Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 08:59:38
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 11119.63 | 980.11 | 980.11 |
Net Site Energy | 11119.63 | 980.11 | 980.11 |
Total Source Energy | 23120.67 | 2037.91 | 2037.91 |
Net Source Energy | 23120.67 | 2037.91 | 2037.91 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 803.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 778.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 766.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 242.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1745.01 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 651.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 637.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 138.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 200.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 3214.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5313.01 | 5806.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 803.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 778.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 766.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 242.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 32.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 637.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 138.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 200.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 3214.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 803.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 778.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 766.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 242.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1745.01 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 651.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 637.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 138.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 200.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 3214.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 88.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 144.99 | 354.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 234.36 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 468.30 | 511.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 88.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 144.99 | 354.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 234.36 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 468.30 | 511.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5313.006 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5313.006 | 100.00 |
Total On-Site and Utility Electric Sources | 5313.006 | 100.00 |
Total Electricity End Uses | 5313.006 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 62.93 | 2.10 |
Air to Air Heat Recovery for Heating | 2933.52 | 97.90 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2996.45 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 697.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7896.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 9.1389 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.3365 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.3365 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 9.2031 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 6.1031 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.8125 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.3656 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 8.7188 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.5531 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.5531 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 6.3938 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.5531 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.3656 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.3656 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7219 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 6.3938 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 6.8557 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 6.8557 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.1389 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.3365 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.3365 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 9.2031 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 6.1031 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.8125 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.3656 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 8.7188 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.5531 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.5531 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 6.3938 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.5531 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.5531 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.5531 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.3656 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.3656 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7219 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 6.3938 | 18.58 | 0.0000 | |
Total | 11345.29 | 6.8557 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 6.8557 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.4542 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUN-19:30 | 21-DEC-17:49 | - | - | - | - | - | - | - | - | - | - | 10-JAN-21:19 |
Heating | 0.00 | 298399.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 144410.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 88772.42 | 89612.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 32159.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38667.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 7508.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4047.70 | 257405.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2353.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 406199.36 | 645417.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 298399.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 144410.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58789.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 14636.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1855.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 38667.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 7508.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4047.70 | 257405.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1056.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1056.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 870.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2465.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2427.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 768.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5526.46 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2063.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2017.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 438.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 636.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.37 | 3484.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 195.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 16826.29 | 6294.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 76.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 217.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 213.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 67.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.11 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 177.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 38.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 56.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 307.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1483.11 | 554.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 76.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 217.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 213.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 67.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.11 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 177.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 38.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 56.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 307.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1483.11 | 554.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 3.01 | 0.501001 | 0.430000 | 1.29 | 1.00 | 0.500000 | 0.000760 | 0.000049 | 1.29 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.469504 | 0.108856 | 0.300000 | 0.140851 | 0.301544 | 0.500000 | 0.003500 | 0.000037 | 0.179791 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.289903 | 0.204150 | 0.479000 | 0.138863 | 0.544400 | 0.500000 | 0.001866 | 0.000015 | 0.138863 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.277292 | 0.451341 | 0.300000 | 0.083188 | 1.00 | 0.500000 | 0.000844 | 0.000022 | 0.110692 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.134704 | 0.536039 | 0.649000 | 0.087423 | 1.00 | 0.500000 | 0.000711 | 0.000015 | 0.087423 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 4.02 | 0.058737 | 0.300000 | 1.21 | 0.300000 | 0.500000 | 0.025740 | 0.000069 | 1.21 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.91 | 0.075287 | 0.536000 | 1.02 | 0.536000 | 0.500000 | 0.005061 | 0.000113 | 1.02 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.79 | 0.172181 | 0.495000 | 2.87 | 0.495000 | 0.500000 | 0.002213 | 0.000282 | 2.87 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.81 | 0.655672 | 0.397000 | 0.718654 | 1.00 | 0.500000 | 0.000581 | 0.000133 | 0.718654 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.70 | 0.093713 | 0.667000 | 1.80 | 0.667000 | 0.500000 | 0.004066 | 0.000135 | 1.80 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.83 | 0.089431 | 0.636000 | 1.80 | 0.636000 | 0.500000 | 0.004260 | 0.000136 | 1.80 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.79 | 0.050702 | 0.300000 | 0.837743 | 0.300000 | 0.500000 | 0.013516 | 0.000059 | 0.837743 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.973838 | 0.322476 | 0.300000 | 0.292151 | 0.859935 | 0.500000 | 0.001181 | 0.000087 | 0.426095 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 5546.62 | 0.000049 | 115.67 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4174.79 | 0.000037 | 113.94 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1708.30 | 0.000015 | 39.49 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2570.12 | 0.000022 | 70.14 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1660.63 | 0.000015 | 42.33 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 7935.95 | 0.000069 | 170.24 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 12924.12 | 0.000113 | 300.07 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 32248.09 | 0.000282 | 734.95 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 7723.64 | 0.000068 | 220.71 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 7729.26 | 0.000068 | 220.87 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 44161.01 | 0.000386 | 1261.92 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 44283.93 | 0.000387 | 1265.43 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 7723.64 | 0.000068 | 220.71 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 7729.26 | 0.000068 | 220.87 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 15159.44 | 0.000133 | 399.42 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2371.73 | 0.000021 | 67.77 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2371.62 | 0.000021 | 67.77 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 11367.20 | 0.000099 | 324.81 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 15432.48 | 0.000135 | 339.52 |
DINING_FLR_6 VAV BOX REHEAT COIL | 15588.55 | 0.000136 | 343.37 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6795.67 | 0.000059 | 148.63 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 9894.59 | 0.000087 | 270.04 |
VAV WITH REHEAT HEATING COIL | 273684.05 | 0.002394 | 4245.69 |
FLR_3_DOAS HEATING COIL | 20913.38 | 0.000183 | 324.43 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.46 | 0.000068 | 0.000472 |
ROOM_2_FLR_3 FAN COIL | 1.43 | 0.000068 | 0.000460 |
ROOM_3_MULT19_FLR_3 FAN COIL | 7.76 | 0.000386 | 0.002493 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.89 | 0.000387 | 0.002334 |
ROOM_5_FLR_3 FAN COIL | 1.27 | 0.000068 | 0.000410 |
ROOM_6_FLR_3 FAN COIL | 1.24 | 0.000068 | 0.000400 |
ROOM_1_FLR_6 FAN COIL | 0.388947 | 0.000021 | 0.000126 |
ROOM_2_FLR_6 FAN COIL | 0.378108 | 0.000021 | 0.000122 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.66 | 0.000099 | 0.000544 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.46 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.43 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.76 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.89 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.27 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.24 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.388947 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.378108 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.66 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008517 | 12.80 | 0.008500 | 0.000472 | 1.46 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008518 | 12.80 | 0.008500 | 0.000460 | 1.43 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008456 | 12.80 | 0.008456 | 0.002493 | 7.76 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008698 | 12.80 | 0.008500 | 0.002334 | 6.89 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008519 | 12.80 | 0.008500 | 0.000410 | 1.27 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008519 | 12.80 | 0.008500 | 0.000400 | 1.24 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008516 | 12.80 | 0.008500 | 0.000126 | 0.388947 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008517 | 12.80 | 0.008500 | 0.000122 | 0.378108 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.82 | 6.70 | 0.008577 | 12.80 | 0.008500 | 0.000544 | 1.66 | |
VAV WITH REHEAT COOLING COIL | 28.30 | 6.70 | 0.007818 | 10.55 | 0.007818 | 0.016952 | 26.84 | 474600.85 |
FLR_3_DOAS COOLING COIL | 33.90 | 6.70 | 0.005475 | 11.72 | 0.005475 | 0.001612 | 2.05 | 45136.60 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 14.42 | 12.28 | 27.00 | 12.28 | 26.84 | 26.84 | 0.300000 | 0.457620 | 26.84 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 26.84 | 11.66 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 26.84 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.016952 | 0.000028 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.002394 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001612 | 0.000295 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000183 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.025925 | 5342.11 | |
HEATSYS1 PUMP | 0.004914 | 1479.87 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.004914 | 0.589678 |
COOLSYS1 | 0.025925 | 3.11 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 561698.07 | 561698.07 | 0.004914 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.025925 | 3698.53 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.025925 | 725821.85 | 726530.26 | 82.82 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 9.139 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.519 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.336 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.096 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.336 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.096 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 9.203 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.583 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 6.103 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.793 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.813 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.343 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.366 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.746 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 8.719 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.789 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.366 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 78.186 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.366 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 78.186 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.722 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2946.209 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 18084.325 | 9.139 | 169.807 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18084.325 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 894.495 | 13.336 | 82.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 894.495 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1035.829 | 13.336 | 82.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1035.829 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 1511.551 | 9.203 | 569.967 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1511.551 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 578.329 | 6.103 | 283.494 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 578.329 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 453.605 | 5.813 | 54.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 453.605 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1957.673 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1957.673 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11405.759 | 8.719 | 27.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11405.759 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 111.660 | 4.553 | 74.440 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.660 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 111.691 | 4.553 | 74.460 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.691 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2489.757 | 6.394 | 118.803 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.757 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 111.691 | 4.553 | 74.460 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.691 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3437.839 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3437.839 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3437.839 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3437.839 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1210.923 | 11.722 | 54.453 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1210.923 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2635.024 | 6.394 | 118.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2635.024 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.8226 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.107 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.174 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.031 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.097 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.048 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7359 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6841 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8028 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7445 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.17638513E-14 | 0.32473881E-16 | -0.15472737E-09 | 0.39084990E-16 |
29 | 8 | 0.22578286E-07 | 0.11136169E-12 | 0.38514655E-03 | -0.25672286E-09 |
30 | 7 | -0.12460867E-01 | 0.57383191E-08 | -0.23401545E-01 | 0.14168460E-03 |
31 | 6 | 0.41130930 | 0.19934685E-05 | 0.47716306 | -0.48180040E-02 |
32 | 5 | -5.2487139 | 0.74343025E-04 | -4.4802041 | 0.63904887E-01 |
33 | 4 | 33.260058 | 0.60748543E-03 | 21.592533 | -0.42553784 |
34 | 3 | -111.77343 | 0.13226915E-02 | -55.924898 | 1.5231004 |
35 | 2 | 197.67353 | 0.74337769E-03 | 78.150831 | -2.9093300 |
36 | 1 | -171.36487 | 0.79295509E-04 | -55.335031 | 2.7490988 |
37 | 0 | 57.057407 | 0.45097929E-06 | 15.545453 | |
38 | 9 | -0.19728226E-15 | 0.38070760E-16 | -0.14134637E-09 | 0.10329039E-17 |
39 | 8 | 0.20696804E-07 | 0.14765672E-12 | 0.36530744E-03 | -0.23532978E-09 |
40 | 7 | -0.11868633E-01 | 0.77667999E-08 | -0.22548754E-01 | 0.13495068E-03 |
41 | 6 | 0.39521686 | 0.27204939E-05 | 0.46345169 | -0.46283129E-02 |
42 | 5 | -5.0916664 | 0.10217830E-03 | -4.3748670 | 0.61957574E-01 |
43 | 4 | 32.565369 | 0.84029717E-03 | 21.180735 | -0.41631434 |
44 | 3 | -110.29532 | 0.18400486E-02 | -55.110745 | 1.5017457 |
45 | 2 | 196.20849 | 0.10394005E-02 | 77.404245 | -2.8860650 |
46 | 1 | -170.82368 | 0.11139293E-03 | -55.118150 | 2.7396138 |
47 | 0 | 57.057407 | 0.63685742E-06 | 15.581450 | |
48 | 9 | 0.13059652E-14 | 0.41030072E-16 | -0.13816519E-09 | -0.47111965E-17 |
49 | 8 | 0.20247126E-07 | 0.15597406E-12 | 0.36047671E-03 | -0.23021680E-09 |
50 | 7 | -0.11724123E-01 | 0.82470298E-08 | -0.22340566E-01 | 0.13330755E-03 |
51 | 6 | 0.39128975 | 0.28947446E-05 | 0.46009809 | -0.45820219E-02 |
52 | 5 | -5.0533361 | 0.10891817E-03 | -4.3490697 | 0.61482301E-01 |
53 | 4 | 32.395785 | 0.89717001E-03 | 21.079809 | -0.41406279 |
54 | 3 | -109.93440 | 0.19673976E-02 | -54.911173 | 1.4965315 |
55 | 2 | 195.85064 | 0.11127485E-02 | 77.221372 | -2.8803827 |
56 | 1 | -170.69145 | 0.11939355E-03 | -55.065279 | 2.7372963 |
57 | 0 | 57.057407 | 0.68346468E-06 | 15.590432 | |
58 | 9 | -0.20590843E-15 | 0.37601014E-16 | -0.14495918E-09 | 0.53749011E-17 |
59 | 8 | 0.21205398E-07 | 0.13808064E-12 | 0.37072834E-03 | -0.24111267E-09 |
60 | 7 | -0.12030653E-01 | 0.72214098E-08 | -0.22782120E-01 | 0.13679291E-03 |
61 | 6 | 0.39961963 | 0.25236359E-05 | 0.46720788 | -0.46802108E-02 |
62 | 5 | -5.1346368 | 0.94596970E-04 | -4.4037454 | 0.62490383E-01 |
63 | 4 | 32.755467 | 0.77656360E-03 | 21.293679 | -0.41883826 |
64 | 3 | -110.69986 | 0.16977958E-02 | -55.334066 | 1.5075900 |
65 | 2 | 196.60952 | 0.95769584E-03 | 77.608945 | -2.8924333 |
66 | 1 | -170.97185 | 0.10250317E-03 | -55.177451 | 2.7422106 |
67 | 0 | 57.057407 | 0.58520576E-06 | 15.571474 | |
68 | 9 | -0.13316196E-15 | 0.35962645E-16 | -0.14184186E-09 | 0.33595795E-17 |
69 | 8 | 0.20766565E-07 | 0.14634888E-12 | 0.36605364E-03 | -0.23612300E-09 |
70 | 7 | -0.11890945E-01 | 0.76921302E-08 | -0.22580893E-01 | 0.13520437E-03 |
71 | 6 | 0.39582317 | 0.26934781E-05 | 0.46396918 | -0.46354598E-02 |
72 | 5 | -5.0975841 | 0.10113583E-03 | -4.3788466 | 0.62030949E-01 |
73 | 4 | 32.591550 | 0.83151862E-03 | 21.196301 | -0.41666193 |
74 | 3 | -110.35104 | 0.18204263E-02 | -55.141525 | 1.5025506 |
75 | 2 | 196.26372 | 0.10281160E-02 | 77.432455 | -2.8869422 |
76 | 1 | -170.84409 | 0.11016374E-03 | -55.126315 | 2.7399715 |
77 | 0 | 57.057407 | 0.62970739E-06 | 15.580070 | |
78 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
79 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
80 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
81 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
82 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
83 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
84 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
85 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
86 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
87 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
88 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
89 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
90 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
91 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
92 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
93 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3856_SHGC_0.4 | 37 | 1 | VerySmooth | 2.191 | 2.191 | 1.000 | 0.401 | ||
2 | RESWINDOW_U_0.3856_SHGC_0.4 | 38 | 1 | VerySmooth | 2.191 | 2.191 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.40174E-002 | 0.31435 | 0.47878 | 0.47878 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11969 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.40174E-002 | 0.31435 | 0.47878 | 0.47878 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11969 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1461 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 7.5908E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1643 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.5821E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1044 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.1106E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.2077E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.3979E-002 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1664 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 9.1627E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1878 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1033 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1156 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.1409E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 4.7248E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.9114E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.5842E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.0691E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.7480E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.5573E-002 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.6539E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0614E-002 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.1419E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.4687E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.5842E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.0691E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.7480E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.5573E-002 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.6539E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0614E-002 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.1419E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.4687E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 33623.35726 | 33623.35726 | 3.00971 | 3.00971 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 27.04267 | 5.46480E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 5244.78893 | 5244.78893 | 0.46950 | 0.46950 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 33.40667 | 5.47451E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3405.06495 | 3405.06495 | 0.17979 | 0.17979 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3238.32873 | 3238.32873 | 0.28990 | 0.28990 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 33.16000 | 5.47412E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1113.76407 | 1113.76407 | 5.88112E-002 | 9.17347E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3098.20813 | 3098.20813 | 0.27729 | 0.27729 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 31.58133 | 5.47170E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 2096.29306 | 2096.29306 | 0.11069 | 0.11069 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1505.04650 | 1505.04650 | 0.13470 | 0.13470 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.47504E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1286.38516 | 1286.38516 | 6.79259E-002 | 6.79259E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44883.33487 | 44883.33487 | 4.01744 | 4.01744 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90000 | 5.47527E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2778.08847 | 2778.08847 | 0.14669 | 0.14669 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 21334.01341 | 21334.01341 | 1.91152 | 1.91152 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 33.40667 | 5.47451E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 8537.08084 | 8537.08084 | 0.45077 | 0.67639 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 64650.57571 | 64650.57571 | 5.78947 | 5.78947 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 19977.28678 | 19977.28678 | 1.05488 | 1.89399 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 12131.60852 | 12131.60852 | 1.46322 | 1.46322 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 7723.73202 | 7723.73202 | 0.41021 | 0.41021 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11822.32289 | 11822.32289 | 1.42591 | 1.42591 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 7729.35095 | 7729.35095 | 0.41051 | 0.41051 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 64335.39801 | 64335.39801 | 7.75939 | 7.75939 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 44161.27814 | 44161.27814 | 2.34556 | 2.34556 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 57116.21622 | 57116.21622 | 6.88928 | 6.88928 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.47504E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 44284.19998 | 44284.19998 | 2.35209 | 2.35209 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10523.52463 | 10523.52463 | 1.26926 | 1.26926 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 27.43733 | 5.46540E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 7723.73202 | 7723.73202 | 0.41021 | 0.41021 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10266.02727 | 10266.02727 | 1.23820 | 1.23820 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 26.59867 | 5.46414E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 7729.35095 | 7729.35095 | 0.41051 | 0.41051 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 20223.68052 | 20223.68052 | 1.81021 | 1.81021 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.90000 | 5.47527E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 12081.49100 | 12081.49100 | 0.63796 | 0.63796 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3224.77905 | 3224.77905 | 0.38895 | 0.38895 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2371.75626 | 2371.75626 | 0.12597 | 0.12597 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3134.91218 | 3134.91218 | 0.37811 | 0.37811 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2371.64493 | 2371.64493 | 0.12596 | 0.12596 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 13741.06005 | 13741.06005 | 1.65739 | 1.65739 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.47489E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 11367.29965 | 11367.29965 | 0.60374 | 0.60374 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 30087.76205 | 30087.76205 | 2.69677 | 2.69677 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.90000 | 5.47527E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 7728.05888 | 7728.05888 | 0.40807 | 1.18780 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31528.94929 | 31528.94929 | 2.82590 | 2.82590 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.90000 | 5.47527E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 7890.38396 | 7890.38396 | 0.41664 | 1.18780 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31110.59326 | 31110.59326 | 2.79248 | 2.79248 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 32.56800 | 5.47322E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 3212.79789 | 3212.79789 | 0.16963 | 0.36735 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -17.90000 | 9.55238E-004 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10879.86575 | 10879.86575 | 0.97384 | 0.97384 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.90000 | 5.47527E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 8069.31920 | 8069.31920 | 0.42610 | 0.42610 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 408452.38 | 26.84467 | 26.84467 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 266046.59 | 7.82866 | 7.82866 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 42510.28 | 20.95681 | 2.05125 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 69708.81 | 7.19476 | 2.05125 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.00971 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.50100 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.29418 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.60478E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.85243E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.29418 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5546.62223 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.85243E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 115.66524 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.46950 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10886 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14085 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30154 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.50003E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.65229E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17979 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4174.78826 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.65229E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 113.93536 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.28990 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20415 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47900 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13886 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54440 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.86627E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.49449E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13886 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1708.29738 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49449E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 39.49338 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.27729 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.45134 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.31876E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.44150E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.24845E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11069 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2570.11724 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.24845E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 70.14000 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.13470 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.53604 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.64900 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.74229E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.10770E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.45279E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.74229E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1660.62836 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.45279E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 42.32681 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.01744 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.87373E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.20523 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.57398E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.94271E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20523 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7935.94703 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.94271E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 170.23727 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.91152 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.52872E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.53600 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.02457 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53600 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.06062E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.13066E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.02457 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12924.11834 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.13066E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 300.07484 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.78947 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17218 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49500 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.86579 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49500 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.21279E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.82120E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.86579 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 32248.09339 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.82120E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 734.95405 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.46322 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.46322 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.75698E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.72326E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51732E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.72326E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.46322 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7723.64154 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.75698E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 220.70732 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.42591 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.42591 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.76189E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.60334E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51772E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.60334E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.42591 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7729.26042 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.76189E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 220.86784 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.75939 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.75939 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.86340E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.49269E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81651 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.45608E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.45608E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.49269E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.75939 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 44161.00831 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.86340E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1261.91548 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.88928 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.88928 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.87415E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.33435E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81550 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.69836E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.33435E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.88928 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 44283.92953 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.87415E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1265.42730 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.26926 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.26926 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.75698E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.09891E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51886E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.09891E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.26926 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7723.64154 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.75698E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 220.70732 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.23820 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.23820 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.76189E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.99894E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51916E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.99894E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.23820 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7729.26042 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.76189E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 220.86784 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.81021 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.65567 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.39700 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.71865 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.81083E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.32621E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71865 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15159.44279 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.32621E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 399.41742 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.38895 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.38895 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.07489E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.25517E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51631E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.25517E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.38895 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2371.73044 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.07489E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 67.77056 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.37811 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.37811 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.07480E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.22033E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51673E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.22033E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.37811 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2371.61911 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.07480E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 67.76738 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.65739 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.65739 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 9.94452E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.43823E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.81582 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57742E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.43823E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.65739 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 11367.19935 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.94452E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 324.80851 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.69677 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.37131E-002 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.66700 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.79875 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66700 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.06560E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.35010E-004 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.79875 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15432.48120 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.35010E-004 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 339.52307 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.82590 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.94310E-002 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.63600 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.79727 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63600 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.26027E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.36375E-004 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.79727 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15588.55418 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.36375E-004 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 343.37307 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.79248 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.07020E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.83774 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.35158E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.94515E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.83774 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6795.66702 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.94515E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 148.62623 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.97384 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32248 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29215 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85993 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18148E-003 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.65622E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42610 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9894.58700 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.65622E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 270.04218 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 14.42294 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 12.28467 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 26.99875 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 12.28467 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 26.84467 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 26.84467 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.45762 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 26.84467 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 26.84467 |
338 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 11.66146 |
339 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.29508 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.55121 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.81768E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.81768E-003 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 474600.85327 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.69516E-002 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 26.84467 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 273684.05238 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.39431E-003 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 4245.68985 |
351 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 26.84467 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.69516E-002 |
353 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.80911E-005 |
354 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.39431E-003 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
356 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
357 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 33.90000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.72145 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 5.47527E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 5.47527E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 45136.60304 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.61217E-003 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 20913.37763 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.82959E-004 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 324.43145 |
369 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.61217E-003 |
371 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.95371E-004 |
372 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.82959E-004 |
373 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.59247E-002 |
374 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 5342.11462 |
375 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.91398E-003 |
376 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.58968 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.91398E-003 |
378 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1479.87489 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 561698.06507 |
381 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 561698.07000 |
382 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.91398E-003 |
383 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.59247E-002 |
384 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.11096 |
385 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.59247E-002 |
386 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3698.52613 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.59247E-002 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 725821.85115 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 726530.26000 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 82.82445 |
391 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
392 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
393 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
394 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
395 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 5575.80 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4192.87 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1716.65 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2581.25 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1668.21 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 7977.03 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 12987.13 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 32407.01 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 8322.59 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 8328.64 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 47585.77 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 47718.21 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 8322.59 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 8328.64 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 15226.35 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2555.59 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2555.47 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 12248.40 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 15510.22 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 15667.02 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6830.50 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 9937.43 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 180200.71 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 13769.91 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 24959.77 | 18081.99 | 6877.79 | 0.72 | 6231.58 | 63.20 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 24325.17 | 17621.54 | 6703.63 | 0.72 | 6071.93 | 61.58 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 132499.32 | 95990.37 | 36508.94 | 0.72 | 34890.98 | 353.88 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 121317.22 | 86335.47 | 34981.75 | 0.71 | 27995.07 | 283.94 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 21657.29 | 15687.03 | 5970.26 | 0.72 | 5402.83 | 54.80 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 21128.52 | 15303.55 | 5824.97 | 0.72 | 5270.10 | 53.45 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 6633.50 | 4806.11 | 1827.39 | 0.72 | 1657.00 | 16.81 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 6449.12 | 4672.32 | 1776.80 | 0.72 | 1610.61 | 16.34 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 28579.69 | 20578.29 | 8001.40 | 0.72 | 6936.03 | 70.35 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 735132.14 | 430346.29 | 304785.85 | 0.59 | 180968.80 | 1835.49 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 46146.10 | 28462.74 | 17683.36 | 0.62 | 4499.01 | 45.63 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.107 | 0.950 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.107 | 0.950 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.107 | 0.950 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.107 | 0.950 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.9620480035E-002 | 3.7528482239E-002 | Pass | Pass | 0.3408345027 | 1.0058127721 | Pass | Fail |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.5891389763E-002 | 0.1185736341 | Pass | Pass | 0.7781888846 | 6.0353813754 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.1449762163E-002 | 6.8328097881E-002 | Pass | Pass | 0.7492869957 | 4.1527445309 | Fail | Fail |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.4528672687E-002 | 2.4336933329E-002 | Pass | Pass | 3.4458503768 | 26.3244159016 | Fail | Fail |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.6003071064E-002 | 3.4037457510E-002 | Pass | Pass | 0.4017423387 | 0.9919969106 | Fail | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.9911048791E-002 | 0.1730989839 | Fail | Fail | 0.1062256628 | 0.2354988521 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1088421424 | 0.1503259922 | Pass | Pass | 2.1545998573 | 22.3042597928 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.6102830836E-002 | 7.7500562566E-002 | Pass | Pass | 0.4008772055 | 1.4785578491 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.3073277753E-002 | 0.1918433754 | Pass | Pass | 0.1743758928 | 0.4654625899 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.9183026302E-002 | 0.2495445246 | Pass | Pass | 0.2359128365 | 0.9972212826 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.2285380208E-002 | 4.5501996883E-002 | Pass | Pass | 3.5954039048E-002 | 7.3924517731E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.6129361144E-002 | 0.1391192011 | Pass | Pass | 0.1717340093 | 0.4155489325 | Fail | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.7668760611E-002 | 0.2566782156 | Pass | Pass | 0.2364344250 | 0.8071988373 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.4004652017E-002 | 0.2272757137 | Pass | Pass | 0.1689727833 | 0.6475244371 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.3469258009E-002 | 2.6457080896E-002 | Pass | Pass | 178.7530900098 | 2124.2281527251 | Fail | Fail |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.0698382678E-002 | 0.2230615752 | Pass | Pass | 0.3242778113 | 1.4126340280 | Pass | Fail |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.5451585806E-002 | 0.3079217297 | Pass | Pass | 0.6993115766 | 4.8391851159 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.7593078320E-002 | 0.3072288855 | Pass | Pass | 0.1983710754 | 0.5013864653 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1349612989 | 0.2116706635 | Pass | Fail | 73.7006619792 | 658.2425797498 | Fail | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1305563321 | 0.2013262936 | Pass | Fail | 0.9996911673 | 6.2588465620 | Fail | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.2022637293 | 0.4085452841 | Fail | Fail | 0.1753019042 | 0.3389553116 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.4563700287E-002 | 4.3168927973E-002 | Pass | Pass | 1.9505381823 | 11.7104200039 | Fail | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4781.13 | 132.67 | 1507.80 | 7266.15 | 3749.23 | 17436.98 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.191 | 0.401 | 0.402 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.191 | 0.401 | 0.402 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.191 | 0.401 | 0.402 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.191 | 0.401 | 0.402 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.191 | 0.401 | 0.402 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.191 | 0.401 | 0.402 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.191 | 0.401 | 0.402 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.191 | 0.401 | 0.402 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.191 | 0.401 | 0.402 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.191 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 432.95 | 2.191 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.191 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.1389 | 1978.83 | 18084.33 | LightsWired | LTG_SCH_BASEMENT | 51.16 | 168.00 | 51.10 | 0.0000 | Y | 173.46 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.3365 | 67.07 | 894.50 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.61 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.3365 | 77.67 | 1035.83 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 9.97 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 9.2031 | 164.24 | 1511.55 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 16.63 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 6.1031 | 94.76 | 578.33 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 2.78 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.8125 | 78.04 | 453.60 | LightsWired | LTG_SCH_LAUNDRY | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 4.37 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.3656 | 188.86 | 1957.67 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.76 | 0.0000 | Y | 17.92 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 8.7188 | 1308.19 | 11405.76 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 56.91 | 0.0000 | Y | 121.84 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.5531 | 156.09 | 710.69 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.5531 | 156.07 | 710.61 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.5531 | 1863.81 | 8486.17 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 76.02 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.5531 | 1864.32 | 8488.49 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 76.04 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.5531 | 156.09 | 710.69 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.5531 | 156.07 | 710.61 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 6.3938 | 1557.62 | 9959.03 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 109.60 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.5531 | 39.02 | 177.67 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.59 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.5531 | 39.02 | 177.65 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.59 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.5531 | 220.77 | 1005.22 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 9.00 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.3656 | 331.66 | 3437.84 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 53.66 | 0.0000 | Y | 34.63 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.3656 | 331.66 | 3437.84 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 53.66 | 0.0000 | Y | 34.63 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7219 | 103.30 | 1210.92 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.33 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 6.3938 | 412.12 | 2635.02 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 29.00 |
Interior Lighting Total | 6.8557 | 11345.29 | 77780.02 | 507.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 11405.76 | 798.40 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 11405.76 | 0.00 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1957.67 | 763.49 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 1957.67 | 0.00 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3437.84 | 687.57 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3437.84 | 0.00 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3437.84 | 687.57 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3437.84 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 15448.40 | AstronomicalClock | - | 83.67 | 83.67 | 242.64 | |
Exterior Lighting Total | 15448.40 | 242.64 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 561698.07 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 726530.26 | 2.96 | 726657.97 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13224.12 | 24959.77 | 18081.99 | 6877.79 | 0.72 | - | 6231.58 | 63.20 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12888.37 | 24325.17 | 17621.54 | 6703.63 | 0.72 | - | 6071.93 | 61.58 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 69790.03 | 132499.32 | 95990.37 | 36508.94 | 0.72 | - | 34890.98 | 353.88 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 65356.72 | 121317.22 | 86335.47 | 34981.75 | 0.71 | - | 27995.07 | 283.94 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11476.06 | 21657.29 | 15687.03 | 5970.26 | 0.72 | - | 5402.83 | 54.80 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11196.19 | 21128.52 | 15303.55 | 5824.97 | 0.72 | - | 5270.10 | 53.45 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3514.21 | 6633.50 | 4806.11 | 1827.39 | 0.72 | - | 1657.00 | 16.81 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3416.67 | 6449.12 | 4672.32 | 1776.80 | 0.72 | - | 1610.61 | 16.34 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 15225.88 | 28579.69 | 20578.29 | 8001.40 | 0.72 | - | 6936.03 | 70.35 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 474600.85 | 735132.14 | 430346.29 | 304785.85 | 0.59 | - | 180968.80 | 1835.49 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 45136.60 | 46146.10 | 28462.74 | 17683.36 | 0.62 | - | 4499.01 | 45.63 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 5546.62 | 5575.80 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4174.79 | 4192.87 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1708.30 | 1716.65 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2570.12 | 2581.25 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1660.63 | 1668.21 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 7935.95 | 7977.03 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12924.12 | 12987.13 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 32248.09 | 32407.01 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7723.64 | 8322.59 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7729.26 | 8328.64 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 44161.01 | 47585.77 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 44283.93 | 47718.21 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7723.64 | 8322.59 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 7729.26 | 8328.64 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 15159.44 | 15226.35 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2371.73 | 2555.59 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2371.62 | 2555.47 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 11367.20 | 12248.40 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 15432.48 | 15510.22 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 15588.55 | 15667.02 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 6795.67 | 6830.50 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9894.59 | 9937.43 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 273684.05 | 180200.71 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 20913.38 | 13769.91 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.46 | 1029.57 | 703.64 | 1.00 | 1.12 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.43 | 1003.32 | 703.64 | 1.00 | 1.12 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 7.76 | 5459.79 | 703.64 | 1.00 | 0.94 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.89 | 4847.55 | 703.64 | 1.00 | 0.95 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.27 | 893.10 | 703.64 | 1.00 | 1.14 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.24 | 871.25 | 703.64 | 1.00 | 1.15 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.39 | 273.68 | 703.64 | 1.00 | 1.55 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.38 | 266.05 | 703.64 | 1.00 | 1.57 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.66 | 1166.20 | 703.64 | 1.00 | 1.09 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 26.84 | 60149.21 | 2240.64 | 1.00 | 1.11 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.025925 | 5342.11 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.004914 | 1479.87 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.025925 | 3698.53 | 142664.32 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 33623.36 | 33623.36 | 16.99 | 3.010 | 3.010 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 24.00 | 24.00 | 0.00922 | 27.04 | 0.00546 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 5244.79 | 5244.79 | 78.20 | 0.470 | 0.470 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00890 | 33.41 | 0.00547 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3238.33 | 3238.33 | 41.69 | 0.290 | 0.290 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00933 | 33.16 | 0.00547 | 0.092 | 0.00 |
MECH_FLR_1 | 3098.21 | 3098.21 | 18.86 | 0.277 | 0.277 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00860 | 31.58 | 0.00547 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1505.05 | 1505.05 | 15.88 | 0.135 | 0.135 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00869 | 33.75 | 0.00548 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44883.33 | 44883.33 | 575.14 | 4.017 | 4.017 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00853 | 33.90 | 0.00548 | 0.000 | 0.00 |
CAFE_FLR_1 | 21334.01 | 21334.01 | 112.96 | 1.912 | 1.912 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 23.99 | 0.00996 | 33.41 | 0.00547 | 0.676 | 0.00 |
LOBBY_FLR_1 | 64650.58 | 64650.58 | 49.42 | 5.789 | 5.789 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.00993 | 33.53 | 0.00547 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 12131.61 | 12131.61 | 310.89 | 1.463 | 1.463 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 32.03 | 0.00547 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11822.32 | 11822.32 | 303.00 | 1.426 | 1.426 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 31.83 | 0.00547 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 64335.40 | 64335.40 | 2623.38 | 7.759 | 7.759 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00846 | 33.53 | 0.00547 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 57116.22 | 57116.22 | 2328.37 | 6.889 | 6.889 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 21.11 | 21.11 | 0.00870 | 33.75 | 0.00548 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10523.52 | 10523.52 | 269.68 | 1.269 | 1.269 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 21.11 | 21.11 | 0.00852 | 27.44 | 0.00547 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10266.03 | 10266.03 | 263.11 | 1.238 | 1.238 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 21.11 | 21.11 | 0.00852 | 26.60 | 0.00546 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 20223.68 | 20223.68 | 51.93 | 1.810 | 1.810 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00939 | 33.90 | 0.00548 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3224.78 | 3224.78 | 82.64 | 0.389 | 0.389 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 32.03 | 0.00547 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3134.91 | 3134.91 | 80.35 | 0.378 | 0.378 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 31.83 | 0.00547 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13741.06 | 13741.06 | 560.16 | 1.657 | 1.657 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00858 | 33.65 | 0.00547 | 0.099 | 0.00 |
BANQUET_FLR_6 | 30087.76 | 30087.76 | 90.72 | 2.697 | 2.697 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.98 | 0.01035 | 33.90 | 0.00548 | 1.188 | 0.00 |
DINING_FLR_6 | 31528.95 | 31528.95 | 95.06 | 2.826 | 2.826 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.98 | 0.01027 | 33.90 | 0.00548 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31110.59 | 31110.59 | 301.15 | 2.792 | 2.792 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01005 | 32.57 | 0.00547 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10879.87 | 10879.87 | 26.40 | 0.974 | 0.974 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00892 | 33.90 | 0.00548 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 22.47 | 0.00096 | -17.90 | 0.00096 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3405.06 | 3405.06 | 50.77 | 0.180 | 0.180 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00759 | -17.90 | 0.00096 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1113.76 | 1113.76 | 14.34 | 0.059 | 0.092 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00752 | -17.90 | 0.00096 | 0.092 | 0.00 |
MECH_FLR_1 | 2096.29 | 2096.29 | 12.76 | 0.111 | 0.111 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00740 | -17.90 | 0.00096 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1286.39 | 1286.39 | 13.58 | 0.068 | 0.068 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00744 | -17.90 | 0.00096 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2778.09 | 2778.09 | 35.60 | 0.147 | 0.147 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00739 | -17.90 | 0.00096 | 0.000 | 0.00 |
CAFE_FLR_1 | 8537.08 | 8537.08 | 45.20 | 0.451 | 0.676 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00763 | -17.90 | 0.00096 | 0.676 | 0.00 |
LOBBY_FLR_1 | 19977.29 | 19977.29 | 15.27 | 1.055 | 1.894 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00756 | -17.90 | 0.00096 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 7723.73 | 7723.73 | 197.93 | 0.410 | 0.410 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00758 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 7729.35 | 7729.35 | 198.10 | 0.411 | 0.411 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00758 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 44161.28 | 44161.28 | 1800.75 | 2.346 | 2.346 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00761 | -17.90 | 0.00096 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 44284.20 | 44284.20 | 1805.27 | 2.352 | 2.352 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00761 | -17.90 | 0.00096 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 7723.73 | 7723.73 | 197.93 | 0.410 | 0.410 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00758 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 7729.35 | 7729.35 | 198.10 | 0.411 | 0.411 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00758 | -17.90 | 0.00096 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 12081.49 | 12081.49 | 31.03 | 0.638 | 0.638 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00767 | -17.90 | 0.00096 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2371.76 | 2371.76 | 60.78 | 0.126 | 0.126 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00765 | -17.90 | 0.00096 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2371.64 | 2371.64 | 60.78 | 0.126 | 0.126 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00765 | -17.90 | 0.00096 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11367.30 | 11367.30 | 463.39 | 0.604 | 0.604 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00767 | -17.90 | 0.00096 | 0.099 | 0.00 |
BANQUET_FLR_6 | 7728.06 | 7728.06 | 23.30 | 0.408 | 1.188 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00774 | -17.90 | 0.00096 | 1.188 | 0.00 |
DINING_FLR_6 | 7890.38 | 7890.38 | 23.79 | 0.417 | 1.188 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00774 | -17.90 | 0.00096 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 3212.80 | 3212.80 | 31.10 | 0.170 | 0.367 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00719 | -17.90 | 0.00096 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 8069.32 | 8069.32 | 19.58 | 0.426 | 0.426 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00778 | -17.90 | 0.00096 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 26.84 | 26.84 | 7.83 | 7.83 | 26.8447 | 12.2847 | 26.8447 | 0.4576 | 0.3000 |
FLR_3_DOAS | 20.96 | 2.05 | 7.19 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 5546.622 | 5546.622 | 1.294177 | 0.00004852 | 115.665 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5546.62 | 5546.62 | 1.294177 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 5577.80 | 5577.80 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4174.788 | 4174.788 | 0.179791 | 0.00003652 | 113.935 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 4174.79 | 4174.79 | 0.179791 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00758547 | 39.8340 | 3405.06 | 0.00 | 4195.49 | 4195.49 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1708.297 | 1708.297 | 0.138863 | 0.00001494 | 39.493 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1708.30 | 1708.30 | 0.138863 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00751592 | 39.4713 | 1113.76 | 0.00 | 1717.44 | 1717.44 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2570.117 | 2570.117 | 0.110692 | 0.00002248 | 70.140 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 2570.12 | 2570.12 | 0.110692 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00740262 | 38.8832 | 2096.29 | 0.00 | 2582.86 | 2582.86 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1660.628 | 1660.628 | 0.087423 | 0.00001453 | 42.327 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 1660.63 | 1660.63 | 0.087423 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00743549 | 39.0538 | 1286.39 | 0.00 | 1669.14 | 1669.14 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7935.947 | 7935.947 | 1.205232 | 0.00006943 | 170.237 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 7935.95 | 7935.95 | 1.205232 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00738611 | 38.7996 | 2778.09 | 0.00 | 7980.12 | 7980.12 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 12924.118 | 12924.118 | 1.024573 | 0.00011307 | 300.075 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 12924.12 | 12924.12 | 1.024573 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00763195 | 40.0746 | 8537.08 | 0.00 | 12993.22 | 12993.22 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 32248.093 | 32248.093 | 2.865790 | 0.00028212 | 734.954 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 32248.09 | 32248.09 | 2.865790 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00755572 | 39.6776 | 19977.29 | 0.00 | 32421.60 | 32421.60 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 13224.120 | -999.000 | 1.463218 | 0.00047233 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 13224.12 | 13181.47 | 1.463218 | 21.82 | 13.52 | 0.00851732 | 12.80 | 10.21 | 0.00850000 | 32.03 | 0.00547238 | 14.46 | 0.0000 | 21.11 | 0.00851732 | 44.3544 | 12131.61 | 0.00 | 16653.74 | 15571.65 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 7723.642 | 7723.642 | 0.410213 | 0.00006757 | 220.707 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 7723.64 | 7723.64 | 0.410213 | 21.11 | 12.48 | 0.00757861 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00757861 | 39.5285 | 7723.73 | 0.00 | 8326.14 | 8326.14 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12888.370 | -999.000 | 1.425914 | 0.00046033 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 12888.37 | 12845.87 | 1.425914 | 21.82 | 13.52 | 0.00851772 | 12.80 | 10.21 | 0.00850000 | 31.83 | 0.00547208 | 14.39 | 0.0000 | 21.11 | 0.00851772 | 44.3564 | 11822.32 | 0.00 | 16230.69 | 15174.71 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 7729.260 | 7729.260 | 0.410512 | 0.00006762 | 220.868 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 7729.26 | 7729.26 | 0.410512 | 21.11 | 12.48 | 0.00757893 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00757893 | 39.5301 | 7729.35 | 0.00 | 8332.20 | 8332.20 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 69790.026 | -999.000 | 7.759386 | 0.00249269 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 69790.03 | 69790.03 | 7.759386 | 21.82 | 13.47 | 0.00845608 | 12.80 | 10.17 | 0.00845608 | 33.53 | 0.00547470 | 14.95 | 0.0000 | 21.11 | 0.00845608 | 44.0390 | 64335.40 | 0.00 | 88066.35 | 83007.99 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 44161.008 | 44161.008 | 2.345559 | 0.00038634 | 1261.915 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 44161.01 | 44161.01 | 2.345559 | 21.11 | 12.50 | 0.00760760 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00760760 | 39.6758 | 44161.28 | 0.00 | 47606.56 | 47606.56 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 65356.725 | -999.000 | 6.889281 | 0.00233435 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | unknown | 7/21 15:10:00 | 65356.72 | 63021.79 | 6.889281 | 21.82 | 13.68 | 0.00869836 | 12.80 | 10.21 | 0.00850000 | 33.75 | 0.00547504 | 15.02 | 0.0000 | 21.11 | 0.00869836 | 45.2854 | 57116.22 | 0.00 | 81834.00 | 73436.24 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 44283.930 | 44283.930 | 2.352087 | 0.00038742 | 1265.427 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 44283.93 | 44283.93 | 2.352087 | 21.11 | 12.50 | 0.00760853 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00760853 | 39.6806 | 44284.20 | 0.00 | 47739.08 | 47739.08 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11476.060 | -999.000 | 1.269262 | 0.00040989 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | 7/21 09:40:00 | 11476.06 | 11435.78 | 1.269262 | 21.82 | 13.53 | 0.00851886 | 12.80 | 10.21 | 0.00850000 | 27.44 | 0.00546540 | 12.88 | 0.0000 | 21.11 | 0.00851886 | 44.3623 | 10523.52 | 0.00 | 14451.55 | 13507.74 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 7723.642 | 7723.642 | 0.410213 | 0.00006757 | 220.707 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 7723.64 | 7723.64 | 0.410213 | 21.11 | 12.48 | 0.00757861 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00757861 | 39.5285 | 7723.73 | 0.00 | 8326.14 | 8326.14 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 11196.188 | -999.000 | 1.238205 | 0.00039989 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | unknown | 7/21 09:20:00 | 11196.19 | 11156.26 | 1.238205 | 21.82 | 13.53 | 0.00851916 | 12.80 | 10.21 | 0.00850000 | 26.60 | 0.00546414 | 12.59 | 0.0000 | 21.11 | 0.00851916 | 44.3638 | 10266.03 | 0.00 | 14098.96 | 13177.25 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 7729.260 | 7729.260 | 0.410512 | 0.00006762 | 220.868 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 7729.26 | 7729.26 | 0.410512 | 21.11 | 12.48 | 0.00757893 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00757893 | 39.5301 | 7729.35 | 0.00 | 8332.20 | 8332.20 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 15159.443 | 15159.443 | 0.718654 | 0.00013262 | 399.417 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 15159.44 | 15159.44 | 0.718654 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00766790 | 40.2589 | 12081.49 | 0.00 | 15235.37 | 15235.37 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3514.212 | -999.000 | 0.388947 | 0.00012552 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3514.21 | 3503.54 | 0.388947 | 21.82 | 13.52 | 0.00851631 | 12.80 | 10.21 | 0.00850000 | 32.03 | 0.00547238 | 14.46 | 0.0000 | 21.11 | 0.00851631 | 44.3492 | 3224.78 | 0.00 | 4425.77 | 4139.17 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2371.730 | 2371.730 | 0.125966 | 0.00002075 | 67.771 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 2371.73 | 2371.73 | 0.125966 | 21.11 | 12.54 | 0.00765300 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00765300 | 39.9117 | 2371.76 | 0.00 | 2556.74 | 2556.74 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3416.666 | -999.000 | 0.378108 | 0.00012203 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3416.67 | 3406.03 | 0.378108 | 21.82 | 13.52 | 0.00851673 | 12.80 | 10.21 | 0.00850000 | 31.83 | 0.00547208 | 14.39 | 0.0000 | 21.11 | 0.00851673 | 44.3513 | 3134.91 | 0.00 | 4302.86 | 4023.83 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2371.619 | 2371.619 | 0.125960 | 0.00002075 | 67.767 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 2371.62 | 2371.62 | 0.125960 | 21.11 | 12.54 | 0.00765301 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00765301 | 39.9117 | 2371.64 | 0.00 | 2556.62 | 2556.62 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 15225.876 | -999.000 | 1.657394 | 0.00054382 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 15225.88 | 15008.83 | 1.657394 | 21.82 | 13.57 | 0.00857742 | 12.80 | 10.21 | 0.00850000 | 33.65 | 0.00547489 | 14.99 | 0.0000 | 21.11 | 0.00857742 | 44.6639 | 13741.06 | 0.00 | 19137.05 | 17647.24 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 11367.199 | 11367.199 | 0.603739 | 0.00009945 | 324.809 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 11367.20 | 11367.20 | 0.603739 | 21.11 | 12.55 | 0.00766598 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00766598 | 39.9777 | 11367.30 | 0.00 | 12254.00 | 12254.00 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 15432.481 | 15432.481 | 1.798749 | 0.00013501 | 339.523 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 15432.48 | 15432.48 | 1.798749 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00773524 | 40.6088 | 7728.06 | 0.00 | 15516.65 | 15516.65 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 15588.554 | 15588.554 | 1.797271 | 0.00013638 | 343.373 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 15588.55 | 15588.55 | 1.797271 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00774048 | 40.6360 | 7890.38 | 0.00 | 15673.53 | 15673.53 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 6795.667 | 6795.667 | 0.837743 | 0.00005945 | 148.626 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 6795.67 | 6795.67 | 0.837743 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00719256 | 37.7974 | 3212.80 | 0.00 | 6833.29 | 6833.29 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 9894.587 | 9894.587 | 0.426095 | 0.00008656 | 270.042 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 9894.59 | 9894.59 | 0.426095 | 16.70 | 11.24 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00777648 | 40.8221 | 8069.32 | 0.00 | 9943.66 | 9943.66 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 474600.853 | -999.000 | 26.844674 | 0.01695164 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 474600.85 | 474600.85 | 26.844674 | 28.30 | 15.12 | 0.00781768 | 10.55 | 8.65 | 0.00781768 | 33.90 | 0.00547527 | 15.07 | 43.4405 | 23.99 | 0.00957900 | 41.8042 | 299619.75 | 0.00 | 564021.54 | 516959.38 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 273684.052 | 273684.052 | 8.053402 | 0.00239431 | 4245.690 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 273684.05 | 273684.05 | 8.053402 | -17.90 | -17.90 | 0.00095524 | 16.70 | 11.24 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 144.8017 | 21.20 | 0.00672659 | 34.9312 | 77688.21 | 0.00 | 217770.06 | 217770.06 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 45136.603 | -999.000 | 2.051317 | 0.00161217 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 45136.60 | 45136.60 | 2.051317 | 33.90 | 15.07 | 0.00547527 | 11.72 | 6.72 | 0.00547527 | 33.90 | 0.00547527 | 15.07 | 99.9965 | 21.11 | 0.00857053 | 44.6279 | 173752.15 | 0.00 | 45179.60 | 45179.60 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 20913.378 | 20913.378 | 0.615395 | 0.00018296 | 324.431 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 20913.38 | 20913.38 | 0.615395 | -17.90 | -17.90 | 0.00095524 | 16.70 | 11.24 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 333.3216 | 21.11 | 0.00760843 | 39.6801 | 135462.34 | 0.00 | 16640.75 | 16640.75 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 5546.622 | 5546.622 | 1.294177 | 0.00004852 | 115.665 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 0.9680 | 0.987474 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5546.62 | 5546.62 | 1.0000 | 1.26497742 | 1.294177 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.04851932 | 60.00 | 32.22 | 27.78 | 0.000 | 5546.62 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 5577.80 | 5577.80 | 1.26497742 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4174.788 | 4174.788 | 0.179791 | 0.00003652 | 113.935 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 0.7286 | 0.743244 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 4174.79 | 4174.79 | 1.0000 | 0.17573477 | 0.179791 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.03651914 | 60.00 | 32.22 | 27.78 | 0.000 | 4174.79 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00758547 | 21.00 | 0.00758547 | 39.8340 | 3405.06 | 0.00 | 4195.49 | 4195.49 | 0.17573477 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60808.7 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1708.297 | 1708.297 | 0.138863 | 0.00001494 | 39.493 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 0.2981 | 0.304131 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1708.30 | 1708.30 | 1.0000 | 0.13573038 | 0.138863 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.01494341 | 60.00 | 32.22 | 27.78 | 0.000 | 1708.30 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00751592 | 21.00 | 0.00751592 | 39.4713 | 1113.76 | 0.00 | 1717.44 | 1717.44 | 0.13573038 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.01 | 17.70 | 0.00800000 | 49588.1 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2570.117 | 2570.117 | 0.110692 | 0.00002248 | 70.140 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 0.4485 | 0.457562 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 2570.12 | 2570.12 | 1.0000 | 0.10819440 | 0.110692 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.02248221 | 60.00 | 32.22 | 27.78 | 0.000 | 2570.12 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00740262 | 21.00 | 0.00740262 | 38.8832 | 2096.29 | 0.00 | 2582.86 | 2582.86 | 0.10819440 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60807.2 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1660.628 | 1660.628 | 0.087423 | 0.00001453 | 42.327 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 0.2898 | 0.295644 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 1660.63 | 1660.63 | 1.0000 | 0.08545046 | 0.087423 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.01452642 | 60.00 | 32.22 | 27.78 | 0.000 | 1660.63 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00743549 | 21.00 | 0.00743549 | 39.0538 | 1286.39 | 0.00 | 1669.14 | 1669.14 | 0.08545046 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.76 | 19.89 | 0.00800000 | 56468.2 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7935.947 | 7935.947 | 1.205232 | 0.00006943 | 170.237 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 1.3850 | 1.412849 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 7935.95 | 7935.95 | 1.0000 | 1.17803913 | 1.205232 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.06942004 | 60.00 | 32.22 | 27.78 | 0.000 | 7935.95 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00738611 | 21.00 | 0.00738611 | 38.7996 | 2778.09 | 0.00 | 7980.12 | 7980.12 | 1.17803913 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.24 | 15.68 | 0.00800000 | 43708.8 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12924.118 | 12924.118 | 1.024573 | 0.00011307 | 300.075 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 2.2555 | 2.300901 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 12924.12 | 12924.12 | 1.0000 | 1.00145664 | 1.024573 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.11305429 | 60.00 | 32.22 | 27.78 | 0.000 | 12924.12 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00763195 | 21.00 | 0.00763195 | 40.0746 | 8537.08 | 0.00 | 12993.22 | 12993.22 | 1.00145664 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.32 | 17.81 | 0.00800000 | 49909.1 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 32248.093 | 32248.093 | 2.865790 | 0.00028212 | 734.954 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 5.6279 | 5.741179 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 32248.09 | 32248.09 | 1.0000 | 2.80113057 | 2.865790 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.28209161 | 60.00 | 32.22 | 27.78 | 0.000 | 32248.09 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00755572 | 21.00 | 0.00755572 | 39.6776 | 19977.29 | 0.00 | 32421.60 | 32421.60 | 2.80113057 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.95 | 17.34 | 0.00800000 | 48509.2 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13224.120 | -999.000 | 1.463218 | 0.00047233 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6733 | 1004.8586 | 0.9774 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.463218 | 1.43020387 | 4197.9300 | 999.8980 | 25.92203020 | 13.37 | 6.70 | 6.67 | 725821.85 | 1.8220 | 1.821917 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 13224.12 | 13181.47 | 1.0000 | 1.43020387 | 1.463218 | 21.82 | 13.52 | 0.00851732 | 43568.5 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.47227793 | 6.70 | 13.37 | 6.67 | 0.000 | 13224.12 | 32.03 | 0.00547238 | 14.46 | 0.00000000 | 0.0000 | 21.11 | 0.00851732 | 21.11 | 0.00851732 | 44.3544 | 12131.61 | 0.00 | 16653.74 | 15571.65 | 1.43020387 | 21.82 | 15.62 | 0.00851732 | 43568.5 | 11.15 | 11.12 | 0.00821728 | 31924.2 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7723.642 | 7723.642 | 0.410213 | 0.00006757 | 220.707 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.463218 | 1.43020387 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 1.3479 | 1.375052 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 7723.64 | 7723.64 | 1.0000 | 0.40095804 | 0.410213 | 21.11 | 12.48 | 0.00757861 | 40462.6 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.06756289 | 60.00 | 32.22 | 27.78 | 0.000 | 7723.64 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00757861 | 21.11 | 0.00757861 | 39.5285 | 7723.73 | 0.00 | 8326.14 | 8326.14 | 0.40095804 | 16.60 | 12.74 | 0.00757861 | 35867.9 | 36.98 | 19.95 | 0.00757861 | 56633.5 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12888.370 | -999.000 | 1.425914 | 0.00046033 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6740 | 1004.8586 | 0.9774 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.425914 | 1.39374204 | 4197.9300 | 999.8980 | 25.92203020 | 13.37 | 6.70 | 6.67 | 725821.85 | 1.7757 | 1.775660 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 12888.37 | 12845.87 | 1.0000 | 1.39374204 | 1.425914 | 21.82 | 13.52 | 0.00851772 | 43569.5 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.46028717 | 6.70 | 13.37 | 6.67 | 0.000 | 12888.37 | 31.83 | 0.00547208 | 14.39 | 0.00000000 | 0.0000 | 21.11 | 0.00851772 | 21.11 | 0.00851772 | 44.3564 | 11822.32 | 0.00 | 16230.69 | 15174.71 | 1.39374204 | 21.82 | 15.62 | 0.00851772 | 43569.5 | 11.15 | 11.12 | 0.00821726 | 31924.1 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7729.260 | 7729.260 | 0.410512 | 0.00006762 | 220.868 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.425914 | 1.39374204 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 1.3489 | 1.376053 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 7729.26 | 7729.26 | 1.0000 | 0.40124974 | 0.410512 | 21.11 | 12.48 | 0.00757893 | 40463.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.06761204 | 60.00 | 32.22 | 27.78 | 0.000 | 7729.26 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00757893 | 21.11 | 0.00757893 | 39.5301 | 7729.35 | 0.00 | 8332.20 | 8332.20 | 0.40124974 | 16.60 | 12.74 | 0.00757893 | 35868.7 | 36.98 | 19.96 | 0.00757893 | 56634.3 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 69790.026 | -999.000 | 7.759386 | 0.00249269 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5594 | 1004.8586 | 0.9774 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.759386 | 7.58431608 | 4197.9300 | 999.8980 | 25.92203020 | 13.37 | 6.70 | 6.67 | 725821.85 | 9.6153 | 9.615131 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | Sensible | 69790.03 | 69790.03 | 1.0000 | 7.58431608 | 7.759386 | 21.82 | 13.47 | 0.00845608 | 43413.2 | 12.80 | 10.17 | 0.00845608 | 34211.3 | 2.49243719 | 6.70 | 13.37 | 6.67 | 0.000 | 69790.03 | 33.53 | 0.00547470 | 14.95 | 0.00000000 | 0.0000 | 21.11 | 0.00845608 | 21.11 | 0.00845608 | 44.0390 | 64335.40 | 0.00 | 88066.35 | 83007.99 | 7.58431608 | 21.82 | 15.56 | 0.00845608 | 43413.2 | 11.09 | 11.07 | 0.00819158 | 31801.5 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 44161.008 | 44161.008 | 2.345559 | 0.00038634 | 1261.915 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.759386 | 7.58431608 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 7.7069 | 7.862055 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 44161.01 | 44161.01 | 1.0000 | 2.29263716 | 2.345559 | 21.11 | 12.50 | 0.00760760 | 40537.1 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.38630035 | 60.00 | 32.22 | 27.78 | 0.000 | 44161.01 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00760760 | 21.11 | 0.00760760 | 39.6758 | 44161.28 | 0.00 | 47606.56 | 47606.56 | 2.29263716 | 16.60 | 12.77 | 0.00760760 | 35941.3 | 36.98 | 19.98 | 0.00760760 | 56706.2 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 65356.725 | -999.000 | 6.889281 | 0.00233435 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0098 | 1004.8586 | 0.9774 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.889281 | 6.73384194 | 4197.9300 | 999.8980 | 25.92203020 | 13.37 | 6.70 | 6.67 | 725821.85 | 9.0045 | 9.004345 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | unknown | unknown | unknown | 7/21 15:10:00 | Sensible | 65356.72 | 63021.79 | 1.0000 | 6.73384194 | 6.889281 | 21.82 | 13.68 | 0.00869836 | 44027.9 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 2.33410906 | 6.70 | 13.37 | 6.67 | 0.000 | 65356.72 | 33.75 | 0.00547504 | 15.02 | 0.00000000 | 0.0000 | 21.11 | 0.00869836 | 21.11 | 0.00869836 | 45.2854 | 57116.22 | 0.00 | 81834.00 | 73436.24 | 6.73384194 | 21.82 | 15.78 | 0.00869836 | 44027.9 | 11.13 | 11.10 | 0.00820380 | 31875.3 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 44283.930 | 44283.930 | 2.352087 | 0.00038742 | 1265.427 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.889281 | 6.73384194 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 7.7284 | 7.883938 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 44283.93 | 44283.93 | 1.0000 | 2.29901868 | 2.352087 | 21.11 | 12.50 | 0.00760853 | 40539.5 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.38737561 | 60.00 | 32.22 | 27.78 | 0.000 | 44283.93 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00760853 | 21.11 | 0.00760853 | 39.6806 | 44284.20 | 0.00 | 47739.08 | 47739.08 | 2.29901868 | 16.60 | 12.77 | 0.00760853 | 35943.6 | 36.98 | 19.98 | 0.00760853 | 56708.6 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11476.060 | -999.000 | 1.269262 | 0.00040989 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6761 | 1004.8586 | 0.9774 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.269262 | 1.24062465 | 4197.9300 | 999.8980 | 25.92203020 | 13.37 | 6.70 | 6.67 | 725821.85 | 1.5811 | 1.581083 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | unknown | unknown | 7/21 09:40:00 | Sensible | 11476.06 | 11435.78 | 1.0000 | 1.24062465 | 1.269262 | 21.82 | 13.53 | 0.00851886 | 43572.4 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.40984882 | 6.70 | 13.37 | 6.67 | 0.000 | 11476.06 | 27.44 | 0.00546540 | 12.88 | 0.00000000 | 0.0000 | 21.11 | 0.00851886 | 21.11 | 0.00851886 | 44.3623 | 10523.52 | 0.00 | 14451.55 | 13507.74 | 1.24062465 | 21.82 | 15.62 | 0.00851886 | 43572.4 | 11.15 | 11.12 | 0.00821717 | 31923.8 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7723.642 | 7723.642 | 0.410213 | 0.00006757 | 220.707 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.269262 | 1.24062465 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 1.3479 | 1.375052 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 7723.64 | 7723.64 | 1.0000 | 0.40095804 | 0.410213 | 21.11 | 12.48 | 0.00757861 | 40462.6 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.06756289 | 60.00 | 32.22 | 27.78 | 0.000 | 7723.64 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00757861 | 21.11 | 0.00757861 | 39.5285 | 7723.73 | 0.00 | 8326.14 | 8326.14 | 0.40095804 | 16.60 | 12.74 | 0.00757861 | 35867.9 | 36.98 | 19.95 | 0.00757861 | 56633.5 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11196.188 | -999.000 | 1.238205 | 0.00039989 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6767 | 1004.8586 | 0.9774 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.238205 | 1.21026803 | 4197.9300 | 999.8980 | 25.92203020 | 13.37 | 6.70 | 6.67 | 725821.85 | 1.5426 | 1.542524 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | unknown | unknown | unknown | 7/21 09:20:00 | Sensible | 11196.19 | 11156.26 | 1.0000 | 1.21026803 | 1.238205 | 21.82 | 13.53 | 0.00851916 | 43573.2 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.39985365 | 6.70 | 13.37 | 6.67 | 0.000 | 11196.19 | 26.60 | 0.00546414 | 12.59 | 0.00000000 | 0.0000 | 21.11 | 0.00851916 | 21.11 | 0.00851916 | 44.3638 | 10266.03 | 0.00 | 14098.96 | 13177.25 | 1.21026803 | 21.82 | 15.62 | 0.00851916 | 43573.2 | 11.15 | 11.12 | 0.00821715 | 31923.7 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7729.260 | 7729.260 | 0.410512 | 0.00006762 | 220.868 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.238205 | 1.21026803 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 1.3489 | 1.376053 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 7729.26 | 7729.26 | 1.0000 | 0.40124974 | 0.410512 | 21.11 | 12.48 | 0.00757893 | 40463.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.06761204 | 60.00 | 32.22 | 27.78 | 0.000 | 7729.26 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00757893 | 21.11 | 0.00757893 | 39.5301 | 7729.35 | 0.00 | 8332.20 | 8332.20 | 0.40124974 | 16.60 | 12.74 | 0.00757893 | 35868.7 | 36.98 | 19.96 | 0.00757893 | 56634.3 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15159.443 | 15159.443 | 0.718654 | 0.00013262 | 399.417 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 2.6456 | 2.698860 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 15159.44 | 15159.44 | 1.0000 | 0.70243927 | 0.718654 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.13260789 | 60.00 | 32.22 | 27.78 | 0.000 | 15159.44 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00766790 | 21.00 | 0.00766790 | 40.2589 | 12081.49 | 0.00 | 15235.37 | 15235.37 | 0.70243927 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 37.87 | 20.54 | 0.00800000 | 58624.0 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3514.212 | -999.000 | 0.388947 | 0.00012552 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6714 | 1004.8586 | 0.9774 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.388947 | 0.38017141 | 4197.9300 | 999.8980 | 25.92203020 | 13.37 | 6.70 | 6.67 | 725821.85 | 0.4842 | 0.484161 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 3514.21 | 3503.54 | 1.0000 | 0.38017141 | 0.388947 | 21.82 | 13.52 | 0.00851631 | 43566.0 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.12550437 | 6.70 | 13.37 | 6.67 | 0.000 | 3514.21 | 32.03 | 0.00547238 | 14.46 | 0.00000000 | 0.0000 | 21.11 | 0.00851631 | 21.11 | 0.00851631 | 44.3492 | 3224.78 | 0.00 | 4425.77 | 4139.17 | 0.38017141 | 21.82 | 15.62 | 0.00851631 | 43566.0 | 11.15 | 11.12 | 0.00821736 | 31924.5 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2371.730 | 2371.730 | 0.125966 | 0.00002075 | 67.771 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.388947 | 0.38017141 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 0.4139 | 0.422243 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 2371.73 | 2371.73 | 1.0000 | 0.12312407 | 0.125966 | 21.11 | 12.54 | 0.00765300 | 40651.6 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.02074682 | 60.00 | 32.22 | 27.78 | 0.000 | 2371.73 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00765300 | 21.11 | 0.00765300 | 39.9117 | 2371.76 | 0.00 | 2556.74 | 2556.74 | 0.12312407 | 16.60 | 12.81 | 0.00765300 | 36056.2 | 36.98 | 20.01 | 0.00765300 | 56821.8 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3416.666 | -999.000 | 0.378108 | 0.00012203 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6722 | 1004.8586 | 0.9774 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.378108 | 0.36957696 | 4197.9300 | 999.8980 | 25.92203020 | 13.37 | 6.70 | 6.67 | 725821.85 | 0.4707 | 0.470722 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3416.67 | 3406.03 | 1.0000 | 0.36957696 | 0.378108 | 21.82 | 13.52 | 0.00851673 | 43567.0 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.12202065 | 6.70 | 13.37 | 6.67 | 0.000 | 3416.67 | 31.83 | 0.00547208 | 14.39 | 0.00000000 | 0.0000 | 21.11 | 0.00851673 | 21.11 | 0.00851673 | 44.3513 | 3134.91 | 0.00 | 4302.86 | 4023.83 | 0.36957696 | 21.82 | 15.62 | 0.00851673 | 43567.0 | 11.15 | 11.12 | 0.00821733 | 31924.3 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2371.619 | 2371.619 | 0.125960 | 0.00002075 | 67.767 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.378108 | 0.36957696 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 0.4139 | 0.422223 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 2371.62 | 2371.62 | 1.0000 | 0.12311829 | 0.125960 | 21.11 | 12.54 | 0.00765301 | 40651.6 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.02074584 | 60.00 | 32.22 | 27.78 | 0.000 | 2371.62 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00765301 | 21.11 | 0.00765301 | 39.9117 | 2371.64 | 0.00 | 2556.62 | 2556.62 | 0.12311829 | 16.60 | 12.81 | 0.00765301 | 36056.2 | 36.98 | 20.01 | 0.00765301 | 56821.8 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15225.876 | -999.000 | 1.657394 | 0.00054382 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7850 | 1004.8586 | 0.9774 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.657394 | 1.61999931 | 4197.9300 | 999.8980 | 25.92203020 | 13.37 | 6.70 | 6.67 | 725821.85 | 2.0977 | 2.097704 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 15225.88 | 15008.83 | 1.0000 | 1.61999931 | 1.657394 | 21.82 | 13.57 | 0.00857742 | 43720.9 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.54376737 | 6.70 | 13.37 | 6.67 | 0.000 | 15225.88 | 33.65 | 0.00547489 | 14.99 | 0.00000000 | 0.0000 | 21.11 | 0.00857742 | 21.11 | 0.00857742 | 44.6639 | 13741.06 | 0.00 | 19137.05 | 17647.24 | 1.61999931 | 21.82 | 15.67 | 0.00857742 | 43720.9 | 11.14 | 11.11 | 0.00821273 | 31907.9 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11367.199 | 11367.199 | 0.603739 | 0.00009945 | 324.809 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.657394 | 1.61999931 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 1.9838 | 2.023721 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 11367.20 | 11367.20 | 1.0000 | 0.59011705 | 0.603739 | 21.11 | 12.55 | 0.00766598 | 40684.9 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.09943507 | 60.00 | 32.22 | 27.78 | 0.000 | 11367.20 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00766598 | 21.11 | 0.00766598 | 39.9777 | 11367.30 | 0.00 | 12254.00 | 12254.00 | 0.59011705 | 16.60 | 12.83 | 0.00766598 | 36089.1 | 36.98 | 20.02 | 0.00766598 | 56854.4 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15432.481 | 15432.481 | 1.798749 | 0.00013501 | 339.523 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 2.6933 | 2.747469 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 15432.48 | 15432.48 | 1.0000 | 1.75816445 | 1.798749 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.13499631 | 60.00 | 32.22 | 27.78 | 0.000 | 15432.48 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00773524 | 21.00 | 0.00773524 | 40.6088 | 7728.06 | 0.00 | 15516.65 | 15516.65 | 1.75816445 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.25 | 16.40 | 0.00800000 | 45760.2 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15588.554 | 15588.554 | 1.797271 | 0.00013638 | 343.373 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 2.7205 | 2.775255 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 15588.55 | 15588.55 | 1.0000 | 1.75672044 | 1.797271 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.13636156 | 60.00 | 32.22 | 27.78 | 0.000 | 15588.55 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00774048 | 21.00 | 0.00774048 | 40.6360 | 7890.38 | 0.00 | 15673.53 | 15673.53 | 1.75672044 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.35 | 16.44 | 0.00800000 | 45856.8 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6795.667 | 6795.667 | 0.837743 | 0.00005945 | 148.626 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 1.1860 | 1.209843 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 6795.67 | 6795.67 | 1.0000 | 0.81884156 | 0.837743 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.05944539 | 60.00 | 32.22 | 27.78 | 0.000 | 6795.67 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.69 | 0.00719256 | 21.00 | 0.00719256 | 37.7974 | 3212.80 | 0.00 | 6833.29 | 6833.29 | 0.81884156 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.78 | 16.24 | 0.00800000 | 45279.8 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9894.587 | 9894.587 | 0.426095 | 0.00008656 | 270.042 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 1.7268 | 1.761549 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 9894.59 | 9894.59 | 1.0000 | 0.41648168 | 0.426095 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.08655333 | 60.00 | 32.22 | 27.78 | 0.000 | 9894.59 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00777648 | 21.00 | 0.00777648 | 40.8221 | 8069.32 | 0.00 | 9943.66 | 9943.66 | 0.41648168 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60810.1 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 474600.853 | -999.000 | 26.844674 | 0.01695164 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3727 | 1004.8586 | 0.9774 | VAV WITH REHEAT FAN | Fan:VariableVolume | 26.844674 | 26.23899453 | 4197.9300 | 999.8980 | 25.92203020 | 13.37 | 6.70 | 6.67 | 725821.85 | 65.3881 | 65.388064 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 474600.85 | 474600.85 | 1.0000 | 26.23899453 | 26.844674 | 28.30 | 15.12 | 0.00781768 | 48394.8 | 10.55 | 8.65 | 0.00781768 | 30307.2 | 16.94991358 | 6.70 | 13.37 | 6.67 | 60149.214 | 414451.64 | 33.90 | 0.00547527 | 15.07 | 11.66146000 | 43.4405 | 23.99 | 0.00961752 | 23.99 | 0.00957900 | 41.8042 | 299619.75 | 0.00 | 564021.54 | 516959.38 | 26.23899453 | 28.30 | 17.31 | 0.00781768 | 48394.8 | 8.97 | 8.96 | 0.00710526 | 26899.2 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 273684.052 | 273684.052 | 8.053402 | 0.00239431 | 4245.690 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV WITH REHEAT FAN | Fan:VariableVolume | 26.844674 | 26.23899453 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 47.7632 | 48.724407 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 273684.05 | 273684.05 | 1.0000 | 7.87169836 | 8.053402 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 2.39406324 | 60.00 | 32.22 | 27.78 | 0.000 | 273684.05 | -17.90 | 0.00095524 | -17.90 | 11.66146000 | 144.8017 | 18.69 | 0.00689512 | 21.20 | 0.00672659 | 34.9312 | 77688.21 | 0.00 | 217770.06 | 217770.06 | 7.87169836 | 2.80 | -2.86 | 0.00095524 | 5207.5 | 30.28 | 11.67 | 0.00095524 | 32872.5 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 45136.603 | -999.000 | 2.051317 | 0.00161217 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1015.0183 | 1004.8586 | 0.9774 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.00496413 | 4197.9300 | 999.8980 | 25.92203020 | 13.37 | 6.70 | 6.67 | 725821.85 | 6.2187 | 6.218689 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 45136.60 | 45136.60 | 1.0000 | 2.00503462 | 2.051317 | 33.90 | 15.07 | 0.00547527 | 48102.5 | 11.72 | 6.72 | 0.00547527 | 25590.8 | 1.61201042 | 6.70 | 13.37 | 6.67 | 2195.006 | 42941.60 | 33.90 | 0.00547527 | 15.07 | 2.05124512 | 99.9965 | 21.11 | 0.00856056 | 21.11 | 0.00857053 | 44.6279 | 173752.15 | 0.00 | 45179.60 | 45179.60 | 2.00503462 | 33.90 | 17.27 | 0.00547527 | 48102.5 | 11.70 | 8.38 | 0.00547527 | 25569.4 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 20913.378 | 20913.378 | 0.615395 | 0.00018296 | 324.431 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.00496413 | 4197.9300 | 999.8980 | 4.91347843 | 54.44 | 82.22 | 27.78 | 573002.46 | 3.6498 | 3.723242 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 20913.38 | 20913.38 | 1.0000 | 0.60151039 | 0.615395 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 16.70 | 11.24 | 0.00800000 | 37036.7 | 0.18294069 | 60.00 | 32.22 | 27.78 | 0.000 | 20913.38 | -17.90 | 0.00095524 | -17.90 | 2.05124512 | 333.3216 | 21.11 | 0.00760782 | 21.11 | 0.00760843 | 39.6801 | 135462.34 | 0.00 | 16640.75 | 16640.75 | 0.60151039 | 2.80 | -2.86 | 0.00095524 | 5207.5 | 30.28 | 11.67 | 0.00095524 | 32872.5 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 11.66 | 26.84 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 673.17 | 5939.00 | 354.33 |
RETAIL_1_FLR_1 | 3238.67 | 5171.00 | 1059.33 |
RETAIL_2_FLR_1 | 1223.00 | 6138.00 | 431.33 |
MECH_FLR_1 | 991.83 | 6790.17 | 461.67 |
STORAGE_FLR_1 | 701.33 | 8682.83 | 699.83 |
LAUNDRY_FLR_1 | 8678.83 | 3462.83 | 3452.50 |
CAFE_FLR_1 | 3277.67 | 4825.83 | 766.17 |
LOBBY_FLR_1 | 1855.67 | 4349.67 | 508.00 |
ROOM_1_FLR_3 | 1807.67 | 8203.17 | 1728.67 |
ROOM_2_FLR_3 | 2644.67 | 8440.00 | 2604.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 2169.17 | 8760.00 | 2169.17 |
ROOM_5_FLR_3 | 1817.00 | 8080.83 | 1735.50 |
ROOM_6_FLR_3 | 2649.17 | 8280.83 | 2610.50 |
CORRIDOR_FLR_3 | 944.83 | 7120.50 | 612.33 |
ROOM_1_FLR_6 | 2662.17 | 8109.83 | 2515.83 |
ROOM_2_FLR_6 | 3649.50 | 8358.33 | 3561.17 |
ROOM_3_MULT9_FLR_6 | 1456.83 | 7783.17 | 1299.33 |
BANQUET_FLR_6 | 2480.33 | 5154.50 | 527.00 |
DINING_FLR_6 | 3279.00 | 3919.17 | 493.17 |
KITCHEN_FLR_6 | 8687.67 | 6258.67 | 6245.33 |
CORRIDOR_FLR_6 | 1499.67 | 6314.17 | 737.00 |
Facility | 8760.00 | 8760.00 | 7896.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.17 | 0.00 | 0.17 |
RETAIL_1_FLR_1 | 0.00 | 7.50 | 0.00 | 7.50 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 385.50 | 0.00 | 385.50 |
CAFE_FLR_1 | 0.00 | 20.00 | 0.00 | 20.00 |
LOBBY_FLR_1 | 0.00 | 4.83 | 0.00 | 4.83 |
ROOM_1_FLR_3 | 0.00 | 0.17 | 0.00 | 0.17 |
ROOM_2_FLR_3 | 0.00 | 0.17 | 0.00 | 0.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.67 | 0.00 | 0.67 |
ROOM_5_FLR_3 | 0.00 | 3.17 | 0.00 | 3.17 |
ROOM_6_FLR_3 | 0.00 | 3.00 | 0.00 | 3.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.50 | 0.00 | 0.50 |
ROOM_2_FLR_6 | 0.00 | 0.17 | 0.00 | 0.17 |
ROOM_3_MULT9_FLR_6 | 0.00 | 1.17 | 0.00 | 1.17 |
BANQUET_FLR_6 | 0.00 | 40.00 | 0.00 | 40.00 |
DINING_FLR_6 | 0.00 | 58.67 | 0.00 | 58.67 |
KITCHEN_FLR_6 | 0.00 | 625.17 | 0.00 | 625.17 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 697.67 | 0.00 | 697.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 106.50 | 4826.41 | 0.971 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.26 | 10.83 | 265.76 | 2.161 | 0.139 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.25 | 12.54 | 307.76 | 1.466 | 0.046 | 0.000 | 0.000 |
MECH_FLR_1 | 1.53 | 2.65 | 650.80 | 0.451 | 0.052 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.714 | 0.052 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 21.267 | 0.150 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.31 | 142.30 | 748.35 | 4.466 | 0.109 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.35 | 422.44 | 5183.56 | 1.844 | 0.045 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.471 | 0.180 | 0.000 | 0.053 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.471 | 0.180 | 0.000 | 0.051 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.534 | 0.080 | 0.000 | 0.081 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.471 | 0.180 | 0.000 | 0.053 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.471 | 0.180 | 0.000 | 0.052 |
CORRIDOR_FLR_3 | 12.12 | 20.96 | 1186.91 | 0.494 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.471 | 0.180 | 0.000 | 0.063 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.471 | 0.180 | 0.000 | 0.061 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.535 | 0.146 | 0.000 | 0.100 |
BANQUET_FLR_6 | 144.55 | 249.90 | 1010.89 | 5.700 | 0.052 | 0.000 | 0.000 |
DINING_FLR_6 | 144.55 | 249.90 | 1010.89 | 5.827 | 0.052 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.86 | 22.24 | 314.87 | 21.950 | 0.150 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.83 | 22.18 | 1256.16 | 0.840 | 0.037 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 106.50 | 4826.41 | 0.461 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.26 | 10.83 | 265.76 | 0.900 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.25 | 12.54 | 307.76 | 0.781 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.53 | 2.65 | 650.80 | 0.217 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.394 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 6.845 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.31 | 142.30 | 748.35 | 2.380 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.35 | 422.44 | 5183.56 | 0.952 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.459 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.458 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.521 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.460 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.459 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.12 | 20.96 | 1186.91 | 0.258 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.459 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.458 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.522 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.55 | 249.90 | 1010.89 | 3.074 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.55 | 249.90 | 1010.89 | 3.074 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.86 | 22.24 | 314.87 | 4.656 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.83 | 22.18 | 1256.16 | 0.395 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.60 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.26 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.25 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.53 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.86 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.31 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.35 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.12 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.55 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.55 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.86 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.83 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 870.81 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 40379549.19 | 0.00 | 40379549.19 | 0.00 | 40379549.19 | 26946214.98 | 69.90 | 8.58 | 8681.52 | 0.00 |
RETAIL_1_FLR_1 | 4968310.54 | 0.00 | 4968310.54 | 319936.80 | 5288247.34 | 2498216.28 | 46.52 | 19.99 | 8693.49 | 0.00 |
RETAIL_2_FLR_1 | 3895354.86 | 0.00 | 3895354.86 | 123496.01 | 4018850.87 | 2892943.94 | 330.24 | 104.83 | 8324.93 | 0.00 |
MECH_FLR_1 | 2538138.08 | 0.00 | 2538138.08 | 291871.20 | 2830009.28 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 2326826.50 | 0.00 | 2326826.50 | 168393.60 | 2495220.11 | 1821682.01 | 575.36 | 125.02 | 8059.63 | 0.00 |
LAUNDRY_FLR_1 | 56694790.96 | 0.00 | 56694790.96 | 398535.21 | 57093326.17 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 28856093.91 | 0.00 | 28856093.91 | 707238.41 | 29563332.32 | 21330615.53 | 456.40 | 121.77 | 8181.83 | 0.00 |
LOBBY_FLR_1 | 82355951.68 | 0.00 | 82355951.68 | 2020741.67 | 84376693.35 | 59728886.00 | 221.60 | 80.52 | 8457.88 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 54904.08 | 2001779.70 | 185701.25 | 2187480.95 | 1946875.62 | 0.00 | 8008.00 | 752.00 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 53390.49 | 2000038.01 | 185687.09 | 2185725.09 | 1946647.51 | 0.00 | 8008.00 | 752.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 58791.55 | 26456678.82 | 51812.73 | 26508491.56 | 26397887.27 | 0.00 | 8018.67 | 741.33 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 52978.92 | 26458084.65 | 51826.90 | 26509911.55 | 26405105.73 | 0.00 | 8023.48 | 736.52 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 55068.24 | 2001943.85 | 185701.25 | 2187645.11 | 1946875.62 | 0.00 | 8008.00 | 752.00 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 53517.05 | 2000164.56 | 185687.09 | 2185851.65 | 1946647.51 | 0.00 | 8008.00 | 752.00 | 0.00 |
CORRIDOR_FLR_3 | 20264763.14 | 0.00 | 20264763.14 | 224550.18 | 20489313.32 | 14972100.18 | 450.23 | 120.96 | 8188.81 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 65543.35 | 552262.25 | 185740.37 | 738002.62 | 486718.90 | 0.00 | 8008.83 | 751.17 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 63587.88 | 550249.75 | 185726.20 | 735975.95 | 486661.88 | 0.00 | 8008.83 | 751.17 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 65488.28 | 3192408.70 | 95031.27 | 3287439.97 | 3126920.42 | 0.00 | 8008.83 | 751.17 | 0.00 |
BANQUET_FLR_6 | 49708608.00 | 0.00 | 49708608.00 | 453531.30 | 50162139.30 | 37458366.31 | 323.37 | 129.58 | 8307.06 | 0.00 |
DINING_FLR_6 | 50776229.81 | 0.00 | 50776229.81 | 453531.30 | 51229761.11 | 37458366.31 | 221.80 | 94.36 | 8443.85 | 0.00 |
KITCHEN_FLR_6 | 59501010.17 | 0.00 | 59501010.17 | 406015.66 | 59907025.83 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 9122473.74 | 0.00 | 9122473.74 | 397385.47 | 9519859.21 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.45E+10 | 10080600.96 | 0.46E+10 | 18713344.22 | 0.46E+10 | 0.43E+10 | 575.87 | 8031.76 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.2804 | 0.0000 | 1.2804 | 0.0000 | 1.2804 | 0.8545 | 69.90 | 8.58 | 8681.52 |
RETAIL_1_FLR_1 | 0.1575 | 0.0000 | 0.1575 | 0.0101 | 0.1677 | 0.0792 | 46.52 | 19.99 | 8693.49 |
RETAIL_2_FLR_1 | 0.1235 | 0.0000 | 0.1235 | 0.0039 | 0.1274 | 0.0917 | 330.24 | 104.83 | 8324.93 |
MECH_FLR_1 | 0.0805 | 0.0000 | 0.0805 | 0.0093 | 0.0897 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0738 | 0.0000 | 0.0738 | 0.0053 | 0.0791 | 0.0578 | 575.36 | 125.02 | 8059.63 |
LAUNDRY_FLR_1 | 1.7978 | 0.0000 | 1.7978 | 0.0126 | 1.8104 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.9150 | 0.0000 | 0.9150 | 0.0224 | 0.9374 | 0.6764 | 456.40 | 121.77 | 8181.83 |
LOBBY_FLR_1 | 2.6115 | 0.0000 | 2.6115 | 0.0641 | 2.6756 | 1.8940 | 221.60 | 80.52 | 8457.88 |
ROOM_1_FLR_3 | 0.0617 | 0.0017 | 0.0635 | 0.0059 | 0.0694 | 0.0617 | 0.00 | 8008.00 | 752.00 |
ROOM_2_FLR_3 | 0.0617 | 0.0017 | 0.0634 | 0.0059 | 0.0693 | 0.0617 | 0.00 | 8008.00 | 752.00 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0017 | 0.8390 | 0.0016 | 0.8406 | 0.8373 | 0.00 | 8023.48 | 736.52 |
ROOM_5_FLR_3 | 0.0617 | 0.0017 | 0.0635 | 0.0059 | 0.0694 | 0.0617 | 0.00 | 8008.00 | 752.00 |
ROOM_6_FLR_3 | 0.0617 | 0.0017 | 0.0634 | 0.0059 | 0.0693 | 0.0617 | 0.00 | 8008.00 | 752.00 |
CORRIDOR_FLR_3 | 0.6426 | 0.0000 | 0.6426 | 0.0071 | 0.6497 | 0.4748 | 450.23 | 120.96 | 8188.81 |
ROOM_1_FLR_6 | 0.0154 | 0.0021 | 0.0175 | 0.0059 | 0.0234 | 0.0154 | 0.00 | 8008.83 | 751.17 |
ROOM_2_FLR_6 | 0.0154 | 0.0020 | 0.0174 | 0.0059 | 0.0233 | 0.0154 | 0.00 | 8008.83 | 751.17 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0021 | 0.1012 | 0.0030 | 0.1042 | 0.0992 | 0.00 | 8008.83 | 751.17 |
BANQUET_FLR_6 | 1.5762 | 0.0000 | 1.5762 | 0.0144 | 1.5906 | 1.1878 | 323.37 | 129.58 | 8307.06 |
DINING_FLR_6 | 1.6101 | 0.0000 | 1.6101 | 0.0144 | 1.6245 | 1.1878 | 221.80 | 94.36 | 8443.85 |
KITCHEN_FLR_6 | 1.8868 | 0.0000 | 1.8868 | 0.0129 | 1.8996 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.2893 | 0.0000 | 0.2893 | 0.0126 | 0.3019 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 80.5186 | 0.1780 | 80.6966 | 0.4685 | 81.1651 | 73.9670 | 575.87 | 8031.76 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.39E+09 | 0.00 | 0.39E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 61804134.73 | 523269.83 | 62327404.56 | 64690340.46 | 8014.82 | 54.20 | 690.99 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 12.4627 | 0.0000 | 12.4627 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.9598 | 0.0166 | 1.9764 | 2.0513 | 8014.82 | 54.20 | 690.99 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 5415.00 | 3345.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 11.1432 | 14.6021 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 1.9600 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1318 |
Defaulted Fields | 1181 |
Fields with Defaults | 4005 |
Autosized Fields | 350 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5313.01 | 72798.18 | 13-MAY-05:00 | 406199.36 | 26-JUN-19:30 |
Electricity:Building | 2518.61 | 32563.12 | 27-MAY-05:00 | 151906.32 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 323.72 | 3705.45 | 02-JAN-02:10 | 24299.15 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2511.52 | 32421.97 | 27-MAY-05:00 | 151664.99 | 02-JAN-20:10 |
InteriorLights:Electricity | 766.51 | 6730.17 | 27-MAY-05:00 | 62892.57 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 173.46 | 1576.23 | 02-JAN-02:10 | 14185.34 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 766.51 | 6730.17 | 27-MAY-05:00 | 62892.57 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 766.51 | 6730.17 | 27-MAY-05:00 | 62892.57 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 173.46 | 1576.23 | 02-JAN-02:10 | 14185.34 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 766.51 | 6730.17 | 27-MAY-05:00 | 62892.57 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.80 | 222.61 | 02-JAN-02:10 | 1390.02 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.61 | 78.27 | 02-JAN-02:10 | 704.41 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.61 | 78.27 | 02-JAN-02:10 | 704.41 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.77 | 257.78 | 02-JAN-02:10 | 1609.65 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.97 | 90.64 | 02-JAN-02:10 | 815.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.97 | 90.64 | 02-JAN-02:10 | 815.72 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 29.11 | 327.88 | 02-JAN-02:10 | 2199.84 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 16.64 | 151.16 | 02-JAN-02:10 | 1360.40 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 16.64 | 151.16 | 02-JAN-02:10 | 1360.40 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.38 | 76.28 | 02-JAN-02:10 | 469.87 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.78 | 25.30 | 02-JAN-02:10 | 227.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.78 | 25.30 | 02-JAN-02:10 | 227.72 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.30 | 1002.39 | 02-JAN-02:10 | 4930.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.37 | 39.69 | 02-JAN-02:10 | 357.21 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.37 | 39.69 | 02-JAN-02:10 | 357.21 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 32.26 | 348.08 | 20-MAY-05:00 | 2727.18 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 17.92 | 144.87 | 20-MAY-05:00 | 1761.91 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 17.92 | 144.87 | 20-MAY-05:00 | 1761.91 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 270.84 | 3198.76 | 27-MAY-05:00 | 20294.39 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 121.84 | 1087.35 | 27-MAY-05:00 | 10265.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 121.84 | 1087.35 | 27-MAY-05:00 | 10265.18 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 18.66 | 264.62 | 01-JAN-02:10 | 1227.54 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 18.66 | 264.59 | 01-JAN-02:10 | 1227.39 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 304.77 | 4565.05 | 01-JAN-02:10 | 20923.25 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 76.02 | 643.59 | 01-JAN-02:10 | 5851.22 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 76.02 | 643.59 | 01-JAN-02:10 | 5851.22 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 304.86 | 4566.30 | 01-JAN-02:10 | 20928.98 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 76.04 | 643.77 | 01-JAN-02:10 | 5852.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 76.04 | 643.77 | 01-JAN-02:10 | 5852.82 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 18.66 | 264.62 | 01-JAN-02:10 | 1227.54 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 18.66 | 264.59 | 01-JAN-02:10 | 1227.39 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.66 | 66.15 | 01-JAN-02:10 | 306.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.50 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.50 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.66 | 66.15 | 01-JAN-02:10 | 306.85 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.49 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.49 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.10 | 540.75 | 01-JAN-02:10 | 2478.43 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 9.00 | 76.24 | 01-JAN-02:10 | 693.10 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 9.00 | 76.24 | 01-JAN-02:10 | 693.10 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 210.49 | 2524.33 | 20-MAY-05:00 | 9841.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 34.63 | 275.03 | 20-MAY-05:00 | 3094.06 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 34.63 | 275.03 | 20-MAY-05:00 | 3094.06 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 210.49 | 2524.33 | 20-MAY-05:00 | 9841.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 34.63 | 275.03 | 20-MAY-05:00 | 3094.06 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 34.63 | 275.03 | 20-MAY-05:00 | 3094.06 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 454.16 | 6253.02 | 02-JAN-02:10 | 18944.06 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.33 | 121.09 | 02-JAN-02:10 | 1089.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.33 | 121.09 | 02-JAN-02:10 | 1089.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1745.01 | 25691.80 | 02-JAN-02:10 | 89475.41 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1745.01 | 25691.80 | 02-JAN-02:10 | 89475.41 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.61 | 1113.62 | 04-DEC-23:30 | 3482.48 | 28-APR-06:00 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1062.41 | 2625.31 | 04-MAY-01:50 | 187441.91 | 26-JUN-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.53 | 0.00 | 01-JAN-11:10 | 2063.71 | 28-APR-06:00 |
MedTempRefrigeration:Refrigeration:Electricity | 33.99 | 963.92 | 14-OCT-04:00 | 1245.48 | 06-JAN-15:20 |
Fans:Electricity | 637.04 | 11924.45 | 12-MAR-04:10 | 52608.46 | 12-SEP-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 870.32 | 14474.46 | 09-MAY-01:30 | 62200.10 | 16-AUG-21:10 |
ExteriorEquipment:Electricity | 651.48 | 9618.58 | 02-JAN-02:20 | 39726.11 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 32.45 | 553.74 | 27-MAY-05:00 | 1868.65 | 28-FEB-21:10 |
ElectricityPurchased:Facility | 5313.01 | 72798.18 | 13-MAY-05:00 | 406199.36 | 26-JUN-19:30 |
ElectricityPurchased:Plant | 5313.01 | 72798.18 | 13-MAY-05:00 | 406199.36 | 26-JUN-19:30 |
Cogeneration:ElectricityPurchased | 5313.01 | 72798.18 | 13-MAY-05:00 | 406199.36 | 26-JUN-19:30 |
General:Cogeneration:ElectricityPurchased | 5313.01 | 72798.18 | 13-MAY-05:00 | 406199.36 | 26-JUN-19:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5313.01 | 72798.18 | 13-MAY-05:00 | 406199.36 | 26-JUN-19:30 |
ElectricityNet:Plant | 5313.01 | 72798.18 | 13-MAY-05:00 | 406199.36 | 26-JUN-19:30 |
Cogeneration:ElectricityNet | 5313.01 | 72798.18 | 13-MAY-05:00 | 406199.36 | 26-JUN-19:30 |
General:Cogeneration:ElectricityNet | 5313.01 | 72798.18 | 13-MAY-05:00 | 406199.36 | 26-JUN-19:30 |
General:Fans:Electricity | 637.04 | 11924.45 | 12-MAR-04:10 | 52608.46 | 12-SEP-21:10 |
ExteriorLights:Electricity | 242.64 | 0.00 | 01-JAN-07:30 | 15448.40 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 242.64 | 0.00 | 01-JAN-07:30 | 15448.40 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 200.83 | 0.00 | 09-JAN-12:50 | 9938.94 | 01-JAN-09:00 |
General:HeatRecovery:Electricity | 200.83 | 0.00 | 09-JAN-12:50 | 9938.94 | 01-JAN-09:00 |
WaterSystems:Electricity | 90.74 | 1086.43 | 05-DEC-03:20 | 4738.69 | 14-DEC-19:10 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.43 | 05-DEC-03:20 | 4738.69 | 14-DEC-19:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 778.60 | 0.00 | 01-JAN-00:30 | 173015.58 | 26-JUN-18:10 |
General:Cooling:Electricity | 778.60 | 0.00 | 01-JAN-00:30 | 173015.58 | 26-JUN-18:10 |
Pumps:Electricity | 138.55 | 47.91 | 26-MAY-07:10 | 7958.29 | 17-JUL-19:20 |
General:Pumps:Electricity | 138.55 | 47.91 | 26-MAY-07:10 | 7958.29 | 17-JUL-19:20 |
WIRED_LTG_ELECTRICITY | 26.98 | 0.00 | 01-JAN-00:10 | 2213.82 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5806.62 | 29270.80 | 11-MAY-01:10 | 645417.42 | 21-DEC-17:50 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 4017.78 | 15908.90 | 19-APR-10:10 | 555805.21 | 21-DEC-17:50 |
WaterSystems:NaturalGas | 3214.53 | 15908.90 | 01-JAN-16:00 | 302067.72 | 23-JAN-21:30 |
Water Heater:WaterSystems:NaturalGas | 3214.53 | 15908.90 | 01-JAN-16:00 | 302067.72 | 23-JAN-21:30 |
Heating:NaturalGas | 803.26 | 0.00 | 09-JAN-13:50 | 348080.04 | 21-DEC-09:10 |
Boiler:Heating:NaturalGas | 803.26 | 0.00 | 09-JAN-13:50 | 348080.04 | 21-DEC-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2378.17 | 0.00 | 01-JAN-00:30 | 473338.70 | 26-JUN-18:10 |
PlantLoopCoolingDemand:HVAC | 2378.17 | 0.00 | 01-JAN-00:30 | 473338.70 | 26-JUN-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 2378.17 | 0.00 | 01-JAN-00:30 | 473338.70 | 26-JUN-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 10-JAN-21:20 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 10-JAN-21:20 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 10-JAN-21:20 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 10-JAN-01:20 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 10-JAN-21:20 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 10-JAN-21:20 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 10-JAN-21:20 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 10-JAN-01:20 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 09-JAN-07:20 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 09-JAN-07:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 18539.26 | 135209.16 | 23-MAR-13:10 | 2078414.87 | 26-JUN-18:10 |
EnergyTransfer:Building | 5383.68 | 38853.27 | 05-DEC-02:30 | 371644.46 | 26-JUN-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 712.37 | 5741.83 | 09-MAY-02:30 | 36763.81 | 05-AUG-10:50 |
Refrigeration:EnergyTransfer | 180.78 | 3989.95 | 04-DEC-23:10 | 10713.22 | 28-APR-06:00 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.39 | 1994.97 | 04-DEC-23:10 | 5356.61 | 28-APR-06:00 |
General:Refrigeration:EnergyTransfer | 90.39 | 1994.97 | 04-DEC-23:10 | 5356.61 | 28-APR-06:00 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.39 | 1994.97 | 04-DEC-23:10 | 5356.61 | 28-APR-06:00 |
EnergyTransfer:Plant | 7210.64 | 14828.87 | 27-APR-01:10 | 1163474.60 | 26-JUN-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.54 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.86 | 1841.76 | 14-OCT-04:00 | 2686.44 | 06-JAN-15:20 |
EnergyTransfer:Zone:BASEMENT | 404.14 | 1586.15 | 21-JAN-23:50 | 24940.10 | 16-OCT-20:50 |
Heating:EnergyTransfer | 212.77 | 0.00 | 01-JAN-08:10 | 140011.38 | 21-DEC-09:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.25 | 0.00 | 01-JAN-00:10 | 4425.73 | 27-FEB-05:40 |
General:Heating:EnergyTransfer | 212.77 | 0.00 | 01-JAN-08:10 | 140011.38 | 21-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.25 | 0.00 | 01-JAN-00:10 | 4425.73 | 27-FEB-05:40 |
Cooling:EnergyTransfer | 5080.52 | 29385.35 | 05-DEC-02:30 | 368156.43 | 26-JUN-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 403.89 | 933.14 | 09-MAY-02:30 | 24940.10 | 16-OCT-20:50 |
General:Cooling:EnergyTransfer | 5080.52 | 29385.35 | 05-DEC-02:30 | 368156.43 | 26-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 403.89 | 933.14 | 09-MAY-02:30 | 24940.10 | 16-OCT-20:50 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 44.50 | 0.25 | 28-NOV-06:10 | 5311.71 | 07-NOV-12:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 1.78 | 0.00 | 01-JAN-00:10 | 2392.23 | 21-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 1.78 | 0.00 | 01-JAN-00:10 | 2392.23 | 21-DEC-08:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 42.72 | 0.00 | 03-JAN-04:30 | 5311.71 | 07-NOV-12:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 42.72 | 0.00 | 03-JAN-04:30 | 5311.71 | 07-NOV-12:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 35.63 | 10.86 | 21-DEC-10:10 | 2333.61 | 26-JUN-20:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 351.29 | 18-MAY-23:40 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 351.29 | 18-MAY-23:40 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 35.60 | 10.86 | 21-DEC-10:10 | 2333.61 | 26-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 35.60 | 10.86 | 21-DEC-10:10 | 2333.61 | 26-JUN-20:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 22.29 | 0.16 | 29-NOV-04:20 | 2291.69 | 26-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.35 | 0.00 | 01-JAN-00:10 | 948.85 | 22-DEC-04:50 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.35 | 0.00 | 01-JAN-00:10 | 948.85 | 22-DEC-04:50 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 21.93 | 0.00 | 05-JAN-02:00 | 2291.69 | 26-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 21.93 | 0.00 | 05-JAN-02:00 | 2291.69 | 26-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 15.92 | 0.20 | 04-FEB-03:40 | 985.49 | 09-OCT-06:20 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.60 | 0.00 | 01-JAN-00:10 | 709.31 | 23-DEC-07:40 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.60 | 0.00 | 01-JAN-00:10 | 709.31 | 23-DEC-07:40 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 15.32 | 0.00 | 04-JAN-10:30 | 985.49 | 09-OCT-06:20 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 15.32 | 0.00 | 04-JAN-10:30 | 985.49 | 09-OCT-06:20 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 586.43 | 4041.72 | 09-MAY-02:30 | 39878.61 | 26-JAN-20:50 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 1918.52 | 19-OCT-02:20 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 1918.52 | 19-OCT-02:20 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 586.37 | 4041.72 | 09-MAY-02:30 | 39878.61 | 26-JAN-20:50 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 586.37 | 4041.72 | 09-MAY-02:30 | 39878.61 | 26-JAN-20:50 |
EnergyTransfer:Zone:CAFE_FLR_1 | 254.54 | 1.58 | 31-OCT-14:30 | 18579.83 | 18-FEB-13:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.29 | 0.00 | 01-JAN-00:10 | 3257.83 | 21-DEC-09:30 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.29 | 0.00 | 01-JAN-00:10 | 3257.83 | 21-DEC-09:30 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 254.25 | 0.00 | 05-JAN-09:10 | 18579.83 | 18-FEB-13:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 254.25 | 0.00 | 05-JAN-09:10 | 18579.83 | 18-FEB-13:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 782.64 | 2685.66 | 05-DEC-02:30 | 43304.12 | 16-AUG-20:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.57 | 0.00 | 01-JAN-00:10 | 8245.24 | 25-APR-01:30 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.57 | 0.00 | 01-JAN-00:10 | 8245.24 | 25-APR-01:30 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 782.07 | 2264.90 | 23-NOV-15:30 | 43304.12 | 16-AUG-20:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 782.07 | 2264.90 | 23-NOV-15:30 | 43304.12 | 16-AUG-20:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 74.21 | 0.21 | 28-FEB-00:10 | 14154.92 | 16-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 17.16 | 0.00 | 01-JAN-08:10 | 8610.55 | 21-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 17.16 | 0.00 | 01-JAN-08:10 | 8610.55 | 21-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 57.05 | 0.00 | 01-JAN-00:10 | 14154.92 | 16-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 57.05 | 0.00 | 01-JAN-00:10 | 14154.92 | 16-AUG-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 68.40 | 0.37 | 01-DEC-18:00 | 13320.81 | 26-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 23.62 | 0.00 | 01-JAN-08:10 | 8697.80 | 21-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 23.62 | 0.00 | 01-JAN-08:10 | 8697.80 | 21-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 44.79 | 0.00 | 01-JAN-00:10 | 13320.81 | 26-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 44.79 | 0.00 | 01-JAN-00:10 | 13320.81 | 26-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 487.29 | 7.19 | 21-MAR-13:40 | 72210.21 | 07-NOV-12:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 13.95 | 0.00 | 01-JAN-00:10 | 31140.43 | 21-DEC-05:40 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 13.95 | 0.00 | 01-JAN-00:10 | 31140.43 | 21-DEC-05:40 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 473.34 | 0.00 | 05-JAN-00:50 | 72210.21 | 07-NOV-12:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 473.34 | 0.00 | 05-JAN-00:50 | 72210.21 | 07-NOV-12:10 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 400.36 | 1.18 | 18-NOV-06:30 | 69111.35 | 16-JUL-15:10 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 73.76 | 0.00 | 01-JAN-08:10 | 56466.57 | 21-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 73.76 | 0.00 | 01-JAN-08:10 | 56466.57 | 21-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 326.60 | 0.00 | 01-JAN-00:10 | 69111.35 | 16-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 326.60 | 0.00 | 01-JAN-00:10 | 69111.35 | 16-JUL-15:10 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 78.36 | 0.15 | 15-DEC-21:40 | 12440.62 | 01-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 17.55 | 0.00 | 01-JAN-08:00 | 8595.21 | 21-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 17.55 | 0.00 | 01-JAN-08:00 | 8595.21 | 21-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 60.80 | 0.00 | 01-JAN-00:10 | 12440.62 | 01-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 60.80 | 0.00 | 01-JAN-00:10 | 12440.62 | 01-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 72.23 | 0.06 | 08-FEB-12:40 | 12486.46 | 01-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 23.92 | 0.00 | 01-JAN-08:10 | 8888.42 | 21-DEC-19:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 23.92 | 0.00 | 01-JAN-08:10 | 8888.42 | 21-DEC-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 48.30 | 0.00 | 01-JAN-00:10 | 12486.46 | 01-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 48.30 | 0.00 | 01-JAN-00:10 | 12486.46 | 01-JUL-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 174.61 | 0.92 | 22-DEC-15:10 | 14414.75 | 26-JUN-18:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 1.41 | 0.00 | 01-JAN-00:10 | 5561.22 | 21-DEC-09:20 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 1.41 | 0.00 | 01-JAN-00:10 | 5561.22 | 21-DEC-09:20 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 173.20 | 0.00 | 05-JAN-07:10 | 14414.75 | 26-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 173.20 | 0.00 | 05-JAN-07:10 | 14414.75 | 26-JUN-18:30 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 20.52 | 0.05 | 10-MAY-05:20 | 3888.19 | 16-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 6.99 | 0.00 | 01-JAN-08:10 | 2701.89 | 21-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 6.99 | 0.00 | 01-JAN-08:10 | 2701.89 | 21-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.53 | 0.00 | 01-JAN-00:10 | 3888.19 | 16-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.53 | 0.00 | 01-JAN-00:10 | 3888.19 | 16-AUG-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 19.84 | 0.03 | 18-FEB-22:40 | 3633.83 | 26-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.28 | 0.00 | 01-JAN-08:10 | 2723.81 | 21-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.28 | 0.00 | 01-JAN-08:10 | 2723.81 | 21-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 10.56 | 0.00 | 01-JAN-00:10 | 3633.83 | 26-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 10.56 | 0.00 | 01-JAN-00:10 | 3633.83 | 26-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 118.55 | 0.29 | 28-MAR-20:10 | 19005.65 | 05-NOV-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 17.73 | 0.00 | 01-JAN-00:10 | 12082.22 | 21-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 17.73 | 0.00 | 01-JAN-00:10 | 12082.22 | 21-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 100.82 | 0.00 | 01-JAN-01:30 | 19005.65 | 05-NOV-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 100.82 | 0.00 | 01-JAN-01:30 | 19005.65 | 05-NOV-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 452.06 | 1729.38 | 23-NOV-15:30 | 23267.47 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.24 | 0.00 | 01-JAN-00:10 | 2469.86 | 08-APR-23:30 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.24 | 0.00 | 01-JAN-00:10 | 2469.86 | 08-APR-23:30 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 451.82 | 907.69 | 23-NOV-15:30 | 23267.47 | 26-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 451.82 | 907.69 | 23-NOV-15:30 | 23267.47 | 26-JUN-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 478.81 | 1746.41 | 23-NOV-15:30 | 24628.73 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.19 | 0.00 | 01-JAN-00:10 | 2343.23 | 08-APR-23:30 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.19 | 0.00 | 01-JAN-00:10 | 2343.23 | 08-APR-23:30 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 478.63 | 1317.04 | 23-NOV-15:30 | 24628.73 | 26-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 478.63 | 1317.04 | 23-NOV-15:30 | 24628.73 | 26-JUN-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.03 | 0.00 | 01-JAN-00:10 | 793.18 | 22-APR-00:40 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.03 | 0.00 | 01-JAN-00:10 | 793.18 | 22-APR-00:40 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 621.95 | 3431.47 | 09-MAY-02:30 | 31706.87 | 05-AUG-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 621.95 | 3431.47 | 09-MAY-02:30 | 31706.87 | 05-AUG-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 80.00 | 0.91 | 31-JAN-08:30 | 7647.34 | 16-AUG-15:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 3.01 | 0.00 | 01-JAN-00:10 | 4460.12 | 23-DEC-07:20 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 3.01 | 0.00 | 01-JAN-00:10 | 4460.12 | 23-DEC-07:20 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 76.99 | 0.00 | 03-JAN-06:00 | 7647.34 | 16-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 76.99 | 0.00 | 03-JAN-06:00 | 7647.34 | 16-AUG-15:10 |
PlantLoopHeatingDemand:Facility | 1356.36 | 9317.93 | 15-AUG-01:40 | 321475.82 | 21-DEC-09:10 |
PlantLoopHeatingDemand:Plant | 786.03 | 9317.93 | 15-AUG-01:40 | 58337.31 | 13-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 786.03 | 9317.93 | 15-AUG-01:40 | 58337.31 | 13-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 786.03 | 9317.93 | 15-AUG-01:40 | 58337.31 | 13-FEB-07:10 |
EnergyTransfer:HVAC | 5944.94 | 206.01 | 23-MAY-10:10 | 712602.40 | 22-DEC-03:00 |
HeatingCoils:EnergyTransfer | 570.33 | 0.00 | 09-JAN-14:00 | 289424.91 | 21-DEC-09:10 |
PlantLoopHeatingDemand:HVAC | 570.33 | 0.00 | 09-JAN-14:00 | 289424.91 | 21-DEC-09:10 |
HeatingCoils:PlantLoopHeatingDemand | 570.33 | 0.00 | 09-JAN-14:00 | 289424.91 | 21-DEC-09:10 |
CoolingCoils:EnergyTransfer | 2378.17 | 0.00 | 01-JAN-00:30 | 473338.70 | 26-JUN-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 2933.52 | 0.00 | 09-JAN-12:50 | 497028.90 | 22-DEC-03:00 |
HeatRecoveryForCooling:EnergyTransfer | 62.93 | 0.00 | 01-JAN-00:10 | 129275.87 | 16-AUG-14:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 786.03 | 9317.93 | 15-AUG-01:40 | 58337.31 | 13-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 786.03 | 9317.93 | 15-AUG-01:40 | 58337.31 | 13-FEB-07:10 |
Boilers:EnergyTransfer | 563.67 | 0.00 | 09-JAN-13:50 | 286180.75 | 21-DEC-09:10 |
Chillers:EnergyTransfer | 2495.97 | 0.00 | 01-JAN-00:30 | 477770.12 | 26-JUN-18:10 |
HeatRejection:EnergyTransfer | 3274.58 | 0.00 | 01-JAN-00:30 | 650785.69 | 26-JUN-18:10 |
General:HeatRejection:EnergyTransfer | 3274.58 | 0.00 | 01-JAN-00:30 | 650785.69 | 26-JUN-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.253 | -403.893 | 0.000 | 0.000 | 134.823 | 173.462 | 150.255 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -54.900 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 1.781 | -42.716 | 0.000 | 0.000 | 14.721 | 8.614 | 10.186 | 36.208 | 0.000 | 0.156 | 0.000 | 0.000 | -13.469 | 0.000 | -4.348 | -11.134 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.030 | -35.598 | 0.000 | 0.000 | 16.506 | 9.975 | 11.795 | 0.000 | 0.000 | 0.065 | 0.000 | 0.000 | 0.000 | 0.000 | -1.718 | -1.054 |
MECH_FLR_1 | 0.000 | 0.000 | 0.352 | -21.934 | 0.000 | 0.000 | 3.573 | 16.635 | 12.471 | 0.000 | 0.000 | 0.144 | 0.000 | 0.000 | 0.000 | 0.000 | -3.955 | -7.286 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.604 | -15.318 | 0.000 | 0.000 | 2.899 | 2.785 | 3.598 | 0.000 | 0.000 | 0.103 | 7.479 | 0.000 | 0.000 | 0.000 | -2.149 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.053 | -586.375 | 0.000 | 0.000 | 10.537 | 4.368 | 658.131 | 0.000 | 0.000 | 0.195 | 0.000 | 0.000 | 0.000 | 0.000 | -5.885 | -81.024 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.291 | -254.252 | 0.000 | 0.000 | 190.168 | 17.918 | 14.341 | 101.746 | 0.000 | 0.378 | 0.000 | 0.000 | -38.536 | 0.000 | -9.725 | -22.328 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.574 | -782.071 | 0.000 | 0.000 | 545.723 | 121.842 | 148.998 | 134.247 | 0.000 | 1.048 | 0.000 | 0.000 | -52.286 | 0.000 | -28.704 | -89.371 |
ROOM_1_FLR_3 | 20.341 | -47.403 | 0.000 | -12.838 | 0.000 | 0.000 | 9.706 | 6.366 | 12.292 | 64.652 | 0.000 | 0.588 | 0.000 | 0.000 | -29.020 | 0.000 | -9.773 | -14.912 |
ROOM_2_FLR_3 | 27.527 | -36.199 | 0.000 | -12.498 | 0.000 | 0.000 | 9.746 | 6.366 | 12.291 | 42.838 | 0.000 | 0.586 | 0.000 | 0.000 | -29.596 | 0.000 | -9.633 | -11.427 |
ROOM_3_MULT19_FLR_3 | 18.576 | -276.782 | 0.000 | -201.173 | 0.000 | 0.000 | 0.000 | 76.021 | 228.754 | 440.369 | 0.000 | 2.247 | 0.004 | 0.000 | -165.941 | 0.000 | -70.042 | -52.029 |
ROOM_4_MULT19_FLR_3 | 114.994 | -200.411 | 0.000 | -167.419 | 0.000 | 0.000 | 185.527 | 76.042 | 228.817 | 105.477 | 0.000 | 4.132 | 0.000 | 0.000 | -162.972 | 0.000 | -57.360 | -126.827 |
ROOM_5_FLR_3 | 20.724 | -51.056 | 0.000 | -12.920 | 0.000 | 0.000 | 9.695 | 6.366 | 12.292 | 67.803 | 0.000 | 0.585 | 0.000 | 0.000 | -28.587 | 0.000 | -9.817 | -15.084 |
ROOM_6_FLR_3 | 27.727 | -39.532 | 0.000 | -12.577 | 0.000 | 0.000 | 9.737 | 6.366 | 12.291 | 45.762 | 0.000 | 0.583 | 0.000 | 0.000 | -28.949 | 0.000 | -9.673 | -11.734 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 1.407 | -173.203 | 0.000 | 0.000 | 113.408 | 109.603 | 0.000 | 60.020 | 0.000 | 0.439 | 0.000 | 0.000 | -38.700 | 0.000 | -12.167 | -60.805 |
ROOM_1_FLR_6 | 7.948 | -11.299 | 0.000 | -3.185 | 0.000 | 0.000 | 2.430 | 1.592 | 3.073 | 16.108 | 0.000 | 0.148 | 0.000 | 0.000 | -7.185 | 0.000 | -2.465 | -7.165 |
ROOM_2_FLR_6 | 10.403 | -8.581 | 0.000 | -3.095 | 0.000 | 0.000 | 2.440 | 1.591 | 3.073 | 10.693 | 0.000 | 0.148 | 0.000 | 0.000 | -7.312 | 0.000 | -2.428 | -6.931 |
ROOM_3_MULT9_FLR_6 | 21.804 | -83.982 | 0.000 | -20.906 | 0.000 | 0.000 | 21.789 | 9.005 | 27.097 | 95.569 | 0.000 | 0.765 | 0.001 | 0.000 | -33.806 | 0.000 | -12.137 | -25.197 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.239 | -451.819 | 0.000 | 0.000 | 327.221 | 34.632 | 175.857 | 10.921 | 0.000 | 0.249 | 0.000 | 0.000 | -21.510 | 0.000 | -6.348 | -69.442 |
DINING_FLR_6 | 0.000 | 0.000 | 0.186 | -478.630 | 0.000 | 0.000 | 322.469 | 34.632 | 175.857 | 10.626 | 0.000 | 0.236 | 0.000 | 0.000 | -22.174 | 0.000 | -6.460 | -36.743 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.026 | -621.941 | 0.000 | 0.000 | 27.789 | 13.327 | 550.372 | 30.402 | 0.000 | 0.194 | 21.560 | 0.000 | -15.672 | 0.000 | -6.058 | -0.003 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 3.011 | -76.993 | 0.000 | 0.000 | 30.128 | 28.999 | 0.000 | 29.939 | 0.000 | 0.190 | 7.378 | 0.000 | -17.257 | 0.000 | -5.395 | -0.000 |
Total Facility | 270.043 | -755.245 | 8.807 | -4391.353 | 0.000 | 0.000 | 1991.035 | 766.506 | 2451.839 | 1303.379 | 0.000 | 13.178 | 36.423 | 0.000 | -712.973 | 0.000 | -276.239 | -705.397 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 03-DEC-02:34 | 0.00 | 0.00 | 0.00 | -44595.60 | 0.00 | 0.00 | 5186.04 | 3152.28 | 3193.83 | 0.00 | 0.00 | 0.00 | 33063.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 23-NOV-11:06 | 0.00 | 0.00 | 0.00 | -6979.93 | 0.00 | 0.00 | 225.89 | 234.80 | 288.68 | 7670.10 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -212.15 | -1227.39 |
RETAIL_2_FLR_1 | 16-NOV-00:37 | 0.00 | 0.00 | 0.00 | -3878.17 | 0.00 | 0.00 | 781.38 | 181.27 | 250.72 | 0.00 | 0.00 | 0.00 | 2744.84 | 0.00 | -0.00 | 0.00 | -80.04 | 0.00 |
MECH_FLR_1 | 26-JUN-20:00 | 0.00 | 0.00 | 0.00 | -2291.87 | 0.00 | 0.00 | 129.08 | 1360.40 | 839.45 | 0.00 | 0.00 | 74.14 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -111.20 |
STORAGE_FLR_1 | 12-OCT-02:59 | 0.00 | 0.00 | 0.00 | -1457.91 | 0.00 | 0.00 | 141.77 | 25.30 | 50.98 | 0.00 | 0.00 | 0.00 | 1344.42 | 0.00 | -0.00 | 0.00 | -104.56 | 0.00 |
LAUNDRY_FLR_1 | 29-MAR-20:41 | 0.00 | 0.00 | 0.00 | -56245.26 | 0.00 | 0.00 | 319.12 | 317.52 | 41967.83 | 0.00 | 0.00 | 0.00 | 13999.66 | 0.00 | -0.00 | 0.00 | -358.87 | 0.00 |
CAFE_FLR_1 | 23-NOV-11:06 | 0.00 | 0.00 | 0.00 | -26115.08 | 0.00 | 0.00 | 2968.27 | 358.25 | 406.43 | 21513.54 | 0.00 | 0.00 | 1337.53 | 0.00 | -0.00 | 0.00 | -468.95 | 0.00 |
LOBBY_FLR_1 | 17-NOV-00:23 | 0.00 | 0.00 | 0.00 | -77114.34 | 0.00 | 0.00 | 26033.64 | 2281.15 | 3167.12 | 0.00 | 0.00 | 0.00 | 50208.51 | 0.00 | -3306.40 | 0.00 | -1269.69 | 0.00 |
ROOM_1_FLR_3 | 16-AUG-15:01 | 0.00 | -18257.57 | 0.00 | -593.41 | 0.00 | 0.00 | 235.26 | 137.21 | 273.93 | 12550.09 | 0.00 | 293.09 | 5361.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 26-JUN-15:01 | 0.00 | -17725.72 | 0.00 | -590.79 | 0.00 | 0.00 | 235.29 | 137.19 | 273.90 | 11084.51 | 0.00 | 358.64 | 6226.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 07-NOV-12:10 | 0.00 | -63909.65 | 0.00 | -8300.18 | 0.00 | 0.00 | 0.00 | 1638.34 | 5097.90 | 100410.29 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -406.77 | -34529.93 |
ROOM_4_MULT19_FLR_3 | 16-JUL-15:01 | 0.00 | -88505.02 | 0.00 | -8291.13 | 0.00 | 0.00 | 2483.63 | 1931.47 | 5687.67 | 19807.69 | 0.00 | 1494.21 | 65391.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 17-JUL-08:61 | 0.00 | -15865.33 | 0.00 | -595.27 | 0.00 | 0.00 | 87.15 | 215.61 | 453.05 | 11276.44 | 0.00 | 131.80 | 4296.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 17-JUL-08:61 | 0.00 | -15516.61 | 0.00 | -597.16 | 0.00 | 0.00 | 87.15 | 215.58 | 452.99 | 11235.73 | 0.00 | 131.08 | 3991.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 26-JUN-18:30 | 0.00 | 0.00 | 0.00 | -14415.62 | 0.00 | 0.00 | 4080.27 | 7967.22 | 0.00 | 3599.57 | 0.00 | 325.80 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1557.23 |
ROOM_1_FLR_6 | 16-AUG-15:01 | 0.00 | -4857.74 | 0.00 | -148.54 | 0.00 | 0.00 | 58.82 | 34.30 | 68.48 | 3122.73 | 0.00 | 72.90 | 1649.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 26-JUN-15:01 | 0.00 | -4704.13 | 0.00 | -147.86 | 0.00 | 0.00 | 58.82 | 34.30 | 68.48 | 2758.98 | 0.00 | 89.31 | 1842.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 28-SEP-15:01 | 0.00 | -21042.39 | 0.00 | -971.52 | 0.00 | 0.00 | 529.39 | 194.07 | 603.86 | 9665.32 | 0.00 | 169.85 | 10851.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 16-NOV-01:01 | 0.00 | 0.00 | 0.00 | -38219.37 | 0.00 | 0.00 | 16228.05 | 515.68 | 2249.30 | 0.00 | 0.00 | 0.00 | 20830.88 | 0.00 | -1311.56 | 0.00 | -292.98 | 0.00 |
DINING_FLR_6 | 17-MAR-22:09 | 0.00 | 0.00 | 0.00 | -40081.54 | 0.00 | 0.00 | 15723.37 | 1031.35 | 6747.90 | 0.00 | 0.00 | 0.00 | 18421.77 | 0.00 | -1513.84 | 0.00 | -329.02 | 0.00 |
KITCHEN_FLR_6 | 23-NOV-11:06 | 0.00 | 0.00 | 0.00 | -42889.26 | 0.00 | 0.00 | 462.77 | 363.28 | 24259.91 | 2064.87 | 0.00 | 0.00 | 16014.33 | 0.00 | -0.00 | 0.00 | -275.88 | 0.00 |
CORRIDOR_FLR_6 | 16-AUG-15:01 | 0.00 | 0.00 | 0.00 | -7655.41 | 0.00 | 0.00 | 771.11 | 658.76 | 0.00 | 2458.22 | 0.00 | 138.68 | 3628.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 26-JUN-18:02 | 0.00 | -209003.63 | 0.00 | -223556.59 | 0.00 | 0.00 | 73978.60 | 53571.31 | 122326.88 | 80226.22 | 0.00 | 7613.34 | 94843.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 16-OCT-02:23 | 0.00 | 0.00 | 11369.87 | 0.00 | 0.00 | 0.00 | 6689.74 | 1576.23 | 2129.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -21765.07 |
RETAIL_1_FLR_1 | 21-DEC-08:06 | 0.00 | 0.00 | 2402.23 | 0.00 | 0.00 | 0.00 | 358.02 | 313.07 | 360.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2021.38 | 0.00 | -455.55 | -957.25 |
RETAIL_2_FLR_1 | 27-MAR-00:13 | 0.00 | 0.00 | 913.30 | 0.00 | 0.00 | 0.00 | 794.24 | 135.95 | 208.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -83.78 | -1968.65 |
MECH_FLR_1 | 22-DEC-04:50 | 0.00 | 0.00 | 948.87 | 0.00 | 0.00 | 0.00 | 197.29 | 151.16 | 176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -430.68 | -1043.36 |
STORAGE_FLR_1 | 23-DEC-07:20 | 0.00 | 0.00 | 709.24 | 0.00 | 0.00 | 0.00 | 84.31 | 75.91 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -255.05 | -716.37 |
LAUNDRY_FLR_1 | 17-NOV-02:38 | 0.00 | 0.00 | 10203.00 | 0.00 | 0.00 | 0.00 | 525.69 | 39.69 | 9326.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -277.46 | -19817.11 |
CAFE_FLR_1 | 12-OCT-02:54 | 0.00 | 0.00 | 6277.77 | 0.00 | 0.00 | 0.00 | 9185.84 | 195.77 | 203.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2548.56 | 0.00 | -487.35 | -12826.68 |
LOBBY_FLR_1 | 16-OCT-02:23 | 0.00 | 0.00 | 21298.53 | 0.00 | 0.00 | 0.00 | 26499.94 | 1140.58 | 2111.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3560.62 | 0.00 | -1340.33 | -46149.50 |
ROOM_1_FLR_3 | 21-DEC-19:01 | 11992.27 | 252.01 | 0.00 | -252.01 | 0.00 | 0.00 | 419.22 | 436.12 | 516.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4046.90 | 0.00 | -1036.89 | -8280.08 |
ROOM_2_FLR_3 | 21-DEC-19:01 | 12020.24 | 248.35 | 0.00 | -248.35 | 0.00 | 0.00 | 419.21 | 436.07 | 516.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3993.21 | 0.00 | -1035.26 | -8363.25 |
ROOM_3_MULT19_FLR_3 | 21-DEC-05:40 | 31140.76 | 2796.53 | 0.00 | -2796.53 | 0.00 | 0.00 | 0.00 | 1287.27 | 3921.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -23962.59 | 0.00 | -5102.22 | -7284.67 |
ROOM_4_MULT19_FLR_3 | 21-DEC-16:01 | 66294.97 | 3132.83 | 0.00 | -3132.83 | 0.00 | 0.00 | 5585.73 | 1638.79 | 5099.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17660.44 | 0.00 | -5080.54 | -55877.80 |
ROOM_5_FLR_3 | 21-DEC-19:01 | 11687.25 | 248.42 | 0.00 | -248.42 | 0.00 | 0.00 | 419.21 | 436.12 | 516.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4090.93 | 0.00 | -1035.35 | -7932.56 |
ROOM_6_FLR_3 | 21-DEC-19:01 | 11700.23 | 244.70 | 0.00 | -244.70 | 0.00 | 0.00 | 419.20 | 436.07 | 516.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4037.17 | 0.00 | -1033.70 | -8000.85 |
CORRIDOR_FLR_3 | 21-DEC-09:03 | 0.00 | 0.00 | 5624.58 | 0.00 | 0.00 | 0.00 | 1385.66 | 3983.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4301.47 | 0.00 | -1283.10 | -5409.28 |
ROOM_1_FLR_6 | 21-DEC-19:01 | 3563.96 | 63.52 | 0.00 | -63.52 | 0.00 | 0.00 | 104.80 | 109.03 | 129.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1012.75 | 0.00 | -259.89 | -2634.22 |
ROOM_2_FLR_6 | 21-DEC-19:01 | 3565.40 | 62.51 | 0.00 | -62.51 | 0.00 | 0.00 | 104.80 | 109.02 | 129.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -997.65 | 0.00 | -259.44 | -2651.18 |
ROOM_3_MULT9_FLR_6 | 21-DEC-09:02 | 16511.07 | 407.38 | 0.00 | -407.38 | 0.00 | 0.00 | 244.99 | 304.96 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3828.83 | 0.00 | -1183.51 | -13047.39 |
BANQUET_FLR_6 | 16-OCT-02:23 | 0.00 | 0.00 | 9353.80 | 0.00 | 0.00 | 0.00 | 15963.19 | 343.78 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1365.81 | 0.00 | -305.39 | -26238.88 |
DINING_FLR_6 | 19-OCT-02:14 | 0.00 | 0.00 | 9626.43 | 0.00 | 0.00 | 0.00 | 15692.79 | 343.78 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1366.59 | 0.00 | -308.33 | -26237.38 |
KITCHEN_FLR_6 | 16-OCT-02:23 | 0.00 | 0.00 | 6633.55 | 0.00 | 0.00 | 0.00 | 1391.17 | 121.09 | 5415.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1180.66 | 0.00 | -287.64 | -12093.49 |
CORRIDOR_FLR_6 | 23-DEC-07:20 | 0.00 | 0.00 | 4459.61 | 0.00 | 0.00 | 0.00 | 916.61 | 790.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2391.59 | 0.00 | -603.33 | -3171.81 |
Total Facility | 21-DEC-09:02 | 95496.27 | 72054.33 | 16360.21 | -72054.33 | 0.00 | 0.00 | 24474.06 | 26712.50 | 88432.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -77309.71 | 0.00 | -26112.43 | -148053.13 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 26.9987 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 26.8447 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 14.4229 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 12.2847 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0097 | 3.0097 | 1.2942 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4695 | 0.4695 | 0.1409 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2899 | 0.2899 | 0.1389 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2773 | 0.2773 | 0.0832 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1347 | 0.1347 | 0.0874 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.0174 | 4.0174 | 1.2052 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9115 | 1.9115 | 1.0246 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7895 | 5.7895 | 2.8658 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8102 | 1.8102 | 0.7187 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6968 | 2.6968 | 1.7987 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8259 | 2.8259 | 1.7973 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7925 | 2.7925 | 0.8377 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9738 | 0.9738 | 0.2922 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 26.9987 | 26.8447 | 26.9987 | 12.2847 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5049 | 1.5049 | 1.2942 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2348 | 0.2348 | 0.1409 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1450 | 0.1450 | 0.1389 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1386 | 0.1386 | 0.0832 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0874 | 0.0874 | 0.0874 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0087 | 2.0087 | 1.2052 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0246 | 1.0246 | 1.0246 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8947 | 2.8947 | 2.8658 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9051 | 0.9051 | 0.7187 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7987 | 1.7987 | 1.7987 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7973 | 1.7973 | 1.7973 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3962 | 1.3962 | 0.8377 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4869 | 0.4869 | 0.2922 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 14.4229 | 12.2847 | 12.2847 | 12.2847 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 697.67 |
Number of hours not met | 697.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 803.26 | 348080.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 778.60 | 173015.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 766.51 | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 242.64 | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.56 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 32.45 | 1868.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 637.04 | 52608.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 138.55 | 7958.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 200.83 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.69 | 3214.53 | 302067.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.53 | 2063.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.99 | 1245.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1806.62 | 5313.01 |
Natural Gas | 1788.84 | 5806.62 |
Additional | 0.00 | 0.00 |
Total | 3595.46 | 11119.63 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 67.56 |
Space Heating | 0.00 |
Space Cooling | 68.63 |
Fans (All) | 56.15 |
Service Water Heating | 8.00 |
Receptacle Equipment | 153.81 |
Miscellaneous (All) | 468.30 |
Subtotal | 468.30 |
Natural Gas [MJ/m2] | |
Space Heating | 70.80 |
Service Water Heating | 283.34 |
Miscellaneous (All) | 511.81 |
Subtotal | 511.81 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.89 |
Space Heating | 7.22 |
Space Cooling | 7.00 |
Fans (All) | 5.73 |
Service Water Heating | 29.72 |
Receptacle Equipment | 31.78 |
Miscellaneous | 11.65 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2667. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 2678. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 3061. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8752.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 7.67 | 0.00 | 0.00 | 0.00 |
Average | 8759.55 | 0.45 | 0.00 | 0.00 | 0.00 |
Sum | 192710.00 | 10.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37189.83 | 13.17 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108173.83 | 95.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 95.17 | 0.00 | 0.00 | 0.00 |
Average | 288882.12 | 4.92 | 0.00 | 0.00 | 0.00 |
Sum | 6355406.67 | 108.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8712.67 | 47.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8712.83 | 47.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8710.00 | 50.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8721.00 | 39.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8710.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 50.00 | 0.00 | 0.00 | 0.00 |
Average | 8751.13 | 8.87 | 0.00 | 0.00 | 0.00 |
Sum | 192524.83 | 195.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 704393.00 | 6024.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2098292.17 | 17136.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100202.67 | 155.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1234740.00 | 10975.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1237262.33 | 8452.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108239.50 | 29.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2098292.17 | 17136.83 | 0.00 | 0.00 | 0.00 |
Average | 286942.80 | 1944.24 | 0.00 | 0.00 | 0.00 |
Sum | 6312741.67 | 42773.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:59:38
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324337E+11 | 35920.29 | 21-JAN-23:52 | 2.00 | 2.00 | 0.818921E+10 | 5112.97 | 28-JAN-00:30 | 3.00 | 3.00 |
February | 0.272412E+11 | 36821.62 | 22-FEB-22:09 | 2.83 | 2.42 | 0.734391E+10 | 5017.50 | 27-FEB-23:40 | 2.00 | -0.6 |
March | 0.286905E+11 | 40044.28 | 02-MAR-21:35 | 0.67 | -3.0 | 0.804846E+10 | 5030.97 | 03-MAR-22:00 | 0.00 | -3.0 |
April | 0.280876E+11 | 35797.19 | 18-APR-04:43 | 7.50 | 1.94 | 0.779698E+10 | 4975.72 | 10-APR-21:19 | 7.50 | 1.94 |
May | 0.294185E+11 | 32370.12 | 02-MAY-21:45 | 2.40 | -0.3 | 0.800817E+10 | 4980.85 | 09-MAY-02:39 | 3.67 | 0.39 |
June | 0.310716E+11 | 19282.97 | 09-JUN-04:20 | 6.60 | 3.51 | 0.787200E+10 | 4837.45 | 07-JUN-21:10 | 6.60 | 3.51 |
July | 0.327518E+11 | 18506.86 | 28-JUL-21:00 | 16.00 | 15.35 | 0.813690E+10 | 4837.14 | 15-JUL-00:10 | 16.00 | 15.35 |
August | 0.366944E+11 | 21018.33 | 18-AUG-21:00 | 19.00 | 9.02 | 0.823380E+10 | 4837.47 | 24-AUG-02:09 | 18.67 | 15.36 |
September | 0.397398E+11 | 35257.85 | 21-SEP-19:47 | 0.00 | -0.5 | 0.797301E+10 | 4929.83 | 16-SEP-04:19 | 0.00 | -0.5 |
October | 0.409892E+11 | 40717.16 | 03-OCT-23:55 | 3.00 | 2.50 | 0.823955E+10 | 5091.38 | 03-OCT-23:49 | 3.00 | 2.50 |
November | 0.388848E+11 | 39464.11 | 12-NOV-21:26 | 2.50 | 2.50 | 0.796630E+10 | 5181.92 | 18-NOV-03:49 | 4.83 | 1.62 |
December | 0.378875E+11 | 44597.29 | 03-DEC-02:34 | 4.67 | -0.6 | 0.822996E+10 | 5206.33 | 05-DEC-02:39 | 3.67 | -2.3 |
Annual Sum or Average | 0.403891E+12 | 0.960382E+11 | ||||||||
Minimum of Months | 0.272412E+11 | 18506.86 | 0.00 | -3.0 | 0.734391E+10 | 4837.14 | 0.00 | -3.0 | ||
Maximum of Months | 0.409892E+11 | 44597.29 | 19.00 | 15.35 | 0.823955E+10 | 5206.33 | 18.67 | 15.36 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.326428E+10 | 6069.23 | 10-JAN-13:41 | 5.00 | 3.98 | 0.694686E+09 | 491.81 | 20-JAN-22:19 | 7.67 | 1.92 |
February | 0.267915E+10 | 6009.77 | 15-FEB-13:22 | 6.00 | 1.29 | 0.625121E+09 | 488.10 | 17-FEB-22:30 | 7.00 | 3.16 |
March | 0.289761E+10 | 5303.31 | 01-MAR-11:46 | 1.17 | -1.2 | 0.707190E+09 | 491.82 | 13-MAR-21:19 | 10.67 | 1.98 |
April | 0.212693E+10 | 3565.13 | 07-APR-12:30 | 20.50 | 8.13 | 0.668189E+09 | 491.83 | 07-APR-21:19 | 11.67 | 6.33 |
May | 0.312254E+10 | 2693.36 | 05-MAY-13:00 | 22.00 | 10.96 | 0.750624E+09 | 491.83 | 16-MAY-21:10 | 16.83 | 10.08 |
June | 0.441696E+10 | 3281.01 | 26-JUN-12:40 | 36.43 | 15.33 | 0.793810E+09 | 491.88 | 07-JUN-21:10 | 36.43 | 15.33 |
July | 0.461809E+10 | 3543.04 | 23-JUL-12:00 | 32.00 | 15.97 | 0.819675E+09 | 491.84 | 21-JUL-22:10 | 32.00 | 15.97 |
August | 0.502889E+10 | 4302.19 | 31-AUG-12:40 | 30.00 | 12.25 | 0.822707E+09 | 491.87 | 25-AUG-22:10 | 30.00 | 12.25 |
September | 0.487935E+10 | 5202.43 | 28-SEP-12:50 | 30.42 | 11.32 | 0.779798E+09 | 491.91 | 01-SEP-01:10 | 30.42 | 11.32 |
October | 0.375571E+10 | 5216.48 | 10-OCT-12:40 | 23.67 | 7.92 | 0.732925E+09 | 491.82 | 10-OCT-21:00 | 13.00 | 4.35 |
November | 0.332806E+10 | 6980.31 | 23-NOV-11:06 | 3.17 | 0.73 | 0.683270E+09 | 491.81 | 07-NOV-22:19 | 3.17 | 0.73 |
December | 0.259812E+10 | 5778.81 | 18-DEC-10:42 | 3.83 | -0.6 | 0.674904E+09 | 481.51 | 14-DEC-22:40 | 3.83 | -0.6 |
Annual Sum or Average | 0.427157E+11 | 0.875290E+10 | ||||||||
Minimum of Months | 0.212693E+10 | 2693.36 | 1.17 | -1.2 | 0.625121E+09 | 481.51 | 3.17 | -0.6 | ||
Maximum of Months | 0.502889E+10 | 6980.31 | 36.43 | 15.97 | 0.822707E+09 | 491.91 | 36.43 | 15.97 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.263758E+10 | 3256.45 | 24-JAN-22:38 | 3.00 | 0.25 | 0.872353E+09 | 591.14 | 24-JAN-00:20 | 3.00 | 0.25 |
February | 0.228303E+10 | 3250.62 | 27-FEB-22:15 | 2.00 | -0.8 | 0.772993E+09 | 596.82 | 27-FEB-23:40 | 2.00 | -0.6 |
March | 0.270505E+10 | 3358.68 | 03-MAR-22:57 | 0.00 | -3.0 | 0.879722E+09 | 607.56 | 03-MAR-22:00 | 0.00 | -3.0 |
April | 0.254812E+10 | 3327.69 | 09-APR-00:07 | 3.83 | 2.02 | 0.845635E+09 | 589.35 | 10-APR-21:19 | 1.00 | -3.0 |
May | 0.307607E+10 | 3148.64 | 18-MAY-23:40 | 5.33 | 3.66 | 0.925188E+09 | 595.26 | 09-MAY-02:39 | 5.33 | 3.66 |
June | 0.359653E+10 | 2333.61 | 26-JUN-20:10 | 32.05 | 13.25 | 0.932644E+09 | 569.60 | 07-JUN-21:10 | 32.05 | 13.25 |
July | 0.368890E+10 | 2227.12 | 17-JUL-21:00 | 29.00 | 13.54 | 0.960520E+09 | 569.55 | 21-JUL-22:10 | 22.83 | 15.84 |
August | 0.370132E+10 | 2326.41 | 16-AUG-20:10 | 28.50 | 11.68 | 0.964995E+09 | 569.58 | 15-AUG-03:00 | 28.50 | 11.68 |
September | 0.342551E+10 | 2416.56 | 21-SEP-20:08 | 0.18 | -0.6 | 0.926198E+09 | 569.80 | 01-SEP-04:40 | 0.18 | -0.6 |
October | 0.291881E+10 | 3504.40 | 03-OCT-23:55 | 3.00 | 2.50 | 0.906349E+09 | 589.08 | 16-OCT-22:30 | 1.50 | -2.2 |
November | 0.261580E+10 | 3878.92 | 16-NOV-00:37 | 3.00 | 2.50 | 0.851079E+09 | 588.54 | 18-NOV-03:49 | 4.83 | 1.62 |
December | 0.240115E+10 | 3425.11 | 05-DEC-02:53 | 4.00 | -2.2 | 0.839662E+09 | 594.00 | 05-DEC-02:39 | 4.00 | -2.2 |
Annual Sum or Average | 0.355979E+11 | 0.106773E+11 | ||||||||
Minimum of Months | 0.228303E+10 | 2227.12 | 0.00 | -3.0 | 0.772993E+09 | 569.55 | 0.00 | -3.0 | ||
Maximum of Months | 0.370132E+10 | 3878.92 | 32.05 | 13.54 | 0.964995E+09 | 607.56 | 32.05 | 15.84 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127630E+10 | 1338.97 | 24-JAN-01:13 | 4.33 | -0.8 | 0.167931E+09 | 116.50 | 24-JAN-22:30 | 3.00 | 0.25 |
February | 0.976791E+09 | 1162.41 | 27-FEB-23:33 | 2.00 | -0.6 | 0.148965E+09 | 117.71 | 27-FEB-22:10 | 2.00 | -0.6 |
March | 0.142841E+10 | 1157.29 | 09-MAR-02:33 | 3.67 | -1.4 | 0.174001E+09 | 120.45 | 16-MAR-21:10 | 10.00 | 4.14 |
April | 0.139050E+10 | 1485.78 | 22-APR-00:43 | 3.17 | 2.66 | 0.169513E+09 | 120.45 | 20-APR-21:10 | 3.17 | 2.66 |
May | 0.188506E+10 | 2186.55 | 18-MAY-23:30 | 5.50 | 3.74 | 0.195092E+09 | 120.50 | 18-MAY-23:49 | 5.17 | 3.59 |
June | 0.282576E+10 | 2291.69 | 26-JUN-20:00 | 32.70 | 13.66 | 0.198856E+09 | 120.47 | 07-JUN-21:10 | 32.70 | 13.66 |
July | 0.300620E+10 | 2285.05 | 17-JUL-20:00 | 30.00 | 13.88 | 0.204805E+09 | 120.46 | 15-JUL-00:10 | 30.00 | 13.88 |
August | 0.279989E+10 | 2171.69 | 16-AUG-20:00 | 29.00 | 11.91 | 0.205555E+09 | 120.46 | 07-AUG-21:19 | 29.00 | 11.91 |
September | 0.237557E+10 | 1967.25 | 12-SEP-20:00 | 23.80 | 13.35 | 0.196057E+09 | 120.47 | 01-SEP-04:40 | 23.80 | 13.35 |
October | 0.160173E+10 | 1489.19 | 12-OCT-02:59 | 3.00 | 0.65 | 0.184830E+09 | 120.45 | 10-OCT-22:10 | 3.00 | 0.65 |
November | 0.130617E+10 | 1301.72 | 17-NOV-00:23 | 3.50 | 1.86 | 0.166817E+09 | 120.45 | 09-NOV-22:19 | 3.50 | 1.86 |
December | 0.106198E+10 | 1355.01 | 05-DEC-02:53 | 4.00 | -2.2 | 0.163708E+09 | 115.56 | 04-DEC-22:10 | 4.00 | -2.2 |
Annual Sum or Average | 0.219344E+11 | 0.217613E+10 | ||||||||
Minimum of Months | 0.976791E+09 | 1157.29 | 2.00 | -2.2 | 0.148965E+09 | 115.56 | 2.00 | -2.2 | ||
Maximum of Months | 0.300620E+10 | 2291.69 | 32.70 | 13.88 | 0.205555E+09 | 120.50 | 32.70 | 13.88 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.863080E+09 | 1303.34 | 24-JAN-01:13 | 4.33 | -0.8 | 0.118894E+09 | 77.54 | 24-JAN-23:00 | 2.00 | 0.10 |
February | 0.625847E+09 | 1096.74 | 27-FEB-23:33 | 2.00 | -0.6 | 0.107196E+09 | 77.97 | 27-FEB-23:40 | 2.00 | -0.6 |
March | 0.979653E+09 | 1130.12 | 09-MAR-02:33 | 3.67 | -1.4 | 0.121952E+09 | 81.17 | 15-MAR-21:40 | 12.33 | 3.01 |
April | 0.101709E+10 | 1445.36 | 22-APR-00:43 | 3.17 | 2.66 | 0.117514E+09 | 78.78 | 20-APR-22:10 | 3.17 | 2.66 |
May | 0.157181E+10 | 1396.37 | 19-MAY-01:37 | 4.33 | 2.88 | 0.131276E+09 | 84.64 | 17-MAY-22:10 | 4.33 | 2.88 |
June | 0.182321E+10 | 1198.94 | 09-JUN-04:20 | 6.60 | 3.51 | 0.140290E+09 | 91.17 | 30-JUN-21:40 | 25.67 | 10.93 |
July | 0.190117E+10 | 957.21 | 04-JUL-04:05 | 9.83 | 7.02 | 0.145529E+09 | 91.75 | 17-JUL-21:40 | 27.00 | 13.09 |
August | 0.186728E+10 | 894.21 | 20-AUG-10:35 | 28.67 | 14.40 | 0.144301E+09 | 90.05 | 16-AUG-21:40 | 28.67 | 14.40 |
September | 0.171454E+10 | 1136.94 | 16-SEP-03:15 | 7.20 | 3.52 | 0.135470E+09 | 88.62 | 12-SEP-21:40 | 7.20 | 3.52 |
October | 0.127914E+10 | 1457.95 | 12-OCT-02:59 | 3.00 | 0.65 | 0.126304E+09 | 82.43 | 11-OCT-21:30 | 3.00 | 0.65 |
November | 0.987731E+09 | 1256.32 | 17-NOV-00:23 | 3.50 | 1.86 | 0.116290E+09 | 78.75 | 09-NOV-22:40 | 3.50 | 1.86 |
December | 0.687495E+09 | 1327.70 | 05-DEC-02:53 | 4.00 | -2.2 | 0.118040E+09 | 77.20 | 05-DEC-02:39 | 4.00 | -2.2 |
Annual Sum or Average | 0.153181E+11 | 0.152306E+10 | ||||||||
Minimum of Months | 0.625847E+09 | 894.21 | 2.00 | -2.2 | 0.107196E+09 | 77.20 | 2.00 | -2.2 | ||
Maximum of Months | 0.190117E+10 | 1457.95 | 28.67 | 14.40 | 0.145529E+09 | 91.75 | 28.67 | 14.40 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.478343E+11 | 53267.59 | 10-JAN-20:27 | 1.00 | 1.00 | 0.651869E+09 | 557.08 | 30-JAN-22:10 | 0.00 | -0.0 |
February | 0.429167E+11 | 53215.39 | 23-FEB-21:28 | 1.50 | 1.27 | 0.587759E+09 | 587.23 | 27-FEB-23:40 | 2.00 | -0.6 |
March | 0.486451E+11 | 56250.62 | 29-MAR-20:41 | 0.00 | -2.6 | 0.655523E+09 | 695.88 | 03-MAR-22:00 | 0.00 | -2.6 |
April | 0.469951E+11 | 50320.52 | 14-APR-20:09 | 0.17 | -0.9 | 0.634312E+09 | 601.67 | 10-APR-20:30 | 0.17 | -0.9 |
May | 0.506727E+11 | 51721.64 | 02-MAY-21:45 | 2.40 | -0.3 | 0.650331E+09 | 543.85 | 11-MAY-23:30 | 5.00 | 3.03 |
June | 0.511031E+11 | 39487.19 | 26-JUN-20:00 | 32.70 | 13.66 | 0.630688E+09 | 382.05 | 07-JUN-21:10 | 32.70 | 13.66 |
July | 0.525920E+11 | 39430.14 | 17-JUL-20:00 | 30.00 | 13.88 | 0.649233E+09 | 381.94 | 07-JUL-21:10 | 30.00 | 13.88 |
August | 0.526747E+11 | 39380.76 | 16-AUG-20:00 | 29.00 | 11.91 | 0.652087E+09 | 382.01 | 31-AUG-21:10 | 23.70 | 11.86 |
September | 0.501118E+11 | 51967.12 | 21-SEP-19:47 | 0.00 | -0.5 | 0.628870E+09 | 444.60 | 16-SEP-04:19 | 0.00 | -0.5 |
October | 0.492023E+11 | 51658.36 | 16-OCT-21:40 | 2.00 | -1.9 | 0.652263E+09 | 535.15 | 03-OCT-23:10 | 2.00 | -1.9 |
November | 0.467068E+11 | 51794.25 | 19-NOV-21:08 | 1.83 | 0.52 | 0.631017E+09 | 518.13 | 16-NOV-00:10 | 1.83 | 0.52 |
December | 0.469201E+11 | 51281.18 | 29-DEC-22:46 | 2.00 | -0.5 | 0.647670E+09 | 528.85 | 13-DEC-23:19 | 2.00 | -0.5 |
Annual Sum or Average | 0.586374E+12 | 0.767162E+10 | ||||||||
Minimum of Months | 0.429167E+11 | 39380.76 | 0.00 | -2.6 | 0.587759E+09 | 381.94 | 0.00 | -2.6 | ||
Maximum of Months | 0.526747E+11 | 56250.62 | 32.70 | 13.88 | 0.655523E+09 | 695.88 | 32.70 | 13.88 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210391E+11 | 23991.17 | 10-JAN-13:41 | 5.00 | 3.98 | 0.973659E+10 | 7266.74 | 24-JAN-02:39 | 3.67 | -1.1 |
February | 0.180092E+11 | 23023.73 | 16-FEB-14:20 | 5.00 | -0.8 | 0.866744E+10 | 7221.98 | 27-FEB-23:40 | 2.00 | -0.6 |
March | 0.196856E+11 | 24149.09 | 09-MAR-02:33 | 3.67 | -1.4 | 0.977879E+10 | 7414.41 | 09-MAR-03:30 | 3.00 | -1.7 |
April | 0.171948E+11 | 17582.43 | 09-APR-00:07 | 3.83 | 2.02 | 0.922783E+10 | 7113.76 | 13-APR-04:49 | 3.50 | 0.99 |
May | 0.206145E+11 | 16953.92 | 19-MAY-01:37 | 4.33 | 2.88 | 0.998595E+10 | 7362.04 | 09-MAY-02:39 | 4.33 | 2.88 |
June | 0.229876E+11 | 14448.76 | 09-JUN-04:20 | 6.60 | 3.51 | 0.103003E+11 | 6461.64 | 07-JUN-21:10 | 6.60 | 3.51 |
July | 0.239378E+11 | 12045.22 | 23-JUL-12:00 | 32.00 | 15.97 | 0.106361E+11 | 6461.22 | 21-JUL-22:10 | 32.00 | 15.97 |
August | 0.250605E+11 | 14257.20 | 26-AUG-12:40 | 31.67 | 13.33 | 0.107545E+11 | 6461.90 | 24-AUG-01:00 | 31.67 | 13.33 |
September | 0.243692E+11 | 16781.46 | 28-SEP-12:50 | 30.42 | 11.32 | 0.103119E+11 | 6557.95 | 16-SEP-04:19 | 30.42 | 11.32 |
October | 0.217522E+11 | 21297.84 | 12-OCT-02:06 | 3.83 | 1.46 | 0.100253E+11 | 7226.19 | 16-OCT-03:09 | 3.00 | -1.0 |
November | 0.207772E+11 | 26117.07 | 23-NOV-11:06 | 3.17 | 0.73 | 0.947286E+10 | 7361.75 | 18-NOV-03:49 | 3.17 | 0.73 |
December | 0.188234E+11 | 23329.35 | 16-DEC-11:20 | 4.33 | -0.3 | 0.940283E+10 | 7447.92 | 05-DEC-02:39 | 4.33 | -0.3 |
Annual Sum or Average | 0.254251E+12 | 0.118300E+12 | ||||||||
Minimum of Months | 0.171948E+11 | 12045.22 | 3.17 | -1.4 | 0.866744E+10 | 6461.22 | 2.00 | -1.7 | ||
Maximum of Months | 0.250605E+11 | 26117.07 | 32.00 | 15.97 | 0.107545E+11 | 7447.92 | 32.00 | 15.97 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.600979E+11 | 74159.77 | 25-JAN-22:54 | 1.00 | -1.0 | 0.309130E+11 | 21407.78 | 24-JAN-00:49 | 1.00 | -1.0 |
February | 0.522893E+11 | 68034.12 | 27-FEB-05:40 | 4.33 | -0.6 | 0.274485E+11 | 20705.58 | 27-FEB-23:40 | 2.00 | -0.6 |
March | 0.606556E+11 | 68577.93 | 03-MAR-22:57 | 0.00 | -3.0 | 0.308908E+11 | 21364.25 | 09-MAR-03:30 | 3.00 | -1.7 |
April | 0.566008E+11 | 75983.73 | 01-APR-02:31 | 2.73 | 1.21 | 0.296450E+11 | 21124.07 | 13-APR-04:49 | 3.50 | 0.99 |
May | 0.663472E+11 | 68698.63 | 18-MAY-23:40 | 5.33 | 3.66 | 0.318185E+11 | 21611.56 | 09-MAY-02:39 | 5.33 | 3.66 |
June | 0.748286E+11 | 55861.46 | 09-JUN-04:17 | 6.60 | 3.51 | 0.314282E+11 | 19186.44 | 01-JUN-01:10 | 6.60 | 3.51 |
July | 0.777011E+11 | 42761.40 | 17-JUL-21:10 | 28.50 | 13.44 | 0.323904E+11 | 19184.83 | 28-JUL-21:19 | 16.00 | 15.35 |
August | 0.785472E+11 | 43304.12 | 16-AUG-20:10 | 28.50 | 11.68 | 0.325821E+11 | 19186.62 | 24-AUG-02:09 | 18.67 | 15.36 |
September | 0.739566E+11 | 56854.57 | 21-SEP-20:19 | 0.37 | -0.6 | 0.314284E+11 | 19599.34 | 16-SEP-04:19 | 0.37 | -0.6 |
October | 0.653605E+11 | 71446.27 | 19-OCT-01:58 | 4.00 | -1.2 | 0.314934E+11 | 20810.43 | 16-OCT-03:09 | 4.00 | -1.2 |
November | 0.594783E+11 | 77129.77 | 17-NOV-00:23 | 3.50 | 1.86 | 0.300493E+11 | 21426.03 | 18-NOV-03:49 | 4.83 | 1.62 |
December | 0.562023E+11 | 68006.23 | 14-DEC-22:32 | 1.33 | -2.0 | 0.299159E+11 | 21502.60 | 05-DEC-02:39 | 1.33 | -2.0 |
Annual Sum or Average | 0.782065E+12 | 0.370003E+12 | ||||||||
Minimum of Months | 0.522893E+11 | 42761.40 | 0.00 | -3.0 | 0.274485E+11 | 19184.83 | 0.37 | -2.0 | ||
Maximum of Months | 0.785472E+11 | 77129.77 | 28.50 | 13.44 | 0.325821E+11 | 21611.56 | 18.67 | 15.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.380114E+09 | 4237.15 | 23-JAN-16:01 | 18.17 | 6.14 | 96306069.13 | 56.69 | 24-JAN-22:19 | 3.00 | 0.25 |
February | 0.389187E+09 | 4189.01 | 26-FEB-16:01 | 17.67 | 5.08 | 86693040.56 | 56.69 | 23-FEB-22:10 | 17.67 | 5.08 |
March | 0.727844E+09 | 4511.35 | 13-MAR-15:01 | 23.00 | 6.97 | 96385831.64 | 56.69 | 10-MAR-22:40 | 23.00 | 6.97 |
April | 0.513602E+09 | 4390.55 | 07-APR-15:01 | 21.00 | 7.80 | 92916501.57 | 56.69 | 07-APR-22:40 | 10.33 | 5.74 |
May | 0.120268E+10 | 4589.42 | 16-MAY-15:01 | 27.00 | 11.83 | 98370921.49 | 56.69 | 18-MAY-00:00 | 14.00 | 7.97 |
June | 0.248556E+10 | 4692.80 | 26-JUN-15:01 | 39.30 | 15.66 | 95827757.41 | 56.69 | 18-JUN-01:10 | 39.30 | 15.66 |
July | 0.239331E+10 | 4676.59 | 15-JUL-15:01 | 34.83 | 13.54 | 98938448.37 | 56.69 | 27-JUL-21:40 | 17.00 | 15.18 |
August | 0.242607E+10 | 4712.70 | 16-AUG-15:01 | 36.17 | 16.19 | 98989184.14 | 56.69 | 20-AUG-00:00 | 20.00 | 15.91 |
September | 0.199640E+10 | 4696.48 | 28-SEP-15:01 | 29.50 | 11.04 | 95541315.98 | 56.69 | 01-SEP-02:09 | 29.50 | 11.04 |
October | 0.994957E+09 | 4648.45 | 11-OCT-15:01 | 25.67 | 9.32 | 97011549.63 | 56.69 | 10-OCT-00:10 | 25.67 | 9.32 |
November | 0.505387E+09 | 4382.22 | 05-NOV-15:01 | 20.67 | 6.59 | 93453990.73 | 56.69 | 06-NOV-23:00 | 6.00 | 1.10 |
December | 0.248579E+09 | 4119.71 | 02-DEC-16:01 | 17.33 | 5.85 | 95263375.87 | 56.69 | 14-DEC-22:10 | 1.83 | -1.9 |
Annual Sum or Average | 0.142637E+11 | 0.114570E+10 | ||||||||
Minimum of Months | 0.248579E+09 | 4119.71 | 17.33 | 5.08 | 86693040.56 | 56.69 | 1.83 | -1.9 | ||
Maximum of Months | 0.248556E+10 | 4712.70 | 39.30 | 16.19 | 98989184.14 | 56.69 | 39.30 | 15.91 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107384E+09 | 4053.07 | 23-JAN-16:01 | 18.17 | 6.14 | 94206318.07 | 56.69 | 10-JAN-01:49 | 18.17 | 6.14 |
February | 0.124873E+09 | 4020.80 | 26-FEB-16:01 | 17.67 | 5.08 | 85128854.30 | 56.69 | 18-FEB-04:40 | 17.67 | 5.08 |
March | 0.399246E+09 | 4325.75 | 13-MAR-15:01 | 23.00 | 6.97 | 95424933.56 | 56.69 | 14-MAR-03:00 | 7.00 | 1.01 |
April | 0.355270E+09 | 4235.36 | 07-APR-15:01 | 21.00 | 7.80 | 92400411.03 | 56.69 | 07-APR-21:40 | 11.33 | 6.32 |
May | 0.108267E+10 | 4472.98 | 16-MAY-15:01 | 27.00 | 11.83 | 98184586.95 | 56.69 | 21-MAY-23:30 | 12.00 | 11.42 |
June | 0.240694E+10 | 4579.12 | 26-JUN-15:01 | 39.30 | 15.66 | 95827779.73 | 56.69 | 18-JUN-00:00 | 39.30 | 15.66 |
July | 0.228955E+10 | 4575.68 | 01-JUL-18:01 | 27.67 | 10.47 | 98930383.47 | 56.69 | 22-JUL-01:30 | 19.50 | 14.92 |
August | 0.212941E+10 | 4576.24 | 16-AUG-15:01 | 36.17 | 16.19 | 98916149.75 | 56.69 | 07-AUG-21:49 | 36.17 | 16.19 |
September | 0.155402E+10 | 4541.28 | 10-SEP-15:01 | 31.70 | 12.51 | 95278866.33 | 56.69 | 01-SEP-22:19 | 31.70 | 12.51 |
October | 0.526509E+09 | 4469.96 | 11-OCT-15:01 | 25.67 | 9.32 | 96040467.01 | 56.69 | 11-OCT-21:00 | 8.00 | 4.10 |
November | 0.156153E+09 | 4177.10 | 05-NOV-15:01 | 20.67 | 6.59 | 91788663.89 | 56.69 | 18-NOV-05:00 | 3.00 | 3.00 |
December | 64748419.40 | 3955.40 | 02-DEC-16:01 | 17.33 | 5.85 | 93683265.46 | 56.69 | 29-DEC-02:49 | 5.00 | 0.56 |
Annual Sum or Average | 0.111968E+11 | 0.113581E+10 | ||||||||
Minimum of Months | 64748419.40 | 3955.40 | 17.33 | 5.08 | 85128854.30 | 56.69 | 3.00 | 0.56 | ||
Maximum of Months | 0.240694E+10 | 4579.12 | 39.30 | 16.19 | 98930383.47 | 56.69 | 39.30 | 16.19 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.538038E+09 | 944.64 | 20-JAN-12:40 | 20.67 | 7.18 | 0.00 | 0.00 | 01-JAN-00:10 | 20.67 | 7.18 |
February | 0.406446E+09 | 907.04 | 18-FEB-13:00 | 20.00 | 7.74 | 0.00 | 0.00 | 01-FEB-00:10 | 20.00 | 7.74 |
March | 0.405587E+09 | 838.39 | 14-MAR-12:40 | 23.33 | 7.71 | 0.00 | 0.00 | 01-MAR-00:10 | 23.33 | 7.71 |
April | 0.221314E+09 | 506.22 | 08-APR-13:10 | 16.00 | 5.20 | 0.00 | 0.00 | 01-APR-00:10 | 16.00 | 5.20 |
May | 0.352172E+09 | 403.74 | 16-MAY-13:30 | 27.50 | 12.26 | 0.00 | 0.00 | 01-MAY-00:10 | 27.50 | 12.26 |
June | 0.624958E+09 | 521.21 | 14-JUN-13:30 | 34.95 | 13.21 | 0.00 | 0.00 | 01-JUN-00:10 | 34.95 | 13.21 |
July | 0.676046E+09 | 557.60 | 23-JUL-13:00 | 34.00 | 16.01 | 0.00 | 0.00 | 01-JUL-00:10 | 34.00 | 16.01 |
August | 0.757237E+09 | 691.52 | 31-AUG-12:50 | 30.00 | 12.10 | 0.00 | 0.00 | 01-AUG-00:10 | 30.00 | 12.10 |
September | 0.757559E+09 | 873.97 | 28-SEP-13:00 | 30.50 | 11.31 | 0.00 | 0.00 | 01-SEP-00:10 | 30.50 | 11.31 |
October | 0.590016E+09 | 900.43 | 10-OCT-12:30 | 23.50 | 7.91 | 0.00 | 0.00 | 01-OCT-00:10 | 23.50 | 7.91 |
November | 0.522615E+09 | 950.13 | 07-NOV-12:10 | 20.00 | 7.48 | 0.00 | 0.00 | 01-NOV-00:10 | 20.00 | 7.48 |
December | 0.376145E+09 | 844.81 | 17-DEC-13:30 | 18.00 | 5.77 | 0.00 | 0.00 | 01-DEC-00:10 | 18.00 | 5.77 |
Annual Sum or Average | 0.622813E+10 | 0.00 | ||||||||
Minimum of Months | 0.221314E+09 | 403.74 | 16.00 | 5.20 | 0.00 | 0.00 | 16.00 | 5.20 | ||
Maximum of Months | 0.757559E+09 | 950.13 | 34.95 | 16.01 | 0.00 | 0.00 | 34.95 | 16.01 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 64180008.59 | 989.65 | 21-JAN-09:01 | 13.00 | 3.75 | 94274229.71 | 56.69 | 18-JAN-22:10 | 13.00 | 3.75 |
February | 58160070.74 | 985.72 | 19-FEB-09:01 | 5.17 | 2.82 | 85072404.74 | 56.69 | 23-FEB-22:10 | 1.00 | 0.92 |
March | 0.147637E+09 | 1114.76 | 14-MAR-15:01 | 22.83 | 7.50 | 95198684.01 | 56.69 | 26-MAR-23:30 | 3.50 | 3.50 |
April | 0.189071E+09 | 1096.92 | 27-APR-15:01 | 20.83 | 10.41 | 92428921.79 | 56.69 | 08-APR-23:10 | 20.83 | 10.41 |
May | 0.494056E+09 | 1252.71 | 17-MAY-15:01 | 26.83 | 11.93 | 97202275.45 | 56.69 | 21-MAY-23:10 | 12.00 | 11.42 |
June | 0.826020E+09 | 1271.31 | 26-JUN-15:01 | 39.30 | 15.66 | 95192025.68 | 56.69 | 07-JUN-22:10 | 39.30 | 15.66 |
July | 0.860684E+09 | 1273.63 | 16-JUL-15:01 | 35.83 | 14.63 | 98342962.14 | 56.69 | 24-JUL-21:00 | 20.00 | 15.36 |
August | 0.747396E+09 | 1266.76 | 18-AUG-15:01 | 34.50 | 13.42 | 98095542.10 | 56.69 | 10-AUG-21:10 | 34.50 | 13.42 |
September | 0.567773E+09 | 1266.29 | 11-SEP-15:01 | 29.22 | 13.50 | 94217668.34 | 56.69 | 01-SEP-01:19 | 29.22 | 13.50 |
October | 0.200954E+09 | 1164.68 | 11-OCT-15:01 | 25.67 | 9.32 | 95490212.24 | 56.69 | 21-OCT-23:19 | 4.00 | 1.94 |
November | 87415792.23 | 990.08 | 09-NOV-19:02 | 11.67 | 7.20 | 91622745.65 | 56.87 | 10-NOV-05:40 | 6.33 | 5.10 |
December | 53969468.76 | 795.62 | 02-DEC-09:01 | 11.75 | 4.10 | 93956063.65 | 56.69 | 14-DEC-22:10 | 1.83 | -1.9 |
Annual Sum or Average | 0.429732E+10 | 0.113109E+10 | ||||||||
Minimum of Months | 53969468.76 | 795.62 | 5.17 | 2.82 | 85072404.74 | 56.69 | 1.00 | -1.9 | ||
Maximum of Months | 0.860684E+09 | 1273.63 | 39.30 | 15.66 | 98342962.14 | 56.87 | 39.30 | 15.66 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.372890E+09 | 3655.05 | 23-JAN-16:01 | 18.17 | 6.14 | 96499342.81 | 56.69 | 25-JAN-22:30 | 2.00 | -0.4 |
February | 0.426351E+09 | 3676.88 | 24-FEB-09:01 | 4.17 | 1.64 | 86964468.78 | 56.69 | 23-FEB-22:10 | 4.17 | 1.64 |
March | 0.775108E+09 | 3895.90 | 13-MAR-15:01 | 23.00 | 6.97 | 96734355.49 | 56.69 | 16-MAR-21:00 | 10.00 | 4.14 |
April | 0.601774E+09 | 3789.56 | 07-APR-15:01 | 21.00 | 7.80 | 93310223.18 | 56.69 | 12-APR-22:10 | 9.50 | 3.98 |
May | 0.130279E+10 | 4028.42 | 16-MAY-15:01 | 27.00 | 11.83 | 98718682.42 | 56.69 | 18-MAY-02:09 | 12.00 | 7.62 |
June | 0.261100E+10 | 4068.40 | 26-JUN-15:01 | 39.30 | 15.66 | 96005832.15 | 56.69 | 21-JUN-23:00 | 39.30 | 15.66 |
July | 0.264885E+10 | 4115.15 | 17-JUL-08:61 | 28.50 | 13.53 | 99082323.80 | 56.69 | 31-JUL-22:19 | 18.40 | 17.00 |
August | 0.265871E+10 | 4068.82 | 16-AUG-15:01 | 36.17 | 16.19 | 99193376.87 | 56.69 | 20-AUG-03:39 | 20.00 | 14.78 |
September | 0.209879E+10 | 4057.36 | 12-SEP-15:01 | 29.68 | 13.86 | 95760006.42 | 56.69 | 01-SEP-02:39 | 29.68 | 13.86 |
October | 0.962470E+09 | 4007.37 | 11-OCT-15:01 | 25.67 | 9.32 | 97225655.95 | 56.69 | 11-OCT-22:00 | 7.00 | 3.61 |
November | 0.489519E+09 | 3783.70 | 05-NOV-15:01 | 20.67 | 6.59 | 93516416.93 | 56.69 | 09-NOV-22:10 | 8.00 | 6.42 |
December | 0.252964E+09 | 3583.87 | 02-DEC-16:01 | 17.33 | 5.85 | 95378674.01 | 56.69 | 29-DEC-02:49 | 5.00 | 0.56 |
Annual Sum or Average | 0.152012E+11 | 0.114839E+10 | ||||||||
Minimum of Months | 0.252964E+09 | 3583.87 | 4.17 | 1.64 | 86964468.78 | 56.69 | 2.00 | -0.4 | ||
Maximum of Months | 0.265871E+10 | 4115.15 | 39.30 | 16.19 | 99193376.87 | 56.69 | 39.30 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110629E+09 | 3358.54 | 20-JAN-09:02 | 10.67 | 3.20 | 94018962.81 | 56.69 | 27-JAN-01:49 | 3.17 | 2.44 |
February | 0.155222E+09 | 3554.23 | 24-FEB-09:01 | 4.17 | 1.64 | 85284028.02 | 56.69 | 27-FEB-05:19 | 4.67 | -0.4 |
March | 0.422914E+09 | 3750.39 | 14-MAR-15:01 | 22.83 | 7.50 | 95855051.21 | 56.69 | 13-MAR-21:30 | 22.83 | 7.50 |
April | 0.433452E+09 | 3665.81 | 19-APR-15:01 | 20.83 | 8.49 | 92901643.76 | 56.69 | 19-APR-21:00 | 12.00 | 6.36 |
May | 0.117411E+10 | 3929.77 | 16-MAY-15:01 | 27.00 | 11.83 | 98601957.84 | 56.69 | 18-MAY-01:00 | 12.00 | 7.62 |
June | 0.252824E+10 | 3972.60 | 26-JUN-15:01 | 39.30 | 15.66 | 96005642.34 | 56.69 | 21-JUN-23:00 | 39.30 | 15.66 |
July | 0.254088E+10 | 4028.45 | 17-JUL-08:61 | 28.50 | 13.53 | 99078121.72 | 56.69 | 24-JUL-02:00 | 19.00 | 15.02 |
August | 0.235381E+10 | 3953.29 | 16-AUG-15:01 | 36.17 | 16.19 | 99175136.01 | 56.69 | 04-AUG-01:39 | 36.17 | 16.19 |
September | 0.163951E+10 | 3938.14 | 06-SEP-15:01 | 31.00 | 11.89 | 95642479.79 | 56.69 | 01-SEP-01:00 | 31.00 | 11.89 |
October | 0.475747E+09 | 3848.86 | 11-OCT-15:01 | 25.67 | 9.32 | 96446670.04 | 56.69 | 10-OCT-22:40 | 25.67 | 9.32 |
November | 0.166487E+09 | 3453.47 | 17-NOV-09:01 | 9.33 | 4.24 | 91554253.04 | 56.69 | 18-NOV-05:00 | 3.00 | 3.00 |
December | 74995363.78 | 3296.44 | 02-DEC-09:01 | 11.75 | 4.10 | 93484364.32 | 56.69 | 26-DEC-05:49 | 6.33 | 0.92 |
Annual Sum or Average | 0.120760E+11 | 0.113805E+10 | ||||||||
Minimum of Months | 74995363.78 | 3296.44 | 4.17 | 1.64 | 85284028.02 | 56.69 | 3.00 | -0.4 | ||
Maximum of Months | 0.254088E+10 | 4028.45 | 39.30 | 16.19 | 99175136.01 | 56.69 | 39.30 | 16.19 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286462E+10 | 2896.22 | 24-JAN-01:13 | 4.33 | -0.8 | 0.132624E+10 | 895.80 | 24-JAN-22:30 | 3.00 | 0.25 |
February | 0.222779E+10 | 2485.00 | 27-FEB-23:33 | 2.00 | -0.6 | 0.118117E+10 | 897.95 | 27-FEB-23:40 | 2.00 | -0.6 |
March | 0.304559E+10 | 2506.70 | 13-MAR-05:05 | 6.17 | 0.88 | 0.136975E+10 | 951.83 | 15-MAR-22:40 | 11.33 | 2.68 |
April | 0.289215E+10 | 3144.88 | 22-APR-00:43 | 3.17 | 2.66 | 0.130295E+10 | 888.01 | 12-APR-21:40 | 3.17 | 2.66 |
May | 0.378448E+10 | 3086.47 | 19-MAY-01:37 | 4.33 | 2.88 | 0.150555E+10 | 951.83 | 16-MAY-21:40 | 4.33 | 2.88 |
June | 0.497927E+10 | 3603.69 | 26-JUN-18:30 | 36.60 | 14.84 | 0.156667E+10 | 951.90 | 07-JUN-21:10 | 36.60 | 14.84 |
July | 0.521192E+10 | 3245.92 | 15-JUL-18:30 | 32.50 | 12.97 | 0.161533E+10 | 951.86 | 15-JUL-00:10 | 32.50 | 12.97 |
August | 0.514284E+10 | 3344.48 | 11-AUG-18:30 | 30.00 | 11.17 | 0.162128E+10 | 951.88 | 07-AUG-21:19 | 30.00 | 11.17 |
September | 0.459599E+10 | 3019.98 | 12-SEP-18:03 | 27.33 | 13.46 | 0.154741E+10 | 951.92 | 01-SEP-01:10 | 27.33 | 13.46 |
October | 0.345565E+10 | 3257.69 | 12-OCT-02:59 | 3.00 | 0.65 | 0.146595E+10 | 951.83 | 11-OCT-22:19 | 3.00 | 0.65 |
November | 0.283759E+10 | 2829.28 | 17-NOV-00:23 | 3.50 | 1.86 | 0.130859E+10 | 903.94 | 09-NOV-22:40 | 3.50 | 1.86 |
December | 0.226270E+10 | 2876.28 | 05-DEC-02:53 | 4.00 | -2.2 | 0.126640E+10 | 843.48 | 05-DEC-02:39 | 4.00 | -2.2 |
Annual Sum or Average | 0.433006E+11 | 0.170773E+11 | ||||||||
Minimum of Months | 0.222779E+10 | 2485.00 | 2.00 | -2.2 | 0.118117E+10 | 843.48 | 2.00 | -2.2 | ||
Maximum of Months | 0.521192E+10 | 3603.69 | 36.60 | 14.84 | 0.162128E+10 | 951.92 | 36.60 | 14.84 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.321904E+09 | 4483.91 | 23-JAN-16:01 | 18.17 | 6.14 | 95744685.17 | 56.69 | 22-JAN-00:10 | 18.17 | 6.14 |
February | 0.341889E+09 | 4419.86 | 26-FEB-16:01 | 17.67 | 5.08 | 86330271.50 | 56.69 | 23-FEB-22:10 | 17.67 | 5.08 |
March | 0.666783E+09 | 4776.46 | 13-MAR-15:01 | 23.00 | 6.97 | 96044340.90 | 56.69 | 16-MAR-23:00 | 9.00 | 4.09 |
April | 0.481105E+09 | 4642.58 | 07-APR-15:01 | 21.00 | 7.80 | 92570293.08 | 56.69 | 12-APR-22:00 | 7.00 | 2.77 |
May | 0.108350E+10 | 4860.59 | 16-MAY-15:01 | 27.00 | 11.83 | 98151022.92 | 56.69 | 25-MAY-03:00 | 11.00 | 10.43 |
June | 0.248682E+10 | 4983.65 | 26-JUN-15:01 | 39.30 | 15.66 | 95756921.56 | 56.70 | 19-JUN-21:30 | 39.30 | 15.66 |
July | 0.236376E+10 | 4958.86 | 15-JUL-15:01 | 34.83 | 13.54 | 98858656.87 | 56.70 | 25-JUL-00:49 | 19.17 | 14.53 |
August | 0.239710E+10 | 5006.23 | 16-AUG-15:01 | 36.17 | 16.19 | 98890550.26 | 56.70 | 07-AUG-21:10 | 36.17 | 16.19 |
September | 0.187106E+10 | 4976.16 | 28-SEP-15:01 | 29.50 | 11.04 | 95367525.97 | 56.69 | 02-SEP-23:10 | 29.50 | 11.04 |
October | 0.864065E+09 | 4916.72 | 11-OCT-15:01 | 25.67 | 9.32 | 96673314.90 | 56.69 | 01-OCT-00:10 | 25.67 | 9.32 |
November | 0.435407E+09 | 4644.56 | 05-NOV-15:01 | 20.67 | 6.59 | 93032819.70 | 56.69 | 09-NOV-23:10 | 8.00 | 6.96 |
December | 0.212421E+09 | 4365.95 | 02-DEC-16:01 | 17.33 | 5.85 | 94786459.38 | 56.69 | 02-DEC-05:00 | 17.33 | 5.85 |
Annual Sum or Average | 0.135258E+11 | 0.114221E+10 | ||||||||
Minimum of Months | 0.212421E+09 | 4365.95 | 17.33 | 5.08 | 86330271.50 | 56.69 | 7.00 | 2.77 | ||
Maximum of Months | 0.248682E+10 | 5006.23 | 39.30 | 16.19 | 98890550.26 | 56.70 | 39.30 | 16.19 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 81737467.75 | 4253.94 | 23-JAN-16:01 | 18.17 | 6.14 | 93616826.69 | 56.69 | 22-JAN-00:10 | 18.17 | 6.14 |
February | 0.101230E+09 | 4218.32 | 26-FEB-16:01 | 17.67 | 5.08 | 84726203.28 | 56.69 | 26-FEB-00:20 | 17.67 | 5.08 |
March | 0.344372E+09 | 4558.53 | 13-MAR-15:01 | 23.00 | 6.97 | 95051183.11 | 56.69 | 15-MAR-02:30 | 13.00 | 4.46 |
April | 0.322657E+09 | 4463.19 | 07-APR-15:01 | 21.00 | 7.80 | 92043548.05 | 56.69 | 19-APR-23:30 | 10.50 | 5.09 |
May | 0.957316E+09 | 4726.10 | 16-MAY-15:01 | 27.00 | 11.83 | 97953195.29 | 56.69 | 14-MAY-23:19 | 27.00 | 11.83 |
June | 0.240198E+10 | 4851.98 | 26-JUN-15:01 | 39.30 | 15.66 | 95760065.83 | 56.70 | 19-JUN-21:30 | 39.30 | 15.66 |
July | 0.225318E+10 | 4839.17 | 01-JUL-18:01 | 27.67 | 10.47 | 98851878.20 | 56.70 | 25-JUL-00:40 | 19.33 | 14.59 |
August | 0.208283E+10 | 4848.89 | 16-AUG-15:01 | 36.17 | 16.19 | 98818699.67 | 56.69 | 04-AUG-21:10 | 36.17 | 16.19 |
September | 0.141186E+10 | 4797.82 | 10-SEP-15:01 | 31.70 | 12.51 | 95070405.92 | 56.69 | 13-SEP-21:49 | 14.58 | 10.79 |
October | 0.423068E+09 | 4706.55 | 11-OCT-15:01 | 25.67 | 9.32 | 95565606.00 | 56.69 | 27-OCT-04:19 | 5.00 | 5.00 |
November | 0.126066E+09 | 4397.72 | 07-NOV-16:01 | 20.00 | 7.03 | 91258092.32 | 56.69 | 18-NOV-05:00 | 3.00 | 3.00 |
December | 50285612.70 | 4163.82 | 02-DEC-16:01 | 17.33 | 5.85 | 93260287.33 | 56.69 | 02-DEC-05:00 | 17.33 | 5.85 |
Annual Sum or Average | 0.105566E+11 | 0.113198E+10 | ||||||||
Minimum of Months | 50285612.70 | 4163.82 | 17.33 | 5.08 | 84726203.28 | 56.69 | 3.00 | 3.00 | ||
Maximum of Months | 0.240198E+10 | 4851.98 | 39.30 | 16.19 | 98851878.20 | 56.70 | 39.30 | 16.19 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.828989E+09 | 2236.34 | 23-JAN-16:01 | 18.17 | 6.14 | 97602543.11 | 56.70 | 28-JAN-00:20 | 3.00 | 3.00 |
February | 0.667954E+09 | 2191.50 | 18-FEB-16:01 | 17.83 | 7.37 | 87759022.23 | 56.69 | 22-FEB-22:10 | 2.83 | 2.42 |
March | 0.706976E+09 | 2364.99 | 13-MAR-15:01 | 23.00 | 6.97 | 96887452.26 | 56.69 | 16-MAR-22:40 | 9.33 | 4.12 |
April | 0.387467E+09 | 2272.45 | 07-APR-15:01 | 21.00 | 7.80 | 93104298.53 | 56.69 | 18-APR-21:19 | 9.33 | 5.05 |
May | 0.664044E+09 | 2381.69 | 16-MAY-15:01 | 27.00 | 11.83 | 98164755.07 | 56.69 | 23-MAY-21:10 | 13.83 | 10.93 |
June | 0.125858E+10 | 2406.02 | 26-JUN-15:01 | 39.30 | 15.66 | 95707226.13 | 56.69 | 20-JUN-22:40 | 39.30 | 15.66 |
July | 0.134445E+10 | 2405.24 | 18-JUL-15:01 | 30.83 | 14.94 | 98832667.27 | 56.69 | 25-JUL-23:10 | 19.83 | 14.74 |
August | 0.148108E+10 | 2427.09 | 16-AUG-15:01 | 36.17 | 16.19 | 98901908.06 | 56.69 | 26-AUG-03:20 | 19.67 | 15.25 |
September | 0.140305E+10 | 2445.97 | 28-SEP-15:01 | 29.50 | 11.04 | 95545540.55 | 56.69 | 12-SEP-21:10 | 29.50 | 11.04 |
October | 0.982666E+09 | 2428.31 | 11-OCT-15:01 | 25.67 | 9.32 | 97322258.04 | 56.83 | 18-OCT-04:00 | 5.00 | -0.4 |
November | 0.865574E+09 | 2326.40 | 05-NOV-15:01 | 20.67 | 6.59 | 94514688.33 | 56.69 | 09-NOV-23:40 | 8.00 | 7.22 |
December | 0.610958E+09 | 2184.01 | 02-DEC-16:01 | 17.33 | 5.85 | 96910559.70 | 56.69 | 15-DEC-22:10 | 2.17 | -0.8 |
Annual Sum or Average | 0.112018E+11 | 0.115125E+10 | ||||||||
Minimum of Months | 0.387467E+09 | 2184.01 | 17.33 | 5.85 | 87759022.23 | 56.69 | 2.17 | -0.8 | ||
Maximum of Months | 0.148108E+10 | 2445.97 | 39.30 | 16.19 | 98901908.06 | 56.83 | 39.30 | 15.66 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334404E+11 | 32363.12 | 25-JAN-22:54 | 1.00 | -1.0 | 0.174220E+11 | 13540.91 | 24-JAN-02:39 | 1.00 | -1.0 |
February | 0.299385E+11 | 32505.42 | 21-FEB-23:44 | 1.00 | 1.00 | 0.156827E+11 | 13634.88 | 27-FEB-23:40 | 2.00 | -0.6 |
March | 0.355144E+11 | 36563.14 | 17-MAR-22:09 | 1.17 | 1.17 | 0.179762E+11 | 13746.74 | 31-MAR-02:20 | 4.00 | 0.83 |
April | 0.350151E+11 | 34812.03 | 01-APR-02:31 | 2.73 | 1.21 | 0.175269E+11 | 13848.02 | 13-APR-04:49 | 3.50 | 0.99 |
May | 0.407822E+11 | 32832.12 | 12-MAY-01:37 | 3.33 | 1.79 | 0.187561E+11 | 14641.89 | 09-MAY-02:39 | 3.33 | 1.79 |
June | 0.439907E+11 | 30350.87 | 09-JUN-04:17 | 6.60 | 3.51 | 0.184895E+11 | 11387.27 | 14-JUN-21:19 | 22.57 | 12.23 |
July | 0.453154E+11 | 23066.27 | 17-JUL-21:20 | 28.00 | 13.33 | 0.190263E+11 | 11371.63 | 14-JUL-21:19 | 28.00 | 13.33 |
August | 0.446076E+11 | 22699.91 | 16-AUG-21:20 | 25.33 | 11.70 | 0.190521E+11 | 11364.36 | 18-AUG-21:19 | 18.67 | 8.73 |
September | 0.410061E+11 | 30717.25 | 21-SEP-21:19 | 0.53 | -0.8 | 0.182248E+11 | 12373.66 | 16-SEP-04:19 | 0.53 | -0.8 |
October | 0.367901E+11 | 31918.69 | 16-OCT-22:45 | 1.17 | -2.4 | 0.181298E+11 | 13326.47 | 16-OCT-03:09 | 1.17 | -2.4 |
November | 0.332713E+11 | 38227.68 | 16-NOV-01:01 | 2.83 | 2.34 | 0.170860E+11 | 14143.19 | 18-NOV-03:49 | 4.83 | 1.62 |
December | 0.321446E+11 | 32297.87 | 26-DEC-23:57 | 2.00 | -1.6 | 0.171148E+11 | 14145.07 | 05-DEC-02:39 | 2.00 | -1.6 |
Annual Sum or Average | 0.451816E+12 | 0.214487E+12 | ||||||||
Minimum of Months | 0.299385E+11 | 22699.91 | 0.53 | -2.4 | 0.156827E+11 | 11364.36 | 0.53 | -2.4 | ||
Maximum of Months | 0.453154E+11 | 38227.68 | 28.00 | 13.33 | 0.190521E+11 | 14641.89 | 28.00 | 13.33 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.356911E+11 | 37969.90 | 25-JAN-22:54 | 1.00 | -1.0 | 0.180326E+11 | 14038.25 | 24-JAN-00:20 | 1.00 | -1.0 |
February | 0.319863E+11 | 34113.51 | 28-FEB-22:52 | 0.00 | -0.0 | 0.162485E+11 | 13751.99 | 27-FEB-23:40 | 0.00 | -0.0 |
March | 0.378748E+11 | 40085.79 | 17-MAR-22:09 | 1.17 | 1.17 | 0.185090E+11 | 13982.41 | 21-MAR-21:49 | 1.17 | 0.24 |
April | 0.374079E+11 | 38030.62 | 01-APR-02:31 | 2.73 | 1.21 | 0.180278E+11 | 14082.78 | 13-APR-04:49 | 3.50 | 0.99 |
May | 0.430932E+11 | 34505.88 | 12-MAY-01:37 | 3.33 | 1.79 | 0.190382E+11 | 14795.04 | 09-MAY-02:39 | 3.33 | 1.79 |
June | 0.462504E+11 | 31764.86 | 09-JUN-04:38 | 6.60 | 3.57 | 0.186307E+11 | 11417.38 | 14-JUN-21:19 | 22.57 | 12.23 |
July | 0.476242E+11 | 24488.54 | 17-JUL-21:20 | 28.00 | 13.33 | 0.191743E+11 | 11408.17 | 14-JUL-21:19 | 28.00 | 13.33 |
August | 0.468361E+11 | 24099.39 | 16-AUG-21:20 | 25.33 | 11.70 | 0.192117E+11 | 11402.02 | 18-AUG-21:19 | 18.67 | 8.73 |
September | 0.430759E+11 | 32348.45 | 21-SEP-21:19 | 0.53 | -0.8 | 0.184261E+11 | 12535.80 | 16-SEP-04:19 | 0.53 | -0.8 |
October | 0.389134E+11 | 34104.44 | 26-OCT-01:15 | 3.43 | 0.43 | 0.185678E+11 | 13541.27 | 16-OCT-03:09 | 3.43 | 0.43 |
November | 0.354028E+11 | 37401.07 | 17-NOV-00:23 | 3.50 | 1.86 | 0.176459E+11 | 14311.23 | 18-NOV-03:49 | 4.83 | 1.62 |
December | 0.344710E+11 | 34235.62 | 26-DEC-23:57 | 2.00 | -1.6 | 0.177258E+11 | 14635.65 | 05-DEC-02:39 | 2.00 | -1.6 |
Annual Sum or Average | 0.478627E+12 | 0.219238E+12 | ||||||||
Minimum of Months | 0.319863E+11 | 24099.39 | 0.00 | -1.6 | 0.162485E+11 | 11402.02 | 0.00 | -1.6 | ||
Maximum of Months | 0.476242E+11 | 40085.79 | 28.00 | 13.33 | 0.192117E+11 | 14795.04 | 28.00 | 13.33 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.487514E+11 | 37472.95 | 10-JAN-13:41 | 5.00 | 3.98 | 0.188925E+11 | 11542.31 | 13-JAN-17:19 | 1.67 | -3.1 |
February | 0.438208E+11 | 39235.65 | 23-FEB-18:01 | 3.83 | 1.38 | 0.170646E+11 | 11472.36 | 15-FEB-17:19 | 3.83 | 1.38 |
March | 0.505642E+11 | 36225.33 | 05-MAR-18:41 | 1.17 | -3.8 | 0.188979E+11 | 11370.33 | 17-MAR-15:30 | 6.50 | 6.21 |
April | 0.492510E+11 | 35886.03 | 09-APR-22:38 | 4.33 | -1.1 | 0.182865E+11 | 11515.84 | 01-APR-17:40 | 4.33 | -1.1 |
May | 0.547733E+11 | 34630.54 | 02-MAY-21:45 | 2.40 | -0.3 | 0.188786E+11 | 11319.60 | 06-MAY-17:19 | 23.67 | 10.28 |
June | 0.568895E+11 | 31385.31 | 26-JUN-10:40 | 32.70 | 15.62 | 0.182662E+11 | 11319.64 | 10-JUN-17:19 | 32.70 | 15.62 |
July | 0.585568E+11 | 31640.96 | 23-JUL-10:50 | 29.83 | 15.95 | 0.188681E+11 | 11319.72 | 08-JUL-17:19 | 29.83 | 15.95 |
August | 0.583850E+11 | 31717.44 | 05-AUG-10:40 | 29.00 | 17.63 | 0.188756E+11 | 11319.74 | 05-AUG-17:19 | 21.33 | 16.54 |
September | 0.546157E+11 | 35828.35 | 21-SEP-16:16 | 0.50 | -0.3 | 0.182625E+11 | 11363.20 | 21-SEP-15:30 | 0.50 | -0.3 |
October | 0.513697E+11 | 36330.22 | 21-OCT-07:41 | 3.67 | 0.90 | 0.188879E+11 | 11335.58 | 28-OCT-17:00 | 9.00 | 4.53 |
November | 0.478156E+11 | 42885.36 | 23-NOV-11:06 | 3.17 | 0.73 | 0.182834E+11 | 11543.53 | 13-NOV-18:10 | 3.17 | 0.73 |
December | 0.471574E+11 | 36907.97 | 16-DEC-09:03 | 2.00 | -1.1 | 0.188825E+11 | 11515.64 | 16-DEC-18:10 | 0.83 | -1.8 |
Annual Sum or Average | 0.621950E+12 | 0.222346E+12 | ||||||||
Minimum of Months | 0.438208E+11 | 31385.31 | 0.50 | -3.8 | 0.170646E+11 | 11319.60 | 0.50 | -3.1 | ||
Maximum of Months | 0.585568E+11 | 42885.36 | 32.70 | 17.63 | 0.188979E+11 | 11543.53 | 32.70 | 16.54 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.393355E+10 | 4606.36 | 24-JAN-01:13 | 4.33 | -0.8 | 0.136208E+10 | 932.78 | 24-JAN-22:30 | 3.00 | 0.25 |
February | 0.306668E+10 | 3956.66 | 27-FEB-23:33 | 2.00 | -0.6 | 0.123287E+10 | 934.14 | 27-FEB-23:40 | 2.00 | -0.6 |
March | 0.457156E+10 | 5741.15 | 15-MAR-13:30 | 20.50 | 6.02 | 0.142873E+10 | 1007.38 | 14-MAR-21:19 | 20.50 | 6.02 |
April | 0.446932E+10 | 5154.72 | 22-APR-00:43 | 3.17 | 2.66 | 0.138919E+10 | 990.99 | 20-APR-21:30 | 3.17 | 2.66 |
May | 0.688470E+10 | 4998.42 | 31-MAY-15:03 | 28.00 | 14.67 | 0.162580E+10 | 1007.41 | 16-MAY-21:10 | 28.00 | 14.67 |
June | 0.105949E+11 | 7334.85 | 26-JUN-14:10 | 37.98 | 15.29 | 0.165966E+10 | 1007.48 | 07-JUN-21:10 | 37.98 | 15.29 |
July | 0.109529E+11 | 7317.89 | 23-JUL-12:50 | 33.67 | 16.02 | 0.170992E+10 | 1007.42 | 15-JUL-00:10 | 33.67 | 16.02 |
August | 0.107842E+11 | 7655.33 | 16-AUG-15:01 | 36.17 | 16.19 | 0.171533E+10 | 1007.46 | 24-AUG-02:09 | 18.67 | 15.36 |
September | 0.893773E+10 | 7348.54 | 09-SEP-12:50 | 32.62 | 13.01 | 0.162770E+10 | 1007.52 | 01-SEP-01:10 | 32.62 | 13.01 |
October | 0.554438E+10 | 5734.02 | 11-OCT-13:10 | 26.17 | 9.50 | 0.151664E+10 | 1007.39 | 10-OCT-22:10 | 26.17 | 9.50 |
November | 0.423357E+10 | 4533.49 | 17-NOV-00:23 | 3.50 | 1.86 | 0.135821E+10 | 966.36 | 09-NOV-22:30 | 3.50 | 1.86 |
December | 0.301942E+10 | 4608.61 | 05-DEC-02:53 | 4.00 | -2.2 | 0.132658E+10 | 893.30 | 04-DEC-22:30 | 4.00 | -2.2 |
Annual Sum or Average | 0.769929E+11 | 0.179527E+11 | ||||||||
Minimum of Months | 0.301942E+10 | 3956.66 | 2.00 | -2.2 | 0.123287E+10 | 893.30 | 2.00 | -2.2 | ||
Maximum of Months | 0.109529E+11 | 7655.33 | 37.98 | 16.19 | 0.171533E+10 | 1007.52 | 37.98 | 16.02 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43612885.44 | 10358.82 | 10-JAN-01:35 | 4.00 |
February | 14609254.58 | 8851.45 | 27-FEB-05:35 | 4.33 |
March | 32975509.56 | 7654.28 | 09-MAR-02:45 | 3.33 |
April | 50196723.97 | 9986.41 | 09-APR-04:20 | 4.00 |
May | 14298038.21 | 8201.73 | 18-MAY-23:35 | 5.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 44304149.39 | 11369.60 | 16-OCT-02:23 | 3.50 |
November | 23598720.71 | 11219.26 | 18-NOV-05:38 | 3.33 |
December | 29078356.76 | 10734.79 | 30-DEC-02:33 | 3.67 |
Annual Sum or Average | 0.252674E+09 | |||
Minimum of Months | 0.00 | 0.00 | 3.33 | |
Maximum of Months | 50196723.97 | 11369.60 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165415E+09 | 1527.10 | 05-JAN-09:10 | -17.0 |
February | 0.349967E+09 | 1295.82 | 05-FEB-17:00 | -7.0 |
March | 0.209129E+09 | 1461.70 | 19-MAR-08:03 | -13.0 |
April | 0.160798E+09 | 879.67 | 03-APR-06:10 | -7.7 |
May | 5268213.06 | 792.28 | 02-MAY-21:44 | 2.40 |
June | 12705.44 | 76.31 | 09-JUN-04:37 | 6.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 359595.41 | 278.13 | 22-SEP-08:28 | 3.30 |
October | 0.217942E+09 | 1212.00 | 31-OCT-15:00 | -8.0 |
November | 0.157134E+09 | 1165.00 | 30-NOV-07:10 | -11.3 |
December | 0.514966E+09 | 2402.31 | 21-DEC-08:06 | -20.0 |
Annual Sum or Average | 0.178099E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.514966E+09 | 2402.31 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4277380.87 | 662.09 | 24-JAN-03:03 | 3.00 |
February | 1574135.05 | 726.37 | 22-FEB-22:43 | 2.17 |
March | 5025032.67 | 913.33 | 27-MAR-00:13 | 3.00 |
April | 4908774.84 | 880.70 | 08-APR-23:23 | 4.00 |
May | 1476288.37 | 702.58 | 18-MAY-23:35 | 5.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 10021.47 | 50.39 | 22-SEP-08:28 | 3.30 |
October | 4301529.08 | 772.00 | 15-OCT-23:44 | 4.17 |
November | 3551681.66 | 627.80 | 15-NOV-24:00 | 3.00 |
December | 4498149.01 | 581.14 | 04-DEC-05:45 | 3.50 |
Annual Sum or Average | 29622993.02 | |||
Minimum of Months | 0.00 | 0.00 | 2.17 | |
Maximum of Months | 5025032.67 | 913.33 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32509636.79 | 452.49 | 06-JAN-04:00 | -12.0 |
February | 48016629.23 | 383.95 | 27-FEB-05:35 | 4.33 |
March | 7764699.22 | 431.10 | 27-MAR-00:26 | 3.00 |
April | 5398051.87 | 452.49 | 06-APR-01:25 | 3.50 |
May | 1221637.55 | 401.59 | 02-MAY-21:44 | 2.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 8699.54 | 33.72 | 23-SEP-04:55 | 7.20 |
October | 11420139.64 | 422.25 | 26-OCT-02:20 | 3.20 |
November | 14791623.29 | 432.42 | 18-NOV-05:38 | 3.33 |
December | 0.230941E+09 | 948.85 | 22-DEC-04:50 | -21.2 |
Annual Sum or Average | 0.352072E+09 | |||
Minimum of Months | 0.00 | 0.00 | -21.2 | |
Maximum of Months | 0.230941E+09 | 948.85 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 69214185.77 | 534.36 | 19-JAN-01:33 | 4.00 |
February | 0.112048E+09 | 509.28 | 10-FEB-15:03 | 4.00 |
March | 33599310.83 | 527.98 | 27-MAR-00:26 | 3.00 |
April | 23723753.12 | 533.07 | 25-APR-01:25 | 3.50 |
May | 3248019.95 | 552.70 | 02-MAY-21:44 | 2.40 |
June | 5036.38 | 41.76 | 09-JUN-04:37 | 6.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 247132.13 | 139.36 | 24-SEP-05:16 | 5.90 |
October | 39188983.41 | 522.37 | 16-OCT-02:23 | 3.50 |
November | 56567951.90 | 539.01 | 18-NOV-05:38 | 3.33 |
December | 0.266342E+09 | 709.31 | 23-DEC-07:40 | -22.1 |
Annual Sum or Average | 0.604184E+09 | |||
Minimum of Months | 0.00 | 0.00 | -22.1 | |
Maximum of Months | 0.266342E+09 | 709.31 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8692070.67 | 8548.44 | 19-JAN-02:23 | 3.50 |
February | 635897.22 | 2349.00 | 27-FEB-05:25 | 4.50 |
March | 6203355.31 | 8818.97 | 09-MAR-04:18 | 3.33 |
April | 4219832.95 | 9119.66 | 01-APR-02:20 | 3.17 |
May | 2998737.29 | 6916.72 | 12-MAY-01:44 | 3.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 17230632.61 | 9819.95 | 19-OCT-02:18 | 3.33 |
November | 7489690.27 | 10200.16 | 17-NOV-02:38 | 3.33 |
December | 5158305.73 | 8680.40 | 30-DEC-02:33 | 3.67 |
Annual Sum or Average | 52628522.04 | |||
Minimum of Months | 0.00 | 0.00 | 3.17 | |
Maximum of Months | 17230632.61 | 10200.16 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26718391.72 | 4894.71 | 24-JAN-00:29 | 4.00 |
February | 26074751.27 | 3134.47 | 27-FEB-23:05 | 2.00 |
March | 27074966.72 | 6194.73 | 09-MAR-03:00 | 3.00 |
April | 36576820.50 | 4773.02 | 25-APR-01:25 | 3.50 |
May | 9798414.32 | 4407.05 | 02-MAY-21:44 | 2.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 1221125.75 | 1782.25 | 22-SEP-08:28 | 3.30 |
October | 58838546.33 | 6278.32 | 12-OCT-02:54 | 3.00 |
November | 24459115.17 | 6263.92 | 17-NOV-02:38 | 3.33 |
December | 80725635.89 | 4731.50 | 30-DEC-00:39 | 3.67 |
Annual Sum or Average | 0.291488E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.00 | |
Maximum of Months | 80725635.89 | 6278.32 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 87398938.47 | 19501.59 | 19-JAN-01:33 | 4.00 |
February | 30035490.78 | 13999.73 | 27-FEB-05:35 | 4.33 |
March | 93043095.69 | 20246.56 | 09-MAR-05:27 | 3.00 |
April | 0.103122E+09 | 20872.01 | 22-APR-00:40 | 3.33 |
May | 31414271.77 | 19144.91 | 12-MAY-01:44 | 3.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 60144.09 | 501.20 | 22-SEP-08:28 | 3.30 |
October | 98460935.99 | 21298.02 | 16-OCT-02:23 | 3.50 |
November | 60264659.76 | 20978.40 | 18-NOV-05:38 | 3.33 |
December | 70124474.78 | 20173.78 | 30-DEC-02:33 | 3.67 |
Annual Sum or Average | 0.573924E+09 | |||
Minimum of Months | 0.00 | 0.00 | 3.00 | |
Maximum of Months | 0.103122E+09 | 21298.02 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.597114E+09 | 2972.35 | 05-JAN-09:01 | -17.0 |
February | 0.715228E+09 | 2958.48 | 05-FEB-16:01 | -6.2 |
March | 0.540965E+09 | 2965.52 | 19-MAR-08:61 | -13.0 |
April | 0.438567E+09 | 2909.96 | 03-APR-08:61 | -4.8 |
May | 34915027.64 | 2646.62 | 02-MAY-08:62 | 3.35 |
June | 729109.06 | 1022.37 | 09-JUN-08:03 | 14.77 |
July | 594249.68 | 716.96 | 02-JUL-08:03 | 18.33 |
August | 884877.10 | 941.65 | 02-AUG-08:03 | 20.00 |
September | 14874844.99 | 2778.63 | 22-SEP-08:61 | 2.57 |
October | 0.374307E+09 | 2968.87 | 31-OCT-15:01 | -8.0 |
November | 0.502622E+09 | 2946.69 | 29-NOV-09:01 | -9.0 |
December | 0.106800E+10 | 2998.05 | 21-DEC-19:01 | -20.2 |
Annual Sum or Average | 0.428880E+10 | |||
Minimum of Months | 594249.68 | 716.96 | -20.2 | |
Maximum of Months | 0.106800E+10 | 2998.05 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.987415E+09 | 2965.45 | 05-JAN-09:01 | -17.0 |
February | 0.100418E+10 | 2948.22 | 05-FEB-16:01 | -6.2 |
March | 0.661969E+09 | 2954.21 | 19-MAR-08:61 | -13.0 |
April | 0.487067E+09 | 2899.33 | 03-APR-08:61 | -4.8 |
May | 39247696.50 | 2707.11 | 02-MAY-08:62 | 3.35 |
June | 687771.11 | 1051.09 | 09-JUN-08:03 | 14.77 |
July | 577183.60 | 591.04 | 20-JUL-08:03 | 16.33 |
August | 1054920.34 | 1062.75 | 14-AUG-08:03 | 22.67 |
September | 19814770.34 | 2777.52 | 22-SEP-08:61 | 2.57 |
October | 0.452879E+09 | 2957.30 | 31-OCT-15:01 | -8.0 |
November | 0.770332E+09 | 2937.98 | 29-NOV-09:01 | -9.0 |
December | 0.147924E+10 | 3005.05 | 21-DEC-19:01 | -20.2 |
Annual Sum or Average | 0.590446E+10 | |||
Minimum of Months | 577183.60 | 591.04 | -20.2 | |
Maximum of Months | 0.147924E+10 | 3005.05 | 22.67 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7877073.73 | 213.08 | 06-JAN-04:30 | -10.0 |
February | 48134032.87 | 282.97 | 07-FEB-03:00 | -8.0 |
March | 25834192.19 | 151.80 | 20-MAR-02:00 | -4.0 |
April | 10443215.90 | 168.88 | 17-APR-05:00 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 20530215.46 | 231.41 | 31-OCT-24:00 | -5.8 |
November | 14228550.30 | 252.48 | 01-NOV-02:70 | -4.2 |
December | 56552076.94 | 409.74 | 21-DEC-05:40 | -18.7 |
Annual Sum or Average | 0.183599E+09 | |||
Minimum of Months | 0.00 | 0.00 | -18.7 | |
Maximum of Months | 56552076.94 | 409.74 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183763E+09 | 866.49 | 05-JAN-16:01 | -15.2 |
February | 0.198516E+09 | 862.95 | 12-FEB-16:01 | -6.2 |
March | 86087147.03 | 856.33 | 04-MAR-16:01 | -9.0 |
April | 41705763.37 | 842.58 | 02-APR-15:01 | -4.0 |
May | 966831.08 | 370.05 | 14-MAY-15:04 | 18.33 |
June | 220383.64 | 302.89 | 28-JUN-08:04 | 20.37 |
July | 264939.33 | 413.84 | 14-JUL-08:04 | 23.17 |
August | 271387.83 | 363.66 | 30-AUG-15:04 | 28.00 |
September | 816078.94 | 449.81 | 22-SEP-08:61 | 2.57 |
October | 51279214.05 | 863.89 | 31-OCT-15:01 | -8.0 |
November | 0.123341E+09 | 863.77 | 29-NOV-16:01 | -9.3 |
December | 0.283315E+09 | 872.30 | 21-DEC-16:01 | -17.8 |
Annual Sum or Average | 0.970547E+09 | |||
Minimum of Months | 220383.64 | 302.89 | -17.8 | |
Maximum of Months | 0.283315E+09 | 872.30 | 28.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.631503E+09 | 2888.46 | 05-JAN-19:01 | -18.7 |
February | 0.753140E+09 | 2877.33 | 05-FEB-16:01 | -6.2 |
March | 0.534048E+09 | 2882.95 | 19-MAR-08:61 | -13.0 |
April | 0.425404E+09 | 2833.78 | 03-APR-08:61 | -4.8 |
May | 31299408.14 | 883.77 | 14-MAY-08:04 | 14.50 |
June | 60795.55 | 410.45 | 16-JUN-08:04 | 15.78 |
July | 124971.01 | 264.02 | 28-JUL-08:05 | 18.00 |
August | 117466.94 | 348.37 | 22-AUG-18:04 | 18.83 |
September | 12499788.00 | 2410.02 | 22-SEP-08:61 | 2.57 |
October | 0.377434E+09 | 2885.68 | 31-OCT-15:01 | -8.0 |
November | 0.536485E+09 | 2867.14 | 29-NOV-09:01 | -9.0 |
December | 0.108553E+10 | 2921.80 | 21-DEC-19:01 | -20.2 |
Annual Sum or Average | 0.438765E+10 | |||
Minimum of Months | 60795.55 | 264.02 | -20.2 | |
Maximum of Months | 0.108553E+10 | 2921.80 | 18.83 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101860E+10 | 2890.21 | 05-JAN-19:01 | -18.7 |
February | 0.103120E+10 | 2865.52 | 05-FEB-16:01 | -6.2 |
March | 0.641602E+09 | 2870.28 | 19-MAR-08:61 | -13.0 |
April | 0.475389E+09 | 2821.57 | 03-APR-08:61 | -4.8 |
May | 35272475.14 | 870.27 | 14-MAY-08:04 | 14.50 |
June | 71880.42 | 421.81 | 16-JUN-08:04 | 15.78 |
July | 148609.00 | 325.21 | 30-JUL-18:04 | 17.00 |
August | 167321.18 | 309.09 | 21-AUG-18:04 | 16.17 |
September | 16336993.59 | 2680.56 | 22-SEP-08:61 | 2.57 |
October | 0.457215E+09 | 2872.75 | 31-OCT-15:01 | -8.0 |
November | 0.816705E+09 | 2867.20 | 29-NOV-19:01 | -13.2 |
December | 0.148762E+10 | 2925.05 | 21-DEC-19:01 | -20.2 |
Annual Sum or Average | 0.598032E+10 | |||
Minimum of Months | 71880.42 | 309.09 | -20.2 | |
Maximum of Months | 0.148762E+10 | 2925.05 | 17.00 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 23784007.94 | 989.52 | 10-JAN-01:35 | 4.00 |
February | 74757738.22 | 843.31 | 05-FEB-16:00 | -6.0 |
March | 16680699.90 | 981.08 | 26-MAR-01:03 | 4.00 |
April | 14665800.31 | 991.27 | 06-APR-01:25 | 3.50 |
May | 3194283.23 | 993.49 | 02-MAY-21:44 | 2.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 21306.43 | 77.15 | 24-SEP-05:16 | 5.90 |
October | 37184677.54 | 916.33 | 26-OCT-02:20 | 3.20 |
November | 18652335.80 | 959.07 | 03-NOV-22:52 | 4.00 |
December | 0.162828E+09 | 1406.20 | 21-DEC-09:03 | -20.0 |
Annual Sum or Average | 0.351769E+09 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.162828E+09 | 1406.20 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102327E+10 | 3532.87 | 05-JAN-09:01 | -17.0 |
February | 0.111004E+10 | 3512.55 | 05-FEB-16:01 | -6.2 |
March | 0.872817E+09 | 3521.82 | 19-MAR-08:61 | -13.0 |
April | 0.732456E+09 | 3450.66 | 03-APR-08:61 | -4.8 |
May | 95788332.57 | 3224.92 | 02-MAY-08:62 | 3.35 |
June | 1080305.26 | 895.39 | 09-JUN-08:03 | 14.77 |
July | 1102482.65 | 1097.01 | 13-JUL-08:03 | 22.17 |
August | 1366548.65 | 1045.66 | 24-AUG-08:03 | 15.00 |
September | 39869526.75 | 3322.42 | 22-SEP-08:61 | 2.57 |
October | 0.652206E+09 | 3524.35 | 31-OCT-15:01 | -8.0 |
November | 0.859747E+09 | 3496.58 | 29-NOV-09:01 | -9.0 |
December | 0.160001E+10 | 3563.95 | 21-DEC-19:01 | -20.2 |
Annual Sum or Average | 0.698974E+10 | |||
Minimum of Months | 1080305.26 | 895.39 | -20.2 | |
Maximum of Months | 0.160001E+10 | 3563.95 | 22.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.156322E+10 | 3518.65 | 05-JAN-09:01 | -17.0 |
February | 0.150334E+10 | 3495.23 | 05-FEB-16:01 | -6.2 |
March | 0.105163E+10 | 3502.91 | 19-MAR-08:61 | -13.0 |
April | 0.807353E+09 | 3433.35 | 03-APR-08:61 | -4.8 |
May | 0.106212E+09 | 3214.85 | 02-MAY-08:62 | 3.35 |
June | 908360.01 | 927.40 | 09-JUN-08:03 | 14.77 |
July | 1040805.37 | 945.02 | 13-JUL-08:03 | 22.17 |
August | 1734690.37 | 1134.61 | 18-AUG-08:03 | 26.17 |
September | 52252307.28 | 3312.64 | 22-SEP-08:61 | 2.57 |
October | 0.808701E+09 | 3505.49 | 31-OCT-15:01 | -8.0 |
November | 0.125831E+10 | 3482.59 | 29-NOV-19:01 | -13.2 |
December | 0.212796E+10 | 3565.38 | 21-DEC-19:01 | -20.2 |
Annual Sum or Average | 0.928265E+10 | |||
Minimum of Months | 908360.01 | 927.40 | -20.2 | |
Maximum of Months | 0.212796E+10 | 3565.38 | 26.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210967E+09 | 1824.20 | 05-JAN-09:01 | -17.0 |
February | 0.323346E+09 | 1824.04 | 05-FEB-16:01 | -6.2 |
March | 0.290801E+09 | 1819.06 | 19-MAR-08:61 | -13.0 |
April | 0.260302E+09 | 1790.14 | 02-APR-15:01 | -4.0 |
May | 24805221.11 | 1664.38 | 02-MAY-08:62 | 3.35 |
June | 760133.78 | 538.15 | 09-JUN-08:03 | 14.77 |
July | 546680.42 | 377.67 | 15-JUL-08:04 | 26.50 |
August | 534298.16 | 494.92 | 14-AUG-08:03 | 22.67 |
September | 8111172.37 | 1713.00 | 22-SEP-08:61 | 2.57 |
October | 0.208480E+09 | 1830.31 | 31-OCT-15:01 | -8.0 |
November | 0.204618E+09 | 1810.17 | 29-NOV-09:01 | -9.0 |
December | 0.436724E+09 | 1834.59 | 21-DEC-09:02 | -20.0 |
Annual Sum or Average | 0.197000E+10 | |||
Minimum of Months | 534298.16 | 377.67 | -20.0 | |
Maximum of Months | 0.436724E+09 | 1834.59 | 26.50 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 42993333.10 | 8633.48 | 27-JAN-01:39 | 3.33 |
February | 13118314.56 | 5633.83 | 25-FEB-23:17 | 3.67 |
March | 31086783.24 | 8642.23 | 27-MAR-00:26 | 3.00 |
April | 30371611.88 | 8730.49 | 22-APR-00:40 | 3.33 |
May | 9653079.74 | 8203.01 | 02-MAY-21:44 | 2.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 81963.93 | 425.79 | 22-SEP-08:28 | 3.30 |
October | 37634512.94 | 9353.32 | 16-OCT-02:23 | 3.50 |
November | 39238151.44 | 9082.03 | 18-NOV-05:38 | 3.33 |
December | 34958925.91 | 8668.08 | 30-DEC-02:33 | 3.67 |
Annual Sum or Average | 0.239137E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.40 | |
Maximum of Months | 42993333.10 | 9353.32 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33367863.42 | 8713.09 | 19-JAN-01:33 | 4.00 |
February | 8302516.13 | 5688.00 | 27-FEB-05:53 | 4.00 |
March | 24769898.30 | 8757.46 | 09-MAR-04:18 | 3.33 |
April | 25667483.39 | 9001.74 | 01-APR-02:20 | 3.17 |
May | 8622762.19 | 8699.29 | 02-MAY-21:44 | 2.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 35593237.63 | 9626.27 | 19-OCT-02:14 | 3.33 |
November | 26183962.09 | 9517.13 | 18-NOV-05:38 | 3.33 |
December | 23553375.40 | 8911.25 | 30-DEC-02:33 | 3.67 |
Annual Sum or Average | 0.186061E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.40 | |
Maximum of Months | 35593237.63 | 9626.27 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4277634.36 | 5246.70 | 27-JAN-01:39 | 3.33 |
February | 745288.88 | 1987.19 | 27-FEB-05:25 | 4.50 |
March | 3444152.85 | 3979.75 | 09-MAR-02:27 | 4.00 |
April | 2625994.38 | 5552.26 | 22-APR-00:40 | 3.33 |
May | 1279164.85 | 4086.41 | 02-MAY-21:44 | 2.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 7669221.50 | 6633.34 | 16-OCT-02:23 | 3.50 |
November | 2869781.36 | 3754.53 | 03-NOV-22:52 | 4.00 |
December | 2776302.95 | 4654.01 | 03-DEC-02:46 | 4.83 |
Annual Sum or Average | 25687541.15 | |||
Minimum of Months | 0.00 | 0.00 | 2.40 | |
Maximum of Months | 7669221.50 | 6633.34 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.386369E+09 | 3041.47 | 05-JAN-09:03 | -17.0 |
February | 0.623065E+09 | 2787.37 | 12-FEB-05:40 | -19.3 |
March | 0.140955E+09 | 1700.31 | 05-MAR-06:00 | -12.0 |
April | 86414108.18 | 1622.33 | 25-APR-01:25 | 3.50 |
May | 5507518.71 | 1624.21 | 02-MAY-21:44 | 2.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 234428.52 | 305.12 | 22-SEP-08:28 | 3.30 |
October | 0.228795E+09 | 1985.61 | 31-OCT-14:00 | -7.0 |
November | 0.254400E+09 | 2425.96 | 30-NOV-07:10 | -11.3 |
December | 0.128549E+10 | 4460.12 | 23-DEC-07:20 | -22.2 |
Annual Sum or Average | 0.301123E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.2 | |
Maximum of Months | 0.128549E+10 | 4460.12 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.147273E+11 | 14185.34 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.132974E+11 | 14185.34 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.147727E+11 | 14185.34 | 01-MAR-20:10 | 0.127855E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.142280E+11 | 14185.34 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.147528E+11 | 14185.34 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.142932E+11 | 14185.34 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.146876E+11 | 14185.34 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.147784E+11 | 14185.34 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.142337E+11 | 14185.34 | 01-SEP-19:10 | 0.123352E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.147216E+11 | 14185.34 | 02-OCT-19:10 | 0.127549E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.142819E+11 | 14185.34 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.146876E+11 | 14185.34 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.173462E+12 | 0.150255E+12 | ||||
Minimum of Months | 0.132974E+11 | 14185.34 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.147784E+11 | 14185.34 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.731324E+09 | 704.41 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.660319E+09 | 704.41 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.733578E+09 | 704.41 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.706528E+09 | 704.41 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.732592E+09 | 704.41 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.709769E+09 | 704.41 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.729351E+09 | 704.41 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.733860E+09 | 704.41 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.706810E+09 | 704.41 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.731042E+09 | 704.41 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.709205E+09 | 704.41 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.729351E+09 | 704.41 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.861373E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.660319E+09 | 704.41 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.733860E+09 | 704.41 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.846876E+09 | 815.72 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.764651E+09 | 815.72 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.849486E+09 | 815.72 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.818162E+09 | 815.72 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.848344E+09 | 815.72 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.821915E+09 | 815.72 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.844592E+09 | 815.72 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.849812E+09 | 815.72 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.818489E+09 | 815.72 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.846549E+09 | 815.72 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.821262E+09 | 815.72 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.844592E+09 | 815.72 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.997473E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.764651E+09 | 815.72 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.849812E+09 | 815.72 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.141236E+10 | 1360.40 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.127524E+10 | 1360.40 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.141672E+10 | 1360.40 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.136448E+10 | 1360.40 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.141481E+10 | 1360.40 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.137074E+10 | 1360.40 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.140855E+10 | 1360.40 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.141726E+10 | 1360.40 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.136502E+10 | 1360.40 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.141182E+10 | 1360.40 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.136965E+10 | 1360.40 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.140855E+10 | 1360.40 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.166352E+11 | 0.124712E+11 | ||||
Minimum of Months | 0.127524E+10 | 1360.40 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.141726E+10 | 1360.40 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.236418E+09 | 227.72 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.213464E+09 | 227.72 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.237147E+09 | 227.72 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.228402E+09 | 227.72 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.236828E+09 | 227.72 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.229450E+09 | 227.72 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.235780E+09 | 227.72 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.237238E+09 | 227.72 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.228493E+09 | 227.72 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.236327E+09 | 227.72 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.229268E+09 | 227.72 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.235780E+09 | 227.72 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.278459E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.213464E+09 | 227.72 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.237238E+09 | 227.72 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.370859E+09 | 357.21 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.334852E+09 | 357.21 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.372002E+09 | 357.21 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.358285E+09 | 357.21 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.371502E+09 | 357.21 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.359929E+09 | 357.21 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.369859E+09 | 357.21 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.372145E+09 | 357.21 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.358428E+09 | 357.21 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.370717E+09 | 357.21 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.359643E+09 | 357.21 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.369859E+09 | 357.21 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.436808E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.334852E+09 | 357.21 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.372145E+09 | 357.21 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.160466E+10 | 1761.91 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.142730E+10 | 1761.91 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.154285E+10 | 1761.91 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.144687E+10 | 1761.91 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.144178E+10 | 1761.91 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.136605E+10 | 1761.91 | 01-JUN-19:19 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.141404E+10 | 1761.91 | 03-JUL-19:19 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.147818E+10 | 1761.91 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.146376E+10 | 1761.91 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.157867E+10 | 1761.91 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.154521E+10 | 1761.91 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.160856E+10 | 1761.91 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.179179E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.136605E+10 | 1761.91 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.160856E+10 | 1761.91 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104260E+11 | 10265.18 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.939169E+10 | 10265.18 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.103923E+11 | 10265.18 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.997333E+10 | 10265.18 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.102823E+11 | 10265.18 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.993044E+10 | 10265.18 | 01-JUN-19:19 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.102162E+11 | 10265.18 | 03-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.103333E+11 | 10265.18 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.999252E+10 | 10265.18 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.103979E+11 | 10265.18 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.100999E+11 | 10265.18 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.104062E+11 | 10265.18 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.121842E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.939169E+10 | 10265.18 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.104260E+11 | 10265.18 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85091918.49 | 76.99 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 76846309.13 | 76.99 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 84415649.14 | 76.99 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 82445007.08 | 76.99 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 84753783.81 | 76.99 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 81790910.76 | 76.99 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 85418966.65 | 76.99 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 84415649.14 | 76.99 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 82467180.11 | 76.99 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 85080831.98 | 76.99 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 82117958.92 | 76.99 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 85430053.17 | 76.99 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.100027E+10 | 0.300992E+10 | ||||
Minimum of Months | 76846309.13 | 76.99 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 85430053.17 | 76.99 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85115186.72 | 77.01 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 76867322.62 | 77.01 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 84438732.44 | 77.01 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 82467551.52 | 77.01 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 84776959.58 | 77.01 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 81813276.33 | 77.01 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 85442324.32 | 77.01 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 84438732.44 | 77.01 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 82489730.61 | 77.01 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 85104097.18 | 77.01 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 82140413.93 | 77.01 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 85453413.86 | 77.01 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.100055E+10 | 0.301074E+10 | ||||
Minimum of Months | 76867322.62 | 77.01 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 85453413.86 | 77.01 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.232638E+10 | 2240.78 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.210051E+10 | 2240.78 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.233355E+10 | 2240.78 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.224750E+10 | 2240.78 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.233041E+10 | 2240.78 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.225781E+10 | 2240.78 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.232011E+10 | 2240.78 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.233445E+10 | 2240.78 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.224840E+10 | 2240.78 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.232548E+10 | 2240.78 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.225602E+10 | 2240.78 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.232011E+10 | 2240.78 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.274007E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.210051E+10 | 2240.78 | 0.00 | 0.00 | |
Maximum of Months | 0.233445E+10 | 2240.78 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85115186.72 | 77.01 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 76867322.62 | 77.01 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 84438732.44 | 77.01 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 82467551.52 | 77.01 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 84776959.58 | 77.01 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 81813276.33 | 77.01 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 85442324.32 | 77.01 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 84438732.44 | 77.01 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 82489730.61 | 77.01 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 85104097.18 | 77.01 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 82140413.93 | 77.01 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 85453413.86 | 77.01 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.100055E+10 | 0.301074E+10 | ||||
Minimum of Months | 76867322.62 | 77.01 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 85453413.86 | 77.01 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.303489E+10 | 3094.06 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.270807E+10 | 3094.06 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.296733E+10 | 3094.06 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.281475E+10 | 3094.06 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.286054E+10 | 3094.06 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.273886E+10 | 3094.06 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.282578E+10 | 3094.06 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.289525E+10 | 3094.06 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.283654E+10 | 3094.06 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.299753E+10 | 3094.06 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.292394E+10 | 3094.06 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.302825E+10 | 3094.06 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.346317E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.270807E+10 | 3094.06 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.303489E+10 | 3094.06 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.303489E+10 | 3094.06 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.270807E+10 | 3094.06 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.296733E+10 | 3094.06 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.281475E+10 | 3094.06 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.286054E+10 | 3094.06 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.273886E+10 | 3094.06 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.282578E+10 | 3094.06 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.289525E+10 | 3094.06 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.283654E+10 | 3094.06 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.299753E+10 | 3094.06 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.292394E+10 | 3094.06 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.302825E+10 | 3094.06 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.346317E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.270807E+10 | 3094.06 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.303489E+10 | 3094.06 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113146E+10 | 1089.83 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.102161E+10 | 1089.83 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.113495E+10 | 1089.83 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.109310E+10 | 1089.83 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.113342E+10 | 1089.83 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.109811E+10 | 1089.83 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.112841E+10 | 1089.83 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.113539E+10 | 1089.83 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.109354E+10 | 1089.83 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.113103E+10 | 1089.83 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.109724E+10 | 1089.83 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.112841E+10 | 1089.83 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.133267E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.102161E+10 | 1089.83 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.113539E+10 | 1089.83 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.246211E+10 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.222306E+10 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.246970E+10 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.237864E+10 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.246638E+10 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.238954E+10 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.245547E+10 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.247065E+10 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.237958E+10 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.246116E+10 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.238765E+10 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.245547E+10 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.289994E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.222306E+10 | 2371.52 | 0.00 | 0.00 | |
Maximum of Months | 0.247065E+10 | 2371.52 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.147273E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.132974E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.147727E+11 | 0.127855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.142280E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.147528E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.142932E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.146876E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.147784E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.142337E+11 | 0.123352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.147216E+11 | 0.127549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.142819E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.146876E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.173462E+12 | 0.150255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.132974E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.147784E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.731324E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597851E+09 |
February | 0.179968E+10 | 0.660319E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.569676E+09 |
March | 0.199990E+10 | 0.733578E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481961E+09 |
April | 0.192973E+10 | 0.706528E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424337E+09 |
May | 0.199475E+10 | 0.732592E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2630714.67 | 0.250890E+09 |
June | 0.193394E+10 | 0.709769E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45860389.33 | 89821695.12 |
July | 0.199054E+10 | 0.729351E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48782997.02 | 80322629.62 |
August | 0.199896E+10 | 0.733860E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39257498.84 | 95947445.46 |
September | 0.192879E+10 | 0.706810E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19451765.06 | 0.153060E+09 |
October | 0.199148E+10 | 0.731042E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 395670.97 | 0.429221E+09 |
November | 0.192552E+10 | 0.709205E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520724E+09 |
December | 0.199054E+10 | 0.729351E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653753E+09 |
Annual Sum or Average | 0.234744E+11 | 0.861373E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156379E+09 | 0.434757E+10 |
Minimum of Months | 0.179968E+10 | 0.660319E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80322629.62 |
Maximum of Months | 0.199990E+10 | 0.733860E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48782997.02 | 0.653753E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.846876E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235185E+09 |
February | 0.208403E+10 | 0.764651E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222411E+09 |
March | 0.231589E+10 | 0.849486E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5452.28 | 0.190368E+09 |
April | 0.223463E+10 | 0.818162E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169967E+09 |
May | 0.230993E+10 | 0.848344E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1540289.27 | 0.101194E+09 |
June | 0.223950E+10 | 0.821915E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18765072.07 | 35945373.26 |
July | 0.230505E+10 | 0.844592E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19930966.24 | 32206925.74 |
August | 0.231480E+10 | 0.849812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16087730.35 | 38173749.32 |
September | 0.223354E+10 | 0.818489E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8079776.02 | 60939482.99 |
October | 0.230614E+10 | 0.846549E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 212262.88 | 0.170389E+09 |
November | 0.222975E+10 | 0.821262E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204895E+09 |
December | 0.230505E+10 | 0.844592E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255892E+09 |
Annual Sum or Average | 0.271834E+11 | 0.997473E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64621549.11 | 0.171757E+10 |
Minimum of Months | 0.208403E+10 | 0.764651E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32206925.74 |
Maximum of Months | 0.231589E+10 | 0.849812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19930966.24 | 0.255892E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.141236E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533740E+09 |
February | 0.440737E+09 | 0.127524E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506216E+09 |
March | 0.489771E+09 | 0.141672E+10 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14755.09 | 0.435077E+09 |
April | 0.472586E+09 | 0.136448E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391269E+09 |
May | 0.488511E+09 | 0.141481E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3207982.64 | 0.240210E+09 |
June | 0.473617E+09 | 0.137074E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41939350.47 | 86441986.46 |
July | 0.487480E+09 | 0.140855E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44560249.13 | 77435390.24 |
August | 0.489542E+09 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35945962.11 | 91766400.09 |
September | 0.472357E+09 | 0.136502E+10 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18028088.83 | 0.144610E+09 |
October | 0.487709E+09 | 0.141182E+10 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 499629.99 | 0.394983E+09 |
November | 0.471555E+09 | 0.136965E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467117E+09 |
December | 0.487480E+09 | 0.140855E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8172.01 | 0.586365E+09 |
Annual Sum or Average | 0.574883E+10 | 0.166352E+11 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144204E+09 | 0.395523E+10 |
Minimum of Months | 0.440737E+09 | 0.127524E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77435390.24 |
Maximum of Months | 0.489771E+09 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44560249.13 | 0.586365E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.236418E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297251E+09 |
February | 0.339028E+09 | 0.213464E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284427E+09 |
March | 0.376747E+09 | 0.237147E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 121875.19 | 0.239222E+09 |
April | 0.363528E+09 | 0.228402E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15337.66 | 0.212724E+09 |
May | 0.375778E+09 | 0.236828E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3376160.85 | 0.121386E+09 |
June | 0.364321E+09 | 0.229450E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29023644.06 | 42047835.79 |
July | 0.374985E+09 | 0.235780E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30462565.52 | 37447443.93 |
August | 0.376571E+09 | 0.237238E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25538787.95 | 43980853.14 |
September | 0.363352E+09 | 0.228493E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13905942.69 | 71647595.93 |
October | 0.375161E+09 | 0.236327E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 630254.23 | 0.212134E+09 |
November | 0.362735E+09 | 0.229268E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18348.36 | 0.256996E+09 |
December | 0.374985E+09 | 0.235780E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21546.90 | 0.330095E+09 |
Annual Sum or Average | 0.442217E+10 | 0.278459E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103114E+09 | 0.214936E+10 |
Minimum of Months | 0.339028E+09 | 0.213464E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37447443.93 |
Maximum of Months | 0.376747E+09 | 0.237238E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30462565.52 | 0.330095E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.370859E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803597E+09 |
February | 0.139600E+10 | 0.334852E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763859E+09 |
March | 0.155131E+10 | 0.372002E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658641E+09 |
April | 0.149688E+10 | 0.358285E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594059E+09 |
May | 0.154732E+10 | 0.371502E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 3267578.49 | 0.347388E+09 |
June | 0.150015E+10 | 0.359929E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 57086084.25 | 0.118426E+09 |
July | 0.154405E+10 | 0.369859E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 60729364.23 | 0.105995E+09 |
August | 0.155059E+10 | 0.372145E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 48886478.35 | 0.125770E+09 |
September | 0.149615E+10 | 0.358428E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 24230299.26 | 0.202020E+09 |
October | 0.154478E+10 | 0.370717E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 493505.60 | 0.581091E+09 |
November | 0.149361E+10 | 0.359643E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701668E+09 |
December | 0.154405E+10 | 0.369859E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882657E+09 |
Annual Sum or Average | 0.182090E+11 | 0.436808E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.194693E+09 | 0.588517E+10 |
Minimum of Months | 0.139600E+10 | 0.334852E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105995E+09 |
Maximum of Months | 0.155131E+10 | 0.372145E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 60729364.23 | 0.882657E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.160466E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134822E+10 |
February | 0.236489E+11 | 0.142730E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127859E+10 |
March | 0.262800E+11 | 0.154285E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108453E+10 |
April | 0.253579E+11 | 0.144687E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.953506E+09 |
May | 0.262123E+11 | 0.144178E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8592614.43 | 0.548482E+09 |
June | 0.254132E+11 | 0.136605E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112488E+09 | 0.191668E+09 |
July | 0.261570E+11 | 0.141404E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118982E+09 | 0.171648E+09 |
August | 0.262677E+11 | 0.147818E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91854731.99 | 0.206388E+09 |
September | 0.253456E+11 | 0.146376E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44720155.14 | 0.337414E+09 |
October | 0.261693E+11 | 0.157867E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 882761.08 | 0.964613E+09 |
November | 0.253025E+11 | 0.154521E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117204E+10 |
December | 0.261570E+11 | 0.160856E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146812E+10 |
Annual Sum or Average | 0.308468E+12 | 0.179179E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377521E+09 | 0.972522E+10 |
Minimum of Months | 0.236489E+11 | 0.136605E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171648E+09 |
Maximum of Months | 0.262800E+11 | 0.160856E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118982E+09 | 0.146812E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.104260E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394270E+10 |
February | 0.702046E+11 | 0.939169E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372642E+10 |
March | 0.780153E+11 | 0.103923E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5356.12 | 0.318765E+10 |
April | 0.752779E+11 | 0.997333E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284336E+10 |
May | 0.778146E+11 | 0.102823E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23473606.78 | 0.168605E+10 |
June | 0.754422E+11 | 0.993044E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308878E+09 | 0.587726E+09 |
July | 0.776503E+11 | 0.102162E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326726E+09 | 0.527783E+09 |
August | 0.779788E+11 | 0.103333E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259002E+09 | 0.625673E+09 |
September | 0.752414E+11 | 0.999252E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127030E+09 | 0.100829E+10 |
October | 0.776868E+11 | 0.103979E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2587851.27 | 0.284497E+10 |
November | 0.751137E+11 | 0.100999E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343819E+10 |
December | 0.776503E+11 | 0.104062E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428508E+10 |
Annual Sum or Average | 0.915726E+12 | 0.121842E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104770E+10 | 0.287039E+11 |
Minimum of Months | 0.702046E+11 | 0.939169E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527783E+09 |
Maximum of Months | 0.780153E+11 | 0.104260E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326726E+09 | 0.428508E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330733E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315613E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98248.24 | 0.262979E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233465E+09 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3288893.11 | 0.127159E+09 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37243091.50 | 33115540.07 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39913426.88 | 27166310.10 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32563679.36 | 34339741.95 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17149691.30 | 66314341.57 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 592849.81 | 0.229109E+09 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284897E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364689E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130850E+09 | 0.230958E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27166310.10 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39913426.88 | 0.364689E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323839E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310240E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 99305.91 | 0.259736E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231574E+09 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3352488.18 | 0.126537E+09 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37256026.45 | 33102515.03 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39944401.45 | 27153958.78 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32660324.91 | 34213097.33 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17292733.82 | 65672197.74 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 631028.24 | 0.226204E+09 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279630E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 702.17 | 0.359420E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131237E+09 | 0.227732E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27153958.78 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39944401.45 | 0.359420E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 85091918.49 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97301166.50 |
February | 0.00 | 76846309.13 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90679657.00 |
March | 0.00 | 84415649.14 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1647.00 | 75327096.33 |
April | 0.00 | 82445007.08 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65899968.88 |
May | 0.00 | 84753783.81 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 593977.78 | 40399469.17 |
June | 0.00 | 81790910.76 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8380892.45 | 13674239.55 |
July | 0.00 | 85418966.65 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8937895.13 | 12062814.26 |
August | 0.00 | 84415649.14 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7252190.67 | 14507547.12 |
September | 0.00 | 82467180.11 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3716560.89 | 23953704.72 |
October | 0.00 | 85080831.98 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 99052.15 | 68145965.22 |
November | 0.00 | 82117958.92 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83783549.89 |
December | 0.00 | 85430053.17 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104039E+09 |
Annual Sum or Average | 0.00 | 0.100027E+10 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28982216.07 | 0.689774E+09 |
Minimum of Months | 0.00 | 76846309.13 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12062814.26 |
Maximum of Months | 0.00 | 85430053.17 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8937895.13 | 0.104039E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 85115186.72 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 911.26 | 90338503.70 |
February | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86481251.33 |
March | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62743.34 | 72417843.50 |
April | 0.293479E+09 | 82467551.52 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 592.71 | 64727167.61 |
May | 0.303504E+09 | 84776959.58 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1124206.13 | 34790385.44 |
June | 0.293842E+09 | 81813276.33 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10725383.28 | 9083332.45 |
July | 0.303141E+09 | 85442324.32 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11447163.32 | 7454680.17 |
August | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9522367.59 | 9332075.15 |
September | 0.293479E+09 | 82489730.61 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5300558.31 | 18009373.70 |
October | 0.303322E+09 | 85104097.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 260408.58 | 62806301.21 |
November | 0.293661E+09 | 82140413.93 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12569.79 | 77816140.42 |
December | 0.303141E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17036.00 | 0.100465E+09 |
Annual Sum or Average | 0.357224E+10 | 0.100055E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38473940.32 | 0.633722E+09 |
Minimum of Months | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7454680.17 |
Maximum of Months | 0.303685E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11447163.32 | 0.100465E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331192E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316314E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98296.74 | 0.264265E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234882E+09 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3255681.97 | 0.128229E+09 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37147399.08 | 33478861.73 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39768386.47 | 27415227.60 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32506089.28 | 34806983.58 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17134476.99 | 66814079.79 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 592381.35 | 0.229755E+09 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285081E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364881E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130503E+09 | 0.231711E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27415227.60 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39768386.47 | 0.364881E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323230E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310652E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98523.83 | 0.261536E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233560E+09 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3260236.63 | 0.127855E+09 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37142114.88 | 33474098.53 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39769039.28 | 27405899.05 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32526530.55 | 34771714.59 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17176676.07 | 66556763.98 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 596493.68 | 0.227590E+09 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278859E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25017.97 | 0.358712E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130595E+09 | 0.228420E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27405899.05 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39769039.28 | 0.358712E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.232638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412392E+09 |
February | 0.348285E+10 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391689E+09 |
March | 0.387034E+10 | 0.233355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.98 | 0.335643E+09 |
April | 0.373454E+10 | 0.224750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297521E+09 |
May | 0.386038E+10 | 0.233041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2517503.01 | 0.181474E+09 |
June | 0.374269E+10 | 0.225781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32046820.20 | 66395451.41 |
July | 0.385223E+10 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34010247.13 | 59652678.93 |
August | 0.386853E+10 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27362491.03 | 70677903.79 |
September | 0.373273E+10 | 0.224840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13529129.22 | 0.111603E+09 |
October | 0.385404E+10 | 0.232548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269930.09 | 0.305978E+09 |
November | 0.372639E+10 | 0.225602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359816E+09 |
December | 0.385223E+10 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.93 | 0.448907E+09 |
Annual Sum or Average | 0.454292E+11 | 0.274007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109737E+09 | 0.304175E+10 |
Minimum of Months | 0.348285E+10 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59652678.93 |
Maximum of Months | 0.387034E+10 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34010247.13 | 0.448907E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330190E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315505E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92918.64 | 0.262945E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233403E+09 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204328.89 | 0.127460E+09 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36852078.72 | 33464830.21 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39499462.99 | 27499706.99 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32187443.33 | 34675789.95 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16905016.62 | 66566946.12 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 575168.07 | 0.229155E+09 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284726E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364321E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129316E+09 | 0.230991E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27499706.99 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39499462.99 | 0.364321E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323020E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309910E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93661.90 | 0.259534E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231474E+09 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3257854.08 | 0.126798E+09 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36857858.57 | 33451280.42 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39524562.29 | 27485275.89 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32278560.74 | 34550434.90 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17069215.21 | 65835617.13 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 628025.07 | 0.225766E+09 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279051E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4380.46 | 0.359098E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129714E+09 | 0.227597E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27485275.89 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39524562.29 | 0.359098E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 85115186.72 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171470E+09 |
February | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163465E+09 |
March | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46876.95 | 0.135917E+09 |
April | 0.293479E+09 | 82467551.52 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120427E+09 |
May | 0.303504E+09 | 84776959.58 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1637006.07 | 65403789.27 |
June | 0.293842E+09 | 81813276.33 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18887487.01 | 17087863.10 |
July | 0.303141E+09 | 85442324.32 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20217024.95 | 14049507.98 |
August | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16460418.71 | 17760717.83 |
September | 0.293479E+09 | 82489730.61 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8625344.48 | 34290029.55 |
October | 0.303322E+09 | 85104097.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 291148.58 | 0.118150E+09 |
November | 0.293661E+09 | 82140413.93 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147755E+09 |
December | 0.303141E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189627E+09 |
Annual Sum or Average | 0.357224E+10 | 0.100055E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66165306.75 | 0.119540E+10 |
Minimum of Months | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14049507.98 |
Maximum of Months | 0.303685E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20217024.95 | 0.189627E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.303489E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.861388E+09 |
February | 0.415303E+11 | 0.270807E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820832E+09 |
March | 0.461508E+11 | 0.296733E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153206.03 | 0.707666E+09 |
April | 0.445315E+11 | 0.281475E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639732E+09 |
May | 0.460320E+11 | 0.286054E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5522385.39 | 0.379916E+09 |
June | 0.446286E+11 | 0.273886E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70549323.09 | 0.132775E+09 |
July | 0.459349E+11 | 0.282578E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75473925.34 | 0.119349E+09 |
August | 0.461292E+11 | 0.289525E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62367934.19 | 0.139754E+09 |
September | 0.445099E+11 | 0.283654E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33742802.85 | 0.221845E+09 |
October | 0.459565E+11 | 0.299753E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1499068.92 | 0.626052E+09 |
November | 0.444343E+11 | 0.292394E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62889.26 | 0.752655E+09 |
December | 0.459349E+11 | 0.302825E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4751.65 | 0.945769E+09 |
Annual Sum or Average | 0.541708E+12 | 0.346317E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249376E+09 | 0.634773E+10 |
Minimum of Months | 0.415303E+11 | 0.270807E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119349E+09 |
Maximum of Months | 0.461508E+11 | 0.303489E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75473925.34 | 0.945769E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.303489E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876384E+09 |
February | 0.415303E+11 | 0.270807E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834721E+09 |
March | 0.461508E+11 | 0.296733E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96912.95 | 0.721293E+09 |
April | 0.445315E+11 | 0.281475E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652797E+09 |
May | 0.460320E+11 | 0.286054E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4585723.69 | 0.387357E+09 |
June | 0.446286E+11 | 0.273886E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67311347.92 | 0.134601E+09 |
July | 0.459349E+11 | 0.282578E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71955580.06 | 0.121064E+09 |
August | 0.461292E+11 | 0.289525E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59053099.34 | 0.142033E+09 |
September | 0.445099E+11 | 0.283654E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31270954.42 | 0.225704E+09 |
October | 0.459565E+11 | 0.299753E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1285263.12 | 0.637104E+09 |
November | 0.444343E+11 | 0.292394E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20671.14 | 0.766405E+09 |
December | 0.459349E+11 | 0.302825E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.960544E+09 |
Annual Sum or Average | 0.541708E+12 | 0.346317E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235580E+09 | 0.646001E+10 |
Minimum of Months | 0.415303E+11 | 0.270807E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121064E+09 |
Maximum of Months | 0.461508E+11 | 0.303489E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71955580.06 | 0.960544E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113146E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826324E+09 |
February | 0.369574E+10 | 0.102161E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.786066E+09 |
March | 0.410691E+10 | 0.113495E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677546E+09 |
April | 0.396281E+10 | 0.109310E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611088E+09 |
May | 0.409635E+10 | 0.113342E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3184551.32 | 0.358252E+09 |
June | 0.397146E+10 | 0.109811E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 57111595.24 | 0.122668E+09 |
July | 0.408770E+10 | 0.112841E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 60752047.25 | 0.110004E+09 |
August | 0.410499E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 48830576.45 | 0.130285E+09 |
September | 0.396089E+10 | 0.109354E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 24070804.62 | 0.208609E+09 |
October | 0.408962E+10 | 0.113103E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 469016.89 | 0.597731E+09 |
November | 0.395417E+10 | 0.109724E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722453E+09 |
December | 0.408770E+10 | 0.112841E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906662E+09 |
Annual Sum or Average | 0.482060E+11 | 0.133267E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.194419E+09 | 0.605769E+10 |
Minimum of Months | 0.369574E+10 | 0.102161E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110004E+09 |
Maximum of Months | 0.410691E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 60752047.25 | 0.906662E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.246211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725059E+09 |
February | 0.368610E+10 | 0.222306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693632E+09 |
March | 0.409620E+10 | 0.246970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593451E+09 |
April | 0.395248E+10 | 0.237864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532444E+09 |
May | 0.408566E+10 | 0.246638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3106187.15 | 0.331049E+09 |
June | 0.396110E+10 | 0.238954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55778581.07 | 0.119191E+09 |
July | 0.407704E+10 | 0.245547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59344070.79 | 0.107043E+09 |
August | 0.409429E+10 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47694888.39 | 0.126509E+09 |
September | 0.395056E+10 | 0.237958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23481344.66 | 0.197565E+09 |
October | 0.407896E+10 | 0.246116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453658.45 | 0.537757E+09 |
November | 0.394385E+10 | 0.238765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635510E+09 |
December | 0.407704E+10 | 0.245547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795367E+09 |
Annual Sum or Average | 0.480803E+11 | 0.289994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189859E+09 | 0.539458E+10 |
Minimum of Months | 0.368610E+10 | 0.222306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107043E+09 |
Maximum of Months | 0.409620E+10 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59344070.79 | 0.795367E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 14185.34 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 14185.34 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 14185.34 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 14185.34 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 14185.34 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 14185.34 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 14185.34 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 14185.34 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 14185.34 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 14185.34 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 14185.34 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 14185.34 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 14185.34 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 14185.34 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 704.41 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 439.30 | 05-JAN-19:00 |
February | 1169.53 | 01-FEB-00:10 | 704.41 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 458.71 | 12-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 704.41 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 400.60 | 19-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 704.41 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 311.40 | 17-APR-03:00 |
May | 1169.53 | 01-MAY-00:10 | 704.41 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.27 | 17-MAY-13:00 | 229.13 | 03-MAY-02:00 |
June | 1169.53 | 01-JUN-00:10 | 704.41 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.30 | 26-JUN-15:00 | 165.23 | 09-JUN-04:37 |
July | 1169.53 | 01-JUL-00:10 | 704.41 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.77 | 16-JUL-13:00 | 136.01 | 02-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 704.41 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.11 | 16-AUG-16:00 | 127.64 | 12-AUG-23:00 |
September | 1169.53 | 01-SEP-00:10 | 704.41 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.65 | 09-SEP-13:00 | 238.74 | 22-SEP-05:00 |
October | 1169.53 | 01-OCT-23:10 | 704.41 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.38 | 11-OCT-14:00 | 334.19 | 30-OCT-06:50 |
November | 1169.53 | 01-NOV-00:10 | 704.41 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 392.16 | 29-NOV-21:00 |
December | 1169.53 | 01-DEC-00:10 | 704.41 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 496.34 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 704.41 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.64 | |||||
Maximum of Months | 1169.53 | 704.41 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 141.30 | 496.34 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 815.72 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 170.06 | 05-JAN-19:00 |
February | 1354.32 | 01-FEB-00:10 | 815.72 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 179.34 | 12-FEB-05:00 |
March | 1354.32 | 01-MAR-00:10 | 815.72 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.81 | 14-MAR-13:00 | 156.32 | 19-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 815.72 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 122.33 | 17-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 815.72 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 17-MAY-13:00 | 95.17 | 03-MAY-02:00 |
June | 1354.32 | 01-JUN-00:10 | 815.72 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.73 | 26-JUN-15:00 | 68.96 | 09-JUN-04:37 |
July | 1354.32 | 01-JUL-00:10 | 815.72 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.45 | 16-JUL-13:00 | 57.06 | 02-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 815.72 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.36 | 16-AUG-16:00 | 50.57 | 12-AUG-24:00 |
September | 1354.32 | 01-SEP-00:10 | 815.72 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.35 | 10-SEP-13:00 | 100.01 | 22-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 815.72 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.91 | 11-OCT-14:00 | 131.84 | 30-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 815.72 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 156.00 | 29-NOV-21:00 |
December | 1354.32 | 01-DEC-00:10 | 815.72 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 191.59 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 815.72 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.57 | |||||
Maximum of Months | 1354.32 | 815.72 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 54.73 | 191.59 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 1360.40 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 400.73 | 05-JAN-19:00 |
February | 286.42 | 01-FEB-00:10 | 1360.40 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 418.45 | 12-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 1360.40 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 | 14-MAR-13:00 | 365.63 | 19-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 1360.40 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 284.05 | 17-APR-03:00 |
May | 286.42 | 01-MAY-00:10 | 1360.40 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.96 | 17-MAY-13:00 | 218.99 | 03-MAY-02:00 |
June | 286.42 | 01-JUN-00:10 | 1360.40 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.90 | 26-JUN-15:00 | 161.91 | 09-JUN-04:38 |
July | 286.42 | 01-JUL-00:10 | 1360.40 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.18 | 16-JUL-13:00 | 138.00 | 02-JUL-05:00 |
August | 286.42 | 01-AUG-00:10 | 1360.40 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.57 | 16-AUG-14:00 | 119.53 | 12-AUG-24:00 |
September | 286.42 | 01-SEP-00:10 | 1360.40 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.50 | 10-SEP-13:00 | 236.57 | 22-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 1360.40 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.17 | 11-OCT-14:00 | 306.15 | 30-OCT-06:40 |
November | 286.42 | 01-NOV-00:10 | 1360.40 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 360.21 | 29-NOV-21:00 |
December | 286.42 | 01-DEC-00:10 | 1360.40 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.40 | 01-DEC-14:00 | 452.79 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.53 | |||||
Maximum of Months | 286.42 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 128.90 | 452.79 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 227.72 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 231.20 | 05-JAN-19:00 |
February | 220.32 | 01-FEB-00:10 | 227.72 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 241.43 | 12-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 227.72 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.34 | 14-MAR-13:00 | 210.84 | 19-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 227.72 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.23 | 19-APR-13:00 | 163.89 | 17-APR-03:00 |
May | 220.32 | 01-MAY-00:10 | 227.72 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.25 | 17-MAY-13:00 | 120.58 | 03-MAY-02:00 |
June | 220.32 | 01-JUN-00:10 | 227.72 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.60 | 26-JUN-15:00 | 87.33 | 09-JUN-04:38 |
July | 220.32 | 01-JUL-00:10 | 227.72 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.54 | 16-JUL-13:00 | 73.56 | 02-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 227.72 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.13 | 16-AUG-16:00 | 63.78 | 12-AUG-23:00 |
September | 220.32 | 01-SEP-00:10 | 227.72 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.50 | 09-SEP-13:00 | 128.86 | 22-SEP-05:30 |
October | 220.32 | 01-OCT-23:10 | 227.72 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.35 | 11-OCT-14:00 | 175.88 | 30-OCT-08:00 |
November | 220.32 | 01-NOV-00:10 | 227.72 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 06-NOV-13:00 | 206.39 | 29-NOV-21:00 |
December | 220.32 | 01-DEC-00:10 | 227.72 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 | 01-DEC-14:00 | 261.24 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 227.72 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.78 | |||||
Maximum of Months | 220.32 | 227.72 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 77.60 | 261.24 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 357.21 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 588.21 | 05-JAN-19:00 |
February | 907.20 | 01-FEB-00:10 | 357.21 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 613.17 | 12-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 357.21 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 539.84 | 19-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 357.21 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 427.95 | 17-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 357.21 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 58.88 | 17-MAY-13:00 | 346.91 | 02-MAY-22:15 |
June | 907.20 | 01-JUN-00:10 | 357.21 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 176.01 | 26-JUN-15:00 | 241.50 | 09-JUN-04:37 |
July | 907.20 | 01-JUL-00:10 | 357.21 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 150.44 | 16-JUL-13:00 | 189.28 | 04-JUL-03:55 |
August | 907.20 | 01-AUG-00:10 | 357.21 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 149.61 | 16-AUG-16:00 | 163.22 | 12-AUG-24:00 |
September | 907.20 | 01-SEP-00:10 | 357.21 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 101.72 | 10-SEP-13:00 | 338.06 | 21-SEP-21:25 |
October | 907.20 | 01-OCT-23:10 | 357.21 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 35.36 | 11-OCT-14:00 | 456.51 | 30-OCT-07:30 |
November | 907.20 | 01-NOV-00:10 | 357.21 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 529.16 | 29-NOV-21:00 |
December | 907.20 | 01-DEC-00:10 | 357.21 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 647.15 | 23-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 163.22 | ||||||
Maximum of Months | 907.20 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 176.01 | 647.15 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1761.91 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 971.02 | 05-JAN-19:00 |
February | 15368.40 | 01-FEB-00:10 | 1761.91 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1014.09 | 12-FEB-05:00 |
March | 15368.40 | 01-MAR-00:10 | 1761.91 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 885.53 | 19-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1761.91 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 691.47 | 17-APR-03:00 |
May | 15368.40 | 01-MAY-00:10 | 1761.91 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.08 | 17-MAY-13:00 | 536.31 | 03-MAY-02:00 |
June | 15368.40 | 01-JUN-00:10 | 1761.91 | 01-JUN-19:19 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 312.38 | 26-JUN-15:00 | 391.74 | 09-JUN-04:37 |
July | 15368.40 | 01-JUL-00:10 | 1761.91 | 03-JUL-19:19 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 274.96 | 16-JUL-13:00 | 298.34 | 02-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 1761.91 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.55 | 16-AUG-16:00 | 276.94 | 12-AUG-23:00 |
September | 15368.40 | 01-SEP-00:10 | 1761.91 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.54 | 10-SEP-13:00 | 558.19 | 22-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 1761.91 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.78 | 11-OCT-14:00 | 742.04 | 30-OCT-04:30 |
November | 15368.40 | 01-NOV-00:10 | 1761.91 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 866.88 | 29-NOV-21:00 |
December | 15368.40 | 01-DEC-00:10 | 1761.91 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1097.28 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1761.91 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.94 | |||||
Maximum of Months | 15368.40 | 1761.91 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 312.38 | 1097.28 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 10265.18 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2807.23 | 05-JAN-19:10 |
February | 45622.98 | 01-FEB-00:10 | 10265.18 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2970.88 | 12-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 10265.18 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.93 | 14-MAR-13:00 | 2599.33 | 19-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 10265.18 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2064.10 | 17-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 10265.18 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.94 | 17-MAY-13:00 | 1604.04 | 03-MAY-02:00 |
June | 45622.98 | 01-JUN-00:10 | 10265.18 | 01-JUN-19:19 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 897.54 | 26-JUN-15:00 | 1134.21 | 09-JUN-04:15 |
July | 45622.98 | 01-JUL-00:10 | 10265.18 | 03-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 783.42 | 16-JUL-13:00 | 936.71 | 02-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 10265.18 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 758.65 | 16-AUG-16:00 | 827.48 | 12-AUG-24:00 |
September | 45622.98 | 01-SEP-00:10 | 10265.18 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 515.80 | 10-SEP-13:00 | 1683.15 | 22-SEP-05:00 |
October | 45622.98 | 01-OCT-23:10 | 10265.18 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.44 | 11-OCT-14:00 | 2217.86 | 30-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 10265.18 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2581.20 | 29-NOV-21:00 |
December | 45622.98 | 01-DEC-00:10 | 10265.18 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3169.88 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 10265.18 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 827.48 | |||||
Maximum of Months | 45622.98 | 10265.18 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 897.54 | 3169.88 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 253.54 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 267.23 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 13-MAR-16:00 | 233.46 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 181.68 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 | 31-MAY-15:10 | 133.90 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 26-JUN-15:10 | 86.23 | 09-JUN-04:43 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.46 | 16-JUL-15:07 | 71.21 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.98 | 16-AUG-16:00 | 59.40 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 10-SEP-16:00 | 139.49 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.91 | 11-OCT-15:10 | 194.91 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 228.57 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 289.09 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.40 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 289.09 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 253.52 | 05-JAN-19:07 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 267.21 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 13-MAR-15:07 | 233.45 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 181.67 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 | 31-MAY-15:10 | 133.89 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 26-JUN-15:10 | 86.23 | 09-JUN-04:50 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.45 | 16-JUL-15:07 | 71.21 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.97 | 16-AUG-16:00 | 59.40 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 10-SEP-16:00 | 139.48 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.91 | 11-OCT-15:10 | 194.89 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 228.56 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 | 01-DEC-12:40 | 289.06 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.40 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 289.06 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 76.99 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 67.46 | 05-JAN-19:00 |
February | 0.00 | 01-FEB-00:10 | 76.99 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 71.34 | 12-FEB-05:00 |
March | 0.00 | 01-MAR-00:10 | 76.99 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 | 14-MAR-13:00 | 61.20 | 19-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 76.99 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 46.83 | 17-APR-03:00 |
May | 0.00 | 01-MAY-00:10 | 76.99 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.61 | 17-MAY-13:00 | 35.36 | 03-MAY-02:00 |
June | 0.00 | 01-JUN-00:10 | 76.99 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.81 | 26-JUN-15:00 | 26.80 | 09-JUN-04:00 |
July | 0.00 | 01-JUL-00:10 | 76.99 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 16-JUL-13:00 | 22.95 | 02-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 76.99 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 | 16-AUG-16:00 | 20.20 | 12-AUG-24:00 |
September | 0.00 | 01-SEP-00:10 | 76.99 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 10-SEP-13:00 | 39.73 | 21-SEP-22:00 |
October | 0.00 | 01-OCT-00:10 | 76.99 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.56 | 11-OCT-14:00 | 50.84 | 30-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 76.99 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 60.45 | 29-NOV-21:00 |
December | 0.00 | 01-DEC-00:10 | 76.99 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 76.60 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 76.99 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.20 | |||||
Maximum of Months | 0.00 | 76.99 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 23.81 | 76.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 77.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 20-JAN-13:00 | 70.76 | 05-JAN-19:09 |
February | 180.00 | 01-FEB-00:10 | 77.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 74.58 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 77.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.42 | 14-MAR-13:00 | 65.16 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 77.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 | 19-APR-13:00 | 50.71 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 77.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 | 31-MAY-15:08 | 37.37 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 77.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.98 | 26-JUN-15:07 | 24.07 | 09-JUN-04:40 |
July | 180.00 | 01-JUL-00:10 | 77.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.18 | 16-JUL-15:10 | 19.87 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 77.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.72 | 16-AUG-16:00 | 16.58 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 77.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 | 10-SEP-16:00 | 38.93 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 77.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.36 | 11-OCT-14:00 | 54.40 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 77.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 06-NOV-13:00 | 63.79 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 77.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 | 01-DEC-14:00 | 80.68 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.58 | |||||
Maximum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 26.98 | 80.68 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 253.54 | 05-JAN-19:07 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 267.23 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 13-MAR-15:07 | 233.47 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 181.68 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.95 | 31-MAY-15:10 | 133.90 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 26-JUN-15:07 | 86.23 | 09-JUN-04:43 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.46 | 16-JUL-15:09 | 71.21 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.98 | 16-AUG-16:00 | 63.31 | 13-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 10-SEP-16:00 | 139.49 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.91 | 11-OCT-15:07 | 194.91 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 228.57 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 289.08 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.31 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 289.08 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 253.52 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 267.22 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 13-MAR-16:00 | 233.45 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 181.67 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 | 31-MAY-15:10 | 133.89 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 26-JUN-15:07 | 86.23 | 09-JUN-04:43 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.45 | 16-JUL-15:09 | 71.21 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.97 | 16-AUG-16:00 | 63.31 | 13-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 10-SEP-16:00 | 139.48 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.91 | 11-OCT-15:10 | 194.89 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 228.55 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.71 | 01-DEC-14:00 | 289.06 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.31 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 289.06 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 2240.78 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 308.64 | 05-JAN-19:00 |
February | 2263.36 | 01-FEB-00:10 | 2240.78 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 322.28 | 12-FEB-05:00 |
March | 2263.36 | 01-MAR-00:10 | 2240.78 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 | 14-MAR-13:00 | 282.86 | 19-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 2240.78 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 218.86 | 17-APR-03:00 |
May | 2263.36 | 01-MAY-00:10 | 2240.78 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.63 | 17-MAY-13:00 | 167.23 | 03-MAY-02:00 |
June | 2263.36 | 01-JUN-00:10 | 2240.78 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.90 | 26-JUN-15:00 | 124.07 | 09-JUN-04:38 |
July | 2263.36 | 01-JUL-00:10 | 2240.78 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.49 | 16-JUL-13:00 | 104.65 | 02-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 2240.78 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.02 | 16-AUG-16:00 | 92.25 | 12-AUG-23:00 |
September | 2263.36 | 01-SEP-00:10 | 2240.78 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.03 | 10-SEP-13:00 | 182.16 | 22-SEP-05:00 |
October | 2263.36 | 01-OCT-23:10 | 2240.78 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.64 | 11-OCT-14:00 | 234.86 | 30-OCT-06:20 |
November | 2263.36 | 01-NOV-00:10 | 2240.78 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 275.55 | 29-NOV-21:00 |
December | 2263.36 | 01-DEC-00:10 | 2240.78 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 | 01-DEC-14:00 | 348.69 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.25 | ||||
Maximum of Months | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.90 | 348.69 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 253.98 | 05-JAN-19:07 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 267.68 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 13-MAR-16:00 | 233.90 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 182.10 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.62 | 31-MAY-15:10 | 134.29 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.38 | 26-JUN-15:10 | 86.60 | 09-JUN-04:43 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.15 | 16-JUL-15:09 | 71.57 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.67 | 16-AUG-16:00 | 59.76 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.82 | 10-SEP-16:00 | 139.89 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.58 | 11-OCT-15:10 | 195.32 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 229.00 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 289.54 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.76 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 96.38 | 289.54 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 253.96 | 05-JAN-19:09 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 267.66 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 13-MAR-15:07 | 233.88 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 182.08 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.62 | 31-MAY-15:10 | 134.28 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.37 | 26-JUN-15:10 | 86.60 | 09-JUN-04:43 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.15 | 16-JUL-15:09 | 71.57 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.67 | 16-AUG-16:00 | 59.76 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.82 | 10-SEP-16:00 | 139.88 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.58 | 11-OCT-15:09 | 195.31 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 228.98 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.30 | 01-DEC-12:40 | 289.52 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.76 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 96.37 | 289.52 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 77.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 129.95 | 05-JAN-19:07 |
February | 180.00 | 01-FEB-00:10 | 77.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 136.96 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 77.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 | 13-MAR-16:00 | 119.67 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 77.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 93.17 | 17-APR-03:00 |
May | 180.00 | 01-MAY-00:10 | 77.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.25 | 31-MAY-15:08 | 68.71 | 03-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 77.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.31 | 26-JUN-15:10 | 44.31 | 09-JUN-04:33 |
July | 180.00 | 01-JUL-00:10 | 77.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.50 | 16-JUL-15:10 | 36.62 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 77.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.32 | 16-AUG-16:00 | 30.58 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 77.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.61 | 10-SEP-16:00 | 71.57 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 77.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.58 | 11-OCT-15:10 | 99.93 | 30-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 77.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 117.16 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 77.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 148.14 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.58 | |||||
Maximum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 49.31 | 148.14 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3094.06 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 637.25 | 05-JAN-19:10 |
February | 26988.77 | 01-FEB-00:10 | 3094.06 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 667.13 | 12-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3094.06 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.80 | 14-MAR-13:00 | 594.00 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3094.06 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 470.19 | 17-APR-03:00 |
May | 26988.77 | 01-MAY-00:10 | 3094.06 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.83 | 17-MAY-13:00 | 361.82 | 03-MAY-02:00 |
June | 26988.77 | 01-JUN-00:10 | 3094.06 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.91 | 26-JUN-15:00 | 261.23 | 09-JUN-04:15 |
July | 26988.77 | 01-JUL-00:10 | 3094.06 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.70 | 16-JUL-13:00 | 203.53 | 02-JUL-05:10 |
August | 26988.77 | 01-AUG-00:10 | 3094.06 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.75 | 16-AUG-14:00 | 187.11 | 12-AUG-23:00 |
September | 26988.77 | 01-SEP-00:10 | 3094.06 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.29 | 10-SEP-13:00 | 376.54 | 22-SEP-05:00 |
October | 26988.77 | 01-OCT-23:10 | 3094.06 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.14 | 11-OCT-14:00 | 501.32 | 30-OCT-04:20 |
November | 26988.77 | 01-NOV-00:10 | 3094.06 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.36 | 07-NOV-14:00 | 580.58 | 29-NOV-21:20 |
December | 26988.77 | 01-DEC-00:10 | 3094.06 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 | 01-DEC-14:00 | 719.89 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.11 | |||||
Maximum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 201.91 | 719.89 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3094.06 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 643.45 | 05-JAN-19:10 |
February | 26988.77 | 01-FEB-00:10 | 3094.06 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 673.00 | 12-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3094.06 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.55 | 14-MAR-13:00 | 600.05 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3094.06 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 476.12 | 17-APR-03:00 |
May | 26988.77 | 01-MAY-00:10 | 3094.06 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.39 | 17-MAY-13:00 | 367.02 | 03-MAY-02:00 |
June | 26988.77 | 01-JUN-00:10 | 3094.06 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.99 | 26-JUN-15:00 | 261.34 | 09-JUN-04:15 |
July | 26988.77 | 01-JUL-00:10 | 3094.06 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.56 | 16-JUL-13:00 | 206.44 | 02-JUL-05:10 |
August | 26988.77 | 01-AUG-00:10 | 3094.06 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.73 | 16-AUG-14:00 | 187.13 | 12-AUG-23:30 |
September | 26988.77 | 01-SEP-00:10 | 3094.06 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.23 | 10-SEP-13:00 | 380.34 | 22-SEP-05:00 |
October | 26988.77 | 01-OCT-23:10 | 3094.06 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.53 | 11-OCT-14:00 | 506.89 | 30-OCT-04:20 |
November | 26988.77 | 01-NOV-00:10 | 3094.06 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.93 | 07-NOV-14:00 | 587.70 | 29-NOV-21:10 |
December | 26988.77 | 01-DEC-00:10 | 3094.06 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 724.88 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.13 | |||||
Maximum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 198.99 | 724.88 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1089.83 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 600.48 | 05-JAN-19:00 |
February | 2401.70 | 01-FEB-00:10 | 1089.83 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 626.01 | 12-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1089.83 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 551.25 | 19-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1089.83 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 437.34 | 17-APR-03:00 |
May | 2401.70 | 01-MAY-00:10 | 1089.83 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 58.91 | 17-MAY-13:00 | 349.74 | 02-MAY-22:15 |
June | 2401.70 | 01-JUN-00:10 | 1089.83 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 178.27 | 26-JUN-15:00 | 250.84 | 09-JUN-04:37 |
July | 2401.70 | 01-JUL-00:10 | 1089.83 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 152.21 | 16-JUL-13:00 | 193.38 | 02-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1089.83 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 151.42 | 16-AUG-16:00 | 167.54 | 12-AUG-24:00 |
September | 2401.70 | 01-SEP-00:10 | 1089.83 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 102.57 | 10-SEP-13:00 | 353.07 | 21-SEP-15:25 |
October | 2401.70 | 01-OCT-23:10 | 1089.83 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 34.96 | 11-OCT-14:00 | 466.43 | 30-OCT-07:06 |
November | 2401.70 | 01-NOV-00:10 | 1089.83 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 540.33 | 29-NOV-21:00 |
December | 2401.70 | 01-DEC-00:10 | 1089.83 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 660.64 | 23-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1089.83 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 167.54 | ||||||
Maximum of Months | 2401.70 | 1089.83 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 178.27 | 660.64 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 547.02 | 05-JAN-19:00 |
February | 2395.44 | 01-FEB-00:10 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 571.17 | 12-FEB-05:00 |
March | 2395.44 | 01-MAR-00:10 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 498.96 | 19-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 388.13 | 17-APR-03:00 |
May | 2395.44 | 01-MAY-00:10 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.51 | 17-MAY-13:00 | 292.06 | 03-MAY-02:00 |
June | 2395.44 | 01-JUN-00:10 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.34 | 26-JUN-15:00 | 217.13 | 09-JUN-04:38 |
July | 2395.44 | 01-JUL-00:10 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.83 | 16-JUL-13:00 | 182.24 | 02-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.00 | 16-AUG-16:00 | 164.01 | 12-AUG-23:10 |
September | 2395.44 | 01-SEP-00:10 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.24 | 10-SEP-13:00 | 311.17 | 22-SEP-05:00 |
October | 2395.44 | 01-OCT-23:10 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.06 | 11-OCT-14:00 | 416.44 | 30-OCT-06:40 |
November | 2395.44 | 01-NOV-00:10 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 488.47 | 29-NOV-21:00 |
December | 2395.44 | 01-DEC-00:10 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 617.96 | 22-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.01 | ||||
Maximum of Months | 2395.44 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.34 | 617.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 35920.29 | 21-JAN-23:52 | 89459.16 | 47285.09 | 42584.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 36821.62 | 22-FEB-22:09 | 115018.92 | 94570.17 | 74522.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 40044.28 | 02-MAR-21:35 | 40895.62 | 50437.18 | 38325.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35797.19 | 18-APR-04:43 | 34505.68 | 9456.84 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32370.12 | 02-MAY-21:45 | 115018.92 | 94570.17 | 74522.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19282.97 | 09-JUN-04:20 | 69011.35 | 18913.67 | 19162.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18506.86 | 28-JUL-21:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 21018.33 | 18-AUG-21:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35257.85 | 21-SEP-19:47 | 89459.16 | 141853.45 | 101138.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40717.16 | 03-OCT-23:55 | 46007.57 | 12609.11 | 12775.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 39464.11 | 12-NOV-21:26 | 102239.04 | 94570.17 | 74522.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 44597.29 | 03-DEC-02:34 | 89459.16 | 31522.79 | 31938.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 18506.86 | 10223.90 | 9456.84 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44597.29 | 115018.92 | 141853.45 | 101138.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6069.23 | 10-JAN-13:41 | 2339.06 | 1761.04 | 2273.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.05 |
February | 6009.77 | 15-FEB-13:22 | 1559.38 | 1174.02 | 1515.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.27 |
March | 5303.31 | 01-MAR-11:46 | 2598.96 | 1956.71 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.67 |
April | 3565.13 | 07-APR-12:30 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.99 |
May | 2693.36 | 05-MAY-13:00 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.52 |
June | 3281.01 | 26-JUN-12:40 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 115.19 | 0.00 |
July | 3543.04 | 23-JUL-12:00 | 389.84 | 234.80 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 75.42 | 0.00 |
August | 4302.19 | 31-AUG-12:40 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 57.04 | 0.00 |
September | 5202.43 | 28-SEP-12:50 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 60.64 | 0.00 |
October | 5216.48 | 10-OCT-12:40 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.93 |
November | 6980.31 | 23-NOV-11:06 | 3898.44 | 2348.05 | 2886.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.15 |
December | 5778.81 | 18-DEC-10:42 | 1559.38 | 1174.02 | 1515.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2693.36 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6980.31 | 3898.44 | 2348.05 | 2886.75 | 0.00 | 0.00 | 0.00 | 0.00 | 115.19 | 234.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3256.45 | 24-JAN-22:38 | 6771.60 | 2719.05 | 2925.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.05 |
February | 3250.62 | 27-FEB-22:15 | 10834.56 | 4350.48 | 4680.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.77 |
March | 3358.68 | 03-MAR-22:57 | 4062.96 | 1631.43 | 1755.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.38 |
April | 3327.69 | 09-APR-00:07 | 3160.08 | 815.72 | 1002.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.43 |
May | 3148.64 | 18-MAY-23:40 | 2708.64 | 362.54 | 501.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.93 |
June | 2333.61 | 26-JUN-20:10 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 29.08 | 0.00 |
July | 2227.12 | 17-JUL-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 18.30 | 0.00 |
August | 2326.41 | 16-AUG-20:10 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 | 0.00 |
September | 2416.56 | 21-SEP-20:08 | 10834.56 | 6525.72 | 6769.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.17 |
October | 3504.40 | 03-OCT-23:55 | 5417.28 | 725.08 | 1002.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.31 |
November | 3878.92 | 16-NOV-00:37 | 4062.96 | 543.81 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.04 |
December | 3425.11 | 05-DEC-02:53 | 4062.96 | 271.91 | 501.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2227.12 | 1203.84 | 271.91 | 501.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3878.92 | 10834.56 | 6525.72 | 6769.31 | 0.00 | 0.00 | 0.00 | 0.00 | 29.08 | 96.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1338.97 | 24-JAN-01:13 | 859.25 | 680.20 | 662.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.38 |
February | 1162.41 | 27-FEB-23:33 | 859.25 | 1360.40 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.07 |
March | 1157.29 | 09-MAR-02:33 | 2864.16 | 1511.55 | 1767.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.21 |
April | 1485.78 | 22-APR-00:43 | 859.25 | 906.93 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.10 |
May | 2186.55 | 18-MAY-23:30 | 1718.50 | 1813.86 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.08 |
June | 2291.69 | 26-JUN-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 74.14 | 0.00 |
July | 2285.05 | 17-JUL-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 51.72 | 0.00 |
August | 2171.69 | 16-AUG-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 43.07 | 0.00 |
September | 1967.25 | 12-SEP-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 |
October | 1489.19 | 12-OCT-02:59 | 2577.74 | 1360.40 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.81 |
November | 1301.72 | 17-NOV-00:23 | 859.25 | 906.93 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.74 |
December | 1355.01 | 05-DEC-02:53 | 859.25 | 453.47 | 530.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1157.29 | 222.77 | 453.47 | 530.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2291.69 | 2864.16 | 1813.86 | 1767.26 | 0.00 | 0.00 | 0.00 | 0.00 | 74.14 | 198.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1303.34 | 24-JAN-01:13 | 660.96 | 113.87 | 191.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.02 |
February | 1096.74 | 27-FEB-23:33 | 660.96 | 227.72 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.52 |
March | 1130.12 | 09-MAR-02:33 | 2203.20 | 253.02 | 509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.88 |
April | 1445.36 | 22-APR-00:43 | 660.96 | 151.81 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.66 |
May | 1396.37 | 19-MAY-01:37 | 1982.88 | 227.72 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.89 |
June | 1198.94 | 09-JUN-04:20 | 1321.92 | 303.62 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.54 |
July | 957.21 | 04-JUL-04:05 | 685.44 | 202.41 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.78 |
August | 894.21 | 20-AUG-10:35 | 146.88 | 151.81 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 0.00 |
September | 1136.94 | 16-SEP-03:15 | 881.28 | 101.21 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.10 |
October | 1457.95 | 12-OCT-02:59 | 1982.88 | 227.72 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.56 |
November | 1256.32 | 17-NOV-00:23 | 660.96 | 151.81 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.35 |
December | 1327.70 | 05-DEC-02:53 | 660.96 | 75.91 | 152.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 894.21 | 146.88 | 75.91 | 152.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1457.95 | 2203.20 | 303.62 | 509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 106.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 53267.59 | 10-JAN-20:27 | 5644.80 | 2857.71 | 36582.41 | 317812.61 | 0.00 | 0.00 | 0.00 | 0.00 | 320.24 |
February | 53215.39 | 23-FEB-21:28 | 4032.00 | 1587.62 | 21660.63 | 188178.52 | 0.00 | 0.00 | 0.00 | 0.00 | 314.97 |
March | 56250.62 | 29-MAR-20:41 | 8064.00 | 3175.23 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 358.87 |
April | 50320.52 | 14-APR-20:09 | 8064.00 | 3175.23 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 327.86 |
May | 51721.64 | 02-MAY-21:45 | 9072.00 | 2381.43 | 33694.32 | 292722.14 | 0.00 | 0.00 | 0.00 | 0.00 | 306.71 |
June | 39487.19 | 26-JUN-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 101.24 | 0.00 |
July | 39430.14 | 17-JUL-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 70.62 | 0.00 |
August | 39380.76 | 16-AUG-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 58.83 | 0.00 |
September | 51967.12 | 21-SEP-19:47 | 7056.00 | 3572.14 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 330.21 |
October | 51658.36 | 16-OCT-21:40 | 8164.80 | 2143.28 | 30324.89 | 263449.93 | 0.00 | 0.00 | 0.00 | 0.00 | 312.37 |
November | 51794.25 | 19-NOV-21:08 | 6451.20 | 1905.14 | 26955.46 | 234177.71 | 0.00 | 0.00 | 0.00 | 0.00 | 296.94 |
December | 51281.18 | 29-DEC-22:46 | 9072.00 | 2381.43 | 33694.32 | 292722.14 | 0.00 | 0.00 | 0.00 | 0.00 | 302.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 39380.76 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 56250.62 | 9072.00 | 3572.14 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 101.24 | 358.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23991.17 | 10-JAN-13:41 | 30736.80 | 2686.91 | 3200.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.65 |
February | 23023.73 | 16-FEB-14:20 | 10245.60 | 895.64 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.20 |
March | 24149.09 | 09-MAR-02:33 | 153684.00 | 1957.67 | 2032.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.46 |
April | 17582.43 | 09-APR-00:07 | 35859.60 | 1761.91 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.79 |
May | 16953.92 | 19-MAY-01:37 | 138315.60 | 1761.91 | 1828.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.76 |
June | 14448.76 | 09-JUN-04:20 | 92210.40 | 2349.21 | 1828.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.31 |
July | 12045.22 | 23-JUL-12:00 | 5122.80 | 358.25 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 166.74 | 0.00 |
August | 14257.20 | 26-AUG-12:40 | 5122.80 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 159.65 | 0.00 |
September | 16781.46 | 28-SEP-12:50 | 3415.20 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 134.29 | 0.00 |
October | 21297.84 | 12-OCT-02:06 | 153684.00 | 1957.67 | 2032.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.10 |
November | 26117.07 | 23-NOV-11:06 | 51228.00 | 3582.54 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.95 |
December | 23329.35 | 16-DEC-11:20 | 15368.40 | 895.64 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12045.22 | 3415.20 | 298.55 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26117.07 | 153684.00 | 3582.54 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 166.74 | 468.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 74159.77 | 25-JAN-22:54 | 364983.84 | 54747.65 | 59119.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1473.73 |
February | 68034.12 | 27-FEB-05:40 | 91245.96 | 4562.30 | 6334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1265.62 |
March | 68577.93 | 03-MAR-22:57 | 136868.94 | 20530.37 | 22169.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1576.63 |
April | 75983.73 | 01-APR-02:31 | 319360.86 | 7984.03 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1351.62 |
May | 68698.63 | 18-MAY-23:40 | 91245.96 | 4562.30 | 6334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1220.79 |
June | 55861.46 | 09-JUN-04:17 | 273737.88 | 13686.91 | 19002.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1122.35 |
July | 42761.40 | 17-JUL-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 269.87 | 0.00 |
August | 43304.12 | 16-AUG-20:10 | 40553.76 | 9124.61 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 268.91 | 0.00 |
September | 56854.57 | 21-SEP-20:19 | 405537.60 | 91246.08 | 95013.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1560.84 |
October | 71446.27 | 19-OCT-01:58 | 456229.80 | 11405.76 | 21114.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1267.24 |
November | 77129.77 | 17-NOV-00:23 | 136868.94 | 6843.46 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1269.69 |
December | 68006.23 | 14-DEC-22:32 | 456229.80 | 68434.56 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1494.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 42761.40 | 40553.76 | 4562.30 | 6334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 77129.77 | 456229.80 | 91246.08 | 95013.56 | 0.00 | 0.00 | 0.00 | 0.00 | 269.87 | 1576.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4237.15 | 23-JAN-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.45 |
February | 4189.01 | 26-FEB-16:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.97 |
March | 4511.35 | 13-MAR-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 | 0.00 |
April | 4390.55 | 07-APR-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.65 |
May | 4589.42 | 16-MAY-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 0.00 |
June | 4692.80 | 26-JUN-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 89.70 | 0.00 |
July | 4676.59 | 15-JUL-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 67.49 | 0.00 |
August | 4712.70 | 16-AUG-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 73.27 | 0.00 |
September | 4696.48 | 28-SEP-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 38.49 | 0.00 |
October | 4648.45 | 11-OCT-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 17.61 | 0.00 |
November | 4382.22 | 05-NOV-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.66 |
December | 4119.71 | 02-DEC-16:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4119.71 | 378.00 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4712.70 | 680.40 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 89.70 | 27.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4053.07 | 23-JAN-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.22 |
February | 4020.80 | 26-FEB-16:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.98 |
March | 4325.75 | 13-MAR-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 4.12 | 0.00 |
April | 4235.36 | 07-APR-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 |
May | 4472.98 | 16-MAY-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 26.71 | 0.00 |
June | 4579.12 | 26-JUN-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 89.66 | 0.00 |
July | 4575.68 | 01-JUL-18:01 | 819.00 | 857.43 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 28.53 | 0.00 |
August | 4576.24 | 16-AUG-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 73.56 | 0.00 |
September | 4541.28 | 10-SEP-15:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 50.83 | 0.00 |
October | 4469.96 | 11-OCT-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 18.57 | 0.00 |
November | 4177.10 | 05-NOV-15:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.18 |
December | 3955.40 | 02-DEC-16:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3955.40 | 378.00 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4579.12 | 819.00 | 857.43 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 89.66 | 26.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 944.64 | 20-JAN-12:40 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 |
February | 907.04 | 18-FEB-13:00 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 |
March | 838.39 | 14-MAR-12:40 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 |
April | 506.22 | 08-APR-13:10 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.64 |
May | 403.74 | 16-MAY-13:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 6.38 | 0.00 |
June | 521.21 | 14-JUN-13:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 17.24 | 0.00 |
July | 557.60 | 23-JUL-13:00 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 16.11 | 0.00 |
August | 691.52 | 31-AUG-12:50 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 10.20 | 0.00 |
September | 873.97 | 28-SEP-13:00 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 10.92 | 0.00 |
October | 900.43 | 10-OCT-12:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 0.00 |
November | 950.13 | 07-NOV-12:10 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 |
December | 844.81 | 17-DEC-13:30 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 403.74 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 950.13 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 17.24 | 11.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 989.65 | 21-JAN-09:01 | 378.00 | 301.88 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.28 |
February | 985.72 | 19-FEB-09:01 | 378.00 | 301.88 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.22 |
March | 1114.76 | 14-MAR-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 | 0.00 |
April | 1096.92 | 27-APR-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 |
May | 1252.71 | 17-MAY-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 6.51 | 0.00 |
June | 1271.31 | 26-JUN-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 24.55 | 0.00 |
July | 1273.63 | 16-JUL-15:01 | 378.00 | 177.90 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 19.66 | 0.00 |
August | 1266.76 | 18-AUG-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 0.00 |
September | 1266.29 | 11-SEP-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 9.96 | 0.00 |
October | 1164.68 | 11-OCT-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 6.12 | 0.00 |
November | 990.08 | 09-NOV-19:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.40 |
December | 795.62 | 02-DEC-09:01 | 378.00 | 301.88 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 795.62 | 378.00 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1273.63 | 831.60 | 411.24 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 24.55 | 26.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3655.05 | 23-JAN-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.81 |
February | 3676.88 | 24-FEB-09:01 | 360.00 | 539.02 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.39 |
March | 3895.90 | 13-MAR-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 | 0.00 |
April | 3789.56 | 07-APR-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 |
May | 4028.42 | 16-MAY-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 26.19 | 0.00 |
June | 4068.40 | 26-JUN-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 90.05 | 0.00 |
July | 4115.15 | 17-JUL-08:61 | 252.00 | 377.32 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 32.95 | 0.00 |
August | 4068.82 | 16-AUG-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 73.92 | 0.00 |
September | 4057.36 | 12-SEP-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 40.18 | 0.00 |
October | 4007.37 | 11-OCT-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 18.36 | 0.00 |
November | 3783.70 | 05-NOV-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.03 |
December | 3583.87 | 02-DEC-16:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3583.87 | 252.00 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4115.15 | 680.40 | 539.02 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 90.05 | 109.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3358.54 | 20-JAN-09:02 | 216.00 | 323.38 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.44 |
February | 3554.23 | 24-FEB-09:01 | 360.00 | 538.96 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.73 |
March | 3750.39 | 14-MAR-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 3.59 | 0.00 |
April | 3665.81 | 19-APR-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.43 |
May | 3929.77 | 16-MAY-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 26.25 | 0.00 |
June | 3972.60 | 26-JUN-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 90.04 | 0.00 |
July | 4028.45 | 17-JUL-08:61 | 252.00 | 377.27 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 32.77 | 0.00 |
August | 3953.29 | 16-AUG-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 74.24 | 0.00 |
September | 3938.14 | 06-SEP-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 47.83 | 0.00 |
October | 3848.86 | 11-OCT-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 19.46 | 0.00 |
November | 3453.47 | 17-NOV-09:01 | 252.00 | 377.27 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.30 |
December | 3296.44 | 02-DEC-09:01 | 378.00 | 480.16 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3296.44 | 216.00 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4028.45 | 680.40 | 538.96 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 90.04 | 108.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2896.22 | 24-JAN-01:13 | 6790.07 | 1120.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.82 |
February | 2485.00 | 27-FEB-23:33 | 6790.07 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.44 |
March | 2506.70 | 13-MAR-05:05 | 17603.88 | 9959.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.21 |
April | 3144.88 | 22-APR-00:43 | 6790.07 | 1493.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.84 |
May | 3086.47 | 19-MAY-01:37 | 20370.20 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.21 |
June | 3603.69 | 26-JUN-18:30 | 1760.39 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.45 | 0.00 |
July | 3245.92 | 15-JUL-18:30 | 1508.90 | 1742.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.98 | 0.00 |
August | 3344.48 | 11-AUG-18:30 | 1760.39 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.41 | 0.00 |
September | 3019.98 | 12-SEP-18:03 | 10562.33 | 11950.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.95 | 0.00 |
October | 3257.69 | 12-OCT-02:59 | 20370.20 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.95 |
November | 2829.28 | 17-NOV-00:23 | 6790.07 | 1493.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.80 |
December | 2876.28 | 05-DEC-02:53 | 6790.07 | 746.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2485.00 | 1508.90 | 746.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3603.69 | 20370.20 | 11950.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.45 | 151.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4483.91 | 23-JAN-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.60 |
February | 4419.86 | 26-FEB-16:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.93 |
March | 4776.46 | 13-MAR-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 2.81 | 0.00 |
April | 4642.58 | 07-APR-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.75 |
May | 4860.59 | 16-MAY-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 26.48 | 0.00 |
June | 4983.65 | 26-JUN-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 89.36 | 0.00 |
July | 4958.86 | 15-JUL-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 67.24 | 0.00 |
August | 5006.23 | 16-AUG-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 72.90 | 0.00 |
September | 4976.16 | 28-SEP-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 38.28 | 0.00 |
October | 4916.72 | 11-OCT-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 17.51 | 0.00 |
November | 4644.56 | 05-NOV-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.92 |
December | 4365.95 | 02-DEC-16:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4365.95 | 378.00 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5006.23 | 680.40 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 89.36 | 27.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4253.94 | 23-JAN-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.01 |
February | 4218.32 | 26-FEB-16:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.75 |
March | 4558.53 | 13-MAR-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 | 0.00 |
April | 4463.19 | 07-APR-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 |
May | 4726.10 | 16-MAY-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 | 0.00 |
June | 4851.98 | 26-JUN-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 89.31 | 0.00 |
July | 4839.17 | 01-JUL-18:01 | 819.00 | 857.43 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 28.28 | 0.00 |
August | 4848.89 | 16-AUG-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 73.20 | 0.00 |
September | 4797.82 | 10-SEP-15:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 50.66 | 0.00 |
October | 4706.55 | 11-OCT-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 18.61 | 0.00 |
November | 4397.72 | 07-NOV-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 |
December | 4163.82 | 02-DEC-16:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4163.82 | 378.00 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4851.98 | 819.00 | 857.43 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 89.31 | 26.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2236.34 | 23-JAN-16:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.26 |
February | 2191.50 | 18-FEB-16:01 | 378.00 | 177.90 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 |
March | 2364.99 | 13-MAR-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 0.00 |
April | 2272.45 | 07-APR-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.47 |
May | 2381.69 | 16-MAY-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 12.95 | 0.00 |
June | 2406.02 | 26-JUN-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 45.64 | 0.00 |
July | 2405.24 | 18-JUL-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 23.19 | 0.00 |
August | 2427.09 | 16-AUG-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 37.08 | 0.00 |
September | 2445.97 | 28-SEP-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 18.87 | 0.00 |
October | 2428.31 | 11-OCT-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 8.09 | 0.00 |
November | 2326.40 | 05-NOV-15:01 | 378.00 | 177.90 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.38 |
December | 2184.01 | 02-DEC-16:01 | 378.00 | 177.90 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2184.01 | 378.00 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2445.97 | 680.40 | 177.90 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 45.64 | 15.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 32363.12 | 25-JAN-22:54 | 215910.14 | 16501.63 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.82 |
February | 32505.42 | 21-FEB-23:44 | 134943.84 | 5156.76 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.33 |
March | 36563.14 | 17-MAR-22:09 | 215910.14 | 8250.81 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.88 |
April | 34812.03 | 01-APR-02:31 | 188921.38 | 2406.49 | 15745.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.19 |
May | 32832.12 | 12-MAY-01:37 | 80966.30 | 1031.35 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.77 |
June | 30350.87 | 09-JUN-04:17 | 161932.61 | 4125.41 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.83 |
July | 23066.27 | 17-JUL-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 52.52 | 0.00 |
August | 22699.91 | 16-AUG-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 0.00 |
September | 30717.25 | 21-SEP-21:19 | 269887.68 | 20627.04 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.09 |
October | 31918.69 | 16-OCT-22:45 | 107955.07 | 4125.41 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.62 |
November | 38227.68 | 16-NOV-01:01 | 188921.38 | 3609.73 | 15745.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.98 |
December | 32297.87 | 26-DEC-23:57 | 80966.30 | 3094.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22699.91 | 26988.77 | 1031.35 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38227.68 | 269887.68 | 20627.04 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 52.52 | 351.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37969.90 | 25-JAN-22:54 | 215910.14 | 16501.63 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.23 |
February | 34113.51 | 28-FEB-22:52 | 134943.84 | 10313.52 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 354.07 |
March | 40085.79 | 17-MAR-22:09 | 215910.14 | 8250.81 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.02 |
April | 38030.62 | 01-APR-02:31 | 188921.38 | 2406.49 | 15745.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.46 |
May | 34505.88 | 12-MAY-01:37 | 80966.30 | 1031.35 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.32 |
June | 31764.86 | 09-JUN-04:38 | 161932.61 | 3850.38 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.21 |
July | 24488.54 | 17-JUL-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 52.38 | 0.00 |
August | 24099.39 | 16-AUG-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | 0.00 |
September | 32348.45 | 21-SEP-21:19 | 269887.68 | 20627.04 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.98 |
October | 34104.44 | 26-OCT-01:15 | 269887.68 | 3437.84 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.97 |
November | 37401.07 | 17-NOV-00:23 | 80966.30 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.96 |
December | 34235.62 | 26-DEC-23:57 | 80966.30 | 3094.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24099.39 | 26988.77 | 1031.35 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40085.79 | 269887.68 | 20627.04 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 52.38 | 354.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37472.95 | 10-JAN-13:41 | 4803.41 | 2724.58 | 134215.70 | 134956.99 | 0.00 | 0.00 | 0.00 | 0.00 | 260.53 |
February | 39235.65 | 23-FEB-18:01 | 12008.52 | 6538.99 | 134215.70 | 202435.49 | 0.00 | 0.00 | 0.00 | 0.00 | 291.25 |
March | 36225.33 | 05-MAR-18:41 | 7471.97 | 4238.23 | 104389.99 | 157449.82 | 0.00 | 0.00 | 0.00 | 0.00 | 305.66 |
April | 35886.03 | 09-APR-22:38 | 21348.48 | 3632.77 | 149128.56 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 265.89 |
May | 34630.54 | 02-MAY-21:45 | 24017.04 | 7265.54 | 149128.56 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 306.88 |
June | 31385.31 | 26-JUN-10:40 | 1067.42 | 605.46 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 101.85 | 0.00 |
July | 31640.96 | 23-JUL-10:50 | 800.57 | 363.28 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 67.82 | 0.00 |
August | 31717.44 | 05-AUG-10:40 | 1601.14 | 605.46 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 58.07 | 0.00 |
September | 35828.35 | 21-SEP-16:16 | 13342.80 | 3027.31 | 149128.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 331.32 |
October | 36330.22 | 21-OCT-07:41 | 13342.80 | 4843.69 | 149128.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 298.08 |
November | 42885.36 | 23-NOV-11:06 | 8005.68 | 3632.77 | 149128.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 0.00 | 275.88 |
December | 36907.97 | 16-DEC-09:03 | 5603.98 | 3390.59 | 104389.99 | 78724.91 | 0.00 | 0.00 | 0.00 | 0.00 | 318.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 31385.31 | 800.57 | 363.28 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42885.36 | 24017.04 | 7265.54 | 149128.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 101.85 | 331.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4606.36 | 24-JAN-01:13 | 7186.32 | 1185.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.48 |
February | 3956.66 | 27-FEB-23:33 | 7186.32 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.17 |
March | 5741.15 | 15-MAR-13:30 | 532.32 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.13 |
April | 5154.72 | 22-APR-00:43 | 7186.32 | 1581.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.12 |
May | 4998.42 | 31-MAY-15:03 | 7984.80 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.21 | 0.00 |
June | 7334.85 | 26-JUN-14:10 | 798.48 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.92 | 0.00 |
July | 7317.89 | 23-JUL-12:50 | 532.32 | 527.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.37 | 0.00 |
August | 7655.33 | 16-AUG-15:01 | 9315.60 | 4611.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.68 | 0.00 |
September | 7348.54 | 09-SEP-12:50 | 798.48 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.28 | 0.00 |
October | 5734.02 | 11-OCT-13:10 | 532.32 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.30 | 0.00 |
November | 4533.49 | 17-NOV-00:23 | 7186.32 | 1581.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.38 |
December | 4608.61 | 05-DEC-02:53 | 7186.32 | 790.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3956.66 | 532.32 | 527.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7655.33 | 9315.60 | 4611.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.92 | 265.17 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.405811E+12 | 260030.37 | 10-JAN-20:49 | 0.566570E+12 | 578134.14 | 05-JAN-17:40 |
February | 0.362636E+12 | 265932.43 | 23-FEB-20:40 | 0.529922E+12 | 523359.79 | 05-FEB-17:40 |
March | 0.402731E+12 | 272340.46 | 14-MAR-18:10 | 0.535120E+12 | 526634.10 | 03-MAR-22:49 |
April | 0.380875E+12 | 270626.80 | 20-APR-19:10 | 0.492919E+12 | 486533.29 | 10-APR-21:40 |
May | 0.429922E+12 | 313853.26 | 31-MAY-19:19 | 0.446398E+12 | 402250.57 | 02-MAY-21:30 |
June | 0.526718E+12 | 406199.36 | 26-JUN-19:30 | 0.401673E+12 | 351420.66 | 01-JUN-17:19 |
July | 0.556019E+12 | 381963.69 | 17-JUL-19:30 | 0.407227E+12 | 349816.88 | 03-JUL-17:19 |
August | 0.543567E+12 | 385793.17 | 16-AUG-19:10 | 0.404172E+12 | 348995.33 | 01-AUG-17:19 |
September | 0.487828E+12 | 358388.69 | 12-SEP-19:10 | 0.399086E+12 | 410958.77 | 21-SEP-17:10 |
October | 0.418744E+12 | 290944.05 | 10-OCT-19:10 | 0.487498E+12 | 497639.05 | 31-OCT-16:40 |
November | 0.397113E+12 | 259980.05 | 14-NOV-20:40 | 0.510646E+12 | 504998.56 | 29-NOV-17:00 |
December | 0.401041E+12 | 256306.88 | 15-DEC-20:19 | 0.625393E+12 | 645417.42 | 21-DEC-17:49 |
Annual Sum or Average | 0.531301E+13 | 0.580662E+13 | ||||
Minimum of Months | 0.362636E+12 | 256306.88 | 0.399086E+12 | 348995.33 | ||
Maximum of Months | 0.556019E+12 | 406199.36 | 0.625393E+12 | 645417.42 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.654635E+11 | 0.249244E+11 | 0.148212E+12 | 0.553309E+11 | 0.511722E+11 | 0.824997E+10 | 0.00 | 0.159745E+11 | 0.00 | 0.00 | 0.235539E+11 | 0.770365E+10 | 0.00 |
February | 0.590027E+11 | 0.209851E+11 | 0.133859E+12 | 0.499764E+11 | 0.455678E+11 | 0.709898E+10 | 0.00 | 0.123458E+11 | 0.00 | 0.00 | 0.221255E+11 | 0.696142E+10 | 0.00 |
March | 0.652008E+11 | 0.210778E+11 | 0.148223E+12 | 0.553337E+11 | 0.501511E+11 | 0.870584E+10 | 0.00 | 0.208962E+11 | 0.00 | 0.00 | 0.202251E+11 | 0.770257E+10 | 0.00 |
April | 0.628520E+11 | 0.182137E+11 | 0.143397E+12 | 0.535455E+11 | 0.468687E+11 | 0.787024E+10 | 0.00 | 0.164631E+11 | 0.00 | 0.00 | 0.191468E+11 | 0.746447E+10 | 0.00 |
May | 0.647982E+11 | 0.169253E+11 | 0.148223E+12 | 0.553319E+11 | 0.501883E+11 | 0.131630E+11 | 0.00 | 0.566133E+11 | 0.00 | 0.00 | 0.117409E+11 | 0.770414E+10 | 0.00 |
June | 0.625908E+11 | 0.153773E+11 | 0.143446E+12 | 0.535480E+11 | 0.575716E+11 | 0.168896E+11 | 0.00 | 0.153864E+12 | 0.00 | 0.00 | 0.108740E+11 | 0.745686E+10 | 0.00 |
July | 0.646227E+11 | 0.163413E+11 | 0.148174E+12 | 0.553289E+11 | 0.595759E+11 | 0.178303E+11 | 0.00 | 0.169656E+12 | 0.00 | 0.00 | 0.115242E+11 | 0.771240E+10 | 0.00 |
August | 0.649450E+11 | 0.179819E+11 | 0.148234E+12 | 0.553335E+11 | 0.607001E+11 | 0.176427E+11 | 0.00 | 0.155696E+12 | 0.00 | 0.00 | 0.100528E+11 | 0.770434E+10 | 0.00 |
September | 0.629479E+11 | 0.194464E+11 | 0.143408E+12 | 0.535457E+11 | 0.574653E+11 | 0.153761E+11 | 0.00 | 0.113440E+12 | 0.00 | 0.00 | 0.967173E+10 | 0.746619E+10 | 0.00 |
October | 0.653206E+11 | 0.223477E+11 | 0.148201E+12 | 0.553308E+11 | 0.544430E+11 | 0.100882E+11 | 0.00 | 0.327886E+11 | 0.00 | 0.00 | 0.173013E+11 | 0.770259E+10 | 0.00 |
November | 0.633476E+11 | 0.235526E+11 | 0.143462E+12 | 0.535468E+11 | 0.516953E+11 | 0.883408E+10 | 0.00 | 0.187724E+11 | 0.00 | 0.00 | 0.213960E+11 | 0.744807E+10 | 0.00 |
December | 0.654142E+11 | 0.254621E+11 | 0.148174E+12 | 0.553297E+11 | 0.516406E+11 | 0.680187E+10 | 0.00 | 0.120940E+11 | 0.00 | 0.00 | 0.232163E+11 | 0.771217E+10 | 0.00 |
Annual Sum or Average | 0.766506E+12 | 0.242636E+12 | 0.174501E+13 | 0.651482E+12 | 0.637040E+12 | 0.138551E+12 | 0.00 | 0.778605E+12 | 0.00 | 0.00 | 0.200829E+12 | 0.907389E+11 | 0.00 |
Minimum of Months | 0.590027E+11 | 0.153773E+11 | 0.133859E+12 | 0.499764E+11 | 0.455678E+11 | 0.680187E+10 | 0.00 | 0.120940E+11 | 0.00 | 0.00 | 0.967173E+10 | 0.696142E+10 | 0.00 |
Maximum of Months | 0.654635E+11 | 0.254621E+11 | 0.148234E+12 | 0.553337E+11 | 0.607001E+11 | 0.178303E+11 | 0.00 | 0.169656E+12 | 0.00 | 0.00 | 0.235539E+11 | 0.771240E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.122827E+12 | 0.00 | 0.291824E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.126764E+12 | 0.00 | 0.265955E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.916547E+11 | 0.00 | 0.291442E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.716792E+11 | 0.00 | 0.274285E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.216420E+11 | 0.00 | 0.272777E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.830315E+09 | 0.00 | 0.253729E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.931618E+09 | 0.00 | 0.254475E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.279454E+09 | 0.00 | 0.251854E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.545023E+10 | 0.00 | 0.246665E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.727968E+11 | 0.00 | 0.262798E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.988902E+11 | 0.00 | 0.264664E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.189512E+12 | 0.00 | 0.284061E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.803258E+12 | 0.00 | 0.321453E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.279454E+09 | 0.00 | 0.246665E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.189512E+12 | 0.00 | 0.291824E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 62892.57 | 02-JAN-20:10 | 15448.40 | 01-JAN-00:10 | 89475.41 | 02-JAN-07:10 | 39726.11 | 02-JAN-07:19 | 51208.78 | 21-JAN-22:19 | 6771.69 | 20-JAN-13:39 | 0.00 | 01-JAN-00:10 |
February | 62892.57 | 01-FEB-20:10 | 15448.40 | 01-FEB-00:10 | 89475.41 | 01-FEB-07:10 | 39726.11 | 01-FEB-07:19 | 50109.09 | 17-FEB-22:00 | 6691.71 | 18-FEB-13:30 | 0.00 | 01-FEB-00:10 |
March | 62892.57 | 01-MAR-20:10 | 15448.40 | 01-MAR-00:10 | 89475.41 | 01-MAR-07:10 | 39726.11 | 13-MAR-06:19 | 50382.39 | 13-MAR-05:19 | 7292.48 | 13-MAR-16:19 | 0.00 | 01-MAR-00:10 |
April | 62892.57 | 03-APR-19:10 | 15448.40 | 01-APR-00:10 | 89475.41 | 03-APR-06:10 | 39725.67 | 03-APR-06:19 | 39542.64 | 10-APR-20:40 | 6780.77 | 07-APR-15:09 | 0.00 | 01-APR-00:10 |
May | 62892.57 | 01-MAY-19:10 | 15448.40 | 01-MAY-00:10 | 89475.41 | 01-MAY-06:10 | 39724.33 | 01-MAY-06:19 | 39380.69 | 20-MAY-04:00 | 7807.99 | 31-MAY-18:49 | 0.00 | 01-MAY-00:10 |
June | 62892.57 | 01-JUN-19:19 | 15448.40 | 01-JUN-00:10 | 89475.41 | 01-JUN-06:10 | 39724.33 | 01-JUN-06:19 | 48390.90 | 30-JUN-21:10 | 7927.03 | 15-JUN-18:19 | 0.00 | 01-JUN-00:10 |
July | 62892.57 | 03-JUL-19:30 | 15448.40 | 01-JUL-00:10 | 89475.41 | 03-JUL-06:10 | 39724.49 | 28-JUL-06:19 | 48465.81 | 18-JUL-21:10 | 7958.29 | 17-JUL-19:19 | 0.00 | 01-JUL-00:10 |
August | 62892.57 | 01-AUG-19:10 | 15448.40 | 01-AUG-00:10 | 89475.41 | 01-AUG-06:10 | 39724.49 | 18-AUG-06:19 | 51044.47 | 16-AUG-21:10 | 7915.92 | 16-AUG-21:40 | 0.00 | 01-AUG-00:10 |
September | 62892.57 | 01-SEP-19:10 | 15448.40 | 01-SEP-00:10 | 89475.41 | 01-SEP-06:10 | 39725.36 | 05-SEP-06:19 | 52608.46 | 12-SEP-21:10 | 7879.52 | 12-SEP-18:10 | 0.00 | 01-SEP-00:10 |
October | 62892.57 | 02-OCT-19:10 | 15448.40 | 01-OCT-00:10 | 89475.41 | 02-OCT-06:10 | 39726.11 | 02-OCT-06:19 | 50823.10 | 18-OCT-04:49 | 7374.44 | 11-OCT-16:19 | 0.00 | 01-OCT-00:10 |
November | 62892.57 | 01-NOV-19:10 | 15448.40 | 01-NOV-00:10 | 89475.41 | 01-NOV-06:10 | 39726.11 | 01-NOV-06:19 | 44319.12 | 24-NOV-22:30 | 6873.55 | 07-NOV-16:10 | 0.00 | 01-NOV-00:10 |
December | 62892.57 | 01-DEC-20:10 | 15448.40 | 01-DEC-00:10 | 89475.41 | 01-DEC-07:10 | 39726.11 | 01-DEC-07:19 | 49673.82 | 17-DEC-22:30 | 6584.76 | 01-DEC-13:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 62892.57 | 15448.40 | 89475.41 | 39724.33 | 39380.69 | 6584.76 | 0.00 | |||||||
Maximum of Months | 62892.57 | 15448.40 | 89475.41 | 39726.11 | 52608.46 | 7958.29 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 66874.78 | 20-JAN-12:00 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4738.33 | 30-JAN-19:49 | 0.00 |
February | 62328.57 | 18-FEB-13:30 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:10 | 4738.34 | 09-FEB-07:10 | 0.00 |
March | 83391.56 | 13-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:10 | 4738.40 | 13-MAR-18:10 | 0.00 |
April | 61828.51 | 07-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4738.37 | 10-APR-06:10 | 0.00 |
May | 93630.25 | 31-MAY-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:10 | 4738.23 | 15-MAY-18:10 | 0.00 |
June | 173015.58 | 26-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-10:39 | 4738.51 | 15-JUN-18:10 | 0.00 |
July | 141864.16 | 16-JUL-15:09 | 0.00 | 0.00 | 9938.94 | 01-JUL-07:19 | 4738.39 | 10-JUL-18:10 | 0.00 |
August | 153774.53 | 16-AUG-15:09 | 0.00 | 0.00 | 9938.94 | 02-AUG-09:00 | 4738.56 | 24-AUG-18:10 | 0.00 |
September | 122602.92 | 10-SEP-15:09 | 0.00 | 0.00 | 9938.94 | 01-SEP-03:30 | 4738.00 | 25-SEP-06:10 | 0.00 |
October | 98868.26 | 11-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:10 | 4738.36 | 19-OCT-06:30 | 0.00 |
November | 71476.68 | 07-NOV-13:00 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4738.27 | 24-NOV-19:30 | 0.00 |
December | 62390.51 | 02-DEC-12:00 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:10 | 4738.69 | 14-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 61828.51 | 0.00 | 0.00 | 9938.94 | 4738.00 | 0.00 | |||
Maximum of Months | 173015.58 | 0.00 | 0.00 | 9938.94 | 4738.69 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 260030.37 | 10-JAN-20:49 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 36627.75 | 4523.85 | 0.00 | 3762.88 | 0.00 |
February | 265932.43 | 23-FEB-20:40 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 41530.15 | 4546.66 | 0.00 | 4477.24 | 0.00 |
March | 272340.46 | 14-MAR-18:10 | 55920.94 | 79417.81 | 15448.40 | 31837.63 | 26792.20 | 6513.87 | 0.00 | 50063.73 | 0.00 |
April | 270626.80 | 20-APR-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 25297.42 | 6032.94 | 0.00 | 33801.36 | 0.00 |
May | 313853.26 | 31-MAY-19:19 | 62892.57 | 88772.42 | 15448.40 | 32158.49 | 30024.19 | 7753.31 | 0.00 | 70522.09 | 0.00 |
June | 406199.36 | 26-JUN-19:30 | 62892.57 | 88772.42 | 15448.40 | 32159.27 | 38667.04 | 7508.89 | 0.00 | 144410.28 | 0.00 |
July | 381963.69 | 17-JUL-19:30 | 62892.57 | 88772.42 | 15448.40 | 32159.27 | 37202.33 | 7943.75 | 0.00 | 121172.31 | 0.00 |
August | 385793.17 | 16-AUG-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 38217.01 | 7505.97 | 0.00 | 124794.02 | 0.00 |
September | 358388.69 | 12-SEP-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 39493.37 | 7833.47 | 0.00 | 96341.88 | 0.00 |
October | 290944.05 | 10-OCT-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 31400.32 | 6655.48 | 0.00 | 47938.91 | 0.00 |
November | 259980.05 | 14-NOV-20:40 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 36505.08 | 4527.82 | 0.00 | 4091.32 | 0.00 |
December | 256306.88 | 15-DEC-20:19 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 32841.01 | 4522.32 | 0.00 | 3907.33 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 256306.88 | 55920.94 | 79417.81 | 15448.40 | 31837.63 | 25297.42 | 4522.32 | 0.00 | 3762.88 | 0.00 | |
Maximum of Months | 406199.36 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 41530.15 | 7943.75 | 0.00 | 144410.28 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 272182.88 | 05-JAN-09:09 | 0.00 | 302067.72 | 23-JAN-21:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 227185.66 | 12-FEB-07:10 | 0.00 | 293449.26 | 14-FEB-21:00 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 213102.46 | 19-MAR-08:09 | 0.00 | 295377.22 | 03-MAR-18:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 166951.74 | 10-APR-21:40 | 0.00 | 297567.87 | 05-APR-20:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 224764.88 | 09-MAY-01:00 | 0.00 | 280831.18 | 02-MAY-20:49 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 61689.98 | 09-JUN-04:19 | 0.00 | 247923.60 | 01-JUN-20:30 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 59099.84 | 02-JUL-04:00 | 0.00 | 246207.70 | 03-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 20088.28 | 23-AUG-04:49 | 0.00 | 245409.61 | 31-AUG-20:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 107329.03 | 21-SEP-15:20 | 0.00 | 246234.92 | 27-SEP-20:19 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 207163.82 | 31-OCT-15:09 | 0.00 | 249364.06 | 16-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 193837.38 | 23-NOV-10:30 | 0.00 | 287167.25 | 17-NOV-21:00 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 348080.04 | 21-DEC-09:09 | 0.00 | 288424.08 | 29-DEC-21:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 20088.28 | 0.00 | 245409.61 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 348080.04 | 0.00 | 302067.72 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.57 | 0.17 | 24.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.57 | 0.17 | 24.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.57 | 0.17 | 24.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.77 | 3.00 | 24.77 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.72 | 1.17 | 24.72 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.59 | 0.17 | 24.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.74 | 1.67 | 24.74 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.64 | 1.50 | 24.64 |
Annual Sum or Average | 0.00 | 0.00 | 7.50 | 24.73 | 7.50 | 24.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.77 | 3.00 | 24.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 59.17 | 25.28 | 59.17 | 25.28 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 | 25.30 | 43.33 | 25.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 51.83 | 25.27 | 51.83 | 25.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 52.17 | 25.31 | 52.17 | 25.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 25.16 | 15.83 | 25.16 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 25.02 | 3.67 | 25.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 25.20 | 45.83 | 25.20 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 65.83 | 25.13 | 65.83 | 25.13 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 47.83 | 25.19 | 47.83 | 25.19 |
Annual Sum or Average | 0.00 | 0.00 | 385.50 | 25.23 | 385.50 | 25.23 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 65.83 | 25.31 | 65.83 | 25.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 24.77 | 5.67 | 24.77 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.72 | 3.00 | 24.72 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.82 | 2.33 | 24.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.65 | 1.33 | 24.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.68 | 0.67 | 24.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.77 | 0.67 | 24.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.73 | 3.50 | 24.73 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.75 | 2.83 | 24.75 |
Annual Sum or Average | 0.00 | 0.00 | 20.00 | 24.75 | 20.00 | 24.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 24.82 | 5.67 | 24.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.72 | 1.50 | 24.72 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.58 | 0.17 | 24.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.80 | 0.67 | 24.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.72 | 0.50 | 24.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.69 | 0.50 | 24.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.57 | 0.67 | 24.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.70 | 0.33 | 24.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.82 | 0.50 | 24.82 |
Annual Sum or Average | 0.00 | 0.00 | 4.83 | 24.71 | 4.83 | 24.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.82 | 1.50 | 24.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 21.69 | 0.67 | 21.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.78 | 1.00 | 21.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.78 | 0.50 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.81 | 1.33 | 21.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 21.78 | 3.17 | 21.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.81 | 1.33 | 21.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.75 | 0.17 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.82 | 1.17 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.84 | 0.50 | 21.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.80 | 1.17 | 21.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.00 | 21.81 | 3.00 | 21.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.84 | 1.17 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.73 | 0.33 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.73 | 0.33 | 21.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.79 | 0.17 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 21.79 | 0.17 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.79 | 0.17 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.90 | 1.00 | 21.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.17 | 21.87 | 1.17 | 21.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.90 | 1.00 | 21.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.96 | 5.17 | 24.96 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.80 | 4.00 | 24.80 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 25.04 | 5.33 | 25.04 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.88 | 8.33 | 24.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.96 | 3.50 | 24.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 24.79 | 7.00 | 24.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.80 | 3.17 | 24.80 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.92 | 3.50 | 24.92 |
Annual Sum or Average | 0.00 | 0.00 | 40.00 | 24.89 | 40.00 | 24.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 25.04 | 8.33 | 25.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 24.98 | 8.17 | 24.98 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.88 | 5.00 | 24.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 25.00 | 8.00 | 25.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 24.90 | 11.50 | 24.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.98 | 4.17 | 24.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 24.84 | 10.33 | 24.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 24.82 | 6.33 | 24.82 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.95 | 5.17 | 24.95 |
Annual Sum or Average | 0.00 | 0.00 | 58.67 | 24.91 | 58.67 | 24.91 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 25.00 | 11.50 | 25.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 98.17 | 25.23 | 98.17 | 25.23 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 91.83 | 25.24 | 91.83 | 25.24 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 79.17 | 25.17 | 79.17 | 25.17 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 72.00 | 25.20 | 72.00 | 25.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 25.08 | 21.33 | 25.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.71 | 0.17 | 24.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 25.05 | 5.50 | 25.05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 67.00 | 25.16 | 67.00 | 25.16 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 109.00 | 25.22 | 109.00 | 25.22 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 81.00 | 25.21 | 81.00 | 25.21 |
Annual Sum or Average | 0.00 | 0.00 | 625.17 | 25.20 | 625.17 | 25.20 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 109.00 | 25.24 | 109.00 | 25.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 560.83 | 23.86 | 0.00 | 23.86 | 0.00 | 23.86 |
February | 620.00 | 23.78 | 0.00 | 23.78 | 0.00 | 23.78 |
March | 734.17 | 23.61 | 0.00 | 23.61 | 0.00 | 23.61 |
April | 642.67 | 23.63 | 0.00 | 23.63 | 0.00 | 23.63 |
May | 647.33 | 23.54 | 1.67 | 23.54 | 0.00 | 23.54 |
June | 438.83 | 23.65 | 138.50 | 23.70 | 85.83 | 23.72 |
July | 440.17 | 23.72 | 216.33 | 23.78 | 163.67 | 23.79 |
August | 307.50 | 23.88 | 268.83 | 23.92 | 103.50 | 23.93 |
September | 238.83 | 23.98 | 44.67 | 23.98 | 1.33 | 23.98 |
October | 364.00 | 23.99 | 0.67 | 23.99 | 0.00 | 23.99 |
November | 297.50 | 23.98 | 2.50 | 23.98 | 0.00 | 23.98 |
December | 647.17 | 23.98 | 0.00 | 23.98 | 0.00 | 23.98 |
Annual Sum or Average | 5939.00 | 23.77 | 673.17 | 23.78 | 354.33 | 23.79 |
Minimum of Months | 238.83 | 23.54 | 0.00 | 23.54 | 0.00 | 23.54 |
Maximum of Months | 734.17 | 23.99 | 268.83 | 23.99 | 163.67 | 23.99 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 552.83 | 21.80 | 194.83 | 22.10 | 70.50 | 22.01 |
February | 502.17 | 21.75 | 235.83 | 21.91 | 138.50 | 21.77 |
March | 560.17 | 21.84 | 149.67 | 21.96 | 78.67 | 21.87 |
April | 607.00 | 21.76 | 127.83 | 21.73 | 102.83 | 21.64 |
May | 487.00 | 22.47 | 73.83 | 22.66 | 2.50 | 22.65 |
June | 195.00 | 23.43 | 438.50 | 23.79 | 77.33 | 23.79 |
July | 239.33 | 23.54 | 508.33 | 23.78 | 153.83 | 23.76 |
August | 190.17 | 23.46 | 530.17 | 23.80 | 103.33 | 23.79 |
September | 222.83 | 22.96 | 302.33 | 23.55 | 2.00 | 23.55 |
October | 486.67 | 22.05 | 228.83 | 22.31 | 86.33 | 22.17 |
November | 514.83 | 21.90 | 191.33 | 22.22 | 60.50 | 22.13 |
December | 613.00 | 21.66 | 257.17 | 21.72 | 183.00 | 21.60 |
Annual Sum or Average | 5171.00 | 22.13 | 3238.67 | 22.58 | 1059.33 | 22.50 |
Minimum of Months | 190.17 | 21.66 | 73.83 | 21.72 | 2.00 | 21.60 |
Maximum of Months | 613.00 | 23.54 | 530.17 | 23.80 | 183.00 | 23.79 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 702.00 | 22.71 | 3.67 | 22.70 | 3.67 | 22.69 |
February | 634.67 | 22.49 | 11.83 | 22.47 | 11.83 | 22.44 |
March | 707.00 | 22.71 | 0.00 | 22.71 | 0.00 | 22.71 |
April | 667.00 | 22.60 | 1.33 | 22.60 | 0.00 | 22.60 |
May | 526.67 | 23.10 | 34.00 | 23.15 | 1.67 | 23.16 |
June | 195.17 | 23.65 | 284.17 | 23.79 | 91.83 | 23.80 |
July | 243.67 | 23.69 | 350.33 | 23.78 | 166.33 | 23.78 |
August | 203.33 | 23.72 | 378.33 | 23.85 | 116.33 | 23.86 |
September | 238.67 | 23.49 | 117.17 | 23.65 | 2.50 | 23.65 |
October | 621.17 | 22.99 | 3.17 | 23.00 | 0.00 | 23.00 |
November | 660.00 | 22.78 | 1.83 | 22.78 | 0.00 | 22.78 |
December | 738.67 | 22.39 | 37.17 | 22.32 | 37.17 | 22.26 |
Annual Sum or Average | 6138.00 | 22.84 | 1223.00 | 22.99 | 431.33 | 23.02 |
Minimum of Months | 195.17 | 22.39 | 0.00 | 22.32 | 0.00 | 22.26 |
Maximum of Months | 738.67 | 23.72 | 378.33 | 23.85 | 166.33 | 23.86 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.90 | 22.00 | 21.88 | 22.00 | 21.85 |
February | 672.00 | 21.73 | 75.83 | 21.65 | 75.83 | 21.59 |
March | 744.00 | 22.18 | 0.33 | 22.18 | 0.33 | 22.17 |
April | 720.00 | 22.26 | 1.33 | 22.26 | 1.33 | 22.26 |
May | 668.33 | 23.32 | 0.00 | 23.32 | 0.00 | 23.32 |
June | 180.17 | 23.98 | 181.00 | 23.98 | 21.33 | 23.98 |
July | 214.50 | 23.97 | 273.83 | 23.97 | 106.67 | 23.97 |
August | 222.00 | 23.96 | 243.33 | 23.98 | 51.50 | 23.98 |
September | 423.50 | 23.74 | 11.50 | 23.75 | 0.00 | 23.75 |
October | 738.67 | 22.83 | 12.50 | 22.80 | 12.50 | 22.77 |
November | 719.00 | 22.17 | 17.50 | 22.14 | 17.50 | 22.11 |
December | 744.00 | 21.67 | 152.67 | 21.56 | 152.67 | 21.48 |
Annual Sum or Average | 6790.17 | 22.50 | 991.83 | 22.58 | 461.67 | 22.56 |
Minimum of Months | 180.17 | 21.67 | 0.00 | 21.56 | 0.00 | 21.48 |
Maximum of Months | 744.00 | 23.98 | 273.83 | 23.98 | 152.67 | 23.98 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.16 | 61.50 | 21.15 | 61.50 | 21.14 |
February | 672.00 | 21.14 | 139.50 | 21.12 | 139.50 | 21.10 |
March | 744.00 | 21.34 | 32.50 | 21.32 | 32.50 | 21.31 |
April | 720.00 | 21.32 | 20.83 | 21.31 | 20.83 | 21.30 |
May | 744.00 | 22.05 | 0.00 | 22.05 | 0.00 | 22.05 |
June | 703.83 | 23.01 | 24.17 | 23.01 | 24.17 | 23.01 |
July | 698.00 | 23.09 | 99.50 | 23.06 | 98.00 | 23.04 |
August | 729.00 | 22.97 | 48.83 | 22.97 | 48.83 | 22.97 |
September | 720.00 | 22.71 | 0.00 | 22.71 | 0.00 | 22.71 |
October | 744.00 | 21.71 | 22.83 | 21.69 | 22.83 | 21.67 |
November | 720.00 | 21.27 | 45.67 | 21.25 | 45.67 | 21.24 |
December | 744.00 | 21.10 | 206.00 | 21.08 | 206.00 | 21.07 |
Annual Sum or Average | 8682.83 | 21.90 | 701.33 | 21.87 | 699.83 | 21.84 |
Minimum of Months | 672.00 | 21.10 | 0.00 | 21.08 | 0.00 | 21.07 |
Maximum of Months | 744.00 | 23.09 | 206.00 | 23.06 | 206.00 | 23.04 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 209.83 | 24.36 | 732.33 | 24.15 | 209.00 | 24.19 |
February | 172.67 | 24.34 | 655.50 | 24.13 | 172.67 | 24.17 |
March | 203.83 | 24.33 | 740.50 | 24.13 | 203.83 | 24.16 |
April | 227.00 | 24.32 | 715.00 | 24.14 | 227.00 | 24.18 |
May | 297.67 | 24.07 | 740.83 | 24.03 | 297.17 | 24.04 |
June | 435.33 | 24.00 | 720.00 | 24.00 | 435.33 | 24.00 |
July | 483.83 | 24.00 | 744.00 | 24.00 | 483.83 | 24.00 |
August | 473.33 | 24.00 | 744.00 | 24.00 | 473.33 | 24.00 |
September | 312.50 | 24.02 | 719.83 | 24.00 | 312.50 | 24.01 |
October | 247.00 | 24.24 | 739.50 | 24.11 | 247.00 | 24.14 |
November | 216.17 | 24.36 | 711.67 | 24.16 | 216.00 | 24.20 |
December | 183.67 | 24.20 | 715.67 | 24.09 | 174.83 | 24.12 |
Annual Sum or Average | 3462.83 | 24.14 | 8678.83 | 24.07 | 3452.50 | 24.09 |
Minimum of Months | 172.67 | 24.00 | 655.50 | 24.00 | 172.67 | 24.00 |
Maximum of Months | 483.83 | 24.36 | 744.00 | 24.16 | 483.83 | 24.20 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.17 | 22.28 | 188.83 | 22.63 | 29.50 | 22.56 |
February | 462.33 | 22.11 | 200.17 | 22.41 | 61.33 | 22.29 |
March | 507.00 | 22.13 | 129.67 | 22.42 | 19.67 | 22.38 |
April | 590.67 | 22.08 | 55.50 | 22.20 | 9.83 | 22.18 |
May | 519.83 | 22.53 | 63.17 | 22.65 | 9.67 | 22.66 |
June | 211.67 | 23.20 | 484.00 | 23.51 | 142.33 | 23.51 |
July | 247.33 | 23.28 | 572.50 | 23.53 | 193.67 | 23.51 |
August | 209.17 | 23.41 | 586.33 | 23.65 | 160.67 | 23.65 |
September | 131.83 | 22.75 | 402.67 | 23.60 | 4.50 | 23.61 |
October | 406.67 | 22.26 | 211.83 | 22.71 | 27.00 | 22.64 |
November | 449.50 | 22.25 | 183.00 | 22.69 | 14.67 | 22.65 |
December | 590.67 | 22.06 | 200.00 | 22.20 | 93.33 | 22.08 |
Annual Sum or Average | 4825.83 | 22.37 | 3277.67 | 22.86 | 766.17 | 22.85 |
Minimum of Months | 131.83 | 22.06 | 55.50 | 22.20 | 4.50 | 22.08 |
Maximum of Months | 590.67 | 23.41 | 586.33 | 23.65 | 193.67 | 23.65 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 488.67 | 23.02 | 2.33 | 23.02 | 0.00 | 23.02 |
February | 460.17 | 22.77 | 0.83 | 22.77 | 0.00 | 22.77 |
March | 547.17 | 22.91 | 0.33 | 22.91 | 0.00 | 22.91 |
April | 550.67 | 22.80 | 33.17 | 22.87 | 0.00 | 22.87 |
May | 359.00 | 23.13 | 128.83 | 23.35 | 10.17 | 23.36 |
June | 172.83 | 23.74 | 410.50 | 23.84 | 136.00 | 23.84 |
July | 204.33 | 23.78 | 472.67 | 23.85 | 187.67 | 23.84 |
August | 175.83 | 23.87 | 499.17 | 23.89 | 158.83 | 23.90 |
September | 66.17 | 23.43 | 244.83 | 23.85 | 4.00 | 23.85 |
October | 307.17 | 22.84 | 36.17 | 22.96 | 0.00 | 22.96 |
November | 399.00 | 22.95 | 15.50 | 23.00 | 0.00 | 23.00 |
December | 618.67 | 22.76 | 11.33 | 22.73 | 11.33 | 22.69 |
Annual Sum or Average | 4349.67 | 23.01 | 1855.67 | 23.27 | 508.00 | 23.31 |
Minimum of Months | 66.17 | 22.76 | 0.33 | 22.73 | 0.00 | 22.69 |
Maximum of Months | 618.67 | 23.87 | 499.17 | 23.89 | 187.67 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 733.83 | 21.28 | 224.83 | 21.17 | 224.83 | 21.10 |
February | 664.50 | 21.21 | 278.67 | 21.08 | 278.67 | 21.01 |
March | 732.33 | 21.22 | 254.17 | 21.07 | 254.17 | 20.99 |
April | 717.50 | 21.20 | 193.17 | 21.06 | 193.17 | 20.97 |
May | 719.83 | 21.55 | 15.67 | 21.54 | 13.83 | 21.53 |
June | 605.83 | 21.42 | 26.50 | 21.50 | 1.00 | 21.50 |
July | 618.33 | 21.39 | 18.17 | 21.44 | 3.33 | 21.45 |
August | 618.50 | 21.39 | 26.50 | 21.47 | 0.83 | 21.47 |
September | 636.33 | 21.47 | 12.17 | 21.50 | 1.00 | 21.50 |
October | 711.50 | 21.28 | 128.67 | 21.16 | 128.67 | 21.07 |
November | 701.83 | 21.28 | 188.50 | 21.16 | 188.50 | 21.08 |
December | 742.83 | 21.11 | 440.67 | 20.98 | 440.67 | 20.91 |
Annual Sum or Average | 8203.17 | 21.31 | 1807.67 | 21.22 | 1728.67 | 21.15 |
Minimum of Months | 605.83 | 21.11 | 12.17 | 20.98 | 0.83 | 20.91 |
Maximum of Months | 742.83 | 21.55 | 440.67 | 21.54 | 440.67 | 21.53 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.87 | 444.33 | 20.78 | 444.33 | 20.73 |
February | 672.00 | 20.87 | 412.17 | 20.76 | 412.17 | 20.72 |
March | 744.00 | 21.04 | 359.67 | 20.91 | 359.67 | 20.84 |
April | 720.00 | 21.08 | 229.67 | 20.95 | 229.67 | 20.87 |
May | 729.50 | 21.53 | 20.50 | 21.51 | 19.17 | 21.50 |
June | 627.17 | 21.48 | 21.33 | 21.54 | 0.67 | 21.54 |
July | 640.83 | 21.46 | 9.33 | 21.48 | 3.67 | 21.49 |
August | 670.83 | 21.52 | 10.50 | 21.55 | 0.67 | 21.55 |
September | 685.50 | 21.55 | 6.33 | 21.55 | 3.83 | 21.55 |
October | 742.17 | 21.18 | 169.33 | 21.05 | 169.33 | 20.97 |
November | 720.00 | 20.98 | 326.83 | 20.87 | 326.83 | 20.80 |
December | 744.00 | 20.78 | 634.67 | 20.73 | 634.67 | 20.71 |
Annual Sum or Average | 8440.00 | 21.19 | 2644.67 | 21.06 | 2604.67 | 20.98 |
Minimum of Months | 627.17 | 20.78 | 6.33 | 20.73 | 0.67 | 20.71 |
Maximum of Months | 744.00 | 21.55 | 634.67 | 21.55 | 634.67 | 21.55 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.86 | 388.83 | 20.78 | 388.83 | 20.75 |
February | 672.00 | 20.84 | 439.83 | 20.78 | 439.83 | 20.76 |
March | 744.00 | 21.01 | 253.17 | 20.94 | 253.17 | 20.90 |
April | 720.00 | 21.10 | 128.67 | 21.05 | 128.67 | 21.01 |
May | 744.00 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
June | 720.00 | 21.60 | 0.17 | 21.60 | 0.17 | 21.60 |
July | 744.00 | 21.62 | 4.67 | 21.62 | 4.67 | 21.62 |
August | 744.00 | 21.55 | 0.83 | 21.55 | 0.83 | 21.55 |
September | 720.00 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
October | 744.00 | 21.08 | 115.50 | 21.02 | 115.50 | 20.97 |
November | 720.00 | 20.92 | 251.83 | 20.84 | 251.83 | 20.79 |
December | 744.00 | 20.81 | 585.67 | 20.77 | 585.67 | 20.76 |
Annual Sum or Average | 8760.00 | 21.19 | 2169.17 | 21.09 | 2169.17 | 21.02 |
Minimum of Months | 672.00 | 20.81 | 0.00 | 20.77 | 0.00 | 20.75 |
Maximum of Months | 744.00 | 21.62 | 585.67 | 21.62 | 585.67 | 21.62 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.33 | 232.83 | 21.22 | 232.83 | 21.15 |
February | 670.33 | 21.28 | 280.17 | 21.13 | 280.17 | 21.05 |
March | 737.67 | 21.31 | 247.00 | 21.15 | 247.00 | 21.06 |
April | 715.17 | 21.29 | 191.67 | 21.15 | 191.67 | 21.06 |
May | 721.67 | 21.63 | 12.67 | 21.62 | 12.67 | 21.61 |
June | 557.33 | 21.29 | 19.00 | 21.36 | 0.67 | 21.36 |
July | 574.83 | 21.28 | 20.33 | 21.35 | 3.17 | 21.35 |
August | 570.67 | 21.27 | 38.67 | 21.41 | 0.00 | 21.41 |
September | 608.50 | 21.43 | 8.00 | 21.45 | 0.83 | 21.45 |
October | 718.83 | 21.35 | 126.33 | 21.22 | 126.17 | 21.13 |
November | 717.83 | 21.33 | 199.83 | 21.21 | 199.83 | 21.12 |
December | 744.00 | 21.12 | 440.50 | 20.99 | 440.50 | 20.93 |
Annual Sum or Average | 8080.83 | 21.33 | 1817.00 | 21.24 | 1735.50 | 21.17 |
Minimum of Months | 557.33 | 21.12 | 8.00 | 20.99 | 0.00 | 20.93 |
Maximum of Months | 744.00 | 21.63 | 440.50 | 21.62 | 440.50 | 21.61 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.83 | 453.50 | 20.75 | 453.50 | 20.72 |
February | 672.00 | 20.89 | 406.00 | 20.80 | 406.00 | 20.75 |
March | 744.00 | 21.16 | 333.17 | 21.02 | 333.17 | 20.95 |
April | 717.67 | 21.21 | 227.00 | 21.07 | 227.00 | 20.99 |
May | 735.33 | 21.64 | 14.17 | 21.63 | 14.17 | 21.62 |
June | 568.67 | 21.33 | 14.17 | 21.38 | 0.67 | 21.38 |
July | 590.17 | 21.33 | 12.50 | 21.37 | 3.33 | 21.38 |
August | 614.00 | 21.41 | 14.83 | 21.46 | 0.50 | 21.46 |
September | 687.83 | 21.62 | 3.00 | 21.63 | 1.33 | 21.62 |
October | 743.17 | 21.27 | 165.00 | 21.14 | 165.00 | 21.05 |
November | 720.00 | 20.93 | 361.00 | 20.83 | 361.00 | 20.78 |
December | 744.00 | 20.73 | 644.83 | 20.70 | 644.83 | 20.69 |
Annual Sum or Average | 8280.83 | 21.19 | 2649.17 | 21.07 | 2610.50 | 20.99 |
Minimum of Months | 568.67 | 20.73 | 3.00 | 20.70 | 0.50 | 20.69 |
Maximum of Months | 744.00 | 21.64 | 644.83 | 21.63 | 644.83 | 21.62 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.95 | 13.33 | 21.93 | 13.33 | 21.92 |
February | 672.00 | 21.82 | 35.67 | 21.77 | 35.67 | 21.74 |
March | 744.00 | 22.18 | 0.00 | 22.18 | 0.00 | 22.18 |
April | 720.00 | 22.03 | 0.00 | 22.03 | 0.00 | 22.03 |
May | 729.17 | 23.15 | 3.83 | 23.15 | 3.83 | 23.15 |
June | 281.00 | 23.94 | 186.33 | 23.94 | 112.00 | 23.94 |
July | 289.00 | 23.93 | 283.50 | 23.94 | 171.50 | 23.93 |
August | 301.00 | 23.94 | 263.67 | 23.95 | 128.50 | 23.95 |
September | 434.83 | 23.76 | 13.17 | 23.76 | 2.17 | 23.77 |
October | 741.50 | 22.91 | 15.67 | 22.87 | 15.67 | 22.83 |
November | 720.00 | 22.15 | 3.83 | 22.14 | 3.83 | 22.14 |
December | 744.00 | 21.51 | 125.83 | 21.44 | 125.83 | 21.38 |
Annual Sum or Average | 7120.50 | 22.52 | 944.83 | 22.62 | 612.33 | 22.64 |
Minimum of Months | 281.00 | 21.51 | 0.00 | 21.44 | 0.00 | 21.38 |
Maximum of Months | 744.00 | 23.94 | 283.50 | 23.95 | 171.50 | 23.95 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 732.67 | 21.18 | 379.33 | 21.05 | 379.33 | 20.99 |
February | 663.00 | 21.14 | 362.50 | 21.01 | 362.50 | 20.94 |
March | 728.50 | 21.14 | 352.83 | 21.00 | 352.83 | 20.93 |
April | 713.33 | 21.12 | 269.00 | 20.97 | 269.00 | 20.88 |
May | 709.00 | 21.49 | 36.00 | 21.46 | 33.67 | 21.44 |
June | 584.00 | 21.34 | 51.67 | 21.48 | 7.17 | 21.48 |
July | 602.17 | 21.33 | 75.50 | 21.44 | 37.67 | 21.43 |
August | 601.17 | 21.32 | 62.17 | 21.45 | 19.83 | 21.45 |
September | 625.00 | 21.41 | 34.83 | 21.45 | 16.50 | 21.44 |
October | 710.67 | 21.22 | 204.50 | 21.07 | 203.50 | 20.98 |
November | 699.00 | 21.19 | 290.00 | 21.06 | 290.00 | 20.99 |
December | 741.33 | 21.02 | 543.83 | 20.90 | 543.83 | 20.85 |
Annual Sum or Average | 8109.83 | 21.23 | 2662.17 | 21.15 | 2515.83 | 21.07 |
Minimum of Months | 584.00 | 21.02 | 34.83 | 20.90 | 7.17 | 20.85 |
Maximum of Months | 741.33 | 21.49 | 543.83 | 21.48 | 543.83 | 21.48 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.75 | 625.00 | 20.70 | 625.00 | 20.68 |
February | 672.00 | 20.78 | 538.33 | 20.71 | 538.33 | 20.69 |
March | 743.83 | 20.97 | 460.33 | 20.84 | 460.33 | 20.79 |
April | 719.50 | 21.01 | 312.33 | 20.87 | 312.33 | 20.80 |
May | 724.17 | 21.48 | 45.83 | 21.45 | 44.00 | 21.42 |
June | 603.17 | 21.40 | 41.50 | 21.51 | 6.67 | 21.51 |
July | 623.00 | 21.39 | 65.33 | 21.46 | 40.17 | 21.45 |
August | 645.83 | 21.44 | 45.17 | 21.49 | 24.50 | 21.48 |
September | 677.50 | 21.49 | 29.50 | 21.48 | 23.67 | 21.46 |
October | 741.33 | 21.08 | 292.33 | 20.95 | 292.33 | 20.87 |
November | 720.00 | 20.88 | 500.00 | 20.79 | 500.00 | 20.75 |
December | 744.00 | 20.69 | 693.83 | 20.66 | 693.83 | 20.65 |
Annual Sum or Average | 8358.33 | 21.10 | 3649.50 | 20.98 | 3561.17 | 20.90 |
Minimum of Months | 603.17 | 20.69 | 29.50 | 20.66 | 6.67 | 20.65 |
Maximum of Months | 744.00 | 21.49 | 693.83 | 21.51 | 693.83 | 21.51 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 648.83 | 21.25 | 135.50 | 21.24 | 115.17 | 21.19 |
February | 597.50 | 21.20 | 210.67 | 21.11 | 204.00 | 21.05 |
March | 688.17 | 21.19 | 212.67 | 21.06 | 212.67 | 20.98 |
April | 703.17 | 21.22 | 191.17 | 21.08 | 191.17 | 21.00 |
May | 728.50 | 21.56 | 16.83 | 21.55 | 16.83 | 21.53 |
June | 617.83 | 21.43 | 5.50 | 21.44 | 4.00 | 21.44 |
July | 628.50 | 21.41 | 21.33 | 21.43 | 16.33 | 21.43 |
August | 610.50 | 21.35 | 45.83 | 21.48 | 3.17 | 21.48 |
September | 603.17 | 21.38 | 37.17 | 21.48 | 2.50 | 21.48 |
October | 647.33 | 21.14 | 140.50 | 21.10 | 121.67 | 21.02 |
November | 626.67 | 21.25 | 151.33 | 21.24 | 125.33 | 21.18 |
December | 683.00 | 21.24 | 288.33 | 21.14 | 286.50 | 21.08 |
Annual Sum or Average | 7783.17 | 21.30 | 1456.83 | 21.26 | 1299.33 | 21.19 |
Minimum of Months | 597.50 | 21.14 | 5.50 | 21.06 | 2.50 | 20.98 |
Maximum of Months | 728.50 | 21.56 | 288.33 | 21.55 | 286.50 | 21.53 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 682.00 | 22.48 | 5.00 | 22.50 | 0.00 | 22.50 |
February | 619.67 | 22.46 | 5.00 | 22.48 | 0.00 | 22.48 |
March | 599.50 | 22.61 | 8.33 | 22.64 | 0.00 | 22.64 |
April | 502.50 | 22.63 | 72.00 | 22.81 | 0.00 | 22.81 |
May | 210.00 | 22.84 | 273.67 | 23.43 | 9.67 | 23.44 |
June | 146.00 | 23.73 | 567.33 | 23.78 | 137.83 | 23.78 |
July | 196.17 | 23.72 | 616.17 | 23.76 | 191.00 | 23.76 |
August | 181.33 | 23.71 | 556.00 | 23.75 | 159.50 | 23.77 |
September | 165.83 | 22.81 | 292.67 | 23.48 | 4.33 | 23.49 |
October | 513.50 | 22.65 | 46.50 | 22.77 | 0.00 | 22.77 |
November | 619.50 | 22.58 | 12.67 | 22.61 | 0.00 | 22.61 |
December | 718.50 | 22.38 | 25.00 | 22.34 | 24.67 | 22.29 |
Annual Sum or Average | 5154.50 | 22.67 | 2480.33 | 23.04 | 527.00 | 23.08 |
Minimum of Months | 146.00 | 22.38 | 5.00 | 22.34 | 0.00 | 22.29 |
Maximum of Months | 718.50 | 23.73 | 616.17 | 23.78 | 191.00 | 23.78 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 538.50 | 22.65 | 33.67 | 22.75 | 0.00 | 22.75 |
February | 499.67 | 22.66 | 25.00 | 22.74 | 0.00 | 22.74 |
March | 449.33 | 22.79 | 46.67 | 22.92 | 0.00 | 22.92 |
April | 337.17 | 22.79 | 161.33 | 23.20 | 0.00 | 23.20 |
May | 85.00 | 23.00 | 404.67 | 23.74 | 9.17 | 23.75 |
June | 136.33 | 23.89 | 658.17 | 23.86 | 135.00 | 23.87 |
July | 189.33 | 23.86 | 698.83 | 23.86 | 188.50 | 23.86 |
August | 157.50 | 23.91 | 661.00 | 23.85 | 156.17 | 23.86 |
September | 71.00 | 22.92 | 412.67 | 23.74 | 4.33 | 23.74 |
October | 363.33 | 22.75 | 122.83 | 23.08 | 0.00 | 23.08 |
November | 467.00 | 22.74 | 51.83 | 22.87 | 0.00 | 22.87 |
December | 625.00 | 22.59 | 2.33 | 22.60 | 0.00 | 22.60 |
Annual Sum or Average | 3919.17 | 22.85 | 3279.00 | 23.33 | 493.17 | 23.36 |
Minimum of Months | 71.00 | 22.59 | 2.33 | 22.60 | 0.00 | 22.60 |
Maximum of Months | 625.00 | 23.91 | 698.83 | 23.86 | 188.50 | 23.87 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.67 | 24.27 | 733.33 | 24.22 | 497.67 | 24.24 |
February | 434.67 | 24.29 | 659.83 | 24.23 | 434.67 | 24.25 |
March | 507.67 | 24.19 | 738.50 | 24.17 | 507.67 | 24.18 |
April | 507.00 | 24.18 | 719.17 | 24.17 | 507.00 | 24.17 |
May | 547.67 | 24.03 | 741.83 | 24.04 | 547.67 | 24.03 |
June | 560.17 | 23.99 | 720.00 | 23.99 | 560.17 | 23.99 |
July | 602.50 | 23.99 | 744.00 | 23.99 | 602.50 | 23.99 |
August | 609.50 | 23.99 | 744.00 | 23.99 | 609.50 | 23.99 |
September | 523.00 | 24.01 | 720.00 | 24.00 | 523.00 | 24.00 |
October | 514.17 | 24.14 | 743.50 | 24.13 | 514.17 | 24.13 |
November | 490.00 | 24.30 | 716.00 | 24.25 | 490.00 | 24.26 |
December | 464.67 | 24.18 | 707.50 | 24.16 | 451.33 | 24.18 |
Annual Sum or Average | 6258.67 | 24.12 | 8687.67 | 24.11 | 6245.33 | 24.11 |
Minimum of Months | 434.67 | 23.99 | 659.83 | 23.99 | 434.67 | 23.99 |
Maximum of Months | 609.50 | 24.30 | 744.00 | 24.25 | 609.50 | 24.26 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.76 | 61.83 | 21.70 | 61.83 | 21.65 |
February | 672.00 | 21.77 | 101.67 | 21.67 | 101.67 | 21.59 |
March | 744.00 | 22.11 | 24.17 | 22.08 | 24.17 | 22.05 |
April | 719.33 | 22.16 | 5.67 | 22.15 | 5.67 | 22.14 |
May | 518.33 | 23.24 | 11.00 | 23.26 | 0.00 | 23.26 |
June | 128.00 | 23.92 | 275.50 | 23.96 | 67.00 | 23.96 |
July | 183.67 | 23.93 | 340.83 | 23.96 | 145.50 | 23.96 |
August | 157.67 | 23.91 | 370.50 | 23.96 | 92.50 | 23.96 |
September | 285.00 | 23.53 | 69.83 | 23.62 | 0.00 | 23.62 |
October | 700.83 | 22.67 | 30.33 | 22.61 | 30.33 | 22.54 |
November | 717.33 | 22.05 | 32.33 | 22.01 | 32.33 | 21.96 |
December | 744.00 | 21.49 | 176.00 | 21.39 | 176.00 | 21.33 |
Annual Sum or Average | 6314.17 | 22.31 | 1499.67 | 22.47 | 737.00 | 22.45 |
Minimum of Months | 128.00 | 21.49 | 5.67 | 21.39 | 0.00 | 21.33 |
Maximum of Months | 744.00 | 23.93 | 370.50 | 23.96 | 176.00 | 23.96 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.89581 | 24.56815 | 0.19680 | 5.89156 |
February | 672.00000 | 23.79299 | 23.44155 | 0.15759 | 5.63662 |
March | 744.00000 | 23.61593 | 22.89147 | 0.10669 | 5.39662 |
April | 720.00000 | 23.66412 | 26.97574 | 0.14579 | 5.62426 |
May | 744.00000 | 23.58538 | 31.02819 | -0.8038 | 18.87332 |
June | 720.00000 | 23.74119 | 38.16663 | -0.6902 | 15.29067 |
July | 744.00000 | 23.79652 | 40.56143 | -0.6516 | 14.19102 |
August | 744.00000 | 23.91357 | 39.57980 | -0.6004 | 12.76260 |
September | 720.00000 | 23.98784 | 28.61116 | -0.6314 | 13.46820 |
October | 744.00000 | 24.00076 | 23.96382 | 0.24436 | 6.29873 |
November | 720.00000 | 24.00080 | 24.92750 | 0.24866 | 6.33326 |
December | 744.00000 | 23.98774 | 19.01315 | 0.19804 | 5.85150 |
Annual Sum or Average | 8760.00000 | 23.83202 | 28.67556 | -0.1754 | 9.66176 |
Minimum of Months | 672.00000 | 23.58538 | 19.01315 | -0.8038 | 5.39662 |
Maximum of Months | 744.00000 | 24.00080 | 40.56143 | 0.24866 | 18.87332 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.37512 | 25.88421 | -0.0973 | 8.56362 |
February | 672.00000 | 22.32628 | 24.23101 | -0.1443 | 9.26678 |
March | 744.00000 | 22.37099 | 23.70314 | -0.1365 | 8.52446 |
April | 720.00000 | 22.10164 | 28.55689 | -0.1974 | 8.22448 |
May | 744.00000 | 22.96430 | 31.38462 | -0.9006 | 24.46423 |
June | 720.00000 | 23.79235 | 37.18188 | -0.4933 | 10.87450 |
July | 744.00000 | 23.81750 | 39.75800 | -0.4644 | 10.27278 |
August | 744.00000 | 23.81034 | 39.28417 | -0.4481 | 10.09926 |
September | 720.00000 | 23.65061 | 29.03670 | -0.5716 | 13.95458 |
October | 744.00000 | 22.71827 | 25.80798 | -0.0012 | 8.31173 |
November | 720.00000 | 22.50622 | 27.00294 | -0.0534 | 8.48068 |
December | 744.00000 | 22.07666 | 20.67080 | -0.2462 | 9.78161 |
Annual Sum or Average | 8760.00000 | 22.87887 | 29.40576 | -0.3141 | 10.92067 |
Minimum of Months | 672.00000 | 22.07666 | 20.67080 | -0.9006 | 8.22448 |
Maximum of Months | 744.00000 | 23.81750 | 39.75800 | -0.0012 | 24.46423 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.77912 | 26.41155 | -0.0310 | 5.72756 |
February | 672.00000 | 22.57839 | 24.99697 | -0.0928 | 6.30343 |
March | 744.00000 | 22.77114 | 24.15815 | -0.0477 | 5.87816 |
April | 720.00000 | 22.69722 | 28.52463 | -0.0410 | 5.95985 |
May | 744.00000 | 23.32339 | 31.58239 | -0.8110 | 19.61717 |
June | 720.00000 | 23.80842 | 37.98135 | -0.5659 | 11.96500 |
July | 744.00000 | 23.82273 | 40.59482 | -0.5446 | 11.43987 |
August | 744.00000 | 23.82593 | 40.17796 | -0.5454 | 11.50236 |
September | 720.00000 | 23.77265 | 29.86130 | -0.6410 | 14.02824 |
October | 744.00000 | 23.14833 | 26.24670 | 0.06772 | 5.98605 |
November | 720.00000 | 22.87581 | 27.56261 | 0.00203 | 5.81909 |
December | 744.00000 | 22.40060 | 21.43649 | -0.1639 | 6.64665 |
Annual Sum or Average | 8760.00000 | 23.15350 | 29.99085 | -0.2858 | 9.26135 |
Minimum of Months | 672.00000 | 22.40060 | 21.43649 | -0.8110 | 5.72756 |
Maximum of Months | 744.00000 | 23.82593 | 40.59482 | 0.06772 | 19.61717 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 24.07266 | 20.92510 | 0.81623 | 20.18319 |
February | 672.00000 | 24.04492 | 19.46509 | 0.79329 | 19.49290 |
March | 744.00000 | 24.06691 | 18.59394 | 0.81498 | 20.06984 |
April | 720.00000 | 24.07968 | 22.67136 | 0.84477 | 21.15456 |
May | 744.00000 | 24.00349 | 26.55270 | 0.26403 | 8.38143 |
June | 720.00000 | 23.99825 | 33.93762 | 0.37915 | 9.84146 |
July | 744.00000 | 23.99853 | 36.55099 | 0.39349 | 9.99568 |
August | 744.00000 | 23.99982 | 36.05235 | 0.38995 | 9.95673 |
September | 720.00000 | 23.99883 | 25.74989 | 0.29483 | 8.57559 |
October | 744.00000 | 24.06375 | 21.03187 | 0.84493 | 20.99509 |
November | 720.00000 | 24.08989 | 22.03471 | 0.83714 | 20.88397 |
December | 744.00000 | 24.01940 | 16.03418 | 0.74892 | 18.01267 |
Annual Sum or Average | 8760.00000 | 24.03622 | 24.99947 | 0.61736 | 15.60247 |
Minimum of Months | 672.00000 | 23.99825 | 16.03418 | 0.26403 | 8.38143 |
Maximum of Months | 744.00000 | 24.08989 | 36.55099 | 0.84493 | 21.15456 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.80938 | 28.59038 | 0.09310 | 7.76754 |
February | 672.00000 | 22.67117 | 27.15799 | 0.02964 | 8.32782 |
March | 744.00000 | 22.68377 | 26.62334 | 0.02508 | 7.50248 |
April | 720.00000 | 22.36212 | 31.36141 | -0.0511 | 6.91880 |
May | 744.00000 | 22.80301 | 34.90944 | -0.8387 | 21.00932 |
June | 720.00000 | 23.46495 | 41.52313 | -0.4912 | 10.65444 |
July | 744.00000 | 23.51809 | 44.05592 | -0.4506 | 9.94577 |
August | 744.00000 | 23.62202 | 43.25697 | -0.3978 | 9.18356 |
September | 720.00000 | 23.59978 | 32.69091 | -0.4765 | 11.42253 |
October | 744.00000 | 22.97676 | 28.74637 | 0.14486 | 8.21377 |
November | 720.00000 | 22.85965 | 29.79323 | 0.11920 | 8.01691 |
December | 744.00000 | 22.45028 | 23.61554 | -0.0650 | 8.18778 |
Annual Sum or Average | 8760.00000 | 22.98671 | 32.72663 | -0.1981 | 9.77993 |
Minimum of Months | 672.00000 | 22.36212 | 23.61554 | -0.8387 | 6.91880 |
Maximum of Months | 744.00000 | 23.62202 | 44.05592 | 0.14486 | 21.00932 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.32147 | 28.37155 | 0.13358 | 6.04350 |
February | 672.00000 | 23.12733 | 27.05682 | 0.07053 | 6.21845 |
March | 744.00000 | 23.19246 | 26.24405 | 0.08577 | 5.90681 |
April | 720.00000 | 23.07007 | 30.60535 | 0.07756 | 5.96016 |
May | 744.00000 | 23.51207 | 33.84478 | -0.7003 | 15.92014 |
June | 720.00000 | 23.79376 | 40.30870 | -0.5131 | 10.73961 |
July | 744.00000 | 23.82367 | 42.83618 | -0.4834 | 10.10945 |
August | 744.00000 | 23.85845 | 42.31517 | -0.4715 | 9.85018 |
September | 720.00000 | 23.87406 | 31.99389 | -0.5436 | 11.44294 |
October | 744.00000 | 23.48496 | 28.26608 | 0.18750 | 6.58836 |
November | 720.00000 | 23.38516 | 29.48933 | 0.16013 | 6.26165 |
December | 744.00000 | 22.95819 | 23.58488 | 0.00122 | 6.25175 |
Annual Sum or Average | 8760.00000 | 23.45191 | 32.10644 | -0.1678 | 8.45760 |
Minimum of Months | 672.00000 | 22.95819 | 23.58488 | -0.7003 | 5.90681 |
Maximum of Months | 744.00000 | 23.87406 | 42.83618 | 0.18750 | 15.92014 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.30643 | 29.35217 | -0.4549 | 10.67995 |
February | 672.00000 | 21.23824 | 27.17494 | -0.4942 | 11.78291 |
March | 744.00000 | 21.24834 | 27.66884 | -0.4511 | 10.75261 |
April | 720.00000 | 21.20702 | 32.63448 | -0.4423 | 10.42731 |
May | 744.00000 | 21.60779 | 36.94906 | -1.3478 | 43.82926 |
June | 720.00000 | 21.71911 | 41.53998 | -1.1415 | 34.09634 |
July | 744.00000 | 21.71984 | 43.11667 | -1.1476 | 34.32394 |
August | 744.00000 | 21.71343 | 43.13876 | -1.1471 | 34.38139 |
September | 720.00000 | 21.68631 | 35.37191 | -1.2371 | 38.77156 |
October | 744.00000 | 21.37256 | 30.89219 | -0.3648 | 9.60501 |
November | 720.00000 | 21.32884 | 31.25508 | -0.4214 | 10.22810 |
December | 744.00000 | 21.11207 | 23.83687 | -0.5804 | 13.62080 |
Annual Sum or Average | 8760.00000 | 21.43946 | 33.61242 | -0.7710 | 21.94138 |
Minimum of Months | 672.00000 | 21.11207 | 23.83687 | -1.3478 | 9.60501 |
Maximum of Months | 744.00000 | 21.71984 | 43.13876 | -0.3648 | 43.82926 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.87111 | 30.00574 | -0.6189 | 13.76255 |
February | 672.00000 | 20.86647 | 27.66108 | -0.6369 | 14.48485 |
March | 744.00000 | 21.04245 | 27.90501 | -0.5388 | 12.09849 |
April | 720.00000 | 21.08201 | 32.82995 | -0.4908 | 11.07659 |
May | 744.00000 | 21.56385 | 37.03832 | -1.3771 | 45.16573 |
June | 720.00000 | 21.71728 | 41.60361 | -1.1500 | 34.36447 |
July | 744.00000 | 21.71689 | 43.23977 | -1.1586 | 34.70653 |
August | 744.00000 | 21.69865 | 43.45104 | -1.1813 | 35.70866 |
September | 720.00000 | 21.63347 | 35.53832 | -1.3048 | 41.71792 |
October | 744.00000 | 21.18371 | 31.12709 | -0.4566 | 10.50862 |
November | 720.00000 | 20.98421 | 31.78990 | -0.5626 | 12.48462 |
December | 744.00000 | 20.78098 | 24.23486 | -0.7128 | 16.55873 |
Annual Sum or Average | 8760.00000 | 21.26399 | 33.90252 | -0.8505 | 23.61280 |
Minimum of Months | 672.00000 | 20.78098 | 24.23486 | -1.3771 | 10.50862 |
Maximum of Months | 744.00000 | 21.71728 | 43.45104 | -0.4566 | 45.16573 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.85632 | 28.99534 | -0.6046 | 12.94393 |
February | 672.00000 | 20.83557 | 26.70832 | -0.6254 | 13.54612 |
March | 744.00000 | 21.01103 | 26.77576 | -0.5527 | 11.56992 |
April | 720.00000 | 21.09793 | 31.64458 | -0.4892 | 10.25372 |
May | 744.00000 | 21.39487 | 35.91437 | -1.5042 | 51.23849 |
June | 720.00000 | 21.59779 | 41.24002 | -1.3418 | 42.91978 |
July | 744.00000 | 21.61581 | 42.93735 | -1.3246 | 42.10197 |
August | 744.00000 | 21.54933 | 43.11175 | -1.3662 | 44.09643 |
September | 720.00000 | 21.43767 | 34.46557 | -1.4828 | 50.18866 |
October | 744.00000 | 21.08298 | 29.96085 | -0.5023 | 10.51536 |
November | 720.00000 | 20.92214 | 30.85725 | -0.5671 | 11.97590 |
December | 744.00000 | 20.80630 | 23.23639 | -0.6612 | 14.57630 |
Annual Sum or Average | 8760.00000 | 21.18597 | 33.02176 | -0.9203 | 26.40479 |
Minimum of Months | 672.00000 | 20.80630 | 23.23639 | -1.5042 | 10.25372 |
Maximum of Months | 744.00000 | 21.61581 | 43.11175 | -0.4892 | 51.23849 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.33488 | 29.32893 | -0.4516 | 10.56084 |
February | 672.00000 | 21.28692 | 27.10905 | -0.4819 | 11.67317 |
March | 744.00000 | 21.32893 | 27.61598 | -0.4262 | 10.46231 |
April | 720.00000 | 21.30002 | 32.51664 | -0.4102 | 10.08592 |
May | 744.00000 | 21.67897 | 36.80116 | -1.3102 | 42.04505 |
June | 720.00000 | 21.75035 | 41.35295 | -1.1154 | 32.99198 |
July | 744.00000 | 21.74586 | 42.85149 | -1.1130 | 32.90814 |
August | 744.00000 | 21.74775 | 42.78152 | -1.1115 | 32.96274 |
September | 720.00000 | 21.72079 | 35.30194 | -1.2130 | 37.69885 |
October | 744.00000 | 21.41343 | 30.85549 | -0.3564 | 9.55400 |
November | 720.00000 | 21.34072 | 31.24397 | -0.4232 | 10.23162 |
December | 744.00000 | 21.12397 | 23.81056 | -0.5783 | 13.51020 |
Annual Sum or Average | 8760.00000 | 21.48213 | 33.49841 | -0.7510 | 21.28548 |
Minimum of Months | 672.00000 | 21.12397 | 23.81056 | -1.3102 | 9.55400 |
Maximum of Months | 744.00000 | 21.75035 | 42.85149 | -0.3564 | 42.04505 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.83103 | 30.03075 | -0.6299 | 13.93570 |
February | 672.00000 | 20.89490 | 27.55970 | -0.6281 | 14.34447 |
March | 744.00000 | 21.15651 | 27.76691 | -0.5067 | 11.50673 |
April | 720.00000 | 21.21354 | 32.63407 | -0.4509 | 10.56713 |
May | 744.00000 | 21.65509 | 36.84417 | -1.3339 | 43.09080 |
June | 720.00000 | 21.75037 | 41.45035 | -1.1234 | 33.24123 |
July | 744.00000 | 21.74514 | 42.97831 | -1.1233 | 33.25284 |
August | 744.00000 | 21.74408 | 43.03999 | -1.1416 | 34.07803 |
September | 720.00000 | 21.70093 | 35.39750 | -1.2698 | 40.08559 |
October | 744.00000 | 21.27481 | 30.97437 | -0.4385 | 10.27128 |
November | 720.00000 | 20.93229 | 31.84474 | -0.5770 | 12.73819 |
December | 744.00000 | 20.73273 | 24.24226 | -0.7228 | 16.73366 |
Annual Sum or Average | 8760.00000 | 21.30491 | 33.76343 | -0.8302 | 22.87548 |
Minimum of Months | 672.00000 | 20.73273 | 24.24226 | -1.3339 | 10.27128 |
Maximum of Months | 744.00000 | 21.75037 | 43.03999 | -0.4385 | 43.09080 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.20804 | 29.69180 | -0.5219 | 12.24814 |
February | 672.00000 | 21.16635 | 27.48744 | -0.5528 | 13.25661 |
March | 744.00000 | 21.18354 | 27.95990 | -0.5015 | 12.04486 |
April | 720.00000 | 21.14059 | 32.97755 | -0.4884 | 11.66474 |
May | 744.00000 | 21.57170 | 37.36859 | -1.3857 | 45.91592 |
June | 720.00000 | 21.71063 | 42.09458 | -1.1429 | 34.47775 |
July | 744.00000 | 21.71024 | 43.78455 | -1.1516 | 34.78475 |
August | 744.00000 | 21.70123 | 43.94058 | -1.1519 | 34.92289 |
September | 720.00000 | 21.66018 | 35.69044 | -1.2663 | 40.45732 |
October | 744.00000 | 21.31425 | 31.19439 | -0.4169 | 10.78841 |
November | 720.00000 | 21.25423 | 31.59769 | -0.4796 | 11.58208 |
December | 744.00000 | 21.02409 | 24.08442 | -0.6470 | 15.51595 |
Annual Sum or Average | 8760.00000 | 21.38831 | 34.02523 | -0.8106 | 23.20408 |
Minimum of Months | 672.00000 | 21.02409 | 24.08442 | -1.3857 | 10.78841 |
Maximum of Months | 744.00000 | 21.71063 | 43.94058 | -0.4169 | 45.91592 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.75415 | 30.40003 | -0.6950 | 15.90538 |
February | 672.00000 | 20.77826 | 28.01840 | -0.7035 | 16.37511 |
March | 744.00000 | 20.96659 | 28.21886 | -0.5950 | 13.63792 |
April | 720.00000 | 21.01300 | 33.18609 | -0.5395 | 12.39221 |
May | 744.00000 | 21.52587 | 37.46557 | -1.4172 | 47.34408 |
June | 720.00000 | 21.70927 | 42.16810 | -1.1515 | 34.73115 |
July | 744.00000 | 21.70755 | 43.92848 | -1.1629 | 35.15859 |
August | 744.00000 | 21.68691 | 44.30780 | -1.1872 | 36.25874 |
September | 720.00000 | 21.59988 | 35.89035 | -1.3399 | 43.65962 |
October | 744.00000 | 21.09301 | 31.48877 | -0.5206 | 12.01107 |
November | 720.00000 | 20.88214 | 32.19943 | -0.6321 | 14.30825 |
December | 744.00000 | 20.69429 | 24.49371 | -0.7825 | 18.80321 |
Annual Sum or Average | 8760.00000 | 21.20329 | 34.34859 | -0.8952 | 25.10665 |
Minimum of Months | 672.00000 | 20.69429 | 24.49371 | -1.4172 | 12.01107 |
Maximum of Months | 744.00000 | 21.70927 | 44.30780 | -0.5206 | 47.34408 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.51867 | 30.92721 | -0.3232 | 9.39386 |
February | 672.00000 | 21.44064 | 28.77767 | -0.3819 | 10.57093 |
March | 744.00000 | 21.35422 | 29.27637 | -0.4007 | 10.36726 |
April | 720.00000 | 21.26976 | 33.99751 | -0.4280 | 10.38896 |
May | 744.00000 | 21.59588 | 37.83854 | -1.3956 | 46.30187 |
June | 720.00000 | 21.70169 | 42.33834 | -1.2223 | 37.86441 |
July | 744.00000 | 21.70662 | 43.74559 | -1.2050 | 37.09084 |
August | 744.00000 | 21.70469 | 43.53855 | -1.1864 | 36.46426 |
September | 720.00000 | 21.69350 | 35.85011 | -1.2431 | 39.45373 |
October | 744.00000 | 21.42702 | 32.33919 | -0.3218 | 9.52520 |
November | 720.00000 | 21.51734 | 32.87244 | -0.3059 | 9.21396 |
December | 744.00000 | 21.41304 | 25.58777 | -0.4308 | 11.21134 |
Annual Sum or Average | 8760.00000 | 21.52913 | 34.79007 | -0.7393 | 22.39619 |
Minimum of Months | 672.00000 | 21.26976 | 25.58777 | -1.3956 | 9.21396 |
Maximum of Months | 744.00000 | 21.70662 | 43.74559 | -0.3059 | 46.30187 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.61063 | 29.02544 | -0.0292 | 5.87255 |
February | 672.00000 | 22.58104 | 27.45270 | -0.0484 | 6.00421 |
March | 744.00000 | 22.87751 | 26.30476 | 0.04529 | 5.80552 |
April | 720.00000 | 23.00529 | 30.38953 | 0.11233 | 6.10207 |
May | 744.00000 | 23.44256 | 33.72374 | -0.6078 | 13.49326 |
June | 720.00000 | 23.68049 | 40.63798 | -0.4061 | 8.78264 |
July | 744.00000 | 23.68637 | 43.29116 | -0.3874 | 8.47179 |
August | 744.00000 | 23.62106 | 42.97972 | -0.4238 | 9.20308 |
September | 720.00000 | 23.49964 | 32.79431 | -0.5684 | 12.47032 |
October | 744.00000 | 23.02455 | 28.70309 | 0.11409 | 6.08907 |
November | 720.00000 | 22.76702 | 30.10567 | 0.02906 | 5.81986 |
December | 744.00000 | 22.43978 | 23.83401 | -0.1207 | 6.39646 |
Annual Sum or Average | 8760.00000 | 23.10580 | 32.46636 | -0.1919 | 7.88671 |
Minimum of Months | 672.00000 | 22.43978 | 23.83401 | -0.6078 | 5.80552 |
Maximum of Months | 744.00000 | 23.68637 | 43.29116 | 0.11409 | 13.49326 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.99440 | 28.52494 | 0.09176 | 5.94581 |
February | 672.00000 | 22.97137 | 26.99708 | 0.07439 | 5.96161 |
March | 744.00000 | 23.23129 | 25.81439 | 0.15837 | 6.11128 |
April | 720.00000 | 23.35549 | 29.82279 | 0.22502 | 6.69669 |
May | 744.00000 | 23.66561 | 33.19041 | -0.4985 | 10.69199 |
June | 720.00000 | 23.82414 | 40.10533 | -0.3262 | 7.45740 |
July | 744.00000 | 23.82983 | 42.74118 | -0.3078 | 7.21769 |
August | 744.00000 | 23.77390 | 42.43386 | -0.3419 | 7.74729 |
September | 720.00000 | 23.67609 | 32.31874 | -0.4786 | 10.29237 |
October | 744.00000 | 23.31653 | 28.24722 | 0.20852 | 6.56921 |
November | 720.00000 | 23.13309 | 29.58982 | 0.14431 | 6.12259 |
December | 744.00000 | 22.81440 | 23.46251 | -0.0001 | 6.11016 |
Annual Sum or Average | 8760.00000 | 23.38429 | 31.96676 | -0.0887 | 7.24984 |
Minimum of Months | 672.00000 | 22.81440 | 23.46251 | -0.4985 | 5.94581 |
Maximum of Months | 744.00000 | 23.82983 | 42.74118 | 0.22502 | 10.69199 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 24.18895 | 27.55298 | 1.00300 | 28.08174 |
February | 672.00000 | 24.19042 | 26.09011 | 0.98883 | 27.68322 |
March | 744.00000 | 24.15354 | 25.12750 | 1.01580 | 28.45342 |
April | 720.00000 | 24.15314 | 29.03921 | 1.04868 | 29.81220 |
May | 744.00000 | 24.03360 | 32.42699 | 0.56721 | 15.40693 |
June | 720.00000 | 23.99230 | 39.41203 | 0.71416 | 19.64019 |
July | 744.00000 | 23.99162 | 41.99331 | 0.72570 | 19.96928 |
August | 744.00000 | 23.99239 | 41.50163 | 0.71589 | 19.51831 |
September | 720.00000 | 24.00192 | 31.55111 | 0.59899 | 16.42753 |
October | 744.00000 | 24.12779 | 27.47171 | 1.04205 | 29.43967 |
November | 720.00000 | 24.21311 | 28.64869 | 1.03118 | 29.28155 |
December | 744.00000 | 24.12701 | 23.11316 | 0.92265 | 24.94874 |
Annual Sum or Average | 8760.00000 | 24.09646 | 31.19140 | 0.86367 | 24.02832 |
Minimum of Months | 672.00000 | 23.99162 | 23.11316 | 0.56721 | 15.40693 |
Maximum of Months | 744.00000 | 24.21311 | 41.99331 | 1.04868 | 29.81220 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.15885 | 25.34718 | -0.4583 | 9.52430 |
February | 672.00000 | 21.14179 | 23.53850 | -0.4832 | 10.04592 |
March | 744.00000 | 21.33796 | 22.53353 | -0.4284 | 9.06814 |
April | 720.00000 | 21.31504 | 27.30044 | -0.4036 | 8.67090 |
May | 744.00000 | 22.05028 | 30.47396 | -1.2800 | 39.49583 |
June | 720.00000 | 23.02385 | 36.79403 | -0.8985 | 22.24326 |
July | 744.00000 | 23.11169 | 39.30892 | -0.8515 | 20.49553 |
August | 744.00000 | 22.97599 | 39.18909 | -0.8997 | 22.30165 |
September | 720.00000 | 22.70608 | 28.48664 | -1.0619 | 29.29550 |
October | 744.00000 | 21.70726 | 24.94039 | -0.3144 | 7.40742 |
November | 720.00000 | 21.26713 | 26.60213 | -0.4193 | 8.87132 |
December | 744.00000 | 21.10199 | 19.52208 | -0.5222 | 10.85068 |
Annual Sum or Average | 8760.00000 | 21.91260 | 28.69957 | -0.6696 | 16.56758 |
Minimum of Months | 672.00000 | 21.10199 | 19.52208 | -1.2800 | 7.40742 |
Maximum of Months | 744.00000 | 23.11169 | 39.30892 | -0.3144 | 39.49583 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.94982 | 28.57029 | -0.2694 | 7.01629 |
February | 672.00000 | 21.81511 | 27.01544 | -0.3172 | 7.87806 |
March | 744.00000 | 22.18443 | 26.09551 | -0.2289 | 6.95211 |
April | 720.00000 | 22.02917 | 30.62956 | -0.2393 | 6.72585 |
May | 744.00000 | 23.16481 | 33.09005 | -0.9423 | 24.44752 |
June | 720.00000 | 23.94428 | 38.81366 | -0.6186 | 13.13803 |
July | 744.00000 | 23.96404 | 41.21537 | -0.5942 | 12.51922 |
August | 744.00000 | 23.95763 | 41.08725 | -0.5984 | 12.62857 |
September | 720.00000 | 23.84235 | 30.93931 | -0.7116 | 15.96086 |
October | 744.00000 | 22.91504 | 27.95695 | -0.0368 | 6.06339 |
November | 720.00000 | 22.15052 | 29.71699 | -0.2141 | 6.58665 |
December | 744.00000 | 21.51414 | 23.43284 | -0.4139 | 8.96930 |
Annual Sum or Average | 8760.00000 | 22.79167 | 31.57346 | -0.4328 | 10.76552 |
Minimum of Months | 672.00000 | 21.51414 | 23.43284 | -0.9423 | 6.06339 |
Maximum of Months | 744.00000 | 23.96404 | 41.21537 | -0.0368 | 24.44752 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.75546 | 27.01848 | -0.3203 | 7.90406 |
February | 672.00000 | 21.77265 | 25.22814 | -0.3358 | 8.36493 |
March | 744.00000 | 22.11434 | 24.27382 | -0.2446 | 7.45771 |
April | 720.00000 | 22.15952 | 28.58939 | -0.2057 | 6.89898 |
May | 744.00000 | 23.44950 | 30.61314 | -0.8185 | 20.19432 |
June | 720.00000 | 23.96914 | 36.57101 | -0.5472 | 11.42490 |
July | 744.00000 | 23.97656 | 39.07540 | -0.5274 | 10.99152 |
August | 744.00000 | 23.96512 | 38.84677 | -0.5355 | 11.15815 |
September | 720.00000 | 23.80180 | 28.92445 | -0.6788 | 15.30936 |
October | 744.00000 | 22.75074 | 26.14773 | -0.0709 | 6.46636 |
November | 720.00000 | 22.05849 | 28.00447 | -0.2366 | 7.21250 |
December | 744.00000 | 21.48547 | 21.60778 | -0.4358 | 9.63010 |
Annual Sum or Average | 8760.00000 | 22.77730 | 29.60039 | -0.4137 | 10.26701 |
Minimum of Months | 672.00000 | 21.48547 | 21.60778 | -0.8185 | 6.46636 |
Maximum of Months | 744.00000 | 23.97656 | 39.07540 | -0.0709 | 20.19432 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.90103 | 24.29030 | -0.2955 | 7.40308 |
February | 672.00000 | 21.72866 | 22.73765 | -0.3510 | 8.29978 |
March | 744.00000 | 22.17576 | 21.72704 | -0.2454 | 6.97702 |
April | 720.00000 | 22.26158 | 25.97313 | -0.1993 | 6.53469 |
May | 744.00000 | 23.38711 | 28.45214 | -0.8803 | 22.05320 |
June | 720.00000 | 23.98002 | 34.79222 | -0.6017 | 12.71269 |
July | 744.00000 | 23.98698 | 37.27200 | -0.5792 | 12.15647 |
August | 744.00000 | 23.97944 | 37.15461 | -0.5898 | 12.43823 |
September | 720.00000 | 23.84551 | 26.83853 | -0.7162 | 16.20376 |
October | 744.00000 | 22.83805 | 23.61781 | -0.0717 | 5.91783 |
November | 720.00000 | 22.16774 | 25.34272 | -0.2247 | 6.70451 |
December | 744.00000 | 21.67111 | 18.91662 | -0.3932 | 8.83312 |
Annual Sum or Average | 8760.00000 | 22.83335 | 27.28602 | -0.4296 | 10.53757 |
Minimum of Months | 672.00000 | 21.67111 | 18.91662 | -0.8803 | 5.91783 |
Maximum of Months | 744.00000 | 23.98698 | 37.27200 | -0.0717 | 22.05320 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.159745E+11 | 66874.78 | 20-JAN-13:00 | 466.43 | 0.510557E+11 | 0.00 | 0.670302E+11 | 2.00 | 3.64 | 20-JAN-13:00 | 0.00 | 0.00 |
February | 0.123458E+11 | 62328.57 | 18-FEB-13:30 | 395.70 | 0.392569E+11 | 0.00 | 0.516028E+11 | 1.87 | 3.60 | 18-FEB-13:30 | 0.00 | 0.00 |
March | 0.208962E+11 | 99980.31 | 13-MAR-15:01 | 488.04 | 0.669563E+11 | 0.00 | 0.878525E+11 | 2.09 | 4.08 | 15-MAR-15:01 | 0.00 | 0.00 |
April | 0.164631E+11 | 77466.80 | 19-APR-15:01 | 459.37 | 0.499759E+11 | 0.00 | 0.664390E+11 | 2.00 | 4.05 | 19-APR-18:01 | 0.00 | 0.00 |
May | 0.566133E+11 | 109590.24 | 16-MAY-15:01 | 698.91 | 0.176085E+12 | 0.00 | 0.232698E+12 | 2.94 | 4.07 | 05-MAY-18:01 | 0.00 | 0.00 |
June | 0.153864E+12 | 188824.38 | 26-JUN-18:03 | 720.00 | 0.489889E+12 | 0.00 | 0.643753E+12 | 3.16 | 4.20 | 20-JUN-18:03 | 0.00 | 0.00 |
July | 0.169656E+12 | 157402.85 | 16-JUL-15:03 | 744.00 | 0.547315E+12 | 0.00 | 0.716971E+12 | 3.19 | 4.51 | 31-JUL-18:02 | 0.00 | 0.00 |
August | 0.155696E+12 | 173209.66 | 16-AUG-15:03 | 744.00 | 0.502882E+12 | 0.00 | 0.658578E+12 | 3.19 | 4.25 | 05-AUG-15:02 | 0.00 | 0.00 |
September | 0.113440E+12 | 139792.79 | 10-SEP-15:03 | 702.87 | 0.367704E+12 | 0.00 | 0.481144E+12 | 3.11 | 4.15 | 03-SEP-08:62 | 0.00 | 0.00 |
October | 0.327886E+11 | 116406.04 | 11-OCT-15:01 | 547.71 | 0.106283E+12 | 0.00 | 0.139072E+12 | 2.35 | 4.06 | 10-OCT-18:01 | 0.00 | 0.00 |
November | 0.187724E+11 | 71476.68 | 07-NOV-14:00 | 506.71 | 0.604194E+11 | 0.00 | 0.791918E+11 | 2.24 | 3.83 | 07-NOV-16:01 | 0.00 | 0.00 |
December | 0.120940E+11 | 62390.51 | 02-DEC-13:00 | 369.45 | 0.381482E+11 | 0.00 | 0.502422E+11 | 1.58 | 3.48 | 02-DEC-13:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.778605E+12 | 6843.20 | 0.249597E+13 | 0.00 | 0.327458E+13 | 2.48 | 0.00 | 0.00 | ||||
Minimum of Months | 0.120940E+11 | 62328.57 | 369.45 | 0.381482E+11 | 0.00 | 0.502422E+11 | 1.58 | 3.48 | 0.00 | 0.00 | ||
Maximum of Months | 0.169656E+12 | 188824.38 | 744.00 | 0.547315E+12 | 0.00 | 0.716971E+12 | 3.19 | 4.51 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.853778E+11 | 0.00 | 703.81 | 250398.16 | 05-JAN-09:03 | 0.00 | 55.56 | 79.83 | 0.29 | 0.00 | 0.06 | 0.45 | 05-JAN-09:03 |
February | 0.897892E+11 | 0.00 | 637.42 | 195522.72 | 12-FEB-09:01 | 0.00 | 54.53 | 79.94 | 0.33 | 0.00 | 0.07 | 0.35 | 12-FEB-09:01 |
March | 0.626044E+11 | 0.00 | 608.38 | 225221.65 | 22-MAR-15:02 | 0.00 | 52.90 | 74.72 | 0.22 | 0.00 | 0.04 | 0.40 | 22-MAR-15:02 |
April | 0.486240E+11 | 0.00 | 574.77 | 199246.34 | 22-APR-15:01 | 0.00 | 51.58 | 73.58 | 0.18 | 0.00 | 0.03 | 0.35 | 22-APR-15:01 |
May | 0.147433E+11 | 0.00 | 301.77 | 180671.09 | 09-MAY-02:00 | 0.00 | 41.96 | 56.09 | 0.04 | 0.00 | 0.01 | 0.32 | 09-MAY-02:00 |
June | 0.538031E+09 | 0.00 | 21.46 | 81016.82 | 09-JUN-04:15 | 0.00 | 47.00 | 47.97 | 0.00 | 0.00 | 0.00 | 0.14 | 09-JUN-04:15 |
July | 0.623990E+09 | 0.00 | 20.89 | 84856.35 | 06-JUL-08:04 | 0.00 | 45.57 | 46.69 | 0.00 | 0.00 | 0.00 | 0.15 | 06-JUL-08:04 |
August | 0.176570E+09 | 0.00 | 19.79 | 35800.02 | 30-AUG-15:04 | 0.00 | 56.81 | 57.45 | 0.00 | 0.00 | 0.00 | 0.06 | 30-AUG-15:04 |
September | 0.359773E+10 | 0.00 | 113.07 | 147613.39 | 22-SEP-08:61 | 0.00 | 53.28 | 57.82 | 0.01 | 0.00 | 0.00 | 0.26 | 22-SEP-08:61 |
October | 0.509108E+11 | 0.00 | 520.15 | 213986.43 | 02-OCT-15:01 | 0.00 | 51.93 | 71.03 | 0.17 | 0.00 | 0.03 | 0.38 | 02-OCT-15:01 |
November | 0.679984E+11 | 0.00 | 641.92 | 185325.39 | 29-NOV-09:03 | 0.00 | 55.28 | 77.89 | 0.25 | 0.00 | 0.05 | 0.33 | 29-NOV-09:03 |
December | 0.138685E+12 | 0.00 | 705.31 | 304895.02 | 21-DEC-09:03 | 0.00 | 54.41 | 80.01 | 0.42 | 0.00 | 0.09 | 0.54 | 21-DEC-09:03 |
Annual Sum or Average | 0.563669E+12 | 0.00 | 4868.74 | 0.00 | 51.71 | 66.84 | 0.16 | 0.00 | 0.03 | ||||
Minimum of Months | 0.176570E+09 | 0.00 | 19.79 | 35800.02 | 0.00 | 41.96 | 46.69 | 0.00 | 0.00 | 0.00 | 0.06 | ||
Maximum of Months | 0.138685E+12 | 0.00 | 705.31 | 304895.02 | 0.00 | 56.81 | 80.01 | 0.42 | 0.00 | 0.09 | 0.54 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.641639E+10 | 0.00 | 178.63 | 0.641639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 133320.62 | 20-JAN-13:00 | 133320.62 | 20-JAN-13:00 | 0.00 | 0.00 | 0.00 |
February | 0.362902E+10 | 0.00 | 129.27 | 0.362902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119864.70 | 18-FEB-13:00 | 119864.70 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 |
March | 0.197927E+11 | 0.00 | 217.48 | 0.197927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167258.36 | 14-MAR-13:00 | 167258.36 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.205285E+11 | 0.00 | 219.32 | 0.205285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118861.67 | 19-APR-10:50 | 118861.67 | 19-APR-10:50 | 0.00 | 0.00 | 0.00 |
May | 0.929566E+11 | 0.00 | 351.36 | 0.929566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 202869.33 | 31-MAY-18:10 | 202869.33 | 31-MAY-18:10 | 0.00 | 0.00 | 0.00 |
June | 0.298236E+12 | 0.00 | 664.71 | 0.295328E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 289028.98 | 26-JUN-18:20 | 289028.98 | 26-JUN-18:20 | 0.00 | 0.00 | 0.00 |
July | 0.340417E+12 | 0.00 | 710.07 | 0.324639E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 300667.68 | 30-JUL-10:35 | 267017.71 | 17-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.305016E+12 | 0.00 | 690.28 | 0.299543E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 273039.11 | 16-AUG-18:20 | 273039.11 | 16-AUG-18:20 | 0.00 | 0.00 | 0.00 |
September | 0.213776E+12 | 0.00 | 540.32 | 0.213776E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 240190.25 | 12-SEP-18:20 | 240190.25 | 12-SEP-18:20 | 0.00 | 0.00 | 0.00 |
October | 0.363658E+11 | 0.00 | 241.20 | 0.363658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 185638.83 | 11-OCT-14:10 | 185638.83 | 11-OCT-14:10 | 0.00 | 0.00 | 0.00 |
November | 0.121905E+11 | 0.00 | 189.05 | 0.121905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 147510.52 | 06-NOV-13:00 | 147510.52 | 06-NOV-13:00 | 0.00 | 0.00 | 0.00 |
December | 0.825937E+10 | 0.00 | 162.99 | 0.825937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 124827.19 | 02-DEC-13:00 | 124827.19 | 02-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135758E+13 | 0.00 | 4294.70 | 0.133343E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.362902E+10 | 0.00 | 129.27 | 0.362902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 118861.67 | 118861.67 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.340417E+12 | 0.00 | 710.07 | 0.324639E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 300667.68 | 289028.98 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.806531E+09 | 0.00 | 29.56 | 0.806531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18772.93 | 20-JAN-14:00 | 18772.93 | 20-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.433446E+09 | 0.00 | 16.78 | 0.433446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15786.89 | 18-FEB-14:00 | 15786.89 | 18-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.270200E+10 | 0.00 | 84.83 | 0.270200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22830.69 | 14-MAR-13:00 | 22830.69 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.323869E+10 | 0.00 | 97.94 | 0.323869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20853.73 | 20-APR-13:00 | 20853.73 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.144894E+11 | 0.00 | 301.25 | 0.144894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26345.92 | 17-MAY-14:00 | 26345.92 | 17-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 0.425535E+11 | 0.00 | 663.67 | 0.413960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34231.28 | 21-JUN-17:40 | 31796.36 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.503092E+11 | 0.00 | 705.67 | 0.462727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38435.62 | 30-JUL-16:00 | 30561.74 | 16-JUL-13:00 | 0.00 | 0.00 | 0.00 |
August | 0.438094E+11 | 0.00 | 691.50 | 0.417923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38985.53 | 05-AUG-14:40 | 30600.89 | 16-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.303321E+11 | 0.00 | 522.67 | 0.303321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28363.15 | 10-SEP-13:50 | 28363.15 | 10-SEP-13:50 | 0.00 | 0.00 | 0.00 |
October | 0.512374E+10 | 0.00 | 132.60 | 0.512374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24648.65 | 11-OCT-14:00 | 24648.65 | 11-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.173918E+10 | 0.00 | 48.02 | 0.173918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20791.64 | 07-NOV-15:00 | 20791.64 | 07-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.121720E+10 | 0.00 | 37.61 | 0.121720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20812.74 | 02-DEC-15:00 | 20812.74 | 02-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196754E+12 | 0.00 | 3332.09 | 0.189543E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.433446E+09 | 0.00 | 16.78 | 0.433446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15786.89 | 15786.89 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.503092E+11 | 0.00 | 705.67 | 0.462727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38985.53 | 31796.36 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.113400E+10 | 0.00 | 178.24 | 0.113400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19048.09 | 23-JAN-16:01 | 19048.09 | 23-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.123643E+10 | 0.00 | 166.01 | 0.123643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18944.40 | 18-FEB-16:01 | 18944.40 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.250797E+10 | 0.00 | 273.12 | 0.250793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19805.06 | 13-MAR-15:01 | 19805.06 | 13-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.162844E+10 | 0.00 | 232.28 | 0.157247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19499.53 | 27-APR-15:01 | 19499.53 | 27-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.406570E+10 | 0.00 | 547.59 | 0.346338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20527.32 | 16-MAY-15:01 | 20527.32 | 16-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.956443E+10 | 0.00 | 676.98 | 0.739393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20551.20 | 05-JUN-15:01 | 20551.20 | 05-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.923971E+10 | 0.00 | 700.00 | 0.671270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20552.79 | 10-JUL-18:01 | 20552.79 | 10-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.938295E+10 | 0.00 | 696.51 | 0.663985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20550.96 | 19-AUG-15:01 | 20550.96 | 19-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.728139E+10 | 0.00 | 638.27 | 0.631041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20547.29 | 12-SEP-15:01 | 20547.29 | 12-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.348693E+10 | 0.00 | 376.45 | 0.344814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20339.00 | 11-OCT-15:01 | 20339.00 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.160409E+10 | 0.00 | 226.37 | 0.159852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19432.56 | 05-NOV-15:01 | 19432.56 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.687830E+09 | 0.00 | 117.94 | 0.687830E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18895.61 | 02-DEC-16:01 | 18895.61 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.518199E+11 | 0.00 | 4829.75 | 0.427056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.687830E+09 | 0.00 | 117.94 | 0.687830E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18895.61 | 18895.61 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.956443E+10 | 0.00 | 700.00 | 0.739393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20552.79 | 20552.79 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.185326E+09 | 0.00 | 37.92 | 0.185326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18562.38 | 23-JAN-16:01 | 18562.38 | 23-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.286584E+09 | 0.00 | 50.06 | 0.286584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18460.42 | 18-FEB-16:01 | 18460.42 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.122427E+10 | 0.00 | 174.08 | 0.122422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19298.92 | 14-MAR-15:01 | 19298.92 | 14-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.102419E+10 | 0.00 | 166.90 | 0.984519E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19002.66 | 27-APR-15:01 | 19002.66 | 27-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.357367E+10 | 0.00 | 513.75 | 0.301247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20003.71 | 16-MAY-15:01 | 20003.71 | 16-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.922813E+10 | 0.00 | 673.03 | 0.715173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20027.15 | 05-JUN-15:01 | 20027.15 | 05-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.878975E+10 | 0.00 | 694.68 | 0.638518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20028.98 | 10-JUL-18:01 | 20028.98 | 10-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.809709E+10 | 0.00 | 682.96 | 0.561719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20027.15 | 19-AUG-15:01 | 20027.15 | 19-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.542478E+10 | 0.00 | 599.13 | 0.457591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20023.53 | 04-SEP-15:01 | 20023.53 | 04-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.164463E+10 | 0.00 | 230.93 | 0.162965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19819.31 | 11-OCT-15:01 | 19819.31 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.333990E+09 | 0.00 | 72.59 | 0.333117E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18935.73 | 05-NOV-15:01 | 18935.73 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 67976446.43 | 0.00 | 19.84 | 67976446.43 | 0.00 | 0.00 | 0.00 | 0.00 | 18412.76 | 02-DEC-16:01 | 18412.76 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.398804E+11 | 0.00 | 3915.88 | 0.314539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 67976446.43 | 0.00 | 19.84 | 67976446.43 | 0.00 | 0.00 | 0.00 | 0.00 | 18412.76 | 18412.76 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.922813E+10 | 0.00 | 694.68 | 0.715173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20028.98 | 20028.98 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.269976E+11 | 0.00 | 305.34 | 0.269976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66400.73 | 20-JAN-12:40 | 66400.73 | 20-JAN-12:40 | 0.00 | 0.00 | 0.00 |
February | 0.199380E+11 | 0.00 | 242.87 | 0.199380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63706.59 | 18-FEB-13:00 | 63706.59 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 |
March | 0.189611E+11 | 0.00 | 256.21 | 0.189611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58437.64 | 11-MAR-13:00 | 58437.64 | 11-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.449156E+10 | 0.00 | 110.27 | 0.449156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33346.81 | 08-APR-13:10 | 33346.81 | 08-APR-13:10 | 0.00 | 0.00 | 0.00 |
May | 0.949923E+10 | 0.00 | 330.78 | 0.864950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22928.25 | 16-MAY-13:30 | 22928.25 | 16-MAY-13:30 | 0.00 | 0.00 | 0.00 |
June | 0.288177E+11 | 0.00 | 591.32 | 0.225120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32259.01 | 14-JUN-13:30 | 32259.01 | 14-JUN-13:30 | 0.00 | 0.00 | 0.00 |
July | 0.322192E+11 | 0.00 | 631.24 | 0.245359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36478.26 | 23-JUL-13:00 | 32612.79 | 18-JUL-13:00 | 0.00 | 0.00 | 0.00 |
August | 0.388565E+11 | 0.00 | 646.13 | 0.305920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45975.42 | 31-AUG-12:50 | 45975.42 | 31-AUG-12:50 | 0.00 | 0.00 | 0.00 |
September | 0.398308E+11 | 0.00 | 599.79 | 0.379223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60492.80 | 28-SEP-13:00 | 60492.80 | 28-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.311800E+11 | 0.00 | 350.33 | 0.311800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62661.19 | 10-OCT-12:30 | 62661.19 | 10-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 0.265403E+11 | 0.00 | 304.07 | 0.265403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67142.64 | 07-NOV-12:10 | 67142.64 | 07-NOV-12:10 | 0.00 | 0.00 | 0.00 |
December | 0.165208E+11 | 0.00 | 191.23 | 0.165208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59815.12 | 17-DEC-12:10 | 59815.12 | 17-DEC-12:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293853E+12 | 0.00 | 4559.57 | 0.268841E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.449156E+10 | 0.00 | 110.27 | 0.449156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22928.25 | 22928.25 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.398308E+11 | 0.00 | 646.13 | 0.379223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67142.64 | 67142.64 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.454559E+09 | 0.00 | 42.95 | 0.454559E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79156.50 | 21-JAN-09:01 | 79156.50 | 21-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.516639E+09 | 0.00 | 40.34 | 0.516639E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78921.20 | 19-FEB-09:01 | 78921.20 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.403605E+10 | 0.00 | 179.29 | 0.399581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86348.73 | 14-MAR-15:01 | 86348.73 | 14-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.583022E+10 | 0.00 | 237.61 | 0.517849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85038.75 | 27-APR-15:01 | 85038.75 | 27-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.251196E+11 | 0.00 | 497.76 | 0.215376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96479.95 | 17-MAY-15:01 | 96479.95 | 17-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.517809E+11 | 0.00 | 552.83 | 0.421432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97286.34 | 25-JUN-08:61 | 97286.34 | 25-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.548152E+11 | 0.00 | 587.94 | 0.433601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97308.90 | 08-JUL-18:01 | 97308.90 | 08-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.458608E+11 | 0.00 | 545.81 | 0.333547E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97294.42 | 25-AUG-18:01 | 97294.42 | 25-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.297250E+11 | 0.00 | 494.31 | 0.262326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97227.42 | 11-SEP-15:01 | 97227.42 | 11-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.598537E+10 | 0.00 | 261.87 | 0.578554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90260.98 | 11-OCT-15:01 | 90260.98 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.125726E+10 | 0.00 | 80.22 | 0.120093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79540.98 | 09-NOV-19:02 | 79540.98 | 09-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.351799E+09 | 0.00 | 28.47 | 0.351799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62312.80 | 02-DEC-09:01 | 62312.80 | 02-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.225733E+12 | 0.00 | 3549.40 | 0.184112E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.351799E+09 | 0.00 | 28.47 | 0.351799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62312.80 | 62312.80 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.548152E+11 | 0.00 | 587.94 | 0.433601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97308.90 | 97308.90 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.110883E+10 | 0.00 | 163.18 | 0.110883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16524.63 | 23-JAN-16:01 | 16524.63 | 23-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.137763E+10 | 0.00 | 184.81 | 0.137763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16434.98 | 18-FEB-16:01 | 16434.98 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.268361E+10 | 0.00 | 294.99 | 0.268344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17180.48 | 13-MAR-15:01 | 17180.48 | 13-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.197442E+10 | 0.00 | 261.08 | 0.189673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16915.78 | 27-APR-15:01 | 16915.78 | 27-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.448210E+10 | 0.00 | 584.69 | 0.387081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17808.19 | 16-MAY-15:01 | 17808.19 | 16-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.101327E+11 | 0.00 | 703.73 | 0.800017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17827.76 | 05-JUN-15:01 | 17827.76 | 05-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.103623E+11 | 0.00 | 722.88 | 0.790240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17828.27 | 12-JUL-18:01 | 17828.27 | 12-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.104300E+11 | 0.00 | 723.97 | 0.778304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17827.20 | 19-AUG-15:01 | 17827.20 | 19-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.771289E+10 | 0.00 | 658.68 | 0.681472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17823.98 | 12-SEP-15:01 | 17823.98 | 12-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.336435E+10 | 0.00 | 378.39 | 0.331865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17642.99 | 11-OCT-15:01 | 17642.99 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.154772E+10 | 0.00 | 219.98 | 0.154170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16857.65 | 05-NOV-15:01 | 16857.65 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.694272E+09 | 0.00 | 124.16 | 0.694272E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16391.24 | 02-DEC-16:01 | 16391.24 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.558708E+11 | 0.00 | 5020.55 | 0.469924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.694272E+09 | 0.00 | 124.16 | 0.694272E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16391.24 | 16391.24 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.104300E+11 | 0.00 | 723.97 | 0.800017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17828.27 | 17828.27 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.190865E+09 | 0.00 | 39.08 | 0.190865E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15559.45 | 20-JAN-09:02 | 15559.45 | 20-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.389735E+09 | 0.00 | 66.44 | 0.389735E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15724.67 | 23-FEB-09:01 | 15724.67 | 23-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.128611E+10 | 0.00 | 193.50 | 0.128608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16759.84 | 13-MAR-15:01 | 16759.84 | 13-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.131061E+10 | 0.00 | 205.03 | 0.124901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16491.40 | 27-APR-15:01 | 16491.40 | 27-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.395477E+10 | 0.00 | 551.35 | 0.338849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17372.40 | 16-MAY-15:01 | 17372.40 | 16-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.977520E+10 | 0.00 | 703.36 | 0.773497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17391.49 | 05-JUN-15:01 | 17391.49 | 05-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.989426E+10 | 0.00 | 721.34 | 0.751461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17392.10 | 12-JUL-18:01 | 17392.10 | 12-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.910830E+10 | 0.00 | 720.20 | 0.656901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17392.15 | 19-AUG-15:01 | 17392.15 | 19-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.578243E+10 | 0.00 | 635.83 | 0.495197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17388.16 | 12-SEP-15:01 | 17388.16 | 12-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.141310E+10 | 0.00 | 231.35 | 0.138493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17211.78 | 11-OCT-15:01 | 17211.78 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.372143E+09 | 0.00 | 70.18 | 0.371104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15732.61 | 19-NOV-09:01 | 15732.61 | 19-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 0.109773E+09 | 0.00 | 24.84 | 0.109773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15149.08 | 02-DEC-09:01 | 15149.08 | 02-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.435873E+11 | 0.00 | 4162.50 | 0.351405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.109773E+09 | 0.00 | 24.84 | 0.109773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15149.08 | 15149.08 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.989426E+10 | 0.00 | 721.34 | 0.773497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17392.15 | 17392.15 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.242682E+09 | 0.00 | 127.15 | 0.242682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5063.13 | 23-JAN-16:01 | 5063.13 | 23-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.276497E+09 | 0.00 | 124.65 | 0.276497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5035.82 | 18-FEB-16:01 | 5035.82 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.584255E+09 | 0.00 | 217.68 | 0.584242E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5264.37 | 13-MAR-15:01 | 5264.37 | 13-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.394339E+09 | 0.00 | 187.45 | 0.384921E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5183.12 | 27-APR-15:01 | 5183.12 | 27-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.917912E+09 | 0.00 | 446.67 | 0.803994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5456.48 | 16-MAY-15:01 | 5456.48 | 16-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.238848E+10 | 0.00 | 673.49 | 0.185463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5463.04 | 13-JUN-08:61 | 5463.04 | 13-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.227233E+10 | 0.00 | 695.45 | 0.164519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5463.11 | 10-JUL-18:01 | 5463.11 | 10-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.230676E+10 | 0.00 | 690.15 | 0.164512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5462.68 | 19-AUG-15:01 | 5462.68 | 19-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.169291E+10 | 0.00 | 613.89 | 0.145899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5461.74 | 12-SEP-15:01 | 5461.74 | 12-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.763726E+09 | 0.00 | 292.29 | 0.758363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5406.33 | 11-OCT-15:01 | 5406.33 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.352372E+09 | 0.00 | 167.13 | 0.352118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5165.42 | 05-NOV-15:01 | 5165.42 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.148083E+09 | 0.00 | 91.75 | 0.148083E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5022.63 | 02-DEC-16:01 | 5022.63 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123403E+11 | 0.00 | 4327.75 | 0.101548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.148083E+09 | 0.00 | 91.75 | 0.148083E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5022.63 | 5022.63 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.238848E+10 | 0.00 | 695.45 | 0.185463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5463.11 | 5463.11 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 36221302.76 | 0.00 | 25.24 | 36221302.76 | 0.00 | 0.00 | 0.00 | 0.00 | 4922.07 | 23-JAN-16:01 | 4922.07 | 23-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 59542315.78 | 0.00 | 34.68 | 59542315.78 | 0.00 | 0.00 | 0.00 | 0.00 | 4894.89 | 18-FEB-16:01 | 4894.89 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.270018E+09 | 0.00 | 128.07 | 0.270000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5117.34 | 14-MAR-15:01 | 5117.34 | 14-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.242124E+09 | 0.00 | 132.69 | 0.235643E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5038.70 | 27-APR-15:01 | 5038.70 | 27-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.790235E+09 | 0.00 | 410.58 | 0.686530E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5304.33 | 16-MAY-15:01 | 5304.33 | 16-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.229745E+10 | 0.00 | 670.93 | 0.178442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5310.91 | 13-JUN-08:61 | 5310.91 | 13-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.215202E+10 | 0.00 | 691.33 | 0.155580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5310.91 | 10-JUL-18:01 | 5310.91 | 10-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.196566E+10 | 0.00 | 675.37 | 0.137700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5310.50 | 19-AUG-15:01 | 5310.50 | 19-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.121530E+10 | 0.00 | 551.99 | 0.102127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5309.58 | 04-SEP-15:01 | 5309.58 | 04-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.331358E+09 | 0.00 | 153.57 | 0.330562E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5255.31 | 11-OCT-15:01 | 5255.31 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 67371733.31 | 0.00 | 48.14 | 67360029.67 | 0.00 | 0.00 | 0.00 | 0.00 | 5021.05 | 05-NOV-15:01 | 5021.05 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 14271410.42 | 0.00 | 14.91 | 14271410.42 | 0.00 | 0.00 | 0.00 | 0.00 | 4882.35 | 02-DEC-16:01 | 4882.35 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.944158E+10 | 0.00 | 3537.51 | 0.743862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 14271410.42 | 0.00 | 14.91 | 14271410.42 | 0.00 | 0.00 | 0.00 | 0.00 | 4882.35 | 4882.35 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.229745E+10 | 0.00 | 691.33 | 0.178442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5310.91 | 5310.91 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.681128E+10 | 0.00 | 354.98 | 0.680484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21626.78 | 23-JAN-16:01 | 21626.78 | 23-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.546330E+10 | 0.00 | 304.32 | 0.546290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21505.89 | 18-FEB-16:01 | 21505.89 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.567808E+10 | 0.00 | 349.74 | 0.567245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22484.07 | 13-MAR-15:01 | 22484.07 | 13-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.273625E+10 | 0.00 | 262.46 | 0.264051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22132.52 | 27-APR-15:01 | 22132.52 | 27-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.468945E+10 | 0.00 | 522.54 | 0.403990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23298.90 | 16-MAY-15:01 | 23298.90 | 16-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.103829E+11 | 0.00 | 665.80 | 0.771375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23317.87 | 30-JUN-08:61 | 23317.87 | 30-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.113264E+11 | 0.00 | 689.35 | 0.811148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23319.82 | 13-JUL-18:01 | 23319.82 | 13-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.126454E+11 | 0.00 | 695.59 | 0.934246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23316.53 | 10-AUG-18:01 | 23316.53 | 10-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.114714E+11 | 0.00 | 645.90 | 0.103343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23310.81 | 11-SEP-15:01 | 23310.81 | 11-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.808582E+10 | 0.00 | 439.00 | 0.797706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23087.71 | 11-OCT-15:01 | 23087.71 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.710749E+10 | 0.00 | 389.10 | 0.707653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22063.65 | 05-NOV-15:01 | 22063.65 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.490644E+10 | 0.00 | 261.61 | 0.490644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21451.53 | 02-DEC-16:01 | 21451.53 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.913042E+11 | 0.00 | 5580.39 | 0.800826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.273625E+10 | 0.00 | 261.61 | 0.264051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21451.53 | 21451.53 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.126454E+11 | 0.00 | 695.59 | 0.103343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23319.82 | 23319.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1420.50 | 1169.35 | 251.15 | 1600.23 | 638.19 | 0.00 | 0.00 | 0.00 |
February | 1344.14 | 1068.74 | 275.40 | 1500.80 | 666.75 | 0.00 | 0.00 | 0.00 |
March | 1009.67 | 667.29 | 342.38 | 1138.44 | 531.15 | 0.00 | 0.00 | 0.00 |
April | 661.13 | 273.51 | 387.62 | 682.78 | 476.26 | 0.00 | 0.00 | 0.00 |
May | 600.77 | 115.53 | 485.24 | 682.28 | 284.04 | 0.00 | 0.00 | 0.00 |
June | 546.20 | 98.60 | 447.60 | 772.95 | 154.18 | 0.00 | 0.00 | 0.00 |
July | 564.16 | 96.11 | 468.05 | 802.65 | 138.49 | 0.00 | 0.00 | 0.00 |
August | 717.82 | 295.32 | 422.50 | 1023.42 | 161.07 | 0.00 | 0.00 | 0.00 |
September | 942.92 | 530.01 | 412.91 | 1259.15 | 248.88 | 0.00 | 0.00 | 0.00 |
October | 1113.04 | 788.63 | 324.41 | 1327.21 | 518.70 | 0.00 | 0.00 | 0.00 |
November | 1364.27 | 1088.18 | 276.09 | 1576.68 | 599.83 | 0.00 | 0.00 | 0.00 |
December | 1301.97 | 1053.98 | 247.99 | 1435.72 | 723.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 963.39 | 601.11 | 362.28 | 1148.16 | 427.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 546.20 | 96.11 | 247.99 | 682.28 | 138.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1420.50 | 1169.35 | 485.24 | 1600.23 | 723.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4000.02 | 3292.81 | 707.21 | 4482.43 | 1838.57 | 0.00 | 0.00 | 0.00 |
February | 3785.00 | 3009.49 | 775.51 | 4203.09 | 1913.62 | 0.00 | 0.00 | 0.00 |
March | 2843.17 | 1879.05 | 964.11 | 3188.56 | 1531.31 | 0.00 | 0.00 | 0.00 |
April | 1861.71 | 770.19 | 1091.52 | 1913.27 | 1377.74 | 0.00 | 0.00 | 0.00 |
May | 1691.72 | 325.32 | 1366.40 | 1932.82 | 805.51 | 0.00 | 0.00 | 0.00 |
June | 1538.07 | 277.65 | 1260.42 | 2196.80 | 423.65 | 0.00 | 0.00 | 0.00 |
July | 1588.64 | 270.64 | 1318.00 | 2276.34 | 381.05 | 0.00 | 0.00 | 0.00 |
August | 2021.34 | 831.60 | 1189.74 | 2887.46 | 447.34 | 0.00 | 0.00 | 0.00 |
September | 2655.19 | 1492.48 | 1162.71 | 3541.24 | 700.43 | 0.00 | 0.00 | 0.00 |
October | 3134.24 | 2220.72 | 913.53 | 3721.65 | 1486.37 | 0.00 | 0.00 | 0.00 |
November | 3841.68 | 3064.24 | 777.45 | 4418.25 | 1723.88 | 0.00 | 0.00 | 0.00 |
December | 3666.25 | 2967.93 | 698.32 | 4021.85 | 2079.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2712.84 | 1692.69 | 1020.15 | 3226.35 | 1221.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1538.07 | 270.64 | 698.32 | 1913.27 | 381.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4000.02 | 3292.81 | 1366.40 | 4482.43 | 2079.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5196.26 | 4277.55 | 918.71 | 5910.67 | 2480.51 | 0.00 | 0.00 | 0.00 |
February | 4916.93 | 3909.50 | 1007.43 | 5551.01 | 2585.80 | 0.00 | 0.00 | 0.00 |
March | 3693.44 | 2441.00 | 1252.44 | 4210.68 | 2088.95 | 0.00 | 0.00 | 0.00 |
April | 2418.46 | 1000.52 | 1417.94 | 2521.72 | 1911.43 | 0.00 | 0.00 | 0.00 |
May | 2197.65 | 422.61 | 1775.03 | 2533.14 | 1120.26 | 0.00 | 0.00 | 0.00 |
June | 1998.04 | 360.68 | 1637.36 | 2901.66 | 570.86 | 0.00 | 0.00 | 0.00 |
July | 2063.73 | 351.57 | 1712.16 | 3008.10 | 512.51 | 0.00 | 0.00 | 0.00 |
August | 2625.83 | 1080.29 | 1545.53 | 3819.62 | 593.20 | 0.00 | 0.00 | 0.00 |
September | 3449.25 | 1938.81 | 1510.43 | 4679.21 | 932.30 | 0.00 | 0.00 | 0.00 |
October | 4071.56 | 2884.84 | 1186.73 | 4908.65 | 2017.44 | 0.00 | 0.00 | 0.00 |
November | 4990.57 | 3980.62 | 1009.95 | 5827.11 | 2333.45 | 0.00 | 0.00 | 0.00 |
December | 4762.67 | 3855.52 | 907.16 | 5301.68 | 2810.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3524.13 | 2198.90 | 1325.23 | 4256.95 | 1657.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1998.04 | 351.57 | 907.16 | 2521.72 | 512.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5196.26 | 4277.55 | 1775.03 | 5910.67 | 2810.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 280.86 | 231.20 | 49.66 | 322.20 | 123.02 | 0.00 | 0.00 | 0.00 |
February | 265.76 | 211.31 | 54.45 | 301.02 | 130.59 | 0.00 | 0.00 | 0.00 |
March | 199.63 | 131.94 | 67.69 | 228.48 | 102.97 | 0.00 | 0.00 | 0.00 |
April | 130.72 | 54.08 | 76.64 | 137.16 | 93.03 | 0.00 | 0.00 | 0.00 |
May | 118.78 | 22.84 | 95.94 | 138.54 | 52.08 | 0.00 | 0.00 | 0.00 |
June | 107.99 | 19.49 | 88.50 | 160.18 | 23.11 | 0.00 | 0.00 | 0.00 |
July | 111.55 | 19.00 | 92.54 | 166.77 | 19.66 | 0.00 | 0.00 | 0.00 |
August | 141.93 | 58.39 | 83.54 | 209.58 | 23.46 | 0.00 | 0.00 | 0.00 |
September | 186.43 | 104.79 | 81.64 | 255.42 | 40.78 | 0.00 | 0.00 | 0.00 |
October | 220.07 | 155.92 | 64.14 | 266.91 | 98.18 | 0.00 | 0.00 | 0.00 |
November | 269.74 | 215.15 | 54.59 | 317.11 | 115.18 | 0.00 | 0.00 | 0.00 |
December | 257.42 | 208.39 | 49.03 | 287.84 | 142.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.48 | 118.85 | 71.63 | 232.20 | 80.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 107.99 | 19.00 | 49.03 | 137.16 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 280.86 | 231.20 | 95.94 | 322.20 | 142.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 181.76 | 115.20 | 66.57 | 168.55 | 252.90 | 0.00 | 0.00 | 0.00 |
February | 219.58 | 136.21 | 83.37 | 201.06 | 260.06 | 0.00 | 0.00 | 0.00 |
March | 256.07 | 141.05 | 115.01 | 253.26 | 195.03 | 0.00 | 0.00 | 0.00 |
April | 241.52 | 102.31 | 139.21 | 230.63 | 169.76 | 0.00 | 0.00 | 0.00 |
May | 295.30 | 104.29 | 191.01 | 340.33 | 94.61 | 0.00 | 0.00 | 0.00 |
June | 360.52 | 173.32 | 187.20 | 497.97 | 42.90 | 0.00 | 0.00 | 0.00 |
July | 293.42 | 107.13 | 186.29 | 410.73 | 36.56 | 0.00 | 0.00 | 0.00 |
August | 307.25 | 151.84 | 155.42 | 419.39 | 43.23 | 0.00 | 0.00 | 0.00 |
September | 273.38 | 131.52 | 141.85 | 354.80 | 76.71 | 0.00 | 0.00 | 0.00 |
October | 228.93 | 130.85 | 98.08 | 245.88 | 188.34 | 0.00 | 0.00 | 0.00 |
November | 187.98 | 114.17 | 73.81 | 180.22 | 227.72 | 0.00 | 0.00 | 0.00 |
December | 151.61 | 89.52 | 62.09 | 127.21 | 289.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 249.85 | 124.63 | 125.22 | 286.20 | 155.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 151.61 | 89.52 | 62.09 | 127.21 | 36.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 360.52 | 173.32 | 191.01 | 497.97 | 289.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.20 | 0.00 | 29.20 | 6.48 | 139.48 | 0.00 | 0.00 | 0.00 |
February | 36.70 | 0.00 | 36.70 | 7.74 | 144.27 | 0.00 | 0.00 | 0.00 |
March | 49.95 | 0.00 | 49.95 | 23.80 | 107.57 | 0.00 | 0.00 | 0.00 |
April | 62.79 | 0.41 | 62.38 | 36.17 | 91.50 | 0.00 | 0.00 | 0.00 |
May | 85.78 | 2.88 | 82.90 | 82.02 | 48.01 | 0.00 | 0.00 | 0.00 |
June | 94.04 | 10.52 | 83.53 | 131.49 | 21.21 | 0.00 | 0.00 | 0.00 |
July | 89.20 | 6.09 | 83.11 | 127.54 | 18.50 | 0.00 | 0.00 | 0.00 |
August | 71.02 | 1.92 | 69.10 | 96.89 | 22.35 | 0.00 | 0.00 | 0.00 |
September | 59.46 | 0.05 | 59.42 | 71.68 | 40.63 | 0.00 | 0.00 | 0.00 |
October | 42.54 | 0.00 | 42.54 | 25.41 | 101.04 | 0.00 | 0.00 | 0.00 |
November | 32.30 | 0.00 | 32.30 | 10.17 | 124.42 | 0.00 | 0.00 | 0.00 |
December | 27.32 | 0.00 | 27.32 | 5.34 | 160.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.80 | 1.83 | 54.97 | 52.31 | 84.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.32 | 0.00 | 27.32 | 5.34 | 18.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.04 | 10.52 | 83.53 | 131.49 | 160.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 181.76 | 115.20 | 66.57 | 175.93 | 246.77 | 0.00 | 0.00 | 0.00 |
February | 219.58 | 136.21 | 83.37 | 208.67 | 254.96 | 0.00 | 0.00 | 0.00 |
March | 256.07 | 141.05 | 115.01 | 259.02 | 192.33 | 0.00 | 0.00 | 0.00 |
April | 241.52 | 102.31 | 139.21 | 233.98 | 168.45 | 0.00 | 0.00 | 0.00 |
May | 295.30 | 104.29 | 191.01 | 341.96 | 94.15 | 0.00 | 0.00 | 0.00 |
June | 360.52 | 173.32 | 187.20 | 498.61 | 42.66 | 0.00 | 0.00 | 0.00 |
July | 293.42 | 107.13 | 186.29 | 411.55 | 36.31 | 0.00 | 0.00 | 0.00 |
August | 307.25 | 151.84 | 155.42 | 421.69 | 42.59 | 0.00 | 0.00 | 0.00 |
September | 273.38 | 131.52 | 141.85 | 358.72 | 75.29 | 0.00 | 0.00 | 0.00 |
October | 228.93 | 130.85 | 98.08 | 251.56 | 185.26 | 0.00 | 0.00 | 0.00 |
November | 187.98 | 114.17 | 73.81 | 187.49 | 222.66 | 0.00 | 0.00 | 0.00 |
December | 151.61 | 89.52 | 62.09 | 133.36 | 284.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 249.85 | 124.63 | 125.22 | 290.56 | 153.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 151.61 | 89.52 | 62.09 | 133.36 | 36.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 360.52 | 173.32 | 191.01 | 498.61 | 284.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 224.64 | 184.92 | 39.72 | 253.91 | 106.63 | 0.00 | 0.00 | 0.00 |
February | 212.57 | 169.01 | 43.55 | 237.66 | 109.81 | 0.00 | 0.00 | 0.00 |
March | 159.67 | 105.53 | 54.14 | 181.16 | 85.69 | 0.00 | 0.00 | 0.00 |
April | 104.55 | 43.25 | 61.30 | 109.32 | 76.60 | 0.00 | 0.00 | 0.00 |
May | 95.01 | 18.27 | 76.74 | 109.42 | 46.09 | 0.00 | 0.00 | 0.00 |
June | 86.38 | 15.59 | 70.79 | 127.13 | 22.60 | 0.00 | 0.00 | 0.00 |
July | 89.22 | 15.20 | 74.02 | 131.85 | 20.07 | 0.00 | 0.00 | 0.00 |
August | 113.52 | 46.70 | 66.82 | 166.19 | 23.56 | 0.00 | 0.00 | 0.00 |
September | 149.12 | 83.82 | 65.30 | 202.43 | 38.48 | 0.00 | 0.00 | 0.00 |
October | 176.02 | 124.71 | 51.30 | 211.58 | 84.62 | 0.00 | 0.00 | 0.00 |
November | 215.75 | 172.09 | 43.66 | 250.80 | 99.52 | 0.00 | 0.00 | 0.00 |
December | 205.90 | 166.68 | 39.22 | 227.15 | 119.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.35 | 95.06 | 57.29 | 183.74 | 69.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.38 | 15.20 | 39.22 | 109.32 | 20.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 224.64 | 184.92 | 76.74 | 253.91 | 119.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.36 | 0.00 | 23.36 | 5.20 | 113.68 | 0.00 | 0.00 | 0.00 |
February | 29.36 | 0.00 | 29.36 | 6.49 | 117.09 | 0.00 | 0.00 | 0.00 |
March | 39.97 | 0.00 | 39.96 | 20.14 | 86.69 | 0.00 | 0.00 | 0.00 |
April | 50.24 | 0.33 | 49.91 | 30.03 | 74.26 | 0.00 | 0.00 | 0.00 |
May | 68.63 | 2.30 | 66.33 | 68.87 | 37.72 | 0.00 | 0.00 | 0.00 |
June | 75.25 | 8.41 | 66.83 | 110.34 | 15.39 | 0.00 | 0.00 | 0.00 |
July | 71.37 | 4.87 | 66.50 | 106.54 | 13.41 | 0.00 | 0.00 | 0.00 |
August | 56.82 | 1.54 | 55.28 | 82.18 | 16.21 | 0.00 | 0.00 | 0.00 |
September | 47.58 | 0.04 | 47.54 | 61.21 | 30.69 | 0.00 | 0.00 | 0.00 |
October | 34.04 | 0.00 | 34.04 | 21.99 | 80.97 | 0.00 | 0.00 | 0.00 |
November | 25.84 | 0.00 | 25.84 | 8.43 | 100.92 | 0.00 | 0.00 | 0.00 |
December | 21.86 | 0.00 | 21.86 | 4.14 | 132.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.44 | 1.46 | 43.98 | 44.01 | 68.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.86 | 0.00 | 21.86 | 4.14 | 13.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.25 | 8.41 | 66.83 | 110.34 | 132.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.16 | 104.08 | 66.09 | 148.04 | 248.63 | 0.00 | 0.00 | 0.00 |
February | 228.12 | 144.37 | 83.74 | 210.32 | 258.92 | 0.00 | 0.00 | 0.00 |
March | 274.79 | 160.40 | 114.40 | 274.12 | 191.53 | 0.00 | 0.00 | 0.00 |
April | 280.52 | 136.63 | 143.89 | 277.31 | 166.14 | 0.00 | 0.00 | 0.00 |
May | 328.86 | 137.67 | 191.19 | 377.77 | 89.28 | 0.00 | 0.00 | 0.00 |
June | 400.16 | 210.02 | 190.14 | 546.71 | 39.14 | 0.00 | 0.00 | 0.00 |
July | 363.22 | 172.60 | 190.62 | 502.80 | 34.46 | 0.00 | 0.00 | 0.00 |
August | 367.26 | 202.34 | 164.92 | 500.15 | 41.74 | 0.00 | 0.00 | 0.00 |
September | 306.08 | 166.38 | 139.70 | 393.79 | 72.69 | 0.00 | 0.00 | 0.00 |
October | 221.49 | 121.47 | 100.02 | 231.52 | 184.68 | 0.00 | 0.00 | 0.00 |
November | 171.88 | 96.86 | 75.02 | 158.03 | 226.22 | 0.00 | 0.00 | 0.00 |
December | 149.07 | 85.90 | 63.17 | 122.08 | 287.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 271.96 | 144.81 | 127.15 | 312.37 | 152.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 149.07 | 85.90 | 63.17 | 122.08 | 34.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 400.16 | 210.02 | 191.19 | 546.71 | 287.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 280.86 | 231.20 | 49.66 | 321.63 | 122.46 | 0.00 | 0.00 | 0.00 |
February | 265.76 | 211.31 | 54.45 | 299.94 | 129.98 | 0.00 | 0.00 | 0.00 |
March | 199.63 | 131.94 | 67.69 | 226.84 | 102.43 | 0.00 | 0.00 | 0.00 |
April | 130.72 | 54.08 | 76.64 | 135.47 | 92.86 | 0.00 | 0.00 | 0.00 |
May | 118.78 | 22.84 | 95.94 | 137.10 | 51.87 | 0.00 | 0.00 | 0.00 |
June | 107.99 | 19.49 | 88.50 | 158.77 | 22.66 | 0.00 | 0.00 | 0.00 |
July | 111.55 | 19.00 | 92.54 | 165.21 | 19.50 | 0.00 | 0.00 | 0.00 |
August | 141.93 | 58.39 | 83.54 | 207.98 | 23.31 | 0.00 | 0.00 | 0.00 |
September | 186.43 | 104.79 | 81.64 | 254.29 | 40.49 | 0.00 | 0.00 | 0.00 |
October | 220.07 | 155.92 | 64.14 | 266.17 | 97.67 | 0.00 | 0.00 | 0.00 |
November | 269.74 | 215.15 | 54.59 | 316.72 | 114.56 | 0.00 | 0.00 | 0.00 |
December | 257.42 | 208.39 | 49.03 | 287.32 | 141.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.48 | 118.85 | 71.63 | 231.06 | 79.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 107.99 | 19.00 | 49.03 | 135.47 | 19.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 280.86 | 231.20 | 95.94 | 321.63 | 141.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.20 | 0.00 | 29.20 | 6.12 | 138.82 | 0.00 | 0.00 | 0.00 |
February | 36.70 | 0.00 | 36.70 | 6.87 | 143.85 | 0.00 | 0.00 | 0.00 |
March | 49.95 | 0.00 | 49.95 | 22.28 | 107.47 | 0.00 | 0.00 | 0.00 |
April | 62.79 | 0.41 | 62.38 | 34.34 | 91.53 | 0.00 | 0.00 | 0.00 |
May | 85.78 | 2.88 | 82.90 | 80.34 | 47.81 | 0.00 | 0.00 | 0.00 |
June | 94.04 | 10.52 | 83.53 | 130.11 | 20.85 | 0.00 | 0.00 | 0.00 |
July | 89.20 | 6.09 | 83.11 | 125.94 | 18.39 | 0.00 | 0.00 | 0.00 |
August | 71.02 | 1.92 | 69.10 | 95.12 | 22.20 | 0.00 | 0.00 | 0.00 |
September | 59.46 | 0.05 | 59.42 | 70.31 | 40.49 | 0.00 | 0.00 | 0.00 |
October | 42.54 | 0.00 | 42.54 | 24.34 | 100.57 | 0.00 | 0.00 | 0.00 |
November | 32.30 | 0.00 | 32.30 | 9.55 | 123.51 | 0.00 | 0.00 | 0.00 |
December | 27.32 | 0.00 | 27.32 | 4.96 | 160.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.80 | 1.83 | 54.97 | 51.11 | 84.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.32 | 0.00 | 27.32 | 4.96 | 18.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.04 | 10.52 | 83.53 | 130.11 | 160.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.16 | 104.08 | 66.09 | 153.23 | 239.43 | 0.00 | 0.00 | 0.00 |
February | 228.12 | 144.37 | 83.74 | 215.75 | 251.36 | 0.00 | 0.00 | 0.00 |
March | 274.79 | 160.40 | 114.40 | 279.06 | 188.44 | 0.00 | 0.00 | 0.00 |
April | 280.52 | 136.63 | 143.89 | 280.11 | 164.75 | 0.00 | 0.00 | 0.00 |
May | 328.86 | 137.67 | 191.19 | 379.14 | 88.83 | 0.00 | 0.00 | 0.00 |
June | 400.16 | 210.02 | 190.14 | 547.43 | 38.98 | 0.00 | 0.00 | 0.00 |
July | 363.22 | 172.60 | 190.62 | 503.62 | 34.26 | 0.00 | 0.00 | 0.00 |
August | 367.26 | 202.34 | 164.92 | 502.25 | 41.12 | 0.00 | 0.00 | 0.00 |
September | 306.08 | 166.38 | 139.70 | 397.18 | 71.30 | 0.00 | 0.00 | 0.00 |
October | 221.49 | 121.47 | 100.02 | 236.51 | 181.40 | 0.00 | 0.00 | 0.00 |
November | 171.88 | 96.86 | 75.02 | 163.68 | 218.89 | 0.00 | 0.00 | 0.00 |
December | 149.07 | 85.90 | 63.17 | 126.65 | 280.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 271.96 | 144.81 | 127.15 | 315.86 | 149.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 149.07 | 85.90 | 63.17 | 126.65 | 34.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 400.16 | 210.02 | 191.19 | 547.43 | 280.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.98 | 0.00 | 36.98 | 5.92 | 195.38 | 0.00 | 0.00 | 0.00 |
February | 46.48 | 0.00 | 46.48 | 7.19 | 198.79 | 0.00 | 0.00 | 0.00 |
March | 63.26 | 0.00 | 63.26 | 27.14 | 149.65 | 0.00 | 0.00 | 0.00 |
April | 79.52 | 0.52 | 79.00 | 43.90 | 127.13 | 0.00 | 0.00 | 0.00 |
May | 108.63 | 3.64 | 104.99 | 100.65 | 70.10 | 0.00 | 0.00 | 0.00 |
June | 119.10 | 13.32 | 105.78 | 162.05 | 34.76 | 0.00 | 0.00 | 0.00 |
July | 112.96 | 7.71 | 105.25 | 156.24 | 31.99 | 0.00 | 0.00 | 0.00 |
August | 89.94 | 2.43 | 87.51 | 118.03 | 38.25 | 0.00 | 0.00 | 0.00 |
September | 75.31 | 0.06 | 75.25 | 86.37 | 64.13 | 0.00 | 0.00 | 0.00 |
October | 53.88 | 0.00 | 53.88 | 28.28 | 145.19 | 0.00 | 0.00 | 0.00 |
November | 40.90 | 0.00 | 40.90 | 10.00 | 174.96 | 0.00 | 0.00 | 0.00 |
December | 34.60 | 0.00 | 34.60 | 5.02 | 221.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 71.93 | 2.31 | 69.61 | 62.88 | 120.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.60 | 0.00 | 34.60 | 5.02 | 31.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.10 | 13.32 | 105.78 | 162.05 | 221.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.63 | 0.00 | 13.63 | 2.18 | 72.02 | 0.00 | 0.00 | 0.00 |
February | 17.13 | 0.00 | 17.13 | 2.65 | 73.28 | 0.00 | 0.00 | 0.00 |
March | 23.32 | 0.00 | 23.32 | 10.01 | 55.17 | 0.00 | 0.00 | 0.00 |
April | 29.31 | 0.19 | 29.12 | 16.18 | 46.87 | 0.00 | 0.00 | 0.00 |
May | 40.05 | 1.34 | 38.70 | 37.11 | 25.84 | 0.00 | 0.00 | 0.00 |
June | 43.91 | 4.91 | 39.00 | 59.74 | 12.82 | 0.00 | 0.00 | 0.00 |
July | 41.64 | 2.84 | 38.80 | 57.60 | 11.79 | 0.00 | 0.00 | 0.00 |
August | 33.16 | 0.90 | 32.26 | 43.51 | 14.10 | 0.00 | 0.00 | 0.00 |
September | 27.76 | 0.02 | 27.74 | 31.84 | 23.64 | 0.00 | 0.00 | 0.00 |
October | 19.86 | 0.00 | 19.86 | 10.43 | 53.52 | 0.00 | 0.00 | 0.00 |
November | 15.08 | 0.00 | 15.08 | 3.68 | 64.50 | 0.00 | 0.00 | 0.00 |
December | 12.75 | 0.00 | 12.75 | 1.85 | 81.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.52 | 0.85 | 25.66 | 23.18 | 44.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.75 | 0.00 | 12.75 | 1.85 | 11.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.91 | 4.91 | 39.00 | 59.74 | 81.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.05 | 107.88 | 23.17 | 150.49 | 60.87 | 0.00 | 0.00 | 0.00 |
February | 124.00 | 98.60 | 25.41 | 140.76 | 64.43 | 0.00 | 0.00 | 0.00 |
March | 93.15 | 61.56 | 31.59 | 106.58 | 51.96 | 0.00 | 0.00 | 0.00 |
April | 60.99 | 25.23 | 35.76 | 63.96 | 47.12 | 0.00 | 0.00 | 0.00 |
May | 55.42 | 10.66 | 44.77 | 64.07 | 27.92 | 0.00 | 0.00 | 0.00 |
June | 50.39 | 9.10 | 41.29 | 73.52 | 14.10 | 0.00 | 0.00 | 0.00 |
July | 52.05 | 8.87 | 43.18 | 76.27 | 12.61 | 0.00 | 0.00 | 0.00 |
August | 66.22 | 27.24 | 38.98 | 96.64 | 14.61 | 0.00 | 0.00 | 0.00 |
September | 86.99 | 48.90 | 38.09 | 118.25 | 23.26 | 0.00 | 0.00 | 0.00 |
October | 102.68 | 72.75 | 29.93 | 124.15 | 50.91 | 0.00 | 0.00 | 0.00 |
November | 125.86 | 100.39 | 25.47 | 148.17 | 57.61 | 0.00 | 0.00 | 0.00 |
December | 120.11 | 97.23 | 22.88 | 134.36 | 69.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.88 | 55.46 | 33.42 | 107.91 | 41.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.39 | 8.87 | 22.88 | 63.96 | 12.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 131.05 | 107.88 | 44.77 | 150.49 | 69.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 355.69 | 292.80 | 62.89 | 408.47 | 165.22 | 0.00 | 0.00 | 0.00 |
February | 336.57 | 267.61 | 68.96 | 382.04 | 174.88 | 0.00 | 0.00 | 0.00 |
March | 252.82 | 167.09 | 85.73 | 289.28 | 141.03 | 0.00 | 0.00 | 0.00 |
April | 165.55 | 68.49 | 97.06 | 173.59 | 127.89 | 0.00 | 0.00 | 0.00 |
May | 150.43 | 28.93 | 121.50 | 173.90 | 75.79 | 0.00 | 0.00 | 0.00 |
June | 136.77 | 24.69 | 112.08 | 199.55 | 38.26 | 0.00 | 0.00 | 0.00 |
July | 141.26 | 24.07 | 117.20 | 207.02 | 34.21 | 0.00 | 0.00 | 0.00 |
August | 179.74 | 73.95 | 105.79 | 262.29 | 39.66 | 0.00 | 0.00 | 0.00 |
September | 236.10 | 132.71 | 103.39 | 320.96 | 63.13 | 0.00 | 0.00 | 0.00 |
October | 278.70 | 197.47 | 81.23 | 336.96 | 138.17 | 0.00 | 0.00 | 0.00 |
November | 341.61 | 272.48 | 69.13 | 402.17 | 156.37 | 0.00 | 0.00 | 0.00 |
December | 326.01 | 263.91 | 62.10 | 364.69 | 189.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 241.23 | 150.52 | 90.71 | 292.89 | 111.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.77 | 24.07 | 62.10 | 173.59 | 34.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 355.69 | 292.80 | 121.50 | 408.47 | 189.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 280.86 | 231.20 | 49.66 | 321.73 | 121.99 | 0.00 | 0.00 | 0.00 |
February | 265.76 | 211.31 | 54.45 | 299.84 | 130.21 | 0.00 | 0.00 | 0.00 |
March | 199.63 | 131.94 | 67.69 | 227.53 | 102.28 | 0.00 | 0.00 | 0.00 |
April | 130.72 | 54.08 | 76.64 | 136.46 | 92.34 | 0.00 | 0.00 | 0.00 |
May | 118.78 | 22.84 | 95.94 | 137.91 | 51.46 | 0.00 | 0.00 | 0.00 |
June | 107.99 | 19.49 | 88.50 | 159.38 | 22.48 | 0.00 | 0.00 | 0.00 |
July | 111.55 | 19.00 | 92.54 | 166.09 | 19.01 | 0.00 | 0.00 | 0.00 |
August | 141.93 | 58.39 | 83.54 | 208.55 | 22.77 | 0.00 | 0.00 | 0.00 |
September | 186.43 | 104.79 | 81.64 | 254.49 | 39.84 | 0.00 | 0.00 | 0.00 |
October | 220.07 | 155.92 | 64.14 | 266.19 | 97.09 | 0.00 | 0.00 | 0.00 |
November | 269.74 | 215.15 | 54.59 | 316.25 | 114.30 | 0.00 | 0.00 | 0.00 |
December | 257.42 | 208.39 | 49.03 | 286.92 | 141.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.48 | 118.85 | 71.63 | 231.38 | 79.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 107.99 | 19.00 | 49.03 | 136.46 | 19.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 280.86 | 231.20 | 95.94 | 321.73 | 141.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 181.76 | 115.20 | 66.57 | 168.30 | 250.09 | 0.00 | 0.00 | 0.00 |
February | 219.58 | 136.21 | 83.37 | 200.15 | 258.80 | 0.00 | 0.00 | 0.00 |
March | 256.07 | 141.05 | 115.01 | 252.17 | 193.46 | 0.00 | 0.00 | 0.00 |
April | 241.52 | 102.31 | 139.21 | 229.49 | 168.31 | 0.00 | 0.00 | 0.00 |
May | 295.30 | 104.29 | 191.01 | 338.83 | 93.35 | 0.00 | 0.00 | 0.00 |
June | 360.52 | 173.32 | 187.20 | 495.87 | 41.74 | 0.00 | 0.00 | 0.00 |
July | 293.42 | 107.13 | 186.29 | 409.12 | 35.35 | 0.00 | 0.00 | 0.00 |
August | 307.25 | 151.84 | 155.42 | 417.60 | 41.96 | 0.00 | 0.00 | 0.00 |
September | 273.38 | 131.52 | 141.85 | 353.73 | 74.88 | 0.00 | 0.00 | 0.00 |
October | 228.93 | 130.85 | 98.08 | 245.21 | 185.99 | 0.00 | 0.00 | 0.00 |
November | 187.98 | 114.17 | 73.81 | 179.65 | 225.54 | 0.00 | 0.00 | 0.00 |
December | 151.61 | 89.52 | 62.09 | 126.94 | 287.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 249.85 | 124.63 | 125.22 | 285.12 | 154.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 151.61 | 89.52 | 62.09 | 126.94 | 35.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 360.52 | 173.32 | 191.01 | 495.87 | 287.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.20 | 0.00 | 29.20 | 6.86 | 137.58 | 0.00 | 0.00 | 0.00 |
February | 36.70 | 0.00 | 36.70 | 7.99 | 143.19 | 0.00 | 0.00 | 0.00 |
March | 49.95 | 0.00 | 49.95 | 24.04 | 106.58 | 0.00 | 0.00 | 0.00 |
April | 62.79 | 0.41 | 62.38 | 36.15 | 90.68 | 0.00 | 0.00 | 0.00 |
May | 85.78 | 2.88 | 82.90 | 81.76 | 47.37 | 0.00 | 0.00 | 0.00 |
June | 94.04 | 10.52 | 83.53 | 130.97 | 20.70 | 0.00 | 0.00 | 0.00 |
July | 89.20 | 6.09 | 83.11 | 127.15 | 17.95 | 0.00 | 0.00 | 0.00 |
August | 71.02 | 1.92 | 69.10 | 96.52 | 21.70 | 0.00 | 0.00 | 0.00 |
September | 59.46 | 0.05 | 59.42 | 71.83 | 39.57 | 0.00 | 0.00 | 0.00 |
October | 42.54 | 0.00 | 42.54 | 25.90 | 99.64 | 0.00 | 0.00 | 0.00 |
November | 32.30 | 0.00 | 32.30 | 10.50 | 122.81 | 0.00 | 0.00 | 0.00 |
December | 27.32 | 0.00 | 27.32 | 5.62 | 159.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.80 | 1.83 | 54.97 | 52.36 | 83.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.32 | 0.00 | 27.32 | 5.62 | 17.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.04 | 10.52 | 83.53 | 130.97 | 159.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 181.76 | 115.20 | 66.57 | 176.59 | 243.85 | 0.00 | 0.00 | 0.00 |
February | 219.58 | 136.21 | 83.37 | 208.56 | 253.54 | 0.00 | 0.00 | 0.00 |
March | 256.07 | 141.05 | 115.01 | 258.44 | 190.58 | 0.00 | 0.00 | 0.00 |
April | 241.52 | 102.31 | 139.21 | 233.11 | 166.90 | 0.00 | 0.00 | 0.00 |
May | 295.30 | 104.29 | 191.01 | 340.59 | 92.83 | 0.00 | 0.00 | 0.00 |
June | 360.52 | 173.32 | 187.20 | 496.54 | 41.50 | 0.00 | 0.00 | 0.00 |
July | 293.42 | 107.13 | 186.29 | 409.97 | 35.09 | 0.00 | 0.00 | 0.00 |
August | 307.25 | 151.84 | 155.42 | 420.00 | 41.27 | 0.00 | 0.00 | 0.00 |
September | 273.38 | 131.52 | 141.85 | 357.97 | 73.27 | 0.00 | 0.00 | 0.00 |
October | 228.93 | 130.85 | 98.08 | 251.66 | 182.48 | 0.00 | 0.00 | 0.00 |
November | 187.98 | 114.17 | 73.81 | 187.77 | 220.14 | 0.00 | 0.00 | 0.00 |
December | 151.61 | 89.52 | 62.09 | 133.64 | 282.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 249.85 | 124.63 | 125.22 | 289.91 | 151.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 151.61 | 89.52 | 62.09 | 133.64 | 35.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 360.52 | 173.32 | 191.01 | 496.54 | 282.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 411.90 | 339.08 | 72.83 | 463.58 | 185.75 | 0.00 | 0.00 | 0.00 |
February | 389.76 | 309.90 | 79.86 | 432.55 | 197.11 | 0.00 | 0.00 | 0.00 |
March | 292.78 | 193.50 | 99.28 | 329.52 | 153.37 | 0.00 | 0.00 | 0.00 |
April | 191.71 | 79.31 | 112.40 | 197.96 | 137.60 | 0.00 | 0.00 | 0.00 |
May | 174.21 | 33.50 | 140.71 | 203.07 | 75.18 | 0.00 | 0.00 | 0.00 |
June | 158.38 | 28.59 | 129.79 | 237.77 | 31.31 | 0.00 | 0.00 | 0.00 |
July | 163.59 | 27.87 | 135.72 | 246.49 | 26.80 | 0.00 | 0.00 | 0.00 |
August | 208.15 | 85.63 | 122.51 | 307.66 | 32.44 | 0.00 | 0.00 | 0.00 |
September | 273.42 | 153.69 | 119.73 | 372.62 | 58.51 | 0.00 | 0.00 | 0.00 |
October | 322.75 | 228.68 | 94.07 | 386.92 | 146.19 | 0.00 | 0.00 | 0.00 |
November | 395.60 | 315.54 | 80.06 | 456.94 | 173.95 | 0.00 | 0.00 | 0.00 |
December | 377.53 | 305.62 | 71.91 | 412.19 | 216.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 279.36 | 174.31 | 105.05 | 336.72 | 119.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 158.38 | 27.87 | 71.91 | 197.96 | 26.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 411.90 | 339.08 | 140.71 | 463.58 | 216.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 204.38 | 0.00 | 204.38 | 33.26 | 1093.05 | 0.00 | 0.00 | 0.00 |
February | 256.88 | 0.00 | 256.88 | 39.68 | 1128.06 | 0.00 | 0.00 | 0.00 |
March | 349.64 | 0.02 | 349.63 | 145.60 | 857.59 | 0.00 | 0.00 | 0.00 |
April | 439.52 | 2.88 | 436.64 | 226.61 | 747.73 | 0.00 | 0.00 | 0.00 |
May | 600.41 | 20.14 | 580.28 | 540.25 | 401.97 | 0.00 | 0.00 | 0.00 |
June | 658.28 | 73.61 | 584.67 | 895.04 | 193.21 | 0.00 | 0.00 | 0.00 |
July | 624.37 | 42.62 | 581.75 | 863.99 | 178.35 | 0.00 | 0.00 | 0.00 |
August | 497.11 | 13.45 | 483.66 | 658.16 | 210.44 | 0.00 | 0.00 | 0.00 |
September | 416.23 | 0.33 | 415.90 | 487.24 | 349.59 | 0.00 | 0.00 | 0.00 |
October | 297.79 | 0.00 | 297.79 | 162.56 | 808.46 | 0.00 | 0.00 | 0.00 |
November | 226.06 | 0.00 | 226.06 | 56.09 | 985.75 | 0.00 | 0.00 | 0.00 |
December | 191.22 | 0.00 | 191.22 | 26.32 | 1259.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 397.56 | 12.79 | 384.77 | 346.29 | 682.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 191.22 | 0.00 | 191.22 | 26.32 | 178.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 658.28 | 73.61 | 584.67 | 895.04 | 1259.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 204.38 | 0.00 | 204.38 | 29.48 | 1127.22 | 0.00 | 0.00 | 0.00 |
February | 256.88 | 0.00 | 256.88 | 35.35 | 1163.26 | 0.00 | 0.00 | 0.00 |
March | 349.64 | 0.02 | 349.63 | 136.50 | 885.76 | 0.00 | 0.00 | 0.00 |
April | 439.52 | 2.88 | 436.64 | 214.95 | 773.64 | 0.00 | 0.00 | 0.00 |
May | 600.41 | 20.14 | 580.28 | 524.77 | 412.32 | 0.00 | 0.00 | 0.00 |
June | 658.28 | 73.61 | 584.67 | 881.16 | 198.91 | 0.00 | 0.00 | 0.00 |
July | 624.37 | 42.62 | 581.75 | 850.34 | 184.36 | 0.00 | 0.00 | 0.00 |
August | 497.11 | 13.45 | 483.66 | 645.21 | 217.35 | 0.00 | 0.00 | 0.00 |
September | 416.23 | 0.33 | 415.90 | 475.79 | 359.64 | 0.00 | 0.00 | 0.00 |
October | 297.79 | 0.00 | 297.79 | 154.97 | 831.46 | 0.00 | 0.00 | 0.00 |
November | 226.06 | 0.00 | 226.06 | 51.45 | 1017.55 | 0.00 | 0.00 | 0.00 |
December | 191.22 | 0.00 | 191.22 | 23.20 | 1295.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 397.56 | 12.79 | 384.77 | 336.95 | 703.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 191.22 | 0.00 | 191.22 | 23.20 | 184.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 658.28 | 73.61 | 584.67 | 881.16 | 1295.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.20 | 0.00 | 29.20 | 7.69 | 145.63 | 0.00 | 0.00 | 0.00 |
February | 36.70 | 0.00 | 36.70 | 8.40 | 153.53 | 0.00 | 0.00 | 0.00 |
March | 49.95 | 0.00 | 49.95 | 26.67 | 116.68 | 0.00 | 0.00 | 0.00 |
April | 62.79 | 0.41 | 62.38 | 40.37 | 102.28 | 0.00 | 0.00 | 0.00 |
May | 85.78 | 2.88 | 82.90 | 95.73 | 55.92 | 0.00 | 0.00 | 0.00 |
June | 94.04 | 10.52 | 83.53 | 151.52 | 27.86 | 0.00 | 0.00 | 0.00 |
July | 89.20 | 6.09 | 83.11 | 146.92 | 25.71 | 0.00 | 0.00 | 0.00 |
August | 71.02 | 1.92 | 69.10 | 115.67 | 29.06 | 0.00 | 0.00 | 0.00 |
September | 59.46 | 0.05 | 59.42 | 86.90 | 46.35 | 0.00 | 0.00 | 0.00 |
October | 42.54 | 0.00 | 42.54 | 30.86 | 107.69 | 0.00 | 0.00 | 0.00 |
November | 32.30 | 0.00 | 32.30 | 12.14 | 131.25 | 0.00 | 0.00 | 0.00 |
December | 27.32 | 0.00 | 27.32 | 5.73 | 171.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.80 | 1.83 | 54.97 | 61.01 | 92.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.32 | 0.00 | 27.32 | 5.73 | 25.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.04 | 10.52 | 83.53 | 151.52 | 171.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 340.30 | 208.14 | 132.16 | 318.33 | 506.93 | 0.00 | 0.00 | 0.00 |
February | 456.20 | 288.73 | 167.48 | 441.79 | 542.02 | 0.00 | 0.00 | 0.00 |
March | 549.55 | 320.77 | 228.78 | 579.54 | 413.69 | 0.00 | 0.00 | 0.00 |
April | 560.99 | 273.23 | 287.76 | 584.84 | 371.94 | 0.00 | 0.00 | 0.00 |
May | 657.67 | 275.33 | 382.35 | 816.00 | 207.91 | 0.00 | 0.00 | 0.00 |
June | 800.26 | 420.00 | 380.26 | 1173.62 | 104.47 | 0.00 | 0.00 | 0.00 |
July | 726.38 | 345.17 | 381.22 | 1085.07 | 96.41 | 0.00 | 0.00 | 0.00 |
August | 734.48 | 404.66 | 329.82 | 1081.16 | 108.30 | 0.00 | 0.00 | 0.00 |
September | 612.12 | 332.73 | 279.39 | 859.54 | 167.55 | 0.00 | 0.00 | 0.00 |
October | 442.95 | 242.93 | 200.02 | 502.31 | 391.30 | 0.00 | 0.00 | 0.00 |
November | 343.73 | 193.71 | 150.02 | 341.16 | 468.66 | 0.00 | 0.00 | 0.00 |
December | 298.11 | 171.79 | 126.33 | 258.92 | 604.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 543.89 | 289.61 | 254.28 | 671.30 | 330.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 298.11 | 171.79 | 126.33 | 258.92 | 96.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 800.26 | 420.00 | 382.35 | 1173.62 | 604.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 280.86 | 231.20 | 49.66 | 331.95 | 127.33 | 0.00 | 0.00 | 0.00 |
February | 265.76 | 211.31 | 54.45 | 308.74 | 138.14 | 0.00 | 0.00 | 0.00 |
March | 199.63 | 131.94 | 67.69 | 236.61 | 110.99 | 0.00 | 0.00 | 0.00 |
April | 130.72 | 54.08 | 76.64 | 143.90 | 102.97 | 0.00 | 0.00 | 0.00 |
May | 118.78 | 22.84 | 95.94 | 153.55 | 59.65 | 0.00 | 0.00 | 0.00 |
June | 107.99 | 19.49 | 88.50 | 180.41 | 29.90 | 0.00 | 0.00 | 0.00 |
July | 111.55 | 19.00 | 92.54 | 186.53 | 26.91 | 0.00 | 0.00 | 0.00 |
August | 141.93 | 58.39 | 83.54 | 229.59 | 29.73 | 0.00 | 0.00 | 0.00 |
September | 186.43 | 104.79 | 81.64 | 273.42 | 46.21 | 0.00 | 0.00 | 0.00 |
October | 220.07 | 155.92 | 64.14 | 278.30 | 103.69 | 0.00 | 0.00 | 0.00 |
November | 269.74 | 215.15 | 54.59 | 326.67 | 120.23 | 0.00 | 0.00 | 0.00 |
December | 257.42 | 208.39 | 49.03 | 293.64 | 150.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.48 | 118.85 | 71.63 | 244.91 | 86.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 107.99 | 19.00 | 49.03 | 143.90 | 26.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 280.86 | 231.20 | 95.94 | 331.95 | 150.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.98 | 0.00 | 36.98 | 5.20 | 195.60 | 0.00 | 0.00 | 0.00 |
February | 46.48 | 0.00 | 46.48 | 6.01 | 200.89 | 0.00 | 0.00 | 0.00 |
March | 63.26 | 0.00 | 63.26 | 24.89 | 150.44 | 0.00 | 0.00 | 0.00 |
April | 79.52 | 0.52 | 79.00 | 40.75 | 129.50 | 0.00 | 0.00 | 0.00 |
May | 108.63 | 3.64 | 104.99 | 95.55 | 72.63 | 0.00 | 0.00 | 0.00 |
June | 119.10 | 13.32 | 105.78 | 158.18 | 36.09 | 0.00 | 0.00 | 0.00 |
July | 112.96 | 7.71 | 105.25 | 152.62 | 33.40 | 0.00 | 0.00 | 0.00 |
August | 89.94 | 2.43 | 87.51 | 114.62 | 39.75 | 0.00 | 0.00 | 0.00 |
September | 75.31 | 0.06 | 75.25 | 83.70 | 65.22 | 0.00 | 0.00 | 0.00 |
October | 53.88 | 0.00 | 53.88 | 26.38 | 145.47 | 0.00 | 0.00 | 0.00 |
November | 40.90 | 0.00 | 40.90 | 8.60 | 176.14 | 0.00 | 0.00 | 0.00 |
December | 34.60 | 0.00 | 34.60 | 4.20 | 223.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 71.93 | 2.31 | 69.61 | 60.36 | 121.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.60 | 0.00 | 34.60 | 4.20 | 33.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.10 | 13.32 | 105.78 | 158.18 | 223.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.08 | 0.00 | 33.08 | 4.66 | 174.98 | 0.00 | 0.00 | 0.00 |
February | 41.58 | 0.00 | 41.58 | 5.38 | 179.74 | 0.00 | 0.00 | 0.00 |
March | 56.60 | 0.00 | 56.60 | 22.27 | 134.60 | 0.00 | 0.00 | 0.00 |
April | 71.15 | 0.47 | 70.68 | 36.46 | 115.86 | 0.00 | 0.00 | 0.00 |
May | 97.19 | 3.26 | 93.93 | 85.49 | 64.98 | 0.00 | 0.00 | 0.00 |
June | 106.56 | 11.92 | 94.64 | 141.53 | 32.29 | 0.00 | 0.00 | 0.00 |
July | 101.07 | 6.90 | 94.17 | 136.55 | 29.88 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 2.18 | 78.29 | 102.55 | 35.56 | 0.00 | 0.00 | 0.00 |
September | 67.38 | 0.05 | 67.32 | 74.89 | 58.35 | 0.00 | 0.00 | 0.00 |
October | 48.21 | 0.00 | 48.21 | 23.60 | 130.15 | 0.00 | 0.00 | 0.00 |
November | 36.59 | 0.00 | 36.59 | 7.70 | 157.59 | 0.00 | 0.00 | 0.00 |
December | 30.95 | 0.00 | 30.95 | 3.76 | 200.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 64.35 | 2.07 | 62.28 | 54.01 | 109.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.95 | 0.00 | 30.95 | 3.76 | 29.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.56 | 11.92 | 94.64 | 141.53 | 200.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1048.52 | 863.14 | 185.38 | 1194.69 | 485.50 | 0.00 | 0.00 | 0.00 |
February | 992.16 | 788.87 | 203.28 | 1113.55 | 519.34 | 0.00 | 0.00 | 0.00 |
March | 745.28 | 492.55 | 252.72 | 841.55 | 418.17 | 0.00 | 0.00 | 0.00 |
April | 488.01 | 201.89 | 286.12 | 500.15 | 384.75 | 0.00 | 0.00 | 0.00 |
May | 443.45 | 85.28 | 358.18 | 497.31 | 232.29 | 0.00 | 0.00 | 0.00 |
June | 403.18 | 72.78 | 330.40 | 576.57 | 117.33 | 0.00 | 0.00 | 0.00 |
July | 416.43 | 70.94 | 345.49 | 599.10 | 105.49 | 0.00 | 0.00 | 0.00 |
August | 529.85 | 217.99 | 311.87 | 761.36 | 121.67 | 0.00 | 0.00 | 0.00 |
September | 696.01 | 391.22 | 304.78 | 935.01 | 189.68 | 0.00 | 0.00 | 0.00 |
October | 821.58 | 582.11 | 239.46 | 984.10 | 408.00 | 0.00 | 0.00 | 0.00 |
November | 1007.02 | 803.22 | 203.79 | 1174.10 | 462.57 | 0.00 | 0.00 | 0.00 |
December | 961.03 | 777.98 | 183.05 | 1063.67 | 563.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 711.12 | 443.70 | 267.41 | 851.92 | 333.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 403.18 | 70.94 | 183.05 | 497.31 | 105.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1048.52 | 863.14 | 358.18 | 1194.69 | 563.91 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380465E+10 | 0.313198E+10 | 0.672671E+09 | 0.428605E+10 | 0.170933E+10 |
February | 0.325173E+10 | 0.258549E+10 | 0.666247E+09 | 0.363074E+10 | 0.161300E+10 |
March | 0.270430E+10 | 0.178728E+10 | 0.917025E+09 | 0.304919E+10 | 0.142263E+10 |
April | 0.171366E+10 | 0.708940E+09 | 0.100472E+10 | 0.176976E+10 | 0.123448E+10 |
May | 0.160910E+10 | 0.309432E+09 | 0.129967E+10 | 0.182741E+10 | 0.760764E+09 |
June | 0.141576E+10 | 0.255570E+09 | 0.116019E+10 | 0.200348E+10 | 0.399629E+09 |
July | 0.151105E+10 | 0.257418E+09 | 0.125363E+10 | 0.214982E+10 | 0.370925E+09 |
August | 0.192261E+10 | 0.790983E+09 | 0.113163E+10 | 0.274112E+10 | 0.431417E+09 |
September | 0.244404E+10 | 0.137379E+10 | 0.107025E+10 | 0.326371E+10 | 0.645095E+09 |
October | 0.298116E+10 | 0.211225E+10 | 0.868910E+09 | 0.355480E+10 | 0.138929E+10 |
November | 0.353618E+10 | 0.282056E+10 | 0.715622E+09 | 0.408676E+10 | 0.155477E+10 |
December | 0.348719E+10 | 0.282298E+10 | 0.664211E+09 | 0.384544E+10 | 0.193755E+10 |
Annual Sum or Average | 0.303814E+11 | 0.189567E+11 | 0.114248E+11 | 0.362083E+11 | 0.134689E+11 |
Minimum of Months | 0.141576E+10 | 0.255570E+09 | 0.664211E+09 | 0.176976E+10 | 0.370925E+09 |
Maximum of Months | 0.380465E+10 | 0.313198E+10 | 0.129967E+10 | 0.428605E+10 | 0.193755E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107137E+11 | 0.881946E+10 | 0.189420E+10 | 0.120057E+11 | 0.492442E+10 |
February | 0.915667E+10 | 0.728056E+10 | 0.187611E+10 | 0.101681E+11 | 0.462943E+10 |
March | 0.761514E+10 | 0.503286E+10 | 0.258228E+10 | 0.854024E+10 | 0.410146E+10 |
April | 0.482554E+10 | 0.199633E+10 | 0.282922E+10 | 0.495919E+10 | 0.357110E+10 |
May | 0.453111E+10 | 0.871340E+09 | 0.365977E+10 | 0.517686E+10 | 0.215749E+10 |
June | 0.398667E+10 | 0.719668E+09 | 0.326701E+10 | 0.569409E+10 | 0.109810E+10 |
July | 0.425500E+10 | 0.724873E+09 | 0.353013E+10 | 0.609696E+10 | 0.102062E+10 |
August | 0.541394E+10 | 0.222736E+10 | 0.318659E+10 | 0.773379E+10 | 0.119816E+10 |
September | 0.688226E+10 | 0.386850E+10 | 0.301376E+10 | 0.917888E+10 | 0.181552E+10 |
October | 0.839476E+10 | 0.594797E+10 | 0.244679E+10 | 0.996806E+10 | 0.398110E+10 |
November | 0.995764E+10 | 0.794250E+10 | 0.201515E+10 | 0.114521E+11 | 0.446829E+10 |
December | 0.981969E+10 | 0.794932E+10 | 0.187038E+10 | 0.107721E+11 | 0.557029E+10 |
Annual Sum or Average | 0.855521E+11 | 0.533807E+11 | 0.321714E+11 | 0.101746E+12 | 0.385360E+11 |
Minimum of Months | 0.398667E+10 | 0.719668E+09 | 0.187038E+10 | 0.495919E+10 | 0.102062E+10 |
Maximum of Months | 0.107137E+11 | 0.881946E+10 | 0.365977E+10 | 0.120057E+11 | 0.557029E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139177E+11 | 0.114570E+11 | 0.246067E+10 | 0.158311E+11 | 0.664379E+10 |
February | 0.118950E+11 | 0.945786E+10 | 0.243717E+10 | 0.134290E+11 | 0.625557E+10 |
March | 0.989250E+10 | 0.653797E+10 | 0.335453E+10 | 0.112779E+11 | 0.559505E+10 |
April | 0.626865E+10 | 0.259334E+10 | 0.367531E+10 | 0.653630E+10 | 0.495443E+10 |
May | 0.588617E+10 | 0.113192E+10 | 0.475425E+10 | 0.678476E+10 | 0.300050E+10 |
June | 0.517892E+10 | 0.934890E+09 | 0.424403E+10 | 0.752110E+10 | 0.147966E+10 |
July | 0.552749E+10 | 0.941651E+09 | 0.458584E+10 | 0.805690E+10 | 0.137271E+10 |
August | 0.703302E+10 | 0.289346E+10 | 0.413956E+10 | 0.102305E+11 | 0.158881E+10 |
September | 0.894045E+10 | 0.502541E+10 | 0.391504E+10 | 0.121285E+11 | 0.241652E+10 |
October | 0.109053E+11 | 0.772675E+10 | 0.317852E+10 | 0.131473E+11 | 0.540350E+10 |
November | 0.129355E+11 | 0.103178E+11 | 0.261779E+10 | 0.151039E+11 | 0.604830E+10 |
December | 0.127563E+11 | 0.103266E+11 | 0.242972E+10 | 0.142000E+11 | 0.752744E+10 |
Annual Sum or Average | 0.111137E+12 | 0.693446E+11 | 0.417924E+11 | 0.134247E+12 | 0.522863E+11 |
Minimum of Months | 0.517892E+10 | 0.934890E+09 | 0.242972E+10 | 0.653630E+10 | 0.137271E+10 |
Maximum of Months | 0.139177E+11 | 0.114570E+11 | 0.475425E+10 | 0.158311E+11 | 0.752744E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.752247E+09 | 0.619247E+09 | 0.133000E+09 | 0.862991E+09 | 0.329495E+09 |
February | 0.642925E+09 | 0.511195E+09 | 0.131730E+09 | 0.728238E+09 | 0.315913E+09 |
March | 0.534689E+09 | 0.353376E+09 | 0.181313E+09 | 0.611952E+09 | 0.275806E+09 |
April | 0.338821E+09 | 0.140170E+09 | 0.198652E+09 | 0.355522E+09 | 0.241143E+09 |
May | 0.318149E+09 | 61180009.99 | 0.256969E+09 | 0.371054E+09 | 0.139481E+09 |
June | 0.279922E+09 | 50530576.00 | 0.229392E+09 | 0.415183E+09 | 59899129.81 |
July | 0.298762E+09 | 50895998.90 | 0.247866E+09 | 0.446670E+09 | 52657142.16 |
August | 0.380136E+09 | 0.156391E+09 | 0.223745E+09 | 0.561334E+09 | 62823462.14 |
September | 0.483231E+09 | 0.271622E+09 | 0.211609E+09 | 0.662059E+09 | 0.105691E+09 |
October | 0.589429E+09 | 0.417629E+09 | 0.171800E+09 | 0.714894E+09 | 0.262959E+09 |
November | 0.699164E+09 | 0.557672E+09 | 0.141492E+09 | 0.821962E+09 | 0.298539E+09 |
December | 0.689478E+09 | 0.558151E+09 | 0.131327E+09 | 0.770938E+09 | 0.380970E+09 |
Annual Sum or Average | 0.600695E+10 | 0.374806E+10 | 0.225889E+10 | 0.732280E+10 | 0.252538E+10 |
Minimum of Months | 0.279922E+09 | 50530576.00 | 0.131327E+09 | 0.355522E+09 | 52657142.16 |
Maximum of Months | 0.752247E+09 | 0.619247E+09 | 0.256969E+09 | 0.862991E+09 | 0.380970E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.486838E+09 | 0.308540E+09 | 0.178298E+09 | 0.451433E+09 | 0.677360E+09 |
February | 0.531210E+09 | 0.329518E+09 | 0.201692E+09 | 0.486398E+09 | 0.629146E+09 |
March | 0.685855E+09 | 0.377802E+09 | 0.308053E+09 | 0.678344E+09 | 0.522376E+09 |
April | 0.626031E+09 | 0.265189E+09 | 0.360842E+09 | 0.597796E+09 | 0.440011E+09 |
May | 0.790932E+09 | 0.279336E+09 | 0.511595E+09 | 0.911536E+09 | 0.253390E+09 |
June | 0.934467E+09 | 0.449246E+09 | 0.485221E+09 | 0.129073E+10 | 0.111197E+09 |
July | 0.785891E+09 | 0.286942E+09 | 0.498950E+09 | 0.110011E+10 | 97920565.32 |
August | 0.822947E+09 | 0.406677E+09 | 0.416270E+09 | 0.112329E+10 | 0.115780E+09 |
September | 0.708590E+09 | 0.340909E+09 | 0.367681E+09 | 0.919640E+09 | 0.198826E+09 |
October | 0.613158E+09 | 0.350463E+09 | 0.262695E+09 | 0.658574E+09 | 0.504450E+09 |
November | 0.487245E+09 | 0.295932E+09 | 0.191313E+09 | 0.467136E+09 | 0.590259E+09 |
December | 0.406065E+09 | 0.239774E+09 | 0.166291E+09 | 0.340713E+09 | 0.774522E+09 |
Annual Sum or Average | 0.787923E+10 | 0.393033E+10 | 0.394890E+10 | 0.902570E+10 | 0.491524E+10 |
Minimum of Months | 0.406065E+09 | 0.239774E+09 | 0.166291E+09 | 0.340713E+09 | 97920565.32 |
Maximum of Months | 0.934467E+09 | 0.449246E+09 | 0.511595E+09 | 0.129073E+10 | 0.774522E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78205352.13 | 0.00 | 78205352.13 | 17346714.33 | 0.373584E+09 |
February | 88782422.62 | 0.00 | 88782422.62 | 18730293.99 | 0.349009E+09 |
March | 0.133789E+09 | 6903.69 | 0.133782E+09 | 63749424.93 | 0.288109E+09 |
April | 0.162755E+09 | 1066367.52 | 0.161689E+09 | 93764021.59 | 0.237175E+09 |
May | 0.229743E+09 | 7705164.64 | 0.222038E+09 | 0.219677E+09 | 0.128588E+09 |
June | 0.243762E+09 | 27259487.35 | 0.216502E+09 | 0.340827E+09 | 54973756.67 |
July | 0.238909E+09 | 16308023.91 | 0.222601E+09 | 0.341608E+09 | 49537791.73 |
August | 0.190216E+09 | 5147653.63 | 0.185068E+09 | 0.259498E+09 | 59856665.52 |
September | 0.154131E+09 | 123096.13 | 0.154008E+09 | 0.185795E+09 | 0.105305E+09 |
October | 0.113948E+09 | 0.00 | 0.113948E+09 | 68063913.90 | 0.270636E+09 |
November | 83710436.95 | 0.00 | 83710436.95 | 26353339.57 | 0.322506E+09 |
December | 73170813.40 | 0.00 | 73170813.40 | 14295939.18 | 0.430314E+09 |
Annual Sum or Average | 0.179112E+10 | 57616696.89 | 0.173351E+10 | 0.164971E+10 | 0.266959E+10 |
Minimum of Months | 73170813.40 | 0.00 | 73170813.40 | 14295939.18 | 49537791.73 |
Maximum of Months | 0.243762E+09 | 27259487.35 | 0.222601E+09 | 0.341608E+09 | 0.430314E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.486838E+09 | 0.308540E+09 | 0.178298E+09 | 0.471217E+09 | 0.660956E+09 |
February | 0.531210E+09 | 0.329518E+09 | 0.201692E+09 | 0.504824E+09 | 0.616799E+09 |
March | 0.685855E+09 | 0.377802E+09 | 0.308053E+09 | 0.693753E+09 | 0.515132E+09 |
April | 0.626031E+09 | 0.265189E+09 | 0.360842E+09 | 0.606482E+09 | 0.436615E+09 |
May | 0.790932E+09 | 0.279336E+09 | 0.511595E+09 | 0.915896E+09 | 0.252163E+09 |
June | 0.934467E+09 | 0.449246E+09 | 0.485221E+09 | 0.129240E+10 | 0.110584E+09 |
July | 0.785891E+09 | 0.286942E+09 | 0.498950E+09 | 0.110229E+10 | 97250855.00 |
August | 0.822947E+09 | 0.406677E+09 | 0.416270E+09 | 0.112944E+10 | 0.114060E+09 |
September | 0.708590E+09 | 0.340909E+09 | 0.367681E+09 | 0.929790E+09 | 0.195146E+09 |
October | 0.613158E+09 | 0.350463E+09 | 0.262695E+09 | 0.673773E+09 | 0.496198E+09 |
November | 0.487245E+09 | 0.295932E+09 | 0.191313E+09 | 0.485967E+09 | 0.577129E+09 |
December | 0.406065E+09 | 0.239774E+09 | 0.166291E+09 | 0.357182E+09 | 0.760661E+09 |
Annual Sum or Average | 0.787923E+10 | 0.393033E+10 | 0.394890E+10 | 0.916302E+10 | 0.483269E+10 |
Minimum of Months | 0.406065E+09 | 0.239774E+09 | 0.166291E+09 | 0.357182E+09 | 97250855.00 |
Maximum of Months | 0.934467E+09 | 0.449246E+09 | 0.511595E+09 | 0.129240E+10 | 0.760661E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.601678E+09 | 0.495299E+09 | 0.106379E+09 | 0.680062E+09 | 0.285593E+09 |
February | 0.514238E+09 | 0.408875E+09 | 0.105363E+09 | 0.574952E+09 | 0.265657E+09 |
March | 0.427666E+09 | 0.282644E+09 | 0.145022E+09 | 0.485232E+09 | 0.229506E+09 |
April | 0.271003E+09 | 0.112113E+09 | 0.158890E+09 | 0.283360E+09 | 0.198546E+09 |
May | 0.254468E+09 | 48934276.29 | 0.205534E+09 | 0.293081E+09 | 0.123455E+09 |
June | 0.223893E+09 | 40416423.07 | 0.183477E+09 | 0.329531E+09 | 58586779.49 |
July | 0.238962E+09 | 40708703.25 | 0.198254E+09 | 0.353144E+09 | 53747360.88 |
August | 0.304048E+09 | 0.125088E+09 | 0.178960E+09 | 0.445110E+09 | 63114755.07 |
September | 0.386508E+09 | 0.217254E+09 | 0.169254E+09 | 0.524690E+09 | 99748093.35 |
October | 0.471449E+09 | 0.334037E+09 | 0.137413E+09 | 0.566700E+09 | 0.226648E+09 |
November | 0.559220E+09 | 0.446049E+09 | 0.113171E+09 | 0.650078E+09 | 0.257967E+09 |
December | 0.551473E+09 | 0.446432E+09 | 0.105041E+09 | 0.608387E+09 | 0.320868E+09 |
Annual Sum or Average | 0.480461E+10 | 0.299785E+10 | 0.180676E+10 | 0.579433E+10 | 0.218344E+10 |
Minimum of Months | 0.223893E+09 | 40416423.07 | 0.105041E+09 | 0.283360E+09 | 53747360.88 |
Maximum of Months | 0.601678E+09 | 0.495299E+09 | 0.205534E+09 | 0.680062E+09 | 0.320868E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62572574.96 | 0.00 | 62572574.96 | 13927769.33 | 0.304469E+09 |
February | 71035352.99 | 0.00 | 71035352.99 | 15699594.85 | 0.283254E+09 |
March | 0.107045E+09 | 5523.69 | 0.107040E+09 | 53946431.57 | 0.232190E+09 |
April | 0.130222E+09 | 853207.10 | 0.129368E+09 | 77844402.22 | 0.192484E+09 |
May | 0.183819E+09 | 6164948.81 | 0.177654E+09 | 0.184467E+09 | 0.101017E+09 |
June | 0.195035E+09 | 21810480.60 | 0.173225E+09 | 0.286007E+09 | 39879613.01 |
July | 0.191153E+09 | 13048148.50 | 0.178104E+09 | 0.285355E+09 | 35920033.10 |
August | 0.152193E+09 | 4118668.79 | 0.148074E+09 | 0.220099E+09 | 43424333.67 |
September | 0.123321E+09 | 98489.96 | 0.123223E+09 | 0.158664E+09 | 79559344.30 |
October | 91170274.99 | 0.00 | 91170274.99 | 58903971.41 | 0.216868E+09 |
November | 66977226.59 | 0.00 | 66977226.59 | 21848498.08 | 0.261588E+09 |
December | 58544410.09 | 0.00 | 58544410.09 | 11095510.99 | 0.353722E+09 |
Annual Sum or Average | 0.143309E+10 | 46099467.45 | 0.138699E+10 | 0.138786E+10 | 0.214437E+10 |
Minimum of Months | 58544410.09 | 0.00 | 58544410.09 | 11095510.99 | 35920033.10 |
Maximum of Months | 0.195035E+09 | 21810480.60 | 0.178104E+09 | 0.286007E+09 | 0.353722E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.455767E+09 | 0.278765E+09 | 0.177003E+09 | 0.396513E+09 | 0.665924E+09 |
February | 0.551865E+09 | 0.349271E+09 | 0.202594E+09 | 0.508818E+09 | 0.626384E+09 |
March | 0.736009E+09 | 0.429611E+09 | 0.306398E+09 | 0.734200E+09 | 0.512992E+09 |
April | 0.727100E+09 | 0.354133E+09 | 0.372967E+09 | 0.718792E+09 | 0.430622E+09 |
May | 0.880818E+09 | 0.368744E+09 | 0.512074E+09 | 0.101182E+10 | 0.239139E+09 |
June | 0.103721E+10 | 0.544363E+09 | 0.492848E+09 | 0.141707E+10 | 0.101443E+09 |
July | 0.972841E+09 | 0.462281E+09 | 0.510560E+09 | 0.134671E+10 | 92300470.24 |
August | 0.983679E+09 | 0.541955E+09 | 0.441724E+09 | 0.133959E+10 | 0.111807E+09 |
September | 0.793362E+09 | 0.431250E+09 | 0.362112E+09 | 0.102070E+10 | 0.188416E+09 |
October | 0.593245E+09 | 0.325358E+09 | 0.267887E+09 | 0.620104E+09 | 0.494653E+09 |
November | 0.445508E+09 | 0.251066E+09 | 0.194443E+09 | 0.409620E+09 | 0.586356E+09 |
December | 0.399261E+09 | 0.230075E+09 | 0.169187E+09 | 0.326973E+09 | 0.770516E+09 |
Annual Sum or Average | 0.857667E+10 | 0.456687E+10 | 0.400980E+10 | 0.985089E+10 | 0.482055E+10 |
Minimum of Months | 0.399261E+09 | 0.230075E+09 | 0.169187E+09 | 0.326973E+09 | 92300470.24 |
Maximum of Months | 0.103721E+10 | 0.544363E+09 | 0.512074E+09 | 0.141707E+10 | 0.770516E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.752247E+09 | 0.619247E+09 | 0.133000E+09 | 0.861467E+09 | 0.327999E+09 |
February | 0.642925E+09 | 0.511195E+09 | 0.131730E+09 | 0.725623E+09 | 0.314439E+09 |
March | 0.534689E+09 | 0.353376E+09 | 0.181313E+09 | 0.607569E+09 | 0.274355E+09 |
April | 0.338821E+09 | 0.140170E+09 | 0.198652E+09 | 0.351127E+09 | 0.240691E+09 |
May | 0.318149E+09 | 61180009.99 | 0.256969E+09 | 0.367203E+09 | 0.138934E+09 |
June | 0.279922E+09 | 50530576.00 | 0.229392E+09 | 0.411543E+09 | 58733536.38 |
July | 0.298762E+09 | 50895998.90 | 0.247866E+09 | 0.442486E+09 | 52219951.45 |
August | 0.380136E+09 | 0.156391E+09 | 0.223745E+09 | 0.557055E+09 | 62435708.00 |
September | 0.483231E+09 | 0.271622E+09 | 0.211609E+09 | 0.659118E+09 | 0.104962E+09 |
October | 0.589429E+09 | 0.417629E+09 | 0.171800E+09 | 0.712914E+09 | 0.261595E+09 |
November | 0.699164E+09 | 0.557672E+09 | 0.141492E+09 | 0.820926E+09 | 0.296932E+09 |
December | 0.689478E+09 | 0.558151E+09 | 0.131327E+09 | 0.769549E+09 | 0.379742E+09 |
Annual Sum or Average | 0.600695E+10 | 0.374806E+10 | 0.225889E+10 | 0.728658E+10 | 0.251304E+10 |
Minimum of Months | 0.279922E+09 | 50530576.00 | 0.131327E+09 | 0.351127E+09 | 52219951.45 |
Maximum of Months | 0.752247E+09 | 0.619247E+09 | 0.256969E+09 | 0.861467E+09 | 0.379742E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78205352.13 | 0.00 | 78205352.13 | 16399770.66 | 0.371820E+09 |
February | 88782422.62 | 0.00 | 88782422.62 | 16620339.25 | 0.348001E+09 |
March | 0.133789E+09 | 6903.69 | 0.133782E+09 | 59668288.18 | 0.287857E+09 |
April | 0.162755E+09 | 1066367.52 | 0.161689E+09 | 89015501.82 | 0.237253E+09 |
May | 0.229743E+09 | 7705164.64 | 0.222038E+09 | 0.215177E+09 | 0.128043E+09 |
June | 0.243762E+09 | 27259487.35 | 0.216502E+09 | 0.337238E+09 | 54038877.22 |
July | 0.238909E+09 | 16308023.91 | 0.222601E+09 | 0.337312E+09 | 49246172.99 |
August | 0.190216E+09 | 5147653.63 | 0.185068E+09 | 0.254764E+09 | 59459836.25 |
September | 0.154131E+09 | 123096.13 | 0.154008E+09 | 0.182235E+09 | 0.104945E+09 |
October | 0.113948E+09 | 0.00 | 0.113948E+09 | 65188907.75 | 0.269378E+09 |
November | 83710436.95 | 0.00 | 83710436.95 | 24755609.87 | 0.320139E+09 |
December | 73170813.40 | 0.00 | 73170813.40 | 13286581.29 | 0.428635E+09 |
Annual Sum or Average | 0.179112E+10 | 57616696.89 | 0.173351E+10 | 0.161166E+10 | 0.265881E+10 |
Minimum of Months | 73170813.40 | 0.00 | 73170813.40 | 13286581.29 | 49246172.99 |
Maximum of Months | 0.243762E+09 | 27259487.35 | 0.222601E+09 | 0.337312E+09 | 0.428635E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.455767E+09 | 0.278765E+09 | 0.177003E+09 | 0.410412E+09 | 0.641299E+09 |
February | 0.551865E+09 | 0.349271E+09 | 0.202594E+09 | 0.521932E+09 | 0.608093E+09 |
March | 0.736009E+09 | 0.429611E+09 | 0.306398E+09 | 0.747421E+09 | 0.504720E+09 |
April | 0.727100E+09 | 0.354133E+09 | 0.372967E+09 | 0.726049E+09 | 0.427029E+09 |
May | 0.880818E+09 | 0.368744E+09 | 0.512074E+09 | 0.101550E+10 | 0.237912E+09 |
June | 0.103721E+10 | 0.544363E+09 | 0.492848E+09 | 0.141894E+10 | 0.101043E+09 |
July | 0.972841E+09 | 0.462281E+09 | 0.510560E+09 | 0.134889E+10 | 91770750.73 |
August | 0.983679E+09 | 0.541955E+09 | 0.441724E+09 | 0.134522E+10 | 0.110126E+09 |
September | 0.793362E+09 | 0.431250E+09 | 0.362112E+09 | 0.102950E+10 | 0.184815E+09 |
October | 0.593245E+09 | 0.325358E+09 | 0.267887E+09 | 0.633475E+09 | 0.485851E+09 |
November | 0.445508E+09 | 0.251066E+09 | 0.194443E+09 | 0.424248E+09 | 0.567361E+09 |
December | 0.399261E+09 | 0.230075E+09 | 0.169187E+09 | 0.339216E+09 | 0.750341E+09 |
Annual Sum or Average | 0.857667E+10 | 0.456687E+10 | 0.400980E+10 | 0.996080E+10 | 0.471036E+10 |
Minimum of Months | 0.399261E+09 | 0.230075E+09 | 0.169187E+09 | 0.339216E+09 | 91770750.73 |
Maximum of Months | 0.103721E+10 | 0.544363E+09 | 0.512074E+09 | 0.141894E+10 | 0.750341E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 99042143.99 | 0.00 | 99042143.99 | 15857273.66 | 0.523303E+09 |
February | 0.112437E+09 | 0.00 | 0.112437E+09 | 17391322.70 | 0.480909E+09 |
March | 0.169435E+09 | 8743.09 | 0.169426E+09 | 72702499.48 | 0.400816E+09 |
April | 0.206120E+09 | 1350487.19 | 0.204769E+09 | 0.113778E+09 | 0.329522E+09 |
May | 0.290956E+09 | 9758104.85 | 0.281198E+09 | 0.269594E+09 | 0.187764E+09 |
June | 0.308709E+09 | 34522420.75 | 0.274187E+09 | 0.420023E+09 | 90108257.03 |
July | 0.302563E+09 | 20653083.30 | 0.281910E+09 | 0.418465E+09 | 85690176.64 |
August | 0.240897E+09 | 6519178.53 | 0.234377E+09 | 0.316136E+09 | 0.102449E+09 |
September | 0.195197E+09 | 155893.49 | 0.195041E+09 | 0.223882E+09 | 0.166227E+09 |
October | 0.144308E+09 | 0.00 | 0.144308E+09 | 75747652.00 | 0.388890E+09 |
November | 0.106014E+09 | 0.00 | 0.106014E+09 | 25909587.87 | 0.453497E+09 |
December | 92666218.35 | 0.00 | 92666218.35 | 13458199.32 | 0.593208E+09 |
Annual Sum or Average | 0.226834E+10 | 72967911.20 | 0.219538E+10 | 0.198294E+10 | 0.380238E+10 |
Minimum of Months | 92666218.35 | 0.00 | 92666218.35 | 13458199.32 | 85690176.64 |
Maximum of Months | 0.308709E+09 | 34522420.75 | 0.281910E+09 | 0.420023E+09 | 0.593208E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36511035.29 | 0.00 | 36511035.29 | 5845647.67 | 0.192911E+09 |
February | 41449057.86 | 0.00 | 41449057.86 | 6411161.67 | 0.177284E+09 |
March | 62460760.84 | 3223.07 | 62457537.77 | 26801151.68 | 0.147757E+09 |
April | 75984197.42 | 497845.50 | 75486351.92 | 41943418.42 | 0.121475E+09 |
May | 0.107258E+09 | 3597241.50 | 0.103661E+09 | 99383482.92 | 69217585.24 |
June | 0.113803E+09 | 12726393.75 | 0.101077E+09 | 0.154838E+09 | 33217634.63 |
July | 0.111537E+09 | 7613581.68 | 0.103924E+09 | 0.154263E+09 | 31588947.26 |
August | 88804449.62 | 2403239.14 | 86401210.48 | 0.116541E+09 | 37766833.74 |
September | 71957805.44 | 57468.79 | 71900336.65 | 82532008.49 | 61278256.73 |
October | 53197764.83 | 0.00 | 53197764.83 | 27923720.99 | 0.143360E+09 |
November | 39081145.14 | 0.00 | 39081145.14 | 9551346.92 | 0.167178E+09 |
December | 34160605.09 | 0.00 | 34160605.09 | 4961249.53 | 0.218681E+09 |
Annual Sum or Average | 0.836205E+09 | 26898993.43 | 0.809306E+09 | 0.730995E+09 | 0.140172E+10 |
Minimum of Months | 34160605.09 | 0.00 | 34160605.09 | 4961249.53 | 31588947.26 |
Maximum of Months | 0.113803E+09 | 12726393.75 | 0.103924E+09 | 0.154838E+09 | 0.218681E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.350995E+09 | 0.288938E+09 | 62057156.81 | 0.403086E+09 | 0.163039E+09 |
February | 0.299986E+09 | 0.238522E+09 | 61464635.60 | 0.340518E+09 | 0.155872E+09 |
March | 0.249484E+09 | 0.164884E+09 | 84600115.41 | 0.285467E+09 | 0.139172E+09 |
April | 0.158093E+09 | 65402535.88 | 92690045.02 | 0.165778E+09 | 0.122134E+09 |
May | 0.148447E+09 | 28546346.13 | 0.119901E+09 | 0.171606E+09 | 74790280.45 |
June | 0.130611E+09 | 23577363.14 | 0.107033E+09 | 0.190565E+09 | 36534700.31 |
July | 0.139401E+09 | 23747867.99 | 0.115653E+09 | 0.204290E+09 | 33761838.25 |
August | 0.177370E+09 | 72971361.76 | 0.104398E+09 | 0.258833E+09 | 39138298.46 |
September | 0.225474E+09 | 0.126738E+09 | 98735936.14 | 0.306505E+09 | 60287217.04 |
October | 0.275025E+09 | 0.194864E+09 | 80161197.76 | 0.332519E+09 | 0.136344E+09 |
November | 0.326227E+09 | 0.260208E+09 | 66019589.62 | 0.384060E+09 | 0.149328E+09 |
December | 0.321708E+09 | 0.260431E+09 | 61276619.87 | 0.359880E+09 | 0.187279E+09 |
Annual Sum or Average | 0.280282E+10 | 0.174883E+10 | 0.105399E+10 | 0.340311E+10 | 0.129768E+10 |
Minimum of Months | 0.130611E+09 | 23577363.14 | 61276619.87 | 0.165778E+09 | 33761838.25 |
Maximum of Months | 0.350995E+09 | 0.288938E+09 | 0.119901E+09 | 0.403086E+09 | 0.187279E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.952673E+09 | 0.784237E+09 | 0.168436E+09 | 0.109406E+10 | 0.442520E+09 |
February | 0.814224E+09 | 0.647396E+09 | 0.166828E+09 | 0.924236E+09 | 0.423069E+09 |
March | 0.677150E+09 | 0.447528E+09 | 0.229622E+09 | 0.774816E+09 | 0.377741E+09 |
April | 0.429096E+09 | 0.177516E+09 | 0.251580E+09 | 0.449955E+09 | 0.331496E+09 |
May | 0.402915E+09 | 77480622.41 | 0.325435E+09 | 0.465773E+09 | 0.202996E+09 |
June | 0.354504E+09 | 63993786.21 | 0.290510E+09 | 0.517233E+09 | 99162649.65 |
July | 0.378364E+09 | 64456571.24 | 0.313907E+09 | 0.554484E+09 | 91636534.85 |
August | 0.481418E+09 | 0.198059E+09 | 0.283359E+09 | 0.702527E+09 | 0.106229E+09 |
September | 0.611982E+09 | 0.343992E+09 | 0.267990E+09 | 0.831917E+09 | 0.163632E+09 |
October | 0.746474E+09 | 0.528901E+09 | 0.217574E+09 | 0.902525E+09 | 0.370066E+09 |
November | 0.885447E+09 | 0.706257E+09 | 0.179191E+09 | 0.104242E+10 | 0.405307E+09 |
December | 0.873180E+09 | 0.706863E+09 | 0.166317E+09 | 0.976788E+09 | 0.508314E+09 |
Annual Sum or Average | 0.760743E+10 | 0.474668E+10 | 0.286075E+10 | 0.923673E+10 | 0.352217E+10 |
Minimum of Months | 0.354504E+09 | 63993786.21 | 0.166317E+09 | 0.449955E+09 | 91636534.85 |
Maximum of Months | 0.952673E+09 | 0.784237E+09 | 0.325435E+09 | 0.109406E+10 | 0.508314E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.752247E+09 | 0.619247E+09 | 0.133000E+09 | 0.861723E+09 | 0.326732E+09 |
February | 0.642925E+09 | 0.511195E+09 | 0.131730E+09 | 0.725371E+09 | 0.315013E+09 |
March | 0.534689E+09 | 0.353376E+09 | 0.181313E+09 | 0.609430E+09 | 0.273938E+09 |
April | 0.338821E+09 | 0.140170E+09 | 0.198652E+09 | 0.353710E+09 | 0.239342E+09 |
May | 0.318149E+09 | 61180009.99 | 0.256969E+09 | 0.369382E+09 | 0.137838E+09 |
June | 0.279922E+09 | 50530576.00 | 0.229392E+09 | 0.413111E+09 | 58257676.07 |
July | 0.298762E+09 | 50895998.90 | 0.247866E+09 | 0.444845E+09 | 50907110.60 |
August | 0.380136E+09 | 0.156391E+09 | 0.223745E+09 | 0.558578E+09 | 60990606.48 |
September | 0.483231E+09 | 0.271622E+09 | 0.211609E+09 | 0.659636E+09 | 0.103256E+09 |
October | 0.589429E+09 | 0.417629E+09 | 0.171800E+09 | 0.712967E+09 | 0.260054E+09 |
November | 0.699164E+09 | 0.557672E+09 | 0.141492E+09 | 0.819720E+09 | 0.296257E+09 |
December | 0.689478E+09 | 0.558151E+09 | 0.131327E+09 | 0.768484E+09 | 0.379843E+09 |
Annual Sum or Average | 0.600695E+10 | 0.374806E+10 | 0.225889E+10 | 0.729695E+10 | 0.250243E+10 |
Minimum of Months | 0.279922E+09 | 50530576.00 | 0.131327E+09 | 0.353710E+09 | 50907110.60 |
Maximum of Months | 0.752247E+09 | 0.619247E+09 | 0.256969E+09 | 0.861723E+09 | 0.379843E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.486838E+09 | 0.308540E+09 | 0.178298E+09 | 0.450781E+09 | 0.669831E+09 |
February | 0.531210E+09 | 0.329518E+09 | 0.201692E+09 | 0.484203E+09 | 0.626087E+09 |
March | 0.685855E+09 | 0.377802E+09 | 0.308053E+09 | 0.675404E+09 | 0.518175E+09 |
April | 0.626031E+09 | 0.265189E+09 | 0.360842E+09 | 0.594848E+09 | 0.436259E+09 |
May | 0.790932E+09 | 0.279336E+09 | 0.511595E+09 | 0.907510E+09 | 0.250020E+09 |
June | 0.934467E+09 | 0.449246E+09 | 0.485221E+09 | 0.128530E+10 | 0.108192E+09 |
July | 0.785891E+09 | 0.286942E+09 | 0.498950E+09 | 0.109579E+10 | 94682664.28 |
August | 0.822947E+09 | 0.406677E+09 | 0.416270E+09 | 0.111849E+10 | 0.112388E+09 |
September | 0.708590E+09 | 0.340909E+09 | 0.367681E+09 | 0.916857E+09 | 0.194085E+09 |
October | 0.613158E+09 | 0.350463E+09 | 0.262695E+09 | 0.656782E+09 | 0.498162E+09 |
November | 0.487245E+09 | 0.295932E+09 | 0.191313E+09 | 0.465650E+09 | 0.584591E+09 |
December | 0.406065E+09 | 0.239774E+09 | 0.166291E+09 | 0.339990E+09 | 0.770411E+09 |
Annual Sum or Average | 0.787923E+10 | 0.393033E+10 | 0.394890E+10 | 0.899160E+10 | 0.486288E+10 |
Minimum of Months | 0.406065E+09 | 0.239774E+09 | 0.166291E+09 | 0.339990E+09 | 94682664.28 |
Maximum of Months | 0.934467E+09 | 0.449246E+09 | 0.511595E+09 | 0.128530E+10 | 0.770411E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78205352.13 | 0.00 | 78205352.13 | 18363048.21 | 0.368483E+09 |
February | 88782422.62 | 0.00 | 88782422.62 | 19328038.61 | 0.346416E+09 |
March | 0.133789E+09 | 6903.69 | 0.133782E+09 | 64390077.72 | 0.285451E+09 |
April | 0.162755E+09 | 1066367.52 | 0.161689E+09 | 93689148.32 | 0.235051E+09 |
May | 0.229743E+09 | 7705164.64 | 0.222038E+09 | 0.218994E+09 | 0.126864E+09 |
June | 0.243762E+09 | 27259487.35 | 0.216502E+09 | 0.339480E+09 | 53658187.41 |
July | 0.238909E+09 | 16308023.91 | 0.222601E+09 | 0.340545E+09 | 48077021.19 |
August | 0.190216E+09 | 5147653.63 | 0.185068E+09 | 0.258516E+09 | 58131777.99 |
September | 0.154131E+09 | 123096.13 | 0.154008E+09 | 0.186194E+09 | 0.102570E+09 |
October | 0.113948E+09 | 0.00 | 0.113948E+09 | 69379343.83 | 0.266871E+09 |
November | 83710436.95 | 0.00 | 83710436.95 | 27226033.50 | 0.318335E+09 |
December | 73170813.40 | 0.00 | 73170813.40 | 15053615.50 | 0.427330E+09 |
Annual Sum or Average | 0.179112E+10 | 57616696.89 | 0.173351E+10 | 0.165116E+10 | 0.263724E+10 |
Minimum of Months | 73170813.40 | 0.00 | 73170813.40 | 15053615.50 | 48077021.19 |
Maximum of Months | 0.243762E+09 | 27259487.35 | 0.222601E+09 | 0.340545E+09 | 0.427330E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.486838E+09 | 0.308540E+09 | 0.178298E+09 | 0.472978E+09 | 0.653122E+09 |
February | 0.531210E+09 | 0.329518E+09 | 0.201692E+09 | 0.504548E+09 | 0.613359E+09 |
March | 0.685855E+09 | 0.377802E+09 | 0.308053E+09 | 0.692193E+09 | 0.510445E+09 |
April | 0.626031E+09 | 0.265189E+09 | 0.360842E+09 | 0.604212E+09 | 0.432596E+09 |
May | 0.790932E+09 | 0.279336E+09 | 0.511595E+09 | 0.912225E+09 | 0.248623E+09 |
June | 0.934467E+09 | 0.449246E+09 | 0.485221E+09 | 0.128703E+10 | 0.107577E+09 |
July | 0.785891E+09 | 0.286942E+09 | 0.498950E+09 | 0.109806E+10 | 93983401.76 |
August | 0.822947E+09 | 0.406677E+09 | 0.416270E+09 | 0.112492E+10 | 0.110529E+09 |
September | 0.708590E+09 | 0.340909E+09 | 0.367681E+09 | 0.927852E+09 | 0.189924E+09 |
October | 0.613158E+09 | 0.350463E+09 | 0.262695E+09 | 0.674059E+09 | 0.488744E+09 |
November | 0.487245E+09 | 0.295932E+09 | 0.191313E+09 | 0.486706E+09 | 0.570599E+09 |
December | 0.406065E+09 | 0.239774E+09 | 0.166291E+09 | 0.357931E+09 | 0.756432E+09 |
Annual Sum or Average | 0.787923E+10 | 0.393033E+10 | 0.394890E+10 | 0.914272E+10 | 0.477593E+10 |
Minimum of Months | 0.406065E+09 | 0.239774E+09 | 0.166291E+09 | 0.357931E+09 | 93983401.76 |
Maximum of Months | 0.934467E+09 | 0.449246E+09 | 0.511595E+09 | 0.128703E+10 | 0.756432E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110324E+10 | 0.908185E+09 | 0.195057E+09 | 0.124165E+10 | 0.497506E+09 |
February | 0.942911E+09 | 0.749717E+09 | 0.193195E+09 | 0.104644E+10 | 0.476854E+09 |
March | 0.784173E+09 | 0.518259E+09 | 0.265914E+09 | 0.882596E+09 | 0.410779E+09 |
April | 0.496914E+09 | 0.205572E+09 | 0.291342E+09 | 0.513117E+09 | 0.356668E+09 |
May | 0.466596E+09 | 89726356.12 | 0.376869E+09 | 0.543915E+09 | 0.201358E+09 |
June | 0.410533E+09 | 74107939.14 | 0.336425E+09 | 0.616298E+09 | 81143360.01 |
July | 0.438164E+09 | 74643866.89 | 0.363520E+09 | 0.660209E+09 | 71792894.57 |
August | 0.557506E+09 | 0.229362E+09 | 0.328143E+09 | 0.824044E+09 | 86895051.11 |
September | 0.708705E+09 | 0.398360E+09 | 0.310345E+09 | 0.965818E+09 | 0.151651E+09 |
October | 0.864454E+09 | 0.612493E+09 | 0.251961E+09 | 0.103633E+10 | 0.391550E+09 |
November | 0.102539E+10 | 0.817880E+09 | 0.207512E+09 | 0.118438E+10 | 0.450891E+09 |
December | 0.101119E+10 | 0.818582E+09 | 0.192604E+09 | 0.110400E+10 | 0.579131E+09 |
Annual Sum or Average | 0.880977E+10 | 0.549689E+10 | 0.331288E+10 | 0.106188E+11 | 0.375622E+10 |
Minimum of Months | 0.410533E+09 | 74107939.14 | 0.192604E+09 | 0.513117E+09 | 71792894.57 |
Maximum of Months | 0.110324E+10 | 0.908185E+09 | 0.376869E+09 | 0.124165E+10 | 0.579131E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.547417E+09 | 0.00 | 0.547417E+09 | 89079395.94 | 0.292762E+10 |
February | 0.621453E+09 | 0.00 | 0.621453E+09 | 96000025.99 | 0.272899E+10 |
March | 0.936486E+09 | 48324.03 | 0.936437E+09 | 0.389966E+09 | 0.229697E+10 |
April | 0.113925E+10 | 7464289.97 | 0.113178E+10 | 0.587384E+09 | 0.193811E+10 |
May | 0.160814E+10 | 53934109.78 | 0.155421E+10 | 0.144702E+10 | 0.107663E+10 |
June | 0.170627E+10 | 0.190809E+09 | 0.151546E+10 | 0.231996E+10 | 0.500798E+09 |
July | 0.167230E+10 | 0.114152E+09 | 0.155815E+10 | 0.231411E+10 | 0.477697E+09 |
August | 0.133146E+10 | 36032210.72 | 0.129543E+10 | 0.176281E+10 | 0.563645E+09 |
September | 0.107888E+10 | 861640.30 | 0.107802E+10 | 0.126293E+10 | 0.906136E+09 |
October | 0.797604E+09 | 0.00 | 0.797604E+09 | 0.435404E+09 | 0.216539E+10 |
November | 0.585951E+09 | 0.00 | 0.585951E+09 | 0.145384E+09 | 0.255506E+10 |
December | 0.512176E+09 | 0.00 | 0.512176E+09 | 70493015.16 | 0.337300E+10 |
Annual Sum or Average | 0.125374E+11 | 0.403302E+09 | 0.121341E+11 | 0.109205E+11 | 0.215100E+11 |
Minimum of Months | 0.512176E+09 | 0.00 | 0.512176E+09 | 70493015.16 | 0.477697E+09 |
Maximum of Months | 0.170627E+10 | 0.190809E+09 | 0.155815E+10 | 0.231996E+10 | 0.337300E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.547417E+09 | 0.00 | 0.547417E+09 | 78951444.46 | 0.301914E+10 |
February | 0.621453E+09 | 0.00 | 0.621453E+09 | 85514157.86 | 0.281416E+10 |
March | 0.936486E+09 | 48324.03 | 0.936437E+09 | 0.365589E+09 | 0.237243E+10 |
April | 0.113925E+10 | 7464289.97 | 0.113178E+10 | 0.557151E+09 | 0.200527E+10 |
May | 0.160814E+10 | 53934109.78 | 0.155421E+10 | 0.140553E+10 | 0.110435E+10 |
June | 0.170627E+10 | 0.190809E+09 | 0.151546E+10 | 0.228395E+10 | 0.515580E+09 |
July | 0.167230E+10 | 0.114152E+09 | 0.155815E+10 | 0.227754E+10 | 0.493788E+09 |
August | 0.133146E+10 | 36032210.72 | 0.129543E+10 | 0.172812E+10 | 0.582138E+09 |
September | 0.107888E+10 | 861640.30 | 0.107802E+10 | 0.123325E+10 | 0.932181E+09 |
October | 0.797604E+09 | 0.00 | 0.797604E+09 | 0.415062E+09 | 0.222698E+10 |
November | 0.585951E+09 | 0.00 | 0.585951E+09 | 0.133358E+09 | 0.263749E+10 |
December | 0.512176E+09 | 0.00 | 0.512176E+09 | 62147297.41 | 0.347047E+10 |
Annual Sum or Average | 0.125374E+11 | 0.403302E+09 | 0.121341E+11 | 0.106262E+11 | 0.221740E+11 |
Minimum of Months | 0.512176E+09 | 0.00 | 0.512176E+09 | 62147297.41 | 0.493788E+09 |
Maximum of Months | 0.170627E+10 | 0.190809E+09 | 0.155815E+10 | 0.228395E+10 | 0.347047E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78205352.13 | 0.00 | 78205352.13 | 20589884.63 | 0.390048E+09 |
February | 88782422.62 | 0.00 | 88782422.62 | 20313426.10 | 0.371416E+09 |
March | 0.133789E+09 | 6903.69 | 0.133782E+09 | 71442772.48 | 0.312516E+09 |
April | 0.162755E+09 | 1066367.52 | 0.161689E+09 | 0.104628E+09 | 0.265100E+09 |
May | 0.229743E+09 | 7705164.64 | 0.222038E+09 | 0.256392E+09 | 0.149789E+09 |
June | 0.243762E+09 | 27259487.35 | 0.216502E+09 | 0.392738E+09 | 72220368.09 |
July | 0.238909E+09 | 16308023.91 | 0.222601E+09 | 0.393523E+09 | 68872940.43 |
August | 0.190216E+09 | 5147653.63 | 0.185068E+09 | 0.309810E+09 | 77821540.86 |
September | 0.154131E+09 | 123096.13 | 0.154008E+09 | 0.225232E+09 | 0.120149E+09 |
October | 0.113948E+09 | 0.00 | 0.113948E+09 | 82665952.80 | 0.288442E+09 |
November | 83710436.95 | 0.00 | 83710436.95 | 31456873.83 | 0.340192E+09 |
December | 73170813.40 | 0.00 | 73170813.40 | 15358389.66 | 0.458598E+09 |
Annual Sum or Average | 0.179112E+10 | 57616696.89 | 0.173351E+10 | 0.192415E+10 | 0.291516E+10 |
Minimum of Months | 73170813.40 | 0.00 | 73170813.40 | 15358389.66 | 68872940.43 |
Maximum of Months | 0.243762E+09 | 27259487.35 | 0.222601E+09 | 0.393523E+09 | 0.458598E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.911470E+09 | 0.557490E+09 | 0.353981E+09 | 0.852622E+09 | 0.135776E+10 |
February | 0.110365E+10 | 0.698492E+09 | 0.405159E+09 | 0.106877E+10 | 0.131126E+10 |
March | 0.147191E+10 | 0.859162E+09 | 0.612752E+09 | 0.155223E+10 | 0.110803E+10 |
April | 0.145410E+10 | 0.708216E+09 | 0.745881E+09 | 0.151590E+10 | 0.964071E+09 |
May | 0.176151E+10 | 0.737435E+09 | 0.102408E+10 | 0.218558E+10 | 0.556874E+09 |
June | 0.207428E+10 | 0.108865E+10 | 0.985627E+09 | 0.304202E+10 | 0.270788E+09 |
July | 0.194554E+10 | 0.924497E+09 | 0.102105E+10 | 0.290624E+10 | 0.258214E+09 |
August | 0.196722E+10 | 0.108383E+10 | 0.883386E+09 | 0.289577E+10 | 0.290072E+09 |
September | 0.158661E+10 | 0.862438E+09 | 0.724173E+09 | 0.222793E+10 | 0.434279E+09 |
October | 0.118641E+10 | 0.650670E+09 | 0.535736E+09 | 0.134538E+10 | 0.104806E+10 |
November | 0.890953E+09 | 0.502095E+09 | 0.388858E+09 | 0.884288E+09 | 0.121477E+10 |
December | 0.798466E+09 | 0.460116E+09 | 0.338350E+09 | 0.693500E+09 | 0.161870E+10 |
Annual Sum or Average | 0.171521E+11 | 0.913309E+10 | 0.801902E+10 | 0.211702E+11 | 0.104329E+11 |
Minimum of Months | 0.798466E+09 | 0.460116E+09 | 0.338350E+09 | 0.693500E+09 | 0.258214E+09 |
Maximum of Months | 0.207428E+10 | 0.108865E+10 | 0.102408E+10 | 0.304202E+10 | 0.161870E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.752247E+09 | 0.619247E+09 | 0.133000E+09 | 0.889107E+09 | 0.341028E+09 |
February | 0.642925E+09 | 0.511195E+09 | 0.131730E+09 | 0.746906E+09 | 0.334180E+09 |
March | 0.534689E+09 | 0.353376E+09 | 0.181313E+09 | 0.633737E+09 | 0.297274E+09 |
April | 0.338821E+09 | 0.140170E+09 | 0.198652E+09 | 0.372989E+09 | 0.266892E+09 |
May | 0.318149E+09 | 61180009.99 | 0.256969E+09 | 0.411262E+09 | 0.159765E+09 |
June | 0.279922E+09 | 50530576.00 | 0.229392E+09 | 0.467628E+09 | 77491081.00 |
July | 0.298762E+09 | 50895998.90 | 0.247866E+09 | 0.499594E+09 | 72064874.50 |
August | 0.380136E+09 | 0.156391E+09 | 0.223745E+09 | 0.614921E+09 | 79633535.74 |
September | 0.483231E+09 | 0.271622E+09 | 0.211609E+09 | 0.708701E+09 | 0.119767E+09 |
October | 0.589429E+09 | 0.417629E+09 | 0.171800E+09 | 0.745395E+09 | 0.277716E+09 |
November | 0.699164E+09 | 0.557672E+09 | 0.141492E+09 | 0.846721E+09 | 0.311632E+09 |
December | 0.689478E+09 | 0.558151E+09 | 0.131327E+09 | 0.786488E+09 | 0.402224E+09 |
Annual Sum or Average | 0.600695E+10 | 0.374806E+10 | 0.225889E+10 | 0.772345E+10 | 0.273967E+10 |
Minimum of Months | 0.279922E+09 | 50530576.00 | 0.131327E+09 | 0.372989E+09 | 72064874.50 |
Maximum of Months | 0.752247E+09 | 0.619247E+09 | 0.256969E+09 | 0.889107E+09 | 0.402224E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 99042143.99 | 0.00 | 99042143.99 | 13937433.94 | 0.523906E+09 |
February | 0.112437E+09 | 0.00 | 0.112437E+09 | 14535923.23 | 0.486003E+09 |
March | 0.169435E+09 | 8743.09 | 0.169426E+09 | 66672869.48 | 0.402946E+09 |
April | 0.206120E+09 | 1350487.19 | 0.204769E+09 | 0.105619E+09 | 0.335656E+09 |
May | 0.290956E+09 | 9758104.85 | 0.281198E+09 | 0.255918E+09 | 0.194521E+09 |
June | 0.308709E+09 | 34522420.75 | 0.274187E+09 | 0.410007E+09 | 93552902.03 |
July | 0.302563E+09 | 20653083.30 | 0.281910E+09 | 0.408776E+09 | 89449262.18 |
August | 0.240897E+09 | 6519178.53 | 0.234377E+09 | 0.307005E+09 | 0.106459E+09 |
September | 0.195197E+09 | 155893.49 | 0.195041E+09 | 0.216950E+09 | 0.169055E+09 |
October | 0.144308E+09 | 0.00 | 0.144308E+09 | 70643973.26 | 0.389613E+09 |
November | 0.106014E+09 | 0.00 | 0.106014E+09 | 22299776.84 | 0.456562E+09 |
December | 92666218.35 | 0.00 | 92666218.35 | 11247436.90 | 0.599209E+09 |
Annual Sum or Average | 0.226834E+10 | 72967911.20 | 0.219538E+10 | 0.190361E+10 | 0.384693E+10 |
Minimum of Months | 92666218.35 | 0.00 | 92666218.35 | 11247436.90 | 89449262.18 |
Maximum of Months | 0.308709E+09 | 34522420.75 | 0.281910E+09 | 0.410007E+09 | 0.599209E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 88613381.50 | 0.00 | 88613381.50 | 12469874.96 | 0.468662E+09 |
February | 0.100598E+09 | 0.00 | 0.100598E+09 | 13005345.59 | 0.434834E+09 |
March | 0.151594E+09 | 7822.48 | 0.151586E+09 | 59652468.95 | 0.360518E+09 |
April | 0.184416E+09 | 1208286.00 | 0.183208E+09 | 94497283.90 | 0.300313E+09 |
May | 0.260319E+09 | 8730613.39 | 0.251589E+09 | 0.228971E+09 | 0.174039E+09 |
June | 0.276203E+09 | 30887340.65 | 0.245316E+09 | 0.366834E+09 | 83702135.91 |
July | 0.270705E+09 | 18478391.88 | 0.252226E+09 | 0.365733E+09 | 80030593.79 |
August | 0.215531E+09 | 5832733.73 | 0.209698E+09 | 0.274678E+09 | 95249574.24 |
September | 0.174644E+09 | 139478.49 | 0.174504E+09 | 0.194106E+09 | 0.151254E+09 |
October | 0.129113E+09 | 0.00 | 0.129113E+09 | 63205430.55 | 0.348589E+09 |
November | 94851115.46 | 0.00 | 94851115.46 | 19951694.83 | 0.408476E+09 |
December | 82908816.67 | 0.00 | 82908816.67 | 10063124.41 | 0.536069E+09 |
Annual Sum or Average | 0.202950E+10 | 65284666.62 | 0.196421E+10 | 0.170317E+10 | 0.344173E+10 |
Minimum of Months | 82908816.67 | 0.00 | 82908816.67 | 10063124.41 | 80030593.79 |
Maximum of Months | 0.276203E+09 | 30887340.65 | 0.252226E+09 | 0.366834E+09 | 0.536069E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.280836E+10 | 0.231183E+10 | 0.496528E+09 | 0.319985E+10 | 0.130037E+10 |
February | 0.240023E+10 | 0.190844E+10 | 0.491787E+09 | 0.269391E+10 | 0.125640E+10 |
March | 0.199615E+10 | 0.131926E+10 | 0.676897E+09 | 0.225401E+10 | 0.112003E+10 |
April | 0.126492E+10 | 0.523295E+09 | 0.741626E+09 | 0.129639E+10 | 0.997275E+09 |
May | 0.118774E+10 | 0.228403E+09 | 0.959340E+09 | 0.133199E+10 | 0.622156E+09 |
June | 0.104503E+10 | 0.188646E+09 | 0.856387E+09 | 0.149446E+10 | 0.304113E+09 |
July | 0.111537E+10 | 0.190010E+09 | 0.925359E+09 | 0.160464E+10 | 0.282550E+09 |
August | 0.141916E+10 | 0.583854E+09 | 0.835306E+09 | 0.203923E+10 | 0.325872E+09 |
September | 0.180405E+10 | 0.101405E+10 | 0.790000E+09 | 0.242356E+10 | 0.491658E+09 |
October | 0.220051E+10 | 0.155913E+10 | 0.641381E+09 | 0.263582E+10 | 0.109278E+10 |
November | 0.261019E+10 | 0.208196E+10 | 0.528232E+09 | 0.304326E+10 | 0.119898E+10 |
December | 0.257403E+10 | 0.208374E+10 | 0.490283E+09 | 0.284894E+10 | 0.151038E+10 |
Annual Sum or Average | 0.224257E+11 | 0.139926E+11 | 0.843312E+10 | 0.268661E+11 | 0.105026E+11 |
Minimum of Months | 0.104503E+10 | 0.188646E+09 | 0.490283E+09 | 0.129639E+10 | 0.282550E+09 |
Maximum of Months | 0.280836E+10 | 0.231183E+10 | 0.959340E+09 | 0.319985E+10 | 0.151038E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1600.23 | 638.19 | 1420.50 | 1169.35 | 251.15 | 0.00 | 0.00 |
February | 1500.80 | 666.75 | 1344.14 | 1068.74 | 275.40 | 0.00 | 0.00 |
March | 1138.44 | 531.15 | 1009.67 | 667.29 | 342.38 | 0.00 | 0.00 |
April | 682.78 | 476.26 | 661.13 | 273.51 | 387.62 | 0.00 | 0.00 |
May | 682.28 | 284.04 | 600.77 | 115.53 | 485.24 | 0.00 | 0.00 |
June | 772.95 | 154.18 | 546.20 | 98.60 | 447.60 | 0.00 | 0.00 |
July | 802.65 | 138.49 | 564.16 | 96.11 | 468.05 | 0.00 | 0.00 |
August | 1023.42 | 161.07 | 717.82 | 295.32 | 422.50 | 0.00 | 0.00 |
September | 1259.15 | 248.88 | 942.92 | 530.01 | 412.91 | 0.00 | 0.00 |
October | 1327.21 | 518.70 | 1113.04 | 788.63 | 324.41 | 0.00 | 0.00 |
November | 1576.68 | 599.83 | 1364.27 | 1088.18 | 276.09 | 0.00 | 0.00 |
December | 1435.72 | 723.40 | 1301.97 | 1053.98 | 247.99 | 0.00 | 0.00 |
Annual Sum or Average | 1148.16 | 427.10 | 963.39 | 601.11 | 362.28 | 0.00 | 0.00 |
Minimum of Months | 682.28 | 138.49 | 546.20 | 96.11 | 247.99 | 0.00 | 0.00 |
Maximum of Months | 1600.23 | 723.40 | 1420.50 | 1169.35 | 485.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4482.43 | 1838.57 | 4000.02 | 3292.81 | 707.21 | 0.00 | 0.00 |
February | 4203.09 | 1913.62 | 3785.00 | 3009.49 | 775.51 | 0.00 | 0.00 |
March | 3188.56 | 1531.31 | 2843.17 | 1879.05 | 964.11 | 0.00 | 0.00 |
April | 1913.27 | 1377.74 | 1861.71 | 770.19 | 1091.52 | 0.00 | 0.00 |
May | 1932.82 | 805.51 | 1691.72 | 325.32 | 1366.40 | 0.00 | 0.00 |
June | 2196.80 | 423.65 | 1538.07 | 277.65 | 1260.42 | 0.00 | 0.00 |
July | 2276.34 | 381.05 | 1588.64 | 270.64 | 1318.00 | 0.00 | 0.00 |
August | 2887.46 | 447.34 | 2021.34 | 831.60 | 1189.74 | 0.00 | 0.00 |
September | 3541.24 | 700.43 | 2655.19 | 1492.48 | 1162.71 | 0.00 | 0.00 |
October | 3721.65 | 1486.37 | 3134.24 | 2220.72 | 913.53 | 0.00 | 0.00 |
November | 4418.25 | 1723.88 | 3841.68 | 3064.24 | 777.45 | 0.00 | 0.00 |
December | 4021.85 | 2079.71 | 3666.25 | 2967.93 | 698.32 | 0.00 | 0.00 |
Annual Sum or Average | 3226.35 | 1221.97 | 2712.84 | 1692.69 | 1020.15 | 0.00 | 0.00 |
Minimum of Months | 1913.27 | 381.05 | 1538.07 | 270.64 | 698.32 | 0.00 | 0.00 |
Maximum of Months | 4482.43 | 2079.71 | 4000.02 | 3292.81 | 1366.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5910.67 | 2480.51 | 5196.26 | 4277.55 | 918.71 | 0.00 | 0.00 |
February | 5551.01 | 2585.80 | 4916.93 | 3909.50 | 1007.43 | 0.00 | 0.00 |
March | 4210.68 | 2088.95 | 3693.44 | 2441.00 | 1252.44 | 0.00 | 0.00 |
April | 2521.72 | 1911.43 | 2418.46 | 1000.52 | 1417.94 | 0.00 | 0.00 |
May | 2533.14 | 1120.26 | 2197.65 | 422.61 | 1775.03 | 0.00 | 0.00 |
June | 2901.66 | 570.86 | 1998.04 | 360.68 | 1637.36 | 0.00 | 0.00 |
July | 3008.10 | 512.51 | 2063.73 | 351.57 | 1712.16 | 0.00 | 0.00 |
August | 3819.62 | 593.20 | 2625.83 | 1080.29 | 1545.53 | 0.00 | 0.00 |
September | 4679.21 | 932.30 | 3449.25 | 1938.81 | 1510.43 | 0.00 | 0.00 |
October | 4908.65 | 2017.44 | 4071.56 | 2884.84 | 1186.73 | 0.00 | 0.00 |
November | 5827.11 | 2333.45 | 4990.57 | 3980.62 | 1009.95 | 0.00 | 0.00 |
December | 5301.68 | 2810.43 | 4762.67 | 3855.52 | 907.16 | 0.00 | 0.00 |
Annual Sum or Average | 4256.95 | 1657.99 | 3524.13 | 2198.90 | 1325.23 | 0.00 | 0.00 |
Minimum of Months | 2521.72 | 512.51 | 1998.04 | 351.57 | 907.16 | 0.00 | 0.00 |
Maximum of Months | 5910.67 | 2810.43 | 5196.26 | 4277.55 | 1775.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 473.36 | 358.52 | 462.62 | 346.40 | 116.23 | 0.00 | 0.00 |
February | 488.86 | 377.43 | 485.34 | 347.52 | 137.82 | 0.00 | 0.00 |
March | 476.27 | 292.54 | 455.70 | 272.99 | 182.71 | 0.00 | 0.00 |
April | 365.12 | 260.12 | 372.24 | 156.39 | 215.85 | 0.00 | 0.00 |
May | 477.80 | 145.61 | 414.08 | 127.13 | 286.95 | 0.00 | 0.00 |
June | 658.01 | 65.87 | 468.51 | 192.81 | 275.70 | 0.00 | 0.00 |
July | 577.41 | 56.13 | 404.96 | 126.13 | 278.83 | 0.00 | 0.00 |
August | 628.65 | 66.37 | 449.18 | 210.23 | 238.95 | 0.00 | 0.00 |
September | 609.53 | 116.79 | 459.81 | 236.32 | 223.49 | 0.00 | 0.00 |
October | 509.81 | 283.53 | 448.99 | 286.77 | 162.22 | 0.00 | 0.00 |
November | 488.28 | 333.84 | 457.72 | 329.32 | 128.40 | 0.00 | 0.00 |
December | 397.20 | 413.56 | 409.03 | 297.91 | 111.12 | 0.00 | 0.00 |
Annual Sum or Average | 512.52 | 230.06 | 440.33 | 243.48 | 196.85 | 0.00 | 0.00 |
Minimum of Months | 365.12 | 56.13 | 372.24 | 126.13 | 111.12 | 0.00 | 0.00 |
Maximum of Months | 658.01 | 413.56 | 485.34 | 347.52 | 286.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 175.25 | 379.09 | 210.96 | 115.20 | 95.77 | 0.00 | 0.00 |
February | 208.77 | 391.58 | 256.28 | 136.21 | 120.07 | 0.00 | 0.00 |
March | 278.93 | 296.01 | 306.02 | 141.06 | 164.96 | 0.00 | 0.00 |
April | 268.25 | 258.04 | 304.32 | 102.72 | 201.59 | 0.00 | 0.00 |
May | 422.40 | 140.58 | 381.08 | 107.17 | 273.91 | 0.00 | 0.00 |
June | 628.18 | 61.94 | 454.56 | 183.84 | 270.73 | 0.00 | 0.00 |
July | 537.86 | 53.58 | 382.62 | 113.22 | 269.40 | 0.00 | 0.00 |
August | 518.12 | 64.48 | 378.27 | 153.76 | 224.51 | 0.00 | 0.00 |
September | 430.01 | 115.53 | 332.84 | 131.57 | 201.27 | 0.00 | 0.00 |
October | 275.25 | 284.58 | 271.47 | 130.85 | 140.62 | 0.00 | 0.00 |
November | 192.91 | 342.34 | 220.28 | 114.17 | 106.10 | 0.00 | 0.00 |
December | 131.74 | 437.71 | 178.93 | 89.52 | 89.40 | 0.00 | 0.00 |
Annual Sum or Average | 339.59 | 234.62 | 306.64 | 126.46 | 180.19 | 0.00 | 0.00 |
Minimum of Months | 131.74 | 53.58 | 178.93 | 89.52 | 89.40 | 0.00 | 0.00 |
Maximum of Months | 628.18 | 437.71 | 454.56 | 183.84 | 273.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 253.91 | 106.63 | 224.64 | 184.92 | 39.72 | 0.00 | 0.00 |
February | 237.66 | 109.81 | 212.57 | 169.01 | 43.55 | 0.00 | 0.00 |
March | 181.16 | 85.69 | 159.67 | 105.53 | 54.14 | 0.00 | 0.00 |
April | 109.32 | 76.60 | 104.55 | 43.25 | 61.30 | 0.00 | 0.00 |
May | 109.42 | 46.09 | 95.01 | 18.27 | 76.74 | 0.00 | 0.00 |
June | 127.13 | 22.60 | 86.38 | 15.59 | 70.79 | 0.00 | 0.00 |
July | 131.85 | 20.07 | 89.22 | 15.20 | 74.02 | 0.00 | 0.00 |
August | 166.19 | 23.56 | 113.52 | 46.70 | 66.82 | 0.00 | 0.00 |
September | 202.43 | 38.48 | 149.12 | 83.82 | 65.30 | 0.00 | 0.00 |
October | 211.58 | 84.62 | 176.02 | 124.71 | 51.30 | 0.00 | 0.00 |
November | 250.80 | 99.52 | 215.75 | 172.09 | 43.66 | 0.00 | 0.00 |
December | 227.15 | 119.80 | 205.90 | 166.68 | 39.22 | 0.00 | 0.00 |
Annual Sum or Average | 183.74 | 69.24 | 152.35 | 95.06 | 57.29 | 0.00 | 0.00 |
Minimum of Months | 109.32 | 20.07 | 86.38 | 15.20 | 39.22 | 0.00 | 0.00 |
Maximum of Months | 253.91 | 119.80 | 224.64 | 184.92 | 76.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.20 | 113.68 | 23.36 | 0.00 | 23.36 | 0.00 | 0.00 |
February | 6.49 | 117.09 | 29.36 | 0.00 | 29.36 | 0.00 | 0.00 |
March | 20.14 | 86.69 | 39.97 | 0.00 | 39.96 | 0.00 | 0.00 |
April | 30.03 | 74.26 | 50.24 | 0.33 | 49.91 | 0.00 | 0.00 |
May | 68.87 | 37.72 | 68.63 | 2.30 | 66.33 | 0.00 | 0.00 |
June | 110.34 | 15.39 | 75.25 | 8.41 | 66.83 | 0.00 | 0.00 |
July | 106.54 | 13.41 | 71.37 | 4.87 | 66.50 | 0.00 | 0.00 |
August | 82.18 | 16.21 | 56.82 | 1.54 | 55.28 | 0.00 | 0.00 |
September | 61.21 | 30.69 | 47.58 | 0.04 | 47.54 | 0.00 | 0.00 |
October | 21.99 | 80.97 | 34.04 | 0.00 | 34.04 | 0.00 | 0.00 |
November | 8.43 | 100.92 | 25.84 | 0.00 | 25.84 | 0.00 | 0.00 |
December | 4.14 | 132.06 | 21.86 | 0.00 | 21.86 | 0.00 | 0.00 |
Annual Sum or Average | 44.01 | 68.00 | 45.44 | 1.46 | 43.98 | 0.00 | 0.00 |
Minimum of Months | 4.14 | 13.41 | 21.86 | 0.00 | 21.86 | 0.00 | 0.00 |
Maximum of Months | 110.34 | 132.06 | 75.25 | 8.41 | 66.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 453.32 | 354.74 | 451.02 | 335.28 | 115.74 | 0.00 | 0.00 |
February | 497.31 | 375.94 | 493.88 | 355.68 | 138.20 | 0.00 | 0.00 |
March | 497.48 | 290.48 | 474.42 | 292.33 | 182.09 | 0.00 | 0.00 |
April | 409.01 | 255.23 | 411.24 | 190.70 | 220.53 | 0.00 | 0.00 |
May | 511.36 | 137.65 | 447.64 | 160.52 | 287.13 | 0.00 | 0.00 |
June | 703.84 | 60.16 | 508.15 | 229.51 | 278.64 | 0.00 | 0.00 |
July | 667.02 | 52.97 | 474.76 | 191.60 | 283.16 | 0.00 | 0.00 |
August | 707.18 | 64.11 | 509.19 | 260.73 | 248.46 | 0.00 | 0.00 |
September | 646.55 | 111.66 | 492.51 | 271.17 | 221.34 | 0.00 | 0.00 |
October | 495.87 | 280.53 | 441.56 | 277.40 | 164.16 | 0.00 | 0.00 |
November | 465.59 | 331.62 | 441.62 | 312.01 | 129.60 | 0.00 | 0.00 |
December | 394.01 | 414.07 | 406.49 | 294.29 | 112.20 | 0.00 | 0.00 |
Annual Sum or Average | 537.50 | 226.62 | 462.44 | 263.66 | 198.78 | 0.00 | 0.00 |
Minimum of Months | 394.01 | 52.97 | 406.49 | 160.52 | 112.20 | 0.00 | 0.00 |
Maximum of Months | 707.18 | 414.07 | 509.19 | 355.68 | 287.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 149.41 | 368.31 | 199.36 | 104.08 | 95.28 | 0.00 | 0.00 |
February | 213.58 | 386.18 | 264.82 | 144.37 | 120.44 | 0.00 | 0.00 |
March | 295.28 | 289.86 | 324.75 | 160.40 | 164.34 | 0.00 | 0.00 |
April | 311.05 | 252.88 | 343.31 | 137.04 | 206.27 | 0.00 | 0.00 |
May | 458.40 | 135.55 | 414.64 | 140.55 | 274.09 | 0.00 | 0.00 |
June | 677.36 | 59.65 | 494.20 | 220.53 | 273.67 | 0.00 | 0.00 |
July | 629.45 | 52.54 | 452.42 | 178.68 | 273.73 | 0.00 | 0.00 |
August | 597.02 | 62.97 | 438.28 | 204.26 | 234.02 | 0.00 | 0.00 |
September | 465.47 | 109.77 | 365.55 | 166.42 | 199.12 | 0.00 | 0.00 |
October | 257.57 | 278.69 | 264.04 | 121.47 | 142.56 | 0.00 | 0.00 |
November | 167.44 | 336.62 | 204.17 | 96.86 | 107.31 | 0.00 | 0.00 |
December | 122.34 | 430.91 | 176.39 | 85.90 | 90.49 | 0.00 | 0.00 |
Annual Sum or Average | 362.78 | 229.49 | 328.76 | 146.64 | 182.12 | 0.00 | 0.00 |
Minimum of Months | 122.34 | 52.54 | 176.39 | 85.90 | 90.49 | 0.00 | 0.00 |
Maximum of Months | 677.36 | 430.91 | 494.20 | 220.53 | 274.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 532.70 | 459.12 | 537.34 | 400.68 | 136.67 | 0.00 | 0.00 |
February | 507.08 | 485.83 | 524.18 | 366.20 | 157.98 | 0.00 | 0.00 |
March | 427.25 | 392.04 | 432.55 | 228.65 | 203.89 | 0.00 | 0.00 |
April | 297.20 | 348.58 | 335.37 | 94.43 | 240.94 | 0.00 | 0.00 |
May | 373.76 | 197.68 | 354.53 | 44.57 | 309.96 | 0.00 | 0.00 |
June | 491.65 | 96.73 | 350.16 | 52.01 | 298.15 | 0.00 | 0.00 |
July | 495.10 | 88.58 | 347.92 | 43.49 | 304.43 | 0.00 | 0.00 |
August | 519.83 | 105.98 | 369.06 | 104.52 | 264.54 | 0.00 | 0.00 |
September | 556.84 | 173.58 | 426.16 | 181.69 | 244.47 | 0.00 | 0.00 |
October | 494.57 | 382.54 | 455.12 | 270.22 | 184.90 | 0.00 | 0.00 |
November | 544.33 | 433.75 | 523.45 | 372.86 | 150.58 | 0.00 | 0.00 |
December | 471.91 | 528.81 | 493.47 | 361.15 | 132.33 | 0.00 | 0.00 |
Annual Sum or Average | 475.80 | 306.79 | 428.55 | 209.14 | 219.41 | 0.00 | 0.00 |
Minimum of Months | 297.20 | 88.58 | 335.37 | 43.49 | 132.33 | 0.00 | 0.00 |
Maximum of Months | 556.84 | 528.81 | 537.34 | 400.68 | 309.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 473.29 | 355.33 | 462.62 | 346.40 | 116.23 | 0.00 | 0.00 |
February | 487.08 | 376.11 | 485.34 | 347.52 | 137.82 | 0.00 | 0.00 |
March | 474.31 | 290.35 | 455.70 | 272.99 | 182.71 | 0.00 | 0.00 |
April | 363.27 | 257.96 | 372.24 | 156.39 | 215.85 | 0.00 | 0.00 |
May | 475.66 | 143.73 | 414.08 | 127.13 | 286.95 | 0.00 | 0.00 |
June | 655.11 | 64.07 | 468.51 | 192.81 | 275.70 | 0.00 | 0.00 |
July | 575.11 | 54.26 | 404.96 | 126.13 | 278.83 | 0.00 | 0.00 |
August | 625.82 | 64.41 | 449.18 | 210.23 | 238.95 | 0.00 | 0.00 |
September | 607.54 | 114.04 | 459.81 | 236.32 | 223.49 | 0.00 | 0.00 |
October | 508.61 | 280.29 | 448.99 | 286.77 | 162.22 | 0.00 | 0.00 |
November | 487.16 | 331.10 | 457.72 | 329.32 | 128.40 | 0.00 | 0.00 |
December | 396.41 | 412.01 | 409.03 | 297.91 | 111.12 | 0.00 | 0.00 |
Annual Sum or Average | 510.79 | 227.83 | 440.33 | 243.48 | 196.85 | 0.00 | 0.00 |
Minimum of Months | 363.27 | 54.26 | 372.24 | 126.13 | 111.12 | 0.00 | 0.00 |
Maximum of Months | 655.11 | 412.01 | 485.34 | 347.52 | 286.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 176.56 | 374.53 | 210.96 | 115.20 | 95.77 | 0.00 | 0.00 |
February | 209.00 | 389.18 | 256.28 | 136.21 | 120.07 | 0.00 | 0.00 |
March | 278.56 | 293.24 | 306.02 | 141.06 | 164.96 | 0.00 | 0.00 |
April | 267.32 | 255.65 | 304.32 | 102.72 | 201.59 | 0.00 | 0.00 |
May | 420.78 | 138.62 | 381.08 | 107.17 | 273.91 | 0.00 | 0.00 |
June | 625.67 | 60.36 | 454.56 | 183.84 | 270.73 | 0.00 | 0.00 |
July | 535.95 | 51.87 | 382.62 | 113.22 | 269.40 | 0.00 | 0.00 |
August | 516.07 | 62.53 | 378.27 | 153.76 | 224.51 | 0.00 | 0.00 |
September | 429.42 | 112.46 | 332.84 | 131.57 | 201.27 | 0.00 | 0.00 |
October | 275.84 | 280.38 | 271.47 | 130.85 | 140.62 | 0.00 | 0.00 |
November | 193.67 | 338.35 | 220.28 | 114.17 | 106.10 | 0.00 | 0.00 |
December | 132.50 | 435.21 | 178.93 | 89.52 | 89.40 | 0.00 | 0.00 |
Annual Sum or Average | 339.06 | 231.86 | 306.64 | 126.46 | 180.19 | 0.00 | 0.00 |
Minimum of Months | 132.50 | 51.87 | 178.93 | 89.52 | 89.40 | 0.00 | 0.00 |
Maximum of Months | 625.67 | 435.21 | 454.56 | 183.84 | 273.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 463.58 | 185.75 | 411.90 | 339.08 | 72.83 | 0.00 | 0.00 |
February | 432.55 | 197.11 | 389.76 | 309.90 | 79.86 | 0.00 | 0.00 |
March | 329.52 | 153.37 | 292.78 | 193.50 | 99.28 | 0.00 | 0.00 |
April | 197.96 | 137.60 | 191.71 | 79.31 | 112.40 | 0.00 | 0.00 |
May | 203.07 | 75.18 | 174.21 | 33.50 | 140.71 | 0.00 | 0.00 |
June | 237.77 | 31.31 | 158.38 | 28.59 | 129.79 | 0.00 | 0.00 |
July | 246.49 | 26.80 | 163.59 | 27.87 | 135.72 | 0.00 | 0.00 |
August | 307.66 | 32.44 | 208.15 | 85.63 | 122.51 | 0.00 | 0.00 |
September | 372.62 | 58.51 | 273.42 | 153.69 | 119.73 | 0.00 | 0.00 |
October | 386.92 | 146.19 | 322.75 | 228.68 | 94.07 | 0.00 | 0.00 |
November | 456.94 | 173.95 | 395.60 | 315.54 | 80.06 | 0.00 | 0.00 |
December | 412.19 | 216.22 | 377.53 | 305.62 | 71.91 | 0.00 | 0.00 |
Annual Sum or Average | 336.72 | 119.11 | 279.36 | 174.31 | 105.05 | 0.00 | 0.00 |
Minimum of Months | 197.96 | 26.80 | 158.38 | 27.87 | 71.91 | 0.00 | 0.00 |
Maximum of Months | 463.58 | 216.22 | 411.90 | 339.08 | 140.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 33.26 | 1093.05 | 204.38 | 0.00 | 204.38 | 0.00 | 0.00 |
February | 39.68 | 1128.06 | 256.88 | 0.00 | 256.88 | 0.00 | 0.00 |
March | 145.60 | 857.59 | 349.64 | 0.02 | 349.63 | 0.00 | 0.00 |
April | 226.61 | 747.73 | 439.52 | 2.88 | 436.64 | 0.00 | 0.00 |
May | 540.25 | 401.97 | 600.41 | 20.14 | 580.28 | 0.00 | 0.00 |
June | 895.04 | 193.21 | 658.28 | 73.61 | 584.67 | 0.00 | 0.00 |
July | 863.99 | 178.35 | 624.37 | 42.62 | 581.75 | 0.00 | 0.00 |
August | 658.16 | 210.44 | 497.11 | 13.45 | 483.66 | 0.00 | 0.00 |
September | 487.24 | 349.59 | 416.23 | 0.33 | 415.90 | 0.00 | 0.00 |
October | 162.56 | 808.46 | 297.79 | 0.00 | 297.79 | 0.00 | 0.00 |
November | 56.09 | 985.75 | 226.06 | 0.00 | 226.06 | 0.00 | 0.00 |
December | 26.32 | 1259.33 | 191.22 | 0.00 | 191.22 | 0.00 | 0.00 |
Annual Sum or Average | 346.29 | 682.08 | 397.56 | 12.79 | 384.77 | 0.00 | 0.00 |
Minimum of Months | 26.32 | 178.35 | 191.22 | 0.00 | 191.22 | 0.00 | 0.00 |
Maximum of Months | 895.04 | 1259.33 | 658.28 | 73.61 | 584.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 29.48 | 1127.22 | 204.38 | 0.00 | 204.38 | 0.00 | 0.00 |
February | 35.35 | 1163.26 | 256.88 | 0.00 | 256.88 | 0.00 | 0.00 |
March | 136.50 | 885.76 | 349.64 | 0.02 | 349.63 | 0.00 | 0.00 |
April | 214.95 | 773.64 | 439.52 | 2.88 | 436.64 | 0.00 | 0.00 |
May | 524.77 | 412.32 | 600.41 | 20.14 | 580.28 | 0.00 | 0.00 |
June | 881.16 | 198.91 | 658.28 | 73.61 | 584.67 | 0.00 | 0.00 |
July | 850.34 | 184.36 | 624.37 | 42.62 | 581.75 | 0.00 | 0.00 |
August | 645.21 | 217.35 | 497.11 | 13.45 | 483.66 | 0.00 | 0.00 |
September | 475.79 | 359.64 | 416.23 | 0.33 | 415.90 | 0.00 | 0.00 |
October | 154.97 | 831.46 | 297.79 | 0.00 | 297.79 | 0.00 | 0.00 |
November | 51.45 | 1017.55 | 226.06 | 0.00 | 226.06 | 0.00 | 0.00 |
December | 23.20 | 1295.73 | 191.22 | 0.00 | 191.22 | 0.00 | 0.00 |
Annual Sum or Average | 336.95 | 703.13 | 397.56 | 12.79 | 384.77 | 0.00 | 0.00 |
Minimum of Months | 23.20 | 184.36 | 191.22 | 0.00 | 191.22 | 0.00 | 0.00 |
Maximum of Months | 881.16 | 1295.73 | 658.28 | 73.61 | 584.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 620.74 | 742.65 | 650.36 | 439.34 | 211.02 | 0.00 | 0.00 |
February | 728.33 | 803.09 | 758.66 | 500.04 | 258.63 | 0.00 | 0.00 |
March | 833.74 | 632.28 | 799.13 | 452.71 | 346.42 | 0.00 | 0.00 |
April | 762.35 | 570.43 | 754.50 | 327.72 | 426.78 | 0.00 | 0.00 |
May | 1060.83 | 319.04 | 862.23 | 301.05 | 561.19 | 0.00 | 0.00 |
June | 1503.44 | 160.12 | 1002.30 | 450.02 | 552.28 | 0.00 | 0.00 |
July | 1417.32 | 147.83 | 927.13 | 370.26 | 556.87 | 0.00 | 0.00 |
August | 1425.27 | 165.94 | 947.42 | 464.97 | 482.45 | 0.00 | 0.00 |
September | 1217.03 | 257.29 | 858.01 | 437.57 | 420.44 | 0.00 | 0.00 |
October | 806.92 | 598.12 | 705.56 | 398.86 | 306.71 | 0.00 | 0.00 |
November | 659.82 | 700.00 | 645.77 | 408.86 | 236.91 | 0.00 | 0.00 |
December | 519.08 | 886.53 | 582.85 | 380.18 | 202.68 | 0.00 | 0.00 |
Annual Sum or Average | 964.04 | 496.95 | 791.17 | 410.29 | 380.88 | 0.00 | 0.00 |
Minimum of Months | 519.08 | 147.83 | 582.85 | 301.05 | 202.68 | 0.00 | 0.00 |
Maximum of Months | 1503.44 | 886.53 | 1002.30 | 500.04 | 561.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1153.40 | 804.94 | 1118.58 | 863.14 | 255.44 | 0.00 | 0.00 |
February | 1085.90 | 860.94 | 1080.22 | 788.87 | 291.35 | 0.00 | 0.00 |
March | 879.75 | 694.25 | 865.14 | 492.56 | 372.58 | 0.00 | 0.00 |
April | 576.67 | 629.42 | 638.68 | 202.88 | 435.80 | 0.00 | 0.00 |
May | 675.08 | 366.62 | 649.28 | 92.18 | 557.10 | 0.00 | 0.00 |
June | 869.93 | 179.37 | 628.84 | 98.02 | 530.82 | 0.00 | 0.00 |
July | 884.26 | 164.76 | 630.46 | 85.55 | 544.91 | 0.00 | 0.00 |
August | 977.32 | 195.76 | 700.26 | 222.60 | 477.67 | 0.00 | 0.00 |
September | 1092.71 | 312.37 | 838.69 | 391.34 | 447.36 | 0.00 | 0.00 |
October | 1026.17 | 675.71 | 923.66 | 582.11 | 341.55 | 0.00 | 0.00 |
November | 1160.36 | 766.26 | 1084.51 | 803.22 | 281.29 | 0.00 | 0.00 |
December | 1020.73 | 936.88 | 1026.58 | 777.98 | 248.60 | 0.00 | 0.00 |
Annual Sum or Average | 949.35 | 547.22 | 847.40 | 448.09 | 399.31 | 0.00 | 0.00 |
Minimum of Months | 576.67 | 164.76 | 628.84 | 85.55 | 248.60 | 0.00 | 0.00 |
Maximum of Months | 1160.36 | 936.88 | 1118.58 | 863.14 | 557.10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.428605E+10 | 0.170933E+10 | 0.380465E+10 | 0.313198E+10 | 0.672671E+09 | 0.00 | 0.00 |
February | 0.363074E+10 | 0.161300E+10 | 0.325173E+10 | 0.258549E+10 | 0.666247E+09 | 0.00 | 0.00 |
March | 0.304919E+10 | 0.142263E+10 | 0.270430E+10 | 0.178728E+10 | 0.917025E+09 | 0.00 | 0.00 |
April | 0.176976E+10 | 0.123448E+10 | 0.171366E+10 | 0.708940E+09 | 0.100472E+10 | 0.00 | 0.00 |
May | 0.182741E+10 | 0.760764E+09 | 0.160910E+10 | 0.309432E+09 | 0.129967E+10 | 0.00 | 0.00 |
June | 0.200348E+10 | 0.399629E+09 | 0.141576E+10 | 0.255570E+09 | 0.116019E+10 | 0.00 | 0.00 |
July | 0.214982E+10 | 0.370925E+09 | 0.151105E+10 | 0.257418E+09 | 0.125363E+10 | 0.00 | 0.00 |
August | 0.274112E+10 | 0.431417E+09 | 0.192261E+10 | 0.790983E+09 | 0.113163E+10 | 0.00 | 0.00 |
September | 0.326371E+10 | 0.645095E+09 | 0.244404E+10 | 0.137379E+10 | 0.107025E+10 | 0.00 | 0.00 |
October | 0.355480E+10 | 0.138929E+10 | 0.298116E+10 | 0.211225E+10 | 0.868910E+09 | 0.00 | 0.00 |
November | 0.408676E+10 | 0.155477E+10 | 0.353618E+10 | 0.282056E+10 | 0.715622E+09 | 0.00 | 0.00 |
December | 0.384544E+10 | 0.193755E+10 | 0.348719E+10 | 0.282298E+10 | 0.664211E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.362083E+11 | 0.134689E+11 | 0.303814E+11 | 0.189567E+11 | 0.114248E+11 | 0.00 | 0.00 |
Minimum of Months | 0.176976E+10 | 0.370925E+09 | 0.141576E+10 | 0.255570E+09 | 0.664211E+09 | 0.00 | 0.00 |
Maximum of Months | 0.428605E+10 | 0.193755E+10 | 0.380465E+10 | 0.313198E+10 | 0.129967E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.120057E+11 | 0.492442E+10 | 0.107137E+11 | 0.881946E+10 | 0.189420E+10 | 0.00 | 0.00 |
February | 0.101681E+11 | 0.462943E+10 | 0.915667E+10 | 0.728056E+10 | 0.187611E+10 | 0.00 | 0.00 |
March | 0.854024E+10 | 0.410146E+10 | 0.761514E+10 | 0.503286E+10 | 0.258228E+10 | 0.00 | 0.00 |
April | 0.495919E+10 | 0.357110E+10 | 0.482554E+10 | 0.199633E+10 | 0.282922E+10 | 0.00 | 0.00 |
May | 0.517686E+10 | 0.215749E+10 | 0.453111E+10 | 0.871340E+09 | 0.365977E+10 | 0.00 | 0.00 |
June | 0.569409E+10 | 0.109810E+10 | 0.398667E+10 | 0.719668E+09 | 0.326701E+10 | 0.00 | 0.00 |
July | 0.609696E+10 | 0.102062E+10 | 0.425500E+10 | 0.724873E+09 | 0.353013E+10 | 0.00 | 0.00 |
August | 0.773379E+10 | 0.119816E+10 | 0.541394E+10 | 0.222736E+10 | 0.318659E+10 | 0.00 | 0.00 |
September | 0.917888E+10 | 0.181552E+10 | 0.688226E+10 | 0.386850E+10 | 0.301376E+10 | 0.00 | 0.00 |
October | 0.996806E+10 | 0.398110E+10 | 0.839476E+10 | 0.594797E+10 | 0.244679E+10 | 0.00 | 0.00 |
November | 0.114521E+11 | 0.446829E+10 | 0.995764E+10 | 0.794250E+10 | 0.201515E+10 | 0.00 | 0.00 |
December | 0.107721E+11 | 0.557029E+10 | 0.981969E+10 | 0.794932E+10 | 0.187038E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.101746E+12 | 0.385360E+11 | 0.855521E+11 | 0.533807E+11 | 0.321714E+11 | 0.00 | 0.00 |
Minimum of Months | 0.495919E+10 | 0.102062E+10 | 0.398667E+10 | 0.719668E+09 | 0.187038E+10 | 0.00 | 0.00 |
Maximum of Months | 0.120057E+11 | 0.557029E+10 | 0.107137E+11 | 0.881946E+10 | 0.365977E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.158311E+11 | 0.664379E+10 | 0.139177E+11 | 0.114570E+11 | 0.246067E+10 | 0.00 | 0.00 |
February | 0.134290E+11 | 0.625557E+10 | 0.118950E+11 | 0.945786E+10 | 0.243717E+10 | 0.00 | 0.00 |
March | 0.112779E+11 | 0.559505E+10 | 0.989250E+10 | 0.653797E+10 | 0.335453E+10 | 0.00 | 0.00 |
April | 0.653630E+10 | 0.495443E+10 | 0.626865E+10 | 0.259334E+10 | 0.367531E+10 | 0.00 | 0.00 |
May | 0.678476E+10 | 0.300050E+10 | 0.588617E+10 | 0.113192E+10 | 0.475425E+10 | 0.00 | 0.00 |
June | 0.752110E+10 | 0.147966E+10 | 0.517892E+10 | 0.934890E+09 | 0.424403E+10 | 0.00 | 0.00 |
July | 0.805690E+10 | 0.137271E+10 | 0.552749E+10 | 0.941651E+09 | 0.458584E+10 | 0.00 | 0.00 |
August | 0.102305E+11 | 0.158881E+10 | 0.703302E+10 | 0.289346E+10 | 0.413956E+10 | 0.00 | 0.00 |
September | 0.121285E+11 | 0.241652E+10 | 0.894045E+10 | 0.502541E+10 | 0.391504E+10 | 0.00 | 0.00 |
October | 0.131473E+11 | 0.540350E+10 | 0.109053E+11 | 0.772675E+10 | 0.317852E+10 | 0.00 | 0.00 |
November | 0.151039E+11 | 0.604830E+10 | 0.129355E+11 | 0.103178E+11 | 0.261779E+10 | 0.00 | 0.00 |
December | 0.142000E+11 | 0.752744E+10 | 0.127563E+11 | 0.103266E+11 | 0.242972E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.134247E+12 | 0.522863E+11 | 0.111137E+12 | 0.693446E+11 | 0.417924E+11 | 0.00 | 0.00 |
Minimum of Months | 0.653630E+10 | 0.137271E+10 | 0.517892E+10 | 0.934890E+09 | 0.242972E+10 | 0.00 | 0.00 |
Maximum of Months | 0.158311E+11 | 0.752744E+10 | 0.139177E+11 | 0.114570E+11 | 0.475425E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.126784E+10 | 0.960269E+09 | 0.123908E+10 | 0.927787E+09 | 0.311298E+09 | 0.00 | 0.00 |
February | 0.118265E+10 | 0.913073E+09 | 0.117414E+10 | 0.840713E+09 | 0.333422E+09 | 0.00 | 0.00 |
March | 0.127564E+10 | 0.783527E+09 | 0.122054E+10 | 0.731177E+09 | 0.489367E+09 | 0.00 | 0.00 |
April | 0.946397E+09 | 0.674235E+09 | 0.964852E+09 | 0.405358E+09 | 0.559494E+09 | 0.00 | 0.00 |
May | 0.127973E+10 | 0.390008E+09 | 0.110908E+10 | 0.340516E+09 | 0.768564E+09 | 0.00 | 0.00 |
June | 0.170555E+10 | 0.170736E+09 | 0.121439E+10 | 0.499776E+09 | 0.714612E+09 | 0.00 | 0.00 |
July | 0.154652E+10 | 0.150325E+09 | 0.108465E+10 | 0.337838E+09 | 0.746816E+09 | 0.00 | 0.00 |
August | 0.168378E+10 | 0.177754E+09 | 0.120308E+10 | 0.563068E+09 | 0.640014E+09 | 0.00 | 0.00 |
September | 0.157990E+10 | 0.302713E+09 | 0.119182E+10 | 0.612531E+09 | 0.579290E+09 | 0.00 | 0.00 |
October | 0.136547E+10 | 0.759410E+09 | 0.120259E+10 | 0.768092E+09 | 0.434495E+09 | 0.00 | 0.00 |
November | 0.126562E+10 | 0.865319E+09 | 0.118641E+10 | 0.853604E+09 | 0.332805E+09 | 0.00 | 0.00 |
December | 0.106385E+10 | 0.110769E+10 | 0.109554E+10 | 0.797925E+09 | 0.297618E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.161629E+11 | 0.725506E+10 | 0.138862E+11 | 0.767839E+10 | 0.620780E+10 | 0.00 | 0.00 |
Minimum of Months | 0.946397E+09 | 0.150325E+09 | 0.964852E+09 | 0.337838E+09 | 0.297618E+09 | 0.00 | 0.00 |
Maximum of Months | 0.170555E+10 | 0.110769E+10 | 0.123908E+10 | 0.927787E+09 | 0.768564E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.469392E+09 | 0.101537E+10 | 0.565044E+09 | 0.308540E+09 | 0.256504E+09 | 0.00 | 0.00 |
February | 0.505059E+09 | 0.947313E+09 | 0.619992E+09 | 0.329518E+09 | 0.290474E+09 | 0.00 | 0.00 |
March | 0.747083E+09 | 0.792822E+09 | 0.819644E+09 | 0.377808E+09 | 0.441835E+09 | 0.00 | 0.00 |
April | 0.695307E+09 | 0.668851E+09 | 0.788786E+09 | 0.266255E+09 | 0.522531E+09 | 0.00 | 0.00 |
May | 0.113136E+10 | 0.376539E+09 | 0.102068E+10 | 0.287041E+09 | 0.733634E+09 | 0.00 | 0.00 |
June | 0.162823E+10 | 0.160559E+09 | 0.117823E+10 | 0.476505E+09 | 0.701723E+09 | 0.00 | 0.00 |
July | 0.144061E+10 | 0.143510E+09 | 0.102480E+10 | 0.303250E+09 | 0.721551E+09 | 0.00 | 0.00 |
August | 0.138772E+10 | 0.172697E+09 | 0.101316E+10 | 0.411825E+09 | 0.601338E+09 | 0.00 | 0.00 |
September | 0.111459E+10 | 0.299459E+09 | 0.862721E+09 | 0.341032E+09 | 0.521689E+09 | 0.00 | 0.00 |
October | 0.737225E+09 | 0.762223E+09 | 0.727106E+09 | 0.350463E+09 | 0.376643E+09 | 0.00 | 0.00 |
November | 0.500024E+09 | 0.887338E+09 | 0.570956E+09 | 0.295932E+09 | 0.275024E+09 | 0.00 | 0.00 |
December | 0.352853E+09 | 0.117235E+10 | 0.479236E+09 | 0.239774E+09 | 0.239462E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107095E+11 | 0.739903E+10 | 0.967035E+10 | 0.398795E+10 | 0.568241E+10 | 0.00 | 0.00 |
Minimum of Months | 0.352853E+09 | 0.143510E+09 | 0.479236E+09 | 0.239774E+09 | 0.239462E+09 | 0.00 | 0.00 |
Maximum of Months | 0.162823E+10 | 0.117235E+10 | 0.117823E+10 | 0.476505E+09 | 0.733634E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.680062E+09 | 0.285593E+09 | 0.601678E+09 | 0.495299E+09 | 0.106379E+09 | 0.00 | 0.00 |
February | 0.574952E+09 | 0.265657E+09 | 0.514238E+09 | 0.408875E+09 | 0.105363E+09 | 0.00 | 0.00 |
March | 0.485232E+09 | 0.229506E+09 | 0.427666E+09 | 0.282644E+09 | 0.145022E+09 | 0.00 | 0.00 |
April | 0.283360E+09 | 0.198546E+09 | 0.271003E+09 | 0.112113E+09 | 0.158890E+09 | 0.00 | 0.00 |
May | 0.293081E+09 | 0.123455E+09 | 0.254468E+09 | 48934276.29 | 0.205534E+09 | 0.00 | 0.00 |
June | 0.329531E+09 | 58586779.49 | 0.223893E+09 | 40416423.07 | 0.183477E+09 | 0.00 | 0.00 |
July | 0.353144E+09 | 53747360.88 | 0.238962E+09 | 40708703.25 | 0.198254E+09 | 0.00 | 0.00 |
August | 0.445110E+09 | 63114755.07 | 0.304048E+09 | 0.125088E+09 | 0.178960E+09 | 0.00 | 0.00 |
September | 0.524690E+09 | 99748093.35 | 0.386508E+09 | 0.217254E+09 | 0.169254E+09 | 0.00 | 0.00 |
October | 0.566700E+09 | 0.226648E+09 | 0.471449E+09 | 0.334037E+09 | 0.137413E+09 | 0.00 | 0.00 |
November | 0.650078E+09 | 0.257967E+09 | 0.559220E+09 | 0.446049E+09 | 0.113171E+09 | 0.00 | 0.00 |
December | 0.608387E+09 | 0.320868E+09 | 0.551473E+09 | 0.446432E+09 | 0.105041E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.579433E+10 | 0.218344E+10 | 0.480461E+10 | 0.299785E+10 | 0.180676E+10 | 0.00 | 0.00 |
Minimum of Months | 0.283360E+09 | 53747360.88 | 0.223893E+09 | 40416423.07 | 0.105041E+09 | 0.00 | 0.00 |
Maximum of Months | 0.680062E+09 | 0.320868E+09 | 0.601678E+09 | 0.495299E+09 | 0.205534E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 13927769.33 | 0.304469E+09 | 62572574.96 | 0.00 | 62572574.96 | 0.00 | 0.00 |
February | 15699594.85 | 0.283254E+09 | 71035352.99 | 0.00 | 71035352.99 | 0.00 | 0.00 |
March | 53946431.57 | 0.232190E+09 | 0.107045E+09 | 5523.69 | 0.107040E+09 | 0.00 | 0.00 |
April | 77844402.22 | 0.192484E+09 | 0.130222E+09 | 853207.10 | 0.129368E+09 | 0.00 | 0.00 |
May | 0.184467E+09 | 0.101017E+09 | 0.183819E+09 | 6164948.81 | 0.177654E+09 | 0.00 | 0.00 |
June | 0.286007E+09 | 39879613.01 | 0.195035E+09 | 21810480.60 | 0.173225E+09 | 0.00 | 0.00 |
July | 0.285355E+09 | 35920033.10 | 0.191153E+09 | 13048148.50 | 0.178104E+09 | 0.00 | 0.00 |
August | 0.220099E+09 | 43424333.67 | 0.152193E+09 | 4118668.79 | 0.148074E+09 | 0.00 | 0.00 |
September | 0.158664E+09 | 79559344.30 | 0.123321E+09 | 98489.96 | 0.123223E+09 | 0.00 | 0.00 |
October | 58903971.41 | 0.216868E+09 | 91170274.99 | 0.00 | 91170274.99 | 0.00 | 0.00 |
November | 21848498.08 | 0.261588E+09 | 66977226.59 | 0.00 | 66977226.59 | 0.00 | 0.00 |
December | 11095510.99 | 0.353722E+09 | 58544410.09 | 0.00 | 58544410.09 | 0.00 | 0.00 |
Annual Sum or Average | 0.138786E+10 | 0.214437E+10 | 0.143309E+10 | 46099467.45 | 0.138699E+10 | 0.00 | 0.00 |
Minimum of Months | 11095510.99 | 35920033.10 | 58544410.09 | 0.00 | 58544410.09 | 0.00 | 0.00 |
Maximum of Months | 0.286007E+09 | 0.353722E+09 | 0.195035E+09 | 21810480.60 | 0.178104E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.121419E+10 | 0.950129E+09 | 0.120801E+10 | 0.898011E+09 | 0.310003E+09 | 0.00 | 0.00 |
February | 0.120309E+10 | 0.909474E+09 | 0.119479E+10 | 0.860466E+09 | 0.334324E+09 | 0.00 | 0.00 |
March | 0.133244E+10 | 0.778016E+09 | 0.127070E+10 | 0.782987E+09 | 0.487711E+09 | 0.00 | 0.00 |
April | 0.106016E+10 | 0.661554E+09 | 0.106592E+10 | 0.494303E+09 | 0.571619E+09 | 0.00 | 0.00 |
May | 0.136963E+10 | 0.368681E+09 | 0.119897E+10 | 0.429924E+09 | 0.769043E+09 | 0.00 | 0.00 |
June | 0.182436E+10 | 0.155930E+09 | 0.131713E+10 | 0.594894E+09 | 0.722240E+09 | 0.00 | 0.00 |
July | 0.178653E+10 | 0.141864E+09 | 0.127160E+10 | 0.513177E+09 | 0.758426E+09 | 0.00 | 0.00 |
August | 0.189412E+10 | 0.171716E+09 | 0.136381E+10 | 0.698346E+09 | 0.665469E+09 | 0.00 | 0.00 |
September | 0.167585E+10 | 0.289418E+09 | 0.127659E+10 | 0.702872E+09 | 0.573721E+09 | 0.00 | 0.00 |
October | 0.132814E+10 | 0.751369E+09 | 0.118267E+10 | 0.742987E+09 | 0.439687E+09 | 0.00 | 0.00 |
November | 0.120682E+10 | 0.859559E+09 | 0.114467E+10 | 0.808738E+09 | 0.335935E+09 | 0.00 | 0.00 |
December | 0.105532E+10 | 0.110905E+10 | 0.108874E+10 | 0.788225E+09 | 0.300514E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.169506E+11 | 0.714676E+10 | 0.145836E+11 | 0.831493E+10 | 0.626869E+10 | 0.00 | 0.00 |
Minimum of Months | 0.105532E+10 | 0.141864E+09 | 0.106592E+10 | 0.429924E+09 | 0.300514E+09 | 0.00 | 0.00 |
Maximum of Months | 0.189412E+10 | 0.110905E+10 | 0.136381E+10 | 0.898011E+09 | 0.769043E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.400169E+09 | 0.986477E+09 | 0.533973E+09 | 0.278765E+09 | 0.255208E+09 | 0.00 | 0.00 |
February | 0.516698E+09 | 0.934240E+09 | 0.640647E+09 | 0.349271E+09 | 0.291376E+09 | 0.00 | 0.00 |
March | 0.790867E+09 | 0.776353E+09 | 0.869798E+09 | 0.429618E+09 | 0.440180E+09 | 0.00 | 0.00 |
April | 0.806242E+09 | 0.655459E+09 | 0.889856E+09 | 0.355199E+09 | 0.534656E+09 | 0.00 | 0.00 |
May | 0.122777E+10 | 0.363049E+09 | 0.111056E+10 | 0.376449E+09 | 0.734112E+09 | 0.00 | 0.00 |
June | 0.175572E+10 | 0.154622E+09 | 0.128097E+10 | 0.571623E+09 | 0.709351E+09 | 0.00 | 0.00 |
July | 0.168591E+10 | 0.140729E+09 | 0.121175E+10 | 0.478590E+09 | 0.733161E+09 | 0.00 | 0.00 |
August | 0.159907E+10 | 0.168663E+09 | 0.117389E+10 | 0.547102E+09 | 0.626792E+09 | 0.00 | 0.00 |
September | 0.120651E+10 | 0.284532E+09 | 0.947493E+09 | 0.431373E+09 | 0.516120E+09 | 0.00 | 0.00 |
October | 0.689873E+09 | 0.746437E+09 | 0.707193E+09 | 0.325358E+09 | 0.381835E+09 | 0.00 | 0.00 |
November | 0.434017E+09 | 0.872514E+09 | 0.529219E+09 | 0.251066E+09 | 0.278153E+09 | 0.00 | 0.00 |
December | 0.327669E+09 | 0.115414E+10 | 0.472432E+09 | 0.230075E+09 | 0.242358E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114405E+11 | 0.723722E+10 | 0.103678E+11 | 0.462449E+10 | 0.574330E+10 | 0.00 | 0.00 |
Minimum of Months | 0.327669E+09 | 0.140729E+09 | 0.472432E+09 | 0.230075E+09 | 0.242358E+09 | 0.00 | 0.00 |
Maximum of Months | 0.175572E+10 | 0.115414E+10 | 0.128097E+10 | 0.571623E+09 | 0.734112E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.142678E+10 | 0.122971E+10 | 0.143922E+10 | 0.107318E+10 | 0.366046E+09 | 0.00 | 0.00 |
February | 0.122673E+10 | 0.117531E+10 | 0.126810E+10 | 0.885918E+09 | 0.382179E+09 | 0.00 | 0.00 |
March | 0.114434E+10 | 0.105004E+10 | 0.115853E+10 | 0.612423E+09 | 0.546106E+09 | 0.00 | 0.00 |
April | 0.770350E+09 | 0.903522E+09 | 0.869292E+09 | 0.244767E+09 | 0.624525E+09 | 0.00 | 0.00 |
May | 0.100107E+10 | 0.529477E+09 | 0.949576E+09 | 0.119382E+09 | 0.830194E+09 | 0.00 | 0.00 |
June | 0.127437E+10 | 0.250731E+09 | 0.907626E+09 | 0.134820E+09 | 0.772806E+09 | 0.00 | 0.00 |
July | 0.132608E+10 | 0.237254E+09 | 0.931865E+09 | 0.116471E+09 | 0.815394E+09 | 0.00 | 0.00 |
August | 0.139232E+10 | 0.283868E+09 | 0.988489E+09 | 0.279953E+09 | 0.708536E+09 | 0.00 | 0.00 |
September | 0.144333E+10 | 0.449923E+09 | 0.110461E+10 | 0.470943E+09 | 0.633667E+09 | 0.00 | 0.00 |
October | 0.132466E+10 | 0.102461E+10 | 0.121900E+10 | 0.723764E+09 | 0.495240E+09 | 0.00 | 0.00 |
November | 0.141091E+10 | 0.112428E+10 | 0.135677E+10 | 0.966464E+09 | 0.390305E+09 | 0.00 | 0.00 |
December | 0.126396E+10 | 0.141636E+10 | 0.132171E+10 | 0.967294E+09 | 0.354421E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.150049E+11 | 0.967508E+10 | 0.135148E+11 | 0.659538E+10 | 0.691942E+10 | 0.00 | 0.00 |
Minimum of Months | 0.770350E+09 | 0.237254E+09 | 0.869292E+09 | 0.116471E+09 | 0.354421E+09 | 0.00 | 0.00 |
Maximum of Months | 0.144333E+10 | 0.141636E+10 | 0.143922E+10 | 0.107318E+10 | 0.830194E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.126767E+10 | 0.951729E+09 | 0.123908E+10 | 0.927787E+09 | 0.311298E+09 | 0.00 | 0.00 |
February | 0.117835E+10 | 0.909880E+09 | 0.117414E+10 | 0.840713E+09 | 0.333422E+09 | 0.00 | 0.00 |
March | 0.127040E+10 | 0.777676E+09 | 0.122054E+10 | 0.731177E+09 | 0.489367E+09 | 0.00 | 0.00 |
April | 0.941590E+09 | 0.668633E+09 | 0.964852E+09 | 0.405358E+09 | 0.559494E+09 | 0.00 | 0.00 |
May | 0.127400E+10 | 0.384970E+09 | 0.110908E+10 | 0.340516E+09 | 0.768564E+09 | 0.00 | 0.00 |
June | 0.169804E+10 | 0.166080E+09 | 0.121439E+10 | 0.499776E+09 | 0.714612E+09 | 0.00 | 0.00 |
July | 0.154038E+10 | 0.145329E+09 | 0.108465E+10 | 0.337838E+09 | 0.746816E+09 | 0.00 | 0.00 |
August | 0.167621E+10 | 0.172516E+09 | 0.120308E+10 | 0.563068E+09 | 0.640014E+09 | 0.00 | 0.00 |
September | 0.157475E+10 | 0.295600E+09 | 0.119182E+10 | 0.612531E+09 | 0.579290E+09 | 0.00 | 0.00 |
October | 0.136227E+10 | 0.750736E+09 | 0.120259E+10 | 0.768092E+09 | 0.434495E+09 | 0.00 | 0.00 |
November | 0.126273E+10 | 0.858207E+09 | 0.118641E+10 | 0.853604E+09 | 0.332805E+09 | 0.00 | 0.00 |
December | 0.106175E+10 | 0.110353E+10 | 0.109554E+10 | 0.797925E+09 | 0.297618E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.161081E+11 | 0.718489E+10 | 0.138862E+11 | 0.767839E+10 | 0.620780E+10 | 0.00 | 0.00 |
Minimum of Months | 0.941590E+09 | 0.145329E+09 | 0.964852E+09 | 0.337838E+09 | 0.297618E+09 | 0.00 | 0.00 |
Maximum of Months | 0.169804E+10 | 0.110353E+10 | 0.123908E+10 | 0.927787E+09 | 0.768564E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.472888E+09 | 0.100315E+10 | 0.565044E+09 | 0.308540E+09 | 0.256504E+09 | 0.00 | 0.00 |
February | 0.505608E+09 | 0.941506E+09 | 0.619992E+09 | 0.329518E+09 | 0.290474E+09 | 0.00 | 0.00 |
March | 0.746098E+09 | 0.785412E+09 | 0.819644E+09 | 0.377808E+09 | 0.441835E+09 | 0.00 | 0.00 |
April | 0.692900E+09 | 0.662645E+09 | 0.788786E+09 | 0.266255E+09 | 0.522531E+09 | 0.00 | 0.00 |
May | 0.112701E+10 | 0.371278E+09 | 0.102068E+10 | 0.287041E+09 | 0.733634E+09 | 0.00 | 0.00 |
June | 0.162174E+10 | 0.156459E+09 | 0.117823E+10 | 0.476505E+09 | 0.701723E+09 | 0.00 | 0.00 |
July | 0.143549E+10 | 0.138941E+09 | 0.102480E+10 | 0.303250E+09 | 0.721551E+09 | 0.00 | 0.00 |
August | 0.138225E+10 | 0.167476E+09 | 0.101316E+10 | 0.411825E+09 | 0.601338E+09 | 0.00 | 0.00 |
September | 0.111306E+10 | 0.291504E+09 | 0.862721E+09 | 0.341032E+09 | 0.521689E+09 | 0.00 | 0.00 |
October | 0.738797E+09 | 0.750975E+09 | 0.727106E+09 | 0.350463E+09 | 0.376643E+09 | 0.00 | 0.00 |
November | 0.502005E+09 | 0.877007E+09 | 0.570956E+09 | 0.295932E+09 | 0.275024E+09 | 0.00 | 0.00 |
December | 0.354882E+09 | 0.116566E+10 | 0.479236E+09 | 0.239774E+09 | 0.239462E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106927E+11 | 0.731201E+10 | 0.967035E+10 | 0.398795E+10 | 0.568241E+10 | 0.00 | 0.00 |
Minimum of Months | 0.354882E+09 | 0.138941E+09 | 0.479236E+09 | 0.239774E+09 | 0.239462E+09 | 0.00 | 0.00 |
Maximum of Months | 0.162174E+10 | 0.116566E+10 | 0.117823E+10 | 0.476505E+09 | 0.733634E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.124165E+10 | 0.497506E+09 | 0.110324E+10 | 0.908185E+09 | 0.195057E+09 | 0.00 | 0.00 |
February | 0.104644E+10 | 0.476854E+09 | 0.942911E+09 | 0.749717E+09 | 0.193195E+09 | 0.00 | 0.00 |
March | 0.882596E+09 | 0.410779E+09 | 0.784173E+09 | 0.518259E+09 | 0.265914E+09 | 0.00 | 0.00 |
April | 0.513117E+09 | 0.356668E+09 | 0.496914E+09 | 0.205572E+09 | 0.291342E+09 | 0.00 | 0.00 |
May | 0.543915E+09 | 0.201358E+09 | 0.466596E+09 | 89726356.12 | 0.376869E+09 | 0.00 | 0.00 |
June | 0.616298E+09 | 81143360.01 | 0.410533E+09 | 74107939.14 | 0.336425E+09 | 0.00 | 0.00 |
July | 0.660209E+09 | 71792894.57 | 0.438164E+09 | 74643866.89 | 0.363520E+09 | 0.00 | 0.00 |
August | 0.824044E+09 | 86895051.11 | 0.557506E+09 | 0.229362E+09 | 0.328143E+09 | 0.00 | 0.00 |
September | 0.965818E+09 | 0.151651E+09 | 0.708705E+09 | 0.398360E+09 | 0.310345E+09 | 0.00 | 0.00 |
October | 0.103633E+10 | 0.391550E+09 | 0.864454E+09 | 0.612493E+09 | 0.251961E+09 | 0.00 | 0.00 |
November | 0.118438E+10 | 0.450891E+09 | 0.102539E+10 | 0.817880E+09 | 0.207512E+09 | 0.00 | 0.00 |
December | 0.110400E+10 | 0.579131E+09 | 0.101119E+10 | 0.818582E+09 | 0.192604E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106188E+11 | 0.375622E+10 | 0.880977E+10 | 0.549689E+10 | 0.331288E+10 | 0.00 | 0.00 |
Minimum of Months | 0.513117E+09 | 71792894.57 | 0.410533E+09 | 74107939.14 | 0.192604E+09 | 0.00 | 0.00 |
Maximum of Months | 0.124165E+10 | 0.579131E+09 | 0.110324E+10 | 0.908185E+09 | 0.376869E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 89079395.94 | 0.292762E+10 | 0.547417E+09 | 0.00 | 0.547417E+09 | 0.00 | 0.00 |
February | 96000025.99 | 0.272899E+10 | 0.621453E+09 | 0.00 | 0.621453E+09 | 0.00 | 0.00 |
March | 0.389966E+09 | 0.229697E+10 | 0.936486E+09 | 48324.03 | 0.936437E+09 | 0.00 | 0.00 |
April | 0.587384E+09 | 0.193811E+10 | 0.113925E+10 | 7464289.97 | 0.113178E+10 | 0.00 | 0.00 |
May | 0.144702E+10 | 0.107663E+10 | 0.160814E+10 | 53934109.78 | 0.155421E+10 | 0.00 | 0.00 |
June | 0.231996E+10 | 0.500798E+09 | 0.170627E+10 | 0.190809E+09 | 0.151546E+10 | 0.00 | 0.00 |
July | 0.231411E+10 | 0.477697E+09 | 0.167230E+10 | 0.114152E+09 | 0.155815E+10 | 0.00 | 0.00 |
August | 0.176281E+10 | 0.563645E+09 | 0.133146E+10 | 36032210.72 | 0.129543E+10 | 0.00 | 0.00 |
September | 0.126293E+10 | 0.906136E+09 | 0.107888E+10 | 861640.30 | 0.107802E+10 | 0.00 | 0.00 |
October | 0.435404E+09 | 0.216539E+10 | 0.797604E+09 | 0.00 | 0.797604E+09 | 0.00 | 0.00 |
November | 0.145384E+09 | 0.255506E+10 | 0.585951E+09 | 0.00 | 0.585951E+09 | 0.00 | 0.00 |
December | 70493015.16 | 0.337300E+10 | 0.512176E+09 | 0.00 | 0.512176E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109205E+11 | 0.215100E+11 | 0.125374E+11 | 0.403302E+09 | 0.121341E+11 | 0.00 | 0.00 |
Minimum of Months | 70493015.16 | 0.477697E+09 | 0.512176E+09 | 0.00 | 0.512176E+09 | 0.00 | 0.00 |
Maximum of Months | 0.231996E+10 | 0.337300E+10 | 0.170627E+10 | 0.190809E+09 | 0.155815E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 78951444.46 | 0.301914E+10 | 0.547417E+09 | 0.00 | 0.547417E+09 | 0.00 | 0.00 |
February | 85514157.86 | 0.281416E+10 | 0.621453E+09 | 0.00 | 0.621453E+09 | 0.00 | 0.00 |
March | 0.365589E+09 | 0.237243E+10 | 0.936486E+09 | 48324.03 | 0.936437E+09 | 0.00 | 0.00 |
April | 0.557151E+09 | 0.200527E+10 | 0.113925E+10 | 7464289.97 | 0.113178E+10 | 0.00 | 0.00 |
May | 0.140553E+10 | 0.110435E+10 | 0.160814E+10 | 53934109.78 | 0.155421E+10 | 0.00 | 0.00 |
June | 0.228395E+10 | 0.515580E+09 | 0.170627E+10 | 0.190809E+09 | 0.151546E+10 | 0.00 | 0.00 |
July | 0.227754E+10 | 0.493788E+09 | 0.167230E+10 | 0.114152E+09 | 0.155815E+10 | 0.00 | 0.00 |
August | 0.172812E+10 | 0.582138E+09 | 0.133146E+10 | 36032210.72 | 0.129543E+10 | 0.00 | 0.00 |
September | 0.123325E+10 | 0.932181E+09 | 0.107888E+10 | 861640.30 | 0.107802E+10 | 0.00 | 0.00 |
October | 0.415062E+09 | 0.222698E+10 | 0.797604E+09 | 0.00 | 0.797604E+09 | 0.00 | 0.00 |
November | 0.133358E+09 | 0.263749E+10 | 0.585951E+09 | 0.00 | 0.585951E+09 | 0.00 | 0.00 |
December | 62147297.41 | 0.347047E+10 | 0.512176E+09 | 0.00 | 0.512176E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106262E+11 | 0.221740E+11 | 0.125374E+11 | 0.403302E+09 | 0.121341E+11 | 0.00 | 0.00 |
Minimum of Months | 62147297.41 | 0.493788E+09 | 0.512176E+09 | 0.00 | 0.512176E+09 | 0.00 | 0.00 |
Maximum of Months | 0.228395E+10 | 0.347047E+10 | 0.170627E+10 | 0.190809E+09 | 0.155815E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.166258E+10 | 0.198910E+10 | 0.174192E+10 | 0.117674E+10 | 0.565186E+09 | 0.00 | 0.00 |
February | 0.176197E+10 | 0.194284E+10 | 0.183536E+10 | 0.120969E+10 | 0.625671E+09 | 0.00 | 0.00 |
March | 0.223308E+10 | 0.169349E+10 | 0.214039E+10 | 0.121254E+10 | 0.927847E+09 | 0.00 | 0.00 |
April | 0.197602E+10 | 0.147856E+10 | 0.195567E+10 | 0.849452E+09 | 0.110622E+10 | 0.00 | 0.00 |
May | 0.284133E+10 | 0.854525E+09 | 0.230940E+10 | 0.806321E+09 | 0.150308E+10 | 0.00 | 0.00 |
June | 0.389693E+10 | 0.415037E+09 | 0.259796E+10 | 0.116644E+10 | 0.143152E+10 | 0.00 | 0.00 |
July | 0.379616E+10 | 0.395952E+09 | 0.248322E+10 | 0.991701E+09 | 0.149151E+10 | 0.00 | 0.00 |
August | 0.381743E+10 | 0.444454E+09 | 0.253757E+10 | 0.124537E+10 | 0.129220E+10 | 0.00 | 0.00 |
September | 0.315455E+10 | 0.666889E+09 | 0.222397E+10 | 0.113418E+10 | 0.108979E+10 | 0.00 | 0.00 |
October | 0.216125E+10 | 0.160202E+10 | 0.188978E+10 | 0.106830E+10 | 0.821483E+09 | 0.00 | 0.00 |
November | 0.171026E+10 | 0.181439E+10 | 0.167383E+10 | 0.105977E+10 | 0.614060E+09 | 0.00 | 0.00 |
December | 0.139030E+10 | 0.237448E+10 | 0.156111E+10 | 0.101827E+10 | 0.542847E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.304019E+11 | 0.156717E+11 | 0.249502E+11 | 0.129388E+11 | 0.120114E+11 | 0.00 | 0.00 |
Minimum of Months | 0.139030E+10 | 0.395952E+09 | 0.156111E+10 | 0.806321E+09 | 0.542847E+09 | 0.00 | 0.00 |
Maximum of Months | 0.389693E+10 | 0.237448E+10 | 0.259796E+10 | 0.124537E+10 | 0.150308E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.308927E+10 | 0.215594E+10 | 0.299602E+10 | 0.231183E+10 | 0.684183E+09 | 0.00 | 0.00 |
February | 0.262701E+10 | 0.208279E+10 | 0.261327E+10 | 0.190844E+10 | 0.704822E+09 | 0.00 | 0.00 |
March | 0.235633E+10 | 0.185948E+10 | 0.231718E+10 | 0.131927E+10 | 0.997910E+09 | 0.00 | 0.00 |
April | 0.149472E+10 | 0.163146E+10 | 0.165546E+10 | 0.525853E+09 | 0.112960E+10 | 0.00 | 0.00 |
May | 0.180812E+10 | 0.981959E+09 | 0.173902E+10 | 0.246892E+09 | 0.149213E+10 | 0.00 | 0.00 |
June | 0.225486E+10 | 0.464930E+09 | 0.162994E+10 | 0.254055E+09 | 0.137589E+10 | 0.00 | 0.00 |
July | 0.236841E+10 | 0.441297E+09 | 0.168864E+10 | 0.229141E+09 | 0.145949E+10 | 0.00 | 0.00 |
August | 0.261766E+10 | 0.524334E+09 | 0.187559E+10 | 0.596206E+09 | 0.127938E+10 | 0.00 | 0.00 |
September | 0.283231E+10 | 0.809667E+09 | 0.217389E+10 | 0.101434E+10 | 0.115955E+10 | 0.00 | 0.00 |
October | 0.274850E+10 | 0.180981E+10 | 0.247393E+10 | 0.155913E+10 | 0.914801E+09 | 0.00 | 0.00 |
November | 0.300764E+10 | 0.198615E+10 | 0.281105E+10 | 0.208196E+10 | 0.729097E+09 | 0.00 | 0.00 |
December | 0.273393E+10 | 0.250933E+10 | 0.274960E+10 | 0.208374E+10 | 0.665858E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.299388E+11 | 0.172572E+11 | 0.267236E+11 | 0.141309E+11 | 0.125927E+11 | 0.00 | 0.00 |
Minimum of Months | 0.149472E+10 | 0.441297E+09 | 0.162994E+10 | 0.229141E+09 | 0.665858E+09 | 0.00 | 0.00 |
Maximum of Months | 0.308927E+10 | 0.250933E+10 | 0.299602E+10 | 0.231183E+10 | 0.149213E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770359E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160818855.9 | 81.21 | 0.00 | 0.00 |
February | 0.696123E+10 | -0.681597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -145263214.4 | 81.21 | 0.00 | 0.00 |
March | 0.770239E+10 | -0.754147E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160922107.7 | 81.21 | 0.00 | 0.00 |
April | 0.746434E+10 | -0.730860E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -155739967.5 | 81.21 | 0.00 | 0.00 |
May | 0.770409E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161287022.1 | 81.21 | 0.00 | 0.00 |
June | 0.745674E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156203141.2 | 81.21 | 0.00 | 0.00 |
July | 0.771226E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161412268.2 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161409932.1 | 81.21 | 0.00 | 0.00 |
September | 0.746611E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156170644.3 | 81.21 | 0.00 | 0.00 |
October | 0.770244E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161004739.4 | 81.21 | 0.00 | 0.00 |
November | 0.744800E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -155564478.1 | 81.21 | 0.00 | 0.00 |
December | 0.771185E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160999275.4 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907373E+11 | -0.888405E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.189680E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696123E+10 | -0.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161412268.2 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771226E+10 | -0.681597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -145263214.4 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.125052E+12 | -0.123322E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172989E+10 | 81.29 | 0.00 | 0.00 |
February | 0.113993E+12 | -0.112427E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.156569E+10 | 81.30 | 0.00 | 0.00 |
March | 0.124833E+12 | -0.123095E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173830E+10 | 81.29 | 0.00 | 0.00 |
April | 0.117441E+12 | -0.115760E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.168020E+10 | 81.27 | 0.00 | 0.00 |
May | 0.116732E+12 | -0.114994E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173829E+10 | 81.26 | 0.00 | 0.00 |
June | 0.108536E+12 | -0.106859E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167751E+10 | 81.25 | 0.00 | 0.00 |
July | 0.108850E+12 | -0.107118E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173182E+10 | 81.25 | 0.00 | 0.00 |
August | 0.107687E+12 | -0.105959E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172826E+10 | 81.25 | 0.00 | 0.00 |
September | 0.105497E+12 | -0.103827E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167031E+10 | 81.25 | 0.00 | 0.00 |
October | 0.112452E+12 | -0.110726E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172570E+10 | 81.25 | 0.00 | 0.00 |
November | 0.113291E+12 | -0.111621E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167011E+10 | 81.26 | 0.00 | 0.00 |
December | 0.121646E+12 | -0.119919E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172642E+10 | 81.26 | 0.00 | 0.00 |
Annual Sum or Average | 0.137601E+13 | -0.135563E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203825E+11 | 81.26 | 0.00 | 0.00 |
Minimum of Months | 0.105497E+12 | -0.123322E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.173830E+10 | 81.25 | 0.00 | 0.00 |
Maximum of Months | 0.125052E+12 | -0.103827E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156569E+10 | 81.30 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.752018E+11 | -0.737356E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146615E+10 | 58.99 | 0.00 | 0.00 |
February | 0.687685E+11 | -0.674403E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.132821E+10 | 58.99 | 0.00 | 0.00 |
March | 0.750928E+11 | -0.736150E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147782E+10 | 58.99 | 0.00 | 0.00 |
April | 0.698154E+11 | -0.683872E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142822E+10 | 58.99 | 0.00 | 0.00 |
May | 0.682008E+11 | -0.667218E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147907E+10 | 58.98 | 0.00 | 0.00 |
June | 0.622112E+11 | -0.607862E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142501E+10 | 58.98 | 0.00 | 0.00 |
July | 0.613784E+11 | -0.599083E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147015E+10 | 58.98 | 0.00 | 0.00 |
August | 0.604347E+11 | -0.589695E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146526E+10 | 58.98 | 0.00 | 0.00 |
September | 0.595602E+11 | -0.581451E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141508E+10 | 58.98 | 0.00 | 0.00 |
October | 0.644782E+11 | -0.630165E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146172E+10 | 58.98 | 0.00 | 0.00 |
November | 0.662369E+11 | -0.648223E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141459E+10 | 58.98 | 0.00 | 0.00 |
December | 0.723549E+11 | -0.708925E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146237E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.803734E+12 | -0.786440E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.172937E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.595602E+11 | -0.737356E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.147907E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.752018E+11 | -0.581451E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.132821E+10 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.93 | 0.93 | 01-JAN-07:49 | 9006.48 | 39.71 | 274.00 | 270.33 | 3430.64 | 33.72 | 231.17 | 258.83 |
February | 245.50 | 0.93 | 0.93 | 01-FEB-10:39 | 12275.63 | 39.09 | 238.17 | 265.50 | 1040.79 | 25.98 | 163.17 | 232.00 |
March | 296.17 | 0.93 | 0.93 | 01-MAR-06:00 | 4379.44 | 25.67 | 129.83 | 331.00 | 631.87 | 22.32 | 236.83 | 269.17 |
April | 296.67 | 0.93 | 0.93 | 03-APR-09:39 | 1395.66 | 20.34 | 80.00 | 343.33 | 560.63 | 22.05 | 214.83 | 274.33 |
May | 415.33 | 0.93 | 0.93 | 01-MAY-05:49 | 1318.03 | 19.97 | 96.33 | 394.50 | 516.50 | 21.69 | 287.17 | 334.17 |
June | 421.50 | 0.93 | 0.93 | 01-JUN-05:40 | 1015.64 | 20.03 | 39.50 | 394.50 | 427.31 | 21.79 | 303.00 | 321.67 |
July | 430.33 | 0.93 | 0.93 | 01-JUL-05:00 | 1179.98 | 19.85 | 70.67 | 398.50 | 471.65 | 21.60 | 281.83 | 330.17 |
August | 394.50 | 0.93 | 0.93 | 01-AUG-05:00 | 1177.91 | 20.10 | 78.17 | 373.17 | 491.81 | 21.84 | 290.33 | 315.83 |
September | 354.00 | 0.93 | 0.93 | 01-SEP-06:10 | 1459.73 | 20.35 | 86.00 | 334.83 | 600.01 | 22.13 | 264.67 | 288.83 |
October | 262.67 | 0.93 | 0.93 | 01-OCT-06:30 | 9622.38 | 35.03 | 224.17 | 301.67 | 803.73 | 23.99 | 233.50 | 253.67 |
November | 257.67 | 0.93 | 0.93 | 01-NOV-08:39 | 10398.47 | 39.58 | 254.00 | 266.50 | 1894.81 | 30.18 | 200.83 | 239.33 |
December | 251.17 | 0.93 | 0.93 | 01-DEC-07:40 | 8347.70 | 40.12 | 250.83 | 259.33 | 5110.81 | 38.23 | 238.17 | 243.00 |
Annual Sum or Average | 3902.00 | 0.93 | 4352.45 | 26.68 | 1821.67 | 3933.17 | 1164.68 | 24.72 | 2945.50 | 3361.00 | ||
Minimum of Months | 245.50 | 0.93 | 0.93 | 1015.64 | 19.85 | 39.50 | 259.33 | 427.31 | 21.60 | 163.17 | 232.00 | |
Maximum of Months | 430.33 | 0.93 | 0.93 | 12275.63 | 40.12 | 274.00 | 398.50 | 5110.81 | 38.23 | 303.00 | 334.17 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.62 | 0.61 | 01-JAN-07:40 | 9632.98 | 39.76 | 274.00 | 275.83 | 4056.53 | 33.31 | 224.67 | 268.50 |
February | 245.50 | 0.62 | 0.61 | 01-FEB-10:39 | 12902.54 | 39.17 | 238.17 | 271.67 | 1666.43 | 25.22 | 125.33 | 254.83 |
March | 296.17 | 0.62 | 0.61 | 01-MAR-06:49 | 4831.99 | 25.67 | 130.67 | 339.67 | 1083.02 | 22.08 | 178.83 | 310.67 |
April | 296.67 | 0.63 | 0.61 | 03-APR-09:39 | 1695.58 | 20.67 | 97.00 | 353.67 | 859.66 | 22.22 | 216.50 | 321.50 |
May | 415.33 | 0.63 | 0.61 | 01-MAY-05:49 | 1539.93 | 20.56 | 162.67 | 405.50 | 737.61 | 22.09 | 315.83 | 376.00 |
June | 421.50 | 0.62 | 0.61 | 01-JUN-05:19 | 1216.10 | 20.62 | 125.83 | 410.33 | 627.19 | 22.19 | 326.33 | 372.50 |
July | 430.33 | 0.62 | 0.61 | 01-JUL-05:19 | 1386.10 | 20.48 | 149.50 | 415.67 | 677.08 | 22.03 | 317.17 | 376.83 |
August | 394.50 | 0.63 | 0.61 | 01-AUG-05:49 | 1450.14 | 20.47 | 107.83 | 382.50 | 763.35 | 22.05 | 287.00 | 355.17 |
September | 354.00 | 0.62 | 0.61 | 01-SEP-05:00 | 1824.45 | 20.47 | 108.17 | 346.33 | 963.80 | 22.12 | 243.17 | 319.50 |
October | 262.67 | 0.62 | 0.61 | 01-OCT-06:30 | 10175.19 | 35.00 | 218.33 | 310.50 | 1354.85 | 23.55 | 179.67 | 287.17 |
November | 257.67 | 0.62 | 0.61 | 01-NOV-08:39 | 11043.24 | 39.64 | 254.00 | 273.17 | 2537.04 | 29.53 | 175.17 | 257.50 |
December | 251.17 | 0.62 | 0.61 | 01-DEC-07:40 | 8980.69 | 40.17 | 250.83 | 264.00 | 5742.10 | 38.08 | 231.33 | 256.50 |
Annual Sum or Average | 3902.00 | 0.62 | 4742.59 | 26.96 | 2117.00 | 4048.83 | 1553.75 | 24.71 | 2821.00 | 3756.67 | ||
Minimum of Months | 245.50 | 0.62 | 0.61 | 1216.10 | 20.47 | 97.00 | 264.00 | 627.19 | 22.03 | 125.33 | 254.83 | |
Maximum of Months | 430.33 | 0.63 | 0.61 | 12902.54 | 40.17 | 274.00 | 415.67 | 5742.10 | 38.08 | 326.33 | 376.83 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.83 | 0.80 | 01-JAN-08:30 | 334.14 | 14.11 | 0.00 | 220.33 | 176.21 | 17.80 | 0.00 | 84.67 |
February | 245.50 | 0.81 | 0.80 | 01-FEB-10:39 | 377.86 | 15.45 | 0.00 | 250.50 | 204.64 | 19.06 | 1.17 | 99.33 |
March | 296.17 | 0.81 | 0.80 | 01-MAR-06:00 | 521.49 | 16.72 | 0.00 | 327.50 | 260.79 | 20.07 | 16.67 | 251.67 |
April | 296.67 | 0.81 | 0.80 | 03-APR-09:39 | 738.01 | 17.86 | 0.00 | 353.33 | 336.11 | 21.04 | 101.83 | 298.67 |
May | 415.33 | 0.81 | 0.80 | 01-MAY-05:49 | 941.22 | 18.19 | 0.00 | 412.50 | 397.87 | 21.84 | 242.67 | 384.17 |
June | 421.50 | 0.80 | 0.80 | 01-JUN-04:00 | 999.43 | 18.88 | 11.00 | 421.00 | 428.13 | 24.13 | 276.50 | 408.00 |
July | 430.33 | 0.80 | 0.80 | 01-JUL-04:00 | 972.18 | 18.33 | 1.83 | 425.83 | 410.16 | 22.72 | 261.83 | 398.00 |
August | 394.50 | 0.81 | 0.80 | 01-AUG-05:49 | 731.29 | 17.85 | 0.00 | 388.83 | 331.61 | 21.10 | 147.17 | 347.83 |
September | 354.00 | 0.81 | 0.80 | 01-SEP-05:00 | 584.71 | 17.12 | 0.00 | 338.33 | 284.76 | 20.40 | 44.83 | 272.83 |
October | 262.67 | 0.81 | 0.80 | 01-OCT-06:40 | 474.60 | 16.49 | 0.00 | 292.17 | 252.98 | 19.95 | 0.50 | 204.67 |
November | 257.67 | 0.82 | 0.80 | 01-NOV-08:39 | 368.44 | 14.91 | 0.00 | 241.17 | 200.48 | 18.57 | 0.00 | 93.67 |
December | 251.17 | 0.82 | 0.80 | 01-DEC-08:20 | 350.20 | 14.52 | 0.00 | 226.67 | 186.77 | 18.22 | 0.00 | 83.67 |
Annual Sum or Average | 3902.00 | 0.81 | 664.31 | 16.98 | 12.83 | 3898.17 | 306.19 | 20.75 | 1093.17 | 2927.17 | ||
Minimum of Months | 245.50 | 0.80 | 0.80 | 334.14 | 14.11 | 0.00 | 220.33 | 176.21 | 17.80 | 0.00 | 83.67 | |
Maximum of Months | 430.33 | 0.83 | 0.80 | 999.43 | 18.88 | 11.00 | 425.83 | 428.13 | 24.13 | 276.50 | 408.00 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.83 | 0.80 | 01-JAN-08:30 | 334.14 | 14.11 | 0.00 | 220.33 | 176.21 | 17.80 | 0.00 | 84.67 |
February | 245.50 | 0.81 | 0.80 | 01-FEB-10:39 | 377.86 | 15.45 | 0.00 | 250.50 | 204.64 | 19.06 | 1.17 | 99.33 |
March | 296.17 | 0.81 | 0.80 | 01-MAR-06:00 | 521.49 | 16.72 | 0.00 | 327.50 | 260.79 | 20.07 | 16.67 | 251.67 |
April | 296.67 | 0.81 | 0.80 | 03-APR-09:39 | 738.01 | 17.86 | 0.00 | 353.33 | 336.11 | 21.04 | 101.83 | 298.67 |
May | 415.33 | 0.81 | 0.80 | 01-MAY-05:49 | 941.22 | 18.19 | 0.00 | 412.50 | 397.87 | 21.84 | 242.67 | 384.17 |
June | 421.50 | 0.80 | 0.80 | 01-JUN-04:00 | 999.43 | 18.88 | 11.00 | 421.00 | 428.13 | 24.13 | 276.50 | 408.00 |
July | 430.33 | 0.80 | 0.80 | 01-JUL-04:00 | 972.18 | 18.33 | 1.83 | 425.83 | 410.16 | 22.72 | 261.83 | 398.00 |
August | 394.50 | 0.81 | 0.80 | 01-AUG-05:49 | 731.29 | 17.85 | 0.00 | 388.83 | 331.61 | 21.10 | 147.17 | 347.83 |
September | 354.00 | 0.81 | 0.80 | 01-SEP-05:00 | 584.71 | 17.12 | 0.00 | 338.33 | 284.76 | 20.40 | 44.83 | 272.83 |
October | 262.67 | 0.81 | 0.80 | 01-OCT-06:40 | 474.60 | 16.49 | 0.00 | 292.17 | 252.98 | 19.95 | 0.50 | 204.67 |
November | 257.67 | 0.82 | 0.80 | 01-NOV-08:39 | 368.44 | 14.91 | 0.00 | 241.17 | 200.48 | 18.57 | 0.00 | 93.67 |
December | 251.17 | 0.82 | 0.80 | 01-DEC-08:20 | 350.20 | 14.52 | 0.00 | 226.67 | 186.77 | 18.22 | 0.00 | 83.67 |
Annual Sum or Average | 3902.00 | 0.81 | 664.31 | 16.98 | 12.83 | 3898.17 | 306.19 | 20.75 | 1093.17 | 2927.17 | ||
Minimum of Months | 245.50 | 0.80 | 0.80 | 334.14 | 14.11 | 0.00 | 220.33 | 176.21 | 17.80 | 0.00 | 83.67 | |
Maximum of Months | 430.33 | 0.83 | 0.80 | 999.43 | 18.88 | 11.00 | 425.83 | 428.13 | 24.13 | 276.50 | 408.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.392487E+11 | 163096.12 | 25-JAN-23:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.335594E+11 | 182904.10 | 23-FEB-23:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.284175E+11 | 183766.30 | 06-MAR-23:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252158E+11 | 176827.08 | 25-APR-00:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130295E+11 | 177206.38 | 09-MAY-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.483545E+09 | 130847.60 | 09-JUN-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.567910E+09 | 41219.25 | 02-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.125541E+09 | 27869.50 | 23-AUG-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.283029E+10 | 165461.50 | 21-SEP-15:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.266478E+11 | 190710.16 | 16-OCT-21:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.313975E+11 | 184937.81 | 23-NOV-10:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.598818E+11 | 191242.46 | 14-DEC-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261405E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.125541E+09 | 27869.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.598818E+11 | 191242.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.519200E+09 | 2276.04 | 05-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.860118E+09 | 2050.82 | 07-FEB-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.747102E+09 | 2211.51 | 19-MAR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.644279E+09 | 1631.98 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36734814.01 | 1037.53 | 01-MAY-01:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9553408.11 | 538.51 | 22-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.539615E+09 | 1963.14 | 31-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.505204E+09 | 1915.02 | 30-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114218E+10 | 3149.68 | 21-DEC-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.500399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114218E+10 | 3149.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 9523003.93 | 409.05 | 05-JAN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 38997876.95 | 803.02 | 07-FEB-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17074840.74 | 731.26 | 20-MAR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9577017.04 | 595.36 | 17-APR-10:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21627013.04 | 496.59 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6287702.51 | 352.34 | 01-NOV-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 88965987.10 | 732.97 | 21-DEC-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88965987.10 | 803.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.126010E+09 | 897.30 | 06-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.274685E+09 | 874.16 | 07-FEB-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 42711745.30 | 616.15 | 20-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31709174.30 | 748.01 | 17-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 51026338.92 | 691.31 | 31-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100147E+09 | 757.98 | 30-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.489674E+09 | 1392.79 | 22-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.489674E+09 | 1392.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.473227E+09 | 914.52 | 05-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.627815E+09 | 984.69 | 07-FEB-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.385893E+09 | 841.72 | 20-MAR-10:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.282601E+09 | 853.32 | 17-APR-10:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7703317.52 | 373.41 | 02-MAY-11:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201342E+09 | 804.65 | 31-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.328242E+09 | 882.72 | 30-NOV-12:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.834800E+09 | 1174.35 | 22-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.314162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.834800E+09 | 1174.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 804276.54 | 3182.10 | 24-JAN-01:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 726134.98 | 1336.07 | 19-FEB-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1313484.72 | 4378.28 | 23-MAR-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1494057.34 | 7470.29 | 22-APR-00:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 196646.55 | 655.49 | 07-OCT-04:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1254940.49 | 6274.70 | 17-NOV-00:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 317645.26 | 1588.23 | 05-DEC-02:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6107185.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1494057.34 | 7470.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.440639E+09 | 6884.02 | 05-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.951297E+09 | 7771.36 | 07-FEB-12:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.980775E+09 | 7414.24 | 20-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.801203E+09 | 6090.03 | 30-APR-14:28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17891194.98 | 4541.08 | 02-MAY-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2948622.02 | 1748.95 | 22-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.837056E+09 | 6292.16 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.440222E+09 | 5758.61 | 29-NOV-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.124754E+10 | 8715.76 | 21-DEC-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.571957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.124754E+10 | 8715.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 43403464.10 | 5200.68 | 05-JAN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.395220E+09 | 11408.21 | 07-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125896E+09 | 7035.96 | 20-MAR-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41333179.97 | 3244.88 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.228205E+09 | 7695.84 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11000841.04 | 3616.92 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.419608E+09 | 11376.59 | 21-DEC-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.419608E+09 | 11408.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.581182E+09 | 6246.85 | 05-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.194718E+10 | 8099.78 | 07-FEB-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.512439E+09 | 5318.26 | 20-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.317677E+09 | 4297.59 | 03-APR-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.614110E+09 | 6787.92 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.728347E+09 | 5833.03 | 01-NOV-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.272390E+10 | 9435.16 | 21-DEC-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.742484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.272390E+10 | 9435.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115271E+10 | 4592.50 | 05-JAN-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.181508E+10 | 4342.43 | 12-FEB-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.839555E+09 | 3258.71 | 05-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.528278E+09 | 2741.22 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.710193E+09 | 3543.64 | 31-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.858901E+09 | 3980.82 | 30-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.276124E+10 | 6006.29 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.866596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.276124E+10 | 6006.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 82235161.21 | 6275.14 | 08-JAN-16:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 85506210.05 | 3819.15 | 07-FEB-11:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11776610.67 | 1595.98 | 22-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7138898.56 | 3153.54 | 04-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 61616188.65 | 2049.59 | 31-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 43847158.62 | 2588.21 | 30-NOV-11:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.410962E+09 | 6825.22 | 11-DEC-11:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.703082E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.410962E+09 | 6825.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 10063361.93 | 776.72 | 05-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2099313.84 | 1985.43 | 07-FEB-11:48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1024138.74 | 360.78 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154452E+09 | 3237.05 | 11-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167639E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.154452E+09 | 3237.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 84932.71 | 424.66 | 24-JAN-01:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 483328.31 | 2416.64 | 22-APR-00:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 301883.54 | 1006.28 | 07-OCT-04:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 870144.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 483328.31 | 2416.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.316190E+10 | 13931.71 | 05-JAN-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.390286E+10 | 12581.25 | 12-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170954E+10 | 10812.52 | 19-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107353E+10 | 5427.60 | 03-APR-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1122062.52 | 549.86 | 03-MAY-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 67780.01 | 0.61 | 21-JUN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 70037.25 | 0.60 | 28-JUL-19:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 55654.53 | 0.60 | 03-AUG-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 773806.63 | 281.18 | 22-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150886E+10 | 8065.45 | 30-OCT-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190500E+10 | 9923.34 | 29-NOV-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.682983E+10 | 15268.82 | 21-DEC-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 55654.53 | 0.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.682983E+10 | 15268.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.270974E+10 | 12298.17 | 05-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.312763E+10 | 12300.28 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.241555E+10 | 12299.11 | 19-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.201934E+10 | 12242.71 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.206318E+09 | 11486.51 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3569431.05 | 4147.24 | 09-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3311369.22 | 3037.57 | 02-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4427935.40 | 3965.57 | 02-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81111525.12 | 11869.36 | 22-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168841E+10 | 12299.84 | 31-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.228379E+10 | 12299.57 | 29-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.458906E+10 | 12298.12 | 19-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3311369.22 | 3037.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.458906E+10 | 12300.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.432092E+10 | 12238.17 | 16-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.433303E+10 | 12238.77 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.294179E+10 | 12237.72 | 19-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.224567E+10 | 12181.51 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.231258E+09 | 11750.93 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3453058.37 | 4259.55 | 09-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3185635.97 | 2613.87 | 31-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5156323.43 | 4455.26 | 14-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107798E+09 | 11838.94 | 22-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208103E+10 | 12238.33 | 31-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.343704E+10 | 12238.05 | 29-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.625788E+10 | 12238.26 | 10-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3185635.97 | 2613.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.625788E+10 | 12238.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.779644E+09 | 18036.27 | 06-JAN-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.431447E+10 | 23183.06 | 07-FEB-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.296937E+10 | 13547.71 | 20-MAR-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117631E+10 | 14794.28 | 17-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.198665E+10 | 19387.08 | 31-OCT-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137193E+10 | 20936.35 | 01-NOV-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.487617E+10 | 32533.80 | 21-DEC-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.487617E+10 | 32533.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.203771E+11 | 67363.91 | 04-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.208004E+11 | 67363.78 | 11-FEB-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109373E+11 | 67151.27 | 04-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.621716E+10 | 66298.26 | 02-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.338361E+09 | 32499.84 | 14-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30355722.03 | 28328.09 | 28-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33483540.98 | 36762.61 | 14-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 38123693.84 | 33061.35 | 30-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.232585E+09 | 37960.32 | 22-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.673410E+10 | 67363.28 | 31-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148829E+11 | 67368.50 | 28-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.282299E+11 | 67358.76 | 20-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108852E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 30355722.03 | 28328.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.282299E+11 | 67368.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.286503E+10 | 11908.52 | 05-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.328161E+10 | 11910.83 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.239394E+10 | 11909.67 | 19-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197090E+10 | 11855.18 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.189336E+09 | 3643.25 | 14-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 454283.80 | 1862.79 | 16-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 793994.02 | 1355.63 | 28-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 680064.81 | 1711.95 | 22-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 70874529.65 | 10125.28 | 22-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.172758E+10 | 11910.35 | 31-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.243658E+10 | 11910.05 | 29-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.467025E+10 | 11907.92 | 20-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 454283.80 | 1355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.467025E+10 | 11910.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.445328E+10 | 11844.09 | 04-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.444302E+10 | 11846.37 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286366E+10 | 11845.18 | 19-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.219359E+10 | 11791.05 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.215881E+09 | 3597.14 | 14-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 530588.28 | 1908.19 | 16-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 929862.57 | 1571.34 | 30-JUL-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1003488.60 | 1499.85 | 28-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 94341233.75 | 11389.12 | 22-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.210683E+10 | 11845.88 | 31-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.362472E+10 | 11845.58 | 29-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.631102E+10 | 11844.79 | 18-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.263088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 530588.28 | 1499.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.631102E+10 | 11846.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110222E+10 | 3655.24 | 15-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117559E+10 | 3655.71 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.939835E+09 | 3655.55 | 04-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.803568E+09 | 3638.67 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133403E+09 | 3543.67 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1501037.91 | 923.30 | 09-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1588131.40 | 1142.78 | 13-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2371973.16 | 1065.24 | 24-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 49051693.20 | 3576.74 | 22-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.712933E+09 | 3655.60 | 31-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.933641E+09 | 3655.49 | 29-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167092E+10 | 3655.46 | 10-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.752661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1501037.91 | 923.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.167092E+10 | 3655.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.164696E+10 | 3630.38 | 16-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157440E+10 | 3630.67 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112730E+10 | 3630.60 | 04-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.884820E+09 | 3613.75 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147036E+09 | 3522.51 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1250203.12 | 954.55 | 09-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1536607.07 | 997.40 | 13-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3408382.24 | 1176.15 | 18-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 66686726.69 | 3552.28 | 22-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.884586E+09 | 3630.55 | 31-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134008E+10 | 3630.44 | 29-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220037E+10 | 3630.42 | 10-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.987843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1250203.12 | 954.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.220037E+10 | 3630.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.231736E+10 | 17009.20 | 04-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.329657E+10 | 17012.26 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.301649E+10 | 17010.50 | 19-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.278585E+10 | 16932.73 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.372247E+09 | 16188.17 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10239421.93 | 5231.54 | 05-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8555716.53 | 3972.51 | 15-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6678493.88 | 4955.47 | 14-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105854E+09 | 16402.24 | 22-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.216171E+10 | 17011.39 | 31-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.218511E+10 | 17010.79 | 29-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.440894E+10 | 17007.95 | 21-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6678493.88 | 3972.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.440894E+10 | 17012.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.641639E+10 | 0.641639E+10 | 133320.62 | 20-JAN-13:00 | 133320.62 | 0.00 |
February | 0.00 | 0.00 | 0.362902E+10 | 0.362902E+10 | 119864.70 | 18-FEB-13:00 | 119864.70 | 0.00 |
March | 0.00 | 0.00 | 0.197927E+11 | 0.197927E+11 | 167258.36 | 14-MAR-13:00 | 167258.36 | 0.00 |
April | 0.00 | 0.00 | 0.205285E+11 | 0.205285E+11 | 118861.67 | 19-APR-10:50 | 118861.67 | 0.00 |
May | 0.00 | 0.00 | 0.929566E+11 | 0.929566E+11 | 202869.33 | 31-MAY-18:10 | 202869.33 | 0.04 |
June | 0.00 | 0.00 | 0.298236E+12 | 0.295328E+12 | 289028.98 | 26-JUN-18:20 | 289028.98 | 0.39 |
July | 0.00 | 0.00 | 0.340417E+12 | 0.324639E+12 | 300667.68 | 30-JUL-10:35 | 173068.79 | 0.49 |
August | 0.00 | 0.00 | 0.305016E+12 | 0.299543E+12 | 273039.11 | 16-AUG-18:20 | 273039.11 | 0.52 |
September | 0.00 | 0.00 | 0.213776E+12 | 0.213776E+12 | 240190.25 | 12-SEP-18:20 | 240190.25 | 0.11 |
October | 0.00 | 0.00 | 0.363658E+11 | 0.363658E+11 | 185638.83 | 11-OCT-14:10 | 185638.83 | 0.00 |
November | 0.00 | 0.00 | 0.121905E+11 | 0.121905E+11 | 147510.52 | 06-NOV-13:00 | 147510.52 | 0.00 |
December | 0.00 | 0.00 | 0.825937E+10 | 0.825937E+10 | 124827.19 | 02-DEC-13:00 | 124827.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.135758E+13 | 0.133343E+13 | 0.13 | |||
Minimum of Months | 0.00 | 0.00 | 0.362902E+10 | 0.362902E+10 | 118861.67 | 118861.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.340417E+12 | 0.324639E+12 | 300667.68 | 289028.98 | 0.52 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.806531E+09 | 0.806531E+09 | 18772.93 | 20-JAN-14:00 | 18772.93 | 0.00 |
February | 0.00 | 0.00 | 0.433446E+09 | 0.433446E+09 | 15786.89 | 18-FEB-14:00 | 15786.89 | 0.00 |
March | 0.00 | 0.00 | 0.270200E+10 | 0.270200E+10 | 22830.69 | 14-MAR-13:00 | 22830.69 | 0.00 |
April | 0.00 | 0.00 | 0.323869E+10 | 0.323869E+10 | 20853.73 | 20-APR-13:00 | 20853.73 | 0.00 |
May | 0.00 | 0.00 | 0.144894E+11 | 0.144894E+11 | 26345.92 | 17-MAY-14:00 | 26345.92 | 0.04 |
June | 0.00 | 0.00 | 0.425535E+11 | 0.413960E+11 | 34231.28 | 21-JUN-17:40 | 22900.88 | 0.39 |
July | 0.00 | 0.00 | 0.503092E+11 | 0.462727E+11 | 38435.62 | 30-JUL-16:00 | 19230.93 | 0.44 |
August | 0.00 | 0.00 | 0.438094E+11 | 0.417923E+11 | 38985.53 | 05-AUG-14:40 | 19893.17 | 0.48 |
September | 0.00 | 0.00 | 0.303321E+11 | 0.303321E+11 | 28363.15 | 10-SEP-13:50 | 28363.15 | 0.09 |
October | 0.00 | 0.00 | 0.512374E+10 | 0.512374E+10 | 24648.65 | 11-OCT-14:00 | 24648.65 | 0.00 |
November | 0.00 | 0.00 | 0.173918E+10 | 0.173918E+10 | 20791.64 | 07-NOV-15:00 | 20791.64 | 0.00 |
December | 0.00 | 0.00 | 0.121720E+10 | 0.121720E+10 | 20812.74 | 02-DEC-15:00 | 20812.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.196754E+12 | 0.189543E+12 | 0.12 | |||
Minimum of Months | 0.00 | 0.00 | 0.433446E+09 | 0.433446E+09 | 15786.89 | 15786.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.503092E+11 | 0.462727E+11 | 38985.53 | 28363.15 | 0.48 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.113400E+10 | 0.113400E+10 | 19048.09 | 23-JAN-16:01 | 19048.09 | 0.00 |
February | 0.00 | 0.00 | 0.123643E+10 | 0.123643E+10 | 18944.40 | 18-FEB-16:01 | 18944.40 | 0.00 |
March | 0.00 | 0.00 | 0.250797E+10 | 0.250793E+10 | 19805.06 | 13-MAR-15:01 | 19805.06 | 0.00 |
April | 0.00 | 0.00 | 0.162844E+10 | 0.157247E+10 | 19499.53 | 27-APR-15:01 | 19499.53 | 0.03 |
May | 0.00 | 0.00 | 0.406570E+10 | 0.346338E+10 | 20527.32 | 16-MAY-15:01 | 20527.32 | 0.25 |
June | 0.00 | 0.00 | 0.956443E+10 | 0.739393E+10 | 20551.20 | 05-JUN-15:01 | 20551.20 | 0.53 |
July | 0.00 | 0.00 | 0.923971E+10 | 0.671270E+10 | 20552.79 | 10-JUL-18:01 | 20552.79 | 0.57 |
August | 0.00 | 0.00 | 0.938295E+10 | 0.663985E+10 | 20550.96 | 19-AUG-15:01 | 20550.96 | 0.64 |
September | 0.00 | 0.00 | 0.728139E+10 | 0.631041E+10 | 20547.29 | 12-SEP-15:01 | 20547.29 | 0.27 |
October | 0.00 | 0.00 | 0.348693E+10 | 0.344814E+10 | 20339.00 | 11-OCT-15:01 | 20339.00 | 0.02 |
November | 0.00 | 0.00 | 0.160409E+10 | 0.159852E+10 | 19432.56 | 05-NOV-15:01 | 19432.56 | 0.01 |
December | 0.00 | 0.00 | 0.687830E+09 | 0.687830E+09 | 18895.61 | 02-DEC-16:01 | 18895.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.518199E+11 | 0.427056E+11 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 0.687830E+09 | 0.687830E+09 | 18895.61 | 18895.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.956443E+10 | 0.739393E+10 | 20552.79 | 20552.79 | 0.64 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.185326E+09 | 0.185326E+09 | 18562.38 | 23-JAN-16:01 | 18562.38 | 0.00 |
February | 0.00 | 0.00 | 0.286584E+09 | 0.286584E+09 | 18460.42 | 18-FEB-16:01 | 18460.42 | 0.00 |
March | 0.00 | 0.00 | 0.122427E+10 | 0.122422E+10 | 19298.92 | 14-MAR-15:01 | 19298.92 | 0.00 |
April | 0.00 | 0.00 | 0.102419E+10 | 0.984519E+09 | 19002.66 | 27-APR-15:01 | 19002.66 | 0.03 |
May | 0.00 | 0.00 | 0.357367E+10 | 0.301247E+10 | 20003.71 | 16-MAY-15:01 | 20003.71 | 0.24 |
June | 0.00 | 0.00 | 0.922813E+10 | 0.715173E+10 | 20027.15 | 05-JUN-15:01 | 20027.15 | 0.53 |
July | 0.00 | 0.00 | 0.878975E+10 | 0.638518E+10 | 20028.98 | 10-JUL-18:01 | 20028.98 | 0.56 |
August | 0.00 | 0.00 | 0.809709E+10 | 0.561719E+10 | 20027.15 | 19-AUG-15:01 | 20027.15 | 0.63 |
September | 0.00 | 0.00 | 0.542478E+10 | 0.457591E+10 | 20023.53 | 04-SEP-15:01 | 20023.53 | 0.26 |
October | 0.00 | 0.00 | 0.164463E+10 | 0.162965E+10 | 19819.31 | 11-OCT-15:01 | 19819.31 | 0.01 |
November | 0.00 | 0.00 | 0.333990E+09 | 0.333117E+09 | 18935.73 | 05-NOV-15:01 | 18935.73 | 0.00 |
December | 0.00 | 0.00 | 67976446.43 | 67976446.43 | 18412.76 | 02-DEC-16:01 | 18412.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.398804E+11 | 0.314539E+11 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 67976446.43 | 67976446.43 | 18412.76 | 18412.76 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.922813E+10 | 0.715173E+10 | 20028.98 | 20028.98 | 0.63 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.269976E+11 | 0.269976E+11 | 66400.73 | 20-JAN-12:40 | 66400.73 | 0.00 |
February | 0.00 | 0.00 | 0.199380E+11 | 0.199380E+11 | 63706.59 | 18-FEB-13:00 | 63706.59 | 0.00 |
March | 0.00 | 0.00 | 0.189611E+11 | 0.189611E+11 | 58437.64 | 11-MAR-13:00 | 58437.64 | 0.00 |
April | 0.00 | 0.00 | 0.449156E+10 | 0.449156E+10 | 33346.81 | 08-APR-13:10 | 33346.81 | 0.00 |
May | 0.00 | 0.00 | 0.949923E+10 | 0.864950E+10 | 22928.25 | 16-MAY-13:30 | 22928.25 | 0.07 |
June | 0.00 | 0.00 | 0.288177E+11 | 0.225120E+11 | 32259.01 | 14-JUN-13:30 | 32259.01 | 0.32 |
July | 0.00 | 0.00 | 0.322192E+11 | 0.245359E+11 | 36478.26 | 23-JUL-13:00 | 31670.22 | 0.37 |
August | 0.00 | 0.00 | 0.388565E+11 | 0.305920E+11 | 45975.42 | 31-AUG-12:50 | 45975.42 | 0.45 |
September | 0.00 | 0.00 | 0.398308E+11 | 0.379223E+11 | 60492.80 | 28-SEP-13:00 | 60492.80 | 0.12 |
October | 0.00 | 0.00 | 0.311800E+11 | 0.311800E+11 | 62661.19 | 10-OCT-12:30 | 62661.19 | 0.00 |
November | 0.00 | 0.00 | 0.265403E+11 | 0.265403E+11 | 67142.64 | 07-NOV-12:10 | 67142.64 | 0.00 |
December | 0.00 | 0.00 | 0.165208E+11 | 0.165208E+11 | 59815.12 | 17-DEC-12:10 | 59815.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.293853E+12 | 0.268841E+12 | 0.11 | |||
Minimum of Months | 0.00 | 0.00 | 0.449156E+10 | 0.449156E+10 | 22928.25 | 22928.25 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.398308E+11 | 0.379223E+11 | 67142.64 | 67142.64 | 0.45 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.454559E+09 | 0.454559E+09 | 79156.50 | 21-JAN-09:01 | 79156.50 | 0.00 |
February | 0.00 | 0.00 | 0.516639E+09 | 0.516639E+09 | 78921.20 | 19-FEB-09:01 | 78921.20 | 0.00 |
March | 0.00 | 0.00 | 0.403605E+10 | 0.399581E+10 | 86348.73 | 14-MAR-15:01 | 86348.73 | 0.01 |
April | 0.00 | 0.00 | 0.583022E+10 | 0.517849E+10 | 85038.75 | 27-APR-15:01 | 85038.75 | 0.07 |
May | 0.00 | 0.00 | 0.251196E+11 | 0.215376E+11 | 96479.95 | 17-MAY-15:01 | 96479.95 | 0.22 |
June | 0.00 | 0.00 | 0.517809E+11 | 0.421432E+11 | 97286.34 | 25-JUN-08:61 | 97286.34 | 0.41 |
July | 0.00 | 0.00 | 0.548152E+11 | 0.433601E+11 | 97308.90 | 08-JUL-18:01 | 97308.90 | 0.43 |
August | 0.00 | 0.00 | 0.458608E+11 | 0.333547E+11 | 97294.42 | 25-AUG-18:01 | 97294.42 | 0.50 |
September | 0.00 | 0.00 | 0.297250E+11 | 0.262326E+11 | 97227.42 | 11-SEP-15:01 | 97227.42 | 0.19 |
October | 0.00 | 0.00 | 0.598537E+10 | 0.578554E+10 | 90260.98 | 11-OCT-15:01 | 90260.98 | 0.03 |
November | 0.00 | 0.00 | 0.125726E+10 | 0.120093E+10 | 79540.98 | 09-NOV-19:02 | 79540.98 | 0.01 |
December | 0.00 | 0.00 | 0.351799E+09 | 0.351799E+09 | 62312.80 | 02-DEC-09:01 | 62312.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.225733E+12 | 0.184112E+12 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 0.351799E+09 | 0.351799E+09 | 62312.80 | 62312.80 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.548152E+11 | 0.433601E+11 | 97308.90 | 97308.90 | 0.50 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.110883E+10 | 0.110883E+10 | 16524.63 | 23-JAN-16:01 | 16524.63 | 0.00 |
February | 0.00 | 0.00 | 0.137763E+10 | 0.137763E+10 | 16434.98 | 18-FEB-16:01 | 16434.98 | 0.00 |
March | 0.00 | 0.00 | 0.268361E+10 | 0.268344E+10 | 17180.48 | 13-MAR-15:01 | 17180.48 | 0.00 |
April | 0.00 | 0.00 | 0.197442E+10 | 0.189673E+10 | 16915.78 | 27-APR-15:01 | 16915.78 | 0.04 |
May | 0.00 | 0.00 | 0.448210E+10 | 0.387081E+10 | 17808.19 | 16-MAY-15:01 | 17808.19 | 0.26 |
June | 0.00 | 0.00 | 0.101327E+11 | 0.800017E+10 | 17827.76 | 05-JUN-15:01 | 17827.76 | 0.56 |
July | 0.00 | 0.00 | 0.103623E+11 | 0.790240E+10 | 17828.27 | 12-JUL-18:01 | 17828.27 | 0.60 |
August | 0.00 | 0.00 | 0.104300E+11 | 0.778304E+10 | 17827.20 | 19-AUG-15:01 | 17827.20 | 0.67 |
September | 0.00 | 0.00 | 0.771289E+10 | 0.681472E+10 | 17823.98 | 12-SEP-15:01 | 17823.98 | 0.28 |
October | 0.00 | 0.00 | 0.336435E+10 | 0.331865E+10 | 17642.99 | 11-OCT-15:01 | 17642.99 | 0.03 |
November | 0.00 | 0.00 | 0.154772E+10 | 0.154170E+10 | 16857.65 | 05-NOV-15:01 | 16857.65 | 0.01 |
December | 0.00 | 0.00 | 0.694272E+09 | 0.694272E+09 | 16391.24 | 02-DEC-16:01 | 16391.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.558708E+11 | 0.469924E+11 | 0.21 | |||
Minimum of Months | 0.00 | 0.00 | 0.694272E+09 | 0.694272E+09 | 16391.24 | 16391.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.104300E+11 | 0.800017E+10 | 17828.27 | 17828.27 | 0.67 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.190865E+09 | 0.190865E+09 | 15559.45 | 20-JAN-09:02 | 15559.45 | 0.00 |
February | 0.00 | 0.00 | 0.389735E+09 | 0.389735E+09 | 15724.67 | 23-FEB-09:01 | 15724.67 | 0.00 |
March | 0.00 | 0.00 | 0.128611E+10 | 0.128608E+10 | 16759.84 | 13-MAR-15:01 | 16759.84 | 0.00 |
April | 0.00 | 0.00 | 0.131061E+10 | 0.124901E+10 | 16491.40 | 27-APR-15:01 | 16491.40 | 0.04 |
May | 0.00 | 0.00 | 0.395477E+10 | 0.338849E+10 | 17372.40 | 16-MAY-15:01 | 17372.40 | 0.25 |
June | 0.00 | 0.00 | 0.977520E+10 | 0.773497E+10 | 17391.49 | 05-JUN-15:01 | 17391.49 | 0.56 |
July | 0.00 | 0.00 | 0.989426E+10 | 0.751461E+10 | 17392.10 | 12-JUL-18:01 | 17392.10 | 0.60 |
August | 0.00 | 0.00 | 0.910830E+10 | 0.656901E+10 | 17392.15 | 19-AUG-15:01 | 17392.15 | 0.67 |
September | 0.00 | 0.00 | 0.578243E+10 | 0.495197E+10 | 17388.16 | 12-SEP-15:01 | 17388.16 | 0.28 |
October | 0.00 | 0.00 | 0.141310E+10 | 0.138493E+10 | 17211.78 | 11-OCT-15:01 | 17211.78 | 0.02 |
November | 0.00 | 0.00 | 0.372143E+09 | 0.371104E+09 | 15732.61 | 19-NOV-09:01 | 15732.61 | 0.00 |
December | 0.00 | 0.00 | 0.109773E+09 | 0.109773E+09 | 15149.08 | 02-DEC-09:01 | 15149.08 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.435873E+11 | 0.351405E+11 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 0.109773E+09 | 0.109773E+09 | 15149.08 | 15149.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.989426E+10 | 0.773497E+10 | 17392.15 | 17392.15 | 0.67 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.242682E+09 | 0.242682E+09 | 5063.13 | 23-JAN-16:01 | 5063.13 | 0.00 |
February | 0.00 | 0.00 | 0.276497E+09 | 0.276497E+09 | 5035.82 | 18-FEB-16:01 | 5035.82 | 0.00 |
March | 0.00 | 0.00 | 0.584255E+09 | 0.584242E+09 | 5264.37 | 13-MAR-15:01 | 5264.37 | 0.00 |
April | 0.00 | 0.00 | 0.394339E+09 | 0.384921E+09 | 5183.12 | 27-APR-15:01 | 5183.12 | 0.02 |
May | 0.00 | 0.00 | 0.917912E+09 | 0.803994E+09 | 5456.48 | 16-MAY-15:01 | 5456.48 | 0.19 |
June | 0.00 | 0.00 | 0.238848E+10 | 0.185463E+10 | 5463.04 | 13-JUN-08:61 | 5463.04 | 0.53 |
July | 0.00 | 0.00 | 0.227233E+10 | 0.164519E+10 | 5463.11 | 10-JUL-18:01 | 5463.11 | 0.58 |
August | 0.00 | 0.00 | 0.230676E+10 | 0.164512E+10 | 5462.68 | 19-AUG-15:01 | 5462.68 | 0.63 |
September | 0.00 | 0.00 | 0.169291E+10 | 0.145899E+10 | 5461.74 | 12-SEP-15:01 | 5461.74 | 0.28 |
October | 0.00 | 0.00 | 0.763726E+09 | 0.758363E+09 | 5406.33 | 11-OCT-15:01 | 5406.33 | 0.01 |
November | 0.00 | 0.00 | 0.352372E+09 | 0.352118E+09 | 5165.42 | 05-NOV-15:01 | 5165.42 | 0.00 |
December | 0.00 | 0.00 | 0.148083E+09 | 0.148083E+09 | 5022.63 | 02-DEC-16:01 | 5022.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.123403E+11 | 0.101548E+11 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 0.148083E+09 | 0.148083E+09 | 5022.63 | 5022.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.238848E+10 | 0.185463E+10 | 5463.11 | 5463.11 | 0.63 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 36221302.76 | 36221302.76 | 4922.07 | 23-JAN-16:01 | 4922.07 | 0.00 |
February | 0.00 | 0.00 | 59542315.78 | 59542315.78 | 4894.89 | 18-FEB-16:01 | 4894.89 | 0.00 |
March | 0.00 | 0.00 | 0.270018E+09 | 0.270000E+09 | 5117.34 | 14-MAR-15:01 | 5117.34 | 0.00 |
April | 0.00 | 0.00 | 0.242124E+09 | 0.235643E+09 | 5038.70 | 27-APR-15:01 | 5038.70 | 0.02 |
May | 0.00 | 0.00 | 0.790235E+09 | 0.686530E+09 | 5304.33 | 16-MAY-15:01 | 5304.33 | 0.18 |
June | 0.00 | 0.00 | 0.229745E+10 | 0.178442E+10 | 5310.91 | 13-JUN-08:61 | 5310.91 | 0.54 |
July | 0.00 | 0.00 | 0.215202E+10 | 0.155580E+10 | 5310.91 | 10-JUL-18:01 | 5310.91 | 0.57 |
August | 0.00 | 0.00 | 0.196566E+10 | 0.137700E+10 | 5310.50 | 19-AUG-15:01 | 5310.50 | 0.62 |
September | 0.00 | 0.00 | 0.121530E+10 | 0.102127E+10 | 5309.58 | 04-SEP-15:01 | 5309.58 | 0.26 |
October | 0.00 | 0.00 | 0.331358E+09 | 0.330562E+09 | 5255.31 | 11-OCT-15:01 | 5255.31 | 0.00 |
November | 0.00 | 0.00 | 67371733.31 | 67360029.67 | 5021.05 | 05-NOV-15:01 | 5021.05 | 0.00 |
December | 0.00 | 0.00 | 14271410.42 | 14271410.42 | 4882.35 | 02-DEC-16:01 | 4882.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.944158E+10 | 0.743862E+10 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 14271410.42 | 14271410.42 | 4882.35 | 4882.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.229745E+10 | 0.178442E+10 | 5310.91 | 5310.91 | 0.62 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.681128E+10 | 0.680484E+10 | 21626.78 | 23-JAN-16:01 | 21626.78 | 0.00 |
February | 0.00 | 0.00 | 0.546330E+10 | 0.546290E+10 | 21505.89 | 18-FEB-16:01 | 21505.89 | 0.00 |
March | 0.00 | 0.00 | 0.567808E+10 | 0.567245E+10 | 22484.07 | 13-MAR-15:01 | 22484.07 | 0.00 |
April | 0.00 | 0.00 | 0.273625E+10 | 0.264051E+10 | 22132.52 | 27-APR-15:01 | 22132.52 | 0.05 |
May | 0.00 | 0.00 | 0.468945E+10 | 0.403990E+10 | 23298.90 | 16-MAY-15:01 | 23298.90 | 0.24 |
June | 0.00 | 0.00 | 0.103829E+11 | 0.771375E+10 | 23317.87 | 30-JUN-08:61 | 23317.87 | 0.56 |
July | 0.00 | 0.00 | 0.113264E+11 | 0.811148E+10 | 23319.82 | 13-JUL-18:01 | 23319.82 | 0.61 |
August | 0.00 | 0.00 | 0.126454E+11 | 0.934246E+10 | 23316.53 | 10-AUG-18:01 | 23316.53 | 0.66 |
September | 0.00 | 0.00 | 0.114714E+11 | 0.103343E+11 | 23310.81 | 11-SEP-15:01 | 23310.81 | 0.29 |
October | 0.00 | 0.00 | 0.808582E+10 | 0.797706E+10 | 23087.71 | 11-OCT-15:01 | 23087.71 | 0.04 |
November | 0.00 | 0.00 | 0.710749E+10 | 0.707653E+10 | 22063.65 | 05-NOV-15:01 | 22063.65 | 0.02 |
December | 0.00 | 0.00 | 0.490644E+10 | 0.490644E+10 | 21451.53 | 02-DEC-16:01 | 21451.53 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.913042E+11 | 0.800826E+11 | 0.21 | |||
Minimum of Months | 0.00 | 0.00 | 0.273625E+10 | 0.264051E+10 | 21451.53 | 21451.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.126454E+11 | 0.103343E+11 | 23319.82 | 23319.82 | 0.66 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 31876.43 | 250398.16 | 05-JAN-09:03 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 37115.23 | 195522.72 | 12-FEB-09:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 23373.80 | 225221.65 | 22-MAR-15:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 18759.25 | 199246.34 | 22-APR-15:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5504.54 | 180671.09 | 09-MAY-02:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 207.59 | 81016.82 | 09-JUN-04:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 232.98 | 84856.35 | 06-JUL-08:04 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 65.93 | 35800.02 | 30-AUG-15:04 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1388.02 | 147613.39 | 22-SEP-08:61 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 19007.91 | 213986.43 | 02-OCT-15:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 26233.96 | 185325.39 | 29-NOV-09:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 51778.96 | 304895.02 | 21-DEC-09:03 |
Annual Sum or Average | 0.00 | 17873.83 | ||||
Minimum of Months | 0.00 | 0.00 | 65.93 | 35800.02 | ||
Maximum of Months | 0.00 | 0.00 | 51778.96 | 304895.02 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 19062.02 | 243294.58 | 20-JAN-13:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 16227.24 | 224189.47 | 18-FEB-13:30 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 24998.63 | 399203.02 | 13-MAR-15:01 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 19280.81 | 304676.07 | 19-APR-15:01 | 0.00 | 0.00 | 01-APR-00:10 |
May | 65742.57 | 411927.14 | 17-MAY-18:01 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 189000.26 | 524399.38 | 26-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 204343.96 | 505872.26 | 29-JUL-18:01 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 187754.75 | 508609.36 | 16-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 141861.00 | 468321.87 | 28-SEP-15:01 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 39681.61 | 440128.64 | 11-OCT-15:01 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 23309.96 | 265837.50 | 07-NOV-16:01 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 14242.91 | 217299.18 | 02-DEC-13:00 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 79146.69 | 0.00 | ||||
Minimum of Months | 14242.91 | 217299.18 | 0.00 | 0.00 | ||
Maximum of Months | 204343.96 | 524399.38 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 29053.31 | 67824.94 | 18-JAN-21:51 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 29408.01 | 66054.50 | 18-FEB-08:23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 29013.28 | 66089.29 | 10-MAR-06:51 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27904.77 | 64104.75 | 13-APR-06:13 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26439.74 | 62960.94 | 08-MAY-06:32 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25020.02 | 56343.72 | 09-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 23939.36 | 50730.29 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23589.75 | 47632.20 | 31-AUG-06:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23988.36 | 54940.57 | 24-SEP-07:04 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25041.22 | 57714.94 | 21-OCT-21:31 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 26526.14 | 63374.22 | 24-NOV-21:21 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 27995.49 | 66752.25 | 14-DEC-07:47 |
Annual Sum or Average | 0.00 | 26476.27 | ||||
Minimum of Months | 0.00 | 0.00 | 23589.75 | 47632.20 | ||
Maximum of Months | 0.00 | 0.00 | 29408.01 | 67824.94 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 1.08 | 2194.93 | 01-JAN-00:05 | 1.08 |
February | 0.530997E+10 | 1.08 | 2194.93 | 01-FEB-00:05 | 1.08 |
March | 0.587890E+10 | 1.08 | 2194.93 | 01-MAR-00:10 | 1.08 |
April | 0.568926E+10 | 1.08 | 2194.93 | 01-APR-00:10 | 1.08 |
May | 0.587890E+10 | 1.08 | 2194.93 | 01-MAY-00:10 | 1.07 |
June | 0.568926E+10 | 1.07 | 2194.93 | 01-JUN-00:10 | 1.07 |
July | 0.587890E+10 | 1.07 | 2194.93 | 01-JUL-00:10 | 1.08 |
August | 0.587890E+10 | 1.07 | 2194.93 | 01-AUG-00:10 | 1.07 |
September | 0.568926E+10 | 1.08 | 2194.93 | 01-SEP-00:10 | 1.08 |
October | 0.587890E+10 | 1.08 | 2194.93 | 01-OCT-00:10 | 1.07 |
November | 0.568926E+10 | 1.08 | 2194.93 | 01-NOV-00:10 | 1.08 |
December | 0.587890E+10 | 1.08 | 2194.93 | 01-DEC-00:03 | 1.08 |
Annual Sum or Average | 0.692193E+11 | 1.08 | |||
Minimum of Months | 0.530997E+10 | 1.07 | 2194.93 | 1.07 | |
Maximum of Months | 0.587890E+10 | 1.08 | 2194.93 | 1.08 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.395949E+11 | 0.96 | 49341.76 | 13-JAN-17:10 | 2.00 |
February | 0.348785E+11 | 0.95 | 47602.10 | 23-FEB-20:55 | 1.94 |
March | 0.390216E+11 | 0.96 | 47594.05 | 13-MAR-05:20 | 1.95 |
April | 0.373706E+11 | 0.95 | 47594.05 | 12-APR-00:32 | 1.95 |
May | 0.395574E+11 | 0.96 | 47594.05 | 02-MAY-21:53 | 1.95 |
June | 0.437016E+11 | 1.03 | 41424.42 | 14-JUN-21:10 | 1.78 |
July | 0.452836E+11 | 1.03 | 41316.64 | 18-JUL-21:10 | 1.77 |
August | 0.465529E+11 | 1.05 | 44277.65 | 16-AUG-21:10 | 1.85 |
September | 0.446654E+11 | 1.05 | 46180.44 | 12-SEP-21:10 | 1.90 |
October | 0.429162E+11 | 1.01 | 48001.34 | 16-OCT-20:40 | 1.96 |
November | 0.406318E+11 | 0.99 | 47594.05 | 04-NOV-18:45 | 1.94 |
December | 0.398032E+11 | 0.97 | 47594.05 | 14-DEC-22:31 | 1.95 |
Annual Sum or Average | 0.493978E+12 | 0.99 | |||
Minimum of Months | 0.348785E+11 | 0.95 | 41316.64 | 1.77 | |
Maximum of Months | 0.465529E+11 | 1.05 | 49341.76 | 2.00 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.33 | 76.61 | 01-JAN-00:05 | 0.33 |
February | 0.185347E+09 | 0.33 | 76.61 | 01-FEB-00:05 | 0.33 |
March | 0.205205E+09 | 0.33 | 76.61 | 01-MAR-00:10 | 0.33 |
April | 0.198586E+09 | 0.33 | 76.61 | 01-APR-00:10 | 0.33 |
May | 0.205205E+09 | 0.33 | 76.61 | 01-MAY-00:10 | 0.33 |
June | 0.198586E+09 | 0.33 | 76.61 | 01-JUN-00:10 | 0.33 |
July | 0.205205E+09 | 0.33 | 76.61 | 01-JUL-00:10 | 0.33 |
August | 0.205205E+09 | 0.33 | 76.61 | 01-AUG-00:10 | 0.32 |
September | 0.198586E+09 | 0.33 | 76.61 | 01-SEP-00:10 | 0.33 |
October | 0.205205E+09 | 0.33 | 76.61 | 01-OCT-00:10 | 0.33 |
November | 0.198586E+09 | 0.33 | 76.61 | 01-NOV-00:10 | 0.33 |
December | 0.205205E+09 | 0.33 | 76.61 | 01-DEC-00:03 | 0.33 |
Annual Sum or Average | 0.241613E+10 | 0.33 | |||
Minimum of Months | 0.185347E+09 | 0.33 | 76.61 | 0.32 | |
Maximum of Months | 0.205205E+09 | 0.33 | 76.61 | 0.33 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.23 | 612.92 | 01-JAN-07:10 | 0.33 |
February | 0.105030E+10 | 0.23 | 612.92 | 01-FEB-07:05 | 0.33 |
March | 0.116283E+10 | 0.23 | 612.92 | 01-MAR-07:05 | 0.33 |
April | 0.112532E+10 | 0.23 | 612.92 | 01-APR-06:05 | 0.33 |
May | 0.116283E+10 | 0.23 | 612.92 | 01-MAY-06:02 | 0.33 |
June | 0.112532E+10 | 0.23 | 612.92 | 01-JUN-06:05 | 0.32 |
July | 0.116283E+10 | 0.23 | 612.92 | 01-JUL-06:05 | 0.33 |
August | 0.116283E+10 | 0.23 | 612.92 | 01-AUG-06:05 | 0.33 |
September | 0.112532E+10 | 0.23 | 612.92 | 01-SEP-06:05 | 0.32 |
October | 0.116283E+10 | 0.23 | 612.92 | 01-OCT-06:03 | 0.33 |
November | 0.112532E+10 | 0.23 | 612.92 | 01-NOV-06:05 | 0.33 |
December | 0.116283E+10 | 0.23 | 612.92 | 01-DEC-07:02 | 0.33 |
Annual Sum or Average | 0.136914E+11 | 0.23 | |||
Minimum of Months | 0.105030E+10 | 0.23 | 612.92 | 0.32 | |
Maximum of Months | 0.116283E+10 | 0.23 | 612.92 | 0.33 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.249443E+09 | 0.57 | 1029.57 | 01-JAN-16:01 | 0.71 |
February | 0.265661E+09 | 0.59 | 1029.57 | 01-FEB-09:01 | 0.71 |
March | 0.303343E+09 | 0.60 | 1029.57 | 01-MAR-19:01 | 0.71 |
April | 0.238168E+09 | 0.57 | 1029.57 | 01-APR-18:01 | 0.71 |
May | 0.255205E+09 | 0.60 | 1029.57 | 02-MAY-15:01 | 0.71 |
June | 0.498215E+09 | 0.66 | 1029.57 | 01-JUN-08:62 | 0.70 |
July | 0.470339E+09 | 0.66 | 1029.57 | 01-JUL-08:61 | 0.71 |
August | 0.480159E+09 | 0.66 | 1029.57 | 01-AUG-15:01 | 0.71 |
September | 0.401591E+09 | 0.65 | 1029.57 | 01-SEP-08:62 | 0.70 |
October | 0.310350E+09 | 0.62 | 1029.57 | 01-OCT-15:01 | 0.71 |
November | 0.245851E+09 | 0.59 | 1029.57 | 01-NOV-08:61 | 0.71 |
December | 0.309725E+09 | 0.58 | 1029.57 | 01-DEC-16:01 | 0.71 |
Annual Sum or Average | 0.402805E+10 | 0.61 | |||
Minimum of Months | 0.238168E+09 | 0.57 | 1029.57 | 0.70 | |
Maximum of Months | 0.498215E+09 | 0.66 | 1029.57 | 0.71 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.278739E+09 | 0.54 | 1003.32 | 01-JAN-09:01 | 0.71 |
February | 0.274701E+09 | 0.57 | 1003.32 | 01-FEB-09:01 | 0.71 |
March | 0.262287E+09 | 0.56 | 1003.32 | 01-MAR-09:01 | 0.71 |
April | 0.216665E+09 | 0.55 | 1003.32 | 01-APR-15:01 | 0.71 |
May | 0.230455E+09 | 0.58 | 1003.32 | 02-MAY-08:62 | 0.71 |
June | 0.482688E+09 | 0.66 | 1003.32 | 01-JUN-08:62 | 0.70 |
July | 0.449516E+09 | 0.66 | 1003.32 | 01-JUL-08:61 | 0.71 |
August | 0.418294E+09 | 0.65 | 1003.32 | 01-AUG-15:01 | 0.71 |
September | 0.311410E+09 | 0.62 | 1003.32 | 01-SEP-15:02 | 0.70 |
October | 0.237563E+09 | 0.56 | 1003.32 | 01-OCT-15:01 | 0.71 |
November | 0.242531E+09 | 0.55 | 1003.32 | 01-NOV-08:61 | 0.71 |
December | 0.353237E+09 | 0.58 | 1003.32 | 01-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.375809E+10 | 0.59 | |||
Minimum of Months | 0.216665E+09 | 0.54 | 1003.32 | 0.70 | |
Maximum of Months | 0.482688E+09 | 0.66 | 1003.32 | 0.71 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141548E+10 | 0.31 | 3184.65 | 20-JAN-12:30 | 0.71 |
February | 0.125759E+10 | 0.35 | 3093.03 | 18-FEB-12:40 | 0.71 |
March | 0.117602E+10 | 0.37 | 2924.85 | 11-MAR-13:00 | 0.71 |
April | 0.316875E+09 | 0.16 | 1548.78 | 08-APR-13:10 | 0.71 |
May | 0.502073E+09 | 0.31 | 1007.29 | 18-MAY-17:06 | 0.71 |
June | 0.132273E+10 | 0.58 | 1366.28 | 14-JUN-13:30 | 0.71 |
July | 0.144994E+10 | 0.60 | 1570.63 | 23-JUL-13:20 | 0.71 |
August | 0.175854E+10 | 0.61 | 2592.14 | 25-AUG-13:10 | 0.71 |
September | 0.186650E+10 | 0.59 | 2787.03 | 28-SEP-13:00 | 0.71 |
October | 0.167128E+10 | 0.39 | 2949.14 | 10-OCT-12:30 | 0.71 |
November | 0.142074E+10 | 0.34 | 3238.69 | 07-NOV-11:25 | 0.71 |
December | 0.109152E+10 | 0.27 | 3004.03 | 17-DEC-12:10 | 0.71 |
Annual Sum or Average | 0.152493E+11 | 0.41 | |||
Minimum of Months | 0.316875E+09 | 0.16 | 1007.29 | 0.71 | |
Maximum of Months | 0.186650E+10 | 0.61 | 3238.69 | 0.71 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.120802E+10 | 0.51 | 4847.55 | 01-JAN-16:01 | 0.71 |
February | 0.118577E+10 | 0.51 | 4847.55 | 01-FEB-09:01 | 0.71 |
March | 0.952508E+09 | 0.50 | 4847.55 | 01-MAR-09:01 | 0.71 |
April | 0.804174E+09 | 0.50 | 4847.55 | 01-APR-15:01 | 0.71 |
May | 0.145852E+10 | 0.50 | 4847.55 | 01-MAY-18:02 | 0.71 |
June | 0.273181E+10 | 0.54 | 4847.55 | 01-JUN-08:62 | 0.70 |
July | 0.283215E+10 | 0.56 | 4847.55 | 01-JUL-08:61 | 0.71 |
August | 0.237070E+10 | 0.52 | 4847.55 | 01-AUG-15:01 | 0.71 |
September | 0.166822E+10 | 0.51 | 4847.55 | 01-SEP-08:62 | 0.70 |
October | 0.826714E+09 | 0.51 | 4847.55 | 01-OCT-08:62 | 0.71 |
November | 0.100088E+10 | 0.51 | 4847.55 | 01-NOV-08:61 | 0.71 |
December | 0.152281E+10 | 0.53 | 4847.55 | 01-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.185623E+11 | 0.52 | |||
Minimum of Months | 0.804174E+09 | 0.50 | 4847.55 | 0.70 | |
Maximum of Months | 0.283215E+10 | 0.56 | 4847.55 | 0.71 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.238693E+09 | 0.56 | 893.10 | 01-JAN-09:01 | 0.71 |
February | 0.261486E+09 | 0.60 | 893.10 | 01-FEB-09:01 | 0.71 |
March | 0.295526E+09 | 0.61 | 893.10 | 01-MAR-09:01 | 0.71 |
April | 0.239681E+09 | 0.59 | 893.10 | 01-APR-15:01 | 0.71 |
May | 0.272477E+09 | 0.64 | 893.10 | 02-MAY-15:01 | 0.71 |
June | 0.530709E+09 | 0.69 | 893.10 | 01-JUN-08:62 | 0.70 |
July | 0.533387E+09 | 0.69 | 893.10 | 01-JUL-08:61 | 0.71 |
August | 0.541889E+09 | 0.69 | 893.10 | 01-AUG-08:62 | 0.71 |
September | 0.421697E+09 | 0.67 | 893.10 | 01-SEP-08:62 | 0.70 |
October | 0.296916E+09 | 0.64 | 893.10 | 01-OCT-08:62 | 0.71 |
November | 0.237854E+09 | 0.59 | 893.10 | 01-NOV-08:61 | 0.71 |
December | 0.287749E+09 | 0.58 | 893.10 | 01-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.415806E+10 | 0.63 | |||
Minimum of Months | 0.237854E+09 | 0.56 | 893.10 | 0.70 | |
Maximum of Months | 0.541889E+09 | 0.69 | 893.10 | 0.71 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.257556E+09 | 0.53 | 871.25 | 01-JAN-16:01 | 0.71 |
February | 0.257890E+09 | 0.57 | 871.25 | 01-FEB-09:01 | 0.71 |
March | 0.243274E+09 | 0.56 | 871.25 | 01-MAR-09:01 | 0.71 |
April | 0.214386E+09 | 0.56 | 871.25 | 01-APR-15:01 | 0.71 |
May | 0.246691E+09 | 0.62 | 871.25 | 03-MAY-08:61 | 0.71 |
June | 0.516272E+09 | 0.69 | 871.25 | 01-JUN-08:62 | 0.70 |
July | 0.514050E+09 | 0.68 | 871.25 | 01-JUL-08:61 | 0.71 |
August | 0.476742E+09 | 0.68 | 871.25 | 01-AUG-08:62 | 0.71 |
September | 0.327726E+09 | 0.66 | 871.25 | 01-SEP-08:62 | 0.70 |
October | 0.213404E+09 | 0.56 | 871.25 | 01-OCT-08:62 | 0.71 |
November | 0.230196E+09 | 0.53 | 871.25 | 01-NOV-08:61 | 0.71 |
December | 0.326192E+09 | 0.57 | 871.25 | 02-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.382438E+10 | 0.60 | |||
Minimum of Months | 0.213404E+09 | 0.53 | 871.25 | 0.70 | |
Maximum of Months | 0.516272E+09 | 0.69 | 871.25 | 0.71 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 77930182.25 | 0.57 | 273.68 | 01-JAN-16:01 | 0.71 |
February | 80102445.09 | 0.59 | 273.68 | 01-FEB-09:01 | 0.71 |
March | 87807018.47 | 0.61 | 273.68 | 01-MAR-09:01 | 0.71 |
April | 72233510.60 | 0.59 | 273.68 | 01-APR-15:01 | 0.71 |
May | 64207327.84 | 0.60 | 273.68 | 02-MAY-08:62 | 0.71 |
June | 0.124717E+09 | 0.66 | 273.68 | 01-JUN-15:02 | 0.71 |
July | 0.116196E+09 | 0.66 | 273.68 | 01-JUL-08:61 | 0.71 |
August | 0.118695E+09 | 0.66 | 273.68 | 01-AUG-15:01 | 0.71 |
September | 95738067.33 | 0.65 | 273.68 | 01-SEP-15:02 | 0.70 |
October | 85705213.87 | 0.62 | 273.68 | 01-OCT-15:01 | 0.71 |
November | 74964427.94 | 0.59 | 273.68 | 01-NOV-08:61 | 0.71 |
December | 95087077.65 | 0.59 | 273.68 | 01-DEC-16:01 | 0.71 |
Annual Sum or Average | 0.109338E+10 | 0.62 | |||
Minimum of Months | 64207327.84 | 0.57 | 273.68 | 0.70 | |
Maximum of Months | 0.124717E+09 | 0.66 | 273.68 | 0.71 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 90327869.11 | 0.58 | 266.05 | 01-JAN-09:01 | 0.71 |
February | 85569654.32 | 0.58 | 266.05 | 01-FEB-09:01 | 0.71 |
March | 79459722.30 | 0.58 | 266.05 | 01-MAR-09:01 | 0.71 |
April | 67444911.88 | 0.57 | 266.05 | 01-APR-15:01 | 0.71 |
May | 58255469.51 | 0.58 | 266.05 | 02-MAY-08:62 | 0.71 |
June | 0.120668E+09 | 0.66 | 266.05 | 01-JUN-15:02 | 0.71 |
July | 0.110546E+09 | 0.66 | 266.05 | 01-JUL-08:61 | 0.71 |
August | 0.102127E+09 | 0.65 | 266.05 | 01-AUG-15:01 | 0.71 |
September | 73043045.20 | 0.62 | 266.05 | 01-SEP-15:02 | 0.70 |
October | 71538262.14 | 0.57 | 266.05 | 01-OCT-15:01 | 0.71 |
November | 78503920.13 | 0.56 | 266.05 | 01-NOV-08:61 | 0.71 |
December | 0.109949E+09 | 0.61 | 266.05 | 01-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.104743E+10 | 0.60 | |||
Minimum of Months | 58255469.51 | 0.56 | 266.05 | 0.70 | |
Maximum of Months | 0.120668E+09 | 0.66 | 266.05 | 0.71 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.514193E+09 | 0.63 | 1166.20 | 01-JAN-09:01 | 0.71 |
February | 0.474928E+09 | 0.64 | 1166.20 | 01-FEB-09:01 | 0.71 |
March | 0.482317E+09 | 0.63 | 1166.20 | 01-MAR-16:02 | 0.71 |
April | 0.315335E+09 | 0.59 | 1166.20 | 01-APR-15:01 | 0.71 |
May | 0.296112E+09 | 0.61 | 1166.20 | 02-MAY-15:01 | 0.71 |
June | 0.529055E+09 | 0.65 | 1166.20 | 01-JUN-15:02 | 0.71 |
July | 0.569287E+09 | 0.66 | 1166.20 | 01-JUL-08:61 | 0.71 |
August | 0.633104E+09 | 0.66 | 1166.20 | 01-AUG-15:01 | 0.71 |
September | 0.620837E+09 | 0.66 | 1166.20 | 01-SEP-08:62 | 0.70 |
October | 0.566378E+09 | 0.64 | 1166.20 | 01-OCT-08:62 | 0.71 |
November | 0.518873E+09 | 0.63 | 1166.20 | 01-NOV-08:61 | 0.71 |
December | 0.494235E+09 | 0.61 | 1166.20 | 01-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.601465E+10 | 0.63 | |||
Minimum of Months | 0.296112E+09 | 0.59 | 1166.20 | 0.70 | |
Maximum of Months | 0.633104E+09 | 0.66 | 1166.20 | 0.71 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.662325E+09 | 0.596092E+09 | 914.56 | 05-JAN-09:03 | 823.10 | 823.10 | 41.49 | 1.47 |
February | 0.672266E+09 | 0.605039E+09 | 873.89 | 21-FEB-23:37 | 786.50 | 786.50 | 52.82 | 1.35 |
March | 0.515267E+09 | 0.463740E+09 | 918.42 | 20-MAR-22:55 | 826.58 | 826.58 | 53.92 | 1.48 |
April | 0.409196E+09 | 0.368276E+09 | 866.20 | 25-APR-01:25 | 779.58 | 779.58 | 52.08 | 1.33 |
May | 0.102175E+09 | 91957255.36 | 813.72 | 12-MAY-02:62 | 732.35 | 732.35 | 58.18 | 1.19 |
June | 3254472.48 | 2929025.24 | 570.23 | 09-JUN-04:15 | 513.20 | 513.20 | 53.00 | 0.72 |
July | 3275035.16 | 2947531.64 | 383.53 | 06-JUL-08:04 | 345.18 | 345.18 | 33.93 | 0.45 |
August | 1657941.41 | 1492147.27 | 295.23 | 30-AUG-15:04 | 265.71 | 265.71 | 53.39 | 0.33 |
September | 30239303.92 | 27215373.53 | 813.32 | 22-SEP-08:61 | 731.99 | 731.99 | 51.07 | 1.19 |
October | 0.393587E+09 | 0.354228E+09 | 848.87 | 26-OCT-03:45 | 763.99 | 763.99 | 57.70 | 1.28 |
November | 0.553692E+09 | 0.498323E+09 | 842.73 | 18-NOV-05:38 | 758.45 | 758.45 | 59.72 | 1.26 |
December | 0.884098E+09 | 0.795688E+09 | 1012.63 | 21-DEC-09:03 | 911.37 | 911.37 | 42.25 | 1.83 |
Annual Sum or Average | 0.423103E+10 | 0.380793E+10 | ||||||
Minimum of Months | 1657941.41 | 1492147.27 | 295.23 | 265.71 | 265.71 | 33.93 | 0.33 | |
Maximum of Months | 0.884098E+09 | 0.795688E+09 | 1012.63 | 911.37 | 911.37 | 59.72 | 1.83 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.124894E+10 | 0.112404E+10 | 3195.74 | 23-JAN-16:03 | 2876.16 | 2876.16 | 7.98 | 7.37 |
February | 0.104223E+10 | 0.938004E+09 | 3014.24 | 18-FEB-16:01 | 2712.82 | 2712.82 | 8.05 | 6.66 |
March | 0.156413E+10 | 0.140772E+10 | 3697.46 | 13-MAR-15:01 | 3327.71 | 3327.71 | 7.29 | 9.99 |
April | 0.122052E+10 | 0.109847E+10 | 3441.21 | 07-APR-15:01 | 3097.09 | 3097.09 | 7.59 | 8.50 |
May | 0.362669E+10 | 0.326402E+10 | 4061.56 | 31-MAY-18:50 | 3655.40 | 3655.40 | 7.20 | 13.36 |
June | 0.717562E+10 | 0.645806E+10 | 4192.75 | 15-JUN-18:13 | 3773.48 | 3773.48 | 6.73 | 15.31 |
July | 0.779260E+10 | 0.701334E+10 | 4211.86 | 17-JUL-19:20 | 3790.67 | 3790.67 | 6.73 | 15.63 |
August | 0.760657E+10 | 0.684591E+10 | 4171.18 | 25-AUG-18:03 | 3754.06 | 3754.06 | 6.73 | 14.96 |
September | 0.586322E+10 | 0.527690E+10 | 4199.99 | 12-SEP-18:03 | 3779.99 | 3779.99 | 6.73 | 15.43 |
October | 0.227365E+10 | 0.204628E+10 | 3743.09 | 11-OCT-15:01 | 3368.78 | 3368.78 | 6.85 | 10.31 |
November | 0.140947E+10 | 0.126852E+10 | 3412.12 | 07-NOV-16:01 | 3070.91 | 3070.91 | 7.64 | 8.35 |
December | 0.870328E+09 | 0.783295E+09 | 2968.26 | 17-DEC-16:03 | 2671.44 | 2671.44 | 8.39 | 6.49 |
Annual Sum or Average | 0.416940E+11 | 0.375246E+11 | ||||||
Minimum of Months | 0.870328E+09 | 0.783295E+09 | 2968.26 | 2671.44 | 2671.44 | 6.73 | 6.49 | |
Maximum of Months | 0.779260E+10 | 0.701334E+10 | 4211.86 | 3790.67 | 3790.67 | 8.39 | 15.63 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.621039E+10 | 0.558935E+10 | 3698.53 | 01-JAN-00:05 | 3328.67 | 3328.67 | 8.40 | 25.92 |
February | 0.526859E+10 | 0.474173E+10 | 3698.53 | 01-FEB-00:05 | 3328.67 | 3328.67 | 8.40 | 25.92 |
March | 0.649813E+10 | 0.584832E+10 | 3698.53 | 01-MAR-04:10 | 3328.67 | 3328.67 | 8.41 | 25.92 |
April | 0.611635E+10 | 0.550471E+10 | 3698.53 | 01-APR-00:10 | 3328.67 | 3328.67 | 8.42 | 25.92 |
May | 0.930583E+10 | 0.837525E+10 | 3698.53 | 01-MAY-05:15 | 3328.67 | 3328.67 | 8.41 | 25.92 |
June | 0.958658E+10 | 0.862792E+10 | 3698.53 | 01-JUN-00:10 | 3328.67 | 3328.67 | 8.81 | 25.92 |
July | 0.990613E+10 | 0.891552E+10 | 3698.53 | 01-JUL-00:10 | 3328.67 | 3328.67 | 9.25 | 25.92 |
August | 0.990613E+10 | 0.891552E+10 | 3698.53 | 01-AUG-00:10 | 3328.67 | 3328.67 | 8.98 | 25.92 |
September | 0.935847E+10 | 0.842263E+10 | 3698.53 | 01-SEP-00:10 | 3328.67 | 3328.67 | 9.04 | 25.92 |
October | 0.729262E+10 | 0.656336E+10 | 3698.53 | 01-OCT-00:10 | 3328.67 | 3328.67 | 8.53 | 25.92 |
November | 0.674674E+10 | 0.607207E+10 | 3698.53 | 01-NOV-01:05 | 3328.67 | 3328.67 | 8.40 | 25.92 |
December | 0.491913E+10 | 0.442722E+10 | 3698.53 | 01-DEC-00:03 | 3328.67 | 3328.67 | 8.48 | 25.92 |
Annual Sum or Average | 0.911151E+11 | 0.820036E+11 | ||||||
Minimum of Months | 0.491913E+10 | 0.442722E+10 | 3698.53 | 3328.67 | 3328.67 | 8.40 | 25.92 | |
Maximum of Months | 0.990613E+10 | 0.891552E+10 | 3698.53 | 3328.67 | 3328.67 | 9.25 | 25.92 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 47.79 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 48.55 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:10 | 14.37 | 14.37 | 48.38 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 51.52 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 51.59 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 52.33 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.10 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 52.54 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 52.85 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 51.99 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 51.66 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 47.92 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 47.79 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 52.85 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 64.62 | 81.00 | 31876.43 | 250398.16 | 05-JAN-09:03 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 58.64 | 81.96 | 37115.23 | 195522.72 | 12-FEB-09:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 62.83 | 81.26 | 23373.80 | 225221.65 | 22-MAR-15:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 51.05 | 80.09 | 18759.25 | 199246.34 | 22-APR-15:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 51.13 | 80.17 | 5504.54 | 180671.09 | 09-MAY-02:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 47.65 | 47.65 | 207.59 | 81016.82 | 09-JUN-04:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 54.53 | 54.53 | 232.98 | 84856.35 | 06-JUL-08:04 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 61.40 | 61.40 | 65.93 | 35800.02 | 30-AUG-15:04 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 54.64 | 54.64 | 1388.02 | 147613.39 | 22-SEP-08:61 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 48.01 | 79.40 | 19007.91 | 213986.43 | 02-OCT-15:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.46 | 82.03 | 26233.96 | 185325.39 | 29-NOV-09:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 54.62 | 80.62 | 51778.96 | 304895.02 | 21-DEC-09:03 |
Annual Sum or Average | 0.00 | 17873.83 | ||||||
Minimum of Months | 0.00 | 0.00 | 47.65 | 47.65 | 65.93 | 35800.02 | ||
Maximum of Months | 0.00 | 0.00 | 64.62 | 82.03 | 51778.96 | 304895.02 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 19062.02 | 243294.58 | 20-JAN-13:00 | 9.80 | 7.56 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 16227.24 | 224189.47 | 18-FEB-13:30 | 9.77 | 7.71 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 24998.63 | 399203.02 | 13-MAR-15:01 | 10.93 | 7.26 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 19280.81 | 304676.07 | 19-APR-15:01 | 10.39 | 7.58 | 0.00 | 0.00 | 01-APR-00:10 |
May | 65742.57 | 411927.14 | 17-MAY-18:01 | 10.97 | 7.18 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 189000.26 | 524399.38 | 26-JUN-18:03 | 11.53 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 204343.96 | 505872.26 | 29-JUL-18:01 | 11.94 | 7.28 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 187754.75 | 508609.36 | 16-AUG-18:03 | 11.38 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 141861.00 | 468321.87 | 28-SEP-15:01 | 11.01 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 39681.61 | 440128.64 | 11-OCT-15:01 | 10.91 | 6.86 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 23309.96 | 265837.50 | 07-NOV-16:01 | 10.16 | 7.71 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 14242.91 | 217299.18 | 02-DEC-13:00 | 9.56 | 7.56 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 79146.69 | 0.00 | ||||||
Minimum of Months | 14242.91 | 217299.18 | 9.56 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 204343.96 | 524399.38 | 11.94 | 7.71 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 47.79 | 59.69 | 29053.31 | 67824.94 | 18-JAN-21:51 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 48.55 | 59.71 | 29408.01 | 66054.50 | 18-FEB-08:23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 48.38 | 58.69 | 29013.28 | 66089.29 | 10-MAR-06:51 |
April | 0.00 | 0.00 | 01-APR-00:10 | 51.52 | 59.31 | 27904.77 | 64104.75 | 13-APR-06:13 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 51.59 | 58.74 | 26439.74 | 62960.94 | 08-MAY-06:32 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 52.33 | 59.26 | 25020.02 | 56343.72 | 09-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.10 | 58.38 | 23939.36 | 50730.29 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 52.54 | 58.62 | 23589.75 | 47632.20 | 31-AUG-06:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 52.85 | 59.14 | 23988.36 | 54940.57 | 24-SEP-07:04 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 51.99 | 59.48 | 25041.22 | 57714.94 | 21-OCT-21:31 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 51.66 | 58.33 | 26526.14 | 63374.22 | 24-NOV-21:21 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 47.92 | 58.20 | 27995.49 | 66752.25 | 14-DEC-07:47 |
Annual Sum or Average | 0.00 | 26476.27 | ||||||
Minimum of Months | 0.00 | 0.00 | 47.79 | 58.20 | 23589.75 | 47632.20 | ||
Maximum of Months | 0.00 | 0.00 | 52.85 | 59.71 | 29408.01 | 67824.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.426878E+11 | 0.00 | 0.641639E+10 | 0.395949E+11 | 0.00 | 0.00 |
February | 0.405581E+11 | 0.00 | 0.362902E+10 | 0.348785E+11 | 0.00 | 0.00 |
March | 0.320821E+11 | 0.00 | 0.197927E+11 | 0.390216E+11 | 0.00 | 0.00 |
April | 0.278816E+11 | 0.00 | 0.205285E+11 | 0.373706E+11 | 0.00 | 0.00 |
May | 0.130918E+11 | 0.00 | 0.929566E+11 | 0.395574E+11 | 0.00 | 0.00 |
June | 0.483545E+09 | 0.00 | 0.298236E+12 | 0.437016E+11 | 0.00 | 0.00 |
July | 0.567910E+09 | 0.00 | 0.340417E+12 | 0.452836E+11 | 0.00 | 0.00 |
August | 0.125541E+09 | 0.00 | 0.305016E+12 | 0.465529E+11 | 0.00 | 0.00 |
September | 0.284279E+10 | 0.00 | 0.213776E+12 | 0.446654E+11 | 0.00 | 0.00 |
October | 0.299141E+11 | 0.00 | 0.363658E+11 | 0.429162E+11 | 0.00 | 0.00 |
November | 0.344210E+11 | 0.00 | 0.121905E+11 | 0.406318E+11 | 0.00 | 0.00 |
December | 0.701554E+11 | 0.00 | 0.825937E+10 | 0.398032E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.294812E+12 | 0.00 | 0.135758E+13 | 0.493978E+12 | 0.00 | 0.00 |
Minimum of Months | 0.125541E+09 | 0.00 | 0.362902E+10 | 0.348785E+11 | 0.00 | 0.00 |
Maximum of Months | 0.701554E+11 | 0.00 | 0.340417E+12 | 0.465529E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.316190E+10 | 0.00 | 0.806531E+09 | 0.587890E+10 | 0.00 | 0.00 |
February | 0.390286E+10 | 0.00 | 0.433446E+09 | 0.530997E+10 | 0.00 | 0.00 |
March | 0.170954E+10 | 0.00 | 0.270200E+10 | 0.587890E+10 | 0.00 | 0.00 |
April | 0.107353E+10 | 0.00 | 0.323869E+10 | 0.568926E+10 | 0.00 | 0.00 |
May | 1122062.52 | 0.00 | 0.144894E+11 | 0.587890E+10 | 0.00 | 0.00 |
June | 67780.01 | 0.00 | 0.425535E+11 | 0.568926E+10 | 0.00 | 0.00 |
July | 70037.25 | 0.00 | 0.503092E+11 | 0.587890E+10 | 0.00 | 0.00 |
August | 55654.53 | 0.00 | 0.438094E+11 | 0.587890E+10 | 0.00 | 0.00 |
September | 773806.63 | 0.00 | 0.303321E+11 | 0.568926E+10 | 0.00 | 0.00 |
October | 0.150886E+10 | 0.00 | 0.512374E+10 | 0.587890E+10 | 0.00 | 0.00 |
November | 0.190500E+10 | 0.00 | 0.173918E+10 | 0.568926E+10 | 0.00 | 0.00 |
December | 0.682983E+10 | 0.00 | 0.121720E+10 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.200936E+11 | 0.00 | 0.196754E+12 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 55654.53 | 0.00 | 0.433446E+09 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 0.682983E+10 | 0.00 | 0.503092E+11 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.395949E+11 | 0.641646E+10 | 0.426878E+11 | 0.401917E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.348785E+11 | 0.362908E+10 | 0.405581E+11 | 0.403899E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.390216E+11 | 0.197927E+11 | 0.320821E+11 | 0.291103E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.373706E+11 | 0.205287E+11 | 0.278816E+11 | 0.245661E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.395574E+11 | 0.929566E+11 | 0.130918E+11 | 0.611658E+11 | 0.261885E+09 | 0.00 | 0.00 | 0.00 |
June | 0.437016E+11 | 0.298236E+12 | 0.483545E+09 | 0.790729E+10 | 0.135830E+11 | 0.00 | 0.00 | 0.00 |
July | 0.452836E+11 | 0.340417E+12 | 0.567910E+09 | 0.771708E+10 | 0.145739E+11 | 0.00 | 0.00 | 0.00 |
August | 0.465529E+11 | 0.305016E+12 | 0.125541E+09 | 0.705706E+10 | 0.934252E+10 | 0.00 | 0.00 | 0.00 |
September | 0.446654E+11 | 0.213776E+12 | 0.284279E+10 | 0.262540E+11 | 0.326093E+10 | 0.00 | 0.00 | 0.00 |
October | 0.429162E+11 | 0.363681E+11 | 0.299141E+11 | 0.207911E+12 | 2972200.13 | 0.00 | 0.00 | 0.00 |
November | 0.406318E+11 | 0.121918E+11 | 0.344210E+11 | 0.314956E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.398032E+11 | 0.825937E+10 | 0.701554E+11 | 0.438044E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.493978E+12 | 0.135759E+13 | 0.294812E+12 | 0.241359E+13 | 0.410252E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.348785E+11 | 0.362908E+10 | 0.125541E+09 | 0.705706E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.465529E+11 | 0.340417E+12 | 0.701554E+11 | 0.438044E+12 | 0.145739E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.806531E+09 | 0.316190E+10 | 0.830990E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.433446E+09 | 0.390286E+10 | 0.794331E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.270200E+10 | 0.170954E+10 | 0.625711E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.323869E+10 | 0.107353E+10 | 0.544234E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.144894E+11 | 1122062.52 | 0.194649E+11 | 0.247929E+09 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.425535E+11 | 67780.01 | 0.130059E+10 | 0.648091E+10 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.503092E+11 | 70037.25 | 0.963396E+09 | 0.782602E+10 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.438094E+11 | 55654.53 | 0.940801E+09 | 0.534035E+10 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.303321E+11 | 773806.63 | 0.759686E+10 | 0.198929E+10 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.512374E+10 | 0.150886E+10 | 0.502668E+11 | 15606319.25 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.173918E+10 | 0.190500E+10 | 0.700692E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.121720E+10 | 0.682983E+10 | 0.898003E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.196754E+12 | 0.200936E+11 | 0.519929E+12 | 0.219001E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.433446E+09 | 55654.53 | 0.940801E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.503092E+11 | 0.682983E+10 | 0.898003E+11 | 0.782602E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.395949E+11 | 0.426878E+11 | 0.641639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.348785E+11 | 0.405581E+11 | 0.362902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.390216E+11 | 0.320821E+11 | 0.197927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.373706E+11 | 0.278816E+11 | 0.205285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.395574E+11 | 0.130918E+11 | 0.929566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.437016E+11 | 0.483545E+09 | 0.298236E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.452836E+11 | 0.567910E+09 | 0.340417E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.465529E+11 | 0.125541E+09 | 0.305016E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.446654E+11 | 0.284279E+10 | 0.213776E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.429162E+11 | 0.299141E+11 | 0.363658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.406318E+11 | 0.344210E+11 | 0.121905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.398032E+11 | 0.701554E+11 | 0.825937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.493978E+12 | 0.294812E+12 | 0.135758E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.348785E+11 | 0.125541E+09 | 0.362902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.465529E+11 | 0.701554E+11 | 0.340417E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 0.316190E+10 | 0.806531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.390286E+10 | 0.433446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.170954E+10 | 0.270200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.107353E+10 | 0.323869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 1122062.52 | 0.144894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 67780.01 | 0.425535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 70037.25 | 0.503092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 55654.53 | 0.438094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 773806.63 | 0.303321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.150886E+10 | 0.512374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.190500E+10 | 0.173918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.682983E+10 | 0.121720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.200936E+11 | 0.196754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 55654.53 | 0.433446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.682983E+10 | 0.503092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.433974E+10 | 0.00 | 0.00 | 85457214.97 | 0.00 | 0.00 | 0.449979E+11 | 0.00 | 0.90 |
February | 0.996841E+10 | 0.00 | 0.00 | 48901834.94 | 0.00 | 0.00 | 0.313924E+11 | 0.00 | 0.85 |
March | 0.176584E+11 | 0.00 | 0.00 | 33944391.57 | 0.00 | 0.00 | 0.251408E+11 | 0.00 | 0.85 |
April | 0.142556E+11 | 0.00 | 0.00 | 37261538.73 | 0.00 | 0.00 | 0.269756E+11 | 0.00 | 0.86 |
May | 0.131594E+11 | 0.00 | 0.00 | 20018339.67 | 1444136.97 | 0.00 | 0.234429E+11 | 0.00 | 0.89 |
June | 0.148460E+10 | 22692646.68 | 0.00 | 30156991.91 | 0.289418E+09 | 0.00 | 0.189468E+11 | 0.00 | 0.92 |
July | 0.598436E+09 | 77479537.37 | 0.00 | 37358674.12 | 0.320312E+09 | 0.00 | 0.180809E+11 | 0.00 | 0.93 |
August | 0.180136E+09 | 0.204200E+09 | 0.00 | 60323460.73 | 7391617.57 | 0.00 | 0.249286E+11 | 0.00 | 1.05 |
September | 4231594.02 | 29878814.64 | 0.00 | 89230381.64 | 0.00 | 0.00 | 0.365554E+11 | 0.00 | 1.19 |
October | 22533936.04 | 0.00 | 0.00 | 0.147869E+09 | 0.00 | 0.00 | 0.580827E+11 | 0.00 | 1.11 |
November | 55162454.98 | 0.00 | 0.00 | 0.161148E+09 | 0.00 | 0.00 | 0.576356E+11 | 0.00 | 1.08 |
December | 0.200918E+09 | 0.00 | 0.00 | 0.140141E+09 | 0.00 | 0.00 | 0.581455E+11 | 0.00 | 1.03 |
Annual Sum or Average | 0.619276E+11 | 0.334251E+09 | 0.00 | 0.891811E+09 | 0.618566E+09 | 0.00 | 0.424325E+12 | 0.00 | 0.97 |
Minimum of Months | 4231594.02 | 0.00 | 0.00 | 20018339.67 | 0.00 | 0.00 | 0.180809E+11 | 0.00 | 0.85 |
Maximum of Months | 0.176584E+11 | 0.204200E+09 | 0.00 | 0.161148E+09 | 0.320312E+09 | 0.00 | 0.581455E+11 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.277692E+10 | 0.00 | 0.00 | 9348492.31 | 0.00 | 0.554887E+09 | 0.268425E+10 | 0.00 | 2.12 |
February | 0.202698E+10 | 0.00 | 0.00 | 8044392.05 | 0.00 | 0.929271E+09 | 0.245703E+10 | 0.00 | 2.08 |
March | 0.227717E+10 | 0.00 | 0.00 | 5525363.76 | 0.00 | 0.832308E+09 | 0.222731E+10 | 0.00 | 2.09 |
April | 0.274401E+10 | 0.00 | 0.00 | 1925938.88 | 0.00 | 0.670229E+09 | 0.104408E+10 | 0.00 | 1.77 |
May | 0.261011E+10 | 293513.38 | 0.00 | 2982211.58 | 0.00 | 1376601.02 | 0.134953E+10 | 0.00 | 1.85 |
June | 0.482579E+09 | 70816253.74 | 0.00 | 6722568.87 | 0.00 | 0.00 | 0.182240E+10 | 0.00 | 2.26 |
July | 0.398752E+09 | 83672301.52 | 0.00 | 6897107.63 | 0.00 | 0.00 | 0.166548E+10 | 0.00 | 2.26 |
August | 0.406817E+09 | 54989810.76 | 0.00 | 8395271.74 | 0.00 | 0.00 | 0.214204E+10 | 0.00 | 2.47 |
September | 0.887239E+09 | 8416824.63 | 0.00 | 8707483.65 | 0.00 | 0.00 | 0.239908E+10 | 0.00 | 2.59 |
October | 0.213556E+10 | 0.00 | 0.00 | 6352198.92 | 0.00 | 0.587198E+09 | 0.289220E+10 | 0.00 | 2.30 |
November | 0.252741E+10 | 0.00 | 0.00 | 8762569.78 | 0.00 | 0.490823E+09 | 0.277733E+10 | 0.00 | 2.15 |
December | 0.264860E+10 | 0.00 | 0.00 | 6195109.90 | 0.00 | 0.113545E+10 | 0.191904E+10 | 0.00 | 1.97 |
Annual Sum or Average | 0.219222E+11 | 0.218189E+09 | 0.00 | 79858709.07 | 0.00 | 0.520154E+10 | 0.253798E+11 | 0.00 | 2.16 |
Minimum of Months | 0.398752E+09 | 0.00 | 0.00 | 1925938.88 | 0.00 | 0.00 | 0.104408E+10 | 0.00 | 1.77 |
Maximum of Months | 0.277692E+10 | 83672301.52 | 0.00 | 9348492.31 | 0.00 | 0.113545E+10 | 0.289220E+10 | 0.00 | 2.59 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.362125E+10 | 0.00 | 0.00 | 1277254.41 | 0.00 | 0.00 | 0.983671E+09 | 0.00 | 1.34 |
February | 0.324432E+10 | 0.00 | 0.00 | 1253927.25 | 0.00 | 200832.19 | 0.884581E+09 | 0.00 | 1.34 |
March | 0.306495E+10 | 0.00 | 0.00 | 1633847.37 | 0.00 | 0.00 | 0.142546E+10 | 0.00 | 1.40 |
April | 0.322386E+10 | 0.00 | 0.00 | 984143.39 | 0.00 | 0.00 | 0.991261E+09 | 0.00 | 1.39 |
May | 0.174615E+10 | 39590.89 | 0.00 | 2030176.06 | 115363.07 | 0.00 | 0.218496E+10 | 0.00 | 1.51 |
June | 69613926.46 | 33451501.18 | 0.00 | 4873687.47 | 416836.72 | 0.00 | 0.229214E+10 | 0.00 | 1.66 |
July | 44247615.65 | 39202702.70 | 0.00 | 5154267.68 | 3481976.16 | 0.00 | 0.206589E+10 | 0.00 | 1.63 |
August | 78945996.67 | 22840683.28 | 0.00 | 5318982.62 | 199128.79 | 0.00 | 0.238808E+10 | 0.00 | 1.66 |
September | 0.331398E+09 | 3113700.34 | 0.00 | 4891527.57 | 9669.21 | 0.00 | 0.269507E+10 | 0.00 | 1.63 |
October | 0.223157E+10 | 0.00 | 0.00 | 2456467.88 | 0.00 | 0.00 | 0.225657E+10 | 0.00 | 1.40 |
November | 0.315023E+10 | 0.00 | 0.00 | 1536997.95 | 0.00 | 0.00 | 0.123085E+10 | 0.00 | 1.32 |
December | 0.407489E+10 | 0.00 | 0.00 | 716145.98 | 0.00 | 0.00 | 0.585325E+09 | 0.00 | 1.31 |
Annual Sum or Average | 0.248814E+11 | 98648178.39 | 0.00 | 32127425.63 | 4222973.96 | 200832.19 | 0.199839E+11 | 0.00 | 1.47 |
Minimum of Months | 44247615.65 | 0.00 | 0.00 | 716145.98 | 0.00 | 0.00 | 0.585325E+09 | 0.00 | 1.31 |
Maximum of Months | 0.407489E+10 | 39202702.70 | 0.00 | 5318982.62 | 3481976.16 | 200832.19 | 0.269507E+10 | 0.00 | 1.66 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.258315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139169E+09 | 0.00 | 0.00 | 0.37 |
February | 0.215221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289609E+09 | 0.00 | 0.00 | 0.37 |
March | 0.250427E+10 | 0.00 | 0.00 | 105187.17 | 0.00 | 13353362.22 | 0.119295E+09 | 0.00 | 0.39 |
April | 0.246869E+10 | 0.00 | 0.00 | 16498.34 | 0.00 | 184406.44 | 26123453.72 | 0.00 | 0.39 |
May | 0.173777E+10 | 10462.10 | 0.00 | 838255.52 | 82364.63 | 0.00 | 0.646422E+09 | 0.00 | 0.43 |
June | 47597593.35 | 28703824.85 | 0.00 | 5127814.22 | 35592.08 | 0.00 | 0.169393E+10 | 0.00 | 0.60 |
July | 20987248.43 | 33574834.49 | 0.00 | 5511624.56 | 99607.78 | 0.00 | 0.159957E+10 | 0.00 | 0.61 |
August | 30687779.36 | 18066628.32 | 0.00 | 5290499.28 | 0.00 | 0.00 | 0.174678E+10 | 0.00 | 0.58 |
September | 0.442685E+09 | 2321060.76 | 0.00 | 3851052.37 | 0.00 | 0.00 | 0.157530E+10 | 0.00 | 0.53 |
October | 0.226786E+10 | 0.00 | 0.00 | 281580.59 | 0.00 | 60030829.43 | 0.284809E+09 | 0.00 | 0.39 |
November | 0.244600E+10 | 0.00 | 0.00 | 26711.13 | 0.00 | 98087775.97 | 38714808.71 | 0.00 | 0.37 |
December | 0.222343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556589E+09 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.189254E+11 | 82676810.52 | 0.00 | 21049223.17 | 217564.49 | 0.115702E+10 | 0.773096E+10 | 0.00 | 0.45 |
Minimum of Months | 20987248.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.258315E+10 | 33574834.49 | 0.00 | 5511624.56 | 99607.78 | 0.556589E+09 | 0.174678E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.247600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384925E+09 | 0.00 | 0.00 | 0.68 |
February | 0.185457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711578E+09 | 0.00 | 0.00 | 0.68 |
March | 0.254123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213950E+09 | 0.00 | 0.00 | 0.70 |
April | 0.246036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161673E+09 | 0.00 | 0.00 | 0.71 |
May | 0.239747E+10 | 0.00 | 0.00 | 0.00 | 97552.86 | 0.00 | 0.00 | 0.00 | 0.75 |
June | 0.127415E+10 | 155669.06 | 0.00 | 34953.52 | 20899727.42 | 0.00 | 32858166.45 | 0.00 | 0.75 |
July | 0.114714E+10 | 0.00 | 0.00 | 31347.57 | 26819766.40 | 0.00 | 24897114.52 | 0.00 | 0.75 |
August | 0.137906E+10 | 0.00 | 0.00 | 2170.50 | 14132919.52 | 0.00 | 2889938.71 | 0.00 | 0.76 |
September | 0.171751E+10 | 0.00 | 0.00 | 0.00 | 1962534.50 | 0.00 | 0.00 | 0.00 | 0.76 |
October | 0.252710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190771E+09 | 0.00 | 0.00 | 0.69 |
November | 0.240770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306054E+09 | 0.00 | 0.00 | 0.67 |
December | 0.206368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.857887E+09 | 0.00 | 0.00 | 0.67 |
Annual Sum or Average | 0.242459E+11 | 155669.06 | 0.00 | 68471.59 | 63912500.70 | 0.282684E+10 | 60645219.68 | 0.00 | 0.71 |
Minimum of Months | 0.114714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
Maximum of Months | 0.254123E+10 | 155669.06 | 0.00 | 34953.52 | 26819766.40 | 0.857887E+09 | 32858166.45 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 20762025.92 | 0.00 | 0.00 | 0.194382E+09 | 0.00 | 0.00 | 0.707048E+11 | 0.00 | 19.88 |
February | 2011497.41 | 0.00 | 0.00 | 0.165680E+09 | 0.00 | 0.00 | 0.632272E+11 | 0.00 | 19.87 |
March | 17180992.44 | 0.00 | 0.00 | 0.194113E+09 | 0.00 | 0.00 | 0.688623E+11 | 0.00 | 20.78 |
April | 15082352.73 | 0.00 | 0.00 | 0.176971E+09 | 0.00 | 0.00 | 0.652870E+11 | 0.00 | 20.94 |
May | 30263840.13 | 2043842.90 | 0.00 | 0.134368E+09 | 0.00 | 0.00 | 0.598988E+11 | 0.00 | 22.69 |
June | 0.00 | 0.430165E+09 | 0.00 | 0.104982E+09 | 0.00 | 0.00 | 0.310367E+11 | 0.00 | 22.74 |
July | 0.00 | 0.535921E+09 | 0.00 | 0.104554E+09 | 0.00 | 0.00 | 0.277987E+11 | 0.00 | 22.53 |
August | 0.00 | 0.292332E+09 | 0.00 | 0.111784E+09 | 0.00 | 0.00 | 0.332764E+11 | 0.00 | 22.94 |
September | 13738627.11 | 38803121.73 | 0.00 | 0.118583E+09 | 0.00 | 0.00 | 0.430356E+11 | 0.00 | 23.20 |
October | 24897316.05 | 0.00 | 0.00 | 0.174016E+09 | 0.00 | 0.00 | 0.679752E+11 | 0.00 | 20.56 |
November | 13816164.99 | 0.00 | 0.00 | 0.208300E+09 | 0.00 | 0.00 | 0.676370E+11 | 0.00 | 19.64 |
December | 79266532.90 | 0.00 | 0.00 | 0.190465E+09 | 0.00 | 0.00 | 0.707439E+11 | 0.00 | 19.34 |
Annual Sum or Average | 0.217019E+09 | 0.129926E+10 | 0.00 | 0.187820E+10 | 0.00 | 0.00 | 0.669484E+12 | 0.00 | 21.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.104554E+09 | 0.00 | 0.00 | 0.277987E+11 | 0.00 | 19.34 |
Maximum of Months | 79266532.90 | 0.535921E+09 | 0.00 | 0.208300E+09 | 0.00 | 0.00 | 0.707439E+11 | 0.00 | 23.20 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126723E+11 | 0.00 | 0.00 | 44783955.26 | 0.00 | 39094424.81 | 0.236146E+11 | 0.00 | 4.40 |
February | 0.122318E+11 | 0.00 | 0.00 | 38132867.60 | 0.00 | 0.425697E+09 | 0.199300E+11 | 0.00 | 4.38 |
March | 0.141591E+11 | 0.00 | 0.00 | 28966310.60 | 0.00 | 15815239.10 | 0.195535E+11 | 0.00 | 4.42 |
April | 0.169835E+11 | 0.00 | 0.00 | 12366002.80 | 0.00 | 2992467.99 | 0.140226E+11 | 0.00 | 4.22 |
May | 0.837544E+10 | 1143293.57 | 0.00 | 15319316.54 | 0.00 | 0.00 | 0.197993E+11 | 0.00 | 4.44 |
June | 0.850597E+09 | 0.251289E+09 | 0.00 | 25014505.86 | 1812107.46 | 0.00 | 0.146942E+11 | 0.00 | 4.52 |
July | 0.785114E+09 | 0.308440E+09 | 0.00 | 26756507.70 | 13295522.20 | 0.00 | 0.131997E+11 | 0.00 | 4.51 |
August | 0.856449E+09 | 0.195083E+09 | 0.00 | 33733706.67 | 148369.22 | 0.00 | 0.157341E+11 | 0.00 | 4.70 |
September | 0.202058E+10 | 28845986.64 | 0.00 | 37557221.16 | 6160.30 | 0.00 | 0.187692E+11 | 0.00 | 4.81 |
October | 0.105764E+11 | 0.00 | 0.00 | 33247971.00 | 0.00 | 0.549473E+09 | 0.228038E+11 | 0.00 | 4.52 |
November | 0.119775E+11 | 0.00 | 0.00 | 41782521.33 | 0.00 | 36257465.11 | 0.226481E+11 | 0.00 | 4.38 |
December | 0.181723E+11 | 0.00 | 0.00 | 29535784.35 | 0.00 | 0.747720E+09 | 0.173043E+11 | 0.00 | 4.28 |
Annual Sum or Average | 0.109661E+12 | 0.784802E+09 | 0.00 | 0.367197E+09 | 15262159.18 | 0.181705E+10 | 0.222073E+12 | 0.00 | 4.47 |
Minimum of Months | 0.785114E+09 | 0.00 | 0.00 | 12366002.80 | 0.00 | 0.00 | 0.131997E+11 | 0.00 | 4.22 |
Maximum of Months | 0.181723E+11 | 0.308440E+09 | 0.00 | 44783955.26 | 13295522.20 | 0.747720E+09 | 0.236146E+11 | 0.00 | 4.81 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.346442E+11 | 0.00 | 0.00 | 92912433.50 | 0.00 | 0.00 | 0.628645E+11 | 0.00 | 1.68 |
February | 0.384256E+11 | 0.00 | 0.00 | 72725199.85 | 0.00 | 0.00 | 0.484163E+11 | 0.00 | 1.67 |
March | 0.390863E+11 | 0.00 | 0.00 | 87738991.51 | 0.00 | 0.00 | 0.559428E+11 | 0.00 | 1.75 |
April | 0.429039E+11 | 0.00 | 0.00 | 62968689.48 | 0.00 | 0.00 | 0.462078E+11 | 0.00 | 1.74 |
May | 0.185433E+11 | 3197856.46 | 0.00 | 84050894.09 | 0.00 | 0.00 | 0.650177E+11 | 0.00 | 1.89 |
June | 0.113337E+10 | 0.685602E+09 | 0.00 | 0.102306E+09 | 10019047.20 | 0.00 | 0.500458E+11 | 0.00 | 2.06 |
July | 0.605914E+09 | 0.845041E+09 | 0.00 | 0.111146E+09 | 36754371.50 | 0.00 | 0.457285E+11 | 0.00 | 2.06 |
August | 0.971399E+09 | 0.484247E+09 | 0.00 | 0.120555E+09 | 1714846.02 | 0.00 | 0.529860E+11 | 0.00 | 2.10 |
September | 0.283097E+10 | 66976472.16 | 0.00 | 0.128397E+09 | 0.00 | 0.00 | 0.629835E+11 | 0.00 | 2.07 |
October | 0.243033E+11 | 0.00 | 0.00 | 0.127686E+09 | 0.00 | 0.00 | 0.720423E+11 | 0.00 | 1.78 |
November | 0.293698E+11 | 0.00 | 0.00 | 0.111941E+09 | 0.00 | 0.00 | 0.638534E+11 | 0.00 | 1.66 |
December | 0.532713E+11 | 0.00 | 0.00 | 70330629.31 | 0.00 | 0.00 | 0.448059E+11 | 0.00 | 1.64 |
Annual Sum or Average | 0.286089E+12 | 0.208506E+10 | 0.00 | 0.117276E+10 | 48488264.72 | 0.00 | 0.670894E+12 | 0.00 | 1.84 |
Minimum of Months | 0.605914E+09 | 0.00 | 0.00 | 62968689.48 | 0.00 | 0.00 | 0.448059E+11 | 0.00 | 1.64 |
Maximum of Months | 0.532713E+11 | 0.845041E+09 | 0.00 | 0.128397E+09 | 36754371.50 | 0.00 | 0.720423E+11 | 0.00 | 2.10 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.274857E+09 | 0.00 | 0.00 | 5886371.81 | 0.00 | 0.870711E+09 | 0.417830E+09 | 0.00 | 0.47 |
February | 0.224412E+09 | 0.00 | 0.00 | 6546239.08 | 0.00 | 0.793687E+09 | 0.388408E+09 | 0.00 | 0.47 |
March | 0.225559E+09 | 0.00 | 0.00 | 8050062.62 | 0.00 | 0.648738E+09 | 0.568480E+09 | 0.00 | 0.47 |
April | 0.246993E+09 | 0.00 | 0.00 | 5469792.53 | 0.00 | 0.610720E+09 | 0.487942E+09 | 0.00 | 0.47 |
May | 0.171542E+09 | 1042681.20 | 0.00 | 10528063.45 | 6557.51 | 0.104750E+09 | 0.933359E+09 | 0.00 | 0.47 |
June | 25614140.41 | 52287024.08 | 2126.84 | 9982352.49 | 2564350.52 | 307551.69 | 0.466147E+09 | 1621.76 | 0.47 |
July | 15256483.47 | 0.100611E+09 | 14174.74 | 8038531.00 | 4446283.15 | 244444.29 | 0.360592E+09 | 3828.60 | 0.47 |
August | 37396964.95 | 73087178.05 | 20999.00 | 10793841.83 | 1416119.24 | 647970.75 | 0.454468E+09 | 1852.64 | 0.47 |
September | 69236818.11 | 8452697.84 | 0.00 | 12805403.80 | 218140.75 | 37755383.61 | 0.700760E+09 | 0.00 | 0.47 |
October | 0.176946E+09 | 0.00 | 0.00 | 10113945.01 | 0.00 | 0.471010E+09 | 0.790780E+09 | 0.00 | 0.47 |
November | 0.241736E+09 | 0.00 | 0.00 | 6821605.08 | 0.00 | 0.699618E+09 | 0.523478E+09 | 0.00 | 0.47 |
December | 0.266745E+09 | 0.00 | 0.00 | 3355281.78 | 0.00 | 0.107675E+10 | 0.266007E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.197629E+10 | 0.235480E+09 | 37300.59 | 98391490.49 | 8651451.17 | 0.531494E+10 | 0.635825E+10 | 7303.00 | 0.47 |
Minimum of Months | 15256483.47 | 0.00 | 0.00 | 3355281.78 | 0.00 | 244444.29 | 0.266007E+09 | 0.00 | 0.47 |
Maximum of Months | 0.274857E+09 | 0.100611E+09 | 20999.00 | 12805403.80 | 4446283.15 | 0.107675E+10 | 0.933359E+09 | 3828.60 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.340363E+09 | 0.00 | 0.00 | 1172570.68 | 0.00 | 0.112458E+10 | 0.102984E+09 | 0.00 | 0.47 |
February | 0.271024E+09 | 0.00 | 0.00 | 1702370.40 | 0.00 | 0.100542E+10 | 0.134743E+09 | 0.00 | 0.47 |
March | 0.294525E+09 | 0.00 | 0.00 | 4173642.99 | 0.00 | 0.765440E+09 | 0.386518E+09 | 0.00 | 0.47 |
April | 0.295673E+09 | 0.00 | 0.00 | 3700526.75 | 0.00 | 0.682840E+09 | 0.368753E+09 | 0.00 | 0.47 |
May | 0.203594E+09 | 1042559.04 | 0.00 | 9477572.72 | 6556.74 | 0.117896E+09 | 0.889067E+09 | 0.00 | 0.47 |
June | 26598452.03 | 51967236.59 | 7615.82 | 9760688.29 | 2871892.47 | 401410.10 | 0.465231E+09 | 1951.24 | 0.47 |
July | 15716399.50 | 99713945.25 | 43812.25 | 7838451.08 | 5300371.76 | 218192.61 | 0.360313E+09 | 4551.14 | 0.47 |
August | 43273758.19 | 72612631.31 | 34212.31 | 9452553.89 | 1867043.28 | 662105.45 | 0.449860E+09 | 3530.22 | 0.47 |
September | 90045047.11 | 8344896.50 | 0.00 | 9842156.14 | 324926.17 | 56486903.85 | 0.664088E+09 | 0.00 | 0.47 |
October | 0.288782E+09 | 0.00 | 0.00 | 5157546.43 | 0.00 | 0.647537E+09 | 0.507203E+09 | 0.00 | 0.47 |
November | 0.320741E+09 | 0.00 | 0.00 | 1627396.68 | 0.00 | 0.976672E+09 | 0.172441E+09 | 0.00 | 0.47 |
December | 0.272795E+09 | 0.00 | 0.00 | 598820.68 | 0.00 | 0.127881E+10 | 60468205.84 | 0.00 | 0.47 |
Annual Sum or Average | 0.246313E+10 | 0.233681E+09 | 85640.37 | 64504296.74 | 10370790.42 | 0.665696E+10 | 0.456167E+10 | 10032.59 | 0.47 |
Minimum of Months | 15716399.50 | 0.00 | 0.00 | 598820.68 | 0.00 | 218192.61 | 60468205.84 | 0.00 | 0.47 |
Maximum of Months | 0.340363E+09 | 99713945.25 | 43812.25 | 9842156.14 | 5300371.76 | 0.127881E+10 | 0.889067E+09 | 4551.14 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112671E+11 | 0.00 | 0.00 | 0.139656E+09 | 0.00 | 0.813742E+09 | 0.905755E+10 | 0.00 | 0.54 |
February | 0.921960E+10 | 0.00 | 0.00 | 0.110584E+09 | 0.00 | 0.253232E+10 | 0.729723E+10 | 0.00 | 0.54 |
March | 0.967348E+10 | 0.00 | 0.00 | 67531277.68 | 0.00 | 0.265024E+10 | 0.728065E+10 | 0.00 | 0.54 |
April | 0.141103E+11 | 0.00 | 0.00 | 16619455.06 | 0.00 | 0.114893E+10 | 0.304417E+10 | 0.00 | 0.54 |
May | 0.914059E+10 | 14226735.89 | 0.00 | 40111083.66 | 0.00 | 0.00 | 0.736382E+10 | 0.00 | 0.54 |
June | 0.113530E+10 | 0.743786E+09 | 0.00 | 51294742.74 | 0.00 | 0.00 | 0.562077E+10 | 0.00 | 0.54 |
July | 0.851494E+09 | 0.142472E+10 | 0.00 | 43441603.92 | 0.00 | 0.00 | 0.431354E+10 | 0.00 | 0.54 |
August | 0.688432E+09 | 0.101046E+10 | 0.00 | 72362952.52 | 43320.25 | 0.00 | 0.606360E+10 | 0.00 | 0.54 |
September | 0.172554E+10 | 0.117569E+09 | 0.00 | 0.101099E+09 | 0.00 | 0.00 | 0.929939E+10 | 0.00 | 0.53 |
October | 0.846114E+10 | 0.00 | 0.00 | 97314309.03 | 0.00 | 0.154840E+10 | 0.953826E+10 | 0.00 | 0.54 |
November | 0.996349E+10 | 0.00 | 0.00 | 0.127767E+09 | 0.00 | 0.112874E+10 | 0.873432E+10 | 0.00 | 0.54 |
December | 0.131512E+11 | 0.00 | 0.00 | 80278739.10 | 0.00 | 0.320429E+10 | 0.543321E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.893877E+11 | 0.331077E+10 | 0.00 | 0.948061E+09 | 43320.25 | 0.130267E+11 | 0.830465E+11 | 0.00 | 0.54 |
Minimum of Months | 0.688432E+09 | 0.00 | 0.00 | 16619455.06 | 0.00 | 0.00 | 0.304417E+10 | 0.00 | 0.53 |
Maximum of Months | 0.141103E+11 | 0.142472E+10 | 0.00 | 0.139656E+09 | 43320.25 | 0.320429E+10 | 0.953826E+10 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.555198E+10 | 0.00 | 0.00 | 8944911.21 | 0.00 | 0.120557E+11 | 0.366726E+10 | 0.00 | 0.54 |
February | 0.514370E+10 | 0.00 | 0.00 | 7567301.69 | 0.00 | 0.111136E+11 | 0.290016E+10 | 0.00 | 0.54 |
March | 0.529690E+10 | 0.00 | 0.00 | 25417223.95 | 0.00 | 0.701799E+10 | 0.733698E+10 | 0.00 | 0.54 |
April | 0.493724E+10 | 0.00 | 0.00 | 36937302.94 | 0.00 | 0.419367E+10 | 0.915721E+10 | 0.00 | 0.54 |
May | 0.387460E+10 | 10904926.51 | 0.00 | 86143516.14 | 3325699.66 | 0.129190E+09 | 0.124591E+11 | 0.00 | 0.53 |
June | 0.527739E+09 | 0.556377E+09 | 746518.39 | 75376898.44 | 0.186809E+09 | 2874596.06 | 0.620323E+10 | 57092.09 | 0.53 |
July | 0.329847E+09 | 0.105175E+10 | 394442.59 | 66205946.26 | 0.372927E+09 | 2109712.30 | 0.481174E+10 | 44304.91 | 0.53 |
August | 0.983547E+09 | 0.847814E+09 | 108943.06 | 69171266.51 | 0.162817E+09 | 4691100.89 | 0.576885E+10 | 43962.71 | 0.53 |
September | 0.164624E+10 | 84600088.97 | 417916.76 | 70812913.07 | 32485670.69 | 0.120148E+09 | 0.929188E+10 | 97267.16 | 0.53 |
October | 0.527092E+10 | 0.00 | 0.00 | 36414312.97 | 0.00 | 0.369146E+10 | 0.106517E+11 | 0.00 | 0.53 |
November | 0.539535E+10 | 0.00 | 0.00 | 12828874.41 | 0.00 | 0.946991E+10 | 0.508169E+10 | 0.00 | 0.54 |
December | 0.493543E+10 | 0.00 | 0.00 | 6059177.32 | 0.00 | 0.141621E+11 | 0.277136E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.438935E+11 | 0.255144E+10 | 1667820.80 | 0.501880E+09 | 0.758364E+09 | 0.619634E+11 | 0.801011E+11 | 242626.88 | 0.53 |
Minimum of Months | 0.329847E+09 | 0.00 | 0.00 | 6059177.32 | 0.00 | 2109712.30 | 0.277136E+10 | 0.00 | 0.53 |
Maximum of Months | 0.555198E+10 | 0.105175E+10 | 746518.39 | 86143516.14 | 0.372927E+09 | 0.141621E+11 | 0.124591E+11 | 97267.16 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.283169E+09 | 0.00 | 0.00 | 5605127.18 | 0.00 | 0.892490E+09 | 0.388021E+09 | 0.00 | 0.47 |
February | 0.204580E+09 | 0.00 | 0.00 | 7532595.04 | 0.00 | 0.781690E+09 | 0.419252E+09 | 0.00 | 0.47 |
March | 0.196558E+09 | 0.00 | 0.00 | 9135581.84 | 0.00 | 0.638657E+09 | 0.606476E+09 | 0.00 | 0.47 |
April | 0.209405E+09 | 0.00 | 0.00 | 7299308.65 | 0.00 | 0.588632E+09 | 0.545788E+09 | 0.00 | 0.47 |
May | 0.109932E+09 | 1014912.89 | 0.00 | 12484666.70 | 34325.82 | 92771960.71 | 0.100499E+10 | 0.00 | 0.47 |
June | 6403355.16 | 52995608.67 | 12178.82 | 12975560.70 | 1846863.77 | 70642.97 | 0.482601E+09 | 471.94 | 0.47 |
July | 5951475.17 | 0.102092E+09 | 41534.97 | 10348642.72 | 2940413.90 | 82306.43 | 0.367749E+09 | 1134.49 | 0.47 |
August | 13003772.12 | 73596681.91 | 0.00 | 14281783.14 | 929467.03 | 212987.81 | 0.475809E+09 | 0.00 | 0.47 |
September | 42434982.91 | 8443654.04 | 0.00 | 15085162.79 | 227184.55 | 39744194.52 | 0.723294E+09 | 0.00 | 0.47 |
October | 0.139490E+09 | 0.00 | 0.00 | 10899952.92 | 0.00 | 0.498936E+09 | 0.799525E+09 | 0.00 | 0.47 |
November | 0.231945E+09 | 0.00 | 0.00 | 7123309.74 | 0.00 | 0.716205E+09 | 0.516381E+09 | 0.00 | 0.47 |
December | 0.269122E+09 | 0.00 | 0.00 | 4131928.68 | 0.00 | 0.106703E+10 | 0.272579E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.171199E+10 | 0.238143E+09 | 53713.79 | 0.116904E+09 | 5978255.08 | 0.531652E+10 | 0.660246E+10 | 1606.44 | 0.47 |
Minimum of Months | 5951475.17 | 0.00 | 0.00 | 4131928.68 | 0.00 | 70642.97 | 0.272579E+09 | 0.00 | 0.47 |
Maximum of Months | 0.283169E+09 | 0.102092E+09 | 41534.97 | 15085162.79 | 2940413.90 | 0.106703E+10 | 0.100499E+10 | 1134.49 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.361532E+09 | 0.00 | 0.00 | 1175692.48 | 0.00 | 0.109021E+10 | 0.116184E+09 | 0.00 | 0.47 |
February | 0.275891E+09 | 0.00 | 0.00 | 2527751.96 | 0.00 | 0.967073E+09 | 0.167397E+09 | 0.00 | 0.47 |
March | 0.279301E+09 | 0.00 | 0.00 | 4821105.24 | 0.00 | 0.729867E+09 | 0.436668E+09 | 0.00 | 0.47 |
April | 0.257358E+09 | 0.00 | 0.00 | 5283250.03 | 0.00 | 0.652044E+09 | 0.436282E+09 | 0.00 | 0.47 |
May | 0.146460E+09 | 1014793.98 | 0.00 | 11276742.49 | 34321.80 | 0.111483E+09 | 0.950815E+09 | 0.00 | 0.47 |
June | 6501025.13 | 52919226.62 | 12299.79 | 12731996.65 | 1916820.23 | 80265.29 | 0.482679E+09 | 349.48 | 0.47 |
July | 6209913.71 | 0.101842E+09 | 41041.73 | 10138303.31 | 3178060.29 | 69350.67 | 0.367669E+09 | 1622.74 | 0.47 |
August | 14319482.91 | 73387040.57 | 23350.10 | 12784788.29 | 1105958.43 | 212962.86 | 0.475931E+09 | 1068.01 | 0.47 |
September | 53432211.50 | 8336707.12 | 28241.88 | 11752828.28 | 304645.84 | 47727321.22 | 0.707549E+09 | 227.83 | 0.47 |
October | 0.287753E+09 | 0.00 | 0.00 | 5274849.21 | 0.00 | 0.645052E+09 | 0.510600E+09 | 0.00 | 0.47 |
November | 0.337687E+09 | 0.00 | 0.00 | 1931148.92 | 0.00 | 0.944197E+09 | 0.187667E+09 | 0.00 | 0.47 |
December | 0.281975E+09 | 0.00 | 0.00 | 769394.64 | 0.00 | 0.125970E+10 | 70231754.33 | 0.00 | 0.47 |
Annual Sum or Average | 0.230842E+10 | 0.237500E+09 | 104933.50 | 80467851.50 | 6539806.59 | 0.644771E+10 | 0.490967E+10 | 3268.06 | 0.47 |
Minimum of Months | 6209913.71 | 0.00 | 0.00 | 769394.64 | 0.00 | 69350.67 | 70231754.33 | 0.00 | 0.47 |
Maximum of Months | 0.361532E+09 | 0.101842E+09 | 41041.73 | 12784788.29 | 3178060.29 | 0.125970E+10 | 0.950815E+09 | 1622.74 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.230635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454480E+09 | 0.00 | 0.00 | 0.44 |
February | 0.193703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172448E+10 | 0.00 | 0.00 | 0.44 |
March | 0.213383E+11 | 0.00 | 0.00 | 1627891.88 | 0.00 | 19413630.58 | 0.134372E+10 | 0.00 | 0.46 |
April | 0.214897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64567118.05 | 0.00 | 0.00 | 0.46 |
May | 0.186760E+11 | 90381.66 | 0.00 | 965893.84 | 711544.52 | 0.00 | 0.104071E+10 | 0.00 | 0.49 |
June | 0.130616E+10 | 0.238345E+09 | 0.00 | 29713747.35 | 334818.96 | 0.00 | 0.107280E+11 | 0.00 | 0.58 |
July | 0.634515E+09 | 0.276120E+09 | 0.00 | 32691033.14 | 3622852.48 | 0.00 | 0.102964E+11 | 0.00 | 0.58 |
August | 0.797495E+09 | 0.163931E+09 | 0.00 | 32984981.74 | 73814.56 | 0.00 | 0.117968E+11 | 0.00 | 0.58 |
September | 0.466137E+10 | 22575713.58 | 0.00 | 25761473.12 | 0.00 | 0.00 | 0.105462E+11 | 0.00 | 0.56 |
October | 0.186734E+11 | 0.00 | 0.00 | 3196015.28 | 0.00 | 0.662539E+09 | 0.309054E+10 | 0.00 | 0.46 |
November | 0.219827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325533E+09 | 0.00 | 0.00 | 0.44 |
December | 0.206073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340923E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.172601E+12 | 0.701062E+09 | 0.00 | 0.126941E+09 | 4743030.52 | 0.666024E+10 | 0.488423E+11 | 0.00 | 0.49 |
Minimum of Months | 0.634515E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.230635E+11 | 0.276120E+09 | 0.00 | 32984981.74 | 3622852.48 | 0.340923E+10 | 0.117968E+11 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 70241982.89 | 0.00 | 0.00 | 1197637.20 | 0.00 | 0.251344E+09 | 69537511.70 | 0.00 | 0.47 |
February | 54491665.12 | 0.00 | 0.00 | 1405346.90 | 0.00 | 0.226698E+09 | 70668452.02 | 0.00 | 0.47 |
March | 53099867.29 | 0.00 | 0.00 | 1793548.22 | 0.00 | 0.194694E+09 | 0.113120E+09 | 0.00 | 0.47 |
April | 55219694.22 | 0.00 | 0.00 | 1262020.11 | 0.00 | 0.187482E+09 | 93817064.02 | 0.00 | 0.47 |
May | 45214862.35 | 260670.30 | 0.00 | 2296521.98 | 1639.38 | 68103244.06 | 0.189430E+09 | 0.00 | 0.47 |
June | 6703761.13 | 13056241.32 | 479.34 | 2301334.50 | 656613.55 | 298319.87 | 0.116209E+09 | 446.59 | 0.47 |
July | 4074023.22 | 25096502.76 | 4527.66 | 1799179.91 | 1165776.61 | 183092.18 | 89976545.38 | 1940.84 | 0.47 |
August | 9811161.94 | 18301461.58 | 5533.01 | 2502583.00 | 324299.86 | 822320.42 | 0.112691E+09 | 242.78 | 0.47 |
September | 18520901.52 | 2111742.64 | 0.00 | 2868093.38 | 55675.35 | 19632572.45 | 0.164118E+09 | 291.65 | 0.47 |
October | 45397804.83 | 0.00 | 0.00 | 2109403.89 | 0.00 | 0.168860E+09 | 0.145846E+09 | 0.00 | 0.47 |
November | 57620578.45 | 0.00 | 0.00 | 1365238.89 | 0.00 | 0.216917E+09 | 92010821.58 | 0.00 | 0.47 |
December | 60092324.26 | 0.00 | 0.00 | 676764.54 | 0.00 | 0.293705E+09 | 48741109.45 | 0.00 | 0.47 |
Annual Sum or Average | 0.480489E+09 | 58826618.60 | 10540.01 | 21577672.53 | 2204004.75 | 0.162874E+10 | 0.130616E+10 | 2921.87 | 0.47 |
Minimum of Months | 4074023.22 | 0.00 | 0.00 | 676764.54 | 0.00 | 183092.18 | 48741109.45 | 0.00 | 0.47 |
Maximum of Months | 70241982.89 | 25096502.76 | 5533.01 | 2868093.38 | 1165776.61 | 0.293705E+09 | 0.189430E+09 | 1940.84 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 71023860.46 | 0.00 | 0.00 | 211478.92 | 0.00 | 0.307716E+09 | 13323500.68 | 0.00 | 0.47 |
February | 61030906.07 | 0.00 | 0.00 | 346397.53 | 0.00 | 0.271842E+09 | 20002691.02 | 0.00 | 0.47 |
March | 66967894.30 | 0.00 | 0.00 | 915310.14 | 0.00 | 0.226740E+09 | 68041197.06 | 0.00 | 0.47 |
April | 65021488.82 | 0.00 | 0.00 | 848146.80 | 0.00 | 0.205244E+09 | 66627636.57 | 0.00 | 0.47 |
May | 52730183.01 | 260639.76 | 0.00 | 2031442.87 | 1639.19 | 74493848.11 | 0.175753E+09 | 0.00 | 0.47 |
June | 6964871.85 | 12975310.63 | 460.84 | 2240373.84 | 735937.57 | 224145.32 | 0.116069E+09 | 464.99 | 0.47 |
July | 4172862.11 | 24867960.14 | 4456.79 | 1743046.33 | 1391242.22 | 134360.72 | 89971319.87 | 2010.96 | 0.47 |
August | 10838635.59 | 18192083.35 | 7672.20 | 2154989.82 | 429108.78 | 1622108.55 | 0.111196E+09 | 489.95 | 0.47 |
September | 22323957.41 | 2088035.77 | 0.00 | 2125354.23 | 79128.28 | 25682420.40 | 0.154984E+09 | 291.62 | 0.47 |
October | 72347470.94 | 0.00 | 0.00 | 1042472.71 | 0.00 | 0.210935E+09 | 77845234.91 | 0.00 | 0.47 |
November | 72617916.18 | 0.00 | 0.00 | 333305.12 | 0.00 | 0.269171E+09 | 25747959.74 | 0.00 | 0.47 |
December | 53036733.08 | 0.00 | 0.00 | 124624.49 | 0.00 | 0.342296E+09 | 7710987.89 | 0.00 | 0.47 |
Annual Sum or Average | 0.559077E+09 | 58384029.65 | 12589.82 | 14116942.79 | 2637056.04 | 0.193610E+10 | 0.927272E+09 | 3257.51 | 0.47 |
Minimum of Months | 4172862.11 | 0.00 | 0.00 | 124624.49 | 0.00 | 134360.72 | 7710987.89 | 0.00 | 0.47 |
Maximum of Months | 72617916.18 | 24867960.14 | 7672.20 | 2240373.84 | 1391242.22 | 0.342296E+09 | 0.175753E+09 | 2010.96 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.259593E+09 | 0.00 | 0.00 | 32473254.57 | 0.00 | 0.947723E+09 | 0.128067E+10 | 0.00 | 0.54 |
February | 0.199231E+09 | 0.00 | 0.00 | 26742347.47 | 0.00 | 0.982381E+09 | 0.106118E+10 | 0.00 | 0.54 |
March | 0.256286E+09 | 0.00 | 0.00 | 19265951.08 | 0.00 | 0.879636E+09 | 0.117502E+10 | 0.00 | 0.54 |
April | 0.358821E+09 | 0.00 | 0.00 | 8756204.19 | 0.00 | 0.883340E+09 | 0.919155E+09 | 0.00 | 0.54 |
May | 0.261570E+09 | 1622077.69 | 0.00 | 12708174.38 | 63128.04 | 0.210404E+09 | 0.147507E+10 | 0.00 | 0.53 |
June | 43788452.63 | 82644659.00 | 33764.58 | 11706485.00 | 5418506.43 | 2265971.22 | 0.748594E+09 | 7108.59 | 0.53 |
July | 27386528.20 | 0.159802E+09 | 116857.28 | 10031303.32 | 8825829.86 | 398093.32 | 0.579146E+09 | 18111.70 | 0.53 |
August | 60528546.33 | 0.117307E+09 | 14429.66 | 15051855.20 | 2373559.34 | 1024439.19 | 0.731768E+09 | 3251.24 | 0.53 |
September | 99116242.11 | 13570015.67 | 1737.27 | 20779885.36 | 353564.54 | 55643669.05 | 0.114238E+10 | 1110.05 | 0.53 |
October | 0.224383E+09 | 0.00 | 0.00 | 22755785.10 | 0.00 | 0.621200E+09 | 0.145869E+10 | 0.00 | 0.53 |
November | 0.233240E+09 | 0.00 | 0.00 | 32774043.23 | 0.00 | 0.749943E+09 | 0.134770E+10 | 0.00 | 0.54 |
December | 0.333271E+09 | 0.00 | 0.00 | 23686091.62 | 0.00 | 0.127712E+10 | 0.956378E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.235722E+10 | 0.374946E+09 | 166788.79 | 0.236731E+09 | 17034588.21 | 0.661108E+10 | 0.128758E+11 | 29581.58 | 0.54 |
Minimum of Months | 27386528.20 | 0.00 | 0.00 | 8756204.19 | 0.00 | 398093.32 | 0.579146E+09 | 0.00 | 0.53 |
Maximum of Months | 0.358821E+09 | 0.159802E+09 | 116857.28 | 32774043.23 | 8825829.86 | 0.127712E+10 | 0.147507E+10 | 18111.70 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.199318E+11 | 0.00 | 0.00 | 41919638.35 | 0.00 | 0.00 | 0.397613E+11 | 0.00 | 5.28 |
February | 0.176557E+11 | 0.00 | 0.00 | 33502132.80 | 0.00 | 0.00 | 0.356435E+11 | 0.00 | 5.26 |
March | 0.136953E+11 | 0.00 | 0.00 | 55116836.73 | 0.00 | 0.00 | 0.442223E+11 | 0.00 | 5.49 |
April | 0.104769E+11 | 0.00 | 0.00 | 60520571.82 | 0.00 | 0.00 | 0.450655E+11 | 0.00 | 5.56 |
May | 0.212391E+10 | 2007174.39 | 0.00 | 72520358.39 | 0.00 | 0.00 | 0.495757E+11 | 0.00 | 5.99 |
June | 0.225974E+09 | 0.432910E+09 | 0.00 | 67975156.52 | 1332749.51 | 0.00 | 0.297703E+11 | 0.00 | 6.29 |
July | 0.144785E+09 | 0.549099E+09 | 0.00 | 68722768.13 | 2889056.65 | 0.00 | 0.267662E+11 | 0.00 | 6.24 |
August | 0.340723E+09 | 0.290336E+09 | 0.00 | 67004162.63 | 722489.43 | 0.00 | 0.306878E+11 | 0.00 | 6.27 |
September | 0.108713E+10 | 40032450.73 | 0.00 | 61048015.26 | 347185.65 | 0.00 | 0.364977E+11 | 0.00 | 6.13 |
October | 0.982424E+10 | 0.00 | 0.00 | 61270729.36 | 0.00 | 0.00 | 0.475815E+11 | 0.00 | 5.45 |
November | 0.161649E+11 | 0.00 | 0.00 | 43313787.77 | 0.00 | 0.00 | 0.404043E+11 | 0.00 | 5.20 |
December | 0.243454E+11 | 0.00 | 0.00 | 34444769.31 | 0.00 | 0.00 | 0.362673E+11 | 0.00 | 5.21 |
Annual Sum or Average | 0.116017E+12 | 0.131438E+10 | 0.00 | 0.667359E+09 | 5291481.23 | 0.00 | 0.462243E+12 | 0.00 | 5.70 |
Minimum of Months | 0.144785E+09 | 0.00 | 0.00 | 33502132.80 | 0.00 | 0.00 | 0.267662E+11 | 0.00 | 5.20 |
Maximum of Months | 0.243454E+11 | 0.549099E+09 | 0.00 | 72520358.39 | 2889056.65 | 0.00 | 0.495757E+11 | 0.00 | 6.29 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124378E+11 | 0.00 | 0.00 | 61801629.32 | 0.00 | 0.00 | 0.478470E+11 | 0.00 | 5.33 |
February | 0.117160E+11 | 0.00 | 0.00 | 49366490.49 | 0.00 | 0.00 | 0.420688E+11 | 0.00 | 5.31 |
March | 0.769211E+10 | 0.00 | 0.00 | 78967201.65 | 0.00 | 0.00 | 0.513341E+11 | 0.00 | 5.58 |
April | 0.539723E+10 | 0.00 | 0.00 | 85167413.27 | 0.00 | 0.00 | 0.514061E+11 | 0.00 | 5.67 |
May | 0.916125E+09 | 2005525.87 | 0.00 | 91647214.49 | 0.00 | 0.00 | 0.525614E+11 | 0.00 | 6.16 |
June | 58847483.90 | 0.440105E+09 | 0.00 | 80177536.71 | 877084.80 | 0.00 | 0.313204E+11 | 0.00 | 6.52 |
July | 30817978.92 | 0.553665E+09 | 0.00 | 80405980.39 | 1378328.98 | 0.00 | 0.281251E+11 | 0.00 | 6.47 |
August | 0.149737E+09 | 0.293389E+09 | 0.00 | 80024813.36 | 721896.04 | 0.00 | 0.322026E+11 | 0.00 | 6.49 |
September | 0.598191E+09 | 40350741.60 | 0.00 | 75446226.54 | 0.00 | 0.00 | 0.384505E+11 | 0.00 | 6.32 |
October | 0.590329E+10 | 0.00 | 0.00 | 83168918.21 | 0.00 | 0.00 | 0.525398E+11 | 0.00 | 5.53 |
November | 0.970653E+10 | 0.00 | 0.00 | 67078313.82 | 0.00 | 0.00 | 0.475366E+11 | 0.00 | 5.26 |
December | 0.184640E+11 | 0.00 | 0.00 | 53521549.02 | 0.00 | 0.00 | 0.426620E+11 | 0.00 | 5.25 |
Annual Sum or Average | 0.730707E+11 | 0.132951E+10 | 0.00 | 0.886773E+09 | 2977309.82 | 0.00 | 0.518054E+12 | 0.00 | 5.83 |
Minimum of Months | 30817978.92 | 0.00 | 0.00 | 49366490.49 | 0.00 | 0.00 | 0.281251E+11 | 0.00 | 5.25 |
Maximum of Months | 0.184640E+11 | 0.553665E+09 | 0.00 | 91647214.49 | 1378328.98 | 0.00 | 0.525614E+11 | 0.00 | 6.52 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2010522.49 | 0.00 | 0.00 | 0.216341E+09 | 0.00 | 0.00 | 0.689046E+11 | 0.00 | 19.68 |
February | 867083.90 | 0.00 | 0.00 | 0.186953E+09 | 0.00 | 0.00 | 0.617573E+11 | 0.00 | 19.55 |
March | 666250.97 | 0.00 | 0.00 | 0.208063E+09 | 0.00 | 0.00 | 0.677557E+11 | 0.00 | 21.11 |
April | 6193209.42 | 0.00 | 0.00 | 0.188637E+09 | 0.00 | 0.00 | 0.648160E+11 | 0.00 | 21.51 |
May | 2547010.98 | 3106021.66 | 0.00 | 0.146349E+09 | 0.00 | 0.00 | 0.594675E+11 | 0.00 | 24.10 |
June | 0.00 | 0.671675E+09 | 0.00 | 0.115195E+09 | 0.00 | 0.00 | 0.303052E+11 | 0.00 | 24.44 |
July | 0.00 | 0.855292E+09 | 0.00 | 0.113156E+09 | 0.00 | 0.00 | 0.266491E+11 | 0.00 | 24.20 |
August | 0.00 | 0.450698E+09 | 0.00 | 0.123291E+09 | 0.00 | 0.00 | 0.328134E+11 | 0.00 | 24.52 |
September | 0.00 | 60787590.11 | 0.00 | 0.130334E+09 | 0.00 | 0.00 | 0.412629E+11 | 0.00 | 24.36 |
October | 2796075.67 | 0.00 | 0.00 | 0.187068E+09 | 0.00 | 0.00 | 0.668568E+11 | 0.00 | 21.15 |
November | 665033.99 | 0.00 | 0.00 | 0.228344E+09 | 0.00 | 0.00 | 0.658684E+11 | 0.00 | 19.59 |
December | 2076818.86 | 0.00 | 0.00 | 0.205259E+09 | 0.00 | 0.00 | 0.682536E+11 | 0.00 | 19.02 |
Annual Sum or Average | 17822006.29 | 0.204156E+10 | 0.00 | 0.204899E+10 | 0.00 | 0.00 | 0.654711E+12 | 0.00 | 21.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.113156E+09 | 0.00 | 0.00 | 0.266491E+11 | 0.00 | 19.02 |
Maximum of Months | 6193209.42 | 0.855292E+09 | 0.00 | 0.228344E+09 | 0.00 | 0.00 | 0.689046E+11 | 0.00 | 24.52 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.821564E+10 | 0.00 | 0.00 | 51028.63 | 0.00 | 0.123886E+10 | 0.106131E+09 | 0.00 | 0.68 |
February | 0.628740E+10 | 0.00 | 0.00 | 69754.68 | 0.00 | 0.216474E+10 | 0.123370E+09 | 0.00 | 0.68 |
March | 0.753457E+10 | 0.00 | 0.00 | 2079382.13 | 0.00 | 0.706412E+09 | 0.110101E+10 | 0.00 | 0.73 |
April | 0.802222E+10 | 0.00 | 0.00 | 260932.87 | 0.00 | 0.485761E+09 | 0.263469E+09 | 0.00 | 0.71 |
May | 0.500755E+10 | 635767.25 | 0.00 | 6645765.25 | 0.00 | 0.00 | 0.322404E+10 | 0.00 | 0.81 |
June | 0.246686E+09 | 0.161332E+09 | 0.00 | 18905007.07 | 0.00 | 0.00 | 0.510230E+10 | 0.00 | 1.13 |
July | 0.123928E+09 | 0.186623E+09 | 0.00 | 18979682.57 | 0.00 | 0.00 | 0.470247E+10 | 0.00 | 1.12 |
August | 0.248965E+09 | 0.110703E+09 | 0.00 | 19950186.47 | 0.00 | 0.00 | 0.535049E+10 | 0.00 | 1.12 |
September | 0.179758E+10 | 14516303.06 | 0.00 | 15134137.53 | 0.00 | 0.00 | 0.469694E+10 | 0.00 | 1.00 |
October | 0.647500E+10 | 0.00 | 0.00 | 3937316.30 | 0.00 | 0.731334E+09 | 0.211538E+10 | 0.00 | 0.74 |
November | 0.796763E+10 | 0.00 | 0.00 | 557322.18 | 0.00 | 0.820236E+09 | 0.298810E+09 | 0.00 | 0.67 |
December | 0.698177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278156E+10 | 0.00 | 0.00 | 0.67 |
Annual Sum or Average | 0.589089E+11 | 0.473810E+09 | 0.00 | 86570515.69 | 0.00 | 0.892890E+10 | 0.270844E+11 | 0.00 | 0.84 |
Minimum of Months | 0.123928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
Maximum of Months | 0.821564E+10 | 0.186623E+09 | 0.00 | 19950186.47 | 0.00 | 0.278156E+10 | 0.535049E+10 | 0.00 | 1.13 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:59:38
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.233745E+12 | 0.175376E+11 | 0.205081E+12 | 0.919551E+12 | 0.128283E+12 |
February | 0.319217E+12 | 0.166363E+11 | 0.193022E+12 | 0.864238E+12 | 0.108556E+12 |
March | 0.424756E+12 | 0.146116E+11 | 0.169882E+12 | 0.784765E+12 | 0.140264E+12 |
April | 0.475701E+12 | 0.132304E+11 | 0.154184E+12 | 0.712218E+12 | 0.111658E+12 |
May | 0.532998E+12 | 0.852930E+10 | 0.896182E+11 | 0.488429E+12 | 0.257013E+12 |
June | 0.575559E+12 | 0.313093E+10 | 0.301596E+11 | 0.221740E+12 | 0.658363E+12 |
July | 0.549660E+12 | 0.259324E+10 | 0.260391E+11 | 0.190904E+12 | 0.731940E+12 |
August | 0.512314E+12 | 0.341481E+10 | 0.359145E+11 | 0.239627E+12 | 0.673269E+12 |
September | 0.384812E+12 | 0.554551E+10 | 0.551205E+11 | 0.343617E+12 | 0.497647E+12 |
October | 0.317815E+12 | 0.131109E+11 | 0.148899E+12 | 0.714228E+12 | 0.183145E+12 |
November | 0.251882E+12 | 0.154563E+11 | 0.180973E+12 | 0.818004E+12 | 0.134628E+12 |
December | 0.202675E+12 | 0.188777E+11 | 0.218909E+12 | 0.968703E+12 | 0.124455E+12 |
Annual Sum or Average | 0.478113E+13 | 0.132675E+12 | 0.150780E+13 | 0.726602E+13 | 0.374922E+13 |
Minimum of Months | 0.202675E+12 | 0.259324E+10 | 0.260391E+11 | 0.190904E+12 | 0.108556E+12 |
Maximum of Months | 0.575559E+12 | 0.188777E+11 | 0.218909E+12 | 0.968703E+12 | 0.731940E+12 |