Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:59

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930

Simulation Timestamp: 2023-10-16 09:01:04


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 10487.12 924.36 924.36
Net Site Energy 10487.12 924.36 924.36
Total Source Energy 21458.26 1891.38 1891.38
Net Source Energy 21458.26 1891.38 1891.38


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 698.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 425.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 766.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 242.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1745.01 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 651.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 543.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 122.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 194.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.74 3155.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 62.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 4844.08 5643.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 698.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 425.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 766.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 242.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 959.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 14.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 8.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 32.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 543.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 122.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 194.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.74 3155.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 20.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 34.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 698.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 425.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 766.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 242.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1745.01 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 651.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 543.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 122.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 194.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 90.74 3155.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 62.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 88.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 104.23 339.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 233.81 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 426.97 497.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 88.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 104.23 339.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 233.81 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 426.97 497.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 4844.084 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 4844.084 100.00
     
Total On-Site and Utility Electric Sources 4844.084 100.00
Total Electricity End Uses 4844.084 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 18.04 0.77
Air to Air Heat Recovery for Heating 2317.58 99.23
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 2335.62 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 474.33
Time Not Comfortable Based on Simple ASHRAE 55-2004 7332.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:59
RunPeriod RUNPERIOD 1
Weather File Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Latitude [deg] 47.47
Longitude [deg] -122.3
Elevation [m] 122.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 9.1389 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 13.3365 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 13.3365 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 9.2031 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 6.1031 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.8125 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 10.3656 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 8.7188 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 4.5531 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 4.5531 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 6.3938 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 4.5531 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.3656 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.3656 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 11.7219 4.65 2934.4875
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 6.3938 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 6.8557 7.07 41.0709
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 6.8557 7.07 41.0709
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 9.1389 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 13.3365 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 13.3365 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 9.2031 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 6.1031 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.8125 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 10.3656 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 8.7188 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 4.5531 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 4.5531 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 4.5531 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 4.5531 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 4.5531 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 4.5531 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 6.3938 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 4.5531 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 4.5531 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 4.5531 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 10.3656 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 10.3656 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 11.7219 4.65 2934.4875  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 6.3938 18.58 0.0000  
Total 11345.29             6.8557 3.54 41.0709  
Conditioned Total 11345.29             6.8557 3.54 41.0709  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 4.4542 8.82 37.1989
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 10-AUG-19:30 22-JAN-18:49 - - - - - - - - - - 03-JAN-21:30
Heating 0.00 186463.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 117286.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 88772.42 100066.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 32159.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 29138.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 8118.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 3897.07 244830.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 2396.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 370048.64 531360.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 186463.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 117286.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 58789.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 25090.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1855.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 30153.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 150.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 29138.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 8118.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 3897.07 244830.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 241.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 1061.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 1093.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 757.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1347.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2428.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 767.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5526.46 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2063.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1720.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 388.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 614.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 287.39 3420.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 196.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 15341.21 6117.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 66.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 118.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 214.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 67.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 487.11 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 151.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 34.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 54.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 301.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1352.21 539.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 66.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 118.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 214.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 67.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 487.11 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 151.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 34.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 54.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 301.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1352.21 539.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.59 0.582734 0.509000 1.32 1.00 0.500000 0.000654 0.000060 1.32 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.478973 0.106704 0.509000 0.243797 0.509000 0.500000 0.003571 0.000031 0.243797 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.241620 0.244946 0.509000 0.122984 0.653188 0.500000 0.001555 0.000012 0.122984 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.219990 0.568906 0.509000 0.111975 1.00 0.500000 0.000670 0.000018 0.111975 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.105999 0.681199 0.509000 0.053954 1.00 0.500000 0.000559 0.000010 0.053954 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.30 0.071537 0.509000 1.68 0.509000 0.500000 0.021134 0.000093 1.68 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.85 0.077922 0.509000 0.940067 0.509000 0.500000 0.004890 0.000094 0.940067 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 5.09 0.195979 0.509000 2.59 0.522611 0.500000 0.001944 0.000237 2.59 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.57 0.753754 0.509000 0.801502 1.00 0.500000 0.000505 0.000110 0.801502 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.13 0.118419 0.509000 1.09 0.509000 0.500000 0.003217 0.000095 1.09 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.24 0.113042 0.509000 1.14 0.509000 0.500000 0.003370 0.000098 1.14 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.29 0.061899 0.509000 1.16 0.509000 0.500000 0.011071 0.000066 1.16 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.810785 0.387327 0.509000 0.412690 1.00 0.500000 0.000984 0.000066 0.412690 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 6854.95 0.000060 142.95
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 3585.89 0.000031 82.68
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1408.91 0.000012 31.34
MECH_FLR_1 VAV BOX REHEAT COIL 2014.09 0.000018 48.23
STORAGE_FLR_1 VAV BOX REHEAT COIL 1159.54 0.000010 28.97
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 10616.37 0.000093 223.88
CAFE_FLR_1 VAV BOX REHEAT COIL 10711.65 0.000094 238.14
LOBBY_FLR_1 VAV BOX REHEAT COIL 27139.73 0.000237 597.49
ROOM_1_FLR_3 FAN COIL HEATING COIL 5287.97 0.000046 151.12
ROOM_2_FLR_3 FAN COIL HEATING COIL 5291.52 0.000046 151.22
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 30397.66 0.000266 868.67
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 30479.30 0.000267 871.00
ROOM_5_FLR_3 FAN COIL HEATING COIL 5295.72 0.000046 151.34
ROOM_6_FLR_3 FAN COIL HEATING COIL 5299.27 0.000046 151.44
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 12534.72 0.000110 292.10
ROOM_1_FLR_6 FAN COIL HEATING COIL 1612.10 0.000014 46.07
ROOM_2_FLR_6 FAN COIL HEATING COIL 1613.93 0.000014 46.12
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 7727.53 0.000068 220.82
BANQUET_FLR_6 VAV BOX REHEAT COIL 10868.62 0.000095 238.09
DINING_FLR_6 VAV BOX REHEAT COIL 11250.60 0.000098 246.15
KITCHEN_FLR_6 VAV BOX REHEAT COIL 7546.41 0.000066 159.40
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 7589.30 0.000066 182.60
VAV WITH REHEAT HEATING COIL 170401.39 0.001491 2909.13
FLR_3_DOAS HEATING COIL 15340.96 0.000134 261.90
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ZoneExhaust

User-Specified Maximum Flow Rate [m3/s]
LOBBY_FLR_1 EXHAUST FAN 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 1.22 0.000046 0.000477
ROOM_2_FLR_3 FAN COIL 1.09 0.000046 0.000430
ROOM_3_MULT19_FLR_3 FAN COIL 8.15 0.000266 0.003139
ROOM_4_MULT19_FLR_3 FAN COIL 5.05 0.000267 0.002098
ROOM_5_FLR_3 FAN COIL 1.09 0.000046 0.000427
ROOM_6_FLR_3 FAN COIL 0.985723 0.000046 0.000388
ROOM_1_FLR_6 FAN COIL 0.317627 0.000014 0.000124
ROOM_2_FLR_6 FAN COIL 0.283286 0.000014 0.000111
ROOM_3_MULT9_FLR_6 FAN COIL 1.72 0.000068 0.000680
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 1.22
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 1.09
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 8.15
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 5.05
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 1.09
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 0.985723
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.317627
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.283286
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.72
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008566 12.80 0.008500 0.000477 1.22  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008573 12.80 0.008500 0.000430 1.09  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008504 12.80 0.008500 0.003139 8.15  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008784 12.80 0.008500 0.002098 5.05  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008574 12.80 0.008500 0.000427 1.09  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008581 12.80 0.008500 0.000388 0.985723  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008563 12.80 0.008500 0.000124 0.317627  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008571 12.80 0.008500 0.000111 0.283286  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008602 12.80 0.008500 0.000680 1.72  
VAV WITH REHEAT COOLING COIL 26.76 6.70 0.009204 10.95 0.008500 0.017321 22.79 484932.30
FLR_3_DOAS COOLING COIL 29.40 6.70 0.008822 11.92 0.008500 0.001623 2.05 45447.84
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 11.66 11.66 22.91 11.66 22.79 22.79 0.300000 0.511759 22.79
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 22.79 11.66
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 11.66
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 22.79
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.017321 0.000027
VAV WITH REHEAT_HEATC_CONTROLLER 0.001491  
FLR_3_DOAS_COOLC_CONTROLLER 0.001623 0.000293
FLR_3_DOAS_HEATC_CONTROLLER 0.000134  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.026817 5526.09  
HEATSYS1 PUMP 0.003430 1032.85 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.003430 0.411556
COOLSYS1 0.026817 3.22
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 392028.15 392028.15 0.003430
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.026817 3825.90
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.026817 750817.87 751446.35 85.66
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 11.40 8.10 5.40 4.50 5.80 8.30 10.90 13.00 15.60 17.70 18.80 15.10


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 47.47 -122.32 -8.00 122.00 99868 1.1870


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 11.22 14.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 9.139 5.380 0.000 0.000 0.000 0.000 14.519 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 13.336 10.760 0.000 0.000 0.000 0.000 24.096 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 13.336 10.760 0.000 0.000 0.000 0.000 24.096 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 9.203 5.380 0.000 0.000 0.000 0.000 14.583 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 6.103 2.690 0.000 0.000 0.000 0.000 8.793 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.813 61.680 535.850 0.000 0.000 0.000 603.343 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 10.366 5.380 0.000 0.000 0.000 0.000 15.746 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 8.719 8.070 0.000 0.000 0.000 0.000 16.789 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 6.394 0.000 0.000 0.000 0.000 0.000 6.394 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 10.366 67.820 0.000 0.000 0.000 0.000 78.186 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 10.366 67.820 0.000 0.000 0.000 0.000 78.186 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 11.722 515.227 2419.260 0.000 0.000 0.000 2946.209 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 6.394 0.000 0.000 0.000 0.000 0.000 6.394 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 18084.325 9.139 169.807 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 18084.325
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 894.495 13.336 82.602 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 894.495
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 1035.829 13.336 82.602 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1035.829
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 1511.551 9.203 569.967 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1511.551
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 578.329 6.103 283.494 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 578.329
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 453.605 5.813 54.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 453.605
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1957.673 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1957.673
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 11405.759 8.719 27.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 11405.759
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 111.660 4.553 74.440 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.660
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 111.691 4.553 74.460 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.691
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 2489.757 6.394 118.803 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2489.757
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 111.691 4.553 74.460 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.691
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 3437.839 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3437.839
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 3437.839 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3437.839
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1210.923 11.722 54.453 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1210.923
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 2635.024 6.394 118.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2635.024


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 457.500 4.429 20.573 0.000 0.250 0.000 0.750 ReachInFreezer 457.500 457.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 285.000 2.759 12.816 0.000 0.250 0.000 0.750 ReachInRefrigerator 285.000 285.000


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.198 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.1864 0.900 0.900 0.770 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.1864 0.900 0.900 0.770 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 0.8226 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.107 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.174 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.031 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.097 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.8346
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.048
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.7359
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6841
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.8028
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.7445
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.312
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.312
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.312
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.312
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.1981135 1.1981135 1.1981135  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
21 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
22 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
23 0 21.357363 0.71091016E-01 5.4032014  
24 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
25 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
26 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
27 0 21.357363 0.71091016E-01 5.4032014  
28 9 -0.17638513E-14 0.32473881E-16 -0.15472737E-09 0.39084990E-16
29 8 0.22578286E-07 0.11136169E-12 0.38514655E-03 -0.25672286E-09
30 7 -0.12460867E-01 0.57383191E-08 -0.23401545E-01 0.14168460E-03
31 6 0.41130930 0.19934685E-05 0.47716306 -0.48180040E-02
32 5 -5.2487139 0.74343025E-04 -4.4802041 0.63904887E-01
33 4 33.260058 0.60748543E-03 21.592533 -0.42553784
34 3 -111.77343 0.13226915E-02 -55.924898 1.5231004
35 2 197.67353 0.74337769E-03 78.150831 -2.9093300
36 1 -171.36487 0.79295509E-04 -55.335031 2.7490988
37 0 57.057407 0.45097929E-06 15.545453  
38 9 -0.19728226E-15 0.38070760E-16 -0.14134637E-09 0.10329039E-17
39 8 0.20696804E-07 0.14765672E-12 0.36530744E-03 -0.23532978E-09
40 7 -0.11868633E-01 0.77667999E-08 -0.22548754E-01 0.13495068E-03
41 6 0.39521686 0.27204939E-05 0.46345169 -0.46283129E-02
42 5 -5.0916664 0.10217830E-03 -4.3748670 0.61957574E-01
43 4 32.565369 0.84029717E-03 21.180735 -0.41631434
44 3 -110.29532 0.18400486E-02 -55.110745 1.5017457
45 2 196.20849 0.10394005E-02 77.404245 -2.8860650
46 1 -170.82368 0.11139293E-03 -55.118150 2.7396138
47 0 57.057407 0.63685742E-06 15.581450  
48 9 0.13059652E-14 0.41030072E-16 -0.13816519E-09 -0.47111965E-17
49 8 0.20247126E-07 0.15597406E-12 0.36047671E-03 -0.23021680E-09
50 7 -0.11724123E-01 0.82470298E-08 -0.22340566E-01 0.13330755E-03
51 6 0.39128975 0.28947446E-05 0.46009809 -0.45820219E-02
52 5 -5.0533361 0.10891817E-03 -4.3490697 0.61482301E-01
53 4 32.395785 0.89717001E-03 21.079809 -0.41406279
54 3 -109.93440 0.19673976E-02 -54.911173 1.4965315
55 2 195.85064 0.11127485E-02 77.221372 -2.8803827
56 1 -170.69145 0.11939355E-03 -55.065279 2.7372963
57 0 57.057407 0.68346468E-06 15.590432  
58 9 -0.20590843E-15 0.37601014E-16 -0.14495918E-09 0.53749011E-17
59 8 0.21205398E-07 0.13808064E-12 0.37072834E-03 -0.24111267E-09
60 7 -0.12030653E-01 0.72214098E-08 -0.22782120E-01 0.13679291E-03
61 6 0.39961963 0.25236359E-05 0.46720788 -0.46802108E-02
62 5 -5.1346368 0.94596970E-04 -4.4037454 0.62490383E-01
63 4 32.755467 0.77656360E-03 21.293679 -0.41883826
64 3 -110.69986 0.16977958E-02 -55.334066 1.5075900
65 2 196.60952 0.95769584E-03 77.608945 -2.8924333
66 1 -170.97185 0.10250317E-03 -55.177451 2.7422106
67 0 57.057407 0.58520576E-06 15.571474  
68 9 -0.13316196E-15 0.35962645E-16 -0.14184186E-09 0.33595795E-17
69 8 0.20766565E-07 0.14634888E-12 0.36605364E-03 -0.23612300E-09
70 7 -0.11890945E-01 0.76921302E-08 -0.22580893E-01 0.13520437E-03
71 6 0.39582317 0.26934781E-05 0.46396918 -0.46354598E-02
72 5 -5.0975841 0.10113583E-03 -4.3788466 0.62030949E-01
73 4 32.591550 0.83151862E-03 21.196301 -0.41666193
74 3 -110.35104 0.18204263E-02 -55.141525 1.5025506
75 2 196.26372 0.10281160E-02 77.432455 -2.8869422
76 1 -170.84409 0.11016374E-03 -55.126315 2.7399715
77 0 57.057407 0.62970739E-06 15.580070  
78 7 -0.15963512E-14 -0.15187529E-16 -0.22427203E-13 0.56155309E-15
79 6 0.17983713E-10 0.23594901E-11 0.52322926E-09 -0.18637893E-10
80 5 -0.60139213E-07 0.11510628E-07 -0.21924491E-05 0.17161312E-06
81 4 0.62746279E-04 0.43399923E-05 0.17681060E-02 -0.28244642E-03
82 3 -0.90508353E-02 0.15320797E-03 -0.21560640 0.43341486E-01
83 2 0.12836503 0.66328859E-03 2.9007871 -0.61911613
84 1 -0.32478029 0.41934727E-03 -7.1379041 1.5697129
85 0 0.20664896 0.54311639E-05 4.4522013  
86 7 -0.22427203E-13 -0.15187529E-16 -0.15963512E-14 0.56155309E-15
87 6 0.52322926E-09 0.23594901E-11 0.17983713E-10 -0.18637893E-10
88 5 -0.21924491E-05 0.11510628E-07 -0.60139213E-07 0.17161312E-06
89 4 0.17681060E-02 0.43399923E-05 0.62746279E-04 -0.28244642E-03
90 3 -0.21560640 0.15320797E-03 -0.90508353E-02 0.43341486E-01
91 2 2.9007871 0.66328859E-03 0.12836503 -0.61911613
92 1 -7.1379041 0.41934727E-03 -0.32478029 1.5697129
93 0 4.4522013 0.54311639E-05 0.20664896  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
103 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
104 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
105 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
106 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
107 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
108 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
109 0 0.43108349 0.21254961E-04 60.838472  
110 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
111 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
112 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
113 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
114 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
115 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
116 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
117 0 0.43108349 0.21254961E-04 60.838472  
118 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
119 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
120 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
121 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
122 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
123 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
124 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
125 0 0.43108349 0.21254961E-04 60.838472  
126 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
127 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
128 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
129 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
130 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
131 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
132 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
133 0 0.43108349 0.21254961E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.3856_SHGC_0.4 37 1 VerySmooth 2.191 2.191 1.000 0.401    
2 RESWINDOW_U_0.3856_SHGC_0.4 38 1 VerySmooth 2.191 2.191 1.000 0.401    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   3.40174E-002 0.31435 0.47878 0.47878 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 0.11969 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   3.40174E-002 0.31435 0.47878 0.47878 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 0.11969 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 1.500
2 RACK2 1 0 Zone Air-Cooled 3.000


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 0.576 0.5074
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 0.263 2.9576E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 3.921E-002 5.846E-004 2.885E-004 0.531 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 1.513E-002 1.949E-004 5.306E-004 0.177 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 3.577E-002 2.178E-004 5.696E-004 0.198 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 2.064E-002 2.178E-004 4.726E-004 0.198 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 4.884E-002 6.258E-004 5.569E-004 0.569 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 8.667E-002 4.589E-004 2.527E-004 0.417 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.248 1.893E-004 3.620E-004 0.172 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 6.349E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 6.350E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 2.751E-002 7.066E-005 5.696E-004 8.345E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.164E-002 4.746E-004 2.589E-004 0.561 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 4.974E-002 4.815E-004 2.609E-004 0.569 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 4.868E-002 1.181E-004 9.784E-005 0.140 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1505
2 Clear Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 8.9294E-002
3 Clear Turbid Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1718
4 Clear Turbid Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 0.1044
5 Intermediate Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1000
6 Intermediate Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 4.0976E-002
7 Overcast Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 4.2077E-002
8 Overcast Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 1.3979E-002
9 Clear Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1725
10 Clear Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 0.1069
11 Clear Turbid Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1978
12 Clear Turbid Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 0.1245
13 Intermediate Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1107
14 Intermediate Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 5.1062E-002
15 Overcast Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 4.7248E-002
16 Overcast Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 1.9114E-002
17 Clear Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 3.9527E-002
18 Clear Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 2.2854E-002
19 Clear Turbid Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 3.0432E-002
20 Clear Turbid Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.7306E-002
21 Intermediate Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.8856E-002
22 Intermediate Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.1489E-002
23 Overcast Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 4.1419E-002
24 Overcast Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.4687E-002
25 Clear Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 3.9527E-002
26 Clear Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 2.2854E-002
27 Clear Turbid Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 3.0432E-002
28 Clear Turbid Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.7306E-002
29 Intermediate Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.8856E-002
30 Intermediate Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.1489E-002
31 Overcast Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 4.1419E-002
32 Overcast Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.4687E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 35105.47130 35105.47130 2.58758 2.58758 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 26.12400 8.81626E-003 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 0.85446 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 6497.64608 6497.64608 0.47897 0.47897 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:20:00 29.05333 8.82094E-003 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 2318.34601 2318.34601 0.10080 0.10080 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3277.67745 3277.67745 0.24162 0.24162 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 29.29600 8.82133E-003 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 769.51877 769.51877 3.34606E-002 9.17347E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 2984.89200 2984.89200 0.21999 0.21999 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 29.19200 8.82116E-003 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1432.08484 1432.08484 6.22704E-002 6.22704E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1438.22015 1438.22015 0.10600 0.10600 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 29.40000 8.82150E-003 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 879.09236 879.09236 3.82250E-002 5.77652E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 44752.70101 44752.70101 3.29863 3.29863 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 29.40000 8.82150E-003 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 1890.62156 1890.62156 8.22061E-002 8.22061E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 25034.65568 25034.65568 1.84689 1.84689 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:20:00 29.05333 8.82094E-003 188.86188 142.30000 0.67639 0.00000
14 CAFE_FLR_1 Heating 5823.45042 5823.45042 0.25321 0.67639 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 188.86188 142.30000 0.67639 0.00000
15 LOBBY_FLR_1 Cooling 68981.24283 68981.24283 5.08645 5.08645 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 29.22667 8.82122E-003 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 13678.68023 13678.68023 0.59478 1.89399 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 12249.78776 12249.78776 1.21668 1.21668 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 28.36000 8.81983E-003 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 5288.08678 5288.08678 0.23128 0.23128 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 11017.88221 11017.88221 1.09432 1.09432 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 28.08267 8.81938E-003 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 5291.63389 5291.63389 0.23144 0.23144 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 82035.79616 82035.79616 8.14762 8.14762 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 29.14000 8.82108E-003 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 30397.98497 30397.98497 1.32953 1.32953 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 50871.94353 50871.94353 5.05289 5.05289 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 29.40000 8.82150E-003 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 30479.61972 30479.61972 1.33310 1.33310 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 10948.80272 10948.80272 1.08746 1.08746 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 25.44800 8.81519E-003 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 5295.83755 5295.83755 0.23162 0.23162 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 9924.47087 9924.47087 0.98572 0.98572 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 09:00:00 23.68000 8.81240E-003 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 5299.38347 5299.38347 0.23178 0.23178 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 21363.81466 21363.81466 1.57466 1.57466 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 29.40000 8.82150E-003 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 8366.32729 8366.32729 0.36379 0.47476 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 3197.94297 3197.94297 0.31763 0.31763 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 28.36000 8.81983E-003 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 1612.13003 1612.13003 7.05085E-002 7.05085E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2852.18311 2852.18311 0.28329 0.28329 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 27.94400 8.81916E-003 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 1613.96726 1613.96726 7.05889E-002 7.05889E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 17290.84334 17290.84334 1.71741 1.71741 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 29.22667 8.82122E-003 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 7727.66243 7727.66243 0.33798 0.33798 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 28918.70850 28918.70850 2.13415 2.13415 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 29.40000 8.82150E-003 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 5218.57896 5218.57896 0.22692 1.18780 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -4.20000 2.69032E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 30294.69545 30294.69545 2.23566 2.23566 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 29.40000 8.82150E-003 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 5332.14830 5332.14830 0.23185 1.18780 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:20:00 -4.20000 2.69032E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 30952.69610 30952.69610 2.28735 2.28735 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 28.46400 8.82000E-003 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 1515.68164 1515.68164 6.58950E-002 0.36735 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 23:30:00 -4.20000 2.69032E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 11000.21624 11000.21624 0.81078 0.81078 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 29.40000 8.82150E-003 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 5442.67036 5442.67036 0.23666 0.23666 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:30:00 -4.20000 2.69032E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 379208.27 22.78522 22.78522 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 181330.16 7.27397 7.27397 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00
3 FLR_3_DOAS Cooling Sensible 40614.20 18.54363 2.05125 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 FLR_3_DOAS Heating Sensible 51134.75 4.06783 2.05125 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.58758
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.58273
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50900
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.31708
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.53815E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.99701E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.31708
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6854.95244
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.99701E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 142.94822
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.47897
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10670
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50900
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24380
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50900
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.57062E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.13710E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.24380
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3585.89367
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.13710E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 82.68476
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.24162
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24495
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50900
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12298
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.65319
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.55545E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.23257E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.12298
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1408.90608
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.23257E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 31.34275
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.21999
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.56891
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50900
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.11197
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.69707E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.76201E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.11197
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2014.08622
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.76201E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 48.22862
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.10600
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.68120
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50900
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.39536E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.59308E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.01442E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.39536E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1159.54158
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.01442E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 28.97237
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.29863
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.15369E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50900
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.67900
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50900
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.11344E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.28766E-005
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.67900
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10616.36998
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.28766E-005
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 223.88168
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.84689
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.79217E-002
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50900
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.94007
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50900
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.88952E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.37102E-005
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.94007
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10711.65227
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.37102E-005
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 238.13551
99 Fan:ZoneExhaust LOBBY_FLR_1 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.08645
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19598
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50900
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.58900
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52261
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.94408E-003
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.37430E-004
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.58900
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
110 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 27139.73327
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.37430E-004
113 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 597.49408
114 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
115 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.21668
116 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.21668
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.62615E-005
118 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.76761E-004
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69134
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56608E-003
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.76761E-004
125 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.21668
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5287.97220
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.62615E-005
128 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 151.11637
129 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
130 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.09432
131 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.09432
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.62925E-005
133 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.29647E-004
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69133
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57313E-003
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.29647E-004
140 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.09432
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5291.51924
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.62925E-005
143 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 151.21771
144 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
145 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 8.14762
146 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 8.14762
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.65932E-004
148 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.13877E-003
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69178
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.50448E-003
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.13877E-003
155 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 8.14762
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 30397.66291
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.65932E-004
158 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 868.67039
159 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
160 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.05289
161 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 5.05289
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.66646E-004
163 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.09835E-003
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69083
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.78368E-003
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.09835E-003
170 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.05289
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 30479.29684
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.66646E-004
173 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 871.00269
174 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
175 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.08746
176 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.08746
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.63293E-005
178 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.27047E-004
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69133
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57394E-003
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.27047E-004
185 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.08746
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5295.72282
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.63293E-005
188 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 151.33780
189 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
190 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.98572
191 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.98572
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.63603E-005
193 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.87884E-004
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69132
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.58138E-003
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.87884E-004
200 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.98572
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5299.26867
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.63603E-005
203 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 151.43910
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.57466
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.75375
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50900
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.80150
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.05470E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.09659E-004
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.80150
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
214 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12534.72289
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.09659E-004
217 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 292.09949
218 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
219 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.31763
220 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.31763
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.41033E-005
222 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.24370E-004
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69135
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56333E-003
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.24370E-004
229 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.31763
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1612.09624
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.41033E-005
232 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 46.06718
233 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
234 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.28329
235 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.28329
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.41194E-005
237 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.11161E-004
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69134
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57113E-003
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.11161E-004
244 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.28329
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1613.93343
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.41194E-005
247 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 46.11967
248 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
249 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.71741
250 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.71741
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 6.76038E-005
252 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 6.79536E-004
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69111
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.60163E-003
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 6.79536E-004
259 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.71741
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 7727.53216
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.76038E-005
262 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 220.81986
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.13415
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11842
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50900
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.08628
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50900
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.21740E-003
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.50834E-005
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.08628
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
273 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10868.62105
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.50834E-005
276 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 238.09312
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.23566
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11304
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50900
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.13795
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50900
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.37044E-003
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.84251E-005
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.13795
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
287 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11250.59670
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.84251E-005
290 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 246.15173
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.28735
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.18987E-002
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50900
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.16426
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50900
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.10709E-002
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.60193E-005
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.16426
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
301 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7546.41144
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.60193E-005
304 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 159.39670
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.81078
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.38733
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50900
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.41269
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.83665E-004
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.63945E-005
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.41269
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
315 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7589.30441
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.63945E-005
318 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 182.60068
319 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 11.66055
320 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 11.66055
321 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 22.90874
322 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 11.66055
323 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 22.78522
324 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 22.78522
325 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
326 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.51176
327 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
328 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
329 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
333 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
334 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
335 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 22.78522
336 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
337 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 22.78522
338 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 11.66146
339 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 11.66146
340 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.75983
341 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.95288
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 9.20444E-003
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 484932.30241
346 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.73207E-002
347 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 22.78522
348 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 170401.38827
349 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.49075E-003
350 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 2909.13105
351 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 22.78522
352 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.73207E-002
353 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 2.74926E-005
354 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.49075E-003
355 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
356 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
357 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
358 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 29.40000
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.91727
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.82150E-003
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 45447.83718
364 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.62329E-003
365 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
366 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 15340.96456
367 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.34209E-004
368 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 261.90442
369 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
370 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.62329E-003
371 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 2.93349E-004
372 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.34209E-004
373 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 2.68175E-002
374 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 5526.08761
375 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 3.42963E-003
376 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.41156
377 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 3.42963E-003
378 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 1032.85493
379 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
380 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 392028.14934
381 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 392028.15000
382 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 3.42963E-003
383 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 2.68175E-002
384 PlantLoop COOLSYS1 Plant Loop Volume [m3] 3.21810
385 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 2.68175E-002
386 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 3825.89684
387 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 2.68175E-002
388 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 750817.87420
389 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 751446.35000
390 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 85.66488
391 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
392 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
393 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
394 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
395 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 6890.40
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 3602.50
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1415.67
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 2022.96
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1164.43
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 10670.69
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 10763.10
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 27271.39
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 5695.76
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 5699.58
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 32741.61
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 32829.53
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 5704.11
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 5707.93
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 12592.19
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 1736.36
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 1738.34
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 8323.18
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 10922.38
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 11306.31
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 7584.97
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 7622.56
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 129793.51
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 11685.10


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 20101.76 16216.41 3885.35 0.81 2304.78 23.38
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 18103.16 14596.81 3506.35 0.81 2075.21 21.05
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 133116.15 107862.70 25253.44 0.81 15290.37 155.08
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 86680.27 68904.48 17775.78 0.79 9883.47 100.24
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 17992.25 14506.55 3485.70 0.81 2062.45 20.92
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 16330.72 13160.00 3170.72 0.81 1871.59 18.98
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 5245.20 4232.21 1012.99 0.81 601.44 6.10
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 4684.66 3777.83 906.83 0.81 537.04 5.45
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 28555.22 22978.47 5576.75 0.80 3270.74 33.17
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 564736.83 393930.71 170806.12 0.70 67754.50 687.20
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 49660.04 34741.99 14918.05 0.70 5487.20 55.65


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 3.93 13.40


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.419 0.394   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.419 0.394   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.419 0.394   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.419 0.394   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.198 1.198   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.107 0.950   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.107 0.950   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.107 0.950   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.107 0.950   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.097 0.942   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.097 0.942   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.097 0.942   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.097 0.942   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.097 0.942   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 4.1123275330E-002 5.4830907302E-002 Pass Pass 0.1798428160 0.5019573521 Fail Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 1.5352113464E-002 4.3666210377E-002 Pass Pass 0.7218030519 2.0762663513 Fail Fail
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 5.9452083119E-002 9.0933808365E-002 Fail Pass 0.3340585306 1.0907716220 Fail Fail
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 2.3065469047E-002 4.2107845142E-002 Pass Pass 0.3730168843 1.5827395286 Fail Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 8.8115916466E-003 2.4021409378E-002 Pass Pass 0.5323456356 1.4075677788 Fail Fail
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 0.2915345998 0.5854183237 Fail Pass 0.1133388078 0.1859829449 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 9.6090619699E-002 0.2233351616 Pass Pass 0.3692736017 1.4712085478 Fail Fail
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 7.7516558155E-002 0.1177471529 Fail Pass 0.3755386433 1.5616514111 Fail Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 8.6075712921E-002 0.2955614783 Pass Pass 0.2603090844 0.9053068675 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 8.6186875922E-002 0.2960410767 Pass Pass 0.4527276256 1.8358502002 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 2.5838893067E-003 1.0221744774E-002 Pass Pass 0.7727228165 3.1513602429 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 2.4535654034E-002 9.5821157305E-002 Pass Pass 1.0885348933 10.5404083543 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 8.5796129468E-002 0.2941461152 Pass Pass 0.2578367068 0.8874627227 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 8.5910841400E-002 0.2944820514 Pass Pass 0.3285987715 1.1195874939 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 1.0020579568E-002 2.7081599133E-002 Pass Pass 0.5450773951 1.5342547214 Fail Fail
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 9.2584893008E-002 0.3322936141 Pass Pass 0.3333081383 1.3889649502 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 9.2611470874E-002 0.3321331018 Pass Pass 0.2987667375 1.1747087133 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 7.4212473659E-002 0.2602181338 Pass Pass 0.1832041503 0.6583140336 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 0.1059081673 0.1985906349 Pass Pass 0.1454274845 0.2653621272 Pass Fail
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 0.1004551873 0.2248000085 Fail Pass 0.1394628087 0.2701254248 Pass Fail
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 0.2552857248 0.5278026225 Fail Pass 0.1207320165 0.1976485340 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 1.7647351137E-002 4.8467937038E-002 Pass Pass 0.4775855913 2.5149484716 Fail Fail



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3545.01 132.86 1716.91 7242.80 2239.93 14877.52



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB -4.20 0.00 -4.20 Wetbulb [C] 4.30 20.00
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 29.40 10.40 18.30 Wetbulb [C] 4.20 350.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 22.00 23      
Apr 0.00 0      
May 0.00 0      
Jun 16.00 20      
Jul 0.00 0      
Aug 24.00 18      
Sep 12.00 15      
Oct 61.00 41      
Nov 0.00 0      
Dec 45.00 41      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.399 0.419 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.399 0.419 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.399 0.419 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.732 0.823 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.23 0.182 0.186 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.732 0.823 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.732 0.823 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.732 0.823 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.23 0.182 0.186 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 0.732 0.823 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.23 0.182 0.186 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.893 1.031 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.893 1.031 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.893 1.031 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.893 1.031 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.893 1.031 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.893 1.031 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.893 1.031 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.893 1.031 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.893 1.031 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.893 1.031 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 0.950 1.107 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 0.950 1.107 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 0.950 1.107 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 0.950 1.107 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.942 1.097 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.942 1.097 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 0.942 1.097 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.942 1.097 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.942 1.097 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.999 1.174 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.23 0.182 0.186 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.23 0.182 0.186 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.186 0.196 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.186 0.196 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.186 0.196 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.186 0.196 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.186 0.196 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.186 0.196 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.186 0.196 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.186 0.196 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.186 0.196 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.186 0.196 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.185 0.196 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.185 0.196 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.185 0.196 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.188 0.196 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   23.26 0.00 0.00 23.26 23.26 2.191 0.401 0.402             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   65.50 0.00 0.00 65.50 65.50 2.191 0.401 0.402             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   85.08 0.00 0.00 85.08 85.08 2.191 0.401 0.402             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.191 0.401 0.402             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.191 0.401 0.402             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.191 0.401 0.402             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.191 0.401 0.402             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   3.68 0.00 0.00 3.68 279.56 2.191 0.401 0.402             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   3.68 0.00 0.00 3.68 279.65 2.191 0.401 0.402             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.191 0.401 0.402             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.191 0.401 0.402             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.191 0.401 0.402             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.191 0.401 0.402             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   5.82 0.00 0.00 5.82 23.30 2.191 0.401 0.402             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   2.15 0.00 0.00 2.15 8.59 2.191 0.401 0.402             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   2.15 0.00 0.00 2.15 8.58 2.191 0.401 0.402             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   5.82 0.00 0.00 5.82 23.30 2.191 0.401 0.402             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.191 0.401 0.402             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 8.58 2.191 0.401 0.402             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.191 0.401 0.402             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 8.58 2.191 0.401 0.402             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   6.74 0.00 0.00 6.74 60.70 2.191 0.401 0.402             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   32.19 0.00 0.00 32.19 32.19 2.191 0.401 0.402             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   32.19 0.00 0.00 32.19 32.19 2.191 0.401 0.402             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.191 0.401 0.402             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   17.17 0.00 0.00 17.17 17.17 2.191 0.401 0.402             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.191 0.401 0.402             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   5.82 0.00 0.00 5.82 5.82 2.191 0.401 0.402             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   5.21 0.00 0.00 5.21 5.21 2.191 0.401 0.402             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   17.17 0.00 0.00 17.17 17.17 2.191 0.401 0.402             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.191 0.401 0.402                      
North Total or Average             432.95 2.191 0.401 0.402                      
Non-North Total or Average             780.84 2.191 0.401 0.402                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.016 1.198 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 9.1389 1978.83 18084.33 LightsWired LTG_SCH_BASEMENT 51.16 168.00 51.10 0.0000 Y 173.46
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 13.3365 67.07 894.50 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 8.61
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 13.3365 77.67 1035.83 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 9.97
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 9.2031 164.24 1511.55 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 16.63
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 6.1031 94.76 578.33 LightsWired LTG_SCH_STORAGE 25.68 168.00 25.65 0.0000 Y 2.78
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.8125 78.04 453.60 LightsWired LTG_SCH_LAUNDRY 51.36 168.00 51.30 0.0000 Y 4.37
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 10.3656 188.86 1957.67 LightsWired LTG_SCH_DINING 58.69 168.00 48.84 0.0000 Y 17.95
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 8.7188 1308.19 11405.76 LightsWired LTG_SCH_LOBBY 58.69 168.00 56.94 0.0000 Y 121.92
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 4.5531 156.09 710.69 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 4.5531 156.07 710.61 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 4.5531 1863.81 8486.17 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 76.02
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 4.5531 1864.32 8488.49 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 76.04
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 4.5531 156.09 710.69 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 4.5531 156.07 710.61 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 6.3938 1557.62 9959.03 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 109.60
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 4.5531 39.02 177.67 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.59
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 4.5531 39.02 177.65 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.59
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 4.5531 220.77 1005.22 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 9.00
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 10.3656 331.66 3437.84 LightsWired LTG_SCH_DINING 58.69 168.00 53.70 0.0000 Y 34.65
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 10.3656 331.66 3437.84 LightsWired LTG_SCH_DINING 58.69 168.00 53.70 0.0000 Y 34.65
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 11.7219 103.30 1210.92 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 13.33
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 6.3938 412.12 2635.02 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 29.00
Interior Lighting Total       6.8557 11345.29 77780.02               507.28


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.07 11405.76 798.40
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.00 11405.76 0.00
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.39 1957.67 763.49
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.00 1957.67 0.00
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3437.84 687.57
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.00 3437.84 0.00
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3437.84 687.57
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.00 3437.84 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 15448.40 AstronomicalClock -   83.55 83.55 242.27
Exterior Lighting Total 15448.40           242.27



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 392028.15 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 751446.35 2.96 751578.43 2.96 3.93 13.40


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 13348.29 20101.76 16216.41 3885.35 0.81 - 2304.78 23.38
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12029.20 18103.16 14596.81 3506.35 0.81 - 2075.21 21.05
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 87878.75 133116.15 107862.70 25253.44 0.81 - 15290.37 155.08
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 58749.36 86680.27 68904.48 17775.78 0.79 - 9883.47 100.24
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11956.41 17992.25 14506.55 3485.70 0.81 - 2062.45 20.92
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10859.93 16330.72 13160.00 3170.72 0.81 - 1871.59 18.98
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3482.09 5245.20 4232.21 1012.99 0.81 - 601.44 6.10
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3112.28 4684.66 3777.83 906.83 0.81 - 537.04 5.45
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 19025.55 28555.22 22978.47 5576.75 0.80 - 3270.74 33.17
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 484932.30 564736.83 393930.71 170806.12 0.70 - 67754.50 687.20
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 45447.84 49660.04 34741.99 14918.05 0.70 - 5487.20 55.65
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 6854.95 6890.40 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 3585.89 3602.50 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1408.91 1415.67 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2014.09 2022.96 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1159.54 1164.43 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 10616.37 10670.69 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 10711.65 10763.10 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 27139.73 27271.39 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5287.97 5695.76 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5291.52 5699.58 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 30397.66 32741.61 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 30479.30 32829.53 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5295.72 5704.11 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5299.27 5707.93 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 12534.72 12592.19 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1612.10 1736.36 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1613.93 1738.34 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 7727.53 8323.18 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 10868.62 10922.38 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 11250.60 11306.31 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 7546.41 7584.97 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 7589.30 7622.56 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 170401.39 129793.51 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 15340.96 11685.10 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.22 856.10 703.64 1.00 1.15 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.09 770.01 703.64 1.00 1.18 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 8.15 5732.96 703.64 1.00 0.94 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 5.05 3555.40 703.64 1.00 0.97 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.09 765.18 703.64 1.00 1.18 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.99 693.59 703.64 1.00 1.20 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 09:00:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.32 223.49 703.64 1.00 1.67 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.28 199.33 703.64 1.00 1.75 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.72 1208.43 703.64 1.00 1.09 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 22.79 51053.45 2240.64 1.00 1.11 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.026817 5526.09 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.003430 1032.85 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.026817 3825.90 142664.32 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.80 0.58 0.51
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.80 0.26 0.03



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 35105.47 35105.47 17.74 2.588 2.588 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 24.00 24.00 0.00919 26.12 0.00882 0.854 0.00
RETAIL_1_FLR_1 6497.65 6497.65 96.88 0.479 0.479 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:20:00 24.00 24.00 0.00888 29.05 0.00882 0.079 0.00
RETAIL_2_FLR_1 3277.68 3277.68 42.20 0.242 0.242 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 24.00 24.00 0.00936 29.30 0.00882 0.092 0.00
MECH_FLR_1 2984.89 2984.89 18.17 0.220 0.220 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 24.00 24.00 0.00871 29.19 0.00882 0.000 0.00
STORAGE_FLR_1 1438.22 1438.22 15.18 0.106 0.106 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 24.00 24.00 0.00882 29.40 0.00882 0.058 0.00
LAUNDRY_FLR_1 44752.70 44752.70 573.46 3.299 3.299 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 24.00 24.00 0.00854 29.40 0.00882 0.000 0.00
CAFE_FLR_1 25034.66 25034.66 132.56 1.847 1.847 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:20:00 24.00 23.99 0.00977 29.05 0.00882 0.676 0.00
LOBBY_FLR_1 68981.24 68981.24 52.73 5.086 5.086 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 24.00 23.99 0.00987 29.23 0.00882 1.894 0.00
ROOM_1_FLR_3 12249.79 12249.79 313.92 1.217 1.217 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 21.11 21.11 0.00857 28.36 0.00882 0.062 0.00
ROOM_2_FLR_3 11017.88 11017.88 282.38 1.094 1.094 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 21.11 21.11 0.00857 28.08 0.00882 0.062 0.00
ROOM_3_MULT19_FLR_3 82035.80 82035.80 3345.14 8.148 8.148 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 21.11 21.11 0.00850 29.14 0.00882 0.837 0.00
ROOM_4_MULT19_FLR_3 50871.94 50871.94 2073.82 5.053 5.053 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 21.11 21.11 0.00878 29.40 0.00882 0.837 0.00
ROOM_5_FLR_3 10948.80 10948.80 280.58 1.087 1.087 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 21.11 21.11 0.00857 25.45 0.00882 0.062 0.00
ROOM_6_FLR_3 9924.47 9924.47 254.36 0.986 0.986 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 09:00:00 21.11 21.11 0.00858 23.68 0.00881 0.062 0.00
CORRIDOR_FLR_3 21363.81 21363.81 54.86 1.575 1.575 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 24.00 24.00 0.00939 29.40 0.00882 0.475 0.00
ROOM_1_FLR_6 3197.94 3197.94 81.95 0.318 0.318 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 21.11 21.11 0.00856 28.36 0.00882 0.015 0.00
ROOM_2_FLR_6 2852.18 2852.18 73.10 0.283 0.283 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 21.11 21.11 0.00857 27.94 0.00882 0.015 0.00
ROOM_3_MULT9_FLR_6 17290.84 17290.84 704.87 1.717 1.717 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 21.11 21.11 0.00860 29.23 0.00882 0.099 0.00
BANQUET_FLR_6 28918.71 28918.71 87.19 2.134 2.134 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 24.00 23.98 0.01044 29.40 0.00882 1.188 0.00
DINING_FLR_6 30294.70 30294.70 91.34 2.236 2.236 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 24.00 23.99 0.01035 29.40 0.00882 1.188 0.00
KITCHEN_FLR_6 30952.70 30952.70 299.63 2.287 2.287 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 24.00 23.97 0.01007 28.46 0.00882 0.367 0.00
CORRIDOR_FLR_6 11000.22 11000.22 26.69 0.811 0.811 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 24.00 24.00 0.00896 29.40 0.00882 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 0.854 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.99 0.00269 -4.20 0.00269 0.854 0.00
RETAIL_1_FLR_1 2318.35 2318.35 34.57 0.101 0.101 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00749 -4.20 0.00269 0.079 0.00
RETAIL_2_FLR_1 769.52 769.52 9.91 0.033 0.092 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00742 -4.20 0.00269 0.092 0.00
MECH_FLR_1 1432.08 1432.08 8.72 0.062 0.062 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00728 -4.20 0.00269 0.000 0.00
STORAGE_FLR_1 879.09 879.09 9.28 0.038 0.058 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00732 -4.20 0.00269 0.058 0.00
LAUNDRY_FLR_1 1890.62 1890.62 24.23 0.082 0.082 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00726 -4.20 0.00269 0.000 0.00
CAFE_FLR_1 5823.45 5823.45 30.83 0.253 0.676 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00755 -4.20 0.00269 0.676 0.00
LOBBY_FLR_1 13678.68 13678.68 10.46 0.595 1.894 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00746 -4.20 0.00269 1.894 0.00
ROOM_1_FLR_3 5288.09 5288.09 135.52 0.231 0.231 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00749 -4.20 0.00269 0.062 0.00
ROOM_2_FLR_3 5291.63 5291.63 135.62 0.231 0.231 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00749 -4.20 0.00269 0.062 0.00
ROOM_3_MULT19_FLR_3 30397.98 30397.98 1239.53 1.330 1.330 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00752 -4.20 0.00269 0.837 0.00
ROOM_4_MULT19_FLR_3 30479.62 30479.62 1242.52 1.333 1.333 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00752 -4.20 0.00269 0.837 0.00
ROOM_5_FLR_3 5295.84 5295.84 135.71 0.232 0.232 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00749 -4.20 0.00269 0.062 0.00
ROOM_6_FLR_3 5299.38 5299.38 135.82 0.232 0.232 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00749 -4.20 0.00269 0.062 0.00
CORRIDOR_FLR_3 8366.33 8366.33 21.48 0.364 0.475 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00760 -4.20 0.00269 0.475 0.00
ROOM_1_FLR_6 1612.13 1612.13 41.31 0.071 0.071 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00757 -4.20 0.00269 0.015 0.00
ROOM_2_FLR_6 1613.97 1613.97 41.37 0.071 0.071 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00757 -4.20 0.00269 0.015 0.00
ROOM_3_MULT9_FLR_6 7727.66 7727.66 315.02 0.338 0.338 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00759 -4.20 0.00269 0.099 0.00
BANQUET_FLR_6 5218.58 5218.58 15.73 0.227 1.188 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00767 -4.20 0.00269 1.188 0.00
DINING_FLR_6 5332.15 5332.15 16.08 0.232 1.188 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:20:00 21.00 21.00 0.00768 -4.20 0.00269 1.188 0.00
KITCHEN_FLR_6 1515.68 1515.68 14.67 0.066 0.367 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 23:30:00 21.00 21.00 0.00585 -4.20 0.00269 0.367 0.00
CORRIDOR_FLR_6 5442.67 5442.67 13.21 0.237 0.237 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:30:00 21.00 21.00 0.00772 -4.20 0.00269 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 22.79 22.79 7.27 7.27 22.7852 11.6605 22.7852 0.5118 0.3000
FLR_3_DOAS 18.54 2.05 4.07 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 6854.952 6854.952 1.317077 0.00005997 142.948 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6854.95 6854.95 1.317077 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00800000 50.9797 0.00 0.00 6893.48 6893.48
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 3585.894 3585.894 0.243797 0.00003137 82.685 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3585.89 3585.89 0.243797 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00749309 47.7895 2318.35 0.00 3605.11 3605.11
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1408.906 1408.906 0.122984 0.00001233 31.343 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1408.91 1408.91 0.122984 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00741935 47.3237 769.52 0.00 1416.56 1416.56
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 2014.086 2014.086 0.111975 0.00001762 48.229 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2014.09 2014.09 0.111975 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00728366 46.4683 1432.08 0.00 2024.63 2024.63
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1159.542 1159.542 0.053954 0.00001014 28.972 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1159.54 1159.54 0.053954 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00732126 46.7054 879.09 0.00 1165.52 1165.52
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10616.370 10616.370 1.679003 0.00009288 223.882 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 10616.37 10616.37 1.679003 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00726278 46.3376 1890.62 0.00 10675.80 10675.80
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 10711.652 10711.652 0.940067 0.00009371 238.136 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 10711.65 10711.65 0.940067 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00754874 48.1398 5823.45 0.00 10769.83 10769.83
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 27139.733 27139.733 2.589003 0.00023743 597.494 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 27139.73 27139.73 2.589003 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00746084 47.5852 13678.68 0.00 27287.71 27287.71
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 13348.290 -999.000 1.216678 0.00047676 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown 8/21 16:30:00 13348.29 13138.63 1.216678 21.69 15.47 0.00856608 12.80 11.97 0.00850000 28.36 0.00881983 18.00 0.0000 21.11 0.00856608 54.1686 12249.79 0.00 13533.71 13087.78
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 5287.972 5287.972 0.231281 0.00004626 151.116 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5287.97 5287.97 0.231281 21.11 14.28 0.00748764 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.11 0.00748764 47.4309 5288.09 0.00 5700.56 5700.56
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 12029.196 -999.000 1.094323 0.00042965 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 unknown 8/21 16:50:00 12029.20 11820.43 1.094323 21.69 15.48 0.00857313 12.80 11.97 0.00850000 28.08 0.00881938 17.91 0.0000 21.11 0.00857313 54.2126 11017.88 0.00 12196.13 11775.23
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 5291.519 5291.519 0.231436 0.00004629 151.218 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5291.52 5291.52 0.231436 21.11 14.28 0.00748799 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.11 0.00748799 47.4331 5291.63 0.00 5704.38 5704.38
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 87878.746 -999.000 8.147616 0.00313877 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown 8/21 13:30:00 87878.75 87783.83 8.147616 21.69 15.42 0.00850448 12.80 11.97 0.00850000 29.14 0.00882108 18.26 0.0000 21.11 0.00850448 53.7831 82035.80 0.00 89110.13 87408.23
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 30397.663 30397.663 1.329534 0.00026593 868.670 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 30397.66 30397.66 1.329534 21.11 14.32 0.00752391 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.11 0.00752391 47.6569 30397.98 0.00 32769.60 32769.60
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 58749.357 -999.000 5.052889 0.00209835 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 unknown 8/21 15:00:00 58749.36 54982.31 5.052889 21.69 15.66 0.00878368 12.80 11.97 0.00850000 29.40 0.00882150 18.34 0.0000 21.11 0.00878368 55.5264 50871.94 0.00 59541.70 54844.74
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 30479.297 30479.297 1.333104 0.00026665 871.003 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 30479.30 30479.30 1.333104 21.11 14.32 0.00752496 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.11 0.00752496 47.6634 30479.62 0.00 32857.61 32857.61
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 11956.415 -999.000 1.087461 0.00042705 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 unknown 8/21 10:00:00 11956.41 11746.66 1.087461 21.69 15.48 0.00857394 12.80 11.97 0.00850000 25.45 0.00881519 17.01 0.0000 21.11 0.00857394 54.2176 10948.80 0.00 12122.32 11701.80
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 5295.723 5295.723 0.231620 0.00004633 151.338 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5295.72 5295.72 0.231620 21.11 14.28 0.00748832 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.11 0.00748832 47.4352 5295.84 0.00 5708.92 5708.92
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 10859.931 -999.000 0.985723 0.00038788 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 09:00:00 unknown 8/21 09:00:00 10859.93 10650.62 0.985723 21.69 15.49 0.00858138 12.80 11.97 0.00850000 23.68 0.00881240 16.40 0.0000 21.11 0.00858138 54.2641 9924.47 0.00 11010.47 10610.46
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 5299.269 5299.269 0.231775 0.00004636 151.439 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5299.27 5299.27 0.231775 21.11 14.28 0.00748866 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.11 0.00748866 47.4373 5299.38 0.00 5712.74 5712.74
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 12534.723 12534.723 0.801502 0.00010966 292.099 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 12534.72 12534.72 0.801502 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00759695 48.4425 8366.33 0.00 12601.67 12601.67
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 3482.092 -999.000 0.317627 0.00012437 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown 8/21 16:30:00 3482.09 3429.64 0.317627 21.69 15.47 0.00856333 12.80 11.97 0.00850000 28.36 0.00881983 18.00 0.0000 21.11 0.00856333 54.1515 3197.94 0.00 3530.48 3416.30
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 1612.096 1612.096 0.070509 0.00001410 46.067 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1612.10 1612.10 0.070509 21.11 14.36 0.00757234 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.11 0.00757234 47.9610 1612.13 0.00 1737.88 1737.88
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 3112.276 -999.000 0.283286 0.00011116 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown 8/21 17:00:00 3112.28 3059.71 0.283286 21.69 15.48 0.00857113 12.80 11.97 0.00850000 27.94 0.00881916 17.86 0.0000 21.11 0.00857113 54.2001 2852.18 0.00 3155.48 3047.97
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 1613.933 1613.933 0.070589 0.00001412 46.120 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1613.93 1613.93 0.070589 21.11 14.36 0.00757282 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.11 0.00757282 47.9640 1613.97 0.00 1739.86 1739.86
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 19025.548 -999.000 1.717406 0.00067954 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 unknown 8/21 13:40:00 19025.55 18569.76 1.717406 21.69 15.50 0.00860163 12.80 11.97 0.00850000 29.23 0.00882122 18.29 0.0000 21.11 0.00860163 54.3910 17290.84 0.00 19288.53 18502.19
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 7727.532 7727.532 0.337983 0.00006760 220.820 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 7727.53 7727.53 0.337983 21.11 14.38 0.00758787 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.11 0.00758787 48.0578 7727.66 0.00 8330.48 8330.48
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10868.621 10868.621 1.086282 0.00009508 238.093 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 10868.62 10868.62 1.086282 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00766908 48.8972 5218.58 0.00 10928.77 10928.77
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 11250.597 11250.597 1.137952 0.00009843 246.152 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:20:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:20:00 11250.60 11250.60 1.137952 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00767570 48.9398 5332.15 0.00 11312.88 11312.88
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 7546.411 7546.411 1.164263 0.00006602 159.397 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 23:30:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 23:30:00 7546.41 7546.41 1.164263 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00584870 37.4067 1515.68 0.00 7588.63 7588.63
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 7589.304 7589.304 0.412690 0.00006639 182.601 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:30:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:30:00 7589.30 7589.30 0.412690 16.70 13.06 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00771919 49.2132 5442.67 0.00 7628.95 7628.95
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 484932.302 -999.000 22.785223 0.01732066 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 484932.30 435121.29 22.785223 26.76 17.78 0.00920444 10.95 10.95 0.00850000 29.40 0.00882150 18.34 51.1799 23.99 0.00956873 50.7107 308783.50 0.00 490131.37 419384.14
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 170401.388 170401.388 6.835567 0.00149075 2909.131 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 170401.39 170401.39 6.835567 -4.20 -4.20 0.00269032 16.70 13.06 0.00800000 -4.20 0.00269032 -4.20 170.5997 21.22 0.00652056 41.1005 52122.17 0.00 156987.14 156987.14
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 45447.837 -999.000 2.051317 0.00162329 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 45447.84 43504.21 2.051317 29.40 18.34 0.00882150 11.92 11.61 0.00850000 29.40 0.00882150 18.34 99.9965 21.11 0.00861245 54.4574 186702.93 0.00 45923.42 42707.30
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 15340.965 15340.965 0.615395 0.00013421 261.904 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 15340.96 15340.96 0.615395 -4.20 -4.20 0.00269032 16.70 13.06 0.00800000 -4.20 0.00269032 -4.20 333.3216 21.11 0.00752475 47.6621 93006.31 0.00 14133.30 14133.30



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 6854.952 6854.952 1.317077 0.00005997 142.948 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 1.7141 1.748587 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6854.95 6854.95 1.0000 1.56335869 1.317077 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.05996400 60.00 32.22 27.78 0.000 6854.95 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 50.9797 0.00 0.00 6893.48 6893.48 1.56335869 16.60 13.15 0.00800000 36934.7 20.92 14.82 0.00800000 41344.1
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 3585.894 3585.894 0.243797 0.00003137 82.685 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 0.8967 0.914703 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3585.89 3585.89 1.0000 0.28938505 0.243797 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.03136776 60.00 32.22 27.78 0.000 3585.89 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00749309 21.00 0.00749309 47.7895 2318.35 0.00 3605.11 3605.11 0.28938505 16.60 13.15 0.00800000 36934.7 28.82 17.64 0.00800000 49392.6
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1408.906 1408.906 0.122984 0.00001233 31.343 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 0.3523 0.359389 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1408.91 1408.91 1.0000 0.14598145 0.122984 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.01232447 60.00 32.22 27.78 0.000 1408.91 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00741935 21.00 0.00741935 47.3237 769.52 0.00 1416.56 1416.56 0.14598145 16.60 13.15 0.00800000 36934.7 26.12 16.71 0.00800000 46638.4
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 2014.086 2014.086 0.111975 0.00001762 48.229 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 0.5036 0.513761 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2014.09 2014.09 1.0000 0.13291296 0.111975 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.01761831 60.00 32.22 27.78 0.000 2014.09 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00728366 21.00 0.00728366 46.4683 1432.08 0.00 2024.63 2024.63 0.13291296 16.60 13.15 0.00800000 36934.7 31.54 18.55 0.00800000 52167.5
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1159.542 1159.542 0.053954 0.00001014 28.972 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 0.2899 0.295780 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1159.54 1159.54 1.0000 0.06404242 0.053954 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.01014314 60.00 32.22 27.78 0.000 1159.54 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00732126 21.00 0.00732126 46.7054 879.09 0.00 1165.52 1165.52 0.06404242 16.60 13.15 0.00800000 36934.7 34.45 19.48 0.00800000 55133.9
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 10616.370 10616.370 1.679003 0.00009288 223.882 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 2.6546 2.708063 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 10616.37 10616.37 1.0000 1.99296164 1.679003 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.09286716 60.00 32.22 27.78 0.000 10616.37 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00726278 21.00 0.00726278 46.3376 1890.62 0.00 10675.80 10675.80 1.99296164 16.60 13.15 0.00800000 36934.7 21.85 15.17 0.00800000 42291.5
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 10711.652 10711.652 0.940067 0.00009371 238.136 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 2.6785 2.732368 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 10711.65 10711.65 1.0000 1.11585050 0.940067 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.09370065 60.00 32.22 27.78 0.000 10711.65 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00754874 21.00 0.00754874 48.1398 5823.45 0.00 10769.83 10769.83 1.11585050 16.60 13.15 0.00800000 36934.7 26.07 16.69 0.00800000 46586.4
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 27139.733 27139.733 2.589003 0.00023743 597.494 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 6.7863 6.922904 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 27139.73 27139.73 1.0000 3.07312256 2.589003 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.23740601 60.00 32.22 27.78 0.000 27139.73 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00746084 21.00 0.00746084 47.5852 13678.68 0.00 27287.71 27287.71 3.07312256 16.60 13.15 0.00800000 36934.7 25.31 16.42 0.00800000 45814.2
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 13348.290 -999.000 1.216678 0.00047676 -999.000 -999.0000 1.00000 1.00000 1020.7639 1004.8586 1.1870 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.216678 1.44418548   4197.9300 999.8980 26.81473915 13.37 6.70 6.67 750817.87 1.7778 1.777800 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown unknown unknown 8/21 16:30:00 Sensible 13348.29 13138.63 1.0000 1.44418548 1.216678 21.69 15.47 0.00856608 43565.0 12.80 11.97 0.00850000 34322.2 0.47671244 6.70 13.37 6.67 0.000 13348.29 28.36 0.00881983 18.00 0.00000000 0.0000 21.11 0.00856608 21.11 0.00856608 54.1686 12249.79 0.00 13533.71 13087.78 1.44418548 21.69 15.62 0.00856608 43565.0 12.81 12.05 0.00844377 34193.8
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 5287.972 5287.972 0.231281 0.00004626 151.116 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.216678 1.44418548   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 1.3223 1.348876 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5287.97 5287.97 1.0000 0.27452838 0.231281 21.11 14.28 0.00748764 40232.5 40.00 21.01 0.00800000 60796.0 0.04625677 60.00 32.22 27.78 0.000 5287.97 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.11 0.00748764 21.11 0.00748764 47.4309 5288.09 0.00 5700.56 5700.56 0.27452838 16.60 12.65 0.00748764 35637.5 36.98 19.89 0.00748764 56402.5
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 12029.196 -999.000 1.094323 0.00042965 -999.000 -999.0000 1.00000 1.00000 1020.7770 1004.8586 1.1870 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.094323 1.29895158   4197.9300 999.8980 26.81473915 13.37 6.70 6.67 750817.87 1.6021 1.602116 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 unknown unknown unknown 8/21 16:50:00 Sensible 12029.20 11820.43 1.0000 1.29895158 1.094323 21.69 15.48 0.00857313 43582.9 12.80 11.97 0.00850000 34322.2 0.42960316 6.70 13.37 6.67 0.000 12029.20 28.08 0.00881938 17.91 0.00000000 0.0000 21.11 0.00857313 21.11 0.00857313 54.2126 11017.88 0.00 12196.13 11775.23 1.29895158 21.69 15.62 0.00857313 43582.9 12.81 12.05 0.00844479 34193.7
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 5291.519 5291.519 0.231436 0.00004629 151.218 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.094323 1.29895158   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 1.3232 1.349780 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5291.52 5291.52 1.0000 0.27471253 0.231436 21.11 14.28 0.00748799 40233.4 40.00 21.01 0.00800000 60796.0 0.04628780 60.00 32.22 27.78 0.000 5291.52 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.11 0.00748799 21.11 0.00748799 47.4331 5291.63 0.00 5704.38 5704.38 0.27471253 16.60 12.65 0.00748799 35638.4 36.98 19.89 0.00748799 56403.3
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 87878.746 -999.000 8.147616 0.00313877 -999.000 -999.0000 1.00000 1.00000 1020.6494 1004.8586 1.1870 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 8.147616 9.67114501   4197.9300 999.8980 26.81473915 13.37 6.70 6.67 750817.87 11.7044 11.704184 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown unknown unknown 8/21 13:30:00 Sensible 87878.75 87783.83 1.0000 9.67114501 8.147616 21.69 15.42 0.00850448 43408.9 12.80 11.97 0.00850000 34322.2 3.13844638 6.70 13.37 6.67 0.000 87878.75 29.14 0.00882108 18.26 0.00000000 0.0000 21.11 0.00850448 21.11 0.00850448 53.7831 82035.80 0.00 89110.13 87408.23 9.67114501 21.69 15.56 0.00850448 43408.9 12.84 12.05 0.00843478 34194.9
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 30397.663 30397.663 1.329534 0.00026593 868.670 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 8.147616 9.67114501   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 7.6010 7.753949 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 30397.66 30397.66 1.0000 1.57814422 1.329534 21.11 14.32 0.00752391 40325.0 40.00 21.01 0.00800000 60796.0 0.26590489 60.00 32.22 27.78 0.000 30397.66 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.11 0.00752391 21.11 0.00752391 47.6569 30397.98 0.00 32769.60 32769.60 1.57814422 16.60 12.69 0.00752391 35729.4 36.98 19.91 0.00752391 56494.0
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 58749.357 -999.000 5.052889 0.00209835 -999.000 -999.0000 1.00000 1.00000 1021.1684 1004.8586 1.1870 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.052889 5.99773249   4197.9300 999.8980 26.81473915 13.37 6.70 6.67 750817.87 7.8247 7.824569 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 unknown unknown unknown 8/21 15:00:00 Sensible 58749.36 54982.31 1.0000 5.99773249 5.052889 21.69 15.66 0.00878368 44117.5 12.80 11.97 0.00850000 34322.2 2.09813766 6.70 13.37 6.67 0.000 58749.36 29.40 0.00882150 18.34 0.00000000 0.0000 21.11 0.00878368 21.11 0.00878368 55.5264 50871.94 0.00 59541.70 54844.74 5.99773249 21.69 15.81 0.00878368 44117.5 12.74 12.05 0.00847349 34190.1
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 30479.297 30479.297 1.333104 0.00026665 871.003 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.052889 5.99773249   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 7.6214 7.774773 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 30479.30 30479.30 1.0000 1.58238238 1.333104 21.11 14.32 0.00752496 40327.6 40.00 21.01 0.00800000 60796.0 0.26661898 60.00 32.22 27.78 0.000 30479.30 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.11 0.00752496 21.11 0.00752496 47.6634 30479.62 0.00 32857.61 32857.61 1.58238238 16.60 12.69 0.00752496 35732.0 36.98 19.91 0.00752496 56496.7
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 11956.415 -999.000 1.087461 0.00042705 -999.000 -999.0000 1.00000 1.00000 1020.7785 1004.8586 1.1870 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.087461 1.29080631   4197.9300 999.8980 26.81473915 13.37 6.70 6.67 750817.87 1.5925 1.592422 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 unknown unknown unknown 8/21 10:00:00 Sensible 11956.41 11746.66 1.0000 1.29080631 1.087461 21.69 15.48 0.00857394 43584.9 12.80 11.97 0.00850000 34322.2 0.42700390 6.70 13.37 6.67 0.000 11956.41 25.45 0.00881519 17.01 0.00000000 0.0000 21.11 0.00857394 21.11 0.00857394 54.2176 10948.80 0.00 12122.32 11701.80 1.29080631 21.69 15.62 0.00857394 43584.9 12.81 12.05 0.00844490 34193.7
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 5295.723 5295.723 0.231620 0.00004633 151.338 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.087461 1.29080631   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 1.3242 1.350853 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5295.72 5295.72 1.0000 0.27493076 0.231620 21.11 14.28 0.00748832 40234.2 40.00 21.01 0.00800000 60796.0 0.04632457 60.00 32.22 27.78 0.000 5295.72 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.11 0.00748832 21.11 0.00748832 47.4352 5295.84 0.00 5708.92 5708.92 0.27493076 16.60 12.65 0.00748832 35639.3 36.98 19.89 0.00748832 56404.2
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 10859.931 -999.000 0.985723 0.00038788 -999.000 -999.0000 1.00000 1.00000 1020.7924 1004.8586 1.1870 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.985723 1.17004415   4197.9300 999.8980 26.81473915 13.37 6.70 6.67 750817.87 1.4464 1.446387 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 09:00:00 unknown unknown unknown 8/21 09:00:00 Sensible 10859.93 10650.62 1.0000 1.17004415 0.985723 21.69 15.49 0.00858138 43603.8 12.80 11.97 0.00850000 34322.2 0.38784477 6.70 13.37 6.67 0.000 10859.93 23.68 0.00881240 16.40 0.00000000 0.0000 21.11 0.00858138 21.11 0.00858138 54.2641 9924.47 0.00 11010.47 10610.46 1.17004415 21.69 15.63 0.00858138 43603.8 12.81 12.05 0.00844597 34193.5
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 5299.269 5299.269 0.231775 0.00004636 151.439 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.985723 1.17004415   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 1.3251 1.351757 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5299.27 5299.27 1.0000 0.27511484 0.231775 21.11 14.28 0.00748866 40235.1 40.00 21.01 0.00800000 60796.0 0.04635558 60.00 32.22 27.78 0.000 5299.27 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.11 0.00748866 21.11 0.00748866 47.4373 5299.38 0.00 5712.74 5712.74 0.27511484 16.60 12.65 0.00748866 35640.1 36.98 19.89 0.00748866 56405.1
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 12534.723 12534.723 0.801502 0.00010966 292.099 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 3.1343 3.197404 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 12534.72 12534.72 1.0000 0.95137512 0.801502 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.10964804 60.00 32.22 27.78 0.000 12534.72 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00759695 21.00 0.00759695 48.4425 8366.33 0.00 12601.67 12601.67 0.95137512 16.60 13.15 0.00800000 36934.7 29.59 17.90 0.00800000 50180.5
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 3482.092 -999.000 0.317627 0.00012437 -999.000 -999.0000 1.00000 1.00000 1020.7588 1004.8586 1.1870 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.317627 0.37702051   4197.9300 999.8980 26.81473915 13.37 6.70 6.67 750817.87 0.4638 0.463765 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown unknown unknown 8/21 16:30:00 Sensible 3482.09 3429.64 1.0000 0.37702051 0.317627 21.69 15.47 0.00856333 43558.0 12.80 11.97 0.00850000 34322.2 0.12435726 6.70 13.37 6.67 0.000 3482.09 28.36 0.00881983 18.00 0.00000000 0.0000 21.11 0.00856333 21.11 0.00856333 54.1515 3197.94 0.00 3530.48 3416.30 0.37702051 21.69 15.61 0.00856333 43558.0 12.81 12.05 0.00844338 34193.9
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 1612.096 1612.096 0.070509 0.00001410 46.067 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.317627 0.37702051   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 0.4031 0.411220 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1612.10 1612.10 1.0000 0.08369298 0.070509 21.11 14.36 0.00757234 40447.6 40.00 21.01 0.00800000 60796.0 0.01410188 60.00 32.22 27.78 0.000 1612.10 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.11 0.00757234 21.11 0.00757234 47.9610 1612.13 0.00 1737.88 1737.88 0.08369298 16.60 12.73 0.00757234 35852.0 36.98 19.95 0.00757234 56616.9
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 3112.276 -999.000 0.283286 0.00011116 -999.000 -999.0000 1.00000 1.00000 1020.7733 1004.8586 1.1870 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.283286 0.33625748   4197.9300 999.8980 26.81473915 13.37 6.70 6.67 750817.87 0.4145 0.414510 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown unknown unknown 8/21 17:00:00 Sensible 3112.28 3059.71 1.0000 0.33625748 0.283286 21.69 15.48 0.00857113 43577.8 12.80 11.97 0.00850000 34322.2 0.11114987 6.70 13.37 6.67 0.000 3112.28 27.94 0.00881916 17.86 0.00000000 0.0000 21.11 0.00857113 21.11 0.00857113 54.2001 2852.18 0.00 3155.48 3047.97 0.33625748 21.69 15.62 0.00857113 43577.8 12.81 12.05 0.00844450 34193.7
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 1613.933 1613.933 0.070589 0.00001412 46.120 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.283286 0.33625748   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 0.4036 0.411688 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1613.93 1613.93 1.0000 0.08378836 0.070589 21.11 14.36 0.00757282 40448.8 40.00 21.01 0.00800000 60796.0 0.01411795 60.00 32.22 27.78 0.000 1613.93 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.11 0.00757282 21.11 0.00757282 47.9640 1613.97 0.00 1739.86 1739.86 0.08378836 16.60 12.73 0.00757282 35853.2 36.98 19.95 0.00757282 56618.1
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 19025.548 -999.000 1.717406 0.00067954 -999.000 -999.0000 1.00000 1.00000 1020.8300 1004.8586 1.1870 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.717406 2.03854549   4197.9300 999.8980 26.81473915 13.37 6.70 6.67 750817.87 2.5340 2.533929 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 unknown unknown unknown 8/21 13:40:00 Sensible 19025.55 18569.76 1.0000 2.03854549 1.717406 21.69 15.50 0.00860163 43655.1 12.80 11.97 0.00850000 34322.2 0.67946649 6.70 13.37 6.67 0.000 19025.55 29.23 0.00882122 18.29 0.00000000 0.0000 21.11 0.00860163 21.11 0.00860163 54.3910 17290.84 0.00 19288.53 18502.19 2.03854549 21.69 15.65 0.00860163 43655.1 12.80 12.05 0.00844885 34193.2
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 7727.532 7727.532 0.337983 0.00006760 220.820 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.717406 2.03854549   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 1.9323 1.971168 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 7727.53 7727.53 1.0000 0.40118236 0.337983 21.11 14.38 0.00758787 40487.2 40.00 21.01 0.00800000 60796.0 0.06759693 60.00 32.22 27.78 0.000 7727.53 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.11 0.00758787 21.11 0.00758787 48.0578 7727.66 0.00 8330.48 8330.48 0.40118236 16.60 12.75 0.00758787 35891.3 36.98 19.96 0.00758787 56656.1
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 10868.621 10868.621 1.086282 0.00009508 238.093 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 2.7177 2.772408 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 10868.62 10868.62 1.0000 1.28940708 1.086282 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.09507374 60.00 32.22 27.78 0.000 10868.62 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00766908 21.00 0.00766908 48.8972 5218.58 0.00 10928.77 10928.77 1.28940708 16.60 13.15 0.00800000 36934.7 24.91 16.28 0.00800000 45410.5
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 11250.597 11250.597 1.137952 0.00009843 246.152 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 2.8132 2.869844 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:20:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:20:00 Sensible 11250.60 11250.60 1.0000 1.35073840 1.137952 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.09841509 60.00 32.22 27.78 0.000 11250.60 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00767570 21.00 0.00767570 48.9398 5332.15 0.00 11312.88 11312.88 1.35073840 16.60 13.15 0.00800000 36934.7 24.81 16.25 0.00800000 45310.1
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 7546.411 7546.411 1.164263 0.00006602 159.397 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 1.8870 1.924967 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 23:30:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 23:30:00 Sensible 7546.41 7546.41 1.0000 1.38196946 1.164263 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.06601256 60.00 32.22 27.78 0.000 7546.41 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.32 0.00584870 21.00 0.00584870 37.4067 1515.68 0.00 7588.63 7588.63 1.38196946 16.60 13.15 0.00800000 36934.7 21.99 15.22 0.00800000 42425.9
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 7589.304 7589.304 0.412690 0.00006639 182.601 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 1.8977 1.935908 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:30:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 19:30:00 Sensible 7589.30 7589.30 1.0000 0.48985867 0.412690 16.70 13.06 0.00800000 37036.7 40.00 21.01 0.00800000 60796.0 0.06638777 60.00 32.22 27.78 0.000 7589.30 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00771919 21.00 0.00771919 49.2132 5442.67 0.00 7628.95 7628.95 0.48985867 16.60 13.15 0.00800000 36934.7 31.87 18.66 0.00800000 52508.5
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 484932.302 -999.000 22.785223 0.01732066 -999.000 -999.0000 1.00000 1.00000 1021.9506 1004.8586 1.1870 VAV WITH REHEAT FAN Fan:VariableVolume 22.785223 27.04585022   4197.9300 999.8980 26.81473915 13.37 6.70 6.67 750817.87 64.5872 64.587208 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 Sensible 484932.30 435121.29 1.0000 27.04585022 22.785223 26.76 17.78 0.00920444 50367.0 10.95 10.95 0.00850000 32437.0 17.31889136 6.70 13.37 6.67 51053.451 433878.85 29.40 0.00882150 18.34 11.66146000 51.1799 23.99 0.00960627 23.99 0.00956873 50.7107 308783.50 0.00 490131.37 419384.14 27.04585022 26.76 17.93 0.00920444 50367.0 11.59 11.25 0.00816743 32244.7
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 170401.388 170401.388 6.835567 0.00149075 2909.131 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 VAV WITH REHEAT FAN Fan:VariableVolume 22.785223 27.04585022   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 42.6091 43.466621 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 170401.39 170401.39 1.0000 8.11375507 6.835567 -4.20 -4.20 0.00269032 2487.0 16.70 13.06 0.00800000 37036.7 1.49059361 60.00 32.22 27.78 0.000 170401.39 -4.20 0.00269032 -4.20 11.66146000 170.5997 18.50 0.00690725 21.22 0.00652056 41.1005 52122.17 0.00 156987.14 156987.14 8.11375507 2.80 0.07 0.00269032 9555.9 21.96 9.93 0.00269032 28904.2
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 45447.837 -999.000 2.051317 0.00162329 -999.000 -999.0000 1.00000 1.00000 1021.2387 1004.8586 1.1870 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.43480905   4197.9300 999.8980 26.81473915 13.37 6.70 6.67 750817.87 6.0531 6.053111 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 Sensible 45447.84 43504.21 1.0000 2.43489466 2.051317 29.40 18.34 0.00882150 52086.5 11.92 11.61 0.00850000 33421.2 1.62312585 6.70 13.37 6.67 2195.006 43252.83 29.40 0.00882150 18.34 2.05124512 99.9965 21.11 0.00860799 21.11 0.00861245 54.4574 186702.93 0.00 45923.42 42707.30 2.43489466 29.40 18.50 0.00882150 52086.5 12.23 11.66 0.00829812 33225.9
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 15340.965 15340.965 0.615395 0.00013421 261.904 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.43480905   4197.9300 999.8980 3.42928341 54.44 82.22 27.78 399917.87 3.8360 3.913230 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 15340.96 15340.96 1.0000 0.73046840 0.615395 -4.20 -4.20 0.00269032 2487.0 16.70 13.06 0.00800000 37036.7 0.13419576 60.00 32.22 27.78 0.000 15340.96 -4.20 0.00269032 -4.20 2.05124512 333.3216 21.11 0.00752312 21.11 0.00752475 47.6621 93006.31 0.00 14133.30 14133.30 0.73046840 2.80 0.07 0.00269032 9555.9 21.96 9.93 0.00269032 28904.2



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 11.66 22.79 -      
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 147.67 6729.17 0.00
RETAIL_1_FLR_1 920.17 7946.67 414.50
RETAIL_2_FLR_1 444.33 7470.33 0.00
MECH_FLR_1 46.33 8504.17 14.33
STORAGE_FLR_1 34.17 8718.83 34.17
LAUNDRY_FLR_1 7425.50 3314.33 2746.67
CAFE_FLR_1 1269.50 6725.50 35.00
LOBBY_FLR_1 1469.17 5879.17 37.83
ROOM_1_FLR_3 1983.83 8396.50 1892.50
ROOM_2_FLR_3 2439.83 8573.00 2410.17
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 943.17 8760.00 943.17
ROOM_5_FLR_3 1914.83 8343.50 1882.83
ROOM_6_FLR_3 2328.33 8562.50 2321.00
CORRIDOR_FLR_3 20.00 8579.33 16.00
ROOM_1_FLR_6 2704.50 8319.83 2556.50
ROOM_2_FLR_6 3101.00 8524.17 3045.67
ROOM_3_MULT9_FLR_6 1352.00 8201.83 1204.83
BANQUET_FLR_6 4652.17 1692.33 40.33
DINING_FLR_6 5975.67 773.67 24.83
KITCHEN_FLR_6 8477.67 6280.33 6248.67
CORRIDOR_FLR_6 254.00 8160.83 36.50
Facility 8755.50 8760.00 7332.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 256.17 0.00 256.17
CAFE_FLR_1 0.00 0.33 0.00 0.33
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 5.83 0.00 5.83
ROOM_2_FLR_3 0.00 4.33 0.00 4.33
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.17 0.00 0.17
ROOM_5_FLR_3 0.00 4.83 0.00 4.83
ROOM_6_FLR_3 0.00 5.17 0.00 5.17
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 11.17 0.00 11.17
ROOM_2_FLR_6 0.00 8.50 0.00 8.50
ROOM_3_MULT9_FLR_6 0.00 2.50 0.00 2.50
BANQUET_FLR_6 0.00 36.67 0.00 36.67
DINING_FLR_6 0.00 51.67 0.00 51.67
KITCHEN_FLR_6 0.00 384.33 0.00 384.33
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 0.00 474.33 0.00 474.33
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.60 106.50 4826.41 0.950 0.000 0.000 0.000
RETAIL_1_FLR_1 6.26 10.83 265.76 3.123 0.138 0.000 0.000
RETAIL_2_FLR_1 7.25 12.54 307.76 1.367 0.046 0.000 0.000
MECH_FLR_1 1.53 2.65 650.80 0.583 0.051 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.486 0.051 0.000 0.000
LAUNDRY_FLR_1 4.86 8.40 309.22 21.559 0.148 0.000 0.000
CAFE_FLR_1 82.31 142.30 748.35 4.294 0.108 0.000 0.000
LOBBY_FLR_1 244.35 422.44 5183.56 1.726 0.045 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.473 0.179 0.000 0.042
ROOM_2_FLR_3 0.95 1.50 118.93 0.473 0.178 0.000 0.044
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.537 0.079 0.000 0.070
ROOM_5_FLR_3 0.95 1.50 118.94 0.473 0.179 0.000 0.042
ROOM_6_FLR_3 0.95 1.50 118.93 0.473 0.178 0.000 0.044
CORRIDOR_FLR_3 12.12 20.96 1186.91 0.572 0.022 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.473 0.179 0.000 0.049
ROOM_2_FLR_6 0.95 1.50 118.93 0.473 0.178 0.000 0.052
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.537 0.145 0.000 0.078
BANQUET_FLR_6 144.55 249.90 1010.89 4.448 0.052 0.000 0.000
DINING_FLR_6 144.55 249.90 1010.89 4.837 0.052 0.000 0.000
KITCHEN_FLR_6 12.86 22.24 314.87 20.376 0.149 0.000 0.000
CORRIDOR_FLR_6 12.83 22.18 1256.16 1.114 0.036 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.60 106.50 4826.41 0.576 0.000 0.000 0.000
RETAIL_1_FLR_1 6.26 10.83 265.76 1.819 0.002 0.000 0.000
RETAIL_2_FLR_1 7.25 12.54 307.76 0.797 0.001 0.000 0.000
MECH_FLR_1 1.53 2.65 650.80 0.341 0.001 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.284 0.001 0.000 0.000
LAUNDRY_FLR_1 4.86 8.40 309.22 11.972 0.002 0.000 0.000
CAFE_FLR_1 82.31 142.30 748.35 2.604 0.002 0.000 0.000
LOBBY_FLR_1 244.35 422.44 5183.56 1.125 0.001 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.457 0.003 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.457 0.003 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.521 0.001 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.457 0.003 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.457 0.003 0.000 0.000
CORRIDOR_FLR_3 12.12 20.96 1186.91 0.334 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.457 0.003 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.457 0.003 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.519 0.002 0.000 0.000
BANQUET_FLR_6 144.55 249.90 1010.89 2.437 0.001 0.000 0.000
DINING_FLR_6 144.55 249.90 1010.89 2.553 0.001 0.000 0.000
KITCHEN_FLR_6 12.86 22.24 314.87 8.392 0.002 0.000 0.000
CORRIDOR_FLR_6 12.83 22.18 1256.16 0.651 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.60 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.26 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.25 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.53 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.86 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.31 142.30 748.35 188.86 0.0000 0.676
LOBBY_FLR_1 VAV WITH REHEAT 244.35 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.12 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 144.55 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 144.55 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.86 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.83 22.18 1256.16 412.12 0.0000 0.126
Total Facility   870.81 1604.23 35184.81 11345.29 0.0000 137.584


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 39370954.07 0.00 39370954.07 0.00 39370954.07 26946214.98 4.16 0.83 8755.00 0.00
RETAIL_1_FLR_1 7180330.78 0.00 7180330.78 316459.92 7496790.69 2498216.28 0.00 0.00 8760.00 0.00
RETAIL_2_FLR_1 3623117.49 0.00 3623117.49 122153.93 3745271.41 2892943.94 169.42 64.62 8525.96 0.00
MECH_FLR_1 3277192.47 0.00 3277192.47 288699.32 3565891.78 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 1578060.25 0.00 1578060.25 166563.60 1744623.85 1821682.01 8760.00 0.00 0.00 0.00
LAUNDRY_FLR_1 57347697.70 0.00 57347697.70 394204.17 57741901.87 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 27689624.85 0.00 27689624.85 699552.56 28389177.41 21330615.53 120.48 27.31 8612.20 0.00
LOBBY_FLR_1 76869761.60 0.00 76869761.60 1998781.45 78868543.05 59728886.00 120.64 23.74 8615.62 0.00
ROOM_1_FLR_3 1946875.62 43454.58 1990330.19 183682.98 2174013.18 1946875.62 0.00 8064.33 695.67 0.00
ROOM_2_FLR_3 1946647.51 45579.52 1992227.03 183668.97 2175896.00 1946647.51 0.00 8064.33 695.67 0.00
ROOM_3_MULT19_FLR_3 26397887.27 47524.69 26445411.96 51249.61 26496661.57 26397887.27 0.00 8081.00 679.00 8760.00
ROOM_4_MULT19_FLR_3 26405105.73 45109.91 26450215.64 51263.63 26501479.26 26405105.73 0.00 8082.74 677.26 0.00
ROOM_5_FLR_3 1946875.62 43413.08 1990288.70 183682.98 2173971.68 1946875.62 0.00 8064.33 695.67 0.00
ROOM_6_FLR_3 1946647.51 45486.87 1992134.38 183668.97 2175803.35 1946647.51 0.00 8064.33 695.67 0.00
CORRIDOR_FLR_3 23442973.82 0.00 23442973.82 222109.68 23665083.51 14972100.18 1.96 0.39 8757.65 0.00
ROOM_1_FLR_6 486718.90 50743.43 537462.34 183721.42 721183.76 486718.90 0.00 8062.67 697.33 0.00
ROOM_2_FLR_6 486661.88 53684.82 540346.70 183707.41 724054.10 486661.88 0.00 8062.67 697.33 0.00
ROOM_3_MULT9_FLR_6 3126920.42 50631.63 3177552.04 93998.31 3271550.35 3126920.42 0.00 8062.83 697.17 0.00
BANQUET_FLR_6 38501713.57 0.00 38501713.57 448601.54 38950315.11 37458366.31 4544.13 328.06 3887.81 0.00
DINING_FLR_6 41858611.98 0.00 41858611.98 448601.54 42307213.52 37458366.31 3187.98 233.42 5338.60 0.00
KITCHEN_FLR_6 54947845.65 0.00 54947845.65 401602.39 55349448.04 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 12086103.84 0.00 12086103.84 393066.01 12479169.85 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.45E+10 8312078.39 0.45E+10 18509960.64 0.46E+10 0.43E+10 8760.00 8128.32 8760.00 8760.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.2484 0.0000 1.2484 0.0000 1.2484 0.8545 4.16 0.83 8755.00
RETAIL_1_FLR_1 0.2277 0.0000 0.2277 0.0100 0.2377 0.0792 0.00 0.00 8760.00
RETAIL_2_FLR_1 0.1149 0.0000 0.1149 0.0039 0.1188 0.0917 169.42 64.62 8525.96
MECH_FLR_1 0.1039 0.0000 0.1039 0.0092 0.1131 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0500 0.0000 0.0500 0.0053 0.0553 0.0578 8760.00 0.00 0.00
LAUNDRY_FLR_1 1.8185 0.0000 1.8185 0.0125 1.8310 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.8780 0.0000 0.8780 0.0222 0.9002 0.6764 120.48 27.31 8612.20
LOBBY_FLR_1 2.4375 0.0000 2.4375 0.0634 2.5009 1.8940 120.64 23.74 8615.62
ROOM_1_FLR_3 0.0617 0.0014 0.0631 0.0058 0.0689 0.0617 0.00 8064.33 695.67
ROOM_2_FLR_3 0.0617 0.0014 0.0632 0.0058 0.0690 0.0617 0.00 8064.33 695.67
ROOM_4_MULT19_FLR_3 0.8373 0.0014 0.8387 0.0016 0.8404 0.8373 0.00 8082.74 677.26
ROOM_5_FLR_3 0.0617 0.0014 0.0631 0.0058 0.0689 0.0617 0.00 8064.33 695.67
ROOM_6_FLR_3 0.0617 0.0014 0.0632 0.0058 0.0690 0.0617 0.00 8064.33 695.67
CORRIDOR_FLR_3 0.7434 0.0000 0.7434 0.0070 0.7504 0.4748 1.96 0.39 8757.65
ROOM_1_FLR_6 0.0154 0.0016 0.0170 0.0058 0.0229 0.0154 0.00 8062.67 697.33
ROOM_2_FLR_6 0.0154 0.0017 0.0171 0.0058 0.0230 0.0154 0.00 8062.67 697.33
ROOM_3_MULT9_FLR_6 0.0992 0.0016 0.1008 0.0030 0.1037 0.0992 0.00 8062.83 697.17
BANQUET_FLR_6 1.2209 0.0000 1.2209 0.0142 1.2351 1.1878 4544.13 328.06 3887.81
DINING_FLR_6 1.3273 0.0000 1.3273 0.0142 1.3416 1.1878 3187.98 233.42 5338.60
KITCHEN_FLR_6 1.7424 0.0000 1.7424 0.0127 1.7551 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.3832 0.0000 0.3832 0.0125 0.3957 0.1256 0.00 0.00 8760.00
Total Facility 80.0721 0.1490 80.2212 0.4634 80.6846 73.9670 8760.00 8128.32 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.55E+09 0.00 0.55E+09 0.22E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 91145268.87 425628.52 91570897.38 64690340.46 0.00 0.00 8760.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 17.3310 0.0000 17.3310 6.9969 0.00 0.00 8760.00
FLR_3_DOAS 2.8902 0.0135 2.9037 2.0513 0.00 0.00 8760.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 5048.63 3587.86 0.00 123.52 0.00 0.00 0.00 0.00 0.00
FLR_3_DOAS 0.00 7343.21 1416.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 16.4324 18.6337 0.0000 16.4979 0.0000 0.0000 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 2.8903 2.8918 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1318
Defaulted Fields 1181
Fields with Defaults 4005
Autosized Fields 350
Autosizable Fields 402
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 4844.08 75844.81 20-NOV-03:20 370048.64 10-AUG-19:30
Electricity:Building 2518.76 32511.05 01-JUL-05:00 151906.32 02-JAN-20:10
Electricity:Zone:BASEMENT 323.72 3705.45 02-JAN-02:10 24299.15 02-JAN-20:10
Electricity:SpaceType:GENERAL 2511.67 32369.91 01-JUL-05:00 151664.99 02-JAN-20:10
InteriorLights:Electricity 766.66 6678.11 01-JUL-05:00 62892.57 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 173.46 1576.23 02-JAN-02:10 14185.34 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 766.66 6678.11 01-JUL-05:00 62892.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity 766.66 6678.11 01-JUL-05:00 62892.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 173.46 1576.23 02-JAN-02:10 14185.34 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 766.66 6678.11 01-JUL-05:00 62892.57 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 18.80 222.61 02-JAN-02:10 1390.02 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.61 78.27 02-JAN-02:10 704.41 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.61 78.27 02-JAN-02:10 704.41 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 21.77 257.78 02-JAN-02:10 1609.65 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.97 90.64 02-JAN-02:10 815.72 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.97 90.64 02-JAN-02:10 815.72 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 29.11 327.88 02-JAN-02:10 2199.84 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 16.64 151.16 02-JAN-02:10 1360.40 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 16.64 151.16 02-JAN-02:10 1360.40 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 6.38 76.28 02-JAN-02:10 469.87 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.78 25.30 02-JAN-02:10 227.72 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.78 25.30 02-JAN-02:10 227.72 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 72.30 1002.39 02-JAN-02:10 4930.01 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.37 39.69 02-JAN-02:10 357.21 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.37 39.69 02-JAN-02:10 357.21 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 32.29 322.63 03-JUN-05:00 2727.18 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 17.95 119.42 03-JUN-05:00 1761.91 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 17.95 119.42 03-JUN-05:00 1761.91 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 270.92 3172.15 01-JUL-05:00 20294.39 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 121.92 1060.74 01-JUL-05:00 10265.18 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 121.92 1060.74 01-JUL-05:00 10265.18 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 18.66 264.62 01-JAN-02:10 1227.54 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 18.66 264.59 01-JAN-02:10 1227.39 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 304.77 4565.05 01-JAN-02:10 20923.25 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 76.02 643.59 01-JAN-02:10 5851.22 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 76.02 643.59 01-JAN-02:10 5851.22 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 304.86 4566.30 01-JAN-02:10 20928.98 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 76.04 643.77 01-JAN-02:10 5852.82 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 76.04 643.77 01-JAN-02:10 5852.82 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 18.66 264.62 01-JAN-02:10 1227.54 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 18.66 264.59 01-JAN-02:10 1227.39 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 4.66 66.15 01-JAN-02:10 306.88 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.59 13.47 01-JAN-02:10 122.50 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.59 13.47 01-JAN-02:10 122.50 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 4.66 66.15 01-JAN-02:10 306.85 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.59 13.47 01-JAN-02:10 122.49 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.59 13.47 01-JAN-02:10 122.49 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 36.10 540.75 01-JAN-02:10 2478.43 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 9.00 76.24 01-JAN-02:10 693.10 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 9.00 76.24 01-JAN-02:10 693.10 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 210.51 2524.33 13-MAY-05:00 9841.96 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 34.65 275.03 13-MAY-05:00 3094.06 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 34.65 275.03 13-MAY-05:00 3094.06 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 210.51 2524.33 13-MAY-05:00 9841.96 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 34.65 275.03 13-MAY-05:00 3094.06 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 34.65 275.03 13-MAY-05:00 3094.06 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 454.16 6253.02 02-JAN-02:10 18944.06 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.33 121.09 02-JAN-02:10 1089.83 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.33 121.09 02-JAN-02:10 1089.83 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
InteriorEquipment:Electricity 1745.01 25691.80 02-JAN-02:10 89475.41 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1745.01 25691.80 02-JAN-02:10 89475.41 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 433.74 5990.78 01-JAN-00:10 16487.34 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
Refrigeration:Electricity 62.09 1116.23 11-FEB-23:30 3445.44 31-MAR-06:20
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 694.17 2595.49 26-APR-02:30 157723.56 10-AUG-18:10
LowTempRefrigeration:Refrigeration:Electricity 20.50 0.00 01-JAN-11:10 2034.09 15-NOV-11:40
MedTempRefrigeration:Refrigeration:Electricity 34.50 973.22 19-FEB-04:10 1245.48 06-MAR-09:10
Fans:Electricity 543.37 12463.13 08-OCT-04:50 41298.23 31-JAN-22:50
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 769.85 13745.78 01-OCT-05:00 48340.39 07-FEB-20:40
ExteriorEquipment:Electricity 651.48 9618.58 02-JAN-02:20 39726.11 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 32.45 553.72 03-JUN-05:00 1868.65 25-JAN-21:10
ElectricityPurchased:Facility 4844.08 75844.81 20-NOV-03:20 370048.64 10-AUG-19:30
ElectricityPurchased:Plant 4844.08 75844.81 20-NOV-03:20 370048.64 10-AUG-19:30
Cogeneration:ElectricityPurchased 4844.08 75844.81 20-NOV-03:20 370048.64 10-AUG-19:30
General:Cogeneration:ElectricityPurchased 4844.08 75844.81 20-NOV-03:20 370048.64 10-AUG-19:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 4844.08 75844.81 20-NOV-03:20 370048.64 10-AUG-19:30
ElectricityNet:Plant 4844.08 75844.81 20-NOV-03:20 370048.64 10-AUG-19:30
Cogeneration:ElectricityNet 4844.08 75844.81 20-NOV-03:20 370048.64 10-AUG-19:30
General:Cogeneration:ElectricityNet 4844.08 75844.81 20-NOV-03:20 370048.64 10-AUG-19:30
General:Fans:Electricity 543.37 12463.13 08-OCT-04:50 41298.23 31-JAN-22:50
ExteriorLights:Electricity 242.27 0.00 01-JAN-08:10 15448.40 01-JAN-00:10
General:ExteriorLights:Electricity 242.27 0.00 01-JAN-08:10 15448.40 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.91 18.80 01-JAN-00:10 188.00 01-JAN-07:10
HeatRecovery:Electricity 194.02 0.00 25-FEB-11:40 9938.94 01-JAN-10:10
General:HeatRecovery:Electricity 194.02 0.00 25-FEB-11:40 9938.94 01-JAN-10:10
WaterSystems:Electricity 90.74 1086.57 13-SEP-00:30 4738.61 31-MAY-18:10
Water Heater:WaterSystems:Electricity 90.74 1086.57 13-SEP-00:30 4738.61 31-MAY-18:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 425.63 0.00 01-JAN-00:20 142582.39 10-AUG-18:10
General:Cooling:Electricity 425.63 0.00 01-JAN-00:20 142582.39 10-AUG-18:10
Pumps:Electricity 122.81 47.91 20-APR-10:10 8225.48 10-AUG-18:10
General:Pumps:Electricity 122.81 47.91 20-APR-10:10 8225.48 10-AUG-18:10
WIRED_LTG_ELECTRICITY 26.99 0.00 01-JAN-00:10 2213.82 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 5643.03 29270.80 28-APR-01:10 531360.57 22-JAN-18:50
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 3854.20 15908.90 14-MAY-10:10 440859.39 09-FEB-21:10
WaterSystems:NaturalGas 3155.64 15908.90 02-JAN-16:10 286457.09 20-APR-20:40
Water Heater:WaterSystems:NaturalGas 3155.64 15908.90 02-JAN-16:10 286457.09 20-APR-20:40
Heating:NaturalGas 698.56 0.00 06-FEB-13:30 186550.53 23-NOV-11:50
Boiler:Heating:NaturalGas 698.56 0.00 06-FEB-13:30 186550.53 23-NOV-11:50


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 1263.41 0.00 01-JAN-00:20 467046.88 10-AUG-18:10
PlantLoopCoolingDemand:HVAC 1263.41 0.00 01-JAN-00:20 467046.88 10-AUG-18:10
CoolingCoils:PlantLoopCoolingDemand 1263.41 0.00 01-JAN-00:20 467046.88 10-AUG-18:10


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 03-JAN-21:30
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 03-JAN-21:30
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 03-JAN-21:30
Water Heater:WaterSystems:Water 5742.51 0.00 03-JAN-01:50 0.00 02-JAN-19:10
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 03-JAN-21:30
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 03-JAN-21:30
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 03-JAN-21:30
Water Heater:WaterSystems:MainsWater 5742.51 0.00 03-JAN-01:50 0.00 02-JAN-19:10
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 02-JAN-07:30
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 02-JAN-07:30


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 13559.56 142647.47 11-JAN-14:40 2007522.18 10-AUG-18:10
EnergyTransfer:Building 4954.08 48904.71 16-MAR-09:40 343619.54 10-AUG-18:20
EnergyTransfer:Zone:KITCHEN_FLR_6 711.05 8188.30 22-APR-01:10 36359.89 13-AUG-10:40
Refrigeration:EnergyTransfer 184.02 4025.83 11-FEB-23:20 10656.68 31-MAR-06:20
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 92.01 2012.91 11-FEB-23:20 5328.34 31-MAR-06:20
General:Refrigeration:EnergyTransfer 92.01 2012.91 11-FEB-23:20 5328.34 31-MAR-06:20
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 92.01 2012.91 11-FEB-23:20 5328.34 31-MAR-06:20
EnergyTransfer:Plant 4509.93 14373.39 28-SEP-02:40 1126005.84 10-AUG-18:10
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.63 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 70.38 1869.65 19-FEB-04:10 2686.44 06-MAR-09:10
EnergyTransfer:Zone:BASEMENT 413.74 1701.82 16-MAR-09:40 23902.51 10-NOV-22:40
Heating:EnergyTransfer 122.91 0.00 01-JAN-08:50 74256.57 26-DEC-16:10
Heating:EnergyTransfer:Zone:BASEMENT 0.02 0.00 01-JAN-00:10 634.67 17-APR-07:50
General:Heating:EnergyTransfer 122.91 0.00 01-JAN-08:50 74256.57 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:BASEMENT 0.02 0.00 01-JAN-00:10 634.67 17-APR-07:50
Cooling:EnergyTransfer 4739.16 38468.48 16-MAR-09:40 340013.54 10-AUG-18:20
Cooling:EnergyTransfer:Zone:BASEMENT 413.72 1701.82 16-MAR-09:40 23902.51 10-NOV-22:40
General:Cooling:EnergyTransfer 4739.16 38468.48 16-MAR-09:40 340013.54 10-AUG-18:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 413.72 1701.82 16-MAR-09:40 23902.51 10-NOV-22:40
EnergyTransfer:Zone:RETAIL_1_FLR_1 40.44 0.02 19-DEC-06:50 4487.61 04-OCT-12:50
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.54 0.00 01-JAN-00:10 761.16 19-FEB-06:00
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.54 0.00 01-JAN-00:10 761.16 19-FEB-06:00
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 39.91 0.00 01-JAN-02:10 4487.61 04-OCT-12:50
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 39.91 0.00 01-JAN-02:10 4487.61 04-OCT-12:50
EnergyTransfer:Zone:RETAIL_2_FLR_1 33.90 22.51 16-MAR-09:40 2121.77 10-AUG-21:00
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.02 0.00 01-JAN-00:10 176.94 23-NOV-18:30
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.02 0.00 01-JAN-00:10 176.94 23-NOV-18:30
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 33.87 18.36 04-DEC-09:40 2121.77 10-AUG-21:00
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 33.87 18.36 04-DEC-09:40 2121.77 10-AUG-21:00
EnergyTransfer:Zone:MECH_FLR_1 27.18 0.43 26-DEC-14:00 1738.30 10-AUG-20:00
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.05 0.00 01-JAN-00:10 191.74 23-NOV-18:30
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.05 0.00 01-JAN-00:10 191.74 23-NOV-18:30
Cooling:EnergyTransfer:Zone:MECH_FLR_1 27.12 0.00 01-JAN-09:30 1738.30 10-AUG-20:00
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 27.12 0.00 01-JAN-09:30 1738.30 10-AUG-20:00
EnergyTransfer:Zone:STORAGE_FLR_1 11.88 0.03 14-FEB-15:20 676.97 10-AUG-10:40
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.07 0.00 01-JAN-00:10 166.69 16-JAN-17:00
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.07 0.00 01-JAN-00:10 166.69 16-JAN-17:00
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 11.81 0.00 01-JAN-09:30 676.97 10-AUG-10:40
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 11.81 0.00 01-JAN-09:30 676.97 10-AUG-10:40
EnergyTransfer:Zone:LAUNDRY_FLR_1 589.94 6147.27 20-MAY-03:40 38867.68 08-FEB-21:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.01 0.00 01-JAN-00:10 529.67 13-OCT-01:50
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.01 0.00 01-JAN-00:10 529.67 13-OCT-01:50
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 589.93 6147.27 20-MAY-03:40 38867.68 08-FEB-21:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 589.93 6147.27 20-MAY-03:40 38867.68 08-FEB-21:00
EnergyTransfer:Zone:CAFE_FLR_1 237.69 284.77 04-DEC-09:40 15597.68 04-OCT-12:50
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.20 0.00 01-JAN-00:10 1223.24 17-APR-07:50
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.20 0.00 01-JAN-00:10 1223.24 17-APR-07:50
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 237.49 0.00 16-MAR-09:40 15597.68 04-OCT-12:50
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 237.49 0.00 16-MAR-09:40 15597.68 04-OCT-12:50
EnergyTransfer:Zone:LOBBY_FLR_1 758.64 919.35 16-MAR-09:40 40992.29 10-AUG-21:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.19 0.00 01-JAN-00:10 3245.13 23-NOV-18:30
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.19 0.00 01-JAN-00:10 3245.13 23-NOV-18:30
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 758.45 919.35 16-MAR-09:40 40992.29 10-AUG-21:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 758.45 919.35 16-MAR-09:40 40992.29 10-AUG-21:10
EnergyTransfer:Zone:ROOM_1_FLR_3 53.47 0.00 08-FEB-21:10 12740.30 10-AUG-18:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 14.59 0.00 01-JAN-08:10 5154.96 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 14.59 0.00 01-JAN-08:10 5154.96 26-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 38.88 0.00 01-JAN-00:10 12740.30 10-AUG-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 38.88 0.00 01-JAN-00:10 12740.30 10-AUG-18:10
EnergyTransfer:Zone:ROOM_2_FLR_3 49.08 0.03 21-OCT-19:00 11970.38 10-AUG-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 17.81 0.00 01-JAN-08:10 5223.79 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 17.81 0.00 01-JAN-08:10 5223.79 26-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 31.27 0.00 01-JAN-00:10 11970.38 10-AUG-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 31.27 0.00 01-JAN-00:10 11970.38 10-AUG-18:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 335.98 0.69 22-FEB-03:30 63432.77 04-OCT-12:30
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 7.76 0.00 01-JAN-07:50 12428.21 19-FEB-06:00
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 7.76 0.00 01-JAN-07:50 12428.21 19-FEB-06:00
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 328.23 0.00 01-JAN-00:10 63432.77 04-OCT-12:30
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 328.23 0.00 01-JAN-00:10 63432.77 04-OCT-12:30
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 321.87 0.95 10-NOV-23:40 57332.03 24-JUL-18:20
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 22.43 0.00 01-JAN-07:10 33434.37 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 22.43 0.00 01-JAN-07:10 33434.37 26-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 299.44 0.00 01-JAN-00:10 57332.03 24-JUL-18:20
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 299.44 0.00 01-JAN-00:10 57332.03 24-JUL-18:20
EnergyTransfer:Zone:ROOM_5_FLR_3 51.85 0.04 07-DEC-15:20 10817.29 10-AUG-08:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 14.64 0.00 01-JAN-08:10 5147.71 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 14.64 0.00 01-JAN-08:10 5147.71 26-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 37.22 0.00 01-JAN-00:10 10817.29 10-AUG-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 37.22 0.00 01-JAN-00:10 10817.29 10-AUG-08:10
EnergyTransfer:Zone:ROOM_6_FLR_3 46.93 0.09 31-DEC-13:30 10263.25 10-AUG-08:10
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 17.75 0.00 01-JAN-08:10 5220.19 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 17.75 0.00 01-JAN-08:10 5220.19 26-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 29.18 0.00 01-JAN-00:10 10263.25 10-AUG-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 29.18 0.00 01-JAN-00:10 10263.25 10-AUG-08:10
EnergyTransfer:Zone:CORRIDOR_FLR_3 182.07 0.37 30-NOV-15:40 10325.62 13-AUG-10:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.56 0.00 01-JAN-00:10 1608.22 04-DEC-09:40
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.56 0.00 01-JAN-00:10 1608.22 04-DEC-09:40
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 181.51 0.00 01-JAN-09:30 10325.62 13-AUG-10:40
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 181.51 0.00 01-JAN-09:30 10325.62 13-AUG-10:40
EnergyTransfer:Zone:ROOM_1_FLR_6 15.10 0.00 13-MAR-19:40 3449.97 10-AUG-18:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 5.84 0.00 01-JAN-08:10 1672.36 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 5.84 0.00 01-JAN-08:10 1672.36 26-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 9.26 0.00 01-JAN-00:10 3449.97 10-AUG-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 9.26 0.00 01-JAN-00:10 3449.97 10-AUG-18:10
EnergyTransfer:Zone:ROOM_2_FLR_6 14.24 0.01 29-JAN-15:00 3150.65 10-AUG-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 6.96 0.00 01-JAN-08:10 1684.35 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 6.96 0.00 01-JAN-08:10 1684.35 26-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 7.28 0.00 01-JAN-00:10 3150.65 10-AUG-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 7.28 0.00 01-JAN-00:10 3150.65 10-AUG-18:10
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 78.89 0.11 16-NOV-00:40 18355.28 14-SEP-15:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 13.17 0.00 01-JAN-08:10 7512.25 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 13.17 0.00 01-JAN-08:10 7512.25 26-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 65.72 0.00 01-JAN-00:10 18355.28 14-SEP-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 65.72 0.00 01-JAN-00:10 18355.28 14-SEP-15:10
EnergyTransfer:Zone:BANQUET_FLR_6 423.27 2131.20 04-DEC-09:40 22656.86 17-APR-22:00
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 166.40 03-MAR-01:00
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 166.40 03-MAR-01:00
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 423.27 2131.20 04-DEC-09:40 22656.86 17-APR-22:00
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 423.27 2131.20 04-DEC-09:40 22656.86 17-APR-22:00
EnergyTransfer:Zone:DINING_FLR_6 465.41 3047.92 04-DEC-09:40 23704.66 24-JUL-21:20
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 58.67 03-MAR-01:00
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 58.67 03-MAR-01:00
Cooling:EnergyTransfer:Zone:DINING_FLR_6 465.41 3047.92 04-DEC-09:40 23704.66 24-JUL-21:20
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 465.41 3047.92 04-DEC-09:40 23704.66 24-JUL-21:20
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 17.15 13-OCT-01:50
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 17.15 13-OCT-01:50
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 619.04 6005.18 22-APR-01:10 31272.16 13-AUG-10:40
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 619.04 6005.18 22-APR-01:10 31272.16 13-AUG-10:40
EnergyTransfer:Zone:CORRIDOR_FLR_6 91.45 2.24 08-JAN-03:20 6834.73 10-AUG-14:20
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.31 0.00 01-JAN-00:10 763.54 19-FEB-06:00
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.31 0.00 01-JAN-00:10 763.54 19-FEB-06:00
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 91.14 0.00 01-JAN-09:30 6834.73 10-AUG-14:20
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 91.14 0.00 01-JAN-09:30 6834.73 10-AUG-14:20
PlantLoopHeatingDemand:Facility 1260.77 9491.03 11-AUG-01:50 191112.97 24-JAN-07:20
PlantLoopHeatingDemand:Plant 764.25 9491.03 11-AUG-01:50 54598.14 09-FEB-07:40
WaterSystems:PlantLoopHeatingDemand 764.25 9491.03 11-AUG-01:50 54598.14 09-FEB-07:40
General:WaterSystems:PlantLoopHeatingDemand 764.25 9491.03 11-AUG-01:50 54598.14 09-FEB-07:40
EnergyTransfer:HVAC 4095.55 130.15 21-OCT-13:40 539197.22 10-AUG-18:10
HeatingCoils:EnergyTransfer 496.52 0.00 07-FEB-15:10 154696.00 26-JAN-16:20
PlantLoopHeatingDemand:HVAC 496.52 0.00 07-FEB-15:10 154696.00 26-JAN-16:20
HeatingCoils:PlantLoopHeatingDemand 496.52 0.00 07-FEB-15:10 154696.00 26-JAN-16:20
CoolingCoils:EnergyTransfer 1263.41 0.00 01-JAN-00:20 467046.88 10-AUG-18:10
HeatRecoveryForHeating:EnergyTransfer 2317.58 0.00 25-FEB-11:40 384704.88 19-FEB-06:30
HeatRecoveryForCooling:EnergyTransfer 18.04 0.00 01-JAN-00:10 85760.12 29-AUG-13:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 764.25 9491.03 11-AUG-01:50 54598.14 09-FEB-07:40
WaterUse:WaterSystems:EnergyTransfer 764.25 9491.03 11-AUG-01:50 54598.14 09-FEB-07:40
Boilers:EnergyTransfer 490.58 0.00 06-FEB-13:30 146683.08 26-JAN-16:20
Chillers:EnergyTransfer 1368.73 0.00 01-JAN-00:20 474720.90 10-AUG-18:10
HeatRejection:EnergyTransfer 1794.36 0.00 01-JAN-00:20 617303.29 10-AUG-18:10
General:HeatRejection:EnergyTransfer 1794.36 0.00 01-JAN-00:20 617303.29 10-AUG-18:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.017 -413.724 0.000 0.000 137.851 173.462 150.255 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -47.860
RETAIL_1_FLR_1 0.000 0.000 0.539 -39.906 0.000 0.000 15.894 8.614 10.186 23.204 0.000 0.030 0.000 0.000 -10.068 0.000 -3.972 -4.520
RETAIL_2_FLR_1 0.000 0.000 0.021 -33.875 0.000 0.000 17.033 9.975 11.795 0.000 0.000 0.011 0.000 0.000 0.000 0.000 -1.700 -3.260
MECH_FLR_1 0.000 0.000 0.054 -27.123 0.000 0.000 3.731 16.635 12.471 0.000 0.000 0.029 0.000 0.000 0.000 0.000 -3.839 -1.958
STORAGE_FLR_1 0.000 0.000 0.069 -11.815 0.000 0.000 2.907 2.785 3.598 0.000 0.000 0.018 4.612 0.000 0.000 0.000 -2.174 -0.000
LAUNDRY_FLR_1 0.000 0.000 0.009 -589.931 0.000 0.000 11.193 4.368 658.131 0.000 0.000 0.042 0.000 0.000 0.000 0.000 -5.747 -78.065
CAFE_FLR_1 0.000 0.000 0.201 -237.491 0.000 0.000 197.654 17.947 14.341 64.408 0.000 0.058 0.000 0.000 -30.235 0.000 -9.434 -17.448
LOBBY_FLR_1 0.000 0.000 0.191 -758.456 0.000 0.000 558.948 121.918 148.998 84.531 0.000 0.165 0.000 0.000 -42.309 0.000 -28.721 -85.266
ROOM_1_FLR_3 19.208 -29.077 0.000 -14.422 0.000 0.000 9.749 6.366 12.292 44.048 0.000 0.153 0.000 0.000 -22.885 0.000 -9.748 -15.683
ROOM_2_FLR_3 22.939 -22.264 0.000 -14.126 0.000 0.000 9.776 6.366 12.291 31.020 0.000 0.157 0.000 0.000 -23.117 0.000 -9.660 -13.381
ROOM_3_MULT19_FLR_3 16.434 -120.006 0.000 -216.893 0.000 0.000 0.000 76.021 228.754 275.756 0.000 0.375 0.000 0.000 -129.135 0.000 -70.946 -60.359
ROOM_4_MULT19_FLR_3 58.597 -143.496 0.000 -192.114 0.000 0.000 185.677 76.042 228.817 77.377 0.000 1.709 0.000 0.000 -127.783 0.000 -59.223 -105.601
ROOM_5_FLR_3 19.256 -27.359 0.000 -14.478 0.000 0.000 9.745 6.366 12.292 42.079 0.000 0.155 0.000 0.000 -22.422 0.000 -9.762 -15.871
ROOM_6_FLR_3 22.914 -20.122 0.000 -14.217 0.000 0.000 9.770 6.366 12.291 28.889 0.000 0.159 0.000 0.000 -22.527 0.000 -9.685 -13.837
CORRIDOR_FLR_3 0.000 0.000 0.561 -181.509 0.000 0.000 119.067 109.603 0.000 39.539 0.000 0.081 0.000 0.000 -29.975 0.000 -11.695 -45.672
ROOM_1_FLR_6 7.195 -7.042 0.000 -3.573 0.000 0.000 2.441 1.592 3.073 10.953 0.000 0.039 0.000 0.000 -5.662 0.000 -2.461 -6.554
ROOM_2_FLR_6 8.447 -5.271 0.000 -3.501 0.000 0.000 2.447 1.591 3.073 7.719 0.000 0.040 0.000 0.000 -5.709 0.000 -2.443 -6.396
ROOM_3_MULT9_FLR_6 19.205 -48.157 0.000 -23.594 0.000 0.000 21.877 9.005 27.097 59.866 0.000 0.247 0.000 0.000 -26.732 0.000 -12.245 -26.570
BANQUET_FLR_6 0.000 0.000 0.000 -423.276 0.000 0.000 315.907 34.655 175.857 7.390 0.000 0.029 0.000 0.000 -18.264 0.000 -6.946 -85.352
DINING_FLR_6 0.000 0.000 0.000 -465.412 0.000 0.000 314.763 34.655 175.857 7.179 0.000 0.029 0.000 0.000 -18.818 0.000 -7.002 -41.250
KITCHEN_FLR_6 0.000 0.000 0.000 -619.031 0.000 0.000 28.235 13.327 550.372 19.553 0.000 0.026 26.240 0.000 -12.444 0.000 -6.279 -0.001
CORRIDOR_FLR_6 0.000 0.000 0.307 -91.140 0.000 0.000 31.643 28.999 0.000 19.335 0.000 0.028 29.530 0.000 -13.522 0.000 -5.180 -0.000
Total Facility 194.194 -422.794 1.969 -4389.605 0.000 0.000 2006.308 766.657 2451.839 842.846 0.000 3.579 60.382 0.000 -561.608 0.000 -278.863 -674.906


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 29-NOV-21:48 0.00 0.00 0.00 -37074.43 0.00 0.00 5924.42 12609.30 9581.50 0.00 0.00 0.00 8959.22 0.00 -0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 12-FEB-12:55 0.00 0.00 0.00 -6214.05 0.00 0.00 212.49 234.80 288.68 7147.62 0.00 0.00 0.00 0.00 -0.00 0.00 -219.13 -1450.40
RETAIL_2_FLR_1 24-APR-23:34 0.00 0.00 0.00 -2175.35 0.00 0.00 809.79 181.27 250.72 0.00 0.00 0.00 1009.39 0.00 -0.00 0.00 -75.82 0.00
MECH_FLR_1 18-MAY-06:25 0.00 0.00 0.00 -1910.37 0.00 0.00 81.13 755.78 530.18 0.00 0.00 0.00 727.68 0.00 -0.00 0.00 -184.38 0.00
STORAGE_FLR_1 18-MAY-06:25 0.00 0.00 0.00 -894.05 0.00 0.00 63.96 126.51 152.94 0.00 0.00 0.00 654.37 0.00 -0.00 0.00 -103.73 0.00
LAUNDRY_FLR_1 07-FEB-20:01 0.00 0.00 0.00 -52365.77 0.00 0.00 337.87 357.21 44299.38 0.00 0.00 0.00 7692.81 0.00 -0.00 0.00 -321.50 0.00
CAFE_FLR_1 12-FEB-12:39 0.00 0.00 0.00 -25065.04 0.00 0.00 2968.95 358.25 406.43 20490.14 0.00 0.00 1329.40 0.00 -0.00 0.00 -488.13 0.00
LOBBY_FLR_1 10-MAY-21:54 0.00 0.00 0.00 -60203.61 0.00 0.00 26625.48 6843.46 7389.94 0.00 0.00 0.00 23566.18 0.00 -2877.99 0.00 -1343.46 0.00
ROOM_1_FLR_3 14-MAY-15:02 0.00 -13482.39 0.00 -735.78 0.00 0.00 130.71 161.71 305.54 11467.07 0.00 64.75 2088.39 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_3 10-AUG-18:02 0.00 -12301.78 0.00 -751.45 0.00 0.00 335.50 436.07 516.20 9465.22 0.00 200.55 2099.68 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 04-OCT-12:30 0.00 -53002.45 0.00 -10424.69 0.00 0.00 0.00 1638.34 5097.90 87514.45 0.00 0.00 0.00 0.00 -0.00 0.00 -398.78 -30424.78
ROOM_4_MULT19_FLR_3 24-JUL-18:02 0.00 -58746.57 0.00 -10256.30 0.00 0.00 6375.30 5209.05 9610.21 15117.80 0.00 807.03 31883.47 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 14-MAY-15:02 0.00 -11874.46 0.00 -724.97 0.00 0.00 130.72 161.71 305.54 3208.98 0.00 81.08 8711.41 0.00 -0.00 0.00 0.00 0.00
ROOM_6_FLR_3 30-JUL-15:02 0.00 -10868.41 0.00 -729.18 0.00 0.00 130.72 161.69 305.51 1829.07 0.00 125.97 9044.64 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 18-MAY-06:25 0.00 0.00 0.00 -13363.23 0.00 0.00 2614.81 4979.51 0.00 0.00 0.00 0.00 7634.90 0.00 -1308.97 0.00 -557.03 0.00
ROOM_1_FLR_6 10-AUG-18:02 0.00 -3542.36 0.00 -187.68 0.00 0.00 83.87 109.03 129.07 2254.67 0.00 49.83 1103.56 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_6 31-JUL-18:02 0.00 -3188.08 0.00 -187.82 0.00 0.00 83.88 109.02 129.05 2364.61 0.00 23.20 666.14 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 04-OCT-15:02 0.00 -18953.77 0.00 -1189.35 0.00 0.00 529.40 194.07 603.86 10410.09 0.00 0.00 8716.01 0.00 -0.00 0.00 -310.31 0.00
BANQUET_FLR_6 31-OCT-03:59 0.00 0.00 0.00 -31685.76 0.00 0.00 15763.17 343.78 2249.30 0.00 0.00 0.00 14903.74 0.00 -1283.60 0.00 -290.63 0.00
DINING_FLR_6 07-APR-23:14 0.00 0.00 0.00 -34087.76 0.00 0.00 16252.14 687.57 2249.30 0.00 0.00 0.00 16247.63 0.00 -1067.31 0.00 -281.57 0.00
KITCHEN_FLR_6 29-MAR-11:16 0.00 0.00 0.00 -39542.32 0.00 0.00 308.87 302.73 24259.91 1473.34 0.00 0.00 13445.49 0.00 -0.00 0.00 -248.02 0.00
CORRIDOR_FLR_6 10-AUG-14:20 0.00 0.00 0.00 -6834.50 0.00 0.00 462.68 658.76 0.00 3529.79 0.00 78.05 2105.22 0.00 -0.00 0.00 0.00 0.00
Total Facility 10-AUG-18:02 0.00 -156018.03 0.00 -216391.56 0.00 0.00 74608.10 53571.31 122326.88 53479.82 0.00 4793.14 63630.34 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 30-OCT-05:03 0.00 0.00 1940.26 0.00 0.00 0.00 5187.65 6304.56 5323.05 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -18755.52
RETAIL_1_FLR_1 23-APR-07:06 0.00 0.00 1918.35 0.00 0.00 0.00 447.56 313.07 360.84 0.00 0.00 0.00 0.00 0.00 -67.11 0.00 -151.86 -2820.86
RETAIL_2_FLR_1 23-NOV-18:25 0.00 0.00 353.89 0.00 0.00 0.00 406.46 453.18 501.43 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -77.18 -1637.78
MECH_FLR_1 02-DEC-07:16 0.00 0.00 435.54 0.00 0.00 0.00 109.60 453.47 353.45 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -167.42 -1184.63
STORAGE_FLR_1 10-DEC-19:47 0.00 0.00 258.86 0.00 0.00 0.00 101.17 177.11 203.92 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -93.62 -647.43
LAUNDRY_FLR_1 13-OCT-01:49 0.00 0.00 2757.28 0.00 0.00 0.00 605.03 39.69 9326.18 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -245.00 -12483.18
CAFE_FLR_1 02-DEC-07:16 0.00 0.00 3311.12 0.00 0.00 0.00 5862.67 587.30 406.43 0.00 0.00 0.00 0.00 0.00 -2019.80 0.00 -413.99 -7733.74
LOBBY_FLR_1 23-NOV-18:25 0.00 0.00 6490.51 0.00 0.00 0.00 13528.22 5702.88 6334.24 0.00 0.00 0.00 0.00 0.00 -2539.27 0.00 -1287.11 -28229.46
ROOM_1_FLR_3 13-DEC-19:01 8692.39 293.24 0.00 -293.24 0.00 0.00 417.94 436.12 516.26 0.00 0.00 0.00 0.00 0.00 -1519.49 0.00 -413.83 -8129.39
ROOM_2_FLR_3 19-FEB-09:01 8538.83 294.71 0.00 -294.71 0.00 0.00 163.33 274.38 653.15 0.00 0.00 0.00 0.00 0.00 -1383.93 0.00 -664.10 -7581.65
ROOM_3_MULT19_FLR_3 19-FEB-06:00 12427.95 3404.35 0.00 -3404.35 0.00 0.00 0.00 643.59 3921.46 0.00 0.00 0.00 580.12 0.00 -13724.83 0.00 -3848.30 0.00
ROOM_4_MULT19_FLR_3 15-JAN-16:01 45213.73 4172.94 0.00 -4172.94 0.00 0.00 3045.63 1931.47 5687.67 0.00 0.00 0.00 0.00 0.00 -8578.28 0.00 -2832.17 -44468.05
ROOM_5_FLR_3 13-DEC-19:01 8525.28 293.51 0.00 -293.51 0.00 0.00 417.73 436.12 516.26 0.00 0.00 0.00 0.00 0.00 -1517.38 0.00 -413.93 -7964.08
ROOM_6_FLR_3 15-JAN-09:01 8344.53 296.24 0.00 -296.24 0.00 0.00 163.33 274.38 653.15 565.85 0.00 0.00 0.00 0.00 -0.00 0.00 -661.88 -9339.36
CORRIDOR_FLR_3 01-DEC-18:20 0.00 0.00 4500.19 0.00 0.00 0.00 3457.18 5975.42 0.00 0.00 0.00 0.00 0.00 0.00 -2006.35 0.00 -518.18 -11408.26
ROOM_1_FLR_6 15-JAN-09:01 2553.44 75.39 0.00 -75.39 0.00 0.00 40.83 68.60 163.31 0.00 0.00 0.00 0.00 0.00 -87.08 0.00 -166.49 -2572.60
ROOM_2_FLR_6 07-JAN-09:01 2524.07 74.60 0.00 -74.60 0.00 0.00 40.83 68.59 163.29 0.00 0.00 0.00 0.00 0.00 -419.41 0.00 -169.51 -2207.87
ROOM_3_MULT9_FLR_6 19-DEC-19:01 12414.83 488.50 0.00 -488.50 0.00 0.00 935.66 616.86 1138.05 0.00 0.00 0.00 0.00 0.00 -1475.87 0.00 -464.62 -13164.91
BANQUET_FLR_6 03-MAR-00:55 0.00 0.00 665.58 0.00 0.00 0.00 15501.78 687.57 2249.30 0.00 0.00 0.00 0.00 0.00 -1080.74 0.00 -313.94 -17709.55
DINING_FLR_6 03-MAR-00:55 0.00 0.00 234.66 0.00 0.00 0.00 15397.99 687.57 2249.30 0.00 0.00 0.00 0.00 0.00 -1104.73 0.00 -316.90 -17147.90
KITCHEN_FLR_6 13-OCT-01:49 0.00 0.00 171.54 0.00 0.00 0.00 1456.79 121.09 5415.98 0.00 0.00 0.00 0.00 0.00 -956.00 0.00 -271.47 -5937.93
CORRIDOR_FLR_6 10-DEC-19:47 0.00 0.00 1943.61 0.00 0.00 0.00 1099.79 1844.52 0.00 0.00 0.00 0.00 0.00 0.00 -821.85 0.00 -222.52 -3843.55
Total Facility 10-NOV-09:01 74269.04 24129.60 14756.71 -24129.60 0.00 0.00 22324.84 26712.50 88432.23 38024.67 0.00 0.00 0.00 0.00 -2929.58 0.00 -10971.84 -250618.57



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 22.9087 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 22.7852 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 11.6605 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.6605 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.000000 142.3000 0.003581 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.001045 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5876 2.5876 1.3171 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4790 0.4790 0.2438 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2416 0.2416 0.1230 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2200 0.2200 0.1120 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1060 0.1060 0.0540 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.2986 3.2986 1.6790 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.8469 1.8469 0.9401 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.0864 5.0864 2.5890 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5747 1.5747 0.8015 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1341 2.1341 1.0863 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2357 2.2357 1.1380 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2874 2.2874 1.1643 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8108 0.8108 0.4127 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 22.9087 22.7852 22.9087 11.6605 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3171 1.3171 1.3171 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2438 0.2438 0.2438 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1230 0.1230 0.1230 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1120 0.1120 0.1120 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0540 0.0540 0.0540 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6790 1.6790 1.6790 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9401 0.9401 0.9401 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5890 2.5890 2.5890 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8015 0.8015 0.8015 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0863 1.0863 1.0863 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1380 1.1380 1.1380 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1643 1.1643 1.1643 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4127 0.4127 0.4127 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 11.6605 11.6605 11.6605 11.6605 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 474.33
Number of hours not met 474.33


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 698.56 186550.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 425.63 142582.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 766.66 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 242.27 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 959.56 59492.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 14.43 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 8.99 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 32.45 1868.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.91 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 543.37 41298.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 122.81 8225.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 194.02 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.74 4738.61 3155.64 286457.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 20.50 2034.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 34.50 1245.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1807.10 4844.08
Natural Gas 1788.84 5643.03
Additional 0.00 0.00
Total 3595.94 10487.12


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 67.57
Space Heating 0.00
Space Cooling 37.52
Fans (All) 47.89
Service Water Heating 8.00
Receptacle Equipment 153.81
Miscellaneous (All) 426.97
Subtotal 426.97


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 61.57
Service Water Heating 278.15
Miscellaneous (All) 497.39
Subtotal 497.39


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 7.31
Space Heating 6.66
Space Cooling 4.06
Fans (All) 5.18
Service Water Heating 30.96
Receptacle Equipment 33.70
Miscellaneous 12.14


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2667. 8760.
LTG_SCH_LOBBY 3061. 8760.
LTG_SCH_STORAGE 1339. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 2678. 8760.
LTG_SCH_GUESTROOM 2482. 8760.
LTG_SCH_CORRIDOR 3061. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3924. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 18.89 365 18.89 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 23.33 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8759.83 0.17 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8758.17 1.83 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8758.17 0.00 0.00 0.00 0.00
Max 8760.00 1.83 0.00 0.00 0.00
Average 8759.91 0.09 0.00 0.00 0.00
Sum 192718.00 2.00 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37202.17 0.83 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108250.83 18.17 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 18.17 0.00 0.00 0.00
Average 288886.18 0.86 0.00 0.00 0.00
Sum 6355496.00 19.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8749.33 10.67 0.00 0.00 0.00
LOBBY_FLR_1 8728.67 31.33 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8716.67 43.33 0.00 0.00 0.00
DINING_FLR_6 8735.67 24.33 0.00 0.00 0.00
KITCHEN_FLR_6 8755.00 5.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8716.67 0.00 0.00 0.00 0.00
Max 8760.00 43.33 0.00 0.00 0.00
Average 8754.79 5.21 0.00 0.00 0.00
Sum 192605.33 114.67 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 709051.67 1365.33 0.00 0.00 0.00
LOBBY_FLR_1 2103707.00 11722.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1236212.50 9502.50 0.00 0.00 0.00
DINING_FLR_6 1240381.00 5334.00 0.00 0.00 0.00
KITCHEN_FLR_6 108237.67 31.33 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2103707.00 11722.00 0.00 0.00 0.00
Average 287616.36 1270.69 0.00 0.00 0.00
Sum 6327559.83 27955.17 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:01:04

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

For: Environment

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C

For: Environment

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE

For: Environment

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.339302E+11 34483.24 09-JAN-22:01 5.60 1.64 0.792619E+10 4946.35 30-JAN-22:19 5.60 3.84
February 0.299838E+11 32768.76 08-FEB-20:21 3.85 1.80 0.705755E+10 4947.76 01-FEB-22:30 3.85 1.80
March 0.325873E+11 26821.85 24-MAR-20:45 5.10 -0.5 0.773932E+10 4885.51 23-MAR-21:30 5.10 -0.5
April 0.315628E+11 23289.15 24-APR-23:34 7.40 5.44 0.736923E+10 4822.42 17-APR-21:19 7.40 5.44
May 0.333016E+11 24364.77 18-MAY-06:25 5.85 5.34 0.765864E+10 4821.39 10-MAY-21:40 5.85 5.34
June 0.333390E+11 20551.20 15-JUN-05:27 9.15 8.12 0.750694E+10 4829.57 23-JUN-21:19 14.23 10.54
July 0.356489E+11 17230.41 04-JUL-05:27 11.40 8.70 0.787441E+10 4837.03 26-JUL-21:19 19.67 16.34
August 0.367012E+11 18109.33 18-AUG-21:00 15.00 12.34 0.800509E+10 4837.06 08-AUG-21:19 15.00 12.34
September 0.362515E+11 26862.61 28-SEP-05:50 8.30 7.54 0.782420E+10 4891.74 27-SEP-04:49 8.30 7.54
October 0.379654E+11 35593.24 16-OCT-06:23 6.40 5.43 0.812122E+10 4931.14 11-OCT-02:49 6.40 5.43
November 0.365797E+11 37074.87 29-NOV-21:48 5.00 3.42 0.787220E+10 4961.49 10-NOV-22:40 5.00 3.42
December 0.358718E+11 36814.45 01-DEC-20:45 5.10 5.05 0.805576E+10 4959.93 20-DEC-23:10 4.82 3.63
                     
Annual Sum or Average 0.413723E+12         0.930107E+11        
Minimum of Months 0.299838E+11 17230.41   3.85 -0.5 0.705755E+10 4821.39   3.85 -0.5
Maximum of Months 0.379654E+11 37074.87   15.00 12.34 0.812122E+10 4961.49   19.67 16.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.964753E+09 4050.99 20-JAN-12:48 6.52 4.54 0.621474E+09 384.04 10-JAN-00:10 6.52 4.54
February 0.178757E+10 6214.52 12-FEB-12:55 6.10 0.89 0.566379E+09 389.14 03-FEB-23:00 6.10 0.89
March 0.285153E+10 3975.74 02-MAR-13:20 12.57 7.60 0.635085E+09 405.73 14-MAR-21:30 12.50 8.53
April 0.361726E+10 3609.41 27-APR-13:10 26.10 16.37 0.620214E+09 434.93 27-APR-21:30 15.80 11.30
May 0.425327E+10 3475.43 04-MAY-13:20 22.77 15.31 0.646141E+09 432.26 04-MAY-21:30 18.35 12.20
June 0.449033E+10 2759.95 28-JUN-10:33 21.50 14.65 0.629144E+09 428.70 28-JUN-21:30 17.50 13.87
July 0.523210E+10 3354.37 31-JUL-13:20 27.57 18.47 0.670266E+09 449.80 24-JUL-21:30 27.57 18.47
August 0.544785E+10 4256.89 24-AUG-13:10 28.93 19.36 0.683535E+09 462.94 10-AUG-21:30 28.93 19.36
September 0.470944E+10 4397.98 14-SEP-13:20 23.17 17.52 0.642403E+09 449.39 12-SEP-21:30 23.17 17.52
October 0.358510E+10 4487.61 04-OCT-12:50 20.60 11.27 0.639159E+09 432.32 04-OCT-21:30 15.00 9.56
November 0.175721E+10 5509.88 11-NOV-12:35 6.13 4.87 0.603245E+09 387.84 10-NOV-22:40 6.13 4.87
December 0.120924E+10 3568.21 05-DEC-11:20 8.87 5.64 0.623266E+09 378.83 07-DEC-22:30 6.10 5.21
                     
Annual Sum or Average 0.399057E+11         0.758031E+10        
Minimum of Months 0.964753E+09 2759.95   6.10 0.89 0.566379E+09 378.83   6.10 0.89
Maximum of Months 0.544785E+10 6214.52   28.93 19.36 0.683535E+09 462.94   28.93 19.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.235816E+10 1750.60 03-JAN-06:34 7.80 6.88 0.785371E+09 537.82 09-JAN-22:10 5.60 1.64
February 0.228363E+10 1929.01 08-FEB-20:27 3.85 1.80 0.730711E+09 553.11 27-FEB-23:10 12.20 10.40
March 0.271364E+10 2153.07 15-MAR-06:07 6.88 5.85 0.846657E+09 566.21 02-MAR-23:10 6.88 5.85
April 0.280278E+10 2175.35 24-APR-23:34 7.40 5.44 0.840578E+09 569.52 26-APR-21:00 12.80 10.12
May 0.304832E+10 2154.21 18-MAY-06:25 5.85 5.34 0.891405E+09 569.54 15-MAY-21:30 5.85 5.34
June 0.306368E+10 1812.69 15-JUN-05:27 9.15 8.12 0.874079E+09 569.52 26-JUN-21:10 15.82 13.04
July 0.334853E+10 1972.80 24-JUL-21:00 22.80 16.50 0.922695E+09 569.54 30-JUL-23:19 19.80 15.74
August 0.340518E+10 2121.77 10-AUG-21:00 23.00 16.96 0.929839E+09 569.55 08-AUG-21:19 23.00 16.96
September 0.308749E+10 1909.36 14-SEP-21:00 18.30 14.89 0.878266E+09 569.54 12-SEP-23:19 18.30 14.89
October 0.286817E+10 2025.00 12-OCT-23:32 7.43 6.58 0.866158E+09 569.53 04-OCT-22:00 7.43 6.58
November 0.248993E+10 1869.58 28-NOV-23:25 7.25 6.32 0.789075E+09 547.97 10-NOV-22:40 7.25 6.32
December 0.240533E+10 1854.28 01-DEC-18:17 6.10 5.39 0.795198E+09 550.66 04-DEC-22:10 4.85 3.28
                     
Annual Sum or Average 0.338748E+11         0.101500E+11        
Minimum of Months 0.228363E+10 1750.60   3.85 1.80 0.730711E+09 537.82   4.85 1.64
Maximum of Months 0.340518E+10 2175.35   23.00 16.96 0.929839E+09 569.55   23.00 16.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.142437E+10 1494.15 01-JAN-20:15 5.93 5.23 0.154024E+09 98.94 30-JAN-22:19 5.60 3.84
February 0.155866E+10 1610.48 26-FEB-01:32 8.87 8.22 0.141380E+09 104.67 28-FEB-22:10 8.12 7.00
March 0.217220E+10 1813.17 15-MAR-06:07 6.88 5.85 0.163092E+09 104.47 20-MAR-21:49 8.22 6.10
April 0.230232E+10 1829.91 24-APR-23:34 7.40 5.44 0.164080E+09 113.80 27-APR-21:19 16.27 11.36
May 0.259112E+10 1910.42 18-MAY-06:25 5.85 5.34 0.178180E+09 116.78 05-MAY-21:19 5.85 5.34
June 0.266623E+10 1591.73 13-JUN-23:40 10.00 8.89 0.178048E+09 119.59 28-JUN-21:10 16.97 13.74
July 0.290701E+10 1598.25 24-JUL-21:00 22.80 16.50 0.189857E+09 120.45 26-JUL-21:19 19.67 16.34
August 0.296204E+10 1738.30 10-AUG-20:00 25.60 17.66 0.192387E+09 120.45 15-AUG-22:10 18.18 14.52
September 0.262834E+10 1656.42 27-SEP-06:30 8.60 8.44 0.177320E+09 120.10 14-SEP-21:10 8.60 8.44
October 0.239098E+10 1712.76 12-OCT-23:32 7.43 6.58 0.170751E+09 113.38 04-OCT-21:10 7.43 6.58
November 0.192883E+10 1569.10 17-NOV-08:35 7.03 6.50 0.154152E+09 106.15 06-NOV-22:10 7.03 6.50
December 0.159049E+10 1550.11 04-DEC-16:10 8.03 4.89 0.154662E+09 101.20 04-DEC-22:10 4.85 3.28
                     
Annual Sum or Average 0.271226E+11         0.201793E+10        
Minimum of Months 0.142437E+10 1494.15   5.85 4.89 0.141380E+09 98.94   4.85 3.28
Maximum of Months 0.296204E+10 1910.42   25.60 17.66 0.192387E+09 120.45   19.67 16.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.397994E+09 643.73 12-JAN-07:10 6.70 6.17 0.116987E+09 72.13 11-JAN-23:10 6.70 6.17
February 0.566064E+09 755.64 26-FEB-01:32 8.87 8.22 0.106799E+09 76.44 28-FEB-23:40 6.47 5.27
March 0.978533E+09 853.54 15-MAR-06:07 6.88 5.85 0.121699E+09 76.09 20-MAR-22:19 7.93 5.90
April 0.106620E+10 862.16 24-APR-23:34 7.40 5.44 0.122596E+09 83.47 27-APR-21:40 15.33 11.23
May 0.120556E+10 894.07 18-MAY-06:25 5.85 5.34 0.133319E+09 85.58 05-MAY-22:10 5.85 5.34
June 0.124477E+10 750.34 13-JUN-23:40 10.00 8.89 0.133479E+09 87.73 28-JUN-22:10 17.75 13.83
July 0.135894E+10 669.20 24-JUL-18:10 28.72 17.86 0.142574E+09 90.77 24-JUL-21:40 21.33 16.04
August 0.138054E+10 681.60 10-AUG-18:08 30.57 19.31 0.144671E+09 91.91 10-AUG-21:40 22.67 16.07
September 0.122591E+10 778.12 27-SEP-05:14 7.57 7.21 0.132917E+09 88.06 14-SEP-21:40 7.57 7.21
October 0.110552E+10 807.70 12-OCT-23:32 7.43 6.58 0.127504E+09 83.25 04-OCT-22:10 7.43 6.58
November 0.774351E+09 724.33 20-NOV-06:13 7.80 6.22 0.115726E+09 77.37 06-NOV-23:10 7.80 6.22
December 0.510128E+09 718.19 03-DEC-09:07 7.98 3.60 0.117136E+09 72.80 04-DEC-22:10 4.85 3.28
                     
Annual Sum or Average 0.118145E+11         0.151541E+10        
Minimum of Months 0.397994E+09 643.73   5.85 3.60 0.106799E+09 72.13   4.85 3.28
Maximum of Months 0.138054E+10 894.07   30.57 19.31 0.144671E+09 91.91   22.67 16.07



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.477958E+11 50428.00 23-JAN-21:40 4.40 2.93 0.592551E+09 489.73 30-JAN-22:19 5.60 3.84
February 0.437722E+11 52379.02 07-FEB-20:01 4.82 2.07 0.535035E+09 508.33 01-FEB-22:30 4.82 2.07
March 0.494526E+11 51226.88 24-MAR-20:45 5.10 -0.5 0.597159E+09 508.23 23-MAR-21:30 5.10 -0.5
April 0.485980E+11 49727.30 17-APR-19:00 5.60 4.36 0.577552E+09 484.48 07-APR-21:30 5.60 4.36
May 0.509700E+11 49684.70 10-MAY-22:00 6.70 5.64 0.597547E+09 470.82 10-MAY-21:40 6.70 5.64
June 0.500619E+11 38426.82 28-JUN-20:00 21.70 15.30 0.576532E+09 389.22 06-JUN-21:10 21.70 15.30
July 0.520262E+11 38712.28 24-JUL-20:00 23.90 16.63 0.596452E+09 382.01 04-JUL-23:10 23.90 16.63
August 0.524473E+11 38783.54 10-AUG-20:00 25.60 17.66 0.598494E+09 381.90 08-AUG-21:10 25.60 17.66
September 0.496470E+11 43398.20 27-SEP-06:59 8.90 8.58 0.576927E+09 426.25 27-SEP-04:49 8.90 8.58
October 0.499847E+11 49333.63 31-OCT-20:29 7.20 6.43 0.596376E+09 477.75 31-OCT-21:10 7.30 6.51
November 0.472546E+11 50329.27 29-NOV-21:48 5.00 3.42 0.576966E+09 513.21 10-NOV-22:40 5.00 3.42
December 0.479215E+11 52305.45 04-DEC-21:40 5.00 3.43 0.594456E+09 503.41 26-DEC-22:10 4.90 4.13
                     
Annual Sum or Average 0.589932E+12         0.701605E+10        
Minimum of Months 0.437722E+11 38426.82   4.40 -0.5 0.535035E+09 381.90   4.82 -0.5
Maximum of Months 0.524473E+11 52379.02   25.60 17.66 0.598494E+09 513.21   25.60 17.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.149587E+11 19794.98 20-JAN-12:48 6.52 4.54 0.862580E+10 6191.64 30-JAN-22:19 5.60 3.84
February 0.157902E+11 25066.42 12-FEB-12:39 5.93 0.82 0.804746E+10 6490.36 03-FEB-23:00 5.93 0.82
March 0.192820E+11 15356.16 01-MAR-13:17 10.97 5.87 0.927766E+10 6625.59 03-MAR-00:49 6.70 5.87
April 0.203233E+11 15994.73 24-APR-23:34 7.40 5.44 0.917838E+10 6466.45 07-APR-23:40 7.40 5.44
May 0.218038E+11 14531.93 27-MAY-04:27 7.80 7.25 0.964391E+10 6460.28 04-MAY-22:10 7.80 7.25
June 0.218533E+11 12889.20 15-JUN-02:29 8.60 7.75 0.946956E+10 6460.27 28-JUN-22:10 17.75 13.83
July 0.237655E+11 12204.95 31-JUL-15:03 28.40 18.96 0.100270E+11 6461.57 24-JUL-23:19 28.40 18.96
August 0.245244E+11 14417.16 24-AUG-14:10 29.18 19.32 0.101775E+11 6461.66 10-AUG-23:19 29.18 19.32
September 0.226561E+11 15450.25 23-SEP-13:20 22.57 17.43 0.959193E+10 6461.67 12-SEP-23:19 22.57 17.43
October 0.207141E+11 15597.68 04-OCT-12:50 20.60 11.27 0.947199E+10 6537.95 13-OCT-02:00 6.70 5.33
November 0.163709E+11 24423.79 11-NOV-12:03 5.28 4.39 0.859339E+10 6225.90 10-NOV-22:40 5.28 4.39
December 0.154476E+11 13989.18 05-DEC-11:20 8.87 5.64 0.870947E+10 6156.78 20-DEC-23:10 4.82 3.63
                     
Annual Sum or Average 0.237490E+12         0.110814E+12        
Minimum of Months 0.149587E+11 12204.95   5.28 0.82 0.804746E+10 6156.78   4.82 0.82
Maximum of Months 0.245244E+11 25066.42   29.18 19.32 0.101775E+11 6625.59   29.18 19.32



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.541567E+11 39305.93 09-JAN-22:20 5.60 1.67 0.280760E+11 19245.90 30-JAN-22:19 5.60 3.84
February 0.521404E+11 46873.94 28-FEB-23:30 6.65 5.48 0.260807E+11 19523.64 03-FEB-23:00 6.65 5.48
March 0.612692E+11 58831.08 21-MAR-21:18 7.03 6.14 0.300532E+11 19740.57 03-MAR-00:49 7.03 6.14
April 0.626827E+11 52477.42 11-APR-22:00 6.70 5.41 0.296029E+11 19610.08 21-APR-23:30 8.30 6.94
May 0.676471E+11 60204.86 10-MAY-21:54 6.70 5.64 0.311203E+11 19641.67 10-MAY-21:40 6.70 5.64
June 0.678339E+11 39862.88 15-JUN-05:27 9.15 8.12 0.304481E+11 19189.33 22-JUN-01:39 12.97 11.68
July 0.733042E+11 39587.72 24-JUL-21:10 22.43 16.40 0.317809E+11 19202.00 19-JUL-04:49 22.43 16.40
August 0.749767E+11 40992.29 10-AUG-21:10 22.92 16.74 0.320038E+11 19225.48 11-AUG-04:30 12.85 11.96
September 0.684981E+11 41913.69 27-SEP-05:14 7.57 7.21 0.305302E+11 19244.43 12-SEP-02:49 7.57 7.21
October 0.645578E+11 59903.72 13-OCT-00:55 7.20 6.12 0.305941E+11 19700.95 13-OCT-02:00 6.70 5.33
November 0.562971E+11 46414.07 28-NOV-23:05 7.62 6.40 0.281092E+11 19544.93 10-NOV-22:40 7.62 6.40
December 0.550881E+11 40018.21 03-DEC-09:07 7.98 3.60 0.283786E+11 19176.07 07-DEC-23:19 6.10 5.28
                     
Annual Sum or Average 0.758452E+12         0.356778E+12        
Minimum of Months 0.521404E+11 39305.93   5.60 1.67 0.260807E+11 19176.07   5.60 3.84
Maximum of Months 0.749767E+11 60204.86   22.92 16.74 0.320038E+11 19740.57   22.43 16.40



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 55344550.57 2107.97 20-JAN-16:02 5.40 3.78 93220246.76 56.69 03-JAN-05:30 5.40 3.78
February 0.123455E+09 3124.92 08-FEB-16:02 7.12 3.76 85376362.34 56.69 08-FEB-22:10 3.22 1.67
March 0.295326E+09 3350.19 18-MAR-15:02 20.10 10.35 95889341.79 56.69 18-MAR-23:30 10.00 8.01
April 0.696646E+09 3483.65 01-APR-18:02 25.13 11.98 94044038.16 56.69 26-APR-21:00 12.80 10.12
May 0.118115E+10 3554.62 14-MAY-15:02 23.30 12.38 98053290.50 56.69 03-MAY-21:00 23.30 12.38
June 0.137157E+10 3300.56 02-JUN-18:01 19.45 12.43 95235484.29 56.70 28-JUN-21:40 17.77 13.93
July 0.202354E+10 3310.12 25-JUL-18:02 22.02 16.61 98597802.45 56.70 27-JUL-21:40 18.17 14.77
August 0.197294E+10 3543.45 10-AUG-18:02 30.57 19.31 98638756.47 56.70 24-AUG-22:40 20.77 16.72
September 0.133524E+10 3267.73 13-SEP-18:02 22.43 16.15 94777491.20 56.69 14-SEP-02:20 14.63 13.65
October 0.492622E+09 3497.16 04-OCT-15:02 21.60 11.48 96392968.52 56.69 04-OCT-21:40 15.37 9.73
November 0.111414E+09 3181.66 04-NOV-15:02 20.92 15.94 91239878.14 56.69 16-NOV-22:30 5.00 4.37
December 61378294.74 2918.11 05-DEC-16:02 6.10 4.53 93541750.99 56.69 28-DEC-04:30 8.60 7.35
                     
Annual Sum or Average 0.972063E+10         0.113501E+10        
Minimum of Months 55344550.57 2107.97   5.40 3.76 85376362.34 56.69   3.22 1.67
Maximum of Months 0.202354E+10 3554.62   30.57 19.31 98638756.47 56.70   23.30 16.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 37623399.94 1010.78 24-JAN-16:03 6.60 5.12 92673850.06 56.69 03-JAN-05:30 6.60 5.12
February 68654442.80 2966.21 27-FEB-16:02 19.32 12.38 84497378.55 56.69 01-FEB-03:49 19.32 12.38
March 0.163487E+09 2994.18 18-MAR-15:02 20.10 10.35 94903312.02 56.69 18-MAR-23:10 10.40 8.02
April 0.493810E+09 3162.17 01-APR-18:02 25.13 11.98 93338745.82 56.69 26-APR-21:30 14.20 10.54
May 0.987151E+09 3217.53 14-MAY-15:02 23.30 12.38 97714869.87 56.69 15-MAY-21:49 12.98 11.14
June 0.122490E+10 3007.49 24-JUN-18:02 18.72 11.75 94995663.30 56.69 28-JUN-21:00 18.30 14.03
July 0.180304E+10 3084.31 20-JUL-15:02 26.88 16.80 98438522.73 56.70 26-JUL-21:40 17.63 15.37
August 0.167413E+10 3263.26 10-AUG-18:02 30.57 19.31 98425790.90 56.70 24-AUG-22:19 21.33 16.95
September 0.973192E+09 3092.85 22-SEP-15:02 23.58 17.29 94329509.33 56.69 22-SEP-21:00 16.70 14.57
October 0.273215E+09 3123.07 04-OCT-15:02 21.60 11.48 95426587.90 56.69 04-OCT-23:19 13.70 9.84
November 74340134.85 2874.86 04-NOV-15:02 20.92 15.94 90600499.48 56.69 14-NOV-22:19 5.60 5.10
December 42920083.80 959.82 03-DEC-19:03 8.72 3.46 92825105.36 56.69 28-DEC-04:30 8.60 7.35
                     
Annual Sum or Average 0.781647E+10         0.112817E+10        
Minimum of Months 37623399.94 959.82   6.60 3.46 84497378.55 56.69   5.60 5.10
Maximum of Months 0.180304E+10 3263.26   30.57 19.31 98438522.73 56.70   21.33 16.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 91606507.14 158.87 08-JAN-14:40 5.40 2.66 0.00 0.00 01-JAN-00:10 5.40 2.66
February 0.180277E+09 536.60 08-FEB-14:00 6.70 3.83 0.00 0.00 01-FEB-00:10 6.70 3.83
March 0.298585E+09 684.17 02-MAR-13:30 12.75 7.74 0.00 0.00 01-MAR-00:10 12.75 7.74
April 0.368416E+09 663.51 27-APR-13:10 26.10 16.37 0.00 0.00 01-APR-00:10 26.10 16.37
May 0.427320E+09 638.43 04-MAY-13:20 22.77 15.31 0.00 0.00 01-MAY-00:10 22.77 15.31
June 0.443342E+09 500.61 28-JUN-13:20 24.60 15.70 0.00 0.00 01-JUN-00:10 24.60 15.70
July 0.578871E+09 618.63 31-JUL-13:20 27.57 18.47 0.00 0.00 01-JUL-00:10 27.57 18.47
August 0.647355E+09 761.86 24-AUG-13:10 28.93 19.36 0.00 0.00 01-AUG-00:10 28.93 19.36
September 0.569253E+09 810.42 14-SEP-13:30 23.35 17.43 0.00 0.00 01-SEP-00:10 23.35 17.43
October 0.407557E+09 834.64 04-OCT-12:30 20.60 11.38 0.00 0.00 01-OCT-00:10 20.60 11.38
November 0.179585E+09 548.58 04-NOV-13:50 21.02 15.96 0.00 0.00 01-NOV-00:10 21.02 15.96
December 0.126592E+09 484.60 05-DEC-12:25 10.30 6.13 0.00 0.00 01-DEC-00:10 10.30 6.13
                     
Annual Sum or Average 0.431876E+10         0.00        
Minimum of Months 91606507.14 158.87   5.40 2.66 0.00 0.00   5.40 2.66
Maximum of Months 0.647355E+09 834.64   28.93 19.36 0.00 0.00   28.93 19.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 74097795.96 449.13 09-JAN-19:04 5.60 1.78 94277827.16 56.69 30-JAN-22:10 5.60 3.84
February 0.104489E+09 684.06 25-FEB-09:03 11.88 10.94 85550882.33 56.69 08-FEB-22:10 11.88 10.94
March 0.193084E+09 706.16 17-MAR-18:01 10.82 7.32 95536634.98 56.69 18-MAR-23:19 10.20 8.02
April 0.324505E+09 844.53 01-APR-18:02 25.13 11.98 93100621.18 56.69 27-APR-21:49 14.87 11.14
May 0.474942E+09 855.37 14-MAY-18:02 21.83 11.88 96859236.62 56.69 15-MAY-21:00 12.80 11.20
June 0.561590E+09 872.45 09-JUN-18:02 22.70 13.21 94019040.09 56.69 08-JUN-22:10 22.70 13.21
July 0.650461E+09 907.93 24-JUL-18:02 28.72 17.86 97186242.78 56.69 24-JUL-21:40 21.33 16.04
August 0.633259E+09 897.11 10-AUG-18:02 30.57 19.31 97211327.17 56.69 28-AUG-22:30 18.45 15.09
September 0.437822E+09 819.11 13-SEP-18:02 22.43 16.15 93398212.05 56.69 25-SEP-21:10 13.90 13.52
October 0.267636E+09 749.42 04-OCT-15:02 21.60 11.48 95745871.31 56.69 06-OCT-21:10 12.70 10.58
November 0.144609E+09 686.71 04-NOV-08:63 13.07 11.67 91917085.44 56.69 06-NOV-23:10 15.40 14.28
December 73519259.12 483.75 05-DEC-19:03 5.37 3.27 94318567.43 56.69 15-DEC-22:10 5.68 5.47
                     
Annual Sum or Average 0.394001E+10         0.112912E+10        
Minimum of Months 73519259.12 449.13   5.37 1.78 85550882.33 56.69   5.60 3.84
Maximum of Months 0.650461E+09 907.93   30.57 19.31 97211327.17 56.69   22.70 16.04



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 55019209.09 926.77 10-JAN-09:03 5.78 3.12 93143830.16 56.69 03-JAN-05:30 5.78 3.12
February 0.120246E+09 2591.79 08-FEB-16:02 7.12 3.76 85384449.00 56.69 04-FEB-01:30 7.12 3.76
March 0.288624E+09 2990.94 18-MAR-15:02 20.10 10.35 96082357.98 56.69 18-MAR-23:10 10.40 8.02
April 0.715203E+09 3098.80 01-APR-18:02 25.13 11.98 94417611.12 56.69 26-APR-21:30 14.20 10.54
May 0.104755E+10 3149.93 14-MAY-15:02 23.30 12.38 98112444.13 56.69 06-MAY-23:30 23.30 12.38
June 0.145340E+10 3006.83 02-JUN-18:01 19.45 12.43 95490524.94 56.69 28-JUN-21:19 17.23 13.81
July 0.178284E+10 3124.78 24-JUL-18:02 28.72 17.86 98698784.78 56.70 31-JUL-22:10 20.05 15.96
August 0.194157E+10 3141.64 10-AUG-18:02 30.57 19.31 98815638.52 56.70 23-AUG-21:49 21.27 16.17
September 0.122719E+10 3042.27 22-SEP-15:02 23.58 17.29 94741911.45 56.70 14-SEP-21:19 23.58 17.29
October 0.487072E+09 3097.86 04-OCT-15:02 21.60 11.48 96531676.75 56.69 04-OCT-21:10 14.27 9.23
November 0.115523E+09 2866.27 04-NOV-15:02 20.92 15.94 91202976.51 56.69 16-NOV-22:30 5.00 4.37
December 70397613.90 967.03 30-DEC-09:03 4.18 3.83 93460705.43 56.69 28-DEC-04:30 4.18 3.83
                     
Annual Sum or Average 0.930464E+10         0.113608E+10        
Minimum of Months 55019209.09 926.77   4.18 3.12 85384449.00 56.69   4.18 3.12
Maximum of Months 0.194157E+10 3149.93   30.57 19.31 98815638.52 56.70   23.58 17.29



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 34011566.35 788.26 05-JAN-09:04 -0.0 -0.1 92640978.49 56.69 03-JAN-05:30 -0.0 -0.1
February 64283743.57 1090.96 27-FEB-09:01 8.77 7.22 84448023.48 56.69 01-FEB-03:49 8.77 7.22
March 0.146134E+09 2522.42 02-MAR-09:01 4.78 3.27 95080013.79 56.69 21-MAR-21:49 6.78 5.71
April 0.499095E+09 2776.38 27-APR-15:02 27.20 17.22 93797057.79 56.69 26-APR-21:10 27.20 17.22
May 0.846698E+09 2871.31 14-MAY-15:02 23.30 12.38 97862195.75 56.69 15-MAY-21:49 12.98 11.14
June 0.129252E+10 2818.92 28-JUN-18:02 25.40 16.48 95390390.57 56.69 28-JUN-21:19 17.23 13.81
July 0.155360E+10 2899.38 30-JUL-15:02 27.30 18.11 98626292.91 56.70 31-JUL-21:00 20.30 16.18
August 0.163063E+10 2892.51 23-AUG-15:02 28.95 18.68 98707683.83 56.70 24-AUG-21:00 21.90 17.18
September 0.854036E+09 2777.66 12-SEP-15:02 24.40 16.76 94367609.42 56.69 15-SEP-00:30 15.55 14.02
October 0.262007E+09 2736.98 04-OCT-15:02 21.60 11.48 95575816.81 56.69 04-OCT-21:10 14.27 9.23
November 70315336.13 1445.16 04-NOV-15:02 20.92 15.94 90559121.96 56.69 14-NOV-22:19 5.60 5.10
December 40698941.98 765.24 03-DEC-09:03 7.98 3.60 92757622.05 56.69 16-DEC-03:39 9.80 8.72
                     
Annual Sum or Average 0.729402E+10         0.112981E+10        
Minimum of Months 34011566.35 765.24   -0.0 -0.1 84448023.48 56.69   -0.0 -0.1
Maximum of Months 0.163063E+10 2899.38   28.95 18.68 98707683.83 56.70   27.20 17.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.194250E+10 2352.63 12-JAN-07:10 6.70 6.17 0.120156E+10 736.61 09-JAN-22:30 6.70 6.17
February 0.247482E+10 2771.06 08-FEB-15:02 7.70 3.86 0.109659E+10 771.97 27-FEB-23:10 12.20 10.40
March 0.365395E+10 3147.70 15-MAR-06:07 6.88 5.85 0.125566E+10 794.60 02-MAR-23:10 6.88 5.85
April 0.404001E+10 3251.67 24-APR-23:34 7.40 5.44 0.127423E+10 871.57 27-APR-21:40 15.33 11.23
May 0.460323E+10 3340.92 18-MAY-06:25 5.85 5.34 0.139444E+10 887.17 15-MAY-21:40 5.85 5.34
June 0.470318E+10 2810.79 13-JUN-23:40 10.00 8.89 0.138610E+10 908.67 28-JUN-21:40 17.77 13.93
July 0.512489E+10 2547.20 24-JUL-18:10 28.72 17.86 0.147919E+10 940.53 24-JUL-21:40 21.33 16.04
August 0.523105E+10 2597.21 10-AUG-18:08 30.57 19.31 0.150609E+10 951.83 10-AUG-21:10 22.92 16.74
September 0.465022E+10 2879.38 27-SEP-05:14 7.57 7.21 0.138429E+10 934.09 14-SEP-21:40 7.57 7.21
October 0.404735E+10 3034.38 12-OCT-23:32 7.43 6.58 0.130416E+10 867.06 04-OCT-22:10 7.43 6.58
November 0.275128E+10 2678.33 28-NOV-23:25 7.25 6.32 0.117606E+10 763.43 05-NOV-23:10 7.25 6.32
December 0.215449E+10 2657.79 10-DEC-19:46 6.78 5.97 0.120395E+10 745.37 05-DEC-22:40 6.78 5.97
                     
Annual Sum or Average 0.453770E+11         0.156623E+11        
Minimum of Months 0.194250E+10 2352.63   5.85 3.86 0.109659E+10 736.61   5.85 5.34
Maximum of Months 0.523105E+10 3340.92   30.57 19.31 0.150609E+10 951.83   22.92 16.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 35818937.20 1787.89 20-JAN-16:02 5.40 3.78 92797360.51 56.69 03-JAN-05:30 5.40 3.78
February 0.106778E+09 3247.32 08-FEB-16:02 7.12 3.76 84946990.88 56.69 01-FEB-03:49 7.12 3.76
March 0.273396E+09 3485.52 18-MAR-15:02 20.10 10.35 95472738.81 56.69 18-MAR-23:19 10.20 8.02
April 0.659540E+09 3635.58 01-APR-18:02 25.13 11.98 93779861.42 56.69 26-APR-21:30 14.20 10.54
May 0.112784E+10 3708.26 14-MAY-15:02 23.30 12.38 97887419.56 56.69 15-MAY-21:40 13.17 11.09
June 0.132285E+10 3427.18 02-JUN-18:01 19.45 12.43 95130644.17 56.70 22-JUN-21:30 16.70 13.38
July 0.201123E+10 3691.26 31-JUL-18:02 26.42 18.31 98499949.47 56.70 26-JUL-21:10 26.42 18.31
August 0.192163E+10 3729.93 10-AUG-18:02 30.57 19.31 98512319.56 56.70 09-AUG-21:00 30.57 19.31
September 0.124614E+10 3382.75 13-SEP-18:02 22.43 16.15 94569435.55 56.69 13-SEP-00:10 22.43 16.15
October 0.417946E+09 3642.92 04-OCT-15:02 21.60 11.48 95981966.87 56.69 09-OCT-00:40 12.40 10.53
November 94219801.43 3251.04 04-NOV-15:02 20.92 15.94 90765168.27 56.69 14-NOV-22:19 5.60 5.10
December 44937269.52 3041.96 05-DEC-16:02 6.10 4.53 93143924.06 56.69 20-DEC-22:10 5.00 4.14
                     
Annual Sum or Average 0.926233E+10         0.113149E+10        
Minimum of Months 35818937.20 1787.89   5.40 3.76 84946990.88 56.69   5.00 3.76
Maximum of Months 0.201123E+10 3729.93   30.57 19.31 98512319.56 56.70   30.57 19.31



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 17910978.04 780.03 11-JAN-16:05 14.03 10.30 92424451.84 56.69 11-JAN-04:30 14.03 10.30
February 50790464.58 3061.62 27-FEB-16:02 19.32 12.38 84114510.67 56.69 03-FEB-03:49 19.32 12.38
March 0.143102E+09 3080.57 18-MAR-15:02 20.10 10.35 94432650.86 56.69 03-MAR-05:19 20.10 10.35
April 0.455685E+09 3274.98 01-APR-18:02 25.13 11.98 93040976.71 56.69 27-APR-03:09 11.10 8.33
May 0.922857E+09 3330.22 14-MAY-15:02 23.30 12.38 97554726.07 56.69 15-MAY-21:30 13.35 11.02
June 0.116249E+10 3103.48 24-JUN-18:02 18.72 11.75 94927148.38 56.69 28-JUN-21:30 17.50 13.87
July 0.177330E+10 3375.83 31-JUL-18:02 26.42 18.31 98375884.35 56.70 24-JUL-21:00 26.42 18.31
August 0.160105E+10 3355.12 10-AUG-18:02 30.57 19.31 98306819.36 56.70 09-AUG-21:00 30.57 19.31
September 0.857426E+09 3147.93 22-SEP-15:02 23.58 17.29 94113066.37 56.70 06-SEP-23:00 23.58 17.29
October 0.214983E+09 3217.72 04-OCT-15:02 21.60 11.48 94916364.82 56.69 05-OCT-00:20 12.57 9.63
November 54977700.60 2960.32 04-NOV-15:02 20.92 15.94 90168525.03 56.69 16-NOV-22:30 5.00 4.37
December 26310987.14 907.75 10-DEC-16:03 9.72 8.43 92497180.42 56.69 26-DEC-22:40 4.60 3.84
                     
Annual Sum or Average 0.728087E+10         0.112487E+10        
Minimum of Months 17910978.04 780.03   9.72 8.43 84114510.67 56.69   4.60 3.84
Maximum of Months 0.177330E+10 3375.83   30.57 19.31 98375884.35 56.70   30.57 19.31



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 99960886.34 1985.77 05-JAN-16:01 5.73 4.38 94473010.90 56.69 26-JAN-22:19 7.60 7.14
February 0.252473E+09 2040.44 10-FEB-16:01 6.52 4.10 86535251.65 56.69 08-FEB-22:10 6.52 4.10
March 0.415549E+09 2156.25 18-MAR-15:02 20.10 10.35 96790380.85 56.69 14-MAR-21:30 20.10 10.35
April 0.602928E+09 2173.03 02-APR-15:02 20.60 11.87 94486912.12 56.69 26-APR-21:00 12.80 10.12
May 0.745590E+09 2224.97 14-MAY-15:02 23.30 12.38 98021801.47 56.69 15-MAY-21:00 12.80 11.20
June 0.841227E+09 2156.88 09-JUN-18:02 22.70 13.21 95166382.13 56.69 09-JUN-21:10 16.70 11.79
July 0.112554E+10 2175.87 24-JUL-18:02 28.72 17.86 98448198.19 56.70 24-JUL-21:40 21.33 16.04
August 0.123961E+10 2209.47 24-AUG-15:02 29.62 19.18 98518582.98 56.70 09-AUG-21:49 29.62 19.18
September 0.102186E+10 2193.70 14-SEP-15:02 23.98 16.97 94822247.91 56.70 14-SEP-21:00 17.20 14.47
October 0.606249E+09 2238.19 04-OCT-15:02 21.60 11.48 97173908.28 56.69 04-OCT-22:00 13.90 9.72
November 0.191806E+09 1989.68 10-NOV-16:01 8.53 6.27 92272943.70 56.69 04-NOV-23:10 8.53 6.27
December 0.159016E+09 1987.83 05-DEC-16:02 6.10 4.53 94716110.19 56.69 26-DEC-22:40 4.60 3.84
                     
Annual Sum or Average 0.730180E+10         0.114143E+10        
Minimum of Months 99960886.34 1985.77   5.73 4.10 86535251.65 56.69   4.60 3.84
Maximum of Months 0.123961E+10 2238.19   29.62 19.18 98518582.98 56.70   29.62 19.18



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.308825E+11 31352.01 30-JAN-23:31 5.93 4.15 0.189080E+11 12722.25 30-JAN-22:19 5.93 4.15
February 0.288338E+11 31633.24 04-FEB-00:37 7.03 6.37 0.171591E+11 12777.81 03-FEB-23:00 7.03 6.37
March 0.338671E+11 31550.20 03-MAR-05:08 7.12 6.62 0.192408E+11 13092.26 18-MAR-00:20 7.03 5.73
April 0.348917E+11 31539.07 07-APR-23:14 7.93 7.28 0.186312E+11 13075.42 07-APR-23:40 7.57 6.58
May 0.383270E+11 31151.59 12-MAY-05:38 7.40 7.02 0.193105E+11 13071.94 20-MAY-03:49 7.80 6.22
June 0.387886E+11 29781.33 15-JUN-01:37 9.07 8.19 0.187229E+11 12421.38 15-JUN-01:30 9.07 8.19
July 0.413285E+11 22509.39 24-JUL-21:10 22.43 16.40 0.192903E+11 11616.20 05-JUL-02:00 22.43 16.40
August 0.412739E+11 22437.89 10-AUG-21:20 22.83 16.52 0.193657E+11 11654.50 03-AUG-03:20 22.83 16.52
September 0.372108E+11 29862.59 28-SEP-05:32 8.30 7.58 0.186498E+11 12650.13 27-SEP-03:00 8.30 7.58
October 0.350621E+11 31689.90 31-OCT-03:59 7.20 6.66 0.191697E+11 12888.27 11-OCT-02:49 7.20 6.66
November 0.316791E+11 31282.57 20-NOV-03:42 7.88 6.22 0.184119E+11 12824.95 09-NOV-05:00 7.88 6.22
December 0.311276E+11 30392.50 04-DEC-21:34 5.00 3.43 0.189414E+11 12529.96 07-DEC-23:19 6.10 5.28
                     
Annual Sum or Average 0.423273E+12         0.225801E+12        
Minimum of Months 0.288338E+11 22437.89   5.00 3.43 0.171591E+11 11616.20   5.93 4.15
Maximum of Months 0.413285E+11 31689.90   22.83 16.52 0.193657E+11 13092.26   22.83 16.52



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.345970E+11 33105.66 30-JAN-23:31 5.93 4.15 0.191143E+11 12877.18 30-JAN-22:19 5.93 4.15
February 0.322192E+11 33312.46 04-FEB-02:25 7.20 6.36 0.173205E+11 12894.05 03-FEB-23:00 7.20 6.36
March 0.377000E+11 33196.19 03-MAR-05:08 7.12 6.62 0.193545E+11 13218.84 18-MAR-00:20 7.03 5.73
April 0.385259E+11 34092.76 07-APR-23:14 7.93 7.28 0.187041E+11 13170.76 07-APR-23:40 7.57 6.58
May 0.418709E+11 33648.57 12-MAY-05:45 7.30 6.96 0.193554E+11 13198.73 20-MAY-03:49 7.80 6.22
June 0.420863E+11 31623.19 15-JUN-05:10 8.98 8.04 0.187460E+11 12491.53 15-JUN-01:30 8.98 8.04
July 0.445243E+11 23704.66 24-JUL-21:20 22.07 16.28 0.193037E+11 11626.58 05-JUL-02:00 22.07 16.28
August 0.444186E+11 23650.32 10-AUG-21:20 22.83 16.52 0.193833E+11 11667.65 03-AUG-03:20 22.83 16.52
September 0.404713E+11 31728.24 28-SEP-05:20 8.30 7.66 0.186850E+11 12712.63 27-SEP-03:00 8.30 7.66
October 0.387622E+11 33547.20 24-OCT-02:20 7.07 6.69 0.192680E+11 12973.00 11-OCT-02:49 7.07 6.69
November 0.353794E+11 32890.02 20-NOV-03:42 7.88 6.22 0.185684E+11 12911.43 09-NOV-05:00 7.88 6.22
December 0.348541E+11 32360.57 30-DEC-18:37 4.80 4.22 0.191417E+11 12648.59 20-DEC-23:10 4.80 4.22
                     
Annual Sum or Average 0.465409E+12         0.226945E+12        
Minimum of Months 0.322192E+11 23650.32   4.80 4.15 0.173205E+11 11626.58   4.80 4.15
Maximum of Months 0.445243E+11 34092.76   22.83 16.52 0.193833E+11 13218.84   22.83 16.52



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.482150E+11 37287.85 30-JAN-18:51 5.60 4.81 0.188307E+11 11516.54 28-JAN-18:40 5.60 4.81
February 0.446695E+11 36821.63 08-FEB-17:21 6.15 3.07 0.170083E+11 11520.84 11-FEB-18:40 5.97 0.97
March 0.510404E+11 39543.45 29-MAR-11:16 7.97 5.28 0.188527E+11 11406.05 04-MAR-18:49 7.97 5.28
April 0.513588E+11 37908.16 11-APR-11:23 8.60 6.96 0.182413E+11 11382.34 08-APR-17:00 8.60 6.96
May 0.544196E+11 38156.54 12-MAY-05:45 7.30 6.96 0.188499E+11 11319.66 20-MAY-17:19 16.87 9.98
June 0.540695E+11 31669.09 15-JUN-05:50 9.32 8.19 0.182454E+11 11319.62 24-JUN-17:19 19.23 11.83
July 0.565844E+11 31245.32 24-JUL-10:37 25.93 17.48 0.188536E+11 11319.69 15-JUL-17:19 25.93 17.48
August 0.568717E+11 31285.32 13-AUG-10:40 24.17 17.28 0.188634E+11 11319.69 12-AUG-17:19 24.17 17.28
September 0.531092E+11 33206.85 28-SEP-06:44 8.80 7.92 0.182432E+11 11319.66 23-SEP-17:19 8.80 7.92
October 0.520377E+11 34742.99 24-OCT-06:20 6.47 6.47 0.188438E+11 11357.89 28-OCT-17:30 10.55 7.51
November 0.481774E+11 37041.01 23-NOV-18:36 5.60 4.52 0.182328E+11 11524.10 25-NOV-18:49 7.70 6.65
December 0.484905E+11 36356.03 13-DEC-18:19 6.47 2.58 0.188354E+11 11419.99 30-DEC-18:00 4.40 3.92
                     
Annual Sum or Average 0.619044E+12         0.221900E+12        
Minimum of Months 0.446695E+11 31245.32   5.60 2.58 0.170083E+11 11319.62   4.40 0.97
Maximum of Months 0.568717E+11 39543.45   25.93 17.48 0.188634E+11 11524.10   25.93 17.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.362216E+10 4728.93 05-JAN-15:03 6.60 5.08 0.127063E+10 778.00 30-JAN-22:19 5.60 3.84
February 0.464713E+10 5869.36 08-FEB-15:02 7.70 3.86 0.115907E+10 831.03 27-FEB-22:40 12.20 10.25
March 0.716678E+10 6436.29 15-MAR-06:07 6.88 5.85 0.131768E+10 845.01 14-MAR-21:40 6.88 5.85
April 0.815759E+10 6582.45 24-APR-23:34 7.40 5.44 0.133255E+10 939.82 27-APR-21:30 15.80 11.30
May 0.938277E+10 6536.01 18-MAY-06:25 5.85 5.34 0.145286E+10 945.96 15-MAY-21:30 5.85 5.34
June 0.973335E+10 5561.11 13-JUN-23:40 10.00 8.89 0.146159E+10 979.25 28-JUN-21:30 17.50 13.87
July 0.106692E+11 5838.08 24-JUL-15:03 30.32 18.75 0.156339E+10 1007.37 24-JUL-21:40 21.33 16.04
August 0.108213E+11 6834.73 10-AUG-14:20 29.67 19.07 0.157561E+10 1007.38 10-AUG-21:10 22.92 16.74
September 0.942356E+10 5595.24 27-SEP-05:14 7.57 7.21 0.143613E+10 976.35 14-SEP-21:30 7.57 7.21
October 0.803386E+10 6030.03 12-OCT-23:32 7.43 6.58 0.135202E+10 905.42 04-OCT-21:40 7.43 6.58
November 0.548261E+10 5456.03 28-NOV-23:25 7.25 6.32 0.124298E+10 815.62 05-NOV-23:10 7.25 6.32
December 0.399921E+10 5086.88 05-DEC-11:20 8.87 5.64 0.127244E+10 778.74 04-DEC-22:10 8.87 5.64
                     
Annual Sum or Average 0.911395E+11         0.164370E+11        
Minimum of Months 0.362216E+10 4728.93   5.85 3.86 0.115907E+10 778.00   5.60 3.84
Maximum of Months 0.108213E+11 6834.73   30.32 19.07 0.157561E+10 1007.38   22.92 16.74



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 284636.27 541.58 28-JAN-23:23 6.10
February 1054906.61 1055.13 22-FEB-06:07 7.62
March 5053534.72 1822.39 03-MAR-00:55 6.70
April 4750217.52 1269.34 17-APR-07:50 5.68
May 3516801.16 1109.00 10-MAY-03:23 7.50
June 0.00 0.00 01-JUN-00:05 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 4515.52 75.26 27-SEP-05:07 7.38
October 1524911.85 1940.24 30-OCT-05:03 7.20
November 153729.09 1049.32 29-NOV-00:02 7.35
December 323707.93 655.16 10-DEC-08:33 6.70
         
Annual Sum or Average 16666960.68      
Minimum of Months 0.00 0.00   5.68
Maximum of Months 5053534.72 1940.24   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.160812E+09 896.97 30-JAN-22:39 5.60
February 68468790.61 930.33 04-FEB-00:17 6.87
March 26647060.47 1911.73 19-MAR-07:50 8.22
April 23164059.31 1918.39 23-APR-07:06 8.48
May 22614921.81 826.24 10-MAY-21:59 6.70
June 1219659.41 582.30 14-JUN-06:20 10.20
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 2560388.18 853.50 27-SEP-05:07 7.38
October 33018667.15 1902.42 25-OCT-07:20 8.17
November 40527904.31 946.73 29-NOV-00:02 7.35
December 0.160096E+09 1765.51 10-DEC-19:47 6.78
         
Annual Sum or Average 0.539130E+09      
Minimum of Months 0.00 0.00   5.60
Maximum of Months 0.160812E+09 1918.39   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 4510388.25 317.88 22-JAN-10:57 6.10
February 1481977.86 322.41 22-FEB-06:07 7.62
March 2188804.99 256.81 04-MAR-07:13 5.97
April 1202033.87 227.02 17-APR-07:50 5.68
May 701957.53 145.86 19-MAY-05:09 7.88
June 1994.40 16.58 15-JUN-03:37 8.30
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 93153.57 165.55 27-SEP-05:07 7.38
October 2913732.07 240.47 30-OCT-05:03 7.20
November 3364758.17 353.88 23-NOV-18:25 5.60
December 4051958.68 353.76 02-DEC-07:16 6.10
         
Annual Sum or Average 20510759.39      
Minimum of Months 0.00 0.00   5.60
Maximum of Months 4510388.25 353.88   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 9080819.55 377.31 29-JAN-07:13 6.50
February 4704880.27 387.60 22-FEB-06:07 7.62
March 7465452.83 382.74 03-MAR-00:55 6.70
April 4821394.55 343.42 01-APR-05:24 7.75
May 3066262.94 255.49 20-MAY-03:40 7.80
June 81464.78 104.38 15-JUN-03:37 8.30
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 348507.46 251.97 27-SEP-04:43 7.20
October 8262826.76 402.95 30-OCT-05:03 7.20
November 7548961.06 384.07 29-NOV-00:02 7.35
December 8280796.90 435.55 02-DEC-07:16 6.10
         
Annual Sum or Average 53661367.10      
Minimum of Months 0.00 0.00   6.10
Maximum of Months 9080819.55 435.55   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 22922098.77 197.10 28-JAN-23:23 6.10
February 10976113.75 187.79 22-FEB-06:07 7.62
March 4883999.73 201.58 03-MAR-00:55 6.70
April 3246688.41 178.73 01-APR-05:24 7.75
May 2169613.51 135.27 20-MAY-03:40 7.80
June 65945.70 61.07 15-JUN-03:37 8.30
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 254109.21 137.93 27-SEP-05:07 7.38
October 5030132.80 206.79 30-OCT-05:03 7.20
November 4597206.77 205.34 29-NOV-00:02 7.35
December 15306019.07 258.86 10-DEC-19:47 6.78
         
Annual Sum or Average 69451927.73      
Minimum of Months 0.00 0.00   6.10
Maximum of Months 22922098.77 258.86   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 412067.96 1441.02 27-JAN-02:15 7.60
February 254703.32 1268.53 03-FEB-03:38 7.57
March 573447.35 1525.10 03-MAR-03:52 7.20
April 1741890.48 1794.26 06-APR-02:24 7.20
May 2075152.00 1958.72 20-MAY-03:04 7.80
June 235134.15 1605.85 15-JUN-03:37 8.30
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 117304.53 1071.34 27-SEP-01:55 8.30
October 3625792.25 2756.83 13-OCT-01:49 6.78
November 212248.73 1215.31 09-NOV-05:37 7.03
December 0.00 0.00 01-DEC-00:03 4.40
         
Annual Sum or Average 9247740.77      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 3625792.25 2756.83   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 35892544.34 2590.22 29-JAN-07:13 6.50
February 11610605.94 3015.23 27-FEB-07:27 7.50
March 27182561.27 2843.55 04-MAR-07:13 5.97
April 18563466.06 2750.26 17-APR-06:27 6.10
May 9596669.08 2027.55 10-MAY-05:46 7.80
June 145452.47 444.58 15-JUN-03:03 8.30
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 2474412.89 1715.92 27-SEP-05:07 7.38
October 28054306.80 2755.61 24-OCT-06:18 6.47
November 30564366.68 3043.39 17-NOV-08:11 6.87
December 36585365.69 3311.28 02-DEC-07:16 6.10
         
Annual Sum or Average 0.200670E+09      
Minimum of Months 0.00 0.00   5.97
Maximum of Months 36585365.69 3311.28   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 52715231.20 4992.15 23-JAN-18:10 6.02
February 12058431.06 4365.03 20-FEB-12:55 6.70
March 19412998.65 5068.23 03-MAR-00:55 6.70
April 9672410.11 3510.98 17-APR-07:50 5.68
May 1494254.04 1402.43 18-MAY-06:10 5.68
June 0.00 0.00 01-JUN-00:05 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 156085.98 1268.92 27-SEP-05:07 7.38
October 14792887.66 3964.27 30-OCT-05:03 7.20
November 35753426.73 6490.26 23-NOV-18:25 5.60
December 45215875.13 5754.40 02-DEC-07:16 6.10
         
Annual Sum or Average 0.191272E+09      
Minimum of Months 0.00 0.00   5.60
Maximum of Months 52715231.20 6490.26   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.100331E+10 2155.79 15-JAN-09:01 -2.5
February 0.597776E+09 2138.34 19-FEB-09:01 -3.1
March 0.297823E+09 2093.93 22-MAR-15:01 6.70
April 99630321.85 2059.07 18-APR-08:61 4.50
May 17498146.66 1840.14 18-MAY-08:62 6.28
June 1979255.50 777.28 18-JUN-08:03 12.57
July 1129302.65 825.74 16-JUL-15:04 17.80
August 1149720.02 739.32 27-AUG-15:04 18.42
September 6811244.45 927.30 27-SEP-08:62 9.08
October 0.138582E+09 2081.38 28-OCT-08:61 8.07
November 0.562939E+09 2156.53 14-NOV-19:01 5.68
December 0.918910E+09 2173.20 13-DEC-19:01 5.00
         
Annual Sum or Average 0.364754E+10      
Minimum of Months 1129302.65 739.32   -3.1
Maximum of Months 0.100331E+10 2173.20   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.115381E+10 2134.26 07-JAN-09:01 -3.1
February 0.761850E+09 2134.71 19-FEB-09:01 -3.1
March 0.405804E+09 2075.45 28-MAR-08:61 6.78
April 0.136220E+09 2030.65 18-APR-08:61 4.50
May 21561519.22 1877.47 18-MAY-08:62 6.28
June 2173729.89 749.90 18-JUN-08:03 12.57
July 959978.30 719.82 04-JUL-18:04 14.08
August 1285922.76 671.57 27-AUG-15:04 18.42
September 9057900.11 1427.39 28-SEP-08:62 10.28
October 0.204720E+09 2050.38 28-OCT-08:61 8.07
November 0.678759E+09 2115.34 14-NOV-19:01 5.68
December 0.107739E+10 2124.80 16-DEC-19:01 7.20
         
Annual Sum or Average 0.445359E+10      
Minimum of Months 959978.30 671.57   -3.1
Maximum of Months 0.115381E+10 2134.71   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 40488576.37 134.17 05-JAN-06:00 -1.1
February 11759313.24 163.53 19-FEB-06:00 -5.6
March 0.00 0.00 01-MAR-00:03 5.92
April 0.00 0.00 01-APR-00:05 7.93
May 0.00 0.00 01-MAY-00:05 10.38
June 0.00 0.00 01-JUN-00:05 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 5757096.89 81.06 30-NOV-24:00 4.40
December 44084253.84 148.33 26-DEC-04:03 -1.0
         
Annual Sum or Average 0.102089E+09      
Minimum of Months 0.00 0.00   -5.6
Maximum of Months 44084253.84 163.53   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.106213E+09 594.92 15-JAN-16:01 1.60
February 65363729.90 589.00 13-FEB-16:01 0.60
March 4939130.07 565.95 05-MAR-16:01 6.02
April 635379.45 383.03 25-APR-15:03 16.20
May 441378.79 302.83 12-MAY-15:05 16.78
June 230703.05 282.45 07-JUN-15:05 15.92
July 192508.31 238.00 25-JUL-08:06 15.18
August 178573.14 258.23 21-AUG-08:05 15.53
September 489146.89 233.35 24-SEP-15:05 16.20
October 1289144.60 548.72 31-OCT-15:01 10.82
November 30853068.15 580.96 30-NOV-16:01 4.50
December 84265552.09 590.40 26-DEC-16:02 3.27
         
Annual Sum or Average 0.295092E+09      
Minimum of Months 178573.14 233.35   0.60
Maximum of Months 0.106213E+09 594.92   16.78



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.100795E+10 2110.59 16-JAN-09:01 -0.5
February 0.600555E+09 2101.98 18-FEB-19:01 -0.8
March 0.287779E+09 2062.94 22-MAR-15:01 6.70
April 93177833.11 2023.84 18-APR-08:61 4.50
May 22745097.13 1806.77 18-MAY-08:62 6.28
June 2665606.26 608.73 02-JUN-18:04 19.45
July 1042865.97 739.66 16-JUL-15:04 17.80
August 939426.18 715.96 27-AUG-15:04 18.42
September 8934064.42 612.30 06-SEP-15:05 16.02
October 0.142011E+09 2042.13 31-OCT-18:01 8.80
November 0.565539E+09 2115.86 14-NOV-19:01 5.68
December 0.925772E+09 2131.42 13-DEC-19:01 5.00
         
Annual Sum or Average 0.365911E+10      
Minimum of Months 939426.18 608.73   -0.8
Maximum of Months 0.100795E+10 2131.42   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.116078E+10 2086.15 15-JAN-09:01 -2.5
February 0.762144E+09 2077.10 19-FEB-19:01 -1.1
March 0.385025E+09 2039.18 22-MAR-15:01 6.70
April 0.125466E+09 1994.61 18-APR-08:61 4.50
May 28571720.01 1840.69 18-MAY-08:62 6.28
June 3086911.26 529.21 29-JUN-15:05 17.30
July 920896.04 675.73 16-JUL-15:04 17.80
August 945325.67 692.58 27-AUG-15:04 18.42
September 11917282.19 987.39 26-SEP-15:02 11.97
October 0.207820E+09 2011.65 31-OCT-18:01 8.80
November 0.673786E+09 2077.17 14-NOV-19:01 5.68
December 0.107714E+10 2084.15 18-DEC-19:01 4.72
         
Annual Sum or Average 0.443760E+10      
Minimum of Months 920896.04 529.21   -2.5
Maximum of Months 0.116078E+10 2086.15   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 23531824.53 748.42 28-JAN-23:23 6.10
February 10825246.90 712.46 27-FEB-07:27 7.50
March 18072796.95 699.20 22-MAR-00:03 7.12
April 11534493.23 661.56 01-APR-05:24 7.75
May 6477641.86 452.29 20-MAY-03:40 7.80
June 183607.38 185.04 15-JUN-03:37 8.30
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 992741.97 518.35 27-SEP-05:07 7.38
October 20212261.96 776.88 30-OCT-05:03 7.20
November 18109774.86 770.26 29-NOV-00:02 7.35
December 30255852.81 1125.03 01-DEC-18:20 6.10
         
Annual Sum or Average 0.140196E+09      
Minimum of Months 0.00 0.00   6.10
Maximum of Months 30255852.81 1125.03   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.146684E+10 2553.44 15-JAN-09:01 -2.5
February 0.926414E+09 2537.29 19-FEB-09:01 -3.1
March 0.543364E+09 2507.76 22-MAR-15:01 6.70
April 0.225777E+09 2455.46 18-APR-08:61 4.50
May 72470261.77 2319.78 18-MAY-08:62 6.28
June 12975557.04 900.17 11-JUN-08:03 14.08
July 1534704.90 791.82 16-JUL-15:04 17.80
August 1534123.75 890.40 19-AUG-08:03 15.08
September 30640566.71 1896.92 27-SEP-08:62 9.08
October 0.303020E+09 2480.39 28-OCT-08:61 8.07
November 0.893988E+09 2542.82 14-NOV-19:01 5.68
December 0.136329E+10 2548.65 17-DEC-19:01 5.50
         
Annual Sum or Average 0.584185E+10      
Minimum of Months 1534123.75 791.82   -3.1
Maximum of Months 0.146684E+10 2553.44   17.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.165702E+10 2524.08 07-JAN-09:01 -3.1
February 0.113656E+10 2523.85 19-FEB-09:01 -3.1
March 0.696340E+09 2472.12 22-MAR-15:01 6.70
April 0.290905E+09 2416.98 18-APR-08:61 4.50
May 85429347.05 2292.73 27-MAY-08:61 8.48
June 15103484.29 708.62 11-JUN-08:03 14.08
July 1387940.36 902.63 16-JUL-15:04 17.80
August 1770262.47 785.83 19-AUG-08:03 15.08
September 42251695.14 2242.94 28-SEP-08:62 10.28
October 0.425740E+09 2437.59 28-OCT-08:61 8.07
November 0.104126E+10 2493.95 14-NOV-19:01 5.68
December 0.156304E+10 2506.61 25-DEC-19:01 -0.7
         
Annual Sum or Average 0.695681E+10      
Minimum of Months 1387940.36 708.62   -3.1
Maximum of Months 0.165702E+10 2524.08   17.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.439315E+09 1366.75 02-JAN-16:11 8.17
February 0.229948E+09 1352.78 17-FEB-09:01 1.02
March 93322242.35 1332.71 22-MAR-15:01 6.70
April 34290780.52 1313.07 18-APR-08:61 4.50
May 8827105.08 1160.82 18-MAY-08:62 6.28
June 1383768.60 564.24 23-JUN-15:04 16.88
July 786269.75 558.35 16-JUL-15:04 17.80
August 762519.03 440.84 21-AUG-08:03 15.53
September 3332202.08 485.45 21-SEP-15:04 17.30
October 33321703.46 1315.29 28-OCT-08:61 8.07
November 0.210849E+09 1367.82 14-NOV-19:01 5.68
December 0.407177E+09 1379.57 19-DEC-19:01 5.60
         
Annual Sum or Average 0.146332E+10      
Minimum of Months 762519.03 440.84   1.02
Maximum of Months 0.439315E+09 1379.57   17.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.92
February 0.00 0.00 01-FEB-00:03 7.00
March 116219.33 665.61 03-MAR-00:55 6.70
April 0.00 0.00 01-APR-00:05 7.93
May 0.00 0.00 01-MAY-00:05 10.38
June 0.00 0.00 01-JUN-00:05 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 58812.62 411.57 13-OCT-01:09 7.12
November 37455.74 190.92 17-NOV-08:11 6.87
December 24948.66 415.81 02-DEC-07:16 6.10
         
Annual Sum or Average 237436.35      
Minimum of Months 0.00 0.00   5.92
Maximum of Months 116219.33 665.61   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.92
February 0.00 0.00 01-FEB-00:03 7.00
March 42720.37 234.67 03-MAR-00:55 6.70
April 0.00 0.00 01-APR-00:05 7.93
May 0.00 0.00 01-MAY-00:05 10.38
June 0.00 0.00 01-JUN-00:05 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 4300.36 50.17 13-OCT-01:09 7.12
November 0.00 0.00 01-NOV-00:03 9.22
December 8086.64 134.78 02-DEC-07:16 6.10
         
Annual Sum or Average 55107.37      
Minimum of Months 0.00 0.00   5.92
Maximum of Months 42720.37 234.67   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 5.92
April 0.00 0.00 01-APR-00:05 7.93
May 0.00 0.00 01-MAY-00:05 10.38
June 0.00 0.00 01-JUN-00:05 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 27301.00 171.54 13-OCT-01:49 6.78
November 0.00 0.00 01-NOV-00:03 9.22
December 0.00 0.00 01-DEC-00:03 4.40
         
Annual Sum or Average 27301.00      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 27301.00 171.54   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 49313738.59 1524.52 30-JAN-22:39 5.60
February 33139515.70 1449.94 27-FEB-07:27 7.50
March 37932742.77 1471.86 03-MAR-00:55 6.70
April 29117099.72 1435.48 17-APR-07:50 5.68
May 22240481.74 1215.39 19-MAY-05:09 7.88
June 910142.47 646.86 15-JUN-03:37 8.30
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:05 17.17
September 3311869.10 1347.18 27-SEP-05:07 7.38
October 47994232.77 1672.56 30-OCT-05:03 7.20
November 34563475.23 1626.67 29-NOV-00:02 7.35
December 48656667.91 1943.64 10-DEC-19:47 6.78
         
Annual Sum or Average 0.307180E+09      
Minimum of Months 0.00 0.00   5.60
Maximum of Months 49313738.59 1943.64   17.17



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.147273E+11 14185.34 02-JAN-20:10 0.127587E+11 10113.80 02-JAN-20:10
February 0.132974E+11 14185.34 01-FEB-20:10 0.115208E+11 10113.80 01-FEB-20:10
March 0.147727E+11 14185.34 01-MAR-20:10 0.127855E+11 10113.80 01-MAR-20:10
April 0.142280E+11 14185.34 03-APR-19:10 0.123314E+11 10113.80 03-APR-19:10
May 0.147528E+11 14185.34 01-MAY-19:10 0.127741E+11 10113.80 01-MAY-19:10
June 0.142932E+11 14185.34 01-JUN-19:10 0.123716E+11 10113.80 01-JUN-19:10
July 0.146876E+11 14185.34 03-JUL-19:10 0.127338E+11 10113.80 03-JUL-19:10
August 0.147784E+11 14185.34 01-AUG-19:10 0.127894E+11 10113.80 01-AUG-19:10
September 0.142337E+11 14185.34 01-SEP-19:10 0.123352E+11 10113.80 01-SEP-19:10
October 0.147216E+11 14185.34 02-OCT-19:10 0.127549E+11 10113.80 02-OCT-19:10
November 0.142819E+11 14185.34 01-NOV-19:10 0.123659E+11 10113.80 01-NOV-19:10
December 0.146876E+11 14185.34 01-DEC-20:10 0.127338E+11 10113.80 01-DEC-20:10
             
Annual Sum or Average 0.173462E+12     0.150255E+12    
Minimum of Months 0.132974E+11 14185.34   0.115208E+11 10113.80  
Maximum of Months 0.147784E+11 14185.34   0.127894E+11 10113.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.731324E+09 704.41 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.660319E+09 704.41 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.733578E+09 704.41 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.706528E+09 704.41 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.732592E+09 704.41 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.709769E+09 704.41 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.729351E+09 704.41 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.733860E+09 704.41 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.706810E+09 704.41 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.731042E+09 704.41 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.709205E+09 704.41 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.729351E+09 704.41 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.861373E+10     0.101856E+11    
Minimum of Months 0.660319E+09 704.41   0.780982E+09 685.60  
Maximum of Months 0.733860E+09 704.41   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.846876E+09 815.72 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.764651E+09 815.72 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.849486E+09 815.72 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.818162E+09 815.72 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.848344E+09 815.72 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.821915E+09 815.72 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.844592E+09 815.72 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.849812E+09 815.72 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.818489E+09 815.72 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.846549E+09 815.72 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.821262E+09 815.72 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.844592E+09 815.72 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.997473E+10     0.117950E+11    
Minimum of Months 0.764651E+09 815.72   0.904380E+09 793.93  
Maximum of Months 0.849812E+09 815.72   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.141236E+10 1360.40 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.127524E+10 1360.40 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.141672E+10 1360.40 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.136448E+10 1360.40 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.141481E+10 1360.40 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.137074E+10 1360.40 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.140855E+10 1360.40 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.141726E+10 1360.40 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.136502E+10 1360.40 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.141182E+10 1360.40 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.136965E+10 1360.40 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.140855E+10 1360.40 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.166352E+11     0.124712E+11    
Minimum of Months 0.127524E+10 1360.40   0.956227E+09 839.45  
Maximum of Months 0.141726E+10 1360.40   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.236418E+09 227.72 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.213464E+09 227.72 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.237147E+09 227.72 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.228402E+09 227.72 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.236828E+09 227.72 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.229450E+09 227.72 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.235780E+09 227.72 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.237238E+09 227.72 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.228493E+09 227.72 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.236327E+09 227.72 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.229268E+09 227.72 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.235780E+09 227.72 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.278459E+10     0.359760E+10    
Minimum of Months 0.213464E+09 227.72   0.275845E+09 242.16  
Maximum of Months 0.237238E+09 227.72   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.370859E+09 357.21 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.334852E+09 357.21 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.372002E+09 357.21 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.358285E+09 357.21 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.371502E+09 357.21 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.359929E+09 357.21 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.369859E+09 357.21 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.372145E+09 357.21 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.358428E+09 357.21 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.370717E+09 357.21 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.359643E+09 357.21 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.369859E+09 357.21 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.436808E+10     0.679355E+11    
Minimum of Months 0.334852E+09 357.21   0.520895E+10 4572.80  
Maximum of Months 0.372145E+09 357.21   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.163951E+10 1761.91 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.144231E+10 1761.91 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.154951E+10 1761.91 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.142806E+10 1761.91 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.143166E+10 1761.91 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.133627E+10 1761.91 01-JUN-19:40 0.118076E+10 965.27 01-JUN-19:10
July 0.139613E+10 1761.91 03-JUL-19:00 0.121533E+10 965.27 03-JUL-19:10
August 0.144637E+10 1761.91 01-AUG-19:19 0.122063E+10 965.27 01-AUG-19:10
September 0.147816E+10 1761.91 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.158607E+10 1761.91 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.157370E+10 1761.91 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.163911E+10 1761.91 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.179469E+11     0.143405E+11    
Minimum of Months 0.133627E+10 1761.91   0.109956E+10 965.27  
Maximum of Months 0.163951E+10 1761.91   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104669E+11 10265.18 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.941056E+10 10265.18 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.104030E+11 10265.18 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.995618E+10 10265.18 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.102736E+11 10265.18 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.990700E+10 10265.18 01-JUN-19:30 0.122682E+11 10029.21 01-JUN-19:10
July 0.102020E+11 10265.18 03-JUL-19:49 0.126273E+11 10029.21 03-JUL-19:10
August 0.103054E+11 10265.18 01-AUG-19:19 0.126824E+11 10029.21 01-AUG-19:10
September 0.100074E+11 10265.18 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.104087E+11 10265.18 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.101340E+11 10265.18 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.104437E+11 10265.18 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.121918E+12     0.148998E+12    
Minimum of Months 0.941056E+10 10265.18   0.114244E+11 10029.21  
Maximum of Months 0.104669E+11 10265.18   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85091918.49 76.99 01-JAN-19:10 0.255708E+09 232.19 01-JAN-08:09
February 76846309.13 76.99 01-FEB-20:10 0.230956E+09 232.19 01-FEB-07:10
March 84415649.14 76.99 01-MAR-20:10 0.255355E+09 232.19 01-MAR-07:10
April 82445007.08 76.99 01-APR-18:10 0.247516E+09 232.19 01-APR-07:10
May 84753783.81 76.99 01-MAY-19:10 0.255532E+09 232.19 01-MAY-06:10
June 81790910.76 76.99 01-JUN-19:10 0.247163E+09 232.19 01-JUN-06:10
July 85418966.65 76.99 01-JUL-18:10 0.255885E+09 232.19 01-JUL-07:10
August 84415649.14 76.99 01-AUG-19:10 0.255355E+09 232.19 01-AUG-06:10
September 82467180.11 76.99 01-SEP-19:10 0.247516E+09 232.19 01-SEP-06:10
October 85080831.98 76.99 01-OCT-18:10 0.255708E+09 232.19 01-OCT-07:10
November 82117958.92 76.99 01-NOV-19:10 0.247340E+09 232.19 01-NOV-06:10
December 85430053.17 76.99 01-DEC-20:10 0.255885E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.100027E+10     0.300992E+10    
Minimum of Months 76846309.13 76.99   0.230956E+09 232.19  
Maximum of Months 85430053.17 76.99   0.255885E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85115186.72 77.01 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 76867322.62 77.01 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 84438732.44 77.01 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 82467551.52 77.01 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 84776959.58 77.01 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 81813276.33 77.01 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 85442324.32 77.01 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 84438732.44 77.01 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 82489730.61 77.01 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 85104097.18 77.01 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 82140413.93 77.01 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 85453413.86 77.01 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.100055E+10     0.301074E+10    
Minimum of Months 76867322.62 77.01   0.231020E+09 232.26  
Maximum of Months 85453413.86 77.01   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.232638E+10 2240.78 02-JAN-20:10 0.00 0.00
February 0.210051E+10 2240.78 01-FEB-20:10 0.00 0.00
March 0.233355E+10 2240.78 01-MAR-20:10 0.00 0.00
April 0.224750E+10 2240.78 03-APR-19:10 0.00 0.00
May 0.233041E+10 2240.78 01-MAY-19:10 0.00 0.00
June 0.225781E+10 2240.78 01-JUN-19:10 0.00 0.00
July 0.232011E+10 2240.78 03-JUL-19:10 0.00 0.00
August 0.233445E+10 2240.78 01-AUG-19:10 0.00 0.00
September 0.224840E+10 2240.78 01-SEP-19:10 0.00 0.00
October 0.232548E+10 2240.78 02-OCT-19:10 0.00 0.00
November 0.225602E+10 2240.78 01-NOV-19:10 0.00 0.00
December 0.232011E+10 2240.78 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.274007E+11     0.00 0.00
Minimum of Months 0.210051E+10 2240.78   0.00 0.00
Maximum of Months 0.233445E+10 2240.78   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85115186.72 77.01 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 76867322.62 77.01 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 84438732.44 77.01 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 82467551.52 77.01 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 84776959.58 77.01 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 81813276.33 77.01 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 85442324.32 77.01 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 84438732.44 77.01 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 82489730.61 77.01 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 85104097.18 77.01 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 82140413.93 77.01 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 85453413.86 77.01 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.100055E+10     0.301074E+10    
Minimum of Months 76867322.62 77.01   0.231020E+09 232.26  
Maximum of Months 85453413.86 77.01   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.305847E+10 3094.06 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.272414E+10 3094.06 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.297416E+10 3094.06 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.279895E+10 3094.06 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.285332E+10 3094.06 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.271329E+10 3094.06 01-JUN-19:40 0.144540E+11 6747.90 01-JUN-06:10
July 0.280106E+10 3094.06 10-JUL-19:30 0.149358E+11 6747.90 01-JUL-06:10
August 0.286712E+10 3094.06 01-AUG-19:19 0.149358E+11 6747.90 01-AUG-06:10
September 0.285021E+10 3094.06 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.300644E+10 3094.06 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.294968E+10 3094.06 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.305788E+10 3094.06 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.346547E+11     0.175857E+12    
Minimum of Months 0.271329E+10 3094.06   0.134904E+11 6747.90  
Maximum of Months 0.305847E+10 3094.06   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.305847E+10 3094.06 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.272414E+10 3094.06 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.297416E+10 3094.06 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.279895E+10 3094.06 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.285332E+10 3094.06 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.271329E+10 3094.06 01-JUN-19:40 0.144540E+11 6747.90 01-JUN-06:10
July 0.280106E+10 3094.06 10-JUL-19:30 0.149358E+11 6747.90 01-JUL-06:10
August 0.286712E+10 3094.06 01-AUG-19:19 0.149358E+11 6747.90 01-AUG-06:10
September 0.285021E+10 3094.06 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.300644E+10 3094.06 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.294968E+10 3094.06 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.305788E+10 3094.06 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.346547E+11     0.175857E+12    
Minimum of Months 0.271329E+10 3094.06   0.134904E+11 6747.90  
Maximum of Months 0.305847E+10 3094.06   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.113146E+10 1089.83 02-JAN-20:10 0.368383E+11 16487.34 01-JAN-07:10
February 0.102161E+10 1089.83 01-FEB-20:10 0.332733E+11 16487.34 01-FEB-07:10
March 0.113495E+10 1089.83 01-MAR-20:10 0.368383E+11 16487.34 01-MAR-07:10
April 0.109310E+10 1089.83 03-APR-19:10 0.356500E+11 16487.34 01-APR-06:10
May 0.113342E+10 1089.83 01-MAY-19:10 0.368383E+11 16487.34 01-MAY-06:10
June 0.109811E+10 1089.83 01-JUN-19:10 0.356500E+11 16487.34 01-JUN-06:10
July 0.112841E+10 1089.83 03-JUL-19:10 0.368383E+11 16487.34 01-JUL-06:10
August 0.113539E+10 1089.83 01-AUG-19:10 0.368383E+11 16487.34 01-AUG-06:10
September 0.109354E+10 1089.83 01-SEP-19:10 0.356500E+11 16487.34 01-SEP-06:10
October 0.113103E+10 1089.83 02-OCT-19:10 0.368383E+11 16487.34 01-OCT-06:10
November 0.109724E+10 1089.83 01-NOV-19:10 0.356500E+11 16487.34 01-NOV-06:10
December 0.112841E+10 1089.83 01-DEC-20:10 0.368383E+11 16487.34 01-DEC-07:10
             
Annual Sum or Average 0.133267E+11     0.433742E+12    
Minimum of Months 0.102161E+10 1089.83   0.332733E+11 16487.34  
Maximum of Months 0.113539E+10 1089.83   0.368383E+11 16487.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.246211E+10 2371.52 02-JAN-20:10 0.00 0.00
February 0.222306E+10 2371.52 01-FEB-20:10 0.00 0.00
March 0.246970E+10 2371.52 01-MAR-20:10 0.00 0.00
April 0.237864E+10 2371.52 03-APR-19:10 0.00 0.00
May 0.246638E+10 2371.52 01-MAY-19:10 0.00 0.00
June 0.238954E+10 2371.52 01-JUN-19:10 0.00 0.00
July 0.245547E+10 2371.52 03-JUL-19:10 0.00 0.00
August 0.247065E+10 2371.52 01-AUG-19:10 0.00 0.00
September 0.237958E+10 2371.52 01-SEP-19:10 0.00 0.00
October 0.246116E+10 2371.52 02-OCT-19:10 0.00 0.00
November 0.238765E+10 2371.52 01-NOV-19:10 0.00 0.00
December 0.245547E+10 2371.52 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.289994E+11     0.00 0.00
Minimum of Months 0.222306E+10 2371.52   0.00 0.00
Maximum of Months 0.247065E+10 2371.52   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.147273E+11 0.127587E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.132974E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.147727E+11 0.127855E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.142280E+11 0.123314E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.147528E+11 0.127741E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.142932E+11 0.123716E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.146876E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.147784E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.142337E+11 0.123352E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.147216E+11 0.127549E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.142819E+11 0.123659E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.146876E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.173462E+12 0.150255E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.132974E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.147784E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.731324E+09 0.864900E+09 0.00 0.00 0.00 0.00 0.00 0.552174E+09
February 0.179968E+10 0.660319E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.458411E+09
March 0.199990E+10 0.733578E+09 0.866718E+09 0.00 0.00 0.00 0.00 0.00 0.426248E+09
April 0.192973E+10 0.706528E+09 0.835931E+09 0.00 0.00 0.00 0.00 1507342.39 0.335918E+09
May 0.199475E+10 0.732592E+09 0.865939E+09 0.00 0.00 0.00 0.00 567217.13 0.277382E+09
June 0.193394E+10 0.709769E+09 0.838659E+09 0.00 0.00 0.00 0.00 2028503.61 0.186826E+09
July 0.199054E+10 0.729351E+09 0.863211E+09 0.00 0.00 0.00 0.00 8749374.86 0.144174E+09
August 0.199896E+10 0.733860E+09 0.866978E+09 0.00 0.00 0.00 0.00 16577804.44 0.119928E+09
September 0.192879E+10 0.706810E+09 0.836191E+09 0.00 0.00 0.00 0.00 177249.10 0.208666E+09
October 0.199148E+10 0.731042E+09 0.864640E+09 0.00 0.00 0.00 0.00 0.00 0.324523E+09
November 0.192552E+10 0.709205E+09 0.838269E+09 0.00 0.00 0.00 0.00 0.00 0.416150E+09
December 0.199054E+10 0.729351E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.00 0.521793E+09
                   
Annual Sum or Average 0.234744E+11 0.861373E+10 0.101856E+11 0.00 0.00 0.00 0.00 29607491.52 0.397219E+10
Minimum of Months 0.179968E+10 0.660319E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.119928E+09
Maximum of Months 0.199990E+10 0.733860E+09 0.866978E+09 0.00 0.00 0.00 0.00 16577804.44 0.552174E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.846876E+09 0.100156E+10 0.00 0.00 0.00 0.00 0.00 0.221075E+09
February 0.208403E+10 0.764651E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 0.185667E+09
March 0.231589E+10 0.849486E+09 0.100366E+10 0.00 0.00 0.00 0.00 0.00 0.178005E+09
April 0.223463E+10 0.818162E+09 0.968011E+09 0.00 0.00 0.00 0.00 693627.97 0.144784E+09
May 0.230993E+10 0.848344E+09 0.100276E+10 0.00 0.00 0.00 0.00 198787.33 0.124728E+09
June 0.223950E+10 0.821915E+09 0.971170E+09 0.00 0.00 0.00 0.00 580727.24 89956306.54
July 0.230505E+10 0.844592E+09 0.999601E+09 0.00 0.00 0.00 0.00 3116861.03 73028324.99
August 0.231480E+10 0.849812E+09 0.100396E+10 0.00 0.00 0.00 0.00 6381287.68 62762288.96
September 0.223354E+10 0.818489E+09 0.968312E+09 0.00 0.00 0.00 0.00 113413.63 96775535.48
October 0.230614E+10 0.846549E+09 0.100126E+10 0.00 0.00 0.00 0.00 0.00 0.140537E+09
November 0.222975E+10 0.821262E+09 0.970719E+09 0.00 0.00 0.00 0.00 0.00 0.172017E+09
December 0.230505E+10 0.844592E+09 0.999601E+09 0.00 0.00 0.00 0.00 0.00 0.210293E+09
                   
Annual Sum or Average 0.271834E+11 0.997473E+10 0.117950E+11 0.00 0.00 0.00 0.00 11084704.88 0.169963E+10
Minimum of Months 0.208403E+10 0.764651E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 62762288.96
Maximum of Months 0.231589E+10 0.849812E+09 0.100396E+10 0.00 0.00 0.00 0.00 6381287.68 0.221075E+09



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.141236E+10 0.105898E+10 0.00 0.00 0.00 0.00 0.00 0.505112E+09
February 0.440737E+09 0.127524E+10 0.956227E+09 0.00 0.00 0.00 0.00 0.00 0.419026E+09
March 0.489771E+09 0.141672E+10 0.106120E+10 0.00 0.00 0.00 0.00 0.00 0.396646E+09
April 0.472586E+09 0.136448E+10 0.102351E+10 0.00 0.00 0.00 0.00 2265437.36 0.322818E+09
May 0.488511E+09 0.141481E+10 0.106025E+10 0.00 0.00 0.00 0.00 832855.19 0.281232E+09
June 0.473617E+09 0.137074E+10 0.102685E+10 0.00 0.00 0.00 0.00 1733102.48 0.205017E+09
July 0.487480E+09 0.140855E+10 0.105691E+10 0.00 0.00 0.00 0.00 7807777.55 0.167323E+09
August 0.489542E+09 0.141726E+10 0.106152E+10 0.00 0.00 0.00 0.00 15755070.58 0.144847E+09
September 0.472357E+09 0.136502E+10 0.102382E+10 0.00 0.00 0.00 0.00 678324.80 0.218267E+09
October 0.487709E+09 0.141182E+10 0.105866E+10 0.00 0.00 0.00 0.00 0.00 0.314355E+09
November 0.471555E+09 0.136965E+10 0.102637E+10 0.00 0.00 0.00 0.00 0.00 0.387872E+09
December 0.487480E+09 0.140855E+10 0.105691E+10 0.00 0.00 0.00 0.00 0.00 0.476767E+09
                   
Annual Sum or Average 0.574883E+10 0.166352E+11 0.124712E+11 0.00 0.00 0.00 0.00 29072567.96 0.383928E+10
Minimum of Months 0.440737E+09 0.127524E+10 0.956227E+09 0.00 0.00 0.00 0.00 0.00 0.144847E+09
Maximum of Months 0.489771E+09 0.141726E+10 0.106152E+10 0.00 0.00 0.00 0.00 15755070.58 0.505112E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.236418E+09 0.305485E+09 0.00 0.00 0.00 0.00 0.00 0.289883E+09
February 0.339028E+09 0.213464E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 0.239562E+09
March 0.376747E+09 0.237147E+09 0.306128E+09 0.00 0.00 0.00 0.00 0.00 0.224260E+09
April 0.363528E+09 0.228402E+09 0.295253E+09 0.00 0.00 0.00 0.00 1345363.78 0.181970E+09
May 0.375778E+09 0.236828E+09 0.305852E+09 0.00 0.00 0.00 0.00 516299.79 0.158021E+09
June 0.364321E+09 0.229450E+09 0.296217E+09 0.00 0.00 0.00 0.00 1098878.63 0.114514E+09
July 0.374985E+09 0.235780E+09 0.304889E+09 0.00 0.00 0.00 0.00 4719138.45 92977003.79
August 0.376571E+09 0.237238E+09 0.306219E+09 0.00 0.00 0.00 0.00 9429318.51 80308877.51
September 0.363352E+09 0.228493E+09 0.295345E+09 0.00 0.00 0.00 0.00 412721.50 0.122011E+09
October 0.375161E+09 0.236327E+09 0.305393E+09 0.00 0.00 0.00 0.00 0.00 0.176734E+09
November 0.362735E+09 0.229268E+09 0.296079E+09 0.00 0.00 0.00 0.00 0.00 0.220472E+09
December 0.374985E+09 0.235780E+09 0.304889E+09 0.00 0.00 0.00 0.00 0.00 0.273098E+09
                   
Annual Sum or Average 0.442217E+10 0.278459E+10 0.359760E+10 0.00 0.00 0.00 0.00 17521720.66 0.217381E+10
Minimum of Months 0.339028E+09 0.213464E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 80308877.51
Maximum of Months 0.376747E+09 0.237238E+09 0.306219E+09 0.00 0.00 0.00 0.00 9429318.51 0.289883E+09



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.370859E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 0.00 0.770533E+09
February 0.139600E+10 0.334852E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.639778E+09
March 0.155131E+10 0.372002E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 0.00 0.605114E+09
April 0.149688E+10 0.358285E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 2215368.69 0.485693E+09
May 0.154732E+10 0.371502E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 1074452.33 0.411354E+09
June 0.150015E+10 0.359929E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 2208660.35 0.292676E+09
July 0.154405E+10 0.369859E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 11725381.15 0.229684E+09
August 0.155059E+10 0.372145E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 23353835.62 0.196229E+09
September 0.149615E+10 0.358428E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 1268195.75 0.312947E+09
October 0.154478E+10 0.370717E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 0.00 0.473375E+09
November 0.149361E+10 0.359643E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 0.00 0.597833E+09
December 0.154405E+10 0.369859E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.00 0.731739E+09
                   
Annual Sum or Average 0.182090E+11 0.436808E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 41845893.88 0.574696E+10
Minimum of Months 0.139600E+10 0.334852E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.196229E+09
Maximum of Months 0.155131E+10 0.372145E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 23353835.62 0.770533E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.163951E+10 0.121771E+10 0.00 0.00 0.00 0.00 0.00 0.124752E+10
February 0.236489E+11 0.144231E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.104950E+10
March 0.262800E+11 0.154951E+10 0.122027E+10 0.00 0.00 0.00 0.00 0.00 0.998007E+09
April 0.253579E+11 0.142806E+10 0.117692E+10 0.00 0.00 0.00 0.00 2858530.66 0.804653E+09
May 0.262123E+11 0.143166E+10 0.121917E+10 0.00 0.00 0.00 0.00 770295.64 0.681724E+09
June 0.254132E+11 0.133627E+10 0.118076E+10 0.00 0.00 0.00 0.00 3111627.92 0.482730E+09
July 0.261570E+11 0.139613E+10 0.121533E+10 0.00 0.00 0.00 0.00 17210401.98 0.387386E+09
August 0.262677E+11 0.144637E+10 0.122063E+10 0.00 0.00 0.00 0.00 33901988.95 0.330096E+09
September 0.253456E+11 0.147816E+10 0.117729E+10 0.00 0.00 0.00 0.00 277574.98 0.527575E+09
October 0.261693E+11 0.158607E+10 0.121734E+10 0.00 0.00 0.00 0.00 0.00 0.781365E+09
November 0.253025E+11 0.157370E+10 0.118021E+10 0.00 0.00 0.00 0.00 0.00 0.958494E+09
December 0.261570E+11 0.163911E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.00 0.118466E+10
                   
Annual Sum or Average 0.308468E+12 0.179469E+11 0.143405E+11 0.00 0.00 0.00 0.00 58130420.13 0.943371E+10
Minimum of Months 0.236489E+11 0.133627E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.330096E+09
Maximum of Months 0.262800E+11 0.163951E+10 0.122063E+10 0.00 0.00 0.00 0.00 33901988.95 0.124752E+10



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.104669E+11 0.126520E+11 0.00 0.00 0.00 0.00 0.00 0.371768E+10
February 0.702046E+11 0.941056E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.313208E+10
March 0.780153E+11 0.104030E+11 0.126786E+11 0.00 0.00 0.00 0.00 0.00 0.300923E+10
April 0.752779E+11 0.995618E+10 0.122282E+11 0.00 0.00 0.00 0.00 9486330.06 0.244882E+10
May 0.778146E+11 0.102736E+11 0.126672E+11 0.00 0.00 0.00 0.00 2277806.46 0.210720E+10
June 0.754422E+11 0.990700E+10 0.122682E+11 0.00 0.00 0.00 0.00 7894664.33 0.153067E+10
July 0.776503E+11 0.102020E+11 0.126273E+11 0.00 0.00 0.00 0.00 47959382.77 0.123506E+10
August 0.779788E+11 0.103054E+11 0.126824E+11 0.00 0.00 0.00 0.00 96653089.38 0.106202E+10
September 0.752414E+11 0.100074E+11 0.122320E+11 0.00 0.00 0.00 0.00 950265.33 0.164243E+10
October 0.776868E+11 0.104087E+11 0.126482E+11 0.00 0.00 0.00 0.00 0.00 0.238885E+10
November 0.751137E+11 0.101340E+11 0.122624E+11 0.00 0.00 0.00 0.00 0.00 0.290768E+10
December 0.776503E+11 0.104437E+11 0.126273E+11 0.00 0.00 0.00 0.00 0.00 0.353926E+10
                   
Annual Sum or Average 0.915726E+12 0.121918E+12 0.148998E+12 0.00 0.00 0.00 0.00 0.165222E+09 0.287210E+11
Minimum of Months 0.702046E+11 0.941056E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.106202E+10
Maximum of Months 0.780153E+11 0.104669E+11 0.126824E+11 0.00 0.00 0.00 0.00 96653089.38 0.371768E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.313975E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.262319E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.00 0.245503E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 1324402.25 0.196041E+09
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 764531.18 0.163321E+09
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 1825824.17 0.111518E+09
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 7274405.44 82909699.23
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 13812637.84 68322560.28
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 1046698.68 0.118721E+09
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 4042.57 0.186401E+09
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 0.237926E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.296757E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 26052542.12 0.228371E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 68322560.28
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 13812637.84 0.313975E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.311521E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.258612E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.00 0.241507E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 1380422.05 0.193245E+09
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 769727.71 0.161931E+09
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 1823218.39 0.110548E+09
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 7319392.84 82329602.63
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 13982538.09 67660013.54
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 1073638.62 0.117017E+09
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 4177.68 0.182629E+09
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 0.235264E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.293713E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 26353115.37 0.225598E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 67660013.54
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 13982538.09 0.311521E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 85091918.49 0.255708E+09 0.00 0.00 0.00 0.00 0.00 80962146.16
February 0.00 76846309.13 0.230956E+09 0.00 0.00 0.00 0.00 0.00 71374084.53
March 0.00 84415649.14 0.255355E+09 0.00 0.00 0.00 0.00 0.00 72463549.39
April 0.00 82445007.08 0.247516E+09 0.00 0.00 0.00 0.00 237966.67 61109732.01
May 0.00 84753783.81 0.255532E+09 0.00 0.00 0.00 0.00 51798.44 52637666.91
June 0.00 81790910.76 0.247163E+09 0.00 0.00 0.00 0.00 187473.92 38335808.44
July 0.00 85418966.65 0.255885E+09 0.00 0.00 0.00 0.00 1246166.61 30312928.63
August 0.00 84415649.14 0.255355E+09 0.00 0.00 0.00 0.00 2647843.49 25863012.76
September 0.00 82467180.11 0.247516E+09 0.00 0.00 0.00 0.00 58417.66 40663145.29
October 0.00 85080831.98 0.255708E+09 0.00 0.00 0.00 0.00 0.00 58486402.74
November 0.00 82117958.92 0.247340E+09 0.00 0.00 0.00 0.00 0.00 64963067.30
December 0.00 85430053.17 0.255885E+09 0.00 0.00 0.00 0.00 0.00 78172028.81
                   
Annual Sum or Average 0.00 0.100027E+10 0.300992E+10 0.00 0.00 0.00 0.00 4429666.79 0.675344E+09
Minimum of Months 0.00 76846309.13 0.230956E+09 0.00 0.00 0.00 0.00 0.00 25863012.76
Maximum of Months 0.00 85430053.17 0.255885E+09 0.00 0.00 0.00 0.00 2647843.49 80962146.16



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 85115186.72 0.255778E+09 0.00 0.00 0.00 0.00 0.00 88560578.47
February 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 0.00 73190807.50
March 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 0.00 68060137.78
April 0.293479E+09 82467551.52 0.247584E+09 0.00 0.00 0.00 0.00 481540.14 53849727.09
May 0.303504E+09 84776959.58 0.255602E+09 0.00 0.00 0.00 0.00 297317.48 44502602.24
June 0.293842E+09 81813276.33 0.247231E+09 0.00 0.00 0.00 0.00 621096.22 30078599.13
July 0.303141E+09 85442324.32 0.255955E+09 0.00 0.00 0.00 0.00 2358865.07 22153413.64
August 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 4433044.29 18290868.33
September 0.293479E+09 82489730.61 0.247584E+09 0.00 0.00 0.00 0.00 411927.24 31961090.44
October 0.303322E+09 85104097.18 0.255778E+09 0.00 0.00 0.00 0.00 1673.21 51263508.14
November 0.293661E+09 82140413.93 0.247408E+09 0.00 0.00 0.00 0.00 0.00 66951575.47
December 0.303141E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 0.00 83438339.27
                   
Annual Sum or Average 0.357224E+10 0.100055E+10 0.301074E+10 0.00 0.00 0.00 0.00 8605463.65 0.632301E+09
Minimum of Months 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 0.00 18290868.33
Maximum of Months 0.303685E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 4433044.29 88560578.47



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.313712E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.262418E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.00 0.246613E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 1351119.12 0.197696E+09
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 795772.48 0.163808E+09
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 1857633.08 0.112498E+09
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 7355134.34 83375856.19
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 13844669.30 68926902.05
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 1082766.50 0.118844E+09
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 4256.10 0.187077E+09
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 0.237799E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.296430E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 26291350.92 0.228920E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 68926902.05
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 13844669.30 0.313712E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.311395E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.258508E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.00 0.242739E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 1408227.88 0.195471E+09
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 802270.19 0.162902E+09
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 1862559.57 0.112146E+09
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 7375192.20 83182333.42
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 13883097.23 68603295.79
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 1103274.59 0.117609E+09
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 4529.56 0.183552E+09
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 0.235105E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.293396E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 26439151.22 0.226461E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 68603295.79
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 13883097.23 0.311395E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.232638E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.387517E+09
February 0.348285E+10 0.210051E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.320328E+09
March 0.387034E+10 0.233355E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.301106E+09
April 0.373454E+10 0.224750E+10 0.00 0.00 0.00 0.00 0.00 1571465.23 0.246078E+09
May 0.386038E+10 0.233041E+10 0.00 0.00 0.00 0.00 0.00 443229.79 0.215709E+09
June 0.374269E+10 0.225781E+10 0.00 0.00 0.00 0.00 0.00 1122858.36 0.155875E+09
July 0.385223E+10 0.232011E+10 0.00 0.00 0.00 0.00 0.00 5545241.74 0.126648E+09
August 0.386853E+10 0.233445E+10 0.00 0.00 0.00 0.00 0.00 11288907.95 0.110049E+09
September 0.373273E+10 0.224840E+10 0.00 0.00 0.00 0.00 0.00 245353.47 0.166485E+09
October 0.385404E+10 0.232548E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.235811E+09
November 0.372639E+10 0.225602E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.292906E+09
December 0.385223E+10 0.232011E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.365330E+09
                   
Annual Sum or Average 0.454292E+11 0.274007E+11 0.00 0.00 0.00 0.00 0.00 20217056.53 0.292384E+10
Minimum of Months 0.348285E+10 0.210051E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.110049E+09
Maximum of Months 0.387034E+10 0.233445E+10 0.00 0.00 0.00 0.00 0.00 11288907.95 0.387517E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.313538E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.261792E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.00 0.245111E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 1290481.89 0.196230E+09
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 710116.92 0.163881E+09
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 1756820.24 0.112224E+09
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 7092876.09 83581357.26
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 13528207.03 68763207.19
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 996948.50 0.119052E+09
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 2863.31 0.186086E+09
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 0.237274E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.296482E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 25378313.99 0.228401E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 68763207.19
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 13528207.03 0.313538E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.311790E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.258234E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.00 0.240871E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 1336809.37 0.193289E+09
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 717891.28 0.162529E+09
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 1750999.57 0.111401E+09
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 7109079.14 83103471.69
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 13658161.68 68097668.42
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 1034784.32 0.117320E+09
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 3126.25 0.181899E+09
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 0.234755E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.293688E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 25610851.61 0.225698E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 68097668.42
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 13658161.68 0.311790E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 85115186.72 0.255778E+09 0.00 0.00 0.00 0.00 0.00 0.163776E+09
February 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 0.00 0.136940E+09
March 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 0.00 0.127960E+09
April 0.293479E+09 82467551.52 0.247584E+09 0.00 0.00 0.00 0.00 666953.35 0.101786E+09
May 0.303504E+09 84776959.58 0.255602E+09 0.00 0.00 0.00 0.00 386340.43 84215640.36
June 0.293842E+09 81813276.33 0.247231E+09 0.00 0.00 0.00 0.00 918692.01 57588381.59
July 0.303141E+09 85442324.32 0.255955E+09 0.00 0.00 0.00 0.00 3676191.37 42756741.37
August 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 6946393.46 35263233.09
September 0.293479E+09 82489730.61 0.247584E+09 0.00 0.00 0.00 0.00 523280.67 61455113.81
October 0.303322E+09 85104097.18 0.255778E+09 0.00 0.00 0.00 0.00 1135.56 97335296.41
November 0.293661E+09 82140413.93 0.247408E+09 0.00 0.00 0.00 0.00 0.00 0.124328E+09
December 0.303141E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 0.00 0.154712E+09
                   
Annual Sum or Average 0.357224E+10 0.100055E+10 0.301074E+10 0.00 0.00 0.00 0.00 13118986.87 0.118812E+10
Minimum of Months 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 0.00 35263233.09
Maximum of Months 0.303685E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 6946393.46 0.163776E+09



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.305847E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.904023E+09
February 0.415303E+11 0.272414E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.755530E+09
March 0.461508E+11 0.297416E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.723306E+09
April 0.445315E+11 0.279895E+10 0.144540E+11 0.00 0.00 0.00 0.00 1440644.59 0.588573E+09
May 0.460320E+11 0.285332E+10 0.149358E+11 0.00 0.00 0.00 0.00 83899.06 0.508209E+09
June 0.446286E+11 0.271329E+10 0.144540E+11 0.00 0.00 0.00 0.00 766984.11 0.373584E+09
July 0.459349E+11 0.280106E+10 0.149358E+11 0.00 0.00 0.00 0.00 8132988.82 0.299212E+09
August 0.461292E+11 0.286712E+10 0.149358E+11 0.00 0.00 0.00 0.00 18258841.99 0.257240E+09
September 0.445099E+11 0.285021E+10 0.144540E+11 0.00 0.00 0.00 0.00 116020.65 0.394129E+09
October 0.459565E+11 0.300644E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.573223E+09
November 0.444343E+11 0.294968E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.708933E+09
December 0.459349E+11 0.305788E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.859626E+09
                   
Annual Sum or Average 0.541708E+12 0.346547E+11 0.175857E+12 0.00 0.00 0.00 0.00 28799379.21 0.694559E+10
Minimum of Months 0.415303E+11 0.271329E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.257240E+09
Maximum of Months 0.461508E+11 0.305847E+10 0.149358E+11 0.00 0.00 0.00 0.00 18258841.99 0.904023E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.305847E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.913268E+09
February 0.415303E+11 0.272414E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.762891E+09
March 0.461508E+11 0.297416E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.729236E+09
April 0.445315E+11 0.279895E+10 0.144540E+11 0.00 0.00 0.00 0.00 1426117.70 0.592539E+09
May 0.460320E+11 0.285332E+10 0.149358E+11 0.00 0.00 0.00 0.00 83890.63 0.510674E+09
June 0.446286E+11 0.271329E+10 0.144540E+11 0.00 0.00 0.00 0.00 766947.94 0.375152E+09
July 0.459349E+11 0.280106E+10 0.149358E+11 0.00 0.00 0.00 0.00 8100348.25 0.300096E+09
August 0.461292E+11 0.286712E+10 0.149358E+11 0.00 0.00 0.00 0.00 18130003.44 0.258312E+09
September 0.445099E+11 0.285021E+10 0.144540E+11 0.00 0.00 0.00 0.00 116008.38 0.396418E+09
October 0.459565E+11 0.300644E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.578364E+09
November 0.444343E+11 0.294968E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.716261E+09
December 0.459349E+11 0.305788E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.868627E+09
                   
Annual Sum or Average 0.541708E+12 0.346547E+11 0.175857E+12 0.00 0.00 0.00 0.00 28623316.35 0.700184E+10
Minimum of Months 0.415303E+11 0.271329E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.258312E+09
Maximum of Months 0.461508E+11 0.305847E+10 0.149358E+11 0.00 0.00 0.00 0.00 18130003.44 0.913268E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.113146E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.823142E+09
February 0.369574E+10 0.102161E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.685330E+09
March 0.410691E+10 0.113495E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.655398E+09
April 0.396281E+10 0.109310E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 1283727.94 0.530190E+09
May 0.409635E+10 0.113342E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 77256.76 0.454785E+09
June 0.397146E+10 0.109811E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 694429.66 0.332975E+09
July 0.408770E+10 0.112841E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 7265200.08 0.266236E+09
August 0.410499E+10 0.113539E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 16221786.92 0.229549E+09
September 0.396089E+10 0.109354E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 106706.07 0.353285E+09
October 0.408962E+10 0.113103E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.518686E+09
November 0.395417E+10 0.109724E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.645159E+09
December 0.408770E+10 0.112841E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.783907E+09
                   
Annual Sum or Average 0.482060E+11 0.133267E+11 0.392709E+12 0.359593E+12 0.00 0.00 0.00 25649107.42 0.627864E+10
Minimum of Months 0.369574E+10 0.102161E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.229549E+09
Maximum of Months 0.410691E+10 0.113539E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 16221786.92 0.823142E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.246211E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.688190E+09
February 0.368610E+10 0.222306E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.569728E+09
March 0.409620E+10 0.246970E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.534413E+09
April 0.395248E+10 0.237864E+10 0.00 0.00 0.00 0.00 0.00 2029053.84 0.435185E+09
May 0.408566E+10 0.246638E+10 0.00 0.00 0.00 0.00 0.00 245387.31 0.380416E+09
June 0.396110E+10 0.238954E+10 0.00 0.00 0.00 0.00 0.00 965927.56 0.278554E+09
July 0.407704E+10 0.245547E+10 0.00 0.00 0.00 0.00 0.00 7634111.87 0.226596E+09
August 0.409429E+10 0.247065E+10 0.00 0.00 0.00 0.00 0.00 16928434.14 0.191638E+09
September 0.395056E+10 0.237958E+10 0.00 0.00 0.00 0.00 0.00 155413.21 0.291386E+09
October 0.407896E+10 0.246116E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.414119E+09
November 0.394385E+10 0.238765E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.521116E+09
December 0.407704E+10 0.245547E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.649032E+09
                   
Annual Sum or Average 0.480803E+11 0.289994E+11 0.00 0.00 0.00 0.00 0.00 27958327.93 0.518037E+10
Minimum of Months 0.368610E+10 0.222306E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.191638E+09
Maximum of Months 0.409620E+10 0.247065E+10 0.00 0.00 0.00 0.00 0.00 16928434.14 0.688190E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 14185.34 02-JAN-20:10 10113.80 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 14185.34 01-FEB-20:10 10113.80 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 14185.34 01-MAR-20:10 10113.80 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 14185.34 03-APR-19:10 10113.80 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 14185.34 01-MAY-19:10 10113.80 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 14185.34 01-JUN-19:10 10113.80 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 14185.34 03-JUL-19:10 10113.80 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 14185.34 01-AUG-19:10 10113.80 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 14185.34 01-SEP-19:10 10113.80 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 14185.34 02-OCT-19:10 10113.80 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 14185.34 01-NOV-19:10 10113.80 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 14185.34 01-DEC-20:10 10113.80 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   14185.34   10113.80   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   14185.34   10113.80   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 704.41 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 323.33 15-JAN-08:00
February 1169.53 01-FEB-00:10 704.41 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 339.03 19-FEB-06:00
March 1169.53 01-MAR-00:10 704.41 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 275.51 01-MAR-07:00
April 1169.53 01-APR-00:10 704.41 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 46.77 01-APR-17:00 243.94 19-APR-05:00
May 1169.53 01-MAY-00:10 704.41 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 30.35 05-MAY-16:00 206.21 11-MAY-03:30
June 1169.53 01-JUN-00:10 704.41 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 48.70 28-JUN-17:00 159.09 15-JUN-03:43
July 1169.53 01-JUL-00:10 704.41 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 74.55 24-JUL-15:00 120.51 07-JUL-05:00
August 1169.53 01-AUG-00:10 704.41 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 94.50 10-AUG-17:00 123.62 01-AUG-05:20
September 1169.53 01-SEP-00:10 704.41 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 18.71 14-SEP-17:00 176.59 27-SEP-04:43
October 1169.53 01-OCT-23:10 704.41 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 190.35 13-OCT-07:00
November 1169.53 01-NOV-00:10 704.41 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 264.95 11-NOV-08:00
December 1169.53 01-DEC-00:10 704.41 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 291.33 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   704.41   685.60   0.00 0.00 0.00 0.00 0.00   120.51  
Maximum of Months 1169.53   704.41   685.60   0.00 0.00 0.00 0.00 94.50   339.03  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 815.72 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 127.49 15-JAN-08:00
February 1354.32 01-FEB-00:10 815.72 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 131.39 19-FEB-05:00
March 1354.32 01-MAR-00:10 815.72 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 113.56 01-MAR-07:00
April 1354.32 01-APR-00:10 815.72 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 21.08 01-APR-16:00 100.39 19-APR-05:00
May 1354.32 01-MAY-00:10 815.72 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 8.75 05-MAY-16:00 88.02 11-MAY-03:00
June 1354.32 01-JUN-00:10 815.72 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 15.79 28-JUN-17:00 69.42 15-JUN-03:43
July 1354.32 01-JUL-00:10 815.72 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 31.21 24-JUL-15:00 57.91 07-JUL-05:00
August 1354.32 01-AUG-00:10 815.72 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 35.49 29-AUG-16:00 58.65 01-AUG-05:25
September 1354.32 01-SEP-00:10 815.72 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 7.97 22-SEP-16:00 75.46 27-SEP-04:43
October 1354.32 01-OCT-23:10 815.72 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 82.87 13-OCT-05:00
November 1354.32 01-NOV-00:10 815.72 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 107.80 11-NOV-08:00
December 1354.32 01-DEC-00:10 815.72 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 114.52 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   815.72   793.93   0.00 0.00 0.00 0.00 0.00   57.91  
Maximum of Months 1354.32   815.72   793.93   0.00 0.00 0.00 0.00 35.49   131.39  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 1360.40 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 294.95 15-JAN-08:00
February 286.42 01-FEB-00:10 1360.40 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 309.29 19-FEB-06:00
March 286.42 01-MAR-00:10 1360.40 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 259.23 01-MAR-07:00
April 286.42 01-APR-00:10 1360.40 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 58.86 01-APR-16:00 225.72 19-APR-05:00
May 286.42 01-MAY-00:10 1360.40 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 24.64 05-MAY-16:00 200.86 11-MAY-03:00
June 286.42 01-JUN-00:10 1360.40 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 40.03 28-JUN-17:00 155.62 15-JUN-03:47
July 286.42 01-JUL-00:10 1360.40 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 75.21 24-JUL-15:00 130.03 19-JUL-05:00
August 286.42 01-AUG-00:10 1360.40 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 85.72 10-AUG-17:00 134.21 01-AUG-06:10
September 286.42 01-SEP-00:10 1360.40 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 25.57 22-SEP-16:00 168.41 27-SEP-04:43
October 286.42 01-OCT-23:10 1360.40 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 185.58 12-OCT-06:57
November 286.42 01-NOV-00:10 1360.40 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 244.35 11-NOV-08:00
December 286.42 01-DEC-00:10 1360.40 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 265.74 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   1360.40   839.45   0.00 0.00 0.00 0.00 0.00   130.03  
Maximum of Months 286.42   1360.40   839.45   0.00 0.00 0.00 0.00 85.72   309.29  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 227.72 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 170.17 15-JAN-08:00
February 220.32 01-FEB-00:10 227.72 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 178.45 19-FEB-06:00
March 220.32 01-MAR-00:10 227.72 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 147.13 01-MAR-07:00
April 220.32 01-APR-00:10 227.72 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 33.94 01-APR-16:00 128.80 19-APR-05:00
May 220.32 01-MAY-00:10 227.72 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 14.53 05-MAY-16:00 114.68 11-MAY-03:00
June 220.32 01-JUN-00:10 227.72 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 23.32 28-JUN-17:00 88.64 15-JUN-03:47
July 220.32 01-JUL-00:10 227.72 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 43.50 24-JUL-15:00 74.25 19-JUL-05:00
August 220.32 01-AUG-00:10 227.72 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 49.45 10-AUG-17:00 75.76 01-AUG-05:40
September 220.32 01-SEP-00:10 227.72 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 14.96 22-SEP-16:00 95.68 27-SEP-04:43
October 220.32 01-OCT-23:10 227.72 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 105.78 13-OCT-05:00
November 220.32 01-NOV-00:10 227.72 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 139.44 11-NOV-07:50
December 220.32 01-DEC-00:10 227.72 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 153.31 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   227.72   242.16   0.00 0.00 0.00 0.00 0.00   74.25  
Maximum of Months 220.32   227.72   242.16   0.00 0.00 0.00 0.00 49.45   178.45  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 357.21 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 0.00 01-JAN-00:05 451.17 15-JAN-08:00
February 907.20 01-FEB-00:10 357.21 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 0.00 01-FEB-00:03 459.77 19-FEB-08:00
March 907.20 01-MAR-00:10 357.21 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 0.00 01-MAR-00:03 390.68 01-MAR-07:00
April 907.20 01-APR-00:10 357.21 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 69.90 01-APR-16:00 347.81 19-APR-05:10
May 907.20 01-MAY-00:10 357.21 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 37.46 05-MAY-16:00 323.61 18-MAY-06:10
June 907.20 01-JUN-00:10 357.21 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 65.81 28-JUN-17:00 258.30 15-JUN-05:07
July 907.20 01-JUL-00:10 357.21 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 108.60 24-JUL-15:00 186.57 04-JUL-05:55
August 907.20 01-AUG-00:10 357.21 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 135.38 10-AUG-17:00 191.91 01-AUG-06:00
September 907.20 01-SEP-00:10 357.21 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 40.24 14-SEP-17:00 279.45 28-SEP-06:55
October 907.20 01-OCT-23:10 357.21 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 0.00 01-OCT-00:10 321.14 16-OCT-06:45
November 907.20 01-NOV-00:10 357.21 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 0.00 01-NOV-00:03 377.34 13-NOV-20:43
December 907.20 01-DEC-00:10 357.21 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 0.00 01-DEC-00:03 410.42 26-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   357.21   4572.80   39726.58   0.00 0.00 0.00 0.00   186.57  
Maximum of Months 907.20   357.21   4572.80   39726.58   0.00 0.00 0.00 135.38   459.77  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 1761.91 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 714.87 15-JAN-08:00
February 15368.40 01-FEB-00:10 1761.91 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 749.52 19-FEB-06:00
March 15368.40 01-MAR-00:10 1761.91 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 620.61 01-MAR-07:00
April 15368.40 01-APR-00:10 1761.91 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 91.95 01-APR-16:00 566.83 19-APR-05:00
May 15368.40 01-MAY-00:10 1761.91 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 53.05 05-MAY-16:00 493.13 11-MAY-03:00
June 15368.40 01-JUN-00:10 1761.91 01-JUN-19:40 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 95.03 28-JUN-17:00 405.34 15-JUN-03:43
July 15368.40 01-JUL-00:10 1761.91 03-JUL-19:00 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 164.81 24-JUL-15:00 322.07 07-JUL-05:00
August 15368.40 01-AUG-00:10 1761.91 01-AUG-19:19 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 203.81 10-AUG-17:00 321.06 01-AUG-05:20
September 15368.40 01-SEP-00:10 1761.91 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 33.82 14-SEP-17:00 442.49 27-SEP-04:43
October 15368.40 01-OCT-23:10 1761.91 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 480.83 13-OCT-01:55
November 15368.40 01-NOV-00:10 1761.91 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 595.82 11-NOV-08:00
December 15368.40 01-DEC-00:10 1761.91 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 644.03 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   1761.91   965.27   0.00 0.00 0.00 0.00 0.00   321.06  
Maximum of Months 15368.40   1761.91   965.27   0.00 0.00 0.00 0.00 203.81   749.52  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 10265.18 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2134.97 15-JAN-08:00
February 45622.98 01-FEB-00:10 10265.18 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 2199.86 19-FEB-05:00
March 45622.98 01-MAR-00:10 10265.18 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 1898.21 01-MAR-07:00
April 45622.98 01-APR-00:10 10265.18 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 314.27 01-APR-16:00 1707.75 19-APR-05:00
May 45622.98 01-MAY-00:10 10265.18 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 129.66 05-MAY-16:00 1494.07 11-MAY-03:00
June 45622.98 01-JUN-00:10 10265.18 01-JUN-19:30 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 252.09 28-JUN-17:00 1201.02 15-JUN-03:47
July 45622.98 01-JUL-00:10 10265.18 03-JUL-19:49 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 501.20 24-JUL-15:00 990.68 07-JUL-05:00
August 45622.98 01-AUG-00:10 10265.18 01-AUG-19:19 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 577.31 10-AUG-17:00 970.22 01-AUG-05:20
September 45622.98 01-SEP-00:10 10265.18 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 96.46 14-SEP-17:00 1302.85 27-SEP-04:43
October 45622.98 01-OCT-23:10 10265.18 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1410.54 13-OCT-05:00
November 45622.98 01-NOV-00:10 10265.18 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 1810.49 11-NOV-08:00
December 45622.98 01-DEC-00:10 10265.18 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 1925.85 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   10265.18   10029.21   0.00 0.00 0.00 0.00 0.00   970.22  
Maximum of Months 45622.98   10265.18   10029.21   0.00 0.00 0.00 0.00 577.31   2199.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 188.81 15-JAN-08:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 197.91 19-FEB-06:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 161.03 01-MAR-07:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 40.05 27-APR-15:40 142.70 19-APR-05:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 25.73 05-MAY-16:00 120.77 11-MAY-03:10
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 36.97 28-JUN-17:00 91.04 15-JUN-03:58
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 60.13 24-JUL-15:10 71.02 07-JUL-05:00
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 69.17 10-AUG-17:00 77.11 01-AUG-08:00
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 25.78 14-SEP-17:00 99.71 27-SEP-04:53
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 2.98 04-OCT-15:10 111.52 13-OCT-05:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 154.89 11-NOV-07:10
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 170.21 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 0.00   71.02  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 69.17   197.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 188.80 15-JAN-08:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 197.90 19-FEB-06:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 161.01 01-MAR-07:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 40.04 27-APR-15:10 142.69 19-APR-05:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 25.73 05-MAY-16:00 120.76 11-MAY-03:10
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 36.97 28-JUN-17:00 91.04 15-JUN-03:58
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 60.13 24-JUL-15:10 71.01 07-JUL-05:00
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 69.17 10-AUG-17:00 76.28 01-AUG-08:00
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 25.78 14-SEP-17:00 99.70 27-SEP-04:53
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 2.98 04-OCT-15:10 111.51 13-OCT-05:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 154.87 11-NOV-07:10
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 170.20 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 0.00   71.01  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 69.17   197.90  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 76.99 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 48.01 15-JAN-08:00
February 0.00 01-FEB-00:10 76.99 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 50.64 19-FEB-06:00
March 0.00 01-MAR-00:10 76.99 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 44.87 01-MAR-07:00
April 0.00 01-APR-00:10 76.99 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 7.06 27-APR-15:13 38.87 19-APR-05:10
May 0.00 01-MAY-00:10 76.99 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 3.03 05-MAY-16:00 35.22 11-MAY-03:00
June 0.00 01-JUN-00:10 76.99 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 6.18 28-JUN-17:00 27.21 01-JUN-03:53
July 0.00 01-JUL-00:10 76.99 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 13.21 24-JUL-15:00 23.12 19-JUL-05:00
August 0.00 01-AUG-00:10 76.99 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 15.27 10-AUG-17:00 23.67 01-AUG-05:55
September 0.00 01-SEP-00:10 76.99 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 3.03 14-SEP-17:00 28.23 27-SEP-03:53
October 0.00 01-OCT-00:10 76.99 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 33.93 13-OCT-07:00
November 0.00 01-NOV-00:10 76.99 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 42.79 11-NOV-23:00
December 0.00 01-DEC-00:10 76.99 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 45.43 06-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   76.99   232.19   0.00 0.00 0.00 0.00 0.00   23.12  
Maximum of Months 0.00   76.99   232.19   0.00 0.00 0.00 0.00 15.27   50.64  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 77.01 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 52.69 15-JAN-08:00
February 180.00 01-FEB-00:10 77.01 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 55.24 19-FEB-06:00
March 180.00 01-MAR-00:10 77.01 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 44.94 01-MAR-07:00
April 180.00 01-APR-00:10 77.01 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 11.17 27-APR-15:10 39.83 19-APR-05:00
May 180.00 01-MAY-00:10 77.01 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 7.18 05-MAY-16:00 33.70 11-MAY-03:10
June 180.00 01-JUN-00:10 77.01 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 10.32 28-JUN-17:00 25.41 15-JUN-03:55
July 180.00 01-JUL-00:10 77.01 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 16.78 24-JUL-15:10 19.82 07-JUL-05:00
August 180.00 01-AUG-00:10 77.01 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 19.31 10-AUG-17:00 20.51 01-AUG-07:30
September 180.00 01-SEP-00:10 77.01 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 7.20 14-SEP-17:00 27.83 27-SEP-05:00
October 180.00 01-OCT-00:10 77.01 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 0.83 04-OCT-15:05 31.12 13-OCT-05:00
November 180.00 01-NOV-00:10 77.01 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 43.23 11-NOV-07:10
December 180.00 01-DEC-00:10 77.01 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 47.50 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 0.00   19.82  
Maximum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 19.31   55.24  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 188.81 15-JAN-08:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 197.91 19-FEB-06:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 161.03 01-MAR-07:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 40.04 27-APR-15:10 142.70 19-APR-05:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 25.73 05-MAY-16:00 120.76 11-MAY-03:10
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 36.97 28-JUN-17:00 91.04 15-JUN-03:58
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 60.14 24-JUL-15:10 71.02 07-JUL-05:00
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 69.17 10-AUG-17:00 81.63 01-AUG-07:50
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 25.78 14-SEP-17:00 99.71 27-SEP-04:53
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 2.98 04-OCT-15:10 111.52 13-OCT-05:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 154.89 11-NOV-07:20
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 170.21 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 0.00   71.02  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 69.17   197.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 188.80 15-JAN-08:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 197.90 19-FEB-06:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 161.01 01-MAR-07:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 40.04 27-APR-15:10 142.69 19-APR-05:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 25.73 05-MAY-16:00 120.76 11-MAY-03:10
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 36.97 28-JUN-17:00 91.04 15-JUN-03:58
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 60.13 24-JUL-15:10 71.01 07-JUL-05:00
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 69.16 10-AUG-17:00 81.21 01-AUG-07:50
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 25.78 14-SEP-17:00 99.70 27-SEP-04:53
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 2.98 04-OCT-15:08 111.51 13-OCT-05:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 154.88 11-NOV-07:10
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 170.20 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 0.00   71.01  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 69.16   197.90  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 2240.78 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 227.31 15-JAN-08:00
February 2263.36 01-FEB-00:10 2240.78 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 238.34 19-FEB-06:00
March 2263.36 01-MAR-00:10 2240.78 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 195.32 01-MAR-07:00
April 2263.36 01-APR-00:10 2240.78 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 43.27 01-APR-16:00 173.36 19-APR-05:00
May 2263.36 01-MAY-00:10 2240.78 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 17.42 05-MAY-16:00 155.45 11-MAY-03:00
June 2263.36 01-JUN-00:10 2240.78 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 28.86 28-JUN-17:00 120.13 15-JUN-03:43
July 2263.36 01-JUL-00:10 2240.78 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 55.35 24-JUL-15:00 99.95 07-JUL-05:00
August 2263.36 01-AUG-00:10 2240.78 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 64.22 29-AUG-16:00 102.39 01-AUG-05:25
September 2263.36 01-SEP-00:10 2240.78 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 17.51 22-SEP-16:00 128.32 27-SEP-04:43
October 2263.36 01-OCT-23:10 2240.78 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 142.66 13-OCT-05:00
November 2263.36 01-NOV-00:10 2240.78 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 186.32 11-NOV-07:50
December 2263.36 01-DEC-00:10 2240.78 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 204.84 26-DEC-07:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   2240.78   0.00 0.00 0.00 0.00 0.00 0.00   99.95  
Maximum of Months 2263.36   2240.78   0.00 0.00 0.00 0.00 0.00 64.22   238.34  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 189.30 15-JAN-08:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 198.40 19-FEB-06:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 161.50 01-MAR-07:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 39.65 27-APR-16:00 143.17 19-APR-05:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 25.34 05-MAY-16:00 121.22 11-MAY-03:10
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 36.58 28-JUN-17:00 91.48 15-JUN-04:00
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 59.74 24-JUL-15:10 71.45 07-JUL-05:00
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 68.80 10-AUG-17:00 75.10 01-AUG-08:00
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 25.39 14-SEP-17:00 100.15 27-SEP-04:53
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 2.58 04-OCT-15:10 111.97 13-OCT-05:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 155.36 11-NOV-07:10
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 170.69 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 0.00   71.45  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 68.80   198.40  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 189.28 15-JAN-08:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 198.38 19-FEB-06:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 161.49 01-MAR-07:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 39.65 27-APR-15:50 143.15 19-APR-05:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 25.34 05-MAY-16:00 121.21 11-MAY-03:10
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 36.57 28-JUN-17:00 91.48 15-JUN-04:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 59.75 24-JUL-15:10 71.45 07-JUL-05:00
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 68.80 10-AUG-17:00 74.25 01-AUG-08:00
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 25.38 14-SEP-17:00 100.14 27-SEP-04:53
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 2.58 04-OCT-15:10 111.96 13-OCT-05:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 155.34 11-NOV-07:10
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 170.67 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 0.00   71.45  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 68.80   198.38  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 77.01 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 96.85 15-JAN-08:00
February 180.00 01-FEB-00:10 77.01 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 101.51 19-FEB-06:00
March 180.00 01-MAR-00:10 77.01 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 82.63 01-MAR-07:00
April 180.00 01-APR-00:10 77.01 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 20.29 27-APR-15:50 73.25 19-APR-05:00
May 180.00 01-MAY-00:10 77.01 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 12.97 05-MAY-16:00 62.02 11-MAY-03:10
June 180.00 01-JUN-00:10 77.01 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 18.72 28-JUN-17:00 46.81 15-JUN-03:55
July 180.00 01-JUL-00:10 77.01 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 30.57 24-JUL-15:10 36.56 07-JUL-05:00
August 180.00 01-AUG-00:10 77.01 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 35.20 10-AUG-17:00 38.40 01-AUG-08:00
September 180.00 01-SEP-00:10 77.01 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 12.99 14-SEP-17:00 51.24 27-SEP-04:53
October 180.00 01-OCT-00:10 77.01 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 1.32 04-OCT-15:10 57.29 13-OCT-05:00
November 180.00 01-NOV-00:10 77.01 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 79.49 11-NOV-07:10
December 180.00 01-DEC-00:10 77.01 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 87.33 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 0.00   36.56  
Maximum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 35.20   101.51  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3094.06 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 515.30 15-JAN-08:00
February 26988.77 01-FEB-00:10 3094.06 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 528.95 19-FEB-06:10
March 26988.77 01-MAR-00:10 3094.06 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 446.49 01-MAR-07:00
April 26988.77 01-APR-00:10 3094.06 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 52.59 01-APR-16:00 401.22 19-APR-05:00
May 26988.77 01-MAY-00:10 3094.06 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 14.69 05-MAY-16:00 346.78 11-MAY-03:10
June 26988.77 01-JUN-00:10 3094.06 01-JUN-19:40 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 42.32 28-JUN-17:00 286.83 15-JUN-03:43
July 26988.77 01-JUL-00:10 3094.06 10-JUL-19:30 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 104.06 24-JUL-15:00 227.85 05-JUL-02:50
August 26988.77 01-AUG-00:10 3094.06 01-AUG-19:19 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 122.20 10-AUG-17:00 228.96 06-AUG-05:00
September 26988.77 01-SEP-00:10 3094.06 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 14.72 14-SEP-17:00 314.93 27-SEP-04:43
October 26988.77 01-OCT-23:10 3094.06 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 327.59 13-OCT-01:55
November 26988.77 01-NOV-00:10 3094.06 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 430.94 11-NOV-07:10
December 26988.77 01-DEC-00:10 3094.06 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 469.25 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 0.00   227.85  
Maximum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 122.20   528.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3094.06 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 515.31 15-JAN-08:00
February 26988.77 01-FEB-00:10 3094.06 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 533.04 19-FEB-06:10
March 26988.77 01-MAR-00:10 3094.06 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 446.49 01-MAR-07:00
April 26988.77 01-APR-00:10 3094.06 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 50.13 27-APR-16:00 401.23 19-APR-05:00
May 26988.77 01-MAY-00:10 3094.06 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 14.69 05-MAY-16:00 346.78 11-MAY-03:10
June 26988.77 01-JUN-00:10 3094.06 01-JUN-19:40 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 42.32 28-JUN-17:00 287.82 15-JUN-03:43
July 26988.77 01-JUL-00:10 3094.06 10-JUL-19:30 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 104.06 24-JUL-15:00 228.02 05-JUL-02:50
August 26988.77 01-AUG-00:10 3094.06 01-AUG-19:19 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 122.20 10-AUG-17:00 229.09 06-AUG-05:00
September 26988.77 01-SEP-00:10 3094.06 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 14.72 14-SEP-17:00 316.16 27-SEP-04:43
October 26988.77 01-OCT-23:10 3094.06 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 329.95 16-OCT-06:45
November 26988.77 01-NOV-00:10 3094.06 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 430.95 11-NOV-07:10
December 26988.77 01-DEC-00:10 3094.06 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 469.25 26-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 0.00   228.02  
Maximum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 122.20   533.04  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1089.83 02-JAN-20:10 14912.86 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 0.00 01-JAN-00:05 461.22 15-JAN-08:00
February 2401.70 01-FEB-00:10 1089.83 01-FEB-20:10 14912.86 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 0.00 01-FEB-00:03 476.25 19-FEB-06:10
March 2401.70 01-MAR-00:10 1089.83 01-MAR-20:10 14912.86 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 0.00 01-MAR-00:03 399.63 01-MAR-07:00
April 2401.70 01-APR-00:10 1089.83 03-APR-19:10 14912.86 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 45.06 27-APR-15:40 357.80 19-APR-05:10
May 2401.70 01-MAY-00:10 1089.83 01-MAY-19:10 14912.86 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 13.32 05-MAY-16:00 327.26 18-MAY-06:15
June 2401.70 01-JUN-00:10 1089.83 01-JUN-19:10 14912.86 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 38.05 28-JUN-17:00 267.27 15-JUN-05:07
July 2401.70 01-JUL-00:10 1089.83 03-JUL-19:10 14912.86 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 93.28 24-JUL-15:00 201.76 19-JUL-05:00
August 2401.70 01-AUG-00:10 1089.83 01-AUG-19:10 14912.86 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 109.57 10-AUG-17:00 207.96 01-AUG-06:15
September 2401.70 01-SEP-00:10 1089.83 01-SEP-19:10 14912.86 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 13.35 14-SEP-17:00 290.52 27-SEP-04:43
October 2401.70 01-OCT-23:10 1089.83 02-OCT-19:10 14912.86 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 0.00 01-OCT-00:10 332.00 13-OCT-07:00
November 2401.70 01-NOV-00:10 1089.83 01-NOV-19:10 14912.86 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 0.00 01-NOV-00:03 385.73 11-NOV-07:10
December 2401.70 01-DEC-00:10 1089.83 01-DEC-20:10 14912.86 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 0.00 01-DEC-00:03 420.01 26-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1089.83   14912.86   22492.83   0.00 0.00 0.00 0.00   201.76  
Maximum of Months 2401.70   1089.83   14912.86   22492.83   0.00 0.00 0.00 109.57   476.25  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 2371.52 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 403.24 15-JAN-08:00
February 2395.44 01-FEB-00:10 2371.52 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 422.74 19-FEB-06:00
March 2395.44 01-MAR-00:10 2371.52 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 343.79 01-MAR-07:00
April 2395.44 01-APR-00:10 2371.52 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 64.51 01-APR-16:00 304.59 19-APR-05:00
May 2395.44 01-MAY-00:10 2371.52 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 23.10 05-MAY-16:00 265.58 11-MAY-03:00
June 2395.44 01-JUN-00:10 2371.52 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 40.74 28-JUN-17:00 206.40 15-JUN-03:43
July 2395.44 01-JUL-00:10 2371.52 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 91.16 24-JUL-15:00 173.30 19-JUL-05:00
August 2395.44 01-AUG-00:10 2371.52 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 107.02 10-AUG-17:00 177.21 01-AUG-05:25
September 2395.44 01-SEP-00:10 2371.52 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 21.35 22-SEP-16:00 220.59 27-SEP-04:43
October 2395.44 01-OCT-23:10 2371.52 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 243.66 13-OCT-05:00
November 2395.44 01-NOV-00:10 2371.52 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:03 330.68 11-NOV-07:50
December 2395.44 01-DEC-00:10 2371.52 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 363.43 26-DEC-07:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   2371.52   0.00 0.00 0.00 0.00 0.00 0.00   173.30  
Maximum of Months 2395.44   2371.52   0.00 0.00 0.00 0.00 0.00 107.02   422.74  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 34483.24 09-JAN-22:01 92015.14 75656.14 59618.20 0.00 0.00 0.00 0.00 0.00 0.00
February 32768.76 08-FEB-20:21 71567.33 113482.76 80910.41 0.00 0.00 0.00 0.00 0.00 0.00
March 26821.85 24-MAR-20:45 40895.62 50437.18 38325.98 0.00 0.00 0.00 0.00 0.00 0.00
April 23289.15 24-APR-23:34 92015.14 25218.23 25550.66 0.00 0.00 0.00 0.00 0.00 0.00
May 24364.77 18-MAY-06:25 40895.62 63046.30 51101.31 0.00 0.00 0.00 0.00 0.00 0.00
June 20551.20 15-JUN-05:27 26837.75 18913.67 15969.16 0.00 0.00 0.00 0.00 0.00 0.00
July 17230.41 04-JUL-05:27 26837.75 14185.53 12775.33 0.00 0.00 0.00 0.00 0.00 0.00
August 18109.33 18-AUG-21:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
September 26862.61 28-SEP-05:50 89459.16 63045.57 53230.53 0.00 0.00 0.00 0.00 0.00 0.00
October 35593.24 16-OCT-06:23 30671.71 47284.72 38325.98 0.00 0.00 0.00 0.00 0.00 0.00
November 37074.87 29-NOV-21:48 102239.04 126092.96 95814.96 0.00 0.00 0.00 0.00 0.00 0.00
December 36814.45 01-DEC-20:45 89459.16 141853.45 101138.01 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17230.41   10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 37074.87   102239.04 141853.45 101138.01 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4050.99 20-JAN-12:48 2598.96 1956.71 2525.91 0.00 0.00 0.00 0.00 0.00 217.42
February 6214.52 12-FEB-12:55 1559.38 939.22 1154.70 0.00 0.00 0.00 0.00 0.00 219.13
March 3975.74 02-MAR-13:20 259.90 195.67 252.59 0.00 0.00 0.00 0.00 0.00 137.29
April 3609.41 27-APR-13:10 259.90 195.67 252.59 0.00 0.00 0.00 0.00 24.04 0.00
May 3475.43 04-MAY-13:20 259.90 195.67 252.59 0.00 0.00 0.00 0.00 0.00 14.41
June 2759.95 28-JUN-10:33 779.69 587.01 757.77 0.00 0.00 0.00 0.00 0.00 9.27
July 3354.37 31-JUL-13:20 259.90 195.67 252.59 0.00 0.00 0.00 0.00 40.93 0.00
August 4256.89 24-AUG-13:10 259.90 195.67 252.59 0.00 0.00 0.00 0.00 56.08 0.00
September 4397.98 14-SEP-13:20 259.90 195.67 252.59 0.00 0.00 0.00 0.00 0.00 9.74
October 4487.61 04-OCT-12:50 259.90 195.67 252.59 0.00 0.00 0.00 0.00 0.00 39.65
November 5509.88 11-NOV-12:35 779.69 469.61 577.35 0.00 0.00 0.00 0.00 0.00 206.86
December 3568.21 05-DEC-11:20 779.69 587.01 757.77 0.00 0.00 0.00 0.00 0.00 173.15
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2759.95   259.90 195.67 252.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6214.52   2598.96 1956.71 2525.91 0.00 0.00 0.00 0.00 56.08 219.13



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1750.60 03-JAN-06:34 10533.60 3625.40 4178.59 0.00 0.00 0.00 0.00 0.00 65.47
February 1929.01 08-FEB-20:27 8426.88 6525.72 6351.45 0.00 0.00 0.00 0.00 0.00 94.01
March 2153.07 15-MAR-06:07 4213.44 3172.23 3510.01 0.00 0.00 0.00 0.00 0.00 77.23
April 2175.35 24-APR-23:34 10834.56 1450.16 2005.72 0.00 0.00 0.00 0.00 0.00 75.82
May 2154.21 18-MAY-06:25 4815.36 3625.40 4011.44 0.00 0.00 0.00 0.00 0.00 79.71
June 1812.69 15-JUN-05:27 3160.08 1087.62 1253.58 0.00 0.00 0.00 0.00 0.00 63.82
July 1972.80 24-JUL-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 0.00 5.39
August 2121.77 10-AUG-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 0.00 4.46
September 1909.36 14-SEP-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 0.00 26.00
October 2025.00 12-OCT-23:32 12188.88 1631.43 2256.44 0.00 0.00 0.00 0.00 0.00 75.51
November 1869.58 28-NOV-23:25 2708.64 543.81 668.57 0.00 0.00 0.00 0.00 0.00 71.95
December 1854.28 01-DEC-18:17 2257.20 1631.43 1755.01 0.00 0.00 0.00 0.00 0.00 72.79
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1750.60   1203.84 543.81 668.57 0.00 0.00 0.00 0.00 0.00 4.46
Maximum of Months 2175.35   12188.88 6525.72 6351.45 0.00 0.00 0.00 0.00 0.00 94.01



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1494.15 01-JAN-20:15 1145.66 7255.45 4771.59 0.00 0.00 0.00 0.00 0.00 172.23
February 1610.48 26-FEB-01:32 2004.91 4081.19 3181.06 0.00 0.00 0.00 0.00 0.00 143.30
March 1813.17 15-MAR-06:07 891.07 5290.43 3711.24 0.00 0.00 0.00 0.00 0.00 170.49
April 1829.91 24-APR-23:34 2291.33 2418.48 2120.71 0.00 0.00 0.00 0.00 0.00 167.04
May 1910.42 18-MAY-06:25 1018.37 6046.21 4241.42 0.00 0.00 0.00 0.00 0.00 184.38
June 1591.73 13-JUN-23:40 572.83 604.62 530.18 0.00 0.00 0.00 0.00 0.00 138.00
July 1598.25 24-JUL-21:00 254.59 1209.24 795.27 0.00 0.00 0.00 0.00 0.00 12.74
August 1738.30 10-AUG-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 16.66 0.00
September 1656.42 27-SEP-06:30 1145.66 6801.98 4771.59 0.00 0.00 0.00 0.00 0.00 152.52
October 1712.76 12-OCT-23:32 2577.74 2720.79 2385.80 0.00 0.00 0.00 0.00 0.00 167.98
November 1569.10 17-NOV-08:35 254.59 1209.24 883.63 0.00 0.00 0.00 0.00 0.00 158.26
December 1550.11 04-DEC-16:10 1591.20 3778.88 3092.70 0.00 0.00 0.00 0.00 0.00 145.65
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1494.15   222.77 604.62 530.18 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1910.42   2577.74 7255.45 4771.59 0.00 0.00 0.00 0.00 16.66 184.38



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 643.73 12-JAN-07:10 195.84 253.02 305.88 0.00 0.00 0.00 0.00 0.00 93.31
February 755.64 26-FEB-01:32 1542.24 683.15 917.65 0.00 0.00 0.00 0.00 0.00 80.64
March 853.54 15-MAR-06:07 685.44 885.57 1070.59 0.00 0.00 0.00 0.00 0.00 96.34
April 862.16 24-APR-23:34 1762.56 404.83 611.77 0.00 0.00 0.00 0.00 0.00 94.40
May 894.07 18-MAY-06:25 783.36 1012.07 1223.53 0.00 0.00 0.00 0.00 0.00 103.73
June 750.34 13-JUN-23:40 440.64 101.21 152.94 0.00 0.00 0.00 0.00 0.00 77.99
July 669.20 24-JUL-18:10 1028.16 1214.49 1376.47 0.00 0.00 0.00 0.00 31.75 0.00
August 681.60 10-AUG-18:08 1028.16 1214.49 1376.47 0.00 0.00 0.00 0.00 41.32 0.00
September 778.12 27-SEP-05:14 1713.60 1012.07 1274.51 0.00 0.00 0.00 0.00 0.00 92.49
October 807.70 12-OCT-23:32 1982.88 455.43 688.24 0.00 0.00 0.00 0.00 0.00 95.16
November 724.33 20-NOV-06:13 514.08 303.62 382.35 0.00 0.00 0.00 0.00 0.00 85.72
December 718.19 03-DEC-09:07 734.40 455.43 611.77 0.00 0.00 0.00 0.00 0.00 84.35
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 643.73   195.84 101.21 152.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 894.07   1982.88 1214.49 1376.47 0.00 0.00 0.00 0.00 41.32 103.73



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 50428.00 23-JAN-21:40 8064.00 3175.23 43321.27 376357.04 0.00 0.00 0.00 0.00 310.97
February 52379.02 07-FEB-20:01 5644.80 2857.71 36582.41 317812.61 0.00 0.00 0.00 0.00 321.50
March 51226.88 24-MAR-20:45 3225.60 1270.09 17328.51 150542.82 0.00 0.00 0.00 0.00 320.78
April 49727.30 17-APR-19:00 7056.00 3175.23 43321.27 376357.04 0.00 0.00 0.00 0.00 295.60
May 49684.70 10-MAY-22:00 9072.00 2381.43 33694.32 292722.14 0.00 0.00 0.00 0.00 286.25
June 38426.82 28-JUN-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 33.52
July 38712.28 24-JUL-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 1.46
August 38783.54 10-AUG-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 22.74 0.00
September 43398.20 27-SEP-06:59 4032.00 1984.52 28880.85 250904.69 0.00 0.00 0.00 0.00 234.65
October 49333.63 31-OCT-20:29 7257.60 2857.71 38989.14 338721.34 0.00 0.00 0.00 0.00 271.77
November 50329.27 29-NOV-21:48 8064.00 3175.23 43321.27 376357.04 0.00 0.00 0.00 0.00 301.34
December 52305.45 04-DEC-21:40 8064.00 3175.23 43321.27 376357.04 0.00 0.00 0.00 0.00 322.17
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 38426.82   705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 52379.02   9072.00 3175.23 43321.27 376357.04 0.00 0.00 0.00 22.74 322.17



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19794.98 20-JAN-12:48 34152.00 2985.45 3556.27 0.00 0.00 0.00 0.00 0.00 480.91
February 25066.42 12-FEB-12:39 51228.00 3582.54 4064.31 0.00 0.00 0.00 0.00 0.00 488.13
March 15356.16 01-MAR-13:17 10245.60 895.64 1066.88 0.00 0.00 0.00 0.00 0.00 344.27
April 15994.73 24-APR-23:34 122947.20 3132.28 2438.58 0.00 0.00 0.00 0.00 0.00 418.55
May 14531.93 27-MAY-04:27 122947.20 1566.14 1625.72 0.00 0.00 0.00 0.00 0.00 390.56
June 12889.20 15-JUN-02:29 153684.00 1957.67 2032.15 0.00 0.00 0.00 0.00 0.00 359.83
July 12204.95 31-JUL-15:03 51228.00 1791.27 2133.76 0.00 0.00 0.00 0.00 111.23 0.00
August 14417.16 24-AUG-14:10 5122.80 298.55 355.63 0.00 0.00 0.00 0.00 130.05 0.00
September 15450.25 23-SEP-13:20 5122.80 298.55 355.63 0.00 0.00 0.00 0.00 0.00 36.80
October 15597.68 04-OCT-12:50 3415.20 298.55 355.63 0.00 0.00 0.00 0.00 0.00 87.64
November 24423.79 11-NOV-12:03 51228.00 3582.54 4064.31 0.00 0.00 0.00 0.00 0.00 513.29
December 13989.18 05-DEC-11:20 10245.60 895.64 1066.88 0.00 0.00 0.00 0.00 0.00 388.04
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 12204.95   3415.20 298.55 355.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25066.42   153684.00 3582.54 4064.31 0.00 0.00 0.00 0.00 130.05 513.29



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 39305.93 09-JAN-22:20 91245.96 13686.91 14779.89 0.00 0.00 0.00 0.00 0.00 1448.58
February 46873.94 28-FEB-23:30 91245.96 6843.46 8445.65 0.00 0.00 0.00 0.00 0.00 1347.13
March 58831.08 21-MAR-21:18 228114.90 34217.28 36949.72 0.00 0.00 0.00 0.00 0.00 1307.50
April 52477.42 11-APR-22:00 456229.80 68434.56 73899.43 0.00 0.00 0.00 0.00 0.00 1347.35
May 60204.86 10-MAY-21:54 456229.80 68434.56 73899.43 0.00 0.00 0.00 0.00 0.00 1343.46
June 39862.88 15-JUN-05:27 106453.62 13048.19 15835.59 0.00 0.00 0.00 0.00 0.00 1084.62
July 39587.72 24-JUL-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 115.12
August 40992.29 10-AUG-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 79.01
September 41913.69 27-SEP-05:14 354845.40 45623.04 52785.31 0.00 0.00 0.00 0.00 0.00 1220.38
October 59903.72 13-OCT-00:55 182491.92 6843.46 10557.06 0.00 0.00 0.00 0.00 0.00 1306.15
November 46414.07 28-NOV-23:05 91245.96 6843.46 8445.65 0.00 0.00 0.00 0.00 0.00 1189.74
December 40018.21 03-DEC-09:07 152076.60 19093.24 25336.95 0.00 0.00 0.00 0.00 0.00 1147.77
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 39305.93   45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 79.01
Maximum of Months 60204.86   456229.80 68434.56 73899.43 0.00 0.00 0.00 0.00 0.00 1448.58



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2107.97 20-JAN-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 114.46
February 3124.92 08-FEB-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 109.43
March 3350.19 18-MAR-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 0.00 16.37
April 3483.65 01-APR-18:02 702.00 735.03 774.39 0.00 0.00 0.00 0.00 18.51 0.00
May 3554.62 14-MAY-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 3.86 0.00
June 3300.56 02-JUN-18:01 970.20 763.21 903.46 0.00 0.00 0.00 0.00 0.00 20.09
July 3310.12 25-JUL-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 0.00 3.17
August 3543.45 10-AUG-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 50.47 0.00
September 3267.73 13-SEP-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 0.00 0.61
October 3497.16 04-OCT-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 7.56
November 3181.66 04-NOV-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 0.00 11.48
December 2918.11 05-DEC-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 110.27
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2107.97   324.00 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3554.62   970.20 763.21 903.46 0.00 0.00 0.00 0.00 50.47 114.46



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1010.78 24-JAN-16:03 972.00 342.97 684.76 0.00 0.00 0.00 0.00 0.00 103.05
February 2966.21 27-FEB-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 20.97
March 2994.18 18-MAR-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 15.61
April 3162.17 01-APR-18:02 702.00 734.94 774.30 0.00 0.00 0.00 0.00 18.36 0.00
May 3217.53 14-MAY-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 3.88 0.00
June 3007.49 24-JUN-18:02 702.00 734.94 774.30 0.00 0.00 0.00 0.00 0.00 26.41
July 3084.31 20-JUL-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 27.91 0.00
August 3263.26 10-AUG-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 50.14 0.00
September 3092.85 22-SEP-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 6.17 0.00
October 3123.07 04-OCT-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 6.72
November 2874.86 04-NOV-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 10.59
December 959.82 03-DEC-19:03 1053.00 1102.42 1161.45 0.00 0.00 0.00 0.00 0.00 87.87
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 959.82   324.00 205.78 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3263.26   1053.00 1102.42 1161.45 0.00 0.00 0.00 0.00 50.14 103.05



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 158.87 08-JAN-14:40 0.00 25.41 74.82 0.00 0.00 0.00 0.00 0.00 36.21
February 536.60 08-FEB-14:00 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 33.32
March 684.17 02-MAR-13:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 20.74
April 663.51 27-APR-13:10 0.00 21.56 67.08 0.00 0.00 0.00 0.00 5.05 0.00
May 638.43 04-MAY-13:20 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 1.16
June 500.61 28-JUN-13:20 0.00 21.56 67.08 0.00 0.00 0.00 0.00 2.29 0.00
July 618.63 31-JUL-13:20 0.00 21.56 67.08 0.00 0.00 0.00 0.00 7.79 0.00
August 761.86 24-AUG-13:10 0.00 21.56 67.08 0.00 0.00 0.00 0.00 10.23 0.00
September 810.42 14-SEP-13:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 0.05
October 834.64 04-OCT-12:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 5.25
November 548.58 04-NOV-13:50 0.00 25.41 74.82 0.00 0.00 0.00 0.00 0.00 4.49
December 484.60 05-DEC-12:25 0.00 43.11 134.16 0.00 0.00 0.00 0.00 0.00 25.53
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 158.87   0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 834.64   0.00 43.11 134.16 0.00 0.00 0.00 0.00 10.23 36.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 449.13 09-JAN-19:04 970.20 479.78 885.15 0.00 0.00 0.00 0.00 0.00 31.39
February 684.06 25-FEB-09:03 162.00 129.38 479.99 0.00 0.00 0.00 0.00 0.00 18.57
March 706.16 17-MAR-18:01 970.20 479.78 885.15 0.00 0.00 0.00 0.00 0.00 20.60
April 844.53 01-APR-18:02 702.00 462.06 758.70 0.00 0.00 0.00 0.00 6.42 0.00
May 855.37 14-MAY-18:02 702.00 462.06 758.70 0.00 0.00 0.00 0.00 0.00 0.78
June 872.45 09-JUN-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 0.54 0.00
July 907.93 24-JUL-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 10.62 0.00
August 897.11 10-AUG-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 14.05 0.00
September 819.11 13-SEP-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 0.49 0.00
October 749.42 04-OCT-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 0.80 0.00
November 686.71 04-NOV-08:63 162.00 129.38 479.99 0.00 0.00 0.00 0.00 0.00 16.19
December 483.75 05-DEC-19:03 1386.00 685.40 1264.50 0.00 0.00 0.00 0.00 0.00 31.32
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 449.13   162.00 129.38 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 907.93   1386.00 685.40 1264.50 0.00 0.00 0.00 0.00 14.05 31.39



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 926.77 10-JAN-09:03 252.00 377.32 792.83 0.00 0.00 0.00 0.00 0.00 110.86
February 2591.79 08-FEB-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 102.25
March 2990.94 18-MAR-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 0.00 15.88
April 3098.80 01-APR-18:02 702.00 735.03 774.39 0.00 0.00 0.00 0.00 19.45 0.00
May 3149.93 14-MAY-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 4.83 0.00
June 3006.83 02-JUN-18:01 970.20 763.21 903.46 0.00 0.00 0.00 0.00 0.00 20.84
July 3124.78 24-JUL-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 40.33 0.00
August 3141.64 10-AUG-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 52.14 0.00
September 3042.27 22-SEP-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 6.85 0.00
October 3097.86 04-OCT-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 6.57
November 2866.27 04-NOV-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 0.00 10.68
December 967.03 30-DEC-09:03 378.00 480.22 1143.15 0.00 0.00 0.00 0.00 0.00 123.02
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 926.77   252.00 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3149.93   970.20 763.21 1143.15 0.00 0.00 0.00 0.00 52.14 123.02



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 788.26 05-JAN-09:04 252.00 377.27 792.74 0.00 0.00 0.00 0.00 0.00 154.39
February 1090.96 27-FEB-09:01 360.00 538.96 1132.48 0.00 0.00 0.00 0.00 0.00 87.80
March 2522.42 02-MAR-09:01 252.00 377.27 792.74 0.00 0.00 0.00 0.00 0.00 124.91
April 2776.38 27-APR-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 30.41 0.00
May 2871.31 14-MAY-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 4.91 0.00
June 2818.92 28-JUN-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 18.68 0.00
July 2899.38 30-JUL-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 31.49 0.00
August 2892.51 23-AUG-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 41.89 0.00
September 2777.66 12-SEP-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 12.06 0.00
October 2736.98 04-OCT-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 4.00
November 1445.16 04-NOV-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 1.83
December 765.24 03-DEC-09:03 324.00 411.57 979.73 0.00 0.00 0.00 0.00 0.00 93.29
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 765.24   252.00 205.78 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2899.38   831.60 654.11 1132.48 0.00 0.00 0.00 0.00 41.89 154.39



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2352.63 12-JAN-07:10 2011.87 2489.76 0.00 0.00 0.00 0.00 0.00 0.00 123.33
February 2771.06 08-FEB-15:02 3017.81 2489.76 0.00 0.00 0.00 0.00 0.00 0.00 118.16
March 3147.70 15-MAR-06:07 7041.55 8714.15 0.00 0.00 0.00 0.00 0.00 0.00 127.88
April 3251.67 24-APR-23:34 18106.85 3983.61 0.00 0.00 0.00 0.00 0.00 0.00 127.86
May 3340.92 18-MAY-06:25 8047.49 9959.03 0.00 0.00 0.00 0.00 0.00 0.00 139.26
June 2810.79 13-JUN-23:40 4526.71 995.90 0.00 0.00 0.00 0.00 0.00 0.00 105.04
July 2547.20 24-JUL-18:10 10562.33 11950.84 0.00 0.00 0.00 0.00 0.00 40.04 0.00
August 2597.21 10-AUG-18:08 10562.33 11950.84 0.00 0.00 0.00 0.00 0.00 52.70 0.00
September 2879.38 27-SEP-05:14 17603.88 9959.03 0.00 0.00 0.00 0.00 0.00 0.00 123.18
October 3034.38 12-OCT-23:32 20370.20 4481.56 0.00 0.00 0.00 0.00 0.00 0.00 128.33
November 2678.33 28-NOV-23:25 4526.71 1493.85 0.00 0.00 0.00 0.00 0.00 0.00 118.47
December 2657.79 10-DEC-19:46 15089.04 17428.30 0.00 0.00 0.00 0.00 0.00 0.00 125.01
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2352.63   2011.87 995.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3340.92   20370.20 17428.30 0.00 0.00 0.00 0.00 0.00 52.70 139.26



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1787.89 20-JAN-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 114.81
February 3247.32 08-FEB-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 109.72
March 3485.52 18-MAR-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 0.00 16.71
April 3635.58 01-APR-18:02 702.00 735.03 774.39 0.00 0.00 0.00 0.00 18.00 0.00
May 3708.26 14-MAY-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 3.36 0.00
June 3427.18 02-JUN-18:01 970.20 763.21 903.46 0.00 0.00 0.00 0.00 0.00 20.36
July 3691.26 31-JUL-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 23.65 0.00
August 3729.93 10-AUG-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 49.83 0.00
September 3382.75 13-SEP-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 0.00 1.01
October 3642.92 04-OCT-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 7.97
November 3251.04 04-NOV-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 0.00 12.18
December 3041.96 05-DEC-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 110.93
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1787.89   324.00 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3729.93   970.20 763.21 903.46 0.00 0.00 0.00 0.00 49.83 114.81



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 780.03 11-JAN-16:05 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 49.79
February 3061.62 27-FEB-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 21.32
March 3080.57 18-MAR-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 15.77
April 3274.98 01-APR-18:02 702.00 734.94 774.30 0.00 0.00 0.00 0.00 17.82 0.00
May 3330.22 14-MAY-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 3.37 0.00
June 3103.48 24-JUN-18:02 702.00 734.94 774.30 0.00 0.00 0.00 0.00 0.00 26.75
July 3375.83 31-JUL-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 23.20 0.00
August 3355.12 10-AUG-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 49.33 0.00
September 3147.93 22-SEP-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 5.59 0.00
October 3217.72 04-OCT-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 6.95
November 2960.32 04-NOV-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 10.90
December 907.75 10-DEC-16:03 378.00 282.96 534.64 0.00 0.00 0.00 0.00 0.00 82.68
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 780.03   324.00 205.78 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3375.83   831.60 734.94 774.30 0.00 0.00 0.00 0.00 49.33 82.68



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1985.77 05-JAN-16:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 0.00 61.28
February 2040.44 10-FEB-16:01 972.00 215.63 670.96 0.00 0.00 0.00 0.00 0.00 59.13
March 2156.25 18-MAR-15:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 0.00 8.99
April 2173.03 02-APR-15:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 0.00 7.21
May 2224.97 14-MAY-15:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 2.22 0.00
June 2156.88 09-JUN-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 0.97 0.00
July 2175.87 24-JUL-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 20.81 0.00
August 2209.47 24-AUG-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 22.70 0.00
September 2193.70 14-SEP-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 3.67 0.00
October 2238.19 04-OCT-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 0.00 4.32
November 1989.68 10-NOV-16:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 0.00 50.85
December 1987.83 05-DEC-16:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 0.00 59.59
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1985.77   324.00 129.38 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2238.19   972.00 411.24 758.70 0.00 0.00 0.00 0.00 22.70 61.28



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 31352.01 30-JAN-23:31 242898.91 9282.17 60731.12 0.00 0.00 0.00 0.00 0.00 320.67
February 31633.24 04-FEB-00:37 269887.68 6875.68 22493.01 0.00 0.00 0.00 0.00 0.00 297.59
March 31550.20 03-MAR-05:08 269887.68 6875.68 22493.01 0.00 0.00 0.00 0.00 0.00 294.44
April 31539.07 07-APR-23:14 269887.68 6875.68 22493.01 0.00 0.00 0.00 0.00 0.00 279.92
May 31151.59 12-MAY-05:38 209912.64 11001.09 56232.52 0.00 0.00 0.00 0.00 0.00 292.13
June 29781.33 15-JUN-01:37 242898.91 3094.06 20243.71 0.00 0.00 0.00 0.00 0.00 260.43
July 22509.39 24-JUL-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 27.46
August 22437.89 10-AUG-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 20.73
September 29862.59 28-SEP-05:32 167930.11 11001.09 44986.02 0.00 0.00 0.00 0.00 0.00 275.70
October 31689.90 31-OCT-03:59 269887.68 3437.84 22493.01 0.00 0.00 0.00 0.00 0.00 290.63
November 31282.57 20-NOV-03:42 161932.61 2062.70 13495.81 0.00 0.00 0.00 0.00 0.00 285.75
December 30392.50 04-DEC-21:34 239900.16 27502.72 67479.03 0.00 0.00 0.00 0.00 0.00 335.19
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 22437.89   26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 20.73
Maximum of Months 31689.90   269887.68 27502.72 67479.03 0.00 0.00 0.00 0.00 0.00 335.19



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 33105.66 30-JAN-23:31 242898.91 9282.17 60731.12 0.00 0.00 0.00 0.00 0.00 322.42
February 33312.46 04-FEB-02:25 107955.07 1375.14 8997.20 0.00 0.00 0.00 0.00 0.00 294.46
March 33196.19 03-MAR-05:08 269887.68 6875.68 22493.01 0.00 0.00 0.00 0.00 0.00 295.43
April 34092.76 07-APR-23:14 269887.68 6875.68 22493.01 0.00 0.00 0.00 0.00 0.00 281.57
May 33648.57 12-MAY-05:45 209912.64 11001.09 56232.52 0.00 0.00 0.00 0.00 0.00 293.66
June 31623.19 15-JUN-05:10 62973.79 3575.35 16869.76 0.00 0.00 0.00 0.00 0.00 265.12
July 23704.66 24-JUL-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 33.61
August 23650.32 10-AUG-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 20.80
September 31728.24 28-SEP-05:20 104956.32 6875.68 28116.26 0.00 0.00 0.00 0.00 0.00 275.21
October 33547.20 24-OCT-02:20 269887.68 3437.84 22493.01 0.00 0.00 0.00 0.00 0.00 297.40
November 32890.02 20-NOV-03:42 161932.61 2062.70 13495.81 0.00 0.00 0.00 0.00 0.00 286.59
December 32360.57 30-DEC-18:37 179925.12 20627.04 67479.03 0.00 0.00 0.00 0.00 0.00 337.54
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 23650.32   26988.77 1375.14 6747.90 0.00 0.00 0.00 0.00 0.00 20.80
Maximum of Months 34092.76   269887.68 20627.04 67479.03 0.00 0.00 0.00 0.00 0.00 337.54



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 37287.85 30-JAN-18:51 9339.96 5085.88 104389.99 157449.82 0.00 0.00 0.00 0.00 307.31
February 36821.63 08-FEB-17:21 9339.96 2119.12 104389.99 157449.82 0.00 0.00 0.00 0.00 296.68
March 39543.45 29-MAR-11:16 5337.12 3027.31 149128.56 187440.26 0.00 0.00 0.00 0.00 248.02
April 37908.16 11-APR-11:23 3735.98 2119.12 104389.99 131208.19 0.00 0.00 0.00 0.00 239.16
May 38156.54 12-MAY-05:45 18679.92 4843.69 125511.30 74976.11 0.00 0.00 0.00 0.00 265.35
June 31669.09 15-JUN-05:50 18679.92 4843.69 125511.30 74976.11 0.00 0.00 0.00 0.00 232.02
July 31245.32 24-JUL-10:37 1601.14 908.19 44738.57 56232.08 0.00 0.00 0.00 26.26 0.00
August 31285.32 13-AUG-10:40 2401.70 1089.83 44738.57 56232.08 0.00 0.00 0.00 0.15 0.00
September 33206.85 28-SEP-06:44 10674.24 6054.62 149128.56 112464.16 0.00 0.00 0.00 0.00 244.74
October 34742.99 24-OCT-06:20 6404.54 3632.77 89477.13 67478.50 0.00 0.00 0.00 0.00 292.12
November 37041.01 23-NOV-18:36 7471.97 4238.23 104389.99 157449.82 0.00 0.00 0.00 0.00 307.20
December 36356.03 13-DEC-18:19 13342.80 7265.54 149128.56 224928.32 0.00 0.00 0.00 0.00 288.30
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 31245.32   1601.14 908.19 44738.57 56232.08 0.00 0.00 0.00 0.00 0.00
Maximum of Months 39543.45   18679.92 7265.54 149128.56 224928.32 0.00 0.00 0.00 26.26 307.31



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4728.93 05-JAN-15:03 7984.80 6587.56 0.00 0.00 0.00 0.00 0.00 0.00 221.96
February 5869.36 08-FEB-15:02 3193.92 2635.02 0.00 0.00 0.00 0.00 0.00 0.00 215.07
March 6436.29 15-MAR-06:07 7452.48 9222.58 0.00 0.00 0.00 0.00 0.00 0.00 226.02
April 6582.45 24-APR-23:34 19163.52 4216.04 0.00 0.00 0.00 0.00 0.00 0.00 223.78
May 6536.01 18-MAY-06:25 8517.12 10540.09 0.00 0.00 0.00 0.00 0.00 0.00 237.01
June 5561.11 13-JUN-23:40 4790.88 1054.01 0.00 0.00 0.00 0.00 0.00 0.00 180.11
July 5838.08 24-JUL-15:03 7984.80 3952.54 0.00 0.00 0.00 0.00 0.00 87.26 0.00
August 6834.73 10-AUG-14:20 798.48 658.76 0.00 0.00 0.00 0.00 0.00 78.05 0.00
September 5595.24 27-SEP-05:14 18631.20 10540.09 0.00 0.00 0.00 0.00 0.00 0.00 208.89
October 6030.03 12-OCT-23:32 21558.96 4743.04 0.00 0.00 0.00 0.00 0.00 0.00 221.45
November 5456.03 28-NOV-23:25 4790.88 1581.01 0.00 0.00 0.00 0.00 0.00 0.00 208.81
December 5086.88 05-DEC-11:20 1596.96 1976.27 0.00 0.00 0.00 0.00 0.00 0.00 187.63
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4728.93   798.48 658.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6834.73   21558.96 10540.09 0.00 0.00 0.00 0.00 0.00 87.26 237.01



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.382706E+12 242728.45 02-JAN-20:00 0.564618E+12 531360.57 22-JAN-18:49
February 0.345646E+12 257645.88 08-FEB-20:19 0.482936E+12 515983.14 09-FEB-21:10
March 0.384814E+12 249027.48 14-MAR-19:10 0.502461E+12 472878.38 04-MAR-20:30
April 0.385287E+12 315838.28 27-APR-19:10 0.461481E+12 427822.76 03-APR-17:40
May 0.411449E+12 306811.02 04-MAY-19:19 0.457469E+12 401507.38 23-MAY-17:10
June 0.417652E+12 322838.52 28-JUN-19:10 0.412990E+12 364591.16 06-JUN-17:00
July 0.464559E+12 350275.09 24-JUL-19:49 0.411734E+12 349882.59 03-JUL-17:19
August 0.487084E+12 370048.64 10-AUG-19:30 0.410322E+12 349546.23 31-AUG-17:10
September 0.415844E+12 306372.06 13-SEP-19:10 0.410682E+12 351829.87 26-SEP-17:00
October 0.393180E+12 275854.22 04-OCT-19:00 0.473026E+12 458732.72 29-OCT-21:49
November 0.370868E+12 248207.81 21-NOV-20:40 0.501041E+12 487303.59 29-NOV-19:00
December 0.384992E+12 250059.21 12-DEC-20:10 0.554273E+12 503183.79 27-DEC-18:49
             
Annual Sum or Average 0.484408E+13     0.564303E+13    
Minimum of Months 0.345646E+12 242728.45   0.410322E+12 349546.23  
Maximum of Months 0.487084E+12 370048.64   0.564618E+12 531360.57  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.655864E+11 0.263426E+11 0.148212E+12 0.553311E+11 0.438311E+11 0.409869E+10 0.00 0.123787E+10 0.00 0.00 0.251287E+11 0.770465E+10 0.00
February 0.590687E+11 0.217174E+11 0.133859E+12 0.499765E+11 0.391046E+11 0.509453E+10 0.00 0.389249E+10 0.00 0.00 0.212434E+11 0.696225E+10 0.00
March 0.652318E+11 0.211983E+11 0.148223E+12 0.553338E+11 0.439875E+11 0.776932E+10 0.00 0.807595E+10 0.00 0.00 0.220406E+11 0.770293E+10 0.00
April 0.627845E+11 0.176575E+11 0.143397E+12 0.535454E+11 0.437748E+11 0.104089E+11 0.00 0.235895E+11 0.00 0.00 0.175788E+11 0.746508E+10 0.00
May 0.647649E+11 0.156832E+11 0.148223E+12 0.553318E+11 0.469917E+11 0.133957E+11 0.00 0.409289E+11 0.00 0.00 0.131434E+11 0.770458E+10 0.00
June 0.624865E+11 0.138016E+11 0.143446E+12 0.535479E+11 0.464254E+11 0.148506E+11 0.00 0.621002E+11 0.00 0.00 0.841274E+10 0.745696E+10 0.00
July 0.645411E+11 0.148953E+11 0.148174E+12 0.553288E+11 0.498713E+11 0.167524E+11 0.00 0.951961E+11 0.00 0.00 0.680073E+10 0.771264E+10 0.00
August 0.648290E+11 0.171014E+11 0.148234E+12 0.553334E+11 0.503864E+11 0.171879E+11 0.00 0.113050E+12 0.00 0.00 0.792341E+10 0.770440E+10 0.00
September 0.630045E+11 0.192703E+11 0.143408E+12 0.535457E+11 0.464131E+11 0.138643E+11 0.00 0.542762E+11 0.00 0.00 0.944745E+10 0.746644E+10 0.00
October 0.653565E+11 0.228667E+11 0.148201E+12 0.553308E+11 0.456018E+11 0.933078E+10 0.00 0.170713E+11 0.00 0.00 0.164398E+11 0.770306E+10 0.00
November 0.634616E+11 0.247205E+11 0.143462E+12 0.535470E+11 0.426848E+11 0.521918E+10 0.00 0.423611E+10 0.00 0.00 0.209976E+11 0.744903E+10 0.00
December 0.655415E+11 0.270193E+11 0.148174E+12 0.553298E+11 0.442974E+11 0.483631E+10 0.00 0.197046E+10 0.00 0.00 0.248662E+11 0.771264E+10 0.00
                           
Annual Sum or Average 0.766657E+12 0.242274E+12 0.174501E+13 0.651482E+12 0.543370E+12 0.122809E+12 0.00 0.425625E+12 0.00 0.00 0.194023E+12 0.907447E+11 0.00
Minimum of Months 0.590687E+11 0.138016E+11 0.133859E+12 0.499765E+11 0.391046E+11 0.409869E+10 0.00 0.123787E+10 0.00 0.00 0.680073E+10 0.696225E+10 0.00
Maximum of Months 0.655864E+11 0.270193E+11 0.148234E+12 0.553338E+11 0.503864E+11 0.171879E+11 0.00 0.113050E+12 0.00 0.00 0.251287E+11 0.771264E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.132621E+12 0.00 0.280079E+12 0.00 0.00
February 0.137204E+12 0.00 0.915097E+11 0.00 0.254223E+12 0.00 0.00
March 0.152024E+12 0.00 0.710507E+11 0.00 0.279386E+12 0.00 0.00
April 0.146956E+12 0.00 0.491919E+11 0.00 0.265333E+12 0.00 0.00
May 0.151978E+12 0.00 0.381083E+11 0.00 0.267382E+12 0.00 0.00
June 0.147114E+12 0.00 0.135053E+11 0.00 0.252371E+12 0.00 0.00
July 0.151820E+12 0.00 0.387149E+10 0.00 0.256043E+12 0.00 0.00
August 0.152039E+12 0.00 0.361550E+10 0.00 0.254668E+12 0.00 0.00
September 0.146971E+12 0.00 0.151773E+11 0.00 0.248534E+12 0.00 0.00
October 0.151903E+12 0.00 0.590992E+11 0.00 0.262024E+12 0.00 0.00
November 0.147091E+12 0.00 0.937745E+11 0.00 0.260176E+12 0.00 0.00
December 0.151820E+12 0.00 0.127031E+12 0.00 0.275421E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.698555E+12 0.00 0.315564E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 0.361550E+10 0.00 0.248534E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.132621E+12 0.00 0.280079E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 62892.57 02-JAN-20:10 15448.40 01-JAN-00:10 89475.41 02-JAN-07:10 39726.11 02-JAN-07:19 41298.23 31-JAN-22:49 4803.74 25-JAN-21:00 0.00 01-JAN-00:10
February 62892.57 01-FEB-20:10 15448.40 01-FEB-00:10 89475.41 01-FEB-07:10 39726.11 01-FEB-07:19 36545.43 07-FEB-20:40 6470.48 27-FEB-15:09 0.00 01-FEB-00:10
March 62892.57 01-MAR-20:10 15448.40 01-MAR-00:10 89475.41 01-MAR-07:10 39726.11 13-MAR-06:19 31054.70 17-MAR-21:10 7047.85 18-MAR-16:10 0.00 01-MAR-00:10
April 62892.57 03-APR-19:10 15448.40 01-APR-00:10 89475.41 03-APR-06:10 39725.67 04-APR-06:19 35006.83 05-APR-02:30 8106.29 26-APR-15:09 0.00 01-APR-00:10
May 62892.57 01-MAY-19:10 15448.40 01-MAY-00:10 89475.41 01-MAY-06:10 39725.51 01-MAY-06:19 30020.36 04-MAY-21:10 8195.07 04-MAY-18:10 0.00 01-MAY-00:10
June 62892.57 01-JUN-19:40 15448.40 01-JUN-00:10 89475.41 01-JUN-06:10 39724.49 14-JUN-06:19 30700.89 28-JUN-21:10 8215.59 27-JUN-18:10 0.00 01-JUN-00:10
July 62892.57 10-JUL-19:30 15448.40 01-JUL-00:10 89475.41 03-JUL-06:10 39724.49 10-JUL-06:19 32006.43 31-JUL-21:10 8187.26 19-JUL-18:10 0.00 01-JUL-00:10
August 62892.57 01-AUG-19:19 15448.40 01-AUG-00:10 89475.41 01-AUG-06:10 39725.08 16-AUG-06:19 34279.93 10-AUG-21:10 8225.48 10-AUG-18:10 0.00 01-AUG-00:10
September 62892.57 01-SEP-19:10 15448.40 01-SEP-00:10 89475.41 01-SEP-06:10 39726.11 06-SEP-06:19 33768.95 14-SEP-21:10 8185.35 08-SEP-16:30 0.00 01-SEP-00:10
October 62892.57 02-OCT-19:10 15448.40 01-OCT-00:10 89475.41 02-OCT-06:10 39726.11 02-OCT-06:19 33225.42 12-OCT-21:10 7701.32 04-OCT-15:09 0.00 01-OCT-00:10
November 62892.57 01-NOV-19:10 15448.40 01-NOV-00:10 89475.41 01-NOV-06:10 39726.11 01-NOV-06:19 33769.78 29-NOV-22:00 7465.98 04-NOV-15:09 0.00 01-NOV-00:10
December 62892.57 01-DEC-20:10 15448.40 01-DEC-00:10 89475.41 01-DEC-07:10 39726.11 01-DEC-07:19 33366.00 14-DEC-22:00 5778.63 05-DEC-12:30 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 62892.57   15448.40   89475.41   39724.49   30020.36   4803.74   0.00  
Maximum of Months 62892.57   15448.40   89475.41   39726.11   41298.23   8225.48   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 4523.89 08-JAN-14:30 0.00 0.00 9938.94 01-JAN-00:10 4738.51 02-JAN-07:30 0.00
February 48063.84 27-FEB-14:00 0.00 0.00 9938.94 01-FEB-00:20 4738.28 10-FEB-07:10 0.00
March 55779.43 18-MAR-15:09 0.00 0.00 9938.94 01-MAR-00:20 4738.30 27-MAR-18:40 0.00
April 99451.79 27-APR-15:09 0.00 0.00 9938.94 01-APR-00:10 4738.37 11-APR-06:19 0.00
May 88139.13 04-MAY-15:09 0.00 0.00 9938.94 01-MAY-00:10 4738.61 31-MAY-18:10 0.00
June 101021.37 28-JUN-18:10 0.00 0.00 9938.94 01-JUN-00:10 4738.35 26-JUN-06:10 0.00
July 124230.06 24-JUL-18:10 0.00 0.00 9938.94 01-JUL-03:39 4738.31 21-JUL-18:30 0.00
August 142582.39 10-AUG-18:10 0.00 0.00 9938.94 01-AUG-02:49 4738.53 21-AUG-06:10 0.00
September 98914.43 14-SEP-15:30 0.00 0.00 9938.94 02-SEP-01:30 4738.54 20-SEP-06:40 0.00
October 74864.05 04-OCT-15:09 0.00 0.00 9938.94 01-OCT-00:10 4738.52 11-OCT-18:10 0.00
November 62746.68 04-NOV-15:09 0.00 0.00 9938.94 01-NOV-00:10 4738.59 02-NOV-06:49 0.00
December 13588.40 05-DEC-12:30 0.00 0.00 9938.94 01-DEC-00:20 4738.30 15-DEC-19:10 0.00
                   
Annual Sum or Average     0.00 0.00         0.00
Minimum of Months 4523.89   0.00 0.00 9938.94   4738.28   0.00
Maximum of Months 142582.39   0.00 0.00 9938.94   4738.61   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 242728.45 02-JAN-20:00 62892.57 88772.42 15448.40 32159.77 22213.30 4192.49 0.00 1217.33 0.00
February 257645.88 08-FEB-20:19 62892.57 88772.42 15448.40 32159.77 35730.63 4512.19 0.00 2115.40 0.00
March 249027.48 14-MAR-19:10 62892.57 88772.42 15448.40 32151.31 22194.79 5884.19 0.00 16236.72 0.00
April 315838.28 27-APR-19:10 62892.57 88772.42 15448.40 32149.92 25522.88 7994.02 0.00 75504.12 0.00
May 306811.02 04-MAY-19:19 62892.57 88772.42 15448.40 32159.77 25375.13 8087.74 0.00 67794.08 0.00
June 322838.52 28-JUN-19:10 60488.76 88772.42 0.00 32148.47 26748.73 8006.73 0.00 90355.92 0.00
July 350275.09 24-JUL-19:49 62892.57 88772.42 15448.40 32159.77 28106.07 8076.30 0.00 98482.52 0.00
August 370048.64 10-AUG-19:30 62892.57 88772.42 15448.40 32159.27 29138.05 8118.19 0.00 117286.87 0.00
September 306372.06 13-SEP-19:10 62892.57 88772.42 15448.40 32151.31 26363.69 7817.25 0.00 66443.13 0.00
October 275854.22 04-OCT-19:00 62892.57 88772.42 15448.40 32159.77 25289.05 6627.70 0.00 38715.61 0.00
November 248207.81 21-NOV-20:40 62892.57 88772.42 15448.40 32159.77 27140.78 4392.31 0.00 1725.64 0.00
December 250059.21 12-DEC-20:10 62892.57 88772.42 15448.40 32151.31 29855.31 4278.81 0.00 1292.95 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 242728.45   60488.76 88772.42 0.00 32148.47 22194.79 4192.49 0.00 1217.33 0.00
Maximum of Months 370048.64   62892.57 88772.42 15448.40 32159.77 35730.63 8118.19 0.00 117286.87 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 186463.87 22-JAN-18:49 0.00 282769.04 18-JAN-21:40 0.00
February 104248.32 01-FEB-18:10 0.00 183030.78 12-FEB-11:30 0.00 278166.04 10-FEB-21:40 0.00
March 104248.32 01-MAR-18:10 0.00 178116.24 23-MAR-08:39 0.00 283177.66 30-MAR-17:30 0.00
April 104248.32 01-APR-17:10 0.00 182289.03 09-APR-06:49 0.00 286457.09 20-APR-20:40 0.00
May 104248.32 01-MAY-17:10 0.00 171470.59 23-MAY-04:40 0.00 261949.09 10-MAY-20:49 0.00
June 104248.32 01-JUN-17:10 0.00 99830.61 15-JUN-02:00 0.00 249428.17 06-JUN-20:00 0.00
July 104248.32 01-JUL-17:10 0.00 51276.26 03-JUL-03:00 0.00 246321.32 03-JUL-20:40 0.00
August 104248.32 01-AUG-17:10 0.00 54598.88 21-AUG-04:00 0.00 245882.77 31-AUG-20:19 0.00
September 104248.32 01-SEP-17:10 0.00 130869.37 27-SEP-04:40 0.00 246508.93 29-SEP-20:30 0.00
October 104248.32 02-OCT-17:10 0.00 182055.50 29-OCT-00:20 0.00 257418.31 31-OCT-20:49 0.00
November 104248.32 01-NOV-17:10 0.00 186550.53 23-NOV-11:50 0.00 265476.66 30-NOV-21:19 0.00
December 104248.32 01-DEC-18:10 0.00 176240.50 15-DEC-09:00 0.00 273215.29 28-DEC-21:00 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 51276.26   0.00 245882.77   0.00
Maximum of Months 104248.32   0.00 186550.53   0.00 286457.09   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 37.50 25.23 37.50 25.23
February 0.00 0.00 0.00 0.00 19.67 25.29 19.67 25.29
March 0.00 0.00 0.00 0.00 35.50 25.14 35.50 25.14
April 0.00 0.00 0.00 0.00 24.17 25.11 24.17 25.11
May 0.00 0.00 0.00 0.00 14.00 25.10 14.00 25.10
June 0.00 0.00 0.00 0.00 0.33 25.11 0.33 25.11
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 1.33 25.03 1.33 25.03
October 0.00 0.00 0.00 0.00 20.33 25.09 20.33 25.09
November 0.00 0.00 0.00 0.00 45.83 25.15 45.83 25.15
December 0.00 0.00 0.00 0.00 57.50 25.25 57.50 25.25
                 
Annual Sum or Average 0.00   0.00   256.17 25.18 256.17 25.18
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 57.50 25.29 57.50 25.29



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.17 24.62 0.17 24.62
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.17 24.65 0.17 24.65
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.33 24.64 0.33 24.64
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 24.65 0.17 24.65



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.77 0.17 21.77
May 0.00 0.00 0.00 0.00 1.00 21.83 1.00 21.83
June 0.00 0.00 0.00 0.00 0.33 21.74 0.33 21.74
July 0.00 0.00 0.00 0.00 1.17 21.73 1.17 21.73
August 0.00 0.00 0.00 0.00 1.83 21.78 1.83 21.78
September 0.00 0.00 0.00 0.00 1.17 21.87 1.17 21.87
October 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   5.83 21.79 5.83 21.79
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.83 21.87 1.83 21.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.33 21.91 0.33 21.91
June 0.00 0.00 0.00 0.00 1.00 21.76 1.00 21.76
July 0.00 0.00 0.00 0.00 1.83 21.79 1.83 21.79
August 0.00 0.00 0.00 0.00 1.17 21.72 1.17 21.72
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.33 21.77 4.33 21.77
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.83 21.91 1.83 21.91



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.17 21.71 0.17 21.71
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.17 21.71 0.17 21.71
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 21.71 0.17 21.71



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.50 21.74 0.50 21.74
May 0.00 0.00 0.00 0.00 0.67 21.77 0.67 21.77
June 0.00 0.00 0.00 0.00 0.83 21.69 0.83 21.69
July 0.00 0.00 0.00 0.00 1.33 21.74 1.33 21.74
August 0.00 0.00 0.00 0.00 1.17 21.71 1.17 21.71
September 0.00 0.00 0.00 0.00 0.33 21.67 0.33 21.67
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.83 21.72 4.83 21.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.33 21.77 1.33 21.77



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.50 21.77 0.50 21.77
May 0.00 0.00 0.00 0.00 0.67 21.85 0.67 21.85
June 0.00 0.00 0.00 0.00 1.17 21.78 1.17 21.78
July 0.00 0.00 0.00 0.00 1.67 21.84 1.67 21.84
August 0.00 0.00 0.00 0.00 1.17 21.78 1.17 21.78
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   5.17 21.80 5.17 21.80
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.67 21.85 1.67 21.85



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 21.82 0.33 21.82
May 0.00 0.00 0.00 0.00 2.33 21.87 2.33 21.87
June 0.00 0.00 0.00 0.00 1.00 21.74 1.00 21.74
July 0.00 0.00 0.00 0.00 2.33 21.76 2.33 21.76
August 0.00 0.00 0.00 0.00 3.00 21.80 3.00 21.80
September 0.00 0.00 0.00 0.00 2.17 21.83 2.17 21.83
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   11.17 21.81 11.17 21.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.00 21.87 3.00 21.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
May 0.00 0.00 0.00 0.00 1.83 21.83 1.83 21.83
June 0.00 0.00 0.00 0.00 1.67 21.79 1.67 21.79
July 0.00 0.00 0.00 0.00 3.00 21.81 3.00 21.81
August 0.00 0.00 0.00 0.00 1.83 21.80 1.83 21.80
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   8.50 21.81 8.50 21.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.00 21.83 3.00 21.83



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.70 0.17 21.70
May 0.00 0.00 0.00 0.00 0.17 21.72 0.17 21.72
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.67 21.70 0.67 21.70
September 0.00 0.00 0.00 0.00 1.17 21.75 1.17 21.75
October 0.00 0.00 0.00 0.00 0.17 21.78 0.17 21.78
November 0.00 0.00 0.00 0.00 0.17 21.67 0.17 21.67
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.50 21.73 2.50 21.73
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.17 21.78 1.17 21.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 3.67 24.72 3.67 24.72
February 0.00 0.00 0.00 0.00 2.83 24.71 2.83 24.71
March 0.00 0.00 0.00 0.00 6.33 24.76 6.33 24.76
April 0.00 0.00 0.00 0.00 3.67 24.73 3.67 24.73
May 0.00 0.00 0.00 0.00 6.00 24.73 6.00 24.73
June 0.00 0.00 0.00 0.00 0.33 24.62 0.33 24.62
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.17 24.70 0.17 24.70
October 0.00 0.00 0.00 0.00 6.33 24.69 6.33 24.69
November 0.00 0.00 0.00 0.00 3.00 24.73 3.00 24.73
December 0.00 0.00 0.00 0.00 4.33 24.78 4.33 24.78
                 
Annual Sum or Average 0.00   0.00   36.67 24.73 36.67 24.73
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.33 24.78 6.33 24.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 5.17 24.78 5.17 24.78
February 0.00 0.00 0.00 0.00 4.17 24.74 4.17 24.74
March 0.00 0.00 0.00 0.00 8.00 24.81 8.00 24.81
April 0.00 0.00 0.00 0.00 4.67 24.75 4.67 24.75
May 0.00 0.00 0.00 0.00 7.50 24.75 7.50 24.75
June 0.00 0.00 0.00 0.00 0.50 24.64 0.50 24.64
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.17 24.74 0.17 24.74
October 0.00 0.00 0.00 0.00 8.67 24.72 8.67 24.72
November 0.00 0.00 0.00 0.00 5.67 24.71 5.67 24.71
December 0.00 0.00 0.00 0.00 7.17 24.77 7.17 24.77
                 
Annual Sum or Average 0.00   0.00   51.67 24.75 51.67 24.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 8.67 24.81 8.67 24.81



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 50.67 25.17 50.67 25.17
February 0.00 0.00 0.00 0.00 33.00 25.14 33.00 25.14
March 0.00 0.00 0.00 0.00 61.17 25.09 61.17 25.09
April 0.00 0.00 0.00 0.00 37.17 25.06 37.17 25.06
May 0.00 0.00 0.00 0.00 25.83 25.09 25.83 25.09
June 0.00 0.00 0.00 0.00 3.83 24.77 3.83 24.77
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 3.17 24.85 3.17 24.85
October 0.00 0.00 0.00 0.00 41.50 24.95 41.50 24.95
November 0.00 0.00 0.00 0.00 57.50 25.05 57.50 25.05
December 0.00 0.00 0.00 0.00 70.50 25.11 70.50 25.11
                 
Annual Sum or Average 0.00   0.00   384.33 25.08 384.33 25.08
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 70.50 25.17 70.50 25.17



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 726.33 23.49 0.00 23.49 0.00 23.49
February 663.17 23.33 0.00 23.33 0.00 23.33
March 739.67 23.19 0.00 23.19 0.00 23.19
April 718.83 23.06 0.00 23.06 0.00 23.06
May 741.33 23.11 0.00 23.11 0.00 23.11
June 679.67 23.18 0.00 23.18 0.00 23.18
July 566.00 23.31 14.50 23.32 0.00 23.32
August 337.83 23.29 36.67 23.36 0.00 23.36
September 236.50 23.43 69.67 23.55 0.00 23.55
October 327.17 23.60 3.00 23.61 0.00 23.61
November 352.17 23.69 23.83 23.71 0.00 23.71
December 640.50 23.65 0.00 23.65 0.00 23.65
             
Annual Sum or Average 6729.17 23.33 147.67 23.34 0.00 23.34
Minimum of Months 236.50 23.06 0.00 23.06 0.00 23.06
Maximum of Months 741.33 23.69 69.67 23.71 0.00 23.71



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 738.83 21.04 167.17 21.04 165.83 21.03
February 646.17 21.10 106.33 21.13 95.67 21.12
March 705.00 21.17 26.00 21.24 6.83 21.24
April 666.83 21.26 30.67 21.37 0.00 21.37
May 677.00 21.32 37.33 21.44 0.00 21.44
June 666.50 21.39 21.00 21.45 0.00 21.45
July 606.00 21.55 88.67 21.81 0.00 21.81
August 555.67 21.53 132.83 21.94 0.00 21.94
September 577.17 21.34 100.83 21.71 0.00 21.71
October 673.67 21.20 48.67 21.38 0.00 21.38
November 705.33 21.06 28.50 21.10 17.83 21.10
December 728.50 21.07 132.17 21.07 128.33 21.06
             
Annual Sum or Average 7946.67 21.24 920.17 21.37 414.50 21.36
Minimum of Months 555.67 21.04 21.00 21.04 0.00 21.03
Maximum of Months 738.83 21.55 167.17 21.94 165.83 21.94



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.68 0.00 21.68 0.00 21.68
February 671.67 21.96 0.00 21.96 0.00 21.96
March 743.50 22.37 0.00 22.37 0.00 22.37
April 682.33 22.60 3.50 22.61 0.00 22.61
May 659.00 22.80 13.17 22.83 0.00 22.83
June 576.50 22.84 25.83 22.89 0.00 22.89
July 417.83 22.98 120.67 23.20 0.00 23.20
August 329.17 22.89 195.00 23.27 0.00 23.27
September 474.67 22.82 86.17 22.99 0.00 22.99
October 710.33 22.60 0.00 22.60 0.00 22.60
November 717.33 22.04 0.00 22.04 0.00 22.04
December 744.00 21.81 0.00 21.81 0.00 21.81
             
Annual Sum or Average 7470.33 22.38 444.33 22.47 0.00 22.47
Minimum of Months 329.17 21.68 0.00 21.68 0.00 21.68
Maximum of Months 744.00 22.98 195.00 23.27 0.00 23.27



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.11 9.33 21.10 9.33 21.10
February 672.00 21.24 5.00 21.23 5.00 21.23
March 744.00 21.56 0.00 21.56 0.00 21.56
April 720.00 21.96 0.00 21.96 0.00 21.96
May 742.50 22.44 0.00 22.44 0.00 22.44
June 710.33 22.73 0.00 22.73 0.00 22.73
July 667.17 23.03 11.33 23.05 0.00 23.05
August 596.17 23.07 20.67 23.10 0.00 23.10
September 700.00 22.71 0.00 22.71 0.00 22.71
October 744.00 22.05 0.00 22.05 0.00 22.05
November 720.00 21.40 0.00 21.40 0.00 21.40
December 744.00 21.14 0.00 21.14 0.00 21.14
             
Annual Sum or Average 8504.17 22.01 46.33 22.02 14.33 22.02
Minimum of Months 596.17 21.11 0.00 21.10 0.00 21.10
Maximum of Months 744.00 23.07 20.67 23.10 9.33 23.10



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.02 17.67 21.02 17.67 21.02
February 672.00 21.09 16.50 21.09 16.50 21.09
March 744.00 21.30 0.00 21.30 0.00 21.30
April 720.00 21.70 0.00 21.70 0.00 21.70
May 744.00 22.20 0.00 22.20 0.00 22.20
June 720.00 22.51 0.00 22.51 0.00 22.51
July 733.17 22.87 0.00 22.87 0.00 22.87
August 713.67 22.96 0.00 22.96 0.00 22.96
September 720.00 22.50 0.00 22.50 0.00 22.50
October 744.00 21.78 0.00 21.78 0.00 21.78
November 720.00 21.20 0.00 21.20 0.00 21.20
December 744.00 21.03 0.00 21.03 0.00 21.03
             
Annual Sum or Average 8718.83 21.85 34.17 21.84 34.17 21.84
Minimum of Months 672.00 21.02 0.00 21.02 0.00 21.02
Maximum of Months 744.00 22.96 17.67 22.96 17.67 22.96



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 260.50 23.15 545.00 23.43 162.50 23.58
February 233.67 23.23 499.00 23.43 159.33 23.57
March 275.33 23.41 600.17 23.48 201.33 23.62
April 267.83 23.61 617.00 23.47 219.17 23.61
May 292.83 23.75 659.50 23.47 260.67 23.60
June 285.83 23.81 641.67 23.45 267.67 23.57
July 297.67 23.91 685.17 23.46 289.00 23.58
August 305.83 23.95 702.33 23.44 302.50 23.57
September 288.00 23.89 660.50 23.46 277.33 23.58
October 291.00 23.63 649.33 23.47 244.00 23.61
November 265.33 23.50 590.83 23.49 198.33 23.64
December 250.50 23.34 575.00 23.48 164.83 23.65
             
Annual Sum or Average 3314.33 23.62 7425.50 23.46 2746.67 23.60
Minimum of Months 233.67 23.15 499.00 23.43 159.33 23.57
Maximum of Months 305.83 23.95 702.33 23.49 302.50 23.65



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 732.67 21.39 10.00 21.41 4.50 21.41
February 625.00 21.62 25.83 21.71 0.17 21.71
March 667.83 21.90 38.17 22.01 0.00 22.01
April 595.67 22.10 63.67 22.25 0.00 22.25
May 568.17 22.22 88.83 22.40 0.00 22.40
June 494.50 22.26 94.17 22.45 0.00 22.45
July 326.00 22.33 264.50 22.85 0.83 22.85
August 312.17 22.32 332.83 23.00 21.83 23.02
September 394.83 22.11 230.67 22.69 0.00 22.69
October 599.00 22.03 82.67 22.25 0.00 22.25
November 690.83 21.59 16.83 21.64 1.17 21.64
December 718.83 21.47 21.33 21.52 6.50 21.51
             
Annual Sum or Average 6725.50 21.88 1269.50 22.15 35.00 22.15
Minimum of Months 312.17 21.39 10.00 21.41 0.00 21.41
Maximum of Months 732.67 22.33 332.83 23.00 21.83 23.02



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 743.33 22.16 0.00 22.16 0.00 22.16
February 651.50 22.42 1.83 22.43 0.00 22.43
March 683.50 22.75 0.83 22.75 0.00 22.75
April 553.17 22.87 36.17 22.93 0.00 22.93
May 423.00 22.87 90.33 23.06 0.00 23.06
June 327.83 22.83 170.17 23.21 0.00 23.21
July 176.83 22.92 330.83 23.54 2.67 23.54
August 149.67 22.99 472.50 23.65 24.83 23.66
September 233.17 22.77 313.00 23.40 8.50 23.41
October 517.67 22.80 37.67 22.88 0.00 22.88
November 675.83 22.43 15.83 22.46 1.83 22.47
December 743.67 22.28 0.00 22.28 0.00 22.28
             
Annual Sum or Average 5879.17 22.58 1469.17 22.84 37.83 22.85
Minimum of Months 149.67 22.16 0.00 22.16 0.00 22.16
Maximum of Months 743.67 22.99 472.50 23.65 24.83 23.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.68 616.50 20.63 616.50 20.62
February 670.67 20.94 319.33 20.83 319.33 20.78
March 742.17 21.16 108.00 21.07 108.00 21.00
April 704.33 21.38 7.83 21.37 5.50 21.37
May 703.33 21.46 6.50 21.48 0.00 21.48
June 679.83 21.51 5.17 21.53 0.00 21.53
July 650.67 21.44 25.17 21.51 0.00 21.51
August 651.83 21.43 32.17 21.52 0.00 21.52
September 655.00 21.37 20.00 21.43 0.00 21.43
October 732.83 21.25 16.00 21.23 16.00 21.20
November 717.83 20.87 299.67 20.77 299.67 20.71
December 744.00 20.76 527.50 20.67 527.50 20.64
             
Annual Sum or Average 8396.50 21.18 1983.83 21.08 1892.50 21.00
Minimum of Months 650.67 20.68 5.17 20.63 0.00 20.62
Maximum of Months 744.00 21.51 616.50 21.53 616.50 21.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.55 677.00 20.52 677.00 20.52
February 672.00 20.73 436.50 20.65 436.50 20.62
March 744.00 20.95 200.50 20.85 200.50 20.79
April 713.67 21.24 17.67 21.22 17.67 21.21
May 722.50 21.43 1.00 21.44 0.17 21.43
June 696.17 21.50 2.50 21.51 0.00 21.51
July 684.50 21.49 13.00 21.53 0.00 21.53
August 692.50 21.49 12.33 21.52 0.00 21.52
September 695.67 21.38 1.00 21.39 0.00 21.39
October 744.00 21.08 37.67 21.03 37.67 20.98
November 720.00 20.73 381.83 20.64 381.83 20.59
December 744.00 20.60 658.83 20.57 658.83 20.56
             
Annual Sum or Average 8573.00 21.09 2439.83 20.97 2410.17 20.88
Minimum of Months 672.00 20.55 1.00 20.52 0.00 20.52
Maximum of Months 744.00 21.50 677.00 21.53 677.00 21.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.85 313.50 20.76 313.50 20.71
February 672.00 20.94 241.17 20.87 241.17 20.83
March 744.00 21.07 56.50 21.06 56.50 21.05
April 720.00 21.22 0.00 21.22 0.00 21.22
May 744.00 21.34 0.00 21.34 0.00 21.34
June 720.00 21.38 0.00 21.38 0.00 21.38
July 744.00 21.41 0.00 21.41 0.00 21.41
August 744.00 21.39 0.00 21.39 0.00 21.39
September 720.00 21.28 0.00 21.28 0.00 21.28
October 744.00 21.14 0.00 21.14 0.00 21.14
November 720.00 20.98 99.83 20.90 99.83 20.84
December 744.00 20.87 232.17 20.76 232.17 20.69
             
Annual Sum or Average 8760.00 21.16 943.17 21.10 943.17 21.05
Minimum of Months 672.00 20.85 0.00 20.76 0.00 20.69
Maximum of Months 744.00 21.41 313.50 21.41 313.50 21.41



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.66 620.00 20.62 620.00 20.61
February 672.00 20.95 314.17 20.85 314.17 20.80
March 744.00 21.22 87.83 21.14 87.83 21.08
April 703.67 21.46 3.50 21.46 3.50 21.45
May 699.50 21.48 0.00 21.48 0.00 21.48
June 656.50 21.51 0.00 21.51 0.00 21.51
July 639.33 21.43 5.00 21.44 0.00 21.44
August 630.83 21.40 18.17 21.45 0.00 21.45
September 652.67 21.37 8.83 21.39 0.00 21.39
October 737.00 21.30 15.00 21.27 15.00 21.25
November 720.00 20.87 303.67 20.77 303.67 20.71
December 744.00 20.74 538.67 20.67 538.67 20.64
             
Annual Sum or Average 8343.50 21.19 1914.83 21.08 1882.83 21.00
Minimum of Months 630.83 20.66 0.00 20.62 0.00 20.61
Maximum of Months 744.00 21.51 620.00 21.51 620.00 21.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.54 668.17 20.51 668.17 20.50
February 672.00 20.72 438.00 20.65 438.00 20.62
March 744.00 21.02 138.83 20.94 138.83 20.89
April 719.50 21.38 8.50 21.37 8.50 21.37
May 734.83 21.52 0.00 21.52 0.00 21.52
June 688.33 21.57 0.00 21.57 0.00 21.57
July 685.67 21.54 2.83 21.55 0.00 21.55
August 670.33 21.49 4.50 21.50 0.00 21.50
September 695.83 21.42 0.00 21.42 0.00 21.42
October 744.00 21.13 32.00 21.09 32.00 21.04
November 720.00 20.72 386.50 20.63 386.50 20.58
December 744.00 20.58 649.00 20.55 649.00 20.53
             
Annual Sum or Average 8562.50 21.13 2328.33 20.99 2321.00 20.91
Minimum of Months 670.33 20.54 0.00 20.51 0.00 20.50
Maximum of Months 744.00 21.57 668.17 21.57 668.17 21.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.02 11.50 21.02 11.50 21.02
February 672.00 21.09 4.50 21.09 4.50 21.09
March 744.00 21.34 0.00 21.34 0.00 21.34
April 720.00 21.83 0.00 21.83 0.00 21.83
May 744.00 22.39 0.00 22.39 0.00 22.39
June 720.00 22.63 0.00 22.63 0.00 22.63
July 711.33 22.97 0.00 22.97 0.00 22.97
August 629.17 23.04 4.00 23.04 0.00 23.04
September 686.83 22.60 0.00 22.60 0.00 22.60
October 744.00 21.74 0.00 21.74 0.00 21.74
November 720.00 21.11 0.00 21.11 0.00 21.11
December 744.00 21.03 0.00 21.03 0.00 21.03
             
Annual Sum or Average 8579.33 21.88 20.00 21.88 16.00 21.88
Minimum of Months 629.17 21.02 0.00 21.02 0.00 21.02
Maximum of Months 744.00 23.04 11.50 23.04 11.50 23.04



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.59 702.50 20.57 702.50 20.57
February 670.33 20.84 423.50 20.75 423.50 20.71
March 740.67 21.07 249.33 20.96 249.33 20.90
April 699.00 21.31 54.50 21.29 49.33 21.26
May 692.50 21.40 14.67 21.44 1.00 21.44
June 664.67 21.46 12.33 21.49 0.00 21.49
July 630.50 21.37 41.83 21.49 0.00 21.49
August 638.67 21.38 45.67 21.51 0.00 21.51
September 647.33 21.31 28.83 21.39 0.50 21.39
October 730.50 21.17 56.83 21.08 56.83 21.00
November 717.67 20.77 426.83 20.67 425.83 20.63
December 744.00 20.68 647.67 20.63 647.67 20.62
             
Annual Sum or Average 8319.83 21.10 2704.50 21.01 2556.50 20.92
Minimum of Months 630.50 20.59 12.33 20.57 0.00 20.57
Maximum of Months 744.00 21.46 702.50 21.51 702.50 21.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.50 728.83 20.50 728.83 20.49
February 672.00 20.64 516.67 20.59 516.67 20.57
March 744.00 20.85 392.67 20.77 392.67 20.73
April 712.33 21.18 78.67 21.13 78.00 21.09
May 715.00 21.39 5.50 21.40 1.00 21.40
June 686.67 21.47 5.00 21.48 0.00 21.48
July 669.83 21.45 21.00 21.51 0.00 21.51
August 682.50 21.45 20.67 21.50 0.00 21.50
September 689.83 21.32 5.00 21.33 1.50 21.33
October 744.00 20.98 116.50 20.86 116.50 20.77
November 720.00 20.64 493.50 20.56 493.50 20.52
December 744.00 20.53 717.00 20.52 717.00 20.52
             
Annual Sum or Average 8524.17 21.03 3101.00 20.90 3045.67 20.81
Minimum of Months 669.83 20.50 5.00 20.50 0.00 20.49
Maximum of Months 744.00 21.47 728.83 21.51 728.83 21.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 739.67 20.92 426.00 20.81 426.00 20.76
February 651.67 21.12 202.17 21.02 202.17 20.96
March 720.67 21.28 50.83 21.23 47.67 21.19
April 683.83 21.42 8.50 21.43 2.67 21.43
May 687.50 21.43 7.50 21.44 0.50 21.44
June 662.17 21.46 0.00 21.46 0.00 21.46
July 644.17 21.39 12.67 21.43 0.00 21.43
August 645.17 21.39 48.83 21.53 0.00 21.53
September 639.17 21.34 52.33 21.49 0.00 21.49
October 688.50 21.27 16.83 21.31 3.50 21.30
November 706.67 21.04 161.00 20.95 157.00 20.88
December 732.67 20.95 365.33 20.83 365.33 20.77
             
Annual Sum or Average 8201.83 21.25 1352.00 21.20 1204.83 21.13
Minimum of Months 639.17 20.92 0.00 20.81 0.00 20.76
Maximum of Months 739.67 21.46 426.00 21.53 426.00 21.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 386.83 23.11 33.50 23.19 0.00 23.19
February 287.50 23.16 111.33 23.40 0.00 23.40
March 194.83 23.21 160.83 23.59 0.00 23.59
April 68.50 23.17 316.33 23.86 0.00 23.86
May 5.83 23.13 603.00 23.98 0.00 23.98
June 0.00 0.00 667.83 23.97 0.00 23.97
July 1.67 23.99 736.17 23.97 1.67 23.97
August 26.33 23.99 743.67 23.96 26.33 23.96
September 12.83 23.82 655.83 23.95 10.50 23.95
October 111.67 23.09 390.00 23.81 0.00 23.81
November 253.50 23.10 195.67 23.49 1.83 23.49
December 342.83 23.06 38.00 23.17 0.00 23.17
             
Annual Sum or Average 1692.33 23.14 4652.17 23.76 40.33 23.76
Minimum of Months 0.00 0.00 33.50 23.17 0.00 23.17
Maximum of Months 386.83 23.99 743.67 23.98 26.33 23.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 232.33 23.18 160.83 23.55 0.00 23.55
February 156.67 23.25 218.83 23.69 0.00 23.69
March 56.50 23.28 364.33 23.93 0.00 23.93
April 2.50 23.23 527.83 24.00 0.00 24.00
May 0.00 0.00 713.17 24.00 0.00 24.00
June 0.00 0.00 717.83 23.98 0.00 23.98
July 0.00 0.00 743.67 23.99 0.00 23.99
August 18.50 23.99 744.00 23.99 18.50 23.99
September 5.17 24.00 712.17 23.96 5.17 23.96
October 7.33 23.14 558.50 23.99 0.00 23.99
November 105.50 23.15 341.83 23.81 1.17 23.81
December 189.17 23.13 172.67 23.57 0.00 23.57
             
Annual Sum or Average 773.67 23.21 5975.67 23.91 24.83 23.91
Minimum of Months 0.00 0.00 160.83 23.55 0.00 23.55
Maximum of Months 232.33 24.00 744.00 24.00 18.50 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 508.67 24.09 666.17 24.05 492.00 24.08
February 465.17 24.06 612.50 24.01 452.17 24.04
March 522.50 24.18 719.50 24.08 522.33 24.11
April 517.17 24.12 713.00 24.02 517.17 24.05
May 542.50 24.06 740.83 23.99 542.50 24.01
June 532.00 24.01 719.33 23.95 532.00 23.97
July 557.67 23.99 744.00 23.95 557.67 23.97
August 564.67 23.99 744.00 23.97 564.67 23.97
September 530.17 24.01 719.50 23.96 530.17 23.97
October 535.00 24.11 740.17 24.01 535.00 24.04
November 503.33 24.15 686.17 24.05 503.33 24.08
December 501.50 24.20 672.50 24.11 499.67 24.14
             
Annual Sum or Average 6280.33 24.08 8477.67 24.01 6248.67 24.03
Minimum of Months 465.17 23.99 612.50 23.95 452.17 23.97
Maximum of Months 564.67 24.20 744.00 24.11 564.67 24.14



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.01 18.33 21.01 18.33 21.01
February 672.00 21.11 18.17 21.11 18.17 21.11
March 744.00 21.33 0.00 21.33 0.00 21.33
April 712.33 21.76 0.00 21.76 0.00 21.76
May 719.17 22.27 0.00 22.27 0.00 22.27
June 673.00 22.60 2.00 22.61 0.00 22.61
July 540.67 22.82 66.83 22.94 0.00 22.94
August 517.50 22.79 119.17 23.00 0.00 23.00
September 630.17 22.34 29.50 22.41 0.00 22.41
October 744.00 21.61 0.00 21.61 0.00 21.61
November 720.00 21.12 0.00 21.12 0.00 21.12
December 744.00 21.04 0.00 21.04 0.00 21.04
             
Annual Sum or Average 8160.83 21.76 254.00 21.81 36.50 21.81
Minimum of Months 517.50 21.01 0.00 21.01 0.00 21.01
Maximum of Months 744.00 22.82 119.17 23.00 18.33 23.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.50438 32.90716 0.16403 5.67808
February 672.00000 23.33554 34.33200 0.12975 5.51133
March 744.00000 23.19678 35.06948 0.09846 5.36711
April 720.00000 23.05683 38.80920 0.08763 5.32747
May 744.00000 23.10950 42.79239 -0.8717 21.26380
June 720.00000 23.21929 45.07495 -0.8132 19.19960
July 744.00000 23.42172 48.66384 -0.7137 15.94791
August 744.00000 23.55559 52.30749 -0.6383 13.72903
September 720.00000 23.71269 48.84834 -0.6018 12.77804
October 744.00000 23.78709 40.34666 0.29668 6.91360
November 720.00000 23.81721 38.21870 0.28910 6.82409
December 744.00000 23.69440 33.98267 0.22394 6.12973
           
Annual Sum or Average 8760.00000 23.45186 40.98080 -0.1977 10.42219
Minimum of Months 672.00000 23.05683 32.90716 -0.8717 5.32747
Maximum of Months 744.00000 23.81721 52.30749 0.29668 21.26380



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.05929 35.25952 -0.4705 9.95670
February 672.00000 21.20417 36.29156 -0.3723 8.90312
March 744.00000 21.30537 36.72374 -0.3003 7.95072
April 720.00000 21.42984 40.32015 -0.2068 7.19478
May 744.00000 21.50630 44.67185 -1.2434 39.17790
June 720.00000 21.52334 47.51949 -1.1962 36.41641
July 744.00000 21.87928 50.98477 -1.0180 29.43590
August 744.00000 22.00779 55.08378 -0.9401 27.03871
September 720.00000 21.77818 52.48800 -1.0681 32.86822
October 744.00000 21.43314 44.13382 -0.1940 7.21040
November 720.00000 21.11259 42.31776 -0.3683 8.51135
December 744.00000 21.11757 36.92985 -0.4367 9.57915
           
Annual Sum or Average 8760.00000 21.44824 43.59708 -0.6529 18.73930
Minimum of Months 672.00000 21.05929 35.25952 -1.2434 7.19478
Maximum of Months 744.00000 22.00779 55.08378 -0.1940 39.17790



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.67953 36.74481 -0.2480 6.60517
February 672.00000 21.96384 37.40432 -0.1661 6.09740
March 744.00000 22.36755 37.32862 -0.0606 5.45897
April 720.00000 22.66037 40.34638 0.03821 5.51214
May 744.00000 22.91914 44.02035 -0.8688 21.60502
June 720.00000 23.02856 46.34793 -0.8091 19.46705
July 744.00000 23.30717 49.72380 -0.6794 15.30218
August 744.00000 23.34754 53.68527 -0.6371 14.14685
September 720.00000 23.12261 51.32663 -0.7408 17.40045
October 744.00000 22.65252 43.91814 0.05758 5.47387
November 720.00000 22.04209 42.84186 -0.1127 5.74870
December 744.00000 21.81068 38.26591 -0.2055 6.22076
           
Annual Sum or Average 8760.00000 22.57864 43.52739 -0.3706 10.77746
Minimum of Months 672.00000 21.67953 36.74481 -0.8688 5.45897
Maximum of Months 744.00000 23.34754 53.68527 0.05758 21.60502



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.06016 29.98946 0.63297 16.34601
February 672.00000 23.06211 31.08438 0.65574 16.85854
March 744.00000 23.12123 31.48785 0.69268 17.86355
April 720.00000 23.13176 34.92841 0.73615 18.98244
May 744.00000 23.12860 38.98789 0.06138 10.02679
June 720.00000 23.08343 41.68086 0.08689 10.13126
July 744.00000 23.11485 45.78191 0.13589 10.13170
August 744.00000 23.11699 49.90131 0.17213 10.39022
September 720.00000 23.11441 46.84751 0.12098 10.11472
October 744.00000 23.14434 38.23392 0.75464 19.44506
November 720.00000 23.11830 36.20196 0.70960 18.49174
December 744.00000 23.09603 31.50405 0.65449 17.03951
           
Annual Sum or Average 8760.00000 23.10801 38.08932 0.44986 14.63609
Minimum of Months 672.00000 23.06016 29.98946 0.06138 10.02679
Maximum of Months 744.00000 23.14434 49.90131 0.75464 19.44506



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.42697 39.47110 -0.2816 7.21027
February 672.00000 21.75429 40.11045 -0.1498 6.73423
March 744.00000 22.07390 40.24100 -0.0384 6.17908
April 720.00000 22.32763 43.40938 0.07527 6.22641
May 744.00000 22.47077 47.40637 -0.8481 21.93031
June 720.00000 22.55960 49.88825 -0.7822 19.11946
July 744.00000 22.88102 53.30986 -0.6199 14.64906
August 744.00000 22.97033 57.23965 -0.5500 13.52590
September 720.00000 22.74352 54.72200 -0.6714 17.69446
October 744.00000 22.32614 46.96254 0.08929 6.51125
November 720.00000 21.66302 45.94671 -0.1478 6.41886
December 744.00000 21.54400 41.05117 -0.2366 6.97260
           
Annual Sum or Average 8760.00000 22.23129 46.68004 -0.3480 11.11964
Minimum of Months 672.00000 21.42697 39.47110 -0.8481 6.17908
Maximum of Months 744.00000 22.97033 57.23965 0.08929 21.93031



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.15673 38.83584 -0.1077 5.78875
February 672.00000 22.46441 39.44561 -0.0148 5.69852
March 744.00000 22.83379 39.43933 0.08792 5.66380
April 720.00000 23.07031 42.49654 0.17789 6.12613
May 744.00000 23.24826 46.18883 -0.7022 16.04375
June 720.00000 23.33654 48.51043 -0.6452 14.37083
July 744.00000 23.52133 51.98781 -0.5432 11.64767
August 744.00000 23.56126 55.78506 -0.4983 10.68219
September 720.00000 23.42763 53.34732 -0.5770 12.81978
October 744.00000 23.08891 45.87016 0.20365 6.36578
November 720.00000 22.50493 44.81313 0.02980 5.72975
December 744.00000 22.27944 40.34047 -0.0657 5.67941
           
Annual Sum or Average 8760.00000 22.96046 45.62020 -0.2226 8.90127
Minimum of Months 672.00000 22.15673 38.83584 -0.7022 5.66380
Maximum of Months 744.00000 23.56126 55.78506 0.20365 16.04375



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.67676 40.04326 -0.6214 13.50922
February 672.00000 20.94283 40.91623 -0.5130 11.25848
March 744.00000 21.16163 41.78989 -0.4089 9.09073
April 720.00000 21.41804 45.15864 -0.2701 7.38892
May 744.00000 21.56245 48.98587 -1.2909 41.08050
June 720.00000 21.61489 51.35774 -1.2306 38.00665
July 744.00000 21.67155 52.63407 -1.1418 34.13211
August 744.00000 21.65992 55.28294 -1.1378 33.92253
September 720.00000 21.54444 55.71464 -1.2354 38.44690
October 744.00000 21.28440 49.94061 -0.3013 7.61518
November 720.00000 20.87401 47.74756 -0.4925 10.69588
December 744.00000 20.75602 41.83357 -0.5855 12.74119
           
Annual Sum or Average 8760.00000 21.26547 47.64611 -0.7708 21.55130
Minimum of Months 672.00000 20.67676 40.04326 -1.2909 7.38892
Maximum of Months 744.00000 21.67155 55.71464 -0.2701 41.08050



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.55088 40.31640 -0.6650 14.75992
February 672.00000 20.72843 41.36422 -0.5865 12.80714
March 744.00000 20.95081 42.22009 -0.4827 10.18108
April 720.00000 21.26138 45.58034 -0.3289 7.85392
May 744.00000 21.48808 49.23795 -1.3378 43.12689
June 720.00000 21.56112 51.55369 -1.2651 39.43636
July 744.00000 21.63779 53.02526 -1.1744 35.35912
August 744.00000 21.61455 56.02120 -1.1804 35.55379
September 720.00000 21.44826 56.76854 -1.3049 41.38301
October 744.00000 21.08296 50.47527 -0.3766 8.31448
November 720.00000 20.73045 48.15595 -0.5414 11.66308
December 744.00000 20.59730 42.19158 -0.6390 14.00354
           
Annual Sum or Average 8760.00000 21.13980 48.10431 -0.8251 22.92864
Minimum of Months 672.00000 20.55088 40.31640 -1.3378 7.85392
Maximum of Months 744.00000 21.63779 56.76854 -0.3289 43.12689



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.85192 38.56990 -0.5397 11.30779
February 672.00000 20.93879 39.75822 -0.4994 10.50181
March 744.00000 21.07367 40.63970 -0.4366 9.06840
April 720.00000 21.22274 44.23023 -0.3549 7.77372
May 744.00000 21.33660 48.14375 -1.4527 48.43294
June 720.00000 21.38142 50.26564 -1.4043 45.86725
July 744.00000 21.41337 52.64959 -1.3671 43.96238
August 744.00000 21.39214 55.68805 -1.3608 43.61079
September 720.00000 21.28383 55.60527 -1.4320 47.30904
October 744.00000 21.13696 48.87595 -0.3605 7.75964
November 720.00000 20.98035 46.29307 -0.4416 9.28729
December 744.00000 20.86980 40.50339 -0.5227 10.88553
           
Annual Sum or Average 8760.00000 21.15793 46.80065 -0.8499 24.73157
Minimum of Months 672.00000 20.85192 38.56990 -1.4527 7.75964
Maximum of Months 744.00000 21.41337 55.68805 -0.3549 48.43294



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.66314 40.06443 -0.6245 13.56960
February 672.00000 20.94810 40.90101 -0.5122 11.14377
March 744.00000 21.21969 41.68128 -0.3943 8.87264
April 720.00000 21.50666 44.96972 -0.2452 7.22833
May 744.00000 21.58649 48.90964 -1.2968 41.39657
June 720.00000 21.66751 50.95292 -1.2035 36.88772
July 744.00000 21.69221 52.70519 -1.1562 34.82377
August 744.00000 21.69075 54.94823 -1.1298 33.64465
September 720.00000 21.54900 55.79500 -1.2461 39.00304
October 744.00000 21.32035 49.81756 -0.2937 7.59632
November 720.00000 20.86709 47.75728 -0.4934 10.68910
December 744.00000 20.73873 41.86666 -0.5892 12.76825
           
Annual Sum or Average 8760.00000 21.28906 47.55961 -0.7671 21.53177
Minimum of Months 672.00000 20.66314 40.06443 -1.2968 7.22833
Maximum of Months 744.00000 21.69221 55.79500 -0.2452 41.39657



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.54431 40.32897 -0.6674 14.85889
February 672.00000 20.72171 41.36423 -0.5882 12.78429
March 744.00000 21.01526 42.07585 -0.4671 9.79017
April 720.00000 21.38164 45.26670 -0.2978 7.51570
May 744.00000 21.53821 49.08563 -1.3367 43.10390
June 720.00000 21.64804 51.08467 -1.2280 37.86062
July 744.00000 21.68092 53.01226 -1.1828 35.81968
August 744.00000 21.67120 55.53313 -1.1651 34.97043
September 720.00000 21.47950 56.57231 -1.3098 41.72112
October 744.00000 21.13207 50.31238 -0.3665 8.17947
November 720.00000 20.72175 48.18712 -0.5427 11.70427
December 744.00000 20.58055 42.22760 -0.6428 14.12563
           
Annual Sum or Average 8760.00000 21.17856 47.94897 -0.8178 22.76248
Minimum of Months 672.00000 20.54431 40.32897 -1.3367 7.51570
Maximum of Months 744.00000 21.68092 56.57231 -0.2978 43.10390



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.59082 40.62667 -0.6791 15.16650
February 672.00000 20.84928 41.56446 -0.5666 12.61146
March 744.00000 21.07866 42.39432 -0.4537 10.06000
April 720.00000 21.36866 45.67905 -0.2997 7.93952
May 744.00000 21.53420 49.53458 -1.3179 42.69016
June 720.00000 21.59754 52.07209 -1.2442 38.91583
July 744.00000 21.65770 53.50932 -1.1463 34.63219
August 744.00000 21.63964 56.45503 -1.1478 34.64146
September 720.00000 21.50509 56.96602 -1.2632 40.07255
October 744.00000 21.20609 50.68699 -0.3437 8.33397
November 720.00000 20.77636 48.59200 -0.5446 11.98573
December 744.00000 20.67856 42.42431 -0.6406 14.22547
           
Annual Sum or Average 8760.00000 21.20867 48.40451 -0.8055 22.66513
Minimum of Months 672.00000 20.59082 40.62667 -1.3179 7.93952
Maximum of Months 744.00000 21.65770 56.96602 -0.2997 42.69016



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.50146 40.83410 -0.7171 16.34722
February 672.00000 20.64344 42.01909 -0.6405 14.31159
March 744.00000 20.85488 42.86209 -0.5328 11.36648
April 720.00000 21.20466 46.12791 -0.3628 8.50162
May 744.00000 21.46183 49.79701 -1.3666 44.80399
June 720.00000 21.55228 52.25346 -1.2778 40.29368
July 744.00000 21.63114 53.91037 -1.1780 35.79804
August 744.00000 21.59635 57.23258 -1.1917 36.30128
September 720.00000 21.40681 58.06270 -1.3382 43.25426
October 744.00000 20.98230 51.29363 -0.4272 9.26399
November 720.00000 20.64039 48.99924 -0.5935 13.02964
December 744.00000 20.53274 42.76691 -0.6931 15.58510
           
Annual Sum or Average 8760.00000 21.08636 48.87515 -0.8614 24.12753
Minimum of Months 672.00000 20.50146 40.83410 -1.3666 8.50162
Maximum of Months 744.00000 21.63114 58.06270 -0.3628 44.80399



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.93138 40.97912 -0.5347 11.73444
February 672.00000 21.18980 41.72275 -0.4172 9.84291
March 744.00000 21.34234 42.90052 -0.3348 8.37273
April 720.00000 21.51650 46.03994 -0.2368 7.30657
May 744.00000 21.56994 49.72830 -1.3152 42.48372
June 720.00000 21.61380 51.68857 -1.2626 39.74236
July 744.00000 21.65180 53.16456 -1.1992 36.95154
August 744.00000 21.64543 55.43837 -1.1735 35.77750
September 720.00000 21.56235 55.68697 -1.2337 38.80042
October 744.00000 21.42797 50.50864 -0.2377 7.27986
November 720.00000 21.08661 48.35222 -0.4153 9.49422
December 744.00000 20.98672 42.84468 -0.4989 11.27470
           
Annual Sum or Average 8760.00000 21.37785 48.28427 -0.7404 21.66032
Minimum of Months 672.00000 20.93138 40.97912 -1.3152 7.27986
Maximum of Months 744.00000 21.65180 55.68697 -0.2368 42.48372



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.53380 38.75285 0.24180 6.69629
February 672.00000 23.61248 39.49443 0.27975 7.11329
March 744.00000 23.76483 39.38451 0.34029 7.68817
April 720.00000 23.85853 42.21749 0.40943 8.69431
May 744.00000 23.92834 45.57155 -0.3924 8.38417
June 720.00000 23.94495 47.79626 -0.3429 7.56448
July 744.00000 23.96835 51.44968 -0.2893 6.86028
August 744.00000 23.95805 55.40208 -0.2688 6.59738
September 720.00000 23.90735 53.05698 -0.3454 7.67817
October 744.00000 23.79547 45.63672 0.40499 8.63174
November 720.00000 23.65242 44.29306 0.33189 7.71707
December 744.00000 23.56431 40.18649 0.26115 6.84496
           
Annual Sum or Average 8760.00000 23.79166 45.30043 0.05110 7.53859
Minimum of Months 672.00000 23.53380 38.75285 -0.3924 6.59738
Maximum of Months 744.00000 23.96835 55.40208 0.40943 8.69431



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.73023 37.57585 0.32974 7.57078
February 672.00000 23.78769 38.36015 0.36188 8.05186
March 744.00000 23.89296 38.32727 0.41008 8.67818
April 720.00000 23.94801 41.27332 0.46780 9.69797
May 744.00000 23.98231 44.77868 -0.3241 7.30187
June 720.00000 23.98077 47.09250 -0.2840 6.75470
July 744.00000 23.98874 50.83874 -0.2391 6.29256
August 744.00000 23.98488 54.77516 -0.2170 6.04998
September 720.00000 23.95943 52.26752 -0.2805 6.75647
October 744.00000 23.90790 44.62746 0.46905 9.71523
November 720.00000 23.81499 43.12364 0.41110 8.79893
December 744.00000 23.75621 38.99224 0.34791 7.78795
           
Annual Sum or Average 8760.00000 23.89504 44.36759 0.11956 7.78353
Minimum of Months 672.00000 23.73023 37.57585 -0.3241 6.04998
Maximum of Months 744.00000 23.98874 54.77516 0.46905 9.71523



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.86517 36.33681 0.97611 27.56151
February 672.00000 23.85252 37.18631 1.00381 28.74255
March 744.00000 23.95632 37.48223 1.06305 31.00059
April 720.00000 23.94218 40.54981 1.12092 33.52189
May 744.00000 23.92495 44.16362 0.59608 17.27504
June 720.00000 23.90833 46.29391 0.64552 18.19701
July 744.00000 23.92920 50.02587 0.69816 19.59510
August 744.00000 23.94335 53.77119 0.73194 20.40868
September 720.00000 23.91930 51.16763 0.65159 18.20432
October 744.00000 23.93084 43.73243 1.11675 33.14452
November 720.00000 23.91308 42.03418 1.05790 30.82536
December 744.00000 23.90812 37.81780 1.00101 28.58719
           
Annual Sum or Average 8760.00000 23.91658 43.41318 0.88784 25.56712
Minimum of Months 672.00000 23.85252 36.33681 0.59608 17.27504
Maximum of Months 744.00000 23.95632 53.77119 1.12092 33.52189



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.01715 34.68750 -0.4573 9.40844
February 672.00000 21.09459 35.82113 -0.4215 8.87313
March 744.00000 21.29761 36.10005 -0.3564 7.77452
April 720.00000 21.70348 39.06521 -0.2371 6.47754
May 744.00000 22.19610 42.42130 -1.1777 34.43049
June 720.00000 22.51049 44.43359 -1.0546 28.72266
July 744.00000 22.88571 47.72565 -0.9017 22.45172
August 744.00000 22.98818 51.66035 -0.8410 20.24122
September 720.00000 22.49747 49.93747 -1.0243 27.54470
October 744.00000 21.77853 42.78736 -0.1961 6.00416
November 720.00000 21.20104 41.52214 -0.3553 7.88653
December 744.00000 21.02766 36.45997 -0.4397 9.06017
           
Annual Sum or Average 8760.00000 21.85464 41.91466 -0.6230 15.77502
Minimum of Months 672.00000 21.01715 34.68750 -1.1777 6.00416
Maximum of Months 744.00000 22.98818 51.66035 -0.1961 34.43049



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.01574 38.03027 -0.4516 9.28718
February 672.00000 21.09344 39.16049 -0.4153 8.71071
March 744.00000 21.34469 39.36030 -0.3425 7.53982
April 720.00000 21.82705 42.11683 -0.2034 6.17468
May 744.00000 22.38561 45.31679 -1.1154 31.46631
June 720.00000 22.63067 47.42929 -1.0144 26.96644
July 744.00000 22.99731 50.69926 -0.8629 21.06479
August 744.00000 23.13795 54.51713 -0.7884 18.46812
September 720.00000 22.64438 52.78697 -0.9749 25.69792
October 744.00000 21.74286 46.13738 -0.2010 6.17564
November 720.00000 21.10785 45.01070 -0.3773 8.11119
December 744.00000 21.03487 39.76966 -0.4348 8.96817
           
Annual Sum or Average 8760.00000 21.91875 45.05633 -0.5995 14.91638
Minimum of Months 672.00000 21.01574 38.03027 -1.1154 6.17468
Maximum of Months 744.00000 23.13795 54.51713 -0.2010 31.46631



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.01446 35.84631 -0.4473 9.21581
February 672.00000 21.11194 36.89841 -0.4010 8.54531
March 744.00000 21.32503 37.13436 -0.3278 7.42401
April 720.00000 21.78310 39.93140 -0.1874 6.25988
May 744.00000 22.31090 43.12268 -1.0897 30.77756
June 720.00000 22.67184 44.96040 -0.9452 24.52535
July 744.00000 23.05951 48.12502 -0.7830 18.75023
August 744.00000 23.08124 52.24966 -0.7480 17.66343
September 720.00000 22.51134 50.77899 -0.9673 25.90461
October 744.00000 21.60516 44.14255 -0.2099 6.27156
November 720.00000 21.11888 42.74823 -0.3605 7.93600
December 744.00000 21.03655 37.57523 -0.4287 8.87342
           
Annual Sum or Average 8760.00000 21.89071 42.82136 -0.5756 14.37343
Minimum of Months 672.00000 21.01446 35.84631 -1.0897 6.25988
Maximum of Months 744.00000 23.08124 52.24966 -0.1874 30.77756



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.10589 34.02409 -0.4232 8.82805
February 672.00000 21.23532 35.01123 -0.3787 8.24781
March 744.00000 21.56332 35.02639 -0.2899 6.93554
April 720.00000 21.96383 37.94520 -0.1716 5.95620
May 744.00000 22.44718 41.24286 -1.0853 30.21960
June 720.00000 22.74800 43.23739 -0.9654 25.05599
July 744.00000 23.11099 46.51530 -0.8154 19.40028
August 744.00000 23.20401 50.40730 -0.7574 17.46716
September 720.00000 22.73845 48.65321 -0.9343 23.91349
October 744.00000 22.05030 41.55084 -0.1282 5.57416
November 720.00000 21.39968 40.51303 -0.3007 7.23095
December 744.00000 21.14091 35.74797 -0.4012 8.42467
           
Annual Sum or Average 8760.00000 22.06408 40.85133 -0.5553 13.96704
Minimum of Months 672.00000 21.10589 34.02409 -1.0853 5.57416
Maximum of Months 744.00000 23.20401 50.40730 -0.1282 30.21960



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.123787E+10 12841.72 17-JAN-19:04 234.35 0.394424E+10 0.00 0.518211E+10 1.00 3.19 01-JAN-05:40 0.00 0.00
February 0.389249E+10 54909.44 27-FEB-16:02 298.15 0.121305E+11 0.00 0.160230E+11 1.41 3.24 27-FEB-16:02 0.00 0.00
March 0.807595E+10 64043.30 18-MAR-15:02 458.31 0.253348E+11 0.00 0.334108E+11 1.96 3.57 18-MAR-18:01 0.00 0.00
April 0.235895E+11 108438.62 27-APR-15:03 565.95 0.746966E+11 0.00 0.982861E+11 2.49 3.84 26-APR-18:02 0.00 0.00
May 0.409289E+11 96349.39 05-MAY-18:02 684.31 0.130480E+12 0.00 0.171409E+12 2.91 3.94 15-MAY-18:03 0.00 0.00
June 0.621002E+11 109522.67 28-JUN-18:03 703.52 0.195900E+12 0.00 0.258000E+12 3.06 4.06 17-JUN-18:02 0.00 0.00
July 0.951961E+11 132736.77 24-JUL-18:03 738.37 0.309052E+12 0.00 0.404248E+12 3.13 4.08 15-JUL-18:03 0.00 0.00
August 0.113050E+12 150424.66 10-AUG-18:03 737.89 0.368524E+12 0.00 0.481574E+12 3.14 4.15 26-AUG-18:02 0.00 0.00
September 0.542762E+11 105544.80 14-SEP-15:03 675.18 0.176132E+12 0.00 0.230408E+12 2.97 4.08 23-SEP-18:02 0.00 0.00
October 0.170713E+11 86220.95 04-OCT-15:02 512.36 0.529883E+11 0.00 0.700596E+11 2.17 3.95 04-OCT-15:02 0.00 0.00
November 0.423611E+10 69154.08 04-NOV-15:02 306.52 0.132698E+11 0.00 0.175059E+11 1.35 3.65 04-NOV-15:02 0.00 0.00
December 0.197046E+10 15506.38 19-DEC-19:03 283.22 0.627874E+10 0.00 0.824919E+10 1.21 3.19 01-DEC-00:03 0.00 0.00
                         
Annual Sum or Average 0.425625E+12     6198.14 0.136873E+13 0.00 0.179436E+13 2.24     0.00 0.00
Minimum of Months 0.123787E+10 12841.72   234.35 0.394424E+10 0.00 0.518211E+10 1.00 3.19   0.00 0.00
Maximum of Months 0.113050E+12 150424.66   738.37 0.368524E+12 0.00 0.481574E+12 3.14 4.15   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.950203E+11 0.00 744.00 219323.84 12-JAN-09:01 0.00 52.29 80.33 0.31 0.00 0.09 0.56 12-JAN-09:01
February 0.638863E+11 0.00 660.03 155691.01 20-FEB-19:15 0.00 51.48 79.60 0.23 0.00 0.07 0.40 20-FEB-19:15
March 0.488672E+11 0.00 717.95 220140.61 03-MAR-09:02 0.00 49.88 78.73 0.15 0.00 0.05 0.56 03-MAR-09:02
April 0.342318E+11 0.00 560.97 128779.20 17-APR-07:50 0.00 42.28 69.80 0.10 0.00 0.03 0.33 17-APR-07:50
May 0.269895E+11 0.00 444.16 173204.07 18-MAY-08:62 0.00 37.91 61.49 0.07 0.00 0.03 0.44 18-MAY-08:62
June 0.919490E+10 0.00 310.46 107998.78 15-JUN-03:03 0.00 32.93 51.94 0.02 0.00 0.01 0.28 15-JUN-03:03
July 0.252943E+10 0.00 185.61 44791.88 13-JUL-08:05 0.00 37.22 47.97 0.01 0.00 0.00 0.11 13-JUL-08:05
August 0.237103E+10 0.00 161.58 44140.32 21-AUG-08:05 0.00 36.02 45.53 0.00 0.00 0.00 0.11 21-AUG-08:05
September 0.101352E+11 0.00 362.04 115435.05 27-SEP-04:53 0.00 39.43 58.95 0.03 0.00 0.01 0.29 27-SEP-04:53
October 0.412105E+11 0.00 627.97 158106.80 16-OCT-08:62 0.00 47.83 73.99 0.12 0.00 0.04 0.40 16-OCT-08:62
November 0.653994E+11 0.00 703.34 194358.47 24-NOV-16:01 0.00 51.17 79.13 0.21 0.00 0.06 0.50 24-NOV-16:01
December 0.907476E+11 0.00 742.85 221560.93 07-DEC-19:03 0.00 51.93 80.12 0.29 0.00 0.09 0.57 07-DEC-19:03
                           
Annual Sum or Average 0.490583E+12 0.00 6220.97     0.00 44.17 67.22 0.13 0.00 0.04    
Minimum of Months 0.237103E+10 0.00 161.58 44140.32   0.00 32.93 45.53 0.00 0.00 0.00 0.11  
Maximum of Months 0.950203E+11 0.00 744.00 221560.93   0.00 52.29 80.33 0.31 0.00 0.09 0.57  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.305234E+09 0.00 179.14 0.305234E+09 0.00 0.00 0.00 0.00 40263.44 04-JAN-21:14 40263.44 04-JAN-21:14 0.00 0.00 0.00
February 0.205599E+10 0.00 144.16 0.205599E+10 0.00 0.00 0.00 0.00 79742.69 27-FEB-15:00 79742.69 27-FEB-15:00 0.00 0.00 0.00
March 0.420411E+10 0.00 169.48 0.420411E+10 0.00 0.00 0.00 0.00 102908.53 18-MAR-16:10 102908.53 18-MAR-16:10 0.00 0.00 0.00
April 0.286744E+11 0.00 217.32 0.286744E+11 0.00 0.00 0.00 0.00 205582.09 27-APR-18:10 205582.09 27-APR-18:10 0.00 0.00 0.00
May 0.552908E+11 0.00 314.17 0.548583E+11 0.00 0.00 0.00 0.00 205273.59 05-MAY-18:00 177065.19 04-MAY-18:03 0.00 0.00 0.00
June 0.985683E+11 0.00 436.29 0.984298E+11 0.00 0.00 0.00 0.00 221214.23 28-JUN-18:10 210065.17 28-JUN-18:10 0.00 0.00 0.00
July 0.167844E+12 0.00 556.76 0.162029E+12 0.00 0.00 0.00 0.00 271313.52 27-JUL-18:40 237611.13 24-JUL-18:20 0.00 0.00 0.00
August 0.212712E+12 0.00 605.01 0.203226E+12 0.00 0.00 0.00 0.00 298764.55 10-AUG-18:07 253018.07 10-AUG-18:07 0.00 0.00 0.00
September 0.808736E+11 0.00 383.75 0.786906E+11 0.00 0.00 0.00 0.00 206178.88 14-SEP-17:15 181446.27 14-SEP-17:15 0.00 0.00 0.00
October 0.149364E+11 0.00 190.78 0.149215E+11 0.00 0.00 0.00 0.00 126558.28 04-OCT-15:03 126558.28 04-OCT-15:03 0.00 0.00 0.00
November 0.365309E+10 0.00 158.27 0.365309E+10 0.00 0.00 0.00 0.00 103185.90 04-NOV-14:20 103185.90 04-NOV-14:20 0.00 0.00 0.00
December 0.377485E+09 0.00 200.14 0.377485E+09 0.00 0.00 0.00 0.00 34606.16 12-DEC-22:37 34606.16 12-DEC-22:37 0.00 0.00 0.00
                               
Annual Sum or Average 0.669495E+12 0.00 3555.27 0.651425E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.305234E+09 0.00 144.16 0.305234E+09 0.00 0.00 0.00 0.00 34606.16   34606.16   0.00 0.00 0.00
Maximum of Months 0.212712E+12 0.00 605.01 0.203226E+12 0.00 0.00 0.00 0.00 298764.55   253018.07   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 0.332455E+09 0.00 10.50 0.332455E+09 0.00 0.00 0.00 0.00 18783.31 27-FEB-15:00 18783.31 27-FEB-15:00 0.00 0.00 0.00
March 0.656272E+09 0.00 31.22 0.656272E+09 0.00 0.00 0.00 0.00 20929.09 18-MAR-16:00 20929.09 18-MAR-16:00 0.00 0.00 0.00
April 0.473027E+10 0.00 108.42 0.473027E+10 0.00 0.00 0.00 0.00 29946.00 27-APR-15:02 29946.00 27-APR-15:02 0.00 0.00 0.00
May 0.970367E+10 0.00 217.97 0.924311E+10 0.00 0.00 0.00 0.00 36235.69 05-MAY-18:02 28414.14 05-MAY-15:02 0.00 0.00 0.00
June 0.167744E+11 0.00 379.13 0.167571E+11 0.00 0.00 0.00 0.00 29532.74 28-JUN-15:02 29532.74 28-JUN-15:02 0.00 0.00 0.00
July 0.301164E+11 0.00 540.17 0.278837E+11 0.00 0.00 0.00 0.00 39786.10 15-JUL-18:00 32735.79 24-JUL-15:00 0.00 0.00 0.00
August 0.384432E+11 0.00 594.67 0.348388E+11 0.00 0.00 0.00 0.00 40345.78 30-AUG-12:40 32850.62 10-AUG-18:02 0.00 0.00 0.00
September 0.144140E+11 0.00 332.04 0.132626E+11 0.00 0.00 0.00 0.00 38717.43 23-SEP-13:30 28194.70 12-SEP-15:02 0.00 0.00 0.00
October 0.254416E+10 0.00 106.42 0.253791E+10 0.00 0.00 0.00 0.00 24147.99 04-OCT-15:00 24147.99 04-OCT-15:00 0.00 0.00 0.00
November 0.658452E+09 0.00 21.53 0.579607E+09 0.00 0.00 0.00 0.00 28029.94 04-NOV-13:50 22855.52 04-NOV-14:20 0.00 0.00 0.00
December 7193.64 0.00 0.06 7193.64 0.00 0.00 0.00 0.00 35.97 05-DEC-11:57 35.97 05-DEC-11:57 0.00 0.00 0.00
                               
Annual Sum or Average 0.118373E+12 0.00 2342.12 0.110822E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.384432E+11 0.00 594.67 0.348388E+11 0.00 0.00 0.00 0.00 40345.78   32850.62   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 9090484.77 0.00 2.22 8412275.13 0.00 0.00 0.00 0.00 9196.44 20-JAN-16:02 9196.44 20-JAN-16:02 0.00 0.00 0.00
February 0.184356E+09 0.00 40.49 0.151650E+09 0.00 0.00 0.00 0.00 14246.83 06-FEB-16:02 14246.83 06-FEB-16:02 0.00 0.00 0.00
March 0.706842E+09 0.00 116.32 0.682674E+09 0.00 0.00 0.00 0.00 14850.72 18-MAR-15:02 14850.72 18-MAR-15:02 0.00 0.00 0.00
April 0.210869E+10 0.00 304.50 0.167351E+10 0.00 0.00 0.00 0.00 15584.30 01-APR-18:02 15584.30 01-APR-18:02 0.00 0.00 0.00
May 0.393075E+10 0.00 490.67 0.281115E+10 0.00 0.00 0.00 0.00 15297.92 14-MAY-15:02 15297.92 14-MAY-15:02 0.00 0.00 0.00
June 0.461639E+10 0.00 572.45 0.292829E+10 0.00 0.00 0.00 0.00 15148.59 12-JUN-15:01 14844.45 08-JUN-15:02 0.00 0.00 0.00
July 0.752916E+10 0.00 666.21 0.482540E+10 0.00 0.00 0.00 0.00 15301.64 16-JUL-15:01 14695.40 25-JUL-18:02 0.00 0.00 0.00
August 0.737773E+10 0.00 655.54 0.459268E+10 0.00 0.00 0.00 0.00 15313.72 28-AUG-15:02 15083.45 10-AUG-18:02 0.00 0.00 0.00
September 0.469678E+10 0.00 537.37 0.283501E+10 0.00 0.00 0.00 0.00 14676.51 22-SEP-18:02 14656.85 15-SEP-18:02 0.00 0.00 0.00
October 0.133658E+10 0.00 241.80 0.954022E+09 0.00 0.00 0.00 0.00 15070.28 04-OCT-15:02 15070.28 04-OCT-15:02 0.00 0.00 0.00
November 0.136637E+09 0.00 32.17 71965650.56 0.00 0.00 0.00 0.00 14006.37 11-NOV-16:02 14006.37 11-NOV-16:02 0.00 0.00 0.00
December 18616092.82 0.00 5.81 17696927.63 0.00 0.00 0.00 0.00 13563.44 05-DEC-16:02 13563.44 05-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.326516E+11 0.00 3665.54 0.215524E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 9090484.77 0.00 2.22 8412275.13 0.00 0.00 0.00 0.00 9196.44   9196.44   0.00 0.00 0.00
Maximum of Months 0.752916E+10 0.00 666.21 0.482540E+10 0.00 0.00 0.00 0.00 15584.30   15584.30   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 2590396.11 0.00 1.44 2153419.97 0.00 0.00 0.00 0.00 3817.89 24-JAN-16:03 3817.89 24-JAN-16:03 0.00 0.00 0.00
February 45560293.78 0.00 15.30 30837153.53 0.00 0.00 0.00 0.00 13295.11 27-FEB-16:02 13295.11 27-FEB-16:02 0.00 0.00 0.00
March 0.274759E+09 0.00 50.96 0.270011E+09 0.00 0.00 0.00 0.00 13367.92 18-MAR-15:02 13367.92 18-MAR-15:02 0.00 0.00 0.00
April 0.135267E+10 0.00 215.29 0.106109E+10 0.00 0.00 0.00 0.00 14029.59 01-APR-18:02 14029.59 01-APR-18:02 0.00 0.00 0.00
May 0.313273E+10 0.00 434.90 0.226434E+10 0.00 0.00 0.00 0.00 13771.06 14-MAY-15:02 13771.06 14-MAY-15:02 0.00 0.00 0.00
June 0.400232E+10 0.00 527.16 0.258256E+10 0.00 0.00 0.00 0.00 13583.18 12-JUN-15:01 13371.71 02-JUN-15:02 0.00 0.00 0.00
July 0.656449E+10 0.00 626.39 0.425716E+10 0.00 0.00 0.00 0.00 13737.19 16-JUL-15:01 13295.24 20-JUL-15:02 0.00 0.00 0.00
August 0.604914E+10 0.00 614.61 0.369354E+10 0.00 0.00 0.00 0.00 13830.87 28-AUG-15:02 13726.49 29-AUG-18:02 0.00 0.00 0.00
September 0.311054E+10 0.00 464.27 0.176382E+10 0.00 0.00 0.00 0.00 13480.98 24-SEP-15:02 13351.61 22-SEP-15:02 0.00 0.00 0.00
October 0.556651E+09 0.00 130.18 0.405752E+09 0.00 0.00 0.00 0.00 13565.85 04-OCT-15:02 13565.85 04-OCT-15:02 0.00 0.00 0.00
November 44752227.89 0.00 11.49 23170043.01 0.00 0.00 0.00 0.00 13492.55 04-NOV-15:02 12753.31 04-NOV-15:02 0.00 0.00 0.00
December 4296991.80 0.00 1.48 3535860.94 0.00 0.00 0.00 0.00 3601.22 03-DEC-19:03 3601.22 03-DEC-19:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.251405E+11 0.00 3093.47 0.163580E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 2590396.11 0.00 1.44 2153419.97 0.00 0.00 0.00 0.00 3601.22   3601.22   0.00 0.00 0.00
Maximum of Months 0.656449E+10 0.00 626.39 0.425716E+10 0.00 0.00 0.00 0.00 14029.59   14029.59   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 20465098.89 0.00 2.00 20465098.89 0.00 0.00 0.00 0.00 4582.63 08-JAN-14:40 4582.63 08-JAN-14:40 0.00 0.00 0.00
February 0.231332E+10 0.00 44.10 0.231332E+10 0.00 0.00 0.00 0.00 34513.54 08-FEB-14:00 34513.54 08-FEB-14:00 0.00 0.00 0.00
March 0.565474E+10 0.00 136.38 0.565474E+10 0.00 0.00 0.00 0.00 46834.27 02-MAR-13:30 46834.27 02-MAR-13:30 0.00 0.00 0.00
April 0.924778E+10 0.00 246.68 0.776762E+10 0.00 0.00 0.00 0.00 42082.96 27-APR-13:20 38095.76 27-APR-13:10 0.00 0.00 0.00
May 0.121638E+11 0.00 322.21 0.925114E+10 0.00 0.00 0.00 0.00 41461.31 04-MAY-13:20 36089.88 04-MAY-13:20 0.00 0.00 0.00
June 0.127592E+11 0.00 379.77 0.688043E+10 0.00 0.00 0.00 0.00 29319.41 28-JUN-13:10 23963.40 09-JUN-12:40 0.00 0.00 0.00
July 0.218399E+11 0.00 480.19 0.117487E+11 0.00 0.00 0.00 0.00 41009.86 31-JUL-13:00 32491.03 31-JUL-13:20 0.00 0.00 0.00
August 0.271512E+11 0.00 500.00 0.155193E+11 0.00 0.00 0.00 0.00 52861.44 24-AUG-14:50 45353.47 23-AUG-12:30 0.00 0.00 0.00
September 0.238370E+11 0.00 390.32 0.148896E+11 0.00 0.00 0.00 0.00 54484.41 14-SEP-13:30 44040.90 10-SEP-15:03 0.00 0.00 0.00
October 0.124482E+11 0.00 220.09 0.109426E+11 0.00 0.00 0.00 0.00 56017.09 04-OCT-12:30 56017.09 04-OCT-12:30 0.00 0.00 0.00
November 0.112967E+10 0.00 26.62 0.739222E+09 0.00 0.00 0.00 0.00 35295.01 04-NOV-13:30 25309.18 04-NOV-13:40 0.00 0.00 0.00
December 0.110088E+10 0.00 23.42 0.110088E+10 0.00 0.00 0.00 0.00 30395.72 05-DEC-12:25 30395.72 05-DEC-12:25 0.00 0.00 0.00
                               
Annual Sum or Average 0.129666E+12 0.00 2771.79 0.868281E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 20465098.89 0.00 2.00 20465098.89 0.00 0.00 0.00 0.00 4582.63   4582.63   0.00 0.00 0.00
Maximum of Months 0.271512E+11 0.00 500.00 0.155193E+11 0.00 0.00 0.00 0.00 56017.09   56017.09   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.239592E+09 0.00 28.46 0.154160E+09 0.00 0.00 0.00 0.00 30315.95 09-JAN-19:04 30315.95 09-JAN-19:04 0.00 0.00 0.00
February 0.132398E+10 0.00 90.02 0.640198E+09 0.00 0.00 0.00 0.00 53766.71 25-FEB-09:03 53766.71 25-FEB-09:03 0.00 0.00 0.00
March 0.346448E+10 0.00 231.72 0.262306E+10 0.00 0.00 0.00 0.00 53956.08 21-MAR-18:02 53956.08 21-MAR-18:02 0.00 0.00 0.00
April 0.110374E+11 0.00 395.85 0.828232E+10 0.00 0.00 0.00 0.00 61385.87 01-APR-18:02 61385.87 01-APR-18:02 0.00 0.00 0.00
May 0.215298E+11 0.00 512.83 0.152820E+11 0.00 0.00 0.00 0.00 63956.87 05-MAY-18:02 61647.79 14-MAY-18:02 0.00 0.00 0.00
June 0.286246E+11 0.00 508.21 0.202742E+11 0.00 0.00 0.00 0.00 62771.73 09-JUN-18:02 62771.73 09-JUN-18:02 0.00 0.00 0.00
July 0.359726E+11 0.00 525.41 0.246532E+11 0.00 0.00 0.00 0.00 66065.56 15-JUL-18:02 64908.93 24-JUL-18:02 0.00 0.00 0.00
August 0.350617E+11 0.00 525.50 0.219150E+11 0.00 0.00 0.00 0.00 65521.64 13-AUG-15:02 64219.08 10-AUG-18:02 0.00 0.00 0.00
September 0.201181E+11 0.00 497.31 0.107798E+11 0.00 0.00 0.00 0.00 61476.70 23-SEP-15:02 58758.54 13-SEP-18:02 0.00 0.00 0.00
October 0.668501E+10 0.00 347.54 0.367824E+10 0.00 0.00 0.00 0.00 58788.80 01-OCT-08:62 55233.57 02-OCT-18:01 0.00 0.00 0.00
November 0.225679E+10 0.00 147.55 0.863824E+09 0.00 0.00 0.00 0.00 56772.97 05-NOV-08:62 53943.92 04-NOV-08:63 0.00 0.00 0.00
December 0.178853E+09 0.00 19.99 0.118246E+09 0.00 0.00 0.00 0.00 33120.92 05-DEC-19:03 33120.92 05-DEC-19:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.166493E+12 0.00 3830.41 0.109264E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.178853E+09 0.00 19.99 0.118246E+09 0.00 0.00 0.00 0.00 30315.95   30315.95   0.00 0.00 0.00
Maximum of Months 0.359726E+11 0.00 525.50 0.246532E+11 0.00 0.00 0.00 0.00 66065.56   64908.93   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 7737990.56 0.00 3.20 7125174.14 0.00 0.00 0.00 0.00 3455.22 10-JAN-09:03 3455.22 10-JAN-09:03 0.00 0.00 0.00
February 0.165255E+09 0.00 39.83 0.128869E+09 0.00 0.00 0.00 0.00 11822.93 08-FEB-16:02 11822.93 08-FEB-16:02 0.00 0.00 0.00
March 0.649575E+09 0.00 135.89 0.605980E+09 0.00 0.00 0.00 0.00 13286.59 18-MAR-15:02 13286.59 18-MAR-15:02 0.00 0.00 0.00
April 0.216076E+10 0.00 340.67 0.168078E+10 0.00 0.00 0.00 0.00 13860.31 01-APR-18:02 13860.31 01-APR-18:02 0.00 0.00 0.00
May 0.338929E+10 0.00 475.80 0.233345E+10 0.00 0.00 0.00 0.00 13686.58 14-MAY-15:02 13686.58 14-MAY-15:02 0.00 0.00 0.00
June 0.499394E+10 0.00 606.15 0.320699E+10 0.00 0.00 0.00 0.00 13641.55 12-JUN-15:01 13281.76 08-JUN-15:02 0.00 0.00 0.00
July 0.649394E+10 0.00 678.58 0.399044E+10 0.00 0.00 0.00 0.00 13917.32 31-JUL-18:02 13553.48 24-JUL-18:02 0.00 0.00 0.00
August 0.729568E+10 0.00 665.50 0.452899E+10 0.00 0.00 0.00 0.00 14054.40 30-AUG-08:62 13678.86 07-AUG-18:02 0.00 0.00 0.00
September 0.424362E+10 0.00 524.11 0.253838E+10 0.00 0.00 0.00 0.00 13492.26 24-SEP-15:02 13279.12 22-SEP-15:02 0.00 0.00 0.00
October 0.131169E+10 0.00 250.05 0.921696E+09 0.00 0.00 0.00 0.00 13482.95 04-OCT-15:02 13482.95 04-OCT-15:02 0.00 0.00 0.00
November 0.141153E+09 0.00 41.47 70111800.17 0.00 0.00 0.00 0.00 13388.00 04-NOV-15:02 12686.75 04-NOV-15:02 0.00 0.00 0.00
December 51142684.37 0.00 14.38 48100787.87 0.00 0.00 0.00 0.00 4002.10 29-DEC-09:03 3646.41 02-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.309038E+11 0.00 3775.63 0.200609E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 7737990.56 0.00 3.20 7125174.14 0.00 0.00 0.00 0.00 3455.22   3455.22   0.00 0.00 0.00
Maximum of Months 0.729568E+10 0.00 678.58 0.452899E+10 0.00 0.00 0.00 0.00 14054.40   13860.31   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 3462527.96 0.00 1.63 3002464.10 0.00 0.00 0.00 0.00 2886.72 05-JAN-09:04 2886.72 05-JAN-09:04 0.00 0.00 0.00
February 20347280.71 0.00 12.83 12919202.77 0.00 0.00 0.00 0.00 4381.11 27-FEB-09:01 3875.98 27-FEB-16:02 0.00 0.00 0.00
March 0.176982E+09 0.00 49.40 0.159658E+09 0.00 0.00 0.00 0.00 11149.89 02-MAR-09:01 11149.89 02-MAR-09:01 0.00 0.00 0.00
April 0.131762E+10 0.00 248.51 0.989489E+09 0.00 0.00 0.00 0.00 12120.61 02-APR-15:02 12120.61 02-APR-15:02 0.00 0.00 0.00
May 0.256288E+10 0.00 422.32 0.175166E+10 0.00 0.00 0.00 0.00 12417.60 14-MAY-15:02 12417.60 14-MAY-15:02 0.00 0.00 0.00
June 0.431044E+10 0.00 578.29 0.282612E+10 0.00 0.00 0.00 0.00 12391.01 12-JUN-15:01 12158.84 28-JUN-18:02 0.00 0.00 0.00
July 0.548881E+10 0.00 666.79 0.340620E+10 0.00 0.00 0.00 0.00 12764.01 31-JUL-18:02 12506.92 30-JUL-15:02 0.00 0.00 0.00
August 0.592044E+10 0.00 639.32 0.355157E+10 0.00 0.00 0.00 0.00 12710.68 09-AUG-18:02 12449.66 23-AUG-15:02 0.00 0.00 0.00
September 0.263955E+10 0.00 443.50 0.148058E+10 0.00 0.00 0.00 0.00 12770.89 23-SEP-15:02 12028.63 11-SEP-15:02 0.00 0.00 0.00
October 0.496829E+09 0.00 126.34 0.324312E+09 0.00 0.00 0.00 0.00 12019.92 04-OCT-15:02 12019.92 04-OCT-15:02 0.00 0.00 0.00
November 23197726.62 0.00 13.42 8691963.98 0.00 0.00 0.00 0.00 6951.11 04-NOV-15:02 4622.58 04-NOV-15:02 0.00 0.00 0.00
December 4934408.93 0.00 1.76 4362900.04 0.00 0.00 0.00 0.00 2777.56 03-DEC-09:03 2777.56 03-DEC-09:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.229655E+11 0.00 3204.11 0.145186E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 3462527.96 0.00 1.63 3002464.10 0.00 0.00 0.00 0.00 2777.56   2777.56   0.00 0.00 0.00
Maximum of Months 0.592044E+10 0.00 666.79 0.355157E+10 0.00 0.00 0.00 0.00 12770.89   12506.92   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 1394549.60 0.00 1.21 1281811.31 0.00 0.00 0.00 0.00 1924.55 20-JAN-16:02 1924.55 20-JAN-16:02 0.00 0.00 0.00
February 45850530.62 0.00 30.17 39190490.32 0.00 0.00 0.00 0.00 3717.99 06-FEB-16:02 3717.99 06-FEB-16:02 0.00 0.00 0.00
March 0.173221E+09 0.00 91.51 0.169062E+09 0.00 0.00 0.00 0.00 3875.77 18-MAR-15:02 3875.77 18-MAR-15:02 0.00 0.00 0.00
April 0.517273E+09 0.00 245.15 0.425556E+09 0.00 0.00 0.00 0.00 4067.07 01-APR-18:02 4067.07 01-APR-18:02 0.00 0.00 0.00
May 0.959932E+09 0.00 421.23 0.719541E+09 0.00 0.00 0.00 0.00 3992.28 14-MAY-15:02 3992.28 14-MAY-15:02 0.00 0.00 0.00
June 0.112154E+10 0.00 512.89 0.737563E+09 0.00 0.00 0.00 0.00 3966.87 12-JUN-15:01 3874.00 08-JUN-15:02 0.00 0.00 0.00
July 0.186964E+10 0.00 648.34 0.122968E+10 0.00 0.00 0.00 0.00 3999.67 16-JUL-15:01 3944.68 31-JUL-18:02 0.00 0.00 0.00
August 0.178891E+10 0.00 621.89 0.114610E+10 0.00 0.00 0.00 0.00 4043.53 25-AUG-08:62 3960.21 10-AUG-18:02 0.00 0.00 0.00
September 0.109975E+10 0.00 459.75 0.695738E+09 0.00 0.00 0.00 0.00 3946.61 23-SEP-08:62 3767.01 23-SEP-18:02 0.00 0.00 0.00
October 0.288514E+09 0.00 176.31 0.218301E+09 0.00 0.00 0.00 0.00 3932.84 04-OCT-15:02 3932.84 04-OCT-15:02 0.00 0.00 0.00
November 32375897.35 0.00 22.53 18660115.35 0.00 0.00 0.00 0.00 3684.11 11-NOV-16:02 3684.11 11-NOV-16:02 0.00 0.00 0.00
December 3514156.28 0.00 2.24 3235718.86 0.00 0.00 0.00 0.00 3559.63 05-DEC-16:02 3559.63 05-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.790192E+10 0.00 3233.21 0.540391E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 1394549.60 0.00 1.21 1281811.31 0.00 0.00 0.00 0.00 1924.55   1924.55   0.00 0.00 0.00
Maximum of Months 0.186964E+10 0.00 648.34 0.122968E+10 0.00 0.00 0.00 0.00 4067.07   4067.07   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 482531.01 0.00 0.32 381086.20 0.00 0.00 0.00 0.00 718.59 11-JAN-16:05 624.44 25-JAN-16:04 0.00 0.00 0.00
February 8682963.43 0.00 11.78 6483379.46 0.00 0.00 0.00 0.00 3440.80 27-FEB-16:02 3440.80 27-FEB-16:02 0.00 0.00 0.00
March 61697128.26 0.00 39.81 60746426.64 0.00 0.00 0.00 0.00 3459.64 18-MAR-15:02 3459.64 18-MAR-15:02 0.00 0.00 0.00
April 0.324437E+09 0.00 170.74 0.263920E+09 0.00 0.00 0.00 0.00 3630.91 01-APR-18:02 3630.91 01-APR-18:02 0.00 0.00 0.00
May 0.749187E+09 0.00 356.51 0.571375E+09 0.00 0.00 0.00 0.00 3564.28 14-MAY-15:02 3564.28 14-MAY-15:02 0.00 0.00 0.00
June 0.954531E+09 0.00 468.44 0.646638E+09 0.00 0.00 0.00 0.00 3526.15 12-JUN-15:01 3460.67 02-JUN-15:02 0.00 0.00 0.00
July 0.160963E+10 0.00 614.51 0.107611E+10 0.00 0.00 0.00 0.00 3566.36 16-JUL-15:01 3557.38 31-JUL-18:02 0.00 0.00 0.00
August 0.143384E+10 0.00 575.66 0.907873E+09 0.00 0.00 0.00 0.00 3585.64 28-AUG-15:02 3527.33 29-AUG-18:02 0.00 0.00 0.00
September 0.684310E+09 0.00 362.05 0.417465E+09 0.00 0.00 0.00 0.00 3510.56 24-SEP-15:02 3418.59 13-SEP-18:02 0.00 0.00 0.00
October 0.107667E+09 0.00 78.34 83883771.99 0.00 0.00 0.00 0.00 3510.88 04-OCT-15:02 3510.88 04-OCT-15:02 0.00 0.00 0.00
November 10803747.32 0.00 7.16 6213853.23 0.00 0.00 0.00 0.00 3499.38 04-NOV-15:02 3296.36 04-NOV-15:02 0.00 0.00 0.00
December 1112348.84 0.00 0.66 948988.11 0.00 0.00 0.00 0.00 847.81 10-DEC-16:03 778.89 05-DEC-16:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.594638E+10 0.00 2685.96 0.404204E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 482531.01 0.00 0.32 381086.20 0.00 0.00 0.00 0.00 718.59   624.44   0.00 0.00 0.00
Maximum of Months 0.160963E+10 0.00 614.51 0.107611E+10 0.00 0.00 0.00 0.00 3630.91   3630.91   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.386361E+09 0.00 47.78 0.381536E+09 0.00 0.00 0.00 0.00 20203.47 20-JAN-16:02 20203.47 20-JAN-16:02 0.00 0.00 0.00
February 0.158324E+10 0.00 151.39 0.139618E+10 0.00 0.00 0.00 0.00 20215.56 01-FEB-16:02 20215.56 01-FEB-16:02 0.00 0.00 0.00
March 0.276938E+10 0.00 259.42 0.255054E+10 0.00 0.00 0.00 0.00 21062.24 18-MAR-15:02 21062.24 18-MAR-15:02 0.00 0.00 0.00
April 0.421691E+10 0.00 401.24 0.332985E+10 0.00 0.00 0.00 0.00 21240.23 27-APR-18:02 21240.23 27-APR-18:02 0.00 0.00 0.00
May 0.533718E+10 0.00 505.19 0.357817E+10 0.00 0.00 0.00 0.00 21702.17 05-MAY-18:02 21694.31 14-MAY-15:02 0.00 0.00 0.00
June 0.605830E+10 0.00 584.13 0.350253E+10 0.00 0.00 0.00 0.00 21739.53 12-JUN-15:01 21589.28 09-JUN-18:02 0.00 0.00 0.00
July 0.894587E+10 0.00 661.30 0.517717E+10 0.00 0.00 0.00 0.00 22173.38 15-JUL-18:02 21474.74 24-JUL-18:02 0.00 0.00 0.00
August 0.101841E+11 0.00 653.03 0.621749E+10 0.00 0.00 0.00 0.00 21810.28 09-AUG-18:02 21669.23 29-AUG-18:02 0.00 0.00 0.00
September 0.818835E+10 0.00 563.78 0.523116E+10 0.00 0.00 0.00 0.00 21059.13 22-SEP-18:02 20829.81 14-SEP-15:02 0.00 0.00 0.00
October 0.427554E+10 0.00 387.98 0.312743E+10 0.00 0.00 0.00 0.00 21373.06 04-OCT-15:02 21373.06 04-OCT-15:02 0.00 0.00 0.00
November 0.104780E+10 0.00 115.17 0.752556E+09 0.00 0.00 0.00 0.00 20211.29 10-NOV-16:01 20211.29 10-NOV-16:01 0.00 0.00 0.00
December 0.879794E+09 0.00 91.54 0.853483E+09 0.00 0.00 0.00 0.00 20208.16 06-DEC-16:02 20208.16 06-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.538728E+11 0.00 4421.96 0.360981E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.386361E+09 0.00 47.78 0.381536E+09 0.00 0.00 0.00 0.00 20203.47   20203.47   0.00 0.00 0.00
Maximum of Months 0.101841E+11 0.00 661.30 0.621749E+10 0.00 0.00 0.00 0.00 22173.38   21694.31   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 438.55 260.88 177.67 386.54 513.67 0.00 0.00 0.00
February 674.87 418.72 256.15 676.06 451.92 0.00 0.00 0.00
March 715.89 378.50 337.40 755.36 375.57 0.00 0.00 0.00
April 756.46 324.65 431.81 851.19 302.22 0.00 0.00 0.00
May 704.79 214.87 489.92 813.57 240.13 0.00 0.00 0.00
June 637.68 170.67 467.01 760.58 177.27 0.00 0.00 0.00
July 692.81 251.56 441.25 894.13 157.10 0.00 0.00 0.00
August 738.59 339.38 399.21 973.19 152.17 0.00 0.00 0.00
September 819.19 448.04 371.15 1008.76 226.59 0.00 0.00 0.00
October 741.03 453.68 287.34 835.07 318.65 0.00 0.00 0.00
November 443.48 253.85 189.63 424.24 406.85 0.00 0.00 0.00
December 464.15 300.16 163.99 448.39 516.41 0.00 0.00 0.00
                 
Annual Sum or Average 651.97 317.29 334.69 735.80 319.25 0.00 0.00 0.00
Minimum of Months 438.55 170.67 163.99 386.54 152.17 0.00 0.00 0.00
Maximum of Months 819.19 453.68 489.92 1008.76 516.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1234.93 734.63 500.29 1072.69 1490.99 0.00 0.00 0.00
February 1900.38 1179.08 721.29 1879.61 1324.18 0.00 0.00 0.00
March 2015.91 1065.82 950.09 2099.72 1123.78 0.00 0.00 0.00
April 2130.15 914.20 1215.94 2362.19 917.07 0.00 0.00 0.00
May 1984.66 605.06 1379.59 2252.86 738.88 0.00 0.00 0.00
June 1795.66 480.59 1315.07 2097.26 561.49 0.00 0.00 0.00
July 1950.90 708.37 1242.53 2477.93 500.24 0.00 0.00 0.00
August 2079.83 955.67 1124.16 2704.05 488.26 0.00 0.00 0.00
September 2306.78 1261.66 1045.13 2809.12 703.94 0.00 0.00 0.00
October 2086.69 1277.54 809.14 2322.79 971.45 0.00 0.00 0.00
November 1248.82 714.83 533.99 1176.37 1201.29 0.00 0.00 0.00
December 1307.01 845.22 461.79 1246.81 1504.20 0.00 0.00 0.00
                 
Annual Sum or Average 1835.92 893.47 942.45 2042.35 958.75 0.00 0.00 0.00
Minimum of Months 1234.93 480.59 461.79 1072.69 488.26 0.00 0.00 0.00
Maximum of Months 2306.78 1277.54 1379.59 2809.12 1504.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1604.24 954.33 649.91 1401.79 2080.88 0.00 0.00 0.00
February 2468.70 1531.69 937.00 2467.40 1838.59 0.00 0.00 0.00
March 2618.78 1384.56 1234.22 2759.72 1570.14 0.00 0.00 0.00
April 2767.18 1187.60 1579.58 3106.03 1280.75 0.00 0.00 0.00
May 2578.18 786.01 1792.17 2956.50 1041.04 0.00 0.00 0.00
June 2332.66 624.32 1708.35 2745.51 795.73 0.00 0.00 0.00
July 2534.33 920.22 1614.12 3256.87 702.02 0.00 0.00 0.00
August 2701.82 1241.47 1460.35 3555.05 679.35 0.00 0.00 0.00
September 2996.64 1638.96 1357.68 3691.43 982.13 0.00 0.00 0.00
October 2710.73 1659.60 1051.12 3050.12 1361.95 0.00 0.00 0.00
November 1622.29 928.61 693.68 1533.41 1695.13 0.00 0.00 0.00
December 1697.88 1097.99 599.89 1632.40 2099.99 0.00 0.00 0.00
                 
Annual Sum or Average 2384.96 1160.66 1224.30 2680.45 1341.61 0.00 0.00 0.00
Minimum of Months 1604.24 624.32 599.89 1401.79 679.35 0.00 0.00 0.00
Maximum of Months 2996.64 1659.60 1792.17 3691.43 2099.99 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 86.71 51.58 35.13 77.90 102.27 0.00 0.00 0.00
February 133.43 82.79 50.64 135.28 89.93 0.00 0.00 0.00
March 141.54 74.84 66.71 150.58 74.86 0.00 0.00 0.00
April 149.57 64.19 85.38 168.05 60.93 0.00 0.00 0.00
May 139.35 42.48 96.87 159.31 48.46 0.00 0.00 0.00
June 126.08 33.74 92.34 148.63 35.18 0.00 0.00 0.00
July 136.98 49.74 87.24 176.12 30.16 0.00 0.00 0.00
August 146.03 67.10 78.93 193.10 28.16 0.00 0.00 0.00
September 161.97 88.59 73.38 201.04 43.84 0.00 0.00 0.00
October 146.51 89.70 56.81 166.48 62.53 0.00 0.00 0.00
November 87.68 50.19 37.49 85.28 80.24 0.00 0.00 0.00
December 91.77 59.35 32.42 90.23 101.90 0.00 0.00 0.00
                 
Annual Sum or Average 128.91 62.73 66.17 146.04 63.08 0.00 0.00 0.00
Minimum of Months 86.71 33.74 32.42 77.90 28.16 0.00 0.00 0.00
Maximum of Months 161.97 89.70 96.87 201.04 102.27 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 62.25 18.52 43.73 27.29 205.51 0.00 0.00 0.00
February 111.04 41.69 69.36 77.41 178.31 0.00 0.00 0.00
March 155.56 52.59 102.96 131.96 142.37 0.00 0.00 0.00
April 236.38 90.26 146.12 240.18 111.04 0.00 0.00 0.00
May 304.75 124.07 180.68 339.09 87.81 0.00 0.00 0.00
June 292.45 113.33 179.11 334.96 63.73 0.00 0.00 0.00
July 361.52 189.97 171.55 448.61 54.77 0.00 0.00 0.00
August 299.20 152.61 146.59 376.37 51.82 0.00 0.00 0.00
September 244.45 117.59 126.86 284.51 81.73 0.00 0.00 0.00
October 139.79 57.47 82.32 130.82 120.25 0.00 0.00 0.00
November 69.23 19.68 49.55 40.62 158.13 0.00 0.00 0.00
December 58.44 20.29 38.15 31.69 203.64 0.00 0.00 0.00
                 
Annual Sum or Average 195.10 83.49 111.61 206.13 121.32 0.00 0.00 0.00
Minimum of Months 58.44 18.52 38.15 27.29 51.82 0.00 0.00 0.00
Maximum of Months 361.52 189.97 180.68 448.61 205.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.55 0.00 19.55 1.07 113.30 0.00 0.00 0.00
February 30.42 0.00 30.42 7.36 98.04 0.00 0.00 0.00
March 44.83 0.00 44.83 21.97 77.11 0.00 0.00 0.00
April 63.66 0.39 63.27 45.01 58.99 0.00 0.00 0.00
May 81.67 2.45 79.22 70.66 45.42 0.00 0.00 0.00
June 85.95 5.75 80.20 83.11 32.26 0.00 0.00 0.00
July 81.81 6.59 75.22 88.09 27.54 0.00 0.00 0.00
August 66.31 1.99 64.32 73.66 26.04 0.00 0.00 0.00
September 51.33 0.04 51.29 44.01 43.57 0.00 0.00 0.00
October 35.14 0.00 35.14 19.35 64.57 0.00 0.00 0.00
November 22.14 0.00 22.14 4.63 85.87 0.00 0.00 0.00
December 16.61 0.00 16.61 0.65 110.53 0.00 0.00 0.00
                 
Annual Sum or Average 50.05 1.44 48.60 38.49 65.11 0.00 0.00 0.00
Minimum of Months 16.61 0.00 16.61 0.65 26.04 0.00 0.00 0.00
Maximum of Months 85.95 6.59 80.20 88.09 113.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 62.25 18.52 43.73 28.98 203.68 0.00 0.00 0.00
February 111.04 41.69 69.36 80.94 175.65 0.00 0.00 0.00
March 155.56 52.59 102.96 136.33 140.17 0.00 0.00 0.00
April 236.38 90.26 146.12 244.31 109.66 0.00 0.00 0.00
May 304.75 124.07 180.68 341.68 87.11 0.00 0.00 0.00
June 292.45 113.33 179.11 336.97 63.24 0.00 0.00 0.00
July 361.52 189.97 171.55 450.75 54.23 0.00 0.00 0.00
August 299.20 152.61 146.59 379.13 51.06 0.00 0.00 0.00
September 244.45 117.59 126.86 288.18 80.30 0.00 0.00 0.00
October 139.79 57.47 82.32 135.24 117.95 0.00 0.00 0.00
November 69.23 19.68 49.55 42.73 156.25 0.00 0.00 0.00
December 58.44 20.29 38.15 33.73 201.52 0.00 0.00 0.00
                 
Annual Sum or Average 195.10 83.49 111.61 209.08 119.81 0.00 0.00 0.00
Minimum of Months 58.44 18.52 38.15 28.98 51.06 0.00 0.00 0.00
Maximum of Months 361.52 189.97 180.68 450.75 203.68 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 69.35 41.26 28.10 62.42 77.58 0.00 0.00 0.00
February 106.72 66.22 40.51 107.43 72.12 0.00 0.00 0.00
March 113.21 59.86 53.36 118.08 65.22 0.00 0.00 0.00
April 119.63 51.34 68.29 131.55 55.00 0.00 0.00 0.00
May 111.46 33.98 77.48 125.30 44.32 0.00 0.00 0.00
June 100.84 26.99 73.85 116.37 33.45 0.00 0.00 0.00
July 109.56 39.78 69.78 139.26 29.07 0.00 0.00 0.00
August 116.80 53.67 63.13 152.49 27.82 0.00 0.00 0.00
September 129.55 70.85 58.69 158.35 41.39 0.00 0.00 0.00
October 117.19 71.75 45.44 130.11 57.34 0.00 0.00 0.00
November 70.13 40.14 29.99 67.22 65.03 0.00 0.00 0.00
December 73.40 47.47 25.93 71.77 79.32 0.00 0.00 0.00
                 
Annual Sum or Average 103.11 50.18 52.93 115.05 53.88 0.00 0.00 0.00
Minimum of Months 69.35 26.99 25.93 62.42 27.82 0.00 0.00 0.00
Maximum of Months 129.55 71.75 77.48 158.35 79.32 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.64 0.00 15.64 0.58 95.73 0.00 0.00 0.00
February 24.34 0.00 24.34 5.28 81.71 0.00 0.00 0.00
March 35.87 0.00 35.87 17.33 63.41 0.00 0.00 0.00
April 50.93 0.31 50.62 37.37 47.46 0.00 0.00 0.00
May 65.34 1.96 63.38 59.54 35.79 0.00 0.00 0.00
June 68.77 4.60 64.17 69.95 25.03 0.00 0.00 0.00
July 65.45 5.27 60.19 75.23 20.63 0.00 0.00 0.00
August 53.06 1.59 51.46 63.24 19.41 0.00 0.00 0.00
September 41.07 0.03 41.04 37.71 33.68 0.00 0.00 0.00
October 28.12 0.00 28.12 15.64 52.78 0.00 0.00 0.00
November 17.71 0.00 17.71 3.19 72.45 0.00 0.00 0.00
December 13.29 0.00 13.29 0.33 93.34 0.00 0.00 0.00
                 
Annual Sum or Average 40.04 1.16 38.89 32.28 53.32 0.00 0.00 0.00
Minimum of Months 13.29 0.00 13.29 0.33 19.41 0.00 0.00 0.00
Maximum of Months 68.77 5.27 64.17 75.23 95.73 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 58.42 14.64 43.78 20.64 203.24 0.00 0.00 0.00
February 107.62 38.12 69.50 69.79 174.86 0.00 0.00 0.00
March 161.29 58.49 102.80 134.71 137.82 0.00 0.00 0.00
April 249.11 103.37 145.74 252.00 106.83 0.00 0.00 0.00
May 265.24 92.35 172.89 284.93 85.21 0.00 0.00 0.00
June 317.46 138.17 179.29 366.61 61.30 0.00 0.00 0.00
July 296.07 133.11 162.96 358.55 50.37 0.00 0.00 0.00
August 290.63 145.38 145.25 361.82 48.45 0.00 0.00 0.00
September 215.23 99.44 115.79 240.97 78.25 0.00 0.00 0.00
October 140.73 60.13 80.60 129.70 117.34 0.00 0.00 0.00
November 68.87 19.50 49.37 38.23 155.71 0.00 0.00 0.00
December 56.34 18.11 38.23 25.98 199.86 0.00 0.00 0.00
                 
Annual Sum or Average 185.93 76.91 109.02 190.94 118.00 0.00 0.00 0.00
Minimum of Months 56.34 14.64 38.23 20.64 48.45 0.00 0.00 0.00
Maximum of Months 317.46 145.38 179.29 366.61 203.24 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 86.71 51.58 35.13 77.87 102.13 0.00 0.00 0.00
February 133.43 82.79 50.64 135.02 89.68 0.00 0.00 0.00
March 141.54 74.84 66.71 149.76 74.63 0.00 0.00 0.00
April 149.57 64.19 85.38 166.76 60.69 0.00 0.00 0.00
May 139.35 42.48 96.87 159.11 47.80 0.00 0.00 0.00
June 126.08 33.74 92.34 147.35 34.87 0.00 0.00 0.00
July 136.98 49.74 87.24 176.11 29.33 0.00 0.00 0.00
August 146.03 67.10 78.93 192.48 27.72 0.00 0.00 0.00
September 161.97 88.59 73.38 200.85 43.08 0.00 0.00 0.00
October 146.51 89.70 56.81 165.91 62.23 0.00 0.00 0.00
November 87.68 50.19 37.49 85.15 80.10 0.00 0.00 0.00
December 91.77 59.35 32.42 90.19 101.73 0.00 0.00 0.00
                 
Annual Sum or Average 128.91 62.73 66.17 145.58 62.70 0.00 0.00 0.00
Minimum of Months 86.71 33.74 32.42 77.87 27.72 0.00 0.00 0.00
Maximum of Months 161.97 89.70 96.87 200.85 102.13 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.55 0.00 19.55 1.04 113.24 0.00 0.00 0.00
February 30.42 0.00 30.42 7.22 97.84 0.00 0.00 0.00
March 44.83 0.00 44.83 21.23 76.98 0.00 0.00 0.00
April 63.66 0.39 63.27 43.71 59.01 0.00 0.00 0.00
May 81.67 2.45 79.22 70.35 44.84 0.00 0.00 0.00
June 85.95 5.75 80.20 81.57 32.00 0.00 0.00 0.00
July 81.81 6.59 75.22 88.06 26.80 0.00 0.00 0.00
August 66.31 1.99 64.32 72.78 25.60 0.00 0.00 0.00
September 51.33 0.04 51.29 43.66 42.88 0.00 0.00 0.00
October 35.14 0.00 35.14 18.73 64.29 0.00 0.00 0.00
November 22.14 0.00 22.14 4.46 85.67 0.00 0.00 0.00
December 16.61 0.00 16.61 0.59 110.37 0.00 0.00 0.00
                 
Annual Sum or Average 50.05 1.44 48.60 37.97 64.80 0.00 0.00 0.00
Minimum of Months 16.61 0.00 16.61 0.59 25.60 0.00 0.00 0.00
Maximum of Months 85.95 6.59 80.20 88.06 113.24 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 58.42 14.64 43.78 21.46 200.65 0.00 0.00 0.00
February 107.62 38.12 69.50 72.21 170.89 0.00 0.00 0.00
March 161.29 58.49 102.80 138.75 135.34 0.00 0.00 0.00
April 249.11 103.37 145.74 255.63 105.36 0.00 0.00 0.00
May 265.24 92.35 172.89 287.20 84.47 0.00 0.00 0.00
June 317.46 138.17 179.29 368.22 60.85 0.00 0.00 0.00
July 296.07 133.11 162.96 360.49 49.82 0.00 0.00 0.00
August 290.63 145.38 145.25 364.26 47.72 0.00 0.00 0.00
September 215.23 99.44 115.79 244.30 76.71 0.00 0.00 0.00
October 140.73 60.13 80.60 133.79 114.80 0.00 0.00 0.00
November 68.87 19.50 49.37 39.73 153.14 0.00 0.00 0.00
December 56.34 18.11 38.23 27.10 196.78 0.00 0.00 0.00
                 
Annual Sum or Average 185.93 76.91 109.02 193.38 116.12 0.00 0.00 0.00
Minimum of Months 56.34 14.64 38.23 21.46 47.72 0.00 0.00 0.00
Maximum of Months 317.46 145.38 179.29 368.22 200.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.76 0.00 24.76 0.71 156.98 0.00 0.00 0.00
February 38.53 0.00 38.53 7.68 134.21 0.00 0.00 0.00
March 56.77 0.00 56.77 25.99 104.79 0.00 0.00 0.00
April 80.62 0.50 80.12 56.58 80.61 0.00 0.00 0.00
May 103.43 3.11 100.32 89.72 63.74 0.00 0.00 0.00
June 108.85 7.28 101.57 104.78 46.66 0.00 0.00 0.00
July 103.60 8.34 95.26 111.27 41.11 0.00 0.00 0.00
August 83.98 2.52 81.46 91.45 40.52 0.00 0.00 0.00
September 65.00 0.05 64.95 54.37 63.22 0.00 0.00 0.00
October 44.51 0.00 44.51 22.34 90.17 0.00 0.00 0.00
November 28.03 0.00 28.03 4.63 118.81 0.00 0.00 0.00
December 21.04 0.00 21.04 0.34 153.35 0.00 0.00 0.00
                 
Annual Sum or Average 63.38 1.83 61.55 47.73 90.98 0.00 0.00 0.00
Minimum of Months 21.04 0.00 21.04 0.34 40.52 0.00 0.00 0.00
Maximum of Months 108.85 8.34 101.57 111.27 156.98 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.13 0.00 9.13 0.26 57.87 0.00 0.00 0.00
February 14.20 0.00 14.20 2.83 49.47 0.00 0.00 0.00
March 20.93 0.00 20.93 9.58 38.63 0.00 0.00 0.00
April 29.72 0.18 29.54 20.86 29.72 0.00 0.00 0.00
May 38.13 1.14 36.98 33.07 23.50 0.00 0.00 0.00
June 40.13 2.68 37.44 38.63 17.20 0.00 0.00 0.00
July 38.19 3.07 35.12 41.02 15.15 0.00 0.00 0.00
August 30.96 0.93 30.03 33.71 14.94 0.00 0.00 0.00
September 23.96 0.02 23.94 20.04 23.31 0.00 0.00 0.00
October 16.41 0.00 16.41 8.23 33.24 0.00 0.00 0.00
November 10.33 0.00 10.33 1.71 43.80 0.00 0.00 0.00
December 7.76 0.00 7.76 0.12 56.53 0.00 0.00 0.00
                 
Annual Sum or Average 23.37 0.67 22.69 17.60 33.54 0.00 0.00 0.00
Minimum of Months 7.76 0.00 7.76 0.12 14.94 0.00 0.00 0.00
Maximum of Months 40.13 3.07 37.44 41.02 57.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 40.46 24.07 16.39 35.57 51.01 0.00 0.00 0.00
February 62.26 38.63 23.63 62.92 44.24 0.00 0.00 0.00
March 66.04 34.92 31.13 70.56 36.84 0.00 0.00 0.00
April 69.79 29.95 39.84 79.13 30.18 0.00 0.00 0.00
May 65.02 19.82 45.20 75.04 24.83 0.00 0.00 0.00
June 58.83 15.74 43.08 69.76 18.68 0.00 0.00 0.00
July 63.91 23.21 40.71 82.66 16.51 0.00 0.00 0.00
August 68.14 31.31 36.83 90.16 15.94 0.00 0.00 0.00
September 75.57 41.33 34.24 94.07 23.00 0.00 0.00 0.00
October 68.36 41.85 26.51 77.89 31.46 0.00 0.00 0.00
November 40.91 23.42 17.49 39.45 40.07 0.00 0.00 0.00
December 42.82 27.69 15.13 41.74 50.91 0.00 0.00 0.00
                 
Annual Sum or Average 60.15 29.27 30.88 68.26 31.92 0.00 0.00 0.00
Minimum of Months 40.46 15.74 15.13 35.57 15.94 0.00 0.00 0.00
Maximum of Months 75.57 41.85 45.20 94.07 51.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.81 65.32 44.49 96.54 138.45 0.00 0.00 0.00
February 168.98 104.85 64.14 170.77 120.07 0.00 0.00 0.00
March 179.26 94.77 84.48 191.50 99.99 0.00 0.00 0.00
April 189.42 81.29 108.12 214.78 81.93 0.00 0.00 0.00
May 176.48 53.80 122.68 203.67 67.40 0.00 0.00 0.00
June 159.67 42.73 116.94 189.35 50.69 0.00 0.00 0.00
July 173.48 62.99 110.49 224.36 44.80 0.00 0.00 0.00
August 184.94 84.98 99.96 244.72 43.26 0.00 0.00 0.00
September 205.12 112.19 92.93 255.33 62.43 0.00 0.00 0.00
October 185.55 113.60 71.95 211.40 85.38 0.00 0.00 0.00
November 111.05 63.56 47.48 107.08 108.76 0.00 0.00 0.00
December 116.22 75.16 41.06 113.30 138.18 0.00 0.00 0.00
                 
Annual Sum or Average 163.25 79.45 83.80 185.28 86.62 0.00 0.00 0.00
Minimum of Months 109.81 42.73 41.06 96.54 43.26 0.00 0.00 0.00
Maximum of Months 205.12 113.60 122.68 255.33 138.45 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 86.71 51.58 35.13 77.96 101.61 0.00 0.00 0.00
February 133.43 82.79 50.64 135.07 89.32 0.00 0.00 0.00
March 141.54 74.84 66.71 150.07 74.26 0.00 0.00 0.00
April 149.57 64.19 85.38 166.98 60.60 0.00 0.00 0.00
May 139.35 42.48 96.87 157.97 48.13 0.00 0.00 0.00
June 126.08 33.74 92.34 147.24 34.86 0.00 0.00 0.00
July 136.98 49.74 87.24 174.61 29.86 0.00 0.00 0.00
August 146.03 67.10 78.93 191.94 27.67 0.00 0.00 0.00
September 161.97 88.59 73.38 200.29 43.19 0.00 0.00 0.00
October 146.51 89.70 56.81 165.99 61.67 0.00 0.00 0.00
November 87.68 50.19 37.49 85.32 79.40 0.00 0.00 0.00
December 91.77 59.35 32.42 90.29 101.00 0.00 0.00 0.00
                 
Annual Sum or Average 128.91 62.73 66.17 145.34 62.50 0.00 0.00 0.00
Minimum of Months 86.71 33.74 32.42 77.96 27.67 0.00 0.00 0.00
Maximum of Months 161.97 89.70 96.87 200.29 101.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 62.25 18.52 43.73 27.58 203.80 0.00 0.00 0.00
February 111.04 41.69 69.36 77.37 176.72 0.00 0.00 0.00
March 155.56 52.59 102.96 131.42 140.91 0.00 0.00 0.00
April 236.38 90.26 146.12 238.28 110.29 0.00 0.00 0.00
May 304.75 124.07 180.68 336.25 87.07 0.00 0.00 0.00
June 292.45 113.33 179.11 332.01 63.01 0.00 0.00 0.00
July 361.52 189.97 171.55 445.21 54.09 0.00 0.00 0.00
August 299.20 152.61 146.59 374.06 50.81 0.00 0.00 0.00
September 244.45 117.59 126.86 283.13 80.35 0.00 0.00 0.00
October 139.79 57.47 82.32 130.42 118.29 0.00 0.00 0.00
November 69.23 19.68 49.55 40.91 156.05 0.00 0.00 0.00
December 58.44 20.29 38.15 31.90 201.22 0.00 0.00 0.00
                 
Annual Sum or Average 195.10 83.49 111.61 204.87 119.95 0.00 0.00 0.00
Minimum of Months 58.44 18.52 38.15 27.58 50.81 0.00 0.00 0.00
Maximum of Months 361.52 189.97 180.68 445.21 203.80 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.55 0.00 19.55 1.15 112.22 0.00 0.00 0.00
February 30.42 0.00 30.42 7.56 97.12 0.00 0.00 0.00
March 44.83 0.00 44.83 22.22 76.22 0.00 0.00 0.00
April 63.66 0.39 63.27 44.89 58.41 0.00 0.00 0.00
May 81.67 2.45 79.22 70.04 44.96 0.00 0.00 0.00
June 85.95 5.75 80.20 82.31 31.87 0.00 0.00 0.00
July 81.81 6.59 75.22 87.25 27.18 0.00 0.00 0.00
August 66.31 1.99 64.32 73.34 25.49 0.00 0.00 0.00
September 51.33 0.04 51.29 43.95 42.75 0.00 0.00 0.00
October 35.14 0.00 35.14 19.81 63.30 0.00 0.00 0.00
November 22.14 0.00 22.14 4.84 84.62 0.00 0.00 0.00
December 16.61 0.00 16.61 0.76 109.05 0.00 0.00 0.00
                 
Annual Sum or Average 50.05 1.44 48.60 38.36 64.27 0.00 0.00 0.00
Minimum of Months 16.61 0.00 16.61 0.76 25.49 0.00 0.00 0.00
Maximum of Months 85.95 6.59 80.20 87.25 112.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 62.25 18.52 43.73 29.20 202.15 0.00 0.00 0.00
February 111.04 41.69 69.36 81.15 174.10 0.00 0.00 0.00
March 155.56 52.59 102.96 136.20 138.54 0.00 0.00 0.00
April 236.38 90.26 146.12 242.78 108.74 0.00 0.00 0.00
May 304.75 124.07 180.68 338.99 86.30 0.00 0.00 0.00
June 292.45 113.33 179.11 334.05 62.49 0.00 0.00 0.00
July 361.52 189.97 171.55 447.38 53.53 0.00 0.00 0.00
August 299.20 152.61 146.59 376.97 49.99 0.00 0.00 0.00
September 244.45 117.59 126.86 287.10 78.70 0.00 0.00 0.00
October 139.79 57.47 82.32 135.40 115.69 0.00 0.00 0.00
November 69.23 19.68 49.55 43.15 154.18 0.00 0.00 0.00
December 58.44 20.29 38.15 34.09 199.19 0.00 0.00 0.00
                 
Annual Sum or Average 195.10 83.49 111.61 208.03 118.37 0.00 0.00 0.00
Minimum of Months 58.44 18.52 38.15 29.20 49.99 0.00 0.00 0.00
Maximum of Months 361.52 189.97 180.68 447.38 202.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 127.17 75.65 51.52 109.81 155.04 0.00 0.00 0.00
February 195.69 121.42 74.28 192.51 136.47 0.00 0.00 0.00
March 207.59 109.75 97.84 215.56 113.04 0.00 0.00 0.00
April 219.35 94.14 125.21 242.13 90.55 0.00 0.00 0.00
May 204.37 62.31 142.06 231.77 70.47 0.00 0.00 0.00
June 184.91 49.49 135.42 216.74 50.68 0.00 0.00 0.00
July 200.90 72.94 127.95 258.24 42.48 0.00 0.00 0.00
August 214.17 98.41 115.76 282.45 39.76 0.00 0.00 0.00
September 237.54 129.92 107.62 292.52 63.67 0.00 0.00 0.00
October 214.88 131.56 83.32 239.15 94.19 0.00 0.00 0.00
November 128.60 73.61 54.99 121.19 121.99 0.00 0.00 0.00
December 134.59 87.04 47.55 128.23 154.35 0.00 0.00 0.00
                 
Annual Sum or Average 189.05 92.00 97.05 210.93 94.18 0.00 0.00 0.00
Minimum of Months 127.17 49.49 47.55 109.81 39.76 0.00 0.00 0.00
Maximum of Months 237.54 131.56 142.06 292.52 155.04 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 136.86 0.00 136.86 1.34 1000.22 0.00 0.00 0.00
February 212.96 0.00 212.96 26.44 862.52 0.00 0.00 0.00
March 313.79 0.00 313.79 109.65 679.15 0.00 0.00 0.00
April 445.58 2.74 442.84 264.77 515.57 0.00 0.00 0.00
May 571.66 17.16 554.50 443.48 394.50 0.00 0.00 0.00
June 601.63 40.25 561.38 524.55 289.60 0.00 0.00 0.00
July 572.63 46.10 526.53 572.51 250.66 0.00 0.00 0.00
August 464.18 13.94 450.24 472.83 244.90 0.00 0.00 0.00
September 359.27 0.27 359.00 270.55 385.23 0.00 0.00 0.00
October 245.99 0.00 245.99 95.87 582.96 0.00 0.00 0.00
November 154.95 0.00 154.95 14.12 782.42 0.00 0.00 0.00
December 116.30 0.00 116.30 0.41 978.56 0.00 0.00 0.00
                 
Annual Sum or Average 350.33 10.11 340.21 234.35 579.16 0.00 0.00 0.00
Minimum of Months 116.30 0.00 116.30 0.41 244.90 0.00 0.00 0.00
Maximum of Months 601.63 46.10 561.38 572.51 1000.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 136.86 0.00 136.86 0.83 1032.51 0.00 0.00 0.00
February 212.96 0.00 212.96 23.13 890.46 0.00 0.00 0.00
March 313.79 0.00 313.79 101.24 698.36 0.00 0.00 0.00
April 445.58 2.74 442.84 254.06 528.92 0.00 0.00 0.00
May 571.66 17.16 554.50 432.69 403.67 0.00 0.00 0.00
June 601.63 40.25 561.38 513.77 296.63 0.00 0.00 0.00
July 572.63 46.10 526.53 563.42 256.98 0.00 0.00 0.00
August 464.18 13.94 450.24 464.01 251.86 0.00 0.00 0.00
September 359.27 0.27 359.00 262.34 395.54 0.00 0.00 0.00
October 245.99 0.00 245.99 88.41 601.34 0.00 0.00 0.00
November 154.95 0.00 154.95 11.87 810.36 0.00 0.00 0.00
December 116.30 0.00 116.30 0.25 1010.84 0.00 0.00 0.00
                 
Annual Sum or Average 350.33 10.11 340.21 227.63 596.71 0.00 0.00 0.00
Minimum of Months 116.30 0.00 116.30 0.25 251.86 0.00 0.00 0.00
Maximum of Months 601.63 46.10 561.38 563.42 1032.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.55 0.00 19.55 1.30 121.09 0.00 0.00 0.00
February 30.42 0.00 30.42 8.71 105.36 0.00 0.00 0.00
March 44.83 0.00 44.83 25.55 83.93 0.00 0.00 0.00
April 63.66 0.39 63.27 53.68 65.68 0.00 0.00 0.00
May 81.67 2.45 79.22 84.73 51.62 0.00 0.00 0.00
June 85.95 5.75 80.20 99.15 39.33 0.00 0.00 0.00
July 81.81 6.59 75.22 107.08 33.84 0.00 0.00 0.00
August 66.31 1.99 64.32 91.47 32.48 0.00 0.00 0.00
September 51.33 0.04 51.29 57.60 46.52 0.00 0.00 0.00
October 35.14 0.00 35.14 24.03 70.41 0.00 0.00 0.00
November 22.14 0.00 22.14 6.39 92.61 0.00 0.00 0.00
December 16.61 0.00 16.61 1.04 118.07 0.00 0.00 0.00
                 
Annual Sum or Average 50.05 1.44 48.60 46.96 71.59 0.00 0.00 0.00
Minimum of Months 16.61 0.00 16.61 1.04 32.48 0.00 0.00 0.00
Maximum of Months 85.95 6.59 80.20 107.08 121.09 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 116.83 29.28 87.55 46.08 435.10 0.00 0.00 0.00
February 215.22 76.23 138.99 152.83 373.28 0.00 0.00 0.00
March 322.56 116.96 205.59 296.89 299.91 0.00 0.00 0.00
April 498.18 206.73 291.45 552.54 238.18 0.00 0.00 0.00
May 530.45 184.69 345.75 628.85 194.08 0.00 0.00 0.00
June 634.88 276.32 358.55 802.05 148.48 0.00 0.00 0.00
July 592.09 266.20 325.89 791.82 125.62 0.00 0.00 0.00
August 581.22 290.74 290.48 799.24 121.43 0.00 0.00 0.00
September 430.43 198.86 231.56 544.26 170.24 0.00 0.00 0.00
October 281.45 120.26 161.19 291.43 255.76 0.00 0.00 0.00
November 137.73 39.00 98.73 88.68 337.10 0.00 0.00 0.00
December 112.67 36.21 76.46 58.84 427.66 0.00 0.00 0.00
                 
Annual Sum or Average 371.83 153.80 218.03 422.50 260.05 0.00 0.00 0.00
Minimum of Months 112.67 29.28 76.46 46.08 121.43 0.00 0.00 0.00
Maximum of Months 634.88 290.74 358.55 802.05 435.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 86.71 51.58 35.13 79.88 110.11 0.00 0.00 0.00
February 133.43 82.79 50.64 140.24 96.55 0.00 0.00 0.00
March 141.54 74.84 66.71 158.13 81.24 0.00 0.00 0.00
April 149.57 64.19 85.38 179.38 67.17 0.00 0.00 0.00
May 139.35 42.48 96.87 174.45 53.93 0.00 0.00 0.00
June 126.08 33.74 92.34 165.33 41.82 0.00 0.00 0.00
July 136.98 49.74 87.24 195.65 35.70 0.00 0.00 0.00
August 146.03 67.10 78.93 212.26 33.84 0.00 0.00 0.00
September 161.97 88.59 73.38 217.76 46.23 0.00 0.00 0.00
October 146.51 89.70 56.81 175.57 68.39 0.00 0.00 0.00
November 87.68 50.19 37.49 89.20 87.24 0.00 0.00 0.00
December 91.77 59.35 32.42 93.28 109.74 0.00 0.00 0.00
                 
Annual Sum or Average 128.91 62.73 66.17 156.83 69.20 0.00 0.00 0.00
Minimum of Months 86.71 33.74 32.42 79.88 33.84 0.00 0.00 0.00
Maximum of Months 161.97 89.70 96.87 217.76 110.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.76 0.00 24.76 0.57 160.64 0.00 0.00 0.00
February 38.53 0.00 38.53 6.69 137.79 0.00 0.00 0.00
March 56.77 0.00 56.77 23.76 107.07 0.00 0.00 0.00
April 80.62 0.50 80.12 53.38 82.08 0.00 0.00 0.00
May 103.43 3.11 100.32 85.96 64.61 0.00 0.00 0.00
June 108.85 7.28 101.57 100.16 47.99 0.00 0.00 0.00
July 103.60 8.34 95.26 106.54 42.50 0.00 0.00 0.00
August 83.98 2.52 81.46 87.94 41.45 0.00 0.00 0.00
September 65.00 0.05 64.95 51.67 63.79 0.00 0.00 0.00
October 44.51 0.00 44.51 20.59 91.36 0.00 0.00 0.00
November 28.03 0.00 28.03 3.93 122.27 0.00 0.00 0.00
December 21.04 0.00 21.04 0.23 156.66 0.00 0.00 0.00
                 
Annual Sum or Average 63.38 1.83 61.55 45.36 92.97 0.00 0.00 0.00
Minimum of Months 21.04 0.00 21.04 0.23 41.45 0.00 0.00 0.00
Maximum of Months 108.85 8.34 101.57 106.54 160.64 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.15 0.00 22.15 0.51 143.72 0.00 0.00 0.00
February 34.47 0.00 34.47 5.98 123.28 0.00 0.00 0.00
March 50.79 0.00 50.79 21.26 95.80 0.00 0.00 0.00
April 72.13 0.44 71.69 47.76 73.44 0.00 0.00 0.00
May 92.54 2.78 89.76 76.91 57.81 0.00 0.00 0.00
June 97.39 6.52 90.87 89.62 42.94 0.00 0.00 0.00
July 92.70 7.46 85.23 95.32 38.02 0.00 0.00 0.00
August 75.14 2.26 72.88 78.68 37.09 0.00 0.00 0.00
September 58.16 0.04 58.11 46.23 57.08 0.00 0.00 0.00
October 39.82 0.00 39.82 18.42 81.74 0.00 0.00 0.00
November 25.08 0.00 25.08 3.52 109.39 0.00 0.00 0.00
December 18.83 0.00 18.83 0.20 140.14 0.00 0.00 0.00
                 
Annual Sum or Average 56.71 1.64 55.07 40.58 83.18 0.00 0.00 0.00
Minimum of Months 18.83 0.00 18.83 0.20 37.09 0.00 0.00 0.00
Maximum of Months 97.39 7.46 90.87 95.32 143.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 323.71 192.57 131.14 279.68 417.99 0.00 0.00 0.00
February 498.14 309.07 189.07 494.83 362.26 0.00 0.00 0.00
March 528.43 279.38 249.05 554.50 301.73 0.00 0.00 0.00
April 558.37 239.64 318.74 620.54 246.97 0.00 0.00 0.00
May 520.24 158.60 361.63 587.10 202.34 0.00 0.00 0.00
June 470.70 125.98 344.72 542.86 154.54 0.00 0.00 0.00
July 511.39 185.68 325.71 645.52 137.25 0.00 0.00 0.00
August 545.19 250.51 294.68 708.59 130.99 0.00 0.00 0.00
September 604.68 330.72 273.96 742.66 186.22 0.00 0.00 0.00
October 546.98 334.88 212.10 614.27 255.66 0.00 0.00 0.00
November 327.35 187.38 139.97 309.64 330.12 0.00 0.00 0.00
December 342.61 221.56 121.05 329.29 416.29 0.00 0.00 0.00
                 
Annual Sum or Average 481.25 234.20 247.05 535.93 261.39 0.00 0.00 0.00
Minimum of Months 323.71 125.98 121.05 279.68 130.99 0.00 0.00 0.00
Maximum of Months 604.68 334.88 361.63 742.66 417.99 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.117461E+10 0.698752E+09 0.475859E+09 0.103531E+10 0.137583E+10
February 0.163263E+10 0.101296E+10 0.619672E+09 0.163551E+10 0.109329E+10
March 0.191745E+10 0.101376E+10 0.903689E+09 0.202315E+10 0.100594E+10
April 0.196075E+10 0.841503E+09 0.111925E+10 0.220628E+10 0.783345E+09
May 0.188772E+10 0.575512E+09 0.131221E+10 0.217907E+10 0.643170E+09
June 0.165286E+10 0.442373E+09 0.121049E+10 0.197142E+10 0.459488E+09
July 0.185562E+10 0.673775E+09 0.118184E+10 0.239484E+10 0.420782E+09
August 0.197825E+10 0.908995E+09 0.106925E+10 0.260659E+10 0.407567E+09
September 0.212334E+10 0.116132E+10 0.962015E+09 0.261469E+10 0.587313E+09
October 0.198477E+10 0.121515E+10 0.769624E+09 0.223666E+10 0.853468E+09
November 0.114951E+10 0.657987E+09 0.491521E+09 0.109962E+10 0.105455E+10
December 0.124317E+10 0.803942E+09 0.439232E+09 0.120097E+10 0.138314E+10
           
Annual Sum or Average 0.205607E+11 0.100060E+11 0.105547E+11 0.232041E+11 0.100679E+11
Minimum of Months 0.114951E+10 0.442373E+09 0.439232E+09 0.103531E+10 0.407567E+09
Maximum of Months 0.212334E+10 0.121515E+10 0.131221E+10 0.261469E+10 0.138314E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.330763E+10 0.196764E+10 0.133999E+10 0.287309E+10 0.399346E+10
February 0.459739E+10 0.285244E+10 0.174495E+10 0.454715E+10 0.320347E+10
March 0.539941E+10 0.285469E+10 0.254473E+10 0.562388E+10 0.300993E+10
April 0.552134E+10 0.236962E+10 0.315172E+10 0.612279E+10 0.237704E+10
May 0.531570E+10 0.162060E+10 0.369510E+10 0.603405E+10 0.197901E+10
June 0.465435E+10 0.124569E+10 0.340866E+10 0.543610E+10 0.145539E+10
July 0.522529E+10 0.189731E+10 0.332799E+10 0.663689E+10 0.133983E+10
August 0.557061E+10 0.255967E+10 0.301095E+10 0.724252E+10 0.130775E+10
September 0.597918E+10 0.327021E+10 0.270897E+10 0.728124E+10 0.182462E+10
October 0.558898E+10 0.342177E+10 0.216721E+10 0.622137E+10 0.260192E+10
November 0.323694E+10 0.185285E+10 0.138409E+10 0.304916E+10 0.311375E+10
December 0.350069E+10 0.226385E+10 0.123685E+10 0.333944E+10 0.402886E+10
           
Annual Sum or Average 0.578975E+11 0.281763E+11 0.297212E+11 0.644077E+11 0.302350E+11
Minimum of Months 0.323694E+10 0.124569E+10 0.123685E+10 0.287309E+10 0.130775E+10
Maximum of Months 0.597918E+10 0.342177E+10 0.369510E+10 0.728124E+10 0.402886E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.429680E+10 0.255608E+10 0.174072E+10 0.375454E+10 0.557344E+10
February 0.597227E+10 0.370548E+10 0.226679E+10 0.596913E+10 0.444792E+10
March 0.701415E+10 0.370840E+10 0.330575E+10 0.739163E+10 0.420547E+10
April 0.717253E+10 0.307827E+10 0.409427E+10 0.805084E+10 0.331971E+10
May 0.690540E+10 0.210526E+10 0.480014E+10 0.791870E+10 0.278832E+10
June 0.604627E+10 0.161823E+10 0.442804E+10 0.711635E+10 0.206252E+10
July 0.678795E+10 0.246471E+10 0.432325E+10 0.872319E+10 0.188029E+10
August 0.723654E+10 0.332516E+10 0.391139E+10 0.952185E+10 0.181956E+10
September 0.776730E+10 0.424819E+10 0.351911E+10 0.956819E+10 0.254569E+10
October 0.726041E+10 0.444508E+10 0.281533E+10 0.816943E+10 0.364785E+10
November 0.420497E+10 0.240696E+10 0.179801E+10 0.397460E+10 0.439378E+10
December 0.454760E+10 0.294087E+10 0.160674E+10 0.437221E+10 0.562460E+10
           
Annual Sum or Average 0.752122E+11 0.366027E+11 0.386095E+11 0.845307E+11 0.423092E+11
Minimum of Months 0.420497E+10 0.161823E+10 0.160674E+10 0.375454E+10 0.181956E+10
Maximum of Months 0.776730E+10 0.444508E+10 0.480014E+10 0.956819E+10 0.562460E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.232241E+09 0.138155E+09 94085984.75 0.208636E+09 0.273922E+09
February 0.322800E+09 0.200280E+09 0.122520E+09 0.327281E+09 0.217562E+09
March 0.379114E+09 0.200438E+09 0.178676E+09 0.403317E+09 0.200498E+09
April 0.387675E+09 0.166380E+09 0.221296E+09 0.435596E+09 0.157929E+09
May 0.373237E+09 0.113789E+09 0.259449E+09 0.426690E+09 0.129789E+09
June 0.326802E+09 87464675.02 0.239337E+09 0.385248E+09 91196169.23
July 0.366890E+09 0.133217E+09 0.233673E+09 0.471712E+09 80775145.47
August 0.391136E+09 0.179724E+09 0.211412E+09 0.517203E+09 75432498.34
September 0.419822E+09 0.229614E+09 0.190208E+09 0.521085E+09 0.113639E+09
October 0.392424E+09 0.240255E+09 0.152169E+09 0.445889E+09 0.167490E+09
November 0.227278E+09 0.130095E+09 97182520.67 0.221049E+09 0.207985E+09
December 0.245797E+09 0.158953E+09 86844037.59 0.241672E+09 0.272932E+09
           
Annual Sum or Average 0.406522E+10 0.197836E+10 0.208685E+10 0.460538E+10 0.198915E+10
Minimum of Months 0.227278E+09 87464675.02 86844037.59 0.208636E+09 75432498.34
Maximum of Months 0.419822E+09 0.240255E+09 0.259449E+09 0.521085E+09 0.273922E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.166731E+09 49599010.86 0.117132E+09 73089345.22 0.550425E+09
February 0.268637E+09 0.100850E+09 0.167787E+09 0.187275E+09 0.431360E+09
March 0.416644E+09 0.140864E+09 0.275781E+09 0.353452E+09 0.381314E+09
April 0.612687E+09 0.233947E+09 0.378739E+09 0.622559E+09 0.287817E+09
May 0.816233E+09 0.332303E+09 0.483930E+09 0.908215E+09 0.235180E+09
June 0.758024E+09 0.293758E+09 0.464266E+09 0.868221E+09 0.165176E+09
July 0.968308E+09 0.508828E+09 0.459480E+09 0.120157E+10 0.146690E+09
August 0.801373E+09 0.408746E+09 0.392627E+09 0.100807E+10 0.138805E+09
September 0.633602E+09 0.304787E+09 0.328815E+09 0.737440E+09 0.211857E+09
October 0.374415E+09 0.153917E+09 0.220498E+09 0.350388E+09 0.322065E+09
November 0.179442E+09 51011659.85 0.128430E+09 0.105295E+09 0.409876E+09
December 0.156513E+09 54332932.01 0.102180E+09 84869690.62 0.545439E+09
           
Annual Sum or Average 0.615261E+10 0.263294E+10 0.351966E+10 0.650044E+10 0.382600E+10
Minimum of Months 0.156513E+09 49599010.86 0.102180E+09 73089345.22 0.138805E+09
Maximum of Months 0.968308E+09 0.508828E+09 0.483930E+09 0.120157E+10 0.550425E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52368466.14 0.00 52368466.14 2875034.45 0.303469E+09
February 73600977.77 0.00 73600977.77 17802553.23 0.237172E+09
March 0.120069E+09 391.48 0.120069E+09 58841781.79 0.206523E+09
April 0.164999E+09 1015143.42 0.163984E+09 0.116669E+09 0.152903E+09
May 0.218743E+09 6567927.74 0.212175E+09 0.189263E+09 0.121650E+09
June 0.222782E+09 14903905.08 0.207878E+09 0.215417E+09 83609515.06
July 0.219114E+09 17639237.34 0.201475E+09 0.235931E+09 73757573.56
August 0.177614E+09 5334198.86 0.172280E+09 0.197301E+09 69752864.78
September 0.133037E+09 99658.47 0.132938E+09 0.114065E+09 0.112943E+09
October 94124964.10 0.00 94124964.10 51822607.15 0.172940E+09
November 57376818.73 0.00 57376818.73 11999165.57 0.222574E+09
December 44499694.93 0.00 44499694.93 1752338.36 0.296040E+09
           
Annual Sum or Average 0.157833E+10 45560462.39 0.153277E+10 0.121374E+10 0.205333E+10
Minimum of Months 44499694.93 0.00 44499694.93 1752338.36 69752864.78
Maximum of Months 0.222782E+09 17639237.34 0.212175E+09 0.235931E+09 0.303469E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.166731E+09 49599010.86 0.117132E+09 77627707.14 0.545544E+09
February 0.268637E+09 0.100850E+09 0.167787E+09 0.195809E+09 0.424938E+09
March 0.416644E+09 0.140864E+09 0.275781E+09 0.365134E+09 0.375441E+09
April 0.612687E+09 0.233947E+09 0.378739E+09 0.633261E+09 0.284227E+09
May 0.816233E+09 0.332303E+09 0.483930E+09 0.915144E+09 0.233328E+09
June 0.758024E+09 0.293758E+09 0.464266E+09 0.873428E+09 0.163909E+09
July 0.968308E+09 0.508828E+09 0.459480E+09 0.120729E+10 0.145249E+09
August 0.801373E+09 0.408746E+09 0.392627E+09 0.101547E+10 0.136769E+09
September 0.633602E+09 0.304787E+09 0.328815E+09 0.746953E+09 0.208131E+09
October 0.374415E+09 0.153917E+09 0.220498E+09 0.362234E+09 0.315918E+09
November 0.179442E+09 51011659.85 0.128430E+09 0.110769E+09 0.404988E+09
December 0.156513E+09 54332932.01 0.102180E+09 90341940.19 0.539743E+09
           
Annual Sum or Average 0.615261E+10 0.263294E+10 0.351966E+10 0.659346E+10 0.377818E+10
Minimum of Months 0.156513E+09 49599010.86 0.102180E+09 77627707.14 0.136769E+09
Maximum of Months 0.968308E+09 0.508828E+09 0.483930E+09 0.120729E+10 0.545544E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.185756E+09 0.110502E+09 75253821.84 0.167193E+09 0.207802E+09
February 0.258189E+09 0.160192E+09 97996810.64 0.259886E+09 0.174476E+09
March 0.303231E+09 0.160319E+09 0.142912E+09 0.316258E+09 0.174673E+09
April 0.310079E+09 0.133077E+09 0.177001E+09 0.340972E+09 0.142549E+09
May 0.298531E+09 91012766.08 0.207518E+09 0.335612E+09 0.118704E+09
June 0.261389E+09 69957827.29 0.191432E+09 0.301636E+09 86702668.08
July 0.293453E+09 0.106552E+09 0.186901E+09 0.372993E+09 77864247.90
August 0.312846E+09 0.143750E+09 0.169096E+09 0.408430E+09 74510772.35
September 0.335791E+09 0.183654E+09 0.152136E+09 0.410448E+09 0.107283E+09
October 0.313877E+09 0.192166E+09 0.121711E+09 0.348483E+09 0.153570E+09
November 0.181786E+09 0.104056E+09 77730558.02 0.174230E+09 0.168569E+09
December 0.196599E+09 0.127137E+09 69461416.07 0.192232E+09 0.212447E+09
           
Annual Sum or Average 0.325153E+10 0.158238E+10 0.166915E+10 0.362837E+10 0.169915E+10
Minimum of Months 0.181786E+09 69957827.29 69461416.07 0.167193E+09 74510772.35
Maximum of Months 0.335791E+09 0.192166E+09 0.207518E+09 0.410448E+09 0.212447E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 41900326.30 0.00 41900326.30 1555799.76 0.256393E+09
February 58888587.20 0.00 58888587.20 12777256.57 0.197670E+09
March 96068061.79 313.23 96067748.57 46404376.91 0.169845E+09
April 0.132017E+09 812222.38 0.131204E+09 96868844.55 0.123006E+09
May 0.175017E+09 5255038.69 0.169762E+09 0.159484E+09 95849072.38
June 0.178249E+09 11924704.54 0.166324E+09 0.181314E+09 64868075.65
July 0.175314E+09 14113260.42 0.161201E+09 0.201509E+09 55244769.76
August 0.142110E+09 4267924.75 0.137842E+09 0.169389E+09 51982203.16
September 0.106444E+09 79737.34 0.106364E+09 97742540.14 87309432.59
October 75309952.72 0.00 75309952.72 41899247.52 0.141372E+09
November 45907539.48 0.00 45907539.48 8279606.33 0.187801E+09
December 35604474.90 0.00 35604474.90 890258.19 0.250013E+09
           
Annual Sum or Average 0.126283E+10 36453201.35 0.122638E+10 0.101811E+10 0.168135E+10
Minimum of Months 35604474.90 0.00 35604474.90 890258.19 51982203.16
Maximum of Months 0.178249E+09 14113260.42 0.169762E+09 0.201509E+09 0.256393E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.156474E+09 39212816.39 0.117262E+09 55283314.80 0.544362E+09
February 0.260353E+09 92217704.15 0.168135E+09 0.168843E+09 0.423010E+09
March 0.431998E+09 0.156650E+09 0.275348E+09 0.360795E+09 0.369150E+09
April 0.645692E+09 0.267941E+09 0.377750E+09 0.653172E+09 0.276899E+09
May 0.710424E+09 0.247357E+09 0.463067E+09 0.763149E+09 0.228222E+09
June 0.822858E+09 0.358142E+09 0.464716E+09 0.950261E+09 0.158892E+09
July 0.792984E+09 0.356523E+09 0.436461E+09 0.960333E+09 0.134915E+09
August 0.778426E+09 0.389384E+09 0.389042E+09 0.969102E+09 0.129780E+09
September 0.557872E+09 0.257746E+09 0.300126E+09 0.624591E+09 0.202815E+09
October 0.376944E+09 0.161062E+09 0.215882E+09 0.347396E+09 0.314274E+09
November 0.178516E+09 50551984.52 0.127964E+09 99095637.53 0.403612E+09
December 0.150900E+09 48501623.07 0.102398E+09 69577649.94 0.535297E+09
           
Annual Sum or Average 0.586344E+10 0.242529E+10 0.343815E+10 0.602160E+10 0.372123E+10
Minimum of Months 0.150900E+09 39212816.39 0.102398E+09 55283314.80 0.129780E+09
Maximum of Months 0.822858E+09 0.389384E+09 0.464716E+09 0.969102E+09 0.544362E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.232241E+09 0.138155E+09 94085984.75 0.208560E+09 0.273534E+09
February 0.322800E+09 0.200280E+09 0.122520E+09 0.326652E+09 0.216962E+09
March 0.379114E+09 0.200438E+09 0.178676E+09 0.401113E+09 0.199878E+09
April 0.387675E+09 0.166380E+09 0.221296E+09 0.432248E+09 0.157300E+09
May 0.373237E+09 0.113789E+09 0.259449E+09 0.426162E+09 0.128018E+09
June 0.326802E+09 87464675.02 0.239337E+09 0.381921E+09 90386308.21
July 0.366890E+09 0.133217E+09 0.233673E+09 0.471703E+09 78554452.93
August 0.391136E+09 0.179724E+09 0.211412E+09 0.515551E+09 74245611.12
September 0.419822E+09 0.229614E+09 0.190208E+09 0.520596E+09 0.111658E+09
October 0.392424E+09 0.240255E+09 0.152169E+09 0.444368E+09 0.166664E+09
November 0.227278E+09 0.130095E+09 97182520.67 0.220715E+09 0.207622E+09
December 0.245797E+09 0.158953E+09 86844037.59 0.241559E+09 0.272468E+09
           
Annual Sum or Average 0.406522E+10 0.197836E+10 0.208685E+10 0.459115E+10 0.197729E+10
Minimum of Months 0.227278E+09 87464675.02 86844037.59 0.208560E+09 74245611.12
Maximum of Months 0.419822E+09 0.240255E+09 0.259449E+09 0.520596E+09 0.273534E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52368466.14 0.00 52368466.14 2782171.88 0.303300E+09
February 73600977.77 0.00 73600977.77 17464333.09 0.236683E+09
March 0.120069E+09 391.48 0.120069E+09 56868370.71 0.206172E+09
April 0.164999E+09 1015143.42 0.163984E+09 0.113304E+09 0.152951E+09
May 0.218743E+09 6567927.74 0.212175E+09 0.188429E+09 0.120109E+09
June 0.222782E+09 14903905.08 0.207878E+09 0.211441E+09 82955734.20
July 0.219114E+09 17639237.34 0.201475E+09 0.235871E+09 71768281.60
August 0.177614E+09 5334198.86 0.172280E+09 0.194927E+09 68567874.87
September 0.133037E+09 99658.47 0.132938E+09 0.113176E+09 0.111139E+09
October 94124964.10 0.00 94124964.10 50166541.52 0.172187E+09
November 57376818.73 0.00 57376818.73 11565950.73 0.222050E+09
December 44499694.93 0.00 44499694.93 1570125.44 0.295611E+09
           
Annual Sum or Average 0.157833E+10 45560462.39 0.153277E+10 0.119757E+10 0.204349E+10
Minimum of Months 44499694.93 0.00 44499694.93 1570125.44 68567874.87
Maximum of Months 0.222782E+09 17639237.34 0.212175E+09 0.235871E+09 0.303300E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.156474E+09 39212816.39 0.117262E+09 57483302.96 0.537409E+09
February 0.260353E+09 92217704.15 0.168135E+09 0.174689E+09 0.413418E+09
March 0.431998E+09 0.156650E+09 0.275348E+09 0.371615E+09 0.362487E+09
April 0.645692E+09 0.267941E+09 0.377750E+09 0.662599E+09 0.273097E+09
May 0.710424E+09 0.247357E+09 0.463067E+09 0.769235E+09 0.226242E+09
June 0.822858E+09 0.358142E+09 0.464716E+09 0.954437E+09 0.157712E+09
July 0.792984E+09 0.356523E+09 0.436461E+09 0.965527E+09 0.133443E+09
August 0.778426E+09 0.389384E+09 0.389042E+09 0.975621E+09 0.127815E+09
September 0.557872E+09 0.257746E+09 0.300126E+09 0.633227E+09 0.198823E+09
October 0.376944E+09 0.161062E+09 0.215882E+09 0.358334E+09 0.307484E+09
November 0.178516E+09 50551984.52 0.127964E+09 0.102985E+09 0.396949E+09
December 0.150900E+09 48501623.07 0.102398E+09 72573696.43 0.527048E+09
           
Annual Sum or Average 0.586344E+10 0.242529E+10 0.343815E+10 0.609832E+10 0.366193E+10
Minimum of Months 0.150900E+09 39212816.39 0.102398E+09 57483302.96 0.127815E+09
Maximum of Months 0.822858E+09 0.389384E+09 0.464716E+09 0.975621E+09 0.537409E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66321358.09 0.00 66321358.09 1909299.81 0.420466E+09
February 93210994.38 0.00 93210994.38 18580301.54 0.324677E+09
March 0.152060E+09 495.79 0.152060E+09 69604519.89 0.280676E+09
April 0.208961E+09 1285615.09 0.207675E+09 0.146645E+09 0.208946E+09
May 0.277024E+09 8317866.07 0.268706E+09 0.240307E+09 0.170731E+09
June 0.282139E+09 18874855.40 0.263264E+09 0.271594E+09 0.120939E+09
July 0.277494E+09 22338981.12 0.255155E+09 0.298024E+09 0.110107E+09
August 0.224937E+09 6755426.29 0.218182E+09 0.244932E+09 0.108540E+09
September 0.168483E+09 126211.16 0.168357E+09 0.140918E+09 0.163867E+09
October 0.119203E+09 0.00 0.119203E+09 59824641.38 0.241498E+09
November 72664120.65 0.00 72664120.65 12006188.11 0.307958E+09
December 56356055.86 0.00 56356055.86 901988.90 0.410736E+09
           
Annual Sum or Average 0.199885E+10 57699450.91 0.194115E+10 0.150525E+10 0.286914E+10
Minimum of Months 56356055.86 0.00 56356055.86 901988.90 0.108540E+09
Maximum of Months 0.282139E+09 22338981.12 0.268706E+09 0.298024E+09 0.420466E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 24448798.74 0.00 24448798.74 703846.97 0.155001E+09
February 34361432.09 0.00 34361432.09 6849468.50 0.119690E+09
March 56055618.56 182.77 56055435.79 25659108.13 0.103469E+09
April 77031535.71 473930.95 76557604.76 54059405.98 77026178.68
May 0.102122E+09 3066309.85 99056130.07 88587040.61 62938639.97
June 0.104008E+09 6958053.25 97050039.40 0.100121E+09 44583228.90
July 0.102296E+09 8235073.42 94060683.56 0.109864E+09 40589830.01
August 82921087.56 2490329.85 80430757.71 90291952.41 40012359.05
September 62109917.75 46526.66 62063391.09 51948292.58 60408161.38
October 43943282.55 0.00 43943282.55 22053839.96 89026232.31
November 26787003.65 0.00 26787003.65 4425978.07 0.113526E+09
December 20775175.71 0.00 20775175.71 332510.46 0.151414E+09
           
Annual Sum or Average 0.736860E+09 21270406.75 0.715590E+09 0.554896E+09 0.105768E+10
Minimum of Months 20775175.71 0.00 20775175.71 332510.46 40012359.05
Maximum of Months 0.104008E+09 8235073.42 99056130.07 0.109864E+09 0.155001E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.108363E+09 64462737.30 43900141.34 95268863.23 0.136629E+09
February 0.150617E+09 93449879.22 57167513.00 0.152205E+09 0.107017E+09
March 0.176893E+09 93523610.87 83369497.89 0.188976E+09 98671897.83
April 0.180888E+09 77632025.32 0.103256E+09 0.205110E+09 78237169.37
May 0.174151E+09 53093294.10 0.121058E+09 0.200987E+09 66514300.29
June 0.152484E+09 40810664.91 0.111674E+09 0.180825E+09 48410577.85
July 0.171189E+09 62158441.70 0.109031E+09 0.221400E+09 44211930.65
August 0.182502E+09 83858412.51 98643882.84 0.241493E+09 42692090.40
September 0.195887E+09 0.107137E+09 88750420.26 0.243835E+09 59618166.87
October 0.183104E+09 0.112102E+09 71001357.22 0.208615E+09 84250671.89
November 0.106047E+09 60701964.75 45344972.53 0.102255E+09 0.103865E+09
December 0.114688E+09 74166869.16 40521077.98 0.111803E+09 0.136358E+09
           
Annual Sum or Average 0.189681E+10 0.923097E+09 0.973717E+09 0.215277E+10 0.100648E+10
Minimum of Months 0.106047E+09 40810664.91 40521077.98 95268863.23 42692090.40
Maximum of Months 0.195887E+09 0.112102E+09 0.121058E+09 0.243835E+09 0.136629E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.294119E+09 0.174965E+09 0.119154E+09 0.258579E+09 0.370838E+09
February 0.408806E+09 0.253642E+09 0.155164E+09 0.413116E+09 0.290465E+09
March 0.480124E+09 0.253842E+09 0.226282E+09 0.512920E+09 0.267816E+09
April 0.490966E+09 0.210709E+09 0.280257E+09 0.556711E+09 0.212352E+09
May 0.472682E+09 0.144106E+09 0.328576E+09 0.545519E+09 0.180533E+09
June 0.413874E+09 0.110768E+09 0.303105E+09 0.490797E+09 0.131396E+09
July 0.464643E+09 0.168711E+09 0.295932E+09 0.600925E+09 0.120000E+09
August 0.495349E+09 0.227609E+09 0.267740E+09 0.655463E+09 0.115875E+09
September 0.531678E+09 0.290791E+09 0.240887E+09 0.661817E+09 0.161816E+09
October 0.496980E+09 0.304268E+09 0.192712E+09 0.566223E+09 0.228674E+09
November 0.287833E+09 0.164758E+09 0.123076E+09 0.277540E+09 0.281912E+09
December 0.311287E+09 0.201304E+09 0.109982E+09 0.303456E+09 0.370104E+09
           
Annual Sum or Average 0.514834E+10 0.250547E+10 0.264287E+10 0.584307E+10 0.273178E+10
Minimum of Months 0.287833E+09 0.110768E+09 0.109982E+09 0.258579E+09 0.115875E+09
Maximum of Months 0.531678E+09 0.304268E+09 0.328576E+09 0.661817E+09 0.370838E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.232241E+09 0.138155E+09 94085984.75 0.208814E+09 0.272162E+09
February 0.322800E+09 0.200280E+09 0.122520E+09 0.326757E+09 0.216071E+09
March 0.379114E+09 0.200438E+09 0.178676E+09 0.401953E+09 0.198896E+09
April 0.387675E+09 0.166380E+09 0.221296E+09 0.432802E+09 0.157086E+09
May 0.373237E+09 0.113789E+09 0.259449E+09 0.423112E+09 0.128901E+09
June 0.326802E+09 87464675.02 0.239337E+09 0.381647E+09 90351599.22
July 0.366890E+09 0.133217E+09 0.233673E+09 0.467684E+09 79984008.52
August 0.391136E+09 0.179724E+09 0.211412E+09 0.514101E+09 74119136.77
September 0.419822E+09 0.229614E+09 0.190208E+09 0.519155E+09 0.111943E+09
October 0.392424E+09 0.240255E+09 0.152169E+09 0.444589E+09 0.165189E+09
November 0.227278E+09 0.130095E+09 97182520.67 0.221156E+09 0.205807E+09
December 0.245797E+09 0.158953E+09 86844037.59 0.241822E+09 0.270522E+09
           
Annual Sum or Average 0.406522E+10 0.197836E+10 0.208685E+10 0.458359E+10 0.197103E+10
Minimum of Months 0.227278E+09 87464675.02 86844037.59 0.208814E+09 74119136.77
Maximum of Months 0.419822E+09 0.240255E+09 0.259449E+09 0.519155E+09 0.272162E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.166731E+09 49599010.86 0.117132E+09 73866539.92 0.545855E+09
February 0.268637E+09 0.100850E+09 0.167787E+09 0.187166E+09 0.427529E+09
March 0.416644E+09 0.140864E+09 0.275781E+09 0.352004E+09 0.377407E+09
April 0.612687E+09 0.233947E+09 0.378739E+09 0.617623E+09 0.285865E+09
May 0.816233E+09 0.332303E+09 0.483930E+09 0.900600E+09 0.233199E+09
June 0.758024E+09 0.293758E+09 0.464266E+09 0.860582E+09 0.163315E+09
July 0.968308E+09 0.508828E+09 0.459480E+09 0.119246E+10 0.144862E+09
August 0.801373E+09 0.408746E+09 0.392627E+09 0.100189E+10 0.136101E+09
September 0.633602E+09 0.304787E+09 0.328815E+09 0.733877E+09 0.208257E+09
October 0.374415E+09 0.153917E+09 0.220498E+09 0.349322E+09 0.316840E+09
November 0.179442E+09 51011659.85 0.128430E+09 0.106044E+09 0.404487E+09
December 0.156513E+09 54332932.01 0.102180E+09 85427923.75 0.538938E+09
           
Annual Sum or Average 0.615261E+10 0.263294E+10 0.351966E+10 0.646087E+10 0.378266E+10
Minimum of Months 0.156513E+09 49599010.86 0.102180E+09 73866539.92 0.136101E+09
Maximum of Months 0.968308E+09 0.508828E+09 0.483930E+09 0.119246E+10 0.545855E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52368466.14 0.00 52368466.14 3077966.81 0.300564E+09
February 73600977.77 0.00 73600977.77 18300827.45 0.234952E+09
March 0.120069E+09 391.48 0.120069E+09 59501450.19 0.204157E+09
April 0.164999E+09 1015143.42 0.163984E+09 0.116348E+09 0.151410E+09
May 0.218743E+09 6567927.74 0.212175E+09 0.187591E+09 0.120419E+09
June 0.222782E+09 14903905.08 0.207878E+09 0.213338E+09 82600487.15
July 0.219114E+09 17639237.34 0.201475E+09 0.233696E+09 72809956.40
August 0.177614E+09 5334198.86 0.172280E+09 0.196433E+09 68267822.21
September 0.133037E+09 99658.47 0.132938E+09 0.113907E+09 0.110819E+09
October 94124964.10 0.00 94124964.10 53052440.07 0.169535E+09
November 57376818.73 0.00 57376818.73 12556348.92 0.219338E+09
December 44499694.93 0.00 44499694.93 2039751.87 0.292086E+09
           
Annual Sum or Average 0.157833E+10 45560462.39 0.153277E+10 0.120984E+10 0.202696E+10
Minimum of Months 44499694.93 0.00 44499694.93 2039751.87 68267822.21
Maximum of Months 0.222782E+09 17639237.34 0.212175E+09 0.233696E+09 0.300564E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.166731E+09 49599010.86 0.117132E+09 78216517.65 0.541441E+09
February 0.268637E+09 0.100850E+09 0.167787E+09 0.196321E+09 0.421192E+09
March 0.416644E+09 0.140864E+09 0.275781E+09 0.364799E+09 0.371054E+09
April 0.612687E+09 0.233947E+09 0.378739E+09 0.629295E+09 0.281852E+09
May 0.816233E+09 0.332303E+09 0.483930E+09 0.907955E+09 0.231142E+09
June 0.758024E+09 0.293758E+09 0.464266E+09 0.865869E+09 0.161965E+09
July 0.968308E+09 0.508828E+09 0.459480E+09 0.119826E+10 0.143366E+09
August 0.801373E+09 0.408746E+09 0.392627E+09 0.100968E+10 0.133890E+09
September 0.633602E+09 0.304787E+09 0.328815E+09 0.744171E+09 0.203996E+09
October 0.374415E+09 0.153917E+09 0.220498E+09 0.362663E+09 0.309861E+09
November 0.179442E+09 51011659.85 0.128430E+09 0.111856E+09 0.399629E+09
December 0.156513E+09 54332932.01 0.102180E+09 91303342.48 0.533500E+09
           
Annual Sum or Average 0.615261E+10 0.263294E+10 0.351966E+10 0.656039E+10 0.373289E+10
Minimum of Months 0.156513E+09 49599010.86 0.102180E+09 78216517.65 0.133890E+09
Maximum of Months 0.968308E+09 0.508828E+09 0.483930E+09 0.119826E+10 0.541441E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.340604E+09 0.202618E+09 0.137986E+09 0.294105E+09 0.415268E+09
February 0.473418E+09 0.293730E+09 0.179688E+09 0.465710E+09 0.330155E+09
March 0.556007E+09 0.293962E+09 0.262045E+09 0.577355E+09 0.302779E+09
April 0.568563E+09 0.244012E+09 0.324552E+09 0.627598E+09 0.234700E+09
May 0.547388E+09 0.166882E+09 0.380507E+09 0.620770E+09 0.188740E+09
June 0.479286E+09 0.128275E+09 0.351011E+09 0.561797E+09 0.131357E+09
July 0.538079E+09 0.195375E+09 0.342704E+09 0.691661E+09 0.113774E+09
August 0.573638E+09 0.263582E+09 0.310056E+09 0.756522E+09 0.106486E+09
September 0.615709E+09 0.336751E+09 0.278959E+09 0.758219E+09 0.165026E+09
October 0.575528E+09 0.352358E+09 0.223170E+09 0.640534E+09 0.252291E+09
November 0.333325E+09 0.190797E+09 0.142527E+09 0.314121E+09 0.316208E+09
December 0.360485E+09 0.233120E+09 0.127365E+09 0.343439E+09 0.413417E+09
           
Annual Sum or Average 0.596203E+10 0.290146E+10 0.306057E+10 0.665183E+10 0.297020E+10
Minimum of Months 0.333325E+09 0.128275E+09 0.127365E+09 0.294105E+09 0.106486E+09
Maximum of Months 0.615709E+09 0.352358E+09 0.380507E+09 0.758219E+09 0.415268E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.366565E+09 0.00 0.366565E+09 3577324.80 0.267900E+10
February 0.515187E+09 0.00 0.515187E+09 63952774.15 0.208660E+10
March 0.840452E+09 2740.29 0.840450E+09 0.293688E+09 0.181902E+10
April 0.115495E+10 7105734.80 0.114784E+10 0.686272E+09 0.133635E+10
May 0.153114E+10 45973752.97 0.148517E+10 0.118780E+10 0.105663E+10
June 0.155941E+10 0.104323E+09 0.145509E+10 0.135962E+10 0.750649E+09
July 0.153374E+10 0.123470E+09 0.141027E+10 0.153341E+10 0.671359E+09
August 0.124325E+10 37337977.86 0.120591E+10 0.126643E+10 0.655939E+09
September 0.931226E+09 697582.85 0.930528E+09 0.701271E+09 0.998509E+09
October 0.658850E+09 0.00 0.658850E+09 0.256768E+09 0.156141E+10
November 0.401623E+09 0.00 0.401623E+09 36596906.24 0.202803E+10
December 0.311486E+09 0.00 0.311486E+09 1092167.38 0.262098E+10
           
Annual Sum or Average 0.110479E+11 0.318911E+09 0.107290E+11 0.739049E+10 0.182645E+11
Minimum of Months 0.311486E+09 0.00 0.311486E+09 1092167.38 0.655939E+09
Maximum of Months 0.155941E+10 0.123470E+09 0.148517E+10 0.153341E+10 0.267900E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.366565E+09 0.00 0.366565E+09 2234891.62 0.276547E+10
February 0.515187E+09 0.00 0.515187E+09 55961551.98 0.215421E+10
March 0.840452E+09 2740.29 0.840450E+09 0.271154E+09 0.187050E+10
April 0.115495E+10 7105734.80 0.114784E+10 0.658522E+09 0.137095E+10
May 0.153114E+10 45973752.97 0.148517E+10 0.115892E+10 0.108120E+10
June 0.155941E+10 0.104323E+09 0.145509E+10 0.133170E+10 0.768873E+09
July 0.153374E+10 0.123470E+09 0.141027E+10 0.150908E+10 0.688291E+09
August 0.124325E+10 37337977.86 0.120591E+10 0.124281E+10 0.674575E+09
September 0.931226E+09 697582.85 0.930528E+09 0.679986E+09 0.102524E+10
October 0.658850E+09 0.00 0.658850E+09 0.236803E+09 0.161062E+10
November 0.401623E+09 0.00 0.401623E+09 30766388.63 0.210046E+10
December 0.311486E+09 0.00 0.311486E+09 668539.84 0.270744E+10
           
Annual Sum or Average 0.110479E+11 0.318911E+09 0.107290E+11 0.717860E+10 0.188178E+11
Minimum of Months 0.311486E+09 0.00 0.311486E+09 668539.84 0.674575E+09
Maximum of Months 0.155941E+10 0.123470E+09 0.148517E+10 0.150908E+10 0.276547E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52368466.14 0.00 52368466.14 3483470.62 0.324334E+09
February 73600977.77 0.00 73600977.77 21062372.66 0.254898E+09
March 0.120069E+09 391.48 0.120069E+09 68424122.38 0.224810E+09
April 0.164999E+09 1015143.42 0.163984E+09 0.139142E+09 0.170233E+09
May 0.218743E+09 6567927.74 0.212175E+09 0.226951E+09 0.138266E+09
June 0.222782E+09 14903905.08 0.207878E+09 0.256990E+09 0.101948E+09
July 0.219114E+09 17639237.34 0.201475E+09 0.286812E+09 90636512.37
August 0.177614E+09 5334198.86 0.172280E+09 0.244988E+09 86994549.32
September 0.133037E+09 99658.47 0.132938E+09 0.149307E+09 0.120582E+09
October 94124964.10 0.00 94124964.10 64361884.09 0.188582E+09
November 57376818.73 0.00 57376818.73 16550896.51 0.240047E+09
December 44499694.93 0.00 44499694.93 2794605.86 0.316251E+09
           
Annual Sum or Average 0.157833E+10 45560462.39 0.153277E+10 0.148087E+10 0.225758E+10
Minimum of Months 44499694.93 0.00 44499694.93 2794605.86 86994549.32
Maximum of Months 0.222782E+09 17639237.34 0.212175E+09 0.286812E+09 0.324334E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.312927E+09 78420063.57 0.234506E+09 0.123431E+09 0.116537E+10
February 0.520668E+09 0.184422E+09 0.336246E+09 0.369724E+09 0.903027E+09
March 0.863935E+09 0.313278E+09 0.550657E+09 0.795185E+09 0.803266E+09
April 0.129129E+10 0.535845E+09 0.755447E+09 0.143218E+10 0.617354E+09
May 0.142075E+10 0.494678E+09 0.926068E+09 0.168431E+10 0.519812E+09
June 0.164560E+10 0.716233E+09 0.929366E+09 0.207891E+10 0.384861E+09
July 0.158586E+10 0.712996E+09 0.872859E+09 0.212080E+10 0.336451E+09
August 0.155674E+10 0.778713E+09 0.778028E+09 0.214069E+10 0.325225E+09
September 0.111566E+10 0.515455E+09 0.600209E+09 0.141072E+10 0.441259E+09
October 0.753835E+09 0.322102E+09 0.431733E+09 0.780559E+09 0.685022E+09
November 0.357007E+09 0.101097E+09 0.255910E+09 0.229850E+09 0.873775E+09
December 0.301778E+09 96996357.68 0.204782E+09 0.157589E+09 0.114545E+10
           
Annual Sum or Average 0.117260E+11 0.485024E+10 0.687581E+10 0.133240E+11 0.820087E+10
Minimum of Months 0.301778E+09 78420063.57 0.204782E+09 0.123431E+09 0.325225E+09
Maximum of Months 0.164560E+10 0.778713E+09 0.929366E+09 0.214069E+10 0.116537E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.232241E+09 0.138155E+09 94085984.75 0.213940E+09 0.294928E+09
February 0.322800E+09 0.200280E+09 0.122520E+09 0.339259E+09 0.233580E+09
March 0.379114E+09 0.200438E+09 0.178676E+09 0.423531E+09 0.217606E+09
April 0.387675E+09 0.166380E+09 0.221296E+09 0.464951E+09 0.174103E+09
May 0.373237E+09 0.113789E+09 0.259449E+09 0.467252E+09 0.144458E+09
June 0.326802E+09 87464675.02 0.239337E+09 0.428528E+09 0.108406E+09
July 0.366890E+09 0.133217E+09 0.233673E+09 0.524017E+09 95609740.63
August 0.391136E+09 0.179724E+09 0.211412E+09 0.568521E+09 90633864.32
September 0.419822E+09 0.229614E+09 0.190208E+09 0.564442E+09 0.119837E+09
October 0.392424E+09 0.240255E+09 0.152169E+09 0.470247E+09 0.183179E+09
November 0.227278E+09 0.130095E+09 97182520.67 0.231209E+09 0.226129E+09
December 0.245797E+09 0.158953E+09 86844037.59 0.249854E+09 0.293932E+09
           
Annual Sum or Average 0.406522E+10 0.197836E+10 0.208685E+10 0.494575E+10 0.218240E+10
Minimum of Months 0.227278E+09 87464675.02 86844037.59 0.213940E+09 90633864.32
Maximum of Months 0.419822E+09 0.240255E+09 0.259449E+09 0.568521E+09 0.294928E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66321358.09 0.00 66321358.09 1522850.89 0.430258E+09
February 93210994.38 0.00 93210994.38 16181341.93 0.333344E+09
March 0.152060E+09 495.79 0.152060E+09 63649488.56 0.286789E+09
April 0.208961E+09 1285615.09 0.207675E+09 0.138361E+09 0.212758E+09
May 0.277024E+09 8317866.07 0.268706E+09 0.230243E+09 0.173063E+09
June 0.282139E+09 18874855.40 0.263264E+09 0.259620E+09 0.124397E+09
July 0.277494E+09 22338981.12 0.255155E+09 0.285359E+09 0.113830E+09
August 0.224937E+09 6755426.29 0.218182E+09 0.235530E+09 0.111019E+09
September 0.168483E+09 126211.16 0.168357E+09 0.133928E+09 0.165356E+09
October 0.119203E+09 0.00 0.119203E+09 55135951.75 0.244688E+09
November 72664120.65 0.00 72664120.65 10189892.76 0.316913E+09
December 56356055.86 0.00 56356055.86 609528.60 0.419586E+09
           
Annual Sum or Average 0.199885E+10 57699450.91 0.194115E+10 0.143033E+10 0.293200E+10
Minimum of Months 56356055.86 0.00 56356055.86 609528.60 0.111019E+09
Maximum of Months 0.282139E+09 22338981.12 0.268706E+09 0.285359E+09 0.430258E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 59337970.38 0.00 59337970.38 1362500.46 0.384929E+09
February 83396229.85 0.00 83396229.85 14477507.94 0.298242E+09
March 0.136049E+09 443.59 0.136048E+09 56947438.58 0.256591E+09
April 0.186958E+09 1150244.69 0.185808E+09 0.123792E+09 0.190356E+09
May 0.247854E+09 7442026.29 0.240412E+09 0.205999E+09 0.154840E+09
June 0.252431E+09 16887404.64 0.235543E+09 0.232283E+09 0.111298E+09
July 0.248275E+09 19986771.05 0.228288E+09 0.255312E+09 0.101845E+09
August 0.201252E+09 6044105.50 0.195208E+09 0.210729E+09 99328938.44
September 0.150743E+09 112921.60 0.150630E+09 0.119826E+09 0.147944E+09
October 0.106652E+09 0.00 0.106652E+09 49330344.94 0.218924E+09
November 65012864.06 0.00 65012864.06 9116935.66 0.283533E+09
December 50421976.71 0.00 50421976.71 545347.54 0.375355E+09
           
Annual Sum or Average 0.178838E+10 51623917.35 0.173676E+10 0.127972E+10 0.262319E+10
Minimum of Months 50421976.71 0.00 50421976.71 545347.54 99328938.44
Maximum of Months 0.252431E+09 19986771.05 0.240412E+09 0.255312E+09 0.384929E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.867026E+09 0.515775E+09 0.351251E+09 0.749092E+09 0.111955E+10
February 0.120511E+10 0.747705E+09 0.457405E+09 0.119710E+10 0.876372E+09
March 0.141535E+10 0.748295E+09 0.667051E+09 0.148516E+10 0.808143E+09
April 0.144731E+10 0.621144E+09 0.826163E+09 0.160845E+10 0.640134E+09
May 0.139341E+10 0.424807E+09 0.968600E+09 0.157249E+10 0.541943E+09
June 0.122005E+10 0.326532E+09 0.893516E+09 0.140710E+10 0.400567E+09
July 0.136971E+10 0.497338E+09 0.872371E+09 0.172895E+10 0.367602E+09
August 0.146023E+10 0.670963E+09 0.789263E+09 0.189787E+10 0.350846E+09
September 0.156732E+10 0.857216E+09 0.710104E+09 0.192499E+10 0.482672E+09
October 0.146504E+10 0.896945E+09 0.568092E+09 0.164527E+10 0.684766E+09
November 0.848496E+09 0.485685E+09 0.362811E+09 0.802579E+09 0.855667E+09
December 0.917634E+09 0.593419E+09 0.324215E+09 0.881976E+09 0.111499E+10
           
Annual Sum or Average 0.151767E+11 0.738582E+10 0.779084E+10 0.169010E+11 0.824325E+10
Minimum of Months 0.848496E+09 0.326532E+09 0.324215E+09 0.749092E+09 0.350846E+09
Maximum of Months 0.156732E+10 0.896945E+09 0.968600E+09 0.192499E+10 0.111955E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 386.54 513.67 438.55 260.88 177.67 0.00 0.00
February 676.06 451.92 674.87 418.72 256.15 0.00 0.00
March 755.36 375.57 715.89 378.50 337.40 0.00 0.00
April 851.19 302.22 756.46 324.65 431.81 0.00 0.00
May 813.57 240.13 704.79 214.87 489.92 0.00 0.00
June 760.58 177.27 637.68 170.67 467.01 0.00 0.00
July 894.13 157.10 692.81 251.56 441.25 0.00 0.00
August 973.19 152.17 738.59 339.38 399.21 0.00 0.00
September 1008.76 226.59 819.19 448.04 371.15 0.00 0.00
October 835.07 318.65 741.03 453.68 287.34 0.00 0.00
November 424.24 406.85 443.48 253.85 189.63 0.00 0.00
December 448.39 516.41 464.15 300.16 163.99 0.00 0.00
               
Annual Sum or Average 735.80 319.25 651.97 317.29 334.69 0.00 0.00
Minimum of Months 386.54 152.17 438.55 170.67 163.99 0.00 0.00
Maximum of Months 1008.76 516.41 819.19 453.68 489.92 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1072.69 1490.99 1234.93 734.63 500.29 0.00 0.00
February 1879.61 1324.18 1900.38 1179.08 721.29 0.00 0.00
March 2099.72 1123.78 2015.91 1065.82 950.09 0.00 0.00
April 2362.19 917.07 2130.15 914.20 1215.94 0.00 0.00
May 2252.86 738.88 1984.66 605.06 1379.59 0.00 0.00
June 2097.26 561.49 1795.66 480.59 1315.07 0.00 0.00
July 2477.93 500.24 1950.90 708.37 1242.53 0.00 0.00
August 2704.05 488.26 2079.83 955.67 1124.16 0.00 0.00
September 2809.12 703.94 2306.78 1261.66 1045.13 0.00 0.00
October 2322.79 971.45 2086.69 1277.54 809.14 0.00 0.00
November 1176.37 1201.29 1248.82 714.83 533.99 0.00 0.00
December 1246.81 1504.20 1307.01 845.22 461.79 0.00 0.00
               
Annual Sum or Average 2042.35 958.75 1835.92 893.47 942.45 0.00 0.00
Minimum of Months 1072.69 488.26 1234.93 480.59 461.79 0.00 0.00
Maximum of Months 2809.12 1504.20 2306.78 1277.54 1379.59 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1401.79 2080.88 1604.24 954.33 649.91 0.00 0.00
February 2467.40 1838.59 2468.70 1531.69 937.00 0.00 0.00
March 2759.72 1570.14 2618.78 1384.56 1234.22 0.00 0.00
April 3106.03 1280.75 2767.18 1187.60 1579.58 0.00 0.00
May 2956.50 1041.04 2578.18 786.01 1792.17 0.00 0.00
June 2745.51 795.73 2332.66 624.32 1708.35 0.00 0.00
July 3256.87 702.02 2534.33 920.22 1614.12 0.00 0.00
August 3555.05 679.35 2701.82 1241.47 1460.35 0.00 0.00
September 3691.43 982.13 2996.64 1638.96 1357.68 0.00 0.00
October 3050.12 1361.95 2710.73 1659.60 1051.12 0.00 0.00
November 1533.41 1695.13 1622.29 928.61 693.68 0.00 0.00
December 1632.40 2099.99 1697.88 1097.99 599.89 0.00 0.00
               
Annual Sum or Average 2680.45 1341.61 2384.96 1160.66 1224.30 0.00 0.00
Minimum of Months 1401.79 679.35 1604.24 624.32 599.89 0.00 0.00
Maximum of Months 3691.43 2099.99 2996.64 1659.60 1792.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 97.21 299.80 148.96 70.10 78.86 0.00 0.00
February 205.91 261.46 244.48 124.48 120.00 0.00 0.00
March 279.92 214.60 297.10 127.43 169.67 0.00 0.00
April 406.69 170.42 385.94 154.45 231.50 0.00 0.00
May 497.30 135.17 444.10 166.55 277.55 0.00 0.00
June 482.86 98.18 418.53 147.08 271.45 0.00 0.00
July 624.10 84.29 498.51 239.71 258.79 0.00 0.00
August 569.10 79.62 445.23 219.71 225.52 0.00 0.00
September 484.66 124.69 406.41 206.17 200.24 0.00 0.00
October 295.06 180.54 286.30 147.17 139.14 0.00 0.00
November 121.98 234.45 156.91 69.87 87.04 0.00 0.00
December 114.80 298.43 150.21 79.63 70.57 0.00 0.00
               
Annual Sum or Average 349.19 181.42 324.01 146.22 177.78 0.00 0.00
Minimum of Months 97.21 79.62 148.96 69.87 70.57 0.00 0.00
Maximum of Months 624.10 299.80 498.51 239.71 277.55 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 26.83 313.76 81.80 18.52 63.28 0.00 0.00
February 85.21 270.60 141.47 41.69 99.78 0.00 0.00
March 156.57 215.55 200.39 52.59 147.79 0.00 0.00
April 288.42 167.74 300.03 90.65 209.38 0.00 0.00
May 411.22 131.42 386.42 126.52 259.90 0.00 0.00
June 418.50 93.91 378.40 119.08 259.31 0.00 0.00
July 537.49 80.43 443.33 196.56 246.77 0.00 0.00
August 451.89 76.21 365.51 154.60 210.91 0.00 0.00
September 331.54 123.23 295.77 117.63 178.15 0.00 0.00
October 153.29 181.22 174.93 57.47 117.47 0.00 0.00
November 45.67 240.42 91.37 19.68 71.68 0.00 0.00
December 31.95 309.61 75.05 20.29 54.76 0.00 0.00
               
Annual Sum or Average 245.91 183.26 245.15 84.93 160.21 0.00 0.00
Minimum of Months 26.83 76.21 75.05 18.52 54.76 0.00 0.00
Maximum of Months 537.49 313.76 443.33 196.56 259.90 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 62.42 77.58 69.35 41.26 28.10 0.00 0.00
February 107.43 72.12 106.72 66.22 40.51 0.00 0.00
March 118.08 65.22 113.21 59.86 53.36 0.00 0.00
April 131.55 55.00 119.63 51.34 68.29 0.00 0.00
May 125.30 44.32 111.46 33.98 77.48 0.00 0.00
June 116.37 33.45 100.84 26.99 73.85 0.00 0.00
July 139.26 29.07 109.56 39.78 69.78 0.00 0.00
August 152.49 27.82 116.80 53.67 63.13 0.00 0.00
September 158.35 41.39 129.55 70.85 58.69 0.00 0.00
October 130.11 57.34 117.19 71.75 45.44 0.00 0.00
November 67.22 65.03 70.13 40.14 29.99 0.00 0.00
December 71.77 79.32 73.40 47.47 25.93 0.00 0.00
               
Annual Sum or Average 115.05 53.88 103.11 50.18 52.93 0.00 0.00
Minimum of Months 62.42 27.82 69.35 26.99 25.93 0.00 0.00
Maximum of Months 158.35 79.32 129.55 71.75 77.48 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.58 95.73 15.64 0.00 15.64 0.00 0.00
February 5.28 81.71 24.34 0.00 24.34 0.00 0.00
March 17.33 63.41 35.87 0.00 35.87 0.00 0.00
April 37.37 47.46 50.93 0.31 50.62 0.00 0.00
May 59.54 35.79 65.34 1.96 63.38 0.00 0.00
June 69.95 25.03 68.77 4.60 64.17 0.00 0.00
July 75.23 20.63 65.45 5.27 60.19 0.00 0.00
August 63.24 19.41 53.06 1.59 51.46 0.00 0.00
September 37.71 33.68 41.07 0.03 41.04 0.00 0.00
October 15.64 52.78 28.12 0.00 28.12 0.00 0.00
November 3.19 72.45 17.71 0.00 17.71 0.00 0.00
December 0.33 93.34 13.29 0.00 13.29 0.00 0.00
               
Annual Sum or Average 32.28 53.32 40.04 1.16 38.89 0.00 0.00
Minimum of Months 0.33 19.41 13.29 0.00 13.29 0.00 0.00
Maximum of Months 75.23 95.73 68.77 5.27 64.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 91.30 298.16 145.13 66.22 78.91 0.00 0.00
February 199.50 259.22 241.05 120.91 120.15 0.00 0.00
March 282.41 210.40 302.83 133.32 169.51 0.00 0.00
April 415.94 164.69 398.68 167.56 231.11 0.00 0.00
May 442.43 131.40 404.59 134.84 269.76 0.00 0.00
June 512.47 94.68 443.54 171.92 271.63 0.00 0.00
July 533.26 78.30 433.05 182.85 250.20 0.00 0.00
August 552.68 74.54 436.66 212.48 224.18 0.00 0.00
September 440.38 119.89 377.20 188.02 189.17 0.00 0.00
October 294.14 178.09 287.25 149.83 137.41 0.00 0.00
November 120.16 232.59 156.56 69.69 86.86 0.00 0.00
December 110.32 295.73 148.11 77.45 70.65 0.00 0.00
               
Annual Sum or Average 333.58 177.75 314.84 139.64 175.20 0.00 0.00
Minimum of Months 91.30 74.54 145.13 66.22 70.65 0.00 0.00
Maximum of Months 552.68 298.16 443.54 212.48 271.63 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 18.70 310.08 77.97 14.64 63.33 0.00 0.00
February 74.64 263.93 138.04 38.12 99.92 0.00 0.00
March 156.35 208.69 206.12 58.49 147.63 0.00 0.00
April 296.77 161.79 312.77 103.76 209.00 0.00 0.00
May 356.73 128.49 346.91 94.80 252.11 0.00 0.00
June 449.17 92.22 403.41 143.92 259.49 0.00 0.00
July 447.70 75.77 377.87 139.70 238.18 0.00 0.00
August 436.61 72.90 356.94 147.37 209.57 0.00 0.00
September 286.12 117.74 266.55 99.48 167.08 0.00 0.00
October 149.93 176.51 175.88 60.13 115.74 0.00 0.00
November 41.72 236.34 91.01 19.50 71.51 0.00 0.00
December 23.89 303.36 72.95 18.11 54.85 0.00 0.00
               
Annual Sum or Average 229.02 178.58 235.98 78.35 157.63 0.00 0.00
Minimum of Months 18.70 72.90 72.95 14.64 54.85 0.00 0.00
Maximum of Months 449.17 310.08 403.41 147.37 259.49 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 117.37 388.61 184.16 89.39 94.77 0.00 0.00
February 232.17 335.97 283.98 143.47 140.50 0.00 0.00
March 294.86 277.49 323.00 129.69 193.31 0.00 0.00
April 370.93 222.02 369.54 111.92 257.62 0.00 0.00
May 399.54 177.51 383.06 77.88 305.18 0.00 0.00
June 399.86 130.57 367.48 68.45 299.03 0.00 0.00
July 456.57 114.83 379.19 97.61 281.58 0.00 0.00
August 458.68 113.30 368.02 119.74 248.28 0.00 0.00
September 423.31 171.46 369.66 153.59 216.07 0.00 0.00
October 316.43 236.80 314.83 155.45 159.37 0.00 0.00
November 145.02 303.59 190.33 86.98 103.35 0.00 0.00
December 141.48 384.95 187.84 102.85 84.99 0.00 0.00
               
Annual Sum or Average 313.44 237.63 310.15 111.22 198.93 0.00 0.00
Minimum of Months 117.37 113.30 184.16 68.45 84.99 0.00 0.00
Maximum of Months 458.68 388.61 383.06 155.45 305.18 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 97.74 297.61 148.96 70.10 78.86 0.00 0.00
February 205.84 259.44 244.48 124.48 120.00 0.00 0.00
March 278.92 212.59 297.10 127.43 169.67 0.00 0.00
April 403.68 169.32 385.94 154.45 231.50 0.00 0.00
May 493.07 134.05 444.10 166.55 277.55 0.00 0.00
June 478.49 97.10 418.53 147.08 271.45 0.00 0.00
July 619.16 83.28 498.51 239.71 258.79 0.00 0.00
August 565.61 78.09 445.23 219.71 225.52 0.00 0.00
September 482.53 122.64 406.41 206.17 200.24 0.00 0.00
October 294.29 177.85 286.30 147.17 139.14 0.00 0.00
November 122.46 231.67 156.91 69.87 87.04 0.00 0.00
December 115.34 295.37 150.21 79.63 70.57 0.00 0.00
               
Annual Sum or Average 347.31 179.54 324.01 146.22 177.78 0.00 0.00
Minimum of Months 97.74 78.09 148.96 69.87 70.57 0.00 0.00
Maximum of Months 619.16 297.61 498.51 239.71 277.55 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 27.24 311.26 81.80 18.52 63.28 0.00 0.00
February 85.76 268.26 141.47 41.69 99.78 0.00 0.00
March 156.68 213.02 200.39 52.59 147.79 0.00 0.00
April 286.73 166.21 300.03 90.65 209.38 0.00 0.00
May 407.92 130.14 386.42 126.52 259.90 0.00 0.00
June 414.83 92.82 378.40 119.08 259.31 0.00 0.00
July 533.33 79.41 443.33 196.56 246.77 0.00 0.00
August 449.41 74.58 365.51 154.60 210.91 0.00 0.00
September 330.38 120.79 295.77 117.63 178.15 0.00 0.00
October 153.92 177.70 174.93 57.47 117.47 0.00 0.00
November 46.40 237.20 91.37 19.68 71.68 0.00 0.00
December 32.56 305.95 75.05 20.29 54.76 0.00 0.00
               
Annual Sum or Average 244.78 181.03 245.15 84.93 160.21 0.00 0.00
Minimum of Months 27.24 74.58 75.05 18.52 54.76 0.00 0.00
Maximum of Months 533.33 311.26 443.33 196.56 259.90 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 109.81 155.04 127.17 75.65 51.52 0.00 0.00
February 192.51 136.47 195.69 121.42 74.28 0.00 0.00
March 215.56 113.04 207.59 109.75 97.84 0.00 0.00
April 242.13 90.55 219.35 94.14 125.21 0.00 0.00
May 231.77 70.47 204.37 62.31 142.06 0.00 0.00
June 216.74 50.68 184.91 49.49 135.42 0.00 0.00
July 258.24 42.48 200.90 72.94 127.95 0.00 0.00
August 282.45 39.76 214.17 98.41 115.76 0.00 0.00
September 292.52 63.67 237.54 129.92 107.62 0.00 0.00
October 239.15 94.19 214.88 131.56 83.32 0.00 0.00
November 121.19 121.99 128.60 73.61 54.99 0.00 0.00
December 128.23 154.35 134.59 87.04 47.55 0.00 0.00
               
Annual Sum or Average 210.93 94.18 189.05 92.00 97.05 0.00 0.00
Minimum of Months 109.81 39.76 127.17 49.49 47.55 0.00 0.00
Maximum of Months 292.52 155.04 237.54 131.56 142.06 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1.34 1000.22 136.86 0.00 136.86 0.00 0.00
February 26.44 862.52 212.96 0.00 212.96 0.00 0.00
March 109.65 679.15 313.79 0.00 313.79 0.00 0.00
April 264.77 515.57 445.58 2.74 442.84 0.00 0.00
May 443.48 394.50 571.66 17.16 554.50 0.00 0.00
June 524.55 289.60 601.63 40.25 561.38 0.00 0.00
July 572.51 250.66 572.63 46.10 526.53 0.00 0.00
August 472.83 244.90 464.18 13.94 450.24 0.00 0.00
September 270.55 385.23 359.27 0.27 359.00 0.00 0.00
October 95.87 582.96 245.99 0.00 245.99 0.00 0.00
November 14.12 782.42 154.95 0.00 154.95 0.00 0.00
December 0.41 978.56 116.30 0.00 116.30 0.00 0.00
               
Annual Sum or Average 234.35 579.16 350.33 10.11 340.21 0.00 0.00
Minimum of Months 0.41 244.90 116.30 0.00 116.30 0.00 0.00
Maximum of Months 572.51 1000.22 601.63 46.10 561.38 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.83 1032.51 136.86 0.00 136.86 0.00 0.00
February 23.13 890.46 212.96 0.00 212.96 0.00 0.00
March 101.24 698.36 313.79 0.00 313.79 0.00 0.00
April 254.06 528.92 445.58 2.74 442.84 0.00 0.00
May 432.69 403.67 571.66 17.16 554.50 0.00 0.00
June 513.77 296.63 601.63 40.25 561.38 0.00 0.00
July 563.42 256.98 572.63 46.10 526.53 0.00 0.00
August 464.01 251.86 464.18 13.94 450.24 0.00 0.00
September 262.34 395.54 359.27 0.27 359.00 0.00 0.00
October 88.41 601.34 245.99 0.00 245.99 0.00 0.00
November 11.87 810.36 154.95 0.00 154.95 0.00 0.00
December 0.25 1010.84 116.30 0.00 116.30 0.00 0.00
               
Annual Sum or Average 227.63 596.71 350.33 10.11 340.21 0.00 0.00
Minimum of Months 0.25 251.86 116.30 0.00 116.30 0.00 0.00
Maximum of Months 563.42 1032.51 601.63 46.10 561.38 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 109.82 648.86 223.09 80.86 142.23 0.00 0.00
February 288.30 561.72 379.08 159.02 220.06 0.00 0.00
March 475.63 460.15 508.93 191.80 317.13 0.00 0.00
April 781.03 366.46 711.41 271.31 440.10 0.00 0.00
May 885.71 297.31 751.47 229.63 521.84 0.00 0.00
June 1064.34 227.45 846.91 315.82 531.09 0.00 0.00
July 1092.52 193.12 810.88 322.53 488.35 0.00 0.00
August 1101.26 186.03 793.57 359.83 433.74 0.00 0.00
September 817.37 260.74 643.72 287.49 356.23 0.00 0.00
October 487.77 391.30 463.11 209.96 253.15 0.00 0.00
November 176.90 509.59 247.55 89.19 158.36 0.00 0.00
December 139.26 641.57 221.06 95.56 125.49 0.00 0.00
               
Annual Sum or Average 620.04 394.59 550.79 217.98 332.81 0.00 0.00
Minimum of Months 109.82 186.03 221.06 80.86 125.49 0.00 0.00
Maximum of Months 1101.26 648.86 846.91 359.83 531.09 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 256.79 698.38 370.63 192.57 178.06 0.00 0.00
February 488.49 604.31 571.15 309.07 262.08 0.00 0.00
March 595.10 500.18 636.00 279.38 356.62 0.00 0.00
April 721.03 401.84 711.12 240.58 470.54 0.00 0.00
May 746.38 321.17 716.21 164.49 551.72 0.00 0.00
June 727.27 240.10 676.94 139.77 537.16 0.00 0.00
July 841.68 212.07 707.69 201.49 506.20 0.00 0.00
August 872.80 207.12 704.31 255.29 449.02 0.00 0.00
September 839.79 306.31 727.83 330.81 397.03 0.00 0.00
October 647.89 423.36 631.31 334.88 296.43 0.00 0.00
November 304.54 549.22 380.47 187.38 193.09 0.00 0.00
December 307.99 691.35 382.47 221.56 160.91 0.00 0.00
               
Annual Sum or Average 613.11 428.79 601.34 237.67 363.67 0.00 0.00
Minimum of Months 256.79 207.12 370.63 139.77 160.91 0.00 0.00
Maximum of Months 872.80 698.38 727.83 334.88 551.72 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.103531E+10 0.137583E+10 0.117461E+10 0.698752E+09 0.475859E+09 0.00 0.00
February 0.163551E+10 0.109329E+10 0.163263E+10 0.101296E+10 0.619672E+09 0.00 0.00
March 0.202315E+10 0.100594E+10 0.191745E+10 0.101376E+10 0.903689E+09 0.00 0.00
April 0.220628E+10 0.783345E+09 0.196075E+10 0.841503E+09 0.111925E+10 0.00 0.00
May 0.217907E+10 0.643170E+09 0.188772E+10 0.575512E+09 0.131221E+10 0.00 0.00
June 0.197142E+10 0.459488E+09 0.165286E+10 0.442373E+09 0.121049E+10 0.00 0.00
July 0.239484E+10 0.420782E+09 0.185562E+10 0.673775E+09 0.118184E+10 0.00 0.00
August 0.260659E+10 0.407567E+09 0.197825E+10 0.908995E+09 0.106925E+10 0.00 0.00
September 0.261469E+10 0.587313E+09 0.212334E+10 0.116132E+10 0.962015E+09 0.00 0.00
October 0.223666E+10 0.853468E+09 0.198477E+10 0.121515E+10 0.769624E+09 0.00 0.00
November 0.109962E+10 0.105455E+10 0.114951E+10 0.657987E+09 0.491521E+09 0.00 0.00
December 0.120097E+10 0.138314E+10 0.124317E+10 0.803942E+09 0.439232E+09 0.00 0.00
               
Annual Sum or Average 0.232041E+11 0.100679E+11 0.205607E+11 0.100060E+11 0.105547E+11 0.00 0.00
Minimum of Months 0.103531E+10 0.407567E+09 0.114951E+10 0.442373E+09 0.439232E+09 0.00 0.00
Maximum of Months 0.261469E+10 0.138314E+10 0.212334E+10 0.121515E+10 0.131221E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.287309E+10 0.399346E+10 0.330763E+10 0.196764E+10 0.133999E+10 0.00 0.00
February 0.454715E+10 0.320347E+10 0.459739E+10 0.285244E+10 0.174495E+10 0.00 0.00
March 0.562388E+10 0.300993E+10 0.539941E+10 0.285469E+10 0.254473E+10 0.00 0.00
April 0.612279E+10 0.237704E+10 0.552134E+10 0.236962E+10 0.315172E+10 0.00 0.00
May 0.603405E+10 0.197901E+10 0.531570E+10 0.162060E+10 0.369510E+10 0.00 0.00
June 0.543610E+10 0.145539E+10 0.465435E+10 0.124569E+10 0.340866E+10 0.00 0.00
July 0.663689E+10 0.133983E+10 0.522529E+10 0.189731E+10 0.332799E+10 0.00 0.00
August 0.724252E+10 0.130775E+10 0.557061E+10 0.255967E+10 0.301095E+10 0.00 0.00
September 0.728124E+10 0.182462E+10 0.597918E+10 0.327021E+10 0.270897E+10 0.00 0.00
October 0.622137E+10 0.260192E+10 0.558898E+10 0.342177E+10 0.216721E+10 0.00 0.00
November 0.304916E+10 0.311375E+10 0.323694E+10 0.185285E+10 0.138409E+10 0.00 0.00
December 0.333944E+10 0.402886E+10 0.350069E+10 0.226385E+10 0.123685E+10 0.00 0.00
               
Annual Sum or Average 0.644077E+11 0.302350E+11 0.578975E+11 0.281763E+11 0.297212E+11 0.00 0.00
Minimum of Months 0.287309E+10 0.130775E+10 0.323694E+10 0.124569E+10 0.123685E+10 0.00 0.00
Maximum of Months 0.728124E+10 0.402886E+10 0.597918E+10 0.342177E+10 0.369510E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.375454E+10 0.557344E+10 0.429680E+10 0.255608E+10 0.174072E+10 0.00 0.00
February 0.596913E+10 0.444792E+10 0.597227E+10 0.370548E+10 0.226679E+10 0.00 0.00
March 0.739163E+10 0.420547E+10 0.701415E+10 0.370840E+10 0.330575E+10 0.00 0.00
April 0.805084E+10 0.331971E+10 0.717253E+10 0.307827E+10 0.409427E+10 0.00 0.00
May 0.791870E+10 0.278832E+10 0.690540E+10 0.210526E+10 0.480014E+10 0.00 0.00
June 0.711635E+10 0.206252E+10 0.604627E+10 0.161823E+10 0.442804E+10 0.00 0.00
July 0.872319E+10 0.188029E+10 0.678795E+10 0.246471E+10 0.432325E+10 0.00 0.00
August 0.952185E+10 0.181956E+10 0.723654E+10 0.332516E+10 0.391139E+10 0.00 0.00
September 0.956819E+10 0.254569E+10 0.776730E+10 0.424819E+10 0.351911E+10 0.00 0.00
October 0.816943E+10 0.364785E+10 0.726041E+10 0.444508E+10 0.281533E+10 0.00 0.00
November 0.397460E+10 0.439378E+10 0.420497E+10 0.240696E+10 0.179801E+10 0.00 0.00
December 0.437221E+10 0.562460E+10 0.454760E+10 0.294087E+10 0.160674E+10 0.00 0.00
               
Annual Sum or Average 0.845307E+11 0.423092E+11 0.752122E+11 0.366027E+11 0.386095E+11 0.00 0.00
Minimum of Months 0.375454E+10 0.181956E+10 0.420497E+10 0.161823E+10 0.160674E+10 0.00 0.00
Maximum of Months 0.956819E+10 0.562460E+10 0.776730E+10 0.444508E+10 0.480014E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.260365E+09 0.802986E+09 0.398972E+09 0.187754E+09 0.211218E+09 0.00 0.00
February 0.498148E+09 0.632514E+09 0.591438E+09 0.301130E+09 0.290308E+09 0.00 0.00
March 0.749730E+09 0.574773E+09 0.795758E+09 0.341302E+09 0.454457E+09 0.00 0.00
April 0.105413E+10 0.441720E+09 0.100036E+10 0.400327E+09 0.600035E+09 0.00 0.00
May 0.133197E+10 0.362032E+09 0.118947E+10 0.446091E+09 0.743379E+09 0.00 0.00
June 0.125157E+10 0.254473E+09 0.108483E+10 0.381223E+09 0.703603E+09 0.00 0.00
July 0.167158E+10 0.225769E+09 0.133520E+10 0.642045E+09 0.693153E+09 0.00 0.00
August 0.152428E+10 0.213249E+09 0.119251E+10 0.588470E+09 0.604039E+09 0.00 0.00
September 0.125623E+10 0.323205E+09 0.105342E+10 0.534400E+09 0.519023E+09 0.00 0.00
October 0.790287E+09 0.483565E+09 0.766839E+09 0.394173E+09 0.372666E+09 0.00 0.00
November 0.316177E+09 0.607695E+09 0.406719E+09 0.181107E+09 0.225612E+09 0.00 0.00
December 0.307480E+09 0.799309E+09 0.402310E+09 0.213286E+09 0.189024E+09 0.00 0.00
               
Annual Sum or Average 0.110120E+11 0.572129E+10 0.102178E+11 0.461131E+10 0.560652E+10 0.00 0.00
Minimum of Months 0.260365E+09 0.213249E+09 0.398972E+09 0.181107E+09 0.189024E+09 0.00 0.00
Maximum of Months 0.167158E+10 0.802986E+09 0.133520E+10 0.642045E+09 0.743379E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 71868377.36 0.840379E+09 0.219099E+09 49599010.86 0.169500E+09 0.00 0.00
February 0.206139E+09 0.654637E+09 0.342238E+09 0.100850E+09 0.241388E+09 0.00 0.00
March 0.419348E+09 0.577337E+09 0.536713E+09 0.140864E+09 0.395849E+09 0.00 0.00
April 0.747580E+09 0.434779E+09 0.777685E+09 0.234962E+09 0.542723E+09 0.00 0.00
May 0.110142E+10 0.351994E+09 0.103498E+10 0.338871E+09 0.696105E+09 0.00 0.00
June 0.108475E+10 0.243425E+09 0.980806E+09 0.308662E+09 0.672144E+09 0.00 0.00
July 0.143963E+10 0.215411E+09 0.118742E+10 0.526467E+09 0.660954E+09 0.00 0.00
August 0.121035E+10 0.204108E+09 0.978987E+09 0.414081E+09 0.564907E+09 0.00 0.00
September 0.859364E+09 0.319418E+09 0.766639E+09 0.304886E+09 0.461753E+09 0.00 0.00
October 0.410583E+09 0.485386E+09 0.468540E+09 0.153917E+09 0.314622E+09 0.00 0.00
November 0.118368E+09 0.623162E+09 0.236818E+09 51011659.85 0.185807E+09 0.00 0.00
December 85565422.92 0.829254E+09 0.201013E+09 54332932.01 0.146680E+09 0.00 0.00
               
Annual Sum or Average 0.775497E+10 0.577929E+10 0.773094E+10 0.267850E+10 0.505243E+10 0.00 0.00
Minimum of Months 71868377.36 0.204108E+09 0.201013E+09 49599010.86 0.146680E+09 0.00 0.00
Maximum of Months 0.143963E+10 0.840379E+09 0.118742E+10 0.526467E+09 0.696105E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.167193E+09 0.207802E+09 0.185756E+09 0.110502E+09 75253821.84 0.00 0.00
February 0.259886E+09 0.174476E+09 0.258189E+09 0.160192E+09 97996810.64 0.00 0.00
March 0.316258E+09 0.174673E+09 0.303231E+09 0.160319E+09 0.142912E+09 0.00 0.00
April 0.340972E+09 0.142549E+09 0.310079E+09 0.133077E+09 0.177001E+09 0.00 0.00
May 0.335612E+09 0.118704E+09 0.298531E+09 91012766.08 0.207518E+09 0.00 0.00
June 0.301636E+09 86702668.08 0.261389E+09 69957827.29 0.191432E+09 0.00 0.00
July 0.372993E+09 77864247.90 0.293453E+09 0.106552E+09 0.186901E+09 0.00 0.00
August 0.408430E+09 74510772.35 0.312846E+09 0.143750E+09 0.169096E+09 0.00 0.00
September 0.410448E+09 0.107283E+09 0.335791E+09 0.183654E+09 0.152136E+09 0.00 0.00
October 0.348483E+09 0.153570E+09 0.313877E+09 0.192166E+09 0.121711E+09 0.00 0.00
November 0.174230E+09 0.168569E+09 0.181786E+09 0.104056E+09 77730558.02 0.00 0.00
December 0.192232E+09 0.212447E+09 0.196599E+09 0.127137E+09 69461416.07 0.00 0.00
               
Annual Sum or Average 0.362837E+10 0.169915E+10 0.325153E+10 0.158238E+10 0.166915E+10 0.00 0.00
Minimum of Months 0.167193E+09 74510772.35 0.181786E+09 69957827.29 69461416.07 0.00 0.00
Maximum of Months 0.410448E+09 0.212447E+09 0.335791E+09 0.192166E+09 0.207518E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 1555799.76 0.256393E+09 41900326.30 0.00 41900326.30 0.00 0.00
February 12777256.57 0.197670E+09 58888587.20 0.00 58888587.20 0.00 0.00
March 46404376.91 0.169845E+09 96068061.79 313.23 96067748.57 0.00 0.00
April 96868844.55 0.123006E+09 0.132017E+09 812222.38 0.131204E+09 0.00 0.00
May 0.159484E+09 95849072.38 0.175017E+09 5255038.69 0.169762E+09 0.00 0.00
June 0.181314E+09 64868075.65 0.178249E+09 11924704.54 0.166324E+09 0.00 0.00
July 0.201509E+09 55244769.76 0.175314E+09 14113260.42 0.161201E+09 0.00 0.00
August 0.169389E+09 51982203.16 0.142110E+09 4267924.75 0.137842E+09 0.00 0.00
September 97742540.14 87309432.59 0.106444E+09 79737.34 0.106364E+09 0.00 0.00
October 41899247.52 0.141372E+09 75309952.72 0.00 75309952.72 0.00 0.00
November 8279606.33 0.187801E+09 45907539.48 0.00 45907539.48 0.00 0.00
December 890258.19 0.250013E+09 35604474.90 0.00 35604474.90 0.00 0.00
               
Annual Sum or Average 0.101811E+10 0.168135E+10 0.126283E+10 36453201.35 0.122638E+10 0.00 0.00
Minimum of Months 890258.19 51982203.16 35604474.90 0.00 35604474.90 0.00 0.00
Maximum of Months 0.201509E+09 0.256393E+09 0.178249E+09 14113260.42 0.169762E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.244543E+09 0.798595E+09 0.388716E+09 0.177368E+09 0.211348E+09 0.00 0.00
February 0.482629E+09 0.627107E+09 0.583153E+09 0.292498E+09 0.290655E+09 0.00 0.00
March 0.756406E+09 0.563526E+09 0.811112E+09 0.357088E+09 0.454024E+09 0.00 0.00
April 0.107811E+10 0.426887E+09 0.103337E+10 0.434321E+09 0.599046E+09 0.00 0.00
May 0.118501E+10 0.351938E+09 0.108366E+10 0.361145E+09 0.722516E+09 0.00 0.00
June 0.132832E+10 0.245416E+09 0.114966E+10 0.445607E+09 0.704053E+09 0.00 0.00
July 0.142827E+10 0.209706E+09 0.115987E+10 0.489740E+09 0.670134E+09 0.00 0.00
August 0.148029E+10 0.199659E+09 0.116956E+10 0.569108E+09 0.600453E+09 0.00 0.00
September 0.114148E+10 0.310763E+09 0.977694E+09 0.487360E+09 0.490334E+09 0.00 0.00
October 0.787829E+09 0.477002E+09 0.769368E+09 0.401318E+09 0.368051E+09 0.00 0.00
November 0.311443E+09 0.602866E+09 0.405794E+09 0.180647E+09 0.225147E+09 0.00 0.00
December 0.295468E+09 0.792096E+09 0.396697E+09 0.207455E+09 0.189242E+09 0.00 0.00
               
Annual Sum or Average 0.105198E+11 0.560556E+10 0.992866E+10 0.440365E+10 0.552500E+10 0.00 0.00
Minimum of Months 0.244543E+09 0.199659E+09 0.388716E+09 0.177368E+09 0.189242E+09 0.00 0.00
Maximum of Months 0.148029E+10 0.798595E+09 0.116956E+10 0.569108E+09 0.722516E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 50086460.34 0.830530E+09 0.208843E+09 39212816.39 0.169630E+09 0.00 0.00
February 0.180563E+09 0.638509E+09 0.333954E+09 92217704.15 0.241736E+09 0.00 0.00
March 0.418774E+09 0.558951E+09 0.552067E+09 0.156651E+09 0.395417E+09 0.00 0.00
April 0.769224E+09 0.419369E+09 0.810690E+09 0.268956E+09 0.541734E+09 0.00 0.00
May 0.955455E+09 0.344142E+09 0.929166E+09 0.253925E+09 0.675242E+09 0.00 0.00
June 0.116425E+10 0.239036E+09 0.104564E+10 0.373046E+09 0.672594E+09 0.00 0.00
July 0.119912E+10 0.202933E+09 0.101210E+10 0.374162E+09 0.637935E+09 0.00 0.00
August 0.116941E+10 0.195249E+09 0.956040E+09 0.394718E+09 0.561321E+09 0.00 0.00
September 0.741627E+09 0.305185E+09 0.690909E+09 0.257846E+09 0.433063E+09 0.00 0.00
October 0.401583E+09 0.472754E+09 0.471069E+09 0.161062E+09 0.310007E+09 0.00 0.00
November 0.108141E+09 0.612590E+09 0.235893E+09 50551984.52 0.185341E+09 0.00 0.00
December 63992017.26 0.812508E+09 0.195400E+09 48501623.07 0.146898E+09 0.00 0.00
               
Annual Sum or Average 0.722223E+10 0.563176E+10 0.744177E+10 0.247085E+10 0.497092E+10 0.00 0.00
Minimum of Months 50086460.34 0.195249E+09 0.195400E+09 39212816.39 0.146898E+09 0.00 0.00
Maximum of Months 0.119912E+10 0.830530E+09 0.104564E+10 0.394718E+09 0.675242E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.314373E+09 0.104084E+10 0.493252E+09 0.239428E+09 0.253824E+09 0.00 0.00
February 0.561674E+09 0.812771E+09 0.686996E+09 0.347092E+09 0.339904E+09 0.00 0.00
March 0.789756E+09 0.743228E+09 0.865133E+09 0.347366E+09 0.517766E+09 0.00 0.00
April 0.961448E+09 0.575484E+09 0.957846E+09 0.290101E+09 0.667746E+09 0.00 0.00
May 0.107012E+10 0.475435E+09 0.102598E+10 0.208584E+09 0.817395E+09 0.00 0.00
June 0.103644E+10 0.338437E+09 0.952505E+09 0.177412E+09 0.775093E+09 0.00 0.00
July 0.122288E+10 0.307571E+09 0.101562E+10 0.261443E+09 0.754179E+09 0.00 0.00
August 0.122852E+10 0.303456E+09 0.985709E+09 0.320713E+09 0.664996E+09 0.00 0.00
September 0.109723E+10 0.444421E+09 0.958159E+09 0.398101E+09 0.560058E+09 0.00 0.00
October 0.847519E+09 0.634252E+09 0.843231E+09 0.416370E+09 0.426860E+09 0.00 0.00
November 0.375884E+09 0.786917E+09 0.493331E+09 0.225460E+09 0.267872E+09 0.00 0.00
December 0.378932E+09 0.103105E+10 0.503106E+09 0.275471E+09 0.227635E+09 0.00 0.00
               
Annual Sum or Average 0.988477E+10 0.749387E+10 0.978087E+10 0.350754E+10 0.627333E+10 0.00 0.00
Minimum of Months 0.314373E+09 0.303456E+09 0.493252E+09 0.177412E+09 0.227635E+09 0.00 0.00
Maximum of Months 0.122852E+10 0.104084E+10 0.102598E+10 0.416370E+09 0.817395E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.261787E+09 0.797124E+09 0.398972E+09 0.187754E+09 0.211218E+09 0.00 0.00
February 0.497969E+09 0.627646E+09 0.591438E+09 0.301130E+09 0.290308E+09 0.00 0.00
March 0.747050E+09 0.569396E+09 0.795758E+09 0.341302E+09 0.454457E+09 0.00 0.00
April 0.104635E+10 0.438874E+09 0.100036E+10 0.400327E+09 0.600035E+09 0.00 0.00
May 0.132064E+10 0.359031E+09 0.118947E+10 0.446091E+09 0.743379E+09 0.00 0.00
June 0.124025E+10 0.251690E+09 0.108483E+10 0.381223E+09 0.703603E+09 0.00 0.00
July 0.165835E+10 0.223053E+09 0.133520E+10 0.642045E+09 0.693153E+09 0.00 0.00
August 0.151494E+10 0.209167E+09 0.119251E+10 0.588470E+09 0.604039E+09 0.00 0.00
September 0.125073E+10 0.317894E+09 0.105342E+10 0.534400E+09 0.519023E+09 0.00 0.00
October 0.788228E+09 0.476344E+09 0.766839E+09 0.394173E+09 0.372666E+09 0.00 0.00
November 0.317405E+09 0.600499E+09 0.406719E+09 0.181107E+09 0.225612E+09 0.00 0.00
December 0.308918E+09 0.791128E+09 0.402310E+09 0.213286E+09 0.189024E+09 0.00 0.00
               
Annual Sum or Average 0.109526E+11 0.566185E+10 0.102178E+11 0.461131E+10 0.560652E+10 0.00 0.00
Minimum of Months 0.261787E+09 0.209167E+09 0.398972E+09 0.181107E+09 0.189024E+09 0.00 0.00
Maximum of Months 0.165835E+10 0.797124E+09 0.133520E+10 0.642045E+09 0.743379E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 72968316.51 0.833679E+09 0.219099E+09 49599010.86 0.169500E+09 0.00 0.00
February 0.207463E+09 0.648985E+09 0.342238E+09 0.100850E+09 0.241388E+09 0.00 0.00
March 0.419651E+09 0.570563E+09 0.536713E+09 0.140864E+09 0.395849E+09 0.00 0.00
April 0.743196E+09 0.430816E+09 0.777685E+09 0.234962E+09 0.542723E+09 0.00 0.00
May 0.109256E+10 0.348580E+09 0.103498E+10 0.338871E+09 0.696105E+09 0.00 0.00
June 0.107524E+10 0.240595E+09 0.980806E+09 0.308662E+09 0.672144E+09 0.00 0.00
July 0.142846E+10 0.212680E+09 0.118742E+10 0.526467E+09 0.660954E+09 0.00 0.00
August 0.120369E+10 0.199743E+09 0.978987E+09 0.414081E+09 0.564907E+09 0.00 0.00
September 0.856357E+09 0.313095E+09 0.766639E+09 0.304886E+09 0.461753E+09 0.00 0.00
October 0.412262E+09 0.475943E+09 0.468540E+09 0.153917E+09 0.314622E+09 0.00 0.00
November 0.120272E+09 0.614827E+09 0.236818E+09 51011659.85 0.185807E+09 0.00 0.00
December 87202517.29 0.819445E+09 0.201013E+09 54332932.01 0.146680E+09 0.00 0.00
               
Annual Sum or Average 0.771933E+10 0.570895E+10 0.773094E+10 0.267850E+10 0.505243E+10 0.00 0.00
Minimum of Months 72968316.51 0.199743E+09 0.201013E+09 49599010.86 0.146680E+09 0.00 0.00
Maximum of Months 0.142846E+10 0.833679E+09 0.118742E+10 0.526467E+09 0.696105E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.294105E+09 0.415268E+09 0.340604E+09 0.202618E+09 0.137986E+09 0.00 0.00
February 0.465710E+09 0.330155E+09 0.473418E+09 0.293730E+09 0.179688E+09 0.00 0.00
March 0.577355E+09 0.302779E+09 0.556007E+09 0.293962E+09 0.262045E+09 0.00 0.00
April 0.627598E+09 0.234700E+09 0.568563E+09 0.244012E+09 0.324552E+09 0.00 0.00
May 0.620770E+09 0.188740E+09 0.547388E+09 0.166882E+09 0.380507E+09 0.00 0.00
June 0.561797E+09 0.131357E+09 0.479286E+09 0.128275E+09 0.351011E+09 0.00 0.00
July 0.691661E+09 0.113774E+09 0.538079E+09 0.195375E+09 0.342704E+09 0.00 0.00
August 0.756522E+09 0.106486E+09 0.573638E+09 0.263582E+09 0.310056E+09 0.00 0.00
September 0.758219E+09 0.165026E+09 0.615709E+09 0.336751E+09 0.278959E+09 0.00 0.00
October 0.640534E+09 0.252291E+09 0.575528E+09 0.352358E+09 0.223170E+09 0.00 0.00
November 0.314121E+09 0.316208E+09 0.333325E+09 0.190797E+09 0.142527E+09 0.00 0.00
December 0.343439E+09 0.413417E+09 0.360485E+09 0.233120E+09 0.127365E+09 0.00 0.00
               
Annual Sum or Average 0.665183E+10 0.297020E+10 0.596203E+10 0.290146E+10 0.306057E+10 0.00 0.00
Minimum of Months 0.294105E+09 0.106486E+09 0.333325E+09 0.128275E+09 0.127365E+09 0.00 0.00
Maximum of Months 0.758219E+09 0.415268E+09 0.615709E+09 0.352358E+09 0.380507E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 3577324.80 0.267900E+10 0.366565E+09 0.00 0.366565E+09 0.00 0.00
February 63952774.15 0.208660E+10 0.515187E+09 0.00 0.515187E+09 0.00 0.00
March 0.293688E+09 0.181902E+10 0.840452E+09 2740.29 0.840450E+09 0.00 0.00
April 0.686272E+09 0.133635E+10 0.115495E+10 7105734.80 0.114784E+10 0.00 0.00
May 0.118780E+10 0.105663E+10 0.153114E+10 45973752.97 0.148517E+10 0.00 0.00
June 0.135962E+10 0.750649E+09 0.155941E+10 0.104323E+09 0.145509E+10 0.00 0.00
July 0.153341E+10 0.671359E+09 0.153374E+10 0.123470E+09 0.141027E+10 0.00 0.00
August 0.126643E+10 0.655939E+09 0.124325E+10 37337977.86 0.120591E+10 0.00 0.00
September 0.701271E+09 0.998509E+09 0.931226E+09 697582.85 0.930528E+09 0.00 0.00
October 0.256768E+09 0.156141E+10 0.658850E+09 0.00 0.658850E+09 0.00 0.00
November 36596906.24 0.202803E+10 0.401623E+09 0.00 0.401623E+09 0.00 0.00
December 1092167.38 0.262098E+10 0.311486E+09 0.00 0.311486E+09 0.00 0.00
               
Annual Sum or Average 0.739049E+10 0.182645E+11 0.110479E+11 0.318911E+09 0.107290E+11 0.00 0.00
Minimum of Months 1092167.38 0.655939E+09 0.311486E+09 0.00 0.311486E+09 0.00 0.00
Maximum of Months 0.153341E+10 0.267900E+10 0.155941E+10 0.123470E+09 0.148517E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 2234891.62 0.276547E+10 0.366565E+09 0.00 0.366565E+09 0.00 0.00
February 55961551.98 0.215421E+10 0.515187E+09 0.00 0.515187E+09 0.00 0.00
March 0.271154E+09 0.187050E+10 0.840452E+09 2740.29 0.840450E+09 0.00 0.00
April 0.658522E+09 0.137095E+10 0.115495E+10 7105734.80 0.114784E+10 0.00 0.00
May 0.115892E+10 0.108120E+10 0.153114E+10 45973752.97 0.148517E+10 0.00 0.00
June 0.133170E+10 0.768873E+09 0.155941E+10 0.104323E+09 0.145509E+10 0.00 0.00
July 0.150908E+10 0.688291E+09 0.153374E+10 0.123470E+09 0.141027E+10 0.00 0.00
August 0.124281E+10 0.674575E+09 0.124325E+10 37337977.86 0.120591E+10 0.00 0.00
September 0.679986E+09 0.102524E+10 0.931226E+09 697582.85 0.930528E+09 0.00 0.00
October 0.236803E+09 0.161062E+10 0.658850E+09 0.00 0.658850E+09 0.00 0.00
November 30766388.63 0.210046E+10 0.401623E+09 0.00 0.401623E+09 0.00 0.00
December 668539.84 0.270744E+10 0.311486E+09 0.00 0.311486E+09 0.00 0.00
               
Annual Sum or Average 0.717860E+10 0.188178E+11 0.110479E+11 0.318911E+09 0.107290E+11 0.00 0.00
Minimum of Months 668539.84 0.674575E+09 0.311486E+09 0.00 0.311486E+09 0.00 0.00
Maximum of Months 0.150908E+10 0.276547E+10 0.155941E+10 0.123470E+09 0.148517E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.294135E+09 0.173791E+10 0.597536E+09 0.216575E+09 0.380961E+09 0.00 0.00
February 0.697456E+09 0.135892E+10 0.917070E+09 0.384702E+09 0.532367E+09 0.00 0.00
March 0.127394E+10 0.123248E+10 0.136312E+10 0.513717E+09 0.849402E+09 0.00 0.00
April 0.202444E+10 0.949860E+09 0.184397E+10 0.703239E+09 0.114073E+10 0.00 0.00
May 0.237228E+10 0.796308E+09 0.201273E+10 0.615035E+09 0.139769E+10 0.00 0.00
June 0.275877E+10 0.589557E+09 0.219518E+10 0.818602E+09 0.137658E+10 0.00 0.00
July 0.292619E+10 0.517257E+09 0.217186E+10 0.863852E+09 0.130801E+10 0.00 0.00
August 0.294962E+10 0.498270E+09 0.212549E+10 0.963771E+09 0.116172E+10 0.00 0.00
September 0.211863E+10 0.675836E+09 0.166852E+10 0.745168E+09 0.923355E+09 0.00 0.00
October 0.130645E+10 0.104806E+10 0.124038E+10 0.562357E+09 0.678027E+09 0.00 0.00
November 0.458527E+09 0.132087E+10 0.641662E+09 0.231192E+09 0.410470E+09 0.00 0.00
December 0.372997E+09 0.171839E+10 0.592075E+09 0.255949E+09 0.336126E+09 0.00 0.00
               
Annual Sum or Average 0.195534E+11 0.124437E+11 0.173696E+11 0.687416E+10 0.104954E+11 0.00 0.00
Minimum of Months 0.294135E+09 0.498270E+09 0.592075E+09 0.216575E+09 0.336126E+09 0.00 0.00
Maximum of Months 0.294962E+10 0.173791E+10 0.219518E+10 0.963771E+09 0.139769E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.687792E+09 0.187055E+10 0.992685E+09 0.515775E+09 0.476910E+09 0.00 0.00
February 0.118176E+10 0.146196E+10 0.138172E+10 0.747705E+09 0.634012E+09 0.00 0.00
March 0.159393E+10 0.133969E+10 0.170345E+10 0.748296E+09 0.955158E+09 0.00 0.00
April 0.186892E+10 0.104156E+10 0.184323E+10 0.623580E+09 0.121965E+10 0.00 0.00
May 0.199911E+10 0.860229E+09 0.191828E+10 0.440567E+09 0.147772E+10 0.00 0.00
June 0.188508E+10 0.622338E+09 0.175462E+10 0.362294E+09 0.139232E+10 0.00 0.00
July 0.225436E+10 0.568015E+09 0.189548E+10 0.539664E+09 0.135581E+10 0.00 0.00
August 0.233770E+10 0.554758E+09 0.188641E+10 0.683762E+09 0.120265E+10 0.00 0.00
September 0.217673E+10 0.793967E+09 0.188655E+10 0.857456E+09 0.102909E+10 0.00 0.00
October 0.173530E+10 0.113393E+10 0.169089E+10 0.896945E+09 0.793947E+09 0.00 0.00
November 0.789361E+09 0.142359E+10 0.986173E+09 0.485685E+09 0.500488E+09 0.00 0.00
December 0.824922E+09 0.185172E+10 0.102441E+10 0.593419E+09 0.430993E+09 0.00 0.00
               
Annual Sum or Average 0.193350E+11 0.135223E+11 0.189639E+11 0.749515E+10 0.114688E+11 0.00 0.00
Minimum of Months 0.687792E+09 0.554758E+09 0.986173E+09 0.362294E+09 0.430993E+09 0.00 0.00
Maximum of Months 0.233770E+10 0.187055E+10 0.191828E+10 0.896945E+09 0.147772E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 4.50 3.10 1.22 3.91 -4.2 29.50 44.23 0.00
February 5.82 4.07 1.77 3.94 -3.8 43.80 82.64 0.00
March 8.33 5.86 2.94 3.85 -1.4 65.55 100.60 0.02
April 10.85 8.04 5.25 4.23 1.22 89.73 150.02 0.00
May 12.97 10.02 7.49 3.85 3.75 114.98 168.60 0.00
June 15.59 11.80 8.88 4.02 5.93 107.53 199.74 0.01
July 17.66 13.41 10.38 3.76 8.02 92.25 247.81 0.00
August 18.80 14.57 11.86 3.84 8.90 79.20 215.47 0.01
September 15.09 12.55 10.74 2.23 5.47 68.06 162.11 0.01
October 11.43 9.19 7.19 4.02 2.10 48.18 106.36 0.04
November 8.07 6.72 5.29 3.86 0.13 33.26 46.10 0.00
December 5.42 4.09 2.46 3.51 -3.8 24.03 50.49 0.04
                 
Annual Sum or Average 11.24 8.64 6.31 3.75 1.89 66.43 131.49 0.01
Minimum of Months 4.50 3.10 1.22 2.23 -4.2 24.03 44.23 0.00
Maximum of Months 18.80 14.57 11.86 4.23 8.90 114.98 247.81 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.40 11-JAN-14:20 10.49 7.20 8.40 3.89 99.17 130.33
February 20.00 27-FEB-14:00 12.17 5.60 2.60 5.54 87.00 691.00
March 20.60 18-MAR-15:00 10.43 0.00 6.20 6.55 111.50 465.50
April 27.20 27-APR-15:09 17.22 11.02 4.10 12.63 151.33 598.33
May 25.00 05-MAY-15:00 17.36 12.80 2.60 18.99 208.50 29.50
June 26.70 28-JUN-16:00 16.74 10.60 3.10 11.84 131.50 527.00
July 30.60 24-JUL-14:00 18.78 12.20 3.10 20.75 267.00 383.50
August 31.80 10-AUG-16:00 18.70 11.10 2.60 16.85 50.50 750.50
September 25.00 14-SEP-16:00 16.69 11.70 3.10 13.54 100.50 235.00
October 21.70 04-OCT-14:00 11.49 1.70 5.20 4.92 56.50 783.50
November 21.10 04-NOV-13:00 15.94 12.80 0.00 6.95 52.50 729.00
December 13.30 14-DEC-11:00 8.44 3.60 13.90 5.33 127.50 85.00
                 
Annual Sum or Average                
Minimum of Months 13.30   8.44 0.00 0.00 3.89 50.50 29.50
Maximum of Months 31.80   18.78 12.80 13.90 20.75 267.00 783.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -3.9 07-JAN-07:00 -3.9 -3.9 2.10 -14.4 0.00 0.00
February -5.6 19-FEB-05:10 -6.1 -7.3 3.77 -22.8 0.00 0.00
March -0.6 01-MAR-06:00 -2.0 -3.9 1.50 -17.3 16.50 102.00
April 1.70 19-APR-04:00 1.21 0.60 3.10 -11.9 0.00 0.00
May 4.40 11-MAY-02:00 3.92 3.30 3.10 -10.9 0.00 0.00
June 8.30 15-JUN-02:00 7.50 6.70 3.10 -3.2 0.00 0.00
July 11.10 03-JUL-03:00 8.19 5.00 2.60 5.54 0.00 0.00
August 11.00 06-AUG-04:00 10.57 10.20 2.60 -3.2 11.00 135.50
September 7.20 27-SEP-04:49 6.72 6.20 0.25 -4.0 0.00 0.00
October 5.60 13-OCT-04:00 4.51 3.30 2.10 -8.5 0.00 0.00
November 0.00 11-NOV-06:00 -0.2 -0.6 2.10 -16.0 0.00 0.00
December -1.7 26-DEC-06:00 -1.7 -1.7 2.10 -15.7 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -5.6   -6.1 -7.3 0.25 -22.8 0.00 0.00
Maximum of Months 11.10   10.57 10.20 3.77 5.54 16.50 135.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.49 11-JAN-13:00 14.40 7.20 8.20 2.85 105.50 249.00
February 12.42 27-FEB-15:00 19.40 6.70 2.60 6.35 88.00 342.50
March 12.45 09-MAR-11:00 17.20 8.90 2.10 12.41 178.00 40.00
April 17.29 27-APR-14:00 27.20 11.10 4.10 12.41 147.50 646.00
May 17.58 06-MAY-12:00 23.90 13.90 5.20 15.57 365.50 282.50
June 16.74 28-JUN-16:00 26.70 10.60 3.10 11.84 131.50 527.00
July 19.18 31-JUL-15:00 28.90 13.90 4.10 14.65 45.00 848.50
August 20.13 29-AUG-12:00 28.90 15.70 2.60 17.39 136.50 655.00
September 17.97 23-SEP-13:00 23.30 15.00 2.10 9.72 148.00 670.50
October 15.15 01-OCT-11:00 17.20 13.90 4.60 13.73 236.50 63.50
November 16.05 04-NOV-12:00 20.60 13.30 0.00 7.95 62.00 746.50
December 10.71 16-DEC-11:00 11.70 10.00 6.70 7.35 89.50 0.00
                 
Annual Sum or Average                
Minimum of Months 10.49   11.70 6.70 0.00 2.85 45.00 0.00
Maximum of Months 20.13   28.90 15.70 8.20 17.39 365.50 848.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.00 11-JAN-21:00 11.10 10.49 4.60 6.75 0.00 0.00
February 11.70 24-FEB-00:00 12.80 12.15 4.10 8.74 0.00 0.00
March 11.70 09-MAR-16:00 12.80 12.15 2.10 8.74 37.50 0.00
April 12.80 28-APR-12:00 16.70 14.35 4.10 8.35 265.50 596.00
May 13.90 05-MAY-16:00 22.80 17.10 2.60 19.17 111.50 27.50
June 13.90 12-JUN-12:00 16.70 15.00 3.60 13.16 263.50 0.00
July 15.00 11-JUL-09:20 16.13 15.49 4.60 12.91 204.17 28.17
August 16.40 30-AUG-07:00 17.40 16.77 5.20 12.41 168.50 34.50
September 15.00 14-SEP-11:20 20.37 16.93 2.10 6.89 152.83 748.17
October 13.90 01-OCT-10:00 16.70 15.01 4.10 13.16 184.50 0.00
November 13.90 03-NOV-19:00 15.00 14.31 4.60 11.46 0.00 0.00
December 10.00 16-DEC-10:00 11.10 10.48 7.70 6.75 81.00 0.00
                 
Annual Sum or Average                
Minimum of Months 10.00   11.10 10.48 2.10 6.75 0.00 0.00
Maximum of Months 16.40   22.80 17.10 7.70 19.17 265.50 748.17



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 11.48 8.35 0.00
February 18.00 13.00 16.00 11.14 14.81 0.00
March 18.00 13.00 16.00 11.69 23.26 0.00
April 18.00 13.00 16.00 12.99 36.00 0.00
May 18.00 13.00 16.00 14.72 45.46 0.00
June 18.00 13.00 16.00 16.40 49.26 0.00
July 18.00 13.00 16.00 17.58 51.50 0.00
August 18.00 13.00 16.00 17.95 42.11 0.00
September 18.00 13.00 16.00 17.39 30.76 0.00
October 18.00 13.00 16.00 16.06 18.91 0.00
November 18.00 13.00 16.00 14.32 9.65 0.00
December 18.00 13.00 16.00 12.65 7.39 0.00
             
Annual Sum or Average 18.00 13.00 16.00 14.55 28.19 0.00
Minimum of Months 18.00 13.00 16.00 11.14 7.39 0.00
Maximum of Months 18.00 13.00 16.00 17.95 51.50 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770454E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -161747520.4 81.21 0.00 0.00
February 0.696210E+10 -0.681598E+10 0.00 0.00 672.00 0.00 -146125333.0 81.21 0.00 0.00
March 0.770293E+10 -0.754145E+10 0.00 0.00 744.00 0.00 -161481800.9 81.21 0.00 0.00
April 0.746488E+10 -0.730858E+10 0.00 0.00 720.00 0.00 -156303825.7 81.21 0.00 0.00
May 0.770436E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -161576234.4 81.21 0.00 0.00
June 0.745695E+10 -0.730053E+10 0.00 0.00 720.00 0.00 -156422948.1 81.21 0.00 0.00
July 0.771243E+10 -0.755084E+10 0.00 0.00 744.00 0.00 -161584127.6 81.21 0.00 0.00
August 0.770434E+10 -0.754280E+10 0.00 0.00 744.00 0.00 -161543930.1 81.21 0.00 0.00
September 0.746632E+10 -0.730993E+10 0.00 0.00 720.00 0.00 -156394914.9 81.21 0.00 0.00
October 0.770298E+10 -0.754143E+10 0.00 0.00 744.00 0.00 -161552461.4 81.21 0.00 0.00
November 0.744881E+10 -0.729242E+10 0.00 0.00 720.00 0.00 -156383624.2 81.21 0.00 0.00
December 0.771248E+10 -0.755087E+10 0.00 0.00 744.00 0.00 -161613397.7 81.21 0.00 0.00
                     
Annual Sum or Average 0.907431E+11 -0.888404E+11 0.00 0.00 8760.00 0.00 -0.190273E+10 81.21 0.00 0.00
Minimum of Months 0.696210E+10 -0.755087E+10 0.00 0.00 672.00 0.00 -161747520.4 81.21 0.00 0.00
Maximum of Months 0.771248E+10 -0.681598E+10 0.00 0.00 744.00 0.00 -146125333.0 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.119920E+12 -0.118179E+12 0.00 0.00 744.00 0.00 -0.174095E+10 81.26 0.00 0.00
February 0.108835E+12 -0.107258E+12 0.00 0.00 672.00 0.00 -0.157708E+10 81.26 0.00 0.00
March 0.119570E+12 -0.117820E+12 0.00 0.00 744.00 0.00 -0.175020E+10 81.26 0.00 0.00
April 0.113558E+12 -0.111860E+12 0.00 0.00 720.00 0.00 -0.169778E+10 81.26 0.00 0.00
May 0.114398E+12 -0.112645E+12 0.00 0.00 744.00 0.00 -0.175273E+10 81.26 0.00 0.00
June 0.107938E+12 -0.106245E+12 0.00 0.00 720.00 0.00 -0.169290E+10 81.25 0.00 0.00
July 0.109524E+12 -0.107781E+12 0.00 0.00 744.00 0.00 -0.174303E+10 81.25 0.00 0.00
August 0.108901E+12 -0.107162E+12 0.00 0.00 744.00 0.00 -0.173912E+10 81.25 0.00 0.00
September 0.106308E+12 -0.104630E+12 0.00 0.00 720.00 0.00 -0.167842E+10 81.25 0.00 0.00
October 0.112106E+12 -0.110374E+12 0.00 0.00 744.00 0.00 -0.173215E+10 81.25 0.00 0.00
November 0.111341E+12 -0.109665E+12 0.00 0.00 720.00 0.00 -0.167542E+10 81.25 0.00 0.00
December 0.117904E+12 -0.116168E+12 0.00 0.00 744.00 0.00 -0.173516E+10 81.26 0.00 0.00
                     
Annual Sum or Average 0.135030E+13 -0.132979E+13 0.00 0.00 8760.00 0.00 -0.205150E+11 81.26 0.00 0.00
Minimum of Months 0.106308E+12 -0.118179E+12 0.00 0.00 672.00 0.00 -0.175273E+10 81.25 0.00 0.00
Maximum of Months 0.119920E+12 -0.104630E+12 0.00 0.00 744.00 0.00 -0.157708E+10 81.26 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.709010E+11 -0.694184E+11 0.00 0.00 744.00 0.00 -0.148253E+10 58.99 0.00 0.00
February 0.644948E+11 -0.631493E+11 0.00 0.00 672.00 0.00 -0.134543E+10 58.99 0.00 0.00
March 0.706687E+11 -0.691733E+11 0.00 0.00 744.00 0.00 -0.149536E+10 58.98 0.00 0.00
April 0.665076E+11 -0.650548E+11 0.00 0.00 720.00 0.00 -0.145277E+10 58.98 0.00 0.00
May 0.662035E+11 -0.647045E+11 0.00 0.00 744.00 0.00 -0.149899E+10 58.98 0.00 0.00
June 0.617044E+11 -0.602583E+11 0.00 0.00 720.00 0.00 -0.144613E+10 58.98 0.00 0.00
July 0.619657E+11 -0.604799E+11 0.00 0.00 744.00 0.00 -0.148585E+10 58.98 0.00 0.00
August 0.614894E+11 -0.600091E+11 0.00 0.00 744.00 0.00 -0.148025E+10 58.98 0.00 0.00
September 0.602628E+11 -0.588367E+11 0.00 0.00 720.00 0.00 -0.142615E+10 58.98 0.00 0.00
October 0.641850E+11 -0.627143E+11 0.00 0.00 744.00 0.00 -0.147070E+10 58.98 0.00 0.00
November 0.645664E+11 -0.631443E+11 0.00 0.00 720.00 0.00 -0.142205E+10 58.99 0.00 0.00
December 0.691667E+11 -0.676921E+11 0.00 0.00 744.00 0.00 -0.147451E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.782116E+12 -0.764635E+12 0.00 0.00 8760.00 0.00 -0.174807E+11 58.98 0.00 0.00
Minimum of Months 0.602628E+11 -0.694184E+11 0.00 0.00 672.00 0.00 -0.149899E+10 58.98 0.00 0.00
Maximum of Months 0.709010E+11 -0.588367E+11 0.00 0.00 744.00 0.00 -0.134543E+10 58.99 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.93 0.93 01-JAN-09:09 2337.27 32.55 223.50 222.17 1771.36 33.51 226.67 178.00
February 259.50 0.93 0.93 01-FEB-08:20 4113.94 33.20 241.33 246.17 1773.37 29.22 210.67 213.17
March 247.00 0.93 0.93 01-MAR-07:19 6052.74 30.55 185.33 316.00 761.34 22.34 172.50 255.17
April 379.50 0.93 0.93 01-APR-06:49 1580.24 19.80 111.50 350.00 611.66 21.53 245.83 290.17
May 427.83 0.93 0.93 01-MAY-06:49 1456.92 19.62 116.17 389.83 557.83 21.32 261.83 318.67
June 375.17 0.93 0.93 01-JUN-05:30 1234.60 19.62 61.50 400.17 494.97 21.36 258.50 319.67
July 471.00 0.94 0.93 01-JUL-04:00 1064.01 18.59 73.50 399.67 426.33 20.35 213.33 291.50
August 366.67 0.94 0.93 01-AUG-05:40 1230.42 19.66 56.83 378.67 500.76 21.41 244.83 303.33
September 301.17 0.93 0.93 01-SEP-07:40 3447.48 24.86 151.83 322.33 690.00 22.39 226.33 269.83
October 245.33 0.93 0.93 01-OCT-07:19 6425.91 34.80 221.33 287.50 922.42 24.27 190.17 245.50
November 242.67 0.93 0.93 01-NOV-07:49 2638.98 32.27 226.33 229.00 1750.20 32.57 225.00 186.50
December 160.33 0.93 0.93 01-DEC-09:39 3133.25 35.79 150.33 211.50 2555.88 36.85 150.33 154.83
                         
Annual Sum or Average 3714.00 0.93     2561.79 24.97 1819.50 3753.00 909.81 24.32 2626.00 3026.33
Minimum of Months 160.33 0.93 0.93   1064.01 18.59 56.83 211.50 426.33 20.35 150.33 154.83
Maximum of Months 471.00 0.94 0.93   6425.91 35.79 241.33 400.17 2555.88 36.85 261.83 319.67



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.63 0.61 01-JAN-09:09 2563.36 32.65 224.33 234.17 1995.62 33.60 227.67 206.50
February 259.50 0.62 0.61 01-FEB-08:09 4422.58 33.32 242.33 254.33 2079.62 29.33 218.00 233.00
March 247.00 0.62 0.61 01-MAR-07:10 6432.72 30.80 184.83 328.67 1138.95 22.42 177.50 291.17
April 379.50 0.62 0.61 01-APR-06:40 1869.23 20.26 116.33 362.17 899.53 21.83 257.50 328.33
May 427.83 0.62 0.61 01-MAY-06:40 1709.19 20.19 138.83 405.00 809.09 21.72 291.00 366.50
June 375.17 0.63 0.61 01-JUN-05:10 1468.57 20.16 118.83 418.50 728.20 21.73 293.83 371.50
July 471.00 0.64 0.61 01-JUL-04:00 1287.41 19.16 106.33 419.00 649.09 20.74 236.00 368.00
August 366.67 0.63 0.61 01-AUG-05:40 1512.61 20.01 87.33 394.33 782.18 21.59 247.83 352.67
September 301.17 0.62 0.61 01-SEP-07:40 3813.41 25.05 158.33 332.17 1054.95 22.47 226.33 304.50
October 245.33 0.63 0.61 01-OCT-07:10 6811.70 34.96 221.33 300.33 1308.51 24.26 186.83 270.17
November 242.67 0.62 0.61 01-NOV-07:49 2864.71 32.38 227.83 240.33 1974.86 32.66 224.83 213.83
December 160.33 0.62 0.61 01-DEC-09:39 3442.21 35.93 150.33 223.83 2862.97 36.95 150.33 192.67
                         
Annual Sum or Average 3714.00 0.63     2844.76 25.31 1977.00 3912.83 1191.67 24.54 2737.67 3498.83
Minimum of Months 160.33 0.62 0.61   1287.41 19.16 87.33 223.83 649.09 20.74 150.33 192.67
Maximum of Months 471.00 0.64 0.61   6811.70 35.93 242.33 419.00 2862.97 36.95 293.83 371.50



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.82 0.80 01-JAN-09:30 353.73 13.79 0.00 200.17 151.23 17.04 0.00 39.33
February 259.50 0.81 0.80 01-FEB-08:39 438.80 15.06 0.00 232.17 193.94 18.34 0.00 112.83
March 247.00 0.81 0.80 01-MAR-07:40 568.80 16.42 0.00 315.00 262.57 19.68 3.17 209.83
April 379.50 0.81 0.80 01-APR-06:49 681.39 17.20 0.00 361.17 304.39 20.36 55.83 305.67
May 427.83 0.81 0.80 01-MAY-06:49 851.55 18.38 17.67 409.17 376.86 21.98 199.67 367.83
June 375.17 0.81 0.80 01-JUN-04:00 885.23 19.66 40.17 427.17 412.85 23.59 229.50 392.17
July 471.00 0.81 0.80 01-JUL-04:49 742.76 18.64 48.00 435.17 347.64 22.71 212.33 341.83
August 366.67 0.81 0.80 01-AUG-05:10 633.49 17.90 13.17 400.50 296.67 21.09 89.00 336.00
September 301.17 0.81 0.80 01-SEP-07:40 606.97 17.24 0.00 325.50 288.63 20.45 28.33 256.33
October 245.33 0.82 0.80 01-OCT-07:19 456.41 15.64 0.00 276.17 218.02 18.97 0.17 150.00
November 242.67 0.82 0.80 01-NOV-07:49 382.63 14.25 0.00 212.33 162.53 17.47 0.00 54.83
December 160.33 0.83 0.80 01-DEC-09:39 320.01 13.93 0.00 180.00 151.06 17.40 0.00 28.00
                         
Annual Sum or Average 3714.00 0.81     623.20 16.98 119.00 3774.50 285.24 20.44 818.00 2594.67
Minimum of Months 160.33 0.81 0.80   320.01 13.79 0.00 180.00 151.06 17.04 0.00 28.00
Maximum of Months 471.00 0.83 0.80   885.23 19.66 48.00 435.17 412.85 23.59 229.50 392.17



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.82 0.80 01-JAN-09:30 353.73 13.79 0.00 200.17 151.23 17.04 0.00 39.33
February 259.50 0.81 0.80 01-FEB-08:39 438.80 15.06 0.00 232.17 193.94 18.34 0.00 112.83
March 247.00 0.81 0.80 01-MAR-07:40 568.80 16.42 0.00 315.00 262.57 19.68 3.17 209.83
April 379.50 0.81 0.80 01-APR-06:49 681.39 17.20 0.00 361.17 304.39 20.36 55.83 305.67
May 427.83 0.81 0.80 01-MAY-06:49 851.55 18.38 17.67 409.17 376.86 21.98 199.67 367.83
June 375.17 0.81 0.80 01-JUN-04:00 885.23 19.66 40.17 427.17 412.85 23.59 229.50 392.17
July 471.00 0.81 0.80 01-JUL-04:49 742.76 18.64 48.00 435.17 347.64 22.71 212.33 341.83
August 366.67 0.81 0.80 01-AUG-05:10 633.49 17.90 13.17 400.50 296.67 21.09 89.00 336.00
September 301.17 0.81 0.80 01-SEP-07:40 606.97 17.24 0.00 325.50 288.63 20.45 28.33 256.33
October 245.33 0.82 0.80 01-OCT-07:19 456.41 15.64 0.00 276.17 218.02 18.97 0.17 150.00
November 242.67 0.82 0.80 01-NOV-07:49 382.63 14.25 0.00 212.33 162.53 17.47 0.00 54.83
December 160.33 0.83 0.80 01-DEC-09:39 320.01 13.93 0.00 180.00 151.06 17.40 0.00 28.00
                         
Annual Sum or Average 3714.00 0.81     623.20 16.98 119.00 3774.50 285.24 20.44 818.00 2594.67
Minimum of Months 160.33 0.81 0.80   320.01 13.79 0.00 180.00 151.06 17.04 0.00 28.00
Maximum of Months 471.00 0.83 0.80   885.23 19.66 48.00 435.17 412.85 23.59 229.50 392.17



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.276946E+11 127714.88 04-JAN-07:24 0.00 0.00 0.00 0.00 0.00
February 0.241989E+11 129819.43 06-FEB-18:25 0.00 0.00 0.00 0.00 0.00
March 0.315996E+11 126750.38 03-MAR-08:57 0.00 0.00 0.00 0.00 0.00
April 0.280330E+11 129234.07 17-APR-07:53 0.00 0.00 0.00 0.00 0.00
May 0.247354E+11 127703.18 18-MAY-06:24 0.00 0.00 0.00 0.00 0.00
June 0.847673E+10 98891.95 15-JUN-03:53 0.00 0.00 0.00 0.00 0.00
July 0.230985E+10 38599.78 04-JUL-05:00 0.00 0.00 0.00 0.00 0.00
August 0.212188E+10 41142.37 21-AUG-05:00 0.00 0.00 0.00 0.00 0.00
September 0.879305E+10 118111.99 28-SEP-05:36 0.00 0.00 0.00 0.00 0.00
October 0.321285E+11 125822.33 29-OCT-04:10 0.00 0.00 0.00 0.00 0.00
November 0.314002E+11 129085.35 22-NOV-23:29 0.00 0.00 0.00 0.00 0.00
December 0.289281E+11 131054.51 09-DEC-23:20 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.250420E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.212188E+10 38599.78   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.321285E+11 131054.51   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.344441E+10 3167.20 23-JAN-18:35 0.00 0.00 0.00 0.00 0.00
February 0.230585E+10 3240.13 22-FEB-08:07 0.00 0.00 0.00 0.00 0.00
March 0.174886E+10 3503.12 19-MAR-07:50 0.00 0.00 0.00 0.00 0.00
April 0.102601E+10 3501.01 23-APR-07:06 0.00 0.00 0.00 0.00 0.00
May 0.678761E+09 3292.06 18-MAY-06:25 0.00 0.00 0.00 0.00 0.00
June 0.380445E+09 2337.46 15-JUN-05:27 0.00 0.00 0.00 0.00 0.00
July 0.133412E+09 1421.75 04-JUL-05:27 0.00 0.00 0.00 0.00 0.00
August 0.157734E+09 1446.10 21-AUG-04:35 0.00 0.00 0.00 0.00 0.00
September 0.473504E+09 2721.60 27-SEP-06:30 0.00 0.00 0.00 0.00 0.00
October 0.122968E+10 3554.85 18-OCT-07:20 0.00 0.00 0.00 0.00 0.00
November 0.252211E+10 3194.74 17-NOV-08:35 0.00 0.00 0.00 0.00 0.00
December 0.324743E+10 3388.05 10-DEC-19:47 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.173482E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.133412E+09 1421.75   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.344441E+10 3554.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 38637955.13 624.57 23-JAN-14:40 0.00 0.00 0.00 0.00 0.00
February 14161598.18 324.82 15-FEB-15:00 0.00 0.00 0.00 0.00 0.00
March 69836.23 74.80 12-MAR-16:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 5819262.45 348.58 26-NOV-16:40 0.00 0.00 0.00 0.00 0.00
December 43087151.46 522.79 27-DEC-11:35 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.101776E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 43087151.46 624.57   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.552859E+09 887.06 23-JAN-13:13 0.00 0.00 0.00 0.00 0.00
February 0.296325E+09 1040.04 20-FEB-18:34 0.00 0.00 0.00 0.00 0.00
March 10246669.30 278.79 05-MAR-18:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.120182E+09 772.13 26-NOV-17:01 0.00 0.00 0.00 0.00 0.00
December 0.398522E+09 860.25 27-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.137813E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.552859E+09 1040.04   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.557795E+09 602.07 23-JAN-18:35 0.00 0.00 0.00 0.00 0.00
February 0.314342E+09 693.43 20-FEB-18:34 0.00 0.00 0.00 0.00 0.00
March 28196538.72 367.02 05-MAR-18:17 0.00 0.00 0.00 0.00 0.00
April 309292.66 190.05 18-APR-10:36 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 327332.84 74.88 31-OCT-17:00 0.00 0.00 0.00 0.00 0.00
November 0.180446E+09 514.29 23-NOV-18:33 0.00 0.00 0.00 0.00 0.00
December 0.439873E+09 629.14 01-DEC-18:17 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.152129E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.557795E+09 693.43   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.119192E+09 5213.48 03-JAN-04:45 0.00 0.00 0.00 0.00 0.00
February 0.113104E+09 6962.85 25-FEB-03:35 0.00 0.00 0.00 0.00 0.00
March 94763343.95 8160.85 15-MAR-04:03 0.00 0.00 0.00 0.00 0.00
April 0.107519E+09 10760.91 29-APR-04:52 0.00 0.00 0.00 0.00 0.00
May 0.188197E+09 11119.84 03-MAY-04:00 0.00 0.00 0.00 0.00 0.00
June 80018406.21 8980.30 15-JUN-02:29 0.00 0.00 0.00 0.00 0.00
July 12752695.71 1665.32 03-JUL-04:00 0.00 0.00 0.00 0.00 0.00
August 10855240.67 3300.88 22-AUG-03:23 0.00 0.00 0.00 0.00 0.00
September 47549436.85 7564.33 20-SEP-03:10 0.00 0.00 0.00 0.00 0.00
October 0.184510E+09 9240.48 19-OCT-03:55 0.00 0.00 0.00 0.00 0.00
November 0.131142E+09 5605.58 21-NOV-16:30 0.00 0.00 0.00 0.00 0.00
December 0.122448E+09 3656.30 28-DEC-04:20 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.121205E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 10855240.67 1665.32   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.188197E+09 11119.84   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.261002E+10 7850.07 23-JAN-18:35 0.00 0.00 0.00 0.00 0.00
February 0.130192E+10 7063.91 01-FEB-09:20 0.00 0.00 0.00 0.00 0.00
March 0.781140E+09 6732.26 21-MAR-09:58 0.00 0.00 0.00 0.00 0.00
April 0.201751E+09 7754.81 04-APR-08:07 0.00 0.00 0.00 0.00 0.00
May 0.116237E+09 5525.84 18-MAY-06:26 0.00 0.00 0.00 0.00 0.00
June 18421055.41 3610.19 14-JUN-06:20 0.00 0.00 0.00 0.00 0.00
July 5786985.31 1833.42 12-JUL-10:35 0.00 0.00 0.00 0.00 0.00
August 2801322.73 1055.50 01-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.130366E+09 5530.79 27-SEP-06:30 0.00 0.00 0.00 0.00 0.00
October 0.515123E+09 9209.21 18-OCT-07:20 0.00 0.00 0.00 0.00 0.00
November 0.167187E+10 7538.12 21-NOV-16:30 0.00 0.00 0.00 0.00 0.00
December 0.250335E+10 7063.13 17-DEC-11:37 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.985879E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2801322.73 1055.50   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.261002E+10 9209.21   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.316507E+09 10857.98 23-JAN-14:40 0.00 0.00 0.00 0.00 0.00
February 94527512.40 5683.44 15-FEB-15:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 53986646.09 3863.63 27-NOV-11:38 0.00 0.00 0.00 0.00 0.00
December 0.419398E+09 6785.47 26-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.884419E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.419398E+09 10857.98   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.618682E+10 8331.37 23-JAN-18:35 0.00 0.00 0.00 0.00 0.00
February 0.306673E+10 7629.68 04-FEB-09:08 0.00 0.00 0.00 0.00 0.00
March 0.474552E+09 7269.09 06-MAR-08:15 0.00 0.00 0.00 0.00 0.00
April 6832603.37 7511.64 01-APR-06:39 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.167412E+09 3541.44 22-OCT-07:50 0.00 0.00 0.00 0.00 0.00
November 0.295899E+10 7785.48 21-NOV-16:30 0.00 0.00 0.00 0.00 0.00
December 0.541585E+10 8241.48 10-DEC-19:47 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.182772E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.618682E+10 8331.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.356030E+10 4180.78 23-JAN-18:35 0.00 0.00 0.00 0.00 0.00
February 0.205834E+10 4434.34 22-FEB-08:07 0.00 0.00 0.00 0.00 0.00
March 0.572150E+09 3918.29 06-MAR-08:15 0.00 0.00 0.00 0.00 0.00
April 0.109184E+09 3636.47 01-APR-06:39 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 100783.07 335.94 27-SEP-03:20 0.00 0.00 0.00 0.00 0.00
October 0.204348E+09 4657.25 18-OCT-07:20 0.00 0.00 0.00 0.00 0.00
November 0.171494E+10 4334.51 17-NOV-08:35 0.00 0.00 0.00 0.00 0.00
December 0.321193E+10 4692.03 10-DEC-19:47 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.114313E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.356030E+10 4692.03   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 448821.33 722.52 19-MAY-02:17 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 448821.33     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 448821.33 722.52   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.757373E+09 4621.92 07-JAN-08:10 0.00 0.00 0.00 0.00 0.00
February 0.440027E+09 5280.68 19-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 43850.61 66.09 01-MAR-07:00 0.00 0.00 0.00 0.00 0.00
April 10297.38 0.72 27-APR-10:10 0.00 0.00 0.00 0.00 0.00
May 20408.65 0.72 14-MAY-20:10 0.00 0.00 0.00 0.00 0.00
June 39911.50 0.72 17-JUN-14:30 0.00 0.00 0.00 0.00 0.00
July 46517.19 0.73 05-JUL-13:40 0.00 0.00 0.00 0.00 0.00
August 52882.47 0.73 26-AUG-01:15 0.00 0.00 0.00 0.00 0.00
September 36426.23 0.71 08-SEP-10:04 0.00 0.00 0.00 0.00 0.00
October 20022.12 0.73 01-OCT-13:00 0.00 0.00 0.00 0.00 0.00
November 4380454.05 581.01 11-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.229519E+09 3441.38 26-DEC-09:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.143157E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 10297.38 0.71   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.757373E+09 5280.68   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.456544E+10 8971.41 07-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.286690E+10 8965.63 19-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.166740E+10 8731.97 05-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.667621E+09 8675.25 18-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.186661E+09 8044.23 18-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 34676054.99 3315.80 18-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 5647562.44 3574.58 16-JUL-15:04 0.00 0.00 0.00 0.00 0.00
August 6767544.63 3269.11 27-AUG-15:04 0.00 0.00 0.00 0.00 0.00
September 80109480.90 4102.05 27-SEP-08:62 0.00 0.00 0.00 0.00 0.00
October 0.906602E+09 8534.76 30-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.278283E+10 8794.18 13-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.423912E+10 8909.85 26-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.180098E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5647562.44 3269.11   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.456544E+10 8971.41   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.520019E+10 8822.92 07-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.355942E+10 8827.40 19-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.216792E+10 8616.98 24-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.887072E+09 8537.61 18-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.227164E+09 8192.66 18-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 41546205.78 3229.56 18-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 4926397.18 3102.81 04-JUL-18:04 0.00 0.00 0.00 0.00 0.00
August 7417098.72 3031.14 27-AUG-15:04 0.00 0.00 0.00 0.00 0.00
September 0.111305E+09 6154.89 28-SEP-08:62 0.00 0.00 0.00 0.00 0.00
October 0.126997E+10 8433.49 30-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.327723E+10 8701.90 13-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.489437E+10 8762.41 26-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.216485E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 4926397.18 3031.14   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.520019E+10 8827.40   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.618548E+10 12741.02 05-JAN-06:00 0.00 0.00 0.00 0.00 0.00
February 0.161188E+10 14878.95 19-FEB-06:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.113513E+10 8876.70 30-NOV-24:00 0.00 0.00 0.00 0.00 0.00
December 0.609807E+10 13769.80 26-DEC-04:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.150306E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.618548E+10 14878.95   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.162664E+11 47772.53 06-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.109521E+11 47626.83 13-FEB-16:01 0.00 0.00 0.00 0.00 0.00
March 0.370272E+10 46743.17 02-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.833546E+09 33024.25 25-APR-15:03 0.00 0.00 0.00 0.00 0.00
May 0.108455E+09 28183.39 12-MAY-15:05 0.00 0.00 0.00 0.00 0.00
June 41998868.06 26296.04 07-JUN-15:05 0.00 0.00 0.00 0.00 0.00
July 41945229.68 22786.71 25-JUL-08:06 0.00 0.00 0.00 0.00 0.00
August 36856210.73 24314.82 21-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 0.107068E+09 22832.46 24-SEP-15:05 0.00 0.00 0.00 0.00 0.00
October 0.125514E+10 45543.80 31-OCT-15:01 0.00 0.00 0.00 0.00 0.00
November 0.729734E+10 47046.93 30-NOV-16:01 0.00 0.00 0.00 0.00 0.00
December 0.146862E+11 47621.61 26-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.553298E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 36856210.73 22786.71   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.162664E+11 47772.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.460209E+10 8794.85 07-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.288877E+10 8744.93 18-FEB-19:01 0.00 0.00 0.00 0.00 0.00
March 0.162520E+10 8569.18 05-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.636604E+09 8518.41 18-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.237318E+09 7867.92 18-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 40804787.14 2807.67 02-JUN-18:04 0.00 0.00 0.00 0.00 0.00
July 5529868.83 3279.01 16-JUL-15:04 0.00 0.00 0.00 0.00 0.00
August 6897764.19 3190.72 27-AUG-15:04 0.00 0.00 0.00 0.00 0.00
September 0.101663E+09 2719.46 06-SEP-15:05 0.00 0.00 0.00 0.00 0.00
October 0.928745E+09 8396.46 30-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.279546E+10 8613.11 29-NOV-19:01 0.00 0.00 0.00 0.00 0.00
December 0.427715E+10 8758.79 26-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.181462E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5529868.83 2719.46   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.460209E+10 8794.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.525909E+10 8670.88 07-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.356929E+10 8601.09 19-FEB-19:01 0.00 0.00 0.00 0.00 0.00
March 0.209056E+10 8447.73 05-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.816876E+09 8380.97 18-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.288151E+09 8003.79 18-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 48451711.56 2457.70 29-JUN-15:05 0.00 0.00 0.00 0.00 0.00
July 5371160.10 3043.91 16-JUL-15:04 0.00 0.00 0.00 0.00 0.00
August 8306331.20 3125.13 27-AUG-15:04 0.00 0.00 0.00 0.00 0.00
September 0.151321E+09 4331.45 26-SEP-15:02 0.00 0.00 0.00 0.00 0.00
October 0.128720E+10 8294.92 30-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.326964E+10 8505.95 13-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.491798E+10 8611.50 26-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.217122E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5371160.10 2457.70   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.525909E+10 8670.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.160411E+10 2665.43 07-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.104640E+10 2666.79 19-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.667209E+09 2618.45 05-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.311461E+09 2602.04 18-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.126022E+09 2560.59 18-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 34302673.82 945.35 11-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 3935237.25 864.38 16-JUL-15:04 0.00 0.00 0.00 0.00 0.00
August 6938661.32 936.98 19-AUG-08:03 0.00 0.00 0.00 0.00 0.00
September 63147690.20 2097.56 27-SEP-08:62 0.00 0.00 0.00 0.00 0.00
October 0.410802E+09 2555.77 30-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.102624E+10 2630.40 11-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.150119E+10 2647.19 26-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.680176E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3935237.25 864.38   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.160411E+10 2666.79   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.180514E+10 2611.81 07-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.126479E+10 2613.11 19-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.832176E+09 2572.86 01-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.391825E+09 2551.33 18-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.146201E+09 2509.52 18-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 40052726.81 777.46 12-JUN-15:04 0.00 0.00 0.00 0.00 0.00
July 4894219.90 974.68 16-JUL-15:04 0.00 0.00 0.00 0.00 0.00
August 9358496.51 841.19 19-AUG-08:03 0.00 0.00 0.00 0.00 0.00
September 89011726.37 2470.10 28-SEP-08:62 0.00 0.00 0.00 0.00 0.00
October 0.553313E+09 2516.53 30-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.118474E+10 2583.31 11-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.170839E+10 2593.95 26-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.802988E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 4894219.90 777.46   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.180514E+10 2613.11   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.485306E+10 12886.83 15-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.274191E+10 12840.52 17-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.143927E+10 12575.09 05-MAR-16:01 0.00 0.00 0.00 0.00 0.00
April 0.634622E+09 12563.92 18-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.256116E+09 11389.19 18-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 49920188.94 5485.93 23-JUN-15:04 0.00 0.00 0.00 0.00 0.00
July 9992027.01 5517.87 16-JUL-15:04 0.00 0.00 0.00 0.00 0.00
August 10877758.84 4468.58 03-AUG-15:04 0.00 0.00 0.00 0.00 0.00
September 90917962.49 4828.45 21-SEP-15:04 0.00 0.00 0.00 0.00 0.00
October 0.665762E+09 12297.19 27-OCT-15:01 0.00 0.00 0.00 0.00 0.00
November 0.266544E+10 12729.95 30-NOV-16:01 0.00 0.00 0.00 0.00 0.00
December 0.452977E+10 12948.96 26-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.179477E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 9992027.01 4468.58   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.485306E+10 12948.96   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.305234E+09 0.305234E+09 40263.44 04-JAN-21:14 40263.44 0.00
February 0.00 0.00 0.205599E+10 0.205599E+10 79742.69 27-FEB-15:00 79742.69 0.02
March 0.00 0.00 0.420411E+10 0.420411E+10 102908.53 18-MAR-16:10 102908.53 0.03
April 0.00 0.00 0.286744E+11 0.286744E+11 205582.09 27-APR-18:10 205582.09 0.09
May 0.00 0.00 0.552908E+11 0.548583E+11 205273.59 05-MAY-18:00 171688.90 0.22
June 0.00 0.00 0.985683E+11 0.984298E+11 221214.23 28-JUN-18:10 210065.17 0.42
July 0.00 0.00 0.167844E+12 0.162029E+12 271313.52 27-JUL-18:40 196191.62 0.62
August 0.00 0.00 0.212712E+12 0.203226E+12 298764.55 10-AUG-18:07 253018.07 0.81
September 0.00 0.00 0.808736E+11 0.786906E+11 206178.88 14-SEP-17:15 181446.27 0.50
October 0.00 0.00 0.149364E+11 0.149215E+11 126558.28 04-OCT-15:03 126558.28 0.11
November 0.00 0.00 0.365309E+10 0.365309E+10 103185.90 04-NOV-14:20 103185.90 0.06
December 0.00 0.00 0.377485E+09 0.377485E+09 34606.16 12-DEC-22:37 34606.16 0.00
                 
Annual Sum or Average 0.00 0.00 0.669495E+12 0.651425E+12       0.24
Minimum of Months 0.00 0.00 0.305234E+09 0.305234E+09 34606.16   34606.16 0.00
Maximum of Months 0.00 0.00 0.212712E+12 0.203226E+12 298764.55   253018.07 0.81



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.332455E+09 0.332455E+09 18783.31 27-FEB-15:00 18783.31 0.01
March 0.00 0.00 0.656272E+09 0.656272E+09 20929.09 18-MAR-16:00 20929.09 0.01
April 0.00 0.00 0.473027E+10 0.473027E+10 29946.00 27-APR-15:02 29946.00 0.05
May 0.00 0.00 0.970367E+10 0.924311E+10 36235.69 05-MAY-18:02 27242.31 0.17
June 0.00 0.00 0.167744E+11 0.167571E+11 29532.74 28-JUN-15:02 29532.74 0.36
July 0.00 0.00 0.301164E+11 0.278837E+11 39786.10 15-JUL-18:00 26404.20 0.61
August 0.00 0.00 0.384432E+11 0.348388E+11 40345.78 30-AUG-12:40 25816.40 0.79
September 0.00 0.00 0.144140E+11 0.132626E+11 38717.43 23-SEP-13:30 26575.57 0.44
October 0.00 0.00 0.254416E+10 0.253791E+10 24147.99 04-OCT-15:00 24147.99 0.06
November 0.00 0.00 0.658452E+09 0.579607E+09 28029.94 04-NOV-13:50 22649.60 0.03
December 0.00 0.00 7193.64 7193.64 35.97 05-DEC-11:57 35.97 0.00
                 
Annual Sum or Average 0.00 0.00 0.118373E+12 0.110822E+12       0.21
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.384432E+11 0.348388E+11 40345.78   29946.00 0.79



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 9090484.77 8412275.13 9196.44 20-JAN-16:02 9196.44 0.00
February 0.00 0.00 0.184356E+09 0.151650E+09 14246.83 06-FEB-16:02 14246.83 0.03
March 0.00 0.00 0.706842E+09 0.682674E+09 14850.72 18-MAR-15:02 14850.72 0.02
April 0.00 0.00 0.210869E+10 0.167351E+10 15584.30 01-APR-18:02 15584.30 0.23
May 0.00 0.00 0.393075E+10 0.281115E+10 15297.92 14-MAY-15:02 15297.92 0.52
June 0.00 0.00 0.461639E+10 0.292829E+10 15148.59 12-JUN-15:01 12844.72 0.75
July 0.00 0.00 0.752916E+10 0.482540E+10 15301.64 16-JUL-15:01 13313.40 0.89
August 0.00 0.00 0.737773E+10 0.459268E+10 15313.72 28-AUG-15:02 14701.94 0.88
September 0.00 0.00 0.469678E+10 0.283501E+10 14676.51 22-SEP-18:02 14235.06 0.75
October 0.00 0.00 0.133658E+10 0.954022E+09 15070.28 04-OCT-15:02 15070.28 0.23
November 0.00 0.00 0.136637E+09 71965650.56 14006.37 11-NOV-16:02 14006.37 0.04
December 0.00 0.00 18616092.82 17696927.63 13563.44 05-DEC-16:02 13563.44 0.00
                 
Annual Sum or Average 0.00 0.00 0.326516E+11 0.215524E+11       0.36
Minimum of Months 0.00 0.00 9090484.77 8412275.13 9196.44   9196.44 0.00
Maximum of Months 0.00 0.00 0.752916E+10 0.482540E+10 15584.30   15584.30 0.89



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 2590396.11 2153419.97 3817.89 24-JAN-16:03 3817.89 0.00
February 0.00 0.00 45560293.78 30837153.53 13295.11 27-FEB-16:02 13295.11 0.01
March 0.00 0.00 0.274759E+09 0.270011E+09 13367.92 18-MAR-15:02 13367.92 0.00
April 0.00 0.00 0.135267E+10 0.106109E+10 14029.59 01-APR-18:02 14029.59 0.16
May 0.00 0.00 0.313273E+10 0.226434E+10 13771.06 14-MAY-15:02 13771.06 0.46
June 0.00 0.00 0.400232E+10 0.258256E+10 13583.18 12-JUN-15:01 11462.20 0.69
July 0.00 0.00 0.656449E+10 0.425716E+10 13737.19 16-JUL-15:01 11903.50 0.84
August 0.00 0.00 0.604914E+10 0.369354E+10 13830.87 28-AUG-15:02 13209.77 0.83
September 0.00 0.00 0.311054E+10 0.176382E+10 13480.98 24-SEP-15:02 11840.92 0.64
October 0.00 0.00 0.556651E+09 0.405752E+09 13565.85 04-OCT-15:02 13565.85 0.12
November 0.00 0.00 44752227.89 23170043.01 13492.55 04-NOV-15:02 12753.31 0.01
December 0.00 0.00 4296991.80 3535860.94 3601.22 03-DEC-19:03 3601.22 0.00
                 
Annual Sum or Average 0.00 0.00 0.251405E+11 0.163580E+11       0.32
Minimum of Months 0.00 0.00 2590396.11 2153419.97 3601.22   3601.22 0.00
Maximum of Months 0.00 0.00 0.656449E+10 0.425716E+10 14029.59   14029.59 0.84



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 20465098.89 20465098.89 4582.63 08-JAN-14:40 4582.63 0.00
February 0.00 0.00 0.231332E+10 0.231332E+10 34513.54 08-FEB-14:00 34513.54 0.00
March 0.00 0.00 0.565474E+10 0.565474E+10 46834.27 02-MAR-13:30 46834.27 0.00
April 0.00 0.00 0.924778E+10 0.776762E+10 42082.96 27-APR-13:20 38029.60 0.11
May 0.00 0.00 0.121638E+11 0.925114E+10 41461.31 04-MAY-13:20 36089.88 0.21
June 0.00 0.00 0.127592E+11 0.688043E+10 29319.41 28-JUN-13:10 19316.03 0.42
July 0.00 0.00 0.218399E+11 0.117487E+11 41009.86 31-JUL-13:00 32300.97 0.55
August 0.00 0.00 0.271512E+11 0.155193E+11 52861.44 24-AUG-14:50 43765.82 0.67
September 0.00 0.00 0.238370E+11 0.148896E+11 54484.41 14-SEP-13:30 40438.62 0.52
October 0.00 0.00 0.124482E+11 0.109426E+11 56017.09 04-OCT-12:30 56017.09 0.11
November 0.00 0.00 0.112967E+10 0.739222E+09 35295.01 04-NOV-13:30 25140.67 0.02
December 0.00 0.00 0.110088E+10 0.110088E+10 30395.72 05-DEC-12:25 30395.72 0.00
                 
Annual Sum or Average 0.00 0.00 0.129666E+12 0.868281E+11       0.22
Minimum of Months 0.00 0.00 20465098.89 20465098.89 4582.63   4582.63 0.00
Maximum of Months 0.00 0.00 0.271512E+11 0.155193E+11 56017.09   56017.09 0.67



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.239592E+09 0.154160E+09 30315.95 09-JAN-19:04 30315.95 0.02
February 0.00 0.00 0.132398E+10 0.640198E+09 53766.71 25-FEB-09:03 53766.71 0.11
March 0.00 0.00 0.346448E+10 0.262306E+10 53956.08 21-MAR-18:02 53956.08 0.13
April 0.00 0.00 0.110374E+11 0.828232E+10 61385.87 01-APR-18:02 61385.87 0.31
May 0.00 0.00 0.215298E+11 0.152820E+11 63956.87 05-MAY-18:02 58385.76 0.56
June 0.00 0.00 0.286246E+11 0.202742E+11 62771.73 09-JUN-18:02 62771.73 0.66
July 0.00 0.00 0.359726E+11 0.246532E+11 66065.56 15-JUL-18:02 58381.65 0.68
August 0.00 0.00 0.350617E+11 0.219150E+11 65521.64 13-AUG-15:02 61683.26 0.71
September 0.00 0.00 0.201181E+11 0.107798E+11 61476.70 23-SEP-15:02 56562.30 0.69
October 0.00 0.00 0.668501E+10 0.367824E+10 58788.80 01-OCT-08:62 52582.89 0.38
November 0.00 0.00 0.225679E+10 0.863824E+09 56772.97 05-NOV-08:62 52182.81 0.19
December 0.00 0.00 0.178853E+09 0.118246E+09 33120.92 05-DEC-19:03 33120.92 0.02
                 
Annual Sum or Average 0.00 0.00 0.166493E+12 0.109264E+12       0.37
Minimum of Months 0.00 0.00 0.178853E+09 0.118246E+09 30315.95   30315.95 0.02
Maximum of Months 0.00 0.00 0.359726E+11 0.246532E+11 66065.56   62771.73 0.71



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 7737990.56 7125174.14 3455.22 10-JAN-09:03 3455.22 0.00
February 0.00 0.00 0.165255E+09 0.128869E+09 11822.93 08-FEB-16:02 11822.93 0.03
March 0.00 0.00 0.649575E+09 0.605980E+09 13286.59 18-MAR-15:02 13286.59 0.03
April 0.00 0.00 0.216076E+10 0.168078E+10 13860.31 01-APR-18:02 13860.31 0.26
May 0.00 0.00 0.338929E+10 0.233345E+10 13686.58 14-MAY-15:02 13686.58 0.51
June 0.00 0.00 0.499394E+10 0.320699E+10 13641.55 12-JUN-15:01 11735.27 0.80
July 0.00 0.00 0.649394E+10 0.399044E+10 13917.32 31-JUL-18:02 13426.62 0.91
August 0.00 0.00 0.729568E+10 0.452899E+10 14054.40 30-AUG-08:62 10302.27 0.89
September 0.00 0.00 0.424362E+10 0.253838E+10 13492.26 24-SEP-15:02 11714.11 0.73
October 0.00 0.00 0.131169E+10 0.921696E+09 13482.95 04-OCT-15:02 13482.95 0.25
November 0.00 0.00 0.141153E+09 70111800.17 13388.00 04-NOV-15:02 12686.75 0.05
December 0.00 0.00 51142684.37 48100787.87 4002.10 29-DEC-09:03 2897.13 0.00
                 
Annual Sum or Average 0.00 0.00 0.309038E+11 0.200609E+11       0.37
Minimum of Months 0.00 0.00 7737990.56 7125174.14 3455.22   2897.13 0.00
Maximum of Months 0.00 0.00 0.729568E+10 0.452899E+10 14054.40   13860.31 0.91



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 3462527.96 3002464.10 2886.72 05-JAN-09:04 2886.72 0.00
February 0.00 0.00 20347280.71 12919202.77 4381.11 27-FEB-09:01 3289.11 0.01
March 0.00 0.00 0.176982E+09 0.159658E+09 11149.89 02-MAR-09:01 11149.89 0.02
April 0.00 0.00 0.131762E+10 0.989489E+09 12120.61 02-APR-15:02 12120.61 0.21
May 0.00 0.00 0.256288E+10 0.175166E+10 12417.60 14-MAY-15:02 12417.60 0.45
June 0.00 0.00 0.431044E+10 0.282612E+10 12391.01 12-JUN-15:01 10640.46 0.77
July 0.00 0.00 0.548881E+10 0.340620E+10 12764.01 31-JUL-18:02 12103.83 0.89
August 0.00 0.00 0.592044E+10 0.355157E+10 12710.68 09-AUG-18:02 12152.14 0.86
September 0.00 0.00 0.263955E+10 0.148058E+10 12770.89 23-SEP-15:02 11538.58 0.62
October 0.00 0.00 0.496829E+09 0.324312E+09 12019.92 04-OCT-15:02 12019.92 0.13
November 0.00 0.00 23197726.62 8691963.98 6951.11 04-NOV-15:02 4622.58 0.02
December 0.00 0.00 4934408.93 4362900.04 2777.56 03-DEC-09:03 2777.56 0.00
                 
Annual Sum or Average 0.00 0.00 0.229655E+11 0.145186E+11       0.33
Minimum of Months 0.00 0.00 3462527.96 3002464.10 2777.56   2777.56 0.00
Maximum of Months 0.00 0.00 0.592044E+10 0.355157E+10 12770.89   12417.60 0.89



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 1394549.60 1281811.31 1924.55 20-JAN-16:02 1924.55 0.00
February 0.00 0.00 45850530.62 39190490.32 3717.99 06-FEB-16:02 3717.99 0.02
March 0.00 0.00 0.173221E+09 0.169062E+09 3875.77 18-MAR-15:02 3875.77 0.01
April 0.00 0.00 0.517273E+09 0.425556E+09 4067.07 01-APR-18:02 4067.07 0.18
May 0.00 0.00 0.959932E+09 0.719541E+09 3992.28 14-MAY-15:02 3992.28 0.43
June 0.00 0.00 0.112154E+10 0.737563E+09 3966.87 12-JUN-15:01 3369.85 0.67
July 0.00 0.00 0.186964E+10 0.122968E+10 3999.67 16-JUL-15:01 3470.64 0.86
August 0.00 0.00 0.178891E+10 0.114610E+10 4043.53 25-AUG-08:62 3314.65 0.84
September 0.00 0.00 0.109975E+10 0.695738E+09 3946.61 23-SEP-08:62 3003.01 0.64
October 0.00 0.00 0.288514E+09 0.218301E+09 3932.84 04-OCT-15:02 3932.84 0.16
November 0.00 0.00 32375897.35 18660115.35 3684.11 11-NOV-16:02 3684.11 0.03
December 0.00 0.00 3514156.28 3235718.86 3559.63 05-DEC-16:02 3559.63 0.00
                 
Annual Sum or Average 0.00 0.00 0.790192E+10 0.540391E+10       0.32
Minimum of Months 0.00 0.00 1394549.60 1281811.31 1924.55   1924.55 0.00
Maximum of Months 0.00 0.00 0.186964E+10 0.122968E+10 4067.07   4067.07 0.86



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 482531.01 381086.20 718.59 11-JAN-16:05 510.85 0.00
February 0.00 0.00 8682963.43 6483379.46 3440.80 27-FEB-16:02 3440.80 0.01
March 0.00 0.00 61697128.26 60746426.64 3459.64 18-MAR-15:02 3459.64 0.00
April 0.00 0.00 0.324437E+09 0.263920E+09 3630.91 01-APR-18:02 3630.91 0.13
May 0.00 0.00 0.749187E+09 0.571375E+09 3564.28 14-MAY-15:02 3564.28 0.36
June 0.00 0.00 0.954531E+09 0.646638E+09 3526.15 12-JUN-15:01 2979.57 0.61
July 0.00 0.00 0.160963E+10 0.107611E+10 3566.36 16-JUL-15:01 3085.35 0.82
August 0.00 0.00 0.143384E+10 0.907873E+09 3585.64 28-AUG-15:02 3415.22 0.77
September 0.00 0.00 0.684310E+09 0.417465E+09 3510.56 24-SEP-15:02 3052.08 0.50
October 0.00 0.00 0.107667E+09 83883771.99 3510.88 04-OCT-15:02 3510.88 0.06
November 0.00 0.00 10803747.32 6213853.23 3499.38 04-NOV-15:02 3296.36 0.01
December 0.00 0.00 1112348.84 948988.11 847.81 10-DEC-16:03 647.20 0.00
                 
Annual Sum or Average 0.00 0.00 0.594638E+10 0.404204E+10       0.27
Minimum of Months 0.00 0.00 482531.01 381086.20 718.59   510.85 0.00
Maximum of Months 0.00 0.00 0.160963E+10 0.107611E+10 3630.91   3630.91 0.82



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.386361E+09 0.381536E+09 20203.47 20-JAN-16:02 20203.47 0.01
February 0.00 0.00 0.158324E+10 0.139618E+10 20215.56 01-FEB-16:02 20215.56 0.09
March 0.00 0.00 0.276938E+10 0.255054E+10 21062.24 18-MAR-15:02 21062.24 0.11
April 0.00 0.00 0.421691E+10 0.332985E+10 21240.23 27-APR-18:02 21240.23 0.32
May 0.00 0.00 0.533718E+10 0.357817E+10 21702.17 05-MAY-18:02 20451.92 0.56
June 0.00 0.00 0.605830E+10 0.350253E+10 21739.53 12-JUN-15:01 18457.43 0.77
July 0.00 0.00 0.894587E+10 0.517717E+10 22173.38 15-JUL-18:02 20069.75 0.87
August 0.00 0.00 0.101841E+11 0.621749E+10 21810.28 09-AUG-18:02 21448.82 0.88
September 0.00 0.00 0.818835E+10 0.523116E+10 21059.13 22-SEP-18:02 20045.06 0.78
October 0.00 0.00 0.427554E+10 0.312743E+10 21373.06 04-OCT-15:02 21373.06 0.43
November 0.00 0.00 0.104780E+10 0.752556E+09 20211.29 10-NOV-16:01 20211.29 0.11
December 0.00 0.00 0.879794E+09 0.853483E+09 20208.16 06-DEC-16:02 20208.16 0.01
                 
Annual Sum or Average 0.00 0.00 0.538728E+11 0.360981E+11       0.41
Minimum of Months 0.00 0.00 0.386361E+09 0.381536E+09 20203.47   18457.43 0.01
Maximum of Months 0.00 0.00 0.101841E+11 0.621749E+10 22173.38   21448.82 0.88



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 35476.51 219323.84 12-JAN-09:01
February 0.12 382.71 06-FEB-13:40 26408.01 155691.01 20-FEB-19:15
March 0.00 0.00 01-MAR-00:03 18244.94 220140.61 03-MAR-09:02
April 0.00 0.00 01-APR-00:05 13206.73 128779.20 17-APR-07:50
May 0.00 0.00 01-MAY-00:05 10076.73 173204.07 18-MAY-08:62
June 0.00 0.00 01-JUN-00:05 3547.43 107998.78 15-JUN-03:03
July 0.00 0.00 01-JUL-00:10 944.39 44791.88 13-JUL-08:05
August 0.00 0.00 01-AUG-00:05 885.25 44140.32 21-AUG-08:05
September 0.00 0.00 01-SEP-00:05 3910.19 115435.05 27-SEP-04:53
October 0.00 0.00 01-OCT-00:10 15386.22 158106.80 16-OCT-08:62
November 0.00 0.00 01-NOV-00:03 25231.25 194358.47 24-NOV-16:01
December 0.00 0.00 01-DEC-00:03 33881.28 221560.93 07-DEC-19:03
             
Annual Sum or Average 0.01     15556.29    
Minimum of Months 0.00 0.00   885.25 44140.32  
Maximum of Months 0.12 382.71   35476.51 221560.93  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 1472.61 40919.30 17-JAN-19:04 0.00 0.00 01-JAN-00:05
February 5014.28 177851.70 27-FEB-16:02 0.00 0.00 01-FEB-00:03
March 9458.93 228614.86 18-MAR-15:02 0.00 0.00 01-MAR-00:03
April 28818.14 389660.76 27-APR-18:03 0.00 0.00 01-APR-00:05
May 48715.51 379435.57 05-MAY-18:02 0.00 0.00 01-MAY-00:05
June 75578.72 410038.20 28-JUN-18:03 0.00 0.00 01-JUN-00:05
July 115386.77 468774.74 31-JUL-18:03 0.00 0.00 01-JUL-00:10
August 137591.27 504116.44 10-AUG-18:03 0.00 0.00 01-AUG-00:05
September 67952.27 410456.17 14-SEP-15:03 0.00 0.00 01-SEP-00:05
October 19783.57 340741.13 04-OCT-15:02 0.00 0.00 01-OCT-00:10
November 5119.50 252242.78 04-NOV-15:02 0.00 0.00 01-NOV-00:03
December 2344.21 49410.07 19-DEC-19:03 0.00 0.00 01-DEC-00:03
             
Annual Sum or Average 43402.19     0.00    
Minimum of Months 1472.61 40919.30   0.00 0.00  
Maximum of Months 137591.27 504116.44   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 27446.20 68449.74 11-JAN-07:11
February 0.00 0.00 01-FEB-00:03 27623.55 68465.66 01-FEB-07:51
March 0.00 0.00 01-MAR-00:03 27328.96 68642.19 07-MAR-07:51
April 0.00 0.00 01-APR-00:05 26606.49 66047.25 01-APR-07:11
May 0.00 0.00 01-MAY-00:05 25674.46 60849.28 19-MAY-06:14
June 0.00 0.00 01-JUN-00:05 24795.16 58820.16 15-JUN-06:38
July 0.00 0.00 01-JUL-00:10 24143.78 52501.01 03-JUL-06:10
August 0.00 0.00 01-AUG-00:05 23968.35 53374.20 18-AUG-06:37
September 0.00 0.00 01-SEP-00:05 24246.92 58025.01 27-SEP-06:55
October 0.00 0.00 01-OCT-00:10 24908.02 61489.80 13-OCT-06:11
November 0.00 0.00 01-NOV-00:03 25872.58 60478.41 19-NOV-07:51
December 0.00 0.00 01-DEC-00:03 26800.76 67787.61 28-DEC-07:01
             
Annual Sum or Average 0.00     25773.92    
Minimum of Months 0.00 0.00   23968.35 52501.01  
Maximum of Months 0.00 0.00   27623.55 68642.19  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.587890E+10 0.89 2194.93 01-JAN-00:05 0.89
February 0.530997E+10 0.89 2194.93 01-FEB-00:03 0.89
March 0.587890E+10 0.89 2194.93 01-MAR-00:03 0.89
April 0.568926E+10 0.89 2194.93 01-APR-00:05 0.89
May 0.587890E+10 0.89 2194.93 01-MAY-00:05 0.89
June 0.568926E+10 0.89 2194.93 01-JUN-00:05 0.89
July 0.587890E+10 0.88 2194.93 01-JUL-00:10 0.88
August 0.587890E+10 0.88 2194.93 01-AUG-00:05 0.88
September 0.568926E+10 0.88 2194.93 01-SEP-00:05 0.88
October 0.587890E+10 0.89 2194.93 01-OCT-00:10 0.88
November 0.568926E+10 0.89 2194.93 01-NOV-00:03 0.89
December 0.587890E+10 0.89 2194.93 01-DEC-00:03 0.89
           
Annual Sum or Average 0.692193E+11 0.89      
Minimum of Months 0.530997E+10 0.88 2194.93   0.88
Maximum of Months 0.587890E+10 0.89 2194.93   0.89



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.334175E+11 0.79 37285.71 09-JAN-21:55 1.53
February 0.303218E+11 0.79 41975.18 07-FEB-20:35 1.64
March 0.347687E+11 0.81 37285.71 17-MAR-21:05 1.52
April 0.342965E+11 0.82 35517.42 21-APR-23:55 1.47
May 0.363308E+11 0.83 35517.42 24-MAY-04:45 1.47
June 0.353395E+11 0.83 24425.23 28-JUN-21:10 1.17
July 0.372988E+11 0.84 25639.02 31-JUL-21:10 1.20
August 0.378723E+11 0.84 27628.34 10-AUG-21:10 1.25
September 0.355130E+11 0.83 28072.14 12-SEP-21:10 1.27
October 0.360095E+11 0.82 41975.18 24-OCT-01:15 1.64
November 0.336614E+11 0.81 38530.42 15-NOV-22:50 1.56
December 0.339541E+11 0.80 37285.71 04-DEC-21:55 1.52
           
Annual Sum or Average 0.418784E+12 0.82      
Minimum of Months 0.303218E+11 0.79 24425.23   1.17
Maximum of Months 0.378723E+11 0.84 41975.18   1.64



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.27 76.61 01-JAN-00:05 0.27
February 0.185347E+09 0.27 76.61 01-FEB-00:03 0.27
March 0.205205E+09 0.27 76.61 01-MAR-00:03 0.27
April 0.198586E+09 0.27 76.61 01-APR-00:05 0.27
May 0.205205E+09 0.27 76.61 01-MAY-00:05 0.27
June 0.198586E+09 0.27 76.61 01-JUN-00:05 0.27
July 0.205205E+09 0.27 76.61 01-JUL-00:10 0.27
August 0.205205E+09 0.27 76.61 01-AUG-00:05 0.27
September 0.198586E+09 0.27 76.61 01-SEP-00:05 0.27
October 0.205205E+09 0.27 76.61 01-OCT-00:10 0.27
November 0.198586E+09 0.27 76.61 01-NOV-00:03 0.27
December 0.205205E+09 0.27 76.61 01-DEC-00:03 0.27
           
Annual Sum or Average 0.241613E+10 0.27      
Minimum of Months 0.185347E+09 0.27 76.61   0.27
Maximum of Months 0.205205E+09 0.27 76.61   0.27



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:05 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:03 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 -0.0 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:05 0.00
May 0.00 -0.0 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:03 0.00
December 0.00 -0.0 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 -0.0 0.00 01-FEB-00:03 0.00
March 0.00 -0.0 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:05 0.00
May 0.00 -0.0 0.00 01-MAY-00:05 0.00
June 0.00 -0.0 0.00 01-JUN-00:05 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 -0.0 0.00 01-SEP-00:05 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:03 0.00
December 0.00 -0.0 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.19 612.92 01-JAN-07:05 0.27
February 0.105030E+10 0.19 612.92 01-FEB-07:05 0.27
March 0.116283E+10 0.19 612.92 01-MAR-07:05 0.27
April 0.112532E+10 0.19 612.92 01-APR-06:05 0.27
May 0.116283E+10 0.19 612.92 01-MAY-06:05 0.27
June 0.112532E+10 0.19 612.92 01-JUN-06:03 0.27
July 0.116283E+10 0.19 612.92 01-JUL-06:10 0.27
August 0.116283E+10 0.19 612.92 01-AUG-06:03 0.27
September 0.112532E+10 0.19 612.92 01-SEP-06:05 0.27
October 0.116283E+10 0.19 612.92 01-OCT-06:10 0.27
November 0.112532E+10 0.19 612.92 01-NOV-06:03 0.27
December 0.116283E+10 0.19 612.92 01-DEC-07:10 0.27
           
Annual Sum or Average 0.136914E+11 0.19      
Minimum of Months 0.105030E+10 0.19 612.92   0.27
Maximum of Months 0.116283E+10 0.19 612.92   0.27



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.287404E+09 0.45 856.10 01-JAN-09:01 0.58
February 0.206213E+09 0.43 856.10 01-FEB-09:02 0.58
March 0.182386E+09 0.43 856.10 01-MAR-16:02 0.58
April 0.199474E+09 0.45 856.10 01-APR-15:02 0.58
May 0.272537E+09 0.48 856.10 01-MAY-15:02 0.58
June 0.294311E+09 0.49 856.10 01-JUN-08:62 0.58
July 0.439880E+09 0.52 856.10 01-JUL-08:62 0.58
August 0.407649E+09 0.51 856.10 01-AUG-08:62 0.58
September 0.288245E+09 0.48 856.10 01-SEP-15:02 0.58
October 0.174188E+09 0.44 856.10 01-OCT-15:02 0.58
November 0.206954E+09 0.43 856.10 01-NOV-08:62 0.58
December 0.274650E+09 0.45 856.10 01-DEC-09:01 0.58
           
Annual Sum or Average 0.323389E+10 0.46      
Minimum of Months 0.174188E+09 0.43 856.10   0.58
Maximum of Months 0.439880E+09 0.52 856.10   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.294637E+09 0.48 770.01 01-JAN-09:01 0.58
February 0.215548E+09 0.44 770.01 01-FEB-09:02 0.58
March 0.171976E+09 0.41 770.01 01-MAR-09:01 0.58
April 0.161222E+09 0.43 770.01 01-APR-15:02 0.58
May 0.225555E+09 0.45 770.01 01-MAY-15:02 0.58
June 0.260393E+09 0.46 770.01 01-JUN-08:62 0.58
July 0.390186E+09 0.49 770.01 01-JUL-08:62 0.58
August 0.337963E+09 0.48 770.01 01-AUG-08:62 0.58
September 0.201558E+09 0.44 770.01 01-SEP-15:02 0.58
October 0.142037E+09 0.42 770.01 01-OCT-15:02 0.58
November 0.210255E+09 0.43 770.01 01-NOV-08:62 0.58
December 0.283040E+09 0.47 770.01 01-DEC-09:01 0.58
           
Annual Sum or Average 0.289437E+10 0.45      
Minimum of Months 0.142037E+09 0.41 770.01   0.58
Maximum of Months 0.390186E+09 0.49 770.01   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.589716E+09 0.28 871.54 05-JAN-06:00 0.58
February 0.274734E+09 0.12 1615.24 08-FEB-14:00 0.59
March 0.337561E+09 0.11 2729.15 02-MAR-13:30 0.58
April 0.549445E+09 0.20 1736.45 27-APR-13:10 0.58
May 0.714689E+09 0.25 1726.14 04-MAY-13:10 0.58
June 0.791445E+09 0.31 1276.27 28-JUN-13:10 0.58
July 0.115865E+10 0.38 1618.92 31-JUL-13:20 0.58
August 0.133159E+10 0.39 2711.15 24-AUG-13:00 0.58
September 0.128629E+10 0.32 3097.42 10-SEP-12:40 0.58
October 0.714622E+09 0.17 3517.14 07-OCT-12:30 0.58
November 0.179923E+09 0.09 1474.09 04-NOV-13:40 0.58
December 0.615642E+09 0.26 1461.71 05-DEC-12:25 0.58
           
Annual Sum or Average 0.854431E+10 0.24      
Minimum of Months 0.179923E+09 0.09 871.54   0.58
Maximum of Months 0.133159E+10 0.39 3517.14   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.932200E+09 0.41 3555.40 01-JAN-16:01 0.58
February 0.732129E+09 0.41 3555.40 01-FEB-16:02 0.58
March 0.554119E+09 0.41 3555.40 02-MAR-09:01 0.58
April 0.782833E+09 0.41 3555.40 01-APR-08:62 0.58
May 0.128392E+10 0.41 3555.40 01-MAY-15:02 0.58
June 0.163692E+10 0.41 3555.40 01-JUN-08:62 0.58
July 0.194972E+10 0.41 3555.40 01-JUL-08:62 0.58
August 0.176454E+10 0.41 3555.40 01-AUG-08:62 0.58
September 0.108236E+10 0.41 3555.40 01-SEP-15:02 0.58
October 0.588931E+09 0.41 3555.40 01-OCT-08:62 0.58
November 0.634629E+09 0.41 3555.40 04-NOV-08:63 0.58
December 0.878431E+09 0.41 3555.40 01-DEC-09:01 0.58
           
Annual Sum or Average 0.128207E+11 0.41      
Minimum of Months 0.554119E+09 0.41 3555.40   0.58
Maximum of Months 0.194972E+10 0.41 3555.40   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.265467E+09 0.45 765.18 01-JAN-09:01 0.58
February 0.189975E+09 0.43 765.18 01-FEB-09:02 0.58
March 0.165802E+09 0.43 765.18 01-MAR-09:01 0.58
April 0.196042E+09 0.47 765.18 01-APR-08:62 0.58
May 0.238342E+09 0.49 765.18 01-MAY-15:02 0.58
June 0.307076E+09 0.52 765.18 01-JUN-08:62 0.58
July 0.367620E+09 0.53 765.18 01-JUL-08:62 0.58
August 0.391482E+09 0.52 765.18 01-AUG-08:62 0.58
September 0.258042E+09 0.49 765.18 01-SEP-15:02 0.58
October 0.166736E+09 0.45 765.18 01-OCT-15:02 0.58
November 0.191124E+09 0.43 765.18 01-NOV-08:62 0.58
December 0.256017E+09 0.45 765.18 01-DEC-09:01 0.58
           
Annual Sum or Average 0.299372E+10 0.47      
Minimum of Months 0.165802E+09 0.43 765.18   0.58
Maximum of Months 0.391482E+09 0.53 765.18   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.276785E+09 0.49 693.59 01-JAN-09:01 0.58
February 0.197992E+09 0.44 693.59 01-FEB-09:02 0.58
March 0.150930E+09 0.41 693.59 01-MAR-09:01 0.58
April 0.150277E+09 0.43 693.59 01-APR-08:62 0.58
May 0.192796E+09 0.47 693.59 01-MAY-15:02 0.58
June 0.271018E+09 0.50 693.59 01-JUN-08:62 0.58
July 0.316556E+09 0.52 693.59 01-JUL-08:62 0.58
August 0.322247E+09 0.51 693.59 01-AUG-08:62 0.58
September 0.172916E+09 0.46 693.59 01-SEP-15:02 0.58
October 0.130771E+09 0.41 693.59 02-OCT-15:02 0.58
November 0.193170E+09 0.43 693.59 01-NOV-08:62 0.58
December 0.263902E+09 0.48 693.59 01-DEC-09:01 0.58
           
Annual Sum or Average 0.263936E+10 0.46      
Minimum of Months 0.130771E+09 0.41 693.59   0.58
Maximum of Months 0.322247E+09 0.52 693.59   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 87849408.13 0.49 223.49 01-JAN-09:01 0.58
February 63677169.45 0.45 223.49 01-FEB-09:02 0.58
March 55969249.45 0.43 223.49 01-MAR-09:01 0.58
April 56714123.38 0.45 223.49 01-APR-15:02 0.58
May 72070665.94 0.48 223.49 01-MAY-15:02 0.58
June 75039619.94 0.49 223.49 01-JUN-15:02 0.58
July 0.111236E+09 0.52 223.49 01-JUL-15:02 0.58
August 0.100631E+09 0.51 223.49 01-AUG-08:62 0.58
September 72170794.88 0.48 223.49 01-SEP-15:02 0.58
October 50102548.77 0.44 223.49 01-OCT-15:02 0.58
November 64212234.84 0.45 223.49 01-NOV-08:62 0.58
December 83977818.57 0.48 223.49 01-DEC-09:01 0.58
           
Annual Sum or Average 0.893651E+09 0.47      
Minimum of Months 50102548.77 0.43 223.49   0.58
Maximum of Months 0.111236E+09 0.52 223.49   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 89393003.22 0.54 199.33 01-JAN-09:01 0.58
February 65693632.77 0.48 199.33 01-FEB-09:02 0.58
March 52934715.65 0.42 199.33 01-MAR-09:01 0.58
April 47246991.46 0.43 199.33 01-APR-15:02 0.58
May 59876357.41 0.46 199.33 02-MAY-15:02 0.58
June 65547205.17 0.47 199.33 01-JUN-15:02 0.58
July 97815230.93 0.50 199.33 01-JUL-15:02 0.58
August 82287710.03 0.48 199.33 01-AUG-08:62 0.58
September 49838787.53 0.45 199.33 01-SEP-15:02 0.58
October 43714880.19 0.41 199.33 01-OCT-15:02 0.58
November 65054113.71 0.47 199.33 01-NOV-08:62 0.58
December 85739126.69 0.51 199.33 01-DEC-09:01 0.58
           
Annual Sum or Average 0.805142E+09 0.47      
Minimum of Months 43714880.19 0.41 199.33   0.58
Maximum of Months 97815230.93 0.54 199.33   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.343225E+09 0.44 1208.43 01-JAN-09:01 0.58
February 0.291223E+09 0.45 1208.43 01-FEB-09:02 0.58
March 0.300199E+09 0.47 1208.43 01-MAR-16:02 0.58
April 0.321850E+09 0.48 1208.43 01-APR-15:02 0.58
May 0.354140E+09 0.49 1208.43 01-MAY-15:02 0.58
June 0.370990E+09 0.50 1208.43 01-JUN-15:02 0.58
July 0.493923E+09 0.52 1208.43 01-JUL-08:62 0.58
August 0.528873E+09 0.51 1208.43 01-AUG-08:62 0.58
September 0.475558E+09 0.49 1208.43 01-SEP-15:02 0.58
October 0.334291E+09 0.47 1208.43 01-OCT-15:02 0.58
November 0.264879E+09 0.44 1208.43 02-NOV-15:02 0.58
December 0.354937E+09 0.46 1208.43 01-DEC-09:01 0.58
           
Annual Sum or Average 0.443409E+10 0.48      
Minimum of Months 0.264879E+09 0.44 1208.43   0.58
Maximum of Months 0.528873E+09 0.52 1208.43   0.58



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.679935E+09 0.611942E+09 687.37 12-JAN-09:01 618.64 618.64 36.15 1.20
February 0.463956E+09 0.417561E+09 681.01 11-FEB-16:01 612.91 612.91 53.24 1.17
March 0.356540E+09 0.320886E+09 703.09 03-MAR-09:02 632.78 632.78 38.34 1.26
April 0.224559E+09 0.202103E+09 573.90 11-APR-09:17 516.51 516.51 65.70 0.84
May 0.155786E+09 0.140207E+09 579.05 18-MAY-08:62 521.14 521.14 32.23 0.87
June 48770197.73 43893177.96 476.18 15-JUN-03:37 428.56 428.56 47.99 0.64
July 14112122.85 12700910.57 206.55 12-JUL-08:07 185.90 185.90 34.12 0.23
August 11975302.84 10777772.56 232.72 03-AUG-08:05 209.45 209.45 44.80 0.26
September 61626148.35 55463533.52 549.54 27-SEP-04:40 494.58 494.58 46.56 0.79
October 0.281366E+09 0.253230E+09 589.99 31-OCT-03:05 530.99 530.99 48.17 0.89
November 0.473867E+09 0.426480E+09 704.49 10-NOV-09:01 634.04 634.04 43.98 1.26
December 0.653735E+09 0.588361E+09 704.93 20-DEC-09:03 634.43 634.43 40.95 1.27
                 
Annual Sum or Average 0.342623E+10 0.308360E+10            
Minimum of Months 11975302.84 10777772.56 206.55   185.90 185.90 32.23 0.23
Maximum of Months 0.679935E+09 0.611942E+09 704.93   634.43 634.43 65.70 1.27



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 62705627.04 56435064.33 1463.68 20-JAN-19:04 1317.31 1317.31 8.40 2.51
February 0.408255E+09 0.367430E+09 3125.57 27-FEB-16:02 2813.02 2813.02 7.83 6.91
March 0.972102E+09 0.874892E+09 3594.57 18-MAR-15:02 3235.11 3235.11 7.73 8.97
April 0.226512E+10 0.203861E+10 4285.87 26-APR-15:02 3857.28 3857.28 6.99 15.02
May 0.368635E+10 0.331772E+10 4368.73 04-MAY-18:03 3931.86 3931.86 7.33 16.37
June 0.498786E+10 0.448908E+10 4366.39 27-JUN-18:03 3929.75 3929.75 7.27 16.33
July 0.644019E+10 0.579617E+10 4363.02 19-JUL-18:03 3926.72 3926.72 7.34 16.28
August 0.688449E+10 0.619605E+10 4383.35 10-AUG-18:03 3945.02 3945.02 6.73 16.62
September 0.437907E+10 0.394116E+10 4327.83 08-SEP-15:02 3895.05 3895.05 7.32 15.69
October 0.186423E+10 0.167780E+10 3983.94 04-OCT-15:02 3585.55 3585.55 7.49 11.54
November 0.399323E+09 0.359391E+09 3835.87 04-NOV-15:02 3452.29 3452.29 7.58 10.41
December 0.153372E+09 0.138035E+09 1721.73 05-DEC-12:30 1549.56 1549.56 8.40 3.05
                 
Annual Sum or Average 0.325031E+11 0.292528E+11            
Minimum of Months 62705627.04 56435064.33 1463.68   1317.31 1317.31 6.73 2.51
Maximum of Months 0.688449E+10 0.619605E+10 4383.35   3945.02 3945.02 8.40 16.62



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.322773E+10 0.290496E+10 3825.90 01-JAN-00:05 3443.31 3443.31 8.41 26.81
February 0.410642E+10 0.369578E+10 3825.90 01-FEB-06:20 3443.31 3443.31 8.41 26.81
March 0.631237E+10 0.568113E+10 3825.90 01-MAR-00:03 3443.31 3443.31 8.41 26.81
April 0.779502E+10 0.701552E+10 3825.90 01-APR-02:30 3443.31 3443.31 8.40 26.81
May 0.942521E+10 0.848269E+10 3825.90 01-MAY-00:05 3443.31 3443.31 8.45 26.81
June 0.968977E+10 0.872080E+10 3825.90 01-JUN-00:05 3443.31 3443.31 8.58 26.81
July 0.101698E+11 0.915283E+10 3825.90 01-JUL-00:10 3443.31 3443.31 8.73 26.81
August 0.101631E+11 0.914680E+10 3825.90 01-AUG-00:05 3443.31 3443.31 8.95 26.81
September 0.929942E+10 0.836947E+10 3825.90 01-SEP-00:05 3443.31 3443.31 8.74 26.81
October 0.705688E+10 0.635119E+10 3825.90 01-OCT-00:10 3443.31 3443.31 8.48 26.81
November 0.422182E+10 0.379964E+10 3825.90 01-NOV-05:02 3443.31 3443.31 8.42 26.81
December 0.390089E+10 0.351080E+10 3825.90 01-DEC-00:03 3443.31 3443.31 8.40 26.81
                 
Annual Sum or Average 0.853684E+11 0.768316E+11            
Minimum of Months 0.322773E+10 0.290496E+10 3825.90   3443.31 3443.31 8.40 26.81
Maximum of Months 0.101698E+11 0.915283E+10 3825.90   3443.31 3443.31 8.95 26.81



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:05 14.37 14.37 48.50 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:03 14.37 14.37 37.55 0.08
March 0.128314E+09 38494137.67 47.91 01-MAR-00:03 14.37 14.37 49.08 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:05 14.37 14.37 51.90 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:05 14.37 14.37 51.91 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:05 14.37 14.37 52.22 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 52.88 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:05 14.37 14.37 52.68 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:05 14.37 14.37 52.66 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 51.55 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:03 14.37 14.37 51.56 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:03 14.37 14.37 49.37 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 37.55 0.08
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 52.88 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 54.38 80.09 35476.51 219323.84 12-JAN-09:01
February 0.12 382.71 06-FEB-13:40 79.88 79.88 26408.01 155691.01 20-FEB-19:15
March 0.00 0.00 01-MAR-00:03 45.25 80.09 18244.94 220140.61 03-MAR-09:02
April 0.00 0.00 01-APR-00:05 54.58 79.75 13206.73 128779.20 17-APR-07:50
May 0.00 0.00 01-MAY-00:05 46.49 79.40 10076.73 173204.07 18-MAY-08:62
June 0.00 0.00 01-JUN-00:05 36.02 36.02 3547.43 107998.78 15-JUN-03:03
July 0.00 0.00 01-JUL-00:10 29.74 29.74 944.39 44791.88 13-JUL-08:05
August 0.00 0.00 01-AUG-00:05 41.17 41.17 885.25 44140.32 21-AUG-08:05
September 0.00 0.00 01-SEP-00:05 48.42 48.42 3910.19 115435.05 27-SEP-04:53
October 0.00 0.00 01-OCT-00:10 48.75 79.40 15386.22 158106.80 16-OCT-08:62
November 0.00 0.00 01-NOV-00:03 52.79 79.53 25231.25 194358.47 24-NOV-16:01
December 0.00 0.00 01-DEC-00:03 56.21 80.34 33881.28 221560.93 07-DEC-19:03
                 
Annual Sum or Average 0.01         15556.29    
Minimum of Months 0.00 0.00   29.74 29.74 885.25 44140.32  
Maximum of Months 0.12 382.71   79.88 80.34 35476.51 221560.93  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 1472.61 40919.30 17-JAN-19:04 8.73 8.37 0.00 0.00 01-JAN-00:05
February 5014.28 177851.70 27-FEB-16:02 9.39 7.81 0.00 0.00 01-FEB-00:03
March 9458.93 228614.86 18-MAR-15:02 9.73 7.69 0.00 0.00 01-MAR-00:03
April 28818.14 389660.76 27-APR-18:03 10.34 6.87 0.00 0.00 01-APR-00:05
May 48715.51 379435.57 05-MAY-18:02 10.66 7.28 0.00 0.00 01-MAY-00:05
June 75578.72 410038.20 28-JUN-18:03 10.54 6.90 0.00 0.00 01-JUN-00:05
July 115386.77 468774.74 31-JUL-18:03 10.92 6.74 0.00 0.00 01-JUL-00:10
August 137591.27 504116.44 10-AUG-18:03 11.19 6.70 0.00 0.00 01-AUG-00:05
September 67952.27 410456.17 14-SEP-15:03 10.76 7.11 0.00 0.00 01-SEP-00:05
October 19783.57 340741.13 04-OCT-15:02 10.50 7.47 0.00 0.00 01-OCT-00:10
November 5119.50 252242.78 04-NOV-15:02 9.81 7.57 0.00 0.00 01-NOV-00:03
December 2344.21 49410.07 19-DEC-19:03 8.81 8.37 0.00 0.00 01-DEC-00:03
                 
Annual Sum or Average 43402.19         0.00    
Minimum of Months 1472.61 40919.30   8.73 6.70 0.00 0.00  
Maximum of Months 137591.27 504116.44   11.19 8.37 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 48.50 59.71 27446.20 68449.74 11-JAN-07:11
February 0.00 0.00 01-FEB-00:03 37.55 58.74 27623.55 68465.66 01-FEB-07:51
March 0.00 0.00 01-MAR-00:03 49.08 59.24 27328.96 68642.19 07-MAR-07:51
April 0.00 0.00 01-APR-00:05 51.90 59.73 26606.49 66047.25 01-APR-07:11
May 0.00 0.00 01-MAY-00:05 51.91 58.99 25674.46 60849.28 19-MAY-06:14
June 0.00 0.00 01-JUN-00:05 52.22 59.02 24795.16 58820.16 15-JUN-06:38
July 0.00 0.00 01-JUL-00:10 52.88 59.66 24143.78 52501.01 03-JUL-06:10
August 0.00 0.00 01-AUG-00:05 52.68 59.50 23968.35 53374.20 18-AUG-06:37
September 0.00 0.00 01-SEP-00:05 52.66 59.49 24246.92 58025.01 27-SEP-06:55
October 0.00 0.00 01-OCT-00:10 51.55 58.83 24908.02 61489.80 13-OCT-06:11
November 0.00 0.00 01-NOV-00:03 51.56 58.69 25872.58 60478.41 19-NOV-07:51
December 0.00 0.00 01-DEC-00:03 49.37 59.42 26800.76 67787.61 28-DEC-07:01
                 
Annual Sum or Average 0.00         25773.92    
Minimum of Months 0.00 0.00   37.55 58.69 23968.35 52501.01  
Maximum of Months 0.00 0.00   52.88 59.73 27623.55 68642.19  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.450811E+11 0.00 0.305234E+09 0.334175E+11 0.00 0.00
February 0.337642E+11 0.00 0.205599E+10 0.303218E+11 0.00 0.00
March 0.353096E+11 0.00 0.420411E+10 0.347687E+11 0.00 0.00
April 0.294846E+11 0.00 0.286744E+11 0.342965E+11 0.00 0.00
May 0.257190E+11 0.00 0.552908E+11 0.363308E+11 0.00 0.00
June 0.895561E+10 0.00 0.985683E+11 0.353395E+11 0.00 0.00
July 0.246180E+10 0.00 0.167844E+12 0.372988E+11 0.00 0.00
August 0.229327E+10 0.00 0.212712E+12 0.378723E+11 0.00 0.00
September 0.944457E+10 0.00 0.808736E+11 0.355130E+11 0.00 0.00
October 0.344299E+11 0.00 0.149364E+11 0.360095E+11 0.00 0.00
November 0.407597E+11 0.00 0.365309E+10 0.336614E+11 0.00 0.00
December 0.447300E+11 0.00 0.377485E+09 0.339541E+11 0.00 0.00
             
Annual Sum or Average 0.312433E+12 0.00 0.669495E+12 0.418784E+12 0.00 0.00
Minimum of Months 0.229327E+10 0.00 0.305234E+09 0.303218E+11 0.00 0.00
Maximum of Months 0.450811E+11 0.00 0.212712E+12 0.378723E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.757373E+09 0.00 0.00 0.587890E+10 0.00 0.00
February 0.440027E+09 0.00 0.332455E+09 0.530997E+10 0.00 0.00
March 43850.61 0.00 0.656272E+09 0.587890E+10 0.00 0.00
April 10297.38 0.00 0.473027E+10 0.568926E+10 0.00 0.00
May 20408.65 0.00 0.970367E+10 0.587890E+10 0.00 0.00
June 39911.50 0.00 0.167744E+11 0.568926E+10 0.00 0.00
July 46517.19 0.00 0.301164E+11 0.587890E+10 0.00 0.00
August 52882.47 0.00 0.384432E+11 0.587890E+10 0.00 0.00
September 36426.23 0.00 0.144140E+11 0.568926E+10 0.00 0.00
October 20022.12 0.00 0.254416E+10 0.587890E+10 0.00 0.00
November 4380454.05 0.00 0.658452E+09 0.568926E+10 0.00 0.00
December 0.229519E+09 0.00 7193.64 0.587890E+10 0.00 0.00
             
Annual Sum or Average 0.143157E+10 0.00 0.118373E+12 0.692193E+11 0.00 0.00
Minimum of Months 10297.38 0.00 0.00 0.530997E+10 0.00 0.00
Maximum of Months 0.757373E+09 0.00 0.384432E+11 0.587890E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.334175E+11 0.305234E+09 0.450811E+11 0.408859E+12 0.00 0.00 0.00 0.00
February 0.303218E+11 0.205599E+10 0.337642E+11 0.313363E+12 0.00 0.00 0.00 0.00
March 0.347687E+11 0.420596E+10 0.353096E+11 0.226039E+12 0.00 0.00 0.00 0.00
April 0.342965E+11 0.286744E+11 0.294846E+11 0.133169E+12 0.185321E+09 0.00 0.00 0.00
May 0.363308E+11 0.552908E+11 0.257190E+11 0.717191E+11 0.00 0.00 0.00 0.00
June 0.353395E+11 0.985683E+11 0.895561E+10 0.232756E+11 1444913.24 0.00 0.00 0.00
July 0.372988E+11 0.167844E+12 0.246180E+10 0.841061E+10 0.237138E+10 0.00 0.00 0.00
August 0.378723E+11 0.212712E+12 0.229327E+10 0.762315E+10 0.687223E+10 0.00 0.00 0.00
September 0.355130E+11 0.808736E+11 0.944457E+10 0.250346E+11 0.00 0.00 0.00 0.00
October 0.360095E+11 0.149367E+11 0.344299E+11 0.914248E+11 0.00 0.00 0.00 0.00
November 0.336614E+11 0.365316E+10 0.407597E+11 0.227999E+12 0.00 0.00 0.00 0.00
December 0.339541E+11 0.377488E+09 0.447300E+11 0.364912E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.418784E+12 0.669497E+12 0.312433E+12 0.190183E+13 0.943038E+10 0.00 0.00 0.00
Minimum of Months 0.303218E+11 0.305234E+09 0.229327E+10 0.762315E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.378723E+11 0.212712E+12 0.450811E+11 0.408859E+12 0.687223E+10 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.587890E+10 0.00 0.757373E+09 0.778261E+11 0.00 0.00 0.00 0.00
February 0.530997E+10 0.332455E+09 0.440027E+09 0.613938E+11 0.00 0.00 0.00 0.00
March 0.587890E+10 0.656272E+09 43850.61 0.500948E+11 0.00 0.00 0.00 0.00
April 0.568926E+10 0.473027E+10 10297.38 0.335072E+11 0.236875E+09 0.00 0.00 0.00
May 0.587890E+10 0.970367E+10 20408.65 0.215303E+11 0.164330E+09 0.00 0.00 0.00
June 0.568926E+10 0.167744E+11 39911.50 0.805486E+10 0.180189E+09 0.00 0.00 0.00
July 0.587890E+10 0.301164E+11 46517.19 0.279146E+10 0.238681E+10 0.00 0.00 0.00
August 0.587890E+10 0.384432E+11 52882.47 0.207611E+10 0.517852E+10 0.00 0.00 0.00
September 0.568926E+10 0.144140E+11 36426.23 0.850301E+10 0.466123E+09 0.00 0.00 0.00
October 0.587890E+10 0.254416E+10 20022.12 0.278872E+11 0.00 0.00 0.00 0.00
November 0.568926E+10 0.658452E+09 4380454.05 0.504869E+11 0.00 0.00 0.00 0.00
December 0.587890E+10 7193.64 0.229519E+09 0.715974E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.692193E+11 0.118373E+12 0.143157E+10 0.415749E+12 0.861285E+10 0.00 0.00 0.00
Minimum of Months 0.530997E+10 0.00 10297.38 0.207611E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.384432E+11 0.757373E+09 0.778261E+11 0.517852E+10 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.334175E+11 0.450811E+11 0.305234E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.303218E+11 0.337642E+11 0.205599E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.347687E+11 0.353096E+11 0.420411E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.342965E+11 0.294846E+11 0.286744E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.363308E+11 0.257190E+11 0.552908E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.353395E+11 0.895561E+10 0.985683E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.372988E+11 0.246180E+10 0.167844E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.378723E+11 0.229327E+10 0.212712E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.355130E+11 0.944457E+10 0.808736E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.360095E+11 0.344299E+11 0.149364E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.336614E+11 0.407597E+11 0.365309E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.339541E+11 0.447300E+11 0.377485E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.418784E+12 0.312433E+12 0.669495E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.303218E+11 0.229327E+10 0.305234E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.378723E+11 0.450811E+11 0.212712E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.587890E+10 0.757373E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.530997E+10 0.440027E+09 0.332455E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.587890E+10 43850.61 0.656272E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.568926E+10 10297.38 0.473027E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.587890E+10 20408.65 0.970367E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.568926E+10 39911.50 0.167744E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.587890E+10 46517.19 0.301164E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.587890E+10 52882.47 0.384432E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.568926E+10 36426.23 0.144140E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.587890E+10 20022.12 0.254416E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.568926E+10 4380454.05 0.658452E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.587890E+10 0.229519E+09 7193.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.692193E+11 0.143157E+10 0.118373E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.530997E+10 10297.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.757373E+09 0.384432E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.278285E+11 0.00 0.00 24216832.50 0.00 0.00 0.199923E+11 0.00 0.92
February 0.328880E+11 0.00 0.00 10248514.80 0.00 0.00 0.102834E+11 0.00 0.92
March 0.420264E+11 0.00 0.00 4520974.64 0.00 0.00 0.683387E+10 0.00 0.90
April 0.416558E+11 0.00 0.00 1678834.00 5884248.33 0.00 0.420263E+10 0.00 0.91
May 0.394766E+11 0.00 0.00 2787745.37 0.00 0.00 0.606874E+10 0.00 0.93
June 0.316327E+11 0.00 0.00 5206330.09 0.00 0.00 0.760050E+10 0.00 0.96
July 0.191139E+11 4879029.82 0.00 11120146.43 89021532.71 0.00 0.156264E+11 0.00 0.97
August 0.861715E+10 11508702.24 0.00 19456551.18 0.318966E+09 0.00 0.228217E+11 0.00 0.98
September 0.107218E+11 0.00 0.00 33470451.07 0.00 0.00 0.317965E+11 0.00 0.99
October 0.116694E+11 0.00 0.00 61599146.78 0.00 0.00 0.415248E+11 0.00 0.99
November 0.860977E+10 0.00 0.00 76757564.38 0.00 0.00 0.421849E+11 0.00 0.97
December 0.170941E+11 0.00 0.00 58230408.01 0.00 0.00 0.330875E+11 0.00 0.95
                   
Annual Sum or Average 0.291334E+12 16387732.06 0.00 0.309293E+09 0.413872E+09 0.00 0.242023E+12 0.00 0.95
Minimum of Months 0.860977E+10 0.00 0.00 1678834.00 0.00 0.00 0.420263E+10 0.00 0.90
Maximum of Months 0.420264E+11 11508702.24 0.00 76757564.38 0.318966E+09 0.00 0.421849E+11 0.00 0.99



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.630337E+10 0.00 0.00 77443.48 0.00 0.228825E+10 70887461.48 0.00 3.03
February 0.674917E+10 0.00 0.00 494184.90 0.00 0.920675E+09 0.301215E+09 0.00 3.06
March 0.852400E+10 0.00 0.00 715454.32 0.00 66318957.62 0.493292E+09 0.00 3.03
April 0.807530E+10 1449072.41 0.00 615995.52 0.00 29576558.70 0.388978E+09 0.00 3.05
May 0.803696E+10 0.00 0.00 662963.42 0.00 12895102.30 0.385159E+09 0.00 3.12
June 0.703120E+10 0.00 0.00 346090.61 0.00 2057521.75 0.229612E+09 0.00 3.20
July 0.605222E+10 15228749.05 0.00 908175.48 2888366.22 0.00 0.349146E+09 0.00 3.25
August 0.533133E+10 66408907.00 0.00 1183388.71 4727780.27 0.00 0.403964E+09 0.00 3.29
September 0.680974E+10 0.00 0.00 2283495.46 0.00 7898411.62 0.835072E+09 0.00 3.29
October 0.838821E+10 0.00 0.00 1115644.83 0.00 50792618.24 0.729230E+09 0.00 3.11
November 0.799134E+10 0.00 0.00 258029.96 0.00 0.536329E+09 0.128805E+09 0.00 3.03
December 0.638956E+10 0.00 0.00 260581.84 0.00 0.218195E+10 0.190784E+09 0.00 3.02
                   
Annual Sum or Average 0.856824E+11 83086728.46 0.00 8921448.54 7616146.49 0.609674E+10 0.450615E+10 0.00 3.12
Minimum of Months 0.533133E+10 0.00 0.00 77443.48 0.00 0.00 70887461.48 0.00 3.02
Maximum of Months 0.852400E+10 66408907.00 0.00 2283495.46 4727780.27 0.228825E+10 0.835072E+09 0.00 3.29



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.436961E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.32
February 0.394219E+10 0.00 0.00 22267.59 0.00 0.00 67035690.07 0.00 1.33
March 0.436816E+10 0.00 0.00 81241.99 0.00 0.00 0.190270E+09 0.00 1.32
April 0.376015E+10 0.00 0.00 338699.93 549452.37 0.00 0.529717E+09 0.00 1.33
May 0.327102E+10 0.00 0.00 716613.51 0.00 0.00 0.996759E+09 0.00 1.37
June 0.248697E+10 0.00 0.00 944471.96 0.00 0.00 0.119903E+10 0.00 1.41
July 0.150461E+10 5039040.11 0.00 1741253.47 3766296.38 0.00 0.178891E+10 0.00 1.45
August 0.131278E+10 16637716.05 0.00 2083307.45 14507581.88 0.00 0.164169E+10 0.00 1.46
September 0.245683E+10 0.00 0.00 1268533.95 0.00 0.00 0.141682E+10 0.00 1.42
October 0.404546E+10 0.00 0.00 332961.79 0.00 0.00 0.552974E+09 0.00 1.34
November 0.430412E+10 0.00 0.00 11997.75 0.00 0.00 57025155.57 0.00 1.32
December 0.440756E+10 0.00 0.00 3552.09 0.00 0.00 10817232.79 0.00 1.32
                   
Annual Sum or Average 0.402295E+11 21676756.16 0.00 7544901.48 18823330.63 0.00 0.845105E+10 0.00 1.37
Minimum of Months 0.131278E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.32
Maximum of Months 0.440756E+10 16637716.05 0.00 2083307.45 14507581.88 0.00 0.178891E+10 0.00 1.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.395423E+10 0.00 0.00 0.00 0.00 24211429.09 0.00 0.00 0.57
February 0.365004E+10 0.00 0.00 0.00 0.00 297734.64 0.00 0.00 0.57
March 0.415043E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.57
April 0.389891E+10 0.00 0.00 0.00 500264.50 0.00 0.00 0.00 0.57
May 0.387010E+10 0.00 0.00 193.32 0.00 0.00 2016815.10 0.00 0.59
June 0.327181E+10 0.00 0.00 32153.76 0.00 0.00 64106008.95 0.00 0.60
July 0.268869E+10 198182.47 0.00 261364.80 7785015.30 0.00 0.254134E+09 0.00 0.61
August 0.235173E+10 1325944.77 0.00 447449.99 26803627.52 0.00 0.288602E+09 0.00 0.61
September 0.341022E+10 0.00 0.00 58666.37 0.00 0.00 73479776.93 0.00 0.60
October 0.418127E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.58
November 0.397074E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.57
December 0.401544E+10 0.00 0.00 0.00 0.00 7397102.98 0.00 0.00 0.57
                   
Annual Sum or Average 0.434136E+11 1524127.25 0.00 799828.25 35088907.32 31906266.71 0.682338E+09 0.00 0.58
Minimum of Months 0.235173E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.57
Maximum of Months 0.418127E+10 1325944.77 0.00 447449.99 26803627.52 24211429.09 0.288602E+09 0.00 0.61



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.166667E+10 0.00 0.00 0.00 0.00 0.250288E+09 0.00 0.00 0.47
February 0.161067E+10 0.00 0.00 0.00 0.00 0.148193E+09 0.00 0.00 0.48
March 0.199960E+10 0.00 0.00 0.00 0.00 231611.26 0.00 0.00 0.47
April 0.187864E+10 0.00 0.00 0.00 241046.08 0.00 0.00 0.00 0.48
May 0.186573E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.49
June 0.160739E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.50
July 0.141439E+10 0.00 0.00 1315.39 3846602.20 0.00 2274173.98 0.00 0.51
August 0.126097E+10 140826.55 0.00 8197.41 13396253.96 0.00 7256559.66 0.00 0.51
September 0.167860E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.50
October 0.201469E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.48
November 0.191218E+10 0.00 0.00 0.00 0.00 1066599.57 0.00 0.00 0.47
December 0.179832E+10 0.00 0.00 0.00 0.00 0.140038E+09 0.00 0.00 0.47
                   
Annual Sum or Average 0.207079E+11 140826.55 0.00 9512.80 17483902.25 0.539818E+09 9530733.63 0.00 0.49
Minimum of Months 0.126097E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.47
Maximum of Months 0.201469E+10 140826.55 0.00 8197.41 13396253.96 0.250288E+09 7256559.66 0.00 0.51



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.112713E+10 0.00 0.00 0.148702E+09 0.00 0.00 0.693350E+11 0.00 20.83
February 0.934178E+09 0.00 0.00 0.122034E+09 0.00 0.00 0.635408E+11 0.00 21.00
March 0.856175E+09 0.00 0.00 0.156337E+09 0.00 0.00 0.733778E+11 0.00 21.01
April 0.175768E+10 7501209.62 0.00 0.139303E+09 0.00 0.00 0.674688E+11 0.00 21.15
May 0.201856E+10 0.00 0.00 0.125779E+09 0.00 0.00 0.669759E+11 0.00 21.79
June 0.614667E+09 0.00 0.00 0.101550E+09 0.00 0.00 0.582137E+11 0.00 22.42
July 85965541.42 0.130517E+09 0.00 99742781.43 29059.38 0.00 0.513480E+11 0.00 22.60
August 0.129136E+09 0.445219E+09 0.00 93888751.52 891167.52 0.00 0.460542E+11 0.00 22.59
September 0.530094E+09 0.00 0.00 0.101090E+09 0.00 0.00 0.611063E+11 0.00 22.39
October 0.183400E+10 0.00 0.00 0.134606E+09 0.00 0.00 0.724991E+11 0.00 21.38
November 0.793437E+09 0.00 0.00 0.155391E+09 0.00 0.00 0.695757E+11 0.00 20.84
December 0.763487E+09 0.00 0.00 0.177737E+09 0.00 0.00 0.705051E+11 0.00 20.67
                   
Annual Sum or Average 0.114445E+11 0.583237E+09 0.00 0.155616E+10 920226.91 0.00 0.770000E+12 0.00 21.56
Minimum of Months 85965541.42 0.00 0.00 93888751.52 0.00 0.00 0.460542E+11 0.00 20.67
Maximum of Months 0.201856E+10 0.445219E+09 0.00 0.177737E+09 891167.52 0.00 0.733778E+11 0.00 22.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.315899E+11 0.00 0.00 934795.53 0.00 4458069.02 0.181418E+10 0.00 4.16
February 0.244500E+11 0.00 0.00 4483345.59 0.00 0.00 0.632584E+10 0.00 4.21
March 0.235352E+11 0.00 0.00 7195816.03 0.00 703715.05 0.115537E+11 0.00 4.18
April 0.196128E+11 5228754.32 0.00 8560363.35 0.00 0.00 0.131643E+11 0.00 4.20
May 0.167679E+11 0.00 0.00 10785073.66 0.00 0.00 0.157674E+11 0.00 4.29
June 0.109870E+11 0.00 0.00 11702806.21 0.00 0.00 0.170080E+11 0.00 4.41
July 0.708281E+10 63183057.40 0.00 17513479.61 5591042.57 0.00 0.175953E+11 0.00 4.47
August 0.579374E+10 0.255101E+09 0.00 18971333.63 7814214.90 0.00 0.163523E+11 0.00 4.51
September 0.108513E+11 0.00 0.00 20373610.40 0.00 0.00 0.186483E+11 0.00 4.52
October 0.205117E+11 0.00 0.00 11121507.88 0.00 3681669.12 0.148643E+11 0.00 4.27
November 0.277040E+11 0.00 0.00 2638886.40 0.00 593961.86 0.569540E+10 0.00 4.17
December 0.306853E+11 0.00 0.00 2240099.72 0.00 4108273.72 0.312589E+10 0.00 4.14
                   
Annual Sum or Average 0.229572E+12 0.323513E+09 0.00 0.116521E+09 13405257.47 13545688.77 0.141915E+12 0.00 4.29
Minimum of Months 0.579374E+10 0.00 0.00 934795.53 0.00 0.00 0.181418E+10 0.00 4.14
Maximum of Months 0.315899E+11 0.255101E+09 0.00 20373610.40 7814214.90 4458069.02 0.186483E+11 0.00 4.52



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.869305E+11 0.00 0.00 1842226.89 0.00 0.00 0.508479E+10 0.00 1.66
February 0.708882E+11 0.00 0.00 7669304.86 0.00 0.00 0.136403E+11 0.00 1.67
March 0.631478E+11 0.00 0.00 25069901.01 0.00 0.00 0.333634E+11 0.00 1.66
April 0.525332E+11 11470501.58 0.00 33085253.88 96272.23 0.00 0.383422E+11 0.00 1.68
May 0.417517E+11 0.00 0.00 50833255.74 0.00 0.00 0.492758E+11 0.00 1.73
June 0.282185E+11 0.00 0.00 54363765.28 0.00 0.00 0.503697E+11 0.00 1.79
July 0.144021E+11 0.155686E+09 0.00 73006468.57 29400442.10 0.00 0.562536E+11 0.00 1.84
August 0.123544E+11 0.581085E+09 0.00 77374640.93 73309776.87 0.00 0.517192E+11 0.00 1.86
September 0.251224E+11 0.00 0.00 69679478.02 0.00 0.00 0.576965E+11 0.00 1.81
October 0.532651E+11 0.00 0.00 38371332.00 0.00 0.00 0.443555E+11 0.00 1.70
November 0.746678E+11 0.00 0.00 8683778.66 0.00 0.00 0.172306E+11 0.00 1.66
December 0.844294E+11 0.00 0.00 4486352.15 0.00 0.00 0.864591E+10 0.00 1.65
                   
Annual Sum or Average 0.607711E+12 0.748241E+09 0.00 0.444466E+09 0.102806E+09 0.00 0.425978E+12 0.00 1.73
Minimum of Months 0.123544E+11 0.00 0.00 1842226.89 0.00 0.00 0.508479E+10 0.00 1.65
Maximum of Months 0.869305E+11 0.581085E+09 0.00 77374640.93 73309776.87 0.00 0.576965E+11 0.00 1.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.338508E+09 0.00 0.00 125366.84 0.00 0.110231E+10 6685546.12 0.00 0.47
February 0.350488E+09 0.00 0.00 1274270.94 0.00 0.899590E+09 0.147441E+09 0.00 0.47
March 0.426061E+09 0.00 0.00 3361642.29 0.00 0.839564E+09 0.404125E+09 0.00 0.47
April 0.363840E+09 2081360.56 0.00 6603529.87 20255.75 0.432550E+09 0.799940E+09 0.00 0.47
May 0.265821E+09 3777161.81 5444.62 11535756.29 157281.01 0.143696E+09 0.114016E+10 126.61 0.47
June 0.207474E+09 1637055.62 0.00 12239501.53 149824.94 22841098.01 0.108717E+10 0.00 0.47
July 0.114544E+09 37858400.61 2514.80 12626766.58 791369.48 1779943.99 0.921644E+09 604.94 0.47
August 0.100853E+09 77010235.28 40563.97 9505630.28 2913716.93 1621325.61 0.728269E+09 4200.84 0.48
September 0.236873E+09 13923012.25 2200.10 10434610.78 439011.56 52183175.07 0.104348E+10 406.48 0.47
October 0.383704E+09 0.00 0.00 4875793.15 0.00 0.579811E+09 0.724700E+09 0.00 0.47
November 0.371695E+09 66290.29 0.00 571647.52 0.00 0.984795E+09 0.127147E+09 0.00 0.47
December 0.333441E+09 0.00 0.00 253553.51 0.00 0.111346E+10 31431577.34 0.00 0.47
                   
Annual Sum or Average 0.349330E+10 0.136354E+09 50723.48 73408069.58 4471459.66 0.617421E+10 0.716219E+10 5338.87 0.47
Minimum of Months 0.100853E+09 0.00 0.00 125366.84 0.00 1621325.61 6685546.12 0.00 0.47
Maximum of Months 0.426061E+09 77010235.28 40563.97 12626766.58 2913716.93 0.111346E+10 0.114016E+10 4200.84 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.279547E+09 0.00 0.00 59151.86 0.00 0.116359E+10 4262535.20 0.00 0.47
February 0.346252E+09 0.00 0.00 383978.84 0.00 0.995421E+09 56572476.86 0.00 0.47
March 0.474016E+09 0.00 0.00 1465853.33 0.00 0.995831E+09 0.201603E+09 0.00 0.47
April 0.426413E+09 2029608.76 0.00 4424671.80 71761.31 0.549324E+09 0.622585E+09 0.00 0.47
May 0.341994E+09 3701862.71 4600.26 9686340.83 232119.13 0.174785E+09 0.103456E+10 970.31 0.47
June 0.258255E+09 1611062.42 0.00 10997858.04 175608.77 26645789.61 0.103367E+10 0.00 0.47
July 0.139745E+09 37242365.10 2365.21 11413984.41 1402876.60 1648939.40 0.897663E+09 754.17 0.47
August 0.122809E+09 73573651.18 37041.81 8326970.00 6340936.77 1763973.79 0.707251E+09 7717.76 0.48
September 0.287567E+09 11753781.37 11067.41 7614650.78 2593774.29 67593908.11 0.980034E+09 4324.29 0.47
October 0.457796E+09 0.00 0.00 2346338.28 0.00 0.753246E+09 0.479504E+09 0.00 0.47
November 0.371672E+09 63269.15 1842.40 196353.94 0.00 0.104173E+10 70439710.59 1170.98 0.47
December 0.304963E+09 0.00 0.00 76267.48 0.00 0.116967E+10 3708636.40 0.00 0.47
                   
Annual Sum or Average 0.381103E+10 0.129976E+09 56917.09 56992419.60 10817076.87 0.694125E+10 0.609186E+10 14937.51 0.47
Minimum of Months 0.122809E+09 0.00 0.00 59151.86 0.00 1648939.40 3708636.40 0.00 0.47
Maximum of Months 0.474016E+09 73573651.18 37041.81 11413984.41 6340936.77 0.116967E+10 0.103456E+10 7717.76 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.132855E+11 0.00 0.00 143781.54 0.00 0.626596E+10 76921191.19 0.00 0.53
February 0.158452E+11 0.00 0.00 14268637.40 0.00 0.148639E+10 0.162048E+10 0.00 0.54
March 0.175300E+11 0.00 0.00 28588424.06 0.00 0.00 0.512733E+10 0.00 0.54
April 0.134440E+11 28496032.19 0.00 36443433.60 0.00 0.00 0.825389E+10 0.00 0.54
May 0.111198E+11 53423056.81 0.00 48196230.80 0.00 0.00 0.100006E+11 0.00 0.54
June 0.774582E+10 24228497.68 0.00 55884508.53 0.00 0.00 0.102282E+11 0.00 0.54
July 0.494462E+10 0.524099E+09 0.00 58529920.98 0.00 0.00 0.924197E+10 0.00 0.54
August 0.402009E+10 0.108430E+10 0.00 45152334.45 0.00 0.00 0.732778E+10 0.00 0.54
September 0.761580E+10 0.194772E+09 0.00 67129338.95 0.00 0.00 0.105265E+11 0.00 0.54
October 0.151110E+11 0.00 0.00 46127328.49 0.00 0.00 0.779968E+10 0.00 0.54
November 0.180170E+11 898836.90 0.00 4440882.73 0.00 0.122160E+10 0.881482E+09 0.00 0.53
December 0.135053E+11 0.00 0.00 6109085.01 0.00 0.569383E+10 0.843094E+09 0.00 0.53
                   
Annual Sum or Average 0.142184E+12 0.191022E+10 0.00 0.411014E+09 0.00 0.146678E+11 0.719279E+11 0.00 0.54
Minimum of Months 0.402009E+10 0.00 0.00 143781.54 0.00 0.00 76921191.19 0.00 0.53
Maximum of Months 0.180170E+11 0.108430E+10 0.00 67129338.95 0.00 0.626596E+10 0.105265E+11 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.518774E+10 0.00 0.00 9457203.74 0.00 0.104333E+11 0.400344E+10 0.00 0.53
February 0.520814E+10 0.00 0.00 15409191.59 0.00 0.741428E+10 0.633374E+10 0.00 0.54
March 0.649696E+10 0.00 0.00 37754347.05 0.00 0.167570E+10 0.144817E+11 0.00 0.54
April 0.614902E+10 12017307.95 51149.59 68986776.89 16430197.62 98883855.51 0.154234E+11 5169.22 0.54
May 0.569640E+10 25683752.59 80434.64 98682378.87 27671858.75 49240175.06 0.153301E+11 1619.27 0.54
June 0.444812E+10 15974212.24 0.00 96536845.77 8260910.68 25226720.72 0.134650E+11 0.00 0.54
July 0.269848E+10 0.294521E+09 259419.80 86245864.43 0.229450E+09 16239205.69 0.114480E+11 11007.30 0.54
August 0.208712E+10 0.528874E+09 508108.66 69632087.92 0.555203E+09 12968265.98 0.922641E+10 15950.61 0.54
September 0.445460E+10 68656075.36 313292.98 65833864.75 0.125831E+09 47360971.52 0.136466E+11 24585.83 0.54
October 0.640889E+10 0.00 0.00 50764033.78 0.00 0.159034E+09 0.163444E+11 0.00 0.54
November 0.535592E+10 866972.57 22832.29 23092511.03 5531.78 0.499436E+10 0.975668E+10 3746.05 0.54
December 0.537785E+10 0.00 0.00 10039270.03 0.00 0.999670E+10 0.466925E+10 0.00 0.53
                   
Annual Sum or Average 0.595692E+11 0.946594E+09 1235237.97 0.632434E+09 0.962852E+09 0.349233E+11 0.134129E+12 62078.27 0.54
Minimum of Months 0.208712E+10 0.00 0.00 9457203.74 0.00 12968265.98 0.400344E+10 0.00 0.53
Maximum of Months 0.649696E+10 0.528874E+09 508108.66 98682378.87 0.555203E+09 0.104333E+11 0.163444E+11 24585.83 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.341156E+09 0.00 0.00 97375.98 0.00 0.109309E+10 13280431.80 0.00 0.47
February 0.369246E+09 0.00 0.00 850494.71 0.00 0.901384E+09 0.127313E+09 0.00 0.47
March 0.408207E+09 0.00 0.00 3602187.90 0.00 0.826954E+09 0.434348E+09 0.00 0.47
April 0.298720E+09 2022647.20 0.00 8008355.33 78969.10 0.417261E+09 0.878944E+09 0.00 0.47
May 0.231001E+09 3715024.24 4314.53 11067881.98 219418.58 0.180468E+09 0.113867E+10 1256.69 0.47
June 0.145879E+09 1555457.94 0.00 14269813.41 231422.61 32036421.21 0.113754E+10 0.00 0.47
July 91421405.79 37078062.21 14710.70 12922431.28 1556473.52 1606414.36 0.944644E+09 3643.41 0.47
August 74329540.88 77538201.29 18331.05 10957295.61 2409532.17 1352403.86 0.753610E+09 2652.52 0.48
September 0.222326E+09 13182114.84 13187.87 10564002.99 1167122.03 59237460.75 0.105084E+10 2205.63 0.47
October 0.350780E+09 0.00 0.00 5261900.89 0.00 0.593694E+09 0.743355E+09 0.00 0.47
November 0.376617E+09 63276.56 2112.22 615583.89 0.00 0.973621E+09 0.133356E+09 901.52 0.47
December 0.332455E+09 0.00 0.00 405802.38 0.00 0.110693E+10 38795516.75 0.00 0.47
                   
Annual Sum or Average 0.324214E+10 0.135155E+09 52656.37 78623126.34 5662938.02 0.618764E+10 0.739470E+10 10659.77 0.47
Minimum of Months 74329540.88 0.00 0.00 97375.98 0.00 1352403.86 13280431.80 0.00 0.47
Maximum of Months 0.408207E+09 77538201.29 18331.05 14269813.41 2409532.17 0.110693E+10 0.113867E+10 3643.41 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.248980E+09 0.00 0.00 68446.23 0.00 0.119358E+10 4826466.61 0.00 0.47
February 0.354708E+09 0.00 0.00 228598.62 0.00 0.982744E+09 60949741.57 0.00 0.47
March 0.478971E+09 0.00 0.00 1273334.64 0.00 0.966324E+09 0.226347E+09 0.00 0.47
April 0.424024E+09 1976030.38 0.00 5355365.10 124714.46 0.508232E+09 0.665134E+09 625.23 0.47
May 0.303196E+09 3661172.48 3667.22 9025580.81 272809.37 0.223788E+09 0.102502E+10 1903.35 0.47
June 0.174996E+09 1505821.55 0.00 12886083.81 280849.64 36794056.82 0.110490E+10 0.00 0.47
July 0.102758E+09 36678535.20 14800.07 11594972.87 1951473.93 1674511.72 0.934444E+09 3551.89 0.47
August 93455659.69 76357186.97 6550.51 9638778.19 3592119.68 1377998.56 0.735678E+09 3490.37 0.48
September 0.271466E+09 11765980.73 32927.13 7360977.89 2559170.84 94025695.75 0.969957E+09 4868.65 0.47
October 0.465448E+09 0.00 0.00 2348284.83 0.00 0.750091E+09 0.475004E+09 0.00 0.47
November 0.367595E+09 63915.29 255.71 193785.72 407.82 0.103875E+10 77497668.97 1703.71 0.47
December 0.291757E+09 0.00 0.00 88589.03 0.00 0.117665E+10 9918754.86 0.00 0.47
                   
Annual Sum or Average 0.357735E+10 0.132009E+09 58200.63 60062797.73 8781545.74 0.697404E+10 0.628967E+10 16143.20 0.47
Minimum of Months 93455659.69 0.00 0.00 68446.23 0.00 1377998.56 4826466.61 0.00 0.47
Maximum of Months 0.478971E+09 76357186.97 32927.13 12886083.81 3592119.68 0.119358E+10 0.110490E+10 4868.65 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.279094E+11 0.00 0.00 0.00 0.00 0.567767E+09 0.00 0.00 0.56
February 0.260816E+11 0.00 0.00 0.00 0.00 47108484.22 0.00 0.00 0.56
March 0.297054E+11 0.00 0.00 0.00 0.00 2904589.62 0.00 0.00 0.55
April 0.279079E+11 0.00 0.00 0.00 3580833.68 0.00 0.00 0.00 0.56
May 0.277162E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.57
June 0.238784E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.59
July 0.208554E+11 711570.59 0.00 183661.68 56431207.64 0.00 0.189479E+09 0.00 0.60
August 0.179511E+11 23252528.29 0.00 1042804.25 0.177867E+09 0.00 0.889103E+09 0.00 0.60
September 0.247062E+11 0.00 0.00 46847.90 0.00 0.00 0.230074E+09 0.00 0.59
October 0.299291E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.57
November 0.283078E+11 0.00 0.00 0.00 0.00 0.114268E+09 0.00 0.00 0.56
December 0.279987E+11 0.00 0.00 0.00 0.00 0.796258E+09 0.00 0.00 0.55
                   
Annual Sum or Average 0.312947E+12 23964098.88 0.00 1273313.83 0.237879E+09 0.152831E+10 0.130866E+10 0.00 0.57
Minimum of Months 0.179511E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.55
Maximum of Months 0.299291E+11 23252528.29 0.00 1042804.25 0.177867E+09 0.796258E+09 0.889103E+09 0.00 0.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 58828780.71 0.00 0.00 19405.39 0.00 0.302209E+09 850270.87 0.00 0.47
February 78032861.88 0.00 0.00 295334.52 0.00 0.247922E+09 23448226.46 0.00 0.47
March 0.106554E+09 0.00 0.00 761203.32 0.00 0.241162E+09 69800106.52 0.00 0.47
April 90244381.26 520340.14 0.00 1479116.14 5063.94 0.153831E+09 0.155179E+09 0.00 0.47
May 66313470.80 945683.26 0.00 2648566.04 39320.25 86005870.87 0.235334E+09 0.00 0.47
June 51422077.74 417789.98 0.00 2888687.86 28930.16 25909312.39 0.252212E+09 0.00 0.47
July 29039273.98 9472429.22 743.28 2973465.59 190013.30 538156.89 0.230098E+09 36.66 0.47
August 26318850.67 19271401.00 5191.41 2090345.11 714654.51 2241392.58 0.179412E+09 932.33 0.48
September 59510215.04 3504617.68 1426.36 2352745.72 85091.00 42869065.24 0.231010E+09 22.55 0.47
October 97805299.39 0.00 0.00 1008991.05 0.00 0.197445E+09 0.127014E+09 0.00 0.47
November 85222012.00 16572.57 0.00 118847.04 0.00 0.265153E+09 20558692.30 0.00 0.47
December 66007707.57 0.00 0.00 48697.11 0.00 0.300129E+09 3461821.48 0.00 0.47
                   
Annual Sum or Average 0.815299E+09 34148833.86 7361.05 16685404.89 1063073.16 0.186542E+10 0.152838E+10 991.54 0.47
Minimum of Months 26318850.67 0.00 0.00 19405.39 0.00 538156.89 850270.87 0.00 0.47
Maximum of Months 0.106554E+09 19271401.00 5191.41 2973465.59 714654.51 0.302209E+09 0.252212E+09 932.33 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 34897940.62 0.00 0.00 6974.40 0.00 0.326808E+09 151880.60 0.00 0.47
February 68880497.05 0.00 0.00 67607.77 0.00 0.271922E+09 8786885.19 0.00 0.47
March 0.116265E+09 0.00 0.00 306097.74 0.00 0.268871E+09 32786704.23 0.00 0.47
April 0.106522E+09 515302.89 0.00 970536.20 10039.63 0.183398E+09 0.109796E+09 0.00 0.47
May 83590735.33 926530.92 1243.43 2186882.38 56964.54 95789637.68 0.208689E+09 149.21 0.47
June 62382827.11 404849.87 0.00 2564939.70 41817.93 29931419.76 0.237514E+09 0.00 0.47
July 34075829.61 9380250.77 656.99 2660946.23 281059.66 524799.55 0.225356E+09 122.86 0.47
August 31038444.67 18582463.46 7348.01 1783719.94 1398515.34 3547441.67 0.173668E+09 1510.07 0.48
September 71764058.39 3137782.78 2783.74 1619823.87 449106.13 59101915.25 0.203217E+09 1064.19 0.47
October 0.115483E+09 0.00 0.00 446080.54 0.00 0.241728E+09 65566146.42 0.00 0.47
November 74900994.23 15817.29 544.90 36998.81 0.00 0.289374E+09 6696513.42 208.45 0.47
December 49644131.35 0.00 0.00 15085.83 0.00 0.319581E+09 364518.14 0.00 0.47
                   
Annual Sum or Average 0.849446E+09 32962997.97 12577.07 12665693.42 2237503.23 0.209058E+10 0.127259E+10 3054.77 0.47
Minimum of Months 31038444.67 0.00 0.00 6974.40 0.00 524799.55 151880.60 0.00 0.47
Maximum of Months 0.116265E+09 18582463.46 7348.01 2660946.23 1398515.34 0.326808E+09 0.237514E+09 1510.07 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.521486E+09 0.00 0.00 1982181.56 0.00 0.158173E+10 0.219870E+09 0.00 0.54
February 0.436706E+09 0.00 0.00 7770712.17 0.00 0.112708E+10 0.675073E+09 0.00 0.54
March 0.497565E+09 0.00 0.00 12055850.96 0.00 0.913069E+09 0.126453E+10 0.00 0.54
April 0.435090E+09 3291239.25 0.00 13383779.84 84213.63 0.449666E+09 0.167637E+10 0.00 0.54
May 0.372454E+09 6011284.20 0.00 15765939.34 316860.37 0.183805E+09 0.193547E+10 0.00 0.54
June 0.306655E+09 2515763.78 0.00 16513735.72 354184.99 27994518.80 0.178454E+10 0.00 0.54
July 0.187745E+09 59823178.78 6613.96 15763475.74 2250987.35 3377278.89 0.148050E+10 489.60 0.54
August 0.163233E+09 0.124153E+09 25027.26 12875652.60 4260055.05 2998095.83 0.117044E+10 1874.72 0.54
September 0.357536E+09 22295190.15 0.00 17567514.65 776163.54 60162834.52 0.172170E+10 0.00 0.54
October 0.467579E+09 0.00 0.00 14494482.65 0.00 0.506560E+09 0.173068E+10 0.00 0.54
November 0.531265E+09 106470.32 0.00 4011828.08 0.00 0.121127E+10 0.637275E+09 0.00 0.54
December 0.458551E+09 0.00 0.00 5025260.39 0.00 0.150597E+10 0.405249E+09 0.00 0.53
                   
Annual Sum or Average 0.473587E+10 0.218196E+09 31641.22 0.137210E+09 8042464.93 0.757369E+10 0.147017E+11 2364.32 0.54
Minimum of Months 0.163233E+09 0.00 0.00 1982181.56 0.00 2998095.83 0.219870E+09 0.00 0.53
Maximum of Months 0.531265E+09 0.124153E+09 25027.26 17567514.65 4260055.05 0.158173E+10 0.193547E+10 1874.72 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.552889E+10 0.00 0.00 70727977.39 0.00 0.00 0.379321E+11 0.00 3.98
February 0.337938E+10 0.00 0.00 65107170.76 0.00 0.00 0.368919E+11 0.00 4.05
March 0.242363E+10 0.00 0.00 96331457.34 0.00 0.00 0.453570E+11 0.00 4.16
April 0.877730E+09 5309846.66 0.00 0.105925E+09 0.00 0.00 0.457490E+11 0.00 4.35
May 0.155560E+09 0.00 0.00 0.114610E+09 0.00 0.00 0.483176E+11 0.00 4.64
June 8742374.31 0.00 0.00 90304936.24 0.00 0.00 0.429297E+11 0.00 4.90
July 0.00 93587377.34 0.00 88604750.26 0.00 0.00 0.392427E+11 0.00 5.08
August 3582311.44 0.315464E+09 0.00 81103561.96 0.00 0.00 0.351977E+11 0.00 5.05
September 0.103542E+09 0.00 0.00 83893229.08 0.00 0.00 0.434621E+11 0.00 4.76
October 0.161032E+10 0.00 0.00 99971007.37 0.00 0.00 0.476130E+11 0.00 4.32
November 0.324288E+10 0.00 0.00 81208677.15 0.00 0.00 0.415983E+11 0.00 4.10
December 0.507745E+10 0.00 0.00 79969067.76 0.00 0.00 0.390706E+11 0.00 3.97
                   
Annual Sum or Average 0.224117E+11 0.414362E+09 0.00 0.105776E+10 0.00 0.00 0.503362E+12 0.00 4.45
Minimum of Months 0.00 0.00 0.00 65107170.76 0.00 0.00 0.351977E+11 0.00 3.97
Maximum of Months 0.552889E+10 0.315464E+09 0.00 0.114610E+09 0.00 0.00 0.483176E+11 0.00 5.08



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.182445E+10 0.00 0.00 96814261.71 0.00 0.00 0.458382E+11 0.00 4.35
February 0.112874E+10 0.00 0.00 86453009.27 0.00 0.00 0.430267E+11 0.00 4.43
March 0.783110E+09 0.00 0.00 0.120427E+09 0.00 0.00 0.516783E+11 0.00 4.56
April 0.170710E+09 5916832.47 0.00 0.126568E+09 0.00 0.00 0.508134E+11 0.00 4.76
May 42841976.70 0.00 0.00 0.131037E+09 0.00 0.00 0.525515E+11 0.00 5.04
June 956779.35 0.00 0.00 0.100963E+09 0.00 0.00 0.463374E+11 0.00 5.29
July 0.00 0.100577E+09 0.00 97453816.20 0.00 0.00 0.420830E+11 0.00 5.46
August 0.00 0.340407E+09 0.00 89430808.24 0.00 0.00 0.377003E+11 0.00 5.42
September 4519197.25 0.00 0.00 95130248.55 0.00 0.00 0.471151E+11 0.00 5.15
October 0.341509E+09 0.00 0.00 0.121837E+09 0.00 0.00 0.534165E+11 0.00 4.71
November 0.107650E+10 0.00 0.00 0.106189E+09 0.00 0.00 0.482003E+11 0.00 4.49
December 0.167822E+10 0.00 0.00 0.107663E+09 0.00 0.00 0.467433E+11 0.00 4.34
                   
Annual Sum or Average 0.705155E+10 0.446901E+09 0.00 0.127997E+10 0.00 0.00 0.565504E+12 0.00 4.84
Minimum of Months 0.00 0.00 0.00 86453009.27 0.00 0.00 0.377003E+11 0.00 4.34
Maximum of Months 0.182445E+10 0.340407E+09 0.00 0.131037E+09 0.00 0.00 0.534165E+11 0.00 5.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 69663291.40 0.00 0.00 0.177519E+09 0.00 0.00 0.631058E+11 0.00 18.88
February 0.102874E+09 0.00 0.00 0.150162E+09 0.00 0.00 0.584842E+11 0.00 19.31
March 28344815.75 0.00 0.00 0.192699E+09 0.00 0.00 0.677830E+11 0.00 19.44
April 0.151321E+09 10208208.42 0.00 0.172596E+09 0.00 0.00 0.639972E+11 0.00 20.14
May 0.225361E+09 0.00 0.00 0.160574E+09 0.00 0.00 0.636072E+11 0.00 20.99
June 54638667.27 0.00 0.00 0.131048E+09 0.00 0.00 0.544687E+11 0.00 21.83
July 0.00 0.162854E+09 0.00 0.127314E+09 0.00 0.00 0.470467E+11 0.00 22.13
August 0.00 0.573190E+09 0.00 0.116778E+09 0.00 0.00 0.416751E+11 0.00 22.01
September 21928695.42 0.00 0.00 0.128699E+09 0.00 0.00 0.570882E+11 0.00 21.63
October 0.181910E+09 0.00 0.00 0.167281E+09 0.00 0.00 0.681701E+11 0.00 20.13
November 30050477.18 0.00 0.00 0.178241E+09 0.00 0.00 0.636655E+11 0.00 19.18
December 22913155.91 0.00 0.00 0.198687E+09 0.00 0.00 0.639684E+11 0.00 18.79
                   
Annual Sum or Average 0.889005E+09 0.746253E+09 0.00 0.190160E+10 0.00 0.00 0.713060E+12 0.00 20.38
Minimum of Months 0.00 0.00 0.00 0.116778E+09 0.00 0.00 0.416751E+11 0.00 18.79
Maximum of Months 0.225361E+09 0.573190E+09 0.00 0.198687E+09 0.00 0.00 0.681701E+11 0.00 22.13



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.141629E+11 0.00 0.00 0.00 0.00 0.499882E+09 0.00 0.00 1.08
February 0.131979E+11 0.00 0.00 0.00 0.00 0.255591E+09 0.00 0.00 1.09
March 0.152966E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.08
April 0.143589E+11 1806519.61 0.00 13350.43 37235.18 0.00 10774560.73 0.00 1.09
May 0.141858E+11 0.00 0.00 153803.90 0.00 0.00 85023619.89 0.00 1.12
June 0.119685E+11 0.00 0.00 560679.83 0.00 0.00 0.325859E+09 0.00 1.15
July 0.968306E+10 28505354.27 0.00 2162823.26 2704586.94 0.00 0.115192E+10 0.00 1.17
August 0.880118E+10 0.104686E+09 0.00 2289828.26 8841300.76 0.00 0.900496E+09 0.00 1.17
September 0.122584E+11 0.00 0.00 1337871.11 0.00 0.00 0.585207E+09 0.00 1.15
October 0.154012E+11 0.00 0.00 688.85 0.00 3244618.76 5866964.80 0.00 1.10
November 0.146325E+11 0.00 0.00 0.00 0.00 1899674.52 0.00 0.00 1.08
December 0.146345E+11 0.00 0.00 0.00 0.00 0.191960E+09 0.00 0.00 1.08
                   
Annual Sum or Average 0.158581E+12 0.134997E+09 0.00 6519045.64 11583122.88 0.952577E+09 0.306515E+10 0.00 1.11
Minimum of Months 0.880118E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.08
Maximum of Months 0.154012E+11 0.104686E+09 0.00 2289828.26 8841300.76 0.499882E+09 0.115192E+10 0.00 1.17



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:01:04

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.619817E+11 0.168566E+11 0.221951E+12 0.884905E+12 0.646852E+11
February 0.133658E+12 0.141656E+11 0.185500E+12 0.752287E+12 0.625105E+11
March 0.253043E+12 0.136736E+11 0.176699E+12 0.733521E+12 0.787474E+11
April 0.406263E+12 0.112791E+11 0.142796E+12 0.611976E+12 0.135231E+12
May 0.532504E+12 0.993078E+10 0.123091E+12 0.549293E+12 0.203694E+12
June 0.547979E+12 0.764947E+10 0.938580E+11 0.431512E+12 0.278222E+12
July 0.570002E+12 0.612995E+10 0.744953E+11 0.360714E+12 0.421175E+12
August 0.449510E+12 0.516891E+10 0.637408E+11 0.310658E+12 0.498482E+12
September 0.286194E+12 0.780249E+10 0.997234E+11 0.448078E+12 0.251429E+12
October 0.191557E+12 0.109457E+11 0.143946E+12 0.603650E+12 0.110428E+12
November 0.720157E+11 0.131848E+11 0.178722E+12 0.707304E+12 0.673413E+11
December 0.403005E+11 0.160702E+11 0.212391E+12 0.848794E+12 0.679758E+11
           
Annual Sum or Average 0.354501E+13 0.132857E+12 0.171691E+13 0.724269E+13 0.223992E+13
Minimum of Months 0.403005E+11 0.516891E+10 0.637408E+11 0.310658E+12 0.625105E+11
Maximum of Months 0.570002E+12 0.168566E+11 0.221951E+12 0.884905E+12 0.498482E+12