.10 | 170.32 | 13-MAY-05:00 | 1761.91 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 18.10 | 170.32 | 13-MAY-05:00 | 1761.91 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 271.03 | 3225.37 | 03-JUN-05:00 | 20294.39 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 122.03 | 1113.96 | 03-JUN-05:00 | 10265.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 122.03 | 1113.96 | 03-JUN-05:00 | 10265.18 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 18.66 | 264.62 | 01-JAN-02:10 | 1227.54 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 18.66 | 264.59 | 01-JAN-02:10 | 1227.39 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 304.77 | 4565.05 | 01-JAN-02:10 | 20923.25 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 76.02 | 643.59 | 01-JAN-02:10 | 5851.22 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 76.02 | 643.59 | 01-JAN-02:10 | 5851.22 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 304.86 | 4566.30 | 01-JAN-02:10 | 20928.98 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 76.04 | 643.77 | 01-JAN-02:10 | 5852.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 76.04 | 643.77 | 01-JAN-02:10 | 5852.82 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 18.66 | 264.62 | 01-JAN-02:10 | 1227.54 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 18.66 | 264.59 | 01-JAN-02:10 | 1227.39 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.66 | 66.15 | 01-JAN-02:10 | 306.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.50 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.50 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.66 | 66.15 | 01-JAN-02:10 | 306.85 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.49 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.49 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.10 | 540.75 | 01-JAN-02:10 | 2478.43 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 9.00 | 76.24 | 01-JAN-02:10 | 693.10 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 9.00 | 76.24 | 01-JAN-02:10 | 693.10 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 210.69 | 2547.25 | 03-JUN-05:00 | 9841.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 34.84 | 297.95 | 03-JUN-05:00 | 3094.06 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 34.84 | 297.95 | 03-JUN-05:00 | 3094.06 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 210.69 | 2547.25 | 03-JUN-05:00 | 9841.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 34.84 | 297.95 | 03-JUN-05:00 | 3094.06 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 34.84 | 297.95 | 03-JUN-05:00 | 3094.06 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 454.16 | 6253.02 | 02-JAN-02:10 | 18944.06 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.33 | 121.09 | 02-JAN-02:10 | 1089.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.33 | 121.09 | 02-JAN-02:10 | 1089.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1745.01 | 25691.80 | 02-JAN-02:10 | 89475.41 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1745.01 | 25691.80 | 02-JAN-02:10 | 89475.41 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 62.33 | 1114.62 | 03-FEB-23:30 | 3263.15 | 14-JUL-06:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1184.87 | 2734.20 | 25-NOV-03:20 | 194311.18 | 16-OCT-10:50 |
LowTempRefrigeration:Refrigeration:Electricity | 20.48 | 0.00 | 01-JAN-11:10 | 1892.65 | 30-SEP-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.76 | 943.52 | 09-JAN-06:00 | 1203.19 | 11-FEB-14:10 |
Fans:Electricity | 561.22 | 13222.12 | 20-FEB-04:30 | 37012.34 | 16-OCT-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 593.68 | 13802.23 | 20-FEB-04:30 | 38229.04 | 16-OCT-21:10 |
ExteriorEquipment:Electricity | 651.48 | 9618.58 | 02-JAN-02:20 | 39726.11 | 18-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 32.45 | 553.76 | 27-MAY-05:00 | 1868.65 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 5159.85 | 72090.71 | 13-MAY-05:00 | 360462.95 | 29-SEP-19:10 |
ElectricityPurchased:Plant | 5159.85 | 72090.71 | 13-MAY-05:00 | 360462.95 | 29-SEP-19:10 |
Cogeneration:ElectricityPurchased | 5159.85 | 72090.71 | 13-MAY-05:00 | 360462.95 | 29-SEP-19:10 |
General:Cogeneration:ElectricityPurchased | 5159.85 | 72090.71 | 13-MAY-05:00 | 360462.95 | 29-SEP-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5159.85 | 72090.71 | 13-MAY-05:00 | 360462.95 | 29-SEP-19:10 |
ElectricityNet:Plant | 5159.85 | 72090.71 | 13-MAY-05:00 | 360462.95 | 29-SEP-19:10 |
Cogeneration:ElectricityNet | 5159.85 | 72090.71 | 13-MAY-05:00 | 360462.95 | 29-SEP-19:10 |
General:Cogeneration:ElectricityNet | 5159.85 | 72090.71 | 13-MAY-05:00 | 360462.95 | 29-SEP-19:10 |
General:Fans:Electricity | 561.22 | 13222.12 | 20-FEB-04:30 | 37012.34 | 16-OCT-21:10 |
ExteriorLights:Electricity | 242.88 | 0.00 | 01-JAN-07:00 | 15448.40 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 242.88 | 0.00 | 01-JAN-07:00 | 15448.40 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
WaterSystems:Electricity | 90.75 | 1086.59 | 26-JUL-00:30 | 4738.61 | 05-JUN-18:10 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.59 | 26-JUL-00:30 | 4738.61 | 05-JUN-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 878.32 | 0.00 | 01-JAN-00:10 | 180333.25 | 16-OCT-10:50 |
General:Cooling:Electricity | 878.32 | 0.00 | 01-JAN-00:10 | 180333.25 | 16-OCT-10:50 |
Pumps:Electricity | 160.57 | 48.96 | 08-OCT-07:10 | 7962.52 | 29-SEP-15:30 |
General:Pumps:Electricity | 160.57 | 48.96 | 08-OCT-07:10 | 7962.52 | 29-SEP-15:30 |
WIRED_LTG_ELECTRICITY | 27.01 | 0.00 | 01-JAN-00:10 | 2213.82 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5637.55 | 29270.80 | 26-APR-01:10 | 517553.47 | 02-JAN-21:00 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3848.71 | 15908.90 | 20-JAN-11:10 | 438939.99 | 29-MAR-22:00 |
WaterSystems:NaturalGas | 2934.36 | 15908.90 | 06-JAN-16:10 | 246240.35 | 02-FEB-22:00 |
Water Heater:WaterSystems:NaturalGas | 2934.36 | 15908.90 | 06-JAN-16:10 | 246240.35 | 02-FEB-22:00 |
Heating:NaturalGas | 914.35 | 0.00 | 02-JAN-11:10 | 230195.00 | 08-JAN-07:00 |
Boiler:Heating:NaturalGas | 914.35 | 0.00 | 02-JAN-11:10 | 230195.00 | 08-JAN-07:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2801.74 | 0.00 | 01-JAN-00:10 | 506162.69 | 16-OCT-10:50 |
PlantLoopCoolingDemand:HVAC | 2801.74 | 0.00 | 01-JAN-00:10 | 506162.69 | 16-OCT-10:50 |
CoolingCoils:PlantLoopCoolingDemand | 2801.74 | 0.00 | 01-JAN-00:10 | 506162.69 | 16-OCT-10:50 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 16791.35 | 143690.89 | 12-FEB-14:50 | 1981314.48 | 16-OCT-10:50 |
EnergyTransfer:Building | 5204.12 | 106337.84 | 29-MAR-12:10 | 303713.36 | 16-OCT-15:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 726.38 | 11775.45 | 29-MAR-03:00 | 35333.77 | 30-SEP-10:50 |
Refrigeration:EnergyTransfer | 185.67 | 4016.79 | 03-FEB-23:10 | 10368.60 | 14-JUL-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.84 | 2008.40 | 03-FEB-23:10 | 5184.30 | 14-JUL-06:20 |
General:Refrigeration:EnergyTransfer | 92.84 | 2008.40 | 03-FEB-23:10 | 5184.30 | 14-JUL-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.84 | 2008.40 | 03-FEB-23:10 | 5184.30 | 14-JUL-06:20 |
EnergyTransfer:Plant | 8157.38 | 21597.27 | 12-FEB-14:50 | 1225912.42 | 16-OCT-10:50 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.67 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 71.17 | 1780.57 | 09-JAN-06:00 | 2559.58 | 11-FEB-14:10 |
EnergyTransfer:Zone:BASEMENT | 405.87 | 10536.90 | 26-JUN-13:20 | 19372.71 | 08-JAN-07:00 |
Heating:EnergyTransfer | 10.60 | 0.00 | 01-JAN-08:10 | 21101.81 | 29-MAR-08:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 10.60 | 0.00 | 01-JAN-08:10 | 21101.81 | 29-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 5100.69 | 101455.84 | 29-MAR-04:00 | 301167.16 | 16-OCT-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 405.87 | 10536.90 | 26-JUN-13:20 | 19372.71 | 08-JAN-07:00 |
General:Cooling:EnergyTransfer | 5100.69 | 101455.84 | 29-MAR-04:00 | 301167.16 | 16-OCT-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 405.87 | 10536.90 | 26-JUN-13:20 | 19372.71 | 08-JAN-07:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 45.98 | 6.45 | 30-MAR-05:10 | 4164.01 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 70.67 | 30-MAR-06:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 70.67 | 30-MAR-06:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 45.98 | 0.00 | 30-MAR-03:00 | 4164.01 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 45.98 | 0.00 | 30-MAR-03:00 | 4164.01 | 16-OCT-12:10 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 38.81 | 834.98 | 29-MAR-12:10 | 2100.96 | 16-OCT-20:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 38.81 | 834.98 | 29-MAR-12:10 | 2100.96 | 16-OCT-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 38.81 | 834.98 | 29-MAR-12:10 | 2100.96 | 16-OCT-20:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 33.80 | 531.19 | 30-MAR-04:00 | 1541.51 | 30-SEP-10:40 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 33.80 | 531.19 | 30-MAR-04:00 | 1541.51 | 30-SEP-10:40 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 33.80 | 531.19 | 30-MAR-04:00 | 1541.51 | 30-SEP-10:40 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 15.68 | 176.32 | 29-MAR-12:00 | 733.64 | 30-SEP-10:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 15.68 | 176.32 | 29-MAR-12:00 | 733.64 | 30-SEP-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 15.68 | 176.32 | 29-MAR-12:00 | 733.64 | 30-SEP-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 606.19 | 9957.15 | 30-MAR-04:00 | 38524.41 | 29-SEP-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 606.19 | 9957.15 | 30-MAR-04:00 | 38524.41 | 29-SEP-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 606.19 | 9957.15 | 30-MAR-04:00 | 38524.41 | 29-SEP-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 235.67 | 2421.47 | 29-MAR-12:10 | 14301.89 | 19-NOV-11:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 235.67 | 2421.47 | 29-MAR-12:10 | 14301.89 | 19-NOV-11:00 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 235.67 | 2421.47 | 29-MAR-12:10 | 14301.89 | 19-NOV-11:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 789.75 | 16852.65 | 29-MAR-11:00 | 40238.61 | 16-OCT-20:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 789.75 | 16852.65 | 29-MAR-11:00 | 40238.61 | 16-OCT-20:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 789.75 | 16852.65 | 29-MAR-11:00 | 40238.61 | 16-OCT-20:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 52.97 | 0.03 | 04-NOV-03:00 | 11064.59 | 15-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 1.04 | 0.00 | 01-JAN-08:10 | 2909.71 | 29-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 1.04 | 0.00 | 01-JAN-08:10 | 2909.71 | 29-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 51.93 | 0.00 | 01-JAN-00:10 | 11064.59 | 15-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 51.93 | 0.00 | 01-JAN-00:10 | 11064.59 | 15-OCT-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 43.16 | 0.02 | 20-APR-03:30 | 9571.88 | 16-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 2.13 | 0.00 | 01-JAN-08:10 | 2884.52 | 29-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 2.13 | 0.00 | 01-JAN-08:10 | 2884.52 | 29-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 41.03 | 0.00 | 01-JAN-00:10 | 9571.88 | 16-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 41.03 | 0.00 | 01-JAN-00:10 | 9571.88 | 16-OCT-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 398.23 | 4360.32 | 30-MAR-08:10 | 56113.10 | 16-OCT-12:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 398.23 | 4360.32 | 30-MAR-08:10 | 56113.10 | 16-OCT-12:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 398.23 | 4360.32 | 30-MAR-08:10 | 56113.10 | 16-OCT-12:20 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 379.78 | 1.43 | 29-MAR-02:50 | 51342.14 | 30-SEP-15:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.82 | 0.00 | 01-JAN-00:10 | 11641.81 | 03-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.82 | 0.00 | 01-JAN-00:10 | 11641.81 | 03-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 378.96 | 0.00 | 03-JAN-01:30 | 51342.14 | 30-SEP-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 378.96 | 0.00 | 03-JAN-01:30 | 51342.14 | 30-SEP-15:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 49.40 | 0.16 | 13-NOV-00:30 | 9161.29 | 15-OCT-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 1.16 | 0.00 | 01-JAN-07:20 | 2579.32 | 29-MAR-18:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 1.16 | 0.00 | 01-JAN-07:20 | 2579.32 | 29-MAR-18:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 48.24 | 0.00 | 01-JAN-00:10 | 9161.29 | 15-OCT-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 48.24 | 0.00 | 01-JAN-00:10 | 9161.29 | 15-OCT-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 40.03 | 0.05 | 07-DEC-05:30 | 8139.22 | 15-OCT-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 2.34 | 0.00 | 01-JAN-07:30 | 2896.64 | 29-MAR-18:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 2.34 | 0.00 | 01-JAN-07:30 | 2896.64 | 29-MAR-18:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 37.69 | 0.00 | 01-JAN-00:10 | 8139.22 | 15-OCT-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 37.69 | 0.00 | 01-JAN-00:10 | 8139.22 | 15-OCT-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 204.72 | 3560.81 | 30-MAR-06:10 | 9449.80 | 17-OCT-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 204.72 | 3560.81 | 30-MAR-06:10 | 9449.80 | 17-OCT-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 204.72 | 3560.81 | 30-MAR-06:10 | 9449.80 | 17-OCT-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 12.53 | 0.00 | 09-MAY-09:00 | 2880.38 | 15-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.85 | 0.00 | 01-JAN-08:10 | 916.75 | 29-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.85 | 0.00 | 01-JAN-08:10 | 916.75 | 29-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 11.67 | 0.00 | 01-JAN-00:10 | 2880.38 | 15-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 11.67 | 0.00 | 01-JAN-00:10 | 2880.38 | 15-OCT-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 10.62 | 0.01 | 12-MAY-21:10 | 2534.91 | 16-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 1.54 | 0.00 | 01-JAN-08:10 | 951.72 | 30-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 1.54 | 0.00 | 01-JAN-08:10 | 951.72 | 30-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.08 | 0.00 | 01-JAN-00:10 | 2534.91 | 16-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.08 | 0.00 | 01-JAN-00:10 | 2534.91 | 16-OCT-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 84.35 | 1.02 | 03-NOV-03:40 | 14049.17 | 16-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.71 | 0.00 | 01-JAN-07:20 | 3418.66 | 29-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.71 | 0.00 | 01-JAN-07:20 | 3418.66 | 29-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 83.64 | 0.00 | 01-JAN-00:10 | 14049.17 | 16-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 83.64 | 0.00 | 01-JAN-00:10 | 14049.17 | 16-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 444.36 | 9517.50 | 29-MAR-11:00 | 21633.43 | 29-SEP-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 444.36 | 9517.50 | 29-MAR-11:00 | 21633.43 | 29-SEP-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 444.36 | 9517.50 | 29-MAR-11:00 | 21633.43 | 29-SEP-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 483.18 | 10552.65 | 29-MAR-11:00 | 22927.48 | 29-SEP-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 483.18 | 10552.65 | 29-MAR-11:00 | 22927.48 | 29-SEP-21:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 483.18 | 10552.65 | 29-MAR-11:00 | 22927.48 | 29-SEP-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 633.54 | 9617.59 | 29-MAR-03:00 | 30317.49 | 30-SEP-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 633.54 | 9617.59 | 29-MAR-03:00 | 30317.49 | 30-SEP-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 102.67 | 697.95 | 30-MAR-06:10 | 5724.55 | 30-SEP-13:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 102.67 | 697.95 | 30-MAR-06:10 | 5724.55 | 30-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 102.67 | 697.95 | 30-MAR-06:10 | 5724.55 | 30-SEP-13:40 |
PlantLoopHeatingDemand:Facility | 1310.05 | 8692.74 | 03-AUG-00:20 | 210427.66 | 03-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 681.94 | 8692.74 | 03-AUG-00:20 | 47494.11 | 30-JAN-07:10 |
WaterSystems:PlantLoopHeatingDemand | 681.94 | 8692.74 | 03-AUG-00:20 | 47494.11 | 30-JAN-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 681.94 | 8692.74 | 03-AUG-00:20 | 47494.11 | 30-JAN-07:10 |
EnergyTransfer:HVAC | 3429.85 | 128.54 | 06-MAY-07:20 | 506387.41 | 18-AUG-15:10 |
HeatingCoils:EnergyTransfer | 628.11 | 0.00 | 02-JAN-11:10 | 183348.18 | 08-JAN-07:00 |
PlantLoopHeatingDemand:HVAC | 628.11 | 0.00 | 02-JAN-11:10 | 183348.18 | 08-JAN-07:00 |
HeatingCoils:PlantLoopHeatingDemand | 628.11 | 0.00 | 02-JAN-11:10 | 183348.18 | 08-JAN-07:00 |
CoolingCoils:EnergyTransfer | 2801.74 | 0.00 | 01-JAN-00:10 | 506162.69 | 16-OCT-10:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 681.94 | 8692.74 | 03-AUG-00:20 | 47494.11 | 30-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 681.94 | 8692.74 | 03-AUG-00:20 | 47494.11 | 30-JAN-07:10 |
Boilers:EnergyTransfer | 622.81 | 0.00 | 02-JAN-11:10 | 181927.27 | 08-JAN-07:00 |
Chillers:EnergyTransfer | 2940.74 | 0.00 | 01-JAN-00:10 | 514811.04 | 18-AUG-15:10 |
HeatRejection:EnergyTransfer | 3819.06 | 0.00 | 01-JAN-00:10 | 691618.65 | 16-OCT-10:50 |
General:HeatRejection:EnergyTransfer | 3819.06 | 0.00 | 01-JAN-00:10 | 691618.65 | 16-OCT-10:50 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -405.872 | 0.000 | 0.000 | 141.074 | 173.462 | 150.255 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -58.919 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.000 | -45.983 | 0.000 | 0.000 | 15.437 | 8.614 | 10.186 | 21.086 | 0.000 | 0.046 | 1.501 | 0.000 | -8.556 | 0.000 | -2.331 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -38.814 | 0.000 | 0.000 | 16.686 | 9.975 | 11.795 | 0.000 | 0.000 | 0.020 | 1.370 | 0.000 | 0.000 | 0.000 | -1.031 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -33.796 | 0.000 | 0.000 | 3.671 | 16.635 | 12.471 | 0.000 | 0.000 | 0.053 | 3.209 | 0.000 | 0.000 | 0.000 | -2.244 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -15.675 | 0.000 | 0.000 | 2.855 | 2.785 | 3.598 | 0.000 | 0.000 | 0.031 | 7.669 | 0.000 | 0.000 | 0.000 | -1.262 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -606.191 | 0.000 | 0.000 | 11.355 | 4.368 | 658.131 | 0.000 | 0.000 | 0.081 | 0.000 | 0.000 | 0.000 | 0.000 | -3.298 | -64.447 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -235.669 | 0.000 | 0.000 | 187.402 | 18.099 | 14.341 | 58.046 | 0.000 | 0.097 | 0.000 | 0.000 | -26.890 | 0.000 | -6.030 | -9.395 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -789.750 | 0.000 | 0.000 | 546.113 | 122.034 | 148.998 | 76.930 | 0.000 | 0.284 | 0.000 | 0.000 | -36.271 | 0.000 | -17.823 | -50.516 |
ROOM_1_FLR_3 | 2.635 | -37.171 | 0.000 | -16.357 | 0.000 | 0.000 | 9.676 | 6.366 | 12.292 | 43.889 | 0.000 | 0.184 | 3.555 | 0.000 | -18.427 | 0.000 | -6.643 | -0.000 |
ROOM_2_FLR_3 | 4.609 | -27.433 | 0.000 | -16.078 | 0.000 | 0.000 | 9.704 | 6.366 | 12.291 | 31.935 | 0.000 | 0.198 | 3.390 | 0.000 | -18.468 | 0.000 | -6.515 | -0.001 |
ROOM_3_MULT19_FLR_3 | 0.017 | -135.438 | 0.000 | -262.817 | 0.000 | 0.000 | 0.000 | 76.021 | 228.754 | 250.557 | 0.000 | 0.505 | 35.113 | 0.000 | -113.765 | 0.000 | -78.947 | -0.008 |
ROOM_4_MULT19_FLR_3 | 11.242 | -177.366 | 0.000 | -212.003 | 0.000 | 0.000 | 185.270 | 76.042 | 228.817 | 71.283 | 0.000 | 1.898 | 0.001 | 0.000 | -97.296 | 0.000 | -53.373 | -34.512 |
ROOM_5_FLR_3 | 2.884 | -33.507 | 0.000 | -16.451 | 0.000 | 0.000 | 9.668 | 6.366 | 12.292 | 40.722 | 0.000 | 0.180 | 2.497 | 0.000 | -17.970 | 0.000 | -6.681 | -0.001 |
ROOM_6_FLR_3 | 4.916 | -24.136 | 0.000 | -16.133 | 0.000 | 0.000 | 9.701 | 6.366 | 12.291 | 28.469 | 0.000 | 0.189 | 2.536 | 0.000 | -17.666 | 0.000 | -6.533 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.000 | -204.720 | 0.000 | 0.000 | 115.508 | 109.603 | 0.000 | 35.992 | 0.000 | 0.142 | 0.000 | 0.000 | -24.870 | 0.000 | -7.042 | -24.613 |
ROOM_1_FLR_6 | 1.553 | -8.296 | 0.000 | -4.074 | 0.000 | 0.000 | 2.421 | 1.592 | 3.073 | 10.863 | 0.000 | 0.046 | 0.000 | 0.000 | -4.527 | 0.000 | -1.709 | -0.942 |
ROOM_2_FLR_6 | 2.506 | -6.051 | 0.000 | -3.998 | 0.000 | 0.000 | 2.429 | 1.591 | 3.073 | 7.913 | 0.000 | 0.049 | 0.000 | 0.000 | -4.515 | 0.000 | -1.673 | -1.325 |
ROOM_3_MULT9_FLR_6 | 2.386 | -58.916 | 0.000 | -26.399 | 0.000 | 0.000 | 21.758 | 9.005 | 27.097 | 54.956 | 0.000 | 0.257 | 0.879 | 0.000 | -21.237 | 0.000 | -9.786 | -0.002 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -444.356 | 0.000 | 0.000 | 315.907 | 34.836 | 175.857 | 5.942 | 0.000 | 0.046 | 0.000 | 0.000 | -14.928 | 0.000 | -4.268 | -69.035 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -483.178 | 0.000 | 0.000 | 314.965 | 34.836 | 175.857 | 5.629 | 0.000 | 0.043 | 0.000 | 0.000 | -15.395 | 0.000 | -4.312 | -28.444 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -633.526 | 0.000 | 0.000 | 28.382 | 13.327 | 550.372 | 18.137 | 0.000 | 0.036 | 38.046 | 0.000 | -10.944 | 0.000 | -3.831 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.000 | -102.671 | 0.000 | 0.000 | 30.934 | 28.999 | 0.000 | 17.530 | 0.000 | 0.050 | 39.304 | 0.000 | -11.078 | 0.000 | -3.069 | 0.000 |
Total Facility | 32.748 | -508.313 | 0.000 | -4614.513 | 0.000 | 0.000 | 1980.917 | 767.286 | 2451.839 | 779.879 | 0.000 | 4.437 | 139.072 | 0.000 | -462.803 | 0.000 | -228.402 | -342.159 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | -19369.67 | 0.00 | 0.00 | 5541.63 | 4728.51 | 4258.44 | 0.00 | 0.00 | 0.00 | 4841.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 16-OCT-12:10 | 0.00 | 0.00 | 0.00 | -4164.04 | 0.00 | 0.00 | 150.60 | 195.67 | 252.59 | 4777.64 | 0.00 | 129.44 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1341.91 |
RETAIL_2_FLR_1 | 16-OCT-20:10 | 0.00 | 0.00 | 0.00 | -2100.49 | 0.00 | 0.00 | 697.63 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -15.74 | -58.63 |
MECH_FLR_1 | 30-SEP-10:33 | 0.00 | 0.00 | 0.00 | -1547.47 | 0.00 | 0.00 | 58.37 | 377.89 | 309.27 | 0.00 | 0.00 | 76.11 | 725.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 30-SEP-10:33 | 0.00 | 0.00 | 0.00 | -735.67 | 0.00 | 0.00 | 44.93 | 63.26 | 89.22 | 0.00 | 0.00 | 43.95 | 494.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 29-SEP-20:00 | 0.00 | 0.00 | 0.00 | -38524.31 | 0.00 | 0.00 | 408.79 | 357.21 | 44299.38 | 0.00 | 0.00 | 14.19 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6555.26 |
CAFE_FLR_1 | 19-NOV-11:00 | 0.00 | 0.00 | 0.00 | -14307.30 | 0.00 | 0.00 | 4947.82 | 358.25 | 406.43 | 13694.30 | 0.00 | 50.65 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5150.16 |
LOBBY_FLR_1 | 16-OCT-20:10 | 0.00 | 0.00 | 0.00 | -40228.96 | 0.00 | 0.00 | 23502.81 | 9124.61 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1253.07 | 0.00 | -257.49 | -389.25 |
ROOM_1_FLR_3 | 15-OCT-15:02 | 0.00 | -11134.84 | 0.00 | -746.59 | 0.00 | 0.00 | 130.71 | 161.71 | 305.54 | 8668.99 | 0.00 | 206.79 | 2407.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 16-OCT-15:02 | 0.00 | -10581.04 | 0.00 | -739.66 | 0.00 | 0.00 | 235.27 | 137.19 | 273.90 | 6664.13 | 0.00 | 183.58 | 3826.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 16-OCT-12:20 | 0.00 | -45552.46 | 0.00 | -10564.12 | 0.00 | 0.00 | 0.00 | 1638.34 | 5097.90 | 57568.56 | 0.00 | 1636.72 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9824.94 |
ROOM_4_MULT19_FLR_3 | 14-OCT-15:02 | 0.00 | -60270.92 | 0.00 | -9665.37 | 0.00 | 0.00 | 2553.35 | 1931.47 | 5687.67 | 10200.39 | 0.00 | 1425.81 | 48137.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 15-OCT-08:62 | 0.00 | -9715.10 | 0.00 | -742.87 | 0.00 | 0.00 | 130.71 | 274.41 | 653.23 | 8606.94 | 0.00 | 178.26 | 614.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 15-OCT-08:62 | 0.00 | -9273.64 | 0.00 | -739.15 | 0.00 | 0.00 | 130.72 | 274.38 | 653.15 | 6985.86 | 0.00 | 179.56 | 1789.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 17-OCT-10:33 | 0.00 | 0.00 | 0.00 | -9469.50 | 0.00 | 0.00 | 1200.12 | 2489.76 | 0.00 | 7563.87 | 0.00 | 234.46 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2018.70 |
ROOM_1_FLR_6 | 15-OCT-15:02 | 0.00 | -2888.73 | 0.00 | -187.10 | 0.00 | 0.00 | 32.68 | 40.43 | 76.39 | 2147.85 | 0.00 | 51.16 | 727.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 16-OCT-15:02 | 0.00 | -2734.49 | 0.00 | -185.19 | 0.00 | 0.00 | 58.82 | 34.30 | 68.48 | 1652.35 | 0.00 | 45.42 | 1060.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 16-OCT-15:02 | 0.00 | -13604.54 | 0.00 | -1212.82 | 0.00 | 0.00 | 529.39 | 194.07 | 603.86 | 5974.72 | 0.00 | 203.43 | 7311.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 29-SEP-21:10 | 0.00 | 0.00 | 0.00 | -21633.84 | 0.00 | 0.00 | 15644.25 | 2062.70 | 6747.90 | 0.00 | 0.00 | 7.86 | 0.00 | 0.00 | -230.35 | 0.00 | 0.00 | -2598.52 |
DINING_FLR_6 | 29-SEP-21:10 | 0.00 | 0.00 | 0.00 | -22928.04 | 0.00 | 0.00 | 15644.15 | 2062.70 | 6747.90 | 0.00 | 0.00 | 7.86 | 0.00 | 0.00 | -246.11 | 0.00 | 0.00 | -1288.45 |
KITCHEN_FLR_6 | 30-SEP-10:50 | 0.00 | 0.00 | 0.00 | -30334.89 | 0.00 | 0.00 | 461.31 | 302.73 | 24259.91 | 2341.07 | 0.00 | 93.86 | 2876.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 30-SEP-13:40 | 0.00 | 0.00 | 0.00 | -5725.16 | 0.00 | 0.00 | 462.68 | 658.76 | 0.00 | 2850.50 | 0.00 | 109.46 | 1643.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-OCT-15:02 | 0.00 | -156410.77 | 0.00 | -176318.88 | 0.00 | 0.00 | 53015.90 | 16768.37 | 77329.74 | 89078.23 | 0.00 | 4354.87 | 92182.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 30-MAR-06:05 | 0.00 | 0.00 | 73.69 | 0.00 | 0.00 | 0.00 | 358.03 | 391.34 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -726.18 | 0.00 | -189.72 | -340.18 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 30-MAR-08:62 | 6319.98 | 354.31 | 0.00 | -354.31 | 0.00 | 0.00 | 105.31 | 215.61 | 453.05 | 323.07 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -305.16 | -7111.87 |
ROOM_2_FLR_3 | 30-MAR-08:62 | 6322.82 | 337.41 | 0.00 | -337.41 | 0.00 | 0.00 | 106.31 | 215.58 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -313.97 | 0.00 | -298.73 | -6485.00 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 30-MAR-08:62 | 34034.09 | 5519.34 | 0.00 | -5519.34 | 0.00 | 0.00 | 1911.57 | 2575.24 | 8433.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2325.75 | 0.00 | -1725.14 | -42903.44 |
ROOM_5_FLR_3 | 28-MAR-08:62 | 6143.31 | 374.65 | 0.00 | -374.65 | 0.00 | 0.00 | 104.08 | 215.61 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1178.41 | 0.00 | -314.33 | -5423.31 |
ROOM_6_FLR_3 | 28-MAR-08:62 | 6106.09 | 371.09 | 0.00 | -371.09 | 0.00 | 0.00 | 104.28 | 215.58 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1173.60 | 0.00 | -312.99 | -5392.36 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 30-MAR-08:62 | 1904.50 | 80.65 | 0.00 | -80.65 | 0.00 | 0.00 | 26.93 | 53.90 | 113.26 | 89.71 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -73.70 | -2114.61 |
ROOM_2_FLR_6 | 30-MAR-08:62 | 1901.54 | 76.61 | 0.00 | -76.61 | 0.00 | 0.00 | 27.16 | 53.90 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -66.45 | 0.00 | -72.16 | -1957.24 |
ROOM_3_MULT9_FLR_6 | 28-MAR-08:62 | 8910.59 | 615.86 | 0.00 | -615.86 | 0.00 | 0.00 | 233.10 | 304.96 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1372.05 | 0.00 | -367.72 | -8707.59 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-MAR-08:62 | -40376.12 | 119987.92 | 0.00 | -119987.92 | 0.00 | 0.00 | 22875.05 | 26712.50 | 88432.23 | 252.83 | 0.00 | 0.00 | 0.00 | 0.00 | -8125.92 | 0.00 | -9331.94 | -80438.63 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 21.2308 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 21.1122 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6557 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6557 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.003540 | 142.3000 | 0.000914 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.003540 | 422.4350 | 0.000305 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.000747 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4616 | 2.4616 | 1.3514 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3255 | 0.3255 | 0.1787 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2393 | 0.2393 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2269 | 0.2269 | 0.1245 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1079 | 0.1079 | 0.0592 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3113 | 3.3113 | 1.8179 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3953 | 1.3953 | 0.7660 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.5297 | 4.5297 | 2.4868 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3510 | 1.3510 | 0.7417 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1302 | 2.1302 | 1.1695 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2345 | 2.2345 | 1.2267 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2252 | 2.2252 | 1.2217 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6926 | 0.6926 | 0.3802 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 21.2308 | 21.1122 | 21.2308 | 11.6557 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3514 | 1.3514 | 1.3514 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1787 | 0.1787 | 0.1787 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1314 | 0.1314 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1245 | 0.1245 | 0.1245 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0592 | 0.0592 | 0.0592 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8179 | 1.8179 | 1.8179 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7660 | 0.7660 | 0.7660 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4868 | 2.4868 | 2.4868 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7417 | 0.7417 | 0.7417 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1695 | 1.1695 | 1.1695 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2267 | 1.2267 | 1.2267 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2217 | 1.2217 | 1.2217 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3802 | 0.3802 | 0.3802 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6557 | 11.6557 | 11.6557 | 11.6557 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 22.50 |
Number of hours not met | 22.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 914.35 | 230195.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 878.32 | 180333.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 767.29 | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 242.88 | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.56 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 32.45 | 1868.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 561.22 | 37012.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 160.57 | 7962.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4738.61 | 2934.36 | 246240.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.48 | 1892.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.76 | 1203.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1807.35 | 5159.85 |
Natural Gas | 1788.84 | 5637.55 |
Additional | 0.00 | 0.00 |
Total | 3596.19 | 10797.40 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 67.63 |
Space Heating | 0.00 |
Space Cooling | 77.42 |
Fans (All) | 49.47 |
Service Water Heating | 8.00 |
Receptacle Equipment | 153.81 |
Miscellaneous (All) | 454.80 |
Subtotal | 454.80 |
Natural Gas [MJ/m2] | |
Space Heating | 80.59 |
Service Water Heating | 258.64 |
Miscellaneous (All) | 496.91 |
Subtotal | 496.91 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.11 |
Space Heating | 8.47 |
Space Cooling | 8.13 |
Fans (All) | 5.20 |
Service Water Heating | 28.02 |
Receptacle Equipment | 32.73 |
Miscellaneous | 10.35 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2667. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 2678. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 3061. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 192720.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 7927.50 | 832.50 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 7942.17 | 817.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 7885.50 | 874.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 7993.17 | 766.83 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8731.50 | 28.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7885.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 874.50 | 0.00 | 0.00 | 0.00 |
Average | 8609.08 | 150.92 | 0.00 | 0.00 | 0.00 |
Sum | 189399.83 | 3320.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 607562.67 | 102854.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1823036.67 | 292392.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1063847.83 | 181867.17 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1084840.17 | 160874.83 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 107978.00 | 291.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1823036.67 | 292392.33 | 0.00 | 0.00 | 0.00 |
Average | 255328.88 | 33558.17 | 0.00 | 0.00 | 0.00 |
Sum | 5617235.33 | 738279.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:53
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.361373E+11 | 19372.71 | 08-JAN-07:00 | 1.00 | -0.3 | 0.791297E+10 | 4836.99 | 20-JAN-23:10 | 13.83 | 13.83 |
February | 0.299458E+11 | 15563.58 | 01-FEB-11:33 | 25.00 | 14.29 | 0.680842E+10 | 4836.86 | 01-FEB-22:19 | 13.00 | 11.68 |
March | 0.324790E+11 | 14986.93 | 12-MAR-10:33 | 21.33 | 14.69 | 0.740488E+10 | 4617.35 | 01-MAR-22:10 | 21.33 | 14.69 |
April | 0.313754E+11 | 15146.86 | 30-APR-10:33 | 25.67 | 16.97 | 0.707536E+10 | 4562.77 | 14-APR-21:10 | 25.67 | 16.97 |
May | 0.323688E+11 | 14866.17 | 28-MAY-10:33 | 21.00 | 15.43 | 0.731554E+10 | 4578.03 | 12-MAY-21:10 | 21.00 | 15.43 |
June | 0.312182E+11 | 14996.96 | 25-JUN-10:33 | 23.00 | 17.26 | 0.701417E+10 | 4519.12 | 09-JUN-21:10 | 23.00 | 17.26 |
July | 0.341351E+11 | 15921.42 | 23-JUL-10:33 | 25.67 | 20.39 | 0.746137E+10 | 4677.01 | 14-JUL-21:19 | 25.67 | 20.39 |
August | 0.346136E+11 | 15903.34 | 06-AUG-10:33 | 24.33 | 20.00 | 0.757192E+10 | 4702.98 | 25-AUG-21:19 | 16.07 | 16.07 |
September | 0.345720E+11 | 16508.01 | 30-SEP-10:33 | 30.57 | 17.23 | 0.755083E+10 | 4837.02 | 13-SEP-21:19 | 30.57 | 17.23 |
October | 0.370909E+11 | 18191.50 | 20-OCT-21:00 | 16.00 | 13.03 | 0.796565E+10 | 4837.03 | 04-OCT-21:19 | 16.00 | 13.03 |
November | 0.358679E+11 | 18811.19 | 30-NOV-22:00 | 11.60 | 5.78 | 0.775786E+10 | 4837.00 | 09-NOV-22:40 | 11.60 | 5.78 |
December | 0.360680E+11 | 18396.42 | 01-DEC-22:00 | 11.00 | 10.48 | 0.794842E+10 | 4836.98 | 21-DEC-22:10 | 10.67 | 10.67 |
Annual Sum or Average | 0.405872E+12 | 0.897874E+11 | ||||||||
Minimum of Months | 0.299458E+11 | 14866.17 | 1.00 | -0.3 | 0.680842E+10 | 4519.12 | 10.67 | 5.78 | ||
Maximum of Months | 0.370909E+11 | 19372.71 | 30.57 | 20.39 | 0.796565E+10 | 4837.03 | 30.57 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.383354E+10 | 3305.32 | 14-JAN-12:40 | 25.33 | 11.70 | 0.672437E+09 | 439.08 | 18-JAN-22:30 | 16.50 | 13.26 |
February | 0.314116E+10 | 2875.02 | 02-FEB-12:40 | 19.33 | 12.36 | 0.598552E+09 | 437.55 | 01-FEB-22:30 | 19.33 | 12.36 |
March | 0.313514E+10 | 2588.16 | 11-MAR-13:00 | 24.00 | 13.82 | 0.652349E+09 | 436.22 | 23-MAR-21:30 | 13.50 | 12.93 |
April | 0.354868E+10 | 2063.21 | 08-APR-10:33 | 21.67 | 16.37 | 0.644362E+09 | 437.43 | 26-APR-21:40 | 16.00 | 15.39 |
May | 0.342433E+10 | 2012.07 | 04-MAY-10:33 | 22.00 | 15.73 | 0.648857E+09 | 439.36 | 04-MAY-21:30 | 17.00 | 15.07 |
June | 0.363236E+10 | 1932.52 | 25-JUN-10:33 | 23.00 | 17.26 | 0.646782E+09 | 436.03 | 28-JUN-21:30 | 17.00 | 16.37 |
July | 0.409890E+10 | 2118.98 | 30-JUL-10:33 | 24.67 | 20.10 | 0.696029E+09 | 452.21 | 31-JUL-21:30 | 18.85 | 17.85 |
August | 0.430847E+10 | 2198.77 | 27-AUG-10:33 | 23.33 | 18.72 | 0.720626E+09 | 459.73 | 18-AUG-21:30 | 23.33 | 18.72 |
September | 0.418376E+10 | 3544.59 | 30-SEP-13:10 | 32.00 | 16.98 | 0.692827E+09 | 491.81 | 29-SEP-21:30 | 32.00 | 16.98 |
October | 0.463570E+10 | 4164.01 | 16-OCT-12:10 | 35.68 | 17.48 | 0.723053E+09 | 491.79 | 16-OCT-21:30 | 19.00 | 11.09 |
November | 0.396438E+10 | 3645.57 | 19-NOV-12:30 | 26.50 | 15.22 | 0.660820E+09 | 442.09 | 27-NOV-22:30 | 16.00 | 5.61 |
December | 0.407634E+10 | 3480.70 | 19-DEC-12:50 | 25.83 | 11.54 | 0.680372E+09 | 456.06 | 05-DEC-22:30 | 25.83 | 11.54 |
Annual Sum or Average | 0.459828E+11 | 0.803707E+10 | ||||||||
Minimum of Months | 0.313514E+10 | 1932.52 | 19.33 | 11.54 | 0.598552E+09 | 436.03 | 13.50 | 5.61 | ||
Maximum of Months | 0.463570E+10 | 4164.01 | 35.68 | 20.10 | 0.723053E+09 | 491.81 | 32.00 | 18.72 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.313912E+10 | 1616.30 | 08-JAN-07:00 | 1.00 | -0.3 | 0.865257E+09 | 569.52 | 20-JAN-23:10 | 13.83 | 13.83 |
February | 0.279252E+10 | 1496.17 | 03-FEB-21:20 | 11.67 | 6.29 | 0.781662E+09 | 569.52 | 02-FEB-23:10 | 11.67 | 6.29 |
March | 0.305160E+10 | 1500.32 | 24-MAR-21:00 | 13.00 | 11.87 | 0.856484E+09 | 569.51 | 23-MAR-21:19 | 13.00 | 11.87 |
April | 0.313204E+10 | 1614.91 | 27-APR-21:00 | 14.00 | 12.84 | 0.854785E+09 | 569.53 | 26-APR-21:19 | 14.00 | 12.84 |
May | 0.320426E+10 | 1625.61 | 03-MAY-21:00 | 16.00 | 14.77 | 0.879485E+09 | 569.52 | 24-MAY-21:19 | 16.00 | 14.13 |
June | 0.323827E+10 | 1679.69 | 30-JUN-21:00 | 16.00 | 14.76 | 0.871421E+09 | 569.53 | 29-JUN-21:19 | 16.00 | 14.76 |
July | 0.351624E+10 | 1788.09 | 31-JUL-21:00 | 19.00 | 17.66 | 0.917514E+09 | 569.53 | 26-JUL-21:19 | 19.00 | 17.66 |
August | 0.357887E+10 | 1849.01 | 18-AUG-21:00 | 19.00 | 17.66 | 0.928851E+09 | 569.53 | 16-AUG-21:19 | 19.00 | 17.66 |
September | 0.337510E+10 | 2050.44 | 29-SEP-21:00 | 24.60 | 13.50 | 0.888565E+09 | 569.54 | 30-SEP-01:19 | 24.20 | 13.95 |
October | 0.349083E+10 | 2100.96 | 16-OCT-20:10 | 20.50 | 12.73 | 0.917576E+09 | 569.54 | 15-OCT-23:19 | 20.50 | 12.73 |
November | 0.311988E+10 | 1552.13 | 19-NOV-11:33 | 26.00 | 15.32 | 0.857958E+09 | 569.53 | 27-NOV-22:30 | 16.00 | 5.61 |
December | 0.317565E+10 | 1576.89 | 05-DEC-22:00 | 17.00 | 9.46 | 0.878251E+09 | 569.51 | 19-DEC-22:10 | 8.33 | 1.76 |
Annual Sum or Average | 0.388144E+11 | 0.104978E+11 | ||||||||
Minimum of Months | 0.279252E+10 | 1496.17 | 1.00 | -0.3 | 0.781662E+09 | 569.51 | 8.33 | 1.76 | ||
Maximum of Months | 0.357887E+10 | 2100.96 | 26.00 | 17.66 | 0.928851E+09 | 569.54 | 24.20 | 17.66 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262049E+10 | 1316.97 | 20-JAN-11:33 | 21.67 | 15.71 | 0.166810E+09 | 111.11 | 18-JAN-22:10 | 21.67 | 15.71 |
February | 0.236589E+10 | 1266.30 | 02-FEB-11:33 | 19.33 | 10.71 | 0.151538E+09 | 109.00 | 03-FEB-22:10 | 9.50 | 4.24 |
March | 0.257022E+10 | 1292.86 | 19-MAR-10:33 | 19.33 | 15.06 | 0.166116E+09 | 108.92 | 24-MAR-21:10 | 13.00 | 11.77 |
April | 0.269371E+10 | 1374.14 | 30-APR-10:33 | 25.67 | 16.97 | 0.166942E+09 | 112.09 | 27-APR-21:10 | 25.67 | 16.97 |
May | 0.285203E+10 | 1394.17 | 04-MAY-10:33 | 22.00 | 15.73 | 0.175858E+09 | 114.60 | 04-MAY-21:19 | 17.00 | 15.07 |
June | 0.294431E+10 | 1452.33 | 25-JUN-10:33 | 23.00 | 17.26 | 0.177162E+09 | 117.20 | 30-JUN-21:19 | 16.03 | 15.21 |
July | 0.319519E+10 | 1514.78 | 23-JUL-10:33 | 25.67 | 20.39 | 0.187461E+09 | 118.80 | 19-JUL-21:19 | 25.67 | 20.39 |
August | 0.318702E+10 | 1501.24 | 19-AUG-10:33 | 24.67 | 20.11 | 0.187798E+09 | 118.70 | 18-AUG-21:19 | 24.67 | 20.11 |
September | 0.295911E+10 | 1547.43 | 30-SEP-10:33 | 30.57 | 17.23 | 0.177288E+09 | 119.59 | 29-SEP-21:10 | 30.57 | 17.23 |
October | 0.308196E+10 | 1538.23 | 16-OCT-10:33 | 36.33 | 17.49 | 0.184623E+09 | 120.45 | 17-OCT-21:10 | 18.00 | 14.87 |
November | 0.265759E+10 | 1351.63 | 19-NOV-11:33 | 26.00 | 15.32 | 0.166856E+09 | 110.75 | 01-NOV-21:10 | 26.00 | 15.32 |
December | 0.266817E+10 | 1315.58 | 19-DEC-11:33 | 25.00 | 11.16 | 0.169489E+09 | 110.92 | 05-DEC-22:19 | 25.00 | 11.16 |
Annual Sum or Average | 0.337957E+11 | 0.207794E+10 | ||||||||
Minimum of Months | 0.236589E+10 | 1266.30 | 19.33 | 10.71 | 0.151538E+09 | 108.92 | 9.50 | 4.24 | ||
Maximum of Months | 0.319519E+10 | 1547.43 | 36.33 | 20.39 | 0.187798E+09 | 120.45 | 30.57 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120914E+10 | 623.22 | 20-JAN-11:33 | 21.67 | 15.71 | 0.125969E+09 | 81.72 | 18-JAN-22:49 | 21.67 | 15.71 |
February | 0.109451E+10 | 598.69 | 02-FEB-11:33 | 19.33 | 10.71 | 0.114249E+09 | 80.14 | 03-FEB-23:10 | 11.67 | 3.87 |
March | 0.117784E+10 | 610.36 | 23-MAR-10:33 | 22.00 | 16.70 | 0.125146E+09 | 80.03 | 24-MAR-22:10 | 13.00 | 11.29 |
April | 0.124971E+10 | 650.04 | 30-APR-10:33 | 25.67 | 16.97 | 0.125877E+09 | 82.30 | 27-APR-22:10 | 25.67 | 16.97 |
May | 0.132063E+10 | 658.80 | 04-MAY-10:33 | 22.00 | 15.73 | 0.132366E+09 | 84.32 | 04-MAY-22:10 | 16.83 | 15.02 |
June | 0.136621E+10 | 684.55 | 25-JUN-10:33 | 23.00 | 17.26 | 0.133452E+09 | 85.95 | 30-JUN-22:10 | 16.13 | 16.03 |
July | 0.148612E+10 | 715.58 | 23-JUL-10:33 | 25.67 | 20.39 | 0.141362E+09 | 87.35 | 19-JUL-22:10 | 25.67 | 20.39 |
August | 0.148365E+10 | 709.72 | 19-AUG-10:33 | 24.67 | 20.11 | 0.141717E+09 | 87.28 | 18-AUG-22:10 | 24.67 | 20.11 |
September | 0.137791E+10 | 735.66 | 30-SEP-10:33 | 30.57 | 17.23 | 0.133901E+09 | 88.56 | 29-SEP-22:10 | 30.57 | 17.23 |
October | 0.143545E+10 | 734.00 | 16-OCT-10:33 | 36.33 | 17.49 | 0.139459E+09 | 89.83 | 16-OCT-22:10 | 20.17 | 11.06 |
November | 0.123478E+10 | 643.94 | 19-NOV-11:33 | 26.00 | 15.32 | 0.125942E+09 | 81.46 | 01-NOV-22:10 | 26.00 | 15.32 |
December | 0.123918E+10 | 625.48 | 19-DEC-11:33 | 25.00 | 11.16 | 0.127934E+09 | 82.02 | 05-DEC-23:10 | 25.00 | 11.16 |
Annual Sum or Average | 0.156751E+11 | 0.156737E+10 | ||||||||
Minimum of Months | 0.109451E+10 | 598.69 | 19.33 | 10.71 | 0.114249E+09 | 80.03 | 11.67 | 3.87 | ||
Maximum of Months | 0.148612E+10 | 735.66 | 36.33 | 20.39 | 0.141717E+09 | 89.83 | 30.57 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.505639E+11 | 37582.47 | 24-JAN-21:00 | 17.00 | 11.91 | 0.578883E+09 | 381.76 | 31-JAN-22:10 | 11.82 | 10.56 |
February | 0.455463E+11 | 37448.00 | 03-FEB-21:00 | 13.00 | 7.33 | 0.524380E+09 | 381.71 | 15-FEB-22:10 | 13.83 | 12.18 |
March | 0.505557E+11 | 37697.31 | 23-MAR-20:00 | 14.00 | 13.42 | 0.580519E+09 | 381.75 | 02-MAR-22:10 | 14.00 | 13.42 |
April | 0.497087E+11 | 38001.83 | 26-APR-20:00 | 17.00 | 15.07 | 0.562641E+09 | 381.68 | 24-APR-21:10 | 17.00 | 15.07 |
May | 0.514691E+11 | 38015.54 | 04-MAY-20:00 | 17.00 | 15.07 | 0.582194E+09 | 381.71 | 23-MAY-21:10 | 13.58 | 12.43 |
June | 0.504779E+11 | 38024.64 | 30-JUN-20:00 | 16.00 | 15.39 | 0.564911E+09 | 381.69 | 02-JUN-21:10 | 16.00 | 15.39 |
July | 0.526151E+11 | 38288.05 | 19-JUL-20:00 | 19.00 | 18.34 | 0.583353E+09 | 381.68 | 18-JUL-21:19 | 19.00 | 18.34 |
August | 0.528982E+11 | 38230.72 | 18-AUG-20:00 | 19.00 | 17.66 | 0.584826E+09 | 381.68 | 18-AUG-21:19 | 19.00 | 17.66 |
September | 0.503986E+11 | 38524.41 | 29-SEP-20:00 | 25.00 | 13.58 | 0.564112E+09 | 381.81 | 14-SEP-21:10 | 25.00 | 13.58 |
October | 0.520845E+11 | 38368.76 | 16-OCT-20:00 | 21.00 | 13.07 | 0.583792E+09 | 381.74 | 31-OCT-21:10 | 16.88 | 14.87 |
November | 0.493093E+11 | 37448.82 | 28-NOV-21:00 | 13.00 | 6.31 | 0.563186E+09 | 381.72 | 02-NOV-21:10 | 13.00 | 6.31 |
December | 0.505632E+11 | 37700.86 | 05-DEC-21:00 | 16.00 | 9.09 | 0.580954E+09 | 381.74 | 08-DEC-22:10 | 14.00 | 12.84 |
Annual Sum or Average | 0.606190E+12 | 0.685375E+10 | ||||||||
Minimum of Months | 0.455463E+11 | 37448.00 | 13.00 | 6.31 | 0.524380E+09 | 381.68 | 11.82 | 6.31 | ||
Maximum of Months | 0.528982E+11 | 38524.41 | 25.00 | 18.34 | 0.584826E+09 | 381.81 | 25.00 | 18.34 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204035E+11 | 13066.57 | 14-JAN-12:40 | 25.33 | 11.70 | 0.102429E+11 | 6461.99 | 21-JAN-02:20 | 14.00 | 13.42 |
February | 0.173754E+11 | 10990.21 | 20-FEB-11:00 | 16.00 | 9.07 | 0.914717E+10 | 6462.04 | 02-FEB-00:20 | 16.00 | 9.07 |
March | 0.184040E+11 | 10917.54 | 11-MAR-12:50 | 24.00 | 13.82 | 0.994475E+10 | 6461.96 | 24-MAR-23:19 | 13.00 | 11.12 |
April | 0.185603E+11 | 9281.91 | 08-APR-10:33 | 21.67 | 16.37 | 0.980810E+10 | 6461.98 | 13-APR-23:19 | 14.67 | 13.68 |
May | 0.183779E+11 | 8907.76 | 04-MAY-21:20 | 17.00 | 15.07 | 0.993076E+10 | 6462.00 | 04-MAY-23:19 | 16.00 | 14.76 |
June | 0.184217E+11 | 8750.62 | 25-JUN-10:33 | 23.00 | 17.26 | 0.982448E+10 | 6462.00 | 27-JUN-23:19 | 17.00 | 16.16 |
July | 0.199644E+11 | 9351.72 | 30-JUL-10:33 | 24.67 | 20.10 | 0.103241E+11 | 6462.01 | 14-JUL-23:19 | 24.67 | 20.10 |
August | 0.207505E+11 | 9692.55 | 27-AUG-10:33 | 23.33 | 18.72 | 0.105759E+11 | 6462.02 | 23-AUG-23:19 | 23.33 | 18.72 |
September | 0.202656E+11 | 12510.34 | 30-SEP-12:00 | 32.00 | 17.11 | 0.102252E+11 | 6462.04 | 30-SEP-01:19 | 32.00 | 17.11 |
October | 0.221068E+11 | 14122.28 | 15-OCT-12:00 | 32.00 | 16.89 | 0.106162E+11 | 6462.05 | 12-OCT-23:19 | 32.00 | 16.89 |
November | 0.200729E+11 | 14301.89 | 19-NOV-11:00 | 26.00 | 15.07 | 0.100663E+11 | 6462.00 | 28-NOV-00:20 | 15.33 | 5.14 |
December | 0.209643E+11 | 12938.47 | 16-DEC-13:00 | 26.00 | 13.31 | 0.103602E+11 | 6462.31 | 01-DEC-00:30 | 26.00 | 13.31 |
Annual Sum or Average | 0.235667E+12 | 0.121066E+12 | ||||||||
Minimum of Months | 0.173754E+11 | 8750.62 | 16.00 | 9.07 | 0.914717E+10 | 6461.96 | 13.00 | 5.14 | ||
Maximum of Months | 0.221068E+11 | 14301.89 | 32.00 | 20.10 | 0.106162E+11 | 6462.31 | 32.00 | 20.10 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.652057E+11 | 33503.26 | 18-JAN-22:10 | 16.83 | 13.41 | 0.310448E+11 | 19185.29 | 31-JAN-00:20 | 13.00 | 11.68 |
February | 0.576449E+11 | 32802.11 | 01-FEB-22:10 | 13.00 | 11.77 | 0.279647E+11 | 19185.35 | 02-FEB-00:20 | 13.33 | 12.00 |
March | 0.626144E+11 | 32101.29 | 24-MAR-21:10 | 13.00 | 11.77 | 0.306509E+11 | 19185.22 | 22-MAR-23:19 | 13.00 | 11.77 |
April | 0.631022E+11 | 32520.34 | 26-APR-22:00 | 16.00 | 15.39 | 0.300927E+11 | 19185.24 | 06-APR-23:19 | 16.00 | 15.39 |
May | 0.645277E+11 | 33670.75 | 04-MAY-21:10 | 17.00 | 15.07 | 0.310152E+11 | 19185.30 | 05-MAY-23:19 | 15.33 | 14.33 |
June | 0.649687E+11 | 33472.85 | 28-JUN-21:10 | 17.00 | 16.37 | 0.304914E+11 | 19185.30 | 07-JUN-23:19 | 17.00 | 16.37 |
July | 0.699207E+11 | 34980.46 | 31-JUL-21:10 | 18.95 | 17.72 | 0.316815E+11 | 19185.28 | 21-JUL-23:19 | 18.95 | 17.72 |
August | 0.713604E+11 | 35567.76 | 18-AUG-21:10 | 19.00 | 17.66 | 0.319647E+11 | 19185.31 | 22-AUG-23:19 | 17.00 | 15.07 |
September | 0.680702E+11 | 39577.34 | 29-SEP-21:10 | 24.58 | 13.52 | 0.308375E+11 | 19185.34 | 30-SEP-01:19 | 24.20 | 13.95 |
October | 0.717644E+11 | 40238.61 | 16-OCT-20:10 | 20.50 | 12.73 | 0.319693E+11 | 19185.35 | 23-OCT-23:19 | 16.33 | 13.70 |
November | 0.645070E+11 | 33567.47 | 20-NOV-22:10 | 14.00 | 12.84 | 0.305028E+11 | 19185.35 | 20-NOV-00:20 | 14.00 | 12.84 |
December | 0.660608E+11 | 35094.34 | 05-DEC-22:10 | 17.17 | 9.45 | 0.313972E+11 | 19187.90 | 01-DEC-01:10 | 17.17 | 9.45 |
Annual Sum or Average | 0.789747E+12 | 0.369613E+12 | ||||||||
Minimum of Months | 0.576449E+11 | 32101.29 | 13.00 | 9.45 | 0.279647E+11 | 19185.22 | 13.00 | 9.45 | ||
Maximum of Months | 0.717644E+11 | 40238.61 | 24.58 | 17.72 | 0.319693E+11 | 19187.90 | 24.20 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.631921E+09 | 2773.34 | 14-JAN-16:02 | 23.00 | 12.42 | 97477264.69 | 56.69 | 20-JAN-22:10 | 13.17 | 13.17 |
February | 0.557410E+09 | 2732.73 | 03-FEB-16:02 | 20.50 | 10.05 | 87694835.84 | 56.69 | 16-FEB-22:10 | 12.00 | 11.46 |
March | 0.580552E+09 | 2788.34 | 11-MAR-16:02 | 21.33 | 12.81 | 97079676.69 | 56.69 | 23-MAR-22:19 | 12.67 | 12.30 |
April | 0.103808E+10 | 2798.83 | 01-APR-15:01 | 22.83 | 11.17 | 94814710.02 | 56.69 | 27-APR-21:10 | 14.00 | 12.84 |
May | 0.990121E+09 | 2670.37 | 17-MAY-15:02 | 21.67 | 15.72 | 97903186.24 | 56.69 | 04-MAY-23:49 | 21.67 | 15.72 |
June | 0.127645E+10 | 2704.29 | 30-JUN-15:02 | 22.95 | 17.86 | 95108077.68 | 56.69 | 22-JUN-21:10 | 22.95 | 17.86 |
July | 0.170560E+10 | 2812.62 | 19-JUL-15:02 | 26.67 | 20.20 | 98586156.20 | 56.69 | 24-JUL-21:30 | 18.00 | 17.35 |
August | 0.175907E+10 | 2786.65 | 18-AUG-15:02 | 26.50 | 20.71 | 98746243.58 | 56.69 | 16-AUG-21:30 | 26.50 | 20.71 |
September | 0.146339E+10 | 2643.57 | 13-SEP-15:02 | 22.83 | 18.37 | 95251107.51 | 56.69 | 30-SEP-23:10 | 18.23 | 17.87 |
October | 0.146166E+10 | 2970.36 | 15-OCT-15:02 | 30.83 | 15.40 | 98269700.78 | 56.69 | 18-OCT-21:10 | 14.83 | 14.34 |
November | 0.799331E+09 | 2767.99 | 19-NOV-09:02 | 24.33 | 12.78 | 94691637.27 | 56.69 | 10-NOV-22:00 | 24.33 | 12.78 |
December | 0.719270E+09 | 2788.91 | 05-DEC-16:02 | 22.67 | 12.42 | 97635148.83 | 56.69 | 07-DEC-22:10 | 12.67 | 12.59 |
Annual Sum or Average | 0.129829E+11 | 0.115326E+10 | ||||||||
Minimum of Months | 0.557410E+09 | 2643.57 | 20.50 | 10.05 | 87694835.84 | 56.69 | 12.00 | 11.46 | ||
Maximum of Months | 0.175907E+10 | 2970.36 | 30.83 | 20.71 | 98746243.58 | 56.69 | 26.50 | 20.71 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.275567E+09 | 2639.25 | 14-JAN-16:02 | 23.00 | 12.42 | 96103948.62 | 56.69 | 20-JAN-23:10 | 13.83 | 13.83 |
February | 0.292818E+09 | 2598.87 | 03-FEB-16:02 | 20.50 | 10.05 | 86863467.88 | 56.69 | 24-FEB-00:20 | 13.00 | 11.87 |
March | 0.377444E+09 | 2657.91 | 11-MAR-16:02 | 21.33 | 12.81 | 96373689.46 | 56.69 | 23-MAR-21:10 | 13.83 | 13.26 |
April | 0.852730E+09 | 2678.29 | 01-APR-15:01 | 22.83 | 11.17 | 94361587.59 | 56.69 | 27-APR-00:49 | 15.00 | 14.90 |
May | 0.948540E+09 | 2590.25 | 17-MAY-15:02 | 21.67 | 15.72 | 97780117.45 | 56.69 | 02-MAY-23:00 | 21.67 | 15.72 |
June | 0.128333E+10 | 2614.88 | 30-JUN-15:02 | 22.95 | 17.86 | 95080435.94 | 56.69 | 28-JUN-21:10 | 22.95 | 17.86 |
July | 0.167926E+10 | 2687.05 | 19-JUL-15:02 | 26.67 | 20.20 | 98544912.63 | 56.69 | 19-JUL-22:19 | 18.00 | 17.35 |
August | 0.160055E+10 | 2675.66 | 19-AUG-15:02 | 25.83 | 18.86 | 98581498.68 | 56.69 | 07-AUG-21:19 | 25.83 | 18.86 |
September | 0.119180E+10 | 2588.08 | 11-SEP-15:02 | 22.00 | 16.76 | 94832675.11 | 56.69 | 05-SEP-23:10 | 22.00 | 16.76 |
October | 0.106749E+10 | 2830.16 | 16-OCT-15:02 | 29.83 | 15.97 | 97687665.23 | 56.69 | 17-OCT-21:19 | 18.00 | 14.77 |
November | 0.391961E+09 | 2568.51 | 27-NOV-16:01 | 19.67 | 7.55 | 93680328.56 | 56.69 | 02-NOV-02:09 | 19.67 | 7.55 |
December | 0.295972E+09 | 2654.36 | 05-DEC-16:02 | 22.67 | 12.42 | 96246262.75 | 56.69 | 05-DEC-22:10 | 17.17 | 9.45 |
Annual Sum or Average | 0.102575E+11 | 0.114614E+10 | ||||||||
Minimum of Months | 0.275567E+09 | 2568.51 | 19.67 | 7.55 | 86863467.88 | 56.69 | 13.00 | 7.55 | ||
Maximum of Months | 0.167926E+10 | 2830.16 | 29.83 | 20.20 | 98581498.68 | 56.69 | 25.83 | 18.86 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.554547E+09 | 633.45 | 14-JAN-12:40 | 25.33 | 11.70 | 0.00 | 0.00 | 01-JAN-00:10 | 25.33 | 11.70 |
February | 0.406038E+09 | 569.66 | 02-FEB-12:30 | 19.50 | 11.91 | 0.00 | 0.00 | 01-FEB-00:10 | 19.50 | 11.91 |
March | 0.346886E+09 | 476.04 | 11-MAR-13:30 | 24.00 | 13.28 | 0.00 | 0.00 | 01-MAR-00:10 | 24.00 | 13.28 |
April | 0.334133E+09 | 355.93 | 08-APR-13:10 | 21.83 | 16.35 | 0.00 | 0.00 | 01-APR-00:10 | 21.83 | 16.35 |
May | 0.269939E+09 | 254.24 | 04-MAY-12:30 | 23.50 | 16.62 | 0.00 | 0.00 | 01-MAY-00:10 | 23.50 | 16.62 |
June | 0.273265E+09 | 184.28 | 29-JUN-17:13 | 22.67 | 18.51 | 0.00 | 0.00 | 01-JUN-00:10 | 22.67 | 18.51 |
July | 0.357452E+09 | 278.20 | 31-JUL-13:00 | 28.00 | 21.19 | 0.00 | 0.00 | 01-JUL-00:10 | 28.00 | 21.19 |
August | 0.444861E+09 | 348.39 | 30-AUG-13:00 | 24.00 | 18.12 | 0.00 | 0.00 | 01-AUG-00:10 | 24.00 | 18.12 |
September | 0.476893E+09 | 629.55 | 30-SEP-13:30 | 32.00 | 17.24 | 0.00 | 0.00 | 01-SEP-00:10 | 32.00 | 17.24 |
October | 0.620077E+09 | 738.33 | 16-OCT-12:20 | 35.37 | 17.35 | 0.00 | 0.00 | 01-OCT-00:10 | 35.37 | 17.35 |
November | 0.549129E+09 | 684.84 | 19-NOV-13:00 | 27.00 | 14.96 | 0.00 | 0.00 | 01-NOV-00:10 | 27.00 | 14.96 |
December | 0.606712E+09 | 642.41 | 19-DEC-13:00 | 26.00 | 11.60 | 0.00 | 0.00 | 01-DEC-00:10 | 26.00 | 11.60 |
Annual Sum or Average | 0.523993E+10 | 0.00 | ||||||||
Minimum of Months | 0.269939E+09 | 184.28 | 19.50 | 11.60 | 0.00 | 0.00 | 19.50 | 11.60 | ||
Maximum of Months | 0.620077E+09 | 738.33 | 35.37 | 21.19 | 0.00 | 0.00 | 35.37 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255566E+09 | 828.61 | 15-JAN-09:02 | 22.50 | 9.56 | 95663256.14 | 56.69 | 19-JAN-22:10 | 14.00 | 12.84 |
February | 0.258580E+09 | 745.81 | 20-FEB-09:02 | 14.00 | 8.40 | 86603082.39 | 56.69 | 13-FEB-22:40 | 14.00 | 8.40 |
March | 0.297644E+09 | 799.31 | 11-MAR-16:02 | 21.33 | 12.81 | 96062510.74 | 56.69 | 23-MAR-21:10 | 13.83 | 13.26 |
April | 0.399958E+09 | 824.70 | 26-APR-15:02 | 22.83 | 16.24 | 93232681.70 | 56.69 | 27-APR-21:00 | 14.00 | 12.84 |
May | 0.467497E+09 | 818.11 | 04-MAY-15:02 | 22.00 | 16.32 | 96570167.20 | 56.69 | 25-MAY-21:00 | 15.00 | 13.80 |
June | 0.544609E+09 | 817.08 | 30-JUN-15:02 | 22.95 | 17.86 | 93755615.18 | 56.69 | 30-JUN-22:00 | 16.30 | 15.68 |
July | 0.636955E+09 | 839.46 | 18-JUL-18:02 | 23.33 | 19.62 | 97110983.54 | 56.69 | 27-JUL-22:30 | 18.00 | 17.35 |
August | 0.598247E+09 | 842.65 | 19-AUG-18:02 | 22.67 | 17.49 | 97080675.08 | 56.69 | 29-AUG-21:00 | 17.30 | 15.46 |
September | 0.485188E+09 | 850.16 | 30-SEP-18:02 | 22.67 | 16.87 | 93416285.28 | 56.69 | 06-SEP-22:10 | 22.67 | 16.87 |
October | 0.492127E+09 | 920.21 | 14-OCT-15:02 | 32.83 | 16.38 | 96508587.82 | 56.69 | 18-OCT-21:00 | 14.00 | 14.00 |
November | 0.293844E+09 | 859.85 | 19-NOV-09:02 | 24.33 | 12.78 | 92844884.10 | 56.69 | 10-NOV-22:10 | 24.33 | 12.78 |
December | 0.256035E+09 | 826.28 | 05-DEC-09:02 | 24.33 | 12.02 | 95622366.17 | 56.69 | 01-DEC-00:00 | 24.33 | 12.02 |
Annual Sum or Average | 0.498625E+10 | 0.113447E+10 | ||||||||
Minimum of Months | 0.255566E+09 | 745.81 | 14.00 | 8.40 | 86603082.39 | 56.69 | 13.83 | 8.40 | ||
Maximum of Months | 0.636955E+09 | 920.21 | 32.83 | 19.62 | 97110983.54 | 56.69 | 24.33 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.657336E+09 | 2455.23 | 14-JAN-16:02 | 23.00 | 12.42 | 97806448.96 | 56.69 | 20-JAN-23:10 | 13.83 | 13.83 |
February | 0.522965E+09 | 2441.81 | 01-FEB-09:02 | 22.33 | 11.86 | 87850322.36 | 56.69 | 01-FEB-22:19 | 13.00 | 11.68 |
March | 0.571397E+09 | 2438.19 | 11-MAR-16:02 | 21.33 | 12.81 | 97292126.67 | 56.69 | 23-MAR-22:19 | 12.67 | 12.30 |
April | 0.948985E+09 | 2473.12 | 01-APR-15:01 | 22.83 | 11.17 | 95057995.13 | 56.69 | 27-APR-00:40 | 15.00 | 14.80 |
May | 0.870594E+09 | 2345.85 | 04-MAY-15:02 | 22.00 | 16.32 | 97984329.68 | 56.69 | 02-MAY-23:00 | 22.00 | 16.32 |
June | 0.110727E+10 | 2332.87 | 02-JUN-15:02 | 20.67 | 15.42 | 95151155.53 | 56.69 | 26-JUN-00:00 | 17.00 | 15.07 |
July | 0.156048E+10 | 2373.99 | 19-JUL-15:02 | 26.67 | 20.20 | 98818645.44 | 56.69 | 18-JUL-21:19 | 26.67 | 20.20 |
August | 0.167406E+10 | 2425.26 | 19-AUG-15:02 | 25.83 | 18.86 | 98943065.47 | 56.69 | 18-AUG-22:10 | 25.83 | 18.86 |
September | 0.128378E+10 | 2364.08 | 30-SEP-18:02 | 22.67 | 16.87 | 95200085.63 | 56.69 | 30-SEP-23:00 | 18.40 | 17.30 |
October | 0.139726E+10 | 2614.49 | 15-OCT-08:62 | 29.67 | 14.37 | 98390704.44 | 56.69 | 01-OCT-00:10 | 29.67 | 14.37 |
November | 0.748297E+09 | 2531.02 | 19-NOV-09:02 | 24.33 | 12.78 | 94861629.61 | 56.69 | 10-NOV-22:10 | 24.33 | 12.78 |
December | 0.717452E+09 | 2515.91 | 05-DEC-09:02 | 24.33 | 12.02 | 97884600.40 | 56.69 | 07-DEC-22:10 | 12.67 | 12.59 |
Annual Sum or Average | 0.120599E+11 | 0.115524E+10 | ||||||||
Minimum of Months | 0.522965E+09 | 2332.87 | 20.67 | 11.17 | 87850322.36 | 56.69 | 12.67 | 11.68 | ||
Maximum of Months | 0.167406E+10 | 2614.49 | 29.67 | 20.20 | 98943065.47 | 56.69 | 29.67 | 20.20 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.315138E+09 | 2190.78 | 14-JAN-16:02 | 23.00 | 12.42 | 96092062.73 | 56.69 | 20-JAN-23:10 | 13.83 | 13.83 |
February | 0.282536E+09 | 2261.59 | 01-FEB-09:02 | 22.33 | 11.86 | 86801641.24 | 56.69 | 24-FEB-00:20 | 13.00 | 11.87 |
March | 0.375330E+09 | 2260.02 | 11-MAR-16:02 | 21.33 | 12.81 | 96517555.00 | 56.69 | 23-MAR-21:10 | 13.83 | 13.26 |
April | 0.762443E+09 | 2309.64 | 26-APR-15:02 | 22.83 | 16.24 | 94626760.73 | 56.69 | 26-APR-23:49 | 15.17 | 14.47 |
May | 0.830451E+09 | 2260.47 | 24-MAY-08:62 | 18.00 | 8.80 | 97849086.12 | 56.69 | 05-MAY-00:30 | 18.00 | 8.80 |
June | 0.111188E+10 | 2251.24 | 02-JUN-15:02 | 20.67 | 15.42 | 95167477.38 | 56.69 | 26-JUN-01:30 | 17.00 | 15.07 |
July | 0.153070E+10 | 2277.44 | 19-JUL-15:02 | 26.67 | 20.20 | 98828986.29 | 56.69 | 18-JUL-21:30 | 26.67 | 20.20 |
August | 0.150466E+10 | 2289.17 | 19-AUG-15:02 | 25.83 | 18.86 | 98882568.46 | 56.69 | 18-AUG-21:40 | 25.83 | 18.86 |
September | 0.101064E+10 | 2287.68 | 30-SEP-18:02 | 22.67 | 16.87 | 94796456.36 | 56.69 | 12-SEP-22:49 | 22.67 | 16.87 |
October | 0.996298E+09 | 2503.20 | 15-OCT-08:62 | 29.67 | 14.37 | 97850991.84 | 56.69 | 17-OCT-21:19 | 18.00 | 14.77 |
November | 0.381187E+09 | 2404.56 | 19-NOV-09:02 | 24.33 | 12.78 | 93422473.49 | 56.69 | 09-NOV-22:19 | 24.33 | 12.78 |
December | 0.321434E+09 | 2392.48 | 05-DEC-09:02 | 24.33 | 12.02 | 96109005.08 | 56.69 | 01-DEC-01:19 | 24.33 | 12.02 |
Annual Sum or Average | 0.942270E+10 | 0.114695E+10 | ||||||||
Minimum of Months | 0.282536E+09 | 2190.78 | 18.00 | 8.80 | 86801641.24 | 56.69 | 13.00 | 8.80 | ||
Maximum of Months | 0.153070E+10 | 2503.20 | 29.67 | 20.20 | 98882568.46 | 56.69 | 26.67 | 20.20 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405399E+10 | 2258.34 | 08-JAN-07:00 | 1.00 | -0.3 | 0.134373E+10 | 856.20 | 20-JAN-23:10 | 13.83 | 13.83 |
February | 0.363365E+10 | 1981.93 | 04-FEB-11:45 | 20.83 | 8.35 | 0.121876E+10 | 853.61 | 03-FEB-23:10 | 20.83 | 8.35 |
March | 0.393145E+10 | 1992.74 | 12-MAR-10:33 | 21.33 | 14.69 | 0.132708E+10 | 848.79 | 24-MAR-21:49 | 13.00 | 11.39 |
April | 0.408109E+10 | 2098.26 | 30-APR-10:33 | 25.67 | 16.97 | 0.133088E+10 | 859.87 | 27-APR-21:49 | 25.67 | 16.97 |
May | 0.424239E+10 | 2099.24 | 04-MAY-10:33 | 22.00 | 15.73 | 0.138470E+10 | 877.69 | 04-MAY-21:49 | 17.00 | 15.07 |
June | 0.431197E+10 | 2151.16 | 25-JUN-10:33 | 23.00 | 17.26 | 0.137936E+10 | 886.67 | 30-JUN-22:10 | 16.13 | 16.03 |
July | 0.471035E+10 | 2248.67 | 23-JUL-10:33 | 25.67 | 20.39 | 0.146570E+10 | 901.31 | 31-JUL-21:49 | 18.75 | 17.98 |
August | 0.478165E+10 | 2268.17 | 19-AUG-10:33 | 24.67 | 20.11 | 0.148790E+10 | 912.16 | 18-AUG-21:49 | 24.67 | 20.11 |
September | 0.446763E+10 | 2357.60 | 30-SEP-10:33 | 30.57 | 17.23 | 0.141089E+10 | 925.90 | 29-SEP-22:10 | 30.57 | 17.23 |
October | 0.469718E+10 | 2367.29 | 17-OCT-10:33 | 31.00 | 16.57 | 0.147927E+10 | 948.76 | 17-OCT-21:40 | 18.00 | 14.57 |
November | 0.410889E+10 | 2120.89 | 19-NOV-11:33 | 26.00 | 15.32 | 0.134788E+10 | 878.76 | 01-NOV-00:10 | 26.00 | 15.32 |
December | 0.415970E+10 | 2032.54 | 05-DEC-11:33 | 23.33 | 12.89 | 0.137603E+10 | 868.43 | 05-DEC-23:10 | 17.33 | 9.21 |
Annual Sum or Average | 0.511799E+11 | 0.165522E+11 | ||||||||
Minimum of Months | 0.363365E+10 | 1981.93 | 1.00 | -0.3 | 0.121876E+10 | 848.79 | 13.00 | 8.35 | ||
Maximum of Months | 0.478165E+10 | 2367.29 | 31.00 | 20.39 | 0.148790E+10 | 948.76 | 30.57 | 20.11 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.494545E+09 | 2866.89 | 14-JAN-16:02 | 23.00 | 12.42 | 97148379.18 | 56.69 | 31-JAN-22:30 | 12.05 | 10.63 |
February | 0.439295E+09 | 2818.64 | 03-FEB-16:02 | 20.50 | 10.05 | 87352183.23 | 56.70 | 17-FEB-00:10 | 12.00 | 11.46 |
March | 0.492509E+09 | 2883.92 | 11-MAR-16:02 | 21.33 | 12.81 | 96796110.06 | 56.69 | 23-MAR-21:19 | 13.67 | 13.10 |
April | 0.948196E+09 | 2892.67 | 01-APR-15:01 | 22.83 | 11.17 | 94733586.06 | 56.69 | 26-APR-03:49 | 13.00 | 11.97 |
May | 0.882761E+09 | 2731.91 | 04-MAY-15:02 | 22.00 | 16.32 | 97800930.88 | 56.69 | 18-MAY-00:00 | 12.00 | 10.91 |
June | 0.120582E+10 | 2768.52 | 28-JUN-15:02 | 22.83 | 18.37 | 95074684.25 | 56.69 | 30-JUN-00:10 | 17.00 | 16.90 |
July | 0.167381E+10 | 2860.19 | 18-JUL-15:02 | 26.00 | 20.07 | 98575921.61 | 56.69 | 24-JUL-00:10 | 17.00 | 16.37 |
August | 0.170555E+10 | 2849.59 | 06-AUG-15:02 | 24.83 | 20.15 | 98696536.47 | 56.69 | 10-AUG-23:49 | 17.08 | 16.63 |
September | 0.135116E+10 | 2730.44 | 08-SEP-15:02 | 21.83 | 18.03 | 95167538.84 | 56.69 | 25-SEP-22:40 | 16.00 | 15.59 |
October | 0.129651E+10 | 3075.83 | 15-OCT-15:02 | 30.83 | 15.40 | 98079855.38 | 56.69 | 17-OCT-21:30 | 18.00 | 14.67 |
November | 0.623662E+09 | 2812.75 | 19-NOV-09:02 | 24.33 | 12.78 | 94385893.96 | 56.69 | 10-NOV-23:10 | 24.33 | 12.78 |
December | 0.558417E+09 | 2882.53 | 05-DEC-16:02 | 22.67 | 12.42 | 97260011.09 | 56.69 | 06-DEC-22:19 | 15.00 | 9.64 |
Annual Sum or Average | 0.116722E+11 | 0.115107E+10 | ||||||||
Minimum of Months | 0.439295E+09 | 2730.44 | 20.50 | 10.05 | 87352183.23 | 56.69 | 12.00 | 9.64 | ||
Maximum of Months | 0.170555E+10 | 3075.83 | 30.83 | 20.15 | 98696536.47 | 56.70 | 24.33 | 16.90 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191627E+09 | 2714.13 | 14-JAN-16:02 | 23.00 | 12.42 | 95597484.12 | 56.69 | 31-JAN-04:19 | 12.00 | 12.00 |
February | 0.209540E+09 | 2665.65 | 03-FEB-16:02 | 20.50 | 10.05 | 86420922.34 | 56.69 | 24-FEB-00:20 | 13.00 | 11.87 |
March | 0.305090E+09 | 2737.82 | 11-MAR-16:02 | 21.33 | 12.81 | 96050377.57 | 56.69 | 23-MAR-21:19 | 13.67 | 13.10 |
April | 0.752991E+09 | 2757.61 | 01-APR-15:01 | 22.83 | 11.17 | 94285350.29 | 56.69 | 14-APR-01:00 | 14.00 | 12.84 |
May | 0.837611E+09 | 2643.24 | 17-MAY-15:02 | 21.67 | 15.72 | 97686658.43 | 56.69 | 20-MAY-03:39 | 13.00 | 10.96 |
June | 0.121092E+10 | 2676.51 | 28-JUN-15:02 | 22.83 | 18.37 | 95056473.21 | 56.69 | 25-JUN-23:00 | 22.83 | 18.37 |
July | 0.164351E+10 | 2768.19 | 18-JUL-15:02 | 26.00 | 20.07 | 98551208.80 | 56.69 | 19-JUL-21:10 | 18.00 | 17.89 |
August | 0.153333E+10 | 2766.27 | 18-AUG-15:02 | 26.50 | 20.71 | 98565243.38 | 56.69 | 25-AUG-23:10 | 16.10 | 16.03 |
September | 0.105721E+10 | 2668.61 | 10-SEP-15:02 | 22.00 | 17.30 | 94755097.29 | 56.69 | 27-SEP-21:00 | 16.70 | 15.11 |
October | 0.892262E+09 | 2919.66 | 16-OCT-15:02 | 29.83 | 15.97 | 97446999.65 | 56.69 | 11-OCT-02:00 | 29.83 | 15.97 |
November | 0.252589E+09 | 2625.90 | 27-NOV-16:01 | 19.67 | 7.55 | 93230658.31 | 56.69 | 13-NOV-22:10 | 19.67 | 7.55 |
December | 0.195844E+09 | 2728.31 | 05-DEC-16:02 | 22.67 | 12.42 | 95670407.38 | 56.69 | 06-DEC-00:30 | 16.00 | 8.84 |
Annual Sum or Average | 0.908252E+10 | 0.114332E+10 | ||||||||
Minimum of Months | 0.191627E+09 | 2625.90 | 19.67 | 7.55 | 86420922.34 | 56.69 | 12.00 | 7.55 | ||
Maximum of Months | 0.164351E+10 | 2919.66 | 29.83 | 20.71 | 98565243.38 | 56.69 | 29.83 | 18.37 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.891740E+09 | 1564.22 | 14-JAN-16:02 | 23.00 | 12.42 | 98338808.66 | 56.69 | 19-JAN-22:19 | 14.00 | 12.84 |
February | 0.607570E+09 | 1524.80 | 03-FEB-16:02 | 20.50 | 10.05 | 88258265.26 | 56.69 | 01-FEB-22:30 | 20.50 | 10.05 |
March | 0.523269E+09 | 1541.67 | 10-MAR-16:02 | 21.67 | 12.40 | 97500518.58 | 56.69 | 24-MAR-21:10 | 13.00 | 11.77 |
April | 0.614892E+09 | 1552.40 | 01-APR-15:01 | 22.83 | 11.17 | 94774648.32 | 56.69 | 11-APR-21:10 | 13.83 | 13.83 |
May | 0.440836E+09 | 1458.93 | 03-MAY-15:02 | 21.83 | 15.33 | 97349318.14 | 56.69 | 04-MAY-23:40 | 16.00 | 14.76 |
June | 0.539206E+09 | 1440.38 | 20-JUN-15:02 | 21.83 | 15.76 | 94508062.05 | 56.69 | 29-JUN-22:30 | 16.50 | 16.50 |
July | 0.767135E+09 | 1452.95 | 31-JUL-15:02 | 25.67 | 20.38 | 98195895.98 | 56.69 | 31-JUL-21:10 | 18.95 | 17.72 |
August | 0.933334E+09 | 1518.08 | 19-AUG-15:02 | 25.83 | 18.86 | 98493088.45 | 56.69 | 21-AUG-21:10 | 15.17 | 13.86 |
September | 0.943124E+09 | 1486.11 | 30-SEP-18:02 | 22.67 | 16.87 | 95091378.03 | 56.69 | 26-SEP-21:00 | 22.67 | 16.87 |
October | 0.115733E+10 | 1646.35 | 16-OCT-15:02 | 29.83 | 15.97 | 98430425.11 | 56.70 | 17-OCT-21:19 | 18.00 | 14.77 |
November | 0.900462E+09 | 1575.24 | 19-NOV-09:02 | 24.33 | 12.78 | 95311041.65 | 56.69 | 20-NOV-23:10 | 14.00 | 12.84 |
December | 0.974676E+09 | 1565.90 | 05-DEC-16:02 | 22.67 | 12.42 | 98435257.81 | 56.69 | 07-DEC-22:10 | 12.67 | 12.59 |
Annual Sum or Average | 0.929357E+10 | 0.115469E+10 | ||||||||
Minimum of Months | 0.440836E+09 | 1440.38 | 20.50 | 10.05 | 88258265.26 | 56.69 | 12.67 | 10.05 | ||
Maximum of Months | 0.115733E+10 | 1646.35 | 29.83 | 20.38 | 98493088.45 | 56.70 | 22.67 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.350092E+11 | 19641.94 | 18-JAN-22:10 | 16.83 | 13.41 | 0.189779E+11 | 11347.81 | 27-JAN-04:19 | 6.00 | 5.49 |
February | 0.318572E+11 | 19019.07 | 01-FEB-23:00 | 13.00 | 11.29 | 0.172260E+11 | 11347.92 | 28-FEB-04:19 | 11.00 | 8.85 |
March | 0.355214E+11 | 19387.93 | 24-MAR-22:00 | 13.00 | 11.29 | 0.191390E+11 | 11347.97 | 31-MAR-03:20 | 6.33 | 5.52 |
April | 0.363203E+11 | 20332.55 | 26-APR-22:00 | 16.00 | 15.39 | 0.185887E+11 | 11348.00 | 18-APR-03:20 | 16.00 | 15.39 |
May | 0.381066E+11 | 20758.19 | 04-MAY-21:10 | 17.00 | 15.07 | 0.192407E+11 | 11347.76 | 16-MAY-23:19 | 12.00 | 11.28 |
June | 0.386578E+11 | 20979.41 | 27-JUN-22:00 | 17.00 | 16.37 | 0.186911E+11 | 11347.75 | 07-JUN-23:19 | 17.00 | 16.37 |
July | 0.411124E+11 | 21220.96 | 19-JUL-22:00 | 18.00 | 17.35 | 0.192621E+11 | 11347.77 | 23-JUL-23:19 | 17.67 | 16.59 |
August | 0.409595E+11 | 21058.94 | 17-AUG-21:10 | 19.00 | 17.66 | 0.193339E+11 | 11347.76 | 20-AUG-23:19 | 16.67 | 16.04 |
September | 0.380932E+11 | 21633.43 | 29-SEP-21:10 | 24.58 | 13.52 | 0.186268E+11 | 11347.76 | 24-SEP-23:19 | 24.58 | 13.52 |
October | 0.389860E+11 | 21252.04 | 04-OCT-22:00 | 21.00 | 18.98 | 0.192143E+11 | 11347.76 | 12-OCT-23:19 | 12.67 | 8.42 |
November | 0.346710E+11 | 19265.95 | 10-NOV-23:00 | 15.00 | 13.80 | 0.184675E+11 | 11347.85 | 24-NOV-04:19 | 7.33 | 1.09 |
December | 0.350609E+11 | 19734.93 | 05-DEC-23:00 | 18.00 | 9.37 | 0.190329E+11 | 11348.83 | 01-DEC-00:49 | 18.00 | 9.37 |
Annual Sum or Average | 0.444355E+12 | 0.225801E+12 | ||||||||
Minimum of Months | 0.318572E+11 | 19019.07 | 13.00 | 9.37 | 0.172260E+11 | 11347.75 | 6.00 | 1.09 | ||
Maximum of Months | 0.411124E+11 | 21633.43 | 24.58 | 18.98 | 0.193339E+11 | 11348.83 | 24.58 | 16.59 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.383504E+11 | 21236.84 | 18-JAN-22:10 | 16.83 | 13.41 | 0.191205E+11 | 11347.84 | 06-JAN-04:19 | 16.83 | 13.41 |
February | 0.349555E+11 | 20667.54 | 01-FEB-22:10 | 13.00 | 11.77 | 0.173401E+11 | 11347.96 | 28-FEB-04:19 | 11.00 | 8.85 |
March | 0.390238E+11 | 20929.87 | 24-MAR-21:10 | 13.00 | 11.77 | 0.192734E+11 | 11348.02 | 31-MAR-03:20 | 6.33 | 5.52 |
April | 0.396484E+11 | 21803.24 | 26-APR-22:00 | 16.00 | 15.39 | 0.186615E+11 | 11348.03 | 18-APR-03:20 | 16.00 | 15.39 |
May | 0.415884E+11 | 22197.20 | 04-MAY-21:10 | 17.00 | 15.07 | 0.193029E+11 | 11347.76 | 16-MAY-23:19 | 12.00 | 11.28 |
June | 0.419058E+11 | 22341.63 | 27-JUN-21:50 | 17.00 | 16.37 | 0.187301E+11 | 11347.76 | 07-JUN-23:19 | 17.00 | 16.37 |
July | 0.442766E+11 | 22546.24 | 19-JUL-22:00 | 18.00 | 17.35 | 0.192895E+11 | 11347.78 | 23-JUL-23:19 | 17.67 | 16.59 |
August | 0.440215E+11 | 22381.49 | 17-AUG-21:10 | 19.00 | 17.66 | 0.193636E+11 | 11347.77 | 20-AUG-23:19 | 16.67 | 16.04 |
September | 0.411529E+11 | 22927.48 | 29-SEP-21:10 | 24.58 | 13.52 | 0.186683E+11 | 11347.77 | 24-SEP-23:19 | 24.58 | 13.52 |
October | 0.420423E+11 | 22569.84 | 04-OCT-22:00 | 21.00 | 18.98 | 0.192633E+11 | 11347.76 | 12-OCT-23:19 | 12.67 | 8.42 |
November | 0.378502E+11 | 20885.67 | 10-NOV-22:10 | 15.00 | 13.80 | 0.185711E+11 | 11347.88 | 24-NOV-04:19 | 7.33 | 1.09 |
December | 0.383614E+11 | 21247.39 | 05-DEC-23:00 | 18.00 | 9.37 | 0.191589E+11 | 11349.07 | 01-DEC-00:49 | 18.00 | 9.37 |
Annual Sum or Average | 0.483177E+12 | 0.226743E+12 | ||||||||
Minimum of Months | 0.349555E+11 | 20667.54 | 13.00 | 9.37 | 0.173401E+11 | 11347.76 | 6.33 | 1.09 | ||
Maximum of Months | 0.442766E+11 | 22927.48 | 24.58 | 18.98 | 0.193636E+11 | 11349.07 | 24.58 | 16.59 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.520488E+11 | 28217.33 | 20-JAN-11:45 | 21.83 | 15.77 | 0.188123E+11 | 11319.73 | 07-JAN-18:19 | 21.83 | 15.77 |
February | 0.468903E+11 | 28098.85 | 01-FEB-11:45 | 25.50 | 14.48 | 0.170017E+11 | 11319.74 | 25-FEB-18:19 | 11.00 | 9.85 |
March | 0.521940E+11 | 28890.45 | 19-MAR-10:50 | 19.67 | 15.35 | 0.188236E+11 | 11319.63 | 25-MAR-17:19 | 11.00 | 10.47 |
April | 0.522099E+11 | 29394.41 | 30-APR-10:33 | 25.67 | 16.97 | 0.182260E+11 | 11319.58 | 08-APR-17:19 | 25.67 | 16.97 |
May | 0.539147E+11 | 29095.03 | 04-MAY-10:33 | 22.00 | 15.73 | 0.188357E+11 | 11319.57 | 20-MAY-17:19 | 17.00 | 12.68 |
June | 0.533030E+11 | 29431.46 | 25-JUN-10:33 | 23.00 | 17.26 | 0.182396E+11 | 11319.63 | 24-JUN-17:19 | 23.00 | 17.26 |
July | 0.561277E+11 | 29906.79 | 23-JUL-10:33 | 25.67 | 20.39 | 0.188471E+11 | 11319.63 | 08-JUL-17:19 | 25.67 | 20.39 |
August | 0.562246E+11 | 29803.87 | 19-AUG-10:33 | 24.67 | 20.11 | 0.188547E+11 | 11319.65 | 19-AUG-17:19 | 23.67 | 17.53 |
September | 0.532314E+11 | 30317.49 | 30-SEP-10:50 | 30.78 | 17.57 | 0.182367E+11 | 11319.61 | 30-SEP-17:19 | 25.00 | 17.45 |
October | 0.546034E+11 | 30146.57 | 15-OCT-10:50 | 31.83 | 16.40 | 0.188407E+11 | 11319.58 | 28-OCT-17:19 | 16.67 | 14.39 |
November | 0.507883E+11 | 28840.06 | 19-NOV-11:50 | 26.00 | 15.39 | 0.182159E+11 | 11319.67 | 25-NOV-18:19 | 13.00 | 11.13 |
December | 0.520030E+11 | 28120.85 | 05-DEC-11:33 | 23.33 | 12.89 | 0.188193E+11 | 11319.71 | 02-DEC-18:19 | 23.33 | 12.89 |
Annual Sum or Average | 0.633539E+12 | 0.221753E+12 | ||||||||
Minimum of Months | 0.468903E+11 | 28098.85 | 19.67 | 12.89 | 0.170017E+11 | 11319.57 | 11.00 | 9.85 | ||
Maximum of Months | 0.562246E+11 | 30317.49 | 31.83 | 20.39 | 0.188547E+11 | 11319.74 | 25.67 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.782994E+10 | 4283.16 | 20-JAN-11:33 | 21.67 | 15.71 | 0.137325E+10 | 889.78 | 18-JAN-22:40 | 21.67 | 15.71 |
February | 0.708182E+10 | 4091.67 | 01-FEB-11:45 | 25.50 | 14.48 | 0.123921E+10 | 868.27 | 01-FEB-22:40 | 13.00 | 11.48 |
March | 0.767177E+10 | 4264.77 | 11-MAR-11:33 | 24.00 | 13.82 | 0.136854E+10 | 885.90 | 24-MAR-21:40 | 13.00 | 11.48 |
April | 0.830943E+10 | 4420.48 | 30-APR-10:33 | 25.67 | 16.97 | 0.139001E+10 | 911.46 | 27-APR-21:40 | 25.67 | 16.97 |
May | 0.859691E+10 | 4495.64 | 04-MAY-10:33 | 22.00 | 15.73 | 0.144123E+10 | 934.99 | 04-MAY-21:40 | 17.00 | 15.07 |
June | 0.889573E+10 | 4572.91 | 30-JUN-10:33 | 23.33 | 17.95 | 0.145481E+10 | 942.11 | 27-JUN-21:40 | 23.33 | 17.95 |
July | 0.978240E+10 | 4797.85 | 30-JUL-10:33 | 24.67 | 20.10 | 0.155347E+10 | 960.40 | 31-JUL-21:40 | 18.80 | 17.92 |
August | 0.989453E+10 | 4791.63 | 19-AUG-10:33 | 24.67 | 20.11 | 0.157263E+10 | 965.82 | 18-AUG-21:40 | 24.67 | 20.11 |
September | 0.911634E+10 | 5724.55 | 30-SEP-13:40 | 32.00 | 17.36 | 0.147335E+10 | 992.55 | 29-SEP-21:40 | 32.00 | 17.36 |
October | 0.945229E+10 | 5648.22 | 16-OCT-12:50 | 34.42 | 16.94 | 0.152791E+10 | 995.52 | 16-OCT-21:40 | 19.33 | 11.10 |
November | 0.801308E+10 | 4509.46 | 19-NOV-11:33 | 26.00 | 15.32 | 0.136441E+10 | 901.22 | 01-NOV-00:10 | 26.00 | 15.32 |
December | 0.802628E+10 | 4335.54 | 19-DEC-11:33 | 25.00 | 11.16 | 0.138715E+10 | 901.73 | 05-DEC-22:40 | 25.00 | 11.16 |
Annual Sum or Average | 0.102671E+12 | 0.171459E+11 | ||||||||
Minimum of Months | 0.708182E+10 | 4091.67 | 21.67 | 11.16 | 0.123921E+10 | 868.27 | 13.00 | 11.10 | ||
Maximum of Months | 0.989453E+10 | 5724.55 | 34.42 | 20.11 | 0.157263E+10 | 995.52 | 32.00 | 20.11 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 170095.71 | 73.70 | 30-MAR-06:05 | 5.58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 170095.71 | |||
Minimum of Months | 0.00 | 0.00 | 5.58 | |
Maximum of Months | 170095.71 | 73.70 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66438499.63 | 1520.23 | 01-JAN-19:02 | 11.00 |
February | 41252291.56 | 1558.87 | 25-FEB-16:02 | 11.00 |
March | 82965259.18 | 1580.00 | 30-MAR-08:62 | 9.50 |
April | 10046261.80 | 619.28 | 11-APR-08:03 | 14.83 |
May | 5950742.98 | 627.38 | 28-MAY-08:03 | 18.17 |
June | 580128.50 | 517.39 | 05-JUN-08:03 | 18.17 |
July | 505060.59 | 664.18 | 23-JUL-08:05 | 23.33 |
August | 531276.00 | 646.21 | 19-AUG-08:05 | 22.33 |
September | 589330.40 | 538.87 | 20-SEP-08:03 | 16.33 |
October | 1077820.41 | 544.04 | 14-OCT-08:05 | 27.67 |
November | 10040119.04 | 851.78 | 24-NOV-16:03 | 15.83 |
December | 39667289.75 | 1091.74 | 12-DEC-19:02 | 9.67 |
Annual Sum or Average | 0.259644E+09 | |||
Minimum of Months | 505060.59 | 517.39 | 9.50 | |
Maximum of Months | 82965259.18 | 1580.00 | 27.67 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160926E+09 | 1570.27 | 03-JAN-09:02 | 11.33 |
February | 74604346.43 | 1554.81 | 25-FEB-16:02 | 11.00 |
March | 0.116602E+09 | 1580.71 | 30-MAR-08:62 | 9.50 |
April | 13053030.61 | 1246.77 | 01-APR-08:62 | 15.67 |
May | 5917911.66 | 618.11 | 14-MAY-08:03 | 15.17 |
June | 514791.92 | 535.47 | 02-JUN-08:03 | 18.17 |
July | 555614.09 | 482.10 | 22-JUL-08:05 | 21.17 |
August | 647915.98 | 643.94 | 19-AUG-08:05 | 22.33 |
September | 961356.97 | 582.10 | 03-SEP-08:03 | 18.33 |
October | 2307041.04 | 616.96 | 24-OCT-15:04 | 19.00 |
November | 39433164.10 | 1026.16 | 05-NOV-08:62 | 11.33 |
December | 0.116428E+09 | 1565.98 | 13-DEC-09:02 | 11.33 |
Annual Sum or Average | 0.531951E+09 | |||
Minimum of Months | 514791.92 | 482.10 | 9.50 | |
Maximum of Months | 0.160926E+09 | 1580.71 | 22.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3171908.80 | 446.12 | 10-JAN-16:02 | 13.83 |
February | 1051879.35 | 307.64 | 04-FEB-16:03 | 16.83 |
March | 1558425.91 | 447.82 | 30-MAR-08:62 | 9.50 |
April | 481420.43 | 279.41 | 28-APR-15:04 | 17.00 |
May | 567291.62 | 281.18 | 20-MAY-15:05 | 18.00 |
June | 175833.77 | 191.31 | 09-JUN-15:05 | 18.83 |
July | 75816.34 | 143.64 | 18-JUL-08:05 | 21.50 |
August | 214817.15 | 178.84 | 15-AUG-08:05 | 22.50 |
September | 291790.06 | 234.46 | 02-SEP-15:04 | 18.83 |
October | 351802.32 | 276.97 | 16-OCT-08:05 | 28.50 |
November | 1283943.67 | 296.31 | 04-NOV-15:03 | 16.58 |
December | 1613776.36 | 446.17 | 13-DEC-16:02 | 12.83 |
Annual Sum or Average | 10838705.78 | |||
Minimum of Months | 75816.34 | 143.64 | 9.50 | |
Maximum of Months | 3171908.80 | 447.82 | 28.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 65964712.22 | 1261.69 | 01-JAN-19:02 | 11.00 |
February | 50441101.47 | 1524.93 | 25-FEB-16:02 | 11.00 |
March | 93696044.26 | 1535.84 | 28-MAR-08:62 | 9.33 |
April | 9592168.33 | 671.23 | 15-APR-15:04 | 17.00 |
May | 7844372.80 | 533.81 | 06-MAY-18:03 | 15.67 |
June | 932270.67 | 477.65 | 09-JUN-18:03 | 16.83 |
July | 253075.62 | 307.82 | 05-JUL-18:05 | 17.83 |
August | 103696.85 | 287.46 | 01-AUG-18:05 | 17.83 |
September | 231089.56 | 364.42 | 18-SEP-15:05 | 19.83 |
October | 626693.19 | 336.68 | 06-OCT-15:05 | 21.00 |
November | 15066242.83 | 709.38 | 24-NOV-16:03 | 15.83 |
December | 46255042.28 | 1401.07 | 12-DEC-19:02 | 9.67 |
Annual Sum or Average | 0.291007E+09 | |||
Minimum of Months | 103696.85 | 287.46 | 9.33 | |
Maximum of Months | 93696044.26 | 1535.84 | 21.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153680E+09 | 1508.20 | 02-JAN-16:02 | 12.67 |
February | 94083253.74 | 1519.74 | 25-FEB-16:02 | 11.00 |
March | 0.130706E+09 | 1526.53 | 28-MAR-08:62 | 9.33 |
April | 14071284.42 | 716.12 | 22-APR-15:03 | 16.83 |
May | 8428651.45 | 521.38 | 06-MAY-18:03 | 15.67 |
June | 698137.69 | 461.98 | 07-JUN-15:05 | 19.00 |
July | 89076.48 | 278.29 | 12-JUL-18:05 | 18.83 |
August | 144526.14 | 308.81 | 27-AUG-18:05 | 17.67 |
September | 641580.17 | 464.38 | 24-SEP-15:05 | 18.83 |
October | 3130960.82 | 522.25 | 24-OCT-15:04 | 19.00 |
November | 53036317.86 | 770.10 | 14-NOV-16:03 | 15.83 |
December | 0.125429E+09 | 1499.47 | 13-DEC-16:02 | 12.83 |
Annual Sum or Average | 0.584139E+09 | |||
Minimum of Months | 89076.48 | 278.29 | 9.33 | |
Maximum of Months | 0.153680E+09 | 1526.53 | 19.00 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186812E+09 | 1847.02 | 03-JAN-09:02 | 11.33 |
February | 0.147956E+09 | 1887.64 | 25-FEB-16:02 | 11.00 |
March | 0.211131E+09 | 1904.50 | 30-MAR-08:62 | 9.50 |
April | 34716246.52 | 1615.16 | 01-APR-08:62 | 15.67 |
May | 26996450.56 | 802.29 | 12-MAY-15:05 | 15.83 |
June | 2134821.64 | 523.81 | 23-JUN-08:03 | 18.50 |
July | 479014.94 | 528.48 | 23-JUL-08:05 | 23.33 |
August | 538096.73 | 500.35 | 19-AUG-08:05 | 22.33 |
September | 674364.03 | 445.02 | 29-SEP-08:05 | 29.67 |
October | 11602761.68 | 716.36 | 24-OCT-15:04 | 19.00 |
November | 75425919.13 | 1023.39 | 24-NOV-09:02 | 14.17 |
December | 0.156488E+09 | 1850.36 | 13-DEC-09:02 | 11.33 |
Annual Sum or Average | 0.854954E+09 | |||
Minimum of Months | 479014.94 | 445.02 | 9.50 | |
Maximum of Months | 0.211131E+09 | 1904.50 | 29.67 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.385208E+09 | 1891.61 | 03-JAN-09:02 | 11.33 |
February | 0.244052E+09 | 1881.60 | 25-FEB-16:02 | 11.00 |
March | 0.287030E+09 | 1901.54 | 30-MAR-08:62 | 9.50 |
April | 46974798.56 | 1832.40 | 01-APR-08:62 | 15.67 |
May | 27331347.07 | 694.41 | 20-MAY-08:04 | 15.17 |
June | 2103036.57 | 524.92 | 08-JUN-15:05 | 18.00 |
July | 490810.84 | 575.58 | 23-JUL-08:05 | 23.33 |
August | 627608.12 | 497.23 | 19-AUG-08:05 | 22.33 |
September | 1291673.45 | 456.57 | 06-SEP-08:03 | 19.33 |
October | 28269139.95 | 1806.65 | 30-OCT-08:62 | 17.67 |
November | 0.175245E+09 | 1848.82 | 05-NOV-08:62 | 11.33 |
December | 0.340835E+09 | 1889.07 | 13-DEC-09:02 | 11.33 |
Annual Sum or Average | 0.153946E+10 | |||
Minimum of Months | 490810.84 | 456.57 | 9.50 | |
Maximum of Months | 0.385208E+09 | 1901.54 | 23.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9438391.51 | 242.33 | 01-JAN-16:05 | 12.67 |
February | 11952939.11 | 977.26 | 25-FEB-16:02 | 11.00 |
March | 38654349.03 | 990.07 | 28-MAR-08:62 | 9.33 |
April | 4694571.38 | 390.89 | 17-APR-15:05 | 17.33 |
May | 6744635.21 | 611.32 | 12-MAY-15:05 | 15.83 |
June | 568390.82 | 320.85 | 08-JUN-15:05 | 18.00 |
July | 405308.71 | 273.54 | 29-JUL-08:05 | 20.33 |
August | 312123.64 | 262.57 | 06-AUG-08:05 | 22.33 |
September | 123314.07 | 215.52 | 18-SEP-18:04 | 15.67 |
October | 328703.63 | 418.78 | 23-OCT-15:05 | 17.00 |
November | 447944.22 | 393.70 | 24-NOV-16:05 | 15.83 |
December | 5503750.80 | 197.09 | 13-DEC-04:30 | 7.00 |
Annual Sum or Average | 79174422.13 | |||
Minimum of Months | 123314.07 | 197.09 | 7.00 | |
Maximum of Months | 38654349.03 | 990.07 | 22.33 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.147273E+11 | 14185.34 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.132974E+11 | 14185.34 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.147727E+11 | 14185.34 | 01-MAR-20:10 | 0.127855E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.142280E+11 | 14185.34 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.147528E+11 | 14185.34 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.142932E+11 | 14185.34 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.146876E+11 | 14185.34 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.147784E+11 | 14185.34 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.142337E+11 | 14185.34 | 01-SEP-19:10 | 0.123352E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.147216E+11 | 14185.34 | 02-OCT-19:10 | 0.127549E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.142819E+11 | 14185.34 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.146876E+11 | 14185.34 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.173462E+12 | 0.150255E+12 | ||||
Minimum of Months | 0.132974E+11 | 14185.34 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.147784E+11 | 14185.34 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.731324E+09 | 704.41 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.660319E+09 | 704.41 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.733578E+09 | 704.41 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.706528E+09 | 704.41 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.732592E+09 | 704.41 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.709769E+09 | 704.41 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.729351E+09 | 704.41 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.733860E+09 | 704.41 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.706810E+09 | 704.41 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.731042E+09 | 704.41 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.709205E+09 | 704.41 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.729351E+09 | 704.41 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.861373E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.660319E+09 | 704.41 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.733860E+09 | 704.41 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.846876E+09 | 815.72 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.764651E+09 | 815.72 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.849486E+09 | 815.72 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.818162E+09 | 815.72 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.848344E+09 | 815.72 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.821915E+09 | 815.72 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.844592E+09 | 815.72 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.849812E+09 | 815.72 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.818489E+09 | 815.72 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.846549E+09 | 815.72 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.821262E+09 | 815.72 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.844592E+09 | 815.72 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.997473E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.764651E+09 | 815.72 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.849812E+09 | 815.72 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.141236E+10 | 1360.40 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.127524E+10 | 1360.40 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.141672E+10 | 1360.40 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.136448E+10 | 1360.40 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.141481E+10 | 1360.40 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.137074E+10 | 1360.40 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.140855E+10 | 1360.40 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.141726E+10 | 1360.40 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.136502E+10 | 1360.40 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.141182E+10 | 1360.40 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.136965E+10 | 1360.40 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.140855E+10 | 1360.40 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.166352E+11 | 0.124712E+11 | ||||
Minimum of Months | 0.127524E+10 | 1360.40 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.141726E+10 | 1360.40 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.236418E+09 | 227.72 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.213464E+09 | 227.72 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.237147E+09 | 227.72 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.228402E+09 | 227.72 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.236828E+09 | 227.72 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.229450E+09 | 227.72 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.235780E+09 | 227.72 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.237238E+09 | 227.72 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.228493E+09 | 227.72 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.236327E+09 | 227.72 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.229268E+09 | 227.72 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.235780E+09 | 227.72 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.278459E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.213464E+09 | 227.72 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.237238E+09 | 227.72 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.370859E+09 | 357.21 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.334852E+09 | 357.21 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.372002E+09 | 357.21 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.358285E+09 | 357.21 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.371502E+09 | 357.21 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.359929E+09 | 357.21 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.369859E+09 | 357.21 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.372145E+09 | 357.21 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.358428E+09 | 357.21 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.370717E+09 | 357.21 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.359643E+09 | 357.21 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.369859E+09 | 357.21 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.436808E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.334852E+09 | 357.21 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.372145E+09 | 357.21 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.158799E+10 | 1761.91 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.141502E+10 | 1761.91 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.155823E+10 | 1761.91 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.146440E+10 | 1761.91 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.148347E+10 | 1761.91 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.143200E+10 | 1761.91 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.147724E+10 | 1761.91 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.150429E+10 | 1761.91 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.149607E+10 | 1761.91 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.156731E+10 | 1761.91 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.153155E+10 | 1761.91 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.158133E+10 | 1761.91 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.180989E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.141502E+10 | 1761.91 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.158799E+10 | 1761.91 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104088E+11 | 10265.18 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.937997E+10 | 10265.18 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.104087E+11 | 10265.18 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.998899E+10 | 10265.18 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.103263E+11 | 10265.18 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.999821E+10 | 10265.18 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.102806E+11 | 10265.18 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.103603E+11 | 10265.18 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.100278E+11 | 10265.18 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.103893E+11 | 10265.18 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.100861E+11 | 10265.18 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.103787E+11 | 10265.18 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.122034E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.937997E+10 | 10265.18 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.104088E+11 | 10265.18 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85091918.49 | 76.99 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 76846309.13 | 76.99 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 84415649.14 | 76.99 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 82445007.08 | 76.99 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 84753783.81 | 76.99 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 81790910.76 | 76.99 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 85418966.65 | 76.99 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 84415649.14 | 76.99 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 82467180.11 | 76.99 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 85080831.98 | 76.99 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 82117958.92 | 76.99 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 85430053.17 | 76.99 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.100027E+10 | 0.300992E+10 | ||||
Minimum of Months | 76846309.13 | 76.99 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 85430053.17 | 76.99 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85115186.72 | 77.01 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 76867322.62 | 77.01 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 84438732.44 | 77.01 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 82467551.52 | 77.01 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 84776959.58 | 77.01 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 81813276.33 | 77.01 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 85442324.32 | 77.01 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 84438732.44 | 77.01 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 82489730.61 | 77.01 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 85104097.18 | 77.01 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 82140413.93 | 77.01 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 85453413.86 | 77.01 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.100055E+10 | 0.301074E+10 | ||||
Minimum of Months | 76867322.62 | 77.01 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 85453413.86 | 77.01 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.232638E+10 | 2240.78 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.210051E+10 | 2240.78 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.233355E+10 | 2240.78 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.224750E+10 | 2240.78 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.233041E+10 | 2240.78 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.225781E+10 | 2240.78 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.232011E+10 | 2240.78 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.233445E+10 | 2240.78 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.224840E+10 | 2240.78 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.232548E+10 | 2240.78 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.225602E+10 | 2240.78 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.232011E+10 | 2240.78 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.274007E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.210051E+10 | 2240.78 | 0.00 | 0.00 | |
Maximum of Months | 0.233445E+10 | 2240.78 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85115186.72 | 77.01 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 76867322.62 | 77.01 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 84438732.44 | 77.01 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 82467551.52 | 77.01 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 84776959.58 | 77.01 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 81813276.33 | 77.01 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 85442324.32 | 77.01 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 84438732.44 | 77.01 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 82489730.61 | 77.01 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 85104097.18 | 77.01 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 82140413.93 | 77.01 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 85453413.86 | 77.01 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.100055E+10 | 0.301074E+10 | ||||
Minimum of Months | 76867322.62 | 77.01 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 85453413.86 | 77.01 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302110E+10 | 3094.06 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.270209E+10 | 3094.06 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.298356E+10 | 3094.06 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.283147E+10 | 3094.06 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.289692E+10 | 3094.06 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.279538E+10 | 3094.06 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.287854E+10 | 3094.06 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.292152E+10 | 3094.06 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.286757E+10 | 3094.06 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.300238E+10 | 3094.06 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.291991E+10 | 3094.06 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.301516E+10 | 3094.06 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.348356E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.270209E+10 | 3094.06 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.302110E+10 | 3094.06 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302110E+10 | 3094.06 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.270209E+10 | 3094.06 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.298356E+10 | 3094.06 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.283147E+10 | 3094.06 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.289692E+10 | 3094.06 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.279538E+10 | 3094.06 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.287854E+10 | 3094.06 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.292152E+10 | 3094.06 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.286757E+10 | 3094.06 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.300238E+10 | 3094.06 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.291991E+10 | 3094.06 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.301516E+10 | 3094.06 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.348356E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.270209E+10 | 3094.06 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.302110E+10 | 3094.06 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113146E+10 | 1089.83 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.102161E+10 | 1089.83 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.113495E+10 | 1089.83 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.109310E+10 | 1089.83 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.113342E+10 | 1089.83 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.109811E+10 | 1089.83 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.112841E+10 | 1089.83 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.113539E+10 | 1089.83 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.109354E+10 | 1089.83 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.113103E+10 | 1089.83 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.109724E+10 | 1089.83 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.112841E+10 | 1089.83 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.133267E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.102161E+10 | 1089.83 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.113539E+10 | 1089.83 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.246211E+10 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.222306E+10 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.246970E+10 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.237864E+10 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.246638E+10 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.238954E+10 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.245547E+10 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.247065E+10 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.237958E+10 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.246116E+10 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.238765E+10 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.245547E+10 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.289994E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.222306E+10 | 2371.52 | 0.00 | 0.00 | |
Maximum of Months | 0.247065E+10 | 2371.52 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.147273E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.132974E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.147727E+11 | 0.127855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.142280E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.147528E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.142932E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.146876E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.147784E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.142337E+11 | 0.123352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.147216E+11 | 0.127549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.142819E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.146876E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.173462E+12 | 0.150255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.132974E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.147784E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.731324E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1038393.46 | 0.288313E+09 |
February | 0.179968E+10 | 0.660319E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72921.62 | 0.248346E+09 |
March | 0.199990E+10 | 0.733578E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288440E+09 |
April | 0.192973E+10 | 0.706528E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1261625.66 | 0.202562E+09 |
May | 0.199475E+10 | 0.732592E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 139530.17 | 0.188926E+09 |
June | 0.193394E+10 | 0.709769E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3052177.95 | 0.126852E+09 |
July | 0.199054E+10 | 0.729351E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9490531.89 | 95417358.36 |
August | 0.199896E+10 | 0.733860E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7854812.31 | 97633577.51 |
September | 0.192879E+10 | 0.706810E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8061177.02 | 0.132076E+09 |
October | 0.199148E+10 | 0.731042E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13977062.56 | 0.137482E+09 |
November | 0.192552E+10 | 0.709205E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 624448.73 | 0.246130E+09 |
December | 0.199054E+10 | 0.729351E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 395351.30 | 0.278766E+09 |
Annual Sum or Average | 0.234744E+11 | 0.861373E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45968032.69 | 0.233094E+10 |
Minimum of Months | 0.179968E+10 | 0.660319E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95417358.36 |
Maximum of Months | 0.199990E+10 | 0.733860E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13977062.56 | 0.288440E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.846876E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 758225.63 | 0.119297E+09 |
February | 0.208403E+10 | 0.764651E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 100611.29 | 0.105070E+09 |
March | 0.231589E+10 | 0.849486E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 121816.82 | 0.122735E+09 |
April | 0.223463E+10 | 0.818162E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 745605.55 | 90828083.45 |
May | 0.230993E+10 | 0.848344E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91804.52 | 89125243.98 |
June | 0.223950E+10 | 0.821915E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 709157.42 | 63807591.80 |
July | 0.230505E+10 | 0.844592E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3211081.49 | 49642874.31 |
August | 0.231480E+10 | 0.849812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3563588.07 | 48251706.30 |
September | 0.223354E+10 | 0.818489E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3222857.34 | 59796706.93 |
October | 0.230614E+10 | 0.846549E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6431651.28 | 61874726.80 |
November | 0.222975E+10 | 0.821262E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 529449.96 | 0.103976E+09 |
December | 0.230505E+10 | 0.844592E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 592127.03 | 0.116171E+09 |
Annual Sum or Average | 0.271834E+11 | 0.997473E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20077976.40 | 0.103057E+10 |
Minimum of Months | 0.208403E+10 | 0.764651E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91804.52 | 48251706.30 |
Maximum of Months | 0.231589E+10 | 0.849812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6431651.28 | 0.122735E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.141236E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2546882.88 | 0.257929E+09 |
February | 0.440737E+09 | 0.127524E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 399114.61 | 0.228203E+09 |
March | 0.489771E+09 | 0.141672E+10 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 669590.68 | 0.268626E+09 |
April | 0.472586E+09 | 0.136448E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2478283.81 | 0.195983E+09 |
May | 0.488511E+09 | 0.141481E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 296519.26 | 0.197713E+09 |
June | 0.473617E+09 | 0.137074E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1446420.19 | 0.142647E+09 |
July | 0.487480E+09 | 0.140855E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7283837.18 | 0.109846E+09 |
August | 0.489542E+09 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8871379.86 | 0.104040E+09 |
September | 0.472357E+09 | 0.136502E+10 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8322845.61 | 0.128005E+09 |
October | 0.487709E+09 | 0.141182E+10 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16443496.55 | 0.135001E+09 |
November | 0.471555E+09 | 0.136965E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1968758.55 | 0.224891E+09 |
December | 0.487480E+09 | 0.140855E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2479664.89 | 0.250922E+09 |
Annual Sum or Average | 0.574883E+10 | 0.166352E+11 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53206794.06 | 0.224381E+10 |
Minimum of Months | 0.440737E+09 | 0.127524E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 296519.26 | 0.104040E+09 |
Maximum of Months | 0.489771E+09 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16443496.55 | 0.268626E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.236418E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1479296.60 | 0.146236E+09 |
February | 0.339028E+09 | 0.213464E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 237150.32 | 0.129057E+09 |
March | 0.376747E+09 | 0.237147E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 392646.72 | 0.152038E+09 |
April | 0.363528E+09 | 0.228402E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1458931.33 | 0.110332E+09 |
May | 0.375778E+09 | 0.236828E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 195199.04 | 0.110922E+09 |
June | 0.364321E+09 | 0.229450E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 942408.51 | 79412600.27 |
July | 0.374985E+09 | 0.235780E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4415580.84 | 60658109.62 |
August | 0.376571E+09 | 0.237238E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5342705.06 | 57444006.33 |
September | 0.363352E+09 | 0.228493E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4892357.93 | 71362558.48 |
October | 0.375161E+09 | 0.236327E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9552244.55 | 75317151.49 |
November | 0.362735E+09 | 0.229268E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1136254.90 | 0.127139E+09 |
December | 0.374985E+09 | 0.235780E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1434106.14 | 0.142087E+09 |
Annual Sum or Average | 0.442217E+10 | 0.278459E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31478881.94 | 0.126200E+10 |
Minimum of Months | 0.339028E+09 | 0.213464E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 195199.04 | 57444006.33 |
Maximum of Months | 0.376747E+09 | 0.237238E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9552244.55 | 0.152038E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.370859E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 2619921.33 | 0.390754E+09 |
February | 0.139600E+10 | 0.334852E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 368669.18 | 0.345827E+09 |
March | 0.155131E+10 | 0.372002E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 473010.13 | 0.408715E+09 |
April | 0.149688E+10 | 0.358285E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 2597591.39 | 0.293374E+09 |
May | 0.154732E+10 | 0.371502E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 400305.54 | 0.290552E+09 |
June | 0.150015E+10 | 0.359929E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 3103299.12 | 0.201309E+09 |
July | 0.154405E+10 | 0.369859E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 13702254.85 | 0.148621E+09 |
August | 0.155059E+10 | 0.372145E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 16309419.53 | 0.141875E+09 |
September | 0.149615E+10 | 0.358428E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 12693254.67 | 0.180199E+09 |
October | 0.154478E+10 | 0.370717E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 24459493.61 | 0.187858E+09 |
November | 0.149361E+10 | 0.359643E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 2158144.06 | 0.333613E+09 |
December | 0.154405E+10 | 0.369859E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 2249086.94 | 0.375754E+09 |
Annual Sum or Average | 0.182090E+11 | 0.436808E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 81134450.35 | 0.329845E+10 |
Minimum of Months | 0.139600E+10 | 0.334852E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 368669.18 | 0.141875E+09 |
Maximum of Months | 0.155131E+10 | 0.372145E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 24459493.61 | 0.408715E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.158799E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1925503.71 | 0.719253E+09 |
February | 0.236489E+11 | 0.141502E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 152115.54 | 0.623623E+09 |
March | 0.262800E+11 | 0.155823E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719089E+09 |
April | 0.253579E+11 | 0.146440E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2273405.77 | 0.525967E+09 |
May | 0.262123E+11 | 0.148347E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 283461.42 | 0.500884E+09 |
June | 0.254132E+11 | 0.143200E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5589332.35 | 0.354956E+09 |
July | 0.261570E+11 | 0.147724E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19861921.70 | 0.274005E+09 |
August | 0.262677E+11 | 0.150429E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17304771.33 | 0.273417E+09 |
September | 0.253456E+11 | 0.149607E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16907842.64 | 0.352067E+09 |
October | 0.261693E+11 | 0.156731E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30633246.70 | 0.365141E+09 |
November | 0.253025E+11 | 0.153155E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1381369.97 | 0.623527E+09 |
December | 0.261570E+11 | 0.158133E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 870813.12 | 0.698436E+09 |
Annual Sum or Average | 0.308468E+12 | 0.180989E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97183784.24 | 0.603036E+10 |
Minimum of Months | 0.236489E+11 | 0.141502E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273417E+09 |
Maximum of Months | 0.262800E+11 | 0.158799E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30633246.70 | 0.719253E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.104088E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7787640.83 | 0.207450E+10 |
February | 0.702046E+11 | 0.937997E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 952925.27 | 0.182330E+10 |
March | 0.780153E+11 | 0.104087E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 795061.10 | 0.211980E+10 |
April | 0.752779E+11 | 0.998899E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8882238.87 | 0.156205E+10 |
May | 0.778146E+11 | 0.103263E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1112364.40 | 0.153909E+10 |
June | 0.754422E+11 | 0.999821E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9627842.58 | 0.110613E+10 |
July | 0.776503E+11 | 0.102806E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48654559.23 | 0.850739E+09 |
August | 0.779788E+11 | 0.103603E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52327067.23 | 0.821696E+09 |
September | 0.752414E+11 | 0.100278E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49614356.35 | 0.103105E+10 |
October | 0.776868E+11 | 0.103893E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94518363.17 | 0.107245E+10 |
November | 0.751137E+11 | 0.100861E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5221172.47 | 0.180376E+10 |
December | 0.776503E+11 | 0.103787E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4823787.21 | 0.201829E+10 |
Annual Sum or Average | 0.915726E+12 | 0.122034E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284317E+09 | 0.178229E+11 |
Minimum of Months | 0.702046E+11 | 0.937997E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 795061.10 | 0.821696E+09 |
Maximum of Months | 0.780153E+11 | 0.104088E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94518363.17 | 0.211980E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1162477.92 | 0.158137E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 197222.35 | 0.138140E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 194069.14 | 0.164760E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1069346.00 | 0.114570E+09 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93118.80 | 0.111720E+09 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1371196.84 | 72066878.91 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5835293.27 | 47630699.61 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6843292.57 | 44639577.51 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6448376.19 | 63855421.14 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11320657.97 | 65376292.28 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 869660.60 | 0.132437E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 961197.02 | 0.151138E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36365908.66 | 0.126447E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93118.80 | 44639577.51 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11320657.97 | 0.164760E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1614477.14 | 0.153577E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 295085.69 | 0.135206E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 336280.38 | 0.162231E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1335340.30 | 0.113107E+09 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 112610.73 | 0.111187E+09 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1426492.06 | 71964025.55 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5952043.17 | 47554478.65 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7212756.49 | 44362405.13 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6652794.19 | 62580211.70 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11993962.26 | 64088534.74 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1215914.22 | 0.129283E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1614635.43 | 0.146959E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39762392.08 | 0.124210E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 112610.73 | 44362405.13 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11993962.26 | 0.162231E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 85091918.49 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 162541.96 | 51490938.51 |
February | 0.00 | 76846309.13 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20887.29 | 44711757.20 |
March | 0.00 | 84415649.14 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14509.61 | 51709301.55 |
April | 0.00 | 82445007.08 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 152470.45 | 38171067.74 |
May | 0.00 | 84753783.81 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8168.14 | 34816875.68 |
June | 0.00 | 81790910.76 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 147467.56 | 23537436.27 |
July | 0.00 | 85418966.65 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 860004.37 | 19145516.58 |
August | 0.00 | 84415649.14 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 980386.66 | 19140997.42 |
September | 0.00 | 82467180.11 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1315516.18 | 24878560.52 |
October | 0.00 | 85080831.98 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2519321.16 | 25554684.51 |
November | 0.00 | 82117958.92 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 156818.98 | 44658091.84 |
December | 0.00 | 85430053.17 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 137984.67 | 50018915.31 |
Annual Sum or Average | 0.00 | 0.100027E+10 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6476077.03 | 0.427834E+09 |
Minimum of Months | 0.00 | 76846309.13 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8168.14 | 19140997.42 |
Maximum of Months | 0.00 | 85430053.17 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2519321.16 | 51709301.55 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 85115186.72 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 625011.50 | 42467750.91 |
February | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 120388.34 | 37409313.77 |
March | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 174119.51 | 45021840.26 |
April | 0.293479E+09 | 82467551.52 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 572825.87 | 30744438.69 |
May | 0.303504E+09 | 84776959.58 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 116582.67 | 30068135.08 |
June | 0.293842E+09 | 81813276.33 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 693837.33 | 19224907.50 |
July | 0.303141E+09 | 85442324.32 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2292732.46 | 12641018.32 |
August | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2858295.67 | 11889979.28 |
September | 0.293479E+09 | 82489730.61 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2139587.00 | 16484378.88 |
October | 0.303322E+09 | 85104097.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3907461.89 | 17324829.53 |
November | 0.293661E+09 | 82140413.93 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 506826.68 | 35291243.14 |
December | 0.303141E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 691275.18 | 40493296.45 |
Annual Sum or Average | 0.357224E+10 | 0.100055E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14698944.11 | 0.339061E+09 |
Minimum of Months | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 116582.67 | 11889979.28 |
Maximum of Months | 0.303685E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3907461.89 | 45021840.26 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1092940.88 | 0.159066E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 188940.39 | 0.138642E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 173829.39 | 0.165653E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 943795.00 | 0.115647E+09 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 88921.71 | 0.112536E+09 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1144643.68 | 72465482.32 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5600389.72 | 48338317.59 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6551309.27 | 45132287.33 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6394614.93 | 63991087.85 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11235400.03 | 65733443.74 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 846558.28 | 0.132919E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 933540.76 | 0.151778E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35194884.02 | 0.127190E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 88921.71 | 45132287.33 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11235400.03 | 0.165653E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1669897.07 | 0.153468E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 273573.60 | 0.134970E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 250589.55 | 0.162883E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1005873.25 | 0.114195E+09 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89435.78 | 0.111988E+09 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1145737.26 | 72438037.45 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5602800.09 | 48335175.06 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6587586.48 | 45006222.47 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6452569.00 | 62725265.56 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11530197.55 | 64296948.99 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1278953.10 | 0.128247E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1636539.37 | 0.146286E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37523752.08 | 0.124484E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89435.78 | 45006222.47 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11530197.55 | 0.162883E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.232638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1555955.11 | 0.204042E+09 |
February | 0.348285E+10 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215277.83 | 0.180338E+09 |
March | 0.387034E+10 | 0.233355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293673.90 | 0.210304E+09 |
April | 0.373454E+10 | 0.224750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1526628.80 | 0.153730E+09 |
May | 0.386038E+10 | 0.233041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150083.43 | 0.152612E+09 |
June | 0.374269E+10 | 0.225781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1102862.92 | 0.107775E+09 |
July | 0.385223E+10 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5276267.15 | 83156579.96 |
August | 0.386853E+10 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5754561.26 | 80994694.30 |
September | 0.373273E+10 | 0.224840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5947201.58 | 0.100962E+09 |
October | 0.385404E+10 | 0.232548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11393554.16 | 0.107339E+09 |
November | 0.372639E+10 | 0.225602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1094837.42 | 0.179021E+09 |
December | 0.385223E+10 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1269532.25 | 0.200218E+09 |
Annual Sum or Average | 0.454292E+11 | 0.274007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35580435.82 | 0.176049E+10 |
Minimum of Months | 0.348285E+10 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150083.43 | 80994694.30 |
Maximum of Months | 0.387034E+10 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11393554.16 | 0.210304E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1136360.03 | 0.158324E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 193598.30 | 0.138095E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 179467.72 | 0.164932E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 997626.99 | 0.115394E+09 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80856.17 | 0.112593E+09 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1189798.26 | 72956178.92 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5535103.52 | 48491098.49 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6538025.66 | 45342007.83 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6344938.65 | 64583076.16 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11165683.54 | 65788610.08 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 846235.75 | 0.132659E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 935353.42 | 0.151204E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35143048.02 | 0.127036E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80856.17 | 45342007.83 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11165683.54 | 0.164932E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1643644.60 | 0.153109E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 313062.97 | 0.134778E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 308576.21 | 0.162235E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1200971.99 | 0.113904E+09 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85552.20 | 0.112089E+09 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1214751.70 | 72866714.90 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5595623.44 | 48430801.66 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6783646.15 | 45083444.64 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6534697.18 | 63341132.21 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11889245.44 | 64377516.62 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1250467.44 | 0.128988E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1713346.22 | 0.146345E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38533585.54 | 0.124555E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85552.20 | 45083444.64 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11889245.44 | 0.162235E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 85115186.72 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 501234.98 | 82709884.91 |
February | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90264.99 | 72112689.38 |
March | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80248.13 | 85665613.46 |
April | 0.293479E+09 | 82467551.52 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 473556.20 | 59291254.24 |
May | 0.303504E+09 | 84776959.58 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41929.96 | 57167058.42 |
June | 0.293842E+09 | 81813276.33 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 656090.35 | 36699450.80 |
July | 0.303141E+09 | 85442324.32 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2893973.98 | 24432791.42 |
August | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3327001.19 | 23002450.37 |
September | 0.293479E+09 | 82489730.61 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3225075.85 | 33068685.42 |
October | 0.303322E+09 | 85104097.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5605478.76 | 34103621.04 |
November | 0.293661E+09 | 82140413.93 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 402330.85 | 69227969.11 |
December | 0.303141E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 444002.36 | 79037969.89 |
Annual Sum or Average | 0.357224E+10 | 0.100055E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17741187.59 | 0.656519E+09 |
Minimum of Months | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41929.96 | 23002450.37 |
Maximum of Months | 0.303685E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5605478.76 | 85665613.46 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.302110E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1298947.97 | 0.485547E+09 |
February | 0.415303E+11 | 0.270209E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 199829.51 | 0.432812E+09 |
March | 0.461508E+11 | 0.298356E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53575.80 | 0.509889E+09 |
April | 0.445315E+11 | 0.283147E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 897987.03 | 0.379777E+09 |
May | 0.460320E+11 | 0.289692E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24700.82 | 0.380334E+09 |
June | 0.446286E+11 | 0.279538E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 258385.76 | 0.275627E+09 |
July | 0.459349E+11 | 0.287854E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4932742.29 | 0.210617E+09 |
August | 0.461292E+11 | 0.292152E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5808709.05 | 0.200422E+09 |
September | 0.445099E+11 | 0.286757E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10018271.05 | 0.249118E+09 |
October | 0.459565E+11 | 0.300238E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20068971.26 | 0.254484E+09 |
November | 0.444343E+11 | 0.291991E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1146875.84 | 0.420822E+09 |
December | 0.459349E+11 | 0.301516E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1188232.80 | 0.468890E+09 |
Annual Sum or Average | 0.541708E+12 | 0.348356E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 45897229.17 | 0.426834E+10 |
Minimum of Months | 0.415303E+11 | 0.270209E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24700.82 | 0.200422E+09 |
Maximum of Months | 0.461508E+11 | 0.302110E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20068971.26 | 0.509889E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.302110E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 999025.62 | 0.491435E+09 |
February | 0.415303E+11 | 0.270209E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 154746.51 | 0.438052E+09 |
March | 0.461508E+11 | 0.298356E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9437.16 | 0.516029E+09 |
April | 0.445315E+11 | 0.283147E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 762461.66 | 0.383487E+09 |
May | 0.460320E+11 | 0.289692E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4770.49 | 0.383834E+09 |
June | 0.446286E+11 | 0.279538E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131102.57 | 0.277906E+09 |
July | 0.459349E+11 | 0.287854E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4476567.54 | 0.211898E+09 |
August | 0.461292E+11 | 0.292152E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5207387.17 | 0.201695E+09 |
September | 0.445099E+11 | 0.286757E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9878675.08 | 0.251394E+09 |
October | 0.459565E+11 | 0.300238E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19469234.16 | 0.256597E+09 |
November | 0.444343E+11 | 0.291991E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 984471.93 | 0.425534E+09 |
December | 0.459349E+11 | 0.301516E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 894343.99 | 0.474209E+09 |
Annual Sum or Average | 0.541708E+12 | 0.348356E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 42972223.88 | 0.431207E+10 |
Minimum of Months | 0.415303E+11 | 0.270209E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4770.49 | 0.201695E+09 |
Maximum of Months | 0.461508E+11 | 0.302110E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19469234.16 | 0.516029E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113146E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 603124.74 | 0.437887E+09 |
February | 0.369574E+10 | 0.102161E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 79948.47 | 0.390787E+09 |
March | 0.410691E+10 | 0.113495E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459292E+09 |
April | 0.396281E+10 | 0.109310E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 607454.29 | 0.340070E+09 |
May | 0.409635E+10 | 0.113342E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339976E+09 |
June | 0.397146E+10 | 0.109811E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 43381.92 | 0.245898E+09 |
July | 0.408770E+10 | 0.112841E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3742074.60 | 0.186933E+09 |
August | 0.410499E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 4236813.68 | 0.178187E+09 |
September | 0.396089E+10 | 0.109354E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 8799105.38 | 0.223111E+09 |
October | 0.408962E+10 | 0.113103E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 16669089.19 | 0.227041E+09 |
November | 0.395417E+10 | 0.109724E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 745058.27 | 0.378857E+09 |
December | 0.408770E+10 | 0.112841E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 451028.56 | 0.422640E+09 |
Annual Sum or Average | 0.482060E+11 | 0.133267E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 35977079.09 | 0.383068E+10 |
Minimum of Months | 0.369574E+10 | 0.102161E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178187E+09 |
Maximum of Months | 0.410691E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 16669089.19 | 0.459292E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.246211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2276558.52 | 0.353062E+09 |
February | 0.368610E+10 | 0.222306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331289.27 | 0.310142E+09 |
March | 0.409620E+10 | 0.246970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300640.50 | 0.367546E+09 |
April | 0.395248E+10 | 0.237864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1647484.62 | 0.271781E+09 |
May | 0.408566E+10 | 0.246638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71376.61 | 0.269046E+09 |
June | 0.396110E+10 | 0.238954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 717539.49 | 0.193592E+09 |
July | 0.407704E+10 | 0.245547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6386239.82 | 0.150602E+09 |
August | 0.409429E+10 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6854626.71 | 0.145318E+09 |
September | 0.395056E+10 | 0.237958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9694008.62 | 0.178095E+09 |
October | 0.407896E+10 | 0.246116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18513639.92 | 0.183888E+09 |
November | 0.394385E+10 | 0.238765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1584828.95 | 0.305479E+09 |
December | 0.407704E+10 | 0.245547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1800943.64 | 0.340892E+09 |
Annual Sum or Average | 0.480803E+11 | 0.289994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50179176.67 | 0.306944E+10 |
Minimum of Months | 0.368610E+10 | 0.222306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71376.61 | 0.145318E+09 |
Maximum of Months | 0.409620E+10 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18513639.92 | 0.367546E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 14185.34 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 14185.34 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 14185.34 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 14185.34 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 14185.34 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 14185.34 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 14185.34 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 14185.34 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 14185.34 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 14185.34 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 14185.34 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 14185.34 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 14185.34 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 14185.34 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 704.41 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 17-JAN-11:55 | 250.88 | 08-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 704.41 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.85 | 01-FEB-11:55 | 196.97 | 04-FEB-05:55 |
March | 1169.53 | 01-MAR-00:10 | 704.41 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 210.81 | 08-MAR-02:00 |
April | 1169.53 | 01-APR-00:10 | 704.41 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.96 | 30-APR-10:55 | 170.87 | 01-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 704.41 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.24 | 03-MAY-12:00 | 158.99 | 15-MAY-05:00 |
June | 1169.53 | 01-JUN-00:10 | 704.41 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.61 | 29-JUN-10:55 | 121.18 | 13-JUN-04:00 |
July | 1169.53 | 01-JUL-00:10 | 704.41 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.31 | 19-JUL-10:55 | 101.71 | 06-JUL-01:00 |
August | 1169.53 | 01-AUG-00:10 | 704.41 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.60 | 14-AUG-10:55 | 92.40 | 28-AUG-03:00 |
September | 1169.53 | 01-SEP-00:10 | 704.41 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.69 | 29-SEP-10:55 | 122.75 | 20-SEP-03:00 |
October | 1169.53 | 01-OCT-23:10 | 704.41 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.56 | 16-OCT-10:55 | 149.72 | 30-OCT-03:00 |
November | 1169.53 | 01-NOV-00:10 | 704.41 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.19 | 19-NOV-13:00 | 187.90 | 29-NOV-23:00 |
December | 1169.53 | 01-DEC-00:10 | 704.41 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.02 | 16-DEC-13:00 | 197.46 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 704.41 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.40 | |||||
Maximum of Months | 1169.53 | 704.41 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 143.56 | 250.88 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 815.72 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 18-JAN-13:00 | 97.88 | 08-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 815.72 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 01-FEB-11:55 | 84.60 | 04-FEB-05:55 |
March | 1354.32 | 01-MAR-00:10 | 815.72 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.25 | 11-MAR-11:50 | 86.71 | 08-MAR-02:00 |
April | 1354.32 | 01-APR-00:10 | 815.72 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.77 | 26-APR-13:00 | 70.68 | 01-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 815.72 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 | 03-MAY-12:00 | 70.16 | 19-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 815.72 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.62 | 29-JUN-10:55 | 55.44 | 13-JUN-04:40 |
July | 1354.32 | 01-JUL-00:10 | 815.72 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.46 | 19-JUL-10:55 | 48.28 | 06-JUL-01:00 |
August | 1354.32 | 01-AUG-00:10 | 815.72 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.31 | 14-AUG-10:55 | 43.26 | 28-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 815.72 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.39 | 29-SEP-10:55 | 56.43 | 20-SEP-03:00 |
October | 1354.32 | 01-OCT-23:10 | 815.72 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.04 | 16-OCT-10:55 | 66.36 | 27-OCT-04:30 |
November | 1354.32 | 01-NOV-00:10 | 815.72 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.10 | 19-NOV-13:00 | 80.29 | 29-NOV-23:00 |
December | 1354.32 | 01-DEC-00:10 | 815.72 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.14 | 16-DEC-13:00 | 84.14 | 03-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 815.72 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 | 43.26 | |||||
Maximum of Months | 1354.32 | 815.72 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 59.04 | 97.88 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 1360.40 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.90 | 13-JAN-14:00 | 228.85 | 08-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 1360.40 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.15 | 01-FEB-11:55 | 189.75 | 04-FEB-05:55 |
March | 286.42 | 01-MAR-00:10 | 1360.40 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.36 | 11-MAR-11:55 | 193.51 | 08-MAR-02:00 |
April | 286.42 | 01-APR-00:10 | 1360.40 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.16 | 26-APR-13:00 | 157.03 | 01-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 1360.40 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.70 | 03-MAY-12:00 | 157.92 | 27-MAY-03:00 |
June | 286.42 | 01-JUN-00:10 | 1360.40 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.20 | 29-JUN-10:55 | 124.84 | 13-JUN-04:40 |
July | 286.42 | 01-JUL-00:10 | 1360.40 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.71 | 19-JUL-10:55 | 108.21 | 06-JUL-01:00 |
August | 286.42 | 01-AUG-00:10 | 1360.40 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.13 | 14-AUG-10:55 | 96.22 | 28-AUG-07:00 |
September | 286.42 | 01-SEP-00:10 | 1360.40 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.20 | 29-SEP-10:55 | 124.24 | 20-SEP-03:00 |
October | 286.42 | 01-OCT-23:10 | 1360.40 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.61 | 16-OCT-10:55 | 148.96 | 12-OCT-06:00 |
November | 286.42 | 01-NOV-00:10 | 1360.40 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.88 | 19-NOV-13:00 | 177.53 | 29-NOV-23:00 |
December | 286.42 | 01-DEC-00:10 | 1360.40 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.46 | 16-DEC-13:00 | 190.27 | 03-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 17.70 | 96.22 | |||||
Maximum of Months | 286.42 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 140.61 | 228.85 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 227.72 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.85 | 13-JAN-14:00 | 132.03 | 08-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 227.72 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.79 | 01-FEB-11:55 | 109.26 | 04-FEB-05:55 |
March | 220.32 | 01-MAR-00:10 | 227.72 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.36 | 11-MAR-11:50 | 110.95 | 08-MAR-02:00 |
April | 220.32 | 01-APR-00:10 | 227.72 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.08 | 26-APR-13:00 | 89.93 | 01-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 227.72 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.48 | 03-MAY-12:00 | 90.38 | 27-MAY-03:00 |
June | 220.32 | 01-JUN-00:10 | 227.72 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 | 29-JUN-10:55 | 71.37 | 13-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 227.72 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.82 | 19-JUL-10:55 | 61.42 | 06-JUL-01:00 |
August | 220.32 | 01-AUG-00:10 | 227.72 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 14-AUG-10:55 | 53.97 | 24-AUG-02:00 |
September | 220.32 | 01-SEP-00:10 | 227.72 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.63 | 29-SEP-10:55 | 71.26 | 20-SEP-03:00 |
October | 220.32 | 01-OCT-23:10 | 227.72 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.77 | 16-OCT-10:55 | 84.72 | 27-OCT-04:20 |
November | 220.32 | 01-NOV-00:10 | 227.72 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 19-NOV-13:00 | 99.66 | 29-NOV-23:00 |
December | 220.32 | 01-DEC-00:10 | 227.72 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.43 | 16-DEC-13:00 | 108.40 | 03-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 227.72 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 10.48 | 53.97 | |||||
Maximum of Months | 220.32 | 227.72 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 80.77 | 132.03 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 357.21 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 67.14 | 14-JAN-11:50 | 312.43 | 08-JAN-07:00 |
February | 907.20 | 01-FEB-00:10 | 357.21 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 60.30 | 01-FEB-11:55 | 264.99 | 09-FEB-06:50 |
March | 907.20 | 01-MAR-00:10 | 357.21 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 39.31 | 11-MAR-11:50 | 280.01 | 30-MAR-06:10 |
April | 907.20 | 01-APR-00:10 | 357.21 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 65.63 | 26-APR-13:00 | 238.89 | 01-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 357.21 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 27.81 | 04-MAY-12:00 | 228.79 | 15-MAY-05:10 |
June | 907.20 | 01-JUN-00:10 | 357.21 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 52.86 | 29-JUN-10:50 | 185.75 | 13-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 357.21 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 94.47 | 19-JUL-10:50 | 144.39 | 08-JUL-24:00 |
August | 907.20 | 01-AUG-00:10 | 357.21 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 94.75 | 14-AUG-10:50 | 147.79 | 28-AUG-07:00 |
September | 907.20 | 01-SEP-00:10 | 357.21 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 202.93 | 29-SEP-10:50 | 179.13 | 20-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 357.21 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 214.36 | 16-OCT-10:50 | 226.82 | 12-OCT-06:00 |
November | 907.20 | 01-NOV-00:10 | 357.21 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 65.51 | 19-NOV-13:10 | 259.59 | 23-NOV-22:00 |
December | 907.20 | 01-DEC-00:10 | 357.21 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 57.17 | 16-DEC-13:00 | 281.93 | 22-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 27.81 | 144.39 | ||||||
Maximum of Months | 907.20 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 214.36 | 312.43 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1761.91 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.44 | 17-JAN-11:55 | 554.53 | 08-JAN-07:00 |
February | 15368.40 | 01-FEB-00:10 | 1761.91 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.53 | 01-FEB-11:55 | 493.56 | 04-FEB-05:55 |
March | 15368.40 | 01-MAR-00:10 | 1761.91 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 499.17 | 08-MAR-02:00 |
April | 15368.40 | 01-APR-00:10 | 1761.91 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.43 | 26-APR-13:00 | 405.24 | 01-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 1761.91 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.08 | 03-MAY-12:00 | 405.47 | 19-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1761.91 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.76 | 29-JUN-10:50 | 326.48 | 13-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1761.91 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.35 | 19-JUL-10:55 | 278.67 | 06-JUL-01:00 |
August | 15368.40 | 01-AUG-00:10 | 1761.91 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.16 | 14-AUG-10:55 | 257.14 | 28-AUG-03:00 |
September | 15368.40 | 01-SEP-00:10 | 1761.91 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.34 | 29-SEP-10:55 | 331.96 | 20-SEP-03:00 |
October | 15368.40 | 01-OCT-23:10 | 1761.91 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 317.36 | 16-OCT-10:55 | 392.59 | 30-OCT-03:00 |
November | 15368.40 | 01-NOV-00:10 | 1761.91 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.61 | 19-NOV-13:00 | 459.89 | 29-NOV-23:00 |
December | 15368.40 | 01-DEC-00:10 | 1761.91 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.92 | 16-DEC-13:00 | 488.01 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1761.91 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.14 | |||||
Maximum of Months | 15368.40 | 1761.91 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 317.36 | 554.53 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 10265.18 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.12 | 13-JAN-14:00 | 1639.97 | 08-JAN-07:00 |
February | 45622.98 | 01-FEB-00:10 | 10265.18 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.89 | 01-FEB-11:55 | 1448.78 | 04-FEB-05:55 |
March | 45622.98 | 01-MAR-00:10 | 10265.18 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.84 | 11-MAR-11:50 | 1475.99 | 08-MAR-02:00 |
April | 45622.98 | 01-APR-00:10 | 10265.18 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 306.52 | 26-APR-13:00 | 1219.14 | 01-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 10265.18 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.40 | 03-MAY-12:00 | 1205.11 | 19-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 10265.18 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.99 | 29-JUN-10:55 | 974.61 | 13-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 10265.18 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 396.25 | 19-JUL-10:55 | 830.05 | 06-JUL-01:00 |
August | 45622.98 | 01-AUG-00:10 | 10265.18 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 389.59 | 14-AUG-10:55 | 750.60 | 24-AUG-02:00 |
September | 45622.98 | 01-SEP-00:10 | 10265.18 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 898.72 | 29-SEP-10:55 | 975.31 | 20-SEP-03:00 |
October | 45622.98 | 01-OCT-23:10 | 10265.18 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 936.63 | 16-OCT-10:55 | 1145.20 | 27-OCT-04:40 |
November | 45622.98 | 01-NOV-00:10 | 10265.18 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.95 | 19-NOV-13:00 | 1316.10 | 23-NOV-22:00 |
December | 45622.98 | 01-DEC-00:10 | 10265.18 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.48 | 16-DEC-13:00 | 1430.91 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 10265.18 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 69.84 | 750.60 | |||||
Maximum of Months | 45622.98 | 10265.18 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 936.63 | 1639.97 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 | 14-JAN-11:00 | 146.71 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 01-FEB-10:00 | 115.41 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 11-MAR-11:00 | 123.45 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.70 | 30-APR-10:00 | 100.25 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 03-MAY-10:00 | 93.35 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 30-JUN-10:00 | 71.39 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 | 19-JUL-10:00 | 56.57 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.71 | 15-AUG-10:00 | 51.47 | 28-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.14 | 29-SEP-10:00 | 70.90 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.32 | 16-OCT-10:00 | 85.84 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.26 | 19-NOV-10:00 | 100.72 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.32 | 05-DEC-10:00 | 115.70 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 51.47 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 89.32 | 146.71 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 | 14-JAN-11:00 | 146.70 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.16 | 01-FEB-11:55 | 115.40 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 11-MAR-11:00 | 123.44 | 08-MAR-02:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.79 | 30-APR-10:02 | 100.25 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 03-MAY-10:00 | 93.35 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 30-JUN-10:00 | 71.39 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 | 19-JUL-10:00 | 56.57 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 | 15-AUG-10:00 | 50.99 | 28-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.14 | 29-SEP-10:00 | 70.89 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.84 | 16-OCT-10:01 | 85.83 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.26 | 19-NOV-10:00 | 100.71 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 | 05-DEC-10:00 | 115.69 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 50.99 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 89.84 | 146.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 76.99 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.88 | 14-JAN-11:00 | 41.00 | 08-JAN-07:00 |
February | 0.00 | 01-FEB-00:10 | 76.99 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.86 | 01-FEB-11:55 | 34.29 | 04-FEB-05:55 |
March | 0.00 | 01-MAR-00:10 | 76.99 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 | 11-MAR-11:05 | 35.11 | 08-MAR-02:00 |
April | 0.00 | 01-APR-00:10 | 76.99 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.69 | 26-APR-13:00 | 27.40 | 15-APR-22:00 |
May | 0.00 | 01-MAY-00:10 | 76.99 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 | 03-MAY-12:50 | 26.24 | 27-MAY-03:00 |
June | 0.00 | 01-JUN-00:10 | 76.99 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 | 29-JUN-10:55 | 20.66 | 12-JUN-21:00 |
July | 0.00 | 01-JUL-00:10 | 76.99 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.51 | 19-JUL-12:00 | 18.32 | 06-JUL-01:00 |
August | 0.00 | 01-AUG-00:10 | 76.99 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.53 | 18-AUG-12:00 | 18.02 | 28-AUG-06:30 |
September | 0.00 | 01-SEP-00:10 | 76.99 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.61 | 29-SEP-10:55 | 22.71 | 20-SEP-03:00 |
October | 0.00 | 01-OCT-00:10 | 76.99 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.37 | 16-OCT-11:00 | 27.42 | 30-OCT-03:00 |
November | 0.00 | 01-NOV-00:10 | 76.99 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.69 | 19-NOV-13:00 | 32.51 | 23-NOV-22:00 |
December | 0.00 | 01-DEC-00:10 | 76.99 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.89 | 16-DEC-13:00 | 35.18 | 03-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 76.99 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 | 18.02 | |||||
Maximum of Months | 0.00 | 76.99 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 24.37 | 41.00 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 77.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.18 | 13-JAN-14:00 | 40.95 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 77.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 | 01-FEB-11:55 | 32.21 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 77.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 | 11-MAR-11:00 | 34.45 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 77.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.18 | 26-APR-13:00 | 27.98 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 77.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.87 | 03-MAY-12:00 | 26.05 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 77.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 29-JUN-10:55 | 19.93 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 77.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.87 | 19-JUL-10:02 | 15.79 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 77.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.85 | 14-AUG-10:55 | 14.06 | 28-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 77.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 29-SEP-10:02 | 19.79 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 77.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.32 | 16-OCT-10:55 | 23.96 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 77.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 | 19-NOV-13:00 | 28.11 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 77.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 05-DEC-10:00 | 32.29 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3.87 | 14.06 | |||||
Maximum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 26.32 | 40.95 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 | 14-JAN-11:00 | 146.71 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 01-FEB-10:00 | 115.41 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 11-MAR-11:00 | 123.45 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.70 | 30-APR-10:00 | 100.25 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 03-MAY-10:00 | 93.35 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 30-JUN-10:00 | 71.39 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 | 19-JUL-10:00 | 56.57 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.71 | 15-AUG-10:00 | 57.72 | 28-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.14 | 29-SEP-10:00 | 70.90 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.32 | 16-OCT-10:00 | 85.84 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.25 | 19-NOV-10:10 | 100.72 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.32 | 05-DEC-10:00 | 115.70 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 56.57 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 89.32 | 146.71 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 | 14-JAN-11:00 | 146.70 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.32 | 01-FEB-11:55 | 115.40 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 11-MAR-11:00 | 123.44 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.70 | 30-APR-10:00 | 100.24 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 03-MAY-10:00 | 93.35 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 30-JUN-10:00 | 71.39 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.69 | 19-JUL-10:00 | 56.57 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 | 15-AUG-10:00 | 57.05 | 28-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.14 | 29-SEP-10:00 | 70.89 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.31 | 16-OCT-10:00 | 85.84 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.26 | 19-NOV-10:00 | 100.71 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 | 05-DEC-10:00 | 115.69 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 56.57 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 89.31 | 146.70 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 2240.78 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.22 | 13-JAN-14:00 | 177.36 | 08-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 2240.78 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.45 | 01-FEB-11:55 | 149.77 | 04-FEB-05:55 |
March | 2263.36 | 01-MAR-00:10 | 2240.78 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 11-MAR-11:50 | 152.40 | 08-MAR-02:00 |
April | 2263.36 | 01-APR-00:10 | 2240.78 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.41 | 26-APR-13:00 | 121.49 | 01-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 2240.78 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.56 | 03-MAY-12:00 | 122.25 | 27-MAY-03:00 |
June | 2263.36 | 01-JUN-00:10 | 2240.78 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.27 | 29-JUN-10:55 | 96.12 | 13-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 2240.78 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.92 | 19-JUL-10:55 | 83.31 | 06-JUL-01:00 |
August | 2263.36 | 01-AUG-00:10 | 2240.78 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.41 | 14-AUG-10:55 | 75.08 | 24-AUG-02:00 |
September | 2263.36 | 01-SEP-00:10 | 2240.78 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.68 | 29-SEP-10:55 | 98.06 | 20-SEP-03:00 |
October | 2263.36 | 01-OCT-23:10 | 2240.78 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.81 | 16-OCT-10:55 | 116.72 | 30-OCT-03:05 |
November | 2263.36 | 01-NOV-00:10 | 2240.78 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.91 | 19-NOV-13:00 | 136.42 | 29-NOV-23:00 |
December | 2263.36 | 01-DEC-00:10 | 2240.78 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.08 | 16-DEC-13:00 | 148.90 | 03-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.56 | 75.08 | ||||
Maximum of Months | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.81 | 177.36 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.95 | 14-JAN-11:00 | 147.18 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.63 | 01-FEB-10:00 | 115.86 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.64 | 11-MAR-11:00 | 123.90 | 08-MAR-02:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.31 | 30-APR-10:00 | 100.69 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 | 03-MAY-10:00 | 93.79 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.64 | 30-JUN-10:00 | 71.83 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.31 | 19-JUL-10:00 | 56.99 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.32 | 15-AUG-10:00 | 50.35 | 28-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.78 | 29-SEP-10:00 | 71.33 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.95 | 16-OCT-10:00 | 86.28 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.87 | 19-NOV-10:00 | 101.16 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.93 | 05-DEC-10:00 | 116.15 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 | 50.35 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 88.95 | 147.18 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.95 | 14-JAN-11:00 | 147.16 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.70 | 01-FEB-11:55 | 115.85 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.64 | 11-MAR-11:00 | 123.89 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 30-APR-10:02 | 100.69 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 | 03-MAY-10:00 | 93.79 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.64 | 30-JUN-10:00 | 71.82 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.31 | 19-JUL-10:00 | 56.99 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.32 | 15-AUG-10:00 | 49.85 | 28-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.77 | 29-SEP-10:00 | 71.32 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.43 | 16-OCT-10:01 | 86.27 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.87 | 19-NOV-10:00 | 101.15 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.93 | 05-DEC-10:00 | 116.14 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 | 49.85 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 89.43 | 147.16 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 77.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.34 | 14-JAN-11:00 | 75.30 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 77.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 01-FEB-10:00 | 59.28 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 77.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 11-MAR-11:00 | 63.39 | 08-MAR-02:00 |
April | 180.00 | 01-APR-00:10 | 77.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.95 | 30-APR-10:00 | 51.52 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 77.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 | 03-MAY-10:00 | 47.99 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 77.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 | 30-JUN-10:00 | 36.75 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 77.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.60 | 19-JUL-10:00 | 29.16 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 77.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.61 | 15-AUG-10:00 | 26.14 | 28-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 77.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.42 | 29-SEP-10:00 | 36.49 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 77.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.51 | 16-OCT-10:00 | 44.14 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 77.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.30 | 19-NOV-10:00 | 51.76 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 77.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 05-DEC-10:00 | 59.42 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 | 26.14 | |||||
Maximum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 45.51 | 75.30 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3094.06 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.62 | 13-JAN-14:00 | 379.97 | 08-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 3094.06 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.92 | 01-FEB-11:55 | 333.25 | 04-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 3094.06 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.49 | 11-MAR-11:40 | 346.61 | 08-MAR-02:00 |
April | 26988.77 | 01-APR-00:10 | 3094.06 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.92 | 26-APR-13:00 | 295.77 | 01-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 3094.06 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 | 03-MAY-12:00 | 278.99 | 15-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 3094.06 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.05 | 29-JUN-10:50 | 224.92 | 13-JUN-04:10 |
July | 26988.77 | 01-JUL-00:10 | 3094.06 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.20 | 19-JUL-10:55 | 188.00 | 06-JUL-01:00 |
August | 26988.77 | 01-AUG-00:10 | 3094.06 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.26 | 14-AUG-10:55 | 170.32 | 31-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 3094.06 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.98 | 29-SEP-10:55 | 223.35 | 20-SEP-03:10 |
October | 26988.77 | 01-OCT-23:10 | 3094.06 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.27 | 16-OCT-10:55 | 260.40 | 30-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 3094.06 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.23 | 19-NOV-13:00 | 297.12 | 24-NOV-01:00 |
December | 26988.77 | 01-DEC-00:10 | 3094.06 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.83 | 19-DEC-13:00 | 332.93 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 | 170.32 | |||||
Maximum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 211.27 | 379.97 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3094.06 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.53 | 13-JAN-14:00 | 382.75 | 08-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 3094.06 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.23 | 01-FEB-11:55 | 333.25 | 04-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 3094.06 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.26 | 11-MAR-11:40 | 349.67 | 08-MAR-02:00 |
April | 26988.77 | 01-APR-00:10 | 3094.06 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.88 | 26-APR-13:00 | 295.77 | 01-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 3094.06 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 03-MAY-12:00 | 279.00 | 15-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 3094.06 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.76 | 29-JUN-10:50 | 224.92 | 13-JUN-04:10 |
July | 26988.77 | 01-JUL-00:10 | 3094.06 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.89 | 19-JUL-10:55 | 188.00 | 06-JUL-01:00 |
August | 26988.77 | 01-AUG-00:10 | 3094.06 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.06 | 14-AUG-10:55 | 170.32 | 31-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 3094.06 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.99 | 29-SEP-10:55 | 223.35 | 20-SEP-03:10 |
October | 26988.77 | 01-OCT-23:10 | 3094.06 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.03 | 16-OCT-10:55 | 260.41 | 30-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 3094.06 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.89 | 19-NOV-13:00 | 297.13 | 24-NOV-01:00 |
December | 26988.77 | 01-DEC-00:10 | 3094.06 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.02 | 19-DEC-13:00 | 333.95 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 170.32 | |||||
Maximum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 209.03 | 382.75 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1089.83 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 27.84 | 14-JAN-11:00 | 340.21 | 08-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 1089.83 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 27.67 | 01-FEB-11:55 | 288.16 | 05-FEB-06:10 |
March | 2401.70 | 01-MAR-00:10 | 1089.83 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 295.37 | 30-MAR-05:30 |
April | 2401.70 | 01-APR-00:10 | 1089.83 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 42.05 | 26-APR-13:00 | 264.70 | 01-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1089.83 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 248.80 | 19-MAY-05:00 |
June | 2401.70 | 01-JUN-00:10 | 1089.83 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 13.16 | 29-JUN-10:55 | 201.36 | 13-JUN-04:10 |
July | 2401.70 | 01-JUL-00:10 | 1089.83 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 56.41 | 19-JUL-12:00 | 158.71 | 06-JUL-01:00 |
August | 2401.70 | 01-AUG-00:10 | 1089.83 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 56.52 | 18-AUG-12:00 | 152.01 | 28-AUG-06:10 |
September | 2401.70 | 01-SEP-00:10 | 1089.83 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 167.09 | 29-SEP-11:10 | 189.66 | 20-SEP-03:30 |
October | 2401.70 | 01-OCT-23:10 | 1089.83 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 180.84 | 16-OCT-11:00 | 232.84 | 12-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 1089.83 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 42.11 | 19-NOV-13:00 | 265.90 | 23-NOV-22:00 |
December | 2401.70 | 01-DEC-00:10 | 1089.83 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 27.93 | 16-DEC-13:00 | 298.99 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1089.83 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 152.01 | ||||||
Maximum of Months | 2401.70 | 1089.83 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 180.84 | 340.21 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.68 | 14-JAN-11:00 | 313.18 | 08-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.47 | 01-FEB-11:55 | 253.81 | 04-FEB-05:55 |
March | 2395.44 | 01-MAR-00:10 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.23 | 11-MAR-11:00 | 263.41 | 08-MAR-04:00 |
April | 2395.44 | 01-APR-00:10 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.77 | 26-APR-13:00 | 213.78 | 01-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.28 | 03-MAY-12:00 | 209.15 | 27-MAY-03:00 |
June | 2395.44 | 01-JUN-00:10 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 | 29-JUN-10:55 | 164.38 | 13-JUN-04:05 |
July | 2395.44 | 01-JUL-00:10 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.41 | 19-JUL-10:55 | 143.96 | 06-JUL-01:00 |
August | 2395.44 | 01-AUG-00:10 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.77 | 14-AUG-10:55 | 129.16 | 28-AUG-03:00 |
September | 2395.44 | 01-SEP-00:10 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.29 | 29-SEP-10:55 | 165.55 | 20-SEP-03:00 |
October | 2395.44 | 01-OCT-23:10 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.48 | 16-OCT-10:55 | 197.47 | 27-OCT-04:05 |
November | 2395.44 | 01-NOV-00:10 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.66 | 19-NOV-13:00 | 235.11 | 29-NOV-23:00 |
December | 2395.44 | 01-DEC-00:10 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.57 | 16-DEC-13:00 | 252.95 | 03-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.28 | 129.16 | ||||
Maximum of Months | 2395.44 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.48 | 313.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19372.71 | 08-JAN-07:00 | 8945.92 | 4728.51 | 4258.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15563.58 | 01-FEB-11:33 | 7667.93 | 11821.18 | 11178.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14986.93 | 12-MAR-10:33 | 11501.89 | 14185.53 | 12775.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15146.86 | 30-APR-10:33 | 11501.89 | 14185.53 | 12775.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14866.17 | 28-MAY-10:33 | 11501.89 | 14185.53 | 12775.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14996.96 | 25-JUN-10:33 | 11501.89 | 14185.53 | 12775.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15921.42 | 23-JUL-10:33 | 11501.89 | 14185.53 | 12775.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15903.34 | 06-AUG-10:33 | 11501.89 | 14185.53 | 12775.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16508.01 | 30-SEP-10:33 | 11501.89 | 11821.18 | 11178.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18191.50 | 20-OCT-21:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18811.19 | 30-NOV-22:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18396.42 | 01-DEC-22:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14866.17 | 7667.93 | 4728.51 | 4258.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19372.71 | 11501.89 | 14185.53 | 12775.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3305.32 | 14-JAN-12:40 | 389.84 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 15.30 | 0.00 |
February | 2875.02 | 02-FEB-12:40 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.64 |
March | 2588.16 | 11-MAR-13:00 | 389.84 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 |
April | 2063.21 | 08-APR-10:33 | 1169.53 | 587.01 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.86 |
May | 2012.07 | 04-MAY-10:33 | 779.69 | 587.01 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.82 |
June | 1932.52 | 25-JUN-10:33 | 1169.53 | 704.41 | 866.03 | 0.00 | 0.00 | 0.00 | 0.00 | 11.56 | 0.00 |
July | 2118.98 | 30-JUL-10:33 | 1169.53 | 704.41 | 866.03 | 0.00 | 0.00 | 0.00 | 0.00 | 21.99 | 0.00 |
August | 2198.77 | 27-AUG-10:33 | 1169.53 | 704.41 | 866.03 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 | 0.00 |
September | 3544.59 | 30-SEP-13:10 | 389.84 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 89.26 | 0.00 |
October | 4164.01 | 16-OCT-12:10 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 129.44 | 0.00 |
November | 3645.57 | 19-NOV-12:30 | 389.84 | 234.80 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 28.55 | 0.00 |
December | 3480.70 | 19-DEC-12:50 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 21.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1932.52 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4164.01 | 1169.53 | 704.41 | 866.03 | 0.00 | 0.00 | 0.00 | 0.00 | 129.44 | 54.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1616.30 | 08-JAN-07:00 | 1053.36 | 271.91 | 334.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.88 |
February | 1496.17 | 03-FEB-21:20 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.37 |
March | 1500.32 | 24-MAR-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.73 |
April | 1614.91 | 27-APR-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.06 |
May | 1625.61 | 03-MAY-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.71 |
June | 1679.69 | 30-JUN-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.53 |
July | 1788.09 | 31-JUL-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.61 |
August | 1849.01 | 18-AUG-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.63 |
September | 2050.44 | 29-SEP-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 | 0.00 |
October | 2100.96 | 16-OCT-20:10 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.74 |
November | 1552.13 | 19-NOV-11:33 | 1354.32 | 815.72 | 1002.86 | 0.00 | 0.00 | 0.00 | 0.00 | 12.96 | 0.00 |
December | 1576.89 | 05-DEC-22:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1496.17 | 1053.36 | 271.91 | 334.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2100.96 | 1354.32 | 815.72 | 1002.86 | 0.00 | 0.00 | 0.00 | 0.00 | 12.96 | 97.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1316.97 | 20-JAN-11:33 | 190.94 | 1133.66 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 |
February | 1266.30 | 02-FEB-11:33 | 190.94 | 1133.66 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.34 |
March | 1292.86 | 19-MAR-10:33 | 286.42 | 1360.40 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.14 |
April | 1374.14 | 30-APR-10:33 | 286.42 | 1360.40 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 36.22 | 0.00 |
May | 1394.17 | 04-MAY-10:33 | 190.94 | 1133.66 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.79 |
June | 1452.33 | 25-JUN-10:33 | 286.42 | 1360.40 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 | 0.00 |
July | 1514.78 | 23-JUL-10:33 | 286.42 | 1360.40 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 | 0.00 |
August | 1501.24 | 19-AUG-10:33 | 286.42 | 1133.66 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 18.77 | 0.00 |
September | 1547.43 | 30-SEP-10:33 | 286.42 | 1133.66 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 76.11 | 0.00 |
October | 1538.23 | 16-OCT-10:33 | 190.94 | 1133.66 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 133.43 | 0.00 |
November | 1351.63 | 19-NOV-11:33 | 286.42 | 1360.40 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 38.85 | 0.00 |
December | 1315.58 | 19-DEC-11:33 | 190.94 | 1133.66 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 28.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1266.30 | 190.94 | 1133.66 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1547.43 | 286.42 | 1360.40 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 133.43 | 29.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 623.22 | 20-JAN-11:33 | 146.88 | 189.77 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 |
February | 598.69 | 02-FEB-11:33 | 146.88 | 189.77 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.60 |
March | 610.36 | 23-MAR-10:33 | 146.88 | 189.77 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 0.00 |
April | 650.04 | 30-APR-10:33 | 220.32 | 227.72 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 21.21 | 0.00 |
May | 658.80 | 04-MAY-10:33 | 146.88 | 189.77 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 |
June | 684.55 | 25-JUN-10:33 | 220.32 | 227.72 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 0.00 |
July | 715.58 | 23-JUL-10:33 | 220.32 | 227.72 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 16.98 | 0.00 |
August | 709.72 | 19-AUG-10:33 | 220.32 | 189.77 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 11.21 | 0.00 |
September | 735.66 | 30-SEP-10:33 | 220.32 | 189.77 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 43.95 | 0.00 |
October | 734.00 | 16-OCT-10:33 | 146.88 | 189.77 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 76.79 | 0.00 |
November | 643.94 | 19-NOV-11:33 | 220.32 | 227.72 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 22.32 | 0.00 |
December | 625.48 | 19-DEC-11:33 | 146.88 | 189.77 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 16.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 598.69 | 146.88 | 189.77 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 735.66 | 220.32 | 227.72 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 76.79 | 16.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37582.47 | 24-JAN-21:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 |
February | 37448.00 | 03-FEB-21:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 164.38 |
March | 37697.31 | 23-MAR-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 148.52 |
April | 38001.83 | 26-APR-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 102.91 |
May | 38015.54 | 04-MAY-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 103.02 |
June | 38024.64 | 30-JUN-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 117.91 |
July | 38288.05 | 19-JUL-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 73.00 |
August | 38230.72 | 18-AUG-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 73.06 |
September | 38524.41 | 29-SEP-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.19 | 0.00 |
October | 38368.76 | 16-OCT-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 43.45 |
November | 37448.82 | 28-NOV-21:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 164.66 |
December | 37700.86 | 05-DEC-21:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 118.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37448.00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38524.41 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.19 | 164.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13066.57 | 14-JAN-12:40 | 5122.80 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 33.85 | 0.00 |
February | 10990.21 | 20-FEB-11:00 | 8538.00 | 358.25 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.88 |
March | 10917.54 | 11-MAR-12:50 | 5122.80 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
April | 9281.91 | 08-APR-10:33 | 15368.40 | 895.64 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.28 |
May | 8907.76 | 04-MAY-21:20 | 15368.40 | 1174.60 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.63 |
June | 8750.62 | 25-JUN-10:33 | 15368.40 | 1074.76 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 13.04 | 0.00 |
July | 9351.72 | 30-JUL-10:33 | 15368.40 | 1074.76 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 41.60 | 0.00 |
August | 9692.55 | 27-AUG-10:33 | 15368.40 | 1074.76 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.42 |
September | 12510.34 | 30-SEP-12:00 | 5122.80 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 197.59 | 0.00 |
October | 14122.28 | 15-OCT-12:00 | 5122.80 | 358.25 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 198.53 | 0.00 |
November | 14301.89 | 19-NOV-11:00 | 8538.00 | 358.25 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 50.65 | 0.00 |
December | 12938.47 | 16-DEC-13:00 | 5122.80 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 50.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8750.62 | 5122.80 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14301.89 | 15368.40 | 1174.60 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 198.53 | 208.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33503.26 | 18-JAN-22:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537.93 |
February | 32802.11 | 01-FEB-22:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 829.98 |
March | 32101.29 | 24-MAR-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 829.84 |
April | 32520.34 | 26-APR-22:00 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.95 |
May | 33670.75 | 04-MAY-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.21 |
June | 33472.85 | 28-JUN-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521.36 |
July | 34980.46 | 31-JUL-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.72 |
August | 35567.76 | 18-AUG-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.32 |
September | 39577.34 | 29-SEP-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 42.14 | 0.00 |
October | 40238.61 | 16-OCT-20:10 | 40553.76 | 9124.61 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.49 |
November | 33567.47 | 20-NOV-22:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 754.28 |
December | 35094.34 | 05-DEC-22:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 32101.29 | 40553.76 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40238.61 | 45622.98 | 9124.61 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 42.14 | 829.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2773.34 | 14-JAN-16:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 | 0.00 |
February | 2732.73 | 03-FEB-16:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.82 |
March | 2788.34 | 11-MAR-16:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.56 |
April | 2798.83 | 01-APR-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 | 0.00 |
May | 2670.37 | 17-MAY-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 |
June | 2704.29 | 30-JUN-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 0.00 |
July | 2812.62 | 19-JUL-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 25.75 | 0.00 |
August | 2786.65 | 18-AUG-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 24.45 | 0.00 |
September | 2643.57 | 13-SEP-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
October | 2970.36 | 15-OCT-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 0.00 |
November | 2767.99 | 19-NOV-09:02 | 324.00 | 411.62 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 | 0.00 |
December | 2788.91 | 05-DEC-16:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2643.57 | 324.00 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2970.36 | 583.20 | 411.62 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 14.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2639.25 | 14-JAN-16:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3.38 | 0.00 |
February | 2598.87 | 03-FEB-16:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.10 |
March | 2657.91 | 11-MAR-16:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.98 |
April | 2678.29 | 01-APR-15:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 | 0.00 |
May | 2590.25 | 17-MAY-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.95 |
June | 2614.88 | 30-JUN-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 0.00 |
July | 2687.05 | 19-JUL-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 25.53 | 0.00 |
August | 2675.66 | 19-AUG-15:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 20.09 | 0.00 |
September | 2588.08 | 11-SEP-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.03 |
October | 2830.16 | 16-OCT-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 45.90 | 0.00 |
November | 2568.51 | 27-NOV-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.90 |
December | 2654.36 | 05-DEC-16:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2568.51 | 324.00 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2830.16 | 680.40 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 45.90 | 19.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 633.45 | 14-JAN-12:40 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 | 0.00 |
February | 569.66 | 02-FEB-12:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.34 |
March | 476.04 | 11-MAR-13:30 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 | 0.00 |
April | 355.93 | 08-APR-13:10 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.91 |
May | 254.24 | 04-MAY-12:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 | 0.00 |
June | 184.28 | 29-JUN-17:13 | 0.00 | 154.75 | 394.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 |
July | 278.20 | 31-JUL-13:00 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 0.00 |
August | 348.39 | 30-AUG-13:00 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 | 0.00 |
September | 629.55 | 30-SEP-13:30 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 15.59 | 0.00 |
October | 738.33 | 16-OCT-12:20 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 21.54 | 0.00 |
November | 684.84 | 19-NOV-13:00 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 6.69 | 0.00 |
December | 642.41 | 19-DEC-13:00 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 4.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 184.28 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 738.33 | 0.00 | 154.75 | 394.73 | 0.00 | 0.00 | 0.00 | 0.00 | 21.54 | 7.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 828.61 | 15-JAN-09:02 | 270.00 | 215.63 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 1.57 | 0.00 |
February | 745.81 | 20-FEB-09:02 | 324.00 | 258.76 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.74 |
March | 799.31 | 11-MAR-16:02 | 324.00 | 152.48 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 | 0.00 |
April | 824.70 | 26-APR-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 | 0.00 |
May | 818.11 | 04-MAY-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 | 0.00 |
June | 817.08 | 30-JUN-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.72 | 0.00 |
July | 839.46 | 18-JUL-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 | 0.00 |
August | 842.65 | 19-AUG-18:02 | 702.00 | 462.06 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 | 0.00 |
September | 850.16 | 30-SEP-18:02 | 702.00 | 462.06 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 | 0.00 |
October | 920.21 | 14-OCT-15:02 | 324.00 | 152.48 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 18.76 | 0.00 |
November | 859.85 | 19-NOV-09:02 | 324.00 | 258.76 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 4.63 | 0.00 |
December | 826.28 | 05-DEC-09:02 | 216.00 | 203.31 | 665.80 | 0.00 | 0.00 | 0.00 | 0.00 | 5.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 745.81 | 216.00 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 920.21 | 831.60 | 462.06 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 18.76 | 14.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2455.23 | 14-JAN-16:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 2.63 | 0.00 |
February | 2441.81 | 01-FEB-09:02 | 216.00 | 323.41 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.01 |
March | 2438.19 | 11-MAR-16:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.87 |
April | 2473.12 | 01-APR-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 | 0.00 |
May | 2345.85 | 04-MAY-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 |
June | 2332.87 | 02-JUN-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.29 |
July | 2373.99 | 19-JUL-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 25.90 | 0.00 |
August | 2425.26 | 19-AUG-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 20.49 | 0.00 |
September | 2364.08 | 30-SEP-18:02 | 702.00 | 735.03 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
October | 2614.49 | 15-OCT-08:62 | 324.00 | 411.62 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 44.56 | 0.00 |
November | 2531.02 | 19-NOV-09:02 | 324.00 | 411.62 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 10.35 | 0.00 |
December | 2515.91 | 05-DEC-09:02 | 216.00 | 323.41 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 10.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2332.87 | 216.00 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2614.49 | 702.00 | 735.03 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 44.56 | 13.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2190.78 | 14-JAN-16:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 | 0.00 |
February | 2261.59 | 01-FEB-09:02 | 216.00 | 323.38 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 | 0.00 |
March | 2260.02 | 11-MAR-16:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 |
April | 2309.64 | 26-APR-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 | 0.00 |
May | 2260.47 | 24-MAY-08:62 | 216.00 | 323.38 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.49 |
June | 2251.24 | 02-JUN-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.41 |
July | 2277.44 | 19-JUL-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 25.74 | 0.00 |
August | 2289.17 | 19-AUG-15:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 20.44 | 0.00 |
September | 2287.68 | 30-SEP-18:02 | 702.00 | 734.94 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
October | 2503.20 | 15-OCT-08:62 | 324.00 | 411.57 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 44.89 | 0.00 |
November | 2404.56 | 19-NOV-09:02 | 324.00 | 411.57 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 11.16 | 0.00 |
December | 2392.48 | 05-DEC-09:02 | 216.00 | 323.38 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 11.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2190.78 | 216.00 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2503.20 | 702.00 | 734.94 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 44.89 | 32.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2258.34 | 08-JAN-07:00 | 1760.39 | 746.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.36 |
February | 1981.93 | 04-FEB-11:45 | 1508.90 | 1244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.88 |
March | 1992.74 | 12-MAR-10:33 | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.34 |
April | 2098.26 | 30-APR-10:33 | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 0.00 |
May | 2099.24 | 04-MAY-10:33 | 1508.90 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 |
June | 2151.16 | 25-JUN-10:33 | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 | 0.00 |
July | 2248.67 | 23-JUL-10:33 | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.06 | 0.00 |
August | 2268.17 | 19-AUG-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.99 | 0.00 |
September | 2357.60 | 30-SEP-10:33 | 2263.36 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.40 | 0.00 |
October | 2367.29 | 17-OCT-10:33 | 1508.90 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.61 | 0.00 |
November | 2120.89 | 19-NOV-11:33 | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.70 | 0.00 |
December | 2032.54 | 05-DEC-11:33 | 1508.90 | 1867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1981.93 | 1508.90 | 746.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2367.29 | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.61 | 177.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2866.89 | 14-JAN-16:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 2.25 | 0.00 |
February | 2818.64 | 03-FEB-16:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.14 |
March | 2883.92 | 11-MAR-16:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.05 |
April | 2892.67 | 01-APR-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 | 0.00 |
May | 2731.91 | 04-MAY-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.82 |
June | 2768.52 | 28-JUN-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 |
July | 2860.19 | 18-JUL-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 20.96 | 0.00 |
August | 2849.59 | 06-AUG-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 13.43 | 0.00 |
September | 2730.44 | 08-SEP-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.93 |
October | 3075.83 | 15-OCT-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 51.16 | 0.00 |
November | 2812.75 | 19-NOV-09:02 | 324.00 | 411.62 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 13.38 | 0.00 |
December | 2882.53 | 05-DEC-16:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2730.44 | 324.00 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3075.83 | 583.20 | 411.62 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 51.16 | 15.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2714.13 | 14-JAN-16:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 | 0.00 |
February | 2665.65 | 03-FEB-16:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 |
March | 2737.82 | 11-MAR-16:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 |
April | 2757.61 | 01-APR-15:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 | 0.00 |
May | 2643.24 | 17-MAY-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.45 |
June | 2676.51 | 28-JUN-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
July | 2768.19 | 18-JUL-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 20.82 | 0.00 |
August | 2766.27 | 18-AUG-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 23.93 | 0.00 |
September | 2668.61 | 10-SEP-15:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 |
October | 2919.66 | 16-OCT-15:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 45.42 | 0.00 |
November | 2625.90 | 27-NOV-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.74 |
December | 2728.31 | 05-DEC-16:02 | 583.20 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2625.90 | 324.00 | 205.78 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2919.66 | 680.40 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 45.42 | 19.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1564.22 | 14-JAN-16:02 | 324.00 | 152.48 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 | 0.00 |
February | 1524.80 | 03-FEB-16:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 |
March | 1541.67 | 10-MAR-16:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.16 |
April | 1552.40 | 01-APR-15:01 | 378.00 | 177.90 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
May | 1458.93 | 03-MAY-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 |
June | 1440.38 | 20-JUN-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.01 |
July | 1452.95 | 31-JUL-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 9.63 | 0.00 |
August | 1518.08 | 19-AUG-15:02 | 324.00 | 152.48 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 10.20 | 0.00 |
September | 1486.11 | 30-SEP-18:02 | 702.00 | 462.06 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
October | 1646.35 | 16-OCT-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 22.60 | 0.00 |
November | 1575.24 | 19-NOV-09:02 | 324.00 | 258.76 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 4.98 | 0.00 |
December | 1565.90 | 05-DEC-16:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1440.38 | 324.00 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1646.35 | 702.00 | 462.06 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 22.60 | 8.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19641.94 | 18-JAN-22:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.39 |
February | 19019.07 | 01-FEB-23:00 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.92 |
March | 19387.93 | 24-MAR-22:00 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.73 |
April | 20332.55 | 26-APR-22:00 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.08 |
May | 20758.19 | 04-MAY-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.86 |
June | 20979.41 | 27-JUN-22:00 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.65 |
July | 21220.96 | 19-JUL-22:00 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.61 |
August | 21058.94 | 17-AUG-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.84 |
September | 21633.43 | 29-SEP-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | 0.00 |
October | 21252.04 | 04-OCT-22:00 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.12 |
November | 19265.95 | 10-NOV-23:00 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.67 |
December | 19734.93 | 05-DEC-23:00 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19019.07 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21633.43 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | 187.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21236.84 | 18-JAN-22:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.39 |
February | 20667.54 | 01-FEB-22:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.95 |
March | 20929.87 | 24-MAR-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.92 |
April | 21803.24 | 26-APR-22:00 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.08 |
May | 22197.20 | 04-MAY-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.86 |
June | 22341.63 | 27-JUN-21:50 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.65 |
July | 22546.24 | 19-JUL-22:00 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.61 |
August | 22381.49 | 17-AUG-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.85 |
September | 22927.48 | 29-SEP-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | 0.00 |
October | 22569.84 | 04-OCT-22:00 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.12 |
November | 20885.67 | 10-NOV-22:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.67 |
December | 21247.39 | 05-DEC-23:00 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20667.54 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22927.48 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | 187.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28217.33 | 20-JAN-11:45 | 1067.42 | 605.46 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 33.47 |
February | 28098.85 | 01-FEB-11:45 | 1067.42 | 605.46 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 20.44 | 0.00 |
March | 28890.45 | 19-MAR-10:50 | 800.57 | 363.28 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 65.78 |
April | 29394.41 | 30-APR-10:33 | 2401.70 | 1089.83 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 22.90 | 0.00 |
May | 29095.03 | 04-MAY-10:33 | 1601.14 | 908.19 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 30.89 |
June | 29431.46 | 25-JUN-10:33 | 2401.70 | 1089.83 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 16.02 |
July | 29906.79 | 23-JUL-10:33 | 2401.70 | 1089.83 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 22.97 | 0.00 |
August | 29803.87 | 19-AUG-10:33 | 2401.70 | 908.19 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 8.40 | 0.00 |
September | 30317.49 | 30-SEP-10:50 | 800.57 | 302.73 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 93.86 | 0.00 |
October | 30146.57 | 15-OCT-10:50 | 1601.14 | 726.55 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 109.49 | 0.00 |
November | 28840.06 | 19-NOV-11:50 | 800.57 | 363.28 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 27.73 | 0.00 |
December | 28120.85 | 05-DEC-11:33 | 1601.14 | 908.19 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 11.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 28098.85 | 800.57 | 302.73 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30317.49 | 2401.70 | 1089.83 | 44738.57 | 56232.08 | 0.00 | 0.00 | 0.00 | 109.49 | 65.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4283.16 | 20-JAN-11:33 | 1596.96 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.81 |
February | 4091.67 | 01-FEB-11:45 | 1064.64 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.79 | 0.00 |
March | 4264.77 | 11-MAR-11:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.99 | 0.00 |
April | 4420.48 | 30-APR-10:33 | 2395.44 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.92 | 0.00 |
May | 4495.64 | 04-MAY-10:33 | 1596.96 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.47 |
June | 4572.91 | 30-JUN-10:33 | 1596.96 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.04 | 0.00 |
July | 4797.85 | 30-JUL-10:33 | 2395.44 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.93 | 0.00 |
August | 4791.63 | 19-AUG-10:33 | 2395.44 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.61 | 0.00 |
September | 5724.55 | 30-SEP-13:40 | 798.48 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.46 | 0.00 |
October | 5648.22 | 16-OCT-12:50 | 532.32 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.51 | 0.00 |
November | 4509.46 | 19-NOV-11:33 | 2395.44 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.61 | 0.00 |
December | 4335.54 | 19-DEC-11:33 | 1596.96 | 1976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4091.67 | 532.32 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5724.55 | 2395.44 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.51 | 18.81 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.401362E+12 | 284097.72 | 17-JAN-20:10 | 0.577963E+12 | 517553.47 | 02-JAN-20:00 |
February | 0.350395E+12 | 256699.86 | 13-FEB-20:30 | 0.494020E+12 | 476040.70 | 06-FEB-22:00 |
March | 0.382177E+12 | 261394.26 | 22-MAR-18:10 | 0.582832E+12 | 512102.86 | 29-MAR-20:49 |
April | 0.397652E+12 | 286073.54 | 26-APR-19:10 | 0.463707E+12 | 426577.75 | 15-APR-21:00 |
May | 0.411364E+12 | 284813.72 | 04-MAY-19:10 | 0.462186E+12 | 409715.91 | 10-MAY-19:00 |
June | 0.434234E+12 | 304396.79 | 29-JUN-18:10 | 0.393845E+12 | 368440.74 | 12-JUN-20:00 |
July | 0.508917E+12 | 335919.20 | 31-JUL-19:10 | 0.394293E+12 | 347184.70 | 24-JUL-17:10 |
August | 0.524645E+12 | 329081.79 | 14-AUG-19:10 | 0.393939E+12 | 347240.13 | 25-AUG-17:10 |
September | 0.461797E+12 | 360462.95 | 29-SEP-19:10 | 0.387504E+12 | 347605.69 | 28-SEP-17:49 |
October | 0.487100E+12 | 338139.32 | 04-OCT-19:00 | 0.424652E+12 | 371715.06 | 11-OCT-20:00 |
November | 0.393565E+12 | 261895.51 | 10-NOV-20:00 | 0.493852E+12 | 489336.13 | 23-NOV-21:00 |
December | 0.406641E+12 | 281743.24 | 05-DEC-20:10 | 0.568755E+12 | 507388.59 | 12-DEC-21:49 |
Annual Sum or Average | 0.515985E+13 | 0.563755E+13 | ||||
Minimum of Months | 0.350395E+12 | 256699.86 | 0.387504E+12 | 347184.70 | ||
Maximum of Months | 0.524645E+12 | 360462.95 | 0.582832E+12 | 517553.47 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.654020E+11 | 0.239327E+11 | 0.148212E+12 | 0.553309E+11 | 0.463819E+11 | 0.114206E+11 | 0.00 | 0.377350E+11 | 0.00 | 0.00 | 0.00 | 0.770493E+10 | 0.00 |
February | 0.589667E+11 | 0.204568E+11 | 0.133859E+12 | 0.499764E+11 | 0.413625E+11 | 0.966565E+10 | 0.00 | 0.243946E+11 | 0.00 | 0.00 | 0.00 | 0.696236E+10 | 0.00 |
March | 0.652650E+11 | 0.209666E+11 | 0.148223E+12 | 0.553338E+11 | 0.452930E+11 | 0.992494E+10 | 0.00 | 0.241913E+11 | 0.00 | 0.00 | 0.00 | 0.770356E+10 | 0.00 |
April | 0.629187E+11 | 0.186400E+11 | 0.143397E+12 | 0.535455E+11 | 0.450119E+11 | 0.126701E+11 | 0.00 | 0.488796E+11 | 0.00 | 0.00 | 0.00 | 0.746525E+10 | 0.00 |
May | 0.649566E+11 | 0.177966E+11 | 0.148223E+12 | 0.553320E+11 | 0.465897E+11 | 0.134118E+11 | 0.00 | 0.520465E+11 | 0.00 | 0.00 | 0.00 | 0.770480E+10 | 0.00 |
June | 0.628376E+11 | 0.164989E+11 | 0.143446E+12 | 0.535482E+11 | 0.465517E+11 | 0.144860E+11 | 0.00 | 0.842378E+11 | 0.00 | 0.00 | 0.00 | 0.745705E+10 | 0.00 |
July | 0.648558E+11 | 0.173702E+11 | 0.148174E+12 | 0.553292E+11 | 0.496383E+11 | 0.169090E+11 | 0.00 | 0.143595E+12 | 0.00 | 0.00 | 0.00 | 0.771273E+10 | 0.00 |
August | 0.650506E+11 | 0.186030E+11 | 0.148234E+12 | 0.553337E+11 | 0.501451E+11 | 0.173589E+11 | 0.00 | 0.156853E+12 | 0.00 | 0.00 | 0.00 | 0.770448E+10 | 0.00 |
September | 0.630776E+11 | 0.195855E+11 | 0.143408E+12 | 0.535458E+11 | 0.474471E+11 | 0.152708E+11 | 0.00 | 0.106821E+12 | 0.00 | 0.00 | 0.00 | 0.746657E+10 | 0.00 |
October | 0.653102E+11 | 0.219491E+11 | 0.148201E+12 | 0.553307E+11 | 0.501702E+11 | 0.158113E+11 | 0.00 | 0.117332E+12 | 0.00 | 0.00 | 0.00 | 0.770319E+10 | 0.00 |
November | 0.633121E+11 | 0.227370E+11 | 0.143462E+12 | 0.535468E+11 | 0.456594E+11 | 0.120344E+11 | 0.00 | 0.402832E+11 | 0.00 | 0.00 | 0.00 | 0.744930E+10 | 0.00 |
December | 0.653333E+11 | 0.243405E+11 | 0.148174E+12 | 0.553296E+11 | 0.469734E+11 | 0.116060E+11 | 0.00 | 0.419471E+11 | 0.00 | 0.00 | 0.00 | 0.771298E+10 | 0.00 |
Annual Sum or Average | 0.767286E+12 | 0.242877E+12 | 0.174501E+13 | 0.651483E+12 | 0.561224E+12 | 0.160570E+12 | 0.00 | 0.878316E+12 | 0.00 | 0.00 | 0.00 | 0.907472E+11 | 0.00 |
Minimum of Months | 0.589667E+11 | 0.164989E+11 | 0.133859E+12 | 0.499764E+11 | 0.413625E+11 | 0.966565E+10 | 0.00 | 0.241913E+11 | 0.00 | 0.00 | 0.00 | 0.696236E+10 | 0.00 |
Maximum of Months | 0.654020E+11 | 0.243405E+11 | 0.148234E+12 | 0.553338E+11 | 0.501702E+11 | 0.173589E+11 | 0.00 | 0.156853E+12 | 0.00 | 0.00 | 0.00 | 0.771298E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.169407E+12 | 0.00 | 0.256638E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.124779E+12 | 0.00 | 0.232037E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.175606E+12 | 0.00 | 0.255202E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.730983E+11 | 0.00 | 0.243653E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.624846E+11 | 0.00 | 0.247723E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.104670E+11 | 0.00 | 0.236264E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.688329E+09 | 0.00 | 0.241784E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.286638E+09 | 0.00 | 0.241614E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.500569E+10 | 0.00 | 0.235527E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.259765E+11 | 0.00 | 0.246772E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.104048E+12 | 0.00 | 0.242713E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.162506E+12 | 0.00 | 0.254429E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.914352E+12 | 0.00 | 0.293436E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.286638E+09 | 0.00 | 0.232037E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.175606E+12 | 0.00 | 0.256638E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 62892.57 | 02-JAN-20:10 | 15448.40 | 01-JAN-00:10 | 89475.41 | 02-JAN-07:10 | 39726.11 | 18-JAN-07:19 | 29641.45 | 18-JAN-22:10 | 7232.59 | 18-JAN-13:30 | 0.00 | 01-JAN-00:10 |
February | 62892.57 | 01-FEB-20:10 | 15448.40 | 01-FEB-00:10 | 89475.41 | 01-FEB-07:10 | 39725.67 | 10-FEB-07:19 | 27881.36 | 01-FEB-22:10 | 7058.36 | 01-FEB-13:09 | 0.00 | 01-FEB-00:10 |
March | 62892.57 | 01-MAR-20:10 | 15448.40 | 01-MAR-00:10 | 89475.41 | 01-MAR-07:10 | 39726.11 | 13-MAR-06:19 | 27770.58 | 23-MAR-21:10 | 7179.93 | 12-MAR-09:00 | 0.00 | 01-MAR-00:10 |
April | 62892.57 | 03-APR-19:10 | 15448.40 | 01-APR-00:10 | 89475.41 | 03-APR-06:10 | 39725.51 | 05-APR-06:19 | 28956.61 | 26-APR-21:10 | 7128.95 | 26-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 62892.57 | 01-MAY-19:10 | 15448.40 | 01-MAY-00:10 | 89475.41 | 01-MAY-06:10 | 39725.08 | 08-MAY-06:19 | 30100.75 | 04-MAY-21:10 | 7207.78 | 18-MAY-15:09 | 0.00 | 01-MAY-00:10 |
June | 62892.57 | 01-JUN-19:10 | 15448.40 | 01-JUN-00:10 | 89475.41 | 01-JUN-06:10 | 39725.08 | 09-JUN-06:19 | 30020.30 | 30-JUN-21:10 | 7517.75 | 29-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 62892.57 | 03-JUL-19:10 | 15448.40 | 01-JUL-00:10 | 89475.41 | 03-JUL-06:10 | 39725.08 | 11-JUL-06:19 | 31771.85 | 31-JUL-21:10 | 7660.71 | 31-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 62892.57 | 01-AUG-19:10 | 15448.40 | 01-AUG-00:10 | 89475.41 | 01-AUG-06:10 | 39725.51 | 21-AUG-06:19 | 31825.03 | 18-AUG-21:10 | 7566.81 | 14-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 62892.57 | 01-SEP-19:10 | 15448.40 | 01-SEP-00:10 | 89475.41 | 01-SEP-06:10 | 39726.11 | 18-SEP-06:19 | 34552.74 | 29-SEP-21:10 | 7962.52 | 29-SEP-15:30 | 0.00 | 01-SEP-00:10 |
October | 62892.57 | 02-OCT-19:10 | 15448.40 | 01-OCT-00:10 | 89475.41 | 02-OCT-06:10 | 39726.11 | 05-OCT-06:19 | 37012.34 | 16-OCT-21:10 | 7715.50 | 16-OCT-18:10 | 0.00 | 01-OCT-00:10 |
November | 62892.57 | 01-NOV-19:10 | 15448.40 | 01-NOV-00:10 | 89475.41 | 01-NOV-06:10 | 39726.11 | 01-NOV-06:19 | 29636.28 | 28-NOV-22:10 | 7500.12 | 19-NOV-10:00 | 0.00 | 01-NOV-00:10 |
December | 62892.57 | 01-DEC-20:10 | 15448.40 | 01-DEC-00:10 | 89475.41 | 01-DEC-07:10 | 39726.11 | 08-DEC-07:19 | 31742.42 | 05-DEC-22:10 | 6994.64 | 16-DEC-15:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 62892.57 | 15448.40 | 89475.41 | 39725.08 | 27770.58 | 6994.64 | 0.00 | |||||||
Maximum of Months | 62892.57 | 15448.40 | 89475.41 | 39726.11 | 37012.34 | 7962.52 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 84570.38 | 14-JAN-11:39 | 0.00 | 0.00 | 0.00 | 4738.43 | 13-JAN-19:10 | 0.00 |
February | 78380.68 | 01-FEB-11:50 | 0.00 | 0.00 | 0.00 | 4738.44 | 13-FEB-19:10 | 0.00 |
March | 72945.77 | 23-MAR-15:20 | 0.00 | 0.00 | 0.00 | 4738.50 | 10-MAR-19:10 | 0.00 |
April | 86769.99 | 26-APR-10:50 | 0.00 | 0.00 | 0.00 | 4738.58 | 04-APR-18:10 | 0.00 |
May | 67373.67 | 04-MAY-15:09 | 0.00 | 0.00 | 0.00 | 4738.43 | 15-MAY-18:10 | 0.00 |
June | 100574.54 | 29-JUN-18:10 | 0.00 | 0.00 | 0.00 | 4738.61 | 05-JUN-18:10 | 0.00 |
July | 128156.10 | 19-JUL-15:20 | 0.00 | 0.00 | 0.00 | 4738.15 | 10-JUL-18:10 | 0.00 |
August | 136342.89 | 18-AUG-15:09 | 0.00 | 0.00 | 0.00 | 4738.33 | 09-AUG-18:19 | 0.00 |
September | 164257.47 | 29-SEP-12:00 | 0.00 | 0.00 | 0.00 | 4738.37 | 11-SEP-18:10 | 0.00 |
October | 180333.25 | 16-OCT-10:50 | 0.00 | 0.00 | 0.00 | 4738.47 | 11-OCT-18:10 | 0.00 |
November | 92481.26 | 19-NOV-10:00 | 0.00 | 0.00 | 0.00 | 4738.53 | 27-NOV-19:10 | 0.00 |
December | 82221.26 | 05-DEC-09:00 | 0.00 | 0.00 | 0.00 | 4738.51 | 18-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 67373.67 | 0.00 | 0.00 | 0.00 | 4738.15 | 0.00 | ||
Maximum of Months | 180333.25 | 0.00 | 0.00 | 0.00 | 4738.61 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 284097.72 | 17-JAN-20:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 23036.21 | 6461.57 | 0.00 | 49411.32 | 0.00 |
February | 256699.86 | 13-FEB-20:30 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 22213.86 | 5353.45 | 0.00 | 23534.30 | 0.00 |
March | 261394.26 | 22-MAR-18:10 | 55920.94 | 79417.81 | 15448.40 | 31837.63 | 21944.25 | 6358.21 | 0.00 | 43306.95 | 0.00 |
April | 286073.54 | 26-APR-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 22898.48 | 6771.73 | 0.00 | 50865.55 | 0.00 |
May | 284813.72 | 04-MAY-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 22980.57 | 6683.83 | 0.00 | 49867.18 | 0.00 |
June | 304396.79 | 29-JUN-18:10 | 53784.22 | 79417.81 | 0.00 | 31835.81 | 24238.47 | 7517.75 | 0.00 | 100574.54 | 0.00 |
July | 335919.20 | 31-JUL-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 25105.20 | 7544.41 | 0.00 | 97679.58 | 0.00 |
August | 329081.79 | 14-AUG-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 24910.74 | 7489.24 | 0.00 | 91093.39 | 0.00 |
September | 360462.95 | 29-SEP-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 29864.99 | 7344.14 | 0.00 | 118286.16 | 0.00 |
October | 338139.32 | 04-OCT-19:00 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 26258.87 | 7516.23 | 0.00 | 98868.56 | 0.00 |
November | 261895.51 | 10-NOV-20:00 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 23546.06 | 5610.65 | 0.00 | 28034.77 | 0.00 |
December | 281743.24 | 05-DEC-20:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 24993.77 | 6341.93 | 0.00 | 45790.88 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 256699.86 | 53784.22 | 79417.81 | 0.00 | 31835.81 | 21944.25 | 5353.45 | 0.00 | 23534.30 | 0.00 | |
Maximum of Months | 360462.95 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 29864.99 | 7544.41 | 0.00 | 118286.16 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 230195.00 | 08-JAN-06:00 | 0.00 | 246231.46 | 30-JAN-21:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 194772.40 | 04-FEB-05:00 | 0.00 | 246240.35 | 02-FEB-21:00 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 226993.60 | 30-MAR-02:00 | 0.00 | 246090.49 | 01-MAR-21:40 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 173656.88 | 01-APR-05:00 | 0.00 | 245526.77 | 04-APR-20:30 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 164638.38 | 14-MAY-04:49 | 0.00 | 244926.86 | 01-MAY-20:49 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 103628.26 | 13-JUN-03:00 | 0.00 | 244190.24 | 01-JUN-20:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 40083.00 | 06-JUL-02:00 | 0.00 | 243623.07 | 03-JUL-20:40 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 10217.39 | 28-AUG-06:30 | 0.00 | 243538.43 | 29-AUG-20:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 98640.15 | 20-SEP-03:00 | 0.00 | 244028.85 | 29-SEP-20:30 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 149508.43 | 12-OCT-05:00 | 0.00 | 244763.04 | 31-OCT-20:40 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 182545.33 | 29-NOV-22:00 | 0.00 | 245415.63 | 28-NOV-21:49 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 197805.55 | 23-DEC-05:00 | 0.00 | 245983.75 | 29-DEC-21:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 10217.39 | 0.00 | 243538.43 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 230195.00 | 0.00 | 246240.35 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 22.08 | 1.17 | 22.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.91 | 2.00 | 21.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.67 | 21.93 | 3.67 | 21.93 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 22.08 | 2.00 | 22.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.95 | 0.67 | 21.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.91 | 0.33 | 21.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 21.94 | 1.00 | 21.94 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.95 | 0.67 | 21.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.79 | 0.33 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 21.79 | 0.33 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.79 | 0.33 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.76 | 0.50 | 21.76 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.80 | 0.50 | 21.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.93 | 0.83 | 21.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.79 | 0.67 | 21.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
Annual Sum or Average | 0.00 | 0.00 | 3.50 | 21.79 | 3.50 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.93 | 0.83 | 21.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.67 | 0.33 | 21.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.69 | 0.50 | 21.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.78 | 0.67 | 21.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.50 | 21.71 | 2.50 | 21.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.78 | 0.67 | 21.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.74 | 0.33 | 21.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 22.08 | 1.83 | 22.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.93 | 2.50 | 21.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
Annual Sum or Average | 0.00 | 0.00 | 5.00 | 21.96 | 5.00 | 21.96 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 22.08 | 2.50 | 22.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 22.00 | 1.00 | 22.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.98 | 0.33 | 21.98 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.33 | 22.00 | 1.33 | 22.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 22.00 | 1.00 | 22.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.92 | 2.83 | 21.92 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.79 | 1.67 | 21.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.82 | 0.83 | 21.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.13 | 1.33 | 22.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 21.98 | 6.17 | 21.98 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.81 | 1.50 | 21.81 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.82 | 3.50 | 21.82 |
Annual Sum or Average | 0.00 | 0.00 | 18.00 | 21.91 | 18.00 | 21.91 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 22.13 | 6.17 | 22.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.33 | 23.40 | 9.50 | 23.41 | 0.00 | 23.41 |
February | 666.50 | 22.95 | 0.00 | 22.95 | 0.00 | 22.95 |
March | 744.00 | 22.74 | 0.00 | 22.74 | 0.00 | 22.74 |
April | 720.00 | 22.64 | 0.00 | 22.64 | 0.00 | 22.64 |
May | 744.00 | 22.64 | 0.00 | 22.64 | 0.00 | 22.64 |
June | 720.00 | 22.52 | 0.00 | 22.52 | 0.00 | 22.52 |
July | 725.50 | 22.84 | 0.00 | 22.84 | 0.00 | 22.84 |
August | 699.17 | 22.92 | 0.00 | 22.92 | 0.00 | 22.92 |
September | 465.17 | 23.13 | 32.00 | 23.19 | 0.00 | 23.19 |
October | 457.17 | 23.41 | 63.00 | 23.47 | 0.00 | 23.47 |
November | 492.17 | 23.53 | 33.50 | 23.56 | 0.00 | 23.56 |
December | 635.67 | 23.47 | 3.00 | 23.48 | 0.00 | 23.48 |
Annual Sum or Average | 7679.67 | 22.97 | 141.00 | 22.99 | 0.00 | 22.99 |
Minimum of Months | 457.17 | 22.52 | 0.00 | 22.52 | 0.00 | 22.52 |
Maximum of Months | 744.00 | 23.53 | 63.00 | 23.56 | 0.00 | 23.56 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 595.67 | 21.64 | 88.00 | 21.92 | 4.17 | 21.91 |
February | 572.50 | 21.50 | 54.83 | 21.70 | 2.50 | 21.70 |
March | 671.67 | 21.37 | 50.33 | 21.51 | 6.33 | 21.51 |
April | 655.83 | 21.65 | 18.17 | 21.70 | 0.00 | 21.70 |
May | 736.67 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
June | 720.00 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
July | 693.33 | 22.08 | 7.17 | 22.10 | 0.00 | 22.10 |
August | 549.00 | 22.26 | 100.33 | 22.44 | 0.00 | 22.44 |
September | 505.33 | 22.09 | 150.67 | 22.46 | 0.00 | 22.46 |
October | 503.17 | 22.12 | 161.17 | 22.54 | 0.00 | 22.54 |
November | 568.17 | 21.78 | 88.67 | 22.07 | 0.67 | 22.07 |
December | 579.00 | 21.72 | 83.50 | 22.00 | 0.00 | 22.00 |
Annual Sum or Average | 7350.33 | 21.76 | 802.83 | 21.95 | 13.67 | 21.95 |
Minimum of Months | 503.17 | 21.37 | 0.00 | 21.44 | 0.00 | 21.44 |
Maximum of Months | 736.67 | 22.26 | 161.17 | 22.54 | 6.33 | 22.54 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 705.83 | 22.63 | 7.50 | 22.64 | 0.00 | 22.64 |
February | 636.83 | 22.59 | 2.17 | 22.59 | 0.00 | 22.59 |
March | 706.83 | 22.42 | 8.00 | 22.44 | 0.00 | 22.44 |
April | 595.17 | 22.65 | 45.33 | 22.73 | 0.00 | 22.73 |
May | 639.33 | 22.62 | 27.67 | 22.67 | 0.00 | 22.67 |
June | 498.00 | 22.71 | 101.00 | 22.89 | 9.33 | 22.90 |
July | 380.83 | 22.89 | 254.33 | 23.23 | 60.00 | 23.26 |
August | 341.17 | 22.99 | 320.50 | 23.35 | 71.83 | 23.37 |
September | 364.00 | 22.90 | 178.67 | 23.20 | 18.83 | 23.20 |
October | 482.67 | 23.02 | 133.00 | 23.19 | 21.17 | 23.20 |
November | 643.83 | 22.84 | 17.17 | 22.87 | 0.00 | 22.87 |
December | 717.17 | 22.81 | 3.00 | 22.81 | 0.00 | 22.81 |
Annual Sum or Average | 6711.67 | 22.73 | 1098.33 | 22.87 | 181.17 | 22.89 |
Minimum of Months | 341.17 | 22.42 | 2.17 | 22.44 | 0.00 | 22.44 |
Maximum of Months | 717.17 | 23.02 | 320.50 | 23.35 | 71.83 | 23.37 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.84 | 0.00 | 21.84 | 0.00 | 21.84 |
February | 672.00 | 21.88 | 0.00 | 21.88 | 0.00 | 21.88 |
March | 744.00 | 21.74 | 0.00 | 21.74 | 0.00 | 21.74 |
April | 720.00 | 22.13 | 0.00 | 22.13 | 0.00 | 22.13 |
May | 744.00 | 22.32 | 0.00 | 22.32 | 0.00 | 22.32 |
June | 699.00 | 22.68 | 0.00 | 22.68 | 0.00 | 22.68 |
July | 657.50 | 22.91 | 0.50 | 22.91 | 0.00 | 22.91 |
August | 665.33 | 22.89 | 0.00 | 22.89 | 0.00 | 22.89 |
September | 708.67 | 22.73 | 1.83 | 22.73 | 0.00 | 22.73 |
October | 684.33 | 22.76 | 2.67 | 22.77 | 0.00 | 22.77 |
November | 720.00 | 22.17 | 0.00 | 22.17 | 0.00 | 22.17 |
December | 744.00 | 22.00 | 0.00 | 22.00 | 0.00 | 22.00 |
Annual Sum or Average | 8502.83 | 22.32 | 5.00 | 22.33 | 0.00 | 22.33 |
Minimum of Months | 657.50 | 21.74 | 0.00 | 21.74 | 0.00 | 21.74 |
Maximum of Months | 744.00 | 22.91 | 2.67 | 22.91 | 0.00 | 22.91 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
February | 672.00 | 21.71 | 0.00 | 21.71 | 0.00 | 21.71 |
March | 744.00 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
April | 720.00 | 21.96 | 0.00 | 21.96 | 0.00 | 21.96 |
May | 744.00 | 22.13 | 0.00 | 22.13 | 0.00 | 22.13 |
June | 720.00 | 22.52 | 0.00 | 22.52 | 0.00 | 22.52 |
July | 744.00 | 22.81 | 0.00 | 22.81 | 0.00 | 22.81 |
August | 744.00 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
September | 716.50 | 22.58 | 0.00 | 22.58 | 0.00 | 22.58 |
October | 741.33 | 22.67 | 0.00 | 22.67 | 0.00 | 22.67 |
November | 720.00 | 22.01 | 0.00 | 22.01 | 0.00 | 22.01 |
December | 744.00 | 21.84 | 0.00 | 21.84 | 0.00 | 21.84 |
Annual Sum or Average | 8753.83 | 22.19 | 0.00 | 22.19 | 0.00 | 22.19 |
Minimum of Months | 672.00 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
Maximum of Months | 744.00 | 22.81 | 0.00 | 22.81 | 0.00 | 22.81 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 284.33 | 23.14 | 580.67 | 23.19 | 201.67 | 23.34 |
February | 254.00 | 23.21 | 543.83 | 23.19 | 186.33 | 23.34 |
March | 305.50 | 23.23 | 612.17 | 23.17 | 227.17 | 23.33 |
April | 295.50 | 23.53 | 624.17 | 23.22 | 250.17 | 23.39 |
May | 306.33 | 23.53 | 649.33 | 23.23 | 259.00 | 23.39 |
June | 296.50 | 23.79 | 653.33 | 23.26 | 278.00 | 23.42 |
July | 297.83 | 23.96 | 700.67 | 23.26 | 296.83 | 23.42 |
August | 300.83 | 23.96 | 703.67 | 23.25 | 300.17 | 23.42 |
September | 290.67 | 23.84 | 659.17 | 23.26 | 277.33 | 23.42 |
October | 282.67 | 23.57 | 651.33 | 23.24 | 242.33 | 23.39 |
November | 281.33 | 23.28 | 583.83 | 23.23 | 212.33 | 23.38 |
December | 266.50 | 23.07 | 575.00 | 23.20 | 180.67 | 23.34 |
Annual Sum or Average | 3462.00 | 23.52 | 7537.17 | 23.23 | 2912.00 | 23.38 |
Minimum of Months | 254.00 | 23.07 | 543.83 | 23.17 | 180.67 | 23.33 |
Maximum of Months | 306.33 | 23.96 | 703.67 | 23.26 | 300.17 | 23.42 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 377.67 | 22.75 | 228.17 | 23.17 | 15.83 | 23.19 |
February | 399.00 | 22.53 | 166.33 | 22.90 | 12.83 | 22.90 |
March | 509.33 | 22.36 | 134.17 | 22.64 | 2.67 | 22.64 |
April | 396.00 | 22.61 | 194.50 | 22.92 | 33.83 | 22.97 |
May | 622.50 | 22.49 | 74.17 | 22.61 | 37.83 | 22.67 |
June | 544.50 | 22.66 | 180.50 | 22.92 | 135.00 | 23.04 |
July | 475.33 | 23.14 | 388.17 | 23.33 | 278.33 | 23.42 |
August | 366.17 | 23.59 | 571.83 | 23.56 | 311.67 | 23.62 |
September | 290.50 | 23.37 | 531.33 | 23.56 | 198.83 | 23.61 |
October | 255.83 | 23.10 | 433.67 | 23.56 | 84.83 | 23.60 |
November | 311.50 | 22.95 | 267.83 | 23.35 | 21.67 | 23.35 |
December | 375.17 | 22.92 | 207.33 | 23.27 | 0.00 | 23.27 |
Annual Sum or Average | 4923.50 | 22.82 | 3378.00 | 23.18 | 1133.33 | 23.25 |
Minimum of Months | 255.83 | 22.36 | 74.17 | 22.61 | 0.00 | 22.64 |
Maximum of Months | 622.50 | 23.59 | 571.83 | 23.56 | 311.67 | 23.62 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 477.50 | 23.05 | 99.00 | 23.20 | 11.00 | 23.21 |
February | 466.33 | 22.98 | 74.00 | 23.10 | 9.33 | 23.11 |
March | 522.33 | 22.76 | 73.50 | 22.90 | 0.33 | 22.90 |
April | 412.83 | 22.84 | 196.83 | 23.18 | 12.83 | 23.20 |
May | 445.50 | 22.78 | 159.50 | 23.08 | 24.83 | 23.11 |
June | 381.67 | 22.98 | 327.50 | 23.40 | 96.33 | 23.46 |
July | 414.00 | 23.39 | 423.50 | 23.63 | 225.00 | 23.70 |
August | 366.33 | 23.67 | 445.50 | 23.78 | 280.50 | 23.82 |
September | 255.17 | 23.56 | 406.83 | 23.74 | 165.67 | 23.78 |
October | 215.00 | 23.39 | 305.50 | 23.67 | 61.83 | 23.70 |
November | 376.00 | 23.24 | 138.50 | 23.41 | 18.67 | 23.42 |
December | 499.83 | 23.28 | 52.33 | 23.34 | 0.00 | 23.34 |
Annual Sum or Average | 4832.50 | 23.12 | 2702.50 | 23.39 | 906.33 | 23.45 |
Minimum of Months | 215.00 | 22.76 | 52.33 | 22.90 | 0.00 | 22.90 |
Maximum of Months | 522.33 | 23.67 | 445.50 | 23.78 | 280.50 | 23.82 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 732.00 | 21.48 | 20.67 | 21.47 | 20.67 | 21.45 |
February | 657.17 | 21.38 | 9.50 | 21.38 | 9.50 | 21.37 |
March | 728.00 | 21.34 | 18.17 | 21.32 | 18.17 | 21.30 |
April | 685.33 | 21.47 | 0.33 | 21.47 | 0.33 | 21.47 |
May | 724.67 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
June | 676.83 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
July | 659.83 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
August | 648.33 | 21.43 | 0.33 | 21.43 | 0.00 | 21.43 |
September | 651.17 | 21.46 | 0.83 | 21.47 | 0.00 | 21.47 |
October | 694.67 | 21.50 | 2.33 | 21.51 | 0.00 | 21.51 |
November | 692.67 | 21.49 | 8.33 | 21.49 | 8.33 | 21.48 |
December | 737.67 | 21.52 | 14.83 | 21.52 | 14.83 | 21.51 |
Annual Sum or Average | 8288.33 | 21.46 | 75.33 | 21.45 | 71.83 | 21.45 |
Minimum of Months | 648.33 | 21.34 | 0.00 | 21.32 | 0.00 | 21.30 |
Maximum of Months | 737.67 | 21.52 | 20.67 | 21.52 | 20.67 | 21.51 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.24 | 87.83 | 21.19 | 87.83 | 21.16 |
February | 672.00 | 21.24 | 28.50 | 21.23 | 28.50 | 21.22 |
March | 742.50 | 21.24 | 24.17 | 21.21 | 24.17 | 21.19 |
April | 705.17 | 21.42 | 2.67 | 21.42 | 2.67 | 21.42 |
May | 733.00 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
June | 677.83 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
July | 667.17 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
August | 670.17 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
September | 686.50 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
October | 728.83 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
November | 720.00 | 21.37 | 30.67 | 21.35 | 30.67 | 21.34 |
December | 744.00 | 21.28 | 72.67 | 21.25 | 72.67 | 21.23 |
Annual Sum or Average | 8491.17 | 21.38 | 246.50 | 21.37 | 246.50 | 21.35 |
Minimum of Months | 667.17 | 21.24 | 0.00 | 21.19 | 0.00 | 21.16 |
Maximum of Months | 744.00 | 21.48 | 87.83 | 21.48 | 87.83 | 21.48 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.12 | 56.33 | 21.11 | 56.33 | 21.10 |
February | 672.00 | 21.16 | 25.83 | 21.16 | 25.83 | 21.16 |
March | 744.00 | 21.17 | 1.50 | 21.17 | 1.50 | 21.17 |
April | 720.00 | 21.26 | 0.00 | 21.26 | 0.00 | 21.26 |
May | 744.00 | 21.29 | 0.00 | 21.29 | 0.00 | 21.29 |
June | 720.00 | 21.34 | 0.00 | 21.34 | 0.00 | 21.34 |
July | 744.00 | 21.40 | 0.00 | 21.40 | 0.00 | 21.40 |
August | 744.00 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
September | 720.00 | 21.30 | 0.00 | 21.30 | 0.00 | 21.30 |
October | 744.00 | 21.29 | 0.00 | 21.29 | 0.00 | 21.29 |
November | 720.00 | 21.17 | 66.00 | 21.17 | 66.00 | 21.16 |
December | 744.00 | 21.13 | 83.50 | 21.12 | 83.50 | 21.12 |
Annual Sum or Average | 8760.00 | 21.25 | 233.17 | 21.25 | 233.17 | 21.24 |
Minimum of Months | 672.00 | 21.12 | 0.00 | 21.11 | 0.00 | 21.10 |
Maximum of Months | 744.00 | 21.40 | 83.50 | 21.40 | 83.50 | 21.40 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.83 | 21.56 | 19.50 | 21.55 | 19.50 | 21.54 |
February | 672.00 | 21.46 | 9.67 | 21.45 | 9.67 | 21.44 |
March | 740.67 | 21.43 | 20.50 | 21.40 | 20.50 | 21.38 |
April | 716.17 | 21.62 | 0.00 | 21.62 | 0.00 | 21.62 |
May | 741.00 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
June | 715.67 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
July | 674.00 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
August | 627.00 | 21.41 | 0.00 | 21.41 | 0.00 | 21.41 |
September | 667.50 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
October | 708.67 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
November | 718.33 | 21.59 | 8.67 | 21.58 | 8.67 | 21.57 |
December | 744.00 | 21.58 | 18.00 | 21.56 | 18.00 | 21.55 |
Annual Sum or Average | 8468.83 | 21.54 | 76.33 | 21.53 | 76.33 | 21.53 |
Minimum of Months | 627.00 | 21.41 | 0.00 | 21.40 | 0.00 | 21.38 |
Maximum of Months | 744.00 | 21.62 | 20.50 | 21.62 | 20.50 | 21.62 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.23 | 55.83 | 21.21 | 55.83 | 21.20 |
February | 672.00 | 21.23 | 23.50 | 21.22 | 23.50 | 21.21 |
March | 744.00 | 21.28 | 30.33 | 21.25 | 30.33 | 21.23 |
April | 719.17 | 21.54 | 0.83 | 21.54 | 0.83 | 21.54 |
May | 743.67 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
June | 714.67 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
July | 691.00 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
August | 689.83 | 21.58 | 0.00 | 21.58 | 0.00 | 21.58 |
September | 717.33 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
October | 744.00 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
November | 720.00 | 21.30 | 35.00 | 21.29 | 35.00 | 21.29 |
December | 744.00 | 21.24 | 56.67 | 21.23 | 56.67 | 21.22 |
Annual Sum or Average | 8643.67 | 21.44 | 202.17 | 21.43 | 202.17 | 21.42 |
Minimum of Months | 672.00 | 21.23 | 0.00 | 21.21 | 0.00 | 21.20 |
Maximum of Months | 744.00 | 21.61 | 56.67 | 21.61 | 56.67 | 21.61 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.06 | 0.00 | 22.06 | 0.00 | 22.06 |
February | 672.00 | 22.08 | 0.00 | 22.08 | 0.00 | 22.08 |
March | 744.00 | 21.87 | 0.00 | 21.87 | 0.00 | 21.87 |
April | 720.00 | 22.25 | 0.00 | 22.25 | 0.00 | 22.25 |
May | 744.00 | 22.30 | 0.00 | 22.30 | 0.00 | 22.30 |
June | 720.00 | 22.57 | 13.83 | 22.57 | 13.83 | 22.58 |
July | 744.00 | 22.90 | 74.33 | 22.91 | 74.33 | 22.91 |
August | 742.17 | 23.01 | 96.83 | 23.01 | 96.83 | 23.02 |
September | 715.17 | 22.83 | 26.67 | 22.83 | 26.67 | 22.83 |
October | 705.50 | 22.97 | 31.50 | 22.98 | 30.50 | 22.99 |
November | 720.00 | 22.42 | 0.00 | 22.42 | 0.00 | 22.42 |
December | 744.00 | 22.30 | 0.00 | 22.30 | 0.00 | 22.30 |
Annual Sum or Average | 8714.83 | 22.46 | 243.17 | 22.48 | 242.17 | 22.49 |
Minimum of Months | 672.00 | 21.87 | 0.00 | 21.87 | 0.00 | 21.87 |
Maximum of Months | 744.00 | 23.01 | 96.83 | 23.01 | 96.83 | 23.02 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 729.17 | 21.42 | 69.00 | 21.38 | 69.00 | 21.35 |
February | 656.17 | 21.31 | 38.00 | 21.29 | 38.00 | 21.26 |
March | 723.17 | 21.28 | 48.67 | 21.24 | 48.50 | 21.20 |
April | 674.50 | 21.43 | 6.33 | 21.43 | 6.17 | 21.42 |
May | 714.50 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
June | 662.00 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
July | 642.50 | 21.40 | 6.17 | 21.42 | 0.00 | 21.42 |
August | 631.50 | 21.37 | 18.00 | 21.42 | 3.00 | 21.42 |
September | 638.33 | 21.41 | 8.83 | 21.43 | 2.33 | 21.44 |
October | 686.83 | 21.45 | 5.50 | 21.47 | 0.17 | 21.47 |
November | 690.67 | 21.44 | 32.17 | 21.42 | 32.17 | 21.41 |
December | 735.17 | 21.46 | 69.50 | 21.43 | 69.50 | 21.40 |
Annual Sum or Average | 8184.50 | 21.40 | 302.17 | 21.40 | 268.83 | 21.38 |
Minimum of Months | 631.50 | 21.28 | 0.00 | 21.24 | 0.00 | 21.20 |
Maximum of Months | 735.17 | 21.46 | 69.50 | 21.47 | 69.50 | 21.47 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.15 | 164.67 | 21.09 | 164.67 | 21.05 |
February | 672.00 | 21.15 | 67.33 | 21.12 | 67.33 | 21.08 |
March | 741.67 | 21.18 | 69.67 | 21.13 | 69.67 | 21.09 |
April | 696.33 | 21.39 | 9.33 | 21.39 | 9.33 | 21.38 |
May | 721.50 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
June | 664.33 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
July | 651.33 | 21.42 | 3.83 | 21.43 | 0.00 | 21.43 |
August | 655.17 | 21.41 | 5.33 | 21.42 | 3.33 | 21.42 |
September | 677.00 | 21.44 | 5.33 | 21.43 | 5.33 | 21.43 |
October | 725.50 | 21.43 | 8.00 | 21.42 | 7.67 | 21.42 |
November | 719.67 | 21.28 | 79.00 | 21.26 | 79.00 | 21.24 |
December | 744.00 | 21.18 | 182.67 | 21.13 | 182.67 | 21.10 |
Annual Sum or Average | 8412.50 | 21.32 | 595.17 | 21.29 | 589.00 | 21.27 |
Minimum of Months | 651.33 | 21.15 | 0.00 | 21.09 | 0.00 | 21.05 |
Maximum of Months | 744.00 | 21.44 | 182.67 | 21.43 | 182.67 | 21.43 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 668.83 | 21.46 | 5.83 | 21.46 | 2.33 | 21.46 |
February | 628.67 | 21.41 | 3.50 | 21.41 | 3.50 | 21.41 |
March | 698.33 | 21.35 | 19.33 | 21.33 | 19.33 | 21.31 |
April | 682.50 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
May | 744.00 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
June | 720.00 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
July | 716.33 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
August | 655.33 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
September | 618.33 | 21.36 | 2.33 | 21.36 | 0.00 | 21.36 |
October | 651.00 | 21.41 | 11.33 | 21.45 | 0.00 | 21.45 |
November | 648.83 | 21.48 | 6.00 | 21.49 | 3.50 | 21.49 |
December | 674.67 | 21.49 | 5.50 | 21.50 | 3.50 | 21.49 |
Annual Sum or Average | 8106.83 | 21.45 | 53.83 | 21.45 | 32.17 | 21.45 |
Minimum of Months | 618.33 | 21.35 | 0.00 | 21.33 | 0.00 | 21.31 |
Maximum of Months | 744.00 | 21.55 | 19.33 | 21.55 | 19.33 | 21.55 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 233.67 | 23.24 | 255.33 | 23.61 | 13.83 | 23.62 |
February | 156.50 | 23.30 | 301.33 | 23.72 | 11.83 | 23.73 |
March | 114.83 | 23.05 | 393.67 | 23.71 | 1.50 | 23.71 |
April | 27.00 | 23.64 | 591.67 | 23.89 | 14.50 | 23.89 |
May | 23.67 | 23.86 | 650.67 | 23.91 | 20.50 | 23.91 |
June | 89.83 | 23.99 | 705.33 | 23.91 | 89.50 | 23.92 |
July | 212.67 | 24.00 | 744.00 | 23.94 | 212.67 | 23.95 |
August | 276.83 | 24.00 | 743.83 | 23.93 | 276.83 | 23.95 |
September | 172.50 | 24.00 | 707.17 | 23.91 | 172.50 | 23.92 |
October | 92.67 | 23.77 | 549.00 | 23.89 | 65.17 | 23.90 |
November | 145.33 | 23.45 | 330.17 | 23.78 | 19.83 | 23.79 |
December | 245.17 | 23.33 | 179.00 | 23.59 | 0.00 | 23.59 |
Annual Sum or Average | 1790.67 | 23.62 | 6151.17 | 23.85 | 898.67 | 23.86 |
Minimum of Months | 23.67 | 23.05 | 179.00 | 23.59 | 0.00 | 23.59 |
Maximum of Months | 276.83 | 24.00 | 744.00 | 23.94 | 276.83 | 23.95 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 94.83 | 23.29 | 391.50 | 23.81 | 6.17 | 23.81 |
February | 43.33 | 23.50 | 438.33 | 23.88 | 9.83 | 23.88 |
March | 24.00 | 23.06 | 556.50 | 23.88 | 0.00 | 23.88 |
April | 11.00 | 24.00 | 666.00 | 23.93 | 11.00 | 23.93 |
May | 9.00 | 24.00 | 719.67 | 23.94 | 9.00 | 23.94 |
June | 74.33 | 24.00 | 717.50 | 23.95 | 74.33 | 23.96 |
July | 197.67 | 24.00 | 744.00 | 23.97 | 197.67 | 23.98 |
August | 262.17 | 24.00 | 744.00 | 23.96 | 262.17 | 23.97 |
September | 149.00 | 24.00 | 718.00 | 23.94 | 149.00 | 23.95 |
October | 62.17 | 23.96 | 609.50 | 23.94 | 58.33 | 23.94 |
November | 55.17 | 23.62 | 456.00 | 23.89 | 14.33 | 23.89 |
December | 81.00 | 23.38 | 293.00 | 23.82 | 0.00 | 23.82 |
Annual Sum or Average | 1063.67 | 23.82 | 7054.00 | 23.92 | 791.83 | 23.93 |
Minimum of Months | 9.00 | 23.06 | 293.00 | 23.81 | 0.00 | 23.81 |
Maximum of Months | 262.17 | 24.00 | 744.00 | 23.97 | 262.17 | 23.98 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 533.17 | 23.92 | 680.67 | 23.89 | 515.00 | 23.92 |
February | 472.50 | 23.99 | 640.50 | 23.90 | 471.00 | 23.93 |
March | 537.17 | 23.94 | 710.00 | 23.88 | 526.17 | 23.91 |
April | 522.33 | 23.99 | 713.33 | 23.90 | 522.33 | 23.93 |
May | 544.17 | 23.99 | 743.17 | 23.90 | 544.17 | 23.93 |
June | 545.83 | 23.99 | 720.00 | 23.93 | 545.83 | 23.95 |
July | 573.17 | 23.99 | 744.00 | 23.94 | 573.17 | 23.96 |
August | 575.50 | 23.99 | 744.00 | 23.94 | 575.50 | 23.96 |
September | 545.00 | 23.99 | 720.00 | 23.93 | 545.00 | 23.95 |
October | 542.83 | 23.99 | 738.83 | 23.93 | 542.83 | 23.94 |
November | 508.33 | 23.99 | 686.83 | 23.91 | 507.00 | 23.93 |
December | 515.33 | 23.97 | 673.17 | 23.92 | 510.17 | 23.94 |
Annual Sum or Average | 6415.33 | 23.98 | 8514.50 | 23.91 | 6378.17 | 23.94 |
Minimum of Months | 472.50 | 23.92 | 640.50 | 23.88 | 471.00 | 23.91 |
Maximum of Months | 575.50 | 23.99 | 744.00 | 23.94 | 575.50 | 23.96 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.82 | 2.67 | 21.82 | 2.67 | 21.81 |
February | 672.00 | 21.77 | 0.00 | 21.77 | 0.00 | 21.77 |
March | 744.00 | 21.70 | 0.00 | 21.70 | 0.00 | 21.70 |
April | 720.00 | 22.21 | 0.00 | 22.21 | 0.00 | 22.21 |
May | 744.00 | 22.22 | 0.00 | 22.22 | 0.00 | 22.22 |
June | 697.33 | 22.60 | 0.00 | 22.60 | 0.00 | 22.60 |
July | 599.50 | 22.91 | 5.50 | 22.92 | 0.00 | 22.92 |
August | 519.00 | 22.94 | 17.67 | 22.97 | 0.00 | 22.97 |
September | 652.50 | 22.71 | 3.17 | 22.72 | 0.00 | 22.72 |
October | 635.00 | 22.70 | 13.67 | 22.73 | 0.00 | 22.73 |
November | 720.00 | 22.08 | 0.00 | 22.08 | 0.00 | 22.08 |
December | 744.00 | 21.92 | 0.00 | 21.92 | 0.00 | 21.92 |
Annual Sum or Average | 8191.33 | 22.27 | 42.67 | 22.27 | 2.67 | 22.27 |
Minimum of Months | 519.00 | 21.70 | 0.00 | 21.70 | 0.00 | 21.70 |
Maximum of Months | 744.00 | 22.94 | 17.67 | 22.97 | 2.67 | 22.97 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.48598 | 38.17317 | 0.20222 | 6.08645 |
February | 672.00000 | 22.95808 | 42.07694 | 0.08766 | 5.36267 |
March | 744.00000 | 22.73806 | 46.15037 | 0.05740 | 5.20949 |
April | 720.00000 | 22.63522 | 51.11327 | 0.06231 | 5.25888 |
May | 744.00000 | 22.63738 | 50.72144 | -0.9869 | 25.78242 |
June | 720.00000 | 22.52214 | 57.88516 | -0.9818 | 25.55594 |
July | 744.00000 | 22.85621 | 60.24725 | -0.8416 | 20.18103 |
August | 744.00000 | 22.96034 | 60.71521 | -0.8003 | 18.72924 |
September | 720.00000 | 23.30972 | 56.36864 | -0.6999 | 15.58361 |
October | 744.00000 | 23.54639 | 45.50496 | 0.26937 | 6.74597 |
November | 720.00000 | 23.63444 | 39.51348 | 0.25068 | 6.54268 |
December | 744.00000 | 23.53280 | 33.19185 | 0.17987 | 5.91711 |
Annual Sum or Average | 8760.00000 | 23.06943 | 48.49425 | -0.2688 | 12.29203 |
Minimum of Months | 672.00000 | 22.52214 | 33.19185 | -0.9869 | 5.20949 |
Maximum of Months | 744.00000 | 23.63444 | 60.71521 | 0.26937 | 25.78242 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.07667 | 40.09168 | -0.0451 | 7.07455 |
February | 672.00000 | 21.83650 | 43.69658 | -0.0989 | 6.85888 |
March | 744.00000 | 21.58432 | 47.96036 | -0.1487 | 6.91080 |
April | 720.00000 | 21.79061 | 52.41771 | -0.0468 | 6.05305 |
May | 744.00000 | 21.45422 | 52.96948 | -1.2636 | 38.97719 |
June | 720.00000 | 21.68965 | 59.58158 | -1.1225 | 32.06405 |
July | 744.00000 | 22.14350 | 61.92473 | -0.9294 | 23.76424 |
August | 744.00000 | 22.50026 | 61.64625 | -0.7944 | 19.21279 |
September | 720.00000 | 22.51316 | 58.02624 | -0.8109 | 20.85414 |
October | 744.00000 | 22.63514 | 46.95589 | 0.16802 | 7.16114 |
November | 720.00000 | 22.21589 | 41.63497 | 0.01007 | 6.79308 |
December | 744.00000 | 22.19966 | 34.66517 | -0.0395 | 7.04646 |
Annual Sum or Average | 8760.00000 | 22.05509 | 50.15326 | -0.4288 | 15.28641 |
Minimum of Months | 672.00000 | 21.45422 | 34.66517 | -1.2636 | 6.05305 |
Maximum of Months | 744.00000 | 22.63514 | 61.92473 | 0.16802 | 38.97719 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.68114 | 40.44685 | 0.05608 | 5.56307 |
February | 672.00000 | 22.64702 | 43.48417 | 0.06372 | 5.46791 |
March | 744.00000 | 22.48639 | 47.39413 | 0.04775 | 5.54584 |
April | 720.00000 | 22.82159 | 51.21724 | 0.16299 | 6.03545 |
May | 744.00000 | 22.76437 | 51.01775 | -0.8681 | 21.59692 |
June | 720.00000 | 22.98345 | 57.13720 | -0.7446 | 17.34350 |
July | 744.00000 | 23.23334 | 59.81430 | -0.6296 | 13.81676 |
August | 744.00000 | 23.32298 | 60.34091 | -0.5910 | 12.76459 |
September | 720.00000 | 23.24705 | 57.28530 | -0.6414 | 14.11180 |
October | 744.00000 | 23.26482 | 46.90996 | 0.25689 | 6.79668 |
November | 720.00000 | 22.93130 | 41.74783 | 0.12957 | 5.71557 |
December | 744.00000 | 22.84190 | 35.18331 | 0.06238 | 5.37735 |
Annual Sum or Average | 8760.00000 | 22.93715 | 49.35207 | -0.2264 | 10.03997 |
Minimum of Months | 672.00000 | 22.48639 | 35.18331 | -0.8681 | 5.37735 |
Maximum of Months | 744.00000 | 23.32298 | 60.34091 | 0.25689 | 21.59692 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.82151 | 35.89769 | 0.67298 | 17.55485 |
February | 672.00000 | 22.83479 | 38.67136 | 0.69051 | 17.95143 |
March | 744.00000 | 22.80138 | 42.41682 | 0.70819 | 18.49904 |
April | 720.00000 | 22.82457 | 47.06796 | 0.76279 | 20.08074 |
May | 744.00000 | 22.83775 | 46.59049 | 0.02414 | 10.81887 |
June | 720.00000 | 22.84236 | 53.34744 | 0.08959 | 10.91340 |
July | 744.00000 | 22.85264 | 56.76363 | 0.13250 | 10.83525 |
August | 744.00000 | 22.84593 | 57.59746 | 0.14049 | 11.00664 |
September | 720.00000 | 22.84844 | 54.27943 | 0.09777 | 10.81342 |
October | 744.00000 | 22.86726 | 43.62235 | 0.76612 | 20.19342 |
November | 720.00000 | 22.87124 | 37.54215 | 0.70323 | 18.32482 |
December | 744.00000 | 22.85545 | 30.77745 | 0.64903 | 16.75282 |
Annual Sum or Average | 8760.00000 | 22.84195 | 45.40699 | 0.45160 | 15.29342 |
Minimum of Months | 672.00000 | 22.80138 | 30.77745 | 0.02414 | 10.81342 |
Maximum of Months | 744.00000 | 22.87124 | 57.59746 | 0.76612 | 20.19342 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.22587 | 43.63590 | 0.29460 | 7.86370 |
February | 672.00000 | 22.99885 | 47.02569 | 0.23952 | 7.21457 |
March | 744.00000 | 22.72776 | 51.04035 | 0.18439 | 6.86807 |
April | 720.00000 | 22.93838 | 55.19308 | 0.27896 | 7.20608 |
May | 744.00000 | 22.63219 | 55.59912 | -0.8179 | 19.93545 |
June | 720.00000 | 22.80484 | 61.95679 | -0.6994 | 16.05472 |
July | 744.00000 | 23.06330 | 64.59792 | -0.5664 | 12.27067 |
August | 744.00000 | 23.32667 | 64.55751 | -0.4545 | 9.75573 |
September | 720.00000 | 23.41587 | 60.93692 | -0.4421 | 9.95627 |
October | 744.00000 | 23.51231 | 50.41707 | 0.43983 | 9.75537 |
November | 720.00000 | 23.36892 | 45.05131 | 0.34593 | 8.22980 |
December | 744.00000 | 23.34909 | 38.56966 | 0.29918 | 7.68959 |
Annual Sum or Average | 8760.00000 | 23.11441 | 53.23782 | -0.0768 | 10.25674 |
Minimum of Months | 672.00000 | 22.63219 | 38.56966 | -0.8179 | 6.86807 |
Maximum of Months | 744.00000 | 23.51231 | 64.59792 | 0.43983 | 19.93545 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.30557 | 42.77140 | 0.23980 | 6.64480 |
February | 672.00000 | 23.22036 | 45.76794 | 0.23272 | 6.51182 |
March | 744.00000 | 23.04145 | 49.63763 | 0.20967 | 6.43831 |
April | 720.00000 | 23.22684 | 53.68262 | 0.29128 | 7.20675 |
May | 744.00000 | 23.16658 | 53.48738 | -0.6983 | 16.04828 |
June | 720.00000 | 23.31400 | 59.58909 | -0.5946 | 13.15113 |
July | 744.00000 | 23.44606 | 62.43018 | -0.5164 | 11.15171 |
August | 744.00000 | 23.51519 | 62.92590 | -0.4829 | 10.32067 |
September | 720.00000 | 23.53713 | 59.66059 | -0.5000 | 10.64765 |
October | 744.00000 | 23.62091 | 49.24741 | 0.38234 | 8.35555 |
November | 720.00000 | 23.47242 | 44.10042 | 0.29503 | 7.12970 |
December | 744.00000 | 23.44471 | 37.68450 | 0.24249 | 6.46905 |
Annual Sum or Average | 8760.00000 | 23.36010 | 51.77041 | -0.0769 | 9.19087 |
Minimum of Months | 672.00000 | 23.04145 | 37.68450 | -0.6983 | 6.43831 |
Maximum of Months | 744.00000 | 23.62091 | 62.92590 | 0.38234 | 16.04828 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.50707 | 46.03617 | -0.2467 | 7.15229 |
February | 672.00000 | 21.42472 | 49.14960 | -0.2497 | 7.02079 |
March | 744.00000 | 21.38631 | 52.60524 | -0.2445 | 7.03184 |
April | 720.00000 | 21.56107 | 55.35057 | -0.1368 | 6.20329 |
May | 744.00000 | 21.52465 | 55.45921 | -1.2850 | 40.35749 |
June | 720.00000 | 21.58422 | 58.70980 | -1.2071 | 36.60678 |
July | 744.00000 | 21.66047 | 58.99494 | -1.1397 | 33.63194 |
August | 744.00000 | 21.67270 | 59.29956 | -1.1285 | 33.22071 |
September | 720.00000 | 21.64290 | 58.47634 | -1.1664 | 34.97118 |
October | 744.00000 | 21.62305 | 50.39704 | -0.1190 | 6.18675 |
November | 720.00000 | 21.56163 | 47.11947 | -0.2029 | 6.76926 |
December | 744.00000 | 21.53963 | 40.57729 | -0.2604 | 7.30769 |
Annual Sum or Average | 8760.00000 | 21.55813 | 52.68583 | -0.6179 | 18.94424 |
Minimum of Months | 672.00000 | 21.38631 | 40.57729 | -1.2850 | 6.18675 |
Maximum of Months | 744.00000 | 21.67270 | 59.29956 | -0.1190 | 40.35749 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.23608 | 46.98691 | -0.3543 | 8.15536 |
February | 672.00000 | 21.24273 | 49.84331 | -0.3233 | 7.60224 |
March | 744.00000 | 21.24158 | 53.31222 | -0.2996 | 7.38441 |
April | 720.00000 | 21.46361 | 56.11716 | -0.1734 | 6.26269 |
May | 744.00000 | 21.49469 | 55.62981 | -1.2992 | 40.97242 |
June | 720.00000 | 21.57545 | 58.62313 | -1.2095 | 36.68674 |
July | 744.00000 | 21.64989 | 59.06290 | -1.1457 | 33.84671 |
August | 744.00000 | 21.63690 | 60.07305 | -1.1538 | 34.21087 |
September | 720.00000 | 21.55852 | 59.91665 | -1.2191 | 37.12573 |
October | 744.00000 | 21.51468 | 51.41920 | -0.1723 | 6.29498 |
November | 720.00000 | 21.36516 | 48.17791 | -0.2888 | 7.33910 |
December | 744.00000 | 21.27741 | 41.33423 | -0.3705 | 8.34087 |
Annual Sum or Average | 8760.00000 | 21.43909 | 53.37815 | -0.6697 | 19.59086 |
Minimum of Months | 672.00000 | 21.23608 | 41.33423 | -1.2992 | 6.26269 |
Maximum of Months | 744.00000 | 21.64989 | 60.07305 | -0.1723 | 40.97242 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.12347 | 45.34343 | -0.3894 | 8.35079 |
February | 672.00000 | 21.16287 | 48.28184 | -0.3552 | 7.76140 |
March | 744.00000 | 21.17434 | 51.82567 | -0.3295 | 7.38288 |
April | 720.00000 | 21.25506 | 55.33991 | -0.2701 | 6.63532 |
May | 744.00000 | 21.28805 | 54.61151 | -1.4309 | 47.21501 |
June | 720.00000 | 21.33904 | 58.45233 | -1.3686 | 43.94557 |
July | 744.00000 | 21.39862 | 60.34329 | -1.3276 | 41.87550 |
August | 744.00000 | 21.37049 | 61.63140 | -1.3382 | 42.39966 |
September | 720.00000 | 21.29885 | 60.19030 | -1.3869 | 44.92413 |
October | 744.00000 | 21.29062 | 50.73670 | -0.2755 | 6.78797 |
November | 720.00000 | 21.17012 | 46.85209 | -0.3577 | 7.85693 |
December | 744.00000 | 21.12644 | 39.79105 | -0.4198 | 8.84376 |
Annual Sum or Average | 8760.00000 | 21.25037 | 52.79371 | -0.7734 | 22.92247 |
Minimum of Months | 672.00000 | 21.12347 | 39.79105 | -1.4309 | 6.63532 |
Maximum of Months | 744.00000 | 21.39862 | 61.63140 | -0.2701 | 47.21501 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.56077 | 45.88401 | -0.2316 | 6.96030 |
February | 672.00000 | 21.45527 | 49.10906 | -0.2473 | 6.98615 |
March | 744.00000 | 21.43581 | 52.35260 | -0.2349 | 6.97037 |
April | 720.00000 | 21.62896 | 55.13460 | -0.1277 | 6.20866 |
May | 744.00000 | 21.56967 | 55.25696 | -1.2847 | 40.34783 |
June | 720.00000 | 21.62004 | 58.96400 | -1.2124 | 36.91779 |
July | 744.00000 | 21.71251 | 59.27641 | -1.1340 | 33.46630 |
August | 744.00000 | 21.71603 | 59.42735 | -1.1200 | 32.90767 |
September | 720.00000 | 21.65380 | 59.10959 | -1.1795 | 35.58209 |
October | 744.00000 | 21.64721 | 50.53382 | -0.1168 | 6.13736 |
November | 720.00000 | 21.58978 | 47.18262 | -0.2012 | 6.67287 |
December | 744.00000 | 21.57568 | 40.53064 | -0.2528 | 7.15116 |
Annual Sum or Average | 8760.00000 | 21.59801 | 52.73395 | -0.6142 | 18.92938 |
Minimum of Months | 672.00000 | 21.43581 | 40.53064 | -1.2847 | 6.13736 |
Maximum of Months | 744.00000 | 21.71603 | 59.42735 | -0.1168 | 40.34783 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.22657 | 46.86205 | -0.3510 | 7.93172 |
February | 672.00000 | 21.22954 | 49.91708 | -0.3294 | 7.53570 |
March | 744.00000 | 21.28171 | 53.10147 | -0.2917 | 7.26754 |
April | 720.00000 | 21.54392 | 55.73357 | -0.1630 | 6.20430 |
May | 744.00000 | 21.54004 | 55.42419 | -1.2990 | 40.94419 |
June | 720.00000 | 21.61869 | 58.89917 | -1.2126 | 36.88994 |
July | 744.00000 | 21.71236 | 59.39483 | -1.1367 | 33.54506 |
August | 744.00000 | 21.70721 | 60.13005 | -1.1379 | 33.60690 |
September | 720.00000 | 21.57848 | 60.32949 | -1.2319 | 37.70544 |
October | 744.00000 | 21.55180 | 51.46652 | -0.1682 | 6.16834 |
November | 720.00000 | 21.30262 | 48.38880 | -0.3052 | 7.27352 |
December | 744.00000 | 21.23899 | 41.44774 | -0.3767 | 8.20812 |
Annual Sum or Average | 8760.00000 | 21.46235 | 53.42696 | -0.6690 | 19.50965 |
Minimum of Months | 672.00000 | 21.22657 | 41.44774 | -1.2990 | 6.16834 |
Maximum of Months | 744.00000 | 21.71236 | 60.32949 | -0.1630 | 40.94419 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.45704 | 46.94413 | -0.2840 | 7.71176 |
February | 672.00000 | 21.36079 | 50.20487 | -0.2892 | 7.60728 |
March | 744.00000 | 21.33493 | 53.71902 | -0.2764 | 7.57164 |
April | 720.00000 | 21.55057 | 56.50513 | -0.1470 | 6.44666 |
May | 744.00000 | 21.51204 | 56.58955 | -1.3039 | 41.50685 |
June | 720.00000 | 21.58461 | 60.03936 | -1.2107 | 37.00921 |
July | 744.00000 | 21.66445 | 60.43245 | -1.1345 | 33.61587 |
August | 744.00000 | 21.66835 | 60.95299 | -1.1275 | 33.38521 |
September | 720.00000 | 21.63003 | 60.35829 | -1.1762 | 35.63074 |
October | 744.00000 | 21.59414 | 51.67684 | -0.1370 | 6.43020 |
November | 720.00000 | 21.51411 | 48.24525 | -0.2373 | 7.22388 |
December | 744.00000 | 21.48322 | 41.33904 | -0.3023 | 7.93127 |
Annual Sum or Average | 8760.00000 | 21.53047 | 53.92179 | -0.6377 | 19.41111 |
Minimum of Months | 672.00000 | 21.33493 | 41.33904 | -1.3039 | 6.43020 |
Maximum of Months | 744.00000 | 21.66835 | 60.95299 | -0.1370 | 41.50685 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.14758 | 47.97869 | -0.4057 | 9.02750 |
February | 672.00000 | 21.15447 | 50.95379 | -0.3724 | 8.39334 |
March | 744.00000 | 21.18185 | 54.45109 | -0.3362 | 8.00425 |
April | 720.00000 | 21.45524 | 57.30472 | -0.1853 | 6.50989 |
May | 744.00000 | 21.48454 | 56.77526 | -1.3178 | 42.09725 |
June | 720.00000 | 21.57835 | 59.98799 | -1.2123 | 37.04168 |
July | 744.00000 | 21.65790 | 60.53957 | -1.1394 | 33.77715 |
August | 744.00000 | 21.64050 | 61.83094 | -1.1512 | 34.29880 |
September | 720.00000 | 21.54844 | 62.01957 | -1.2303 | 37.82974 |
October | 744.00000 | 21.47620 | 52.84638 | -0.1953 | 6.59165 |
November | 720.00000 | 21.28524 | 49.34389 | -0.3367 | 8.03435 |
December | 744.00000 | 21.17721 | 42.20501 | -0.4285 | 9.34308 |
Annual Sum or Average | 8760.00000 | 21.40023 | 54.68994 | -0.6947 | 20.15017 |
Minimum of Months | 672.00000 | 21.14758 | 42.20501 | -1.3178 | 6.50989 |
Maximum of Months | 744.00000 | 21.65790 | 62.01957 | -0.1853 | 42.09725 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.64490 | 45.59438 | -0.1707 | 6.86099 |
February | 672.00000 | 21.53258 | 48.90124 | -0.2087 | 6.92677 |
March | 744.00000 | 21.47154 | 52.25711 | -0.2250 | 7.08908 |
April | 720.00000 | 21.58241 | 55.49957 | -0.1568 | 6.43574 |
May | 744.00000 | 21.46509 | 56.26002 | -1.3670 | 44.38859 |
June | 720.00000 | 21.50978 | 60.63086 | -1.2979 | 40.86883 |
July | 744.00000 | 21.61716 | 61.55072 | -1.2197 | 37.29023 |
August | 744.00000 | 21.64925 | 60.89919 | -1.1836 | 35.79055 |
September | 720.00000 | 21.63537 | 58.54641 | -1.1936 | 36.45558 |
October | 744.00000 | 21.65344 | 50.14881 | -0.1075 | 6.35731 |
November | 720.00000 | 21.66570 | 46.60718 | -0.1520 | 6.70239 |
December | 744.00000 | 21.66357 | 40.35100 | -0.1872 | 7.03686 |
Annual Sum or Average | 8760.00000 | 21.59130 | 53.11412 | -0.6250 | 20.26588 |
Minimum of Months | 672.00000 | 21.46509 | 40.35100 | -1.3670 | 6.35731 |
Maximum of Months | 744.00000 | 21.66570 | 61.55072 | -0.1075 | 44.38859 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.64944 | 43.28469 | 0.35063 | 7.97602 |
February | 672.00000 | 23.69475 | 45.67883 | 0.38171 | 8.33480 |
March | 744.00000 | 23.69265 | 49.16787 | 0.40765 | 8.74301 |
April | 720.00000 | 23.82042 | 52.91729 | 0.48982 | 10.19540 |
May | 744.00000 | 23.84679 | 52.31803 | -0.3797 | 8.19813 |
June | 720.00000 | 23.89182 | 58.19711 | -0.2939 | 6.93640 |
July | 744.00000 | 23.92503 | 61.15163 | -0.2424 | 6.28615 |
August | 744.00000 | 23.91042 | 61.98971 | -0.2458 | 6.32932 |
September | 720.00000 | 23.87381 | 59.22262 | -0.3020 | 7.05695 |
October | 744.00000 | 23.85455 | 49.40945 | 0.49128 | 10.33004 |
November | 720.00000 | 23.73500 | 44.51275 | 0.39108 | 8.52291 |
December | 744.00000 | 23.68827 | 38.36864 | 0.32728 | 7.52987 |
Annual Sum or Average | 8760.00000 | 23.79909 | 51.37230 | 0.11292 | 8.03258 |
Minimum of Months | 672.00000 | 23.64944 | 38.36864 | -0.3797 | 6.28615 |
Maximum of Months | 744.00000 | 23.92503 | 61.98971 | 0.49128 | 10.33004 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.78595 | 42.31945 | 0.41723 | 8.95025 |
February | 672.00000 | 23.82456 | 44.68063 | 0.44730 | 9.40692 |
March | 744.00000 | 23.82947 | 48.12843 | 0.47563 | 9.91574 |
April | 720.00000 | 23.90930 | 52.00904 | 0.54434 | 11.33044 |
May | 744.00000 | 23.92563 | 51.43947 | -0.3035 | 7.03731 |
June | 720.00000 | 23.94794 | 57.42194 | -0.2286 | 6.17183 |
July | 744.00000 | 23.96454 | 60.47105 | -0.1860 | 5.75682 |
August | 744.00000 | 23.95309 | 61.31068 | -0.1897 | 5.78794 |
September | 720.00000 | 23.93038 | 58.45877 | -0.2389 | 6.29531 |
October | 744.00000 | 23.91607 | 48.68499 | 0.53499 | 11.23229 |
November | 720.00000 | 23.84708 | 43.60041 | 0.45045 | 9.51270 |
December | 744.00000 | 23.81267 | 37.44519 | 0.39035 | 8.41762 |
Annual Sum or Average | 8760.00000 | 23.88750 | 50.51929 | 0.17439 | 8.30887 |
Minimum of Months | 672.00000 | 23.78595 | 37.44519 | -0.3035 | 5.75682 |
Maximum of Months | 744.00000 | 23.96454 | 61.31068 | 0.54434 | 11.33044 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.74795 | 40.94966 | 1.05206 | 31.06765 |
February | 672.00000 | 23.79177 | 43.35266 | 1.07548 | 31.71967 |
March | 744.00000 | 23.76812 | 46.73268 | 1.09753 | 32.85577 |
April | 720.00000 | 23.83115 | 50.84039 | 1.17513 | 35.98366 |
May | 744.00000 | 23.83793 | 50.41058 | 0.58744 | 17.01712 |
June | 720.00000 | 23.87673 | 56.42925 | 0.67278 | 18.78320 |
July | 744.00000 | 23.90287 | 59.46170 | 0.73341 | 20.27581 |
August | 744.00000 | 23.90520 | 60.18947 | 0.73918 | 20.39444 |
September | 720.00000 | 23.88249 | 57.26634 | 0.67775 | 18.81927 |
October | 744.00000 | 23.87074 | 47.67274 | 1.17730 | 35.96255 |
November | 720.00000 | 23.80113 | 42.35356 | 1.08331 | 32.05802 |
December | 744.00000 | 23.77982 | 36.19594 | 1.02751 | 29.83465 |
Annual Sum or Average | 8760.00000 | 23.83317 | 49.34399 | 0.92392 | 27.03321 |
Minimum of Months | 672.00000 | 23.74795 | 36.19594 | 0.58744 | 17.01712 |
Maximum of Months | 744.00000 | 23.90520 | 60.18947 | 1.17730 | 35.98366 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.68839 | 39.58386 | -0.2327 | 6.60258 |
February | 672.00000 | 21.70860 | 42.73063 | -0.2100 | 6.07924 |
March | 744.00000 | 21.56831 | 46.76570 | -0.2201 | 6.29183 |
April | 720.00000 | 21.96398 | 50.68192 | -0.0963 | 5.44022 |
May | 744.00000 | 22.12953 | 49.85743 | -1.1486 | 32.95316 |
June | 720.00000 | 22.51526 | 55.70422 | -0.9751 | 25.25097 |
July | 744.00000 | 22.80775 | 58.62929 | -0.8520 | 20.41314 |
August | 744.00000 | 22.78968 | 59.65173 | -0.8524 | 20.41579 |
September | 720.00000 | 22.58182 | 56.63325 | -0.9459 | 24.06048 |
October | 744.00000 | 22.67312 | 45.60723 | 0.05339 | 5.43499 |
November | 720.00000 | 22.00940 | 40.87501 | -0.1451 | 5.67141 |
December | 744.00000 | 21.84124 | 33.97701 | -0.2297 | 6.32546 |
Annual Sum or Average | 8760.00000 | 22.19286 | 48.40967 | -0.4896 | 13.79303 |
Minimum of Months | 672.00000 | 21.56831 | 33.97701 | -1.1486 | 5.43499 |
Maximum of Months | 744.00000 | 22.80775 | 59.65173 | 0.05339 | 32.95316 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.06414 | 42.46943 | -0.1435 | 5.85063 |
February | 672.00000 | 22.07722 | 45.59043 | -0.1229 | 5.46097 |
March | 744.00000 | 21.87216 | 49.60706 | -0.1485 | 5.74876 |
April | 720.00000 | 22.24623 | 53.54393 | -0.0299 | 5.26641 |
May | 744.00000 | 22.30252 | 53.04588 | -1.1022 | 30.81917 |
June | 720.00000 | 22.56764 | 59.20531 | -0.9688 | 24.99616 |
July | 744.00000 | 22.89629 | 61.80994 | -0.8335 | 19.74786 |
August | 744.00000 | 23.00955 | 62.32631 | -0.7898 | 18.20750 |
September | 720.00000 | 22.83868 | 59.42006 | -0.8699 | 21.11729 |
October | 744.00000 | 23.00459 | 48.45021 | 0.13231 | 5.69164 |
November | 720.00000 | 22.42297 | 43.69324 | -0.0467 | 5.23506 |
December | 744.00000 | 22.30443 | 36.85992 | -0.1196 | 5.47739 |
Annual Sum or Average | 8760.00000 | 22.46984 | 51.35353 | -0.4221 | 12.84708 |
Minimum of Months | 672.00000 | 21.87216 | 36.85992 | -1.1022 | 5.23506 |
Maximum of Months | 744.00000 | 23.00955 | 62.32631 | 0.13231 | 30.81917 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.81919 | 40.45628 | -0.1809 | 6.25943 |
February | 672.00000 | 21.77083 | 43.71025 | -0.1737 | 5.96435 |
March | 744.00000 | 21.70479 | 47.54012 | -0.1670 | 6.06605 |
April | 720.00000 | 22.21077 | 51.12887 | -0.0117 | 5.42369 |
May | 744.00000 | 22.22493 | 50.71799 | -1.0834 | 30.19864 |
June | 720.00000 | 22.61888 | 56.49373 | -0.9024 | 22.60622 |
July | 744.00000 | 23.00339 | 58.85997 | -0.7455 | 16.92619 |
August | 744.00000 | 23.08925 | 59.44252 | -0.7109 | 15.84726 |
September | 720.00000 | 22.78875 | 57.01419 | -0.8374 | 20.22123 |
October | 744.00000 | 22.83625 | 46.23047 | 0.12118 | 5.88713 |
November | 720.00000 | 22.08107 | 41.83348 | -0.1046 | 5.60411 |
December | 744.00000 | 21.92339 | 35.03108 | -0.1882 | 6.11000 |
Annual Sum or Average | 8760.00000 | 22.34303 | 49.05377 | -0.4168 | 12.29807 |
Minimum of Months | 672.00000 | 21.70479 | 35.03108 | -1.0834 | 5.42369 |
Maximum of Months | 744.00000 | 23.08925 | 59.44252 | 0.12118 | 30.19864 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.84032 | 38.66090 | -0.1908 | 6.31457 |
February | 672.00000 | 21.87966 | 41.73556 | -0.1638 | 5.77808 |
March | 744.00000 | 21.74243 | 45.75456 | -0.1729 | 5.96035 |
April | 720.00000 | 22.13389 | 49.62788 | -0.0491 | 5.36394 |
May | 744.00000 | 22.31835 | 48.75145 | -1.0737 | 29.61876 |
June | 720.00000 | 22.70100 | 54.53058 | -0.8998 | 22.38375 |
July | 744.00000 | 22.98463 | 57.38353 | -0.7792 | 17.99443 |
August | 744.00000 | 22.95920 | 58.39695 | -0.7823 | 18.08647 |
September | 720.00000 | 22.74247 | 55.50533 | -0.8791 | 21.57644 |
October | 744.00000 | 22.83173 | 44.56281 | 0.09883 | 5.64543 |
November | 720.00000 | 22.16902 | 39.91078 | -0.1011 | 5.50950 |
December | 744.00000 | 21.99928 | 33.09056 | -0.1865 | 6.01968 |
Annual Sum or Average | 8760.00000 | 22.36158 | 47.34372 | -0.4333 | 12.56336 |
Minimum of Months | 672.00000 | 21.74243 | 33.09056 | -1.0737 | 5.36394 |
Maximum of Months | 744.00000 | 22.98463 | 58.39695 | 0.09883 | 29.61876 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.377350E+11 | 85736.54 | 14-JAN-11:33 | 626.19 | 0.117040E+12 | 0.00 | 0.154775E+12 | 2.63 | 3.82 | 15-JAN-09:02 | 0.00 | 0.00 |
February | 0.243946E+11 | 78386.10 | 01-FEB-11:50 | 557.57 | 0.747856E+11 | 0.00 | 0.991802E+11 | 2.59 | 3.79 | 01-FEB-09:02 | 0.00 | 0.00 |
March | 0.241913E+11 | 80682.58 | 23-MAR-15:02 | 576.18 | 0.753369E+11 | 0.00 | 0.995282E+11 | 2.43 | 3.96 | 23-MAR-15:02 | 0.00 | 0.00 |
April | 0.488796E+11 | 86823.93 | 26-APR-10:45 | 692.58 | 0.151196E+12 | 0.00 | 0.200076E+12 | 2.99 | 4.00 | 26-APR-18:03 | 0.00 | 0.00 |
May | 0.520465E+11 | 86417.46 | 18-MAY-15:02 | 730.81 | 0.156713E+12 | 0.00 | 0.208760E+12 | 3.01 | 4.05 | 18-MAY-15:02 | 0.00 | 0.00 |
June | 0.842378E+11 | 109045.63 | 29-JUN-18:03 | 719.17 | 0.270468E+12 | 0.00 | 0.354706E+12 | 3.12 | 4.32 | 27-JUN-18:03 | 0.00 | 0.00 |
July | 0.143595E+12 | 136483.46 | 19-JUL-15:02 | 744.00 | 0.509930E+12 | 0.00 | 0.653525E+12 | 3.40 | 4.45 | 13-JUL-18:03 | 0.00 | 0.00 |
August | 0.156853E+12 | 144554.20 | 18-AUG-15:03 | 744.00 | 0.569249E+12 | 0.00 | 0.726102E+12 | 3.50 | 4.48 | 24-AUG-18:03 | 0.00 | 0.00 |
September | 0.106821E+12 | 165153.37 | 29-SEP-10:33 | 719.50 | 0.358074E+12 | 0.00 | 0.464895E+12 | 3.23 | 4.39 | 09-SEP-18:02 | 0.00 | 0.00 |
October | 0.117332E+12 | 181196.94 | 16-OCT-11:00 | 742.17 | 0.400618E+12 | 0.00 | 0.517950E+12 | 3.26 | 4.45 | 05-OCT-18:02 | 0.00 | 0.00 |
November | 0.402832E+11 | 93575.15 | 19-NOV-09:02 | 668.79 | 0.125063E+12 | 0.00 | 0.165346E+12 | 2.89 | 3.82 | 19-NOV-09:02 | 0.00 | 0.00 |
December | 0.419471E+11 | 88881.68 | 05-DEC-09:02 | 638.56 | 0.132266E+12 | 0.00 | 0.174213E+12 | 2.69 | 3.89 | 05-DEC-19:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.878316E+12 | 8159.51 | 0.294074E+13 | 0.00 | 0.381906E+13 | 2.98 | 0.00 | 0.00 | ||||
Minimum of Months | 0.241913E+11 | 78386.10 | 557.57 | 0.747856E+11 | 0.00 | 0.991802E+11 | 2.43 | 3.79 | 0.00 | 0.00 | ||
Maximum of Months | 0.156853E+12 | 181196.94 | 744.00 | 0.569249E+12 | 0.00 | 0.726102E+12 | 3.50 | 4.48 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.121428E+12 | 0.00 | 556.59 | 181927.27 | 08-JAN-07:00 | 0.00 | 42.96 | 71.89 | 0.29 | 0.00 | 0.16 | 0.64 | 08-JAN-07:00 |
February | 0.845217E+11 | 0.00 | 548.06 | 151955.47 | 04-FEB-06:00 | 0.00 | 39.02 | 72.28 | 0.21 | 0.00 | 0.12 | 0.54 | 04-FEB-06:00 |
March | 0.121528E+12 | 0.00 | 600.96 | 185956.25 | 29-MAR-08:62 | 0.00 | 36.59 | 71.36 | 0.28 | 0.00 | 0.16 | 0.66 | 29-MAR-08:62 |
April | 0.452232E+11 | 0.00 | 409.43 | 136896.41 | 01-APR-06:00 | 0.00 | 31.10 | 58.63 | 0.09 | 0.00 | 0.06 | 0.48 | 01-APR-06:00 |
May | 0.393756E+11 | 0.00 | 372.85 | 116742.77 | 14-MAY-04:50 | 0.00 | 31.08 | 54.97 | 0.08 | 0.00 | 0.05 | 0.41 | 14-MAY-04:50 |
June | 0.632708E+10 | 0.00 | 163.63 | 63382.46 | 13-JUN-04:00 | 0.00 | 33.83 | 44.83 | 0.01 | 0.00 | 0.01 | 0.22 | 13-JUN-04:00 |
July | 0.420170E+09 | 0.00 | 40.96 | 33541.50 | 18-JUL-08:05 | 0.00 | 43.22 | 45.39 | 0.00 | 0.00 | 0.00 | 0.12 | 18-JUL-08:05 |
August | 0.178425E+09 | 0.00 | 36.72 | 31740.51 | 29-AUG-18:05 | 0.00 | 51.70 | 53.21 | 0.00 | 0.00 | 0.00 | 0.11 | 29-AUG-18:05 |
September | 0.301940E+10 | 0.00 | 103.35 | 59258.40 | 20-SEP-04:00 | 0.00 | 44.15 | 49.99 | 0.01 | 0.00 | 0.00 | 0.21 | 20-SEP-04:00 |
October | 0.161750E+11 | 0.00 | 196.80 | 97168.53 | 29-OCT-06:00 | 0.00 | 42.05 | 53.02 | 0.03 | 0.00 | 0.02 | 0.34 | 29-OCT-06:00 |
November | 0.693283E+11 | 0.00 | 510.26 | 144072.18 | 29-NOV-23:00 | 0.00 | 39.83 | 68.76 | 0.16 | 0.00 | 0.09 | 0.51 | 29-NOV-23:00 |
December | 0.115281E+12 | 0.00 | 565.62 | 156372.34 | 23-DEC-06:00 | 0.00 | 43.33 | 72.55 | 0.27 | 0.00 | 0.15 | 0.55 | 23-DEC-06:00 |
Annual Sum or Average | 0.622805E+12 | 0.00 | 4105.21 | 0.00 | 39.94 | 59.68 | 0.12 | 0.00 | 0.07 | ||||
Minimum of Months | 0.178425E+09 | 0.00 | 36.72 | 31740.51 | 0.00 | 31.08 | 44.83 | 0.00 | 0.00 | 0.00 | 0.11 | ||
Maximum of Months | 0.121528E+12 | 0.00 | 600.96 | 185956.25 | 0.00 | 51.70 | 72.55 | 0.29 | 0.00 | 0.16 | 0.66 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.572450E+11 | 0.00 | 284.67 | 0.571054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 208585.96 | 14-JAN-11:45 | 208585.96 | 14-JAN-11:45 | 0.00 | 0.00 | 0.00 |
February | 0.316038E+11 | 0.00 | 229.89 | 0.308895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 196578.24 | 01-FEB-11:45 | 196578.24 | 01-FEB-11:45 | 0.00 | 0.00 | 0.00 |
March | 0.353233E+11 | 0.00 | 211.83 | 0.346290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 183126.88 | 23-MAR-10:50 | 176357.25 | 11-MAR-11:45 | 0.00 | 0.00 | 0.00 |
April | 0.843398E+11 | 0.00 | 358.47 | 0.827112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 251962.06 | 26-APR-10:45 | 207485.73 | 30-APR-10:45 | 0.00 | 0.00 | 0.00 |
May | 0.901865E+11 | 0.00 | 436.58 | 0.891896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 161605.97 | 18-MAY-10:50 | 157042.39 | 04-MAY-12:00 | 0.00 | 0.00 | 0.00 |
June | 0.168634E+12 | 0.00 | 614.92 | 0.146349E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 312457.46 | 29-JUN-10:50 | 191271.96 | 29-JUN-10:50 | 0.00 | 0.00 | 0.00 |
July | 0.346290E+12 | 0.00 | 735.08 | 0.224669E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 381630.33 | 31-JUL-10:45 | 241095.37 | 19-JUL-10:45 | 0.00 | 0.00 | 0.00 |
August | 0.390374E+12 | 0.00 | 736.67 | 0.234633E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 409086.71 | 14-AUG-10:45 | 241002.03 | 14-AUG-10:45 | 0.00 | 0.00 | 0.00 |
September | 0.229545E+12 | 0.00 | 675.00 | 0.176186E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 373514.51 | 22-SEP-12:00 | 364902.33 | 29-SEP-10:50 | 0.00 | 0.00 | 0.00 |
October | 0.260389E+12 | 0.00 | 619.33 | 0.209062E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 384410.71 | 16-OCT-10:50 | 384410.71 | 16-OCT-10:50 | 0.00 | 0.00 | 0.00 |
November | 0.593969E+11 | 0.00 | 341.61 | 0.587286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 213511.11 | 19-NOV-11:50 | 213511.11 | 19-NOV-11:50 | 0.00 | 0.00 | 0.00 |
December | 0.661316E+11 | 0.00 | 294.67 | 0.661316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 192550.31 | 16-DEC-13:00 | 192550.31 | 16-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181946E+13 | 0.00 | 5538.72 | 0.141028E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.316038E+11 | 0.00 | 211.83 | 0.308895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 161605.97 | 157042.39 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.390374E+12 | 0.00 | 736.67 | 0.234633E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 409086.71 | 384410.71 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.113067E+11 | 0.00 | 275.67 | 0.111344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35831.89 | 17-JAN-14:00 | 34701.69 | 18-JAN-13:00 | 0.00 | 0.00 | 0.00 |
February | 0.624901E+10 | 0.00 | 211.33 | 0.601784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34702.50 | 01-FEB-12:00 | 34702.50 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.724922E+10 | 0.00 | 192.33 | 0.662458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38122.69 | 23-MAR-15:00 | 29771.76 | 11-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.170527E+11 | 0.00 | 332.17 | 0.156679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45682.01 | 26-APR-11:00 | 37320.26 | 26-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.176695E+11 | 0.00 | 414.50 | 0.169867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33097.58 | 04-MAY-13:10 | 29927.15 | 04-MAY-12:00 | 0.00 | 0.00 | 0.00 |
June | 0.354046E+11 | 0.00 | 609.17 | 0.276503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50379.43 | 29-JUN-11:00 | 30610.28 | 29-JUN-11:00 | 0.00 | 0.00 | 0.00 |
July | 0.697043E+11 | 0.00 | 736.00 | 0.417303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59117.88 | 31-JUL-12:20 | 37187.60 | 19-JUL-10:55 | 0.00 | 0.00 | 0.00 |
August | 0.780509E+11 | 0.00 | 737.50 | 0.433674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59096.39 | 14-AUG-10:55 | 36192.18 | 18-AUG-12:00 | 0.00 | 0.00 | 0.00 |
September | 0.472441E+11 | 0.00 | 667.50 | 0.329404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61100.16 | 22-SEP-12:00 | 59337.85 | 29-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.510747E+11 | 0.00 | 612.50 | 0.388693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61507.15 | 16-OCT-10:55 | 61507.15 | 16-OCT-10:55 | 0.00 | 0.00 | 0.00 |
November | 0.116003E+11 | 0.00 | 320.50 | 0.113170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37158.21 | 19-NOV-13:00 | 37158.21 | 19-NOV-13:00 | 0.00 | 0.00 | 0.00 |
December | 0.131328E+11 | 0.00 | 279.83 | 0.131083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34610.58 | 16-DEC-13:00 | 34610.58 | 16-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.365739E+12 | 0.00 | 5389.00 | 0.265414E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.624901E+10 | 0.00 | 192.33 | 0.601784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33097.58 | 29771.76 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.780509E+11 | 0.00 | 737.50 | 0.433674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61507.15 | 61507.15 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.167757E+10 | 0.00 | 381.65 | 0.105151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11929.51 | 14-JAN-16:02 | 11929.51 | 14-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.152445E+10 | 0.00 | 302.75 | 0.101002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11678.58 | 03-FEB-16:02 | 11678.58 | 03-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.160785E+10 | 0.00 | 308.88 | 0.968103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11815.35 | 10-MAR-16:02 | 11815.35 | 10-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.340876E+10 | 0.00 | 511.20 | 0.196408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11922.54 | 01-APR-15:01 | 11922.54 | 01-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.310158E+10 | 0.00 | 519.81 | 0.170419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11743.85 | 05-MAY-15:02 | 11407.46 | 17-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.460590E+10 | 0.00 | 571.79 | 0.248976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12184.22 | 30-JUN-08:62 | 11463.31 | 15-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.685750E+10 | 0.00 | 644.47 | 0.381100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13164.59 | 23-JUL-08:62 | 11942.11 | 19-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.719296E+10 | 0.00 | 660.36 | 0.399312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13523.18 | 19-AUG-08:62 | 11814.34 | 18-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.552526E+10 | 0.00 | 616.13 | 0.304819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13118.57 | 22-SEP-08:62 | 11300.79 | 08-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.513354E+10 | 0.00 | 611.16 | 0.349989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13275.74 | 01-OCT-08:62 | 12326.07 | 16-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.234656E+10 | 0.00 | 465.74 | 0.146174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12055.01 | 19-NOV-09:02 | 12055.01 | 19-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.198098E+10 | 0.00 | 409.04 | 0.159187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11917.15 | 05-DEC-16:02 | 11917.15 | 05-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.449629E+11 | 0.00 | 6002.98 | 0.265935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.152445E+10 | 0.00 | 302.75 | 0.968103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11678.58 | 11300.79 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.719296E+10 | 0.00 | 660.36 | 0.399312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13523.18 | 12326.07 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.396938E+09 | 0.00 | 158.36 | 0.225828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11446.81 | 14-JAN-16:02 | 11446.81 | 14-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.558520E+09 | 0.00 | 169.35 | 0.344585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11205.46 | 03-FEB-16:02 | 11205.46 | 03-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.853553E+09 | 0.00 | 199.85 | 0.496276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11336.92 | 10-MAR-16:02 | 11336.92 | 10-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.261472E+10 | 0.00 | 452.02 | 0.146576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11439.41 | 01-APR-15:01 | 11439.41 | 01-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.292197E+10 | 0.00 | 508.92 | 0.161743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11230.55 | 02-MAY-18:02 | 11018.60 | 17-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.465320E+10 | 0.00 | 567.29 | 0.257987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11689.22 | 30-JUN-08:62 | 11029.10 | 15-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.674789E+10 | 0.00 | 631.84 | 0.381449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12627.80 | 23-JUL-08:62 | 11345.50 | 19-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.645108E+10 | 0.00 | 625.90 | 0.351908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12946.53 | 19-AUG-08:62 | 11303.98 | 17-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.424767E+10 | 0.00 | 570.03 | 0.217541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12915.19 | 21-SEP-15:02 | 10948.36 | 11-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.342109E+10 | 0.00 | 528.16 | 0.213797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12772.75 | 05-OCT-15:02 | 11827.44 | 16-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.735816E+09 | 0.00 | 286.83 | 0.389047E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11176.40 | 10-NOV-16:02 | 11098.19 | 27-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.429877E+09 | 0.00 | 188.15 | 0.348158E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11434.15 | 05-DEC-16:02 | 11434.15 | 05-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.340323E+11 | 0.00 | 4886.70 | 0.191139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.396938E+09 | 0.00 | 158.36 | 0.225828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11176.40 | 10948.36 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.674789E+10 | 0.00 | 631.84 | 0.381449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12946.53 | 11827.44 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.211135E+11 | 0.00 | 385.68 | 0.179172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39662.68 | 14-JAN-12:40 | 39662.68 | 14-JAN-12:40 | 0.00 | 0.00 | 0.00 |
February | 0.131170E+11 | 0.00 | 269.04 | 0.111413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35465.32 | 02-FEB-12:40 | 35465.32 | 02-FEB-12:40 | 0.00 | 0.00 | 0.00 |
March | 0.649196E+10 | 0.00 | 203.79 | 0.409571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26740.55 | 11-MAR-13:30 | 26740.55 | 11-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.491772E+10 | 0.00 | 211.00 | 0.191348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18554.34 | 08-APR-12:40 | 10747.00 | 08-APR-13:10 | 0.00 | 0.00 | 0.00 |
May | 0.494295E+09 | 0.00 | 29.53 | 0.141755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9160.34 | 04-MAY-12:30 | 3405.57 | 03-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 62706442.41 | 0.00 | 14.00 | 7747375.92 | 0.00 | 0.00 | 0.00 | 0.00 | 3981.21 | 29-JUN-17:20 | 764.47 | 29-JUN-17:13 | 0.00 | 0.00 | 0.00 |
July | 0.348987E+10 | 0.00 | 186.44 | 0.930989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15212.93 | 31-JUL-12:40 | 6116.17 | 31-JUL-13:00 | 0.00 | 0.00 | 0.00 |
August | 0.106381E+11 | 0.00 | 361.39 | 0.383658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20269.30 | 18-AUG-12:00 | 10040.55 | 30-AUG-13:00 | 0.00 | 0.00 | 0.00 |
September | 0.146799E+11 | 0.00 | 358.74 | 0.835094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42675.74 | 30-SEP-13:20 | 41640.02 | 30-SEP-13:20 | 0.00 | 0.00 | 0.00 |
October | 0.248966E+11 | 0.00 | 458.44 | 0.196440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47884.96 | 16-OCT-12:20 | 47884.96 | 16-OCT-12:20 | 0.00 | 0.00 | 0.00 |
November | 0.219667E+11 | 0.00 | 411.16 | 0.181932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44781.56 | 19-NOV-12:30 | 44781.56 | 19-NOV-12:30 | 0.00 | 0.00 | 0.00 |
December | 0.250156E+11 | 0.00 | 425.14 | 0.227463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40370.32 | 19-DEC-13:00 | 40370.32 | 19-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146884E+12 | 0.00 | 3314.35 | 0.108919E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 62706442.41 | 0.00 | 14.00 | 7747375.92 | 0.00 | 0.00 | 0.00 | 0.00 | 3981.21 | 764.47 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.250156E+11 | 0.00 | 458.44 | 0.227463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47884.96 | 47884.96 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.625529E+10 | 0.00 | 305.04 | 0.308970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61071.85 | 21-JAN-09:02 | 60902.83 | 15-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.685124E+10 | 0.00 | 344.54 | 0.339437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61815.13 | 13-FEB-19:03 | 56664.32 | 20-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.899609E+10 | 0.00 | 382.64 | 0.439060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59201.65 | 24-MAR-15:02 | 58393.37 | 11-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.168809E+11 | 0.00 | 492.39 | 0.834024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61654.77 | 26-APR-08:62 | 59635.78 | 26-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.217435E+11 | 0.00 | 520.26 | 0.118797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62073.70 | 06-MAY-08:62 | 58960.59 | 04-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.309790E+11 | 0.00 | 507.94 | 0.169582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70023.53 | 29-JUN-18:02 | 58792.75 | 30-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.403928E+11 | 0.00 | 525.67 | 0.222747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73697.62 | 29-JUL-18:02 | 60875.98 | 18-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.372729E+11 | 0.00 | 524.65 | 0.192001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73413.17 | 19-AUG-08:62 | 60611.69 | 19-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.253313E+11 | 0.00 | 505.74 | 0.119549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71223.61 | 22-SEP-08:62 | 61219.68 | 30-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.228420E+11 | 0.00 | 515.34 | 0.138766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73594.49 | 01-OCT-08:62 | 66740.23 | 14-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.836355E+10 | 0.00 | 397.71 | 0.434354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62934.17 | 12-NOV-09:02 | 62677.43 | 19-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.546331E+10 | 0.00 | 295.69 | 0.370225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60549.93 | 05-DEC-09:02 | 60549.93 | 05-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231372E+12 | 0.00 | 5317.61 | 0.123405E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.546331E+10 | 0.00 | 295.69 | 0.308970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59201.65 | 56664.32 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.403928E+11 | 0.00 | 525.67 | 0.222747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73697.62 | 66740.23 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.177537E+10 | 0.00 | 381.30 | 0.121757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10450.78 | 14-JAN-16:02 | 10450.78 | 14-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.141568E+10 | 0.00 | 286.19 | 0.995173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10371.29 | 01-FEB-09:02 | 10371.29 | 01-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.158181E+10 | 0.00 | 308.38 | 0.982038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10350.59 | 10-MAR-16:02 | 10350.59 | 10-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.305241E+10 | 0.00 | 517.35 | 0.178156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10444.33 | 01-APR-15:01 | 10444.33 | 01-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.262533E+10 | 0.00 | 486.50 | 0.146614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10381.43 | 03-MAY-08:62 | 9980.20 | 24-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.384522E+10 | 0.00 | 592.95 | 0.203496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11170.86 | 28-JUN-15:02 | 9952.63 | 02-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.619719E+10 | 0.00 | 683.76 | 0.337836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11632.36 | 24-JUL-18:02 | 10041.81 | 19-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.682480E+10 | 0.00 | 691.19 | 0.374731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11522.98 | 13-AUG-18:02 | 10205.70 | 19-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.469226E+10 | 0.00 | 633.12 | 0.255503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12019.78 | 21-SEP-15:02 | 9960.81 | 30-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.484046E+10 | 0.00 | 618.48 | 0.337393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11653.92 | 05-OCT-15:02 | 10797.87 | 16-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.213919E+10 | 0.00 | 443.58 | 0.145854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10560.53 | 19-NOV-09:02 | 10560.53 | 19-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.197589E+10 | 0.00 | 406.78 | 0.167452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10553.10 | 05-DEC-09:02 | 10553.10 | 05-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.409656E+11 | 0.00 | 6049.58 | 0.246652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.141568E+10 | 0.00 | 286.19 | 0.982038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10350.59 | 9952.63 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.682480E+10 | 0.00 | 691.19 | 0.374731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12019.78 | 10797.87 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.554613E+09 | 0.00 | 175.30 | 0.343863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9791.04 | 21-JAN-09:02 | 9366.02 | 14-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.526729E+09 | 0.00 | 158.62 | 0.349499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9627.52 | 01-FEB-09:02 | 9627.52 | 01-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.840309E+09 | 0.00 | 200.07 | 0.484219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9964.39 | 23-MAR-15:02 | 9629.17 | 11-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.226941E+10 | 0.00 | 398.49 | 0.131612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10013.89 | 27-APR-08:62 | 9728.95 | 26-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.245638E+10 | 0.00 | 454.93 | 0.139075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9986.96 | 03-MAY-08:62 | 9575.32 | 24-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.387558E+10 | 0.00 | 585.36 | 0.211615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10725.63 | 28-JUN-15:02 | 9551.66 | 02-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.605871E+10 | 0.00 | 676.67 | 0.336823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11150.52 | 24-JUL-18:02 | 9580.87 | 19-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.602291E+10 | 0.00 | 677.08 | 0.327006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11090.40 | 18-AUG-18:02 | 9601.80 | 19-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.341423E+10 | 0.00 | 536.70 | 0.175982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11550.72 | 21-SEP-15:02 | 9637.05 | 30-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.309766E+10 | 0.00 | 501.98 | 0.202022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11276.35 | 01-OCT-15:02 | 10359.83 | 16-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.716842E+09 | 0.00 | 243.80 | 0.445051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10131.72 | 19-NOV-09:02 | 10131.72 | 19-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.530637E+09 | 0.00 | 171.81 | 0.453635E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10125.24 | 05-DEC-09:02 | 10125.24 | 05-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.303640E+11 | 0.00 | 4780.82 | 0.173176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.526729E+09 | 0.00 | 158.62 | 0.343863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9627.52 | 9366.02 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.605871E+10 | 0.00 | 677.08 | 0.336823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11550.72 | 10359.83 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.313628E+09 | 0.00 | 275.47 | 0.205366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3095.08 | 21-JAN-09:02 | 3087.32 | 14-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.301922E+09 | 0.00 | 212.16 | 0.207315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3022.38 | 03-FEB-16:02 | 3022.38 | 03-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.351290E+09 | 0.00 | 223.72 | 0.223317E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3057.80 | 10-MAR-16:02 | 3057.80 | 10-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.780373E+09 | 0.00 | 425.17 | 0.473370E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3155.92 | 26-APR-08:62 | 3085.60 | 01-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.687295E+09 | 0.00 | 425.88 | 0.399465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3119.83 | 03-MAY-08:62 | 2944.11 | 31-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.107496E+10 | 0.00 | 537.93 | 0.595907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3259.91 | 30-JUN-08:62 | 2943.32 | 18-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.166885E+10 | 0.00 | 658.94 | 0.921015E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3518.97 | 23-JUL-08:62 | 3041.35 | 18-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.172563E+10 | 0.00 | 668.31 | 0.940275E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3615.85 | 19-AUG-08:62 | 3041.89 | 06-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.124165E+10 | 0.00 | 604.02 | 0.689069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3427.36 | 09-SEP-08:62 | 2939.16 | 08-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.111639E+10 | 0.00 | 541.68 | 0.764593E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3541.27 | 01-OCT-08:62 | 3189.94 | 16-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.440913E+09 | 0.00 | 337.23 | 0.278623E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3090.47 | 19-NOV-09:02 | 3090.47 | 19-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.366628E+09 | 0.00 | 299.09 | 0.304996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3084.09 | 05-DEC-16:02 | 3084.09 | 05-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100695E+11 | 0.00 | 5209.59 | 0.600331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.301922E+09 | 0.00 | 212.16 | 0.205366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3022.38 | 2939.16 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.172563E+10 | 0.00 | 668.31 | 0.940275E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3615.85 | 3189.94 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 57610929.74 | 0.00 | 77.43 | 38175223.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2953.80 | 14-JAN-16:02 | 2953.80 | 14-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 93999769.81 | 0.00 | 91.15 | 65507291.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2891.52 | 03-FEB-16:02 | 2891.52 | 03-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.177157E+09 | 0.00 | 129.39 | 0.112044E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2925.41 | 10-MAR-16:02 | 2925.41 | 10-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.581347E+09 | 0.00 | 348.36 | 0.347682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3008.10 | 26-APR-08:62 | 2951.90 | 01-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.639517E+09 | 0.00 | 409.28 | 0.376636E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2973.79 | 03-MAY-08:62 | 2814.25 | 17-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.108174E+10 | 0.00 | 536.83 | 0.610800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3115.06 | 30-JUN-08:62 | 2824.81 | 28-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.163473E+10 | 0.00 | 648.52 | 0.911334E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3362.30 | 23-JUL-08:62 | 2928.18 | 18-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.152123E+10 | 0.00 | 638.24 | 0.816673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3455.01 | 19-AUG-08:62 | 2923.98 | 18-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.896266E+09 | 0.00 | 536.71 | 0.472317E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3315.11 | 21-SEP-15:02 | 2832.39 | 12-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.686723E+09 | 0.00 | 432.37 | 0.438813E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3398.48 | 01-OCT-08:62 | 3051.91 | 16-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 98484518.06 | 0.00 | 129.10 | 57942258.37 | 0.00 | 0.00 | 0.00 | 0.00 | 2889.94 | 10-NOV-16:02 | 2855.09 | 27-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 59379140.44 | 0.00 | 69.10 | 51328712.73 | 0.00 | 0.00 | 0.00 | 0.00 | 2950.51 | 05-DEC-16:02 | 2950.51 | 05-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.752818E+10 | 0.00 | 4046.48 | 0.429925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 57610929.74 | 0.00 | 69.10 | 38175223.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2889.94 | 2814.25 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.163473E+10 | 0.00 | 648.52 | 0.911334E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3455.01 | 3051.91 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.666781E+10 | 0.00 | 541.36 | 0.540311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14400.58 | 14-JAN-16:02 | 14400.58 | 14-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.429756E+10 | 0.00 | 405.18 | 0.334891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14098.65 | 03-FEB-16:02 | 14098.65 | 03-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.352153E+10 | 0.00 | 400.36 | 0.229234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14263.23 | 10-MAR-16:02 | 14263.23 | 10-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.424207E+10 | 0.00 | 527.99 | 0.235058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14392.95 | 01-APR-15:01 | 14392.95 | 01-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.242793E+10 | 0.00 | 411.15 | 0.114391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14230.38 | 06-MAY-15:02 | 13639.21 | 03-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.348554E+10 | 0.00 | 502.50 | 0.155435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15655.13 | 29-JUN-18:02 | 13594.05 | 20-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.617776E+10 | 0.00 | 619.58 | 0.291538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16644.96 | 24-JUL-18:02 | 13663.96 | 31-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.812750E+10 | 0.00 | 655.04 | 0.409419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16552.29 | 13-AUG-18:02 | 14143.55 | 19-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.786616E+10 | 0.00 | 631.18 | 0.449974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15880.45 | 22-SEP-08:62 | 13819.08 | 08-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.936631E+10 | 0.00 | 631.36 | 0.706369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16331.11 | 01-OCT-18:02 | 14879.47 | 16-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.684814E+10 | 0.00 | 572.03 | 0.531526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14548.63 | 19-NOV-09:02 | 14548.63 | 19-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.733512E+10 | 0.00 | 550.91 | 0.648983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14538.28 | 05-DEC-09:02 | 14538.28 | 05-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.703634E+11 | 0.00 | 6448.62 | 0.464713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.242793E+10 | 0.00 | 400.36 | 0.114391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14098.65 | 13594.05 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.936631E+10 | 0.00 | 655.04 | 0.706369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16644.96 | 14879.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 691.88 | 507.95 | 183.94 | 1013.94 | 373.46 | 0.00 | 0.00 | 0.00 |
February | 546.53 | 338.18 | 208.36 | 763.99 | 337.07 | 0.00 | 0.00 | 0.00 |
March | 435.89 | 212.33 | 223.56 | 605.99 | 347.96 | 0.00 | 0.00 | 0.00 |
April | 364.49 | 140.88 | 223.62 | 542.22 | 280.09 | 0.00 | 0.00 | 0.00 |
May | 256.82 | 31.10 | 225.72 | 327.90 | 245.67 | 0.00 | 0.00 | 0.00 |
June | 225.30 | 13.21 | 212.09 | 293.07 | 184.04 | 0.00 | 0.00 | 0.00 |
July | 237.61 | 25.41 | 212.20 | 349.63 | 162.48 | 0.00 | 0.00 | 0.00 |
August | 305.17 | 94.83 | 210.34 | 498.67 | 175.84 | 0.00 | 0.00 | 0.00 |
September | 419.06 | 208.19 | 210.87 | 675.38 | 209.46 | 0.00 | 0.00 | 0.00 |
October | 548.73 | 368.52 | 180.22 | 885.12 | 232.74 | 0.00 | 0.00 | 0.00 |
November | 666.54 | 472.26 | 194.28 | 980.08 | 335.96 | 0.00 | 0.00 | 0.00 |
December | 740.41 | 564.21 | 176.20 | 1091.06 | 374.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 452.81 | 247.78 | 205.03 | 668.65 | 271.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 225.30 | 13.21 | 176.20 | 293.07 | 162.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 740.41 | 564.21 | 225.72 | 1091.06 | 374.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1948.30 | 1430.34 | 517.96 | 2808.08 | 1157.01 | 0.00 | 0.00 | 0.00 |
February | 1539.00 | 952.28 | 586.71 | 2104.50 | 1058.24 | 0.00 | 0.00 | 0.00 |
March | 1227.43 | 597.91 | 629.52 | 1660.39 | 1086.04 | 0.00 | 0.00 | 0.00 |
April | 1026.39 | 396.71 | 629.69 | 1483.29 | 885.12 | 0.00 | 0.00 | 0.00 |
May | 723.18 | 87.58 | 635.60 | 875.61 | 783.29 | 0.00 | 0.00 | 0.00 |
June | 634.43 | 37.21 | 597.22 | 779.47 | 598.20 | 0.00 | 0.00 | 0.00 |
July | 669.08 | 71.55 | 597.53 | 947.97 | 520.58 | 0.00 | 0.00 | 0.00 |
August | 859.34 | 267.03 | 592.31 | 1374.21 | 557.46 | 0.00 | 0.00 | 0.00 |
September | 1180.05 | 586.24 | 593.81 | 1869.41 | 662.96 | 0.00 | 0.00 | 0.00 |
October | 1545.20 | 1037.72 | 507.48 | 2456.53 | 728.55 | 0.00 | 0.00 | 0.00 |
November | 1876.94 | 1329.86 | 547.08 | 2712.38 | 1047.70 | 0.00 | 0.00 | 0.00 |
December | 2084.94 | 1588.78 | 496.16 | 3024.40 | 1159.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1275.09 | 697.73 | 577.36 | 1840.62 | 852.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 634.43 | 37.21 | 496.16 | 779.47 | 520.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2084.94 | 1588.78 | 635.60 | 3024.40 | 1159.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2530.95 | 1858.09 | 672.86 | 3731.62 | 1537.79 | 0.00 | 0.00 | 0.00 |
February | 1999.24 | 1237.07 | 762.17 | 2793.00 | 1428.32 | 0.00 | 0.00 | 0.00 |
March | 1594.50 | 776.72 | 817.79 | 2200.09 | 1477.68 | 0.00 | 0.00 | 0.00 |
April | 1333.34 | 515.34 | 818.00 | 1969.84 | 1202.48 | 0.00 | 0.00 | 0.00 |
May | 939.45 | 113.77 | 825.68 | 1140.21 | 1089.34 | 0.00 | 0.00 | 0.00 |
June | 824.17 | 48.34 | 775.83 | 1010.17 | 834.52 | 0.00 | 0.00 | 0.00 |
July | 869.17 | 92.94 | 776.23 | 1245.24 | 717.42 | 0.00 | 0.00 | 0.00 |
August | 1116.33 | 346.89 | 769.44 | 1828.01 | 748.67 | 0.00 | 0.00 | 0.00 |
September | 1532.95 | 761.56 | 771.39 | 2489.18 | 884.95 | 0.00 | 0.00 | 0.00 |
October | 2007.30 | 1348.05 | 659.24 | 3260.61 | 964.37 | 0.00 | 0.00 | 0.00 |
November | 2438.25 | 1727.56 | 710.69 | 3602.71 | 1393.58 | 0.00 | 0.00 | 0.00 |
December | 2708.45 | 2063.92 | 644.54 | 4014.76 | 1540.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1656.41 | 906.39 | 750.02 | 2439.45 | 1150.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 824.17 | 48.34 | 644.54 | 1010.17 | 717.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2708.45 | 2063.92 | 825.68 | 4014.76 | 1540.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.80 | 100.43 | 36.37 | 204.39 | 71.20 | 0.00 | 0.00 | 0.00 |
February | 108.06 | 66.86 | 41.20 | 152.47 | 65.11 | 0.00 | 0.00 | 0.00 |
March | 86.18 | 41.98 | 44.20 | 120.27 | 68.93 | 0.00 | 0.00 | 0.00 |
April | 72.07 | 27.85 | 44.21 | 107.05 | 54.85 | 0.00 | 0.00 | 0.00 |
May | 50.78 | 6.15 | 44.63 | 62.88 | 49.44 | 0.00 | 0.00 | 0.00 |
June | 44.55 | 2.61 | 41.93 | 56.66 | 35.64 | 0.00 | 0.00 | 0.00 |
July | 46.98 | 5.02 | 41.96 | 69.54 | 29.56 | 0.00 | 0.00 | 0.00 |
August | 60.34 | 18.75 | 41.59 | 100.65 | 30.70 | 0.00 | 0.00 | 0.00 |
September | 82.86 | 41.16 | 41.69 | 136.06 | 37.05 | 0.00 | 0.00 | 0.00 |
October | 108.49 | 72.86 | 35.63 | 178.85 | 40.50 | 0.00 | 0.00 | 0.00 |
November | 131.79 | 93.37 | 38.41 | 196.98 | 63.28 | 0.00 | 0.00 | 0.00 |
December | 146.39 | 111.55 | 34.84 | 219.78 | 70.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.53 | 48.99 | 40.54 | 133.75 | 51.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.55 | 2.61 | 34.84 | 56.66 | 29.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 146.39 | 111.55 | 44.63 | 219.78 | 71.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.13 | 49.99 | 49.14 | 125.11 | 144.00 | 0.00 | 0.00 | 0.00 |
February | 118.40 | 54.72 | 63.67 | 143.57 | 127.68 | 0.00 | 0.00 | 0.00 |
March | 135.41 | 59.84 | 75.57 | 169.05 | 130.16 | 0.00 | 0.00 | 0.00 |
April | 186.62 | 97.02 | 89.60 | 264.96 | 99.05 | 0.00 | 0.00 | 0.00 |
May | 183.33 | 84.55 | 98.78 | 255.16 | 87.82 | 0.00 | 0.00 | 0.00 |
June | 194.16 | 96.95 | 97.21 | 287.91 | 62.53 | 0.00 | 0.00 | 0.00 |
July | 205.59 | 109.90 | 95.69 | 322.70 | 51.97 | 0.00 | 0.00 | 0.00 |
August | 192.92 | 104.46 | 88.46 | 304.95 | 55.00 | 0.00 | 0.00 | 0.00 |
September | 165.33 | 88.43 | 76.90 | 251.34 | 67.26 | 0.00 | 0.00 | 0.00 |
October | 127.00 | 69.58 | 57.41 | 198.43 | 78.77 | 0.00 | 0.00 | 0.00 |
November | 114.28 | 59.82 | 54.46 | 149.22 | 126.05 | 0.00 | 0.00 | 0.00 |
December | 100.52 | 53.75 | 46.77 | 129.00 | 143.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.02 | 77.52 | 74.51 | 217.15 | 97.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.13 | 49.99 | 46.77 | 125.11 | 51.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 205.59 | 109.90 | 98.78 | 322.70 | 144.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.68 | 0.00 | 20.68 | 15.26 | 76.53 | 0.00 | 0.00 | 0.00 |
February | 25.96 | 0.00 | 25.96 | 17.25 | 68.85 | 0.00 | 0.00 | 0.00 |
March | 31.81 | 0.00 | 31.81 | 24.95 | 70.90 | 0.00 | 0.00 | 0.00 |
April | 36.84 | 0.30 | 36.55 | 34.77 | 52.73 | 0.00 | 0.00 | 0.00 |
May | 44.32 | 2.31 | 42.01 | 44.46 | 45.30 | 0.00 | 0.00 | 0.00 |
June | 46.98 | 4.64 | 42.34 | 57.08 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 44.50 | 3.78 | 40.73 | 60.43 | 27.34 | 0.00 | 0.00 | 0.00 |
August | 37.00 | 0.82 | 36.18 | 48.96 | 28.94 | 0.00 | 0.00 | 0.00 |
September | 31.23 | 0.01 | 31.23 | 37.81 | 36.51 | 0.00 | 0.00 | 0.00 |
October | 24.77 | 0.00 | 24.77 | 33.73 | 41.91 | 0.00 | 0.00 | 0.00 |
November | 22.43 | 0.00 | 22.43 | 17.44 | 67.82 | 0.00 | 0.00 | 0.00 |
December | 19.25 | 0.00 | 19.25 | 13.85 | 76.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.17 | 0.99 | 31.18 | 33.94 | 52.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.25 | 0.00 | 19.25 | 13.85 | 27.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 46.98 | 4.64 | 42.34 | 60.43 | 76.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.13 | 49.99 | 49.14 | 131.73 | 139.51 | 0.00 | 0.00 | 0.00 |
February | 118.40 | 54.72 | 63.67 | 148.59 | 124.72 | 0.00 | 0.00 | 0.00 |
March | 135.41 | 59.84 | 75.57 | 173.05 | 128.12 | 0.00 | 0.00 | 0.00 |
April | 186.62 | 97.02 | 89.60 | 267.96 | 97.82 | 0.00 | 0.00 | 0.00 |
May | 183.33 | 84.55 | 98.78 | 256.04 | 87.59 | 0.00 | 0.00 | 0.00 |
June | 194.16 | 96.95 | 97.21 | 288.06 | 62.55 | 0.00 | 0.00 | 0.00 |
July | 205.59 | 109.90 | 95.69 | 323.12 | 51.88 | 0.00 | 0.00 | 0.00 |
August | 192.92 | 104.46 | 88.46 | 306.69 | 54.35 | 0.00 | 0.00 | 0.00 |
September | 165.33 | 88.43 | 76.90 | 254.62 | 65.85 | 0.00 | 0.00 | 0.00 |
October | 127.00 | 69.58 | 57.41 | 202.65 | 76.56 | 0.00 | 0.00 | 0.00 |
November | 114.28 | 59.82 | 54.46 | 155.08 | 122.45 | 0.00 | 0.00 | 0.00 |
December | 100.52 | 53.75 | 46.77 | 135.78 | 139.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.02 | 77.52 | 74.51 | 220.64 | 95.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.13 | 49.99 | 46.77 | 131.73 | 51.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 205.59 | 109.90 | 98.78 | 323.12 | 139.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.42 | 80.33 | 29.09 | 159.35 | 66.08 | 0.00 | 0.00 | 0.00 |
February | 86.43 | 53.48 | 32.95 | 118.28 | 60.26 | 0.00 | 0.00 | 0.00 |
March | 68.93 | 33.58 | 35.35 | 93.21 | 61.77 | 0.00 | 0.00 | 0.00 |
April | 57.64 | 22.28 | 35.36 | 83.59 | 49.69 | 0.00 | 0.00 | 0.00 |
May | 40.61 | 4.92 | 35.70 | 50.10 | 42.27 | 0.00 | 0.00 | 0.00 |
June | 35.63 | 2.09 | 33.54 | 45.63 | 30.62 | 0.00 | 0.00 | 0.00 |
July | 37.58 | 4.02 | 33.56 | 54.49 | 27.70 | 0.00 | 0.00 | 0.00 |
August | 48.26 | 15.00 | 33.26 | 78.65 | 29.99 | 0.00 | 0.00 | 0.00 |
September | 66.27 | 32.92 | 33.35 | 106.47 | 36.21 | 0.00 | 0.00 | 0.00 |
October | 86.78 | 58.28 | 28.50 | 139.98 | 39.80 | 0.00 | 0.00 | 0.00 |
November | 105.41 | 74.68 | 30.72 | 153.60 | 59.69 | 0.00 | 0.00 | 0.00 |
December | 117.09 | 89.23 | 27.86 | 171.54 | 66.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 71.61 | 39.18 | 32.42 | 104.54 | 47.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.63 | 2.09 | 27.86 | 45.63 | 27.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.09 | 89.23 | 35.70 | 171.54 | 66.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.54 | 0.00 | 16.54 | 12.90 | 61.25 | 0.00 | 0.00 | 0.00 |
February | 20.77 | 0.00 | 20.77 | 14.67 | 55.12 | 0.00 | 0.00 | 0.00 |
March | 25.45 | 0.00 | 25.45 | 21.03 | 56.79 | 0.00 | 0.00 | 0.00 |
April | 29.48 | 0.24 | 29.24 | 30.86 | 40.84 | 0.00 | 0.00 | 0.00 |
May | 35.46 | 1.85 | 33.61 | 38.85 | 35.23 | 0.00 | 0.00 | 0.00 |
June | 37.59 | 3.71 | 33.88 | 49.80 | 24.58 | 0.00 | 0.00 | 0.00 |
July | 35.61 | 3.02 | 32.58 | 53.18 | 20.11 | 0.00 | 0.00 | 0.00 |
August | 29.60 | 0.66 | 28.95 | 43.78 | 21.03 | 0.00 | 0.00 | 0.00 |
September | 24.99 | 0.00 | 24.98 | 33.79 | 27.00 | 0.00 | 0.00 | 0.00 |
October | 19.82 | 0.00 | 19.82 | 29.77 | 31.71 | 0.00 | 0.00 | 0.00 |
November | 17.95 | 0.00 | 17.95 | 15.23 | 53.29 | 0.00 | 0.00 | 0.00 |
December | 15.40 | 0.00 | 15.40 | 11.94 | 61.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.74 | 0.79 | 24.95 | 29.74 | 40.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.40 | 0.00 | 15.40 | 11.94 | 20.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 37.59 | 3.71 | 33.88 | 53.18 | 61.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.03 | 55.59 | 48.45 | 127.20 | 136.58 | 0.00 | 0.00 | 0.00 |
February | 109.78 | 50.23 | 59.54 | 125.13 | 122.21 | 0.00 | 0.00 | 0.00 |
March | 133.98 | 59.84 | 74.14 | 162.32 | 124.32 | 0.00 | 0.00 | 0.00 |
April | 170.78 | 85.69 | 85.09 | 237.08 | 94.94 | 0.00 | 0.00 | 0.00 |
May | 160.86 | 67.04 | 93.82 | 218.24 | 84.92 | 0.00 | 0.00 | 0.00 |
June | 160.04 | 69.48 | 90.57 | 234.22 | 61.83 | 0.00 | 0.00 | 0.00 |
July | 181.24 | 90.04 | 91.20 | 284.66 | 51.92 | 0.00 | 0.00 | 0.00 |
August | 179.13 | 95.20 | 83.93 | 283.59 | 53.69 | 0.00 | 0.00 | 0.00 |
September | 130.78 | 60.15 | 70.63 | 195.46 | 65.75 | 0.00 | 0.00 | 0.00 |
October | 115.26 | 59.16 | 56.10 | 176.39 | 75.02 | 0.00 | 0.00 | 0.00 |
November | 104.83 | 53.07 | 51.76 | 129.36 | 120.96 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 56.17 | 44.61 | 122.65 | 136.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 137.81 | 66.94 | 70.87 | 191.82 | 93.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.77 | 50.23 | 44.61 | 122.65 | 51.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 181.24 | 95.20 | 93.82 | 284.66 | 136.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.80 | 100.43 | 36.37 | 203.44 | 70.98 | 0.00 | 0.00 | 0.00 |
February | 108.06 | 66.86 | 41.20 | 151.91 | 64.51 | 0.00 | 0.00 | 0.00 |
March | 86.18 | 41.98 | 44.20 | 119.33 | 68.38 | 0.00 | 0.00 | 0.00 |
April | 72.07 | 27.85 | 44.21 | 105.93 | 53.90 | 0.00 | 0.00 | 0.00 |
May | 50.78 | 6.15 | 44.63 | 62.15 | 48.41 | 0.00 | 0.00 | 0.00 |
June | 44.55 | 2.61 | 41.93 | 56.14 | 34.51 | 0.00 | 0.00 | 0.00 |
July | 46.98 | 5.02 | 41.96 | 68.68 | 28.54 | 0.00 | 0.00 | 0.00 |
August | 60.34 | 18.75 | 41.59 | 99.75 | 29.79 | 0.00 | 0.00 | 0.00 |
September | 82.86 | 41.16 | 41.69 | 135.89 | 35.88 | 0.00 | 0.00 | 0.00 |
October | 108.49 | 72.86 | 35.63 | 178.38 | 39.92 | 0.00 | 0.00 | 0.00 |
November | 131.79 | 93.37 | 38.41 | 196.49 | 62.66 | 0.00 | 0.00 | 0.00 |
December | 146.39 | 111.55 | 34.84 | 219.06 | 70.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.53 | 48.99 | 40.54 | 133.04 | 50.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.55 | 2.61 | 34.84 | 56.14 | 28.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 146.39 | 111.55 | 44.63 | 219.06 | 70.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.68 | 0.00 | 20.68 | 14.57 | 76.08 | 0.00 | 0.00 | 0.00 |
February | 25.96 | 0.00 | 25.96 | 16.77 | 68.05 | 0.00 | 0.00 | 0.00 |
March | 31.81 | 0.00 | 31.81 | 24.08 | 70.36 | 0.00 | 0.00 | 0.00 |
April | 36.84 | 0.30 | 36.55 | 33.72 | 51.93 | 0.00 | 0.00 | 0.00 |
May | 44.32 | 2.31 | 42.01 | 43.93 | 44.47 | 0.00 | 0.00 | 0.00 |
June | 46.98 | 4.64 | 42.34 | 56.88 | 31.54 | 0.00 | 0.00 | 0.00 |
July | 44.50 | 3.78 | 40.73 | 59.79 | 26.58 | 0.00 | 0.00 | 0.00 |
August | 37.00 | 0.82 | 36.18 | 47.97 | 28.16 | 0.00 | 0.00 | 0.00 |
September | 31.23 | 0.01 | 31.23 | 37.57 | 35.29 | 0.00 | 0.00 | 0.00 |
October | 24.77 | 0.00 | 24.77 | 33.17 | 41.32 | 0.00 | 0.00 | 0.00 |
November | 22.43 | 0.00 | 22.43 | 17.07 | 66.70 | 0.00 | 0.00 | 0.00 |
December | 19.25 | 0.00 | 19.25 | 13.28 | 75.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.17 | 0.99 | 31.18 | 33.33 | 51.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.25 | 0.00 | 19.25 | 13.28 | 26.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 46.98 | 4.64 | 42.34 | 59.79 | 76.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.03 | 55.59 | 48.45 | 133.52 | 131.04 | 0.00 | 0.00 | 0.00 |
February | 109.78 | 50.23 | 59.54 | 130.12 | 118.64 | 0.00 | 0.00 | 0.00 |
March | 133.98 | 59.84 | 74.14 | 166.14 | 122.01 | 0.00 | 0.00 | 0.00 |
April | 170.78 | 85.69 | 85.09 | 239.86 | 93.61 | 0.00 | 0.00 | 0.00 |
May | 160.86 | 67.04 | 93.82 | 219.10 | 84.66 | 0.00 | 0.00 | 0.00 |
June | 160.04 | 69.48 | 90.57 | 234.34 | 61.89 | 0.00 | 0.00 | 0.00 |
July | 181.24 | 90.04 | 91.20 | 284.99 | 51.85 | 0.00 | 0.00 | 0.00 |
August | 179.13 | 95.20 | 83.93 | 284.96 | 53.01 | 0.00 | 0.00 | 0.00 |
September | 130.78 | 60.15 | 70.63 | 198.58 | 64.15 | 0.00 | 0.00 | 0.00 |
October | 115.26 | 59.16 | 56.10 | 180.36 | 72.67 | 0.00 | 0.00 | 0.00 |
November | 104.83 | 53.07 | 51.76 | 135.23 | 116.14 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 56.17 | 44.61 | 129.24 | 130.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 137.81 | 66.94 | 70.87 | 195.15 | 91.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.77 | 50.23 | 44.61 | 129.24 | 51.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 181.24 | 95.20 | 93.82 | 284.99 | 131.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.19 | 0.00 | 26.19 | 16.60 | 107.96 | 0.00 | 0.00 | 0.00 |
February | 32.87 | 0.00 | 32.87 | 19.48 | 97.67 | 0.00 | 0.00 | 0.00 |
March | 40.29 | 0.00 | 40.29 | 30.19 | 97.81 | 0.00 | 0.00 | 0.00 |
April | 46.66 | 0.38 | 46.28 | 44.40 | 73.30 | 0.00 | 0.00 | 0.00 |
May | 56.13 | 2.93 | 53.20 | 56.60 | 63.38 | 0.00 | 0.00 | 0.00 |
June | 59.50 | 5.88 | 53.62 | 72.79 | 46.76 | 0.00 | 0.00 | 0.00 |
July | 56.36 | 4.78 | 51.58 | 76.49 | 41.03 | 0.00 | 0.00 | 0.00 |
August | 46.86 | 1.04 | 45.82 | 61.08 | 44.46 | 0.00 | 0.00 | 0.00 |
September | 39.55 | 0.01 | 39.55 | 46.72 | 54.74 | 0.00 | 0.00 | 0.00 |
October | 31.37 | 0.00 | 31.37 | 39.88 | 64.67 | 0.00 | 0.00 | 0.00 |
November | 28.41 | 0.00 | 28.41 | 19.24 | 97.62 | 0.00 | 0.00 | 0.00 |
December | 24.38 | 0.00 | 24.38 | 14.36 | 110.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.75 | 1.26 | 39.49 | 41.62 | 74.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.38 | 0.00 | 24.38 | 14.36 | 41.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.50 | 5.88 | 53.62 | 76.49 | 110.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.65 | 0.00 | 9.65 | 6.12 | 39.80 | 0.00 | 0.00 | 0.00 |
February | 12.12 | 0.00 | 12.12 | 7.18 | 36.01 | 0.00 | 0.00 | 0.00 |
March | 14.85 | 0.00 | 14.85 | 11.13 | 36.06 | 0.00 | 0.00 | 0.00 |
April | 17.20 | 0.14 | 17.06 | 16.37 | 27.02 | 0.00 | 0.00 | 0.00 |
May | 20.69 | 1.08 | 19.61 | 20.86 | 23.36 | 0.00 | 0.00 | 0.00 |
June | 21.93 | 2.17 | 19.77 | 26.83 | 17.24 | 0.00 | 0.00 | 0.00 |
July | 20.78 | 1.76 | 19.01 | 28.20 | 15.13 | 0.00 | 0.00 | 0.00 |
August | 17.27 | 0.38 | 16.89 | 22.52 | 16.39 | 0.00 | 0.00 | 0.00 |
September | 14.58 | 0.00 | 14.58 | 17.22 | 20.18 | 0.00 | 0.00 | 0.00 |
October | 11.57 | 0.00 | 11.57 | 14.70 | 23.84 | 0.00 | 0.00 | 0.00 |
November | 10.47 | 0.00 | 10.47 | 7.09 | 35.99 | 0.00 | 0.00 | 0.00 |
December | 8.99 | 0.00 | 8.99 | 5.29 | 40.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.02 | 0.46 | 14.56 | 15.34 | 27.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.99 | 0.00 | 8.99 | 5.29 | 15.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 21.93 | 2.17 | 19.77 | 28.20 | 40.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.83 | 46.86 | 16.97 | 95.74 | 35.78 | 0.00 | 0.00 | 0.00 |
February | 50.42 | 31.20 | 19.22 | 71.24 | 33.24 | 0.00 | 0.00 | 0.00 |
March | 40.21 | 19.59 | 20.62 | 56.40 | 34.52 | 0.00 | 0.00 | 0.00 |
April | 33.63 | 13.00 | 20.63 | 50.66 | 27.64 | 0.00 | 0.00 | 0.00 |
May | 23.69 | 2.87 | 20.82 | 29.65 | 25.26 | 0.00 | 0.00 | 0.00 |
June | 20.79 | 1.22 | 19.57 | 26.65 | 18.82 | 0.00 | 0.00 | 0.00 |
July | 21.92 | 2.34 | 19.58 | 32.57 | 16.22 | 0.00 | 0.00 | 0.00 |
August | 28.15 | 8.75 | 19.41 | 47.00 | 17.09 | 0.00 | 0.00 | 0.00 |
September | 38.66 | 19.21 | 19.45 | 63.67 | 20.06 | 0.00 | 0.00 | 0.00 |
October | 50.62 | 34.00 | 16.63 | 83.10 | 22.40 | 0.00 | 0.00 | 0.00 |
November | 61.49 | 43.57 | 17.92 | 92.01 | 32.57 | 0.00 | 0.00 | 0.00 |
December | 68.31 | 52.05 | 16.25 | 102.66 | 36.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.77 | 22.86 | 18.92 | 62.59 | 26.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.79 | 1.22 | 16.25 | 26.65 | 16.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.31 | 52.05 | 20.82 | 102.66 | 36.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 173.25 | 127.19 | 46.06 | 259.85 | 97.10 | 0.00 | 0.00 | 0.00 |
February | 136.85 | 84.68 | 52.17 | 193.35 | 90.21 | 0.00 | 0.00 | 0.00 |
March | 109.15 | 53.17 | 55.98 | 153.09 | 93.70 | 0.00 | 0.00 | 0.00 |
April | 91.27 | 35.28 | 55.99 | 137.50 | 75.03 | 0.00 | 0.00 | 0.00 |
May | 64.31 | 7.79 | 56.52 | 80.47 | 68.57 | 0.00 | 0.00 | 0.00 |
June | 56.42 | 3.31 | 53.11 | 72.34 | 51.09 | 0.00 | 0.00 | 0.00 |
July | 59.50 | 6.36 | 53.13 | 88.39 | 44.01 | 0.00 | 0.00 | 0.00 |
August | 76.41 | 23.74 | 52.67 | 127.55 | 46.38 | 0.00 | 0.00 | 0.00 |
September | 104.93 | 52.13 | 52.80 | 172.81 | 54.43 | 0.00 | 0.00 | 0.00 |
October | 137.40 | 92.28 | 45.13 | 225.56 | 60.80 | 0.00 | 0.00 | 0.00 |
November | 166.90 | 118.25 | 48.65 | 249.74 | 88.40 | 0.00 | 0.00 | 0.00 |
December | 185.40 | 141.28 | 44.12 | 278.65 | 97.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 113.38 | 62.04 | 51.34 | 169.88 | 72.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.42 | 3.31 | 44.12 | 72.34 | 44.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 185.40 | 141.28 | 56.52 | 278.65 | 97.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.80 | 100.43 | 36.37 | 203.64 | 70.05 | 0.00 | 0.00 | 0.00 |
February | 108.06 | 66.86 | 41.20 | 151.45 | 63.93 | 0.00 | 0.00 | 0.00 |
March | 86.18 | 41.98 | 44.20 | 119.34 | 68.13 | 0.00 | 0.00 | 0.00 |
April | 72.07 | 27.85 | 44.21 | 105.69 | 54.27 | 0.00 | 0.00 | 0.00 |
May | 50.78 | 6.15 | 44.63 | 61.83 | 48.95 | 0.00 | 0.00 | 0.00 |
June | 44.55 | 2.61 | 41.93 | 55.65 | 35.24 | 0.00 | 0.00 | 0.00 |
July | 46.98 | 5.02 | 41.96 | 68.47 | 29.17 | 0.00 | 0.00 | 0.00 |
August | 60.34 | 18.75 | 41.59 | 99.43 | 30.24 | 0.00 | 0.00 | 0.00 |
September | 82.86 | 41.16 | 41.69 | 134.75 | 36.38 | 0.00 | 0.00 | 0.00 |
October | 108.49 | 72.86 | 35.63 | 177.79 | 39.55 | 0.00 | 0.00 | 0.00 |
November | 131.79 | 93.37 | 38.41 | 195.96 | 62.11 | 0.00 | 0.00 | 0.00 |
December | 146.39 | 111.55 | 34.84 | 218.95 | 69.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.53 | 48.99 | 40.54 | 132.70 | 50.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.55 | 2.61 | 34.84 | 55.65 | 29.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 146.39 | 111.55 | 44.63 | 218.95 | 70.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.13 | 49.99 | 49.14 | 124.14 | 141.16 | 0.00 | 0.00 | 0.00 |
February | 118.40 | 54.72 | 63.67 | 142.32 | 124.96 | 0.00 | 0.00 | 0.00 |
March | 135.41 | 59.84 | 75.57 | 167.05 | 128.25 | 0.00 | 0.00 | 0.00 |
April | 186.62 | 97.02 | 89.60 | 261.25 | 97.77 | 0.00 | 0.00 | 0.00 |
May | 183.33 | 84.55 | 98.78 | 251.47 | 86.69 | 0.00 | 0.00 | 0.00 |
June | 194.16 | 96.95 | 97.21 | 283.68 | 61.63 | 0.00 | 0.00 | 0.00 |
July | 205.59 | 109.90 | 95.69 | 318.62 | 51.09 | 0.00 | 0.00 | 0.00 |
August | 192.92 | 104.46 | 88.46 | 301.20 | 54.02 | 0.00 | 0.00 | 0.00 |
September | 165.33 | 88.43 | 76.90 | 248.27 | 65.92 | 0.00 | 0.00 | 0.00 |
October | 127.00 | 69.58 | 57.41 | 196.90 | 76.71 | 0.00 | 0.00 | 0.00 |
November | 114.28 | 59.82 | 54.46 | 148.07 | 123.27 | 0.00 | 0.00 | 0.00 |
December | 100.52 | 53.75 | 46.77 | 128.36 | 140.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.02 | 77.52 | 74.51 | 214.64 | 95.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.13 | 49.99 | 46.77 | 124.14 | 51.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 205.59 | 109.90 | 98.78 | 318.62 | 141.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.68 | 0.00 | 20.68 | 15.82 | 74.62 | 0.00 | 0.00 | 0.00 |
February | 25.96 | 0.00 | 25.96 | 17.72 | 67.13 | 0.00 | 0.00 | 0.00 |
March | 31.81 | 0.00 | 31.81 | 25.00 | 69.76 | 0.00 | 0.00 | 0.00 |
April | 36.84 | 0.30 | 36.55 | 34.18 | 52.01 | 0.00 | 0.00 | 0.00 |
May | 44.32 | 2.31 | 42.01 | 43.72 | 44.75 | 0.00 | 0.00 | 0.00 |
June | 46.98 | 4.64 | 42.34 | 55.95 | 31.92 | 0.00 | 0.00 | 0.00 |
July | 44.50 | 3.78 | 40.73 | 59.36 | 26.92 | 0.00 | 0.00 | 0.00 |
August | 37.00 | 0.82 | 36.18 | 48.23 | 28.45 | 0.00 | 0.00 | 0.00 |
September | 31.23 | 0.01 | 31.23 | 37.41 | 35.74 | 0.00 | 0.00 | 0.00 |
October | 24.77 | 0.00 | 24.77 | 34.01 | 40.63 | 0.00 | 0.00 | 0.00 |
November | 22.43 | 0.00 | 22.43 | 18.04 | 65.96 | 0.00 | 0.00 | 0.00 |
December | 19.25 | 0.00 | 19.25 | 14.62 | 74.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.17 | 0.99 | 31.18 | 33.77 | 50.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.25 | 0.00 | 19.25 | 14.62 | 26.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 46.98 | 4.64 | 42.34 | 59.36 | 74.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.13 | 49.99 | 49.14 | 131.76 | 136.01 | 0.00 | 0.00 | 0.00 |
February | 118.40 | 54.72 | 63.67 | 148.09 | 121.54 | 0.00 | 0.00 | 0.00 |
March | 135.41 | 59.84 | 75.57 | 171.47 | 125.97 | 0.00 | 0.00 | 0.00 |
April | 186.62 | 97.02 | 89.60 | 264.46 | 96.38 | 0.00 | 0.00 | 0.00 |
May | 183.33 | 84.55 | 98.78 | 252.36 | 86.45 | 0.00 | 0.00 | 0.00 |
June | 194.16 | 96.95 | 97.21 | 283.80 | 61.66 | 0.00 | 0.00 | 0.00 |
July | 205.59 | 109.90 | 95.69 | 319.02 | 51.00 | 0.00 | 0.00 | 0.00 |
August | 192.92 | 104.46 | 88.46 | 302.95 | 53.32 | 0.00 | 0.00 | 0.00 |
September | 165.33 | 88.43 | 76.90 | 251.76 | 64.33 | 0.00 | 0.00 | 0.00 |
October | 127.00 | 69.58 | 57.41 | 201.60 | 74.18 | 0.00 | 0.00 | 0.00 |
November | 114.28 | 59.82 | 54.46 | 154.91 | 119.01 | 0.00 | 0.00 | 0.00 |
December | 100.52 | 53.75 | 46.77 | 136.29 | 135.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.02 | 77.52 | 74.51 | 218.56 | 93.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.13 | 49.99 | 46.77 | 131.76 | 51.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 205.59 | 109.90 | 98.78 | 319.02 | 136.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 200.63 | 147.29 | 53.34 | 293.10 | 107.57 | 0.00 | 0.00 | 0.00 |
February | 158.48 | 98.06 | 60.42 | 218.07 | 97.28 | 0.00 | 0.00 | 0.00 |
March | 126.40 | 61.57 | 64.83 | 172.26 | 102.14 | 0.00 | 0.00 | 0.00 |
April | 105.69 | 40.85 | 64.84 | 155.09 | 78.68 | 0.00 | 0.00 | 0.00 |
May | 74.47 | 9.02 | 65.45 | 92.91 | 69.73 | 0.00 | 0.00 | 0.00 |
June | 65.33 | 3.83 | 61.50 | 85.17 | 48.98 | 0.00 | 0.00 | 0.00 |
July | 68.90 | 7.37 | 61.53 | 104.24 | 39.87 | 0.00 | 0.00 | 0.00 |
August | 88.49 | 27.50 | 60.99 | 148.14 | 42.11 | 0.00 | 0.00 | 0.00 |
September | 121.52 | 60.37 | 61.15 | 197.78 | 52.42 | 0.00 | 0.00 | 0.00 |
October | 159.12 | 106.86 | 52.26 | 258.94 | 59.01 | 0.00 | 0.00 | 0.00 |
November | 193.28 | 136.94 | 56.34 | 282.96 | 94.72 | 0.00 | 0.00 | 0.00 |
December | 214.70 | 163.60 | 51.09 | 315.49 | 106.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 131.30 | 71.85 | 59.45 | 193.63 | 74.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 65.33 | 3.83 | 51.09 | 85.17 | 39.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 214.70 | 163.60 | 65.45 | 315.49 | 107.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 144.74 | 0.00 | 144.74 | 68.19 | 676.71 | 0.00 | 0.00 | 0.00 |
February | 181.69 | 0.00 | 181.69 | 77.89 | 627.39 | 0.00 | 0.00 | 0.00 |
March | 222.66 | 0.00 | 222.66 | 124.75 | 633.01 | 0.00 | 0.00 | 0.00 |
April | 257.88 | 2.08 | 255.81 | 191.95 | 472.06 | 0.00 | 0.00 | 0.00 |
May | 310.23 | 16.18 | 294.05 | 244.96 | 407.13 | 0.00 | 0.00 | 0.00 |
June | 328.85 | 32.49 | 296.36 | 333.57 | 303.06 | 0.00 | 0.00 | 0.00 |
July | 311.50 | 26.43 | 285.07 | 364.16 | 260.46 | 0.00 | 0.00 | 0.00 |
August | 258.99 | 5.75 | 253.24 | 290.59 | 281.35 | 0.00 | 0.00 | 0.00 |
September | 218.62 | 0.04 | 218.58 | 219.47 | 346.82 | 0.00 | 0.00 | 0.00 |
October | 173.40 | 0.00 | 173.40 | 194.30 | 399.43 | 0.00 | 0.00 | 0.00 |
November | 157.00 | 0.00 | 157.00 | 82.52 | 604.58 | 0.00 | 0.00 | 0.00 |
December | 134.74 | 0.00 | 134.74 | 60.26 | 677.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 225.21 | 6.95 | 218.26 | 188.41 | 473.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 134.74 | 0.00 | 134.74 | 60.26 | 260.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 328.85 | 32.49 | 296.36 | 364.16 | 677.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 144.74 | 0.00 | 144.74 | 60.96 | 698.60 | 0.00 | 0.00 | 0.00 |
February | 181.69 | 0.00 | 181.69 | 69.56 | 648.98 | 0.00 | 0.00 | 0.00 |
March | 222.66 | 0.00 | 222.66 | 114.23 | 653.16 | 0.00 | 0.00 | 0.00 |
April | 257.88 | 2.08 | 255.81 | 180.07 | 485.78 | 0.00 | 0.00 | 0.00 |
May | 310.23 | 16.18 | 294.05 | 231.08 | 418.29 | 0.00 | 0.00 | 0.00 |
June | 328.85 | 32.49 | 296.36 | 320.72 | 312.09 | 0.00 | 0.00 | 0.00 |
July | 311.50 | 26.43 | 285.07 | 352.80 | 268.23 | 0.00 | 0.00 | 0.00 |
August | 258.99 | 5.75 | 253.24 | 280.32 | 290.17 | 0.00 | 0.00 | 0.00 |
September | 218.62 | 0.04 | 218.58 | 209.91 | 358.18 | 0.00 | 0.00 | 0.00 |
October | 173.40 | 0.00 | 173.40 | 185.83 | 411.97 | 0.00 | 0.00 | 0.00 |
November | 157.00 | 0.00 | 157.00 | 74.65 | 623.40 | 0.00 | 0.00 | 0.00 |
December | 134.74 | 0.00 | 134.74 | 53.70 | 699.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 225.21 | 6.95 | 218.26 | 178.51 | 488.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 134.74 | 0.00 | 134.74 | 53.70 | 268.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 328.85 | 32.49 | 296.36 | 352.80 | 699.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.68 | 0.00 | 20.68 | 15.02 | 87.88 | 0.00 | 0.00 | 0.00 |
February | 25.96 | 0.00 | 25.96 | 16.33 | 83.29 | 0.00 | 0.00 | 0.00 |
March | 31.81 | 0.00 | 31.81 | 24.51 | 84.77 | 0.00 | 0.00 | 0.00 |
April | 36.84 | 0.30 | 36.55 | 37.51 | 63.89 | 0.00 | 0.00 | 0.00 |
May | 44.32 | 2.31 | 42.01 | 47.96 | 56.72 | 0.00 | 0.00 | 0.00 |
June | 46.98 | 4.64 | 42.34 | 62.68 | 42.69 | 0.00 | 0.00 | 0.00 |
July | 44.50 | 3.78 | 40.73 | 67.97 | 36.96 | 0.00 | 0.00 | 0.00 |
August | 37.00 | 0.82 | 36.18 | 55.84 | 39.23 | 0.00 | 0.00 | 0.00 |
September | 31.23 | 0.01 | 31.23 | 42.70 | 45.38 | 0.00 | 0.00 | 0.00 |
October | 24.77 | 0.00 | 24.77 | 37.61 | 51.78 | 0.00 | 0.00 | 0.00 |
November | 22.43 | 0.00 | 22.43 | 17.85 | 78.42 | 0.00 | 0.00 | 0.00 |
December | 19.25 | 0.00 | 19.25 | 13.77 | 88.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.17 | 0.99 | 31.18 | 36.77 | 63.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.25 | 0.00 | 19.25 | 13.77 | 36.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 46.98 | 4.64 | 42.34 | 67.97 | 88.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 208.05 | 111.16 | 96.89 | 270.64 | 306.45 | 0.00 | 0.00 | 0.00 |
February | 219.54 | 100.46 | 119.08 | 258.05 | 294.29 | 0.00 | 0.00 | 0.00 |
March | 267.94 | 119.67 | 148.26 | 334.22 | 297.80 | 0.00 | 0.00 | 0.00 |
April | 341.54 | 171.37 | 170.17 | 496.42 | 232.27 | 0.00 | 0.00 | 0.00 |
May | 321.70 | 134.06 | 187.64 | 453.68 | 214.60 | 0.00 | 0.00 | 0.00 |
June | 320.07 | 138.95 | 181.12 | 492.11 | 165.73 | 0.00 | 0.00 | 0.00 |
July | 362.45 | 180.07 | 182.38 | 602.54 | 143.21 | 0.00 | 0.00 | 0.00 |
August | 358.23 | 190.39 | 167.84 | 600.88 | 147.83 | 0.00 | 0.00 | 0.00 |
September | 261.54 | 120.30 | 141.24 | 418.85 | 167.46 | 0.00 | 0.00 | 0.00 |
October | 230.50 | 118.31 | 112.19 | 379.27 | 185.38 | 0.00 | 0.00 | 0.00 |
November | 209.64 | 106.13 | 103.51 | 274.00 | 276.30 | 0.00 | 0.00 | 0.00 |
December | 201.53 | 112.32 | 89.21 | 260.68 | 306.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.60 | 133.87 | 141.73 | 404.45 | 227.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 201.53 | 100.46 | 89.21 | 258.05 | 143.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.45 | 190.39 | 187.64 | 602.54 | 306.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.80 | 100.43 | 36.37 | 209.76 | 80.39 | 0.00 | 0.00 | 0.00 |
February | 108.06 | 66.86 | 41.20 | 155.19 | 78.34 | 0.00 | 0.00 | 0.00 |
March | 86.18 | 41.98 | 44.20 | 122.64 | 81.97 | 0.00 | 0.00 | 0.00 |
April | 72.07 | 27.85 | 44.21 | 111.99 | 65.24 | 0.00 | 0.00 | 0.00 |
May | 50.78 | 6.15 | 44.63 | 66.50 | 60.62 | 0.00 | 0.00 | 0.00 |
June | 44.55 | 2.61 | 41.93 | 62.40 | 45.81 | 0.00 | 0.00 | 0.00 |
July | 46.98 | 5.02 | 41.96 | 77.55 | 38.95 | 0.00 | 0.00 | 0.00 |
August | 60.34 | 18.75 | 41.59 | 108.87 | 40.40 | 0.00 | 0.00 | 0.00 |
September | 82.86 | 41.16 | 41.69 | 143.71 | 45.33 | 0.00 | 0.00 | 0.00 |
October | 108.49 | 72.86 | 35.63 | 186.24 | 49.65 | 0.00 | 0.00 | 0.00 |
November | 131.79 | 93.37 | 38.41 | 202.43 | 72.52 | 0.00 | 0.00 | 0.00 |
December | 146.39 | 111.55 | 34.84 | 225.26 | 80.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.53 | 48.99 | 40.54 | 139.35 | 61.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.55 | 2.61 | 34.84 | 62.40 | 38.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 146.39 | 111.55 | 44.63 | 225.26 | 81.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.19 | 0.00 | 26.19 | 15.06 | 107.70 | 0.00 | 0.00 | 0.00 |
February | 32.87 | 0.00 | 32.87 | 17.95 | 97.01 | 0.00 | 0.00 | 0.00 |
March | 40.29 | 0.00 | 40.29 | 27.75 | 98.31 | 0.00 | 0.00 | 0.00 |
April | 46.66 | 0.38 | 46.28 | 40.67 | 74.38 | 0.00 | 0.00 | 0.00 |
May | 56.13 | 2.93 | 53.20 | 52.75 | 64.14 | 0.00 | 0.00 | 0.00 |
June | 59.50 | 5.88 | 53.62 | 67.78 | 48.21 | 0.00 | 0.00 | 0.00 |
July | 56.36 | 4.78 | 51.58 | 71.21 | 42.66 | 0.00 | 0.00 | 0.00 |
August | 46.86 | 1.04 | 45.82 | 56.40 | 46.30 | 0.00 | 0.00 | 0.00 |
September | 39.55 | 0.01 | 39.55 | 43.32 | 55.93 | 0.00 | 0.00 | 0.00 |
October | 31.37 | 0.00 | 31.37 | 37.57 | 65.05 | 0.00 | 0.00 | 0.00 |
November | 28.41 | 0.00 | 28.41 | 17.89 | 96.47 | 0.00 | 0.00 | 0.00 |
December | 24.38 | 0.00 | 24.38 | 13.27 | 108.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.75 | 1.26 | 39.49 | 38.59 | 75.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.38 | 0.00 | 24.38 | 13.27 | 42.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.50 | 5.88 | 53.62 | 71.21 | 108.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.43 | 0.00 | 23.43 | 13.48 | 96.35 | 0.00 | 0.00 | 0.00 |
February | 29.41 | 0.00 | 29.41 | 16.06 | 86.79 | 0.00 | 0.00 | 0.00 |
March | 36.04 | 0.00 | 36.04 | 24.83 | 87.96 | 0.00 | 0.00 | 0.00 |
April | 41.74 | 0.34 | 41.41 | 36.38 | 66.55 | 0.00 | 0.00 | 0.00 |
May | 50.22 | 2.62 | 47.60 | 47.20 | 57.38 | 0.00 | 0.00 | 0.00 |
June | 53.23 | 5.26 | 47.97 | 60.65 | 43.13 | 0.00 | 0.00 | 0.00 |
July | 50.42 | 4.28 | 46.15 | 63.71 | 38.17 | 0.00 | 0.00 | 0.00 |
August | 41.92 | 0.93 | 40.99 | 50.46 | 41.42 | 0.00 | 0.00 | 0.00 |
September | 35.39 | 0.01 | 35.38 | 38.76 | 50.04 | 0.00 | 0.00 | 0.00 |
October | 28.07 | 0.00 | 28.07 | 33.62 | 58.20 | 0.00 | 0.00 | 0.00 |
November | 25.41 | 0.00 | 25.41 | 16.00 | 86.31 | 0.00 | 0.00 | 0.00 |
December | 21.81 | 0.00 | 21.81 | 11.87 | 96.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.46 | 1.13 | 35.33 | 34.53 | 67.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.81 | 0.00 | 21.81 | 11.87 | 38.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.23 | 5.26 | 47.97 | 63.71 | 96.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 510.71 | 374.93 | 135.77 | 756.79 | 285.75 | 0.00 | 0.00 | 0.00 |
February | 403.42 | 249.62 | 153.80 | 560.40 | 264.79 | 0.00 | 0.00 | 0.00 |
March | 321.75 | 156.73 | 165.02 | 440.50 | 278.56 | 0.00 | 0.00 | 0.00 |
April | 269.05 | 103.99 | 165.06 | 391.91 | 225.23 | 0.00 | 0.00 | 0.00 |
May | 189.57 | 22.96 | 166.61 | 225.19 | 205.79 | 0.00 | 0.00 | 0.00 |
June | 166.31 | 9.75 | 156.55 | 199.51 | 156.30 | 0.00 | 0.00 | 0.00 |
July | 175.39 | 18.75 | 156.63 | 245.61 | 135.93 | 0.00 | 0.00 | 0.00 |
August | 225.26 | 70.00 | 155.26 | 360.88 | 143.09 | 0.00 | 0.00 | 0.00 |
September | 309.33 | 153.67 | 155.66 | 496.34 | 164.25 | 0.00 | 0.00 | 0.00 |
October | 405.04 | 272.02 | 133.03 | 653.78 | 180.80 | 0.00 | 0.00 | 0.00 |
November | 492.00 | 348.59 | 143.41 | 727.29 | 257.99 | 0.00 | 0.00 | 0.00 |
December | 546.52 | 416.47 | 130.06 | 813.42 | 284.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 334.24 | 182.90 | 151.34 | 489.11 | 215.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 166.31 | 9.75 | 130.06 | 199.51 | 135.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 546.52 | 416.47 | 166.61 | 813.42 | 285.75 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185314E+10 | 0.136048E+10 | 0.492663E+09 | 0.271573E+10 | 0.100029E+10 |
February | 0.132217E+10 | 0.818116E+09 | 0.504052E+09 | 0.184825E+10 | 0.815436E+09 |
March | 0.116748E+10 | 0.568705E+09 | 0.598776E+09 | 0.162307E+10 | 0.931984E+09 |
April | 0.944769E+09 | 0.365158E+09 | 0.579611E+09 | 0.140543E+10 | 0.725988E+09 |
May | 0.687861E+09 | 83301651.90 | 0.604559E+09 | 0.878244E+09 | 0.658001E+09 |
June | 0.583982E+09 | 34251187.10 | 0.549731E+09 | 0.759647E+09 | 0.477026E+09 |
July | 0.636401E+09 | 68053370.08 | 0.568348E+09 | 0.936446E+09 | 0.435199E+09 |
August | 0.817369E+09 | 0.253989E+09 | 0.563379E+09 | 0.133563E+10 | 0.470970E+09 |
September | 0.108621E+10 | 0.539619E+09 | 0.546586E+09 | 0.175059E+10 | 0.542923E+09 |
October | 0.146973E+10 | 0.987033E+09 | 0.482692E+09 | 0.237070E+10 | 0.623367E+09 |
November | 0.172768E+10 | 0.122410E+10 | 0.503575E+09 | 0.254037E+10 | 0.870802E+09 |
December | 0.198311E+10 | 0.151118E+10 | 0.471925E+09 | 0.292229E+10 | 0.100401E+10 |
Annual Sum or Average | 0.142799E+11 | 0.781399E+10 | 0.646590E+10 | 0.210864E+11 | 0.855599E+10 |
Minimum of Months | 0.583982E+09 | 34251187.10 | 0.471925E+09 | 0.759647E+09 | 0.435199E+09 |
Maximum of Months | 0.198311E+10 | 0.151118E+10 | 0.604559E+09 | 0.292229E+10 | 0.100401E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.521833E+10 | 0.383102E+10 | 0.138731E+10 | 0.752117E+10 | 0.309894E+10 |
February | 0.372314E+10 | 0.230376E+10 | 0.141938E+10 | 0.509120E+10 | 0.256009E+10 |
March | 0.328755E+10 | 0.160144E+10 | 0.168611E+10 | 0.444719E+10 | 0.290884E+10 |
April | 0.266041E+10 | 0.102826E+10 | 0.163215E+10 | 0.384469E+10 | 0.229423E+10 |
May | 0.193697E+10 | 0.234572E+09 | 0.170240E+10 | 0.234523E+10 | 0.209797E+10 |
June | 0.164445E+10 | 96449084.55 | 0.154801E+10 | 0.202039E+10 | 0.155053E+10 |
July | 0.179206E+10 | 0.191634E+09 | 0.160043E+10 | 0.253905E+10 | 0.139433E+10 |
August | 0.230166E+10 | 0.715217E+09 | 0.158644E+10 | 0.368069E+10 | 0.149310E+10 |
September | 0.305868E+10 | 0.151953E+10 | 0.153915E+10 | 0.484551E+10 | 0.171839E+10 |
October | 0.413865E+10 | 0.277942E+10 | 0.135923E+10 | 0.657957E+10 | 0.195136E+10 |
November | 0.486503E+10 | 0.344700E+10 | 0.141803E+10 | 0.703050E+10 | 0.271563E+10 |
December | 0.558430E+10 | 0.425539E+10 | 0.132891E+10 | 0.810054E+10 | 0.310675E+10 |
Annual Sum or Average | 0.402112E+11 | 0.220037E+11 | 0.182075E+11 | 0.580457E+11 | 0.268902E+11 |
Minimum of Months | 0.164445E+10 | 96449084.55 | 0.132891E+10 | 0.202039E+10 | 0.139433E+10 |
Maximum of Months | 0.558430E+10 | 0.425539E+10 | 0.170240E+10 | 0.810054E+10 | 0.310675E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.677891E+10 | 0.497672E+10 | 0.180219E+10 | 0.999478E+10 | 0.411882E+10 |
February | 0.483657E+10 | 0.299272E+10 | 0.184385E+10 | 0.675683E+10 | 0.345538E+10 |
March | 0.427071E+10 | 0.208036E+10 | 0.219036E+10 | 0.589271E+10 | 0.395781E+10 |
April | 0.345602E+10 | 0.133577E+10 | 0.212025E+10 | 0.510583E+10 | 0.311682E+10 |
May | 0.251623E+10 | 0.304722E+09 | 0.221151E+10 | 0.305395E+10 | 0.291770E+10 |
June | 0.213624E+10 | 0.125293E+09 | 0.201095E+10 | 0.261836E+10 | 0.216306E+10 |
July | 0.232799E+10 | 0.248943E+09 | 0.207905E+10 | 0.333524E+10 | 0.192155E+10 |
August | 0.298998E+10 | 0.929108E+09 | 0.206087E+10 | 0.489614E+10 | 0.200523E+10 |
September | 0.397340E+10 | 0.197396E+10 | 0.199944E+10 | 0.645195E+10 | 0.229378E+10 |
October | 0.537634E+10 | 0.361063E+10 | 0.176572E+10 | 0.873321E+10 | 0.258298E+10 |
November | 0.631995E+10 | 0.447785E+10 | 0.184211E+10 | 0.933822E+10 | 0.361217E+10 |
December | 0.725432E+10 | 0.552799E+10 | 0.172633E+10 | 0.107531E+11 | 0.412603E+10 |
Annual Sum or Average | 0.522367E+11 | 0.285840E+11 | 0.236526E+11 | 0.769304E+11 | 0.362713E+11 |
Minimum of Months | 0.213624E+10 | 0.125293E+09 | 0.172633E+10 | 0.261836E+10 | 0.192155E+10 |
Maximum of Months | 0.725432E+10 | 0.552799E+10 | 0.221151E+10 | 0.107531E+11 | 0.412603E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.366399E+09 | 0.268990E+09 | 97408702.42 | 0.547443E+09 | 0.190690E+09 |
February | 0.261416E+09 | 0.161756E+09 | 99660556.79 | 0.368858E+09 | 0.157519E+09 |
March | 0.230832E+09 | 0.112443E+09 | 0.118389E+09 | 0.322133E+09 | 0.184624E+09 |
April | 0.186798E+09 | 72197917.93 | 0.114600E+09 | 0.277470E+09 | 0.142171E+09 |
May | 0.136003E+09 | 16470167.27 | 0.119533E+09 | 0.168420E+09 | 0.132428E+09 |
June | 0.115465E+09 | 6772047.95 | 0.108693E+09 | 0.146872E+09 | 92376436.79 |
July | 0.125829E+09 | 13455320.07 | 0.112374E+09 | 0.186262E+09 | 79171769.19 |
August | 0.161609E+09 | 50218052.04 | 0.111391E+09 | 0.269592E+09 | 82222708.01 |
September | 0.214763E+09 | 0.106692E+09 | 0.108071E+09 | 0.352676E+09 | 96023543.40 |
October | 0.290591E+09 | 0.195153E+09 | 95437466.31 | 0.479028E+09 | 0.108479E+09 |
November | 0.341593E+09 | 0.242027E+09 | 99566205.17 | 0.510562E+09 | 0.164021E+09 |
December | 0.392095E+09 | 0.298787E+09 | 93308334.56 | 0.588660E+09 | 0.189849E+09 |
Annual Sum or Average | 0.282339E+10 | 0.154496E+10 | 0.127843E+10 | 0.421798E+10 | 0.161958E+10 |
Minimum of Months | 0.115465E+09 | 6772047.95 | 93308334.56 | 0.146872E+09 | 79171769.19 |
Maximum of Months | 0.392095E+09 | 0.298787E+09 | 0.119533E+09 | 0.588660E+09 | 0.190690E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265521E+09 | 0.133901E+09 | 0.131620E+09 | 0.335088E+09 | 0.385677E+09 |
February | 0.286426E+09 | 0.132386E+09 | 0.154039E+09 | 0.347315E+09 | 0.308886E+09 |
March | 0.362688E+09 | 0.160278E+09 | 0.202410E+09 | 0.452778E+09 | 0.348625E+09 |
April | 0.483730E+09 | 0.251482E+09 | 0.232247E+09 | 0.686767E+09 | 0.256736E+09 |
May | 0.491022E+09 | 0.226458E+09 | 0.264564E+09 | 0.683428E+09 | 0.235218E+09 |
June | 0.503264E+09 | 0.251292E+09 | 0.251972E+09 | 0.746276E+09 | 0.162065E+09 |
July | 0.550654E+09 | 0.294353E+09 | 0.256300E+09 | 0.864328E+09 | 0.139204E+09 |
August | 0.516705E+09 | 0.279782E+09 | 0.236923E+09 | 0.816778E+09 | 0.147306E+09 |
September | 0.428535E+09 | 0.229221E+09 | 0.199314E+09 | 0.651472E+09 | 0.174349E+09 |
October | 0.340146E+09 | 0.186368E+09 | 0.153778E+09 | 0.531467E+09 | 0.210970E+09 |
November | 0.296219E+09 | 0.155051E+09 | 0.141168E+09 | 0.386780E+09 | 0.326722E+09 |
December | 0.269240E+09 | 0.143959E+09 | 0.125281E+09 | 0.345506E+09 | 0.385228E+09 |
Annual Sum or Average | 0.479415E+10 | 0.244453E+10 | 0.234962E+10 | 0.684798E+10 | 0.308099E+10 |
Minimum of Months | 0.265521E+09 | 0.132386E+09 | 0.125281E+09 | 0.335088E+09 | 0.139204E+09 |
Maximum of Months | 0.550654E+09 | 0.294353E+09 | 0.264564E+09 | 0.864328E+09 | 0.385677E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55383852.68 | 0.00 | 55383852.68 | 40879352.62 | 0.204985E+09 |
February | 62793579.01 | 0.00 | 62793579.01 | 41725259.44 | 0.166556E+09 |
March | 85200912.64 | 780.17 | 85200132.47 | 66837596.60 | 0.189886E+09 |
April | 95493362.34 | 768414.00 | 94724948.34 | 90129469.92 | 0.136672E+09 |
May | 0.118708E+09 | 6190456.55 | 0.112517E+09 | 0.119095E+09 | 0.121319E+09 |
June | 0.121773E+09 | 12029988.47 | 0.109743E+09 | 0.147962E+09 | 83836118.54 |
July | 0.119193E+09 | 10114061.15 | 0.109079E+09 | 0.161844E+09 | 73237678.13 |
August | 99102290.78 | 2201816.78 | 96900474.00 | 0.131135E+09 | 77513959.65 |
September | 80955510.48 | 16100.43 | 80939410.05 | 97993518.69 | 94624226.53 |
October | 66349884.71 | 0.00 | 66349884.71 | 90331331.74 | 0.112239E+09 |
November | 58137116.95 | 0.00 | 58137116.95 | 45213912.07 | 0.175800E+09 |
December | 51557659.69 | 0.00 | 51557659.69 | 37108207.11 | 0.205487E+09 |
Annual Sum or Average | 0.101465E+10 | 31321617.54 | 0.983326E+09 | 0.107025E+10 | 0.164216E+10 |
Minimum of Months | 51557659.69 | 0.00 | 51557659.69 | 37108207.11 | 73237678.13 |
Maximum of Months | 0.121773E+09 | 12029988.47 | 0.112517E+09 | 0.161844E+09 | 0.205487E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265521E+09 | 0.133901E+09 | 0.131620E+09 | 0.352829E+09 | 0.373655E+09 |
February | 0.286426E+09 | 0.132386E+09 | 0.154039E+09 | 0.359457E+09 | 0.301714E+09 |
March | 0.362688E+09 | 0.160278E+09 | 0.202410E+09 | 0.463485E+09 | 0.343157E+09 |
April | 0.483730E+09 | 0.251482E+09 | 0.232247E+09 | 0.694543E+09 | 0.253547E+09 |
May | 0.491022E+09 | 0.226458E+09 | 0.264564E+09 | 0.685766E+09 | 0.234610E+09 |
June | 0.503264E+09 | 0.251292E+09 | 0.251972E+09 | 0.746639E+09 | 0.162117E+09 |
July | 0.550654E+09 | 0.294353E+09 | 0.256300E+09 | 0.865453E+09 | 0.138952E+09 |
August | 0.516705E+09 | 0.279782E+09 | 0.236923E+09 | 0.821436E+09 | 0.145560E+09 |
September | 0.428535E+09 | 0.229221E+09 | 0.199314E+09 | 0.659978E+09 | 0.170685E+09 |
October | 0.340146E+09 | 0.186368E+09 | 0.153778E+09 | 0.542788E+09 | 0.205059E+09 |
November | 0.296219E+09 | 0.155051E+09 | 0.141168E+09 | 0.401963E+09 | 0.317379E+09 |
December | 0.269240E+09 | 0.143959E+09 | 0.125281E+09 | 0.363665E+09 | 0.372900E+09 |
Annual Sum or Average | 0.479415E+10 | 0.244453E+10 | 0.234962E+10 | 0.695800E+10 | 0.301933E+10 |
Minimum of Months | 0.265521E+09 | 0.132386E+09 | 0.125281E+09 | 0.352829E+09 | 0.138952E+09 |
Maximum of Months | 0.550654E+09 | 0.294353E+09 | 0.264564E+09 | 0.865453E+09 | 0.373655E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.293061E+09 | 0.215149E+09 | 77911467.45 | 0.426815E+09 | 0.176991E+09 |
February | 0.209091E+09 | 0.129379E+09 | 79712592.74 | 0.286147E+09 | 0.145779E+09 |
March | 0.184629E+09 | 89936327.87 | 94692605.60 | 0.249664E+09 | 0.165457E+09 |
April | 0.149409E+09 | 57746850.06 | 91662135.38 | 0.216660E+09 | 0.128785E+09 |
May | 0.108781E+09 | 13173513.96 | 95607483.13 | 0.134177E+09 | 0.113226E+09 |
June | 92353413.13 | 5416561.15 | 86936851.98 | 0.118283E+09 | 79375060.74 |
July | 0.100643E+09 | 10762115.76 | 89881160.52 | 0.145950E+09 | 74180890.34 |
August | 0.129262E+09 | 40166453.60 | 89095338.36 | 0.210647E+09 | 80337703.60 |
September | 0.171776E+09 | 85336561.19 | 86439337.30 | 0.275965E+09 | 93865309.02 |
October | 0.232427E+09 | 0.156092E+09 | 76334792.12 | 0.374927E+09 | 0.106591E+09 |
November | 0.273220E+09 | 0.193583E+09 | 79637126.46 | 0.398129E+09 | 0.154706E+09 |
December | 0.313614E+09 | 0.238982E+09 | 74631825.39 | 0.459444E+09 | 0.177618E+09 |
Annual Sum or Average | 0.225827E+10 | 0.123572E+10 | 0.102254E+10 | 0.329681E+10 | 0.149691E+10 |
Minimum of Months | 92353413.13 | 5416561.15 | 74631825.39 | 0.118283E+09 | 74180890.34 |
Maximum of Months | 0.313614E+09 | 0.238982E+09 | 95607483.13 | 0.459444E+09 | 0.177618E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44312955.30 | 0.00 | 44312955.30 | 34551159.78 | 0.164058E+09 |
February | 50241522.13 | 0.00 | 50241522.13 | 35479383.49 | 0.133345E+09 |
March | 68169765.21 | 624.22 | 68169140.99 | 56314143.45 | 0.152097E+09 |
April | 76404816.42 | 614812.68 | 75790003.74 | 79991180.14 | 0.105868E+09 |
May | 94978755.02 | 4953021.70 | 90025733.32 | 0.104063E+09 | 94355141.15 |
June | 97431324.50 | 9625266.49 | 87806058.00 | 0.129083E+09 | 63698431.68 |
July | 95367114.15 | 8092321.46 | 87274792.68 | 0.142427E+09 | 53866852.02 |
August | 79292341.88 | 1761686.91 | 77530654.97 | 0.117261E+09 | 56321320.55 |
September | 64772993.27 | 12882.05 | 64760111.22 | 87573164.77 | 69977794.95 |
October | 53086943.81 | 0.00 | 53086943.81 | 79735594.50 | 84938642.90 |
November | 46515858.69 | 0.00 | 46515858.69 | 39468909.35 | 0.138134E+09 |
December | 41251595.16 | 0.00 | 41251595.16 | 31986376.18 | 0.163551E+09 |
Annual Sum or Average | 0.811826E+09 | 25060615.52 | 0.786765E+09 | 0.937933E+09 | 0.128021E+10 |
Minimum of Months | 41251595.16 | 0.00 | 41251595.16 | 31986376.18 | 53866852.02 |
Maximum of Months | 97431324.50 | 9625266.49 | 90025733.32 | 0.142427E+09 | 0.164058E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.278642E+09 | 0.148882E+09 | 0.129760E+09 | 0.340684E+09 | 0.365816E+09 |
February | 0.265576E+09 | 0.121526E+09 | 0.144050E+09 | 0.302716E+09 | 0.295650E+09 |
March | 0.358848E+09 | 0.160278E+09 | 0.198570E+09 | 0.434748E+09 | 0.332981E+09 |
April | 0.442664E+09 | 0.222110E+09 | 0.220555E+09 | 0.614519E+09 | 0.246085E+09 |
May | 0.430846E+09 | 0.179547E+09 | 0.251299E+09 | 0.584541E+09 | 0.227445E+09 |
June | 0.414835E+09 | 0.180091E+09 | 0.234745E+09 | 0.607106E+09 | 0.160251E+09 |
July | 0.485425E+09 | 0.241161E+09 | 0.244264E+09 | 0.762424E+09 | 0.139063E+09 |
August | 0.479775E+09 | 0.254984E+09 | 0.224791E+09 | 0.759565E+09 | 0.143797E+09 |
September | 0.338985E+09 | 0.155919E+09 | 0.183066E+09 | 0.506636E+09 | 0.170431E+09 |
October | 0.308711E+09 | 0.158449E+09 | 0.150261E+09 | 0.472433E+09 | 0.200944E+09 |
November | 0.271708E+09 | 0.137555E+09 | 0.134153E+09 | 0.335289E+09 | 0.313526E+09 |
December | 0.269909E+09 | 0.150433E+09 | 0.119475E+09 | 0.328497E+09 | 0.365505E+09 |
Annual Sum or Average | 0.434593E+10 | 0.211093E+10 | 0.223499E+10 | 0.604916E+10 | 0.296149E+10 |
Minimum of Months | 0.265576E+09 | 0.121526E+09 | 0.119475E+09 | 0.302716E+09 | 0.139063E+09 |
Maximum of Months | 0.485425E+09 | 0.254984E+09 | 0.251299E+09 | 0.762424E+09 | 0.365816E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.366399E+09 | 0.268990E+09 | 97408702.42 | 0.544900E+09 | 0.190112E+09 |
February | 0.261416E+09 | 0.161756E+09 | 99660556.79 | 0.367503E+09 | 0.156066E+09 |
March | 0.230832E+09 | 0.112443E+09 | 0.118389E+09 | 0.319616E+09 | 0.183152E+09 |
April | 0.186798E+09 | 72197917.93 | 0.114600E+09 | 0.274562E+09 | 0.139716E+09 |
May | 0.136003E+09 | 16470167.27 | 0.119533E+09 | 0.166461E+09 | 0.129664E+09 |
June | 0.115465E+09 | 6772047.95 | 0.108693E+09 | 0.145508E+09 | 89461690.52 |
July | 0.125829E+09 | 13455320.07 | 0.112374E+09 | 0.183950E+09 | 76435453.34 |
August | 0.161609E+09 | 50218052.04 | 0.111391E+09 | 0.267166E+09 | 79796698.52 |
September | 0.214763E+09 | 0.106692E+09 | 0.108071E+09 | 0.352234E+09 | 93011001.67 |
October | 0.290591E+09 | 0.195153E+09 | 95437466.31 | 0.477776E+09 | 0.106911E+09 |
November | 0.341593E+09 | 0.242027E+09 | 99566205.17 | 0.509297E+09 | 0.162417E+09 |
December | 0.392095E+09 | 0.298787E+09 | 93308334.56 | 0.586721E+09 | 0.188727E+09 |
Annual Sum or Average | 0.282339E+10 | 0.154496E+10 | 0.127843E+10 | 0.419569E+10 | 0.159547E+10 |
Minimum of Months | 0.115465E+09 | 6772047.95 | 93308334.56 | 0.145508E+09 | 76435453.34 |
Maximum of Months | 0.392095E+09 | 0.298787E+09 | 0.119533E+09 | 0.586721E+09 | 0.190112E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55383852.68 | 0.00 | 55383852.68 | 39016850.52 | 0.203781E+09 |
February | 62793579.01 | 0.00 | 62793579.01 | 40574992.43 | 0.164616E+09 |
March | 85200912.64 | 780.17 | 85200132.47 | 64497719.60 | 0.188463E+09 |
April | 95493362.34 | 768414.00 | 94724948.34 | 87392142.67 | 0.134614E+09 |
May | 0.118708E+09 | 6190456.55 | 0.112517E+09 | 0.117655E+09 | 0.119099E+09 |
June | 0.121773E+09 | 12029988.47 | 0.109743E+09 | 0.147437E+09 | 81762142.35 |
July | 0.119193E+09 | 10114061.15 | 0.109079E+09 | 0.160136E+09 | 71196587.38 |
August | 99102290.78 | 2201816.78 | 96900474.00 | 0.128478E+09 | 75425538.95 |
September | 80955510.48 | 16100.43 | 80939410.05 | 97387628.23 | 91467756.20 |
October | 66349884.71 | 0.00 | 66349884.71 | 88830516.28 | 0.110683E+09 |
November | 58137116.95 | 0.00 | 58137116.95 | 44244676.37 | 0.172895E+09 |
December | 51557659.69 | 0.00 | 51557659.69 | 35575860.18 | 0.203388E+09 |
Annual Sum or Average | 0.101465E+10 | 31321617.54 | 0.983326E+09 | 0.105123E+10 | 0.161739E+10 |
Minimum of Months | 51557659.69 | 0.00 | 51557659.69 | 35575860.18 | 71196587.38 |
Maximum of Months | 0.121773E+09 | 12029988.47 | 0.112517E+09 | 0.160136E+09 | 0.203781E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.278642E+09 | 0.148882E+09 | 0.129760E+09 | 0.357611E+09 | 0.350976E+09 |
February | 0.265576E+09 | 0.121526E+09 | 0.144050E+09 | 0.314782E+09 | 0.287007E+09 |
March | 0.358848E+09 | 0.160278E+09 | 0.198570E+09 | 0.444996E+09 | 0.326780E+09 |
April | 0.442664E+09 | 0.222110E+09 | 0.220555E+09 | 0.621727E+09 | 0.242632E+09 |
May | 0.430846E+09 | 0.179547E+09 | 0.251299E+09 | 0.586844E+09 | 0.226753E+09 |
June | 0.414835E+09 | 0.180091E+09 | 0.234745E+09 | 0.607416E+09 | 0.160412E+09 |
July | 0.485425E+09 | 0.241161E+09 | 0.244264E+09 | 0.763325E+09 | 0.138871E+09 |
August | 0.479775E+09 | 0.254984E+09 | 0.224791E+09 | 0.763231E+09 | 0.141983E+09 |
September | 0.338985E+09 | 0.155919E+09 | 0.183066E+09 | 0.514714E+09 | 0.166270E+09 |
October | 0.308711E+09 | 0.158449E+09 | 0.150261E+09 | 0.483083E+09 | 0.194629E+09 |
November | 0.271708E+09 | 0.137555E+09 | 0.134153E+09 | 0.350507E+09 | 0.301032E+09 |
December | 0.269909E+09 | 0.150433E+09 | 0.119475E+09 | 0.346163E+09 | 0.350105E+09 |
Annual Sum or Average | 0.434593E+10 | 0.211093E+10 | 0.223499E+10 | 0.615440E+10 | 0.288745E+10 |
Minimum of Months | 0.265576E+09 | 0.121526E+09 | 0.119475E+09 | 0.314782E+09 | 0.138871E+09 |
Maximum of Months | 0.485425E+09 | 0.254984E+09 | 0.251299E+09 | 0.763325E+09 | 0.350976E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70140154.89 | 0.00 | 70140154.89 | 44469712.19 | 0.289150E+09 |
February | 79524105.76 | 0.00 | 79524105.76 | 47117711.47 | 0.236283E+09 |
March | 0.107902E+09 | 988.04 | 0.107901E+09 | 80850130.82 | 0.261980E+09 |
April | 0.120936E+09 | 973147.84 | 0.119963E+09 | 0.115076E+09 | 0.189994E+09 |
May | 0.150336E+09 | 7839822.62 | 0.142496E+09 | 0.151588E+09 | 0.169745E+09 |
June | 0.154218E+09 | 15235221.35 | 0.138983E+09 | 0.188679E+09 | 0.121203E+09 |
July | 0.150951E+09 | 12808820.29 | 0.138142E+09 | 0.204858E+09 | 0.109906E+09 |
August | 0.125507E+09 | 2788462.02 | 0.122718E+09 | 0.163606E+09 | 0.119076E+09 |
September | 0.102525E+09 | 20390.18 | 0.102505E+09 | 0.121094E+09 | 0.141898E+09 |
October | 84027942.54 | 0.00 | 84027942.54 | 0.106808E+09 | 0.173211E+09 |
November | 73626990.37 | 0.00 | 73626990.37 | 49865746.94 | 0.253043E+09 |
December | 65294522.88 | 0.00 | 65294522.88 | 38454870.69 | 0.294829E+09 |
Annual Sum or Average | 0.128499E+10 | 39666852.34 | 0.124532E+10 | 0.131247E+10 | 0.236032E+10 |
Minimum of Months | 65294522.88 | 0.00 | 65294522.88 | 38454870.69 | 0.109906E+09 |
Maximum of Months | 0.154218E+09 | 15235221.35 | 0.142496E+09 | 0.204858E+09 | 0.294829E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25856565.37 | 0.00 | 25856565.37 | 16393377.26 | 0.106593E+09 |
February | 29315878.22 | 0.00 | 29315878.22 | 17369539.44 | 87103579.25 |
March | 39776990.23 | 364.23 | 39776626.00 | 29804705.96 | 96576705.26 |
April | 44582134.43 | 358742.59 | 44223391.84 | 42421744.98 | 70039535.57 |
May | 55420009.14 | 2890083.24 | 52529925.90 | 55881431.30 | 62575151.47 |
June | 56851080.99 | 5616333.43 | 51234747.56 | 69554882.22 | 44680626.36 |
July | 55646616.31 | 4721861.53 | 50924754.78 | 75519049.39 | 40515959.26 |
August | 46267002.67 | 1027942.56 | 45239060.11 | 60312085.66 | 43896260.02 |
September | 37794977.19 | 7516.66 | 37787460.52 | 44640222.71 | 52309654.41 |
October | 30976178.94 | 0.00 | 30976178.94 | 39373963.15 | 63852770.35 |
November | 27141957.31 | 0.00 | 27141957.31 | 18382579.10 | 93282191.46 |
December | 24070264.77 | 0.00 | 24070264.77 | 14176057.63 | 0.108686E+09 |
Annual Sum or Average | 0.473700E+09 | 14622844.25 | 0.459077E+09 | 0.483830E+09 | 0.870111E+09 |
Minimum of Months | 24070264.77 | 0.00 | 24070264.77 | 14176057.63 | 40515959.26 |
Maximum of Months | 56851080.99 | 5616333.43 | 52529925.90 | 75519049.39 | 0.108686E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170960E+09 | 0.125510E+09 | 45450508.02 | 0.256421E+09 | 95820919.47 |
February | 0.121976E+09 | 75474510.52 | 46501214.20 | 0.172335E+09 | 80403566.33 |
March | 0.107705E+09 | 52465342.08 | 55239968.79 | 0.151069E+09 | 92468866.80 |
April | 87159368.36 | 33687257.57 | 53472110.79 | 0.131307E+09 | 71654053.12 |
May | 63458586.31 | 7684913.68 | 55773672.63 | 79411705.14 | 67664574.99 |
June | 53875375.24 | 3159810.28 | 50715564.96 | 69086419.50 | 48789043.64 |
July | 58711357.72 | 6278198.12 | 52433159.60 | 87225812.04 | 43430841.98 |
August | 75406282.36 | 23431540.72 | 51974741.64 | 0.125872E+09 | 45772913.97 |
September | 0.100207E+09 | 49782017.80 | 50425334.32 | 0.165031E+09 | 51983615.81 |
October | 0.135589E+09 | 91057819.93 | 44530737.20 | 0.222581E+09 | 59995149.62 |
November | 0.159386E+09 | 0.112929E+09 | 46457190.11 | 0.238499E+09 | 84422102.65 |
December | 0.182950E+09 | 0.139413E+09 | 43537292.90 | 0.274973E+09 | 96675199.21 |
Annual Sum or Average | 0.131738E+10 | 0.720873E+09 | 0.596511E+09 | 0.197381E+10 | 0.839081E+09 |
Minimum of Months | 53875375.24 | 3159810.28 | 43537292.90 | 69086419.50 | 43430841.98 |
Maximum of Months | 0.182950E+09 | 0.139413E+09 | 55773672.63 | 0.274973E+09 | 96675199.21 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.464021E+09 | 0.340659E+09 | 0.123362E+09 | 0.695980E+09 | 0.260078E+09 |
February | 0.331067E+09 | 0.204853E+09 | 0.126214E+09 | 0.467753E+09 | 0.218232E+09 |
March | 0.292334E+09 | 0.142402E+09 | 0.149933E+09 | 0.410032E+09 | 0.250979E+09 |
April | 0.236568E+09 | 91434107.63 | 0.145134E+09 | 0.356394E+09 | 0.194484E+09 |
May | 0.172240E+09 | 20858427.64 | 0.151381E+09 | 0.215540E+09 | 0.183655E+09 |
June | 0.146229E+09 | 8576371.43 | 0.137652E+09 | 0.187515E+09 | 0.132423E+09 |
July | 0.159355E+09 | 17040313.89 | 0.142314E+09 | 0.236749E+09 | 0.117880E+09 |
August | 0.204668E+09 | 63597994.32 | 0.141070E+09 | 0.341643E+09 | 0.124237E+09 |
September | 0.271983E+09 | 0.135119E+09 | 0.136865E+09 | 0.447927E+09 | 0.141094E+09 |
October | 0.368015E+09 | 0.247150E+09 | 0.120866E+09 | 0.604130E+09 | 0.162839E+09 |
November | 0.432606E+09 | 0.306511E+09 | 0.126094E+09 | 0.647334E+09 | 0.229139E+09 |
December | 0.496564E+09 | 0.378395E+09 | 0.118169E+09 | 0.746333E+09 | 0.262396E+09 |
Annual Sum or Average | 0.357565E+10 | 0.195660E+10 | 0.161905E+10 | 0.535733E+10 | 0.227744E+10 |
Minimum of Months | 0.146229E+09 | 8576371.43 | 0.118169E+09 | 0.187515E+09 | 0.117880E+09 |
Maximum of Months | 0.496564E+09 | 0.378395E+09 | 0.151381E+09 | 0.746333E+09 | 0.262396E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.366399E+09 | 0.268990E+09 | 97408702.42 | 0.545428E+09 | 0.187611E+09 |
February | 0.261416E+09 | 0.161756E+09 | 99660556.79 | 0.366391E+09 | 0.154660E+09 |
March | 0.230832E+09 | 0.112443E+09 | 0.118389E+09 | 0.319631E+09 | 0.182491E+09 |
April | 0.186798E+09 | 72197917.93 | 0.114600E+09 | 0.273942E+09 | 0.140657E+09 |
May | 0.136003E+09 | 16470167.27 | 0.119533E+09 | 0.165606E+09 | 0.131094E+09 |
June | 0.115465E+09 | 6772047.95 | 0.108693E+09 | 0.144254E+09 | 91330799.31 |
July | 0.125829E+09 | 13455320.07 | 0.112374E+09 | 0.183377E+09 | 78141391.98 |
August | 0.161609E+09 | 50218052.04 | 0.111391E+09 | 0.266318E+09 | 80985843.26 |
September | 0.214763E+09 | 0.106692E+09 | 0.108071E+09 | 0.349271E+09 | 94306710.45 |
October | 0.290591E+09 | 0.195153E+09 | 95437466.31 | 0.476193E+09 | 0.105919E+09 |
November | 0.341593E+09 | 0.242027E+09 | 99566205.17 | 0.507931E+09 | 0.160980E+09 |
December | 0.392095E+09 | 0.298787E+09 | 93308334.56 | 0.586447E+09 | 0.186197E+09 |
Annual Sum or Average | 0.282339E+10 | 0.154496E+10 | 0.127843E+10 | 0.418479E+10 | 0.159438E+10 |
Minimum of Months | 0.115465E+09 | 6772047.95 | 93308334.56 | 0.144254E+09 | 78141391.98 |
Maximum of Months | 0.392095E+09 | 0.298787E+09 | 0.119533E+09 | 0.586447E+09 | 0.187611E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265521E+09 | 0.133901E+09 | 0.131620E+09 | 0.332501E+09 | 0.378077E+09 |
February | 0.286426E+09 | 0.132386E+09 | 0.154039E+09 | 0.344294E+09 | 0.302292E+09 |
March | 0.362688E+09 | 0.160278E+09 | 0.202410E+09 | 0.447438E+09 | 0.343495E+09 |
April | 0.483730E+09 | 0.251482E+09 | 0.232247E+09 | 0.677172E+09 | 0.253413E+09 |
May | 0.491022E+09 | 0.226458E+09 | 0.264564E+09 | 0.673528E+09 | 0.232180E+09 |
June | 0.503264E+09 | 0.251292E+09 | 0.251972E+09 | 0.735300E+09 | 0.159734E+09 |
July | 0.550654E+09 | 0.294353E+09 | 0.256300E+09 | 0.853400E+09 | 0.136847E+09 |
August | 0.516705E+09 | 0.279782E+09 | 0.236923E+09 | 0.806741E+09 | 0.144674E+09 |
September | 0.428535E+09 | 0.229221E+09 | 0.199314E+09 | 0.643517E+09 | 0.170864E+09 |
October | 0.340146E+09 | 0.186368E+09 | 0.153778E+09 | 0.527364E+09 | 0.205465E+09 |
November | 0.296219E+09 | 0.155051E+09 | 0.141168E+09 | 0.383806E+09 | 0.319521E+09 |
December | 0.269240E+09 | 0.143959E+09 | 0.125281E+09 | 0.343805E+09 | 0.376364E+09 |
Annual Sum or Average | 0.479415E+10 | 0.244453E+10 | 0.234962E+10 | 0.676887E+10 | 0.302293E+10 |
Minimum of Months | 0.265521E+09 | 0.132386E+09 | 0.125281E+09 | 0.332501E+09 | 0.136847E+09 |
Maximum of Months | 0.550654E+09 | 0.294353E+09 | 0.264564E+09 | 0.853400E+09 | 0.378077E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55383852.68 | 0.00 | 55383852.68 | 42374082.82 | 0.199873E+09 |
February | 62793579.01 | 0.00 | 62793579.01 | 42874063.21 | 0.162411E+09 |
March | 85200912.64 | 780.17 | 85200132.47 | 66947056.03 | 0.186837E+09 |
April | 95493362.34 | 768414.00 | 94724948.34 | 88591339.77 | 0.134813E+09 |
May | 0.118708E+09 | 6190456.55 | 0.112517E+09 | 0.117107E+09 | 0.119854E+09 |
June | 0.121773E+09 | 12029988.47 | 0.109743E+09 | 0.145029E+09 | 82749008.62 |
July | 0.119193E+09 | 10114061.15 | 0.109079E+09 | 0.158984E+09 | 72102656.48 |
August | 99102290.78 | 2201816.78 | 96900474.00 | 0.129179E+09 | 76189431.27 |
September | 80955510.48 | 16100.43 | 80939410.05 | 96968982.63 | 92638789.55 |
October | 66349884.71 | 0.00 | 66349884.71 | 91096245.70 | 0.108832E+09 |
November | 58137116.95 | 0.00 | 58137116.95 | 46766288.08 | 0.170972E+09 |
December | 51557659.69 | 0.00 | 51557659.69 | 39170450.41 | 0.199471E+09 |
Annual Sum or Average | 0.101465E+10 | 31321617.54 | 0.983326E+09 | 0.106509E+10 | 0.160674E+10 |
Minimum of Months | 51557659.69 | 0.00 | 51557659.69 | 39170450.41 | 72102656.48 |
Maximum of Months | 0.121773E+09 | 12029988.47 | 0.112517E+09 | 0.158984E+09 | 0.199873E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265521E+09 | 0.133901E+09 | 0.131620E+09 | 0.352911E+09 | 0.364279E+09 |
February | 0.286426E+09 | 0.132386E+09 | 0.154039E+09 | 0.358257E+09 | 0.294036E+09 |
March | 0.362688E+09 | 0.160278E+09 | 0.202410E+09 | 0.459276E+09 | 0.337405E+09 |
April | 0.483730E+09 | 0.251482E+09 | 0.232247E+09 | 0.685468E+09 | 0.249826E+09 |
May | 0.491022E+09 | 0.226458E+09 | 0.264564E+09 | 0.675922E+09 | 0.231536E+09 |
June | 0.503264E+09 | 0.251292E+09 | 0.251972E+09 | 0.735602E+09 | 0.159811E+09 |
July | 0.550654E+09 | 0.294353E+09 | 0.256300E+09 | 0.854462E+09 | 0.136602E+09 |
August | 0.516705E+09 | 0.279782E+09 | 0.236923E+09 | 0.811425E+09 | 0.142800E+09 |
September | 0.428535E+09 | 0.229221E+09 | 0.199314E+09 | 0.652565E+09 | 0.166752E+09 |
October | 0.340146E+09 | 0.186368E+09 | 0.153778E+09 | 0.539975E+09 | 0.198671E+09 |
November | 0.296219E+09 | 0.155051E+09 | 0.141168E+09 | 0.401515E+09 | 0.308470E+09 |
December | 0.269240E+09 | 0.143959E+09 | 0.125281E+09 | 0.365035E+09 | 0.362007E+09 |
Annual Sum or Average | 0.479415E+10 | 0.244453E+10 | 0.234962E+10 | 0.689241E+10 | 0.295220E+10 |
Minimum of Months | 0.265521E+09 | 0.132386E+09 | 0.125281E+09 | 0.352911E+09 | 0.136602E+09 |
Maximum of Months | 0.550654E+09 | 0.294353E+09 | 0.264564E+09 | 0.854462E+09 | 0.364279E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.537359E+09 | 0.394500E+09 | 0.142859E+09 | 0.785049E+09 | 0.288115E+09 |
February | 0.383392E+09 | 0.237230E+09 | 0.146162E+09 | 0.527555E+09 | 0.235349E+09 |
March | 0.338537E+09 | 0.164908E+09 | 0.173629E+09 | 0.461381E+09 | 0.273563E+09 |
April | 0.273958E+09 | 0.105885E+09 | 0.168073E+09 | 0.401984E+09 | 0.203945E+09 |
May | 0.199462E+09 | 24155080.95 | 0.175307E+09 | 0.248840E+09 | 0.186757E+09 |
June | 0.169340E+09 | 9931858.23 | 0.159408E+09 | 0.220768E+09 | 0.126946E+09 |
July | 0.184540E+09 | 19733518.19 | 0.164807E+09 | 0.279191E+09 | 0.106775E+09 |
August | 0.237016E+09 | 73649592.75 | 0.163366E+09 | 0.396779E+09 | 0.112791E+09 |
September | 0.314970E+09 | 0.156474E+09 | 0.158496E+09 | 0.512642E+09 | 0.135868E+09 |
October | 0.426179E+09 | 0.286211E+09 | 0.139968E+09 | 0.693542E+09 | 0.158040E+09 |
November | 0.500979E+09 | 0.354955E+09 | 0.146023E+09 | 0.733428E+09 | 0.245506E+09 |
December | 0.575045E+09 | 0.438199E+09 | 0.136846E+09 | 0.845019E+09 | 0.286005E+09 |
Annual Sum or Average | 0.414078E+10 | 0.226583E+10 | 0.187494E+10 | 0.610618E+10 | 0.235966E+10 |
Minimum of Months | 0.169340E+09 | 9931858.23 | 0.136846E+09 | 0.220768E+09 | 0.106775E+09 |
Maximum of Months | 0.575045E+09 | 0.438199E+09 | 0.175307E+09 | 0.845019E+09 | 0.288115E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.387672E+09 | 0.00 | 0.387672E+09 | 0.182644E+09 | 0.181250E+10 |
February | 0.439538E+09 | 0.00 | 0.439538E+09 | 0.188423E+09 | 0.151778E+10 |
March | 0.596384E+09 | 5460.98 | 0.596378E+09 | 0.334129E+09 | 0.169546E+10 |
April | 0.668428E+09 | 5378694.26 | 0.663050E+09 | 0.497526E+09 | 0.122357E+10 |
May | 0.830922E+09 | 43331554.67 | 0.787591E+09 | 0.656108E+09 | 0.109047E+10 |
June | 0.852379E+09 | 84206730.00 | 0.768172E+09 | 0.864624E+09 | 0.785539E+09 |
July | 0.834320E+09 | 70795746.72 | 0.763524E+09 | 0.975367E+09 | 0.697611E+09 |
August | 0.693690E+09 | 15412133.73 | 0.678278E+09 | 0.778304E+09 | 0.753555E+09 |
September | 0.566667E+09 | 112698.72 | 0.566554E+09 | 0.568867E+09 | 0.898964E+09 |
October | 0.464432E+09 | 0.00 | 0.464432E+09 | 0.520426E+09 | 0.106983E+10 |
November | 0.406944E+09 | 0.00 | 0.406944E+09 | 0.213899E+09 | 0.156706E+10 |
December | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.161409E+09 | 0.181554E+10 |
Annual Sum or Average | 0.710227E+10 | 0.219243E+09 | 0.688302E+10 | 0.594173E+10 | 0.149279E+11 |
Minimum of Months | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.161409E+09 | 0.697611E+09 |
Maximum of Months | 0.852379E+09 | 84206730.00 | 0.787591E+09 | 0.975367E+09 | 0.181554E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.387672E+09 | 0.00 | 0.387672E+09 | 0.163275E+09 | 0.187114E+10 |
February | 0.439538E+09 | 0.00 | 0.439538E+09 | 0.168285E+09 | 0.157001E+10 |
March | 0.596384E+09 | 5460.98 | 0.596378E+09 | 0.305947E+09 | 0.174941E+10 |
April | 0.668428E+09 | 5378694.26 | 0.663050E+09 | 0.466747E+09 | 0.125914E+10 |
May | 0.830922E+09 | 43331554.67 | 0.787591E+09 | 0.618911E+09 | 0.112035E+10 |
June | 0.852379E+09 | 84206730.00 | 0.768172E+09 | 0.831315E+09 | 0.808932E+09 |
July | 0.834320E+09 | 70795746.72 | 0.763524E+09 | 0.944949E+09 | 0.718414E+09 |
August | 0.693690E+09 | 15412133.73 | 0.678278E+09 | 0.750805E+09 | 0.777182E+09 |
September | 0.566667E+09 | 112698.72 | 0.566554E+09 | 0.544091E+09 | 0.928394E+09 |
October | 0.464432E+09 | 0.00 | 0.464432E+09 | 0.497714E+09 | 0.110341E+10 |
November | 0.406944E+09 | 0.00 | 0.406944E+09 | 0.193481E+09 | 0.161584E+10 |
December | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.143822E+09 | 0.187287E+10 |
Annual Sum or Average | 0.710227E+10 | 0.219243E+09 | 0.688302E+10 | 0.562934E+10 | 0.153951E+11 |
Minimum of Months | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.143822E+09 | 0.718414E+09 |
Maximum of Months | 0.852379E+09 | 84206730.00 | 0.787591E+09 | 0.944949E+09 | 0.187287E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55383852.68 | 0.00 | 55383852.68 | 40219697.27 | 0.235382E+09 |
February | 62793579.01 | 0.00 | 62793579.01 | 39516138.32 | 0.201506E+09 |
March | 85200912.64 | 780.17 | 85200132.47 | 65644869.65 | 0.227047E+09 |
April | 95493362.34 | 768414.00 | 94724948.34 | 97237095.50 | 0.165598E+09 |
May | 0.118708E+09 | 6190456.55 | 0.112517E+09 | 0.128462E+09 | 0.151907E+09 |
June | 0.121773E+09 | 12029988.47 | 0.109743E+09 | 0.162459E+09 | 0.110644E+09 |
July | 0.119193E+09 | 10114061.15 | 0.109079E+09 | 0.182056E+09 | 98993295.20 |
August | 99102290.78 | 2201816.78 | 96900474.00 | 0.149550E+09 | 0.105062E+09 |
September | 80955510.48 | 16100.43 | 80939410.05 | 0.110667E+09 | 0.117618E+09 |
October | 66349884.71 | 0.00 | 66349884.71 | 0.100726E+09 | 0.138678E+09 |
November | 58137116.95 | 0.00 | 58137116.95 | 46274472.91 | 0.203267E+09 |
December | 51557659.69 | 0.00 | 51557659.69 | 36874386.79 | 0.235915E+09 |
Annual Sum or Average | 0.101465E+10 | 31321617.54 | 0.983326E+09 | 0.115969E+10 | 0.199162E+10 |
Minimum of Months | 51557659.69 | 0.00 | 51557659.69 | 36874386.79 | 98993295.20 |
Maximum of Months | 0.121773E+09 | 12029988.47 | 0.112517E+09 | 0.182056E+09 | 0.235915E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.557245E+09 | 0.297743E+09 | 0.259502E+09 | 0.724871E+09 | 0.820807E+09 |
February | 0.531115E+09 | 0.243035E+09 | 0.288080E+09 | 0.624275E+09 | 0.711950E+09 |
March | 0.717645E+09 | 0.320532E+09 | 0.397113E+09 | 0.895167E+09 | 0.797618E+09 |
April | 0.885266E+09 | 0.444188E+09 | 0.441078E+09 | 0.128672E+10 | 0.602031E+09 |
May | 0.861631E+09 | 0.359068E+09 | 0.502562E+09 | 0.121512E+10 | 0.574775E+09 |
June | 0.829612E+09 | 0.360156E+09 | 0.469456E+09 | 0.127555E+10 | 0.429563E+09 |
July | 0.970781E+09 | 0.482287E+09 | 0.488494E+09 | 0.161383E+10 | 0.383575E+09 |
August | 0.959482E+09 | 0.509932E+09 | 0.449550E+09 | 0.160938E+10 | 0.395959E+09 |
September | 0.677922E+09 | 0.311816E+09 | 0.366105E+09 | 0.108566E+10 | 0.434057E+09 |
October | 0.617378E+09 | 0.316876E+09 | 0.300501E+09 | 0.101583E+10 | 0.496519E+09 |
November | 0.543378E+09 | 0.275091E+09 | 0.268287E+09 | 0.710202E+09 | 0.716159E+09 |
December | 0.539779E+09 | 0.300845E+09 | 0.238934E+09 | 0.698193E+09 | 0.821319E+09 |
Annual Sum or Average | 0.869123E+10 | 0.422157E+10 | 0.446966E+10 | 0.127548E+11 | 0.718433E+10 |
Minimum of Months | 0.531115E+09 | 0.243035E+09 | 0.238934E+09 | 0.624275E+09 | 0.383575E+09 |
Maximum of Months | 0.970781E+09 | 0.509932E+09 | 0.502562E+09 | 0.161383E+10 | 0.821319E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.366399E+09 | 0.268990E+09 | 97408702.42 | 0.561831E+09 | 0.215313E+09 |
February | 0.261416E+09 | 0.161756E+09 | 99660556.79 | 0.375445E+09 | 0.189520E+09 |
March | 0.230832E+09 | 0.112443E+09 | 0.118389E+09 | 0.328486E+09 | 0.219541E+09 |
April | 0.186798E+09 | 72197917.93 | 0.114600E+09 | 0.290266E+09 | 0.169106E+09 |
May | 0.136003E+09 | 16470167.27 | 0.119533E+09 | 0.178106E+09 | 0.162353E+09 |
June | 0.115465E+09 | 6772047.95 | 0.108693E+09 | 0.161738E+09 | 0.118752E+09 |
July | 0.125829E+09 | 13455320.07 | 0.112374E+09 | 0.207706E+09 | 0.104321E+09 |
August | 0.161609E+09 | 50218052.04 | 0.111391E+09 | 0.291592E+09 | 0.108202E+09 |
September | 0.214763E+09 | 0.106692E+09 | 0.108071E+09 | 0.372504E+09 | 0.117496E+09 |
October | 0.290591E+09 | 0.195153E+09 | 95437466.31 | 0.498814E+09 | 0.132996E+09 |
November | 0.341593E+09 | 0.242027E+09 | 99566205.17 | 0.524687E+09 | 0.187985E+09 |
December | 0.392095E+09 | 0.298787E+09 | 93308334.56 | 0.603339E+09 | 0.214564E+09 |
Annual Sum or Average | 0.282339E+10 | 0.154496E+10 | 0.127843E+10 | 0.439451E+10 | 0.194015E+10 |
Minimum of Months | 0.115465E+09 | 6772047.95 | 93308334.56 | 0.161738E+09 | 0.104321E+09 |
Maximum of Months | 0.392095E+09 | 0.298787E+09 | 0.119533E+09 | 0.603339E+09 | 0.219541E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70140154.89 | 0.00 | 70140154.89 | 40342938.04 | 0.288472E+09 |
February | 79524105.76 | 0.00 | 79524105.76 | 43415630.38 | 0.234685E+09 |
March | 0.107902E+09 | 988.04 | 0.107901E+09 | 74319581.64 | 0.263310E+09 |
April | 0.120936E+09 | 973147.84 | 0.119963E+09 | 0.105408E+09 | 0.192789E+09 |
May | 0.150336E+09 | 7839822.62 | 0.142496E+09 | 0.141285E+09 | 0.171783E+09 |
June | 0.154218E+09 | 15235221.35 | 0.138983E+09 | 0.175696E+09 | 0.124961E+09 |
July | 0.150951E+09 | 12808820.29 | 0.138142E+09 | 0.190736E+09 | 0.114260E+09 |
August | 0.125507E+09 | 2788462.02 | 0.122718E+09 | 0.151061E+09 | 0.124010E+09 |
September | 0.102525E+09 | 20390.18 | 0.102505E+09 | 0.112287E+09 | 0.144975E+09 |
October | 84027942.54 | 0.00 | 84027942.54 | 0.100638E+09 | 0.174243E+09 |
November | 73626990.37 | 0.00 | 73626990.37 | 46360462.08 | 0.250049E+09 |
December | 65294522.88 | 0.00 | 65294522.88 | 35543386.15 | 0.290216E+09 |
Annual Sum or Average | 0.128499E+10 | 39666852.34 | 0.124532E+10 | 0.121709E+10 | 0.237375E+10 |
Minimum of Months | 65294522.88 | 0.00 | 65294522.88 | 35543386.15 | 0.114260E+09 |
Maximum of Months | 0.154218E+09 | 15235221.35 | 0.142496E+09 | 0.190736E+09 | 0.290216E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62754662.34 | 0.00 | 62754662.34 | 36094979.53 | 0.258073E+09 |
February | 71150518.74 | 0.00 | 71150518.74 | 38844129.00 | 0.209974E+09 |
March | 96539952.45 | 884.00 | 96539068.45 | 66494011.29 | 0.235584E+09 |
April | 0.108202E+09 | 870679.06 | 0.107332E+09 | 94308501.62 | 0.172489E+09 |
May | 0.134506E+09 | 7014319.00 | 0.127492E+09 | 0.126408E+09 | 0.153695E+09 |
June | 0.137979E+09 | 13631010.27 | 0.124348E+09 | 0.157196E+09 | 0.111803E+09 |
July | 0.135056E+09 | 11460100.04 | 0.123596E+09 | 0.170652E+09 | 0.102229E+09 |
August | 0.112291E+09 | 2494847.54 | 0.109797E+09 | 0.135155E+09 | 0.110952E+09 |
September | 91729547.13 | 18243.17 | 91711303.96 | 0.100463E+09 | 0.129709E+09 |
October | 75180118.57 | 0.00 | 75180118.57 | 90041610.31 | 0.155896E+09 |
November | 65874347.26 | 0.00 | 65874347.26 | 41478881.08 | 0.223717E+09 |
December | 58419257.03 | 0.00 | 58419257.03 | 31800802.26 | 0.259623E+09 |
Annual Sum or Average | 0.114968E+10 | 35490083.08 | 0.111419E+10 | 0.108894E+10 | 0.212375E+10 |
Minimum of Months | 58419257.03 | 0.00 | 58419257.03 | 31800802.26 | 0.102229E+09 |
Maximum of Months | 0.137979E+09 | 13631010.27 | 0.127492E+09 | 0.170652E+09 | 0.259623E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136788E+10 | 0.100422E+10 | 0.363656E+09 | 0.202698E+10 | 0.765359E+09 |
February | 0.975944E+09 | 0.603882E+09 | 0.372063E+09 | 0.135572E+10 | 0.640570E+09 |
March | 0.861765E+09 | 0.419782E+09 | 0.441983E+09 | 0.117982E+10 | 0.746092E+09 |
April | 0.697374E+09 | 0.269536E+09 | 0.427838E+09 | 0.101583E+10 | 0.583786E+09 |
May | 0.507741E+09 | 61488042.30 | 0.446253E+09 | 0.603143E+09 | 0.551184E+09 |
June | 0.431064E+09 | 25282072.96 | 0.405782E+09 | 0.517131E+09 | 0.405133E+09 |
July | 0.469758E+09 | 50232719.31 | 0.419525E+09 | 0.657848E+09 | 0.364085E+09 |
August | 0.603336E+09 | 0.187479E+09 | 0.415857E+09 | 0.966585E+09 | 0.383257E+09 |
September | 0.801773E+09 | 0.398313E+09 | 0.403460E+09 | 0.128652E+10 | 0.425726E+09 |
October | 0.108486E+10 | 0.728566E+09 | 0.356297E+09 | 0.175109E+10 | 0.484246E+09 |
November | 0.127527E+10 | 0.903557E+09 | 0.371710E+09 | 0.188513E+10 | 0.668712E+09 |
December | 0.146381E+10 | 0.111546E+10 | 0.348348E+09 | 0.217866E+10 | 0.762773E+09 |
Annual Sum or Average | 0.105406E+11 | 0.576780E+10 | 0.477277E+10 | 0.154245E+11 | 0.678092E+10 |
Minimum of Months | 0.431064E+09 | 25282072.96 | 0.348348E+09 | 0.517131E+09 | 0.364085E+09 |
Maximum of Months | 0.146381E+10 | 0.111546E+10 | 0.446253E+09 | 0.217866E+10 | 0.765359E+09 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1013.94 | 373.46 | 691.88 | 507.95 | 183.94 | 0.00 | 0.00 |
February | 763.99 | 337.07 | 546.53 | 338.18 | 208.36 | 0.00 | 0.00 |
March | 605.99 | 347.96 | 435.89 | 212.33 | 223.56 | 0.00 | 0.00 |
April | 542.22 | 280.09 | 364.49 | 140.88 | 223.62 | 0.00 | 0.00 |
May | 327.90 | 245.67 | 256.82 | 31.10 | 225.72 | 0.00 | 0.00 |
June | 293.07 | 184.04 | 225.30 | 13.21 | 212.09 | 0.00 | 0.00 |
July | 349.63 | 162.48 | 237.61 | 25.41 | 212.20 | 0.00 | 0.00 |
August | 498.67 | 175.84 | 305.17 | 94.83 | 210.34 | 0.00 | 0.00 |
September | 675.38 | 209.46 | 419.06 | 208.19 | 210.87 | 0.00 | 0.00 |
October | 885.12 | 232.74 | 548.73 | 368.52 | 180.22 | 0.00 | 0.00 |
November | 980.08 | 335.96 | 666.54 | 472.26 | 194.28 | 0.00 | 0.00 |
December | 1091.06 | 374.85 | 740.41 | 564.21 | 176.20 | 0.00 | 0.00 |
Annual Sum or Average | 668.65 | 271.31 | 452.81 | 247.78 | 205.03 | 0.00 | 0.00 |
Minimum of Months | 293.07 | 162.48 | 225.30 | 13.21 | 176.20 | 0.00 | 0.00 |
Maximum of Months | 1091.06 | 374.85 | 740.41 | 564.21 | 225.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2808.08 | 1157.01 | 1948.30 | 1430.34 | 517.96 | 0.00 | 0.00 |
February | 2104.50 | 1058.24 | 1539.00 | 952.28 | 586.71 | 0.00 | 0.00 |
March | 1660.39 | 1086.04 | 1227.43 | 597.91 | 629.52 | 0.00 | 0.00 |
April | 1483.29 | 885.12 | 1026.39 | 396.71 | 629.69 | 0.00 | 0.00 |
May | 875.61 | 783.29 | 723.18 | 87.58 | 635.60 | 0.00 | 0.00 |
June | 779.47 | 598.20 | 634.43 | 37.21 | 597.22 | 0.00 | 0.00 |
July | 947.97 | 520.58 | 669.08 | 71.55 | 597.53 | 0.00 | 0.00 |
August | 1374.21 | 557.46 | 859.34 | 267.03 | 592.31 | 0.00 | 0.00 |
September | 1869.41 | 662.96 | 1180.05 | 586.24 | 593.81 | 0.00 | 0.00 |
October | 2456.53 | 728.55 | 1545.20 | 1037.72 | 507.48 | 0.00 | 0.00 |
November | 2712.38 | 1047.70 | 1876.94 | 1329.86 | 547.08 | 0.00 | 0.00 |
December | 3024.40 | 1159.93 | 2084.94 | 1588.78 | 496.16 | 0.00 | 0.00 |
Annual Sum or Average | 1840.62 | 852.68 | 1275.09 | 697.73 | 577.36 | 0.00 | 0.00 |
Minimum of Months | 779.47 | 520.58 | 634.43 | 37.21 | 496.16 | 0.00 | 0.00 |
Maximum of Months | 3024.40 | 1159.93 | 2084.94 | 1588.78 | 635.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3731.62 | 1537.79 | 2530.95 | 1858.09 | 672.86 | 0.00 | 0.00 |
February | 2793.00 | 1428.32 | 1999.24 | 1237.07 | 762.17 | 0.00 | 0.00 |
March | 2200.09 | 1477.68 | 1594.50 | 776.72 | 817.79 | 0.00 | 0.00 |
April | 1969.84 | 1202.48 | 1333.34 | 515.34 | 818.00 | 0.00 | 0.00 |
May | 1140.21 | 1089.34 | 939.45 | 113.77 | 825.68 | 0.00 | 0.00 |
June | 1010.17 | 834.52 | 824.17 | 48.34 | 775.83 | 0.00 | 0.00 |
July | 1245.24 | 717.42 | 869.17 | 92.94 | 776.23 | 0.00 | 0.00 |
August | 1828.01 | 748.67 | 1116.33 | 346.89 | 769.44 | 0.00 | 0.00 |
September | 2489.18 | 884.95 | 1532.95 | 761.56 | 771.39 | 0.00 | 0.00 |
October | 3260.61 | 964.37 | 2007.30 | 1348.05 | 659.24 | 0.00 | 0.00 |
November | 3602.71 | 1393.58 | 2438.25 | 1727.56 | 710.69 | 0.00 | 0.00 |
December | 4014.76 | 1540.48 | 2708.45 | 2063.92 | 644.54 | 0.00 | 0.00 |
Annual Sum or Average | 2439.45 | 1150.16 | 1656.41 | 906.39 | 750.02 | 0.00 | 0.00 |
Minimum of Months | 1010.17 | 717.42 | 824.17 | 48.34 | 644.54 | 0.00 | 0.00 |
Maximum of Months | 4014.76 | 1540.48 | 2708.45 | 2063.92 | 825.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 323.04 | 208.73 | 235.93 | 150.42 | 85.51 | 0.00 | 0.00 |
February | 292.54 | 189.30 | 226.46 | 121.59 | 104.87 | 0.00 | 0.00 |
March | 286.88 | 196.66 | 221.59 | 101.82 | 119.77 | 0.00 | 0.00 |
April | 370.09 | 151.98 | 258.69 | 124.88 | 133.81 | 0.00 | 0.00 |
May | 316.01 | 135.23 | 234.10 | 90.70 | 143.41 | 0.00 | 0.00 |
June | 342.54 | 96.13 | 238.71 | 99.56 | 139.15 | 0.00 | 0.00 |
July | 390.68 | 79.97 | 252.57 | 114.92 | 137.65 | 0.00 | 0.00 |
August | 404.47 | 84.56 | 253.25 | 123.21 | 130.05 | 0.00 | 0.00 |
September | 386.21 | 103.11 | 248.19 | 129.60 | 118.59 | 0.00 | 0.00 |
October | 375.70 | 117.69 | 235.49 | 142.44 | 93.05 | 0.00 | 0.00 |
November | 341.66 | 184.80 | 246.07 | 153.19 | 92.88 | 0.00 | 0.00 |
December | 341.49 | 207.42 | 246.91 | 165.30 | 81.61 | 0.00 | 0.00 |
Annual Sum or Average | 347.93 | 146.08 | 241.55 | 126.51 | 115.04 | 0.00 | 0.00 |
Minimum of Months | 286.88 | 79.97 | 221.59 | 90.70 | 81.61 | 0.00 | 0.00 |
Maximum of Months | 404.47 | 208.73 | 258.69 | 165.30 | 143.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 145.02 | 214.07 | 119.81 | 49.99 | 69.82 | 0.00 | 0.00 |
February | 163.80 | 191.53 | 144.35 | 54.72 | 89.63 | 0.00 | 0.00 |
March | 195.84 | 196.85 | 167.22 | 59.84 | 107.38 | 0.00 | 0.00 |
April | 301.71 | 149.53 | 223.47 | 97.32 | 126.15 | 0.00 | 0.00 |
May | 299.33 | 131.72 | 227.65 | 86.86 | 140.79 | 0.00 | 0.00 |
June | 344.14 | 93.89 | 241.14 | 101.59 | 139.55 | 0.00 | 0.00 |
July | 382.96 | 78.64 | 250.09 | 113.68 | 136.42 | 0.00 | 0.00 |
August | 355.14 | 82.77 | 229.92 | 105.28 | 124.64 | 0.00 | 0.00 |
September | 291.23 | 101.16 | 196.56 | 88.44 | 108.12 | 0.00 | 0.00 |
October | 235.54 | 117.62 | 151.77 | 69.58 | 82.19 | 0.00 | 0.00 |
November | 170.22 | 187.97 | 136.71 | 59.82 | 76.89 | 0.00 | 0.00 |
December | 147.42 | 213.73 | 119.77 | 53.75 | 66.02 | 0.00 | 0.00 |
Annual Sum or Average | 253.16 | 146.40 | 184.20 | 78.51 | 105.69 | 0.00 | 0.00 |
Minimum of Months | 145.02 | 78.64 | 119.77 | 49.99 | 66.02 | 0.00 | 0.00 |
Maximum of Months | 382.96 | 214.07 | 250.09 | 113.68 | 140.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 159.35 | 66.08 | 109.42 | 80.33 | 29.09 | 0.00 | 0.00 |
February | 118.28 | 60.26 | 86.43 | 53.48 | 32.95 | 0.00 | 0.00 |
March | 93.21 | 61.77 | 68.93 | 33.58 | 35.35 | 0.00 | 0.00 |
April | 83.59 | 49.69 | 57.64 | 22.28 | 35.36 | 0.00 | 0.00 |
May | 50.10 | 42.27 | 40.61 | 4.92 | 35.70 | 0.00 | 0.00 |
June | 45.63 | 30.62 | 35.63 | 2.09 | 33.54 | 0.00 | 0.00 |
July | 54.49 | 27.70 | 37.58 | 4.02 | 33.56 | 0.00 | 0.00 |
August | 78.65 | 29.99 | 48.26 | 15.00 | 33.26 | 0.00 | 0.00 |
September | 106.47 | 36.21 | 66.27 | 32.92 | 33.35 | 0.00 | 0.00 |
October | 139.98 | 39.80 | 86.78 | 58.28 | 28.50 | 0.00 | 0.00 |
November | 153.60 | 59.69 | 105.41 | 74.68 | 30.72 | 0.00 | 0.00 |
December | 171.54 | 66.32 | 117.09 | 89.23 | 27.86 | 0.00 | 0.00 |
Annual Sum or Average | 104.54 | 47.47 | 71.61 | 39.18 | 32.42 | 0.00 | 0.00 |
Minimum of Months | 45.63 | 27.70 | 35.63 | 2.09 | 27.86 | 0.00 | 0.00 |
Maximum of Months | 171.54 | 66.32 | 117.09 | 89.23 | 35.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12.90 | 61.25 | 16.54 | 0.00 | 16.54 | 0.00 | 0.00 |
February | 14.67 | 55.12 | 20.77 | 0.00 | 20.77 | 0.00 | 0.00 |
March | 21.03 | 56.79 | 25.45 | 0.00 | 25.45 | 0.00 | 0.00 |
April | 30.86 | 40.84 | 29.48 | 0.24 | 29.24 | 0.00 | 0.00 |
May | 38.85 | 35.23 | 35.46 | 1.85 | 33.61 | 0.00 | 0.00 |
June | 49.80 | 24.58 | 37.59 | 3.71 | 33.88 | 0.00 | 0.00 |
July | 53.18 | 20.11 | 35.61 | 3.02 | 32.58 | 0.00 | 0.00 |
August | 43.78 | 21.03 | 29.60 | 0.66 | 28.95 | 0.00 | 0.00 |
September | 33.79 | 27.00 | 24.99 | 0.00 | 24.98 | 0.00 | 0.00 |
October | 29.77 | 31.71 | 19.82 | 0.00 | 19.82 | 0.00 | 0.00 |
November | 15.23 | 53.29 | 17.95 | 0.00 | 17.95 | 0.00 | 0.00 |
December | 11.94 | 61.06 | 15.40 | 0.00 | 15.40 | 0.00 | 0.00 |
Annual Sum or Average | 29.74 | 40.60 | 25.74 | 0.79 | 24.95 | 0.00 | 0.00 |
Minimum of Months | 11.94 | 20.11 | 15.40 | 0.00 | 15.40 | 0.00 | 0.00 |
Maximum of Months | 53.18 | 61.25 | 37.59 | 3.71 | 33.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 327.38 | 204.30 | 240.83 | 156.02 | 84.82 | 0.00 | 0.00 |
February | 274.62 | 184.30 | 217.84 | 117.10 | 100.74 | 0.00 | 0.00 |
March | 278.69 | 189.75 | 220.16 | 101.82 | 118.34 | 0.00 | 0.00 |
April | 340.54 | 146.38 | 242.85 | 113.54 | 129.30 | 0.00 | 0.00 |
May | 277.85 | 130.79 | 211.64 | 73.18 | 138.45 | 0.00 | 0.00 |
June | 289.11 | 95.09 | 204.59 | 72.09 | 132.50 | 0.00 | 0.00 |
July | 352.76 | 79.89 | 228.22 | 95.06 | 133.15 | 0.00 | 0.00 |
August | 382.45 | 82.60 | 239.47 | 113.95 | 125.52 | 0.00 | 0.00 |
September | 330.64 | 100.92 | 213.64 | 101.32 | 112.32 | 0.00 | 0.00 |
October | 353.62 | 113.79 | 223.75 | 132.02 | 91.73 | 0.00 | 0.00 |
November | 322.92 | 180.70 | 236.61 | 146.44 | 90.17 | 0.00 | 0.00 |
December | 338.35 | 203.57 | 247.16 | 167.72 | 79.44 | 0.00 | 0.00 |
Annual Sum or Average | 322.82 | 142.46 | 227.34 | 115.93 | 111.41 | 0.00 | 0.00 |
Minimum of Months | 274.62 | 79.89 | 204.59 | 72.09 | 79.44 | 0.00 | 0.00 |
Maximum of Months | 382.45 | 204.30 | 247.16 | 167.72 | 138.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 142.68 | 201.72 | 124.71 | 55.59 | 69.12 | 0.00 | 0.00 |
February | 142.94 | 182.74 | 135.73 | 50.23 | 85.50 | 0.00 | 0.00 |
March | 185.64 | 187.79 | 165.79 | 59.84 | 105.95 | 0.00 | 0.00 |
April | 271.43 | 143.40 | 207.62 | 85.99 | 121.64 | 0.00 | 0.00 |
May | 261.83 | 127.93 | 205.18 | 69.35 | 135.83 | 0.00 | 0.00 |
June | 289.59 | 91.80 | 207.02 | 74.12 | 132.90 | 0.00 | 0.00 |
July | 343.47 | 77.12 | 225.74 | 93.82 | 131.92 | 0.00 | 0.00 |
August | 332.34 | 80.58 | 216.13 | 96.02 | 120.11 | 0.00 | 0.00 |
September | 235.36 | 98.64 | 162.01 | 60.16 | 101.85 | 0.00 | 0.00 |
October | 211.23 | 111.69 | 140.03 | 59.16 | 80.87 | 0.00 | 0.00 |
November | 148.07 | 178.62 | 127.26 | 53.07 | 74.19 | 0.00 | 0.00 |
December | 136.98 | 201.11 | 120.02 | 56.17 | 63.86 | 0.00 | 0.00 |
Annual Sum or Average | 225.69 | 140.05 | 169.98 | 67.93 | 102.05 | 0.00 | 0.00 |
Minimum of Months | 136.98 | 77.12 | 120.02 | 50.23 | 63.86 | 0.00 | 0.00 |
Maximum of Months | 343.47 | 201.72 | 225.74 | 96.02 | 135.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 367.97 | 270.29 | 272.92 | 174.05 | 98.87 | 0.00 | 0.00 |
February | 285.53 | 251.40 | 232.26 | 115.88 | 116.38 | 0.00 | 0.00 |
March | 248.71 | 260.00 | 204.49 | 72.76 | 131.74 | 0.00 | 0.00 |
April | 248.62 | 202.70 | 188.75 | 48.79 | 139.97 | 0.00 | 0.00 |
May | 185.54 | 178.53 | 164.82 | 14.66 | 150.16 | 0.00 | 0.00 |
June | 195.56 | 130.84 | 158.63 | 12.57 | 146.06 | 0.00 | 0.00 |
July | 223.36 | 114.11 | 158.55 | 15.25 | 143.30 | 0.00 | 0.00 |
August | 257.47 | 123.64 | 168.70 | 33.92 | 134.78 | 0.00 | 0.00 |
September | 300.28 | 149.27 | 197.73 | 71.35 | 126.38 | 0.00 | 0.00 |
October | 360.49 | 168.96 | 230.96 | 126.27 | 104.69 | 0.00 | 0.00 |
November | 360.13 | 246.63 | 267.27 | 161.82 | 105.45 | 0.00 | 0.00 |
December | 389.08 | 272.83 | 287.07 | 193.33 | 93.74 | 0.00 | 0.00 |
Annual Sum or Average | 285.32 | 197.16 | 210.92 | 86.62 | 124.30 | 0.00 | 0.00 |
Minimum of Months | 185.54 | 114.11 | 158.55 | 12.57 | 93.74 | 0.00 | 0.00 |
Maximum of Months | 389.08 | 272.83 | 287.07 | 193.33 | 150.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 321.71 | 205.13 | 235.93 | 150.42 | 85.51 | 0.00 | 0.00 |
February | 290.48 | 185.60 | 226.46 | 121.59 | 104.87 | 0.00 | 0.00 |
March | 284.00 | 193.99 | 221.59 | 101.82 | 119.77 | 0.00 | 0.00 |
April | 364.97 | 150.06 | 258.69 | 124.88 | 133.81 | 0.00 | 0.00 |
May | 311.21 | 133.54 | 234.10 | 90.70 | 143.41 | 0.00 | 0.00 |
June | 337.22 | 94.74 | 238.71 | 99.56 | 139.15 | 0.00 | 0.00 |
July | 385.45 | 78.63 | 252.57 | 114.92 | 137.65 | 0.00 | 0.00 |
August | 399.46 | 83.07 | 253.25 | 123.21 | 130.05 | 0.00 | 0.00 |
September | 381.79 | 101.08 | 248.19 | 129.60 | 118.59 | 0.00 | 0.00 |
October | 373.23 | 114.80 | 235.49 | 142.44 | 93.05 | 0.00 | 0.00 |
November | 339.77 | 181.12 | 246.07 | 153.19 | 92.88 | 0.00 | 0.00 |
December | 340.49 | 203.21 | 246.91 | 165.30 | 81.61 | 0.00 | 0.00 |
Annual Sum or Average | 344.46 | 143.53 | 241.55 | 126.51 | 115.04 | 0.00 | 0.00 |
Minimum of Months | 284.00 | 78.63 | 221.59 | 90.70 | 81.61 | 0.00 | 0.00 |
Maximum of Months | 399.46 | 205.13 | 258.69 | 165.30 | 143.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 145.67 | 208.72 | 119.81 | 49.99 | 69.82 | 0.00 | 0.00 |
February | 163.79 | 186.66 | 144.35 | 54.72 | 89.63 | 0.00 | 0.00 |
March | 194.26 | 193.53 | 167.22 | 59.84 | 107.38 | 0.00 | 0.00 |
April | 297.57 | 147.33 | 223.47 | 97.32 | 126.15 | 0.00 | 0.00 |
May | 294.89 | 130.00 | 227.65 | 86.86 | 140.79 | 0.00 | 0.00 |
June | 338.75 | 92.58 | 241.14 | 101.59 | 139.55 | 0.00 | 0.00 |
July | 377.81 | 77.36 | 250.09 | 113.68 | 136.42 | 0.00 | 0.00 |
August | 350.65 | 81.23 | 229.92 | 105.28 | 124.64 | 0.00 | 0.00 |
September | 287.94 | 98.84 | 196.56 | 88.44 | 108.12 | 0.00 | 0.00 |
October | 234.77 | 113.97 | 151.77 | 69.58 | 82.19 | 0.00 | 0.00 |
November | 170.68 | 182.71 | 136.71 | 59.82 | 76.89 | 0.00 | 0.00 |
December | 148.80 | 207.51 | 119.77 | 53.75 | 66.02 | 0.00 | 0.00 |
Annual Sum or Average | 250.92 | 143.16 | 184.20 | 78.51 | 105.69 | 0.00 | 0.00 |
Minimum of Months | 145.67 | 77.36 | 119.77 | 49.99 | 66.02 | 0.00 | 0.00 |
Maximum of Months | 377.81 | 208.72 | 250.09 | 113.68 | 140.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 293.10 | 107.57 | 200.63 | 147.29 | 53.34 | 0.00 | 0.00 |
February | 218.07 | 97.28 | 158.48 | 98.06 | 60.42 | 0.00 | 0.00 |
March | 172.26 | 102.14 | 126.40 | 61.57 | 64.83 | 0.00 | 0.00 |
April | 155.09 | 78.68 | 105.69 | 40.85 | 64.84 | 0.00 | 0.00 |
May | 92.91 | 69.73 | 74.47 | 9.02 | 65.45 | 0.00 | 0.00 |
June | 85.17 | 48.98 | 65.33 | 3.83 | 61.50 | 0.00 | 0.00 |
July | 104.24 | 39.87 | 68.90 | 7.37 | 61.53 | 0.00 | 0.00 |
August | 148.14 | 42.11 | 88.49 | 27.50 | 60.99 | 0.00 | 0.00 |
September | 197.78 | 52.42 | 121.52 | 60.37 | 61.15 | 0.00 | 0.00 |
October | 258.94 | 59.01 | 159.12 | 106.86 | 52.26 | 0.00 | 0.00 |
November | 282.96 | 94.72 | 193.28 | 136.94 | 56.34 | 0.00 | 0.00 |
December | 315.49 | 106.78 | 214.70 | 163.60 | 51.09 | 0.00 | 0.00 |
Annual Sum or Average | 193.63 | 74.82 | 131.30 | 71.85 | 59.45 | 0.00 | 0.00 |
Minimum of Months | 85.17 | 39.87 | 65.33 | 3.83 | 51.09 | 0.00 | 0.00 |
Maximum of Months | 315.49 | 107.57 | 214.70 | 163.60 | 65.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 68.19 | 676.71 | 144.74 | 0.00 | 144.74 | 0.00 | 0.00 |
February | 77.89 | 627.39 | 181.69 | 0.00 | 181.69 | 0.00 | 0.00 |
March | 124.75 | 633.01 | 222.66 | 0.00 | 222.66 | 0.00 | 0.00 |
April | 191.95 | 472.06 | 257.88 | 2.08 | 255.81 | 0.00 | 0.00 |
May | 244.96 | 407.13 | 310.23 | 16.18 | 294.05 | 0.00 | 0.00 |
June | 333.57 | 303.06 | 328.85 | 32.49 | 296.36 | 0.00 | 0.00 |
July | 364.16 | 260.46 | 311.50 | 26.43 | 285.07 | 0.00 | 0.00 |
August | 290.59 | 281.35 | 258.99 | 5.75 | 253.24 | 0.00 | 0.00 |
September | 219.47 | 346.82 | 218.62 | 0.04 | 218.58 | 0.00 | 0.00 |
October | 194.30 | 399.43 | 173.40 | 0.00 | 173.40 | 0.00 | 0.00 |
November | 82.52 | 604.58 | 157.00 | 0.00 | 157.00 | 0.00 | 0.00 |
December | 60.26 | 677.85 | 134.74 | 0.00 | 134.74 | 0.00 | 0.00 |
Annual Sum or Average | 188.41 | 473.36 | 225.21 | 6.95 | 218.26 | 0.00 | 0.00 |
Minimum of Months | 60.26 | 260.46 | 134.74 | 0.00 | 134.74 | 0.00 | 0.00 |
Maximum of Months | 364.16 | 677.85 | 328.85 | 32.49 | 296.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 60.96 | 698.60 | 144.74 | 0.00 | 144.74 | 0.00 | 0.00 |
February | 69.56 | 648.98 | 181.69 | 0.00 | 181.69 | 0.00 | 0.00 |
March | 114.23 | 653.16 | 222.66 | 0.00 | 222.66 | 0.00 | 0.00 |
April | 180.07 | 485.78 | 257.88 | 2.08 | 255.81 | 0.00 | 0.00 |
May | 231.08 | 418.29 | 310.23 | 16.18 | 294.05 | 0.00 | 0.00 |
June | 320.72 | 312.09 | 328.85 | 32.49 | 296.36 | 0.00 | 0.00 |
July | 352.80 | 268.23 | 311.50 | 26.43 | 285.07 | 0.00 | 0.00 |
August | 280.32 | 290.17 | 258.99 | 5.75 | 253.24 | 0.00 | 0.00 |
September | 209.91 | 358.18 | 218.62 | 0.04 | 218.58 | 0.00 | 0.00 |
October | 185.83 | 411.97 | 173.40 | 0.00 | 173.40 | 0.00 | 0.00 |
November | 74.65 | 623.40 | 157.00 | 0.00 | 157.00 | 0.00 | 0.00 |
December | 53.70 | 699.25 | 134.74 | 0.00 | 134.74 | 0.00 | 0.00 |
Annual Sum or Average | 178.51 | 488.18 | 225.21 | 6.95 | 218.26 | 0.00 | 0.00 |
Minimum of Months | 53.70 | 268.23 | 134.74 | 0.00 | 134.74 | 0.00 | 0.00 |
Maximum of Months | 352.80 | 699.25 | 328.85 | 32.49 | 296.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 484.62 | 463.93 | 365.53 | 211.59 | 153.93 | 0.00 | 0.00 |
February | 422.43 | 448.78 | 353.56 | 167.32 | 186.23 | 0.00 | 0.00 |
March | 473.46 | 456.63 | 385.93 | 161.65 | 224.28 | 0.00 | 0.00 |
April | 641.21 | 356.69 | 450.45 | 199.52 | 250.93 | 0.00 | 0.00 |
May | 564.12 | 327.91 | 416.79 | 142.52 | 274.27 | 0.00 | 0.00 |
June | 614.28 | 251.32 | 411.59 | 146.20 | 265.39 | 0.00 | 0.00 |
July | 746.16 | 217.22 | 453.93 | 188.87 | 265.06 | 0.00 | 0.00 |
August | 764.15 | 226.03 | 455.57 | 209.96 | 245.61 | 0.00 | 0.00 |
September | 603.86 | 256.77 | 375.63 | 161.47 | 214.16 | 0.00 | 0.00 |
October | 599.64 | 283.34 | 363.77 | 191.17 | 172.60 | 0.00 | 0.00 |
November | 485.48 | 418.45 | 363.85 | 199.51 | 164.35 | 0.00 | 0.00 |
December | 488.61 | 463.75 | 367.17 | 223.88 | 143.29 | 0.00 | 0.00 |
Annual Sum or Average | 575.12 | 347.03 | 397.30 | 183.85 | 213.45 | 0.00 | 0.00 |
Minimum of Months | 422.43 | 217.22 | 353.56 | 142.52 | 143.29 | 0.00 | 0.00 |
Maximum of Months | 764.15 | 463.93 | 455.57 | 223.88 | 274.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 769.84 | 474.33 | 560.32 | 374.93 | 185.39 | 0.00 | 0.00 |
February | 585.78 | 439.97 | 465.70 | 249.62 | 216.08 | 0.00 | 0.00 |
March | 489.81 | 461.56 | 398.08 | 156.73 | 241.35 | 0.00 | 0.00 |
April | 468.47 | 365.66 | 357.45 | 104.70 | 252.75 | 0.00 | 0.00 |
May | 321.53 | 323.70 | 295.92 | 28.50 | 267.41 | 0.00 | 0.00 |
June | 322.22 | 241.93 | 279.04 | 20.89 | 258.15 | 0.00 | 0.00 |
July | 376.16 | 212.38 | 282.17 | 27.82 | 254.35 | 0.00 | 0.00 |
August | 466.56 | 229.64 | 314.04 | 71.97 | 242.07 | 0.00 | 0.00 |
September | 578.17 | 269.97 | 384.27 | 153.68 | 230.58 | 0.00 | 0.00 |
October | 720.80 | 299.89 | 464.48 | 272.02 | 192.47 | 0.00 | 0.00 |
November | 749.39 | 428.99 | 545.82 | 348.59 | 197.23 | 0.00 | 0.00 |
December | 821.30 | 472.81 | 592.71 | 416.47 | 176.25 | 0.00 | 0.00 |
Annual Sum or Average | 555.88 | 351.28 | 411.44 | 185.28 | 226.16 | 0.00 | 0.00 |
Minimum of Months | 321.53 | 212.38 | 279.04 | 20.89 | 176.25 | 0.00 | 0.00 |
Maximum of Months | 821.30 | 474.33 | 592.71 | 416.47 | 267.41 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.271573E+10 | 0.100029E+10 | 0.185314E+10 | 0.136048E+10 | 0.492663E+09 | 0.00 | 0.00 |
February | 0.184825E+10 | 0.815436E+09 | 0.132217E+10 | 0.818116E+09 | 0.504052E+09 | 0.00 | 0.00 |
March | 0.162307E+10 | 0.931984E+09 | 0.116748E+10 | 0.568705E+09 | 0.598776E+09 | 0.00 | 0.00 |
April | 0.140543E+10 | 0.725988E+09 | 0.944769E+09 | 0.365158E+09 | 0.579611E+09 | 0.00 | 0.00 |
May | 0.878244E+09 | 0.658001E+09 | 0.687861E+09 | 83301651.90 | 0.604559E+09 | 0.00 | 0.00 |
June | 0.759647E+09 | 0.477026E+09 | 0.583982E+09 | 34251187.10 | 0.549731E+09 | 0.00 | 0.00 |
July | 0.936446E+09 | 0.435199E+09 | 0.636401E+09 | 68053370.08 | 0.568348E+09 | 0.00 | 0.00 |
August | 0.133563E+10 | 0.470970E+09 | 0.817369E+09 | 0.253989E+09 | 0.563379E+09 | 0.00 | 0.00 |
September | 0.175059E+10 | 0.542923E+09 | 0.108621E+10 | 0.539619E+09 | 0.546586E+09 | 0.00 | 0.00 |
October | 0.237070E+10 | 0.623367E+09 | 0.146973E+10 | 0.987033E+09 | 0.482692E+09 | 0.00 | 0.00 |
November | 0.254037E+10 | 0.870802E+09 | 0.172768E+10 | 0.122410E+10 | 0.503575E+09 | 0.00 | 0.00 |
December | 0.292229E+10 | 0.100401E+10 | 0.198311E+10 | 0.151118E+10 | 0.471925E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.210864E+11 | 0.855599E+10 | 0.142799E+11 | 0.781399E+10 | 0.646590E+10 | 0.00 | 0.00 |
Minimum of Months | 0.759647E+09 | 0.435199E+09 | 0.583982E+09 | 34251187.10 | 0.471925E+09 | 0.00 | 0.00 |
Maximum of Months | 0.292229E+10 | 0.100401E+10 | 0.198311E+10 | 0.151118E+10 | 0.604559E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.752117E+10 | 0.309894E+10 | 0.521833E+10 | 0.383102E+10 | 0.138731E+10 | 0.00 | 0.00 |
February | 0.509120E+10 | 0.256009E+10 | 0.372314E+10 | 0.230376E+10 | 0.141938E+10 | 0.00 | 0.00 |
March | 0.444719E+10 | 0.290884E+10 | 0.328755E+10 | 0.160144E+10 | 0.168611E+10 | 0.00 | 0.00 |
April | 0.384469E+10 | 0.229423E+10 | 0.266041E+10 | 0.102826E+10 | 0.163215E+10 | 0.00 | 0.00 |
May | 0.234523E+10 | 0.209797E+10 | 0.193697E+10 | 0.234572E+09 | 0.170240E+10 | 0.00 | 0.00 |
June | 0.202039E+10 | 0.155053E+10 | 0.164445E+10 | 96449084.55 | 0.154801E+10 | 0.00 | 0.00 |
July | 0.253905E+10 | 0.139433E+10 | 0.179206E+10 | 0.191634E+09 | 0.160043E+10 | 0.00 | 0.00 |
August | 0.368069E+10 | 0.149310E+10 | 0.230166E+10 | 0.715217E+09 | 0.158644E+10 | 0.00 | 0.00 |
September | 0.484551E+10 | 0.171839E+10 | 0.305868E+10 | 0.151953E+10 | 0.153915E+10 | 0.00 | 0.00 |
October | 0.657957E+10 | 0.195136E+10 | 0.413865E+10 | 0.277942E+10 | 0.135923E+10 | 0.00 | 0.00 |
November | 0.703050E+10 | 0.271563E+10 | 0.486503E+10 | 0.344700E+10 | 0.141803E+10 | 0.00 | 0.00 |
December | 0.810054E+10 | 0.310675E+10 | 0.558430E+10 | 0.425539E+10 | 0.132891E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.580457E+11 | 0.268902E+11 | 0.402112E+11 | 0.220037E+11 | 0.182075E+11 | 0.00 | 0.00 |
Minimum of Months | 0.202039E+10 | 0.139433E+10 | 0.164445E+10 | 96449084.55 | 0.132891E+10 | 0.00 | 0.00 |
Maximum of Months | 0.810054E+10 | 0.310675E+10 | 0.558430E+10 | 0.425539E+10 | 0.170240E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.999478E+10 | 0.411882E+10 | 0.677891E+10 | 0.497672E+10 | 0.180219E+10 | 0.00 | 0.00 |
February | 0.675683E+10 | 0.345538E+10 | 0.483657E+10 | 0.299272E+10 | 0.184385E+10 | 0.00 | 0.00 |
March | 0.589271E+10 | 0.395781E+10 | 0.427071E+10 | 0.208036E+10 | 0.219036E+10 | 0.00 | 0.00 |
April | 0.510583E+10 | 0.311682E+10 | 0.345602E+10 | 0.133577E+10 | 0.212025E+10 | 0.00 | 0.00 |
May | 0.305395E+10 | 0.291770E+10 | 0.251623E+10 | 0.304722E+09 | 0.221151E+10 | 0.00 | 0.00 |
June | 0.261836E+10 | 0.216306E+10 | 0.213624E+10 | 0.125293E+09 | 0.201095E+10 | 0.00 | 0.00 |
July | 0.333524E+10 | 0.192155E+10 | 0.232799E+10 | 0.248943E+09 | 0.207905E+10 | 0.00 | 0.00 |
August | 0.489614E+10 | 0.200523E+10 | 0.298998E+10 | 0.929108E+09 | 0.206087E+10 | 0.00 | 0.00 |
September | 0.645195E+10 | 0.229378E+10 | 0.397340E+10 | 0.197396E+10 | 0.199944E+10 | 0.00 | 0.00 |
October | 0.873321E+10 | 0.258298E+10 | 0.537634E+10 | 0.361063E+10 | 0.176572E+10 | 0.00 | 0.00 |
November | 0.933822E+10 | 0.361217E+10 | 0.631995E+10 | 0.447785E+10 | 0.184211E+10 | 0.00 | 0.00 |
December | 0.107531E+11 | 0.412603E+10 | 0.725432E+10 | 0.552799E+10 | 0.172633E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.769304E+11 | 0.362713E+11 | 0.522367E+11 | 0.285840E+11 | 0.236526E+11 | 0.00 | 0.00 |
Minimum of Months | 0.261836E+10 | 0.192155E+10 | 0.213624E+10 | 0.125293E+09 | 0.172633E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107531E+11 | 0.412603E+10 | 0.725432E+10 | 0.552799E+10 | 0.221151E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.865234E+09 | 0.559070E+09 | 0.631920E+09 | 0.402891E+09 | 0.229029E+09 | 0.00 | 0.00 |
February | 0.707723E+09 | 0.457956E+09 | 0.547842E+09 | 0.294142E+09 | 0.253700E+09 | 0.00 | 0.00 |
March | 0.768390E+09 | 0.526727E+09 | 0.593520E+09 | 0.272721E+09 | 0.320799E+09 | 0.00 | 0.00 |
April | 0.959275E+09 | 0.393945E+09 | 0.670528E+09 | 0.323680E+09 | 0.346848E+09 | 0.00 | 0.00 |
May | 0.846392E+09 | 0.362189E+09 | 0.627025E+09 | 0.242928E+09 | 0.384097E+09 | 0.00 | 0.00 |
June | 0.887873E+09 | 0.249167E+09 | 0.618729E+09 | 0.258064E+09 | 0.360665E+09 | 0.00 | 0.00 |
July | 0.104641E+10 | 0.214195E+09 | 0.676483E+09 | 0.307809E+09 | 0.368674E+09 | 0.00 | 0.00 |
August | 0.108333E+10 | 0.226492E+09 | 0.678314E+09 | 0.330001E+09 | 0.348314E+09 | 0.00 | 0.00 |
September | 0.100105E+10 | 0.267274E+09 | 0.643298E+09 | 0.335913E+09 | 0.307385E+09 | 0.00 | 0.00 |
October | 0.100627E+10 | 0.315222E+09 | 0.630737E+09 | 0.381522E+09 | 0.249215E+09 | 0.00 | 0.00 |
November | 0.885589E+09 | 0.478990E+09 | 0.637811E+09 | 0.397077E+09 | 0.240734E+09 | 0.00 | 0.00 |
December | 0.914637E+09 | 0.555548E+09 | 0.661336E+09 | 0.442746E+09 | 0.218589E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109722E+11 | 0.460678E+10 | 0.761754E+10 | 0.398949E+10 | 0.362805E+10 | 0.00 | 0.00 |
Minimum of Months | 0.707723E+09 | 0.214195E+09 | 0.547842E+09 | 0.242928E+09 | 0.218589E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108333E+10 | 0.559070E+09 | 0.678314E+09 | 0.442746E+09 | 0.384097E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.388425E+09 | 0.573357E+09 | 0.320905E+09 | 0.133901E+09 | 0.187004E+09 | 0.00 | 0.00 |
February | 0.396267E+09 | 0.463354E+09 | 0.349219E+09 | 0.132386E+09 | 0.216833E+09 | 0.00 | 0.00 |
March | 0.524535E+09 | 0.527255E+09 | 0.447889E+09 | 0.160279E+09 | 0.287610E+09 | 0.00 | 0.00 |
April | 0.782036E+09 | 0.387582E+09 | 0.579223E+09 | 0.252251E+09 | 0.326972E+09 | 0.00 | 0.00 |
May | 0.801723E+09 | 0.352791E+09 | 0.609729E+09 | 0.232648E+09 | 0.377081E+09 | 0.00 | 0.00 |
June | 0.892010E+09 | 0.243363E+09 | 0.625037E+09 | 0.263322E+09 | 0.361715E+09 | 0.00 | 0.00 |
July | 0.102573E+10 | 0.210625E+09 | 0.669847E+09 | 0.304467E+09 | 0.365379E+09 | 0.00 | 0.00 |
August | 0.951200E+09 | 0.221704E+09 | 0.615807E+09 | 0.281984E+09 | 0.333823E+09 | 0.00 | 0.00 |
September | 0.754877E+09 | 0.262216E+09 | 0.509491E+09 | 0.229238E+09 | 0.280253E+09 | 0.00 | 0.00 |
October | 0.630859E+09 | 0.315038E+09 | 0.406496E+09 | 0.186368E+09 | 0.220128E+09 | 0.00 | 0.00 |
November | 0.441218E+09 | 0.487220E+09 | 0.354356E+09 | 0.155051E+09 | 0.199305E+09 | 0.00 | 0.00 |
December | 0.394854E+09 | 0.572468E+09 | 0.320798E+09 | 0.143959E+09 | 0.176839E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.798374E+10 | 0.461697E+10 | 0.580880E+10 | 0.247585E+10 | 0.333294E+10 | 0.00 | 0.00 |
Minimum of Months | 0.388425E+09 | 0.210625E+09 | 0.320798E+09 | 0.132386E+09 | 0.176839E+09 | 0.00 | 0.00 |
Maximum of Months | 0.102573E+10 | 0.573357E+09 | 0.669847E+09 | 0.304467E+09 | 0.377081E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.426815E+09 | 0.176991E+09 | 0.293061E+09 | 0.215149E+09 | 77911467.45 | 0.00 | 0.00 |
February | 0.286147E+09 | 0.145779E+09 | 0.209091E+09 | 0.129379E+09 | 79712592.74 | 0.00 | 0.00 |
March | 0.249664E+09 | 0.165457E+09 | 0.184629E+09 | 89936327.87 | 94692605.60 | 0.00 | 0.00 |
April | 0.216660E+09 | 0.128785E+09 | 0.149409E+09 | 57746850.06 | 91662135.38 | 0.00 | 0.00 |
May | 0.134177E+09 | 0.113226E+09 | 0.108781E+09 | 13173513.96 | 95607483.13 | 0.00 | 0.00 |
June | 0.118283E+09 | 79375060.74 | 92353413.13 | 5416561.15 | 86936851.98 | 0.00 | 0.00 |
July | 0.145950E+09 | 74180890.34 | 0.100643E+09 | 10762115.76 | 89881160.52 | 0.00 | 0.00 |
August | 0.210647E+09 | 80337703.60 | 0.129262E+09 | 40166453.60 | 89095338.36 | 0.00 | 0.00 |
September | 0.275965E+09 | 93865309.02 | 0.171776E+09 | 85336561.19 | 86439337.30 | 0.00 | 0.00 |
October | 0.374927E+09 | 0.106591E+09 | 0.232427E+09 | 0.156092E+09 | 76334792.12 | 0.00 | 0.00 |
November | 0.398129E+09 | 0.154706E+09 | 0.273220E+09 | 0.193583E+09 | 79637126.46 | 0.00 | 0.00 |
December | 0.459444E+09 | 0.177618E+09 | 0.313614E+09 | 0.238982E+09 | 74631825.39 | 0.00 | 0.00 |
Annual Sum or Average | 0.329681E+10 | 0.149691E+10 | 0.225827E+10 | 0.123572E+10 | 0.102254E+10 | 0.00 | 0.00 |
Minimum of Months | 0.118283E+09 | 74180890.34 | 92353413.13 | 5416561.15 | 74631825.39 | 0.00 | 0.00 |
Maximum of Months | 0.459444E+09 | 0.177618E+09 | 0.313614E+09 | 0.238982E+09 | 95607483.13 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 34551159.78 | 0.164058E+09 | 44312955.30 | 0.00 | 44312955.30 | 0.00 | 0.00 |
February | 35479383.49 | 0.133345E+09 | 50241522.13 | 0.00 | 50241522.13 | 0.00 | 0.00 |
March | 56314143.45 | 0.152097E+09 | 68169765.21 | 624.22 | 68169140.99 | 0.00 | 0.00 |
April | 79991180.14 | 0.105868E+09 | 76404816.42 | 614812.68 | 75790003.74 | 0.00 | 0.00 |
May | 0.104063E+09 | 94355141.15 | 94978755.02 | 4953021.70 | 90025733.32 | 0.00 | 0.00 |
June | 0.129083E+09 | 63698431.68 | 97431324.50 | 9625266.49 | 87806058.00 | 0.00 | 0.00 |
July | 0.142427E+09 | 53866852.02 | 95367114.15 | 8092321.46 | 87274792.68 | 0.00 | 0.00 |
August | 0.117261E+09 | 56321320.55 | 79292341.88 | 1761686.91 | 77530654.97 | 0.00 | 0.00 |
September | 87573164.77 | 69977794.95 | 64772993.27 | 12882.05 | 64760111.22 | 0.00 | 0.00 |
October | 79735594.50 | 84938642.90 | 53086943.81 | 0.00 | 53086943.81 | 0.00 | 0.00 |
November | 39468909.35 | 0.138134E+09 | 46515858.69 | 0.00 | 46515858.69 | 0.00 | 0.00 |
December | 31986376.18 | 0.163551E+09 | 41251595.16 | 0.00 | 41251595.16 | 0.00 | 0.00 |
Annual Sum or Average | 0.937933E+09 | 0.128021E+10 | 0.811826E+09 | 25060615.52 | 0.786765E+09 | 0.00 | 0.00 |
Minimum of Months | 31986376.18 | 53866852.02 | 41251595.16 | 0.00 | 41251595.16 | 0.00 | 0.00 |
Maximum of Months | 0.142427E+09 | 0.164058E+09 | 97431324.50 | 9625266.49 | 90025733.32 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.876862E+09 | 0.547206E+09 | 0.645041E+09 | 0.417872E+09 | 0.227169E+09 | 0.00 | 0.00 |
February | 0.664349E+09 | 0.445847E+09 | 0.526993E+09 | 0.283282E+09 | 0.243711E+09 | 0.00 | 0.00 |
March | 0.746457E+09 | 0.508225E+09 | 0.589680E+09 | 0.272720E+09 | 0.316960E+09 | 0.00 | 0.00 |
April | 0.882687E+09 | 0.379408E+09 | 0.629463E+09 | 0.294307E+09 | 0.335155E+09 | 0.00 | 0.00 |
May | 0.744189E+09 | 0.350296E+09 | 0.566849E+09 | 0.196017E+09 | 0.370832E+09 | 0.00 | 0.00 |
June | 0.749367E+09 | 0.246466E+09 | 0.530300E+09 | 0.186863E+09 | 0.343438E+09 | 0.00 | 0.00 |
July | 0.944841E+09 | 0.213966E+09 | 0.611254E+09 | 0.254616E+09 | 0.356638E+09 | 0.00 | 0.00 |
August | 0.102437E+10 | 0.221228E+09 | 0.641384E+09 | 0.305202E+09 | 0.336182E+09 | 0.00 | 0.00 |
September | 0.857014E+09 | 0.261586E+09 | 0.553748E+09 | 0.262611E+09 | 0.291136E+09 | 0.00 | 0.00 |
October | 0.947128E+09 | 0.304774E+09 | 0.599302E+09 | 0.353603E+09 | 0.245699E+09 | 0.00 | 0.00 |
November | 0.837010E+09 | 0.468367E+09 | 0.613301E+09 | 0.379582E+09 | 0.233719E+09 | 0.00 | 0.00 |
December | 0.906226E+09 | 0.545240E+09 | 0.662004E+09 | 0.449220E+09 | 0.212784E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101805E+11 | 0.449261E+10 | 0.716932E+10 | 0.365590E+10 | 0.351342E+10 | 0.00 | 0.00 |
Minimum of Months | 0.664349E+09 | 0.213966E+09 | 0.526993E+09 | 0.186863E+09 | 0.212784E+09 | 0.00 | 0.00 |
Maximum of Months | 0.102437E+10 | 0.547206E+09 | 0.662004E+09 | 0.449220E+09 | 0.370832E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.382167E+09 | 0.540296E+09 | 0.334026E+09 | 0.148882E+09 | 0.185144E+09 | 0.00 | 0.00 |
February | 0.345810E+09 | 0.442076E+09 | 0.328370E+09 | 0.121526E+09 | 0.206844E+09 | 0.00 | 0.00 |
March | 0.497228E+09 | 0.502978E+09 | 0.444049E+09 | 0.160278E+09 | 0.283771E+09 | 0.00 | 0.00 |
April | 0.703559E+09 | 0.371685E+09 | 0.538158E+09 | 0.222878E+09 | 0.315280E+09 | 0.00 | 0.00 |
May | 0.701293E+09 | 0.342647E+09 | 0.549554E+09 | 0.185737E+09 | 0.363816E+09 | 0.00 | 0.00 |
June | 0.750619E+09 | 0.237939E+09 | 0.536608E+09 | 0.192121E+09 | 0.344488E+09 | 0.00 | 0.00 |
July | 0.919949E+09 | 0.206556E+09 | 0.604618E+09 | 0.251275E+09 | 0.353343E+09 | 0.00 | 0.00 |
August | 0.890132E+09 | 0.215832E+09 | 0.578877E+09 | 0.257186E+09 | 0.321691E+09 | 0.00 | 0.00 |
September | 0.610041E+09 | 0.255677E+09 | 0.419941E+09 | 0.155935E+09 | 0.264005E+09 | 0.00 | 0.00 |
October | 0.565753E+09 | 0.299152E+09 | 0.375061E+09 | 0.158449E+09 | 0.216611E+09 | 0.00 | 0.00 |
November | 0.383803E+09 | 0.462979E+09 | 0.329845E+09 | 0.137555E+09 | 0.192290E+09 | 0.00 | 0.00 |
December | 0.366895E+09 | 0.538650E+09 | 0.321466E+09 | 0.150433E+09 | 0.171033E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.711725E+10 | 0.441647E+10 | 0.536057E+10 | 0.214226E+10 | 0.321832E+10 | 0.00 | 0.00 |
Minimum of Months | 0.345810E+09 | 0.206556E+09 | 0.321466E+09 | 0.121526E+09 | 0.171033E+09 | 0.00 | 0.00 |
Maximum of Months | 0.919949E+09 | 0.540296E+09 | 0.604618E+09 | 0.257186E+09 | 0.363816E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.985565E+09 | 0.723942E+09 | 0.730978E+09 | 0.466169E+09 | 0.264809E+09 | 0.00 | 0.00 |
February | 0.690745E+09 | 0.608190E+09 | 0.561883E+09 | 0.280328E+09 | 0.281555E+09 | 0.00 | 0.00 |
March | 0.666147E+09 | 0.696396E+09 | 0.547718E+09 | 0.194868E+09 | 0.352850E+09 | 0.00 | 0.00 |
April | 0.644417E+09 | 0.525390E+09 | 0.489246E+09 | 0.126453E+09 | 0.362793E+09 | 0.00 | 0.00 |
May | 0.496950E+09 | 0.478171E+09 | 0.441454E+09 | 39273247.18 | 0.402181E+09 | 0.00 | 0.00 |
June | 0.506883E+09 | 0.339145E+09 | 0.411173E+09 | 32587736.49 | 0.378585E+09 | 0.00 | 0.00 |
July | 0.598250E+09 | 0.305632E+09 | 0.424663E+09 | 40849193.83 | 0.383814E+09 | 0.00 | 0.00 |
August | 0.689608E+09 | 0.331156E+09 | 0.451848E+09 | 90845939.63 | 0.361002E+09 | 0.00 | 0.00 |
September | 0.778315E+09 | 0.386909E+09 | 0.512511E+09 | 0.184929E+09 | 0.327582E+09 | 0.00 | 0.00 |
October | 0.965545E+09 | 0.452550E+09 | 0.618608E+09 | 0.338207E+09 | 0.280400E+09 | 0.00 | 0.00 |
November | 0.933457E+09 | 0.639262E+09 | 0.692760E+09 | 0.419440E+09 | 0.273320E+09 | 0.00 | 0.00 |
December | 0.104210E+10 | 0.730755E+09 | 0.768878E+09 | 0.517807E+09 | 0.251071E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.899799E+10 | 0.621750E+10 | 0.665172E+10 | 0.273176E+10 | 0.391996E+10 | 0.00 | 0.00 |
Minimum of Months | 0.496950E+09 | 0.305632E+09 | 0.411173E+09 | 32587736.49 | 0.251071E+09 | 0.00 | 0.00 |
Maximum of Months | 0.104210E+10 | 0.730755E+09 | 0.768878E+09 | 0.517807E+09 | 0.402181E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.861655E+09 | 0.549414E+09 | 0.631920E+09 | 0.402891E+09 | 0.229029E+09 | 0.00 | 0.00 |
February | 0.702727E+09 | 0.448995E+09 | 0.547842E+09 | 0.294142E+09 | 0.253700E+09 | 0.00 | 0.00 |
March | 0.760656E+09 | 0.519573E+09 | 0.593520E+09 | 0.272721E+09 | 0.320799E+09 | 0.00 | 0.00 |
April | 0.946001E+09 | 0.388957E+09 | 0.670528E+09 | 0.323680E+09 | 0.346848E+09 | 0.00 | 0.00 |
May | 0.833542E+09 | 0.357682E+09 | 0.627025E+09 | 0.242928E+09 | 0.384097E+09 | 0.00 | 0.00 |
June | 0.874066E+09 | 0.245577E+09 | 0.618729E+09 | 0.258064E+09 | 0.360665E+09 | 0.00 | 0.00 |
July | 0.103239E+10 | 0.210601E+09 | 0.676483E+09 | 0.307809E+09 | 0.368674E+09 | 0.00 | 0.00 |
August | 0.106990E+10 | 0.222504E+09 | 0.678314E+09 | 0.330001E+09 | 0.348314E+09 | 0.00 | 0.00 |
September | 0.989604E+09 | 0.261987E+09 | 0.643298E+09 | 0.335913E+09 | 0.307385E+09 | 0.00 | 0.00 |
October | 0.999647E+09 | 0.307475E+09 | 0.630737E+09 | 0.381522E+09 | 0.249215E+09 | 0.00 | 0.00 |
November | 0.880689E+09 | 0.469453E+09 | 0.637811E+09 | 0.397077E+09 | 0.240734E+09 | 0.00 | 0.00 |
December | 0.911981E+09 | 0.544289E+09 | 0.661336E+09 | 0.442746E+09 | 0.218589E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108629E+11 | 0.452651E+10 | 0.761754E+10 | 0.398949E+10 | 0.362805E+10 | 0.00 | 0.00 |
Minimum of Months | 0.702727E+09 | 0.210601E+09 | 0.547842E+09 | 0.242928E+09 | 0.218589E+09 | 0.00 | 0.00 |
Maximum of Months | 0.106990E+10 | 0.549414E+09 | 0.678314E+09 | 0.442746E+09 | 0.384097E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.390173E+09 | 0.559040E+09 | 0.320905E+09 | 0.133901E+09 | 0.187004E+09 | 0.00 | 0.00 |
February | 0.396249E+09 | 0.451565E+09 | 0.349219E+09 | 0.132386E+09 | 0.216833E+09 | 0.00 | 0.00 |
March | 0.520318E+09 | 0.518338E+09 | 0.447889E+09 | 0.160279E+09 | 0.287610E+09 | 0.00 | 0.00 |
April | 0.771296E+09 | 0.381875E+09 | 0.579223E+09 | 0.252251E+09 | 0.326972E+09 | 0.00 | 0.00 |
May | 0.789823E+09 | 0.348185E+09 | 0.609729E+09 | 0.232648E+09 | 0.377081E+09 | 0.00 | 0.00 |
June | 0.878051E+09 | 0.239979E+09 | 0.625037E+09 | 0.263322E+09 | 0.361715E+09 | 0.00 | 0.00 |
July | 0.101193E+10 | 0.207189E+09 | 0.669847E+09 | 0.304467E+09 | 0.365379E+09 | 0.00 | 0.00 |
August | 0.939173E+09 | 0.217559E+09 | 0.615807E+09 | 0.281984E+09 | 0.333823E+09 | 0.00 | 0.00 |
September | 0.746345E+09 | 0.256202E+09 | 0.509491E+09 | 0.229238E+09 | 0.280253E+09 | 0.00 | 0.00 |
October | 0.628811E+09 | 0.305244E+09 | 0.406496E+09 | 0.186368E+09 | 0.220128E+09 | 0.00 | 0.00 |
November | 0.442412E+09 | 0.473574E+09 | 0.354356E+09 | 0.155051E+09 | 0.199305E+09 | 0.00 | 0.00 |
December | 0.398533E+09 | 0.555805E+09 | 0.320798E+09 | 0.143959E+09 | 0.176839E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.791311E+10 | 0.451455E+10 | 0.580880E+10 | 0.247585E+10 | 0.333294E+10 | 0.00 | 0.00 |
Minimum of Months | 0.390173E+09 | 0.207189E+09 | 0.320798E+09 | 0.132386E+09 | 0.176839E+09 | 0.00 | 0.00 |
Maximum of Months | 0.101193E+10 | 0.559040E+09 | 0.669847E+09 | 0.304467E+09 | 0.377081E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.785049E+09 | 0.288115E+09 | 0.537359E+09 | 0.394500E+09 | 0.142859E+09 | 0.00 | 0.00 |
February | 0.527555E+09 | 0.235349E+09 | 0.383392E+09 | 0.237230E+09 | 0.146162E+09 | 0.00 | 0.00 |
March | 0.461381E+09 | 0.273563E+09 | 0.338537E+09 | 0.164908E+09 | 0.173629E+09 | 0.00 | 0.00 |
April | 0.401984E+09 | 0.203945E+09 | 0.273958E+09 | 0.105885E+09 | 0.168073E+09 | 0.00 | 0.00 |
May | 0.248840E+09 | 0.186757E+09 | 0.199462E+09 | 24155080.95 | 0.175307E+09 | 0.00 | 0.00 |
June | 0.220768E+09 | 0.126946E+09 | 0.169340E+09 | 9931858.23 | 0.159408E+09 | 0.00 | 0.00 |
July | 0.279191E+09 | 0.106775E+09 | 0.184540E+09 | 19733518.19 | 0.164807E+09 | 0.00 | 0.00 |
August | 0.396779E+09 | 0.112791E+09 | 0.237016E+09 | 73649592.75 | 0.163366E+09 | 0.00 | 0.00 |
September | 0.512642E+09 | 0.135868E+09 | 0.314970E+09 | 0.156474E+09 | 0.158496E+09 | 0.00 | 0.00 |
October | 0.693542E+09 | 0.158040E+09 | 0.426179E+09 | 0.286211E+09 | 0.139968E+09 | 0.00 | 0.00 |
November | 0.733428E+09 | 0.245506E+09 | 0.500979E+09 | 0.354955E+09 | 0.146023E+09 | 0.00 | 0.00 |
December | 0.845019E+09 | 0.286005E+09 | 0.575045E+09 | 0.438199E+09 | 0.136846E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.610618E+10 | 0.235966E+10 | 0.414078E+10 | 0.226583E+10 | 0.187494E+10 | 0.00 | 0.00 |
Minimum of Months | 0.220768E+09 | 0.106775E+09 | 0.169340E+09 | 9931858.23 | 0.136846E+09 | 0.00 | 0.00 |
Maximum of Months | 0.845019E+09 | 0.288115E+09 | 0.575045E+09 | 0.438199E+09 | 0.175307E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.182644E+09 | 0.181250E+10 | 0.387672E+09 | 0.00 | 0.387672E+09 | 0.00 | 0.00 |
February | 0.188423E+09 | 0.151778E+10 | 0.439538E+09 | 0.00 | 0.439538E+09 | 0.00 | 0.00 |
March | 0.334129E+09 | 0.169546E+10 | 0.596384E+09 | 5460.98 | 0.596378E+09 | 0.00 | 0.00 |
April | 0.497526E+09 | 0.122357E+10 | 0.668428E+09 | 5378694.26 | 0.663050E+09 | 0.00 | 0.00 |
May | 0.656108E+09 | 0.109047E+10 | 0.830922E+09 | 43331554.67 | 0.787591E+09 | 0.00 | 0.00 |
June | 0.864624E+09 | 0.785539E+09 | 0.852379E+09 | 84206730.00 | 0.768172E+09 | 0.00 | 0.00 |
July | 0.975367E+09 | 0.697611E+09 | 0.834320E+09 | 70795746.72 | 0.763524E+09 | 0.00 | 0.00 |
August | 0.778304E+09 | 0.753555E+09 | 0.693690E+09 | 15412133.73 | 0.678278E+09 | 0.00 | 0.00 |
September | 0.568867E+09 | 0.898964E+09 | 0.566667E+09 | 112698.72 | 0.566554E+09 | 0.00 | 0.00 |
October | 0.520426E+09 | 0.106983E+10 | 0.464432E+09 | 0.00 | 0.464432E+09 | 0.00 | 0.00 |
November | 0.213899E+09 | 0.156706E+10 | 0.406944E+09 | 0.00 | 0.406944E+09 | 0.00 | 0.00 |
December | 0.161409E+09 | 0.181554E+10 | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.594173E+10 | 0.149279E+11 | 0.710227E+10 | 0.219243E+09 | 0.688302E+10 | 0.00 | 0.00 |
Minimum of Months | 0.161409E+09 | 0.697611E+09 | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.00 | 0.00 |
Maximum of Months | 0.975367E+09 | 0.181554E+10 | 0.852379E+09 | 84206730.00 | 0.787591E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.163275E+09 | 0.187114E+10 | 0.387672E+09 | 0.00 | 0.387672E+09 | 0.00 | 0.00 |
February | 0.168285E+09 | 0.157001E+10 | 0.439538E+09 | 0.00 | 0.439538E+09 | 0.00 | 0.00 |
March | 0.305947E+09 | 0.174941E+10 | 0.596384E+09 | 5460.98 | 0.596378E+09 | 0.00 | 0.00 |
April | 0.466747E+09 | 0.125914E+10 | 0.668428E+09 | 5378694.26 | 0.663050E+09 | 0.00 | 0.00 |
May | 0.618911E+09 | 0.112035E+10 | 0.830922E+09 | 43331554.67 | 0.787591E+09 | 0.00 | 0.00 |
June | 0.831315E+09 | 0.808932E+09 | 0.852379E+09 | 84206730.00 | 0.768172E+09 | 0.00 | 0.00 |
July | 0.944949E+09 | 0.718414E+09 | 0.834320E+09 | 70795746.72 | 0.763524E+09 | 0.00 | 0.00 |
August | 0.750805E+09 | 0.777182E+09 | 0.693690E+09 | 15412133.73 | 0.678278E+09 | 0.00 | 0.00 |
September | 0.544091E+09 | 0.928394E+09 | 0.566667E+09 | 112698.72 | 0.566554E+09 | 0.00 | 0.00 |
October | 0.497714E+09 | 0.110341E+10 | 0.464432E+09 | 0.00 | 0.464432E+09 | 0.00 | 0.00 |
November | 0.193481E+09 | 0.161584E+10 | 0.406944E+09 | 0.00 | 0.406944E+09 | 0.00 | 0.00 |
December | 0.143822E+09 | 0.187287E+10 | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.562934E+10 | 0.153951E+11 | 0.710227E+10 | 0.219243E+09 | 0.688302E+10 | 0.00 | 0.00 |
Minimum of Months | 0.143822E+09 | 0.718414E+09 | 0.360890E+09 | 0.00 | 0.360890E+09 | 0.00 | 0.00 |
Maximum of Months | 0.944949E+09 | 0.187287E+10 | 0.852379E+09 | 84206730.00 | 0.787591E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.129801E+10 | 0.124259E+10 | 0.979027E+09 | 0.566733E+09 | 0.412294E+09 | 0.00 | 0.00 |
February | 0.102194E+10 | 0.108568E+10 | 0.855325E+09 | 0.404791E+09 | 0.450534E+09 | 0.00 | 0.00 |
March | 0.126813E+10 | 0.122304E+10 | 0.103368E+10 | 0.432976E+09 | 0.600702E+09 | 0.00 | 0.00 |
April | 0.166202E+10 | 0.924534E+09 | 0.116756E+10 | 0.517154E+09 | 0.650404E+09 | 0.00 | 0.00 |
May | 0.151094E+10 | 0.878283E+09 | 0.111634E+10 | 0.381729E+09 | 0.734613E+09 | 0.00 | 0.00 |
June | 0.159221E+10 | 0.651428E+09 | 0.106685E+10 | 0.378958E+09 | 0.687892E+09 | 0.00 | 0.00 |
July | 0.199852E+10 | 0.581813E+09 | 0.121580E+10 | 0.505857E+09 | 0.709947E+09 | 0.00 | 0.00 |
August | 0.204670E+10 | 0.605395E+09 | 0.122019E+10 | 0.562352E+09 | 0.657842E+09 | 0.00 | 0.00 |
September | 0.156521E+10 | 0.665543E+09 | 0.973640E+09 | 0.418524E+09 | 0.555116E+09 | 0.00 | 0.00 |
October | 0.160608E+10 | 0.758894E+09 | 0.974319E+09 | 0.512030E+09 | 0.462289E+09 | 0.00 | 0.00 |
November | 0.125837E+10 | 0.108462E+10 | 0.943108E+09 | 0.517117E+09 | 0.425991E+09 | 0.00 | 0.00 |
December | 0.130871E+10 | 0.124210E+10 | 0.983432E+09 | 0.599632E+09 | 0.383800E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.181368E+11 | 0.109439E+11 | 0.125293E+11 | 0.579785E+10 | 0.673142E+10 | 0.00 | 0.00 |
Minimum of Months | 0.102194E+10 | 0.581813E+09 | 0.855325E+09 | 0.378958E+09 | 0.383800E+09 | 0.00 | 0.00 |
Maximum of Months | 0.204670E+10 | 0.124259E+10 | 0.122019E+10 | 0.599632E+09 | 0.734613E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.206195E+10 | 0.127044E+10 | 0.150077E+10 | 0.100422E+10 | 0.496551E+09 | 0.00 | 0.00 |
February | 0.141713E+10 | 0.106438E+10 | 0.112662E+10 | 0.603882E+09 | 0.522737E+09 | 0.00 | 0.00 |
March | 0.131190E+10 | 0.123625E+10 | 0.106621E+10 | 0.419784E+09 | 0.646422E+09 | 0.00 | 0.00 |
April | 0.121428E+10 | 0.947796E+09 | 0.926512E+09 | 0.271380E+09 | 0.655132E+09 | 0.00 | 0.00 |
May | 0.861184E+09 | 0.867011E+09 | 0.792583E+09 | 76342183.92 | 0.716240E+09 | 0.00 | 0.00 |
June | 0.835196E+09 | 0.627071E+09 | 0.723261E+09 | 54148304.57 | 0.669113E+09 | 0.00 | 0.00 |
July | 0.100750E+10 | 0.568835E+09 | 0.755764E+09 | 74501639.64 | 0.681262E+09 | 0.00 | 0.00 |
August | 0.124964E+10 | 0.615059E+09 | 0.841134E+09 | 0.192762E+09 | 0.648372E+09 | 0.00 | 0.00 |
September | 0.149861E+10 | 0.699750E+09 | 0.996027E+09 | 0.398351E+09 | 0.597676E+09 | 0.00 | 0.00 |
October | 0.193060E+10 | 0.803220E+09 | 0.124407E+10 | 0.728566E+09 | 0.515505E+09 | 0.00 | 0.00 |
November | 0.194243E+10 | 0.111194E+10 | 0.141477E+10 | 0.903557E+09 | 0.511212E+09 | 0.00 | 0.00 |
December | 0.219976E+10 | 0.126637E+10 | 0.158752E+10 | 0.111546E+10 | 0.472062E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.175302E+11 | 0.110781E+11 | 0.129752E+11 | 0.584296E+10 | 0.713228E+10 | 0.00 | 0.00 |
Minimum of Months | 0.835196E+09 | 0.568835E+09 | 0.723261E+09 | 54148304.57 | 0.472062E+09 | 0.00 | 0.00 |
Maximum of Months | 0.219976E+10 | 0.127044E+10 | 0.158752E+10 | 0.111546E+10 | 0.716240E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770487E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162087104.9 | 81.21 | 0.00 | 0.00 |
February | 0.696227E+10 | -0.681598E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146289432.8 | 81.21 | 0.00 | 0.00 |
March | 0.770350E+10 | -0.754147E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162029748.9 | 81.21 | 0.00 | 0.00 |
April | 0.746523E+10 | -0.730860E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156633620.0 | 81.21 | 0.00 | 0.00 |
May | 0.770464E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161835576.9 | 81.21 | 0.00 | 0.00 |
June | 0.745705E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156512351.7 | 81.21 | 0.00 | 0.00 |
July | 0.771250E+10 | -0.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161657535.7 | 81.21 | 0.00 | 0.00 |
August | 0.770445E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161650769.2 | 81.21 | 0.00 | 0.00 |
September | 0.746642E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156496655.4 | 81.21 | 0.00 | 0.00 |
October | 0.770318E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161744699.0 | 81.21 | 0.00 | 0.00 |
November | 0.744914E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156714032.2 | 81.21 | 0.00 | 0.00 |
December | 0.771287E+10 | -0.755087E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161996866.7 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907461E+11 | -0.888405E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190565E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696227E+10 | -0.755087E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162087104.9 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771287E+10 | -0.681598E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146289432.8 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.109790E+12 | -0.108049E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174097E+10 | 81.24 | 0.00 | 0.00 |
February | 0.992511E+11 | -0.976640E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.158713E+10 | 81.25 | 0.00 | 0.00 |
March | 0.109120E+12 | -0.107357E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176382E+10 | 81.25 | 0.00 | 0.00 |
April | 0.104193E+12 | -0.102483E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170993E+10 | 81.25 | 0.00 | 0.00 |
May | 0.105914E+12 | -0.104147E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176680E+10 | 81.25 | 0.00 | 0.00 |
June | 0.100979E+12 | -0.992661E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.171322E+10 | 81.25 | 0.00 | 0.00 |
July | 0.103369E+12 | -0.101609E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176011E+10 | 81.25 | 0.00 | 0.00 |
August | 0.103266E+12 | -0.101509E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175701E+10 | 81.25 | 0.00 | 0.00 |
September | 0.100695E+12 | -0.990054E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169006E+10 | 81.25 | 0.00 | 0.00 |
October | 0.105521E+12 | -0.103781E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173921E+10 | 81.25 | 0.00 | 0.00 |
November | 0.103810E+12 | -0.102129E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.168055E+10 | 81.25 | 0.00 | 0.00 |
December | 0.108831E+12 | -0.107092E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173972E+10 | 81.25 | 0.00 | 0.00 |
Annual Sum or Average | 0.125474E+13 | -0.123409E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206485E+11 | 81.25 | 0.00 | 0.00 |
Minimum of Months | 0.992511E+11 | -0.108049E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.176680E+10 | 81.24 | 0.00 | 0.00 |
Maximum of Months | 0.109790E+12 | -0.976640E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158713E+10 | 81.25 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.621955E+11 | -0.607124E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148315E+10 | 58.98 | 0.00 | 0.00 |
February | 0.562692E+11 | -0.549097E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.135955E+10 | 58.98 | 0.00 | 0.00 |
March | 0.616857E+11 | -0.601713E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151442E+10 | 58.98 | 0.00 | 0.00 |
April | 0.584509E+11 | -0.569812E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146970E+10 | 58.98 | 0.00 | 0.00 |
May | 0.588980E+11 | -0.573794E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151860E+10 | 58.98 | 0.00 | 0.00 |
June | 0.557117E+11 | -0.542374E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.147425E+10 | 58.98 | 0.00 | 0.00 |
July | 0.566677E+11 | -0.551583E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150942E+10 | 58.98 | 0.00 | 0.00 |
August | 0.566341E+11 | -0.551290E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150508E+10 | 58.98 | 0.00 | 0.00 |
September | 0.554291E+11 | -0.539867E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.144241E+10 | 58.98 | 0.00 | 0.00 |
October | 0.585120E+11 | -0.570314E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148062E+10 | 58.98 | 0.00 | 0.00 |
November | 0.580835E+11 | -0.566542E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142929E+10 | 58.98 | 0.00 | 0.00 |
December | 0.613663E+11 | -0.598851E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148121E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.699904E+12 | -0.682236E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.176677E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.554291E+11 | -0.607124E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.151860E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.621955E+11 | -0.539867E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.135955E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.93 | 0.93 | 01-JAN-07:19 | 6411.39 | 37.26 | 284.83 | 280.00 | 922.74 | 26.85 | 188.50 | 262.67 |
February | 279.67 | 0.93 | 0.93 | 01-FEB-07:19 | 4458.45 | 31.97 | 218.17 | 274.67 | 609.14 | 23.53 | 166.67 | 242.83 |
March | 338.17 | 0.93 | 0.93 | 01-MAR-06:49 | 1168.52 | 19.66 | 14.00 | 320.33 | 435.63 | 20.93 | 153.50 | 258.00 |
April | 358.33 | 0.93 | 0.93 | 01-APR-06:30 | 803.80 | 19.17 | 0.00 | 332.33 | 339.22 | 20.93 | 142.83 | 259.50 |
May | 393.83 | 0.94 | 0.93 | 01-MAY-06:10 | 730.15 | 18.66 | 0.00 | 363.33 | 297.49 | 20.40 | 116.67 | 254.50 |
June | 381.00 | 0.94 | 0.93 | 01-JUN-06:10 | 631.55 | 18.47 | 0.00 | 354.33 | 265.96 | 20.23 | 65.50 | 229.17 |
July | 408.67 | 0.94 | 0.93 | 01-JUL-05:00 | 622.22 | 18.59 | 0.00 | 363.67 | 271.55 | 20.36 | 95.83 | 243.00 |
August | 390.67 | 0.94 | 0.93 | 01-AUG-06:49 | 676.69 | 18.85 | 0.00 | 353.33 | 294.84 | 20.61 | 140.67 | 263.83 |
September | 328.83 | 0.93 | 0.93 | 01-SEP-06:40 | 908.83 | 19.16 | 0.00 | 308.00 | 378.48 | 20.94 | 142.83 | 252.67 |
October | 296.17 | 0.93 | 0.93 | 01-OCT-09:39 | 3075.66 | 27.00 | 136.33 | 304.17 | 448.06 | 21.45 | 101.83 | 248.00 |
November | 300.00 | 0.93 | 0.93 | 01-NOV-06:40 | 6241.58 | 37.10 | 294.67 | 280.17 | 808.97 | 26.43 | 201.33 | 266.83 |
December | 297.00 | 0.93 | 0.93 | 01-DEC-07:10 | 6274.56 | 37.68 | 289.17 | 280.67 | 1131.34 | 28.40 | 185.67 | 265.33 |
Annual Sum or Average | 4065.67 | 0.93 | 2411.25 | 24.44 | 1237.17 | 3815.00 | 489.56 | 22.32 | 1701.83 | 3046.33 | ||
Minimum of Months | 279.67 | 0.93 | 0.93 | 622.22 | 18.47 | 0.00 | 274.67 | 265.96 | 20.23 | 65.50 | 229.17 | |
Maximum of Months | 408.67 | 0.94 | 0.93 | 6411.39 | 37.68 | 294.67 | 363.67 | 1131.34 | 28.40 | 201.33 | 266.83 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.62 | 0.61 | 01-JAN-07:19 | 6782.76 | 37.34 | 285.00 | 284.67 | 1295.92 | 26.60 | 174.33 | 272.50 |
February | 279.67 | 0.62 | 0.61 | 01-FEB-07:10 | 4753.37 | 32.08 | 218.50 | 281.50 | 903.67 | 23.62 | 167.33 | 262.00 |
March | 338.17 | 0.63 | 0.61 | 01-MAR-06:49 | 1396.04 | 20.17 | 29.67 | 328.67 | 662.32 | 21.27 | 185.33 | 298.33 |
April | 358.33 | 0.63 | 0.61 | 01-APR-06:19 | 987.44 | 19.80 | 14.67 | 345.50 | 522.42 | 21.35 | 195.83 | 313.00 |
May | 393.83 | 0.63 | 0.61 | 01-MAY-05:00 | 860.02 | 19.52 | 0.00 | 378.50 | 426.94 | 21.03 | 208.50 | 339.17 |
June | 381.00 | 0.63 | 0.61 | 01-JUN-05:49 | 748.47 | 19.36 | 0.00 | 367.83 | 382.50 | 20.89 | 196.83 | 329.50 |
July | 408.67 | 0.63 | 0.61 | 01-JUL-05:40 | 745.77 | 19.44 | 0.00 | 377.17 | 394.74 | 20.98 | 246.67 | 344.50 |
August | 390.67 | 0.63 | 0.61 | 01-AUG-06:40 | 830.15 | 19.56 | 0.17 | 367.17 | 447.92 | 21.11 | 208.33 | 333.83 |
September | 328.83 | 0.63 | 0.61 | 01-SEP-06:19 | 1128.27 | 19.66 | 18.17 | 321.33 | 597.42 | 21.26 | 157.83 | 289.33 |
October | 296.17 | 0.62 | 0.61 | 01-OCT-09:39 | 3376.77 | 27.08 | 137.00 | 315.83 | 747.20 | 21.45 | 102.67 | 281.00 |
November | 300.00 | 0.63 | 0.61 | 01-NOV-06:40 | 6591.11 | 37.15 | 294.83 | 285.83 | 1155.94 | 26.24 | 191.83 | 275.17 |
December | 297.00 | 0.63 | 0.61 | 01-DEC-06:00 | 6661.12 | 37.76 | 289.17 | 286.50 | 1517.25 | 28.09 | 172.00 | 275.67 |
Annual Sum or Average | 4065.67 | 0.63 | 2637.86 | 24.92 | 1287.17 | 3940.50 | 715.59 | 22.60 | 2207.50 | 3614.00 | ||
Minimum of Months | 279.67 | 0.62 | 0.61 | 745.77 | 19.36 | 0.00 | 281.50 | 382.50 | 20.89 | 102.67 | 262.00 | |
Maximum of Months | 408.67 | 0.63 | 0.61 | 6782.76 | 37.76 | 294.83 | 378.50 | 1517.25 | 28.09 | 246.67 | 344.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.82 | 0.80 | 01-JAN-08:30 | 301.36 | 14.31 | 0.00 | 238.83 | 156.01 | 17.88 | 0.00 | 33.67 |
February | 279.67 | 0.82 | 0.80 | 01-FEB-08:09 | 376.92 | 15.19 | 0.00 | 255.67 | 180.84 | 18.52 | 0.00 | 90.33 |
March | 338.17 | 0.82 | 0.80 | 01-MAR-07:30 | 451.38 | 15.76 | 0.00 | 313.17 | 207.38 | 18.97 | 0.00 | 177.17 |
April | 358.33 | 0.81 | 0.80 | 01-APR-06:30 | 475.61 | 16.70 | 0.00 | 343.00 | 232.82 | 19.97 | 14.00 | 269.17 |
May | 393.83 | 0.81 | 0.80 | 01-MAY-05:00 | 639.55 | 17.65 | 12.50 | 386.67 | 287.88 | 20.86 | 61.17 | 345.50 |
June | 381.00 | 0.81 | 0.80 | 01-JUN-05:49 | 677.31 | 19.68 | 58.83 | 380.83 | 313.34 | 22.08 | 109.67 | 340.17 |
July | 408.67 | 0.81 | 0.80 | 01-JUL-05:19 | 615.82 | 18.94 | 44.67 | 390.00 | 271.44 | 20.54 | 86.50 | 357.83 |
August | 390.67 | 0.81 | 0.80 | 01-AUG-06:40 | 487.91 | 16.78 | 0.00 | 370.33 | 234.53 | 20.07 | 34.00 | 297.17 |
September | 328.83 | 0.81 | 0.80 | 01-SEP-06:30 | 419.01 | 16.05 | 0.00 | 310.83 | 208.00 | 19.34 | 0.00 | 183.50 |
October | 296.17 | 0.83 | 0.80 | 01-OCT-09:39 | 312.26 | 14.67 | 0.00 | 253.17 | 158.55 | 18.12 | 0.00 | 56.50 |
November | 300.00 | 0.83 | 0.80 | 01-NOV-07:10 | 309.11 | 14.12 | 0.00 | 243.67 | 157.57 | 17.57 | 0.00 | 51.67 |
December | 297.00 | 0.83 | 0.80 | 01-DEC-07:40 | 271.81 | 13.78 | 0.00 | 229.83 | 144.72 | 17.41 | 0.00 | 19.33 |
Annual Sum or Average | 4065.67 | 0.82 | 460.64 | 16.35 | 116.00 | 3716.00 | 219.11 | 19.44 | 305.33 | 2222.00 | ||
Minimum of Months | 279.67 | 0.81 | 0.80 | 271.81 | 13.78 | 0.00 | 229.83 | 144.72 | 17.41 | 0.00 | 19.33 | |
Maximum of Months | 408.67 | 0.83 | 0.80 | 677.31 | 19.68 | 58.83 | 390.00 | 313.34 | 22.08 | 109.67 | 357.83 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.82 | 0.80 | 01-JAN-08:30 | 301.36 | 14.31 | 0.00 | 238.83 | 156.01 | 17.88 | 0.00 | 33.67 |
February | 279.67 | 0.82 | 0.80 | 01-FEB-08:09 | 376.92 | 15.19 | 0.00 | 255.67 | 180.84 | 18.52 | 0.00 | 90.33 |
March | 338.17 | 0.82 | 0.80 | 01-MAR-07:30 | 451.38 | 15.76 | 0.00 | 313.17 | 207.38 | 18.97 | 0.00 | 177.17 |
April | 358.33 | 0.81 | 0.80 | 01-APR-06:30 | 475.61 | 16.70 | 0.00 | 343.00 | 232.82 | 19.97 | 14.00 | 269.17 |
May | 393.83 | 0.81 | 0.80 | 01-MAY-05:00 | 639.55 | 17.65 | 12.50 | 386.67 | 287.88 | 20.86 | 61.17 | 345.50 |
June | 381.00 | 0.81 | 0.80 | 01-JUN-05:49 | 677.31 | 19.68 | 58.83 | 380.83 | 313.34 | 22.08 | 109.67 | 340.17 |
July | 408.67 | 0.81 | 0.80 | 01-JUL-05:19 | 615.82 | 18.94 | 44.67 | 390.00 | 271.44 | 20.54 | 86.50 | 357.83 |
August | 390.67 | 0.81 | 0.80 | 01-AUG-06:40 | 487.91 | 16.78 | 0.00 | 370.33 | 234.53 | 20.07 | 34.00 | 297.17 |
September | 328.83 | 0.81 | 0.80 | 01-SEP-06:30 | 419.01 | 16.05 | 0.00 | 310.83 | 208.00 | 19.34 | 0.00 | 183.50 |
October | 296.17 | 0.83 | 0.80 | 01-OCT-09:39 | 312.26 | 14.67 | 0.00 | 253.17 | 158.55 | 18.12 | 0.00 | 56.50 |
November | 300.00 | 0.83 | 0.80 | 01-NOV-07:10 | 309.11 | 14.12 | 0.00 | 243.67 | 157.57 | 17.57 | 0.00 | 51.67 |
December | 297.00 | 0.83 | 0.80 | 01-DEC-07:40 | 271.81 | 13.78 | 0.00 | 229.83 | 144.72 | 17.41 | 0.00 | 19.33 |
Annual Sum or Average | 4065.67 | 0.82 | 460.64 | 16.35 | 116.00 | 3716.00 | 219.11 | 19.44 | 305.33 | 2222.00 | ||
Minimum of Months | 279.67 | 0.81 | 0.80 | 271.81 | 13.78 | 0.00 | 229.83 | 144.72 | 17.41 | 0.00 | 19.33 | |
Maximum of Months | 408.67 | 0.83 | 0.80 | 677.31 | 19.68 | 58.83 | 390.00 | 313.34 | 22.08 | 109.67 | 357.83 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.989590E+11 | 127747.89 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.686204E+11 | 126477.63 | 06-FEB-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.988612E+11 | 127599.62 | 29-MAR-20:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.371493E+11 | 106908.07 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.324143E+11 | 95727.35 | 14-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.508468E+10 | 51968.68 | 13-JUN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.275393E+09 | 20211.25 | 06-JUL-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 69849887.12 | 5182.08 | 31-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.233899E+10 | 49132.85 | 20-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134289E+11 | 81240.71 | 12-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.569776E+11 | 128935.97 | 29-NOV-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.950321E+11 | 127807.41 | 12-DEC-21:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.509212E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 69849887.12 | 5182.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.989590E+11 | 128935.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.252693E+09 | 1845.89 | 08-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.302483E+09 | 995.42 | 25-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.504795E+09 | 1603.24 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126058E+09 | 1045.16 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170397E+09 | 811.52 | 14-MAY-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27542017.62 | 327.91 | 13-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 386138.92 | 351.68 | 18-SEP-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13594708.35 | 418.72 | 25-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 68905624.97 | 495.20 | 05-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150149E+09 | 1007.39 | 13-DEC-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.504795E+09 | 1845.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 183565.18 | 119.45 | 29-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 183565.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 183565.18 | 119.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 15442854.46 | 598.37 | 03-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 32305.76 | 41.37 | 28-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20398856.22 | 530.48 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 65938.46 | 118.11 | 01-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35939954.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20398856.22 | 598.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 15820494.43 | 343.29 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1503850.95 | 120.51 | 28-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21278538.99 | 318.26 | 30-MAR-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 297036.94 | 44.60 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38899921.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21278538.99 | 343.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.364282E+09 | 7924.13 | 03-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141179E+09 | 3532.30 | 04-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.303775E+09 | 5969.22 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101548E+09 | 1585.67 | 01-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 88966319.84 | 1334.38 | 13-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 48586303.93 | 914.79 | 12-JUN-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 23114121.86 | 562.84 | 10-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20100082.07 | 562.97 | 28-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43263421.22 | 740.83 | 19-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44344248.35 | 874.16 | 28-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118402E+09 | 1254.29 | 06-NOV-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149792E+09 | 3789.66 | 23-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 20100082.07 | 562.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.364282E+09 | 7924.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 9592236.05 | 1795.90 | 08-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 49297223.38 | 1704.93 | 12-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 84410238.39 | 3051.30 | 29-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 431895.03 | 553.31 | 22-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3244333.87 | 1361.82 | 09-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 257632.93 | 350.62 | 08-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 413473.46 | 571.45 | 18-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 152492.28 | 254.15 | 12-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84410238.39 | 3051.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 36980844.90 | 2788.95 | 03-JAN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 32826052.10 | 1947.80 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 69806896.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36980844.90 | 2788.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.195038E+09 | 3264.85 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24229312.02 | 825.23 | 28-FEB-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195010E+09 | 2391.06 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10255135.62 | 979.26 | 01-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 30376701.79 | 969.92 | 13-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.454909E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.195038E+09 | 3264.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2333122.75 | 1010.15 | 09-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1258231.76 | 683.04 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3591354.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2333122.75 | 1010.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.147285E+11 | 14923.41 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118617E+11 | 14101.57 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159855E+11 | 14310.90 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.718571E+10 | 13687.88 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.618449E+10 | 13483.38 | 14-MAY-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108226E+10 | 8912.65 | 13-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 62562347.84 | 4002.30 | 06-JUL-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29890880.57 | 1528.18 | 24-AUG-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.542137E+09 | 8913.69 | 20-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.245036E+10 | 13274.30 | 28-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100455E+11 | 13690.40 | 05-NOV-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146291E+11 | 14104.79 | 24-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.847876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 29890880.57 | 1528.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.159855E+11 | 14923.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.567249E+09 | 6585.15 | 01-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.402775E+09 | 6607.73 | 25-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.645226E+09 | 6700.03 | 29-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97544399.96 | 2730.24 | 11-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73130598.95 | 2854.07 | 28-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6853425.71 | 2432.85 | 05-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3239905.80 | 3037.11 | 23-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3362327.72 | 2950.96 | 19-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4109239.29 | 2449.79 | 20-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21593378.89 | 2621.84 | 14-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173133E+09 | 3622.83 | 24-NOV-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.419887E+09 | 4749.73 | 12-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.241810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3239905.80 | 2432.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.645226E+09 | 6700.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.112014E+10 | 6613.23 | 12-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.662265E+09 | 6579.16 | 25-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.877611E+09 | 6663.54 | 29-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134632E+09 | 5327.55 | 01-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74180589.92 | 2737.24 | 14-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7023602.27 | 2507.22 | 02-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3506963.68 | 2390.54 | 22-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4047470.96 | 2947.96 | 19-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5905503.20 | 2691.54 | 03-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 52114531.22 | 2836.75 | 24-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.415852E+09 | 4449.88 | 05-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.899832E+09 | 6602.34 | 13-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.425711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3506963.68 | 2390.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.112014E+10 | 6663.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15007835.11 | 2392.26 | 30-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15007835.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15007835.11 | 2392.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.339853E+10 | 37779.30 | 12-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.995392E+09 | 27557.61 | 04-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188031E+10 | 37908.58 | 29-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194629E+09 | 26469.14 | 28-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107472E+09 | 27048.60 | 20-MAY-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41233284.28 | 20842.66 | 09-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29069682.84 | 18174.55 | 18-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 50071136.51 | 20346.26 | 15-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 72003953.72 | 24036.10 | 02-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101390E+09 | 27227.92 | 16-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.901297E+09 | 27496.58 | 04-NOV-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.259436E+10 | 37620.05 | 15-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 29069682.84 | 18174.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.339853E+10 | 37908.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.558392E+09 | 5448.95 | 01-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.473833E+09 | 6461.90 | 25-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.698437E+09 | 6544.51 | 29-MAR-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117549E+09 | 3000.48 | 15-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110419E+09 | 2419.29 | 06-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12504666.76 | 2265.50 | 08-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1679897.04 | 1625.37 | 05-JUL-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 742289.83 | 1574.18 | 29-AUG-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3573094.24 | 1917.27 | 18-SEP-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26035717.57 | 1850.98 | 06-OCT-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213118E+09 | 3106.19 | 24-NOV-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.451739E+09 | 6052.44 | 12-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.266802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 742289.83 | 1574.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.698437E+09 | 6544.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107568E+10 | 6454.25 | 02-JAN-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.753479E+09 | 6428.93 | 25-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.936364E+09 | 6511.21 | 29-MAR-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172595E+09 | 3174.23 | 22-APR-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119370E+09 | 2421.82 | 15-MAY-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11566904.02 | 2263.84 | 07-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 608859.34 | 1553.12 | 12-JUL-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1074342.87 | 1628.14 | 27-AUG-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11672405.81 | 2268.77 | 24-SEP-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 68417791.85 | 2498.72 | 24-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.493807E+09 | 3353.60 | 23-NOV-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.931698E+09 | 6433.71 | 13-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.457634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 608859.34 | 1553.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107568E+10 | 6511.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.293541E+09 | 1989.04 | 01-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.242827E+09 | 2003.11 | 25-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.321638E+09 | 2026.63 | 29-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 72191270.12 | 1723.92 | 01-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 65803211.00 | 862.48 | 12-MAY-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11378862.58 | 618.87 | 23-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 781441.95 | 632.45 | 23-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1074029.95 | 601.75 | 19-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3516502.53 | 564.75 | 29-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33447463.15 | 805.90 | 24-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145778E+09 | 1124.90 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.253538E+09 | 1984.46 | 12-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 781441.95 | 564.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.321638E+09 | 2026.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.535715E+09 | 1998.42 | 12-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.363508E+09 | 1991.64 | 25-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.417709E+09 | 2011.66 | 29-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 99632363.77 | 1960.50 | 01-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 67748849.82 | 756.09 | 20-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10907431.10 | 612.82 | 08-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 782757.87 | 677.90 | 23-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1221429.54 | 600.07 | 19-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7275451.86 | 562.58 | 06-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 65340656.10 | 1959.46 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.289602E+09 | 1967.28 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.488825E+09 | 1995.47 | 13-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 782757.87 | 562.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.535715E+09 | 2011.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.324386E+09 | 2691.91 | 01-JAN-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.348780E+09 | 9442.31 | 25-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.752806E+09 | 9581.20 | 29-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154112E+09 | 4101.55 | 17-APR-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.241258E+09 | 5919.37 | 12-MAY-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35460767.14 | 3509.61 | 08-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9203315.49 | 3229.78 | 29-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5635367.79 | 3143.63 | 06-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4860530.25 | 2471.99 | 18-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23675578.10 | 4307.92 | 23-OCT-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 80639012.46 | 4017.56 | 24-NOV-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.223691E+09 | 2640.45 | 13-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4860530.25 | 2471.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.752806E+09 | 9581.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.572450E+11 | 0.571054E+11 | 208585.96 | 14-JAN-11:45 | 208585.96 | 0.21 |
February | 0.00 | 0.00 | 0.316038E+11 | 0.308895E+11 | 196578.24 | 01-FEB-11:45 | 196578.24 | 0.20 |
March | 0.00 | 0.00 | 0.353233E+11 | 0.346290E+11 | 183126.88 | 23-MAR-10:50 | 146052.42 | 0.22 |
April | 0.00 | 0.00 | 0.843398E+11 | 0.827112E+11 | 251962.06 | 26-APR-10:45 | 204536.53 | 0.44 |
May | 0.00 | 0.00 | 0.901865E+11 | 0.891896E+11 | 161605.97 | 18-MAY-10:50 | 142285.93 | 0.52 |
June | 0.00 | 0.00 | 0.168634E+12 | 0.146349E+12 | 312457.46 | 29-JUN-10:50 | 191271.96 | 0.85 |
July | 0.00 | 0.00 | 0.346290E+12 | 0.224669E+12 | 381630.33 | 31-JUL-10:45 | 224186.46 | 0.99 |
August | 0.00 | 0.00 | 0.390374E+12 | 0.234633E+12 | 409086.71 | 14-AUG-10:45 | 241002.03 | 0.99 |
September | 0.00 | 0.00 | 0.229545E+12 | 0.176186E+12 | 373514.51 | 22-SEP-12:00 | 184847.47 | 0.90 |
October | 0.00 | 0.00 | 0.260389E+12 | 0.209062E+12 | 384410.71 | 16-OCT-10:50 | 384410.71 | 0.59 |
November | 0.00 | 0.00 | 0.593969E+11 | 0.587286E+11 | 213511.11 | 19-NOV-11:50 | 213511.11 | 0.28 |
December | 0.00 | 0.00 | 0.661316E+11 | 0.661316E+11 | 192550.31 | 16-DEC-13:00 | 192550.31 | 0.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.181946E+13 | 0.141028E+13 | 0.53 | |||
Minimum of Months | 0.00 | 0.00 | 0.316038E+11 | 0.308895E+11 | 161605.97 | 142285.93 | 0.09 | |
Maximum of Months | 0.00 | 0.00 | 0.390374E+12 | 0.234633E+12 | 409086.71 | 384410.71 | 0.99 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.113067E+11 | 0.111344E+11 | 35831.89 | 17-JAN-14:00 | 29957.41 | 0.20 |
February | 0.00 | 0.00 | 0.624901E+10 | 0.601784E+10 | 34702.50 | 01-FEB-12:00 | 34702.50 | 0.18 |
March | 0.00 | 0.00 | 0.724922E+10 | 0.662458E+10 | 38122.69 | 23-MAR-15:00 | 25060.26 | 0.20 |
April | 0.00 | 0.00 | 0.170527E+11 | 0.156679E+11 | 45682.01 | 26-APR-11:00 | 34952.45 | 0.41 |
May | 0.00 | 0.00 | 0.176695E+11 | 0.169867E+11 | 33097.58 | 04-MAY-13:10 | 27478.84 | 0.49 |
June | 0.00 | 0.00 | 0.354046E+11 | 0.276503E+11 | 50379.43 | 29-JUN-11:00 | 30610.28 | 0.84 |
July | 0.00 | 0.00 | 0.697043E+11 | 0.417303E+11 | 59117.88 | 31-JUL-12:20 | 36173.22 | 0.99 |
August | 0.00 | 0.00 | 0.780509E+11 | 0.433674E+11 | 59096.39 | 14-AUG-10:55 | 36182.71 | 0.99 |
September | 0.00 | 0.00 | 0.472441E+11 | 0.329404E+11 | 61100.16 | 22-SEP-12:00 | 30033.85 | 0.89 |
October | 0.00 | 0.00 | 0.510747E+11 | 0.388693E+11 | 61507.15 | 16-OCT-10:55 | 61507.15 | 0.58 |
November | 0.00 | 0.00 | 0.116003E+11 | 0.113170E+11 | 37158.21 | 19-NOV-13:00 | 37158.21 | 0.25 |
December | 0.00 | 0.00 | 0.131328E+11 | 0.131083E+11 | 34610.58 | 16-DEC-13:00 | 34610.58 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.365739E+12 | 0.265414E+12 | 0.51 | |||
Minimum of Months | 0.00 | 0.00 | 0.624901E+10 | 0.601784E+10 | 33097.58 | 25060.26 | 0.08 | |
Maximum of Months | 0.00 | 0.00 | 0.780509E+11 | 0.433674E+11 | 61507.15 | 61507.15 | 0.99 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.167757E+10 | 0.105151E+10 | 11929.51 | 14-JAN-16:02 | 11929.51 | 0.37 |
February | 0.00 | 0.00 | 0.152445E+10 | 0.101002E+10 | 11678.58 | 03-FEB-16:02 | 11678.58 | 0.34 |
March | 0.00 | 0.00 | 0.160785E+10 | 0.968103E+09 | 11815.35 | 10-MAR-16:02 | 11815.35 | 0.37 |
April | 0.00 | 0.00 | 0.340876E+10 | 0.196408E+10 | 11922.54 | 01-APR-15:01 | 11922.54 | 0.69 |
May | 0.00 | 0.00 | 0.310158E+10 | 0.170419E+10 | 11743.85 | 05-MAY-15:02 | 10466.87 | 0.69 |
June | 0.00 | 0.00 | 0.460590E+10 | 0.248976E+10 | 12184.22 | 30-JUN-08:62 | 9717.20 | 0.79 |
July | 0.00 | 0.00 | 0.685750E+10 | 0.381100E+10 | 13164.59 | 23-JUL-08:62 | 10388.13 | 0.87 |
August | 0.00 | 0.00 | 0.719296E+10 | 0.399312E+10 | 13523.18 | 19-AUG-08:62 | 9923.57 | 0.89 |
September | 0.00 | 0.00 | 0.552526E+10 | 0.304819E+10 | 13118.57 | 22-SEP-08:62 | 9093.77 | 0.86 |
October | 0.00 | 0.00 | 0.513354E+10 | 0.349989E+10 | 13275.74 | 01-OCT-08:62 | 9616.71 | 0.61 |
November | 0.00 | 0.00 | 0.234656E+10 | 0.146174E+10 | 12055.01 | 19-NOV-09:02 | 12055.01 | 0.48 |
December | 0.00 | 0.00 | 0.198098E+10 | 0.159187E+10 | 11917.15 | 05-DEC-16:02 | 11917.15 | 0.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.449629E+11 | 0.265935E+11 | 0.60 | |||
Minimum of Months | 0.00 | 0.00 | 0.152445E+10 | 0.968103E+09 | 11678.58 | 9093.77 | 0.24 | |
Maximum of Months | 0.00 | 0.00 | 0.719296E+10 | 0.399312E+10 | 13523.18 | 12055.01 | 0.89 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.396938E+09 | 0.225828E+09 | 11446.81 | 14-JAN-16:02 | 11446.81 | 0.17 |
February | 0.00 | 0.00 | 0.558520E+09 | 0.344585E+09 | 11205.46 | 03-FEB-16:02 | 11205.46 | 0.20 |
March | 0.00 | 0.00 | 0.853553E+09 | 0.496276E+09 | 11336.92 | 10-MAR-16:02 | 11336.92 | 0.24 |
April | 0.00 | 0.00 | 0.261472E+10 | 0.146576E+10 | 11439.41 | 01-APR-15:01 | 11439.41 | 0.62 |
May | 0.00 | 0.00 | 0.292197E+10 | 0.161743E+10 | 11230.55 | 02-MAY-18:02 | 9996.77 | 0.67 |
June | 0.00 | 0.00 | 0.465320E+10 | 0.257987E+10 | 11689.22 | 30-JUN-08:62 | 9409.03 | 0.79 |
July | 0.00 | 0.00 | 0.674789E+10 | 0.381449E+10 | 12627.80 | 23-JUL-08:62 | 10020.40 | 0.85 |
August | 0.00 | 0.00 | 0.645108E+10 | 0.351908E+10 | 12946.53 | 19-AUG-08:62 | 9476.78 | 0.84 |
September | 0.00 | 0.00 | 0.424767E+10 | 0.217541E+10 | 12915.19 | 21-SEP-15:02 | 10542.22 | 0.79 |
October | 0.00 | 0.00 | 0.342109E+10 | 0.213797E+10 | 12772.75 | 05-OCT-15:02 | 10021.71 | 0.53 |
November | 0.00 | 0.00 | 0.735816E+09 | 0.389047E+09 | 11176.40 | 10-NOV-16:02 | 10173.88 | 0.31 |
December | 0.00 | 0.00 | 0.429877E+09 | 0.348158E+09 | 11434.15 | 05-DEC-16:02 | 11434.15 | 0.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.340323E+11 | 0.191139E+11 | 0.51 | |||
Minimum of Months | 0.00 | 0.00 | 0.396938E+09 | 0.225828E+09 | 11176.40 | 9409.03 | 0.10 | |
Maximum of Months | 0.00 | 0.00 | 0.674789E+10 | 0.381449E+10 | 12946.53 | 11446.81 | 0.85 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.211135E+11 | 0.179172E+11 | 39662.68 | 14-JAN-12:40 | 39662.68 | 0.26 |
February | 0.00 | 0.00 | 0.131170E+11 | 0.111413E+11 | 35465.32 | 02-FEB-12:40 | 35465.32 | 0.19 |
March | 0.00 | 0.00 | 0.649196E+10 | 0.409571E+10 | 26740.55 | 11-MAR-13:30 | 26740.55 | 0.21 |
April | 0.00 | 0.00 | 0.491772E+10 | 0.191348E+10 | 18554.34 | 08-APR-12:40 | 10633.71 | 0.29 |
May | 0.00 | 0.00 | 0.494295E+09 | 0.141755E+09 | 9160.34 | 04-MAY-12:30 | 3380.25 | 0.04 |
June | 0.00 | 0.00 | 62706442.41 | 7747375.92 | 3981.21 | 29-JUN-17:20 | 763.98 | 0.02 |
July | 0.00 | 0.00 | 0.348987E+10 | 0.930989E+09 | 15212.93 | 31-JUL-12:40 | 6086.89 | 0.25 |
August | 0.00 | 0.00 | 0.106381E+11 | 0.383658E+10 | 20269.30 | 18-AUG-12:00 | 9690.94 | 0.49 |
September | 0.00 | 0.00 | 0.146799E+11 | 0.835094E+10 | 42675.74 | 30-SEP-13:20 | 41640.02 | 0.47 |
October | 0.00 | 0.00 | 0.248966E+11 | 0.196440E+11 | 47884.96 | 16-OCT-12:20 | 47884.96 | 0.38 |
November | 0.00 | 0.00 | 0.219667E+11 | 0.181932E+11 | 44781.56 | 19-NOV-12:30 | 44781.56 | 0.31 |
December | 0.00 | 0.00 | 0.250156E+11 | 0.227463E+11 | 40370.32 | 19-DEC-13:00 | 40370.32 | 0.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.146884E+12 | 0.108919E+12 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 62706442.41 | 7747375.92 | 3981.21 | 763.98 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.250156E+11 | 0.227463E+11 | 47884.96 | 47884.96 | 0.49 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.625529E+10 | 0.308970E+10 | 61071.85 | 21-JAN-09:02 | 52472.99 | 0.33 |
February | 0.00 | 0.00 | 0.685124E+10 | 0.339437E+10 | 61815.13 | 13-FEB-19:03 | 49513.02 | 0.42 |
March | 0.00 | 0.00 | 0.899609E+10 | 0.439060E+10 | 59201.65 | 24-MAR-15:02 | 52208.51 | 0.45 |
April | 0.00 | 0.00 | 0.168809E+11 | 0.834024E+10 | 61654.77 | 26-APR-08:62 | 55197.90 | 0.66 |
May | 0.00 | 0.00 | 0.217435E+11 | 0.118797E+11 | 62073.70 | 06-MAY-08:62 | 53045.95 | 0.69 |
June | 0.00 | 0.00 | 0.309790E+11 | 0.169582E+11 | 70023.53 | 29-JUN-18:02 | 56935.31 | 0.71 |
July | 0.00 | 0.00 | 0.403928E+11 | 0.222747E+11 | 73697.62 | 29-JUL-18:02 | 52529.64 | 0.71 |
August | 0.00 | 0.00 | 0.372729E+11 | 0.192001E+11 | 73413.17 | 19-AUG-08:62 | 54611.96 | 0.71 |
September | 0.00 | 0.00 | 0.253313E+11 | 0.119549E+11 | 71223.61 | 22-SEP-08:62 | 50041.88 | 0.70 |
October | 0.00 | 0.00 | 0.228420E+11 | 0.138766E+11 | 73594.49 | 01-OCT-08:62 | 51531.83 | 0.52 |
November | 0.00 | 0.00 | 0.836355E+10 | 0.434354E+10 | 62934.17 | 12-NOV-09:02 | 51238.62 | 0.42 |
December | 0.00 | 0.00 | 0.546331E+10 | 0.370225E+10 | 60549.93 | 05-DEC-09:02 | 60549.93 | 0.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.231372E+12 | 0.123405E+12 | 0.54 | |||
Minimum of Months | 0.00 | 0.00 | 0.546331E+10 | 0.308970E+10 | 59201.65 | 49513.02 | 0.20 | |
Maximum of Months | 0.00 | 0.00 | 0.403928E+11 | 0.222747E+11 | 73697.62 | 60549.93 | 0.71 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.177537E+10 | 0.121757E+10 | 10450.78 | 14-JAN-16:02 | 10450.78 | 0.38 |
February | 0.00 | 0.00 | 0.141568E+10 | 0.995173E+09 | 10371.29 | 01-FEB-09:02 | 10371.29 | 0.31 |
March | 0.00 | 0.00 | 0.158181E+10 | 0.982038E+09 | 10350.59 | 10-MAR-16:02 | 10350.59 | 0.37 |
April | 0.00 | 0.00 | 0.305241E+10 | 0.178156E+10 | 10444.33 | 01-APR-15:01 | 10444.33 | 0.69 |
May | 0.00 | 0.00 | 0.262533E+10 | 0.146614E+10 | 10381.43 | 03-MAY-08:62 | 9340.99 | 0.64 |
June | 0.00 | 0.00 | 0.384522E+10 | 0.203496E+10 | 11170.86 | 28-JUN-15:02 | 9448.58 | 0.82 |
July | 0.00 | 0.00 | 0.619719E+10 | 0.337836E+10 | 11632.36 | 24-JUL-18:02 | 9025.98 | 0.92 |
August | 0.00 | 0.00 | 0.682480E+10 | 0.374731E+10 | 11522.98 | 13-AUG-18:02 | 8957.02 | 0.93 |
September | 0.00 | 0.00 | 0.469226E+10 | 0.255503E+10 | 12019.78 | 21-SEP-15:02 | 9490.68 | 0.88 |
October | 0.00 | 0.00 | 0.484046E+10 | 0.337393E+10 | 11653.92 | 05-OCT-15:02 | 9155.67 | 0.61 |
November | 0.00 | 0.00 | 0.213919E+10 | 0.145854E+10 | 10560.53 | 19-NOV-09:02 | 10560.53 | 0.45 |
December | 0.00 | 0.00 | 0.197589E+10 | 0.167452E+10 | 10553.10 | 05-DEC-09:02 | 10553.10 | 0.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.409656E+11 | 0.246652E+11 | 0.60 | |||
Minimum of Months | 0.00 | 0.00 | 0.141568E+10 | 0.982038E+09 | 10350.59 | 8957.02 | 0.22 | |
Maximum of Months | 0.00 | 0.00 | 0.682480E+10 | 0.374731E+10 | 12019.78 | 10560.53 | 0.93 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.554613E+09 | 0.343863E+09 | 9791.04 | 21-JAN-09:02 | 8442.23 | 0.18 |
February | 0.00 | 0.00 | 0.526729E+09 | 0.349499E+09 | 9627.52 | 01-FEB-09:02 | 9627.52 | 0.18 |
March | 0.00 | 0.00 | 0.840309E+09 | 0.484219E+09 | 9964.39 | 23-MAR-15:02 | 9238.05 | 0.24 |
April | 0.00 | 0.00 | 0.226941E+10 | 0.131612E+10 | 10013.89 | 27-APR-08:62 | 8674.71 | 0.54 |
May | 0.00 | 0.00 | 0.245638E+10 | 0.139075E+10 | 9986.96 | 03-MAY-08:62 | 8946.69 | 0.60 |
June | 0.00 | 0.00 | 0.387558E+10 | 0.211615E+10 | 10725.63 | 28-JUN-15:02 | 9060.76 | 0.81 |
July | 0.00 | 0.00 | 0.605871E+10 | 0.336823E+10 | 11150.52 | 24-JUL-18:02 | 8665.96 | 0.91 |
August | 0.00 | 0.00 | 0.602291E+10 | 0.327006E+10 | 11090.40 | 18-AUG-18:02 | 8573.16 | 0.91 |
September | 0.00 | 0.00 | 0.341423E+10 | 0.175982E+10 | 11550.72 | 21-SEP-15:02 | 9094.87 | 0.75 |
October | 0.00 | 0.00 | 0.309766E+10 | 0.202022E+10 | 11276.35 | 01-OCT-15:02 | 8737.89 | 0.50 |
November | 0.00 | 0.00 | 0.716842E+09 | 0.445051E+09 | 10131.72 | 19-NOV-09:02 | 10131.72 | 0.26 |
December | 0.00 | 0.00 | 0.530637E+09 | 0.453635E+09 | 10125.24 | 05-DEC-09:02 | 10125.24 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.303640E+11 | 0.173176E+11 | 0.50 | |||
Minimum of Months | 0.00 | 0.00 | 0.526729E+09 | 0.343863E+09 | 9627.52 | 8442.23 | 0.08 | |
Maximum of Months | 0.00 | 0.00 | 0.605871E+10 | 0.336823E+10 | 11550.72 | 10131.72 | 0.91 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.313628E+09 | 0.205366E+09 | 3095.08 | 21-JAN-09:02 | 2262.22 | 0.26 |
February | 0.00 | 0.00 | 0.301922E+09 | 0.207315E+09 | 3022.38 | 03-FEB-16:02 | 3022.38 | 0.23 |
March | 0.00 | 0.00 | 0.351290E+09 | 0.223317E+09 | 3057.80 | 10-MAR-16:02 | 3057.80 | 0.27 |
April | 0.00 | 0.00 | 0.780373E+09 | 0.473370E+09 | 3155.92 | 26-APR-08:62 | 2472.82 | 0.57 |
May | 0.00 | 0.00 | 0.687295E+09 | 0.399465E+09 | 3119.83 | 03-MAY-08:62 | 2365.55 | 0.56 |
June | 0.00 | 0.00 | 0.107496E+10 | 0.595907E+09 | 3259.91 | 30-JUN-08:62 | 2426.50 | 0.75 |
July | 0.00 | 0.00 | 0.166885E+10 | 0.921015E+09 | 3518.97 | 23-JUL-08:62 | 2581.96 | 0.89 |
August | 0.00 | 0.00 | 0.172563E+10 | 0.940275E+09 | 3615.85 | 19-AUG-08:62 | 2439.44 | 0.90 |
September | 0.00 | 0.00 | 0.124165E+10 | 0.689069E+09 | 3427.36 | 09-SEP-08:62 | 2373.13 | 0.84 |
October | 0.00 | 0.00 | 0.111639E+10 | 0.764593E+09 | 3541.27 | 01-OCT-08:62 | 2348.95 | 0.54 |
November | 0.00 | 0.00 | 0.440913E+09 | 0.278623E+09 | 3090.47 | 19-NOV-09:02 | 3090.47 | 0.35 |
December | 0.00 | 0.00 | 0.366628E+09 | 0.304996E+09 | 3084.09 | 05-DEC-16:02 | 3084.09 | 0.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.100695E+11 | 0.600331E+10 | 0.53 | |||
Minimum of Months | 0.00 | 0.00 | 0.301922E+09 | 0.205366E+09 | 3022.38 | 2262.22 | 0.16 | |
Maximum of Months | 0.00 | 0.00 | 0.172563E+10 | 0.940275E+09 | 3615.85 | 3090.47 | 0.90 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 57610929.74 | 38175223.26 | 2953.80 | 14-JAN-16:02 | 2953.80 | 0.08 |
February | 0.00 | 0.00 | 93999769.81 | 65507291.98 | 2891.52 | 03-FEB-16:02 | 2891.52 | 0.10 |
March | 0.00 | 0.00 | 0.177157E+09 | 0.112044E+09 | 2925.41 | 10-MAR-16:02 | 2925.41 | 0.15 |
April | 0.00 | 0.00 | 0.581347E+09 | 0.347682E+09 | 3008.10 | 26-APR-08:62 | 2338.91 | 0.47 |
May | 0.00 | 0.00 | 0.639517E+09 | 0.376636E+09 | 2973.79 | 03-MAY-08:62 | 2242.38 | 0.54 |
June | 0.00 | 0.00 | 0.108174E+10 | 0.610800E+09 | 3115.06 | 30-JUN-08:62 | 2346.47 | 0.75 |
July | 0.00 | 0.00 | 0.163473E+10 | 0.911334E+09 | 3362.30 | 23-JUL-08:62 | 2486.45 | 0.87 |
August | 0.00 | 0.00 | 0.152123E+10 | 0.816673E+09 | 3455.01 | 19-AUG-08:62 | 2319.80 | 0.86 |
September | 0.00 | 0.00 | 0.896266E+09 | 0.472317E+09 | 3315.11 | 21-SEP-15:02 | 2730.65 | 0.75 |
October | 0.00 | 0.00 | 0.686723E+09 | 0.438813E+09 | 3398.48 | 01-OCT-08:62 | 2190.73 | 0.44 |
November | 0.00 | 0.00 | 98484518.06 | 57942258.37 | 2889.94 | 10-NOV-16:02 | 2621.93 | 0.14 |
December | 0.00 | 0.00 | 59379140.44 | 51328712.73 | 2950.51 | 05-DEC-16:02 | 2950.51 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.752818E+10 | 0.429925E+10 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 57610929.74 | 38175223.26 | 2889.94 | 2190.73 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.163473E+10 | 0.911334E+09 | 3455.01 | 2953.80 | 0.87 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.666781E+10 | 0.540311E+10 | 14400.58 | 14-JAN-16:02 | 14400.58 | 0.51 |
February | 0.00 | 0.00 | 0.429756E+10 | 0.334891E+10 | 14098.65 | 03-FEB-16:02 | 14098.65 | 0.45 |
March | 0.00 | 0.00 | 0.352153E+10 | 0.229234E+10 | 14263.23 | 10-MAR-16:02 | 14263.23 | 0.49 |
April | 0.00 | 0.00 | 0.424207E+10 | 0.235058E+10 | 14392.95 | 01-APR-15:01 | 14392.95 | 0.71 |
May | 0.00 | 0.00 | 0.242793E+10 | 0.114391E+10 | 14230.38 | 06-MAY-15:02 | 13005.56 | 0.54 |
June | 0.00 | 0.00 | 0.348554E+10 | 0.155435E+10 | 15655.13 | 29-JUN-18:02 | 12503.08 | 0.70 |
July | 0.00 | 0.00 | 0.617776E+10 | 0.291538E+10 | 16644.96 | 24-JUL-18:02 | 12091.91 | 0.83 |
August | 0.00 | 0.00 | 0.812750E+10 | 0.409419E+10 | 16552.29 | 13-AUG-18:02 | 11896.32 | 0.88 |
September | 0.00 | 0.00 | 0.786616E+10 | 0.449974E+10 | 15880.45 | 22-SEP-08:62 | 10926.28 | 0.88 |
October | 0.00 | 0.00 | 0.936631E+10 | 0.706369E+10 | 16331.11 | 01-OCT-18:02 | 11908.12 | 0.63 |
November | 0.00 | 0.00 | 0.684814E+10 | 0.531526E+10 | 14548.63 | 19-NOV-09:02 | 14548.63 | 0.60 |
December | 0.00 | 0.00 | 0.733512E+10 | 0.648983E+10 | 14538.28 | 05-DEC-09:02 | 14538.28 | 0.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.703634E+11 | 0.464713E+11 | 0.63 | |||
Minimum of Months | 0.00 | 0.00 | 0.242793E+10 | 0.114391E+10 | 14098.65 | 10926.28 | 0.36 | |
Maximum of Months | 0.00 | 0.00 | 0.936631E+10 | 0.706369E+10 | 16644.96 | 14548.63 | 0.88 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 45336.02 | 181927.27 | 08-JAN-07:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 34937.89 | 151955.47 | 04-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 45373.33 | 185956.25 | 29-MAR-08:62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 17447.24 | 136896.41 | 01-APR-06:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14701.16 | 116742.77 | 14-MAY-04:50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 2441.02 | 63382.46 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 156.90 | 33541.50 | 18-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 66.63 | 31740.51 | 29-AUG-18:05 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 1164.91 | 59258.40 | 20-SEP-04:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 6039.08 | 97168.53 | 29-OCT-06:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 26747.03 | 144072.18 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 43040.82 | 156372.34 | 23-DEC-06:00 |
Annual Sum or Average | 0.00 | 19749.04 | ||||
Minimum of Months | 0.00 | 0.00 | 66.63 | 31740.51 | ||
Maximum of Months | 0.00 | 0.00 | 45373.33 | 185956.25 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 43697.86 | 301569.72 | 14-JAN-11:33 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30913.37 | 283067.89 | 01-FEB-09:02 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 28127.59 | 319709.88 | 23-MAR-15:02 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 58331.92 | 310300.87 | 26-APR-10:45 | 0.00 | 0.00 | 01-APR-00:10 |
May | 58510.11 | 349838.88 | 18-MAY-15:02 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 104347.26 | 468120.75 | 29-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 190386.04 | 547707.06 | 31-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 212533.24 | 548150.58 | 18-AUG-15:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 138145.82 | 501377.32 | 29-SEP-15:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 149573.66 | 525519.36 | 14-OCT-15:02 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 48249.55 | 357548.61 | 19-NOV-09:02 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 49382.42 | 334891.99 | 05-DEC-09:02 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 93250.27 | 0.00 | ||||
Minimum of Months | 28127.59 | 283067.89 | 0.00 | 0.00 | ||
Maximum of Months | 212533.24 | 548150.58 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 24241.71 | 49031.35 | 31-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 24271.54 | 49034.02 | 01-FEB-07:30 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 24039.58 | 48751.99 | 01-MAR-07:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23559.33 | 47892.22 | 04-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22999.63 | 46886.13 | 02-MAY-06:45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 22503.26 | 45690.28 | 01-JUN-06:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22173.39 | 44779.11 | 03-JUL-06:15 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 22161.83 | 44690.92 | 31-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22406.70 | 45422.39 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22870.18 | 46574.03 | 31-OCT-06:30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 23433.60 | 47721.50 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23932.85 | 48581.99 | 29-DEC-07:40 |
Annual Sum or Average | 0.00 | 23210.09 | ||||
Minimum of Months | 0.00 | 0.00 | 22161.83 | 44690.92 | ||
Maximum of Months | 0.00 | 0.00 | 24271.54 | 49034.02 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 0.89 | 2194.93 | 01-JAN-00:10 | 0.89 |
February | 0.530997E+10 | 0.89 | 2194.93 | 01-FEB-00:03 | 0.89 |
March | 0.587890E+10 | 0.89 | 2194.93 | 01-MAR-00:03 | 0.89 |
April | 0.568926E+10 | 0.89 | 2194.93 | 01-APR-00:10 | 0.89 |
May | 0.587890E+10 | 0.89 | 2194.93 | 01-MAY-00:05 | 0.88 |
June | 0.568926E+10 | 0.89 | 2194.93 | 01-JUN-00:05 | 0.89 |
July | 0.587890E+10 | 0.89 | 2194.93 | 01-JUL-00:10 | 0.88 |
August | 0.587890E+10 | 0.89 | 2194.93 | 01-AUG-00:05 | 0.89 |
September | 0.568926E+10 | 0.89 | 2194.93 | 01-SEP-00:05 | 0.88 |
October | 0.587890E+10 | 0.89 | 2194.93 | 01-OCT-00:10 | 0.89 |
November | 0.568926E+10 | 0.89 | 2194.93 | 01-NOV-00:05 | 0.89 |
December | 0.587890E+10 | 0.89 | 2194.93 | 01-DEC-00:03 | 0.90 |
Annual Sum or Average | 0.692193E+11 | 0.89 | |||
Minimum of Months | 0.530997E+10 | 0.89 | 2194.93 | 0.88 | |
Maximum of Months | 0.587890E+10 | 0.89 | 2194.93 | 0.90 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.362558E+11 | 0.87 | 24963.38 | 18-JAN-22:10 | 1.24 |
February | 0.327383E+11 | 0.87 | 23429.79 | 01-FEB-22:10 | 1.20 |
March | 0.360980E+11 | 0.86 | 23237.41 | 24-MAR-21:10 | 1.19 |
April | 0.357103E+11 | 0.87 | 24250.74 | 26-APR-21:10 | 1.22 |
May | 0.371815E+11 | 0.88 | 25339.90 | 04-MAY-21:10 | 1.25 |
June | 0.368371E+11 | 0.89 | 25087.94 | 27-JUN-21:10 | 1.24 |
July | 0.386167E+11 | 0.89 | 26100.10 | 31-JUL-21:10 | 1.27 |
August | 0.388967E+11 | 0.90 | 26480.46 | 18-AUG-21:10 | 1.28 |
September | 0.370456E+11 | 0.89 | 28547.92 | 29-SEP-21:10 | 1.36 |
October | 0.389313E+11 | 0.90 | 30185.71 | 16-OCT-21:10 | 1.41 |
November | 0.358542E+11 | 0.88 | 25187.70 | 28-NOV-22:10 | 1.26 |
December | 0.366770E+11 | 0.87 | 26821.02 | 05-DEC-22:10 | 1.31 |
Annual Sum or Average | 0.440843E+12 | 0.88 | |||
Minimum of Months | 0.327383E+11 | 0.86 | 23237.41 | 1.19 | |
Maximum of Months | 0.389313E+11 | 0.90 | 30185.71 | 1.41 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:10 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:03 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:05 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:05 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:05 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:05 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:05 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:05 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156351E+09 | 0.47 | 668.83 | 01-JAN-19:02 | 0.58 |
February | 0.137141E+09 | 0.46 | 668.83 | 01-FEB-09:02 | 0.59 |
March | 0.153507E+09 | 0.45 | 668.83 | 01-MAR-16:01 | 0.58 |
April | 0.210767E+09 | 0.47 | 668.83 | 01-APR-15:01 | 0.59 |
May | 0.195568E+09 | 0.46 | 668.83 | 01-MAY-15:01 | 0.58 |
June | 0.250303E+09 | 0.47 | 668.83 | 01-JUN-15:02 | 0.58 |
July | 0.344484E+09 | 0.50 | 668.83 | 01-JUL-08:62 | 0.58 |
August | 0.355678E+09 | 0.52 | 668.83 | 01-AUG-08:62 | 0.58 |
September | 0.291488E+09 | 0.50 | 668.83 | 01-SEP-15:02 | 0.58 |
October | 0.284029E+09 | 0.50 | 668.83 | 01-OCT-08:62 | 0.58 |
November | 0.164041E+09 | 0.48 | 668.83 | 01-NOV-08:62 | 0.58 |
December | 0.166364E+09 | 0.48 | 668.83 | 02-DEC-16:02 | 0.58 |
Annual Sum or Average | 0.270972E+10 | 0.48 | |||
Minimum of Months | 0.137141E+09 | 0.45 | 668.83 | 0.58 | |
Maximum of Months | 0.355678E+09 | 0.52 | 668.83 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.114477E+09 | 0.42 | 641.51 | 01-JAN-09:02 | 0.58 |
February | 97974686.33 | 0.43 | 641.51 | 01-FEB-16:02 | 0.58 |
March | 0.124420E+09 | 0.42 | 641.51 | 01-MAR-09:02 | 0.58 |
April | 0.170499E+09 | 0.45 | 641.51 | 01-APR-15:01 | 0.59 |
May | 0.185400E+09 | 0.45 | 641.51 | 01-MAY-15:01 | 0.58 |
June | 0.252081E+09 | 0.47 | 641.51 | 01-JUN-15:02 | 0.58 |
July | 0.339011E+09 | 0.50 | 641.51 | 01-JUL-08:62 | 0.58 |
August | 0.319213E+09 | 0.49 | 641.51 | 01-AUG-08:62 | 0.58 |
September | 0.228796E+09 | 0.46 | 641.51 | 01-SEP-15:02 | 0.58 |
October | 0.197479E+09 | 0.46 | 641.51 | 01-OCT-08:62 | 0.58 |
November | 93281419.16 | 0.44 | 641.51 | 01-NOV-15:02 | 0.58 |
December | 0.107042E+09 | 0.43 | 641.51 | 02-DEC-16:02 | 0.58 |
Annual Sum or Average | 0.222967E+10 | 0.45 | |||
Minimum of Months | 93281419.16 | 0.42 | 641.51 | 0.58 | |
Maximum of Months | 0.339011E+09 | 0.50 | 641.51 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.117027E+10 | 0.30 | 2482.88 | 22-JAN-13:30 | 0.58 |
February | 0.705163E+09 | 0.23 | 2387.29 | 02-FEB-14:00 | 0.59 |
March | 0.356946E+09 | 0.16 | 1144.05 | 11-MAR-13:40 | 0.59 |
April | 0.288290E+09 | 0.17 | 803.59 | 08-APR-13:10 | 0.58 |
May | 32143914.08 | 0.02 | 486.17 | 03-MAY-13:10 | 0.58 |
June | 5834262.80 | 0.01 | 247.29 | 29-JUN-17:13 | 0.58 |
July | 0.191442E+09 | 0.15 | 619.17 | 31-JUL-13:00 | 0.58 |
August | 0.516198E+09 | 0.28 | 774.40 | 30-AUG-13:00 | 0.58 |
September | 0.714372E+09 | 0.29 | 2512.70 | 30-SEP-13:20 | 0.59 |
October | 0.125274E+10 | 0.36 | 2574.61 | 31-OCT-13:10 | 0.59 |
November | 0.118787E+10 | 0.33 | 2297.35 | 18-NOV-13:30 | 0.59 |
December | 0.136699E+10 | 0.34 | 2346.46 | 03-DEC-12:50 | 0.58 |
Annual Sum or Average | 0.778827E+10 | 0.22 | |||
Minimum of Months | 5834262.80 | 0.01 | 247.29 | 0.58 | |
Maximum of Months | 0.136699E+10 | 0.36 | 2574.61 | 0.59 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.675706E+09 | 0.41 | 3635.11 | 01-JAN-09:02 | 0.58 |
February | 0.558400E+09 | 0.41 | 3635.11 | 01-FEB-19:02 | 0.58 |
March | 0.709211E+09 | 0.41 | 3635.11 | 03-MAR-16:02 | 0.58 |
April | 0.940660E+09 | 0.41 | 3635.11 | 01-APR-08:62 | 0.59 |
May | 0.117153E+10 | 0.41 | 3635.11 | 01-MAY-15:01 | 0.58 |
June | 0.146626E+10 | 0.41 | 3635.11 | 01-JUN-15:02 | 0.58 |
July | 0.181427E+10 | 0.41 | 3635.11 | 01-JUL-08:62 | 0.58 |
August | 0.162773E+10 | 0.41 | 3635.11 | 01-AUG-08:62 | 0.58 |
September | 0.121144E+10 | 0.41 | 3635.11 | 01-SEP-15:02 | 0.58 |
October | 0.119381E+10 | 0.41 | 3635.11 | 01-OCT-08:62 | 0.58 |
November | 0.627043E+09 | 0.41 | 3635.11 | 01-NOV-08:62 | 0.58 |
December | 0.608083E+09 | 0.41 | 3635.11 | 02-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.126041E+11 | 0.41 | |||
Minimum of Months | 0.558400E+09 | 0.41 | 3635.11 | 0.58 | |
Maximum of Months | 0.181427E+10 | 0.41 | 3635.11 | 0.59 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156436E+09 | 0.47 | 585.18 | 01-JAN-09:02 | 0.58 |
February | 0.132281E+09 | 0.46 | 585.18 | 01-FEB-09:02 | 0.59 |
March | 0.148644E+09 | 0.45 | 585.18 | 01-MAR-09:02 | 0.58 |
April | 0.187742E+09 | 0.49 | 585.18 | 01-APR-08:62 | 0.59 |
May | 0.164380E+09 | 0.46 | 585.18 | 01-MAY-08:62 | 0.58 |
June | 0.207661E+09 | 0.49 | 585.18 | 01-JUN-08:62 | 0.58 |
July | 0.310135E+09 | 0.54 | 585.18 | 01-JUL-08:62 | 0.58 |
August | 0.335951E+09 | 0.54 | 585.18 | 01-AUG-08:62 | 0.58 |
September | 0.247855E+09 | 0.52 | 585.18 | 01-SEP-08:62 | 0.58 |
October | 0.267906E+09 | 0.51 | 585.18 | 01-OCT-08:62 | 0.58 |
November | 0.156382E+09 | 0.48 | 585.18 | 01-NOV-08:62 | 0.58 |
December | 0.164479E+09 | 0.48 | 585.18 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.247985E+10 | 0.49 | |||
Minimum of Months | 0.132281E+09 | 0.45 | 585.18 | 0.58 | |
Maximum of Months | 0.335951E+09 | 0.54 | 585.18 | 0.59 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.109871E+09 | 0.41 | 561.19 | 01-JAN-09:02 | 0.58 |
February | 93473689.05 | 0.41 | 561.19 | 01-FEB-09:02 | 0.59 |
March | 0.117764E+09 | 0.41 | 561.19 | 01-MAR-09:02 | 0.58 |
April | 0.146611E+09 | 0.43 | 561.19 | 01-APR-08:62 | 0.59 |
May | 0.154663E+09 | 0.44 | 561.19 | 01-MAY-08:62 | 0.58 |
June | 0.208857E+09 | 0.49 | 561.19 | 01-JUN-08:62 | 0.58 |
July | 0.304794E+09 | 0.53 | 561.19 | 01-JUL-08:62 | 0.58 |
August | 0.298127E+09 | 0.53 | 561.19 | 01-AUG-08:62 | 0.58 |
September | 0.181866E+09 | 0.45 | 561.19 | 01-SEP-08:62 | 0.58 |
October | 0.177041E+09 | 0.45 | 561.19 | 01-OCT-08:62 | 0.58 |
November | 89615748.02 | 0.41 | 561.19 | 01-NOV-08:62 | 0.58 |
December | 0.104072E+09 | 0.41 | 561.19 | 02-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.198675E+10 | 0.45 | |||
Minimum of Months | 89615748.02 | 0.41 | 561.19 | 0.58 | |
Maximum of Months | 0.304794E+09 | 0.53 | 561.19 | 0.59 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 40645294.25 | 0.47 | 173.14 | 01-JAN-19:02 | 0.58 |
February | 37689418.98 | 0.46 | 173.14 | 01-FEB-16:02 | 0.58 |
March | 43491363.95 | 0.45 | 173.14 | 01-MAR-16:01 | 0.58 |
April | 52393942.28 | 0.47 | 173.14 | 01-APR-15:01 | 0.59 |
May | 47604584.00 | 0.46 | 173.14 | 01-MAY-15:01 | 0.58 |
June | 60293086.89 | 0.48 | 173.14 | 01-JUN-15:02 | 0.58 |
July | 85851392.67 | 0.52 | 173.14 | 01-JUL-08:62 | 0.58 |
August | 87728732.34 | 0.52 | 173.14 | 01-AUG-08:62 | 0.58 |
September | 67478362.35 | 0.50 | 173.14 | 01-SEP-15:02 | 0.58 |
October | 65049652.59 | 0.50 | 173.14 | 01-OCT-08:62 | 0.58 |
November | 39273028.24 | 0.48 | 173.14 | 01-NOV-15:02 | 0.58 |
December | 42018407.08 | 0.48 | 173.14 | 02-DEC-16:02 | 0.58 |
Annual Sum or Average | 0.669517E+09 | 0.48 | |||
Minimum of Months | 37689418.98 | 0.45 | 173.14 | 0.58 | |
Maximum of Months | 87728732.34 | 0.52 | 173.14 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 37350743.16 | 0.42 | 165.58 | 01-JAN-09:02 | 0.58 |
February | 31124406.92 | 0.42 | 165.58 | 01-FEB-16:02 | 0.58 |
March | 38026561.78 | 0.42 | 165.58 | 01-MAR-09:02 | 0.58 |
April | 43149820.39 | 0.45 | 165.58 | 01-APR-08:62 | 0.59 |
May | 44938060.18 | 0.45 | 165.58 | 01-MAY-15:01 | 0.58 |
June | 60836746.03 | 0.48 | 165.58 | 01-JUN-15:02 | 0.58 |
July | 84760831.91 | 0.51 | 165.58 | 01-JUL-08:62 | 0.58 |
August | 77672328.81 | 0.50 | 165.58 | 01-AUG-08:62 | 0.58 |
September | 50373094.30 | 0.47 | 165.58 | 01-SEP-15:02 | 0.58 |
October | 44509667.93 | 0.46 | 165.58 | 01-OCT-08:62 | 0.58 |
November | 28295285.64 | 0.43 | 165.58 | 01-NOV-15:02 | 0.58 |
December | 35880286.32 | 0.42 | 165.58 | 02-DEC-16:02 | 0.58 |
Annual Sum or Average | 0.576918E+09 | 0.45 | |||
Minimum of Months | 28295285.64 | 0.42 | 165.58 | 0.58 | |
Maximum of Months | 84760831.91 | 0.51 | 165.58 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.418076E+09 | 0.52 | 800.36 | 01-JAN-09:02 | 0.58 |
February | 0.285382E+09 | 0.49 | 800.36 | 01-FEB-09:02 | 0.59 |
March | 0.256013E+09 | 0.47 | 800.36 | 01-MAR-09:02 | 0.58 |
April | 0.248366E+09 | 0.49 | 800.36 | 01-APR-15:01 | 0.59 |
May | 0.165006E+09 | 0.43 | 800.36 | 01-MAY-15:01 | 0.58 |
June | 0.189304E+09 | 0.44 | 800.36 | 01-JUN-15:02 | 0.58 |
July | 0.299924E+09 | 0.49 | 800.36 | 01-JUL-08:62 | 0.58 |
August | 0.383127E+09 | 0.51 | 800.36 | 01-AUG-08:62 | 0.58 |
September | 0.394687E+09 | 0.51 | 800.36 | 01-SEP-15:02 | 0.58 |
October | 0.509405E+09 | 0.51 | 800.36 | 01-OCT-08:62 | 0.58 |
November | 0.406224E+09 | 0.52 | 800.36 | 01-NOV-08:62 | 0.58 |
December | 0.454560E+09 | 0.52 | 800.36 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.401007E+10 | 0.49 | |||
Minimum of Months | 0.165006E+09 | 0.43 | 800.36 | 0.58 | |
Maximum of Months | 0.509405E+09 | 0.52 | 800.36 | 0.59 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.495717E+09 | 0.446145E+09 | 567.45 | 03-JAN-05:00 | 510.70 | 510.70 | 46.64 | 1.27 |
February | 0.369936E+09 | 0.332943E+09 | 547.29 | 04-FEB-05:55 | 492.56 | 492.56 | 47.73 | 1.12 |
March | 0.502910E+09 | 0.452619E+09 | 569.47 | 30-MAR-04:00 | 512.52 | 512.52 | 47.56 | 1.29 |
April | 0.195331E+09 | 0.175798E+09 | 520.78 | 01-APR-06:00 | 468.70 | 468.70 | 46.09 | 0.97 |
May | 0.170092E+09 | 0.153083E+09 | 478.79 | 14-MAY-04:50 | 430.91 | 430.91 | 44.81 | 0.80 |
June | 27747152.52 | 24972437.27 | 280.58 | 13-JUN-04:00 | 252.52 | 252.52 | 36.51 | 0.35 |
July | 2060098.82 | 1854088.94 | 171.88 | 26-JUL-08:05 | 154.69 | 154.69 | 49.95 | 0.20 |
August | 1203462.12 | 1083115.91 | 192.27 | 15-AUG-08:05 | 173.04 | 173.04 | 54.80 | 0.22 |
September | 13573856.30 | 12216470.67 | 258.80 | 20-SEP-04:00 | 232.92 | 232.92 | 35.01 | 0.32 |
October | 71389867.97 | 64250881.18 | 410.82 | 29-OCT-06:00 | 369.74 | 369.74 | 41.26 | 0.61 |
November | 0.301765E+09 | 0.271589E+09 | 527.50 | 05-NOV-05:07 | 474.75 | 474.75 | 47.09 | 1.00 |
December | 0.483138E+09 | 0.434824E+09 | 553.03 | 13-DEC-06:00 | 497.73 | 497.73 | 47.94 | 1.16 |
Annual Sum or Average | 0.263486E+10 | 0.237138E+10 | ||||||
Minimum of Months | 1203462.12 | 1083115.91 | 171.88 | 154.69 | 154.69 | 35.01 | 0.20 | |
Maximum of Months | 0.502910E+09 | 0.452619E+09 | 569.47 | 512.52 | 512.52 | 54.80 | 1.29 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.295260E+10 | 0.265734E+10 | 3792.99 | 24-JAN-16:02 | 3413.69 | 3413.69 | 7.17 | 12.21 |
February | 0.219547E+10 | 0.197592E+10 | 3530.89 | 01-FEB-13:10 | 3177.80 | 3177.80 | 7.24 | 9.77 |
March | 0.207627E+10 | 0.186864E+10 | 3701.48 | 23-MAR-15:02 | 3331.34 | 3331.34 | 7.45 | 11.21 |
April | 0.367501E+10 | 0.330751E+10 | 3601.48 | 26-APR-17:00 | 3241.33 | 3241.33 | 7.44 | 10.31 |
May | 0.395900E+10 | 0.356310E+10 | 3768.31 | 18-MAY-15:03 | 3391.48 | 3391.48 | 7.46 | 11.92 |
June | 0.532553E+10 | 0.479298E+10 | 4030.46 | 29-JUN-18:03 | 3627.42 | 3627.42 | 7.50 | 15.87 |
July | 0.745899E+10 | 0.671309E+10 | 4178.80 | 31-JUL-18:03 | 3760.92 | 3760.92 | 7.33 | 18.08 |
August | 0.790971E+10 | 0.711874E+10 | 4082.54 | 14-AUG-18:03 | 3674.28 | 3674.28 | 7.46 | 16.72 |
September | 0.612029E+10 | 0.550826E+10 | 4463.59 | 29-SEP-15:25 | 4017.23 | 4017.23 | 6.73 | 20.77 |
October | 0.631495E+10 | 0.568346E+10 | 4228.68 | 16-OCT-18:05 | 3805.81 | 3805.81 | 7.16 | 18.67 |
November | 0.323092E+10 | 0.290783E+10 | 3972.65 | 19-NOV-11:00 | 3575.39 | 3575.39 | 6.84 | 14.88 |
December | 0.299568E+10 | 0.269612E+10 | 3536.79 | 05-DEC-09:02 | 3183.11 | 3183.11 | 7.12 | 9.81 |
Annual Sum or Average | 0.542144E+11 | 0.487930E+11 | ||||||
Minimum of Months | 0.207627E+10 | 0.186864E+10 | 3530.89 | 3177.80 | 3177.80 | 6.73 | 9.77 | |
Maximum of Months | 0.790971E+10 | 0.711874E+10 | 4463.59 | 4017.23 | 4017.23 | 7.50 | 20.77 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.784397E+10 | 0.705958E+10 | 3479.56 | 01-JAN-07:30 | 3131.60 | 3131.60 | 8.41 | 24.39 |
February | 0.698435E+10 | 0.628591E+10 | 3479.56 | 01-FEB-00:03 | 3131.60 | 3131.60 | 8.44 | 24.39 |
March | 0.721744E+10 | 0.649570E+10 | 3479.56 | 01-MAR-07:05 | 3131.60 | 3131.60 | 8.41 | 24.39 |
April | 0.867559E+10 | 0.780803E+10 | 3479.56 | 01-APR-06:40 | 3131.60 | 3131.60 | 8.42 | 24.39 |
May | 0.915438E+10 | 0.823894E+10 | 3479.56 | 01-MAY-00:05 | 3131.60 | 3131.60 | 8.70 | 24.39 |
June | 0.900858E+10 | 0.810773E+10 | 3479.56 | 01-JUN-00:05 | 3131.60 | 3131.60 | 8.51 | 24.39 |
July | 0.931966E+10 | 0.838769E+10 | 3479.56 | 01-JUL-00:10 | 3131.60 | 3131.60 | 9.16 | 24.39 |
August | 0.931966E+10 | 0.838769E+10 | 3479.56 | 01-AUG-00:05 | 3131.60 | 3131.60 | 9.71 | 24.39 |
September | 0.901276E+10 | 0.811148E+10 | 3479.56 | 01-SEP-00:05 | 3131.60 | 3131.60 | 8.80 | 24.39 |
October | 0.929669E+10 | 0.836702E+10 | 3479.56 | 01-OCT-00:10 | 3131.60 | 3131.60 | 9.84 | 24.39 |
November | 0.837756E+10 | 0.753981E+10 | 3479.56 | 01-NOV-00:05 | 3131.60 | 3131.60 | 8.61 | 24.39 |
December | 0.799881E+10 | 0.719893E+10 | 3479.56 | 01-DEC-00:03 | 3131.60 | 3131.60 | 8.45 | 24.39 |
Annual Sum or Average | 0.102209E+12 | 0.919885E+11 | ||||||
Minimum of Months | 0.698435E+10 | 0.628591E+10 | 3479.56 | 3131.60 | 3131.60 | 8.41 | 24.39 | |
Maximum of Months | 0.931966E+10 | 0.838769E+10 | 3479.56 | 3131.60 | 3131.60 | 9.84 | 24.39 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 50.01 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 50.13 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 49.69 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.74 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 52.90 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 52.42 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.44 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 53.26 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 53.21 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 51.95 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 52.92 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 50.44 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 49.69 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.44 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 43.34 | 79.60 | 45336.02 | 181927.27 | 08-JAN-07:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 32.10 | 79.40 | 34937.89 | 151955.47 | 04-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 45.02 | 79.80 | 45373.33 | 185956.25 | 29-MAR-08:62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 42.09 | 79.46 | 17447.24 | 136896.41 | 01-APR-06:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 36.19 | 36.19 | 14701.16 | 116742.77 | 14-MAY-04:50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.41 | 79.40 | 2441.02 | 63382.46 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 29.46 | 29.46 | 156.90 | 33541.50 | 18-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 52.07 | 52.07 | 66.63 | 31740.51 | 29-AUG-18:05 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 41.20 | 41.20 | 1164.91 | 59258.40 | 20-SEP-04:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.74 | 53.74 | 6039.08 | 97168.53 | 29-OCT-06:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 31.52 | 31.52 | 26747.03 | 144072.18 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 35.38 | 79.40 | 43040.82 | 156372.34 | 23-DEC-06:00 |
Annual Sum or Average | 0.00 | 19749.04 | ||||||
Minimum of Months | 0.00 | 0.00 | 26.41 | 29.46 | 66.63 | 31740.51 | ||
Maximum of Months | 0.00 | 0.00 | 53.74 | 79.80 | 45373.33 | 185956.25 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 43697.86 | 301569.72 | 14-JAN-11:33 | 9.76 | 6.81 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30913.37 | 283067.89 | 01-FEB-09:02 | 10.13 | 7.36 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 28127.59 | 319709.88 | 23-MAR-15:02 | 10.56 | 7.43 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 58331.92 | 310300.87 | 26-APR-10:45 | 9.89 | 6.86 | 0.00 | 0.00 | 01-APR-00:10 |
May | 58510.11 | 349838.88 | 18-MAY-15:02 | 10.86 | 7.43 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 104347.26 | 468120.75 | 29-JUN-18:03 | 12.07 | 7.48 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 190386.04 | 547707.06 | 31-JUL-18:03 | 12.67 | 7.31 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 212533.24 | 548150.58 | 18-AUG-15:03 | 12.10 | 6.73 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 138145.82 | 501377.32 | 29-SEP-15:02 | 11.61 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 149573.66 | 525519.36 | 14-OCT-15:02 | 11.84 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 48249.55 | 357548.61 | 19-NOV-09:02 | 10.55 | 7.06 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 49382.42 | 334891.99 | 05-DEC-09:02 | 10.33 | 7.06 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 93250.27 | 0.00 | ||||||
Minimum of Months | 28127.59 | 283067.89 | 9.76 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 212533.24 | 548150.58 | 12.67 | 7.48 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 50.01 | 59.50 | 24241.71 | 49031.35 | 31-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 50.13 | 59.59 | 24271.54 | 49034.02 | 01-FEB-07:30 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 49.69 | 58.14 | 24039.58 | 48751.99 | 01-MAR-07:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.74 | 58.98 | 23559.33 | 47892.22 | 04-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 52.90 | 59.79 | 22999.63 | 46886.13 | 02-MAY-06:45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 52.42 | 58.33 | 22503.26 | 45690.28 | 01-JUN-06:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.44 | 59.55 | 22173.39 | 44779.11 | 03-JUL-06:15 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 53.26 | 59.69 | 22161.83 | 44690.92 | 31-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 53.21 | 59.59 | 22406.70 | 45422.39 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 51.95 | 58.47 | 22870.18 | 46574.03 | 31-OCT-06:30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 52.92 | 59.47 | 23433.60 | 47721.50 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 50.44 | 59.02 | 23932.85 | 48581.99 | 29-DEC-07:40 |
Annual Sum or Average | 0.00 | 23210.09 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.69 | 58.14 | 22161.83 | 44690.92 | ||
Maximum of Months | 0.00 | 0.00 | 53.44 | 59.79 | 24271.54 | 49034.02 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.998511E+11 | 0.00 | 0.572450E+11 | 0.362558E+11 | 0.00 | 0.00 |
February | 0.691391E+11 | 0.00 | 0.316038E+11 | 0.327383E+11 | 0.00 | 0.00 |
March | 0.100025E+12 | 0.00 | 0.353233E+11 | 0.360980E+11 | 0.00 | 0.00 |
April | 0.373880E+11 | 0.00 | 0.843398E+11 | 0.357103E+11 | 0.00 | 0.00 |
May | 0.326769E+11 | 0.00 | 0.901865E+11 | 0.371815E+11 | 0.00 | 0.00 |
June | 0.516107E+10 | 0.00 | 0.168634E+12 | 0.368371E+11 | 0.00 | 0.00 |
July | 0.298507E+09 | 0.00 | 0.346290E+12 | 0.386167E+11 | 0.00 | 0.00 |
August | 89949969.18 | 0.00 | 0.390374E+12 | 0.388967E+11 | 0.00 | 0.00 |
September | 0.238306E+10 | 0.00 | 0.229545E+12 | 0.370456E+11 | 0.00 | 0.00 |
October | 0.134868E+11 | 0.00 | 0.260389E+12 | 0.389313E+11 | 0.00 | 0.00 |
November | 0.571649E+11 | 0.00 | 0.593969E+11 | 0.358542E+11 | 0.00 | 0.00 |
December | 0.953626E+11 | 0.00 | 0.661316E+11 | 0.366770E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.513027E+12 | 0.00 | 0.181946E+13 | 0.440843E+12 | 0.00 | 0.00 |
Minimum of Months | 89949969.18 | 0.00 | 0.316038E+11 | 0.327383E+11 | 0.00 | 0.00 |
Maximum of Months | 0.100025E+12 | 0.00 | 0.390374E+12 | 0.389313E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.147285E+11 | 0.00 | 0.113067E+11 | 0.587890E+10 | 0.00 | 0.00 |
February | 0.118617E+11 | 0.00 | 0.624901E+10 | 0.530997E+10 | 0.00 | 0.00 |
March | 0.159855E+11 | 0.00 | 0.724922E+10 | 0.587890E+10 | 0.00 | 0.00 |
April | 0.718571E+10 | 0.00 | 0.170527E+11 | 0.568926E+10 | 0.00 | 0.00 |
May | 0.618449E+10 | 0.00 | 0.176695E+11 | 0.587890E+10 | 0.00 | 0.00 |
June | 0.108226E+10 | 0.00 | 0.354046E+11 | 0.568926E+10 | 0.00 | 0.00 |
July | 62562347.84 | 0.00 | 0.697043E+11 | 0.587890E+10 | 0.00 | 0.00 |
August | 29890880.57 | 0.00 | 0.780509E+11 | 0.587890E+10 | 0.00 | 0.00 |
September | 0.542137E+09 | 0.00 | 0.472441E+11 | 0.568926E+10 | 0.00 | 0.00 |
October | 0.245036E+10 | 0.00 | 0.510747E+11 | 0.587890E+10 | 0.00 | 0.00 |
November | 0.100455E+11 | 0.00 | 0.116003E+11 | 0.568926E+10 | 0.00 | 0.00 |
December | 0.146291E+11 | 0.00 | 0.131328E+11 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.847876E+11 | 0.00 | 0.365739E+12 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 29890880.57 | 0.00 | 0.624901E+10 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 0.159855E+11 | 0.00 | 0.780509E+11 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.362558E+11 | 0.572450E+11 | 0.998511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.327383E+11 | 0.316038E+11 | 0.691391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.360980E+11 | 0.353233E+11 | 0.100025E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.357103E+11 | 0.843398E+11 | 0.373880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.371815E+11 | 0.901865E+11 | 0.326769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.368371E+11 | 0.168634E+12 | 0.516107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.386167E+11 | 0.346290E+12 | 0.298507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.388967E+11 | 0.390374E+12 | 89949969.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.370456E+11 | 0.229545E+12 | 0.238306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.389313E+11 | 0.260389E+12 | 0.134868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.358542E+11 | 0.593969E+11 | 0.571649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.366770E+11 | 0.661316E+11 | 0.953626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.440843E+12 | 0.181946E+13 | 0.513027E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.327383E+11 | 0.316038E+11 | 89949969.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.389313E+11 | 0.390374E+12 | 0.100025E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.113067E+11 | 0.147285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.624901E+10 | 0.118617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.724922E+10 | 0.159855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.170527E+11 | 0.718571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.176695E+11 | 0.618449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.354046E+11 | 0.108226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.697043E+11 | 62562347.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.780509E+11 | 29890880.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.472441E+11 | 0.542137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.510747E+11 | 0.245036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.116003E+11 | 0.100455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.131328E+11 | 0.146291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.365739E+12 | 0.847876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.624901E+10 | 29890880.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.780509E+11 | 0.159855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.362558E+11 | 0.998511E+11 | 0.572450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.327383E+11 | 0.691391E+11 | 0.316038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.360980E+11 | 0.100025E+12 | 0.353233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.357103E+11 | 0.373880E+11 | 0.843398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.371815E+11 | 0.326769E+11 | 0.901865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.368371E+11 | 0.516107E+10 | 0.168634E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.386167E+11 | 0.298507E+09 | 0.346290E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.388967E+11 | 89949969.18 | 0.390374E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.370456E+11 | 0.238306E+10 | 0.229545E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.389313E+11 | 0.134868E+11 | 0.260389E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.358542E+11 | 0.571649E+11 | 0.593969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.366770E+11 | 0.953626E+11 | 0.661316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.440843E+12 | 0.513027E+12 | 0.181946E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.327383E+11 | 89949969.18 | 0.316038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.389313E+11 | 0.100025E+12 | 0.390374E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 0.147285E+11 | 0.113067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.118617E+11 | 0.624901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.159855E+11 | 0.724922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.718571E+10 | 0.170527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.618449E+10 | 0.176695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.108226E+10 | 0.354046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 62562347.84 | 0.697043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 29890880.57 | 0.780509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.542137E+09 | 0.472441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.245036E+10 | 0.510747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.100455E+11 | 0.116003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.146291E+11 | 0.131328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.847876E+11 | 0.365739E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 29890880.57 | 0.624901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.159855E+11 | 0.780509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.252795E+11 | 0.00 | 0.00 | 14605869.98 | 62937718.79 | 0.00 | 0.302347E+11 | 0.00 | 1.02 |
February | 0.435853E+11 | 0.00 | 0.00 | 1361383.41 | 13544443.32 | 0.00 | 0.505670E+10 | 0.00 | 1.01 |
March | 0.556806E+11 | 0.00 | 0.00 | 9501.82 | 290032.42 | 0.00 | 0.215327E+09 | 0.00 | 1.01 |
April | 0.436268E+11 | 0.00 | 0.00 | 0.00 | 73733317.84 | 0.00 | 0.00 | 0.00 | 1.01 |
May | 0.439281E+11 | 0.00 | 0.00 | 0.00 | 9904590.58 | 0.00 | 0.00 | 0.00 | 1.01 |
June | 0.327849E+11 | 0.00 | 0.00 | 0.00 | 0.565800E+09 | 0.00 | 0.00 | 0.00 | 1.02 |
July | 0.197863E+11 | 2021865.09 | 0.00 | 555365.11 | 0.460641E+10 | 0.00 | 0.143257E+10 | 0.00 | 1.03 |
August | 0.157542E+11 | 0.00 | 0.00 | 1373309.25 | 0.556426E+10 | 0.00 | 0.225884E+10 | 0.00 | 1.03 |
September | 0.196293E+11 | 84174451.02 | 0.00 | 7165871.74 | 0.164352E+10 | 0.00 | 0.906109E+10 | 0.00 | 1.03 |
October | 0.659989E+10 | 0.200549E+09 | 0.00 | 18437867.50 | 0.284469E+10 | 0.00 | 0.240687E+11 | 0.00 | 1.04 |
November | 0.127990E+11 | 7011331.64 | 0.00 | 24385243.97 | 39472057.09 | 0.00 | 0.374508E+11 | 0.00 | 1.04 |
December | 0.189867E+11 | 0.00 | 0.00 | 16678430.60 | 22866902.55 | 0.00 | 0.353476E+11 | 0.00 | 1.03 |
Annual Sum or Average | 0.338441E+12 | 0.293756E+09 | 0.00 | 84572843.38 | 0.154474E+11 | 0.00 | 0.145126E+12 | 0.00 | 1.02 |
Minimum of Months | 0.659989E+10 | 0.00 | 0.00 | 0.00 | 290032.42 | 0.00 | 0.00 | 0.00 | 1.01 |
Maximum of Months | 0.556806E+11 | 0.200549E+09 | 0.00 | 24385243.97 | 0.556426E+10 | 0.00 | 0.374508E+11 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.649396E+10 | 12004624.86 | 0.00 | 2025425.69 | 273225.17 | 0.00 | 0.863151E+09 | 0.00 | 2.51 |
February | 0.592487E+10 | 2336847.59 | 0.00 | 1289673.53 | 0.00 | 0.00 | 0.542000E+09 | 0.00 | 2.46 |
March | 0.712254E+10 | 10880.96 | 0.00 | 551836.49 | 27467.04 | 27905912.43 | 0.241903E+09 | 0.00 | 2.42 |
April | 0.562498E+10 | 4921349.68 | 0.00 | 174715.92 | 4827648.89 | 0.00 | 0.143167E+09 | 0.00 | 2.42 |
May | 0.580452E+10 | 676221.03 | 0.00 | 6046.58 | 633361.15 | 0.00 | 3630564.07 | 0.00 | 2.43 |
June | 0.433481E+10 | 0.00 | 0.00 | 0.00 | 74809972.52 | 0.00 | 0.00 | 0.00 | 2.45 |
July | 0.280084E+10 | 0.115362E+09 | 0.00 | 3452.48 | 0.493963E+09 | 0.00 | 4782898.97 | 0.00 | 2.47 |
August | 0.228834E+10 | 0.383154E+09 | 0.00 | 89925.06 | 0.352551E+09 | 0.00 | 93428376.77 | 0.00 | 2.47 |
September | 0.333910E+10 | 0.186628E+09 | 0.00 | 860364.70 | 84195456.17 | 0.00 | 0.453850E+09 | 0.00 | 2.50 |
October | 0.329887E+10 | 0.445662E+09 | 0.00 | 1739149.68 | 94595891.96 | 0.00 | 0.711152E+09 | 0.00 | 2.62 |
November | 0.579553E+10 | 9777072.00 | 0.00 | 2091875.17 | 0.00 | 0.00 | 0.763647E+09 | 0.00 | 2.52 |
December | 0.630322E+10 | 4687139.06 | 0.00 | 2863435.20 | 0.00 | 0.00 | 0.892774E+09 | 0.00 | 2.56 |
Annual Sum or Average | 0.591316E+11 | 0.116522E+10 | 0.00 | 11695900.51 | 0.110588E+10 | 27905912.43 | 0.471348E+10 | 0.00 | 2.49 |
Minimum of Months | 0.228834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 |
Maximum of Months | 0.712254E+10 | 0.445662E+09 | 0.00 | 2863435.20 | 0.493963E+09 | 27905912.43 | 0.892774E+09 | 0.00 | 2.62 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.445563E+10 | 0.00 | 0.00 | 332758.13 | 6117403.82 | 0.00 | 0.884378E+09 | 0.00 | 1.54 |
February | 0.396830E+10 | 0.00 | 0.00 | 320834.90 | 1316489.24 | 0.00 | 0.760288E+09 | 0.00 | 1.54 |
March | 0.481461E+10 | 0.00 | 0.00 | 243538.00 | 28190.49 | 0.00 | 0.619387E+09 | 0.00 | 1.54 |
April | 0.317153E+10 | 0.00 | 0.00 | 600347.92 | 7166711.61 | 0.00 | 0.107481E+10 | 0.00 | 1.55 |
May | 0.331134E+10 | 0.00 | 0.00 | 501391.88 | 962703.79 | 0.00 | 0.961726E+09 | 0.00 | 1.55 |
June | 0.192969E+10 | 828940.57 | 0.00 | 908845.89 | 54165579.63 | 0.00 | 0.126903E+10 | 0.00 | 1.57 |
July | 0.672774E+09 | 20231136.47 | 0.00 | 1541533.28 | 0.427815E+09 | 0.00 | 0.141065E+10 | 0.00 | 1.59 |
August | 0.366987E+09 | 12173589.04 | 0.00 | 1913449.26 | 0.528678E+09 | 0.00 | 0.141851E+10 | 0.00 | 1.60 |
September | 0.123577E+10 | 44639808.16 | 0.00 | 1453432.59 | 0.123360E+09 | 0.00 | 0.158333E+10 | 0.00 | 1.59 |
October | 0.144678E+10 | 0.118131E+09 | 0.00 | 1603192.58 | 0.177759E+09 | 0.00 | 0.152690E+10 | 0.00 | 1.59 |
November | 0.360030E+10 | 0.00 | 0.00 | 589784.10 | 4518080.18 | 0.00 | 0.116232E+10 | 0.00 | 1.54 |
December | 0.419206E+10 | 0.00 | 0.00 | 463582.22 | 2222611.17 | 0.00 | 0.102308E+10 | 0.00 | 1.54 |
Annual Sum or Average | 0.331658E+11 | 0.196005E+09 | 0.00 | 10472690.76 | 0.133411E+10 | 0.00 | 0.136944E+11 | 0.00 | 1.56 |
Minimum of Months | 0.366987E+09 | 0.00 | 0.00 | 243538.00 | 28190.49 | 0.00 | 0.619387E+09 | 0.00 | 1.54 |
Maximum of Months | 0.481461E+10 | 0.118131E+09 | 0.00 | 1913449.26 | 0.528678E+09 | 0.00 | 0.158333E+10 | 0.00 | 1.60 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.506338E+10 | 0.00 | 0.00 | 0.00 | 5800212.61 | 0.00 | 0.00 | 0.00 | 0.69 |
February | 0.448240E+10 | 0.00 | 0.00 | 0.00 | 1248228.45 | 0.00 | 0.00 | 0.00 | 0.69 |
March | 0.515126E+10 | 0.00 | 0.00 | 0.00 | 26728.80 | 0.00 | 0.00 | 0.00 | 0.69 |
April | 0.402056E+10 | 0.00 | 0.00 | 0.00 | 6795113.14 | 0.00 | 0.00 | 0.00 | 0.69 |
May | 0.404832E+10 | 0.00 | 0.00 | 0.00 | 912786.99 | 0.00 | 0.00 | 0.00 | 0.69 |
June | 0.300215E+10 | 0.00 | 0.00 | 3371.07 | 52143019.95 | 0.00 | 19235126.93 | 0.00 | 0.70 |
July | 0.189766E+10 | 1197884.56 | 0.00 | 59150.55 | 0.423506E+09 | 0.00 | 57815428.45 | 0.00 | 0.70 |
August | 0.158836E+10 | 0.00 | 0.00 | 48967.09 | 0.512791E+09 | 0.00 | 71767543.34 | 0.00 | 0.70 |
September | 0.263284E+10 | 136341.26 | 0.00 | 33530.51 | 0.158954E+09 | 0.00 | 9337482.32 | 0.00 | 0.70 |
October | 0.269340E+10 | 6275720.41 | 0.00 | 96910.99 | 0.273856E+09 | 0.00 | 83678373.05 | 0.00 | 0.70 |
November | 0.451432E+10 | 0.00 | 0.00 | 0.00 | 4283814.90 | 0.00 | 0.00 | 0.00 | 0.69 |
December | 0.494209E+10 | 0.00 | 0.00 | 0.00 | 2107367.39 | 0.00 | 0.00 | 0.00 | 0.69 |
Annual Sum or Average | 0.440367E+11 | 7609946.23 | 0.00 | 241930.21 | 0.144242E+10 | 0.00 | 0.241834E+09 | 0.00 | 0.70 |
Minimum of Months | 0.158836E+10 | 0.00 | 0.00 | 0.00 | 26728.80 | 0.00 | 0.00 | 0.00 | 0.69 |
Maximum of Months | 0.515126E+10 | 6275720.41 | 0.00 | 96910.99 | 0.512791E+09 | 0.00 | 83678373.05 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.240835E+10 | 0.00 | 0.00 | 0.00 | 2758814.13 | 0.00 | 0.00 | 0.00 | 0.57 |
February | 0.213201E+10 | 0.00 | 0.00 | 0.00 | 593707.60 | 0.00 | 0.00 | 0.00 | 0.57 |
March | 0.245015E+10 | 0.00 | 0.00 | 0.00 | 12713.29 | 0.00 | 0.00 | 0.00 | 0.57 |
April | 0.191234E+10 | 0.00 | 0.00 | 0.00 | 3232028.79 | 0.00 | 0.00 | 0.00 | 0.57 |
May | 0.192554E+10 | 0.00 | 0.00 | 0.00 | 434158.16 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.143710E+10 | 0.00 | 0.00 | 0.00 | 24801315.09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.930132E+09 | 0.00 | 0.00 | 0.00 | 0.202006E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.789645E+09 | 0.00 | 0.00 | 0.00 | 0.243904E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.125674E+10 | 0.00 | 0.00 | 0.00 | 75669847.04 | 0.00 | 0.00 | 0.00 | 0.58 |
October | 0.132057E+10 | 0.00 | 0.00 | 0.00 | 0.133242E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
November | 0.214719E+10 | 0.00 | 0.00 | 0.00 | 2037554.46 | 0.00 | 0.00 | 0.00 | 0.57 |
December | 0.235066E+10 | 0.00 | 0.00 | 0.00 | 1002348.59 | 0.00 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.210604E+11 | 0.00 | 0.00 | 0.00 | 0.689695E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
Minimum of Months | 0.789645E+09 | 0.00 | 0.00 | 0.00 | 12713.29 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.245015E+10 | 0.00 | 0.00 | 0.00 | 0.243904E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.311327E+09 | 84664949.65 | 0.00 | 91710746.82 | 0.00 | 0.00 | 0.842604E+11 | 0.00 | 23.96 |
February | 0.233773E+09 | 18220228.41 | 0.00 | 82459208.03 | 0.00 | 0.00 | 0.745606E+11 | 0.00 | 23.97 |
March | 0.251804E+09 | 390156.82 | 0.00 | 90173039.33 | 0.00 | 0.00 | 0.857987E+11 | 0.00 | 23.95 |
April | 0.200734E+09 | 99187383.37 | 0.00 | 91255809.29 | 0.00 | 0.00 | 0.671629E+11 | 0.00 | 23.96 |
May | 0.205041E+09 | 13323833.13 | 0.00 | 95445874.97 | 0.00 | 0.00 | 0.676970E+11 | 0.00 | 24.06 |
June | 63504400.44 | 0.768452E+09 | 0.00 | 90407850.18 | 293715.61 | 0.00 | 0.508913E+11 | 0.00 | 24.34 |
July | 20908348.92 | 0.637155E+10 | 0.00 | 76242636.72 | 11983549.68 | 0.00 | 0.323115E+11 | 0.00 | 24.35 |
August | 1278036.10 | 0.758840E+10 | 0.00 | 71234797.92 | 20586001.27 | 0.00 | 0.278308E+11 | 0.00 | 24.49 |
September | 55700000.97 | 0.237497E+10 | 0.00 | 83457719.18 | 0.00 | 0.00 | 0.441218E+11 | 0.00 | 24.41 |
October | 0.115742E+09 | 0.420952E+10 | 0.00 | 79652875.11 | 15250711.79 | 0.00 | 0.464774E+11 | 0.00 | 24.30 |
November | 0.240724E+09 | 62530289.34 | 0.00 | 89585019.31 | 0.00 | 0.00 | 0.753081E+11 | 0.00 | 24.02 |
December | 0.277834E+09 | 31056934.95 | 0.00 | 92461165.39 | 0.00 | 0.00 | 0.824910E+11 | 0.00 | 23.98 |
Annual Sum or Average | 0.197837E+10 | 0.216223E+11 | 0.00 | 0.103409E+10 | 48113978.36 | 0.00 | 0.738912E+12 | 0.00 | 24.15 |
Minimum of Months | 1278036.10 | 390156.82 | 0.00 | 71234797.92 | 0.00 | 0.00 | 0.278308E+11 | 0.00 | 23.95 |
Maximum of Months | 0.311327E+09 | 0.758840E+10 | 0.00 | 95445874.97 | 20586001.27 | 0.00 | 0.857987E+11 | 0.00 | 24.49 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.649645E+10 | 47901849.94 | 0.00 | 23561113.17 | 879752.94 | 0.00 | 0.251357E+11 | 0.00 | 3.84 |
February | 0.769594E+10 | 9240496.70 | 0.00 | 17264881.55 | 0.00 | 0.00 | 0.200993E+11 | 0.00 | 3.77 |
March | 0.121364E+11 | 164404.10 | 0.00 | 12439078.31 | 0.00 | 0.00 | 0.195666E+11 | 0.00 | 3.71 |
April | 0.651984E+10 | 31891217.90 | 0.00 | 12894488.30 | 9904316.53 | 0.00 | 0.182198E+11 | 0.00 | 3.71 |
May | 0.874534E+10 | 2899068.99 | 0.00 | 9095293.92 | 2715321.75 | 0.00 | 0.161635E+11 | 0.00 | 3.72 |
June | 0.467529E+10 | 39487065.63 | 0.00 | 11781366.44 | 0.281235E+09 | 0.00 | 0.139110E+11 | 0.00 | 3.76 |
July | 0.169776E+10 | 0.174737E+10 | 0.00 | 14789743.92 | 0.864911E+09 | 0.00 | 0.103555E+11 | 0.00 | 3.79 |
August | 0.817796E+09 | 0.246046E+10 | 0.00 | 17965161.88 | 0.693627E+09 | 0.00 | 0.951056E+10 | 0.00 | 3.82 |
September | 0.191435E+10 | 0.856664E+09 | 0.00 | 21246578.16 | 0.220065E+09 | 0.00 | 0.145351E+11 | 0.00 | 3.85 |
October | 0.191200E+10 | 0.190629E+10 | 0.00 | 25361851.15 | 0.154476E+09 | 0.00 | 0.157187E+11 | 0.00 | 4.00 |
November | 0.356617E+10 | 38110984.42 | 0.00 | 25423415.44 | 0.00 | 0.00 | 0.246779E+11 | 0.00 | 3.86 |
December | 0.484691E+10 | 17849854.73 | 0.00 | 28049321.08 | 0.00 | 0.00 | 0.261756E+11 | 0.00 | 3.92 |
Annual Sum or Average | 0.610242E+11 | 0.715832E+10 | 0.00 | 0.219872E+09 | 0.222781E+10 | 0.00 | 0.214069E+12 | 0.00 | 3.81 |
Minimum of Months | 0.817796E+09 | 164404.10 | 0.00 | 9095293.92 | 0.00 | 0.00 | 0.951056E+10 | 0.00 | 3.71 |
Maximum of Months | 0.121364E+11 | 0.246046E+10 | 0.00 | 28049321.08 | 0.864911E+09 | 0.00 | 0.261756E+11 | 0.00 | 4.00 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.372521E+11 | 89847027.15 | 0.00 | 42641057.80 | 25968239.34 | 0.00 | 0.649341E+11 | 0.00 | 1.76 |
February | 0.341548E+11 | 15120162.10 | 0.00 | 36123395.18 | 9803736.36 | 0.00 | 0.563173E+11 | 0.00 | 1.75 |
March | 0.481980E+11 | 0.00 | 0.00 | 30696740.68 | 533705.10 | 0.00 | 0.551570E+11 | 0.00 | 1.74 |
April | 0.281238E+11 | 0.00 | 0.00 | 42065480.66 | 0.135681E+09 | 0.00 | 0.531065E+11 | 0.00 | 1.76 |
May | 0.277610E+11 | 0.00 | 0.00 | 42792517.46 | 18225998.96 | 0.00 | 0.538795E+11 | 0.00 | 1.76 |
June | 0.142067E+11 | 17581138.98 | 0.00 | 55625273.33 | 0.102358E+10 | 0.00 | 0.475255E+11 | 0.00 | 1.80 |
July | 0.481357E+10 | 0.130461E+10 | 0.00 | 66741328.17 | 0.717924E+10 | 0.00 | 0.358954E+11 | 0.00 | 1.83 |
August | 0.254879E+10 | 0.211555E+10 | 0.00 | 71200709.09 | 0.812462E+10 | 0.00 | 0.328558E+11 | 0.00 | 1.85 |
September | 0.823700E+10 | 0.166331E+10 | 0.00 | 66767783.46 | 0.154700E+10 | 0.00 | 0.469418E+11 | 0.00 | 1.84 |
October | 0.733725E+10 | 0.419561E+10 | 0.00 | 73755500.10 | 0.143894E+10 | 0.00 | 0.516229E+11 | 0.00 | 1.86 |
November | 0.203884E+11 | 85836675.74 | 0.00 | 54804193.79 | 683117.46 | 0.00 | 0.716094E+11 | 0.00 | 1.77 |
December | 0.256870E+11 | 33428616.93 | 0.00 | 52814873.46 | 8650067.57 | 0.00 | 0.746994E+11 | 0.00 | 1.77 |
Annual Sum or Average | 0.258708E+12 | 0.952089E+10 | 0.00 | 0.636029E+09 | 0.195129E+11 | 0.00 | 0.644545E+12 | 0.00 | 1.79 |
Minimum of Months | 0.254879E+10 | 0.00 | 0.00 | 30696740.68 | 533705.10 | 0.00 | 0.328558E+11 | 0.00 | 1.74 |
Maximum of Months | 0.481980E+11 | 0.419561E+10 | 0.00 | 73755500.10 | 0.812462E+10 | 0.00 | 0.746994E+11 | 0.00 | 1.86 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.246619E+09 | 11627008.99 | 0.00 | 5788794.55 | 5885317.94 | 0.633931E+09 | 0.117242E+10 | 0.00 | 0.47 |
February | 0.287303E+09 | 3662442.99 | 0.00 | 5286647.38 | 801606.20 | 0.432231E+09 | 0.110113E+10 | 0.00 | 0.47 |
March | 0.364014E+09 | 7265418.93 | 0.00 | 5124783.11 | 2288715.22 | 0.650292E+09 | 0.108763E+10 | 0.00 | 0.47 |
April | 0.186008E+09 | 17560880.94 | 0.00 | 9100473.02 | 6138085.31 | 77770692.49 | 0.123162E+10 | 0.00 | 0.47 |
May | 0.181806E+09 | 3354438.57 | 0.00 | 9356653.08 | 4373528.07 | 70282696.78 | 0.118900E+10 | 0.00 | 0.47 |
June | 85834702.83 | 81524684.34 | 0.00 | 9040103.43 | 28697615.05 | 945561.22 | 0.737117E+09 | 0.00 | 0.48 |
July | 20118790.23 | 0.368732E+09 | 209586.71 | 6486828.64 | 61659869.54 | 266188.34 | 0.318401E+09 | 11555.18 | 0.48 |
August | 17841322.63 | 0.482175E+09 | 354410.14 | 5733474.45 | 65240395.45 | 132986.28 | 0.243960E+09 | 16733.73 | 0.48 |
September | 69042000.22 | 0.189384E+09 | 81239.70 | 8125525.56 | 29085111.60 | 1237265.11 | 0.621707E+09 | 2618.92 | 0.48 |
October | 87556665.12 | 0.308345E+09 | 296171.50 | 6808469.73 | 29327078.02 | 7204306.77 | 0.822380E+09 | 14672.56 | 0.48 |
November | 0.211530E+09 | 11860928.75 | 2108.23 | 7333418.64 | 2167096.02 | 0.234851E+09 | 0.133165E+10 | 2122.07 | 0.47 |
December | 0.246559E+09 | 11846448.36 | 5245.66 | 6478415.17 | 2316323.72 | 0.529948E+09 | 0.121598E+10 | 1323.66 | 0.47 |
Annual Sum or Average | 0.200423E+10 | 0.149734E+10 | 948761.93 | 84663586.75 | 0.237981E+09 | 0.263909E+10 | 0.110730E+11 | 49026.11 | 0.47 |
Minimum of Months | 17841322.63 | 3354438.57 | 0.00 | 5124783.11 | 801606.20 | 132986.28 | 0.243960E+09 | 0.00 | 0.47 |
Maximum of Months | 0.364014E+09 | 0.482175E+09 | 354410.14 | 9356653.08 | 65240395.45 | 0.650292E+09 | 0.133165E+10 | 16733.73 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.327669E+09 | 6241164.38 | 4805.43 | 2180630.94 | 11260339.04 | 0.104755E+10 | 0.681111E+09 | 3966.24 | 0.47 |
February | 0.330353E+09 | 1151521.65 | 0.00 | 2579222.68 | 3312004.52 | 0.726149E+09 | 0.766656E+09 | 0.00 | 0.47 |
March | 0.394589E+09 | 3742374.45 | 0.00 | 3154145.90 | 5810640.29 | 0.817774E+09 | 0.891298E+09 | 0.00 | 0.47 |
April | 0.208233E+09 | 10565681.54 | 0.00 | 7460564.18 | 13130508.03 | 0.113880E+09 | 0.117475E+10 | 0.00 | 0.47 |
May | 0.188365E+09 | 2947130.59 | 0.00 | 9053842.99 | 4779930.60 | 73677338.63 | 0.117918E+10 | 0.00 | 0.47 |
June | 86745694.66 | 74569969.69 | 0.00 | 9224532.87 | 35639415.54 | 884480.93 | 0.735985E+09 | 0.00 | 0.48 |
July | 20054733.45 | 0.356014E+09 | 228083.57 | 6544628.66 | 74308179.86 | 193407.00 | 0.318440E+09 | 12460.43 | 0.48 |
August | 18817656.68 | 0.436720E+09 | 354194.86 | 5303140.88 | 0.110631E+09 | 238808.53 | 0.243276E+09 | 16905.52 | 0.48 |
September | 78155749.88 | 0.156882E+09 | 92427.89 | 6670210.33 | 61548552.20 | 1309134.89 | 0.613895E+09 | 4172.86 | 0.48 |
October | 95173035.02 | 0.268673E+09 | 357022.52 | 4751334.05 | 68899716.92 | 53588935.71 | 0.770328E+09 | 13704.41 | 0.48 |
November | 0.268412E+09 | 7328982.74 | 734.68 | 3458809.07 | 6699444.72 | 0.521503E+09 | 0.991782E+09 | 1448.85 | 0.47 |
December | 0.309019E+09 | 5541624.25 | 3078.17 | 2398737.42 | 8621089.97 | 0.977180E+09 | 0.710138E+09 | 1888.86 | 0.47 |
Annual Sum or Average | 0.232559E+10 | 0.133038E+10 | 1040347.12 | 62779799.97 | 0.404641E+09 | 0.433393E+10 | 0.907683E+10 | 54547.19 | 0.47 |
Minimum of Months | 18817656.68 | 1151521.65 | 0.00 | 2180630.94 | 3312004.52 | 193407.00 | 0.243276E+09 | 0.00 | 0.47 |
Maximum of Months | 0.394589E+09 | 0.436720E+09 | 357022.52 | 9224532.87 | 0.110631E+09 | 0.104755E+10 | 0.117918E+10 | 16905.52 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.146664E+11 | 0.237451E+09 | 0.00 | 69479795.26 | 0.00 | 0.00 | 0.131790E+11 | 0.00 | 0.54 |
February | 0.148124E+11 | 59929836.88 | 0.00 | 48092579.74 | 598666.43 | 0.00 | 0.989777E+10 | 0.00 | 0.54 |
March | 0.209140E+11 | 0.129545E+09 | 0.00 | 25339621.84 | 0.00 | 0.00 | 0.763058E+10 | 0.00 | 0.54 |
April | 0.145206E+11 | 0.293389E+09 | 0.00 | 20880527.12 | 27947235.00 | 0.00 | 0.585812E+10 | 0.00 | 0.54 |
May | 0.188300E+11 | 36747582.76 | 0.00 | 3390767.09 | 68036713.76 | 0.00 | 0.833324E+09 | 0.00 | 0.54 |
June | 0.112006E+11 | 0.657554E+09 | 0.00 | 98478.14 | 0.836962E+09 | 0.00 | 93224674.06 | 0.00 | 0.54 |
July | 0.440425E+10 | 0.527890E+10 | 0.00 | 1495970.35 | 0.559833E+09 | 0.00 | 0.275841E+09 | 0.00 | 0.54 |
August | 0.225760E+10 | 0.712630E+10 | 0.00 | 7313951.71 | 0.301186E+09 | 0.00 | 0.136442E+10 | 0.00 | 0.54 |
September | 0.486449E+10 | 0.291309E+10 | 0.00 | 25328065.57 | 50284975.13 | 0.00 | 0.460307E+10 | 0.00 | 0.54 |
October | 0.533378E+10 | 0.449702E+10 | 0.00 | 39295846.51 | 85723449.60 | 0.00 | 0.715485E+10 | 0.00 | 0.54 |
November | 0.104497E+11 | 0.190265E+09 | 0.00 | 71567146.60 | 0.00 | 0.00 | 0.136867E+11 | 0.00 | 0.54 |
December | 0.125517E+11 | 0.192124E+09 | 0.00 | 77868231.08 | 0.00 | 0.00 | 0.144747E+11 | 0.00 | 0.54 |
Annual Sum or Average | 0.134805E+12 | 0.216123E+11 | 0.00 | 0.390151E+09 | 0.193057E+10 | 0.00 | 0.790516E+11 | 0.00 | 0.54 |
Minimum of Months | 0.225760E+10 | 36747582.76 | 0.00 | 98478.14 | 0.00 | 0.00 | 93224674.06 | 0.00 | 0.54 |
Maximum of Months | 0.209140E+11 | 0.712630E+10 | 0.00 | 77868231.08 | 0.836962E+09 | 0.00 | 0.144747E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.464244E+10 | 24259306.00 | 36384.09 | 31309702.83 | 0.213211E+09 | 0.208823E+10 | 0.211605E+11 | 9336.66 | 0.53 |
February | 0.481434E+10 | 9420834.02 | 108517.40 | 33644438.01 | 51008993.13 | 0.151814E+09 | 0.197652E+11 | 6710.16 | 0.54 |
March | 0.557720E+10 | 22151297.10 | 17754.34 | 39305735.71 | 0.107408E+09 | 0.771760E+09 | 0.221894E+11 | 4232.06 | 0.54 |
April | 0.341376E+10 | 65735508.99 | 308464.62 | 56589241.75 | 0.255379E+09 | 45954343.27 | 0.168889E+11 | 2114.55 | 0.54 |
May | 0.318555E+10 | 8612603.10 | 89697.29 | 69836938.37 | 96104670.58 | 40813022.36 | 0.163759E+11 | 5978.63 | 0.54 |
June | 0.154460E+10 | 0.488568E+09 | 153223.27 | 72385856.66 | 0.100620E+10 | 10677216.85 | 0.966931E+10 | 7122.48 | 0.54 |
July | 0.361467E+09 | 0.247198E+10 | 2586616.70 | 52003785.99 | 0.336572E+10 | 1455691.42 | 0.426794E+10 | 38494.30 | 0.54 |
August | 0.298162E+09 | 0.311961E+10 | 9686643.25 | 42455537.01 | 0.430011E+10 | 2583332.77 | 0.328712E+10 | 114922.31 | 0.54 |
September | 0.117849E+10 | 0.116332E+10 | 4938062.72 | 50948288.62 | 0.179586E+10 | 15167871.49 | 0.825088E+10 | 76205.76 | 0.54 |
October | 0.140118E+10 | 0.216152E+10 | 6643074.69 | 42698182.72 | 0.241575E+10 | 11219265.99 | 0.110763E+11 | 89139.83 | 0.54 |
November | 0.413673E+10 | 26254164.48 | 103526.73 | 37769554.31 | 0.163940E+09 | 0.161805E+09 | 0.198783E+11 | 18792.43 | 0.54 |
December | 0.438105E+10 | 50649089.59 | 0.00 | 31064483.47 | 0.141527E+09 | 0.417649E+09 | 0.222819E+11 | 0.00 | 0.53 |
Annual Sum or Average | 0.349350E+11 | 0.961208E+10 | 24671965.11 | 0.560012E+09 | 0.139122E+11 | 0.371913E+10 | 0.175092E+12 | 373049.16 | 0.54 |
Minimum of Months | 0.298162E+09 | 8612603.10 | 0.00 | 31064483.47 | 51008993.13 | 1455691.42 | 0.328712E+10 | 0.00 | 0.53 |
Maximum of Months | 0.557720E+10 | 0.311961E+10 | 9686643.25 | 72385856.66 | 0.430011E+10 | 0.208823E+10 | 0.222819E+11 | 114922.31 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.240715E+09 | 12587622.68 | 0.00 | 6621273.43 | 4924704.25 | 0.628411E+09 | 0.118301E+10 | 0.00 | 0.47 |
February | 0.270529E+09 | 4017047.45 | 0.00 | 5381856.27 | 447001.74 | 0.489897E+09 | 0.106014E+10 | 0.00 | 0.47 |
March | 0.365508E+09 | 9209511.58 | 0.00 | 5414017.53 | 344622.57 | 0.650604E+09 | 0.108554E+10 | 0.00 | 0.47 |
April | 0.162580E+09 | 22744086.33 | 0.00 | 8833199.93 | 954879.91 | 0.117671E+09 | 0.121541E+10 | 0.00 | 0.47 |
May | 0.187432E+09 | 7164335.39 | 0.00 | 8318687.37 | 563631.24 | 0.106959E+09 | 0.114774E+10 | 0.00 | 0.47 |
June | 88080559.32 | 0.103152E+09 | 0.00 | 8031978.27 | 7070175.31 | 5622678.49 | 0.731203E+09 | 0.00 | 0.48 |
July | 18056586.64 | 0.404832E+09 | 0.00 | 6151818.49 | 25781620.39 | 284705.56 | 0.320780E+09 | 0.00 | 0.48 |
August | 15303783.64 | 0.520011E+09 | 0.00 | 5601878.54 | 27774809.23 | 159116.18 | 0.246603E+09 | 0.00 | 0.48 |
September | 67773151.07 | 0.199894E+09 | 0.00 | 7322070.71 | 18658691.45 | 831027.33 | 0.624186E+09 | 0.00 | 0.48 |
October | 74458330.88 | 0.314059E+09 | 162590.34 | 7225723.14 | 23756510.32 | 17441734.93 | 0.824823E+09 | 4536.93 | 0.48 |
November | 0.203750E+09 | 12422403.41 | 0.00 | 7418289.78 | 1609851.67 | 0.290110E+09 | 0.128409E+10 | 0.00 | 0.47 |
December | 0.247397E+09 | 12826309.28 | 0.00 | 6862987.19 | 1343032.12 | 0.555950E+09 | 0.118876E+10 | 0.00 | 0.47 |
Annual Sum or Average | 0.194158E+10 | 0.162292E+10 | 162590.34 | 83183780.64 | 0.113230E+09 | 0.286394E+10 | 0.109123E+11 | 4536.93 | 0.47 |
Minimum of Months | 15303783.64 | 4017047.45 | 0.00 | 5381856.27 | 344622.57 | 159116.18 | 0.246603E+09 | 0.00 | 0.47 |
Maximum of Months | 0.365508E+09 | 0.520011E+09 | 162590.34 | 8833199.93 | 27774809.23 | 0.650604E+09 | 0.128409E+10 | 4536.93 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.341188E+09 | 1774595.42 | 15022.33 | 2416200.68 | 15718450.43 | 0.102255E+10 | 0.692355E+09 | 2206.93 | 0.47 |
February | 0.352903E+09 | 694263.63 | 8597.93 | 2370197.33 | 3760504.91 | 0.813437E+09 | 0.657026E+09 | 159.70 | 0.47 |
March | 0.407792E+09 | 4405424.06 | 1272.44 | 3205588.08 | 5145027.38 | 0.876175E+09 | 0.819643E+09 | 1290.86 | 0.47 |
April | 0.227348E+09 | 20896385.49 | 0.00 | 6914634.48 | 2799804.08 | 0.174878E+09 | 0.109518E+10 | 0.00 | 0.47 |
May | 0.202677E+09 | 6719309.05 | 0.00 | 7932351.30 | 1007752.14 | 0.116403E+09 | 0.112326E+10 | 0.00 | 0.47 |
June | 91702359.18 | 0.102411E+09 | 0.00 | 8238209.73 | 7798800.28 | 4842025.24 | 0.728058E+09 | 0.00 | 0.48 |
July | 17817682.97 | 0.400699E+09 | 0.00 | 6247368.70 | 29863529.76 | 107305.07 | 0.321060E+09 | 0.00 | 0.48 |
August | 15868609.22 | 0.512309E+09 | 0.00 | 5182952.21 | 35413261.68 | 176658.58 | 0.246408E+09 | 0.00 | 0.48 |
September | 80220461.76 | 0.170715E+09 | 30277.29 | 5725819.23 | 47776141.67 | 1570425.20 | 0.612513E+09 | 5270.00 | 0.48 |
October | 97624715.09 | 0.281541E+09 | 298024.04 | 4920565.68 | 56091363.63 | 73099672.38 | 0.748196E+09 | 12778.05 | 0.48 |
November | 0.304934E+09 | 3373742.09 | 2305.53 | 3108920.52 | 10652025.65 | 0.583597E+09 | 0.893515E+09 | 2537.73 | 0.47 |
December | 0.322915E+09 | 3733693.77 | 0.00 | 2354004.30 | 10433709.30 | 0.966894E+09 | 0.706573E+09 | 278.18 | 0.47 |
Annual Sum or Average | 0.246299E+10 | 0.150927E+10 | 355499.55 | 58616812.23 | 0.226460E+09 | 0.463373E+10 | 0.864379E+10 | 24521.45 | 0.47 |
Minimum of Months | 15868609.22 | 694263.63 | 0.00 | 2354004.30 | 1007752.14 | 107305.07 | 0.246408E+09 | 0.00 | 0.47 |
Maximum of Months | 0.407792E+09 | 0.512309E+09 | 298024.04 | 8238209.73 | 56091363.63 | 0.102255E+10 | 0.112326E+10 | 12778.05 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.301544E+11 | 0.00 | 0.00 | 0.00 | 34542550.15 | 0.00 | 0.00 | 0.00 | 0.56 |
February | 0.266945E+11 | 0.00 | 0.00 | 0.00 | 7433691.94 | 0.00 | 0.00 | 0.00 | 0.56 |
March | 0.306778E+11 | 0.00 | 0.00 | 0.00 | 159180.53 | 0.00 | 0.00 | 0.00 | 0.56 |
April | 0.239440E+11 | 0.00 | 0.00 | 0.00 | 40467574.58 | 0.00 | 0.00 | 0.00 | 0.56 |
May | 0.241093E+11 | 0.00 | 0.00 | 0.00 | 5436006.00 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.179936E+11 | 0.00 | 0.00 | 0.00 | 0.310532E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.116460E+11 | 0.00 | 0.00 | 0.00 | 0.252928E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.988698E+10 | 0.00 | 0.00 | 0.00 | 0.305387E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.157316E+11 | 0.00 | 0.00 | 54.44 | 0.947447E+09 | 0.00 | 3793777.69 | 0.00 | 0.58 |
October | 0.161469E+11 | 54940890.80 | 0.00 | 265520.77 | 0.161336E+10 | 0.00 | 0.387364E+09 | 0.00 | 0.57 |
November | 0.268846E+11 | 0.00 | 0.00 | 0.00 | 25511804.64 | 0.00 | 0.00 | 0.00 | 0.56 |
December | 0.294321E+11 | 0.00 | 0.00 | 0.00 | 12550202.69 | 0.00 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 0.263302E+12 | 54940890.80 | 0.00 | 265575.21 | 0.858059E+10 | 0.00 | 0.391158E+09 | 0.00 | 0.57 |
Minimum of Months | 0.988698E+10 | 0.00 | 0.00 | 0.00 | 159180.53 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.306778E+11 | 54940890.80 | 0.00 | 265520.77 | 0.305387E+10 | 0.00 | 0.387364E+09 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 63322343.42 | 2859941.20 | 0.00 | 1124325.05 | 1518140.53 | 0.252985E+09 | 0.197257E+09 | 0.00 | 0.47 |
February | 72836153.50 | 886848.01 | 0.00 | 1044663.48 | 229164.29 | 0.216228E+09 | 0.166379E+09 | 0.00 | 0.47 |
March | 90610903.09 | 1893902.47 | 0.00 | 1088087.29 | 494631.06 | 0.254890E+09 | 0.180177E+09 | 0.00 | 0.47 |
April | 45718270.85 | 4634025.36 | 185.78 | 2065523.47 | 1290279.93 | 66888161.83 | 0.261452E+09 | 250.49 | 0.47 |
May | 44577830.37 | 971953.77 | 0.00 | 2110411.49 | 960037.89 | 63196496.44 | 0.252727E+09 | 0.00 | 0.47 |
June | 20826011.40 | 21989283.82 | 0.00 | 2043959.43 | 5566291.03 | 7946951.24 | 0.177418E+09 | 0.00 | 0.48 |
July | 4989309.83 | 94565819.48 | 40475.39 | 1458576.99 | 13045270.74 | 67118.13 | 79803220.37 | 1751.46 | 0.48 |
August | 4448467.78 | 0.121693E+09 | 79552.53 | 1239883.56 | 15172094.81 | 67091.95 | 61161381.85 | 2270.81 | 0.48 |
September | 17301671.31 | 47864848.15 | 20097.20 | 1742988.94 | 6752340.10 | 1011191.75 | 0.154972E+09 | 867.45 | 0.48 |
October | 22304045.80 | 76528346.88 | 88898.94 | 1345975.40 | 7874784.33 | 37448253.32 | 0.169889E+09 | 3687.79 | 0.48 |
November | 55223355.04 | 2942873.99 | 617.06 | 1416368.35 | 564132.21 | 0.159173E+09 | 0.230529E+09 | 440.51 | 0.47 |
December | 63819268.85 | 2873031.18 | 0.00 | 1238620.95 | 669304.17 | 0.238055E+09 | 0.196629E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.505978E+09 | 0.379703E+09 | 229826.91 | 17919384.39 | 54136471.09 | 0.129796E+10 | 0.212839E+10 | 9268.51 | 0.47 |
Minimum of Months | 4448467.78 | 886848.01 | 0.00 | 1044663.48 | 229164.29 | 67091.95 | 61161381.85 | 0.00 | 0.47 |
Maximum of Months | 90610903.09 | 0.121693E+09 | 88898.94 | 2110411.49 | 15172094.81 | 0.254890E+09 | 0.261452E+09 | 3687.79 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 83688488.18 | 1504651.70 | 1185.78 | 350255.11 | 2870724.15 | 0.366359E+09 | 64230590.90 | 1007.14 | 0.47 |
February | 84407012.14 | 257083.71 | 0.00 | 449092.74 | 858797.84 | 0.283513E+09 | 88065050.94 | 0.00 | 0.47 |
March | 98692768.66 | 961361.65 | 0.00 | 633584.18 | 1426892.03 | 0.311052E+09 | 0.116326E+09 | 0.00 | 0.47 |
April | 51724627.75 | 3123411.08 | 0.00 | 1637676.26 | 2800200.09 | 95145456.96 | 0.227573E+09 | 436.22 | 0.47 |
May | 46310918.67 | 842580.81 | 0.00 | 2027371.42 | 1089184.49 | 66020421.17 | 0.248210E+09 | 0.00 | 0.47 |
June | 21214539.73 | 21350092.73 | 0.00 | 2087344.43 | 6202253.58 | 7766438.87 | 0.177142E+09 | 0.00 | 0.48 |
July | 4980433.68 | 92361583.24 | 53169.22 | 1472737.33 | 15223841.66 | 65966.36 | 79788974.51 | 2109.78 | 0.48 |
August | 4669818.88 | 0.115307E+09 | 79592.47 | 1130794.63 | 21542172.10 | 75581.43 | 61032789.91 | 2221.29 | 0.48 |
September | 19569211.14 | 40291601.44 | 26406.25 | 1360223.01 | 14313002.12 | 4750736.06 | 0.149327E+09 | 741.43 | 0.48 |
October | 24168869.67 | 66963709.03 | 94129.27 | 854540.28 | 17425055.46 | 69203287.45 | 0.136734E+09 | 2924.26 | 0.48 |
November | 71071378.66 | 1820421.98 | 81.20 | 548493.61 | 1686684.88 | 0.246271E+09 | 0.128398E+09 | 464.68 | 0.47 |
December | 79370493.63 | 1228684.32 | 1238.71 | 375763.96 | 2311994.23 | 0.352034E+09 | 67903305.81 | 3.05 | 0.47 |
Annual Sum or Average | 0.589869E+09 | 0.346012E+09 | 255802.90 | 12927876.97 | 87750802.65 | 0.180226E+10 | 0.154473E+10 | 9907.85 | 0.47 |
Minimum of Months | 4669818.88 | 257083.71 | 0.00 | 350255.11 | 858797.84 | 65966.36 | 61032789.91 | 0.00 | 0.47 |
Maximum of Months | 98692768.66 | 0.115307E+09 | 94129.27 | 2087344.43 | 21542172.10 | 0.366359E+09 | 0.248210E+09 | 2924.26 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.298154E+09 | 25143556.63 | 0.00 | 19729729.61 | 2983382.79 | 0.364484E+09 | 0.262424E+10 | 0.00 | 0.54 |
February | 0.388294E+09 | 6903738.23 | 0.00 | 13444011.58 | 266070.88 | 0.328888E+09 | 0.220207E+10 | 0.00 | 0.54 |
March | 0.517880E+09 | 14664878.91 | 0.00 | 10400996.11 | 680229.33 | 0.723205E+09 | 0.213271E+10 | 0.00 | 0.54 |
April | 0.281639E+09 | 33468021.87 | 0.00 | 11479294.85 | 4595417.15 | 0.122555E+09 | 0.200073E+10 | 0.00 | 0.54 |
May | 0.335773E+09 | 6063550.25 | 0.00 | 8113036.52 | 6348509.57 | 0.215063E+09 | 0.177064E+10 | 0.00 | 0.54 |
June | 0.169258E+09 | 0.131354E+09 | 15199.33 | 7744110.40 | 45659091.62 | 2865874.32 | 0.115793E+10 | 2080.45 | 0.54 |
July | 41242389.37 | 0.585192E+09 | 206429.88 | 6046682.20 | 0.106210E+09 | 760792.35 | 0.506501E+09 | 9501.35 | 0.54 |
August | 34993459.62 | 0.780065E+09 | 487496.05 | 6504260.91 | 99241727.20 | 550281.20 | 0.387858E+09 | 16911.24 | 0.54 |
September | 0.114301E+09 | 0.317929E+09 | 4551.30 | 10857886.06 | 33088795.95 | 1509200.64 | 0.997797E+09 | 100.00 | 0.54 |
October | 0.125631E+09 | 0.507965E+09 | 180771.91 | 12277625.64 | 34690159.62 | 5184516.23 | 0.134088E+10 | 5516.18 | 0.54 |
November | 0.242610E+09 | 21233333.09 | 0.00 | 19196018.70 | 1304185.20 | 33944883.90 | 0.257176E+10 | 0.00 | 0.54 |
December | 0.290073E+09 | 22157991.86 | 0.00 | 20476516.70 | 599703.85 | 0.200533E+09 | 0.269951E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.283985E+10 | 0.245214E+10 | 894448.47 | 0.146270E+09 | 0.335667E+09 | 0.199954E+10 | 0.203926E+11 | 34109.23 | 0.54 |
Minimum of Months | 34993459.62 | 6063550.25 | 0.00 | 6046682.20 | 266070.88 | 550281.20 | 0.387858E+09 | 0.00 | 0.54 |
Maximum of Months | 0.517880E+09 | 0.780065E+09 | 487496.05 | 20476516.70 | 0.106210E+09 | 0.723205E+09 | 0.269951E+10 | 16911.24 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128501E+10 | 53841635.37 | 0.00 | 57322897.40 | 624485.17 | 0.00 | 0.520944E+11 | 0.00 | 4.63 |
February | 0.864229E+09 | 10972686.33 | 0.00 | 54467458.20 | 748635.90 | 0.00 | 0.471323E+11 | 0.00 | 4.68 |
March | 0.100193E+10 | 250993.22 | 0.00 | 60930254.41 | 0.00 | 0.00 | 0.540059E+11 | 0.00 | 4.67 |
April | 0.193432E+09 | 62784681.60 | 0.00 | 69493319.49 | 1065504.03 | 0.00 | 0.448287E+11 | 0.00 | 4.83 |
May | 73104526.03 | 8571404.15 | 0.00 | 75359146.96 | 0.00 | 0.00 | 0.460062E+11 | 0.00 | 4.91 |
June | 10856157.63 | 0.499160E+09 | 0.00 | 75869436.57 | 0.00 | 0.00 | 0.360971E+11 | 0.00 | 5.14 |
July | 0.00 | 0.417901E+10 | 0.00 | 67586776.20 | 0.00 | 0.00 | 0.242717E+11 | 0.00 | 5.25 |
August | 1117731.28 | 0.495420E+10 | 0.00 | 61037152.01 | 1259473.26 | 0.00 | 0.208504E+11 | 0.00 | 5.24 |
September | 34057501.64 | 0.156574E+10 | 0.00 | 68274510.42 | 9375277.25 | 0.00 | 0.309694E+11 | 0.00 | 5.10 |
October | 72145782.64 | 0.272758E+10 | 0.00 | 63621013.95 | 9891103.61 | 0.00 | 0.322532E+11 | 0.00 | 5.05 |
November | 0.591823E+09 | 40957045.02 | 0.00 | 60382696.25 | 10034.02 | 0.00 | 0.484279E+11 | 0.00 | 4.72 |
December | 0.849162E+09 | 18584644.46 | 0.00 | 59328746.05 | 1204307.13 | 0.00 | 0.518466E+11 | 0.00 | 4.66 |
Annual Sum or Average | 0.497687E+10 | 0.141216E+11 | 0.00 | 0.773673E+09 | 24178820.38 | 0.00 | 0.488784E+12 | 0.00 | 4.91 |
Minimum of Months | 0.00 | 250993.22 | 0.00 | 54467458.20 | 0.00 | 0.00 | 0.208504E+11 | 0.00 | 4.63 |
Maximum of Months | 0.128501E+10 | 0.495420E+10 | 0.00 | 75869436.57 | 9891103.61 | 0.00 | 0.540059E+11 | 0.00 | 5.25 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.481682E+09 | 57319019.01 | 0.00 | 71260408.02 | 0.00 | 0.00 | 0.573816E+11 | 0.00 | 5.00 |
February | 0.182031E+09 | 12294953.35 | 0.00 | 66933031.15 | 0.00 | 0.00 | 0.519353E+11 | 0.00 | 5.06 |
March | 0.264415E+09 | 263276.60 | 0.00 | 75087677.21 | 0.00 | 0.00 | 0.595025E+11 | 0.00 | 5.06 |
April | 3661610.15 | 67423916.57 | 0.00 | 82066130.68 | 0.00 | 0.00 | 0.488423E+11 | 0.00 | 5.23 |
May | 2397069.04 | 9098134.88 | 0.00 | 87632587.38 | 0.00 | 0.00 | 0.500020E+11 | 0.00 | 5.32 |
June | 0.00 | 0.529394E+09 | 0.00 | 85495290.72 | 0.00 | 0.00 | 0.389524E+11 | 0.00 | 5.54 |
July | 0.00 | 0.448884E+10 | 0.00 | 74105697.50 | 0.00 | 0.00 | 0.259920E+11 | 0.00 | 5.63 |
August | 0.00 | 0.529584E+10 | 0.00 | 66573253.64 | 0.00 | 0.00 | 0.222717E+11 | 0.00 | 5.61 |
September | 2185556.72 | 0.168012E+10 | 0.00 | 76955805.23 | 0.00 | 0.00 | 0.333422E+11 | 0.00 | 5.48 |
October | 3218813.29 | 0.291766E+10 | 0.00 | 71817399.31 | 656021.54 | 0.00 | 0.347501E+11 | 0.00 | 5.41 |
November | 81835985.87 | 43415889.99 | 0.00 | 73364406.18 | 0.00 | 0.00 | 0.530091E+11 | 0.00 | 5.09 |
December | 0.281418E+09 | 20655434.43 | 0.00 | 72925787.58 | 101970.91 | 0.00 | 0.568713E+11 | 0.00 | 5.03 |
Annual Sum or Average | 0.130284E+10 | 0.151223E+11 | 0.00 | 0.904217E+09 | 757992.45 | 0.00 | 0.532853E+12 | 0.00 | 5.29 |
Minimum of Months | 0.00 | 263276.60 | 0.00 | 66573253.64 | 0.00 | 0.00 | 0.222717E+11 | 0.00 | 5.00 |
Maximum of Months | 0.481682E+09 | 0.529584E+10 | 0.00 | 87632587.38 | 656021.54 | 0.00 | 0.595025E+11 | 0.00 | 5.63 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5287322.93 | 0.103083E+09 | 0.00 | 0.115060E+09 | 0.00 | 0.00 | 0.716127E+11 | 0.00 | 21.70 |
February | 0.00 | 22265850.38 | 0.00 | 0.103246E+09 | 0.00 | 0.00 | 0.645624E+11 | 0.00 | 21.73 |
March | 4835789.41 | 477136.35 | 0.00 | 0.113501E+09 | 0.00 | 0.00 | 0.736723E+11 | 0.00 | 21.70 |
April | 0.00 | 0.121252E+09 | 0.00 | 0.117017E+09 | 0.00 | 0.00 | 0.574995E+11 | 0.00 | 22.07 |
May | 0.00 | 16227065.59 | 0.00 | 0.120984E+09 | 0.00 | 0.00 | 0.579218E+11 | 0.00 | 22.13 |
June | 0.00 | 0.929713E+09 | 0.00 | 0.112190E+09 | 0.00 | 0.00 | 0.429137E+11 | 0.00 | 22.51 |
July | 0.00 | 0.757594E+10 | 0.00 | 88770035.54 | 0.00 | 0.00 | 0.266397E+11 | 0.00 | 22.68 |
August | 0.00 | 0.914806E+10 | 0.00 | 76832736.92 | 0.00 | 0.00 | 0.222822E+11 | 0.00 | 22.73 |
September | 0.00 | 0.280555E+10 | 0.00 | 0.102501E+09 | 0.00 | 0.00 | 0.373301E+11 | 0.00 | 22.56 |
October | 0.00 | 0.494197E+10 | 0.00 | 94870395.20 | 0.00 | 0.00 | 0.386787E+11 | 0.00 | 22.37 |
November | 0.00 | 76260723.72 | 0.00 | 0.112401E+09 | 0.00 | 0.00 | 0.645955E+11 | 0.00 | 21.87 |
December | 0.00 | 37508692.96 | 0.00 | 0.116113E+09 | 0.00 | 0.00 | 0.702139E+11 | 0.00 | 21.77 |
Annual Sum or Average | 10123112.34 | 0.257783E+11 | 0.00 | 0.127349E+10 | 0.00 | 0.00 | 0.627922E+12 | 0.00 | 22.15 |
Minimum of Months | 0.00 | 477136.35 | 0.00 | 76832736.92 | 0.00 | 0.00 | 0.222822E+11 | 0.00 | 21.70 |
Maximum of Months | 5287322.93 | 0.914806E+10 | 0.00 | 0.120984E+09 | 0.00 | 0.00 | 0.736723E+11 | 0.00 | 22.73 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154581E+11 | 0.00 | 0.00 | 0.00 | 17707635.06 | 0.00 | 0.00 | 0.00 | 1.09 |
February | 0.136845E+11 | 0.00 | 0.00 | 0.00 | 3810752.34 | 0.00 | 0.00 | 0.00 | 1.09 |
March | 0.157264E+11 | 0.00 | 0.00 | 0.00 | 81601.12 | 0.00 | 0.00 | 0.00 | 1.09 |
April | 0.122745E+11 | 0.00 | 0.00 | 0.00 | 20744995.35 | 0.00 | 0.00 | 0.00 | 1.09 |
May | 0.123592E+11 | 0.00 | 0.00 | 0.00 | 2786673.54 | 0.00 | 0.00 | 0.00 | 1.09 |
June | 0.922410E+10 | 0.00 | 0.00 | 0.00 | 0.159189E+09 | 0.00 | 0.00 | 0.00 | 1.11 |
July | 0.597001E+10 | 0.269505E+09 | 0.00 | 494.37 | 0.102709E+10 | 0.00 | 103400.70 | 0.00 | 1.11 |
August | 0.505297E+10 | 0.480794E+09 | 0.00 | 9733.66 | 0.108472E+10 | 0.00 | 15408244.68 | 0.00 | 1.12 |
September | 0.802360E+10 | 0.181614E+09 | 0.00 | 124612.53 | 0.321050E+09 | 0.00 | 42755611.66 | 0.00 | 1.12 |
October | 0.824677E+10 | 0.470052E+09 | 0.00 | 273744.64 | 0.407439E+09 | 0.00 | 0.229120E+09 | 0.00 | 1.11 |
November | 0.137819E+11 | 0.00 | 0.00 | 0.00 | 13078181.09 | 0.00 | 0.00 | 0.00 | 1.09 |
December | 0.150878E+11 | 0.00 | 0.00 | 0.00 | 6433642.23 | 0.00 | 0.00 | 0.00 | 1.09 |
Annual Sum or Average | 0.134890E+12 | 0.140197E+10 | 0.00 | 408585.19 | 0.306413E+10 | 0.00 | 0.287387E+09 | 0.00 | 1.10 |
Minimum of Months | 0.505297E+10 | 0.00 | 0.00 | 0.00 | 81601.12 | 0.00 | 0.00 | 0.00 | 1.09 |
Maximum of Months | 0.157264E+11 | 0.480794E+09 | 0.00 | 273744.64 | 0.108472E+10 | 0.00 | 0.229120E+09 | 0.00 | 1.12 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:59:53
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.161840E+12 | 0.937022E+10 | 0.114307E+12 | 0.534056E+12 | 0.217661E+12 |
February | 0.210879E+12 | 0.829834E+10 | 0.106644E+12 | 0.473604E+12 | 0.152708E+12 |
March | 0.300212E+12 | 0.950199E+10 | 0.121521E+12 | 0.543653E+12 | 0.168242E+12 |
April | 0.388554E+12 | 0.749089E+10 | 0.934855E+11 | 0.425532E+12 | 0.242616E+12 |
May | 0.416878E+12 | 0.771615E+10 | 0.945412E+11 | 0.429178E+12 | 0.246872E+12 |
June | 0.410797E+12 | 0.554647E+10 | 0.685732E+11 | 0.309899E+12 | 0.373667E+12 |
July | 0.434824E+12 | 0.227230E+10 | 0.309320E+11 | 0.151969E+12 | 0.669508E+12 |
August | 0.395038E+12 | 0.145120E+10 | 0.213695E+11 | 0.111530E+12 | 0.742089E+12 |
September | 0.311012E+12 | 0.440527E+10 | 0.552572E+11 | 0.255985E+12 | 0.481595E+12 |
October | 0.212038E+12 | 0.459036E+10 | 0.527192E+11 | 0.263340E+12 | 0.542773E+12 |
November | 0.177915E+12 | 0.842223E+10 | 0.102537E+12 | 0.480070E+12 | 0.214363E+12 |
December | 0.142003E+12 | 0.923793E+10 | 0.111351E+12 | 0.524328E+12 | 0.236214E+12 |
Annual Sum or Average | 0.356199E+13 | 0.783034E+11 | 0.973237E+12 | 0.450314E+13 | 0.428831E+13 |
Minimum of Months | 0.142003E+12 | 0.145120E+10 | 0.213695E+11 | 0.111530E+12 | 0.152708E+12 |