Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700

Simulation Timestamp: 2023-10-16 09:00:07


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 10894.26 960.25 960.25
Net Site Energy 10894.26 960.25 960.25
Total Source Energy 24293.05 2141.25 2141.25
Net Source Energy 24293.05 2141.25 2141.25


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 268.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1434.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 767.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 242.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1745.01 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 651.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 634.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 179.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 185.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.74 2843.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 61.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 5993.12 4901.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 268.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 1434.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 767.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 242.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 959.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 14.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 8.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 32.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 634.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 179.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 185.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.74 2843.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 20.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 34.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 268.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 1434.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 767.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 242.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1745.01 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 651.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 634.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 179.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 185.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 90.74 2843.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 61.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 89.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 206.22 274.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 233.01 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 528.25 432.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 89.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 206.22 274.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 233.01 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 528.25 432.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 5993.124 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 5993.124 100.00
     
Total On-Site and Utility Electric Sources 5993.124 100.00
Total Electricity End Uses 5993.124 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 324.70 22.81
Air to Air Heat Recovery for Heating 1098.59 77.19
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 1423.29 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 193.17
Time Not Comfortable Based on Simple ASHRAE 55-2004 7930.67


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58
RunPeriod RUNPERIOD 1
Weather File El Paso International Ap Ut TX USA TMY3 WMO#=722700
Latitude [deg] 31.77
Longitude [deg] -106.5
Elevation [m] 1186.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 9.1389 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 13.3365 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 13.3365 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 9.2031 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 6.1031 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.8125 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 10.3656 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 8.7188 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 4.5531 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 4.5531 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 6.3938 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 4.5531 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.3656 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.3656 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 11.7219 4.65 2934.4875
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 6.3938 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 6.8557 7.07 41.0709
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 6.8557 7.07 41.0709
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 9.1389 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 13.3365 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 13.3365 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 9.2031 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 6.1031 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.8125 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 10.3656 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 8.7188 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 4.5531 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 4.5531 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 4.5531 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 4.5531 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 4.5531 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 4.5531 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 6.3938 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 4.5531 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 4.5531 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 4.5531 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 10.3656 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 10.3656 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 11.7219 4.65 2934.4875  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 6.3938 18.58 0.0000  
Total 11345.29             6.8557 3.54 41.0709  
Conditioned Total 11345.29             6.8557 3.54 41.0709  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 4.4542 8.82 37.1989
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 25-JUL-19:10 18-DEC-21:49 - - - - - - - - - - 05-JAN-21:10
Heating 0.00 123172.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 155051.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 88772.42 75123.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 32150.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 38655.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 8348.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 3685.21 253258.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 1870.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 416814.12 451554.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 123172.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 155051.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 58789.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 37488.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 37635.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1846.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 30153.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 150.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 38655.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 8348.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 3685.21 253258.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 241.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 535.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 1093.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 290.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 4544.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2429.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 769.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5526.46 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2063.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2009.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 568.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 586.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 287.38 3082.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 195.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 18980.22 5312.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 25.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 400.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 214.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 67.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 487.11 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 177.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 50.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 51.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 271.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1672.96 468.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 25.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 400.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 214.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 67.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 487.11 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 177.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 50.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 51.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 271.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1672.96 468.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.92 0.516942 0.430000 1.25 1.00 0.500000 0.000737 0.000050 1.25 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.376128 0.135880 0.309000 0.116224 0.376404 0.500000 0.002804 0.000029 0.135644 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.282903 0.209202 0.476000 0.134662 0.557871 0.500000 0.001821 0.000013 0.134662 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.288826 0.433317 0.300000 0.086648 1.00 0.500000 0.000879 0.000018 0.086648 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.141502 0.510285 0.599000 0.084760 1.00 0.500000 0.000747 0.000012 0.084760 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.78 0.062433 0.300000 1.13 0.300000 0.500000 0.024216 0.000065 1.13 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.59 0.090776 0.626000 0.992438 0.626000 0.500000 0.004197 0.000100 0.992438 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 5.26 0.189502 0.528000 2.78 0.528000 0.500000 0.002011 0.000252 2.78 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.66 0.716584 0.420000 0.695662 1.00 0.500000 0.000532 0.000113 0.695662 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.54 0.099390 0.685000 1.74 0.685000 0.500000 0.003833 0.000124 1.74 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.66 0.094883 0.654000 1.74 0.654000 0.500000 0.004015 0.000126 1.74 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.58 0.054874 0.300000 0.774056 0.300000 0.500000 0.012488 0.000050 0.774056 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.872474 0.359941 0.300000 0.261742 0.959842 0.500000 0.001059 0.000071 0.325861 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 5743.47 0.000050 119.77
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 3365.31 0.000029 91.84
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1531.88 0.000013 34.63
MECH_FLR_1 VAV BOX REHEAT COIL 2082.82 0.000018 56.16
STORAGE_FLR_1 VAV BOX REHEAT COIL 1390.24 0.000012 33.55
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 7442.01 0.000065 158.76
CAFE_FLR_1 VAV BOX REHEAT COIL 11437.51 0.000100 259.04
LOBBY_FLR_1 VAV BOX REHEAT COIL 28849.77 0.000252 644.23
ROOM_1_FLR_3 FAN COIL HEATING COIL 6029.05 0.000053 172.28
ROOM_2_FLR_3 FAN COIL HEATING COIL 6022.55 0.000053 172.10
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 34778.84 0.000304 993.81
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 34674.06 0.000303 990.81
ROOM_5_FLR_3 FAN COIL HEATING COIL 6016.79 0.000053 171.93
ROOM_6_FLR_3 FAN COIL HEATING COIL 6010.28 0.000053 171.75
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 12868.85 0.000113 319.69
ROOM_1_FLR_6 FAN COIL HEATING COIL 1862.63 0.000016 53.22
ROOM_2_FLR_6 FAN COIL HEATING COIL 1861.83 0.000016 53.20
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 8972.06 0.000078 256.37
BANQUET_FLR_6 VAV BOX REHEAT COIL 14225.72 0.000124 309.27
DINING_FLR_6 VAV BOX REHEAT COIL 14360.28 0.000126 312.48
KITCHEN_FLR_6 VAV BOX REHEAT COIL 5673.76 0.000050 122.13
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 8084.94 0.000071 220.65
VAV WITH REHEAT HEATING COIL 171111.74 0.001497 2904.80
FLR_3_DOAS HEATING COIL 14143.00 0.000124 240.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ZoneExhaust

User-Specified Maximum Flow Rate [m3/s]
LOBBY_FLR_1 EXHAUST FAN 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 1.15 0.000053 0.000396
ROOM_2_FLR_3 FAN COIL 1.14 0.000053 0.000393
ROOM_3_MULT19_FLR_3 FAN COIL 6.34 0.000304 0.002165
ROOM_4_MULT19_FLR_3 FAN COIL 6.93 0.000303 0.002502
ROOM_5_FLR_3 FAN COIL 0.998411 0.000053 0.000346
ROOM_6_FLR_3 FAN COIL 0.990326 0.000053 0.000343
ROOM_1_FLR_6 FAN COIL 0.304699 0.000016 0.000105
ROOM_2_FLR_6 FAN COIL 0.301986 0.000016 0.000104
ROOM_3_MULT9_FLR_6 FAN COIL 1.34 0.000078 0.000471
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 1.15
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 1.14
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 6.34
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 6.93
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 0.998411
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 0.990326
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.304699
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.301986
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.34
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.77 6.70 0.008543 12.80 0.008500 0.000396 1.15  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.77 6.70 0.008544 12.80 0.008500 0.000393 1.14  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.77 6.70 0.008472 12.80 0.008472 0.002165 6.34  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.77 6.70 0.008704 12.80 0.008500 0.002502 6.93  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.77 6.70 0.008549 12.80 0.008500 0.000346 0.998411  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.77 6.70 0.008549 12.80 0.008500 0.000343 0.990326  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.77 6.70 0.008541 12.80 0.008500 0.000105 0.304699  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.77 6.70 0.008541 12.80 0.008500 0.000104 0.301986  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.77 6.70 0.008612 12.80 0.008500 0.000471 1.34  
VAV WITH REHEAT COOLING COIL 30.62 6.70 0.008339 10.70 0.008339 0.018818 24.82 526849.16
FLR_3_DOAS COOLING COIL 38.10 6.70 0.006871 11.79 0.006871 0.002048 2.05 57348.72
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 13.72 11.80 24.95 11.80 24.82 24.82 0.300000 0.475275 24.82
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 24.82 11.66
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 11.66
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 24.82
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.018818 0.000025
VAV WITH REHEAT_HEATC_CONTROLLER 0.001497  
FLR_3_DOAS_COOLC_CONTROLLER 0.002048 0.000232
FLR_3_DOAS_HEATC_CONTROLLER 0.000124  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.027692 5706.34  
HEATSYS1 PUMP 0.003574 1076.36 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.003574 0.428890
COOLSYS1 0.027692 3.32
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 408539.38 408539.38 0.003574
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.027692 3950.69
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.027692 775307.86 775976.71 88.46
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.30 11.20 6.80 8.10 10.30 12.50 19.20 23.80 27.90 27.50 26.30 23.40


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 El Paso International Ap Ut TX USA TMY3 WMO#=722700 31.77 -106.50 -7.00 1186.00 87865 1.0443


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 17.94 21.10 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 9.139 5.380 0.000 0.000 0.000 0.000 14.519 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 13.336 10.760 0.000 0.000 0.000 0.000 24.096 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 13.336 10.760 0.000 0.000 0.000 0.000 24.096 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 9.203 5.380 0.000 0.000 0.000 0.000 14.583 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 6.103 2.690 0.000 0.000 0.000 0.000 8.793 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.813 61.680 535.850 0.000 0.000 0.000 603.343 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 10.366 5.380 0.000 0.000 0.000 0.000 15.746 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 8.719 8.070 0.000 0.000 0.000 0.000 16.789 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 6.394 0.000 0.000 0.000 0.000 0.000 6.394 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 10.366 67.820 0.000 0.000 0.000 0.000 78.186 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 10.366 67.820 0.000 0.000 0.000 0.000 78.186 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 11.722 515.227 2419.260 0.000 0.000 0.000 2946.209 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 6.394 0.000 0.000 0.000 0.000 0.000 6.394 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 18084.325 9.139 169.807 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 18084.325
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 894.495 13.336 82.602 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 894.495
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 1035.829 13.336 82.602 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1035.829
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 1511.551 9.203 569.967 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1511.551
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 578.329 6.103 283.494 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 578.329
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 453.605 5.813 54.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 453.605
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1957.673 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1957.673
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 11405.759 8.719 27.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 11405.759
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 111.660 4.553 74.440 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.660
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 111.691 4.553 74.460 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.691
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 2489.757 6.394 118.803 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2489.757
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 111.691 4.553 74.460 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.691
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 3437.839 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3437.839
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 3437.839 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3437.839
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1210.923 11.722 54.453 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1210.923
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 2635.024 6.394 118.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2635.024


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 457.500 4.429 20.573 0.000 0.250 0.000 0.750 ReachInFreezer 457.500 457.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 285.000 2.759 12.816 0.000 0.250 0.000 0.750 ReachInRefrigerator 285.000 285.000


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.464 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.198 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 1.067 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.370 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.442 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.217 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.286 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2887
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.8346
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.7702
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.5624
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.5260
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.6546
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6103
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.4637404 3.4637404 3.4637404  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.1981135 1.1981135 1.1981135  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
21 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
22 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
23 0 21.361010 0.87247630E-01 5.4456762  
24 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
25 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
26 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
27 0 21.361010 0.87247630E-01 5.4456762  
28 9 -0.55514967E-15 0.35055860E-16 -0.14326465E-09 0.28783368E-17
29 8 0.20966873E-07 0.14258959E-12 0.36819155E-03 -0.23840058E-09
30 7 -0.11954852E-01 0.74774803E-08 -0.22672946E-01 0.13593102E-03
31 6 0.39755982 0.26159305E-05 0.46545104 -0.46559307E-02
32 5 -5.1145337 0.98147117E-04 -4.3902405 0.62241115E-01
33 4 32.666535 0.80637729E-03 21.240866 -0.41765750
34 3 -110.51061 0.17642800E-02 -55.229641 1.5048560
35 2 196.42192 0.99585215E-03 77.513220 -2.8894543
36 1 -170.90254 0.10665179E-03 -55.149704 2.7409959
37 0 57.057407 0.60929387E-06 15.576129  
38 9 0.10314710E-14 0.47183642E-16 -0.12881513E-09 -0.40099708E-17
39 8 0.18927665E-07 0.17950474E-12 0.34608657E-03 -0.21521408E-09
40 7 -0.11292911E-01 0.96443222E-08 -0.21719088E-01 0.12840450E-03
41 6 0.37957032 0.34070209E-05 0.45007157 -0.44438791E-02
42 5 -4.9389364 0.12890179E-03 -4.2718596 0.60063826E-01
43 4 31.889569 0.10670331E-02 20.777560 -0.40734193
44 3 -108.85680 0.23501275E-02 -54.313423 1.4809641
45 2 194.78196 0.13343675E-02 76.673975 -2.8634131
46 1 -170.29645 0.14368413E-03 -54.907648 2.7303734
47 0 57.057407 0.82565881E-06 15.617726  
48 9 0.86975537E-15 0.52023775E-16 -0.12536948E-09 -0.54620444E-17
49 8 0.18440443E-07 0.18784465E-12 0.34068694E-03 -0.20967419E-09
50 7 -0.11130813E-01 0.10155400E-07 -0.21485363E-01 0.12656138E-03
51 6 0.37516444 0.35965268E-05 0.44629465 -0.43919449E-02
52 5 -4.8959230 0.13636263E-03 -4.2427425 0.59530495E-01
53 4 31.699203 0.11309484E-02 20.663505 -0.40481456
54 3 -108.45147 0.24950915E-02 -54.087828 1.4751087
55 2 194.37988 0.14187814E-02 76.467519 -2.8570287
56 1 -170.14779 0.15298304E-03 -54.848449 2.7277680
57 0 57.057407 0.88039223E-06 15.628184  
58 9 0.12430042E-14 0.43603463E-16 -0.13615479E-09 -0.52742981E-17
59 8 0.19963588E-07 0.16114398E-12 0.35741204E-03 -0.22699287E-09
60 7 -0.11632381E-01 0.85488282E-08 -0.22208377E-01 0.13226440E-03
61 6 0.38879653 0.30047059E-05 0.45796739 -0.45526330E-02
62 5 -5.0290001 0.11318598E-03 -4.3326723 0.61180550E-01
63 4 32.288109 0.93328928E-03 21.015642 -0.41263319
64 3 -109.70522 0.20484795E-02 -54.784283 1.4932205
65 2 195.62339 0.11595496E-02 77.105128 -2.8767741
66 1 -170.60747 0.12450863E-03 -55.031726 2.7358244
67 0 57.057407 0.71328115E-06 15.596176  
68 9 0.10418955E-14 0.45554749E-16 -0.13285794E-09 -0.34221686E-17
69 8 0.19498290E-07 0.16949498E-12 0.35235048E-03 -0.22170227E-09
70 7 -0.11480752E-01 0.90423087E-08 -0.21989859E-01 0.13054032E-03
71 6 0.38467563 0.31853038E-05 0.45444290 -0.45040579E-02
72 5 -4.9887746 0.12022067E-03 -4.3055366 0.60681782E-01
73 4 32.110117 0.99300969E-03 20.909427 -0.41027004
74 3 -109.32633 0.21828955E-02 -54.574228 1.4877470
75 2 195.24766 0.12373115E-02 76.912747 -2.8708078
76 1 -170.46860 0.13302463E-03 -54.976289 2.7333905
77 0 57.057407 0.76310210E-06 15.605744  
78 7 -0.15963512E-14 -0.15187529E-16 -0.22427203E-13 0.56155309E-15
79 6 0.17983713E-10 0.23594901E-11 0.52322926E-09 -0.18637893E-10
80 5 -0.60139213E-07 0.11510628E-07 -0.21924491E-05 0.17161312E-06
81 4 0.62746279E-04 0.43399923E-05 0.17681060E-02 -0.28244642E-03
82 3 -0.90508353E-02 0.15320797E-03 -0.21560640 0.43341486E-01
83 2 0.12836503 0.66328859E-03 2.9007871 -0.61911613
84 1 -0.32478029 0.41934727E-03 -7.1379041 1.5697129
85 0 0.20664896 0.54311639E-05 4.4522013  
86 7 -0.22427203E-13 -0.15187529E-16 -0.15963512E-14 0.56155309E-15
87 6 0.52322926E-09 0.23594901E-11 0.17983713E-10 -0.18637893E-10
88 5 -0.21924491E-05 0.11510628E-07 -0.60139213E-07 0.17161312E-06
89 4 0.17681060E-02 0.43399923E-05 0.62746279E-04 -0.28244642E-03
90 3 -0.21560640 0.15320797E-03 -0.90508353E-02 0.43341486E-01
91 2 2.9007871 0.66328859E-03 0.12836503 -0.61911613
92 1 -7.1379041 0.41934727E-03 -0.32478029 1.5697129
93 0 4.4522013 0.54311639E-05 0.20664896  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
103 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
104 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
105 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
106 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
107 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
108 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
109 0 1.0055995 0.48413807E-04 60.838472  
110 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
111 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
112 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
113 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
114 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
115 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
116 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
117 0 1.0055995 0.48413807E-04 60.838472  
118 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
119 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
120 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
121 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
122 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
123 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
124 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
125 0 1.0055995 0.48413807E-04 60.838472  
126 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
127 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
128 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
129 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
130 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
131 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
132 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
133 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.4711_SHGC_0.25 37 1 VerySmooth 2.678 2.678 1.000 0.251    
2 RESWINDOW_U_0.4711_SHGC_0.25 38 1 VerySmooth 2.678 2.678 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   2.39142E-002 0.16139 0.61472 0.61472 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11798 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   2.39142E-002 0.16139 0.61472 0.61472 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11798 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 1.500
2 RACK2 1 0 Zone Air-Cooled 3.000


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 0.576 0.5074
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 0.263 2.9576E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 3.921E-002 5.846E-004 2.885E-004 0.531 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 1.513E-002 1.949E-004 5.306E-004 0.177 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 3.577E-002 2.178E-004 5.696E-004 0.198 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 2.064E-002 2.178E-004 4.726E-004 0.198 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 4.884E-002 6.258E-004 5.569E-004 0.569 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 8.667E-002 4.589E-004 2.527E-004 0.417 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.248 1.893E-004 3.620E-004 0.172 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 6.349E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 6.350E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 2.751E-002 7.066E-005 5.696E-004 8.345E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.164E-002 4.746E-004 2.589E-004 0.561 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 4.974E-002 4.815E-004 2.609E-004 0.569 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 4.868E-002 1.181E-004 9.784E-005 0.140 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 8.5405E-002
2 Clear Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 3.8071E-002
3 Clear Turbid Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 9.4529E-002
4 Clear Turbid Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 4.1339E-002
5 Intermediate Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 6.5404E-002
6 Intermediate Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 2.4194E-002
7 Overcast Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 2.6511E-002
8 Overcast Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 8.7811E-003
9 Clear Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 9.6576E-002
10 Clear Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 4.6681E-002
11 Clear Turbid Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1072
12 Clear Turbid Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 5.0654E-002
13 Intermediate Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 7.2445E-002
14 Intermediate Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 3.0583E-002
15 Overcast Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 2.9789E-002
16 Overcast Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 1.2036E-002
17 Clear Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.0964E-002
18 Clear Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.1972E-002
19 Clear Turbid Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.6150E-002
20 Clear Turbid Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 9.0418E-003
21 Intermediate Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.5433E-002
22 Intermediate Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 6.1646E-003
23 Overcast Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.6108E-002
24 Overcast Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 9.2309E-003
25 Clear Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.0964E-002
26 Clear Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.1972E-002
27 Clear Turbid Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.6150E-002
28 Clear Turbid Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 9.0418E-003
29 Intermediate Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.5433E-002
30 Intermediate Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 6.1646E-003
31 Overcast Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.6108E-002
32 Overcast Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 9.2309E-003


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 34816.87302 34816.87302 2.91690 2.91690 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 30.43000 6.85931E-003 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 0.85446 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 4489.20702 4489.20702 0.37613 0.37613 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 37.99167 6.87130E-003 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 2744.70018 2744.70018 0.13564 0.13564 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 -5.20000 2.80840E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3376.42503 3376.42503 0.28290 0.28290 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 35.84667 6.86787E-003 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 915.76226 915.76226 4.52589E-002 9.17347E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 -5.20000 2.80840E-003 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 3447.91952 3447.91952 0.28883 0.28883 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 33.03000 6.86340E-003 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1686.46283 1686.46283 8.33482E-002 8.33482E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 -5.20000 2.80840E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1689.19897 1689.19897 0.14150 0.14150 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 35.84667 6.86787E-003 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 1002.50476 1002.50476 4.95457E-002 5.77652E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 -5.20000 2.80840E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 45115.89851 45115.89851 3.77962 3.77962 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 37.14667 6.86994E-003 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 2255.84139 2255.84139 0.11148 0.11148 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 -5.20000 2.80840E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 18904.87740 18904.87740 1.58536 1.58536 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 37.99167 6.87130E-003 188.86188 142.30000 0.67639 0.00000
14 CAFE_FLR_1 Heating 6896.33397 6896.33397 0.34082 0.67639 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 -5.20000 2.80840E-003 188.86188 142.30000 0.67639 0.00000
15 LOBBY_FLR_1 Cooling 62762.54279 62762.54279 5.26031 5.26031 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 38.10000 6.87148E-003 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 16141.53833 16141.53833 0.79775 1.89399 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 -5.20000 2.80840E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 10148.74751 10148.74751 1.14567 1.14567 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 36.62667 6.86912E-003 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 6029.16885 6029.16885 0.29972 0.29972 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 10071.62283 10071.62283 1.13696 1.13696 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 36.62667 6.86912E-003 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 6022.66753 6022.66753 0.29939 0.29939 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 56169.92329 56169.92329 6.34067 6.34067 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 38.10000 6.87148E-003 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 34779.17169 34779.17169 1.72895 1.72895 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 61420.94874 61420.94874 6.93399 6.93399 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 37.71000 6.87086E-003 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 34674.39384 34674.39384 1.72375 1.72375 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 8844.26363 8844.26363 0.99841 0.99841 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 33.48500 6.86412E-003 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 6016.90550 6016.90550 0.29911 0.29911 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 8772.64884 8772.64884 0.99033 0.99033 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 33.16000 6.86360E-003 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 6010.40248 6010.40248 0.29878 0.29878 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 19771.06416 19771.06416 1.65634 1.65634 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 37.84000 6.87107E-003 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 9685.15661 9685.15661 0.47867 0.47867 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 2699.12977 2699.12977 0.30470 0.30470 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 36.80000 6.86940E-003 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 1862.67040 1862.67040 9.25952E-002 9.25952E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2675.09705 2675.09705 0.30199 0.30199 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 36.62667 6.86912E-003 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 1861.86078 1861.86078 9.25549E-002 9.25549E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 11852.85882 11852.85882 1.33809 1.33809 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 38.10000 6.87148E-003 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 8972.19828 8972.19828 0.44602 0.44602 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 30311.97684 30311.97684 2.54273 2.54273 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 38.10000 6.87148E-003 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 6253.81623 6253.81623 0.30908 1.18780 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 31752.38433 31752.38433 2.66352 2.66352 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 38.10000 6.87148E-003 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 6387.60712 6387.60712 0.31569 1.18780 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 -5.20000 2.80840E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 30714.36361 30714.36361 2.58019 2.58019 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 36.93000 6.86961E-003 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 2138.99900 2138.99900 0.10570 0.36735 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:30:00 -5.20000 2.80840E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 10414.50118 10414.50118 0.87247 0.87247 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 38.10000 6.87148E-003 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 6593.39145 6593.39145 0.32586 0.32586 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 -5.20000 2.80840E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 464089.78 24.81824 24.81824 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 171268.08 7.45228 7.45228 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00
3 FLR_3_DOAS Cooling Sensible 54460.49 19.03245 2.05125 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 FLR_3_DOAS Heating Sensible 47141.68 5.28087 2.05125 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.91690
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.51694
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.43000
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.25427
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.37027E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.02464E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.25427
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5743.47159
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.02464E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 119.77020
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.37613
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13588
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30900
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.11622
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.37640
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.80394E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.94412E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13564
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3365.31015
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.94412E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 91.84447
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.28290
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20920
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.47600
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13466
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.55787
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.82121E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.34015E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13466
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1531.87642
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.34015E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 34.62965
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.28883
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.43332
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.66478E-002
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.79263E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.82214E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.66478E-002
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2082.81836
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.82214E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 56.15743
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.14150
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.51028
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.59900
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.47600E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.46642E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.21624E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.47600E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1390.23512
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.21624E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 33.55026
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.77962
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.24332E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.13389
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.42161E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.51059E-005
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.13389
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7442.00679
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.51059E-005
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 158.76401
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.58536
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.07758E-002
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.62600
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.99244
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.62600
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.19715E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.00060E-004
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.99244
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11437.50599
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.00060E-004
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 259.03904
99 Fan:ZoneExhaust LOBBY_FLR_1 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.26031
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18950
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.77744
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52800
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.01054E-003
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.52390E-004
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.77744
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
110 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 28849.76647
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.52390E-004
113 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 644.22920
114 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
115 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.14567
116 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.14567
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.27448E-005
118 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.95994E-004
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.77086
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.54347E-003
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.95994E-004
125 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.14567
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6029.04981
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.27448E-005
128 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 172.28274
129 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
130 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.13696
131 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.13696
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.26879E-005
133 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.93016E-004
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.77085
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.54376E-003
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.93016E-004
140 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.13696
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6022.54861
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.26879E-005
143 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 172.09700
144 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
145 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 6.34067
146 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 6.34067
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.04260E-004
148 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.16547E-003
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.77125
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.47163E-003
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.47163E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.16547E-003
155 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 6.34067
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 34778.84195
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.04260E-004
158 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 993.80689
159 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
160 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 6.93399
161 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 6.93399
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.03344E-004
163 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.50232E-003
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.77029
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.70439E-003
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.50232E-003
170 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 6.93399
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 34674.06500
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.03344E-004
173 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 990.81354
174 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
175 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.99841
176 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.99841
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.26375E-005
178 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.45627E-004
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.77085
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.54910E-003
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.45627E-004
185 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.99841
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6016.78668
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.26375E-005
188 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 171.93239
189 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
190 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.99033
191 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.99033
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.25806E-005
193 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.42860E-004
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.77085
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.54943E-003
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.42860E-004
200 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.99033
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6010.28378
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.25806E-005
203 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 171.74660
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.65634
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.71658
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.42000
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.69566
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.31689E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.12582E-004
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.69566
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
214 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12868.84709
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.12582E-004
217 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 319.68643
218 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
219 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.30470
220 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.30470
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.62951E-005
222 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.05243E-004
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.77086
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.54089E-003
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.05243E-004
229 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.30470
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1862.63479
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.62951E-005
232 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 53.22339
233 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
234 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.30199
235 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.30199
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.62881E-005
237 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.04316E-004
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.77086
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.54126E-003
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.04316E-004
244 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.30199
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1861.82519
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.62881E-005
247 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 53.20026
248 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
249 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.33809
250 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.33809
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 7.84915E-005
252 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.71158E-004
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.77051
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.61185E-003
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.71158E-004
259 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.33809
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 8972.06113
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 7.84915E-005
262 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 256.36819
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.54273
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.93903E-002
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.68500
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.74177
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.68500
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.83337E-003
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.24453E-004
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.74177
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
273 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14225.72396
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.24453E-004
276 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 309.27272
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.66352
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.48832E-002
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.65400
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.74194
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.65400
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.01546E-003
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.25630E-004
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.74194
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
287 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14360.27516
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.25630E-004
290 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 312.48269
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.58019
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 5.48737E-002
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.77406
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.24883E-002
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.96365E-005
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.77406
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
301 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5673.75994
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.96365E-005
304 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 122.13218
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.87247
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.35994
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.26174
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.95984
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.05851E-003
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.07306E-005
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.32586
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
315 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8084.94226
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.07306E-005
318 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 220.65436
319 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 13.71504
320 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 11.79550
321 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 24.94680
322 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 11.79550
323 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 24.81824
324 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 24.81824
325 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
326 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.47528
327 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
328 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
329 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
333 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
334 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
335 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 24.81824
336 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
337 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 24.81824
338 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 11.66146
339 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 11.66146
340 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 30.61917
341 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.69725
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.33878E-003
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.33878E-003
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 526849.15645
346 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.88178E-002
347 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 24.81824
348 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 171111.74393
349 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.49696E-003
350 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 2904.79849
351 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 24.81824
352 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.88178E-002
353 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 2.53053E-005
354 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.49696E-003
355 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
356 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
357 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
358 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 38.10000
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.79311
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 6.87148E-003
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 6.87148E-003
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 57348.72296
364 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.04836E-003
365 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
366 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 14143.00265
367 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.23729E-004
368 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 240.09207
369 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
370 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 2.04836E-003
371 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 2.32474E-004
372 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.23729E-004
373 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 2.76922E-002
374 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 5706.33615
375 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 3.57408E-003
376 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.42889
377 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 3.57408E-003
378 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 1076.35616
379 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
380 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 408539.38281
381 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 408539.38000
382 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 3.57408E-003
383 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 2.76922E-002
384 PlantLoop COOLSYS1 Plant Loop Volume [m3] 3.32306
385 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 2.76922E-002
386 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 3950.68898
387 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 2.76922E-002
388 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 775307.86251
389 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 775976.71000
390 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 88.46134
391 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
392 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
393 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
394 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
395 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 5773.50
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 3379.23
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1539.33
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 2091.50
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1396.61
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 7480.30
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 11493.11
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 28991.54
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 6495.58
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 6488.58
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 37469.88
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 37357.01
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 6482.37
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 6475.37
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 12926.57
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 2006.72
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 2005.85
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 9666.06
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 14298.02
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 14433.21
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 5702.78
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 8118.37
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 128868.67
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 10651.46


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 19326.80 14631.60 4695.21 0.76 3107.84 31.52
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 19180.90 14520.74 4660.16 0.76 3084.24 31.28
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 106443.82 80883.92 25559.91 0.76 17465.16 177.14
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 120264.02 89717.09 30546.93 0.75 18886.89 191.56
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 16859.35 12756.74 4102.61 0.76 2708.57 27.47
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 16723.83 12653.78 4070.04 0.76 2686.65 27.25
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 5137.75 3890.56 1247.20 0.76 826.52 8.38
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 5092.34 3856.03 1236.31 0.76 819.17 8.31
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 22843.24 17183.51 5659.73 0.75 3633.77 36.86
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 657043.29 408823.80 248219.49 0.62 94171.97 955.14
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 51198.70 32051.32 19147.38 0.63 5018.41 50.90


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 3.93 13.40


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.940 0.824   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.198 1.198   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.370 1.137   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.370 1.137   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.370 1.137   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.370 1.137   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.286 1.078   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.286 1.078   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.286 1.078   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.286 1.078   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.286 1.078   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 2.2854485109E-002 3.6417926872E-002 Pass Pass 0.1397990370 0.4261713077 Fail Fail
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 6.8938599535E-002 9.1665750668E-002 Pass Pass 0.1875934376 1.0122414484 Fail Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 5.7263700033E-002 6.9984161083E-002 Pass Pass 0.1217947123 0.3184985555 Fail Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 2.5161899379E-002 2.6454578829E-002 Pass Pass 0.1432839278 0.5201413933 Fail Fail
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 2.4780721023E-002 3.2211972635E-002 Pass Pass 0.1097118193 0.2077680942 Fail Fail
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 0.1585653581 0.3948409605 Fail Pass 9.8392589906E-002 0.1970808883 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 0.1316839770 0.1895525334 Pass Pass 0.1257583865 0.3859893252 Fail Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 7.1664374851E-002 9.0516792723E-002 Pass Pass 0.1144862844 0.2661634854 Fail Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 4.8809732947E-002 0.1936807737 Pass Pass 0.2221653823 0.5214764941 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 4.7429750320E-002 0.1697669114 Pass Pass 0.2264568744 0.8894375837 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 1.4782415541E-002 3.0127790382E-002 Pass Pass 3.1399338663E-002 6.3545642718E-002 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 1.0645972752E-002 4.0974309749E-002 Pass Pass 0.1549959072 0.2858858729 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 4.7311780609E-002 0.1782244936 Pass Pass 0.1630085722 0.4931039772 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 2.3993961851E-002 8.1243231637E-002 Pass Pass 0.1313302839 0.3317068366 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 2.2409069699E-002 2.4392788467E-002 Pass Pass 0.1315167970 0.3976812720 Fail Fail
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 5.3540602364E-002 0.1961408433 Pass Pass 0.2278542014 0.6802298066 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 6.4798841285E-002 0.1915502319 Pass Pass 0.2043472267 0.6941834224 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 6.6830506586E-002 0.2695658626 Pass Pass 0.2405165366 0.6348369291 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 0.1416336842 0.2262486470 Fail Fail 0.1306207554 0.3693040131 Fail Fail
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 0.1269137781 0.2101782842 Fail Fail 0.1292836157 0.4281201330 Fail Fail
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 0.1600627903 0.3647620116 Fail Pass 0.1088960089 0.2211504973 Pass Fail
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 3.5334674328E-002 3.4227030562E-002 Pass Pass 0.1228581293 0.3053477304 Fail Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3235.00 66.86 753.95 3856.46 6262.61 14174.88



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB -5.20 0.00 -5.20 Wetbulb [C] 2.20 20.00
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 38.10 13.00 18.10 Wetbulb [C] 3.90 280.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 3.00 6      
Feb 3.00 4      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 18.00 7      
Jul 27.00 16      
Aug 41.00 15      
Sep 0.00 0      
Oct 23.00 18      
Nov 0.00 0      
Dec 7.00 7      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.845 0.940 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.920 1.067 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.920 1.067 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.920 1.067 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.920 1.067 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 0.920 1.067 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.55 0.221 0.228 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.029 1.217 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.029 1.217 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.029 1.217 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.029 1.217 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.029 1.217 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.029 1.217 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.029 1.217 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.029 1.217 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.029 1.217 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.029 1.217 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 1.137 1.370 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 1.137 1.370 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 1.137 1.370 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 1.137 1.370 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.078 1.286 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.078 1.286 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 1.078 1.286 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.078 1.286 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.078 1.286 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.186 1.442 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.55 0.221 0.228 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.55 0.221 0.228 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.186 0.196 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.186 0.196 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.186 0.196 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.186 0.196 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.186 0.196 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.186 0.196 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.186 0.196 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.186 0.196 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.186 0.196 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.186 0.196 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.185 0.196 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.185 0.196 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.185 0.196 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.188 0.196 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   23.26 0.00 0.00 23.26 23.26 2.678 0.251 0.251             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   65.50 0.00 0.00 65.50 65.50 2.678 0.251 0.251             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   85.08 0.00 0.00 85.08 85.08 2.678 0.251 0.251             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.678 0.251 0.251             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.678 0.251 0.251             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.678 0.251 0.251             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.678 0.251 0.251             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   3.68 0.00 0.00 3.68 279.56 2.678 0.251 0.251             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   3.68 0.00 0.00 3.68 279.65 2.678 0.251 0.251             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.678 0.251 0.251             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.678 0.251 0.251             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.678 0.251 0.251             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.678 0.251 0.251             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.678 0.251 0.251             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   2.15 0.00 0.00 2.15 8.59 2.678 0.251 0.251             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   2.15 0.00 0.00 2.15 8.58 2.678 0.251 0.251             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.678 0.251 0.251             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.678 0.251 0.251             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.678 0.251 0.251             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.678 0.251 0.251             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.678 0.251 0.251             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   6.74 0.00 0.00 6.74 60.70 2.678 0.251 0.251             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.678 0.251 0.251             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.678 0.251 0.251             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.678 0.251 0.251             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.678 0.251 0.251             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.678 0.251 0.251             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   5.82 0.00 0.00 5.82 5.82 2.678 0.251 0.251             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   5.21 0.00 0.00 5.21 5.21 2.678 0.251 0.251             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.678 0.251 0.251             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.678 0.251 0.251                      
North Total or Average             432.95 2.678 0.251 0.251                      
Non-North Total or Average             780.84 2.678 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.016 1.198 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 9.1389 1978.83 18084.33 LightsWired LTG_SCH_BASEMENT 51.16 168.00 51.10 0.0000 Y 173.46
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 13.3365 67.07 894.50 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 8.61
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 13.3365 77.67 1035.83 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 9.97
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 9.2031 164.24 1511.55 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 16.63
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 6.1031 94.76 578.33 LightsWired LTG_SCH_STORAGE 25.68 168.00 25.65 0.0000 Y 2.78
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.8125 78.04 453.60 LightsWired LTG_SCH_LAUNDRY 51.36 168.00 51.30 0.0000 Y 4.37
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 10.3656 188.86 1957.67 LightsWired LTG_SCH_DINING 58.69 168.00 49.12 0.0000 Y 18.05
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 8.7188 1308.19 11405.76 LightsWired LTG_SCH_LOBBY 58.69 168.00 56.99 0.0000 Y 122.01
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 4.5531 156.09 710.69 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 4.5531 156.07 710.61 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 4.5531 1863.81 8486.17 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 76.02
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 4.5531 1864.32 8488.49 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 76.04
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 4.5531 156.09 710.69 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 4.5531 156.07 710.61 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 6.3938 1557.62 9959.03 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 109.60
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 4.5531 39.02 177.67 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.59
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 4.5531 39.02 177.65 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.59
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 4.5531 220.77 1005.22 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 9.00
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 10.3656 331.66 3437.84 LightsWired LTG_SCH_DINING 58.69 168.00 53.88 0.0000 Y 34.77
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 10.3656 331.66 3437.84 LightsWired LTG_SCH_DINING 58.69 168.00 53.88 0.0000 Y 34.77
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 11.7219 103.30 1210.92 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 13.33
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 6.3938 412.12 2635.02 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 29.00
Interior Lighting Total       6.8557 11345.29 77780.02               507.72


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.07 11405.76 798.40
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.00 11405.76 0.00
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.39 1957.67 763.49
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.00 1957.67 0.00
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3437.84 687.57
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.00 3437.84 0.00
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3437.84 687.57
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.00 3437.84 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 15448.40 AstronomicalClock -   83.77 83.77 242.91
Exterior Lighting Total 15448.40           242.91



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 408539.38 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 775976.71 2.96 776113.11 2.96 3.93 13.40


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11087.00 19326.80 14631.60 4695.21 0.76 - 3107.84 31.52
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11003.61 19180.90 14520.74 4660.16 0.76 - 3084.24 31.28
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 60628.54 106443.82 80883.92 25559.91 0.76 - 17465.16 177.14
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 70059.62 120264.02 89717.09 30546.93 0.75 - 18886.89 191.56
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 9676.82 16859.35 12756.74 4102.61 0.76 - 2708.57 27.47
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 9599.35 16723.83 12653.78 4070.04 0.76 - 2686.65 27.25
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2946.58 5137.75 3890.56 1247.20 0.76 - 826.52 8.38
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2920.64 5092.34 3856.03 1236.31 0.76 - 819.17 8.31
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 13191.40 22843.24 17183.51 5659.73 0.75 - 3633.77 36.86
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 526849.16 657043.29 408823.80 248219.49 0.62 - 94171.97 955.14
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 57348.72 51198.70 32051.32 19147.38 0.63 - 5018.41 50.90
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 5743.47 5773.50 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 3365.31 3379.23 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1531.88 1539.33 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2082.82 2091.50 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1390.24 1396.61 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 7442.01 7480.30 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 11437.51 11493.11 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 28849.77 28991.54 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 6029.05 6495.58 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 6022.55 6488.58 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 34778.84 37469.88 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 34674.06 37357.01 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 6016.79 6482.37 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 6010.28 6475.37 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 12868.85 12926.57 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1862.63 2006.72 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1861.83 2005.85 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 8972.06 9666.06 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 14225.72 14298.02 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 14360.28 14433.21 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 5673.76 5702.78 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 8084.94 8118.37 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 171111.74 128868.67 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 14143.00 10651.46 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.15 806.14 703.64 1.00 1.16 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.14 800.01 703.64 1.00 1.17 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 6.34 4461.52 703.64 1.00 0.96 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 6.93 4879.01 703.64 1.00 0.95 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.00 702.52 703.64 1.00 1.20 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.99 696.83 703.64 1.00 1.20 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.30 214.40 703.64 1.00 1.70 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.30 212.49 703.64 1.00 1.71 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.34 941.53 703.64 1.00 1.13 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 24.82 55608.71 2240.64 1.00 1.11 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.027692 5706.34 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.003574 1076.36 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.027692 3950.69 142664.32 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.80 0.58 0.51
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.80 0.26 0.03



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 34816.87 34816.87 17.59 2.917 2.917 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 24.00 24.00 0.00919 30.43 0.00686 0.854 0.00
RETAIL_1_FLR_1 4489.21 4489.21 66.93 0.376 0.376 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 24.00 24.00 0.00899 37.99 0.00687 0.079 0.00
RETAIL_2_FLR_1 3376.43 3376.43 43.47 0.283 0.283 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 24.00 24.00 0.00931 35.85 0.00687 0.092 0.00
MECH_FLR_1 3447.92 3447.92 20.99 0.289 0.289 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 24.00 24.00 0.00862 33.03 0.00686 0.000 0.00
STORAGE_FLR_1 1689.20 1689.20 17.83 0.142 0.142 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 24.00 24.00 0.00871 35.85 0.00687 0.058 0.00
LAUNDRY_FLR_1 45115.90 45115.90 578.12 3.780 3.780 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 24.00 24.00 0.00854 37.15 0.00687 0.000 0.00
CAFE_FLR_1 18904.88 18904.88 100.10 1.585 1.585 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 24.00 23.99 0.01016 37.99 0.00687 0.676 0.00
LOBBY_FLR_1 62762.54 62762.54 47.98 5.260 5.260 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 23.99 0.00999 38.10 0.00687 1.894 0.00
ROOM_1_FLR_3 10148.75 10148.75 260.08 1.146 1.146 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 21.11 21.11 0.00854 36.63 0.00687 0.062 0.00
ROOM_2_FLR_3 10071.62 10071.62 258.13 1.137 1.137 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 21.11 21.11 0.00854 36.63 0.00687 0.062 0.00
ROOM_3_MULT19_FLR_3 56169.92 56169.92 2290.42 6.341 6.341 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 21.11 21.11 0.00847 38.10 0.00687 0.837 0.00
ROOM_4_MULT19_FLR_3 61420.95 61420.95 2503.86 6.934 6.934 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 21.11 21.11 0.00870 37.71 0.00687 0.837 0.00
ROOM_5_FLR_3 8844.26 8844.26 226.65 0.998 0.998 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 21.11 21.11 0.00855 33.48 0.00686 0.062 0.00
ROOM_6_FLR_3 8772.65 8772.65 224.84 0.990 0.990 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 21.11 21.11 0.00855 33.16 0.00686 0.062 0.00
CORRIDOR_FLR_3 19771.06 19771.06 50.77 1.656 1.656 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 24.00 24.00 0.00942 37.84 0.00687 0.475 0.00
ROOM_1_FLR_6 2699.13 2699.13 69.17 0.305 0.305 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 21.11 21.11 0.00854 36.80 0.00687 0.015 0.00
ROOM_2_FLR_6 2675.10 2675.10 68.56 0.302 0.302 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 21.11 21.11 0.00854 36.63 0.00687 0.015 0.00
ROOM_3_MULT9_FLR_6 11852.86 11852.86 483.19 1.338 1.338 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 21.11 21.11 0.00861 38.10 0.00687 0.099 0.00
BANQUET_FLR_6 30311.98 30311.98 91.40 2.543 2.543 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 23.98 0.01034 38.10 0.00687 1.188 0.00
DINING_FLR_6 31752.38 31752.38 95.74 2.664 2.664 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 23.98 0.01026 38.10 0.00687 1.188 0.00
KITCHEN_FLR_6 30714.36 30714.36 297.32 2.580 2.580 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 24.00 23.97 0.01007 36.93 0.00687 0.367 0.00
CORRIDOR_FLR_6 10414.50 10414.50 25.27 0.872 0.872 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00896 38.10 0.00687 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 0.854 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 23.40 0.00281 -5.20 0.00281 0.854 0.00
RETAIL_1_FLR_1 2744.70 2744.70 40.92 0.136 0.136 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.00 21.00 0.00762 -5.20 0.00281 0.079 0.00
RETAIL_2_FLR_1 915.76 915.76 11.79 0.045 0.092 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.00 21.00 0.00757 -5.20 0.00281 0.092 0.00
MECH_FLR_1 1686.46 1686.46 10.27 0.083 0.083 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.00 21.00 0.00746 -5.20 0.00281 0.000 0.00
STORAGE_FLR_1 1002.50 1002.50 10.58 0.050 0.058 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.00 21.00 0.00747 -5.20 0.00281 0.058 0.00
LAUNDRY_FLR_1 2255.84 2255.84 28.91 0.111 0.111 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.00 21.00 0.00745 -5.20 0.00281 0.000 0.00
CAFE_FLR_1 6896.33 6896.33 36.52 0.341 0.676 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.00 21.00 0.00766 -5.20 0.00281 0.676 0.00
LOBBY_FLR_1 16141.54 16141.54 12.34 0.798 1.894 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.00 21.00 0.00760 -5.20 0.00281 1.894 0.00
ROOM_1_FLR_3 6029.17 6029.17 154.51 0.300 0.300 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00760 -5.20 0.00281 0.062 0.00
ROOM_2_FLR_3 6022.67 6022.67 154.36 0.299 0.299 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00760 -5.20 0.00281 0.062 0.00
ROOM_3_MULT19_FLR_3 34779.17 34779.17 1418.18 1.729 1.729 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00763 -5.20 0.00281 0.837 0.00
ROOM_4_MULT19_FLR_3 34674.39 34674.39 1413.52 1.724 1.724 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00763 -5.20 0.00281 0.837 0.00
ROOM_5_FLR_3 6016.91 6016.91 154.19 0.299 0.299 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00760 -5.20 0.00281 0.062 0.00
ROOM_6_FLR_3 6010.40 6010.40 154.04 0.299 0.299 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00760 -5.20 0.00281 0.062 0.00
CORRIDOR_FLR_3 9685.16 9685.16 24.87 0.479 0.479 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00769 -5.20 0.00281 0.475 0.00
ROOM_1_FLR_6 1862.67 1862.67 47.73 0.093 0.093 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00767 -5.20 0.00281 0.015 0.00
ROOM_2_FLR_6 1861.86 1861.86 47.72 0.093 0.093 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00767 -5.20 0.00281 0.015 0.00
ROOM_3_MULT9_FLR_6 8972.20 8972.20 365.76 0.446 0.446 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00769 -5.20 0.00281 0.099 0.00
BANQUET_FLR_6 6253.82 6253.82 18.86 0.309 1.188 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00776 -5.20 0.00281 1.188 0.00
DINING_FLR_6 6387.61 6387.61 19.26 0.316 1.188 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.00 21.00 0.00776 -5.20 0.00281 1.188 0.00
KITCHEN_FLR_6 2139.00 2139.00 20.71 0.106 0.367 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:30:00 21.00 21.00 0.00684 -5.20 0.00281 0.367 0.00
CORRIDOR_FLR_6 6593.39 6593.39 16.00 0.326 0.326 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.00 21.00 0.00780 -5.20 0.00281 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 24.82 24.82 7.45 7.45 24.8182 11.7955 24.8182 0.4753 0.3000
FLR_3_DOAS 19.03 2.05 5.28 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 5743.472 5743.472 1.254268 0.00005025 119.770 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5743.47 5743.47 1.254268 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00800000 44.8527 0.00 0.00 5775.75 5775.75
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 3365.310 3365.310 0.135644 0.00002944 91.844 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 3365.31 3365.31 0.135644 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00762119 42.7563 2744.70 0.00 3382.00 3382.00
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1531.876 1531.876 0.134662 0.00001340 34.630 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 1531.88 1531.88 0.134662 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00756670 42.4531 915.76 0.00 1540.14 1540.14
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 2082.818 2082.818 0.086648 0.00001822 56.157 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 2082.82 2082.82 0.086648 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00745675 41.8436 1686.46 0.00 2093.18 2093.18
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1390.235 1390.235 0.084760 0.00001216 33.550 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 1390.24 1390.24 0.084760 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00747111 41.9233 1002.50 0.00 1397.49 1397.49
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 7442.007 7442.007 1.133886 0.00006511 158.764 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 7442.01 7442.01 1.133886 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00744668 41.7889 2255.84 0.00 7483.51 7483.51
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 11437.506 11437.506 0.992438 0.00010006 259.039 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 11437.51 11437.51 0.992438 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00766378 42.9920 6896.33 0.00 11499.18 11499.18
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 28849.766 28849.766 2.777444 0.00025239 644.229 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 28849.77 28849.77 2.777444 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00759534 42.6119 16141.54 0.00 29006.18 29006.18
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 11086.997 -999.000 1.145671 0.00039599 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown 7/21 16:40:00 11087.00 10990.34 1.145671 21.77 14.20 0.00854347 12.80 10.82 0.00850000 36.63 0.00686912 17.72 0.0000 21.11 0.00854347 47.5338 10148.75 0.00 12828.32 12266.16
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 6029.050 6029.050 0.299716 0.00005274 172.283 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6029.05 6029.05 0.299716 21.11 13.15 0.00760345 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00760345 42.3680 6029.17 0.00 6499.46 6499.46
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 11003.607 -999.000 1.136965 0.00039302 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown 7/21 16:40:00 11003.61 10907.05 1.136965 21.77 14.20 0.00854376 12.80 10.82 0.00850000 36.63 0.00686912 17.72 0.0000 21.11 0.00854376 47.5353 10071.62 0.00 12731.76 12172.99
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 6022.549 6022.549 0.299392 0.00005269 172.097 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6022.55 6022.55 0.299392 21.11 13.15 0.00760309 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00760309 42.3660 6022.67 0.00 6492.46 6492.46
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 60628.542 -999.000 6.340668 0.00216547 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown 7/21 14:10:00 60628.54 60628.54 6.340668 21.77 14.14 0.00847163 12.80 10.79 0.00847163 38.10 0.00687148 18.17 0.0000 21.11 0.00847163 47.1385 56169.92 0.00 70249.89 68127.09
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 34778.842 34778.842 1.728954 0.00030426 993.807 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 34778.84 34778.84 1.728954 21.11 13.17 0.00763330 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00763330 42.5314 34779.17 0.00 37492.66 37492.66
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 70059.621 -999.000 6.933994 0.00250232 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 unknown 7/21 15:30:00 70059.62 67277.34 6.933994 21.77 14.34 0.00870439 12.80 10.82 0.00850000 37.71 0.00687086 18.05 0.0000 21.11 0.00870439 48.4179 61420.95 0.00 80827.64 74416.94
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 34674.065 34674.065 1.723745 0.00030334 990.814 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 34674.06 34674.06 1.723745 21.11 13.17 0.00763217 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00763217 42.5252 34674.39 0.00 37379.71 37379.71
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 9676.818 -999.000 0.998411 0.00034563 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 unknown 7/21 10:10:00 9676.82 9581.64 0.998411 21.77 14.20 0.00854910 12.80 10.82 0.00850000 33.48 0.00686412 16.74 0.0000 21.11 0.00854910 47.5647 8844.26 0.00 11195.40 10690.34
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 6016.787 6016.787 0.299106 0.00005264 171.932 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6016.79 6016.79 0.299106 21.11 13.15 0.00760271 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00760271 42.3639 6016.91 0.00 6486.24 6486.24
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 9599.345 -999.000 0.990326 0.00034286 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown 7/21 10:00:00 9599.35 9504.29 0.990326 21.77 14.20 0.00854943 12.80 10.82 0.00850000 33.16 0.00686360 16.64 0.0000 21.11 0.00854943 47.5665 8772.65 0.00 11105.69 10603.83
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 6010.284 6010.284 0.298783 0.00005258 171.747 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6010.28 6010.28 0.298783 21.11 13.15 0.00760234 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00760234 42.3618 6010.40 0.00 6479.23 6479.23
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 12868.847 12868.847 0.695662 0.00011258 319.686 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 12868.85 12868.85 0.695662 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00769399 43.1582 9685.16 0.00 12935.31 12935.31
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 2946.581 -999.000 0.304699 0.00010524 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 unknown 7/21 16:30:00 2946.58 2922.40 0.304699 21.77 14.20 0.00854089 12.80 10.82 0.00850000 36.80 0.00686940 17.78 0.0000 21.11 0.00854089 47.5196 2699.13 0.00 3409.55 3262.15
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 1862.635 1862.635 0.092595 0.00001630 53.223 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1862.63 1862.63 0.092595 21.11 13.21 0.00767430 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00767430 42.7579 1862.67 0.00 2007.97 2007.97
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2920.638 -999.000 0.301986 0.00010432 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown 7/21 16:40:00 2920.64 2896.46 0.301986 21.77 14.20 0.00854126 12.80 10.82 0.00850000 36.63 0.00686912 17.72 0.0000 21.11 0.00854126 47.5216 2675.10 0.00 3379.50 3233.12
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 1861.825 1861.825 0.092555 0.00001629 53.200 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1861.83 1861.83 0.092555 21.11 13.21 0.00767419 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00767419 42.7573 1861.86 0.00 2007.09 2007.09
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 13191.404 -999.000 1.338087 0.00047116 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown 7/21 14:10:00 13191.40 12899.49 1.338087 21.77 14.26 0.00861185 12.80 10.82 0.00850000 38.10 0.00687148 18.17 0.0000 21.11 0.00861185 47.9098 11852.86 0.00 15242.65 14339.55
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 8972.061 8972.061 0.446021 0.00007849 256.368 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 8972.06 8972.06 0.446021 21.11 13.22 0.00768778 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00768778 42.8318 8972.20 0.00 9672.12 9672.12
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 14225.724 14225.724 1.741772 0.00012445 309.273 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 14225.72 14225.72 1.741772 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00775765 43.5112 6253.82 0.00 14304.61 14304.61
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 14360.275 14360.275 1.741941 0.00012563 312.483 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 14360.28 14360.28 1.741941 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00776249 43.5381 6387.61 0.00 14439.88 14439.88
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 5673.760 5673.760 0.774056 0.00004964 122.132 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:30:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:30:00 5673.76 5673.76 0.774056 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00684144 38.4343 2139.00 0.00 5705.31 5705.31
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 8084.942 8084.942 0.325861 0.00007073 220.654 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 8084.94 8084.94 0.325861 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00779698 43.7290 6593.39 0.00 8125.04 8125.04
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 526849.156 -999.000 24.818243 0.01881783 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 526849.16 526849.14 24.818243 30.62 16.97 0.00833878 10.70 9.81 0.00833878 38.10 0.00687148 18.17 46.9875 23.99 0.00960458 44.7822 296036.68 0.00 582197.28 538238.13
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 171111.744 171111.744 7.445473 0.00149696 2904.798 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 171111.74 171111.74 7.445473 -5.20 -5.20 0.00280840 16.70 11.86 0.00800000 -5.20 0.00280840 -5.20 156.6248 21.41 0.00684713 37.4982 62392.14 0.00 155828.90 155828.90
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 57348.723 -999.000 2.051317 0.00204836 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 57348.72 57348.72 2.051317 38.10 18.17 0.00687148 11.79 8.78 0.00687148 38.10 0.00687148 18.17 99.9965 21.11 0.00859321 47.8069 168280.60 0.00 51614.51 51614.51
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 14143.003 14143.003 0.615395 0.00012373 240.092 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 14143.00 14143.00 0.615395 -5.20 -5.20 0.00280840 16.70 11.86 0.00800000 -5.20 0.00280840 -5.20 333.3216 21.11 0.00763305 42.5301 106229.44 0.00 12879.82 12879.82



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 5743.472 5743.472 1.254268 0.00005025 119.770 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 1.3781 1.405855 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5743.47 5743.47 1.0000 1.30987141 1.254268 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.05024127 60.00 32.22 27.78 0.000 5743.47 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 44.8527 0.00 0.00 5775.75 5775.75 1.30987141 16.60 13.15 0.00800000 36934.7 20.92 14.82 0.00800000 41344.1
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 3365.310 3365.310 0.135644 0.00002944 91.844 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 0.8075 0.823742 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 3365.31 3365.31 1.0000 0.14165719 0.135644 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.02943820 60.00 32.22 27.78 0.000 3365.31 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00762119 21.00 0.00762119 42.7563 2744.70 0.00 3382.00 3382.00 0.14165719 16.60 13.15 0.00800000 36934.7 40.01 21.19 0.00800000 60809.3
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1531.876 1531.876 0.134662 0.00001340 34.630 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 0.3676 0.374964 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 1531.88 1531.88 1.0000 0.14063138 0.134662 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.01340016 60.00 32.22 27.78 0.000 1531.88 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00756670 21.00 0.00756670 42.4531 915.76 0.00 1540.14 1540.14 0.14063138 16.60 13.15 0.00800000 36934.7 27.34 17.13 0.00800000 47886.4
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 2082.818 2082.818 0.086648 0.00001822 56.157 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 0.4998 0.509821 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 2082.82 2082.82 1.0000 0.09048907 0.086648 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.01821954 60.00 32.22 27.78 0.000 2082.82 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00745675 21.00 0.00745675 41.8436 1686.46 0.00 2093.18 2093.18 0.09048907 16.60 13.15 0.00800000 36934.7 39.28 20.97 0.00800000 60066.6
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1390.235 1390.235 0.084760 0.00001216 33.550 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 0.3336 0.340294 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 1390.24 1390.24 1.0000 0.08851754 0.084760 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.01216114 60.00 32.22 27.78 0.000 1390.24 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00747111 21.00 0.00747111 41.9233 1002.50 0.00 1397.49 1397.49 0.08851754 16.60 13.15 0.00800000 36934.7 32.08 18.72 0.00800000 52722.4
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 7442.007 7442.007 1.133886 0.00006511 158.764 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 1.7857 1.821613 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 7442.01 7442.01 1.0000 1.18415307 1.133886 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.06509928 60.00 32.22 27.78 0.000 7442.01 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00744668 21.00 0.00744668 41.7889 2255.84 0.00 7483.51 7483.51 1.18415307 16.60 13.15 0.00800000 36934.7 22.80 15.52 0.00800000 43254.4
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 11437.506 11437.506 0.992438 0.00010006 259.039 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 2.7444 2.799609 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 11437.51 11437.51 1.0000 1.03643433 0.992438 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.10005008 60.00 32.22 27.78 0.000 11437.51 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00766378 21.00 0.00766378 42.9920 6896.33 0.00 11499.18 11499.18 1.03643433 16.60 13.15 0.00800000 36934.7 27.48 17.18 0.00800000 48029.7
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 28849.766 28849.766 2.777444 0.00025239 644.229 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 6.9224 7.061686 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 28849.77 28849.77 1.0000 2.90057288 2.777444 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.25236460 60.00 32.22 27.78 0.000 28849.77 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00759534 21.00 0.00759534 42.6119 16141.54 0.00 29006.18 29006.18 2.90057288 16.60 13.15 0.00800000 36934.7 26.41 16.81 0.00800000 46934.9
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 11086.997 -999.000 1.145671 0.00039599 -999.000 -999.0000 1.00000 1.00000 1020.7219 1004.8586 1.0443 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.145671 1.19646062   4197.9300 999.8980 27.68937556 13.37 6.70 6.67 775307.86 1.4300 1.429985 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown unknown unknown 7/21 16:40:00 Sensible 11087.00 10990.34 1.0000 1.19646062 1.145671 21.77 14.20 0.00854347 43588.7 12.80 10.82 0.00850000 34322.2 0.39595404 6.70 13.37 6.67 0.000 11087.00 36.63 0.00686912 17.72 0.00000000 0.0000 21.11 0.00854347 21.11 0.00854347 47.5338 10148.75 0.00 12828.32 12266.16 1.19646062 21.77 15.62 0.00854347 43588.7 11.73 11.51 0.00835722 32866.8
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 6029.050 6029.050 0.299716 0.00005274 172.283 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.145671 1.19646062   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 1.4466 1.475757 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6029.05 6029.05 1.0000 0.31300251 0.299716 21.11 13.15 0.00760345 40526.7 40.00 19.53 0.00800000 60796.0 0.05273938 60.00 32.22 27.78 0.000 6029.05 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00760345 21.11 0.00760345 42.3680 6029.17 0.00 6499.46 6499.46 0.31300251 16.60 12.76 0.00760345 35930.8 36.98 19.97 0.00760345 56695.6
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 11003.607 -999.000 1.136965 0.00039302 -999.000 -999.0000 1.00000 1.00000 1020.7224 1004.8586 1.0443 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.136965 1.18736832   4197.9300 999.8980 27.68937556 13.37 6.70 6.67 775307.86 1.4193 1.419230 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown unknown unknown 7/21 16:40:00 Sensible 11003.61 10907.05 1.0000 1.18736832 1.136965 21.77 14.20 0.00854376 43589.4 12.80 10.82 0.00850000 34322.2 0.39297591 6.70 13.37 6.67 0.000 11003.61 36.63 0.00686912 17.72 0.00000000 0.0000 21.11 0.00854376 21.11 0.00854376 47.5353 10071.62 0.00 12731.76 12172.99 1.18736832 21.77 15.62 0.00854376 43589.4 11.73 11.51 0.00835721 32866.7
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 6022.549 6022.549 0.299392 0.00005269 172.097 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.136965 1.18736832   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 1.4451 1.474166 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6022.55 6022.55 1.0000 0.31266499 0.299392 21.11 13.15 0.00760309 40525.8 40.00 19.53 0.00800000 60796.0 0.05268251 60.00 32.22 27.78 0.000 6022.55 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00760309 21.11 0.00760309 42.3660 6022.67 0.00 6492.46 6492.46 0.31266499 16.60 12.76 0.00760309 35929.8 36.98 19.97 0.00760309 56694.7
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 60628.542 -999.000 6.340668 0.00216547 -999.000 -999.0000 1.00000 1.00000 1020.5883 1004.8586 1.0443 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.340668 6.62176045   4197.9300 999.8980 27.68937556 13.37 6.70 6.67 775307.86 7.8199 7.819785 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown unknown unknown 7/21 14:10:00 Sensible 60628.54 60628.54 1.0000 6.62176045 6.340668 21.77 14.14 0.00847163 43406.5 12.80 10.79 0.00847163 34250.6 2.16524971 6.70 13.37 6.67 0.000 60628.54 38.10 0.00687148 18.17 0.00000000 0.0000 21.11 0.00847163 21.11 0.00847163 47.1385 56169.92 0.00 70249.89 68127.09 6.62176045 21.77 15.56 0.00847163 43406.5 11.69 11.48 0.00834455 32797.6
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 34778.842 34778.842 1.728954 0.00030426 993.807 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.340668 6.62176045   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 8.3450 8.512972 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 34778.84 34778.84 1.0000 1.80560148 1.728954 21.11 13.17 0.00763330 40602.9 40.00 19.53 0.00800000 60796.0 0.30422944 60.00 32.22 27.78 0.000 34778.84 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00763330 21.11 0.00763330 42.5314 34779.17 0.00 37492.66 37492.66 1.80560148 16.60 12.79 0.00763330 36006.3 36.98 20.00 0.00763330 56771.0
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 70059.621 -999.000 6.933994 0.00250232 -999.000 -999.0000 1.00000 1.00000 1021.0210 1004.8586 1.0443 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.933994 7.24138990   4197.9300 999.8980 27.68937556 13.37 6.70 6.67 775307.86 9.0364 9.036193 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 unknown unknown unknown 7/21 15:30:00 Sensible 70059.62 67277.34 1.0000 7.24138990 6.933994 21.77 14.34 0.00870439 43997.1 12.80 10.82 0.00850000 34322.2 2.50206534 6.70 13.37 6.67 0.000 70059.62 37.71 0.00687086 18.05 0.00000000 0.0000 21.11 0.00870439 21.11 0.00870439 48.4179 61420.95 0.00 80827.64 74416.94 7.24138990 21.77 15.77 0.00870439 43997.1 11.71 11.50 0.00835346 32835.2
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 34674.065 34674.065 1.723745 0.00030334 990.814 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.933994 7.24138990   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 8.3199 8.487325 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 34674.06 34674.06 1.0000 1.80016181 1.723745 21.11 13.17 0.00763217 40600.0 40.00 19.53 0.00800000 60796.0 0.30331290 60.00 32.22 27.78 0.000 34674.06 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00763217 21.11 0.00763217 42.5252 34674.39 0.00 37379.71 37379.71 1.80016181 16.60 12.79 0.00763217 36003.5 36.98 19.99 0.00763217 56768.1
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 9676.818 -999.000 0.998411 0.00034563 -999.000 -999.0000 1.00000 1.00000 1020.7323 1004.8586 1.0443 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.998411 1.04267192   4197.9300 999.8980 27.68937556 13.37 6.70 6.67 775307.86 1.2481 1.248103 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 unknown unknown unknown 7/21 10:10:00 Sensible 9676.82 9581.64 1.0000 1.04267192 0.998411 21.77 14.20 0.00854910 43603.0 12.80 10.82 0.00850000 34322.2 0.34559181 6.70 13.37 6.67 0.000 9676.82 33.48 0.00686412 16.74 0.00000000 0.0000 21.11 0.00854910 21.11 0.00854910 47.5647 8844.26 0.00 11195.40 10690.34 1.04267192 21.77 15.63 0.00854910 43603.0 11.73 11.51 0.00835709 32865.8
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 6016.787 6016.787 0.299106 0.00005264 171.932 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.998411 1.04267192   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 1.4437 1.472756 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6016.79 6016.79 1.0000 0.31236586 0.299106 21.11 13.15 0.00760271 40524.8 40.00 19.53 0.00800000 60796.0 0.05263211 60.00 32.22 27.78 0.000 6016.79 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00760271 21.11 0.00760271 42.3639 6016.91 0.00 6486.24 6486.24 0.31236586 16.60 12.76 0.00760271 35928.9 36.98 19.97 0.00760271 56693.8
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 9599.345 -999.000 0.990326 0.00034286 -999.000 -999.0000 1.00000 1.00000 1020.7330 1004.8586 1.0443 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.990326 1.03422908   4197.9300 999.8980 27.68937556 13.37 6.70 6.67 775307.86 1.2381 1.238110 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown unknown unknown 7/21 10:00:00 Sensible 9599.35 9504.29 1.0000 1.03422908 0.990326 21.77 14.20 0.00854943 43603.8 12.80 10.82 0.00850000 34322.2 0.34282498 6.70 13.37 6.67 0.000 9599.35 33.16 0.00686360 16.64 0.00000000 0.0000 21.11 0.00854943 21.11 0.00854943 47.5665 8772.65 0.00 11105.69 10603.83 1.03422908 21.77 15.63 0.00854943 43603.8 11.73 11.51 0.00835708 32865.7
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 6010.284 6010.284 0.298783 0.00005258 171.747 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.990326 1.03422908   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 1.4421 1.471164 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6010.28 6010.28 1.0000 0.31202825 0.298783 21.11 13.15 0.00760234 40523.9 40.00 19.53 0.00800000 60796.0 0.05257522 60.00 32.22 27.78 0.000 6010.28 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00760234 21.11 0.00760234 42.3618 6010.40 0.00 6479.23 6479.23 0.31202825 16.60 12.76 0.00760234 35927.9 36.98 19.97 0.00760234 56692.8
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 12868.847 12868.847 0.695662 0.00011258 319.686 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 3.0878 3.149965 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 12868.85 12868.85 1.0000 0.72650191 0.695662 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.11257080 60.00 32.22 27.78 0.000 12868.85 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00769399 21.00 0.00769399 43.1582 9685.16 0.00 12935.31 12935.31 0.72650191 16.60 13.15 0.00800000 36934.7 34.06 19.36 0.00800000 54739.7
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 2946.581 -999.000 0.304699 0.00010524 -999.000 -999.0000 1.00000 1.00000 1020.7171 1004.8586 1.0443 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.304699 0.31820693   4197.9300 999.8980 27.68937556 13.37 6.70 6.67 775307.86 0.3801 0.380046 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 unknown unknown unknown 7/21 16:30:00 Sensible 2946.58 2922.40 1.0000 0.31820693 0.304699 21.77 14.20 0.00854089 43582.1 12.80 10.82 0.00850000 34322.2 0.10523233 6.70 13.37 6.67 0.000 2946.58 36.80 0.00686940 17.78 0.00000000 0.0000 21.11 0.00854089 21.11 0.00854089 47.5196 2699.13 0.00 3409.55 3262.15 0.31820693 21.77 15.62 0.00854089 43582.1 11.73 11.51 0.00835728 32867.3
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 1862.635 1862.635 0.092595 0.00001630 53.223 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.304699 0.31820693   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 0.4469 0.455925 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1862.63 1862.63 1.0000 0.09670008 0.092595 21.11 13.21 0.00767430 40706.7 40.00 19.53 0.00800000 60796.0 0.01629348 60.00 32.22 27.78 0.000 1862.63 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00767430 21.11 0.00767430 42.7579 1862.67 0.00 2007.97 2007.97 0.09670008 16.60 12.83 0.00767430 36110.1 36.98 20.03 0.00767430 56875.0
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2920.638 -999.000 0.301986 0.00010432 -999.000 -999.0000 1.00000 1.00000 1020.7178 1004.8586 1.0443 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.301986 0.31537365   4197.9300 999.8980 27.68937556 13.37 6.70 6.67 775307.86 0.3767 0.376700 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown unknown unknown 7/21 16:40:00 Sensible 2920.64 2896.46 1.0000 0.31537365 0.301986 21.77 14.20 0.00854126 43583.1 12.80 10.82 0.00850000 34322.2 0.10430583 6.70 13.37 6.67 0.000 2920.64 36.63 0.00686912 17.72 0.00000000 0.0000 21.11 0.00854126 21.11 0.00854126 47.5216 2675.10 0.00 3379.50 3233.12 0.31537365 21.77 15.62 0.00854126 43583.1 11.73 11.51 0.00835727 32867.2
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 1861.825 1861.825 0.092555 0.00001629 53.200 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.301986 0.31537365   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 0.4467 0.455727 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1861.83 1861.83 1.0000 0.09665804 0.092555 21.11 13.21 0.00767419 40706.4 40.00 19.53 0.00800000 60796.0 0.01628640 60.00 32.22 27.78 0.000 1861.83 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00767419 21.11 0.00767419 42.7573 1861.86 0.00 2007.09 2007.09 0.09665804 16.60 12.83 0.00767419 36109.8 36.98 20.03 0.00767419 56874.7
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 13191.404 -999.000 1.338087 0.00047116 -999.000 -999.0000 1.00000 1.00000 1020.8490 1004.8586 1.0443 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.338087 1.39740682   4197.9300 999.8980 27.68937556 13.37 6.70 6.67 775307.86 1.7014 1.701409 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown unknown unknown 7/21 14:10:00 Sensible 13191.40 12899.49 1.0000 1.39740682 1.338087 21.77 14.26 0.00861185 43762.1 12.80 10.82 0.00850000 34322.2 0.47110953 6.70 13.37 6.67 0.000 13191.40 38.10 0.00687148 18.17 0.00000000 0.0000 21.11 0.00861185 21.11 0.00861185 47.9098 11852.86 0.00 15242.65 14339.55 1.39740682 21.77 15.68 0.00861185 43762.1 11.72 11.50 0.00835567 32854.3
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 8972.061 8972.061 0.446021 0.00007849 256.368 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.338087 1.39740682   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 2.1528 2.196131 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 8972.06 8972.06 1.0000 0.46579419 0.446021 21.11 13.22 0.00768778 40741.0 40.00 19.53 0.00800000 60796.0 0.07848350 60.00 32.22 27.78 0.000 8972.06 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00768778 21.11 0.00768778 42.8318 8972.20 0.00 9672.12 9672.12 0.46579419 16.60 12.85 0.00768778 36144.3 36.98 20.04 0.00768778 56909.1
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 14225.724 14225.724 1.741772 0.00012445 309.273 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 3.4134 3.482094 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 14225.72 14225.72 1.0000 1.81898792 1.741772 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.12444014 60.00 32.22 27.78 0.000 14225.72 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00775765 21.00 0.00775765 43.5112 6253.82 0.00 14304.61 14304.61 1.81898792 16.60 13.15 0.00800000 36934.7 24.31 16.07 0.00800000 44798.8
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 14360.275 14360.275 1.741941 0.00012563 312.483 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 3.4457 3.515028 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 14360.28 14360.28 1.0000 1.81916374 1.741941 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.12561714 60.00 32.22 27.78 0.000 14360.28 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00776249 21.00 0.00776249 43.5381 6387.61 0.00 14439.88 14439.88 1.81916374 16.60 13.15 0.00800000 36934.7 24.38 16.09 0.00800000 44872.4
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 5673.760 5673.760 0.774056 0.00004964 122.132 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 1.3614 1.388791 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:30:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:30:00 Sensible 5673.76 5673.76 1.0000 0.80837097 0.774056 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.04963146 60.00 32.22 27.78 0.000 5673.76 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.52 0.00684144 21.00 0.00684144 38.4343 2139.00 0.00 5705.31 5705.31 0.80837097 16.60 13.15 0.00800000 36934.7 23.52 15.78 0.00800000 43992.5
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 8084.942 8084.942 0.325861 0.00007073 220.654 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 1.9399 1.978987 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 8084.94 8084.94 1.0000 0.34030704 0.325861 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.07072339 60.00 32.22 27.78 0.000 8084.94 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00779698 21.00 0.00779698 43.7290 6593.39 0.00 8125.04 8125.04 0.34030704 16.60 13.15 0.00800000 36934.7 40.01 21.19 0.00800000 60810.3
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 526849.156 -999.000 24.818243 0.01881783 -999.000 -999.0000 1.00000 1.00000 1020.3414 1004.8586 1.0443 VAV WITH REHEAT FAN Fan:VariableVolume 24.818243 25.91847822   4197.9300 999.8980 27.68937556 13.37 6.70 6.67 775307.86 67.9535 67.953542 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 Sensible 526849.16 526849.14 1.0000 25.91847822 24.818243 30.62 16.97 0.00833878 52096.8 10.70 9.81 0.00833878 31769.6 18.81591154 6.70 13.37 6.67 55608.712 471240.44 38.10 0.00687148 18.17 11.66146000 46.9875 23.99 0.00963932 23.99 0.00960458 44.7822 296036.68 0.00 582197.28 538238.13 25.91847822 30.62 18.51 0.00833878 52096.8 10.27 10.16 0.00766575 29634.2
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 171111.744 171111.744 7.445473 0.00149696 2904.798 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 VAV WITH REHEAT FAN Fan:VariableVolume 24.818243 25.91847822   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 41.0575 41.883782 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 171111.74 171111.74 1.0000 7.77554347 7.445473 -5.20 -5.20 0.00280840 1771.3 16.70 11.86 0.00800000 37036.7 1.49680748 60.00 32.22 27.78 0.000 171111.74 -5.20 0.00280840 -5.20 11.66146000 156.6248 18.57 0.00707986 21.41 0.00684713 37.4982 62392.14 0.00 155828.90 155828.90 7.77554347 2.80 0.24 0.00280840 9851.8 22.64 10.36 0.00280840 29892.7
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 57348.723 -999.000 2.051317 0.00204836 -999.000 -999.0000 1.00000 1.00000 1017.6137 1004.8586 1.0443 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.14218037   4197.9300 999.8980 27.68937556 13.37 6.70 6.67 775307.86 7.3969 7.396897 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 Sensible 57348.72 57348.72 1.0000 2.14225568 2.051317 38.10 18.17 0.00687148 55956.2 11.79 8.78 0.00687148 29186.0 2.04815455 6.70 13.37 6.67 2195.006 55153.72 38.10 0.00687148 18.17 2.05124512 99.9965 21.11 0.00858477 21.11 0.00859321 47.8069 168280.60 0.00 51614.51 51614.51 2.14225568 38.10 19.77 0.00687148 55956.2 14.42 11.12 0.00687148 31862.7
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 14143.003 14143.003 0.615395 0.00012373 240.092 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.14218037   4197.9300 999.8980 3.57371615 54.44 82.22 27.78 416761.40 3.3935 3.461846 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 14143.00 14143.00 1.0000 0.64267671 0.615395 -5.20 -5.20 0.00280840 1771.3 16.70 11.86 0.00800000 37036.7 0.12371654 60.00 32.22 27.78 0.000 14143.00 -5.20 0.00280840 -5.20 2.05124512 333.3216 21.11 0.00763208 21.11 0.00763305 42.5301 106229.44 0.00 12879.82 12879.82 0.64267671 2.80 0.24 0.00280840 9851.8 22.64 10.36 0.00280840 29892.7



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 11.66 24.82 -      
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 2200.33 5889.00 907.67
RETAIL_1_FLR_1 3648.67 4596.67 1000.83
RETAIL_2_FLR_1 2851.33 5599.33 1019.50
MECH_FLR_1 2452.00 5797.67 522.17
STORAGE_FLR_1 946.00 7592.33 666.83
LAUNDRY_FLR_1 8721.17 4527.83 4527.50
CAFE_FLR_1 3388.17 5749.67 1541.00
LOBBY_FLR_1 3233.33 5607.50 1554.17
ROOM_1_FLR_3 874.67 8077.50 733.00
ROOM_2_FLR_3 1680.17 8210.50 1593.83
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 1346.50 8760.00 1346.50
ROOM_5_FLR_3 742.17 7935.17 709.17
ROOM_6_FLR_3 1555.50 8049.83 1522.00
CORRIDOR_FLR_3 2418.00 6698.50 1279.67
ROOM_1_FLR_6 1821.50 7989.83 1561.67
ROOM_2_FLR_6 2724.50 8111.00 2535.17
ROOM_3_MULT9_FLR_6 494.83 8099.67 420.83
BANQUET_FLR_6 3550.33 5463.67 1552.00
DINING_FLR_6 4056.33 4479.33 1535.33
KITCHEN_FLR_6 8748.50 6708.00 6708.00
CORRIDOR_FLR_6 2800.50 5698.17 867.50
Facility 8759.67 8760.00 7930.67
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 123.50 0.00 123.50
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 8.83 0.00 8.83
ROOM_2_FLR_3 0.00 6.17 0.00 6.17
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 2.17 0.00 2.17
ROOM_5_FLR_3 0.00 4.00 0.00 4.00
ROOM_6_FLR_3 0.00 3.17 0.00 3.17
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 13.17 0.00 13.17
ROOM_2_FLR_6 0.00 10.50 0.00 10.50
ROOM_3_MULT9_FLR_6 0.00 9.17 0.00 9.17
BANQUET_FLR_6 0.00 3.83 0.00 3.83
DINING_FLR_6 0.00 8.50 0.00 8.50
KITCHEN_FLR_6 0.00 151.83 0.00 151.83
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 0.00 193.17 0.00 193.17
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.60 106.50 4826.41 0.981 0.000 0.000 0.000
RETAIL_1_FLR_1 6.26 10.83 265.76 1.862 0.135 0.000 0.000
RETAIL_2_FLR_1 7.25 12.54 307.76 1.500 0.045 0.000 0.000
MECH_FLR_1 1.53 2.65 650.80 0.515 0.050 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.717 0.050 0.000 0.000
LAUNDRY_FLR_1 4.86 8.40 309.22 20.641 0.145 0.000 0.000
CAFE_FLR_1 82.31 142.30 748.35 4.282 0.106 0.000 0.000
LOBBY_FLR_1 244.35 422.44 5183.56 1.836 0.044 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.473 0.175 0.000 0.055
ROOM_2_FLR_3 0.95 1.50 118.93 0.472 0.175 0.000 0.055
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.536 0.077 0.000 0.087
ROOM_5_FLR_3 0.95 1.50 118.94 0.473 0.175 0.000 0.055
ROOM_6_FLR_3 0.95 1.50 118.93 0.472 0.175 0.000 0.055
CORRIDOR_FLR_3 12.12 20.96 1186.91 0.497 0.021 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.473 0.175 0.000 0.066
ROOM_2_FLR_6 0.95 1.50 118.93 0.472 0.175 0.000 0.065
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.537 0.142 0.000 0.104
BANQUET_FLR_6 144.55 249.90 1010.89 5.686 0.051 0.000 0.000
DINING_FLR_6 144.55 249.90 1010.89 5.808 0.051 0.000 0.000
KITCHEN_FLR_6 12.86 22.24 314.87 21.601 0.146 0.000 0.000
CORRIDOR_FLR_6 12.83 22.18 1256.16 0.841 0.036 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.60 106.50 4826.41 0.497 0.000 0.000 0.000
RETAIL_1_FLR_1 6.26 10.83 265.76 0.806 0.002 0.000 0.000
RETAIL_2_FLR_1 7.25 12.54 307.76 0.820 0.001 0.000 0.000
MECH_FLR_1 1.53 2.65 650.80 0.245 0.001 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.413 0.001 0.000 0.000
LAUNDRY_FLR_1 4.86 8.40 309.22 7.058 0.002 0.000 0.000
CAFE_FLR_1 82.31 142.30 748.35 2.505 0.002 0.000 0.000
LOBBY_FLR_1 244.35 422.44 5183.56 1.025 0.001 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.461 0.003 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.459 0.003 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.523 0.001 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.461 0.003 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.460 0.003 0.000 0.000
CORRIDOR_FLR_3 12.12 20.96 1186.91 0.269 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.460 0.003 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.458 0.003 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.523 0.002 0.000 0.000
BANQUET_FLR_6 144.55 249.90 1010.89 3.300 0.001 0.000 0.000
DINING_FLR_6 144.55 249.90 1010.89 3.301 0.001 0.000 0.000
KITCHEN_FLR_6 12.86 22.24 314.87 4.726 0.002 0.000 0.000
CORRIDOR_FLR_6 12.83 22.18 1256.16 0.382 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.60 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.26 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.25 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.53 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.86 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.31 142.30 748.35 188.86 0.0000 0.676
LOBBY_FLR_1 VAV WITH REHEAT 244.35 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.12 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 144.55 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 144.55 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.86 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.83 22.18 1256.16 412.12 0.0000 0.126
Total Facility   870.81 1604.23 35184.81 11345.29 0.0000 137.584


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 40677987.43 0.00 40677987.43 0.00 40677987.43 26946214.98 209.25 27.83 8522.92 0.00
RETAIL_1_FLR_1 4254374.38 0.00 4254374.38 309826.10 4564200.48 2498216.28 75.88 56.44 8627.69 0.00
RETAIL_2_FLR_1 3967683.30 0.00 3967683.30 119593.27 4087276.57 2892943.94 64.00 50.66 8645.34 0.00
MECH_FLR_1 2883470.03 0.00 2883470.03 282647.43 3166117.47 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 2327082.39 0.00 2327082.39 163072.00 2490154.39 1821682.01 585.42 99.03 8075.56 0.00
LAUNDRY_FLR_1 54840329.47 0.00 54840329.47 385940.64 55226270.11 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 27569660.38 0.00 27569660.38 684888.14 28254548.51 21330615.53 472.85 117.75 8169.40 0.00
LOBBY_FLR_1 81682800.63 0.00 81682800.63 1956881.84 83639682.47 59728886.00 54.25 47.37 8658.37 0.00
ROOM_1_FLR_3 1946875.62 56800.18 2003675.80 179831.92 2183507.72 1946875.62 0.00 7863.83 896.17 0.00
ROOM_2_FLR_3 1946647.51 56337.77 2002985.28 179818.20 2182803.48 1946647.51 0.00 7863.83 896.17 0.00
ROOM_3_MULT19_FLR_3 26397887.27 61063.43 26458950.71 50175.12 26509125.83 26397887.27 0.00 7930.17 829.83 8760.00
ROOM_4_MULT19_FLR_3 26405105.73 56072.63 26461178.36 50188.84 26511367.20 26405105.73 0.00 7959.51 800.49 0.00
ROOM_5_FLR_3 1946875.62 57030.87 2003906.49 179831.92 2183738.41 1946875.62 0.00 7864.00 896.00 0.00
ROOM_6_FLR_3 1946647.51 56558.84 2003206.36 179818.20 2183024.56 1946647.51 0.00 7864.00 896.00 0.00
CORRIDOR_FLR_3 20284182.03 0.00 20284182.03 217452.98 20501635.01 14972100.18 90.22 62.39 8607.39 0.00
ROOM_1_FLR_6 486718.90 67420.74 554139.64 179868.73 734008.37 486718.90 0.00 7860.33 899.67 0.00
ROOM_2_FLR_6 486661.88 66857.72 553519.60 179855.01 733374.60 486661.88 0.00 7860.33 899.67 0.00
ROOM_3_MULT9_FLR_6 3126920.42 67461.92 3194382.33 92027.14 3286409.47 3126920.42 0.00 7860.42 899.58 0.00
BANQUET_FLR_6 49405738.39 0.00 49405738.39 439194.23 49844932.62 37458366.31 184.78 105.11 8470.11 0.00
DINING_FLR_6 50418380.07 0.00 50418380.07 439194.23 50857574.30 37458366.31 57.47 70.00 8632.53 0.00
KITCHEN_FLR_6 58325608.78 0.00 58325608.78 393180.66 58718789.45 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 9082595.47 0.00 9082595.47 384823.29 9467418.76 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.45E+10 10550687.37 0.46E+10 18121884.23 0.46E+10 0.43E+10 589.53 7999.79 8760.00 8760.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.2899 0.0000 1.2899 0.0000 1.2899 0.8545 209.25 27.83 8522.92
RETAIL_1_FLR_1 0.1349 0.0000 0.1349 0.0098 0.1447 0.0792 75.88 56.44 8627.69
RETAIL_2_FLR_1 0.1258 0.0000 0.1258 0.0038 0.1296 0.0917 64.00 50.66 8645.34
MECH_FLR_1 0.0914 0.0000 0.0914 0.0090 0.1004 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0738 0.0000 0.0738 0.0052 0.0790 0.0578 585.42 99.03 8075.56
LAUNDRY_FLR_1 1.7390 0.0000 1.7390 0.0122 1.7512 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.8742 0.0000 0.8742 0.0217 0.8959 0.6764 472.85 117.75 8169.40
LOBBY_FLR_1 2.5901 0.0000 2.5901 0.0621 2.6522 1.8940 54.25 47.37 8658.37
ROOM_1_FLR_3 0.0617 0.0018 0.0635 0.0057 0.0692 0.0617 0.00 7863.83 896.17
ROOM_2_FLR_3 0.0617 0.0018 0.0635 0.0057 0.0692 0.0617 0.00 7863.83 896.17
ROOM_4_MULT19_FLR_3 0.8373 0.0018 0.8391 0.0016 0.8407 0.8373 0.00 7959.51 800.49
ROOM_5_FLR_3 0.0617 0.0018 0.0635 0.0057 0.0692 0.0617 0.00 7864.00 896.00
ROOM_6_FLR_3 0.0617 0.0018 0.0635 0.0057 0.0692 0.0617 0.00 7864.00 896.00
CORRIDOR_FLR_3 0.6432 0.0000 0.6432 0.0069 0.6501 0.4748 90.22 62.39 8607.39
ROOM_1_FLR_6 0.0154 0.0021 0.0176 0.0057 0.0233 0.0154 0.00 7860.33 899.67
ROOM_2_FLR_6 0.0154 0.0021 0.0176 0.0057 0.0233 0.0154 0.00 7860.33 899.67
ROOM_3_MULT9_FLR_6 0.0992 0.0021 0.1013 0.0029 0.1042 0.0992 0.00 7860.42 899.58
BANQUET_FLR_6 1.5666 0.0000 1.5666 0.0139 1.5806 1.1878 184.78 105.11 8470.11
DINING_FLR_6 1.5988 0.0000 1.5988 0.0139 1.6127 1.1878 57.47 70.00 8632.53
KITCHEN_FLR_6 1.8495 0.0000 1.8495 0.0125 1.8620 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.2880 0.0000 0.2880 0.0122 0.3002 0.1256 0.00 0.00 8760.00
Total Facility 80.3407 0.1874 80.5281 0.4537 80.9818 73.9670 589.53 7999.79 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.44E+09 0.00 0.44E+09 0.22E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 70553146.19 545604.10 71098750.29 64690340.46 0.00 0.00 8760.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 14.0330 0.0000 14.0330 6.9969 0.00 0.00 8760.00
FLR_3_DOAS 2.2372 0.0173 2.2545 2.0513 0.00 0.00 8760.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 4933.27 3826.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLR_3_DOAS 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 12.7190 15.7307 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 2.2372 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1318
Defaulted Fields 1181
Fields with Defaults 4005
Autosized Fields 350
Autosizable Fields 402
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 5993.12 75217.23 18-JAN-02:30 416814.12 25-JUL-19:10
Electricity:Building 2519.20 32804.76 02-JAN-02:10 151906.32 02-JAN-20:10
Electricity:Zone:BASEMENT 323.72 3705.45 02-JAN-02:10 24299.15 02-JAN-20:10
Electricity:SpaceType:GENERAL 2512.10 32663.61 02-JAN-02:10 151664.99 02-JAN-20:10
InteriorLights:Electricity 767.09 6971.81 02-JAN-02:10 62892.57 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 173.46 1576.23 02-JAN-02:10 14185.34 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 767.09 6971.81 02-JAN-02:10 62892.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity 767.09 6971.81 02-JAN-02:10 62892.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 173.46 1576.23 02-JAN-02:10 14185.34 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 767.09 6971.81 02-JAN-02:10 62892.57 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 18.80 222.61 02-JAN-02:10 1390.02 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.61 78.27 02-JAN-02:10 704.41 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.61 78.27 02-JAN-02:10 704.41 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 21.77 257.78 02-JAN-02:10 1609.65 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.97 90.64 02-JAN-02:10 815.72 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.97 90.64 02-JAN-02:10 815.72 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 29.11 327.88 02-JAN-02:10 2199.84 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 16.64 151.16 02-JAN-02:10 1360.40 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 16.64 151.16 02-JAN-02:10 1360.40 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 6.38 76.28 02-JAN-02:10 469.87 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.78 25.30 02-JAN-02:10 227.72 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.78 25.30 02-JAN-02:10 227.72 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 72.30 1002.39 02-JAN-02:10 4930.01 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.37 39.69 02-JAN-02:10 357.21 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.37 39.69 02-JAN-02:10 357.21 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 32.39 398.98 02-JAN-02:10 2727.18 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 18.05 195.77 02-JAN-02:10 1761.91 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 18.05 195.77 02-JAN-02:10 1761.91 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 271.01 3251.99 02-JAN-02:10 20294.39 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 122.01 1140.58 02-JAN-02:10 10265.18 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 122.01 1140.58 02-JAN-02:10 10265.18 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 18.66 264.62 01-JAN-02:10 1227.54 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 18.66 264.59 01-JAN-02:10 1227.39 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 304.77 4565.05 01-JAN-02:10 20923.25 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 76.02 643.59 01-JAN-02:10 5851.22 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 76.02 643.59 01-JAN-02:10 5851.22 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 304.86 4566.30 01-JAN-02:10 20928.98 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 76.04 643.77 01-JAN-02:10 5852.82 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 76.04 643.77 01-JAN-02:10 5852.82 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 18.66 264.62 01-JAN-02:10 1227.54 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 18.66 264.59 01-JAN-02:10 1227.39 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 4.66 66.15 01-JAN-02:10 306.88 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.59 13.47 01-JAN-02:10 122.50 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.59 13.47 01-JAN-02:10 122.50 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 4.66 66.15 01-JAN-02:10 306.85 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.59 13.47 01-JAN-02:10 122.49 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.59 13.47 01-JAN-02:10 122.49 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 36.10 540.75 01-JAN-02:10 2478.43 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 9.00 76.24 01-JAN-02:10 693.10 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 9.00 76.24 01-JAN-02:10 693.10 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 210.63 2593.08 02-JAN-02:10 9841.96 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 34.77 343.78 02-JAN-02:10 3094.06 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 34.77 343.78 02-JAN-02:10 3094.06 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 210.63 2593.08 02-JAN-02:10 9841.96 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 34.77 343.78 02-JAN-02:10 3094.06 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 34.77 343.78 02-JAN-02:10 3094.06 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 454.16 6253.02 02-JAN-02:10 18944.06 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.33 121.09 02-JAN-02:10 1089.83 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.33 121.09 02-JAN-02:10 1089.83 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
InteriorEquipment:Electricity 1745.01 25691.80 02-JAN-02:10 89475.41 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1745.01 25691.80 02-JAN-02:10 89475.41 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 433.74 5990.78 01-JAN-00:10 16487.34 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
Refrigeration:Electricity 61.88 1107.34 09-JAN-23:30 3452.57 13-JAN-07:30
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 1759.79 2610.92 12-APR-01:20 182168.00 14-JUN-18:10
LowTempRefrigeration:Refrigeration:Electricity 20.52 0.00 01-JAN-11:10 2032.19 13-JAN-07:30
MedTempRefrigeration:Refrigeration:Electricity 34.27 967.98 11-JAN-00:30 1245.48 16-FEB-09:10
Fans:Electricity 634.57 12164.12 15-MAR-04:00 50591.54 07-AUG-21:10
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 852.20 13367.00 10-MAR-04:00 61747.18 07-AUG-21:10
ExteriorEquipment:Electricity 651.48 9618.58 02-JAN-02:20 39726.11 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 32.45 553.78 11-JAN-02:30 1868.65 02-JAN-21:10
ElectricityPurchased:Facility 5993.12 75217.23 18-JAN-02:30 416814.12 25-JUL-19:10
ElectricityPurchased:Plant 5993.12 75217.23 18-JAN-02:30 416814.12 25-JUL-19:10
Cogeneration:ElectricityPurchased 5993.12 75217.23 18-JAN-02:30 416814.12 25-JUL-19:10
General:Cogeneration:ElectricityPurchased 5993.12 75217.23 18-JAN-02:30 416814.12 25-JUL-19:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 5993.12 75217.23 18-JAN-02:30 416814.12 25-JUL-19:10
ElectricityNet:Plant 5993.12 75217.23 18-JAN-02:30 416814.12 25-JUL-19:10
Cogeneration:ElectricityNet 5993.12 75217.23 18-JAN-02:30 416814.12 25-JUL-19:10
General:Cogeneration:ElectricityNet 5993.12 75217.23 18-JAN-02:30 416814.12 25-JUL-19:10
General:Fans:Electricity 634.57 12164.12 15-MAR-04:00 50591.54 07-AUG-21:10
ExteriorLights:Electricity 242.91 0.00 01-JAN-07:20 15448.40 01-JAN-00:10
General:ExteriorLights:Electricity 242.91 0.00 01-JAN-07:20 15448.40 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.91 18.80 01-JAN-00:10 188.00 01-JAN-07:10
HeatRecovery:Electricity 185.17 0.00 01-JAN-12:10 9938.94 01-JAN-08:30
General:HeatRecovery:Electricity 185.17 0.00 01-JAN-12:10 9938.94 01-JAN-08:30
WaterSystems:Electricity 90.74 1086.56 05-DEC-02:30 4738.75 07-SEP-18:10
Water Heater:WaterSystems:Electricity 90.74 1086.56 05-DEC-02:30 4738.75 07-SEP-18:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 1434.84 0.00 01-JAN-03:20 167567.16 14-JUN-18:10
General:Cooling:Electricity 1434.84 0.00 01-JAN-03:20 167567.16 14-JUN-18:10
Pumps:Electricity 179.41 47.91 24-APR-07:10 8638.43 18-JUL-20:50
General:Pumps:Electricity 179.41 47.91 24-APR-07:10 8638.43 18-JUL-20:50
WIRED_LTG_ELECTRICITY 27.00 0.00 01-JAN-00:10 2213.82 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 4901.14 29270.80 16-MAR-01:20 451554.94 18-DEC-21:50
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 3112.30 15908.90 01-JUN-10:10 412692.32 21-JAN-24:00
WaterSystems:NaturalGas 2843.91 15908.90 03-FEB-16:10 256972.59 27-FEB-21:30
Water Heater:WaterSystems:NaturalGas 2843.91 15908.90 03-FEB-16:10 256972.59 27-FEB-21:30
Heating:NaturalGas 268.39 0.00 01-JAN-11:10 191594.86 03-JAN-01:10
Boiler:Heating:NaturalGas 268.39 0.00 01-JAN-11:10 191594.86 03-JAN-01:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 4395.00 -278.62 17-FEB-01:00 625920.64 18-JUL-20:50
PlantLoopCoolingDemand:HVAC 4395.00 -278.62 17-FEB-01:00 625920.64 18-JUL-20:50
CoolingCoils:PlantLoopCoolingDemand 4395.00 -278.62 17-FEB-01:00 625920.64 18-JUL-20:50


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 05-JAN-21:10
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 05-JAN-21:10
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 05-JAN-21:10
Water Heater:WaterSystems:Water 5742.51 0.00 11-JAN-02:30 0.00 02-JAN-19:20
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 05-JAN-21:10
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 05-JAN-21:10
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 05-JAN-21:10
Water Heater:WaterSystems:MainsWater 5742.51 0.00 11-JAN-02:30 0.00 02-JAN-19:20
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 04-JAN-07:10
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 04-JAN-07:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 23164.28 133094.56 29-NOV-14:40 2336798.06 18-JUL-20:50
EnergyTransfer:Building 5702.44 56953.85 02-FEB-10:50 365115.00 15-JUN-18:10
EnergyTransfer:Zone:KITCHEN_FLR_6 730.71 6796.63 11-APR-02:50 36174.68 02-JUL-10:40
Refrigeration:EnergyTransfer 182.55 3973.53 09-JAN-23:30 10647.72 13-JAN-07:30
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 91.27 1986.76 09-JAN-23:30 5323.86 13-JAN-07:30
General:Refrigeration:EnergyTransfer 91.27 1986.76 09-JAN-23:30 5323.86 13-JAN-07:30
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 91.27 1986.76 09-JAN-23:30 5323.86 13-JAN-07:30
EnergyTransfer:Plant 11458.08 12522.32 25-OCT-03:00 1431926.88 18-JUL-20:50
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.58 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 69.69 1853.94 11-JAN-00:30 2686.44 16-FEB-09:10
EnergyTransfer:Zone:BASEMENT 418.79 1458.13 02-FEB-10:50 27543.86 18-DEC-21:20
Heating:EnergyTransfer 50.71 0.00 01-JAN-08:20 54747.61 26-DEC-16:10
Heating:EnergyTransfer:Zone:BASEMENT 0.02 0.00 01-JAN-00:10 1874.32 15-FEB-23:10
General:Heating:EnergyTransfer 50.71 0.00 01-JAN-08:20 54747.61 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:BASEMENT 0.02 0.00 01-JAN-00:10 1874.32 15-FEB-23:10
Cooling:EnergyTransfer 5560.46 39824.47 02-FEB-10:50 361639.61 15-JUN-18:10
Cooling:EnergyTransfer:Zone:BASEMENT 418.77 1458.13 02-FEB-10:50 27543.86 18-DEC-21:20
General:Cooling:EnergyTransfer 5560.46 39824.47 02-FEB-10:50 361639.61 15-JUN-18:10
General:Cooling:EnergyTransfer:Zone:BASEMENT 418.77 1458.13 02-FEB-10:50 27543.86 18-DEC-21:20
EnergyTransfer:Zone:RETAIL_1_FLR_1 43.45 0.15 19-DEC-06:30 3750.87 18-OCT-13:00
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.06 0.00 01-JAN-00:20 806.17 27-DEC-07:30
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.06 0.00 01-JAN-00:20 806.17 27-DEC-07:30
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 43.39 0.00 07-JAN-07:10 3750.87 18-OCT-13:00
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 43.39 0.00 07-JAN-07:10 3750.87 18-OCT-13:00
EnergyTransfer:Zone:RETAIL_2_FLR_1 40.18 51.90 02-FEB-10:50 2494.28 15-JUN-21:00
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.01 0.00 01-JAN-00:10 125.35 23-DEC-00:10
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.01 0.00 01-JAN-00:10 125.35 23-DEC-00:10
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 40.17 0.00 02-FEB-10:50 2494.28 15-JUN-21:00
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 40.17 0.00 02-FEB-10:50 2494.28 15-JUN-21:00
EnergyTransfer:Zone:MECH_FLR_1 29.37 25.74 16-FEB-09:00 2636.68 15-JUN-20:00
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.01 0.00 01-JAN-00:20 155.51 23-DEC-00:10
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.01 0.00 01-JAN-00:20 155.51 23-DEC-00:10
Cooling:EnergyTransfer:Zone:MECH_FLR_1 29.36 0.00 09-JAN-07:10 2636.68 15-JUN-20:00
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 29.36 0.00 09-JAN-07:10 2636.68 15-JUN-20:00
EnergyTransfer:Zone:STORAGE_FLR_1 19.29 0.15 28-DEC-06:00 984.89 15-JUN-21:00
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.03 0.00 01-JAN-00:20 189.76 23-DEC-00:10
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.03 0.00 01-JAN-00:20 189.76 23-DEC-00:10
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 19.26 0.00 09-JAN-07:10 984.89 15-JUN-21:00
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 19.26 0.00 09-JAN-07:10 984.89 15-JUN-21:00
EnergyTransfer:Zone:LAUNDRY_FLR_1 601.91 5772.14 25-OCT-03:10 39770.82 15-JUN-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 281.18 11-APR-02:40
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 281.18 11-APR-02:40
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 601.91 5772.14 25-OCT-03:10 39770.82 15-JUN-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 601.91 5772.14 25-OCT-03:10 39770.82 15-JUN-20:00
EnergyTransfer:Zone:CAFE_FLR_1 260.00 375.76 09-JAN-07:10 12764.49 18-OCT-15:10
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.06 0.00 01-JAN-00:10 874.98 02-DEC-07:30
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.06 0.00 01-JAN-00:10 874.98 02-DEC-07:30
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 259.94 194.66 09-JAN-07:10 12764.49 18-OCT-15:10
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 259.94 194.66 09-JAN-07:10 12764.49 18-OCT-15:10
EnergyTransfer:Zone:LOBBY_FLR_1 831.71 807.90 02-FEB-10:50 44431.94 07-AUG-21:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.07 0.00 01-JAN-00:10 3099.57 11-NOV-04:40
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.07 0.00 01-JAN-00:10 3099.57 11-NOV-04:40
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 831.64 735.29 02-FEB-10:50 44431.94 07-AUG-21:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 831.64 735.29 02-FEB-10:50 44431.94 07-AUG-21:10
EnergyTransfer:Zone:ROOM_1_FLR_3 78.00 0.00 11-MAR-03:10 11664.48 15-JUN-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 4.73 0.00 01-JAN-00:10 4296.43 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 4.73 0.00 01-JAN-00:10 4296.43 26-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 73.28 0.00 01-JAN-00:20 11664.48 15-JUN-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 73.28 0.00 01-JAN-00:20 11664.48 15-JUN-15:10
EnergyTransfer:Zone:ROOM_2_FLR_3 72.24 0.02 24-NOV-03:30 11891.00 15-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 8.16 0.00 01-JAN-08:10 4581.57 27-DEC-09:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 8.16 0.00 01-JAN-08:10 4581.57 27-DEC-09:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 64.09 0.00 01-JAN-00:10 11891.00 15-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 64.09 0.00 01-JAN-00:10 11891.00 15-JUN-18:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 502.74 2149.92 27-DEC-06:00 50813.59 22-OCT-13:20
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 502.74 2149.92 27-DEC-06:00 50813.59 22-OCT-13:20
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 502.74 2149.92 27-DEC-06:00 50813.59 22-OCT-13:20
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 486.73 0.47 26-NOV-11:00 69794.72 15-JUN-18:20
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 14.34 0.00 01-JAN-00:10 29056.67 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 14.34 0.00 01-JAN-00:10 29056.67 26-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 472.39 0.00 02-JAN-02:10 69794.72 15-JUN-18:20
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 472.39 0.00 02-JAN-02:10 69794.72 15-JUN-18:20
EnergyTransfer:Zone:ROOM_5_FLR_3 78.98 0.08 13-FEB-07:30 9947.82 15-JUN-08:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 4.85 0.00 01-JAN-08:10 4285.85 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 4.85 0.00 01-JAN-08:10 4285.85 26-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 74.13 0.00 01-JAN-00:10 9947.82 15-JUN-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 74.13 0.00 01-JAN-00:10 9947.82 15-JUN-08:10
EnergyTransfer:Zone:ROOM_6_FLR_3 72.69 0.09 07-JAN-10:20 10069.64 15-JUN-08:10
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 8.04 0.00 01-JAN-08:10 4321.19 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 8.04 0.00 01-JAN-08:10 4321.19 26-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 64.65 0.00 01-JAN-00:10 10069.64 15-JUN-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 64.65 0.00 01-JAN-00:10 10069.64 15-JUN-08:10
EnergyTransfer:Zone:CORRIDOR_FLR_3 199.72 307.91 16-FEB-09:00 13937.68 15-JUN-18:30
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.12 0.00 01-JAN-00:20 1287.78 23-DEC-00:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.12 0.00 01-JAN-00:20 1287.78 23-DEC-00:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 199.60 0.00 09-JAN-07:10 13937.68 15-JUN-18:30
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 199.60 0.00 09-JAN-07:10 13937.68 15-JUN-18:30
EnergyTransfer:Zone:ROOM_1_FLR_6 20.07 0.01 25-OCT-00:50 3168.48 15-JUN-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 2.52 0.00 01-JAN-08:10 1305.99 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 2.52 0.00 01-JAN-08:10 1305.99 26-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 17.54 0.00 01-JAN-00:10 3168.48 15-JUN-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 17.54 0.00 01-JAN-00:10 3168.48 15-JUN-15:10
EnergyTransfer:Zone:ROOM_2_FLR_6 19.27 0.01 11-FEB-20:10 3185.94 15-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 3.88 0.00 01-JAN-08:10 1492.73 27-DEC-09:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 3.88 0.00 01-JAN-08:10 1492.73 27-DEC-09:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 15.39 0.00 01-JAN-00:10 3185.94 15-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 15.39 0.00 01-JAN-00:10 3185.94 15-JUN-18:10
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 112.55 0.09 29-DEC-23:40 15226.16 29-OCT-15:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 3.65 0.00 01-JAN-00:10 5590.73 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 3.65 0.00 01-JAN-00:10 5590.73 26-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 108.90 0.00 01-JAN-05:30 15226.16 29-OCT-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 108.90 0.00 01-JAN-05:30 15226.16 29-OCT-15:10
EnergyTransfer:Zone:BANQUET_FLR_6 483.02 1074.31 02-FEB-10:50 23624.35 15-JUN-21:10
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.04 0.00 01-JAN-00:10 1031.27 11-NOV-04:40
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.04 0.00 01-JAN-00:10 1031.27 11-NOV-04:40
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 482.98 804.41 02-FEB-10:50 23624.35 15-JUN-21:10
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 482.98 804.41 02-FEB-10:50 23624.35 15-JUN-21:10
EnergyTransfer:Zone:DINING_FLR_6 508.45 1874.68 02-FEB-10:50 24968.40 15-JUN-21:20
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.02 0.00 01-JAN-00:10 811.46 11-NOV-04:40
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.02 0.00 01-JAN-00:10 811.46 11-NOV-04:40
Cooling:EnergyTransfer:Zone:DINING_FLR_6 508.44 1874.68 02-FEB-10:50 24968.40 15-JUN-21:20
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 508.44 1874.68 02-FEB-10:50 24968.40 15-JUN-21:20
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 60.55 06-MAR-00:30
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 60.55 06-MAR-00:30
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 639.43 4474.93 11-APR-02:50 31110.72 02-JUL-10:50
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 639.43 4474.93 11-APR-02:50 31110.72 02-JUL-10:50
EnergyTransfer:Zone:CORRIDOR_FLR_6 92.56 0.17 03-FEB-04:20 7016.23 03-JUL-14:30
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.11 0.00 01-JAN-00:20 1319.63 27-DEC-07:30
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.11 0.00 01-JAN-00:20 1319.63 27-DEC-07:30
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 92.45 0.00 09-JAN-07:10 7016.23 03-JUL-14:30
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 92.45 0.00 09-JAN-07:10 7016.23 03-JUL-14:30
PlantLoopHeatingDemand:Facility 833.97 7205.63 01-AUG-01:40 165335.40 25-DEC-07:30
PlantLoopHeatingDemand:Plant 648.51 7205.63 01-AUG-01:40 50237.28 27-JAN-08:00
WaterSystems:PlantLoopHeatingDemand 648.51 7205.63 01-AUG-01:40 50237.28 27-JAN-08:00
General:WaterSystems:PlantLoopHeatingDemand 648.51 7205.63 01-AUG-01:40 50237.28 27-JAN-08:00
EnergyTransfer:HVAC 6003.76 52.05 11-APR-12:20 663995.60 21-JUL-18:10
HeatingCoils:EnergyTransfer 185.46 0.00 01-JAN-11:10 141861.80 24-DEC-23:50
PlantLoopHeatingDemand:HVAC 185.46 0.00 01-JAN-11:10 141861.80 24-DEC-23:50
HeatingCoils:PlantLoopHeatingDemand 185.46 0.00 01-JAN-11:10 141861.80 24-DEC-23:50
CoolingCoils:EnergyTransfer 4395.00 -278.62 17-FEB-01:00 625920.64 18-JUL-20:50
HeatRecoveryForHeating:EnergyTransfer 1098.59 0.00 01-JAN-12:10 347758.81 02-MAR-05:00
HeatRecoveryForCooling:EnergyTransfer 324.70 0.00 01-JAN-00:10 151838.02 20-JUL-16:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 648.51 7205.63 01-AUG-01:40 50237.28 27-JAN-08:00
WaterUse:WaterSystems:EnergyTransfer 648.51 7205.63 01-AUG-01:40 50237.28 27-JAN-08:00
Boilers:EnergyTransfer 182.93 0.00 01-JAN-11:10 140148.01 24-DEC-23:50
Chillers:EnergyTransfer 4550.26 0.00 01-JAN-03:20 629435.00 18-JUL-20:50
HeatRejection:EnergyTransfer 5985.10 0.00 01-JAN-03:20 771297.79 18-JUL-20:50
General:HeatRejection:EnergyTransfer 5985.10 0.00 01-JAN-03:20 771297.79 18-JUL-20:50



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.024 -418.771 0.000 0.000 137.068 173.462 150.255 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -42.039
RETAIL_1_FLR_1 0.000 0.000 0.062 -43.385 0.000 0.000 14.291 8.614 10.186 23.363 0.000 0.450 0.001 0.000 -9.077 0.000 -2.291 -2.211
RETAIL_2_FLR_1 0.000 0.000 0.007 -40.174 0.000 0.000 16.261 9.975 11.795 0.000 0.000 0.182 2.858 0.000 0.000 0.000 -0.904 -0.000
MECH_FLR_1 0.000 0.000 0.012 -29.356 0.000 0.000 3.496 16.635 12.471 0.000 0.000 0.416 0.000 0.000 0.000 0.000 -2.061 -1.614
STORAGE_FLR_1 0.000 0.000 0.025 -19.265 0.000 0.000 2.837 2.785 3.598 0.000 0.000 0.280 10.811 0.000 0.000 0.000 -1.070 -0.000
LAUNDRY_FLR_1 0.000 0.000 0.001 -601.917 0.000 0.000 10.561 4.368 658.131 0.000 0.000 0.560 0.000 0.000 0.000 0.000 -3.144 -68.560
CAFE_FLR_1 0.000 0.000 0.062 -259.944 0.000 0.000 189.604 18.050 14.341 66.570 0.000 1.152 0.583 0.000 -25.457 0.000 -4.960 -0.000
LOBBY_FLR_1 0.000 0.000 0.071 -831.644 0.000 0.000 543.217 122.013 148.998 87.564 0.000 3.050 0.000 0.000 -35.002 0.000 -15.080 -23.187
ROOM_1_FLR_3 6.701 -59.918 0.000 -15.337 0.000 0.000 9.675 6.366 12.292 50.954 0.000 1.664 10.802 0.000 -18.172 0.000 -5.029 -0.000
ROOM_2_FLR_3 10.784 -51.668 0.000 -15.045 0.000 0.000 9.707 6.366 12.291 38.632 0.000 1.668 10.935 0.000 -18.757 0.000 -4.911 -0.001
ROOM_3_MULT19_FLR_3 0.001 -253.855 0.000 -248.880 0.000 0.000 0.000 76.021 228.754 288.108 0.000 6.402 59.011 0.000 -110.147 0.000 -45.414 -0.004
ROOM_4_MULT19_FLR_3 37.284 -294.187 0.000 -201.136 0.000 0.000 184.918 76.042 228.817 104.052 0.000 10.797 0.000 0.000 -100.899 0.000 -32.116 -13.572
ROOM_5_FLR_3 6.773 -60.630 0.000 -15.426 0.000 0.000 9.664 6.366 12.292 50.974 0.000 1.661 10.865 0.000 -17.466 0.000 -5.072 -0.000
ROOM_6_FLR_3 10.603 -52.082 0.000 -15.134 0.000 0.000 9.698 6.366 12.291 38.066 0.000 1.662 10.959 0.000 -17.477 0.000 -4.952 -0.001
CORRIDOR_FLR_3 0.000 0.000 0.117 -199.606 0.000 0.000 111.189 109.603 0.000 42.148 0.000 1.276 0.001 0.000 -25.159 0.000 -6.294 -33.275
ROOM_1_FLR_6 3.189 -14.400 0.000 -3.808 0.000 0.000 2.422 1.592 3.073 12.697 0.000 0.417 0.531 0.000 -4.439 0.000 -1.274 -0.000
ROOM_2_FLR_6 4.690 -12.479 0.000 -3.729 0.000 0.000 2.431 1.591 3.073 9.650 0.000 0.418 0.162 0.000 -4.566 0.000 -1.241 -0.000
ROOM_3_MULT9_FLR_6 5.909 -86.268 0.000 -24.888 0.000 0.000 21.728 9.005 27.097 63.940 0.000 2.069 8.695 0.000 -20.667 0.000 -6.621 -0.000
BANQUET_FLR_6 0.000 0.000 0.039 -482.987 0.000 0.000 325.658 34.773 175.857 10.082 0.000 0.704 0.000 0.000 -14.585 0.000 -3.307 -46.232
DINING_FLR_6 0.000 0.000 0.018 -508.439 0.000 0.000 321.584 34.773 175.857 9.714 0.000 0.676 0.000 0.000 -15.209 0.000 -3.394 -15.579
KITCHEN_FLR_6 0.000 0.000 0.000 -639.426 0.000 0.000 27.902 13.327 550.372 23.035 0.000 0.560 38.588 0.000 -11.113 0.000 -3.245 -0.001
CORRIDOR_FLR_6 0.000 0.000 0.112 -92.448 0.000 0.000 29.429 28.999 0.000 20.347 0.000 0.548 27.110 0.000 -11.291 0.000 -2.806 -0.000
Total Facility 85.934 -885.488 0.549 -4710.744 0.000 0.000 1983.339 767.092 2451.839 939.896 0.000 36.612 191.912 0.000 -459.482 0.000 -155.188 -246.279


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 19-NOV-23:56 0.00 0.00 0.00 -40522.70 0.00 0.00 5947.74 4728.51 4258.44 0.00 0.00 0.00 25588.02 0.00 -0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 18-OCT-13:00 0.00 0.00 0.00 -3750.75 0.00 0.00 150.60 195.67 252.59 4420.54 0.00 38.38 0.00 0.00 -0.00 0.00 0.00 -1307.03
RETAIL_2_FLR_1 08-FEB-22:01 0.00 0.00 0.00 -3206.86 0.00 0.00 766.58 543.81 585.00 0.00 0.00 0.00 1399.90 0.00 -0.00 0.00 -88.43 0.00
MECH_FLR_1 15-JUN-20:00 0.00 0.00 0.00 -2636.84 0.00 0.00 129.08 1360.40 839.45 0.00 0.00 88.47 219.44 0.00 -0.00 0.00 0.00 0.00
STORAGE_FLR_1 17-MAR-03:44 0.00 0.00 0.00 -1269.32 0.00 0.00 145.59 25.30 50.98 0.00 0.00 0.00 1138.53 0.00 -0.00 0.00 -91.08 0.00
LAUNDRY_FLR_1 08-FEB-20:40 0.00 0.00 0.00 -52905.68 0.00 0.00 404.66 357.21 44299.38 0.00 0.00 0.00 8144.54 0.00 -0.00 0.00 -300.11 0.00
CAFE_FLR_1 23-DEC-00:33 0.00 0.00 0.00 -20250.84 0.00 0.00 9072.05 391.53 304.82 0.00 0.00 0.00 13653.86 0.00 -2762.28 0.00 -409.16 0.00
LOBBY_FLR_1 11-APR-04:15 0.00 0.00 0.00 -62840.03 0.00 0.00 26331.89 2281.15 3167.12 0.00 0.00 0.00 36238.91 0.00 -3907.58 0.00 -1271.45 0.00
ROOM_1_FLR_3 20-MAY-15:01 0.00 -13710.80 0.00 -643.89 0.00 0.00 130.72 161.71 305.54 7789.68 0.00 219.45 5747.59 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_3 15-JUN-18:02 0.00 -13629.41 0.00 -644.43 0.00 0.00 335.50 436.07 516.20 6541.36 0.00 300.12 6144.58 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 22-OCT-13:20 0.00 -41436.13 0.00 -9379.12 0.00 0.00 0.00 1930.94 5686.12 52841.55 0.00 322.51 0.00 0.00 -0.00 0.00 0.00 -9965.88
ROOM_4_MULT19_FLR_3 02-JUN-18:01 0.00 -85204.60 0.00 -8848.53 0.00 0.00 6374.67 5209.05 9610.21 9450.74 0.00 1686.98 61721.49 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 15-JUN-08:61 0.00 -12048.91 0.00 -649.60 0.00 0.00 87.15 215.61 453.05 7856.16 0.00 162.67 3923.88 0.00 -0.00 0.00 0.00 0.00
ROOM_6_FLR_3 15-JUN-08:61 0.00 -11969.95 0.00 -650.66 0.00 0.00 87.15 215.58 452.99 7973.69 0.00 162.25 3728.95 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 15-JUN-18:30 0.00 0.00 0.00 -13938.46 0.00 0.00 4080.27 7967.22 0.00 2736.32 0.00 316.05 0.00 0.00 -0.00 0.00 0.00 -1161.41
ROOM_1_FLR_6 15-JUN-15:02 0.00 -3643.47 0.00 -160.64 0.00 0.00 58.82 34.30 68.48 2007.17 0.00 87.36 1547.98 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_6 15-JUN-18:02 0.00 -3617.60 0.00 -161.02 0.00 0.00 83.88 109.02 129.05 1625.21 0.00 74.74 1756.72 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 30-SEP-15:01 0.00 -16277.57 0.00 -1046.93 0.00 0.00 294.12 228.73 673.54 5652.25 0.00 146.04 10329.82 0.00 -0.00 0.00 0.00 0.00
BANQUET_FLR_6 15-FEB-23:57 0.00 0.00 0.00 -32415.89 0.00 0.00 15871.78 1031.35 6747.90 0.00 0.00 0.00 10550.44 0.00 -1485.65 0.00 -299.94 0.00
DINING_FLR_6 17-MAR-04:10 0.00 0.00 0.00 -41476.55 0.00 0.00 15856.70 687.57 2249.30 0.00 0.00 0.00 24545.79 0.00 -1577.83 0.00 -284.99 0.00
KITCHEN_FLR_6 27-DEC-11:51 0.00 0.00 0.00 -38360.84 0.00 0.00 264.75 302.73 24259.91 718.68 0.00 0.00 13109.14 0.00 -0.00 0.00 -294.37 0.00
CORRIDOR_FLR_6 03-JUL-14:30 0.00 0.00 0.00 -7016.36 0.00 0.00 462.68 658.76 0.00 1880.04 0.00 162.42 3852.46 0.00 -0.00 0.00 0.00 0.00
Total Facility 15-JUN-18:02 0.00 -182215.52 0.00 -223513.66 0.00 0.00 74518.35 53784.22 122326.88 61813.62 0.00 7220.42 86065.70 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 15-FEB-23:10 0.00 0.00 3749.07 0.00 0.00 0.00 6716.62 4728.51 4258.44 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -19452.64
RETAIL_1_FLR_1 27-DEC-07:15 0.00 0.00 810.01 0.00 0.00 0.00 358.03 391.34 433.01 0.00 0.00 0.00 0.00 0.00 -1247.05 0.00 -285.35 -459.98
RETAIL_2_FLR_1 31-DEC-09:57 0.00 0.00 373.83 0.00 0.00 0.00 490.48 271.91 334.29 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -76.10 -1394.41
MECH_FLR_1 31-DEC-09:57 0.00 0.00 357.78 0.00 0.00 0.00 109.40 453.47 353.45 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -167.08 -1107.02
STORAGE_FLR_1 22-NOV-05:53 0.00 0.00 382.30 0.00 0.00 0.00 150.18 50.60 76.47 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -88.02 -571.54
LAUNDRY_FLR_1 11-APR-02:36 0.00 0.00 2812.82 0.00 0.00 0.00 543.98 39.69 9326.18 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -248.72 -12473.95
CAFE_FLR_1 03-DEC-11:58 0.00 0.00 3554.43 0.00 0.00 0.00 3528.46 358.25 406.43 2127.08 0.00 0.00 0.00 0.00 -0.00 0.00 -372.08 -9602.58
LOBBY_FLR_1 22-NOV-05:53 0.00 0.00 7529.71 0.00 0.00 0.00 26878.41 2281.15 3167.12 0.00 0.00 0.00 0.00 0.00 -3668.37 0.00 -1257.12 -34930.90
ROOM_1_FLR_3 27-DEC-09:01 9213.61 272.35 0.00 -272.35 0.00 0.00 108.88 215.61 453.05 1087.56 0.00 0.00 0.00 0.00 -0.00 0.00 -530.81 -10547.90
ROOM_2_FLR_3 07-DEC-09:01 9284.86 273.87 0.00 -273.87 0.00 0.00 107.92 215.58 452.99 0.00 0.00 0.00 0.00 0.00 -854.64 0.00 -389.88 -8816.84
ROOM_3_MULT19_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 27-JAN-09:01 52745.99 4294.99 0.00 -4294.99 0.00 0.00 1978.02 2575.24 8433.45 0.00 0.00 0.00 0.00 0.00 -9239.98 0.00 -2976.47 -53516.25
ROOM_5_FLR_3 26-DEC-09:01 8885.24 282.47 0.00 -282.47 0.00 0.00 108.13 215.61 453.05 0.00 0.00 0.00 0.00 0.00 -487.68 0.00 -526.42 -8647.92
ROOM_6_FLR_3 26-NOV-19:01 8920.51 287.33 0.00 -287.33 0.00 0.00 347.35 489.96 516.20 0.00 0.00 0.00 0.00 0.00 -1914.65 0.00 -382.99 -7976.38
CORRIDOR_FLR_3 31-DEC-09:57 0.00 0.00 2738.54 0.00 0.00 0.00 3430.75 2987.71 0.00 4001.60 0.00 0.00 0.00 0.00 -0.00 0.00 -521.24 -12637.36
ROOM_1_FLR_6 26-NOV-19:01 2768.64 66.74 0.00 -66.74 0.00 0.00 88.39 122.50 129.07 0.00 0.00 0.00 0.00 0.00 -463.64 0.00 -94.17 -2550.79
ROOM_2_FLR_6 07-DEC-09:01 2776.84 66.00 0.00 -66.00 0.00 0.00 27.22 53.90 113.25 0.00 0.00 0.00 0.00 0.00 -199.44 0.00 -96.90 -2674.86
ROOM_3_MULT9_FLR_6 26-DEC-09:01 12750.36 495.67 0.00 -495.67 0.00 0.00 239.44 304.96 998.70 0.00 0.00 0.00 0.00 0.00 -602.90 0.00 -619.81 -13070.75
BANQUET_FLR_6 19-DEC-10:59 0.00 0.00 4061.86 0.00 0.00 0.00 4104.03 687.57 6747.90 0.00 0.00 0.00 0.00 0.00 -444.58 0.00 -274.35 -14882.43
DINING_FLR_6 19-DEC-10:59 0.00 0.00 3193.32 0.00 0.00 0.00 4004.92 687.57 6747.90 0.00 0.00 0.00 0.00 0.00 -492.34 0.00 -281.76 -13859.61
KITCHEN_FLR_6 06-MAR-00:28 0.00 0.00 605.36 0.00 0.00 0.00 1394.83 242.18 5415.98 0.00 0.00 0.00 0.00 0.00 -1234.12 0.00 -264.86 -6159.37
CORRIDOR_FLR_6 27-DEC-07:30 0.00 0.00 1319.43 0.00 0.00 0.00 733.31 1317.51 0.00 0.00 0.00 0.00 0.00 0.00 -1634.21 0.00 -354.65 -1381.39
Total Facility 27-DEC-09:01 2849.90 110142.97 151.24 -110142.97 0.00 0.00 23709.37 26712.50 88432.23 66081.34 0.00 0.00 0.00 0.00 -10822.51 0.00 -14079.73 -183034.33



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 24.9468 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 24.8182 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 13.7150 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.7955 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.000000 142.3000 0.003581 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.001045 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.9169 2.9169 1.2543 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3761 0.3761 0.1162 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2829 0.2829 0.1347 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2888 0.2888 0.0866 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1415 0.1415 0.0848 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.7796 3.7796 1.1339 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5854 1.5854 0.9924 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.2603 5.2603 2.7774 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6563 1.6563 0.6957 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5427 2.5427 1.7418 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6635 2.6635 1.7419 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5802 2.5802 0.7741 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8725 0.8725 0.2617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 24.9468 24.8182 24.9468 11.7955 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4585 1.4585 1.2543 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1881 0.1881 0.1162 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1415 0.1415 0.1347 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1444 0.1444 0.0866 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0848 0.0848 0.0848 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.8898 1.8898 1.1339 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9924 0.9924 0.9924 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.7774 2.7774 2.7774 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8282 0.8282 0.6957 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7418 1.7418 1.7418 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7419 1.7419 1.7419 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2901 1.2901 0.7741 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4362 0.4362 0.2617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 13.7150 11.7955 11.7955 11.7955 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 193.17
Number of hours not met 193.17


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 268.39 191594.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 1434.84 167567.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 767.09 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 242.91 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 959.56 59492.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 14.43 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 8.99 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 32.45 1868.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.91 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 634.57 50591.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 179.41 8638.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 185.17 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.74 4738.75 2843.91 256972.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 20.52 2032.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 34.27 1245.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1806.89 5993.12
Natural Gas 1788.84 4901.14
Additional 0.00 0.00
Total 3595.73 10894.26


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 67.61
Space Heating 0.00
Space Cooling 126.47
Fans (All) 55.93
Service Water Heating 8.00
Receptacle Equipment 153.81
Miscellaneous (All) 528.25
Subtotal 528.25


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 23.66
Service Water Heating 250.67
Miscellaneous (All) 432.00
Subtotal 432.00


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 7.04
Space Heating 2.46
Space Cooling 13.17
Fans (All) 5.82
Service Water Heating 26.94
Receptacle Equipment 32.44
Miscellaneous 12.12


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2667. 8760.
LTG_SCH_LOBBY 3061. 8760.
LTG_SCH_STORAGE 1339. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 2678. 8760.
LTG_SCH_GUESTROOM 2482. 8760.
LTG_SCH_CORRIDOR 3061. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3924. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 18.89 365 18.89 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 23.33 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8759.67 0.33 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8759.50 0.50 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8759.50 0.00 0.00 0.00 0.00
Max 8760.00 0.50 0.00 0.00 0.00
Average 8759.96 0.04 0.00 0.00 0.00
Sum 192719.17 0.83 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37201.00 2.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108264.50 4.50 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 4.50 0.00 0.00 0.00
Average 288886.75 0.30 0.00 0.00 0.00
Sum 6355508.50 6.50 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8736.67 23.33 0.00 0.00 0.00
RETAIL_2_FLR_1 8748.83 11.17 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8361.00 399.00 0.00 0.00 0.00
LOBBY_FLR_1 8351.00 409.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8611.17 148.83 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8335.33 424.67 0.00 0.00 0.00
DINING_FLR_6 8350.00 410.00 0.00 0.00 0.00
KITCHEN_FLR_6 8759.33 0.67 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8335.33 0.00 0.00 0.00 0.00
Max 8760.00 424.67 0.00 0.00 0.00
Average 8676.97 83.03 0.00 0.00 0.00
Sum 190893.33 1826.67 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 49974.33 204.67 0.00 0.00 0.00
RETAIL_2_FLR_1 59034.17 121.83 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 659890.83 50526.17 0.00 0.00 0.00
LOBBY_FLR_1 1969512.83 145916.17 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 97861.33 2496.67 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1154881.33 90833.67 0.00 0.00 0.00
DINING_FLR_6 1158345.83 87369.17 0.00 0.00 0.00
KITCHEN_FLR_6 108265.17 3.83 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 1969512.83 145916.17 0.00 0.00 0.00
Average 271729.22 17157.83 0.00 0.00 0.00
Sum 5978042.83 377472.17 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:07

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

For: Environment

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B

For: Environment

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO

For: Environment

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.342492E+11 36391.18 26-JAN-20:51 3.90 -2.9 0.819417E+10 5002.88 20-JAN-00:10 3.90 -2.9
February 0.256963E+11 34516.86 02-FEB-22:34 2.93 -2.7 0.709716E+10 4940.41 08-FEB-22:10 3.03 0.14
March 0.257623E+11 19817.85 17-MAR-03:44 5.87 -0.4 0.732802E+10 4779.73 01-MAR-22:10 5.87 -0.4
April 0.259205E+11 17820.58 11-APR-04:30 5.30 0.69 0.712978E+10 4616.30 11-APR-21:10 13.12 3.77
May 0.285093E+11 14617.15 06-MAY-06:00 10.00 2.15 0.760571E+10 4753.06 12-MAY-22:10 21.52 10.32
June 0.293915E+11 13973.73 23-JUN-21:00 23.30 15.34 0.760139E+10 4837.19 30-JUN-22:10 28.43 17.10
July 0.361337E+11 20668.26 19-JUL-21:00 23.90 20.39 0.817137E+10 4837.14 05-JUL-21:00 23.90 20.39
August 0.413630E+11 23564.24 24-AUG-21:00 26.70 16.71 0.825800E+10 4837.26 22-AUG-00:10 26.70 16.71
September 0.444782E+11 25575.64 21-SEP-21:00 26.10 17.37 0.797676E+10 4851.12 25-SEP-03:39 10.77 9.09
October 0.453757E+11 35484.32 25-OCT-05:30 6.95 5.28 0.823624E+10 5023.98 25-OCT-03:20 6.95 5.28
November 0.422185E+11 40523.33 19-NOV-23:56 4.40 -1.2 0.796397E+10 5044.75 17-NOV-00:20 4.40 -1.2
December 0.396697E+11 37239.34 02-DEC-07:38 4.80 0.46 0.823113E+10 5071.99 23-DEC-00:20 5.20 0.42
                     
Annual Sum or Average 0.418768E+12         0.937937E+11        
Minimum of Months 0.256963E+11 13973.73   2.93 -2.9 0.709716E+10 4616.30   3.03 -2.9
Maximum of Months 0.453757E+11 40523.33   26.70 20.39 0.825800E+10 5071.99   28.43 20.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.243335E+10 3119.63 26-JAN-12:32 4.23 -2.6 0.699966E+09 487.20 12-JAN-22:10 4.23 -2.6
February 0.243152E+10 3000.98 07-FEB-13:30 20.30 9.54 0.649135E+09 491.82 21-FEB-22:40 11.47 3.03
March 0.267115E+10 2431.99 16-MAR-13:10 22.30 9.05 0.739660E+09 491.82 06-MAR-22:19 22.30 9.05
April 0.328368E+10 2529.23 03-APR-14:10 26.70 11.67 0.771026E+09 491.82 19-APR-23:30 25.00 11.56
May 0.392103E+10 2489.31 19-MAY-18:15 32.93 15.38 0.825551E+09 491.86 18-MAY-00:10 32.93 15.38
June 0.462944E+10 2868.32 15-JUN-18:15 35.73 14.50 0.811813E+09 491.86 30-JUN-22:10 28.43 17.10
July 0.480353E+10 2836.02 26-JUL-18:03 33.77 19.75 0.836165E+09 491.84 05-JUL-21:00 33.77 19.75
August 0.480685E+10 3004.70 27-AUG-12:00 33.30 15.93 0.837598E+09 491.86 22-AUG-00:10 33.30 15.93
September 0.481621E+10 3612.28 19-SEP-13:20 33.17 16.78 0.804779E+09 491.85 19-SEP-23:10 23.85 15.15
October 0.427791E+10 3750.87 18-OCT-13:00 27.80 18.14 0.804875E+09 491.86 10-OCT-21:10 27.80 18.14
November 0.312891E+10 3487.24 10-NOV-12:00 21.10 12.09 0.718155E+09 491.81 07-NOV-22:40 21.10 12.09
December 0.218156E+10 3219.97 21-DEC-12:55 8.90 2.48 0.684811E+09 468.05 15-DEC-22:19 8.90 2.48
                     
Annual Sum or Average 0.433851E+11         0.918353E+10        
Minimum of Months 0.218156E+10 2431.99   4.23 -2.6 0.649135E+09 468.05   4.23 -2.6
Maximum of Months 0.481621E+10 3750.87   35.73 19.75 0.837598E+09 491.86   33.77 19.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.273046E+10 2549.95 04-JAN-22:44 4.90 -1.3 0.868205E+09 573.82 04-JAN-22:00 5.00 -1.3
February 0.256761E+10 3206.90 08-FEB-22:01 3.03 0.14 0.799143E+09 587.74 08-FEB-22:10 3.03 0.14
March 0.295296E+10 2819.68 20-MAR-22:00 6.70 1.01 0.904057E+09 593.28 17-MAR-21:49 6.70 1.01
April 0.326803E+10 2086.76 28-APR-21:00 22.80 12.84 0.911839E+09 570.97 10-APR-21:00 22.80 12.84
May 0.374806E+10 2281.44 19-MAY-21:00 30.00 13.65 0.959743E+09 569.58 18-MAY-00:10 30.00 13.65
June 0.398598E+10 2494.28 15-JUN-21:00 33.30 13.72 0.937067E+09 569.57 30-JUN-22:10 28.43 17.10
July 0.408894E+10 2428.08 25-JUL-21:00 31.70 17.64 0.964514E+09 569.55 05-JUL-21:00 31.70 17.64
August 0.401846E+10 2462.69 07-AUG-21:00 31.70 16.85 0.967542E+09 569.57 22-AUG-00:10 24.22 16.48
September 0.378948E+10 2333.05 20-SEP-20:10 25.40 15.25 0.933609E+09 569.58 19-SEP-04:10 25.40 15.25
October 0.347631E+10 2249.81 05-OCT-20:10 23.80 16.56 0.948003E+09 569.57 10-OCT-21:10 14.13 9.16
November 0.289593E+10 2182.30 26-NOV-00:14 4.80 2.00 0.875620E+09 572.42 17-NOV-00:20 4.80 2.00
December 0.265180E+10 2254.77 06-DEC-22:20 5.73 0.69 0.852585E+09 565.28 06-DEC-23:10 5.00 0.09
                     
Annual Sum or Average 0.401740E+11         0.109219E+11        
Minimum of Months 0.256761E+10 2086.76   3.03 -1.3 0.799143E+09 565.28   3.03 -1.3
Maximum of Months 0.408894E+10 3206.90   33.30 17.64 0.967542E+09 593.28   31.70 17.64



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.157569E+10 1283.31 02-JAN-00:33 4.83 3.01 0.169145E+09 112.36 03-JAN-22:10 12.43 6.06
February 0.150436E+10 1242.12 05-FEB-00:17 5.93 1.82 0.157686E+09 117.50 08-FEB-22:10 3.03 0.14
March 0.177323E+10 1404.18 17-MAR-03:44 5.87 -0.4 0.181745E+09 120.45 16-MAR-22:10 5.87 -0.4
April 0.212856E+10 1865.10 21-APR-20:00 26.10 11.77 0.191258E+09 120.55 10-APR-21:00 26.10 11.77
May 0.294918E+10 2295.32 31-MAY-20:00 29.40 14.60 0.204508E+09 120.46 18-MAY-00:10 29.40 14.60
June 0.368893E+10 2636.68 15-JUN-20:00 33.90 14.00 0.199164E+09 120.46 30-JUN-22:10 28.43 17.10
July 0.379759E+10 2583.04 03-JUL-20:00 28.30 19.12 0.205006E+09 120.46 05-JUL-21:00 27.80 17.53
August 0.348434E+10 2509.96 07-AUG-20:00 31.70 17.36 0.205741E+09 120.46 22-AUG-00:10 24.22 16.48
September 0.293457E+10 2190.86 22-SEP-20:00 26.10 18.64 0.198255E+09 120.46 19-SEP-04:19 26.10 18.64
October 0.229674E+10 2052.43 05-OCT-20:00 23.90 16.65 0.199101E+09 120.46 10-OCT-21:10 14.13 9.16
November 0.172165E+10 1347.33 26-NOV-00:14 4.80 2.00 0.175611E+09 120.45 09-NOV-22:19 4.80 2.00
December 0.150136E+10 1121.34 30-DEC-10:29 4.15 0.79 0.165399E+09 109.04 15-DEC-22:10 4.15 0.79
                     
Annual Sum or Average 0.293562E+11         0.225262E+10        
Minimum of Months 0.150136E+10 1121.34   4.15 -0.4 0.157686E+09 109.04   3.03 -0.4
Maximum of Months 0.379759E+10 2636.68   33.90 19.12 0.205741E+09 120.55   29.40 18.64



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.111166E+10 1154.20 02-JAN-00:33 4.83 3.01 0.118055E+09 74.47 04-JAN-23:10 4.53 -1.5
February 0.114778E+10 1068.91 05-FEB-00:17 5.93 1.82 0.108671E+09 77.99 08-FEB-22:10 3.03 0.14
March 0.141544E+10 1269.36 17-MAR-03:44 5.87 -0.4 0.123601E+09 79.67 16-MAR-21:49 5.87 -0.4
April 0.165013E+10 1118.84 11-APR-04:30 5.30 0.69 0.130170E+09 86.69 21-APR-22:10 24.13 8.96
May 0.190840E+10 916.63 31-MAY-18:07 30.92 15.25 0.144012E+09 91.06 31-MAY-22:10 27.12 13.11
June 0.201197E+10 984.89 15-JUN-21:00 33.30 13.72 0.146720E+09 92.66 16-JUN-22:10 30.92 15.69
July 0.207596E+10 976.50 03-JUL-10:35 34.07 18.96 0.150776E+09 92.66 03-JUL-21:19 26.50 18.67
August 0.202200E+10 967.48 06-AUG-10:35 31.67 18.03 0.149157E+09 92.66 07-AUG-21:49 29.45 17.70
September 0.188204E+10 919.71 25-SEP-03:12 10.93 9.15 0.140314E+09 90.42 22-SEP-22:10 10.93 9.15
October 0.173986E+10 1070.36 25-OCT-04:07 8.12 5.97 0.136315E+09 88.74 05-OCT-21:40 8.12 5.97
November 0.136108E+10 1205.92 26-NOV-00:14 4.80 2.00 0.119913E+09 81.13 09-NOV-22:40 4.80 2.00
December 0.938395E+09 976.33 09-DEC-23:15 5.73 1.35 0.117407E+09 72.69 15-DEC-23:10 13.80 4.57
                     
Annual Sum or Average 0.192647E+11         0.158511E+10        
Minimum of Months 0.938395E+09 916.63   4.80 -0.4 0.108671E+09 72.69   3.03 -1.5
Maximum of Months 0.207596E+10 1269.36   34.07 18.96 0.150776E+09 92.66   30.92 18.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.482120E+11 51918.33 26-JAN-20:51 3.90 -2.9 0.648909E+09 545.14 20-JAN-00:10 3.90 -2.9
February 0.442190E+11 52902.86 08-FEB-20:40 3.50 -0.4 0.585578E+09 578.87 15-FEB-23:19 5.00 1.14
March 0.497726E+11 49190.93 28-MAR-21:27 4.45 1.48 0.650085E+09 522.24 17-MAR-21:49 4.45 1.48
April 0.497882E+11 39211.09 12-APR-06:38 5.57 0.02 0.628781E+09 449.71 11-APR-02:00 5.57 0.02
May 0.527560E+11 39365.87 30-MAY-20:00 28.90 14.28 0.650702E+09 384.96 08-MAY-04:30 28.90 14.28
June 0.521745E+11 39770.82 15-JUN-20:00 33.90 14.00 0.630917E+09 381.86 16-JUN-21:10 32.52 14.90
July 0.536071E+11 39720.01 03-JUL-20:00 28.30 19.12 0.649368E+09 381.85 25-JUL-21:10 31.42 17.57
August 0.534612E+11 39636.36 04-AUG-20:00 33.30 17.89 0.652107E+09 381.87 22-AUG-21:10 29.22 13.60
September 0.511278E+11 39287.97 20-SEP-20:00 25.60 15.27 0.629090E+09 381.89 19-SEP-21:10 25.60 15.27
October 0.511837E+11 39041.42 05-OCT-20:00 23.90 16.65 0.648537E+09 467.89 25-OCT-03:20 7.57 5.72
November 0.477851E+11 49602.81 27-NOV-21:46 2.67 0.42 0.626167E+09 447.60 18-NOV-04:49 2.67 0.42
December 0.478261E+11 50674.71 29-DEC-22:56 2.80 -0.9 0.647794E+09 544.65 23-DEC-00:20 2.80 -0.9
                     
Annual Sum or Average 0.601913E+12         0.764803E+10        
Minimum of Months 0.442190E+11 39041.42   2.67 -2.9 0.585578E+09 381.85   2.67 -2.9
Maximum of Months 0.536071E+11 52902.86   33.90 19.12 0.652107E+09 578.87   32.52 17.57



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.192331E+11 14942.01 02-JAN-00:33 4.83 3.01 0.948591E+10 6775.40 02-JAN-00:40 4.83 3.01
February 0.180006E+11 14006.05 05-FEB-00:17 5.93 1.82 0.868327E+10 6636.08 15-FEB-23:19 5.00 1.14
March 0.199287E+11 15671.14 17-MAR-03:44 5.87 -0.4 0.967762E+10 6562.40 17-MAR-21:49 6.83 0.34
April 0.209109E+11 13392.31 11-APR-04:30 5.30 0.69 0.973578E+10 6472.15 11-APR-02:00 5.30 0.69
May 0.226871E+11 11195.62 19-MAY-21:10 29.90 13.55 0.103056E+11 6460.84 08-MAY-22:40 29.90 13.55
June 0.236288E+11 11957.56 15-JUN-21:10 32.57 13.55 0.102480E+11 6461.65 21-JUN-01:49 24.72 16.02
July 0.244372E+11 11819.14 26-JUL-21:10 28.62 18.19 0.105619E+11 6461.05 05-JUL-21:00 28.62 18.19
August 0.244951E+11 12366.60 07-AUG-21:10 31.25 17.07 0.106417E+11 6461.61 11-AUG-03:00 24.40 15.32
September 0.240043E+11 12330.40 20-SEP-15:03 33.30 17.34 0.103034E+11 6461.45 19-SEP-23:10 33.30 17.34
October 0.235115E+11 12897.92 25-OCT-04:07 8.12 5.97 0.103661E+11 6619.13 25-OCT-03:20 8.12 5.97
November 0.203937E+11 14769.65 26-NOV-00:14 4.80 2.00 0.953667E+10 6522.56 18-NOV-05:40 4.80 2.00
December 0.187113E+11 20257.70 23-DEC-00:33 5.40 0.46 0.931828E+10 6681.66 23-DEC-00:20 5.40 0.46
                     
Annual Sum or Average 0.259942E+12         0.118864E+12        
Minimum of Months 0.180006E+11 11195.62   4.80 -0.4 0.868327E+10 6460.84   4.80 0.34
Maximum of Months 0.244951E+11 20257.70   33.30 18.19 0.106417E+11 6775.40   33.30 18.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.597417E+11 62095.90 20-JAN-00:05 4.32 2.79 0.304518E+11 20143.63 20-JAN-00:10 4.32 2.79
February 0.556075E+11 62404.06 17-FEB-01:00 5.00 1.32 0.278435E+11 20175.91 15-FEB-23:19 5.00 1.32
March 0.627758E+11 61348.30 20-MAR-22:00 6.70 1.01 0.311638E+11 20215.93 17-MAR-21:49 6.70 1.01
April 0.671549E+11 62847.71 11-APR-04:15 5.40 0.74 0.308191E+11 19981.42 11-APR-02:00 5.40 0.74
May 0.751855E+11 41462.75 31-MAY-21:10 28.13 13.59 0.321684E+11 19229.78 08-MAY-04:30 28.13 13.59
June 0.788825E+11 44225.37 15-JUN-21:10 32.57 13.55 0.313739E+11 19185.06 30-JUN-22:10 28.43 17.10
July 0.814125E+11 43583.03 26-JUL-21:10 28.62 18.19 0.323119E+11 19184.37 05-JUL-21:00 28.62 18.19
August 0.806463E+11 44431.94 07-AUG-21:10 31.25 17.07 0.324523E+11 19185.43 22-AUG-00:10 24.22 16.48
September 0.766084E+11 42454.93 21-SEP-21:10 26.10 17.46 0.313752E+11 19185.93 19-SEP-04:10 26.10 17.46
October 0.728435E+11 41653.58 05-OCT-21:10 23.22 16.17 0.321607E+11 20122.22 25-OCT-03:20 7.57 5.72
November 0.624212E+11 60457.17 11-NOV-06:10 5.73 3.72 0.303003E+11 19995.56 17-NOV-00:20 5.03 0.87
December 0.583578E+11 53643.45 29-DEC-22:56 2.80 -0.9 0.300882E+11 20143.36 23-DEC-00:20 2.80 -0.9
                     
Annual Sum or Average 0.831638E+12         0.372509E+12        
Minimum of Months 0.556075E+11 41462.75   2.80 -0.9 0.278435E+11 19184.37   2.80 -0.9
Maximum of Months 0.814125E+11 62847.71   32.57 18.19 0.324523E+11 20215.93   28.62 18.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.285635E+09 3247.51 03-JAN-16:01 20.10 7.84 96150093.52 56.69 01-JAN-05:49 20.10 7.84
February 0.413089E+09 3439.09 20-FEB-16:01 23.12 8.59 87418641.31 56.69 06-FEB-23:10 23.12 8.59
March 0.715846E+09 3456.16 21-MAR-15:01 24.50 9.45 97552836.46 56.69 06-MAR-22:40 24.50 9.45
April 0.155336E+10 3568.37 16-APR-15:01 29.50 11.50 95275747.72 56.69 28-APR-21:00 21.70 12.89
May 0.228159E+10 3588.67 20-MAY-15:01 32.20 15.53 98871201.10 56.69 23-MAY-23:19 19.63 15.09
June 0.276725E+10 3584.50 15-JUN-15:02 38.22 15.87 95943685.26 56.70 16-JUN-21:00 31.10 15.68
July 0.276541E+10 3230.66 11-JUL-08:61 27.48 17.81 99030715.49 56.70 31-JUL-21:30 30.10 17.72
August 0.260916E+10 3214.32 08-AUG-18:01 29.22 19.49 99055496.15 56.70 09-AUG-21:10 28.03 17.04
September 0.237919E+10 3586.97 30-SEP-15:01 28.30 13.14 95727797.28 56.70 13-SEP-02:30 28.30 13.14
October 0.165710E+10 3558.55 21-OCT-15:01 26.10 12.52 98476830.96 56.70 05-OCT-00:00 26.10 12.52
November 0.693615E+09 3447.44 09-NOV-16:01 23.22 12.98 94156735.27 56.69 01-NOV-01:10 23.22 12.98
December 0.198656E+09 3117.46 23-DEC-16:01 16.73 6.11 95839056.47 56.69 18-DEC-04:19 16.73 6.11
                     
Annual Sum or Average 0.183199E+11         0.115350E+10        
Minimum of Months 0.198656E+09 3117.46   16.73 6.11 87418641.31 56.69   16.73 6.11
Maximum of Months 0.276725E+10 3588.67   38.22 19.49 99055496.15 56.70   31.10 17.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.110826E+09 3111.70 12-JAN-16:01 18.72 10.12 94420758.77 56.69 21-JAN-03:09 5.60 2.53
February 0.197621E+09 3368.39 20-FEB-16:01 23.12 8.59 86088979.89 56.69 11-FEB-04:49 23.12 8.59
March 0.476275E+09 3389.10 21-MAR-15:01 24.50 9.45 96648030.36 56.69 16-MAR-21:10 24.50 9.45
April 0.136600E+10 3526.43 30-APR-18:01 29.63 12.67 95020930.41 56.69 28-APR-21:40 29.63 12.67
May 0.223149E+10 3561.12 20-MAY-18:01 31.52 15.16 98841412.71 56.70 28-MAY-00:10 21.02 16.91
June 0.278115E+10 3568.43 15-JUN-18:02 35.92 14.47 95968225.21 56.70 27-JUN-21:19 28.33 16.38
July 0.275250E+10 3198.73 11-JUL-08:61 27.48 17.81 99043307.74 56.70 26-JUL-21:30 28.05 18.23
August 0.247435E+10 3207.09 08-AUG-18:01 29.22 19.49 99022307.06 56.70 04-AUG-21:30 29.22 19.49
September 0.203873E+10 3525.56 30-SEP-15:01 28.30 13.14 95590204.00 56.70 13-SEP-00:49 28.30 13.14
October 0.120338E+10 3487.99 21-OCT-15:01 26.10 12.52 97903552.51 56.69 04-OCT-23:10 26.10 12.52
November 0.311548E+09 3380.84 09-NOV-16:01 23.22 12.98 92898871.92 56.69 01-NOV-00:00 23.22 12.98
December 78055155.24 2896.50 16-DEC-16:02 14.72 4.08 93995847.71 56.69 14-DEC-22:40 14.72 4.08
                     
Annual Sum or Average 0.160219E+11         0.114544E+10        
Minimum of Months 78055155.24 2896.50   14.72 4.08 86088979.89 56.69   5.60 2.53
Maximum of Months 0.278115E+10 3568.43   35.92 19.49 99043307.74 56.70   29.63 19.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.382642E+09 558.38 12-JAN-14:30 18.60 9.87 0.00 0.00 01-JAN-00:10 18.60 9.87
February 0.365942E+09 539.78 07-FEB-13:40 20.20 9.50 0.00 0.00 01-FEB-00:10 20.20 9.50
March 0.348948E+09 439.99 16-MAR-13:30 22.50 9.16 0.00 0.00 01-MAR-00:10 22.50 9.16
April 0.462105E+09 426.99 04-APR-13:30 26.95 10.78 0.00 0.00 01-APR-00:10 26.95 10.78
May 0.565659E+09 383.28 19-MAY-20:20 30.73 14.26 0.00 0.00 01-MAY-00:10 30.73 14.26
June 0.692993E+09 441.43 15-JUN-17:13 36.83 15.02 0.00 0.00 01-JUN-00:10 36.83 15.02
July 0.729244E+09 441.85 26-JUL-17:17 35.20 19.91 0.00 0.00 01-JUL-00:10 35.20 19.91
August 0.739556E+09 495.40 27-AUG-13:40 34.40 16.46 0.00 0.00 01-AUG-00:10 34.40 16.46
September 0.774132E+09 600.10 19-SEP-13:30 33.35 16.80 0.00 0.00 01-SEP-00:10 33.35 16.80
October 0.695190E+09 668.60 22-OCT-13:20 25.97 14.61 0.00 0.00 01-OCT-00:10 25.97 14.61
November 0.518481E+09 624.97 09-NOV-13:50 23.22 12.39 0.00 0.00 01-NOV-00:10 23.22 12.39
December 0.340085E+09 472.07 16-DEC-14:10 15.00 4.30 0.00 0.00 01-DEC-00:10 15.00 4.30
                     
Annual Sum or Average 0.661498E+10         0.00        
Minimum of Months 0.340085E+09 383.28   15.00 4.30 0.00 0.00   15.00 4.30
Maximum of Months 0.774132E+09 668.60   36.83 19.91 0.00 0.00   36.83 19.91



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.100715E+09 676.35 15-JAN-09:01 7.88 7.51 94848498.37 56.69 03-JAN-22:10 7.88 7.51
February 0.152337E+09 971.53 20-FEB-09:01 11.23 4.20 86037019.95 56.69 06-FEB-22:19 11.23 4.20
March 0.268801E+09 1093.48 21-MAR-18:01 22.57 8.48 95927964.97 56.69 16-MAR-21:19 22.57 8.48
April 0.537161E+09 1232.45 21-APR-18:01 29.95 11.64 93859433.61 56.69 28-APR-21:10 22.62 12.85
May 0.805025E+09 1236.05 20-MAY-18:01 31.52 15.16 97972273.51 56.69 28-MAY-01:39 20.20 16.18
June 0.983590E+09 1237.53 02-JUN-18:01 36.83 15.80 95465629.24 56.69 02-JUN-21:10 31.52 14.93
July 0.999974E+09 1152.04 26-JUL-15:02 36.60 20.09 98514902.56 56.69 05-JUL-21:00 36.60 20.09
August 0.893606E+09 1150.75 04-AUG-15:02 35.68 19.44 98287014.26 56.69 30-AUG-21:10 25.68 16.75
September 0.714015E+09 1205.75 11-SEP-18:01 27.65 13.06 94554218.31 56.69 01-SEP-21:10 27.65 13.06
October 0.494290E+09 1127.84 19-OCT-18:01 22.62 11.36 96682787.57 56.69 04-OCT-23:19 22.62 11.36
November 0.182761E+09 1052.74 08-NOV-19:01 20.92 10.67 92336690.49 56.69 01-NOV-01:10 20.92 10.67
December 83320400.75 833.91 09-DEC-09:02 14.40 6.77 94622874.72 56.69 12-DEC-23:49 6.20 4.93
                     
Annual Sum or Average 0.621560E+10         0.113911E+10        
Minimum of Months 83320400.75 676.35   7.88 4.20 86037019.95 56.69   6.20 4.20
Maximum of Months 0.999974E+09 1237.53   36.83 20.09 98514902.56 56.69   36.60 20.09



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.271148E+09 2836.05 12-JAN-16:01 18.72 10.12 96265176.53 56.69 21-JAN-03:09 5.60 2.53
February 0.460113E+09 3000.13 20-FEB-16:01 23.12 8.59 87857806.39 56.69 07-FEB-23:10 23.12 8.59
March 0.732529E+09 3029.28 21-MAR-15:01 24.50 9.45 97975218.45 56.69 16-MAR-22:40 24.50 9.45
April 0.161755E+10 3119.04 03-APR-15:01 26.88 11.50 95728645.48 56.69 18-APR-21:19 21.83 14.00
May 0.231416E+10 3137.75 20-MAY-15:01 32.20 15.53 99159954.62 56.69 23-MAY-00:40 22.20 15.41
June 0.283039E+10 3174.63 15-JUN-08:61 29.78 13.66 96022855.14 56.70 16-JUN-22:10 30.92 15.69
July 0.282432E+10 2881.59 31-JUL-08:61 24.87 18.88 99117343.68 56.70 31-JUL-21:00 29.60 17.58
August 0.265817E+10 2900.48 03-AUG-08:61 26.28 20.18 99163845.09 56.70 02-AUG-21:10 26.28 20.18
September 0.238203E+10 3132.17 30-SEP-15:01 28.30 13.14 95907792.30 56.69 08-SEP-23:40 28.30 13.14
October 0.156228E+10 3108.16 21-OCT-15:01 26.10 12.52 98591555.18 56.69 03-OCT-23:19 26.10 12.52
November 0.664489E+09 3013.95 09-NOV-16:01 23.22 12.98 94448995.94 56.69 01-NOV-01:49 23.22 12.98
December 0.216251E+09 2696.77 16-DEC-09:02 8.48 2.42 95938930.95 56.69 01-DEC-04:49 8.48 2.42
                     
Annual Sum or Average 0.185334E+11         0.115618E+10        
Minimum of Months 0.216251E+09 2696.77   8.48 2.42 87857806.39 56.69   5.60 2.42
Maximum of Months 0.283039E+10 3174.63   32.20 20.18 99163845.09 56.70   30.92 20.18



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 94656722.00 2276.70 04-JAN-09:02 8.98 3.34 94370545.08 56.69 01-JAN-05:10 8.98 3.34
February 0.225249E+09 2849.07 21-FEB-16:01 22.70 8.11 86422775.51 56.69 26-FEB-05:49 7.88 4.10
March 0.487446E+09 2966.97 22-MAR-15:01 23.90 8.87 97055478.86 56.69 22-MAR-21:10 11.52 4.66
April 0.141806E+10 3087.53 30-APR-18:01 29.63 12.67 95606264.69 56.69 28-APR-21:49 29.63 12.67
May 0.226101E+10 3111.84 20-MAY-15:01 32.20 15.53 99156055.24 56.69 22-MAY-01:10 20.60 14.61
June 0.284476E+10 3155.16 15-JUN-08:61 29.78 13.66 96024892.87 56.70 02-JUN-21:49 29.78 13.66
July 0.281112E+10 2853.82 30-JUL-18:01 28.80 20.02 99117770.92 56.70 27-JUL-21:40 28.80 20.02
August 0.251977E+10 2886.28 08-AUG-18:01 29.22 19.49 99156218.45 56.70 04-AUG-22:19 29.22 19.49
September 0.203054E+10 3077.04 30-SEP-15:01 28.30 13.14 95872454.28 56.69 13-SEP-02:39 28.30 13.14
October 0.109309E+10 3043.82 21-OCT-15:01 26.10 12.52 98169487.98 56.69 03-OCT-22:19 26.10 12.52
November 0.298310E+09 2888.40 09-NOV-16:01 23.22 12.98 92859089.26 56.69 01-NOV-00:00 23.22 12.98
December 78997582.71 2481.58 09-DEC-09:02 14.40 6.77 94013451.98 56.69 29-DEC-23:10 2.33 -1.1
                     
Annual Sum or Average 0.161630E+11         0.114782E+10        
Minimum of Months 78997582.71 2276.70   8.98 3.34 86422775.51 56.69   2.33 -1.1
Maximum of Months 0.284476E+10 3155.16   32.20 20.02 99156218.45 56.70   29.78 20.02



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.308284E+10 2569.02 02-JAN-00:33 4.83 3.01 0.130882E+10 848.26 04-JAN-23:10 4.53 -1.5
February 0.297505E+10 2469.44 05-FEB-00:17 5.93 1.82 0.122662E+10 879.04 22-FEB-22:40 14.40 4.97
March 0.349436E+10 2808.05 17-MAR-03:44 5.87 -0.4 0.141074E+10 904.25 16-MAR-21:40 5.87 -0.4
April 0.391952E+10 2501.63 11-APR-04:30 5.30 0.69 0.148546E+10 951.82 28-APR-22:49 20.78 12.73
May 0.473900E+10 2978.06 19-MAY-18:30 32.75 15.27 0.160508E+10 951.86 18-MAY-00:10 32.75 15.27
June 0.540017E+10 3484.42 15-JUN-18:30 35.55 14.53 0.157207E+10 951.87 30-JUN-22:30 28.30 17.29
July 0.548208E+10 3338.51 26-JUL-18:30 32.50 19.69 0.161820E+10 951.86 05-JUL-21:00 32.50 19.69
August 0.529368E+10 3246.25 07-AUG-18:30 33.05 18.14 0.162114E+10 951.87 22-AUG-00:10 24.22 16.48
September 0.488675E+10 2954.46 20-SEP-18:15 30.40 15.98 0.156259E+10 951.86 18-SEP-01:10 30.40 15.98
October 0.425151E+10 2774.72 05-OCT-20:10 23.80 16.56 0.156049E+10 951.85 05-OCT-23:49 20.65 16.69
November 0.345792E+10 2685.56 26-NOV-00:14 4.80 2.00 0.138368E+10 926.76 01-NOV-00:10 4.80 2.00
December 0.291828E+10 2351.43 30-DEC-10:29 4.15 0.79 0.127698E+10 802.01 15-DEC-22:49 4.15 0.79
                     
Annual Sum or Average 0.499012E+11         0.176319E+11        
Minimum of Months 0.291828E+10 2351.43   4.15 -0.4 0.122662E+10 802.01   4.15 -1.5
Maximum of Months 0.548208E+10 3484.42   35.55 19.69 0.162114E+10 951.87   32.75 19.69



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.216786E+09 3420.04 12-JAN-16:01 18.72 10.12 95518917.43 56.69 21-JAN-03:09 5.60 2.53
February 0.328457E+09 3634.62 20-FEB-16:01 23.12 8.59 86929961.00 56.69 06-FEB-23:10 23.12 8.59
March 0.586881E+09 3648.58 21-MAR-15:01 24.50 9.45 97122807.41 56.69 16-MAR-22:10 24.50 9.45
April 0.143264E+10 3783.45 16-APR-15:01 29.50 11.50 95074243.74 56.69 28-APR-21:30 22.25 12.88
May 0.221703E+10 3804.08 20-MAY-15:01 32.20 15.53 98768938.67 56.70 24-MAY-21:19 21.67 16.43
June 0.283893E+10 3804.09 15-JUN-15:02 38.22 15.87 95924675.11 56.70 21-JUN-00:30 24.45 15.79
July 0.283459E+10 3408.84 18-JUL-18:02 30.40 21.72 99002160.22 56.70 31-JUL-21:10 30.43 17.80
August 0.263096E+10 3392.37 07-AUG-08:61 28.48 17.49 99001330.84 56.70 07-AUG-21:40 29.90 17.57
September 0.232093E+10 3795.06 30-SEP-15:01 28.30 13.14 95628999.67 56.70 13-SEP-00:20 28.30 13.14
October 0.145179E+10 3764.56 21-OCT-15:01 26.10 12.52 98207312.13 56.70 04-OCT-22:00 26.10 12.52
November 0.530755E+09 3643.32 09-NOV-16:01 23.22 12.98 93654932.52 56.69 01-NOV-01:10 23.22 12.98
December 0.152729E+09 3286.20 23-DEC-16:01 16.73 6.11 95214626.15 56.69 18-DEC-04:19 16.73 6.11
                     
Annual Sum or Average 0.175425E+11         0.115005E+10        
Minimum of Months 0.152729E+09 3286.20   16.73 6.11 86929961.00 56.69   5.60 2.53
Maximum of Months 0.283893E+10 3804.09   38.22 21.72 99002160.22 56.70   30.43 17.80



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 80216450.64 3236.63 12-JAN-16:01 18.72 10.12 93701069.58 56.69 18-JAN-04:40 5.93 4.12
February 0.149251E+09 3547.18 20-FEB-16:01 23.12 8.59 85506666.74 56.69 17-FEB-01:10 23.12 8.59
March 0.372202E+09 3566.03 21-MAR-15:01 24.50 9.45 96120504.77 56.69 16-MAR-22:30 24.50 9.45
April 0.124054E+10 3732.07 16-APR-15:01 29.50 11.50 94802244.03 56.69 17-APR-01:19 18.13 13.06
May 0.216452E+10 3769.84 20-MAY-15:01 32.20 15.53 98737256.25 56.70 23-MAY-22:10 20.92 15.65
June 0.285305E+10 3778.58 15-JUN-18:02 35.92 14.47 95956798.64 56.70 19-JUN-02:20 24.03 16.43
July 0.282089E+10 3388.15 18-JUL-18:02 30.40 21.72 99016759.20 56.70 24-JUL-21:10 29.63 17.48
August 0.248948E+10 3371.89 08-AUG-18:01 29.22 19.49 98965886.91 56.70 02-AUG-22:49 29.22 19.49
September 0.196292E+10 3722.01 30-SEP-15:01 28.30 13.14 95476428.47 56.70 21-SEP-23:00 28.30 13.14
October 0.989675E+09 3679.37 21-OCT-15:01 26.10 12.52 97539880.73 56.70 04-OCT-22:10 26.10 12.52
November 0.212110E+09 3559.50 09-NOV-16:01 23.22 12.98 92207113.88 56.69 03-NOV-21:19 23.22 12.98
December 58952495.12 2964.76 16-DEC-16:02 14.72 4.08 93334228.17 56.69 09-DEC-04:19 14.72 4.08
                     
Annual Sum or Average 0.153938E+11         0.114136E+10        
Minimum of Months 58952495.12 2964.76   14.72 4.08 85506666.74 56.69   5.93 4.08
Maximum of Months 0.285305E+10 3778.58   35.92 21.72 99016759.20 56.70   29.63 19.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.544697E+09 1772.29 03-JAN-16:01 20.10 7.84 97526369.74 56.69 03-JAN-22:10 12.43 6.06
February 0.554519E+09 1855.93 20-FEB-16:01 23.12 8.59 88364601.98 56.69 07-FEB-22:30 23.12 8.59
March 0.569408E+09 1866.12 14-MAR-15:01 23.98 9.90 97897156.09 56.69 22-MAR-21:10 11.52 4.66
April 0.869398E+09 1906.52 03-APR-15:01 26.88 11.50 95178159.90 56.69 18-APR-21:30 21.65 13.85
May 0.113006E+10 1902.35 20-MAY-15:01 32.20 15.53 98718357.67 56.69 21-MAY-23:10 21.60 15.78
June 0.142070E+10 1900.33 02-JUN-18:01 36.83 15.80 95821156.58 56.69 21-JUN-02:30 24.45 15.96
July 0.148224E+10 1743.60 14-JUL-18:02 29.27 18.93 98947490.60 56.70 03-JUL-21:30 29.27 18.93
August 0.148114E+10 1739.45 08-AUG-18:01 29.22 19.49 98970018.78 56.70 04-AUG-22:10 29.22 19.49
September 0.149027E+10 1924.95 30-SEP-15:01 28.30 13.14 95696759.47 56.70 12-SEP-21:30 28.30 13.14
October 0.125409E+10 1922.88 21-OCT-15:01 26.10 12.52 98549408.89 56.69 05-OCT-02:49 26.10 12.52
November 0.809384E+09 1864.39 09-NOV-16:01 23.22 12.98 94839588.69 56.69 08-NOV-23:19 23.22 12.98
December 0.494094E+09 1701.11 23-DEC-16:01 16.73 6.11 97484083.53 56.69 21-DEC-22:40 16.73 6.11
                     
Annual Sum or Average 0.121000E+11         0.115799E+10        
Minimum of Months 0.494094E+09 1701.11   16.73 6.11 88364601.98 56.69   11.52 4.66
Maximum of Months 0.149027E+10 1924.95   36.83 19.49 98970018.78 56.70   29.27 19.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.349403E+11 31715.93 31-JAN-23:56 6.70 1.99 0.174017E+11 13119.25 20-JAN-00:10 6.70 1.99
February 0.327280E+11 32423.09 15-FEB-23:57 5.00 1.14 0.159706E+11 13238.58 15-FEB-23:19 5.00 1.14
March 0.378219E+11 31224.39 06-MAR-05:33 5.77 1.16 0.180900E+11 12834.43 17-MAR-21:49 6.83 0.34
April 0.402817E+11 31628.14 10-APR-22:40 7.40 1.81 0.180173E+11 12714.45 11-APR-02:00 6.10 0.79
May 0.445641E+11 22834.90 31-MAY-21:10 28.13 13.59 0.189081E+11 11346.54 18-MAY-00:10 28.13 13.59
June 0.457855E+11 23624.35 15-JUN-21:10 32.57 13.55 0.184634E+11 11350.19 06-JUN-22:00 32.57 13.55
July 0.470199E+11 23302.86 26-JUL-21:10 28.62 18.19 0.189956E+11 11356.74 25-JUL-22:00 28.62 18.19
August 0.460691E+11 23491.52 07-AUG-21:10 31.25 17.07 0.190214E+11 11353.41 04-AUG-22:00 31.25 17.07
September 0.428234E+11 22133.37 22-SEP-22:00 25.00 17.90 0.182290E+11 11346.57 19-SEP-04:10 25.00 17.90
October 0.410092E+11 23528.26 25-OCT-04:07 8.12 5.97 0.185055E+11 12670.91 25-OCT-03:20 8.12 5.97
November 0.356776E+11 31188.99 15-NOV-23:33 5.37 2.41 0.172196E+11 12351.78 18-NOV-05:40 6.47 0.95
December 0.342633E+11 31123.70 11-DEC-24:00 5.00 1.72 0.172280E+11 12647.32 23-DEC-00:20 5.20 0.42
                     
Annual Sum or Average 0.482984E+12         0.216050E+12        
Minimum of Months 0.327280E+11 22133.37   5.00 1.14 0.159706E+11 11346.54   5.00 0.34
Maximum of Months 0.470199E+11 32423.09   32.57 18.19 0.190214E+11 13238.58   32.57 18.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.372258E+11 33452.42 31-JAN-23:56 6.70 1.99 0.180142E+11 13226.15 20-JAN-00:10 6.70 1.99
February 0.347269E+11 34429.07 15-FEB-23:57 5.00 1.14 0.164684E+11 13388.85 15-FEB-23:19 5.00 1.14
March 0.400058E+11 41485.29 17-MAR-04:10 5.32 -0.8 0.185726E+11 12906.22 17-MAR-21:49 6.83 0.34
April 0.423169E+11 33198.84 10-APR-22:40 7.40 1.81 0.182811E+11 12889.98 11-APR-02:00 6.10 0.79
May 0.467318E+11 24215.24 31-MAY-21:10 28.13 13.59 0.190854E+11 11406.14 08-MAY-04:30 28.13 13.59
June 0.479740E+11 24968.40 15-JUN-21:20 31.83 13.36 0.186053E+11 11370.81 06-JUN-22:00 31.83 13.36
July 0.492678E+11 24677.13 26-JUL-21:10 28.62 18.19 0.191428E+11 11378.29 25-JUL-22:00 28.62 18.19
August 0.482531E+11 24855.02 07-AUG-21:10 31.25 17.07 0.191750E+11 11374.26 04-AUG-22:00 31.25 17.07
September 0.448183E+11 23407.56 22-SEP-22:00 25.00 17.90 0.184119E+11 11347.16 30-SEP-03:20 11.33 7.00
October 0.429280E+11 24427.14 25-OCT-05:30 6.95 5.28 0.187956E+11 12909.59 25-OCT-03:20 6.95 5.28
November 0.376204E+11 34719.95 19-NOV-23:56 4.40 -1.2 0.176930E+11 12612.72 18-NOV-05:40 4.40 -1.2
December 0.365667E+11 33070.92 11-DEC-24:00 5.00 1.72 0.178787E+11 13005.90 23-DEC-00:20 5.20 0.42
                     
Annual Sum or Average 0.508436E+12         0.220124E+12        
Minimum of Months 0.347269E+11 23407.56   4.40 -1.2 0.164684E+11 11347.16   4.40 -1.2
Maximum of Months 0.492678E+11 41485.29   31.83 18.19 0.191750E+11 13388.85   31.83 18.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.490744E+11 35265.66 07-JAN-09:28 3.90 -0.8 0.188818E+11 11362.98 21-JAN-18:49 8.68 4.78
February 0.454878E+11 36234.04 28-FEB-06:44 5.18 4.12 0.170507E+11 11319.47 04-FEB-18:19 5.18 4.12
March 0.516709E+11 34265.88 25-MAR-06:36 5.57 2.06 0.188793E+11 11319.53 18-MAR-17:19 5.57 2.06
April 0.531736E+11 33388.45 10-APR-22:40 7.40 1.81 0.182639E+11 11319.65 15-APR-17:19 27.43 11.91
May 0.571786E+11 30390.24 21-MAY-10:40 29.47 14.38 0.188718E+11 11319.65 27-MAY-17:19 30.40 15.99
June 0.573502E+11 30978.20 18-JUN-10:40 32.43 16.35 0.182662E+11 11319.65 24-JUN-17:19 31.67 16.29
July 0.591820E+11 31125.63 02-JUL-10:40 32.23 20.13 0.188684E+11 11319.71 29-JUL-17:19 34.23 18.70
August 0.585267E+11 31022.49 06-AUG-10:50 31.93 18.13 0.188757E+11 11319.67 05-AUG-17:19 31.93 18.13
September 0.556868E+11 30629.34 17-SEP-10:40 29.47 15.71 0.182617E+11 11319.65 30-SEP-17:19 26.47 12.09
October 0.544511E+11 30051.23 05-OCT-10:40 27.60 18.63 0.188691E+11 11319.59 21-OCT-17:19 24.83 12.12
November 0.491268E+11 34879.55 16-NOV-08:24 5.00 2.47 0.182649E+11 11327.17 25-NOV-18:10 8.12 3.81
December 0.485249E+11 38375.89 27-DEC-11:51 4.40 0.81 0.188804E+11 11396.31 02-DEC-18:10 4.40 0.81
                     
Annual Sum or Average 0.639434E+12         0.222234E+12        
Minimum of Months 0.454878E+11 30051.23   3.90 -0.8 0.170507E+11 11319.47   4.40 0.81
Maximum of Months 0.591820E+11 38375.89   32.43 20.13 0.188818E+11 11396.31   34.23 18.70



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.438829E+10 3775.47 02-JAN-00:33 4.83 3.01 0.135879E+10 896.05 12-JAN-22:19 9.47 5.03
February 0.439167E+10 3678.03 05-FEB-00:17 5.93 1.82 0.128843E+10 953.94 22-FEB-22:40 14.40 4.97
March 0.532221E+10 4215.58 17-MAR-03:44 5.87 -0.4 0.150333E+10 1002.92 16-MAR-21:30 5.87 -0.4
April 0.699864E+10 5114.38 30-APR-13:00 29.40 12.28 0.160687E+10 1007.39 19-APR-23:49 29.40 12.28
May 0.951049E+10 6045.78 30-MAY-15:02 34.32 17.72 0.170925E+10 1007.44 18-MAY-00:10 34.32 17.72
June 0.118375E+11 6869.13 15-JUN-18:03 35.92 14.47 0.166563E+10 1007.44 30-JUN-22:10 28.43 17.10
July 0.121482E+11 7016.23 03-JUL-14:30 37.50 18.90 0.171452E+10 1007.42 03-JUL-03:09 37.50 18.90
August 0.114172E+11 6858.41 07-AUG-15:03 35.37 18.63 0.172099E+10 1007.44 22-AUG-00:10 24.22 16.48
September 0.997601E+10 6544.93 20-SEP-15:03 33.30 17.34 0.165413E+10 1007.42 18-SEP-01:10 33.30 17.34
October 0.753392E+10 6189.78 03-OCT-13:30 31.70 19.34 0.166330E+10 1007.42 05-OCT-23:49 20.65 16.69
November 0.508511E+10 3930.51 26-NOV-00:14 4.80 2.00 0.143950E+10 1007.37 09-NOV-22:10 4.80 2.00
December 0.383828E+10 3536.94 30-DEC-10:29 4.15 0.79 0.132690E+10 858.66 15-DEC-22:49 4.15 0.79
                     
Annual Sum or Average 0.924476E+11         0.186516E+11        
Minimum of Months 0.383828E+10 3536.94   4.15 -0.4 0.128843E+10 858.66   4.15 -0.4
Maximum of Months 0.121482E+11 7016.23   37.50 19.34 0.172099E+10 1007.44   37.50 18.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 2060308.32 2998.76 18-JAN-04:26 5.85
February 3987517.71 3748.63 15-FEB-23:10 5.00
March 6344861.36 2710.45 06-MAR-00:28 5.55
April 7061840.32 3200.29 11-APR-02:36 6.10
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 62900.85 209.67 25-OCT-03:10 7.38
November 3130184.20 3243.96 20-NOV-04:17 5.77
December 1552594.46 1790.75 09-DEC-04:10 5.47
         
Annual Sum or Average 24200207.21      
Minimum of Months 0.00 0.00   5.00
Maximum of Months 7061840.32 3748.63   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 8825487.07 488.61 18-JAN-04:26 5.85
February 4110495.94 432.30 17-FEB-00:59 5.00
March 3379319.12 352.28 06-MAR-06:03 5.68
April 1653208.92 421.89 11-APR-02:36 6.10
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 110711.73 227.01 25-OCT-03:10 7.38
November 7602774.53 441.37 22-NOV-05:53 6.10
December 36320109.70 810.00 27-DEC-07:15 -4.2
         
Annual Sum or Average 62002107.00      
Minimum of Months 0.00 0.00   -4.2
Maximum of Months 36320109.70 810.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1799663.83 372.29 18-JAN-04:26 5.85
February 893126.28 268.19 17-FEB-00:13 5.73
March 371997.77 186.44 06-MAR-06:03 5.68
April 438784.22 260.11 11-APR-02:36 6.10
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 25309.00 84.36 25-OCT-03:10 7.38
November 1516770.79 297.64 22-NOV-05:53 6.10
December 2185043.36 373.84 31-DEC-09:57 4.40
         
Annual Sum or Average 7230695.26      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 2185043.36 373.84   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 3512093.18 312.50 18-JAN-04:26 5.85
February 1845480.84 281.57 17-FEB-00:13 5.73
March 680451.18 217.67 06-MAR-06:03 5.68
April 439360.06 214.35 13-APR-05:15 4.63
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 35965.22 119.88 25-OCT-03:10 7.38
November 1971706.14 307.54 22-NOV-05:53 6.10
December 3734694.99 357.78 31-DEC-09:57 4.40
         
Annual Sum or Average 12219751.61      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 3734694.99 357.78   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 6988276.74 356.07 18-JAN-04:26 5.85
February 3859588.20 367.59 17-FEB-00:13 5.73
March 1684443.53 306.00 06-MAR-00:28 5.55
April 1128168.25 304.43 13-APR-05:15 4.63
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 100440.87 210.01 25-OCT-03:10 7.38
November 4765404.55 382.29 22-NOV-05:53 6.10
December 6676042.73 379.53 23-DEC-00:10 5.10
         
Annual Sum or Average 25202364.88      
Minimum of Months 0.00 0.00   4.63
Maximum of Months 6988276.74 382.29   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 114515.97 1908.60 18-JAN-04:26 5.85
February 0.00 0.00 01-FEB-00:05 6.42
March 13814.81 187.73 17-MAR-03:47 5.87
April 392465.00 2811.79 11-APR-02:36 6.10
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 139226.45 2176.60 20-NOV-04:17 5.77
December 161348.29 1394.48 09-DEC-04:03 5.47
         
Annual Sum or Average 821370.52      
Minimum of Months 0.00 0.00   5.47
Maximum of Months 392465.00 2811.79   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 16712797.73 3134.44 01-JAN-08:10 5.47
February 6829575.62 1715.12 24-FEB-05:02 5.40
March 4976745.09 2211.48 25-MAR-06:38 5.57
April 4999069.53 2210.59 11-APR-02:36 6.10
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 175027.76 763.85 25-OCT-06:08 6.88
November 16515119.38 2502.86 11-NOV-05:19 5.77
December 12020585.95 3554.50 03-DEC-11:58 5.60
         
Annual Sum or Average 62228921.06      
Minimum of Months 0.00 0.00   5.40
Maximum of Months 16712797.73 3554.50   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 11224876.86 4987.51 18-JAN-04:26 5.85
February 8958888.95 6715.41 17-FEB-00:13 5.73
March 3940157.94 3096.61 06-MAR-06:03 5.68
April 7740119.28 7256.35 11-APR-02:36 6.10
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 44897.83 149.66 25-OCT-03:10 7.38
November 21027964.71 7530.17 22-NOV-05:53 6.10
December 17573720.67 6101.22 23-DEC-00:10 5.10
         
Annual Sum or Average 70510626.24      
Minimum of Months 0.00 0.00   5.10
Maximum of Months 21027964.71 7530.17   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.316451E+09 2279.20 27-JAN-09:01 -1.2
February 0.184498E+09 2262.42 02-FEB-09:01 1.38
March 87780978.48 2273.09 02-MAR-09:01 0.47
April 6053114.48 1399.94 11-APR-08:62 6.88
May 914062.70 783.24 28-MAY-08:04 22.38
June 787302.90 627.00 25-JUN-08:04 22.67
July 846189.61 716.37 21-JUL-08:04 22.30
August 912640.35 761.47 19-AUG-08:04 23.07
September 867549.74 717.06 16-SEP-08:04 22.07
October 1498505.28 754.12 15-OCT-08:03 13.90
November 0.135306E+09 2282.31 26-NOV-19:01 4.90
December 0.445368E+09 2303.41 27-DEC-09:01 -0.7
         
Annual Sum or Average 0.118128E+10      
Minimum of Months 787302.90 627.00   -1.2
Maximum of Months 0.445368E+09 2303.41   23.07



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.561291E+09 2319.33 27-JAN-09:01 -1.2
February 0.328607E+09 2302.62 02-FEB-09:01 1.38
March 0.144433E+09 2291.59 02-MAR-09:01 0.47
April 9037200.41 1636.67 11-APR-08:62 6.88
May 882940.44 754.13 06-MAY-08:03 17.48
June 683927.99 582.98 30-JUN-08:04 22.38
July 776675.99 827.94 21-JUL-08:04 22.30
August 1005330.24 765.30 12-AUG-08:04 22.57
September 1091808.46 799.32 30-SEP-08:03 17.67
October 2048949.26 725.59 28-OCT-08:03 13.68
November 0.236835E+09 2299.99 26-NOV-19:01 4.90
December 0.752550E+09 2321.22 07-DEC-09:01 4.37
         
Annual Sum or Average 0.203924E+10      
Minimum of Months 683927.99 582.98   -1.2
Maximum of Months 0.752550E+09 2321.22   22.57



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:05 6.42
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:05 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 48628381.09 694.03 27-JAN-09:01 -1.2
February 28950018.79 688.04 03-FEB-09:01 2.95
March 7589737.08 682.41 02-MAR-09:01 0.47
April 1334981.20 368.84 10-APR-15:04 17.67
May 390882.83 379.42 07-MAY-15:04 28.07
June 77896.62 176.37 03-JUN-18:06 26.42
July 104648.01 284.07 05-JUL-08:05 22.57
August 214693.64 346.13 24-AUG-08:04 21.60
September 399366.68 337.22 21-SEP-08:04 23.17
October 912092.28 336.27 31-OCT-08:03 15.37
November 14910627.53 674.78 26-NOV-19:01 4.90
December 85192449.16 692.13 27-DEC-09:01 -0.7
         
Annual Sum or Average 0.188706E+09      
Minimum of Months 77896.62 176.37   -1.2
Maximum of Months 85192449.16 694.03   28.07



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.336682E+09 2177.36 15-JAN-09:01 7.88
February 0.174471E+09 2092.70 13-FEB-16:01 12.30
March 91099443.21 2179.23 02-MAR-09:01 0.47
April 5202265.73 668.01 06-APR-15:04 16.10
May 278920.92 518.46 02-MAY-18:04 24.90
June 4512.86 45.13 29-JUN-18:05 27.70
July 17130.85 98.00 07-JUL-08:04 23.80
August 208006.49 646.57 17-AUG-18:04 25.50
September 62462.50 515.73 24-SEP-18:04 20.73
October 1728107.26 677.88 07-OCT-15:04 17.88
November 0.149043E+09 2213.49 26-NOV-19:01 4.90
December 0.453478E+09 2221.32 26-DEC-09:01 -0.5
         
Annual Sum or Average 0.121227E+10      
Minimum of Months 4512.86 45.13   -0.5
Maximum of Months 0.453478E+09 2221.32   27.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.573724E+09 2181.16 26-JAN-19:01 3.22
February 0.292965E+09 2160.58 02-FEB-19:01 7.43
March 0.143345E+09 2196.94 02-MAR-09:01 0.47
April 8044891.70 800.59 06-APR-15:04 16.10
May 351153.68 659.51 02-MAY-18:04 24.90
June 0.00 0.00 01-JUN-00:10 25.03
July 8007.20 43.40 07-JUL-18:05 27.02
August 262370.14 765.80 17-AUG-18:04 25.50
September 150950.52 443.51 30-SEP-18:04 24.45
October 3844144.31 771.92 24-OCT-15:03 17.88
November 0.245144E+09 2230.14 26-NOV-19:01 4.90
December 0.741727E+09 2229.36 26-DEC-09:01 -0.5
         
Annual Sum or Average 0.200957E+10      
Minimum of Months 0.00 0.00   -0.5
Maximum of Months 0.741727E+09 2230.14   27.02



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 9245497.43 678.77 18-JAN-04:26 5.85
February 4271350.50 597.13 17-FEB-00:13 5.73
March 1658835.15 468.55 05-MAR-04:23 5.85
April 929890.34 436.61 13-APR-05:15 4.63
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 62142.94 207.14 25-OCT-03:10 7.38
November 4079287.02 569.01 22-NOV-05:53 6.10
December 9013020.89 684.64 31-DEC-09:57 4.40
         
Annual Sum or Average 29260024.28      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 9245497.43 684.64   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.643194E+09 2737.45 27-JAN-09:01 -1.2
February 0.419165E+09 2722.94 02-FEB-09:01 1.38
March 0.251064E+09 2724.50 02-MAR-09:01 0.47
April 34056243.84 2567.67 11-APR-08:62 6.88
May 1237534.29 717.32 10-MAY-08:03 20.78
June 763393.23 639.82 04-JUN-08:04 24.27
July 1058412.02 801.89 18-JUL-08:04 24.08
August 1164429.76 763.64 23-AUG-08:04 24.27
September 915664.59 631.86 03-SEP-08:04 22.57
October 12554276.26 861.58 06-OCT-08:03 12.30
November 0.333620E+09 2768.66 26-NOV-19:01 4.90
December 0.824187E+09 2744.73 27-DEC-09:01 -0.7
         
Annual Sum or Average 0.252298E+10      
Minimum of Months 763393.23 631.86   -1.2
Maximum of Months 0.824187E+09 2768.66   24.27



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.100145E+10 2765.79 27-JAN-09:01 -1.2
February 0.649407E+09 2745.34 02-FEB-09:01 1.38
March 0.358874E+09 2730.31 02-MAR-09:01 0.47
April 43097008.51 2570.17 11-APR-08:62 6.88
May 1185177.15 766.54 27-MAY-08:04 21.38
June 745507.75 628.65 04-JUN-08:04 24.27
July 1005005.97 756.13 18-JUL-08:04 24.08
August 1245263.39 697.95 23-AUG-08:04 24.27
September 1222692.76 720.18 23-SEP-08:04 23.58
October 29456324.41 2323.83 25-OCT-08:62 11.15
November 0.544011E+09 2747.07 26-NOV-19:01 4.90
December 0.124417E+10 2776.84 07-DEC-09:01 4.37
         
Annual Sum or Average 0.387587E+10      
Minimum of Months 745507.75 628.65   -1.2
Maximum of Months 0.124417E+10 2776.84   24.27



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 96565000.83 1382.58 15-JAN-09:01 7.88
February 60955697.53 1192.72 13-FEB-16:01 12.30
March 42403092.35 1403.69 02-MAR-09:01 0.47
April 6300510.30 884.47 11-APR-08:62 6.88
May 943177.94 442.77 05-MAY-18:04 24.82
June 757594.58 473.18 19-JUN-08:04 25.37
July 634988.38 469.59 10-JUL-08:04 26.88
August 637292.59 470.86 11-AUG-08:04 25.87
September 314373.30 381.16 19-SEP-08:04 24.27
October 416245.81 431.04 14-OCT-15:04 19.60
November 53656616.24 1401.36 26-NOV-19:01 4.90
December 0.142039E+09 1416.71 26-DEC-09:01 -0.5
         
Annual Sum or Average 0.405623E+09      
Minimum of Months 314373.30 381.16   -0.5
Maximum of Months 0.142039E+09 1416.71   26.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 8835194.97 3466.88 01-JAN-08:10 5.47
February 3918344.71 3266.19 03-FEB-10:19 7.23
March 659761.53 2055.81 06-MAR-00:28 5.55
April 933356.79 3117.85 11-APR-02:36 6.10
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 9597052.11 3375.78 11-NOV-05:19 5.77
December 14566188.92 4061.95 19-DEC-10:59 4.40
         
Annual Sum or Average 38509899.04      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 14566188.92 4061.95   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 3341787.01 2663.83 01-JAN-08:10 5.47
February 1591380.09 2363.84 03-FEB-10:19 7.23
March 179443.03 761.27 06-MAR-00:28 5.55
April 562484.35 2981.50 11-APR-02:36 6.10
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 5403682.48 2975.38 11-NOV-05:19 5.77
December 6673832.70 3193.39 19-DEC-10:59 4.40
         
Annual Sum or Average 17752609.66      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 6673832.70 3193.39   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 11852.16 166.62 18-JAN-04:26 5.85
February 0.00 0.00 01-FEB-00:05 6.42
March 36331.26 605.52 06-MAR-00:28 5.55
April 31447.11 401.35 11-APR-02:36 6.10
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 35173.35 273.58 11-NOV-05:19 5.77
December 0.00 0.00 01-DEC-00:05 8.95
         
Annual Sum or Average 114803.88      
Minimum of Months 0.00 0.00   5.55
Maximum of Months 36331.26 605.52   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 22960816.05 1087.39 18-JAN-04:26 5.85
February 13507401.35 970.50 17-FEB-00:59 5.00
March 3129498.01 771.26 06-MAR-06:03 5.68
April 1905533.49 755.23 13-APR-05:15 4.63
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 138890.90 413.72 25-OCT-03:10 7.38
November 9298567.89 1004.38 22-NOV-05:53 6.10
December 60635235.48 1319.63 27-DEC-07:30 -4.2
         
Annual Sum or Average 0.111576E+09      
Minimum of Months 0.00 0.00   -4.2
Maximum of Months 60635235.48 1319.63   27.63



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.147273E+11 14185.34 02-JAN-20:10 0.127587E+11 10113.80 02-JAN-20:10
February 0.132974E+11 14185.34 01-FEB-20:10 0.115208E+11 10113.80 01-FEB-20:10
March 0.147727E+11 14185.34 01-MAR-20:10 0.127855E+11 10113.80 01-MAR-20:10
April 0.142280E+11 14185.34 03-APR-19:10 0.123314E+11 10113.80 03-APR-19:10
May 0.147528E+11 14185.34 01-MAY-19:10 0.127741E+11 10113.80 01-MAY-19:10
June 0.142932E+11 14185.34 01-JUN-19:10 0.123716E+11 10113.80 01-JUN-19:10
July 0.146876E+11 14185.34 03-JUL-19:10 0.127338E+11 10113.80 03-JUL-19:10
August 0.147784E+11 14185.34 01-AUG-19:10 0.127894E+11 10113.80 01-AUG-19:10
September 0.142337E+11 14185.34 01-SEP-19:10 0.123352E+11 10113.80 01-SEP-19:10
October 0.147216E+11 14185.34 02-OCT-19:10 0.127549E+11 10113.80 02-OCT-19:10
November 0.142819E+11 14185.34 01-NOV-19:10 0.123659E+11 10113.80 01-NOV-19:10
December 0.146876E+11 14185.34 01-DEC-20:10 0.127338E+11 10113.80 01-DEC-20:10
             
Annual Sum or Average 0.173462E+12     0.150255E+12    
Minimum of Months 0.132974E+11 14185.34   0.115208E+11 10113.80  
Maximum of Months 0.147784E+11 14185.34   0.127894E+11 10113.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.731324E+09 704.41 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.660319E+09 704.41 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.733578E+09 704.41 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.706528E+09 704.41 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.732592E+09 704.41 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.709769E+09 704.41 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.729351E+09 704.41 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.733860E+09 704.41 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.706810E+09 704.41 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.731042E+09 704.41 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.709205E+09 704.41 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.729351E+09 704.41 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.861373E+10     0.101856E+11    
Minimum of Months 0.660319E+09 704.41   0.780982E+09 685.60  
Maximum of Months 0.733860E+09 704.41   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.846876E+09 815.72 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.764651E+09 815.72 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.849486E+09 815.72 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.818162E+09 815.72 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.848344E+09 815.72 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.821915E+09 815.72 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.844592E+09 815.72 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.849812E+09 815.72 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.818489E+09 815.72 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.846549E+09 815.72 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.821262E+09 815.72 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.844592E+09 815.72 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.997473E+10     0.117950E+11    
Minimum of Months 0.764651E+09 815.72   0.904380E+09 793.93  
Maximum of Months 0.849812E+09 815.72   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.141236E+10 1360.40 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.127524E+10 1360.40 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.141672E+10 1360.40 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.136448E+10 1360.40 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.141481E+10 1360.40 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.137074E+10 1360.40 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.140855E+10 1360.40 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.141726E+10 1360.40 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.136502E+10 1360.40 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.141182E+10 1360.40 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.136965E+10 1360.40 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.140855E+10 1360.40 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.166352E+11     0.124712E+11    
Minimum of Months 0.127524E+10 1360.40   0.956227E+09 839.45  
Maximum of Months 0.141726E+10 1360.40   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.236418E+09 227.72 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.213464E+09 227.72 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.237147E+09 227.72 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.228402E+09 227.72 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.236828E+09 227.72 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.229450E+09 227.72 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.235780E+09 227.72 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.237238E+09 227.72 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.228493E+09 227.72 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.236327E+09 227.72 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.229268E+09 227.72 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.235780E+09 227.72 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.278459E+10     0.359760E+10    
Minimum of Months 0.213464E+09 227.72   0.275845E+09 242.16  
Maximum of Months 0.237238E+09 227.72   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.370859E+09 357.21 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.334852E+09 357.21 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.372002E+09 357.21 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.358285E+09 357.21 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.371502E+09 357.21 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.359929E+09 357.21 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.369859E+09 357.21 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.372145E+09 357.21 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.358428E+09 357.21 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.370717E+09 357.21 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.359643E+09 357.21 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.369859E+09 357.21 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.436808E+10     0.679355E+11    
Minimum of Months 0.334852E+09 357.21   0.520895E+10 4572.80  
Maximum of Months 0.372145E+09 357.21   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.159856E+10 1761.91 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.141918E+10 1761.91 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.154488E+10 1761.91 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.145180E+10 1761.91 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.148666E+10 1761.91 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.141991E+10 1761.91 01-JUN-19:10 0.118076E+10 965.27 01-JUN-19:10
July 0.145980E+10 1761.91 03-JUL-19:10 0.121533E+10 965.27 03-JUL-19:10
August 0.150656E+10 1761.91 01-AUG-19:10 0.122063E+10 965.27 01-AUG-19:10
September 0.147181E+10 1761.91 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.157293E+10 1761.91 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.152628E+10 1761.91 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.159121E+10 1761.91 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.180496E+11     0.143405E+11    
Minimum of Months 0.141918E+10 1761.91   0.109956E+10 965.27  
Maximum of Months 0.159856E+10 1761.91   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104201E+11 10265.18 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.938499E+10 10265.18 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.104002E+11 10265.18 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.997990E+10 10265.18 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.103301E+11 10265.18 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.999248E+10 10265.18 01-JUN-19:10 0.122682E+11 10029.21 01-JUN-19:10
July 0.102711E+11 10265.18 03-JUL-19:10 0.126273E+11 10029.21 03-JUL-19:10
August 0.103657E+11 10265.18 01-AUG-19:10 0.126824E+11 10029.21 01-AUG-19:10
September 0.100075E+11 10265.18 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.103913E+11 10265.18 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.100809E+11 10265.18 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.103887E+11 10265.18 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.122013E+12     0.148998E+12    
Minimum of Months 0.938499E+10 10265.18   0.114244E+11 10029.21  
Maximum of Months 0.104201E+11 10265.18   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85091918.49 76.99 01-JAN-19:10 0.255708E+09 232.19 01-JAN-08:09
February 76846309.13 76.99 01-FEB-20:10 0.230956E+09 232.19 01-FEB-07:10
March 84415649.14 76.99 01-MAR-20:10 0.255355E+09 232.19 01-MAR-07:10
April 82445007.08 76.99 01-APR-18:10 0.247516E+09 232.19 01-APR-07:10
May 84753783.81 76.99 01-MAY-19:10 0.255532E+09 232.19 01-MAY-06:10
June 81790910.76 76.99 01-JUN-19:10 0.247163E+09 232.19 01-JUN-06:10
July 85418966.65 76.99 01-JUL-18:10 0.255885E+09 232.19 01-JUL-07:10
August 84415649.14 76.99 01-AUG-19:10 0.255355E+09 232.19 01-AUG-06:10
September 82467180.11 76.99 01-SEP-19:10 0.247516E+09 232.19 01-SEP-06:10
October 85080831.98 76.99 01-OCT-18:10 0.255708E+09 232.19 01-OCT-07:10
November 82117958.92 76.99 01-NOV-19:10 0.247340E+09 232.19 01-NOV-06:10
December 85430053.17 76.99 01-DEC-20:10 0.255885E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.100027E+10     0.300992E+10    
Minimum of Months 76846309.13 76.99   0.230956E+09 232.19  
Maximum of Months 85430053.17 76.99   0.255885E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85115186.72 77.01 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 76867322.62 77.01 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 84438732.44 77.01 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 82467551.52 77.01 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 84776959.58 77.01 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 81813276.33 77.01 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 85442324.32 77.01 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 84438732.44 77.01 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 82489730.61 77.01 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 85104097.18 77.01 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 82140413.93 77.01 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 85453413.86 77.01 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.100055E+10     0.301074E+10    
Minimum of Months 76867322.62 77.01   0.231020E+09 232.26  
Maximum of Months 85453413.86 77.01   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.232638E+10 2240.78 02-JAN-20:10 0.00 0.00
February 0.210051E+10 2240.78 01-FEB-20:10 0.00 0.00
March 0.233355E+10 2240.78 01-MAR-20:10 0.00 0.00
April 0.224750E+10 2240.78 03-APR-19:10 0.00 0.00
May 0.233041E+10 2240.78 01-MAY-19:10 0.00 0.00
June 0.225781E+10 2240.78 01-JUN-19:10 0.00 0.00
July 0.232011E+10 2240.78 03-JUL-19:10 0.00 0.00
August 0.233445E+10 2240.78 01-AUG-19:10 0.00 0.00
September 0.224840E+10 2240.78 01-SEP-19:10 0.00 0.00
October 0.232548E+10 2240.78 02-OCT-19:10 0.00 0.00
November 0.225602E+10 2240.78 01-NOV-19:10 0.00 0.00
December 0.232011E+10 2240.78 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.274007E+11     0.00 0.00
Minimum of Months 0.210051E+10 2240.78   0.00 0.00
Maximum of Months 0.233445E+10 2240.78   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85115186.72 77.01 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 76867322.62 77.01 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 84438732.44 77.01 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 82467551.52 77.01 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 84776959.58 77.01 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 81813276.33 77.01 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 85442324.32 77.01 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 84438732.44 77.01 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 82489730.61 77.01 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 85104097.18 77.01 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 82140413.93 77.01 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 85453413.86 77.01 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.100055E+10     0.301074E+10    
Minimum of Months 76867322.62 77.01   0.231020E+09 232.26  
Maximum of Months 85453413.86 77.01   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.303266E+10 3094.06 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.271117E+10 3094.06 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.297615E+10 3094.06 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.281606E+10 3094.06 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.289246E+10 3094.06 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.278243E+10 3094.06 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.285773E+10 3094.06 03-JUL-19:19 0.149358E+11 6747.90 01-JUL-06:10
August 0.292096E+10 3094.06 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.284760E+10 3094.06 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.299951E+10 3094.06 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.291802E+10 3094.06 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.301853E+10 3094.06 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.347733E+11     0.175857E+12    
Minimum of Months 0.271117E+10 3094.06   0.134904E+11 6747.90  
Maximum of Months 0.303266E+10 3094.06   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.303266E+10 3094.06 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.271117E+10 3094.06 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.297615E+10 3094.06 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.281606E+10 3094.06 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.289246E+10 3094.06 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.278243E+10 3094.06 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.285773E+10 3094.06 03-JUL-19:19 0.149358E+11 6747.90 01-JUL-06:10
August 0.292096E+10 3094.06 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.284760E+10 3094.06 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.299951E+10 3094.06 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.291802E+10 3094.06 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.301853E+10 3094.06 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.347733E+11     0.175857E+12    
Minimum of Months 0.271117E+10 3094.06   0.134904E+11 6747.90  
Maximum of Months 0.303266E+10 3094.06   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.113146E+10 1089.83 02-JAN-20:10 0.368383E+11 16487.34 01-JAN-07:10
February 0.102161E+10 1089.83 01-FEB-20:10 0.332733E+11 16487.34 01-FEB-07:10
March 0.113495E+10 1089.83 01-MAR-20:10 0.368383E+11 16487.34 01-MAR-07:10
April 0.109310E+10 1089.83 03-APR-19:10 0.356500E+11 16487.34 01-APR-06:10
May 0.113342E+10 1089.83 01-MAY-19:10 0.368383E+11 16487.34 01-MAY-06:10
June 0.109811E+10 1089.83 01-JUN-19:10 0.356500E+11 16487.34 01-JUN-06:10
July 0.112841E+10 1089.83 03-JUL-19:10 0.368383E+11 16487.34 01-JUL-06:10
August 0.113539E+10 1089.83 01-AUG-19:10 0.368383E+11 16487.34 01-AUG-06:10
September 0.109354E+10 1089.83 01-SEP-19:10 0.356500E+11 16487.34 01-SEP-06:10
October 0.113103E+10 1089.83 02-OCT-19:10 0.368383E+11 16487.34 01-OCT-06:10
November 0.109724E+10 1089.83 01-NOV-19:10 0.356500E+11 16487.34 01-NOV-06:10
December 0.112841E+10 1089.83 01-DEC-20:10 0.368383E+11 16487.34 01-DEC-07:10
             
Annual Sum or Average 0.133267E+11     0.433742E+12    
Minimum of Months 0.102161E+10 1089.83   0.332733E+11 16487.34  
Maximum of Months 0.113539E+10 1089.83   0.368383E+11 16487.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.246211E+10 2371.52 02-JAN-20:10 0.00 0.00
February 0.222306E+10 2371.52 01-FEB-20:10 0.00 0.00
March 0.246970E+10 2371.52 01-MAR-20:10 0.00 0.00
April 0.237864E+10 2371.52 03-APR-19:10 0.00 0.00
May 0.246638E+10 2371.52 01-MAY-19:10 0.00 0.00
June 0.238954E+10 2371.52 01-JUN-19:10 0.00 0.00
July 0.245547E+10 2371.52 03-JUL-19:10 0.00 0.00
August 0.247065E+10 2371.52 01-AUG-19:10 0.00 0.00
September 0.237958E+10 2371.52 01-SEP-19:10 0.00 0.00
October 0.246116E+10 2371.52 02-OCT-19:10 0.00 0.00
November 0.238765E+10 2371.52 01-NOV-19:10 0.00 0.00
December 0.245547E+10 2371.52 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.289994E+11     0.00 0.00
Minimum of Months 0.222306E+10 2371.52   0.00 0.00
Maximum of Months 0.247065E+10 2371.52   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.147273E+11 0.127587E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.132974E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.147727E+11 0.127855E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.142280E+11 0.123314E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.147528E+11 0.127741E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.142932E+11 0.123716E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.146876E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.147784E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.142337E+11 0.123352E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.147216E+11 0.127549E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.142819E+11 0.123659E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.146876E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.173462E+12 0.150255E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.132974E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.147784E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.731324E+09 0.864900E+09 0.00 0.00 0.00 0.00 0.00 0.413107E+09
February 0.179968E+10 0.660319E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.322276E+09
March 0.199990E+10 0.733578E+09 0.866718E+09 0.00 0.00 0.00 0.00 140916.59 0.293830E+09
April 0.192973E+10 0.706528E+09 0.835931E+09 0.00 0.00 0.00 0.00 20331454.48 0.138193E+09
May 0.199475E+10 0.732592E+09 0.865939E+09 0.00 0.00 0.00 0.00 57274323.70 59673125.96
June 0.193394E+10 0.709769E+09 0.838659E+09 0.00 0.00 0.00 0.00 0.117317E+09 18763955.81
July 0.199054E+10 0.729351E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.107475E+09 12996583.65
August 0.199896E+10 0.733860E+09 0.866978E+09 0.00 0.00 0.00 0.00 87174309.25 26294858.79
September 0.192879E+10 0.706810E+09 0.836191E+09 0.00 0.00 0.00 0.00 48616705.15 65589870.45
October 0.199148E+10 0.731042E+09 0.864640E+09 0.00 0.00 0.00 0.00 11492151.38 0.162446E+09
November 0.192552E+10 0.709205E+09 0.838269E+09 0.00 0.00 0.00 0.00 0.00 0.327245E+09
December 0.199054E+10 0.729351E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.00 0.451046E+09
                   
Annual Sum or Average 0.234744E+11 0.861373E+10 0.101856E+11 0.00 0.00 0.00 0.00 0.449822E+09 0.229146E+10
Minimum of Months 0.179968E+10 0.660319E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 12996583.65
Maximum of Months 0.199990E+10 0.733860E+09 0.866978E+09 0.00 0.00 0.00 0.00 0.117317E+09 0.451046E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.846876E+09 0.100156E+10 0.00 0.00 0.00 0.00 0.00 0.162860E+09
February 0.208403E+10 0.764651E+09 0.904380E+09 0.00 0.00 0.00 0.00 3335.31 0.127054E+09
March 0.231589E+10 0.849486E+09 0.100366E+10 0.00 0.00 0.00 0.00 267298.58 0.116465E+09
April 0.223463E+10 0.818162E+09 0.968011E+09 0.00 0.00 0.00 0.00 9338769.25 55249210.69
May 0.230993E+10 0.848344E+09 0.100276E+10 0.00 0.00 0.00 0.00 23767926.13 23895136.95
June 0.223950E+10 0.821915E+09 0.971170E+09 0.00 0.00 0.00 0.00 46389835.01 7322505.68
July 0.230505E+10 0.844592E+09 0.999601E+09 0.00 0.00 0.00 0.00 42613491.57 5054536.78
August 0.231480E+10 0.849812E+09 0.100396E+10 0.00 0.00 0.00 0.00 34720058.91 10208313.68
September 0.223354E+10 0.818489E+09 0.968312E+09 0.00 0.00 0.00 0.00 19771253.52 25742680.39
October 0.230614E+10 0.846549E+09 0.100126E+10 0.00 0.00 0.00 0.00 5006002.83 63647039.67
November 0.222975E+10 0.821262E+09 0.970719E+09 0.00 0.00 0.00 0.00 11819.80 0.129083E+09
December 0.230505E+10 0.844592E+09 0.999601E+09 0.00 0.00 0.00 0.00 0.00 0.177483E+09
                   
Annual Sum or Average 0.271834E+11 0.997473E+10 0.117950E+11 0.00 0.00 0.00 0.00 0.181890E+09 0.904064E+09
Minimum of Months 0.208403E+10 0.764651E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 5054536.78
Maximum of Months 0.231589E+10 0.849812E+09 0.100396E+10 0.00 0.00 0.00 0.00 46389835.01 0.177483E+09



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.141236E+10 0.105898E+10 0.00 0.00 0.00 0.00 0.00 0.365681E+09
February 0.440737E+09 0.127524E+10 0.956227E+09 0.00 0.00 0.00 0.00 113237.44 0.285706E+09
March 0.489771E+09 0.141672E+10 0.106120E+10 0.00 0.00 0.00 0.00 1067676.98 0.264640E+09
April 0.472586E+09 0.136448E+10 0.102351E+10 0.00 0.00 0.00 0.00 21362717.60 0.129811E+09
May 0.488511E+09 0.141481E+10 0.106025E+10 0.00 0.00 0.00 0.00 52823875.73 57427323.42
June 0.473617E+09 0.137074E+10 0.102685E+10 0.00 0.00 0.00 0.00 0.107041E+09 17521873.08
July 0.487480E+09 0.140855E+10 0.105691E+10 0.00 0.00 0.00 0.00 98041141.20 12119193.92
August 0.489542E+09 0.141726E+10 0.106152E+10 0.00 0.00 0.00 0.00 79606486.80 24799977.47
September 0.472357E+09 0.136502E+10 0.102382E+10 0.00 0.00 0.00 0.00 44654699.51 61299204.45
October 0.487709E+09 0.141182E+10 0.105866E+10 0.00 0.00 0.00 0.00 11468264.68 0.149809E+09
November 0.471555E+09 0.136965E+10 0.102637E+10 0.00 0.00 0.00 0.00 83225.43 0.293039E+09
December 0.487480E+09 0.140855E+10 0.105691E+10 0.00 0.00 0.00 0.00 0.00 0.399054E+09
                   
Annual Sum or Average 0.574883E+10 0.166352E+11 0.124712E+11 0.00 0.00 0.00 0.00 0.416262E+09 0.206091E+10
Minimum of Months 0.440737E+09 0.127524E+10 0.956227E+09 0.00 0.00 0.00 0.00 0.00 12119193.92
Maximum of Months 0.489771E+09 0.141726E+10 0.106152E+10 0.00 0.00 0.00 0.00 0.107041E+09 0.399054E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.236418E+09 0.305485E+09 0.00 0.00 0.00 0.00 0.00 0.197775E+09
February 0.339028E+09 0.213464E+09 0.275845E+09 0.00 0.00 0.00 0.00 352435.59 0.151368E+09
March 0.376747E+09 0.237147E+09 0.306128E+09 0.00 0.00 0.00 0.00 1510122.76 0.136231E+09
April 0.363528E+09 0.228402E+09 0.295253E+09 0.00 0.00 0.00 0.00 17407151.97 62324908.86
May 0.375778E+09 0.236828E+09 0.305852E+09 0.00 0.00 0.00 0.00 37653964.12 26305425.22
June 0.364321E+09 0.229450E+09 0.296217E+09 0.00 0.00 0.00 0.00 66754167.35 7898958.74
July 0.374985E+09 0.235780E+09 0.304889E+09 0.00 0.00 0.00 0.00 62134412.17 4951371.67
August 0.376571E+09 0.237238E+09 0.306219E+09 0.00 0.00 0.00 0.00 51874415.90 10441618.98
September 0.363352E+09 0.228493E+09 0.295345E+09 0.00 0.00 0.00 0.00 31890240.35 28642312.33
October 0.375161E+09 0.236327E+09 0.305393E+09 0.00 0.00 0.00 0.00 9852287.49 72017157.87
November 0.362735E+09 0.229268E+09 0.296079E+09 0.00 0.00 0.00 0.00 273209.00 0.152844E+09
December 0.374985E+09 0.235780E+09 0.304889E+09 0.00 0.00 0.00 0.00 0.00 0.219549E+09
                   
Annual Sum or Average 0.442217E+10 0.278459E+10 0.359760E+10 0.00 0.00 0.00 0.00 0.279702E+09 0.107035E+10
Minimum of Months 0.339028E+09 0.213464E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 4951371.67
Maximum of Months 0.376747E+09 0.237238E+09 0.306219E+09 0.00 0.00 0.00 0.00 66754167.35 0.219549E+09



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.370859E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 0.00 0.573232E+09
February 0.139600E+10 0.334852E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.446201E+09
March 0.155131E+10 0.372002E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 175438.40 0.408854E+09
April 0.149688E+10 0.358285E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 25305596.47 0.189101E+09
May 0.154732E+10 0.371502E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 71298046.97 79735581.20
June 0.150015E+10 0.359929E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 0.146112E+09 23949821.77
July 0.154405E+10 0.369859E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.133849E+09 16546943.85
August 0.155059E+10 0.372145E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.108567E+09 34091275.15
September 0.149615E+10 0.358428E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 60540056.32 84117966.19
October 0.154478E+10 0.370717E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 14312753.02 0.215493E+09
November 0.149361E+10 0.359643E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 0.00 0.446086E+09
December 0.154405E+10 0.369859E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.00 0.626609E+09
                   
Annual Sum or Average 0.182090E+11 0.436808E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 0.560160E+09 0.314402E+10
Minimum of Months 0.139600E+10 0.334852E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 16546943.85
Maximum of Months 0.155131E+10 0.372145E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.146112E+09 0.626609E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.159856E+10 0.121771E+10 0.00 0.00 0.00 0.00 0.00 0.917338E+09
February 0.236489E+11 0.141918E+10 0.109956E+10 0.00 0.00 0.00 0.00 899.43 0.709604E+09
March 0.262800E+11 0.154488E+10 0.122027E+10 0.00 0.00 0.00 0.00 1210811.81 0.632288E+09
April 0.253579E+11 0.145180E+10 0.117692E+10 0.00 0.00 0.00 0.00 61310917.98 0.282797E+09
May 0.262123E+11 0.148666E+10 0.121917E+10 0.00 0.00 0.00 0.00 0.160466E+09 0.116081E+09
June 0.254132E+11 0.141991E+10 0.118076E+10 0.00 0.00 0.00 0.00 0.292309E+09 34263995.47
July 0.261570E+11 0.145980E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.272013E+09 23064766.88
August 0.262677E+11 0.150656E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.217199E+09 47714674.76
September 0.253456E+11 0.147181E+10 0.117729E+10 0.00 0.00 0.00 0.00 0.118980E+09 0.132890E+09
October 0.261693E+11 0.157293E+10 0.121734E+10 0.00 0.00 0.00 0.00 28288227.86 0.340457E+09
November 0.253025E+11 0.152628E+10 0.118021E+10 0.00 0.00 0.00 0.00 3133.24 0.721606E+09
December 0.261570E+11 0.159121E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.00 0.100236E+10
                   
Annual Sum or Average 0.308468E+12 0.180496E+11 0.143405E+11 0.00 0.00 0.00 0.00 0.115178E+10 0.496046E+10
Minimum of Months 0.236489E+11 0.141918E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 23064766.88
Maximum of Months 0.262800E+11 0.159856E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.292309E+09 0.100236E+10



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.104201E+11 0.126520E+11 0.00 0.00 0.00 0.00 0.00 0.273564E+10
February 0.702046E+11 0.938499E+10 0.114244E+11 0.00 0.00 0.00 0.00 12543.09 0.213167E+10
March 0.780153E+11 0.104002E+11 0.126786E+11 0.00 0.00 0.00 0.00 3900986.39 0.194134E+10
April 0.752779E+11 0.997990E+10 0.122282E+11 0.00 0.00 0.00 0.00 0.157464E+09 0.906978E+09
May 0.778146E+11 0.103301E+11 0.126672E+11 0.00 0.00 0.00 0.00 0.405130E+09 0.387431E+09
June 0.754422E+11 0.999248E+10 0.122682E+11 0.00 0.00 0.00 0.00 0.777867E+09 0.117585E+09
July 0.776503E+11 0.102711E+11 0.126273E+11 0.00 0.00 0.00 0.00 0.715435E+09 81127591.64
August 0.779788E+11 0.103657E+11 0.126824E+11 0.00 0.00 0.00 0.00 0.581233E+09 0.163820E+09
September 0.752414E+11 0.100075E+11 0.122320E+11 0.00 0.00 0.00 0.00 0.328838E+09 0.418283E+09
October 0.776868E+11 0.103913E+11 0.126482E+11 0.00 0.00 0.00 0.00 79911670.56 0.105131E+10
November 0.751137E+11 0.100809E+11 0.122624E+11 0.00 0.00 0.00 0.00 81795.28 0.215944E+10
December 0.776503E+11 0.103887E+11 0.126273E+11 0.00 0.00 0.00 0.00 0.00 0.298540E+10
                   
Annual Sum or Average 0.915726E+12 0.122013E+12 0.148998E+12 0.00 0.00 0.00 0.00 0.304987E+10 0.150800E+11
Minimum of Months 0.702046E+11 0.938499E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 81127591.64
Maximum of Months 0.780153E+11 0.104201E+11 0.126824E+11 0.00 0.00 0.00 0.00 0.777867E+09 0.298540E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.221660E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 145793.73 0.169139E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 853599.40 0.150290E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 20267972.43 60293330.20
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 51295856.03 19331384.26
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 93855052.06 3145118.97
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 90753133.96 992456.81
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 75041297.93 4916489.59
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 43293275.22 19695485.14
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 12432785.25 68766996.86
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 189622.97 0.167688E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.245603E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.388128E+09 0.113152E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 992456.81
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 93855052.06 0.245603E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.215682E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 165081.77 0.164705E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 978002.37 0.147246E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 20563425.23 59675717.90
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 51350032.89 19257182.52
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 93816529.92 3158446.02
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 90732894.96 998484.62
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 75118670.57 4878530.49
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 43564862.14 19548179.18
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 12733916.09 67231667.43
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 194947.52 0.163659E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.239259E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.389218E+09 0.110530E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 998484.62
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 93816529.92 0.239259E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 85091918.49 0.255708E+09 0.00 0.00 0.00 0.00 0.00 67859488.02
February 0.00 76846309.13 0.230956E+09 0.00 0.00 0.00 0.00 0.00 53044118.62
March 0.00 84415649.14 0.255355E+09 0.00 0.00 0.00 0.00 65001.03 47816029.35
April 0.00 82445007.08 0.247516E+09 0.00 0.00 0.00 0.00 4003850.18 21673330.83
May 0.00 84753783.81 0.255532E+09 0.00 0.00 0.00 0.00 10702837.59 8755501.02
June 0.00 81790910.76 0.247163E+09 0.00 0.00 0.00 0.00 20951924.46 2389346.91
July 0.00 85418966.65 0.255885E+09 0.00 0.00 0.00 0.00 19492227.80 1488624.73
August 0.00 84415649.14 0.255355E+09 0.00 0.00 0.00 0.00 15911000.13 3411165.08
September 0.00 82467180.11 0.247516E+09 0.00 0.00 0.00 0.00 9116501.65 9461176.50
October 0.00 85080831.98 0.255708E+09 0.00 0.00 0.00 0.00 2322944.70 25327857.41
November 0.00 82117958.92 0.247340E+09 0.00 0.00 0.00 0.00 4323.00 52813589.16
December 0.00 85430053.17 0.255885E+09 0.00 0.00 0.00 0.00 0.00 74200244.54
                   
Annual Sum or Average 0.00 0.100027E+10 0.300992E+10 0.00 0.00 0.00 0.00 82570610.55 0.368240E+09
Minimum of Months 0.00 76846309.13 0.230956E+09 0.00 0.00 0.00 0.00 0.00 1488624.73
Maximum of Months 0.00 85430053.17 0.255885E+09 0.00 0.00 0.00 0.00 20951924.46 74200244.54



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 85115186.72 0.255778E+09 0.00 0.00 0.00 0.00 0.00 60501609.94
February 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 139287.45 45972780.32
March 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 481704.58 40792159.61
April 0.293479E+09 82467551.52 0.247584E+09 0.00 0.00 0.00 0.00 6381476.50 16390515.15
May 0.303504E+09 84776959.58 0.255602E+09 0.00 0.00 0.00 0.00 14948922.66 5263259.50
June 0.293842E+09 81813276.33 0.247231E+09 0.00 0.00 0.00 0.00 26563690.39 851468.38
July 0.303141E+09 85442324.32 0.255955E+09 0.00 0.00 0.00 0.00 25735456.33 265538.31
August 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 21500877.78 1283784.91
September 0.293479E+09 82489730.61 0.247584E+09 0.00 0.00 0.00 0.00 12924655.74 5384977.20
October 0.303322E+09 85104097.18 0.255778E+09 0.00 0.00 0.00 0.00 4183896.43 18412173.32
November 0.293661E+09 82140413.93 0.247408E+09 0.00 0.00 0.00 0.00 146500.99 45212841.52
December 0.303141E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 0.00 67239130.63
                   
Annual Sum or Average 0.357224E+10 0.100055E+10 0.301074E+10 0.00 0.00 0.00 0.00 0.113006E+09 0.307570E+09
Minimum of Months 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 0.00 265538.31
Maximum of Months 0.303685E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 26563690.39 67239130.63



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.222108E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 146078.33 0.170472E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 873662.57 0.151988E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 20231559.41 61613893.82
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 51157493.41 19933607.13
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 93686281.78 3271762.33
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 90524015.48 1040127.71
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 74894497.07 5086474.47
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 43245178.39 20072599.12
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 12464069.94 69193881.28
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 190244.44 0.168462E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.245874E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.387413E+09 0.113912E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 1040127.71
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 93686281.78 0.245874E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.215661E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 187851.53 0.165827E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 976222.82 0.149206E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 20274575.32 61276697.57
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 51159239.06 19926692.12
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 93665335.03 3274349.67
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 90512764.14 1040973.94
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 74912955.46 5068789.96
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 43326646.03 20024876.62
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 12599620.17 68168347.70
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 247702.48 0.163506E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.239265E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.387863E+09 0.111225E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 1040973.94
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 93665335.03 0.239265E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.232638E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.278777E+09
February 0.348285E+10 0.210051E+10 0.00 0.00 0.00 0.00 0.00 37516.72 0.218501E+09
March 0.387034E+10 0.233355E+10 0.00 0.00 0.00 0.00 0.00 615156.81 0.201396E+09
April 0.373454E+10 0.224750E+10 0.00 0.00 0.00 0.00 0.00 16712614.61 97666550.64
May 0.386038E+10 0.233041E+10 0.00 0.00 0.00 0.00 0.00 40871984.99 43431633.35
June 0.374269E+10 0.225781E+10 0.00 0.00 0.00 0.00 0.00 82010028.04 13526930.91
July 0.385223E+10 0.232011E+10 0.00 0.00 0.00 0.00 0.00 75099289.62 9395632.75
August 0.386853E+10 0.233445E+10 0.00 0.00 0.00 0.00 0.00 61040596.18 18817811.68
September 0.373273E+10 0.224840E+10 0.00 0.00 0.00 0.00 0.00 34058444.77 46974026.37
October 0.385404E+10 0.232548E+10 0.00 0.00 0.00 0.00 0.00 8504230.00 0.114274E+09
November 0.372639E+10 0.225602E+10 0.00 0.00 0.00 0.00 0.00 32336.06 0.226459E+09
December 0.385223E+10 0.232011E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.304165E+09
                   
Annual Sum or Average 0.454292E+11 0.274007E+11 0.00 0.00 0.00 0.00 0.00 0.318982E+09 0.157338E+10
Minimum of Months 0.348285E+10 0.210051E+10 0.00 0.00 0.00 0.00 0.00 0.00 9395632.75
Maximum of Months 0.387034E+10 0.233445E+10 0.00 0.00 0.00 0.00 0.00 82010028.04 0.304165E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.220743E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 136521.57 0.168587E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 820462.25 0.149941E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 19951698.17 60363977.23
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 50730672.49 19458470.93
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 93066741.93 3216341.62
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 89912836.21 1032337.60
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 74286857.24 4978933.95
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 42751190.45 19856428.94
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 12217004.76 68799429.64
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 180246.99 0.167269E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.244751E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.384054E+09 0.112900E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 1032337.60
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 93066741.93 0.244751E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.214385E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 172640.51 0.163804E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 994718.49 0.146597E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 20237106.63 59683469.50
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 50785653.99 19378413.52
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 93016926.87 3232002.23
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 89888625.67 1039099.55
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 74361448.60 4938330.99
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 43046585.57 19697603.13
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 12598708.56 67015873.63
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 194561.19 0.162533E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.238177E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.385297E+09 0.110048E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 1039099.55
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 93016926.87 0.238177E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 85115186.72 0.255778E+09 0.00 0.00 0.00 0.00 0.00 0.116087E+09
February 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 68841.12 88506759.33
March 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 418333.17 78179453.29
April 0.293479E+09 82467551.52 0.247584E+09 0.00 0.00 0.00 0.00 10219447.96 31168503.50
May 0.303504E+09 84776959.58 0.255602E+09 0.00 0.00 0.00 0.00 26036944.85 9966168.72
June 0.293842E+09 81813276.33 0.247231E+09 0.00 0.00 0.00 0.00 47747618.14 1628055.16
July 0.303141E+09 85442324.32 0.255955E+09 0.00 0.00 0.00 0.00 46098320.75 524977.50
August 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 38061564.81 2550374.99
September 0.293479E+09 82489730.61 0.247584E+09 0.00 0.00 0.00 0.00 21844058.25 10219469.72
October 0.303322E+09 85104097.18 0.255778E+09 0.00 0.00 0.00 0.00 6207817.75 35682585.25
November 0.293661E+09 82140413.93 0.247408E+09 0.00 0.00 0.00 0.00 87315.51 87222166.37
December 0.303141E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 0.00 0.128779E+09
                   
Annual Sum or Average 0.357224E+10 0.100055E+10 0.301074E+10 0.00 0.00 0.00 0.00 0.196790E+09 0.590515E+09
Minimum of Months 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 0.00 524977.50
Maximum of Months 0.303685E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 47747618.14 0.128779E+09



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.303266E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.598194E+09
February 0.415303E+11 0.271117E+10 0.134904E+11 0.00 0.00 0.00 0.00 201718.65 0.466298E+09
March 0.461508E+11 0.297615E+10 0.149358E+11 0.00 0.00 0.00 0.00 1422184.27 0.429250E+09
April 0.445315E+11 0.281606E+10 0.144540E+11 0.00 0.00 0.00 0.00 36866679.92 0.202080E+09
May 0.460320E+11 0.289246E+10 0.149358E+11 0.00 0.00 0.00 0.00 91539983.51 87106343.64
June 0.446286E+11 0.278243E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.174919E+09 26735499.79
July 0.459349E+11 0.285773E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.161704E+09 18650711.41
August 0.461292E+11 0.292096E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.133657E+09 36968701.38
September 0.445099E+11 0.284760E+10 0.144540E+11 0.00 0.00 0.00 0.00 80929720.34 92811165.80
October 0.459565E+11 0.299951E+10 0.149358E+11 0.00 0.00 0.00 0.00 22700708.61 0.227343E+09
November 0.444343E+11 0.291802E+10 0.144540E+11 0.00 0.00 0.00 0.00 317861.31 0.466757E+09
December 0.459349E+11 0.301853E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.655183E+09
                   
Annual Sum or Average 0.541708E+12 0.347733E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.704260E+09 0.330738E+10
Minimum of Months 0.415303E+11 0.271117E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 18650711.41
Maximum of Months 0.461508E+11 0.303266E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.174919E+09 0.655183E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.303266E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.614120E+09
February 0.415303E+11 0.271117E+10 0.134904E+11 0.00 0.00 0.00 0.00 61527.57 0.479159E+09
March 0.461508E+11 0.297615E+10 0.149358E+11 0.00 0.00 0.00 0.00 865663.92 0.441495E+09
April 0.445315E+11 0.281606E+10 0.144540E+11 0.00 0.00 0.00 0.00 33860057.72 0.207013E+09
May 0.460320E+11 0.289246E+10 0.149358E+11 0.00 0.00 0.00 0.00 87173305.40 88879238.40
June 0.446286E+11 0.278243E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.170334E+09 27360894.01
July 0.459349E+11 0.285773E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.156889E+09 19203370.91
August 0.461292E+11 0.292096E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.129085E+09 37986160.22
September 0.445099E+11 0.284760E+10 0.144540E+11 0.00 0.00 0.00 0.00 76638025.39 94589609.57
October 0.459565E+11 0.299951E+10 0.149358E+11 0.00 0.00 0.00 0.00 20592345.07 0.233602E+09
November 0.444343E+11 0.291802E+10 0.144540E+11 0.00 0.00 0.00 0.00 168963.36 0.479052E+09
December 0.459349E+11 0.301853E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.672004E+09
                   
Annual Sum or Average 0.541708E+12 0.347733E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.675668E+09 0.339446E+10
Minimum of Months 0.415303E+11 0.271117E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 19203370.91
Maximum of Months 0.461508E+11 0.303266E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.170334E+09 0.672004E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.113146E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.590405E+09
February 0.369574E+10 0.102161E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.459816E+09
March 0.410691E+10 0.113495E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 145836.58 0.421693E+09
April 0.396281E+10 0.109310E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 25019302.69 0.195657E+09
May 0.409635E+10 0.113342E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 71044630.10 82901612.37
June 0.397146E+10 0.109811E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.146643E+09 25308908.97
July 0.408770E+10 0.112841E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.134012E+09 17778574.91
August 0.410499E+10 0.113539E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.108566E+09 35978299.03
September 0.396089E+10 0.109354E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 60321794.10 87565776.64
October 0.408962E+10 0.113103E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 14135195.38 0.222920E+09
November 0.395417E+10 0.109724E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.460037E+09
December 0.408770E+10 0.112841E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.645244E+09
                   
Annual Sum or Average 0.482060E+11 0.133267E+11 0.392709E+12 0.359593E+12 0.00 0.00 0.00 0.559888E+09 0.324531E+10
Minimum of Months 0.369574E+10 0.102161E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 0.00 17778574.91
Maximum of Months 0.410691E+10 0.113539E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.146643E+09 0.645244E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.246211E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.491336E+09
February 0.368610E+10 0.222306E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.388363E+09
March 0.409620E+10 0.246970E+10 0.00 0.00 0.00 0.00 0.00 338206.08 0.362008E+09
April 0.395248E+10 0.237864E+10 0.00 0.00 0.00 0.00 0.00 24677835.69 0.179441E+09
May 0.408566E+10 0.246638E+10 0.00 0.00 0.00 0.00 0.00 69393879.34 79386528.21
June 0.396110E+10 0.238954E+10 0.00 0.00 0.00 0.00 0.00 0.143340E+09 24793430.74
July 0.407704E+10 0.245547E+10 0.00 0.00 0.00 0.00 0.00 0.130987E+09 17443091.07
August 0.409429E+10 0.247065E+10 0.00 0.00 0.00 0.00 0.00 0.106107E+09 35083183.95
September 0.395056E+10 0.237958E+10 0.00 0.00 0.00 0.00 0.00 58903007.63 84336211.65
October 0.407896E+10 0.246116E+10 0.00 0.00 0.00 0.00 0.00 13797901.10 0.207074E+09
November 0.394385E+10 0.238765E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.399311E+09
December 0.407704E+10 0.245547E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.536932E+09
                   
Annual Sum or Average 0.480803E+11 0.289994E+11 0.00 0.00 0.00 0.00 0.00 0.547545E+09 0.280551E+10
Minimum of Months 0.368610E+10 0.222306E+10 0.00 0.00 0.00 0.00 0.00 0.00 17443091.07
Maximum of Months 0.409620E+10 0.247065E+10 0.00 0.00 0.00 0.00 0.00 0.143340E+09 0.536932E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 14185.34 02-JAN-20:10 10113.80 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 14185.34 01-FEB-20:10 10113.80 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 14185.34 01-MAR-20:10 10113.80 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 14185.34 03-APR-19:10 10113.80 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 14185.34 01-MAY-19:10 10113.80 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 14185.34 01-JUN-19:10 10113.80 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 14185.34 03-JUL-19:10 10113.80 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 14185.34 01-AUG-19:10 10113.80 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 14185.34 01-SEP-19:10 10113.80 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 14185.34 02-OCT-19:10 10113.80 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 14185.34 01-NOV-19:10 10113.80 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 14185.34 01-DEC-20:10 10113.80 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   14185.34   10113.80   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   14185.34   10113.80   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 704.41 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 286.22 27-JAN-07:00
February 1169.53 01-FEB-00:10 704.41 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 300.78 03-FEB-07:00
March 1169.53 01-MAR-00:10 704.41 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 10.06 21-MAR-16:00 282.96 02-MAR-05:00
April 1169.53 01-APR-00:10 704.41 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 80.90 21-APR-14:00 193.30 12-APR-06:00
May 1169.53 01-MAY-00:10 704.41 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 108.34 21-MAY-14:00 138.59 02-MAY-06:00
June 1169.53 01-JUN-00:10 704.41 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 144.65 02-JUN-16:00 91.94 13-JUN-05:00
July 1169.53 01-JUL-00:10 704.41 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 139.37 02-JUL-16:00 59.91 05-JUL-06:00
August 1169.53 01-AUG-00:10 704.41 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 129.08 07-AUG-16:00 74.52 31-AUG-06:00
September 1169.53 01-SEP-00:10 704.41 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 97.61 19-SEP-14:00 154.99 30-SEP-05:55
October 1169.53 01-OCT-23:10 704.41 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 87.26 01-OCT-15:00 167.41 11-OCT-06:00
November 1169.53 01-NOV-00:10 704.41 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 242.61 28-NOV-05:00
December 1169.53 01-DEC-00:10 704.41 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 287.28 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   704.41   685.60   0.00 0.00 0.00 0.00 0.00   59.91  
Maximum of Months 1169.53   704.41   685.60   0.00 0.00 0.00 0.00 144.65   300.78  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 815.72 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 115.87 27-JAN-07:00
February 1354.32 01-FEB-00:10 815.72 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 0.82 20-FEB-15:00 121.82 03-FEB-07:00
March 1354.32 01-MAR-00:10 815.72 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 7.97 22-MAR-13:00 114.76 02-MAR-05:30
April 1354.32 01-APR-00:10 815.72 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 33.41 21-APR-14:00 83.06 12-APR-06:00
May 1354.32 01-MAY-00:10 815.72 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 43.13 19-MAY-14:00 58.90 02-MAY-06:00
June 1354.32 01-JUN-00:10 815.72 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 56.12 02-JUN-16:00 36.48 13-JUN-05:00
July 1354.32 01-JUL-00:10 815.72 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 54.76 02-JUL-16:00 24.95 05-JUL-06:00
August 1354.32 01-AUG-00:10 815.72 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 49.83 07-AUG-16:00 29.64 31-AUG-06:00
September 1354.32 01-SEP-00:10 815.72 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 38.14 19-SEP-14:00 64.24 30-SEP-05:55
October 1354.32 01-OCT-23:10 815.72 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 34.66 01-OCT-15:00 70.65 25-OCT-06:00
November 1354.32 01-NOV-00:10 815.72 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 2.27 03-NOV-16:00 101.13 17-NOV-04:00
December 1354.32 01-DEC-00:10 815.72 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 115.51 19-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   815.72   793.93   0.00 0.00 0.00 0.00 0.00   24.95  
Maximum of Months 1354.32   815.72   793.93   0.00 0.00 0.00 0.00 56.12   121.82  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 1360.40 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 265.04 27-JAN-07:00
February 286.42 01-FEB-00:10 1360.40 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 7.36 20-FEB-15:00 277.08 03-FEB-07:00
March 286.42 01-MAR-00:10 1360.40 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 24.11 21-MAR-16:00 262.21 02-MAR-05:30
April 286.42 01-APR-00:10 1360.40 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 74.51 21-APR-14:00 193.55 12-APR-06:00
May 286.42 01-MAY-00:10 1360.40 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 98.84 21-MAY-14:00 138.96 02-MAY-06:00
June 286.42 01-JUN-00:10 1360.40 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 131.95 02-JUN-16:00 86.21 13-JUN-05:00
July 286.42 01-JUL-00:10 1360.40 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 127.14 02-JUL-16:00 58.98 05-JUL-06:00
August 286.42 01-AUG-00:10 1360.40 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 117.75 07-AUG-16:00 70.06 31-AUG-06:00
September 286.42 01-SEP-00:10 1360.40 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 89.05 19-SEP-14:00 152.01 30-SEP-05:55
October 286.42 01-OCT-23:10 1360.40 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 80.58 01-OCT-15:00 164.92 11-OCT-06:00
November 286.42 01-NOV-00:10 1360.40 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 9.19 08-NOV-15:00 230.72 17-NOV-04:00
December 286.42 01-DEC-00:10 1360.40 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 262.67 19-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   1360.40   839.45   0.00 0.00 0.00 0.00 0.00   58.98  
Maximum of Months 286.42   1360.40   839.45   0.00 0.00 0.00 0.00 131.95   277.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 227.72 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 150.64 27-JAN-07:00
February 220.32 01-FEB-00:10 227.72 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 9.37 20-FEB-15:00 158.30 03-FEB-07:00
March 220.32 01-MAR-00:10 227.72 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 19.41 21-MAR-16:00 148.92 02-MAR-05:20
April 220.32 01-APR-00:10 227.72 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 49.09 21-APR-14:00 104.31 12-APR-06:00
May 220.32 01-MAY-00:10 227.72 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 61.57 19-MAY-16:00 72.94 02-MAY-06:00
June 220.32 01-JUN-00:10 227.72 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 79.24 02-JUN-16:00 46.04 13-JUN-05:00
July 220.32 01-JUL-00:10 227.72 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 76.21 01-JUL-17:00 29.86 05-JUL-06:00
August 220.32 01-AUG-00:10 227.72 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 70.07 07-AUG-16:00 35.56 31-AUG-06:00
September 220.32 01-SEP-00:10 227.72 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 55.98 19-SEP-16:00 80.68 30-SEP-05:55
October 220.32 01-OCT-23:10 227.72 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 52.25 01-OCT-15:00 87.73 11-OCT-06:00
November 220.32 01-NOV-00:10 227.72 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 11.07 03-NOV-16:00 127.67 28-NOV-05:00
December 220.32 01-DEC-00:10 227.72 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 151.20 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   227.72   242.16   0.00 0.00 0.00 0.00 0.00   29.86  
Maximum of Months 220.32   227.72   242.16   0.00 0.00 0.00 0.00 79.24   158.30  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 357.21 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 0.00 01-JAN-00:05 398.60 27-JAN-07:00
February 907.20 01-FEB-00:10 357.21 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 0.00 01-FEB-00:05 416.88 03-FEB-07:00
March 907.20 01-MAR-00:10 357.21 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 12.53 21-MAR-16:00 394.88 02-MAR-06:00
April 907.20 01-APR-00:10 357.21 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 100.77 21-APR-14:00 321.23 11-APR-05:25
May 907.20 01-MAY-00:10 357.21 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 134.95 21-MAY-14:00 193.73 02-MAY-06:00
June 907.20 01-JUN-00:10 357.21 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 180.18 02-JUN-16:00 117.71 13-JUN-05:00
July 907.20 01-JUL-00:10 357.21 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 173.60 02-JUL-16:00 80.53 05-JUL-06:00
August 907.20 01-AUG-00:10 357.21 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 160.80 07-AUG-16:00 95.66 31-AUG-06:00
September 907.20 01-SEP-00:10 357.21 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 121.60 19-SEP-14:00 210.15 30-SEP-06:00
October 907.20 01-OCT-23:10 357.21 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 108.69 01-OCT-15:00 265.06 25-OCT-05:10
November 907.20 01-NOV-00:10 357.21 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 0.00 01-NOV-00:10 342.57 28-NOV-01:00
December 907.20 01-DEC-00:10 357.21 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 0.00 01-DEC-00:05 400.09 27-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   357.21   4572.80   39726.58   0.00 0.00 0.00 0.00   80.53  
Maximum of Months 907.20   357.21   4572.80   39726.58   0.00 0.00 0.00 180.18   416.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 1761.91 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 636.98 27-JAN-07:00
February 15368.40 01-FEB-00:10 1761.91 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 1.50 22-FEB-16:00 668.57 03-FEB-07:00
March 15368.40 01-MAR-00:10 1761.91 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 35.34 21-MAR-16:00 642.57 02-MAR-05:20
April 15368.40 01-APR-00:10 1761.91 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 192.60 21-APR-15:00 467.39 13-APR-05:15
May 15368.40 01-MAY-00:10 1761.91 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 259.29 21-MAY-14:00 309.47 02-MAY-06:00
June 15368.40 01-JUN-00:10 1761.91 01-JUN-19:10 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 332.83 02-JUN-17:00 201.10 13-JUN-05:00
July 15368.40 01-JUL-00:10 1761.91 03-JUL-19:10 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 329.79 02-JUL-16:00 123.36 05-JUL-06:00
August 15368.40 01-AUG-00:10 1761.91 01-AUG-19:10 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 290.10 07-AUG-16:00 153.45 31-AUG-06:00
September 15368.40 01-SEP-00:10 1761.91 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 215.81 19-SEP-14:00 340.27 30-SEP-05:55
October 15368.40 01-OCT-23:10 1761.91 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 192.91 01-OCT-15:00 404.49 25-OCT-03:10
November 15368.40 01-NOV-00:10 1761.91 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 2.15 08-NOV-15:40 565.99 17-NOV-04:00
December 15368.40 01-DEC-00:10 1761.91 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 648.73 19-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   1761.91   965.27   0.00 0.00 0.00 0.00 0.00   123.36  
Maximum of Months 15368.40   1761.91   965.27   0.00 0.00 0.00 0.00 332.83   668.57  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 10265.18 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1931.92 27-JAN-07:00
February 45622.98 01-FEB-00:10 10265.18 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 8.19 20-FEB-16:00 2022.92 03-FEB-07:00
March 45622.98 01-MAR-00:10 10265.18 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 122.36 22-MAR-13:00 1928.90 02-MAR-05:30
April 45622.98 01-APR-00:10 10265.18 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 550.33 21-APR-14:00 1377.40 12-APR-06:00
May 45622.98 01-MAY-00:10 10265.18 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 721.73 19-MAY-14:00 973.67 02-MAY-06:00
June 45622.98 01-JUN-00:10 10265.18 01-JUN-19:10 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 929.14 02-JUN-16:00 596.75 13-JUN-05:00
July 45622.98 01-JUL-00:10 10265.18 03-JUL-19:10 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 917.71 02-JUL-16:00 408.22 05-JUL-06:00
August 45622.98 01-AUG-00:10 10265.18 01-AUG-19:10 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 818.44 07-AUG-16:00 484.95 31-AUG-06:00
September 45622.98 01-SEP-00:10 10265.18 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 624.25 19-SEP-14:00 1055.14 30-SEP-05:55
October 45622.98 01-OCT-23:10 10265.18 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 566.91 01-OCT-15:00 1173.54 25-OCT-03:10
November 45622.98 01-NOV-00:10 10265.18 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 28.78 08-NOV-15:00 1692.14 17-NOV-04:00
December 45622.98 01-DEC-00:10 10265.18 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 1940.25 19-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   10265.18   10029.21   0.00 0.00 0.00 0.00 0.00   408.22  
Maximum of Months 45622.98   10265.18   10029.21   0.00 0.00 0.00 0.00 929.14   2022.92  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 167.12 27-JAN-07:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 11.69 20-FEB-16:07 175.57 03-FEB-07:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 22.51 21-MAR-16:00 165.23 02-MAR-05:10
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 62.17 21-APR-15:08 112.76 12-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 78.87 19-MAY-16:00 72.67 02-MAY-06:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 99.99 02-JUN-16:00 37.51 13-JUN-05:00
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 96.99 02-JUL-16:00 20.31 05-JUL-06:00
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 91.07 07-AUG-16:00 27.20 31-AUG-06:00
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 71.76 19-SEP-16:00 80.18 30-SEP-06:00
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 63.87 01-OCT-15:10 91.19 25-OCT-05:57
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 16.23 03-NOV-16:00 141.79 28-NOV-05:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 167.75 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 0.00   20.31  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 99.99   175.57  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 167.11 27-JAN-07:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 11.69 20-FEB-16:09 175.56 03-FEB-07:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 22.51 21-MAR-16:00 165.22 02-MAR-05:10
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 62.17 21-APR-15:07 112.76 12-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 78.86 19-MAY-16:00 72.66 02-MAY-06:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 99.99 02-JUN-16:00 37.51 13-JUN-05:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 96.99 02-JUL-16:00 20.31 05-JUL-06:00
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 91.07 07-AUG-16:00 27.20 31-AUG-06:00
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 72.85 19-SEP-16:00 80.18 30-SEP-06:00
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 66.01 01-OCT-15:10 91.18 25-OCT-05:57
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 16.23 03-NOV-16:00 141.78 28-NOV-05:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 167.73 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 0.00   20.31  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 99.99   175.56  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 76.99 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 46.05 27-JAN-07:20
February 0.00 01-FEB-00:10 76.99 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 49.21 03-FEB-07:00
March 0.00 01-MAR-00:10 76.99 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 2.65 21-MAR-16:00 44.68 02-MAR-05:00
April 0.00 01-APR-00:10 76.99 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 14.10 21-APR-14:00 32.51 12-APR-06:00
May 0.00 01-MAY-00:10 76.99 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 18.54 21-MAY-14:00 23.15 02-MAY-06:00
June 0.00 01-JUN-00:10 76.99 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 24.41 02-JUN-16:00 14.23 13-JUN-05:00
July 0.00 01-JUL-00:10 76.99 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 23.55 02-JUL-16:00 8.93 05-JUL-06:00
August 0.00 01-AUG-00:10 76.99 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 21.89 07-AUG-16:00 10.92 31-AUG-06:00
September 0.00 01-SEP-00:10 76.99 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 16.81 19-SEP-14:00 25.81 30-SEP-05:55
October 0.00 01-OCT-00:10 76.99 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 15.13 01-OCT-15:00 28.42 25-OCT-06:00
November 0.00 01-NOV-00:10 76.99 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 0.86 08-NOV-15:00 40.88 17-NOV-04:00
December 0.00 01-DEC-00:10 76.99 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 46.50 19-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   76.99   232.19   0.00 0.00 0.00 0.00 0.00   8.93  
Maximum of Months 0.00   76.99   232.19   0.00 0.00 0.00 0.00 24.41   49.21  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 77.01 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 46.64 27-JAN-07:00
February 180.00 01-FEB-00:10 77.01 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 3.26 20-FEB-16:04 49.00 03-FEB-07:00
March 180.00 01-MAR-00:10 77.01 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 6.28 21-MAR-16:00 46.11 02-MAR-05:10
April 180.00 01-APR-00:10 77.01 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 17.35 21-APR-15:10 31.47 12-APR-06:00
May 180.00 01-MAY-00:10 77.01 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 22.01 19-MAY-16:00 20.28 02-MAY-06:00
June 180.00 01-JUN-00:10 77.01 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 27.91 02-JUN-16:00 10.47 13-JUN-05:00
July 180.00 01-JUL-00:10 77.01 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 27.07 02-JUL-16:00 5.67 05-JUL-06:00
August 180.00 01-AUG-00:10 77.01 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 25.42 07-AUG-16:00 7.59 31-AUG-06:00
September 180.00 01-SEP-00:10 77.01 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 20.33 19-SEP-16:00 22.38 30-SEP-06:00
October 180.00 01-OCT-00:10 77.01 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 18.43 01-OCT-15:08 25.45 25-OCT-06:00
November 180.00 01-NOV-00:10 77.01 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 4.53 03-NOV-16:00 39.57 28-NOV-05:00
December 180.00 01-DEC-00:10 77.01 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 46.82 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 0.00   5.67  
Maximum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 27.91   49.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 167.12 27-JAN-07:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 11.69 20-FEB-16:09 175.57 03-FEB-07:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 22.51 21-MAR-16:00 165.23 02-MAR-05:10
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 62.17 21-APR-15:08 112.76 12-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 78.87 19-MAY-16:00 72.67 02-MAY-06:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 99.99 02-JUN-16:00 37.51 13-JUN-05:00
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 96.99 02-JUL-16:00 21.07 05-JUL-07:10
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 91.08 07-AUG-16:00 28.62 30-AUG-07:10
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 72.85 19-SEP-16:00 80.18 30-SEP-05:55
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 66.01 01-OCT-15:10 91.19 25-OCT-05:57
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 16.24 03-NOV-16:00 141.79 28-NOV-05:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 167.75 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 0.00   21.07  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 99.99   175.57  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 167.11 27-JAN-07:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 11.69 20-FEB-16:06 175.56 03-FEB-07:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 22.51 21-MAR-16:00 165.22 02-MAR-05:10
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 62.17 21-APR-15:10 112.76 12-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 78.86 19-MAY-16:00 72.66 02-MAY-06:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 99.99 02-JUN-16:00 37.51 13-JUN-05:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 96.99 02-JUL-16:00 21.11 05-JUL-07:10
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 91.07 07-AUG-16:00 28.15 30-AUG-07:10
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 72.85 19-SEP-16:00 80.18 30-SEP-06:00
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 66.01 01-OCT-15:08 91.18 25-OCT-05:57
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 16.23 03-NOV-16:00 141.78 28-NOV-05:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 167.73 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 0.00   21.11  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 99.99   175.56  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 2240.78 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 201.84 27-JAN-07:00
February 2263.36 01-FEB-00:10 2240.78 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 3.90 20-FEB-15:00 212.95 03-FEB-07:00
March 2263.36 01-MAR-00:10 2240.78 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 15.21 21-MAR-16:00 202.38 02-MAR-05:20
April 2263.36 01-APR-00:10 2240.78 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 57.87 21-APR-14:00 148.29 12-APR-06:00
May 2263.36 01-MAY-00:10 2240.78 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 75.74 21-MAY-14:00 105.49 02-MAY-06:00
June 2263.36 01-JUN-00:10 2240.78 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 101.23 02-JUN-16:00 66.58 13-JUN-05:00
July 2263.36 01-JUL-00:10 2240.78 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 97.52 02-JUL-16:00 45.03 05-JUL-06:00
August 2263.36 01-AUG-00:10 2240.78 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 90.30 07-AUG-16:00 53.55 31-AUG-06:00
September 2263.36 01-SEP-00:10 2240.78 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 68.22 19-SEP-14:00 115.80 30-SEP-05:55
October 2263.36 01-OCT-23:10 2240.78 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 60.95 01-OCT-15:00 125.90 25-OCT-06:00
November 2263.36 01-NOV-00:10 2240.78 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 5.27 08-NOV-15:00 180.56 17-NOV-04:00
December 2263.36 01-DEC-00:10 2240.78 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 203.43 19-DEC-05:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   2240.78   0.00 0.00 0.00 0.00 0.00 0.00   45.03  
Maximum of Months 2263.36   2240.78   0.00 0.00 0.00 0.00 0.00 101.23   212.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 167.55 27-JAN-07:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 11.34 20-FEB-16:07 176.00 03-FEB-07:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 22.16 21-MAR-16:00 165.66 02-MAR-05:10
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 61.84 21-APR-15:08 113.16 12-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 78.54 19-MAY-16:00 73.05 02-MAY-06:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 99.68 02-JUN-16:00 37.88 13-JUN-05:00
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 96.65 02-JUL-16:00 20.67 05-JUL-06:00
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 90.70 07-AUG-16:00 27.57 31-AUG-06:00
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 70.75 19-SEP-16:00 80.57 30-SEP-06:00
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 63.39 01-OCT-15:10 91.58 25-OCT-05:57
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 15.88 03-NOV-16:00 142.21 28-NOV-05:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 168.17 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 0.00   20.67  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 99.68   176.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 167.54 27-JAN-07:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 11.34 20-FEB-16:09 175.98 03-FEB-07:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 22.16 21-MAR-16:00 165.65 02-MAR-05:10
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 61.84 21-APR-15:07 113.15 12-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 78.54 19-MAY-16:00 73.05 02-MAY-06:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 99.67 02-JUN-16:00 37.88 13-JUN-05:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 96.64 02-JUL-16:00 20.67 05-JUL-06:00
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 90.72 07-AUG-16:00 27.57 31-AUG-06:00
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 72.51 19-SEP-16:00 80.56 30-SEP-06:00
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 65.68 01-OCT-15:10 91.58 25-OCT-05:57
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 15.88 03-NOV-16:00 142.20 28-NOV-05:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 168.16 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 0.00   20.67  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 99.67   175.98  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 77.01 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 85.72 27-JAN-07:00
February 180.00 01-FEB-00:10 77.01 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 5.80 20-FEB-16:09 90.05 03-FEB-07:00
March 180.00 01-MAR-00:10 77.01 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 11.34 21-MAR-16:00 84.76 02-MAR-05:10
April 180.00 01-APR-00:10 77.01 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 31.64 21-APR-15:08 57.90 12-APR-06:00
May 180.00 01-MAY-00:10 77.01 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 40.19 19-MAY-16:00 37.38 02-MAY-06:00
June 180.00 01-JUN-00:10 77.01 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 51.00 02-JUN-16:00 19.38 13-JUN-05:00
July 180.00 01-JUL-00:10 77.01 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 49.46 02-JUL-16:00 10.58 05-JUL-06:00
August 180.00 01-AUG-00:10 77.01 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 46.43 07-AUG-16:00 14.11 31-AUG-06:00
September 180.00 01-SEP-00:10 77.01 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 37.05 19-SEP-16:00 41.22 30-SEP-06:00
October 180.00 01-OCT-00:10 77.01 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 31.23 01-OCT-15:10 46.86 25-OCT-06:00
November 180.00 01-NOV-00:10 77.01 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 7.99 03-NOV-16:00 72.76 28-NOV-05:00
December 180.00 01-DEC-00:10 77.01 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 86.04 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 0.00   10.58  
Maximum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 51.00   90.05  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3094.06 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 433.72 27-JAN-07:00
February 26988.77 01-FEB-00:10 3094.06 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 14.65 20-FEB-16:00 453.08 03-FEB-07:00
March 26988.77 01-MAR-00:10 3094.06 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 36.30 22-MAR-13:00 432.16 02-MAR-05:20
April 26988.77 01-APR-00:10 3094.06 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 127.27 21-APR-14:00 324.32 13-APR-05:15
May 26988.77 01-MAY-00:10 3094.06 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 163.43 19-MAY-14:00 220.84 02-MAY-06:00
June 26988.77 01-JUN-00:10 3094.06 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 207.91 02-JUN-16:30 135.39 13-JUN-05:00
July 26988.77 01-JUL-00:10 3094.06 03-JUL-19:19 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 206.87 02-JUL-16:00 93.08 05-JUL-06:00
August 26988.77 01-AUG-00:10 3094.06 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 184.92 07-AUG-16:00 110.32 31-AUG-06:00
September 26988.77 01-SEP-00:10 3094.06 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 151.44 19-SEP-14:00 234.49 30-SEP-05:55
October 26988.77 01-OCT-23:10 3094.06 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 139.07 01-OCT-15:00 275.70 25-OCT-03:10
November 26988.77 01-NOV-00:10 3094.06 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 22.03 08-NOV-15:00 378.47 27-NOV-23:00
December 26988.77 01-DEC-00:10 3094.06 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 433.31 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 0.00   93.08  
Maximum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 207.91   453.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3094.06 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 440.06 27-JAN-07:00
February 26988.77 01-FEB-00:10 3094.06 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 9.13 20-FEB-16:00 459.19 03-FEB-07:00
March 26988.77 01-MAR-00:10 3094.06 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 31.02 22-MAR-13:00 437.52 02-MAR-05:20
April 26988.77 01-APR-00:10 3094.06 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 123.28 21-APR-14:00 326.49 13-APR-05:15
May 26988.77 01-MAY-00:10 3094.06 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 159.39 19-MAY-14:00 221.93 02-MAY-06:00
June 26988.77 01-JUN-00:10 3094.06 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 203.68 02-JUN-16:00 135.40 13-JUN-05:00
July 26988.77 01-JUL-00:10 3094.06 03-JUL-19:19 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 202.48 02-JUL-16:00 93.08 05-JUL-06:00
August 26988.77 01-AUG-00:10 3094.06 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 181.61 07-AUG-16:00 110.32 31-AUG-06:00
September 26988.77 01-SEP-00:10 3094.06 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 147.59 19-SEP-14:00 237.71 30-SEP-05:55
October 26988.77 01-OCT-23:10 3094.06 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 134.78 01-OCT-15:00 278.97 25-OCT-03:10
November 26988.77 01-NOV-00:10 3094.06 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 17.14 08-NOV-15:00 382.33 27-NOV-23:00
December 26988.77 01-DEC-00:10 3094.06 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 439.83 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 0.00   93.08  
Maximum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 203.68   459.19  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1089.83 02-JAN-20:10 14912.86 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 0.00 01-JAN-00:05 407.41 27-JAN-07:00
February 2401.70 01-FEB-00:10 1089.83 01-FEB-20:10 14912.86 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 0.00 01-FEB-00:05 426.04 03-FEB-07:00
March 2401.70 01-MAR-00:10 1089.83 01-MAR-20:10 14912.86 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 11.66 21-MAR-16:00 403.73 02-MAR-05:10
April 2401.70 01-APR-00:10 1089.83 03-APR-19:10 14912.86 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 101.50 21-APR-14:00 332.08 11-APR-05:25
May 2401.70 01-MAY-00:10 1089.83 01-MAY-19:10 14912.86 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 136.32 21-MAY-14:00 198.79 02-MAY-06:07
June 2401.70 01-JUN-00:10 1089.83 01-JUN-19:10 14912.86 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 182.50 02-JUN-16:00 121.20 13-JUN-05:00
July 2401.70 01-JUL-00:10 1089.83 03-JUL-19:10 14912.86 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 175.80 02-JUL-16:00 83.28 05-JUL-06:00
August 2401.70 01-AUG-00:10 1089.83 01-AUG-19:10 14912.86 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 162.76 07-AUG-16:00 98.71 31-AUG-06:00
September 2401.70 01-SEP-00:10 1089.83 01-SEP-19:10 14912.86 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 122.73 19-SEP-14:00 215.40 30-SEP-06:00
October 2401.70 01-OCT-23:10 1089.83 02-OCT-19:10 14912.86 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 109.59 01-OCT-15:00 269.05 25-OCT-03:10
November 2401.70 01-NOV-00:10 1089.83 01-NOV-19:10 14912.86 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 0.00 01-NOV-00:10 351.96 28-NOV-05:00
December 2401.70 01-DEC-00:10 1089.83 01-DEC-20:10 14912.86 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 0.00 01-DEC-00:05 408.95 27-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1089.83   14912.86   22492.83   0.00 0.00 0.00 0.00   83.28  
Maximum of Months 2401.70   1089.83   14912.86   22492.83   0.00 0.00 0.00 182.50   426.04  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 2371.52 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 356.93 27-JAN-07:00
February 2395.44 01-FEB-00:10 2371.52 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 375.01 03-FEB-07:00
March 2395.44 01-MAR-00:10 2371.52 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 17.18 21-MAR-16:00 352.89 02-MAR-05:00
April 2395.44 01-APR-00:10 2371.52 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 99.23 21-APR-14:00 255.33 12-APR-06:00
May 2395.44 01-MAY-00:10 2371.52 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 133.32 21-MAY-14:00 184.31 02-MAY-06:00
June 2395.44 01-JUN-00:10 2371.52 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 178.42 02-JUN-16:00 118.71 13-JUN-05:00
July 2395.44 01-JUL-00:10 2371.52 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 171.86 02-JUL-16:00 81.10 05-JUL-06:00
August 2395.44 01-AUG-00:10 2371.52 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 159.08 07-AUG-16:00 95.96 31-AUG-06:00
September 2395.44 01-SEP-00:10 2371.52 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 119.99 19-SEP-14:00 201.12 30-SEP-05:55
October 2395.44 01-OCT-23:10 2371.52 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 107.12 01-OCT-15:00 218.48 11-OCT-06:00
November 2395.44 01-NOV-00:10 2371.52 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 307.55 17-NOV-04:00
December 2395.44 01-DEC-00:10 2371.52 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 358.28 27-DEC-07:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   2371.52   0.00 0.00 0.00 0.00 0.00 0.00   81.10  
Maximum of Months 2395.44   2371.52   0.00 0.00 0.00 0.00 0.00 178.42   375.01  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 36391.18 26-JAN-20:51 71567.33 113482.76 80910.41 0.00 0.00 0.00 0.00 0.00 0.00
February 34516.86 02-FEB-22:34 103517.03 85113.15 67070.47 0.00 0.00 0.00 0.00 0.00 0.00
March 19817.85 17-MAR-03:44 115018.92 15762.30 21292.21 0.00 0.00 0.00 0.00 0.00 0.00
April 17820.58 11-APR-04:30 46007.57 12609.11 12775.33 0.00 0.00 0.00 0.00 0.00 0.00
May 14617.15 06-MAY-06:00 17891.83 9457.02 8516.89 0.00 0.00 0.00 0.00 0.00 0.00
June 13973.73 23-JUN-21:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
July 20668.26 19-JUL-21:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
August 23564.24 24-AUG-21:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
September 25575.64 21-SEP-21:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
October 35484.32 25-OCT-05:30 26837.75 18913.67 15969.16 0.00 0.00 0.00 0.00 0.00 0.00
November 40523.33 19-NOV-23:56 102239.04 47285.09 42584.43 0.00 0.00 0.00 0.00 0.00 0.00
December 37239.34 02-DEC-07:38 51119.52 37828.07 34067.54 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 13973.73   10223.90 9457.02 8516.89 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 40523.33   115018.92 113482.76 80910.41 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3119.63 26-JAN-12:32 2598.96 1956.71 2525.91 0.00 0.00 0.00 0.00 0.00 213.04
February 3000.98 07-FEB-13:30 259.90 195.67 252.59 0.00 0.00 0.00 0.00 0.00 37.97
March 2431.99 16-MAR-13:10 259.90 195.67 252.59 0.00 0.00 0.00 0.00 0.00 17.34
April 2529.23 03-APR-14:10 389.84 195.67 252.59 0.00 0.00 0.00 0.00 27.21 0.00
May 2489.31 19-MAY-18:15 1819.27 1252.29 1299.04 0.00 0.00 0.00 0.00 88.23 0.00
June 2868.32 15-JUN-18:15 1819.27 1252.29 1299.04 0.00 0.00 0.00 0.00 114.74 0.00
July 2836.02 26-JUL-18:03 5457.82 3756.88 3897.11 0.00 0.00 0.00 0.00 96.65 0.00
August 3004.70 27-AUG-12:00 389.84 234.80 288.68 0.00 0.00 0.00 0.00 92.38 0.00
September 3612.28 19-SEP-13:20 259.90 195.67 252.59 0.00 0.00 0.00 0.00 90.60 0.00
October 3750.87 18-OCT-13:00 259.90 195.67 252.59 0.00 0.00 0.00 0.00 38.38 0.00
November 3487.24 10-NOV-12:00 259.90 195.67 252.59 0.00 0.00 0.00 0.00 0.00 29.81
December 3219.97 21-DEC-12:55 519.79 391.34 505.18 0.00 0.00 0.00 0.00 0.00 163.09
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2431.99   259.90 195.67 252.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3750.87   5457.82 3756.88 3897.11 0.00 0.00 0.00 0.00 114.74 213.04



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2549.95 04-JAN-22:44 13543.20 5438.10 5850.02 0.00 0.00 0.00 0.00 0.00 80.45
February 3206.90 08-FEB-22:01 9480.24 3806.67 4095.01 0.00 0.00 0.00 0.00 0.00 88.43
March 2819.68 20-MAR-22:00 13543.20 5438.10 5850.02 0.00 0.00 0.00 0.00 0.00 72.46
April 2086.76 28-APR-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 0.00 4.75
May 2281.44 19-MAY-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 23.06 0.00
June 2494.28 15-JUN-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 35.40 0.00
July 2428.08 25-JUL-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 29.67 0.00
August 2462.69 07-AUG-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 29.59 0.00
September 2333.05 20-SEP-20:10 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 5.47 0.00
October 2249.81 05-OCT-20:10 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 0.00 0.80
November 2182.30 26-NOV-00:14 7373.52 1903.34 2340.01 0.00 0.00 0.00 0.00 0.00 78.05
December 2254.77 06-DEC-22:20 2708.64 1087.62 1170.00 0.00 0.00 0.00 0.00 0.00 74.29
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2086.76   1203.84 725.08 752.15 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3206.90   13543.20 5438.10 5850.02 0.00 0.00 0.00 0.00 35.40 88.43



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1283.31 02-JAN-00:33 859.25 906.93 795.27 0.00 0.00 0.00 0.00 0.00 175.47
February 1242.12 05-FEB-00:17 668.30 1360.40 1060.35 0.00 0.00 0.00 0.00 0.00 159.99
March 1404.18 17-MAR-03:44 2864.16 1511.55 1767.26 0.00 0.00 0.00 0.00 0.00 169.39
April 1865.10 21-APR-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 19.19 0.00
May 2295.32 31-MAY-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 49.33 0.00
June 2636.68 15-JUN-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 88.47 0.00
July 2583.04 03-JUL-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 39.39 0.00
August 2509.96 07-AUG-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 69.70 0.00
September 2190.86 22-SEP-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 19.36 0.00
October 2052.43 05-OCT-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 0.00 0.96
November 1347.33 26-NOV-00:14 1559.38 3174.26 2474.16 0.00 0.00 0.00 0.00 0.00 178.61
December 1121.34 30-DEC-10:29 954.72 4534.65 3534.51 0.00 0.00 0.00 0.00 0.00 168.53
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1121.34   222.77 906.93 795.27 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2636.68   2864.16 4534.65 3534.51 0.00 0.00 0.00 0.00 88.47 178.61



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1154.20 02-JAN-00:33 660.96 151.81 229.41 0.00 0.00 0.00 0.00 0.00 94.80
February 1068.91 05-FEB-00:17 514.08 227.72 305.88 0.00 0.00 0.00 0.00 0.00 86.48
March 1269.36 17-MAR-03:44 2203.20 253.02 509.80 0.00 0.00 0.00 0.00 0.00 91.08
April 1118.84 11-APR-04:30 881.28 202.41 305.88 0.00 0.00 0.00 0.00 0.00 94.47
May 916.63 31-MAY-18:07 1028.16 1214.49 1376.47 0.00 0.00 0.00 0.00 39.58 0.00
June 984.89 15-JUN-21:00 195.84 202.41 229.41 0.00 0.00 0.00 0.00 48.26 0.00
July 976.50 03-JUL-10:35 97.92 126.52 178.43 0.00 0.00 0.00 0.00 54.50 0.00
August 967.48 06-AUG-10:35 146.88 151.81 203.92 0.00 0.00 0.00 0.00 43.12 0.00
September 919.71 25-SEP-03:12 1101.60 126.51 254.90 0.00 0.00 0.00 0.00 0.00 65.10
October 1070.36 25-OCT-04:07 660.96 151.81 229.41 0.00 0.00 0.00 0.00 0.00 77.96
November 1205.92 26-NOV-00:14 1199.52 531.34 713.73 0.00 0.00 0.00 0.00 0.00 95.89
December 976.33 09-DEC-23:15 342.72 151.81 203.92 0.00 0.00 0.00 0.00 0.00 88.84
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 916.63   97.92 126.51 178.43 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1269.36   2203.20 1214.49 1376.47 0.00 0.00 0.00 0.00 54.50 95.89



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 51918.33 26-JAN-20:51 5644.80 2857.71 36582.41 317812.61 0.00 0.00 0.00 0.00 291.23
February 52902.86 08-FEB-20:40 2822.40 1428.86 18291.20 158906.31 0.00 0.00 0.00 0.00 300.11
March 49190.93 28-MAR-21:27 7257.60 1905.14 26955.46 234177.71 0.00 0.00 0.00 0.00 278.45
April 39211.09 12-APR-06:38 3628.80 1786.07 25992.76 225814.22 0.00 0.00 0.00 0.00 252.87
May 39365.87 30-MAY-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 61.21 0.00
June 39770.82 15-JUN-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 120.81 0.00
July 39720.01 03-JUL-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 53.78 0.00
August 39636.36 04-AUG-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 114.33 0.00
September 39287.97 20-SEP-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 20.15 0.00
October 39041.42 05-OCT-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 1.31
November 49602.81 27-NOV-21:46 8064.00 3175.23 43321.27 376357.04 0.00 0.00 0.00 0.00 308.79
December 50674.71 29-DEC-22:56 9072.00 2381.43 33694.32 292722.14 0.00 0.00 0.00 0.00 310.93
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 39041.42   705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 52902.86   9072.00 3175.23 43321.27 376357.04 0.00 0.00 0.00 120.81 310.93



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 14942.01 02-JAN-00:33 46105.20 1174.60 914.47 0.00 0.00 0.00 0.00 0.00 429.55
February 14006.05 05-FEB-00:17 35859.60 1761.91 1219.29 0.00 0.00 0.00 0.00 0.00 381.61
March 15671.14 17-MAR-03:44 153684.00 1957.67 2032.15 0.00 0.00 0.00 0.00 0.00 400.14
April 13392.31 11-APR-04:30 61473.60 1566.14 1219.29 0.00 0.00 0.00 0.00 0.00 402.24
May 11195.62 19-MAY-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 130.00 0.00
June 11957.56 15-JUN-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 187.22 0.00
July 11819.14 26-JUL-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 102.76 0.00
August 12366.60 07-AUG-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 159.89 0.00
September 12330.40 20-SEP-15:03 51228.00 1791.27 2133.76 0.00 0.00 0.00 0.00 203.11 0.00
October 12897.92 25-OCT-04:07 46105.20 1174.60 914.47 0.00 0.00 0.00 0.00 0.00 334.74
November 14769.65 26-NOV-00:14 83672.40 4111.11 2845.02 0.00 0.00 0.00 0.00 0.00 416.64
December 20257.70 23-DEC-00:33 61473.60 1566.14 1219.29 0.00 0.00 0.00 0.00 0.00 409.16
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 11195.62   15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20257.70   153684.00 4111.11 2845.02 0.00 0.00 0.00 0.00 203.11 429.55



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 62095.90 20-JAN-00:05 182491.92 9124.61 12668.47 0.00 0.00 0.00 0.00 0.00 1352.04
February 62404.06 17-FEB-01:00 456229.80 22811.52 31671.19 0.00 0.00 0.00 0.00 0.00 1320.55
March 61348.30 20-MAR-22:00 456229.80 68434.56 73899.43 0.00 0.00 0.00 0.00 0.00 1185.67
April 62847.71 11-APR-04:15 182491.92 9124.61 12668.47 0.00 0.00 0.00 0.00 0.00 1271.45
May 41462.75 31-MAY-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 262.55 0.00
June 44225.37 15-JUN-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 534.78 0.00
July 43583.03 26-JUL-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 293.47 0.00
August 44431.94 07-AUG-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 456.69 0.00
September 42454.93 21-SEP-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 134.26 0.00
October 41653.58 05-OCT-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 50.67
November 60457.17 11-NOV-06:10 141938.16 13686.91 16891.30 0.00 0.00 0.00 0.00 0.00 1249.99
December 53643.45 29-DEC-22:56 456229.80 68434.56 73899.43 0.00 0.00 0.00 0.00 0.00 1480.11
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 41462.75   45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 62847.71   456229.80 68434.56 73899.43 0.00 0.00 0.00 0.00 534.78 1480.11



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3247.51 03-JAN-16:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 0.00 13.29
February 3439.09 20-FEB-16:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 3.18 0.00
March 3456.16 21-MAR-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 11.67 0.00
April 3568.37 16-APR-15:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 40.16 0.00
May 3588.67 20-MAY-15:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 54.86 0.00
June 3584.50 15-JUN-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 87.71 0.00
July 3230.66 11-JUL-08:61 252.00 377.32 792.83 0.00 0.00 0.00 0.00 30.07 0.00
August 3214.32 08-AUG-18:01 970.20 763.21 903.46 0.00 0.00 0.00 0.00 38.64 0.00
September 3586.97 30-SEP-15:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 32.75 0.00
October 3558.55 21-OCT-15:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 20.47 0.00
November 3447.44 09-NOV-16:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 3.77 0.00
December 3117.46 23-DEC-16:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 0.00 34.05
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3117.46   252.00 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3588.67   970.20 763.21 903.46 0.00 0.00 0.00 0.00 87.71 34.05



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3111.70 12-JAN-16:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 0.00 20.30
February 3368.39 20-FEB-16:01 378.00 282.96 534.64 0.00 0.00 0.00 0.00 4.05 0.00
March 3389.10 21-MAR-15:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 12.45 0.00
April 3526.43 30-APR-18:01 819.00 857.43 903.35 0.00 0.00 0.00 0.00 41.22 0.00
May 3561.12 20-MAY-18:01 819.00 857.43 903.35 0.00 0.00 0.00 0.00 51.09 0.00
June 3568.43 15-JUN-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 75.03 0.00
July 3198.73 11-JUL-08:61 252.00 377.27 792.74 0.00 0.00 0.00 0.00 29.92 0.00
August 3207.09 08-AUG-18:01 970.20 763.12 903.35 0.00 0.00 0.00 0.00 38.69 0.00
September 3525.56 30-SEP-15:01 378.00 282.96 534.64 0.00 0.00 0.00 0.00 33.40 0.00
October 3487.99 21-OCT-15:01 378.00 282.96 534.64 0.00 0.00 0.00 0.00 21.29 0.00
November 3380.84 09-NOV-16:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 4.55 0.00
December 2896.50 16-DEC-16:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 43.37
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2896.50   252.00 240.08 458.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3568.43   970.20 857.43 903.35 0.00 0.00 0.00 0.00 75.03 43.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 558.38 12-JAN-14:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 8.09
February 539.78 07-FEB-13:40 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 5.28
March 439.99 16-MAR-13:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 1.45
April 426.99 04-APR-13:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 5.84 0.00
May 383.28 19-MAY-20:20 0.00 68.52 180.59 0.00 0.00 0.00 0.00 11.84 0.00
June 441.43 15-JUN-17:13 0.00 154.75 394.73 0.00 0.00 0.00 0.00 21.17 0.00
July 441.85 26-JUL-17:17 0.00 206.33 526.30 0.00 0.00 0.00 0.00 18.79 0.00
August 495.40 27-AUG-13:40 0.00 25.41 74.82 0.00 0.00 0.00 0.00 17.60 0.00
September 600.10 19-SEP-13:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 15.96 0.00
October 668.60 22-OCT-13:20 0.00 25.41 74.82 0.00 0.00 0.00 0.00 4.24 0.00
November 624.97 09-NOV-13:50 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 0.27
December 472.07 16-DEC-14:10 0.00 25.41 74.82 0.00 0.00 0.00 0.00 0.00 14.37
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 383.28   0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 668.60   0.00 206.33 526.30 0.00 0.00 0.00 0.00 21.17 14.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 676.35 15-JAN-09:01 540.00 431.26 1599.98 0.00 0.00 0.00 0.00 0.00 23.16
February 971.53 20-FEB-09:01 378.00 301.88 1119.99 0.00 0.00 0.00 0.00 0.00 17.68
March 1093.48 21-MAR-18:01 970.20 479.78 885.15 0.00 0.00 0.00 0.00 1.60 0.00
April 1232.45 21-APR-18:01 970.20 479.78 885.15 0.00 0.00 0.00 0.00 11.54 0.00
May 1236.05 20-MAY-18:01 819.00 539.08 885.15 0.00 0.00 0.00 0.00 14.05 0.00
June 1237.53 02-JUN-18:01 970.20 479.78 885.15 0.00 0.00 0.00 0.00 22.20 0.00
July 1152.04 26-JUL-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 21.93 0.00
August 1150.75 04-AUG-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 20.60 0.00
September 1205.75 11-SEP-18:01 970.20 479.78 885.15 0.00 0.00 0.00 0.00 8.52 0.00
October 1127.84 19-OCT-18:01 970.20 479.78 885.15 0.00 0.00 0.00 0.00 1.01 0.00
November 1052.74 08-NOV-19:01 970.20 479.78 885.15 0.00 0.00 0.00 0.00 0.00 0.71
December 833.91 09-DEC-09:02 324.00 258.76 959.99 0.00 0.00 0.00 0.00 0.00 11.61
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 676.35   324.00 129.38 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1237.53   970.20 539.08 1599.98 0.00 0.00 0.00 0.00 22.20 23.16



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2836.05 12-JAN-16:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 0.00 22.55
February 3000.13 20-FEB-16:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 3.58 0.00
March 3029.28 21-MAR-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 11.76 0.00
April 3119.04 03-APR-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 25.21 0.00
May 3137.75 20-MAY-15:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 55.10 0.00
June 3174.63 15-JUN-08:61 252.00 377.32 792.83 0.00 0.00 0.00 0.00 40.67 0.00
July 2881.59 31-JUL-08:61 252.00 377.32 792.83 0.00 0.00 0.00 0.00 12.47 0.00
August 2900.48 03-AUG-08:61 252.00 377.32 792.83 0.00 0.00 0.00 0.00 20.74 0.00
September 3132.17 30-SEP-15:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 33.08 0.00
October 3108.16 21-OCT-15:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 20.78 0.00
November 3013.95 09-NOV-16:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 4.03 0.00
December 2696.77 16-DEC-09:02 324.00 411.62 979.84 0.00 0.00 0.00 0.00 0.00 87.26
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2696.77   252.00 240.11 479.39 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3174.63   680.40 411.62 979.84 0.00 0.00 0.00 0.00 55.10 87.26



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2276.70 04-JAN-09:02 216.00 323.38 679.49 0.00 0.00 0.00 0.00 0.00 76.27
February 2849.07 21-FEB-16:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 4.19 0.00
March 2966.97 22-MAR-15:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 8.68 0.00
April 3087.53 30-APR-18:01 819.00 857.43 903.35 0.00 0.00 0.00 0.00 41.34 0.00
May 3111.84 20-MAY-15:01 378.00 282.96 534.64 0.00 0.00 0.00 0.00 55.14 0.00
June 3155.16 15-JUN-08:61 252.00 377.27 792.74 0.00 0.00 0.00 0.00 40.56 0.00
July 2853.82 30-JUL-18:01 819.00 857.43 903.35 0.00 0.00 0.00 0.00 36.06 0.00
August 2886.28 08-AUG-18:01 970.20 763.12 903.35 0.00 0.00 0.00 0.00 38.38 0.00
September 3077.04 30-SEP-15:01 378.00 282.96 534.64 0.00 0.00 0.00 0.00 33.73 0.00
October 3043.82 21-OCT-15:01 378.00 282.96 534.64 0.00 0.00 0.00 0.00 21.64 0.00
November 2888.40 09-NOV-16:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 6.73 0.00
December 2481.58 09-DEC-09:02 324.00 411.57 979.73 0.00 0.00 0.00 0.00 0.00 43.04
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2276.70   216.00 240.08 479.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3155.16   970.20 857.43 979.73 0.00 0.00 0.00 0.00 55.14 76.27



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2569.02 02-JAN-00:33 6790.07 1493.85 0.00 0.00 0.00 0.00 0.00 0.00 134.83
February 2469.44 05-FEB-00:17 5281.16 2240.78 0.00 0.00 0.00 0.00 0.00 0.00 122.25
March 2808.05 17-MAR-03:44 22633.56 2489.76 0.00 0.00 0.00 0.00 0.00 0.00 129.91
April 2501.63 11-APR-04:30 9053.42 1991.81 0.00 0.00 0.00 0.00 0.00 0.00 134.52
May 2978.06 19-MAY-18:30 1760.39 1991.81 0.00 0.00 0.00 0.00 0.00 60.39 0.00
June 3484.42 15-JUN-18:30 1760.39 1991.81 0.00 0.00 0.00 0.00 0.00 79.01 0.00
July 3338.51 26-JUL-18:30 1760.39 1991.81 0.00 0.00 0.00 0.00 0.00 58.99 0.00
August 3246.25 07-AUG-18:30 1760.39 1991.81 0.00 0.00 0.00 0.00 0.00 62.61 0.00
September 2954.46 20-SEP-18:15 3520.78 3983.61 0.00 0.00 0.00 0.00 0.00 44.45 0.00
October 2774.72 05-OCT-20:10 2011.87 1991.81 0.00 0.00 0.00 0.00 0.00 0.00 1.76
November 2685.56 26-NOV-00:14 12322.72 5228.49 0.00 0.00 0.00 0.00 0.00 0.00 136.76
December 2351.43 30-DEC-10:29 7544.52 7469.27 0.00 0.00 0.00 0.00 0.00 0.00 131.28
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2351.43   1760.39 1493.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3484.42   22633.56 7469.27 0.00 0.00 0.00 0.00 0.00 79.01 136.76



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3420.04 12-JAN-16:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 0.00 22.76
February 3634.62 20-FEB-16:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 3.06 0.00
March 3648.58 21-MAR-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 11.62 0.00
April 3783.45 16-APR-15:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 39.85 0.00
May 3804.08 20-MAY-15:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 54.57 0.00
June 3804.09 15-JUN-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 87.36 0.00
July 3408.84 18-JUL-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 46.35 0.00
August 3392.37 07-AUG-08:61 252.00 377.32 792.83 0.00 0.00 0.00 0.00 35.30 0.00
September 3795.06 30-SEP-15:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 32.58 0.00
October 3764.56 21-OCT-15:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 20.29 0.00
November 3643.32 09-NOV-16:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 3.65 0.00
December 3286.20 23-DEC-16:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 0.00 34.03
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3286.20   252.00 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3804.09   831.60 654.18 792.83 0.00 0.00 0.00 0.00 87.36 34.03



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3236.63 12-JAN-16:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 0.00 19.30
February 3547.18 20-FEB-16:01 378.00 282.96 534.64 0.00 0.00 0.00 0.00 4.06 0.00
March 3566.03 21-MAR-15:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 12.53 0.00
April 3732.07 16-APR-15:01 378.00 282.96 534.64 0.00 0.00 0.00 0.00 40.18 0.00
May 3769.84 20-MAY-15:01 378.00 282.96 534.64 0.00 0.00 0.00 0.00 54.60 0.00
June 3778.58 15-JUN-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 74.74 0.00
July 3388.15 18-JUL-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 46.35 0.00
August 3371.89 08-AUG-18:01 970.20 763.12 903.35 0.00 0.00 0.00 0.00 38.53 0.00
September 3722.01 30-SEP-15:01 378.00 282.96 534.64 0.00 0.00 0.00 0.00 33.28 0.00
October 3679.37 21-OCT-15:01 378.00 282.96 534.64 0.00 0.00 0.00 0.00 21.22 0.00
November 3559.50 09-NOV-16:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 4.58 0.00
December 2964.76 16-DEC-16:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 41.23
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2964.76   324.00 240.08 458.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3778.58   970.20 763.12 903.35 0.00 0.00 0.00 0.00 74.74 41.23



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1772.29 03-JAN-16:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 0.00 7.83
February 1855.93 20-FEB-16:01 378.00 177.90 523.86 0.00 0.00 0.00 0.00 0.93 0.00
March 1866.12 14-MAR-15:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 3.57 0.00
April 1906.52 03-APR-15:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 12.38 0.00
May 1902.35 20-MAY-15:01 378.00 177.90 523.86 0.00 0.00 0.00 0.00 27.95 0.00
June 1900.33 02-JUN-18:01 970.20 479.78 885.15 0.00 0.00 0.00 0.00 41.03 0.00
July 1743.60 14-JUL-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 19.84 0.00
August 1739.45 08-AUG-18:01 970.20 479.78 885.15 0.00 0.00 0.00 0.00 19.37 0.00
September 1924.95 30-SEP-15:01 378.00 177.90 523.86 0.00 0.00 0.00 0.00 16.23 0.00
October 1922.88 21-OCT-15:01 378.00 177.90 523.86 0.00 0.00 0.00 0.00 9.70 0.00
November 1864.39 09-NOV-16:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 1.16 0.00
December 1701.11 23-DEC-16:01 378.00 177.90 523.86 0.00 0.00 0.00 0.00 0.00 18.52
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1701.11   378.00 150.94 469.67 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1924.95   970.20 479.78 885.15 0.00 0.00 0.00 0.00 41.03 18.52



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 31715.93 31-JAN-23:56 188921.38 7219.46 47235.32 0.00 0.00 0.00 0.00 0.00 268.76
February 32423.09 15-FEB-23:57 80966.30 3094.06 20243.71 0.00 0.00 0.00 0.00 0.00 299.94
March 31224.39 06-MAR-05:33 161932.61 4125.41 13495.81 0.00 0.00 0.00 0.00 0.00 285.38
April 31628.14 10-APR-22:40 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 257.53
May 22834.90 31-MAY-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 57.52 0.00
June 23624.35 15-JUN-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 118.64 0.00
July 23302.86 26-JUL-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 64.45 0.00
August 23491.52 07-AUG-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 101.10 0.00
September 22133.37 22-SEP-22:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 12.98 0.00
October 23528.26 25-OCT-04:07 80966.30 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 223.54
November 31188.99 15-NOV-23:33 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 292.72
December 31123.70 11-DEC-24:00 134943.84 5156.76 33739.51 0.00 0.00 0.00 0.00 0.00 296.04
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 22133.37   26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 32423.09   269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 118.64 299.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 33452.42 31-JAN-23:56 188921.38 7219.46 47235.32 0.00 0.00 0.00 0.00 0.00 270.06
February 34429.07 15-FEB-23:57 80966.30 3094.06 20243.71 0.00 0.00 0.00 0.00 0.00 302.44
March 41485.29 17-MAR-04:10 269887.68 6875.68 22493.01 0.00 0.00 0.00 0.00 0.00 284.99
April 33198.84 10-APR-22:40 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 257.94
May 24215.24 31-MAY-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 57.52 0.00
June 24968.40 15-JUN-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 108.54 0.00
July 24677.13 26-JUL-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 64.45 0.00
August 24855.02 07-AUG-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 101.10 0.00
September 23407.56 22-SEP-22:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 12.98 0.00
October 24427.14 25-OCT-05:30 62973.79 4125.41 16869.76 0.00 0.00 0.00 0.00 0.00 265.29
November 34719.95 19-NOV-23:56 239900.16 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 305.84
December 33070.92 11-DEC-24:00 134943.84 5156.76 33739.51 0.00 0.00 0.00 0.00 0.00 298.65
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 23407.56   26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 41485.29   269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 108.54 305.84



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 35265.66 07-JAN-09:28 8005.68 4843.69 149128.56 112464.16 0.00 0.00 0.00 0.00 287.15
February 36234.04 28-FEB-06:44 18679.92 4843.69 125511.30 74976.11 0.00 0.00 0.00 0.00 263.88
March 34265.88 25-MAR-06:36 13342.80 3632.77 149128.56 112464.16 0.00 0.00 0.00 0.00 257.65
April 33388.45 10-APR-22:40 24017.04 3632.77 149128.56 37488.05 0.00 0.00 0.00 0.00 237.16
May 30390.24 21-MAY-10:40 1601.14 726.55 29825.71 37488.05 0.00 0.00 0.00 68.28 0.00
June 30978.20 18-JUN-10:40 1601.14 726.55 29825.71 37488.05 0.00 0.00 0.00 105.06 0.00
July 31125.63 02-JUL-10:40 1601.14 726.55 29825.71 37488.05 0.00 0.00 0.00 101.94 0.00
August 31022.49 06-AUG-10:50 800.57 363.28 14912.86 18744.03 0.00 0.00 0.00 98.79 0.00
September 30629.34 17-SEP-10:40 1601.14 726.55 29825.71 37488.05 0.00 0.00 0.00 68.49 0.00
October 30051.23 05-OCT-10:40 1067.42 605.46 29825.71 37488.05 0.00 0.00 0.00 44.90 0.00
November 34879.55 16-NOV-08:24 10674.24 4843.69 149128.56 149952.21 0.00 0.00 0.00 0.00 279.91
December 38375.89 27-DEC-11:51 4269.70 2421.85 119302.85 149952.21 0.00 0.00 0.00 0.00 294.37
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 30051.23   800.57 363.28 14912.86 18744.03 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38375.89   24017.04 4843.69 149128.56 149952.21 0.00 0.00 0.00 105.06 294.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3775.47 02-JAN-00:33 7186.32 1581.01 0.00 0.00 0.00 0.00 0.00 0.00 235.12
February 3678.03 05-FEB-00:17 5589.36 2371.52 0.00 0.00 0.00 0.00 0.00 0.00 215.34
March 4215.58 17-MAR-03:44 23954.40 2635.02 0.00 0.00 0.00 0.00 0.00 0.00 230.41
April 5114.38 30-APR-13:00 532.32 527.00 0.00 0.00 0.00 0.00 0.00 66.23 0.00
May 6045.78 30-MAY-15:02 7984.80 3952.54 0.00 0.00 0.00 0.00 0.00 125.38 0.00
June 6869.13 15-JUN-18:03 11178.72 12648.11 0.00 0.00 0.00 0.00 0.00 143.44 0.00
July 7016.23 03-JUL-14:30 798.48 658.76 0.00 0.00 0.00 0.00 0.00 162.42 0.00
August 6858.41 07-AUG-15:03 7984.80 3952.54 0.00 0.00 0.00 0.00 0.00 137.67 0.00
September 6544.93 20-SEP-15:03 7984.80 3952.54 0.00 0.00 0.00 0.00 0.00 112.86 0.00
October 6189.78 03-OCT-13:30 532.32 658.76 0.00 0.00 0.00 0.00 0.00 93.86 0.00
November 3930.51 26-NOV-00:14 13041.84 5533.55 0.00 0.00 0.00 0.00 0.00 0.00 237.51
December 3536.94 30-DEC-10:29 7984.80 7905.07 0.00 0.00 0.00 0.00 0.00 0.00 233.17
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 3536.94   532.32 527.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7016.23   23954.40 12648.11 0.00 0.00 0.00 0.00 0.00 162.42 237.51



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.391960E+12 254868.63 26-JAN-20:49 0.488058E+12 441915.32 21-JAN-23:00
February 0.363791E+12 272887.96 06-FEB-20:10 0.419068E+12 415108.00 02-FEB-19:30
March 0.413908E+12 296573.83 14-MAR-18:10 0.438537E+12 396407.70 01-MAR-19:40
April 0.474905E+12 354674.04 19-APR-19:19 0.395346E+12 349889.22 10-APR-16:00
May 0.563893E+12 384067.05 19-MAY-19:10 0.387873E+12 347076.51 01-MAY-17:40
June 0.618819E+12 413212.08 05-JUN-19:10 0.364103E+12 319653.96 08-JUN-17:19
July 0.674194E+12 416814.12 25-JUL-19:10 0.369527E+12 316679.48 03-JUL-17:10
August 0.635053E+12 410466.14 04-AUG-19:19 0.369877E+12 316821.37 31-AUG-17:10
September 0.573611E+12 385256.26 22-SEP-19:19 0.364707E+12 319436.01 29-SEP-17:19
October 0.491342E+12 380386.93 03-OCT-19:00 0.391479E+12 347117.52 31-OCT-17:40
November 0.400454E+12 301512.76 09-NOV-20:00 0.426542E+12 417936.25 27-NOV-19:30
December 0.391194E+12 249254.54 06-DEC-20:10 0.486019E+12 451554.94 18-DEC-21:49
             
Annual Sum or Average 0.599312E+13     0.490114E+13    
Minimum of Months 0.363791E+12 249254.54   0.364103E+12 316679.48  
Maximum of Months 0.674194E+12 416814.12   0.488058E+12 451554.94  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.654470E+11 0.238585E+11 0.148212E+12 0.553309E+11 0.472598E+11 0.845661E+10 0.00 0.113613E+11 0.00 0.00 0.191094E+11 0.770402E+10 0.00
February 0.589941E+11 0.204104E+11 0.133859E+12 0.499764E+11 0.417046E+11 0.922705E+10 0.00 0.238075E+11 0.00 0.00 0.141537E+11 0.696171E+10 0.00
March 0.652284E+11 0.209758E+11 0.148223E+12 0.553337E+11 0.461421E+11 0.114630E+11 0.00 0.403665E+11 0.00 0.00 0.132818E+11 0.770276E+10 0.00
April 0.628662E+11 0.186678E+11 0.143397E+12 0.535455E+11 0.485914E+11 0.156889E+11 0.00 0.108445E+12 0.00 0.00 0.112123E+11 0.746487E+10 0.00
May 0.649547E+11 0.178892E+11 0.148223E+12 0.553320E+11 0.552393E+11 0.187007E+11 0.00 0.175666E+12 0.00 0.00 0.149343E+11 0.770424E+10 0.00
June 0.627939E+11 0.166101E+11 0.143446E+12 0.535482E+11 0.594682E+11 0.197178E+11 0.00 0.231373E+12 0.00 0.00 0.192805E+11 0.745687E+10 0.00
July 0.647873E+11 0.174721E+11 0.148174E+12 0.553291E+11 0.620224E+11 0.210605E+11 0.00 0.270882E+12 0.00 0.00 0.214183E+11 0.771238E+10 0.00
August 0.650572E+11 0.186678E+11 0.148234E+12 0.553337E+11 0.621478E+11 0.205544E+11 0.00 0.234206E+12 0.00 0.00 0.178023E+11 0.770435E+10 0.00
September 0.629931E+11 0.195762E+11 0.143408E+12 0.535457E+11 0.590797E+11 0.192066E+11 0.00 0.190406E+12 0.00 0.00 0.127684E+11 0.746622E+10 0.00
October 0.653122E+11 0.219305E+11 0.148201E+12 0.553308E+11 0.554219E+11 0.166280E+11 0.00 0.107001E+12 0.00 0.00 0.852904E+10 0.770291E+10 0.00
November 0.632978E+11 0.226443E+11 0.143462E+12 0.535468E+11 0.491732E+11 0.106225E+11 0.00 0.327012E+11 0.00 0.00 0.125192E+11 0.744854E+10 0.00
December 0.653599E+11 0.242107E+11 0.148174E+12 0.553296E+11 0.483219E+11 0.808571E+10 0.00 0.862815E+10 0.00 0.00 0.201634E+11 0.771224E+10 0.00
                           
Annual Sum or Average 0.767092E+12 0.242914E+12 0.174501E+13 0.651482E+12 0.634572E+12 0.179412E+12 0.00 0.143484E+13 0.00 0.00 0.185173E+12 0.907411E+11 0.00
Minimum of Months 0.589941E+11 0.166101E+11 0.133859E+12 0.499764E+11 0.417046E+11 0.808571E+10 0.00 0.862815E+10 0.00 0.00 0.852904E+10 0.696171E+10 0.00
Maximum of Months 0.654470E+11 0.242107E+11 0.148234E+12 0.553337E+11 0.621478E+11 0.210605E+11 0.00 0.270882E+12 0.00 0.00 0.214183E+11 0.771238E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.706266E+11 0.00 0.265514E+12 0.00 0.00
February 0.137204E+12 0.00 0.421249E+11 0.00 0.239739E+12 0.00 0.00
March 0.152024E+12 0.00 0.272596E+11 0.00 0.259254E+12 0.00 0.00
April 0.146956E+12 0.00 0.825313E+10 0.00 0.240137E+12 0.00 0.00
May 0.151978E+12 0.00 0.619206E+09 0.00 0.235275E+12 0.00 0.00
June 0.147114E+12 0.00 77712501.15 0.00 0.216912E+12 0.00 0.00
July 0.151820E+12 0.00 73199593.94 0.00 0.217633E+12 0.00 0.00
August 0.152039E+12 0.00 92449919.67 0.00 0.217746E+12 0.00 0.00
September 0.146971E+12 0.00 0.767954E+09 0.00 0.216968E+12 0.00 0.00
October 0.151903E+12 0.00 0.423069E+10 0.00 0.235345E+12 0.00 0.00
November 0.147091E+12 0.00 0.392705E+11 0.00 0.240180E+12 0.00 0.00
December 0.151820E+12 0.00 0.749945E+11 0.00 0.259204E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.268390E+12 0.00 0.284391E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 73199593.94 0.00 0.216912E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.749945E+11 0.00 0.265514E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 62892.57 02-JAN-20:10 15448.40 01-JAN-00:10 89475.41 02-JAN-07:10 39726.11 02-JAN-07:19 36368.83 09-JAN-22:49 6600.30 12-JAN-16:10 0.00 01-JAN-00:10
February 62892.57 01-FEB-20:10 15448.40 01-FEB-00:10 89475.41 01-FEB-07:10 39726.11 01-FEB-07:19 40938.68 08-FEB-21:19 7381.78 20-FEB-16:10 0.00 01-FEB-00:10
March 62892.57 01-MAR-20:10 15448.40 01-MAR-00:10 89475.41 01-MAR-07:10 39726.11 13-MAR-06:19 36144.00 20-MAR-22:30 7505.52 22-MAR-15:30 0.00 01-MAR-00:10
April 62892.57 03-APR-19:10 15448.40 01-APR-00:10 89475.41 03-APR-06:10 39726.11 04-APR-06:19 37803.09 21-APR-21:10 8360.94 28-APR-19:10 0.00 01-APR-00:10
May 62892.57 01-MAY-19:10 15448.40 01-MAY-00:10 89475.41 01-MAY-06:10 39725.67 03-MAY-06:19 42287.52 31-MAY-21:10 8462.84 19-MAY-18:10 0.00 01-MAY-00:10
June 62892.57 01-JUN-19:10 15448.40 01-JUN-00:10 89475.41 01-JUN-06:10 39724.49 01-JUN-06:19 45740.26 15-JUN-21:10 8609.49 05-JUN-19:10 0.00 01-JUN-00:10
July 62892.57 03-JUL-19:19 15448.40 01-JUL-00:10 89475.41 03-JUL-06:10 39725.08 19-JUL-06:19 47887.56 26-JUL-21:10 8638.43 18-JUL-20:49 0.00 01-JUL-00:10
August 62892.57 01-AUG-19:10 15448.40 01-AUG-00:10 89475.41 01-AUG-06:10 39726.11 14-AUG-06:19 50591.54 07-AUG-21:10 8595.97 01-AUG-20:00 0.00 01-AUG-00:10
September 62892.57 01-SEP-19:10 15448.40 01-SEP-00:10 89475.41 01-SEP-06:10 39726.11 25-SEP-06:19 49298.70 22-SEP-21:10 8557.53 18-SEP-19:10 0.00 01-SEP-00:10
October 62892.57 02-OCT-19:10 15448.40 01-OCT-00:10 89475.41 02-OCT-06:10 39726.11 02-OCT-06:19 48560.58 05-OCT-21:10 8496.33 03-OCT-19:00 0.00 01-OCT-00:10
November 62892.57 01-NOV-19:10 15448.40 01-NOV-00:10 89475.41 01-NOV-06:10 39726.11 01-NOV-06:19 45508.09 15-NOV-22:00 8192.89 03-NOV-15:50 0.00 01-NOV-00:10
December 62892.57 01-DEC-20:10 15448.40 01-DEC-00:10 89475.41 01-DEC-07:10 39726.11 11-DEC-07:19 36719.63 18-DEC-21:49 5987.04 23-DEC-14:00 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 62892.57   15448.40   89475.41   39724.49   36144.00   5987.04   0.00  
Maximum of Months 62892.57   15448.40   89475.41   39726.11   50591.54   8638.43   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 51245.69 03-JAN-14:00 0.00 0.00 9938.94 01-JAN-00:10 4738.44 12-JAN-19:10 0.00
February 72211.41 20-FEB-16:10 0.00 0.00 9938.94 01-FEB-00:20 4738.12 16-FEB-19:10 0.00
March 75046.59 22-MAR-15:09 0.00 0.00 9938.94 01-MAR-00:10 4738.38 14-MAR-06:49 0.00
April 114379.47 21-APR-18:10 0.00 0.00 9938.94 01-APR-00:10 4738.63 06-APR-18:10 0.00
May 134776.07 19-MAY-18:19 0.00 0.00 9938.94 02-MAY-00:20 4738.59 25-MAY-18:10 0.00
June 167567.16 14-JUN-18:10 0.00 0.00 9938.94 01-JUN-00:10 4738.66 08-JUN-18:10 0.00
July 167034.93 26-JUL-18:10 0.00 0.00 9938.94 01-JUL-00:10 4738.58 20-JUL-18:10 0.00
August 155823.93 04-AUG-18:10 0.00 0.00 9938.94 01-AUG-00:10 4738.58 24-AUG-18:10 0.00
September 135124.49 20-SEP-15:20 0.00 0.00 9938.94 01-SEP-08:20 4738.75 07-SEP-18:10 0.00
October 129899.53 04-OCT-18:10 0.00 0.00 9938.94 01-OCT-09:50 4738.57 05-OCT-18:10 0.00
November 77018.79 03-NOV-15:50 0.00 0.00 9938.94 01-NOV-00:10 4738.29 17-NOV-07:10 0.00
December 33154.39 23-DEC-14:00 0.00 0.00 9938.94 01-DEC-00:30 4738.15 28-DEC-07:10 0.00
                   
Annual Sum or Average     0.00 0.00         0.00
Minimum of Months 33154.39   0.00 0.00 9938.94   4738.12   0.00
Maximum of Months 167567.16   0.00 0.00 9938.94   4738.75   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 254868.63 26-JAN-20:49 62892.57 88772.42 15448.40 32159.77 33499.00 4389.14 0.00 1300.49 0.00
February 272887.96 06-FEB-20:10 62892.57 88772.42 15448.40 32151.31 22652.94 6123.83 0.00 38428.59 0.00
March 296573.83 14-MAR-18:10 55920.94 79417.81 15448.40 31837.02 24074.01 7380.55 0.00 74880.82 0.00
April 354674.04 19-APR-19:19 62892.57 88772.42 15448.40 32159.77 28239.19 7918.21 0.00 102992.14 0.00
May 384067.05 19-MAY-19:10 62892.57 88772.42 15448.40 32151.31 34756.14 8441.51 0.00 126244.94 0.00
June 413212.08 05-JUN-19:10 62892.57 88772.42 15448.40 32150.87 34715.41 8609.49 0.00 154282.50 0.00
July 416814.12 25-JUL-19:10 62892.57 88772.42 15448.40 32150.62 38655.68 8348.76 0.00 155051.09 0.00
August 410466.14 04-AUG-19:19 62892.57 88772.42 15448.40 32159.77 41025.11 8303.98 0.00 146090.61 0.00
September 385256.26 22-SEP-19:19 62892.57 88772.42 15448.40 32159.77 38427.66 8309.66 0.00 123457.06 0.00
October 380386.93 03-OCT-19:00 62892.57 88772.42 15448.40 32159.77 35808.93 8496.33 0.00 129776.14 0.00
November 301512.76 09-NOV-20:00 62892.57 88772.42 15448.40 32159.77 29725.21 7257.47 0.00 59164.46 0.00
December 249254.54 06-DEC-20:10 62892.57 88772.42 15448.40 32151.31 26141.90 4569.37 0.00 3339.27 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 249254.54   55920.94 79417.81 15448.40 31837.02 22652.94 4389.14 0.00 1300.49 0.00
Maximum of Months 416814.12   62892.57 88772.42 15448.40 32159.77 41025.11 8609.49 0.00 155051.09 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 191594.86 03-JAN-01:10 0.00 255618.32 04-JAN-21:30 0.00
February 104248.32 01-FEB-18:10 0.00 186468.17 11-FEB-05:19 0.00 256972.59 27-FEB-21:30 0.00
March 104248.32 01-MAR-18:10 0.00 179492.34 31-MAR-04:10 0.00 248249.89 28-MAR-20:49 0.00
April 104248.32 01-APR-17:10 0.00 140457.05 12-APR-04:40 0.00 247428.25 10-APR-20:00 0.00
May 104248.32 01-MAY-17:10 0.00 53882.71 02-MAY-05:30 0.00 242828.19 01-MAY-17:40 0.00
June 104248.32 01-JUN-17:10 0.00 5233.45 01-JUN-08:09 0.00 218918.91 01-JUN-19:10 0.00
July 104248.32 01-JUL-17:10 0.00 5796.36 05-JUL-08:09 0.00 212834.69 03-JUL-20:30 0.00
August 104248.32 01-AUG-17:10 0.00 7283.87 24-AUG-08:09 0.00 212989.50 31-AUG-20:40 0.00
September 104248.32 01-SEP-17:10 0.00 72313.48 25-SEP-04:00 0.00 220732.35 30-SEP-21:40 0.00
October 104248.32 02-OCT-17:10 0.00 91486.65 25-OCT-04:00 0.00 243495.20 31-OCT-20:19 0.00
November 104248.32 01-NOV-17:10 0.00 171303.53 30-NOV-00:30 0.00 246599.43 28-NOV-18:30 0.00
December 104248.32 01-DEC-18:10 0.00 181612.06 18-DEC-04:19 0.00 253960.68 22-DEC-21:40 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 5233.45   0.00 212834.69   0.00
Maximum of Months 104248.32   0.00 191594.86   0.00 256972.59   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 31.83 25.26 31.83 25.26
February 0.00 0.00 0.00 0.00 21.00 25.25 21.00 25.25
March 0.00 0.00 0.00 0.00 11.33 25.08 11.33 25.08
April 0.00 0.00 0.00 0.00 4.50 25.16 4.50 25.16
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 1.17 24.84 1.17 24.84
November 0.00 0.00 0.00 0.00 21.33 25.03 21.33 25.03
December 0.00 0.00 0.00 0.00 32.33 25.06 32.33 25.06
                 
Annual Sum or Average 0.00   0.00   123.50 25.14 123.50 25.14
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 32.33 25.26 32.33 25.26



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 21.72 0.33 21.72
May 0.00 0.00 0.00 0.00 0.67 21.77 0.67 21.77
June 0.00 0.00 0.00 0.00 3.00 21.88 3.00 21.88
July 0.00 0.00 0.00 0.00 0.50 21.72 0.50 21.72
August 0.00 0.00 0.00 0.00 1.83 21.77 1.83 21.77
September 0.00 0.00 0.00 0.00 1.67 21.84 1.67 21.84
October 0.00 0.00 0.00 0.00 0.83 21.82 0.83 21.82
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   8.83 21.82 8.83 21.82
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.00 21.88 3.00 21.88



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.00 21.73 1.00 21.73
June 0.00 0.00 0.00 0.00 3.33 21.89 3.33 21.89
July 0.00 0.00 0.00 0.00 0.50 21.72 0.50 21.72
August 0.00 0.00 0.00 0.00 1.00 21.72 1.00 21.72
September 0.00 0.00 0.00 0.00 0.33 21.68 0.33 21.68
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   6.17 21.81 6.17 21.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.33 21.89 3.33 21.89



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.33 21.71 0.33 21.71
June 0.00 0.00 0.00 0.00 1.67 21.76 1.67 21.76
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.17 21.75 2.17 21.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.67 21.76 1.67 21.76



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 21.78 0.33 21.78
May 0.00 0.00 0.00 0.00 0.50 21.76 0.50 21.76
June 0.00 0.00 0.00 0.00 1.67 21.79 1.67 21.79
July 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
August 0.00 0.00 0.00 0.00 0.33 21.71 0.33 21.71
September 0.00 0.00 0.00 0.00 0.50 21.74 0.50 21.74
October 0.00 0.00 0.00 0.00 0.33 21.74 0.33 21.74
November 0.00 0.00 0.00 0.00 0.17 21.83 0.17 21.83
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.00 21.76 4.00 21.76
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.67 21.83 1.67 21.83



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 21.77 0.33 21.77
May 0.00 0.00 0.00 0.00 0.50 21.78 0.50 21.78
June 0.00 0.00 0.00 0.00 2.00 21.79 2.00 21.79
July 0.00 0.00 0.00 0.00 0.33 21.68 0.33 21.68
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.17 21.77 3.17 21.77
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.00 21.79 2.00 21.79



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 21.76 0.33 21.76
May 0.00 0.00 0.00 0.00 0.67 21.83 0.67 21.83
June 0.00 0.00 0.00 0.00 5.00 21.88 5.00 21.88
July 0.00 0.00 0.00 0.00 1.00 21.80 1.00 21.80
August 0.00 0.00 0.00 0.00 2.67 21.80 2.67 21.80
September 0.00 0.00 0.00 0.00 2.50 21.84 2.50 21.84
October 0.00 0.00 0.00 0.00 1.00 21.80 1.00 21.80
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   13.17 21.84 13.17 21.84
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.00 21.88 5.00 21.88



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.00 21.77 1.00 21.77
June 0.00 0.00 0.00 0.00 5.83 21.88 5.83 21.88
July 0.00 0.00 0.00 0.00 1.33 21.77 1.33 21.77
August 0.00 0.00 0.00 0.00 1.83 21.75 1.83 21.75
September 0.00 0.00 0.00 0.00 0.50 21.70 0.50 21.70
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   10.50 21.82 10.50 21.82
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.83 21.88 5.83 21.88



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.83 21.77 0.83 21.77
July 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
August 0.00 0.00 0.00 0.00 0.83 21.76 0.83 21.76
September 0.00 0.00 0.00 0.00 3.50 21.87 3.50 21.87
October 0.00 0.00 0.00 0.00 3.50 21.96 3.50 21.96
November 0.00 0.00 0.00 0.00 0.33 22.00 0.33 22.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   9.17 21.89 9.17 21.89
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.50 22.00 3.50 22.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.67 24.80 1.67 24.80
February 0.00 0.00 0.00 0.00 0.67 24.83 0.67 24.83
March 0.00 0.00 0.00 0.00 0.67 24.87 0.67 24.87
April 0.00 0.00 0.00 0.00 0.17 24.93 0.17 24.93
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.33 24.57 0.33 24.57
December 0.00 0.00 0.00 0.00 0.33 24.72 0.33 24.72
                 
Annual Sum or Average 0.00   0.00   3.83 24.80 3.83 24.80
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.67 24.93 1.67 24.93



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 2.17 24.88 2.17 24.88
February 0.00 0.00 0.00 0.00 1.50 24.81 1.50 24.81
March 0.00 0.00 0.00 0.00 0.67 24.97 0.67 24.97
April 0.00 0.00 0.00 0.00 1.00 24.69 1.00 24.69
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.17 24.64 0.17 24.64
November 0.00 0.00 0.00 0.00 1.00 24.67 1.00 24.67
December 0.00 0.00 0.00 0.00 2.00 24.66 2.00 24.66
                 
Annual Sum or Average 0.00   0.00   8.50 24.77 8.50 24.77
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.17 24.97 2.17 24.97



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 36.67 25.17 36.67 25.17
February 0.00 0.00 0.00 0.00 24.00 25.20 24.00 25.20
March 0.00 0.00 0.00 0.00 14.00 25.14 14.00 25.14
April 0.00 0.00 0.00 0.00 5.50 25.25 5.50 25.25
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 1.33 24.88 1.33 24.88
November 0.00 0.00 0.00 0.00 29.83 25.12 29.83 25.12
December 0.00 0.00 0.00 0.00 40.50 25.14 40.50 25.14
                 
Annual Sum or Average 0.00   0.00   151.83 25.15 151.83 25.15
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 40.50 25.25 40.50 25.25



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 580.17 23.89 0.00 23.89 0.00 23.89
February 665.17 23.39 0.00 23.39 0.00 23.39
March 744.00 22.63 0.00 22.63 0.00 22.63
April 720.00 22.71 0.00 22.71 0.00 22.71
May 733.83 23.02 12.00 23.02 12.00 23.03
June 595.17 23.26 82.50 23.30 65.50 23.32
July 384.67 23.93 634.00 23.92 364.67 23.93
August 219.00 24.00 643.17 23.98 219.00 23.99
September 201.33 24.00 501.33 24.00 201.33 24.00
October 98.83 24.00 308.50 24.00 45.17 24.00
November 396.00 24.00 18.83 24.00 0.00 24.00
December 550.83 23.99 0.00 23.99 0.00 23.99
             
Annual Sum or Average 5889.00 23.39 2200.33 23.54 907.67 23.58
Minimum of Months 98.83 22.63 0.00 22.63 0.00 22.63
Maximum of Months 744.00 24.00 643.17 24.00 364.67 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 606.50 22.03 38.17 22.09 11.00 22.07
February 539.17 22.29 17.50 22.29 8.50 22.27
March 609.17 22.53 6.00 22.51 6.00 22.50
April 390.67 23.10 76.83 23.24 0.00 23.24
May 181.00 23.46 320.17 23.79 14.50 23.80
June 74.17 23.87 614.00 23.97 54.00 23.97
July 351.00 23.98 744.00 23.99 351.00 23.98
August 227.67 23.90 728.50 23.95 227.67 23.94
September 241.33 23.82 610.50 23.93 214.00 23.92
October 268.33 23.04 360.00 23.56 59.50 23.58
November 484.17 22.36 88.00 22.55 11.83 22.52
December 623.50 21.88 45.00 21.83 42.83 21.78
             
Annual Sum or Average 4596.67 22.71 3648.67 23.24 1000.83 23.29
Minimum of Months 74.17 21.88 6.00 21.83 0.00 21.78
Maximum of Months 623.50 23.98 744.00 23.99 351.00 23.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 735.83 22.67 0.00 22.67 0.00 22.67
February 666.83 22.87 0.00 22.87 0.00 22.87
March 732.17 23.02 0.00 23.02 0.00 23.02
April 534.83 23.39 22.17 23.42 0.00 23.42
May 245.00 23.52 210.50 23.70 18.67 23.71
June 114.00 23.84 433.83 23.92 61.00 23.92
July 375.33 23.95 732.67 23.91 375.33 23.92
August 254.83 23.91 673.83 23.89 253.17 23.90
September 262.83 23.90 539.17 23.90 237.50 23.91
October 303.33 23.41 235.33 23.60 73.83 23.62
November 630.33 23.03 3.83 23.04 0.00 23.04
December 744.00 22.51 0.00 22.51 0.00 22.51
             
Annual Sum or Average 5599.33 23.13 2851.33 23.39 1019.50 23.45
Minimum of Months 114.00 22.51 0.00 22.51 0.00 22.51
Maximum of Months 744.00 23.95 732.67 23.92 375.33 23.92



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.96 0.00 21.96 0.00 21.96
February 672.00 22.25 0.00 22.25 0.00 22.25
March 744.00 22.61 0.00 22.61 0.00 22.61
April 650.17 23.48 0.00 23.48 0.00 23.48
May 348.00 23.87 143.17 23.91 1.17 23.91
June 105.33 24.00 341.33 24.00 12.17 24.00
July 232.67 24.00 733.50 24.00 232.67 24.00
August 117.50 23.98 631.17 23.99 117.50 23.99
September 213.67 23.94 479.50 23.98 144.00 23.98
October 506.83 23.51 123.33 23.60 14.67 23.61
November 719.50 22.66 0.00 22.66 0.00 22.66
December 744.00 21.75 0.00 21.75 0.00 21.75
             
Annual Sum or Average 5797.67 22.79 2452.00 23.15 522.17 23.20
Minimum of Months 105.33 21.75 0.00 21.75 0.00 21.75
Maximum of Months 744.00 24.00 733.50 24.00 232.67 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.09 40.17 21.08 40.17 21.08
February 672.00 21.24 31.33 21.23 31.33 21.22
March 744.00 21.44 13.00 21.43 13.00 21.43
April 720.00 22.28 0.00 22.28 0.00 22.28
May 718.33 22.95 1.50 22.95 1.50 22.95
June 437.50 23.36 47.50 23.39 11.33 23.39
July 312.17 23.36 407.50 23.47 241.33 23.46
August 436.83 23.17 191.33 23.25 121.33 23.26
September 617.50 23.00 147.50 23.03 140.67 23.04
October 726.00 22.41 14.33 22.42 14.33 22.43
November 720.00 21.53 0.00 21.53 0.00 21.53
December 744.00 21.04 51.83 21.04 51.83 21.04
             
Annual Sum or Average 7592.33 22.09 946.00 22.20 666.83 22.25
Minimum of Months 312.17 21.04 0.00 21.04 0.00 21.04
Maximum of Months 744.00 23.36 407.50 23.47 241.33 23.46



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 201.83 24.25 736.17 24.07 201.83 24.10
February 174.67 24.18 665.83 24.04 174.67 24.07
March 191.83 24.08 738.33 24.01 191.67 24.02
April 236.33 24.02 716.67 24.01 236.33 24.01
May 383.17 24.00 744.00 24.00 383.17 24.00
June 523.33 24.00 720.00 24.00 523.33 24.00
July 737.17 24.00 744.00 24.00 737.17 24.00
August 682.00 24.00 744.00 24.00 682.00 24.00
September 608.33 24.00 720.00 24.00 608.33 24.00
October 412.00 24.00 744.00 23.99 412.00 23.99
November 205.00 24.11 715.50 24.02 205.00 24.04
December 172.17 24.24 732.67 24.06 172.00 24.09
             
Annual Sum or Average 4527.83 24.04 8721.17 24.01 4527.50 24.02
Minimum of Months 172.17 24.00 665.83 23.99 172.00 23.99
Maximum of Months 737.17 24.25 744.00 24.07 737.17 24.10



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 629.00 22.24 46.17 22.35 0.00 22.35
February 568.00 22.36 38.00 22.46 0.00 22.46
March 671.17 22.39 6.33 22.40 0.00 22.40
April 514.00 22.58 42.33 22.67 0.00 22.67
May 392.50 22.69 212.17 22.97 63.67 23.01
June 231.17 23.16 455.00 23.43 139.67 23.46
July 501.00 23.49 710.00 23.42 494.67 23.45
August 396.33 23.42 695.33 23.43 381.83 23.44
September 362.00 23.45 636.17 23.55 325.17 23.55
October 352.17 22.84 388.33 23.27 135.83 23.29
November 483.67 22.43 130.67 22.75 0.00 22.75
December 648.67 22.12 27.67 22.19 0.17 22.19
             
Annual Sum or Average 5749.67 22.67 3388.17 22.99 1541.00 23.07
Minimum of Months 231.17 22.12 6.33 22.19 0.00 22.19
Maximum of Months 671.17 23.49 710.00 23.55 494.67 23.55



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 692.17 23.01 0.00 23.01 0.00 23.01
February 629.00 23.15 2.00 23.15 0.00 23.15
March 673.67 23.16 6.50 23.16 0.00 23.16
April 453.50 23.28 53.00 23.36 0.00 23.36
May 256.50 23.36 241.00 23.61 59.33 23.63
June 174.33 23.72 464.67 23.84 125.33 23.84
July 505.83 23.86 730.17 23.81 505.83 23.83
August 389.17 23.83 710.17 23.80 388.67 23.81
September 345.33 23.87 622.33 23.86 337.83 23.86
October 251.67 23.51 374.67 23.71 137.17 23.73
November 502.50 23.20 28.83 23.24 0.00 23.24
December 733.83 22.94 0.00 22.94 0.00 22.94
             
Annual Sum or Average 5607.50 23.32 3233.33 23.51 1554.17 23.56
Minimum of Months 174.33 22.94 0.00 22.94 0.00 22.94
Maximum of Months 733.83 23.87 730.17 23.86 505.83 23.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.26 168.83 21.18 168.83 21.12
February 672.00 21.37 124.00 21.31 124.00 21.27
March 744.00 21.46 65.00 21.42 65.00 21.39
April 702.33 21.59 0.83 21.59 0.83 21.59
May 676.17 21.53 3.17 21.54 0.00 21.54
June 615.50 21.47 13.33 21.51 0.00 21.51
July 593.83 21.33 48.50 21.47 4.67 21.48
August 607.33 21.36 35.83 21.47 1.50 21.47
September 585.33 21.35 38.00 21.47 2.50 21.47
October 680.33 21.48 14.83 21.52 3.33 21.51
November 712.67 21.43 86.50 21.36 86.50 21.31
December 744.00 21.21 275.83 21.13 275.83 21.08
             
Annual Sum or Average 8077.50 21.40 874.67 21.39 733.00 21.36
Minimum of Months 585.33 21.21 0.83 21.13 0.00 21.08
Maximum of Months 744.00 21.59 275.83 21.59 275.83 21.59



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.90 400.83 20.82 400.83 20.78
February 672.00 21.07 289.83 21.00 289.83 20.96
March 744.00 21.27 126.67 21.21 126.67 21.16
April 709.50 21.55 7.50 21.54 7.50 21.54
May 682.33 21.54 2.83 21.55 0.00 21.55
June 620.33 21.49 14.33 21.53 0.00 21.53
July 597.33 21.34 44.00 21.47 4.33 21.48
August 629.17 21.42 21.17 21.48 1.67 21.48
September 627.33 21.45 11.33 21.48 3.00 21.48
October 720.50 21.47 6.83 21.47 5.17 21.47
November 720.00 21.20 176.67 21.12 176.67 21.07
December 744.00 20.83 578.17 20.79 578.17 20.77
             
Annual Sum or Average 8210.50 21.28 1680.17 21.22 1593.83 21.16
Minimum of Months 597.33 20.83 2.83 20.79 0.00 20.77
Maximum of Months 744.00 21.55 578.17 21.55 578.17 21.55



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.96 333.00 20.92 333.00 20.90
February 672.00 21.04 242.33 21.01 242.33 20.98
March 744.00 21.15 115.33 21.13 115.33 21.11
April 720.00 21.36 3.50 21.36 3.50 21.36
May 744.00 21.52 0.00 21.52 0.00 21.52
June 720.00 21.64 0.00 21.64 0.00 21.64
July 744.00 21.64 5.33 21.64 5.33 21.64
August 744.00 21.57 0.33 21.57 0.33 21.57
September 720.00 21.49 3.67 21.49 3.67 21.49
October 744.00 21.31 0.00 21.31 0.00 21.31
November 720.00 21.07 187.17 21.04 187.17 21.02
December 744.00 20.93 455.83 20.89 455.83 20.87
             
Annual Sum or Average 8760.00 21.31 1346.50 21.25 1346.50 21.21
Minimum of Months 672.00 20.93 0.00 20.89 0.00 20.87
Maximum of Months 744.00 21.64 455.83 21.64 455.83 21.64



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.29 162.50 21.22 162.50 21.17
February 672.00 21.46 102.17 21.41 102.17 21.37
March 744.00 21.56 62.17 21.52 62.17 21.49
April 703.67 21.68 1.83 21.68 1.83 21.68
May 673.17 21.58 1.17 21.58 0.00 21.58
June 578.00 21.37 5.00 21.38 0.00 21.38
July 555.50 21.21 15.33 21.27 2.17 21.27
August 570.67 21.26 7.83 21.28 1.50 21.28
September 555.83 21.28 7.83 21.30 0.83 21.31
October 674.83 21.50 5.17 21.50 4.83 21.50
November 719.50 21.50 92.17 21.42 92.17 21.37
December 744.00 21.23 279.00 21.16 279.00 21.12
             
Annual Sum or Average 7935.17 21.42 742.17 21.39 709.17 21.36
Minimum of Months 555.50 21.21 1.17 21.16 0.00 21.12
Maximum of Months 744.00 21.68 279.00 21.68 279.00 21.68



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.90 420.00 20.85 420.00 20.83
February 672.00 21.14 246.50 21.08 246.50 21.05
March 744.00 21.38 104.33 21.33 104.33 21.29
April 711.67 21.67 5.67 21.67 5.67 21.67
May 676.00 21.58 1.50 21.59 0.00 21.59
June 577.50 21.37 6.67 21.39 0.00 21.39
July 554.67 21.21 16.17 21.27 1.83 21.27
August 581.50 21.29 7.17 21.32 1.33 21.32
September 599.17 21.41 6.00 21.43 1.00 21.43
October 725.33 21.55 11.33 21.55 11.17 21.54
November 720.00 21.18 167.17 21.12 167.17 21.08
December 744.00 20.83 563.00 20.80 563.00 20.78
             
Annual Sum or Average 8049.83 21.29 1555.50 21.22 1522.00 21.17
Minimum of Months 554.67 20.83 1.50 20.80 0.00 20.78
Maximum of Months 744.00 21.67 563.00 21.67 563.00 21.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.79 0.00 21.79 0.00 21.79
February 672.00 22.14 0.00 22.14 0.00 22.14
March 744.00 22.46 0.00 22.46 0.00 22.46
April 696.67 23.33 0.00 23.33 0.00 23.33
May 428.00 23.77 126.83 23.80 33.00 23.81
June 195.33 23.96 312.83 23.96 75.50 23.96
July 460.50 23.97 727.50 23.97 460.50 23.97
August 327.67 23.90 608.00 23.93 327.67 23.92
September 367.33 23.90 485.00 23.93 285.83 23.94
October 599.00 23.48 157.83 23.53 97.17 23.53
November 720.00 22.67 0.00 22.67 0.00 22.67
December 744.00 21.56 0.00 21.56 0.00 21.56
             
Annual Sum or Average 6698.50 22.84 2418.00 23.13 1279.67 23.23
Minimum of Months 195.33 21.56 0.00 21.56 0.00 21.56
Maximum of Months 744.00 23.97 727.50 23.97 460.50 23.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.14 349.17 21.04 349.17 20.99
February 672.00 21.27 268.67 21.17 268.67 21.12
March 744.00 21.38 179.17 21.29 179.17 21.24
April 693.83 21.53 36.67 21.51 35.83 21.48
May 662.33 21.48 9.17 21.51 0.00 21.51
June 587.83 21.38 32.83 21.49 0.17 21.49
July 581.50 21.29 88.50 21.54 13.17 21.54
August 594.33 21.32 74.50 21.51 13.00 21.50
September 575.83 21.31 79.33 21.51 17.17 21.52
October 677.17 21.43 37.67 21.47 19.67 21.46
November 713.00 21.34 188.33 21.24 188.17 21.17
December 744.00 21.10 477.50 21.01 477.50 20.98
             
Annual Sum or Average 7989.83 21.33 1821.50 21.31 1561.67 21.26
Minimum of Months 575.83 21.10 9.17 21.01 0.00 20.98
Maximum of Months 744.00 21.53 477.50 21.54 477.50 21.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.76 607.83 20.72 607.83 20.70
February 672.00 20.95 434.50 20.87 434.50 20.84
March 744.00 21.16 293.50 21.07 293.50 21.02
April 704.33 21.49 48.67 21.46 48.67 21.43
May 669.33 21.49 8.67 21.51 0.00 21.51
June 590.33 21.40 32.50 21.50 0.17 21.50
July 583.33 21.30 81.17 21.53 11.67 21.54
August 609.67 21.36 59.00 21.49 13.83 21.49
September 612.17 21.38 52.17 21.48 23.33 21.48
October 717.83 21.40 38.33 21.40 33.50 21.39
November 720.00 21.06 361.17 20.97 361.17 20.93
December 744.00 20.70 707.00 20.69 707.00 20.69
             
Annual Sum or Average 8111.00 21.19 2724.50 21.13 2535.17 21.06
Minimum of Months 583.33 20.70 8.67 20.69 0.00 20.69
Maximum of Months 744.00 21.49 707.00 21.53 707.00 21.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 729.67 21.48 77.50 21.42 77.50 21.37
February 663.83 21.54 55.17 21.51 55.17 21.48
March 744.00 21.55 67.67 21.51 67.67 21.47
April 711.00 21.61 11.67 21.60 11.67 21.59
May 716.50 21.61 0.00 21.61 0.00 21.61
June 656.00 21.56 0.00 21.56 0.00 21.56
July 620.33 21.40 10.83 21.41 10.83 21.41
August 622.50 21.39 4.33 21.39 4.33 21.39
September 584.33 21.34 40.67 21.46 5.33 21.47
October 635.83 21.38 39.67 21.48 3.67 21.48
November 672.50 21.44 48.17 21.41 45.50 21.38
December 743.17 21.51 139.17 21.43 139.17 21.37
             
Annual Sum or Average 8099.67 21.49 494.83 21.48 420.83 21.46
Minimum of Months 584.33 21.34 0.00 21.39 0.00 21.37
Maximum of Months 744.00 21.61 139.17 21.61 139.17 21.61



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 699.00 22.50 0.67 22.50 0.00 22.50
February 598.00 22.62 6.17 22.63 0.00 22.63
March 597.67 22.73 10.00 22.75 0.00 22.75
April 324.83 22.82 111.67 23.08 0.00 23.08
May 169.33 23.17 399.00 23.55 62.83 23.58
June 144.00 23.79 590.83 23.74 135.00 23.76
July 502.17 23.82 741.00 23.72 502.17 23.75
August 389.67 23.77 717.67 23.67 389.00 23.70
September 363.50 23.61 600.50 23.62 326.83 23.64
October 350.83 22.98 339.83 23.32 136.17 23.37
November 600.67 22.65 33.00 22.71 0.00 22.71
December 724.00 22.45 0.00 22.45 0.00 22.45
             
Annual Sum or Average 5463.67 22.94 3550.33 23.23 1552.00 23.31
Minimum of Months 144.00 22.45 0.00 22.45 0.00 22.45
Maximum of Months 724.00 23.82 741.00 23.74 502.17 23.76



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 570.00 22.72 14.50 22.75 0.00 22.75
February 483.50 22.81 31.50 22.88 0.00 22.88
March 447.67 22.88 18.83 22.92 0.00 22.92
April 196.50 22.93 183.50 23.39 0.00 23.39
May 99.33 23.46 484.33 23.75 58.67 23.76
June 128.83 23.91 642.17 23.84 128.67 23.85
July 495.67 23.90 744.00 23.83 495.67 23.85
August 385.83 23.85 743.00 23.77 385.83 23.79
September 335.33 23.82 658.67 23.75 330.17 23.77
October 240.17 23.31 466.00 23.59 136.33 23.62
November 466.83 22.81 66.67 22.95 0.00 22.95
December 629.67 22.72 3.17 22.73 0.00 22.73
             
Annual Sum or Average 4479.33 23.16 4056.33 23.45 1535.33 23.51
Minimum of Months 99.33 22.72 3.17 22.73 0.00 22.73
Maximum of Months 629.67 23.91 744.00 23.84 495.67 23.85



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 497.67 24.13 742.17 24.10 497.67 24.11
February 453.67 24.09 670.00 24.07 453.67 24.07
March 502.33 24.05 741.00 24.04 502.33 24.04
April 508.83 24.00 719.17 24.00 508.83 24.00
May 551.00 23.99 744.00 23.99 551.00 23.99
June 588.50 23.99 720.00 23.99 588.50 23.99
July 738.50 23.99 744.00 23.99 738.50 23.99
August 680.67 23.99 744.00 23.99 680.67 23.99
September 646.17 23.99 720.00 23.99 646.17 23.99
October 563.50 23.99 744.00 23.99 563.50 23.99
November 493.83 24.07 719.50 24.06 493.83 24.06
December 483.33 24.13 740.67 24.10 483.33 24.11
             
Annual Sum or Average 6708.00 24.03 8748.50 24.02 6708.00 24.03
Minimum of Months 453.67 23.99 670.00 23.99 453.67 23.99
Maximum of Months 738.50 24.13 744.00 24.10 738.50 24.11



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.68 2.00 21.67 2.00 21.67
February 672.00 22.15 0.00 22.15 0.00 22.15
March 744.00 22.59 0.00 22.59 0.00 22.59
April 553.33 23.54 5.67 23.55 0.00 23.55
May 241.33 23.85 192.17 23.91 9.83 23.91
June 84.67 23.99 451.00 24.00 42.00 24.00
July 325.83 24.00 744.00 24.00 325.83 24.00
August 207.83 23.98 685.33 23.99 207.83 23.99
September 261.83 23.90 529.33 23.96 212.00 23.96
October 421.67 23.48 183.17 23.61 60.17 23.63
November 697.67 22.54 0.00 22.54 0.00 22.54
December 744.00 21.47 7.83 21.47 7.83 21.46
             
Annual Sum or Average 5698.17 22.69 2800.50 23.11 867.50 23.19
Minimum of Months 84.67 21.47 0.00 21.47 0.00 21.46
Maximum of Months 744.00 24.00 744.00 24.00 325.83 24.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.90713 24.80033 0.20746 5.98133
February 672.00000 23.39495 22.87603 0.05321 5.22878
March 744.00000 22.62758 22.24560 -0.1422 5.59853
April 720.00000 22.70977 25.47879 -0.1000 5.41106
May 744.00000 23.02837 35.90373 -0.9641 24.98980
June 720.00000 23.34346 44.10018 -0.7943 18.70987
July 744.00000 23.86337 56.57665 -0.5033 10.41643
August 744.00000 23.97481 52.47735 -0.4709 9.68636
September 720.00000 23.99874 49.01646 -0.4689 9.70651
October 744.00000 23.99918 39.82320 0.36630 7.92683
November 720.00000 24.00079 24.47096 0.25536 6.42068
December 744.00000 23.99398 21.98032 0.22551 6.09916
           
Annual Sum or Average 8760.00000 23.57224 35.06998 -0.1958 9.71370
Minimum of Months 672.00000 22.62758 21.98032 -0.9641 5.22878
Maximum of Months 744.00000 24.00079 56.57665 0.36630 24.98980



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.39046 26.93740 -0.1168 7.23605
February 672.00000 22.62362 23.52443 -0.0704 6.77869
March 744.00000 22.79130 21.92287 -0.0397 6.48899
April 720.00000 23.49938 24.00223 0.17554 6.61444
May 744.00000 23.84301 33.57766 -0.5429 12.02195
June 720.00000 23.98237 41.32465 -0.3907 8.40852
July 744.00000 23.98891 55.71841 -0.2864 6.79767
August 744.00000 23.96101 52.32059 -0.3206 7.38619
September 720.00000 23.92673 49.49281 -0.3408 8.06658
October 744.00000 23.61537 41.34697 0.35844 8.57663
November 720.00000 22.89520 26.81943 0.04012 7.17923
December 744.00000 22.22549 24.61057 -0.1833 7.63112
           
Annual Sum or Average 8760.00000 23.31467 35.22555 -0.1439 7.77579
Minimum of Months 672.00000 22.22549 21.92287 -0.5429 6.48899
Maximum of Months 744.00000 23.98891 55.71841 0.35844 12.02195



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.68460 26.96802 -0.0482 5.41926
February 672.00000 22.87485 23.63724 -0.0192 5.33548
March 744.00000 23.03231 22.03954 0.01344 5.37950
April 720.00000 23.52803 24.49486 0.16552 5.92372
May 744.00000 23.76235 34.30149 -0.6059 13.14628
June 720.00000 23.87933 42.36624 -0.4913 10.28415
July 744.00000 23.88381 56.63122 -0.3925 8.33422
August 744.00000 23.86344 53.34770 -0.4261 8.94974
September 720.00000 23.86687 50.36442 -0.4480 9.44100
October 744.00000 23.64319 41.93422 0.31750 7.38574
November 720.00000 23.13909 27.03541 0.07400 5.61181
December 744.00000 22.51437 24.77082 -0.1067 5.56461
           
Annual Sum or Average 8760.00000 23.39124 35.75193 -0.1650 7.58020
Minimum of Months 672.00000 22.51437 22.03954 -0.6059 5.33548
Maximum of Months 744.00000 23.88381 56.63122 0.31750 13.14628



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 24.01159 21.06711 0.80918 19.82710
February 672.00000 23.99719 18.14653 0.80193 19.49569
March 744.00000 23.98691 16.81003 0.80644 19.57619
April 720.00000 23.99547 19.93679 0.86848 21.78337
May 744.00000 23.99968 30.22502 0.35106 9.50205
June 720.00000 24.00034 38.64565 0.44427 10.89497
July 744.00000 24.00012 52.57686 0.53453 12.45106
August 744.00000 24.00009 49.29669 0.50374 11.91132
September 720.00000 23.99846 46.26011 0.46818 11.19484
October 744.00000 23.98634 37.14884 0.98037 26.05994
November 720.00000 23.99220 21.70857 0.83394 20.57090
December 744.00000 24.00122 18.88626 0.78340 18.93399
           
Annual Sum or Average 8760.00000 23.99748 30.98896 0.68145 16.83647
Minimum of Months 672.00000 23.98634 16.81003 0.35106 9.50205
Maximum of Months 744.00000 24.01159 52.57686 0.98037 26.05994



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.44867 29.68079 -0.0129 6.11671
February 672.00000 22.56566 26.41198 0.00689 5.94537
March 744.00000 22.48926 24.99453 -0.0193 5.72967
April 720.00000 22.83474 27.97685 0.11345 5.97828
May 744.00000 23.01529 38.62894 -0.6946 16.12480
June 720.00000 23.28501 46.77621 -0.5071 11.10685
July 744.00000 23.31853 61.32368 -0.3962 8.85290
August 744.00000 23.38134 57.72077 -0.3984 9.01636
September 720.00000 23.52412 54.15891 -0.3642 8.68046
October 744.00000 23.26578 45.44198 0.36542 8.78366
November 720.00000 22.85968 29.88737 0.11963 6.80724
December 744.00000 22.30057 27.39313 -0.0731 6.21061
           
Annual Sum or Average 8760.00000 22.94178 39.29922 -0.1563 8.30009
Minimum of Months 672.00000 22.30057 24.99453 -0.6946 5.72967
Maximum of Months 744.00000 23.52412 61.32368 0.36542 16.12480



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.07195 29.31792 0.07494 5.46318
February 672.00000 23.19600 26.11803 0.08975 5.46340
March 744.00000 23.23192 24.68679 0.09286 5.53076
April 720.00000 23.51633 27.26547 0.19920 6.17281
May 744.00000 23.64632 37.14226 -0.5963 12.97113
June 720.00000 23.75089 45.12568 -0.4804 10.18492
July 744.00000 23.76780 59.38639 -0.3765 8.17698
August 744.00000 23.76795 56.04994 -0.4029 8.60915
September 720.00000 23.81722 52.96591 -0.4100 8.74725
October 744.00000 23.71013 44.36472 0.37528 8.19607
November 720.00000 23.40844 29.48827 0.17389 6.04129
December 744.00000 22.95591 27.13269 0.02780 5.34697
           
Annual Sum or Average 8760.00000 23.48763 38.34840 -0.1040 7.59037
Minimum of Months 672.00000 22.95591 24.68679 -0.5963 5.34697
Maximum of Months 744.00000 23.81722 59.38639 0.37528 12.97113



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.25940 31.31825 -0.4501 9.88221
February 672.00000 21.36788 27.57331 -0.4195 9.36012
March 744.00000 21.46020 26.00460 -0.3723 8.62679
April 720.00000 21.63120 29.16328 -0.2380 7.17268
May 744.00000 21.69711 37.50255 -1.2059 36.91549
June 720.00000 21.73555 42.69346 -1.1090 32.36893
July 744.00000 21.73269 50.85450 -1.0685 30.59360
August 744.00000 21.72135 49.88593 -1.0926 31.68468
September 720.00000 21.71705 49.12816 -1.1082 32.54362
October 744.00000 21.64173 45.85758 -0.1289 6.25565
November 720.00000 21.44922 31.90907 -0.3443 8.50434
December 744.00000 21.21381 28.35631 -0.4967 10.75031
           
Annual Sum or Average 8760.00000 21.55289 37.59464 -0.6712 18.78285
Minimum of Months 672.00000 21.21381 26.00460 -1.2059 6.25565
Maximum of Months 744.00000 21.73555 50.85450 -0.1289 36.91549



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.89926 31.86383 -0.5779 12.33726
February 672.00000 21.06859 27.96485 -0.5300 11.29633
March 744.00000 21.26591 26.26601 -0.4454 9.63513
April 720.00000 21.57268 29.27117 -0.2674 7.36918
May 744.00000 21.68885 37.52941 -1.2138 37.24524
June 720.00000 21.73849 42.66937 -1.1066 32.24435
July 744.00000 21.73390 50.88888 -1.0691 30.59047
August 744.00000 21.71373 50.17163 -1.1073 32.24407
September 720.00000 21.68962 49.86456 -1.1500 34.22206
October 744.00000 21.52818 46.69769 -0.1886 6.40386
November 720.00000 21.19638 32.32256 -0.4516 9.88450
December 744.00000 20.83327 28.87745 -0.6296 13.61671
           
Annual Sum or Average 8760.00000 21.41203 37.93969 -0.7296 19.81412
Minimum of Months 672.00000 20.83327 26.26601 -1.2138 6.40386
Maximum of Months 744.00000 21.73849 50.88888 -0.1886 37.24524



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.96264 30.37565 -0.5517 11.52884
February 672.00000 21.04300 26.46230 -0.5380 11.19594
March 744.00000 21.14859 24.84024 -0.4992 10.29658
April 720.00000 21.36051 28.03568 -0.3889 8.44983
May 744.00000 21.52274 37.01799 -1.4042 46.10760
June 720.00000 21.64161 42.88305 -1.2972 40.72468
July 744.00000 21.63701 52.49349 -1.2437 38.10722
August 744.00000 21.57438 51.24619 -1.2894 40.24287
September 720.00000 21.49218 50.64056 -1.3442 42.93664
October 744.00000 21.30707 46.07637 -0.3032 7.12805
November 720.00000 21.06682 31.02458 -0.5005 10.37716
December 744.00000 20.92975 27.46986 -0.5837 12.28286
           
Annual Sum or Average 8760.00000 21.30845 37.46185 -0.8305 23.35521
Minimum of Months 672.00000 20.92975 24.84024 -1.4042 7.12805
Maximum of Months 744.00000 21.64161 52.49349 -0.3032 46.10760



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.28536 31.25829 -0.4470 9.73225
February 672.00000 21.45610 27.44819 -0.3914 8.96039
March 744.00000 21.56167 25.89320 -0.3455 8.35974
April 720.00000 21.71710 29.04097 -0.2095 7.00497
May 744.00000 21.74321 37.39742 -1.1834 35.89640
June 720.00000 21.75465 42.77927 -1.0926 31.72984
July 744.00000 21.75007 50.92160 -1.0539 30.04826
August 744.00000 21.74111 49.87855 -1.0784 31.14450
September 720.00000 21.74422 49.04749 -1.0961 32.06244
October 744.00000 21.66566 46.04206 -0.1284 6.30825
November 720.00000 21.49697 31.85512 -0.3367 8.41376
December 744.00000 21.22902 28.30319 -0.4914 10.54453
           
Annual Sum or Average 8760.00000 21.59566 37.56372 -0.6564 18.41171
Minimum of Months 672.00000 21.22902 25.89320 -1.1834 6.30825
Maximum of Months 744.00000 21.75465 50.92160 -0.1284 35.89640



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.89650 31.81700 -0.5808 12.30542
February 672.00000 21.14058 27.82154 -0.5044 10.70565
March 744.00000 21.38500 26.10573 -0.4153 9.13826
April 720.00000 21.69298 29.10387 -0.2320 7.11077
May 744.00000 21.74251 37.43709 -1.1891 36.12055
June 720.00000 21.75574 42.81014 -1.0906 31.62458
July 744.00000 21.75040 50.99321 -1.0547 30.05410
August 744.00000 21.73849 50.15934 -1.0915 31.63510
September 720.00000 21.73566 49.50481 -1.1334 33.55073
October 744.00000 21.59417 46.59856 -0.1814 6.42181
November 720.00000 21.18182 32.31049 -0.4563 9.82063
December 744.00000 20.83231 28.82090 -0.6273 13.55446
           
Annual Sum or Average 8760.00000 21.45491 37.86512 -0.7146 19.39474
Minimum of Months 672.00000 20.83231 26.10573 -1.1891 6.42181
Maximum of Months 744.00000 21.75574 50.99321 -0.1814 36.12055



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.14167 31.73471 -0.5168 11.34152
February 672.00000 21.26967 27.87931 -0.4792 10.62661
March 744.00000 21.37967 26.24794 -0.4227 9.61869
April 720.00000 21.59650 29.33089 -0.2615 7.64341
May 744.00000 21.68198 37.83695 -1.2174 37.69033
June 720.00000 21.73415 43.04022 -1.0989 32.17215
July 744.00000 21.73039 51.36334 -1.0583 30.37169
August 744.00000 21.71469 50.55628 -1.0886 31.74063
September 720.00000 21.70381 50.01662 -1.1158 33.16364
October 744.00000 21.59740 46.87722 -0.1562 6.58638
November 720.00000 21.36226 32.28190 -0.4031 9.62359
December 744.00000 21.09971 28.72858 -0.5636 12.32423
           
Annual Sum or Average 8760.00000 21.50182 38.06686 -0.7001 19.46714
Minimum of Months 672.00000 21.09971 26.24794 -1.2174 6.58638
Maximum of Months 744.00000 21.73415 51.36334 -0.1562 37.69033



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.75808 32.32834 -0.6521 14.34395
February 672.00000 20.94525 28.31860 -0.5981 13.01231
March 744.00000 21.16363 26.54817 -0.5033 10.89921
April 720.00000 21.53463 29.45127 -0.2930 7.88791
May 744.00000 21.67331 37.86076 -1.2257 38.03358
June 720.00000 21.73799 43.01303 -1.0962 32.03030
July 744.00000 21.73191 51.38968 -1.0588 30.36077
August 744.00000 21.70706 50.88351 -1.1035 32.29281
September 720.00000 21.67408 50.88425 -1.1595 34.90447
October 744.00000 21.46346 47.83344 -0.2238 6.85057
November 720.00000 21.06394 32.76968 -0.5259 11.49808
December 744.00000 20.70476 29.28621 -0.7017 15.70972
           
Annual Sum or Average 8760.00000 21.34810 38.45617 -0.7631 20.70459
Minimum of Months 672.00000 20.70476 26.54817 -1.2257 6.85057
Maximum of Months 744.00000 21.73799 51.38968 -0.2238 38.03358



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.51123 32.61674 -0.3376 8.60477
February 672.00000 21.56361 28.63340 -0.3342 8.48809
March 744.00000 21.55387 26.95294 -0.3481 8.54338
April 720.00000 21.63020 29.98589 -0.2687 7.59557
May 744.00000 21.67309 38.44121 -1.2878 40.81054
June 720.00000 21.71479 43.79813 -1.1905 36.05617
July 744.00000 21.71803 52.02970 -1.1370 33.62139
August 744.00000 21.70828 50.65944 -1.1479 34.21983
September 720.00000 21.71502 49.71374 -1.1395 34.17830
October 744.00000 21.66026 46.05166 -0.1235 6.48880
November 720.00000 21.56228 32.91198 -0.2814 8.05848
December 744.00000 21.51542 29.68900 -0.3641 9.01423
           
Annual Sum or Average 8760.00000 21.62738 38.53066 -0.6654 19.71154
Minimum of Months 672.00000 21.51123 26.95294 -1.2878 6.48880
Maximum of Months 744.00000 21.71803 52.02970 -0.1235 40.81054



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.58185 29.52214 -0.0139 5.66613
February 672.00000 22.75516 26.17317 0.02343 5.64368
March 744.00000 22.95374 24.59057 0.08149 5.68703
April 720.00000 23.33485 27.35031 0.23803 6.67006
May 744.00000 23.53226 37.46774 -0.4945 10.79241
June 720.00000 23.64859 45.60376 -0.3584 8.13698
July 744.00000 23.64724 59.85963 -0.2650 6.78783
August 744.00000 23.58686 56.79158 -0.3226 7.59417
September 720.00000 23.49424 54.07931 -0.3994 8.95289
October 744.00000 23.26722 45.35883 0.33538 7.92651
November 720.00000 22.83902 29.92019 0.07613 5.75981
December 744.00000 22.48992 27.25381 -0.0609 5.69413
           
Annual Sum or Average 8760.00000 23.17939 38.76063 -0.0975 7.11838
Minimum of Months 672.00000 22.48992 24.59057 -0.4945 5.64368
Maximum of Months 744.00000 23.64859 59.85963 0.33538 10.79241



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.97169 29.00535 0.10775 5.82594
February 672.00000 23.11022 25.74653 0.13482 5.91194
March 744.00000 23.27308 24.19612 0.18274 6.12730
April 720.00000 23.54402 26.92186 0.30925 7.37233
May 744.00000 23.69199 36.94220 -0.4109 9.06440
June 720.00000 23.79044 45.06015 -0.2806 6.97004
July 744.00000 23.78787 59.19463 -0.1877 5.92688
August 744.00000 23.73269 56.13523 -0.2441 6.51885
September 720.00000 23.65711 53.41527 -0.3160 7.54584
October 744.00000 23.47902 44.74177 0.40574 8.91132
November 720.00000 23.15568 29.46431 0.17555 6.16691
December 744.00000 22.89862 26.78724 0.06638 5.64958
           
Annual Sum or Average 8760.00000 23.42572 38.22967 -0.0057 6.83819
Minimum of Months 672.00000 22.89862 24.19612 -0.4109 5.64958
Maximum of Months 744.00000 23.79044 59.19463 0.40574 9.06440



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 24.08403 28.06723 0.98748 27.13749
February 672.00000 24.05382 24.97588 0.98586 27.05062
March 744.00000 24.02842 23.50921 0.99687 27.52293
April 720.00000 24.00347 26.29664 1.07679 31.09929
May 744.00000 23.99176 36.17855 0.64379 17.70079
June 720.00000 23.99235 44.33461 0.75563 20.50118
July 744.00000 23.99301 57.95409 0.84331 23.07553
August 744.00000 23.99308 54.77367 0.80210 21.81218
September 720.00000 23.99214 51.83756 0.75518 20.49818
October 744.00000 23.99205 43.08713 1.17491 35.32737
November 720.00000 24.04768 28.45935 1.01627 28.34492
December 744.00000 24.08478 26.01312 0.96121 26.08262
           
Annual Sum or Average 8760.00000 24.02125 37.21710 0.91622 25.50452
Minimum of Months 672.00000 23.99176 23.50921 0.64379 17.70079
Maximum of Months 744.00000 24.08478 57.95409 1.17491 35.32737



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.08560 25.73984 -0.4630 9.55980
February 672.00000 21.24189 22.10646 -0.4414 9.19132
March 744.00000 21.44252 20.33313 -0.3989 8.47241
April 720.00000 22.27866 22.76459 -0.1768 5.97554
May 744.00000 22.96220 32.67492 -0.9449 24.35674
June 720.00000 23.47493 40.51289 -0.7134 15.92538
July 744.00000 23.46675 55.49163 -0.6153 13.05406
August 744.00000 23.30611 52.29477 -0.6944 15.34317
September 720.00000 23.05198 49.90680 -0.7983 18.78026
October 744.00000 22.43435 41.57616 -0.0182 5.35675
November 720.00000 21.53425 25.81107 -0.3444 7.76491
December 744.00000 21.04479 23.15310 -0.4944 10.15064
           
Annual Sum or Average 8760.00000 22.28214 34.46030 -0.5092 12.01600
Minimum of Months 672.00000 21.04479 20.33313 -0.9449 5.35675
Maximum of Months 744.00000 23.47493 55.49163 -0.0182 24.35674



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.78704 29.31592 -0.3031 7.08241
February 672.00000 22.14367 25.63699 -0.2382 6.34286
March 744.00000 22.46488 23.89696 -0.1703 5.78343
April 720.00000 23.35386 26.13289 0.06172 5.34944
May 744.00000 23.84354 35.42615 -0.6831 15.13025
June 720.00000 23.97698 43.25333 -0.5715 11.96164
July 744.00000 23.97810 57.59942 -0.4732 9.68770
August 744.00000 23.94462 54.36436 -0.5102 10.49482
September 720.00000 23.93673 51.55798 -0.5341 11.12945
October 744.00000 23.55939 43.61776 0.23210 6.34208
November 720.00000 22.67468 28.89896 -0.0867 5.59921
December 744.00000 21.56393 27.04189 -0.3717 7.96807
           
Annual Sum or Average 8760.00000 23.10596 37.32128 -0.3048 8.59163
Minimum of Months 672.00000 21.56393 23.89696 -0.6831 5.34944
Maximum of Months 744.00000 23.97810 57.59942 0.23210 15.13025



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.67520 27.74434 -0.3285 7.54600
February 672.00000 22.14559 23.95165 -0.2346 6.57367
March 744.00000 22.59303 22.04663 -0.1346 5.84539
April 720.00000 23.64354 23.73217 0.14683 5.88684
May 744.00000 23.94557 33.09060 -0.5990 12.86544
June 720.00000 23.99882 40.89065 -0.4916 10.18976
July 744.00000 23.99954 55.06346 -0.3938 8.24290
August 744.00000 23.99391 51.83649 -0.4280 8.87660
September 720.00000 23.95597 49.25779 -0.4728 9.92033
October 744.00000 23.67803 41.34625 0.27781 6.93682
November 720.00000 22.58186 27.25982 -0.1048 6.08545
December 744.00000 21.46991 25.45104 -0.3974 8.47504
           
Annual Sum or Average 8760.00000 23.14382 35.22960 -0.2640 8.13416
Minimum of Months 672.00000 21.46991 22.04663 -0.5990 5.84539
Maximum of Months 744.00000 23.99954 55.06346 0.27781 12.86544



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.95561 24.64162 -0.2761 6.82139
February 672.00000 22.25488 21.04342 -0.2265 6.37161
March 744.00000 22.60650 19.26196 -0.1527 5.78555
April 720.00000 23.52737 21.28497 0.08783 5.50276
May 744.00000 23.93672 30.76992 -0.6441 14.02085
June 720.00000 23.99815 39.12697 -0.5384 11.19954
July 744.00000 23.99952 53.70075 -0.4370 8.99806
August 744.00000 23.98963 50.17265 -0.4748 9.75667
September 720.00000 23.97276 47.35783 -0.5123 10.67489
October 744.00000 23.63451 38.98956 0.23723 6.44806
November 720.00000 22.66262 24.37366 -0.1053 5.72344
December 744.00000 21.74566 22.40306 -0.3406 7.62896
           
Annual Sum or Average 8760.00000 23.19418 32.85382 -0.2825 8.25937
Minimum of Months 672.00000 21.74566 19.26196 -0.6441 5.50276
Maximum of Months 744.00000 23.99952 53.70075 0.23723 14.02085



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.113613E+11 58737.52 03-JAN-16:03 480.40 0.350771E+11 0.00 0.464384E+11 2.04 3.28 12-JAN-16:03 0.00 0.00
February 0.238075E+11 84700.05 20-FEB-16:01 506.59 0.714686E+11 0.00 0.952761E+11 2.35 3.70 21-FEB-16:01 0.00 0.00
March 0.403665E+11 93030.81 14-MAR-18:01 608.48 0.120319E+12 0.00 0.160686E+12 2.52 3.92 15-MAR-18:02 0.00 0.00
April 0.108445E+12 131748.74 21-APR-15:03 705.14 0.332665E+12 0.00 0.441110E+12 3.00 3.91 12-APR-18:01 0.00 0.00
May 0.175666E+12 143480.54 19-MAY-18:05 743.57 0.541329E+12 0.00 0.716995E+12 3.06 3.88 01-MAY-18:02 0.00 0.00
June 0.231373E+12 183740.12 14-JUN-18:03 720.00 0.700633E+12 0.00 0.932006E+12 3.04 3.96 19-JUN-18:03 0.00 0.00
July 0.270882E+12 177175.59 26-JUL-18:03 744.00 0.897443E+12 0.00 0.116833E+13 3.33 4.51 18-JUL-21:00 0.00 0.00
August 0.234206E+12 168689.95 04-AUG-18:03 744.00 0.751003E+12 0.00 0.985209E+12 3.20 4.29 16-AUG-18:02 0.00 0.00
September 0.190406E+12 146096.90 20-SEP-15:03 720.00 0.631108E+12 0.00 0.821514E+12 3.27 4.45 23-SEP-18:03 0.00 0.00
October 0.107001E+12 145936.19 04-OCT-18:03 735.64 0.342939E+12 0.00 0.449941E+12 3.11 4.23 03-OCT-21:00 0.00 0.00
November 0.327012E+11 89121.44 09-NOV-16:01 553.52 0.993361E+11 0.00 0.132037E+12 2.39 3.95 08-NOV-19:01 0.00 0.00
December 0.862815E+10 33154.39 23-DEC-15:00 468.44 0.269385E+11 0.00 0.355666E+11 1.99 3.19 02-DEC-06:10 0.00 0.00
                         
Annual Sum or Average 0.143484E+13     7729.77 0.455026E+13 0.00 0.598510E+13 2.78     0.00 0.00
Minimum of Months 0.862815E+10 33154.39   468.44 0.269385E+11 0.00 0.355666E+11 1.99 3.19   0.00 0.00
Maximum of Months 0.270882E+12 183740.12   744.00 0.897443E+12 0.00 0.116833E+13 3.33 4.51   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.483451E+11 0.00 710.74 207629.42 17-JAN-09:01 0.00 55.49 79.01 0.18 0.00 0.04 0.51 17-JAN-09:01
February 0.285141E+11 0.00 566.17 149433.58 17-FEB-09:01 0.00 55.39 75.89 0.12 0.00 0.03 0.37 17-FEB-09:01
March 0.184266E+11 0.00 463.44 121670.79 31-MAR-04:00 0.00 54.87 69.63 0.07 0.00 0.02 0.30 31-MAR-04:00
April 0.572989E+10 0.00 138.65 126183.98 13-APR-04:53 0.00 45.09 51.32 0.02 0.00 0.01 0.31 13-APR-04:53
May 0.411772E+09 0.00 20.69 78417.52 02-MAY-18:04 0.00 49.34 50.30 0.00 0.00 0.00 0.19 02-MAY-18:04
June 48509449.36 0.00 1.65 23758.49 01-JUN-08:04 0.00 59.82 59.86 0.00 0.00 0.00 0.06 01-JUN-08:04
July 45608288.07 0.00 2.37 21751.99 05-JUL-08:05 0.00 62.44 62.49 0.00 0.00 0.00 0.05 05-JUL-08:05
August 58231720.29 0.00 2.40 36268.08 24-AUG-08:04 0.00 61.60 61.65 0.00 0.00 0.00 0.09 24-AUG-08:04
September 0.513054E+09 0.00 17.29 46455.89 25-SEP-05:10 0.00 56.29 57.13 0.00 0.00 0.00 0.11 25-SEP-05:10
October 0.276710E+10 0.00 168.95 79268.89 25-OCT-05:10 0.00 51.61 58.10 0.01 0.00 0.00 0.19 25-OCT-05:10
November 0.268639E+11 0.00 531.66 151510.14 26-NOV-16:01 0.00 57.77 74.44 0.10 0.00 0.03 0.37 26-NOV-16:01
December 0.512090E+11 0.00 721.32 158292.18 02-DEC-19:05 0.00 55.42 79.34 0.19 0.00 0.05 0.39 02-DEC-19:05
                           
Annual Sum or Average 0.182933E+12 0.00 3345.33     0.00 55.43 64.89 0.06 0.00 0.01    
Minimum of Months 45608288.07 0.00 1.65 21751.99   0.00 45.09 50.30 0.00 0.00 0.00 0.05  
Maximum of Months 0.512090E+11 0.00 721.32 207629.42   0.00 62.44 79.34 0.19 0.00 0.05 0.51  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.716861E+10 0.00 175.53 0.716861E+10 0.00 0.00 0.00 0.00 93651.60 03-JAN-17:00 93651.60 03-JAN-17:00 0.00 0.00 0.00
February 0.347043E+11 0.00 247.95 0.347043E+11 0.00 0.00 0.00 0.00 128540.56 20-FEB-16:20 128540.56 20-FEB-16:20 0.00 0.00 0.00
March 0.702420E+11 0.00 351.30 0.702420E+11 0.00 0.00 0.00 0.00 165916.23 14-MAR-17:13 165916.23 14-MAR-17:13 0.00 0.00 0.00
April 0.215062E+12 0.00 570.21 0.215062E+12 0.00 0.00 0.00 0.00 228369.22 19-APR-21:00 228369.22 19-APR-21:00 0.00 0.00 0.00
May 0.357119E+12 0.00 714.78 0.355312E+12 0.00 0.00 0.00 0.00 257953.19 19-MAY-20:10 257953.19 19-MAY-20:10 0.00 0.00 0.00
June 0.463005E+12 0.00 720.00 0.457562E+12 0.00 0.00 0.00 0.00 304214.02 19-JUN-18:07 287067.60 05-JUN-20:10 0.00 0.00 0.00
July 0.618069E+12 0.00 744.00 0.481303E+12 0.00 0.00 0.00 0.00 472231.72 18-JUL-20:50 287535.40 25-JUL-20:10 0.00 0.00 0.00
August 0.504514E+12 0.00 744.00 0.450042E+12 0.00 0.00 0.00 0.00 467350.66 01-AUG-20:50 294023.67 04-AUG-20:10 0.00 0.00 0.00
September 0.412748E+12 0.00 696.01 0.354800E+12 0.00 0.00 0.00 0.00 346303.91 09-SEP-20:00 259810.54 19-SEP-18:20 0.00 0.00 0.00
October 0.204981E+12 0.00 551.31 0.195856E+12 0.00 0.00 0.00 0.00 395164.94 03-OCT-20:00 247317.98 04-OCT-20:10 0.00 0.00 0.00
November 0.433069E+11 0.00 292.74 0.433069E+11 0.00 0.00 0.00 0.00 152247.78 03-NOV-16:00 152247.78 03-NOV-16:00 0.00 0.00 0.00
December 0.436754E+10 0.00 186.95 0.436754E+10 0.00 0.00 0.00 0.00 52907.71 23-DEC-15:00 52907.71 23-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.293529E+13 0.00 5994.78 0.266972E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.436754E+10 0.00 175.53 0.436754E+10 0.00 0.00 0.00 0.00 52907.71   52907.71   0.00 0.00 0.00
Maximum of Months 0.618069E+12 0.00 744.00 0.481303E+12 0.00 0.00 0.00 0.00 472231.72   294023.67   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.122870E+10 0.00 63.75 0.122870E+10 0.00 0.00 0.00 0.00 18651.05 03-JAN-15:00 18651.05 03-JAN-15:00 0.00 0.00 0.00
February 0.618797E+10 0.00 159.53 0.618797E+10 0.00 0.00 0.00 0.00 23693.24 20-FEB-16:00 23693.24 20-FEB-16:00 0.00 0.00 0.00
March 0.122343E+11 0.00 278.02 0.122343E+11 0.00 0.00 0.00 0.00 24657.75 22-MAR-13:00 24657.75 22-MAR-13:00 0.00 0.00 0.00
April 0.348126E+11 0.00 548.56 0.348126E+11 0.00 0.00 0.00 0.00 29774.81 21-APR-15:00 29774.81 21-APR-15:00 0.00 0.00 0.00
May 0.557264E+11 0.00 713.33 0.546336E+11 0.00 0.00 0.00 0.00 34982.72 24-MAY-13:00 31559.35 21-MAY-14:00 0.00 0.00 0.00
June 0.679277E+11 0.00 720.00 0.656138E+11 0.00 0.00 0.00 0.00 40511.58 27-JUN-24:00 33168.57 15-JUN-15:00 0.00 0.00 0.00
July 0.903037E+11 0.00 744.00 0.685052E+11 0.00 0.00 0.00 0.00 55414.96 21-JUL-08:00 33162.18 02-JUL-15:02 0.00 0.00 0.00
August 0.760520E+11 0.00 744.00 0.648652E+11 0.00 0.00 0.00 0.00 47992.63 02-AUG-03:50 32198.70 08-AUG-15:00 0.00 0.00 0.00
September 0.649768E+11 0.00 692.83 0.520160E+11 0.00 0.00 0.00 0.00 47427.38 22-SEP-02:00 30656.69 19-SEP-14:00 0.00 0.00 0.00
October 0.332051E+11 0.00 534.83 0.304518E+11 0.00 0.00 0.00 0.00 42555.84 03-OCT-20:40 30238.31 03-OCT-14:00 0.00 0.00 0.00
November 0.750498E+10 0.00 211.42 0.750498E+10 0.00 0.00 0.00 0.00 24036.88 08-NOV-15:00 24036.88 08-NOV-15:00 0.00 0.00 0.00
December 0.724517E+09 0.00 54.21 0.724517E+09 0.00 0.00 0.00 0.00 11238.19 10-DEC-15:00 11238.19 10-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.450885E+12 0.00 5464.49 0.398779E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.724517E+09 0.00 54.21 0.724517E+09 0.00 0.00 0.00 0.00 11238.19   11238.19   0.00 0.00 0.00
Maximum of Months 0.903037E+11 0.00 744.00 0.685052E+11 0.00 0.00 0.00 0.00 55414.96   33168.57   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.671030E+09 0.00 160.75 0.670438E+09 0.00 0.00 0.00 0.00 14474.63 03-JAN-16:01 14474.63 03-JAN-16:01 0.00 0.00 0.00
February 0.110388E+10 0.00 217.85 0.110256E+10 0.00 0.00 0.00 0.00 14890.92 20-FEB-16:01 14890.92 20-FEB-16:01 0.00 0.00 0.00
March 0.212310E+10 0.00 363.72 0.211888E+10 0.00 0.00 0.00 0.00 15048.49 21-MAR-15:01 15048.49 21-MAR-15:01 0.00 0.00 0.00
April 0.528641E+10 0.00 591.23 0.494931E+10 0.00 0.00 0.00 0.00 15387.69 19-APR-18:01 15387.69 19-APR-18:01 0.00 0.00 0.00
May 0.833939E+10 0.00 682.97 0.704930E+10 0.00 0.00 0.00 0.00 15388.05 20-MAY-18:01 15388.05 20-MAY-18:01 0.00 0.00 0.00
June 0.106356E+11 0.00 682.64 0.828857E+10 0.00 0.00 0.00 0.00 15385.19 17-JUN-15:02 15385.19 17-JUN-15:02 0.00 0.00 0.00
July 0.115254E+11 0.00 706.39 0.737916E+10 0.00 0.00 0.00 0.00 17009.89 20-JUL-08:61 14315.18 11-JUL-08:61 0.00 0.00 0.00
August 0.104753E+11 0.00 695.48 0.681315E+10 0.00 0.00 0.00 0.00 15794.40 02-AUG-08:61 14174.61 11-AUG-08:61 0.00 0.00 0.00
September 0.949976E+10 0.00 674.15 0.630370E+10 0.00 0.00 0.00 0.00 15800.63 09-SEP-08:61 15385.93 11-SEP-18:01 0.00 0.00 0.00
October 0.602678E+10 0.00 640.32 0.435033E+10 0.00 0.00 0.00 0.00 15305.24 21-OCT-15:01 15305.24 21-OCT-15:01 0.00 0.00 0.00
November 0.212641E+10 0.00 358.77 0.200685E+10 0.00 0.00 0.00 0.00 14930.59 09-NOV-16:01 14930.59 09-NOV-16:01 0.00 0.00 0.00
December 0.369382E+09 0.00 110.18 0.369382E+09 0.00 0.00 0.00 0.00 14069.01 23-DEC-16:01 14069.01 23-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.681824E+11 0.00 5884.45 0.514016E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.369382E+09 0.00 110.18 0.369382E+09 0.00 0.00 0.00 0.00 14069.01   14069.01   0.00 0.00 0.00
Maximum of Months 0.115254E+11 0.00 706.39 0.828857E+10 0.00 0.00 0.00 0.00 17009.89   15388.05   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.131543E+09 0.00 38.26 0.130999E+09 0.00 0.00 0.00 0.00 13985.84 12-JAN-16:01 13985.84 12-JAN-16:01 0.00 0.00 0.00
February 0.368761E+09 0.00 99.85 0.368091E+09 0.00 0.00 0.00 0.00 14777.23 20-FEB-16:01 14777.23 20-FEB-16:01 0.00 0.00 0.00
March 0.123588E+10 0.00 245.64 0.123317E+10 0.00 0.00 0.00 0.00 14934.58 21-MAR-15:01 14934.58 21-MAR-15:01 0.00 0.00 0.00
April 0.451657E+10 0.00 549.83 0.420757E+10 0.00 0.00 0.00 0.00 15270.26 19-APR-18:01 15270.26 19-APR-18:01 0.00 0.00 0.00
May 0.812970E+10 0.00 675.31 0.685950E+10 0.00 0.00 0.00 0.00 15271.49 20-MAY-18:01 15271.49 20-MAY-18:01 0.00 0.00 0.00
June 0.107027E+11 0.00 683.99 0.838306E+10 0.00 0.00 0.00 0.00 15268.60 17-JUN-15:02 15268.60 17-JUN-15:02 0.00 0.00 0.00
July 0.114724E+11 0.00 707.08 0.738141E+10 0.00 0.00 0.00 0.00 16518.49 08-JUL-08:61 14141.31 11-JUL-08:61 0.00 0.00 0.00
August 0.988001E+10 0.00 688.04 0.631301E+10 0.00 0.00 0.00 0.00 15765.98 02-AUG-08:61 14092.94 18-AUG-18:02 0.00 0.00 0.00
September 0.798041E+10 0.00 653.37 0.495802E+10 0.00 0.00 0.00 0.00 15608.10 09-SEP-08:61 15269.11 11-SEP-18:01 0.00 0.00 0.00
October 0.406955E+10 0.00 558.47 0.271128E+10 0.00 0.00 0.00 0.00 15188.88 21-OCT-15:01 15188.88 21-OCT-15:01 0.00 0.00 0.00
November 0.690078E+09 0.00 185.46 0.633956E+09 0.00 0.00 0.00 0.00 14818.10 09-NOV-16:01 14818.10 09-NOV-16:01 0.00 0.00 0.00
December 52500207.29 0.00 16.77 52500207.29 0.00 0.00 0.00 0.00 13314.87 16-DEC-16:02 13314.87 16-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.592300E+11 0.00 5102.07 0.432326E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 52500207.29 0.00 16.77 52500207.29 0.00 0.00 0.00 0.00 13314.87   13314.87   0.00 0.00 0.00
Maximum of Months 0.114724E+11 0.00 707.08 0.838306E+10 0.00 0.00 0.00 0.00 16518.49   15271.49   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.129405E+11 0.00 291.70 0.129405E+11 0.00 0.00 0.00 0.00 36097.79 12-JAN-14:30 36097.79 12-JAN-14:30 0.00 0.00 0.00
February 0.122174E+11 0.00 271.52 0.122174E+11 0.00 0.00 0.00 0.00 33506.84 07-FEB-13:40 33506.84 07-FEB-13:40 0.00 0.00 0.00
March 0.844895E+10 0.00 263.17 0.844895E+10 0.00 0.00 0.00 0.00 25257.35 16-MAR-13:30 25257.35 16-MAR-13:30 0.00 0.00 0.00
April 0.149179E+11 0.00 424.83 0.143412E+11 0.00 0.00 0.00 0.00 24186.74 04-APR-13:30 24186.74 04-APR-13:30 0.00 0.00 0.00
May 0.204865E+11 0.00 559.21 0.166138E+11 0.00 0.00 0.00 0.00 20983.79 19-MAY-17:20 20671.11 19-MAY-20:20 0.00 0.00 0.00
June 0.305562E+11 0.00 672.84 0.217467E+11 0.00 0.00 0.00 0.00 25309.39 15-JUN-17:13 25309.39 15-JUN-17:13 0.00 0.00 0.00
July 0.356368E+11 0.00 719.67 0.157876E+11 0.00 0.00 0.00 0.00 27910.78 26-JUL-17:20 18936.68 26-JUL-17:20 0.00 0.00 0.00
August 0.352593E+11 0.00 682.67 0.186574E+11 0.00 0.00 0.00 0.00 30610.73 29-AUG-13:20 29522.79 27-AUG-13:40 0.00 0.00 0.00
September 0.403219E+11 0.00 672.08 0.264905E+11 0.00 0.00 0.00 0.00 39123.09 20-SEP-15:02 34878.53 18-SEP-12:40 0.00 0.00 0.00
October 0.338967E+11 0.00 564.53 0.275361E+11 0.00 0.00 0.00 0.00 44065.97 22-OCT-13:20 41305.54 29-OCT-13:10 0.00 0.00 0.00
November 0.230354E+11 0.00 370.55 0.227344E+11 0.00 0.00 0.00 0.00 40218.59 09-NOV-13:50 40218.59 09-NOV-13:50 0.00 0.00 0.00
December 0.990409E+10 0.00 252.48 0.990409E+10 0.00 0.00 0.00 0.00 30365.89 16-DEC-14:10 30365.89 16-DEC-14:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.277622E+12 0.00 5745.25 0.207419E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.844895E+10 0.00 252.48 0.844895E+10 0.00 0.00 0.00 0.00 20983.79   18936.68   0.00 0.00 0.00
Maximum of Months 0.403219E+11 0.00 719.67 0.275361E+11 0.00 0.00 0.00 0.00 44065.97   41305.54   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.104106E+10 0.00 91.72 0.100813E+10 0.00 0.00 0.00 0.00 52497.96 15-JAN-09:01 47194.05 15-JAN-09:01 0.00 0.00 0.00
February 0.297821E+10 0.00 191.32 0.279047E+10 0.00 0.00 0.00 0.00 77279.99 20-FEB-09:01 77279.99 20-FEB-09:01 0.00 0.00 0.00
March 0.813544E+10 0.00 348.77 0.795461E+10 0.00 0.00 0.00 0.00 84187.57 21-MAR-18:01 84187.57 21-MAR-18:01 0.00 0.00 0.00
April 0.255835E+11 0.00 493.80 0.241104E+11 0.00 0.00 0.00 0.00 94232.94 21-APR-18:01 94232.94 21-APR-18:01 0.00 0.00 0.00
May 0.458559E+11 0.00 542.66 0.387127E+11 0.00 0.00 0.00 0.00 94325.56 20-MAY-18:01 94325.56 20-MAY-18:01 0.00 0.00 0.00
June 0.617328E+11 0.00 577.74 0.490262E+11 0.00 0.00 0.00 0.00 94339.11 06-JUN-15:02 94339.11 06-JUN-15:02 0.00 0.00 0.00
July 0.695542E+11 0.00 589.54 0.451298E+11 0.00 0.00 0.00 0.00 104574.26 08-JUL-08:61 87732.60 26-JUL-15:02 0.00 0.00 0.00
August 0.581977E+11 0.00 558.45 0.371416E+11 0.00 0.00 0.00 0.00 95961.01 02-AUG-08:61 87989.35 04-AUG-15:02 0.00 0.00 0.00
September 0.440525E+11 0.00 509.02 0.271598E+11 0.00 0.00 0.00 0.00 95012.57 23-SEP-08:61 92404.10 11-SEP-18:01 0.00 0.00 0.00
October 0.244524E+11 0.00 518.64 0.154547E+11 0.00 0.00 0.00 0.00 89606.94 03-OCT-18:02 86948.54 21-OCT-15:01 0.00 0.00 0.00
November 0.408310E+10 0.00 232.86 0.351030E+10 0.00 0.00 0.00 0.00 81213.16 08-NOV-19:01 81213.16 08-NOV-19:01 0.00 0.00 0.00
December 0.686038E+09 0.00 62.24 0.686038E+09 0.00 0.00 0.00 0.00 66057.82 09-DEC-09:02 66057.82 09-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.346353E+12 0.00 4716.77 0.252685E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.686038E+09 0.00 62.24 0.686038E+09 0.00 0.00 0.00 0.00 52497.96   47194.05   0.00 0.00 0.00
Maximum of Months 0.695542E+11 0.00 589.54 0.490262E+11 0.00 0.00 0.00 0.00 104574.26   94339.11   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.599809E+09 0.00 140.63 0.596618E+09 0.00 0.00 0.00 0.00 12497.15 12-JAN-16:01 12497.15 12-JAN-16:01 0.00 0.00 0.00
February 0.125603E+10 0.00 255.08 0.124417E+10 0.00 0.00 0.00 0.00 12982.40 20-FEB-16:01 12982.40 20-FEB-16:01 0.00 0.00 0.00
March 0.216217E+10 0.00 404.34 0.215637E+10 0.00 0.00 0.00 0.00 13120.39 21-MAR-15:01 13120.39 21-MAR-15:01 0.00 0.00 0.00
April 0.554281E+10 0.00 634.86 0.521033E+10 0.00 0.00 0.00 0.00 13416.25 27-APR-18:01 13416.25 27-APR-18:01 0.00 0.00 0.00
May 0.848276E+10 0.00 718.06 0.721765E+10 0.00 0.00 0.00 0.00 13415.84 09-MAY-18:01 13415.84 09-MAY-18:01 0.00 0.00 0.00
June 0.108921E+11 0.00 704.90 0.860525E+10 0.00 0.00 0.00 0.00 13414.48 17-JUN-15:02 13414.48 17-JUN-15:02 0.00 0.00 0.00
July 0.117779E+11 0.00 724.87 0.764782E+10 0.00 0.00 0.00 0.00 14539.09 19-JUL-08:62 12440.29 18-JUL-15:02 0.00 0.00 0.00
August 0.106839E+11 0.00 717.83 0.707298E+10 0.00 0.00 0.00 0.00 13274.96 18-AUG-08:62 12410.03 08-AUG-18:01 0.00 0.00 0.00
September 0.953444E+10 0.00 695.32 0.634253E+10 0.00 0.00 0.00 0.00 13414.80 11-SEP-18:01 13414.80 11-SEP-18:01 0.00 0.00 0.00
October 0.561140E+10 0.00 638.70 0.408191E+10 0.00 0.00 0.00 0.00 13343.94 21-OCT-15:01 13343.94 21-OCT-15:01 0.00 0.00 0.00
November 0.200246E+10 0.00 367.69 0.191424E+10 0.00 0.00 0.00 0.00 13017.35 09-NOV-16:01 13017.35 09-NOV-16:01 0.00 0.00 0.00
December 0.416595E+09 0.00 108.98 0.416595E+09 0.00 0.00 0.00 0.00 12106.53 16-DEC-09:02 12106.53 16-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.689624E+11 0.00 6111.28 0.525065E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.416595E+09 0.00 108.98 0.416595E+09 0.00 0.00 0.00 0.00 12106.53   12106.53   0.00 0.00 0.00
Maximum of Months 0.117779E+11 0.00 724.87 0.860525E+10 0.00 0.00 0.00 0.00 14539.09   13416.25   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 66604105.40 0.00 30.41 65894318.75 0.00 0.00 0.00 0.00 10246.66 04-JAN-09:02 10246.66 04-JAN-09:02 0.00 0.00 0.00
February 0.435069E+09 0.00 115.54 0.425738E+09 0.00 0.00 0.00 0.00 12459.22 21-FEB-16:01 12459.22 21-FEB-16:01 0.00 0.00 0.00
March 0.121903E+10 0.00 268.03 0.121532E+10 0.00 0.00 0.00 0.00 12952.42 22-MAR-15:01 12952.42 22-MAR-15:01 0.00 0.00 0.00
April 0.471166E+10 0.00 595.70 0.440141E+10 0.00 0.00 0.00 0.00 13307.96 27-APR-18:01 13307.96 27-APR-18:01 0.00 0.00 0.00
May 0.825733E+10 0.00 717.59 0.700053E+10 0.00 0.00 0.00 0.00 13307.54 09-MAY-18:01 13307.54 09-MAY-18:01 0.00 0.00 0.00
June 0.109533E+11 0.00 705.46 0.868780E+10 0.00 0.00 0.00 0.00 13306.23 17-JUN-15:02 13306.23 17-JUN-15:02 0.00 0.00 0.00
July 0.117174E+11 0.00 724.90 0.763290E+10 0.00 0.00 0.00 0.00 14375.65 19-JUL-08:62 12267.50 21-JUL-15:02 0.00 0.00 0.00
August 0.100750E+11 0.00 713.00 0.650388E+10 0.00 0.00 0.00 0.00 13245.32 16-AUG-15:02 12371.12 08-AUG-18:01 0.00 0.00 0.00
September 0.799423E+10 0.00 686.43 0.501261E+10 0.00 0.00 0.00 0.00 13306.38 11-SEP-18:01 13306.38 11-SEP-18:01 0.00 0.00 0.00
October 0.360864E+10 0.00 535.84 0.244157E+10 0.00 0.00 0.00 0.00 13235.82 21-OCT-15:01 13235.82 21-OCT-15:01 0.00 0.00 0.00
November 0.632305E+09 0.00 161.38 0.591539E+09 0.00 0.00 0.00 0.00 12625.58 09-NOV-16:01 12625.58 09-NOV-16:01 0.00 0.00 0.00
December 47021796.35 0.00 18.38 47021796.35 0.00 0.00 0.00 0.00 11256.06 09-DEC-09:02 11256.06 09-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.597176E+11 0.00 5272.66 0.440262E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 47021796.35 0.00 18.38 47021796.35 0.00 0.00 0.00 0.00 10246.66   10246.66   0.00 0.00 0.00
Maximum of Months 0.117174E+11 0.00 724.90 0.868780E+10 0.00 0.00 0.00 0.00 14375.65   13307.96   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.123977E+09 0.00 94.12 0.123824E+09 0.00 0.00 0.00 0.00 3848.79 03-JAN-16:01 3848.79 03-JAN-16:01 0.00 0.00 0.00
February 0.218500E+09 0.00 149.48 0.218313E+09 0.00 0.00 0.00 0.00 3959.53 20-FEB-16:01 3959.53 20-FEB-16:01 0.00 0.00 0.00
March 0.432427E+09 0.00 258.83 0.432389E+09 0.00 0.00 0.00 0.00 4001.44 21-MAR-15:01 4001.44 21-MAR-15:01 0.00 0.00 0.00
April 0.120958E+10 0.00 537.09 0.112591E+10 0.00 0.00 0.00 0.00 4091.51 19-APR-18:01 4091.51 19-APR-18:01 0.00 0.00 0.00
May 0.201804E+10 0.00 672.58 0.167916E+10 0.00 0.00 0.00 0.00 4091.68 20-MAY-18:01 4091.68 20-MAY-18:01 0.00 0.00 0.00
June 0.273804E+10 0.00 681.07 0.211493E+10 0.00 0.00 0.00 0.00 4090.98 17-JUN-15:02 4090.98 17-JUN-15:02 0.00 0.00 0.00
July 0.296315E+10 0.00 703.83 0.187179E+10 0.00 0.00 0.00 0.00 4689.66 20-JUL-08:61 3793.34 18-JUL-18:02 0.00 0.00 0.00
August 0.264212E+10 0.00 694.40 0.170211E+10 0.00 0.00 0.00 0.00 4316.95 02-AUG-08:61 3788.92 26-AUG-08:61 0.00 0.00 0.00
September 0.230778E+10 0.00 666.05 0.149588E+10 0.00 0.00 0.00 0.00 4337.65 09-SEP-08:61 4091.09 11-SEP-18:01 0.00 0.00 0.00
October 0.130232E+10 0.00 550.54 0.932957E+09 0.00 0.00 0.00 0.00 4069.74 21-OCT-15:01 4069.74 21-OCT-15:01 0.00 0.00 0.00
November 0.393475E+09 0.00 258.56 0.374931E+09 0.00 0.00 0.00 0.00 3970.08 09-NOV-16:01 3970.08 09-NOV-16:01 0.00 0.00 0.00
December 68596471.03 0.00 61.45 68596471.03 0.00 0.00 0.00 0.00 3740.98 23-DEC-16:01 3740.98 23-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.164180E+11 0.00 5327.99 0.121408E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 68596471.03 0.00 61.45 68596471.03 0.00 0.00 0.00 0.00 3740.98   3740.98   0.00 0.00 0.00
Maximum of Months 0.296315E+10 0.00 703.83 0.211493E+10 0.00 0.00 0.00 0.00 4689.66   4091.68   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 19453280.16 0.00 22.32 19308246.28 0.00 0.00 0.00 0.00 3669.60 12-JAN-16:01 3669.60 12-JAN-16:01 0.00 0.00 0.00
February 63847607.68 0.00 52.98 63727887.10 0.00 0.00 0.00 0.00 3924.17 20-FEB-16:01 3924.17 20-FEB-16:01 0.00 0.00 0.00
March 0.234176E+09 0.00 164.33 0.234133E+09 0.00 0.00 0.00 0.00 3965.90 21-MAR-15:01 3965.90 21-MAR-15:01 0.00 0.00 0.00
April 0.101414E+10 0.00 494.67 0.939172E+09 0.00 0.00 0.00 0.00 4055.30 19-APR-18:01 4055.30 19-APR-18:01 0.00 0.00 0.00
May 0.196328E+10 0.00 665.83 0.162926E+10 0.00 0.00 0.00 0.00 4055.38 20-MAY-18:01 4055.38 20-MAY-18:01 0.00 0.00 0.00
June 0.275526E+10 0.00 682.92 0.213764E+10 0.00 0.00 0.00 0.00 4054.67 17-JUN-15:02 4054.67 17-JUN-15:02 0.00 0.00 0.00
July 0.294932E+10 0.00 705.10 0.186731E+10 0.00 0.00 0.00 0.00 4560.54 08-JUL-08:61 3768.07 18-JUL-18:02 0.00 0.00 0.00
August 0.248524E+10 0.00 687.38 0.156596E+10 0.00 0.00 0.00 0.00 4316.69 02-AUG-08:61 3759.37 26-AUG-08:61 0.00 0.00 0.00
September 0.190710E+10 0.00 645.74 0.115134E+10 0.00 0.00 0.00 0.00 4273.28 23-SEP-08:61 4054.89 11-SEP-18:01 0.00 0.00 0.00
October 0.817569E+09 0.00 434.34 0.542648E+09 0.00 0.00 0.00 0.00 4033.50 21-OCT-15:01 4033.50 21-OCT-15:01 0.00 0.00 0.00
November 0.107922E+09 0.00 93.54 0.100690E+09 0.00 0.00 0.00 0.00 3934.91 09-NOV-16:01 3934.91 09-NOV-16:01 0.00 0.00 0.00
December 8203954.65 0.00 9.80 8203954.65 0.00 0.00 0.00 0.00 3444.38 16-DEC-16:02 3444.38 16-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.143255E+11 0.00 4658.94 0.102594E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 8203954.65 0.00 9.80 8203954.65 0.00 0.00 0.00 0.00 3444.38   3444.38   0.00 0.00 0.00
Maximum of Months 0.294932E+10 0.00 705.10 0.213764E+10 0.00 0.00 0.00 0.00 4560.54   4055.38   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.396812E+10 0.00 360.59 0.395843E+10 0.00 0.00 0.00 0.00 17001.46 03-JAN-16:01 17001.46 03-JAN-16:01 0.00 0.00 0.00
February 0.398326E+10 0.00 378.94 0.396888E+10 0.00 0.00 0.00 0.00 17490.48 20-FEB-16:01 17490.48 20-FEB-16:01 0.00 0.00 0.00
March 0.384131E+10 0.00 439.02 0.382890E+10 0.00 0.00 0.00 0.00 17675.70 21-MAR-15:01 17675.70 21-MAR-15:01 0.00 0.00 0.00
April 0.622106E+10 0.00 581.43 0.577389E+10 0.00 0.00 0.00 0.00 18067.01 21-APR-18:01 18067.01 21-APR-18:01 0.00 0.00 0.00
May 0.858777E+10 0.00 667.69 0.693302E+10 0.00 0.00 0.00 0.00 18070.33 12-MAY-15:02 18070.33 12-MAY-15:02 0.00 0.00 0.00
June 0.116712E+11 0.00 670.14 0.867014E+10 0.00 0.00 0.00 0.00 18068.67 11-JUN-18:01 18068.67 11-JUN-18:01 0.00 0.00 0.00
July 0.135021E+11 0.00 693.57 0.818210E+10 0.00 0.00 0.00 0.00 20926.61 20-JUL-08:61 16788.34 26-JUL-08:62 0.00 0.00 0.00
August 0.129933E+11 0.00 688.40 0.829040E+10 0.00 0.00 0.00 0.00 18902.72 02-AUG-08:61 16764.87 18-AUG-18:02 0.00 0.00 0.00
September 0.131179E+11 0.00 673.58 0.899396E+10 0.00 0.00 0.00 0.00 19046.99 09-SEP-08:61 18067.88 30-SEP-15:01 0.00 0.00 0.00
October 0.103338E+11 0.00 648.36 0.809790E+10 0.00 0.00 0.00 0.00 17976.73 21-OCT-15:01 17976.73 21-OCT-15:01 0.00 0.00 0.00
November 0.625146E+10 0.00 450.97 0.605658E+10 0.00 0.00 0.00 0.00 17534.77 09-NOV-16:01 17534.77 09-NOV-16:01 0.00 0.00 0.00
December 0.354599E+10 0.00 335.12 0.354579E+10 0.00 0.00 0.00 0.00 16559.95 10-DEC-16:01 16559.95 10-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.980173E+11 0.00 6587.81 0.763000E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.354599E+10 0.00 335.12 0.354579E+10 0.00 0.00 0.00 0.00 16559.95   16559.95   0.00 0.00 0.00
Maximum of Months 0.135021E+11 0.00 693.57 0.899396E+10 0.00 0.00 0.00 0.00 20926.61   18070.33   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 706.15 535.07 171.08 936.90 526.87 0.00 0.00 0.00
February 664.38 471.17 193.21 899.09 470.98 0.00 0.00 0.00
March 519.74 294.46 225.28 722.65 414.77 0.00 0.00 0.00
April 362.15 135.95 226.20 570.90 253.53 0.00 0.00 0.00
May 257.00 37.69 219.31 454.65 145.71 0.00 0.00 0.00
June 219.82 13.83 205.99 484.63 68.67 0.00 0.00 0.00
July 223.23 19.79 203.44 493.07 52.25 0.00 0.00 0.00
August 281.79 71.59 210.20 579.52 78.82 0.00 0.00 0.00
September 446.25 231.85 214.40 827.70 166.54 0.00 0.00 0.00
October 612.55 416.17 196.38 965.68 273.03 0.00 0.00 0.00
November 737.24 563.91 173.33 1026.16 450.35 0.00 0.00 0.00
December 724.95 544.65 180.31 942.51 563.25 0.00 0.00 0.00
                 
Annual Sum or Average 478.50 276.88 201.63 740.82 287.82 0.00 0.00 0.00
Minimum of Months 219.82 13.83 171.08 454.65 52.25 0.00 0.00 0.00
Maximum of Months 737.24 563.91 226.20 1026.16 563.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1988.48 1506.73 481.75 2631.95 1514.06 0.00 0.00 0.00
February 1870.85 1326.79 544.06 2528.06 1342.97 0.00 0.00 0.00
March 1463.55 829.18 634.37 2049.72 1168.12 0.00 0.00 0.00
April 1019.80 382.82 636.98 1648.81 688.96 0.00 0.00 0.00
May 723.68 106.13 617.55 1346.07 384.20 0.00 0.00 0.00
June 618.99 38.95 580.04 1429.59 179.07 0.00 0.00 0.00
July 628.60 55.73 572.87 1449.74 133.55 0.00 0.00 0.00
August 793.51 201.60 591.90 1679.22 208.36 0.00 0.00 0.00
September 1256.61 652.87 603.74 2350.75 450.04 0.00 0.00 0.00
October 1724.89 1171.91 552.99 2729.66 753.87 0.00 0.00 0.00
November 2076.02 1587.93 488.09 2877.82 1276.61 0.00 0.00 0.00
December 2041.42 1533.69 507.73 2645.50 1618.29 0.00 0.00 0.00
                 
Annual Sum or Average 1347.44 779.68 567.76 2110.91 807.23 0.00 0.00 0.00
Minimum of Months 618.99 38.95 481.75 1346.07 133.55 0.00 0.00 0.00
Maximum of Months 2076.02 1587.93 636.98 2877.82 1618.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2583.15 1957.32 625.82 3473.40 2080.95 0.00 0.00 0.00
February 2430.34 1723.58 706.76 3336.16 1849.02 0.00 0.00 0.00
March 1901.24 1077.15 824.09 2691.88 1622.84 0.00 0.00 0.00
April 1324.78 497.31 827.47 2157.31 964.80 0.00 0.00 0.00
May 940.11 137.87 802.24 1743.19 538.11 0.00 0.00 0.00
June 804.10 50.59 753.51 1865.14 243.97 0.00 0.00 0.00
July 816.59 72.40 744.19 1892.59 182.42 0.00 0.00 0.00
August 1030.81 261.90 768.91 2207.31 281.11 0.00 0.00 0.00
September 1632.41 848.12 784.29 3110.07 600.14 0.00 0.00 0.00
October 2240.73 1522.37 718.36 3601.92 1024.88 0.00 0.00 0.00
November 2696.87 2062.81 634.06 3801.65 1748.72 0.00 0.00 0.00
December 2651.92 1992.35 659.58 3487.65 2224.92 0.00 0.00 0.00
                 
Annual Sum or Average 1750.40 1012.84 737.56 2776.64 1109.90 0.00 0.00 0.00
Minimum of Months 804.10 50.59 625.82 1743.19 182.42 0.00 0.00 0.00
Maximum of Months 2696.87 2062.81 827.47 3801.65 2224.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 139.62 105.79 33.83 189.57 99.44 0.00 0.00 0.00
February 131.36 93.16 38.20 182.26 87.41 0.00 0.00 0.00
March 102.76 58.22 44.54 146.28 76.12 0.00 0.00 0.00
April 71.60 26.88 44.73 118.71 40.70 0.00 0.00 0.00
May 50.81 7.45 43.36 99.97 19.23 0.00 0.00 0.00
June 43.46 2.73 40.73 111.48 6.72 0.00 0.00 0.00
July 44.14 3.91 40.22 112.62 3.80 0.00 0.00 0.00
August 55.72 14.16 41.56 127.64 7.58 0.00 0.00 0.00
September 88.23 45.84 42.39 172.30 22.33 0.00 0.00 0.00
October 121.11 82.28 38.83 197.58 43.68 0.00 0.00 0.00
November 145.77 111.49 34.27 208.08 81.83 0.00 0.00 0.00
December 143.34 107.69 35.65 191.78 107.59 0.00 0.00 0.00
                 
Annual Sum or Average 94.61 54.74 39.87 154.65 49.52 0.00 0.00 0.00
Minimum of Months 43.46 2.73 33.83 99.97 3.80 0.00 0.00 0.00
Maximum of Months 145.77 111.49 44.73 208.08 107.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 107.40 60.54 46.87 114.60 205.39 0.00 0.00 0.00
February 120.90 64.15 56.75 139.65 180.25 0.00 0.00 0.00
March 164.97 88.46 76.51 213.32 147.44 0.00 0.00 0.00
April 189.31 102.11 87.19 294.22 75.12 0.00 0.00 0.00
May 204.29 109.33 94.96 361.44 35.56 0.00 0.00 0.00
June 198.79 106.74 92.05 408.04 12.47 0.00 0.00 0.00
July 176.54 87.72 88.82 367.99 6.88 0.00 0.00 0.00
August 170.94 87.09 83.85 338.71 14.04 0.00 0.00 0.00
September 175.49 97.97 77.52 318.07 42.21 0.00 0.00 0.00
October 151.21 88.52 62.68 233.75 85.60 0.00 0.00 0.00
November 126.16 76.76 49.40 154.17 169.33 0.00 0.00 0.00
December 101.75 55.25 46.51 102.62 225.91 0.00 0.00 0.00
                 
Annual Sum or Average 157.45 85.45 72.00 254.38 99.63 0.00 0.00 0.00
Minimum of Months 101.75 55.25 46.51 102.62 6.88 0.00 0.00 0.00
Maximum of Months 204.29 109.33 94.96 408.04 225.91 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.40 0.00 20.40 4.64 110.65 0.00 0.00 0.00
February 24.91 0.00 24.91 12.21 96.66 0.00 0.00 0.00
March 32.60 0.00 32.60 24.55 79.59 0.00 0.00 0.00
April 37.86 0.48 37.38 49.54 39.27 0.00 0.00 0.00
May 44.72 3.30 41.43 83.78 17.76 0.00 0.00 0.00
June 47.56 5.93 41.63 118.02 6.47 0.00 0.00 0.00
July 43.94 4.31 39.63 110.18 3.62 0.00 0.00 0.00
August 37.16 0.88 36.28 86.70 7.22 0.00 0.00 0.00
September 32.33 0.04 32.29 62.47 22.07 0.00 0.00 0.00
October 26.80 0.00 26.80 33.04 45.17 0.00 0.00 0.00
November 21.63 0.00 21.63 8.90 91.14 0.00 0.00 0.00
December 20.24 0.00 20.24 3.32 122.10 0.00 0.00 0.00
                 
Annual Sum or Average 32.55 1.25 31.30 49.98 53.27 0.00 0.00 0.00
Minimum of Months 20.24 0.00 20.24 3.32 3.62 0.00 0.00 0.00
Maximum of Months 47.56 5.93 41.63 118.02 122.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 107.40 60.54 46.87 121.21 199.06 0.00 0.00 0.00
February 120.90 64.15 56.75 146.11 175.21 0.00 0.00 0.00
March 164.97 88.46 76.51 218.52 144.71 0.00 0.00 0.00
April 189.31 102.11 87.19 296.77 74.23 0.00 0.00 0.00
May 204.29 109.33 94.96 362.02 35.41 0.00 0.00 0.00
June 198.79 106.74 92.05 407.88 12.48 0.00 0.00 0.00
July 176.54 87.72 88.82 368.10 6.86 0.00 0.00 0.00
August 170.94 87.09 83.85 339.96 13.81 0.00 0.00 0.00
September 175.49 97.97 77.52 320.99 41.14 0.00 0.00 0.00
October 151.21 88.52 62.68 238.48 83.17 0.00 0.00 0.00
November 126.16 76.76 49.40 160.47 164.30 0.00 0.00 0.00
December 101.75 55.25 46.51 109.09 219.29 0.00 0.00 0.00
                 
Annual Sum or Average 157.45 85.45 72.00 257.95 97.10 0.00 0.00 0.00
Minimum of Months 101.75 55.25 46.51 109.09 6.86 0.00 0.00 0.00
Maximum of Months 204.29 109.33 94.96 407.88 219.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 111.67 84.62 27.06 146.83 89.20 0.00 0.00 0.00
February 105.07 74.51 30.55 141.11 79.40 0.00 0.00 0.00
March 82.19 46.57 35.63 113.38 68.18 0.00 0.00 0.00
April 57.27 21.50 35.77 92.64 38.61 0.00 0.00 0.00
May 40.64 5.96 34.68 77.73 19.86 0.00 0.00 0.00
June 34.76 2.19 32.58 86.17 8.05 0.00 0.00 0.00
July 35.30 3.13 32.17 86.57 5.59 0.00 0.00 0.00
August 44.56 11.32 33.24 98.89 9.55 0.00 0.00 0.00
September 70.57 36.67 33.91 135.67 23.22 0.00 0.00 0.00
October 96.87 65.81 31.06 154.76 42.29 0.00 0.00 0.00
November 116.59 89.18 27.41 162.46 74.20 0.00 0.00 0.00
December 114.65 86.13 28.51 148.19 95.29 0.00 0.00 0.00
                 
Annual Sum or Average 75.67 43.79 31.89 120.21 45.96 0.00 0.00 0.00
Minimum of Months 34.76 2.19 27.06 77.73 5.59 0.00 0.00 0.00
Maximum of Months 116.59 89.18 35.77 162.46 95.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.32 0.00 16.32 3.62 90.39 0.00 0.00 0.00
February 19.93 0.00 19.93 10.40 78.15 0.00 0.00 0.00
March 26.09 0.00 26.09 21.37 63.04 0.00 0.00 0.00
April 30.29 0.39 29.91 43.83 29.66 0.00 0.00 0.00
May 35.78 2.64 33.15 72.80 12.63 0.00 0.00 0.00
June 38.05 4.74 33.31 101.15 4.15 0.00 0.00 0.00
July 35.16 3.45 31.71 94.69 2.07 0.00 0.00 0.00
August 29.73 0.71 29.03 75.55 4.62 0.00 0.00 0.00
September 25.87 0.03 25.84 55.18 15.53 0.00 0.00 0.00
October 21.44 0.00 21.44 29.73 34.10 0.00 0.00 0.00
November 17.31 0.00 17.31 8.11 72.40 0.00 0.00 0.00
December 16.19 0.00 16.19 2.46 100.42 0.00 0.00 0.00
                 
Annual Sum or Average 26.04 1.00 25.04 43.41 42.10 0.00 0.00 0.00
Minimum of Months 16.19 0.00 16.19 2.46 2.07 0.00 0.00 0.00
Maximum of Months 38.05 4.74 33.31 101.15 100.42 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 101.70 55.11 46.60 95.67 194.75 0.00 0.00 0.00
February 136.50 77.83 58.67 153.15 167.70 0.00 0.00 0.00
March 168.25 92.64 75.61 208.89 135.81 0.00 0.00 0.00
April 202.82 112.49 90.33 310.16 67.96 0.00 0.00 0.00
May 209.08 113.58 95.50 367.85 32.33 0.00 0.00 0.00
June 209.17 116.31 92.86 425.66 11.62 0.00 0.00 0.00
July 187.70 98.13 89.57 387.06 6.61 0.00 0.00 0.00
August 178.80 91.56 87.24 352.65 13.18 0.00 0.00 0.00
September 177.40 101.30 76.10 317.17 38.57 0.00 0.00 0.00
October 135.78 73.14 62.64 201.20 80.17 0.00 0.00 0.00
November 121.58 70.62 50.96 134.18 157.79 0.00 0.00 0.00
December 101.78 53.93 47.85 91.42 213.59 0.00 0.00 0.00
                 
Annual Sum or Average 160.90 88.01 72.89 254.11 93.00 0.00 0.00 0.00
Minimum of Months 101.70 53.93 46.60 91.42 6.61 0.00 0.00 0.00
Maximum of Months 209.17 116.31 95.50 425.66 213.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 139.62 105.79 33.83 188.94 98.86 0.00 0.00 0.00
February 131.36 93.16 38.20 180.59 87.22 0.00 0.00 0.00
March 102.76 58.22 44.54 144.51 75.64 0.00 0.00 0.00
April 71.60 26.88 44.73 117.12 40.60 0.00 0.00 0.00
May 50.81 7.45 43.36 98.90 19.03 0.00 0.00 0.00
June 43.46 2.73 40.73 110.64 6.54 0.00 0.00 0.00
July 44.14 3.91 40.22 111.91 3.66 0.00 0.00 0.00
August 55.72 14.16 41.56 127.01 7.44 0.00 0.00 0.00
September 88.23 45.84 42.39 171.61 22.01 0.00 0.00 0.00
October 121.11 82.28 38.83 197.07 42.92 0.00 0.00 0.00
November 145.77 111.49 34.27 207.22 81.20 0.00 0.00 0.00
December 143.34 107.69 35.65 191.10 107.19 0.00 0.00 0.00
                 
Annual Sum or Average 94.61 54.74 39.87 153.69 49.18 0.00 0.00 0.00
Minimum of Months 43.46 2.73 33.83 98.90 3.66 0.00 0.00 0.00
Maximum of Months 145.77 111.49 44.73 207.22 107.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.40 0.00 20.40 4.33 110.31 0.00 0.00 0.00
February 24.91 0.00 24.91 11.39 97.20 0.00 0.00 0.00
March 32.60 0.00 32.60 23.27 79.76 0.00 0.00 0.00
April 37.86 0.48 37.38 47.81 39.34 0.00 0.00 0.00
May 44.72 3.30 41.43 82.56 17.47 0.00 0.00 0.00
June 47.56 5.93 41.63 117.26 6.30 0.00 0.00 0.00
July 43.94 4.31 39.63 109.52 3.49 0.00 0.00 0.00
August 37.16 0.88 36.28 85.98 7.07 0.00 0.00 0.00
September 32.33 0.04 32.29 61.66 21.86 0.00 0.00 0.00
October 26.80 0.00 26.80 32.34 44.58 0.00 0.00 0.00
November 21.63 0.00 21.63 8.46 90.51 0.00 0.00 0.00
December 20.24 0.00 20.24 2.99 122.08 0.00 0.00 0.00
                 
Annual Sum or Average 32.55 1.25 31.30 49.17 53.12 0.00 0.00 0.00
Minimum of Months 20.24 0.00 20.24 2.99 3.49 0.00 0.00 0.00
Maximum of Months 47.56 5.93 41.63 117.26 122.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 101.70 55.11 46.60 100.85 186.73 0.00 0.00 0.00
February 136.50 77.83 58.67 159.00 161.99 0.00 0.00 0.00
March 168.25 92.64 75.61 213.58 132.88 0.00 0.00 0.00
April 202.82 112.49 90.33 312.25 67.14 0.00 0.00 0.00
May 209.08 113.58 95.50 368.35 32.20 0.00 0.00 0.00
June 209.17 116.31 92.86 425.61 11.63 0.00 0.00 0.00
July 187.70 98.13 89.57 387.24 6.60 0.00 0.00 0.00
August 178.80 91.56 87.24 353.83 12.98 0.00 0.00 0.00
September 177.40 101.30 76.10 319.86 37.59 0.00 0.00 0.00
October 135.78 73.14 62.64 205.45 77.76 0.00 0.00 0.00
November 121.58 70.62 50.96 140.23 151.68 0.00 0.00 0.00
December 101.78 53.93 47.85 95.73 204.75 0.00 0.00 0.00
                 
Annual Sum or Average 160.90 88.01 72.89 257.17 89.99 0.00 0.00 0.00
Minimum of Months 101.70 53.93 46.60 95.73 6.60 0.00 0.00 0.00
Maximum of Months 209.17 116.31 95.50 425.61 204.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.83 0.00 25.83 3.57 156.83 0.00 0.00 0.00
February 31.55 0.00 31.55 12.62 138.16 0.00 0.00 0.00
March 41.29 0.00 41.29 28.24 113.65 0.00 0.00 0.00
April 47.95 0.61 47.34 59.14 61.61 0.00 0.00 0.00
May 56.64 4.17 52.47 99.53 31.73 0.00 0.00 0.00
June 60.23 7.51 52.73 140.82 13.85 0.00 0.00 0.00
July 55.65 5.46 50.19 130.16 9.96 0.00 0.00 0.00
August 47.06 1.12 45.94 101.27 16.36 0.00 0.00 0.00
September 40.94 0.05 40.89 73.62 39.56 0.00 0.00 0.00
October 33.94 0.00 33.94 36.69 72.54 0.00 0.00 0.00
November 27.40 0.00 27.40 7.92 134.40 0.00 0.00 0.00
December 25.63 0.00 25.63 2.50 171.22 0.00 0.00 0.00
                 
Annual Sum or Average 41.22 1.58 39.64 58.24 79.70 0.00 0.00 0.00
Minimum of Months 25.63 0.00 25.63 2.50 9.96 0.00 0.00 0.00
Maximum of Months 60.23 7.51 52.73 140.82 171.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.52 0.00 9.52 1.32 57.81 0.00 0.00 0.00
February 11.63 0.00 11.63 4.65 50.93 0.00 0.00 0.00
March 15.22 0.00 15.22 10.41 41.90 0.00 0.00 0.00
April 17.68 0.23 17.45 21.80 22.71 0.00 0.00 0.00
May 20.88 1.54 19.34 36.69 11.70 0.00 0.00 0.00
June 22.20 2.77 19.44 51.91 5.10 0.00 0.00 0.00
July 20.51 2.01 18.50 47.98 3.67 0.00 0.00 0.00
August 17.35 0.41 16.94 37.33 6.03 0.00 0.00 0.00
September 15.09 0.02 15.07 27.14 14.58 0.00 0.00 0.00
October 12.51 0.00 12.51 13.53 26.74 0.00 0.00 0.00
November 10.10 0.00 10.10 2.92 49.55 0.00 0.00 0.00
December 9.45 0.00 9.45 0.92 63.12 0.00 0.00 0.00
                 
Annual Sum or Average 15.20 0.58 14.61 21.47 29.38 0.00 0.00 0.00
Minimum of Months 9.45 0.00 9.45 0.92 3.67 0.00 0.00 0.00
Maximum of Months 22.20 2.77 19.44 51.91 63.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 65.15 49.36 15.78 88.27 49.82 0.00 0.00 0.00
February 61.29 43.47 17.82 84.70 44.44 0.00 0.00 0.00
March 47.95 27.17 20.78 67.89 39.10 0.00 0.00 0.00
April 33.41 12.54 20.87 54.51 23.11 0.00 0.00 0.00
May 23.71 3.48 20.23 44.55 12.61 0.00 0.00 0.00
June 20.28 1.28 19.00 48.91 5.36 0.00 0.00 0.00
July 20.59 1.83 18.77 49.22 3.88 0.00 0.00 0.00
August 26.00 6.60 19.39 56.77 6.28 0.00 0.00 0.00
September 41.17 21.39 19.78 78.82 14.38 0.00 0.00 0.00
October 56.51 38.39 18.12 90.86 25.01 0.00 0.00 0.00
November 68.01 52.02 15.99 96.31 42.70 0.00 0.00 0.00
December 66.88 50.25 16.63 89.25 53.21 0.00 0.00 0.00
                 
Annual Sum or Average 44.14 25.54 18.60 70.74 26.57 0.00 0.00 0.00
Minimum of Months 20.28 1.28 15.78 44.55 3.88 0.00 0.00 0.00
Maximum of Months 68.01 52.02 20.87 96.31 53.21 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 176.82 133.98 42.84 239.59 135.22 0.00 0.00 0.00
February 166.36 117.98 48.38 229.90 120.62 0.00 0.00 0.00
March 130.14 73.73 56.41 184.26 106.13 0.00 0.00 0.00
April 90.68 34.04 56.64 147.96 62.72 0.00 0.00 0.00
May 64.35 9.44 54.91 120.93 34.22 0.00 0.00 0.00
June 55.04 3.46 51.58 132.74 14.55 0.00 0.00 0.00
July 55.90 4.96 50.94 133.58 10.52 0.00 0.00 0.00
August 70.56 17.93 52.63 154.09 17.04 0.00 0.00 0.00
September 111.74 58.05 53.69 213.93 39.04 0.00 0.00 0.00
October 153.38 104.21 49.17 246.62 67.89 0.00 0.00 0.00
November 184.60 141.20 43.40 261.40 115.89 0.00 0.00 0.00
December 181.53 136.38 45.15 242.24 144.41 0.00 0.00 0.00
                 
Annual Sum or Average 119.82 69.33 50.49 192.00 72.11 0.00 0.00 0.00
Minimum of Months 55.04 3.46 42.84 120.93 10.52 0.00 0.00 0.00
Maximum of Months 184.60 141.20 56.64 261.40 144.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 139.62 105.79 33.83 188.93 97.91 0.00 0.00 0.00
February 131.36 93.16 38.20 181.60 85.84 0.00 0.00 0.00
March 102.76 58.22 44.54 145.52 74.70 0.00 0.00 0.00
April 71.60 26.88 44.73 118.03 39.47 0.00 0.00 0.00
May 50.81 7.45 43.36 99.90 18.28 0.00 0.00 0.00
June 43.46 2.73 40.73 111.64 6.26 0.00 0.00 0.00
July 44.14 3.91 40.22 112.45 3.48 0.00 0.00 0.00
August 55.72 14.16 41.56 127.22 7.08 0.00 0.00 0.00
September 88.23 45.84 42.39 171.24 21.46 0.00 0.00 0.00
October 121.11 82.28 38.83 196.60 42.45 0.00 0.00 0.00
November 145.77 111.49 34.27 207.51 80.12 0.00 0.00 0.00
December 143.34 107.69 35.65 191.54 106.01 0.00 0.00 0.00
                 
Annual Sum or Average 94.61 54.74 39.87 154.15 48.41 0.00 0.00 0.00
Minimum of Months 43.46 2.73 33.83 99.90 3.48 0.00 0.00 0.00
Maximum of Months 145.77 111.49 44.73 207.51 106.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 107.40 60.54 46.87 114.26 201.77 0.00 0.00 0.00
February 120.90 64.15 56.75 139.15 176.57 0.00 0.00 0.00
March 164.97 88.46 76.51 212.14 144.28 0.00 0.00 0.00
April 189.31 102.11 87.19 292.56 72.72 0.00 0.00 0.00
May 204.29 109.33 94.96 359.67 33.74 0.00 0.00 0.00
June 198.79 106.74 92.05 406.55 11.66 0.00 0.00 0.00
July 176.54 87.72 88.82 366.44 6.29 0.00 0.00 0.00
August 170.94 87.09 83.85 337.24 13.11 0.00 0.00 0.00
September 175.49 97.97 77.52 316.27 40.55 0.00 0.00 0.00
October 151.21 88.52 62.68 232.80 82.89 0.00 0.00 0.00
November 126.16 76.76 49.40 153.74 165.23 0.00 0.00 0.00
December 101.75 55.25 46.51 102.71 221.90 0.00 0.00 0.00
                 
Annual Sum or Average 157.45 85.45 72.00 253.30 97.18 0.00 0.00 0.00
Minimum of Months 101.75 55.25 46.51 102.71 6.29 0.00 0.00 0.00
Maximum of Months 204.29 109.33 94.96 406.55 221.90 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.40 0.00 20.40 5.13 108.44 0.00 0.00 0.00
February 24.91 0.00 24.91 12.83 94.44 0.00 0.00 0.00
March 32.60 0.00 32.60 25.21 77.73 0.00 0.00 0.00
April 37.86 0.48 37.38 49.77 37.99 0.00 0.00 0.00
May 44.72 3.30 41.43 83.90 16.87 0.00 0.00 0.00
June 47.56 5.93 41.63 117.92 6.06 0.00 0.00 0.00
July 43.94 4.31 39.63 109.94 3.33 0.00 0.00 0.00
August 37.16 0.88 36.28 86.71 6.74 0.00 0.00 0.00
September 32.33 0.04 32.29 62.35 21.16 0.00 0.00 0.00
October 26.80 0.00 26.80 33.55 43.55 0.00 0.00 0.00
November 21.63 0.00 21.63 9.63 88.54 0.00 0.00 0.00
December 20.24 0.00 20.24 3.73 119.76 0.00 0.00 0.00
                 
Annual Sum or Average 32.55 1.25 31.30 50.25 51.85 0.00 0.00 0.00
Minimum of Months 20.24 0.00 20.24 3.73 3.33 0.00 0.00 0.00
Maximum of Months 47.56 5.93 41.63 117.92 119.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 107.40 60.54 46.87 121.68 195.29 0.00 0.00 0.00
February 120.90 64.15 56.75 146.42 171.28 0.00 0.00 0.00
March 164.97 88.46 76.51 218.04 141.27 0.00 0.00 0.00
April 189.31 102.11 87.19 295.34 71.75 0.00 0.00 0.00
May 204.29 109.33 94.96 360.29 33.59 0.00 0.00 0.00
June 198.79 106.74 92.05 406.37 11.67 0.00 0.00 0.00
July 176.54 87.72 88.82 366.55 6.27 0.00 0.00 0.00
August 170.94 87.09 83.85 338.55 12.88 0.00 0.00 0.00
September 175.49 97.97 77.52 319.40 39.40 0.00 0.00 0.00
October 151.21 88.52 62.68 238.19 80.07 0.00 0.00 0.00
November 126.16 76.76 49.40 161.18 159.53 0.00 0.00 0.00
December 101.75 55.25 46.51 109.89 215.31 0.00 0.00 0.00
                 
Annual Sum or Average 157.45 85.45 72.00 257.31 94.50 0.00 0.00 0.00
Minimum of Months 101.75 55.25 46.51 109.89 6.27 0.00 0.00 0.00
Maximum of Months 204.29 109.33 94.96 406.37 215.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 204.76 155.16 49.61 269.03 150.76 0.00 0.00 0.00
February 192.65 136.63 56.02 259.50 131.42 0.00 0.00 0.00
March 150.71 85.38 65.33 209.51 111.58 0.00 0.00 0.00
April 105.01 39.42 65.59 174.21 56.95 0.00 0.00 0.00
May 74.52 10.93 63.59 151.45 25.36 0.00 0.00 0.00
June 63.74 4.01 59.73 170.72 8.16 0.00 0.00 0.00
July 64.73 5.74 58.99 171.15 4.34 0.00 0.00 0.00
August 81.71 20.76 60.95 191.19 9.57 0.00 0.00 0.00
September 129.40 67.23 62.17 252.83 30.49 0.00 0.00 0.00
October 177.62 120.68 56.94 286.47 63.13 0.00 0.00 0.00
November 213.78 163.52 50.26 298.62 122.20 0.00 0.00 0.00
December 210.22 157.93 52.28 271.85 163.14 0.00 0.00 0.00
                 
Annual Sum or Average 138.75 80.29 58.47 225.28 72.82 0.00 0.00 0.00
Minimum of Months 63.74 4.01 49.61 151.45 4.34 0.00 0.00 0.00
Maximum of Months 213.78 163.52 65.59 298.62 163.14 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 142.78 0.00 142.78 15.55 919.78 0.00 0.00 0.00
February 174.35 0.00 174.35 63.66 805.89 0.00 0.00 0.00
March 228.22 0.01 228.21 144.98 666.27 0.00 0.00 0.00
April 265.01 3.38 261.64 320.23 358.11 0.00 0.00 0.00
May 313.05 23.07 289.98 548.04 184.19 0.00 0.00 0.00
June 332.91 41.48 291.42 774.30 84.43 0.00 0.00 0.00
July 307.56 30.17 277.39 714.65 63.43 0.00 0.00 0.00
August 260.12 6.19 253.93 560.71 99.09 0.00 0.00 0.00
September 226.30 0.29 226.02 415.58 220.82 0.00 0.00 0.00
October 187.59 0.00 187.59 207.93 406.55 0.00 0.00 0.00
November 151.44 0.00 151.44 43.82 759.69 0.00 0.00 0.00
December 141.68 0.00 141.68 10.85 1001.11 0.00 0.00 0.00
                 
Annual Sum or Average 227.84 8.76 219.09 319.68 462.49 0.00 0.00 0.00
Minimum of Months 141.68 0.00 141.68 10.85 63.43 0.00 0.00 0.00
Maximum of Months 332.91 41.48 291.42 774.30 1001.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 142.78 0.00 142.78 11.54 961.27 0.00 0.00 0.00
February 174.35 0.00 174.35 55.99 839.97 0.00 0.00 0.00
March 228.22 0.01 228.21 132.95 692.95 0.00 0.00 0.00
April 265.01 3.38 261.64 305.80 371.72 0.00 0.00 0.00
May 313.05 23.07 289.98 531.44 191.63 0.00 0.00 0.00
June 332.91 41.48 291.42 756.62 88.94 0.00 0.00 0.00
July 307.56 30.17 277.39 697.28 67.96 0.00 0.00 0.00
August 260.12 6.19 253.93 544.14 104.67 0.00 0.00 0.00
September 226.30 0.29 226.02 402.26 230.13 0.00 0.00 0.00
October 187.59 0.00 187.59 197.07 422.59 0.00 0.00 0.00
November 151.44 0.00 151.44 37.50 790.32 0.00 0.00 0.00
December 141.68 0.00 141.68 8.15 1045.20 0.00 0.00 0.00
                 
Annual Sum or Average 227.84 8.76 219.09 308.04 482.27 0.00 0.00 0.00
Minimum of Months 141.68 0.00 141.68 8.15 67.96 0.00 0.00 0.00
Maximum of Months 332.91 41.48 291.42 756.62 1045.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.40 0.00 20.40 2.54 134.14 0.00 0.00 0.00
February 24.91 0.00 24.91 10.71 117.25 0.00 0.00 0.00
March 32.60 0.00 32.60 23.23 97.31 0.00 0.00 0.00
April 37.86 0.48 37.38 53.86 53.06 0.00 0.00 0.00
May 44.72 3.30 41.43 90.22 29.40 0.00 0.00 0.00
June 47.56 5.93 41.63 125.88 15.00 0.00 0.00 0.00
July 43.94 4.31 39.63 118.20 12.01 0.00 0.00 0.00
August 37.16 0.88 36.28 95.00 16.85 0.00 0.00 0.00
September 32.33 0.04 32.29 72.49 32.18 0.00 0.00 0.00
October 26.80 0.00 26.80 36.94 58.20 0.00 0.00 0.00
November 21.63 0.00 21.63 8.18 109.26 0.00 0.00 0.00
December 20.24 0.00 20.24 1.94 144.91 0.00 0.00 0.00
                 
Annual Sum or Average 32.55 1.25 31.30 53.49 68.07 0.00 0.00 0.00
Minimum of Months 20.24 0.00 20.24 1.94 12.01 0.00 0.00 0.00
Maximum of Months 47.56 5.93 41.63 125.88 144.91 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 203.40 110.21 93.19 190.34 455.85 0.00 0.00 0.00
February 272.98 155.65 117.32 313.82 395.30 0.00 0.00 0.00
March 336.47 185.26 151.21 428.31 327.86 0.00 0.00 0.00
April 405.62 224.97 180.65 647.17 184.88 0.00 0.00 0.00
May 418.14 227.15 190.99 764.41 108.70 0.00 0.00 0.00
June 418.31 232.60 185.71 881.15 56.06 0.00 0.00 0.00
July 375.38 196.25 179.13 804.21 45.48 0.00 0.00 0.00
August 357.58 183.11 174.47 739.63 62.93 0.00 0.00 0.00
September 354.77 202.59 152.18 680.23 114.99 0.00 0.00 0.00
October 271.54 146.27 125.28 428.27 206.50 0.00 0.00 0.00
November 243.14 141.22 101.92 277.01 368.85 0.00 0.00 0.00
December 203.55 107.86 95.69 183.15 489.76 0.00 0.00 0.00
                 
Annual Sum or Average 321.77 176.00 145.77 528.88 234.03 0.00 0.00 0.00
Minimum of Months 203.40 107.86 93.19 183.15 45.48 0.00 0.00 0.00
Maximum of Months 418.31 232.60 190.99 881.15 489.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 139.62 105.79 33.83 190.25 116.52 0.00 0.00 0.00
February 131.36 93.16 38.20 183.55 103.40 0.00 0.00 0.00
March 102.76 58.22 44.54 147.73 90.79 0.00 0.00 0.00
April 71.60 26.88 44.73 123.66 53.75 0.00 0.00 0.00
May 50.81 7.45 43.36 105.86 30.94 0.00 0.00 0.00
June 43.46 2.73 40.73 118.78 15.29 0.00 0.00 0.00
July 44.14 3.91 40.22 120.36 12.28 0.00 0.00 0.00
August 55.72 14.16 41.56 136.56 17.19 0.00 0.00 0.00
September 88.23 45.84 42.39 183.76 31.97 0.00 0.00 0.00
October 121.11 82.28 38.83 204.77 55.26 0.00 0.00 0.00
November 145.77 111.49 34.27 211.71 95.53 0.00 0.00 0.00
December 143.34 107.69 35.65 192.63 123.35 0.00 0.00 0.00
                 
Annual Sum or Average 94.61 54.74 39.87 159.78 61.99 0.00 0.00 0.00
Minimum of Months 43.46 2.73 33.83 105.86 12.28 0.00 0.00 0.00
Maximum of Months 145.77 111.49 44.73 211.71 123.35 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.83 0.00 25.83 2.80 158.24 0.00 0.00 0.00
February 31.55 0.00 31.55 10.95 139.91 0.00 0.00 0.00
March 41.29 0.00 41.29 25.43 116.01 0.00 0.00 0.00
April 47.95 0.61 47.34 54.55 64.45 0.00 0.00 0.00
May 56.64 4.17 52.47 95.35 33.21 0.00 0.00 0.00
June 60.23 7.51 52.73 136.50 14.96 0.00 0.00 0.00
July 55.65 5.46 50.19 125.57 11.20 0.00 0.00 0.00
August 47.06 1.12 45.94 97.06 17.86 0.00 0.00 0.00
September 40.94 0.05 40.89 70.35 41.22 0.00 0.00 0.00
October 33.94 0.00 33.94 33.62 75.04 0.00 0.00 0.00
November 27.40 0.00 27.40 6.51 135.23 0.00 0.00 0.00
December 25.63 0.00 25.63 2.07 172.44 0.00 0.00 0.00
                 
Annual Sum or Average 41.22 1.58 39.64 55.30 81.36 0.00 0.00 0.00
Minimum of Months 25.63 0.00 25.63 2.07 11.20 0.00 0.00 0.00
Maximum of Months 60.23 7.51 52.73 136.50 172.44 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.11 0.00 23.11 2.51 141.58 0.00 0.00 0.00
February 28.22 0.00 28.22 9.80 125.18 0.00 0.00 0.00
March 36.94 0.00 36.94 22.75 103.80 0.00 0.00 0.00
April 42.90 0.55 42.35 48.80 57.67 0.00 0.00 0.00
May 50.68 3.73 46.94 85.31 29.72 0.00 0.00 0.00
June 53.89 6.72 47.17 122.13 13.38 0.00 0.00 0.00
July 49.79 4.88 44.90 112.35 10.02 0.00 0.00 0.00
August 42.11 1.00 41.11 86.84 15.98 0.00 0.00 0.00
September 36.63 0.05 36.59 62.94 36.88 0.00 0.00 0.00
October 30.37 0.00 30.37 30.08 67.14 0.00 0.00 0.00
November 24.51 0.00 24.51 5.83 120.99 0.00 0.00 0.00
December 22.93 0.00 22.93 1.85 154.27 0.00 0.00 0.00
                 
Annual Sum or Average 36.88 1.42 35.46 49.47 72.79 0.00 0.00 0.00
Minimum of Months 22.93 0.00 22.93 1.85 10.02 0.00 0.00 0.00
Maximum of Months 53.89 6.72 47.17 122.13 154.27 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 521.24 394.96 126.28 695.59 399.84 0.00 0.00 0.00
February 490.41 347.79 142.61 665.47 359.23 0.00 0.00 0.00
March 383.64 217.35 166.29 528.32 318.72 0.00 0.00 0.00
April 267.32 100.35 166.97 419.30 193.45 0.00 0.00 0.00
May 189.70 27.82 161.88 343.83 105.74 0.00 0.00 0.00
June 162.26 10.21 152.05 379.33 46.31 0.00 0.00 0.00
July 164.78 14.61 150.17 380.51 35.00 0.00 0.00 0.00
August 208.00 52.85 155.16 440.66 55.01 0.00 0.00 0.00
September 329.40 171.14 158.26 617.99 120.00 0.00 0.00 0.00
October 452.15 307.19 144.96 712.46 206.68 0.00 0.00 0.00
November 544.19 416.24 127.94 759.61 342.06 0.00 0.00 0.00
December 535.12 402.02 133.09 704.64 425.75 0.00 0.00 0.00
                 
Annual Sum or Average 353.20 204.38 148.83 553.17 216.61 0.00 0.00 0.00
Minimum of Months 162.26 10.21 126.28 343.83 35.00 0.00 0.00 0.00
Maximum of Months 544.19 416.24 166.97 759.61 425.75 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.189136E+10 0.143314E+10 0.458222E+09 0.250939E+10 0.141116E+10
February 0.160727E+10 0.113986E+10 0.467406E+09 0.217508E+10 0.113939E+10
March 0.139207E+10 0.788679E+09 0.603391E+09 0.193554E+10 0.111093E+10
April 0.938702E+09 0.352379E+09 0.586322E+09 0.147978E+10 0.657155E+09
May 0.688337E+09 0.100947E+09 0.587390E+09 0.121775E+10 0.390267E+09
June 0.569764E+09 35850177.24 0.533914E+09 0.125617E+10 0.177994E+09
July 0.597898E+09 53010019.83 0.544888E+09 0.132064E+10 0.139959E+09
August 0.754750E+09 0.191758E+09 0.562992E+09 0.155219E+10 0.211114E+09
September 0.115668E+10 0.600953E+09 0.555729E+09 0.214540E+10 0.431669E+09
October 0.164065E+10 0.111467E+10 0.525978E+09 0.258648E+10 0.731275E+09
November 0.191093E+10 0.146165E+10 0.449279E+09 0.265980E+10 0.116730E+10
December 0.194172E+10 0.145878E+10 0.482936E+09 0.252443E+10 0.150861E+10
           
Annual Sum or Average 0.150901E+11 0.873168E+10 0.635845E+10 0.233626E+11 0.907682E+10
Minimum of Months 0.569764E+09 35850177.24 0.449279E+09 0.121775E+10 0.139959E+09
Maximum of Months 0.194172E+10 0.146165E+10 0.603391E+09 0.265980E+10 0.150861E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.532594E+10 0.403562E+10 0.129032E+10 0.704941E+10 0.405525E+10
February 0.452597E+10 0.320978E+10 0.131618E+10 0.611588E+10 0.324890E+10
March 0.391998E+10 0.222087E+10 0.169911E+10 0.548997E+10 0.312870E+10
April 0.264332E+10 0.992277E+09 0.165105E+10 0.427372E+10 0.178579E+10
May 0.193831E+10 0.284261E+09 0.165405E+10 0.360530E+10 0.102903E+10
June 0.160442E+10 0.100952E+09 0.150347E+10 0.370550E+10 0.464145E+09
July 0.168364E+10 0.149273E+09 0.153437E+10 0.388299E+10 0.357712E+09
August 0.212533E+10 0.539978E+09 0.158535E+10 0.449762E+10 0.558074E+09
September 0.325714E+10 0.169224E+10 0.156490E+10 0.609315E+10 0.116649E+10
October 0.461996E+10 0.313884E+10 0.148112E+10 0.731112E+10 0.201917E+10
November 0.538106E+10 0.411592E+10 0.126514E+10 0.745931E+10 0.330898E+10
December 0.546774E+10 0.410783E+10 0.135992E+10 0.708571E+10 0.433442E+10
           
Annual Sum or Average 0.424928E+11 0.245878E+11 0.179050E+11 0.665697E+11 0.254567E+11
Minimum of Months 0.160442E+10 0.100952E+09 0.126514E+10 0.360530E+10 0.357712E+09
Maximum of Months 0.546774E+10 0.411592E+10 0.169911E+10 0.745931E+10 0.433442E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.691870E+10 0.524250E+10 0.167620E+10 0.930317E+10 0.557361E+10
February 0.587949E+10 0.416969E+10 0.170980E+10 0.807084E+10 0.447315E+10
March 0.509227E+10 0.288503E+10 0.220724E+10 0.720993E+10 0.434662E+10
April 0.343383E+10 0.128902E+10 0.214480E+10 0.559174E+10 0.250076E+10
May 0.251798E+10 0.369271E+09 0.214871E+10 0.466897E+10 0.144128E+10
June 0.208423E+10 0.131142E+09 0.195309E+10 0.483444E+10 0.632373E+09
July 0.218715E+10 0.193914E+09 0.199323E+10 0.506911E+10 0.488592E+09
August 0.276092E+10 0.701462E+09 0.205946E+10 0.591205E+10 0.752937E+09
September 0.423121E+10 0.219832E+10 0.203289E+10 0.806130E+10 0.155556E+10
October 0.600158E+10 0.407753E+10 0.192406E+10 0.964740E+10 0.274504E+10
November 0.699030E+10 0.534681E+10 0.164349E+10 0.985387E+10 0.453269E+10
December 0.710291E+10 0.533630E+10 0.176661E+10 0.934133E+10 0.595922E+10
           
Annual Sum or Average 0.552006E+11 0.319410E+11 0.232596E+11 0.875641E+11 0.350018E+11
Minimum of Months 0.208423E+10 0.131142E+09 0.164349E+10 0.466897E+10 0.488592E+09
Maximum of Months 0.710291E+10 0.534681E+10 0.220724E+10 0.985387E+10 0.595922E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.373955E+09 0.283356E+09 90599047.15 0.507741E+09 0.266349E+09
February 0.317786E+09 0.225371E+09 92415031.30 0.440913E+09 0.211471E+09
March 0.275237E+09 0.155935E+09 0.119302E+09 0.391786E+09 0.203876E+09
April 0.185599E+09 69671463.64 0.115927E+09 0.307699E+09 0.105505E+09
May 0.136098E+09 19958985.63 0.116139E+09 0.267753E+09 51514406.61
June 0.112654E+09 7088195.76 0.105566E+09 0.288968E+09 17426584.73
July 0.118216E+09 10480991.36 0.107735E+09 0.301650E+09 10183568.87
August 0.149228E+09 37913864.16 0.111315E+09 0.341864E+09 20314018.77
September 0.228697E+09 0.118819E+09 0.109878E+09 0.446598E+09 57872508.02
October 0.324385E+09 0.220389E+09 0.103996E+09 0.529194E+09 0.116997E+09
November 0.377825E+09 0.288994E+09 88830943.98 0.539335E+09 0.212108E+09
December 0.383911E+09 0.288426E+09 95485408.74 0.513656E+09 0.288157E+09
           
Annual Sum or Average 0.298359E+10 0.172640E+10 0.125719E+10 0.487716E+10 0.156177E+10
Minimum of Months 0.112654E+09 7088195.76 88830943.98 0.267753E+09 10183568.87
Maximum of Months 0.383911E+09 0.288994E+09 0.119302E+09 0.539335E+09 0.288157E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.287674E+09 0.162146E+09 0.125527E+09 0.306955E+09 0.550118E+09
February 0.292474E+09 0.155192E+09 0.137282E+09 0.337852E+09 0.436052E+09
March 0.441845E+09 0.236918E+09 0.204927E+09 0.571344E+09 0.394911E+09
April 0.490686E+09 0.264679E+09 0.226007E+09 0.762617E+09 0.194700E+09
May 0.547180E+09 0.292832E+09 0.254348E+09 0.968072E+09 95233568.32
June 0.515254E+09 0.276659E+09 0.238595E+09 0.105763E+10 32325466.60
July 0.472844E+09 0.234945E+09 0.237900E+09 0.985635E+09 18423872.51
August 0.457839E+09 0.233254E+09 0.224585E+09 0.907192E+09 37594331.37
September 0.454872E+09 0.253932E+09 0.200940E+09 0.824439E+09 0.109403E+09
October 0.404989E+09 0.237094E+09 0.167895E+09 0.626085E+09 0.229283E+09
November 0.327016E+09 0.198972E+09 0.128044E+09 0.399598E+09 0.438902E+09
December 0.272539E+09 0.147971E+09 0.124568E+09 0.274846E+09 0.605087E+09
           
Annual Sum or Average 0.496521E+10 0.269459E+10 0.227062E+10 0.802227E+10 0.314203E+10
Minimum of Months 0.272539E+09 0.147971E+09 0.124568E+09 0.274846E+09 18423872.51
Maximum of Months 0.547180E+09 0.292832E+09 0.254348E+09 0.105763E+10 0.605087E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 54635219.79 0.00 54635219.79 12421868.40 0.296352E+09
February 60259072.44 0.00 60259072.44 29536830.79 0.233851E+09
March 87327152.96 3456.98 87323695.98 65748081.69 0.213179E+09
April 98134921.78 1250183.62 96884738.16 0.128418E+09 0.101790E+09
May 0.119788E+09 8827959.99 0.110960E+09 0.224383E+09 47562107.32
June 0.123276E+09 15361483.16 0.107914E+09 0.305909E+09 16775183.22
July 0.117686E+09 11543657.45 0.106142E+09 0.295095E+09 9703668.62
August 99533259.29 2367984.07 97165275.22 0.232211E+09 19343785.47
September 83800633.79 105909.72 83694724.07 0.161925E+09 57198856.07
October 71778804.06 0.00 71778804.06 88506373.86 0.120989E+09
November 56077421.72 0.00 56077421.72 23073994.77 0.236231E+09
December 54212081.06 0.00 54212081.06 8892105.27 0.327041E+09
           
Annual Sum or Average 0.102651E+10 39460634.99 0.987047E+09 0.157612E+10 0.168002E+10
Minimum of Months 54212081.06 0.00 54212081.06 8892105.27 9703668.62
Maximum of Months 0.123276E+09 15361483.16 0.110960E+09 0.305909E+09 0.327041E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.287674E+09 0.162146E+09 0.125527E+09 0.324640E+09 0.533154E+09
February 0.292474E+09 0.155192E+09 0.137282E+09 0.353461E+09 0.423861E+09
March 0.441845E+09 0.236918E+09 0.204927E+09 0.585277E+09 0.387586E+09
April 0.490686E+09 0.264679E+09 0.226007E+09 0.769231E+09 0.192404E+09
May 0.547180E+09 0.292832E+09 0.254348E+09 0.969636E+09 94853032.86
June 0.515254E+09 0.276659E+09 0.238595E+09 0.105723E+10 32349550.86
July 0.472844E+09 0.234945E+09 0.237900E+09 0.985932E+09 18361922.52
August 0.457839E+09 0.233254E+09 0.224585E+09 0.910536E+09 36993339.15
September 0.454872E+09 0.253932E+09 0.200940E+09 0.832012E+09 0.106636E+09
October 0.404989E+09 0.237094E+09 0.167895E+09 0.638757E+09 0.222758E+09
November 0.327016E+09 0.198972E+09 0.128044E+09 0.415927E+09 0.425856E+09
December 0.272539E+09 0.147971E+09 0.124568E+09 0.292178E+09 0.587356E+09
           
Annual Sum or Average 0.496521E+10 0.269459E+10 0.227062E+10 0.813481E+10 0.306217E+10
Minimum of Months 0.272539E+09 0.147971E+09 0.124568E+09 0.292178E+09 18361922.52
Maximum of Months 0.547180E+09 0.292832E+09 0.254348E+09 0.105723E+10 0.587356E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.299104E+09 0.226640E+09 72464826.42 0.393281E+09 0.238915E+09
February 0.254178E+09 0.180261E+09 73917324.87 0.341381E+09 0.192079E+09
March 0.220146E+09 0.124724E+09 95422629.83 0.303670E+09 0.182619E+09
April 0.148450E+09 55726088.50 92723544.22 0.240119E+09 0.100087E+09
May 0.108857E+09 15964013.69 92892545.85 0.208191E+09 53205808.91
June 90105188.78 5669429.11 84435759.67 0.223350E+09 20874701.66
July 94554156.30 8383125.91 86171030.39 0.231874E+09 14970905.08
August 0.119359E+09 30325060.49 89033931.16 0.264859E+09 25565559.15
September 0.182921E+09 95036114.58 87885276.20 0.351662E+09 60178026.66
October 0.259457E+09 0.176276E+09 83180150.54 0.414509E+09 0.113262E+09
November 0.302200E+09 0.231149E+09 71050625.13 0.421086E+09 0.192333E+09
December 0.307068E+09 0.230695E+09 76373138.43 0.396914E+09 0.255217E+09
           
Annual Sum or Average 0.238640E+10 0.138085E+10 0.100555E+10 0.379090E+10 0.144931E+10
Minimum of Months 90105188.78 5669429.11 71050625.13 0.208191E+09 14970905.08
Maximum of Months 0.307068E+09 0.231149E+09 95422629.83 0.421086E+09 0.255217E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 43713969.60 0.00 43713969.60 9704887.14 0.242102E+09
February 48213648.10 0.00 48213648.10 25149655.52 0.189063E+09
March 69870982.94 2765.95 69868216.99 57242008.37 0.168837E+09
April 78518344.10 1000279.47 77518064.63 0.113607E+09 76890738.99
May 95843144.60 7063304.15 88779840.45 0.194994E+09 33815363.02
June 98633813.54 12290815.53 86342998.01 0.262173E+09 10763610.52
July 94160895.41 9236150.10 84924745.31 0.253615E+09 5540435.89
August 79637162.39 1894638.37 77742524.03 0.202349E+09 12371518.69
September 67049393.63 84739.01 66964654.62 0.143021E+09 40258526.93
October 57430655.00 0.00 57430655.00 79631418.21 91335854.75
November 44867884.08 0.00 44867884.08 21019159.04 0.187666E+09
December 43375413.74 0.00 43375413.74 6596807.47 0.268970E+09
           
Annual Sum or Average 0.821315E+09 31572692.58 0.789743E+09 0.136910E+10 0.132761E+10
Minimum of Months 43375413.74 0.00 43375413.74 6596807.47 5540435.89
Maximum of Months 98633813.54 12290815.53 88779840.45 0.262173E+09 0.268970E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.272406E+09 0.147604E+09 0.124803E+09 0.256244E+09 0.521623E+09
February 0.330219E+09 0.188293E+09 0.141926E+09 0.370504E+09 0.405697E+09
March 0.450634E+09 0.248122E+09 0.202511E+09 0.559493E+09 0.363758E+09
April 0.525720E+09 0.291582E+09 0.234138E+09 0.803938E+09 0.176161E+09
May 0.560008E+09 0.304221E+09 0.255786E+09 0.985239E+09 86594933.85
June 0.542173E+09 0.301473E+09 0.240700E+09 0.110332E+10 30112166.56
July 0.502747E+09 0.262839E+09 0.239908E+09 0.103671E+10 17707067.77
August 0.478911E+09 0.245239E+09 0.233671E+09 0.944537E+09 35313887.83
September 0.459814E+09 0.262571E+09 0.197243E+09 0.822109E+09 99960538.69
October 0.363675E+09 0.195894E+09 0.167781E+09 0.538890E+09 0.214731E+09
November 0.315129E+09 0.183035E+09 0.132093E+09 0.347790E+09 0.408979E+09
December 0.272612E+09 0.144459E+09 0.128153E+09 0.244865E+09 0.572080E+09
           
Annual Sum or Average 0.507405E+10 0.277533E+10 0.229871E+10 0.801364E+10 0.293272E+10
Minimum of Months 0.272406E+09 0.144459E+09 0.124803E+09 0.244865E+09 17707067.77
Maximum of Months 0.560008E+09 0.304221E+09 0.255786E+09 0.110332E+10 0.572080E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.373955E+09 0.283356E+09 90599047.15 0.506055E+09 0.264789E+09
February 0.317786E+09 0.225371E+09 92415031.30 0.436884E+09 0.210999E+09
March 0.275237E+09 0.155935E+09 0.119302E+09 0.387047E+09 0.202598E+09
April 0.185599E+09 69671463.64 0.115927E+09 0.303584E+09 0.105246E+09
May 0.136098E+09 19958985.63 0.116139E+09 0.264901E+09 50975257.25
June 0.112654E+09 7088195.76 0.105566E+09 0.286783E+09 16946456.22
July 0.118216E+09 10480991.36 0.107735E+09 0.299741E+09 9792206.14
August 0.149228E+09 37913864.16 0.111315E+09 0.340184E+09 19929786.28
September 0.228697E+09 0.118819E+09 0.109878E+09 0.444813E+09 57051968.73
October 0.324385E+09 0.220389E+09 0.103996E+09 0.527820E+09 0.114954E+09
November 0.377825E+09 0.288994E+09 88830943.98 0.537120E+09 0.210473E+09
December 0.383911E+09 0.288426E+09 95485408.74 0.511840E+09 0.287099E+09
           
Annual Sum or Average 0.298359E+10 0.172640E+10 0.125719E+10 0.484677E+10 0.155085E+10
Minimum of Months 0.112654E+09 7088195.76 88830943.98 0.264901E+09 9792206.14
Maximum of Months 0.383911E+09 0.288994E+09 0.119302E+09 0.537120E+09 0.287099E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 54635219.79 0.00 54635219.79 11609827.60 0.295466E+09
February 60259072.44 0.00 60259072.44 27550196.64 0.235157E+09
March 87327152.96 3456.98 87323695.98 62331413.29 0.213639E+09
April 98134921.78 1250183.62 96884738.16 0.123936E+09 0.101963E+09
May 0.119788E+09 8827959.99 0.110960E+09 0.221127E+09 46802687.52
June 0.123276E+09 15361483.16 0.107914E+09 0.303941E+09 16322502.51
July 0.117686E+09 11543657.45 0.106142E+09 0.293325E+09 9352811.58
August 99533259.29 2367984.07 97165275.22 0.230295E+09 18929448.73
September 83800633.79 105909.72 83694724.07 0.159823E+09 56651205.92
October 71778804.06 0.00 71778804.06 86617353.48 0.119400E+09
November 56077421.72 0.00 56077421.72 21922540.94 0.234593E+09
December 54212081.06 0.00 54212081.06 8005493.69 0.326969E+09
           
Annual Sum or Average 0.102651E+10 39460634.99 0.987047E+09 0.155048E+10 0.167525E+10
Minimum of Months 54212081.06 0.00 54212081.06 8005493.69 9352811.58
Maximum of Months 0.123276E+09 15361483.16 0.110960E+09 0.303941E+09 0.326969E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.272406E+09 0.147604E+09 0.124803E+09 0.270117E+09 0.500126E+09
February 0.330219E+09 0.188293E+09 0.141926E+09 0.384642E+09 0.391880E+09
March 0.450634E+09 0.248122E+09 0.202511E+09 0.572053E+09 0.355915E+09
April 0.525720E+09 0.291582E+09 0.234138E+09 0.809343E+09 0.174015E+09
May 0.560008E+09 0.304221E+09 0.255786E+09 0.986592E+09 86250809.28
June 0.542173E+09 0.301473E+09 0.240700E+09 0.110318E+10 30153063.12
July 0.502747E+09 0.262839E+09 0.239908E+09 0.103718E+10 17668027.97
August 0.478911E+09 0.245239E+09 0.233671E+09 0.947686E+09 34756074.04
September 0.459814E+09 0.262571E+09 0.197243E+09 0.829086E+09 97423093.94
October 0.363675E+09 0.195894E+09 0.167781E+09 0.550277E+09 0.208269E+09
November 0.315129E+09 0.183035E+09 0.132093E+09 0.363468E+09 0.393143E+09
December 0.272612E+09 0.144459E+09 0.128153E+09 0.256395E+09 0.548394E+09
           
Annual Sum or Average 0.507405E+10 0.277533E+10 0.229871E+10 0.811001E+10 0.283799E+10
Minimum of Months 0.272406E+09 0.144459E+09 0.124803E+09 0.256395E+09 17668027.97
Maximum of Months 0.560008E+09 0.304221E+09 0.255786E+09 0.110318E+10 0.548394E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 69192058.57 0.00 69192058.57 9565454.92 0.420050E+09
February 76314313.11 0.00 76314313.11 30541023.28 0.334231E+09
March 0.110594E+09 4378.05 0.110590E+09 75639160.96 0.304399E+09
April 0.124282E+09 1583278.67 0.122698E+09 0.153283E+09 0.159685E+09
May 0.151704E+09 11180054.31 0.140524E+09 0.266572E+09 84990722.68
June 0.156121E+09 19454349.17 0.136667E+09 0.365013E+09 35891140.84
July 0.149041E+09 14619313.80 0.134422E+09 0.348611E+09 26664166.16
August 0.126053E+09 2998902.41 0.123054E+09 0.271241E+09 43820155.46
September 0.106128E+09 134127.98 0.105994E+09 0.190819E+09 0.102528E+09
October 90903326.35 0.00 90903326.35 98279750.95 0.194289E+09
November 71018516.32 0.00 71018516.32 20523835.28 0.348362E+09
December 68656180.07 0.00 68656180.07 6688806.42 0.458598E+09
           
Annual Sum or Average 0.130001E+10 49974404.39 0.125003E+10 0.183678E+10 0.251351E+10
Minimum of Months 68656180.07 0.00 68656180.07 6688806.42 26664166.16
Maximum of Months 0.156121E+09 19454349.17 0.140524E+09 0.365013E+09 0.458598E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 25507057.81 0.00 25507057.81 3526222.76 0.154848E+09
February 28132615.74 0.00 28132615.74 11258685.79 0.123211E+09
March 40769649.09 1613.93 40768035.16 27883726.70 0.112214E+09
April 45815375.73 583662.08 45231713.65 56506401.72 58866454.03
May 55924379.60 4121430.95 51802948.65 98269390.27 31331099.57
June 57552732.16 7171678.64 50381053.51 0.134559E+09 13230960.65
July 54942788.87 5389284.40 49553504.47 0.128512E+09 9829515.72
August 46468205.09 1105519.60 45362685.49 99990754.53 16153923.75
September 39123254.53 49445.13 39073809.41 70343907.66 37796099.84
October 33510730.10 0.00 33510730.10 36229985.64 71622965.64
November 26180365.76 0.00 26180365.76 7565935.51 0.128421E+09
December 25309510.80 0.00 25309510.80 2465771.01 0.169058E+09
           
Annual Sum or Average 0.479237E+09 18422634.73 0.460814E+09 0.677112E+09 0.926583E+09
Minimum of Months 25309510.80 0.00 25309510.80 2465771.01 9829515.72
Maximum of Months 57552732.16 7171678.64 51802948.65 0.134559E+09 0.169058E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.174486E+09 0.132213E+09 42273150.31 0.236427E+09 0.133435E+09
February 0.148278E+09 0.105157E+09 43120481.20 0.204912E+09 0.107509E+09
March 0.128425E+09 72758842.37 55665836.43 0.181827E+09 0.104727E+09
April 86599719.45 32508424.18 54091295.27 0.141298E+09 59897867.18
May 63502666.49 9312782.27 54189884.22 0.119333E+09 33768480.89
June 52563848.94 3307323.58 49256525.36 0.126763E+09 13893355.04
July 55159202.88 4890388.33 50268814.55 0.131818E+09 10382875.26
August 69629375.31 17690456.23 51938919.07 0.152053E+09 16818835.74
September 0.106709E+09 55440358.52 51268838.62 0.204296E+09 37278411.91
October 0.151357E+09 0.102833E+09 48524052.02 0.243366E+09 66990388.39
November 0.176291E+09 0.134843E+09 41448160.50 0.249633E+09 0.110671E+09
December 0.179131E+09 0.134578E+09 44553106.94 0.239043E+09 0.142509E+09
           
Annual Sum or Average 0.139213E+10 0.805533E+09 0.586599E+09 0.223077E+10 0.837882E+09
Minimum of Months 52563848.94 3307323.58 41448160.50 0.119333E+09 10382875.26
Maximum of Months 0.179131E+09 0.134843E+09 55665836.43 0.249633E+09 0.142509E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.473590E+09 0.358852E+09 0.114738E+09 0.641710E+09 0.362170E+09
February 0.402456E+09 0.285418E+09 0.117038E+09 0.556172E+09 0.291802E+09
March 0.348571E+09 0.197482E+09 0.151088E+09 0.493517E+09 0.284250E+09
April 0.235049E+09 88234512.68 0.146815E+09 0.383511E+09 0.162575E+09
May 0.172359E+09 25276795.96 0.147082E+09 0.323894E+09 91654564.32
June 0.142669E+09 8976752.69 0.133692E+09 0.344061E+09 37709407.39
July 0.149713E+09 13273514.24 0.136440E+09 0.357782E+09 28181247.22
August 0.188988E+09 48015516.72 0.140973E+09 0.412702E+09 45649760.42
September 0.289631E+09 0.150476E+09 0.139154E+09 0.554500E+09 0.101181E+09
October 0.410813E+09 0.279109E+09 0.131704E+09 0.660546E+09 0.181826E+09
November 0.478491E+09 0.365992E+09 0.112499E+09 0.677555E+09 0.300385E+09
December 0.486199E+09 0.365273E+09 0.120926E+09 0.648811E+09 0.386798E+09
           
Annual Sum or Average 0.377853E+10 0.218638E+10 0.159215E+10 0.605476E+10 0.227418E+10
Minimum of Months 0.142669E+09 8976752.69 0.112499E+09 0.323894E+09 28181247.22
Maximum of Months 0.486199E+09 0.365992E+09 0.151088E+09 0.677555E+09 0.386798E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.373955E+09 0.283356E+09 90599047.15 0.506036E+09 0.262253E+09
February 0.317786E+09 0.225371E+09 92415031.30 0.439328E+09 0.207666E+09
March 0.275237E+09 0.155935E+09 0.119302E+09 0.389768E+09 0.200071E+09
April 0.185599E+09 69671463.64 0.115927E+09 0.305938E+09 0.102315E+09
May 0.136098E+09 19958985.63 0.116139E+09 0.267565E+09 48965892.10
June 0.112654E+09 7088195.76 0.105566E+09 0.289364E+09 16221336.17
July 0.118216E+09 10480991.36 0.107735E+09 0.301197E+09 9329347.43
August 0.149228E+09 37913864.16 0.111315E+09 0.340751E+09 18963078.21
September 0.228697E+09 0.118819E+09 0.109878E+09 0.443851E+09 55634141.39
October 0.324385E+09 0.220389E+09 0.103996E+09 0.526586E+09 0.113699E+09
November 0.377825E+09 0.288994E+09 88830943.98 0.537865E+09 0.207668E+09
December 0.383911E+09 0.288426E+09 95485408.74 0.513026E+09 0.283932E+09
           
Annual Sum or Average 0.298359E+10 0.172640E+10 0.125719E+10 0.486127E+10 0.152672E+10
Minimum of Months 0.112654E+09 7088195.76 88830943.98 0.267565E+09 9329347.43
Maximum of Months 0.383911E+09 0.288994E+09 0.119302E+09 0.537865E+09 0.283932E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.287674E+09 0.162146E+09 0.125527E+09 0.306041E+09 0.540412E+09
February 0.292474E+09 0.155192E+09 0.137282E+09 0.336628E+09 0.427167E+09
March 0.441845E+09 0.236918E+09 0.204927E+09 0.568204E+09 0.386447E+09
April 0.490686E+09 0.264679E+09 0.226007E+09 0.758314E+09 0.188498E+09
May 0.547180E+09 0.292832E+09 0.254348E+09 0.963343E+09 90376873.33
June 0.515254E+09 0.276659E+09 0.238595E+09 0.105378E+10 30214174.68
July 0.472844E+09 0.234945E+09 0.237900E+09 0.981477E+09 16856551.28
August 0.457839E+09 0.233254E+09 0.224585E+09 0.903255E+09 35114544.10
September 0.454872E+09 0.253932E+09 0.200940E+09 0.819775E+09 0.105094E+09
October 0.404989E+09 0.237094E+09 0.167895E+09 0.623530E+09 0.222019E+09
November 0.327016E+09 0.198972E+09 0.128044E+09 0.398489E+09 0.428267E+09
December 0.272539E+09 0.147971E+09 0.124568E+09 0.275093E+09 0.594330E+09
           
Annual Sum or Average 0.496521E+10 0.269459E+10 0.227062E+10 0.798793E+10 0.306480E+10
Minimum of Months 0.272539E+09 0.147971E+09 0.124568E+09 0.275093E+09 16856551.28
Maximum of Months 0.547180E+09 0.292832E+09 0.254348E+09 0.105378E+10 0.594330E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 54635219.79 0.00 54635219.79 13742770.96 0.290437E+09
February 60259072.44 0.00 60259072.44 31042023.31 0.228480E+09
March 87327152.96 3456.98 87323695.98 67524240.43 0.208189E+09
April 98134921.78 1250183.62 96884738.16 0.129003E+09 98474028.52
May 0.119788E+09 8827959.99 0.110960E+09 0.224727E+09 45189351.82
June 0.123276E+09 15361483.16 0.107914E+09 0.305657E+09 15702236.74
July 0.117686E+09 11543657.45 0.106142E+09 0.294474E+09 8908853.40
August 99533259.29 2367984.07 97165275.22 0.232250E+09 18056047.58
September 83800633.79 105909.72 83694724.07 0.161611E+09 54847168.69
October 71778804.06 0.00 71778804.06 89847157.74 0.116647E+09
November 56077421.72 0.00 56077421.72 24971360.77 0.229505E+09
December 54212081.06 0.00 54212081.06 9991618.04 0.320766E+09
           
Annual Sum or Average 0.102651E+10 39460634.99 0.987047E+09 0.158484E+10 0.163520E+10
Minimum of Months 54212081.06 0.00 54212081.06 9991618.04 8908853.40
Maximum of Months 0.123276E+09 15361483.16 0.110960E+09 0.305657E+09 0.320766E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.287674E+09 0.162146E+09 0.125527E+09 0.325895E+09 0.523061E+09
February 0.292474E+09 0.155192E+09 0.137282E+09 0.354227E+09 0.414358E+09
March 0.441845E+09 0.236918E+09 0.204927E+09 0.583995E+09 0.378390E+09
April 0.490686E+09 0.264679E+09 0.226007E+09 0.765525E+09 0.185965E+09
May 0.547180E+09 0.292832E+09 0.254348E+09 0.965013E+09 89980165.84
June 0.515254E+09 0.276659E+09 0.238595E+09 0.105331E+10 30245131.82
July 0.472844E+09 0.234945E+09 0.237900E+09 0.981760E+09 16800496.29
August 0.457839E+09 0.233254E+09 0.224585E+09 0.906760E+09 34491453.24
September 0.454872E+09 0.253932E+09 0.200940E+09 0.827888E+09 0.102115E+09
October 0.404989E+09 0.237094E+09 0.167895E+09 0.637965E+09 0.214455E+09
November 0.327016E+09 0.198972E+09 0.128044E+09 0.417790E+09 0.413497E+09
December 0.272539E+09 0.147971E+09 0.124568E+09 0.294318E+09 0.576676E+09
           
Annual Sum or Average 0.496521E+10 0.269459E+10 0.227062E+10 0.811444E+10 0.298003E+10
Minimum of Months 0.272539E+09 0.147971E+09 0.124568E+09 0.294318E+09 16800496.29
Maximum of Months 0.547180E+09 0.292832E+09 0.254348E+09 0.105331E+10 0.576676E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.548441E+09 0.415568E+09 0.132872E+09 0.720569E+09 0.403784E+09
February 0.466063E+09 0.330528E+09 0.135536E+09 0.627784E+09 0.317924E+09
March 0.403662E+09 0.228694E+09 0.174968E+09 0.561162E+09 0.298844E+09
April 0.272199E+09 0.102180E+09 0.170019E+09 0.451546E+09 0.147621E+09
May 0.199600E+09 29271767.90 0.170329E+09 0.405650E+09 67913909.06
June 0.165218E+09 10395519.34 0.154822E+09 0.442496E+09 21139273.72
July 0.173375E+09 15371379.69 0.158004E+09 0.458421E+09 11630592.27
August 0.218858E+09 55604320.39 0.163253E+09 0.512087E+09 25637620.15
September 0.335406E+09 0.174259E+09 0.161147E+09 0.655344E+09 79030791.30
October 0.475742E+09 0.323222E+09 0.152520E+09 0.767294E+09 0.169082E+09
November 0.554116E+09 0.423837E+09 0.130279E+09 0.774017E+09 0.316754E+09
December 0.563043E+09 0.423004E+09 0.140039E+09 0.728111E+09 0.436943E+09
           
Annual Sum or Average 0.437572E+10 0.253194E+10 0.184379E+10 0.710448E+10 0.229630E+10
Minimum of Months 0.165218E+09 10395519.34 0.130279E+09 0.405650E+09 11630592.27
Maximum of Months 0.563043E+09 0.423837E+09 0.174968E+09 0.774017E+09 0.436943E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.382432E+09 0.00 0.382432E+09 41661808.54 0.246355E+10
February 0.421798E+09 0.00 0.421798E+09 0.154004E+09 0.194960E+10
March 0.611267E+09 24197.95 0.611243E+09 0.388310E+09 0.178455E+10
April 0.686918E+09 8750953.90 0.678167E+09 0.830028E+09 0.928219E+09
May 0.838485E+09 61793379.53 0.776691E+09 0.146786E+10 0.493323E+09
June 0.862899E+09 0.107526E+09 0.755372E+09 0.200698E+10 0.218844E+09
July 0.823767E+09 80802541.81 0.742965E+09 0.191411E+10 0.169889E+09
August 0.696706E+09 16575260.69 0.680131E+09 0.150180E+10 0.265407E+09
September 0.586582E+09 741339.97 0.585841E+09 0.107719E+10 0.572372E+09
October 0.502433E+09 0.00 0.502433E+09 0.556930E+09 0.108891E+10
November 0.392527E+09 0.00 0.392527E+09 0.113576E+09 0.196912E+10
December 0.379470E+09 0.00 0.379470E+09 29062726.31 0.268136E+10
           
Annual Sum or Average 0.718528E+10 0.276214E+09 0.690907E+10 0.100815E+11 0.145851E+11
Minimum of Months 0.379470E+09 0.00 0.379470E+09 29062726.31 0.169889E+09
Maximum of Months 0.862899E+09 0.107526E+09 0.776691E+09 0.200698E+10 0.268136E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.382432E+09 0.00 0.382432E+09 30903013.88 0.257468E+10
February 0.421798E+09 0.00 0.421798E+09 0.135454E+09 0.203207E+10
March 0.611267E+09 24197.95 0.611243E+09 0.356098E+09 0.185600E+10
April 0.686918E+09 8750953.90 0.678167E+09 0.792637E+09 0.963510E+09
May 0.838485E+09 61793379.53 0.776691E+09 0.142342E+10 0.513253E+09
June 0.862899E+09 0.107526E+09 0.755372E+09 0.196115E+10 0.230532E+09
July 0.823767E+09 80802541.81 0.742965E+09 0.186761E+10 0.182017E+09
August 0.696706E+09 16575260.69 0.680131E+09 0.145742E+10 0.280342E+09
September 0.586582E+09 741339.97 0.585841E+09 0.104267E+10 0.596488E+09
October 0.502433E+09 0.00 0.502433E+09 0.527825E+09 0.113186E+10
November 0.392527E+09 0.00 0.392527E+09 97200265.02 0.204852E+10
December 0.379470E+09 0.00 0.379470E+09 21840316.58 0.279947E+10
           
Annual Sum or Average 0.718528E+10 0.276214E+09 0.690907E+10 0.971423E+10 0.152087E+11
Minimum of Months 0.379470E+09 0.00 0.379470E+09 21840316.58 0.182017E+09
Maximum of Months 0.862899E+09 0.107526E+09 0.776691E+09 0.196115E+10 0.279947E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 54635219.79 0.00 54635219.79 6800242.32 0.359279E+09
February 60259072.44 0.00 60259072.44 25917023.51 0.283648E+09
March 87327152.96 3456.98 87323695.98 62218215.57 0.260639E+09
April 98134921.78 1250183.62 96884738.16 0.139615E+09 0.137535E+09
May 0.119788E+09 8827959.99 0.110960E+09 0.241650E+09 78742534.01
June 0.123276E+09 15361483.16 0.107914E+09 0.326282E+09 38871726.78
July 0.117686E+09 11543657.45 0.106142E+09 0.316583E+09 32175785.05
August 99533259.29 2367984.07 97165275.22 0.254452E+09 45137728.11
September 83800633.79 105909.72 83694724.07 0.187902E+09 83399872.24
October 71778804.06 0.00 71778804.06 98930622.02 0.155894E+09
November 56077421.72 0.00 56077421.72 21210061.52 0.283197E+09
December 54212081.06 0.00 54212081.06 5183467.49 0.388123E+09
           
Annual Sum or Average 0.102651E+10 39460634.99 0.987047E+09 0.168674E+10 0.214664E+10
Minimum of Months 54212081.06 0.00 54212081.06 5183467.49 32175785.05
Maximum of Months 0.123276E+09 15361483.16 0.110960E+09 0.326282E+09 0.388123E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.544774E+09 0.295186E+09 0.249587E+09 0.509796E+09 0.122095E+10
February 0.660391E+09 0.376560E+09 0.283831E+09 0.759187E+09 0.956303E+09
March 0.901204E+09 0.496210E+09 0.404994E+09 0.114718E+10 0.878129E+09
April 0.105137E+10 0.583122E+09 0.468243E+09 0.167747E+10 0.479207E+09
May 0.111994E+10 0.608399E+09 0.511536E+09 0.204738E+10 0.291138E+09
June 0.108427E+10 0.602903E+09 0.481366E+09 0.228394E+10 0.145300E+09
July 0.100542E+10 0.525641E+09 0.479782E+09 0.215399E+10 0.121804E+09
August 0.957753E+09 0.490444E+09 0.467309E+09 0.198102E+10 0.168551E+09
September 0.919563E+09 0.525105E+09 0.394458E+09 0.176316E+10 0.298053E+09
October 0.727299E+09 0.391760E+09 0.335538E+09 0.114708E+10 0.553093E+09
November 0.630213E+09 0.366045E+09 0.264168E+09 0.718007E+09 0.956062E+09
December 0.545185E+09 0.288898E+09 0.256287E+09 0.490549E+09 0.131178E+10
           
Annual Sum or Average 0.101474E+11 0.555027E+10 0.459710E+10 0.166788E+11 0.738036E+10
Minimum of Months 0.544774E+09 0.288898E+09 0.249587E+09 0.490549E+09 0.121804E+09
Maximum of Months 0.111994E+10 0.608399E+09 0.511536E+09 0.228394E+10 0.131178E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.373955E+09 0.283356E+09 90599047.15 0.509553E+09 0.312079E+09
February 0.317786E+09 0.225371E+09 92415031.30 0.444037E+09 0.250133E+09
March 0.275237E+09 0.155935E+09 0.119302E+09 0.395675E+09 0.243169E+09
April 0.185599E+09 69671463.64 0.115927E+09 0.320524E+09 0.139322E+09
May 0.136098E+09 19958985.63 0.116139E+09 0.283542E+09 82865139.31
June 0.112654E+09 7088195.76 0.105566E+09 0.307877E+09 39639236.20
July 0.118216E+09 10480991.36 0.107735E+09 0.322361E+09 32890216.07
August 0.149228E+09 37913864.16 0.111315E+09 0.365770E+09 46045506.34
September 0.228697E+09 0.118819E+09 0.109878E+09 0.476308E+09 82874209.88
October 0.324385E+09 0.220389E+09 0.103996E+09 0.548456E+09 0.148000E+09
November 0.377825E+09 0.288994E+09 88830943.98 0.548758E+09 0.247622E+09
December 0.383911E+09 0.288426E+09 95485408.74 0.515933E+09 0.330385E+09
           
Annual Sum or Average 0.298359E+10 0.172640E+10 0.125719E+10 0.503880E+10 0.195502E+10
Minimum of Months 0.112654E+09 7088195.76 88830943.98 0.283542E+09 32890216.07
Maximum of Months 0.383911E+09 0.288994E+09 0.119302E+09 0.548758E+09 0.330385E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 69192058.57 0.00 69192058.57 7500575.96 0.423834E+09
February 76314313.11 0.00 76314313.11 26496962.82 0.338472E+09
March 0.110594E+09 4378.05 0.110590E+09 68106369.76 0.310726E+09
April 0.124282E+09 1583278.67 0.122698E+09 0.141381E+09 0.167059E+09
May 0.151704E+09 11180054.31 0.140524E+09 0.255393E+09 88955912.52
June 0.156121E+09 19454349.17 0.136667E+09 0.353807E+09 38767769.72
July 0.149041E+09 14619313.80 0.134422E+09 0.336334E+09 29996852.84
August 0.126053E+09 2998902.41 0.123054E+09 0.259977E+09 47847435.53
September 0.106128E+09 134127.98 0.105994E+09 0.182344E+09 0.106830E+09
October 90903326.35 0.00 90903326.35 90053583.81 0.200990E+09
November 71018516.32 0.00 71018516.32 16875369.93 0.350515E+09
December 68656180.07 0.00 68656180.07 5551930.38 0.461853E+09
           
Annual Sum or Average 0.130001E+10 49974404.39 0.125003E+10 0.174382E+10 0.256585E+10
Minimum of Months 68656180.07 0.00 68656180.07 5551930.38 29996852.84
Maximum of Months 0.156121E+09 19454349.17 0.140524E+09 0.353807E+09 0.461853E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 61906396.97 0.00 61906396.97 6710793.73 0.379206E+09
February 68278705.09 0.00 68278705.09 23706933.03 0.302832E+09
March 98949165.36 3917.06 98945248.31 60935027.08 0.278008E+09
April 0.111195E+09 1416565.43 0.109779E+09 0.126495E+09 0.149469E+09
May 0.135730E+09 10002836.96 0.125727E+09 0.228501E+09 79589191.98
June 0.139682E+09 17405879.91 0.122276E+09 0.316552E+09 34685670.46
July 0.133348E+09 13079955.45 0.120268E+09 0.300919E+09 26838297.90
August 0.112780E+09 2683129.35 0.110097E+09 0.232603E+09 42809281.86
September 94953316.23 120004.81 94833311.42 0.163144E+09 95581113.97
October 81331550.52 0.00 81331550.52 80571282.64 0.179827E+09
November 63540535.64 0.00 63540535.64 15098457.41 0.313606E+09
December 61426944.44 0.00 61426944.44 4967333.15 0.413204E+09
           
Annual Sum or Average 0.116312E+10 44712288.96 0.111841E+10 0.156020E+10 0.229566E+10
Minimum of Months 61426944.44 0.00 61426944.44 4967333.15 26838297.90
Maximum of Months 0.139682E+09 17405879.91 0.125727E+09 0.316552E+09 0.413204E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.139608E+10 0.105785E+10 0.338233E+09 0.186307E+10 0.107094E+10
February 0.118639E+10 0.841376E+09 0.345013E+09 0.160991E+10 0.869045E+09
March 0.102754E+10 0.582153E+09 0.445390E+09 0.141505E+10 0.853657E+09
April 0.692896E+09 0.260104E+09 0.432792E+09 0.108683E+10 0.501434E+09
May 0.508093E+09 74512840.84 0.433581E+09 0.920904E+09 0.283218E+09
June 0.420571E+09 26462346.95 0.394108E+09 0.983226E+09 0.120030E+09
July 0.441336E+09 39128663.92 0.402208E+09 0.101917E+10 93741152.14
August 0.557114E+09 0.141544E+09 0.415570E+09 0.118027E+10 0.147350E+09
September 0.853795E+09 0.443586E+09 0.410209E+09 0.160183E+10 0.311028E+09
October 0.121103E+10 0.822779E+09 0.388248E+09 0.190826E+10 0.553585E+09
November 0.141053E+10 0.107890E+10 0.331632E+09 0.196891E+10 0.886609E+09
December 0.143326E+10 0.107678E+10 0.356475E+09 0.188730E+10 0.114033E+10
           
Annual Sum or Average 0.111386E+11 0.644518E+10 0.469346E+10 0.174447E+11 0.683097E+10
Minimum of Months 0.420571E+09 26462346.95 0.331632E+09 0.920904E+09 93741152.14
Maximum of Months 0.143326E+10 0.107890E+10 0.445390E+09 0.196891E+10 0.114033E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 936.90 526.87 706.15 535.07 171.08 0.00 0.00
February 899.09 470.98 664.38 471.17 193.21 0.00 0.00
March 722.65 414.77 519.74 294.46 225.28 0.00 0.00
April 570.90 253.53 362.15 135.95 226.20 0.00 0.00
May 454.65 145.71 257.00 37.69 219.31 0.00 0.00
June 484.63 68.67 219.82 13.83 205.99 0.00 0.00
July 493.07 52.25 223.23 19.79 203.44 0.00 0.00
August 579.52 78.82 281.79 71.59 210.20 0.00 0.00
September 827.70 166.54 446.25 231.85 214.40 0.00 0.00
October 965.68 273.03 612.55 416.17 196.38 0.00 0.00
November 1026.16 450.35 737.24 563.91 173.33 0.00 0.00
December 942.51 563.25 724.95 544.65 180.31 0.00 0.00
               
Annual Sum or Average 740.82 287.82 478.50 276.88 201.63 0.00 0.00
Minimum of Months 454.65 52.25 219.82 13.83 171.08 0.00 0.00
Maximum of Months 1026.16 563.25 737.24 563.91 226.20 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2631.95 1514.06 1988.48 1506.73 481.75 0.00 0.00
February 2528.06 1342.97 1870.85 1326.79 544.06 0.00 0.00
March 2049.72 1168.12 1463.55 829.18 634.37 0.00 0.00
April 1648.81 688.96 1019.80 382.82 636.98 0.00 0.00
May 1346.07 384.20 723.68 106.13 617.55 0.00 0.00
June 1429.59 179.07 618.99 38.95 580.04 0.00 0.00
July 1449.74 133.55 628.60 55.73 572.87 0.00 0.00
August 1679.22 208.36 793.51 201.60 591.90 0.00 0.00
September 2350.75 450.04 1256.61 652.87 603.74 0.00 0.00
October 2729.66 753.87 1724.89 1171.91 552.99 0.00 0.00
November 2877.82 1276.61 2076.02 1587.93 488.09 0.00 0.00
December 2645.50 1618.29 2041.42 1533.69 507.73 0.00 0.00
               
Annual Sum or Average 2110.91 807.23 1347.44 779.68 567.76 0.00 0.00
Minimum of Months 1346.07 133.55 618.99 38.95 481.75 0.00 0.00
Maximum of Months 2877.82 1618.29 2076.02 1587.93 636.98 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3473.40 2080.95 2583.15 1957.32 625.82 0.00 0.00
February 3336.16 1849.02 2430.34 1723.58 706.76 0.00 0.00
March 2691.88 1622.84 1901.24 1077.15 824.09 0.00 0.00
April 2157.31 964.80 1324.78 497.31 827.47 0.00 0.00
May 1743.19 538.11 940.11 137.87 802.24 0.00 0.00
June 1865.14 243.97 804.10 50.59 753.51 0.00 0.00
July 1892.59 182.42 816.59 72.40 744.19 0.00 0.00
August 2207.31 281.11 1030.81 261.90 768.91 0.00 0.00
September 3110.07 600.14 1632.41 848.12 784.29 0.00 0.00
October 3601.92 1024.88 2240.73 1522.37 718.36 0.00 0.00
November 3801.65 1748.72 2696.87 2062.81 634.06 0.00 0.00
December 3487.65 2224.92 2651.92 1992.35 659.58 0.00 0.00
               
Annual Sum or Average 2776.64 1109.90 1750.40 1012.84 737.56 0.00 0.00
Minimum of Months 1743.19 182.42 804.10 50.59 625.82 0.00 0.00
Maximum of Months 3801.65 2224.92 2696.87 2062.81 827.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 289.82 290.48 247.02 166.33 80.69 0.00 0.00
February 310.95 256.70 252.26 157.31 94.95 0.00 0.00
March 355.14 219.11 267.73 146.67 121.05 0.00 0.00
April 411.95 114.84 260.91 128.99 131.92 0.00 0.00
May 461.33 54.71 255.11 116.78 138.32 0.00 0.00
June 519.52 19.19 242.25 109.47 132.78 0.00 0.00
July 480.55 10.61 220.68 91.63 129.05 0.00 0.00
August 466.30 21.57 226.65 101.24 125.41 0.00 0.00
September 490.15 64.32 263.72 143.81 119.91 0.00 0.00
October 429.15 127.10 272.32 170.80 101.51 0.00 0.00
November 351.71 240.63 271.93 188.26 83.67 0.00 0.00
December 276.75 315.86 245.09 162.93 82.16 0.00 0.00
               
Annual Sum or Average 403.94 144.06 252.05 140.19 111.87 0.00 0.00
Minimum of Months 276.75 10.61 220.68 91.63 80.69 0.00 0.00
Maximum of Months 519.52 315.86 272.32 188.26 138.32 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 121.69 305.55 127.80 60.54 67.26 0.00 0.00
February 155.19 268.75 145.81 64.15 81.66 0.00 0.00
March 240.83 222.06 197.57 88.46 109.11 0.00 0.00
April 345.65 112.83 227.17 102.60 124.57 0.00 0.00
May 445.08 52.45 249.02 112.63 136.39 0.00 0.00
June 525.60 18.66 246.35 112.66 133.68 0.00 0.00
July 478.10 10.30 220.48 92.03 128.45 0.00 0.00
August 426.49 20.87 208.10 87.97 120.13 0.00 0.00
September 383.42 63.17 207.82 98.01 109.81 0.00 0.00
October 270.96 127.77 178.00 88.52 89.48 0.00 0.00
November 166.21 252.28 147.80 76.76 71.03 0.00 0.00
December 107.54 336.53 121.99 55.25 66.75 0.00 0.00
               
Annual Sum or Average 306.25 148.70 190.00 86.70 103.30 0.00 0.00
Minimum of Months 107.54 10.30 121.99 55.25 66.75 0.00 0.00
Maximum of Months 525.60 336.53 249.02 112.66 136.39 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 146.83 89.20 111.67 84.62 27.06 0.00 0.00
February 141.11 79.40 105.07 74.51 30.55 0.00 0.00
March 113.38 68.18 82.19 46.57 35.63 0.00 0.00
April 92.64 38.61 57.27 21.50 35.77 0.00 0.00
May 77.73 19.86 40.64 5.96 34.68 0.00 0.00
June 86.17 8.05 34.76 2.19 32.58 0.00 0.00
July 86.57 5.59 35.30 3.13 32.17 0.00 0.00
August 98.89 9.55 44.56 11.32 33.24 0.00 0.00
September 135.67 23.22 70.57 36.67 33.91 0.00 0.00
October 154.76 42.29 96.87 65.81 31.06 0.00 0.00
November 162.46 74.20 116.59 89.18 27.41 0.00 0.00
December 148.19 95.29 114.65 86.13 28.51 0.00 0.00
               
Annual Sum or Average 120.21 45.96 75.67 43.79 31.89 0.00 0.00
Minimum of Months 77.73 5.59 34.76 2.19 27.06 0.00 0.00
Maximum of Months 162.46 95.29 116.59 89.18 35.77 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3.62 90.39 16.32 0.00 16.32 0.00 0.00
February 10.40 78.15 19.93 0.00 19.93 0.00 0.00
March 21.37 63.04 26.09 0.00 26.09 0.00 0.00
April 43.83 29.66 30.29 0.39 29.91 0.00 0.00
May 72.80 12.63 35.78 2.64 33.15 0.00 0.00
June 101.15 4.15 38.05 4.74 33.31 0.00 0.00
July 94.69 2.07 35.16 3.45 31.71 0.00 0.00
August 75.55 4.62 29.73 0.71 29.03 0.00 0.00
September 55.18 15.53 25.87 0.03 25.84 0.00 0.00
October 29.73 34.10 21.44 0.00 21.44 0.00 0.00
November 8.11 72.40 17.31 0.00 17.31 0.00 0.00
December 2.46 100.42 16.19 0.00 16.19 0.00 0.00
               
Annual Sum or Average 43.41 42.10 26.04 1.00 25.04 0.00 0.00
Minimum of Months 2.46 2.07 16.19 0.00 16.19 0.00 0.00
Maximum of Months 101.15 100.42 38.05 4.74 33.31 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 276.12 285.12 241.32 160.90 80.42 0.00 0.00
February 328.20 249.37 267.86 170.99 96.87 0.00 0.00
March 348.61 206.66 271.01 150.86 120.15 0.00 0.00
April 423.15 104.44 274.43 139.37 135.06 0.00 0.00
May 465.00 49.61 259.90 121.04 138.86 0.00 0.00
June 536.01 17.86 252.63 119.04 133.59 0.00 0.00
July 498.85 10.14 231.84 102.05 129.80 0.00 0.00
August 479.28 20.25 234.52 105.72 128.80 0.00 0.00
September 487.40 59.19 265.63 147.14 118.49 0.00 0.00
October 397.34 122.16 256.89 155.42 101.47 0.00 0.00
November 335.98 233.56 267.34 182.11 85.23 0.00 0.00
December 271.20 309.46 245.12 161.62 83.50 0.00 0.00
               
Annual Sum or Average 404.09 138.46 255.51 142.75 112.76 0.00 0.00
Minimum of Months 271.20 10.14 231.84 102.05 80.42 0.00 0.00
Maximum of Months 536.01 309.46 274.43 182.11 138.86 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 95.91 287.77 122.10 55.11 66.99 0.00 0.00
February 160.41 249.22 161.41 77.83 83.58 0.00 0.00
March 229.00 204.80 200.85 92.64 108.21 0.00 0.00
April 356.60 103.02 240.68 112.98 127.71 0.00 0.00
May 450.57 49.33 253.81 116.88 136.93 0.00 0.00
June 542.85 17.91 256.73 122.24 134.50 0.00 0.00
July 496.70 10.04 231.64 102.44 129.20 0.00 0.00
August 439.71 19.95 215.97 92.45 123.52 0.00 0.00
September 379.86 57.78 209.73 101.34 108.39 0.00 0.00
October 234.93 119.47 162.58 73.14 89.44 0.00 0.00
November 140.23 233.73 143.21 70.62 72.60 0.00 0.00
December 87.57 315.68 122.02 53.93 68.09 0.00 0.00
               
Annual Sum or Average 301.77 138.55 193.45 89.26 104.19 0.00 0.00
Minimum of Months 87.57 10.04 122.02 53.93 66.99 0.00 0.00
Maximum of Months 542.85 315.68 256.73 122.24 136.93 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 309.39 376.33 277.32 183.34 93.98 0.00 0.00
February 315.08 337.35 270.83 161.45 109.38 0.00 0.00
March 285.32 295.30 234.60 100.90 133.70 0.00 0.00
April 282.91 169.64 189.72 47.42 142.30 0.00 0.00
May 300.63 89.19 165.58 18.63 146.95 0.00 0.00
June 373.76 38.24 157.76 15.01 142.75 0.00 0.00
July 360.37 27.47 152.65 14.25 138.40 0.00 0.00
August 349.15 45.40 160.97 26.06 134.90 0.00 0.00
September 393.16 107.22 208.95 79.51 129.43 0.00 0.00
October 384.08 188.56 256.34 142.60 113.74 0.00 0.00
November 350.47 324.45 290.12 193.22 96.89 0.00 0.00
December 305.43 402.49 283.49 186.62 96.87 0.00 0.00
               
Annual Sum or Average 334.13 199.45 220.38 97.04 123.34 0.00 0.00
Minimum of Months 282.91 27.47 152.65 14.25 93.98 0.00 0.00
Maximum of Months 393.16 402.49 290.12 193.22 146.95 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 289.53 286.01 247.02 166.33 80.69 0.00 0.00
February 310.33 251.99 252.26 157.31 94.95 0.00 0.00
March 353.44 214.75 267.73 146.67 121.05 0.00 0.00
April 409.64 111.25 260.91 128.99 131.92 0.00 0.00
May 459.49 51.95 255.11 116.78 138.32 0.00 0.00
June 518.19 17.91 242.25 109.47 132.78 0.00 0.00
July 478.83 9.71 220.68 91.63 129.05 0.00 0.00
August 464.41 20.14 226.65 101.24 125.41 0.00 0.00
September 487.32 61.82 263.72 143.81 119.91 0.00 0.00
October 427.46 123.40 272.32 170.80 101.51 0.00 0.00
November 351.35 235.45 271.93 188.26 83.67 0.00 0.00
December 277.43 311.09 245.09 162.93 82.16 0.00 0.00
               
Annual Sum or Average 402.61 140.76 252.05 140.19 111.87 0.00 0.00
Minimum of Months 277.43 9.71 220.68 91.63 80.69 0.00 0.00
Maximum of Months 518.19 311.09 272.32 188.26 138.32 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 122.96 299.88 127.80 60.54 67.26 0.00 0.00
February 156.33 262.80 145.81 64.15 81.66 0.00 0.00
March 241.11 216.86 197.57 88.46 109.11 0.00 0.00
April 344.45 109.07 227.17 102.60 124.57 0.00 0.00
May 443.51 49.78 249.02 112.63 136.39 0.00 0.00
June 524.02 17.46 246.35 112.66 133.68 0.00 0.00
July 476.33 9.44 220.48 92.03 128.45 0.00 0.00
August 425.11 19.47 208.10 87.97 120.13 0.00 0.00
September 381.71 60.52 207.82 98.01 109.81 0.00 0.00
October 271.18 123.07 178.00 88.52 89.48 0.00 0.00
November 167.90 245.15 147.80 76.76 71.03 0.00 0.00
December 109.16 330.61 121.99 55.25 66.75 0.00 0.00
               
Annual Sum or Average 306.00 144.79 190.00 86.70 103.30 0.00 0.00
Minimum of Months 109.16 9.44 121.99 55.25 66.75 0.00 0.00
Maximum of Months 524.02 330.61 249.02 112.66 136.39 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 269.03 150.76 204.76 155.16 49.61 0.00 0.00
February 259.50 131.42 192.65 136.63 56.02 0.00 0.00
March 209.51 111.58 150.71 85.38 65.33 0.00 0.00
April 174.21 56.95 105.01 39.42 65.59 0.00 0.00
May 151.45 25.36 74.52 10.93 63.59 0.00 0.00
June 170.72 8.16 63.74 4.01 59.73 0.00 0.00
July 171.15 4.34 64.73 5.74 58.99 0.00 0.00
August 191.19 9.57 81.71 20.76 60.95 0.00 0.00
September 252.83 30.49 129.40 67.23 62.17 0.00 0.00
October 286.47 63.13 177.62 120.68 56.94 0.00 0.00
November 298.62 122.20 213.78 163.52 50.26 0.00 0.00
December 271.85 163.14 210.22 157.93 52.28 0.00 0.00
               
Annual Sum or Average 225.28 72.82 138.75 80.29 58.47 0.00 0.00
Minimum of Months 151.45 4.34 63.74 4.01 49.61 0.00 0.00
Maximum of Months 298.62 163.14 213.78 163.52 65.59 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 15.55 919.78 142.78 0.00 142.78 0.00 0.00
February 63.66 805.89 174.35 0.00 174.35 0.00 0.00
March 144.98 666.27 228.22 0.01 228.21 0.00 0.00
April 320.23 358.11 265.01 3.38 261.64 0.00 0.00
May 548.04 184.19 313.05 23.07 289.98 0.00 0.00
June 774.30 84.43 332.91 41.48 291.42 0.00 0.00
July 714.65 63.43 307.56 30.17 277.39 0.00 0.00
August 560.71 99.09 260.12 6.19 253.93 0.00 0.00
September 415.58 220.82 226.30 0.29 226.02 0.00 0.00
October 207.93 406.55 187.59 0.00 187.59 0.00 0.00
November 43.82 759.69 151.44 0.00 151.44 0.00 0.00
December 10.85 1001.11 141.68 0.00 141.68 0.00 0.00
               
Annual Sum or Average 319.68 462.49 227.84 8.76 219.09 0.00 0.00
Minimum of Months 10.85 63.43 141.68 0.00 141.68 0.00 0.00
Maximum of Months 774.30 1001.11 332.91 41.48 291.42 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 11.54 961.27 142.78 0.00 142.78 0.00 0.00
February 55.99 839.97 174.35 0.00 174.35 0.00 0.00
March 132.95 692.95 228.22 0.01 228.21 0.00 0.00
April 305.80 371.72 265.01 3.38 261.64 0.00 0.00
May 531.44 191.63 313.05 23.07 289.98 0.00 0.00
June 756.62 88.94 332.91 41.48 291.42 0.00 0.00
July 697.28 67.96 307.56 30.17 277.39 0.00 0.00
August 544.14 104.67 260.12 6.19 253.93 0.00 0.00
September 402.26 230.13 226.30 0.29 226.02 0.00 0.00
October 197.07 422.59 187.59 0.00 187.59 0.00 0.00
November 37.50 790.32 151.44 0.00 151.44 0.00 0.00
December 8.15 1045.20 141.68 0.00 141.68 0.00 0.00
               
Annual Sum or Average 308.04 482.27 227.84 8.76 219.09 0.00 0.00
Minimum of Months 8.15 67.96 141.68 0.00 141.68 0.00 0.00
Maximum of Months 756.62 1045.20 332.91 41.48 291.42 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 353.43 676.82 363.41 216.00 147.41 0.00 0.00
February 486.22 594.08 429.25 248.81 180.43 0.00 0.00
March 584.65 501.34 471.84 243.48 228.35 0.00 0.00
April 817.08 284.07 515.08 252.33 262.75 0.00 0.00
May 958.04 166.59 513.67 237.90 275.77 0.00 0.00
June 1125.40 85.94 509.34 241.26 268.07 0.00 0.00
July 1042.54 69.55 463.46 204.47 258.98 0.00 0.00
August 970.63 96.41 450.46 198.15 252.31 0.00 0.00
September 933.76 176.41 475.33 248.47 226.86 0.00 0.00
October 665.98 315.97 419.45 228.55 190.90 0.00 0.00
November 478.40 555.13 410.54 252.72 157.82 0.00 0.00
December 339.46 719.77 367.13 215.55 151.58 0.00 0.00
               
Annual Sum or Average 730.44 352.39 448.93 231.99 216.94 0.00 0.00
Minimum of Months 339.46 69.55 363.41 198.15 147.41 0.00 0.00
Maximum of Months 1125.40 719.77 515.08 252.72 275.77 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 665.63 664.40 570.18 394.96 175.23 0.00 0.00
February 660.72 598.81 550.17 347.79 202.38 0.00 0.00
March 567.72 529.75 461.88 217.35 244.52 0.00 0.00
April 521.84 314.76 358.17 101.51 256.66 0.00 0.00
May 522.61 166.79 297.02 35.73 261.29 0.00 0.00
June 636.67 73.36 276.38 24.43 251.95 0.00 0.00
July 617.31 55.09 270.21 24.95 245.26 0.00 0.00
August 623.96 88.25 297.17 54.97 242.20 0.00 0.00
September 750.74 197.55 406.97 171.23 235.74 0.00 0.00
October 770.41 343.11 516.45 307.19 209.26 0.00 0.00
November 744.55 570.88 596.10 416.24 179.86 0.00 0.00
December 664.23 708.12 583.68 402.02 181.66 0.00 0.00
               
Annual Sum or Average 645.21 358.04 431.31 207.38 223.93 0.00 0.00
Minimum of Months 521.84 55.09 270.21 24.43 175.23 0.00 0.00
Maximum of Months 770.41 708.12 596.10 416.24 261.29 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.250939E+10 0.141116E+10 0.189136E+10 0.143314E+10 0.458222E+09 0.00 0.00
February 0.217508E+10 0.113939E+10 0.160727E+10 0.113986E+10 0.467406E+09 0.00 0.00
March 0.193554E+10 0.111093E+10 0.139207E+10 0.788679E+09 0.603391E+09 0.00 0.00
April 0.147978E+10 0.657155E+09 0.938702E+09 0.352379E+09 0.586322E+09 0.00 0.00
May 0.121775E+10 0.390267E+09 0.688337E+09 0.100947E+09 0.587390E+09 0.00 0.00
June 0.125617E+10 0.177994E+09 0.569764E+09 35850177.24 0.533914E+09 0.00 0.00
July 0.132064E+10 0.139959E+09 0.597898E+09 53010019.83 0.544888E+09 0.00 0.00
August 0.155219E+10 0.211114E+09 0.754750E+09 0.191758E+09 0.562992E+09 0.00 0.00
September 0.214540E+10 0.431669E+09 0.115668E+10 0.600953E+09 0.555729E+09 0.00 0.00
October 0.258648E+10 0.731275E+09 0.164065E+10 0.111467E+10 0.525978E+09 0.00 0.00
November 0.265980E+10 0.116730E+10 0.191093E+10 0.146165E+10 0.449279E+09 0.00 0.00
December 0.252443E+10 0.150861E+10 0.194172E+10 0.145878E+10 0.482936E+09 0.00 0.00
               
Annual Sum or Average 0.233626E+11 0.907682E+10 0.150901E+11 0.873168E+10 0.635845E+10 0.00 0.00
Minimum of Months 0.121775E+10 0.139959E+09 0.569764E+09 35850177.24 0.449279E+09 0.00 0.00
Maximum of Months 0.265980E+10 0.150861E+10 0.194172E+10 0.146165E+10 0.603391E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.704941E+10 0.405525E+10 0.532594E+10 0.403562E+10 0.129032E+10 0.00 0.00
February 0.611588E+10 0.324890E+10 0.452597E+10 0.320978E+10 0.131618E+10 0.00 0.00
March 0.548997E+10 0.312870E+10 0.391998E+10 0.222087E+10 0.169911E+10 0.00 0.00
April 0.427372E+10 0.178579E+10 0.264332E+10 0.992277E+09 0.165105E+10 0.00 0.00
May 0.360530E+10 0.102903E+10 0.193831E+10 0.284261E+09 0.165405E+10 0.00 0.00
June 0.370550E+10 0.464145E+09 0.160442E+10 0.100952E+09 0.150347E+10 0.00 0.00
July 0.388299E+10 0.357712E+09 0.168364E+10 0.149273E+09 0.153437E+10 0.00 0.00
August 0.449762E+10 0.558074E+09 0.212533E+10 0.539978E+09 0.158535E+10 0.00 0.00
September 0.609315E+10 0.116649E+10 0.325714E+10 0.169224E+10 0.156490E+10 0.00 0.00
October 0.731112E+10 0.201917E+10 0.461996E+10 0.313884E+10 0.148112E+10 0.00 0.00
November 0.745931E+10 0.330898E+10 0.538106E+10 0.411592E+10 0.126514E+10 0.00 0.00
December 0.708571E+10 0.433442E+10 0.546774E+10 0.410783E+10 0.135992E+10 0.00 0.00
               
Annual Sum or Average 0.665697E+11 0.254567E+11 0.424928E+11 0.245878E+11 0.179050E+11 0.00 0.00
Minimum of Months 0.360530E+10 0.357712E+09 0.160442E+10 0.100952E+09 0.126514E+10 0.00 0.00
Maximum of Months 0.745931E+10 0.433442E+10 0.546774E+10 0.411592E+10 0.169911E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.930317E+10 0.557361E+10 0.691870E+10 0.524250E+10 0.167620E+10 0.00 0.00
February 0.807084E+10 0.447315E+10 0.587949E+10 0.416969E+10 0.170980E+10 0.00 0.00
March 0.720993E+10 0.434662E+10 0.509227E+10 0.288503E+10 0.220724E+10 0.00 0.00
April 0.559174E+10 0.250076E+10 0.343383E+10 0.128902E+10 0.214480E+10 0.00 0.00
May 0.466897E+10 0.144128E+10 0.251798E+10 0.369271E+09 0.214871E+10 0.00 0.00
June 0.483444E+10 0.632373E+09 0.208423E+10 0.131142E+09 0.195309E+10 0.00 0.00
July 0.506911E+10 0.488592E+09 0.218715E+10 0.193914E+09 0.199323E+10 0.00 0.00
August 0.591205E+10 0.752937E+09 0.276092E+10 0.701462E+09 0.205946E+10 0.00 0.00
September 0.806130E+10 0.155556E+10 0.423121E+10 0.219832E+10 0.203289E+10 0.00 0.00
October 0.964740E+10 0.274504E+10 0.600158E+10 0.407753E+10 0.192406E+10 0.00 0.00
November 0.985387E+10 0.453269E+10 0.699030E+10 0.534681E+10 0.164349E+10 0.00 0.00
December 0.934133E+10 0.595922E+10 0.710291E+10 0.533630E+10 0.176661E+10 0.00 0.00
               
Annual Sum or Average 0.875641E+11 0.350018E+11 0.552006E+11 0.319410E+11 0.232596E+11 0.00 0.00
Minimum of Months 0.466897E+10 0.488592E+09 0.208423E+10 0.131142E+09 0.164349E+10 0.00 0.00
Maximum of Months 0.985387E+10 0.595922E+10 0.710291E+10 0.534681E+10 0.220724E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.776259E+09 0.778030E+09 0.661628E+09 0.445502E+09 0.216126E+09 0.00 0.00
February 0.752251E+09 0.621010E+09 0.610259E+09 0.380562E+09 0.229697E+09 0.00 0.00
March 0.951207E+09 0.586863E+09 0.717083E+09 0.392853E+09 0.324229E+09 0.00 0.00
April 0.106778E+10 0.297671E+09 0.676285E+09 0.334351E+09 0.341935E+09 0.00 0.00
May 0.123562E+10 0.146544E+09 0.683278E+09 0.312791E+09 0.370487E+09 0.00 0.00
June 0.134660E+10 49748918.05 0.627908E+09 0.283748E+09 0.344161E+09 0.00 0.00
July 0.128711E+10 28430516.15 0.591061E+09 0.245426E+09 0.345635E+09 0.00 0.00
August 0.124893E+10 57782774.39 0.607067E+09 0.271168E+09 0.335899E+09 0.00 0.00
September 0.127048E+10 0.166714E+09 0.683569E+09 0.372750E+09 0.310819E+09 0.00 0.00
October 0.114943E+10 0.340432E+09 0.729374E+09 0.457483E+09 0.271891E+09 0.00 0.00
November 0.911627E+09 0.623704E+09 0.704840E+09 0.487965E+09 0.216875E+09 0.00 0.00
December 0.741250E+09 0.845993E+09 0.656450E+09 0.436397E+09 0.220053E+09 0.00 0.00
               
Annual Sum or Average 0.127385E+11 0.454292E+10 0.794880E+10 0.442100E+10 0.352781E+10 0.00 0.00
Minimum of Months 0.741250E+09 28430516.15 0.591061E+09 0.245426E+09 0.216126E+09 0.00 0.00
Maximum of Months 0.134660E+10 0.845993E+09 0.729374E+09 0.487965E+09 0.370487E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.325933E+09 0.818377E+09 0.342309E+09 0.162146E+09 0.180162E+09 0.00 0.00
February 0.375434E+09 0.650148E+09 0.352733E+09 0.155192E+09 0.197541E+09 0.00 0.00
March 0.645038E+09 0.594778E+09 0.529172E+09 0.236921E+09 0.292251E+09 0.00 0.00
April 0.895915E+09 0.292461E+09 0.588821E+09 0.265930E+09 0.322892E+09 0.00 0.00
May 0.119209E+10 0.140485E+09 0.666968E+09 0.301660E+09 0.365308E+09 0.00 0.00
June 0.136237E+10 48355265.45 0.638530E+09 0.292021E+09 0.346509E+09 0.00 0.00
July 0.128054E+10 27579189.67 0.590530E+09 0.246488E+09 0.344041E+09 0.00 0.00
August 0.114231E+10 55904784.10 0.557372E+09 0.235622E+09 0.321750E+09 0.00 0.00
September 0.993830E+09 0.163728E+09 0.538673E+09 0.254037E+09 0.284635E+09 0.00 0.00
October 0.725734E+09 0.342219E+09 0.476768E+09 0.237094E+09 0.239674E+09 0.00 0.00
November 0.430813E+09 0.653899E+09 0.383093E+09 0.198972E+09 0.184121E+09 0.00 0.00
December 0.288045E+09 0.901373E+09 0.326751E+09 0.147971E+09 0.178780E+09 0.00 0.00
               
Annual Sum or Average 0.965806E+10 0.468931E+10 0.599172E+10 0.273405E+10 0.325767E+10 0.00 0.00
Minimum of Months 0.288045E+09 27579189.67 0.326751E+09 0.147971E+09 0.178780E+09 0.00 0.00
Maximum of Months 0.136237E+10 0.901373E+09 0.666968E+09 0.301660E+09 0.365308E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.393281E+09 0.238915E+09 0.299104E+09 0.226640E+09 72464826.42 0.00 0.00
February 0.341381E+09 0.192079E+09 0.254178E+09 0.180261E+09 73917324.87 0.00 0.00
March 0.303670E+09 0.182619E+09 0.220146E+09 0.124724E+09 95422629.83 0.00 0.00
April 0.240119E+09 0.100087E+09 0.148450E+09 55726088.50 92723544.22 0.00 0.00
May 0.208191E+09 53205808.91 0.108857E+09 15964013.69 92892545.85 0.00 0.00
June 0.223350E+09 20874701.66 90105188.78 5669429.11 84435759.67 0.00 0.00
July 0.231874E+09 14970905.08 94554156.30 8383125.91 86171030.39 0.00 0.00
August 0.264859E+09 25565559.15 0.119359E+09 30325060.49 89033931.16 0.00 0.00
September 0.351662E+09 60178026.66 0.182921E+09 95036114.58 87885276.20 0.00 0.00
October 0.414509E+09 0.113262E+09 0.259457E+09 0.176276E+09 83180150.54 0.00 0.00
November 0.421086E+09 0.192333E+09 0.302200E+09 0.231149E+09 71050625.13 0.00 0.00
December 0.396914E+09 0.255217E+09 0.307068E+09 0.230695E+09 76373138.43 0.00 0.00
               
Annual Sum or Average 0.379090E+10 0.144931E+10 0.238640E+10 0.138085E+10 0.100555E+10 0.00 0.00
Minimum of Months 0.208191E+09 14970905.08 90105188.78 5669429.11 71050625.13 0.00 0.00
Maximum of Months 0.421086E+09 0.255217E+09 0.307068E+09 0.231149E+09 95422629.83 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 9704887.14 0.242102E+09 43713969.60 0.00 43713969.60 0.00 0.00
February 25149655.52 0.189063E+09 48213648.10 0.00 48213648.10 0.00 0.00
March 57242008.37 0.168837E+09 69870982.94 2765.95 69868216.99 0.00 0.00
April 0.113607E+09 76890738.99 78518344.10 1000279.47 77518064.63 0.00 0.00
May 0.194994E+09 33815363.02 95843144.60 7063304.15 88779840.45 0.00 0.00
June 0.262173E+09 10763610.52 98633813.54 12290815.53 86342998.01 0.00 0.00
July 0.253615E+09 5540435.89 94160895.41 9236150.10 84924745.31 0.00 0.00
August 0.202349E+09 12371518.69 79637162.39 1894638.37 77742524.03 0.00 0.00
September 0.143021E+09 40258526.93 67049393.63 84739.01 66964654.62 0.00 0.00
October 79631418.21 91335854.75 57430655.00 0.00 57430655.00 0.00 0.00
November 21019159.04 0.187666E+09 44867884.08 0.00 44867884.08 0.00 0.00
December 6596807.47 0.268970E+09 43375413.74 0.00 43375413.74 0.00 0.00
               
Annual Sum or Average 0.136910E+10 0.132761E+10 0.821315E+09 31572692.58 0.789743E+09 0.00 0.00
Minimum of Months 6596807.47 5540435.89 43375413.74 0.00 43375413.74 0.00 0.00
Maximum of Months 0.262173E+09 0.268970E+09 98633813.54 12290815.53 88779840.45 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.739557E+09 0.763670E+09 0.646361E+09 0.430960E+09 0.215402E+09 0.00 0.00
February 0.793970E+09 0.603279E+09 0.648005E+09 0.413664E+09 0.234341E+09 0.00 0.00
March 0.933706E+09 0.553521E+09 0.725871E+09 0.404058E+09 0.321813E+09 0.00 0.00
April 0.109681E+10 0.270697E+09 0.711319E+09 0.361253E+09 0.350066E+09 0.00 0.00
May 0.124545E+10 0.132877E+09 0.696105E+09 0.324180E+09 0.371925E+09 0.00 0.00
June 0.138933E+10 46286543.03 0.654827E+09 0.308561E+09 0.346266E+09 0.00 0.00
July 0.133613E+10 27172157.28 0.620963E+09 0.273320E+09 0.347643E+09 0.00 0.00
August 0.128370E+10 54224434.96 0.628139E+09 0.283153E+09 0.344986E+09 0.00 0.00
September 0.126334E+10 0.153429E+09 0.688511E+09 0.381390E+09 0.307121E+09 0.00 0.00
October 0.106423E+10 0.327204E+09 0.688060E+09 0.416283E+09 0.271777E+09 0.00 0.00
November 0.870850E+09 0.605392E+09 0.692953E+09 0.472029E+09 0.220924E+09 0.00 0.00
December 0.726383E+09 0.828858E+09 0.656523E+09 0.432885E+09 0.223638E+09 0.00 0.00
               
Annual Sum or Average 0.127435E+11 0.436661E+10 0.805764E+10 0.450174E+10 0.355590E+10 0.00 0.00
Minimum of Months 0.726383E+09 27172157.28 0.620963E+09 0.273320E+09 0.215402E+09 0.00 0.00
Maximum of Months 0.138933E+10 0.828858E+09 0.725871E+09 0.472029E+09 0.371925E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.256895E+09 0.770761E+09 0.327041E+09 0.147604E+09 0.179438E+09 0.00 0.00
February 0.388060E+09 0.602905E+09 0.390478E+09 0.188293E+09 0.202185E+09 0.00 0.00
March 0.613362E+09 0.548531E+09 0.537961E+09 0.248126E+09 0.289835E+09 0.00 0.00
April 0.924319E+09 0.267017E+09 0.623855E+09 0.292832E+09 0.331023E+09 0.00 0.00
May 0.120680E+10 0.132132E+09 0.679796E+09 0.313049E+09 0.366746E+09 0.00 0.00
June 0.140707E+10 46428480.83 0.665449E+09 0.316834E+09 0.348614E+09 0.00 0.00
July 0.133036E+10 26879439.03 0.620433E+09 0.274383E+09 0.346050E+09 0.00 0.00
August 0.117773E+10 53434268.12 0.578444E+09 0.247607E+09 0.330837E+09 0.00 0.00
September 0.984605E+09 0.149770E+09 0.543615E+09 0.262677E+09 0.280938E+09 0.00 0.00
October 0.629225E+09 0.319999E+09 0.435454E+09 0.195894E+09 0.239560E+09 0.00 0.00
November 0.363488E+09 0.605834E+09 0.371206E+09 0.183035E+09 0.188171E+09 0.00 0.00
December 0.234549E+09 0.845511E+09 0.326824E+09 0.144459E+09 0.182365E+09 0.00 0.00
               
Annual Sum or Average 0.951646E+10 0.436920E+10 0.610055E+10 0.281479E+10 0.328576E+10 0.00 0.00
Minimum of Months 0.234549E+09 26879439.03 0.326824E+09 0.144459E+09 0.179438E+09 0.00 0.00
Maximum of Months 0.140707E+10 0.845511E+09 0.679796E+09 0.316834E+09 0.366746E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.828680E+09 0.100795E+10 0.742775E+09 0.491065E+09 0.251710E+09 0.00 0.00
February 0.762252E+09 0.816123E+09 0.655180E+09 0.390575E+09 0.264605E+09 0.00 0.00
March 0.764202E+09 0.790925E+09 0.628360E+09 0.270247E+09 0.358112E+09 0.00 0.00
April 0.733292E+09 0.439718E+09 0.491746E+09 0.122910E+09 0.368836E+09 0.00 0.00
May 0.805209E+09 0.238886E+09 0.443490E+09 49891063.49 0.393599E+09 0.00 0.00
June 0.968785E+09 99113426.61 0.408907E+09 38910104.08 0.369997E+09 0.00 0.00
July 0.965228E+09 73562860.60 0.408857E+09 38172500.78 0.370684E+09 0.00 0.00
August 0.935157E+09 0.121612E+09 0.431139E+09 69810394.97 0.361328E+09 0.00 0.00
September 0.101908E+10 0.277904E+09 0.541591E+09 0.206100E+09 0.335491E+09 0.00 0.00
October 0.102873E+10 0.505037E+09 0.686584E+09 0.381942E+09 0.304642E+09 0.00 0.00
November 0.908410E+09 0.840971E+09 0.751982E+09 0.500836E+09 0.251146E+09 0.00 0.00
December 0.818070E+09 0.107802E+10 0.759297E+09 0.499852E+09 0.259445E+09 0.00 0.00
               
Annual Sum or Average 0.105371E+11 0.628983E+10 0.694991E+10 0.306031E+10 0.388960E+10 0.00 0.00
Minimum of Months 0.733292E+09 73562860.60 0.408857E+09 38172500.78 0.251146E+09 0.00 0.00
Maximum of Months 0.102873E+10 0.107802E+10 0.759297E+09 0.500836E+09 0.393599E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.775470E+09 0.766057E+09 0.661628E+09 0.445502E+09 0.216126E+09 0.00 0.00
February 0.750741E+09 0.609619E+09 0.610259E+09 0.380562E+09 0.229697E+09 0.00 0.00
March 0.946653E+09 0.575199E+09 0.717083E+09 0.392853E+09 0.324229E+09 0.00 0.00
April 0.106179E+10 0.288353E+09 0.676285E+09 0.334351E+09 0.341935E+09 0.00 0.00
May 0.123070E+10 0.139131E+09 0.683278E+09 0.312791E+09 0.370487E+09 0.00 0.00
June 0.134314E+10 46430323.45 0.627908E+09 0.283748E+09 0.344161E+09 0.00 0.00
July 0.128249E+10 26002006.78 0.591061E+09 0.245426E+09 0.345635E+09 0.00 0.00
August 0.124388E+10 53947434.65 0.607067E+09 0.271168E+09 0.335899E+09 0.00 0.00
September 0.126312E+10 0.160226E+09 0.683569E+09 0.372750E+09 0.310819E+09 0.00 0.00
October 0.114491E+10 0.330513E+09 0.729374E+09 0.457483E+09 0.271891E+09 0.00 0.00
November 0.910701E+09 0.610284E+09 0.704840E+09 0.487965E+09 0.216875E+09 0.00 0.00
December 0.743081E+09 0.833225E+09 0.656450E+09 0.436397E+09 0.220053E+09 0.00 0.00
               
Annual Sum or Average 0.126967E+11 0.443899E+10 0.794880E+10 0.442100E+10 0.352781E+10 0.00 0.00
Minimum of Months 0.743081E+09 26002006.78 0.591061E+09 0.245426E+09 0.216126E+09 0.00 0.00
Maximum of Months 0.134314E+10 0.833225E+09 0.729374E+09 0.487965E+09 0.370487E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.329339E+09 0.803200E+09 0.342309E+09 0.162146E+09 0.180162E+09 0.00 0.00
February 0.378198E+09 0.635768E+09 0.352733E+09 0.155192E+09 0.197541E+09 0.00 0.00
March 0.645790E+09 0.580849E+09 0.529172E+09 0.236921E+09 0.292251E+09 0.00 0.00
April 0.892811E+09 0.282722E+09 0.588821E+09 0.265930E+09 0.322892E+09 0.00 0.00
May 0.118790E+10 0.133330E+09 0.666968E+09 0.301660E+09 0.365308E+09 0.00 0.00
June 0.135827E+10 45250194.73 0.638530E+09 0.292021E+09 0.346509E+09 0.00 0.00
July 0.127580E+10 25272364.24 0.590530E+09 0.246488E+09 0.344041E+09 0.00 0.00
August 0.113860E+10 52141229.08 0.557372E+09 0.235622E+09 0.321750E+09 0.00 0.00
September 0.989393E+09 0.156857E+09 0.538673E+09 0.254037E+09 0.284635E+09 0.00 0.00
October 0.726336E+09 0.329625E+09 0.476768E+09 0.237094E+09 0.239674E+09 0.00 0.00
November 0.435186E+09 0.635427E+09 0.383093E+09 0.198972E+09 0.184121E+09 0.00 0.00
December 0.292380E+09 0.885512E+09 0.326751E+09 0.147971E+09 0.178780E+09 0.00 0.00
               
Annual Sum or Average 0.965000E+10 0.456595E+10 0.599172E+10 0.273405E+10 0.325767E+10 0.00 0.00
Minimum of Months 0.292380E+09 25272364.24 0.326751E+09 0.147971E+09 0.178780E+09 0.00 0.00
Maximum of Months 0.135827E+10 0.885512E+09 0.666968E+09 0.301660E+09 0.365308E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.720569E+09 0.403784E+09 0.548441E+09 0.415568E+09 0.132872E+09 0.00 0.00
February 0.627784E+09 0.317924E+09 0.466063E+09 0.330528E+09 0.135536E+09 0.00 0.00
March 0.561162E+09 0.298844E+09 0.403662E+09 0.228694E+09 0.174968E+09 0.00 0.00
April 0.451546E+09 0.147621E+09 0.272199E+09 0.102180E+09 0.170019E+09 0.00 0.00
May 0.405650E+09 67913909.06 0.199600E+09 29271767.90 0.170329E+09 0.00 0.00
June 0.442496E+09 21139273.72 0.165218E+09 10395519.34 0.154822E+09 0.00 0.00
July 0.458421E+09 11630592.27 0.173375E+09 15371379.69 0.158004E+09 0.00 0.00
August 0.512087E+09 25637620.15 0.218858E+09 55604320.39 0.163253E+09 0.00 0.00
September 0.655344E+09 79030791.30 0.335406E+09 0.174259E+09 0.161147E+09 0.00 0.00
October 0.767294E+09 0.169082E+09 0.475742E+09 0.323222E+09 0.152520E+09 0.00 0.00
November 0.774017E+09 0.316754E+09 0.554116E+09 0.423837E+09 0.130279E+09 0.00 0.00
December 0.728111E+09 0.436943E+09 0.563043E+09 0.423004E+09 0.140039E+09 0.00 0.00
               
Annual Sum or Average 0.710448E+10 0.229630E+10 0.437572E+10 0.253194E+10 0.184379E+10 0.00 0.00
Minimum of Months 0.405650E+09 11630592.27 0.165218E+09 10395519.34 0.130279E+09 0.00 0.00
Maximum of Months 0.774017E+09 0.436943E+09 0.563043E+09 0.423837E+09 0.174968E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 41661808.54 0.246355E+10 0.382432E+09 0.00 0.382432E+09 0.00 0.00
February 0.154004E+09 0.194960E+10 0.421798E+09 0.00 0.421798E+09 0.00 0.00
March 0.388310E+09 0.178455E+10 0.611267E+09 24197.95 0.611243E+09 0.00 0.00
April 0.830028E+09 0.928219E+09 0.686918E+09 8750953.90 0.678167E+09 0.00 0.00
May 0.146786E+10 0.493323E+09 0.838485E+09 61793379.53 0.776691E+09 0.00 0.00
June 0.200698E+10 0.218844E+09 0.862899E+09 0.107526E+09 0.755372E+09 0.00 0.00
July 0.191411E+10 0.169889E+09 0.823767E+09 80802541.81 0.742965E+09 0.00 0.00
August 0.150180E+10 0.265407E+09 0.696706E+09 16575260.69 0.680131E+09 0.00 0.00
September 0.107719E+10 0.572372E+09 0.586582E+09 741339.97 0.585841E+09 0.00 0.00
October 0.556930E+09 0.108891E+10 0.502433E+09 0.00 0.502433E+09 0.00 0.00
November 0.113576E+09 0.196912E+10 0.392527E+09 0.00 0.392527E+09 0.00 0.00
December 29062726.31 0.268136E+10 0.379470E+09 0.00 0.379470E+09 0.00 0.00
               
Annual Sum or Average 0.100815E+11 0.145851E+11 0.718528E+10 0.276214E+09 0.690907E+10 0.00 0.00
Minimum of Months 29062726.31 0.169889E+09 0.379470E+09 0.00 0.379470E+09 0.00 0.00
Maximum of Months 0.200698E+10 0.268136E+10 0.862899E+09 0.107526E+09 0.776691E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 30903013.88 0.257468E+10 0.382432E+09 0.00 0.382432E+09 0.00 0.00
February 0.135454E+09 0.203207E+10 0.421798E+09 0.00 0.421798E+09 0.00 0.00
March 0.356098E+09 0.185600E+10 0.611267E+09 24197.95 0.611243E+09 0.00 0.00
April 0.792637E+09 0.963510E+09 0.686918E+09 8750953.90 0.678167E+09 0.00 0.00
May 0.142342E+10 0.513253E+09 0.838485E+09 61793379.53 0.776691E+09 0.00 0.00
June 0.196115E+10 0.230532E+09 0.862899E+09 0.107526E+09 0.755372E+09 0.00 0.00
July 0.186761E+10 0.182017E+09 0.823767E+09 80802541.81 0.742965E+09 0.00 0.00
August 0.145742E+10 0.280342E+09 0.696706E+09 16575260.69 0.680131E+09 0.00 0.00
September 0.104267E+10 0.596488E+09 0.586582E+09 741339.97 0.585841E+09 0.00 0.00
October 0.527825E+09 0.113186E+10 0.502433E+09 0.00 0.502433E+09 0.00 0.00
November 97200265.02 0.204852E+10 0.392527E+09 0.00 0.392527E+09 0.00 0.00
December 21840316.58 0.279947E+10 0.379470E+09 0.00 0.379470E+09 0.00 0.00
               
Annual Sum or Average 0.971423E+10 0.152087E+11 0.718528E+10 0.276214E+09 0.690907E+10 0.00 0.00
Minimum of Months 21840316.58 0.182017E+09 0.379470E+09 0.00 0.379470E+09 0.00 0.00
Maximum of Months 0.196115E+10 0.279947E+10 0.862899E+09 0.107526E+09 0.776691E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.946634E+09 0.181279E+10 0.973364E+09 0.578542E+09 0.394822E+09 0.00 0.00
February 0.117627E+10 0.143721E+10 0.103844E+10 0.601931E+09 0.436505E+09 0.00 0.00
March 0.156593E+10 0.134279E+10 0.126377E+10 0.652149E+09 0.611620E+09 0.00 0.00
April 0.211786E+10 0.736322E+09 0.133510E+10 0.654044E+09 0.681055E+09 0.00 0.00
May 0.256602E+10 0.446186E+09 0.137582E+10 0.637186E+09 0.738635E+09 0.00 0.00
June 0.291704E+10 0.222751E+09 0.132020E+10 0.625352E+09 0.694846E+09 0.00 0.00
July 0.279234E+10 0.186271E+09 0.124132E+10 0.547666E+09 0.693659E+09 0.00 0.00
August 0.259972E+10 0.258221E+09 0.120652E+10 0.530726E+09 0.675789E+09 0.00 0.00
September 0.242029E+10 0.457255E+09 0.123206E+10 0.644030E+09 0.588031E+09 0.00 0.00
October 0.178376E+10 0.846285E+09 0.112346E+10 0.612150E+09 0.511313E+09 0.00 0.00
November 0.124000E+10 0.143891E+10 0.106411E+10 0.655039E+09 0.409076E+09 0.00 0.00
December 0.909223E+09 0.192784E+10 0.983308E+09 0.577324E+09 0.405984E+09 0.00 0.00
               
Annual Sum or Average 0.230351E+11 0.111128E+11 0.141575E+11 0.731614E+10 0.684134E+10 0.00 0.00
Minimum of Months 0.909223E+09 0.186271E+09 0.973364E+09 0.530726E+09 0.394822E+09 0.00 0.00
Maximum of Months 0.291704E+10 0.192784E+10 0.137582E+10 0.655039E+09 0.738635E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.178283E+10 0.177953E+10 0.152718E+10 0.105785E+10 0.469332E+09 0.00 0.00
February 0.159840E+10 0.144863E+10 0.133098E+10 0.841376E+09 0.489606E+09 0.00 0.00
March 0.152058E+10 0.141888E+10 0.123709E+10 0.582162E+09 0.654925E+09 0.00 0.00
April 0.135260E+10 0.815852E+09 0.928373E+09 0.263104E+09 0.665269E+09 0.00 0.00
May 0.139975E+10 0.446720E+09 0.795528E+09 95695732.11 0.699832E+09 0.00 0.00
June 0.165026E+10 0.190155E+09 0.716374E+09 63322576.03 0.653051E+09 0.00 0.00
July 0.165340E+10 0.147552E+09 0.723725E+09 66827933.17 0.656897E+09 0.00 0.00
August 0.167122E+10 0.236379E+09 0.795946E+09 0.147226E+09 0.648721E+09 0.00 0.00
September 0.194592E+10 0.512051E+09 0.105488E+10 0.443840E+09 0.611036E+09 0.00 0.00
October 0.206345E+10 0.918973E+09 0.138326E+10 0.822779E+09 0.560482E+09 0.00 0.00
November 0.192987E+10 0.147972E+10 0.154509E+10 0.107890E+10 0.466191E+09 0.00 0.00
December 0.177906E+10 0.189663E+10 0.156334E+10 0.107678E+10 0.486559E+09 0.00 0.00
               
Annual Sum or Average 0.203474E+11 0.112911E+11 0.136018E+11 0.653986E+10 0.706190E+10 0.00 0.00
Minimum of Months 0.135260E+10 0.147552E+09 0.716374E+09 63322576.03 0.466191E+09 0.00 0.00
Maximum of Months 0.206345E+10 0.189663E+10 0.156334E+10 0.107890E+10 0.699832E+09 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 8.14 3.28 -3.0 3.49 -5.4 41.12 223.64 0.00
February 10.27 3.71 -4.6 3.82 -5.0 51.61 245.22 0.00
March 12.55 4.68 -5.5 4.62 -3.1 72.41 273.25 0.00
April 19.23 8.50 -2.7 4.72 3.38 79.21 314.56 0.00
May 23.84 12.23 2.64 5.25 8.38 86.83 326.20 0.00
June 27.86 15.03 5.88 4.15 14.09 80.19 344.14 0.01
July 27.54 18.92 14.64 3.53 17.44 86.25 283.04 0.01
August 26.28 17.11 12.00 3.28 15.48 80.55 269.68 0.02
September 23.38 15.82 11.20 2.23 11.29 66.71 294.09 0.00
October 18.30 12.02 7.27 3.24 6.21 54.59 257.93 0.01
November 11.18 5.22 -1.5 3.40 -3.3 40.23 258.80 0.00
December 6.79 1.84 -4.8 2.82 -8.9 42.65 217.21 0.00
                 
Annual Sum or Average 17.98 9.90 2.67 3.71 4.26 65.29 275.60 0.00
Minimum of Months 6.79 1.84 -5.5 2.23 -8.9 40.23 217.21 0.00
Maximum of Months 27.86 18.92 14.64 5.25 17.44 86.83 344.14 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 20.60 03-JAN-14:00 8.39 -5.0 9.80 2.22 118.50 530.50
February 23.30 20-FEB-14:00 8.88 -7.8 4.10 4.10 55.00 955.00
March 25.00 21-MAR-15:00 9.53 -8.3 6.20 5.54 50.00 873.00
April 32.20 21-APR-13:00 15.21 2.80 13.90 18.28 265.50 638.50
May 35.00 19-MAY-13:00 17.23 6.10 10.30 21.78 145.00 874.50
June 38.90 02-JUN-15:00 16.22 -1.1 4.60 20.40 234.50 284.00
July 38.30 01-JUL-16:00 19.19 8.90 3.60 26.81 165.50 256.50
August 37.20 07-AUG-15:00 17.89 6.70 5.70 24.66 143.50 615.00
September 33.90 19-SEP-13:00 16.85 6.70 3.10 17.75 113.00 912.00
October 32.80 01-OCT-14:00 15.90 4.40 5.70 16.12 127.50 736.50
November 23.90 03-NOV-15:00 13.45 6.10 5.70 12.22 48.50 648.50
December 18.30 10-DEC-14:00 7.97 -2.8 7.20 4.10 123.00 52.50
                 
Annual Sum or Average                
Minimum of Months 18.30   7.97 -8.3 3.10 2.22 48.50 52.50
Maximum of Months 38.90   19.19 8.90 13.90 26.81 265.50 955.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -4.4 27-JAN-06:00 -7.5 -15.0 3.60 -23.6 0.00 0.00
February -5.6 03-FEB-06:00 -7.5 -11.7 1.50 -23.9 0.00 0.00
March -3.9 02-MAR-04:00 -6.5 -12.8 1.50 -21.3 0.00 0.00
April 3.30 12-APR-05:00 -1.8 -9.4 2.10 -14.9 37.00 217.50
May 9.40 02-MAY-05:00 3.98 -2.2 3.60 -7.6 51.00 277.50
June 15.00 13-JUN-04:00 4.43 -10.6 2.10 -4.3 0.00 0.00
July 17.80 05-JUL-05:00 15.98 15.00 4.10 4.31 39.00 249.00
August 16.70 31-AUG-05:00 13.89 12.20 4.10 2.64 36.00 126.50
September 8.30 30-SEP-05:00 5.77 3.30 1.50 -7.3 0.00 0.00
October 6.70 11-OCT-05:00 5.82 5.00 1.50 -5.5 0.00 0.00
November -0.6 17-NOV-03:00 -3.1 -6.7 1.50 -18.1 0.00 0.00
December -4.4 27-DEC-06:00 -5.1 -6.1 2.10 -18.6 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -5.6   -7.5 -15.0 1.50 -23.9 0.00 0.00
Maximum of Months 17.80   15.98 15.00 4.10 4.31 51.00 277.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.18 12-JAN-15:00 18.90 2.80 3.60 6.15 70.50 491.50
February 11.42 13-FEB-16:00 12.80 10.60 4.10 6.55 34.00 18.50
March 10.75 10-MAR-18:00 13.30 8.90 1.50 8.54 0.00 0.00
April 15.74 29-APR-13:00 30.00 6.70 4.10 18.28 336.50 432.50
May 19.12 24-MAY-12:00 27.80 15.00 5.20 17.57 188.50 862.00
June 20.21 03-JUN-14:00 33.90 13.90 8.80 23.66 264.50 316.00
July 22.88 20-JUL-15:39 25.53 21.87 2.93 18.99 184.00 15.83
August 21.18 02-AUG-11:00 30.60 17.20 3.60 20.75 154.50 850.00
September 20.65 14-SEP-09:00 25.00 18.90 2.10 14.47 126.50 835.50
October 19.64 03-OCT-13:00 32.80 13.30 2.60 21.44 224.50 577.50
November 13.57 03-NOV-14:00 23.30 7.20 0.00 10.88 72.50 802.00
December 8.30 10-DEC-12:00 17.20 -0.6 5.70 1.58 198.50 507.50
                 
Annual Sum or Average                
Minimum of Months 8.30   12.80 -0.6 0.00 1.58 0.00 0.00
Maximum of Months 22.88   33.90 21.87 8.80 23.66 336.50 862.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 9.00 16-JAN-01:00 9.00 9.00 2.10 4.51 0.00 0.00
February 10.60 13-FEB-13:09 12.20 11.24 5.53 5.71 147.33 0.00
March 10.00 11-MAR-00:00 10.60 10.24 2.10 6.15 0.00 0.00
April 10.60 17-APR-01:00 17.80 13.38 7.20 3.48 0.00 0.00
May 15.00 24-MAY-10:00 25.60 18.41 7.20 15.39 171.00 872.50
June 17.20 19-JUN-17:00 23.90 19.20 3.60 15.39 86.00 324.00
July 22.20 20-JUL-14:00 24.40 22.82 4.60 17.93 283.00 59.50
August 18.90 01-AUG-20:00 22.20 19.91 4.60 17.75 0.00 0.00
September 19.40 22-SEP-01:00 20.60 19.76 1.50 16.30 0.00 0.00
October 17.20 03-OCT-19:00 23.30 19.11 4.60 18.46 0.00 0.00
November 10.00 01-NOV-09:00 13.30 11.28 3.10 8.94 123.50 0.00
December 6.10 13-DEC-00:00 8.30 7.10 7.70 3.06 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 6.10   8.30 7.10 1.50 3.06 0.00 0.00
Maximum of Months 22.20   25.60 22.82 7.70 18.46 283.00 872.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 15.16 28.38 0.00
February 18.00 13.00 16.00 15.21 35.58 0.00
March 18.00 13.00 16.00 16.80 47.71 0.00
April 18.00 13.00 16.00 19.62 58.45 0.00
May 18.00 13.00 16.00 22.88 63.58 0.00
June 18.00 13.00 16.00 25.71 66.73 0.00
July 18.00 13.00 16.00 27.35 58.19 0.00
August 18.00 13.00 16.00 27.33 54.44 0.00
September 18.00 13.00 16.00 25.68 50.89 0.00
October 18.00 13.00 16.00 22.83 39.37 0.00
November 18.00 13.00 16.00 19.57 32.11 0.00
December 18.00 13.00 16.00 16.77 26.90 0.00
             
Annual Sum or Average 18.00 13.00 16.00 21.28 46.90 0.00
Minimum of Months 18.00 13.00 16.00 15.16 26.90 0.00
Maximum of Months 18.00 13.00 16.00 27.35 66.73 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770391E+10 -0.754278E+10 0.00 0.00 744.00 0.00 -161132060.0 81.21 0.00 0.00
February 0.696159E+10 -0.681597E+10 0.00 0.00 672.00 0.00 -145621119.2 81.21 0.00 0.00
March 0.770276E+10 -0.754146E+10 0.00 0.00 744.00 0.00 -161297839.2 81.21 0.00 0.00
April 0.746476E+10 -0.730859E+10 0.00 0.00 720.00 0.00 -156170683.9 81.21 0.00 0.00
May 0.770421E+10 -0.754280E+10 0.00 0.00 744.00 0.00 -161411697.3 81.21 0.00 0.00
June 0.745674E+10 -0.730054E+10 0.00 0.00 720.00 0.00 -156203483.3 81.21 0.00 0.00
July 0.771226E+10 -0.755085E+10 0.00 0.00 744.00 0.00 -161408303.2 81.21 0.00 0.00
August 0.770422E+10 -0.754281E+10 0.00 0.00 744.00 0.00 -161408201.7 81.21 0.00 0.00
September 0.746614E+10 -0.730994E+10 0.00 0.00 720.00 0.00 -156204007.7 81.21 0.00 0.00
October 0.770285E+10 -0.754144E+10 0.00 0.00 744.00 0.00 -161412206.8 81.21 0.00 0.00
November 0.744846E+10 -0.729243E+10 0.00 0.00 720.00 0.00 -156034980.2 81.21 0.00 0.00
December 0.771199E+10 -0.755086E+10 0.00 0.00 744.00 0.00 -161128706.2 81.21 0.00 0.00
                     
Annual Sum or Average 0.907399E+11 -0.888405E+11 0.00 0.00 8760.00 0.00 -0.189943E+10 81.21 0.00 0.00
Minimum of Months 0.696159E+10 -0.755086E+10 0.00 0.00 672.00 0.00 -161412206.8 81.21 0.00 0.00
Maximum of Months 0.771226E+10 -0.681597E+10 0.00 0.00 744.00 0.00 -145621119.2 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.113621E+12 -0.111892E+12 0.00 0.00 744.00 0.00 -0.172854E+10 81.25 0.00 0.00
February 0.102573E+12 -0.100997E+12 0.00 0.00 672.00 0.00 -0.157524E+10 81.25 0.00 0.00
March 0.110873E+12 -0.109106E+12 0.00 0.00 744.00 0.00 -0.176721E+10 81.26 0.00 0.00
April 0.102672E+12 -0.100964E+12 0.00 0.00 720.00 0.00 -0.170773E+10 81.25 0.00 0.00
May 0.100552E+12 -0.987971E+11 0.00 0.00 744.00 0.00 -0.175489E+10 81.25 0.00 0.00
June 0.926529E+11 -0.909639E+11 0.00 0.00 720.00 0.00 -0.168894E+10 81.24 0.00 0.00
July 0.929599E+11 -0.912303E+11 0.00 0.00 744.00 0.00 -0.172956E+10 81.24 0.00 0.00
August 0.929797E+11 -0.912535E+11 0.00 0.00 744.00 0.00 -0.172619E+10 81.24 0.00 0.00
September 0.926945E+11 -0.910246E+11 0.00 0.00 720.00 0.00 -0.166982E+10 81.24 0.00 0.00
October 0.100608E+12 -0.988823E+11 0.00 0.00 744.00 0.00 -0.172551E+10 81.24 0.00 0.00
November 0.102716E+12 -0.101046E+12 0.00 0.00 720.00 0.00 -0.166990E+10 81.25 0.00 0.00
December 0.110894E+12 -0.109168E+12 0.00 0.00 744.00 0.00 -0.172573E+10 81.25 0.00 0.00
                     
Annual Sum or Average 0.121579E+13 -0.119533E+13 0.00 0.00 8760.00 0.00 -0.204693E+11 81.25 0.00 0.00
Minimum of Months 0.926529E+11 -0.111892E+12 0.00 0.00 672.00 0.00 -0.176721E+10 81.24 0.00 0.00
Maximum of Months 0.113621E+12 -0.909639E+11 0.00 0.00 744.00 0.00 -0.157524E+10 81.26 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.654904E+11 -0.640247E+11 0.00 0.00 744.00 0.00 -0.146564E+10 58.98 0.00 0.00
February 0.591275E+11 -0.577844E+11 0.00 0.00 672.00 0.00 -0.134309E+10 58.98 0.00 0.00
March 0.631989E+11 -0.616799E+11 0.00 0.00 744.00 0.00 -0.151899E+10 58.98 0.00 0.00
April 0.571383E+11 -0.556717E+11 0.00 0.00 720.00 0.00 -0.146664E+10 58.98 0.00 0.00
May 0.542652E+11 -0.527630E+11 0.00 0.00 744.00 0.00 -0.150218E+10 58.98 0.00 0.00
June 0.485081E+11 -0.470672E+11 0.00 0.00 720.00 0.00 -0.144090E+10 58.98 0.00 0.00
July 0.476711E+11 -0.462039E+11 0.00 0.00 744.00 0.00 -0.146720E+10 58.98 0.00 0.00
August 0.477338E+11 -0.462712E+11 0.00 0.00 744.00 0.00 -0.146257E+10 58.98 0.00 0.00
September 0.485126E+11 -0.470981E+11 0.00 0.00 720.00 0.00 -0.141447E+10 58.98 0.00 0.00
October 0.542673E+11 -0.528057E+11 0.00 0.00 744.00 0.00 -0.146166E+10 58.98 0.00 0.00
November 0.571356E+11 -0.557211E+11 0.00 0.00 720.00 0.00 -0.141450E+10 58.98 0.00 0.00
December 0.631361E+11 -0.616740E+11 0.00 0.00 744.00 0.00 -0.146201E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.666185E+12 -0.648765E+12 0.00 0.00 8760.00 0.00 -0.174199E+11 58.98 0.00 0.00
Minimum of Months 0.476711E+11 -0.640247E+11 0.00 0.00 672.00 0.00 -0.151899E+10 58.98 0.00 0.00
Maximum of Months 0.654904E+11 -0.462039E+11 0.00 0.00 744.00 0.00 -0.134309E+10 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.93 0.93 01-JAN-07:00 7206.50 38.27 274.17 278.00 949.80 26.84 164.83 257.17
February 268.33 0.93 0.93 01-FEB-07:49 5842.96 33.62 210.83 270.83 596.94 23.71 144.50 237.17
March 351.83 0.93 0.93 01-MAR-06:00 1032.16 19.53 12.00 317.83 398.13 20.87 123.83 242.50
April 373.83 0.94 0.93 01-APR-06:49 746.19 19.06 0.00 335.17 316.76 20.82 122.83 235.50
May 408.83 0.94 0.93 01-MAY-06:10 624.18 18.70 0.00 359.00 269.25 20.45 85.17 234.33
June 398.00 0.94 0.93 01-JUN-06:19 547.31 18.62 0.00 349.50 242.61 20.43 37.33 166.67
July 400.17 0.94 0.93 01-JUL-06:19 599.84 18.49 0.00 356.67 257.08 20.27 73.83 184.33
August 377.83 0.94 0.93 01-AUG-06:19 702.43 18.82 0.00 346.00 297.01 20.57 125.67 230.33
September 365.83 0.94 0.93 01-SEP-07:10 806.86 18.93 0.00 314.83 341.27 20.72 128.67 224.33
October 318.83 0.93 0.93 01-OCT-06:49 2910.30 26.00 124.83 312.50 466.70 21.79 115.83 273.00
November 295.83 0.93 0.93 01-NOV-12:39 7457.25 37.43 288.17 288.17 727.39 25.69 136.67 266.67
December 289.50 0.93 0.93 01-DEC-07:10 6497.88 37.79 284.33 276.50 1060.41 27.46 184.33 266.50
                         
Annual Sum or Average 4125.67 0.93     2543.52 24.34 1194.33 3805.00 460.33 22.15 1443.50 2818.50
Minimum of Months 268.33 0.93 0.93   547.31 18.49 0.00 270.83 242.61 20.27 37.33 166.67
Maximum of Months 408.83 0.94 0.93   7457.25 38.27 288.17 359.00 1060.41 27.46 184.33 273.00



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.62 0.61 01-JAN-07:00 7610.17 38.33 274.50 284.33 1352.56 26.47 156.83 270.50
February 268.33 0.62 0.61 01-FEB-07:40 6205.02 33.63 210.83 278.67 958.55 23.49 138.50 257.00
March 351.83 0.63 0.61 01-MAR-06:00 1286.02 19.88 20.67 333.83 651.44 21.06 143.67 302.50
April 373.83 0.63 0.61 01-APR-06:40 920.68 19.70 7.67 350.50 490.82 21.24 177.00 312.67
May 408.83 0.63 0.61 01-MAY-05:00 752.17 19.52 0.17 376.50 396.87 21.05 208.83 340.50
June 398.00 0.63 0.61 01-JUN-06:10 661.81 19.52 0.00 369.83 356.78 21.09 144.50 331.67
July 400.17 0.63 0.61 01-JUL-06:10 716.11 19.37 0.00 377.00 372.99 20.91 169.33 327.50
August 377.83 0.63 0.61 01-AUG-05:00 847.90 19.58 1.50 362.33 442.08 21.11 183.17 318.00
September 365.83 0.63 0.61 01-SEP-06:30 1017.82 19.43 8.50 333.50 551.77 21.02 148.83 296.50
October 318.83 0.62 0.61 01-OCT-06:49 3229.67 26.08 127.17 317.50 785.09 21.76 130.50 300.00
November 295.83 0.62 0.61 01-NOV-12:39 7834.17 37.51 288.17 293.83 1104.66 25.34 129.83 280.83
December 289.50 0.62 0.61 01-DEC-06:00 6887.49 37.85 284.50 281.83 1451.83 27.17 168.83 274.83
                         
Annual Sum or Average 4125.67 0.63     2777.70 24.81 1223.67 3959.67 694.22 22.38 1899.83 3612.50
Minimum of Months 268.33 0.62 0.61   661.81 19.37 0.00 278.67 356.78 20.91 129.83 257.00
Maximum of Months 408.83 0.63 0.61   7834.17 38.33 288.17 377.00 1451.83 27.17 208.83 340.50



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.83 0.80 01-JAN-08:20 282.51 14.00 0.00 221.33 148.80 17.64 0.00 33.83
February 268.33 0.82 0.80 01-FEB-08:30 319.80 14.70 0.00 229.33 166.71 18.22 0.00 66.17
March 351.83 0.82 0.80 01-MAR-07:19 383.61 15.50 0.00 301.00 188.13 18.82 0.00 130.50
April 373.83 0.81 0.80 01-APR-06:40 462.52 16.65 0.00 353.33 221.28 19.90 9.17 208.50
May 408.83 0.81 0.80 01-MAY-05:49 601.05 17.37 5.33 388.67 257.13 20.48 73.50 350.33
June 398.00 0.80 0.80 01-JUN-05:49 649.91 20.42 82.83 384.33 274.53 20.93 76.83 347.83
July 400.17 0.81 0.80 01-JUL-05:49 620.53 18.61 39.33 395.67 292.41 21.45 78.33 323.17
August 377.83 0.81 0.80 01-AUG-05:49 511.22 16.84 0.00 367.67 242.84 20.10 26.17 279.17
September 365.83 0.81 0.80 01-SEP-06:10 377.61 15.82 0.00 317.67 190.57 19.13 0.00 140.33
October 318.83 0.82 0.80 01-OCT-07:10 337.61 15.04 0.00 284.67 173.22 18.47 0.00 75.17
November 295.83 0.83 0.80 01-NOV-12:39 269.97 14.03 0.00 230.33 143.33 17.64 0.00 14.50
December 289.50 0.83 0.80 01-DEC-07:49 289.86 14.04 0.00 231.00 150.74 17.64 0.00 26.33
                         
Annual Sum or Average 4125.67 0.81     442.92 16.32 127.50 3705.00 210.63 19.37 264.00 1995.83
Minimum of Months 268.33 0.80 0.80   269.97 14.00 0.00 221.33 143.33 17.64 0.00 14.50
Maximum of Months 408.83 0.83 0.80   649.91 20.42 82.83 395.67 292.41 21.45 78.33 350.33



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.83 0.80 01-JAN-08:20 282.51 14.00 0.00 221.33 148.80 17.64 0.00 33.83
February 268.33 0.82 0.80 01-FEB-08:30 319.80 14.70 0.00 229.33 166.71 18.22 0.00 66.17
March 351.83 0.82 0.80 01-MAR-07:19 383.61 15.50 0.00 301.00 188.13 18.82 0.00 130.50
April 373.83 0.81 0.80 01-APR-06:40 462.52 16.65 0.00 353.33 221.28 19.90 9.17 208.50
May 408.83 0.81 0.80 01-MAY-05:49 601.05 17.37 5.33 388.67 257.13 20.48 73.50 350.33
June 398.00 0.80 0.80 01-JUN-05:49 649.91 20.42 82.83 384.33 274.53 20.93 76.83 347.83
July 400.17 0.81 0.80 01-JUL-05:49 620.53 18.61 39.33 395.67 292.41 21.45 78.33 323.17
August 377.83 0.81 0.80 01-AUG-05:49 511.22 16.84 0.00 367.67 242.84 20.10 26.17 279.17
September 365.83 0.81 0.80 01-SEP-06:10 377.61 15.82 0.00 317.67 190.57 19.13 0.00 140.33
October 318.83 0.82 0.80 01-OCT-07:10 337.61 15.04 0.00 284.67 173.22 18.47 0.00 75.17
November 295.83 0.83 0.80 01-NOV-12:39 269.97 14.03 0.00 230.33 143.33 17.64 0.00 14.50
December 289.50 0.83 0.80 01-DEC-07:49 289.86 14.04 0.00 231.00 150.74 17.64 0.00 26.33
                         
Annual Sum or Average 4125.67 0.81     442.92 16.32 127.50 3705.00 210.63 19.37 264.00 1995.83
Minimum of Months 268.33 0.80 0.80   269.97 14.00 0.00 221.33 143.33 17.64 0.00 14.50
Maximum of Months 408.83 0.83 0.80   649.91 20.42 82.83 395.67 292.41 21.45 78.33 350.33



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.267111E+11 150503.22 09-JAN-23:45 0.00 0.00 0.00 0.00 0.00
February 0.156889E+11 127213.93 24-FEB-05:15 0.00 0.00 0.00 0.00 0.00
March 0.119959E+11 128923.39 13-MAR-03:22 0.00 0.00 0.00 0.00 0.00
April 0.506861E+10 127472.10 13-APR-04:53 0.00 0.00 0.00 0.00 0.00
May 0.313832E+09 41315.69 02-MAY-05:30 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.448287E+09 48612.52 25-SEP-05:00 0.00 0.00 0.00 0.00 0.00
October 0.242664E+10 102499.65 25-OCT-03:10 0.00 0.00 0.00 0.00 0.00
November 0.166087E+11 149086.72 18-NOV-04:25 0.00 0.00 0.00 0.00 0.00
December 0.217781E+11 133193.50 21-DEC-23:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.101040E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.267111E+11 150503.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.185694E+09 969.31 27-JAN-07:30 0.00 0.00 0.00 0.00 0.00
February 86835953.87 915.56 03-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 51083670.29 831.23 02-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 39470.94 99.78 12-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 90656966.42 1254.66 27-NOV-11:52 0.00 0.00 0.00 0.00 0.00
December 0.314284E+09 1473.36 27-DEC-07:15 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.728594E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.314284E+09 1473.36   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 262946.07 93.80 15-JAN-16:00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 143062.11 406.04 27-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 406008.18     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 262946.07 406.04   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 99139.92 62.93 28-JAN-06:00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 16173727.66 761.63 27-DEC-12:54 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 16272867.57     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 16173727.66 761.63   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.224087E+09 715.03 11-JAN-08:40 0.00 0.00 0.00 0.00 0.00
February 0.106089E+09 606.75 03-FEB-09:39 0.00 0.00 0.00 0.00 0.00
March 40353440.12 545.08 02-MAR-11:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 58890202.89 805.04 27-NOV-11:52 0.00 0.00 0.00 0.00 0.00
December 0.380684E+09 1022.42 27-DEC-12:54 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.810104E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.380684E+09 1022.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 697156.31 2451.69 02-JAN-00:33 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 697156.31     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 697156.31 2451.69   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.289750E+09 6147.32 14-JAN-09:06 0.00 0.00 0.00 0.00 0.00
February 0.112818E+09 3419.57 27-FEB-09:07 0.00 0.00 0.00 0.00 0.00
March 85294454.05 4737.37 27-MAR-08:13 0.00 0.00 0.00 0.00 0.00
April 6098932.08 2353.29 11-APR-08:18 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 218560.25 259.71 16-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 3561414.26 1125.09 14-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.212640E+09 6949.77 27-NOV-11:52 0.00 0.00 0.00 0.00 0.00
December 0.272622E+09 9290.52 03-DEC-11:58 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.983003E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.289750E+09 9290.52   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 2501517.39 1520.59 15-JAN-16:00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2501517.39     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 2501517.39 1520.59   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 14094029.93 1264.15 17-JAN-11:23 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.175453E+09 4932.89 03-DEC-11:58 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.189547E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.175453E+09 4932.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.179402E+09 2095.45 27-JAN-07:15 0.00 0.00 0.00 0.00 0.00
February 90991115.21 2197.45 03-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 29019497.08 1541.18 02-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 81484594.09 2011.28 27-NOV-11:52 0.00 0.00 0.00 0.00 0.00
December 0.593488E+09 2812.66 27-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.974385E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.593488E+09 2812.66   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 12130231.83 3387.63 23-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 5990384.97 1912.23 01-FEB-11:13 0.00 0.00 0.00 0.00 0.00
March 3571646.11 3636.74 02-MAR-11:40 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 6244617.37 7356.88 27-NOV-11:52 0.00 0.00 0.00 0.00 0.00
December 24230081.35 8434.23 19-DEC-12:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 52166961.63     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 24230081.35 8434.23   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 69943.19 233.14 23-JAN-11:45 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 582539.43 837.51 02-MAR-11:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 2193678.73 3914.83 27-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2846161.35     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 2193678.73 3914.83   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 48888398.20 2447.72 27-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 71253799.96 2914.84 03-FEB-07:00 0.00 0.00 0.00 0.00 0.00
March 34408146.74 2447.73 02-MAR-06:00 0.00 0.00 0.00 0.00 0.00
April 33259.54 0.50 30-APR-16:50 0.00 0.00 0.00 0.00 0.00
May 48666.88 0.50 13-MAY-15:40 0.00 0.00 0.00 0.00 0.00
June 50726.14 0.51 08-JUN-02:40 0.00 0.00 0.00 0.00 0.00
July 15400.64 0.51 12-JUL-04:50 0.00 0.00 0.00 0.00 0.00
August 31376.35 0.51 11-AUG-08:07 0.00 0.00 0.00 0.00 0.00
September 20445.35 0.50 21-SEP-07:08 0.00 0.00 0.00 0.00 0.00
October 29792.77 0.50 04-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 4826319.49 678.04 28-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.205105E+09 3422.98 27-DEC-07:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.364712E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 15400.64 0.50   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.205105E+09 3422.98   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.164341E+10 9568.32 27-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.101161E+10 9499.84 02-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.557949E+09 9523.04 02-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 56283918.63 5930.77 11-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 4563122.11 3481.65 28-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 4127699.85 2879.01 25-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 4354082.16 3103.80 21-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 4757677.97 3397.91 12-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 4557210.23 3226.74 16-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 11710817.74 3198.75 15-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.756288E+09 9426.84 28-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.218576E+10 9619.18 27-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.624536E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 4127699.85 2879.01   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.218576E+10 9619.18   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.270264E+10 9612.52 27-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.167743E+10 9582.22 10-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.857862E+09 9550.46 02-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 78771629.65 6907.79 11-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 4440477.25 3246.55 06-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 3700423.72 2712.46 30-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 4018910.19 3529.91 21-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 5134014.69 3413.28 12-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 5559323.78 3509.05 10-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 27310656.35 3093.43 28-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.126804E+10 9456.74 28-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.347584E+10 9596.10 27-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.101108E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3700423.72 2712.46   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.347584E+10 9612.52   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 502779.05 720.15 27-DEC-06:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 502779.05     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 502779.05 720.15   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.936228E+10 55057.05 27-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.546752E+10 54726.72 03-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.219175E+10 54422.06 02-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.217617E+09 32453.03 10-APR-15:04 0.00 0.00 0.00 0.00 0.00
May 63049408.75 34561.85 07-MAY-15:04 0.00 0.00 0.00 0.00 0.00
June 24936769.49 19713.69 03-JUN-18:06 0.00 0.00 0.00 0.00 0.00
July 26290029.64 27635.35 05-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 37128042.96 32113.21 24-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 56302695.82 31512.73 21-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 0.120005E+09 29070.28 31-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.422571E+10 53820.16 28-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.128133E+11 54940.66 27-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.346059E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 24936769.49 19713.69   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.128133E+11 55057.05   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.172939E+10 8978.77 26-JAN-19:01 0.00 0.00 0.00 0.00 0.00
February 0.951498E+09 8846.01 27-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.564359E+09 9155.72 02-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 52408445.49 2901.79 11-APR-18:03 0.00 0.00 0.00 0.00 0.00
May 1737748.32 2469.84 02-MAY-18:04 0.00 0.00 0.00 0.00 0.00
June 66084.46 660.84 29-JUN-18:05 0.00 0.00 0.00 0.00 0.00
July 330369.21 847.37 07-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 1348763.26 2963.69 17-AUG-18:04 0.00 0.00 0.00 0.00 0.00
September 390667.88 2451.05 24-SEP-18:04 0.00 0.00 0.00 0.00 0.00
October 24612976.59 2997.61 07-OCT-15:04 0.00 0.00 0.00 0.00 0.00
November 0.819723E+09 9101.36 27-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.221014E+10 9261.26 26-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.635600E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 66084.46 660.84   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.221014E+10 9261.26   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.277024E+10 9091.10 26-JAN-19:01 0.00 0.00 0.00 0.00 0.00
February 0.151712E+10 8990.38 01-FEB-19:02 0.00 0.00 0.00 0.00 0.00
March 0.824225E+09 9192.20 02-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 72651431.39 3531.49 18-APR-18:04 0.00 0.00 0.00 0.00 0.00
May 2087754.50 3018.49 02-MAY-18:04 0.00 0.00 0.00 0.00 0.00
June 22093.52 220.94 29-JUN-18:05 0.00 0.00 0.00 0.00 0.00
July 266957.04 654.74 07-JUL-18:05 0.00 0.00 0.00 0.00 0.00
August 1585410.73 3426.53 17-AUG-18:04 0.00 0.00 0.00 0.00 0.00
September 1155399.29 2181.84 30-SEP-18:04 0.00 0.00 0.00 0.00 0.00
October 58118681.52 3360.92 24-OCT-15:03 0.00 0.00 0.00 0.00 0.00
November 0.130643E+10 9105.82 27-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.344553E+10 9261.17 26-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.999943E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 22093.52 220.94   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.344553E+10 9261.17   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.746539E+09 2882.53 27-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.503094E+09 2870.98 10-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.326170E+09 2863.99 02-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 52835060.80 2768.08 11-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 2818464.01 802.09 10-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 1019963.47 733.95 04-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 1304130.15 888.69 18-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 1479380.92 849.61 23-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 1867936.78 724.61 03-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 31957936.12 903.63 06-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.406471E+09 2836.18 28-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.929321E+09 2877.70 27-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.300488E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1019963.47 724.61   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.929321E+09 2882.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.111230E+10 2875.70 27-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.744454E+09 2866.67 10-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.447127E+09 2857.19 02-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 66115037.86 2766.39 11-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 2932851.24 855.23 27-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 989069.66 723.22 04-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 1239161.89 845.03 18-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 1558113.34 787.47 23-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 3111659.77 810.97 23-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 64191254.12 2497.37 25-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.643088E+09 2829.45 28-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.135353E+10 2870.86 27-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.444064E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 989069.66 723.22   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.135353E+10 2875.70   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.131043E+10 12969.27 14-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.857639E+09 11368.62 27-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.664063E+09 13320.37 02-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.136067E+09 8487.58 11-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 13481259.16 4621.62 05-MAY-18:04 0.00 0.00 0.00 0.00 0.00
June 8762695.56 4886.32 19-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 7489244.03 4855.43 10-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 7796623.01 4866.93 11-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 4343399.16 4087.97 19-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 21860723.44 4457.88 14-OCT-15:04 0.00 0.00 0.00 0.00 0.00
November 0.753099E+09 13184.91 27-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.175080E+10 13388.60 26-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.553584E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 4343399.16 4087.97   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.175080E+10 13388.60   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.716861E+10 0.716861E+10 93651.60 03-JAN-17:00 93651.60 0.00
February 0.00 0.00 0.347043E+11 0.347043E+11 128540.56 20-FEB-16:20 128540.56 0.00
March 0.00 0.00 0.702420E+11 0.702420E+11 165916.23 14-MAR-17:13 165916.23 0.00
April 0.00 0.00 0.215062E+12 0.215062E+12 228369.22 19-APR-21:00 228369.22 0.06
May 0.00 0.00 0.357119E+12 0.355312E+12 257953.19 19-MAY-20:10 257953.19 0.37
June 0.00 0.00 0.463005E+12 0.457562E+12 304214.02 19-JUN-18:07 211860.42 0.68
July 0.00 0.00 0.618069E+12 0.481303E+12 472231.72 18-JUL-20:50 160634.94 1.00
August 0.00 0.00 0.504514E+12 0.450042E+12 467350.66 01-AUG-20:50 217572.10 0.97
September 0.00 0.00 0.412748E+12 0.354800E+12 346303.91 09-SEP-20:00 190090.30 0.81
October 0.00 0.00 0.204981E+12 0.195856E+12 395164.94 03-OCT-20:00 214577.20 0.41
November 0.00 0.00 0.433069E+11 0.433069E+11 152247.78 03-NOV-16:00 152247.78 0.03
December 0.00 0.00 0.436754E+10 0.436754E+10 52907.71 23-DEC-15:00 52907.71 0.00
                 
Annual Sum or Average 0.00 0.00 0.293529E+13 0.266972E+13       0.36
Minimum of Months 0.00 0.00 0.436754E+10 0.436754E+10 52907.71   52907.71 0.00
Maximum of Months 0.00 0.00 0.618069E+12 0.481303E+12 472231.72   257953.19 1.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.122870E+10 0.122870E+10 18651.05 03-JAN-15:00 18651.05 0.00
February 0.00 0.00 0.618797E+10 0.618797E+10 23693.24 20-FEB-16:00 23693.24 0.00
March 0.00 0.00 0.122343E+11 0.122343E+11 24657.75 22-MAR-13:00 24657.75 0.00
April 0.00 0.00 0.348126E+11 0.348126E+11 29774.81 21-APR-15:00 29774.81 0.05
May 0.00 0.00 0.557264E+11 0.546336E+11 34982.72 24-MAY-13:00 27324.60 0.28
June 0.00 0.00 0.679277E+11 0.656138E+11 40511.58 27-JUN-24:00 20042.19 0.58
July 0.00 0.00 0.903037E+11 0.685052E+11 55414.96 21-JUL-08:00 18921.20 1.00
August 0.00 0.00 0.760520E+11 0.648652E+11 47992.63 02-AUG-03:50 20101.26 0.95
September 0.00 0.00 0.649768E+11 0.520160E+11 47427.38 22-SEP-02:00 17001.66 0.79
October 0.00 0.00 0.332051E+11 0.304518E+11 42555.84 03-OCT-20:40 21350.30 0.41
November 0.00 0.00 0.750498E+10 0.750498E+10 24036.88 08-NOV-15:00 24036.88 0.02
December 0.00 0.00 0.724517E+09 0.724517E+09 11238.19 10-DEC-15:00 11238.19 0.00
                 
Annual Sum or Average 0.00 0.00 0.450885E+12 0.398779E+12       0.34
Minimum of Months 0.00 0.00 0.724517E+09 0.724517E+09 11238.19   11238.19 0.00
Maximum of Months 0.00 0.00 0.903037E+11 0.685052E+11 55414.96   29774.81 1.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.671030E+09 0.670438E+09 14474.63 03-JAN-16:01 14474.63 0.00
February 0.00 0.00 0.110388E+10 0.110256E+10 14890.92 20-FEB-16:01 14890.92 0.00
March 0.00 0.00 0.212310E+10 0.211888E+10 15048.49 21-MAR-15:01 15048.49 0.01
April 0.00 0.00 0.528641E+10 0.494931E+10 15387.69 19-APR-18:01 15387.69 0.14
May 0.00 0.00 0.833939E+10 0.704930E+10 15388.05 20-MAY-18:01 15388.05 0.40
June 0.00 0.00 0.106356E+11 0.828857E+10 15385.19 17-JUN-15:02 15385.19 0.70
July 0.00 0.00 0.115254E+11 0.737916E+10 17009.89 20-JUL-08:61 11749.60 0.95
August 0.00 0.00 0.104753E+11 0.681315E+10 15794.40 02-AUG-08:61 12714.78 0.93
September 0.00 0.00 0.949976E+10 0.630370E+10 15800.63 09-SEP-08:61 12262.88 0.87
October 0.00 0.00 0.602678E+10 0.435033E+10 15305.24 21-OCT-15:01 15305.24 0.56
November 0.00 0.00 0.212641E+10 0.200685E+10 14930.59 09-NOV-16:01 14930.59 0.07
December 0.00 0.00 0.369382E+09 0.369382E+09 14069.01 23-DEC-16:01 14069.01 0.00
                 
Annual Sum or Average 0.00 0.00 0.681824E+11 0.514016E+11       0.39
Minimum of Months 0.00 0.00 0.369382E+09 0.369382E+09 14069.01   11749.60 0.00
Maximum of Months 0.00 0.00 0.115254E+11 0.828857E+10 17009.89   15388.05 0.95



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.131543E+09 0.130999E+09 13985.84 12-JAN-16:01 13985.84 0.00
February 0.00 0.00 0.368761E+09 0.368091E+09 14777.23 20-FEB-16:01 14777.23 0.00
March 0.00 0.00 0.123588E+10 0.123317E+10 14934.58 21-MAR-15:01 14934.58 0.00
April 0.00 0.00 0.451657E+10 0.420757E+10 15270.26 19-APR-18:01 15270.26 0.13
May 0.00 0.00 0.812970E+10 0.685950E+10 15271.49 20-MAY-18:01 15271.49 0.40
June 0.00 0.00 0.107027E+11 0.838306E+10 15268.60 17-JUN-15:02 15268.60 0.70
July 0.00 0.00 0.114724E+11 0.738141E+10 16518.49 08-JUL-08:61 12133.18 0.95
August 0.00 0.00 0.988001E+10 0.631301E+10 15765.98 02-AUG-08:61 12566.41 0.92
September 0.00 0.00 0.798041E+10 0.495802E+10 15608.10 09-SEP-08:61 12209.68 0.84
October 0.00 0.00 0.406955E+10 0.271128E+10 15188.88 21-OCT-15:01 15188.88 0.50
November 0.00 0.00 0.690078E+09 0.633956E+09 14818.10 09-NOV-16:01 14818.10 0.04
December 0.00 0.00 52500207.29 52500207.29 13314.87 16-DEC-16:02 13314.87 0.00
                 
Annual Sum or Average 0.00 0.00 0.592300E+11 0.432326E+11       0.38
Minimum of Months 0.00 0.00 52500207.29 52500207.29 13314.87   12133.18 0.00
Maximum of Months 0.00 0.00 0.114724E+11 0.838306E+10 16518.49   15271.49 0.95



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.129405E+11 0.129405E+11 36097.79 12-JAN-14:30 36097.79 0.00
February 0.00 0.00 0.122174E+11 0.122174E+11 33506.84 07-FEB-13:40 33506.84 0.00
March 0.00 0.00 0.844895E+10 0.844895E+10 25257.35 16-MAR-13:30 25257.35 0.00
April 0.00 0.00 0.149179E+11 0.143412E+11 24186.74 04-APR-13:30 24186.74 0.04
May 0.00 0.00 0.204865E+11 0.166138E+11 20983.79 19-MAY-17:20 13742.21 0.23
June 0.00 0.00 0.305562E+11 0.217467E+11 25309.39 15-JUN-17:13 25309.39 0.53
July 0.00 0.00 0.356368E+11 0.157876E+11 27910.78 26-JUL-17:20 18936.68 0.97
August 0.00 0.00 0.352593E+11 0.186574E+11 30610.73 29-AUG-13:20 21886.54 0.88
September 0.00 0.00 0.403219E+11 0.264905E+11 39123.09 20-SEP-15:02 33495.76 0.77
October 0.00 0.00 0.338967E+11 0.275361E+11 44065.97 22-OCT-13:20 39376.11 0.38
November 0.00 0.00 0.230354E+11 0.227344E+11 40218.59 09-NOV-13:50 40218.59 0.03
December 0.00 0.00 0.990409E+10 0.990409E+10 30365.89 16-DEC-14:10 30365.89 0.00
                 
Annual Sum or Average 0.00 0.00 0.277622E+12 0.207419E+12       0.32
Minimum of Months 0.00 0.00 0.844895E+10 0.844895E+10 20983.79   13742.21 0.00
Maximum of Months 0.00 0.00 0.403219E+11 0.275361E+11 44065.97   40218.59 0.97



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.104106E+10 0.100813E+10 52497.96 15-JAN-09:01 47194.05 0.01
February 0.00 0.00 0.297821E+10 0.279047E+10 77279.99 20-FEB-09:01 77279.99 0.03
March 0.00 0.00 0.813544E+10 0.795461E+10 84187.57 21-MAR-18:01 84187.57 0.02
April 0.00 0.00 0.255835E+11 0.241104E+11 94232.94 21-APR-18:01 94232.94 0.09
May 0.00 0.00 0.458559E+11 0.387127E+11 94325.56 20-MAY-18:01 94325.56 0.31
June 0.00 0.00 0.617328E+11 0.490262E+11 94339.11 06-JUN-15:02 94339.11 0.57
July 0.00 0.00 0.695542E+11 0.451298E+11 104574.26 08-JUL-08:61 74424.13 0.79
August 0.00 0.00 0.581977E+11 0.371416E+11 95961.01 02-AUG-08:61 74834.31 0.75
September 0.00 0.00 0.440525E+11 0.271598E+11 95012.57 23-SEP-08:61 77653.86 0.63
October 0.00 0.00 0.244524E+11 0.154547E+11 89606.94 03-OCT-18:02 81404.23 0.45
November 0.00 0.00 0.408310E+10 0.351030E+10 81213.16 08-NOV-19:01 81213.16 0.06
December 0.00 0.00 0.686038E+09 0.686038E+09 66057.82 09-DEC-09:02 66057.82 0.00
                 
Annual Sum or Average 0.00 0.00 0.346353E+12 0.252685E+12       0.31
Minimum of Months 0.00 0.00 0.686038E+09 0.686038E+09 52497.96   47194.05 0.00
Maximum of Months 0.00 0.00 0.695542E+11 0.490262E+11 104574.26   94339.11 0.79



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.599809E+09 0.596618E+09 12497.15 12-JAN-16:01 12497.15 0.00
February 0.00 0.00 0.125603E+10 0.124417E+10 12982.40 20-FEB-16:01 12982.40 0.01
March 0.00 0.00 0.216217E+10 0.215637E+10 13120.39 21-MAR-15:01 13120.39 0.01
April 0.00 0.00 0.554281E+10 0.521033E+10 13416.25 27-APR-18:01 13416.25 0.15
May 0.00 0.00 0.848276E+10 0.721765E+10 13415.84 09-MAY-18:01 13415.84 0.42
June 0.00 0.00 0.108921E+11 0.860525E+10 13414.48 17-JUN-15:02 13414.48 0.73
July 0.00 0.00 0.117779E+11 0.764782E+10 14539.09 19-JUL-08:62 9310.29 0.97
August 0.00 0.00 0.106839E+11 0.707298E+10 13274.96 18-AUG-08:62 10888.52 0.96
September 0.00 0.00 0.953444E+10 0.634253E+10 13414.80 11-SEP-18:01 13414.80 0.90
October 0.00 0.00 0.561140E+10 0.408191E+10 13343.94 21-OCT-15:01 13343.94 0.56
November 0.00 0.00 0.200246E+10 0.191424E+10 13017.35 09-NOV-16:01 13017.35 0.06
December 0.00 0.00 0.416595E+09 0.416595E+09 12106.53 16-DEC-09:02 12106.53 0.00
                 
Annual Sum or Average 0.00 0.00 0.689624E+11 0.525065E+11       0.40
Minimum of Months 0.00 0.00 0.416595E+09 0.416595E+09 12106.53   9310.29 0.00
Maximum of Months 0.00 0.00 0.117779E+11 0.860525E+10 14539.09   13416.25 0.97



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 66604105.40 65894318.75 10246.66 04-JAN-09:02 10246.66 0.00
February 0.00 0.00 0.435069E+09 0.425738E+09 12459.22 21-FEB-16:01 12459.22 0.01
March 0.00 0.00 0.121903E+10 0.121532E+10 12952.42 22-MAR-15:01 12952.42 0.01
April 0.00 0.00 0.471166E+10 0.440141E+10 13307.96 27-APR-18:01 13307.96 0.14
May 0.00 0.00 0.825733E+10 0.700053E+10 13307.54 09-MAY-18:01 13307.54 0.42
June 0.00 0.00 0.109533E+11 0.868780E+10 13306.23 17-JUN-15:02 13306.23 0.73
July 0.00 0.00 0.117174E+11 0.763290E+10 14375.65 19-JUL-08:62 9251.62 0.97
August 0.00 0.00 0.100750E+11 0.650388E+10 13245.32 16-AUG-15:02 11547.91 0.96
September 0.00 0.00 0.799423E+10 0.501261E+10 13306.38 11-SEP-18:01 13306.38 0.88
October 0.00 0.00 0.360864E+10 0.244157E+10 13235.82 21-OCT-15:01 13235.82 0.49
November 0.00 0.00 0.632305E+09 0.591539E+09 12625.58 09-NOV-16:01 12625.58 0.03
December 0.00 0.00 47021796.35 47021796.35 11256.06 09-DEC-09:02 11256.06 0.00
                 
Annual Sum or Average 0.00 0.00 0.597176E+11 0.440262E+11       0.39
Minimum of Months 0.00 0.00 47021796.35 47021796.35 10246.66   9251.62 0.00
Maximum of Months 0.00 0.00 0.117174E+11 0.868780E+10 14375.65   13307.96 0.97



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.123977E+09 0.123824E+09 3848.79 03-JAN-16:01 3848.79 0.00
February 0.00 0.00 0.218500E+09 0.218313E+09 3959.53 20-FEB-16:01 3959.53 0.00
March 0.00 0.00 0.432427E+09 0.432389E+09 4001.44 21-MAR-15:01 4001.44 0.00
April 0.00 0.00 0.120958E+10 0.112591E+10 4091.51 19-APR-18:01 4091.51 0.14
May 0.00 0.00 0.201804E+10 0.167916E+10 4091.68 20-MAY-18:01 4091.68 0.41
June 0.00 0.00 0.273804E+10 0.211493E+10 4090.98 17-JUN-15:02 4090.98 0.70
July 0.00 0.00 0.296315E+10 0.187179E+10 4689.66 20-JUL-08:61 2995.83 0.95
August 0.00 0.00 0.264212E+10 0.170211E+10 4316.95 02-AUG-08:61 3263.67 0.93
September 0.00 0.00 0.230778E+10 0.149588E+10 4337.65 09-SEP-08:61 3115.94 0.87
October 0.00 0.00 0.130232E+10 0.932957E+09 4069.74 21-OCT-15:01 4069.74 0.48
November 0.00 0.00 0.393475E+09 0.374931E+09 3970.08 09-NOV-16:01 3970.08 0.04
December 0.00 0.00 68596471.03 68596471.03 3740.98 23-DEC-16:01 3740.98 0.00
                 
Annual Sum or Average 0.00 0.00 0.164180E+11 0.121408E+11       0.38
Minimum of Months 0.00 0.00 68596471.03 68596471.03 3740.98   2995.83 0.00
Maximum of Months 0.00 0.00 0.296315E+10 0.211493E+10 4689.66   4091.68 0.95



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 19453280.16 19308246.28 3669.60 12-JAN-16:01 3669.60 0.00
February 0.00 0.00 63847607.68 63727887.10 3924.17 20-FEB-16:01 3924.17 0.00
March 0.00 0.00 0.234176E+09 0.234133E+09 3965.90 21-MAR-15:01 3965.90 0.00
April 0.00 0.00 0.101414E+10 0.939172E+09 4055.30 19-APR-18:01 4055.30 0.13
May 0.00 0.00 0.196328E+10 0.162926E+10 4055.38 20-MAY-18:01 4055.38 0.41
June 0.00 0.00 0.275526E+10 0.213764E+10 4054.67 17-JUN-15:02 4054.67 0.70
July 0.00 0.00 0.294932E+10 0.186731E+10 4560.54 08-JUL-08:61 3114.25 0.95
August 0.00 0.00 0.248524E+10 0.156596E+10 4316.69 02-AUG-08:61 3224.56 0.92
September 0.00 0.00 0.190710E+10 0.115134E+10 4273.28 23-SEP-08:61 3250.60 0.84
October 0.00 0.00 0.817569E+09 0.542648E+09 4033.50 21-OCT-15:01 4033.50 0.40
November 0.00 0.00 0.107922E+09 0.100690E+09 3934.91 09-NOV-16:01 3934.91 0.02
December 0.00 0.00 8203954.65 8203954.65 3444.38 16-DEC-16:02 3444.38 0.00
                 
Annual Sum or Average 0.00 0.00 0.143255E+11 0.102594E+11       0.37
Minimum of Months 0.00 0.00 8203954.65 8203954.65 3444.38   3114.25 0.00
Maximum of Months 0.00 0.00 0.294932E+10 0.213764E+10 4560.54   4055.38 0.95



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.396812E+10 0.395843E+10 17001.46 03-JAN-16:01 17001.46 0.01
February 0.00 0.00 0.398326E+10 0.396888E+10 17490.48 20-FEB-16:01 17490.48 0.01
March 0.00 0.00 0.384131E+10 0.382890E+10 17675.70 21-MAR-15:01 17675.70 0.01
April 0.00 0.00 0.622106E+10 0.577389E+10 18067.01 21-APR-18:01 18067.01 0.15
May 0.00 0.00 0.858777E+10 0.693302E+10 18070.33 12-MAY-15:02 18070.33 0.42
June 0.00 0.00 0.116712E+11 0.867014E+10 18068.67 11-JUN-18:01 18068.67 0.70
July 0.00 0.00 0.135021E+11 0.818210E+10 20926.61 20-JUL-08:61 12856.85 0.93
August 0.00 0.00 0.129933E+11 0.829040E+10 18902.72 02-AUG-08:61 14451.73 0.93
September 0.00 0.00 0.131179E+11 0.899396E+10 19046.99 09-SEP-08:61 14157.05 0.87
October 0.00 0.00 0.103338E+11 0.809790E+10 17976.73 21-OCT-15:01 17976.73 0.58
November 0.00 0.00 0.625146E+10 0.605658E+10 17534.77 09-NOV-16:01 17534.77 0.09
December 0.00 0.00 0.354599E+10 0.354579E+10 16559.95 10-DEC-16:01 16559.95 0.00
                 
Annual Sum or Average 0.00 0.00 0.980173E+11 0.763000E+11       0.39
Minimum of Months 0.00 0.00 0.354599E+10 0.354579E+10 16559.95   12856.85 0.00
Maximum of Months 0.00 0.00 0.135021E+11 0.899396E+10 20926.61   18070.33 0.93



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 18050.00 207629.42 17-JAN-09:01
February 0.00 0.00 01-FEB-00:05 11786.58 149433.58 17-FEB-09:01
March 0.00 0.00 01-MAR-00:10 6879.71 121670.79 31-MAR-04:00
April 0.00 0.00 01-APR-00:10 2210.61 126183.98 13-APR-04:53
May 0.00 0.00 01-MAY-00:10 153.75 78417.52 02-MAY-18:04
June 0.00 0.00 01-JUN-00:10 18.72 23758.49 01-JUN-08:04
July 0.00 0.00 01-JUL-00:10 17.03 21751.99 05-JUL-08:05
August 0.00 0.00 01-AUG-00:10 21.74 36268.08 24-AUG-08:04
September 0.00 0.00 01-SEP-00:10 197.94 46455.89 25-SEP-05:10
October 0.00 0.00 01-OCT-00:10 1033.12 79268.89 25-OCT-05:10
November 0.00 0.00 01-NOV-00:10 10364.14 151510.14 26-NOV-16:01
December 0.00 0.00 01-DEC-00:05 19119.25 158292.18 02-DEC-19:05
             
Annual Sum or Average 0.00     5800.76    
Minimum of Months 0.00 0.00   17.03 21751.99  
Maximum of Months 0.00 0.00   19119.25 207629.42  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 13096.28 191318.58 03-JAN-16:03 0.00 0.00 01-JAN-00:05
February 29542.23 312525.30 20-FEB-16:01 0.00 0.00 01-FEB-00:05
March 44922.07 357836.17 14-MAR-18:01 0.00 0.00 01-MAR-00:10
April 128342.83 432476.62 19-APR-18:03 0.00 0.00 01-APR-00:10
May 202109.21 446198.98 15-MAY-18:03 0.00 0.00 01-MAY-00:10
June 270306.07 526157.01 18-JUN-18:02 0.00 0.00 01-JUN-00:10
July 335066.90 629435.00 18-JUL-20:50 0.00 0.00 01-JUL-00:10
August 280392.31 594876.37 01-AUG-20:50 0.00 0.00 01-AUG-00:10
September 243483.05 510544.37 22-SEP-08:61 0.00 0.00 01-SEP-00:10
October 128038.85 532061.36 03-OCT-20:00 0.00 0.00 01-OCT-00:10
November 38324.10 334455.76 09-NOV-16:01 0.00 0.00 01-NOV-00:10
December 10057.67 96231.98 23-DEC-15:00 0.00 0.00 01-DEC-00:05
             
Annual Sum or Average 144287.80     0.00    
Minimum of Months 10057.67 96231.98   0.00 0.00  
Maximum of Months 335066.90 629435.00   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 25402.54 63640.46 25-JAN-07:01
February 0.00 0.00 01-FEB-00:05 25416.60 62862.44 24-FEB-07:51
March 0.00 0.00 01-MAR-00:10 24577.96 56141.27 13-MAR-06:25
April 0.00 0.00 01-APR-00:10 23041.97 52370.67 13-APR-06:24
May 0.00 0.00 01-MAY-00:10 21279.74 44499.86 01-MAY-06:10
June 0.00 0.00 01-JUN-00:10 19745.25 40781.93 01-JUN-07:00
July 0.00 0.00 01-JUL-00:10 18838.55 38088.58 03-JUL-06:30
August 0.00 0.00 01-AUG-00:10 18864.24 38237.03 31-AUG-06:40
September 0.00 0.00 01-SEP-00:10 19752.80 43158.93 25-SEP-06:15
October 0.00 0.00 01-OCT-00:10 21280.51 49130.40 25-OCT-06:08
November 0.00 0.00 01-NOV-00:10 23022.73 56909.33 21-NOV-07:31
December 0.00 0.00 01-DEC-00:05 24528.32 58382.95 10-DEC-08:11
             
Annual Sum or Average 0.00     22127.33    
Minimum of Months 0.00 0.00   18838.55 38088.58  
Maximum of Months 0.00 0.00   25416.60 63640.46  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.587890E+10 1.01 2194.93 01-JAN-00:05 1.01
February 0.530997E+10 1.01 2194.93 01-FEB-00:05 1.01
March 0.587890E+10 1.01 2194.93 01-MAR-00:10 1.01
April 0.568926E+10 1.01 2194.93 01-APR-00:10 1.02
May 0.587890E+10 1.01 2194.93 01-MAY-00:10 1.01
June 0.568926E+10 1.01 2194.93 01-JUN-00:10 1.01
July 0.587890E+10 1.00 2194.93 01-JUL-00:10 1.00
August 0.587890E+10 1.00 2194.93 01-AUG-00:10 1.00
September 0.568926E+10 1.00 2194.93 01-SEP-00:10 1.00
October 0.587890E+10 1.01 2194.93 01-OCT-00:10 1.01
November 0.568926E+10 1.01 2194.93 01-NOV-00:10 1.01
December 0.587890E+10 1.01 2194.93 01-DEC-00:05 1.01
           
Annual Sum or Average 0.692193E+11 1.01      
Minimum of Months 0.530997E+10 1.00 2194.93   1.00
Maximum of Months 0.587890E+10 1.01 2194.93   1.02



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.373875E+11 0.91 43728.93 09-JAN-22:45 1.82
February 0.329253E+11 0.90 44052.41 08-FEB-21:40 1.83
March 0.366613E+11 0.91 33552.02 17-MAR-21:27 1.54
April 0.376419E+11 0.94 34542.94 22-APR-05:15 1.57
May 0.419622E+11 0.97 34988.72 31-MAY-21:10 1.57
June 0.445456E+11 1.02 37699.29 15-JUN-21:10 1.65
July 0.467919E+11 1.02 40046.31 26-JUL-21:10 1.70
August 0.475880E+11 1.03 42560.53 07-AUG-21:10 1.77
September 0.455316E+11 1.03 42767.10 22-SEP-21:10 1.77
October 0.433921E+11 0.99 42196.05 05-OCT-21:10 1.76
November 0.391589E+11 0.95 43551.85 18-NOV-04:25 1.82
December 0.383637E+11 0.93 44329.05 06-DEC-22:55 1.84
           
Annual Sum or Average 0.491950E+12 0.97      
Minimum of Months 0.329253E+11 0.90 33552.02   1.54
Maximum of Months 0.475880E+11 1.03 44329.05   1.84



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.31 76.61 01-JAN-00:05 0.31
February 0.185347E+09 0.31 76.61 01-FEB-00:05 0.31
March 0.205205E+09 0.31 76.61 01-MAR-00:10 0.31
April 0.198586E+09 0.31 76.61 01-APR-00:10 0.31
May 0.205205E+09 0.31 76.61 01-MAY-00:10 0.31
June 0.198586E+09 0.30 76.61 01-JUN-00:10 0.31
July 0.205205E+09 0.30 76.61 01-JUL-00:10 0.30
August 0.205205E+09 0.30 76.61 01-AUG-00:10 0.30
September 0.198586E+09 0.30 76.61 01-SEP-00:10 0.30
October 0.205205E+09 0.30 76.61 01-OCT-00:10 0.31
November 0.198586E+09 0.31 76.61 01-NOV-00:10 0.31
December 0.205205E+09 0.31 76.61 01-DEC-00:05 0.31
           
Annual Sum or Average 0.241613E+10 0.31      
Minimum of Months 0.185347E+09 0.30 76.61   0.30
Maximum of Months 0.205205E+09 0.31 76.61   0.31



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:05 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:05 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:05 0.00
March 0.00 -0.0 0.00 01-MAR-00:10 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:10 0.00
September 0.00 -0.0 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:05 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 -0.0 0.00 01-FEB-00:05 0.00
March 0.00 -0.0 0.00 01-MAR-00:10 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:10 0.00
December 0.00 -0.0 0.00 01-DEC-00:05 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.22 612.92 01-JAN-07:03 0.30
February 0.105030E+10 0.22 612.92 01-FEB-07:05 0.31
March 0.116283E+10 0.22 612.92 01-MAR-07:05 0.31
April 0.112532E+10 0.22 612.92 01-APR-06:05 0.31
May 0.116283E+10 0.22 612.92 01-MAY-06:05 0.31
June 0.112532E+10 0.22 612.92 01-JUN-06:05 0.31
July 0.116283E+10 0.21 612.92 01-JUL-06:05 0.30
August 0.116283E+10 0.21 612.92 01-AUG-06:05 0.30
September 0.112532E+10 0.21 612.92 01-SEP-06:05 0.30
October 0.116283E+10 0.22 612.92 01-OCT-06:10 0.31
November 0.112532E+10 0.22 612.92 01-NOV-06:10 0.30
December 0.116283E+10 0.22 612.92 01-DEC-07:01 0.31
           
Annual Sum or Average 0.136914E+11 0.22      
Minimum of Months 0.105030E+10 0.21 612.92   0.30
Maximum of Months 0.116283E+10 0.22 612.92   0.31



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.165503E+09 0.50 806.14 01-JAN-16:02 0.66
February 0.148239E+09 0.51 806.14 01-FEB-09:01 0.66
March 0.181015E+09 0.53 806.14 01-MAR-09:01 0.66
April 0.310336E+09 0.58 806.14 01-APR-15:01 0.66
May 0.452199E+09 0.61 806.14 01-MAY-15:01 0.67
June 0.560091E+09 0.63 806.14 01-JUN-08:61 0.66
July 0.550914E+09 0.63 806.14 01-JUL-08:62 0.66
August 0.523339E+09 0.62 806.14 01-AUG-08:61 0.66
September 0.479059E+09 0.62 806.14 01-SEP-08:62 0.66
October 0.334101E+09 0.58 806.14 01-OCT-08:62 0.66
November 0.191278E+09 0.54 806.14 02-NOV-15:02 0.66
December 0.174495E+09 0.49 806.14 01-DEC-16:01 0.66
           
Annual Sum or Average 0.407057E+10 0.57      
Minimum of Months 0.148239E+09 0.49 806.14   0.66
Maximum of Months 0.560091E+09 0.63 806.14   0.67



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.189970E+09 0.47 800.01 01-JAN-16:02 0.66
February 0.143895E+09 0.48 800.01 01-FEB-09:01 0.66
March 0.148275E+09 0.49 800.01 01-MAR-09:01 0.66
April 0.271593E+09 0.55 800.01 01-APR-15:01 0.66
May 0.441908E+09 0.60 800.01 01-MAY-15:01 0.67
June 0.566301E+09 0.63 800.01 01-JUN-08:61 0.66
July 0.549087E+09 0.63 800.01 01-JUL-08:62 0.66
August 0.491751E+09 0.61 800.01 01-AUG-08:61 0.66
September 0.401854E+09 0.60 800.01 01-SEP-08:62 0.66
October 0.232173E+09 0.53 800.01 01-OCT-08:62 0.66
November 0.142048E+09 0.49 800.01 02-NOV-15:02 0.66
December 0.220033E+09 0.48 800.01 01-DEC-09:02 0.66
           
Annual Sum or Average 0.379889E+10 0.55      
Minimum of Months 0.142048E+09 0.47 800.01   0.66
Maximum of Months 0.566301E+09 0.63 800.01   0.67



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.681260E+09 0.26 1954.34 12-JAN-14:30 0.66
February 0.621786E+09 0.27 1462.97 07-FEB-13:40 0.67
March 0.457031E+09 0.24 1122.33 16-MAR-13:30 0.67
April 0.771044E+09 0.39 1047.12 04-APR-13:30 0.67
May 0.102602E+10 0.50 998.41 19-MAY-20:10 0.66
June 0.145223E+10 0.62 1094.54 08-JUN-17:12 0.66
July 0.152923E+10 0.64 1102.79 26-JUL-17:20 0.66
August 0.156097E+10 0.61 1239.02 27-AUG-13:40 0.66
September 0.177638E+10 0.62 2242.15 17-SEP-13:40 0.66
October 0.165783E+10 0.50 2636.61 29-OCT-12:30 0.66
November 0.117216E+10 0.34 2079.44 10-NOV-13:20 0.66
December 0.525533E+09 0.23 1396.44 16-DEC-14:10 0.67
           
Annual Sum or Average 0.132315E+11 0.43      
Minimum of Months 0.457031E+09 0.23 998.41   0.66
Maximum of Months 0.177638E+10 0.64 2636.61   0.67



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.831092E+09 0.47 4879.01 02-JAN-09:01 0.66
February 0.666360E+09 0.47 4879.01 01-FEB-09:01 0.66
March 0.763948E+09 0.47 4879.01 01-MAR-16:01 0.67
April 0.147878E+10 0.47 4879.01 01-APR-08:62 0.67
May 0.250865E+10 0.48 4879.01 01-MAY-15:01 0.67
June 0.327061E+10 0.53 4879.01 01-JUN-08:61 0.66
July 0.329982E+10 0.52 4879.01 01-JUL-08:62 0.66
August 0.281720E+10 0.50 4879.01 01-AUG-08:61 0.66
September 0.211957E+10 0.47 4879.01 01-SEP-08:62 0.66
October 0.134171E+10 0.47 4879.01 01-OCT-08:62 0.66
November 0.677109E+09 0.47 4879.01 08-NOV-19:01 0.66
December 0.989103E+09 0.47 4879.01 01-DEC-16:01 0.67
           
Annual Sum or Average 0.207640E+11 0.48      
Minimum of Months 0.666360E+09 0.47 4879.01   0.66
Maximum of Months 0.329982E+10 0.53 4879.01   0.67



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.152169E+09 0.48 702.52 01-JAN-16:02 0.66
February 0.144851E+09 0.52 702.52 03-FEB-16:01 0.67
March 0.176808E+09 0.55 702.52 01-MAR-09:01 0.66
April 0.322023E+09 0.62 702.52 01-APR-08:62 0.66
May 0.462263E+09 0.64 702.52 01-MAY-08:62 0.67
June 0.577343E+09 0.65 702.52 01-JUN-08:61 0.66
July 0.569633E+09 0.64 702.52 01-JUL-08:62 0.66
August 0.530518E+09 0.64 702.52 01-AUG-08:61 0.66
September 0.481739E+09 0.64 702.52 01-SEP-08:62 0.66
October 0.314820E+09 0.59 702.52 01-OCT-08:62 0.66
November 0.182810E+09 0.56 702.52 02-NOV-15:02 0.66
December 0.161603E+09 0.47 702.52 01-DEC-09:02 0.66
           
Annual Sum or Average 0.407658E+10 0.58      
Minimum of Months 0.144851E+09 0.47 702.52   0.66
Maximum of Months 0.577343E+09 0.65 702.52   0.67



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.171676E+09 0.47 696.83 05-JAN-16:01 0.67
February 0.127355E+09 0.47 696.83 01-FEB-16:02 0.67
March 0.136740E+09 0.47 696.83 01-MAR-16:01 0.67
April 0.278741E+09 0.59 696.83 01-APR-08:62 0.66
May 0.452523E+09 0.64 696.83 01-MAY-08:62 0.67
June 0.582980E+09 0.65 696.83 01-JUN-08:61 0.66
July 0.568413E+09 0.64 696.83 01-JUL-08:62 0.66
August 0.500896E+09 0.63 696.83 01-AUG-08:61 0.66
September 0.399832E+09 0.63 696.83 01-SEP-08:62 0.66
October 0.207256E+09 0.53 696.83 01-OCT-08:62 0.66
November 0.129944E+09 0.47 696.83 03-NOV-08:62 0.66
December 0.197138E+09 0.48 696.83 02-DEC-16:01 0.67
           
Annual Sum or Average 0.375349E+10 0.56      
Minimum of Months 0.127355E+09 0.47 696.83   0.66
Maximum of Months 0.582980E+09 0.65 696.83   0.67



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 53361073.07 0.50 214.40 01-JAN-16:02 0.66
February 45611969.03 0.51 214.40 01-FEB-09:01 0.66
March 49595419.05 0.52 214.40 01-MAR-09:01 0.66
April 74401069.33 0.58 214.40 01-APR-15:01 0.66
May 0.110663E+09 0.61 214.40 01-MAY-15:01 0.67
June 0.145772E+09 0.63 214.40 01-JUN-08:61 0.66
July 0.143378E+09 0.62 214.40 01-JUL-08:62 0.66
August 0.133104E+09 0.62 214.40 01-AUG-08:61 0.66
September 0.117858E+09 0.61 214.40 01-SEP-08:62 0.66
October 75554380.00 0.57 214.40 01-OCT-08:62 0.66
November 50895255.91 0.54 214.40 02-NOV-08:62 0.66
December 57631266.88 0.49 214.40 02-DEC-09:02 0.66
           
Annual Sum or Average 0.105783E+10 0.57      
Minimum of Months 45611969.03 0.49 214.40   0.66
Maximum of Months 0.145772E+09 0.63 214.40   0.67



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 63458911.31 0.50 212.49 01-JAN-09:02 0.66
February 47850289.74 0.48 212.49 01-FEB-09:01 0.66
March 44324421.07 0.48 212.49 01-MAR-09:01 0.66
April 64748214.52 0.55 212.49 01-APR-15:01 0.66
May 0.108127E+09 0.60 212.49 01-MAY-15:01 0.67
June 0.147304E+09 0.63 212.49 01-JUN-08:61 0.66
July 0.143110E+09 0.63 212.49 01-JUL-08:62 0.66
August 0.124907E+09 0.61 212.49 01-AUG-08:61 0.66
September 97469965.77 0.60 212.49 01-SEP-08:62 0.66
October 51841072.63 0.52 212.49 01-OCT-15:02 0.66
November 46946955.52 0.49 212.49 02-NOV-08:62 0.66
December 72040824.60 0.51 212.49 01-DEC-09:02 0.66
           
Annual Sum or Average 0.101213E+10 0.55      
Minimum of Months 44324421.07 0.48 212.49   0.66
Maximum of Months 0.147304E+09 0.63 212.49   0.67



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.316855E+09 0.57 941.53 01-JAN-16:02 0.66
February 0.287819E+09 0.57 941.53 01-FEB-16:02 0.67
March 0.276185E+09 0.56 941.53 01-MAR-16:01 0.67
April 0.364705E+09 0.59 941.53 01-APR-15:01 0.66
May 0.467782E+09 0.60 941.53 01-MAY-15:01 0.67
June 0.606893E+09 0.62 941.53 01-JUN-08:61 0.66
July 0.630030E+09 0.61 941.53 01-JUL-08:62 0.66
August 0.630223E+09 0.61 941.53 01-AUG-08:61 0.66
September 0.661254E+09 0.62 941.53 01-SEP-08:62 0.66
October 0.567603E+09 0.60 941.53 01-OCT-08:62 0.66
November 0.407948E+09 0.58 941.53 02-NOV-15:02 0.66
December 0.313715E+09 0.56 941.53 01-DEC-09:02 0.66
           
Annual Sum or Average 0.553101E+10 0.59      
Minimum of Months 0.276185E+09 0.56 941.53   0.66
Maximum of Months 0.661254E+09 0.62 941.53   0.67



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.410068E+09 0.369062E+09 695.75 09-JAN-09:01 626.18 626.18 56.45 1.16
February 0.249937E+09 0.224943E+09 646.47 16-FEB-00:13 581.82 581.82 48.35 1.01
March 0.166167E+09 0.149550E+09 594.79 05-MAR-04:33 535.31 535.31 54.53 0.87
April 37937027.69 34143324.92 609.79 13-APR-04:53 548.81 548.81 47.23 0.91
May 2525310.50 2272779.45 351.57 02-MAY-18:04 316.41 316.41 35.51 0.43
June 558713.40 502842.06 262.29 30-JUN-08:04 236.06 236.06 61.94 0.30
July 612388.47 551149.62 251.77 05-JUL-08:05 226.59 226.59 61.18 0.29
August 726291.35 653662.21 368.33 24-AUG-08:04 331.50 331.50 60.05 0.45
September 3033619.56 2730257.61 318.27 21-SEP-08:04 286.44 286.44 58.96 0.38
October 20532065.36 18478858.82 505.73 25-OCT-03:10 455.15 455.15 64.30 0.68
November 0.233943E+09 0.210549E+09 649.65 26-NOV-23:25 584.68 584.68 49.70 1.02
December 0.443344E+09 0.399010E+09 636.07 14-DEC-24:00 572.46 572.46 48.21 0.98
                 
Annual Sum or Average 0.156938E+10 0.141245E+10            
Minimum of Months 558713.40 502842.06 251.77   226.59 226.59 35.51 0.29
Maximum of Months 0.443344E+09 0.399010E+09 695.75   626.18 626.18 64.30 1.16



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.108575E+10 0.977172E+09 3128.96 12-JAN-16:03 2816.07 2816.07 7.92 6.78
February 0.165626E+10 0.149064E+10 3752.28 20-FEB-16:01 3377.05 3377.05 7.25 9.48
March 0.251442E+10 0.226298E+10 3807.62 14-MAR-18:01 3426.85 3426.85 7.26 9.79
April 0.549792E+10 0.494813E+10 4397.79 28-APR-18:03 3958.01 3958.01 6.73 15.09
May 0.799454E+10 0.719508E+10 4498.39 19-MAY-18:05 4048.55 4048.55 6.73 16.69
June 0.935289E+10 0.841760E+10 4632.79 05-JUN-18:03 4169.51 4169.51 6.73 18.94
July 0.103500E+11 0.931503E+10 4639.84 18-JUL-20:50 4175.85 4175.85 7.59 19.05
August 0.984386E+10 0.885947E+10 4597.38 01-AUG-21:00 4137.64 4137.64 7.38 18.37
September 0.883920E+10 0.795528E+10 4558.93 18-SEP-19:10 4103.04 4103.04 6.73 17.73
October 0.601657E+10 0.541491E+10 4497.73 03-OCT-20:00 4047.96 4047.96 7.24 16.68
November 0.239202E+10 0.215282E+10 4194.29 03-NOV-15:50 3774.86 3774.86 7.17 12.65
December 0.851704E+09 0.766533E+09 2426.68 16-DEC-16:03 2184.01 2184.01 8.40 4.67
                 
Annual Sum or Average 0.663952E+11 0.597557E+11            
Minimum of Months 0.851704E+09 0.766533E+09 2426.68   2184.01 2184.01 6.73 4.67
Maximum of Months 0.103500E+11 0.931503E+10 4639.84   4175.85 4175.85 8.40 19.05



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.683248E+10 0.614924E+10 3950.69 01-JAN-00:05 3555.62 3555.62 8.41 27.69
February 0.720496E+10 0.648446E+10 3950.69 01-FEB-04:10 3555.62 3555.62 8.40 27.69
March 0.865409E+10 0.778868E+10 3950.69 01-MAR-04:10 3555.62 3555.62 8.40 27.69
April 0.100289E+11 0.902601E+10 3950.69 01-APR-00:10 3555.62 3555.62 8.43 27.69
May 0.105754E+11 0.951783E+10 3950.69 01-MAY-00:10 3555.62 3555.62 8.85 27.69
June 0.102402E+11 0.921617E+10 3950.69 01-JUN-00:10 3555.62 3555.62 8.99 27.69
July 0.105815E+11 0.952337E+10 3950.69 01-JUL-00:10 3555.62 3555.62 8.94 27.69
August 0.105815E+11 0.952337E+10 3950.69 01-AUG-00:10 3555.62 3555.62 9.29 27.69
September 0.102402E+11 0.921617E+10 3950.69 01-SEP-00:10 3555.62 3555.62 9.11 27.69
October 0.104626E+11 0.941635E+10 3950.69 01-OCT-00:10 3555.62 3555.62 8.79 27.69
November 0.787238E+10 0.708514E+10 3950.69 01-NOV-00:10 3555.62 3555.62 8.47 27.69
December 0.666235E+10 0.599611E+10 3950.69 01-DEC-04:33 3555.62 3555.62 8.42 27.69
                 
Annual Sum or Average 0.109937E+12 0.989429E+11            
Minimum of Months 0.666235E+10 0.599611E+10 3950.69   3555.62 3555.62 8.40 27.69
Maximum of Months 0.105815E+11 0.952337E+10 3950.69   3555.62 3555.62 9.29 27.69



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:05 14.37 14.37 34.18 0.08
February 0.115896E+09 34768898.54 47.91 01-FEB-00:05 14.37 14.37 49.49 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:10 14.37 14.37 50.01 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 52.72 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:10 14.37 14.37 53.52 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:10 14.37 14.37 53.43 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 53.52 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:10 14.37 14.37 53.87 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:10 14.37 14.37 54.38 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 53.17 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:10 14.37 14.37 52.89 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:05 14.37 14.37 50.07 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 34.18 0.08
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 54.38 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 53.47 79.95 18050.00 207629.42 17-JAN-09:01
February 0.00 0.00 01-FEB-00:05 45.95 80.00 11786.58 149433.58 17-FEB-09:01
March 0.00 0.00 01-MAR-00:10 52.43 79.85 6879.71 121670.79 31-MAR-04:00
April 0.00 0.00 01-APR-00:10 52.02 79.40 2210.61 126183.98 13-APR-04:53
May 0.00 0.00 01-MAY-00:10 47.26 47.26 153.75 78417.52 02-MAY-18:04
June 0.00 0.00 01-JUN-00:10 55.55 55.55 18.72 23758.49 01-JUN-08:04
July 0.00 0.00 01-JUL-00:10 61.66 61.66 17.03 21751.99 05-JUL-08:05
August 0.00 0.00 01-AUG-00:10 62.77 62.77 21.74 36268.08 24-AUG-08:04
September 0.00 0.00 01-SEP-00:10 60.59 60.59 197.94 46455.89 25-SEP-05:10
October 0.00 0.00 01-OCT-00:10 52.80 52.80 1033.12 79268.89 25-OCT-05:10
November 0.00 0.00 01-NOV-00:10 64.30 79.40 10364.14 151510.14 26-NOV-16:01
December 0.00 0.00 01-DEC-00:05 64.92 79.58 19119.25 158292.18 02-DEC-19:05
                 
Annual Sum or Average 0.00         5800.76    
Minimum of Months 0.00 0.00   45.95 47.26 17.03 21751.99  
Maximum of Months 0.00 0.00   64.92 80.00 19119.25 207629.42  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 13096.28 191318.58 03-JAN-16:03 9.34 7.69 0.00 0.00 01-JAN-00:05
February 29542.23 312525.30 20-FEB-16:01 9.93 7.24 0.00 0.00 01-FEB-00:05
March 44922.07 357836.17 14-MAR-18:01 10.35 7.27 0.00 0.00 01-MAR-00:10
April 128342.83 432476.62 19-APR-18:03 10.43 6.70 0.00 0.00 01-APR-00:10
May 202109.21 446198.98 15-MAY-18:03 10.55 6.70 0.00 0.00 01-MAY-00:10
June 270306.07 526157.01 18-JUN-18:02 11.24 6.70 0.00 0.00 01-JUN-00:10
July 335066.90 629435.00 18-JUL-20:50 13.01 7.58 0.00 0.00 01-JUL-00:10
August 280392.31 594876.37 01-AUG-20:50 12.34 7.21 0.00 0.00 01-AUG-00:10
September 243483.05 510544.37 22-SEP-08:61 11.64 7.24 0.00 0.00 01-SEP-00:10
October 128038.85 532061.36 03-OCT-20:00 11.80 7.21 0.00 0.00 01-OCT-00:10
November 38324.10 334455.76 09-NOV-16:01 10.11 7.22 0.00 0.00 01-NOV-00:10
December 10057.67 96231.98 23-DEC-15:00 8.79 7.96 0.00 0.00 01-DEC-00:05
                 
Annual Sum or Average 144287.80         0.00    
Minimum of Months 10057.67 96231.98   8.79 6.70 0.00 0.00  
Maximum of Months 335066.90 629435.00   13.01 7.96 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 34.18 59.85 25402.54 63640.46 25-JAN-07:01
February 0.00 0.00 01-FEB-00:05 49.49 59.75 25416.60 62862.44 24-FEB-07:51
March 0.00 0.00 01-MAR-00:10 50.01 58.74 24577.96 56141.27 13-MAR-06:25
April 0.00 0.00 01-APR-00:10 52.72 58.99 23041.97 52370.67 13-APR-06:24
May 0.00 0.00 01-MAY-00:10 53.52 59.64 21279.74 44499.86 01-MAY-06:10
June 0.00 0.00 01-JUN-00:10 53.43 58.61 19745.25 40781.93 01-JUN-07:00
July 0.00 0.00 01-JUL-00:10 53.52 58.33 18838.55 38088.58 03-JUL-06:30
August 0.00 0.00 01-AUG-00:10 53.87 58.56 18864.24 38237.03 31-AUG-06:40
September 0.00 0.00 01-SEP-00:10 54.38 59.65 19752.80 43158.93 25-SEP-06:15
October 0.00 0.00 01-OCT-00:10 53.17 59.24 21280.51 49130.40 25-OCT-06:08
November 0.00 0.00 01-NOV-00:10 52.89 58.69 23022.73 56909.33 21-NOV-07:31
December 0.00 0.00 01-DEC-00:05 50.07 58.32 24528.32 58382.95 10-DEC-08:11
                 
Annual Sum or Average 0.00         22127.33    
Minimum of Months 0.00 0.00   34.18 58.32 18838.55 38088.58  
Maximum of Months 0.00 0.00   54.38 59.85 25416.60 63640.46  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.276199E+11 0.00 0.716861E+10 0.373875E+11 0.00 0.00
February 0.160916E+11 0.00 0.347043E+11 0.329253E+11 0.00 0.00
March 0.122058E+11 0.00 0.702420E+11 0.366613E+11 0.00 0.00
April 0.507475E+10 0.00 0.215062E+12 0.376419E+11 0.00 0.00
May 0.313832E+09 0.00 0.357119E+12 0.419622E+11 0.00 0.00
June 0.00 0.00 0.463005E+12 0.445456E+11 0.00 0.00
July 0.00 0.00 0.618069E+12 0.467919E+11 0.00 0.00
August 218560.25 0.00 0.504514E+12 0.475880E+11 0.00 0.00
September 0.448287E+09 0.00 0.412748E+12 0.455316E+11 0.00 0.00
October 0.243020E+10 0.00 0.204981E+12 0.433921E+11 0.00 0.00
November 0.170586E+11 0.00 0.433069E+11 0.391589E+11 0.00 0.00
December 0.235573E+11 0.00 0.436754E+10 0.383637E+11 0.00 0.00
             
Annual Sum or Average 0.104800E+12 0.00 0.293529E+13 0.491950E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.436754E+10 0.329253E+11 0.00 0.00
Maximum of Months 0.276199E+11 0.00 0.618069E+12 0.475880E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 48888398.20 0.00 0.122870E+10 0.587890E+10 0.00 0.00
February 71253799.96 0.00 0.618797E+10 0.530997E+10 0.00 0.00
March 34408146.74 0.00 0.122343E+11 0.587890E+10 0.00 0.00
April 33259.54 0.00 0.348126E+11 0.568926E+10 0.00 0.00
May 48666.88 0.00 0.557264E+11 0.587890E+10 0.00 0.00
June 50726.14 0.00 0.679277E+11 0.568926E+10 0.00 0.00
July 15400.64 0.00 0.903037E+11 0.587890E+10 0.00 0.00
August 31376.35 0.00 0.760520E+11 0.587890E+10 0.00 0.00
September 20445.35 0.00 0.649768E+11 0.568926E+10 0.00 0.00
October 29792.77 0.00 0.332051E+11 0.587890E+10 0.00 0.00
November 4826319.49 0.00 0.750498E+10 0.568926E+10 0.00 0.00
December 0.205105E+09 0.00 0.724517E+09 0.587890E+10 0.00 0.00
             
Annual Sum or Average 0.364712E+09 0.00 0.450885E+12 0.692193E+11 0.00 0.00
Minimum of Months 15400.64 0.00 0.724517E+09 0.530997E+10 0.00 0.00
Maximum of Months 0.205105E+09 0.00 0.903037E+11 0.587890E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.373875E+11 0.716957E+10 0.276199E+11 0.187478E+12 0.00 0.00 0.00 0.00
February 0.329253E+11 0.347046E+11 0.160916E+11 0.141144E+12 0.00 0.00 0.00 0.00
March 0.366613E+11 0.702429E+11 0.122058E+11 0.109662E+12 0.00 0.00 0.00 0.00
April 0.376419E+11 0.215062E+12 0.507475E+10 0.275858E+11 0.399386E+10 0.00 0.00 0.00
May 0.419622E+11 0.357119E+12 0.313832E+09 0.192558E+11 0.177776E+11 0.00 0.00 0.00
June 0.445456E+11 0.463005E+12 0.00 0.218571E+11 0.440077E+11 0.00 0.00 0.00
July 0.467919E+11 0.618069E+12 0.00 0.910899E+10 0.775526E+11 0.00 0.00 0.00
August 0.475880E+11 0.504514E+12 218560.25 0.110843E+11 0.375240E+11 0.00 0.00 0.00
September 0.455316E+11 0.412748E+12 0.448287E+09 0.729694E+10 0.212880E+11 0.00 0.00 0.00
October 0.433921E+11 0.204981E+12 0.243020E+10 0.160286E+11 0.367142E+10 0.00 0.00 0.00
November 0.391589E+11 0.433080E+11 0.170586E+11 0.108101E+12 0.00 0.00 0.00 0.00
December 0.383637E+11 0.436754E+10 0.235573E+11 0.238882E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.491950E+12 0.293529E+13 0.104800E+12 0.897485E+12 0.205815E+12 0.00 0.00 0.00
Minimum of Months 0.329253E+11 0.436754E+10 0.00 0.729694E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.475880E+11 0.618069E+12 0.276199E+11 0.238882E+12 0.775526E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.587890E+10 0.122870E+10 48888398.20 0.456477E+11 0.00 0.00 0.00 0.00
February 0.530997E+10 0.618797E+10 71253799.96 0.319895E+11 0.00 0.00 0.00 0.00
March 0.587890E+10 0.122343E+11 34408146.74 0.251290E+11 37001735.09 0.00 0.00 0.00
April 0.568926E+10 0.348126E+11 33259.54 0.663288E+10 0.249123E+10 0.00 0.00 0.00
May 0.587890E+10 0.557264E+11 48666.88 0.170914E+10 0.941032E+10 0.00 0.00 0.00
June 0.568926E+10 0.679277E+11 50726.14 0.428313E+09 0.200745E+11 0.00 0.00 0.00
July 0.587890E+10 0.903037E+11 15400.64 0.00 0.416160E+11 0.00 0.00 0.00
August 0.587890E+10 0.760520E+11 31376.35 0.106620E+09 0.259490E+11 0.00 0.00 0.00
September 0.568926E+10 0.649768E+11 20445.35 0.943559E+09 0.154394E+11 0.00 0.00 0.00
October 0.587890E+10 0.332051E+11 29792.77 0.528014E+10 0.383007E+10 0.00 0.00 0.00
November 0.568926E+10 0.750498E+10 4826319.49 0.293229E+11 36576506.12 0.00 0.00 0.00
December 0.587890E+10 0.724517E+09 0.205105E+09 0.539185E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.692193E+11 0.450885E+12 0.364712E+09 0.201108E+12 0.118884E+12 0.00 0.00 0.00
Minimum of Months 0.530997E+10 0.724517E+09 15400.64 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.903037E+11 0.205105E+09 0.539185E+11 0.416160E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.373875E+11 0.276199E+11 0.716861E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.329253E+11 0.160916E+11 0.347043E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.366613E+11 0.122058E+11 0.702420E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.376419E+11 0.507475E+10 0.215062E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.419622E+11 0.313832E+09 0.357119E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.445456E+11 0.00 0.463005E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.467919E+11 0.00 0.618069E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.475880E+11 218560.25 0.504514E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.455316E+11 0.448287E+09 0.412748E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.433921E+11 0.243020E+10 0.204981E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.391589E+11 0.170586E+11 0.433069E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.383637E+11 0.235573E+11 0.436754E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.491950E+12 0.104800E+12 0.293529E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.329253E+11 0.00 0.436754E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.475880E+11 0.276199E+11 0.618069E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.587890E+10 48888398.20 0.122870E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.530997E+10 71253799.96 0.618797E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.587890E+10 34408146.74 0.122343E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.568926E+10 33259.54 0.348126E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.587890E+10 48666.88 0.557264E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.568926E+10 50726.14 0.679277E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.587890E+10 15400.64 0.903037E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.587890E+10 31376.35 0.760520E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.568926E+10 20445.35 0.649768E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.587890E+10 29792.77 0.332051E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.568926E+10 4826319.49 0.750498E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.587890E+10 0.205105E+09 0.724517E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.692193E+11 0.364712E+09 0.450885E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.530997E+10 15400.64 0.724517E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.205105E+09 0.903037E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.254338E+10 0.00 0.00 82082051.81 0.00 0.00 0.469358E+11 0.00 0.94
February 0.251113E+11 0.00 0.00 11869076.15 0.00 0.00 0.109644E+11 0.00 0.86
March 0.362358E+11 0.00 0.00 199738.27 0.00 0.00 0.395490E+09 0.00 0.87
April 0.242422E+11 0.00 0.00 716.20 76862464.00 0.00 37259397.14 0.00 0.87
May 0.140616E+11 0.00 0.00 1694057.24 0.450919E+09 0.00 0.113419E+10 0.00 0.83
June 0.555414E+10 54185277.25 0.00 6389537.65 0.132409E+10 0.00 0.231033E+10 0.00 0.78
July 55469267.97 0.651536E+10 0.00 18789985.58 0.501649E+09 0.00 0.229434E+10 0.00 0.85
August 16461.22 0.212915E+10 0.00 55791048.94 16362510.38 0.00 0.931049E+10 0.00 1.01
September 0.00 0.148897E+10 0.00 70461841.05 0.00 0.00 0.184624E+11 0.00 1.22
October 0.00 0.246584E+09 0.00 94602097.36 0.00 0.00 0.417752E+11 0.00 1.29
November 8308593.37 0.00 0.00 0.118019E+09 0.00 0.00 0.562900E+11 0.00 1.19
December 91044543.09 0.00 0.00 0.122570E+09 0.00 0.00 0.560685E+11 0.00 1.05
                   
Annual Sum or Average 0.107903E+12 0.104342E+11 0.00 0.582469E+09 0.236988E+10 0.00 0.245978E+12 0.00 0.98
Minimum of Months 0.00 0.00 0.00 716.20 0.00 0.00 37259397.14 0.00 0.78
Maximum of Months 0.362358E+11 0.651536E+10 0.00 0.122570E+09 0.132409E+10 0.00 0.562900E+11 0.00 1.29



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.294498E+10 0.00 0.00 2319214.50 0.00 57978865.80 0.134101E+10 0.00 1.56
February 0.239782E+10 0.00 0.00 2453451.54 0.00 20620574.79 0.118749E+10 0.00 1.67
March 0.242356E+10 0.00 0.00 2414110.95 0.00 25674015.99 0.109752E+10 0.00 1.62
April 0.117455E+10 13844696.72 0.00 4629208.92 0.00 0.00 0.120415E+10 0.00 1.75
May 0.352295E+09 72217135.75 0.00 5687779.54 0.00 0.00 0.120887E+10 0.00 1.82
June 3027127.31 0.242467E+09 0.00 5691730.30 0.00 0.00 0.897207E+09 0.00 2.00
July 1355969.77 0.896569E+09 0.00 2360837.33 1274480.19 0.00 0.252174E+09 0.00 1.99
August 37595925.28 0.297670E+09 0.00 5476602.40 195375.69 0.00 0.734476E+09 0.00 2.06
September 0.140144E+09 0.217884E+09 0.00 6152016.95 87442.74 0.00 0.119986E+10 0.00 2.28
October 0.104208E+10 39764616.27 0.00 6842254.76 0.00 0.00 0.204264E+10 0.00 2.22
November 0.209801E+10 0.00 0.00 4447091.78 0.00 39348895.12 0.213698E+10 0.00 1.88
December 0.289824E+10 0.00 0.00 2010175.72 0.00 0.232141E+09 0.106658E+10 0.00 1.49
                   
Annual Sum or Average 0.155137E+11 0.178042E+10 0.00 50484474.69 1557298.62 0.375764E+09 0.143690E+11 0.00 1.86
Minimum of Months 1355969.77 0.00 0.00 2010175.72 0.00 0.00 0.252174E+09 0.00 1.49
Maximum of Months 0.294498E+10 0.896569E+09 0.00 6842254.76 1274480.19 0.232141E+09 0.213698E+10 0.00 2.28



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.387675E+10 0.00 0.00 479877.30 0.00 0.00 0.686731E+09 0.00 1.37
February 0.292241E+10 0.00 0.00 659441.90 0.00 0.00 0.926408E+09 0.00 1.44
March 0.254221E+10 0.00 0.00 1137505.23 0.00 0.00 0.143124E+10 0.00 1.48
April 0.745705E+09 4527053.50 0.00 2951696.56 3725111.10 0.00 0.197909E+10 0.00 1.54
May 0.100394E+09 40653566.96 0.00 4854889.94 7829513.58 0.00 0.171029E+10 0.00 1.56
June 6656369.42 0.149718E+09 0.00 5008028.72 4399726.12 0.00 0.998086E+09 0.00 1.54
July 231371.06 0.723791E+09 0.00 2381699.95 33742031.79 0.00 0.274762E+09 0.00 1.51
August 18119699.66 0.208321E+09 0.00 4527746.63 8294546.36 0.00 0.836512E+09 0.00 1.55
September 26151831.88 0.129810E+09 0.00 4781765.89 6946809.80 0.00 0.144949E+10 0.00 1.63
October 0.653829E+09 20736229.70 0.00 3631439.21 1680235.77 0.00 0.250010E+10 0.00 1.60
November 0.254750E+10 0.00 0.00 1373573.00 0.00 0.00 0.163100E+10 0.00 1.43
December 0.403466E+10 0.00 0.00 202900.81 0.00 0.00 0.443930E+09 0.00 1.35
                   
Annual Sum or Average 0.174746E+11 0.127756E+10 0.00 31990565.13 66617974.52 0.00 0.148676E+11 0.00 1.50
Minimum of Months 231371.06 0.00 0.00 202900.81 0.00 0.00 0.274762E+09 0.00 1.35
Maximum of Months 0.403466E+10 0.723791E+09 0.00 5008028.72 33742031.79 0.00 0.250010E+10 0.00 1.63



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.293199E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.42
February 0.246273E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
March 0.246764E+10 0.00 0.00 35483.32 0.00 0.00 63349419.29 0.00 0.45
April 0.113803E+10 3172911.53 0.00 1304737.95 2136932.41 0.00 0.616264E+09 0.00 0.47
May 0.173303E+09 32901302.94 0.00 4708501.21 3018414.12 0.00 0.116540E+10 0.00 0.56
June 467512.55 0.146017E+09 0.00 5241501.35 6042.86 0.00 0.868053E+09 0.00 0.66
July 0.00 0.673587E+09 0.00 2230527.07 0.00 0.00 0.240906E+09 0.00 0.65
August 8325510.73 0.191487E+09 0.00 4475204.73 151543.69 0.00 0.674471E+09 0.00 0.62
September 57206677.91 0.106837E+09 0.00 4001778.33 86995.48 0.00 0.100234E+10 0.00 0.59
October 0.122824E+10 17028905.76 0.00 1611185.80 782779.48 0.00 0.801312E+09 0.00 0.50
November 0.256052E+10 0.00 0.00 68742.57 0.00 0.00 91704363.55 0.00 0.43
December 0.288030E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.41
                   
Annual Sum or Average 0.159088E+11 0.117103E+10 0.00 23677662.32 6182708.03 0.00 0.552379E+10 0.00 0.52
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.41
Maximum of Months 0.293199E+10 0.673587E+09 0.00 5241501.35 3018414.12 0.00 0.116540E+10 0.00 0.66



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.286759E+10 0.00 0.00 0.00 0.00 519961.91 0.00 0.00 0.70
February 0.240847E+10 0.00 0.00 0.00 0.00 606860.62 0.00 0.00 0.73
March 0.247546E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.75
April 0.164074E+10 0.00 0.00 0.00 5194155.67 0.00 0.00 0.00 0.75
May 0.101845E+10 0.00 0.00 10985.30 30471857.43 0.00 8543951.36 0.00 0.72
June 0.395636E+09 18813551.80 0.00 410979.13 74313337.62 0.00 0.135132E+09 0.00 0.68
July 0.100720E+09 48982724.72 0.00 198530.27 0.377779E+09 0.00 43417965.86 0.00 0.67
August 0.438136E+09 17244027.71 0.00 119021.03 0.104608E+09 0.00 30990828.61 0.00 0.69
September 0.811096E+09 520484.33 0.00 4842.45 80163620.76 0.00 1594101.80 0.00 0.73
October 0.186910E+10 0.00 0.00 0.00 12528102.25 0.00 0.00 0.00 0.77
November 0.258880E+10 0.00 0.00 0.00 0.00 915390.58 0.00 0.00 0.72
December 0.279139E+10 0.00 0.00 0.00 0.00 26160582.36 0.00 0.00 0.69
                   
Annual Sum or Average 0.194056E+11 85560788.57 0.00 744358.18 0.685058E+09 28202795.46 0.219679E+09 0.00 0.72
Minimum of Months 0.100720E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.67
Maximum of Months 0.286759E+10 48982724.72 0.00 410979.13 0.377779E+09 26160582.36 0.135132E+09 0.00 0.77



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 9763101.43 0.00 0.00 0.159029E+09 0.00 0.00 0.678745E+11 0.00 19.81
February 8689014.31 0.00 0.00 0.125851E+09 0.00 0.00 0.577973E+11 0.00 21.03
March 12179159.08 0.00 0.00 0.128808E+09 0.00 0.00 0.597175E+11 0.00 21.90
April 7398540.44 0.102062E+09 0.00 0.116698E+09 0.00 0.00 0.385239E+11 0.00 21.99
May 0.00 0.585258E+09 0.00 0.103111E+09 0.00 0.00 0.234124E+11 0.00 20.97
June 0.00 0.197812E+10 0.00 76785851.73 0.00 0.00 0.114477E+11 0.00 19.33
July 0.00 0.102534E+11 0.00 28770832.26 0.00 0.00 0.292302E+10 0.00 18.97
August 0.00 0.295424E+10 0.00 73292860.56 0.00 0.00 0.101506E+11 0.00 19.80
September 0.00 0.182168E+10 0.00 82003237.78 0.00 0.00 0.185992E+11 0.00 21.27
October 0.00 0.323676E+09 0.00 0.108601E+09 0.00 0.00 0.443503E+11 0.00 22.51
November 23943556.07 0.00 0.00 0.135568E+09 0.00 0.00 0.626174E+11 0.00 20.83
December 8921672.39 0.00 0.00 0.160751E+09 0.00 0.00 0.666830E+11 0.00 19.36
                   
Annual Sum or Average 70895043.72 0.180184E+11 0.00 0.129927E+10 0.00 0.00 0.464097E+12 0.00 20.64
Minimum of Months 0.00 0.00 0.00 28770832.26 0.00 0.00 0.292302E+10 0.00 18.97
Maximum of Months 23943556.07 0.102534E+11 0.00 0.160751E+09 0.00 0.00 0.678745E+11 0.00 22.51



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.161362E+11 0.00 0.00 10196493.34 0.00 0.00 0.175316E+11 0.00 4.17
February 0.121222E+11 0.00 0.00 10680006.73 0.00 0.00 0.161443E+11 0.00 4.36
March 0.117089E+11 0.00 0.00 10176936.77 0.00 0.00 0.172679E+11 0.00 4.45
April 0.578889E+10 59858973.49 0.00 14821933.94 958367.97 0.00 0.134319E+11 0.00 4.44
May 0.183587E+10 0.309425E+09 0.00 17394254.78 47363861.09 0.00 0.102222E+11 0.00 4.28
June 0.396267E+09 0.988337E+09 0.00 19110948.70 0.102288E+09 0.00 0.594102E+10 0.00 4.05
July 28451589.21 0.418183E+10 0.00 10972956.55 0.845164E+09 0.00 0.169784E+10 0.00 3.99
August 0.510820E+09 0.130264E+10 0.00 19136211.65 0.139001E+09 0.00 0.507216E+10 0.00 4.14
September 0.752890E+09 0.885673E+09 0.00 23161623.06 75485112.17 0.00 0.888810E+10 0.00 4.42
October 0.408899E+10 0.142292E+09 0.00 26974572.78 14037241.23 0.00 0.180005E+11 0.00 4.65
November 0.101267E+11 0.00 0.00 19854337.88 0.00 570800.73 0.204719E+11 0.00 4.36
December 0.184157E+11 0.00 0.00 7748977.42 0.00 702043.71 0.146317E+11 0.00 4.09
                   
Annual Sum or Average 0.819118E+11 0.787006E+10 0.00 0.190229E+09 0.122430E+10 1272844.45 0.149301E+12 0.00 4.28
Minimum of Months 28451589.21 0.00 0.00 7748977.42 0.00 0.00 0.169784E+10 0.00 3.99
Maximum of Months 0.184157E+11 0.418183E+10 0.00 26974572.78 0.845164E+09 702043.71 0.204719E+11 0.00 4.65



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.517363E+11 0.00 0.00 33178458.00 0.00 0.00 0.429921E+11 0.00 1.70
February 0.357320E+11 0.00 0.00 36165523.57 0.00 0.00 0.442005E+11 0.00 1.78
March 0.328140E+11 0.00 0.00 43261411.12 0.00 0.00 0.495388E+11 0.00 1.83
April 0.116304E+11 0.121475E+09 0.00 67958575.83 48728484.43 0.00 0.451213E+11 0.00 1.89
May 0.254606E+10 0.758389E+09 0.00 86002204.66 0.240311E+09 0.00 0.352895E+11 0.00 1.90
June 0.350325E+09 0.284429E+10 0.00 87729590.01 0.254512E+09 0.00 0.207266E+11 0.00 1.85
July 15491195.98 0.139492E+11 0.00 46605286.81 0.139684E+10 0.00 0.583230E+10 0.00 1.82
August 0.558933E+09 0.404793E+10 0.00 82764297.39 0.313733E+09 0.00 0.176362E+11 0.00 1.88
September 0.610864E+09 0.258052E+10 0.00 90877340.63 0.193705E+09 0.00 0.303810E+11 0.00 1.98
October 0.806232E+10 0.424141E+09 0.00 93756521.60 24201767.26 0.00 0.581922E+11 0.00 1.98
November 0.252510E+11 0.00 0.00 59144498.16 0.00 0.00 0.618914E+11 0.00 1.78
December 0.578780E+11 0.00 0.00 23763902.12 0.00 0.00 0.347634E+11 0.00 1.66
                   
Annual Sum or Average 0.227186E+12 0.247260E+11 0.00 0.751208E+09 0.247203E+10 0.00 0.446565E+12 0.00 1.84
Minimum of Months 15491195.98 0.00 0.00 23763902.12 0.00 0.00 0.583230E+10 0.00 1.66
Maximum of Months 0.578780E+11 0.139492E+11 0.00 93756521.60 0.139684E+10 0.00 0.618914E+11 0.00 1.98



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.371703E+09 0.00 0.00 2972234.47 0.00 0.751799E+09 0.433723E+09 0.00 0.47
February 0.290662E+09 0.00 0.00 3816912.27 0.00 0.494340E+09 0.521240E+09 0.00 0.47
March 0.258402E+09 44307.74 0.00 6529413.88 0.00 0.341251E+09 0.725134E+09 0.00 0.47
April 0.107736E+09 15323151.95 6017.82 10020518.28 667074.12 40144836.03 0.649140E+09 1728.45 0.47
May 28838921.36 83960235.59 11368.89 8314545.56 4406113.28 346663.61 0.368705E+09 12390.02 0.47
June 2243382.32 0.179169E+09 61982.91 4149433.52 7765546.63 22047.27 75911469.04 24063.60 0.47
July 0.00 0.764838E+09 518583.67 24296.83 37152532.10 0.00 126824.83 38716.06 0.47
August 2795379.25 0.384412E+09 247259.69 1689660.04 22112929.38 50038.85 33582252.19 35799.78 0.47
September 15711090.49 0.353371E+09 222467.20 4942835.51 17420831.77 199482.35 0.208722E+09 30001.39 0.48
October 0.111065E+09 71321501.98 70104.92 9692884.88 4042287.10 2128827.36 0.750921E+09 3098.04 0.47
November 0.240907E+09 614842.14 0.00 6586203.14 0.00 0.386325E+09 0.752923E+09 0.00 0.47
December 0.386277E+09 0.00 0.00 2127473.72 0.00 0.835520E+09 0.338819E+09 0.00 0.47
                   
Annual Sum or Average 0.181634E+10 0.185305E+10 1137785.09 60866412.09 93567314.38 0.285213E+10 0.485895E+10 145797.33 0.47
Minimum of Months 0.00 0.00 0.00 24296.83 0.00 0.00 126824.83 0.00 0.47
Maximum of Months 0.386277E+09 0.764838E+09 518583.67 10020518.28 37152532.10 0.835520E+09 0.752923E+09 38716.06 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.431234E+09 0.00 0.00 819814.23 0.00 0.993856E+09 0.134104E+09 0.00 0.47
February 0.339736E+09 0.00 0.00 1539849.80 0.00 0.714021E+09 0.254608E+09 0.00 0.47
March 0.299652E+09 44152.10 0.00 4171048.77 0.00 0.484061E+09 0.543278E+09 150.44 0.47
April 0.119794E+09 14525029.84 6515.06 8884578.15 1462244.28 57605246.44 0.620662E+09 2308.76 0.47
May 30377289.01 83443990.08 12326.68 8178290.95 4912005.37 349733.90 0.367252E+09 11429.43 0.47
June 2176618.60 0.179234E+09 55538.84 4203952.31 7686814.64 22044.69 75914070.82 21568.21 0.47
July 0.00 0.765900E+09 504459.27 24946.06 36014045.97 0.00 126157.89 35449.29 0.47
August 2801356.86 0.381538E+09 245357.66 1625444.90 24939594.44 50032.99 33636029.57 37668.65 0.47
September 17865341.98 0.349015E+09 218513.80 4126724.39 21737724.88 305157.45 0.207251E+09 30463.32 0.48
October 0.151378E+09 64379351.97 82815.60 6587913.59 10959046.88 10174078.34 0.705565E+09 6939.05 0.47
November 0.317002E+09 444669.84 0.00 2774820.83 170100.27 0.615269E+09 0.451532E+09 0.00 0.47
December 0.425120E+09 0.00 0.00 448315.64 0.00 0.106723E+10 69765282.57 0.00 0.47
                   
Annual Sum or Average 0.213714E+10 0.183852E+10 1125526.92 43385699.63 0.107882E+09 0.394294E+10 0.346369E+10 145977.15 0.47
Minimum of Months 0.00 0.00 0.00 24946.06 0.00 0.00 126157.89 0.00 0.47
Maximum of Months 0.431234E+09 0.765900E+09 504459.27 8884578.15 36014045.97 0.106723E+10 0.705565E+09 37668.65 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.120365E+11 0.00 0.00 52305234.36 0.00 0.00 0.906603E+10 0.00 0.54
February 0.964700E+10 0.00 0.00 47271774.40 0.00 0.00 0.806895E+10 0.00 0.54
March 0.112459E+11 600773.22 0.00 36050919.81 0.00 0.00 0.676947E+10 0.00 0.54
April 0.528988E+10 0.216918E+09 0.00 46974087.44 0.00 0.00 0.560589E+10 0.00 0.54
May 0.180266E+10 0.119849E+10 0.00 35408690.02 0.00 0.00 0.366971E+10 0.00 0.54
June 0.111665E+09 0.253583E+10 0.00 20998994.92 0.00 0.00 0.983607E+09 0.00 0.54
July 721850.41 0.108818E+11 0.00 66571.86 0.00 0.00 1260651.88 0.00 0.54
August 58828609.09 0.550898E+10 0.00 8502667.21 6975392.05 0.00 0.449506E+09 0.00 0.54
September 0.284351E+09 0.502632E+10 0.00 31676441.26 4718165.86 0.00 0.279681E+10 0.00 0.54
October 0.287380E+10 0.102286E+10 0.00 76437073.92 0.00 0.00 0.889781E+10 0.00 0.54
November 0.826974E+10 8336707.97 0.00 79009680.14 0.00 0.00 0.104542E+11 0.00 0.54
December 0.127726E+11 0.00 0.00 45147276.04 0.00 0.00 0.837164E+10 0.00 0.53
                   
Annual Sum or Average 0.643937E+11 0.264002E+11 0.00 0.479849E+09 11693557.91 0.00 0.651349E+11 0.00 0.54
Minimum of Months 721850.41 0.00 0.00 66571.86 0.00 0.00 1260651.88 0.00 0.53
Maximum of Months 0.127726E+11 0.108818E+11 0.00 79009680.14 6975392.05 0.00 0.104542E+11 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.593868E+10 0.00 0.00 13015296.64 0.00 0.737877E+10 0.783018E+10 0.00 0.53
February 0.469959E+10 0.00 0.00 20234920.45 0.00 0.377195E+10 0.927631E+10 0.00 0.53
March 0.429882E+10 600937.50 0.00 39634606.62 0.00 0.114526E+10 0.125727E+11 0.00 0.54
April 0.195291E+10 0.101500E+09 680568.70 70646570.46 0.114647E+09 52200786.01 0.886998E+10 149685.36 0.54
May 0.485823E+09 0.797401E+09 2042992.15 66157757.88 0.399129E+09 1844509.25 0.495546E+10 245723.32 0.54
June 38834632.34 0.213856E+10 1476869.55 33915985.14 0.396436E+09 274946.45 0.104355E+10 45921.00 0.54
July 0.00 0.930467E+10 5153098.40 256623.69 0.157489E+10 0.00 1793010.77 84432.04 0.54
August 39013791.47 0.438256E+10 2498456.54 14541387.53 0.113223E+10 483050.51 0.462940E+09 168932.28 0.54
September 0.313859E+09 0.387096E+10 3763236.10 30561689.79 0.115746E+10 2771724.25 0.276650E+10 228340.74 0.54
October 0.227883E+10 0.641128E+09 1469885.51 51286241.85 0.380475E+09 29410764.88 0.949176E+10 64054.97 0.54
November 0.465934E+10 1226321.42 31834.41 24584179.58 7067994.99 0.303531E+10 0.110889E+11 12836.82 0.53
December 0.600414E+10 0.00 0.00 9263242.30 0.00 0.949471E+10 0.568707E+10 0.00 0.53
                   
Annual Sum or Average 0.307098E+11 0.212386E+11 17116941.36 0.374099E+09 0.516235E+10 0.249130E+11 0.740471E+11 999926.53 0.54
Minimum of Months 0.00 0.00 0.00 256623.69 0.00 0.00 1793010.77 0.00 0.53
Maximum of Months 0.600414E+10 0.930467E+10 5153098.40 70646570.46 0.157489E+10 0.949471E+10 0.125727E+11 245723.32 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.410740E+09 0.00 0.00 3039313.49 0.00 0.747148E+09 0.399269E+09 0.00 0.47
February 0.272545E+09 0.00 0.00 4985549.51 0.00 0.456661E+09 0.575867E+09 0.00 0.47
March 0.198434E+09 44157.28 0.00 7194108.11 0.00 0.330739E+09 0.794950E+09 150.46 0.47
April 55669842.67 15599499.26 8070.49 11814444.98 386696.43 35576987.44 0.703979E+09 3706.17 0.47
May 8543054.20 84951367.31 36405.04 9799150.24 3397012.90 58584.79 0.387804E+09 5322.52 0.47
June 1036898.91 0.182834E+09 12485.71 4730866.77 4173407.59 0.00 76558566.46 163.23 0.47
July 0.00 0.782201E+09 79495.72 31453.62 20266000.68 0.00 119668.04 664.12 0.47
August 1752573.56 0.394447E+09 99464.11 1922617.03 12255575.26 47115.50 34395024.24 6783.65 0.47
September 7353804.61 0.361891E+09 24372.92 5414932.98 9128931.81 21015.06 0.216786E+09 40.75 0.48
October 88114248.99 71849625.03 71570.53 9988612.65 3512583.77 10591697.08 0.765113E+09 3212.71 0.47
November 0.209804E+09 614842.14 0.00 7407191.72 0.00 0.408293E+09 0.761237E+09 0.00 0.47
December 0.432465E+09 0.00 0.00 2450088.19 0.00 0.807124E+09 0.320704E+09 0.00 0.47
                   
Annual Sum or Average 0.168646E+10 0.189443E+10 331864.52 68778329.29 53120208.43 0.279626E+10 0.503678E+10 20043.61 0.47
Minimum of Months 0.00 0.00 0.00 31453.62 0.00 0.00 119668.04 0.00 0.47
Maximum of Months 0.432465E+09 0.782201E+09 99464.11 11814444.98 20266000.68 0.807124E+09 0.794950E+09 6783.65 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.437814E+09 0.00 0.00 575189.08 0.00 0.986343E+09 0.135282E+09 0.00 0.47
February 0.343337E+09 0.00 0.00 2013663.16 0.00 0.632963E+09 0.331591E+09 0.00 0.47
March 0.305366E+09 44152.10 0.00 4367120.26 0.00 0.442520E+09 0.578908E+09 150.44 0.47
April 78267941.07 15496030.74 28708.52 10470362.90 460982.23 52943367.92 0.665265E+09 10376.45 0.47
May 9011087.65 84975625.49 45851.00 9653725.46 3352044.85 58980.10 0.387434E+09 6230.24 0.47
June 993915.07 0.182931E+09 0.00 4801625.89 4067261.19 0.00 76521145.46 0.00 0.47
July 0.00 0.782000E+09 88194.89 32014.75 20365066.07 0.00 119089.20 259.62 0.47
August 1752368.22 0.393069E+09 100788.41 1857362.40 13581794.54 47109.98 34456023.73 8770.47 0.47
September 9352253.69 0.359576E+09 73305.71 4504105.09 11350412.89 32298.21 0.215660E+09 1980.62 0.48
October 0.125451E+09 67785823.15 128819.61 6596010.14 7499552.65 21637593.97 0.720021E+09 13958.09 0.47
November 0.340681E+09 90275.58 2319.02 2777431.92 521069.49 0.588128E+09 0.454992E+09 1106.02 0.47
December 0.429259E+09 0.00 0.00 430665.81 0.00 0.103651E+10 96365047.78 0.00 0.47
                   
Annual Sum or Average 0.208128E+10 0.188597E+10 467987.15 48079276.85 61198183.90 0.376118E+10 0.369661E+10 42831.95 0.47
Minimum of Months 0.00 0.00 0.00 32014.75 0.00 0.00 119089.20 0.00 0.47
Maximum of Months 0.437814E+09 0.782000E+09 128819.61 10470362.90 20365066.07 0.103651E+10 0.720021E+09 13958.09 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.235399E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.46
February 0.197723E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.48
March 0.203171E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.49
April 0.124195E+11 11415476.67 0.00 2015021.29 31215217.46 0.00 0.106978E+10 0.00 0.49
May 0.270111E+10 0.221656E+09 0.00 18602478.48 38973163.35 0.00 0.615804E+10 0.00 0.51
June 95438171.51 0.921006E+09 0.00 26081540.59 8426167.42 0.00 0.494245E+10 0.00 0.53
July 3878865.33 0.380910E+10 0.00 12121251.43 0.180307E+09 0.00 0.138041E+10 0.00 0.52
August 0.484945E+09 0.113071E+10 0.00 21244716.44 46488147.95 0.00 0.374086E+10 0.00 0.52
September 0.111068E+10 0.702420E+09 0.00 21029917.15 30985488.86 0.00 0.604773E+10 0.00 0.54
October 0.115709E+11 0.106652E+09 0.00 6809158.42 14364388.88 0.00 0.388939E+10 0.00 0.51
November 0.212549E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.47
December 0.231243E+11 0.00 0.00 0.00 0.00 492106.53 0.00 0.00 0.45
                   
Annual Sum or Average 0.136395E+12 0.690295E+10 0.00 0.107904E+09 0.350759E+09 492106.53 0.272287E+11 0.00 0.50
Minimum of Months 3878865.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45
Maximum of Months 0.235399E+11 0.380910E+10 0.00 26081540.59 0.180307E+09 492106.53 0.615804E+10 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 94515804.08 0.00 0.00 558923.22 0.00 0.230485E+09 64489493.29 0.00 0.47
February 76289495.72 0.00 0.00 746970.30 0.00 0.174243E+09 76234962.53 0.00 0.47
March 67276183.15 11076.94 0.00 1336713.16 0.00 0.146168E+09 0.118048E+09 0.00 0.47
April 28579770.20 3828313.26 1617.36 2181217.60 169243.26 29146960.30 0.141852E+09 319.21 0.47
May 7596555.96 20941518.39 1477.48 1833553.83 1152296.94 650786.71 91470417.00 2234.13 0.47
June 596280.52 44863558.77 14582.15 962998.84 1871523.93 10479.96 19011823.71 5367.77 0.47
July 0.00 0.191003E+09 144418.59 4690.57 9477556.47 0.00 33089.84 12102.39 0.47
August 701783.62 95847592.22 70147.54 365929.18 5775323.59 10803.30 8450816.48 9040.37 0.47
September 3977523.56 87954098.37 47168.26 1074659.84 4753494.34 235798.78 52105863.04 6431.79 0.48
October 30895894.84 17695540.20 12308.17 1960505.42 1150432.26 24644987.74 0.160950E+09 967.38 0.47
November 62754138.69 153710.53 0.00 1232486.57 0.00 0.149853E+09 0.132845E+09 0.00 0.47
December 97726604.88 0.00 0.00 399015.30 0.00 0.246303E+09 46256928.31 0.00 0.47
                   
Annual Sum or Average 0.470910E+09 0.462298E+09 291719.56 12657663.83 24349870.81 0.100175E+10 0.911749E+09 36463.03 0.47
Minimum of Months 0.00 0.00 0.00 4690.57 0.00 0.00 33089.84 0.00 0.47
Maximum of Months 97726604.88 0.191003E+09 144418.59 2181217.60 9477556.47 0.246303E+09 0.160950E+09 12102.39 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 98018273.39 0.00 0.00 135936.10 0.00 0.275184E+09 16664771.01 0.00 0.47
February 82114793.60 0.00 0.00 279800.72 0.00 0.213269E+09 31813068.67 0.00 0.47
March 75555928.77 11038.03 36.15 812470.94 0.00 0.177738E+09 78683878.54 1.47 0.47
April 31302695.17 3661281.51 1523.62 1903572.63 335806.64 35868546.45 0.132662E+09 412.72 0.47
May 7805043.56 20852964.47 1323.42 1798925.03 1238262.25 1335221.32 90600225.37 2387.76 0.47
June 572148.53 44823813.32 14039.31 976653.90 1906411.83 6947.68 19023421.49 5290.13 0.47
July 0.00 0.191181E+09 142657.43 4805.74 9278076.99 0.00 32970.24 11501.32 0.47
August 707627.06 95130903.26 69632.57 350045.41 6480105.94 10802.04 8459741.57 9546.06 0.47
September 4546146.44 86921982.66 37585.28 866406.12 5784930.91 1727651.48 50246916.66 5825.58 0.48
October 38597287.40 16078424.92 23188.31 1211156.73 2752613.36 49596023.26 0.129022E+09 2811.78 0.47
November 78626836.19 99737.76 0.00 468648.07 53954.76 0.216168E+09 51380766.72 0.00 0.47
December 94612973.83 0.00 0.00 80197.40 0.00 0.287391E+09 8555724.42 0.00 0.47
                   
Annual Sum or Average 0.512460E+09 0.458761E+09 289986.08 8888618.80 27830162.68 0.125830E+10 0.617145E+09 37776.81 0.47
Minimum of Months 0.00 0.00 0.00 4805.74 0.00 0.00 32970.24 0.00 0.47
Maximum of Months 98018273.39 0.191181E+09 142657.43 1903572.63 9278076.99 0.287391E+09 0.132662E+09 11501.32 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.345913E+09 0.00 0.00 14423545.69 0.00 0.732011E+09 0.141352E+10 0.00 0.54
February 0.275896E+09 0.00 0.00 12830453.39 0.00 0.505693E+09 0.130970E+10 0.00 0.54
March 0.309035E+09 71163.65 0.00 11550383.46 0.00 0.411362E+09 0.140631E+10 0.00 0.54
April 0.157170E+09 24658448.15 11453.87 12208224.36 1022078.75 99243123.86 0.102758E+10 2719.93 0.54
May 46339265.86 0.131269E+09 76240.08 9480345.11 10595933.80 2997025.71 0.593599E+09 23750.55 0.54
June 4146745.59 0.283277E+09 130109.31 4907527.10 16917701.73 44640.55 0.123127E+09 52275.97 0.54
July 0.00 0.121230E+10 868820.03 28848.96 75753193.42 0.00 213870.91 62922.39 0.54
August 4508601.37 0.611800E+09 518756.49 2170087.84 41007767.01 83074.50 54459331.90 57748.53 0.54
September 25299628.23 0.568896E+09 254040.77 6844940.30 26770400.22 207385.98 0.336374E+09 22660.02 0.54
October 0.162605E+09 0.116580E+09 66642.37 16965541.83 4510138.96 2208183.89 0.122166E+10 4732.44 0.54
November 0.273557E+09 987511.69 0.00 18404035.81 0.00 0.426150E+09 0.150916E+10 0.00 0.53
December 0.348665E+09 0.00 0.00 14523613.12 0.00 0.836535E+09 0.131023E+10 0.00 0.53
                   
Annual Sum or Average 0.195314E+10 0.294984E+10 1926062.92 0.124338E+09 0.176577E+09 0.301653E+10 0.103059E+11 226809.83 0.54
Minimum of Months 0.00 0.00 0.00 28848.96 0.00 0.00 213870.91 0.00 0.53
Maximum of Months 0.348665E+09 0.121230E+10 868820.03 18404035.81 75753193.42 0.836535E+09 0.150916E+10 62922.39 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.207009E+11 0.00 0.00 31053505.84 0.00 0.00 0.385711E+11 0.00 5.43
February 0.120036E+11 0.00 0.00 30999709.95 0.00 0.00 0.378741E+11 0.00 5.68
March 0.844912E+10 0.00 0.00 39951322.92 0.00 0.00 0.430041E+11 0.00 5.84
April 0.173616E+10 0.105701E+09 0.00 53162231.18 1036378.49 0.00 0.330942E+11 0.00 5.95
May 0.324789E+09 0.605814E+09 0.00 59289718.19 20366040.84 0.00 0.221919E+11 0.00 5.85
June 71730827.81 0.189024E+10 0.00 53963891.73 30319067.40 0.00 0.120108E+11 0.00 5.57
July 2609342.84 0.899364E+10 0.00 26188793.26 0.216447E+09 0.00 0.328317E+10 0.00 5.47
August 89570082.91 0.254352E+10 0.00 48461827.92 73273938.42 0.00 0.103091E+11 0.00 5.63
September 0.266243E+09 0.159921E+10 0.00 46984933.64 86099586.03 0.00 0.172555E+11 0.00 5.87
October 0.172026E+10 0.248568E+09 0.00 48058005.03 14640195.65 0.00 0.375446E+11 0.00 6.01
November 0.116632E+11 0.00 0.00 35095602.07 0.00 0.00 0.419845E+11 0.00 5.60
December 0.206400E+11 0.00 0.00 27285160.85 0.00 0.00 0.374413E+11 0.00 5.32
                   
Annual Sum or Average 0.776682E+11 0.159867E+11 0.00 0.500495E+09 0.442183E+09 0.00 0.334564E+12 0.00 5.69
Minimum of Months 2609342.84 0.00 0.00 26188793.26 0.00 0.00 0.328317E+10 0.00 5.32
Maximum of Months 0.207009E+11 0.899364E+10 0.00 59289718.19 0.216447E+09 0.00 0.430041E+11 0.00 6.01



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.110819E+11 0.00 0.00 48190303.43 0.00 0.00 0.487581E+11 0.00 5.48
February 0.638001E+10 0.00 0.00 45518655.03 0.00 0.00 0.441364E+11 0.00 5.74
March 0.380641E+10 0.00 0.00 55687812.99 0.00 0.00 0.485176E+11 0.00 5.93
April 0.826980E+09 0.106731E+09 0.00 67652253.73 16840.61 0.00 0.350164E+11 0.00 6.10
May 0.156033E+09 0.621947E+09 0.00 70927555.72 4440929.61 0.00 0.232818E+11 0.00 6.03
June 13948576.73 0.192227E+10 0.00 61434217.11 13495325.91 0.00 0.125865E+11 0.00 5.75
July 188311.95 0.937081E+10 0.00 28497659.97 59229565.01 0.00 0.343609E+10 0.00 5.64
August 30371613.71 0.263004E+10 0.00 56229189.47 35982979.17 0.00 0.107936E+11 0.00 5.81
September 0.114106E+09 0.165471E+10 0.00 55690743.24 47889939.64 0.00 0.180870E+11 0.00 6.04
October 0.717039E+09 0.259658E+09 0.00 60152624.45 8286718.63 0.00 0.394256E+11 0.00 6.14
November 0.584614E+10 0.00 0.00 49130133.72 0.00 0.00 0.484342E+11 0.00 5.66
December 0.128720E+11 0.00 0.00 43109614.49 0.00 0.00 0.456467E+11 0.00 5.36
                   
Annual Sum or Average 0.418451E+11 0.165662E+11 0.00 0.642221E+09 0.169342E+09 0.00 0.378120E+12 0.00 5.81
Minimum of Months 188311.95 0.00 0.00 28497659.97 0.00 0.00 0.343609E+10 0.00 5.36
Maximum of Months 0.128720E+11 0.937081E+10 0.00 70927555.72 59229565.01 0.00 0.487581E+11 0.00 6.14



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 2628210.68 0.00 0.00 0.162188E+09 0.00 0.00 0.667512E+11 0.00 19.96
February 0.00 0.00 0.00 0.129803E+09 0.00 0.00 0.563107E+11 0.00 21.41
March 1262069.07 0.00 0.00 0.134876E+09 0.00 0.00 0.576505E+11 0.00 22.43
April 0.00 0.157569E+09 0.00 0.125142E+09 0.00 0.00 0.372316E+11 0.00 22.96
May 0.00 0.925803E+09 0.00 0.106302E+09 0.00 0.00 0.223560E+11 0.00 22.36
June 0.00 0.283083E+10 0.00 78638850.55 0.00 0.00 0.113035E+11 0.00 21.12
July 0.00 0.119678E+11 0.00 28296853.91 0.00 0.00 0.288729E+10 0.00 20.85
August 0.00 0.354172E+10 0.00 76472126.47 0.00 0.00 0.101005E+11 0.00 21.49
September 0.00 0.237801E+10 0.00 84665712.04 0.00 0.00 0.177127E+11 0.00 22.54
October 0.00 0.375977E+09 0.00 0.116461E+09 0.00 0.00 0.431307E+11 0.00 23.40
November 779378.61 0.00 0.00 0.143775E+09 0.00 0.00 0.608722E+11 0.00 21.27
December 0.00 0.00 0.00 0.167293E+09 0.00 0.00 0.655310E+11 0.00 19.46
                   
Annual Sum or Average 4669658.36 0.221777E+11 0.00 0.135391E+10 0.00 0.00 0.451838E+12 0.00 21.60
Minimum of Months 0.00 0.00 0.00 28296853.91 0.00 0.00 0.288729E+10 0.00 19.46
Maximum of Months 2628210.68 0.119678E+11 0.00 0.167293E+09 0.00 0.00 0.667512E+11 0.00 23.40



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.879052E+10 0.00 0.00 0.00 0.00 66327541.92 0.00 0.00 0.65
February 0.736302E+10 0.00 0.00 5943.41 0.00 70359816.75 5937470.85 0.00 0.68
March 0.753227E+10 0.00 0.00 154277.40 0.00 2032644.82 0.109881E+09 0.00 0.70
April 0.294216E+10 26153868.38 0.00 8065238.48 134325.02 0.00 0.232792E+10 0.00 0.79
May 0.513985E+09 0.176261E+09 0.00 14706968.71 0.00 0.00 0.317258E+10 0.00 0.93
June 0.00 0.618156E+09 0.00 15047252.85 0.00 0.00 0.229759E+10 0.00 1.08
July 0.00 0.228280E+10 0.00 6077492.15 0.00 0.00 0.641629E+09 0.00 1.07
August 11096122.57 0.712969E+09 0.00 13574747.55 0.00 0.00 0.185479E+10 0.00 1.04
September 0.384216E+09 0.447934E+09 0.00 12385565.18 27405.70 0.00 0.254056E+10 0.00 1.00
October 0.326424E+10 72139632.11 0.00 8742373.98 0.00 0.00 0.278950E+10 0.00 0.83
November 0.759872E+10 0.00 0.00 692609.05 0.00 596923.65 0.416127E+09 0.00 0.67
December 0.830866E+10 0.00 0.00 0.00 0.00 0.392038E+09 0.00 0.00 0.64
                   
Annual Sum or Average 0.467089E+11 0.433641E+10 0.00 79452468.77 161730.71 0.531355E+09 0.161565E+11 0.00 0.84
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.64
Maximum of Months 0.879052E+10 0.228280E+10 0.00 15047252.85 134325.02 0.392038E+09 0.317258E+10 0.00 1.08



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:00:07

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.191977E+12 0.125798E+11 0.147065E+12 0.687118E+12 0.886772E+11
February 0.199263E+12 0.101327E+11 0.112997E+12 0.555986E+12 0.124724E+12
March 0.319238E+12 0.967552E+10 0.105203E+12 0.534734E+12 0.186000E+12
April 0.331034E+12 0.523688E+10 0.551719E+11 0.300672E+12 0.458486E+12
May 0.362838E+12 0.260567E+10 0.269484E+11 0.163637E+12 0.731651E+12
June 0.344683E+12 0.259727E+09 -239365059.4 0.357336E+11 0.946522E+12
July 0.333635E+12 -0.345416E+10 -0.383202E+11 -0.164160E+12 0.118343E+13
August 0.303577E+12 -509141480.1 -0.152646E+10 0.805422E+09 0.100010E+13
September 0.259798E+12 0.106262E+10 0.134542E+11 0.937570E+11 0.836146E+12
October 0.244553E+12 0.536940E+10 0.597133E+11 0.336684E+12 0.465928E+12
November 0.188828E+12 0.102463E+11 0.114817E+12 0.572403E+12 0.161728E+12
December 0.155575E+12 0.136553E+11 0.158663E+12 0.738985E+12 0.792107E+11
           
Annual Sum or Average 0.323500E+13 0.668605E+11 0.753947E+12 0.385636E+13 0.626261E+13
Minimum of Months 0.155575E+12 -0.345416E+10 -0.383202E+11 -0.164160E+12 0.792107E+11
Maximum of Months 0.362838E+12 0.136553E+11 0.158663E+12 0.738985E+12 0.118343E+13