Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:59

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904

Simulation Timestamp: 2023-10-16 08:59:53


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 10797.40 951.71 951.71
Net Site Energy 10797.40 951.71 951.71
Total Source Energy 22452.34 1979.00 1979.00
Net Source Energy 22452.34 1979.00 1979.00


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 914.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 878.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 767.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 242.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1745.01 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 651.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 561.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 160.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.75 2934.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 62.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 5159.85 5637.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 914.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 878.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 767.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 242.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 959.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 14.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 8.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 32.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 561.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 160.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.75 2934.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 20.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 34.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 914.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 878.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 767.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 242.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1745.01 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 651.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 561.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 160.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 90.75 2934.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 62.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 89.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 149.04 339.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 216.73 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 454.80 496.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 89.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 149.04 339.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 216.73 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 454.80 496.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 5159.849 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 5159.849 100.00
     
Total On-Site and Utility Electric Sources 5159.849 100.00
Total Electricity End Uses 5159.849 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 22.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 7353.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:59
RunPeriod RUNPERIOD 1
Weather File San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Latitude [deg] 32.58
Longitude [deg] -117.0
Elevation [m] 159.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 9.1389 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 13.3365 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 13.3365 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 9.2031 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 6.1031 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.8125 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 10.3656 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 8.7188 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 4.5531 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 4.5531 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 6.3938 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 4.5531 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.3656 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.3656 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 11.7219 4.65 2934.4875
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 6.3938 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 6.8557 7.07 41.0709
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 6.8557 7.07 41.0709
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 9.1389 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 13.3365 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 13.3365 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 9.2031 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 6.1031 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.8125 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 10.3656 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 8.7188 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 4.5531 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 4.5531 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 4.5531 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 4.5531 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 4.5531 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 4.5531 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 6.3938 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 4.5531 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 4.5531 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 4.5531 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 10.3656 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 10.3656 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 11.7219 4.65 2934.4875  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 6.3938 18.58 0.0000  
Total 11345.29             6.8557 3.54 41.0709  
Conditioned Total 11345.29             6.8557 3.54 41.0709  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 4.4542 8.82 37.1989
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 29-SEP-19:10 02-JAN-20:00 - - - - - - - - - - 02-JAN-21:10
Heating 0.00 185003.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 118286.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 88772.42 89710.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 32151.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 29864.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 7344.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 3873.13 242839.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 1829.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 360462.95 517553.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 185003.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 118286.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 58789.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 49984.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1847.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 30153.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 150.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 29864.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 7344.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 3873.13 242839.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 241.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 530.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 1058.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 991.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 2781.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2430.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 769.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5526.46 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2063.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1777.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 508.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 287.40 3180.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 197.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 16341.24 6111.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 87.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 245.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 214.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 67.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 487.11 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 156.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 44.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 280.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1440.36 538.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 87.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 245.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 214.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 67.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 487.11 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 156.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 44.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 280.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1440.36 538.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.46 0.612567 0.549000 1.35 1.00 0.500000 0.000622 0.000061 1.35 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.325467 0.157031 0.549000 0.178681 0.549000 0.500000 0.002426 0.000025 0.178681 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.239258 0.247364 0.549000 0.131353 0.659636 0.500000 0.001540 0.000012 0.131353 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.226852 0.551695 0.549000 0.124542 1.00 0.500000 0.000691 0.000016 0.124542 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.107900 0.669199 0.549000 0.059237 1.00 0.500000 0.000569 0.000009 0.059237 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.31 0.071262 0.549000 1.82 0.549000 0.500000 0.021216 0.000096 1.82 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.40 0.103139 0.549000 0.766035 0.549000 0.500000 0.003694 0.000076 0.766035 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 4.53 0.220069 0.549000 2.49 0.586852 0.500000 0.001731 0.000211 2.49 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.35 0.878542 0.549000 0.741696 1.00 0.500000 0.000434 0.000093 0.741696 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.13 0.118637 0.549000 1.17 0.549000 0.500000 0.003211 0.000090 1.17 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.23 0.113102 0.549000 1.23 0.549000 0.500000 0.003369 0.000094 1.23 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.23 0.063627 0.549000 1.22 0.549000 0.500000 0.010770 0.000060 1.22 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.692564 0.453444 0.549000 0.380217 1.00 0.500000 0.000840 0.000057 0.380217 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 7002.68 0.000061 146.03
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 2809.35 0.000025 65.58
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1326.93 0.000012 29.11
MECH_FLR_1 VAV BOX REHEAT COIL 1826.68 0.000016 42.13
STORAGE_FLR_1 VAV BOX REHEAT COIL 1010.38 0.000009 23.95
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 10967.84 0.000096 230.68
CAFE_FLR_1 VAV BOX REHEAT COIL 8715.34 0.000076 193.82
LOBBY_FLR_1 VAV BOX REHEAT COIL 24162.54 0.000211 527.94
ROOM_1_FLR_3 FAN COIL HEATING COIL 4141.15 0.000036 118.33
ROOM_2_FLR_3 FAN COIL HEATING COIL 4141.31 0.000036 118.34
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 24034.76 0.000210 686.77
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 24049.92 0.000210 687.21
ROOM_5_FLR_3 FAN COIL HEATING COIL 4140.33 0.000036 118.31
ROOM_6_FLR_3 FAN COIL HEATING COIL 4140.48 0.000036 118.31
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 10588.30 0.000093 243.14
ROOM_1_FLR_6 FAN COIL HEATING COIL 1278.80 0.000011 36.54
ROOM_2_FLR_6 FAN COIL HEATING COIL 1278.34 0.000011 36.53
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 6171.36 0.000054 176.34
BANQUET_FLR_6 VAV BOX REHEAT COIL 10341.95 0.000090 223.90
DINING_FLR_6 VAV BOX REHEAT COIL 10722.38 0.000094 231.88
KITCHEN_FLR_6 VAV BOX REHEAT COIL 6853.18 0.000060 143.53
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 6495.13 0.000057 154.04
VAV WITH REHEAT HEATING COIL 97025.27 0.000849 1739.02
FLR_3_DOAS HEATING COIL 9427.25 0.000082 168.97
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ZoneExhaust

User-Specified Maximum Flow Rate [m3/s]
LOBBY_FLR_1 EXHAUST FAN 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 0.950535 0.000036 0.000371
ROOM_2_FLR_3 FAN COIL 0.911701 0.000036 0.000357
ROOM_3_MULT19_FLR_3 FAN COIL 5.55 0.000210 0.002125
ROOM_4_MULT19_FLR_3 FAN COIL 5.17 0.000210 0.002127
ROOM_5_FLR_3 FAN COIL 0.831655 0.000036 0.000326
ROOM_6_FLR_3 FAN COIL 0.797561 0.000036 0.000313
ROOM_1_FLR_6 FAN COIL 0.246072 0.000011 0.000096
ROOM_2_FLR_6 FAN COIL 0.235326 0.000011 0.000092
ROOM_3_MULT9_FLR_6 FAN COIL 1.14 0.000054 0.000453
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 0.950535
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 0.911701
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 5.55
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 5.17
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 0.831655
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 0.797561
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.246072
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.235326
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.14
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008571 12.80 0.008500 0.000371 0.950535  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008574 12.80 0.008500 0.000357 0.911701  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008495 12.80 0.008495 0.002125 5.55  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008766 12.80 0.008500 0.002127 5.17  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008581 12.80 0.008500 0.000326 0.831655  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008585 12.80 0.008500 0.000313 0.797561  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008569 12.80 0.008500 0.000096 0.246072  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008572 12.80 0.008500 0.000092 0.235326  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008640 12.80 0.008500 0.000453 1.14  
VAV WITH REHEAT COOLING COIL 28.03 6.70 0.008886 10.94 0.008500 0.016418 21.11 459657.95
FLR_3_DOAS COOLING COIL 31.30 6.70 0.008233 11.91 0.008233 0.001713 2.05 47946.25
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 11.66 11.66 21.23 11.66 21.11 21.11 0.300000 0.552086 21.11
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 21.11  
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 21.11
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.016418 0.000029
VAV WITH REHEAT_HEATC_CONTROLLER 0.000849  
FLR_3_DOAS_COOLC_CONTROLLER 0.001713 0.000278
FLR_3_DOAS_HEATC_CONTROLLER 0.000082  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.024390 5025.84  
HEATSYS1 PUMP 0.002473 744.69 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.002473 0.296731
COOLSYS1 0.024390 2.93
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 282651.66 282651.66 0.002473
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.024390 3479.56
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.024390 682850.76 683446.96 77.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.80 14.30 13.60 13.20 13.30 12.60 15.30 15.60 17.70 19.40 19.70 18.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 32.58 -116.98 -8.00 159.00 99429 1.1818


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 16.00 7.10 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 9.139 5.380 0.000 0.000 0.000 0.000 14.519 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 13.336 10.760 0.000 0.000 0.000 0.000 24.096 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 13.336 10.760 0.000 0.000 0.000 0.000 24.096 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 9.203 5.380 0.000 0.000 0.000 0.000 14.583 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 6.103 2.690 0.000 0.000 0.000 0.000 8.793 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.813 61.680 535.850 0.000 0.000 0.000 603.343 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 10.366 5.380 0.000 0.000 0.000 0.000 15.746 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 8.719 8.070 0.000 0.000 0.000 0.000 16.789 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 6.394 0.000 0.000 0.000 0.000 0.000 6.394 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 10.366 67.820 0.000 0.000 0.000 0.000 78.186 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 10.366 67.820 0.000 0.000 0.000 0.000 78.186 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 11.722 515.227 2419.260 0.000 0.000 0.000 2946.209 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 6.394 0.000 0.000 0.000 0.000 0.000 6.394 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 18084.325 9.139 169.807 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 18084.325
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 894.495 13.336 82.602 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 894.495
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 1035.829 13.336 82.602 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1035.829
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 1511.551 9.203 569.967 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1511.551
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 578.329 6.103 283.494 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 578.329
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 453.605 5.813 54.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 453.605
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1957.673 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1957.673
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 11405.759 8.719 27.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 11405.759
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 111.660 4.553 74.440 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.660
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 111.691 4.553 74.460 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.691
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 2489.757 6.394 118.803 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2489.757
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 111.691 4.553 74.460 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.691
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 3437.839 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3437.839
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 3437.839 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3437.839
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1210.923 11.722 54.453 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1210.923
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 2635.024 6.394 118.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2635.024


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 457.500 4.429 20.573 0.000 0.250 0.000 0.750 ReachInFreezer 457.500 457.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 285.000 2.759 12.816 0.000 0.250 0.000 0.750 ReachInRefrigerator 285.000 285.000


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.464 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.198 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 1.067 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.370 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.442 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.217 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.286 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2887
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.8346
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.7702
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.5624
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.5260
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.6546
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6103
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.4637404 3.4637404 3.4637404  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.1981135 1.1981135 1.1981135  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
21 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
22 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
23 0 21.361010 0.87247630E-01 5.4456762  
24 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
25 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
26 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
27 0 21.361010 0.87247630E-01 5.4456762  
28 9 -0.55514967E-15 0.35055860E-16 -0.14326465E-09 0.28783368E-17
29 8 0.20966873E-07 0.14258959E-12 0.36819155E-03 -0.23840058E-09
30 7 -0.11954852E-01 0.74774803E-08 -0.22672946E-01 0.13593102E-03
31 6 0.39755982 0.26159305E-05 0.46545104 -0.46559307E-02
32 5 -5.1145337 0.98147117E-04 -4.3902405 0.62241115E-01
33 4 32.666535 0.80637729E-03 21.240866 -0.41765750
34 3 -110.51061 0.17642800E-02 -55.229641 1.5048560
35 2 196.42192 0.99585215E-03 77.513220 -2.8894543
36 1 -170.90254 0.10665179E-03 -55.149704 2.7409959
37 0 57.057407 0.60929387E-06 15.576129  
38 9 0.10314710E-14 0.47183642E-16 -0.12881513E-09 -0.40099708E-17
39 8 0.18927665E-07 0.17950474E-12 0.34608657E-03 -0.21521408E-09
40 7 -0.11292911E-01 0.96443222E-08 -0.21719088E-01 0.12840450E-03
41 6 0.37957032 0.34070209E-05 0.45007157 -0.44438791E-02
42 5 -4.9389364 0.12890179E-03 -4.2718596 0.60063826E-01
43 4 31.889569 0.10670331E-02 20.777560 -0.40734193
44 3 -108.85680 0.23501275E-02 -54.313423 1.4809641
45 2 194.78196 0.13343675E-02 76.673975 -2.8634131
46 1 -170.29645 0.14368413E-03 -54.907648 2.7303734
47 0 57.057407 0.82565881E-06 15.617726  
48 9 0.86975537E-15 0.52023775E-16 -0.12536948E-09 -0.54620444E-17
49 8 0.18440443E-07 0.18784465E-12 0.34068694E-03 -0.20967419E-09
50 7 -0.11130813E-01 0.10155400E-07 -0.21485363E-01 0.12656138E-03
51 6 0.37516444 0.35965268E-05 0.44629465 -0.43919449E-02
52 5 -4.8959230 0.13636263E-03 -4.2427425 0.59530495E-01
53 4 31.699203 0.11309484E-02 20.663505 -0.40481456
54 3 -108.45147 0.24950915E-02 -54.087828 1.4751087
55 2 194.37988 0.14187814E-02 76.467519 -2.8570287
56 1 -170.14779 0.15298304E-03 -54.848449 2.7277680
57 0 57.057407 0.88039223E-06 15.628184  
58 9 0.12430042E-14 0.43603463E-16 -0.13615479E-09 -0.52742981E-17
59 8 0.19963588E-07 0.16114398E-12 0.35741204E-03 -0.22699287E-09
60 7 -0.11632381E-01 0.85488282E-08 -0.22208377E-01 0.13226440E-03
61 6 0.38879653 0.30047059E-05 0.45796739 -0.45526330E-02
62 5 -5.0290001 0.11318598E-03 -4.3326723 0.61180550E-01
63 4 32.288109 0.93328928E-03 21.015642 -0.41263319
64 3 -109.70522 0.20484795E-02 -54.784283 1.4932205
65 2 195.62339 0.11595496E-02 77.105128 -2.8767741
66 1 -170.60747 0.12450863E-03 -55.031726 2.7358244
67 0 57.057407 0.71328115E-06 15.596176  
68 9 0.10418955E-14 0.45554749E-16 -0.13285794E-09 -0.34221686E-17
69 8 0.19498290E-07 0.16949498E-12 0.35235048E-03 -0.22170227E-09
70 7 -0.11480752E-01 0.90423087E-08 -0.21989859E-01 0.13054032E-03
71 6 0.38467563 0.31853038E-05 0.45444290 -0.45040579E-02
72 5 -4.9887746 0.12022067E-03 -4.3055366 0.60681782E-01
73 4 32.110117 0.99300969E-03 20.909427 -0.41027004
74 3 -109.32633 0.21828955E-02 -54.574228 1.4877470
75 2 195.24766 0.12373115E-02 76.912747 -2.8708078
76 1 -170.46860 0.13302463E-03 -54.976289 2.7333905
77 0 57.057407 0.76310210E-06 15.605744  
78 7 -0.15963512E-14 -0.15187529E-16 -0.22427203E-13 0.56155309E-15
79 6 0.17983713E-10 0.23594901E-11 0.52322926E-09 -0.18637893E-10
80 5 -0.60139213E-07 0.11510628E-07 -0.21924491E-05 0.17161312E-06
81 4 0.62746279E-04 0.43399923E-05 0.17681060E-02 -0.28244642E-03
82 3 -0.90508353E-02 0.15320797E-03 -0.21560640 0.43341486E-01
83 2 0.12836503 0.66328859E-03 2.9007871 -0.61911613
84 1 -0.32478029 0.41934727E-03 -7.1379041 1.5697129
85 0 0.20664896 0.54311639E-05 4.4522013  
86 7 -0.22427203E-13 -0.15187529E-16 -0.15963512E-14 0.56155309E-15
87 6 0.52322926E-09 0.23594901E-11 0.17983713E-10 -0.18637893E-10
88 5 -0.21924491E-05 0.11510628E-07 -0.60139213E-07 0.17161312E-06
89 4 0.17681060E-02 0.43399923E-05 0.62746279E-04 -0.28244642E-03
90 3 -0.21560640 0.15320797E-03 -0.90508353E-02 0.43341486E-01
91 2 2.9007871 0.66328859E-03 0.12836503 -0.61911613
92 1 -7.1379041 0.41934727E-03 -0.32478029 1.5697129
93 0 4.4522013 0.54311639E-05 0.20664896  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
103 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
104 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
105 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
106 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
107 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
108 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
109 0 1.0055995 0.48413807E-04 60.838472  
110 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
111 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
112 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
113 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
114 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
115 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
116 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
117 0 1.0055995 0.48413807E-04 60.838472  
118 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
119 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
120 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
121 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
122 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
123 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
124 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
125 0 1.0055995 0.48413807E-04 60.838472  
126 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
127 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
128 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
129 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
130 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
131 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
132 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
133 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.4711_SHGC_0.25 37 1 VerySmooth 2.678 2.678 1.000 0.251    
2 RESWINDOW_U_0.4711_SHGC_0.25 38 1 VerySmooth 2.678 2.678 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   2.39142E-002 0.16139 0.61472 0.61472 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11798 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   2.39142E-002 0.16139 0.61472 0.61472 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11798 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 1.500
2 RACK2 1 0 Zone Air-Cooled 3.000


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 0.576 0.5074
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 0.263 2.9576E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 3.921E-002 5.846E-004 2.885E-004 0.531 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 1.513E-002 1.949E-004 5.306E-004 0.177 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 3.577E-002 2.178E-004 5.696E-004 0.198 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 2.064E-002 2.178E-004 4.726E-004 0.198 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 4.884E-002 6.258E-004 5.569E-004 0.569 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 8.667E-002 4.589E-004 2.527E-004 0.417 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.248 1.893E-004 3.620E-004 0.172 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 6.349E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 6.350E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 2.751E-002 7.066E-005 5.696E-004 8.345E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.164E-002 4.746E-004 2.589E-004 0.561 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 4.974E-002 4.815E-004 2.609E-004 0.569 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 4.868E-002 1.181E-004 9.784E-005 0.140 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 8.7013E-002
2 Clear Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 3.9098E-002
3 Clear Turbid Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 9.6674E-002
4 Clear Turbid Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 4.2679E-002
5 Intermediate Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 6.5685E-002
6 Intermediate Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 2.4415E-002
7 Overcast Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 2.6511E-002
8 Overcast Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 8.7811E-003
9 Clear Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 9.8305E-002
10 Clear Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 4.7836E-002
11 Clear Turbid Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1095
12 Clear Turbid Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 5.2162E-002
13 Intermediate Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 7.2719E-002
14 Intermediate Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 3.0822E-002
15 Overcast Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 2.9789E-002
16 Overcast Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 1.2036E-002
17 Clear Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.1172E-002
18 Clear Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.2102E-002
19 Clear Turbid Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.6312E-002
20 Clear Turbid Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 9.1416E-003
21 Intermediate Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.5604E-002
22 Intermediate Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 6.2330E-003
23 Overcast Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.6108E-002
24 Overcast Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 9.2309E-003
25 Clear Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.1172E-002
26 Clear Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.2102E-002
27 Clear Turbid Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.6312E-002
28 Clear Turbid Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 9.1416E-003
29 Intermediate Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.5604E-002
30 Intermediate Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 6.2330E-003
31 Overcast Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.6108E-002
32 Overcast Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 9.2309E-003


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 33249.06263 33249.06263 2.46156 2.46156 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:30:00 27.33950 8.22721E-003 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 0.85446   00:10:00 3.80000 5.05843E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 4395.80487 4395.80487 0.32547 0.32547 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 30.92917 8.23290E-003 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 1884.07006 1884.07006 8.22847E-002 8.22847E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3231.38937 3231.38937 0.23926 0.23926 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 30.05400 8.23151E-003 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 646.75392 646.75392 2.82467E-002 9.17347E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 3064.49973 3064.49973 0.22685 0.22685 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 29.16400 8.23009E-003 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1181.87653 1181.87653 5.16179E-002 5.16179E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1457.58689 1457.58689 0.10790 0.10790 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 31.03300 8.23307E-003 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 703.67493 703.67493 3.07327E-002 5.77652E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 44727.99419 44727.99419 3.31133 3.31133 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 31.30000 8.23349E-003 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 1556.31490 1556.31490 6.79703E-002 6.79703E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 18829.82543 18829.82543 1.39533 1.39533 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 30.92917 8.23290E-003 188.86188 142.30000 0.67638 0.00000
14 CAFE_FLR_1 Heating 4748.18961 4748.18961 0.20737 0.67638 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 188.86188 142.30000 0.67638 0.00000
15 LOBBY_FLR_1 Cooling 61159.89549 61159.89549 4.52965 4.52965 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 31.07750 8.23314E-003 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 11284.83873 11284.83873 0.49286 1.89399 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 9528.23709 9528.23709 0.95054 0.95054 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 30.52867 8.23226E-003 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 4141.20192 4141.20192 0.18192 0.18192 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 9138.95646 9138.95646 0.91170 0.91170 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 30.41000 8.23207E-003 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 4141.35643 4141.35643 0.18193 0.18193 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 55588.18086 55588.18086 5.54523 5.54523 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 31.07750 8.23314E-003 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 24034.90505 24034.90505 1.05588 1.05588 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 51784.34227 51784.34227 5.16618 5.16618 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 31.30000 8.23349E-003 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 24050.06627 24050.06627 1.05654 1.05654 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 8336.56893 8336.56893 0.83165 0.83165 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 27.16150 8.22694E-003 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 4140.37938 4140.37938 0.18189 0.18189 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 7994.80962 7994.80962 0.79756 0.79756 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 26.65717 8.22614E-003 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 4140.53389 4140.53389 0.18190 0.18190 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 18248.79246 18248.79246 1.35099 1.35099 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 31.30000 8.23349E-003 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 6746.85422 6746.85422 0.29467 0.47476 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 2466.64007 2466.64007 0.24607 0.24607 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 30.52867 8.23226E-003 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 1278.81174 1278.81174 5.61787E-002 5.61787E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2358.92700 2358.92700 0.23533 0.23533 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 30.41000 8.23207E-003 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 1278.35738 1278.35738 5.61587E-002 5.61587E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 11401.65860 11401.65860 1.13746 1.13746 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 31.07750 8.23314E-003 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 6171.41618 6171.41618 0.27111 0.27111 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 28738.68261 28738.68261 2.13023 2.13023 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 31.30000 8.23349E-003 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 4284.35023 4284.35023 0.18712 1.18780 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 30145.60093 30145.60093 2.23448 2.23448 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 31.30000 8.23349E-003 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 4368.38133 4368.38133 0.19079 1.18780 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 3.80000 5.05843E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 29978.97688 29978.97688 2.22523 2.22523 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 30.49900 8.23222E-003 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 562.44009 562.44009 2.45622E-002 0.36735 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 3.80000 5.05843E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 9355.00460 9355.00460 0.69256 0.69256 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 31.30000 8.23349E-003 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 4525.60994 4525.60994 0.19765 0.19765 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 3.80000 5.05843E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 381714.54 21.11217 21.11217 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 110165.83 7.19144 7.19144 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00
3 FLR_3_DOAS Cooling Sensible 45064.07 15.11240 2.05125 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 FLR_3_DOAS Heating Sensible 31423.05 3.22351 2.05125 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.46156
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.61257
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54900
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.35140
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.21973E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.12625E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.35140
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7002.68251
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.12625E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 146.02887
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.32547
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15703
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54900
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.17868
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54900
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.42627E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.45775E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.17868
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2809.35365
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.45775E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 65.58172
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.23926
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24736
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54900
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13135
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.65964
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.54024E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.16086E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13135
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1326.93407
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.16086E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 29.11200
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.22685
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.55170
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54900
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12454
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.90599E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.59806E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.12454
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1826.68157
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.59806E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 42.13136
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.10790
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.66920
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54900
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.92371E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.69338E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.83922E-006
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.92371E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1010.37681
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.83922E-006
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 23.95464
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.31133
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.12625E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54900
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.81792
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54900
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.12158E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.59514E-005
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.81792
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10967.83701
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.59514E-005
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 230.68082
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.39533
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10314
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54900
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.76603
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54900
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.69404E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.62456E-005
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.76603
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8715.33939
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.62456E-005
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 193.82311
99 Fan:ZoneExhaust LOBBY_FLR_1 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.52965
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22007
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54900
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.48678
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.58685
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.73127E-003
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.11384E-004
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.48678
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
110 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 24162.54279
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.11384E-004
113 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 527.94094
114 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
115 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.95054
116 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.95054
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.62286E-005
118 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.71493E-004
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69394
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57148E-003
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.71493E-004
125 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.95054
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4141.15101
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.62286E-005
128 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 118.33178
129 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
130 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.91170
131 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.91170
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.62299E-005
133 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.56602E-004
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69394
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57440E-003
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.56602E-004
140 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.91170
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4141.30551
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.62299E-005
143 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 118.33619
144 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
145 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.54523
146 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 5.54523
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.10267E-004
148 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.12479E-003
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69438
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.49458E-003
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.49458E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.12479E-003
155 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.54523
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 24034.76091
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.10267E-004
158 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 686.77459
159 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
160 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.16618
161 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 5.16618
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.10399E-004
163 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.12676E-003
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69344
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.76599E-003
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.12676E-003
170 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.16618
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 24049.92204
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.10399E-004
173 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 687.20777
174 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
175 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.83165
176 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.83165
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.62214E-005
178 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.25904E-004
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69393
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.58126E-003
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.25904E-004
185 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.83165
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4140.32848
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.62214E-005
188 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 118.30828
189 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
190 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.79756
191 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.79756
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.62228E-005
193 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.12832E-004
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69392
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.58462E-003
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.12832E-004
200 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.79756
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4140.48298
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.62228E-005
203 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 118.31269
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.35099
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.87854
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54900
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.74170
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.33673E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.26311E-005
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.74170
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
214 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10588.30396
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.26311E-005
217 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 243.13548
218 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
219 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.24607
220 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.24607
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.11875E-005
222 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 9.61089E-005
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69395
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56912E-003
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.61089E-005
229 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.24607
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1278.79645
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.11875E-005
232 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 36.53985
233 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
234 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.23533
235 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.23533
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.11835E-005
237 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 9.19887E-005
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69394
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57216E-003
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.19887E-005
244 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.23533
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1278.34210
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.11835E-005
247 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 36.52686
248 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
249 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.13746
250 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.13746
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.39897E-005
252 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.52930E-004
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69365
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.64030E-003
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.52930E-004
259 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.13746
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6171.35682
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.39897E-005
262 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 176.33691
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.13023
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11864
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54900
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.16949
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54900
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.21148E-003
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.04759E-005
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.16949
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
273 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10341.95293
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.04759E-005
276 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 223.89711
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.23448
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11310
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54900
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.22673
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54900
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.36865E-003
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.38040E-005
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.22673
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
287 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10722.37911
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.38040E-005
290 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 231.88419
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.22523
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.36268E-002
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54900
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.22165
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54900
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.07703E-002
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.99546E-005
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.22165
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
301 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6853.18138
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.99546E-005
304 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 143.52567
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.69256
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.45344
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.54900
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.38022
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.40236E-004
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.68222E-005
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.38022
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
315 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6495.12887
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.68222E-005
318 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 154.03790
319 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 11.65573
320 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 11.65573
321 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 21.23084
322 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 11.65573
323 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 21.11217
324 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 21.11217
325 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
326 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.55209
327 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
328 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
329 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
333 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
334 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
335 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 21.11217
336 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
337 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.11217
338 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 28.02796
339 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
340 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.94366
341 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.88632E-003
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 459657.94592
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.64179E-002
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 21.11217
346 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 97025.27081
347 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.48819E-004
348 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1739.01847
349 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 21.11217
350 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.64179E-002
351 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 2.90043E-005
352 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 8.48819E-004
353 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
354 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
355 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 31.30000
356 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
357 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.91243
358 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.23349E-003
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.23349E-003
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 47946.24805
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.71253E-003
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
363 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 9427.24706
364 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.24737E-005
365 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 168.96790
366 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
367 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.71253E-003
368 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 2.78063E-004
369 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 8.24737E-005
370 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 2.43898E-002
371 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 5025.84349
372 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.47276E-003
373 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.29673
374 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.47276E-003
375 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 744.68672
376 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
377 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 282651.65822
378 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 282651.66000
379 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.47276E-003
380 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 2.43898E-002
381 PlantLoop COOLSYS1 Plant Loop Volume [m3] 2.92678
382 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 2.43898E-002
383 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 3479.56096
384 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 2.43898E-002
385 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 682850.76018
386 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 683446.96000
387 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 77.91295
388 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
389 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
390 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
391 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
392 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 7038.90
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 2822.23
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1333.49
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 1835.15
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1014.94
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 11024.12
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 8757.22
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 24282.41
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 4460.31
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 4460.47
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 25886.94
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 25903.27
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 4459.42
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 4459.59
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 10637.59
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 1377.32
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 1376.83
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 6646.82
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 10393.66
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 10776.04
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 6888.49
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 6524.47
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 81423.36
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 7911.32


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 15730.56 12659.45 3071.12 0.80 1816.63 18.43
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 15095.79 12146.06 2949.72 0.80 1743.17 17.68
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 90618.53 73305.78 17312.75 0.81 10497.08 106.47
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 88419.50 70215.28 18204.22 0.79 10156.28 103.01
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 13787.30 11087.83 2699.47 0.80 1591.74 16.14
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 13230.05 10637.13 2592.91 0.80 1527.25 15.49
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 4070.56 3276.40 794.15 0.80 470.12 4.77
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 3894.93 3134.36 760.57 0.80 449.79 4.56
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 19054.42 15260.31 3794.11 0.80 2196.02 22.27
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 526583.54 365115.68 161467.85 0.69 62561.83 634.54
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 51527.24 35531.42 15995.82 0.69 5813.13 58.96


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 3.93 13.40


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.940 0.824   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.198 1.198   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.370 1.137   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.370 1.137   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.370 1.137   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.370 1.137   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.286 1.078   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.286 1.078   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.286 1.078   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.286 1.078   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.286 1.078   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.9330096377E-002 2.3999274279E-002 Pass Pass 5.6420342345E-003 1.7225031033E-002 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 1.7037736591E-002 4.2608514548E-002 Pass Pass 5.0736795029E-002 6.2109563814E-002 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 2.9243092201E-002 3.0898379369E-002 Pass Pass 7.8344425634E-003 2.0689982595E-002 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 1.2620056967E-002 1.6055975051E-002 Pass Pass 1.0253781398E-002 2.8396126962E-002 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 4.5058277555E-003 7.0100878455E-003 Pass Pass 1.5606816831E-002 2.5277417543E-002 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 8.1791577161E-002 0.2273228279 Pass Pass 1.9318097533E-002 4.9301029782E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 6.4939206729E-002 7.9038065784E-002 Pass Pass 1.3892685237E-002 2.5454676411E-002 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 4.1352291482E-002 4.4872286514E-002 Pass Pass 8.3685954528E-003 1.9337937788E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 3.0897671313E-002 8.4360594238E-002 Pass Pass 0.2356684303 1.2986967943 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 4.4693241318E-002 0.1425003749 Pass Pass 0.1125958531 0.2858003915 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 4.5508076606E-002 5.6694836536E-002 Pass Pass 9.7618932452E-003 1.0088286694E-002 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 1.3541056371E-002 5.5911831861E-002 Pass Pass 0.1304364220 0.3828743630 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 4.3445083626E-002 0.1611854435 Pass Pass 0.7430953737 6.1633148562 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 4.0533839968E-002 0.1380539500 Pass Pass 0.2435923034 0.7794268697 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 1.0662895423E-002 1.1346697438E-002 Pass Pass 1.2857545873E-002 2.4584687824E-002 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 4.4494669654E-002 0.1321541353 Pass Pass 2.6209547608 27.4466324297 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 6.2384980425E-002 0.2065337032 Pass Pass 0.2320364715 0.9150408177 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 4.2331157257E-002 0.1579011661 Pass Pass 0.1756647377 0.4013961946 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 3.6003431501E-002 7.1181055514E-002 Pass Pass 1.2202916974E-002 3.5753075197E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 2.5691172703E-002 5.8915262557E-002 Pass Pass 1.3392390645E-002 3.7652741314E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 2.4219974133E-002 7.3986255943E-002 Pass Pass 2.1121439556E-002 4.0971496408E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 1.1455868118E-002 1.5257389060E-002 Pass Pass 1.6754472378E-002 2.4768742863E-002 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3561.99 78.30 973.24 4503.31 4288.33 13405.17



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 3.80 0.00 3.80 Wetbulb [C] 3.00 120.00
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 31.30 8.90 18.40 Wetbulb [C] 4.10 280.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 2.00 2      
Feb 59.00 53      
Mar 58.58 43      
Apr 46.42 14      
May 18.00 12      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 3.00 6      
Oct 0.00 0      
Nov 18.00 12      
Dec 4.00 4      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.845 0.940 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.920 1.067 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.920 1.067 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.920 1.067 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.920 1.067 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 0.920 1.067 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.55 0.221 0.228 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.029 1.217 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.029 1.217 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.029 1.217 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.029 1.217 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.029 1.217 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.029 1.217 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.029 1.217 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.029 1.217 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.029 1.217 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.029 1.217 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 1.137 1.370 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 1.137 1.370 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 1.137 1.370 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 1.137 1.370 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.078 1.286 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.078 1.286 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 1.078 1.286 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.078 1.286 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.078 1.286 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.186 1.442 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.55 0.221 0.228 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.55 0.221 0.228 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.186 0.196 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.186 0.196 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.186 0.196 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.186 0.196 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.186 0.196 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.186 0.196 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.186 0.196 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.186 0.196 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.186 0.196 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.186 0.196 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.185 0.196 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.185 0.196 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.185 0.196 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.188 0.196 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   23.26 0.00 0.00 23.26 23.26 2.678 0.251 0.251             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   65.50 0.00 0.00 65.50 65.50 2.678 0.251 0.251             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   85.08 0.00 0.00 85.08 85.08 2.678 0.251 0.251             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.678 0.251 0.251             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.678 0.251 0.251             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.678 0.251 0.251             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.678 0.251 0.251             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   3.68 0.00 0.00 3.68 279.56 2.678 0.251 0.251             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   3.68 0.00 0.00 3.68 279.65 2.678 0.251 0.251             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.678 0.251 0.251             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.678 0.251 0.251             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.678 0.251 0.251             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.678 0.251 0.251             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.678 0.251 0.251             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   2.15 0.00 0.00 2.15 8.59 2.678 0.251 0.251             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   2.15 0.00 0.00 2.15 8.58 2.678 0.251 0.251             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.678 0.251 0.251             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.678 0.251 0.251             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.678 0.251 0.251             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.678 0.251 0.251             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.678 0.251 0.251             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   6.74 0.00 0.00 6.74 60.70 2.678 0.251 0.251             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.678 0.251 0.251             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.678 0.251 0.251             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.678 0.251 0.251             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.678 0.251 0.251             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.678 0.251 0.251             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   5.82 0.00 0.00 5.82 5.82 2.678 0.251 0.251             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   5.21 0.00 0.00 5.21 5.21 2.678 0.251 0.251             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.678 0.251 0.251             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.678 0.251 0.251                      
North Total or Average             432.95 2.678 0.251 0.251                      
Non-North Total or Average             780.84 2.678 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.016 1.198 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 9.1389 1978.83 18084.33 LightsWired LTG_SCH_BASEMENT 51.16 168.00 51.10 0.0000 Y 173.46
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 13.3365 67.07 894.50 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 8.61
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 13.3365 77.67 1035.83 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 9.97
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 9.2031 164.24 1511.55 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 16.63
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 6.1031 94.76 578.33 LightsWired LTG_SCH_STORAGE 25.68 168.00 25.65 0.0000 Y 2.78
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.8125 78.04 453.60 LightsWired LTG_SCH_LAUNDRY 51.36 168.00 51.30 0.0000 Y 4.37
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 10.3656 188.86 1957.67 LightsWired LTG_SCH_DINING 58.69 168.00 49.25 0.0000 Y 18.10
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 8.7188 1308.19 11405.76 LightsWired LTG_SCH_LOBBY 58.69 168.00 57.00 0.0000 Y 122.03
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 4.5531 156.09 710.69 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 4.5531 156.07 710.61 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 4.5531 1863.81 8486.17 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 76.02
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 4.5531 1864.32 8488.49 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 76.04
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 4.5531 156.09 710.69 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 4.5531 156.07 710.61 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 6.3938 1557.62 9959.03 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 109.60
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 4.5531 39.02 177.67 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.59
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 4.5531 39.02 177.65 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.59
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 4.5531 220.77 1005.22 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 9.00
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 10.3656 331.66 3437.84 LightsWired LTG_SCH_DINING 58.69 168.00 53.98 0.0000 Y 34.83
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 10.3656 331.66 3437.84 LightsWired LTG_SCH_DINING 58.69 168.00 53.98 0.0000 Y 34.83
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 11.7219 103.30 1210.92 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 13.33
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 6.3938 412.12 2635.02 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 29.00
Interior Lighting Total       6.8557 11345.29 77780.02               507.91


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.07 11405.76 798.40
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.00 11405.76 0.00
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.39 1957.67 763.49
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.00 1957.67 0.00
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3437.84 687.57
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.00 3437.84 0.00
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3437.84 687.57
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.00 3437.84 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 15448.40 AstronomicalClock -   83.75 83.75 242.88
Exterior Lighting Total 15448.40           242.88



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 282651.66 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 683446.96 2.96 683567.09 2.96 3.93 13.40


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10401.02 15730.56 12659.45 3071.12 0.80 - 1816.63 18.43
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 9984.08 15095.79 12146.06 2949.72 0.80 - 1743.17 17.68
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 59489.45 90618.53 73305.78 17312.75 0.81 - 10497.08 106.47
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 59544.64 88419.50 70215.28 18204.22 0.79 - 10156.28 103.01
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 9124.62 13787.30 11087.83 2699.47 0.80 - 1591.74 16.14
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 8758.62 13230.05 10637.13 2592.91 0.80 - 1527.25 15.49
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2690.84 4070.56 3276.40 794.15 0.80 - 470.12 4.77
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2575.49 3894.93 3134.36 760.57 0.80 - 449.79 4.56
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 12681.08 19054.42 15260.31 3794.11 0.80 - 2196.02 22.27
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 459657.95 526583.54 365115.68 161467.85 0.69 - 62561.83 634.54
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 47946.25 51527.24 35531.42 15995.82 0.69 - 5813.13 58.96
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 7002.68 7038.90 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2809.35 2822.23 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1326.93 1333.49 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1826.68 1835.15 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1010.38 1014.94 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 10967.84 11024.12 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 8715.34 8757.22 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 24162.54 24282.41 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 4141.15 4460.31 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 4141.31 4460.47 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 24034.76 25886.94 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 24049.92 25903.27 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 4140.33 4459.42 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 4140.48 4459.59 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 10588.30 10637.59 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1278.80 1377.32 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1278.34 1376.83 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 6171.36 6646.82 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 10341.95 10393.66 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 10722.38 10776.04 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 6853.18 6888.49 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 6495.13 6524.47 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 97025.27 81423.36 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 9427.25 7911.32 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.95 668.83 703.64 1.00 1.21 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.91 641.51 703.64 1.00 1.22 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 5.55 3901.82 703.64 1.00 0.96 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 5.17 3635.11 703.64 1.00 0.97 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.83 585.18 703.64 1.00 1.25 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.80 561.19 703.64 1.00 1.26 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.25 173.14 703.64 1.00 1.86 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.24 165.58 703.64 1.00 1.90 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.14 800.36 703.64 1.00 1.17 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 21.11 47304.74 2240.64 1.00 1.11 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.024390 5025.84 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.002473 744.69 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.024390 3479.56 142664.32 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.80 0.58 0.51
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.80 0.26 0.03



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 33249.06 33249.06 16.80 2.462 2.462 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:30:00 24.00 24.00 0.00923 27.34 0.00823 0.854 0.00
RETAIL_1_FLR_1 4395.80 4395.80 65.54 0.325 0.325 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 24.00 24.00 0.00903 30.93 0.00823 0.079 0.00
RETAIL_2_FLR_1 3231.39 3231.39 41.60 0.239 0.239 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 24.00 24.00 0.00936 30.05 0.00823 0.092 0.00
MECH_FLR_1 3064.50 3064.50 18.66 0.227 0.227 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 24.00 24.00 0.00868 29.16 0.00823 0.000 0.00
STORAGE_FLR_1 1457.59 1457.59 15.38 0.108 0.108 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 24.00 24.00 0.00879 31.03 0.00823 0.058 0.00
LAUNDRY_FLR_1 44727.99 44727.99 573.15 3.311 3.311 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 24.00 24.00 0.00854 31.30 0.00823 0.000 0.00
CAFE_FLR_1 18829.83 18829.83 99.70 1.395 1.395 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 24.00 23.99 0.01018 30.93 0.00823 0.676 0.00
LOBBY_FLR_1 61159.90 61159.90 46.75 4.530 4.530 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 24.00 23.99 0.01004 31.08 0.00823 1.894 0.00
ROOM_1_FLR_3 9528.24 9528.24 244.18 0.951 0.951 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 21.11 21.11 0.00857 30.53 0.00823 0.062 0.00
ROOM_2_FLR_3 9138.96 9138.96 234.23 0.912 0.912 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 21.11 21.11 0.00857 30.41 0.00823 0.062 0.00
ROOM_3_MULT19_FLR_3 55588.18 55588.18 2266.70 5.545 5.545 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 21.11 21.11 0.00849 31.08 0.00823 0.837 0.00
ROOM_4_MULT19_FLR_3 51784.34 51784.34 2111.01 5.166 5.166 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 21.11 21.11 0.00877 31.30 0.00823 0.837 0.00
ROOM_5_FLR_3 8336.57 8336.57 213.64 0.832 0.832 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 21.11 21.11 0.00858 27.16 0.00823 0.062 0.00
ROOM_6_FLR_3 7994.81 7994.81 204.90 0.798 0.798 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 21.11 21.11 0.00858 26.66 0.00823 0.062 0.00
CORRIDOR_FLR_3 18248.79 18248.79 46.86 1.351 1.351 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 24.00 24.00 0.00952 31.30 0.00823 0.475 0.00
ROOM_1_FLR_6 2466.64 2466.64 63.21 0.246 0.246 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 21.11 21.11 0.00857 30.53 0.00823 0.015 0.00
ROOM_2_FLR_6 2358.93 2358.93 60.46 0.235 0.235 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 21.11 21.11 0.00857 30.41 0.00823 0.015 0.00
ROOM_3_MULT9_FLR_6 11401.66 11401.66 464.79 1.137 1.137 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 21.11 21.11 0.00864 31.08 0.00823 0.099 0.00
BANQUET_FLR_6 28738.68 28738.68 86.65 2.130 2.130 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 24.00 23.98 0.01045 31.30 0.00823 1.188 0.00
DINING_FLR_6 30145.60 30145.60 90.89 2.234 2.234 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 24.00 23.99 0.01036 31.30 0.00823 1.188 0.00
KITCHEN_FLR_6 29978.98 29978.98 290.20 2.225 2.225 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 24.00 23.97 0.01011 30.50 0.00823 0.367 0.00
CORRIDOR_FLR_6 9355.00 9355.00 22.70 0.693 0.693 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 24.00 24.00 0.00903 31.30 0.00823 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 0.854   00:10:00 21.00 22.01 0.00506 3.80 0.00506 0.854 0.00
RETAIL_1_FLR_1 1884.07 1884.07 28.09 0.082 0.082 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00767 3.80 0.00506 0.079 0.00
RETAIL_2_FLR_1 646.75 646.75 8.33 0.028 0.092 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00764 3.80 0.00506 0.092 0.00
MECH_FLR_1 1181.88 1181.88 7.20 0.052 0.052 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00755 3.80 0.00506 0.000 0.00
STORAGE_FLR_1 703.67 703.67 7.43 0.031 0.058 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00756 3.80 0.00506 0.058 0.00
LAUNDRY_FLR_1 1556.31 1556.31 19.94 0.068 0.068 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00753 3.80 0.00506 0.000 0.00
CAFE_FLR_1 4748.19 4748.19 25.14 0.207 0.676 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00771 3.80 0.00506 0.676 0.00
LOBBY_FLR_1 11284.84 11284.84 8.63 0.493 1.894 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00766 3.80 0.00506 1.894 0.00
ROOM_1_FLR_3 4141.20 4141.20 106.12 0.182 0.182 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00766 3.80 0.00506 0.062 0.00
ROOM_2_FLR_3 4141.36 4141.36 106.14 0.182 0.182 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00766 3.80 0.00506 0.062 0.00
ROOM_3_MULT19_FLR_3 24034.91 24034.91 980.06 1.056 1.056 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00768 3.80 0.00506 0.837 0.00
ROOM_4_MULT19_FLR_3 24050.07 24050.07 980.41 1.057 1.057 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00768 3.80 0.00506 0.837 0.00
ROOM_5_FLR_3 4140.38 4140.38 106.10 0.182 0.182 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00766 3.80 0.00506 0.062 0.00
ROOM_6_FLR_3 4140.53 4140.53 106.12 0.182 0.182 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00766 3.80 0.00506 0.062 0.00
CORRIDOR_FLR_3 6746.85 6746.85 17.33 0.295 0.475 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00774 3.80 0.00506 0.475 0.00
ROOM_1_FLR_6 1278.81 1278.81 32.77 0.056 0.056 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00772 3.80 0.00506 0.015 0.00
ROOM_2_FLR_6 1278.36 1278.36 32.76 0.056 0.056 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00772 3.80 0.00506 0.015 0.00
ROOM_3_MULT9_FLR_6 6171.42 6171.42 251.58 0.271 0.271 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00773 3.80 0.00506 0.099 0.00
BANQUET_FLR_6 4284.35 4284.35 12.92 0.187 1.188 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00779 3.80 0.00506 1.188 0.00
DINING_FLR_6 4368.38 4368.38 13.17 0.191 1.188 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 21.00 21.00 0.00779 3.80 0.00506 1.188 0.00
KITCHEN_FLR_6 562.44 562.44 5.44 0.025 0.367 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 21.00 21.00 0.00491 3.80 0.00506 0.367 0.00
CORRIDOR_FLR_6 4525.61 4525.61 10.98 0.198 0.198 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 21.00 21.00 0.00782 3.80 0.00506 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 21.11 21.11 7.19 7.19 21.1122 11.6557 21.1122 0.5521 0.3000
FLR_3_DOAS 15.11 2.05 3.22 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 7002.683 7002.683 1.351396 0.00006126 146.029   12/21 00:10:00   12/21 00:10:00 7002.68 7002.68 1.351396 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00800000 50.7558 0.00 0.00 7042.04 7042.04
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 2809.354 2809.354 0.178681 0.00002458 65.582 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2809.35 2809.35 0.178681 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00767295 48.7070 1884.07 0.00 2824.35 2824.35
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1326.934 1326.934 0.131353 0.00001161 29.112 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1326.93 1326.93 0.131353 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00763711 48.4817 646.75 0.00 1334.27 1334.27
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 1826.682 1826.682 0.124542 0.00001598 42.131 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1826.68 1826.68 0.124542 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00754698 47.9164 1181.88 0.00 1836.47 1836.47
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1010.377 1010.377 0.059237 0.00000884 23.955 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1010.38 1010.38 0.059237 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00755893 47.9913 703.67 0.00 1015.75 1015.75
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10967.837 10967.837 1.817922 0.00009595 230.681 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 10967.84 10967.84 1.817922 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00753315 47.8301 1556.31 0.00 11029.29 11029.29
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 8715.339 8715.339 0.766035 0.00007625 193.823 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 8715.34 8715.34 0.766035 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00770916 48.9338 4748.19 0.00 8762.67 8762.67
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 24162.543 24162.543 2.486780 0.00021138 527.941 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 24162.54 24162.54 2.486780 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00765707 48.6068 11284.84 0.00 24296.34 24296.34
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 10401.022 -999.000 0.950535 0.00037149 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 unknown 8/21 16:20:00 10401.02 10225.69 0.950535 21.69 15.43 0.00857148 12.80 11.93 0.00850000 30.53 0.00823226 18.20 0.0000 21.11 0.00857148 53.9641 9528.24 0.00 10588.55 10225.00
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 4141.151 4141.151 0.181924 0.00003623 118.332 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4141.15 4141.15 0.181924 21.11 14.40 0.00765847 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00765847 48.2859 4141.20 0.00 4464.29 4464.29
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 9984.080 -999.000 0.911701 0.00035660 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown 8/21 16:30:00 9984.08 9809.01 0.911701 21.69 15.44 0.00857440 12.80 11.93 0.00850000 30.41 0.00823207 18.16 0.0000 21.11 0.00857440 53.9822 9138.96 0.00 10164.02 9808.47
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 4141.306 4141.306 0.181931 0.00003623 118.336 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4141.31 4141.31 0.181931 21.11 14.40 0.00765851 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00765851 48.2861 4141.36 0.00 4464.45 4464.45
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 59489.454 -999.000 5.545226 0.00212479 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown 8/21 13:30:00 59489.45 59489.45 5.545226 21.69 15.37 0.00849458 12.80 11.93 0.00849458 31.08 0.00823314 18.38 0.0000 21.11 0.00849458 53.4853 55588.18 0.00 60562.58 59508.29
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 24034.761 24034.761 1.055878 0.00021027 686.775 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 24034.76 24034.76 1.055878 21.11 14.42 0.00768487 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00768487 48.4498 24034.91 0.00 25910.27 25910.27
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 59544.639 -999.000 5.166180 0.00212676 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 unknown 8/21 15:00:00 59544.64 55972.76 5.166180 21.69 15.60 0.00876599 12.80 11.93 0.00850000 31.30 0.00823349 18.45 0.0000 21.11 0.00876599 55.1727 51784.34 0.00 60590.69 56012.06
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 24049.922 24049.922 1.056544 0.00021040 687.208 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 24049.92 24049.92 1.056544 21.11 14.42 0.00768497 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00768497 48.4504 24050.07 0.00 25926.62 25926.62
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 9124.617 -999.000 0.831655 0.00032590 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 unknown 8/21 09:30:00 9124.62 8950.15 0.831655 21.69 15.44 0.00858126 12.80 11.93 0.00850000 27.16 0.00822694 17.07 0.0000 21.11 0.00858126 54.0249 8336.57 0.00 9288.91 8949.90
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 4140.328 4140.328 0.181888 0.00003622 118.308 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4140.33 4140.33 0.181888 21.11 14.40 0.00765841 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00765841 48.2855 4140.38 0.00 4463.40 4463.40
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 8758.617 -999.000 0.797561 0.00031283 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 unknown 8/21 09:10:00 8758.62 8584.34 0.797561 21.69 15.44 0.00858462 12.80 11.93 0.00850000 26.66 0.00822614 16.89 0.0000 21.11 0.00858462 54.0458 7994.81 0.00 8916.25 8584.22
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 4140.483 4140.483 0.181895 0.00003622 118.313 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4140.48 4140.48 0.181895 21.11 14.40 0.00765845 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00765845 48.2857 4140.53 0.00 4463.57 4463.57
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 10588.304 10588.304 0.741696 0.00009263 243.135 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 10588.30 10588.30 0.741696 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00773711 49.1085 6746.85 0.00 10645.12 10645.12
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 2690.844 -999.000 0.246072 0.00009611 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 unknown 8/21 16:20:00 2690.84 2646.95 0.246072 21.69 15.43 0.00856912 12.80 11.93 0.00850000 30.53 0.00823226 18.20 0.0000 21.11 0.00856912 53.9495 2466.64 0.00 2739.38 2646.75
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 1278.796 1278.796 0.056179 0.00001119 36.540 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1278.80 1278.80 0.056179 21.11 14.45 0.00771720 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00771720 48.6517 1278.81 0.00 1378.58 1378.58
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2575.487 -999.000 0.235326 0.00009199 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown 8/21 16:30:00 2575.49 2531.66 0.235326 21.69 15.43 0.00857216 12.80 11.93 0.00850000 30.41 0.00823207 18.16 0.0000 21.11 0.00857216 53.9683 2358.93 0.00 2621.92 2531.50
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 1278.342 1278.342 0.056159 0.00001118 36.527 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1278.34 1278.34 0.056159 21.11 14.45 0.00771713 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00771713 48.6512 1278.36 0.00 1378.09 1378.09
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 12681.079 -999.000 1.137458 0.00045293 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown 8/21 13:30:00 12681.08 12268.15 1.137458 21.69 15.49 0.00864030 12.80 11.93 0.00850000 31.08 0.00823314 18.38 0.0000 21.11 0.00864030 54.3922 11401.66 0.00 12907.59 12270.73
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 6171.357 6171.357 0.271114 0.00005399 176.337 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6171.36 6171.36 0.271114 21.11 14.46 0.00772897 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00772897 48.7248 6171.42 0.00 6652.92 6652.92
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10341.953 10341.953 1.169494 0.00009048 223.897 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 10341.95 10341.95 1.169494 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00778721 49.4228 4284.35 0.00 10399.37 10399.37
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10722.379 10722.379 1.226728 0.00009380 231.884 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 10722.38 10722.38 1.226728 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00779092 49.4462 4368.38 0.00 10781.92 10781.92
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 6853.181 6853.181 1.221652 0.00005995 143.526 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 6853.18 6853.18 1.221652 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00490514 31.2793 562.44 0.00 6891.64 6891.64
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 6495.129 6495.129 0.380217 0.00005682 154.038 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 6495.13 6495.13 0.380217 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00782122 49.6360 4525.61 0.00 6529.65 6529.65
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 459657.946 -999.000 21.112167 0.01641792 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 459657.95 434532.88 21.112167 28.03 17.90 0.00888632 10.94 10.94 0.00850000 31.30 0.00823349 18.45 55.2357 23.99 0.00966535 50.9909 284934.11 0.00 465887.15 418616.82
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 97025.271 97025.271 6.333650 0.00084882 1739.018 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 97025.27 97025.27 6.333650 3.80 3.80 0.00505843 16.70 13.02 0.00800000 3.80 0.00505843 3.80 184.1191 21.22 0.00705317 44.2087 42135.47 0.00 98560.12 98560.12
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 47946.248 -999.000 2.051317 0.00171253 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 47946.25 47946.25 2.051317 31.30 18.45 0.00823349 11.91 11.29 0.00823349 31.30 0.00823349 18.45 99.9965 21.11 0.00862658 54.3062 151487.96 0.00 48572.77 47970.12
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 9427.247 9427.247 0.615395 0.00008247 168.968 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 9427.25 9427.25 0.615395 3.80 3.80 0.00505843 16.70 13.02 0.00800000 3.80 0.00505843 3.80 333.3216 21.11 0.00768513 48.4514 73377.03 0.00 9576.38 9576.38



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 7002.683 7002.683 1.351396 0.00006126 146.029 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 2.4286 2.477496   12/21 00:10:00 unknown unknown   12/21 00:10:00 Sensible 7002.68 7002.68 1.0000 1.59705040 1.351396 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.06125627 60.00 32.22 27.78 0.000 7002.68 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 50.7558 0.00 0.00 7042.04 7042.04 1.59705040 16.60 13.15 0.00800000 36934.7 20.92 14.82 0.00800000 41344.1
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 2809.354 2809.354 0.178681 0.00002458 65.582 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 0.9743 0.993928 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2809.35 2809.35 1.0000 0.21116155 0.178681 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.02457494 60.00 32.22 27.78 0.000 2809.35 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00767295 21.00 0.00767295 48.7070 1884.07 0.00 2824.35 2824.35 0.21116155 16.60 13.15 0.00800000 36934.7 29.72 17.94 0.00800000 50310.0
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1326.934 1326.934 0.131353 0.00001161 29.112 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 0.4602 0.469459 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1326.93 1326.93 1.0000 0.15522968 0.131353 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.01160741 60.00 32.22 27.78 0.000 1326.93 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00763711 21.00 0.00763711 48.4817 646.75 0.00 1334.27 1334.27 0.15522968 16.60 13.15 0.00800000 36934.7 25.03 16.32 0.00800000 45530.2
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 1826.682 1826.682 0.124542 0.00001598 42.131 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 0.6335 0.646266 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1826.68 1826.68 1.0000 0.14718093 0.124542 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.01597898 60.00 32.22 27.78 0.000 1826.68 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00754698 21.00 0.00754698 47.9164 1181.88 0.00 1836.47 1836.47 0.14718093 16.60 13.15 0.00800000 36934.7 28.84 17.65 0.00800000 49412.4
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1010.377 1010.377 0.059237 0.00000884 23.955 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 0.3504 0.357464 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1010.38 1010.38 1.0000 0.07000516 0.059237 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.00883832 60.00 32.22 27.78 0.000 1010.38 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00755893 21.00 0.00755893 47.9913 703.67 0.00 1015.75 1015.75 0.07000516 16.60 13.15 0.00800000 36934.7 30.83 18.31 0.00800000 51444.3
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 10967.837 10967.837 1.817922 0.00009595 230.681 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 3.8038 3.880337 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 10967.84 10967.84 1.0000 2.14838088 1.817922 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.09594163 60.00 32.22 27.78 0.000 10967.84 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00753315 21.00 0.00753315 47.8301 1556.31 0.00 11029.29 11029.29 2.14838088 16.60 13.15 0.00800000 36934.7 21.63 15.09 0.00800000 42068.5
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 8715.339 8715.339 0.766035 0.00007625 193.823 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 3.0226 3.083421 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 8715.34 8715.34 1.0000 0.90528376 0.766035 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.07623781 60.00 32.22 27.78 0.000 8715.34 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00770916 21.00 0.00770916 48.9338 4748.19 0.00 8762.67 8762.67 0.90528376 16.60 13.15 0.00800000 36934.7 26.09 16.70 0.00800000 46614.2
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 24162.543 24162.543 2.486780 0.00021138 527.941 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 8.3799 8.548523 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 24162.54 24162.54 1.0000 2.93882303 2.486780 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.21136290 60.00 32.22 27.78 0.000 24162.54 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00765707 21.00 0.00765707 48.6068 11284.84 0.00 24296.34 24296.34 2.93882303 16.60 13.15 0.00800000 36934.7 24.71 16.21 0.00800000 45202.1
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 10401.022 -999.000 0.950535 0.00037149 -999.000 -999.0000 1.00000 1.00000 1020.7739 1004.8586 1.1818 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.950535 1.12332230   4197.9300 999.8980 24.38735896 13.37 6.70 6.67 682850.76 1.5232 1.523148 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 unknown unknown unknown 8/21 16:20:00 Sensible 10401.02 10225.69 1.0000 1.12332230 0.950535 21.69 15.43 0.00857148 43581.4 12.80 11.93 0.00850000 34322.2 0.37145558 6.70 13.37 6.67 0.000 10401.02 30.53 0.00823226 18.20 0.00000000 0.0000 21.11 0.00857148 21.11 0.00857148 53.9641 9528.24 0.00 10588.55 10225.00 1.12332230 21.69 15.62 0.00857148 43581.4 12.78 12.03 0.00844328 34155.3
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 4141.151 4141.151 0.181924 0.00003623 118.332 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.950535 1.12332230   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 1.4362 1.465108 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4141.15 4141.15 1.0000 0.21499445 0.181924 21.11 14.40 0.00765847 40666.8 40.00 20.96 0.00800000 60796.0 0.03622490 60.00 32.22 27.78 0.000 4141.15 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00765847 21.11 0.00765847 48.2859 4141.20 0.00 4464.29 4464.29 0.21499445 16.60 12.82 0.00765847 36070.1 36.98 20.01 0.00765847 56834.7
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 9984.080 -999.000 0.911701 0.00035660 -999.000 -999.0000 1.00000 1.00000 1020.7794 1004.8586 1.1818 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.911701 1.07742879   4197.9300 999.8980 24.38735896 13.37 6.70 6.67 682850.76 1.4621 1.462090 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown unknown unknown 8/21 16:30:00 Sensible 9984.08 9809.01 1.0000 1.07742879 0.911701 21.69 15.44 0.00857440 43588.8 12.80 11.93 0.00850000 34322.2 0.35656517 6.70 13.37 6.67 0.000 9984.08 30.41 0.00823207 18.16 0.00000000 0.0000 21.11 0.00857440 21.11 0.00857440 53.9822 9138.96 0.00 10164.02 9808.47 1.07742879 21.69 15.62 0.00857440 43588.8 12.78 12.03 0.00844369 34155.2
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 4141.306 4141.306 0.181931 0.00003623 118.336 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.911701 1.07742879   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 1.4363 1.465162 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4141.31 4141.31 1.0000 0.21500247 0.181931 21.11 14.40 0.00765851 40666.9 40.00 20.96 0.00800000 60796.0 0.03622625 60.00 32.22 27.78 0.000 4141.31 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00765851 21.11 0.00765851 48.2861 4141.36 0.00 4464.45 4464.45 0.21500247 16.60 12.82 0.00765851 36070.1 36.98 20.01 0.00765851 56834.8
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 59489.454 -999.000 5.545226 0.00212479 -999.000 -999.0000 1.00000 1.00000 1020.6310 1004.8586 1.1818 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.545226 6.55323009   4197.9300 999.8980 24.38735896 13.37 6.70 6.67 682850.76 8.7119 8.711763 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown unknown unknown 8/21 13:30:00 Sensible 59489.45 59489.45 1.0000 6.55323009 5.545226 21.69 15.37 0.00849458 43386.4 12.80 11.93 0.00849458 34308.5 2.12456903 6.70 13.37 6.67 0.000 59489.45 31.08 0.00823314 18.38 0.00000000 0.0000 21.11 0.00849458 21.11 0.00849458 53.4853 55588.18 0.00 60562.58 59508.29 6.55323009 21.69 15.55 0.00849458 43386.4 12.80 12.03 0.00843086 34144.8
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 24034.761 24034.761 1.055878 0.00021027 686.775 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.545226 6.55323009   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 8.3356 8.503315 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 24034.76 24034.76 1.0000 1.24781453 1.055878 21.11 14.42 0.00768487 40734.0 40.00 20.96 0.00800000 60796.0 0.21024512 60.00 32.22 27.78 0.000 24034.76 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00768487 21.11 0.00768487 48.4498 24034.91 0.00 25910.27 25910.27 1.24781453 16.60 12.84 0.00768487 36136.9 36.97 20.03 0.00768487 56901.4
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 59544.639 -999.000 5.166180 0.00212676 -999.000 -999.0000 1.00000 1.00000 1021.1355 1004.8586 1.1818 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.166180 6.10528117   4197.9300 999.8980 24.38735896 13.37 6.70 6.67 682850.76 8.7200 8.719845 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 unknown unknown unknown 8/21 15:00:00 Sensible 59544.64 55972.76 1.0000 6.10528117 5.166180 21.69 15.60 0.00876599 44075.2 12.80 11.93 0.00850000 34322.2 2.12653988 6.70 13.37 6.67 0.000 59544.64 31.30 0.00823349 18.45 0.00000000 0.0000 21.11 0.00876599 21.11 0.00876599 55.1727 51784.34 0.00 60590.69 56012.06 6.10528117 21.69 15.79 0.00876599 44075.2 12.71 12.03 0.00846893 34150.9
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 24049.922 24049.922 1.056544 0.00021040 687.208 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.166180 6.10528117   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 8.3408 8.508679 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 24049.92 24049.92 1.0000 1.24860165 1.056544 21.11 14.42 0.00768497 40734.3 40.00 20.96 0.00800000 60796.0 0.21037775 60.00 32.22 27.78 0.000 24049.92 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00768497 21.11 0.00768497 48.4504 24050.07 0.00 25926.62 25926.62 1.24860165 16.60 12.84 0.00768497 36137.1 36.97 20.03 0.00768497 56901.7
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 9124.617 -999.000 0.831655 0.00032590 -999.000 -999.0000 1.00000 1.00000 1020.7921 1004.8586 1.1818 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.831655 0.98283208   4197.9300 999.8980 24.38735896 13.37 6.70 6.67 682850.76 1.3363 1.336229 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 unknown unknown unknown 8/21 09:30:00 Sensible 9124.62 8950.15 1.0000 0.98283208 0.831655 21.69 15.44 0.00858126 43606.2 12.80 11.93 0.00850000 34322.2 0.32587085 6.70 13.37 6.67 0.000 9124.62 27.16 0.00822694 17.07 0.00000000 0.0000 21.11 0.00858126 21.11 0.00858126 54.0249 8336.57 0.00 9288.91 8949.90 0.98283208 21.69 15.63 0.00858126 43606.2 12.77 12.03 0.00844463 34155.0
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 4140.328 4140.328 0.181888 0.00003622 118.308 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.831655 0.98283208   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 1.4359 1.464817 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4140.33 4140.33 1.0000 0.21495174 0.181888 21.11 14.40 0.00765841 40666.6 40.00 20.96 0.00800000 60796.0 0.03621770 60.00 32.22 27.78 0.000 4140.33 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00765841 21.11 0.00765841 48.2855 4140.38 0.00 4463.40 4463.40 0.21495174 16.60 12.82 0.00765841 36069.9 36.98 20.01 0.00765841 56834.6
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 8758.617 -999.000 0.797561 0.00031283 -999.000 -999.0000 1.00000 1.00000 1020.7984 1004.8586 1.1818 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.797561 0.94254084   4197.9300 999.8980 24.38735896 13.37 6.70 6.67 682850.76 1.2827 1.282631 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 unknown unknown unknown 8/21 09:10:00 Sensible 8758.62 8584.34 1.0000 0.94254084 0.797561 21.69 15.44 0.00858462 43614.8 12.80 11.93 0.00850000 34322.2 0.31279974 6.70 13.37 6.67 0.000 8758.62 26.66 0.00822614 16.89 0.00000000 0.0000 21.11 0.00858462 21.11 0.00858462 54.0458 7994.81 0.00 8916.25 8584.22 0.94254084 21.69 15.63 0.00858462 43614.8 12.77 12.03 0.00844509 34155.0
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 4140.483 4140.483 0.181895 0.00003622 118.313 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.797561 0.94254084   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 1.4360 1.464871 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4140.48 4140.48 1.0000 0.21495977 0.181895 21.11 14.40 0.00765845 40666.7 40.00 20.96 0.00800000 60796.0 0.03621906 60.00 32.22 27.78 0.000 4140.48 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00765845 21.11 0.00765845 48.2857 4140.53 0.00 4463.57 4463.57 0.21495977 16.60 12.82 0.00765845 36070.0 36.98 20.01 0.00765845 56834.6
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 10588.304 10588.304 0.741696 0.00009263 243.135 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 3.6722 3.746061 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 10588.30 10588.30 1.0000 0.87652038 0.741696 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.09262165 60.00 32.22 27.78 0.000 10588.30 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00773711 21.00 0.00773711 49.1085 6746.85 0.00 10645.12 10645.12 0.87652038 16.60 13.15 0.00800000 36934.7 28.51 17.54 0.00800000 49079.5
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 2690.844 -999.000 0.246072 0.00009611 -999.000 -999.0000 1.00000 1.00000 1020.7696 1004.8586 1.1818 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.246072 0.29080206   4197.9300 999.8980 24.38735896 13.37 6.70 6.67 682850.76 0.3941 0.394053 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 unknown unknown unknown 8/21 16:20:00 Sensible 2690.84 2646.95 1.0000 0.29080206 0.246072 21.69 15.43 0.00856912 43575.4 12.80 11.93 0.00850000 34322.2 0.09609913 6.70 13.37 6.67 0.000 2690.84 30.53 0.00823226 18.20 0.00000000 0.0000 21.11 0.00856912 21.11 0.00856912 53.9495 2466.64 0.00 2739.38 2646.75 0.29080206 21.69 15.62 0.00856912 43575.4 12.78 12.03 0.00844296 34155.3
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 1278.796 1278.796 0.056179 0.00001119 36.540 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.246072 0.29080206   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 0.4435 0.452428 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1278.80 1278.80 1.0000 0.06639074 0.056179 21.11 14.45 0.00771720 40816.0 40.00 20.96 0.00800000 60796.0 0.01118633 60.00 32.22 27.78 0.000 1278.80 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00771720 21.11 0.00771720 48.6517 1278.81 0.00 1378.58 1378.58 0.06639074 16.60 12.88 0.00771720 36218.8 36.97 20.06 0.00771720 56983.4
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2575.487 -999.000 0.235326 0.00009199 -999.000 -999.0000 1.00000 1.00000 1020.7752 1004.8586 1.1818 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.235326 0.27810343   4197.9300 999.8980 24.38735896 13.37 6.70 6.67 682850.76 0.3772 0.377160 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown unknown unknown 8/21 16:30:00 Sensible 2575.49 2531.66 1.0000 0.27810343 0.235326 21.69 15.43 0.00857216 43583.1 12.80 11.93 0.00850000 34322.2 0.09197931 6.70 13.37 6.67 0.000 2575.49 30.41 0.00823207 18.16 0.00000000 0.0000 21.11 0.00857216 21.11 0.00857216 53.9683 2358.93 0.00 2621.92 2531.50 0.27810343 21.69 15.62 0.00857216 43583.1 12.78 12.03 0.00844338 34155.2
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 1278.342 1278.342 0.056159 0.00001118 36.527 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.235326 0.27810343   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 0.4433 0.452268 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1278.34 1278.34 1.0000 0.06636716 0.056159 21.11 14.45 0.00771713 40815.8 40.00 20.96 0.00800000 60796.0 0.01118235 60.00 32.22 27.78 0.000 1278.34 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00771713 21.11 0.00771713 48.6512 1278.36 0.00 1378.09 1378.09 0.06636716 16.60 12.88 0.00771713 36218.6 36.97 20.06 0.00771713 56983.2
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 12681.079 -999.000 1.137458 0.00045293 -999.000 -999.0000 1.00000 1.00000 1020.9019 1004.8586 1.1818 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.137458 1.34422388   4197.9300 999.8980 24.38735896 13.37 6.70 6.67 682850.76 1.8571 1.857044 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown unknown unknown 8/21 13:30:00 Sensible 12681.08 12268.15 1.0000 1.34422388 1.137458 21.69 15.49 0.00864030 43756.0 12.80 11.93 0.00850000 34322.2 0.45288409 6.70 13.37 6.67 0.000 12681.08 31.08 0.00823314 18.38 0.00000000 0.0000 21.11 0.00864030 21.11 0.00864030 54.3922 11401.66 0.00 12907.59 12270.73 1.34422388 21.69 15.68 0.00864030 43756.0 12.75 12.03 0.00845264 34153.7
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 6171.357 6171.357 0.271114 0.00005399 176.337 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.137458 1.34422388   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 2.1403 2.183379 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6171.36 6171.36 1.0000 0.32039681 0.271114 21.11 14.46 0.00772897 40845.9 40.00 20.96 0.00800000 60796.0 0.05398421 60.00 32.22 27.78 0.000 6171.36 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00772897 21.11 0.00772897 48.7248 6171.42 0.00 6652.92 6652.92 0.32039681 16.60 12.89 0.00772897 36248.5 36.97 20.07 0.00772897 57013.2
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 10341.953 10341.953 1.169494 0.00009048 223.897 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 3.5867 3.658904 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 10341.95 10341.95 1.0000 1.38208281 1.169494 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.09046669 60.00 32.22 27.78 0.000 10341.95 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00778721 21.00 0.00778721 49.4228 4284.35 0.00 10399.37 10399.37 1.38208281 16.60 13.15 0.00800000 36934.7 23.98 15.95 0.00800000 44459.1
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 10722.379 10722.379 1.226728 0.00009380 231.884 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 3.7187 3.793496 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 Sensible 10722.38 10722.38 1.0000 1.44972072 1.226728 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.09379448 60.00 32.22 27.78 0.000 10722.38 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00779092 21.00 0.00779092 49.4462 4368.38 0.00 10781.92 10781.92 1.44972072 16.60 13.15 0.00800000 36934.7 23.89 15.92 0.00800000 44372.0
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 6853.181 6853.181 1.221652 0.00005995 143.526 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 2.3768 2.424603 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 Sensible 6853.18 6853.18 1.0000 1.44372168 1.221652 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.05994850 60.00 32.22 27.78 0.000 6853.18 3.80 0.00505843 3.80 0.00000000 0.0000 18.06 0.00490514 21.00 0.00490514 31.2793 562.44 0.00 6891.64 6891.64 1.44372168 16.60 13.15 0.00800000 36934.7 21.28 14.96 0.00800000 41708.3
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 6495.129 6495.129 0.380217 0.00005682 154.038 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 2.2526 2.297927 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 Sensible 6495.13 6495.13 1.0000 0.44933287 0.380217 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.05681642 60.00 32.22 27.78 0.000 6495.13 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00782122 21.00 0.00782122 49.6360 4525.61 0.00 6529.65 6529.65 0.44933287 16.60 13.15 0.00800000 36934.7 30.85 18.32 0.00800000 51466.6
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 459657.946 -999.000 21.112167 0.01641792 -999.000 -999.0000 1.00000 1.00000 1021.3592 1004.8586 1.1818 VAV WITH REHEAT FAN Fan:VariableVolume 21.112167 24.94990805   4197.9300 999.8980 24.38735896 13.37 6.70 6.67 682850.76 67.3146 67.314554 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 Sensible 459657.95 434532.88 1.0000 24.94990805 21.112167 28.03 17.90 0.00888632 50850.8 10.94 10.94 0.00850000 32427.5 16.41624200 6.70 13.37 6.67 47304.736 412353.21 31.30 0.00823349 18.45 11.66146000 55.2357 23.99 0.00969219 23.99 0.00966535 50.9909 284934.11 0.00 465887.15 418616.82 24.94990805 28.03 18.10 0.00888632 50850.8 11.60 11.23 0.00813524 32177.9
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 97025.271 97025.271 6.333650 0.00084882 1739.018 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 VAV WITH REHEAT FAN Fan:VariableVolume 21.112167 24.94990805   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 33.6496 34.326800 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:20:00 Sensible 97025.27 97025.27 1.0000 7.48497241 6.333650 3.80 3.80 0.00505843 16505.0 16.70 13.02 0.00800000 37036.7 0.84873281 60.00 32.22 27.78 0.000 97025.27 3.80 0.00505843 3.80 11.66146000 184.1191 18.36 0.00726635 21.22 0.00705317 44.2087 42135.47 0.00 98560.12 98560.12 7.48497241 2.80 2.80 0.00505843 15490.7 15.78 9.78 0.00505843 28658.4
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 47946.248 -999.000 2.051317 0.00171253 -999.000 -999.0000 1.00000 1.00000 1020.1456 1004.8586 1.1818 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.42411771   4197.9300 999.8980 24.38735896 13.37 6.70 6.67 682850.76 7.0215 7.021483 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 Sensible 47946.25 47946.25 1.0000 2.42420295 2.051317 31.30 18.45 0.00823349 52522.0 11.91 11.29 0.00823349 32743.9 1.71235419 6.70 13.37 6.67 2195.006 45751.24 31.30 0.00823349 18.45 2.05124512 99.9965 21.11 0.00861962 21.11 0.00862658 54.3062 151487.96 0.00 48572.77 47970.12 2.42420295 31.30 18.65 0.00823349 52522.0 11.90 11.35 0.00813496 32485.4
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 9427.247 9427.247 0.615395 0.00008247 168.968 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.42411771   4197.9300 999.8980 2.47250776 54.44 82.22 27.78 288340.14 3.2695 3.335288 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 9427.25 9427.25 1.0000 0.72726088 0.615395 3.80 3.80 0.00505843 16505.0 16.70 13.02 0.00800000 37036.7 0.08246526 60.00 32.22 27.78 0.000 9427.25 3.80 0.00505843 3.80 2.05124512 333.3216 21.11 0.00768378 21.11 0.00768513 48.4514 73377.03 0.00 9576.38 9576.38 0.72726088 2.80 2.80 0.00505843 15490.7 15.78 9.78 0.00505843 28658.4



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 21.11 -      
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.003540 0.000914 0.000000 0.000000 Sum   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.003540 0.000305 0.000000 0.000000 Sum   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 141.00 7679.67 0.00
RETAIL_1_FLR_1 802.83 7350.33 13.67
RETAIL_2_FLR_1 1098.33 6711.67 181.17
MECH_FLR_1 5.00 8502.83 0.00
STORAGE_FLR_1 0.00 8753.83 0.00
LAUNDRY_FLR_1 7537.17 3462.00 2912.00
CAFE_FLR_1 3378.00 4923.50 1133.33
LOBBY_FLR_1 2702.50 4832.50 906.33
ROOM_1_FLR_3 75.33 8288.33 71.83
ROOM_2_FLR_3 246.50 8491.17 246.50
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 233.17 8760.00 233.17
ROOM_5_FLR_3 76.33 8468.83 76.33
ROOM_6_FLR_3 202.17 8643.67 202.17
CORRIDOR_FLR_3 243.17 8714.83 242.17
ROOM_1_FLR_6 302.17 8184.50 268.83
ROOM_2_FLR_6 595.17 8412.50 589.00
ROOM_3_MULT9_FLR_6 53.83 8106.83 32.17
BANQUET_FLR_6 6151.17 1790.67 898.67
DINING_FLR_6 7054.00 1063.67 791.83
KITCHEN_FLR_6 8514.50 6415.33 6378.17
CORRIDOR_FLR_6 42.67 8191.33 2.67
Facility 8720.50 8760.00 7353.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 3.67 0.00 3.67
ROOM_2_FLR_3 0.00 1.00 0.00 1.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.33 0.00 0.33
ROOM_5_FLR_3 0.00 3.50 0.00 3.50
ROOM_6_FLR_3 0.00 2.50 0.00 2.50
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 5.00 0.00 5.00
ROOM_2_FLR_6 0.00 1.33 0.00 1.33
ROOM_3_MULT9_FLR_6 0.00 18.00 0.00 18.00
BANQUET_FLR_6 0.00 0.00 0.00 0.00
DINING_FLR_6 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 0.00 22.50 0.00 22.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.78 106.50 4826.41 1.025 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 2.487 0.136 0.000 0.000
RETAIL_2_FLR_1 7.27 12.54 307.76 1.563 0.045 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.695 0.051 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.573 0.050 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 24.150 0.145 0.000 0.000
CAFE_FLR_1 82.55 142.30 748.35 3.813 0.107 0.000 0.000
LOBBY_FLR_1 245.05 422.44 5183.56 1.791 0.044 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.475 0.176 0.000 0.092
ROOM_2_FLR_3 0.95 1.50 118.93 0.474 0.175 0.000 0.091
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.538 0.078 0.000 0.143
ROOM_5_FLR_3 0.95 1.50 118.94 0.475 0.176 0.000 0.093
ROOM_6_FLR_3 0.95 1.50 118.93 0.475 0.175 0.000 0.091
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.568 0.021 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.475 0.176 0.000 0.104
ROOM_2_FLR_6 0.95 1.50 118.93 0.475 0.176 0.000 0.102
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.539 0.143 0.000 0.165
BANQUET_FLR_6 144.96 249.90 1010.89 4.909 0.051 0.000 0.000
DINING_FLR_6 144.96 249.90 1010.89 5.289 0.051 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 22.153 0.146 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 1.100 0.036 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.78 106.50 4826.41 0.965 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 2.317 0.003 0.000 0.000
RETAIL_2_FLR_1 7.27 12.54 307.76 1.474 0.001 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.660 0.001 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.544 0.001 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 20.261 0.003 0.000 0.000
CAFE_FLR_1 82.55 142.30 748.35 3.541 0.002 0.000 0.000
LOBBY_FLR_1 245.05 422.44 5183.56 1.657 0.001 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.463 0.004 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.462 0.004 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.526 0.002 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.464 0.004 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.463 0.004 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.539 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.463 0.004 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.462 0.004 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.526 0.003 0.000 0.000
BANQUET_FLR_6 144.96 249.90 1010.89 4.153 0.001 0.000 0.000
DINING_FLR_6 144.96 249.90 1010.89 4.361 0.001 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 13.534 0.003 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 1.046 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.78 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.27 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.55 142.30 748.35 188.86 0.0000 0.173
LOBBY_FLR_1 VAV WITH REHEAT 245.05 422.44 5183.56 1308.19 0.0000 0.399
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 144.96 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 144.96 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.11 1604.23 35184.81 11345.29 0.0000 135.585


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 42428738.66 0.00 42428738.66 0.00 42428738.66 26946214.98 0.00 0.00 8760.00 0.00
RETAIL_1_FLR_1 5689291.46 0.00 5689291.46 310101.36 5999392.81 2498216.28 0.00 0.00 8760.00 0.00
RETAIL_2_FLR_1 4125288.72 0.00 4125288.72 119699.52 4244988.24 2892943.94 0.00 0.00 8760.00 0.00
MECH_FLR_1 3892113.81 0.00 3892113.81 282898.54 4175012.35 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 1851209.97 0.00 1851209.97 163216.88 2014426.85 1821682.01 1145.94 1101.61 6512.45 0.00
LAUNDRY_FLR_1 64130195.81 0.00 64130195.81 386283.51 64516479.33 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 24434692.83 0.00 24434692.83 685496.60 25120189.43 14544917.54 0.00 0.00 8760.00 0.00
LOBBY_FLR_1 79433436.34 0.00 79433436.34 1958620.37 81392056.71 39585427.43 0.00 0.00 8760.00 0.00
ROOM_1_FLR_3 1946875.62 94539.83 2041415.45 179991.83 2221407.27 1946875.62 0.00 7138.83 1621.17 0.00
ROOM_2_FLR_3 1946647.51 93368.59 2040016.11 179978.09 2219994.20 1946647.51 0.00 7138.83 1621.17 0.00
ROOM_3_MULT19_FLR_3 26397887.27 105375.58 26503262.85 50219.74 26553482.59 26397887.27 0.00 7150.67 1609.33 8760.00
ROOM_4_MULT19_FLR_3 26405105.73 92216.18 26497321.91 50233.47 26547555.38 26405105.73 0.00 7175.80 1584.20 0.00
ROOM_5_FLR_3 1946875.62 94797.57 2041673.19 179991.83 2221665.02 1946875.62 0.00 7138.83 1621.17 0.00
ROOM_6_FLR_3 1946647.51 93614.96 2040262.47 179978.09 2220240.57 1946647.51 0.00 7138.83 1621.17 0.00
CORRIDOR_FLR_3 23178623.16 0.00 23178623.16 217646.33 23396269.49 14972100.18 0.00 0.00 8760.00 0.00
ROOM_1_FLR_6 486718.90 106408.24 593127.14 180028.86 773156.00 486718.90 0.00 7138.83 1621.17 0.00
ROOM_2_FLR_6 486661.88 104937.98 591599.86 180015.12 771614.98 486661.88 0.00 7138.83 1621.17 0.00
ROOM_3_MULT9_FLR_6 3126920.42 106148.55 3233068.97 92109.06 3325178.03 3126920.42 0.00 7139.00 1621.00 0.00
BANQUET_FLR_6 42376069.74 0.00 42376069.74 439585.22 42815654.96 37458366.31 3543.83 299.35 4916.82 0.00
DINING_FLR_6 45658373.76 0.00 45658373.76 439585.22 46097958.99 37458366.31 0.00 0.00 8760.00 0.00
KITCHEN_FLR_6 59603430.71 0.00 59603430.71 393530.69 59996961.40 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 11887088.77 0.00 11887088.77 385165.88 12272254.65 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.46E+10 17688941.13 0.46E+10 18137997.94 0.46E+10 0.43E+10 4659.09 7261.15 8760.00 8760.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.3454 0.0000 1.3454 0.0000 1.3454 0.8545 0.00 0.00 8760.00
RETAIL_1_FLR_1 0.1804 0.0000 0.1804 0.0098 0.1902 0.0792 0.00 0.00 8760.00
RETAIL_2_FLR_1 0.1308 0.0000 0.1308 0.0038 0.1346 0.0917 0.00 0.00 8760.00
MECH_FLR_1 0.1234 0.0000 0.1234 0.0090 0.1324 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0587 0.0000 0.0587 0.0052 0.0639 0.0578 1145.94 1101.61 6512.45
LAUNDRY_FLR_1 2.0336 0.0000 2.0336 0.0122 2.0458 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.7748 0.0000 0.7748 0.0217 0.7966 0.4612 0.00 0.00 8760.00
LOBBY_FLR_1 2.5188 0.0000 2.5188 0.0621 2.5809 1.2552 0.00 0.00 8760.00
ROOM_1_FLR_3 0.0617 0.0030 0.0647 0.0057 0.0704 0.0617 0.00 7138.83 1621.17
ROOM_2_FLR_3 0.0617 0.0030 0.0647 0.0057 0.0704 0.0617 0.00 7138.83 1621.17
ROOM_4_MULT19_FLR_3 0.8373 0.0029 0.8402 0.0016 0.8418 0.8373 0.00 7175.80 1584.20
ROOM_5_FLR_3 0.0617 0.0030 0.0647 0.0057 0.0704 0.0617 0.00 7138.83 1621.17
ROOM_6_FLR_3 0.0617 0.0030 0.0647 0.0057 0.0704 0.0617 0.00 7138.83 1621.17
CORRIDOR_FLR_3 0.7350 0.0000 0.7350 0.0069 0.7419 0.4748 0.00 0.00 8760.00
ROOM_1_FLR_6 0.0154 0.0034 0.0188 0.0057 0.0245 0.0154 0.00 7138.83 1621.17
ROOM_2_FLR_6 0.0154 0.0033 0.0188 0.0057 0.0245 0.0154 0.00 7138.83 1621.17
ROOM_3_MULT9_FLR_6 0.0992 0.0034 0.1025 0.0029 0.1054 0.0992 0.00 7139.00 1621.00
BANQUET_FLR_6 1.3437 0.0000 1.3437 0.0139 1.3577 1.1878 3543.83 299.35 4916.82
DINING_FLR_6 1.4478 0.0000 1.4478 0.0139 1.4618 1.1878 0.00 0.00 8760.00
KITCHEN_FLR_6 1.8900 0.0000 1.8900 0.0125 1.9025 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.3769 0.0000 0.3769 0.0122 0.3892 0.1256 0.00 0.00 8760.00
Total Facility 80.7102 0.3070 81.0171 0.4541 81.4713 73.1130 4659.09 7261.15 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.57E+09 0.00 0.57E+09 0.19E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 90346581.89 891407.49 91237989.37 64690340.46 0.00 0.00 8760.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 18.0991 0.0000 18.0991 6.1430 0.00 0.00 8760.00
FLR_3_DOAS 2.8649 0.0283 2.8931 2.0513 0.00 0.00 8760.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 0.00 7724.90 0.00 0.00 0.00 1035.10 0.00 0.00 0.00
FLR_3_DOAS 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 0.0000 18.1620 0.0000 0.0000 0.0000 17.6479 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 2.8649 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1314
Defaulted Fields 1179
Fields with Defaults 3965
Autosized Fields 347
Autosizable Fields 400
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 5159.85 72090.71 13-MAY-05:00 360462.95 29-SEP-19:10
Electricity:Building 2519.39 32661.02 03-JUN-05:00 151906.32 02-JAN-20:10
Electricity:Zone:BASEMENT 323.72 3705.45 02-JAN-02:10 24299.15 02-JAN-20:10
Electricity:SpaceType:GENERAL 2512.30 32519.87 03-JUN-05:00 151664.99 02-JAN-20:10
InteriorLights:Electricity 767.29 6828.07 03-JUN-05:00 62892.57 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 173.46 1576.23 02-JAN-02:10 14185.34 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 767.29 6828.07 03-JUN-05:00 62892.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity 767.29 6828.07 03-JUN-05:00 62892.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 173.46 1576.23 02-JAN-02:10 14185.34 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 767.29 6828.07 03-JUN-05:00 62892.57 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 18.80 222.61 02-JAN-02:10 1390.02 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.61 78.27 02-JAN-02:10 704.41 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.61 78.27 02-JAN-02:10 704.41 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 21.77 257.78 02-JAN-02:10 1609.65 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.97 90.64 02-JAN-02:10 815.72 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.97 90.64 02-JAN-02:10 815.72 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 29.11 327.88 02-JAN-02:10 2199.84 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 16.64 151.16 02-JAN-02:10 1360.40 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 16.64 151.16 02-JAN-02:10 1360.40 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 6.38 76.28 02-JAN-02:10 469.87 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.78 25.30 02-JAN-02:10 227.72 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.78 25.30 02-JAN-02:10 227.72 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 72.30 1002.39 02-JAN-02:10 4930.01 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.37 39.69 02-JAN-02:10 357.21 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.37 39.69 02-JAN-02:10 357.21 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 32.44 373.53 13-MAY-05:00 2727.18 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 18.10 170.32 13-MAY-05:00 1761.91 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 18.10 170.32 13-MAY-05:00 1761.91 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 271.03 3225.37 03-JUN-05:00 20294.39 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 122.03 1113.96 03-JUN-05:00 10265.18 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 122.03 1113.96 03-JUN-05:00 10265.18 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 18.66 264.62 01-JAN-02:10 1227.54 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 18.66 264.59 01-JAN-02:10 1227.39 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 304.77 4565.05 01-JAN-02:10 20923.25 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 76.02 643.59 01-JAN-02:10 5851.22 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 76.02 643.59 01-JAN-02:10 5851.22 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 304.86 4566.30 01-JAN-02:10 20928.98 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 76.04 643.77 01-JAN-02:10 5852.82 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 76.04 643.77 01-JAN-02:10 5852.82 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 18.66 264.62 01-JAN-02:10 1227.54 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 18.66 264.59 01-JAN-02:10 1227.39 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 4.66 66.15 01-JAN-02:10 306.88 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.59 13.47 01-JAN-02:10 122.50 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.59 13.47 01-JAN-02:10 122.50 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 4.66 66.15 01-JAN-02:10 306.85 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.59 13.47 01-JAN-02:10 122.49 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.59 13.47 01-JAN-02:10 122.49 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 36.10 540.75 01-JAN-02:10 2478.43 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 9.00 76.24 01-JAN-02:10 693.10 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 9.00 76.24 01-JAN-02:10 693.10 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 210.69 2547.25 03-JUN-05:00 9841.96 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 34.84 297.95 03-JUN-05:00 3094.06 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 34.84 297.95 03-JUN-05:00 3094.06 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 210.69 2547.25 03-JUN-05:00 9841.96 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 34.84 297.95 03-JUN-05:00 3094.06 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 34.84 297.95 03-JUN-05:00 3094.06 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 454.16 6253.02 02-JAN-02:10 18944.06 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.33 121.09 02-JAN-02:10 1089.83 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.33 121.09 02-JAN-02:10 1089.83 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
InteriorEquipment:Electricity 1745.01 25691.80 02-JAN-02:10 89475.41 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1745.01 25691.80 02-JAN-02:10 89475.41 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 433.74 5990.78 01-JAN-00:10 16487.34 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
Refrigeration:Electricity 62.33 1114.62 03-FEB-23:30 3263.15 14-JUL-06:20
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 1184.87 2734.20 25-NOV-03:20 194311.18 16-OCT-10:50
LowTempRefrigeration:Refrigeration:Electricity 20.48 0.00 01-JAN-11:10 1892.65 30-SEP-10:50
MedTempRefrigeration:Refrigeration:Electricity 34.76 943.52 09-JAN-06:00 1203.19 11-FEB-14:10
Fans:Electricity 561.22 13222.12 20-FEB-04:30 37012.34 16-OCT-21:10
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 593.68 13802.23 20-FEB-04:30 38229.04 16-OCT-21:10
ExteriorEquipment:Electricity 651.48 9618.58 02-JAN-02:20 39726.11 18-JAN-07:20
Transformer:ExteriorEquipment:Electricity 32.45 553.76 27-MAY-05:00 1868.65 02-JAN-21:10
ElectricityPurchased:Facility 5159.85 72090.71 13-MAY-05:00 360462.95 29-SEP-19:10
ElectricityPurchased:Plant 5159.85 72090.71 13-MAY-05:00 360462.95 29-SEP-19:10
Cogeneration:ElectricityPurchased 5159.85 72090.71 13-MAY-05:00 360462.95 29-SEP-19:10
General:Cogeneration:ElectricityPurchased 5159.85 72090.71 13-MAY-05:00 360462.95 29-SEP-19:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 5159.85 72090.71 13-MAY-05:00 360462.95 29-SEP-19:10
ElectricityNet:Plant 5159.85 72090.71 13-MAY-05:00 360462.95 29-SEP-19:10
Cogeneration:ElectricityNet 5159.85 72090.71 13-MAY-05:00 360462.95 29-SEP-19:10
General:Cogeneration:ElectricityNet 5159.85 72090.71 13-MAY-05:00 360462.95 29-SEP-19:10
General:Fans:Electricity 561.22 13222.12 20-FEB-04:30 37012.34 16-OCT-21:10
ExteriorLights:Electricity 242.88 0.00 01-JAN-07:00 15448.40 01-JAN-00:10
General:ExteriorLights:Electricity 242.88 0.00 01-JAN-07:00 15448.40 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.91 18.80 01-JAN-00:10 188.00 01-JAN-07:10
WaterSystems:Electricity 90.75 1086.59 26-JUL-00:30 4738.61 05-JUN-18:10
Water Heater:WaterSystems:Electricity 90.75 1086.59 26-JUL-00:30 4738.61 05-JUN-18:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 878.32 0.00 01-JAN-00:10 180333.25 16-OCT-10:50
General:Cooling:Electricity 878.32 0.00 01-JAN-00:10 180333.25 16-OCT-10:50
Pumps:Electricity 160.57 48.96 08-OCT-07:10 7962.52 29-SEP-15:30
General:Pumps:Electricity 160.57 48.96 08-OCT-07:10 7962.52 29-SEP-15:30
WIRED_LTG_ELECTRICITY 27.01 0.00 01-JAN-00:10 2213.82 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 5637.55 29270.80 26-APR-01:10 517553.47 02-JAN-21:00
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 3848.71 15908.90 20-JAN-11:10 438939.99 29-MAR-22:00
WaterSystems:NaturalGas 2934.36 15908.90 06-JAN-16:10 246240.35 02-FEB-22:00
Water Heater:WaterSystems:NaturalGas 2934.36 15908.90 06-JAN-16:10 246240.35 02-FEB-22:00
Heating:NaturalGas 914.35 0.00 02-JAN-11:10 230195.00 08-JAN-07:00
Boiler:Heating:NaturalGas 914.35 0.00 02-JAN-11:10 230195.00 08-JAN-07:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 2801.74 0.00 01-JAN-00:10 506162.69 16-OCT-10:50
PlantLoopCoolingDemand:HVAC 2801.74 0.00 01-JAN-00:10 506162.69 16-OCT-10:50
CoolingCoils:PlantLoopCoolingDemand 2801.74 0.00 01-JAN-00:10 506162.69 16-OCT-10:50


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
Water Heater:WaterSystems:Water 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:10
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
Water Heater:WaterSystems:MainsWater 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:10
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 03-JAN-07:10
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 03-JAN-07:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 16791.35 143690.89 12-FEB-14:50 1981314.48 16-OCT-10:50
EnergyTransfer:Building 5204.12 106337.84 29-MAR-12:10 303713.36 16-OCT-15:20
EnergyTransfer:Zone:KITCHEN_FLR_6 726.38 11775.45 29-MAR-03:00 35333.77 30-SEP-10:50
Refrigeration:EnergyTransfer 185.67 4016.79 03-FEB-23:10 10368.60 14-JUL-06:20
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 92.84 2008.40 03-FEB-23:10 5184.30 14-JUL-06:20
General:Refrigeration:EnergyTransfer 92.84 2008.40 03-FEB-23:10 5184.30 14-JUL-06:20
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 92.84 2008.40 03-FEB-23:10 5184.30 14-JUL-06:20
EnergyTransfer:Plant 8157.38 21597.27 12-FEB-14:50 1225912.42 16-OCT-10:50
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.67 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 71.17 1780.57 09-JAN-06:00 2559.58 11-FEB-14:10
EnergyTransfer:Zone:BASEMENT 405.87 10536.90 26-JUN-13:20 19372.71 08-JAN-07:00
Heating:EnergyTransfer 10.60 0.00 01-JAN-08:10 21101.81 29-MAR-08:10
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 10.60 0.00 01-JAN-08:10 21101.81 29-MAR-08:10
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 5100.69 101455.84 29-MAR-04:00 301167.16 16-OCT-15:20
Cooling:EnergyTransfer:Zone:BASEMENT 405.87 10536.90 26-JUN-13:20 19372.71 08-JAN-07:00
General:Cooling:EnergyTransfer 5100.69 101455.84 29-MAR-04:00 301167.16 16-OCT-15:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 405.87 10536.90 26-JUN-13:20 19372.71 08-JAN-07:00
EnergyTransfer:Zone:RETAIL_1_FLR_1 45.98 6.45 30-MAR-05:10 4164.01 16-OCT-12:10
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.00 0.00 01-JAN-00:10 70.67 30-MAR-06:10
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.00 0.00 01-JAN-00:10 70.67 30-MAR-06:10
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 45.98 0.00 30-MAR-03:00 4164.01 16-OCT-12:10
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 45.98 0.00 30-MAR-03:00 4164.01 16-OCT-12:10
EnergyTransfer:Zone:RETAIL_2_FLR_1 38.81 834.98 29-MAR-12:10 2100.96 16-OCT-20:10
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 38.81 834.98 29-MAR-12:10 2100.96 16-OCT-20:10
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 38.81 834.98 29-MAR-12:10 2100.96 16-OCT-20:10
EnergyTransfer:Zone:MECH_FLR_1 33.80 531.19 30-MAR-04:00 1541.51 30-SEP-10:40
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:MECH_FLR_1 33.80 531.19 30-MAR-04:00 1541.51 30-SEP-10:40
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 33.80 531.19 30-MAR-04:00 1541.51 30-SEP-10:40
EnergyTransfer:Zone:STORAGE_FLR_1 15.68 176.32 29-MAR-12:00 733.64 30-SEP-10:40
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 15.68 176.32 29-MAR-12:00 733.64 30-SEP-10:40
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 15.68 176.32 29-MAR-12:00 733.64 30-SEP-10:40
EnergyTransfer:Zone:LAUNDRY_FLR_1 606.19 9957.15 30-MAR-04:00 38524.41 29-SEP-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 606.19 9957.15 30-MAR-04:00 38524.41 29-SEP-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 606.19 9957.15 30-MAR-04:00 38524.41 29-SEP-20:00
EnergyTransfer:Zone:CAFE_FLR_1 235.67 2421.47 29-MAR-12:10 14301.89 19-NOV-11:00
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 235.67 2421.47 29-MAR-12:10 14301.89 19-NOV-11:00
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 235.67 2421.47 29-MAR-12:10 14301.89 19-NOV-11:00
EnergyTransfer:Zone:LOBBY_FLR_1 789.75 16852.65 29-MAR-11:00 40238.61 16-OCT-20:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 789.75 16852.65 29-MAR-11:00 40238.61 16-OCT-20:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 789.75 16852.65 29-MAR-11:00 40238.61 16-OCT-20:10
EnergyTransfer:Zone:ROOM_1_FLR_3 52.97 0.03 04-NOV-03:00 11064.59 15-OCT-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 1.04 0.00 01-JAN-08:10 2909.71 29-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 1.04 0.00 01-JAN-08:10 2909.71 29-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 51.93 0.00 01-JAN-00:10 11064.59 15-OCT-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 51.93 0.00 01-JAN-00:10 11064.59 15-OCT-15:10
EnergyTransfer:Zone:ROOM_2_FLR_3 43.16 0.02 20-APR-03:30 9571.88 16-OCT-15:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 2.13 0.00 01-JAN-08:10 2884.52 29-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 2.13 0.00 01-JAN-08:10 2884.52 29-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 41.03 0.00 01-JAN-00:10 9571.88 16-OCT-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 41.03 0.00 01-JAN-00:10 9571.88 16-OCT-15:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 398.23 4360.32 30-MAR-08:10 56113.10 16-OCT-12:20
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 398.23 4360.32 30-MAR-08:10 56113.10 16-OCT-12:20
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 398.23 4360.32 30-MAR-08:10 56113.10 16-OCT-12:20
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 379.78 1.43 29-MAR-02:50 51342.14 30-SEP-15:20
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 0.82 0.00 01-JAN-00:10 11641.81 03-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 0.82 0.00 01-JAN-00:10 11641.81 03-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 378.96 0.00 03-JAN-01:30 51342.14 30-SEP-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 378.96 0.00 03-JAN-01:30 51342.14 30-SEP-15:20
EnergyTransfer:Zone:ROOM_5_FLR_3 49.40 0.16 13-NOV-00:30 9161.29 15-OCT-08:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 1.16 0.00 01-JAN-07:20 2579.32 29-MAR-18:10
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 1.16 0.00 01-JAN-07:20 2579.32 29-MAR-18:10
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 48.24 0.00 01-JAN-00:10 9161.29 15-OCT-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 48.24 0.00 01-JAN-00:10 9161.29 15-OCT-08:10
EnergyTransfer:Zone:ROOM_6_FLR_3 40.03 0.05 07-DEC-05:30 8139.22 15-OCT-08:10
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 2.34 0.00 01-JAN-07:30 2896.64 29-MAR-18:10
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 2.34 0.00 01-JAN-07:30 2896.64 29-MAR-18:10
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 37.69 0.00 01-JAN-00:10 8139.22 15-OCT-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 37.69 0.00 01-JAN-00:10 8139.22 15-OCT-08:10
EnergyTransfer:Zone:CORRIDOR_FLR_3 204.72 3560.81 30-MAR-06:10 9449.80 17-OCT-10:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 204.72 3560.81 30-MAR-06:10 9449.80 17-OCT-10:40
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 204.72 3560.81 30-MAR-06:10 9449.80 17-OCT-10:40
EnergyTransfer:Zone:ROOM_1_FLR_6 12.53 0.00 09-MAY-09:00 2880.38 15-OCT-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 0.85 0.00 01-JAN-08:10 916.75 29-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 0.85 0.00 01-JAN-08:10 916.75 29-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 11.67 0.00 01-JAN-00:10 2880.38 15-OCT-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 11.67 0.00 01-JAN-00:10 2880.38 15-OCT-15:10
EnergyTransfer:Zone:ROOM_2_FLR_6 10.62 0.01 12-MAY-21:10 2534.91 16-OCT-15:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 1.54 0.00 01-JAN-08:10 951.72 30-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 1.54 0.00 01-JAN-08:10 951.72 30-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 9.08 0.00 01-JAN-00:10 2534.91 16-OCT-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 9.08 0.00 01-JAN-00:10 2534.91 16-OCT-15:10
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 84.35 1.02 03-NOV-03:40 14049.17 16-OCT-15:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 0.71 0.00 01-JAN-07:20 3418.66 29-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 0.71 0.00 01-JAN-07:20 3418.66 29-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 83.64 0.00 01-JAN-00:10 14049.17 16-OCT-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 83.64 0.00 01-JAN-00:10 14049.17 16-OCT-15:10
EnergyTransfer:Zone:BANQUET_FLR_6 444.36 9517.50 29-MAR-11:00 21633.43 29-SEP-21:10
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 444.36 9517.50 29-MAR-11:00 21633.43 29-SEP-21:10
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 444.36 9517.50 29-MAR-11:00 21633.43 29-SEP-21:10
EnergyTransfer:Zone:DINING_FLR_6 483.18 10552.65 29-MAR-11:00 22927.48 29-SEP-21:10
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 483.18 10552.65 29-MAR-11:00 22927.48 29-SEP-21:10
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 483.18 10552.65 29-MAR-11:00 22927.48 29-SEP-21:10
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 633.54 9617.59 29-MAR-03:00 30317.49 30-SEP-10:50
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 633.54 9617.59 29-MAR-03:00 30317.49 30-SEP-10:50
EnergyTransfer:Zone:CORRIDOR_FLR_6 102.67 697.95 30-MAR-06:10 5724.55 30-SEP-13:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 102.67 697.95 30-MAR-06:10 5724.55 30-SEP-13:40
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 102.67 697.95 30-MAR-06:10 5724.55 30-SEP-13:40
PlantLoopHeatingDemand:Facility 1310.05 8692.74 03-AUG-00:20 210427.66 03-JAN-07:10
PlantLoopHeatingDemand:Plant 681.94 8692.74 03-AUG-00:20 47494.11 30-JAN-07:10
WaterSystems:PlantLoopHeatingDemand 681.94 8692.74 03-AUG-00:20 47494.11 30-JAN-07:10
General:WaterSystems:PlantLoopHeatingDemand 681.94 8692.74 03-AUG-00:20 47494.11 30-JAN-07:10
EnergyTransfer:HVAC 3429.85 128.54 06-MAY-07:20 506387.41 18-AUG-15:10
HeatingCoils:EnergyTransfer 628.11 0.00 02-JAN-11:10 183348.18 08-JAN-07:00
PlantLoopHeatingDemand:HVAC 628.11 0.00 02-JAN-11:10 183348.18 08-JAN-07:00
HeatingCoils:PlantLoopHeatingDemand 628.11 0.00 02-JAN-11:10 183348.18 08-JAN-07:00
CoolingCoils:EnergyTransfer 2801.74 0.00 01-JAN-00:10 506162.69 16-OCT-10:50
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 681.94 8692.74 03-AUG-00:20 47494.11 30-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 681.94 8692.74 03-AUG-00:20 47494.11 30-JAN-07:10
Boilers:EnergyTransfer 622.81 0.00 02-JAN-11:10 181927.27 08-JAN-07:00
Chillers:EnergyTransfer 2940.74 0.00 01-JAN-00:10 514811.04 18-AUG-15:10
HeatRejection:EnergyTransfer 3819.06 0.00 01-JAN-00:10 691618.65 16-OCT-10:50
General:HeatRejection:EnergyTransfer 3819.06 0.00 01-JAN-00:10 691618.65 16-OCT-10:50



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -405.872 0.000 0.000 141.074 173.462 150.255 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -58.919
RETAIL_1_FLR_1 0.000 0.000 0.000 -45.983 0.000 0.000 15.437 8.614 10.186 21.086 0.000 0.046 1.501 0.000 -8.556 0.000 -2.331 -0.000
RETAIL_2_FLR_1 0.000 0.000 0.000 -38.814 0.000 0.000 16.686 9.975 11.795 0.000 0.000 0.020 1.370 0.000 0.000 0.000 -1.031 -0.000
MECH_FLR_1 0.000 0.000 0.000 -33.796 0.000 0.000 3.671 16.635 12.471 0.000 0.000 0.053 3.209 0.000 0.000 0.000 -2.244 -0.000
STORAGE_FLR_1 0.000 0.000 0.000 -15.675 0.000 0.000 2.855 2.785 3.598 0.000 0.000 0.031 7.669 0.000 0.000 0.000 -1.262 0.000
LAUNDRY_FLR_1 0.000 0.000 0.000 -606.191 0.000 0.000 11.355 4.368 658.131 0.000 0.000 0.081 0.000 0.000 0.000 0.000 -3.298 -64.447
CAFE_FLR_1 0.000 0.000 0.000 -235.669 0.000 0.000 187.402 18.099 14.341 58.046 0.000 0.097 0.000 0.000 -26.890 0.000 -6.030 -9.395
LOBBY_FLR_1 0.000 0.000 0.000 -789.750 0.000 0.000 546.113 122.034 148.998 76.930 0.000 0.284 0.000 0.000 -36.271 0.000 -17.823 -50.516
ROOM_1_FLR_3 2.635 -37.171 0.000 -16.357 0.000 0.000 9.676 6.366 12.292 43.889 0.000 0.184 3.555 0.000 -18.427 0.000 -6.643 -0.000
ROOM_2_FLR_3 4.609 -27.433 0.000 -16.078 0.000 0.000 9.704 6.366 12.291 31.935 0.000 0.198 3.390 0.000 -18.468 0.000 -6.515 -0.001
ROOM_3_MULT19_FLR_3 0.017 -135.438 0.000 -262.817 0.000 0.000 0.000 76.021 228.754 250.557 0.000 0.505 35.113 0.000 -113.765 0.000 -78.947 -0.008
ROOM_4_MULT19_FLR_3 11.242 -177.366 0.000 -212.003 0.000 0.000 185.270 76.042 228.817 71.283 0.000 1.898 0.001 0.000 -97.296 0.000 -53.373 -34.512
ROOM_5_FLR_3 2.884 -33.507 0.000 -16.451 0.000 0.000 9.668 6.366 12.292 40.722 0.000 0.180 2.497 0.000 -17.970 0.000 -6.681 -0.001
ROOM_6_FLR_3 4.916 -24.136 0.000 -16.133 0.000 0.000 9.701 6.366 12.291 28.469 0.000 0.189 2.536 0.000 -17.666 0.000 -6.533 -0.000
CORRIDOR_FLR_3 0.000 0.000 0.000 -204.720 0.000 0.000 115.508 109.603 0.000 35.992 0.000 0.142 0.000 0.000 -24.870 0.000 -7.042 -24.613
ROOM_1_FLR_6 1.553 -8.296 0.000 -4.074 0.000 0.000 2.421 1.592 3.073 10.863 0.000 0.046 0.000 0.000 -4.527 0.000 -1.709 -0.942
ROOM_2_FLR_6 2.506 -6.051 0.000 -3.998 0.000 0.000 2.429 1.591 3.073 7.913 0.000 0.049 0.000 0.000 -4.515 0.000 -1.673 -1.325
ROOM_3_MULT9_FLR_6 2.386 -58.916 0.000 -26.399 0.000 0.000 21.758 9.005 27.097 54.956 0.000 0.257 0.879 0.000 -21.237 0.000 -9.786 -0.002
BANQUET_FLR_6 0.000 0.000 0.000 -444.356 0.000 0.000 315.907 34.836 175.857 5.942 0.000 0.046 0.000 0.000 -14.928 0.000 -4.268 -69.035
DINING_FLR_6 0.000 0.000 0.000 -483.178 0.000 0.000 314.965 34.836 175.857 5.629 0.000 0.043 0.000 0.000 -15.395 0.000 -4.312 -28.444
KITCHEN_FLR_6 0.000 0.000 0.000 -633.526 0.000 0.000 28.382 13.327 550.372 18.137 0.000 0.036 38.046 0.000 -10.944 0.000 -3.831 -0.000
CORRIDOR_FLR_6 0.000 0.000 0.000 -102.671 0.000 0.000 30.934 28.999 0.000 17.530 0.000 0.050 39.304 0.000 -11.078 0.000 -3.069 0.000
Total Facility 32.748 -508.313 0.000 -4614.513 0.000 0.000 1980.917 767.286 2451.839 779.879 0.000 4.437 139.072 0.000 -462.803 0.000 -228.402 -342.159


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 08-JAN-07:00 0.00 0.00 0.00 -19369.67 0.00 0.00 5541.63 4728.51 4258.44 0.00 0.00 0.00 4841.08 0.00 -0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 16-OCT-12:10 0.00 0.00 0.00 -4164.04 0.00 0.00 150.60 195.67 252.59 4777.64 0.00 129.44 0.00 0.00 -0.00 0.00 0.00 -1341.91
RETAIL_2_FLR_1 16-OCT-20:10 0.00 0.00 0.00 -2100.49 0.00 0.00 697.63 725.08 752.15 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -15.74 -58.63
MECH_FLR_1 30-SEP-10:33 0.00 0.00 0.00 -1547.47 0.00 0.00 58.37 377.89 309.27 0.00 0.00 76.11 725.83 0.00 -0.00 0.00 0.00 0.00
STORAGE_FLR_1 30-SEP-10:33 0.00 0.00 0.00 -735.67 0.00 0.00 44.93 63.26 89.22 0.00 0.00 43.95 494.32 0.00 -0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 29-SEP-20:00 0.00 0.00 0.00 -38524.31 0.00 0.00 408.79 357.21 44299.38 0.00 0.00 14.19 0.00 0.00 -0.00 0.00 0.00 -6555.26
CAFE_FLR_1 19-NOV-11:00 0.00 0.00 0.00 -14307.30 0.00 0.00 4947.82 358.25 406.43 13694.30 0.00 50.65 0.00 0.00 -0.00 0.00 0.00 -5150.16
LOBBY_FLR_1 16-OCT-20:10 0.00 0.00 0.00 -40228.96 0.00 0.00 23502.81 9124.61 9501.36 0.00 0.00 0.00 0.00 0.00 -1253.07 0.00 -257.49 -389.25
ROOM_1_FLR_3 15-OCT-15:02 0.00 -11134.84 0.00 -746.59 0.00 0.00 130.71 161.71 305.54 8668.99 0.00 206.79 2407.69 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_3 16-OCT-15:02 0.00 -10581.04 0.00 -739.66 0.00 0.00 235.27 137.19 273.90 6664.13 0.00 183.58 3826.62 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 16-OCT-12:20 0.00 -45552.46 0.00 -10564.12 0.00 0.00 0.00 1638.34 5097.90 57568.56 0.00 1636.72 0.00 0.00 -0.00 0.00 0.00 -9824.94
ROOM_4_MULT19_FLR_3 14-OCT-15:02 0.00 -60270.92 0.00 -9665.37 0.00 0.00 2553.35 1931.47 5687.67 10200.39 0.00 1425.81 48137.59 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 15-OCT-08:62 0.00 -9715.10 0.00 -742.87 0.00 0.00 130.71 274.41 653.23 8606.94 0.00 178.26 614.41 0.00 -0.00 0.00 0.00 0.00
ROOM_6_FLR_3 15-OCT-08:62 0.00 -9273.64 0.00 -739.15 0.00 0.00 130.72 274.38 653.15 6985.86 0.00 179.56 1789.11 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 17-OCT-10:33 0.00 0.00 0.00 -9469.50 0.00 0.00 1200.12 2489.76 0.00 7563.87 0.00 234.46 0.00 0.00 -0.00 0.00 0.00 -2018.70
ROOM_1_FLR_6 15-OCT-15:02 0.00 -2888.73 0.00 -187.10 0.00 0.00 32.68 40.43 76.39 2147.85 0.00 51.16 727.33 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_6 16-OCT-15:02 0.00 -2734.49 0.00 -185.19 0.00 0.00 58.82 34.30 68.48 1652.35 0.00 45.42 1060.32 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 16-OCT-15:02 0.00 -13604.54 0.00 -1212.82 0.00 0.00 529.39 194.07 603.86 5974.72 0.00 203.43 7311.89 0.00 -0.00 0.00 0.00 0.00
BANQUET_FLR_6 29-SEP-21:10 0.00 0.00 0.00 -21633.84 0.00 0.00 15644.25 2062.70 6747.90 0.00 0.00 7.86 0.00 0.00 -230.35 0.00 0.00 -2598.52
DINING_FLR_6 29-SEP-21:10 0.00 0.00 0.00 -22928.04 0.00 0.00 15644.15 2062.70 6747.90 0.00 0.00 7.86 0.00 0.00 -246.11 0.00 0.00 -1288.45
KITCHEN_FLR_6 30-SEP-10:50 0.00 0.00 0.00 -30334.89 0.00 0.00 461.31 302.73 24259.91 2341.07 0.00 93.86 2876.00 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 30-SEP-13:40 0.00 0.00 0.00 -5725.16 0.00 0.00 462.68 658.76 0.00 2850.50 0.00 109.46 1643.76 0.00 -0.00 0.00 0.00 0.00
Total Facility 16-OCT-15:02 0.00 -156410.77 0.00 -176318.88 0.00 0.00 53015.90 16768.37 77329.74 89078.23 0.00 4354.87 92182.55 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 30-MAR-06:05 0.00 0.00 73.69 0.00 0.00 0.00 358.03 391.34 433.01 0.00 0.00 0.00 0.00 0.00 -726.18 0.00 -189.72 -340.18
RETAIL_2_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MECH_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 30-MAR-08:62 6319.98 354.31 0.00 -354.31 0.00 0.00 105.31 215.61 453.05 323.07 0.00 0.00 0.00 0.00 -0.00 0.00 -305.16 -7111.87
ROOM_2_FLR_3 30-MAR-08:62 6322.82 337.41 0.00 -337.41 0.00 0.00 106.31 215.58 452.99 0.00 0.00 0.00 0.00 0.00 -313.97 0.00 -298.73 -6485.00
ROOM_3_MULT19_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 30-MAR-08:62 34034.09 5519.34 0.00 -5519.34 0.00 0.00 1911.57 2575.24 8433.45 0.00 0.00 0.00 0.00 0.00 -2325.75 0.00 -1725.14 -42903.44
ROOM_5_FLR_3 28-MAR-08:62 6143.31 374.65 0.00 -374.65 0.00 0.00 104.08 215.61 453.05 0.00 0.00 0.00 0.00 0.00 -1178.41 0.00 -314.33 -5423.31
ROOM_6_FLR_3 28-MAR-08:62 6106.09 371.09 0.00 -371.09 0.00 0.00 104.28 215.58 452.99 0.00 0.00 0.00 0.00 0.00 -1173.60 0.00 -312.99 -5392.36
CORRIDOR_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 30-MAR-08:62 1904.50 80.65 0.00 -80.65 0.00 0.00 26.93 53.90 113.26 89.71 0.00 0.00 0.00 0.00 -0.00 0.00 -73.70 -2114.61
ROOM_2_FLR_6 30-MAR-08:62 1901.54 76.61 0.00 -76.61 0.00 0.00 27.16 53.90 113.25 0.00 0.00 0.00 0.00 0.00 -66.45 0.00 -72.16 -1957.24
ROOM_3_MULT9_FLR_6 28-MAR-08:62 8910.59 615.86 0.00 -615.86 0.00 0.00 233.10 304.96 998.70 0.00 0.00 0.00 0.00 0.00 -1372.05 0.00 -367.72 -8707.59
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 29-MAR-08:62 -40376.12 119987.92 0.00 -119987.92 0.00 0.00 22875.05 26712.50 88432.23 252.83 0.00 0.00 0.00 0.00 -8125.92 0.00 -9331.94 -80438.63



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 21.2308 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 21.1122 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 11.6557 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.6557 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.003540 142.3000 0.000914 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.003540 422.4350 0.000305 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.000747 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4616 2.4616 1.3514 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3255 0.3255 0.1787 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2393 0.2393 0.1314 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2269 0.2269 0.1245 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1079 0.1079 0.0592 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.3113 3.3113 1.8179 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3953 1.3953 0.7660 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.5297 4.5297 2.4868 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3510 1.3510 0.7417 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1302 2.1302 1.1695 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2345 2.2345 1.2267 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2252 2.2252 1.2217 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6926 0.6926 0.3802 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 21.2308 21.1122 21.2308 11.6557 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3514 1.3514 1.3514 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1787 0.1787 0.1787 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1314 0.1314 0.1314 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1245 0.1245 0.1245 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0592 0.0592 0.0592 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.8179 1.8179 1.8179 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7660 0.7660 0.7660 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4868 2.4868 2.4868 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7417 0.7417 0.7417 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1695 1.1695 1.1695 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2267 1.2267 1.2267 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2217 1.2217 1.2217 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3802 0.3802 0.3802 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 11.6557 11.6557 11.6557 11.6557 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 22.50
Number of hours not met 22.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 914.35 230195.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 878.32 180333.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 767.29 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 242.88 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 959.56 59492.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 14.43 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 8.99 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 32.45 1868.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.91 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 561.22 37012.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 160.57 7962.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.75 4738.61 2934.36 246240.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 20.48 1892.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 34.76 1203.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1807.35 5159.85
Natural Gas 1788.84 5637.55
Additional 0.00 0.00
Total 3596.19 10797.40


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 67.63
Space Heating 0.00
Space Cooling 77.42
Fans (All) 49.47
Service Water Heating 8.00
Receptacle Equipment 153.81
Miscellaneous (All) 454.80
Subtotal 454.80


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 80.59
Service Water Heating 258.64
Miscellaneous (All) 496.91
Subtotal 496.91


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 7.11
Space Heating 8.47
Space Cooling 8.13
Fans (All) 5.20
Service Water Heating 28.02
Receptacle Equipment 32.73
Miscellaneous 10.35


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2667. 8760.
LTG_SCH_LOBBY 3061. 8760.
LTG_SCH_STORAGE 1339. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 2678. 8760.
LTG_SCH_GUESTROOM 2482. 8760.
LTG_SCH_CORRIDOR 3061. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3924. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 18.89 365 18.89 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 23.33 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8760.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 8760.00 0.00 0.00 0.00 0.00
Sum 192720.00 0.00 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 0.00 0.00 0.00 0.00
Average 288887.05 0.00 0.00 0.00 0.00
Sum 6355515.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 7927.50 832.50 0.00 0.00 0.00
LOBBY_FLR_1 7942.17 817.83 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 7885.50 874.50 0.00 0.00 0.00
DINING_FLR_6 7993.17 766.83 0.00 0.00 0.00
KITCHEN_FLR_6 8731.50 28.50 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 7885.50 0.00 0.00 0.00 0.00
Max 8760.00 874.50 0.00 0.00 0.00
Average 8609.08 150.92 0.00 0.00 0.00
Sum 189399.83 3320.17 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 607562.67 102854.33 0.00 0.00 0.00
LOBBY_FLR_1 1823036.67 292392.33 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1063847.83 181867.17 0.00 0.00 0.00
DINING_FLR_6 1084840.17 160874.83 0.00 0.00 0.00
KITCHEN_FLR_6 107978.00 291.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 1823036.67 292392.33 0.00 0.00 0.00
Average 255328.88 33558.17 0.00 0.00 0.00
Sum 5617235.33 738279.67 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:53

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

For: Environment

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C

For: Environment

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO

For: Environment

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.361373E+11 19372.71 08-JAN-07:00 1.00 -0.3 0.791297E+10 4836.99 20-JAN-23:10 13.83 13.83
February 0.299458E+11 15563.58 01-FEB-11:33 25.00 14.29 0.680842E+10 4836.86 01-FEB-22:19 13.00 11.68
March 0.324790E+11 14986.93 12-MAR-10:33 21.33 14.69 0.740488E+10 4617.35 01-MAR-22:10 21.33 14.69
April 0.313754E+11 15146.86 30-APR-10:33 25.67 16.97 0.707536E+10 4562.77 14-APR-21:10 25.67 16.97
May 0.323688E+11 14866.17 28-MAY-10:33 21.00 15.43 0.731554E+10 4578.03 12-MAY-21:10 21.00 15.43
June 0.312182E+11 14996.96 25-JUN-10:33 23.00 17.26 0.701417E+10 4519.12 09-JUN-21:10 23.00 17.26
July 0.341351E+11 15921.42 23-JUL-10:33 25.67 20.39 0.746137E+10 4677.01 14-JUL-21:19 25.67 20.39
August 0.346136E+11 15903.34 06-AUG-10:33 24.33 20.00 0.757192E+10 4702.98 25-AUG-21:19 16.07 16.07
September 0.345720E+11 16508.01 30-SEP-10:33 30.57 17.23 0.755083E+10 4837.02 13-SEP-21:19 30.57 17.23
October 0.370909E+11 18191.50 20-OCT-21:00 16.00 13.03 0.796565E+10 4837.03 04-OCT-21:19 16.00 13.03
November 0.358679E+11 18811.19 30-NOV-22:00 11.60 5.78 0.775786E+10 4837.00 09-NOV-22:40 11.60 5.78
December 0.360680E+11 18396.42 01-DEC-22:00 11.00 10.48 0.794842E+10 4836.98 21-DEC-22:10 10.67 10.67
                     
Annual Sum or Average 0.405872E+12         0.897874E+11        
Minimum of Months 0.299458E+11 14866.17   1.00 -0.3 0.680842E+10 4519.12   10.67 5.78
Maximum of Months 0.370909E+11 19372.71   30.57 20.39 0.796565E+10 4837.03   30.57 20.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.383354E+10 3305.32 14-JAN-12:40 25.33 11.70 0.672437E+09 439.08 18-JAN-22:30 16.50 13.26
February 0.314116E+10 2875.02 02-FEB-12:40 19.33 12.36 0.598552E+09 437.55 01-FEB-22:30 19.33 12.36
March 0.313514E+10 2588.16 11-MAR-13:00 24.00 13.82 0.652349E+09 436.22 23-MAR-21:30 13.50 12.93
April 0.354868E+10 2063.21 08-APR-10:33 21.67 16.37 0.644362E+09 437.43 26-APR-21:40 16.00 15.39
May 0.342433E+10 2012.07 04-MAY-10:33 22.00 15.73 0.648857E+09 439.36 04-MAY-21:30 17.00 15.07
June 0.363236E+10 1932.52 25-JUN-10:33 23.00 17.26 0.646782E+09 436.03 28-JUN-21:30 17.00 16.37
July 0.409890E+10 2118.98 30-JUL-10:33 24.67 20.10 0.696029E+09 452.21 31-JUL-21:30 18.85 17.85
August 0.430847E+10 2198.77 27-AUG-10:33 23.33 18.72 0.720626E+09 459.73 18-AUG-21:30 23.33 18.72
September 0.418376E+10 3544.59 30-SEP-13:10 32.00 16.98 0.692827E+09 491.81 29-SEP-21:30 32.00 16.98
October 0.463570E+10 4164.01 16-OCT-12:10 35.68 17.48 0.723053E+09 491.79 16-OCT-21:30 19.00 11.09
November 0.396438E+10 3645.57 19-NOV-12:30 26.50 15.22 0.660820E+09 442.09 27-NOV-22:30 16.00 5.61
December 0.407634E+10 3480.70 19-DEC-12:50 25.83 11.54 0.680372E+09 456.06 05-DEC-22:30 25.83 11.54
                     
Annual Sum or Average 0.459828E+11         0.803707E+10        
Minimum of Months 0.313514E+10 1932.52   19.33 11.54 0.598552E+09 436.03   13.50 5.61
Maximum of Months 0.463570E+10 4164.01   35.68 20.10 0.723053E+09 491.81   32.00 18.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.313912E+10 1616.30 08-JAN-07:00 1.00 -0.3 0.865257E+09 569.52 20-JAN-23:10 13.83 13.83
February 0.279252E+10 1496.17 03-FEB-21:20 11.67 6.29 0.781662E+09 569.52 02-FEB-23:10 11.67 6.29
March 0.305160E+10 1500.32 24-MAR-21:00 13.00 11.87 0.856484E+09 569.51 23-MAR-21:19 13.00 11.87
April 0.313204E+10 1614.91 27-APR-21:00 14.00 12.84 0.854785E+09 569.53 26-APR-21:19 14.00 12.84
May 0.320426E+10 1625.61 03-MAY-21:00 16.00 14.77 0.879485E+09 569.52 24-MAY-21:19 16.00 14.13
June 0.323827E+10 1679.69 30-JUN-21:00 16.00 14.76 0.871421E+09 569.53 29-JUN-21:19 16.00 14.76
July 0.351624E+10 1788.09 31-JUL-21:00 19.00 17.66 0.917514E+09 569.53 26-JUL-21:19 19.00 17.66
August 0.357887E+10 1849.01 18-AUG-21:00 19.00 17.66 0.928851E+09 569.53 16-AUG-21:19 19.00 17.66
September 0.337510E+10 2050.44 29-SEP-21:00 24.60 13.50 0.888565E+09 569.54 30-SEP-01:19 24.20 13.95
October 0.349083E+10 2100.96 16-OCT-20:10 20.50 12.73 0.917576E+09 569.54 15-OCT-23:19 20.50 12.73
November 0.311988E+10 1552.13 19-NOV-11:33 26.00 15.32 0.857958E+09 569.53 27-NOV-22:30 16.00 5.61
December 0.317565E+10 1576.89 05-DEC-22:00 17.00 9.46 0.878251E+09 569.51 19-DEC-22:10 8.33 1.76
                     
Annual Sum or Average 0.388144E+11         0.104978E+11        
Minimum of Months 0.279252E+10 1496.17   1.00 -0.3 0.781662E+09 569.51   8.33 1.76
Maximum of Months 0.357887E+10 2100.96   26.00 17.66 0.928851E+09 569.54   24.20 17.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.262049E+10 1316.97 20-JAN-11:33 21.67 15.71 0.166810E+09 111.11 18-JAN-22:10 21.67 15.71
February 0.236589E+10 1266.30 02-FEB-11:33 19.33 10.71 0.151538E+09 109.00 03-FEB-22:10 9.50 4.24
March 0.257022E+10 1292.86 19-MAR-10:33 19.33 15.06 0.166116E+09 108.92 24-MAR-21:10 13.00 11.77
April 0.269371E+10 1374.14 30-APR-10:33 25.67 16.97 0.166942E+09 112.09 27-APR-21:10 25.67 16.97
May 0.285203E+10 1394.17 04-MAY-10:33 22.00 15.73 0.175858E+09 114.60 04-MAY-21:19 17.00 15.07
June 0.294431E+10 1452.33 25-JUN-10:33 23.00 17.26 0.177162E+09 117.20 30-JUN-21:19 16.03 15.21
July 0.319519E+10 1514.78 23-JUL-10:33 25.67 20.39 0.187461E+09 118.80 19-JUL-21:19 25.67 20.39
August 0.318702E+10 1501.24 19-AUG-10:33 24.67 20.11 0.187798E+09 118.70 18-AUG-21:19 24.67 20.11
September 0.295911E+10 1547.43 30-SEP-10:33 30.57 17.23 0.177288E+09 119.59 29-SEP-21:10 30.57 17.23
October 0.308196E+10 1538.23 16-OCT-10:33 36.33 17.49 0.184623E+09 120.45 17-OCT-21:10 18.00 14.87
November 0.265759E+10 1351.63 19-NOV-11:33 26.00 15.32 0.166856E+09 110.75 01-NOV-21:10 26.00 15.32
December 0.266817E+10 1315.58 19-DEC-11:33 25.00 11.16 0.169489E+09 110.92 05-DEC-22:19 25.00 11.16
                     
Annual Sum or Average 0.337957E+11         0.207794E+10        
Minimum of Months 0.236589E+10 1266.30   19.33 10.71 0.151538E+09 108.92   9.50 4.24
Maximum of Months 0.319519E+10 1547.43   36.33 20.39 0.187798E+09 120.45   30.57 20.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.120914E+10 623.22 20-JAN-11:33 21.67 15.71 0.125969E+09 81.72 18-JAN-22:49 21.67 15.71
February 0.109451E+10 598.69 02-FEB-11:33 19.33 10.71 0.114249E+09 80.14 03-FEB-23:10 11.67 3.87
March 0.117784E+10 610.36 23-MAR-10:33 22.00 16.70 0.125146E+09 80.03 24-MAR-22:10 13.00 11.29
April 0.124971E+10 650.04 30-APR-10:33 25.67 16.97 0.125877E+09 82.30 27-APR-22:10 25.67 16.97
May 0.132063E+10 658.80 04-MAY-10:33 22.00 15.73 0.132366E+09 84.32 04-MAY-22:10 16.83 15.02
June 0.136621E+10 684.55 25-JUN-10:33 23.00 17.26 0.133452E+09 85.95 30-JUN-22:10 16.13 16.03
July 0.148612E+10 715.58 23-JUL-10:33 25.67 20.39 0.141362E+09 87.35 19-JUL-22:10 25.67 20.39
August 0.148365E+10 709.72 19-AUG-10:33 24.67 20.11 0.141717E+09 87.28 18-AUG-22:10 24.67 20.11
September 0.137791E+10 735.66 30-SEP-10:33 30.57 17.23 0.133901E+09 88.56 29-SEP-22:10 30.57 17.23
October 0.143545E+10 734.00 16-OCT-10:33 36.33 17.49 0.139459E+09 89.83 16-OCT-22:10 20.17 11.06
November 0.123478E+10 643.94 19-NOV-11:33 26.00 15.32 0.125942E+09 81.46 01-NOV-22:10 26.00 15.32
December 0.123918E+10 625.48 19-DEC-11:33 25.00 11.16 0.127934E+09 82.02 05-DEC-23:10 25.00 11.16
                     
Annual Sum or Average 0.156751E+11         0.156737E+10        
Minimum of Months 0.109451E+10 598.69   19.33 10.71 0.114249E+09 80.03   11.67 3.87
Maximum of Months 0.148612E+10 735.66   36.33 20.39 0.141717E+09 89.83   30.57 20.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.505639E+11 37582.47 24-JAN-21:00 17.00 11.91 0.578883E+09 381.76 31-JAN-22:10 11.82 10.56
February 0.455463E+11 37448.00 03-FEB-21:00 13.00 7.33 0.524380E+09 381.71 15-FEB-22:10 13.83 12.18
March 0.505557E+11 37697.31 23-MAR-20:00 14.00 13.42 0.580519E+09 381.75 02-MAR-22:10 14.00 13.42
April 0.497087E+11 38001.83 26-APR-20:00 17.00 15.07 0.562641E+09 381.68 24-APR-21:10 17.00 15.07
May 0.514691E+11 38015.54 04-MAY-20:00 17.00 15.07 0.582194E+09 381.71 23-MAY-21:10 13.58 12.43
June 0.504779E+11 38024.64 30-JUN-20:00 16.00 15.39 0.564911E+09 381.69 02-JUN-21:10 16.00 15.39
July 0.526151E+11 38288.05 19-JUL-20:00 19.00 18.34 0.583353E+09 381.68 18-JUL-21:19 19.00 18.34
August 0.528982E+11 38230.72 18-AUG-20:00 19.00 17.66 0.584826E+09 381.68 18-AUG-21:19 19.00 17.66
September 0.503986E+11 38524.41 29-SEP-20:00 25.00 13.58 0.564112E+09 381.81 14-SEP-21:10 25.00 13.58
October 0.520845E+11 38368.76 16-OCT-20:00 21.00 13.07 0.583792E+09 381.74 31-OCT-21:10 16.88 14.87
November 0.493093E+11 37448.82 28-NOV-21:00 13.00 6.31 0.563186E+09 381.72 02-NOV-21:10 13.00 6.31
December 0.505632E+11 37700.86 05-DEC-21:00 16.00 9.09 0.580954E+09 381.74 08-DEC-22:10 14.00 12.84
                     
Annual Sum or Average 0.606190E+12         0.685375E+10        
Minimum of Months 0.455463E+11 37448.00   13.00 6.31 0.524380E+09 381.68   11.82 6.31
Maximum of Months 0.528982E+11 38524.41   25.00 18.34 0.584826E+09 381.81   25.00 18.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.204035E+11 13066.57 14-JAN-12:40 25.33 11.70 0.102429E+11 6461.99 21-JAN-02:20 14.00 13.42
February 0.173754E+11 10990.21 20-FEB-11:00 16.00 9.07 0.914717E+10 6462.04 02-FEB-00:20 16.00 9.07
March 0.184040E+11 10917.54 11-MAR-12:50 24.00 13.82 0.994475E+10 6461.96 24-MAR-23:19 13.00 11.12
April 0.185603E+11 9281.91 08-APR-10:33 21.67 16.37 0.980810E+10 6461.98 13-APR-23:19 14.67 13.68
May 0.183779E+11 8907.76 04-MAY-21:20 17.00 15.07 0.993076E+10 6462.00 04-MAY-23:19 16.00 14.76
June 0.184217E+11 8750.62 25-JUN-10:33 23.00 17.26 0.982448E+10 6462.00 27-JUN-23:19 17.00 16.16
July 0.199644E+11 9351.72 30-JUL-10:33 24.67 20.10 0.103241E+11 6462.01 14-JUL-23:19 24.67 20.10
August 0.207505E+11 9692.55 27-AUG-10:33 23.33 18.72 0.105759E+11 6462.02 23-AUG-23:19 23.33 18.72
September 0.202656E+11 12510.34 30-SEP-12:00 32.00 17.11 0.102252E+11 6462.04 30-SEP-01:19 32.00 17.11
October 0.221068E+11 14122.28 15-OCT-12:00 32.00 16.89 0.106162E+11 6462.05 12-OCT-23:19 32.00 16.89
November 0.200729E+11 14301.89 19-NOV-11:00 26.00 15.07 0.100663E+11 6462.00 28-NOV-00:20 15.33 5.14
December 0.209643E+11 12938.47 16-DEC-13:00 26.00 13.31 0.103602E+11 6462.31 01-DEC-00:30 26.00 13.31
                     
Annual Sum or Average 0.235667E+12         0.121066E+12        
Minimum of Months 0.173754E+11 8750.62   16.00 9.07 0.914717E+10 6461.96   13.00 5.14
Maximum of Months 0.221068E+11 14301.89   32.00 20.10 0.106162E+11 6462.31   32.00 20.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.652057E+11 33503.26 18-JAN-22:10 16.83 13.41 0.310448E+11 19185.29 31-JAN-00:20 13.00 11.68
February 0.576449E+11 32802.11 01-FEB-22:10 13.00 11.77 0.279647E+11 19185.35 02-FEB-00:20 13.33 12.00
March 0.626144E+11 32101.29 24-MAR-21:10 13.00 11.77 0.306509E+11 19185.22 22-MAR-23:19 13.00 11.77
April 0.631022E+11 32520.34 26-APR-22:00 16.00 15.39 0.300927E+11 19185.24 06-APR-23:19 16.00 15.39
May 0.645277E+11 33670.75 04-MAY-21:10 17.00 15.07 0.310152E+11 19185.30 05-MAY-23:19 15.33 14.33
June 0.649687E+11 33472.85 28-JUN-21:10 17.00 16.37 0.304914E+11 19185.30 07-JUN-23:19 17.00 16.37
July 0.699207E+11 34980.46 31-JUL-21:10 18.95 17.72 0.316815E+11 19185.28 21-JUL-23:19 18.95 17.72
August 0.713604E+11 35567.76 18-AUG-21:10 19.00 17.66 0.319647E+11 19185.31 22-AUG-23:19 17.00 15.07
September 0.680702E+11 39577.34 29-SEP-21:10 24.58 13.52 0.308375E+11 19185.34 30-SEP-01:19 24.20 13.95
October 0.717644E+11 40238.61 16-OCT-20:10 20.50 12.73 0.319693E+11 19185.35 23-OCT-23:19 16.33 13.70
November 0.645070E+11 33567.47 20-NOV-22:10 14.00 12.84 0.305028E+11 19185.35 20-NOV-00:20 14.00 12.84
December 0.660608E+11 35094.34 05-DEC-22:10 17.17 9.45 0.313972E+11 19187.90 01-DEC-01:10 17.17 9.45
                     
Annual Sum or Average 0.789747E+12         0.369613E+12        
Minimum of Months 0.576449E+11 32101.29   13.00 9.45 0.279647E+11 19185.22   13.00 9.45
Maximum of Months 0.717644E+11 40238.61   24.58 17.72 0.319693E+11 19187.90   24.20 17.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.631921E+09 2773.34 14-JAN-16:02 23.00 12.42 97477264.69 56.69 20-JAN-22:10 13.17 13.17
February 0.557410E+09 2732.73 03-FEB-16:02 20.50 10.05 87694835.84 56.69 16-FEB-22:10 12.00 11.46
March 0.580552E+09 2788.34 11-MAR-16:02 21.33 12.81 97079676.69 56.69 23-MAR-22:19 12.67 12.30
April 0.103808E+10 2798.83 01-APR-15:01 22.83 11.17 94814710.02 56.69 27-APR-21:10 14.00 12.84
May 0.990121E+09 2670.37 17-MAY-15:02 21.67 15.72 97903186.24 56.69 04-MAY-23:49 21.67 15.72
June 0.127645E+10 2704.29 30-JUN-15:02 22.95 17.86 95108077.68 56.69 22-JUN-21:10 22.95 17.86
July 0.170560E+10 2812.62 19-JUL-15:02 26.67 20.20 98586156.20 56.69 24-JUL-21:30 18.00 17.35
August 0.175907E+10 2786.65 18-AUG-15:02 26.50 20.71 98746243.58 56.69 16-AUG-21:30 26.50 20.71
September 0.146339E+10 2643.57 13-SEP-15:02 22.83 18.37 95251107.51 56.69 30-SEP-23:10 18.23 17.87
October 0.146166E+10 2970.36 15-OCT-15:02 30.83 15.40 98269700.78 56.69 18-OCT-21:10 14.83 14.34
November 0.799331E+09 2767.99 19-NOV-09:02 24.33 12.78 94691637.27 56.69 10-NOV-22:00 24.33 12.78
December 0.719270E+09 2788.91 05-DEC-16:02 22.67 12.42 97635148.83 56.69 07-DEC-22:10 12.67 12.59
                     
Annual Sum or Average 0.129829E+11         0.115326E+10        
Minimum of Months 0.557410E+09 2643.57   20.50 10.05 87694835.84 56.69   12.00 11.46
Maximum of Months 0.175907E+10 2970.36   30.83 20.71 98746243.58 56.69   26.50 20.71



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.275567E+09 2639.25 14-JAN-16:02 23.00 12.42 96103948.62 56.69 20-JAN-23:10 13.83 13.83
February 0.292818E+09 2598.87 03-FEB-16:02 20.50 10.05 86863467.88 56.69 24-FEB-00:20 13.00 11.87
March 0.377444E+09 2657.91 11-MAR-16:02 21.33 12.81 96373689.46 56.69 23-MAR-21:10 13.83 13.26
April 0.852730E+09 2678.29 01-APR-15:01 22.83 11.17 94361587.59 56.69 27-APR-00:49 15.00 14.90
May 0.948540E+09 2590.25 17-MAY-15:02 21.67 15.72 97780117.45 56.69 02-MAY-23:00 21.67 15.72
June 0.128333E+10 2614.88 30-JUN-15:02 22.95 17.86 95080435.94 56.69 28-JUN-21:10 22.95 17.86
July 0.167926E+10 2687.05 19-JUL-15:02 26.67 20.20 98544912.63 56.69 19-JUL-22:19 18.00 17.35
August 0.160055E+10 2675.66 19-AUG-15:02 25.83 18.86 98581498.68 56.69 07-AUG-21:19 25.83 18.86
September 0.119180E+10 2588.08 11-SEP-15:02 22.00 16.76 94832675.11 56.69 05-SEP-23:10 22.00 16.76
October 0.106749E+10 2830.16 16-OCT-15:02 29.83 15.97 97687665.23 56.69 17-OCT-21:19 18.00 14.77
November 0.391961E+09 2568.51 27-NOV-16:01 19.67 7.55 93680328.56 56.69 02-NOV-02:09 19.67 7.55
December 0.295972E+09 2654.36 05-DEC-16:02 22.67 12.42 96246262.75 56.69 05-DEC-22:10 17.17 9.45
                     
Annual Sum or Average 0.102575E+11         0.114614E+10        
Minimum of Months 0.275567E+09 2568.51   19.67 7.55 86863467.88 56.69   13.00 7.55
Maximum of Months 0.167926E+10 2830.16   29.83 20.20 98581498.68 56.69   25.83 18.86



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.554547E+09 633.45 14-JAN-12:40 25.33 11.70 0.00 0.00 01-JAN-00:10 25.33 11.70
February 0.406038E+09 569.66 02-FEB-12:30 19.50 11.91 0.00 0.00 01-FEB-00:10 19.50 11.91
March 0.346886E+09 476.04 11-MAR-13:30 24.00 13.28 0.00 0.00 01-MAR-00:10 24.00 13.28
April 0.334133E+09 355.93 08-APR-13:10 21.83 16.35 0.00 0.00 01-APR-00:10 21.83 16.35
May 0.269939E+09 254.24 04-MAY-12:30 23.50 16.62 0.00 0.00 01-MAY-00:10 23.50 16.62
June 0.273265E+09 184.28 29-JUN-17:13 22.67 18.51 0.00 0.00 01-JUN-00:10 22.67 18.51
July 0.357452E+09 278.20 31-JUL-13:00 28.00 21.19 0.00 0.00 01-JUL-00:10 28.00 21.19
August 0.444861E+09 348.39 30-AUG-13:00 24.00 18.12 0.00 0.00 01-AUG-00:10 24.00 18.12
September 0.476893E+09 629.55 30-SEP-13:30 32.00 17.24 0.00 0.00 01-SEP-00:10 32.00 17.24
October 0.620077E+09 738.33 16-OCT-12:20 35.37 17.35 0.00 0.00 01-OCT-00:10 35.37 17.35
November 0.549129E+09 684.84 19-NOV-13:00 27.00 14.96 0.00 0.00 01-NOV-00:10 27.00 14.96
December 0.606712E+09 642.41 19-DEC-13:00 26.00 11.60 0.00 0.00 01-DEC-00:10 26.00 11.60
                     
Annual Sum or Average 0.523993E+10         0.00        
Minimum of Months 0.269939E+09 184.28   19.50 11.60 0.00 0.00   19.50 11.60
Maximum of Months 0.620077E+09 738.33   35.37 21.19 0.00 0.00   35.37 21.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.255566E+09 828.61 15-JAN-09:02 22.50 9.56 95663256.14 56.69 19-JAN-22:10 14.00 12.84
February 0.258580E+09 745.81 20-FEB-09:02 14.00 8.40 86603082.39 56.69 13-FEB-22:40 14.00 8.40
March 0.297644E+09 799.31 11-MAR-16:02 21.33 12.81 96062510.74 56.69 23-MAR-21:10 13.83 13.26
April 0.399958E+09 824.70 26-APR-15:02 22.83 16.24 93232681.70 56.69 27-APR-21:00 14.00 12.84
May 0.467497E+09 818.11 04-MAY-15:02 22.00 16.32 96570167.20 56.69 25-MAY-21:00 15.00 13.80
June 0.544609E+09 817.08 30-JUN-15:02 22.95 17.86 93755615.18 56.69 30-JUN-22:00 16.30 15.68
July 0.636955E+09 839.46 18-JUL-18:02 23.33 19.62 97110983.54 56.69 27-JUL-22:30 18.00 17.35
August 0.598247E+09 842.65 19-AUG-18:02 22.67 17.49 97080675.08 56.69 29-AUG-21:00 17.30 15.46
September 0.485188E+09 850.16 30-SEP-18:02 22.67 16.87 93416285.28 56.69 06-SEP-22:10 22.67 16.87
October 0.492127E+09 920.21 14-OCT-15:02 32.83 16.38 96508587.82 56.69 18-OCT-21:00 14.00 14.00
November 0.293844E+09 859.85 19-NOV-09:02 24.33 12.78 92844884.10 56.69 10-NOV-22:10 24.33 12.78
December 0.256035E+09 826.28 05-DEC-09:02 24.33 12.02 95622366.17 56.69 01-DEC-00:00 24.33 12.02
                     
Annual Sum or Average 0.498625E+10         0.113447E+10        
Minimum of Months 0.255566E+09 745.81   14.00 8.40 86603082.39 56.69   13.83 8.40
Maximum of Months 0.636955E+09 920.21   32.83 19.62 97110983.54 56.69   24.33 17.35



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.657336E+09 2455.23 14-JAN-16:02 23.00 12.42 97806448.96 56.69 20-JAN-23:10 13.83 13.83
February 0.522965E+09 2441.81 01-FEB-09:02 22.33 11.86 87850322.36 56.69 01-FEB-22:19 13.00 11.68
March 0.571397E+09 2438.19 11-MAR-16:02 21.33 12.81 97292126.67 56.69 23-MAR-22:19 12.67 12.30
April 0.948985E+09 2473.12 01-APR-15:01 22.83 11.17 95057995.13 56.69 27-APR-00:40 15.00 14.80
May 0.870594E+09 2345.85 04-MAY-15:02 22.00 16.32 97984329.68 56.69 02-MAY-23:00 22.00 16.32
June 0.110727E+10 2332.87 02-JUN-15:02 20.67 15.42 95151155.53 56.69 26-JUN-00:00 17.00 15.07
July 0.156048E+10 2373.99 19-JUL-15:02 26.67 20.20 98818645.44 56.69 18-JUL-21:19 26.67 20.20
August 0.167406E+10 2425.26 19-AUG-15:02 25.83 18.86 98943065.47 56.69 18-AUG-22:10 25.83 18.86
September 0.128378E+10 2364.08 30-SEP-18:02 22.67 16.87 95200085.63 56.69 30-SEP-23:00 18.40 17.30
October 0.139726E+10 2614.49 15-OCT-08:62 29.67 14.37 98390704.44 56.69 01-OCT-00:10 29.67 14.37
November 0.748297E+09 2531.02 19-NOV-09:02 24.33 12.78 94861629.61 56.69 10-NOV-22:10 24.33 12.78
December 0.717452E+09 2515.91 05-DEC-09:02 24.33 12.02 97884600.40 56.69 07-DEC-22:10 12.67 12.59
                     
Annual Sum or Average 0.120599E+11         0.115524E+10        
Minimum of Months 0.522965E+09 2332.87   20.67 11.17 87850322.36 56.69   12.67 11.68
Maximum of Months 0.167406E+10 2614.49   29.67 20.20 98943065.47 56.69   29.67 20.20



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.315138E+09 2190.78 14-JAN-16:02 23.00 12.42 96092062.73 56.69 20-JAN-23:10 13.83 13.83
February 0.282536E+09 2261.59 01-FEB-09:02 22.33 11.86 86801641.24 56.69 24-FEB-00:20 13.00 11.87
March 0.375330E+09 2260.02 11-MAR-16:02 21.33 12.81 96517555.00 56.69 23-MAR-21:10 13.83 13.26
April 0.762443E+09 2309.64 26-APR-15:02 22.83 16.24 94626760.73 56.69 26-APR-23:49 15.17 14.47
May 0.830451E+09 2260.47 24-MAY-08:62 18.00 8.80 97849086.12 56.69 05-MAY-00:30 18.00 8.80
June 0.111188E+10 2251.24 02-JUN-15:02 20.67 15.42 95167477.38 56.69 26-JUN-01:30 17.00 15.07
July 0.153070E+10 2277.44 19-JUL-15:02 26.67 20.20 98828986.29 56.69 18-JUL-21:30 26.67 20.20
August 0.150466E+10 2289.17 19-AUG-15:02 25.83 18.86 98882568.46 56.69 18-AUG-21:40 25.83 18.86
September 0.101064E+10 2287.68 30-SEP-18:02 22.67 16.87 94796456.36 56.69 12-SEP-22:49 22.67 16.87
October 0.996298E+09 2503.20 15-OCT-08:62 29.67 14.37 97850991.84 56.69 17-OCT-21:19 18.00 14.77
November 0.381187E+09 2404.56 19-NOV-09:02 24.33 12.78 93422473.49 56.69 09-NOV-22:19 24.33 12.78
December 0.321434E+09 2392.48 05-DEC-09:02 24.33 12.02 96109005.08 56.69 01-DEC-01:19 24.33 12.02
                     
Annual Sum or Average 0.942270E+10         0.114695E+10        
Minimum of Months 0.282536E+09 2190.78   18.00 8.80 86801641.24 56.69   13.00 8.80
Maximum of Months 0.153070E+10 2503.20   29.67 20.20 98882568.46 56.69   26.67 20.20



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.405399E+10 2258.34 08-JAN-07:00 1.00 -0.3 0.134373E+10 856.20 20-JAN-23:10 13.83 13.83
February 0.363365E+10 1981.93 04-FEB-11:45 20.83 8.35 0.121876E+10 853.61 03-FEB-23:10 20.83 8.35
March 0.393145E+10 1992.74 12-MAR-10:33 21.33 14.69 0.132708E+10 848.79 24-MAR-21:49 13.00 11.39
April 0.408109E+10 2098.26 30-APR-10:33 25.67 16.97 0.133088E+10 859.87 27-APR-21:49 25.67 16.97
May 0.424239E+10 2099.24 04-MAY-10:33 22.00 15.73 0.138470E+10 877.69 04-MAY-21:49 17.00 15.07
June 0.431197E+10 2151.16 25-JUN-10:33 23.00 17.26 0.137936E+10 886.67 30-JUN-22:10 16.13 16.03
July 0.471035E+10 2248.67 23-JUL-10:33 25.67 20.39 0.146570E+10 901.31 31-JUL-21:49 18.75 17.98
August 0.478165E+10 2268.17 19-AUG-10:33 24.67 20.11 0.148790E+10 912.16 18-AUG-21:49 24.67 20.11
September 0.446763E+10 2357.60 30-SEP-10:33 30.57 17.23 0.141089E+10 925.90 29-SEP-22:10 30.57 17.23
October 0.469718E+10 2367.29 17-OCT-10:33 31.00 16.57 0.147927E+10 948.76 17-OCT-21:40 18.00 14.57
November 0.410889E+10 2120.89 19-NOV-11:33 26.00 15.32 0.134788E+10 878.76 01-NOV-00:10 26.00 15.32
December 0.415970E+10 2032.54 05-DEC-11:33 23.33 12.89 0.137603E+10 868.43 05-DEC-23:10 17.33 9.21
                     
Annual Sum or Average 0.511799E+11         0.165522E+11        
Minimum of Months 0.363365E+10 1981.93   1.00 -0.3 0.121876E+10 848.79   13.00 8.35
Maximum of Months 0.478165E+10 2367.29   31.00 20.39 0.148790E+10 948.76   30.57 20.11



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.494545E+09 2866.89 14-JAN-16:02 23.00 12.42 97148379.18 56.69 31-JAN-22:30 12.05 10.63
February 0.439295E+09 2818.64 03-FEB-16:02 20.50 10.05 87352183.23 56.70 17-FEB-00:10 12.00 11.46
March 0.492509E+09 2883.92 11-MAR-16:02 21.33 12.81 96796110.06 56.69 23-MAR-21:19 13.67 13.10
April 0.948196E+09 2892.67 01-APR-15:01 22.83 11.17 94733586.06 56.69 26-APR-03:49 13.00 11.97
May 0.882761E+09 2731.91 04-MAY-15:02 22.00 16.32 97800930.88 56.69 18-MAY-00:00 12.00 10.91
June 0.120582E+10 2768.52 28-JUN-15:02 22.83 18.37 95074684.25 56.69 30-JUN-00:10 17.00 16.90
July 0.167381E+10 2860.19 18-JUL-15:02 26.00 20.07 98575921.61 56.69 24-JUL-00:10 17.00 16.37
August 0.170555E+10 2849.59 06-AUG-15:02 24.83 20.15 98696536.47 56.69 10-AUG-23:49 17.08 16.63
September 0.135116E+10 2730.44 08-SEP-15:02 21.83 18.03 95167538.84 56.69 25-SEP-22:40 16.00 15.59
October 0.129651E+10 3075.83 15-OCT-15:02 30.83 15.40 98079855.38 56.69 17-OCT-21:30 18.00 14.67
November 0.623662E+09 2812.75 19-NOV-09:02 24.33 12.78 94385893.96 56.69 10-NOV-23:10 24.33 12.78
December 0.558417E+09 2882.53 05-DEC-16:02 22.67 12.42 97260011.09 56.69 06-DEC-22:19 15.00 9.64
                     
Annual Sum or Average 0.116722E+11         0.115107E+10        
Minimum of Months 0.439295E+09 2730.44   20.50 10.05 87352183.23 56.69   12.00 9.64
Maximum of Months 0.170555E+10 3075.83   30.83 20.15 98696536.47 56.70   24.33 16.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.191627E+09 2714.13 14-JAN-16:02 23.00 12.42 95597484.12 56.69 31-JAN-04:19 12.00 12.00
February 0.209540E+09 2665.65 03-FEB-16:02 20.50 10.05 86420922.34 56.69 24-FEB-00:20 13.00 11.87
March 0.305090E+09 2737.82 11-MAR-16:02 21.33 12.81 96050377.57 56.69 23-MAR-21:19 13.67 13.10
April 0.752991E+09 2757.61 01-APR-15:01 22.83 11.17 94285350.29 56.69 14-APR-01:00 14.00 12.84
May 0.837611E+09 2643.24 17-MAY-15:02 21.67 15.72 97686658.43 56.69 20-MAY-03:39 13.00 10.96
June 0.121092E+10 2676.51 28-JUN-15:02 22.83 18.37 95056473.21 56.69 25-JUN-23:00 22.83 18.37
July 0.164351E+10 2768.19 18-JUL-15:02 26.00 20.07 98551208.80 56.69 19-JUL-21:10 18.00 17.89
August 0.153333E+10 2766.27 18-AUG-15:02 26.50 20.71 98565243.38 56.69 25-AUG-23:10 16.10 16.03
September 0.105721E+10 2668.61 10-SEP-15:02 22.00 17.30 94755097.29 56.69 27-SEP-21:00 16.70 15.11
October 0.892262E+09 2919.66 16-OCT-15:02 29.83 15.97 97446999.65 56.69 11-OCT-02:00 29.83 15.97
November 0.252589E+09 2625.90 27-NOV-16:01 19.67 7.55 93230658.31 56.69 13-NOV-22:10 19.67 7.55
December 0.195844E+09 2728.31 05-DEC-16:02 22.67 12.42 95670407.38 56.69 06-DEC-00:30 16.00 8.84
                     
Annual Sum or Average 0.908252E+10         0.114332E+10        
Minimum of Months 0.191627E+09 2625.90   19.67 7.55 86420922.34 56.69   12.00 7.55
Maximum of Months 0.164351E+10 2919.66   29.83 20.71 98565243.38 56.69   29.83 18.37



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.891740E+09 1564.22 14-JAN-16:02 23.00 12.42 98338808.66 56.69 19-JAN-22:19 14.00 12.84
February 0.607570E+09 1524.80 03-FEB-16:02 20.50 10.05 88258265.26 56.69 01-FEB-22:30 20.50 10.05
March 0.523269E+09 1541.67 10-MAR-16:02 21.67 12.40 97500518.58 56.69 24-MAR-21:10 13.00 11.77
April 0.614892E+09 1552.40 01-APR-15:01 22.83 11.17 94774648.32 56.69 11-APR-21:10 13.83 13.83
May 0.440836E+09 1458.93 03-MAY-15:02 21.83 15.33 97349318.14 56.69 04-MAY-23:40 16.00 14.76
June 0.539206E+09 1440.38 20-JUN-15:02 21.83 15.76 94508062.05 56.69 29-JUN-22:30 16.50 16.50
July 0.767135E+09 1452.95 31-JUL-15:02 25.67 20.38 98195895.98 56.69 31-JUL-21:10 18.95 17.72
August 0.933334E+09 1518.08 19-AUG-15:02 25.83 18.86 98493088.45 56.69 21-AUG-21:10 15.17 13.86
September 0.943124E+09 1486.11 30-SEP-18:02 22.67 16.87 95091378.03 56.69 26-SEP-21:00 22.67 16.87
October 0.115733E+10 1646.35 16-OCT-15:02 29.83 15.97 98430425.11 56.70 17-OCT-21:19 18.00 14.77
November 0.900462E+09 1575.24 19-NOV-09:02 24.33 12.78 95311041.65 56.69 20-NOV-23:10 14.00 12.84
December 0.974676E+09 1565.90 05-DEC-16:02 22.67 12.42 98435257.81 56.69 07-DEC-22:10 12.67 12.59
                     
Annual Sum or Average 0.929357E+10         0.115469E+10        
Minimum of Months 0.440836E+09 1440.38   20.50 10.05 88258265.26 56.69   12.67 10.05
Maximum of Months 0.115733E+10 1646.35   29.83 20.38 98493088.45 56.70   22.67 17.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.350092E+11 19641.94 18-JAN-22:10 16.83 13.41 0.189779E+11 11347.81 27-JAN-04:19 6.00 5.49
February 0.318572E+11 19019.07 01-FEB-23:00 13.00 11.29 0.172260E+11 11347.92 28-FEB-04:19 11.00 8.85
March 0.355214E+11 19387.93 24-MAR-22:00 13.00 11.29 0.191390E+11 11347.97 31-MAR-03:20 6.33 5.52
April 0.363203E+11 20332.55 26-APR-22:00 16.00 15.39 0.185887E+11 11348.00 18-APR-03:20 16.00 15.39
May 0.381066E+11 20758.19 04-MAY-21:10 17.00 15.07 0.192407E+11 11347.76 16-MAY-23:19 12.00 11.28
June 0.386578E+11 20979.41 27-JUN-22:00 17.00 16.37 0.186911E+11 11347.75 07-JUN-23:19 17.00 16.37
July 0.411124E+11 21220.96 19-JUL-22:00 18.00 17.35 0.192621E+11 11347.77 23-JUL-23:19 17.67 16.59
August 0.409595E+11 21058.94 17-AUG-21:10 19.00 17.66 0.193339E+11 11347.76 20-AUG-23:19 16.67 16.04
September 0.380932E+11 21633.43 29-SEP-21:10 24.58 13.52 0.186268E+11 11347.76 24-SEP-23:19 24.58 13.52
October 0.389860E+11 21252.04 04-OCT-22:00 21.00 18.98 0.192143E+11 11347.76 12-OCT-23:19 12.67 8.42
November 0.346710E+11 19265.95 10-NOV-23:00 15.00 13.80 0.184675E+11 11347.85 24-NOV-04:19 7.33 1.09
December 0.350609E+11 19734.93 05-DEC-23:00 18.00 9.37 0.190329E+11 11348.83 01-DEC-00:49 18.00 9.37
                     
Annual Sum or Average 0.444355E+12         0.225801E+12        
Minimum of Months 0.318572E+11 19019.07   13.00 9.37 0.172260E+11 11347.75   6.00 1.09
Maximum of Months 0.411124E+11 21633.43   24.58 18.98 0.193339E+11 11348.83   24.58 16.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.383504E+11 21236.84 18-JAN-22:10 16.83 13.41 0.191205E+11 11347.84 06-JAN-04:19 16.83 13.41
February 0.349555E+11 20667.54 01-FEB-22:10 13.00 11.77 0.173401E+11 11347.96 28-FEB-04:19 11.00 8.85
March 0.390238E+11 20929.87 24-MAR-21:10 13.00 11.77 0.192734E+11 11348.02 31-MAR-03:20 6.33 5.52
April 0.396484E+11 21803.24 26-APR-22:00 16.00 15.39 0.186615E+11 11348.03 18-APR-03:20 16.00 15.39
May 0.415884E+11 22197.20 04-MAY-21:10 17.00 15.07 0.193029E+11 11347.76 16-MAY-23:19 12.00 11.28
June 0.419058E+11 22341.63 27-JUN-21:50 17.00 16.37 0.187301E+11 11347.76 07-JUN-23:19 17.00 16.37
July 0.442766E+11 22546.24 19-JUL-22:00 18.00 17.35 0.192895E+11 11347.78 23-JUL-23:19 17.67 16.59
August 0.440215E+11 22381.49 17-AUG-21:10 19.00 17.66 0.193636E+11 11347.77 20-AUG-23:19 16.67 16.04
September 0.411529E+11 22927.48 29-SEP-21:10 24.58 13.52 0.186683E+11 11347.77 24-SEP-23:19 24.58 13.52
October 0.420423E+11 22569.84 04-OCT-22:00 21.00 18.98 0.192633E+11 11347.76 12-OCT-23:19 12.67 8.42
November 0.378502E+11 20885.67 10-NOV-22:10 15.00 13.80 0.185711E+11 11347.88 24-NOV-04:19 7.33 1.09
December 0.383614E+11 21247.39 05-DEC-23:00 18.00 9.37 0.191589E+11 11349.07 01-DEC-00:49 18.00 9.37
                     
Annual Sum or Average 0.483177E+12         0.226743E+12        
Minimum of Months 0.349555E+11 20667.54   13.00 9.37 0.173401E+11 11347.76   6.33 1.09
Maximum of Months 0.442766E+11 22927.48   24.58 18.98 0.193636E+11 11349.07   24.58 16.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.520488E+11 28217.33 20-JAN-11:45 21.83 15.77 0.188123E+11 11319.73 07-JAN-18:19 21.83 15.77
February 0.468903E+11 28098.85 01-FEB-11:45 25.50 14.48 0.170017E+11 11319.74 25-FEB-18:19 11.00 9.85
March 0.521940E+11 28890.45 19-MAR-10:50 19.67 15.35 0.188236E+11 11319.63 25-MAR-17:19 11.00 10.47
April 0.522099E+11 29394.41 30-APR-10:33 25.67 16.97 0.182260E+11 11319.58 08-APR-17:19 25.67 16.97
May 0.539147E+11 29095.03 04-MAY-10:33 22.00 15.73 0.188357E+11 11319.57 20-MAY-17:19 17.00 12.68
June 0.533030E+11 29431.46 25-JUN-10:33 23.00 17.26 0.182396E+11 11319.63 24-JUN-17:19 23.00 17.26
July 0.561277E+11 29906.79 23-JUL-10:33 25.67 20.39 0.188471E+11 11319.63 08-JUL-17:19 25.67 20.39
August 0.562246E+11 29803.87 19-AUG-10:33 24.67 20.11 0.188547E+11 11319.65 19-AUG-17:19 23.67 17.53
September 0.532314E+11 30317.49 30-SEP-10:50 30.78 17.57 0.182367E+11 11319.61 30-SEP-17:19 25.00 17.45
October 0.546034E+11 30146.57 15-OCT-10:50 31.83 16.40 0.188407E+11 11319.58 28-OCT-17:19 16.67 14.39
November 0.507883E+11 28840.06 19-NOV-11:50 26.00 15.39 0.182159E+11 11319.67 25-NOV-18:19 13.00 11.13
December 0.520030E+11 28120.85 05-DEC-11:33 23.33 12.89 0.188193E+11 11319.71 02-DEC-18:19 23.33 12.89
                     
Annual Sum or Average 0.633539E+12         0.221753E+12        
Minimum of Months 0.468903E+11 28098.85   19.67 12.89 0.170017E+11 11319.57   11.00 9.85
Maximum of Months 0.562246E+11 30317.49   31.83 20.39 0.188547E+11 11319.74   25.67 20.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.782994E+10 4283.16 20-JAN-11:33 21.67 15.71 0.137325E+10 889.78 18-JAN-22:40 21.67 15.71
February 0.708182E+10 4091.67 01-FEB-11:45 25.50 14.48 0.123921E+10 868.27 01-FEB-22:40 13.00 11.48
March 0.767177E+10 4264.77 11-MAR-11:33 24.00 13.82 0.136854E+10 885.90 24-MAR-21:40 13.00 11.48
April 0.830943E+10 4420.48 30-APR-10:33 25.67 16.97 0.139001E+10 911.46 27-APR-21:40 25.67 16.97
May 0.859691E+10 4495.64 04-MAY-10:33 22.00 15.73 0.144123E+10 934.99 04-MAY-21:40 17.00 15.07
June 0.889573E+10 4572.91 30-JUN-10:33 23.33 17.95 0.145481E+10 942.11 27-JUN-21:40 23.33 17.95
July 0.978240E+10 4797.85 30-JUL-10:33 24.67 20.10 0.155347E+10 960.40 31-JUL-21:40 18.80 17.92
August 0.989453E+10 4791.63 19-AUG-10:33 24.67 20.11 0.157263E+10 965.82 18-AUG-21:40 24.67 20.11
September 0.911634E+10 5724.55 30-SEP-13:40 32.00 17.36 0.147335E+10 992.55 29-SEP-21:40 32.00 17.36
October 0.945229E+10 5648.22 16-OCT-12:50 34.42 16.94 0.152791E+10 995.52 16-OCT-21:40 19.33 11.10
November 0.801308E+10 4509.46 19-NOV-11:33 26.00 15.32 0.136441E+10 901.22 01-NOV-00:10 26.00 15.32
December 0.802628E+10 4335.54 19-DEC-11:33 25.00 11.16 0.138715E+10 901.73 05-DEC-22:40 25.00 11.16
                     
Annual Sum or Average 0.102671E+12         0.171459E+11        
Minimum of Months 0.708182E+10 4091.67   21.67 11.16 0.123921E+10 868.27   13.00 11.10
Maximum of Months 0.989453E+10 5724.55   34.42 20.11 0.157263E+10 995.52   32.00 20.11



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 170095.71 73.70 30-MAR-06:05 5.58
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 170095.71      
Minimum of Months 0.00 0.00   5.58
Maximum of Months 170095.71 73.70   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 66438499.63 1520.23 01-JAN-19:02 11.00
February 41252291.56 1558.87 25-FEB-16:02 11.00
March 82965259.18 1580.00 30-MAR-08:62 9.50
April 10046261.80 619.28 11-APR-08:03 14.83
May 5950742.98 627.38 28-MAY-08:03 18.17
June 580128.50 517.39 05-JUN-08:03 18.17
July 505060.59 664.18 23-JUL-08:05 23.33
August 531276.00 646.21 19-AUG-08:05 22.33
September 589330.40 538.87 20-SEP-08:03 16.33
October 1077820.41 544.04 14-OCT-08:05 27.67
November 10040119.04 851.78 24-NOV-16:03 15.83
December 39667289.75 1091.74 12-DEC-19:02 9.67
         
Annual Sum or Average 0.259644E+09      
Minimum of Months 505060.59 517.39   9.50
Maximum of Months 82965259.18 1580.00   27.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.160926E+09 1570.27 03-JAN-09:02 11.33
February 74604346.43 1554.81 25-FEB-16:02 11.00
March 0.116602E+09 1580.71 30-MAR-08:62 9.50
April 13053030.61 1246.77 01-APR-08:62 15.67
May 5917911.66 618.11 14-MAY-08:03 15.17
June 514791.92 535.47 02-JUN-08:03 18.17
July 555614.09 482.10 22-JUL-08:05 21.17
August 647915.98 643.94 19-AUG-08:05 22.33
September 961356.97 582.10 03-SEP-08:03 18.33
October 2307041.04 616.96 24-OCT-15:04 19.00
November 39433164.10 1026.16 05-NOV-08:62 11.33
December 0.116428E+09 1565.98 13-DEC-09:02 11.33
         
Annual Sum or Average 0.531951E+09      
Minimum of Months 514791.92 482.10   9.50
Maximum of Months 0.160926E+09 1580.71   22.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 3171908.80 446.12 10-JAN-16:02 13.83
February 1051879.35 307.64 04-FEB-16:03 16.83
March 1558425.91 447.82 30-MAR-08:62 9.50
April 481420.43 279.41 28-APR-15:04 17.00
May 567291.62 281.18 20-MAY-15:05 18.00
June 175833.77 191.31 09-JUN-15:05 18.83
July 75816.34 143.64 18-JUL-08:05 21.50
August 214817.15 178.84 15-AUG-08:05 22.50
September 291790.06 234.46 02-SEP-15:04 18.83
October 351802.32 276.97 16-OCT-08:05 28.50
November 1283943.67 296.31 04-NOV-15:03 16.58
December 1613776.36 446.17 13-DEC-16:02 12.83
         
Annual Sum or Average 10838705.78      
Minimum of Months 75816.34 143.64   9.50
Maximum of Months 3171908.80 447.82   28.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 65964712.22 1261.69 01-JAN-19:02 11.00
February 50441101.47 1524.93 25-FEB-16:02 11.00
March 93696044.26 1535.84 28-MAR-08:62 9.33
April 9592168.33 671.23 15-APR-15:04 17.00
May 7844372.80 533.81 06-MAY-18:03 15.67
June 932270.67 477.65 09-JUN-18:03 16.83
July 253075.62 307.82 05-JUL-18:05 17.83
August 103696.85 287.46 01-AUG-18:05 17.83
September 231089.56 364.42 18-SEP-15:05 19.83
October 626693.19 336.68 06-OCT-15:05 21.00
November 15066242.83 709.38 24-NOV-16:03 15.83
December 46255042.28 1401.07 12-DEC-19:02 9.67
         
Annual Sum or Average 0.291007E+09      
Minimum of Months 103696.85 287.46   9.33
Maximum of Months 93696044.26 1535.84   21.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.153680E+09 1508.20 02-JAN-16:02 12.67
February 94083253.74 1519.74 25-FEB-16:02 11.00
March 0.130706E+09 1526.53 28-MAR-08:62 9.33
April 14071284.42 716.12 22-APR-15:03 16.83
May 8428651.45 521.38 06-MAY-18:03 15.67
June 698137.69 461.98 07-JUN-15:05 19.00
July 89076.48 278.29 12-JUL-18:05 18.83
August 144526.14 308.81 27-AUG-18:05 17.67
September 641580.17 464.38 24-SEP-15:05 18.83
October 3130960.82 522.25 24-OCT-15:04 19.00
November 53036317.86 770.10 14-NOV-16:03 15.83
December 0.125429E+09 1499.47 13-DEC-16:02 12.83
         
Annual Sum or Average 0.584139E+09      
Minimum of Months 89076.48 278.29   9.33
Maximum of Months 0.153680E+09 1526.53   19.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.186812E+09 1847.02 03-JAN-09:02 11.33
February 0.147956E+09 1887.64 25-FEB-16:02 11.00
March 0.211131E+09 1904.50 30-MAR-08:62 9.50
April 34716246.52 1615.16 01-APR-08:62 15.67
May 26996450.56 802.29 12-MAY-15:05 15.83
June 2134821.64 523.81 23-JUN-08:03 18.50
July 479014.94 528.48 23-JUL-08:05 23.33
August 538096.73 500.35 19-AUG-08:05 22.33
September 674364.03 445.02 29-SEP-08:05 29.67
October 11602761.68 716.36 24-OCT-15:04 19.00
November 75425919.13 1023.39 24-NOV-09:02 14.17
December 0.156488E+09 1850.36 13-DEC-09:02 11.33
         
Annual Sum or Average 0.854954E+09      
Minimum of Months 479014.94 445.02   9.50
Maximum of Months 0.211131E+09 1904.50   29.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.385208E+09 1891.61 03-JAN-09:02 11.33
February 0.244052E+09 1881.60 25-FEB-16:02 11.00
March 0.287030E+09 1901.54 30-MAR-08:62 9.50
April 46974798.56 1832.40 01-APR-08:62 15.67
May 27331347.07 694.41 20-MAY-08:04 15.17
June 2103036.57 524.92 08-JUN-15:05 18.00
July 490810.84 575.58 23-JUL-08:05 23.33
August 627608.12 497.23 19-AUG-08:05 22.33
September 1291673.45 456.57 06-SEP-08:03 19.33
October 28269139.95 1806.65 30-OCT-08:62 17.67
November 0.175245E+09 1848.82 05-NOV-08:62 11.33
December 0.340835E+09 1889.07 13-DEC-09:02 11.33
         
Annual Sum or Average 0.153946E+10      
Minimum of Months 490810.84 456.57   9.50
Maximum of Months 0.385208E+09 1901.54   23.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 9438391.51 242.33 01-JAN-16:05 12.67
February 11952939.11 977.26 25-FEB-16:02 11.00
March 38654349.03 990.07 28-MAR-08:62 9.33
April 4694571.38 390.89 17-APR-15:05 17.33
May 6744635.21 611.32 12-MAY-15:05 15.83
June 568390.82 320.85 08-JUN-15:05 18.00
July 405308.71 273.54 29-JUL-08:05 20.33
August 312123.64 262.57 06-AUG-08:05 22.33
September 123314.07 215.52 18-SEP-18:04 15.67
October 328703.63 418.78 23-OCT-15:05 17.00
November 447944.22 393.70 24-NOV-16:05 15.83
December 5503750.80 197.09 13-DEC-04:30 7.00
         
Annual Sum or Average 79174422.13      
Minimum of Months 123314.07 197.09   7.00
Maximum of Months 38654349.03 990.07   22.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.147273E+11 14185.34 02-JAN-20:10 0.127587E+11 10113.80 02-JAN-20:10
February 0.132974E+11 14185.34 01-FEB-20:10 0.115208E+11 10113.80 01-FEB-20:10
March 0.147727E+11 14185.34 01-MAR-20:10 0.127855E+11 10113.80 01-MAR-20:10
April 0.142280E+11 14185.34 03-APR-19:10 0.123314E+11 10113.80 03-APR-19:10
May 0.147528E+11 14185.34 01-MAY-19:10 0.127741E+11 10113.80 01-MAY-19:10
June 0.142932E+11 14185.34 01-JUN-19:10 0.123716E+11 10113.80 01-JUN-19:10
July 0.146876E+11 14185.34 03-JUL-19:10 0.127338E+11 10113.80 03-JUL-19:10
August 0.147784E+11 14185.34 01-AUG-19:10 0.127894E+11 10113.80 01-AUG-19:10
September 0.142337E+11 14185.34 01-SEP-19:10 0.123352E+11 10113.80 01-SEP-19:10
October 0.147216E+11 14185.34 02-OCT-19:10 0.127549E+11 10113.80 02-OCT-19:10
November 0.142819E+11 14185.34 01-NOV-19:10 0.123659E+11 10113.80 01-NOV-19:10
December 0.146876E+11 14185.34 01-DEC-20:10 0.127338E+11 10113.80 01-DEC-20:10
             
Annual Sum or Average 0.173462E+12     0.150255E+12    
Minimum of Months 0.132974E+11 14185.34   0.115208E+11 10113.80  
Maximum of Months 0.147784E+11 14185.34   0.127894E+11 10113.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.731324E+09 704.41 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.660319E+09 704.41 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.733578E+09 704.41 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.706528E+09 704.41 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.732592E+09 704.41 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.709769E+09 704.41 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.729351E+09 704.41 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.733860E+09 704.41 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.706810E+09 704.41 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.731042E+09 704.41 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.709205E+09 704.41 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.729351E+09 704.41 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.861373E+10     0.101856E+11    
Minimum of Months 0.660319E+09 704.41   0.780982E+09 685.60  
Maximum of Months 0.733860E+09 704.41   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.846876E+09 815.72 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.764651E+09 815.72 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.849486E+09 815.72 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.818162E+09 815.72 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.848344E+09 815.72 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.821915E+09 815.72 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.844592E+09 815.72 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.849812E+09 815.72 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.818489E+09 815.72 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.846549E+09 815.72 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.821262E+09 815.72 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.844592E+09 815.72 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.997473E+10     0.117950E+11    
Minimum of Months 0.764651E+09 815.72   0.904380E+09 793.93  
Maximum of Months 0.849812E+09 815.72   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.141236E+10 1360.40 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.127524E+10 1360.40 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.141672E+10 1360.40 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.136448E+10 1360.40 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.141481E+10 1360.40 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.137074E+10 1360.40 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.140855E+10 1360.40 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.141726E+10 1360.40 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.136502E+10 1360.40 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.141182E+10 1360.40 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.136965E+10 1360.40 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.140855E+10 1360.40 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.166352E+11     0.124712E+11    
Minimum of Months 0.127524E+10 1360.40   0.956227E+09 839.45  
Maximum of Months 0.141726E+10 1360.40   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.236418E+09 227.72 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.213464E+09 227.72 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.237147E+09 227.72 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.228402E+09 227.72 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.236828E+09 227.72 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.229450E+09 227.72 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.235780E+09 227.72 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.237238E+09 227.72 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.228493E+09 227.72 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.236327E+09 227.72 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.229268E+09 227.72 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.235780E+09 227.72 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.278459E+10     0.359760E+10    
Minimum of Months 0.213464E+09 227.72   0.275845E+09 242.16  
Maximum of Months 0.237238E+09 227.72   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.370859E+09 357.21 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.334852E+09 357.21 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.372002E+09 357.21 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.358285E+09 357.21 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.371502E+09 357.21 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.359929E+09 357.21 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.369859E+09 357.21 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.372145E+09 357.21 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.358428E+09 357.21 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.370717E+09 357.21 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.359643E+09 357.21 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.369859E+09 357.21 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.436808E+10     0.679355E+11    
Minimum of Months 0.334852E+09 357.21   0.520895E+10 4572.80  
Maximum of Months 0.372145E+09 357.21   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.158799E+10 1761.91 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.141502E+10 1761.91 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.155823E+10 1761.91 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.146440E+10 1761.91 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.148347E+10 1761.91 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.143200E+10 1761.91 01-JUN-19:10 0.118076E+10 965.27 01-JUN-19:10
July 0.147724E+10 1761.91 03-JUL-19:10 0.121533E+10 965.27 03-JUL-19:10
August 0.150429E+10 1761.91 01-AUG-19:10 0.122063E+10 965.27 01-AUG-19:10
September 0.149607E+10 1761.91 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.156731E+10 1761.91 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.153155E+10 1761.91 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.158133E+10 1761.91 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.180989E+11     0.143405E+11    
Minimum of Months 0.141502E+10 1761.91   0.109956E+10 965.27  
Maximum of Months 0.158799E+10 1761.91   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104088E+11 10265.18 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.937997E+10 10265.18 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.104087E+11 10265.18 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.998899E+10 10265.18 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.103263E+11 10265.18 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.999821E+10 10265.18 01-JUN-19:10 0.122682E+11 10029.21 01-JUN-19:10
July 0.102806E+11 10265.18 03-JUL-19:10 0.126273E+11 10029.21 03-JUL-19:10
August 0.103603E+11 10265.18 01-AUG-19:10 0.126824E+11 10029.21 01-AUG-19:10
September 0.100278E+11 10265.18 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.103893E+11 10265.18 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.100861E+11 10265.18 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.103787E+11 10265.18 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.122034E+12     0.148998E+12    
Minimum of Months 0.937997E+10 10265.18   0.114244E+11 10029.21  
Maximum of Months 0.104088E+11 10265.18   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85091918.49 76.99 01-JAN-19:10 0.255708E+09 232.19 01-JAN-08:09
February 76846309.13 76.99 01-FEB-20:10 0.230956E+09 232.19 01-FEB-07:10
March 84415649.14 76.99 01-MAR-20:10 0.255355E+09 232.19 01-MAR-07:10
April 82445007.08 76.99 01-APR-18:10 0.247516E+09 232.19 01-APR-07:10
May 84753783.81 76.99 01-MAY-19:10 0.255532E+09 232.19 01-MAY-06:10
June 81790910.76 76.99 01-JUN-19:10 0.247163E+09 232.19 01-JUN-06:10
July 85418966.65 76.99 01-JUL-18:10 0.255885E+09 232.19 01-JUL-07:10
August 84415649.14 76.99 01-AUG-19:10 0.255355E+09 232.19 01-AUG-06:10
September 82467180.11 76.99 01-SEP-19:10 0.247516E+09 232.19 01-SEP-06:10
October 85080831.98 76.99 01-OCT-18:10 0.255708E+09 232.19 01-OCT-07:10
November 82117958.92 76.99 01-NOV-19:10 0.247340E+09 232.19 01-NOV-06:10
December 85430053.17 76.99 01-DEC-20:10 0.255885E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.100027E+10     0.300992E+10    
Minimum of Months 76846309.13 76.99   0.230956E+09 232.19  
Maximum of Months 85430053.17 76.99   0.255885E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85115186.72 77.01 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 76867322.62 77.01 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 84438732.44 77.01 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 82467551.52 77.01 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 84776959.58 77.01 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 81813276.33 77.01 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 85442324.32 77.01 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 84438732.44 77.01 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 82489730.61 77.01 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 85104097.18 77.01 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 82140413.93 77.01 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 85453413.86 77.01 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.100055E+10     0.301074E+10    
Minimum of Months 76867322.62 77.01   0.231020E+09 232.26  
Maximum of Months 85453413.86 77.01   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.232638E+10 2240.78 02-JAN-20:10 0.00 0.00
February 0.210051E+10 2240.78 01-FEB-20:10 0.00 0.00
March 0.233355E+10 2240.78 01-MAR-20:10 0.00 0.00
April 0.224750E+10 2240.78 03-APR-19:10 0.00 0.00
May 0.233041E+10 2240.78 01-MAY-19:10 0.00 0.00
June 0.225781E+10 2240.78 01-JUN-19:10 0.00 0.00
July 0.232011E+10 2240.78 03-JUL-19:10 0.00 0.00
August 0.233445E+10 2240.78 01-AUG-19:10 0.00 0.00
September 0.224840E+10 2240.78 01-SEP-19:10 0.00 0.00
October 0.232548E+10 2240.78 02-OCT-19:10 0.00 0.00
November 0.225602E+10 2240.78 01-NOV-19:10 0.00 0.00
December 0.232011E+10 2240.78 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.274007E+11     0.00 0.00
Minimum of Months 0.210051E+10 2240.78   0.00 0.00
Maximum of Months 0.233445E+10 2240.78   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85115186.72 77.01 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 76867322.62 77.01 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 84438732.44 77.01 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 82467551.52 77.01 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 84776959.58 77.01 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 81813276.33 77.01 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 85442324.32 77.01 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 84438732.44 77.01 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 82489730.61 77.01 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 85104097.18 77.01 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 82140413.93 77.01 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 85453413.86 77.01 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.100055E+10     0.301074E+10    
Minimum of Months 76867322.62 77.01   0.231020E+09 232.26  
Maximum of Months 85453413.86 77.01   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.302110E+10 3094.06 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.270209E+10 3094.06 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.298356E+10 3094.06 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.283147E+10 3094.06 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.289692E+10 3094.06 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.279538E+10 3094.06 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.287854E+10 3094.06 03-JUL-19:10 0.149358E+11 6747.90 01-JUL-06:10
August 0.292152E+10 3094.06 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.286757E+10 3094.06 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.300238E+10 3094.06 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.291991E+10 3094.06 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.301516E+10 3094.06 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.348356E+11     0.175857E+12    
Minimum of Months 0.270209E+10 3094.06   0.134904E+11 6747.90  
Maximum of Months 0.302110E+10 3094.06   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.302110E+10 3094.06 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.270209E+10 3094.06 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.298356E+10 3094.06 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.283147E+10 3094.06 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.289692E+10 3094.06 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.279538E+10 3094.06 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.287854E+10 3094.06 03-JUL-19:10 0.149358E+11 6747.90 01-JUL-06:10
August 0.292152E+10 3094.06 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.286757E+10 3094.06 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.300238E+10 3094.06 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.291991E+10 3094.06 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.301516E+10 3094.06 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.348356E+11     0.175857E+12    
Minimum of Months 0.270209E+10 3094.06   0.134904E+11 6747.90  
Maximum of Months 0.302110E+10 3094.06   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.113146E+10 1089.83 02-JAN-20:10 0.368383E+11 16487.34 01-JAN-07:10
February 0.102161E+10 1089.83 01-FEB-20:10 0.332733E+11 16487.34 01-FEB-07:10
March 0.113495E+10 1089.83 01-MAR-20:10 0.368383E+11 16487.34 01-MAR-07:10
April 0.109310E+10 1089.83 03-APR-19:10 0.356500E+11 16487.34 01-APR-06:10
May 0.113342E+10 1089.83 01-MAY-19:10 0.368383E+11 16487.34 01-MAY-06:10
June 0.109811E+10 1089.83 01-JUN-19:10 0.356500E+11 16487.34 01-JUN-06:10
July 0.112841E+10 1089.83 03-JUL-19:10 0.368383E+11 16487.34 01-JUL-06:10
August 0.113539E+10 1089.83 01-AUG-19:10 0.368383E+11 16487.34 01-AUG-06:10
September 0.109354E+10 1089.83 01-SEP-19:10 0.356500E+11 16487.34 01-SEP-06:10
October 0.113103E+10 1089.83 02-OCT-19:10 0.368383E+11 16487.34 01-OCT-06:10
November 0.109724E+10 1089.83 01-NOV-19:10 0.356500E+11 16487.34 01-NOV-06:10
December 0.112841E+10 1089.83 01-DEC-20:10 0.368383E+11 16487.34 01-DEC-07:10
             
Annual Sum or Average 0.133267E+11     0.433742E+12    
Minimum of Months 0.102161E+10 1089.83   0.332733E+11 16487.34  
Maximum of Months 0.113539E+10 1089.83   0.368383E+11 16487.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.246211E+10 2371.52 02-JAN-20:10 0.00 0.00
February 0.222306E+10 2371.52 01-FEB-20:10 0.00 0.00
March 0.246970E+10 2371.52 01-MAR-20:10 0.00 0.00
April 0.237864E+10 2371.52 03-APR-19:10 0.00 0.00
May 0.246638E+10 2371.52 01-MAY-19:10 0.00 0.00
June 0.238954E+10 2371.52 01-JUN-19:10 0.00 0.00
July 0.245547E+10 2371.52 03-JUL-19:10 0.00 0.00
August 0.247065E+10 2371.52 01-AUG-19:10 0.00 0.00
September 0.237958E+10 2371.52 01-SEP-19:10 0.00 0.00
October 0.246116E+10 2371.52 02-OCT-19:10 0.00 0.00
November 0.238765E+10 2371.52 01-NOV-19:10 0.00 0.00
December 0.245547E+10 2371.52 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.289994E+11     0.00 0.00
Minimum of Months 0.222306E+10 2371.52   0.00 0.00
Maximum of Months 0.247065E+10 2371.52   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.147273E+11 0.127587E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.132974E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.147727E+11 0.127855E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.142280E+11 0.123314E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.147528E+11 0.127741E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.142932E+11 0.123716E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.146876E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.147784E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.142337E+11 0.123352E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.147216E+11 0.127549E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.142819E+11 0.123659E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.146876E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.173462E+12 0.150255E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.132974E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.147784E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.731324E+09 0.864900E+09 0.00 0.00 0.00 0.00 1038393.46 0.288313E+09
February 0.179968E+10 0.660319E+09 0.780982E+09 0.00 0.00 0.00 0.00 72921.62 0.248346E+09
March 0.199990E+10 0.733578E+09 0.866718E+09 0.00 0.00 0.00 0.00 0.00 0.288440E+09
April 0.192973E+10 0.706528E+09 0.835931E+09 0.00 0.00 0.00 0.00 1261625.66 0.202562E+09
May 0.199475E+10 0.732592E+09 0.865939E+09 0.00 0.00 0.00 0.00 139530.17 0.188926E+09
June 0.193394E+10 0.709769E+09 0.838659E+09 0.00 0.00 0.00 0.00 3052177.95 0.126852E+09
July 0.199054E+10 0.729351E+09 0.863211E+09 0.00 0.00 0.00 0.00 9490531.89 95417358.36
August 0.199896E+10 0.733860E+09 0.866978E+09 0.00 0.00 0.00 0.00 7854812.31 97633577.51
September 0.192879E+10 0.706810E+09 0.836191E+09 0.00 0.00 0.00 0.00 8061177.02 0.132076E+09
October 0.199148E+10 0.731042E+09 0.864640E+09 0.00 0.00 0.00 0.00 13977062.56 0.137482E+09
November 0.192552E+10 0.709205E+09 0.838269E+09 0.00 0.00 0.00 0.00 624448.73 0.246130E+09
December 0.199054E+10 0.729351E+09 0.863211E+09 0.00 0.00 0.00 0.00 395351.30 0.278766E+09
                   
Annual Sum or Average 0.234744E+11 0.861373E+10 0.101856E+11 0.00 0.00 0.00 0.00 45968032.69 0.233094E+10
Minimum of Months 0.179968E+10 0.660319E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 95417358.36
Maximum of Months 0.199990E+10 0.733860E+09 0.866978E+09 0.00 0.00 0.00 0.00 13977062.56 0.288440E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.846876E+09 0.100156E+10 0.00 0.00 0.00 0.00 758225.63 0.119297E+09
February 0.208403E+10 0.764651E+09 0.904380E+09 0.00 0.00 0.00 0.00 100611.29 0.105070E+09
March 0.231589E+10 0.849486E+09 0.100366E+10 0.00 0.00 0.00 0.00 121816.82 0.122735E+09
April 0.223463E+10 0.818162E+09 0.968011E+09 0.00 0.00 0.00 0.00 745605.55 90828083.45
May 0.230993E+10 0.848344E+09 0.100276E+10 0.00 0.00 0.00 0.00 91804.52 89125243.98
June 0.223950E+10 0.821915E+09 0.971170E+09 0.00 0.00 0.00 0.00 709157.42 63807591.80
July 0.230505E+10 0.844592E+09 0.999601E+09 0.00 0.00 0.00 0.00 3211081.49 49642874.31
August 0.231480E+10 0.849812E+09 0.100396E+10 0.00 0.00 0.00 0.00 3563588.07 48251706.30
September 0.223354E+10 0.818489E+09 0.968312E+09 0.00 0.00 0.00 0.00 3222857.34 59796706.93
October 0.230614E+10 0.846549E+09 0.100126E+10 0.00 0.00 0.00 0.00 6431651.28 61874726.80
November 0.222975E+10 0.821262E+09 0.970719E+09 0.00 0.00 0.00 0.00 529449.96 0.103976E+09
December 0.230505E+10 0.844592E+09 0.999601E+09 0.00 0.00 0.00 0.00 592127.03 0.116171E+09
                   
Annual Sum or Average 0.271834E+11 0.997473E+10 0.117950E+11 0.00 0.00 0.00 0.00 20077976.40 0.103057E+10
Minimum of Months 0.208403E+10 0.764651E+09 0.904380E+09 0.00 0.00 0.00 0.00 91804.52 48251706.30
Maximum of Months 0.231589E+10 0.849812E+09 0.100396E+10 0.00 0.00 0.00 0.00 6431651.28 0.122735E+09



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.141236E+10 0.105898E+10 0.00 0.00 0.00 0.00 2546882.88 0.257929E+09
February 0.440737E+09 0.127524E+10 0.956227E+09 0.00 0.00 0.00 0.00 399114.61 0.228203E+09
March 0.489771E+09 0.141672E+10 0.106120E+10 0.00 0.00 0.00 0.00 669590.68 0.268626E+09
April 0.472586E+09 0.136448E+10 0.102351E+10 0.00 0.00 0.00 0.00 2478283.81 0.195983E+09
May 0.488511E+09 0.141481E+10 0.106025E+10 0.00 0.00 0.00 0.00 296519.26 0.197713E+09
June 0.473617E+09 0.137074E+10 0.102685E+10 0.00 0.00 0.00 0.00 1446420.19 0.142647E+09
July 0.487480E+09 0.140855E+10 0.105691E+10 0.00 0.00 0.00 0.00 7283837.18 0.109846E+09
August 0.489542E+09 0.141726E+10 0.106152E+10 0.00 0.00 0.00 0.00 8871379.86 0.104040E+09
September 0.472357E+09 0.136502E+10 0.102382E+10 0.00 0.00 0.00 0.00 8322845.61 0.128005E+09
October 0.487709E+09 0.141182E+10 0.105866E+10 0.00 0.00 0.00 0.00 16443496.55 0.135001E+09
November 0.471555E+09 0.136965E+10 0.102637E+10 0.00 0.00 0.00 0.00 1968758.55 0.224891E+09
December 0.487480E+09 0.140855E+10 0.105691E+10 0.00 0.00 0.00 0.00 2479664.89 0.250922E+09
                   
Annual Sum or Average 0.574883E+10 0.166352E+11 0.124712E+11 0.00 0.00 0.00 0.00 53206794.06 0.224381E+10
Minimum of Months 0.440737E+09 0.127524E+10 0.956227E+09 0.00 0.00 0.00 0.00 296519.26 0.104040E+09
Maximum of Months 0.489771E+09 0.141726E+10 0.106152E+10 0.00 0.00 0.00 0.00 16443496.55 0.268626E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.236418E+09 0.305485E+09 0.00 0.00 0.00 0.00 1479296.60 0.146236E+09
February 0.339028E+09 0.213464E+09 0.275845E+09 0.00 0.00 0.00 0.00 237150.32 0.129057E+09
March 0.376747E+09 0.237147E+09 0.306128E+09 0.00 0.00 0.00 0.00 392646.72 0.152038E+09
April 0.363528E+09 0.228402E+09 0.295253E+09 0.00 0.00 0.00 0.00 1458931.33 0.110332E+09
May 0.375778E+09 0.236828E+09 0.305852E+09 0.00 0.00 0.00 0.00 195199.04 0.110922E+09
June 0.364321E+09 0.229450E+09 0.296217E+09 0.00 0.00 0.00 0.00 942408.51 79412600.27
July 0.374985E+09 0.235780E+09 0.304889E+09 0.00 0.00 0.00 0.00 4415580.84 60658109.62
August 0.376571E+09 0.237238E+09 0.306219E+09 0.00 0.00 0.00 0.00 5342705.06 57444006.33
September 0.363352E+09 0.228493E+09 0.295345E+09 0.00 0.00 0.00 0.00 4892357.93 71362558.48
October 0.375161E+09 0.236327E+09 0.305393E+09 0.00 0.00 0.00 0.00 9552244.55 75317151.49
November 0.362735E+09 0.229268E+09 0.296079E+09 0.00 0.00 0.00 0.00 1136254.90 0.127139E+09
December 0.374985E+09 0.235780E+09 0.304889E+09 0.00 0.00 0.00 0.00 1434106.14 0.142087E+09
                   
Annual Sum or Average 0.442217E+10 0.278459E+10 0.359760E+10 0.00 0.00 0.00 0.00 31478881.94 0.126200E+10
Minimum of Months 0.339028E+09 0.213464E+09 0.275845E+09 0.00 0.00 0.00 0.00 195199.04 57444006.33
Maximum of Months 0.376747E+09 0.237238E+09 0.306219E+09 0.00 0.00 0.00 0.00 9552244.55 0.152038E+09



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.370859E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 2619921.33 0.390754E+09
February 0.139600E+10 0.334852E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 368669.18 0.345827E+09
March 0.155131E+10 0.372002E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 473010.13 0.408715E+09
April 0.149688E+10 0.358285E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 2597591.39 0.293374E+09
May 0.154732E+10 0.371502E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 400305.54 0.290552E+09
June 0.150015E+10 0.359929E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 3103299.12 0.201309E+09
July 0.154405E+10 0.369859E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 13702254.85 0.148621E+09
August 0.155059E+10 0.372145E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 16309419.53 0.141875E+09
September 0.149615E+10 0.358428E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 12693254.67 0.180199E+09
October 0.154478E+10 0.370717E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 24459493.61 0.187858E+09
November 0.149361E+10 0.359643E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 2158144.06 0.333613E+09
December 0.154405E+10 0.369859E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 2249086.94 0.375754E+09
                   
Annual Sum or Average 0.182090E+11 0.436808E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 81134450.35 0.329845E+10
Minimum of Months 0.139600E+10 0.334852E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 368669.18 0.141875E+09
Maximum of Months 0.155131E+10 0.372145E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 24459493.61 0.408715E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.158799E+10 0.121771E+10 0.00 0.00 0.00 0.00 1925503.71 0.719253E+09
February 0.236489E+11 0.141502E+10 0.109956E+10 0.00 0.00 0.00 0.00 152115.54 0.623623E+09
March 0.262800E+11 0.155823E+10 0.122027E+10 0.00 0.00 0.00 0.00 0.00 0.719089E+09
April 0.253579E+11 0.146440E+10 0.117692E+10 0.00 0.00 0.00 0.00 2273405.77 0.525967E+09
May 0.262123E+11 0.148347E+10 0.121917E+10 0.00 0.00 0.00 0.00 283461.42 0.500884E+09
June 0.254132E+11 0.143200E+10 0.118076E+10 0.00 0.00 0.00 0.00 5589332.35 0.354956E+09
July 0.261570E+11 0.147724E+10 0.121533E+10 0.00 0.00 0.00 0.00 19861921.70 0.274005E+09
August 0.262677E+11 0.150429E+10 0.122063E+10 0.00 0.00 0.00 0.00 17304771.33 0.273417E+09
September 0.253456E+11 0.149607E+10 0.117729E+10 0.00 0.00 0.00 0.00 16907842.64 0.352067E+09
October 0.261693E+11 0.156731E+10 0.121734E+10 0.00 0.00 0.00 0.00 30633246.70 0.365141E+09
November 0.253025E+11 0.153155E+10 0.118021E+10 0.00 0.00 0.00 0.00 1381369.97 0.623527E+09
December 0.261570E+11 0.158133E+10 0.121533E+10 0.00 0.00 0.00 0.00 870813.12 0.698436E+09
                   
Annual Sum or Average 0.308468E+12 0.180989E+11 0.143405E+11 0.00 0.00 0.00 0.00 97183784.24 0.603036E+10
Minimum of Months 0.236489E+11 0.141502E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.273417E+09
Maximum of Months 0.262800E+11 0.158799E+10 0.122063E+10 0.00 0.00 0.00 0.00 30633246.70 0.719253E+09



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.104088E+11 0.126520E+11 0.00 0.00 0.00 0.00 7787640.83 0.207450E+10
February 0.702046E+11 0.937997E+10 0.114244E+11 0.00 0.00 0.00 0.00 952925.27 0.182330E+10
March 0.780153E+11 0.104087E+11 0.126786E+11 0.00 0.00 0.00 0.00 795061.10 0.211980E+10
April 0.752779E+11 0.998899E+10 0.122282E+11 0.00 0.00 0.00 0.00 8882238.87 0.156205E+10
May 0.778146E+11 0.103263E+11 0.126672E+11 0.00 0.00 0.00 0.00 1112364.40 0.153909E+10
June 0.754422E+11 0.999821E+10 0.122682E+11 0.00 0.00 0.00 0.00 9627842.58 0.110613E+10
July 0.776503E+11 0.102806E+11 0.126273E+11 0.00 0.00 0.00 0.00 48654559.23 0.850739E+09
August 0.779788E+11 0.103603E+11 0.126824E+11 0.00 0.00 0.00 0.00 52327067.23 0.821696E+09
September 0.752414E+11 0.100278E+11 0.122320E+11 0.00 0.00 0.00 0.00 49614356.35 0.103105E+10
October 0.776868E+11 0.103893E+11 0.126482E+11 0.00 0.00 0.00 0.00 94518363.17 0.107245E+10
November 0.751137E+11 0.100861E+11 0.122624E+11 0.00 0.00 0.00 0.00 5221172.47 0.180376E+10
December 0.776503E+11 0.103787E+11 0.126273E+11 0.00 0.00 0.00 0.00 4823787.21 0.201829E+10
                   
Annual Sum or Average 0.915726E+12 0.122034E+12 0.148998E+12 0.00 0.00 0.00 0.00 0.284317E+09 0.178229E+11
Minimum of Months 0.702046E+11 0.937997E+10 0.114244E+11 0.00 0.00 0.00 0.00 795061.10 0.821696E+09
Maximum of Months 0.780153E+11 0.104088E+11 0.126824E+11 0.00 0.00 0.00 0.00 94518363.17 0.211980E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 1162477.92 0.158137E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 197222.35 0.138140E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 194069.14 0.164760E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 1069346.00 0.114570E+09
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 93118.80 0.111720E+09
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 1371196.84 72066878.91
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 5835293.27 47630699.61
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 6843292.57 44639577.51
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 6448376.19 63855421.14
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 11320657.97 65376292.28
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 869660.60 0.132437E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 961197.02 0.151138E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 36365908.66 0.126447E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 93118.80 44639577.51
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 11320657.97 0.164760E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 1614477.14 0.153577E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 295085.69 0.135206E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 336280.38 0.162231E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 1335340.30 0.113107E+09
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 112610.73 0.111187E+09
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 1426492.06 71964025.55
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 5952043.17 47554478.65
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 7212756.49 44362405.13
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 6652794.19 62580211.70
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 11993962.26 64088534.74
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 1215914.22 0.129283E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 1614635.43 0.146959E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 39762392.08 0.124210E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 112610.73 44362405.13
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 11993962.26 0.162231E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 85091918.49 0.255708E+09 0.00 0.00 0.00 0.00 162541.96 51490938.51
February 0.00 76846309.13 0.230956E+09 0.00 0.00 0.00 0.00 20887.29 44711757.20
March 0.00 84415649.14 0.255355E+09 0.00 0.00 0.00 0.00 14509.61 51709301.55
April 0.00 82445007.08 0.247516E+09 0.00 0.00 0.00 0.00 152470.45 38171067.74
May 0.00 84753783.81 0.255532E+09 0.00 0.00 0.00 0.00 8168.14 34816875.68
June 0.00 81790910.76 0.247163E+09 0.00 0.00 0.00 0.00 147467.56 23537436.27
July 0.00 85418966.65 0.255885E+09 0.00 0.00 0.00 0.00 860004.37 19145516.58
August 0.00 84415649.14 0.255355E+09 0.00 0.00 0.00 0.00 980386.66 19140997.42
September 0.00 82467180.11 0.247516E+09 0.00 0.00 0.00 0.00 1315516.18 24878560.52
October 0.00 85080831.98 0.255708E+09 0.00 0.00 0.00 0.00 2519321.16 25554684.51
November 0.00 82117958.92 0.247340E+09 0.00 0.00 0.00 0.00 156818.98 44658091.84
December 0.00 85430053.17 0.255885E+09 0.00 0.00 0.00 0.00 137984.67 50018915.31
                   
Annual Sum or Average 0.00 0.100027E+10 0.300992E+10 0.00 0.00 0.00 0.00 6476077.03 0.427834E+09
Minimum of Months 0.00 76846309.13 0.230956E+09 0.00 0.00 0.00 0.00 8168.14 19140997.42
Maximum of Months 0.00 85430053.17 0.255885E+09 0.00 0.00 0.00 0.00 2519321.16 51709301.55



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 85115186.72 0.255778E+09 0.00 0.00 0.00 0.00 625011.50 42467750.91
February 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 120388.34 37409313.77
March 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 174119.51 45021840.26
April 0.293479E+09 82467551.52 0.247584E+09 0.00 0.00 0.00 0.00 572825.87 30744438.69
May 0.303504E+09 84776959.58 0.255602E+09 0.00 0.00 0.00 0.00 116582.67 30068135.08
June 0.293842E+09 81813276.33 0.247231E+09 0.00 0.00 0.00 0.00 693837.33 19224907.50
July 0.303141E+09 85442324.32 0.255955E+09 0.00 0.00 0.00 0.00 2292732.46 12641018.32
August 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 2858295.67 11889979.28
September 0.293479E+09 82489730.61 0.247584E+09 0.00 0.00 0.00 0.00 2139587.00 16484378.88
October 0.303322E+09 85104097.18 0.255778E+09 0.00 0.00 0.00 0.00 3907461.89 17324829.53
November 0.293661E+09 82140413.93 0.247408E+09 0.00 0.00 0.00 0.00 506826.68 35291243.14
December 0.303141E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 691275.18 40493296.45
                   
Annual Sum or Average 0.357224E+10 0.100055E+10 0.301074E+10 0.00 0.00 0.00 0.00 14698944.11 0.339061E+09
Minimum of Months 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 116582.67 11889979.28
Maximum of Months 0.303685E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 3907461.89 45021840.26



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 1092940.88 0.159066E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 188940.39 0.138642E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 173829.39 0.165653E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 943795.00 0.115647E+09
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 88921.71 0.112536E+09
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 1144643.68 72465482.32
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 5600389.72 48338317.59
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 6551309.27 45132287.33
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 6394614.93 63991087.85
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 11235400.03 65733443.74
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 846558.28 0.132919E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 933540.76 0.151778E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 35194884.02 0.127190E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 88921.71 45132287.33
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 11235400.03 0.165653E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 1669897.07 0.153468E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 273573.60 0.134970E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 250589.55 0.162883E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 1005873.25 0.114195E+09
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 89435.78 0.111988E+09
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 1145737.26 72438037.45
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 5602800.09 48335175.06
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 6587586.48 45006222.47
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 6452569.00 62725265.56
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 11530197.55 64296948.99
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 1278953.10 0.128247E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 1636539.37 0.146286E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 37523752.08 0.124484E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 89435.78 45006222.47
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 11530197.55 0.162883E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.232638E+10 0.00 0.00 0.00 0.00 0.00 1555955.11 0.204042E+09
February 0.348285E+10 0.210051E+10 0.00 0.00 0.00 0.00 0.00 215277.83 0.180338E+09
March 0.387034E+10 0.233355E+10 0.00 0.00 0.00 0.00 0.00 293673.90 0.210304E+09
April 0.373454E+10 0.224750E+10 0.00 0.00 0.00 0.00 0.00 1526628.80 0.153730E+09
May 0.386038E+10 0.233041E+10 0.00 0.00 0.00 0.00 0.00 150083.43 0.152612E+09
June 0.374269E+10 0.225781E+10 0.00 0.00 0.00 0.00 0.00 1102862.92 0.107775E+09
July 0.385223E+10 0.232011E+10 0.00 0.00 0.00 0.00 0.00 5276267.15 83156579.96
August 0.386853E+10 0.233445E+10 0.00 0.00 0.00 0.00 0.00 5754561.26 80994694.30
September 0.373273E+10 0.224840E+10 0.00 0.00 0.00 0.00 0.00 5947201.58 0.100962E+09
October 0.385404E+10 0.232548E+10 0.00 0.00 0.00 0.00 0.00 11393554.16 0.107339E+09
November 0.372639E+10 0.225602E+10 0.00 0.00 0.00 0.00 0.00 1094837.42 0.179021E+09
December 0.385223E+10 0.232011E+10 0.00 0.00 0.00 0.00 0.00 1269532.25 0.200218E+09
                   
Annual Sum or Average 0.454292E+11 0.274007E+11 0.00 0.00 0.00 0.00 0.00 35580435.82 0.176049E+10
Minimum of Months 0.348285E+10 0.210051E+10 0.00 0.00 0.00 0.00 0.00 150083.43 80994694.30
Maximum of Months 0.387034E+10 0.233445E+10 0.00 0.00 0.00 0.00 0.00 11393554.16 0.210304E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 1136360.03 0.158324E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 193598.30 0.138095E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 179467.72 0.164932E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 997626.99 0.115394E+09
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 80856.17 0.112593E+09
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 1189798.26 72956178.92
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 5535103.52 48491098.49
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 6538025.66 45342007.83
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 6344938.65 64583076.16
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 11165683.54 65788610.08
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 846235.75 0.132659E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 935353.42 0.151204E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 35143048.02 0.127036E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 80856.17 45342007.83
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 11165683.54 0.164932E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 1643644.60 0.153109E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 313062.97 0.134778E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 308576.21 0.162235E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 1200971.99 0.113904E+09
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 85552.20 0.112089E+09
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 1214751.70 72866714.90
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 5595623.44 48430801.66
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 6783646.15 45083444.64
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 6534697.18 63341132.21
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 11889245.44 64377516.62
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 1250467.44 0.128988E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 1713346.22 0.146345E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 38533585.54 0.124555E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 85552.20 45083444.64
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 11889245.44 0.162235E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 85115186.72 0.255778E+09 0.00 0.00 0.00 0.00 501234.98 82709884.91
February 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 90264.99 72112689.38
March 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 80248.13 85665613.46
April 0.293479E+09 82467551.52 0.247584E+09 0.00 0.00 0.00 0.00 473556.20 59291254.24
May 0.303504E+09 84776959.58 0.255602E+09 0.00 0.00 0.00 0.00 41929.96 57167058.42
June 0.293842E+09 81813276.33 0.247231E+09 0.00 0.00 0.00 0.00 656090.35 36699450.80
July 0.303141E+09 85442324.32 0.255955E+09 0.00 0.00 0.00 0.00 2893973.98 24432791.42
August 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 3327001.19 23002450.37
September 0.293479E+09 82489730.61 0.247584E+09 0.00 0.00 0.00 0.00 3225075.85 33068685.42
October 0.303322E+09 85104097.18 0.255778E+09 0.00 0.00 0.00 0.00 5605478.76 34103621.04
November 0.293661E+09 82140413.93 0.247408E+09 0.00 0.00 0.00 0.00 402330.85 69227969.11
December 0.303141E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 444002.36 79037969.89
                   
Annual Sum or Average 0.357224E+10 0.100055E+10 0.301074E+10 0.00 0.00 0.00 0.00 17741187.59 0.656519E+09
Minimum of Months 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 41929.96 23002450.37
Maximum of Months 0.303685E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 5605478.76 85665613.46



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.302110E+10 0.149358E+11 0.00 0.00 0.00 0.00 1298947.97 0.485547E+09
February 0.415303E+11 0.270209E+10 0.134904E+11 0.00 0.00 0.00 0.00 199829.51 0.432812E+09
March 0.461508E+11 0.298356E+10 0.149358E+11 0.00 0.00 0.00 0.00 53575.80 0.509889E+09
April 0.445315E+11 0.283147E+10 0.144540E+11 0.00 0.00 0.00 0.00 897987.03 0.379777E+09
May 0.460320E+11 0.289692E+10 0.149358E+11 0.00 0.00 0.00 0.00 24700.82 0.380334E+09
June 0.446286E+11 0.279538E+10 0.144540E+11 0.00 0.00 0.00 0.00 258385.76 0.275627E+09
July 0.459349E+11 0.287854E+10 0.149358E+11 0.00 0.00 0.00 0.00 4932742.29 0.210617E+09
August 0.461292E+11 0.292152E+10 0.149358E+11 0.00 0.00 0.00 0.00 5808709.05 0.200422E+09
September 0.445099E+11 0.286757E+10 0.144540E+11 0.00 0.00 0.00 0.00 10018271.05 0.249118E+09
October 0.459565E+11 0.300238E+10 0.149358E+11 0.00 0.00 0.00 0.00 20068971.26 0.254484E+09
November 0.444343E+11 0.291991E+10 0.144540E+11 0.00 0.00 0.00 0.00 1146875.84 0.420822E+09
December 0.459349E+11 0.301516E+10 0.149358E+11 0.00 0.00 0.00 0.00 1188232.80 0.468890E+09
                   
Annual Sum or Average 0.541708E+12 0.348356E+11 0.175857E+12 0.00 0.00 0.00 0.00 45897229.17 0.426834E+10
Minimum of Months 0.415303E+11 0.270209E+10 0.134904E+11 0.00 0.00 0.00 0.00 24700.82 0.200422E+09
Maximum of Months 0.461508E+11 0.302110E+10 0.149358E+11 0.00 0.00 0.00 0.00 20068971.26 0.509889E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.302110E+10 0.149358E+11 0.00 0.00 0.00 0.00 999025.62 0.491435E+09
February 0.415303E+11 0.270209E+10 0.134904E+11 0.00 0.00 0.00 0.00 154746.51 0.438052E+09
March 0.461508E+11 0.298356E+10 0.149358E+11 0.00 0.00 0.00 0.00 9437.16 0.516029E+09
April 0.445315E+11 0.283147E+10 0.144540E+11 0.00 0.00 0.00 0.00 762461.66 0.383487E+09
May 0.460320E+11 0.289692E+10 0.149358E+11 0.00 0.00 0.00 0.00 4770.49 0.383834E+09
June 0.446286E+11 0.279538E+10 0.144540E+11 0.00 0.00 0.00 0.00 131102.57 0.277906E+09
July 0.459349E+11 0.287854E+10 0.149358E+11 0.00 0.00 0.00 0.00 4476567.54 0.211898E+09
August 0.461292E+11 0.292152E+10 0.149358E+11 0.00 0.00 0.00 0.00 5207387.17 0.201695E+09
September 0.445099E+11 0.286757E+10 0.144540E+11 0.00 0.00 0.00 0.00 9878675.08 0.251394E+09
October 0.459565E+11 0.300238E+10 0.149358E+11 0.00 0.00 0.00 0.00 19469234.16 0.256597E+09
November 0.444343E+11 0.291991E+10 0.144540E+11 0.00 0.00 0.00 0.00 984471.93 0.425534E+09
December 0.459349E+11 0.301516E+10 0.149358E+11 0.00 0.00 0.00 0.00 894343.99 0.474209E+09
                   
Annual Sum or Average 0.541708E+12 0.348356E+11 0.175857E+12 0.00 0.00 0.00 0.00 42972223.88 0.431207E+10
Minimum of Months 0.415303E+11 0.270209E+10 0.134904E+11 0.00 0.00 0.00 0.00 4770.49 0.201695E+09
Maximum of Months 0.461508E+11 0.302110E+10 0.149358E+11 0.00 0.00 0.00 0.00 19469234.16 0.516029E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.113146E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 603124.74 0.437887E+09
February 0.369574E+10 0.102161E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 79948.47 0.390787E+09
March 0.410691E+10 0.113495E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.459292E+09
April 0.396281E+10 0.109310E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 607454.29 0.340070E+09
May 0.409635E+10 0.113342E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.339976E+09
June 0.397146E+10 0.109811E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 43381.92 0.245898E+09
July 0.408770E+10 0.112841E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 3742074.60 0.186933E+09
August 0.410499E+10 0.113539E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 4236813.68 0.178187E+09
September 0.396089E+10 0.109354E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 8799105.38 0.223111E+09
October 0.408962E+10 0.113103E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 16669089.19 0.227041E+09
November 0.395417E+10 0.109724E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 745058.27 0.378857E+09
December 0.408770E+10 0.112841E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 451028.56 0.422640E+09
                   
Annual Sum or Average 0.482060E+11 0.133267E+11 0.392709E+12 0.359593E+12 0.00 0.00 0.00 35977079.09 0.383068E+10
Minimum of Months 0.369574E+10 0.102161E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.178187E+09
Maximum of Months 0.410691E+10 0.113539E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 16669089.19 0.459292E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.246211E+10 0.00 0.00 0.00 0.00 0.00 2276558.52 0.353062E+09
February 0.368610E+10 0.222306E+10 0.00 0.00 0.00 0.00 0.00 331289.27 0.310142E+09
March 0.409620E+10 0.246970E+10 0.00 0.00 0.00 0.00 0.00 300640.50 0.367546E+09
April 0.395248E+10 0.237864E+10 0.00 0.00 0.00 0.00 0.00 1647484.62 0.271781E+09
May 0.408566E+10 0.246638E+10 0.00 0.00 0.00 0.00 0.00 71376.61 0.269046E+09
June 0.396110E+10 0.238954E+10 0.00 0.00 0.00 0.00 0.00 717539.49 0.193592E+09
July 0.407704E+10 0.245547E+10 0.00 0.00 0.00 0.00 0.00 6386239.82 0.150602E+09
August 0.409429E+10 0.247065E+10 0.00 0.00 0.00 0.00 0.00 6854626.71 0.145318E+09
September 0.395056E+10 0.237958E+10 0.00 0.00 0.00 0.00 0.00 9694008.62 0.178095E+09
October 0.407896E+10 0.246116E+10 0.00 0.00 0.00 0.00 0.00 18513639.92 0.183888E+09
November 0.394385E+10 0.238765E+10 0.00 0.00 0.00 0.00 0.00 1584828.95 0.305479E+09
December 0.407704E+10 0.245547E+10 0.00 0.00 0.00 0.00 0.00 1800943.64 0.340892E+09
                   
Annual Sum or Average 0.480803E+11 0.289994E+11 0.00 0.00 0.00 0.00 0.00 50179176.67 0.306944E+10
Minimum of Months 0.368610E+10 0.222306E+10 0.00 0.00 0.00 0.00 0.00 71376.61 0.145318E+09
Maximum of Months 0.409620E+10 0.247065E+10 0.00 0.00 0.00 0.00 0.00 18513639.92 0.367546E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 14185.34 02-JAN-20:10 10113.80 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 14185.34 01-FEB-20:10 10113.80 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 14185.34 01-MAR-20:10 10113.80 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 14185.34 03-APR-19:10 10113.80 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 14185.34 01-MAY-19:10 10113.80 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 14185.34 01-JUN-19:10 10113.80 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 14185.34 03-JUL-19:10 10113.80 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 14185.34 01-AUG-19:10 10113.80 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 14185.34 01-SEP-19:10 10113.80 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 14185.34 02-OCT-19:10 10113.80 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 14185.34 01-NOV-19:10 10113.80 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 14185.34 01-DEC-20:10 10113.80 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   14185.34   10113.80   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   14185.34   10113.80   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 704.41 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 30.67 17-JAN-11:55 250.88 08-JAN-07:00
February 1169.53 01-FEB-00:10 704.41 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 22.85 01-FEB-11:55 196.97 04-FEB-05:55
March 1169.53 01-MAR-00:10 704.41 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 210.81 08-MAR-02:00
April 1169.53 01-APR-00:10 704.41 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 41.96 30-APR-10:55 170.87 01-APR-06:00
May 1169.53 01-MAY-00:10 704.41 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 12.24 03-MAY-12:00 158.99 15-MAY-05:00
June 1169.53 01-JUN-00:10 704.41 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 34.61 29-JUN-10:55 121.18 13-JUN-04:00
July 1169.53 01-JUL-00:10 704.41 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 64.31 19-JUL-10:55 101.71 06-JUL-01:00
August 1169.53 01-AUG-00:10 704.41 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 58.60 14-AUG-10:55 92.40 28-AUG-03:00
September 1169.53 01-SEP-00:10 704.41 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 132.69 29-SEP-10:55 122.75 20-SEP-03:00
October 1169.53 01-OCT-23:10 704.41 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 143.56 16-OCT-10:55 149.72 30-OCT-03:00
November 1169.53 01-NOV-00:10 704.41 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 34.19 19-NOV-13:00 187.90 29-NOV-23:00
December 1169.53 01-DEC-00:10 704.41 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 23.02 16-DEC-13:00 197.46 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   704.41   685.60   0.00 0.00 0.00 0.00 0.00   92.40  
Maximum of Months 1169.53   704.41   685.60   0.00 0.00 0.00 0.00 143.56   250.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 815.72 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 15.83 18-JAN-13:00 97.88 08-JAN-07:00
February 1354.32 01-FEB-00:10 815.72 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 16.00 01-FEB-11:55 84.60 04-FEB-05:55
March 1354.32 01-MAR-00:10 815.72 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 7.25 11-MAR-11:50 86.71 08-MAR-02:00
April 1354.32 01-APR-00:10 815.72 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 19.77 26-APR-13:00 70.68 01-APR-06:00
May 1354.32 01-MAY-00:10 815.72 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 6.99 03-MAY-12:00 70.16 19-MAY-05:00
June 1354.32 01-JUN-00:10 815.72 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 11.62 29-JUN-10:55 55.44 13-JUN-04:40
July 1354.32 01-JUL-00:10 815.72 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 24.46 19-JUL-10:55 48.28 06-JUL-01:00
August 1354.32 01-AUG-00:10 815.72 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 24.31 14-AUG-10:55 43.26 28-AUG-06:00
September 1354.32 01-SEP-00:10 815.72 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 56.39 29-SEP-10:55 56.43 20-SEP-03:00
October 1354.32 01-OCT-23:10 815.72 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 59.04 16-OCT-10:55 66.36 27-OCT-04:30
November 1354.32 01-NOV-00:10 815.72 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 17.10 19-NOV-13:00 80.29 29-NOV-23:00
December 1354.32 01-DEC-00:10 815.72 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 15.14 16-DEC-13:00 84.14 03-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   815.72   793.93   0.00 0.00 0.00 0.00 6.99   43.26  
Maximum of Months 1354.32   815.72   793.93   0.00 0.00 0.00 0.00 59.04   97.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 1360.40 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 46.90 13-JAN-14:00 228.85 08-JAN-07:00
February 286.42 01-FEB-00:10 1360.40 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 43.15 01-FEB-11:55 189.75 04-FEB-05:55
March 286.42 01-MAR-00:10 1360.40 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 25.36 11-MAR-11:55 193.51 08-MAR-02:00
April 286.42 01-APR-00:10 1360.40 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 50.16 26-APR-13:00 157.03 01-APR-06:00
May 286.42 01-MAY-00:10 1360.40 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 17.70 03-MAY-12:00 157.92 27-MAY-03:00
June 286.42 01-JUN-00:10 1360.40 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 25.20 29-JUN-10:55 124.84 13-JUN-04:40
July 286.42 01-JUL-00:10 1360.40 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 54.71 19-JUL-10:55 108.21 06-JUL-01:00
August 286.42 01-AUG-00:10 1360.40 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 56.13 14-AUG-10:55 96.22 28-AUG-07:00
September 286.42 01-SEP-00:10 1360.40 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 135.20 29-SEP-10:55 124.24 20-SEP-03:00
October 286.42 01-OCT-23:10 1360.40 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 140.61 16-OCT-10:55 148.96 12-OCT-06:00
November 286.42 01-NOV-00:10 1360.40 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 48.88 19-NOV-13:00 177.53 29-NOV-23:00
December 286.42 01-DEC-00:10 1360.40 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 46.46 16-DEC-13:00 190.27 03-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   1360.40   839.45   0.00 0.00 0.00 0.00 17.70   96.22  
Maximum of Months 286.42   1360.40   839.45   0.00 0.00 0.00 0.00 140.61   228.85  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 227.72 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 26.85 13-JAN-14:00 132.03 08-JAN-07:00
February 220.32 01-FEB-00:10 227.72 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 24.79 01-FEB-11:55 109.26 04-FEB-05:55
March 220.32 01-MAR-00:10 227.72 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 14.36 11-MAR-11:50 110.95 08-MAR-02:00
April 220.32 01-APR-00:10 227.72 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 29.08 26-APR-13:00 89.93 01-APR-06:00
May 220.32 01-MAY-00:10 227.72 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 10.48 03-MAY-12:00 90.38 27-MAY-03:00
June 220.32 01-JUN-00:10 227.72 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 14.94 29-JUN-10:55 71.37 13-JUN-05:00
July 220.32 01-JUL-00:10 227.72 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 31.82 19-JUL-10:55 61.42 06-JUL-01:00
August 220.32 01-AUG-00:10 227.72 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 32.47 14-AUG-10:55 53.97 24-AUG-02:00
September 220.32 01-SEP-00:10 227.72 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 77.63 29-SEP-10:55 71.26 20-SEP-03:00
October 220.32 01-OCT-23:10 227.72 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 80.77 16-OCT-10:55 84.72 27-OCT-04:20
November 220.32 01-NOV-00:10 227.72 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 28.00 19-NOV-13:00 99.66 29-NOV-23:00
December 220.32 01-DEC-00:10 227.72 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 26.43 16-DEC-13:00 108.40 03-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   227.72   242.16   0.00 0.00 0.00 0.00 10.48   53.97  
Maximum of Months 220.32   227.72   242.16   0.00 0.00 0.00 0.00 80.77   132.03  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 357.21 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 67.14 14-JAN-11:50 312.43 08-JAN-07:00
February 907.20 01-FEB-00:10 357.21 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 60.30 01-FEB-11:55 264.99 09-FEB-06:50
March 907.20 01-MAR-00:10 357.21 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 39.31 11-MAR-11:50 280.01 30-MAR-06:10
April 907.20 01-APR-00:10 357.21 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 65.63 26-APR-13:00 238.89 01-APR-06:00
May 907.20 01-MAY-00:10 357.21 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 27.81 04-MAY-12:00 228.79 15-MAY-05:10
June 907.20 01-JUN-00:10 357.21 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 52.86 29-JUN-10:50 185.75 13-JUN-05:10
July 907.20 01-JUL-00:10 357.21 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 94.47 19-JUL-10:50 144.39 08-JUL-24:00
August 907.20 01-AUG-00:10 357.21 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 94.75 14-AUG-10:50 147.79 28-AUG-07:00
September 907.20 01-SEP-00:10 357.21 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 202.93 29-SEP-10:50 179.13 20-SEP-06:00
October 907.20 01-OCT-23:10 357.21 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 214.36 16-OCT-10:50 226.82 12-OCT-06:00
November 907.20 01-NOV-00:10 357.21 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 65.51 19-NOV-13:10 259.59 23-NOV-22:00
December 907.20 01-DEC-00:10 357.21 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 57.17 16-DEC-13:00 281.93 22-DEC-07:10
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   357.21   4572.80   39726.58   0.00 0.00 0.00 27.81   144.39  
Maximum of Months 907.20   357.21   4572.80   39726.58   0.00 0.00 0.00 214.36   312.43  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 1761.91 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 60.44 17-JAN-11:55 554.53 08-JAN-07:00
February 15368.40 01-FEB-00:10 1761.91 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 50.53 01-FEB-11:55 493.56 04-FEB-05:55
March 15368.40 01-MAR-00:10 1761.91 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 499.17 08-MAR-02:00
April 15368.40 01-APR-00:10 1761.91 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 94.43 26-APR-13:00 405.24 01-APR-06:00
May 15368.40 01-MAY-00:10 1761.91 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 29.08 03-MAY-12:00 405.47 19-MAY-05:00
June 15368.40 01-JUN-00:10 1761.91 01-JUN-19:10 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 78.76 29-JUN-10:50 326.48 13-JUN-05:00
July 15368.40 01-JUL-00:10 1761.91 03-JUL-19:10 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 146.35 19-JUL-10:55 278.67 06-JUL-01:00
August 15368.40 01-AUG-00:10 1761.91 01-AUG-19:10 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 135.16 14-AUG-10:55 257.14 28-AUG-03:00
September 15368.40 01-SEP-00:10 1761.91 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 293.34 29-SEP-10:55 331.96 20-SEP-03:00
October 15368.40 01-OCT-23:10 1761.91 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 317.36 16-OCT-10:55 392.59 30-OCT-03:00
November 15368.40 01-NOV-00:10 1761.91 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 75.61 19-NOV-13:00 459.89 29-NOV-23:00
December 15368.40 01-DEC-00:10 1761.91 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 50.92 16-DEC-13:00 488.01 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   1761.91   965.27   0.00 0.00 0.00 0.00 0.00   257.14  
Maximum of Months 15368.40   1761.91   965.27   0.00 0.00 0.00 0.00 317.36   554.53  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 10265.18 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 200.12 13-JAN-14:00 1639.97 08-JAN-07:00
February 45622.98 01-FEB-00:10 10265.18 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 214.89 01-FEB-11:55 1448.78 04-FEB-05:55
March 45622.98 01-MAR-00:10 10265.18 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 69.84 11-MAR-11:50 1475.99 08-MAR-02:00
April 45622.98 01-APR-00:10 10265.18 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 306.52 26-APR-13:00 1219.14 01-APR-06:00
May 45622.98 01-MAY-00:10 10265.18 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 97.40 03-MAY-12:00 1205.11 19-MAY-05:00
June 45622.98 01-JUN-00:10 10265.18 01-JUN-19:10 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 186.99 29-JUN-10:55 974.61 13-JUN-05:00
July 45622.98 01-JUL-00:10 10265.18 03-JUL-19:10 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 396.25 19-JUL-10:55 830.05 06-JUL-01:00
August 45622.98 01-AUG-00:10 10265.18 01-AUG-19:10 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 389.59 14-AUG-10:55 750.60 24-AUG-02:00
September 45622.98 01-SEP-00:10 10265.18 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 898.72 29-SEP-10:55 975.31 20-SEP-03:00
October 45622.98 01-OCT-23:10 10265.18 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 936.63 16-OCT-10:55 1145.20 27-OCT-04:40
November 45622.98 01-NOV-00:10 10265.18 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 222.95 19-NOV-13:00 1316.10 23-NOV-22:00
December 45622.98 01-DEC-00:10 10265.18 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 180.48 16-DEC-13:00 1430.91 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   10265.18   10029.21   0.00 0.00 0.00 0.00 69.84   750.60  
Maximum of Months 45622.98   10265.18   10029.21   0.00 0.00 0.00 0.00 936.63   1639.97  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 32.34 14-JAN-11:00 146.71 08-JAN-07:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 19.03 01-FEB-10:00 115.41 04-FEB-06:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 19.03 11-MAR-11:00 123.45 08-MAR-04:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 25.70 30-APR-10:00 100.25 01-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 12.41 03-MAY-10:00 93.35 15-MAY-05:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 19.03 30-JUN-10:00 71.39 13-JUN-04:10
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 38.70 19-JUL-10:00 56.57 06-JUL-01:00
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 38.71 15-AUG-10:00 51.47 28-AUG-07:10
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 89.14 29-SEP-10:00 70.90 20-SEP-03:10
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 89.32 16-OCT-10:00 85.84 30-OCT-04:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 32.26 19-NOV-10:00 100.72 24-NOV-01:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 32.32 05-DEC-10:00 115.70 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 12.41   51.47  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 89.32   146.71  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 32.34 14-JAN-11:00 146.70 08-JAN-07:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 27.16 01-FEB-11:55 115.40 04-FEB-06:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 19.03 11-MAR-11:00 123.44 08-MAR-02:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 25.79 30-APR-10:02 100.25 01-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 12.41 03-MAY-10:00 93.35 15-MAY-05:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 19.03 30-JUN-10:00 71.39 13-JUN-04:10
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 38.70 19-JUL-10:00 56.57 06-JUL-01:00
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 38.70 15-AUG-10:00 50.99 28-AUG-07:10
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 89.14 29-SEP-10:00 70.89 20-SEP-03:10
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 89.84 16-OCT-10:01 85.83 30-OCT-04:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 32.26 19-NOV-10:00 100.71 24-NOV-01:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 32.31 05-DEC-10:00 115.69 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 12.41   50.99  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 89.84   146.70  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 76.99 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 4.88 14-JAN-11:00 41.00 08-JAN-07:00
February 0.00 01-FEB-00:10 76.99 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 4.86 01-FEB-11:55 34.29 04-FEB-05:55
March 0.00 01-MAR-00:10 76.99 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 1.16 11-MAR-11:05 35.11 08-MAR-02:00
April 0.00 01-APR-00:10 76.99 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 6.69 26-APR-13:00 27.40 15-APR-22:00
May 0.00 01-MAY-00:10 76.99 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 1.16 03-MAY-12:50 26.24 27-MAY-03:00
June 0.00 01-JUN-00:10 76.99 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 3.29 29-JUN-10:55 20.66 12-JUN-21:00
July 0.00 01-JUL-00:10 76.99 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 8.51 19-JUL-12:00 18.32 06-JUL-01:00
August 0.00 01-AUG-00:10 76.99 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 8.53 18-AUG-12:00 18.02 28-AUG-06:30
September 0.00 01-SEP-00:10 76.99 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 22.61 29-SEP-10:55 22.71 20-SEP-03:00
October 0.00 01-OCT-00:10 76.99 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 24.37 16-OCT-11:00 27.42 30-OCT-03:00
November 0.00 01-NOV-00:10 76.99 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 6.69 19-NOV-13:00 32.51 23-NOV-22:00
December 0.00 01-DEC-00:10 76.99 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 4.89 16-DEC-13:00 35.18 03-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   76.99   232.19   0.00 0.00 0.00 0.00 1.16   18.02  
Maximum of Months 0.00   76.99   232.19   0.00 0.00 0.00 0.00 24.37   41.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 77.01 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 9.18 13-JAN-14:00 40.95 08-JAN-07:00
February 180.00 01-FEB-00:10 77.01 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 8.52 01-FEB-11:55 32.21 04-FEB-06:00
March 180.00 01-MAR-00:10 77.01 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 5.31 11-MAR-11:00 34.45 08-MAR-04:00
April 180.00 01-APR-00:10 77.01 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 9.18 26-APR-13:00 27.98 01-APR-06:00
May 180.00 01-MAY-00:10 77.01 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 3.87 03-MAY-12:00 26.05 15-MAY-05:00
June 180.00 01-JUN-00:10 77.01 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 5.70 29-JUN-10:55 19.93 13-JUN-04:10
July 180.00 01-JUL-00:10 77.01 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 10.87 19-JUL-10:02 15.79 06-JUL-01:00
August 180.00 01-AUG-00:10 77.01 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 10.85 14-AUG-10:55 14.06 28-AUG-07:10
September 180.00 01-SEP-00:10 77.01 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 25.00 29-SEP-10:02 19.79 20-SEP-03:10
October 180.00 01-OCT-00:10 77.01 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 26.32 16-OCT-10:55 23.96 30-OCT-04:00
November 180.00 01-NOV-00:10 77.01 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 9.62 19-NOV-13:00 28.11 24-NOV-01:00
December 180.00 01-DEC-00:10 77.01 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 9.02 05-DEC-10:00 32.29 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 3.87   14.06  
Maximum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 26.32   40.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 32.34 14-JAN-11:00 146.71 08-JAN-07:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 19.03 01-FEB-10:00 115.41 04-FEB-06:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 19.03 11-MAR-11:00 123.45 08-MAR-04:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 25.70 30-APR-10:00 100.25 01-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 12.41 03-MAY-10:00 93.35 15-MAY-05:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 19.03 30-JUN-10:00 71.39 13-JUN-04:10
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 38.70 19-JUL-10:00 56.57 06-JUL-01:00
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 38.71 15-AUG-10:00 57.72 28-AUG-07:20
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 89.14 29-SEP-10:00 70.90 20-SEP-03:10
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 89.32 16-OCT-10:00 85.84 30-OCT-04:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 32.25 19-NOV-10:10 100.72 24-NOV-01:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 32.32 05-DEC-10:00 115.70 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 12.41   56.57  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 89.32   146.71  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 32.34 14-JAN-11:00 146.70 08-JAN-07:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 24.32 01-FEB-11:55 115.40 04-FEB-06:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 19.03 11-MAR-11:00 123.44 08-MAR-04:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 25.70 30-APR-10:00 100.24 01-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 12.40 03-MAY-10:00 93.35 15-MAY-05:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 19.03 30-JUN-10:00 71.39 13-JUN-04:10
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 38.69 19-JUL-10:00 56.57 06-JUL-01:00
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 38.70 15-AUG-10:00 57.05 28-AUG-07:20
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 89.14 29-SEP-10:00 70.89 20-SEP-03:10
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 89.31 16-OCT-10:00 85.84 30-OCT-04:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 32.26 19-NOV-10:00 100.71 24-NOV-01:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 32.31 05-DEC-10:00 115.69 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 12.40   56.57  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 89.31   146.70  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 2240.78 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 30.22 13-JAN-14:00 177.36 08-JAN-07:00
February 2263.36 01-FEB-00:10 2240.78 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 29.45 01-FEB-11:55 149.77 04-FEB-05:55
March 2263.36 01-MAR-00:10 2240.78 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 14.67 11-MAR-11:50 152.40 08-MAR-02:00
April 2263.36 01-APR-00:10 2240.78 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 36.41 26-APR-13:00 121.49 01-APR-06:00
May 2263.36 01-MAY-00:10 2240.78 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 11.56 03-MAY-12:00 122.25 27-MAY-03:00
June 2263.36 01-JUN-00:10 2240.78 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 19.27 29-JUN-10:55 96.12 13-JUN-05:00
July 2263.36 01-JUL-00:10 2240.78 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 41.92 19-JUL-10:55 83.31 06-JUL-01:00
August 2263.36 01-AUG-00:10 2240.78 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 41.41 14-AUG-10:55 75.08 24-AUG-02:00
September 2263.36 01-SEP-00:10 2240.78 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 100.68 29-SEP-10:55 98.06 20-SEP-03:00
October 2263.36 01-OCT-23:10 2240.78 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 104.81 16-OCT-10:55 116.72 30-OCT-03:05
November 2263.36 01-NOV-00:10 2240.78 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 32.91 19-NOV-13:00 136.42 29-NOV-23:00
December 2263.36 01-DEC-00:10 2240.78 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 30.08 16-DEC-13:00 148.90 03-DEC-01:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   2240.78   0.00 0.00 0.00 0.00 0.00 11.56   75.08  
Maximum of Months 2263.36   2240.78   0.00 0.00 0.00 0.00 0.00 104.81   177.36  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 31.95 14-JAN-11:00 147.18 08-JAN-07:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 18.63 01-FEB-10:00 115.86 04-FEB-06:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 18.64 11-MAR-11:00 123.90 08-MAR-02:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 25.31 30-APR-10:00 100.69 01-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 12.01 03-MAY-10:00 93.79 15-MAY-05:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 18.64 30-JUN-10:00 71.83 13-JUN-04:10
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 38.31 19-JUL-10:00 56.99 06-JUL-01:00
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 38.32 15-AUG-10:00 50.35 28-AUG-07:10
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 88.78 29-SEP-10:00 71.33 20-SEP-03:10
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 88.95 16-OCT-10:00 86.28 30-OCT-04:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 31.87 19-NOV-10:00 101.16 24-NOV-01:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 31.93 05-DEC-10:00 116.15 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 12.01   50.35  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 88.95   147.18  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 31.95 14-JAN-11:00 147.16 08-JAN-07:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 27.70 01-FEB-11:55 115.85 04-FEB-06:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 18.64 11-MAR-11:00 123.89 08-MAR-04:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 25.33 30-APR-10:02 100.69 01-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 12.01 03-MAY-10:00 93.79 15-MAY-05:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 18.64 30-JUN-10:00 71.82 13-JUN-04:10
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 38.31 19-JUL-10:00 56.99 06-JUL-01:00
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 38.32 15-AUG-10:00 49.85 28-AUG-07:10
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 88.77 29-SEP-10:00 71.32 20-SEP-03:10
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 89.43 16-OCT-10:01 86.27 30-OCT-04:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 31.87 19-NOV-10:00 101.15 24-NOV-01:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 31.93 05-DEC-10:00 116.14 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 12.01   49.85  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 89.43   147.16  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 77.01 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 16.34 14-JAN-11:00 75.30 08-JAN-07:00
February 180.00 01-FEB-00:10 77.01 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 9.53 01-FEB-10:00 59.28 04-FEB-06:00
March 180.00 01-MAR-00:10 77.01 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 9.53 11-MAR-11:00 63.39 08-MAR-02:00
April 180.00 01-APR-00:10 77.01 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 12.95 30-APR-10:00 51.52 01-APR-06:00
May 180.00 01-MAY-00:10 77.01 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 6.15 03-MAY-10:00 47.99 15-MAY-05:00
June 180.00 01-JUN-00:10 77.01 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 9.54 30-JUN-10:00 36.75 13-JUN-04:10
July 180.00 01-JUL-00:10 77.01 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 19.60 19-JUL-10:00 29.16 06-JUL-01:00
August 180.00 01-AUG-00:10 77.01 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 19.61 15-AUG-10:00 26.14 28-AUG-07:10
September 180.00 01-SEP-00:10 77.01 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 45.42 29-SEP-10:00 36.49 20-SEP-03:10
October 180.00 01-OCT-00:10 77.01 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 45.51 16-OCT-10:00 44.14 30-OCT-04:00
November 180.00 01-NOV-00:10 77.01 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 16.30 19-NOV-10:00 51.76 24-NOV-01:00
December 180.00 01-DEC-00:10 77.01 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 16.33 05-DEC-10:00 59.42 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 6.15   26.14  
Maximum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 45.51   75.30  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3094.06 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 45.62 13-JAN-14:00 379.97 08-JAN-07:00
February 26988.77 01-FEB-00:10 3094.06 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 48.92 01-FEB-11:55 333.25 04-FEB-06:00
March 26988.77 01-MAR-00:10 3094.06 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 10.49 11-MAR-11:40 346.61 08-MAR-02:00
April 26988.77 01-APR-00:10 3094.06 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 52.92 26-APR-13:00 295.77 01-APR-06:00
May 26988.77 01-MAY-00:10 3094.06 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 6.46 03-MAY-12:00 278.99 15-MAY-05:00
June 26988.77 01-JUN-00:10 3094.06 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 26.05 29-JUN-10:50 224.92 13-JUN-04:10
July 26988.77 01-JUL-00:10 3094.06 03-JUL-19:10 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 74.20 19-JUL-10:55 188.00 06-JUL-01:00
August 26988.77 01-AUG-00:10 3094.06 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 75.26 14-AUG-10:55 170.32 31-AUG-04:00
September 26988.77 01-SEP-00:10 3094.06 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 196.98 29-SEP-10:55 223.35 20-SEP-03:10
October 26988.77 01-OCT-23:10 3094.06 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 211.27 16-OCT-10:55 260.40 30-OCT-04:00
November 26988.77 01-NOV-00:10 3094.06 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 51.23 19-NOV-13:00 297.12 24-NOV-01:00
December 26988.77 01-DEC-00:10 3094.06 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 42.83 19-DEC-13:00 332.93 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 6.46   170.32  
Maximum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 211.27   379.97  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3094.06 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 40.53 13-JAN-14:00 382.75 08-JAN-07:00
February 26988.77 01-FEB-00:10 3094.06 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 44.23 01-FEB-11:55 333.25 04-FEB-06:00
March 26988.77 01-MAR-00:10 3094.06 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 6.26 11-MAR-11:40 349.67 08-MAR-02:00
April 26988.77 01-APR-00:10 3094.06 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 48.88 26-APR-13:00 295.77 01-APR-06:00
May 26988.77 01-MAY-00:10 3094.06 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 2.67 03-MAY-12:00 279.00 15-MAY-05:00
June 26988.77 01-JUN-00:10 3094.06 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 22.76 29-JUN-10:50 224.92 13-JUN-04:10
July 26988.77 01-JUL-00:10 3094.06 03-JUL-19:10 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 70.89 19-JUL-10:55 188.00 06-JUL-01:00
August 26988.77 01-AUG-00:10 3094.06 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 72.06 14-AUG-10:55 170.32 31-AUG-04:00
September 26988.77 01-SEP-00:10 3094.06 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 193.99 29-SEP-10:55 223.35 20-SEP-03:10
October 26988.77 01-OCT-23:10 3094.06 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 209.03 16-OCT-10:55 260.41 30-OCT-04:00
November 26988.77 01-NOV-00:10 3094.06 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 47.89 19-NOV-13:00 297.13 24-NOV-01:00
December 26988.77 01-DEC-00:10 3094.06 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 39.02 19-DEC-13:00 333.95 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 2.67   170.32  
Maximum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 209.03   382.75  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1089.83 02-JAN-20:10 14912.86 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 27.84 14-JAN-11:00 340.21 08-JAN-07:00
February 2401.70 01-FEB-00:10 1089.83 01-FEB-20:10 14912.86 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 27.67 01-FEB-11:55 288.16 05-FEB-06:10
March 2401.70 01-MAR-00:10 1089.83 01-MAR-20:10 14912.86 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 0.00 01-MAR-00:03 295.37 30-MAR-05:30
April 2401.70 01-APR-00:10 1089.83 03-APR-19:10 14912.86 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 42.05 26-APR-13:00 264.70 01-APR-06:00
May 2401.70 01-MAY-00:10 1089.83 01-MAY-19:10 14912.86 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 0.00 01-MAY-00:05 248.80 19-MAY-05:00
June 2401.70 01-JUN-00:10 1089.83 01-JUN-19:10 14912.86 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 13.16 29-JUN-10:55 201.36 13-JUN-04:10
July 2401.70 01-JUL-00:10 1089.83 03-JUL-19:10 14912.86 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 56.41 19-JUL-12:00 158.71 06-JUL-01:00
August 2401.70 01-AUG-00:10 1089.83 01-AUG-19:10 14912.86 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 56.52 18-AUG-12:00 152.01 28-AUG-06:10
September 2401.70 01-SEP-00:10 1089.83 01-SEP-19:10 14912.86 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 167.09 29-SEP-11:10 189.66 20-SEP-03:30
October 2401.70 01-OCT-23:10 1089.83 02-OCT-19:10 14912.86 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 180.84 16-OCT-11:00 232.84 12-OCT-06:00
November 2401.70 01-NOV-00:10 1089.83 01-NOV-19:10 14912.86 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 42.11 19-NOV-13:00 265.90 23-NOV-22:00
December 2401.70 01-DEC-00:10 1089.83 01-DEC-20:10 14912.86 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 27.93 16-DEC-13:00 298.99 22-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1089.83   14912.86   22492.83   0.00 0.00 0.00 0.00   152.01  
Maximum of Months 2401.70   1089.83   14912.86   22492.83   0.00 0.00 0.00 180.84   340.21  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 2371.52 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 49.68 14-JAN-11:00 313.18 08-JAN-07:00
February 2395.44 01-FEB-00:10 2371.52 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 48.47 01-FEB-11:55 253.81 04-FEB-05:55
March 2395.44 01-MAR-00:10 2371.52 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 19.23 11-MAR-11:00 263.41 08-MAR-04:00
April 2395.44 01-APR-00:10 2371.52 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 53.77 26-APR-13:00 213.78 01-APR-06:00
May 2395.44 01-MAY-00:10 2371.52 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 11.28 03-MAY-12:00 209.15 27-MAY-03:00
June 2395.44 01-JUN-00:10 2371.52 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 26.89 29-JUN-10:55 164.38 13-JUN-04:05
July 2395.44 01-JUL-00:10 2371.52 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 67.41 19-JUL-10:55 143.96 06-JUL-01:00
August 2395.44 01-AUG-00:10 2371.52 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 66.77 14-AUG-10:55 129.16 28-AUG-03:00
September 2395.44 01-SEP-00:10 2371.52 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 169.29 29-SEP-10:55 165.55 20-SEP-03:00
October 2395.44 01-OCT-23:10 2371.52 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 177.48 16-OCT-10:55 197.47 27-OCT-04:05
November 2395.44 01-NOV-00:10 2371.52 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 50.66 19-NOV-13:00 235.11 29-NOV-23:00
December 2395.44 01-DEC-00:10 2371.52 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 47.57 16-DEC-13:00 252.95 03-DEC-01:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   2371.52   0.00 0.00 0.00 0.00 0.00 11.28   129.16  
Maximum of Months 2395.44   2371.52   0.00 0.00 0.00 0.00 0.00 177.48   313.18  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 19372.71 08-JAN-07:00 8945.92 4728.51 4258.44 0.00 0.00 0.00 0.00 0.00 0.00
February 15563.58 01-FEB-11:33 7667.93 11821.18 11178.41 0.00 0.00 0.00 0.00 0.00 0.00
March 14986.93 12-MAR-10:33 11501.89 14185.53 12775.33 0.00 0.00 0.00 0.00 0.00 0.00
April 15146.86 30-APR-10:33 11501.89 14185.53 12775.33 0.00 0.00 0.00 0.00 0.00 0.00
May 14866.17 28-MAY-10:33 11501.89 14185.53 12775.33 0.00 0.00 0.00 0.00 0.00 0.00
June 14996.96 25-JUN-10:33 11501.89 14185.53 12775.33 0.00 0.00 0.00 0.00 0.00 0.00
July 15921.42 23-JUL-10:33 11501.89 14185.53 12775.33 0.00 0.00 0.00 0.00 0.00 0.00
August 15903.34 06-AUG-10:33 11501.89 14185.53 12775.33 0.00 0.00 0.00 0.00 0.00 0.00
September 16508.01 30-SEP-10:33 11501.89 11821.18 11178.41 0.00 0.00 0.00 0.00 0.00 0.00
October 18191.50 20-OCT-21:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
November 18811.19 30-NOV-22:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
December 18396.42 01-DEC-22:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 14866.17   7667.93 4728.51 4258.44 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19372.71   11501.89 14185.53 12775.33 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3305.32 14-JAN-12:40 389.84 195.67 252.59 0.00 0.00 0.00 0.00 15.30 0.00
February 2875.02 02-FEB-12:40 259.90 195.67 252.59 0.00 0.00 0.00 0.00 0.00 54.64
March 2588.16 11-MAR-13:00 389.84 195.67 252.59 0.00 0.00 0.00 0.00 0.00 0.03
April 2063.21 08-APR-10:33 1169.53 587.01 757.77 0.00 0.00 0.00 0.00 0.00 12.86
May 2012.07 04-MAY-10:33 779.69 587.01 757.77 0.00 0.00 0.00 0.00 0.00 5.82
June 1932.52 25-JUN-10:33 1169.53 704.41 866.03 0.00 0.00 0.00 0.00 11.56 0.00
July 2118.98 30-JUL-10:33 1169.53 704.41 866.03 0.00 0.00 0.00 0.00 21.99 0.00
August 2198.77 27-AUG-10:33 1169.53 704.41 866.03 0.00 0.00 0.00 0.00 1.60 0.00
September 3544.59 30-SEP-13:10 389.84 195.67 252.59 0.00 0.00 0.00 0.00 89.26 0.00
October 4164.01 16-OCT-12:10 259.90 195.67 252.59 0.00 0.00 0.00 0.00 129.44 0.00
November 3645.57 19-NOV-12:30 389.84 234.80 288.68 0.00 0.00 0.00 0.00 28.55 0.00
December 3480.70 19-DEC-12:50 259.90 195.67 252.59 0.00 0.00 0.00 0.00 21.01 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1932.52   259.90 195.67 252.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4164.01   1169.53 704.41 866.03 0.00 0.00 0.00 0.00 129.44 54.64



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1616.30 08-JAN-07:00 1053.36 271.91 334.29 0.00 0.00 0.00 0.00 0.00 97.88
February 1496.17 03-FEB-21:20 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 0.00 57.37
March 1500.32 24-MAR-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 0.00 50.73
April 1614.91 27-APR-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 0.00 46.06
May 1625.61 03-MAY-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 0.00 36.71
June 1679.69 30-JUN-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 0.00 36.53
July 1788.09 31-JUL-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 0.00 22.61
August 1849.01 18-AUG-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 0.00 22.63
September 2050.44 29-SEP-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 2.64 0.00
October 2100.96 16-OCT-20:10 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 0.00 15.74
November 1552.13 19-NOV-11:33 1354.32 815.72 1002.86 0.00 0.00 0.00 0.00 12.96 0.00
December 1576.89 05-DEC-22:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 0.00 32.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1496.17   1053.36 271.91 334.29 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2100.96   1354.32 815.72 1002.86 0.00 0.00 0.00 0.00 12.96 97.88



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1316.97 20-JAN-11:33 190.94 1133.66 927.81 0.00 0.00 0.00 0.00 0.00 6.67
February 1266.30 02-FEB-11:33 190.94 1133.66 927.81 0.00 0.00 0.00 0.00 0.00 29.34
March 1292.86 19-MAR-10:33 286.42 1360.40 1060.35 0.00 0.00 0.00 0.00 0.00 27.14
April 1374.14 30-APR-10:33 286.42 1360.40 1060.35 0.00 0.00 0.00 0.00 36.22 0.00
May 1394.17 04-MAY-10:33 190.94 1133.66 927.81 0.00 0.00 0.00 0.00 0.00 4.79
June 1452.33 25-JUN-10:33 286.42 1360.40 1060.35 0.00 0.00 0.00 0.00 3.11 0.00
July 1514.78 23-JUL-10:33 286.42 1360.40 1060.35 0.00 0.00 0.00 0.00 28.67 0.00
August 1501.24 19-AUG-10:33 286.42 1133.66 927.81 0.00 0.00 0.00 0.00 18.77 0.00
September 1547.43 30-SEP-10:33 286.42 1133.66 927.81 0.00 0.00 0.00 0.00 76.11 0.00
October 1538.23 16-OCT-10:33 190.94 1133.66 927.81 0.00 0.00 0.00 0.00 133.43 0.00
November 1351.63 19-NOV-11:33 286.42 1360.40 1060.35 0.00 0.00 0.00 0.00 38.85 0.00
December 1315.58 19-DEC-11:33 190.94 1133.66 927.81 0.00 0.00 0.00 0.00 28.49 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1266.30   190.94 1133.66 927.81 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1547.43   286.42 1360.40 1060.35 0.00 0.00 0.00 0.00 133.43 29.34



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 623.22 20-JAN-11:33 146.88 189.77 267.65 0.00 0.00 0.00 0.00 0.00 3.57
February 598.69 02-FEB-11:33 146.88 189.77 267.65 0.00 0.00 0.00 0.00 0.00 16.60
March 610.36 23-MAR-10:33 146.88 189.77 267.65 0.00 0.00 0.00 0.00 1.08 0.00
April 650.04 30-APR-10:33 220.32 227.72 305.88 0.00 0.00 0.00 0.00 21.21 0.00
May 658.80 04-MAY-10:33 146.88 189.77 267.65 0.00 0.00 0.00 0.00 0.00 2.39
June 684.55 25-JUN-10:33 220.32 227.72 305.88 0.00 0.00 0.00 0.00 2.33 0.00
July 715.58 23-JUL-10:33 220.32 227.72 305.88 0.00 0.00 0.00 0.00 16.98 0.00
August 709.72 19-AUG-10:33 220.32 189.77 267.65 0.00 0.00 0.00 0.00 11.21 0.00
September 735.66 30-SEP-10:33 220.32 189.77 267.65 0.00 0.00 0.00 0.00 43.95 0.00
October 734.00 16-OCT-10:33 146.88 189.77 267.65 0.00 0.00 0.00 0.00 76.79 0.00
November 643.94 19-NOV-11:33 220.32 227.72 305.88 0.00 0.00 0.00 0.00 22.32 0.00
December 625.48 19-DEC-11:33 146.88 189.77 267.65 0.00 0.00 0.00 0.00 16.46 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 598.69   146.88 189.77 267.65 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 735.66   220.32 227.72 305.88 0.00 0.00 0.00 0.00 76.79 16.60



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 37582.47 24-JAN-21:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 103.36
February 37448.00 03-FEB-21:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 164.38
March 37697.31 23-MAR-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 148.52
April 38001.83 26-APR-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 102.91
May 38015.54 04-MAY-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 103.02
June 38024.64 30-JUN-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 117.91
July 38288.05 19-JUL-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 73.00
August 38230.72 18-AUG-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 73.06
September 38524.41 29-SEP-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 14.19 0.00
October 38368.76 16-OCT-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 43.45
November 37448.82 28-NOV-21:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 164.66
December 37700.86 05-DEC-21:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 118.46
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 37448.00   705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38524.41   705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 14.19 164.66



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 13066.57 14-JAN-12:40 5122.80 298.55 355.63 0.00 0.00 0.00 0.00 33.85 0.00
February 10990.21 20-FEB-11:00 8538.00 358.25 406.43 0.00 0.00 0.00 0.00 0.00 208.88
March 10917.54 11-MAR-12:50 5122.80 298.55 355.63 0.00 0.00 0.00 0.00 0.00 0.04
April 9281.91 08-APR-10:33 15368.40 895.64 1066.88 0.00 0.00 0.00 0.00 0.00 40.28
May 8907.76 04-MAY-21:20 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 0.00 182.63
June 8750.62 25-JUN-10:33 15368.40 1074.76 1219.29 0.00 0.00 0.00 0.00 13.04 0.00
July 9351.72 30-JUL-10:33 15368.40 1074.76 1219.29 0.00 0.00 0.00 0.00 41.60 0.00
August 9692.55 27-AUG-10:33 15368.40 1074.76 1219.29 0.00 0.00 0.00 0.00 0.00 3.42
September 12510.34 30-SEP-12:00 5122.80 298.55 355.63 0.00 0.00 0.00 0.00 197.59 0.00
October 14122.28 15-OCT-12:00 5122.80 358.25 406.43 0.00 0.00 0.00 0.00 198.53 0.00
November 14301.89 19-NOV-11:00 8538.00 358.25 406.43 0.00 0.00 0.00 0.00 50.65 0.00
December 12938.47 16-DEC-13:00 5122.80 298.55 355.63 0.00 0.00 0.00 0.00 50.92 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8750.62   5122.80 298.55 355.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14301.89   15368.40 1174.60 1219.29 0.00 0.00 0.00 0.00 198.53 208.88



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 33503.26 18-JAN-22:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 537.93
February 32802.11 01-FEB-22:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 829.98
March 32101.29 24-MAR-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 829.84
April 32520.34 26-APR-22:00 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 598.95
May 33670.75 04-MAY-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 522.21
June 33472.85 28-JUN-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 521.36
July 34980.46 31-JUL-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 373.72
August 35567.76 18-AUG-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 370.32
September 39577.34 29-SEP-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 42.14 0.00
October 40238.61 16-OCT-20:10 40553.76 9124.61 9501.36 0.00 0.00 0.00 0.00 0.00 257.49
November 33567.47 20-NOV-22:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 754.28
December 35094.34 05-DEC-22:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 510.89
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 32101.29   40553.76 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 40238.61   45622.98 9124.61 9501.36 0.00 0.00 0.00 0.00 42.14 829.98



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2773.34 14-JAN-16:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 2.70 0.00
February 2732.73 03-FEB-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 14.82
March 2788.34 11-MAR-16:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 0.00 9.56
April 2798.83 01-APR-15:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 0.98 0.00
May 2670.37 17-MAY-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 6.90
June 2704.29 30-JUN-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 1.25 0.00
July 2812.62 19-JUL-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 25.75 0.00
August 2786.65 18-AUG-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 24.45 0.00
September 2643.57 13-SEP-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.08
October 2970.36 15-OCT-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 51.70 0.00
November 2767.99 19-NOV-09:02 324.00 411.62 979.84 0.00 0.00 0.00 0.00 12.44 0.00
December 2788.91 05-DEC-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.04 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2643.57   324.00 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2970.36   583.20 411.62 979.84 0.00 0.00 0.00 0.00 51.70 14.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2639.25 14-JAN-16:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 3.38 0.00
February 2598.87 03-FEB-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 14.10
March 2657.91 11-MAR-16:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 8.98
April 2678.29 01-APR-15:01 378.00 282.96 534.64 0.00 0.00 0.00 0.00 1.31 0.00
May 2590.25 17-MAY-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 6.95
June 2614.88 30-JUN-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 1.08 0.00
July 2687.05 19-JUL-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 25.53 0.00
August 2675.66 19-AUG-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 20.09 0.00
September 2588.08 11-SEP-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 5.03
October 2830.16 16-OCT-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 45.90 0.00
November 2568.51 27-NOV-16:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 0.00 19.90
December 2654.36 05-DEC-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.72 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2568.51   324.00 205.78 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2830.16   680.40 282.96 534.64 0.00 0.00 0.00 0.00 45.90 19.90



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 633.45 14-JAN-12:40 0.00 25.41 74.82 0.00 0.00 0.00 0.00 3.64 0.00
February 569.66 02-FEB-12:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 7.34
March 476.04 11-MAR-13:30 0.00 25.41 74.82 0.00 0.00 0.00 0.00 1.16 0.00
April 355.93 08-APR-13:10 0.00 25.41 74.82 0.00 0.00 0.00 0.00 0.00 2.91
May 254.24 04-MAY-12:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.23 0.00
June 184.28 29-JUN-17:13 0.00 154.75 394.73 0.00 0.00 0.00 0.00 0.00 1.33
July 278.20 31-JUL-13:00 0.00 21.56 67.08 0.00 0.00 0.00 0.00 8.50 0.00
August 348.39 30-AUG-13:00 0.00 21.56 67.08 0.00 0.00 0.00 0.00 1.16 0.00
September 629.55 30-SEP-13:30 0.00 25.41 74.82 0.00 0.00 0.00 0.00 15.59 0.00
October 738.33 16-OCT-12:20 0.00 21.56 67.08 0.00 0.00 0.00 0.00 21.54 0.00
November 684.84 19-NOV-13:00 0.00 25.41 74.82 0.00 0.00 0.00 0.00 6.69 0.00
December 642.41 19-DEC-13:00 0.00 21.56 67.08 0.00 0.00 0.00 0.00 4.87 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 184.28   0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 738.33   0.00 154.75 394.73 0.00 0.00 0.00 0.00 21.54 7.34



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 828.61 15-JAN-09:02 270.00 215.63 799.99 0.00 0.00 0.00 0.00 1.57 0.00
February 745.81 20-FEB-09:02 324.00 258.76 959.99 0.00 0.00 0.00 0.00 0.00 14.74
March 799.31 11-MAR-16:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 0.25 0.00
April 824.70 26-APR-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 1.98 0.00
May 818.11 04-MAY-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 0.07 0.00
June 817.08 30-JUN-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 1.72 0.00
July 839.46 18-JUL-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 1.11 0.00
August 842.65 19-AUG-18:02 702.00 462.06 758.70 0.00 0.00 0.00 0.00 0.48 0.00
September 850.16 30-SEP-18:02 702.00 462.06 758.70 0.00 0.00 0.00 0.00 0.45 0.00
October 920.21 14-OCT-15:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 18.76 0.00
November 859.85 19-NOV-09:02 324.00 258.76 959.99 0.00 0.00 0.00 0.00 4.63 0.00
December 826.28 05-DEC-09:02 216.00 203.31 665.80 0.00 0.00 0.00 0.00 5.56 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 745.81   216.00 129.38 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 920.21   831.60 462.06 959.99 0.00 0.00 0.00 0.00 18.76 14.74



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2455.23 14-JAN-16:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 2.63 0.00
February 2441.81 01-FEB-09:02 216.00 323.41 679.57 0.00 0.00 0.00 0.00 0.00 2.01
March 2438.19 11-MAR-16:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 0.00 8.87
April 2473.12 01-APR-15:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 1.02 0.00
May 2345.85 04-MAY-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 4.84
June 2332.87 02-JUN-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 13.29
July 2373.99 19-JUL-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 25.90 0.00
August 2425.26 19-AUG-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 20.49 0.00
September 2364.08 30-SEP-18:02 702.00 735.03 774.39 0.00 0.00 0.00 0.00 0.00 0.39
October 2614.49 15-OCT-08:62 324.00 411.62 979.84 0.00 0.00 0.00 0.00 44.56 0.00
November 2531.02 19-NOV-09:02 324.00 411.62 979.84 0.00 0.00 0.00 0.00 10.35 0.00
December 2515.91 05-DEC-09:02 216.00 323.41 679.57 0.00 0.00 0.00 0.00 10.68 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2332.87   216.00 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2614.49   702.00 735.03 979.84 0.00 0.00 0.00 0.00 44.56 13.29



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2190.78 14-JAN-16:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 9.51 0.00
February 2261.59 01-FEB-09:02 216.00 323.38 679.49 0.00 0.00 0.00 0.00 1.47 0.00
March 2260.02 11-MAR-16:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 5.55
April 2309.64 26-APR-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.96 0.00
May 2260.47 24-MAY-08:62 216.00 323.38 679.49 0.00 0.00 0.00 0.00 0.00 32.49
June 2251.24 02-JUN-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 13.41
July 2277.44 19-JUL-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 25.74 0.00
August 2289.17 19-AUG-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 20.44 0.00
September 2287.68 30-SEP-18:02 702.00 734.94 774.30 0.00 0.00 0.00 0.00 0.00 0.18
October 2503.20 15-OCT-08:62 324.00 411.57 979.73 0.00 0.00 0.00 0.00 44.89 0.00
November 2404.56 19-NOV-09:02 324.00 411.57 979.73 0.00 0.00 0.00 0.00 11.16 0.00
December 2392.48 05-DEC-09:02 216.00 323.38 679.49 0.00 0.00 0.00 0.00 11.44 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2190.78   216.00 205.78 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2503.20   702.00 734.94 979.73 0.00 0.00 0.00 0.00 44.89 32.49



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2258.34 08-JAN-07:00 1760.39 746.93 0.00 0.00 0.00 0.00 0.00 0.00 177.36
February 1981.93 04-FEB-11:45 1508.90 1244.88 0.00 0.00 0.00 0.00 0.00 0.00 13.88
March 1992.74 12-MAR-10:33 2263.36 2240.78 0.00 0.00 0.00 0.00 0.00 0.00 7.34
April 2098.26 30-APR-10:33 2263.36 2240.78 0.00 0.00 0.00 0.00 0.00 25.73 0.00
May 2099.24 04-MAY-10:33 1508.90 1867.32 0.00 0.00 0.00 0.00 0.00 0.00 4.83
June 2151.16 25-JUN-10:33 2263.36 2240.78 0.00 0.00 0.00 0.00 0.00 2.55 0.00
July 2248.67 23-JUL-10:33 2263.36 2240.78 0.00 0.00 0.00 0.00 0.00 22.06 0.00
August 2268.17 19-AUG-10:33 2263.36 1867.32 0.00 0.00 0.00 0.00 0.00 12.99 0.00
September 2357.60 30-SEP-10:33 2263.36 1867.32 0.00 0.00 0.00 0.00 0.00 56.40 0.00
October 2367.29 17-OCT-10:33 1508.90 1867.32 0.00 0.00 0.00 0.00 0.00 58.61 0.00
November 2120.89 19-NOV-11:33 2263.36 2240.78 0.00 0.00 0.00 0.00 0.00 25.70 0.00
December 2032.54 05-DEC-11:33 1508.90 1867.32 0.00 0.00 0.00 0.00 0.00 5.48 0.00
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1981.93   1508.90 746.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2367.29   2263.36 2240.78 0.00 0.00 0.00 0.00 0.00 58.61 177.36



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2866.89 14-JAN-16:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 2.25 0.00
February 2818.64 03-FEB-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 15.14
March 2883.92 11-MAR-16:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 0.00 10.05
April 2892.67 01-APR-15:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 0.54 0.00
May 2731.91 04-MAY-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 4.82
June 2768.52 28-JUN-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.07
July 2860.19 18-JUL-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 20.96 0.00
August 2849.59 06-AUG-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 13.43 0.00
September 2730.44 08-SEP-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 5.93
October 3075.83 15-OCT-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 51.16 0.00
November 2812.75 19-NOV-09:02 324.00 411.62 979.84 0.00 0.00 0.00 0.00 13.38 0.00
December 2882.53 05-DEC-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.40
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2730.44   324.00 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3075.83   583.20 411.62 979.84 0.00 0.00 0.00 0.00 51.16 15.14



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2714.13 14-JAN-16:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 3.07 0.00
February 2665.65 03-FEB-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 14.26
March 2737.82 11-MAR-16:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 9.39
April 2757.61 01-APR-15:01 378.00 282.96 534.64 0.00 0.00 0.00 0.00 0.94 0.00
May 2643.24 17-MAY-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 7.45
June 2676.51 28-JUN-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 0.22
July 2768.19 18-JUL-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 20.82 0.00
August 2766.27 18-AUG-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 23.93 0.00
September 2668.61 10-SEP-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 5.41
October 2919.66 16-OCT-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 45.42 0.00
November 2625.90 27-NOV-16:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 0.00 19.74
December 2728.31 05-DEC-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.44 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2625.90   324.00 205.78 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2919.66   680.40 282.96 534.64 0.00 0.00 0.00 0.00 45.42 19.74



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1564.22 14-JAN-16:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 0.29 0.00
February 1524.80 03-FEB-16:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 0.00 8.33
March 1541.67 10-MAR-16:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 0.00 4.16
April 1552.40 01-APR-15:01 378.00 177.90 523.86 0.00 0.00 0.00 0.00 0.00 0.05
May 1458.93 03-MAY-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 0.00 3.30
June 1440.38 20-JUN-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 0.00 3.01
July 1452.95 31-JUL-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 9.63 0.00
August 1518.08 19-AUG-15:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 10.20 0.00
September 1486.11 30-SEP-18:02 702.00 462.06 758.70 0.00 0.00 0.00 0.00 0.00 0.58
October 1646.35 16-OCT-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 22.60 0.00
November 1575.24 19-NOV-09:02 324.00 258.76 959.99 0.00 0.00 0.00 0.00 4.98 0.00
December 1565.90 05-DEC-16:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 0.00 0.93
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1440.38   324.00 129.38 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1646.35   702.00 462.06 959.99 0.00 0.00 0.00 0.00 22.60 8.33



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19641.94 18-JAN-22:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 122.39
February 19019.07 01-FEB-23:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 187.92
March 19387.93 24-MAR-22:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 187.73
April 20332.55 26-APR-22:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 136.08
May 20758.19 04-MAY-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 118.86
June 20979.41 27-JUN-22:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 118.65
July 21220.96 19-JUL-22:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 101.61
August 21058.94 17-AUG-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 84.84
September 21633.43 29-SEP-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 7.86 0.00
October 21252.04 04-OCT-22:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 51.12
November 19265.95 10-NOV-23:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 153.67
December 19734.93 05-DEC-23:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 102.11
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 19019.07   26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21633.43   26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 7.86 187.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 21236.84 18-JAN-22:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 122.39
February 20667.54 01-FEB-22:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 187.95
March 20929.87 24-MAR-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 187.92
April 21803.24 26-APR-22:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 136.08
May 22197.20 04-MAY-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 118.86
June 22341.63 27-JUN-21:50 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 118.65
July 22546.24 19-JUL-22:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 101.61
August 22381.49 17-AUG-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 84.85
September 22927.48 29-SEP-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 7.86 0.00
October 22569.84 04-OCT-22:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 51.12
November 20885.67 10-NOV-22:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 153.67
December 21247.39 05-DEC-23:00 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 102.11
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 20667.54   26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22927.48   26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 7.86 187.95



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 28217.33 20-JAN-11:45 1067.42 605.46 29825.71 37488.05 0.00 0.00 0.00 0.00 33.47
February 28098.85 01-FEB-11:45 1067.42 605.46 29825.71 37488.05 0.00 0.00 0.00 20.44 0.00
March 28890.45 19-MAR-10:50 800.57 363.28 14912.86 18744.03 0.00 0.00 0.00 0.00 65.78
April 29394.41 30-APR-10:33 2401.70 1089.83 44738.57 56232.08 0.00 0.00 0.00 22.90 0.00
May 29095.03 04-MAY-10:33 1601.14 908.19 44738.57 56232.08 0.00 0.00 0.00 0.00 30.89
June 29431.46 25-JUN-10:33 2401.70 1089.83 44738.57 56232.08 0.00 0.00 0.00 0.00 16.02
July 29906.79 23-JUL-10:33 2401.70 1089.83 44738.57 56232.08 0.00 0.00 0.00 22.97 0.00
August 29803.87 19-AUG-10:33 2401.70 908.19 44738.57 56232.08 0.00 0.00 0.00 8.40 0.00
September 30317.49 30-SEP-10:50 800.57 302.73 14912.86 18744.03 0.00 0.00 0.00 93.86 0.00
October 30146.57 15-OCT-10:50 1601.14 726.55 29825.71 37488.05 0.00 0.00 0.00 109.49 0.00
November 28840.06 19-NOV-11:50 800.57 363.28 14912.86 18744.03 0.00 0.00 0.00 27.73 0.00
December 28120.85 05-DEC-11:33 1601.14 908.19 44738.57 56232.08 0.00 0.00 0.00 0.00 11.20
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 28098.85   800.57 302.73 14912.86 18744.03 0.00 0.00 0.00 0.00 0.00
Maximum of Months 30317.49   2401.70 1089.83 44738.57 56232.08 0.00 0.00 0.00 109.49 65.78



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4283.16 20-JAN-11:33 1596.96 1976.27 0.00 0.00 0.00 0.00 0.00 0.00 18.81
February 4091.67 01-FEB-11:45 1064.64 1317.51 0.00 0.00 0.00 0.00 0.00 41.79 0.00
March 4264.77 11-MAR-11:33 2395.44 1976.27 0.00 0.00 0.00 0.00 0.00 17.99 0.00
April 4420.48 30-APR-10:33 2395.44 2371.52 0.00 0.00 0.00 0.00 0.00 40.92 0.00
May 4495.64 04-MAY-10:33 1596.96 1976.27 0.00 0.00 0.00 0.00 0.00 0.00 15.47
June 4572.91 30-JUN-10:33 1596.96 1976.27 0.00 0.00 0.00 0.00 0.00 2.04 0.00
July 4797.85 30-JUL-10:33 2395.44 2371.52 0.00 0.00 0.00 0.00 0.00 16.93 0.00
August 4791.63 19-AUG-10:33 2395.44 1976.27 0.00 0.00 0.00 0.00 0.00 17.61 0.00
September 5724.55 30-SEP-13:40 798.48 658.76 0.00 0.00 0.00 0.00 0.00 109.46 0.00
October 5648.22 16-OCT-12:50 532.32 658.76 0.00 0.00 0.00 0.00 0.00 142.51 0.00
November 4509.46 19-NOV-11:33 2395.44 2371.52 0.00 0.00 0.00 0.00 0.00 39.61 0.00
December 4335.54 19-DEC-11:33 1596.96 1976.27 0.00 0.00 0.00 0.00 0.00 27.31 0.00
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4091.67   532.32 658.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5724.55   2395.44 2371.52 0.00 0.00 0.00 0.00 0.00 142.51 18.81



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.401362E+12 284097.72 17-JAN-20:10 0.577963E+12 517553.47 02-JAN-20:00
February 0.350395E+12 256699.86 13-FEB-20:30 0.494020E+12 476040.70 06-FEB-22:00
March 0.382177E+12 261394.26 22-MAR-18:10 0.582832E+12 512102.86 29-MAR-20:49
April 0.397652E+12 286073.54 26-APR-19:10 0.463707E+12 426577.75 15-APR-21:00
May 0.411364E+12 284813.72 04-MAY-19:10 0.462186E+12 409715.91 10-MAY-19:00
June 0.434234E+12 304396.79 29-JUN-18:10 0.393845E+12 368440.74 12-JUN-20:00
July 0.508917E+12 335919.20 31-JUL-19:10 0.394293E+12 347184.70 24-JUL-17:10
August 0.524645E+12 329081.79 14-AUG-19:10 0.393939E+12 347240.13 25-AUG-17:10
September 0.461797E+12 360462.95 29-SEP-19:10 0.387504E+12 347605.69 28-SEP-17:49
October 0.487100E+12 338139.32 04-OCT-19:00 0.424652E+12 371715.06 11-OCT-20:00
November 0.393565E+12 261895.51 10-NOV-20:00 0.493852E+12 489336.13 23-NOV-21:00
December 0.406641E+12 281743.24 05-DEC-20:10 0.568755E+12 507388.59 12-DEC-21:49
             
Annual Sum or Average 0.515985E+13     0.563755E+13    
Minimum of Months 0.350395E+12 256699.86   0.387504E+12 347184.70  
Maximum of Months 0.524645E+12 360462.95   0.582832E+12 517553.47  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.654020E+11 0.239327E+11 0.148212E+12 0.553309E+11 0.463819E+11 0.114206E+11 0.00 0.377350E+11 0.00 0.00 0.00 0.770493E+10 0.00
February 0.589667E+11 0.204568E+11 0.133859E+12 0.499764E+11 0.413625E+11 0.966565E+10 0.00 0.243946E+11 0.00 0.00 0.00 0.696236E+10 0.00
March 0.652650E+11 0.209666E+11 0.148223E+12 0.553338E+11 0.452930E+11 0.992494E+10 0.00 0.241913E+11 0.00 0.00 0.00 0.770356E+10 0.00
April 0.629187E+11 0.186400E+11 0.143397E+12 0.535455E+11 0.450119E+11 0.126701E+11 0.00 0.488796E+11 0.00 0.00 0.00 0.746525E+10 0.00
May 0.649566E+11 0.177966E+11 0.148223E+12 0.553320E+11 0.465897E+11 0.134118E+11 0.00 0.520465E+11 0.00 0.00 0.00 0.770480E+10 0.00
June 0.628376E+11 0.164989E+11 0.143446E+12 0.535482E+11 0.465517E+11 0.144860E+11 0.00 0.842378E+11 0.00 0.00 0.00 0.745705E+10 0.00
July 0.648558E+11 0.173702E+11 0.148174E+12 0.553292E+11 0.496383E+11 0.169090E+11 0.00 0.143595E+12 0.00 0.00 0.00 0.771273E+10 0.00
August 0.650506E+11 0.186030E+11 0.148234E+12 0.553337E+11 0.501451E+11 0.173589E+11 0.00 0.156853E+12 0.00 0.00 0.00 0.770448E+10 0.00
September 0.630776E+11 0.195855E+11 0.143408E+12 0.535458E+11 0.474471E+11 0.152708E+11 0.00 0.106821E+12 0.00 0.00 0.00 0.746657E+10 0.00
October 0.653102E+11 0.219491E+11 0.148201E+12 0.553307E+11 0.501702E+11 0.158113E+11 0.00 0.117332E+12 0.00 0.00 0.00 0.770319E+10 0.00
November 0.633121E+11 0.227370E+11 0.143462E+12 0.535468E+11 0.456594E+11 0.120344E+11 0.00 0.402832E+11 0.00 0.00 0.00 0.744930E+10 0.00
December 0.653333E+11 0.243405E+11 0.148174E+12 0.553296E+11 0.469734E+11 0.116060E+11 0.00 0.419471E+11 0.00 0.00 0.00 0.771298E+10 0.00
                           
Annual Sum or Average 0.767286E+12 0.242877E+12 0.174501E+13 0.651483E+12 0.561224E+12 0.160570E+12 0.00 0.878316E+12 0.00 0.00 0.00 0.907472E+11 0.00
Minimum of Months 0.589667E+11 0.164989E+11 0.133859E+12 0.499764E+11 0.413625E+11 0.966565E+10 0.00 0.241913E+11 0.00 0.00 0.00 0.696236E+10 0.00
Maximum of Months 0.654020E+11 0.243405E+11 0.148234E+12 0.553338E+11 0.501702E+11 0.173589E+11 0.00 0.156853E+12 0.00 0.00 0.00 0.771298E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.169407E+12 0.00 0.256638E+12 0.00 0.00
February 0.137204E+12 0.00 0.124779E+12 0.00 0.232037E+12 0.00 0.00
March 0.152024E+12 0.00 0.175606E+12 0.00 0.255202E+12 0.00 0.00
April 0.146956E+12 0.00 0.730983E+11 0.00 0.243653E+12 0.00 0.00
May 0.151978E+12 0.00 0.624846E+11 0.00 0.247723E+12 0.00 0.00
June 0.147114E+12 0.00 0.104670E+11 0.00 0.236264E+12 0.00 0.00
July 0.151820E+12 0.00 0.688329E+09 0.00 0.241784E+12 0.00 0.00
August 0.152039E+12 0.00 0.286638E+09 0.00 0.241614E+12 0.00 0.00
September 0.146971E+12 0.00 0.500569E+10 0.00 0.235527E+12 0.00 0.00
October 0.151903E+12 0.00 0.259765E+11 0.00 0.246772E+12 0.00 0.00
November 0.147091E+12 0.00 0.104048E+12 0.00 0.242713E+12 0.00 0.00
December 0.151820E+12 0.00 0.162506E+12 0.00 0.254429E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.914352E+12 0.00 0.293436E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 0.286638E+09 0.00 0.232037E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.175606E+12 0.00 0.256638E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 62892.57 02-JAN-20:10 15448.40 01-JAN-00:10 89475.41 02-JAN-07:10 39726.11 18-JAN-07:19 29641.45 18-JAN-22:10 7232.59 18-JAN-13:30 0.00 01-JAN-00:10
February 62892.57 01-FEB-20:10 15448.40 01-FEB-00:10 89475.41 01-FEB-07:10 39725.67 10-FEB-07:19 27881.36 01-FEB-22:10 7058.36 01-FEB-13:09 0.00 01-FEB-00:10
March 62892.57 01-MAR-20:10 15448.40 01-MAR-00:10 89475.41 01-MAR-07:10 39726.11 13-MAR-06:19 27770.58 23-MAR-21:10 7179.93 12-MAR-09:00 0.00 01-MAR-00:10
April 62892.57 03-APR-19:10 15448.40 01-APR-00:10 89475.41 03-APR-06:10 39725.51 05-APR-06:19 28956.61 26-APR-21:10 7128.95 26-APR-16:00 0.00 01-APR-00:10
May 62892.57 01-MAY-19:10 15448.40 01-MAY-00:10 89475.41 01-MAY-06:10 39725.08 08-MAY-06:19 30100.75 04-MAY-21:10 7207.78 18-MAY-15:09 0.00 01-MAY-00:10
June 62892.57 01-JUN-19:10 15448.40 01-JUN-00:10 89475.41 01-JUN-06:10 39725.08 09-JUN-06:19 30020.30 30-JUN-21:10 7517.75 29-JUN-18:10 0.00 01-JUN-00:10
July 62892.57 03-JUL-19:10 15448.40 01-JUL-00:10 89475.41 03-JUL-06:10 39725.08 11-JUL-06:19 31771.85 31-JUL-21:10 7660.71 31-JUL-18:10 0.00 01-JUL-00:10
August 62892.57 01-AUG-19:10 15448.40 01-AUG-00:10 89475.41 01-AUG-06:10 39725.51 21-AUG-06:19 31825.03 18-AUG-21:10 7566.81 14-AUG-18:10 0.00 01-AUG-00:10
September 62892.57 01-SEP-19:10 15448.40 01-SEP-00:10 89475.41 01-SEP-06:10 39726.11 18-SEP-06:19 34552.74 29-SEP-21:10 7962.52 29-SEP-15:30 0.00 01-SEP-00:10
October 62892.57 02-OCT-19:10 15448.40 01-OCT-00:10 89475.41 02-OCT-06:10 39726.11 05-OCT-06:19 37012.34 16-OCT-21:10 7715.50 16-OCT-18:10 0.00 01-OCT-00:10
November 62892.57 01-NOV-19:10 15448.40 01-NOV-00:10 89475.41 01-NOV-06:10 39726.11 01-NOV-06:19 29636.28 28-NOV-22:10 7500.12 19-NOV-10:00 0.00 01-NOV-00:10
December 62892.57 01-DEC-20:10 15448.40 01-DEC-00:10 89475.41 01-DEC-07:10 39726.11 08-DEC-07:19 31742.42 05-DEC-22:10 6994.64 16-DEC-15:50 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 62892.57   15448.40   89475.41   39725.08   27770.58   6994.64   0.00  
Maximum of Months 62892.57   15448.40   89475.41   39726.11   37012.34   7962.52   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 84570.38 14-JAN-11:39 0.00 0.00 0.00 4738.43 13-JAN-19:10 0.00
February 78380.68 01-FEB-11:50 0.00 0.00 0.00 4738.44 13-FEB-19:10 0.00
March 72945.77 23-MAR-15:20 0.00 0.00 0.00 4738.50 10-MAR-19:10 0.00
April 86769.99 26-APR-10:50 0.00 0.00 0.00 4738.58 04-APR-18:10 0.00
May 67373.67 04-MAY-15:09 0.00 0.00 0.00 4738.43 15-MAY-18:10 0.00
June 100574.54 29-JUN-18:10 0.00 0.00 0.00 4738.61 05-JUN-18:10 0.00
July 128156.10 19-JUL-15:20 0.00 0.00 0.00 4738.15 10-JUL-18:10 0.00
August 136342.89 18-AUG-15:09 0.00 0.00 0.00 4738.33 09-AUG-18:19 0.00
September 164257.47 29-SEP-12:00 0.00 0.00 0.00 4738.37 11-SEP-18:10 0.00
October 180333.25 16-OCT-10:50 0.00 0.00 0.00 4738.47 11-OCT-18:10 0.00
November 92481.26 19-NOV-10:00 0.00 0.00 0.00 4738.53 27-NOV-19:10 0.00
December 82221.26 05-DEC-09:00 0.00 0.00 0.00 4738.51 18-DEC-19:10 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 67373.67   0.00 0.00 0.00 4738.15   0.00
Maximum of Months 180333.25   0.00 0.00 0.00 4738.61   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 284097.72 17-JAN-20:10 62892.57 88772.42 15448.40 32151.31 23036.21 6461.57 0.00 49411.32 0.00
February 256699.86 13-FEB-20:30 62892.57 88772.42 15448.40 32159.77 22213.86 5353.45 0.00 23534.30 0.00
March 261394.26 22-MAR-18:10 55920.94 79417.81 15448.40 31837.63 21944.25 6358.21 0.00 43306.95 0.00
April 286073.54 26-APR-19:10 62892.57 88772.42 15448.40 32151.31 22898.48 6771.73 0.00 50865.55 0.00
May 284813.72 04-MAY-19:10 62892.57 88772.42 15448.40 32151.31 22980.57 6683.83 0.00 49867.18 0.00
June 304396.79 29-JUN-18:10 53784.22 79417.81 0.00 31835.81 24238.47 7517.75 0.00 100574.54 0.00
July 335919.20 31-JUL-19:10 62892.57 88772.42 15448.40 32151.31 25105.20 7544.41 0.00 97679.58 0.00
August 329081.79 14-AUG-19:10 62892.57 88772.42 15448.40 32151.31 24910.74 7489.24 0.00 91093.39 0.00
September 360462.95 29-SEP-19:10 62892.57 88772.42 15448.40 32151.31 29864.99 7344.14 0.00 118286.16 0.00
October 338139.32 04-OCT-19:00 62892.57 88772.42 15448.40 32159.77 26258.87 7516.23 0.00 98868.56 0.00
November 261895.51 10-NOV-20:00 62892.57 88772.42 15448.40 32159.77 23546.06 5610.65 0.00 28034.77 0.00
December 281743.24 05-DEC-20:10 62892.57 88772.42 15448.40 32151.31 24993.77 6341.93 0.00 45790.88 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 256699.86   53784.22 79417.81 0.00 31835.81 21944.25 5353.45 0.00 23534.30 0.00
Maximum of Months 360462.95   62892.57 88772.42 15448.40 32159.77 29864.99 7544.41 0.00 118286.16 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 230195.00 08-JAN-06:00 0.00 246231.46 30-JAN-21:30 0.00
February 104248.32 01-FEB-18:10 0.00 194772.40 04-FEB-05:00 0.00 246240.35 02-FEB-21:00 0.00
March 104248.32 01-MAR-18:10 0.00 226993.60 30-MAR-02:00 0.00 246090.49 01-MAR-21:40 0.00
April 104248.32 01-APR-17:10 0.00 173656.88 01-APR-05:00 0.00 245526.77 04-APR-20:30 0.00
May 104248.32 01-MAY-17:10 0.00 164638.38 14-MAY-04:49 0.00 244926.86 01-MAY-20:49 0.00
June 104248.32 01-JUN-17:10 0.00 103628.26 13-JUN-03:00 0.00 244190.24 01-JUN-20:19 0.00
July 104248.32 01-JUL-17:10 0.00 40083.00 06-JUL-02:00 0.00 243623.07 03-JUL-20:40 0.00
August 104248.32 01-AUG-17:10 0.00 10217.39 28-AUG-06:30 0.00 243538.43 29-AUG-20:49 0.00
September 104248.32 01-SEP-17:10 0.00 98640.15 20-SEP-03:00 0.00 244028.85 29-SEP-20:30 0.00
October 104248.32 02-OCT-17:10 0.00 149508.43 12-OCT-05:00 0.00 244763.04 31-OCT-20:40 0.00
November 104248.32 01-NOV-17:10 0.00 182545.33 29-NOV-22:00 0.00 245415.63 28-NOV-21:49 0.00
December 104248.32 01-DEC-18:10 0.00 197805.55 23-DEC-05:00 0.00 245983.75 29-DEC-21:30 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 10217.39   0.00 243538.43   0.00
Maximum of Months 104248.32   0.00 230195.00   0.00 246240.35   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.33 21.68 0.33 21.68
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.70 0.17 21.70
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 1.17 22.08 1.17 22.08
October 0.00 0.00 0.00 0.00 2.00 21.91 2.00 21.91
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.67 21.93 3.67 21.93
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.00 22.08 2.00 22.08



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.67 21.95 0.67 21.95
October 0.00 0.00 0.00 0.00 0.33 21.91 0.33 21.91
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1.00 21.94 1.00 21.94
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.67 21.95 0.67 21.95



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.33 21.79 0.33 21.79
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.33 21.79 0.33 21.79
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.33 21.79 0.33 21.79



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 21.71 0.17 21.71
February 0.00 0.00 0.00 0.00 0.50 21.76 0.50 21.76
March 0.00 0.00 0.00 0.00 0.50 21.80 0.50 21.80
April 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.33 21.69 0.33 21.69
September 0.00 0.00 0.00 0.00 0.83 21.93 0.83 21.93
October 0.00 0.00 0.00 0.00 0.67 21.79 0.67 21.79
November 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
December 0.00 0.00 0.00 0.00 0.17 21.71 0.17 21.71
                 
Annual Sum or Average 0.00   0.00   3.50 21.79 3.50 21.79
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.83 21.93 0.83 21.93



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.33 21.68 0.33 21.68
April 0.00 0.00 0.00 0.00 0.17 21.71 0.17 21.71
May 0.00 0.00 0.00 0.00 0.33 21.67 0.33 21.67
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.50 21.69 0.50 21.69
August 0.00 0.00 0.00 0.00 0.50 21.70 0.50 21.70
September 0.00 0.00 0.00 0.00 0.67 21.78 0.67 21.78
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.50 21.71 2.50 21.71
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.67 21.78 0.67 21.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.17 21.67 0.17 21.67
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 21.74 0.33 21.74
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 1.83 22.08 1.83 22.08
October 0.00 0.00 0.00 0.00 2.50 21.93 2.50 21.93
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
                 
Annual Sum or Average 0.00   0.00   5.00 21.96 5.00 21.96
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.50 22.08 2.50 22.08



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 1.00 22.00 1.00 22.00
October 0.00 0.00 0.00 0.00 0.33 21.98 0.33 21.98
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1.33 22.00 1.33 22.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.00 22.00 1.00 22.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 2.83 21.92 2.83 21.92
February 0.00 0.00 0.00 0.00 1.67 21.79 1.67 21.79
March 0.00 0.00 0.00 0.00 0.83 21.82 0.83 21.82
April 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 1.33 22.13 1.33 22.13
October 0.00 0.00 0.00 0.00 6.17 21.98 6.17 21.98
November 0.00 0.00 0.00 0.00 1.50 21.81 1.50 21.81
December 0.00 0.00 0.00 0.00 3.50 21.82 3.50 21.82
                 
Annual Sum or Average 0.00   0.00   18.00 21.91 18.00 21.91
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.17 22.13 6.17 22.13



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 610.33 23.40 9.50 23.41 0.00 23.41
February 666.50 22.95 0.00 22.95 0.00 22.95
March 744.00 22.74 0.00 22.74 0.00 22.74
April 720.00 22.64 0.00 22.64 0.00 22.64
May 744.00 22.64 0.00 22.64 0.00 22.64
June 720.00 22.52 0.00 22.52 0.00 22.52
July 725.50 22.84 0.00 22.84 0.00 22.84
August 699.17 22.92 0.00 22.92 0.00 22.92
September 465.17 23.13 32.00 23.19 0.00 23.19
October 457.17 23.41 63.00 23.47 0.00 23.47
November 492.17 23.53 33.50 23.56 0.00 23.56
December 635.67 23.47 3.00 23.48 0.00 23.48
             
Annual Sum or Average 7679.67 22.97 141.00 22.99 0.00 22.99
Minimum of Months 457.17 22.52 0.00 22.52 0.00 22.52
Maximum of Months 744.00 23.53 63.00 23.56 0.00 23.56



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 595.67 21.64 88.00 21.92 4.17 21.91
February 572.50 21.50 54.83 21.70 2.50 21.70
March 671.67 21.37 50.33 21.51 6.33 21.51
April 655.83 21.65 18.17 21.70 0.00 21.70
May 736.67 21.44 0.00 21.44 0.00 21.44
June 720.00 21.69 0.00 21.69 0.00 21.69
July 693.33 22.08 7.17 22.10 0.00 22.10
August 549.00 22.26 100.33 22.44 0.00 22.44
September 505.33 22.09 150.67 22.46 0.00 22.46
October 503.17 22.12 161.17 22.54 0.00 22.54
November 568.17 21.78 88.67 22.07 0.67 22.07
December 579.00 21.72 83.50 22.00 0.00 22.00
             
Annual Sum or Average 7350.33 21.76 802.83 21.95 13.67 21.95
Minimum of Months 503.17 21.37 0.00 21.44 0.00 21.44
Maximum of Months 736.67 22.26 161.17 22.54 6.33 22.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 705.83 22.63 7.50 22.64 0.00 22.64
February 636.83 22.59 2.17 22.59 0.00 22.59
March 706.83 22.42 8.00 22.44 0.00 22.44
April 595.17 22.65 45.33 22.73 0.00 22.73
May 639.33 22.62 27.67 22.67 0.00 22.67
June 498.00 22.71 101.00 22.89 9.33 22.90
July 380.83 22.89 254.33 23.23 60.00 23.26
August 341.17 22.99 320.50 23.35 71.83 23.37
September 364.00 22.90 178.67 23.20 18.83 23.20
October 482.67 23.02 133.00 23.19 21.17 23.20
November 643.83 22.84 17.17 22.87 0.00 22.87
December 717.17 22.81 3.00 22.81 0.00 22.81
             
Annual Sum or Average 6711.67 22.73 1098.33 22.87 181.17 22.89
Minimum of Months 341.17 22.42 2.17 22.44 0.00 22.44
Maximum of Months 717.17 23.02 320.50 23.35 71.83 23.37



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.84 0.00 21.84 0.00 21.84
February 672.00 21.88 0.00 21.88 0.00 21.88
March 744.00 21.74 0.00 21.74 0.00 21.74
April 720.00 22.13 0.00 22.13 0.00 22.13
May 744.00 22.32 0.00 22.32 0.00 22.32
June 699.00 22.68 0.00 22.68 0.00 22.68
July 657.50 22.91 0.50 22.91 0.00 22.91
August 665.33 22.89 0.00 22.89 0.00 22.89
September 708.67 22.73 1.83 22.73 0.00 22.73
October 684.33 22.76 2.67 22.77 0.00 22.77
November 720.00 22.17 0.00 22.17 0.00 22.17
December 744.00 22.00 0.00 22.00 0.00 22.00
             
Annual Sum or Average 8502.83 22.32 5.00 22.33 0.00 22.33
Minimum of Months 657.50 21.74 0.00 21.74 0.00 21.74
Maximum of Months 744.00 22.91 2.67 22.91 0.00 22.91



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.69 0.00 21.69 0.00 21.69
February 672.00 21.71 0.00 21.71 0.00 21.71
March 744.00 21.57 0.00 21.57 0.00 21.57
April 720.00 21.96 0.00 21.96 0.00 21.96
May 744.00 22.13 0.00 22.13 0.00 22.13
June 720.00 22.52 0.00 22.52 0.00 22.52
July 744.00 22.81 0.00 22.81 0.00 22.81
August 744.00 22.79 0.00 22.79 0.00 22.79
September 716.50 22.58 0.00 22.58 0.00 22.58
October 741.33 22.67 0.00 22.67 0.00 22.67
November 720.00 22.01 0.00 22.01 0.00 22.01
December 744.00 21.84 0.00 21.84 0.00 21.84
             
Annual Sum or Average 8753.83 22.19 0.00 22.19 0.00 22.19
Minimum of Months 672.00 21.57 0.00 21.57 0.00 21.57
Maximum of Months 744.00 22.81 0.00 22.81 0.00 22.81



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 284.33 23.14 580.67 23.19 201.67 23.34
February 254.00 23.21 543.83 23.19 186.33 23.34
March 305.50 23.23 612.17 23.17 227.17 23.33
April 295.50 23.53 624.17 23.22 250.17 23.39
May 306.33 23.53 649.33 23.23 259.00 23.39
June 296.50 23.79 653.33 23.26 278.00 23.42
July 297.83 23.96 700.67 23.26 296.83 23.42
August 300.83 23.96 703.67 23.25 300.17 23.42
September 290.67 23.84 659.17 23.26 277.33 23.42
October 282.67 23.57 651.33 23.24 242.33 23.39
November 281.33 23.28 583.83 23.23 212.33 23.38
December 266.50 23.07 575.00 23.20 180.67 23.34
             
Annual Sum or Average 3462.00 23.52 7537.17 23.23 2912.00 23.38
Minimum of Months 254.00 23.07 543.83 23.17 180.67 23.33
Maximum of Months 306.33 23.96 703.67 23.26 300.17 23.42



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 377.67 22.75 228.17 23.17 15.83 23.19
February 399.00 22.53 166.33 22.90 12.83 22.90
March 509.33 22.36 134.17 22.64 2.67 22.64
April 396.00 22.61 194.50 22.92 33.83 22.97
May 622.50 22.49 74.17 22.61 37.83 22.67
June 544.50 22.66 180.50 22.92 135.00 23.04
July 475.33 23.14 388.17 23.33 278.33 23.42
August 366.17 23.59 571.83 23.56 311.67 23.62
September 290.50 23.37 531.33 23.56 198.83 23.61
October 255.83 23.10 433.67 23.56 84.83 23.60
November 311.50 22.95 267.83 23.35 21.67 23.35
December 375.17 22.92 207.33 23.27 0.00 23.27
             
Annual Sum or Average 4923.50 22.82 3378.00 23.18 1133.33 23.25
Minimum of Months 255.83 22.36 74.17 22.61 0.00 22.64
Maximum of Months 622.50 23.59 571.83 23.56 311.67 23.62



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 477.50 23.05 99.00 23.20 11.00 23.21
February 466.33 22.98 74.00 23.10 9.33 23.11
March 522.33 22.76 73.50 22.90 0.33 22.90
April 412.83 22.84 196.83 23.18 12.83 23.20
May 445.50 22.78 159.50 23.08 24.83 23.11
June 381.67 22.98 327.50 23.40 96.33 23.46
July 414.00 23.39 423.50 23.63 225.00 23.70
August 366.33 23.67 445.50 23.78 280.50 23.82
September 255.17 23.56 406.83 23.74 165.67 23.78
October 215.00 23.39 305.50 23.67 61.83 23.70
November 376.00 23.24 138.50 23.41 18.67 23.42
December 499.83 23.28 52.33 23.34 0.00 23.34
             
Annual Sum or Average 4832.50 23.12 2702.50 23.39 906.33 23.45
Minimum of Months 215.00 22.76 52.33 22.90 0.00 22.90
Maximum of Months 522.33 23.67 445.50 23.78 280.50 23.82



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 732.00 21.48 20.67 21.47 20.67 21.45
February 657.17 21.38 9.50 21.38 9.50 21.37
March 728.00 21.34 18.17 21.32 18.17 21.30
April 685.33 21.47 0.33 21.47 0.33 21.47
May 724.67 21.48 0.00 21.48 0.00 21.48
June 676.83 21.47 0.00 21.47 0.00 21.47
July 659.83 21.45 0.00 21.45 0.00 21.45
August 648.33 21.43 0.33 21.43 0.00 21.43
September 651.17 21.46 0.83 21.47 0.00 21.47
October 694.67 21.50 2.33 21.51 0.00 21.51
November 692.67 21.49 8.33 21.49 8.33 21.48
December 737.67 21.52 14.83 21.52 14.83 21.51
             
Annual Sum or Average 8288.33 21.46 75.33 21.45 71.83 21.45
Minimum of Months 648.33 21.34 0.00 21.32 0.00 21.30
Maximum of Months 737.67 21.52 20.67 21.52 20.67 21.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.24 87.83 21.19 87.83 21.16
February 672.00 21.24 28.50 21.23 28.50 21.22
March 742.50 21.24 24.17 21.21 24.17 21.19
April 705.17 21.42 2.67 21.42 2.67 21.42
May 733.00 21.47 0.00 21.47 0.00 21.47
June 677.83 21.47 0.00 21.47 0.00 21.47
July 667.17 21.46 0.00 21.46 0.00 21.46
August 670.17 21.45 0.00 21.45 0.00 21.45
September 686.50 21.47 0.00 21.47 0.00 21.47
October 728.83 21.48 0.00 21.48 0.00 21.48
November 720.00 21.37 30.67 21.35 30.67 21.34
December 744.00 21.28 72.67 21.25 72.67 21.23
             
Annual Sum or Average 8491.17 21.38 246.50 21.37 246.50 21.35
Minimum of Months 667.17 21.24 0.00 21.19 0.00 21.16
Maximum of Months 744.00 21.48 87.83 21.48 87.83 21.48



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.12 56.33 21.11 56.33 21.10
February 672.00 21.16 25.83 21.16 25.83 21.16
March 744.00 21.17 1.50 21.17 1.50 21.17
April 720.00 21.26 0.00 21.26 0.00 21.26
May 744.00 21.29 0.00 21.29 0.00 21.29
June 720.00 21.34 0.00 21.34 0.00 21.34
July 744.00 21.40 0.00 21.40 0.00 21.40
August 744.00 21.37 0.00 21.37 0.00 21.37
September 720.00 21.30 0.00 21.30 0.00 21.30
October 744.00 21.29 0.00 21.29 0.00 21.29
November 720.00 21.17 66.00 21.17 66.00 21.16
December 744.00 21.13 83.50 21.12 83.50 21.12
             
Annual Sum or Average 8760.00 21.25 233.17 21.25 233.17 21.24
Minimum of Months 672.00 21.12 0.00 21.11 0.00 21.10
Maximum of Months 744.00 21.40 83.50 21.40 83.50 21.40



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 743.83 21.56 19.50 21.55 19.50 21.54
February 672.00 21.46 9.67 21.45 9.67 21.44
March 740.67 21.43 20.50 21.40 20.50 21.38
April 716.17 21.62 0.00 21.62 0.00 21.62
May 741.00 21.56 0.00 21.56 0.00 21.56
June 715.67 21.61 0.00 21.61 0.00 21.61
July 674.00 21.54 0.00 21.54 0.00 21.54
August 627.00 21.41 0.00 21.41 0.00 21.41
September 667.50 21.52 0.00 21.52 0.00 21.52
October 708.67 21.56 0.00 21.56 0.00 21.56
November 718.33 21.59 8.67 21.58 8.67 21.57
December 744.00 21.58 18.00 21.56 18.00 21.55
             
Annual Sum or Average 8468.83 21.54 76.33 21.53 76.33 21.53
Minimum of Months 627.00 21.41 0.00 21.40 0.00 21.38
Maximum of Months 744.00 21.62 20.50 21.62 20.50 21.62



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.23 55.83 21.21 55.83 21.20
February 672.00 21.23 23.50 21.22 23.50 21.21
March 744.00 21.28 30.33 21.25 30.33 21.23
April 719.17 21.54 0.83 21.54 0.83 21.54
May 743.67 21.54 0.00 21.54 0.00 21.54
June 714.67 21.61 0.00 21.61 0.00 21.61
July 691.00 21.59 0.00 21.59 0.00 21.59
August 689.83 21.58 0.00 21.58 0.00 21.58
September 717.33 21.57 0.00 21.57 0.00 21.57
October 744.00 21.55 0.00 21.55 0.00 21.55
November 720.00 21.30 35.00 21.29 35.00 21.29
December 744.00 21.24 56.67 21.23 56.67 21.22
             
Annual Sum or Average 8643.67 21.44 202.17 21.43 202.17 21.42
Minimum of Months 672.00 21.23 0.00 21.21 0.00 21.20
Maximum of Months 744.00 21.61 56.67 21.61 56.67 21.61



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 22.06 0.00 22.06 0.00 22.06
February 672.00 22.08 0.00 22.08 0.00 22.08
March 744.00 21.87 0.00 21.87 0.00 21.87
April 720.00 22.25 0.00 22.25 0.00 22.25
May 744.00 22.30 0.00 22.30 0.00 22.30
June 720.00 22.57 13.83 22.57 13.83 22.58
July 744.00 22.90 74.33 22.91 74.33 22.91
August 742.17 23.01 96.83 23.01 96.83 23.02
September 715.17 22.83 26.67 22.83 26.67 22.83
October 705.50 22.97 31.50 22.98 30.50 22.99
November 720.00 22.42 0.00 22.42 0.00 22.42
December 744.00 22.30 0.00 22.30 0.00 22.30
             
Annual Sum or Average 8714.83 22.46 243.17 22.48 242.17 22.49
Minimum of Months 672.00 21.87 0.00 21.87 0.00 21.87
Maximum of Months 744.00 23.01 96.83 23.01 96.83 23.02



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 729.17 21.42 69.00 21.38 69.00 21.35
February 656.17 21.31 38.00 21.29 38.00 21.26
March 723.17 21.28 48.67 21.24 48.50 21.20
April 674.50 21.43 6.33 21.43 6.17 21.42
May 714.50 21.44 0.00 21.44 0.00 21.44
June 662.00 21.43 0.00 21.43 0.00 21.43
July 642.50 21.40 6.17 21.42 0.00 21.42
August 631.50 21.37 18.00 21.42 3.00 21.42
September 638.33 21.41 8.83 21.43 2.33 21.44
October 686.83 21.45 5.50 21.47 0.17 21.47
November 690.67 21.44 32.17 21.42 32.17 21.41
December 735.17 21.46 69.50 21.43 69.50 21.40
             
Annual Sum or Average 8184.50 21.40 302.17 21.40 268.83 21.38
Minimum of Months 631.50 21.28 0.00 21.24 0.00 21.20
Maximum of Months 735.17 21.46 69.50 21.47 69.50 21.47



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.15 164.67 21.09 164.67 21.05
February 672.00 21.15 67.33 21.12 67.33 21.08
March 741.67 21.18 69.67 21.13 69.67 21.09
April 696.33 21.39 9.33 21.39 9.33 21.38
May 721.50 21.43 0.00 21.43 0.00 21.43
June 664.33 21.43 0.00 21.43 0.00 21.43
July 651.33 21.42 3.83 21.43 0.00 21.43
August 655.17 21.41 5.33 21.42 3.33 21.42
September 677.00 21.44 5.33 21.43 5.33 21.43
October 725.50 21.43 8.00 21.42 7.67 21.42
November 719.67 21.28 79.00 21.26 79.00 21.24
December 744.00 21.18 182.67 21.13 182.67 21.10
             
Annual Sum or Average 8412.50 21.32 595.17 21.29 589.00 21.27
Minimum of Months 651.33 21.15 0.00 21.09 0.00 21.05
Maximum of Months 744.00 21.44 182.67 21.43 182.67 21.43



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 668.83 21.46 5.83 21.46 2.33 21.46
February 628.67 21.41 3.50 21.41 3.50 21.41
March 698.33 21.35 19.33 21.33 19.33 21.31
April 682.50 21.49 0.00 21.49 0.00 21.49
May 744.00 21.47 0.00 21.47 0.00 21.47
June 720.00 21.51 0.00 21.51 0.00 21.51
July 716.33 21.55 0.00 21.55 0.00 21.55
August 655.33 21.42 0.00 21.42 0.00 21.42
September 618.33 21.36 2.33 21.36 0.00 21.36
October 651.00 21.41 11.33 21.45 0.00 21.45
November 648.83 21.48 6.00 21.49 3.50 21.49
December 674.67 21.49 5.50 21.50 3.50 21.49
             
Annual Sum or Average 8106.83 21.45 53.83 21.45 32.17 21.45
Minimum of Months 618.33 21.35 0.00 21.33 0.00 21.31
Maximum of Months 744.00 21.55 19.33 21.55 19.33 21.55



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 233.67 23.24 255.33 23.61 13.83 23.62
February 156.50 23.30 301.33 23.72 11.83 23.73
March 114.83 23.05 393.67 23.71 1.50 23.71
April 27.00 23.64 591.67 23.89 14.50 23.89
May 23.67 23.86 650.67 23.91 20.50 23.91
June 89.83 23.99 705.33 23.91 89.50 23.92
July 212.67 24.00 744.00 23.94 212.67 23.95
August 276.83 24.00 743.83 23.93 276.83 23.95
September 172.50 24.00 707.17 23.91 172.50 23.92
October 92.67 23.77 549.00 23.89 65.17 23.90
November 145.33 23.45 330.17 23.78 19.83 23.79
December 245.17 23.33 179.00 23.59 0.00 23.59
             
Annual Sum or Average 1790.67 23.62 6151.17 23.85 898.67 23.86
Minimum of Months 23.67 23.05 179.00 23.59 0.00 23.59
Maximum of Months 276.83 24.00 744.00 23.94 276.83 23.95



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 94.83 23.29 391.50 23.81 6.17 23.81
February 43.33 23.50 438.33 23.88 9.83 23.88
March 24.00 23.06 556.50 23.88 0.00 23.88
April 11.00 24.00 666.00 23.93 11.00 23.93
May 9.00 24.00 719.67 23.94 9.00 23.94
June 74.33 24.00 717.50 23.95 74.33 23.96
July 197.67 24.00 744.00 23.97 197.67 23.98
August 262.17 24.00 744.00 23.96 262.17 23.97
September 149.00 24.00 718.00 23.94 149.00 23.95
October 62.17 23.96 609.50 23.94 58.33 23.94
November 55.17 23.62 456.00 23.89 14.33 23.89
December 81.00 23.38 293.00 23.82 0.00 23.82
             
Annual Sum or Average 1063.67 23.82 7054.00 23.92 791.83 23.93
Minimum of Months 9.00 23.06 293.00 23.81 0.00 23.81
Maximum of Months 262.17 24.00 744.00 23.97 262.17 23.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 533.17 23.92 680.67 23.89 515.00 23.92
February 472.50 23.99 640.50 23.90 471.00 23.93
March 537.17 23.94 710.00 23.88 526.17 23.91
April 522.33 23.99 713.33 23.90 522.33 23.93
May 544.17 23.99 743.17 23.90 544.17 23.93
June 545.83 23.99 720.00 23.93 545.83 23.95
July 573.17 23.99 744.00 23.94 573.17 23.96
August 575.50 23.99 744.00 23.94 575.50 23.96
September 545.00 23.99 720.00 23.93 545.00 23.95
October 542.83 23.99 738.83 23.93 542.83 23.94
November 508.33 23.99 686.83 23.91 507.00 23.93
December 515.33 23.97 673.17 23.92 510.17 23.94
             
Annual Sum or Average 6415.33 23.98 8514.50 23.91 6378.17 23.94
Minimum of Months 472.50 23.92 640.50 23.88 471.00 23.91
Maximum of Months 575.50 23.99 744.00 23.94 575.50 23.96



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.82 2.67 21.82 2.67 21.81
February 672.00 21.77 0.00 21.77 0.00 21.77
March 744.00 21.70 0.00 21.70 0.00 21.70
April 720.00 22.21 0.00 22.21 0.00 22.21
May 744.00 22.22 0.00 22.22 0.00 22.22
June 697.33 22.60 0.00 22.60 0.00 22.60
July 599.50 22.91 5.50 22.92 0.00 22.92
August 519.00 22.94 17.67 22.97 0.00 22.97
September 652.50 22.71 3.17 22.72 0.00 22.72
October 635.00 22.70 13.67 22.73 0.00 22.73
November 720.00 22.08 0.00 22.08 0.00 22.08
December 744.00 21.92 0.00 21.92 0.00 21.92
             
Annual Sum or Average 8191.33 22.27 42.67 22.27 2.67 22.27
Minimum of Months 519.00 21.70 0.00 21.70 0.00 21.70
Maximum of Months 744.00 22.94 17.67 22.97 2.67 22.97



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.48598 38.17317 0.20222 6.08645
February 672.00000 22.95808 42.07694 0.08766 5.36267
March 744.00000 22.73806 46.15037 0.05740 5.20949
April 720.00000 22.63522 51.11327 0.06231 5.25888
May 744.00000 22.63738 50.72144 -0.9869 25.78242
June 720.00000 22.52214 57.88516 -0.9818 25.55594
July 744.00000 22.85621 60.24725 -0.8416 20.18103
August 744.00000 22.96034 60.71521 -0.8003 18.72924
September 720.00000 23.30972 56.36864 -0.6999 15.58361
October 744.00000 23.54639 45.50496 0.26937 6.74597
November 720.00000 23.63444 39.51348 0.25068 6.54268
December 744.00000 23.53280 33.19185 0.17987 5.91711
           
Annual Sum or Average 8760.00000 23.06943 48.49425 -0.2688 12.29203
Minimum of Months 672.00000 22.52214 33.19185 -0.9869 5.20949
Maximum of Months 744.00000 23.63444 60.71521 0.26937 25.78242



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.07667 40.09168 -0.0451 7.07455
February 672.00000 21.83650 43.69658 -0.0989 6.85888
March 744.00000 21.58432 47.96036 -0.1487 6.91080
April 720.00000 21.79061 52.41771 -0.0468 6.05305
May 744.00000 21.45422 52.96948 -1.2636 38.97719
June 720.00000 21.68965 59.58158 -1.1225 32.06405
July 744.00000 22.14350 61.92473 -0.9294 23.76424
August 744.00000 22.50026 61.64625 -0.7944 19.21279
September 720.00000 22.51316 58.02624 -0.8109 20.85414
October 744.00000 22.63514 46.95589 0.16802 7.16114
November 720.00000 22.21589 41.63497 0.01007 6.79308
December 744.00000 22.19966 34.66517 -0.0395 7.04646
           
Annual Sum or Average 8760.00000 22.05509 50.15326 -0.4288 15.28641
Minimum of Months 672.00000 21.45422 34.66517 -1.2636 6.05305
Maximum of Months 744.00000 22.63514 61.92473 0.16802 38.97719



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.68114 40.44685 0.05608 5.56307
February 672.00000 22.64702 43.48417 0.06372 5.46791
March 744.00000 22.48639 47.39413 0.04775 5.54584
April 720.00000 22.82159 51.21724 0.16299 6.03545
May 744.00000 22.76437 51.01775 -0.8681 21.59692
June 720.00000 22.98345 57.13720 -0.7446 17.34350
July 744.00000 23.23334 59.81430 -0.6296 13.81676
August 744.00000 23.32298 60.34091 -0.5910 12.76459
September 720.00000 23.24705 57.28530 -0.6414 14.11180
October 744.00000 23.26482 46.90996 0.25689 6.79668
November 720.00000 22.93130 41.74783 0.12957 5.71557
December 744.00000 22.84190 35.18331 0.06238 5.37735
           
Annual Sum or Average 8760.00000 22.93715 49.35207 -0.2264 10.03997
Minimum of Months 672.00000 22.48639 35.18331 -0.8681 5.37735
Maximum of Months 744.00000 23.32298 60.34091 0.25689 21.59692



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.82151 35.89769 0.67298 17.55485
February 672.00000 22.83479 38.67136 0.69051 17.95143
March 744.00000 22.80138 42.41682 0.70819 18.49904
April 720.00000 22.82457 47.06796 0.76279 20.08074
May 744.00000 22.83775 46.59049 0.02414 10.81887
June 720.00000 22.84236 53.34744 0.08959 10.91340
July 744.00000 22.85264 56.76363 0.13250 10.83525
August 744.00000 22.84593 57.59746 0.14049 11.00664
September 720.00000 22.84844 54.27943 0.09777 10.81342
October 744.00000 22.86726 43.62235 0.76612 20.19342
November 720.00000 22.87124 37.54215 0.70323 18.32482
December 744.00000 22.85545 30.77745 0.64903 16.75282
           
Annual Sum or Average 8760.00000 22.84195 45.40699 0.45160 15.29342
Minimum of Months 672.00000 22.80138 30.77745 0.02414 10.81342
Maximum of Months 744.00000 22.87124 57.59746 0.76612 20.19342



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.22587 43.63590 0.29460 7.86370
February 672.00000 22.99885 47.02569 0.23952 7.21457
March 744.00000 22.72776 51.04035 0.18439 6.86807
April 720.00000 22.93838 55.19308 0.27896 7.20608
May 744.00000 22.63219 55.59912 -0.8179 19.93545
June 720.00000 22.80484 61.95679 -0.6994 16.05472
July 744.00000 23.06330 64.59792 -0.5664 12.27067
August 744.00000 23.32667 64.55751 -0.4545 9.75573
September 720.00000 23.41587 60.93692 -0.4421 9.95627
October 744.00000 23.51231 50.41707 0.43983 9.75537
November 720.00000 23.36892 45.05131 0.34593 8.22980
December 744.00000 23.34909 38.56966 0.29918 7.68959
           
Annual Sum or Average 8760.00000 23.11441 53.23782 -0.0768 10.25674
Minimum of Months 672.00000 22.63219 38.56966 -0.8179 6.86807
Maximum of Months 744.00000 23.51231 64.59792 0.43983 19.93545



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.30557 42.77140 0.23980 6.64480
February 672.00000 23.22036 45.76794 0.23272 6.51182
March 744.00000 23.04145 49.63763 0.20967 6.43831
April 720.00000 23.22684 53.68262 0.29128 7.20675
May 744.00000 23.16658 53.48738 -0.6983 16.04828
June 720.00000 23.31400 59.58909 -0.5946 13.15113
July 744.00000 23.44606 62.43018 -0.5164 11.15171
August 744.00000 23.51519 62.92590 -0.4829 10.32067
September 720.00000 23.53713 59.66059 -0.5000 10.64765
October 744.00000 23.62091 49.24741 0.38234 8.35555
November 720.00000 23.47242 44.10042 0.29503 7.12970
December 744.00000 23.44471 37.68450 0.24249 6.46905
           
Annual Sum or Average 8760.00000 23.36010 51.77041 -0.0769 9.19087
Minimum of Months 672.00000 23.04145 37.68450 -0.6983 6.43831
Maximum of Months 744.00000 23.62091 62.92590 0.38234 16.04828



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.50707 46.03617 -0.2467 7.15229
February 672.00000 21.42472 49.14960 -0.2497 7.02079
March 744.00000 21.38631 52.60524 -0.2445 7.03184
April 720.00000 21.56107 55.35057 -0.1368 6.20329
May 744.00000 21.52465 55.45921 -1.2850 40.35749
June 720.00000 21.58422 58.70980 -1.2071 36.60678
July 744.00000 21.66047 58.99494 -1.1397 33.63194
August 744.00000 21.67270 59.29956 -1.1285 33.22071
September 720.00000 21.64290 58.47634 -1.1664 34.97118
October 744.00000 21.62305 50.39704 -0.1190 6.18675
November 720.00000 21.56163 47.11947 -0.2029 6.76926
December 744.00000 21.53963 40.57729 -0.2604 7.30769
           
Annual Sum or Average 8760.00000 21.55813 52.68583 -0.6179 18.94424
Minimum of Months 672.00000 21.38631 40.57729 -1.2850 6.18675
Maximum of Months 744.00000 21.67270 59.29956 -0.1190 40.35749



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.23608 46.98691 -0.3543 8.15536
February 672.00000 21.24273 49.84331 -0.3233 7.60224
March 744.00000 21.24158 53.31222 -0.2996 7.38441
April 720.00000 21.46361 56.11716 -0.1734 6.26269
May 744.00000 21.49469 55.62981 -1.2992 40.97242
June 720.00000 21.57545 58.62313 -1.2095 36.68674
July 744.00000 21.64989 59.06290 -1.1457 33.84671
August 744.00000 21.63690 60.07305 -1.1538 34.21087
September 720.00000 21.55852 59.91665 -1.2191 37.12573
October 744.00000 21.51468 51.41920 -0.1723 6.29498
November 720.00000 21.36516 48.17791 -0.2888 7.33910
December 744.00000 21.27741 41.33423 -0.3705 8.34087
           
Annual Sum or Average 8760.00000 21.43909 53.37815 -0.6697 19.59086
Minimum of Months 672.00000 21.23608 41.33423 -1.2992 6.26269
Maximum of Months 744.00000 21.64989 60.07305 -0.1723 40.97242



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.12347 45.34343 -0.3894 8.35079
February 672.00000 21.16287 48.28184 -0.3552 7.76140
March 744.00000 21.17434 51.82567 -0.3295 7.38288
April 720.00000 21.25506 55.33991 -0.2701 6.63532
May 744.00000 21.28805 54.61151 -1.4309 47.21501
June 720.00000 21.33904 58.45233 -1.3686 43.94557
July 744.00000 21.39862 60.34329 -1.3276 41.87550
August 744.00000 21.37049 61.63140 -1.3382 42.39966
September 720.00000 21.29885 60.19030 -1.3869 44.92413
October 744.00000 21.29062 50.73670 -0.2755 6.78797
November 720.00000 21.17012 46.85209 -0.3577 7.85693
December 744.00000 21.12644 39.79105 -0.4198 8.84376
           
Annual Sum or Average 8760.00000 21.25037 52.79371 -0.7734 22.92247
Minimum of Months 672.00000 21.12347 39.79105 -1.4309 6.63532
Maximum of Months 744.00000 21.39862 61.63140 -0.2701 47.21501



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.56077 45.88401 -0.2316 6.96030
February 672.00000 21.45527 49.10906 -0.2473 6.98615
March 744.00000 21.43581 52.35260 -0.2349 6.97037
April 720.00000 21.62896 55.13460 -0.1277 6.20866
May 744.00000 21.56967 55.25696 -1.2847 40.34783
June 720.00000 21.62004 58.96400 -1.2124 36.91779
July 744.00000 21.71251 59.27641 -1.1340 33.46630
August 744.00000 21.71603 59.42735 -1.1200 32.90767
September 720.00000 21.65380 59.10959 -1.1795 35.58209
October 744.00000 21.64721 50.53382 -0.1168 6.13736
November 720.00000 21.58978 47.18262 -0.2012 6.67287
December 744.00000 21.57568 40.53064 -0.2528 7.15116
           
Annual Sum or Average 8760.00000 21.59801 52.73395 -0.6142 18.92938
Minimum of Months 672.00000 21.43581 40.53064 -1.2847 6.13736
Maximum of Months 744.00000 21.71603 59.42735 -0.1168 40.34783



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.22657 46.86205 -0.3510 7.93172
February 672.00000 21.22954 49.91708 -0.3294 7.53570
March 744.00000 21.28171 53.10147 -0.2917 7.26754
April 720.00000 21.54392 55.73357 -0.1630 6.20430
May 744.00000 21.54004 55.42419 -1.2990 40.94419
June 720.00000 21.61869 58.89917 -1.2126 36.88994
July 744.00000 21.71236 59.39483 -1.1367 33.54506
August 744.00000 21.70721 60.13005 -1.1379 33.60690
September 720.00000 21.57848 60.32949 -1.2319 37.70544
October 744.00000 21.55180 51.46652 -0.1682 6.16834
November 720.00000 21.30262 48.38880 -0.3052 7.27352
December 744.00000 21.23899 41.44774 -0.3767 8.20812
           
Annual Sum or Average 8760.00000 21.46235 53.42696 -0.6690 19.50965
Minimum of Months 672.00000 21.22657 41.44774 -1.2990 6.16834
Maximum of Months 744.00000 21.71236 60.32949 -0.1630 40.94419



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.45704 46.94413 -0.2840 7.71176
February 672.00000 21.36079 50.20487 -0.2892 7.60728
March 744.00000 21.33493 53.71902 -0.2764 7.57164
April 720.00000 21.55057 56.50513 -0.1470 6.44666
May 744.00000 21.51204 56.58955 -1.3039 41.50685
June 720.00000 21.58461 60.03936 -1.2107 37.00921
July 744.00000 21.66445 60.43245 -1.1345 33.61587
August 744.00000 21.66835 60.95299 -1.1275 33.38521
September 720.00000 21.63003 60.35829 -1.1762 35.63074
October 744.00000 21.59414 51.67684 -0.1370 6.43020
November 720.00000 21.51411 48.24525 -0.2373 7.22388
December 744.00000 21.48322 41.33904 -0.3023 7.93127
           
Annual Sum or Average 8760.00000 21.53047 53.92179 -0.6377 19.41111
Minimum of Months 672.00000 21.33493 41.33904 -1.3039 6.43020
Maximum of Months 744.00000 21.66835 60.95299 -0.1370 41.50685



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.14758 47.97869 -0.4057 9.02750
February 672.00000 21.15447 50.95379 -0.3724 8.39334
March 744.00000 21.18185 54.45109 -0.3362 8.00425
April 720.00000 21.45524 57.30472 -0.1853 6.50989
May 744.00000 21.48454 56.77526 -1.3178 42.09725
June 720.00000 21.57835 59.98799 -1.2123 37.04168
July 744.00000 21.65790 60.53957 -1.1394 33.77715
August 744.00000 21.64050 61.83094 -1.1512 34.29880
September 720.00000 21.54844 62.01957 -1.2303 37.82974
October 744.00000 21.47620 52.84638 -0.1953 6.59165
November 720.00000 21.28524 49.34389 -0.3367 8.03435
December 744.00000 21.17721 42.20501 -0.4285 9.34308
           
Annual Sum or Average 8760.00000 21.40023 54.68994 -0.6947 20.15017
Minimum of Months 672.00000 21.14758 42.20501 -1.3178 6.50989
Maximum of Months 744.00000 21.65790 62.01957 -0.1853 42.09725



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.64490 45.59438 -0.1707 6.86099
February 672.00000 21.53258 48.90124 -0.2087 6.92677
March 744.00000 21.47154 52.25711 -0.2250 7.08908
April 720.00000 21.58241 55.49957 -0.1568 6.43574
May 744.00000 21.46509 56.26002 -1.3670 44.38859
June 720.00000 21.50978 60.63086 -1.2979 40.86883
July 744.00000 21.61716 61.55072 -1.2197 37.29023
August 744.00000 21.64925 60.89919 -1.1836 35.79055
September 720.00000 21.63537 58.54641 -1.1936 36.45558
October 744.00000 21.65344 50.14881 -0.1075 6.35731
November 720.00000 21.66570 46.60718 -0.1520 6.70239
December 744.00000 21.66357 40.35100 -0.1872 7.03686
           
Annual Sum or Average 8760.00000 21.59130 53.11412 -0.6250 20.26588
Minimum of Months 672.00000 21.46509 40.35100 -1.3670 6.35731
Maximum of Months 744.00000 21.66570 61.55072 -0.1075 44.38859



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.64944 43.28469 0.35063 7.97602
February 672.00000 23.69475 45.67883 0.38171 8.33480
March 744.00000 23.69265 49.16787 0.40765 8.74301
April 720.00000 23.82042 52.91729 0.48982 10.19540
May 744.00000 23.84679 52.31803 -0.3797 8.19813
June 720.00000 23.89182 58.19711 -0.2939 6.93640
July 744.00000 23.92503 61.15163 -0.2424 6.28615
August 744.00000 23.91042 61.98971 -0.2458 6.32932
September 720.00000 23.87381 59.22262 -0.3020 7.05695
October 744.00000 23.85455 49.40945 0.49128 10.33004
November 720.00000 23.73500 44.51275 0.39108 8.52291
December 744.00000 23.68827 38.36864 0.32728 7.52987
           
Annual Sum or Average 8760.00000 23.79909 51.37230 0.11292 8.03258
Minimum of Months 672.00000 23.64944 38.36864 -0.3797 6.28615
Maximum of Months 744.00000 23.92503 61.98971 0.49128 10.33004



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.78595 42.31945 0.41723 8.95025
February 672.00000 23.82456 44.68063 0.44730 9.40692
March 744.00000 23.82947 48.12843 0.47563 9.91574
April 720.00000 23.90930 52.00904 0.54434 11.33044
May 744.00000 23.92563 51.43947 -0.3035 7.03731
June 720.00000 23.94794 57.42194 -0.2286 6.17183
July 744.00000 23.96454 60.47105 -0.1860 5.75682
August 744.00000 23.95309 61.31068 -0.1897 5.78794
September 720.00000 23.93038 58.45877 -0.2389 6.29531
October 744.00000 23.91607 48.68499 0.53499 11.23229
November 720.00000 23.84708 43.60041 0.45045 9.51270
December 744.00000 23.81267 37.44519 0.39035 8.41762
           
Annual Sum or Average 8760.00000 23.88750 50.51929 0.17439 8.30887
Minimum of Months 672.00000 23.78595 37.44519 -0.3035 5.75682
Maximum of Months 744.00000 23.96454 61.31068 0.54434 11.33044



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.74795 40.94966 1.05206 31.06765
February 672.00000 23.79177 43.35266 1.07548 31.71967
March 744.00000 23.76812 46.73268 1.09753 32.85577
April 720.00000 23.83115 50.84039 1.17513 35.98366
May 744.00000 23.83793 50.41058 0.58744 17.01712
June 720.00000 23.87673 56.42925 0.67278 18.78320
July 744.00000 23.90287 59.46170 0.73341 20.27581
August 744.00000 23.90520 60.18947 0.73918 20.39444
September 720.00000 23.88249 57.26634 0.67775 18.81927
October 744.00000 23.87074 47.67274 1.17730 35.96255
November 720.00000 23.80113 42.35356 1.08331 32.05802
December 744.00000 23.77982 36.19594 1.02751 29.83465
           
Annual Sum or Average 8760.00000 23.83317 49.34399 0.92392 27.03321
Minimum of Months 672.00000 23.74795 36.19594 0.58744 17.01712
Maximum of Months 744.00000 23.90520 60.18947 1.17730 35.98366



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.68839 39.58386 -0.2327 6.60258
February 672.00000 21.70860 42.73063 -0.2100 6.07924
March 744.00000 21.56831 46.76570 -0.2201 6.29183
April 720.00000 21.96398 50.68192 -0.0963 5.44022
May 744.00000 22.12953 49.85743 -1.1486 32.95316
June 720.00000 22.51526 55.70422 -0.9751 25.25097
July 744.00000 22.80775 58.62929 -0.8520 20.41314
August 744.00000 22.78968 59.65173 -0.8524 20.41579
September 720.00000 22.58182 56.63325 -0.9459 24.06048
October 744.00000 22.67312 45.60723 0.05339 5.43499
November 720.00000 22.00940 40.87501 -0.1451 5.67141
December 744.00000 21.84124 33.97701 -0.2297 6.32546
           
Annual Sum or Average 8760.00000 22.19286 48.40967 -0.4896 13.79303
Minimum of Months 672.00000 21.56831 33.97701 -1.1486 5.43499
Maximum of Months 744.00000 22.80775 59.65173 0.05339 32.95316



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.06414 42.46943 -0.1435 5.85063
February 672.00000 22.07722 45.59043 -0.1229 5.46097
March 744.00000 21.87216 49.60706 -0.1485 5.74876
April 720.00000 22.24623 53.54393 -0.0299 5.26641
May 744.00000 22.30252 53.04588 -1.1022 30.81917
June 720.00000 22.56764 59.20531 -0.9688 24.99616
July 744.00000 22.89629 61.80994 -0.8335 19.74786
August 744.00000 23.00955 62.32631 -0.7898 18.20750
September 720.00000 22.83868 59.42006 -0.8699 21.11729
October 744.00000 23.00459 48.45021 0.13231 5.69164
November 720.00000 22.42297 43.69324 -0.0467 5.23506
December 744.00000 22.30443 36.85992 -0.1196 5.47739
           
Annual Sum or Average 8760.00000 22.46984 51.35353 -0.4221 12.84708
Minimum of Months 672.00000 21.87216 36.85992 -1.1022 5.23506
Maximum of Months 744.00000 23.00955 62.32631 0.13231 30.81917



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.81919 40.45628 -0.1809 6.25943
February 672.00000 21.77083 43.71025 -0.1737 5.96435
March 744.00000 21.70479 47.54012 -0.1670 6.06605
April 720.00000 22.21077 51.12887 -0.0117 5.42369
May 744.00000 22.22493 50.71799 -1.0834 30.19864
June 720.00000 22.61888 56.49373 -0.9024 22.60622
July 744.00000 23.00339 58.85997 -0.7455 16.92619
August 744.00000 23.08925 59.44252 -0.7109 15.84726
September 720.00000 22.78875 57.01419 -0.8374 20.22123
October 744.00000 22.83625 46.23047 0.12118 5.88713
November 720.00000 22.08107 41.83348 -0.1046 5.60411
December 744.00000 21.92339 35.03108 -0.1882 6.11000
           
Annual Sum or Average 8760.00000 22.34303 49.05377 -0.4168 12.29807
Minimum of Months 672.00000 21.70479 35.03108 -1.0834 5.42369
Maximum of Months 744.00000 23.08925 59.44252 0.12118 30.19864



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.84032 38.66090 -0.1908 6.31457
February 672.00000 21.87966 41.73556 -0.1638 5.77808
March 744.00000 21.74243 45.75456 -0.1729 5.96035
April 720.00000 22.13389 49.62788 -0.0491 5.36394
May 744.00000 22.31835 48.75145 -1.0737 29.61876
June 720.00000 22.70100 54.53058 -0.8998 22.38375
July 744.00000 22.98463 57.38353 -0.7792 17.99443
August 744.00000 22.95920 58.39695 -0.7823 18.08647
September 720.00000 22.74247 55.50533 -0.8791 21.57644
October 744.00000 22.83173 44.56281 0.09883 5.64543
November 720.00000 22.16902 39.91078 -0.1011 5.50950
December 744.00000 21.99928 33.09056 -0.1865 6.01968
           
Annual Sum or Average 8760.00000 22.36158 47.34372 -0.4333 12.56336
Minimum of Months 672.00000 21.74243 33.09056 -1.0737 5.36394
Maximum of Months 744.00000 22.98463 58.39695 0.09883 29.61876



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.377350E+11 85736.54 14-JAN-11:33 626.19 0.117040E+12 0.00 0.154775E+12 2.63 3.82 15-JAN-09:02 0.00 0.00
February 0.243946E+11 78386.10 01-FEB-11:50 557.57 0.747856E+11 0.00 0.991802E+11 2.59 3.79 01-FEB-09:02 0.00 0.00
March 0.241913E+11 80682.58 23-MAR-15:02 576.18 0.753369E+11 0.00 0.995282E+11 2.43 3.96 23-MAR-15:02 0.00 0.00
April 0.488796E+11 86823.93 26-APR-10:45 692.58 0.151196E+12 0.00 0.200076E+12 2.99 4.00 26-APR-18:03 0.00 0.00
May 0.520465E+11 86417.46 18-MAY-15:02 730.81 0.156713E+12 0.00 0.208760E+12 3.01 4.05 18-MAY-15:02 0.00 0.00
June 0.842378E+11 109045.63 29-JUN-18:03 719.17 0.270468E+12 0.00 0.354706E+12 3.12 4.32 27-JUN-18:03 0.00 0.00
July 0.143595E+12 136483.46 19-JUL-15:02 744.00 0.509930E+12 0.00 0.653525E+12 3.40 4.45 13-JUL-18:03 0.00 0.00
August 0.156853E+12 144554.20 18-AUG-15:03 744.00 0.569249E+12 0.00 0.726102E+12 3.50 4.48 24-AUG-18:03 0.00 0.00
September 0.106821E+12 165153.37 29-SEP-10:33 719.50 0.358074E+12 0.00 0.464895E+12 3.23 4.39 09-SEP-18:02 0.00 0.00
October 0.117332E+12 181196.94 16-OCT-11:00 742.17 0.400618E+12 0.00 0.517950E+12 3.26 4.45 05-OCT-18:02 0.00 0.00
November 0.402832E+11 93575.15 19-NOV-09:02 668.79 0.125063E+12 0.00 0.165346E+12 2.89 3.82 19-NOV-09:02 0.00 0.00
December 0.419471E+11 88881.68 05-DEC-09:02 638.56 0.132266E+12 0.00 0.174213E+12 2.69 3.89 05-DEC-19:02 0.00 0.00
                         
Annual Sum or Average 0.878316E+12     8159.51 0.294074E+13 0.00 0.381906E+13 2.98     0.00 0.00
Minimum of Months 0.241913E+11 78386.10   557.57 0.747856E+11 0.00 0.991802E+11 2.43 3.79   0.00 0.00
Maximum of Months 0.156853E+12 181196.94   744.00 0.569249E+12 0.00 0.726102E+12 3.50 4.48   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.121428E+12 0.00 556.59 181927.27 08-JAN-07:00 0.00 42.96 71.89 0.29 0.00 0.16 0.64 08-JAN-07:00
February 0.845217E+11 0.00 548.06 151955.47 04-FEB-06:00 0.00 39.02 72.28 0.21 0.00 0.12 0.54 04-FEB-06:00
March 0.121528E+12 0.00 600.96 185956.25 29-MAR-08:62 0.00 36.59 71.36 0.28 0.00 0.16 0.66 29-MAR-08:62
April 0.452232E+11 0.00 409.43 136896.41 01-APR-06:00 0.00 31.10 58.63 0.09 0.00 0.06 0.48 01-APR-06:00
May 0.393756E+11 0.00 372.85 116742.77 14-MAY-04:50 0.00 31.08 54.97 0.08 0.00 0.05 0.41 14-MAY-04:50
June 0.632708E+10 0.00 163.63 63382.46 13-JUN-04:00 0.00 33.83 44.83 0.01 0.00 0.01 0.22 13-JUN-04:00
July 0.420170E+09 0.00 40.96 33541.50 18-JUL-08:05 0.00 43.22 45.39 0.00 0.00 0.00 0.12 18-JUL-08:05
August 0.178425E+09 0.00 36.72 31740.51 29-AUG-18:05 0.00 51.70 53.21 0.00 0.00 0.00 0.11 29-AUG-18:05
September 0.301940E+10 0.00 103.35 59258.40 20-SEP-04:00 0.00 44.15 49.99 0.01 0.00 0.00 0.21 20-SEP-04:00
October 0.161750E+11 0.00 196.80 97168.53 29-OCT-06:00 0.00 42.05 53.02 0.03 0.00 0.02 0.34 29-OCT-06:00
November 0.693283E+11 0.00 510.26 144072.18 29-NOV-23:00 0.00 39.83 68.76 0.16 0.00 0.09 0.51 29-NOV-23:00
December 0.115281E+12 0.00 565.62 156372.34 23-DEC-06:00 0.00 43.33 72.55 0.27 0.00 0.15 0.55 23-DEC-06:00
                           
Annual Sum or Average 0.622805E+12 0.00 4105.21     0.00 39.94 59.68 0.12 0.00 0.07    
Minimum of Months 0.178425E+09 0.00 36.72 31740.51   0.00 31.08 44.83 0.00 0.00 0.00 0.11  
Maximum of Months 0.121528E+12 0.00 600.96 185956.25   0.00 51.70 72.55 0.29 0.00 0.16 0.66  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.572450E+11 0.00 284.67 0.571054E+11 0.00 0.00 0.00 0.00 208585.96 14-JAN-11:45 208585.96 14-JAN-11:45 0.00 0.00 0.00
February 0.316038E+11 0.00 229.89 0.308895E+11 0.00 0.00 0.00 0.00 196578.24 01-FEB-11:45 196578.24 01-FEB-11:45 0.00 0.00 0.00
March 0.353233E+11 0.00 211.83 0.346290E+11 0.00 0.00 0.00 0.00 183126.88 23-MAR-10:50 176357.25 11-MAR-11:45 0.00 0.00 0.00
April 0.843398E+11 0.00 358.47 0.827112E+11 0.00 0.00 0.00 0.00 251962.06 26-APR-10:45 207485.73 30-APR-10:45 0.00 0.00 0.00
May 0.901865E+11 0.00 436.58 0.891896E+11 0.00 0.00 0.00 0.00 161605.97 18-MAY-10:50 157042.39 04-MAY-12:00 0.00 0.00 0.00
June 0.168634E+12 0.00 614.92 0.146349E+12 0.00 0.00 0.00 0.00 312457.46 29-JUN-10:50 191271.96 29-JUN-10:50 0.00 0.00 0.00
July 0.346290E+12 0.00 735.08 0.224669E+12 0.00 0.00 0.00 0.00 381630.33 31-JUL-10:45 241095.37 19-JUL-10:45 0.00 0.00 0.00
August 0.390374E+12 0.00 736.67 0.234633E+12 0.00 0.00 0.00 0.00 409086.71 14-AUG-10:45 241002.03 14-AUG-10:45 0.00 0.00 0.00
September 0.229545E+12 0.00 675.00 0.176186E+12 0.00 0.00 0.00 0.00 373514.51 22-SEP-12:00 364902.33 29-SEP-10:50 0.00 0.00 0.00
October 0.260389E+12 0.00 619.33 0.209062E+12 0.00 0.00 0.00 0.00 384410.71 16-OCT-10:50 384410.71 16-OCT-10:50 0.00 0.00 0.00
November 0.593969E+11 0.00 341.61 0.587286E+11 0.00 0.00 0.00 0.00 213511.11 19-NOV-11:50 213511.11 19-NOV-11:50 0.00 0.00 0.00
December 0.661316E+11 0.00 294.67 0.661316E+11 0.00 0.00 0.00 0.00 192550.31 16-DEC-13:00 192550.31 16-DEC-13:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.181946E+13 0.00 5538.72 0.141028E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.316038E+11 0.00 211.83 0.308895E+11 0.00 0.00 0.00 0.00 161605.97   157042.39   0.00 0.00 0.00
Maximum of Months 0.390374E+12 0.00 736.67 0.234633E+12 0.00 0.00 0.00 0.00 409086.71   384410.71   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.113067E+11 0.00 275.67 0.111344E+11 0.00 0.00 0.00 0.00 35831.89 17-JAN-14:00 34701.69 18-JAN-13:00 0.00 0.00 0.00
February 0.624901E+10 0.00 211.33 0.601784E+10 0.00 0.00 0.00 0.00 34702.50 01-FEB-12:00 34702.50 01-FEB-12:00 0.00 0.00 0.00
March 0.724922E+10 0.00 192.33 0.662458E+10 0.00 0.00 0.00 0.00 38122.69 23-MAR-15:00 29771.76 11-MAR-13:00 0.00 0.00 0.00
April 0.170527E+11 0.00 332.17 0.156679E+11 0.00 0.00 0.00 0.00 45682.01 26-APR-11:00 37320.26 26-APR-13:00 0.00 0.00 0.00
May 0.176695E+11 0.00 414.50 0.169867E+11 0.00 0.00 0.00 0.00 33097.58 04-MAY-13:10 29927.15 04-MAY-12:00 0.00 0.00 0.00
June 0.354046E+11 0.00 609.17 0.276503E+11 0.00 0.00 0.00 0.00 50379.43 29-JUN-11:00 30610.28 29-JUN-11:00 0.00 0.00 0.00
July 0.697043E+11 0.00 736.00 0.417303E+11 0.00 0.00 0.00 0.00 59117.88 31-JUL-12:20 37187.60 19-JUL-10:55 0.00 0.00 0.00
August 0.780509E+11 0.00 737.50 0.433674E+11 0.00 0.00 0.00 0.00 59096.39 14-AUG-10:55 36192.18 18-AUG-12:00 0.00 0.00 0.00
September 0.472441E+11 0.00 667.50 0.329404E+11 0.00 0.00 0.00 0.00 61100.16 22-SEP-12:00 59337.85 29-SEP-13:00 0.00 0.00 0.00
October 0.510747E+11 0.00 612.50 0.388693E+11 0.00 0.00 0.00 0.00 61507.15 16-OCT-10:55 61507.15 16-OCT-10:55 0.00 0.00 0.00
November 0.116003E+11 0.00 320.50 0.113170E+11 0.00 0.00 0.00 0.00 37158.21 19-NOV-13:00 37158.21 19-NOV-13:00 0.00 0.00 0.00
December 0.131328E+11 0.00 279.83 0.131083E+11 0.00 0.00 0.00 0.00 34610.58 16-DEC-13:00 34610.58 16-DEC-13:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.365739E+12 0.00 5389.00 0.265414E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.624901E+10 0.00 192.33 0.601784E+10 0.00 0.00 0.00 0.00 33097.58   29771.76   0.00 0.00 0.00
Maximum of Months 0.780509E+11 0.00 737.50 0.433674E+11 0.00 0.00 0.00 0.00 61507.15   61507.15   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.167757E+10 0.00 381.65 0.105151E+10 0.00 0.00 0.00 0.00 11929.51 14-JAN-16:02 11929.51 14-JAN-16:02 0.00 0.00 0.00
February 0.152445E+10 0.00 302.75 0.101002E+10 0.00 0.00 0.00 0.00 11678.58 03-FEB-16:02 11678.58 03-FEB-16:02 0.00 0.00 0.00
March 0.160785E+10 0.00 308.88 0.968103E+09 0.00 0.00 0.00 0.00 11815.35 10-MAR-16:02 11815.35 10-MAR-16:02 0.00 0.00 0.00
April 0.340876E+10 0.00 511.20 0.196408E+10 0.00 0.00 0.00 0.00 11922.54 01-APR-15:01 11922.54 01-APR-15:01 0.00 0.00 0.00
May 0.310158E+10 0.00 519.81 0.170419E+10 0.00 0.00 0.00 0.00 11743.85 05-MAY-15:02 11407.46 17-MAY-15:02 0.00 0.00 0.00
June 0.460590E+10 0.00 571.79 0.248976E+10 0.00 0.00 0.00 0.00 12184.22 30-JUN-08:62 11463.31 15-JUN-15:02 0.00 0.00 0.00
July 0.685750E+10 0.00 644.47 0.381100E+10 0.00 0.00 0.00 0.00 13164.59 23-JUL-08:62 11942.11 19-JUL-15:02 0.00 0.00 0.00
August 0.719296E+10 0.00 660.36 0.399312E+10 0.00 0.00 0.00 0.00 13523.18 19-AUG-08:62 11814.34 18-AUG-15:02 0.00 0.00 0.00
September 0.552526E+10 0.00 616.13 0.304819E+10 0.00 0.00 0.00 0.00 13118.57 22-SEP-08:62 11300.79 08-SEP-15:02 0.00 0.00 0.00
October 0.513354E+10 0.00 611.16 0.349989E+10 0.00 0.00 0.00 0.00 13275.74 01-OCT-08:62 12326.07 16-OCT-15:02 0.00 0.00 0.00
November 0.234656E+10 0.00 465.74 0.146174E+10 0.00 0.00 0.00 0.00 12055.01 19-NOV-09:02 12055.01 19-NOV-09:02 0.00 0.00 0.00
December 0.198098E+10 0.00 409.04 0.159187E+10 0.00 0.00 0.00 0.00 11917.15 05-DEC-16:02 11917.15 05-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.449629E+11 0.00 6002.98 0.265935E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.152445E+10 0.00 302.75 0.968103E+09 0.00 0.00 0.00 0.00 11678.58   11300.79   0.00 0.00 0.00
Maximum of Months 0.719296E+10 0.00 660.36 0.399312E+10 0.00 0.00 0.00 0.00 13523.18   12326.07   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.396938E+09 0.00 158.36 0.225828E+09 0.00 0.00 0.00 0.00 11446.81 14-JAN-16:02 11446.81 14-JAN-16:02 0.00 0.00 0.00
February 0.558520E+09 0.00 169.35 0.344585E+09 0.00 0.00 0.00 0.00 11205.46 03-FEB-16:02 11205.46 03-FEB-16:02 0.00 0.00 0.00
March 0.853553E+09 0.00 199.85 0.496276E+09 0.00 0.00 0.00 0.00 11336.92 10-MAR-16:02 11336.92 10-MAR-16:02 0.00 0.00 0.00
April 0.261472E+10 0.00 452.02 0.146576E+10 0.00 0.00 0.00 0.00 11439.41 01-APR-15:01 11439.41 01-APR-15:01 0.00 0.00 0.00
May 0.292197E+10 0.00 508.92 0.161743E+10 0.00 0.00 0.00 0.00 11230.55 02-MAY-18:02 11018.60 17-MAY-15:02 0.00 0.00 0.00
June 0.465320E+10 0.00 567.29 0.257987E+10 0.00 0.00 0.00 0.00 11689.22 30-JUN-08:62 11029.10 15-JUN-15:02 0.00 0.00 0.00
July 0.674789E+10 0.00 631.84 0.381449E+10 0.00 0.00 0.00 0.00 12627.80 23-JUL-08:62 11345.50 19-JUL-15:02 0.00 0.00 0.00
August 0.645108E+10 0.00 625.90 0.351908E+10 0.00 0.00 0.00 0.00 12946.53 19-AUG-08:62 11303.98 17-AUG-15:02 0.00 0.00 0.00
September 0.424767E+10 0.00 570.03 0.217541E+10 0.00 0.00 0.00 0.00 12915.19 21-SEP-15:02 10948.36 11-SEP-15:02 0.00 0.00 0.00
October 0.342109E+10 0.00 528.16 0.213797E+10 0.00 0.00 0.00 0.00 12772.75 05-OCT-15:02 11827.44 16-OCT-15:02 0.00 0.00 0.00
November 0.735816E+09 0.00 286.83 0.389047E+09 0.00 0.00 0.00 0.00 11176.40 10-NOV-16:02 11098.19 27-NOV-16:01 0.00 0.00 0.00
December 0.429877E+09 0.00 188.15 0.348158E+09 0.00 0.00 0.00 0.00 11434.15 05-DEC-16:02 11434.15 05-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.340323E+11 0.00 4886.70 0.191139E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.396938E+09 0.00 158.36 0.225828E+09 0.00 0.00 0.00 0.00 11176.40   10948.36   0.00 0.00 0.00
Maximum of Months 0.674789E+10 0.00 631.84 0.381449E+10 0.00 0.00 0.00 0.00 12946.53   11827.44   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.211135E+11 0.00 385.68 0.179172E+11 0.00 0.00 0.00 0.00 39662.68 14-JAN-12:40 39662.68 14-JAN-12:40 0.00 0.00 0.00
February 0.131170E+11 0.00 269.04 0.111413E+11 0.00 0.00 0.00 0.00 35465.32 02-FEB-12:40 35465.32 02-FEB-12:40 0.00 0.00 0.00
March 0.649196E+10 0.00 203.79 0.409571E+10 0.00 0.00 0.00 0.00 26740.55 11-MAR-13:30 26740.55 11-MAR-13:30 0.00 0.00 0.00
April 0.491772E+10 0.00 211.00 0.191348E+10 0.00 0.00 0.00 0.00 18554.34 08-APR-12:40 10747.00 08-APR-13:10 0.00 0.00 0.00
May 0.494295E+09 0.00 29.53 0.141755E+09 0.00 0.00 0.00 0.00 9160.34 04-MAY-12:30 3405.57 03-MAY-13:00 0.00 0.00 0.00
June 62706442.41 0.00 14.00 7747375.92 0.00 0.00 0.00 0.00 3981.21 29-JUN-17:20 764.47 29-JUN-17:13 0.00 0.00 0.00
July 0.348987E+10 0.00 186.44 0.930989E+09 0.00 0.00 0.00 0.00 15212.93 31-JUL-12:40 6116.17 31-JUL-13:00 0.00 0.00 0.00
August 0.106381E+11 0.00 361.39 0.383658E+10 0.00 0.00 0.00 0.00 20269.30 18-AUG-12:00 10040.55 30-AUG-13:00 0.00 0.00 0.00
September 0.146799E+11 0.00 358.74 0.835094E+10 0.00 0.00 0.00 0.00 42675.74 30-SEP-13:20 41640.02 30-SEP-13:20 0.00 0.00 0.00
October 0.248966E+11 0.00 458.44 0.196440E+11 0.00 0.00 0.00 0.00 47884.96 16-OCT-12:20 47884.96 16-OCT-12:20 0.00 0.00 0.00
November 0.219667E+11 0.00 411.16 0.181932E+11 0.00 0.00 0.00 0.00 44781.56 19-NOV-12:30 44781.56 19-NOV-12:30 0.00 0.00 0.00
December 0.250156E+11 0.00 425.14 0.227463E+11 0.00 0.00 0.00 0.00 40370.32 19-DEC-13:00 40370.32 19-DEC-13:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.146884E+12 0.00 3314.35 0.108919E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 62706442.41 0.00 14.00 7747375.92 0.00 0.00 0.00 0.00 3981.21   764.47   0.00 0.00 0.00
Maximum of Months 0.250156E+11 0.00 458.44 0.227463E+11 0.00 0.00 0.00 0.00 47884.96   47884.96   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.625529E+10 0.00 305.04 0.308970E+10 0.00 0.00 0.00 0.00 61071.85 21-JAN-09:02 60902.83 15-JAN-09:02 0.00 0.00 0.00
February 0.685124E+10 0.00 344.54 0.339437E+10 0.00 0.00 0.00 0.00 61815.13 13-FEB-19:03 56664.32 20-FEB-09:02 0.00 0.00 0.00
March 0.899609E+10 0.00 382.64 0.439060E+10 0.00 0.00 0.00 0.00 59201.65 24-MAR-15:02 58393.37 11-MAR-16:02 0.00 0.00 0.00
April 0.168809E+11 0.00 492.39 0.834024E+10 0.00 0.00 0.00 0.00 61654.77 26-APR-08:62 59635.78 26-APR-15:02 0.00 0.00 0.00
May 0.217435E+11 0.00 520.26 0.118797E+11 0.00 0.00 0.00 0.00 62073.70 06-MAY-08:62 58960.59 04-MAY-15:02 0.00 0.00 0.00
June 0.309790E+11 0.00 507.94 0.169582E+11 0.00 0.00 0.00 0.00 70023.53 29-JUN-18:02 58792.75 30-JUN-15:02 0.00 0.00 0.00
July 0.403928E+11 0.00 525.67 0.222747E+11 0.00 0.00 0.00 0.00 73697.62 29-JUL-18:02 60875.98 18-JUL-18:02 0.00 0.00 0.00
August 0.372729E+11 0.00 524.65 0.192001E+11 0.00 0.00 0.00 0.00 73413.17 19-AUG-08:62 60611.69 19-AUG-18:02 0.00 0.00 0.00
September 0.253313E+11 0.00 505.74 0.119549E+11 0.00 0.00 0.00 0.00 71223.61 22-SEP-08:62 61219.68 30-SEP-18:02 0.00 0.00 0.00
October 0.228420E+11 0.00 515.34 0.138766E+11 0.00 0.00 0.00 0.00 73594.49 01-OCT-08:62 66740.23 14-OCT-15:02 0.00 0.00 0.00
November 0.836355E+10 0.00 397.71 0.434354E+10 0.00 0.00 0.00 0.00 62934.17 12-NOV-09:02 62677.43 19-NOV-09:02 0.00 0.00 0.00
December 0.546331E+10 0.00 295.69 0.370225E+10 0.00 0.00 0.00 0.00 60549.93 05-DEC-09:02 60549.93 05-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.231372E+12 0.00 5317.61 0.123405E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.546331E+10 0.00 295.69 0.308970E+10 0.00 0.00 0.00 0.00 59201.65   56664.32   0.00 0.00 0.00
Maximum of Months 0.403928E+11 0.00 525.67 0.222747E+11 0.00 0.00 0.00 0.00 73697.62   66740.23   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.177537E+10 0.00 381.30 0.121757E+10 0.00 0.00 0.00 0.00 10450.78 14-JAN-16:02 10450.78 14-JAN-16:02 0.00 0.00 0.00
February 0.141568E+10 0.00 286.19 0.995173E+09 0.00 0.00 0.00 0.00 10371.29 01-FEB-09:02 10371.29 01-FEB-09:02 0.00 0.00 0.00
March 0.158181E+10 0.00 308.38 0.982038E+09 0.00 0.00 0.00 0.00 10350.59 10-MAR-16:02 10350.59 10-MAR-16:02 0.00 0.00 0.00
April 0.305241E+10 0.00 517.35 0.178156E+10 0.00 0.00 0.00 0.00 10444.33 01-APR-15:01 10444.33 01-APR-15:01 0.00 0.00 0.00
May 0.262533E+10 0.00 486.50 0.146614E+10 0.00 0.00 0.00 0.00 10381.43 03-MAY-08:62 9980.20 24-MAY-08:62 0.00 0.00 0.00
June 0.384522E+10 0.00 592.95 0.203496E+10 0.00 0.00 0.00 0.00 11170.86 28-JUN-15:02 9952.63 02-JUN-15:02 0.00 0.00 0.00
July 0.619719E+10 0.00 683.76 0.337836E+10 0.00 0.00 0.00 0.00 11632.36 24-JUL-18:02 10041.81 19-JUL-15:02 0.00 0.00 0.00
August 0.682480E+10 0.00 691.19 0.374731E+10 0.00 0.00 0.00 0.00 11522.98 13-AUG-18:02 10205.70 19-AUG-15:02 0.00 0.00 0.00
September 0.469226E+10 0.00 633.12 0.255503E+10 0.00 0.00 0.00 0.00 12019.78 21-SEP-15:02 9960.81 30-SEP-18:02 0.00 0.00 0.00
October 0.484046E+10 0.00 618.48 0.337393E+10 0.00 0.00 0.00 0.00 11653.92 05-OCT-15:02 10797.87 16-OCT-15:02 0.00 0.00 0.00
November 0.213919E+10 0.00 443.58 0.145854E+10 0.00 0.00 0.00 0.00 10560.53 19-NOV-09:02 10560.53 19-NOV-09:02 0.00 0.00 0.00
December 0.197589E+10 0.00 406.78 0.167452E+10 0.00 0.00 0.00 0.00 10553.10 05-DEC-09:02 10553.10 05-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.409656E+11 0.00 6049.58 0.246652E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.141568E+10 0.00 286.19 0.982038E+09 0.00 0.00 0.00 0.00 10350.59   9952.63   0.00 0.00 0.00
Maximum of Months 0.682480E+10 0.00 691.19 0.374731E+10 0.00 0.00 0.00 0.00 12019.78   10797.87   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.554613E+09 0.00 175.30 0.343863E+09 0.00 0.00 0.00 0.00 9791.04 21-JAN-09:02 9366.02 14-JAN-16:02 0.00 0.00 0.00
February 0.526729E+09 0.00 158.62 0.349499E+09 0.00 0.00 0.00 0.00 9627.52 01-FEB-09:02 9627.52 01-FEB-09:02 0.00 0.00 0.00
March 0.840309E+09 0.00 200.07 0.484219E+09 0.00 0.00 0.00 0.00 9964.39 23-MAR-15:02 9629.17 11-MAR-16:02 0.00 0.00 0.00
April 0.226941E+10 0.00 398.49 0.131612E+10 0.00 0.00 0.00 0.00 10013.89 27-APR-08:62 9728.95 26-APR-15:02 0.00 0.00 0.00
May 0.245638E+10 0.00 454.93 0.139075E+10 0.00 0.00 0.00 0.00 9986.96 03-MAY-08:62 9575.32 24-MAY-08:62 0.00 0.00 0.00
June 0.387558E+10 0.00 585.36 0.211615E+10 0.00 0.00 0.00 0.00 10725.63 28-JUN-15:02 9551.66 02-JUN-15:02 0.00 0.00 0.00
July 0.605871E+10 0.00 676.67 0.336823E+10 0.00 0.00 0.00 0.00 11150.52 24-JUL-18:02 9580.87 19-JUL-15:02 0.00 0.00 0.00
August 0.602291E+10 0.00 677.08 0.327006E+10 0.00 0.00 0.00 0.00 11090.40 18-AUG-18:02 9601.80 19-AUG-15:02 0.00 0.00 0.00
September 0.341423E+10 0.00 536.70 0.175982E+10 0.00 0.00 0.00 0.00 11550.72 21-SEP-15:02 9637.05 30-SEP-18:02 0.00 0.00 0.00
October 0.309766E+10 0.00 501.98 0.202022E+10 0.00 0.00 0.00 0.00 11276.35 01-OCT-15:02 10359.83 16-OCT-15:02 0.00 0.00 0.00
November 0.716842E+09 0.00 243.80 0.445051E+09 0.00 0.00 0.00 0.00 10131.72 19-NOV-09:02 10131.72 19-NOV-09:02 0.00 0.00 0.00
December 0.530637E+09 0.00 171.81 0.453635E+09 0.00 0.00 0.00 0.00 10125.24 05-DEC-09:02 10125.24 05-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.303640E+11 0.00 4780.82 0.173176E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.526729E+09 0.00 158.62 0.343863E+09 0.00 0.00 0.00 0.00 9627.52   9366.02   0.00 0.00 0.00
Maximum of Months 0.605871E+10 0.00 677.08 0.336823E+10 0.00 0.00 0.00 0.00 11550.72   10359.83   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.313628E+09 0.00 275.47 0.205366E+09 0.00 0.00 0.00 0.00 3095.08 21-JAN-09:02 3087.32 14-JAN-16:02 0.00 0.00 0.00
February 0.301922E+09 0.00 212.16 0.207315E+09 0.00 0.00 0.00 0.00 3022.38 03-FEB-16:02 3022.38 03-FEB-16:02 0.00 0.00 0.00
March 0.351290E+09 0.00 223.72 0.223317E+09 0.00 0.00 0.00 0.00 3057.80 10-MAR-16:02 3057.80 10-MAR-16:02 0.00 0.00 0.00
April 0.780373E+09 0.00 425.17 0.473370E+09 0.00 0.00 0.00 0.00 3155.92 26-APR-08:62 3085.60 01-APR-15:01 0.00 0.00 0.00
May 0.687295E+09 0.00 425.88 0.399465E+09 0.00 0.00 0.00 0.00 3119.83 03-MAY-08:62 2944.11 31-MAY-15:02 0.00 0.00 0.00
June 0.107496E+10 0.00 537.93 0.595907E+09 0.00 0.00 0.00 0.00 3259.91 30-JUN-08:62 2943.32 18-JUN-15:02 0.00 0.00 0.00
July 0.166885E+10 0.00 658.94 0.921015E+09 0.00 0.00 0.00 0.00 3518.97 23-JUL-08:62 3041.35 18-JUL-15:02 0.00 0.00 0.00
August 0.172563E+10 0.00 668.31 0.940275E+09 0.00 0.00 0.00 0.00 3615.85 19-AUG-08:62 3041.89 06-AUG-15:02 0.00 0.00 0.00
September 0.124165E+10 0.00 604.02 0.689069E+09 0.00 0.00 0.00 0.00 3427.36 09-SEP-08:62 2939.16 08-SEP-15:02 0.00 0.00 0.00
October 0.111639E+10 0.00 541.68 0.764593E+09 0.00 0.00 0.00 0.00 3541.27 01-OCT-08:62 3189.94 16-OCT-15:02 0.00 0.00 0.00
November 0.440913E+09 0.00 337.23 0.278623E+09 0.00 0.00 0.00 0.00 3090.47 19-NOV-09:02 3090.47 19-NOV-09:02 0.00 0.00 0.00
December 0.366628E+09 0.00 299.09 0.304996E+09 0.00 0.00 0.00 0.00 3084.09 05-DEC-16:02 3084.09 05-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.100695E+11 0.00 5209.59 0.600331E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.301922E+09 0.00 212.16 0.205366E+09 0.00 0.00 0.00 0.00 3022.38   2939.16   0.00 0.00 0.00
Maximum of Months 0.172563E+10 0.00 668.31 0.940275E+09 0.00 0.00 0.00 0.00 3615.85   3189.94   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 57610929.74 0.00 77.43 38175223.26 0.00 0.00 0.00 0.00 2953.80 14-JAN-16:02 2953.80 14-JAN-16:02 0.00 0.00 0.00
February 93999769.81 0.00 91.15 65507291.98 0.00 0.00 0.00 0.00 2891.52 03-FEB-16:02 2891.52 03-FEB-16:02 0.00 0.00 0.00
March 0.177157E+09 0.00 129.39 0.112044E+09 0.00 0.00 0.00 0.00 2925.41 10-MAR-16:02 2925.41 10-MAR-16:02 0.00 0.00 0.00
April 0.581347E+09 0.00 348.36 0.347682E+09 0.00 0.00 0.00 0.00 3008.10 26-APR-08:62 2951.90 01-APR-15:01 0.00 0.00 0.00
May 0.639517E+09 0.00 409.28 0.376636E+09 0.00 0.00 0.00 0.00 2973.79 03-MAY-08:62 2814.25 17-MAY-15:02 0.00 0.00 0.00
June 0.108174E+10 0.00 536.83 0.610800E+09 0.00 0.00 0.00 0.00 3115.06 30-JUN-08:62 2824.81 28-JUN-15:02 0.00 0.00 0.00
July 0.163473E+10 0.00 648.52 0.911334E+09 0.00 0.00 0.00 0.00 3362.30 23-JUL-08:62 2928.18 18-JUL-15:02 0.00 0.00 0.00
August 0.152123E+10 0.00 638.24 0.816673E+09 0.00 0.00 0.00 0.00 3455.01 19-AUG-08:62 2923.98 18-AUG-15:02 0.00 0.00 0.00
September 0.896266E+09 0.00 536.71 0.472317E+09 0.00 0.00 0.00 0.00 3315.11 21-SEP-15:02 2832.39 12-SEP-15:02 0.00 0.00 0.00
October 0.686723E+09 0.00 432.37 0.438813E+09 0.00 0.00 0.00 0.00 3398.48 01-OCT-08:62 3051.91 16-OCT-15:02 0.00 0.00 0.00
November 98484518.06 0.00 129.10 57942258.37 0.00 0.00 0.00 0.00 2889.94 10-NOV-16:02 2855.09 27-NOV-16:01 0.00 0.00 0.00
December 59379140.44 0.00 69.10 51328712.73 0.00 0.00 0.00 0.00 2950.51 05-DEC-16:02 2950.51 05-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.752818E+10 0.00 4046.48 0.429925E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 57610929.74 0.00 69.10 38175223.26 0.00 0.00 0.00 0.00 2889.94   2814.25   0.00 0.00 0.00
Maximum of Months 0.163473E+10 0.00 648.52 0.911334E+09 0.00 0.00 0.00 0.00 3455.01   3051.91   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.666781E+10 0.00 541.36 0.540311E+10 0.00 0.00 0.00 0.00 14400.58 14-JAN-16:02 14400.58 14-JAN-16:02 0.00 0.00 0.00
February 0.429756E+10 0.00 405.18 0.334891E+10 0.00 0.00 0.00 0.00 14098.65 03-FEB-16:02 14098.65 03-FEB-16:02 0.00 0.00 0.00
March 0.352153E+10 0.00 400.36 0.229234E+10 0.00 0.00 0.00 0.00 14263.23 10-MAR-16:02 14263.23 10-MAR-16:02 0.00 0.00 0.00
April 0.424207E+10 0.00 527.99 0.235058E+10 0.00 0.00 0.00 0.00 14392.95 01-APR-15:01 14392.95 01-APR-15:01 0.00 0.00 0.00
May 0.242793E+10 0.00 411.15 0.114391E+10 0.00 0.00 0.00 0.00 14230.38 06-MAY-15:02 13639.21 03-MAY-15:02 0.00 0.00 0.00
June 0.348554E+10 0.00 502.50 0.155435E+10 0.00 0.00 0.00 0.00 15655.13 29-JUN-18:02 13594.05 20-JUN-15:02 0.00 0.00 0.00
July 0.617776E+10 0.00 619.58 0.291538E+10 0.00 0.00 0.00 0.00 16644.96 24-JUL-18:02 13663.96 31-JUL-15:02 0.00 0.00 0.00
August 0.812750E+10 0.00 655.04 0.409419E+10 0.00 0.00 0.00 0.00 16552.29 13-AUG-18:02 14143.55 19-AUG-15:02 0.00 0.00 0.00
September 0.786616E+10 0.00 631.18 0.449974E+10 0.00 0.00 0.00 0.00 15880.45 22-SEP-08:62 13819.08 08-SEP-15:02 0.00 0.00 0.00
October 0.936631E+10 0.00 631.36 0.706369E+10 0.00 0.00 0.00 0.00 16331.11 01-OCT-18:02 14879.47 16-OCT-15:02 0.00 0.00 0.00
November 0.684814E+10 0.00 572.03 0.531526E+10 0.00 0.00 0.00 0.00 14548.63 19-NOV-09:02 14548.63 19-NOV-09:02 0.00 0.00 0.00
December 0.733512E+10 0.00 550.91 0.648983E+10 0.00 0.00 0.00 0.00 14538.28 05-DEC-09:02 14538.28 05-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.703634E+11 0.00 6448.62 0.464713E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.242793E+10 0.00 400.36 0.114391E+10 0.00 0.00 0.00 0.00 14098.65   13594.05   0.00 0.00 0.00
Maximum of Months 0.936631E+10 0.00 655.04 0.706369E+10 0.00 0.00 0.00 0.00 16644.96   14879.47   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 691.88 507.95 183.94 1013.94 373.46 0.00 0.00 0.00
February 546.53 338.18 208.36 763.99 337.07 0.00 0.00 0.00
March 435.89 212.33 223.56 605.99 347.96 0.00 0.00 0.00
April 364.49 140.88 223.62 542.22 280.09 0.00 0.00 0.00
May 256.82 31.10 225.72 327.90 245.67 0.00 0.00 0.00
June 225.30 13.21 212.09 293.07 184.04 0.00 0.00 0.00
July 237.61 25.41 212.20 349.63 162.48 0.00 0.00 0.00
August 305.17 94.83 210.34 498.67 175.84 0.00 0.00 0.00
September 419.06 208.19 210.87 675.38 209.46 0.00 0.00 0.00
October 548.73 368.52 180.22 885.12 232.74 0.00 0.00 0.00
November 666.54 472.26 194.28 980.08 335.96 0.00 0.00 0.00
December 740.41 564.21 176.20 1091.06 374.85 0.00 0.00 0.00
                 
Annual Sum or Average 452.81 247.78 205.03 668.65 271.31 0.00 0.00 0.00
Minimum of Months 225.30 13.21 176.20 293.07 162.48 0.00 0.00 0.00
Maximum of Months 740.41 564.21 225.72 1091.06 374.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1948.30 1430.34 517.96 2808.08 1157.01 0.00 0.00 0.00
February 1539.00 952.28 586.71 2104.50 1058.24 0.00 0.00 0.00
March 1227.43 597.91 629.52 1660.39 1086.04 0.00 0.00 0.00
April 1026.39 396.71 629.69 1483.29 885.12 0.00 0.00 0.00
May 723.18 87.58 635.60 875.61 783.29 0.00 0.00 0.00
June 634.43 37.21 597.22 779.47 598.20 0.00 0.00 0.00
July 669.08 71.55 597.53 947.97 520.58 0.00 0.00 0.00
August 859.34 267.03 592.31 1374.21 557.46 0.00 0.00 0.00
September 1180.05 586.24 593.81 1869.41 662.96 0.00 0.00 0.00
October 1545.20 1037.72 507.48 2456.53 728.55 0.00 0.00 0.00
November 1876.94 1329.86 547.08 2712.38 1047.70 0.00 0.00 0.00
December 2084.94 1588.78 496.16 3024.40 1159.93 0.00 0.00 0.00
                 
Annual Sum or Average 1275.09 697.73 577.36 1840.62 852.68 0.00 0.00 0.00
Minimum of Months 634.43 37.21 496.16 779.47 520.58 0.00 0.00 0.00
Maximum of Months 2084.94 1588.78 635.60 3024.40 1159.93 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2530.95 1858.09 672.86 3731.62 1537.79 0.00 0.00 0.00
February 1999.24 1237.07 762.17 2793.00 1428.32 0.00 0.00 0.00
March 1594.50 776.72 817.79 2200.09 1477.68 0.00 0.00 0.00
April 1333.34 515.34 818.00 1969.84 1202.48 0.00 0.00 0.00
May 939.45 113.77 825.68 1140.21 1089.34 0.00 0.00 0.00
June 824.17 48.34 775.83 1010.17 834.52 0.00 0.00 0.00
July 869.17 92.94 776.23 1245.24 717.42 0.00 0.00 0.00
August 1116.33 346.89 769.44 1828.01 748.67 0.00 0.00 0.00
September 1532.95 761.56 771.39 2489.18 884.95 0.00 0.00 0.00
October 2007.30 1348.05 659.24 3260.61 964.37 0.00 0.00 0.00
November 2438.25 1727.56 710.69 3602.71 1393.58 0.00 0.00 0.00
December 2708.45 2063.92 644.54 4014.76 1540.48 0.00 0.00 0.00
                 
Annual Sum or Average 1656.41 906.39 750.02 2439.45 1150.16 0.00 0.00 0.00
Minimum of Months 824.17 48.34 644.54 1010.17 717.42 0.00 0.00 0.00
Maximum of Months 2708.45 2063.92 825.68 4014.76 1540.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 136.80 100.43 36.37 204.39 71.20 0.00 0.00 0.00
February 108.06 66.86 41.20 152.47 65.11 0.00 0.00 0.00
March 86.18 41.98 44.20 120.27 68.93 0.00 0.00 0.00
April 72.07 27.85 44.21 107.05 54.85 0.00 0.00 0.00
May 50.78 6.15 44.63 62.88 49.44 0.00 0.00 0.00
June 44.55 2.61 41.93 56.66 35.64 0.00 0.00 0.00
July 46.98 5.02 41.96 69.54 29.56 0.00 0.00 0.00
August 60.34 18.75 41.59 100.65 30.70 0.00 0.00 0.00
September 82.86 41.16 41.69 136.06 37.05 0.00 0.00 0.00
October 108.49 72.86 35.63 178.85 40.50 0.00 0.00 0.00
November 131.79 93.37 38.41 196.98 63.28 0.00 0.00 0.00
December 146.39 111.55 34.84 219.78 70.88 0.00 0.00 0.00
                 
Annual Sum or Average 89.53 48.99 40.54 133.75 51.36 0.00 0.00 0.00
Minimum of Months 44.55 2.61 34.84 56.66 29.56 0.00 0.00 0.00
Maximum of Months 146.39 111.55 44.63 219.78 71.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.13 49.99 49.14 125.11 144.00 0.00 0.00 0.00
February 118.40 54.72 63.67 143.57 127.68 0.00 0.00 0.00
March 135.41 59.84 75.57 169.05 130.16 0.00 0.00 0.00
April 186.62 97.02 89.60 264.96 99.05 0.00 0.00 0.00
May 183.33 84.55 98.78 255.16 87.82 0.00 0.00 0.00
June 194.16 96.95 97.21 287.91 62.53 0.00 0.00 0.00
July 205.59 109.90 95.69 322.70 51.97 0.00 0.00 0.00
August 192.92 104.46 88.46 304.95 55.00 0.00 0.00 0.00
September 165.33 88.43 76.90 251.34 67.26 0.00 0.00 0.00
October 127.00 69.58 57.41 198.43 78.77 0.00 0.00 0.00
November 114.28 59.82 54.46 149.22 126.05 0.00 0.00 0.00
December 100.52 53.75 46.77 129.00 143.83 0.00 0.00 0.00
                 
Annual Sum or Average 152.02 77.52 74.51 217.15 97.70 0.00 0.00 0.00
Minimum of Months 99.13 49.99 46.77 125.11 51.97 0.00 0.00 0.00
Maximum of Months 205.59 109.90 98.78 322.70 144.00 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.68 0.00 20.68 15.26 76.53 0.00 0.00 0.00
February 25.96 0.00 25.96 17.25 68.85 0.00 0.00 0.00
March 31.81 0.00 31.81 24.95 70.90 0.00 0.00 0.00
April 36.84 0.30 36.55 34.77 52.73 0.00 0.00 0.00
May 44.32 2.31 42.01 44.46 45.30 0.00 0.00 0.00
June 46.98 4.64 42.34 57.08 32.34 0.00 0.00 0.00
July 44.50 3.78 40.73 60.43 27.34 0.00 0.00 0.00
August 37.00 0.82 36.18 48.96 28.94 0.00 0.00 0.00
September 31.23 0.01 31.23 37.81 36.51 0.00 0.00 0.00
October 24.77 0.00 24.77 33.73 41.91 0.00 0.00 0.00
November 22.43 0.00 22.43 17.44 67.82 0.00 0.00 0.00
December 19.25 0.00 19.25 13.85 76.72 0.00 0.00 0.00
                 
Annual Sum or Average 32.17 0.99 31.18 33.94 52.07 0.00 0.00 0.00
Minimum of Months 19.25 0.00 19.25 13.85 27.34 0.00 0.00 0.00
Maximum of Months 46.98 4.64 42.34 60.43 76.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.13 49.99 49.14 131.73 139.51 0.00 0.00 0.00
February 118.40 54.72 63.67 148.59 124.72 0.00 0.00 0.00
March 135.41 59.84 75.57 173.05 128.12 0.00 0.00 0.00
April 186.62 97.02 89.60 267.96 97.82 0.00 0.00 0.00
May 183.33 84.55 98.78 256.04 87.59 0.00 0.00 0.00
June 194.16 96.95 97.21 288.06 62.55 0.00 0.00 0.00
July 205.59 109.90 95.69 323.12 51.88 0.00 0.00 0.00
August 192.92 104.46 88.46 306.69 54.35 0.00 0.00 0.00
September 165.33 88.43 76.90 254.62 65.85 0.00 0.00 0.00
October 127.00 69.58 57.41 202.65 76.56 0.00 0.00 0.00
November 114.28 59.82 54.46 155.08 122.45 0.00 0.00 0.00
December 100.52 53.75 46.77 135.78 139.22 0.00 0.00 0.00
                 
Annual Sum or Average 152.02 77.52 74.51 220.64 95.74 0.00 0.00 0.00
Minimum of Months 99.13 49.99 46.77 131.73 51.88 0.00 0.00 0.00
Maximum of Months 205.59 109.90 98.78 323.12 139.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.42 80.33 29.09 159.35 66.08 0.00 0.00 0.00
February 86.43 53.48 32.95 118.28 60.26 0.00 0.00 0.00
March 68.93 33.58 35.35 93.21 61.77 0.00 0.00 0.00
April 57.64 22.28 35.36 83.59 49.69 0.00 0.00 0.00
May 40.61 4.92 35.70 50.10 42.27 0.00 0.00 0.00
June 35.63 2.09 33.54 45.63 30.62 0.00 0.00 0.00
July 37.58 4.02 33.56 54.49 27.70 0.00 0.00 0.00
August 48.26 15.00 33.26 78.65 29.99 0.00 0.00 0.00
September 66.27 32.92 33.35 106.47 36.21 0.00 0.00 0.00
October 86.78 58.28 28.50 139.98 39.80 0.00 0.00 0.00
November 105.41 74.68 30.72 153.60 59.69 0.00 0.00 0.00
December 117.09 89.23 27.86 171.54 66.32 0.00 0.00 0.00
                 
Annual Sum or Average 71.61 39.18 32.42 104.54 47.47 0.00 0.00 0.00
Minimum of Months 35.63 2.09 27.86 45.63 27.70 0.00 0.00 0.00
Maximum of Months 117.09 89.23 35.70 171.54 66.32 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.54 0.00 16.54 12.90 61.25 0.00 0.00 0.00
February 20.77 0.00 20.77 14.67 55.12 0.00 0.00 0.00
March 25.45 0.00 25.45 21.03 56.79 0.00 0.00 0.00
April 29.48 0.24 29.24 30.86 40.84 0.00 0.00 0.00
May 35.46 1.85 33.61 38.85 35.23 0.00 0.00 0.00
June 37.59 3.71 33.88 49.80 24.58 0.00 0.00 0.00
July 35.61 3.02 32.58 53.18 20.11 0.00 0.00 0.00
August 29.60 0.66 28.95 43.78 21.03 0.00 0.00 0.00
September 24.99 0.00 24.98 33.79 27.00 0.00 0.00 0.00
October 19.82 0.00 19.82 29.77 31.71 0.00 0.00 0.00
November 17.95 0.00 17.95 15.23 53.29 0.00 0.00 0.00
December 15.40 0.00 15.40 11.94 61.06 0.00 0.00 0.00
                 
Annual Sum or Average 25.74 0.79 24.95 29.74 40.60 0.00 0.00 0.00
Minimum of Months 15.40 0.00 15.40 11.94 20.11 0.00 0.00 0.00
Maximum of Months 37.59 3.71 33.88 53.18 61.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 104.03 55.59 48.45 127.20 136.58 0.00 0.00 0.00
February 109.78 50.23 59.54 125.13 122.21 0.00 0.00 0.00
March 133.98 59.84 74.14 162.32 124.32 0.00 0.00 0.00
April 170.78 85.69 85.09 237.08 94.94 0.00 0.00 0.00
May 160.86 67.04 93.82 218.24 84.92 0.00 0.00 0.00
June 160.04 69.48 90.57 234.22 61.83 0.00 0.00 0.00
July 181.24 90.04 91.20 284.66 51.92 0.00 0.00 0.00
August 179.13 95.20 83.93 283.59 53.69 0.00 0.00 0.00
September 130.78 60.15 70.63 195.46 65.75 0.00 0.00 0.00
October 115.26 59.16 56.10 176.39 75.02 0.00 0.00 0.00
November 104.83 53.07 51.76 129.36 120.96 0.00 0.00 0.00
December 100.77 56.17 44.61 122.65 136.46 0.00 0.00 0.00
                 
Annual Sum or Average 137.81 66.94 70.87 191.82 93.91 0.00 0.00 0.00
Minimum of Months 100.77 50.23 44.61 122.65 51.92 0.00 0.00 0.00
Maximum of Months 181.24 95.20 93.82 284.66 136.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 136.80 100.43 36.37 203.44 70.98 0.00 0.00 0.00
February 108.06 66.86 41.20 151.91 64.51 0.00 0.00 0.00
March 86.18 41.98 44.20 119.33 68.38 0.00 0.00 0.00
April 72.07 27.85 44.21 105.93 53.90 0.00 0.00 0.00
May 50.78 6.15 44.63 62.15 48.41 0.00 0.00 0.00
June 44.55 2.61 41.93 56.14 34.51 0.00 0.00 0.00
July 46.98 5.02 41.96 68.68 28.54 0.00 0.00 0.00
August 60.34 18.75 41.59 99.75 29.79 0.00 0.00 0.00
September 82.86 41.16 41.69 135.89 35.88 0.00 0.00 0.00
October 108.49 72.86 35.63 178.38 39.92 0.00 0.00 0.00
November 131.79 93.37 38.41 196.49 62.66 0.00 0.00 0.00
December 146.39 111.55 34.84 219.06 70.46 0.00 0.00 0.00
                 
Annual Sum or Average 89.53 48.99 40.54 133.04 50.59 0.00 0.00 0.00
Minimum of Months 44.55 2.61 34.84 56.14 28.54 0.00 0.00 0.00
Maximum of Months 146.39 111.55 44.63 219.06 70.98 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.68 0.00 20.68 14.57 76.08 0.00 0.00 0.00
February 25.96 0.00 25.96 16.77 68.05 0.00 0.00 0.00
March 31.81 0.00 31.81 24.08 70.36 0.00 0.00 0.00
April 36.84 0.30 36.55 33.72 51.93 0.00 0.00 0.00
May 44.32 2.31 42.01 43.93 44.47 0.00 0.00 0.00
June 46.98 4.64 42.34 56.88 31.54 0.00 0.00 0.00
July 44.50 3.78 40.73 59.79 26.58 0.00 0.00 0.00
August 37.00 0.82 36.18 47.97 28.16 0.00 0.00 0.00
September 31.23 0.01 31.23 37.57 35.29 0.00 0.00 0.00
October 24.77 0.00 24.77 33.17 41.32 0.00 0.00 0.00
November 22.43 0.00 22.43 17.07 66.70 0.00 0.00 0.00
December 19.25 0.00 19.25 13.28 75.94 0.00 0.00 0.00
                 
Annual Sum or Average 32.17 0.99 31.18 33.33 51.29 0.00 0.00 0.00
Minimum of Months 19.25 0.00 19.25 13.28 26.58 0.00 0.00 0.00
Maximum of Months 46.98 4.64 42.34 59.79 76.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 104.03 55.59 48.45 133.52 131.04 0.00 0.00 0.00
February 109.78 50.23 59.54 130.12 118.64 0.00 0.00 0.00
March 133.98 59.84 74.14 166.14 122.01 0.00 0.00 0.00
April 170.78 85.69 85.09 239.86 93.61 0.00 0.00 0.00
May 160.86 67.04 93.82 219.10 84.66 0.00 0.00 0.00
June 160.04 69.48 90.57 234.34 61.89 0.00 0.00 0.00
July 181.24 90.04 91.20 284.99 51.85 0.00 0.00 0.00
August 179.13 95.20 83.93 284.96 53.01 0.00 0.00 0.00
September 130.78 60.15 70.63 198.58 64.15 0.00 0.00 0.00
October 115.26 59.16 56.10 180.36 72.67 0.00 0.00 0.00
November 104.83 53.07 51.76 135.23 116.14 0.00 0.00 0.00
December 100.77 56.17 44.61 129.24 130.71 0.00 0.00 0.00
                 
Annual Sum or Average 137.81 66.94 70.87 195.15 91.56 0.00 0.00 0.00
Minimum of Months 100.77 50.23 44.61 129.24 51.85 0.00 0.00 0.00
Maximum of Months 181.24 95.20 93.82 284.99 131.04 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.19 0.00 26.19 16.60 107.96 0.00 0.00 0.00
February 32.87 0.00 32.87 19.48 97.67 0.00 0.00 0.00
March 40.29 0.00 40.29 30.19 97.81 0.00 0.00 0.00
April 46.66 0.38 46.28 44.40 73.30 0.00 0.00 0.00
May 56.13 2.93 53.20 56.60 63.38 0.00 0.00 0.00
June 59.50 5.88 53.62 72.79 46.76 0.00 0.00 0.00
July 56.36 4.78 51.58 76.49 41.03 0.00 0.00 0.00
August 46.86 1.04 45.82 61.08 44.46 0.00 0.00 0.00
September 39.55 0.01 39.55 46.72 54.74 0.00 0.00 0.00
October 31.37 0.00 31.37 39.88 64.67 0.00 0.00 0.00
November 28.41 0.00 28.41 19.24 97.62 0.00 0.00 0.00
December 24.38 0.00 24.38 14.36 110.08 0.00 0.00 0.00
                 
Annual Sum or Average 40.75 1.26 39.49 41.62 74.85 0.00 0.00 0.00
Minimum of Months 24.38 0.00 24.38 14.36 41.03 0.00 0.00 0.00
Maximum of Months 59.50 5.88 53.62 76.49 110.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.65 0.00 9.65 6.12 39.80 0.00 0.00 0.00
February 12.12 0.00 12.12 7.18 36.01 0.00 0.00 0.00
March 14.85 0.00 14.85 11.13 36.06 0.00 0.00 0.00
April 17.20 0.14 17.06 16.37 27.02 0.00 0.00 0.00
May 20.69 1.08 19.61 20.86 23.36 0.00 0.00 0.00
June 21.93 2.17 19.77 26.83 17.24 0.00 0.00 0.00
July 20.78 1.76 19.01 28.20 15.13 0.00 0.00 0.00
August 17.27 0.38 16.89 22.52 16.39 0.00 0.00 0.00
September 14.58 0.00 14.58 17.22 20.18 0.00 0.00 0.00
October 11.57 0.00 11.57 14.70 23.84 0.00 0.00 0.00
November 10.47 0.00 10.47 7.09 35.99 0.00 0.00 0.00
December 8.99 0.00 8.99 5.29 40.58 0.00 0.00 0.00
                 
Annual Sum or Average 15.02 0.46 14.56 15.34 27.59 0.00 0.00 0.00
Minimum of Months 8.99 0.00 8.99 5.29 15.13 0.00 0.00 0.00
Maximum of Months 21.93 2.17 19.77 28.20 40.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 63.83 46.86 16.97 95.74 35.78 0.00 0.00 0.00
February 50.42 31.20 19.22 71.24 33.24 0.00 0.00 0.00
March 40.21 19.59 20.62 56.40 34.52 0.00 0.00 0.00
April 33.63 13.00 20.63 50.66 27.64 0.00 0.00 0.00
May 23.69 2.87 20.82 29.65 25.26 0.00 0.00 0.00
June 20.79 1.22 19.57 26.65 18.82 0.00 0.00 0.00
July 21.92 2.34 19.58 32.57 16.22 0.00 0.00 0.00
August 28.15 8.75 19.41 47.00 17.09 0.00 0.00 0.00
September 38.66 19.21 19.45 63.67 20.06 0.00 0.00 0.00
October 50.62 34.00 16.63 83.10 22.40 0.00 0.00 0.00
November 61.49 43.57 17.92 92.01 32.57 0.00 0.00 0.00
December 68.31 52.05 16.25 102.66 36.09 0.00 0.00 0.00
                 
Annual Sum or Average 41.77 22.86 18.92 62.59 26.61 0.00 0.00 0.00
Minimum of Months 20.79 1.22 16.25 26.65 16.22 0.00 0.00 0.00
Maximum of Months 68.31 52.05 20.82 102.66 36.09 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 173.25 127.19 46.06 259.85 97.10 0.00 0.00 0.00
February 136.85 84.68 52.17 193.35 90.21 0.00 0.00 0.00
March 109.15 53.17 55.98 153.09 93.70 0.00 0.00 0.00
April 91.27 35.28 55.99 137.50 75.03 0.00 0.00 0.00
May 64.31 7.79 56.52 80.47 68.57 0.00 0.00 0.00
June 56.42 3.31 53.11 72.34 51.09 0.00 0.00 0.00
July 59.50 6.36 53.13 88.39 44.01 0.00 0.00 0.00
August 76.41 23.74 52.67 127.55 46.38 0.00 0.00 0.00
September 104.93 52.13 52.80 172.81 54.43 0.00 0.00 0.00
October 137.40 92.28 45.13 225.56 60.80 0.00 0.00 0.00
November 166.90 118.25 48.65 249.74 88.40 0.00 0.00 0.00
December 185.40 141.28 44.12 278.65 97.97 0.00 0.00 0.00
                 
Annual Sum or Average 113.38 62.04 51.34 169.88 72.22 0.00 0.00 0.00
Minimum of Months 56.42 3.31 44.12 72.34 44.01 0.00 0.00 0.00
Maximum of Months 185.40 141.28 56.52 278.65 97.97 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 136.80 100.43 36.37 203.64 70.05 0.00 0.00 0.00
February 108.06 66.86 41.20 151.45 63.93 0.00 0.00 0.00
March 86.18 41.98 44.20 119.34 68.13 0.00 0.00 0.00
April 72.07 27.85 44.21 105.69 54.27 0.00 0.00 0.00
May 50.78 6.15 44.63 61.83 48.95 0.00 0.00 0.00
June 44.55 2.61 41.93 55.65 35.24 0.00 0.00 0.00
July 46.98 5.02 41.96 68.47 29.17 0.00 0.00 0.00
August 60.34 18.75 41.59 99.43 30.24 0.00 0.00 0.00
September 82.86 41.16 41.69 134.75 36.38 0.00 0.00 0.00
October 108.49 72.86 35.63 177.79 39.55 0.00 0.00 0.00
November 131.79 93.37 38.41 195.96 62.11 0.00 0.00 0.00
December 146.39 111.55 34.84 218.95 69.52 0.00 0.00 0.00
                 
Annual Sum or Average 89.53 48.99 40.54 132.70 50.56 0.00 0.00 0.00
Minimum of Months 44.55 2.61 34.84 55.65 29.17 0.00 0.00 0.00
Maximum of Months 146.39 111.55 44.63 218.95 70.05 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.13 49.99 49.14 124.14 141.16 0.00 0.00 0.00
February 118.40 54.72 63.67 142.32 124.96 0.00 0.00 0.00
March 135.41 59.84 75.57 167.05 128.25 0.00 0.00 0.00
April 186.62 97.02 89.60 261.25 97.77 0.00 0.00 0.00
May 183.33 84.55 98.78 251.47 86.69 0.00 0.00 0.00
June 194.16 96.95 97.21 283.68 61.63 0.00 0.00 0.00
July 205.59 109.90 95.69 318.62 51.09 0.00 0.00 0.00
August 192.92 104.46 88.46 301.20 54.02 0.00 0.00 0.00
September 165.33 88.43 76.90 248.27 65.92 0.00 0.00 0.00
October 127.00 69.58 57.41 196.90 76.71 0.00 0.00 0.00
November 114.28 59.82 54.46 148.07 123.27 0.00 0.00 0.00
December 100.52 53.75 46.77 128.36 140.52 0.00 0.00 0.00
                 
Annual Sum or Average 152.02 77.52 74.51 214.64 95.86 0.00 0.00 0.00
Minimum of Months 99.13 49.99 46.77 124.14 51.09 0.00 0.00 0.00
Maximum of Months 205.59 109.90 98.78 318.62 141.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.68 0.00 20.68 15.82 74.62 0.00 0.00 0.00
February 25.96 0.00 25.96 17.72 67.13 0.00 0.00 0.00
March 31.81 0.00 31.81 25.00 69.76 0.00 0.00 0.00
April 36.84 0.30 36.55 34.18 52.01 0.00 0.00 0.00
May 44.32 2.31 42.01 43.72 44.75 0.00 0.00 0.00
June 46.98 4.64 42.34 55.95 31.92 0.00 0.00 0.00
July 44.50 3.78 40.73 59.36 26.92 0.00 0.00 0.00
August 37.00 0.82 36.18 48.23 28.45 0.00 0.00 0.00
September 31.23 0.01 31.23 37.41 35.74 0.00 0.00 0.00
October 24.77 0.00 24.77 34.01 40.63 0.00 0.00 0.00
November 22.43 0.00 22.43 18.04 65.96 0.00 0.00 0.00
December 19.25 0.00 19.25 14.62 74.47 0.00 0.00 0.00
                 
Annual Sum or Average 32.17 0.99 31.18 33.77 50.95 0.00 0.00 0.00
Minimum of Months 19.25 0.00 19.25 14.62 26.92 0.00 0.00 0.00
Maximum of Months 46.98 4.64 42.34 59.36 74.62 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.13 49.99 49.14 131.76 136.01 0.00 0.00 0.00
February 118.40 54.72 63.67 148.09 121.54 0.00 0.00 0.00
March 135.41 59.84 75.57 171.47 125.97 0.00 0.00 0.00
April 186.62 97.02 89.60 264.46 96.38 0.00 0.00 0.00
May 183.33 84.55 98.78 252.36 86.45 0.00 0.00 0.00
June 194.16 96.95 97.21 283.80 61.66 0.00 0.00 0.00
July 205.59 109.90 95.69 319.02 51.00 0.00 0.00 0.00
August 192.92 104.46 88.46 302.95 53.32 0.00 0.00 0.00
September 165.33 88.43 76.90 251.76 64.33 0.00 0.00 0.00
October 127.00 69.58 57.41 201.60 74.18 0.00 0.00 0.00
November 114.28 59.82 54.46 154.91 119.01 0.00 0.00 0.00
December 100.52 53.75 46.77 136.29 135.16 0.00 0.00 0.00
                 
Annual Sum or Average 152.02 77.52 74.51 218.56 93.61 0.00 0.00 0.00
Minimum of Months 99.13 49.99 46.77 131.76 51.00 0.00 0.00 0.00
Maximum of Months 205.59 109.90 98.78 319.02 136.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 200.63 147.29 53.34 293.10 107.57 0.00 0.00 0.00
February 158.48 98.06 60.42 218.07 97.28 0.00 0.00 0.00
March 126.40 61.57 64.83 172.26 102.14 0.00 0.00 0.00
April 105.69 40.85 64.84 155.09 78.68 0.00 0.00 0.00
May 74.47 9.02 65.45 92.91 69.73 0.00 0.00 0.00
June 65.33 3.83 61.50 85.17 48.98 0.00 0.00 0.00
July 68.90 7.37 61.53 104.24 39.87 0.00 0.00 0.00
August 88.49 27.50 60.99 148.14 42.11 0.00 0.00 0.00
September 121.52 60.37 61.15 197.78 52.42 0.00 0.00 0.00
October 159.12 106.86 52.26 258.94 59.01 0.00 0.00 0.00
November 193.28 136.94 56.34 282.96 94.72 0.00 0.00 0.00
December 214.70 163.60 51.09 315.49 106.78 0.00 0.00 0.00
                 
Annual Sum or Average 131.30 71.85 59.45 193.63 74.82 0.00 0.00 0.00
Minimum of Months 65.33 3.83 51.09 85.17 39.87 0.00 0.00 0.00
Maximum of Months 214.70 163.60 65.45 315.49 107.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 144.74 0.00 144.74 68.19 676.71 0.00 0.00 0.00
February 181.69 0.00 181.69 77.89 627.39 0.00 0.00 0.00
March 222.66 0.00 222.66 124.75 633.01 0.00 0.00 0.00
April 257.88 2.08 255.81 191.95 472.06 0.00 0.00 0.00
May 310.23 16.18 294.05 244.96 407.13 0.00 0.00 0.00
June 328.85 32.49 296.36 333.57 303.06 0.00 0.00 0.00
July 311.50 26.43 285.07 364.16 260.46 0.00 0.00 0.00
August 258.99 5.75 253.24 290.59 281.35 0.00 0.00 0.00
September 218.62 0.04 218.58 219.47 346.82 0.00 0.00 0.00
October 173.40 0.00 173.40 194.30 399.43 0.00 0.00 0.00
November 157.00 0.00 157.00 82.52 604.58 0.00 0.00 0.00
December 134.74 0.00 134.74 60.26 677.85 0.00 0.00 0.00
                 
Annual Sum or Average 225.21 6.95 218.26 188.41 473.36 0.00 0.00 0.00
Minimum of Months 134.74 0.00 134.74 60.26 260.46 0.00 0.00 0.00
Maximum of Months 328.85 32.49 296.36 364.16 677.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 144.74 0.00 144.74 60.96 698.60 0.00 0.00 0.00
February 181.69 0.00 181.69 69.56 648.98 0.00 0.00 0.00
March 222.66 0.00 222.66 114.23 653.16 0.00 0.00 0.00
April 257.88 2.08 255.81 180.07 485.78 0.00 0.00 0.00
May 310.23 16.18 294.05 231.08 418.29 0.00 0.00 0.00
June 328.85 32.49 296.36 320.72 312.09 0.00 0.00 0.00
July 311.50 26.43 285.07 352.80 268.23 0.00 0.00 0.00
August 258.99 5.75 253.24 280.32 290.17 0.00 0.00 0.00
September 218.62 0.04 218.58 209.91 358.18 0.00 0.00 0.00
October 173.40 0.00 173.40 185.83 411.97 0.00 0.00 0.00
November 157.00 0.00 157.00 74.65 623.40 0.00 0.00 0.00
December 134.74 0.00 134.74 53.70 699.25 0.00 0.00 0.00
                 
Annual Sum or Average 225.21 6.95 218.26 178.51 488.18 0.00 0.00 0.00
Minimum of Months 134.74 0.00 134.74 53.70 268.23 0.00 0.00 0.00
Maximum of Months 328.85 32.49 296.36 352.80 699.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.68 0.00 20.68 15.02 87.88 0.00 0.00 0.00
February 25.96 0.00 25.96 16.33 83.29 0.00 0.00 0.00
March 31.81 0.00 31.81 24.51 84.77 0.00 0.00 0.00
April 36.84 0.30 36.55 37.51 63.89 0.00 0.00 0.00
May 44.32 2.31 42.01 47.96 56.72 0.00 0.00 0.00
June 46.98 4.64 42.34 62.68 42.69 0.00 0.00 0.00
July 44.50 3.78 40.73 67.97 36.96 0.00 0.00 0.00
August 37.00 0.82 36.18 55.84 39.23 0.00 0.00 0.00
September 31.23 0.01 31.23 42.70 45.38 0.00 0.00 0.00
October 24.77 0.00 24.77 37.61 51.78 0.00 0.00 0.00
November 22.43 0.00 22.43 17.85 78.42 0.00 0.00 0.00
December 19.25 0.00 19.25 13.77 88.08 0.00 0.00 0.00
                 
Annual Sum or Average 32.17 0.99 31.18 36.77 63.15 0.00 0.00 0.00
Minimum of Months 19.25 0.00 19.25 13.77 36.96 0.00 0.00 0.00
Maximum of Months 46.98 4.64 42.34 67.97 88.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 208.05 111.16 96.89 270.64 306.45 0.00 0.00 0.00
February 219.54 100.46 119.08 258.05 294.29 0.00 0.00 0.00
March 267.94 119.67 148.26 334.22 297.80 0.00 0.00 0.00
April 341.54 171.37 170.17 496.42 232.27 0.00 0.00 0.00
May 321.70 134.06 187.64 453.68 214.60 0.00 0.00 0.00
June 320.07 138.95 181.12 492.11 165.73 0.00 0.00 0.00
July 362.45 180.07 182.38 602.54 143.21 0.00 0.00 0.00
August 358.23 190.39 167.84 600.88 147.83 0.00 0.00 0.00
September 261.54 120.30 141.24 418.85 167.46 0.00 0.00 0.00
October 230.50 118.31 112.19 379.27 185.38 0.00 0.00 0.00
November 209.64 106.13 103.51 274.00 276.30 0.00 0.00 0.00
December 201.53 112.32 89.21 260.68 306.65 0.00 0.00 0.00
                 
Annual Sum or Average 275.60 133.87 141.73 404.45 227.81 0.00 0.00 0.00
Minimum of Months 201.53 100.46 89.21 258.05 143.21 0.00 0.00 0.00
Maximum of Months 362.45 190.39 187.64 602.54 306.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 136.80 100.43 36.37 209.76 80.39 0.00 0.00 0.00
February 108.06 66.86 41.20 155.19 78.34 0.00 0.00 0.00
March 86.18 41.98 44.20 122.64 81.97 0.00 0.00 0.00
April 72.07 27.85 44.21 111.99 65.24 0.00 0.00 0.00
May 50.78 6.15 44.63 66.50 60.62 0.00 0.00 0.00
June 44.55 2.61 41.93 62.40 45.81 0.00 0.00 0.00
July 46.98 5.02 41.96 77.55 38.95 0.00 0.00 0.00
August 60.34 18.75 41.59 108.87 40.40 0.00 0.00 0.00
September 82.86 41.16 41.69 143.71 45.33 0.00 0.00 0.00
October 108.49 72.86 35.63 186.24 49.65 0.00 0.00 0.00
November 131.79 93.37 38.41 202.43 72.52 0.00 0.00 0.00
December 146.39 111.55 34.84 225.26 80.11 0.00 0.00 0.00
                 
Annual Sum or Average 89.53 48.99 40.54 139.35 61.52 0.00 0.00 0.00
Minimum of Months 44.55 2.61 34.84 62.40 38.95 0.00 0.00 0.00
Maximum of Months 146.39 111.55 44.63 225.26 81.97 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.19 0.00 26.19 15.06 107.70 0.00 0.00 0.00
February 32.87 0.00 32.87 17.95 97.01 0.00 0.00 0.00
March 40.29 0.00 40.29 27.75 98.31 0.00 0.00 0.00
April 46.66 0.38 46.28 40.67 74.38 0.00 0.00 0.00
May 56.13 2.93 53.20 52.75 64.14 0.00 0.00 0.00
June 59.50 5.88 53.62 67.78 48.21 0.00 0.00 0.00
July 56.36 4.78 51.58 71.21 42.66 0.00 0.00 0.00
August 46.86 1.04 45.82 56.40 46.30 0.00 0.00 0.00
September 39.55 0.01 39.55 43.32 55.93 0.00 0.00 0.00
October 31.37 0.00 31.37 37.57 65.05 0.00 0.00 0.00
November 28.41 0.00 28.41 17.89 96.47 0.00 0.00 0.00
December 24.38 0.00 24.38 13.27 108.35 0.00 0.00 0.00
                 
Annual Sum or Average 40.75 1.26 39.49 38.59 75.27 0.00 0.00 0.00
Minimum of Months 24.38 0.00 24.38 13.27 42.66 0.00 0.00 0.00
Maximum of Months 59.50 5.88 53.62 71.21 108.35 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.43 0.00 23.43 13.48 96.35 0.00 0.00 0.00
February 29.41 0.00 29.41 16.06 86.79 0.00 0.00 0.00
March 36.04 0.00 36.04 24.83 87.96 0.00 0.00 0.00
April 41.74 0.34 41.41 36.38 66.55 0.00 0.00 0.00
May 50.22 2.62 47.60 47.20 57.38 0.00 0.00 0.00
June 53.23 5.26 47.97 60.65 43.13 0.00 0.00 0.00
July 50.42 4.28 46.15 63.71 38.17 0.00 0.00 0.00
August 41.92 0.93 40.99 50.46 41.42 0.00 0.00 0.00
September 35.39 0.01 35.38 38.76 50.04 0.00 0.00 0.00
October 28.07 0.00 28.07 33.62 58.20 0.00 0.00 0.00
November 25.41 0.00 25.41 16.00 86.31 0.00 0.00 0.00
December 21.81 0.00 21.81 11.87 96.93 0.00 0.00 0.00
                 
Annual Sum or Average 36.46 1.13 35.33 34.53 67.34 0.00 0.00 0.00
Minimum of Months 21.81 0.00 21.81 11.87 38.17 0.00 0.00 0.00
Maximum of Months 53.23 5.26 47.97 63.71 96.93 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 510.71 374.93 135.77 756.79 285.75 0.00 0.00 0.00
February 403.42 249.62 153.80 560.40 264.79 0.00 0.00 0.00
March 321.75 156.73 165.02 440.50 278.56 0.00 0.00 0.00
April 269.05 103.99 165.06 391.91 225.23 0.00 0.00 0.00
May 189.57 22.96 166.61 225.19 205.79 0.00 0.00 0.00
June 166.31 9.75 156.55 199.51 156.30 0.00 0.00 0.00
July 175.39 18.75 156.63 245.61 135.93 0.00 0.00 0.00
August 225.26 70.00 155.26 360.88 143.09 0.00 0.00 0.00
September 309.33 153.67 155.66 496.34 164.25 0.00 0.00 0.00
October 405.04 272.02 133.03 653.78 180.80 0.00 0.00 0.00
November 492.00 348.59 143.41 727.29 257.99 0.00 0.00 0.00
December 546.52 416.47 130.06 813.42 284.79 0.00 0.00 0.00
                 
Annual Sum or Average 334.24 182.90 151.34 489.11 215.02 0.00 0.00 0.00
Minimum of Months 166.31 9.75 130.06 199.51 135.93 0.00 0.00 0.00
Maximum of Months 546.52 416.47 166.61 813.42 285.75 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.185314E+10 0.136048E+10 0.492663E+09 0.271573E+10 0.100029E+10
February 0.132217E+10 0.818116E+09 0.504052E+09 0.184825E+10 0.815436E+09
March 0.116748E+10 0.568705E+09 0.598776E+09 0.162307E+10 0.931984E+09
April 0.944769E+09 0.365158E+09 0.579611E+09 0.140543E+10 0.725988E+09
May 0.687861E+09 83301651.90 0.604559E+09 0.878244E+09 0.658001E+09
June 0.583982E+09 34251187.10 0.549731E+09 0.759647E+09 0.477026E+09
July 0.636401E+09 68053370.08 0.568348E+09 0.936446E+09 0.435199E+09
August 0.817369E+09 0.253989E+09 0.563379E+09 0.133563E+10 0.470970E+09
September 0.108621E+10 0.539619E+09 0.546586E+09 0.175059E+10 0.542923E+09
October 0.146973E+10 0.987033E+09 0.482692E+09 0.237070E+10 0.623367E+09
November 0.172768E+10 0.122410E+10 0.503575E+09 0.254037E+10 0.870802E+09
December 0.198311E+10 0.151118E+10 0.471925E+09 0.292229E+10 0.100401E+10
           
Annual Sum or Average 0.142799E+11 0.781399E+10 0.646590E+10 0.210864E+11 0.855599E+10
Minimum of Months 0.583982E+09 34251187.10 0.471925E+09 0.759647E+09 0.435199E+09
Maximum of Months 0.198311E+10 0.151118E+10 0.604559E+09 0.292229E+10 0.100401E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.521833E+10 0.383102E+10 0.138731E+10 0.752117E+10 0.309894E+10
February 0.372314E+10 0.230376E+10 0.141938E+10 0.509120E+10 0.256009E+10
March 0.328755E+10 0.160144E+10 0.168611E+10 0.444719E+10 0.290884E+10
April 0.266041E+10 0.102826E+10 0.163215E+10 0.384469E+10 0.229423E+10
May 0.193697E+10 0.234572E+09 0.170240E+10 0.234523E+10 0.209797E+10
June 0.164445E+10 96449084.55 0.154801E+10 0.202039E+10 0.155053E+10
July 0.179206E+10 0.191634E+09 0.160043E+10 0.253905E+10 0.139433E+10
August 0.230166E+10 0.715217E+09 0.158644E+10 0.368069E+10 0.149310E+10
September 0.305868E+10 0.151953E+10 0.153915E+10 0.484551E+10 0.171839E+10
October 0.413865E+10 0.277942E+10 0.135923E+10 0.657957E+10 0.195136E+10
November 0.486503E+10 0.344700E+10 0.141803E+10 0.703050E+10 0.271563E+10
December 0.558430E+10 0.425539E+10 0.132891E+10 0.810054E+10 0.310675E+10
           
Annual Sum or Average 0.402112E+11 0.220037E+11 0.182075E+11 0.580457E+11 0.268902E+11
Minimum of Months 0.164445E+10 96449084.55 0.132891E+10 0.202039E+10 0.139433E+10
Maximum of Months 0.558430E+10 0.425539E+10 0.170240E+10 0.810054E+10 0.310675E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.677891E+10 0.497672E+10 0.180219E+10 0.999478E+10 0.411882E+10
February 0.483657E+10 0.299272E+10 0.184385E+10 0.675683E+10 0.345538E+10
March 0.427071E+10 0.208036E+10 0.219036E+10 0.589271E+10 0.395781E+10
April 0.345602E+10 0.133577E+10 0.212025E+10 0.510583E+10 0.311682E+10
May 0.251623E+10 0.304722E+09 0.221151E+10 0.305395E+10 0.291770E+10
June 0.213624E+10 0.125293E+09 0.201095E+10 0.261836E+10 0.216306E+10
July 0.232799E+10 0.248943E+09 0.207905E+10 0.333524E+10 0.192155E+10
August 0.298998E+10 0.929108E+09 0.206087E+10 0.489614E+10 0.200523E+10
September 0.397340E+10 0.197396E+10 0.199944E+10 0.645195E+10 0.229378E+10
October 0.537634E+10 0.361063E+10 0.176572E+10 0.873321E+10 0.258298E+10
November 0.631995E+10 0.447785E+10 0.184211E+10 0.933822E+10 0.361217E+10
December 0.725432E+10 0.552799E+10 0.172633E+10 0.107531E+11 0.412603E+10
           
Annual Sum or Average 0.522367E+11 0.285840E+11 0.236526E+11 0.769304E+11 0.362713E+11
Minimum of Months 0.213624E+10 0.125293E+09 0.172633E+10 0.261836E+10 0.192155E+10
Maximum of Months 0.725432E+10 0.552799E+10 0.221151E+10 0.107531E+11 0.412603E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.366399E+09 0.268990E+09 97408702.42 0.547443E+09 0.190690E+09
February 0.261416E+09 0.161756E+09 99660556.79 0.368858E+09 0.157519E+09
March 0.230832E+09 0.112443E+09 0.118389E+09 0.322133E+09 0.184624E+09
April 0.186798E+09 72197917.93 0.114600E+09 0.277470E+09 0.142171E+09
May 0.136003E+09 16470167.27 0.119533E+09 0.168420E+09 0.132428E+09
June 0.115465E+09 6772047.95 0.108693E+09 0.146872E+09 92376436.79
July 0.125829E+09 13455320.07 0.112374E+09 0.186262E+09 79171769.19
August 0.161609E+09 50218052.04 0.111391E+09 0.269592E+09 82222708.01
September 0.214763E+09 0.106692E+09 0.108071E+09 0.352676E+09 96023543.40
October 0.290591E+09 0.195153E+09 95437466.31 0.479028E+09 0.108479E+09
November 0.341593E+09 0.242027E+09 99566205.17 0.510562E+09 0.164021E+09
December 0.392095E+09 0.298787E+09 93308334.56 0.588660E+09 0.189849E+09
           
Annual Sum or Average 0.282339E+10 0.154496E+10 0.127843E+10 0.421798E+10 0.161958E+10
Minimum of Months 0.115465E+09 6772047.95 93308334.56 0.146872E+09 79171769.19
Maximum of Months 0.392095E+09 0.298787E+09 0.119533E+09 0.588660E+09 0.190690E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265521E+09 0.133901E+09 0.131620E+09 0.335088E+09 0.385677E+09
February 0.286426E+09 0.132386E+09 0.154039E+09 0.347315E+09 0.308886E+09
March 0.362688E+09 0.160278E+09 0.202410E+09 0.452778E+09 0.348625E+09
April 0.483730E+09 0.251482E+09 0.232247E+09 0.686767E+09 0.256736E+09
May 0.491022E+09 0.226458E+09 0.264564E+09 0.683428E+09 0.235218E+09
June 0.503264E+09 0.251292E+09 0.251972E+09 0.746276E+09 0.162065E+09
July 0.550654E+09 0.294353E+09 0.256300E+09 0.864328E+09 0.139204E+09
August 0.516705E+09 0.279782E+09 0.236923E+09 0.816778E+09 0.147306E+09
September 0.428535E+09 0.229221E+09 0.199314E+09 0.651472E+09 0.174349E+09
October 0.340146E+09 0.186368E+09 0.153778E+09 0.531467E+09 0.210970E+09
November 0.296219E+09 0.155051E+09 0.141168E+09 0.386780E+09 0.326722E+09
December 0.269240E+09 0.143959E+09 0.125281E+09 0.345506E+09 0.385228E+09
           
Annual Sum or Average 0.479415E+10 0.244453E+10 0.234962E+10 0.684798E+10 0.308099E+10
Minimum of Months 0.265521E+09 0.132386E+09 0.125281E+09 0.335088E+09 0.139204E+09
Maximum of Months 0.550654E+09 0.294353E+09 0.264564E+09 0.864328E+09 0.385677E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 55383852.68 0.00 55383852.68 40879352.62 0.204985E+09
February 62793579.01 0.00 62793579.01 41725259.44 0.166556E+09
March 85200912.64 780.17 85200132.47 66837596.60 0.189886E+09
April 95493362.34 768414.00 94724948.34 90129469.92 0.136672E+09
May 0.118708E+09 6190456.55 0.112517E+09 0.119095E+09 0.121319E+09
June 0.121773E+09 12029988.47 0.109743E+09 0.147962E+09 83836118.54
July 0.119193E+09 10114061.15 0.109079E+09 0.161844E+09 73237678.13
August 99102290.78 2201816.78 96900474.00 0.131135E+09 77513959.65
September 80955510.48 16100.43 80939410.05 97993518.69 94624226.53
October 66349884.71 0.00 66349884.71 90331331.74 0.112239E+09
November 58137116.95 0.00 58137116.95 45213912.07 0.175800E+09
December 51557659.69 0.00 51557659.69 37108207.11 0.205487E+09
           
Annual Sum or Average 0.101465E+10 31321617.54 0.983326E+09 0.107025E+10 0.164216E+10
Minimum of Months 51557659.69 0.00 51557659.69 37108207.11 73237678.13
Maximum of Months 0.121773E+09 12029988.47 0.112517E+09 0.161844E+09 0.205487E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265521E+09 0.133901E+09 0.131620E+09 0.352829E+09 0.373655E+09
February 0.286426E+09 0.132386E+09 0.154039E+09 0.359457E+09 0.301714E+09
March 0.362688E+09 0.160278E+09 0.202410E+09 0.463485E+09 0.343157E+09
April 0.483730E+09 0.251482E+09 0.232247E+09 0.694543E+09 0.253547E+09
May 0.491022E+09 0.226458E+09 0.264564E+09 0.685766E+09 0.234610E+09
June 0.503264E+09 0.251292E+09 0.251972E+09 0.746639E+09 0.162117E+09
July 0.550654E+09 0.294353E+09 0.256300E+09 0.865453E+09 0.138952E+09
August 0.516705E+09 0.279782E+09 0.236923E+09 0.821436E+09 0.145560E+09
September 0.428535E+09 0.229221E+09 0.199314E+09 0.659978E+09 0.170685E+09
October 0.340146E+09 0.186368E+09 0.153778E+09 0.542788E+09 0.205059E+09
November 0.296219E+09 0.155051E+09 0.141168E+09 0.401963E+09 0.317379E+09
December 0.269240E+09 0.143959E+09 0.125281E+09 0.363665E+09 0.372900E+09
           
Annual Sum or Average 0.479415E+10 0.244453E+10 0.234962E+10 0.695800E+10 0.301933E+10
Minimum of Months 0.265521E+09 0.132386E+09 0.125281E+09 0.352829E+09 0.138952E+09
Maximum of Months 0.550654E+09 0.294353E+09 0.264564E+09 0.865453E+09 0.373655E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.293061E+09 0.215149E+09 77911467.45 0.426815E+09 0.176991E+09
February 0.209091E+09 0.129379E+09 79712592.74 0.286147E+09 0.145779E+09
March 0.184629E+09 89936327.87 94692605.60 0.249664E+09 0.165457E+09
April 0.149409E+09 57746850.06 91662135.38 0.216660E+09 0.128785E+09
May 0.108781E+09 13173513.96 95607483.13 0.134177E+09 0.113226E+09
June 92353413.13 5416561.15 86936851.98 0.118283E+09 79375060.74
July 0.100643E+09 10762115.76 89881160.52 0.145950E+09 74180890.34
August 0.129262E+09 40166453.60 89095338.36 0.210647E+09 80337703.60
September 0.171776E+09 85336561.19 86439337.30 0.275965E+09 93865309.02
October 0.232427E+09 0.156092E+09 76334792.12 0.374927E+09 0.106591E+09
November 0.273220E+09 0.193583E+09 79637126.46 0.398129E+09 0.154706E+09
December 0.313614E+09 0.238982E+09 74631825.39 0.459444E+09 0.177618E+09
           
Annual Sum or Average 0.225827E+10 0.123572E+10 0.102254E+10 0.329681E+10 0.149691E+10
Minimum of Months 92353413.13 5416561.15 74631825.39 0.118283E+09 74180890.34
Maximum of Months 0.313614E+09 0.238982E+09 95607483.13 0.459444E+09 0.177618E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 44312955.30 0.00 44312955.30 34551159.78 0.164058E+09
February 50241522.13 0.00 50241522.13 35479383.49 0.133345E+09
March 68169765.21 624.22 68169140.99 56314143.45 0.152097E+09
April 76404816.42 614812.68 75790003.74 79991180.14 0.105868E+09
May 94978755.02 4953021.70 90025733.32 0.104063E+09 94355141.15
June 97431324.50 9625266.49 87806058.00 0.129083E+09 63698431.68
July 95367114.15 8092321.46 87274792.68 0.142427E+09 53866852.02
August 79292341.88 1761686.91 77530654.97 0.117261E+09 56321320.55
September 64772993.27 12882.05 64760111.22 87573164.77 69977794.95
October 53086943.81 0.00 53086943.81 79735594.50 84938642.90
November 46515858.69 0.00 46515858.69 39468909.35 0.138134E+09
December 41251595.16 0.00 41251595.16 31986376.18 0.163551E+09
           
Annual Sum or Average 0.811826E+09 25060615.52 0.786765E+09 0.937933E+09 0.128021E+10
Minimum of Months 41251595.16 0.00 41251595.16 31986376.18 53866852.02
Maximum of Months 97431324.50 9625266.49 90025733.32 0.142427E+09 0.164058E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.278642E+09 0.148882E+09 0.129760E+09 0.340684E+09 0.365816E+09
February 0.265576E+09 0.121526E+09 0.144050E+09 0.302716E+09 0.295650E+09
March 0.358848E+09 0.160278E+09 0.198570E+09 0.434748E+09 0.332981E+09
April 0.442664E+09 0.222110E+09 0.220555E+09 0.614519E+09 0.246085E+09
May 0.430846E+09 0.179547E+09 0.251299E+09 0.584541E+09 0.227445E+09
June 0.414835E+09 0.180091E+09 0.234745E+09 0.607106E+09 0.160251E+09
July 0.485425E+09 0.241161E+09 0.244264E+09 0.762424E+09 0.139063E+09
August 0.479775E+09 0.254984E+09 0.224791E+09 0.759565E+09 0.143797E+09
September 0.338985E+09 0.155919E+09 0.183066E+09 0.506636E+09 0.170431E+09
October 0.308711E+09 0.158449E+09 0.150261E+09 0.472433E+09 0.200944E+09
November 0.271708E+09 0.137555E+09 0.134153E+09 0.335289E+09 0.313526E+09
December 0.269909E+09 0.150433E+09 0.119475E+09 0.328497E+09 0.365505E+09
           
Annual Sum or Average 0.434593E+10 0.211093E+10 0.223499E+10 0.604916E+10 0.296149E+10
Minimum of Months 0.265576E+09 0.121526E+09 0.119475E+09 0.302716E+09 0.139063E+09
Maximum of Months 0.485425E+09 0.254984E+09 0.251299E+09 0.762424E+09 0.365816E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.366399E+09 0.268990E+09 97408702.42 0.544900E+09 0.190112E+09
February 0.261416E+09 0.161756E+09 99660556.79 0.367503E+09 0.156066E+09
March 0.230832E+09 0.112443E+09 0.118389E+09 0.319616E+09 0.183152E+09
April 0.186798E+09 72197917.93 0.114600E+09 0.274562E+09 0.139716E+09
May 0.136003E+09 16470167.27 0.119533E+09 0.166461E+09 0.129664E+09
June 0.115465E+09 6772047.95 0.108693E+09 0.145508E+09 89461690.52
July 0.125829E+09 13455320.07 0.112374E+09 0.183950E+09 76435453.34
August 0.161609E+09 50218052.04 0.111391E+09 0.267166E+09 79796698.52
September 0.214763E+09 0.106692E+09 0.108071E+09 0.352234E+09 93011001.67
October 0.290591E+09 0.195153E+09 95437466.31 0.477776E+09 0.106911E+09
November 0.341593E+09 0.242027E+09 99566205.17 0.509297E+09 0.162417E+09
December 0.392095E+09 0.298787E+09 93308334.56 0.586721E+09 0.188727E+09
           
Annual Sum or Average 0.282339E+10 0.154496E+10 0.127843E+10 0.419569E+10 0.159547E+10
Minimum of Months 0.115465E+09 6772047.95 93308334.56 0.145508E+09 76435453.34
Maximum of Months 0.392095E+09 0.298787E+09 0.119533E+09 0.586721E+09 0.190112E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 55383852.68 0.00 55383852.68 39016850.52 0.203781E+09
February 62793579.01 0.00 62793579.01 40574992.43 0.164616E+09
March 85200912.64 780.17 85200132.47 64497719.60 0.188463E+09
April 95493362.34 768414.00 94724948.34 87392142.67 0.134614E+09
May 0.118708E+09 6190456.55 0.112517E+09 0.117655E+09 0.119099E+09
June 0.121773E+09 12029988.47 0.109743E+09 0.147437E+09 81762142.35
July 0.119193E+09 10114061.15 0.109079E+09 0.160136E+09 71196587.38
August 99102290.78 2201816.78 96900474.00 0.128478E+09 75425538.95
September 80955510.48 16100.43 80939410.05 97387628.23 91467756.20
October 66349884.71 0.00 66349884.71 88830516.28 0.110683E+09
November 58137116.95 0.00 58137116.95 44244676.37 0.172895E+09
December 51557659.69 0.00 51557659.69 35575860.18 0.203388E+09
           
Annual Sum or Average 0.101465E+10 31321617.54 0.983326E+09 0.105123E+10 0.161739E+10
Minimum of Months 51557659.69 0.00 51557659.69 35575860.18 71196587.38
Maximum of Months 0.121773E+09 12029988.47 0.112517E+09 0.160136E+09 0.203781E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.278642E+09 0.148882E+09 0.129760E+09 0.357611E+09 0.350976E+09
February 0.265576E+09 0.121526E+09 0.144050E+09 0.314782E+09 0.287007E+09
March 0.358848E+09 0.160278E+09 0.198570E+09 0.444996E+09 0.326780E+09
April 0.442664E+09 0.222110E+09 0.220555E+09 0.621727E+09 0.242632E+09
May 0.430846E+09 0.179547E+09 0.251299E+09 0.586844E+09 0.226753E+09
June 0.414835E+09 0.180091E+09 0.234745E+09 0.607416E+09 0.160412E+09
July 0.485425E+09 0.241161E+09 0.244264E+09 0.763325E+09 0.138871E+09
August 0.479775E+09 0.254984E+09 0.224791E+09 0.763231E+09 0.141983E+09
September 0.338985E+09 0.155919E+09 0.183066E+09 0.514714E+09 0.166270E+09
October 0.308711E+09 0.158449E+09 0.150261E+09 0.483083E+09 0.194629E+09
November 0.271708E+09 0.137555E+09 0.134153E+09 0.350507E+09 0.301032E+09
December 0.269909E+09 0.150433E+09 0.119475E+09 0.346163E+09 0.350105E+09
           
Annual Sum or Average 0.434593E+10 0.211093E+10 0.223499E+10 0.615440E+10 0.288745E+10
Minimum of Months 0.265576E+09 0.121526E+09 0.119475E+09 0.314782E+09 0.138871E+09
Maximum of Months 0.485425E+09 0.254984E+09 0.251299E+09 0.763325E+09 0.350976E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70140154.89 0.00 70140154.89 44469712.19 0.289150E+09
February 79524105.76 0.00 79524105.76 47117711.47 0.236283E+09
March 0.107902E+09 988.04 0.107901E+09 80850130.82 0.261980E+09
April 0.120936E+09 973147.84 0.119963E+09 0.115076E+09 0.189994E+09
May 0.150336E+09 7839822.62 0.142496E+09 0.151588E+09 0.169745E+09
June 0.154218E+09 15235221.35 0.138983E+09 0.188679E+09 0.121203E+09
July 0.150951E+09 12808820.29 0.138142E+09 0.204858E+09 0.109906E+09
August 0.125507E+09 2788462.02 0.122718E+09 0.163606E+09 0.119076E+09
September 0.102525E+09 20390.18 0.102505E+09 0.121094E+09 0.141898E+09
October 84027942.54 0.00 84027942.54 0.106808E+09 0.173211E+09
November 73626990.37 0.00 73626990.37 49865746.94 0.253043E+09
December 65294522.88 0.00 65294522.88 38454870.69 0.294829E+09
           
Annual Sum or Average 0.128499E+10 39666852.34 0.124532E+10 0.131247E+10 0.236032E+10
Minimum of Months 65294522.88 0.00 65294522.88 38454870.69 0.109906E+09
Maximum of Months 0.154218E+09 15235221.35 0.142496E+09 0.204858E+09 0.294829E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 25856565.37 0.00 25856565.37 16393377.26 0.106593E+09
February 29315878.22 0.00 29315878.22 17369539.44 87103579.25
March 39776990.23 364.23 39776626.00 29804705.96 96576705.26
April 44582134.43 358742.59 44223391.84 42421744.98 70039535.57
May 55420009.14 2890083.24 52529925.90 55881431.30 62575151.47
June 56851080.99 5616333.43 51234747.56 69554882.22 44680626.36
July 55646616.31 4721861.53 50924754.78 75519049.39 40515959.26
August 46267002.67 1027942.56 45239060.11 60312085.66 43896260.02
September 37794977.19 7516.66 37787460.52 44640222.71 52309654.41
October 30976178.94 0.00 30976178.94 39373963.15 63852770.35
November 27141957.31 0.00 27141957.31 18382579.10 93282191.46
December 24070264.77 0.00 24070264.77 14176057.63 0.108686E+09
           
Annual Sum or Average 0.473700E+09 14622844.25 0.459077E+09 0.483830E+09 0.870111E+09
Minimum of Months 24070264.77 0.00 24070264.77 14176057.63 40515959.26
Maximum of Months 56851080.99 5616333.43 52529925.90 75519049.39 0.108686E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.170960E+09 0.125510E+09 45450508.02 0.256421E+09 95820919.47
February 0.121976E+09 75474510.52 46501214.20 0.172335E+09 80403566.33
March 0.107705E+09 52465342.08 55239968.79 0.151069E+09 92468866.80
April 87159368.36 33687257.57 53472110.79 0.131307E+09 71654053.12
May 63458586.31 7684913.68 55773672.63 79411705.14 67664574.99
June 53875375.24 3159810.28 50715564.96 69086419.50 48789043.64
July 58711357.72 6278198.12 52433159.60 87225812.04 43430841.98
August 75406282.36 23431540.72 51974741.64 0.125872E+09 45772913.97
September 0.100207E+09 49782017.80 50425334.32 0.165031E+09 51983615.81
October 0.135589E+09 91057819.93 44530737.20 0.222581E+09 59995149.62
November 0.159386E+09 0.112929E+09 46457190.11 0.238499E+09 84422102.65
December 0.182950E+09 0.139413E+09 43537292.90 0.274973E+09 96675199.21
           
Annual Sum or Average 0.131738E+10 0.720873E+09 0.596511E+09 0.197381E+10 0.839081E+09
Minimum of Months 53875375.24 3159810.28 43537292.90 69086419.50 43430841.98
Maximum of Months 0.182950E+09 0.139413E+09 55773672.63 0.274973E+09 96675199.21



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.464021E+09 0.340659E+09 0.123362E+09 0.695980E+09 0.260078E+09
February 0.331067E+09 0.204853E+09 0.126214E+09 0.467753E+09 0.218232E+09
March 0.292334E+09 0.142402E+09 0.149933E+09 0.410032E+09 0.250979E+09
April 0.236568E+09 91434107.63 0.145134E+09 0.356394E+09 0.194484E+09
May 0.172240E+09 20858427.64 0.151381E+09 0.215540E+09 0.183655E+09
June 0.146229E+09 8576371.43 0.137652E+09 0.187515E+09 0.132423E+09
July 0.159355E+09 17040313.89 0.142314E+09 0.236749E+09 0.117880E+09
August 0.204668E+09 63597994.32 0.141070E+09 0.341643E+09 0.124237E+09
September 0.271983E+09 0.135119E+09 0.136865E+09 0.447927E+09 0.141094E+09
October 0.368015E+09 0.247150E+09 0.120866E+09 0.604130E+09 0.162839E+09
November 0.432606E+09 0.306511E+09 0.126094E+09 0.647334E+09 0.229139E+09
December 0.496564E+09 0.378395E+09 0.118169E+09 0.746333E+09 0.262396E+09
           
Annual Sum or Average 0.357565E+10 0.195660E+10 0.161905E+10 0.535733E+10 0.227744E+10
Minimum of Months 0.146229E+09 8576371.43 0.118169E+09 0.187515E+09 0.117880E+09
Maximum of Months 0.496564E+09 0.378395E+09 0.151381E+09 0.746333E+09 0.262396E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.366399E+09 0.268990E+09 97408702.42 0.545428E+09 0.187611E+09
February 0.261416E+09 0.161756E+09 99660556.79 0.366391E+09 0.154660E+09
March 0.230832E+09 0.112443E+09 0.118389E+09 0.319631E+09 0.182491E+09
April 0.186798E+09 72197917.93 0.114600E+09 0.273942E+09 0.140657E+09
May 0.136003E+09 16470167.27 0.119533E+09 0.165606E+09 0.131094E+09
June 0.115465E+09 6772047.95 0.108693E+09 0.144254E+09 91330799.31
July 0.125829E+09 13455320.07 0.112374E+09 0.183377E+09 78141391.98
August 0.161609E+09 50218052.04 0.111391E+09 0.266318E+09 80985843.26
September 0.214763E+09 0.106692E+09 0.108071E+09 0.349271E+09 94306710.45
October 0.290591E+09 0.195153E+09 95437466.31 0.476193E+09 0.105919E+09
November 0.341593E+09 0.242027E+09 99566205.17 0.507931E+09 0.160980E+09
December 0.392095E+09 0.298787E+09 93308334.56 0.586447E+09 0.186197E+09
           
Annual Sum or Average 0.282339E+10 0.154496E+10 0.127843E+10 0.418479E+10 0.159438E+10
Minimum of Months 0.115465E+09 6772047.95 93308334.56 0.144254E+09 78141391.98
Maximum of Months 0.392095E+09 0.298787E+09 0.119533E+09 0.586447E+09 0.187611E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265521E+09 0.133901E+09 0.131620E+09 0.332501E+09 0.378077E+09
February 0.286426E+09 0.132386E+09 0.154039E+09 0.344294E+09 0.302292E+09
March 0.362688E+09 0.160278E+09 0.202410E+09 0.447438E+09 0.343495E+09
April 0.483730E+09 0.251482E+09 0.232247E+09 0.677172E+09 0.253413E+09
May 0.491022E+09 0.226458E+09 0.264564E+09 0.673528E+09 0.232180E+09
June 0.503264E+09 0.251292E+09 0.251972E+09 0.735300E+09 0.159734E+09
July 0.550654E+09 0.294353E+09 0.256300E+09 0.853400E+09 0.136847E+09
August 0.516705E+09 0.279782E+09 0.236923E+09 0.806741E+09 0.144674E+09
September 0.428535E+09 0.229221E+09 0.199314E+09 0.643517E+09 0.170864E+09
October 0.340146E+09 0.186368E+09 0.153778E+09 0.527364E+09 0.205465E+09
November 0.296219E+09 0.155051E+09 0.141168E+09 0.383806E+09 0.319521E+09
December 0.269240E+09 0.143959E+09 0.125281E+09 0.343805E+09 0.376364E+09
           
Annual Sum or Average 0.479415E+10 0.244453E+10 0.234962E+10 0.676887E+10 0.302293E+10
Minimum of Months 0.265521E+09 0.132386E+09 0.125281E+09 0.332501E+09 0.136847E+09
Maximum of Months 0.550654E+09 0.294353E+09 0.264564E+09 0.853400E+09 0.378077E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 55383852.68 0.00 55383852.68 42374082.82 0.199873E+09
February 62793579.01 0.00 62793579.01 42874063.21 0.162411E+09
March 85200912.64 780.17 85200132.47 66947056.03 0.186837E+09
April 95493362.34 768414.00 94724948.34 88591339.77 0.134813E+09
May 0.118708E+09 6190456.55 0.112517E+09 0.117107E+09 0.119854E+09
June 0.121773E+09 12029988.47 0.109743E+09 0.145029E+09 82749008.62
July 0.119193E+09 10114061.15 0.109079E+09 0.158984E+09 72102656.48
August 99102290.78 2201816.78 96900474.00 0.129179E+09 76189431.27
September 80955510.48 16100.43 80939410.05 96968982.63 92638789.55
October 66349884.71 0.00 66349884.71 91096245.70 0.108832E+09
November 58137116.95 0.00 58137116.95 46766288.08 0.170972E+09
December 51557659.69 0.00 51557659.69 39170450.41 0.199471E+09
           
Annual Sum or Average 0.101465E+10 31321617.54 0.983326E+09 0.106509E+10 0.160674E+10
Minimum of Months 51557659.69 0.00 51557659.69 39170450.41 72102656.48
Maximum of Months 0.121773E+09 12029988.47 0.112517E+09 0.158984E+09 0.199873E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265521E+09 0.133901E+09 0.131620E+09 0.352911E+09 0.364279E+09
February 0.286426E+09 0.132386E+09 0.154039E+09 0.358257E+09 0.294036E+09
March 0.362688E+09 0.160278E+09 0.202410E+09 0.459276E+09 0.337405E+09
April 0.483730E+09 0.251482E+09 0.232247E+09 0.685468E+09 0.249826E+09
May 0.491022E+09 0.226458E+09 0.264564E+09 0.675922E+09 0.231536E+09
June 0.503264E+09 0.251292E+09 0.251972E+09 0.735602E+09 0.159811E+09
July 0.550654E+09 0.294353E+09 0.256300E+09 0.854462E+09 0.136602E+09
August 0.516705E+09 0.279782E+09 0.236923E+09 0.811425E+09 0.142800E+09
September 0.428535E+09 0.229221E+09 0.199314E+09 0.652565E+09 0.166752E+09
October 0.340146E+09 0.186368E+09 0.153778E+09 0.539975E+09 0.198671E+09
November 0.296219E+09 0.155051E+09 0.141168E+09 0.401515E+09 0.308470E+09
December 0.269240E+09 0.143959E+09 0.125281E+09 0.365035E+09 0.362007E+09
           
Annual Sum or Average 0.479415E+10 0.244453E+10 0.234962E+10 0.689241E+10 0.295220E+10
Minimum of Months 0.265521E+09 0.132386E+09 0.125281E+09 0.352911E+09 0.136602E+09
Maximum of Months 0.550654E+09 0.294353E+09 0.264564E+09 0.854462E+09 0.364279E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.537359E+09 0.394500E+09 0.142859E+09 0.785049E+09 0.288115E+09
February 0.383392E+09 0.237230E+09 0.146162E+09 0.527555E+09 0.235349E+09
March 0.338537E+09 0.164908E+09 0.173629E+09 0.461381E+09 0.273563E+09
April 0.273958E+09 0.105885E+09 0.168073E+09 0.401984E+09 0.203945E+09
May 0.199462E+09 24155080.95 0.175307E+09 0.248840E+09 0.186757E+09
June 0.169340E+09 9931858.23 0.159408E+09 0.220768E+09 0.126946E+09
July 0.184540E+09 19733518.19 0.164807E+09 0.279191E+09 0.106775E+09
August 0.237016E+09 73649592.75 0.163366E+09 0.396779E+09 0.112791E+09
September 0.314970E+09 0.156474E+09 0.158496E+09 0.512642E+09 0.135868E+09
October 0.426179E+09 0.286211E+09 0.139968E+09 0.693542E+09 0.158040E+09
November 0.500979E+09 0.354955E+09 0.146023E+09 0.733428E+09 0.245506E+09
December 0.575045E+09 0.438199E+09 0.136846E+09 0.845019E+09 0.286005E+09
           
Annual Sum or Average 0.414078E+10 0.226583E+10 0.187494E+10 0.610618E+10 0.235966E+10
Minimum of Months 0.169340E+09 9931858.23 0.136846E+09 0.220768E+09 0.106775E+09
Maximum of Months 0.575045E+09 0.438199E+09 0.175307E+09 0.845019E+09 0.288115E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.387672E+09 0.00 0.387672E+09 0.182644E+09 0.181250E+10
February 0.439538E+09 0.00 0.439538E+09 0.188423E+09 0.151778E+10
March 0.596384E+09 5460.98 0.596378E+09 0.334129E+09 0.169546E+10
April 0.668428E+09 5378694.26 0.663050E+09 0.497526E+09 0.122357E+10
May 0.830922E+09 43331554.67 0.787591E+09 0.656108E+09 0.109047E+10
June 0.852379E+09 84206730.00 0.768172E+09 0.864624E+09 0.785539E+09
July 0.834320E+09 70795746.72 0.763524E+09 0.975367E+09 0.697611E+09
August 0.693690E+09 15412133.73 0.678278E+09 0.778304E+09 0.753555E+09
September 0.566667E+09 112698.72 0.566554E+09 0.568867E+09 0.898964E+09
October 0.464432E+09 0.00 0.464432E+09 0.520426E+09 0.106983E+10
November 0.406944E+09 0.00 0.406944E+09 0.213899E+09 0.156706E+10
December 0.360890E+09 0.00 0.360890E+09 0.161409E+09 0.181554E+10
           
Annual Sum or Average 0.710227E+10 0.219243E+09 0.688302E+10 0.594173E+10 0.149279E+11
Minimum of Months 0.360890E+09 0.00 0.360890E+09 0.161409E+09 0.697611E+09
Maximum of Months 0.852379E+09 84206730.00 0.787591E+09 0.975367E+09 0.181554E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.387672E+09 0.00 0.387672E+09 0.163275E+09 0.187114E+10
February 0.439538E+09 0.00 0.439538E+09 0.168285E+09 0.157001E+10
March 0.596384E+09 5460.98 0.596378E+09 0.305947E+09 0.174941E+10
April 0.668428E+09 5378694.26 0.663050E+09 0.466747E+09 0.125914E+10
May 0.830922E+09 43331554.67 0.787591E+09 0.618911E+09 0.112035E+10
June 0.852379E+09 84206730.00 0.768172E+09 0.831315E+09 0.808932E+09
July 0.834320E+09 70795746.72 0.763524E+09 0.944949E+09 0.718414E+09
August 0.693690E+09 15412133.73 0.678278E+09 0.750805E+09 0.777182E+09
September 0.566667E+09 112698.72 0.566554E+09 0.544091E+09 0.928394E+09
October 0.464432E+09 0.00 0.464432E+09 0.497714E+09 0.110341E+10
November 0.406944E+09 0.00 0.406944E+09 0.193481E+09 0.161584E+10
December 0.360890E+09 0.00 0.360890E+09 0.143822E+09 0.187287E+10
           
Annual Sum or Average 0.710227E+10 0.219243E+09 0.688302E+10 0.562934E+10 0.153951E+11
Minimum of Months 0.360890E+09 0.00 0.360890E+09 0.143822E+09 0.718414E+09
Maximum of Months 0.852379E+09 84206730.00 0.787591E+09 0.944949E+09 0.187287E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 55383852.68 0.00 55383852.68 40219697.27 0.235382E+09
February 62793579.01 0.00 62793579.01 39516138.32 0.201506E+09
March 85200912.64 780.17 85200132.47 65644869.65 0.227047E+09
April 95493362.34 768414.00 94724948.34 97237095.50 0.165598E+09
May 0.118708E+09 6190456.55 0.112517E+09 0.128462E+09 0.151907E+09
June 0.121773E+09 12029988.47 0.109743E+09 0.162459E+09 0.110644E+09
July 0.119193E+09 10114061.15 0.109079E+09 0.182056E+09 98993295.20
August 99102290.78 2201816.78 96900474.00 0.149550E+09 0.105062E+09
September 80955510.48 16100.43 80939410.05 0.110667E+09 0.117618E+09
October 66349884.71 0.00 66349884.71 0.100726E+09 0.138678E+09
November 58137116.95 0.00 58137116.95 46274472.91 0.203267E+09
December 51557659.69 0.00 51557659.69 36874386.79 0.235915E+09
           
Annual Sum or Average 0.101465E+10 31321617.54 0.983326E+09 0.115969E+10 0.199162E+10
Minimum of Months 51557659.69 0.00 51557659.69 36874386.79 98993295.20
Maximum of Months 0.121773E+09 12029988.47 0.112517E+09 0.182056E+09 0.235915E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.557245E+09 0.297743E+09 0.259502E+09 0.724871E+09 0.820807E+09
February 0.531115E+09 0.243035E+09 0.288080E+09 0.624275E+09 0.711950E+09
March 0.717645E+09 0.320532E+09 0.397113E+09 0.895167E+09 0.797618E+09
April 0.885266E+09 0.444188E+09 0.441078E+09 0.128672E+10 0.602031E+09
May 0.861631E+09 0.359068E+09 0.502562E+09 0.121512E+10 0.574775E+09
June 0.829612E+09 0.360156E+09 0.469456E+09 0.127555E+10 0.429563E+09
July 0.970781E+09 0.482287E+09 0.488494E+09 0.161383E+10 0.383575E+09
August 0.959482E+09 0.509932E+09 0.449550E+09 0.160938E+10 0.395959E+09
September 0.677922E+09 0.311816E+09 0.366105E+09 0.108566E+10 0.434057E+09
October 0.617378E+09 0.316876E+09 0.300501E+09 0.101583E+10 0.496519E+09
November 0.543378E+09 0.275091E+09 0.268287E+09 0.710202E+09 0.716159E+09
December 0.539779E+09 0.300845E+09 0.238934E+09 0.698193E+09 0.821319E+09
           
Annual Sum or Average 0.869123E+10 0.422157E+10 0.446966E+10 0.127548E+11 0.718433E+10
Minimum of Months 0.531115E+09 0.243035E+09 0.238934E+09 0.624275E+09 0.383575E+09
Maximum of Months 0.970781E+09 0.509932E+09 0.502562E+09 0.161383E+10 0.821319E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.366399E+09 0.268990E+09 97408702.42 0.561831E+09 0.215313E+09
February 0.261416E+09 0.161756E+09 99660556.79 0.375445E+09 0.189520E+09
March 0.230832E+09 0.112443E+09 0.118389E+09 0.328486E+09 0.219541E+09
April 0.186798E+09 72197917.93 0.114600E+09 0.290266E+09 0.169106E+09
May 0.136003E+09 16470167.27 0.119533E+09 0.178106E+09 0.162353E+09
June 0.115465E+09 6772047.95 0.108693E+09 0.161738E+09 0.118752E+09
July 0.125829E+09 13455320.07 0.112374E+09 0.207706E+09 0.104321E+09
August 0.161609E+09 50218052.04 0.111391E+09 0.291592E+09 0.108202E+09
September 0.214763E+09 0.106692E+09 0.108071E+09 0.372504E+09 0.117496E+09
October 0.290591E+09 0.195153E+09 95437466.31 0.498814E+09 0.132996E+09
November 0.341593E+09 0.242027E+09 99566205.17 0.524687E+09 0.187985E+09
December 0.392095E+09 0.298787E+09 93308334.56 0.603339E+09 0.214564E+09
           
Annual Sum or Average 0.282339E+10 0.154496E+10 0.127843E+10 0.439451E+10 0.194015E+10
Minimum of Months 0.115465E+09 6772047.95 93308334.56 0.161738E+09 0.104321E+09
Maximum of Months 0.392095E+09 0.298787E+09 0.119533E+09 0.603339E+09 0.219541E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70140154.89 0.00 70140154.89 40342938.04 0.288472E+09
February 79524105.76 0.00 79524105.76 43415630.38 0.234685E+09
March 0.107902E+09 988.04 0.107901E+09 74319581.64 0.263310E+09
April 0.120936E+09 973147.84 0.119963E+09 0.105408E+09 0.192789E+09
May 0.150336E+09 7839822.62 0.142496E+09 0.141285E+09 0.171783E+09
June 0.154218E+09 15235221.35 0.138983E+09 0.175696E+09 0.124961E+09
July 0.150951E+09 12808820.29 0.138142E+09 0.190736E+09 0.114260E+09
August 0.125507E+09 2788462.02 0.122718E+09 0.151061E+09 0.124010E+09
September 0.102525E+09 20390.18 0.102505E+09 0.112287E+09 0.144975E+09
October 84027942.54 0.00 84027942.54 0.100638E+09 0.174243E+09
November 73626990.37 0.00 73626990.37 46360462.08 0.250049E+09
December 65294522.88 0.00 65294522.88 35543386.15 0.290216E+09
           
Annual Sum or Average 0.128499E+10 39666852.34 0.124532E+10 0.121709E+10 0.237375E+10
Minimum of Months 65294522.88 0.00 65294522.88 35543386.15 0.114260E+09
Maximum of Months 0.154218E+09 15235221.35 0.142496E+09 0.190736E+09 0.290216E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62754662.34 0.00 62754662.34 36094979.53 0.258073E+09
February 71150518.74 0.00 71150518.74 38844129.00 0.209974E+09
March 96539952.45 884.00 96539068.45 66494011.29 0.235584E+09
April 0.108202E+09 870679.06 0.107332E+09 94308501.62 0.172489E+09
May 0.134506E+09 7014319.00 0.127492E+09 0.126408E+09 0.153695E+09
June 0.137979E+09 13631010.27 0.124348E+09 0.157196E+09 0.111803E+09
July 0.135056E+09 11460100.04 0.123596E+09 0.170652E+09 0.102229E+09
August 0.112291E+09 2494847.54 0.109797E+09 0.135155E+09 0.110952E+09
September 91729547.13 18243.17 91711303.96 0.100463E+09 0.129709E+09
October 75180118.57 0.00 75180118.57 90041610.31 0.155896E+09
November 65874347.26 0.00 65874347.26 41478881.08 0.223717E+09
December 58419257.03 0.00 58419257.03 31800802.26 0.259623E+09
           
Annual Sum or Average 0.114968E+10 35490083.08 0.111419E+10 0.108894E+10 0.212375E+10
Minimum of Months 58419257.03 0.00 58419257.03 31800802.26 0.102229E+09
Maximum of Months 0.137979E+09 13631010.27 0.127492E+09 0.170652E+09 0.259623E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.136788E+10 0.100422E+10 0.363656E+09 0.202698E+10 0.765359E+09
February 0.975944E+09 0.603882E+09 0.372063E+09 0.135572E+10 0.640570E+09
March 0.861765E+09 0.419782E+09 0.441983E+09 0.117982E+10 0.746092E+09
April 0.697374E+09 0.269536E+09 0.427838E+09 0.101583E+10 0.583786E+09
May 0.507741E+09 61488042.30 0.446253E+09 0.603143E+09 0.551184E+09
June 0.431064E+09 25282072.96 0.405782E+09 0.517131E+09 0.405133E+09
July 0.469758E+09 50232719.31 0.419525E+09 0.657848E+09 0.364085E+09
August 0.603336E+09 0.187479E+09 0.415857E+09 0.966585E+09 0.383257E+09
September 0.801773E+09 0.398313E+09 0.403460E+09 0.128652E+10 0.425726E+09
October 0.108486E+10 0.728566E+09 0.356297E+09 0.175109E+10 0.484246E+09
November 0.127527E+10 0.903557E+09 0.371710E+09 0.188513E+10 0.668712E+09
December 0.146381E+10 0.111546E+10 0.348348E+09 0.217866E+10 0.762773E+09
           
Annual Sum or Average 0.105406E+11 0.576780E+10 0.477277E+10 0.154245E+11 0.678092E+10
Minimum of Months 0.431064E+09 25282072.96 0.348348E+09 0.517131E+09 0.364085E+09
Maximum of Months 0.146381E+10 0.111546E+10 0.446253E+09 0.217866E+10 0.765359E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1013.94 373.46 691.88 507.95 183.94 0.00 0.00
February 763.99 337.07 546.53 338.18 208.36 0.00 0.00
March 605.99 347.96 435.89 212.33 223.56 0.00 0.00
April 542.22 280.09 364.49 140.88 223.62 0.00 0.00
May 327.90 245.67 256.82 31.10 225.72 0.00 0.00
June 293.07 184.04 225.30 13.21 212.09 0.00 0.00
July 349.63 162.48 237.61 25.41 212.20 0.00 0.00
August 498.67 175.84 305.17 94.83 210.34 0.00 0.00
September 675.38 209.46 419.06 208.19 210.87 0.00 0.00
October 885.12 232.74 548.73 368.52 180.22 0.00 0.00
November 980.08 335.96 666.54 472.26 194.28 0.00 0.00
December 1091.06 374.85 740.41 564.21 176.20 0.00 0.00
               
Annual Sum or Average 668.65 271.31 452.81 247.78 205.03 0.00 0.00
Minimum of Months 293.07 162.48 225.30 13.21 176.20 0.00 0.00
Maximum of Months 1091.06 374.85 740.41 564.21 225.72 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2808.08 1157.01 1948.30 1430.34 517.96 0.00 0.00
February 2104.50 1058.24 1539.00 952.28 586.71 0.00 0.00
March 1660.39 1086.04 1227.43 597.91 629.52 0.00 0.00
April 1483.29 885.12 1026.39 396.71 629.69 0.00 0.00
May 875.61 783.29 723.18 87.58 635.60 0.00 0.00
June 779.47 598.20 634.43 37.21 597.22 0.00 0.00
July 947.97 520.58 669.08 71.55 597.53 0.00 0.00
August 1374.21 557.46 859.34 267.03 592.31 0.00 0.00
September 1869.41 662.96 1180.05 586.24 593.81 0.00 0.00
October 2456.53 728.55 1545.20 1037.72 507.48 0.00 0.00
November 2712.38 1047.70 1876.94 1329.86 547.08 0.00 0.00
December 3024.40 1159.93 2084.94 1588.78 496.16 0.00 0.00
               
Annual Sum or Average 1840.62 852.68 1275.09 697.73 577.36 0.00 0.00
Minimum of Months 779.47 520.58 634.43 37.21 496.16 0.00 0.00
Maximum of Months 3024.40 1159.93 2084.94 1588.78 635.60 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3731.62 1537.79 2530.95 1858.09 672.86 0.00 0.00
February 2793.00 1428.32 1999.24 1237.07 762.17 0.00 0.00
March 2200.09 1477.68 1594.50 776.72 817.79 0.00 0.00
April 1969.84 1202.48 1333.34 515.34 818.00 0.00 0.00
May 1140.21 1089.34 939.45 113.77 825.68 0.00 0.00
June 1010.17 834.52 824.17 48.34 775.83 0.00 0.00
July 1245.24 717.42 869.17 92.94 776.23 0.00 0.00
August 1828.01 748.67 1116.33 346.89 769.44 0.00 0.00
September 2489.18 884.95 1532.95 761.56 771.39 0.00 0.00
October 3260.61 964.37 2007.30 1348.05 659.24 0.00 0.00
November 3602.71 1393.58 2438.25 1727.56 710.69 0.00 0.00
December 4014.76 1540.48 2708.45 2063.92 644.54 0.00 0.00
               
Annual Sum or Average 2439.45 1150.16 1656.41 906.39 750.02 0.00 0.00
Minimum of Months 1010.17 717.42 824.17 48.34 644.54 0.00 0.00
Maximum of Months 4014.76 1540.48 2708.45 2063.92 825.68 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 323.04 208.73 235.93 150.42 85.51 0.00 0.00
February 292.54 189.30 226.46 121.59 104.87 0.00 0.00
March 286.88 196.66 221.59 101.82 119.77 0.00 0.00
April 370.09 151.98 258.69 124.88 133.81 0.00 0.00
May 316.01 135.23 234.10 90.70 143.41 0.00 0.00
June 342.54 96.13 238.71 99.56 139.15 0.00 0.00
July 390.68 79.97 252.57 114.92 137.65 0.00 0.00
August 404.47 84.56 253.25 123.21 130.05 0.00 0.00
September 386.21 103.11 248.19 129.60 118.59 0.00 0.00
October 375.70 117.69 235.49 142.44 93.05 0.00 0.00
November 341.66 184.80 246.07 153.19 92.88 0.00 0.00
December 341.49 207.42 246.91 165.30 81.61 0.00 0.00
               
Annual Sum or Average 347.93 146.08 241.55 126.51 115.04 0.00 0.00
Minimum of Months 286.88 79.97 221.59 90.70 81.61 0.00 0.00
Maximum of Months 404.47 208.73 258.69 165.30 143.41 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 145.02 214.07 119.81 49.99 69.82 0.00 0.00
February 163.80 191.53 144.35 54.72 89.63 0.00 0.00
March 195.84 196.85 167.22 59.84 107.38 0.00 0.00
April 301.71 149.53 223.47 97.32 126.15 0.00 0.00
May 299.33 131.72 227.65 86.86 140.79 0.00 0.00
June 344.14 93.89 241.14 101.59 139.55 0.00 0.00
July 382.96 78.64 250.09 113.68 136.42 0.00 0.00
August 355.14 82.77 229.92 105.28 124.64 0.00 0.00
September 291.23 101.16 196.56 88.44 108.12 0.00 0.00
October 235.54 117.62 151.77 69.58 82.19 0.00 0.00
November 170.22 187.97 136.71 59.82 76.89 0.00 0.00
December 147.42 213.73 119.77 53.75 66.02 0.00 0.00
               
Annual Sum or Average 253.16 146.40 184.20 78.51 105.69 0.00 0.00
Minimum of Months 145.02 78.64 119.77 49.99 66.02 0.00 0.00
Maximum of Months 382.96 214.07 250.09 113.68 140.79 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 159.35 66.08 109.42 80.33 29.09 0.00 0.00
February 118.28 60.26 86.43 53.48 32.95 0.00 0.00
March 93.21 61.77 68.93 33.58 35.35 0.00 0.00
April 83.59 49.69 57.64 22.28 35.36 0.00 0.00
May 50.10 42.27 40.61 4.92 35.70 0.00 0.00
June 45.63 30.62 35.63 2.09 33.54 0.00 0.00
July 54.49 27.70 37.58 4.02 33.56 0.00 0.00
August 78.65 29.99 48.26 15.00 33.26 0.00 0.00
September 106.47 36.21 66.27 32.92 33.35 0.00 0.00
October 139.98 39.80 86.78 58.28 28.50 0.00 0.00
November 153.60 59.69 105.41 74.68 30.72 0.00 0.00
December 171.54 66.32 117.09 89.23 27.86 0.00 0.00
               
Annual Sum or Average 104.54 47.47 71.61 39.18 32.42 0.00 0.00
Minimum of Months 45.63 27.70 35.63 2.09 27.86 0.00 0.00
Maximum of Months 171.54 66.32 117.09 89.23 35.70 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 12.90 61.25 16.54 0.00 16.54 0.00 0.00
February 14.67 55.12 20.77 0.00 20.77 0.00 0.00
March 21.03 56.79 25.45 0.00 25.45 0.00 0.00
April 30.86 40.84 29.48 0.24 29.24 0.00 0.00
May 38.85 35.23 35.46 1.85 33.61 0.00 0.00
June 49.80 24.58 37.59 3.71 33.88 0.00 0.00
July 53.18 20.11 35.61 3.02 32.58 0.00 0.00
August 43.78 21.03 29.60 0.66 28.95 0.00 0.00
September 33.79 27.00 24.99 0.00 24.98 0.00 0.00
October 29.77 31.71 19.82 0.00 19.82 0.00 0.00
November 15.23 53.29 17.95 0.00 17.95 0.00 0.00
December 11.94 61.06 15.40 0.00 15.40 0.00 0.00
               
Annual Sum or Average 29.74 40.60 25.74 0.79 24.95 0.00 0.00
Minimum of Months 11.94 20.11 15.40 0.00 15.40 0.00 0.00
Maximum of Months 53.18 61.25 37.59 3.71 33.88 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 327.38 204.30 240.83 156.02 84.82 0.00 0.00
February 274.62 184.30 217.84 117.10 100.74 0.00 0.00
March 278.69 189.75 220.16 101.82 118.34 0.00 0.00
April 340.54 146.38 242.85 113.54 129.30 0.00 0.00
May 277.85 130.79 211.64 73.18 138.45 0.00 0.00
June 289.11 95.09 204.59 72.09 132.50 0.00 0.00
July 352.76 79.89 228.22 95.06 133.15 0.00 0.00
August 382.45 82.60 239.47 113.95 125.52 0.00 0.00
September 330.64 100.92 213.64 101.32 112.32 0.00 0.00
October 353.62 113.79 223.75 132.02 91.73 0.00 0.00
November 322.92 180.70 236.61 146.44 90.17 0.00 0.00
December 338.35 203.57 247.16 167.72 79.44 0.00 0.00
               
Annual Sum or Average 322.82 142.46 227.34 115.93 111.41 0.00 0.00
Minimum of Months 274.62 79.89 204.59 72.09 79.44 0.00 0.00
Maximum of Months 382.45 204.30 247.16 167.72 138.45 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 142.68 201.72 124.71 55.59 69.12 0.00 0.00
February 142.94 182.74 135.73 50.23 85.50 0.00 0.00
March 185.64 187.79 165.79 59.84 105.95 0.00 0.00
April 271.43 143.40 207.62 85.99 121.64 0.00 0.00
May 261.83 127.93 205.18 69.35 135.83 0.00 0.00
June 289.59 91.80 207.02 74.12 132.90 0.00 0.00
July 343.47 77.12 225.74 93.82 131.92 0.00 0.00
August 332.34 80.58 216.13 96.02 120.11 0.00 0.00
September 235.36 98.64 162.01 60.16 101.85 0.00 0.00
October 211.23 111.69 140.03 59.16 80.87 0.00 0.00
November 148.07 178.62 127.26 53.07 74.19 0.00 0.00
December 136.98 201.11 120.02 56.17 63.86 0.00 0.00
               
Annual Sum or Average 225.69 140.05 169.98 67.93 102.05 0.00 0.00
Minimum of Months 136.98 77.12 120.02 50.23 63.86 0.00 0.00
Maximum of Months 343.47 201.72 225.74 96.02 135.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 367.97 270.29 272.92 174.05 98.87 0.00 0.00
February 285.53 251.40 232.26 115.88 116.38 0.00 0.00
March 248.71 260.00 204.49 72.76 131.74 0.00 0.00
April 248.62 202.70 188.75 48.79 139.97 0.00 0.00
May 185.54 178.53 164.82 14.66 150.16 0.00 0.00
June 195.56 130.84 158.63 12.57 146.06 0.00 0.00
July 223.36 114.11 158.55 15.25 143.30 0.00 0.00
August 257.47 123.64 168.70 33.92 134.78 0.00 0.00
September 300.28 149.27 197.73 71.35 126.38 0.00 0.00
October 360.49 168.96 230.96 126.27 104.69 0.00 0.00
November 360.13 246.63 267.27 161.82 105.45 0.00 0.00
December 389.08 272.83 287.07 193.33 93.74 0.00 0.00
               
Annual Sum or Average 285.32 197.16 210.92 86.62 124.30 0.00 0.00
Minimum of Months 185.54 114.11 158.55 12.57 93.74 0.00 0.00
Maximum of Months 389.08 272.83 287.07 193.33 150.16 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 321.71 205.13 235.93 150.42 85.51 0.00 0.00
February 290.48 185.60 226.46 121.59 104.87 0.00 0.00
March 284.00 193.99 221.59 101.82 119.77 0.00 0.00
April 364.97 150.06 258.69 124.88 133.81 0.00 0.00
May 311.21 133.54 234.10 90.70 143.41 0.00 0.00
June 337.22 94.74 238.71 99.56 139.15 0.00 0.00
July 385.45 78.63 252.57 114.92 137.65 0.00 0.00
August 399.46 83.07 253.25 123.21 130.05 0.00 0.00
September 381.79 101.08 248.19 129.60 118.59 0.00 0.00
October 373.23 114.80 235.49 142.44 93.05 0.00 0.00
November 339.77 181.12 246.07 153.19 92.88 0.00 0.00
December 340.49 203.21 246.91 165.30 81.61 0.00 0.00
               
Annual Sum or Average 344.46 143.53 241.55 126.51 115.04 0.00 0.00
Minimum of Months 284.00 78.63 221.59 90.70 81.61 0.00 0.00
Maximum of Months 399.46 205.13 258.69 165.30 143.41 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 145.67 208.72 119.81 49.99 69.82 0.00 0.00
February 163.79 186.66 144.35 54.72 89.63 0.00 0.00
March 194.26 193.53 167.22 59.84 107.38 0.00 0.00
April 297.57 147.33 223.47 97.32 126.15 0.00 0.00
May 294.89 130.00 227.65 86.86 140.79 0.00 0.00
June 338.75 92.58 241.14 101.59 139.55 0.00 0.00
July 377.81 77.36 250.09 113.68 136.42 0.00 0.00
August 350.65 81.23 229.92 105.28 124.64 0.00 0.00
September 287.94 98.84 196.56 88.44 108.12 0.00 0.00
October 234.77 113.97 151.77 69.58 82.19 0.00 0.00
November 170.68 182.71 136.71 59.82 76.89 0.00 0.00
December 148.80 207.51 119.77 53.75 66.02 0.00 0.00
               
Annual Sum or Average 250.92 143.16 184.20 78.51 105.69 0.00 0.00
Minimum of Months 145.67 77.36 119.77 49.99 66.02 0.00 0.00
Maximum of Months 377.81 208.72 250.09 113.68 140.79 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 293.10 107.57 200.63 147.29 53.34 0.00 0.00
February 218.07 97.28 158.48 98.06 60.42 0.00 0.00
March 172.26 102.14 126.40 61.57 64.83 0.00 0.00
April 155.09 78.68 105.69 40.85 64.84 0.00 0.00
May 92.91 69.73 74.47 9.02 65.45 0.00 0.00
June 85.17 48.98 65.33 3.83 61.50 0.00 0.00
July 104.24 39.87 68.90 7.37 61.53 0.00 0.00
August 148.14 42.11 88.49 27.50 60.99 0.00 0.00
September 197.78 52.42 121.52 60.37 61.15 0.00 0.00
October 258.94 59.01 159.12 106.86 52.26 0.00 0.00
November 282.96 94.72 193.28 136.94 56.34 0.00 0.00
December 315.49 106.78 214.70 163.60 51.09 0.00 0.00
               
Annual Sum or Average 193.63 74.82 131.30 71.85 59.45 0.00 0.00
Minimum of Months 85.17 39.87 65.33 3.83 51.09 0.00 0.00
Maximum of Months 315.49 107.57 214.70 163.60 65.45 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 68.19 676.71 144.74 0.00 144.74 0.00 0.00
February 77.89 627.39 181.69 0.00 181.69 0.00 0.00
March 124.75 633.01 222.66 0.00 222.66 0.00 0.00
April 191.95 472.06 257.88 2.08 255.81 0.00 0.00
May 244.96 407.13 310.23 16.18 294.05 0.00 0.00
June 333.57 303.06 328.85 32.49 296.36 0.00 0.00
July 364.16 260.46 311.50 26.43 285.07 0.00 0.00
August 290.59 281.35 258.99 5.75 253.24 0.00 0.00
September 219.47 346.82 218.62 0.04 218.58 0.00 0.00
October 194.30 399.43 173.40 0.00 173.40 0.00 0.00
November 82.52 604.58 157.00 0.00 157.00 0.00 0.00
December 60.26 677.85 134.74 0.00 134.74 0.00 0.00
               
Annual Sum or Average 188.41 473.36 225.21 6.95 218.26 0.00 0.00
Minimum of Months 60.26 260.46 134.74 0.00 134.74 0.00 0.00
Maximum of Months 364.16 677.85 328.85 32.49 296.36 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 60.96 698.60 144.74 0.00 144.74 0.00 0.00
February 69.56 648.98 181.69 0.00 181.69 0.00 0.00
March 114.23 653.16 222.66 0.00 222.66 0.00 0.00
April 180.07 485.78 257.88 2.08 255.81 0.00 0.00
May 231.08 418.29 310.23 16.18 294.05 0.00 0.00
June 320.72 312.09 328.85 32.49 296.36 0.00 0.00
July 352.80 268.23 311.50 26.43 285.07 0.00 0.00
August 280.32 290.17 258.99 5.75 253.24 0.00 0.00
September 209.91 358.18 218.62 0.04 218.58 0.00 0.00
October 185.83 411.97 173.40 0.00 173.40 0.00 0.00
November 74.65 623.40 157.00 0.00 157.00 0.00 0.00
December 53.70 699.25 134.74 0.00 134.74 0.00 0.00
               
Annual Sum or Average 178.51 488.18 225.21 6.95 218.26 0.00 0.00
Minimum of Months 53.70 268.23 134.74 0.00 134.74 0.00 0.00
Maximum of Months 352.80 699.25 328.85 32.49 296.36 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 484.62 463.93 365.53 211.59 153.93 0.00 0.00
February 422.43 448.78 353.56 167.32 186.23 0.00 0.00
March 473.46 456.63 385.93 161.65 224.28 0.00 0.00
April 641.21 356.69 450.45 199.52 250.93 0.00 0.00
May 564.12 327.91 416.79 142.52 274.27 0.00 0.00
June 614.28 251.32 411.59 146.20 265.39 0.00 0.00
July 746.16 217.22 453.93 188.87 265.06 0.00 0.00
August 764.15 226.03 455.57 209.96 245.61 0.00 0.00
September 603.86 256.77 375.63 161.47 214.16 0.00 0.00
October 599.64 283.34 363.77 191.17 172.60 0.00 0.00
November 485.48 418.45 363.85 199.51 164.35 0.00 0.00
December 488.61 463.75 367.17 223.88 143.29 0.00 0.00
               
Annual Sum or Average 575.12 347.03 397.30 183.85 213.45 0.00 0.00
Minimum of Months 422.43 217.22 353.56 142.52 143.29 0.00 0.00
Maximum of Months 764.15 463.93 455.57 223.88 274.27 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 769.84 474.33 560.32 374.93 185.39 0.00 0.00
February 585.78 439.97 465.70 249.62 216.08 0.00 0.00
March 489.81 461.56 398.08 156.73 241.35 0.00 0.00
April 468.47 365.66 357.45 104.70 252.75 0.00 0.00
May 321.53 323.70 295.92 28.50 267.41 0.00 0.00
June 322.22 241.93 279.04 20.89 258.15 0.00 0.00
July 376.16 212.38 282.17 27.82 254.35 0.00 0.00
August 466.56 229.64 314.04 71.97 242.07 0.00 0.00
September 578.17 269.97 384.27 153.68 230.58 0.00 0.00
October 720.80 299.89 464.48 272.02 192.47 0.00 0.00
November 749.39 428.99 545.82 348.59 197.23 0.00 0.00
December 821.30 472.81 592.71 416.47 176.25 0.00 0.00
               
Annual Sum or Average 555.88 351.28 411.44 185.28 226.16 0.00 0.00
Minimum of Months 321.53 212.38 279.04 20.89 176.25 0.00 0.00
Maximum of Months 821.30 474.33 592.71 416.47 267.41 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.271573E+10 0.100029E+10 0.185314E+10 0.136048E+10 0.492663E+09 0.00 0.00
February 0.184825E+10 0.815436E+09 0.132217E+10 0.818116E+09 0.504052E+09 0.00 0.00
March 0.162307E+10 0.931984E+09 0.116748E+10 0.568705E+09 0.598776E+09 0.00 0.00
April 0.140543E+10 0.725988E+09 0.944769E+09 0.365158E+09 0.579611E+09 0.00 0.00
May 0.878244E+09 0.658001E+09 0.687861E+09 83301651.90 0.604559E+09 0.00 0.00
June 0.759647E+09 0.477026E+09 0.583982E+09 34251187.10 0.549731E+09 0.00 0.00
July 0.936446E+09 0.435199E+09 0.636401E+09 68053370.08 0.568348E+09 0.00 0.00
August 0.133563E+10 0.470970E+09 0.817369E+09 0.253989E+09 0.563379E+09 0.00 0.00
September 0.175059E+10 0.542923E+09 0.108621E+10 0.539619E+09 0.546586E+09 0.00 0.00
October 0.237070E+10 0.623367E+09 0.146973E+10 0.987033E+09 0.482692E+09 0.00 0.00
November 0.254037E+10 0.870802E+09 0.172768E+10 0.122410E+10 0.503575E+09 0.00 0.00
December 0.292229E+10 0.100401E+10 0.198311E+10 0.151118E+10 0.471925E+09 0.00 0.00
               
Annual Sum or Average 0.210864E+11 0.855599E+10 0.142799E+11 0.781399E+10 0.646590E+10 0.00 0.00
Minimum of Months 0.759647E+09 0.435199E+09 0.583982E+09 34251187.10 0.471925E+09 0.00 0.00
Maximum of Months 0.292229E+10 0.100401E+10 0.198311E+10 0.151118E+10 0.604559E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.752117E+10 0.309894E+10 0.521833E+10 0.383102E+10 0.138731E+10 0.00 0.00
February 0.509120E+10 0.256009E+10 0.372314E+10 0.230376E+10 0.141938E+10 0.00 0.00
March 0.444719E+10 0.290884E+10 0.328755E+10 0.160144E+10 0.168611E+10 0.00 0.00
April 0.384469E+10 0.229423E+10 0.266041E+10 0.102826E+10 0.163215E+10 0.00 0.00
May 0.234523E+10 0.209797E+10 0.193697E+10 0.234572E+09 0.170240E+10 0.00 0.00
June 0.202039E+10 0.155053E+10 0.164445E+10 96449084.55 0.154801E+10 0.00 0.00
July 0.253905E+10 0.139433E+10 0.179206E+10 0.191634E+09 0.160043E+10 0.00 0.00
August 0.368069E+10 0.149310E+10 0.230166E+10 0.715217E+09 0.158644E+10 0.00 0.00
September 0.484551E+10 0.171839E+10 0.305868E+10 0.151953E+10 0.153915E+10 0.00 0.00
October 0.657957E+10 0.195136E+10 0.413865E+10 0.277942E+10 0.135923E+10 0.00 0.00
November 0.703050E+10 0.271563E+10 0.486503E+10 0.344700E+10 0.141803E+10 0.00 0.00
December 0.810054E+10 0.310675E+10 0.558430E+10 0.425539E+10 0.132891E+10 0.00 0.00
               
Annual Sum or Average 0.580457E+11 0.268902E+11 0.402112E+11 0.220037E+11 0.182075E+11 0.00 0.00
Minimum of Months 0.202039E+10 0.139433E+10 0.164445E+10 96449084.55 0.132891E+10 0.00 0.00
Maximum of Months 0.810054E+10 0.310675E+10 0.558430E+10 0.425539E+10 0.170240E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.999478E+10 0.411882E+10 0.677891E+10 0.497672E+10 0.180219E+10 0.00 0.00
February 0.675683E+10 0.345538E+10 0.483657E+10 0.299272E+10 0.184385E+10 0.00 0.00
March 0.589271E+10 0.395781E+10 0.427071E+10 0.208036E+10 0.219036E+10 0.00 0.00
April 0.510583E+10 0.311682E+10 0.345602E+10 0.133577E+10 0.212025E+10 0.00 0.00
May 0.305395E+10 0.291770E+10 0.251623E+10 0.304722E+09 0.221151E+10 0.00 0.00
June 0.261836E+10 0.216306E+10 0.213624E+10 0.125293E+09 0.201095E+10 0.00 0.00
July 0.333524E+10 0.192155E+10 0.232799E+10 0.248943E+09 0.207905E+10 0.00 0.00
August 0.489614E+10 0.200523E+10 0.298998E+10 0.929108E+09 0.206087E+10 0.00 0.00
September 0.645195E+10 0.229378E+10 0.397340E+10 0.197396E+10 0.199944E+10 0.00 0.00
October 0.873321E+10 0.258298E+10 0.537634E+10 0.361063E+10 0.176572E+10 0.00 0.00
November 0.933822E+10 0.361217E+10 0.631995E+10 0.447785E+10 0.184211E+10 0.00 0.00
December 0.107531E+11 0.412603E+10 0.725432E+10 0.552799E+10 0.172633E+10 0.00 0.00
               
Annual Sum or Average 0.769304E+11 0.362713E+11 0.522367E+11 0.285840E+11 0.236526E+11 0.00 0.00
Minimum of Months 0.261836E+10 0.192155E+10 0.213624E+10 0.125293E+09 0.172633E+10 0.00 0.00
Maximum of Months 0.107531E+11 0.412603E+10 0.725432E+10 0.552799E+10 0.221151E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.865234E+09 0.559070E+09 0.631920E+09 0.402891E+09 0.229029E+09 0.00 0.00
February 0.707723E+09 0.457956E+09 0.547842E+09 0.294142E+09 0.253700E+09 0.00 0.00
March 0.768390E+09 0.526727E+09 0.593520E+09 0.272721E+09 0.320799E+09 0.00 0.00
April 0.959275E+09 0.393945E+09 0.670528E+09 0.323680E+09 0.346848E+09 0.00 0.00
May 0.846392E+09 0.362189E+09 0.627025E+09 0.242928E+09 0.384097E+09 0.00 0.00
June 0.887873E+09 0.249167E+09 0.618729E+09 0.258064E+09 0.360665E+09 0.00 0.00
July 0.104641E+10 0.214195E+09 0.676483E+09 0.307809E+09 0.368674E+09 0.00 0.00
August 0.108333E+10 0.226492E+09 0.678314E+09 0.330001E+09 0.348314E+09 0.00 0.00
September 0.100105E+10 0.267274E+09 0.643298E+09 0.335913E+09 0.307385E+09 0.00 0.00
October 0.100627E+10 0.315222E+09 0.630737E+09 0.381522E+09 0.249215E+09 0.00 0.00
November 0.885589E+09 0.478990E+09 0.637811E+09 0.397077E+09 0.240734E+09 0.00 0.00
December 0.914637E+09 0.555548E+09 0.661336E+09 0.442746E+09 0.218589E+09 0.00 0.00
               
Annual Sum or Average 0.109722E+11 0.460678E+10 0.761754E+10 0.398949E+10 0.362805E+10 0.00 0.00
Minimum of Months 0.707723E+09 0.214195E+09 0.547842E+09 0.242928E+09 0.218589E+09 0.00 0.00
Maximum of Months 0.108333E+10 0.559070E+09 0.678314E+09 0.442746E+09 0.384097E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.388425E+09 0.573357E+09 0.320905E+09 0.133901E+09 0.187004E+09 0.00 0.00
February 0.396267E+09 0.463354E+09 0.349219E+09 0.132386E+09 0.216833E+09 0.00 0.00
March 0.524535E+09 0.527255E+09 0.447889E+09 0.160279E+09 0.287610E+09 0.00 0.00
April 0.782036E+09 0.387582E+09 0.579223E+09 0.252251E+09 0.326972E+09 0.00 0.00
May 0.801723E+09 0.352791E+09 0.609729E+09 0.232648E+09 0.377081E+09 0.00 0.00
June 0.892010E+09 0.243363E+09 0.625037E+09 0.263322E+09 0.361715E+09 0.00 0.00
July 0.102573E+10 0.210625E+09 0.669847E+09 0.304467E+09 0.365379E+09 0.00 0.00
August 0.951200E+09 0.221704E+09 0.615807E+09 0.281984E+09 0.333823E+09 0.00 0.00
September 0.754877E+09 0.262216E+09 0.509491E+09 0.229238E+09 0.280253E+09 0.00 0.00
October 0.630859E+09 0.315038E+09 0.406496E+09 0.186368E+09 0.220128E+09 0.00 0.00
November 0.441218E+09 0.487220E+09 0.354356E+09 0.155051E+09 0.199305E+09 0.00 0.00
December 0.394854E+09 0.572468E+09 0.320798E+09 0.143959E+09 0.176839E+09 0.00 0.00
               
Annual Sum or Average 0.798374E+10 0.461697E+10 0.580880E+10 0.247585E+10 0.333294E+10 0.00 0.00
Minimum of Months 0.388425E+09 0.210625E+09 0.320798E+09 0.132386E+09 0.176839E+09 0.00 0.00
Maximum of Months 0.102573E+10 0.573357E+09 0.669847E+09 0.304467E+09 0.377081E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.426815E+09 0.176991E+09 0.293061E+09 0.215149E+09 77911467.45 0.00 0.00
February 0.286147E+09 0.145779E+09 0.209091E+09 0.129379E+09 79712592.74 0.00 0.00
March 0.249664E+09 0.165457E+09 0.184629E+09 89936327.87 94692605.60 0.00 0.00
April 0.216660E+09 0.128785E+09 0.149409E+09 57746850.06 91662135.38 0.00 0.00
May 0.134177E+09 0.113226E+09 0.108781E+09 13173513.96 95607483.13 0.00 0.00
June 0.118283E+09 79375060.74 92353413.13 5416561.15 86936851.98 0.00 0.00
July 0.145950E+09 74180890.34 0.100643E+09 10762115.76 89881160.52 0.00 0.00
August 0.210647E+09 80337703.60 0.129262E+09 40166453.60 89095338.36 0.00 0.00
September 0.275965E+09 93865309.02 0.171776E+09 85336561.19 86439337.30 0.00 0.00
October 0.374927E+09 0.106591E+09 0.232427E+09 0.156092E+09 76334792.12 0.00 0.00
November 0.398129E+09 0.154706E+09 0.273220E+09 0.193583E+09 79637126.46 0.00 0.00
December 0.459444E+09 0.177618E+09 0.313614E+09 0.238982E+09 74631825.39 0.00 0.00
               
Annual Sum or Average 0.329681E+10 0.149691E+10 0.225827E+10 0.123572E+10 0.102254E+10 0.00 0.00
Minimum of Months 0.118283E+09 74180890.34 92353413.13 5416561.15 74631825.39 0.00 0.00
Maximum of Months 0.459444E+09 0.177618E+09 0.313614E+09 0.238982E+09 95607483.13 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 34551159.78 0.164058E+09 44312955.30 0.00 44312955.30 0.00 0.00
February 35479383.49 0.133345E+09 50241522.13 0.00 50241522.13 0.00 0.00
March 56314143.45 0.152097E+09 68169765.21 624.22 68169140.99 0.00 0.00
April 79991180.14 0.105868E+09 76404816.42 614812.68 75790003.74 0.00 0.00
May 0.104063E+09 94355141.15 94978755.02 4953021.70 90025733.32 0.00 0.00
June 0.129083E+09 63698431.68 97431324.50 9625266.49 87806058.00 0.00 0.00
July 0.142427E+09 53866852.02 95367114.15 8092321.46 87274792.68 0.00 0.00
August 0.117261E+09 56321320.55 79292341.88 1761686.91 77530654.97 0.00 0.00
September 87573164.77 69977794.95 64772993.27 12882.05 64760111.22 0.00 0.00
October 79735594.50 84938642.90 53086943.81 0.00 53086943.81 0.00 0.00
November 39468909.35 0.138134E+09 46515858.69 0.00 46515858.69 0.00 0.00
December 31986376.18 0.163551E+09 41251595.16 0.00 41251595.16 0.00 0.00
               
Annual Sum or Average 0.937933E+09 0.128021E+10 0.811826E+09 25060615.52 0.786765E+09 0.00 0.00
Minimum of Months 31986376.18 53866852.02 41251595.16 0.00 41251595.16 0.00 0.00
Maximum of Months 0.142427E+09 0.164058E+09 97431324.50 9625266.49 90025733.32 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.876862E+09 0.547206E+09 0.645041E+09 0.417872E+09 0.227169E+09 0.00 0.00
February 0.664349E+09 0.445847E+09 0.526993E+09 0.283282E+09 0.243711E+09 0.00 0.00
March 0.746457E+09 0.508225E+09 0.589680E+09 0.272720E+09 0.316960E+09 0.00 0.00
April 0.882687E+09 0.379408E+09 0.629463E+09 0.294307E+09 0.335155E+09 0.00 0.00
May 0.744189E+09 0.350296E+09 0.566849E+09 0.196017E+09 0.370832E+09 0.00 0.00
June 0.749367E+09 0.246466E+09 0.530300E+09 0.186863E+09 0.343438E+09 0.00 0.00
July 0.944841E+09 0.213966E+09 0.611254E+09 0.254616E+09 0.356638E+09 0.00 0.00
August 0.102437E+10 0.221228E+09 0.641384E+09 0.305202E+09 0.336182E+09 0.00 0.00
September 0.857014E+09 0.261586E+09 0.553748E+09 0.262611E+09 0.291136E+09 0.00 0.00
October 0.947128E+09 0.304774E+09 0.599302E+09 0.353603E+09 0.245699E+09 0.00 0.00
November 0.837010E+09 0.468367E+09 0.613301E+09 0.379582E+09 0.233719E+09 0.00 0.00
December 0.906226E+09 0.545240E+09 0.662004E+09 0.449220E+09 0.212784E+09 0.00 0.00
               
Annual Sum or Average 0.101805E+11 0.449261E+10 0.716932E+10 0.365590E+10 0.351342E+10 0.00 0.00
Minimum of Months 0.664349E+09 0.213966E+09 0.526993E+09 0.186863E+09 0.212784E+09 0.00 0.00
Maximum of Months 0.102437E+10 0.547206E+09 0.662004E+09 0.449220E+09 0.370832E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.382167E+09 0.540296E+09 0.334026E+09 0.148882E+09 0.185144E+09 0.00 0.00
February 0.345810E+09 0.442076E+09 0.328370E+09 0.121526E+09 0.206844E+09 0.00 0.00
March 0.497228E+09 0.502978E+09 0.444049E+09 0.160278E+09 0.283771E+09 0.00 0.00
April 0.703559E+09 0.371685E+09 0.538158E+09 0.222878E+09 0.315280E+09 0.00 0.00
May 0.701293E+09 0.342647E+09 0.549554E+09 0.185737E+09 0.363816E+09 0.00 0.00
June 0.750619E+09 0.237939E+09 0.536608E+09 0.192121E+09 0.344488E+09 0.00 0.00
July 0.919949E+09 0.206556E+09 0.604618E+09 0.251275E+09 0.353343E+09 0.00 0.00
August 0.890132E+09 0.215832E+09 0.578877E+09 0.257186E+09 0.321691E+09 0.00 0.00
September 0.610041E+09 0.255677E+09 0.419941E+09 0.155935E+09 0.264005E+09 0.00 0.00
October 0.565753E+09 0.299152E+09 0.375061E+09 0.158449E+09 0.216611E+09 0.00 0.00
November 0.383803E+09 0.462979E+09 0.329845E+09 0.137555E+09 0.192290E+09 0.00 0.00
December 0.366895E+09 0.538650E+09 0.321466E+09 0.150433E+09 0.171033E+09 0.00 0.00
               
Annual Sum or Average 0.711725E+10 0.441647E+10 0.536057E+10 0.214226E+10 0.321832E+10 0.00 0.00
Minimum of Months 0.345810E+09 0.206556E+09 0.321466E+09 0.121526E+09 0.171033E+09 0.00 0.00
Maximum of Months 0.919949E+09 0.540296E+09 0.604618E+09 0.257186E+09 0.363816E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.985565E+09 0.723942E+09 0.730978E+09 0.466169E+09 0.264809E+09 0.00 0.00
February 0.690745E+09 0.608190E+09 0.561883E+09 0.280328E+09 0.281555E+09 0.00 0.00
March 0.666147E+09 0.696396E+09 0.547718E+09 0.194868E+09 0.352850E+09 0.00 0.00
April 0.644417E+09 0.525390E+09 0.489246E+09 0.126453E+09 0.362793E+09 0.00 0.00
May 0.496950E+09 0.478171E+09 0.441454E+09 39273247.18 0.402181E+09 0.00 0.00
June 0.506883E+09 0.339145E+09 0.411173E+09 32587736.49 0.378585E+09 0.00 0.00
July 0.598250E+09 0.305632E+09 0.424663E+09 40849193.83 0.383814E+09 0.00 0.00
August 0.689608E+09 0.331156E+09 0.451848E+09 90845939.63 0.361002E+09 0.00 0.00
September 0.778315E+09 0.386909E+09 0.512511E+09 0.184929E+09 0.327582E+09 0.00 0.00
October 0.965545E+09 0.452550E+09 0.618608E+09 0.338207E+09 0.280400E+09 0.00 0.00
November 0.933457E+09 0.639262E+09 0.692760E+09 0.419440E+09 0.273320E+09 0.00 0.00
December 0.104210E+10 0.730755E+09 0.768878E+09 0.517807E+09 0.251071E+09 0.00 0.00
               
Annual Sum or Average 0.899799E+10 0.621750E+10 0.665172E+10 0.273176E+10 0.391996E+10 0.00 0.00
Minimum of Months 0.496950E+09 0.305632E+09 0.411173E+09 32587736.49 0.251071E+09 0.00 0.00
Maximum of Months 0.104210E+10 0.730755E+09 0.768878E+09 0.517807E+09 0.402181E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.861655E+09 0.549414E+09 0.631920E+09 0.402891E+09 0.229029E+09 0.00 0.00
February 0.702727E+09 0.448995E+09 0.547842E+09 0.294142E+09 0.253700E+09 0.00 0.00
March 0.760656E+09 0.519573E+09 0.593520E+09 0.272721E+09 0.320799E+09 0.00 0.00
April 0.946001E+09 0.388957E+09 0.670528E+09 0.323680E+09 0.346848E+09 0.00 0.00
May 0.833542E+09 0.357682E+09 0.627025E+09 0.242928E+09 0.384097E+09 0.00 0.00
June 0.874066E+09 0.245577E+09 0.618729E+09 0.258064E+09 0.360665E+09 0.00 0.00
July 0.103239E+10 0.210601E+09 0.676483E+09 0.307809E+09 0.368674E+09 0.00 0.00
August 0.106990E+10 0.222504E+09 0.678314E+09 0.330001E+09 0.348314E+09 0.00 0.00
September 0.989604E+09 0.261987E+09 0.643298E+09 0.335913E+09 0.307385E+09 0.00 0.00
October 0.999647E+09 0.307475E+09 0.630737E+09 0.381522E+09 0.249215E+09 0.00 0.00
November 0.880689E+09 0.469453E+09 0.637811E+09 0.397077E+09 0.240734E+09 0.00 0.00
December 0.911981E+09 0.544289E+09 0.661336E+09 0.442746E+09 0.218589E+09 0.00 0.00
               
Annual Sum or Average 0.108629E+11 0.452651E+10 0.761754E+10 0.398949E+10 0.362805E+10 0.00 0.00
Minimum of Months 0.702727E+09 0.210601E+09 0.547842E+09 0.242928E+09 0.218589E+09 0.00 0.00
Maximum of Months 0.106990E+10 0.549414E+09 0.678314E+09 0.442746E+09 0.384097E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.390173E+09 0.559040E+09 0.320905E+09 0.133901E+09 0.187004E+09 0.00 0.00
February 0.396249E+09 0.451565E+09 0.349219E+09 0.132386E+09 0.216833E+09 0.00 0.00
March 0.520318E+09 0.518338E+09 0.447889E+09 0.160279E+09 0.287610E+09 0.00 0.00
April 0.771296E+09 0.381875E+09 0.579223E+09 0.252251E+09 0.326972E+09 0.00 0.00
May 0.789823E+09 0.348185E+09 0.609729E+09 0.232648E+09 0.377081E+09 0.00 0.00
June 0.878051E+09 0.239979E+09 0.625037E+09 0.263322E+09 0.361715E+09 0.00 0.00
July 0.101193E+10 0.207189E+09 0.669847E+09 0.304467E+09 0.365379E+09 0.00 0.00
August 0.939173E+09 0.217559E+09 0.615807E+09 0.281984E+09 0.333823E+09 0.00 0.00
September 0.746345E+09 0.256202E+09 0.509491E+09 0.229238E+09 0.280253E+09 0.00 0.00
October 0.628811E+09 0.305244E+09 0.406496E+09 0.186368E+09 0.220128E+09 0.00 0.00
November 0.442412E+09 0.473574E+09 0.354356E+09 0.155051E+09 0.199305E+09 0.00 0.00
December 0.398533E+09 0.555805E+09 0.320798E+09 0.143959E+09 0.176839E+09 0.00 0.00
               
Annual Sum or Average 0.791311E+10 0.451455E+10 0.580880E+10 0.247585E+10 0.333294E+10 0.00 0.00
Minimum of Months 0.390173E+09 0.207189E+09 0.320798E+09 0.132386E+09 0.176839E+09 0.00 0.00
Maximum of Months 0.101193E+10 0.559040E+09 0.669847E+09 0.304467E+09 0.377081E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.785049E+09 0.288115E+09 0.537359E+09 0.394500E+09 0.142859E+09 0.00 0.00
February 0.527555E+09 0.235349E+09 0.383392E+09 0.237230E+09 0.146162E+09 0.00 0.00
March 0.461381E+09 0.273563E+09 0.338537E+09 0.164908E+09 0.173629E+09 0.00 0.00
April 0.401984E+09 0.203945E+09 0.273958E+09 0.105885E+09 0.168073E+09 0.00 0.00
May 0.248840E+09 0.186757E+09 0.199462E+09 24155080.95 0.175307E+09 0.00 0.00
June 0.220768E+09 0.126946E+09 0.169340E+09 9931858.23 0.159408E+09 0.00 0.00
July 0.279191E+09 0.106775E+09 0.184540E+09 19733518.19 0.164807E+09 0.00 0.00
August 0.396779E+09 0.112791E+09 0.237016E+09 73649592.75 0.163366E+09 0.00 0.00
September 0.512642E+09 0.135868E+09 0.314970E+09 0.156474E+09 0.158496E+09 0.00 0.00
October 0.693542E+09 0.158040E+09 0.426179E+09 0.286211E+09 0.139968E+09 0.00 0.00
November 0.733428E+09 0.245506E+09 0.500979E+09 0.354955E+09 0.146023E+09 0.00 0.00
December 0.845019E+09 0.286005E+09 0.575045E+09 0.438199E+09 0.136846E+09 0.00 0.00
               
Annual Sum or Average 0.610618E+10 0.235966E+10 0.414078E+10 0.226583E+10 0.187494E+10 0.00 0.00
Minimum of Months 0.220768E+09 0.106775E+09 0.169340E+09 9931858.23 0.136846E+09 0.00 0.00
Maximum of Months 0.845019E+09 0.288115E+09 0.575045E+09 0.438199E+09 0.175307E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.182644E+09 0.181250E+10 0.387672E+09 0.00 0.387672E+09 0.00 0.00
February 0.188423E+09 0.151778E+10 0.439538E+09 0.00 0.439538E+09 0.00 0.00
March 0.334129E+09 0.169546E+10 0.596384E+09 5460.98 0.596378E+09 0.00 0.00
April 0.497526E+09 0.122357E+10 0.668428E+09 5378694.26 0.663050E+09 0.00 0.00
May 0.656108E+09 0.109047E+10 0.830922E+09 43331554.67 0.787591E+09 0.00 0.00
June 0.864624E+09 0.785539E+09 0.852379E+09 84206730.00 0.768172E+09 0.00 0.00
July 0.975367E+09 0.697611E+09 0.834320E+09 70795746.72 0.763524E+09 0.00 0.00
August 0.778304E+09 0.753555E+09 0.693690E+09 15412133.73 0.678278E+09 0.00 0.00
September 0.568867E+09 0.898964E+09 0.566667E+09 112698.72 0.566554E+09 0.00 0.00
October 0.520426E+09 0.106983E+10 0.464432E+09 0.00 0.464432E+09 0.00 0.00
November 0.213899E+09 0.156706E+10 0.406944E+09 0.00 0.406944E+09 0.00 0.00
December 0.161409E+09 0.181554E+10 0.360890E+09 0.00 0.360890E+09 0.00 0.00
               
Annual Sum or Average 0.594173E+10 0.149279E+11 0.710227E+10 0.219243E+09 0.688302E+10 0.00 0.00
Minimum of Months 0.161409E+09 0.697611E+09 0.360890E+09 0.00 0.360890E+09 0.00 0.00
Maximum of Months 0.975367E+09 0.181554E+10 0.852379E+09 84206730.00 0.787591E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.163275E+09 0.187114E+10 0.387672E+09 0.00 0.387672E+09 0.00 0.00
February 0.168285E+09 0.157001E+10 0.439538E+09 0.00 0.439538E+09 0.00 0.00
March 0.305947E+09 0.174941E+10 0.596384E+09 5460.98 0.596378E+09 0.00 0.00
April 0.466747E+09 0.125914E+10 0.668428E+09 5378694.26 0.663050E+09 0.00 0.00
May 0.618911E+09 0.112035E+10 0.830922E+09 43331554.67 0.787591E+09 0.00 0.00
June 0.831315E+09 0.808932E+09 0.852379E+09 84206730.00 0.768172E+09 0.00 0.00
July 0.944949E+09 0.718414E+09 0.834320E+09 70795746.72 0.763524E+09 0.00 0.00
August 0.750805E+09 0.777182E+09 0.693690E+09 15412133.73 0.678278E+09 0.00 0.00
September 0.544091E+09 0.928394E+09 0.566667E+09 112698.72 0.566554E+09 0.00 0.00
October 0.497714E+09 0.110341E+10 0.464432E+09 0.00 0.464432E+09 0.00 0.00
November 0.193481E+09 0.161584E+10 0.406944E+09 0.00 0.406944E+09 0.00 0.00
December 0.143822E+09 0.187287E+10 0.360890E+09 0.00 0.360890E+09 0.00 0.00
               
Annual Sum or Average 0.562934E+10 0.153951E+11 0.710227E+10 0.219243E+09 0.688302E+10 0.00 0.00
Minimum of Months 0.143822E+09 0.718414E+09 0.360890E+09 0.00 0.360890E+09 0.00 0.00
Maximum of Months 0.944949E+09 0.187287E+10 0.852379E+09 84206730.00 0.787591E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.129801E+10 0.124259E+10 0.979027E+09 0.566733E+09 0.412294E+09 0.00 0.00
February 0.102194E+10 0.108568E+10 0.855325E+09 0.404791E+09 0.450534E+09 0.00 0.00
March 0.126813E+10 0.122304E+10 0.103368E+10 0.432976E+09 0.600702E+09 0.00 0.00
April 0.166202E+10 0.924534E+09 0.116756E+10 0.517154E+09 0.650404E+09 0.00 0.00
May 0.151094E+10 0.878283E+09 0.111634E+10 0.381729E+09 0.734613E+09 0.00 0.00
June 0.159221E+10 0.651428E+09 0.106685E+10 0.378958E+09 0.687892E+09 0.00 0.00
July 0.199852E+10 0.581813E+09 0.121580E+10 0.505857E+09 0.709947E+09 0.00 0.00
August 0.204670E+10 0.605395E+09 0.122019E+10 0.562352E+09 0.657842E+09 0.00 0.00
September 0.156521E+10 0.665543E+09 0.973640E+09 0.418524E+09 0.555116E+09 0.00 0.00
October 0.160608E+10 0.758894E+09 0.974319E+09 0.512030E+09 0.462289E+09 0.00 0.00
November 0.125837E+10 0.108462E+10 0.943108E+09 0.517117E+09 0.425991E+09 0.00 0.00
December 0.130871E+10 0.124210E+10 0.983432E+09 0.599632E+09 0.383800E+09 0.00 0.00
               
Annual Sum or Average 0.181368E+11 0.109439E+11 0.125293E+11 0.579785E+10 0.673142E+10 0.00 0.00
Minimum of Months 0.102194E+10 0.581813E+09 0.855325E+09 0.378958E+09 0.383800E+09 0.00 0.00
Maximum of Months 0.204670E+10 0.124259E+10 0.122019E+10 0.599632E+09 0.734613E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.206195E+10 0.127044E+10 0.150077E+10 0.100422E+10 0.496551E+09 0.00 0.00
February 0.141713E+10 0.106438E+10 0.112662E+10 0.603882E+09 0.522737E+09 0.00 0.00
March 0.131190E+10 0.123625E+10 0.106621E+10 0.419784E+09 0.646422E+09 0.00 0.00
April 0.121428E+10 0.947796E+09 0.926512E+09 0.271380E+09 0.655132E+09 0.00 0.00
May 0.861184E+09 0.867011E+09 0.792583E+09 76342183.92 0.716240E+09 0.00 0.00
June 0.835196E+09 0.627071E+09 0.723261E+09 54148304.57 0.669113E+09 0.00 0.00
July 0.100750E+10 0.568835E+09 0.755764E+09 74501639.64 0.681262E+09 0.00 0.00
August 0.124964E+10 0.615059E+09 0.841134E+09 0.192762E+09 0.648372E+09 0.00 0.00
September 0.149861E+10 0.699750E+09 0.996027E+09 0.398351E+09 0.597676E+09 0.00 0.00
October 0.193060E+10 0.803220E+09 0.124407E+10 0.728566E+09 0.515505E+09 0.00 0.00
November 0.194243E+10 0.111194E+10 0.141477E+10 0.903557E+09 0.511212E+09 0.00 0.00
December 0.219976E+10 0.126637E+10 0.158752E+10 0.111546E+10 0.472062E+09 0.00 0.00
               
Annual Sum or Average 0.175302E+11 0.110781E+11 0.129752E+11 0.584296E+10 0.713228E+10 0.00 0.00
Minimum of Months 0.835196E+09 0.568835E+09 0.723261E+09 54148304.57 0.472062E+09 0.00 0.00
Maximum of Months 0.219976E+10 0.127044E+10 0.158752E+10 0.111546E+10 0.716240E+09 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 13.22 9.61 5.99 2.23 0.81 45.19 208.20 0.00
February 13.28 10.20 7.03 3.12 2.96 66.07 175.60 0.04
March 12.64 10.61 8.97 2.93 3.55 84.90 179.28 0.03
April 15.30 12.62 10.61 2.62 4.76 81.20 282.81 0.02
May 15.56 12.65 10.56 2.92 6.17 105.80 234.18 0.01
June 17.67 14.80 13.02 2.53 9.03 98.05 261.27 0.00
July 19.43 16.76 15.28 2.35 9.62 86.54 312.15 0.00
August 19.66 17.23 15.95 2.55 9.62 74.58 307.55 0.00
September 18.47 15.50 13.65 2.19 8.99 70.75 240.05 0.00
October 18.77 13.72 9.60 2.71 7.74 53.88 216.36 0.00
November 14.32 10.43 6.22 2.47 2.41 50.75 207.87 0.01
December 13.59 8.82 3.19 2.50 0.05 39.49 221.83 0.00
                 
Annual Sum or Average 16.01 12.76 10.02 2.59 5.49 71.44 237.65 0.01
Minimum of Months 12.64 8.82 3.19 2.19 0.05 39.49 175.60 0.00
Maximum of Months 19.66 17.23 15.95 3.12 9.62 105.80 312.15 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 26.00 13-JAN-13:00 15.46 8.00 3.10 11.84 120.00 725.00
February 26.00 01-FEB-11:00 14.67 6.00 4.10 10.11 166.00 715.50
March 24.00 11-MAR-10:00 13.82 6.00 2.60 8.15 120.00 907.00
April 27.00 26-APR-12:00 17.13 11.00 4.10 12.22 159.00 884.00
May 24.00 03-MAY-11:00 15.05 9.00 4.10 12.98 187.00 842.50
June 25.00 29-JUN-10:00 19.59 17.00 4.60 11.65 177.50 829.00
July 28.00 19-JUL-10:00 20.49 17.00 3.60 14.65 173.00 813.00
August 28.00 14-AUG-10:00 21.19 18.00 3.60 14.84 148.00 840.00
September 36.00 29-SEP-10:00 17.91 5.00 3.60 19.35 159.50 790.00
October 37.00 16-OCT-10:00 17.87 4.00 5.70 20.05 122.00 871.50
November 27.00 19-NOV-12:00 14.96 6.00 4.10 11.07 128.50 796.00
December 26.00 05-DEC-09:00 13.09 1.00 3.60 8.94 75.50 857.00
                 
Annual Sum or Average                
Minimum of Months 24.00   13.09 1.00 2.60 8.15 75.50 715.50
Maximum of Months 37.00   21.19 18.00 5.70 20.05 187.00 907.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 1.00 08-JAN-06:00 -0.3 -2.0 3.10 -15.5 11.50 193.50
February 5.00 04-FEB-05:00 0.22 -8.0 4.10 -10.9 0.00 0.00
March 4.00 07-MAR-04:00 3.53 3.00 0.00 -11.4 0.00 0.00
April 7.00 01-APR-05:00 4.33 1.00 4.10 -9.0 23.50 211.00
May 8.00 14-MAY-03:00 7.45 7.00 1.50 -6.6 0.00 0.00
June 11.00 13-JUN-03:00 9.85 9.00 2.10 -3.4 0.00 0.00
July 13.00 06-JUL-00:00 13.00 13.00 0.00 -0.6 0.00 0.00
August 14.00 24-AUG-01:00 14.00 14.00 0.00 0.51 0.00 0.00
September 11.00 20-SEP-02:00 9.85 9.00 1.50 -3.4 0.00 0.00
October 9.00 12-OCT-04:00 6.56 4.00 3.10 -6.4 0.00 0.00
November 7.00 05-NOV-01:00 5.54 4.00 3.10 -8.3 0.00 0.00
December 5.00 03-DEC-00:00 5.00 5.00 2.10 -0.4 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 1.00   -0.3 -8.0 0.00 -15.5 0.00 0.00
Maximum of Months 14.00   14.00 14.00 4.10 0.51 23.50 211.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 17.04 17-JAN-11:00 24.00 13.00 3.10 12.79 223.50 9.00
February 16.80 11-FEB-13:00 18.00 16.20 1.10 15.02 241.00 12.50
March 17.41 22-MAR-12:00 22.00 15.00 3.10 8.35 145.50 876.00
April 18.33 26-APR-10:00 26.00 14.00 4.10 12.03 141.50 915.50
May 16.69 05-MAY-14:00 18.00 16.00 5.10 8.74 303.50 269.00
June 19.59 29-JUN-10:00 25.00 17.00 4.60 11.65 177.50 829.00
July 21.19 19-JUL-11:00 28.00 18.00 4.60 14.84 182.50 808.00
August 21.20 18-AUG-11:00 28.00 18.00 3.60 17.21 244.00 667.50
September 21.85 22-SEP-11:00 26.00 20.00 2.60 20.05 284.00 21.00
October 21.09 01-OCT-11:00 26.00 19.00 3.60 13.16 102.00 899.50
November 16.52 10-NOV-12:00 21.00 14.00 5.10 7.15 131.00 808.50
December 15.64 07-DEC-12:00 20.00 13.00 5.10 5.94 89.00 868.50
                 
Annual Sum or Average                
Minimum of Months 15.64   18.00 13.00 1.10 5.94 89.00 9.00
Maximum of Months 21.85   28.00 20.00 5.10 20.05 303.50 915.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.00 17-JAN-12:00 22.00 16.85 2.10 11.65 241.50 67.50
February 16.20 11-FEB-13:00 18.00 16.80 1.10 15.02 241.00 12.50
March 15.00 23-MAR-15:20 21.67 17.34 3.77 8.02 112.00 809.83
April 15.00 26-APR-21:19 16.00 15.39 2.23 6.15 0.00 0.00
May 16.00 05-MAY-14:00 18.00 16.69 5.10 8.74 303.50 269.00
June 17.00 28-JUN-08:00 19.00 17.66 1.50 16.12 285.00 428.50
July 18.00 18-JUL-10:00 26.00 20.47 4.60 12.79 169.00 819.00
August 18.10 14-AUG-09:00 26.90 20.93 3.40 13.73 139.00 817.00
September 20.00 22-SEP-09:00 22.00 20.55 1.50 16.30 296.00 18.00
October 19.00 01-OCT-07:10 19.17 19.06 0.25 16.82 53.33 0.00
November 15.00 10-NOV-17:19 16.67 15.62 2.77 3.34 0.00 0.00
December 13.00 07-DEC-12:00 20.00 15.64 5.10 5.94 89.00 868.50
                 
Annual Sum or Average                
Minimum of Months 13.00   16.00 15.39 0.25 3.34 0.00 0.00
Maximum of Months 20.00   26.90 20.93 5.10 16.82 303.50 868.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 17.43 27.46 0.00
February 18.00 13.00 16.00 17.38 30.87 0.00
March 18.00 13.00 16.00 17.83 38.09 0.00
April 18.00 13.00 16.00 18.69 55.75 0.00
May 18.00 13.00 16.00 19.73 55.13 0.00
June 18.00 13.00 16.00 20.65 58.21 0.00
July 18.00 13.00 16.00 21.22 63.49 0.00
August 18.00 13.00 16.00 21.28 59.02 0.00
September 18.00 13.00 16.00 20.81 46.26 0.00
October 18.00 13.00 16.00 19.94 34.64 0.00
November 18.00 13.00 16.00 18.91 29.25 0.00
December 18.00 13.00 16.00 17.99 26.27 0.00
             
Annual Sum or Average 18.00 13.00 16.00 19.33 43.77 0.00
Minimum of Months 18.00 13.00 16.00 17.38 26.27 0.00
Maximum of Months 18.00 13.00 16.00 21.28 63.49 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770487E+10 -0.754278E+10 0.00 0.00 744.00 0.00 -162087104.9 81.21 0.00 0.00
February 0.696227E+10 -0.681598E+10 0.00 0.00 672.00 0.00 -146289432.8 81.21 0.00 0.00
March 0.770350E+10 -0.754147E+10 0.00 0.00 744.00 0.00 -162029748.9 81.21 0.00 0.00
April 0.746523E+10 -0.730860E+10 0.00 0.00 720.00 0.00 -156633620.0 81.21 0.00 0.00
May 0.770464E+10 -0.754280E+10 0.00 0.00 744.00 0.00 -161835576.9 81.21 0.00 0.00
June 0.745705E+10 -0.730053E+10 0.00 0.00 720.00 0.00 -156512351.7 81.21 0.00 0.00
July 0.771250E+10 -0.755084E+10 0.00 0.00 744.00 0.00 -161657535.7 81.21 0.00 0.00
August 0.770445E+10 -0.754280E+10 0.00 0.00 744.00 0.00 -161650769.2 81.21 0.00 0.00
September 0.746642E+10 -0.730993E+10 0.00 0.00 720.00 0.00 -156496655.4 81.21 0.00 0.00
October 0.770318E+10 -0.754143E+10 0.00 0.00 744.00 0.00 -161744699.0 81.21 0.00 0.00
November 0.744914E+10 -0.729243E+10 0.00 0.00 720.00 0.00 -156714032.2 81.21 0.00 0.00
December 0.771287E+10 -0.755087E+10 0.00 0.00 744.00 0.00 -161996866.7 81.21 0.00 0.00
                     
Annual Sum or Average 0.907461E+11 -0.888405E+11 0.00 0.00 8760.00 0.00 -0.190565E+10 81.21 0.00 0.00
Minimum of Months 0.696227E+10 -0.755087E+10 0.00 0.00 672.00 0.00 -162087104.9 81.21 0.00 0.00
Maximum of Months 0.771287E+10 -0.681598E+10 0.00 0.00 744.00 0.00 -146289432.8 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.109790E+12 -0.108049E+12 0.00 0.00 744.00 0.00 -0.174097E+10 81.24 0.00 0.00
February 0.992511E+11 -0.976640E+11 0.00 0.00 672.00 0.00 -0.158713E+10 81.25 0.00 0.00
March 0.109120E+12 -0.107357E+12 0.00 0.00 744.00 0.00 -0.176382E+10 81.25 0.00 0.00
April 0.104193E+12 -0.102483E+12 0.00 0.00 720.00 0.00 -0.170993E+10 81.25 0.00 0.00
May 0.105914E+12 -0.104147E+12 0.00 0.00 744.00 0.00 -0.176680E+10 81.25 0.00 0.00
June 0.100979E+12 -0.992661E+11 0.00 0.00 720.00 0.00 -0.171322E+10 81.25 0.00 0.00
July 0.103369E+12 -0.101609E+12 0.00 0.00 744.00 0.00 -0.176011E+10 81.25 0.00 0.00
August 0.103266E+12 -0.101509E+12 0.00 0.00 744.00 0.00 -0.175701E+10 81.25 0.00 0.00
September 0.100695E+12 -0.990054E+11 0.00 0.00 720.00 0.00 -0.169006E+10 81.25 0.00 0.00
October 0.105521E+12 -0.103781E+12 0.00 0.00 744.00 0.00 -0.173921E+10 81.25 0.00 0.00
November 0.103810E+12 -0.102129E+12 0.00 0.00 720.00 0.00 -0.168055E+10 81.25 0.00 0.00
December 0.108831E+12 -0.107092E+12 0.00 0.00 744.00 0.00 -0.173972E+10 81.25 0.00 0.00
                     
Annual Sum or Average 0.125474E+13 -0.123409E+13 0.00 0.00 8760.00 0.00 -0.206485E+11 81.25 0.00 0.00
Minimum of Months 0.992511E+11 -0.108049E+12 0.00 0.00 672.00 0.00 -0.176680E+10 81.24 0.00 0.00
Maximum of Months 0.109790E+12 -0.976640E+11 0.00 0.00 744.00 0.00 -0.158713E+10 81.25 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.621955E+11 -0.607124E+11 0.00 0.00 744.00 0.00 -0.148315E+10 58.98 0.00 0.00
February 0.562692E+11 -0.549097E+11 0.00 0.00 672.00 0.00 -0.135955E+10 58.98 0.00 0.00
March 0.616857E+11 -0.601713E+11 0.00 0.00 744.00 0.00 -0.151442E+10 58.98 0.00 0.00
April 0.584509E+11 -0.569812E+11 0.00 0.00 720.00 0.00 -0.146970E+10 58.98 0.00 0.00
May 0.588980E+11 -0.573794E+11 0.00 0.00 744.00 0.00 -0.151860E+10 58.98 0.00 0.00
June 0.557117E+11 -0.542374E+11 0.00 0.00 720.00 0.00 -0.147425E+10 58.98 0.00 0.00
July 0.566677E+11 -0.551583E+11 0.00 0.00 744.00 0.00 -0.150942E+10 58.98 0.00 0.00
August 0.566341E+11 -0.551290E+11 0.00 0.00 744.00 0.00 -0.150508E+10 58.98 0.00 0.00
September 0.554291E+11 -0.539867E+11 0.00 0.00 720.00 0.00 -0.144241E+10 58.98 0.00 0.00
October 0.585120E+11 -0.570314E+11 0.00 0.00 744.00 0.00 -0.148062E+10 58.98 0.00 0.00
November 0.580835E+11 -0.566542E+11 0.00 0.00 720.00 0.00 -0.142929E+10 58.98 0.00 0.00
December 0.613663E+11 -0.598851E+11 0.00 0.00 744.00 0.00 -0.148121E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.699904E+12 -0.682236E+12 0.00 0.00 8760.00 0.00 -0.176677E+11 58.98 0.00 0.00
Minimum of Months 0.554291E+11 -0.607124E+11 0.00 0.00 672.00 0.00 -0.151860E+10 58.98 0.00 0.00
Maximum of Months 0.621955E+11 -0.539867E+11 0.00 0.00 744.00 0.00 -0.135955E+10 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.93 0.93 01-JAN-07:19 6411.39 37.26 284.83 280.00 922.74 26.85 188.50 262.67
February 279.67 0.93 0.93 01-FEB-07:19 4458.45 31.97 218.17 274.67 609.14 23.53 166.67 242.83
March 338.17 0.93 0.93 01-MAR-06:49 1168.52 19.66 14.00 320.33 435.63 20.93 153.50 258.00
April 358.33 0.93 0.93 01-APR-06:30 803.80 19.17 0.00 332.33 339.22 20.93 142.83 259.50
May 393.83 0.94 0.93 01-MAY-06:10 730.15 18.66 0.00 363.33 297.49 20.40 116.67 254.50
June 381.00 0.94 0.93 01-JUN-06:10 631.55 18.47 0.00 354.33 265.96 20.23 65.50 229.17
July 408.67 0.94 0.93 01-JUL-05:00 622.22 18.59 0.00 363.67 271.55 20.36 95.83 243.00
August 390.67 0.94 0.93 01-AUG-06:49 676.69 18.85 0.00 353.33 294.84 20.61 140.67 263.83
September 328.83 0.93 0.93 01-SEP-06:40 908.83 19.16 0.00 308.00 378.48 20.94 142.83 252.67
October 296.17 0.93 0.93 01-OCT-09:39 3075.66 27.00 136.33 304.17 448.06 21.45 101.83 248.00
November 300.00 0.93 0.93 01-NOV-06:40 6241.58 37.10 294.67 280.17 808.97 26.43 201.33 266.83
December 297.00 0.93 0.93 01-DEC-07:10 6274.56 37.68 289.17 280.67 1131.34 28.40 185.67 265.33
                         
Annual Sum or Average 4065.67 0.93     2411.25 24.44 1237.17 3815.00 489.56 22.32 1701.83 3046.33
Minimum of Months 279.67 0.93 0.93   622.22 18.47 0.00 274.67 265.96 20.23 65.50 229.17
Maximum of Months 408.67 0.94 0.93   6411.39 37.68 294.67 363.67 1131.34 28.40 201.33 266.83



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.62 0.61 01-JAN-07:19 6782.76 37.34 285.00 284.67 1295.92 26.60 174.33 272.50
February 279.67 0.62 0.61 01-FEB-07:10 4753.37 32.08 218.50 281.50 903.67 23.62 167.33 262.00
March 338.17 0.63 0.61 01-MAR-06:49 1396.04 20.17 29.67 328.67 662.32 21.27 185.33 298.33
April 358.33 0.63 0.61 01-APR-06:19 987.44 19.80 14.67 345.50 522.42 21.35 195.83 313.00
May 393.83 0.63 0.61 01-MAY-05:00 860.02 19.52 0.00 378.50 426.94 21.03 208.50 339.17
June 381.00 0.63 0.61 01-JUN-05:49 748.47 19.36 0.00 367.83 382.50 20.89 196.83 329.50
July 408.67 0.63 0.61 01-JUL-05:40 745.77 19.44 0.00 377.17 394.74 20.98 246.67 344.50
August 390.67 0.63 0.61 01-AUG-06:40 830.15 19.56 0.17 367.17 447.92 21.11 208.33 333.83
September 328.83 0.63 0.61 01-SEP-06:19 1128.27 19.66 18.17 321.33 597.42 21.26 157.83 289.33
October 296.17 0.62 0.61 01-OCT-09:39 3376.77 27.08 137.00 315.83 747.20 21.45 102.67 281.00
November 300.00 0.63 0.61 01-NOV-06:40 6591.11 37.15 294.83 285.83 1155.94 26.24 191.83 275.17
December 297.00 0.63 0.61 01-DEC-06:00 6661.12 37.76 289.17 286.50 1517.25 28.09 172.00 275.67
                         
Annual Sum or Average 4065.67 0.63     2637.86 24.92 1287.17 3940.50 715.59 22.60 2207.50 3614.00
Minimum of Months 279.67 0.62 0.61   745.77 19.36 0.00 281.50 382.50 20.89 102.67 262.00
Maximum of Months 408.67 0.63 0.61   6782.76 37.76 294.83 378.50 1517.25 28.09 246.67 344.50



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.82 0.80 01-JAN-08:30 301.36 14.31 0.00 238.83 156.01 17.88 0.00 33.67
February 279.67 0.82 0.80 01-FEB-08:09 376.92 15.19 0.00 255.67 180.84 18.52 0.00 90.33
March 338.17 0.82 0.80 01-MAR-07:30 451.38 15.76 0.00 313.17 207.38 18.97 0.00 177.17
April 358.33 0.81 0.80 01-APR-06:30 475.61 16.70 0.00 343.00 232.82 19.97 14.00 269.17
May 393.83 0.81 0.80 01-MAY-05:00 639.55 17.65 12.50 386.67 287.88 20.86 61.17 345.50
June 381.00 0.81 0.80 01-JUN-05:49 677.31 19.68 58.83 380.83 313.34 22.08 109.67 340.17
July 408.67 0.81 0.80 01-JUL-05:19 615.82 18.94 44.67 390.00 271.44 20.54 86.50 357.83
August 390.67 0.81 0.80 01-AUG-06:40 487.91 16.78 0.00 370.33 234.53 20.07 34.00 297.17
September 328.83 0.81 0.80 01-SEP-06:30 419.01 16.05 0.00 310.83 208.00 19.34 0.00 183.50
October 296.17 0.83 0.80 01-OCT-09:39 312.26 14.67 0.00 253.17 158.55 18.12 0.00 56.50
November 300.00 0.83 0.80 01-NOV-07:10 309.11 14.12 0.00 243.67 157.57 17.57 0.00 51.67
December 297.00 0.83 0.80 01-DEC-07:40 271.81 13.78 0.00 229.83 144.72 17.41 0.00 19.33
                         
Annual Sum or Average 4065.67 0.82     460.64 16.35 116.00 3716.00 219.11 19.44 305.33 2222.00
Minimum of Months 279.67 0.81 0.80   271.81 13.78 0.00 229.83 144.72 17.41 0.00 19.33
Maximum of Months 408.67 0.83 0.80   677.31 19.68 58.83 390.00 313.34 22.08 109.67 357.83



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.82 0.80 01-JAN-08:30 301.36 14.31 0.00 238.83 156.01 17.88 0.00 33.67
February 279.67 0.82 0.80 01-FEB-08:09 376.92 15.19 0.00 255.67 180.84 18.52 0.00 90.33
March 338.17 0.82 0.80 01-MAR-07:30 451.38 15.76 0.00 313.17 207.38 18.97 0.00 177.17
April 358.33 0.81 0.80 01-APR-06:30 475.61 16.70 0.00 343.00 232.82 19.97 14.00 269.17
May 393.83 0.81 0.80 01-MAY-05:00 639.55 17.65 12.50 386.67 287.88 20.86 61.17 345.50
June 381.00 0.81 0.80 01-JUN-05:49 677.31 19.68 58.83 380.83 313.34 22.08 109.67 340.17
July 408.67 0.81 0.80 01-JUL-05:19 615.82 18.94 44.67 390.00 271.44 20.54 86.50 357.83
August 390.67 0.81 0.80 01-AUG-06:40 487.91 16.78 0.00 370.33 234.53 20.07 34.00 297.17
September 328.83 0.81 0.80 01-SEP-06:30 419.01 16.05 0.00 310.83 208.00 19.34 0.00 183.50
October 296.17 0.83 0.80 01-OCT-09:39 312.26 14.67 0.00 253.17 158.55 18.12 0.00 56.50
November 300.00 0.83 0.80 01-NOV-07:10 309.11 14.12 0.00 243.67 157.57 17.57 0.00 51.67
December 297.00 0.83 0.80 01-DEC-07:40 271.81 13.78 0.00 229.83 144.72 17.41 0.00 19.33
                         
Annual Sum or Average 4065.67 0.82     460.64 16.35 116.00 3716.00 219.11 19.44 305.33 2222.00
Minimum of Months 279.67 0.81 0.80   271.81 13.78 0.00 229.83 144.72 17.41 0.00 19.33
Maximum of Months 408.67 0.83 0.80   677.31 19.68 58.83 390.00 313.34 22.08 109.67 357.83



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.989590E+11 127747.89 08-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 0.686204E+11 126477.63 06-FEB-23:00 0.00 0.00 0.00 0.00 0.00
March 0.988612E+11 127599.62 29-MAR-20:30 0.00 0.00 0.00 0.00 0.00
April 0.371493E+11 106908.07 01-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 0.324143E+11 95727.35 14-MAY-04:00 0.00 0.00 0.00 0.00 0.00
June 0.508468E+10 51968.68 13-JUN-05:00 0.00 0.00 0.00 0.00 0.00
July 0.275393E+09 20211.25 06-JUL-03:00 0.00 0.00 0.00 0.00 0.00
August 69849887.12 5182.08 31-AUG-04:00 0.00 0.00 0.00 0.00 0.00
September 0.233899E+10 49132.85 20-SEP-03:00 0.00 0.00 0.00 0.00 0.00
October 0.134289E+11 81240.71 12-OCT-06:00 0.00 0.00 0.00 0.00 0.00
November 0.569776E+11 128935.97 29-NOV-23:00 0.00 0.00 0.00 0.00 0.00
December 0.950321E+11 127807.41 12-DEC-21:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.509212E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 69849887.12 5182.08   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.989590E+11 128935.97   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.252693E+09 1845.89 08-JAN-06:50 0.00 0.00 0.00 0.00 0.00
February 0.302483E+09 995.42 25-FEB-18:00 0.00 0.00 0.00 0.00 0.00
March 0.504795E+09 1603.24 30-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 0.126058E+09 1045.16 01-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.170397E+09 811.52 14-MAY-04:40 0.00 0.00 0.00 0.00 0.00
June 27542017.62 327.91 13-JUN-04:00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 386138.92 351.68 18-SEP-10:37 0.00 0.00 0.00 0.00 0.00
October 13594708.35 418.72 25-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 68905624.97 495.20 05-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.150149E+09 1007.39 13-DEC-04:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.161700E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.504795E+09 1845.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 183565.18 119.45 29-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 183565.18     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 183565.18 119.45   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 15442854.46 598.37 03-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 32305.76 41.37 28-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 20398856.22 530.48 30-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 65938.46 118.11 01-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 35939954.90     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 20398856.22 598.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 15820494.43 343.29 08-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 1503850.95 120.51 28-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 21278538.99 318.26 30-MAR-03:10 0.00 0.00 0.00 0.00 0.00
April 297036.94 44.60 01-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 38899921.32     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 21278538.99 343.29   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.364282E+09 7924.13 03-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 0.141179E+09 3532.30 04-FEB-06:00 0.00 0.00 0.00 0.00 0.00
March 0.303775E+09 5969.22 30-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 0.101548E+09 1585.67 01-APR-05:00 0.00 0.00 0.00 0.00 0.00
May 88966319.84 1334.38 13-MAY-04:50 0.00 0.00 0.00 0.00 0.00
June 48586303.93 914.79 12-JUN-03:50 0.00 0.00 0.00 0.00 0.00
July 23114121.86 562.84 10-JUL-04:00 0.00 0.00 0.00 0.00 0.00
August 20100082.07 562.97 28-AUG-04:00 0.00 0.00 0.00 0.00 0.00
September 43263421.22 740.83 19-SEP-04:00 0.00 0.00 0.00 0.00 0.00
October 44344248.35 874.16 28-OCT-05:00 0.00 0.00 0.00 0.00 0.00
November 0.118402E+09 1254.29 06-NOV-04:50 0.00 0.00 0.00 0.00 0.00
December 0.149792E+09 3789.66 23-DEC-06:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.144735E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 20100082.07 562.84   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.364282E+09 7924.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 9592236.05 1795.90 08-JAN-06:50 0.00 0.00 0.00 0.00 0.00
February 49297223.38 1704.93 12-FEB-16:00 0.00 0.00 0.00 0.00 0.00
March 84410238.39 3051.30 29-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 431895.03 553.31 22-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 3244333.87 1361.82 09-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 257632.93 350.62 08-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 413473.46 571.45 18-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 152492.28 254.15 12-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.147800E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 84410238.39 3051.30   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 36980844.90 2788.95 03-JAN-07:07 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 32826052.10 1947.80 30-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 69806896.99     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 36980844.90 2788.95   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.195038E+09 3264.85 08-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 24229312.02 825.23 28-FEB-11:35 0.00 0.00 0.00 0.00 0.00
March 0.195010E+09 2391.06 30-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 10255135.62 979.26 01-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 30376701.79 969.92 13-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.454909E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.195038E+09 3264.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 2333122.75 1010.15 09-JAN-06:00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 1258231.76 683.04 30-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 3591354.51     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 2333122.75 1010.15   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.147285E+11 14923.41 08-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 0.118617E+11 14101.57 05-FEB-06:00 0.00 0.00 0.00 0.00 0.00
March 0.159855E+11 14310.90 30-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 0.718571E+10 13687.88 01-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 0.618449E+10 13483.38 14-MAY-04:30 0.00 0.00 0.00 0.00 0.00
June 0.108226E+10 8912.65 13-JUN-04:00 0.00 0.00 0.00 0.00 0.00
July 62562347.84 4002.30 06-JUL-01:00 0.00 0.00 0.00 0.00 0.00
August 29890880.57 1528.18 24-AUG-02:00 0.00 0.00 0.00 0.00 0.00
September 0.542137E+09 8913.69 20-SEP-03:00 0.00 0.00 0.00 0.00 0.00
October 0.245036E+10 13274.30 28-OCT-05:00 0.00 0.00 0.00 0.00 0.00
November 0.100455E+11 13690.40 05-NOV-03:10 0.00 0.00 0.00 0.00 0.00
December 0.146291E+11 14104.79 24-DEC-04:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.847876E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 29890880.57 1528.18   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.159855E+11 14923.41   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.567249E+09 6585.15 01-JAN-19:02 0.00 0.00 0.00 0.00 0.00
February 0.402775E+09 6607.73 25-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.645226E+09 6700.03 29-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 97544399.96 2730.24 11-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 73130598.95 2854.07 28-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 6853425.71 2432.85 05-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 3239905.80 3037.11 23-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 3362327.72 2950.96 19-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 4109239.29 2449.79 20-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 21593378.89 2621.84 14-OCT-08:05 0.00 0.00 0.00 0.00 0.00
November 0.173133E+09 3622.83 24-NOV-16:03 0.00 0.00 0.00 0.00 0.00
December 0.419887E+09 4749.73 12-DEC-19:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.241810E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3239905.80 2432.85   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.645226E+09 6700.03   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.112014E+10 6613.23 12-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.662265E+09 6579.16 25-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.877611E+09 6663.54 29-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 0.134632E+09 5327.55 01-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 74180589.92 2737.24 14-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 7023602.27 2507.22 02-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 3506963.68 2390.54 22-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 4047470.96 2947.96 19-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 5905503.20 2691.54 03-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 52114531.22 2836.75 24-OCT-15:04 0.00 0.00 0.00 0.00 0.00
November 0.415852E+09 4449.88 05-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 0.899832E+09 6602.34 13-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.425711E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3506963.68 2390.54   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.112014E+10 6663.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 15007835.11 2392.26 30-MAR-05:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 15007835.11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 15007835.11 2392.26   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.339853E+10 37779.30 12-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.995392E+09 27557.61 04-FEB-16:03 0.00 0.00 0.00 0.00 0.00
March 0.188031E+10 37908.58 29-MAR-15:02 0.00 0.00 0.00 0.00 0.00
April 0.194629E+09 26469.14 28-APR-15:04 0.00 0.00 0.00 0.00 0.00
May 0.107472E+09 27048.60 20-MAY-15:05 0.00 0.00 0.00 0.00 0.00
June 41233284.28 20842.66 09-JUN-15:05 0.00 0.00 0.00 0.00 0.00
July 29069682.84 18174.55 18-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 50071136.51 20346.26 15-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 72003953.72 24036.10 02-SEP-15:04 0.00 0.00 0.00 0.00 0.00
October 0.101390E+09 27227.92 16-OCT-08:05 0.00 0.00 0.00 0.00 0.00
November 0.901297E+09 27496.58 04-NOV-15:03 0.00 0.00 0.00 0.00 0.00
December 0.259436E+10 37620.05 15-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.103658E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 29069682.84 18174.55   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.339853E+10 37908.58   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.558392E+09 5448.95 01-JAN-19:02 0.00 0.00 0.00 0.00 0.00
February 0.473833E+09 6461.90 25-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.698437E+09 6544.51 29-MAR-18:02 0.00 0.00 0.00 0.00 0.00
April 0.117549E+09 3000.48 15-APR-15:04 0.00 0.00 0.00 0.00 0.00
May 0.110419E+09 2419.29 06-MAY-18:03 0.00 0.00 0.00 0.00 0.00
June 12504666.76 2265.50 08-JUN-15:05 0.00 0.00 0.00 0.00 0.00
July 1679897.04 1625.37 05-JUL-18:05 0.00 0.00 0.00 0.00 0.00
August 742289.83 1574.18 29-AUG-18:05 0.00 0.00 0.00 0.00 0.00
September 3573094.24 1917.27 18-SEP-15:05 0.00 0.00 0.00 0.00 0.00
October 26035717.57 1850.98 06-OCT-15:05 0.00 0.00 0.00 0.00 0.00
November 0.213118E+09 3106.19 24-NOV-16:03 0.00 0.00 0.00 0.00 0.00
December 0.451739E+09 6052.44 12-DEC-19:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.266802E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 742289.83 1574.18   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.698437E+09 6544.51   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.107568E+10 6454.25 02-JAN-19:03 0.00 0.00 0.00 0.00 0.00
February 0.753479E+09 6428.93 25-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.936364E+09 6511.21 29-MAR-18:02 0.00 0.00 0.00 0.00 0.00
April 0.172595E+09 3174.23 22-APR-15:03 0.00 0.00 0.00 0.00 0.00
May 0.119370E+09 2421.82 15-MAY-15:05 0.00 0.00 0.00 0.00 0.00
June 11566904.02 2263.84 07-JUN-15:05 0.00 0.00 0.00 0.00 0.00
July 608859.34 1553.12 12-JUL-18:05 0.00 0.00 0.00 0.00 0.00
August 1074342.87 1628.14 27-AUG-18:05 0.00 0.00 0.00 0.00 0.00
September 11672405.81 2268.77 24-SEP-15:05 0.00 0.00 0.00 0.00 0.00
October 68417791.85 2498.72 24-OCT-15:04 0.00 0.00 0.00 0.00 0.00
November 0.493807E+09 3353.60 23-NOV-16:03 0.00 0.00 0.00 0.00 0.00
December 0.931698E+09 6433.71 13-DEC-19:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.457634E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 608859.34 1553.12   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.107568E+10 6511.21   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.293541E+09 1989.04 01-JAN-19:02 0.00 0.00 0.00 0.00 0.00
February 0.242827E+09 2003.11 25-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.321638E+09 2026.63 29-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 72191270.12 1723.92 01-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 65803211.00 862.48 12-MAY-15:05 0.00 0.00 0.00 0.00 0.00
June 11378862.58 618.87 23-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 781441.95 632.45 23-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 1074029.95 601.75 19-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 3516502.53 564.75 29-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 33447463.15 805.90 24-OCT-15:04 0.00 0.00 0.00 0.00 0.00
November 0.145778E+09 1124.90 24-NOV-09:02 0.00 0.00 0.00 0.00 0.00
December 0.253538E+09 1984.46 12-DEC-19:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.144551E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 781441.95 564.75   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.321638E+09 2026.63   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.535715E+09 1998.42 12-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.363508E+09 1991.64 25-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.417709E+09 2011.66 29-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 99632363.77 1960.50 01-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 67748849.82 756.09 20-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 10907431.10 612.82 08-JUN-15:05 0.00 0.00 0.00 0.00 0.00
July 782757.87 677.90 23-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 1221429.54 600.07 19-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 7275451.86 562.58 06-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 65340656.10 1959.46 30-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.289602E+09 1967.28 24-NOV-09:02 0.00 0.00 0.00 0.00 0.00
December 0.488825E+09 1995.47 13-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.234827E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 782757.87 562.58   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.535715E+09 2011.66   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.324386E+09 2691.91 01-JAN-16:05 0.00 0.00 0.00 0.00 0.00
February 0.348780E+09 9442.31 25-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.752806E+09 9581.20 29-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 0.154112E+09 4101.55 17-APR-15:05 0.00 0.00 0.00 0.00 0.00
May 0.241258E+09 5919.37 12-MAY-15:05 0.00 0.00 0.00 0.00 0.00
June 35460767.14 3509.61 08-JUN-15:05 0.00 0.00 0.00 0.00 0.00
July 9203315.49 3229.78 29-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 5635367.79 3143.63 06-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 4860530.25 2471.99 18-SEP-18:04 0.00 0.00 0.00 0.00 0.00
October 23675578.10 4307.92 23-OCT-15:05 0.00 0.00 0.00 0.00 0.00
November 80639012.46 4017.56 24-NOV-16:05 0.00 0.00 0.00 0.00 0.00
December 0.223691E+09 2640.45 13-DEC-06:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.220451E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 4860530.25 2471.99   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.752806E+09 9581.20   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.572450E+11 0.571054E+11 208585.96 14-JAN-11:45 208585.96 0.21
February 0.00 0.00 0.316038E+11 0.308895E+11 196578.24 01-FEB-11:45 196578.24 0.20
March 0.00 0.00 0.353233E+11 0.346290E+11 183126.88 23-MAR-10:50 146052.42 0.22
April 0.00 0.00 0.843398E+11 0.827112E+11 251962.06 26-APR-10:45 204536.53 0.44
May 0.00 0.00 0.901865E+11 0.891896E+11 161605.97 18-MAY-10:50 142285.93 0.52
June 0.00 0.00 0.168634E+12 0.146349E+12 312457.46 29-JUN-10:50 191271.96 0.85
July 0.00 0.00 0.346290E+12 0.224669E+12 381630.33 31-JUL-10:45 224186.46 0.99
August 0.00 0.00 0.390374E+12 0.234633E+12 409086.71 14-AUG-10:45 241002.03 0.99
September 0.00 0.00 0.229545E+12 0.176186E+12 373514.51 22-SEP-12:00 184847.47 0.90
October 0.00 0.00 0.260389E+12 0.209062E+12 384410.71 16-OCT-10:50 384410.71 0.59
November 0.00 0.00 0.593969E+11 0.587286E+11 213511.11 19-NOV-11:50 213511.11 0.28
December 0.00 0.00 0.661316E+11 0.661316E+11 192550.31 16-DEC-13:00 192550.31 0.09
                 
Annual Sum or Average 0.00 0.00 0.181946E+13 0.141028E+13       0.53
Minimum of Months 0.00 0.00 0.316038E+11 0.308895E+11 161605.97   142285.93 0.09
Maximum of Months 0.00 0.00 0.390374E+12 0.234633E+12 409086.71   384410.71 0.99



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.113067E+11 0.111344E+11 35831.89 17-JAN-14:00 29957.41 0.20
February 0.00 0.00 0.624901E+10 0.601784E+10 34702.50 01-FEB-12:00 34702.50 0.18
March 0.00 0.00 0.724922E+10 0.662458E+10 38122.69 23-MAR-15:00 25060.26 0.20
April 0.00 0.00 0.170527E+11 0.156679E+11 45682.01 26-APR-11:00 34952.45 0.41
May 0.00 0.00 0.176695E+11 0.169867E+11 33097.58 04-MAY-13:10 27478.84 0.49
June 0.00 0.00 0.354046E+11 0.276503E+11 50379.43 29-JUN-11:00 30610.28 0.84
July 0.00 0.00 0.697043E+11 0.417303E+11 59117.88 31-JUL-12:20 36173.22 0.99
August 0.00 0.00 0.780509E+11 0.433674E+11 59096.39 14-AUG-10:55 36182.71 0.99
September 0.00 0.00 0.472441E+11 0.329404E+11 61100.16 22-SEP-12:00 30033.85 0.89
October 0.00 0.00 0.510747E+11 0.388693E+11 61507.15 16-OCT-10:55 61507.15 0.58
November 0.00 0.00 0.116003E+11 0.113170E+11 37158.21 19-NOV-13:00 37158.21 0.25
December 0.00 0.00 0.131328E+11 0.131083E+11 34610.58 16-DEC-13:00 34610.58 0.08
                 
Annual Sum or Average 0.00 0.00 0.365739E+12 0.265414E+12       0.51
Minimum of Months 0.00 0.00 0.624901E+10 0.601784E+10 33097.58   25060.26 0.08
Maximum of Months 0.00 0.00 0.780509E+11 0.433674E+11 61507.15   61507.15 0.99



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.167757E+10 0.105151E+10 11929.51 14-JAN-16:02 11929.51 0.37
February 0.00 0.00 0.152445E+10 0.101002E+10 11678.58 03-FEB-16:02 11678.58 0.34
March 0.00 0.00 0.160785E+10 0.968103E+09 11815.35 10-MAR-16:02 11815.35 0.37
April 0.00 0.00 0.340876E+10 0.196408E+10 11922.54 01-APR-15:01 11922.54 0.69
May 0.00 0.00 0.310158E+10 0.170419E+10 11743.85 05-MAY-15:02 10466.87 0.69
June 0.00 0.00 0.460590E+10 0.248976E+10 12184.22 30-JUN-08:62 9717.20 0.79
July 0.00 0.00 0.685750E+10 0.381100E+10 13164.59 23-JUL-08:62 10388.13 0.87
August 0.00 0.00 0.719296E+10 0.399312E+10 13523.18 19-AUG-08:62 9923.57 0.89
September 0.00 0.00 0.552526E+10 0.304819E+10 13118.57 22-SEP-08:62 9093.77 0.86
October 0.00 0.00 0.513354E+10 0.349989E+10 13275.74 01-OCT-08:62 9616.71 0.61
November 0.00 0.00 0.234656E+10 0.146174E+10 12055.01 19-NOV-09:02 12055.01 0.48
December 0.00 0.00 0.198098E+10 0.159187E+10 11917.15 05-DEC-16:02 11917.15 0.24
                 
Annual Sum or Average 0.00 0.00 0.449629E+11 0.265935E+11       0.60
Minimum of Months 0.00 0.00 0.152445E+10 0.968103E+09 11678.58   9093.77 0.24
Maximum of Months 0.00 0.00 0.719296E+10 0.399312E+10 13523.18   12055.01 0.89



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.396938E+09 0.225828E+09 11446.81 14-JAN-16:02 11446.81 0.17
February 0.00 0.00 0.558520E+09 0.344585E+09 11205.46 03-FEB-16:02 11205.46 0.20
March 0.00 0.00 0.853553E+09 0.496276E+09 11336.92 10-MAR-16:02 11336.92 0.24
April 0.00 0.00 0.261472E+10 0.146576E+10 11439.41 01-APR-15:01 11439.41 0.62
May 0.00 0.00 0.292197E+10 0.161743E+10 11230.55 02-MAY-18:02 9996.77 0.67
June 0.00 0.00 0.465320E+10 0.257987E+10 11689.22 30-JUN-08:62 9409.03 0.79
July 0.00 0.00 0.674789E+10 0.381449E+10 12627.80 23-JUL-08:62 10020.40 0.85
August 0.00 0.00 0.645108E+10 0.351908E+10 12946.53 19-AUG-08:62 9476.78 0.84
September 0.00 0.00 0.424767E+10 0.217541E+10 12915.19 21-SEP-15:02 10542.22 0.79
October 0.00 0.00 0.342109E+10 0.213797E+10 12772.75 05-OCT-15:02 10021.71 0.53
November 0.00 0.00 0.735816E+09 0.389047E+09 11176.40 10-NOV-16:02 10173.88 0.31
December 0.00 0.00 0.429877E+09 0.348158E+09 11434.15 05-DEC-16:02 11434.15 0.10
                 
Annual Sum or Average 0.00 0.00 0.340323E+11 0.191139E+11       0.51
Minimum of Months 0.00 0.00 0.396938E+09 0.225828E+09 11176.40   9409.03 0.10
Maximum of Months 0.00 0.00 0.674789E+10 0.381449E+10 12946.53   11446.81 0.85



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.211135E+11 0.179172E+11 39662.68 14-JAN-12:40 39662.68 0.26
February 0.00 0.00 0.131170E+11 0.111413E+11 35465.32 02-FEB-12:40 35465.32 0.19
March 0.00 0.00 0.649196E+10 0.409571E+10 26740.55 11-MAR-13:30 26740.55 0.21
April 0.00 0.00 0.491772E+10 0.191348E+10 18554.34 08-APR-12:40 10633.71 0.29
May 0.00 0.00 0.494295E+09 0.141755E+09 9160.34 04-MAY-12:30 3380.25 0.04
June 0.00 0.00 62706442.41 7747375.92 3981.21 29-JUN-17:20 763.98 0.02
July 0.00 0.00 0.348987E+10 0.930989E+09 15212.93 31-JUL-12:40 6086.89 0.25
August 0.00 0.00 0.106381E+11 0.383658E+10 20269.30 18-AUG-12:00 9690.94 0.49
September 0.00 0.00 0.146799E+11 0.835094E+10 42675.74 30-SEP-13:20 41640.02 0.47
October 0.00 0.00 0.248966E+11 0.196440E+11 47884.96 16-OCT-12:20 47884.96 0.38
November 0.00 0.00 0.219667E+11 0.181932E+11 44781.56 19-NOV-12:30 44781.56 0.31
December 0.00 0.00 0.250156E+11 0.227463E+11 40370.32 19-DEC-13:00 40370.32 0.20
                 
Annual Sum or Average 0.00 0.00 0.146884E+12 0.108919E+12       0.26
Minimum of Months 0.00 0.00 62706442.41 7747375.92 3981.21   763.98 0.02
Maximum of Months 0.00 0.00 0.250156E+11 0.227463E+11 47884.96   47884.96 0.49



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.625529E+10 0.308970E+10 61071.85 21-JAN-09:02 52472.99 0.33
February 0.00 0.00 0.685124E+10 0.339437E+10 61815.13 13-FEB-19:03 49513.02 0.42
March 0.00 0.00 0.899609E+10 0.439060E+10 59201.65 24-MAR-15:02 52208.51 0.45
April 0.00 0.00 0.168809E+11 0.834024E+10 61654.77 26-APR-08:62 55197.90 0.66
May 0.00 0.00 0.217435E+11 0.118797E+11 62073.70 06-MAY-08:62 53045.95 0.69
June 0.00 0.00 0.309790E+11 0.169582E+11 70023.53 29-JUN-18:02 56935.31 0.71
July 0.00 0.00 0.403928E+11 0.222747E+11 73697.62 29-JUL-18:02 52529.64 0.71
August 0.00 0.00 0.372729E+11 0.192001E+11 73413.17 19-AUG-08:62 54611.96 0.71
September 0.00 0.00 0.253313E+11 0.119549E+11 71223.61 22-SEP-08:62 50041.88 0.70
October 0.00 0.00 0.228420E+11 0.138766E+11 73594.49 01-OCT-08:62 51531.83 0.52
November 0.00 0.00 0.836355E+10 0.434354E+10 62934.17 12-NOV-09:02 51238.62 0.42
December 0.00 0.00 0.546331E+10 0.370225E+10 60549.93 05-DEC-09:02 60549.93 0.20
                 
Annual Sum or Average 0.00 0.00 0.231372E+12 0.123405E+12       0.54
Minimum of Months 0.00 0.00 0.546331E+10 0.308970E+10 59201.65   49513.02 0.20
Maximum of Months 0.00 0.00 0.403928E+11 0.222747E+11 73697.62   60549.93 0.71



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.177537E+10 0.121757E+10 10450.78 14-JAN-16:02 10450.78 0.38
February 0.00 0.00 0.141568E+10 0.995173E+09 10371.29 01-FEB-09:02 10371.29 0.31
March 0.00 0.00 0.158181E+10 0.982038E+09 10350.59 10-MAR-16:02 10350.59 0.37
April 0.00 0.00 0.305241E+10 0.178156E+10 10444.33 01-APR-15:01 10444.33 0.69
May 0.00 0.00 0.262533E+10 0.146614E+10 10381.43 03-MAY-08:62 9340.99 0.64
June 0.00 0.00 0.384522E+10 0.203496E+10 11170.86 28-JUN-15:02 9448.58 0.82
July 0.00 0.00 0.619719E+10 0.337836E+10 11632.36 24-JUL-18:02 9025.98 0.92
August 0.00 0.00 0.682480E+10 0.374731E+10 11522.98 13-AUG-18:02 8957.02 0.93
September 0.00 0.00 0.469226E+10 0.255503E+10 12019.78 21-SEP-15:02 9490.68 0.88
October 0.00 0.00 0.484046E+10 0.337393E+10 11653.92 05-OCT-15:02 9155.67 0.61
November 0.00 0.00 0.213919E+10 0.145854E+10 10560.53 19-NOV-09:02 10560.53 0.45
December 0.00 0.00 0.197589E+10 0.167452E+10 10553.10 05-DEC-09:02 10553.10 0.22
                 
Annual Sum or Average 0.00 0.00 0.409656E+11 0.246652E+11       0.60
Minimum of Months 0.00 0.00 0.141568E+10 0.982038E+09 10350.59   8957.02 0.22
Maximum of Months 0.00 0.00 0.682480E+10 0.374731E+10 12019.78   10560.53 0.93



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.554613E+09 0.343863E+09 9791.04 21-JAN-09:02 8442.23 0.18
February 0.00 0.00 0.526729E+09 0.349499E+09 9627.52 01-FEB-09:02 9627.52 0.18
March 0.00 0.00 0.840309E+09 0.484219E+09 9964.39 23-MAR-15:02 9238.05 0.24
April 0.00 0.00 0.226941E+10 0.131612E+10 10013.89 27-APR-08:62 8674.71 0.54
May 0.00 0.00 0.245638E+10 0.139075E+10 9986.96 03-MAY-08:62 8946.69 0.60
June 0.00 0.00 0.387558E+10 0.211615E+10 10725.63 28-JUN-15:02 9060.76 0.81
July 0.00 0.00 0.605871E+10 0.336823E+10 11150.52 24-JUL-18:02 8665.96 0.91
August 0.00 0.00 0.602291E+10 0.327006E+10 11090.40 18-AUG-18:02 8573.16 0.91
September 0.00 0.00 0.341423E+10 0.175982E+10 11550.72 21-SEP-15:02 9094.87 0.75
October 0.00 0.00 0.309766E+10 0.202022E+10 11276.35 01-OCT-15:02 8737.89 0.50
November 0.00 0.00 0.716842E+09 0.445051E+09 10131.72 19-NOV-09:02 10131.72 0.26
December 0.00 0.00 0.530637E+09 0.453635E+09 10125.24 05-DEC-09:02 10125.24 0.08
                 
Annual Sum or Average 0.00 0.00 0.303640E+11 0.173176E+11       0.50
Minimum of Months 0.00 0.00 0.526729E+09 0.343863E+09 9627.52   8442.23 0.08
Maximum of Months 0.00 0.00 0.605871E+10 0.336823E+10 11550.72   10131.72 0.91



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.313628E+09 0.205366E+09 3095.08 21-JAN-09:02 2262.22 0.26
February 0.00 0.00 0.301922E+09 0.207315E+09 3022.38 03-FEB-16:02 3022.38 0.23
March 0.00 0.00 0.351290E+09 0.223317E+09 3057.80 10-MAR-16:02 3057.80 0.27
April 0.00 0.00 0.780373E+09 0.473370E+09 3155.92 26-APR-08:62 2472.82 0.57
May 0.00 0.00 0.687295E+09 0.399465E+09 3119.83 03-MAY-08:62 2365.55 0.56
June 0.00 0.00 0.107496E+10 0.595907E+09 3259.91 30-JUN-08:62 2426.50 0.75
July 0.00 0.00 0.166885E+10 0.921015E+09 3518.97 23-JUL-08:62 2581.96 0.89
August 0.00 0.00 0.172563E+10 0.940275E+09 3615.85 19-AUG-08:62 2439.44 0.90
September 0.00 0.00 0.124165E+10 0.689069E+09 3427.36 09-SEP-08:62 2373.13 0.84
October 0.00 0.00 0.111639E+10 0.764593E+09 3541.27 01-OCT-08:62 2348.95 0.54
November 0.00 0.00 0.440913E+09 0.278623E+09 3090.47 19-NOV-09:02 3090.47 0.35
December 0.00 0.00 0.366628E+09 0.304996E+09 3084.09 05-DEC-16:02 3084.09 0.16
                 
Annual Sum or Average 0.00 0.00 0.100695E+11 0.600331E+10       0.53
Minimum of Months 0.00 0.00 0.301922E+09 0.205366E+09 3022.38   2262.22 0.16
Maximum of Months 0.00 0.00 0.172563E+10 0.940275E+09 3615.85   3090.47 0.90



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 57610929.74 38175223.26 2953.80 14-JAN-16:02 2953.80 0.08
February 0.00 0.00 93999769.81 65507291.98 2891.52 03-FEB-16:02 2891.52 0.10
March 0.00 0.00 0.177157E+09 0.112044E+09 2925.41 10-MAR-16:02 2925.41 0.15
April 0.00 0.00 0.581347E+09 0.347682E+09 3008.10 26-APR-08:62 2338.91 0.47
May 0.00 0.00 0.639517E+09 0.376636E+09 2973.79 03-MAY-08:62 2242.38 0.54
June 0.00 0.00 0.108174E+10 0.610800E+09 3115.06 30-JUN-08:62 2346.47 0.75
July 0.00 0.00 0.163473E+10 0.911334E+09 3362.30 23-JUL-08:62 2486.45 0.87
August 0.00 0.00 0.152123E+10 0.816673E+09 3455.01 19-AUG-08:62 2319.80 0.86
September 0.00 0.00 0.896266E+09 0.472317E+09 3315.11 21-SEP-15:02 2730.65 0.75
October 0.00 0.00 0.686723E+09 0.438813E+09 3398.48 01-OCT-08:62 2190.73 0.44
November 0.00 0.00 98484518.06 57942258.37 2889.94 10-NOV-16:02 2621.93 0.14
December 0.00 0.00 59379140.44 51328712.73 2950.51 05-DEC-16:02 2950.51 0.03
                 
Annual Sum or Average 0.00 0.00 0.752818E+10 0.429925E+10       0.43
Minimum of Months 0.00 0.00 57610929.74 38175223.26 2889.94   2190.73 0.03
Maximum of Months 0.00 0.00 0.163473E+10 0.911334E+09 3455.01   2953.80 0.87



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.666781E+10 0.540311E+10 14400.58 14-JAN-16:02 14400.58 0.51
February 0.00 0.00 0.429756E+10 0.334891E+10 14098.65 03-FEB-16:02 14098.65 0.45
March 0.00 0.00 0.352153E+10 0.229234E+10 14263.23 10-MAR-16:02 14263.23 0.49
April 0.00 0.00 0.424207E+10 0.235058E+10 14392.95 01-APR-15:01 14392.95 0.71
May 0.00 0.00 0.242793E+10 0.114391E+10 14230.38 06-MAY-15:02 13005.56 0.54
June 0.00 0.00 0.348554E+10 0.155435E+10 15655.13 29-JUN-18:02 12503.08 0.70
July 0.00 0.00 0.617776E+10 0.291538E+10 16644.96 24-JUL-18:02 12091.91 0.83
August 0.00 0.00 0.812750E+10 0.409419E+10 16552.29 13-AUG-18:02 11896.32 0.88
September 0.00 0.00 0.786616E+10 0.449974E+10 15880.45 22-SEP-08:62 10926.28 0.88
October 0.00 0.00 0.936631E+10 0.706369E+10 16331.11 01-OCT-18:02 11908.12 0.63
November 0.00 0.00 0.684814E+10 0.531526E+10 14548.63 19-NOV-09:02 14548.63 0.60
December 0.00 0.00 0.733512E+10 0.648983E+10 14538.28 05-DEC-09:02 14538.28 0.36
                 
Annual Sum or Average 0.00 0.00 0.703634E+11 0.464713E+11       0.63
Minimum of Months 0.00 0.00 0.242793E+10 0.114391E+10 14098.65   10926.28 0.36
Maximum of Months 0.00 0.00 0.936631E+10 0.706369E+10 16644.96   14548.63 0.88



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 45336.02 181927.27 08-JAN-07:00
February 0.00 0.00 01-FEB-00:03 34937.89 151955.47 04-FEB-06:00
March 0.00 0.00 01-MAR-00:03 45373.33 185956.25 29-MAR-08:62
April 0.00 0.00 01-APR-00:10 17447.24 136896.41 01-APR-06:00
May 0.00 0.00 01-MAY-00:05 14701.16 116742.77 14-MAY-04:50
June 0.00 0.00 01-JUN-00:05 2441.02 63382.46 13-JUN-04:00
July 0.00 0.00 01-JUL-00:10 156.90 33541.50 18-JUL-08:05
August 0.00 0.00 01-AUG-00:05 66.63 31740.51 29-AUG-18:05
September 0.00 0.00 01-SEP-00:05 1164.91 59258.40 20-SEP-04:00
October 0.00 0.00 01-OCT-00:10 6039.08 97168.53 29-OCT-06:00
November 0.00 0.00 01-NOV-00:05 26747.03 144072.18 29-NOV-23:00
December 0.00 0.00 01-DEC-00:03 43040.82 156372.34 23-DEC-06:00
             
Annual Sum or Average 0.00     19749.04    
Minimum of Months 0.00 0.00   66.63 31740.51  
Maximum of Months 0.00 0.00   45373.33 185956.25  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 43697.86 301569.72 14-JAN-11:33 0.00 0.00 01-JAN-00:10
February 30913.37 283067.89 01-FEB-09:02 0.00 0.00 01-FEB-00:03
March 28127.59 319709.88 23-MAR-15:02 0.00 0.00 01-MAR-00:03
April 58331.92 310300.87 26-APR-10:45 0.00 0.00 01-APR-00:10
May 58510.11 349838.88 18-MAY-15:02 0.00 0.00 01-MAY-00:05
June 104347.26 468120.75 29-JUN-18:03 0.00 0.00 01-JUN-00:05
July 190386.04 547707.06 31-JUL-18:03 0.00 0.00 01-JUL-00:10
August 212533.24 548150.58 18-AUG-15:03 0.00 0.00 01-AUG-00:05
September 138145.82 501377.32 29-SEP-15:02 0.00 0.00 01-SEP-00:05
October 149573.66 525519.36 14-OCT-15:02 0.00 0.00 01-OCT-00:10
November 48249.55 357548.61 19-NOV-09:02 0.00 0.00 01-NOV-00:05
December 49382.42 334891.99 05-DEC-09:02 0.00 0.00 01-DEC-00:03
             
Annual Sum or Average 93250.27     0.00    
Minimum of Months 28127.59 283067.89   0.00 0.00  
Maximum of Months 212533.24 548150.58   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 24241.71 49031.35 31-JAN-07:20
February 0.00 0.00 01-FEB-00:03 24271.54 49034.02 01-FEB-07:30
March 0.00 0.00 01-MAR-00:03 24039.58 48751.99 01-MAR-07:50
April 0.00 0.00 01-APR-00:10 23559.33 47892.22 04-APR-06:20
May 0.00 0.00 01-MAY-00:05 22999.63 46886.13 02-MAY-06:45
June 0.00 0.00 01-JUN-00:05 22503.26 45690.28 01-JUN-06:20
July 0.00 0.00 01-JUL-00:10 22173.39 44779.11 03-JUL-06:15
August 0.00 0.00 01-AUG-00:05 22161.83 44690.92 31-AUG-06:20
September 0.00 0.00 01-SEP-00:05 22406.70 45422.39 29-SEP-06:20
October 0.00 0.00 01-OCT-00:10 22870.18 46574.03 31-OCT-06:30
November 0.00 0.00 01-NOV-00:05 23433.60 47721.50 30-NOV-07:20
December 0.00 0.00 01-DEC-00:03 23932.85 48581.99 29-DEC-07:40
             
Annual Sum or Average 0.00     23210.09    
Minimum of Months 0.00 0.00   22161.83 44690.92  
Maximum of Months 0.00 0.00   24271.54 49034.02  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.587890E+10 0.89 2194.93 01-JAN-00:10 0.89
February 0.530997E+10 0.89 2194.93 01-FEB-00:03 0.89
March 0.587890E+10 0.89 2194.93 01-MAR-00:03 0.89
April 0.568926E+10 0.89 2194.93 01-APR-00:10 0.89
May 0.587890E+10 0.89 2194.93 01-MAY-00:05 0.88
June 0.568926E+10 0.89 2194.93 01-JUN-00:05 0.89
July 0.587890E+10 0.89 2194.93 01-JUL-00:10 0.88
August 0.587890E+10 0.89 2194.93 01-AUG-00:05 0.89
September 0.568926E+10 0.89 2194.93 01-SEP-00:05 0.88
October 0.587890E+10 0.89 2194.93 01-OCT-00:10 0.89
November 0.568926E+10 0.89 2194.93 01-NOV-00:05 0.89
December 0.587890E+10 0.89 2194.93 01-DEC-00:03 0.90
           
Annual Sum or Average 0.692193E+11 0.89      
Minimum of Months 0.530997E+10 0.89 2194.93   0.88
Maximum of Months 0.587890E+10 0.89 2194.93   0.90



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.362558E+11 0.87 24963.38 18-JAN-22:10 1.24
February 0.327383E+11 0.87 23429.79 01-FEB-22:10 1.20
March 0.360980E+11 0.86 23237.41 24-MAR-21:10 1.19
April 0.357103E+11 0.87 24250.74 26-APR-21:10 1.22
May 0.371815E+11 0.88 25339.90 04-MAY-21:10 1.25
June 0.368371E+11 0.89 25087.94 27-JUN-21:10 1.24
July 0.386167E+11 0.89 26100.10 31-JUL-21:10 1.27
August 0.388967E+11 0.90 26480.46 18-AUG-21:10 1.28
September 0.370456E+11 0.89 28547.92 29-SEP-21:10 1.36
October 0.389313E+11 0.90 30185.71 16-OCT-21:10 1.41
November 0.358542E+11 0.88 25187.70 28-NOV-22:10 1.26
December 0.366770E+11 0.87 26821.02 05-DEC-22:10 1.31
           
Annual Sum or Average 0.440843E+12 0.88      
Minimum of Months 0.327383E+11 0.86 23237.41   1.19
Maximum of Months 0.389313E+11 0.90 30185.71   1.41



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.27 76.61 01-JAN-00:10 0.27
February 0.185347E+09 0.27 76.61 01-FEB-00:03 0.27
March 0.205205E+09 0.27 76.61 01-MAR-00:03 0.27
April 0.198586E+09 0.27 76.61 01-APR-00:10 0.27
May 0.205205E+09 0.27 76.61 01-MAY-00:05 0.27
June 0.198586E+09 0.27 76.61 01-JUN-00:05 0.27
July 0.205205E+09 0.27 76.61 01-JUL-00:10 0.27
August 0.205205E+09 0.27 76.61 01-AUG-00:05 0.27
September 0.198586E+09 0.27 76.61 01-SEP-00:05 0.27
October 0.205205E+09 0.27 76.61 01-OCT-00:10 0.27
November 0.198586E+09 0.27 76.61 01-NOV-00:05 0.27
December 0.205205E+09 0.27 76.61 01-DEC-00:03 0.27
           
Annual Sum or Average 0.241613E+10 0.27      
Minimum of Months 0.185347E+09 0.27 76.61   0.27
Maximum of Months 0.205205E+09 0.27 76.61   0.27



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:10 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:10 0.00
February 0.00 -0.0 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:10 0.00
February 0.00 -0.0 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00
June 0.00 -0.0 0.00 01-JUN-00:05 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 -0.0 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.19 612.92 01-JAN-07:05 0.27
February 0.105030E+10 0.19 612.92 01-FEB-07:05 0.27
March 0.116283E+10 0.19 612.92 01-MAR-07:05 0.27
April 0.112532E+10 0.19 612.92 01-APR-06:05 0.27
May 0.116283E+10 0.19 612.92 01-MAY-06:05 0.27
June 0.112532E+10 0.19 612.92 01-JUN-06:05 0.27
July 0.116283E+10 0.19 612.92 01-JUL-06:10 0.27
August 0.116283E+10 0.19 612.92 01-AUG-06:05 0.27
September 0.112532E+10 0.19 612.92 01-SEP-06:05 0.27
October 0.116283E+10 0.19 612.92 01-OCT-06:10 0.27
November 0.112532E+10 0.19 612.92 01-NOV-06:05 0.27
December 0.116283E+10 0.19 612.92 01-DEC-07:05 0.27
           
Annual Sum or Average 0.136914E+11 0.19      
Minimum of Months 0.105030E+10 0.19 612.92   0.27
Maximum of Months 0.116283E+10 0.19 612.92   0.27



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.156351E+09 0.47 668.83 01-JAN-19:02 0.58
February 0.137141E+09 0.46 668.83 01-FEB-09:02 0.59
March 0.153507E+09 0.45 668.83 01-MAR-16:01 0.58
April 0.210767E+09 0.47 668.83 01-APR-15:01 0.59
May 0.195568E+09 0.46 668.83 01-MAY-15:01 0.58
June 0.250303E+09 0.47 668.83 01-JUN-15:02 0.58
July 0.344484E+09 0.50 668.83 01-JUL-08:62 0.58
August 0.355678E+09 0.52 668.83 01-AUG-08:62 0.58
September 0.291488E+09 0.50 668.83 01-SEP-15:02 0.58
October 0.284029E+09 0.50 668.83 01-OCT-08:62 0.58
November 0.164041E+09 0.48 668.83 01-NOV-08:62 0.58
December 0.166364E+09 0.48 668.83 02-DEC-16:02 0.58
           
Annual Sum or Average 0.270972E+10 0.48      
Minimum of Months 0.137141E+09 0.45 668.83   0.58
Maximum of Months 0.355678E+09 0.52 668.83   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.114477E+09 0.42 641.51 01-JAN-09:02 0.58
February 97974686.33 0.43 641.51 01-FEB-16:02 0.58
March 0.124420E+09 0.42 641.51 01-MAR-09:02 0.58
April 0.170499E+09 0.45 641.51 01-APR-15:01 0.59
May 0.185400E+09 0.45 641.51 01-MAY-15:01 0.58
June 0.252081E+09 0.47 641.51 01-JUN-15:02 0.58
July 0.339011E+09 0.50 641.51 01-JUL-08:62 0.58
August 0.319213E+09 0.49 641.51 01-AUG-08:62 0.58
September 0.228796E+09 0.46 641.51 01-SEP-15:02 0.58
October 0.197479E+09 0.46 641.51 01-OCT-08:62 0.58
November 93281419.16 0.44 641.51 01-NOV-15:02 0.58
December 0.107042E+09 0.43 641.51 02-DEC-16:02 0.58
           
Annual Sum or Average 0.222967E+10 0.45      
Minimum of Months 93281419.16 0.42 641.51   0.58
Maximum of Months 0.339011E+09 0.50 641.51   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.117027E+10 0.30 2482.88 22-JAN-13:30 0.58
February 0.705163E+09 0.23 2387.29 02-FEB-14:00 0.59
March 0.356946E+09 0.16 1144.05 11-MAR-13:40 0.59
April 0.288290E+09 0.17 803.59 08-APR-13:10 0.58
May 32143914.08 0.02 486.17 03-MAY-13:10 0.58
June 5834262.80 0.01 247.29 29-JUN-17:13 0.58
July 0.191442E+09 0.15 619.17 31-JUL-13:00 0.58
August 0.516198E+09 0.28 774.40 30-AUG-13:00 0.58
September 0.714372E+09 0.29 2512.70 30-SEP-13:20 0.59
October 0.125274E+10 0.36 2574.61 31-OCT-13:10 0.59
November 0.118787E+10 0.33 2297.35 18-NOV-13:30 0.59
December 0.136699E+10 0.34 2346.46 03-DEC-12:50 0.58
           
Annual Sum or Average 0.778827E+10 0.22      
Minimum of Months 5834262.80 0.01 247.29   0.58
Maximum of Months 0.136699E+10 0.36 2574.61   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.675706E+09 0.41 3635.11 01-JAN-09:02 0.58
February 0.558400E+09 0.41 3635.11 01-FEB-19:02 0.58
March 0.709211E+09 0.41 3635.11 03-MAR-16:02 0.58
April 0.940660E+09 0.41 3635.11 01-APR-08:62 0.59
May 0.117153E+10 0.41 3635.11 01-MAY-15:01 0.58
June 0.146626E+10 0.41 3635.11 01-JUN-15:02 0.58
July 0.181427E+10 0.41 3635.11 01-JUL-08:62 0.58
August 0.162773E+10 0.41 3635.11 01-AUG-08:62 0.58
September 0.121144E+10 0.41 3635.11 01-SEP-15:02 0.58
October 0.119381E+10 0.41 3635.11 01-OCT-08:62 0.58
November 0.627043E+09 0.41 3635.11 01-NOV-08:62 0.58
December 0.608083E+09 0.41 3635.11 02-DEC-09:02 0.58
           
Annual Sum or Average 0.126041E+11 0.41      
Minimum of Months 0.558400E+09 0.41 3635.11   0.58
Maximum of Months 0.181427E+10 0.41 3635.11   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.156436E+09 0.47 585.18 01-JAN-09:02 0.58
February 0.132281E+09 0.46 585.18 01-FEB-09:02 0.59
March 0.148644E+09 0.45 585.18 01-MAR-09:02 0.58
April 0.187742E+09 0.49 585.18 01-APR-08:62 0.59
May 0.164380E+09 0.46 585.18 01-MAY-08:62 0.58
June 0.207661E+09 0.49 585.18 01-JUN-08:62 0.58
July 0.310135E+09 0.54 585.18 01-JUL-08:62 0.58
August 0.335951E+09 0.54 585.18 01-AUG-08:62 0.58
September 0.247855E+09 0.52 585.18 01-SEP-08:62 0.58
October 0.267906E+09 0.51 585.18 01-OCT-08:62 0.58
November 0.156382E+09 0.48 585.18 01-NOV-08:62 0.58
December 0.164479E+09 0.48 585.18 01-DEC-09:02 0.58
           
Annual Sum or Average 0.247985E+10 0.49      
Minimum of Months 0.132281E+09 0.45 585.18   0.58
Maximum of Months 0.335951E+09 0.54 585.18   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.109871E+09 0.41 561.19 01-JAN-09:02 0.58
February 93473689.05 0.41 561.19 01-FEB-09:02 0.59
March 0.117764E+09 0.41 561.19 01-MAR-09:02 0.58
April 0.146611E+09 0.43 561.19 01-APR-08:62 0.59
May 0.154663E+09 0.44 561.19 01-MAY-08:62 0.58
June 0.208857E+09 0.49 561.19 01-JUN-08:62 0.58
July 0.304794E+09 0.53 561.19 01-JUL-08:62 0.58
August 0.298127E+09 0.53 561.19 01-AUG-08:62 0.58
September 0.181866E+09 0.45 561.19 01-SEP-08:62 0.58
October 0.177041E+09 0.45 561.19 01-OCT-08:62 0.58
November 89615748.02 0.41 561.19 01-NOV-08:62 0.58
December 0.104072E+09 0.41 561.19 02-DEC-09:02 0.58
           
Annual Sum or Average 0.198675E+10 0.45      
Minimum of Months 89615748.02 0.41 561.19   0.58
Maximum of Months 0.304794E+09 0.53 561.19   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 40645294.25 0.47 173.14 01-JAN-19:02 0.58
February 37689418.98 0.46 173.14 01-FEB-16:02 0.58
March 43491363.95 0.45 173.14 01-MAR-16:01 0.58
April 52393942.28 0.47 173.14 01-APR-15:01 0.59
May 47604584.00 0.46 173.14 01-MAY-15:01 0.58
June 60293086.89 0.48 173.14 01-JUN-15:02 0.58
July 85851392.67 0.52 173.14 01-JUL-08:62 0.58
August 87728732.34 0.52 173.14 01-AUG-08:62 0.58
September 67478362.35 0.50 173.14 01-SEP-15:02 0.58
October 65049652.59 0.50 173.14 01-OCT-08:62 0.58
November 39273028.24 0.48 173.14 01-NOV-15:02 0.58
December 42018407.08 0.48 173.14 02-DEC-16:02 0.58
           
Annual Sum or Average 0.669517E+09 0.48      
Minimum of Months 37689418.98 0.45 173.14   0.58
Maximum of Months 87728732.34 0.52 173.14   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 37350743.16 0.42 165.58 01-JAN-09:02 0.58
February 31124406.92 0.42 165.58 01-FEB-16:02 0.58
March 38026561.78 0.42 165.58 01-MAR-09:02 0.58
April 43149820.39 0.45 165.58 01-APR-08:62 0.59
May 44938060.18 0.45 165.58 01-MAY-15:01 0.58
June 60836746.03 0.48 165.58 01-JUN-15:02 0.58
July 84760831.91 0.51 165.58 01-JUL-08:62 0.58
August 77672328.81 0.50 165.58 01-AUG-08:62 0.58
September 50373094.30 0.47 165.58 01-SEP-15:02 0.58
October 44509667.93 0.46 165.58 01-OCT-08:62 0.58
November 28295285.64 0.43 165.58 01-NOV-15:02 0.58
December 35880286.32 0.42 165.58 02-DEC-16:02 0.58
           
Annual Sum or Average 0.576918E+09 0.45      
Minimum of Months 28295285.64 0.42 165.58   0.58
Maximum of Months 84760831.91 0.51 165.58   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.418076E+09 0.52 800.36 01-JAN-09:02 0.58
February 0.285382E+09 0.49 800.36 01-FEB-09:02 0.59
March 0.256013E+09 0.47 800.36 01-MAR-09:02 0.58
April 0.248366E+09 0.49 800.36 01-APR-15:01 0.59
May 0.165006E+09 0.43 800.36 01-MAY-15:01 0.58
June 0.189304E+09 0.44 800.36 01-JUN-15:02 0.58
July 0.299924E+09 0.49 800.36 01-JUL-08:62 0.58
August 0.383127E+09 0.51 800.36 01-AUG-08:62 0.58
September 0.394687E+09 0.51 800.36 01-SEP-15:02 0.58
October 0.509405E+09 0.51 800.36 01-OCT-08:62 0.58
November 0.406224E+09 0.52 800.36 01-NOV-08:62 0.58
December 0.454560E+09 0.52 800.36 01-DEC-09:02 0.58
           
Annual Sum or Average 0.401007E+10 0.49      
Minimum of Months 0.165006E+09 0.43 800.36   0.58
Maximum of Months 0.509405E+09 0.52 800.36   0.59



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.495717E+09 0.446145E+09 567.45 03-JAN-05:00 510.70 510.70 46.64 1.27
February 0.369936E+09 0.332943E+09 547.29 04-FEB-05:55 492.56 492.56 47.73 1.12
March 0.502910E+09 0.452619E+09 569.47 30-MAR-04:00 512.52 512.52 47.56 1.29
April 0.195331E+09 0.175798E+09 520.78 01-APR-06:00 468.70 468.70 46.09 0.97
May 0.170092E+09 0.153083E+09 478.79 14-MAY-04:50 430.91 430.91 44.81 0.80
June 27747152.52 24972437.27 280.58 13-JUN-04:00 252.52 252.52 36.51 0.35
July 2060098.82 1854088.94 171.88 26-JUL-08:05 154.69 154.69 49.95 0.20
August 1203462.12 1083115.91 192.27 15-AUG-08:05 173.04 173.04 54.80 0.22
September 13573856.30 12216470.67 258.80 20-SEP-04:00 232.92 232.92 35.01 0.32
October 71389867.97 64250881.18 410.82 29-OCT-06:00 369.74 369.74 41.26 0.61
November 0.301765E+09 0.271589E+09 527.50 05-NOV-05:07 474.75 474.75 47.09 1.00
December 0.483138E+09 0.434824E+09 553.03 13-DEC-06:00 497.73 497.73 47.94 1.16
                 
Annual Sum or Average 0.263486E+10 0.237138E+10            
Minimum of Months 1203462.12 1083115.91 171.88   154.69 154.69 35.01 0.20
Maximum of Months 0.502910E+09 0.452619E+09 569.47   512.52 512.52 54.80 1.29



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.295260E+10 0.265734E+10 3792.99 24-JAN-16:02 3413.69 3413.69 7.17 12.21
February 0.219547E+10 0.197592E+10 3530.89 01-FEB-13:10 3177.80 3177.80 7.24 9.77
March 0.207627E+10 0.186864E+10 3701.48 23-MAR-15:02 3331.34 3331.34 7.45 11.21
April 0.367501E+10 0.330751E+10 3601.48 26-APR-17:00 3241.33 3241.33 7.44 10.31
May 0.395900E+10 0.356310E+10 3768.31 18-MAY-15:03 3391.48 3391.48 7.46 11.92
June 0.532553E+10 0.479298E+10 4030.46 29-JUN-18:03 3627.42 3627.42 7.50 15.87
July 0.745899E+10 0.671309E+10 4178.80 31-JUL-18:03 3760.92 3760.92 7.33 18.08
August 0.790971E+10 0.711874E+10 4082.54 14-AUG-18:03 3674.28 3674.28 7.46 16.72
September 0.612029E+10 0.550826E+10 4463.59 29-SEP-15:25 4017.23 4017.23 6.73 20.77
October 0.631495E+10 0.568346E+10 4228.68 16-OCT-18:05 3805.81 3805.81 7.16 18.67
November 0.323092E+10 0.290783E+10 3972.65 19-NOV-11:00 3575.39 3575.39 6.84 14.88
December 0.299568E+10 0.269612E+10 3536.79 05-DEC-09:02 3183.11 3183.11 7.12 9.81
                 
Annual Sum or Average 0.542144E+11 0.487930E+11            
Minimum of Months 0.207627E+10 0.186864E+10 3530.89   3177.80 3177.80 6.73 9.77
Maximum of Months 0.790971E+10 0.711874E+10 4463.59   4017.23 4017.23 7.50 20.77



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.784397E+10 0.705958E+10 3479.56 01-JAN-07:30 3131.60 3131.60 8.41 24.39
February 0.698435E+10 0.628591E+10 3479.56 01-FEB-00:03 3131.60 3131.60 8.44 24.39
March 0.721744E+10 0.649570E+10 3479.56 01-MAR-07:05 3131.60 3131.60 8.41 24.39
April 0.867559E+10 0.780803E+10 3479.56 01-APR-06:40 3131.60 3131.60 8.42 24.39
May 0.915438E+10 0.823894E+10 3479.56 01-MAY-00:05 3131.60 3131.60 8.70 24.39
June 0.900858E+10 0.810773E+10 3479.56 01-JUN-00:05 3131.60 3131.60 8.51 24.39
July 0.931966E+10 0.838769E+10 3479.56 01-JUL-00:10 3131.60 3131.60 9.16 24.39
August 0.931966E+10 0.838769E+10 3479.56 01-AUG-00:05 3131.60 3131.60 9.71 24.39
September 0.901276E+10 0.811148E+10 3479.56 01-SEP-00:05 3131.60 3131.60 8.80 24.39
October 0.929669E+10 0.836702E+10 3479.56 01-OCT-00:10 3131.60 3131.60 9.84 24.39
November 0.837756E+10 0.753981E+10 3479.56 01-NOV-00:05 3131.60 3131.60 8.61 24.39
December 0.799881E+10 0.719893E+10 3479.56 01-DEC-00:03 3131.60 3131.60 8.45 24.39
                 
Annual Sum or Average 0.102209E+12 0.919885E+11            
Minimum of Months 0.698435E+10 0.628591E+10 3479.56   3131.60 3131.60 8.41 24.39
Maximum of Months 0.931966E+10 0.838769E+10 3479.56   3131.60 3131.60 9.84 24.39



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:10 14.37 14.37 50.01 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:03 14.37 14.37 50.13 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:03 14.37 14.37 49.69 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 52.74 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:05 14.37 14.37 52.90 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:05 14.37 14.37 52.42 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 53.44 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:05 14.37 14.37 53.26 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:05 14.37 14.37 53.21 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 51.95 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:05 14.37 14.37 52.92 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:03 14.37 14.37 50.44 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 49.69 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 53.44 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 43.34 79.60 45336.02 181927.27 08-JAN-07:00
February 0.00 0.00 01-FEB-00:03 32.10 79.40 34937.89 151955.47 04-FEB-06:00
March 0.00 0.00 01-MAR-00:03 45.02 79.80 45373.33 185956.25 29-MAR-08:62
April 0.00 0.00 01-APR-00:10 42.09 79.46 17447.24 136896.41 01-APR-06:00
May 0.00 0.00 01-MAY-00:05 36.19 36.19 14701.16 116742.77 14-MAY-04:50
June 0.00 0.00 01-JUN-00:05 26.41 79.40 2441.02 63382.46 13-JUN-04:00
July 0.00 0.00 01-JUL-00:10 29.46 29.46 156.90 33541.50 18-JUL-08:05
August 0.00 0.00 01-AUG-00:05 52.07 52.07 66.63 31740.51 29-AUG-18:05
September 0.00 0.00 01-SEP-00:05 41.20 41.20 1164.91 59258.40 20-SEP-04:00
October 0.00 0.00 01-OCT-00:10 53.74 53.74 6039.08 97168.53 29-OCT-06:00
November 0.00 0.00 01-NOV-00:05 31.52 31.52 26747.03 144072.18 29-NOV-23:00
December 0.00 0.00 01-DEC-00:03 35.38 79.40 43040.82 156372.34 23-DEC-06:00
                 
Annual Sum or Average 0.00         19749.04    
Minimum of Months 0.00 0.00   26.41 29.46 66.63 31740.51  
Maximum of Months 0.00 0.00   53.74 79.80 45373.33 185956.25  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 43697.86 301569.72 14-JAN-11:33 9.76 6.81 0.00 0.00 01-JAN-00:10
February 30913.37 283067.89 01-FEB-09:02 10.13 7.36 0.00 0.00 01-FEB-00:03
March 28127.59 319709.88 23-MAR-15:02 10.56 7.43 0.00 0.00 01-MAR-00:03
April 58331.92 310300.87 26-APR-10:45 9.89 6.86 0.00 0.00 01-APR-00:10
May 58510.11 349838.88 18-MAY-15:02 10.86 7.43 0.00 0.00 01-MAY-00:05
June 104347.26 468120.75 29-JUN-18:03 12.07 7.48 0.00 0.00 01-JUN-00:05
July 190386.04 547707.06 31-JUL-18:03 12.67 7.31 0.00 0.00 01-JUL-00:10
August 212533.24 548150.58 18-AUG-15:03 12.10 6.73 0.00 0.00 01-AUG-00:05
September 138145.82 501377.32 29-SEP-15:02 11.61 6.70 0.00 0.00 01-SEP-00:05
October 149573.66 525519.36 14-OCT-15:02 11.84 6.70 0.00 0.00 01-OCT-00:10
November 48249.55 357548.61 19-NOV-09:02 10.55 7.06 0.00 0.00 01-NOV-00:05
December 49382.42 334891.99 05-DEC-09:02 10.33 7.06 0.00 0.00 01-DEC-00:03
                 
Annual Sum or Average 93250.27         0.00    
Minimum of Months 28127.59 283067.89   9.76 6.70 0.00 0.00  
Maximum of Months 212533.24 548150.58   12.67 7.48 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 50.01 59.50 24241.71 49031.35 31-JAN-07:20
February 0.00 0.00 01-FEB-00:03 50.13 59.59 24271.54 49034.02 01-FEB-07:30
March 0.00 0.00 01-MAR-00:03 49.69 58.14 24039.58 48751.99 01-MAR-07:50
April 0.00 0.00 01-APR-00:10 52.74 58.98 23559.33 47892.22 04-APR-06:20
May 0.00 0.00 01-MAY-00:05 52.90 59.79 22999.63 46886.13 02-MAY-06:45
June 0.00 0.00 01-JUN-00:05 52.42 58.33 22503.26 45690.28 01-JUN-06:20
July 0.00 0.00 01-JUL-00:10 53.44 59.55 22173.39 44779.11 03-JUL-06:15
August 0.00 0.00 01-AUG-00:05 53.26 59.69 22161.83 44690.92 31-AUG-06:20
September 0.00 0.00 01-SEP-00:05 53.21 59.59 22406.70 45422.39 29-SEP-06:20
October 0.00 0.00 01-OCT-00:10 51.95 58.47 22870.18 46574.03 31-OCT-06:30
November 0.00 0.00 01-NOV-00:05 52.92 59.47 23433.60 47721.50 30-NOV-07:20
December 0.00 0.00 01-DEC-00:03 50.44 59.02 23932.85 48581.99 29-DEC-07:40
                 
Annual Sum or Average 0.00         23210.09    
Minimum of Months 0.00 0.00   49.69 58.14 22161.83 44690.92  
Maximum of Months 0.00 0.00   53.44 59.79 24271.54 49034.02  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.998511E+11 0.00 0.572450E+11 0.362558E+11 0.00 0.00
February 0.691391E+11 0.00 0.316038E+11 0.327383E+11 0.00 0.00
March 0.100025E+12 0.00 0.353233E+11 0.360980E+11 0.00 0.00
April 0.373880E+11 0.00 0.843398E+11 0.357103E+11 0.00 0.00
May 0.326769E+11 0.00 0.901865E+11 0.371815E+11 0.00 0.00
June 0.516107E+10 0.00 0.168634E+12 0.368371E+11 0.00 0.00
July 0.298507E+09 0.00 0.346290E+12 0.386167E+11 0.00 0.00
August 89949969.18 0.00 0.390374E+12 0.388967E+11 0.00 0.00
September 0.238306E+10 0.00 0.229545E+12 0.370456E+11 0.00 0.00
October 0.134868E+11 0.00 0.260389E+12 0.389313E+11 0.00 0.00
November 0.571649E+11 0.00 0.593969E+11 0.358542E+11 0.00 0.00
December 0.953626E+11 0.00 0.661316E+11 0.366770E+11 0.00 0.00
             
Annual Sum or Average 0.513027E+12 0.00 0.181946E+13 0.440843E+12 0.00 0.00
Minimum of Months 89949969.18 0.00 0.316038E+11 0.327383E+11 0.00 0.00
Maximum of Months 0.100025E+12 0.00 0.390374E+12 0.389313E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.147285E+11 0.00 0.113067E+11 0.587890E+10 0.00 0.00
February 0.118617E+11 0.00 0.624901E+10 0.530997E+10 0.00 0.00
March 0.159855E+11 0.00 0.724922E+10 0.587890E+10 0.00 0.00
April 0.718571E+10 0.00 0.170527E+11 0.568926E+10 0.00 0.00
May 0.618449E+10 0.00 0.176695E+11 0.587890E+10 0.00 0.00
June 0.108226E+10 0.00 0.354046E+11 0.568926E+10 0.00 0.00
July 62562347.84 0.00 0.697043E+11 0.587890E+10 0.00 0.00
August 29890880.57 0.00 0.780509E+11 0.587890E+10 0.00 0.00
September 0.542137E+09 0.00 0.472441E+11 0.568926E+10 0.00 0.00
October 0.245036E+10 0.00 0.510747E+11 0.587890E+10 0.00 0.00
November 0.100455E+11 0.00 0.116003E+11 0.568926E+10 0.00 0.00
December 0.146291E+11 0.00 0.131328E+11 0.587890E+10 0.00 0.00
             
Annual Sum or Average 0.847876E+11 0.00 0.365739E+12 0.692193E+11 0.00 0.00
Minimum of Months 29890880.57 0.00 0.624901E+10 0.530997E+10 0.00 0.00
Maximum of Months 0.159855E+11 0.00 0.780509E+11 0.587890E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.362558E+11 0.572450E+11 0.998511E+11 0.00 0.00 0.00 0.00 0.00
February 0.327383E+11 0.316038E+11 0.691391E+11 0.00 0.00 0.00 0.00 0.00
March 0.360980E+11 0.353233E+11 0.100025E+12 0.00 0.00 0.00 0.00 0.00
April 0.357103E+11 0.843398E+11 0.373880E+11 0.00 0.00 0.00 0.00 0.00
May 0.371815E+11 0.901865E+11 0.326769E+11 0.00 0.00 0.00 0.00 0.00
June 0.368371E+11 0.168634E+12 0.516107E+10 0.00 0.00 0.00 0.00 0.00
July 0.386167E+11 0.346290E+12 0.298507E+09 0.00 0.00 0.00 0.00 0.00
August 0.388967E+11 0.390374E+12 89949969.18 0.00 0.00 0.00 0.00 0.00
September 0.370456E+11 0.229545E+12 0.238306E+10 0.00 0.00 0.00 0.00 0.00
October 0.389313E+11 0.260389E+12 0.134868E+11 0.00 0.00 0.00 0.00 0.00
November 0.358542E+11 0.593969E+11 0.571649E+11 0.00 0.00 0.00 0.00 0.00
December 0.366770E+11 0.661316E+11 0.953626E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.440843E+12 0.181946E+13 0.513027E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.327383E+11 0.316038E+11 89949969.18 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.389313E+11 0.390374E+12 0.100025E+12 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.587890E+10 0.113067E+11 0.147285E+11 0.00 0.00 0.00 0.00 0.00
February 0.530997E+10 0.624901E+10 0.118617E+11 0.00 0.00 0.00 0.00 0.00
March 0.587890E+10 0.724922E+10 0.159855E+11 0.00 0.00 0.00 0.00 0.00
April 0.568926E+10 0.170527E+11 0.718571E+10 0.00 0.00 0.00 0.00 0.00
May 0.587890E+10 0.176695E+11 0.618449E+10 0.00 0.00 0.00 0.00 0.00
June 0.568926E+10 0.354046E+11 0.108226E+10 0.00 0.00 0.00 0.00 0.00
July 0.587890E+10 0.697043E+11 62562347.84 0.00 0.00 0.00 0.00 0.00
August 0.587890E+10 0.780509E+11 29890880.57 0.00 0.00 0.00 0.00 0.00
September 0.568926E+10 0.472441E+11 0.542137E+09 0.00 0.00 0.00 0.00 0.00
October 0.587890E+10 0.510747E+11 0.245036E+10 0.00 0.00 0.00 0.00 0.00
November 0.568926E+10 0.116003E+11 0.100455E+11 0.00 0.00 0.00 0.00 0.00
December 0.587890E+10 0.131328E+11 0.146291E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.692193E+11 0.365739E+12 0.847876E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.530997E+10 0.624901E+10 29890880.57 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.780509E+11 0.159855E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.362558E+11 0.998511E+11 0.572450E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.327383E+11 0.691391E+11 0.316038E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.360980E+11 0.100025E+12 0.353233E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.357103E+11 0.373880E+11 0.843398E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.371815E+11 0.326769E+11 0.901865E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.368371E+11 0.516107E+10 0.168634E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.386167E+11 0.298507E+09 0.346290E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.388967E+11 89949969.18 0.390374E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.370456E+11 0.238306E+10 0.229545E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.389313E+11 0.134868E+11 0.260389E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.358542E+11 0.571649E+11 0.593969E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.366770E+11 0.953626E+11 0.661316E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.440843E+12 0.513027E+12 0.181946E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.327383E+11 89949969.18 0.316038E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.389313E+11 0.100025E+12 0.390374E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.587890E+10 0.147285E+11 0.113067E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.530997E+10 0.118617E+11 0.624901E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.587890E+10 0.159855E+11 0.724922E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.568926E+10 0.718571E+10 0.170527E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.587890E+10 0.618449E+10 0.176695E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.568926E+10 0.108226E+10 0.354046E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.587890E+10 62562347.84 0.697043E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.587890E+10 29890880.57 0.780509E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.568926E+10 0.542137E+09 0.472441E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.587890E+10 0.245036E+10 0.510747E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.568926E+10 0.100455E+11 0.116003E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.587890E+10 0.146291E+11 0.131328E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.692193E+11 0.847876E+11 0.365739E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.530997E+10 29890880.57 0.624901E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.159855E+11 0.780509E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.252795E+11 0.00 0.00 14605869.98 62937718.79 0.00 0.302347E+11 0.00 1.02
February 0.435853E+11 0.00 0.00 1361383.41 13544443.32 0.00 0.505670E+10 0.00 1.01
March 0.556806E+11 0.00 0.00 9501.82 290032.42 0.00 0.215327E+09 0.00 1.01
April 0.436268E+11 0.00 0.00 0.00 73733317.84 0.00 0.00 0.00 1.01
May 0.439281E+11 0.00 0.00 0.00 9904590.58 0.00 0.00 0.00 1.01
June 0.327849E+11 0.00 0.00 0.00 0.565800E+09 0.00 0.00 0.00 1.02
July 0.197863E+11 2021865.09 0.00 555365.11 0.460641E+10 0.00 0.143257E+10 0.00 1.03
August 0.157542E+11 0.00 0.00 1373309.25 0.556426E+10 0.00 0.225884E+10 0.00 1.03
September 0.196293E+11 84174451.02 0.00 7165871.74 0.164352E+10 0.00 0.906109E+10 0.00 1.03
October 0.659989E+10 0.200549E+09 0.00 18437867.50 0.284469E+10 0.00 0.240687E+11 0.00 1.04
November 0.127990E+11 7011331.64 0.00 24385243.97 39472057.09 0.00 0.374508E+11 0.00 1.04
December 0.189867E+11 0.00 0.00 16678430.60 22866902.55 0.00 0.353476E+11 0.00 1.03
                   
Annual Sum or Average 0.338441E+12 0.293756E+09 0.00 84572843.38 0.154474E+11 0.00 0.145126E+12 0.00 1.02
Minimum of Months 0.659989E+10 0.00 0.00 0.00 290032.42 0.00 0.00 0.00 1.01
Maximum of Months 0.556806E+11 0.200549E+09 0.00 24385243.97 0.556426E+10 0.00 0.374508E+11 0.00 1.04



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.649396E+10 12004624.86 0.00 2025425.69 273225.17 0.00 0.863151E+09 0.00 2.51
February 0.592487E+10 2336847.59 0.00 1289673.53 0.00 0.00 0.542000E+09 0.00 2.46
March 0.712254E+10 10880.96 0.00 551836.49 27467.04 27905912.43 0.241903E+09 0.00 2.42
April 0.562498E+10 4921349.68 0.00 174715.92 4827648.89 0.00 0.143167E+09 0.00 2.42
May 0.580452E+10 676221.03 0.00 6046.58 633361.15 0.00 3630564.07 0.00 2.43
June 0.433481E+10 0.00 0.00 0.00 74809972.52 0.00 0.00 0.00 2.45
July 0.280084E+10 0.115362E+09 0.00 3452.48 0.493963E+09 0.00 4782898.97 0.00 2.47
August 0.228834E+10 0.383154E+09 0.00 89925.06 0.352551E+09 0.00 93428376.77 0.00 2.47
September 0.333910E+10 0.186628E+09 0.00 860364.70 84195456.17 0.00 0.453850E+09 0.00 2.50
October 0.329887E+10 0.445662E+09 0.00 1739149.68 94595891.96 0.00 0.711152E+09 0.00 2.62
November 0.579553E+10 9777072.00 0.00 2091875.17 0.00 0.00 0.763647E+09 0.00 2.52
December 0.630322E+10 4687139.06 0.00 2863435.20 0.00 0.00 0.892774E+09 0.00 2.56
                   
Annual Sum or Average 0.591316E+11 0.116522E+10 0.00 11695900.51 0.110588E+10 27905912.43 0.471348E+10 0.00 2.49
Minimum of Months 0.228834E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.42
Maximum of Months 0.712254E+10 0.445662E+09 0.00 2863435.20 0.493963E+09 27905912.43 0.892774E+09 0.00 2.62



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.445563E+10 0.00 0.00 332758.13 6117403.82 0.00 0.884378E+09 0.00 1.54
February 0.396830E+10 0.00 0.00 320834.90 1316489.24 0.00 0.760288E+09 0.00 1.54
March 0.481461E+10 0.00 0.00 243538.00 28190.49 0.00 0.619387E+09 0.00 1.54
April 0.317153E+10 0.00 0.00 600347.92 7166711.61 0.00 0.107481E+10 0.00 1.55
May 0.331134E+10 0.00 0.00 501391.88 962703.79 0.00 0.961726E+09 0.00 1.55
June 0.192969E+10 828940.57 0.00 908845.89 54165579.63 0.00 0.126903E+10 0.00 1.57
July 0.672774E+09 20231136.47 0.00 1541533.28 0.427815E+09 0.00 0.141065E+10 0.00 1.59
August 0.366987E+09 12173589.04 0.00 1913449.26 0.528678E+09 0.00 0.141851E+10 0.00 1.60
September 0.123577E+10 44639808.16 0.00 1453432.59 0.123360E+09 0.00 0.158333E+10 0.00 1.59
October 0.144678E+10 0.118131E+09 0.00 1603192.58 0.177759E+09 0.00 0.152690E+10 0.00 1.59
November 0.360030E+10 0.00 0.00 589784.10 4518080.18 0.00 0.116232E+10 0.00 1.54
December 0.419206E+10 0.00 0.00 463582.22 2222611.17 0.00 0.102308E+10 0.00 1.54
                   
Annual Sum or Average 0.331658E+11 0.196005E+09 0.00 10472690.76 0.133411E+10 0.00 0.136944E+11 0.00 1.56
Minimum of Months 0.366987E+09 0.00 0.00 243538.00 28190.49 0.00 0.619387E+09 0.00 1.54
Maximum of Months 0.481461E+10 0.118131E+09 0.00 1913449.26 0.528678E+09 0.00 0.158333E+10 0.00 1.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.506338E+10 0.00 0.00 0.00 5800212.61 0.00 0.00 0.00 0.69
February 0.448240E+10 0.00 0.00 0.00 1248228.45 0.00 0.00 0.00 0.69
March 0.515126E+10 0.00 0.00 0.00 26728.80 0.00 0.00 0.00 0.69
April 0.402056E+10 0.00 0.00 0.00 6795113.14 0.00 0.00 0.00 0.69
May 0.404832E+10 0.00 0.00 0.00 912786.99 0.00 0.00 0.00 0.69
June 0.300215E+10 0.00 0.00 3371.07 52143019.95 0.00 19235126.93 0.00 0.70
July 0.189766E+10 1197884.56 0.00 59150.55 0.423506E+09 0.00 57815428.45 0.00 0.70
August 0.158836E+10 0.00 0.00 48967.09 0.512791E+09 0.00 71767543.34 0.00 0.70
September 0.263284E+10 136341.26 0.00 33530.51 0.158954E+09 0.00 9337482.32 0.00 0.70
October 0.269340E+10 6275720.41 0.00 96910.99 0.273856E+09 0.00 83678373.05 0.00 0.70
November 0.451432E+10 0.00 0.00 0.00 4283814.90 0.00 0.00 0.00 0.69
December 0.494209E+10 0.00 0.00 0.00 2107367.39 0.00 0.00 0.00 0.69
                   
Annual Sum or Average 0.440367E+11 7609946.23 0.00 241930.21 0.144242E+10 0.00 0.241834E+09 0.00 0.70
Minimum of Months 0.158836E+10 0.00 0.00 0.00 26728.80 0.00 0.00 0.00 0.69
Maximum of Months 0.515126E+10 6275720.41 0.00 96910.99 0.512791E+09 0.00 83678373.05 0.00 0.70



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.240835E+10 0.00 0.00 0.00 2758814.13 0.00 0.00 0.00 0.57
February 0.213201E+10 0.00 0.00 0.00 593707.60 0.00 0.00 0.00 0.57
March 0.245015E+10 0.00 0.00 0.00 12713.29 0.00 0.00 0.00 0.57
April 0.191234E+10 0.00 0.00 0.00 3232028.79 0.00 0.00 0.00 0.57
May 0.192554E+10 0.00 0.00 0.00 434158.16 0.00 0.00 0.00 0.57
June 0.143710E+10 0.00 0.00 0.00 24801315.09 0.00 0.00 0.00 0.58
July 0.930132E+09 0.00 0.00 0.00 0.202006E+09 0.00 0.00 0.00 0.58
August 0.789645E+09 0.00 0.00 0.00 0.243904E+09 0.00 0.00 0.00 0.58
September 0.125674E+10 0.00 0.00 0.00 75669847.04 0.00 0.00 0.00 0.58
October 0.132057E+10 0.00 0.00 0.00 0.133242E+09 0.00 0.00 0.00 0.58
November 0.214719E+10 0.00 0.00 0.00 2037554.46 0.00 0.00 0.00 0.57
December 0.235066E+10 0.00 0.00 0.00 1002348.59 0.00 0.00 0.00 0.57
                   
Annual Sum or Average 0.210604E+11 0.00 0.00 0.00 0.689695E+09 0.00 0.00 0.00 0.57
Minimum of Months 0.789645E+09 0.00 0.00 0.00 12713.29 0.00 0.00 0.00 0.57
Maximum of Months 0.245015E+10 0.00 0.00 0.00 0.243904E+09 0.00 0.00 0.00 0.58



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.311327E+09 84664949.65 0.00 91710746.82 0.00 0.00 0.842604E+11 0.00 23.96
February 0.233773E+09 18220228.41 0.00 82459208.03 0.00 0.00 0.745606E+11 0.00 23.97
March 0.251804E+09 390156.82 0.00 90173039.33 0.00 0.00 0.857987E+11 0.00 23.95
April 0.200734E+09 99187383.37 0.00 91255809.29 0.00 0.00 0.671629E+11 0.00 23.96
May 0.205041E+09 13323833.13 0.00 95445874.97 0.00 0.00 0.676970E+11 0.00 24.06
June 63504400.44 0.768452E+09 0.00 90407850.18 293715.61 0.00 0.508913E+11 0.00 24.34
July 20908348.92 0.637155E+10 0.00 76242636.72 11983549.68 0.00 0.323115E+11 0.00 24.35
August 1278036.10 0.758840E+10 0.00 71234797.92 20586001.27 0.00 0.278308E+11 0.00 24.49
September 55700000.97 0.237497E+10 0.00 83457719.18 0.00 0.00 0.441218E+11 0.00 24.41
October 0.115742E+09 0.420952E+10 0.00 79652875.11 15250711.79 0.00 0.464774E+11 0.00 24.30
November 0.240724E+09 62530289.34 0.00 89585019.31 0.00 0.00 0.753081E+11 0.00 24.02
December 0.277834E+09 31056934.95 0.00 92461165.39 0.00 0.00 0.824910E+11 0.00 23.98
                   
Annual Sum or Average 0.197837E+10 0.216223E+11 0.00 0.103409E+10 48113978.36 0.00 0.738912E+12 0.00 24.15
Minimum of Months 1278036.10 390156.82 0.00 71234797.92 0.00 0.00 0.278308E+11 0.00 23.95
Maximum of Months 0.311327E+09 0.758840E+10 0.00 95445874.97 20586001.27 0.00 0.857987E+11 0.00 24.49



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.649645E+10 47901849.94 0.00 23561113.17 879752.94 0.00 0.251357E+11 0.00 3.84
February 0.769594E+10 9240496.70 0.00 17264881.55 0.00 0.00 0.200993E+11 0.00 3.77
March 0.121364E+11 164404.10 0.00 12439078.31 0.00 0.00 0.195666E+11 0.00 3.71
April 0.651984E+10 31891217.90 0.00 12894488.30 9904316.53 0.00 0.182198E+11 0.00 3.71
May 0.874534E+10 2899068.99 0.00 9095293.92 2715321.75 0.00 0.161635E+11 0.00 3.72
June 0.467529E+10 39487065.63 0.00 11781366.44 0.281235E+09 0.00 0.139110E+11 0.00 3.76
July 0.169776E+10 0.174737E+10 0.00 14789743.92 0.864911E+09 0.00 0.103555E+11 0.00 3.79
August 0.817796E+09 0.246046E+10 0.00 17965161.88 0.693627E+09 0.00 0.951056E+10 0.00 3.82
September 0.191435E+10 0.856664E+09 0.00 21246578.16 0.220065E+09 0.00 0.145351E+11 0.00 3.85
October 0.191200E+10 0.190629E+10 0.00 25361851.15 0.154476E+09 0.00 0.157187E+11 0.00 4.00
November 0.356617E+10 38110984.42 0.00 25423415.44 0.00 0.00 0.246779E+11 0.00 3.86
December 0.484691E+10 17849854.73 0.00 28049321.08 0.00 0.00 0.261756E+11 0.00 3.92
                   
Annual Sum or Average 0.610242E+11 0.715832E+10 0.00 0.219872E+09 0.222781E+10 0.00 0.214069E+12 0.00 3.81
Minimum of Months 0.817796E+09 164404.10 0.00 9095293.92 0.00 0.00 0.951056E+10 0.00 3.71
Maximum of Months 0.121364E+11 0.246046E+10 0.00 28049321.08 0.864911E+09 0.00 0.261756E+11 0.00 4.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.372521E+11 89847027.15 0.00 42641057.80 25968239.34 0.00 0.649341E+11 0.00 1.76
February 0.341548E+11 15120162.10 0.00 36123395.18 9803736.36 0.00 0.563173E+11 0.00 1.75
March 0.481980E+11 0.00 0.00 30696740.68 533705.10 0.00 0.551570E+11 0.00 1.74
April 0.281238E+11 0.00 0.00 42065480.66 0.135681E+09 0.00 0.531065E+11 0.00 1.76
May 0.277610E+11 0.00 0.00 42792517.46 18225998.96 0.00 0.538795E+11 0.00 1.76
June 0.142067E+11 17581138.98 0.00 55625273.33 0.102358E+10 0.00 0.475255E+11 0.00 1.80
July 0.481357E+10 0.130461E+10 0.00 66741328.17 0.717924E+10 0.00 0.358954E+11 0.00 1.83
August 0.254879E+10 0.211555E+10 0.00 71200709.09 0.812462E+10 0.00 0.328558E+11 0.00 1.85
September 0.823700E+10 0.166331E+10 0.00 66767783.46 0.154700E+10 0.00 0.469418E+11 0.00 1.84
October 0.733725E+10 0.419561E+10 0.00 73755500.10 0.143894E+10 0.00 0.516229E+11 0.00 1.86
November 0.203884E+11 85836675.74 0.00 54804193.79 683117.46 0.00 0.716094E+11 0.00 1.77
December 0.256870E+11 33428616.93 0.00 52814873.46 8650067.57 0.00 0.746994E+11 0.00 1.77
                   
Annual Sum or Average 0.258708E+12 0.952089E+10 0.00 0.636029E+09 0.195129E+11 0.00 0.644545E+12 0.00 1.79
Minimum of Months 0.254879E+10 0.00 0.00 30696740.68 533705.10 0.00 0.328558E+11 0.00 1.74
Maximum of Months 0.481980E+11 0.419561E+10 0.00 73755500.10 0.812462E+10 0.00 0.746994E+11 0.00 1.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.246619E+09 11627008.99 0.00 5788794.55 5885317.94 0.633931E+09 0.117242E+10 0.00 0.47
February 0.287303E+09 3662442.99 0.00 5286647.38 801606.20 0.432231E+09 0.110113E+10 0.00 0.47
March 0.364014E+09 7265418.93 0.00 5124783.11 2288715.22 0.650292E+09 0.108763E+10 0.00 0.47
April 0.186008E+09 17560880.94 0.00 9100473.02 6138085.31 77770692.49 0.123162E+10 0.00 0.47
May 0.181806E+09 3354438.57 0.00 9356653.08 4373528.07 70282696.78 0.118900E+10 0.00 0.47
June 85834702.83 81524684.34 0.00 9040103.43 28697615.05 945561.22 0.737117E+09 0.00 0.48
July 20118790.23 0.368732E+09 209586.71 6486828.64 61659869.54 266188.34 0.318401E+09 11555.18 0.48
August 17841322.63 0.482175E+09 354410.14 5733474.45 65240395.45 132986.28 0.243960E+09 16733.73 0.48
September 69042000.22 0.189384E+09 81239.70 8125525.56 29085111.60 1237265.11 0.621707E+09 2618.92 0.48
October 87556665.12 0.308345E+09 296171.50 6808469.73 29327078.02 7204306.77 0.822380E+09 14672.56 0.48
November 0.211530E+09 11860928.75 2108.23 7333418.64 2167096.02 0.234851E+09 0.133165E+10 2122.07 0.47
December 0.246559E+09 11846448.36 5245.66 6478415.17 2316323.72 0.529948E+09 0.121598E+10 1323.66 0.47
                   
Annual Sum or Average 0.200423E+10 0.149734E+10 948761.93 84663586.75 0.237981E+09 0.263909E+10 0.110730E+11 49026.11 0.47
Minimum of Months 17841322.63 3354438.57 0.00 5124783.11 801606.20 132986.28 0.243960E+09 0.00 0.47
Maximum of Months 0.364014E+09 0.482175E+09 354410.14 9356653.08 65240395.45 0.650292E+09 0.133165E+10 16733.73 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.327669E+09 6241164.38 4805.43 2180630.94 11260339.04 0.104755E+10 0.681111E+09 3966.24 0.47
February 0.330353E+09 1151521.65 0.00 2579222.68 3312004.52 0.726149E+09 0.766656E+09 0.00 0.47
March 0.394589E+09 3742374.45 0.00 3154145.90 5810640.29 0.817774E+09 0.891298E+09 0.00 0.47
April 0.208233E+09 10565681.54 0.00 7460564.18 13130508.03 0.113880E+09 0.117475E+10 0.00 0.47
May 0.188365E+09 2947130.59 0.00 9053842.99 4779930.60 73677338.63 0.117918E+10 0.00 0.47
June 86745694.66 74569969.69 0.00 9224532.87 35639415.54 884480.93 0.735985E+09 0.00 0.48
July 20054733.45 0.356014E+09 228083.57 6544628.66 74308179.86 193407.00 0.318440E+09 12460.43 0.48
August 18817656.68 0.436720E+09 354194.86 5303140.88 0.110631E+09 238808.53 0.243276E+09 16905.52 0.48
September 78155749.88 0.156882E+09 92427.89 6670210.33 61548552.20 1309134.89 0.613895E+09 4172.86 0.48
October 95173035.02 0.268673E+09 357022.52 4751334.05 68899716.92 53588935.71 0.770328E+09 13704.41 0.48
November 0.268412E+09 7328982.74 734.68 3458809.07 6699444.72 0.521503E+09 0.991782E+09 1448.85 0.47
December 0.309019E+09 5541624.25 3078.17 2398737.42 8621089.97 0.977180E+09 0.710138E+09 1888.86 0.47
                   
Annual Sum or Average 0.232559E+10 0.133038E+10 1040347.12 62779799.97 0.404641E+09 0.433393E+10 0.907683E+10 54547.19 0.47
Minimum of Months 18817656.68 1151521.65 0.00 2180630.94 3312004.52 193407.00 0.243276E+09 0.00 0.47
Maximum of Months 0.394589E+09 0.436720E+09 357022.52 9224532.87 0.110631E+09 0.104755E+10 0.117918E+10 16905.52 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.146664E+11 0.237451E+09 0.00 69479795.26 0.00 0.00 0.131790E+11 0.00 0.54
February 0.148124E+11 59929836.88 0.00 48092579.74 598666.43 0.00 0.989777E+10 0.00 0.54
March 0.209140E+11 0.129545E+09 0.00 25339621.84 0.00 0.00 0.763058E+10 0.00 0.54
April 0.145206E+11 0.293389E+09 0.00 20880527.12 27947235.00 0.00 0.585812E+10 0.00 0.54
May 0.188300E+11 36747582.76 0.00 3390767.09 68036713.76 0.00 0.833324E+09 0.00 0.54
June 0.112006E+11 0.657554E+09 0.00 98478.14 0.836962E+09 0.00 93224674.06 0.00 0.54
July 0.440425E+10 0.527890E+10 0.00 1495970.35 0.559833E+09 0.00 0.275841E+09 0.00 0.54
August 0.225760E+10 0.712630E+10 0.00 7313951.71 0.301186E+09 0.00 0.136442E+10 0.00 0.54
September 0.486449E+10 0.291309E+10 0.00 25328065.57 50284975.13 0.00 0.460307E+10 0.00 0.54
October 0.533378E+10 0.449702E+10 0.00 39295846.51 85723449.60 0.00 0.715485E+10 0.00 0.54
November 0.104497E+11 0.190265E+09 0.00 71567146.60 0.00 0.00 0.136867E+11 0.00 0.54
December 0.125517E+11 0.192124E+09 0.00 77868231.08 0.00 0.00 0.144747E+11 0.00 0.54
                   
Annual Sum or Average 0.134805E+12 0.216123E+11 0.00 0.390151E+09 0.193057E+10 0.00 0.790516E+11 0.00 0.54
Minimum of Months 0.225760E+10 36747582.76 0.00 98478.14 0.00 0.00 93224674.06 0.00 0.54
Maximum of Months 0.209140E+11 0.712630E+10 0.00 77868231.08 0.836962E+09 0.00 0.144747E+11 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.464244E+10 24259306.00 36384.09 31309702.83 0.213211E+09 0.208823E+10 0.211605E+11 9336.66 0.53
February 0.481434E+10 9420834.02 108517.40 33644438.01 51008993.13 0.151814E+09 0.197652E+11 6710.16 0.54
March 0.557720E+10 22151297.10 17754.34 39305735.71 0.107408E+09 0.771760E+09 0.221894E+11 4232.06 0.54
April 0.341376E+10 65735508.99 308464.62 56589241.75 0.255379E+09 45954343.27 0.168889E+11 2114.55 0.54
May 0.318555E+10 8612603.10 89697.29 69836938.37 96104670.58 40813022.36 0.163759E+11 5978.63 0.54
June 0.154460E+10 0.488568E+09 153223.27 72385856.66 0.100620E+10 10677216.85 0.966931E+10 7122.48 0.54
July 0.361467E+09 0.247198E+10 2586616.70 52003785.99 0.336572E+10 1455691.42 0.426794E+10 38494.30 0.54
August 0.298162E+09 0.311961E+10 9686643.25 42455537.01 0.430011E+10 2583332.77 0.328712E+10 114922.31 0.54
September 0.117849E+10 0.116332E+10 4938062.72 50948288.62 0.179586E+10 15167871.49 0.825088E+10 76205.76 0.54
October 0.140118E+10 0.216152E+10 6643074.69 42698182.72 0.241575E+10 11219265.99 0.110763E+11 89139.83 0.54
November 0.413673E+10 26254164.48 103526.73 37769554.31 0.163940E+09 0.161805E+09 0.198783E+11 18792.43 0.54
December 0.438105E+10 50649089.59 0.00 31064483.47 0.141527E+09 0.417649E+09 0.222819E+11 0.00 0.53
                   
Annual Sum or Average 0.349350E+11 0.961208E+10 24671965.11 0.560012E+09 0.139122E+11 0.371913E+10 0.175092E+12 373049.16 0.54
Minimum of Months 0.298162E+09 8612603.10 0.00 31064483.47 51008993.13 1455691.42 0.328712E+10 0.00 0.53
Maximum of Months 0.557720E+10 0.311961E+10 9686643.25 72385856.66 0.430011E+10 0.208823E+10 0.222819E+11 114922.31 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.240715E+09 12587622.68 0.00 6621273.43 4924704.25 0.628411E+09 0.118301E+10 0.00 0.47
February 0.270529E+09 4017047.45 0.00 5381856.27 447001.74 0.489897E+09 0.106014E+10 0.00 0.47
March 0.365508E+09 9209511.58 0.00 5414017.53 344622.57 0.650604E+09 0.108554E+10 0.00 0.47
April 0.162580E+09 22744086.33 0.00 8833199.93 954879.91 0.117671E+09 0.121541E+10 0.00 0.47
May 0.187432E+09 7164335.39 0.00 8318687.37 563631.24 0.106959E+09 0.114774E+10 0.00 0.47
June 88080559.32 0.103152E+09 0.00 8031978.27 7070175.31 5622678.49 0.731203E+09 0.00 0.48
July 18056586.64 0.404832E+09 0.00 6151818.49 25781620.39 284705.56 0.320780E+09 0.00 0.48
August 15303783.64 0.520011E+09 0.00 5601878.54 27774809.23 159116.18 0.246603E+09 0.00 0.48
September 67773151.07 0.199894E+09 0.00 7322070.71 18658691.45 831027.33 0.624186E+09 0.00 0.48
October 74458330.88 0.314059E+09 162590.34 7225723.14 23756510.32 17441734.93 0.824823E+09 4536.93 0.48
November 0.203750E+09 12422403.41 0.00 7418289.78 1609851.67 0.290110E+09 0.128409E+10 0.00 0.47
December 0.247397E+09 12826309.28 0.00 6862987.19 1343032.12 0.555950E+09 0.118876E+10 0.00 0.47
                   
Annual Sum or Average 0.194158E+10 0.162292E+10 162590.34 83183780.64 0.113230E+09 0.286394E+10 0.109123E+11 4536.93 0.47
Minimum of Months 15303783.64 4017047.45 0.00 5381856.27 344622.57 159116.18 0.246603E+09 0.00 0.47
Maximum of Months 0.365508E+09 0.520011E+09 162590.34 8833199.93 27774809.23 0.650604E+09 0.128409E+10 4536.93 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.341188E+09 1774595.42 15022.33 2416200.68 15718450.43 0.102255E+10 0.692355E+09 2206.93 0.47
February 0.352903E+09 694263.63 8597.93 2370197.33 3760504.91 0.813437E+09 0.657026E+09 159.70 0.47
March 0.407792E+09 4405424.06 1272.44 3205588.08 5145027.38 0.876175E+09 0.819643E+09 1290.86 0.47
April 0.227348E+09 20896385.49 0.00 6914634.48 2799804.08 0.174878E+09 0.109518E+10 0.00 0.47
May 0.202677E+09 6719309.05 0.00 7932351.30 1007752.14 0.116403E+09 0.112326E+10 0.00 0.47
June 91702359.18 0.102411E+09 0.00 8238209.73 7798800.28 4842025.24 0.728058E+09 0.00 0.48
July 17817682.97 0.400699E+09 0.00 6247368.70 29863529.76 107305.07 0.321060E+09 0.00 0.48
August 15868609.22 0.512309E+09 0.00 5182952.21 35413261.68 176658.58 0.246408E+09 0.00 0.48
September 80220461.76 0.170715E+09 30277.29 5725819.23 47776141.67 1570425.20 0.612513E+09 5270.00 0.48
October 97624715.09 0.281541E+09 298024.04 4920565.68 56091363.63 73099672.38 0.748196E+09 12778.05 0.48
November 0.304934E+09 3373742.09 2305.53 3108920.52 10652025.65 0.583597E+09 0.893515E+09 2537.73 0.47
December 0.322915E+09 3733693.77 0.00 2354004.30 10433709.30 0.966894E+09 0.706573E+09 278.18 0.47
                   
Annual Sum or Average 0.246299E+10 0.150927E+10 355499.55 58616812.23 0.226460E+09 0.463373E+10 0.864379E+10 24521.45 0.47
Minimum of Months 15868609.22 694263.63 0.00 2354004.30 1007752.14 107305.07 0.246408E+09 0.00 0.47
Maximum of Months 0.407792E+09 0.512309E+09 298024.04 8238209.73 56091363.63 0.102255E+10 0.112326E+10 12778.05 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.301544E+11 0.00 0.00 0.00 34542550.15 0.00 0.00 0.00 0.56
February 0.266945E+11 0.00 0.00 0.00 7433691.94 0.00 0.00 0.00 0.56
March 0.306778E+11 0.00 0.00 0.00 159180.53 0.00 0.00 0.00 0.56
April 0.239440E+11 0.00 0.00 0.00 40467574.58 0.00 0.00 0.00 0.56
May 0.241093E+11 0.00 0.00 0.00 5436006.00 0.00 0.00 0.00 0.57
June 0.179936E+11 0.00 0.00 0.00 0.310532E+09 0.00 0.00 0.00 0.57
July 0.116460E+11 0.00 0.00 0.00 0.252928E+10 0.00 0.00 0.00 0.58
August 0.988698E+10 0.00 0.00 0.00 0.305387E+10 0.00 0.00 0.00 0.58
September 0.157316E+11 0.00 0.00 54.44 0.947447E+09 0.00 3793777.69 0.00 0.58
October 0.161469E+11 54940890.80 0.00 265520.77 0.161336E+10 0.00 0.387364E+09 0.00 0.57
November 0.268846E+11 0.00 0.00 0.00 25511804.64 0.00 0.00 0.00 0.56
December 0.294321E+11 0.00 0.00 0.00 12550202.69 0.00 0.00 0.00 0.56
                   
Annual Sum or Average 0.263302E+12 54940890.80 0.00 265575.21 0.858059E+10 0.00 0.391158E+09 0.00 0.57
Minimum of Months 0.988698E+10 0.00 0.00 0.00 159180.53 0.00 0.00 0.00 0.56
Maximum of Months 0.306778E+11 54940890.80 0.00 265520.77 0.305387E+10 0.00 0.387364E+09 0.00 0.58



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 63322343.42 2859941.20 0.00 1124325.05 1518140.53 0.252985E+09 0.197257E+09 0.00 0.47
February 72836153.50 886848.01 0.00 1044663.48 229164.29 0.216228E+09 0.166379E+09 0.00 0.47
March 90610903.09 1893902.47 0.00 1088087.29 494631.06 0.254890E+09 0.180177E+09 0.00 0.47
April 45718270.85 4634025.36 185.78 2065523.47 1290279.93 66888161.83 0.261452E+09 250.49 0.47
May 44577830.37 971953.77 0.00 2110411.49 960037.89 63196496.44 0.252727E+09 0.00 0.47
June 20826011.40 21989283.82 0.00 2043959.43 5566291.03 7946951.24 0.177418E+09 0.00 0.48
July 4989309.83 94565819.48 40475.39 1458576.99 13045270.74 67118.13 79803220.37 1751.46 0.48
August 4448467.78 0.121693E+09 79552.53 1239883.56 15172094.81 67091.95 61161381.85 2270.81 0.48
September 17301671.31 47864848.15 20097.20 1742988.94 6752340.10 1011191.75 0.154972E+09 867.45 0.48
October 22304045.80 76528346.88 88898.94 1345975.40 7874784.33 37448253.32 0.169889E+09 3687.79 0.48
November 55223355.04 2942873.99 617.06 1416368.35 564132.21 0.159173E+09 0.230529E+09 440.51 0.47
December 63819268.85 2873031.18 0.00 1238620.95 669304.17 0.238055E+09 0.196629E+09 0.00 0.47
                   
Annual Sum or Average 0.505978E+09 0.379703E+09 229826.91 17919384.39 54136471.09 0.129796E+10 0.212839E+10 9268.51 0.47
Minimum of Months 4448467.78 886848.01 0.00 1044663.48 229164.29 67091.95 61161381.85 0.00 0.47
Maximum of Months 90610903.09 0.121693E+09 88898.94 2110411.49 15172094.81 0.254890E+09 0.261452E+09 3687.79 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 83688488.18 1504651.70 1185.78 350255.11 2870724.15 0.366359E+09 64230590.90 1007.14 0.47
February 84407012.14 257083.71 0.00 449092.74 858797.84 0.283513E+09 88065050.94 0.00 0.47
March 98692768.66 961361.65 0.00 633584.18 1426892.03 0.311052E+09 0.116326E+09 0.00 0.47
April 51724627.75 3123411.08 0.00 1637676.26 2800200.09 95145456.96 0.227573E+09 436.22 0.47
May 46310918.67 842580.81 0.00 2027371.42 1089184.49 66020421.17 0.248210E+09 0.00 0.47
June 21214539.73 21350092.73 0.00 2087344.43 6202253.58 7766438.87 0.177142E+09 0.00 0.48
July 4980433.68 92361583.24 53169.22 1472737.33 15223841.66 65966.36 79788974.51 2109.78 0.48
August 4669818.88 0.115307E+09 79592.47 1130794.63 21542172.10 75581.43 61032789.91 2221.29 0.48
September 19569211.14 40291601.44 26406.25 1360223.01 14313002.12 4750736.06 0.149327E+09 741.43 0.48
October 24168869.67 66963709.03 94129.27 854540.28 17425055.46 69203287.45 0.136734E+09 2924.26 0.48
November 71071378.66 1820421.98 81.20 548493.61 1686684.88 0.246271E+09 0.128398E+09 464.68 0.47
December 79370493.63 1228684.32 1238.71 375763.96 2311994.23 0.352034E+09 67903305.81 3.05 0.47
                   
Annual Sum or Average 0.589869E+09 0.346012E+09 255802.90 12927876.97 87750802.65 0.180226E+10 0.154473E+10 9907.85 0.47
Minimum of Months 4669818.88 257083.71 0.00 350255.11 858797.84 65966.36 61032789.91 0.00 0.47
Maximum of Months 98692768.66 0.115307E+09 94129.27 2087344.43 21542172.10 0.366359E+09 0.248210E+09 2924.26 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.298154E+09 25143556.63 0.00 19729729.61 2983382.79 0.364484E+09 0.262424E+10 0.00 0.54
February 0.388294E+09 6903738.23 0.00 13444011.58 266070.88 0.328888E+09 0.220207E+10 0.00 0.54
March 0.517880E+09 14664878.91 0.00 10400996.11 680229.33 0.723205E+09 0.213271E+10 0.00 0.54
April 0.281639E+09 33468021.87 0.00 11479294.85 4595417.15 0.122555E+09 0.200073E+10 0.00 0.54
May 0.335773E+09 6063550.25 0.00 8113036.52 6348509.57 0.215063E+09 0.177064E+10 0.00 0.54
June 0.169258E+09 0.131354E+09 15199.33 7744110.40 45659091.62 2865874.32 0.115793E+10 2080.45 0.54
July 41242389.37 0.585192E+09 206429.88 6046682.20 0.106210E+09 760792.35 0.506501E+09 9501.35 0.54
August 34993459.62 0.780065E+09 487496.05 6504260.91 99241727.20 550281.20 0.387858E+09 16911.24 0.54
September 0.114301E+09 0.317929E+09 4551.30 10857886.06 33088795.95 1509200.64 0.997797E+09 100.00 0.54
October 0.125631E+09 0.507965E+09 180771.91 12277625.64 34690159.62 5184516.23 0.134088E+10 5516.18 0.54
November 0.242610E+09 21233333.09 0.00 19196018.70 1304185.20 33944883.90 0.257176E+10 0.00 0.54
December 0.290073E+09 22157991.86 0.00 20476516.70 599703.85 0.200533E+09 0.269951E+10 0.00 0.54
                   
Annual Sum or Average 0.283985E+10 0.245214E+10 894448.47 0.146270E+09 0.335667E+09 0.199954E+10 0.203926E+11 34109.23 0.54
Minimum of Months 34993459.62 6063550.25 0.00 6046682.20 266070.88 550281.20 0.387858E+09 0.00 0.54
Maximum of Months 0.517880E+09 0.780065E+09 487496.05 20476516.70 0.106210E+09 0.723205E+09 0.269951E+10 16911.24 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.128501E+10 53841635.37 0.00 57322897.40 624485.17 0.00 0.520944E+11 0.00 4.63
February 0.864229E+09 10972686.33 0.00 54467458.20 748635.90 0.00 0.471323E+11 0.00 4.68
March 0.100193E+10 250993.22 0.00 60930254.41 0.00 0.00 0.540059E+11 0.00 4.67
April 0.193432E+09 62784681.60 0.00 69493319.49 1065504.03 0.00 0.448287E+11 0.00 4.83
May 73104526.03 8571404.15 0.00 75359146.96 0.00 0.00 0.460062E+11 0.00 4.91
June 10856157.63 0.499160E+09 0.00 75869436.57 0.00 0.00 0.360971E+11 0.00 5.14
July 0.00 0.417901E+10 0.00 67586776.20 0.00 0.00 0.242717E+11 0.00 5.25
August 1117731.28 0.495420E+10 0.00 61037152.01 1259473.26 0.00 0.208504E+11 0.00 5.24
September 34057501.64 0.156574E+10 0.00 68274510.42 9375277.25 0.00 0.309694E+11 0.00 5.10
October 72145782.64 0.272758E+10 0.00 63621013.95 9891103.61 0.00 0.322532E+11 0.00 5.05
November 0.591823E+09 40957045.02 0.00 60382696.25 10034.02 0.00 0.484279E+11 0.00 4.72
December 0.849162E+09 18584644.46 0.00 59328746.05 1204307.13 0.00 0.518466E+11 0.00 4.66
                   
Annual Sum or Average 0.497687E+10 0.141216E+11 0.00 0.773673E+09 24178820.38 0.00 0.488784E+12 0.00 4.91
Minimum of Months 0.00 250993.22 0.00 54467458.20 0.00 0.00 0.208504E+11 0.00 4.63
Maximum of Months 0.128501E+10 0.495420E+10 0.00 75869436.57 9891103.61 0.00 0.540059E+11 0.00 5.25



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.481682E+09 57319019.01 0.00 71260408.02 0.00 0.00 0.573816E+11 0.00 5.00
February 0.182031E+09 12294953.35 0.00 66933031.15 0.00 0.00 0.519353E+11 0.00 5.06
March 0.264415E+09 263276.60 0.00 75087677.21 0.00 0.00 0.595025E+11 0.00 5.06
April 3661610.15 67423916.57 0.00 82066130.68 0.00 0.00 0.488423E+11 0.00 5.23
May 2397069.04 9098134.88 0.00 87632587.38 0.00 0.00 0.500020E+11 0.00 5.32
June 0.00 0.529394E+09 0.00 85495290.72 0.00 0.00 0.389524E+11 0.00 5.54
July 0.00 0.448884E+10 0.00 74105697.50 0.00 0.00 0.259920E+11 0.00 5.63
August 0.00 0.529584E+10 0.00 66573253.64 0.00 0.00 0.222717E+11 0.00 5.61
September 2185556.72 0.168012E+10 0.00 76955805.23 0.00 0.00 0.333422E+11 0.00 5.48
October 3218813.29 0.291766E+10 0.00 71817399.31 656021.54 0.00 0.347501E+11 0.00 5.41
November 81835985.87 43415889.99 0.00 73364406.18 0.00 0.00 0.530091E+11 0.00 5.09
December 0.281418E+09 20655434.43 0.00 72925787.58 101970.91 0.00 0.568713E+11 0.00 5.03
                   
Annual Sum or Average 0.130284E+10 0.151223E+11 0.00 0.904217E+09 757992.45 0.00 0.532853E+12 0.00 5.29
Minimum of Months 0.00 263276.60 0.00 66573253.64 0.00 0.00 0.222717E+11 0.00 5.00
Maximum of Months 0.481682E+09 0.529584E+10 0.00 87632587.38 656021.54 0.00 0.595025E+11 0.00 5.63



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 5287322.93 0.103083E+09 0.00 0.115060E+09 0.00 0.00 0.716127E+11 0.00 21.70
February 0.00 22265850.38 0.00 0.103246E+09 0.00 0.00 0.645624E+11 0.00 21.73
March 4835789.41 477136.35 0.00 0.113501E+09 0.00 0.00 0.736723E+11 0.00 21.70
April 0.00 0.121252E+09 0.00 0.117017E+09 0.00 0.00 0.574995E+11 0.00 22.07
May 0.00 16227065.59 0.00 0.120984E+09 0.00 0.00 0.579218E+11 0.00 22.13
June 0.00 0.929713E+09 0.00 0.112190E+09 0.00 0.00 0.429137E+11 0.00 22.51
July 0.00 0.757594E+10 0.00 88770035.54 0.00 0.00 0.266397E+11 0.00 22.68
August 0.00 0.914806E+10 0.00 76832736.92 0.00 0.00 0.222822E+11 0.00 22.73
September 0.00 0.280555E+10 0.00 0.102501E+09 0.00 0.00 0.373301E+11 0.00 22.56
October 0.00 0.494197E+10 0.00 94870395.20 0.00 0.00 0.386787E+11 0.00 22.37
November 0.00 76260723.72 0.00 0.112401E+09 0.00 0.00 0.645955E+11 0.00 21.87
December 0.00 37508692.96 0.00 0.116113E+09 0.00 0.00 0.702139E+11 0.00 21.77
                   
Annual Sum or Average 10123112.34 0.257783E+11 0.00 0.127349E+10 0.00 0.00 0.627922E+12 0.00 22.15
Minimum of Months 0.00 477136.35 0.00 76832736.92 0.00 0.00 0.222822E+11 0.00 21.70
Maximum of Months 5287322.93 0.914806E+10 0.00 0.120984E+09 0.00 0.00 0.736723E+11 0.00 22.73



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.154581E+11 0.00 0.00 0.00 17707635.06 0.00 0.00 0.00 1.09
February 0.136845E+11 0.00 0.00 0.00 3810752.34 0.00 0.00 0.00 1.09
March 0.157264E+11 0.00 0.00 0.00 81601.12 0.00 0.00 0.00 1.09
April 0.122745E+11 0.00 0.00 0.00 20744995.35 0.00 0.00 0.00 1.09
May 0.123592E+11 0.00 0.00 0.00 2786673.54 0.00 0.00 0.00 1.09
June 0.922410E+10 0.00 0.00 0.00 0.159189E+09 0.00 0.00 0.00 1.11
July 0.597001E+10 0.269505E+09 0.00 494.37 0.102709E+10 0.00 103400.70 0.00 1.11
August 0.505297E+10 0.480794E+09 0.00 9733.66 0.108472E+10 0.00 15408244.68 0.00 1.12
September 0.802360E+10 0.181614E+09 0.00 124612.53 0.321050E+09 0.00 42755611.66 0.00 1.12
October 0.824677E+10 0.470052E+09 0.00 273744.64 0.407439E+09 0.00 0.229120E+09 0.00 1.11
November 0.137819E+11 0.00 0.00 0.00 13078181.09 0.00 0.00 0.00 1.09
December 0.150878E+11 0.00 0.00 0.00 6433642.23 0.00 0.00 0.00 1.09
                   
Annual Sum or Average 0.134890E+12 0.140197E+10 0.00 408585.19 0.306413E+10 0.00 0.287387E+09 0.00 1.10
Minimum of Months 0.505297E+10 0.00 0.00 0.00 81601.12 0.00 0.00 0.00 1.09
Maximum of Months 0.157264E+11 0.480794E+09 0.00 273744.64 0.108472E+10 0.00 0.229120E+09 0.00 1.12



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:59:53

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.161840E+12 0.937022E+10 0.114307E+12 0.534056E+12 0.217661E+12
February 0.210879E+12 0.829834E+10 0.106644E+12 0.473604E+12 0.152708E+12
March 0.300212E+12 0.950199E+10 0.121521E+12 0.543653E+12 0.168242E+12
April 0.388554E+12 0.749089E+10 0.934855E+11 0.425532E+12 0.242616E+12
May 0.416878E+12 0.771615E+10 0.945412E+11 0.429178E+12 0.246872E+12
June 0.410797E+12 0.554647E+10 0.685732E+11 0.309899E+12 0.373667E+12
July 0.434824E+12 0.227230E+10 0.309320E+11 0.151969E+12 0.669508E+12
August 0.395038E+12 0.145120E+10 0.213695E+11 0.111530E+12 0.742089E+12
September 0.311012E+12 0.440527E+10 0.552572E+11 0.255985E+12 0.481595E+12
October 0.212038E+12 0.459036E+10 0.527192E+11 0.263340E+12 0.542773E+12
November 0.177915E+12 0.842223E+10 0.102537E+12 0.480070E+12 0.214363E+12
December 0.142003E+12 0.923793E+10 0.111351E+12 0.524328E+12 0.236214E+12
           
Annual Sum or Average 0.356199E+13 0.783034E+11 0.973237E+12 0.450314E+13 0.428831E+13
Minimum of Months 0.142003E+12 0.145120E+10 0.213695E+11 0.111530E+12 0.152708E+12
Maximum of Months 0.434824E+12 0.950199E+10 0.121521E+12 0.543653E+12 0.742089E+12