Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 09:00:07
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10894.26 | 960.25 | 960.25 |
Net Site Energy | 10894.26 | 960.25 | 960.25 |
Total Source Energy | 24293.05 | 2141.25 | 2141.25 |
Net Source Energy | 24293.05 | 2141.25 | 2141.25 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 268.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1434.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 767.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 242.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1745.01 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 651.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 634.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 179.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 185.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 2843.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5993.12 | 4901.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 268.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1434.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 767.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 242.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 32.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 634.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 179.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 185.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 2843.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 268.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1434.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 767.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 242.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1745.01 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 651.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 634.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 179.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 185.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 2843.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 89.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 206.22 | 274.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 233.01 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 528.25 | 432.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 89.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 206.22 | 274.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 233.01 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 528.25 | 432.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5993.124 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5993.124 | 100.00 |
Total On-Site and Utility Electric Sources | 5993.124 | 100.00 |
Total Electricity End Uses | 5993.124 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 324.70 | 22.81 |
Air to Air Heat Recovery for Heating | 1098.59 | 77.19 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 1423.29 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 193.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7930.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 9.1389 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.3365 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.3365 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 9.2031 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 6.1031 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.8125 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.3656 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 8.7188 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.5531 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.5531 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 6.3938 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.5531 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.3656 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.3656 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7219 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 6.3938 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 6.8557 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 6.8557 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.1389 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.3365 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.3365 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 9.2031 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 6.1031 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.8125 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.3656 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 8.7188 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.5531 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.5531 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 6.3938 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.5531 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.5531 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.5531 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.3656 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.3656 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7219 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 6.3938 | 18.58 | 0.0000 | |
Total | 11345.29 | 6.8557 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 6.8557 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.4542 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 25-JUL-19:10 | 18-DEC-21:49 | - | - | - | - | - | - | - | - | - | - | 05-JAN-21:10 |
Heating | 0.00 | 123172.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 155051.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 88772.42 | 75123.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 32150.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38655.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 8348.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3685.21 | 253258.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1870.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 416814.12 | 451554.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 123172.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 155051.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58789.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1846.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 38655.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 8348.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3685.21 | 253258.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 535.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1093.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 290.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4544.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2429.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 769.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5526.46 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2063.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2009.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 568.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 586.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.38 | 3082.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 195.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 18980.22 | 5312.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 25.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 400.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 214.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 67.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.11 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 177.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 50.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 51.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 271.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1672.96 | 468.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 25.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 400.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 214.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 67.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.11 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 177.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 50.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 51.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 271.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1672.96 | 468.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.92 | 0.516942 | 0.430000 | 1.25 | 1.00 | 0.500000 | 0.000737 | 0.000050 | 1.25 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.376128 | 0.135880 | 0.309000 | 0.116224 | 0.376404 | 0.500000 | 0.002804 | 0.000029 | 0.135644 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.282903 | 0.209202 | 0.476000 | 0.134662 | 0.557871 | 0.500000 | 0.001821 | 0.000013 | 0.134662 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.288826 | 0.433317 | 0.300000 | 0.086648 | 1.00 | 0.500000 | 0.000879 | 0.000018 | 0.086648 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.141502 | 0.510285 | 0.599000 | 0.084760 | 1.00 | 0.500000 | 0.000747 | 0.000012 | 0.084760 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.78 | 0.062433 | 0.300000 | 1.13 | 0.300000 | 0.500000 | 0.024216 | 0.000065 | 1.13 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.59 | 0.090776 | 0.626000 | 0.992438 | 0.626000 | 0.500000 | 0.004197 | 0.000100 | 0.992438 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.26 | 0.189502 | 0.528000 | 2.78 | 0.528000 | 0.500000 | 0.002011 | 0.000252 | 2.78 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.66 | 0.716584 | 0.420000 | 0.695662 | 1.00 | 0.500000 | 0.000532 | 0.000113 | 0.695662 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.54 | 0.099390 | 0.685000 | 1.74 | 0.685000 | 0.500000 | 0.003833 | 0.000124 | 1.74 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.66 | 0.094883 | 0.654000 | 1.74 | 0.654000 | 0.500000 | 0.004015 | 0.000126 | 1.74 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.58 | 0.054874 | 0.300000 | 0.774056 | 0.300000 | 0.500000 | 0.012488 | 0.000050 | 0.774056 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.872474 | 0.359941 | 0.300000 | 0.261742 | 0.959842 | 0.500000 | 0.001059 | 0.000071 | 0.325861 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 5743.47 | 0.000050 | 119.77 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3365.31 | 0.000029 | 91.84 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1531.88 | 0.000013 | 34.63 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2082.82 | 0.000018 | 56.16 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1390.24 | 0.000012 | 33.55 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 7442.01 | 0.000065 | 158.76 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 11437.51 | 0.000100 | 259.04 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 28849.77 | 0.000252 | 644.23 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 6029.05 | 0.000053 | 172.28 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 6022.55 | 0.000053 | 172.10 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 34778.84 | 0.000304 | 993.81 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 34674.06 | 0.000303 | 990.81 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 6016.79 | 0.000053 | 171.93 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 6010.28 | 0.000053 | 171.75 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12868.85 | 0.000113 | 319.69 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1862.63 | 0.000016 | 53.22 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1861.83 | 0.000016 | 53.20 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8972.06 | 0.000078 | 256.37 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 14225.72 | 0.000124 | 309.27 |
DINING_FLR_6 VAV BOX REHEAT COIL | 14360.28 | 0.000126 | 312.48 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 5673.76 | 0.000050 | 122.13 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8084.94 | 0.000071 | 220.65 |
VAV WITH REHEAT HEATING COIL | 171111.74 | 0.001497 | 2904.80 |
FLR_3_DOAS HEATING COIL | 14143.00 | 0.000124 | 240.09 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.15 | 0.000053 | 0.000396 |
ROOM_2_FLR_3 FAN COIL | 1.14 | 0.000053 | 0.000393 |
ROOM_3_MULT19_FLR_3 FAN COIL | 6.34 | 0.000304 | 0.002165 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.93 | 0.000303 | 0.002502 |
ROOM_5_FLR_3 FAN COIL | 0.998411 | 0.000053 | 0.000346 |
ROOM_6_FLR_3 FAN COIL | 0.990326 | 0.000053 | 0.000343 |
ROOM_1_FLR_6 FAN COIL | 0.304699 | 0.000016 | 0.000105 |
ROOM_2_FLR_6 FAN COIL | 0.301986 | 0.000016 | 0.000104 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.34 | 0.000078 | 0.000471 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.15 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.14 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.34 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.93 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.998411 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.990326 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.304699 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.301986 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.34 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008543 | 12.80 | 0.008500 | 0.000396 | 1.15 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008544 | 12.80 | 0.008500 | 0.000393 | 1.14 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008472 | 12.80 | 0.008472 | 0.002165 | 6.34 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008704 | 12.80 | 0.008500 | 0.002502 | 6.93 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008549 | 12.80 | 0.008500 | 0.000346 | 0.998411 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008549 | 12.80 | 0.008500 | 0.000343 | 0.990326 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008541 | 12.80 | 0.008500 | 0.000105 | 0.304699 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008541 | 12.80 | 0.008500 | 0.000104 | 0.301986 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008612 | 12.80 | 0.008500 | 0.000471 | 1.34 | |
VAV WITH REHEAT COOLING COIL | 30.62 | 6.70 | 0.008339 | 10.70 | 0.008339 | 0.018818 | 24.82 | 526849.16 |
FLR_3_DOAS COOLING COIL | 38.10 | 6.70 | 0.006871 | 11.79 | 0.006871 | 0.002048 | 2.05 | 57348.72 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 13.72 | 11.80 | 24.95 | 11.80 | 24.82 | 24.82 | 0.300000 | 0.475275 | 24.82 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 24.82 | 11.66 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 24.82 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.018818 | 0.000025 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001497 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002048 | 0.000232 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000124 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.027692 | 5706.34 | |
HEATSYS1 PUMP | 0.003574 | 1076.36 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003574 | 0.428890 |
COOLSYS1 | 0.027692 | 3.32 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 408539.38 | 408539.38 | 0.003574 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.027692 | 3950.69 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.027692 | 775307.86 | 775976.71 | 88.46 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 9.139 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.519 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.336 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.096 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.336 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.096 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 9.203 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.583 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 6.103 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.793 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.813 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.343 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.366 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.746 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 8.719 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.789 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.366 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 78.186 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.366 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 78.186 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.722 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2946.209 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 18084.325 | 9.139 | 169.807 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18084.325 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 894.495 | 13.336 | 82.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 894.495 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1035.829 | 13.336 | 82.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1035.829 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 1511.551 | 9.203 | 569.967 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1511.551 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 578.329 | 6.103 | 283.494 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 578.329 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 453.605 | 5.813 | 54.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 453.605 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1957.673 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1957.673 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11405.759 | 8.719 | 27.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11405.759 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 111.660 | 4.553 | 74.440 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.660 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 111.691 | 4.553 | 74.460 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.691 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2489.757 | 6.394 | 118.803 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.757 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 111.691 | 4.553 | 74.460 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.691 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3437.839 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3437.839 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3437.839 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3437.839 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1210.923 | 11.722 | 54.453 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1210.923 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2635.024 | 6.394 | 118.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2635.024 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 1.067 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.370 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.442 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.217 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.286 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7702 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5624 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5260 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6546 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6103 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.55514967E-15 | 0.35055860E-16 | -0.14326465E-09 | 0.28783368E-17 |
29 | 8 | 0.20966873E-07 | 0.14258959E-12 | 0.36819155E-03 | -0.23840058E-09 |
30 | 7 | -0.11954852E-01 | 0.74774803E-08 | -0.22672946E-01 | 0.13593102E-03 |
31 | 6 | 0.39755982 | 0.26159305E-05 | 0.46545104 | -0.46559307E-02 |
32 | 5 | -5.1145337 | 0.98147117E-04 | -4.3902405 | 0.62241115E-01 |
33 | 4 | 32.666535 | 0.80637729E-03 | 21.240866 | -0.41765750 |
34 | 3 | -110.51061 | 0.17642800E-02 | -55.229641 | 1.5048560 |
35 | 2 | 196.42192 | 0.99585215E-03 | 77.513220 | -2.8894543 |
36 | 1 | -170.90254 | 0.10665179E-03 | -55.149704 | 2.7409959 |
37 | 0 | 57.057407 | 0.60929387E-06 | 15.576129 | |
38 | 9 | 0.10314710E-14 | 0.47183642E-16 | -0.12881513E-09 | -0.40099708E-17 |
39 | 8 | 0.18927665E-07 | 0.17950474E-12 | 0.34608657E-03 | -0.21521408E-09 |
40 | 7 | -0.11292911E-01 | 0.96443222E-08 | -0.21719088E-01 | 0.12840450E-03 |
41 | 6 | 0.37957032 | 0.34070209E-05 | 0.45007157 | -0.44438791E-02 |
42 | 5 | -4.9389364 | 0.12890179E-03 | -4.2718596 | 0.60063826E-01 |
43 | 4 | 31.889569 | 0.10670331E-02 | 20.777560 | -0.40734193 |
44 | 3 | -108.85680 | 0.23501275E-02 | -54.313423 | 1.4809641 |
45 | 2 | 194.78196 | 0.13343675E-02 | 76.673975 | -2.8634131 |
46 | 1 | -170.29645 | 0.14368413E-03 | -54.907648 | 2.7303734 |
47 | 0 | 57.057407 | 0.82565881E-06 | 15.617726 | |
48 | 9 | 0.86975537E-15 | 0.52023775E-16 | -0.12536948E-09 | -0.54620444E-17 |
49 | 8 | 0.18440443E-07 | 0.18784465E-12 | 0.34068694E-03 | -0.20967419E-09 |
50 | 7 | -0.11130813E-01 | 0.10155400E-07 | -0.21485363E-01 | 0.12656138E-03 |
51 | 6 | 0.37516444 | 0.35965268E-05 | 0.44629465 | -0.43919449E-02 |
52 | 5 | -4.8959230 | 0.13636263E-03 | -4.2427425 | 0.59530495E-01 |
53 | 4 | 31.699203 | 0.11309484E-02 | 20.663505 | -0.40481456 |
54 | 3 | -108.45147 | 0.24950915E-02 | -54.087828 | 1.4751087 |
55 | 2 | 194.37988 | 0.14187814E-02 | 76.467519 | -2.8570287 |
56 | 1 | -170.14779 | 0.15298304E-03 | -54.848449 | 2.7277680 |
57 | 0 | 57.057407 | 0.88039223E-06 | 15.628184 | |
58 | 9 | 0.12430042E-14 | 0.43603463E-16 | -0.13615479E-09 | -0.52742981E-17 |
59 | 8 | 0.19963588E-07 | 0.16114398E-12 | 0.35741204E-03 | -0.22699287E-09 |
60 | 7 | -0.11632381E-01 | 0.85488282E-08 | -0.22208377E-01 | 0.13226440E-03 |
61 | 6 | 0.38879653 | 0.30047059E-05 | 0.45796739 | -0.45526330E-02 |
62 | 5 | -5.0290001 | 0.11318598E-03 | -4.3326723 | 0.61180550E-01 |
63 | 4 | 32.288109 | 0.93328928E-03 | 21.015642 | -0.41263319 |
64 | 3 | -109.70522 | 0.20484795E-02 | -54.784283 | 1.4932205 |
65 | 2 | 195.62339 | 0.11595496E-02 | 77.105128 | -2.8767741 |
66 | 1 | -170.60747 | 0.12450863E-03 | -55.031726 | 2.7358244 |
67 | 0 | 57.057407 | 0.71328115E-06 | 15.596176 | |
68 | 9 | 0.10418955E-14 | 0.45554749E-16 | -0.13285794E-09 | -0.34221686E-17 |
69 | 8 | 0.19498290E-07 | 0.16949498E-12 | 0.35235048E-03 | -0.22170227E-09 |
70 | 7 | -0.11480752E-01 | 0.90423087E-08 | -0.21989859E-01 | 0.13054032E-03 |
71 | 6 | 0.38467563 | 0.31853038E-05 | 0.45444290 | -0.45040579E-02 |
72 | 5 | -4.9887746 | 0.12022067E-03 | -4.3055366 | 0.60681782E-01 |
73 | 4 | 32.110117 | 0.99300969E-03 | 20.909427 | -0.41027004 |
74 | 3 | -109.32633 | 0.21828955E-02 | -54.574228 | 1.4877470 |
75 | 2 | 195.24766 | 0.12373115E-02 | 76.912747 | -2.8708078 |
76 | 1 | -170.46860 | 0.13302463E-03 | -54.976289 | 2.7333905 |
77 | 0 | 57.057407 | 0.76310210E-06 | 15.605744 | |
78 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
79 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
80 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
81 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
82 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
83 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
84 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
85 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
86 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
87 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
88 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
89 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
90 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
91 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
92 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
93 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4711_SHGC_0.25 | 37 | 1 | VerySmooth | 2.678 | 2.678 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.4711_SHGC_0.25 | 38 | 1 | VerySmooth | 2.678 | 2.678 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.39142E-002 | 0.16139 | 0.61472 | 0.61472 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11798 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.39142E-002 | 0.16139 | 0.61472 | 0.61472 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11798 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 8.5405E-002 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.8071E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.4529E-002 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.1339E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 6.5404E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.4194E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.6511E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.7811E-003 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 9.6576E-002 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.6681E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1072 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.0654E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.2445E-002 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.0583E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 2.9789E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.2036E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.0964E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.1972E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.6150E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.0418E-003 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.5433E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.1646E-003 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.6108E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.2309E-003 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.0964E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.1972E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.6150E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.0418E-003 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.5433E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.1646E-003 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.6108E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.2309E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 34816.87302 | 34816.87302 | 2.91690 | 2.91690 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 30.43000 | 6.85931E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4489.20702 | 4489.20702 | 0.37613 | 0.37613 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2744.70018 | 2744.70018 | 0.13564 | 0.13564 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3376.42503 | 3376.42503 | 0.28290 | 0.28290 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 35.84667 | 6.86787E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 915.76226 | 915.76226 | 4.52589E-002 | 9.17347E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3447.91952 | 3447.91952 | 0.28883 | 0.28883 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1686.46283 | 1686.46283 | 8.33482E-002 | 8.33482E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1689.19897 | 1689.19897 | 0.14150 | 0.14150 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 35.84667 | 6.86787E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1002.50476 | 1002.50476 | 4.95457E-002 | 5.77652E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 45115.89851 | 45115.89851 | 3.77962 | 3.77962 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 37.14667 | 6.86994E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2255.84139 | 2255.84139 | 0.11148 | 0.11148 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 18904.87740 | 18904.87740 | 1.58536 | 1.58536 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 6896.33397 | 6896.33397 | 0.34082 | 0.67639 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 62762.54279 | 62762.54279 | 5.26031 | 5.26031 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 16141.53833 | 16141.53833 | 0.79775 | 1.89399 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 10148.74751 | 10148.74751 | 1.14567 | 1.14567 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 6029.16885 | 6029.16885 | 0.29972 | 0.29972 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10071.62283 | 10071.62283 | 1.13696 | 1.13696 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 6022.66753 | 6022.66753 | 0.29939 | 0.29939 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 56169.92329 | 56169.92329 | 6.34067 | 6.34067 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 34779.17169 | 34779.17169 | 1.72895 | 1.72895 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 61420.94874 | 61420.94874 | 6.93399 | 6.93399 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 37.71000 | 6.87086E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 34674.39384 | 34674.39384 | 1.72375 | 1.72375 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 8844.26363 | 8844.26363 | 0.99841 | 0.99841 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 33.48500 | 6.86412E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 6016.90550 | 6016.90550 | 0.29911 | 0.29911 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 8772.64884 | 8772.64884 | 0.99033 | 0.99033 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 33.16000 | 6.86360E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 6010.40248 | 6010.40248 | 0.29878 | 0.29878 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 19771.06416 | 19771.06416 | 1.65634 | 1.65634 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 37.84000 | 6.87107E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 9685.15661 | 9685.15661 | 0.47867 | 0.47867 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2699.12977 | 2699.12977 | 0.30470 | 0.30470 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80000 | 6.86940E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1862.67040 | 1862.67040 | 9.25952E-002 | 9.25952E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2675.09705 | 2675.09705 | 0.30199 | 0.30199 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1861.86078 | 1861.86078 | 9.25549E-002 | 9.25549E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 11852.85882 | 11852.85882 | 1.33809 | 1.33809 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 8972.19828 | 8972.19828 | 0.44602 | 0.44602 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 30311.97684 | 30311.97684 | 2.54273 | 2.54273 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 6253.81623 | 6253.81623 | 0.30908 | 1.18780 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31752.38433 | 31752.38433 | 2.66352 | 2.66352 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 6387.60712 | 6387.60712 | 0.31569 | 1.18780 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30714.36361 | 30714.36361 | 2.58019 | 2.58019 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 36.93000 | 6.86961E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2138.99900 | 2138.99900 | 0.10570 | 0.36735 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -5.20000 | 2.80840E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10414.50118 | 10414.50118 | 0.87247 | 0.87247 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 38.10000 | 6.87148E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6593.39145 | 6593.39145 | 0.32586 | 0.32586 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 464089.78 | 24.81824 | 24.81824 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 171268.08 | 7.45228 | 7.45228 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 54460.49 | 19.03245 | 2.05125 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 47141.68 | 5.28087 | 2.05125 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.91690 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.51694 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.25427 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.37027E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.02464E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.25427 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5743.47159 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.02464E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 119.77020 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.37613 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13588 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30900 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11622 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37640 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.80394E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.94412E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13564 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3365.31015 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.94412E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 91.84447 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.28290 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20920 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47600 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13466 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55787 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.82121E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.34015E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13466 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1531.87642 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.34015E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 34.62965 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.28883 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.43332 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.66478E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.79263E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.82214E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.66478E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2082.81836 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.82214E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 56.15743 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.14150 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.51028 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.59900 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47600E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.46642E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21624E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.47600E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1390.23512 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21624E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 33.55026 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.77962 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.24332E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.13389 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.42161E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.51059E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.13389 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7442.00679 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.51059E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 158.76401 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.58536 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.07758E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.62600 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.99244 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62600 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.19715E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00060E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.99244 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11437.50599 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00060E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 259.03904 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.26031 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18950 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52800 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.77744 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52800 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.01054E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.52390E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.77744 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 28849.76647 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.52390E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 644.22920 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.14567 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.14567 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.27448E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.95994E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77086 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54347E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.95994E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.14567 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6029.04981 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.27448E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 172.28274 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.13696 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.13696 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.26879E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.93016E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77085 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54376E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.93016E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.13696 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6022.54861 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.26879E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 172.09700 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.34067 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.34067 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.04260E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.16547E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77125 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47163E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47163E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.16547E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.34067 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 34778.84195 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.04260E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 993.80689 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.93399 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.93399 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.03344E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.50232E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77029 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.70439E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.50232E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.93399 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 34674.06500 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.03344E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 990.81354 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.99841 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.99841 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.26375E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.45627E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77085 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54910E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.45627E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.99841 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6016.78668 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.26375E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 171.93239 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.99033 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.99033 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.25806E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.42860E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77085 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54943E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.42860E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.99033 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6010.28378 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.25806E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 171.74660 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.65634 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.71658 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.42000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.69566 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.31689E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.12582E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.69566 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12868.84709 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12582E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 319.68643 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.30470 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.30470 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.62951E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.05243E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77086 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54089E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.05243E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.30470 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1862.63479 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.62951E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 53.22339 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.30199 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.30199 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.62881E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.04316E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77086 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54126E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.04316E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.30199 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1861.82519 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.62881E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 53.20026 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.33809 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.33809 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.84915E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.71158E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77051 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61185E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.71158E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.33809 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8972.06113 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.84915E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 256.36819 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.54273 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.93903E-002 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.68500 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.74177 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68500 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.83337E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.24453E-004 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.74177 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14225.72396 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.24453E-004 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 309.27272 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.66352 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.48832E-002 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.65400 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.74194 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65400 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.01546E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.25630E-004 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.74194 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14360.27516 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25630E-004 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 312.48269 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.58019 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.48737E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77406 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.24883E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.96365E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.77406 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5673.75994 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.96365E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 122.13218 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87247 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35994 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26174 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.95984 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05851E-003 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.07306E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32586 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8084.94226 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.07306E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 220.65436 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 13.71504 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.79550 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.94680 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.79550 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.81824 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 24.81824 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.47528 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 24.81824 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.81824 |
338 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 11.66146 |
339 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 30.61917 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.69725 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.33878E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.33878E-003 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 526849.15645 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.88178E-002 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 24.81824 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 171111.74393 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49696E-003 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2904.79849 |
351 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 24.81824 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.88178E-002 |
353 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.53053E-005 |
354 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.49696E-003 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
356 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
357 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 38.10000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.79311 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.87148E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.87148E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 57348.72296 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.04836E-003 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 14143.00265 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.23729E-004 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 240.09207 |
369 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.04836E-003 |
371 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.32474E-004 |
372 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.23729E-004 |
373 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.76922E-002 |
374 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 5706.33615 |
375 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.57408E-003 |
376 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.42889 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.57408E-003 |
378 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1076.35616 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 408539.38281 |
381 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 408539.38000 |
382 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.57408E-003 |
383 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.76922E-002 |
384 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.32306 |
385 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.76922E-002 |
386 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3950.68898 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.76922E-002 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 775307.86251 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 775976.71000 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 88.46134 |
391 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
392 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
393 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
394 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
395 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 5773.50 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3379.23 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1539.33 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2091.50 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1396.61 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 7480.30 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 11493.11 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 28991.54 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 6495.58 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 6488.58 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 37469.88 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 37357.01 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 6482.37 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 6475.37 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12926.57 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2006.72 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2005.85 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 9666.06 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 14298.02 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 14433.21 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 5702.78 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8118.37 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 128868.67 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 10651.46 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 19326.80 | 14631.60 | 4695.21 | 0.76 | 3107.84 | 31.52 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 19180.90 | 14520.74 | 4660.16 | 0.76 | 3084.24 | 31.28 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 106443.82 | 80883.92 | 25559.91 | 0.76 | 17465.16 | 177.14 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 120264.02 | 89717.09 | 30546.93 | 0.75 | 18886.89 | 191.56 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 16859.35 | 12756.74 | 4102.61 | 0.76 | 2708.57 | 27.47 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 16723.83 | 12653.78 | 4070.04 | 0.76 | 2686.65 | 27.25 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5137.75 | 3890.56 | 1247.20 | 0.76 | 826.52 | 8.38 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 5092.34 | 3856.03 | 1236.31 | 0.76 | 819.17 | 8.31 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 22843.24 | 17183.51 | 5659.73 | 0.75 | 3633.77 | 36.86 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 657043.29 | 408823.80 | 248219.49 | 0.62 | 94171.97 | 955.14 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 51198.70 | 32051.32 | 19147.38 | 0.63 | 5018.41 | 50.90 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.370 | 1.137 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.370 | 1.137 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.370 | 1.137 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.370 | 1.137 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 2.2854485109E-002 | 3.6417926872E-002 | Pass | Pass | 0.1397990370 | 0.4261713077 | Fail | Fail |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.8938599535E-002 | 9.1665750668E-002 | Pass | Pass | 0.1875934376 | 1.0122414484 | Fail | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.7263700033E-002 | 6.9984161083E-002 | Pass | Pass | 0.1217947123 | 0.3184985555 | Fail | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.5161899379E-002 | 2.6454578829E-002 | Pass | Pass | 0.1432839278 | 0.5201413933 | Fail | Fail |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.4780721023E-002 | 3.2211972635E-002 | Pass | Pass | 0.1097118193 | 0.2077680942 | Fail | Fail |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1585653581 | 0.3948409605 | Fail | Pass | 9.8392589906E-002 | 0.1970808883 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1316839770 | 0.1895525334 | Pass | Pass | 0.1257583865 | 0.3859893252 | Fail | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.1664374851E-002 | 9.0516792723E-002 | Pass | Pass | 0.1144862844 | 0.2661634854 | Fail | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.8809732947E-002 | 0.1936807737 | Pass | Pass | 0.2221653823 | 0.5214764941 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.7429750320E-002 | 0.1697669114 | Pass | Pass | 0.2264568744 | 0.8894375837 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.4782415541E-002 | 3.0127790382E-002 | Pass | Pass | 3.1399338663E-002 | 6.3545642718E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.0645972752E-002 | 4.0974309749E-002 | Pass | Pass | 0.1549959072 | 0.2858858729 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.7311780609E-002 | 0.1782244936 | Pass | Pass | 0.1630085722 | 0.4931039772 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.3993961851E-002 | 8.1243231637E-002 | Pass | Pass | 0.1313302839 | 0.3317068366 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.2409069699E-002 | 2.4392788467E-002 | Pass | Pass | 0.1315167970 | 0.3976812720 | Fail | Fail |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.3540602364E-002 | 0.1961408433 | Pass | Pass | 0.2278542014 | 0.6802298066 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.4798841285E-002 | 0.1915502319 | Pass | Pass | 0.2043472267 | 0.6941834224 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.6830506586E-002 | 0.2695658626 | Pass | Pass | 0.2405165366 | 0.6348369291 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1416336842 | 0.2262486470 | Fail | Fail | 0.1306207554 | 0.3693040131 | Fail | Fail |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1269137781 | 0.2101782842 | Fail | Fail | 0.1292836157 | 0.4281201330 | Fail | Fail |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1600627903 | 0.3647620116 | Fail | Pass | 0.1088960089 | 0.2211504973 | Pass | Fail |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.5334674328E-002 | 3.4227030562E-002 | Pass | Pass | 0.1228581293 | 0.3053477304 | Fail | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3235.00 | 66.86 | 753.95 | 3856.46 | 6262.61 | 14174.88 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.678 | 0.251 | 0.251 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.678 | 0.251 | 0.251 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.678 | 0.251 | 0.251 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.678 | 0.251 | 0.251 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.678 | 0.251 | 0.251 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.678 | 0.251 | 0.251 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.678 | 0.251 | 0.251 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.678 | 0.251 | 0.251 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.678 | 0.251 | 0.251 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.678 | 0.251 | 0.251 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.678 | 0.251 | 0.251 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.678 | 0.251 | 0.251 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.678 | 0.251 | 0.251 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.678 | 0.251 | 0.251 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.678 | 0.251 | 0.251 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.678 | 0.251 | 0.251 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.678 | 0.251 | 0.251 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.678 | 0.251 | 0.251 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.678 | 0.251 | 0.251 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.678 | 0.251 | 0.251 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.678 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.678 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.678 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.678 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 432.95 | 2.678 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.678 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.1389 | 1978.83 | 18084.33 | LightsWired | LTG_SCH_BASEMENT | 51.16 | 168.00 | 51.10 | 0.0000 | Y | 173.46 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.3365 | 67.07 | 894.50 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.61 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.3365 | 77.67 | 1035.83 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 9.97 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 9.2031 | 164.24 | 1511.55 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 16.63 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 6.1031 | 94.76 | 578.33 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 2.78 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.8125 | 78.04 | 453.60 | LightsWired | LTG_SCH_LAUNDRY | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 4.37 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.3656 | 188.86 | 1957.67 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.12 | 0.0000 | Y | 18.05 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 8.7188 | 1308.19 | 11405.76 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 56.99 | 0.0000 | Y | 122.01 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.5531 | 156.09 | 710.69 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.5531 | 156.07 | 710.61 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.5531 | 1863.81 | 8486.17 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 76.02 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.5531 | 1864.32 | 8488.49 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 76.04 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.5531 | 156.09 | 710.69 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.5531 | 156.07 | 710.61 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 6.3938 | 1557.62 | 9959.03 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 109.60 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.5531 | 39.02 | 177.67 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.59 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.5531 | 39.02 | 177.65 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.59 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.5531 | 220.77 | 1005.22 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 9.00 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.3656 | 331.66 | 3437.84 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 53.88 | 0.0000 | Y | 34.77 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.3656 | 331.66 | 3437.84 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 53.88 | 0.0000 | Y | 34.77 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7219 | 103.30 | 1210.92 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.33 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 6.3938 | 412.12 | 2635.02 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 29.00 |
Interior Lighting Total | 6.8557 | 11345.29 | 77780.02 | 507.72 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 11405.76 | 798.40 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 11405.76 | 0.00 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1957.67 | 763.49 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 1957.67 | 0.00 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3437.84 | 687.57 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3437.84 | 0.00 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3437.84 | 687.57 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3437.84 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 15448.40 | AstronomicalClock | - | 83.77 | 83.77 | 242.91 | |
Exterior Lighting Total | 15448.40 | 242.91 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 408539.38 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 775976.71 | 2.96 | 776113.11 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11087.00 | 19326.80 | 14631.60 | 4695.21 | 0.76 | - | 3107.84 | 31.52 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11003.61 | 19180.90 | 14520.74 | 4660.16 | 0.76 | - | 3084.24 | 31.28 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 60628.54 | 106443.82 | 80883.92 | 25559.91 | 0.76 | - | 17465.16 | 177.14 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 70059.62 | 120264.02 | 89717.09 | 30546.93 | 0.75 | - | 18886.89 | 191.56 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9676.82 | 16859.35 | 12756.74 | 4102.61 | 0.76 | - | 2708.57 | 27.47 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9599.35 | 16723.83 | 12653.78 | 4070.04 | 0.76 | - | 2686.65 | 27.25 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2946.58 | 5137.75 | 3890.56 | 1247.20 | 0.76 | - | 826.52 | 8.38 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2920.64 | 5092.34 | 3856.03 | 1236.31 | 0.76 | - | 819.17 | 8.31 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 13191.40 | 22843.24 | 17183.51 | 5659.73 | 0.75 | - | 3633.77 | 36.86 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 526849.16 | 657043.29 | 408823.80 | 248219.49 | 0.62 | - | 94171.97 | 955.14 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 57348.72 | 51198.70 | 32051.32 | 19147.38 | 0.63 | - | 5018.41 | 50.90 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 5743.47 | 5773.50 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3365.31 | 3379.23 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1531.88 | 1539.33 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2082.82 | 2091.50 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1390.24 | 1396.61 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 7442.01 | 7480.30 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11437.51 | 11493.11 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 28849.77 | 28991.54 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6029.05 | 6495.58 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6022.55 | 6488.58 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 34778.84 | 37469.88 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 34674.06 | 37357.01 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6016.79 | 6482.37 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6010.28 | 6475.37 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12868.85 | 12926.57 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1862.63 | 2006.72 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1861.83 | 2005.85 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 8972.06 | 9666.06 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14225.72 | 14298.02 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14360.28 | 14433.21 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 5673.76 | 5702.78 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8084.94 | 8118.37 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 171111.74 | 128868.67 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 14143.00 | 10651.46 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.15 | 806.14 | 703.64 | 1.00 | 1.16 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.14 | 800.01 | 703.64 | 1.00 | 1.17 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.34 | 4461.52 | 703.64 | 1.00 | 0.96 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.93 | 4879.01 | 703.64 | 1.00 | 0.95 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.00 | 702.52 | 703.64 | 1.00 | 1.20 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.99 | 696.83 | 703.64 | 1.00 | 1.20 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.30 | 214.40 | 703.64 | 1.00 | 1.70 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.30 | 212.49 | 703.64 | 1.00 | 1.71 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.34 | 941.53 | 703.64 | 1.00 | 1.13 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 24.82 | 55608.71 | 2240.64 | 1.00 | 1.11 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.027692 | 5706.34 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003574 | 1076.36 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.027692 | 3950.69 | 142664.32 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 34816.87 | 34816.87 | 17.59 | 2.917 | 2.917 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00919 | 30.43 | 0.00686 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4489.21 | 4489.21 | 66.93 | 0.376 | 0.376 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00899 | 37.99 | 0.00687 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3376.43 | 3376.43 | 43.47 | 0.283 | 0.283 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00931 | 35.85 | 0.00687 | 0.092 | 0.00 |
MECH_FLR_1 | 3447.92 | 3447.92 | 20.99 | 0.289 | 0.289 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00862 | 33.03 | 0.00686 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1689.20 | 1689.20 | 17.83 | 0.142 | 0.142 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00871 | 35.85 | 0.00687 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 45115.90 | 45115.90 | 578.12 | 3.780 | 3.780 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 24.00 | 24.00 | 0.00854 | 37.15 | 0.00687 | 0.000 | 0.00 |
CAFE_FLR_1 | 18904.88 | 18904.88 | 100.10 | 1.585 | 1.585 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 23.99 | 0.01016 | 37.99 | 0.00687 | 0.676 | 0.00 |
LOBBY_FLR_1 | 62762.54 | 62762.54 | 47.98 | 5.260 | 5.260 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.99 | 0.00999 | 38.10 | 0.00687 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 10148.75 | 10148.75 | 260.08 | 1.146 | 1.146 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00854 | 36.63 | 0.00687 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10071.62 | 10071.62 | 258.13 | 1.137 | 1.137 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00854 | 36.63 | 0.00687 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 56169.92 | 56169.92 | 2290.42 | 6.341 | 6.341 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21.11 | 21.11 | 0.00847 | 38.10 | 0.00687 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 61420.95 | 61420.95 | 2503.86 | 6.934 | 6.934 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 21.11 | 21.11 | 0.00870 | 37.71 | 0.00687 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8844.26 | 8844.26 | 226.65 | 0.998 | 0.998 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 21.11 | 21.11 | 0.00855 | 33.48 | 0.00686 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8772.65 | 8772.65 | 224.84 | 0.990 | 0.990 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 21.11 | 21.11 | 0.00855 | 33.16 | 0.00686 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 19771.06 | 19771.06 | 50.77 | 1.656 | 1.656 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00942 | 37.84 | 0.00687 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2699.13 | 2699.13 | 69.17 | 0.305 | 0.305 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 21.11 | 21.11 | 0.00854 | 36.80 | 0.00687 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2675.10 | 2675.10 | 68.56 | 0.302 | 0.302 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00854 | 36.63 | 0.00687 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11852.86 | 11852.86 | 483.19 | 1.338 | 1.338 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21.11 | 21.11 | 0.00861 | 38.10 | 0.00687 | 0.099 | 0.00 |
BANQUET_FLR_6 | 30311.98 | 30311.98 | 91.40 | 2.543 | 2.543 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 23.98 | 0.01034 | 38.10 | 0.00687 | 1.188 | 0.00 |
DINING_FLR_6 | 31752.38 | 31752.38 | 95.74 | 2.664 | 2.664 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 23.98 | 0.01026 | 38.10 | 0.00687 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30714.36 | 30714.36 | 297.32 | 2.580 | 2.580 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01007 | 36.93 | 0.00687 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10414.50 | 10414.50 | 25.27 | 0.872 | 0.872 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00896 | 38.10 | 0.00687 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 23.40 | 0.00281 | -5.20 | 0.00281 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2744.70 | 2744.70 | 40.92 | 0.136 | 0.136 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00762 | -5.20 | 0.00281 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 915.76 | 915.76 | 11.79 | 0.045 | 0.092 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00757 | -5.20 | 0.00281 | 0.092 | 0.00 |
MECH_FLR_1 | 1686.46 | 1686.46 | 10.27 | 0.083 | 0.083 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00746 | -5.20 | 0.00281 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1002.50 | 1002.50 | 10.58 | 0.050 | 0.058 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00747 | -5.20 | 0.00281 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2255.84 | 2255.84 | 28.91 | 0.111 | 0.111 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00745 | -5.20 | 0.00281 | 0.000 | 0.00 |
CAFE_FLR_1 | 6896.33 | 6896.33 | 36.52 | 0.341 | 0.676 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00766 | -5.20 | 0.00281 | 0.676 | 0.00 |
LOBBY_FLR_1 | 16141.54 | 16141.54 | 12.34 | 0.798 | 1.894 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00760 | -5.20 | 0.00281 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 6029.17 | 6029.17 | 154.51 | 0.300 | 0.300 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00760 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 6022.67 | 6022.67 | 154.36 | 0.299 | 0.299 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00760 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 34779.17 | 34779.17 | 1418.18 | 1.729 | 1.729 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00763 | -5.20 | 0.00281 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 34674.39 | 34674.39 | 1413.52 | 1.724 | 1.724 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00763 | -5.20 | 0.00281 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 6016.91 | 6016.91 | 154.19 | 0.299 | 0.299 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00760 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 6010.40 | 6010.40 | 154.04 | 0.299 | 0.299 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00760 | -5.20 | 0.00281 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 9685.16 | 9685.16 | 24.87 | 0.479 | 0.479 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00769 | -5.20 | 0.00281 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1862.67 | 1862.67 | 47.73 | 0.093 | 0.093 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00767 | -5.20 | 0.00281 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1861.86 | 1861.86 | 47.72 | 0.093 | 0.093 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00767 | -5.20 | 0.00281 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8972.20 | 8972.20 | 365.76 | 0.446 | 0.446 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00769 | -5.20 | 0.00281 | 0.099 | 0.00 |
BANQUET_FLR_6 | 6253.82 | 6253.82 | 18.86 | 0.309 | 1.188 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00776 | -5.20 | 0.00281 | 1.188 | 0.00 |
DINING_FLR_6 | 6387.61 | 6387.61 | 19.26 | 0.316 | 1.188 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00776 | -5.20 | 0.00281 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2139.00 | 2139.00 | 20.71 | 0.106 | 0.367 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00684 | -5.20 | 0.00281 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 6593.39 | 6593.39 | 16.00 | 0.326 | 0.326 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00780 | -5.20 | 0.00281 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 24.82 | 24.82 | 7.45 | 7.45 | 24.8182 | 11.7955 | 24.8182 | 0.4753 | 0.3000 |
FLR_3_DOAS | 19.03 | 2.05 | 5.28 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 5743.472 | 5743.472 | 1.254268 | 0.00005025 | 119.770 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5743.47 | 5743.47 | 1.254268 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 0.00 | 0.00 | 5775.75 | 5775.75 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3365.310 | 3365.310 | 0.135644 | 0.00002944 | 91.844 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 3365.31 | 3365.31 | 0.135644 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00762119 | 42.7563 | 2744.70 | 0.00 | 3382.00 | 3382.00 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1531.876 | 1531.876 | 0.134662 | 0.00001340 | 34.630 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 1531.88 | 1531.88 | 0.134662 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00756670 | 42.4531 | 915.76 | 0.00 | 1540.14 | 1540.14 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2082.818 | 2082.818 | 0.086648 | 0.00001822 | 56.157 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 2082.82 | 2082.82 | 0.086648 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00745675 | 41.8436 | 1686.46 | 0.00 | 2093.18 | 2093.18 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1390.235 | 1390.235 | 0.084760 | 0.00001216 | 33.550 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 1390.24 | 1390.24 | 0.084760 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00747111 | 41.9233 | 1002.50 | 0.00 | 1397.49 | 1397.49 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7442.007 | 7442.007 | 1.133886 | 0.00006511 | 158.764 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 7442.01 | 7442.01 | 1.133886 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00744668 | 41.7889 | 2255.84 | 0.00 | 7483.51 | 7483.51 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 11437.506 | 11437.506 | 0.992438 | 0.00010006 | 259.039 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 11437.51 | 11437.51 | 0.992438 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00766378 | 42.9920 | 6896.33 | 0.00 | 11499.18 | 11499.18 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 28849.766 | 28849.766 | 2.777444 | 0.00025239 | 644.229 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 28849.77 | 28849.77 | 2.777444 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00759534 | 42.6119 | 16141.54 | 0.00 | 29006.18 | 29006.18 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 11086.997 | -999.000 | 1.145671 | 0.00039599 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 11087.00 | 10990.34 | 1.145671 | 21.77 | 14.20 | 0.00854347 | 12.80 | 10.82 | 0.00850000 | 36.63 | 0.00686912 | 17.72 | 0.0000 | 21.11 | 0.00854347 | 47.5338 | 10148.75 | 0.00 | 12828.32 | 12266.16 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 6029.050 | 6029.050 | 0.299716 | 0.00005274 | 172.283 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6029.05 | 6029.05 | 0.299716 | 21.11 | 13.15 | 0.00760345 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00760345 | 42.3680 | 6029.17 | 0.00 | 6499.46 | 6499.46 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11003.607 | -999.000 | 1.136965 | 0.00039302 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 11003.61 | 10907.05 | 1.136965 | 21.77 | 14.20 | 0.00854376 | 12.80 | 10.82 | 0.00850000 | 36.63 | 0.00686912 | 17.72 | 0.0000 | 21.11 | 0.00854376 | 47.5353 | 10071.62 | 0.00 | 12731.76 | 12172.99 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 6022.549 | 6022.549 | 0.299392 | 0.00005269 | 172.097 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6022.55 | 6022.55 | 0.299392 | 21.11 | 13.15 | 0.00760309 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00760309 | 42.3660 | 6022.67 | 0.00 | 6492.46 | 6492.46 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 60628.542 | -999.000 | 6.340668 | 0.00216547 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 60628.54 | 60628.54 | 6.340668 | 21.77 | 14.14 | 0.00847163 | 12.80 | 10.79 | 0.00847163 | 38.10 | 0.00687148 | 18.17 | 0.0000 | 21.11 | 0.00847163 | 47.1385 | 56169.92 | 0.00 | 70249.89 | 68127.09 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 34778.842 | 34778.842 | 1.728954 | 0.00030426 | 993.807 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 34778.84 | 34778.84 | 1.728954 | 21.11 | 13.17 | 0.00763330 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00763330 | 42.5314 | 34779.17 | 0.00 | 37492.66 | 37492.66 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 70059.621 | -999.000 | 6.933994 | 0.00250232 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | unknown | 7/21 15:30:00 | 70059.62 | 67277.34 | 6.933994 | 21.77 | 14.34 | 0.00870439 | 12.80 | 10.82 | 0.00850000 | 37.71 | 0.00687086 | 18.05 | 0.0000 | 21.11 | 0.00870439 | 48.4179 | 61420.95 | 0.00 | 80827.64 | 74416.94 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 34674.065 | 34674.065 | 1.723745 | 0.00030334 | 990.814 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 34674.06 | 34674.06 | 1.723745 | 21.11 | 13.17 | 0.00763217 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00763217 | 42.5252 | 34674.39 | 0.00 | 37379.71 | 37379.71 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9676.818 | -999.000 | 0.998411 | 0.00034563 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | unknown | 7/21 10:10:00 | 9676.82 | 9581.64 | 0.998411 | 21.77 | 14.20 | 0.00854910 | 12.80 | 10.82 | 0.00850000 | 33.48 | 0.00686412 | 16.74 | 0.0000 | 21.11 | 0.00854910 | 47.5647 | 8844.26 | 0.00 | 11195.40 | 10690.34 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 6016.787 | 6016.787 | 0.299106 | 0.00005264 | 171.932 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6016.79 | 6016.79 | 0.299106 | 21.11 | 13.15 | 0.00760271 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00760271 | 42.3639 | 6016.91 | 0.00 | 6486.24 | 6486.24 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9599.345 | -999.000 | 0.990326 | 0.00034286 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | 7/21 10:00:00 | 9599.35 | 9504.29 | 0.990326 | 21.77 | 14.20 | 0.00854943 | 12.80 | 10.82 | 0.00850000 | 33.16 | 0.00686360 | 16.64 | 0.0000 | 21.11 | 0.00854943 | 47.5665 | 8772.65 | 0.00 | 11105.69 | 10603.83 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 6010.284 | 6010.284 | 0.298783 | 0.00005258 | 171.747 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6010.28 | 6010.28 | 0.298783 | 21.11 | 13.15 | 0.00760234 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00760234 | 42.3618 | 6010.40 | 0.00 | 6479.23 | 6479.23 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 12868.847 | 12868.847 | 0.695662 | 0.00011258 | 319.686 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 12868.85 | 12868.85 | 0.695662 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00769399 | 43.1582 | 9685.16 | 0.00 | 12935.31 | 12935.31 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2946.581 | -999.000 | 0.304699 | 0.00010524 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | 7/21 16:30:00 | 2946.58 | 2922.40 | 0.304699 | 21.77 | 14.20 | 0.00854089 | 12.80 | 10.82 | 0.00850000 | 36.80 | 0.00686940 | 17.78 | 0.0000 | 21.11 | 0.00854089 | 47.5196 | 2699.13 | 0.00 | 3409.55 | 3262.15 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1862.635 | 1862.635 | 0.092595 | 0.00001630 | 53.223 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1862.63 | 1862.63 | 0.092595 | 21.11 | 13.21 | 0.00767430 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00767430 | 42.7579 | 1862.67 | 0.00 | 2007.97 | 2007.97 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2920.638 | -999.000 | 0.301986 | 0.00010432 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 2920.64 | 2896.46 | 0.301986 | 21.77 | 14.20 | 0.00854126 | 12.80 | 10.82 | 0.00850000 | 36.63 | 0.00686912 | 17.72 | 0.0000 | 21.11 | 0.00854126 | 47.5216 | 2675.10 | 0.00 | 3379.50 | 3233.12 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1861.825 | 1861.825 | 0.092555 | 0.00001629 | 53.200 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1861.83 | 1861.83 | 0.092555 | 21.11 | 13.21 | 0.00767419 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00767419 | 42.7573 | 1861.86 | 0.00 | 2007.09 | 2007.09 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13191.404 | -999.000 | 1.338087 | 0.00047116 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 13191.40 | 12899.49 | 1.338087 | 21.77 | 14.26 | 0.00861185 | 12.80 | 10.82 | 0.00850000 | 38.10 | 0.00687148 | 18.17 | 0.0000 | 21.11 | 0.00861185 | 47.9098 | 11852.86 | 0.00 | 15242.65 | 14339.55 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 8972.061 | 8972.061 | 0.446021 | 0.00007849 | 256.368 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 8972.06 | 8972.06 | 0.446021 | 21.11 | 13.22 | 0.00768778 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00768778 | 42.8318 | 8972.20 | 0.00 | 9672.12 | 9672.12 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14225.724 | 14225.724 | 1.741772 | 0.00012445 | 309.273 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 14225.72 | 14225.72 | 1.741772 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00775765 | 43.5112 | 6253.82 | 0.00 | 14304.61 | 14304.61 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14360.275 | 14360.275 | 1.741941 | 0.00012563 | 312.483 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 14360.28 | 14360.28 | 1.741941 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00776249 | 43.5381 | 6387.61 | 0.00 | 14439.88 | 14439.88 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 5673.760 | 5673.760 | 0.774056 | 0.00004964 | 122.132 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 5673.76 | 5673.76 | 0.774056 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00684144 | 38.4343 | 2139.00 | 0.00 | 5705.31 | 5705.31 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 8084.942 | 8084.942 | 0.325861 | 0.00007073 | 220.654 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 8084.94 | 8084.94 | 0.325861 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00779698 | 43.7290 | 6593.39 | 0.00 | 8125.04 | 8125.04 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 526849.156 | -999.000 | 24.818243 | 0.01881783 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 526849.16 | 526849.14 | 24.818243 | 30.62 | 16.97 | 0.00833878 | 10.70 | 9.81 | 0.00833878 | 38.10 | 0.00687148 | 18.17 | 46.9875 | 23.99 | 0.00960458 | 44.7822 | 296036.68 | 0.00 | 582197.28 | 538238.13 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 171111.744 | 171111.744 | 7.445473 | 0.00149696 | 2904.798 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 171111.74 | 171111.74 | 7.445473 | -5.20 | -5.20 | 0.00280840 | 16.70 | 11.86 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 156.6248 | 21.41 | 0.00684713 | 37.4982 | 62392.14 | 0.00 | 155828.90 | 155828.90 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 57348.723 | -999.000 | 2.051317 | 0.00204836 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 57348.72 | 57348.72 | 2.051317 | 38.10 | 18.17 | 0.00687148 | 11.79 | 8.78 | 0.00687148 | 38.10 | 0.00687148 | 18.17 | 99.9965 | 21.11 | 0.00859321 | 47.8069 | 168280.60 | 0.00 | 51614.51 | 51614.51 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 14143.003 | 14143.003 | 0.615395 | 0.00012373 | 240.092 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 14143.00 | 14143.00 | 0.615395 | -5.20 | -5.20 | 0.00280840 | 16.70 | 11.86 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 333.3216 | 21.11 | 0.00763305 | 42.5301 | 106229.44 | 0.00 | 12879.82 | 12879.82 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 5743.472 | 5743.472 | 1.254268 | 0.00005025 | 119.770 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 1.3781 | 1.405855 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5743.47 | 5743.47 | 1.0000 | 1.30987141 | 1.254268 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05024127 | 60.00 | 32.22 | 27.78 | 0.000 | 5743.47 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 0.00 | 0.00 | 5775.75 | 5775.75 | 1.30987141 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3365.310 | 3365.310 | 0.135644 | 0.00002944 | 91.844 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 0.8075 | 0.823742 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 3365.31 | 3365.31 | 1.0000 | 0.14165719 | 0.135644 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.02943820 | 60.00 | 32.22 | 27.78 | 0.000 | 3365.31 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00762119 | 21.00 | 0.00762119 | 42.7563 | 2744.70 | 0.00 | 3382.00 | 3382.00 | 0.14165719 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60809.3 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1531.876 | 1531.876 | 0.134662 | 0.00001340 | 34.630 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 0.3676 | 0.374964 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 1531.88 | 1531.88 | 1.0000 | 0.14063138 | 0.134662 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01340016 | 60.00 | 32.22 | 27.78 | 0.000 | 1531.88 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00756670 | 21.00 | 0.00756670 | 42.4531 | 915.76 | 0.00 | 1540.14 | 1540.14 | 0.14063138 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.34 | 17.13 | 0.00800000 | 47886.4 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2082.818 | 2082.818 | 0.086648 | 0.00001822 | 56.157 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 0.4998 | 0.509821 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 2082.82 | 2082.82 | 1.0000 | 0.09048907 | 0.086648 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01821954 | 60.00 | 32.22 | 27.78 | 0.000 | 2082.82 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00745675 | 21.00 | 0.00745675 | 41.8436 | 1686.46 | 0.00 | 2093.18 | 2093.18 | 0.09048907 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 39.28 | 20.97 | 0.00800000 | 60066.6 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1390.235 | 1390.235 | 0.084760 | 0.00001216 | 33.550 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 0.3336 | 0.340294 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 1390.24 | 1390.24 | 1.0000 | 0.08851754 | 0.084760 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01216114 | 60.00 | 32.22 | 27.78 | 0.000 | 1390.24 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00747111 | 21.00 | 0.00747111 | 41.9233 | 1002.50 | 0.00 | 1397.49 | 1397.49 | 0.08851754 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.08 | 18.72 | 0.00800000 | 52722.4 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7442.007 | 7442.007 | 1.133886 | 0.00006511 | 158.764 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 1.7857 | 1.821613 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 7442.01 | 7442.01 | 1.0000 | 1.18415307 | 1.133886 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.06509928 | 60.00 | 32.22 | 27.78 | 0.000 | 7442.01 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00744668 | 21.00 | 0.00744668 | 41.7889 | 2255.84 | 0.00 | 7483.51 | 7483.51 | 1.18415307 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.80 | 15.52 | 0.00800000 | 43254.4 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11437.506 | 11437.506 | 0.992438 | 0.00010006 | 259.039 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 2.7444 | 2.799609 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 11437.51 | 11437.51 | 1.0000 | 1.03643433 | 0.992438 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.10005008 | 60.00 | 32.22 | 27.78 | 0.000 | 11437.51 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00766378 | 21.00 | 0.00766378 | 42.9920 | 6896.33 | 0.00 | 11499.18 | 11499.18 | 1.03643433 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.48 | 17.18 | 0.00800000 | 48029.7 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 28849.766 | 28849.766 | 2.777444 | 0.00025239 | 644.229 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 6.9224 | 7.061686 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 28849.77 | 28849.77 | 1.0000 | 2.90057288 | 2.777444 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.25236460 | 60.00 | 32.22 | 27.78 | 0.000 | 28849.77 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00759534 | 21.00 | 0.00759534 | 42.6119 | 16141.54 | 0.00 | 29006.18 | 29006.18 | 2.90057288 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.41 | 16.81 | 0.00800000 | 46934.9 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11086.997 | -999.000 | 1.145671 | 0.00039599 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7219 | 1004.8586 | 1.0443 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.145671 | 1.19646062 | 4197.9300 | 999.8980 | 27.68937556 | 13.37 | 6.70 | 6.67 | 775307.86 | 1.4300 | 1.429985 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 11087.00 | 10990.34 | 1.0000 | 1.19646062 | 1.145671 | 21.77 | 14.20 | 0.00854347 | 43588.7 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.39595404 | 6.70 | 13.37 | 6.67 | 0.000 | 11087.00 | 36.63 | 0.00686912 | 17.72 | 0.00000000 | 0.0000 | 21.11 | 0.00854347 | 21.11 | 0.00854347 | 47.5338 | 10148.75 | 0.00 | 12828.32 | 12266.16 | 1.19646062 | 21.77 | 15.62 | 0.00854347 | 43588.7 | 11.73 | 11.51 | 0.00835722 | 32866.8 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6029.050 | 6029.050 | 0.299716 | 0.00005274 | 172.283 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.145671 | 1.19646062 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 1.4466 | 1.475757 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6029.05 | 6029.05 | 1.0000 | 0.31300251 | 0.299716 | 21.11 | 13.15 | 0.00760345 | 40526.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05273938 | 60.00 | 32.22 | 27.78 | 0.000 | 6029.05 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00760345 | 21.11 | 0.00760345 | 42.3680 | 6029.17 | 0.00 | 6499.46 | 6499.46 | 0.31300251 | 16.60 | 12.76 | 0.00760345 | 35930.8 | 36.98 | 19.97 | 0.00760345 | 56695.6 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11003.607 | -999.000 | 1.136965 | 0.00039302 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7224 | 1004.8586 | 1.0443 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.136965 | 1.18736832 | 4197.9300 | 999.8980 | 27.68937556 | 13.37 | 6.70 | 6.67 | 775307.86 | 1.4193 | 1.419230 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 11003.61 | 10907.05 | 1.0000 | 1.18736832 | 1.136965 | 21.77 | 14.20 | 0.00854376 | 43589.4 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.39297591 | 6.70 | 13.37 | 6.67 | 0.000 | 11003.61 | 36.63 | 0.00686912 | 17.72 | 0.00000000 | 0.0000 | 21.11 | 0.00854376 | 21.11 | 0.00854376 | 47.5353 | 10071.62 | 0.00 | 12731.76 | 12172.99 | 1.18736832 | 21.77 | 15.62 | 0.00854376 | 43589.4 | 11.73 | 11.51 | 0.00835721 | 32866.7 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6022.549 | 6022.549 | 0.299392 | 0.00005269 | 172.097 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.136965 | 1.18736832 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 1.4451 | 1.474166 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6022.55 | 6022.55 | 1.0000 | 0.31266499 | 0.299392 | 21.11 | 13.15 | 0.00760309 | 40525.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05268251 | 60.00 | 32.22 | 27.78 | 0.000 | 6022.55 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00760309 | 21.11 | 0.00760309 | 42.3660 | 6022.67 | 0.00 | 6492.46 | 6492.46 | 0.31266499 | 16.60 | 12.76 | 0.00760309 | 35929.8 | 36.98 | 19.97 | 0.00760309 | 56694.7 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 60628.542 | -999.000 | 6.340668 | 0.00216547 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5883 | 1004.8586 | 1.0443 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.340668 | 6.62176045 | 4197.9300 | 999.8980 | 27.68937556 | 13.37 | 6.70 | 6.67 | 775307.86 | 7.8199 | 7.819785 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 60628.54 | 60628.54 | 1.0000 | 6.62176045 | 6.340668 | 21.77 | 14.14 | 0.00847163 | 43406.5 | 12.80 | 10.79 | 0.00847163 | 34250.6 | 2.16524971 | 6.70 | 13.37 | 6.67 | 0.000 | 60628.54 | 38.10 | 0.00687148 | 18.17 | 0.00000000 | 0.0000 | 21.11 | 0.00847163 | 21.11 | 0.00847163 | 47.1385 | 56169.92 | 0.00 | 70249.89 | 68127.09 | 6.62176045 | 21.77 | 15.56 | 0.00847163 | 43406.5 | 11.69 | 11.48 | 0.00834455 | 32797.6 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34778.842 | 34778.842 | 1.728954 | 0.00030426 | 993.807 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.340668 | 6.62176045 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 8.3450 | 8.512972 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 34778.84 | 34778.84 | 1.0000 | 1.80560148 | 1.728954 | 21.11 | 13.17 | 0.00763330 | 40602.9 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.30422944 | 60.00 | 32.22 | 27.78 | 0.000 | 34778.84 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00763330 | 21.11 | 0.00763330 | 42.5314 | 34779.17 | 0.00 | 37492.66 | 37492.66 | 1.80560148 | 16.60 | 12.79 | 0.00763330 | 36006.3 | 36.98 | 20.00 | 0.00763330 | 56771.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 70059.621 | -999.000 | 6.933994 | 0.00250232 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0210 | 1004.8586 | 1.0443 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.933994 | 7.24138990 | 4197.9300 | 999.8980 | 27.68937556 | 13.37 | 6.70 | 6.67 | 775307.86 | 9.0364 | 9.036193 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | unknown | unknown | unknown | 7/21 15:30:00 | Sensible | 70059.62 | 67277.34 | 1.0000 | 7.24138990 | 6.933994 | 21.77 | 14.34 | 0.00870439 | 43997.1 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 2.50206534 | 6.70 | 13.37 | 6.67 | 0.000 | 70059.62 | 37.71 | 0.00687086 | 18.05 | 0.00000000 | 0.0000 | 21.11 | 0.00870439 | 21.11 | 0.00870439 | 48.4179 | 61420.95 | 0.00 | 80827.64 | 74416.94 | 7.24138990 | 21.77 | 15.77 | 0.00870439 | 43997.1 | 11.71 | 11.50 | 0.00835346 | 32835.2 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34674.065 | 34674.065 | 1.723745 | 0.00030334 | 990.814 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.933994 | 7.24138990 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 8.3199 | 8.487325 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 34674.06 | 34674.06 | 1.0000 | 1.80016181 | 1.723745 | 21.11 | 13.17 | 0.00763217 | 40600.0 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.30331290 | 60.00 | 32.22 | 27.78 | 0.000 | 34674.06 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00763217 | 21.11 | 0.00763217 | 42.5252 | 34674.39 | 0.00 | 37379.71 | 37379.71 | 1.80016181 | 16.60 | 12.79 | 0.00763217 | 36003.5 | 36.98 | 19.99 | 0.00763217 | 56768.1 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9676.818 | -999.000 | 0.998411 | 0.00034563 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7323 | 1004.8586 | 1.0443 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.998411 | 1.04267192 | 4197.9300 | 999.8980 | 27.68937556 | 13.37 | 6.70 | 6.67 | 775307.86 | 1.2481 | 1.248103 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | unknown | unknown | unknown | 7/21 10:10:00 | Sensible | 9676.82 | 9581.64 | 1.0000 | 1.04267192 | 0.998411 | 21.77 | 14.20 | 0.00854910 | 43603.0 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.34559181 | 6.70 | 13.37 | 6.67 | 0.000 | 9676.82 | 33.48 | 0.00686412 | 16.74 | 0.00000000 | 0.0000 | 21.11 | 0.00854910 | 21.11 | 0.00854910 | 47.5647 | 8844.26 | 0.00 | 11195.40 | 10690.34 | 1.04267192 | 21.77 | 15.63 | 0.00854910 | 43603.0 | 11.73 | 11.51 | 0.00835709 | 32865.8 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6016.787 | 6016.787 | 0.299106 | 0.00005264 | 171.932 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.998411 | 1.04267192 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 1.4437 | 1.472756 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6016.79 | 6016.79 | 1.0000 | 0.31236586 | 0.299106 | 21.11 | 13.15 | 0.00760271 | 40524.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05263211 | 60.00 | 32.22 | 27.78 | 0.000 | 6016.79 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00760271 | 21.11 | 0.00760271 | 42.3639 | 6016.91 | 0.00 | 6486.24 | 6486.24 | 0.31236586 | 16.60 | 12.76 | 0.00760271 | 35928.9 | 36.98 | 19.97 | 0.00760271 | 56693.8 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9599.345 | -999.000 | 0.990326 | 0.00034286 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7330 | 1004.8586 | 1.0443 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.990326 | 1.03422908 | 4197.9300 | 999.8980 | 27.68937556 | 13.37 | 6.70 | 6.67 | 775307.86 | 1.2381 | 1.238110 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | unknown | unknown | 7/21 10:00:00 | Sensible | 9599.35 | 9504.29 | 1.0000 | 1.03422908 | 0.990326 | 21.77 | 14.20 | 0.00854943 | 43603.8 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.34282498 | 6.70 | 13.37 | 6.67 | 0.000 | 9599.35 | 33.16 | 0.00686360 | 16.64 | 0.00000000 | 0.0000 | 21.11 | 0.00854943 | 21.11 | 0.00854943 | 47.5665 | 8772.65 | 0.00 | 11105.69 | 10603.83 | 1.03422908 | 21.77 | 15.63 | 0.00854943 | 43603.8 | 11.73 | 11.51 | 0.00835708 | 32865.7 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6010.284 | 6010.284 | 0.298783 | 0.00005258 | 171.747 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.990326 | 1.03422908 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 1.4421 | 1.471164 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6010.28 | 6010.28 | 1.0000 | 0.31202825 | 0.298783 | 21.11 | 13.15 | 0.00760234 | 40523.9 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05257522 | 60.00 | 32.22 | 27.78 | 0.000 | 6010.28 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00760234 | 21.11 | 0.00760234 | 42.3618 | 6010.40 | 0.00 | 6479.23 | 6479.23 | 0.31202825 | 16.60 | 12.76 | 0.00760234 | 35927.9 | 36.98 | 19.97 | 0.00760234 | 56692.8 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12868.847 | 12868.847 | 0.695662 | 0.00011258 | 319.686 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 3.0878 | 3.149965 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 12868.85 | 12868.85 | 1.0000 | 0.72650191 | 0.695662 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.11257080 | 60.00 | 32.22 | 27.78 | 0.000 | 12868.85 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00769399 | 21.00 | 0.00769399 | 43.1582 | 9685.16 | 0.00 | 12935.31 | 12935.31 | 0.72650191 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.06 | 19.36 | 0.00800000 | 54739.7 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2946.581 | -999.000 | 0.304699 | 0.00010524 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7171 | 1004.8586 | 1.0443 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.304699 | 0.31820693 | 4197.9300 | 999.8980 | 27.68937556 | 13.37 | 6.70 | 6.67 | 775307.86 | 0.3801 | 0.380046 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | unknown | unknown | 7/21 16:30:00 | Sensible | 2946.58 | 2922.40 | 1.0000 | 0.31820693 | 0.304699 | 21.77 | 14.20 | 0.00854089 | 43582.1 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.10523233 | 6.70 | 13.37 | 6.67 | 0.000 | 2946.58 | 36.80 | 0.00686940 | 17.78 | 0.00000000 | 0.0000 | 21.11 | 0.00854089 | 21.11 | 0.00854089 | 47.5196 | 2699.13 | 0.00 | 3409.55 | 3262.15 | 0.31820693 | 21.77 | 15.62 | 0.00854089 | 43582.1 | 11.73 | 11.51 | 0.00835728 | 32867.3 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1862.635 | 1862.635 | 0.092595 | 0.00001630 | 53.223 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.304699 | 0.31820693 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 0.4469 | 0.455925 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1862.63 | 1862.63 | 1.0000 | 0.09670008 | 0.092595 | 21.11 | 13.21 | 0.00767430 | 40706.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01629348 | 60.00 | 32.22 | 27.78 | 0.000 | 1862.63 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00767430 | 21.11 | 0.00767430 | 42.7579 | 1862.67 | 0.00 | 2007.97 | 2007.97 | 0.09670008 | 16.60 | 12.83 | 0.00767430 | 36110.1 | 36.98 | 20.03 | 0.00767430 | 56875.0 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2920.638 | -999.000 | 0.301986 | 0.00010432 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7178 | 1004.8586 | 1.0443 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.301986 | 0.31537365 | 4197.9300 | 999.8980 | 27.68937556 | 13.37 | 6.70 | 6.67 | 775307.86 | 0.3767 | 0.376700 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 2920.64 | 2896.46 | 1.0000 | 0.31537365 | 0.301986 | 21.77 | 14.20 | 0.00854126 | 43583.1 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.10430583 | 6.70 | 13.37 | 6.67 | 0.000 | 2920.64 | 36.63 | 0.00686912 | 17.72 | 0.00000000 | 0.0000 | 21.11 | 0.00854126 | 21.11 | 0.00854126 | 47.5216 | 2675.10 | 0.00 | 3379.50 | 3233.12 | 0.31537365 | 21.77 | 15.62 | 0.00854126 | 43583.1 | 11.73 | 11.51 | 0.00835727 | 32867.2 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1861.825 | 1861.825 | 0.092555 | 0.00001629 | 53.200 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.301986 | 0.31537365 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 0.4467 | 0.455727 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1861.83 | 1861.83 | 1.0000 | 0.09665804 | 0.092555 | 21.11 | 13.21 | 0.00767419 | 40706.4 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01628640 | 60.00 | 32.22 | 27.78 | 0.000 | 1861.83 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00767419 | 21.11 | 0.00767419 | 42.7573 | 1861.86 | 0.00 | 2007.09 | 2007.09 | 0.09665804 | 16.60 | 12.83 | 0.00767419 | 36109.8 | 36.98 | 20.03 | 0.00767419 | 56874.7 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13191.404 | -999.000 | 1.338087 | 0.00047116 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8490 | 1004.8586 | 1.0443 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.338087 | 1.39740682 | 4197.9300 | 999.8980 | 27.68937556 | 13.37 | 6.70 | 6.67 | 775307.86 | 1.7014 | 1.701409 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 13191.40 | 12899.49 | 1.0000 | 1.39740682 | 1.338087 | 21.77 | 14.26 | 0.00861185 | 43762.1 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.47110953 | 6.70 | 13.37 | 6.67 | 0.000 | 13191.40 | 38.10 | 0.00687148 | 18.17 | 0.00000000 | 0.0000 | 21.11 | 0.00861185 | 21.11 | 0.00861185 | 47.9098 | 11852.86 | 0.00 | 15242.65 | 14339.55 | 1.39740682 | 21.77 | 15.68 | 0.00861185 | 43762.1 | 11.72 | 11.50 | 0.00835567 | 32854.3 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8972.061 | 8972.061 | 0.446021 | 0.00007849 | 256.368 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.338087 | 1.39740682 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 2.1528 | 2.196131 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 8972.06 | 8972.06 | 1.0000 | 0.46579419 | 0.446021 | 21.11 | 13.22 | 0.00768778 | 40741.0 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.07848350 | 60.00 | 32.22 | 27.78 | 0.000 | 8972.06 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00768778 | 21.11 | 0.00768778 | 42.8318 | 8972.20 | 0.00 | 9672.12 | 9672.12 | 0.46579419 | 16.60 | 12.85 | 0.00768778 | 36144.3 | 36.98 | 20.04 | 0.00768778 | 56909.1 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14225.724 | 14225.724 | 1.741772 | 0.00012445 | 309.273 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 3.4134 | 3.482094 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 14225.72 | 14225.72 | 1.0000 | 1.81898792 | 1.741772 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.12444014 | 60.00 | 32.22 | 27.78 | 0.000 | 14225.72 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00775765 | 21.00 | 0.00775765 | 43.5112 | 6253.82 | 0.00 | 14304.61 | 14304.61 | 1.81898792 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.31 | 16.07 | 0.00800000 | 44798.8 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14360.275 | 14360.275 | 1.741941 | 0.00012563 | 312.483 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 3.4457 | 3.515028 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 14360.28 | 14360.28 | 1.0000 | 1.81916374 | 1.741941 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.12561714 | 60.00 | 32.22 | 27.78 | 0.000 | 14360.28 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00776249 | 21.00 | 0.00776249 | 43.5381 | 6387.61 | 0.00 | 14439.88 | 14439.88 | 1.81916374 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.38 | 16.09 | 0.00800000 | 44872.4 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5673.760 | 5673.760 | 0.774056 | 0.00004964 | 122.132 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 1.3614 | 1.388791 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 5673.76 | 5673.76 | 1.0000 | 0.80837097 | 0.774056 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.04963146 | 60.00 | 32.22 | 27.78 | 0.000 | 5673.76 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.52 | 0.00684144 | 21.00 | 0.00684144 | 38.4343 | 2139.00 | 0.00 | 5705.31 | 5705.31 | 0.80837097 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.52 | 15.78 | 0.00800000 | 43992.5 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8084.942 | 8084.942 | 0.325861 | 0.00007073 | 220.654 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 1.9399 | 1.978987 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 8084.94 | 8084.94 | 1.0000 | 0.34030704 | 0.325861 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.07072339 | 60.00 | 32.22 | 27.78 | 0.000 | 8084.94 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00779698 | 21.00 | 0.00779698 | 43.7290 | 6593.39 | 0.00 | 8125.04 | 8125.04 | 0.34030704 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60810.3 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 526849.156 | -999.000 | 24.818243 | 0.01881783 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3414 | 1004.8586 | 1.0443 | VAV WITH REHEAT FAN | Fan:VariableVolume | 24.818243 | 25.91847822 | 4197.9300 | 999.8980 | 27.68937556 | 13.37 | 6.70 | 6.67 | 775307.86 | 67.9535 | 67.953542 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | Sensible | 526849.16 | 526849.14 | 1.0000 | 25.91847822 | 24.818243 | 30.62 | 16.97 | 0.00833878 | 52096.8 | 10.70 | 9.81 | 0.00833878 | 31769.6 | 18.81591154 | 6.70 | 13.37 | 6.67 | 55608.712 | 471240.44 | 38.10 | 0.00687148 | 18.17 | 11.66146000 | 46.9875 | 23.99 | 0.00963932 | 23.99 | 0.00960458 | 44.7822 | 296036.68 | 0.00 | 582197.28 | 538238.13 | 25.91847822 | 30.62 | 18.51 | 0.00833878 | 52096.8 | 10.27 | 10.16 | 0.00766575 | 29634.2 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 171111.744 | 171111.744 | 7.445473 | 0.00149696 | 2904.798 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | VAV WITH REHEAT FAN | Fan:VariableVolume | 24.818243 | 25.91847822 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 41.0575 | 41.883782 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 171111.74 | 171111.74 | 1.0000 | 7.77554347 | 7.445473 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 1.49680748 | 60.00 | 32.22 | 27.78 | 0.000 | 171111.74 | -5.20 | 0.00280840 | -5.20 | 11.66146000 | 156.6248 | 18.57 | 0.00707986 | 21.41 | 0.00684713 | 37.4982 | 62392.14 | 0.00 | 155828.90 | 155828.90 | 7.77554347 | 2.80 | 0.24 | 0.00280840 | 9851.8 | 22.64 | 10.36 | 0.00280840 | 29892.7 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 57348.723 | -999.000 | 2.051317 | 0.00204836 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.6137 | 1004.8586 | 1.0443 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.14218037 | 4197.9300 | 999.8980 | 27.68937556 | 13.37 | 6.70 | 6.67 | 775307.86 | 7.3969 | 7.396897 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 57348.72 | 57348.72 | 1.0000 | 2.14225568 | 2.051317 | 38.10 | 18.17 | 0.00687148 | 55956.2 | 11.79 | 8.78 | 0.00687148 | 29186.0 | 2.04815455 | 6.70 | 13.37 | 6.67 | 2195.006 | 55153.72 | 38.10 | 0.00687148 | 18.17 | 2.05124512 | 99.9965 | 21.11 | 0.00858477 | 21.11 | 0.00859321 | 47.8069 | 168280.60 | 0.00 | 51614.51 | 51614.51 | 2.14225568 | 38.10 | 19.77 | 0.00687148 | 55956.2 | 14.42 | 11.12 | 0.00687148 | 31862.7 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 14143.003 | 14143.003 | 0.615395 | 0.00012373 | 240.092 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.14218037 | 4197.9300 | 999.8980 | 3.57371615 | 54.44 | 82.22 | 27.78 | 416761.40 | 3.3935 | 3.461846 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 14143.00 | 14143.00 | 1.0000 | 0.64267671 | 0.615395 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 0.12371654 | 60.00 | 32.22 | 27.78 | 0.000 | 14143.00 | -5.20 | 0.00280840 | -5.20 | 2.05124512 | 333.3216 | 21.11 | 0.00763208 | 21.11 | 0.00763305 | 42.5301 | 106229.44 | 0.00 | 12879.82 | 12879.82 | 0.64267671 | 2.80 | 0.24 | 0.00280840 | 9851.8 | 22.64 | 10.36 | 0.00280840 | 29892.7 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 11.66 | 24.82 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2200.33 | 5889.00 | 907.67 |
RETAIL_1_FLR_1 | 3648.67 | 4596.67 | 1000.83 |
RETAIL_2_FLR_1 | 2851.33 | 5599.33 | 1019.50 |
MECH_FLR_1 | 2452.00 | 5797.67 | 522.17 |
STORAGE_FLR_1 | 946.00 | 7592.33 | 666.83 |
LAUNDRY_FLR_1 | 8721.17 | 4527.83 | 4527.50 |
CAFE_FLR_1 | 3388.17 | 5749.67 | 1541.00 |
LOBBY_FLR_1 | 3233.33 | 5607.50 | 1554.17 |
ROOM_1_FLR_3 | 874.67 | 8077.50 | 733.00 |
ROOM_2_FLR_3 | 1680.17 | 8210.50 | 1593.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1346.50 | 8760.00 | 1346.50 |
ROOM_5_FLR_3 | 742.17 | 7935.17 | 709.17 |
ROOM_6_FLR_3 | 1555.50 | 8049.83 | 1522.00 |
CORRIDOR_FLR_3 | 2418.00 | 6698.50 | 1279.67 |
ROOM_1_FLR_6 | 1821.50 | 7989.83 | 1561.67 |
ROOM_2_FLR_6 | 2724.50 | 8111.00 | 2535.17 |
ROOM_3_MULT9_FLR_6 | 494.83 | 8099.67 | 420.83 |
BANQUET_FLR_6 | 3550.33 | 5463.67 | 1552.00 |
DINING_FLR_6 | 4056.33 | 4479.33 | 1535.33 |
KITCHEN_FLR_6 | 8748.50 | 6708.00 | 6708.00 |
CORRIDOR_FLR_6 | 2800.50 | 5698.17 | 867.50 |
Facility | 8759.67 | 8760.00 | 7930.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 123.50 | 0.00 | 123.50 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 8.83 | 0.00 | 8.83 |
ROOM_2_FLR_3 | 0.00 | 6.17 | 0.00 | 6.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 2.17 | 0.00 | 2.17 |
ROOM_5_FLR_3 | 0.00 | 4.00 | 0.00 | 4.00 |
ROOM_6_FLR_3 | 0.00 | 3.17 | 0.00 | 3.17 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 13.17 | 0.00 | 13.17 |
ROOM_2_FLR_6 | 0.00 | 10.50 | 0.00 | 10.50 |
ROOM_3_MULT9_FLR_6 | 0.00 | 9.17 | 0.00 | 9.17 |
BANQUET_FLR_6 | 0.00 | 3.83 | 0.00 | 3.83 |
DINING_FLR_6 | 0.00 | 8.50 | 0.00 | 8.50 |
KITCHEN_FLR_6 | 0.00 | 151.83 | 0.00 | 151.83 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 193.17 | 0.00 | 193.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 106.50 | 4826.41 | 0.981 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.26 | 10.83 | 265.76 | 1.862 | 0.135 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.25 | 12.54 | 307.76 | 1.500 | 0.045 | 0.000 | 0.000 |
MECH_FLR_1 | 1.53 | 2.65 | 650.80 | 0.515 | 0.050 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.717 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 20.641 | 0.145 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.31 | 142.30 | 748.35 | 4.282 | 0.106 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.35 | 422.44 | 5183.56 | 1.836 | 0.044 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.175 | 0.000 | 0.055 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.472 | 0.175 | 0.000 | 0.055 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.536 | 0.077 | 0.000 | 0.087 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.175 | 0.000 | 0.055 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.472 | 0.175 | 0.000 | 0.055 |
CORRIDOR_FLR_3 | 12.12 | 20.96 | 1186.91 | 0.497 | 0.021 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.473 | 0.175 | 0.000 | 0.066 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.472 | 0.175 | 0.000 | 0.065 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.537 | 0.142 | 0.000 | 0.104 |
BANQUET_FLR_6 | 144.55 | 249.90 | 1010.89 | 5.686 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 144.55 | 249.90 | 1010.89 | 5.808 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.86 | 22.24 | 314.87 | 21.601 | 0.146 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.83 | 22.18 | 1256.16 | 0.841 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 106.50 | 4826.41 | 0.497 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.26 | 10.83 | 265.76 | 0.806 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.25 | 12.54 | 307.76 | 0.820 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.53 | 2.65 | 650.80 | 0.245 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.413 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 7.058 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.31 | 142.30 | 748.35 | 2.505 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.35 | 422.44 | 5183.56 | 1.025 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.461 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.459 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.523 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.461 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.460 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.12 | 20.96 | 1186.91 | 0.269 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.460 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.458 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.523 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.55 | 249.90 | 1010.89 | 3.300 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.55 | 249.90 | 1010.89 | 3.301 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.86 | 22.24 | 314.87 | 4.726 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.83 | 22.18 | 1256.16 | 0.382 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.60 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.26 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.25 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.53 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.86 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.31 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.35 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.12 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.55 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.55 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.86 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.83 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 870.81 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 40677987.43 | 0.00 | 40677987.43 | 0.00 | 40677987.43 | 26946214.98 | 209.25 | 27.83 | 8522.92 | 0.00 |
RETAIL_1_FLR_1 | 4254374.38 | 0.00 | 4254374.38 | 309826.10 | 4564200.48 | 2498216.28 | 75.88 | 56.44 | 8627.69 | 0.00 |
RETAIL_2_FLR_1 | 3967683.30 | 0.00 | 3967683.30 | 119593.27 | 4087276.57 | 2892943.94 | 64.00 | 50.66 | 8645.34 | 0.00 |
MECH_FLR_1 | 2883470.03 | 0.00 | 2883470.03 | 282647.43 | 3166117.47 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 2327082.39 | 0.00 | 2327082.39 | 163072.00 | 2490154.39 | 1821682.01 | 585.42 | 99.03 | 8075.56 | 0.00 |
LAUNDRY_FLR_1 | 54840329.47 | 0.00 | 54840329.47 | 385940.64 | 55226270.11 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 27569660.38 | 0.00 | 27569660.38 | 684888.14 | 28254548.51 | 21330615.53 | 472.85 | 117.75 | 8169.40 | 0.00 |
LOBBY_FLR_1 | 81682800.63 | 0.00 | 81682800.63 | 1956881.84 | 83639682.47 | 59728886.00 | 54.25 | 47.37 | 8658.37 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 56800.18 | 2003675.80 | 179831.92 | 2183507.72 | 1946875.62 | 0.00 | 7863.83 | 896.17 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 56337.77 | 2002985.28 | 179818.20 | 2182803.48 | 1946647.51 | 0.00 | 7863.83 | 896.17 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 61063.43 | 26458950.71 | 50175.12 | 26509125.83 | 26397887.27 | 0.00 | 7930.17 | 829.83 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 56072.63 | 26461178.36 | 50188.84 | 26511367.20 | 26405105.73 | 0.00 | 7959.51 | 800.49 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 57030.87 | 2003906.49 | 179831.92 | 2183738.41 | 1946875.62 | 0.00 | 7864.00 | 896.00 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 56558.84 | 2003206.36 | 179818.20 | 2183024.56 | 1946647.51 | 0.00 | 7864.00 | 896.00 | 0.00 |
CORRIDOR_FLR_3 | 20284182.03 | 0.00 | 20284182.03 | 217452.98 | 20501635.01 | 14972100.18 | 90.22 | 62.39 | 8607.39 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 67420.74 | 554139.64 | 179868.73 | 734008.37 | 486718.90 | 0.00 | 7860.33 | 899.67 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 66857.72 | 553519.60 | 179855.01 | 733374.60 | 486661.88 | 0.00 | 7860.33 | 899.67 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 67461.92 | 3194382.33 | 92027.14 | 3286409.47 | 3126920.42 | 0.00 | 7860.42 | 899.58 | 0.00 |
BANQUET_FLR_6 | 49405738.39 | 0.00 | 49405738.39 | 439194.23 | 49844932.62 | 37458366.31 | 184.78 | 105.11 | 8470.11 | 0.00 |
DINING_FLR_6 | 50418380.07 | 0.00 | 50418380.07 | 439194.23 | 50857574.30 | 37458366.31 | 57.47 | 70.00 | 8632.53 | 0.00 |
KITCHEN_FLR_6 | 58325608.78 | 0.00 | 58325608.78 | 393180.66 | 58718789.45 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 9082595.47 | 0.00 | 9082595.47 | 384823.29 | 9467418.76 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.45E+10 | 10550687.37 | 0.46E+10 | 18121884.23 | 0.46E+10 | 0.43E+10 | 589.53 | 7999.79 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.2899 | 0.0000 | 1.2899 | 0.0000 | 1.2899 | 0.8545 | 209.25 | 27.83 | 8522.92 |
RETAIL_1_FLR_1 | 0.1349 | 0.0000 | 0.1349 | 0.0098 | 0.1447 | 0.0792 | 75.88 | 56.44 | 8627.69 |
RETAIL_2_FLR_1 | 0.1258 | 0.0000 | 0.1258 | 0.0038 | 0.1296 | 0.0917 | 64.00 | 50.66 | 8645.34 |
MECH_FLR_1 | 0.0914 | 0.0000 | 0.0914 | 0.0090 | 0.1004 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0738 | 0.0000 | 0.0738 | 0.0052 | 0.0790 | 0.0578 | 585.42 | 99.03 | 8075.56 |
LAUNDRY_FLR_1 | 1.7390 | 0.0000 | 1.7390 | 0.0122 | 1.7512 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.8742 | 0.0000 | 0.8742 | 0.0217 | 0.8959 | 0.6764 | 472.85 | 117.75 | 8169.40 |
LOBBY_FLR_1 | 2.5901 | 0.0000 | 2.5901 | 0.0621 | 2.6522 | 1.8940 | 54.25 | 47.37 | 8658.37 |
ROOM_1_FLR_3 | 0.0617 | 0.0018 | 0.0635 | 0.0057 | 0.0692 | 0.0617 | 0.00 | 7863.83 | 896.17 |
ROOM_2_FLR_3 | 0.0617 | 0.0018 | 0.0635 | 0.0057 | 0.0692 | 0.0617 | 0.00 | 7863.83 | 896.17 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0018 | 0.8391 | 0.0016 | 0.8407 | 0.8373 | 0.00 | 7959.51 | 800.49 |
ROOM_5_FLR_3 | 0.0617 | 0.0018 | 0.0635 | 0.0057 | 0.0692 | 0.0617 | 0.00 | 7864.00 | 896.00 |
ROOM_6_FLR_3 | 0.0617 | 0.0018 | 0.0635 | 0.0057 | 0.0692 | 0.0617 | 0.00 | 7864.00 | 896.00 |
CORRIDOR_FLR_3 | 0.6432 | 0.0000 | 0.6432 | 0.0069 | 0.6501 | 0.4748 | 90.22 | 62.39 | 8607.39 |
ROOM_1_FLR_6 | 0.0154 | 0.0021 | 0.0176 | 0.0057 | 0.0233 | 0.0154 | 0.00 | 7860.33 | 899.67 |
ROOM_2_FLR_6 | 0.0154 | 0.0021 | 0.0176 | 0.0057 | 0.0233 | 0.0154 | 0.00 | 7860.33 | 899.67 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0021 | 0.1013 | 0.0029 | 0.1042 | 0.0992 | 0.00 | 7860.42 | 899.58 |
BANQUET_FLR_6 | 1.5666 | 0.0000 | 1.5666 | 0.0139 | 1.5806 | 1.1878 | 184.78 | 105.11 | 8470.11 |
DINING_FLR_6 | 1.5988 | 0.0000 | 1.5988 | 0.0139 | 1.6127 | 1.1878 | 57.47 | 70.00 | 8632.53 |
KITCHEN_FLR_6 | 1.8495 | 0.0000 | 1.8495 | 0.0125 | 1.8620 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.2880 | 0.0000 | 0.2880 | 0.0122 | 0.3002 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 80.3407 | 0.1874 | 80.5281 | 0.4537 | 80.9818 | 73.9670 | 589.53 | 7999.79 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.44E+09 | 0.00 | 0.44E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 70553146.19 | 545604.10 | 71098750.29 | 64690340.46 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 14.0330 | 0.0000 | 14.0330 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 2.2372 | 0.0173 | 2.2545 | 2.0513 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 4933.27 | 3826.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 12.7190 | 15.7307 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 2.2372 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1318 |
Defaulted Fields | 1181 |
Fields with Defaults | 4005 |
Autosized Fields | 350 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5993.12 | 75217.23 | 18-JAN-02:30 | 416814.12 | 25-JUL-19:10 |
Electricity:Building | 2519.20 | 32804.76 | 02-JAN-02:10 | 151906.32 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 323.72 | 3705.45 | 02-JAN-02:10 | 24299.15 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2512.10 | 32663.61 | 02-JAN-02:10 | 151664.99 | 02-JAN-20:10 |
InteriorLights:Electricity | 767.09 | 6971.81 | 02-JAN-02:10 | 62892.57 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 173.46 | 1576.23 | 02-JAN-02:10 | 14185.34 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 767.09 | 6971.81 | 02-JAN-02:10 | 62892.57 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 767.09 | 6971.81 | 02-JAN-02:10 | 62892.57 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 173.46 | 1576.23 | 02-JAN-02:10 | 14185.34 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 767.09 | 6971.81 | 02-JAN-02:10 | 62892.57 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.80 | 222.61 | 02-JAN-02:10 | 1390.02 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.61 | 78.27 | 02-JAN-02:10 | 704.41 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.61 | 78.27 | 02-JAN-02:10 | 704.41 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.77 | 257.78 | 02-JAN-02:10 | 1609.65 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.97 | 90.64 | 02-JAN-02:10 | 815.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.97 | 90.64 | 02-JAN-02:10 | 815.72 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 29.11 | 327.88 | 02-JAN-02:10 | 2199.84 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 16.64 | 151.16 | 02-JAN-02:10 | 1360.40 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 16.64 | 151.16 | 02-JAN-02:10 | 1360.40 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.38 | 76.28 | 02-JAN-02:10 | 469.87 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.78 | 25.30 | 02-JAN-02:10 | 227.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.78 | 25.30 | 02-JAN-02:10 | 227.72 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.30 | 1002.39 | 02-JAN-02:10 | 4930.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.37 | 39.69 | 02-JAN-02:10 | 357.21 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.37 | 39.69 | 02-JAN-02:10 | 357.21 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 32.39 | 398.98 | 02-JAN-02:10 | 2727.18 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 18.05 | 195.77 | 02-JAN-02:10 | 1761.91 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 18.05 | 195.77 | 02-JAN-02:10 | 1761.91 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 271.01 | 3251.99 | 02-JAN-02:10 | 20294.39 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 122.01 | 1140.58 | 02-JAN-02:10 | 10265.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 122.01 | 1140.58 | 02-JAN-02:10 | 10265.18 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 18.66 | 264.62 | 01-JAN-02:10 | 1227.54 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 18.66 | 264.59 | 01-JAN-02:10 | 1227.39 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 304.77 | 4565.05 | 01-JAN-02:10 | 20923.25 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 76.02 | 643.59 | 01-JAN-02:10 | 5851.22 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 76.02 | 643.59 | 01-JAN-02:10 | 5851.22 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 304.86 | 4566.30 | 01-JAN-02:10 | 20928.98 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 76.04 | 643.77 | 01-JAN-02:10 | 5852.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 76.04 | 643.77 | 01-JAN-02:10 | 5852.82 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 18.66 | 264.62 | 01-JAN-02:10 | 1227.54 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 18.66 | 264.59 | 01-JAN-02:10 | 1227.39 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.66 | 66.15 | 01-JAN-02:10 | 306.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.50 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.50 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.66 | 66.15 | 01-JAN-02:10 | 306.85 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.49 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.49 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.10 | 540.75 | 01-JAN-02:10 | 2478.43 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 9.00 | 76.24 | 01-JAN-02:10 | 693.10 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 9.00 | 76.24 | 01-JAN-02:10 | 693.10 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 210.63 | 2593.08 | 02-JAN-02:10 | 9841.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 34.77 | 343.78 | 02-JAN-02:10 | 3094.06 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 34.77 | 343.78 | 02-JAN-02:10 | 3094.06 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 210.63 | 2593.08 | 02-JAN-02:10 | 9841.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 34.77 | 343.78 | 02-JAN-02:10 | 3094.06 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 34.77 | 343.78 | 02-JAN-02:10 | 3094.06 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 454.16 | 6253.02 | 02-JAN-02:10 | 18944.06 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.33 | 121.09 | 02-JAN-02:10 | 1089.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.33 | 121.09 | 02-JAN-02:10 | 1089.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1745.01 | 25691.80 | 02-JAN-02:10 | 89475.41 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1745.01 | 25691.80 | 02-JAN-02:10 | 89475.41 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.88 | 1107.34 | 09-JAN-23:30 | 3452.57 | 13-JAN-07:30 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1759.79 | 2610.92 | 12-APR-01:20 | 182168.00 | 14-JUN-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.52 | 0.00 | 01-JAN-11:10 | 2032.19 | 13-JAN-07:30 |
MedTempRefrigeration:Refrigeration:Electricity | 34.27 | 967.98 | 11-JAN-00:30 | 1245.48 | 16-FEB-09:10 |
Fans:Electricity | 634.57 | 12164.12 | 15-MAR-04:00 | 50591.54 | 07-AUG-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 852.20 | 13367.00 | 10-MAR-04:00 | 61747.18 | 07-AUG-21:10 |
ExteriorEquipment:Electricity | 651.48 | 9618.58 | 02-JAN-02:20 | 39726.11 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 32.45 | 553.78 | 11-JAN-02:30 | 1868.65 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 5993.12 | 75217.23 | 18-JAN-02:30 | 416814.12 | 25-JUL-19:10 |
ElectricityPurchased:Plant | 5993.12 | 75217.23 | 18-JAN-02:30 | 416814.12 | 25-JUL-19:10 |
Cogeneration:ElectricityPurchased | 5993.12 | 75217.23 | 18-JAN-02:30 | 416814.12 | 25-JUL-19:10 |
General:Cogeneration:ElectricityPurchased | 5993.12 | 75217.23 | 18-JAN-02:30 | 416814.12 | 25-JUL-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5993.12 | 75217.23 | 18-JAN-02:30 | 416814.12 | 25-JUL-19:10 |
ElectricityNet:Plant | 5993.12 | 75217.23 | 18-JAN-02:30 | 416814.12 | 25-JUL-19:10 |
Cogeneration:ElectricityNet | 5993.12 | 75217.23 | 18-JAN-02:30 | 416814.12 | 25-JUL-19:10 |
General:Cogeneration:ElectricityNet | 5993.12 | 75217.23 | 18-JAN-02:30 | 416814.12 | 25-JUL-19:10 |
General:Fans:Electricity | 634.57 | 12164.12 | 15-MAR-04:00 | 50591.54 | 07-AUG-21:10 |
ExteriorLights:Electricity | 242.91 | 0.00 | 01-JAN-07:20 | 15448.40 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 242.91 | 0.00 | 01-JAN-07:20 | 15448.40 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 185.17 | 0.00 | 01-JAN-12:10 | 9938.94 | 01-JAN-08:30 |
General:HeatRecovery:Electricity | 185.17 | 0.00 | 01-JAN-12:10 | 9938.94 | 01-JAN-08:30 |
WaterSystems:Electricity | 90.74 | 1086.56 | 05-DEC-02:30 | 4738.75 | 07-SEP-18:10 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.56 | 05-DEC-02:30 | 4738.75 | 07-SEP-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1434.84 | 0.00 | 01-JAN-03:20 | 167567.16 | 14-JUN-18:10 |
General:Cooling:Electricity | 1434.84 | 0.00 | 01-JAN-03:20 | 167567.16 | 14-JUN-18:10 |
Pumps:Electricity | 179.41 | 47.91 | 24-APR-07:10 | 8638.43 | 18-JUL-20:50 |
General:Pumps:Electricity | 179.41 | 47.91 | 24-APR-07:10 | 8638.43 | 18-JUL-20:50 |
WIRED_LTG_ELECTRICITY | 27.00 | 0.00 | 01-JAN-00:10 | 2213.82 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4901.14 | 29270.80 | 16-MAR-01:20 | 451554.94 | 18-DEC-21:50 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3112.30 | 15908.90 | 01-JUN-10:10 | 412692.32 | 21-JAN-24:00 |
WaterSystems:NaturalGas | 2843.91 | 15908.90 | 03-FEB-16:10 | 256972.59 | 27-FEB-21:30 |
Water Heater:WaterSystems:NaturalGas | 2843.91 | 15908.90 | 03-FEB-16:10 | 256972.59 | 27-FEB-21:30 |
Heating:NaturalGas | 268.39 | 0.00 | 01-JAN-11:10 | 191594.86 | 03-JAN-01:10 |
Boiler:Heating:NaturalGas | 268.39 | 0.00 | 01-JAN-11:10 | 191594.86 | 03-JAN-01:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 4395.00 | -278.62 | 17-FEB-01:00 | 625920.64 | 18-JUL-20:50 |
PlantLoopCoolingDemand:HVAC | 4395.00 | -278.62 | 17-FEB-01:00 | 625920.64 | 18-JUL-20:50 |
CoolingCoils:PlantLoopCoolingDemand | 4395.00 | -278.62 | 17-FEB-01:00 | 625920.64 | 18-JUL-20:50 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 11-JAN-02:30 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 11-JAN-02:30 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 04-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 04-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 23164.28 | 133094.56 | 29-NOV-14:40 | 2336798.06 | 18-JUL-20:50 |
EnergyTransfer:Building | 5702.44 | 56953.85 | 02-FEB-10:50 | 365115.00 | 15-JUN-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 730.71 | 6796.63 | 11-APR-02:50 | 36174.68 | 02-JUL-10:40 |
Refrigeration:EnergyTransfer | 182.55 | 3973.53 | 09-JAN-23:30 | 10647.72 | 13-JAN-07:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.27 | 1986.76 | 09-JAN-23:30 | 5323.86 | 13-JAN-07:30 |
General:Refrigeration:EnergyTransfer | 91.27 | 1986.76 | 09-JAN-23:30 | 5323.86 | 13-JAN-07:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.27 | 1986.76 | 09-JAN-23:30 | 5323.86 | 13-JAN-07:30 |
EnergyTransfer:Plant | 11458.08 | 12522.32 | 25-OCT-03:00 | 1431926.88 | 18-JUL-20:50 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.58 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.69 | 1853.94 | 11-JAN-00:30 | 2686.44 | 16-FEB-09:10 |
EnergyTransfer:Zone:BASEMENT | 418.79 | 1458.13 | 02-FEB-10:50 | 27543.86 | 18-DEC-21:20 |
Heating:EnergyTransfer | 50.71 | 0.00 | 01-JAN-08:20 | 54747.61 | 26-DEC-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.02 | 0.00 | 01-JAN-00:10 | 1874.32 | 15-FEB-23:10 |
General:Heating:EnergyTransfer | 50.71 | 0.00 | 01-JAN-08:20 | 54747.61 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.02 | 0.00 | 01-JAN-00:10 | 1874.32 | 15-FEB-23:10 |
Cooling:EnergyTransfer | 5560.46 | 39824.47 | 02-FEB-10:50 | 361639.61 | 15-JUN-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 418.77 | 1458.13 | 02-FEB-10:50 | 27543.86 | 18-DEC-21:20 |
General:Cooling:EnergyTransfer | 5560.46 | 39824.47 | 02-FEB-10:50 | 361639.61 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 418.77 | 1458.13 | 02-FEB-10:50 | 27543.86 | 18-DEC-21:20 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 43.45 | 0.15 | 19-DEC-06:30 | 3750.87 | 18-OCT-13:00 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.06 | 0.00 | 01-JAN-00:20 | 806.17 | 27-DEC-07:30 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.06 | 0.00 | 01-JAN-00:20 | 806.17 | 27-DEC-07:30 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 43.39 | 0.00 | 07-JAN-07:10 | 3750.87 | 18-OCT-13:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 43.39 | 0.00 | 07-JAN-07:10 | 3750.87 | 18-OCT-13:00 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 40.18 | 51.90 | 02-FEB-10:50 | 2494.28 | 15-JUN-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 125.35 | 23-DEC-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 125.35 | 23-DEC-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 40.17 | 0.00 | 02-FEB-10:50 | 2494.28 | 15-JUN-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 40.17 | 0.00 | 02-FEB-10:50 | 2494.28 | 15-JUN-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 29.37 | 25.74 | 16-FEB-09:00 | 2636.68 | 15-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.01 | 0.00 | 01-JAN-00:20 | 155.51 | 23-DEC-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.01 | 0.00 | 01-JAN-00:20 | 155.51 | 23-DEC-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 29.36 | 0.00 | 09-JAN-07:10 | 2636.68 | 15-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 29.36 | 0.00 | 09-JAN-07:10 | 2636.68 | 15-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 19.29 | 0.15 | 28-DEC-06:00 | 984.89 | 15-JUN-21:00 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.03 | 0.00 | 01-JAN-00:20 | 189.76 | 23-DEC-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.03 | 0.00 | 01-JAN-00:20 | 189.76 | 23-DEC-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 19.26 | 0.00 | 09-JAN-07:10 | 984.89 | 15-JUN-21:00 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 19.26 | 0.00 | 09-JAN-07:10 | 984.89 | 15-JUN-21:00 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 601.91 | 5772.14 | 25-OCT-03:10 | 39770.82 | 15-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 281.18 | 11-APR-02:40 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 281.18 | 11-APR-02:40 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 601.91 | 5772.14 | 25-OCT-03:10 | 39770.82 | 15-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 601.91 | 5772.14 | 25-OCT-03:10 | 39770.82 | 15-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 260.00 | 375.76 | 09-JAN-07:10 | 12764.49 | 18-OCT-15:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.06 | 0.00 | 01-JAN-00:10 | 874.98 | 02-DEC-07:30 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.06 | 0.00 | 01-JAN-00:10 | 874.98 | 02-DEC-07:30 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 259.94 | 194.66 | 09-JAN-07:10 | 12764.49 | 18-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 259.94 | 194.66 | 09-JAN-07:10 | 12764.49 | 18-OCT-15:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 831.71 | 807.90 | 02-FEB-10:50 | 44431.94 | 07-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.07 | 0.00 | 01-JAN-00:10 | 3099.57 | 11-NOV-04:40 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.07 | 0.00 | 01-JAN-00:10 | 3099.57 | 11-NOV-04:40 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 831.64 | 735.29 | 02-FEB-10:50 | 44431.94 | 07-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 831.64 | 735.29 | 02-FEB-10:50 | 44431.94 | 07-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 78.00 | 0.00 | 11-MAR-03:10 | 11664.48 | 15-JUN-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 4.73 | 0.00 | 01-JAN-00:10 | 4296.43 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 4.73 | 0.00 | 01-JAN-00:10 | 4296.43 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 73.28 | 0.00 | 01-JAN-00:20 | 11664.48 | 15-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 73.28 | 0.00 | 01-JAN-00:20 | 11664.48 | 15-JUN-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 72.24 | 0.02 | 24-NOV-03:30 | 11891.00 | 15-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 8.16 | 0.00 | 01-JAN-08:10 | 4581.57 | 27-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 8.16 | 0.00 | 01-JAN-08:10 | 4581.57 | 27-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 64.09 | 0.00 | 01-JAN-00:10 | 11891.00 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 64.09 | 0.00 | 01-JAN-00:10 | 11891.00 | 15-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 502.74 | 2149.92 | 27-DEC-06:00 | 50813.59 | 22-OCT-13:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 502.74 | 2149.92 | 27-DEC-06:00 | 50813.59 | 22-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 502.74 | 2149.92 | 27-DEC-06:00 | 50813.59 | 22-OCT-13:20 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 486.73 | 0.47 | 26-NOV-11:00 | 69794.72 | 15-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 14.34 | 0.00 | 01-JAN-00:10 | 29056.67 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 14.34 | 0.00 | 01-JAN-00:10 | 29056.67 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 472.39 | 0.00 | 02-JAN-02:10 | 69794.72 | 15-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 472.39 | 0.00 | 02-JAN-02:10 | 69794.72 | 15-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 78.98 | 0.08 | 13-FEB-07:30 | 9947.82 | 15-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 4.85 | 0.00 | 01-JAN-08:10 | 4285.85 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 4.85 | 0.00 | 01-JAN-08:10 | 4285.85 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 74.13 | 0.00 | 01-JAN-00:10 | 9947.82 | 15-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 74.13 | 0.00 | 01-JAN-00:10 | 9947.82 | 15-JUN-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 72.69 | 0.09 | 07-JAN-10:20 | 10069.64 | 15-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 8.04 | 0.00 | 01-JAN-08:10 | 4321.19 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 8.04 | 0.00 | 01-JAN-08:10 | 4321.19 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 64.65 | 0.00 | 01-JAN-00:10 | 10069.64 | 15-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 64.65 | 0.00 | 01-JAN-00:10 | 10069.64 | 15-JUN-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 199.72 | 307.91 | 16-FEB-09:00 | 13937.68 | 15-JUN-18:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.12 | 0.00 | 01-JAN-00:20 | 1287.78 | 23-DEC-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.12 | 0.00 | 01-JAN-00:20 | 1287.78 | 23-DEC-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 199.60 | 0.00 | 09-JAN-07:10 | 13937.68 | 15-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 199.60 | 0.00 | 09-JAN-07:10 | 13937.68 | 15-JUN-18:30 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 20.07 | 0.01 | 25-OCT-00:50 | 3168.48 | 15-JUN-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.52 | 0.00 | 01-JAN-08:10 | 1305.99 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.52 | 0.00 | 01-JAN-08:10 | 1305.99 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.54 | 0.00 | 01-JAN-00:10 | 3168.48 | 15-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.54 | 0.00 | 01-JAN-00:10 | 3168.48 | 15-JUN-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 19.27 | 0.01 | 11-FEB-20:10 | 3185.94 | 15-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 3.88 | 0.00 | 01-JAN-08:10 | 1492.73 | 27-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 3.88 | 0.00 | 01-JAN-08:10 | 1492.73 | 27-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 15.39 | 0.00 | 01-JAN-00:10 | 3185.94 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 15.39 | 0.00 | 01-JAN-00:10 | 3185.94 | 15-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 112.55 | 0.09 | 29-DEC-23:40 | 15226.16 | 29-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 3.65 | 0.00 | 01-JAN-00:10 | 5590.73 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 3.65 | 0.00 | 01-JAN-00:10 | 5590.73 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 108.90 | 0.00 | 01-JAN-05:30 | 15226.16 | 29-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 108.90 | 0.00 | 01-JAN-05:30 | 15226.16 | 29-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 483.02 | 1074.31 | 02-FEB-10:50 | 23624.35 | 15-JUN-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.04 | 0.00 | 01-JAN-00:10 | 1031.27 | 11-NOV-04:40 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.04 | 0.00 | 01-JAN-00:10 | 1031.27 | 11-NOV-04:40 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 482.98 | 804.41 | 02-FEB-10:50 | 23624.35 | 15-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 482.98 | 804.41 | 02-FEB-10:50 | 23624.35 | 15-JUN-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 508.45 | 1874.68 | 02-FEB-10:50 | 24968.40 | 15-JUN-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 811.46 | 11-NOV-04:40 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 811.46 | 11-NOV-04:40 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 508.44 | 1874.68 | 02-FEB-10:50 | 24968.40 | 15-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 508.44 | 1874.68 | 02-FEB-10:50 | 24968.40 | 15-JUN-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 60.55 | 06-MAR-00:30 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 60.55 | 06-MAR-00:30 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 639.43 | 4474.93 | 11-APR-02:50 | 31110.72 | 02-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 639.43 | 4474.93 | 11-APR-02:50 | 31110.72 | 02-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 92.56 | 0.17 | 03-FEB-04:20 | 7016.23 | 03-JUL-14:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.11 | 0.00 | 01-JAN-00:20 | 1319.63 | 27-DEC-07:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.11 | 0.00 | 01-JAN-00:20 | 1319.63 | 27-DEC-07:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 92.45 | 0.00 | 09-JAN-07:10 | 7016.23 | 03-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 92.45 | 0.00 | 09-JAN-07:10 | 7016.23 | 03-JUL-14:30 |
PlantLoopHeatingDemand:Facility | 833.97 | 7205.63 | 01-AUG-01:40 | 165335.40 | 25-DEC-07:30 |
PlantLoopHeatingDemand:Plant | 648.51 | 7205.63 | 01-AUG-01:40 | 50237.28 | 27-JAN-08:00 |
WaterSystems:PlantLoopHeatingDemand | 648.51 | 7205.63 | 01-AUG-01:40 | 50237.28 | 27-JAN-08:00 |
General:WaterSystems:PlantLoopHeatingDemand | 648.51 | 7205.63 | 01-AUG-01:40 | 50237.28 | 27-JAN-08:00 |
EnergyTransfer:HVAC | 6003.76 | 52.05 | 11-APR-12:20 | 663995.60 | 21-JUL-18:10 |
HeatingCoils:EnergyTransfer | 185.46 | 0.00 | 01-JAN-11:10 | 141861.80 | 24-DEC-23:50 |
PlantLoopHeatingDemand:HVAC | 185.46 | 0.00 | 01-JAN-11:10 | 141861.80 | 24-DEC-23:50 |
HeatingCoils:PlantLoopHeatingDemand | 185.46 | 0.00 | 01-JAN-11:10 | 141861.80 | 24-DEC-23:50 |
CoolingCoils:EnergyTransfer | 4395.00 | -278.62 | 17-FEB-01:00 | 625920.64 | 18-JUL-20:50 |
HeatRecoveryForHeating:EnergyTransfer | 1098.59 | 0.00 | 01-JAN-12:10 | 347758.81 | 02-MAR-05:00 |
HeatRecoveryForCooling:EnergyTransfer | 324.70 | 0.00 | 01-JAN-00:10 | 151838.02 | 20-JUL-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 648.51 | 7205.63 | 01-AUG-01:40 | 50237.28 | 27-JAN-08:00 |
WaterUse:WaterSystems:EnergyTransfer | 648.51 | 7205.63 | 01-AUG-01:40 | 50237.28 | 27-JAN-08:00 |
Boilers:EnergyTransfer | 182.93 | 0.00 | 01-JAN-11:10 | 140148.01 | 24-DEC-23:50 |
Chillers:EnergyTransfer | 4550.26 | 0.00 | 01-JAN-03:20 | 629435.00 | 18-JUL-20:50 |
HeatRejection:EnergyTransfer | 5985.10 | 0.00 | 01-JAN-03:20 | 771297.79 | 18-JUL-20:50 |
General:HeatRejection:EnergyTransfer | 5985.10 | 0.00 | 01-JAN-03:20 | 771297.79 | 18-JUL-20:50 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.024 | -418.771 | 0.000 | 0.000 | 137.068 | 173.462 | 150.255 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -42.039 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.062 | -43.385 | 0.000 | 0.000 | 14.291 | 8.614 | 10.186 | 23.363 | 0.000 | 0.450 | 0.001 | 0.000 | -9.077 | 0.000 | -2.291 | -2.211 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.007 | -40.174 | 0.000 | 0.000 | 16.261 | 9.975 | 11.795 | 0.000 | 0.000 | 0.182 | 2.858 | 0.000 | 0.000 | 0.000 | -0.904 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.012 | -29.356 | 0.000 | 0.000 | 3.496 | 16.635 | 12.471 | 0.000 | 0.000 | 0.416 | 0.000 | 0.000 | 0.000 | 0.000 | -2.061 | -1.614 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.025 | -19.265 | 0.000 | 0.000 | 2.837 | 2.785 | 3.598 | 0.000 | 0.000 | 0.280 | 10.811 | 0.000 | 0.000 | 0.000 | -1.070 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.001 | -601.917 | 0.000 | 0.000 | 10.561 | 4.368 | 658.131 | 0.000 | 0.000 | 0.560 | 0.000 | 0.000 | 0.000 | 0.000 | -3.144 | -68.560 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.062 | -259.944 | 0.000 | 0.000 | 189.604 | 18.050 | 14.341 | 66.570 | 0.000 | 1.152 | 0.583 | 0.000 | -25.457 | 0.000 | -4.960 | -0.000 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.071 | -831.644 | 0.000 | 0.000 | 543.217 | 122.013 | 148.998 | 87.564 | 0.000 | 3.050 | 0.000 | 0.000 | -35.002 | 0.000 | -15.080 | -23.187 |
ROOM_1_FLR_3 | 6.701 | -59.918 | 0.000 | -15.337 | 0.000 | 0.000 | 9.675 | 6.366 | 12.292 | 50.954 | 0.000 | 1.664 | 10.802 | 0.000 | -18.172 | 0.000 | -5.029 | -0.000 |
ROOM_2_FLR_3 | 10.784 | -51.668 | 0.000 | -15.045 | 0.000 | 0.000 | 9.707 | 6.366 | 12.291 | 38.632 | 0.000 | 1.668 | 10.935 | 0.000 | -18.757 | 0.000 | -4.911 | -0.001 |
ROOM_3_MULT19_FLR_3 | 0.001 | -253.855 | 0.000 | -248.880 | 0.000 | 0.000 | 0.000 | 76.021 | 228.754 | 288.108 | 0.000 | 6.402 | 59.011 | 0.000 | -110.147 | 0.000 | -45.414 | -0.004 |
ROOM_4_MULT19_FLR_3 | 37.284 | -294.187 | 0.000 | -201.136 | 0.000 | 0.000 | 184.918 | 76.042 | 228.817 | 104.052 | 0.000 | 10.797 | 0.000 | 0.000 | -100.899 | 0.000 | -32.116 | -13.572 |
ROOM_5_FLR_3 | 6.773 | -60.630 | 0.000 | -15.426 | 0.000 | 0.000 | 9.664 | 6.366 | 12.292 | 50.974 | 0.000 | 1.661 | 10.865 | 0.000 | -17.466 | 0.000 | -5.072 | -0.000 |
ROOM_6_FLR_3 | 10.603 | -52.082 | 0.000 | -15.134 | 0.000 | 0.000 | 9.698 | 6.366 | 12.291 | 38.066 | 0.000 | 1.662 | 10.959 | 0.000 | -17.477 | 0.000 | -4.952 | -0.001 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.117 | -199.606 | 0.000 | 0.000 | 111.189 | 109.603 | 0.000 | 42.148 | 0.000 | 1.276 | 0.001 | 0.000 | -25.159 | 0.000 | -6.294 | -33.275 |
ROOM_1_FLR_6 | 3.189 | -14.400 | 0.000 | -3.808 | 0.000 | 0.000 | 2.422 | 1.592 | 3.073 | 12.697 | 0.000 | 0.417 | 0.531 | 0.000 | -4.439 | 0.000 | -1.274 | -0.000 |
ROOM_2_FLR_6 | 4.690 | -12.479 | 0.000 | -3.729 | 0.000 | 0.000 | 2.431 | 1.591 | 3.073 | 9.650 | 0.000 | 0.418 | 0.162 | 0.000 | -4.566 | 0.000 | -1.241 | -0.000 |
ROOM_3_MULT9_FLR_6 | 5.909 | -86.268 | 0.000 | -24.888 | 0.000 | 0.000 | 21.728 | 9.005 | 27.097 | 63.940 | 0.000 | 2.069 | 8.695 | 0.000 | -20.667 | 0.000 | -6.621 | -0.000 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.039 | -482.987 | 0.000 | 0.000 | 325.658 | 34.773 | 175.857 | 10.082 | 0.000 | 0.704 | 0.000 | 0.000 | -14.585 | 0.000 | -3.307 | -46.232 |
DINING_FLR_6 | 0.000 | 0.000 | 0.018 | -508.439 | 0.000 | 0.000 | 321.584 | 34.773 | 175.857 | 9.714 | 0.000 | 0.676 | 0.000 | 0.000 | -15.209 | 0.000 | -3.394 | -15.579 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -639.426 | 0.000 | 0.000 | 27.902 | 13.327 | 550.372 | 23.035 | 0.000 | 0.560 | 38.588 | 0.000 | -11.113 | 0.000 | -3.245 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.112 | -92.448 | 0.000 | 0.000 | 29.429 | 28.999 | 0.000 | 20.347 | 0.000 | 0.548 | 27.110 | 0.000 | -11.291 | 0.000 | -2.806 | -0.000 |
Total Facility | 85.934 | -885.488 | 0.549 | -4710.744 | 0.000 | 0.000 | 1983.339 | 767.092 | 2451.839 | 939.896 | 0.000 | 36.612 | 191.912 | 0.000 | -459.482 | 0.000 | -155.188 | -246.279 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 19-NOV-23:56 | 0.00 | 0.00 | 0.00 | -40522.70 | 0.00 | 0.00 | 5947.74 | 4728.51 | 4258.44 | 0.00 | 0.00 | 0.00 | 25588.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 18-OCT-13:00 | 0.00 | 0.00 | 0.00 | -3750.75 | 0.00 | 0.00 | 150.60 | 195.67 | 252.59 | 4420.54 | 0.00 | 38.38 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1307.03 |
RETAIL_2_FLR_1 | 08-FEB-22:01 | 0.00 | 0.00 | 0.00 | -3206.86 | 0.00 | 0.00 | 766.58 | 543.81 | 585.00 | 0.00 | 0.00 | 0.00 | 1399.90 | 0.00 | -0.00 | 0.00 | -88.43 | 0.00 |
MECH_FLR_1 | 15-JUN-20:00 | 0.00 | 0.00 | 0.00 | -2636.84 | 0.00 | 0.00 | 129.08 | 1360.40 | 839.45 | 0.00 | 0.00 | 88.47 | 219.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 17-MAR-03:44 | 0.00 | 0.00 | 0.00 | -1269.32 | 0.00 | 0.00 | 145.59 | 25.30 | 50.98 | 0.00 | 0.00 | 0.00 | 1138.53 | 0.00 | -0.00 | 0.00 | -91.08 | 0.00 |
LAUNDRY_FLR_1 | 08-FEB-20:40 | 0.00 | 0.00 | 0.00 | -52905.68 | 0.00 | 0.00 | 404.66 | 357.21 | 44299.38 | 0.00 | 0.00 | 0.00 | 8144.54 | 0.00 | -0.00 | 0.00 | -300.11 | 0.00 |
CAFE_FLR_1 | 23-DEC-00:33 | 0.00 | 0.00 | 0.00 | -20250.84 | 0.00 | 0.00 | 9072.05 | 391.53 | 304.82 | 0.00 | 0.00 | 0.00 | 13653.86 | 0.00 | -2762.28 | 0.00 | -409.16 | 0.00 |
LOBBY_FLR_1 | 11-APR-04:15 | 0.00 | 0.00 | 0.00 | -62840.03 | 0.00 | 0.00 | 26331.89 | 2281.15 | 3167.12 | 0.00 | 0.00 | 0.00 | 36238.91 | 0.00 | -3907.58 | 0.00 | -1271.45 | 0.00 |
ROOM_1_FLR_3 | 20-MAY-15:01 | 0.00 | -13710.80 | 0.00 | -643.89 | 0.00 | 0.00 | 130.72 | 161.71 | 305.54 | 7789.68 | 0.00 | 219.45 | 5747.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 15-JUN-18:02 | 0.00 | -13629.41 | 0.00 | -644.43 | 0.00 | 0.00 | 335.50 | 436.07 | 516.20 | 6541.36 | 0.00 | 300.12 | 6144.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 22-OCT-13:20 | 0.00 | -41436.13 | 0.00 | -9379.12 | 0.00 | 0.00 | 0.00 | 1930.94 | 5686.12 | 52841.55 | 0.00 | 322.51 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9965.88 |
ROOM_4_MULT19_FLR_3 | 02-JUN-18:01 | 0.00 | -85204.60 | 0.00 | -8848.53 | 0.00 | 0.00 | 6374.67 | 5209.05 | 9610.21 | 9450.74 | 0.00 | 1686.98 | 61721.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 15-JUN-08:61 | 0.00 | -12048.91 | 0.00 | -649.60 | 0.00 | 0.00 | 87.15 | 215.61 | 453.05 | 7856.16 | 0.00 | 162.67 | 3923.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 15-JUN-08:61 | 0.00 | -11969.95 | 0.00 | -650.66 | 0.00 | 0.00 | 87.15 | 215.58 | 452.99 | 7973.69 | 0.00 | 162.25 | 3728.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 15-JUN-18:30 | 0.00 | 0.00 | 0.00 | -13938.46 | 0.00 | 0.00 | 4080.27 | 7967.22 | 0.00 | 2736.32 | 0.00 | 316.05 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1161.41 |
ROOM_1_FLR_6 | 15-JUN-15:02 | 0.00 | -3643.47 | 0.00 | -160.64 | 0.00 | 0.00 | 58.82 | 34.30 | 68.48 | 2007.17 | 0.00 | 87.36 | 1547.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 15-JUN-18:02 | 0.00 | -3617.60 | 0.00 | -161.02 | 0.00 | 0.00 | 83.88 | 109.02 | 129.05 | 1625.21 | 0.00 | 74.74 | 1756.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 30-SEP-15:01 | 0.00 | -16277.57 | 0.00 | -1046.93 | 0.00 | 0.00 | 294.12 | 228.73 | 673.54 | 5652.25 | 0.00 | 146.04 | 10329.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 15-FEB-23:57 | 0.00 | 0.00 | 0.00 | -32415.89 | 0.00 | 0.00 | 15871.78 | 1031.35 | 6747.90 | 0.00 | 0.00 | 0.00 | 10550.44 | 0.00 | -1485.65 | 0.00 | -299.94 | 0.00 |
DINING_FLR_6 | 17-MAR-04:10 | 0.00 | 0.00 | 0.00 | -41476.55 | 0.00 | 0.00 | 15856.70 | 687.57 | 2249.30 | 0.00 | 0.00 | 0.00 | 24545.79 | 0.00 | -1577.83 | 0.00 | -284.99 | 0.00 |
KITCHEN_FLR_6 | 27-DEC-11:51 | 0.00 | 0.00 | 0.00 | -38360.84 | 0.00 | 0.00 | 264.75 | 302.73 | 24259.91 | 718.68 | 0.00 | 0.00 | 13109.14 | 0.00 | -0.00 | 0.00 | -294.37 | 0.00 |
CORRIDOR_FLR_6 | 03-JUL-14:30 | 0.00 | 0.00 | 0.00 | -7016.36 | 0.00 | 0.00 | 462.68 | 658.76 | 0.00 | 1880.04 | 0.00 | 162.42 | 3852.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-JUN-18:02 | 0.00 | -182215.52 | 0.00 | -223513.66 | 0.00 | 0.00 | 74518.35 | 53784.22 | 122326.88 | 61813.62 | 0.00 | 7220.42 | 86065.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 15-FEB-23:10 | 0.00 | 0.00 | 3749.07 | 0.00 | 0.00 | 0.00 | 6716.62 | 4728.51 | 4258.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19452.64 |
RETAIL_1_FLR_1 | 27-DEC-07:15 | 0.00 | 0.00 | 810.01 | 0.00 | 0.00 | 0.00 | 358.03 | 391.34 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1247.05 | 0.00 | -285.35 | -459.98 |
RETAIL_2_FLR_1 | 31-DEC-09:57 | 0.00 | 0.00 | 373.83 | 0.00 | 0.00 | 0.00 | 490.48 | 271.91 | 334.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -76.10 | -1394.41 |
MECH_FLR_1 | 31-DEC-09:57 | 0.00 | 0.00 | 357.78 | 0.00 | 0.00 | 0.00 | 109.40 | 453.47 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -167.08 | -1107.02 |
STORAGE_FLR_1 | 22-NOV-05:53 | 0.00 | 0.00 | 382.30 | 0.00 | 0.00 | 0.00 | 150.18 | 50.60 | 76.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -88.02 | -571.54 |
LAUNDRY_FLR_1 | 11-APR-02:36 | 0.00 | 0.00 | 2812.82 | 0.00 | 0.00 | 0.00 | 543.98 | 39.69 | 9326.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -248.72 | -12473.95 |
CAFE_FLR_1 | 03-DEC-11:58 | 0.00 | 0.00 | 3554.43 | 0.00 | 0.00 | 0.00 | 3528.46 | 358.25 | 406.43 | 2127.08 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -372.08 | -9602.58 |
LOBBY_FLR_1 | 22-NOV-05:53 | 0.00 | 0.00 | 7529.71 | 0.00 | 0.00 | 0.00 | 26878.41 | 2281.15 | 3167.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3668.37 | 0.00 | -1257.12 | -34930.90 |
ROOM_1_FLR_3 | 27-DEC-09:01 | 9213.61 | 272.35 | 0.00 | -272.35 | 0.00 | 0.00 | 108.88 | 215.61 | 453.05 | 1087.56 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -530.81 | -10547.90 |
ROOM_2_FLR_3 | 07-DEC-09:01 | 9284.86 | 273.87 | 0.00 | -273.87 | 0.00 | 0.00 | 107.92 | 215.58 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -854.64 | 0.00 | -389.88 | -8816.84 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 27-JAN-09:01 | 52745.99 | 4294.99 | 0.00 | -4294.99 | 0.00 | 0.00 | 1978.02 | 2575.24 | 8433.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9239.98 | 0.00 | -2976.47 | -53516.25 |
ROOM_5_FLR_3 | 26-DEC-09:01 | 8885.24 | 282.47 | 0.00 | -282.47 | 0.00 | 0.00 | 108.13 | 215.61 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -487.68 | 0.00 | -526.42 | -8647.92 |
ROOM_6_FLR_3 | 26-NOV-19:01 | 8920.51 | 287.33 | 0.00 | -287.33 | 0.00 | 0.00 | 347.35 | 489.96 | 516.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1914.65 | 0.00 | -382.99 | -7976.38 |
CORRIDOR_FLR_3 | 31-DEC-09:57 | 0.00 | 0.00 | 2738.54 | 0.00 | 0.00 | 0.00 | 3430.75 | 2987.71 | 0.00 | 4001.60 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -521.24 | -12637.36 |
ROOM_1_FLR_6 | 26-NOV-19:01 | 2768.64 | 66.74 | 0.00 | -66.74 | 0.00 | 0.00 | 88.39 | 122.50 | 129.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -463.64 | 0.00 | -94.17 | -2550.79 |
ROOM_2_FLR_6 | 07-DEC-09:01 | 2776.84 | 66.00 | 0.00 | -66.00 | 0.00 | 0.00 | 27.22 | 53.90 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -199.44 | 0.00 | -96.90 | -2674.86 |
ROOM_3_MULT9_FLR_6 | 26-DEC-09:01 | 12750.36 | 495.67 | 0.00 | -495.67 | 0.00 | 0.00 | 239.44 | 304.96 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -602.90 | 0.00 | -619.81 | -13070.75 |
BANQUET_FLR_6 | 19-DEC-10:59 | 0.00 | 0.00 | 4061.86 | 0.00 | 0.00 | 0.00 | 4104.03 | 687.57 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -444.58 | 0.00 | -274.35 | -14882.43 |
DINING_FLR_6 | 19-DEC-10:59 | 0.00 | 0.00 | 3193.32 | 0.00 | 0.00 | 0.00 | 4004.92 | 687.57 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -492.34 | 0.00 | -281.76 | -13859.61 |
KITCHEN_FLR_6 | 06-MAR-00:28 | 0.00 | 0.00 | 605.36 | 0.00 | 0.00 | 0.00 | 1394.83 | 242.18 | 5415.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1234.12 | 0.00 | -264.86 | -6159.37 |
CORRIDOR_FLR_6 | 27-DEC-07:30 | 0.00 | 0.00 | 1319.43 | 0.00 | 0.00 | 0.00 | 733.31 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1634.21 | 0.00 | -354.65 | -1381.39 |
Total Facility | 27-DEC-09:01 | 2849.90 | 110142.97 | 151.24 | -110142.97 | 0.00 | 0.00 | 23709.37 | 26712.50 | 88432.23 | 66081.34 | 0.00 | 0.00 | 0.00 | 0.00 | -10822.51 | 0.00 | -14079.73 | -183034.33 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 24.9468 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 24.8182 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 13.7150 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.7955 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9169 | 2.9169 | 1.2543 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3761 | 0.3761 | 0.1162 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2829 | 0.2829 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2888 | 0.2888 | 0.0866 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1415 | 0.1415 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7796 | 3.7796 | 1.1339 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5854 | 1.5854 | 0.9924 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2603 | 5.2603 | 2.7774 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6563 | 1.6563 | 0.6957 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5427 | 2.5427 | 1.7418 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6635 | 2.6635 | 1.7419 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5802 | 2.5802 | 0.7741 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8725 | 0.8725 | 0.2617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 24.9468 | 24.8182 | 24.9468 | 11.7955 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4585 | 1.4585 | 1.2543 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1881 | 0.1881 | 0.1162 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1415 | 0.1415 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1444 | 0.1444 | 0.0866 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0848 | 0.0848 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8898 | 1.8898 | 1.1339 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9924 | 0.9924 | 0.9924 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7774 | 2.7774 | 2.7774 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8282 | 0.8282 | 0.6957 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7418 | 1.7418 | 1.7418 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7419 | 1.7419 | 1.7419 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2901 | 1.2901 | 0.7741 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4362 | 0.4362 | 0.2617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 13.7150 | 11.7955 | 11.7955 | 11.7955 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 193.17 |
Number of hours not met | 193.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 268.39 | 191594.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1434.84 | 167567.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 767.09 | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 242.91 | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.56 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 32.45 | 1868.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 634.57 | 50591.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 179.41 | 8638.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 185.17 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.75 | 2843.91 | 256972.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.52 | 2032.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.27 | 1245.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1806.89 | 5993.12 |
Natural Gas | 1788.84 | 4901.14 |
Additional | 0.00 | 0.00 |
Total | 3595.73 | 10894.26 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 67.61 |
Space Heating | 0.00 |
Space Cooling | 126.47 |
Fans (All) | 55.93 |
Service Water Heating | 8.00 |
Receptacle Equipment | 153.81 |
Miscellaneous (All) | 528.25 |
Subtotal | 528.25 |
Natural Gas [MJ/m2] | |
Space Heating | 23.66 |
Service Water Heating | 250.67 |
Miscellaneous (All) | 432.00 |
Subtotal | 432.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.04 |
Space Heating | 2.46 |
Space Cooling | 13.17 |
Fans (All) | 5.82 |
Service Water Heating | 26.94 |
Receptacle Equipment | 32.44 |
Miscellaneous | 12.12 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2667. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 2678. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 3061. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8759.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.50 | 0.00 | 0.00 | 0.00 |
Average | 8759.96 | 0.04 | 0.00 | 0.00 | 0.00 |
Sum | 192719.17 | 0.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37201.00 | 2.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108264.50 | 4.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 4.50 | 0.00 | 0.00 | 0.00 |
Average | 288886.75 | 0.30 | 0.00 | 0.00 | 0.00 |
Sum | 6355508.50 | 6.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8736.67 | 23.33 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8748.83 | 11.17 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8361.00 | 399.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8351.00 | 409.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8611.17 | 148.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8335.33 | 424.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8350.00 | 410.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8335.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 424.67 | 0.00 | 0.00 | 0.00 |
Average | 8676.97 | 83.03 | 0.00 | 0.00 | 0.00 |
Sum | 190893.33 | 1826.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 49974.33 | 204.67 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59034.17 | 121.83 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 659890.83 | 50526.17 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1969512.83 | 145916.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 97861.33 | 2496.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1154881.33 | 90833.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1158345.83 | 87369.17 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108265.17 | 3.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1969512.83 | 145916.17 | 0.00 | 0.00 | 0.00 |
Average | 271729.22 | 17157.83 | 0.00 | 0.00 | 0.00 |
Sum | 5978042.83 | 377472.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:07
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342492E+11 | 36391.18 | 26-JAN-20:51 | 3.90 | -2.9 | 0.819417E+10 | 5002.88 | 20-JAN-00:10 | 3.90 | -2.9 |
February | 0.256963E+11 | 34516.86 | 02-FEB-22:34 | 2.93 | -2.7 | 0.709716E+10 | 4940.41 | 08-FEB-22:10 | 3.03 | 0.14 |
March | 0.257623E+11 | 19817.85 | 17-MAR-03:44 | 5.87 | -0.4 | 0.732802E+10 | 4779.73 | 01-MAR-22:10 | 5.87 | -0.4 |
April | 0.259205E+11 | 17820.58 | 11-APR-04:30 | 5.30 | 0.69 | 0.712978E+10 | 4616.30 | 11-APR-21:10 | 13.12 | 3.77 |
May | 0.285093E+11 | 14617.15 | 06-MAY-06:00 | 10.00 | 2.15 | 0.760571E+10 | 4753.06 | 12-MAY-22:10 | 21.52 | 10.32 |
June | 0.293915E+11 | 13973.73 | 23-JUN-21:00 | 23.30 | 15.34 | 0.760139E+10 | 4837.19 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.361337E+11 | 20668.26 | 19-JUL-21:00 | 23.90 | 20.39 | 0.817137E+10 | 4837.14 | 05-JUL-21:00 | 23.90 | 20.39 |
August | 0.413630E+11 | 23564.24 | 24-AUG-21:00 | 26.70 | 16.71 | 0.825800E+10 | 4837.26 | 22-AUG-00:10 | 26.70 | 16.71 |
September | 0.444782E+11 | 25575.64 | 21-SEP-21:00 | 26.10 | 17.37 | 0.797676E+10 | 4851.12 | 25-SEP-03:39 | 10.77 | 9.09 |
October | 0.453757E+11 | 35484.32 | 25-OCT-05:30 | 6.95 | 5.28 | 0.823624E+10 | 5023.98 | 25-OCT-03:20 | 6.95 | 5.28 |
November | 0.422185E+11 | 40523.33 | 19-NOV-23:56 | 4.40 | -1.2 | 0.796397E+10 | 5044.75 | 17-NOV-00:20 | 4.40 | -1.2 |
December | 0.396697E+11 | 37239.34 | 02-DEC-07:38 | 4.80 | 0.46 | 0.823113E+10 | 5071.99 | 23-DEC-00:20 | 5.20 | 0.42 |
Annual Sum or Average | 0.418768E+12 | 0.937937E+11 | ||||||||
Minimum of Months | 0.256963E+11 | 13973.73 | 2.93 | -2.9 | 0.709716E+10 | 4616.30 | 3.03 | -2.9 | ||
Maximum of Months | 0.453757E+11 | 40523.33 | 26.70 | 20.39 | 0.825800E+10 | 5071.99 | 28.43 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243335E+10 | 3119.63 | 26-JAN-12:32 | 4.23 | -2.6 | 0.699966E+09 | 487.20 | 12-JAN-22:10 | 4.23 | -2.6 |
February | 0.243152E+10 | 3000.98 | 07-FEB-13:30 | 20.30 | 9.54 | 0.649135E+09 | 491.82 | 21-FEB-22:40 | 11.47 | 3.03 |
March | 0.267115E+10 | 2431.99 | 16-MAR-13:10 | 22.30 | 9.05 | 0.739660E+09 | 491.82 | 06-MAR-22:19 | 22.30 | 9.05 |
April | 0.328368E+10 | 2529.23 | 03-APR-14:10 | 26.70 | 11.67 | 0.771026E+09 | 491.82 | 19-APR-23:30 | 25.00 | 11.56 |
May | 0.392103E+10 | 2489.31 | 19-MAY-18:15 | 32.93 | 15.38 | 0.825551E+09 | 491.86 | 18-MAY-00:10 | 32.93 | 15.38 |
June | 0.462944E+10 | 2868.32 | 15-JUN-18:15 | 35.73 | 14.50 | 0.811813E+09 | 491.86 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.480353E+10 | 2836.02 | 26-JUL-18:03 | 33.77 | 19.75 | 0.836165E+09 | 491.84 | 05-JUL-21:00 | 33.77 | 19.75 |
August | 0.480685E+10 | 3004.70 | 27-AUG-12:00 | 33.30 | 15.93 | 0.837598E+09 | 491.86 | 22-AUG-00:10 | 33.30 | 15.93 |
September | 0.481621E+10 | 3612.28 | 19-SEP-13:20 | 33.17 | 16.78 | 0.804779E+09 | 491.85 | 19-SEP-23:10 | 23.85 | 15.15 |
October | 0.427791E+10 | 3750.87 | 18-OCT-13:00 | 27.80 | 18.14 | 0.804875E+09 | 491.86 | 10-OCT-21:10 | 27.80 | 18.14 |
November | 0.312891E+10 | 3487.24 | 10-NOV-12:00 | 21.10 | 12.09 | 0.718155E+09 | 491.81 | 07-NOV-22:40 | 21.10 | 12.09 |
December | 0.218156E+10 | 3219.97 | 21-DEC-12:55 | 8.90 | 2.48 | 0.684811E+09 | 468.05 | 15-DEC-22:19 | 8.90 | 2.48 |
Annual Sum or Average | 0.433851E+11 | 0.918353E+10 | ||||||||
Minimum of Months | 0.218156E+10 | 2431.99 | 4.23 | -2.6 | 0.649135E+09 | 468.05 | 4.23 | -2.6 | ||
Maximum of Months | 0.481621E+10 | 3750.87 | 35.73 | 19.75 | 0.837598E+09 | 491.86 | 33.77 | 19.75 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.273046E+10 | 2549.95 | 04-JAN-22:44 | 4.90 | -1.3 | 0.868205E+09 | 573.82 | 04-JAN-22:00 | 5.00 | -1.3 |
February | 0.256761E+10 | 3206.90 | 08-FEB-22:01 | 3.03 | 0.14 | 0.799143E+09 | 587.74 | 08-FEB-22:10 | 3.03 | 0.14 |
March | 0.295296E+10 | 2819.68 | 20-MAR-22:00 | 6.70 | 1.01 | 0.904057E+09 | 593.28 | 17-MAR-21:49 | 6.70 | 1.01 |
April | 0.326803E+10 | 2086.76 | 28-APR-21:00 | 22.80 | 12.84 | 0.911839E+09 | 570.97 | 10-APR-21:00 | 22.80 | 12.84 |
May | 0.374806E+10 | 2281.44 | 19-MAY-21:00 | 30.00 | 13.65 | 0.959743E+09 | 569.58 | 18-MAY-00:10 | 30.00 | 13.65 |
June | 0.398598E+10 | 2494.28 | 15-JUN-21:00 | 33.30 | 13.72 | 0.937067E+09 | 569.57 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.408894E+10 | 2428.08 | 25-JUL-21:00 | 31.70 | 17.64 | 0.964514E+09 | 569.55 | 05-JUL-21:00 | 31.70 | 17.64 |
August | 0.401846E+10 | 2462.69 | 07-AUG-21:00 | 31.70 | 16.85 | 0.967542E+09 | 569.57 | 22-AUG-00:10 | 24.22 | 16.48 |
September | 0.378948E+10 | 2333.05 | 20-SEP-20:10 | 25.40 | 15.25 | 0.933609E+09 | 569.58 | 19-SEP-04:10 | 25.40 | 15.25 |
October | 0.347631E+10 | 2249.81 | 05-OCT-20:10 | 23.80 | 16.56 | 0.948003E+09 | 569.57 | 10-OCT-21:10 | 14.13 | 9.16 |
November | 0.289593E+10 | 2182.30 | 26-NOV-00:14 | 4.80 | 2.00 | 0.875620E+09 | 572.42 | 17-NOV-00:20 | 4.80 | 2.00 |
December | 0.265180E+10 | 2254.77 | 06-DEC-22:20 | 5.73 | 0.69 | 0.852585E+09 | 565.28 | 06-DEC-23:10 | 5.00 | 0.09 |
Annual Sum or Average | 0.401740E+11 | 0.109219E+11 | ||||||||
Minimum of Months | 0.256761E+10 | 2086.76 | 3.03 | -1.3 | 0.799143E+09 | 565.28 | 3.03 | -1.3 | ||
Maximum of Months | 0.408894E+10 | 3206.90 | 33.30 | 17.64 | 0.967542E+09 | 593.28 | 31.70 | 17.64 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157569E+10 | 1283.31 | 02-JAN-00:33 | 4.83 | 3.01 | 0.169145E+09 | 112.36 | 03-JAN-22:10 | 12.43 | 6.06 |
February | 0.150436E+10 | 1242.12 | 05-FEB-00:17 | 5.93 | 1.82 | 0.157686E+09 | 117.50 | 08-FEB-22:10 | 3.03 | 0.14 |
March | 0.177323E+10 | 1404.18 | 17-MAR-03:44 | 5.87 | -0.4 | 0.181745E+09 | 120.45 | 16-MAR-22:10 | 5.87 | -0.4 |
April | 0.212856E+10 | 1865.10 | 21-APR-20:00 | 26.10 | 11.77 | 0.191258E+09 | 120.55 | 10-APR-21:00 | 26.10 | 11.77 |
May | 0.294918E+10 | 2295.32 | 31-MAY-20:00 | 29.40 | 14.60 | 0.204508E+09 | 120.46 | 18-MAY-00:10 | 29.40 | 14.60 |
June | 0.368893E+10 | 2636.68 | 15-JUN-20:00 | 33.90 | 14.00 | 0.199164E+09 | 120.46 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.379759E+10 | 2583.04 | 03-JUL-20:00 | 28.30 | 19.12 | 0.205006E+09 | 120.46 | 05-JUL-21:00 | 27.80 | 17.53 |
August | 0.348434E+10 | 2509.96 | 07-AUG-20:00 | 31.70 | 17.36 | 0.205741E+09 | 120.46 | 22-AUG-00:10 | 24.22 | 16.48 |
September | 0.293457E+10 | 2190.86 | 22-SEP-20:00 | 26.10 | 18.64 | 0.198255E+09 | 120.46 | 19-SEP-04:19 | 26.10 | 18.64 |
October | 0.229674E+10 | 2052.43 | 05-OCT-20:00 | 23.90 | 16.65 | 0.199101E+09 | 120.46 | 10-OCT-21:10 | 14.13 | 9.16 |
November | 0.172165E+10 | 1347.33 | 26-NOV-00:14 | 4.80 | 2.00 | 0.175611E+09 | 120.45 | 09-NOV-22:19 | 4.80 | 2.00 |
December | 0.150136E+10 | 1121.34 | 30-DEC-10:29 | 4.15 | 0.79 | 0.165399E+09 | 109.04 | 15-DEC-22:10 | 4.15 | 0.79 |
Annual Sum or Average | 0.293562E+11 | 0.225262E+10 | ||||||||
Minimum of Months | 0.150136E+10 | 1121.34 | 4.15 | -0.4 | 0.157686E+09 | 109.04 | 3.03 | -0.4 | ||
Maximum of Months | 0.379759E+10 | 2636.68 | 33.90 | 19.12 | 0.205741E+09 | 120.55 | 29.40 | 18.64 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111166E+10 | 1154.20 | 02-JAN-00:33 | 4.83 | 3.01 | 0.118055E+09 | 74.47 | 04-JAN-23:10 | 4.53 | -1.5 |
February | 0.114778E+10 | 1068.91 | 05-FEB-00:17 | 5.93 | 1.82 | 0.108671E+09 | 77.99 | 08-FEB-22:10 | 3.03 | 0.14 |
March | 0.141544E+10 | 1269.36 | 17-MAR-03:44 | 5.87 | -0.4 | 0.123601E+09 | 79.67 | 16-MAR-21:49 | 5.87 | -0.4 |
April | 0.165013E+10 | 1118.84 | 11-APR-04:30 | 5.30 | 0.69 | 0.130170E+09 | 86.69 | 21-APR-22:10 | 24.13 | 8.96 |
May | 0.190840E+10 | 916.63 | 31-MAY-18:07 | 30.92 | 15.25 | 0.144012E+09 | 91.06 | 31-MAY-22:10 | 27.12 | 13.11 |
June | 0.201197E+10 | 984.89 | 15-JUN-21:00 | 33.30 | 13.72 | 0.146720E+09 | 92.66 | 16-JUN-22:10 | 30.92 | 15.69 |
July | 0.207596E+10 | 976.50 | 03-JUL-10:35 | 34.07 | 18.96 | 0.150776E+09 | 92.66 | 03-JUL-21:19 | 26.50 | 18.67 |
August | 0.202200E+10 | 967.48 | 06-AUG-10:35 | 31.67 | 18.03 | 0.149157E+09 | 92.66 | 07-AUG-21:49 | 29.45 | 17.70 |
September | 0.188204E+10 | 919.71 | 25-SEP-03:12 | 10.93 | 9.15 | 0.140314E+09 | 90.42 | 22-SEP-22:10 | 10.93 | 9.15 |
October | 0.173986E+10 | 1070.36 | 25-OCT-04:07 | 8.12 | 5.97 | 0.136315E+09 | 88.74 | 05-OCT-21:40 | 8.12 | 5.97 |
November | 0.136108E+10 | 1205.92 | 26-NOV-00:14 | 4.80 | 2.00 | 0.119913E+09 | 81.13 | 09-NOV-22:40 | 4.80 | 2.00 |
December | 0.938395E+09 | 976.33 | 09-DEC-23:15 | 5.73 | 1.35 | 0.117407E+09 | 72.69 | 15-DEC-23:10 | 13.80 | 4.57 |
Annual Sum or Average | 0.192647E+11 | 0.158511E+10 | ||||||||
Minimum of Months | 0.938395E+09 | 916.63 | 4.80 | -0.4 | 0.108671E+09 | 72.69 | 3.03 | -1.5 | ||
Maximum of Months | 0.207596E+10 | 1269.36 | 34.07 | 18.96 | 0.150776E+09 | 92.66 | 30.92 | 18.67 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.482120E+11 | 51918.33 | 26-JAN-20:51 | 3.90 | -2.9 | 0.648909E+09 | 545.14 | 20-JAN-00:10 | 3.90 | -2.9 |
February | 0.442190E+11 | 52902.86 | 08-FEB-20:40 | 3.50 | -0.4 | 0.585578E+09 | 578.87 | 15-FEB-23:19 | 5.00 | 1.14 |
March | 0.497726E+11 | 49190.93 | 28-MAR-21:27 | 4.45 | 1.48 | 0.650085E+09 | 522.24 | 17-MAR-21:49 | 4.45 | 1.48 |
April | 0.497882E+11 | 39211.09 | 12-APR-06:38 | 5.57 | 0.02 | 0.628781E+09 | 449.71 | 11-APR-02:00 | 5.57 | 0.02 |
May | 0.527560E+11 | 39365.87 | 30-MAY-20:00 | 28.90 | 14.28 | 0.650702E+09 | 384.96 | 08-MAY-04:30 | 28.90 | 14.28 |
June | 0.521745E+11 | 39770.82 | 15-JUN-20:00 | 33.90 | 14.00 | 0.630917E+09 | 381.86 | 16-JUN-21:10 | 32.52 | 14.90 |
July | 0.536071E+11 | 39720.01 | 03-JUL-20:00 | 28.30 | 19.12 | 0.649368E+09 | 381.85 | 25-JUL-21:10 | 31.42 | 17.57 |
August | 0.534612E+11 | 39636.36 | 04-AUG-20:00 | 33.30 | 17.89 | 0.652107E+09 | 381.87 | 22-AUG-21:10 | 29.22 | 13.60 |
September | 0.511278E+11 | 39287.97 | 20-SEP-20:00 | 25.60 | 15.27 | 0.629090E+09 | 381.89 | 19-SEP-21:10 | 25.60 | 15.27 |
October | 0.511837E+11 | 39041.42 | 05-OCT-20:00 | 23.90 | 16.65 | 0.648537E+09 | 467.89 | 25-OCT-03:20 | 7.57 | 5.72 |
November | 0.477851E+11 | 49602.81 | 27-NOV-21:46 | 2.67 | 0.42 | 0.626167E+09 | 447.60 | 18-NOV-04:49 | 2.67 | 0.42 |
December | 0.478261E+11 | 50674.71 | 29-DEC-22:56 | 2.80 | -0.9 | 0.647794E+09 | 544.65 | 23-DEC-00:20 | 2.80 | -0.9 |
Annual Sum or Average | 0.601913E+12 | 0.764803E+10 | ||||||||
Minimum of Months | 0.442190E+11 | 39041.42 | 2.67 | -2.9 | 0.585578E+09 | 381.85 | 2.67 | -2.9 | ||
Maximum of Months | 0.536071E+11 | 52902.86 | 33.90 | 19.12 | 0.652107E+09 | 578.87 | 32.52 | 17.57 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.192331E+11 | 14942.01 | 02-JAN-00:33 | 4.83 | 3.01 | 0.948591E+10 | 6775.40 | 02-JAN-00:40 | 4.83 | 3.01 |
February | 0.180006E+11 | 14006.05 | 05-FEB-00:17 | 5.93 | 1.82 | 0.868327E+10 | 6636.08 | 15-FEB-23:19 | 5.00 | 1.14 |
March | 0.199287E+11 | 15671.14 | 17-MAR-03:44 | 5.87 | -0.4 | 0.967762E+10 | 6562.40 | 17-MAR-21:49 | 6.83 | 0.34 |
April | 0.209109E+11 | 13392.31 | 11-APR-04:30 | 5.30 | 0.69 | 0.973578E+10 | 6472.15 | 11-APR-02:00 | 5.30 | 0.69 |
May | 0.226871E+11 | 11195.62 | 19-MAY-21:10 | 29.90 | 13.55 | 0.103056E+11 | 6460.84 | 08-MAY-22:40 | 29.90 | 13.55 |
June | 0.236288E+11 | 11957.56 | 15-JUN-21:10 | 32.57 | 13.55 | 0.102480E+11 | 6461.65 | 21-JUN-01:49 | 24.72 | 16.02 |
July | 0.244372E+11 | 11819.14 | 26-JUL-21:10 | 28.62 | 18.19 | 0.105619E+11 | 6461.05 | 05-JUL-21:00 | 28.62 | 18.19 |
August | 0.244951E+11 | 12366.60 | 07-AUG-21:10 | 31.25 | 17.07 | 0.106417E+11 | 6461.61 | 11-AUG-03:00 | 24.40 | 15.32 |
September | 0.240043E+11 | 12330.40 | 20-SEP-15:03 | 33.30 | 17.34 | 0.103034E+11 | 6461.45 | 19-SEP-23:10 | 33.30 | 17.34 |
October | 0.235115E+11 | 12897.92 | 25-OCT-04:07 | 8.12 | 5.97 | 0.103661E+11 | 6619.13 | 25-OCT-03:20 | 8.12 | 5.97 |
November | 0.203937E+11 | 14769.65 | 26-NOV-00:14 | 4.80 | 2.00 | 0.953667E+10 | 6522.56 | 18-NOV-05:40 | 4.80 | 2.00 |
December | 0.187113E+11 | 20257.70 | 23-DEC-00:33 | 5.40 | 0.46 | 0.931828E+10 | 6681.66 | 23-DEC-00:20 | 5.40 | 0.46 |
Annual Sum or Average | 0.259942E+12 | 0.118864E+12 | ||||||||
Minimum of Months | 0.180006E+11 | 11195.62 | 4.80 | -0.4 | 0.868327E+10 | 6460.84 | 4.80 | 0.34 | ||
Maximum of Months | 0.244951E+11 | 20257.70 | 33.30 | 18.19 | 0.106417E+11 | 6775.40 | 33.30 | 18.19 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.597417E+11 | 62095.90 | 20-JAN-00:05 | 4.32 | 2.79 | 0.304518E+11 | 20143.63 | 20-JAN-00:10 | 4.32 | 2.79 |
February | 0.556075E+11 | 62404.06 | 17-FEB-01:00 | 5.00 | 1.32 | 0.278435E+11 | 20175.91 | 15-FEB-23:19 | 5.00 | 1.32 |
March | 0.627758E+11 | 61348.30 | 20-MAR-22:00 | 6.70 | 1.01 | 0.311638E+11 | 20215.93 | 17-MAR-21:49 | 6.70 | 1.01 |
April | 0.671549E+11 | 62847.71 | 11-APR-04:15 | 5.40 | 0.74 | 0.308191E+11 | 19981.42 | 11-APR-02:00 | 5.40 | 0.74 |
May | 0.751855E+11 | 41462.75 | 31-MAY-21:10 | 28.13 | 13.59 | 0.321684E+11 | 19229.78 | 08-MAY-04:30 | 28.13 | 13.59 |
June | 0.788825E+11 | 44225.37 | 15-JUN-21:10 | 32.57 | 13.55 | 0.313739E+11 | 19185.06 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.814125E+11 | 43583.03 | 26-JUL-21:10 | 28.62 | 18.19 | 0.323119E+11 | 19184.37 | 05-JUL-21:00 | 28.62 | 18.19 |
August | 0.806463E+11 | 44431.94 | 07-AUG-21:10 | 31.25 | 17.07 | 0.324523E+11 | 19185.43 | 22-AUG-00:10 | 24.22 | 16.48 |
September | 0.766084E+11 | 42454.93 | 21-SEP-21:10 | 26.10 | 17.46 | 0.313752E+11 | 19185.93 | 19-SEP-04:10 | 26.10 | 17.46 |
October | 0.728435E+11 | 41653.58 | 05-OCT-21:10 | 23.22 | 16.17 | 0.321607E+11 | 20122.22 | 25-OCT-03:20 | 7.57 | 5.72 |
November | 0.624212E+11 | 60457.17 | 11-NOV-06:10 | 5.73 | 3.72 | 0.303003E+11 | 19995.56 | 17-NOV-00:20 | 5.03 | 0.87 |
December | 0.583578E+11 | 53643.45 | 29-DEC-22:56 | 2.80 | -0.9 | 0.300882E+11 | 20143.36 | 23-DEC-00:20 | 2.80 | -0.9 |
Annual Sum or Average | 0.831638E+12 | 0.372509E+12 | ||||||||
Minimum of Months | 0.556075E+11 | 41462.75 | 2.80 | -0.9 | 0.278435E+11 | 19184.37 | 2.80 | -0.9 | ||
Maximum of Months | 0.814125E+11 | 62847.71 | 32.57 | 18.19 | 0.324523E+11 | 20215.93 | 28.62 | 18.19 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285635E+09 | 3247.51 | 03-JAN-16:01 | 20.10 | 7.84 | 96150093.52 | 56.69 | 01-JAN-05:49 | 20.10 | 7.84 |
February | 0.413089E+09 | 3439.09 | 20-FEB-16:01 | 23.12 | 8.59 | 87418641.31 | 56.69 | 06-FEB-23:10 | 23.12 | 8.59 |
March | 0.715846E+09 | 3456.16 | 21-MAR-15:01 | 24.50 | 9.45 | 97552836.46 | 56.69 | 06-MAR-22:40 | 24.50 | 9.45 |
April | 0.155336E+10 | 3568.37 | 16-APR-15:01 | 29.50 | 11.50 | 95275747.72 | 56.69 | 28-APR-21:00 | 21.70 | 12.89 |
May | 0.228159E+10 | 3588.67 | 20-MAY-15:01 | 32.20 | 15.53 | 98871201.10 | 56.69 | 23-MAY-23:19 | 19.63 | 15.09 |
June | 0.276725E+10 | 3584.50 | 15-JUN-15:02 | 38.22 | 15.87 | 95943685.26 | 56.70 | 16-JUN-21:00 | 31.10 | 15.68 |
July | 0.276541E+10 | 3230.66 | 11-JUL-08:61 | 27.48 | 17.81 | 99030715.49 | 56.70 | 31-JUL-21:30 | 30.10 | 17.72 |
August | 0.260916E+10 | 3214.32 | 08-AUG-18:01 | 29.22 | 19.49 | 99055496.15 | 56.70 | 09-AUG-21:10 | 28.03 | 17.04 |
September | 0.237919E+10 | 3586.97 | 30-SEP-15:01 | 28.30 | 13.14 | 95727797.28 | 56.70 | 13-SEP-02:30 | 28.30 | 13.14 |
October | 0.165710E+10 | 3558.55 | 21-OCT-15:01 | 26.10 | 12.52 | 98476830.96 | 56.70 | 05-OCT-00:00 | 26.10 | 12.52 |
November | 0.693615E+09 | 3447.44 | 09-NOV-16:01 | 23.22 | 12.98 | 94156735.27 | 56.69 | 01-NOV-01:10 | 23.22 | 12.98 |
December | 0.198656E+09 | 3117.46 | 23-DEC-16:01 | 16.73 | 6.11 | 95839056.47 | 56.69 | 18-DEC-04:19 | 16.73 | 6.11 |
Annual Sum or Average | 0.183199E+11 | 0.115350E+10 | ||||||||
Minimum of Months | 0.198656E+09 | 3117.46 | 16.73 | 6.11 | 87418641.31 | 56.69 | 16.73 | 6.11 | ||
Maximum of Months | 0.276725E+10 | 3588.67 | 38.22 | 19.49 | 99055496.15 | 56.70 | 31.10 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110826E+09 | 3111.70 | 12-JAN-16:01 | 18.72 | 10.12 | 94420758.77 | 56.69 | 21-JAN-03:09 | 5.60 | 2.53 |
February | 0.197621E+09 | 3368.39 | 20-FEB-16:01 | 23.12 | 8.59 | 86088979.89 | 56.69 | 11-FEB-04:49 | 23.12 | 8.59 |
March | 0.476275E+09 | 3389.10 | 21-MAR-15:01 | 24.50 | 9.45 | 96648030.36 | 56.69 | 16-MAR-21:10 | 24.50 | 9.45 |
April | 0.136600E+10 | 3526.43 | 30-APR-18:01 | 29.63 | 12.67 | 95020930.41 | 56.69 | 28-APR-21:40 | 29.63 | 12.67 |
May | 0.223149E+10 | 3561.12 | 20-MAY-18:01 | 31.52 | 15.16 | 98841412.71 | 56.70 | 28-MAY-00:10 | 21.02 | 16.91 |
June | 0.278115E+10 | 3568.43 | 15-JUN-18:02 | 35.92 | 14.47 | 95968225.21 | 56.70 | 27-JUN-21:19 | 28.33 | 16.38 |
July | 0.275250E+10 | 3198.73 | 11-JUL-08:61 | 27.48 | 17.81 | 99043307.74 | 56.70 | 26-JUL-21:30 | 28.05 | 18.23 |
August | 0.247435E+10 | 3207.09 | 08-AUG-18:01 | 29.22 | 19.49 | 99022307.06 | 56.70 | 04-AUG-21:30 | 29.22 | 19.49 |
September | 0.203873E+10 | 3525.56 | 30-SEP-15:01 | 28.30 | 13.14 | 95590204.00 | 56.70 | 13-SEP-00:49 | 28.30 | 13.14 |
October | 0.120338E+10 | 3487.99 | 21-OCT-15:01 | 26.10 | 12.52 | 97903552.51 | 56.69 | 04-OCT-23:10 | 26.10 | 12.52 |
November | 0.311548E+09 | 3380.84 | 09-NOV-16:01 | 23.22 | 12.98 | 92898871.92 | 56.69 | 01-NOV-00:00 | 23.22 | 12.98 |
December | 78055155.24 | 2896.50 | 16-DEC-16:02 | 14.72 | 4.08 | 93995847.71 | 56.69 | 14-DEC-22:40 | 14.72 | 4.08 |
Annual Sum or Average | 0.160219E+11 | 0.114544E+10 | ||||||||
Minimum of Months | 78055155.24 | 2896.50 | 14.72 | 4.08 | 86088979.89 | 56.69 | 5.60 | 2.53 | ||
Maximum of Months | 0.278115E+10 | 3568.43 | 35.92 | 19.49 | 99043307.74 | 56.70 | 29.63 | 19.49 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.382642E+09 | 558.38 | 12-JAN-14:30 | 18.60 | 9.87 | 0.00 | 0.00 | 01-JAN-00:10 | 18.60 | 9.87 |
February | 0.365942E+09 | 539.78 | 07-FEB-13:40 | 20.20 | 9.50 | 0.00 | 0.00 | 01-FEB-00:10 | 20.20 | 9.50 |
March | 0.348948E+09 | 439.99 | 16-MAR-13:30 | 22.50 | 9.16 | 0.00 | 0.00 | 01-MAR-00:10 | 22.50 | 9.16 |
April | 0.462105E+09 | 426.99 | 04-APR-13:30 | 26.95 | 10.78 | 0.00 | 0.00 | 01-APR-00:10 | 26.95 | 10.78 |
May | 0.565659E+09 | 383.28 | 19-MAY-20:20 | 30.73 | 14.26 | 0.00 | 0.00 | 01-MAY-00:10 | 30.73 | 14.26 |
June | 0.692993E+09 | 441.43 | 15-JUN-17:13 | 36.83 | 15.02 | 0.00 | 0.00 | 01-JUN-00:10 | 36.83 | 15.02 |
July | 0.729244E+09 | 441.85 | 26-JUL-17:17 | 35.20 | 19.91 | 0.00 | 0.00 | 01-JUL-00:10 | 35.20 | 19.91 |
August | 0.739556E+09 | 495.40 | 27-AUG-13:40 | 34.40 | 16.46 | 0.00 | 0.00 | 01-AUG-00:10 | 34.40 | 16.46 |
September | 0.774132E+09 | 600.10 | 19-SEP-13:30 | 33.35 | 16.80 | 0.00 | 0.00 | 01-SEP-00:10 | 33.35 | 16.80 |
October | 0.695190E+09 | 668.60 | 22-OCT-13:20 | 25.97 | 14.61 | 0.00 | 0.00 | 01-OCT-00:10 | 25.97 | 14.61 |
November | 0.518481E+09 | 624.97 | 09-NOV-13:50 | 23.22 | 12.39 | 0.00 | 0.00 | 01-NOV-00:10 | 23.22 | 12.39 |
December | 0.340085E+09 | 472.07 | 16-DEC-14:10 | 15.00 | 4.30 | 0.00 | 0.00 | 01-DEC-00:10 | 15.00 | 4.30 |
Annual Sum or Average | 0.661498E+10 | 0.00 | ||||||||
Minimum of Months | 0.340085E+09 | 383.28 | 15.00 | 4.30 | 0.00 | 0.00 | 15.00 | 4.30 | ||
Maximum of Months | 0.774132E+09 | 668.60 | 36.83 | 19.91 | 0.00 | 0.00 | 36.83 | 19.91 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100715E+09 | 676.35 | 15-JAN-09:01 | 7.88 | 7.51 | 94848498.37 | 56.69 | 03-JAN-22:10 | 7.88 | 7.51 |
February | 0.152337E+09 | 971.53 | 20-FEB-09:01 | 11.23 | 4.20 | 86037019.95 | 56.69 | 06-FEB-22:19 | 11.23 | 4.20 |
March | 0.268801E+09 | 1093.48 | 21-MAR-18:01 | 22.57 | 8.48 | 95927964.97 | 56.69 | 16-MAR-21:19 | 22.57 | 8.48 |
April | 0.537161E+09 | 1232.45 | 21-APR-18:01 | 29.95 | 11.64 | 93859433.61 | 56.69 | 28-APR-21:10 | 22.62 | 12.85 |
May | 0.805025E+09 | 1236.05 | 20-MAY-18:01 | 31.52 | 15.16 | 97972273.51 | 56.69 | 28-MAY-01:39 | 20.20 | 16.18 |
June | 0.983590E+09 | 1237.53 | 02-JUN-18:01 | 36.83 | 15.80 | 95465629.24 | 56.69 | 02-JUN-21:10 | 31.52 | 14.93 |
July | 0.999974E+09 | 1152.04 | 26-JUL-15:02 | 36.60 | 20.09 | 98514902.56 | 56.69 | 05-JUL-21:00 | 36.60 | 20.09 |
August | 0.893606E+09 | 1150.75 | 04-AUG-15:02 | 35.68 | 19.44 | 98287014.26 | 56.69 | 30-AUG-21:10 | 25.68 | 16.75 |
September | 0.714015E+09 | 1205.75 | 11-SEP-18:01 | 27.65 | 13.06 | 94554218.31 | 56.69 | 01-SEP-21:10 | 27.65 | 13.06 |
October | 0.494290E+09 | 1127.84 | 19-OCT-18:01 | 22.62 | 11.36 | 96682787.57 | 56.69 | 04-OCT-23:19 | 22.62 | 11.36 |
November | 0.182761E+09 | 1052.74 | 08-NOV-19:01 | 20.92 | 10.67 | 92336690.49 | 56.69 | 01-NOV-01:10 | 20.92 | 10.67 |
December | 83320400.75 | 833.91 | 09-DEC-09:02 | 14.40 | 6.77 | 94622874.72 | 56.69 | 12-DEC-23:49 | 6.20 | 4.93 |
Annual Sum or Average | 0.621560E+10 | 0.113911E+10 | ||||||||
Minimum of Months | 83320400.75 | 676.35 | 7.88 | 4.20 | 86037019.95 | 56.69 | 6.20 | 4.20 | ||
Maximum of Months | 0.999974E+09 | 1237.53 | 36.83 | 20.09 | 98514902.56 | 56.69 | 36.60 | 20.09 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.271148E+09 | 2836.05 | 12-JAN-16:01 | 18.72 | 10.12 | 96265176.53 | 56.69 | 21-JAN-03:09 | 5.60 | 2.53 |
February | 0.460113E+09 | 3000.13 | 20-FEB-16:01 | 23.12 | 8.59 | 87857806.39 | 56.69 | 07-FEB-23:10 | 23.12 | 8.59 |
March | 0.732529E+09 | 3029.28 | 21-MAR-15:01 | 24.50 | 9.45 | 97975218.45 | 56.69 | 16-MAR-22:40 | 24.50 | 9.45 |
April | 0.161755E+10 | 3119.04 | 03-APR-15:01 | 26.88 | 11.50 | 95728645.48 | 56.69 | 18-APR-21:19 | 21.83 | 14.00 |
May | 0.231416E+10 | 3137.75 | 20-MAY-15:01 | 32.20 | 15.53 | 99159954.62 | 56.69 | 23-MAY-00:40 | 22.20 | 15.41 |
June | 0.283039E+10 | 3174.63 | 15-JUN-08:61 | 29.78 | 13.66 | 96022855.14 | 56.70 | 16-JUN-22:10 | 30.92 | 15.69 |
July | 0.282432E+10 | 2881.59 | 31-JUL-08:61 | 24.87 | 18.88 | 99117343.68 | 56.70 | 31-JUL-21:00 | 29.60 | 17.58 |
August | 0.265817E+10 | 2900.48 | 03-AUG-08:61 | 26.28 | 20.18 | 99163845.09 | 56.70 | 02-AUG-21:10 | 26.28 | 20.18 |
September | 0.238203E+10 | 3132.17 | 30-SEP-15:01 | 28.30 | 13.14 | 95907792.30 | 56.69 | 08-SEP-23:40 | 28.30 | 13.14 |
October | 0.156228E+10 | 3108.16 | 21-OCT-15:01 | 26.10 | 12.52 | 98591555.18 | 56.69 | 03-OCT-23:19 | 26.10 | 12.52 |
November | 0.664489E+09 | 3013.95 | 09-NOV-16:01 | 23.22 | 12.98 | 94448995.94 | 56.69 | 01-NOV-01:49 | 23.22 | 12.98 |
December | 0.216251E+09 | 2696.77 | 16-DEC-09:02 | 8.48 | 2.42 | 95938930.95 | 56.69 | 01-DEC-04:49 | 8.48 | 2.42 |
Annual Sum or Average | 0.185334E+11 | 0.115618E+10 | ||||||||
Minimum of Months | 0.216251E+09 | 2696.77 | 8.48 | 2.42 | 87857806.39 | 56.69 | 5.60 | 2.42 | ||
Maximum of Months | 0.283039E+10 | 3174.63 | 32.20 | 20.18 | 99163845.09 | 56.70 | 30.92 | 20.18 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 94656722.00 | 2276.70 | 04-JAN-09:02 | 8.98 | 3.34 | 94370545.08 | 56.69 | 01-JAN-05:10 | 8.98 | 3.34 |
February | 0.225249E+09 | 2849.07 | 21-FEB-16:01 | 22.70 | 8.11 | 86422775.51 | 56.69 | 26-FEB-05:49 | 7.88 | 4.10 |
March | 0.487446E+09 | 2966.97 | 22-MAR-15:01 | 23.90 | 8.87 | 97055478.86 | 56.69 | 22-MAR-21:10 | 11.52 | 4.66 |
April | 0.141806E+10 | 3087.53 | 30-APR-18:01 | 29.63 | 12.67 | 95606264.69 | 56.69 | 28-APR-21:49 | 29.63 | 12.67 |
May | 0.226101E+10 | 3111.84 | 20-MAY-15:01 | 32.20 | 15.53 | 99156055.24 | 56.69 | 22-MAY-01:10 | 20.60 | 14.61 |
June | 0.284476E+10 | 3155.16 | 15-JUN-08:61 | 29.78 | 13.66 | 96024892.87 | 56.70 | 02-JUN-21:49 | 29.78 | 13.66 |
July | 0.281112E+10 | 2853.82 | 30-JUL-18:01 | 28.80 | 20.02 | 99117770.92 | 56.70 | 27-JUL-21:40 | 28.80 | 20.02 |
August | 0.251977E+10 | 2886.28 | 08-AUG-18:01 | 29.22 | 19.49 | 99156218.45 | 56.70 | 04-AUG-22:19 | 29.22 | 19.49 |
September | 0.203054E+10 | 3077.04 | 30-SEP-15:01 | 28.30 | 13.14 | 95872454.28 | 56.69 | 13-SEP-02:39 | 28.30 | 13.14 |
October | 0.109309E+10 | 3043.82 | 21-OCT-15:01 | 26.10 | 12.52 | 98169487.98 | 56.69 | 03-OCT-22:19 | 26.10 | 12.52 |
November | 0.298310E+09 | 2888.40 | 09-NOV-16:01 | 23.22 | 12.98 | 92859089.26 | 56.69 | 01-NOV-00:00 | 23.22 | 12.98 |
December | 78997582.71 | 2481.58 | 09-DEC-09:02 | 14.40 | 6.77 | 94013451.98 | 56.69 | 29-DEC-23:10 | 2.33 | -1.1 |
Annual Sum or Average | 0.161630E+11 | 0.114782E+10 | ||||||||
Minimum of Months | 78997582.71 | 2276.70 | 8.98 | 3.34 | 86422775.51 | 56.69 | 2.33 | -1.1 | ||
Maximum of Months | 0.284476E+10 | 3155.16 | 32.20 | 20.02 | 99156218.45 | 56.70 | 29.78 | 20.02 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.308284E+10 | 2569.02 | 02-JAN-00:33 | 4.83 | 3.01 | 0.130882E+10 | 848.26 | 04-JAN-23:10 | 4.53 | -1.5 |
February | 0.297505E+10 | 2469.44 | 05-FEB-00:17 | 5.93 | 1.82 | 0.122662E+10 | 879.04 | 22-FEB-22:40 | 14.40 | 4.97 |
March | 0.349436E+10 | 2808.05 | 17-MAR-03:44 | 5.87 | -0.4 | 0.141074E+10 | 904.25 | 16-MAR-21:40 | 5.87 | -0.4 |
April | 0.391952E+10 | 2501.63 | 11-APR-04:30 | 5.30 | 0.69 | 0.148546E+10 | 951.82 | 28-APR-22:49 | 20.78 | 12.73 |
May | 0.473900E+10 | 2978.06 | 19-MAY-18:30 | 32.75 | 15.27 | 0.160508E+10 | 951.86 | 18-MAY-00:10 | 32.75 | 15.27 |
June | 0.540017E+10 | 3484.42 | 15-JUN-18:30 | 35.55 | 14.53 | 0.157207E+10 | 951.87 | 30-JUN-22:30 | 28.30 | 17.29 |
July | 0.548208E+10 | 3338.51 | 26-JUL-18:30 | 32.50 | 19.69 | 0.161820E+10 | 951.86 | 05-JUL-21:00 | 32.50 | 19.69 |
August | 0.529368E+10 | 3246.25 | 07-AUG-18:30 | 33.05 | 18.14 | 0.162114E+10 | 951.87 | 22-AUG-00:10 | 24.22 | 16.48 |
September | 0.488675E+10 | 2954.46 | 20-SEP-18:15 | 30.40 | 15.98 | 0.156259E+10 | 951.86 | 18-SEP-01:10 | 30.40 | 15.98 |
October | 0.425151E+10 | 2774.72 | 05-OCT-20:10 | 23.80 | 16.56 | 0.156049E+10 | 951.85 | 05-OCT-23:49 | 20.65 | 16.69 |
November | 0.345792E+10 | 2685.56 | 26-NOV-00:14 | 4.80 | 2.00 | 0.138368E+10 | 926.76 | 01-NOV-00:10 | 4.80 | 2.00 |
December | 0.291828E+10 | 2351.43 | 30-DEC-10:29 | 4.15 | 0.79 | 0.127698E+10 | 802.01 | 15-DEC-22:49 | 4.15 | 0.79 |
Annual Sum or Average | 0.499012E+11 | 0.176319E+11 | ||||||||
Minimum of Months | 0.291828E+10 | 2351.43 | 4.15 | -0.4 | 0.122662E+10 | 802.01 | 4.15 | -1.5 | ||
Maximum of Months | 0.548208E+10 | 3484.42 | 35.55 | 19.69 | 0.162114E+10 | 951.87 | 32.75 | 19.69 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.216786E+09 | 3420.04 | 12-JAN-16:01 | 18.72 | 10.12 | 95518917.43 | 56.69 | 21-JAN-03:09 | 5.60 | 2.53 |
February | 0.328457E+09 | 3634.62 | 20-FEB-16:01 | 23.12 | 8.59 | 86929961.00 | 56.69 | 06-FEB-23:10 | 23.12 | 8.59 |
March | 0.586881E+09 | 3648.58 | 21-MAR-15:01 | 24.50 | 9.45 | 97122807.41 | 56.69 | 16-MAR-22:10 | 24.50 | 9.45 |
April | 0.143264E+10 | 3783.45 | 16-APR-15:01 | 29.50 | 11.50 | 95074243.74 | 56.69 | 28-APR-21:30 | 22.25 | 12.88 |
May | 0.221703E+10 | 3804.08 | 20-MAY-15:01 | 32.20 | 15.53 | 98768938.67 | 56.70 | 24-MAY-21:19 | 21.67 | 16.43 |
June | 0.283893E+10 | 3804.09 | 15-JUN-15:02 | 38.22 | 15.87 | 95924675.11 | 56.70 | 21-JUN-00:30 | 24.45 | 15.79 |
July | 0.283459E+10 | 3408.84 | 18-JUL-18:02 | 30.40 | 21.72 | 99002160.22 | 56.70 | 31-JUL-21:10 | 30.43 | 17.80 |
August | 0.263096E+10 | 3392.37 | 07-AUG-08:61 | 28.48 | 17.49 | 99001330.84 | 56.70 | 07-AUG-21:40 | 29.90 | 17.57 |
September | 0.232093E+10 | 3795.06 | 30-SEP-15:01 | 28.30 | 13.14 | 95628999.67 | 56.70 | 13-SEP-00:20 | 28.30 | 13.14 |
October | 0.145179E+10 | 3764.56 | 21-OCT-15:01 | 26.10 | 12.52 | 98207312.13 | 56.70 | 04-OCT-22:00 | 26.10 | 12.52 |
November | 0.530755E+09 | 3643.32 | 09-NOV-16:01 | 23.22 | 12.98 | 93654932.52 | 56.69 | 01-NOV-01:10 | 23.22 | 12.98 |
December | 0.152729E+09 | 3286.20 | 23-DEC-16:01 | 16.73 | 6.11 | 95214626.15 | 56.69 | 18-DEC-04:19 | 16.73 | 6.11 |
Annual Sum or Average | 0.175425E+11 | 0.115005E+10 | ||||||||
Minimum of Months | 0.152729E+09 | 3286.20 | 16.73 | 6.11 | 86929961.00 | 56.69 | 5.60 | 2.53 | ||
Maximum of Months | 0.283893E+10 | 3804.09 | 38.22 | 21.72 | 99002160.22 | 56.70 | 30.43 | 17.80 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 80216450.64 | 3236.63 | 12-JAN-16:01 | 18.72 | 10.12 | 93701069.58 | 56.69 | 18-JAN-04:40 | 5.93 | 4.12 |
February | 0.149251E+09 | 3547.18 | 20-FEB-16:01 | 23.12 | 8.59 | 85506666.74 | 56.69 | 17-FEB-01:10 | 23.12 | 8.59 |
March | 0.372202E+09 | 3566.03 | 21-MAR-15:01 | 24.50 | 9.45 | 96120504.77 | 56.69 | 16-MAR-22:30 | 24.50 | 9.45 |
April | 0.124054E+10 | 3732.07 | 16-APR-15:01 | 29.50 | 11.50 | 94802244.03 | 56.69 | 17-APR-01:19 | 18.13 | 13.06 |
May | 0.216452E+10 | 3769.84 | 20-MAY-15:01 | 32.20 | 15.53 | 98737256.25 | 56.70 | 23-MAY-22:10 | 20.92 | 15.65 |
June | 0.285305E+10 | 3778.58 | 15-JUN-18:02 | 35.92 | 14.47 | 95956798.64 | 56.70 | 19-JUN-02:20 | 24.03 | 16.43 |
July | 0.282089E+10 | 3388.15 | 18-JUL-18:02 | 30.40 | 21.72 | 99016759.20 | 56.70 | 24-JUL-21:10 | 29.63 | 17.48 |
August | 0.248948E+10 | 3371.89 | 08-AUG-18:01 | 29.22 | 19.49 | 98965886.91 | 56.70 | 02-AUG-22:49 | 29.22 | 19.49 |
September | 0.196292E+10 | 3722.01 | 30-SEP-15:01 | 28.30 | 13.14 | 95476428.47 | 56.70 | 21-SEP-23:00 | 28.30 | 13.14 |
October | 0.989675E+09 | 3679.37 | 21-OCT-15:01 | 26.10 | 12.52 | 97539880.73 | 56.70 | 04-OCT-22:10 | 26.10 | 12.52 |
November | 0.212110E+09 | 3559.50 | 09-NOV-16:01 | 23.22 | 12.98 | 92207113.88 | 56.69 | 03-NOV-21:19 | 23.22 | 12.98 |
December | 58952495.12 | 2964.76 | 16-DEC-16:02 | 14.72 | 4.08 | 93334228.17 | 56.69 | 09-DEC-04:19 | 14.72 | 4.08 |
Annual Sum or Average | 0.153938E+11 | 0.114136E+10 | ||||||||
Minimum of Months | 58952495.12 | 2964.76 | 14.72 | 4.08 | 85506666.74 | 56.69 | 5.93 | 4.08 | ||
Maximum of Months | 0.285305E+10 | 3778.58 | 35.92 | 21.72 | 99016759.20 | 56.70 | 29.63 | 19.49 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.544697E+09 | 1772.29 | 03-JAN-16:01 | 20.10 | 7.84 | 97526369.74 | 56.69 | 03-JAN-22:10 | 12.43 | 6.06 |
February | 0.554519E+09 | 1855.93 | 20-FEB-16:01 | 23.12 | 8.59 | 88364601.98 | 56.69 | 07-FEB-22:30 | 23.12 | 8.59 |
March | 0.569408E+09 | 1866.12 | 14-MAR-15:01 | 23.98 | 9.90 | 97897156.09 | 56.69 | 22-MAR-21:10 | 11.52 | 4.66 |
April | 0.869398E+09 | 1906.52 | 03-APR-15:01 | 26.88 | 11.50 | 95178159.90 | 56.69 | 18-APR-21:30 | 21.65 | 13.85 |
May | 0.113006E+10 | 1902.35 | 20-MAY-15:01 | 32.20 | 15.53 | 98718357.67 | 56.69 | 21-MAY-23:10 | 21.60 | 15.78 |
June | 0.142070E+10 | 1900.33 | 02-JUN-18:01 | 36.83 | 15.80 | 95821156.58 | 56.69 | 21-JUN-02:30 | 24.45 | 15.96 |
July | 0.148224E+10 | 1743.60 | 14-JUL-18:02 | 29.27 | 18.93 | 98947490.60 | 56.70 | 03-JUL-21:30 | 29.27 | 18.93 |
August | 0.148114E+10 | 1739.45 | 08-AUG-18:01 | 29.22 | 19.49 | 98970018.78 | 56.70 | 04-AUG-22:10 | 29.22 | 19.49 |
September | 0.149027E+10 | 1924.95 | 30-SEP-15:01 | 28.30 | 13.14 | 95696759.47 | 56.70 | 12-SEP-21:30 | 28.30 | 13.14 |
October | 0.125409E+10 | 1922.88 | 21-OCT-15:01 | 26.10 | 12.52 | 98549408.89 | 56.69 | 05-OCT-02:49 | 26.10 | 12.52 |
November | 0.809384E+09 | 1864.39 | 09-NOV-16:01 | 23.22 | 12.98 | 94839588.69 | 56.69 | 08-NOV-23:19 | 23.22 | 12.98 |
December | 0.494094E+09 | 1701.11 | 23-DEC-16:01 | 16.73 | 6.11 | 97484083.53 | 56.69 | 21-DEC-22:40 | 16.73 | 6.11 |
Annual Sum or Average | 0.121000E+11 | 0.115799E+10 | ||||||||
Minimum of Months | 0.494094E+09 | 1701.11 | 16.73 | 6.11 | 88364601.98 | 56.69 | 11.52 | 4.66 | ||
Maximum of Months | 0.149027E+10 | 1924.95 | 36.83 | 19.49 | 98970018.78 | 56.70 | 29.27 | 19.49 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.349403E+11 | 31715.93 | 31-JAN-23:56 | 6.70 | 1.99 | 0.174017E+11 | 13119.25 | 20-JAN-00:10 | 6.70 | 1.99 |
February | 0.327280E+11 | 32423.09 | 15-FEB-23:57 | 5.00 | 1.14 | 0.159706E+11 | 13238.58 | 15-FEB-23:19 | 5.00 | 1.14 |
March | 0.378219E+11 | 31224.39 | 06-MAR-05:33 | 5.77 | 1.16 | 0.180900E+11 | 12834.43 | 17-MAR-21:49 | 6.83 | 0.34 |
April | 0.402817E+11 | 31628.14 | 10-APR-22:40 | 7.40 | 1.81 | 0.180173E+11 | 12714.45 | 11-APR-02:00 | 6.10 | 0.79 |
May | 0.445641E+11 | 22834.90 | 31-MAY-21:10 | 28.13 | 13.59 | 0.189081E+11 | 11346.54 | 18-MAY-00:10 | 28.13 | 13.59 |
June | 0.457855E+11 | 23624.35 | 15-JUN-21:10 | 32.57 | 13.55 | 0.184634E+11 | 11350.19 | 06-JUN-22:00 | 32.57 | 13.55 |
July | 0.470199E+11 | 23302.86 | 26-JUL-21:10 | 28.62 | 18.19 | 0.189956E+11 | 11356.74 | 25-JUL-22:00 | 28.62 | 18.19 |
August | 0.460691E+11 | 23491.52 | 07-AUG-21:10 | 31.25 | 17.07 | 0.190214E+11 | 11353.41 | 04-AUG-22:00 | 31.25 | 17.07 |
September | 0.428234E+11 | 22133.37 | 22-SEP-22:00 | 25.00 | 17.90 | 0.182290E+11 | 11346.57 | 19-SEP-04:10 | 25.00 | 17.90 |
October | 0.410092E+11 | 23528.26 | 25-OCT-04:07 | 8.12 | 5.97 | 0.185055E+11 | 12670.91 | 25-OCT-03:20 | 8.12 | 5.97 |
November | 0.356776E+11 | 31188.99 | 15-NOV-23:33 | 5.37 | 2.41 | 0.172196E+11 | 12351.78 | 18-NOV-05:40 | 6.47 | 0.95 |
December | 0.342633E+11 | 31123.70 | 11-DEC-24:00 | 5.00 | 1.72 | 0.172280E+11 | 12647.32 | 23-DEC-00:20 | 5.20 | 0.42 |
Annual Sum or Average | 0.482984E+12 | 0.216050E+12 | ||||||||
Minimum of Months | 0.327280E+11 | 22133.37 | 5.00 | 1.14 | 0.159706E+11 | 11346.54 | 5.00 | 0.34 | ||
Maximum of Months | 0.470199E+11 | 32423.09 | 32.57 | 18.19 | 0.190214E+11 | 13238.58 | 32.57 | 18.19 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.372258E+11 | 33452.42 | 31-JAN-23:56 | 6.70 | 1.99 | 0.180142E+11 | 13226.15 | 20-JAN-00:10 | 6.70 | 1.99 |
February | 0.347269E+11 | 34429.07 | 15-FEB-23:57 | 5.00 | 1.14 | 0.164684E+11 | 13388.85 | 15-FEB-23:19 | 5.00 | 1.14 |
March | 0.400058E+11 | 41485.29 | 17-MAR-04:10 | 5.32 | -0.8 | 0.185726E+11 | 12906.22 | 17-MAR-21:49 | 6.83 | 0.34 |
April | 0.423169E+11 | 33198.84 | 10-APR-22:40 | 7.40 | 1.81 | 0.182811E+11 | 12889.98 | 11-APR-02:00 | 6.10 | 0.79 |
May | 0.467318E+11 | 24215.24 | 31-MAY-21:10 | 28.13 | 13.59 | 0.190854E+11 | 11406.14 | 08-MAY-04:30 | 28.13 | 13.59 |
June | 0.479740E+11 | 24968.40 | 15-JUN-21:20 | 31.83 | 13.36 | 0.186053E+11 | 11370.81 | 06-JUN-22:00 | 31.83 | 13.36 |
July | 0.492678E+11 | 24677.13 | 26-JUL-21:10 | 28.62 | 18.19 | 0.191428E+11 | 11378.29 | 25-JUL-22:00 | 28.62 | 18.19 |
August | 0.482531E+11 | 24855.02 | 07-AUG-21:10 | 31.25 | 17.07 | 0.191750E+11 | 11374.26 | 04-AUG-22:00 | 31.25 | 17.07 |
September | 0.448183E+11 | 23407.56 | 22-SEP-22:00 | 25.00 | 17.90 | 0.184119E+11 | 11347.16 | 30-SEP-03:20 | 11.33 | 7.00 |
October | 0.429280E+11 | 24427.14 | 25-OCT-05:30 | 6.95 | 5.28 | 0.187956E+11 | 12909.59 | 25-OCT-03:20 | 6.95 | 5.28 |
November | 0.376204E+11 | 34719.95 | 19-NOV-23:56 | 4.40 | -1.2 | 0.176930E+11 | 12612.72 | 18-NOV-05:40 | 4.40 | -1.2 |
December | 0.365667E+11 | 33070.92 | 11-DEC-24:00 | 5.00 | 1.72 | 0.178787E+11 | 13005.90 | 23-DEC-00:20 | 5.20 | 0.42 |
Annual Sum or Average | 0.508436E+12 | 0.220124E+12 | ||||||||
Minimum of Months | 0.347269E+11 | 23407.56 | 4.40 | -1.2 | 0.164684E+11 | 11347.16 | 4.40 | -1.2 | ||
Maximum of Months | 0.492678E+11 | 41485.29 | 31.83 | 18.19 | 0.191750E+11 | 13388.85 | 31.83 | 18.19 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.490744E+11 | 35265.66 | 07-JAN-09:28 | 3.90 | -0.8 | 0.188818E+11 | 11362.98 | 21-JAN-18:49 | 8.68 | 4.78 |
February | 0.454878E+11 | 36234.04 | 28-FEB-06:44 | 5.18 | 4.12 | 0.170507E+11 | 11319.47 | 04-FEB-18:19 | 5.18 | 4.12 |
March | 0.516709E+11 | 34265.88 | 25-MAR-06:36 | 5.57 | 2.06 | 0.188793E+11 | 11319.53 | 18-MAR-17:19 | 5.57 | 2.06 |
April | 0.531736E+11 | 33388.45 | 10-APR-22:40 | 7.40 | 1.81 | 0.182639E+11 | 11319.65 | 15-APR-17:19 | 27.43 | 11.91 |
May | 0.571786E+11 | 30390.24 | 21-MAY-10:40 | 29.47 | 14.38 | 0.188718E+11 | 11319.65 | 27-MAY-17:19 | 30.40 | 15.99 |
June | 0.573502E+11 | 30978.20 | 18-JUN-10:40 | 32.43 | 16.35 | 0.182662E+11 | 11319.65 | 24-JUN-17:19 | 31.67 | 16.29 |
July | 0.591820E+11 | 31125.63 | 02-JUL-10:40 | 32.23 | 20.13 | 0.188684E+11 | 11319.71 | 29-JUL-17:19 | 34.23 | 18.70 |
August | 0.585267E+11 | 31022.49 | 06-AUG-10:50 | 31.93 | 18.13 | 0.188757E+11 | 11319.67 | 05-AUG-17:19 | 31.93 | 18.13 |
September | 0.556868E+11 | 30629.34 | 17-SEP-10:40 | 29.47 | 15.71 | 0.182617E+11 | 11319.65 | 30-SEP-17:19 | 26.47 | 12.09 |
October | 0.544511E+11 | 30051.23 | 05-OCT-10:40 | 27.60 | 18.63 | 0.188691E+11 | 11319.59 | 21-OCT-17:19 | 24.83 | 12.12 |
November | 0.491268E+11 | 34879.55 | 16-NOV-08:24 | 5.00 | 2.47 | 0.182649E+11 | 11327.17 | 25-NOV-18:10 | 8.12 | 3.81 |
December | 0.485249E+11 | 38375.89 | 27-DEC-11:51 | 4.40 | 0.81 | 0.188804E+11 | 11396.31 | 02-DEC-18:10 | 4.40 | 0.81 |
Annual Sum or Average | 0.639434E+12 | 0.222234E+12 | ||||||||
Minimum of Months | 0.454878E+11 | 30051.23 | 3.90 | -0.8 | 0.170507E+11 | 11319.47 | 4.40 | 0.81 | ||
Maximum of Months | 0.591820E+11 | 38375.89 | 32.43 | 20.13 | 0.188818E+11 | 11396.31 | 34.23 | 18.70 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.438829E+10 | 3775.47 | 02-JAN-00:33 | 4.83 | 3.01 | 0.135879E+10 | 896.05 | 12-JAN-22:19 | 9.47 | 5.03 |
February | 0.439167E+10 | 3678.03 | 05-FEB-00:17 | 5.93 | 1.82 | 0.128843E+10 | 953.94 | 22-FEB-22:40 | 14.40 | 4.97 |
March | 0.532221E+10 | 4215.58 | 17-MAR-03:44 | 5.87 | -0.4 | 0.150333E+10 | 1002.92 | 16-MAR-21:30 | 5.87 | -0.4 |
April | 0.699864E+10 | 5114.38 | 30-APR-13:00 | 29.40 | 12.28 | 0.160687E+10 | 1007.39 | 19-APR-23:49 | 29.40 | 12.28 |
May | 0.951049E+10 | 6045.78 | 30-MAY-15:02 | 34.32 | 17.72 | 0.170925E+10 | 1007.44 | 18-MAY-00:10 | 34.32 | 17.72 |
June | 0.118375E+11 | 6869.13 | 15-JUN-18:03 | 35.92 | 14.47 | 0.166563E+10 | 1007.44 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.121482E+11 | 7016.23 | 03-JUL-14:30 | 37.50 | 18.90 | 0.171452E+10 | 1007.42 | 03-JUL-03:09 | 37.50 | 18.90 |
August | 0.114172E+11 | 6858.41 | 07-AUG-15:03 | 35.37 | 18.63 | 0.172099E+10 | 1007.44 | 22-AUG-00:10 | 24.22 | 16.48 |
September | 0.997601E+10 | 6544.93 | 20-SEP-15:03 | 33.30 | 17.34 | 0.165413E+10 | 1007.42 | 18-SEP-01:10 | 33.30 | 17.34 |
October | 0.753392E+10 | 6189.78 | 03-OCT-13:30 | 31.70 | 19.34 | 0.166330E+10 | 1007.42 | 05-OCT-23:49 | 20.65 | 16.69 |
November | 0.508511E+10 | 3930.51 | 26-NOV-00:14 | 4.80 | 2.00 | 0.143950E+10 | 1007.37 | 09-NOV-22:10 | 4.80 | 2.00 |
December | 0.383828E+10 | 3536.94 | 30-DEC-10:29 | 4.15 | 0.79 | 0.132690E+10 | 858.66 | 15-DEC-22:49 | 4.15 | 0.79 |
Annual Sum or Average | 0.924476E+11 | 0.186516E+11 | ||||||||
Minimum of Months | 0.383828E+10 | 3536.94 | 4.15 | -0.4 | 0.128843E+10 | 858.66 | 4.15 | -0.4 | ||
Maximum of Months | 0.121482E+11 | 7016.23 | 37.50 | 19.34 | 0.172099E+10 | 1007.44 | 37.50 | 18.90 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2060308.32 | 2998.76 | 18-JAN-04:26 | 5.85 |
February | 3987517.71 | 3748.63 | 15-FEB-23:10 | 5.00 |
March | 6344861.36 | 2710.45 | 06-MAR-00:28 | 5.55 |
April | 7061840.32 | 3200.29 | 11-APR-02:36 | 6.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 62900.85 | 209.67 | 25-OCT-03:10 | 7.38 |
November | 3130184.20 | 3243.96 | 20-NOV-04:17 | 5.77 |
December | 1552594.46 | 1790.75 | 09-DEC-04:10 | 5.47 |
Annual Sum or Average | 24200207.21 | |||
Minimum of Months | 0.00 | 0.00 | 5.00 | |
Maximum of Months | 7061840.32 | 3748.63 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8825487.07 | 488.61 | 18-JAN-04:26 | 5.85 |
February | 4110495.94 | 432.30 | 17-FEB-00:59 | 5.00 |
March | 3379319.12 | 352.28 | 06-MAR-06:03 | 5.68 |
April | 1653208.92 | 421.89 | 11-APR-02:36 | 6.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 110711.73 | 227.01 | 25-OCT-03:10 | 7.38 |
November | 7602774.53 | 441.37 | 22-NOV-05:53 | 6.10 |
December | 36320109.70 | 810.00 | 27-DEC-07:15 | -4.2 |
Annual Sum or Average | 62002107.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.2 | |
Maximum of Months | 36320109.70 | 810.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1799663.83 | 372.29 | 18-JAN-04:26 | 5.85 |
February | 893126.28 | 268.19 | 17-FEB-00:13 | 5.73 |
March | 371997.77 | 186.44 | 06-MAR-06:03 | 5.68 |
April | 438784.22 | 260.11 | 11-APR-02:36 | 6.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 25309.00 | 84.36 | 25-OCT-03:10 | 7.38 |
November | 1516770.79 | 297.64 | 22-NOV-05:53 | 6.10 |
December | 2185043.36 | 373.84 | 31-DEC-09:57 | 4.40 |
Annual Sum or Average | 7230695.26 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 2185043.36 | 373.84 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3512093.18 | 312.50 | 18-JAN-04:26 | 5.85 |
February | 1845480.84 | 281.57 | 17-FEB-00:13 | 5.73 |
March | 680451.18 | 217.67 | 06-MAR-06:03 | 5.68 |
April | 439360.06 | 214.35 | 13-APR-05:15 | 4.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 35965.22 | 119.88 | 25-OCT-03:10 | 7.38 |
November | 1971706.14 | 307.54 | 22-NOV-05:53 | 6.10 |
December | 3734694.99 | 357.78 | 31-DEC-09:57 | 4.40 |
Annual Sum or Average | 12219751.61 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 3734694.99 | 357.78 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6988276.74 | 356.07 | 18-JAN-04:26 | 5.85 |
February | 3859588.20 | 367.59 | 17-FEB-00:13 | 5.73 |
March | 1684443.53 | 306.00 | 06-MAR-00:28 | 5.55 |
April | 1128168.25 | 304.43 | 13-APR-05:15 | 4.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 100440.87 | 210.01 | 25-OCT-03:10 | 7.38 |
November | 4765404.55 | 382.29 | 22-NOV-05:53 | 6.10 |
December | 6676042.73 | 379.53 | 23-DEC-00:10 | 5.10 |
Annual Sum or Average | 25202364.88 | |||
Minimum of Months | 0.00 | 0.00 | 4.63 | |
Maximum of Months | 6988276.74 | 382.29 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 114515.97 | 1908.60 | 18-JAN-04:26 | 5.85 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 |
March | 13814.81 | 187.73 | 17-MAR-03:47 | 5.87 |
April | 392465.00 | 2811.79 | 11-APR-02:36 | 6.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 139226.45 | 2176.60 | 20-NOV-04:17 | 5.77 |
December | 161348.29 | 1394.48 | 09-DEC-04:03 | 5.47 |
Annual Sum or Average | 821370.52 | |||
Minimum of Months | 0.00 | 0.00 | 5.47 | |
Maximum of Months | 392465.00 | 2811.79 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16712797.73 | 3134.44 | 01-JAN-08:10 | 5.47 |
February | 6829575.62 | 1715.12 | 24-FEB-05:02 | 5.40 |
March | 4976745.09 | 2211.48 | 25-MAR-06:38 | 5.57 |
April | 4999069.53 | 2210.59 | 11-APR-02:36 | 6.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 175027.76 | 763.85 | 25-OCT-06:08 | 6.88 |
November | 16515119.38 | 2502.86 | 11-NOV-05:19 | 5.77 |
December | 12020585.95 | 3554.50 | 03-DEC-11:58 | 5.60 |
Annual Sum or Average | 62228921.06 | |||
Minimum of Months | 0.00 | 0.00 | 5.40 | |
Maximum of Months | 16712797.73 | 3554.50 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11224876.86 | 4987.51 | 18-JAN-04:26 | 5.85 |
February | 8958888.95 | 6715.41 | 17-FEB-00:13 | 5.73 |
March | 3940157.94 | 3096.61 | 06-MAR-06:03 | 5.68 |
April | 7740119.28 | 7256.35 | 11-APR-02:36 | 6.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 44897.83 | 149.66 | 25-OCT-03:10 | 7.38 |
November | 21027964.71 | 7530.17 | 22-NOV-05:53 | 6.10 |
December | 17573720.67 | 6101.22 | 23-DEC-00:10 | 5.10 |
Annual Sum or Average | 70510626.24 | |||
Minimum of Months | 0.00 | 0.00 | 5.10 | |
Maximum of Months | 21027964.71 | 7530.17 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316451E+09 | 2279.20 | 27-JAN-09:01 | -1.2 |
February | 0.184498E+09 | 2262.42 | 02-FEB-09:01 | 1.38 |
March | 87780978.48 | 2273.09 | 02-MAR-09:01 | 0.47 |
April | 6053114.48 | 1399.94 | 11-APR-08:62 | 6.88 |
May | 914062.70 | 783.24 | 28-MAY-08:04 | 22.38 |
June | 787302.90 | 627.00 | 25-JUN-08:04 | 22.67 |
July | 846189.61 | 716.37 | 21-JUL-08:04 | 22.30 |
August | 912640.35 | 761.47 | 19-AUG-08:04 | 23.07 |
September | 867549.74 | 717.06 | 16-SEP-08:04 | 22.07 |
October | 1498505.28 | 754.12 | 15-OCT-08:03 | 13.90 |
November | 0.135306E+09 | 2282.31 | 26-NOV-19:01 | 4.90 |
December | 0.445368E+09 | 2303.41 | 27-DEC-09:01 | -0.7 |
Annual Sum or Average | 0.118128E+10 | |||
Minimum of Months | 787302.90 | 627.00 | -1.2 | |
Maximum of Months | 0.445368E+09 | 2303.41 | 23.07 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.561291E+09 | 2319.33 | 27-JAN-09:01 | -1.2 |
February | 0.328607E+09 | 2302.62 | 02-FEB-09:01 | 1.38 |
March | 0.144433E+09 | 2291.59 | 02-MAR-09:01 | 0.47 |
April | 9037200.41 | 1636.67 | 11-APR-08:62 | 6.88 |
May | 882940.44 | 754.13 | 06-MAY-08:03 | 17.48 |
June | 683927.99 | 582.98 | 30-JUN-08:04 | 22.38 |
July | 776675.99 | 827.94 | 21-JUL-08:04 | 22.30 |
August | 1005330.24 | 765.30 | 12-AUG-08:04 | 22.57 |
September | 1091808.46 | 799.32 | 30-SEP-08:03 | 17.67 |
October | 2048949.26 | 725.59 | 28-OCT-08:03 | 13.68 |
November | 0.236835E+09 | 2299.99 | 26-NOV-19:01 | 4.90 |
December | 0.752550E+09 | 2321.22 | 07-DEC-09:01 | 4.37 |
Annual Sum or Average | 0.203924E+10 | |||
Minimum of Months | 683927.99 | 582.98 | -1.2 | |
Maximum of Months | 0.752550E+09 | 2321.22 | 22.57 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 48628381.09 | 694.03 | 27-JAN-09:01 | -1.2 |
February | 28950018.79 | 688.04 | 03-FEB-09:01 | 2.95 |
March | 7589737.08 | 682.41 | 02-MAR-09:01 | 0.47 |
April | 1334981.20 | 368.84 | 10-APR-15:04 | 17.67 |
May | 390882.83 | 379.42 | 07-MAY-15:04 | 28.07 |
June | 77896.62 | 176.37 | 03-JUN-18:06 | 26.42 |
July | 104648.01 | 284.07 | 05-JUL-08:05 | 22.57 |
August | 214693.64 | 346.13 | 24-AUG-08:04 | 21.60 |
September | 399366.68 | 337.22 | 21-SEP-08:04 | 23.17 |
October | 912092.28 | 336.27 | 31-OCT-08:03 | 15.37 |
November | 14910627.53 | 674.78 | 26-NOV-19:01 | 4.90 |
December | 85192449.16 | 692.13 | 27-DEC-09:01 | -0.7 |
Annual Sum or Average | 0.188706E+09 | |||
Minimum of Months | 77896.62 | 176.37 | -1.2 | |
Maximum of Months | 85192449.16 | 694.03 | 28.07 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.336682E+09 | 2177.36 | 15-JAN-09:01 | 7.88 |
February | 0.174471E+09 | 2092.70 | 13-FEB-16:01 | 12.30 |
March | 91099443.21 | 2179.23 | 02-MAR-09:01 | 0.47 |
April | 5202265.73 | 668.01 | 06-APR-15:04 | 16.10 |
May | 278920.92 | 518.46 | 02-MAY-18:04 | 24.90 |
June | 4512.86 | 45.13 | 29-JUN-18:05 | 27.70 |
July | 17130.85 | 98.00 | 07-JUL-08:04 | 23.80 |
August | 208006.49 | 646.57 | 17-AUG-18:04 | 25.50 |
September | 62462.50 | 515.73 | 24-SEP-18:04 | 20.73 |
October | 1728107.26 | 677.88 | 07-OCT-15:04 | 17.88 |
November | 0.149043E+09 | 2213.49 | 26-NOV-19:01 | 4.90 |
December | 0.453478E+09 | 2221.32 | 26-DEC-09:01 | -0.5 |
Annual Sum or Average | 0.121227E+10 | |||
Minimum of Months | 4512.86 | 45.13 | -0.5 | |
Maximum of Months | 0.453478E+09 | 2221.32 | 27.70 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.573724E+09 | 2181.16 | 26-JAN-19:01 | 3.22 |
February | 0.292965E+09 | 2160.58 | 02-FEB-19:01 | 7.43 |
March | 0.143345E+09 | 2196.94 | 02-MAR-09:01 | 0.47 |
April | 8044891.70 | 800.59 | 06-APR-15:04 | 16.10 |
May | 351153.68 | 659.51 | 02-MAY-18:04 | 24.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 8007.20 | 43.40 | 07-JUL-18:05 | 27.02 |
August | 262370.14 | 765.80 | 17-AUG-18:04 | 25.50 |
September | 150950.52 | 443.51 | 30-SEP-18:04 | 24.45 |
October | 3844144.31 | 771.92 | 24-OCT-15:03 | 17.88 |
November | 0.245144E+09 | 2230.14 | 26-NOV-19:01 | 4.90 |
December | 0.741727E+09 | 2229.36 | 26-DEC-09:01 | -0.5 |
Annual Sum or Average | 0.200957E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.5 | |
Maximum of Months | 0.741727E+09 | 2230.14 | 27.02 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9245497.43 | 678.77 | 18-JAN-04:26 | 5.85 |
February | 4271350.50 | 597.13 | 17-FEB-00:13 | 5.73 |
March | 1658835.15 | 468.55 | 05-MAR-04:23 | 5.85 |
April | 929890.34 | 436.61 | 13-APR-05:15 | 4.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 62142.94 | 207.14 | 25-OCT-03:10 | 7.38 |
November | 4079287.02 | 569.01 | 22-NOV-05:53 | 6.10 |
December | 9013020.89 | 684.64 | 31-DEC-09:57 | 4.40 |
Annual Sum or Average | 29260024.28 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 9245497.43 | 684.64 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.643194E+09 | 2737.45 | 27-JAN-09:01 | -1.2 |
February | 0.419165E+09 | 2722.94 | 02-FEB-09:01 | 1.38 |
March | 0.251064E+09 | 2724.50 | 02-MAR-09:01 | 0.47 |
April | 34056243.84 | 2567.67 | 11-APR-08:62 | 6.88 |
May | 1237534.29 | 717.32 | 10-MAY-08:03 | 20.78 |
June | 763393.23 | 639.82 | 04-JUN-08:04 | 24.27 |
July | 1058412.02 | 801.89 | 18-JUL-08:04 | 24.08 |
August | 1164429.76 | 763.64 | 23-AUG-08:04 | 24.27 |
September | 915664.59 | 631.86 | 03-SEP-08:04 | 22.57 |
October | 12554276.26 | 861.58 | 06-OCT-08:03 | 12.30 |
November | 0.333620E+09 | 2768.66 | 26-NOV-19:01 | 4.90 |
December | 0.824187E+09 | 2744.73 | 27-DEC-09:01 | -0.7 |
Annual Sum or Average | 0.252298E+10 | |||
Minimum of Months | 763393.23 | 631.86 | -1.2 | |
Maximum of Months | 0.824187E+09 | 2768.66 | 24.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100145E+10 | 2765.79 | 27-JAN-09:01 | -1.2 |
February | 0.649407E+09 | 2745.34 | 02-FEB-09:01 | 1.38 |
March | 0.358874E+09 | 2730.31 | 02-MAR-09:01 | 0.47 |
April | 43097008.51 | 2570.17 | 11-APR-08:62 | 6.88 |
May | 1185177.15 | 766.54 | 27-MAY-08:04 | 21.38 |
June | 745507.75 | 628.65 | 04-JUN-08:04 | 24.27 |
July | 1005005.97 | 756.13 | 18-JUL-08:04 | 24.08 |
August | 1245263.39 | 697.95 | 23-AUG-08:04 | 24.27 |
September | 1222692.76 | 720.18 | 23-SEP-08:04 | 23.58 |
October | 29456324.41 | 2323.83 | 25-OCT-08:62 | 11.15 |
November | 0.544011E+09 | 2747.07 | 26-NOV-19:01 | 4.90 |
December | 0.124417E+10 | 2776.84 | 07-DEC-09:01 | 4.37 |
Annual Sum or Average | 0.387587E+10 | |||
Minimum of Months | 745507.75 | 628.65 | -1.2 | |
Maximum of Months | 0.124417E+10 | 2776.84 | 24.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 96565000.83 | 1382.58 | 15-JAN-09:01 | 7.88 |
February | 60955697.53 | 1192.72 | 13-FEB-16:01 | 12.30 |
March | 42403092.35 | 1403.69 | 02-MAR-09:01 | 0.47 |
April | 6300510.30 | 884.47 | 11-APR-08:62 | 6.88 |
May | 943177.94 | 442.77 | 05-MAY-18:04 | 24.82 |
June | 757594.58 | 473.18 | 19-JUN-08:04 | 25.37 |
July | 634988.38 | 469.59 | 10-JUL-08:04 | 26.88 |
August | 637292.59 | 470.86 | 11-AUG-08:04 | 25.87 |
September | 314373.30 | 381.16 | 19-SEP-08:04 | 24.27 |
October | 416245.81 | 431.04 | 14-OCT-15:04 | 19.60 |
November | 53656616.24 | 1401.36 | 26-NOV-19:01 | 4.90 |
December | 0.142039E+09 | 1416.71 | 26-DEC-09:01 | -0.5 |
Annual Sum or Average | 0.405623E+09 | |||
Minimum of Months | 314373.30 | 381.16 | -0.5 | |
Maximum of Months | 0.142039E+09 | 1416.71 | 26.88 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8835194.97 | 3466.88 | 01-JAN-08:10 | 5.47 |
February | 3918344.71 | 3266.19 | 03-FEB-10:19 | 7.23 |
March | 659761.53 | 2055.81 | 06-MAR-00:28 | 5.55 |
April | 933356.79 | 3117.85 | 11-APR-02:36 | 6.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 9597052.11 | 3375.78 | 11-NOV-05:19 | 5.77 |
December | 14566188.92 | 4061.95 | 19-DEC-10:59 | 4.40 |
Annual Sum or Average | 38509899.04 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 14566188.92 | 4061.95 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3341787.01 | 2663.83 | 01-JAN-08:10 | 5.47 |
February | 1591380.09 | 2363.84 | 03-FEB-10:19 | 7.23 |
March | 179443.03 | 761.27 | 06-MAR-00:28 | 5.55 |
April | 562484.35 | 2981.50 | 11-APR-02:36 | 6.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 5403682.48 | 2975.38 | 11-NOV-05:19 | 5.77 |
December | 6673832.70 | 3193.39 | 19-DEC-10:59 | 4.40 |
Annual Sum or Average | 17752609.66 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 6673832.70 | 3193.39 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11852.16 | 166.62 | 18-JAN-04:26 | 5.85 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 |
March | 36331.26 | 605.52 | 06-MAR-00:28 | 5.55 |
April | 31447.11 | 401.35 | 11-APR-02:36 | 6.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 35173.35 | 273.58 | 11-NOV-05:19 | 5.77 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 114803.88 | |||
Minimum of Months | 0.00 | 0.00 | 5.55 | |
Maximum of Months | 36331.26 | 605.52 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22960816.05 | 1087.39 | 18-JAN-04:26 | 5.85 |
February | 13507401.35 | 970.50 | 17-FEB-00:59 | 5.00 |
March | 3129498.01 | 771.26 | 06-MAR-06:03 | 5.68 |
April | 1905533.49 | 755.23 | 13-APR-05:15 | 4.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 138890.90 | 413.72 | 25-OCT-03:10 | 7.38 |
November | 9298567.89 | 1004.38 | 22-NOV-05:53 | 6.10 |
December | 60635235.48 | 1319.63 | 27-DEC-07:30 | -4.2 |
Annual Sum or Average | 0.111576E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.2 | |
Maximum of Months | 60635235.48 | 1319.63 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.147273E+11 | 14185.34 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.132974E+11 | 14185.34 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.147727E+11 | 14185.34 | 01-MAR-20:10 | 0.127855E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.142280E+11 | 14185.34 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.147528E+11 | 14185.34 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.142932E+11 | 14185.34 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.146876E+11 | 14185.34 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.147784E+11 | 14185.34 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.142337E+11 | 14185.34 | 01-SEP-19:10 | 0.123352E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.147216E+11 | 14185.34 | 02-OCT-19:10 | 0.127549E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.142819E+11 | 14185.34 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.146876E+11 | 14185.34 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.173462E+12 | 0.150255E+12 | ||||
Minimum of Months | 0.132974E+11 | 14185.34 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.147784E+11 | 14185.34 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.731324E+09 | 704.41 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.660319E+09 | 704.41 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.733578E+09 | 704.41 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.706528E+09 | 704.41 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.732592E+09 | 704.41 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.709769E+09 | 704.41 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.729351E+09 | 704.41 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.733860E+09 | 704.41 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.706810E+09 | 704.41 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.731042E+09 | 704.41 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.709205E+09 | 704.41 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.729351E+09 | 704.41 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.861373E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.660319E+09 | 704.41 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.733860E+09 | 704.41 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.846876E+09 | 815.72 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.764651E+09 | 815.72 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.849486E+09 | 815.72 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.818162E+09 | 815.72 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.848344E+09 | 815.72 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.821915E+09 | 815.72 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.844592E+09 | 815.72 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.849812E+09 | 815.72 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.818489E+09 | 815.72 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.846549E+09 | 815.72 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.821262E+09 | 815.72 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.844592E+09 | 815.72 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.997473E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.764651E+09 | 815.72 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.849812E+09 | 815.72 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.141236E+10 | 1360.40 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.127524E+10 | 1360.40 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.141672E+10 | 1360.40 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.136448E+10 | 1360.40 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.141481E+10 | 1360.40 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.137074E+10 | 1360.40 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.140855E+10 | 1360.40 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.141726E+10 | 1360.40 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.136502E+10 | 1360.40 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.141182E+10 | 1360.40 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.136965E+10 | 1360.40 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.140855E+10 | 1360.40 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.166352E+11 | 0.124712E+11 | ||||
Minimum of Months | 0.127524E+10 | 1360.40 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.141726E+10 | 1360.40 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.236418E+09 | 227.72 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.213464E+09 | 227.72 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.237147E+09 | 227.72 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.228402E+09 | 227.72 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.236828E+09 | 227.72 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.229450E+09 | 227.72 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.235780E+09 | 227.72 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.237238E+09 | 227.72 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.228493E+09 | 227.72 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.236327E+09 | 227.72 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.229268E+09 | 227.72 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.235780E+09 | 227.72 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.278459E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.213464E+09 | 227.72 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.237238E+09 | 227.72 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.370859E+09 | 357.21 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.334852E+09 | 357.21 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.372002E+09 | 357.21 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.358285E+09 | 357.21 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.371502E+09 | 357.21 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.359929E+09 | 357.21 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.369859E+09 | 357.21 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.372145E+09 | 357.21 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.358428E+09 | 357.21 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.370717E+09 | 357.21 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.359643E+09 | 357.21 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.369859E+09 | 357.21 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.436808E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.334852E+09 | 357.21 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.372145E+09 | 357.21 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.159856E+10 | 1761.91 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.141918E+10 | 1761.91 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.154488E+10 | 1761.91 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.145180E+10 | 1761.91 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.148666E+10 | 1761.91 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.141991E+10 | 1761.91 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.145980E+10 | 1761.91 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.150656E+10 | 1761.91 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.147181E+10 | 1761.91 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.157293E+10 | 1761.91 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.152628E+10 | 1761.91 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.159121E+10 | 1761.91 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.180496E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.141918E+10 | 1761.91 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.159856E+10 | 1761.91 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104201E+11 | 10265.18 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.938499E+10 | 10265.18 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.104002E+11 | 10265.18 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.997990E+10 | 10265.18 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.103301E+11 | 10265.18 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.999248E+10 | 10265.18 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.102711E+11 | 10265.18 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.103657E+11 | 10265.18 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.100075E+11 | 10265.18 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.103913E+11 | 10265.18 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.100809E+11 | 10265.18 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.103887E+11 | 10265.18 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.122013E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.938499E+10 | 10265.18 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.104201E+11 | 10265.18 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85091918.49 | 76.99 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 76846309.13 | 76.99 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 84415649.14 | 76.99 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 82445007.08 | 76.99 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 84753783.81 | 76.99 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 81790910.76 | 76.99 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 85418966.65 | 76.99 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 84415649.14 | 76.99 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 82467180.11 | 76.99 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 85080831.98 | 76.99 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 82117958.92 | 76.99 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 85430053.17 | 76.99 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.100027E+10 | 0.300992E+10 | ||||
Minimum of Months | 76846309.13 | 76.99 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 85430053.17 | 76.99 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85115186.72 | 77.01 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 76867322.62 | 77.01 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 84438732.44 | 77.01 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 82467551.52 | 77.01 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 84776959.58 | 77.01 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 81813276.33 | 77.01 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 85442324.32 | 77.01 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 84438732.44 | 77.01 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 82489730.61 | 77.01 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 85104097.18 | 77.01 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 82140413.93 | 77.01 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 85453413.86 | 77.01 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.100055E+10 | 0.301074E+10 | ||||
Minimum of Months | 76867322.62 | 77.01 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 85453413.86 | 77.01 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.232638E+10 | 2240.78 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.210051E+10 | 2240.78 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.233355E+10 | 2240.78 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.224750E+10 | 2240.78 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.233041E+10 | 2240.78 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.225781E+10 | 2240.78 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.232011E+10 | 2240.78 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.233445E+10 | 2240.78 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.224840E+10 | 2240.78 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.232548E+10 | 2240.78 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.225602E+10 | 2240.78 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.232011E+10 | 2240.78 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.274007E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.210051E+10 | 2240.78 | 0.00 | 0.00 | |
Maximum of Months | 0.233445E+10 | 2240.78 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85115186.72 | 77.01 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 76867322.62 | 77.01 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 84438732.44 | 77.01 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 82467551.52 | 77.01 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 84776959.58 | 77.01 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 81813276.33 | 77.01 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 85442324.32 | 77.01 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 84438732.44 | 77.01 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 82489730.61 | 77.01 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 85104097.18 | 77.01 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 82140413.93 | 77.01 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 85453413.86 | 77.01 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.100055E+10 | 0.301074E+10 | ||||
Minimum of Months | 76867322.62 | 77.01 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 85453413.86 | 77.01 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.303266E+10 | 3094.06 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.271117E+10 | 3094.06 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.297615E+10 | 3094.06 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.281606E+10 | 3094.06 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.289246E+10 | 3094.06 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.278243E+10 | 3094.06 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.285773E+10 | 3094.06 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.292096E+10 | 3094.06 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.284760E+10 | 3094.06 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.299951E+10 | 3094.06 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.291802E+10 | 3094.06 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.301853E+10 | 3094.06 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.347733E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.271117E+10 | 3094.06 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.303266E+10 | 3094.06 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.303266E+10 | 3094.06 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.271117E+10 | 3094.06 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.297615E+10 | 3094.06 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.281606E+10 | 3094.06 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.289246E+10 | 3094.06 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.278243E+10 | 3094.06 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.285773E+10 | 3094.06 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.292096E+10 | 3094.06 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.284760E+10 | 3094.06 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.299951E+10 | 3094.06 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.291802E+10 | 3094.06 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.301853E+10 | 3094.06 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.347733E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.271117E+10 | 3094.06 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.303266E+10 | 3094.06 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113146E+10 | 1089.83 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.102161E+10 | 1089.83 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.113495E+10 | 1089.83 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.109310E+10 | 1089.83 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.113342E+10 | 1089.83 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.109811E+10 | 1089.83 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.112841E+10 | 1089.83 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.113539E+10 | 1089.83 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.109354E+10 | 1089.83 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.113103E+10 | 1089.83 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.109724E+10 | 1089.83 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.112841E+10 | 1089.83 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.133267E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.102161E+10 | 1089.83 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.113539E+10 | 1089.83 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.246211E+10 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.222306E+10 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.246970E+10 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.237864E+10 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.246638E+10 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.238954E+10 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.245547E+10 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.247065E+10 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.237958E+10 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.246116E+10 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.238765E+10 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.245547E+10 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.289994E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.222306E+10 | 2371.52 | 0.00 | 0.00 | |
Maximum of Months | 0.247065E+10 | 2371.52 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.147273E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.132974E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.147727E+11 | 0.127855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.142280E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.147528E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.142932E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.146876E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.147784E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.142337E+11 | 0.123352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.147216E+11 | 0.127549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.142819E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.146876E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.173462E+12 | 0.150255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.132974E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.147784E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.731324E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413107E+09 |
February | 0.179968E+10 | 0.660319E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322276E+09 |
March | 0.199990E+10 | 0.733578E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 140916.59 | 0.293830E+09 |
April | 0.192973E+10 | 0.706528E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20331454.48 | 0.138193E+09 |
May | 0.199475E+10 | 0.732592E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57274323.70 | 59673125.96 |
June | 0.193394E+10 | 0.709769E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117317E+09 | 18763955.81 |
July | 0.199054E+10 | 0.729351E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107475E+09 | 12996583.65 |
August | 0.199896E+10 | 0.733860E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87174309.25 | 26294858.79 |
September | 0.192879E+10 | 0.706810E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48616705.15 | 65589870.45 |
October | 0.199148E+10 | 0.731042E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11492151.38 | 0.162446E+09 |
November | 0.192552E+10 | 0.709205E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327245E+09 |
December | 0.199054E+10 | 0.729351E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451046E+09 |
Annual Sum or Average | 0.234744E+11 | 0.861373E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449822E+09 | 0.229146E+10 |
Minimum of Months | 0.179968E+10 | 0.660319E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12996583.65 |
Maximum of Months | 0.199990E+10 | 0.733860E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117317E+09 | 0.451046E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.846876E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162860E+09 |
February | 0.208403E+10 | 0.764651E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3335.31 | 0.127054E+09 |
March | 0.231589E+10 | 0.849486E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 267298.58 | 0.116465E+09 |
April | 0.223463E+10 | 0.818162E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9338769.25 | 55249210.69 |
May | 0.230993E+10 | 0.848344E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23767926.13 | 23895136.95 |
June | 0.223950E+10 | 0.821915E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46389835.01 | 7322505.68 |
July | 0.230505E+10 | 0.844592E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42613491.57 | 5054536.78 |
August | 0.231480E+10 | 0.849812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34720058.91 | 10208313.68 |
September | 0.223354E+10 | 0.818489E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19771253.52 | 25742680.39 |
October | 0.230614E+10 | 0.846549E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5006002.83 | 63647039.67 |
November | 0.222975E+10 | 0.821262E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11819.80 | 0.129083E+09 |
December | 0.230505E+10 | 0.844592E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177483E+09 |
Annual Sum or Average | 0.271834E+11 | 0.997473E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181890E+09 | 0.904064E+09 |
Minimum of Months | 0.208403E+10 | 0.764651E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5054536.78 |
Maximum of Months | 0.231589E+10 | 0.849812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46389835.01 | 0.177483E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.141236E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365681E+09 |
February | 0.440737E+09 | 0.127524E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 113237.44 | 0.285706E+09 |
March | 0.489771E+09 | 0.141672E+10 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1067676.98 | 0.264640E+09 |
April | 0.472586E+09 | 0.136448E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21362717.60 | 0.129811E+09 |
May | 0.488511E+09 | 0.141481E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52823875.73 | 57427323.42 |
June | 0.473617E+09 | 0.137074E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107041E+09 | 17521873.08 |
July | 0.487480E+09 | 0.140855E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98041141.20 | 12119193.92 |
August | 0.489542E+09 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79606486.80 | 24799977.47 |
September | 0.472357E+09 | 0.136502E+10 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44654699.51 | 61299204.45 |
October | 0.487709E+09 | 0.141182E+10 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11468264.68 | 0.149809E+09 |
November | 0.471555E+09 | 0.136965E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83225.43 | 0.293039E+09 |
December | 0.487480E+09 | 0.140855E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399054E+09 |
Annual Sum or Average | 0.574883E+10 | 0.166352E+11 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416262E+09 | 0.206091E+10 |
Minimum of Months | 0.440737E+09 | 0.127524E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12119193.92 |
Maximum of Months | 0.489771E+09 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107041E+09 | 0.399054E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.236418E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197775E+09 |
February | 0.339028E+09 | 0.213464E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 352435.59 | 0.151368E+09 |
March | 0.376747E+09 | 0.237147E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1510122.76 | 0.136231E+09 |
April | 0.363528E+09 | 0.228402E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17407151.97 | 62324908.86 |
May | 0.375778E+09 | 0.236828E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37653964.12 | 26305425.22 |
June | 0.364321E+09 | 0.229450E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66754167.35 | 7898958.74 |
July | 0.374985E+09 | 0.235780E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62134412.17 | 4951371.67 |
August | 0.376571E+09 | 0.237238E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51874415.90 | 10441618.98 |
September | 0.363352E+09 | 0.228493E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31890240.35 | 28642312.33 |
October | 0.375161E+09 | 0.236327E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9852287.49 | 72017157.87 |
November | 0.362735E+09 | 0.229268E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 273209.00 | 0.152844E+09 |
December | 0.374985E+09 | 0.235780E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219549E+09 |
Annual Sum or Average | 0.442217E+10 | 0.278459E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279702E+09 | 0.107035E+10 |
Minimum of Months | 0.339028E+09 | 0.213464E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4951371.67 |
Maximum of Months | 0.376747E+09 | 0.237238E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66754167.35 | 0.219549E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.370859E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573232E+09 |
February | 0.139600E+10 | 0.334852E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446201E+09 |
March | 0.155131E+10 | 0.372002E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 175438.40 | 0.408854E+09 |
April | 0.149688E+10 | 0.358285E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 25305596.47 | 0.189101E+09 |
May | 0.154732E+10 | 0.371502E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 71298046.97 | 79735581.20 |
June | 0.150015E+10 | 0.359929E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.146112E+09 | 23949821.77 |
July | 0.154405E+10 | 0.369859E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.133849E+09 | 16546943.85 |
August | 0.155059E+10 | 0.372145E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.108567E+09 | 34091275.15 |
September | 0.149615E+10 | 0.358428E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 60540056.32 | 84117966.19 |
October | 0.154478E+10 | 0.370717E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 14312753.02 | 0.215493E+09 |
November | 0.149361E+10 | 0.359643E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446086E+09 |
December | 0.154405E+10 | 0.369859E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626609E+09 |
Annual Sum or Average | 0.182090E+11 | 0.436808E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.560160E+09 | 0.314402E+10 |
Minimum of Months | 0.139600E+10 | 0.334852E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16546943.85 |
Maximum of Months | 0.155131E+10 | 0.372145E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.146112E+09 | 0.626609E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.159856E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.917338E+09 |
February | 0.236489E+11 | 0.141918E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 899.43 | 0.709604E+09 |
March | 0.262800E+11 | 0.154488E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1210811.81 | 0.632288E+09 |
April | 0.253579E+11 | 0.145180E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61310917.98 | 0.282797E+09 |
May | 0.262123E+11 | 0.148666E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160466E+09 | 0.116081E+09 |
June | 0.254132E+11 | 0.141991E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292309E+09 | 34263995.47 |
July | 0.261570E+11 | 0.145980E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272013E+09 | 23064766.88 |
August | 0.262677E+11 | 0.150656E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217199E+09 | 47714674.76 |
September | 0.253456E+11 | 0.147181E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118980E+09 | 0.132890E+09 |
October | 0.261693E+11 | 0.157293E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28288227.86 | 0.340457E+09 |
November | 0.253025E+11 | 0.152628E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3133.24 | 0.721606E+09 |
December | 0.261570E+11 | 0.159121E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100236E+10 |
Annual Sum or Average | 0.308468E+12 | 0.180496E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115178E+10 | 0.496046E+10 |
Minimum of Months | 0.236489E+11 | 0.141918E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23064766.88 |
Maximum of Months | 0.262800E+11 | 0.159856E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292309E+09 | 0.100236E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.104201E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273564E+10 |
February | 0.702046E+11 | 0.938499E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12543.09 | 0.213167E+10 |
March | 0.780153E+11 | 0.104002E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3900986.39 | 0.194134E+10 |
April | 0.752779E+11 | 0.997990E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157464E+09 | 0.906978E+09 |
May | 0.778146E+11 | 0.103301E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405130E+09 | 0.387431E+09 |
June | 0.754422E+11 | 0.999248E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777867E+09 | 0.117585E+09 |
July | 0.776503E+11 | 0.102711E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715435E+09 | 81127591.64 |
August | 0.779788E+11 | 0.103657E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581233E+09 | 0.163820E+09 |
September | 0.752414E+11 | 0.100075E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328838E+09 | 0.418283E+09 |
October | 0.776868E+11 | 0.103913E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79911670.56 | 0.105131E+10 |
November | 0.751137E+11 | 0.100809E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81795.28 | 0.215944E+10 |
December | 0.776503E+11 | 0.103887E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298540E+10 |
Annual Sum or Average | 0.915726E+12 | 0.122013E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304987E+10 | 0.150800E+11 |
Minimum of Months | 0.702046E+11 | 0.938499E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81127591.64 |
Maximum of Months | 0.780153E+11 | 0.104201E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777867E+09 | 0.298540E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221660E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 145793.73 | 0.169139E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 853599.40 | 0.150290E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20267972.43 | 60293330.20 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51295856.03 | 19331384.26 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93855052.06 | 3145118.97 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90753133.96 | 992456.81 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75041297.93 | 4916489.59 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43293275.22 | 19695485.14 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12432785.25 | 68766996.86 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 189622.97 | 0.167688E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245603E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388128E+09 | 0.113152E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 992456.81 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93855052.06 | 0.245603E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215682E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 165081.77 | 0.164705E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 978002.37 | 0.147246E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20563425.23 | 59675717.90 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51350032.89 | 19257182.52 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93816529.92 | 3158446.02 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90732894.96 | 998484.62 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75118670.57 | 4878530.49 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43564862.14 | 19548179.18 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12733916.09 | 67231667.43 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 194947.52 | 0.163659E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239259E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389218E+09 | 0.110530E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 998484.62 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93816529.92 | 0.239259E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 85091918.49 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67859488.02 |
February | 0.00 | 76846309.13 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53044118.62 |
March | 0.00 | 84415649.14 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65001.03 | 47816029.35 |
April | 0.00 | 82445007.08 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4003850.18 | 21673330.83 |
May | 0.00 | 84753783.81 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10702837.59 | 8755501.02 |
June | 0.00 | 81790910.76 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20951924.46 | 2389346.91 |
July | 0.00 | 85418966.65 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19492227.80 | 1488624.73 |
August | 0.00 | 84415649.14 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15911000.13 | 3411165.08 |
September | 0.00 | 82467180.11 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9116501.65 | 9461176.50 |
October | 0.00 | 85080831.98 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2322944.70 | 25327857.41 |
November | 0.00 | 82117958.92 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4323.00 | 52813589.16 |
December | 0.00 | 85430053.17 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74200244.54 |
Annual Sum or Average | 0.00 | 0.100027E+10 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82570610.55 | 0.368240E+09 |
Minimum of Months | 0.00 | 76846309.13 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1488624.73 |
Maximum of Months | 0.00 | 85430053.17 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20951924.46 | 74200244.54 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 85115186.72 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60501609.94 |
February | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 139287.45 | 45972780.32 |
March | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 481704.58 | 40792159.61 |
April | 0.293479E+09 | 82467551.52 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6381476.50 | 16390515.15 |
May | 0.303504E+09 | 84776959.58 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14948922.66 | 5263259.50 |
June | 0.293842E+09 | 81813276.33 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26563690.39 | 851468.38 |
July | 0.303141E+09 | 85442324.32 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25735456.33 | 265538.31 |
August | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21500877.78 | 1283784.91 |
September | 0.293479E+09 | 82489730.61 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12924655.74 | 5384977.20 |
October | 0.303322E+09 | 85104097.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4183896.43 | 18412173.32 |
November | 0.293661E+09 | 82140413.93 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 146500.99 | 45212841.52 |
December | 0.303141E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67239130.63 |
Annual Sum or Average | 0.357224E+10 | 0.100055E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113006E+09 | 0.307570E+09 |
Minimum of Months | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265538.31 |
Maximum of Months | 0.303685E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26563690.39 | 67239130.63 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222108E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 146078.33 | 0.170472E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 873662.57 | 0.151988E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20231559.41 | 61613893.82 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51157493.41 | 19933607.13 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93686281.78 | 3271762.33 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90524015.48 | 1040127.71 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74894497.07 | 5086474.47 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43245178.39 | 20072599.12 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12464069.94 | 69193881.28 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 190244.44 | 0.168462E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245874E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387413E+09 | 0.113912E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1040127.71 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93686281.78 | 0.245874E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215661E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 187851.53 | 0.165827E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 976222.82 | 0.149206E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20274575.32 | 61276697.57 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51159239.06 | 19926692.12 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93665335.03 | 3274349.67 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90512764.14 | 1040973.94 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74912955.46 | 5068789.96 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43326646.03 | 20024876.62 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12599620.17 | 68168347.70 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 247702.48 | 0.163506E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239265E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387863E+09 | 0.111225E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1040973.94 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93665335.03 | 0.239265E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.232638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278777E+09 |
February | 0.348285E+10 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37516.72 | 0.218501E+09 |
March | 0.387034E+10 | 0.233355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 615156.81 | 0.201396E+09 |
April | 0.373454E+10 | 0.224750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16712614.61 | 97666550.64 |
May | 0.386038E+10 | 0.233041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40871984.99 | 43431633.35 |
June | 0.374269E+10 | 0.225781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82010028.04 | 13526930.91 |
July | 0.385223E+10 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75099289.62 | 9395632.75 |
August | 0.386853E+10 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61040596.18 | 18817811.68 |
September | 0.373273E+10 | 0.224840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34058444.77 | 46974026.37 |
October | 0.385404E+10 | 0.232548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8504230.00 | 0.114274E+09 |
November | 0.372639E+10 | 0.225602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32336.06 | 0.226459E+09 |
December | 0.385223E+10 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304165E+09 |
Annual Sum or Average | 0.454292E+11 | 0.274007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318982E+09 | 0.157338E+10 |
Minimum of Months | 0.348285E+10 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9395632.75 |
Maximum of Months | 0.387034E+10 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82010028.04 | 0.304165E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220743E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 136521.57 | 0.168587E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 820462.25 | 0.149941E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19951698.17 | 60363977.23 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50730672.49 | 19458470.93 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93066741.93 | 3216341.62 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89912836.21 | 1032337.60 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74286857.24 | 4978933.95 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42751190.45 | 19856428.94 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12217004.76 | 68799429.64 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 180246.99 | 0.167269E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244751E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384054E+09 | 0.112900E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1032337.60 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93066741.93 | 0.244751E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214385E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 172640.51 | 0.163804E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 994718.49 | 0.146597E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20237106.63 | 59683469.50 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50785653.99 | 19378413.52 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93016926.87 | 3232002.23 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89888625.67 | 1039099.55 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74361448.60 | 4938330.99 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43046585.57 | 19697603.13 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12598708.56 | 67015873.63 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 194561.19 | 0.162533E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238177E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385297E+09 | 0.110048E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1039099.55 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93016926.87 | 0.238177E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 85115186.72 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116087E+09 |
February | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68841.12 | 88506759.33 |
March | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 418333.17 | 78179453.29 |
April | 0.293479E+09 | 82467551.52 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10219447.96 | 31168503.50 |
May | 0.303504E+09 | 84776959.58 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26036944.85 | 9966168.72 |
June | 0.293842E+09 | 81813276.33 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47747618.14 | 1628055.16 |
July | 0.303141E+09 | 85442324.32 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46098320.75 | 524977.50 |
August | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38061564.81 | 2550374.99 |
September | 0.293479E+09 | 82489730.61 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21844058.25 | 10219469.72 |
October | 0.303322E+09 | 85104097.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6207817.75 | 35682585.25 |
November | 0.293661E+09 | 82140413.93 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87315.51 | 87222166.37 |
December | 0.303141E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128779E+09 |
Annual Sum or Average | 0.357224E+10 | 0.100055E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196790E+09 | 0.590515E+09 |
Minimum of Months | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524977.50 |
Maximum of Months | 0.303685E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47747618.14 | 0.128779E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.303266E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598194E+09 |
February | 0.415303E+11 | 0.271117E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 201718.65 | 0.466298E+09 |
March | 0.461508E+11 | 0.297615E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1422184.27 | 0.429250E+09 |
April | 0.445315E+11 | 0.281606E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36866679.92 | 0.202080E+09 |
May | 0.460320E+11 | 0.289246E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91539983.51 | 87106343.64 |
June | 0.446286E+11 | 0.278243E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174919E+09 | 26735499.79 |
July | 0.459349E+11 | 0.285773E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161704E+09 | 18650711.41 |
August | 0.461292E+11 | 0.292096E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133657E+09 | 36968701.38 |
September | 0.445099E+11 | 0.284760E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80929720.34 | 92811165.80 |
October | 0.459565E+11 | 0.299951E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22700708.61 | 0.227343E+09 |
November | 0.444343E+11 | 0.291802E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 317861.31 | 0.466757E+09 |
December | 0.459349E+11 | 0.301853E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655183E+09 |
Annual Sum or Average | 0.541708E+12 | 0.347733E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704260E+09 | 0.330738E+10 |
Minimum of Months | 0.415303E+11 | 0.271117E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18650711.41 |
Maximum of Months | 0.461508E+11 | 0.303266E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174919E+09 | 0.655183E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.303266E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614120E+09 |
February | 0.415303E+11 | 0.271117E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61527.57 | 0.479159E+09 |
March | 0.461508E+11 | 0.297615E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 865663.92 | 0.441495E+09 |
April | 0.445315E+11 | 0.281606E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33860057.72 | 0.207013E+09 |
May | 0.460320E+11 | 0.289246E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87173305.40 | 88879238.40 |
June | 0.446286E+11 | 0.278243E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170334E+09 | 27360894.01 |
July | 0.459349E+11 | 0.285773E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156889E+09 | 19203370.91 |
August | 0.461292E+11 | 0.292096E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129085E+09 | 37986160.22 |
September | 0.445099E+11 | 0.284760E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76638025.39 | 94589609.57 |
October | 0.459565E+11 | 0.299951E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20592345.07 | 0.233602E+09 |
November | 0.444343E+11 | 0.291802E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168963.36 | 0.479052E+09 |
December | 0.459349E+11 | 0.301853E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672004E+09 |
Annual Sum or Average | 0.541708E+12 | 0.347733E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675668E+09 | 0.339446E+10 |
Minimum of Months | 0.415303E+11 | 0.271117E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19203370.91 |
Maximum of Months | 0.461508E+11 | 0.303266E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170334E+09 | 0.672004E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113146E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590405E+09 |
February | 0.369574E+10 | 0.102161E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459816E+09 |
March | 0.410691E+10 | 0.113495E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 145836.58 | 0.421693E+09 |
April | 0.396281E+10 | 0.109310E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 25019302.69 | 0.195657E+09 |
May | 0.409635E+10 | 0.113342E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 71044630.10 | 82901612.37 |
June | 0.397146E+10 | 0.109811E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.146643E+09 | 25308908.97 |
July | 0.408770E+10 | 0.112841E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.134012E+09 | 17778574.91 |
August | 0.410499E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.108566E+09 | 35978299.03 |
September | 0.396089E+10 | 0.109354E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 60321794.10 | 87565776.64 |
October | 0.408962E+10 | 0.113103E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 14135195.38 | 0.222920E+09 |
November | 0.395417E+10 | 0.109724E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460037E+09 |
December | 0.408770E+10 | 0.112841E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645244E+09 |
Annual Sum or Average | 0.482060E+11 | 0.133267E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.559888E+09 | 0.324531E+10 |
Minimum of Months | 0.369574E+10 | 0.102161E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17778574.91 |
Maximum of Months | 0.410691E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.146643E+09 | 0.645244E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.246211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491336E+09 |
February | 0.368610E+10 | 0.222306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388363E+09 |
March | 0.409620E+10 | 0.246970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338206.08 | 0.362008E+09 |
April | 0.395248E+10 | 0.237864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24677835.69 | 0.179441E+09 |
May | 0.408566E+10 | 0.246638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69393879.34 | 79386528.21 |
June | 0.396110E+10 | 0.238954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143340E+09 | 24793430.74 |
July | 0.407704E+10 | 0.245547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130987E+09 | 17443091.07 |
August | 0.409429E+10 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106107E+09 | 35083183.95 |
September | 0.395056E+10 | 0.237958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58903007.63 | 84336211.65 |
October | 0.407896E+10 | 0.246116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13797901.10 | 0.207074E+09 |
November | 0.394385E+10 | 0.238765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399311E+09 |
December | 0.407704E+10 | 0.245547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536932E+09 |
Annual Sum or Average | 0.480803E+11 | 0.289994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547545E+09 | 0.280551E+10 |
Minimum of Months | 0.368610E+10 | 0.222306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17443091.07 |
Maximum of Months | 0.409620E+10 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143340E+09 | 0.536932E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 14185.34 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 14185.34 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 14185.34 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 14185.34 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 14185.34 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 14185.34 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 14185.34 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 14185.34 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 14185.34 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 14185.34 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 14185.34 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 14185.34 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 14185.34 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 14185.34 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 704.41 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 286.22 | 27-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 704.41 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 300.78 | 03-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 704.41 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.06 | 21-MAR-16:00 | 282.96 | 02-MAR-05:00 |
April | 1169.53 | 01-APR-00:10 | 704.41 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.90 | 21-APR-14:00 | 193.30 | 12-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 704.41 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.34 | 21-MAY-14:00 | 138.59 | 02-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 704.41 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.65 | 02-JUN-16:00 | 91.94 | 13-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 704.41 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.37 | 02-JUL-16:00 | 59.91 | 05-JUL-06:00 |
August | 1169.53 | 01-AUG-00:10 | 704.41 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.08 | 07-AUG-16:00 | 74.52 | 31-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 704.41 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.61 | 19-SEP-14:00 | 154.99 | 30-SEP-05:55 |
October | 1169.53 | 01-OCT-23:10 | 704.41 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.26 | 01-OCT-15:00 | 167.41 | 11-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 704.41 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 242.61 | 28-NOV-05:00 |
December | 1169.53 | 01-DEC-00:10 | 704.41 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 287.28 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 704.41 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.91 | |||||
Maximum of Months | 1169.53 | 704.41 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 144.65 | 300.78 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 815.72 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 115.87 | 27-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 815.72 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 | 20-FEB-15:00 | 121.82 | 03-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 815.72 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.97 | 22-MAR-13:00 | 114.76 | 02-MAR-05:30 |
April | 1354.32 | 01-APR-00:10 | 815.72 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.41 | 21-APR-14:00 | 83.06 | 12-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 815.72 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.13 | 19-MAY-14:00 | 58.90 | 02-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 815.72 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.12 | 02-JUN-16:00 | 36.48 | 13-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 815.72 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.76 | 02-JUL-16:00 | 24.95 | 05-JUL-06:00 |
August | 1354.32 | 01-AUG-00:10 | 815.72 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.83 | 07-AUG-16:00 | 29.64 | 31-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 815.72 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.14 | 19-SEP-14:00 | 64.24 | 30-SEP-05:55 |
October | 1354.32 | 01-OCT-23:10 | 815.72 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.66 | 01-OCT-15:00 | 70.65 | 25-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 815.72 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.27 | 03-NOV-16:00 | 101.13 | 17-NOV-04:00 |
December | 1354.32 | 01-DEC-00:10 | 815.72 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 115.51 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 815.72 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.95 | |||||
Maximum of Months | 1354.32 | 815.72 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 56.12 | 121.82 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 1360.40 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 265.04 | 27-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 1360.40 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.36 | 20-FEB-15:00 | 277.08 | 03-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 1360.40 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.11 | 21-MAR-16:00 | 262.21 | 02-MAR-05:30 |
April | 286.42 | 01-APR-00:10 | 1360.40 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.51 | 21-APR-14:00 | 193.55 | 12-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 1360.40 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.84 | 21-MAY-14:00 | 138.96 | 02-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 1360.40 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.95 | 02-JUN-16:00 | 86.21 | 13-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 1360.40 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.14 | 02-JUL-16:00 | 58.98 | 05-JUL-06:00 |
August | 286.42 | 01-AUG-00:10 | 1360.40 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.75 | 07-AUG-16:00 | 70.06 | 31-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 1360.40 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.05 | 19-SEP-14:00 | 152.01 | 30-SEP-05:55 |
October | 286.42 | 01-OCT-23:10 | 1360.40 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.58 | 01-OCT-15:00 | 164.92 | 11-OCT-06:00 |
November | 286.42 | 01-NOV-00:10 | 1360.40 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.19 | 08-NOV-15:00 | 230.72 | 17-NOV-04:00 |
December | 286.42 | 01-DEC-00:10 | 1360.40 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 262.67 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.98 | |||||
Maximum of Months | 286.42 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 131.95 | 277.08 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 227.72 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 150.64 | 27-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 227.72 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.37 | 20-FEB-15:00 | 158.30 | 03-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 227.72 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.41 | 21-MAR-16:00 | 148.92 | 02-MAR-05:20 |
April | 220.32 | 01-APR-00:10 | 227.72 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.09 | 21-APR-14:00 | 104.31 | 12-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 227.72 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.57 | 19-MAY-16:00 | 72.94 | 02-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 227.72 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.24 | 02-JUN-16:00 | 46.04 | 13-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 227.72 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.21 | 01-JUL-17:00 | 29.86 | 05-JUL-06:00 |
August | 220.32 | 01-AUG-00:10 | 227.72 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.07 | 07-AUG-16:00 | 35.56 | 31-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 227.72 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.98 | 19-SEP-16:00 | 80.68 | 30-SEP-05:55 |
October | 220.32 | 01-OCT-23:10 | 227.72 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.25 | 01-OCT-15:00 | 87.73 | 11-OCT-06:00 |
November | 220.32 | 01-NOV-00:10 | 227.72 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.07 | 03-NOV-16:00 | 127.67 | 28-NOV-05:00 |
December | 220.32 | 01-DEC-00:10 | 227.72 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 151.20 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 227.72 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.86 | |||||
Maximum of Months | 220.32 | 227.72 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 79.24 | 158.30 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 357.21 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 398.60 | 27-JAN-07:00 |
February | 907.20 | 01-FEB-00:10 | 357.21 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 416.88 | 03-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 357.21 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 12.53 | 21-MAR-16:00 | 394.88 | 02-MAR-06:00 |
April | 907.20 | 01-APR-00:10 | 357.21 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 100.77 | 21-APR-14:00 | 321.23 | 11-APR-05:25 |
May | 907.20 | 01-MAY-00:10 | 357.21 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 134.95 | 21-MAY-14:00 | 193.73 | 02-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 357.21 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 180.18 | 02-JUN-16:00 | 117.71 | 13-JUN-05:00 |
July | 907.20 | 01-JUL-00:10 | 357.21 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 173.60 | 02-JUL-16:00 | 80.53 | 05-JUL-06:00 |
August | 907.20 | 01-AUG-00:10 | 357.21 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 160.80 | 07-AUG-16:00 | 95.66 | 31-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 357.21 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 121.60 | 19-SEP-14:00 | 210.15 | 30-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 357.21 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 108.69 | 01-OCT-15:00 | 265.06 | 25-OCT-05:10 |
November | 907.20 | 01-NOV-00:10 | 357.21 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 342.57 | 28-NOV-01:00 |
December | 907.20 | 01-DEC-00:10 | 357.21 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 400.09 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 80.53 | ||||||
Maximum of Months | 907.20 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 180.18 | 416.88 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1761.91 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 636.98 | 27-JAN-07:00 |
February | 15368.40 | 01-FEB-00:10 | 1761.91 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 22-FEB-16:00 | 668.57 | 03-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1761.91 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.34 | 21-MAR-16:00 | 642.57 | 02-MAR-05:20 |
April | 15368.40 | 01-APR-00:10 | 1761.91 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.60 | 21-APR-15:00 | 467.39 | 13-APR-05:15 |
May | 15368.40 | 01-MAY-00:10 | 1761.91 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.29 | 21-MAY-14:00 | 309.47 | 02-MAY-06:00 |
June | 15368.40 | 01-JUN-00:10 | 1761.91 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.83 | 02-JUN-17:00 | 201.10 | 13-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1761.91 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.79 | 02-JUL-16:00 | 123.36 | 05-JUL-06:00 |
August | 15368.40 | 01-AUG-00:10 | 1761.91 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.10 | 07-AUG-16:00 | 153.45 | 31-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 1761.91 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.81 | 19-SEP-14:00 | 340.27 | 30-SEP-05:55 |
October | 15368.40 | 01-OCT-23:10 | 1761.91 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.91 | 01-OCT-15:00 | 404.49 | 25-OCT-03:10 |
November | 15368.40 | 01-NOV-00:10 | 1761.91 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.15 | 08-NOV-15:40 | 565.99 | 17-NOV-04:00 |
December | 15368.40 | 01-DEC-00:10 | 1761.91 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 648.73 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1761.91 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.36 | |||||
Maximum of Months | 15368.40 | 1761.91 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 332.83 | 668.57 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 10265.18 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1931.92 | 27-JAN-07:00 |
February | 45622.98 | 01-FEB-00:10 | 10265.18 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.19 | 20-FEB-16:00 | 2022.92 | 03-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 10265.18 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.36 | 22-MAR-13:00 | 1928.90 | 02-MAR-05:30 |
April | 45622.98 | 01-APR-00:10 | 10265.18 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 550.33 | 21-APR-14:00 | 1377.40 | 12-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 10265.18 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 721.73 | 19-MAY-14:00 | 973.67 | 02-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 10265.18 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 929.14 | 02-JUN-16:00 | 596.75 | 13-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 10265.18 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 917.71 | 02-JUL-16:00 | 408.22 | 05-JUL-06:00 |
August | 45622.98 | 01-AUG-00:10 | 10265.18 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 818.44 | 07-AUG-16:00 | 484.95 | 31-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 10265.18 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 624.25 | 19-SEP-14:00 | 1055.14 | 30-SEP-05:55 |
October | 45622.98 | 01-OCT-23:10 | 10265.18 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 566.91 | 01-OCT-15:00 | 1173.54 | 25-OCT-03:10 |
November | 45622.98 | 01-NOV-00:10 | 10265.18 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.78 | 08-NOV-15:00 | 1692.14 | 17-NOV-04:00 |
December | 45622.98 | 01-DEC-00:10 | 10265.18 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1940.25 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 10265.18 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.22 | |||||
Maximum of Months | 45622.98 | 10265.18 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 929.14 | 2022.92 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 167.12 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 | 20-FEB-16:07 | 175.57 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 21-MAR-16:00 | 165.23 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.17 | 21-APR-15:08 | 112.76 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.87 | 19-MAY-16:00 | 72.67 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.99 | 02-JUN-16:00 | 37.51 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.99 | 02-JUL-16:00 | 20.31 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.07 | 07-AUG-16:00 | 27.20 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.76 | 19-SEP-16:00 | 80.18 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.87 | 01-OCT-15:10 | 91.19 | 25-OCT-05:57 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 | 03-NOV-16:00 | 141.79 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 167.75 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 99.99 | 175.57 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 167.11 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 | 20-FEB-16:09 | 175.56 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 21-MAR-16:00 | 165.22 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.17 | 21-APR-15:07 | 112.76 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.86 | 19-MAY-16:00 | 72.66 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.99 | 02-JUN-16:00 | 37.51 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.99 | 02-JUL-16:00 | 20.31 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.07 | 07-AUG-16:00 | 27.20 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.85 | 19-SEP-16:00 | 80.18 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.01 | 01-OCT-15:10 | 91.18 | 25-OCT-05:57 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 | 03-NOV-16:00 | 141.78 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 167.73 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 99.99 | 175.56 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 76.99 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 46.05 | 27-JAN-07:20 |
February | 0.00 | 01-FEB-00:10 | 76.99 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 49.21 | 03-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 76.99 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.65 | 21-MAR-16:00 | 44.68 | 02-MAR-05:00 |
April | 0.00 | 01-APR-00:10 | 76.99 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.10 | 21-APR-14:00 | 32.51 | 12-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 76.99 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 | 21-MAY-14:00 | 23.15 | 02-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 76.99 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.41 | 02-JUN-16:00 | 14.23 | 13-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 76.99 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.55 | 02-JUL-16:00 | 8.93 | 05-JUL-06:00 |
August | 0.00 | 01-AUG-00:10 | 76.99 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.89 | 07-AUG-16:00 | 10.92 | 31-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 76.99 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.81 | 19-SEP-14:00 | 25.81 | 30-SEP-05:55 |
October | 0.00 | 01-OCT-00:10 | 76.99 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.13 | 01-OCT-15:00 | 28.42 | 25-OCT-06:00 |
November | 0.00 | 01-NOV-00:10 | 76.99 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 | 08-NOV-15:00 | 40.88 | 17-NOV-04:00 |
December | 0.00 | 01-DEC-00:10 | 76.99 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 46.50 | 19-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 76.99 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.93 | |||||
Maximum of Months | 0.00 | 76.99 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 24.41 | 49.21 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 77.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 46.64 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 77.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.26 | 20-FEB-16:04 | 49.00 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 77.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 | 21-MAR-16:00 | 46.11 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 77.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.35 | 21-APR-15:10 | 31.47 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 77.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.01 | 19-MAY-16:00 | 20.28 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 77.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.91 | 02-JUN-16:00 | 10.47 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 77.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.07 | 02-JUL-16:00 | 5.67 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 77.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.42 | 07-AUG-16:00 | 7.59 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 77.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 19-SEP-16:00 | 22.38 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 77.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.43 | 01-OCT-15:08 | 25.45 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 77.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.53 | 03-NOV-16:00 | 39.57 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 77.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 46.82 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | |||||
Maximum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 27.91 | 49.00 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 167.12 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 | 20-FEB-16:09 | 175.57 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 21-MAR-16:00 | 165.23 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.17 | 21-APR-15:08 | 112.76 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.87 | 19-MAY-16:00 | 72.67 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.99 | 02-JUN-16:00 | 37.51 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.99 | 02-JUL-16:00 | 21.07 | 05-JUL-07:10 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.08 | 07-AUG-16:00 | 28.62 | 30-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.85 | 19-SEP-16:00 | 80.18 | 30-SEP-05:55 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.01 | 01-OCT-15:10 | 91.19 | 25-OCT-05:57 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.24 | 03-NOV-16:00 | 141.79 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 167.75 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.07 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 99.99 | 175.57 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 167.11 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 | 20-FEB-16:06 | 175.56 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 21-MAR-16:00 | 165.22 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.17 | 21-APR-15:10 | 112.76 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.86 | 19-MAY-16:00 | 72.66 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.99 | 02-JUN-16:00 | 37.51 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.99 | 02-JUL-16:00 | 21.11 | 05-JUL-07:10 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.07 | 07-AUG-16:00 | 28.15 | 30-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.85 | 19-SEP-16:00 | 80.18 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.01 | 01-OCT-15:08 | 91.18 | 25-OCT-05:57 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 | 03-NOV-16:00 | 141.78 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 167.73 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.11 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 99.99 | 175.56 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 2240.78 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 201.84 | 27-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 2240.78 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.90 | 20-FEB-15:00 | 212.95 | 03-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 2240.78 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.21 | 21-MAR-16:00 | 202.38 | 02-MAR-05:20 |
April | 2263.36 | 01-APR-00:10 | 2240.78 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.87 | 21-APR-14:00 | 148.29 | 12-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 2240.78 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.74 | 21-MAY-14:00 | 105.49 | 02-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 2240.78 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.23 | 02-JUN-16:00 | 66.58 | 13-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 2240.78 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.52 | 02-JUL-16:00 | 45.03 | 05-JUL-06:00 |
August | 2263.36 | 01-AUG-00:10 | 2240.78 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.30 | 07-AUG-16:00 | 53.55 | 31-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 2240.78 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.22 | 19-SEP-14:00 | 115.80 | 30-SEP-05:55 |
October | 2263.36 | 01-OCT-23:10 | 2240.78 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.95 | 01-OCT-15:00 | 125.90 | 25-OCT-06:00 |
November | 2263.36 | 01-NOV-00:10 | 2240.78 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.27 | 08-NOV-15:00 | 180.56 | 17-NOV-04:00 |
December | 2263.36 | 01-DEC-00:10 | 2240.78 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 203.43 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.03 | ||||
Maximum of Months | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.23 | 212.95 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 167.55 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 20-FEB-16:07 | 176.00 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 | 21-MAR-16:00 | 165.66 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.84 | 21-APR-15:08 | 113.16 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.54 | 19-MAY-16:00 | 73.05 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.68 | 02-JUN-16:00 | 37.88 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.65 | 02-JUL-16:00 | 20.67 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.70 | 07-AUG-16:00 | 27.57 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.75 | 19-SEP-16:00 | 80.57 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.39 | 01-OCT-15:10 | 91.58 | 25-OCT-05:57 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.88 | 03-NOV-16:00 | 142.21 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 168.17 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 99.68 | 176.00 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 167.54 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 20-FEB-16:09 | 175.98 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 | 21-MAR-16:00 | 165.65 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.84 | 21-APR-15:07 | 113.15 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.54 | 19-MAY-16:00 | 73.05 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.67 | 02-JUN-16:00 | 37.88 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.64 | 02-JUL-16:00 | 20.67 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.72 | 07-AUG-16:00 | 27.57 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.51 | 19-SEP-16:00 | 80.56 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.68 | 01-OCT-15:10 | 91.58 | 25-OCT-05:57 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.88 | 03-NOV-16:00 | 142.20 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 168.16 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 99.67 | 175.98 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 77.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 85.72 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 77.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.80 | 20-FEB-16:09 | 90.05 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 77.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 21-MAR-16:00 | 84.76 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 77.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 | 21-APR-15:08 | 57.90 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 77.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.19 | 19-MAY-16:00 | 37.38 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 77.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 | 02-JUN-16:00 | 19.38 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 77.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.46 | 02-JUL-16:00 | 10.58 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 77.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.43 | 07-AUG-16:00 | 14.11 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 77.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.05 | 19-SEP-16:00 | 41.22 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 77.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.23 | 01-OCT-15:10 | 46.86 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 77.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 03-NOV-16:00 | 72.76 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 77.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 86.04 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.58 | |||||
Maximum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 | 90.05 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3094.06 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 433.72 | 27-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 3094.06 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.65 | 20-FEB-16:00 | 453.08 | 03-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3094.06 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.30 | 22-MAR-13:00 | 432.16 | 02-MAR-05:20 |
April | 26988.77 | 01-APR-00:10 | 3094.06 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.27 | 21-APR-14:00 | 324.32 | 13-APR-05:15 |
May | 26988.77 | 01-MAY-00:10 | 3094.06 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.43 | 19-MAY-14:00 | 220.84 | 02-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 3094.06 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.91 | 02-JUN-16:30 | 135.39 | 13-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3094.06 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.87 | 02-JUL-16:00 | 93.08 | 05-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 3094.06 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.92 | 07-AUG-16:00 | 110.32 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 3094.06 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.44 | 19-SEP-14:00 | 234.49 | 30-SEP-05:55 |
October | 26988.77 | 01-OCT-23:10 | 3094.06 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.07 | 01-OCT-15:00 | 275.70 | 25-OCT-03:10 |
November | 26988.77 | 01-NOV-00:10 | 3094.06 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.03 | 08-NOV-15:00 | 378.47 | 27-NOV-23:00 |
December | 26988.77 | 01-DEC-00:10 | 3094.06 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 433.31 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.08 | |||||
Maximum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 207.91 | 453.08 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3094.06 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 440.06 | 27-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 3094.06 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 | 20-FEB-16:00 | 459.19 | 03-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3094.06 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.02 | 22-MAR-13:00 | 437.52 | 02-MAR-05:20 |
April | 26988.77 | 01-APR-00:10 | 3094.06 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.28 | 21-APR-14:00 | 326.49 | 13-APR-05:15 |
May | 26988.77 | 01-MAY-00:10 | 3094.06 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.39 | 19-MAY-14:00 | 221.93 | 02-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 3094.06 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.68 | 02-JUN-16:00 | 135.40 | 13-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3094.06 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.48 | 02-JUL-16:00 | 93.08 | 05-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 3094.06 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.61 | 07-AUG-16:00 | 110.32 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 3094.06 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.59 | 19-SEP-14:00 | 237.71 | 30-SEP-05:55 |
October | 26988.77 | 01-OCT-23:10 | 3094.06 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.78 | 01-OCT-15:00 | 278.97 | 25-OCT-03:10 |
November | 26988.77 | 01-NOV-00:10 | 3094.06 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.14 | 08-NOV-15:00 | 382.33 | 27-NOV-23:00 |
December | 26988.77 | 01-DEC-00:10 | 3094.06 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 439.83 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.08 | |||||
Maximum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 203.68 | 459.19 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1089.83 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 407.41 | 27-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 1089.83 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 426.04 | 03-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1089.83 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 11.66 | 21-MAR-16:00 | 403.73 | 02-MAR-05:10 |
April | 2401.70 | 01-APR-00:10 | 1089.83 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 101.50 | 21-APR-14:00 | 332.08 | 11-APR-05:25 |
May | 2401.70 | 01-MAY-00:10 | 1089.83 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 136.32 | 21-MAY-14:00 | 198.79 | 02-MAY-06:07 |
June | 2401.70 | 01-JUN-00:10 | 1089.83 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 182.50 | 02-JUN-16:00 | 121.20 | 13-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1089.83 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 175.80 | 02-JUL-16:00 | 83.28 | 05-JUL-06:00 |
August | 2401.70 | 01-AUG-00:10 | 1089.83 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 162.76 | 07-AUG-16:00 | 98.71 | 31-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1089.83 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 122.73 | 19-SEP-14:00 | 215.40 | 30-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1089.83 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 109.59 | 01-OCT-15:00 | 269.05 | 25-OCT-03:10 |
November | 2401.70 | 01-NOV-00:10 | 1089.83 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 351.96 | 28-NOV-05:00 |
December | 2401.70 | 01-DEC-00:10 | 1089.83 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 408.95 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1089.83 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 83.28 | ||||||
Maximum of Months | 2401.70 | 1089.83 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 182.50 | 426.04 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 356.93 | 27-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 375.01 | 03-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.18 | 21-MAR-16:00 | 352.89 | 02-MAR-05:00 |
April | 2395.44 | 01-APR-00:10 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.23 | 21-APR-14:00 | 255.33 | 12-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.32 | 21-MAY-14:00 | 184.31 | 02-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.42 | 02-JUN-16:00 | 118.71 | 13-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.86 | 02-JUL-16:00 | 81.10 | 05-JUL-06:00 |
August | 2395.44 | 01-AUG-00:10 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.08 | 07-AUG-16:00 | 95.96 | 31-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.99 | 19-SEP-14:00 | 201.12 | 30-SEP-05:55 |
October | 2395.44 | 01-OCT-23:10 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.12 | 01-OCT-15:00 | 218.48 | 11-OCT-06:00 |
November | 2395.44 | 01-NOV-00:10 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 307.55 | 17-NOV-04:00 |
December | 2395.44 | 01-DEC-00:10 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 358.28 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.10 | ||||
Maximum of Months | 2395.44 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.42 | 375.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 36391.18 | 26-JAN-20:51 | 71567.33 | 113482.76 | 80910.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 34516.86 | 02-FEB-22:34 | 103517.03 | 85113.15 | 67070.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19817.85 | 17-MAR-03:44 | 115018.92 | 15762.30 | 21292.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17820.58 | 11-APR-04:30 | 46007.57 | 12609.11 | 12775.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14617.15 | 06-MAY-06:00 | 17891.83 | 9457.02 | 8516.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13973.73 | 23-JUN-21:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20668.26 | 19-JUL-21:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23564.24 | 24-AUG-21:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25575.64 | 21-SEP-21:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35484.32 | 25-OCT-05:30 | 26837.75 | 18913.67 | 15969.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 40523.33 | 19-NOV-23:56 | 102239.04 | 47285.09 | 42584.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 37239.34 | 02-DEC-07:38 | 51119.52 | 37828.07 | 34067.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13973.73 | 10223.90 | 9457.02 | 8516.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40523.33 | 115018.92 | 113482.76 | 80910.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3119.63 | 26-JAN-12:32 | 2598.96 | 1956.71 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.04 |
February | 3000.98 | 07-FEB-13:30 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.97 |
March | 2431.99 | 16-MAR-13:10 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.34 |
April | 2529.23 | 03-APR-14:10 | 389.84 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 27.21 | 0.00 |
May | 2489.31 | 19-MAY-18:15 | 1819.27 | 1252.29 | 1299.04 | 0.00 | 0.00 | 0.00 | 0.00 | 88.23 | 0.00 |
June | 2868.32 | 15-JUN-18:15 | 1819.27 | 1252.29 | 1299.04 | 0.00 | 0.00 | 0.00 | 0.00 | 114.74 | 0.00 |
July | 2836.02 | 26-JUL-18:03 | 5457.82 | 3756.88 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 96.65 | 0.00 |
August | 3004.70 | 27-AUG-12:00 | 389.84 | 234.80 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 92.38 | 0.00 |
September | 3612.28 | 19-SEP-13:20 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 90.60 | 0.00 |
October | 3750.87 | 18-OCT-13:00 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 38.38 | 0.00 |
November | 3487.24 | 10-NOV-12:00 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.81 |
December | 3219.97 | 21-DEC-12:55 | 519.79 | 391.34 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2431.99 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3750.87 | 5457.82 | 3756.88 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 114.74 | 213.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2549.95 | 04-JAN-22:44 | 13543.20 | 5438.10 | 5850.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.45 |
February | 3206.90 | 08-FEB-22:01 | 9480.24 | 3806.67 | 4095.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.43 |
March | 2819.68 | 20-MAR-22:00 | 13543.20 | 5438.10 | 5850.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.46 |
April | 2086.76 | 28-APR-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.75 |
May | 2281.44 | 19-MAY-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 23.06 | 0.00 |
June | 2494.28 | 15-JUN-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 35.40 | 0.00 |
July | 2428.08 | 25-JUL-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 0.00 |
August | 2462.69 | 07-AUG-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 29.59 | 0.00 |
September | 2333.05 | 20-SEP-20:10 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.47 | 0.00 |
October | 2249.81 | 05-OCT-20:10 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 |
November | 2182.30 | 26-NOV-00:14 | 7373.52 | 1903.34 | 2340.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.05 |
December | 2254.77 | 06-DEC-22:20 | 2708.64 | 1087.62 | 1170.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2086.76 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3206.90 | 13543.20 | 5438.10 | 5850.02 | 0.00 | 0.00 | 0.00 | 0.00 | 35.40 | 88.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1283.31 | 02-JAN-00:33 | 859.25 | 906.93 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.47 |
February | 1242.12 | 05-FEB-00:17 | 668.30 | 1360.40 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.99 |
March | 1404.18 | 17-MAR-03:44 | 2864.16 | 1511.55 | 1767.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.39 |
April | 1865.10 | 21-APR-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 19.19 | 0.00 |
May | 2295.32 | 31-MAY-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 49.33 | 0.00 |
June | 2636.68 | 15-JUN-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 88.47 | 0.00 |
July | 2583.04 | 03-JUL-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 39.39 | 0.00 |
August | 2509.96 | 07-AUG-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 69.70 | 0.00 |
September | 2190.86 | 22-SEP-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 19.36 | 0.00 |
October | 2052.43 | 05-OCT-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 |
November | 1347.33 | 26-NOV-00:14 | 1559.38 | 3174.26 | 2474.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.61 |
December | 1121.34 | 30-DEC-10:29 | 954.72 | 4534.65 | 3534.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1121.34 | 222.77 | 906.93 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2636.68 | 2864.16 | 4534.65 | 3534.51 | 0.00 | 0.00 | 0.00 | 0.00 | 88.47 | 178.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1154.20 | 02-JAN-00:33 | 660.96 | 151.81 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.80 |
February | 1068.91 | 05-FEB-00:17 | 514.08 | 227.72 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.48 |
March | 1269.36 | 17-MAR-03:44 | 2203.20 | 253.02 | 509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.08 |
April | 1118.84 | 11-APR-04:30 | 881.28 | 202.41 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.47 |
May | 916.63 | 31-MAY-18:07 | 1028.16 | 1214.49 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 39.58 | 0.00 |
June | 984.89 | 15-JUN-21:00 | 195.84 | 202.41 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 48.26 | 0.00 |
July | 976.50 | 03-JUL-10:35 | 97.92 | 126.52 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 54.50 | 0.00 |
August | 967.48 | 06-AUG-10:35 | 146.88 | 151.81 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 43.12 | 0.00 |
September | 919.71 | 25-SEP-03:12 | 1101.60 | 126.51 | 254.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.10 |
October | 1070.36 | 25-OCT-04:07 | 660.96 | 151.81 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.96 |
November | 1205.92 | 26-NOV-00:14 | 1199.52 | 531.34 | 713.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.89 |
December | 976.33 | 09-DEC-23:15 | 342.72 | 151.81 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 916.63 | 97.92 | 126.51 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1269.36 | 2203.20 | 1214.49 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 54.50 | 95.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 51918.33 | 26-JAN-20:51 | 5644.80 | 2857.71 | 36582.41 | 317812.61 | 0.00 | 0.00 | 0.00 | 0.00 | 291.23 |
February | 52902.86 | 08-FEB-20:40 | 2822.40 | 1428.86 | 18291.20 | 158906.31 | 0.00 | 0.00 | 0.00 | 0.00 | 300.11 |
March | 49190.93 | 28-MAR-21:27 | 7257.60 | 1905.14 | 26955.46 | 234177.71 | 0.00 | 0.00 | 0.00 | 0.00 | 278.45 |
April | 39211.09 | 12-APR-06:38 | 3628.80 | 1786.07 | 25992.76 | 225814.22 | 0.00 | 0.00 | 0.00 | 0.00 | 252.87 |
May | 39365.87 | 30-MAY-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 61.21 | 0.00 |
June | 39770.82 | 15-JUN-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 120.81 | 0.00 |
July | 39720.01 | 03-JUL-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 53.78 | 0.00 |
August | 39636.36 | 04-AUG-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 114.33 | 0.00 |
September | 39287.97 | 20-SEP-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 20.15 | 0.00 |
October | 39041.42 | 05-OCT-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 |
November | 49602.81 | 27-NOV-21:46 | 8064.00 | 3175.23 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 308.79 |
December | 50674.71 | 29-DEC-22:56 | 9072.00 | 2381.43 | 33694.32 | 292722.14 | 0.00 | 0.00 | 0.00 | 0.00 | 310.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 39041.42 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52902.86 | 9072.00 | 3175.23 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 120.81 | 310.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14942.01 | 02-JAN-00:33 | 46105.20 | 1174.60 | 914.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.55 |
February | 14006.05 | 05-FEB-00:17 | 35859.60 | 1761.91 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 381.61 |
March | 15671.14 | 17-MAR-03:44 | 153684.00 | 1957.67 | 2032.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.14 |
April | 13392.31 | 11-APR-04:30 | 61473.60 | 1566.14 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.24 |
May | 11195.62 | 19-MAY-21:10 | 15368.40 | 1174.60 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 130.00 | 0.00 |
June | 11957.56 | 15-JUN-21:10 | 15368.40 | 1174.60 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 187.22 | 0.00 |
July | 11819.14 | 26-JUL-21:10 | 15368.40 | 1174.60 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 102.76 | 0.00 |
August | 12366.60 | 07-AUG-21:10 | 15368.40 | 1174.60 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 159.89 | 0.00 |
September | 12330.40 | 20-SEP-15:03 | 51228.00 | 1791.27 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 203.11 | 0.00 |
October | 12897.92 | 25-OCT-04:07 | 46105.20 | 1174.60 | 914.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.74 |
November | 14769.65 | 26-NOV-00:14 | 83672.40 | 4111.11 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.64 |
December | 20257.70 | 23-DEC-00:33 | 61473.60 | 1566.14 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11195.62 | 15368.40 | 1174.60 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20257.70 | 153684.00 | 4111.11 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 203.11 | 429.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 62095.90 | 20-JAN-00:05 | 182491.92 | 9124.61 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1352.04 |
February | 62404.06 | 17-FEB-01:00 | 456229.80 | 22811.52 | 31671.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1320.55 |
March | 61348.30 | 20-MAR-22:00 | 456229.80 | 68434.56 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.67 |
April | 62847.71 | 11-APR-04:15 | 182491.92 | 9124.61 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1271.45 |
May | 41462.75 | 31-MAY-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 262.55 | 0.00 |
June | 44225.37 | 15-JUN-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 534.78 | 0.00 |
July | 43583.03 | 26-JUL-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 293.47 | 0.00 |
August | 44431.94 | 07-AUG-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 456.69 | 0.00 |
September | 42454.93 | 21-SEP-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 134.26 | 0.00 |
October | 41653.58 | 05-OCT-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.67 |
November | 60457.17 | 11-NOV-06:10 | 141938.16 | 13686.91 | 16891.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1249.99 |
December | 53643.45 | 29-DEC-22:56 | 456229.80 | 68434.56 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1480.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 41462.75 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 62847.71 | 456229.80 | 68434.56 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 534.78 | 1480.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3247.51 | 03-JAN-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.29 |
February | 3439.09 | 20-FEB-16:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 | 0.00 |
March | 3456.16 | 21-MAR-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 0.00 |
April | 3568.37 | 16-APR-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 40.16 | 0.00 |
May | 3588.67 | 20-MAY-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 54.86 | 0.00 |
June | 3584.50 | 15-JUN-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 87.71 | 0.00 |
July | 3230.66 | 11-JUL-08:61 | 252.00 | 377.32 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 30.07 | 0.00 |
August | 3214.32 | 08-AUG-18:01 | 970.20 | 763.21 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 38.64 | 0.00 |
September | 3586.97 | 30-SEP-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 32.75 | 0.00 |
October | 3558.55 | 21-OCT-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 20.47 | 0.00 |
November | 3447.44 | 09-NOV-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 | 0.00 |
December | 3117.46 | 23-DEC-16:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3117.46 | 252.00 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3588.67 | 970.20 | 763.21 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 87.71 | 34.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3111.70 | 12-JAN-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.30 |
February | 3368.39 | 20-FEB-16:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 4.05 | 0.00 |
March | 3389.10 | 21-MAR-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 12.45 | 0.00 |
April | 3526.43 | 30-APR-18:01 | 819.00 | 857.43 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 41.22 | 0.00 |
May | 3561.12 | 20-MAY-18:01 | 819.00 | 857.43 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 51.09 | 0.00 |
June | 3568.43 | 15-JUN-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 75.03 | 0.00 |
July | 3198.73 | 11-JUL-08:61 | 252.00 | 377.27 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 29.92 | 0.00 |
August | 3207.09 | 08-AUG-18:01 | 970.20 | 763.12 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 38.69 | 0.00 |
September | 3525.56 | 30-SEP-15:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 33.40 | 0.00 |
October | 3487.99 | 21-OCT-15:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 0.00 |
November | 3380.84 | 09-NOV-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 4.55 | 0.00 |
December | 2896.50 | 16-DEC-16:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2896.50 | 252.00 | 240.08 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3568.43 | 970.20 | 857.43 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 75.03 | 43.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 558.38 | 12-JAN-14:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.09 |
February | 539.78 | 07-FEB-13:40 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 |
March | 439.99 | 16-MAR-13:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.45 |
April | 426.99 | 04-APR-13:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 | 0.00 |
May | 383.28 | 19-MAY-20:20 | 0.00 | 68.52 | 180.59 | 0.00 | 0.00 | 0.00 | 0.00 | 11.84 | 0.00 |
June | 441.43 | 15-JUN-17:13 | 0.00 | 154.75 | 394.73 | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 0.00 |
July | 441.85 | 26-JUL-17:17 | 0.00 | 206.33 | 526.30 | 0.00 | 0.00 | 0.00 | 0.00 | 18.79 | 0.00 |
August | 495.40 | 27-AUG-13:40 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 0.00 |
September | 600.10 | 19-SEP-13:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 15.96 | 0.00 |
October | 668.60 | 22-OCT-13:20 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 | 0.00 |
November | 624.97 | 09-NOV-13:50 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
December | 472.07 | 16-DEC-14:10 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 383.28 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 668.60 | 0.00 | 206.33 | 526.30 | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 14.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 676.35 | 15-JAN-09:01 | 540.00 | 431.26 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.16 |
February | 971.53 | 20-FEB-09:01 | 378.00 | 301.88 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 |
March | 1093.48 | 21-MAR-18:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 | 0.00 |
April | 1232.45 | 21-APR-18:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | 0.00 |
May | 1236.05 | 20-MAY-18:01 | 819.00 | 539.08 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 14.05 | 0.00 |
June | 1237.53 | 02-JUN-18:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 22.20 | 0.00 |
July | 1152.04 | 26-JUL-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 21.93 | 0.00 |
August | 1150.75 | 04-AUG-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 20.60 | 0.00 |
September | 1205.75 | 11-SEP-18:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 | 0.00 |
October | 1127.84 | 19-OCT-18:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 | 0.00 |
November | 1052.74 | 08-NOV-19:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 |
December | 833.91 | 09-DEC-09:02 | 324.00 | 258.76 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 676.35 | 324.00 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1237.53 | 970.20 | 539.08 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 22.20 | 23.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2836.05 | 12-JAN-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.55 |
February | 3000.13 | 20-FEB-16:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3.58 | 0.00 |
March | 3029.28 | 21-MAR-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 | 0.00 |
April | 3119.04 | 03-APR-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 25.21 | 0.00 |
May | 3137.75 | 20-MAY-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 55.10 | 0.00 |
June | 3174.63 | 15-JUN-08:61 | 252.00 | 377.32 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 | 0.00 |
July | 2881.59 | 31-JUL-08:61 | 252.00 | 377.32 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 0.00 |
August | 2900.48 | 03-AUG-08:61 | 252.00 | 377.32 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 20.74 | 0.00 |
September | 3132.17 | 30-SEP-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 33.08 | 0.00 |
October | 3108.16 | 21-OCT-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 0.00 |
November | 3013.95 | 09-NOV-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 4.03 | 0.00 |
December | 2696.77 | 16-DEC-09:02 | 324.00 | 411.62 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2696.77 | 252.00 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3174.63 | 680.40 | 411.62 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 55.10 | 87.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2276.70 | 04-JAN-09:02 | 216.00 | 323.38 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.27 |
February | 2849.07 | 21-FEB-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 | 0.00 |
March | 2966.97 | 22-MAR-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 8.68 | 0.00 |
April | 3087.53 | 30-APR-18:01 | 819.00 | 857.43 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 41.34 | 0.00 |
May | 3111.84 | 20-MAY-15:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 55.14 | 0.00 |
June | 3155.16 | 15-JUN-08:61 | 252.00 | 377.27 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 40.56 | 0.00 |
July | 2853.82 | 30-JUL-18:01 | 819.00 | 857.43 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 36.06 | 0.00 |
August | 2886.28 | 08-AUG-18:01 | 970.20 | 763.12 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 38.38 | 0.00 |
September | 3077.04 | 30-SEP-15:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 33.73 | 0.00 |
October | 3043.82 | 21-OCT-15:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 21.64 | 0.00 |
November | 2888.40 | 09-NOV-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 6.73 | 0.00 |
December | 2481.58 | 09-DEC-09:02 | 324.00 | 411.57 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2276.70 | 216.00 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3155.16 | 970.20 | 857.43 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 55.14 | 76.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2569.02 | 02-JAN-00:33 | 6790.07 | 1493.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.83 |
February | 2469.44 | 05-FEB-00:17 | 5281.16 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.25 |
March | 2808.05 | 17-MAR-03:44 | 22633.56 | 2489.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.91 |
April | 2501.63 | 11-APR-04:30 | 9053.42 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.52 |
May | 2978.06 | 19-MAY-18:30 | 1760.39 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.39 | 0.00 |
June | 3484.42 | 15-JUN-18:30 | 1760.39 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.01 | 0.00 |
July | 3338.51 | 26-JUL-18:30 | 1760.39 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.99 | 0.00 |
August | 3246.25 | 07-AUG-18:30 | 1760.39 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.61 | 0.00 |
September | 2954.46 | 20-SEP-18:15 | 3520.78 | 3983.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.45 | 0.00 |
October | 2774.72 | 05-OCT-20:10 | 2011.87 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.76 |
November | 2685.56 | 26-NOV-00:14 | 12322.72 | 5228.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.76 |
December | 2351.43 | 30-DEC-10:29 | 7544.52 | 7469.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2351.43 | 1760.39 | 1493.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3484.42 | 22633.56 | 7469.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.01 | 136.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3420.04 | 12-JAN-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.76 |
February | 3634.62 | 20-FEB-16:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3.06 | 0.00 |
March | 3648.58 | 21-MAR-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 11.62 | 0.00 |
April | 3783.45 | 16-APR-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 39.85 | 0.00 |
May | 3804.08 | 20-MAY-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 54.57 | 0.00 |
June | 3804.09 | 15-JUN-15:02 | 583.20 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 87.36 | 0.00 |
July | 3408.84 | 18-JUL-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 46.35 | 0.00 |
August | 3392.37 | 07-AUG-08:61 | 252.00 | 377.32 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 35.30 | 0.00 |
September | 3795.06 | 30-SEP-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 32.58 | 0.00 |
October | 3764.56 | 21-OCT-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 20.29 | 0.00 |
November | 3643.32 | 09-NOV-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 3.65 | 0.00 |
December | 3286.20 | 23-DEC-16:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3286.20 | 252.00 | 205.81 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3804.09 | 831.60 | 654.18 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 87.36 | 34.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3236.63 | 12-JAN-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.30 |
February | 3547.18 | 20-FEB-16:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 0.00 |
March | 3566.03 | 21-MAR-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 12.53 | 0.00 |
April | 3732.07 | 16-APR-15:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 40.18 | 0.00 |
May | 3769.84 | 20-MAY-15:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 54.60 | 0.00 |
June | 3778.58 | 15-JUN-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 74.74 | 0.00 |
July | 3388.15 | 18-JUL-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 46.35 | 0.00 |
August | 3371.89 | 08-AUG-18:01 | 970.20 | 763.12 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 38.53 | 0.00 |
September | 3722.01 | 30-SEP-15:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 33.28 | 0.00 |
October | 3679.37 | 21-OCT-15:01 | 378.00 | 282.96 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 21.22 | 0.00 |
November | 3559.50 | 09-NOV-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 4.58 | 0.00 |
December | 2964.76 | 16-DEC-16:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2964.76 | 324.00 | 240.08 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3778.58 | 970.20 | 763.12 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 74.74 | 41.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1772.29 | 03-JAN-16:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 |
February | 1855.93 | 20-FEB-16:01 | 378.00 | 177.90 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 0.00 |
March | 1866.12 | 14-MAR-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 | 0.00 |
April | 1906.52 | 03-APR-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 12.38 | 0.00 |
May | 1902.35 | 20-MAY-15:01 | 378.00 | 177.90 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 27.95 | 0.00 |
June | 1900.33 | 02-JUN-18:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 41.03 | 0.00 |
July | 1743.60 | 14-JUL-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 19.84 | 0.00 |
August | 1739.45 | 08-AUG-18:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 0.00 |
September | 1924.95 | 30-SEP-15:01 | 378.00 | 177.90 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 | 0.00 |
October | 1922.88 | 21-OCT-15:01 | 378.00 | 177.90 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 9.70 | 0.00 |
November | 1864.39 | 09-NOV-16:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 | 0.00 |
December | 1701.11 | 23-DEC-16:01 | 378.00 | 177.90 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1701.11 | 378.00 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1924.95 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 41.03 | 18.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 31715.93 | 31-JAN-23:56 | 188921.38 | 7219.46 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.76 |
February | 32423.09 | 15-FEB-23:57 | 80966.30 | 3094.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.94 |
March | 31224.39 | 06-MAR-05:33 | 161932.61 | 4125.41 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.38 |
April | 31628.14 | 10-APR-22:40 | 269887.68 | 10313.52 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.53 |
May | 22834.90 | 31-MAY-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 57.52 | 0.00 |
June | 23624.35 | 15-JUN-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 118.64 | 0.00 |
July | 23302.86 | 26-JUL-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 64.45 | 0.00 |
August | 23491.52 | 07-AUG-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 101.10 | 0.00 |
September | 22133.37 | 22-SEP-22:00 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 12.98 | 0.00 |
October | 23528.26 | 25-OCT-04:07 | 80966.30 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.54 |
November | 31188.99 | 15-NOV-23:33 | 269887.68 | 10313.52 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.72 |
December | 31123.70 | 11-DEC-24:00 | 134943.84 | 5156.76 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22133.37 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32423.09 | 269887.68 | 10313.52 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 118.64 | 299.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33452.42 | 31-JAN-23:56 | 188921.38 | 7219.46 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.06 |
February | 34429.07 | 15-FEB-23:57 | 80966.30 | 3094.06 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.44 |
March | 41485.29 | 17-MAR-04:10 | 269887.68 | 6875.68 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.99 |
April | 33198.84 | 10-APR-22:40 | 269887.68 | 10313.52 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.94 |
May | 24215.24 | 31-MAY-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 57.52 | 0.00 |
June | 24968.40 | 15-JUN-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 108.54 | 0.00 |
July | 24677.13 | 26-JUL-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 64.45 | 0.00 |
August | 24855.02 | 07-AUG-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 101.10 | 0.00 |
September | 23407.56 | 22-SEP-22:00 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 12.98 | 0.00 |
October | 24427.14 | 25-OCT-05:30 | 62973.79 | 4125.41 | 16869.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.29 |
November | 34719.95 | 19-NOV-23:56 | 239900.16 | 10313.52 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.84 |
December | 33070.92 | 11-DEC-24:00 | 134943.84 | 5156.76 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 23407.56 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41485.29 | 269887.68 | 10313.52 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 108.54 | 305.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35265.66 | 07-JAN-09:28 | 8005.68 | 4843.69 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 287.15 |
February | 36234.04 | 28-FEB-06:44 | 18679.92 | 4843.69 | 125511.30 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 263.88 |
March | 34265.88 | 25-MAR-06:36 | 13342.80 | 3632.77 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 257.65 |
April | 33388.45 | 10-APR-22:40 | 24017.04 | 3632.77 | 149128.56 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 237.16 |
May | 30390.24 | 21-MAY-10:40 | 1601.14 | 726.55 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 68.28 | 0.00 |
June | 30978.20 | 18-JUN-10:40 | 1601.14 | 726.55 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 105.06 | 0.00 |
July | 31125.63 | 02-JUL-10:40 | 1601.14 | 726.55 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 101.94 | 0.00 |
August | 31022.49 | 06-AUG-10:50 | 800.57 | 363.28 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 98.79 | 0.00 |
September | 30629.34 | 17-SEP-10:40 | 1601.14 | 726.55 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 68.49 | 0.00 |
October | 30051.23 | 05-OCT-10:40 | 1067.42 | 605.46 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 44.90 | 0.00 |
November | 34879.55 | 16-NOV-08:24 | 10674.24 | 4843.69 | 149128.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 279.91 |
December | 38375.89 | 27-DEC-11:51 | 4269.70 | 2421.85 | 119302.85 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 294.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 30051.23 | 800.57 | 363.28 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38375.89 | 24017.04 | 4843.69 | 149128.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 105.06 | 294.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3775.47 | 02-JAN-00:33 | 7186.32 | 1581.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.12 |
February | 3678.03 | 05-FEB-00:17 | 5589.36 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.34 |
March | 4215.58 | 17-MAR-03:44 | 23954.40 | 2635.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.41 |
April | 5114.38 | 30-APR-13:00 | 532.32 | 527.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.23 | 0.00 |
May | 6045.78 | 30-MAY-15:02 | 7984.80 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.38 | 0.00 |
June | 6869.13 | 15-JUN-18:03 | 11178.72 | 12648.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.44 | 0.00 |
July | 7016.23 | 03-JUL-14:30 | 798.48 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.42 | 0.00 |
August | 6858.41 | 07-AUG-15:03 | 7984.80 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.67 | 0.00 |
September | 6544.93 | 20-SEP-15:03 | 7984.80 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.86 | 0.00 |
October | 6189.78 | 03-OCT-13:30 | 532.32 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.86 | 0.00 |
November | 3930.51 | 26-NOV-00:14 | 13041.84 | 5533.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.51 |
December | 3536.94 | 30-DEC-10:29 | 7984.80 | 7905.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3536.94 | 532.32 | 527.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7016.23 | 23954.40 | 12648.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.42 | 237.51 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.391960E+12 | 254868.63 | 26-JAN-20:49 | 0.488058E+12 | 441915.32 | 21-JAN-23:00 |
February | 0.363791E+12 | 272887.96 | 06-FEB-20:10 | 0.419068E+12 | 415108.00 | 02-FEB-19:30 |
March | 0.413908E+12 | 296573.83 | 14-MAR-18:10 | 0.438537E+12 | 396407.70 | 01-MAR-19:40 |
April | 0.474905E+12 | 354674.04 | 19-APR-19:19 | 0.395346E+12 | 349889.22 | 10-APR-16:00 |
May | 0.563893E+12 | 384067.05 | 19-MAY-19:10 | 0.387873E+12 | 347076.51 | 01-MAY-17:40 |
June | 0.618819E+12 | 413212.08 | 05-JUN-19:10 | 0.364103E+12 | 319653.96 | 08-JUN-17:19 |
July | 0.674194E+12 | 416814.12 | 25-JUL-19:10 | 0.369527E+12 | 316679.48 | 03-JUL-17:10 |
August | 0.635053E+12 | 410466.14 | 04-AUG-19:19 | 0.369877E+12 | 316821.37 | 31-AUG-17:10 |
September | 0.573611E+12 | 385256.26 | 22-SEP-19:19 | 0.364707E+12 | 319436.01 | 29-SEP-17:19 |
October | 0.491342E+12 | 380386.93 | 03-OCT-19:00 | 0.391479E+12 | 347117.52 | 31-OCT-17:40 |
November | 0.400454E+12 | 301512.76 | 09-NOV-20:00 | 0.426542E+12 | 417936.25 | 27-NOV-19:30 |
December | 0.391194E+12 | 249254.54 | 06-DEC-20:10 | 0.486019E+12 | 451554.94 | 18-DEC-21:49 |
Annual Sum or Average | 0.599312E+13 | 0.490114E+13 | ||||
Minimum of Months | 0.363791E+12 | 249254.54 | 0.364103E+12 | 316679.48 | ||
Maximum of Months | 0.674194E+12 | 416814.12 | 0.488058E+12 | 451554.94 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.654470E+11 | 0.238585E+11 | 0.148212E+12 | 0.553309E+11 | 0.472598E+11 | 0.845661E+10 | 0.00 | 0.113613E+11 | 0.00 | 0.00 | 0.191094E+11 | 0.770402E+10 | 0.00 |
February | 0.589941E+11 | 0.204104E+11 | 0.133859E+12 | 0.499764E+11 | 0.417046E+11 | 0.922705E+10 | 0.00 | 0.238075E+11 | 0.00 | 0.00 | 0.141537E+11 | 0.696171E+10 | 0.00 |
March | 0.652284E+11 | 0.209758E+11 | 0.148223E+12 | 0.553337E+11 | 0.461421E+11 | 0.114630E+11 | 0.00 | 0.403665E+11 | 0.00 | 0.00 | 0.132818E+11 | 0.770276E+10 | 0.00 |
April | 0.628662E+11 | 0.186678E+11 | 0.143397E+12 | 0.535455E+11 | 0.485914E+11 | 0.156889E+11 | 0.00 | 0.108445E+12 | 0.00 | 0.00 | 0.112123E+11 | 0.746487E+10 | 0.00 |
May | 0.649547E+11 | 0.178892E+11 | 0.148223E+12 | 0.553320E+11 | 0.552393E+11 | 0.187007E+11 | 0.00 | 0.175666E+12 | 0.00 | 0.00 | 0.149343E+11 | 0.770424E+10 | 0.00 |
June | 0.627939E+11 | 0.166101E+11 | 0.143446E+12 | 0.535482E+11 | 0.594682E+11 | 0.197178E+11 | 0.00 | 0.231373E+12 | 0.00 | 0.00 | 0.192805E+11 | 0.745687E+10 | 0.00 |
July | 0.647873E+11 | 0.174721E+11 | 0.148174E+12 | 0.553291E+11 | 0.620224E+11 | 0.210605E+11 | 0.00 | 0.270882E+12 | 0.00 | 0.00 | 0.214183E+11 | 0.771238E+10 | 0.00 |
August | 0.650572E+11 | 0.186678E+11 | 0.148234E+12 | 0.553337E+11 | 0.621478E+11 | 0.205544E+11 | 0.00 | 0.234206E+12 | 0.00 | 0.00 | 0.178023E+11 | 0.770435E+10 | 0.00 |
September | 0.629931E+11 | 0.195762E+11 | 0.143408E+12 | 0.535457E+11 | 0.590797E+11 | 0.192066E+11 | 0.00 | 0.190406E+12 | 0.00 | 0.00 | 0.127684E+11 | 0.746622E+10 | 0.00 |
October | 0.653122E+11 | 0.219305E+11 | 0.148201E+12 | 0.553308E+11 | 0.554219E+11 | 0.166280E+11 | 0.00 | 0.107001E+12 | 0.00 | 0.00 | 0.852904E+10 | 0.770291E+10 | 0.00 |
November | 0.632978E+11 | 0.226443E+11 | 0.143462E+12 | 0.535468E+11 | 0.491732E+11 | 0.106225E+11 | 0.00 | 0.327012E+11 | 0.00 | 0.00 | 0.125192E+11 | 0.744854E+10 | 0.00 |
December | 0.653599E+11 | 0.242107E+11 | 0.148174E+12 | 0.553296E+11 | 0.483219E+11 | 0.808571E+10 | 0.00 | 0.862815E+10 | 0.00 | 0.00 | 0.201634E+11 | 0.771224E+10 | 0.00 |
Annual Sum or Average | 0.767092E+12 | 0.242914E+12 | 0.174501E+13 | 0.651482E+12 | 0.634572E+12 | 0.179412E+12 | 0.00 | 0.143484E+13 | 0.00 | 0.00 | 0.185173E+12 | 0.907411E+11 | 0.00 |
Minimum of Months | 0.589941E+11 | 0.166101E+11 | 0.133859E+12 | 0.499764E+11 | 0.417046E+11 | 0.808571E+10 | 0.00 | 0.862815E+10 | 0.00 | 0.00 | 0.852904E+10 | 0.696171E+10 | 0.00 |
Maximum of Months | 0.654470E+11 | 0.242107E+11 | 0.148234E+12 | 0.553337E+11 | 0.621478E+11 | 0.210605E+11 | 0.00 | 0.270882E+12 | 0.00 | 0.00 | 0.214183E+11 | 0.771238E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.706266E+11 | 0.00 | 0.265514E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.421249E+11 | 0.00 | 0.239739E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.272596E+11 | 0.00 | 0.259254E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.825313E+10 | 0.00 | 0.240137E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.619206E+09 | 0.00 | 0.235275E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 77712501.15 | 0.00 | 0.216912E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 73199593.94 | 0.00 | 0.217633E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 92449919.67 | 0.00 | 0.217746E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.767954E+09 | 0.00 | 0.216968E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.423069E+10 | 0.00 | 0.235345E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.392705E+11 | 0.00 | 0.240180E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.749945E+11 | 0.00 | 0.259204E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.268390E+12 | 0.00 | 0.284391E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 73199593.94 | 0.00 | 0.216912E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.749945E+11 | 0.00 | 0.265514E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 62892.57 | 02-JAN-20:10 | 15448.40 | 01-JAN-00:10 | 89475.41 | 02-JAN-07:10 | 39726.11 | 02-JAN-07:19 | 36368.83 | 09-JAN-22:49 | 6600.30 | 12-JAN-16:10 | 0.00 | 01-JAN-00:10 |
February | 62892.57 | 01-FEB-20:10 | 15448.40 | 01-FEB-00:10 | 89475.41 | 01-FEB-07:10 | 39726.11 | 01-FEB-07:19 | 40938.68 | 08-FEB-21:19 | 7381.78 | 20-FEB-16:10 | 0.00 | 01-FEB-00:10 |
March | 62892.57 | 01-MAR-20:10 | 15448.40 | 01-MAR-00:10 | 89475.41 | 01-MAR-07:10 | 39726.11 | 13-MAR-06:19 | 36144.00 | 20-MAR-22:30 | 7505.52 | 22-MAR-15:30 | 0.00 | 01-MAR-00:10 |
April | 62892.57 | 03-APR-19:10 | 15448.40 | 01-APR-00:10 | 89475.41 | 03-APR-06:10 | 39726.11 | 04-APR-06:19 | 37803.09 | 21-APR-21:10 | 8360.94 | 28-APR-19:10 | 0.00 | 01-APR-00:10 |
May | 62892.57 | 01-MAY-19:10 | 15448.40 | 01-MAY-00:10 | 89475.41 | 01-MAY-06:10 | 39725.67 | 03-MAY-06:19 | 42287.52 | 31-MAY-21:10 | 8462.84 | 19-MAY-18:10 | 0.00 | 01-MAY-00:10 |
June | 62892.57 | 01-JUN-19:10 | 15448.40 | 01-JUN-00:10 | 89475.41 | 01-JUN-06:10 | 39724.49 | 01-JUN-06:19 | 45740.26 | 15-JUN-21:10 | 8609.49 | 05-JUN-19:10 | 0.00 | 01-JUN-00:10 |
July | 62892.57 | 03-JUL-19:19 | 15448.40 | 01-JUL-00:10 | 89475.41 | 03-JUL-06:10 | 39725.08 | 19-JUL-06:19 | 47887.56 | 26-JUL-21:10 | 8638.43 | 18-JUL-20:49 | 0.00 | 01-JUL-00:10 |
August | 62892.57 | 01-AUG-19:10 | 15448.40 | 01-AUG-00:10 | 89475.41 | 01-AUG-06:10 | 39726.11 | 14-AUG-06:19 | 50591.54 | 07-AUG-21:10 | 8595.97 | 01-AUG-20:00 | 0.00 | 01-AUG-00:10 |
September | 62892.57 | 01-SEP-19:10 | 15448.40 | 01-SEP-00:10 | 89475.41 | 01-SEP-06:10 | 39726.11 | 25-SEP-06:19 | 49298.70 | 22-SEP-21:10 | 8557.53 | 18-SEP-19:10 | 0.00 | 01-SEP-00:10 |
October | 62892.57 | 02-OCT-19:10 | 15448.40 | 01-OCT-00:10 | 89475.41 | 02-OCT-06:10 | 39726.11 | 02-OCT-06:19 | 48560.58 | 05-OCT-21:10 | 8496.33 | 03-OCT-19:00 | 0.00 | 01-OCT-00:10 |
November | 62892.57 | 01-NOV-19:10 | 15448.40 | 01-NOV-00:10 | 89475.41 | 01-NOV-06:10 | 39726.11 | 01-NOV-06:19 | 45508.09 | 15-NOV-22:00 | 8192.89 | 03-NOV-15:50 | 0.00 | 01-NOV-00:10 |
December | 62892.57 | 01-DEC-20:10 | 15448.40 | 01-DEC-00:10 | 89475.41 | 01-DEC-07:10 | 39726.11 | 11-DEC-07:19 | 36719.63 | 18-DEC-21:49 | 5987.04 | 23-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 62892.57 | 15448.40 | 89475.41 | 39724.49 | 36144.00 | 5987.04 | 0.00 | |||||||
Maximum of Months | 62892.57 | 15448.40 | 89475.41 | 39726.11 | 50591.54 | 8638.43 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 51245.69 | 03-JAN-14:00 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4738.44 | 12-JAN-19:10 | 0.00 |
February | 72211.41 | 20-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 4738.12 | 16-FEB-19:10 | 0.00 |
March | 75046.59 | 22-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:10 | 4738.38 | 14-MAR-06:49 | 0.00 |
April | 114379.47 | 21-APR-18:10 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4738.63 | 06-APR-18:10 | 0.00 |
May | 134776.07 | 19-MAY-18:19 | 0.00 | 0.00 | 9938.94 | 02-MAY-00:20 | 4738.59 | 25-MAY-18:10 | 0.00 |
June | 167567.16 | 14-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-00:10 | 4738.66 | 08-JUN-18:10 | 0.00 |
July | 167034.93 | 26-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUL-00:10 | 4738.58 | 20-JUL-18:10 | 0.00 |
August | 155823.93 | 04-AUG-18:10 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 4738.58 | 24-AUG-18:10 | 0.00 |
September | 135124.49 | 20-SEP-15:20 | 0.00 | 0.00 | 9938.94 | 01-SEP-08:20 | 4738.75 | 07-SEP-18:10 | 0.00 |
October | 129899.53 | 04-OCT-18:10 | 0.00 | 0.00 | 9938.94 | 01-OCT-09:50 | 4738.57 | 05-OCT-18:10 | 0.00 |
November | 77018.79 | 03-NOV-15:50 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4738.29 | 17-NOV-07:10 | 0.00 |
December | 33154.39 | 23-DEC-14:00 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:30 | 4738.15 | 28-DEC-07:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 33154.39 | 0.00 | 0.00 | 9938.94 | 4738.12 | 0.00 | |||
Maximum of Months | 167567.16 | 0.00 | 0.00 | 9938.94 | 4738.75 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 254868.63 | 26-JAN-20:49 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 33499.00 | 4389.14 | 0.00 | 1300.49 | 0.00 |
February | 272887.96 | 06-FEB-20:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 22652.94 | 6123.83 | 0.00 | 38428.59 | 0.00 |
March | 296573.83 | 14-MAR-18:10 | 55920.94 | 79417.81 | 15448.40 | 31837.02 | 24074.01 | 7380.55 | 0.00 | 74880.82 | 0.00 |
April | 354674.04 | 19-APR-19:19 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 28239.19 | 7918.21 | 0.00 | 102992.14 | 0.00 |
May | 384067.05 | 19-MAY-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 34756.14 | 8441.51 | 0.00 | 126244.94 | 0.00 |
June | 413212.08 | 05-JUN-19:10 | 62892.57 | 88772.42 | 15448.40 | 32150.87 | 34715.41 | 8609.49 | 0.00 | 154282.50 | 0.00 |
July | 416814.12 | 25-JUL-19:10 | 62892.57 | 88772.42 | 15448.40 | 32150.62 | 38655.68 | 8348.76 | 0.00 | 155051.09 | 0.00 |
August | 410466.14 | 04-AUG-19:19 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 41025.11 | 8303.98 | 0.00 | 146090.61 | 0.00 |
September | 385256.26 | 22-SEP-19:19 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 38427.66 | 8309.66 | 0.00 | 123457.06 | 0.00 |
October | 380386.93 | 03-OCT-19:00 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 35808.93 | 8496.33 | 0.00 | 129776.14 | 0.00 |
November | 301512.76 | 09-NOV-20:00 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 29725.21 | 7257.47 | 0.00 | 59164.46 | 0.00 |
December | 249254.54 | 06-DEC-20:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 26141.90 | 4569.37 | 0.00 | 3339.27 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 249254.54 | 55920.94 | 79417.81 | 15448.40 | 31837.02 | 22652.94 | 4389.14 | 0.00 | 1300.49 | 0.00 | |
Maximum of Months | 416814.12 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 41025.11 | 8609.49 | 0.00 | 155051.09 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 191594.86 | 03-JAN-01:10 | 0.00 | 255618.32 | 04-JAN-21:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 186468.17 | 11-FEB-05:19 | 0.00 | 256972.59 | 27-FEB-21:30 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 179492.34 | 31-MAR-04:10 | 0.00 | 248249.89 | 28-MAR-20:49 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 140457.05 | 12-APR-04:40 | 0.00 | 247428.25 | 10-APR-20:00 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 53882.71 | 02-MAY-05:30 | 0.00 | 242828.19 | 01-MAY-17:40 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 5233.45 | 01-JUN-08:09 | 0.00 | 218918.91 | 01-JUN-19:10 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 5796.36 | 05-JUL-08:09 | 0.00 | 212834.69 | 03-JUL-20:30 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 7283.87 | 24-AUG-08:09 | 0.00 | 212989.50 | 31-AUG-20:40 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 72313.48 | 25-SEP-04:00 | 0.00 | 220732.35 | 30-SEP-21:40 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 91486.65 | 25-OCT-04:00 | 0.00 | 243495.20 | 31-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 171303.53 | 30-NOV-00:30 | 0.00 | 246599.43 | 28-NOV-18:30 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 181612.06 | 18-DEC-04:19 | 0.00 | 253960.68 | 22-DEC-21:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 5233.45 | 0.00 | 212834.69 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 191594.86 | 0.00 | 256972.59 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 31.83 | 25.26 | 31.83 | 25.26 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 25.25 | 21.00 | 25.25 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 25.08 | 11.33 | 25.08 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 25.16 | 4.50 | 25.16 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.84 | 1.17 | 24.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 25.03 | 21.33 | 25.03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 25.06 | 32.33 | 25.06 |
Annual Sum or Average | 0.00 | 0.00 | 123.50 | 25.14 | 123.50 | 25.14 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 25.26 | 32.33 | 25.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.77 | 0.67 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.88 | 3.00 | 21.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.77 | 1.83 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.84 | 1.67 | 21.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.82 | 0.83 | 21.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.83 | 21.82 | 8.83 | 21.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.88 | 3.00 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.73 | 1.00 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.89 | 3.33 | 21.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.72 | 1.00 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.17 | 21.81 | 6.17 | 21.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.89 | 3.33 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.76 | 1.67 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.17 | 21.75 | 2.17 | 21.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.76 | 1.67 | 21.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.78 | 0.33 | 21.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.76 | 0.50 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.79 | 1.67 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.74 | 0.50 | 21.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.74 | 0.33 | 21.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.83 | 0.17 | 21.83 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.00 | 21.76 | 4.00 | 21.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.83 | 1.67 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.77 | 0.33 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.78 | 0.50 | 21.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.79 | 2.00 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 21.77 | 3.17 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.79 | 2.00 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.83 | 0.67 | 21.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 21.88 | 5.00 | 21.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.80 | 1.00 | 21.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.80 | 2.67 | 21.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.84 | 2.50 | 21.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.80 | 1.00 | 21.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13.17 | 21.84 | 13.17 | 21.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 21.88 | 5.00 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.77 | 1.00 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 21.88 | 5.83 | 21.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.77 | 1.33 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.75 | 1.83 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.50 | 21.82 | 10.50 | 21.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 21.88 | 5.83 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.77 | 0.83 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.76 | 0.83 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.87 | 3.50 | 21.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.96 | 3.50 | 21.96 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.00 | 0.33 | 22.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.17 | 21.89 | 9.17 | 21.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 22.00 | 3.50 | 22.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.80 | 1.67 | 24.80 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.83 | 0.67 | 24.83 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.87 | 0.67 | 24.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.93 | 0.17 | 24.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.57 | 0.33 | 24.57 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.72 | 0.33 | 24.72 |
Annual Sum or Average | 0.00 | 0.00 | 3.83 | 24.80 | 3.83 | 24.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.93 | 1.67 | 24.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.88 | 2.17 | 24.88 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.81 | 1.50 | 24.81 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.97 | 0.67 | 24.97 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.69 | 1.00 | 24.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.64 | 0.17 | 24.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.67 | 1.00 | 24.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.66 | 2.00 | 24.66 |
Annual Sum or Average | 0.00 | 0.00 | 8.50 | 24.77 | 8.50 | 24.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.97 | 2.17 | 24.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 | 25.17 | 36.67 | 25.17 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 | 25.20 | 24.00 | 25.20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 25.14 | 14.00 | 25.14 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 25.25 | 5.50 | 25.25 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.88 | 1.33 | 24.88 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 | 25.12 | 29.83 | 25.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 40.50 | 25.14 | 40.50 | 25.14 |
Annual Sum or Average | 0.00 | 0.00 | 151.83 | 25.15 | 151.83 | 25.15 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 40.50 | 25.25 | 40.50 | 25.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 580.17 | 23.89 | 0.00 | 23.89 | 0.00 | 23.89 |
February | 665.17 | 23.39 | 0.00 | 23.39 | 0.00 | 23.39 |
March | 744.00 | 22.63 | 0.00 | 22.63 | 0.00 | 22.63 |
April | 720.00 | 22.71 | 0.00 | 22.71 | 0.00 | 22.71 |
May | 733.83 | 23.02 | 12.00 | 23.02 | 12.00 | 23.03 |
June | 595.17 | 23.26 | 82.50 | 23.30 | 65.50 | 23.32 |
July | 384.67 | 23.93 | 634.00 | 23.92 | 364.67 | 23.93 |
August | 219.00 | 24.00 | 643.17 | 23.98 | 219.00 | 23.99 |
September | 201.33 | 24.00 | 501.33 | 24.00 | 201.33 | 24.00 |
October | 98.83 | 24.00 | 308.50 | 24.00 | 45.17 | 24.00 |
November | 396.00 | 24.00 | 18.83 | 24.00 | 0.00 | 24.00 |
December | 550.83 | 23.99 | 0.00 | 23.99 | 0.00 | 23.99 |
Annual Sum or Average | 5889.00 | 23.39 | 2200.33 | 23.54 | 907.67 | 23.58 |
Minimum of Months | 98.83 | 22.63 | 0.00 | 22.63 | 0.00 | 22.63 |
Maximum of Months | 744.00 | 24.00 | 643.17 | 24.00 | 364.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 606.50 | 22.03 | 38.17 | 22.09 | 11.00 | 22.07 |
February | 539.17 | 22.29 | 17.50 | 22.29 | 8.50 | 22.27 |
March | 609.17 | 22.53 | 6.00 | 22.51 | 6.00 | 22.50 |
April | 390.67 | 23.10 | 76.83 | 23.24 | 0.00 | 23.24 |
May | 181.00 | 23.46 | 320.17 | 23.79 | 14.50 | 23.80 |
June | 74.17 | 23.87 | 614.00 | 23.97 | 54.00 | 23.97 |
July | 351.00 | 23.98 | 744.00 | 23.99 | 351.00 | 23.98 |
August | 227.67 | 23.90 | 728.50 | 23.95 | 227.67 | 23.94 |
September | 241.33 | 23.82 | 610.50 | 23.93 | 214.00 | 23.92 |
October | 268.33 | 23.04 | 360.00 | 23.56 | 59.50 | 23.58 |
November | 484.17 | 22.36 | 88.00 | 22.55 | 11.83 | 22.52 |
December | 623.50 | 21.88 | 45.00 | 21.83 | 42.83 | 21.78 |
Annual Sum or Average | 4596.67 | 22.71 | 3648.67 | 23.24 | 1000.83 | 23.29 |
Minimum of Months | 74.17 | 21.88 | 6.00 | 21.83 | 0.00 | 21.78 |
Maximum of Months | 623.50 | 23.98 | 744.00 | 23.99 | 351.00 | 23.98 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 735.83 | 22.67 | 0.00 | 22.67 | 0.00 | 22.67 |
February | 666.83 | 22.87 | 0.00 | 22.87 | 0.00 | 22.87 |
March | 732.17 | 23.02 | 0.00 | 23.02 | 0.00 | 23.02 |
April | 534.83 | 23.39 | 22.17 | 23.42 | 0.00 | 23.42 |
May | 245.00 | 23.52 | 210.50 | 23.70 | 18.67 | 23.71 |
June | 114.00 | 23.84 | 433.83 | 23.92 | 61.00 | 23.92 |
July | 375.33 | 23.95 | 732.67 | 23.91 | 375.33 | 23.92 |
August | 254.83 | 23.91 | 673.83 | 23.89 | 253.17 | 23.90 |
September | 262.83 | 23.90 | 539.17 | 23.90 | 237.50 | 23.91 |
October | 303.33 | 23.41 | 235.33 | 23.60 | 73.83 | 23.62 |
November | 630.33 | 23.03 | 3.83 | 23.04 | 0.00 | 23.04 |
December | 744.00 | 22.51 | 0.00 | 22.51 | 0.00 | 22.51 |
Annual Sum or Average | 5599.33 | 23.13 | 2851.33 | 23.39 | 1019.50 | 23.45 |
Minimum of Months | 114.00 | 22.51 | 0.00 | 22.51 | 0.00 | 22.51 |
Maximum of Months | 744.00 | 23.95 | 732.67 | 23.92 | 375.33 | 23.92 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.96 | 0.00 | 21.96 | 0.00 | 21.96 |
February | 672.00 | 22.25 | 0.00 | 22.25 | 0.00 | 22.25 |
March | 744.00 | 22.61 | 0.00 | 22.61 | 0.00 | 22.61 |
April | 650.17 | 23.48 | 0.00 | 23.48 | 0.00 | 23.48 |
May | 348.00 | 23.87 | 143.17 | 23.91 | 1.17 | 23.91 |
June | 105.33 | 24.00 | 341.33 | 24.00 | 12.17 | 24.00 |
July | 232.67 | 24.00 | 733.50 | 24.00 | 232.67 | 24.00 |
August | 117.50 | 23.98 | 631.17 | 23.99 | 117.50 | 23.99 |
September | 213.67 | 23.94 | 479.50 | 23.98 | 144.00 | 23.98 |
October | 506.83 | 23.51 | 123.33 | 23.60 | 14.67 | 23.61 |
November | 719.50 | 22.66 | 0.00 | 22.66 | 0.00 | 22.66 |
December | 744.00 | 21.75 | 0.00 | 21.75 | 0.00 | 21.75 |
Annual Sum or Average | 5797.67 | 22.79 | 2452.00 | 23.15 | 522.17 | 23.20 |
Minimum of Months | 105.33 | 21.75 | 0.00 | 21.75 | 0.00 | 21.75 |
Maximum of Months | 744.00 | 24.00 | 733.50 | 24.00 | 232.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.09 | 40.17 | 21.08 | 40.17 | 21.08 |
February | 672.00 | 21.24 | 31.33 | 21.23 | 31.33 | 21.22 |
March | 744.00 | 21.44 | 13.00 | 21.43 | 13.00 | 21.43 |
April | 720.00 | 22.28 | 0.00 | 22.28 | 0.00 | 22.28 |
May | 718.33 | 22.95 | 1.50 | 22.95 | 1.50 | 22.95 |
June | 437.50 | 23.36 | 47.50 | 23.39 | 11.33 | 23.39 |
July | 312.17 | 23.36 | 407.50 | 23.47 | 241.33 | 23.46 |
August | 436.83 | 23.17 | 191.33 | 23.25 | 121.33 | 23.26 |
September | 617.50 | 23.00 | 147.50 | 23.03 | 140.67 | 23.04 |
October | 726.00 | 22.41 | 14.33 | 22.42 | 14.33 | 22.43 |
November | 720.00 | 21.53 | 0.00 | 21.53 | 0.00 | 21.53 |
December | 744.00 | 21.04 | 51.83 | 21.04 | 51.83 | 21.04 |
Annual Sum or Average | 7592.33 | 22.09 | 946.00 | 22.20 | 666.83 | 22.25 |
Minimum of Months | 312.17 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
Maximum of Months | 744.00 | 23.36 | 407.50 | 23.47 | 241.33 | 23.46 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 201.83 | 24.25 | 736.17 | 24.07 | 201.83 | 24.10 |
February | 174.67 | 24.18 | 665.83 | 24.04 | 174.67 | 24.07 |
March | 191.83 | 24.08 | 738.33 | 24.01 | 191.67 | 24.02 |
April | 236.33 | 24.02 | 716.67 | 24.01 | 236.33 | 24.01 |
May | 383.17 | 24.00 | 744.00 | 24.00 | 383.17 | 24.00 |
June | 523.33 | 24.00 | 720.00 | 24.00 | 523.33 | 24.00 |
July | 737.17 | 24.00 | 744.00 | 24.00 | 737.17 | 24.00 |
August | 682.00 | 24.00 | 744.00 | 24.00 | 682.00 | 24.00 |
September | 608.33 | 24.00 | 720.00 | 24.00 | 608.33 | 24.00 |
October | 412.00 | 24.00 | 744.00 | 23.99 | 412.00 | 23.99 |
November | 205.00 | 24.11 | 715.50 | 24.02 | 205.00 | 24.04 |
December | 172.17 | 24.24 | 732.67 | 24.06 | 172.00 | 24.09 |
Annual Sum or Average | 4527.83 | 24.04 | 8721.17 | 24.01 | 4527.50 | 24.02 |
Minimum of Months | 172.17 | 24.00 | 665.83 | 23.99 | 172.00 | 23.99 |
Maximum of Months | 737.17 | 24.25 | 744.00 | 24.07 | 737.17 | 24.10 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 629.00 | 22.24 | 46.17 | 22.35 | 0.00 | 22.35 |
February | 568.00 | 22.36 | 38.00 | 22.46 | 0.00 | 22.46 |
March | 671.17 | 22.39 | 6.33 | 22.40 | 0.00 | 22.40 |
April | 514.00 | 22.58 | 42.33 | 22.67 | 0.00 | 22.67 |
May | 392.50 | 22.69 | 212.17 | 22.97 | 63.67 | 23.01 |
June | 231.17 | 23.16 | 455.00 | 23.43 | 139.67 | 23.46 |
July | 501.00 | 23.49 | 710.00 | 23.42 | 494.67 | 23.45 |
August | 396.33 | 23.42 | 695.33 | 23.43 | 381.83 | 23.44 |
September | 362.00 | 23.45 | 636.17 | 23.55 | 325.17 | 23.55 |
October | 352.17 | 22.84 | 388.33 | 23.27 | 135.83 | 23.29 |
November | 483.67 | 22.43 | 130.67 | 22.75 | 0.00 | 22.75 |
December | 648.67 | 22.12 | 27.67 | 22.19 | 0.17 | 22.19 |
Annual Sum or Average | 5749.67 | 22.67 | 3388.17 | 22.99 | 1541.00 | 23.07 |
Minimum of Months | 231.17 | 22.12 | 6.33 | 22.19 | 0.00 | 22.19 |
Maximum of Months | 671.17 | 23.49 | 710.00 | 23.55 | 494.67 | 23.55 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 692.17 | 23.01 | 0.00 | 23.01 | 0.00 | 23.01 |
February | 629.00 | 23.15 | 2.00 | 23.15 | 0.00 | 23.15 |
March | 673.67 | 23.16 | 6.50 | 23.16 | 0.00 | 23.16 |
April | 453.50 | 23.28 | 53.00 | 23.36 | 0.00 | 23.36 |
May | 256.50 | 23.36 | 241.00 | 23.61 | 59.33 | 23.63 |
June | 174.33 | 23.72 | 464.67 | 23.84 | 125.33 | 23.84 |
July | 505.83 | 23.86 | 730.17 | 23.81 | 505.83 | 23.83 |
August | 389.17 | 23.83 | 710.17 | 23.80 | 388.67 | 23.81 |
September | 345.33 | 23.87 | 622.33 | 23.86 | 337.83 | 23.86 |
October | 251.67 | 23.51 | 374.67 | 23.71 | 137.17 | 23.73 |
November | 502.50 | 23.20 | 28.83 | 23.24 | 0.00 | 23.24 |
December | 733.83 | 22.94 | 0.00 | 22.94 | 0.00 | 22.94 |
Annual Sum or Average | 5607.50 | 23.32 | 3233.33 | 23.51 | 1554.17 | 23.56 |
Minimum of Months | 174.33 | 22.94 | 0.00 | 22.94 | 0.00 | 22.94 |
Maximum of Months | 733.83 | 23.87 | 730.17 | 23.86 | 505.83 | 23.86 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.26 | 168.83 | 21.18 | 168.83 | 21.12 |
February | 672.00 | 21.37 | 124.00 | 21.31 | 124.00 | 21.27 |
March | 744.00 | 21.46 | 65.00 | 21.42 | 65.00 | 21.39 |
April | 702.33 | 21.59 | 0.83 | 21.59 | 0.83 | 21.59 |
May | 676.17 | 21.53 | 3.17 | 21.54 | 0.00 | 21.54 |
June | 615.50 | 21.47 | 13.33 | 21.51 | 0.00 | 21.51 |
July | 593.83 | 21.33 | 48.50 | 21.47 | 4.67 | 21.48 |
August | 607.33 | 21.36 | 35.83 | 21.47 | 1.50 | 21.47 |
September | 585.33 | 21.35 | 38.00 | 21.47 | 2.50 | 21.47 |
October | 680.33 | 21.48 | 14.83 | 21.52 | 3.33 | 21.51 |
November | 712.67 | 21.43 | 86.50 | 21.36 | 86.50 | 21.31 |
December | 744.00 | 21.21 | 275.83 | 21.13 | 275.83 | 21.08 |
Annual Sum or Average | 8077.50 | 21.40 | 874.67 | 21.39 | 733.00 | 21.36 |
Minimum of Months | 585.33 | 21.21 | 0.83 | 21.13 | 0.00 | 21.08 |
Maximum of Months | 744.00 | 21.59 | 275.83 | 21.59 | 275.83 | 21.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.90 | 400.83 | 20.82 | 400.83 | 20.78 |
February | 672.00 | 21.07 | 289.83 | 21.00 | 289.83 | 20.96 |
March | 744.00 | 21.27 | 126.67 | 21.21 | 126.67 | 21.16 |
April | 709.50 | 21.55 | 7.50 | 21.54 | 7.50 | 21.54 |
May | 682.33 | 21.54 | 2.83 | 21.55 | 0.00 | 21.55 |
June | 620.33 | 21.49 | 14.33 | 21.53 | 0.00 | 21.53 |
July | 597.33 | 21.34 | 44.00 | 21.47 | 4.33 | 21.48 |
August | 629.17 | 21.42 | 21.17 | 21.48 | 1.67 | 21.48 |
September | 627.33 | 21.45 | 11.33 | 21.48 | 3.00 | 21.48 |
October | 720.50 | 21.47 | 6.83 | 21.47 | 5.17 | 21.47 |
November | 720.00 | 21.20 | 176.67 | 21.12 | 176.67 | 21.07 |
December | 744.00 | 20.83 | 578.17 | 20.79 | 578.17 | 20.77 |
Annual Sum or Average | 8210.50 | 21.28 | 1680.17 | 21.22 | 1593.83 | 21.16 |
Minimum of Months | 597.33 | 20.83 | 2.83 | 20.79 | 0.00 | 20.77 |
Maximum of Months | 744.00 | 21.55 | 578.17 | 21.55 | 578.17 | 21.55 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.96 | 333.00 | 20.92 | 333.00 | 20.90 |
February | 672.00 | 21.04 | 242.33 | 21.01 | 242.33 | 20.98 |
March | 744.00 | 21.15 | 115.33 | 21.13 | 115.33 | 21.11 |
April | 720.00 | 21.36 | 3.50 | 21.36 | 3.50 | 21.36 |
May | 744.00 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
June | 720.00 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
July | 744.00 | 21.64 | 5.33 | 21.64 | 5.33 | 21.64 |
August | 744.00 | 21.57 | 0.33 | 21.57 | 0.33 | 21.57 |
September | 720.00 | 21.49 | 3.67 | 21.49 | 3.67 | 21.49 |
October | 744.00 | 21.31 | 0.00 | 21.31 | 0.00 | 21.31 |
November | 720.00 | 21.07 | 187.17 | 21.04 | 187.17 | 21.02 |
December | 744.00 | 20.93 | 455.83 | 20.89 | 455.83 | 20.87 |
Annual Sum or Average | 8760.00 | 21.31 | 1346.50 | 21.25 | 1346.50 | 21.21 |
Minimum of Months | 672.00 | 20.93 | 0.00 | 20.89 | 0.00 | 20.87 |
Maximum of Months | 744.00 | 21.64 | 455.83 | 21.64 | 455.83 | 21.64 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.29 | 162.50 | 21.22 | 162.50 | 21.17 |
February | 672.00 | 21.46 | 102.17 | 21.41 | 102.17 | 21.37 |
March | 744.00 | 21.56 | 62.17 | 21.52 | 62.17 | 21.49 |
April | 703.67 | 21.68 | 1.83 | 21.68 | 1.83 | 21.68 |
May | 673.17 | 21.58 | 1.17 | 21.58 | 0.00 | 21.58 |
June | 578.00 | 21.37 | 5.00 | 21.38 | 0.00 | 21.38 |
July | 555.50 | 21.21 | 15.33 | 21.27 | 2.17 | 21.27 |
August | 570.67 | 21.26 | 7.83 | 21.28 | 1.50 | 21.28 |
September | 555.83 | 21.28 | 7.83 | 21.30 | 0.83 | 21.31 |
October | 674.83 | 21.50 | 5.17 | 21.50 | 4.83 | 21.50 |
November | 719.50 | 21.50 | 92.17 | 21.42 | 92.17 | 21.37 |
December | 744.00 | 21.23 | 279.00 | 21.16 | 279.00 | 21.12 |
Annual Sum or Average | 7935.17 | 21.42 | 742.17 | 21.39 | 709.17 | 21.36 |
Minimum of Months | 555.50 | 21.21 | 1.17 | 21.16 | 0.00 | 21.12 |
Maximum of Months | 744.00 | 21.68 | 279.00 | 21.68 | 279.00 | 21.68 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.90 | 420.00 | 20.85 | 420.00 | 20.83 |
February | 672.00 | 21.14 | 246.50 | 21.08 | 246.50 | 21.05 |
March | 744.00 | 21.38 | 104.33 | 21.33 | 104.33 | 21.29 |
April | 711.67 | 21.67 | 5.67 | 21.67 | 5.67 | 21.67 |
May | 676.00 | 21.58 | 1.50 | 21.59 | 0.00 | 21.59 |
June | 577.50 | 21.37 | 6.67 | 21.39 | 0.00 | 21.39 |
July | 554.67 | 21.21 | 16.17 | 21.27 | 1.83 | 21.27 |
August | 581.50 | 21.29 | 7.17 | 21.32 | 1.33 | 21.32 |
September | 599.17 | 21.41 | 6.00 | 21.43 | 1.00 | 21.43 |
October | 725.33 | 21.55 | 11.33 | 21.55 | 11.17 | 21.54 |
November | 720.00 | 21.18 | 167.17 | 21.12 | 167.17 | 21.08 |
December | 744.00 | 20.83 | 563.00 | 20.80 | 563.00 | 20.78 |
Annual Sum or Average | 8049.83 | 21.29 | 1555.50 | 21.22 | 1522.00 | 21.17 |
Minimum of Months | 554.67 | 20.83 | 1.50 | 20.80 | 0.00 | 20.78 |
Maximum of Months | 744.00 | 21.67 | 563.00 | 21.67 | 563.00 | 21.67 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.79 | 0.00 | 21.79 | 0.00 | 21.79 |
February | 672.00 | 22.14 | 0.00 | 22.14 | 0.00 | 22.14 |
March | 744.00 | 22.46 | 0.00 | 22.46 | 0.00 | 22.46 |
April | 696.67 | 23.33 | 0.00 | 23.33 | 0.00 | 23.33 |
May | 428.00 | 23.77 | 126.83 | 23.80 | 33.00 | 23.81 |
June | 195.33 | 23.96 | 312.83 | 23.96 | 75.50 | 23.96 |
July | 460.50 | 23.97 | 727.50 | 23.97 | 460.50 | 23.97 |
August | 327.67 | 23.90 | 608.00 | 23.93 | 327.67 | 23.92 |
September | 367.33 | 23.90 | 485.00 | 23.93 | 285.83 | 23.94 |
October | 599.00 | 23.48 | 157.83 | 23.53 | 97.17 | 23.53 |
November | 720.00 | 22.67 | 0.00 | 22.67 | 0.00 | 22.67 |
December | 744.00 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
Annual Sum or Average | 6698.50 | 22.84 | 2418.00 | 23.13 | 1279.67 | 23.23 |
Minimum of Months | 195.33 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
Maximum of Months | 744.00 | 23.97 | 727.50 | 23.97 | 460.50 | 23.97 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.14 | 349.17 | 21.04 | 349.17 | 20.99 |
February | 672.00 | 21.27 | 268.67 | 21.17 | 268.67 | 21.12 |
March | 744.00 | 21.38 | 179.17 | 21.29 | 179.17 | 21.24 |
April | 693.83 | 21.53 | 36.67 | 21.51 | 35.83 | 21.48 |
May | 662.33 | 21.48 | 9.17 | 21.51 | 0.00 | 21.51 |
June | 587.83 | 21.38 | 32.83 | 21.49 | 0.17 | 21.49 |
July | 581.50 | 21.29 | 88.50 | 21.54 | 13.17 | 21.54 |
August | 594.33 | 21.32 | 74.50 | 21.51 | 13.00 | 21.50 |
September | 575.83 | 21.31 | 79.33 | 21.51 | 17.17 | 21.52 |
October | 677.17 | 21.43 | 37.67 | 21.47 | 19.67 | 21.46 |
November | 713.00 | 21.34 | 188.33 | 21.24 | 188.17 | 21.17 |
December | 744.00 | 21.10 | 477.50 | 21.01 | 477.50 | 20.98 |
Annual Sum or Average | 7989.83 | 21.33 | 1821.50 | 21.31 | 1561.67 | 21.26 |
Minimum of Months | 575.83 | 21.10 | 9.17 | 21.01 | 0.00 | 20.98 |
Maximum of Months | 744.00 | 21.53 | 477.50 | 21.54 | 477.50 | 21.54 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.76 | 607.83 | 20.72 | 607.83 | 20.70 |
February | 672.00 | 20.95 | 434.50 | 20.87 | 434.50 | 20.84 |
March | 744.00 | 21.16 | 293.50 | 21.07 | 293.50 | 21.02 |
April | 704.33 | 21.49 | 48.67 | 21.46 | 48.67 | 21.43 |
May | 669.33 | 21.49 | 8.67 | 21.51 | 0.00 | 21.51 |
June | 590.33 | 21.40 | 32.50 | 21.50 | 0.17 | 21.50 |
July | 583.33 | 21.30 | 81.17 | 21.53 | 11.67 | 21.54 |
August | 609.67 | 21.36 | 59.00 | 21.49 | 13.83 | 21.49 |
September | 612.17 | 21.38 | 52.17 | 21.48 | 23.33 | 21.48 |
October | 717.83 | 21.40 | 38.33 | 21.40 | 33.50 | 21.39 |
November | 720.00 | 21.06 | 361.17 | 20.97 | 361.17 | 20.93 |
December | 744.00 | 20.70 | 707.00 | 20.69 | 707.00 | 20.69 |
Annual Sum or Average | 8111.00 | 21.19 | 2724.50 | 21.13 | 2535.17 | 21.06 |
Minimum of Months | 583.33 | 20.70 | 8.67 | 20.69 | 0.00 | 20.69 |
Maximum of Months | 744.00 | 21.49 | 707.00 | 21.53 | 707.00 | 21.54 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 729.67 | 21.48 | 77.50 | 21.42 | 77.50 | 21.37 |
February | 663.83 | 21.54 | 55.17 | 21.51 | 55.17 | 21.48 |
March | 744.00 | 21.55 | 67.67 | 21.51 | 67.67 | 21.47 |
April | 711.00 | 21.61 | 11.67 | 21.60 | 11.67 | 21.59 |
May | 716.50 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
June | 656.00 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
July | 620.33 | 21.40 | 10.83 | 21.41 | 10.83 | 21.41 |
August | 622.50 | 21.39 | 4.33 | 21.39 | 4.33 | 21.39 |
September | 584.33 | 21.34 | 40.67 | 21.46 | 5.33 | 21.47 |
October | 635.83 | 21.38 | 39.67 | 21.48 | 3.67 | 21.48 |
November | 672.50 | 21.44 | 48.17 | 21.41 | 45.50 | 21.38 |
December | 743.17 | 21.51 | 139.17 | 21.43 | 139.17 | 21.37 |
Annual Sum or Average | 8099.67 | 21.49 | 494.83 | 21.48 | 420.83 | 21.46 |
Minimum of Months | 584.33 | 21.34 | 0.00 | 21.39 | 0.00 | 21.37 |
Maximum of Months | 744.00 | 21.61 | 139.17 | 21.61 | 139.17 | 21.61 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 699.00 | 22.50 | 0.67 | 22.50 | 0.00 | 22.50 |
February | 598.00 | 22.62 | 6.17 | 22.63 | 0.00 | 22.63 |
March | 597.67 | 22.73 | 10.00 | 22.75 | 0.00 | 22.75 |
April | 324.83 | 22.82 | 111.67 | 23.08 | 0.00 | 23.08 |
May | 169.33 | 23.17 | 399.00 | 23.55 | 62.83 | 23.58 |
June | 144.00 | 23.79 | 590.83 | 23.74 | 135.00 | 23.76 |
July | 502.17 | 23.82 | 741.00 | 23.72 | 502.17 | 23.75 |
August | 389.67 | 23.77 | 717.67 | 23.67 | 389.00 | 23.70 |
September | 363.50 | 23.61 | 600.50 | 23.62 | 326.83 | 23.64 |
October | 350.83 | 22.98 | 339.83 | 23.32 | 136.17 | 23.37 |
November | 600.67 | 22.65 | 33.00 | 22.71 | 0.00 | 22.71 |
December | 724.00 | 22.45 | 0.00 | 22.45 | 0.00 | 22.45 |
Annual Sum or Average | 5463.67 | 22.94 | 3550.33 | 23.23 | 1552.00 | 23.31 |
Minimum of Months | 144.00 | 22.45 | 0.00 | 22.45 | 0.00 | 22.45 |
Maximum of Months | 724.00 | 23.82 | 741.00 | 23.74 | 502.17 | 23.76 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 570.00 | 22.72 | 14.50 | 22.75 | 0.00 | 22.75 |
February | 483.50 | 22.81 | 31.50 | 22.88 | 0.00 | 22.88 |
March | 447.67 | 22.88 | 18.83 | 22.92 | 0.00 | 22.92 |
April | 196.50 | 22.93 | 183.50 | 23.39 | 0.00 | 23.39 |
May | 99.33 | 23.46 | 484.33 | 23.75 | 58.67 | 23.76 |
June | 128.83 | 23.91 | 642.17 | 23.84 | 128.67 | 23.85 |
July | 495.67 | 23.90 | 744.00 | 23.83 | 495.67 | 23.85 |
August | 385.83 | 23.85 | 743.00 | 23.77 | 385.83 | 23.79 |
September | 335.33 | 23.82 | 658.67 | 23.75 | 330.17 | 23.77 |
October | 240.17 | 23.31 | 466.00 | 23.59 | 136.33 | 23.62 |
November | 466.83 | 22.81 | 66.67 | 22.95 | 0.00 | 22.95 |
December | 629.67 | 22.72 | 3.17 | 22.73 | 0.00 | 22.73 |
Annual Sum or Average | 4479.33 | 23.16 | 4056.33 | 23.45 | 1535.33 | 23.51 |
Minimum of Months | 99.33 | 22.72 | 3.17 | 22.73 | 0.00 | 22.73 |
Maximum of Months | 629.67 | 23.91 | 744.00 | 23.84 | 495.67 | 23.85 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.67 | 24.13 | 742.17 | 24.10 | 497.67 | 24.11 |
February | 453.67 | 24.09 | 670.00 | 24.07 | 453.67 | 24.07 |
March | 502.33 | 24.05 | 741.00 | 24.04 | 502.33 | 24.04 |
April | 508.83 | 24.00 | 719.17 | 24.00 | 508.83 | 24.00 |
May | 551.00 | 23.99 | 744.00 | 23.99 | 551.00 | 23.99 |
June | 588.50 | 23.99 | 720.00 | 23.99 | 588.50 | 23.99 |
July | 738.50 | 23.99 | 744.00 | 23.99 | 738.50 | 23.99 |
August | 680.67 | 23.99 | 744.00 | 23.99 | 680.67 | 23.99 |
September | 646.17 | 23.99 | 720.00 | 23.99 | 646.17 | 23.99 |
October | 563.50 | 23.99 | 744.00 | 23.99 | 563.50 | 23.99 |
November | 493.83 | 24.07 | 719.50 | 24.06 | 493.83 | 24.06 |
December | 483.33 | 24.13 | 740.67 | 24.10 | 483.33 | 24.11 |
Annual Sum or Average | 6708.00 | 24.03 | 8748.50 | 24.02 | 6708.00 | 24.03 |
Minimum of Months | 453.67 | 23.99 | 670.00 | 23.99 | 453.67 | 23.99 |
Maximum of Months | 738.50 | 24.13 | 744.00 | 24.10 | 738.50 | 24.11 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.68 | 2.00 | 21.67 | 2.00 | 21.67 |
February | 672.00 | 22.15 | 0.00 | 22.15 | 0.00 | 22.15 |
March | 744.00 | 22.59 | 0.00 | 22.59 | 0.00 | 22.59 |
April | 553.33 | 23.54 | 5.67 | 23.55 | 0.00 | 23.55 |
May | 241.33 | 23.85 | 192.17 | 23.91 | 9.83 | 23.91 |
June | 84.67 | 23.99 | 451.00 | 24.00 | 42.00 | 24.00 |
July | 325.83 | 24.00 | 744.00 | 24.00 | 325.83 | 24.00 |
August | 207.83 | 23.98 | 685.33 | 23.99 | 207.83 | 23.99 |
September | 261.83 | 23.90 | 529.33 | 23.96 | 212.00 | 23.96 |
October | 421.67 | 23.48 | 183.17 | 23.61 | 60.17 | 23.63 |
November | 697.67 | 22.54 | 0.00 | 22.54 | 0.00 | 22.54 |
December | 744.00 | 21.47 | 7.83 | 21.47 | 7.83 | 21.46 |
Annual Sum or Average | 5698.17 | 22.69 | 2800.50 | 23.11 | 867.50 | 23.19 |
Minimum of Months | 84.67 | 21.47 | 0.00 | 21.47 | 0.00 | 21.46 |
Maximum of Months | 744.00 | 24.00 | 744.00 | 24.00 | 325.83 | 24.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.90713 | 24.80033 | 0.20746 | 5.98133 |
February | 672.00000 | 23.39495 | 22.87603 | 0.05321 | 5.22878 |
March | 744.00000 | 22.62758 | 22.24560 | -0.1422 | 5.59853 |
April | 720.00000 | 22.70977 | 25.47879 | -0.1000 | 5.41106 |
May | 744.00000 | 23.02837 | 35.90373 | -0.9641 | 24.98980 |
June | 720.00000 | 23.34346 | 44.10018 | -0.7943 | 18.70987 |
July | 744.00000 | 23.86337 | 56.57665 | -0.5033 | 10.41643 |
August | 744.00000 | 23.97481 | 52.47735 | -0.4709 | 9.68636 |
September | 720.00000 | 23.99874 | 49.01646 | -0.4689 | 9.70651 |
October | 744.00000 | 23.99918 | 39.82320 | 0.36630 | 7.92683 |
November | 720.00000 | 24.00079 | 24.47096 | 0.25536 | 6.42068 |
December | 744.00000 | 23.99398 | 21.98032 | 0.22551 | 6.09916 |
Annual Sum or Average | 8760.00000 | 23.57224 | 35.06998 | -0.1958 | 9.71370 |
Minimum of Months | 672.00000 | 22.62758 | 21.98032 | -0.9641 | 5.22878 |
Maximum of Months | 744.00000 | 24.00079 | 56.57665 | 0.36630 | 24.98980 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.39046 | 26.93740 | -0.1168 | 7.23605 |
February | 672.00000 | 22.62362 | 23.52443 | -0.0704 | 6.77869 |
March | 744.00000 | 22.79130 | 21.92287 | -0.0397 | 6.48899 |
April | 720.00000 | 23.49938 | 24.00223 | 0.17554 | 6.61444 |
May | 744.00000 | 23.84301 | 33.57766 | -0.5429 | 12.02195 |
June | 720.00000 | 23.98237 | 41.32465 | -0.3907 | 8.40852 |
July | 744.00000 | 23.98891 | 55.71841 | -0.2864 | 6.79767 |
August | 744.00000 | 23.96101 | 52.32059 | -0.3206 | 7.38619 |
September | 720.00000 | 23.92673 | 49.49281 | -0.3408 | 8.06658 |
October | 744.00000 | 23.61537 | 41.34697 | 0.35844 | 8.57663 |
November | 720.00000 | 22.89520 | 26.81943 | 0.04012 | 7.17923 |
December | 744.00000 | 22.22549 | 24.61057 | -0.1833 | 7.63112 |
Annual Sum or Average | 8760.00000 | 23.31467 | 35.22555 | -0.1439 | 7.77579 |
Minimum of Months | 672.00000 | 22.22549 | 21.92287 | -0.5429 | 6.48899 |
Maximum of Months | 744.00000 | 23.98891 | 55.71841 | 0.35844 | 12.02195 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.68460 | 26.96802 | -0.0482 | 5.41926 |
February | 672.00000 | 22.87485 | 23.63724 | -0.0192 | 5.33548 |
March | 744.00000 | 23.03231 | 22.03954 | 0.01344 | 5.37950 |
April | 720.00000 | 23.52803 | 24.49486 | 0.16552 | 5.92372 |
May | 744.00000 | 23.76235 | 34.30149 | -0.6059 | 13.14628 |
June | 720.00000 | 23.87933 | 42.36624 | -0.4913 | 10.28415 |
July | 744.00000 | 23.88381 | 56.63122 | -0.3925 | 8.33422 |
August | 744.00000 | 23.86344 | 53.34770 | -0.4261 | 8.94974 |
September | 720.00000 | 23.86687 | 50.36442 | -0.4480 | 9.44100 |
October | 744.00000 | 23.64319 | 41.93422 | 0.31750 | 7.38574 |
November | 720.00000 | 23.13909 | 27.03541 | 0.07400 | 5.61181 |
December | 744.00000 | 22.51437 | 24.77082 | -0.1067 | 5.56461 |
Annual Sum or Average | 8760.00000 | 23.39124 | 35.75193 | -0.1650 | 7.58020 |
Minimum of Months | 672.00000 | 22.51437 | 22.03954 | -0.6059 | 5.33548 |
Maximum of Months | 744.00000 | 23.88381 | 56.63122 | 0.31750 | 13.14628 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 24.01159 | 21.06711 | 0.80918 | 19.82710 |
February | 672.00000 | 23.99719 | 18.14653 | 0.80193 | 19.49569 |
March | 744.00000 | 23.98691 | 16.81003 | 0.80644 | 19.57619 |
April | 720.00000 | 23.99547 | 19.93679 | 0.86848 | 21.78337 |
May | 744.00000 | 23.99968 | 30.22502 | 0.35106 | 9.50205 |
June | 720.00000 | 24.00034 | 38.64565 | 0.44427 | 10.89497 |
July | 744.00000 | 24.00012 | 52.57686 | 0.53453 | 12.45106 |
August | 744.00000 | 24.00009 | 49.29669 | 0.50374 | 11.91132 |
September | 720.00000 | 23.99846 | 46.26011 | 0.46818 | 11.19484 |
October | 744.00000 | 23.98634 | 37.14884 | 0.98037 | 26.05994 |
November | 720.00000 | 23.99220 | 21.70857 | 0.83394 | 20.57090 |
December | 744.00000 | 24.00122 | 18.88626 | 0.78340 | 18.93399 |
Annual Sum or Average | 8760.00000 | 23.99748 | 30.98896 | 0.68145 | 16.83647 |
Minimum of Months | 672.00000 | 23.98634 | 16.81003 | 0.35106 | 9.50205 |
Maximum of Months | 744.00000 | 24.01159 | 52.57686 | 0.98037 | 26.05994 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.44867 | 29.68079 | -0.0129 | 6.11671 |
February | 672.00000 | 22.56566 | 26.41198 | 0.00689 | 5.94537 |
March | 744.00000 | 22.48926 | 24.99453 | -0.0193 | 5.72967 |
April | 720.00000 | 22.83474 | 27.97685 | 0.11345 | 5.97828 |
May | 744.00000 | 23.01529 | 38.62894 | -0.6946 | 16.12480 |
June | 720.00000 | 23.28501 | 46.77621 | -0.5071 | 11.10685 |
July | 744.00000 | 23.31853 | 61.32368 | -0.3962 | 8.85290 |
August | 744.00000 | 23.38134 | 57.72077 | -0.3984 | 9.01636 |
September | 720.00000 | 23.52412 | 54.15891 | -0.3642 | 8.68046 |
October | 744.00000 | 23.26578 | 45.44198 | 0.36542 | 8.78366 |
November | 720.00000 | 22.85968 | 29.88737 | 0.11963 | 6.80724 |
December | 744.00000 | 22.30057 | 27.39313 | -0.0731 | 6.21061 |
Annual Sum or Average | 8760.00000 | 22.94178 | 39.29922 | -0.1563 | 8.30009 |
Minimum of Months | 672.00000 | 22.30057 | 24.99453 | -0.6946 | 5.72967 |
Maximum of Months | 744.00000 | 23.52412 | 61.32368 | 0.36542 | 16.12480 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.07195 | 29.31792 | 0.07494 | 5.46318 |
February | 672.00000 | 23.19600 | 26.11803 | 0.08975 | 5.46340 |
March | 744.00000 | 23.23192 | 24.68679 | 0.09286 | 5.53076 |
April | 720.00000 | 23.51633 | 27.26547 | 0.19920 | 6.17281 |
May | 744.00000 | 23.64632 | 37.14226 | -0.5963 | 12.97113 |
June | 720.00000 | 23.75089 | 45.12568 | -0.4804 | 10.18492 |
July | 744.00000 | 23.76780 | 59.38639 | -0.3765 | 8.17698 |
August | 744.00000 | 23.76795 | 56.04994 | -0.4029 | 8.60915 |
September | 720.00000 | 23.81722 | 52.96591 | -0.4100 | 8.74725 |
October | 744.00000 | 23.71013 | 44.36472 | 0.37528 | 8.19607 |
November | 720.00000 | 23.40844 | 29.48827 | 0.17389 | 6.04129 |
December | 744.00000 | 22.95591 | 27.13269 | 0.02780 | 5.34697 |
Annual Sum or Average | 8760.00000 | 23.48763 | 38.34840 | -0.1040 | 7.59037 |
Minimum of Months | 672.00000 | 22.95591 | 24.68679 | -0.5963 | 5.34697 |
Maximum of Months | 744.00000 | 23.81722 | 59.38639 | 0.37528 | 12.97113 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.25940 | 31.31825 | -0.4501 | 9.88221 |
February | 672.00000 | 21.36788 | 27.57331 | -0.4195 | 9.36012 |
March | 744.00000 | 21.46020 | 26.00460 | -0.3723 | 8.62679 |
April | 720.00000 | 21.63120 | 29.16328 | -0.2380 | 7.17268 |
May | 744.00000 | 21.69711 | 37.50255 | -1.2059 | 36.91549 |
June | 720.00000 | 21.73555 | 42.69346 | -1.1090 | 32.36893 |
July | 744.00000 | 21.73269 | 50.85450 | -1.0685 | 30.59360 |
August | 744.00000 | 21.72135 | 49.88593 | -1.0926 | 31.68468 |
September | 720.00000 | 21.71705 | 49.12816 | -1.1082 | 32.54362 |
October | 744.00000 | 21.64173 | 45.85758 | -0.1289 | 6.25565 |
November | 720.00000 | 21.44922 | 31.90907 | -0.3443 | 8.50434 |
December | 744.00000 | 21.21381 | 28.35631 | -0.4967 | 10.75031 |
Annual Sum or Average | 8760.00000 | 21.55289 | 37.59464 | -0.6712 | 18.78285 |
Minimum of Months | 672.00000 | 21.21381 | 26.00460 | -1.2059 | 6.25565 |
Maximum of Months | 744.00000 | 21.73555 | 50.85450 | -0.1289 | 36.91549 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.89926 | 31.86383 | -0.5779 | 12.33726 |
February | 672.00000 | 21.06859 | 27.96485 | -0.5300 | 11.29633 |
March | 744.00000 | 21.26591 | 26.26601 | -0.4454 | 9.63513 |
April | 720.00000 | 21.57268 | 29.27117 | -0.2674 | 7.36918 |
May | 744.00000 | 21.68885 | 37.52941 | -1.2138 | 37.24524 |
June | 720.00000 | 21.73849 | 42.66937 | -1.1066 | 32.24435 |
July | 744.00000 | 21.73390 | 50.88888 | -1.0691 | 30.59047 |
August | 744.00000 | 21.71373 | 50.17163 | -1.1073 | 32.24407 |
September | 720.00000 | 21.68962 | 49.86456 | -1.1500 | 34.22206 |
October | 744.00000 | 21.52818 | 46.69769 | -0.1886 | 6.40386 |
November | 720.00000 | 21.19638 | 32.32256 | -0.4516 | 9.88450 |
December | 744.00000 | 20.83327 | 28.87745 | -0.6296 | 13.61671 |
Annual Sum or Average | 8760.00000 | 21.41203 | 37.93969 | -0.7296 | 19.81412 |
Minimum of Months | 672.00000 | 20.83327 | 26.26601 | -1.2138 | 6.40386 |
Maximum of Months | 744.00000 | 21.73849 | 50.88888 | -0.1886 | 37.24524 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.96264 | 30.37565 | -0.5517 | 11.52884 |
February | 672.00000 | 21.04300 | 26.46230 | -0.5380 | 11.19594 |
March | 744.00000 | 21.14859 | 24.84024 | -0.4992 | 10.29658 |
April | 720.00000 | 21.36051 | 28.03568 | -0.3889 | 8.44983 |
May | 744.00000 | 21.52274 | 37.01799 | -1.4042 | 46.10760 |
June | 720.00000 | 21.64161 | 42.88305 | -1.2972 | 40.72468 |
July | 744.00000 | 21.63701 | 52.49349 | -1.2437 | 38.10722 |
August | 744.00000 | 21.57438 | 51.24619 | -1.2894 | 40.24287 |
September | 720.00000 | 21.49218 | 50.64056 | -1.3442 | 42.93664 |
October | 744.00000 | 21.30707 | 46.07637 | -0.3032 | 7.12805 |
November | 720.00000 | 21.06682 | 31.02458 | -0.5005 | 10.37716 |
December | 744.00000 | 20.92975 | 27.46986 | -0.5837 | 12.28286 |
Annual Sum or Average | 8760.00000 | 21.30845 | 37.46185 | -0.8305 | 23.35521 |
Minimum of Months | 672.00000 | 20.92975 | 24.84024 | -1.4042 | 7.12805 |
Maximum of Months | 744.00000 | 21.64161 | 52.49349 | -0.3032 | 46.10760 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.28536 | 31.25829 | -0.4470 | 9.73225 |
February | 672.00000 | 21.45610 | 27.44819 | -0.3914 | 8.96039 |
March | 744.00000 | 21.56167 | 25.89320 | -0.3455 | 8.35974 |
April | 720.00000 | 21.71710 | 29.04097 | -0.2095 | 7.00497 |
May | 744.00000 | 21.74321 | 37.39742 | -1.1834 | 35.89640 |
June | 720.00000 | 21.75465 | 42.77927 | -1.0926 | 31.72984 |
July | 744.00000 | 21.75007 | 50.92160 | -1.0539 | 30.04826 |
August | 744.00000 | 21.74111 | 49.87855 | -1.0784 | 31.14450 |
September | 720.00000 | 21.74422 | 49.04749 | -1.0961 | 32.06244 |
October | 744.00000 | 21.66566 | 46.04206 | -0.1284 | 6.30825 |
November | 720.00000 | 21.49697 | 31.85512 | -0.3367 | 8.41376 |
December | 744.00000 | 21.22902 | 28.30319 | -0.4914 | 10.54453 |
Annual Sum or Average | 8760.00000 | 21.59566 | 37.56372 | -0.6564 | 18.41171 |
Minimum of Months | 672.00000 | 21.22902 | 25.89320 | -1.1834 | 6.30825 |
Maximum of Months | 744.00000 | 21.75465 | 50.92160 | -0.1284 | 35.89640 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.89650 | 31.81700 | -0.5808 | 12.30542 |
February | 672.00000 | 21.14058 | 27.82154 | -0.5044 | 10.70565 |
March | 744.00000 | 21.38500 | 26.10573 | -0.4153 | 9.13826 |
April | 720.00000 | 21.69298 | 29.10387 | -0.2320 | 7.11077 |
May | 744.00000 | 21.74251 | 37.43709 | -1.1891 | 36.12055 |
June | 720.00000 | 21.75574 | 42.81014 | -1.0906 | 31.62458 |
July | 744.00000 | 21.75040 | 50.99321 | -1.0547 | 30.05410 |
August | 744.00000 | 21.73849 | 50.15934 | -1.0915 | 31.63510 |
September | 720.00000 | 21.73566 | 49.50481 | -1.1334 | 33.55073 |
October | 744.00000 | 21.59417 | 46.59856 | -0.1814 | 6.42181 |
November | 720.00000 | 21.18182 | 32.31049 | -0.4563 | 9.82063 |
December | 744.00000 | 20.83231 | 28.82090 | -0.6273 | 13.55446 |
Annual Sum or Average | 8760.00000 | 21.45491 | 37.86512 | -0.7146 | 19.39474 |
Minimum of Months | 672.00000 | 20.83231 | 26.10573 | -1.1891 | 6.42181 |
Maximum of Months | 744.00000 | 21.75574 | 50.99321 | -0.1814 | 36.12055 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.14167 | 31.73471 | -0.5168 | 11.34152 |
February | 672.00000 | 21.26967 | 27.87931 | -0.4792 | 10.62661 |
March | 744.00000 | 21.37967 | 26.24794 | -0.4227 | 9.61869 |
April | 720.00000 | 21.59650 | 29.33089 | -0.2615 | 7.64341 |
May | 744.00000 | 21.68198 | 37.83695 | -1.2174 | 37.69033 |
June | 720.00000 | 21.73415 | 43.04022 | -1.0989 | 32.17215 |
July | 744.00000 | 21.73039 | 51.36334 | -1.0583 | 30.37169 |
August | 744.00000 | 21.71469 | 50.55628 | -1.0886 | 31.74063 |
September | 720.00000 | 21.70381 | 50.01662 | -1.1158 | 33.16364 |
October | 744.00000 | 21.59740 | 46.87722 | -0.1562 | 6.58638 |
November | 720.00000 | 21.36226 | 32.28190 | -0.4031 | 9.62359 |
December | 744.00000 | 21.09971 | 28.72858 | -0.5636 | 12.32423 |
Annual Sum or Average | 8760.00000 | 21.50182 | 38.06686 | -0.7001 | 19.46714 |
Minimum of Months | 672.00000 | 21.09971 | 26.24794 | -1.2174 | 6.58638 |
Maximum of Months | 744.00000 | 21.73415 | 51.36334 | -0.1562 | 37.69033 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.75808 | 32.32834 | -0.6521 | 14.34395 |
February | 672.00000 | 20.94525 | 28.31860 | -0.5981 | 13.01231 |
March | 744.00000 | 21.16363 | 26.54817 | -0.5033 | 10.89921 |
April | 720.00000 | 21.53463 | 29.45127 | -0.2930 | 7.88791 |
May | 744.00000 | 21.67331 | 37.86076 | -1.2257 | 38.03358 |
June | 720.00000 | 21.73799 | 43.01303 | -1.0962 | 32.03030 |
July | 744.00000 | 21.73191 | 51.38968 | -1.0588 | 30.36077 |
August | 744.00000 | 21.70706 | 50.88351 | -1.1035 | 32.29281 |
September | 720.00000 | 21.67408 | 50.88425 | -1.1595 | 34.90447 |
October | 744.00000 | 21.46346 | 47.83344 | -0.2238 | 6.85057 |
November | 720.00000 | 21.06394 | 32.76968 | -0.5259 | 11.49808 |
December | 744.00000 | 20.70476 | 29.28621 | -0.7017 | 15.70972 |
Annual Sum or Average | 8760.00000 | 21.34810 | 38.45617 | -0.7631 | 20.70459 |
Minimum of Months | 672.00000 | 20.70476 | 26.54817 | -1.2257 | 6.85057 |
Maximum of Months | 744.00000 | 21.73799 | 51.38968 | -0.2238 | 38.03358 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.51123 | 32.61674 | -0.3376 | 8.60477 |
February | 672.00000 | 21.56361 | 28.63340 | -0.3342 | 8.48809 |
March | 744.00000 | 21.55387 | 26.95294 | -0.3481 | 8.54338 |
April | 720.00000 | 21.63020 | 29.98589 | -0.2687 | 7.59557 |
May | 744.00000 | 21.67309 | 38.44121 | -1.2878 | 40.81054 |
June | 720.00000 | 21.71479 | 43.79813 | -1.1905 | 36.05617 |
July | 744.00000 | 21.71803 | 52.02970 | -1.1370 | 33.62139 |
August | 744.00000 | 21.70828 | 50.65944 | -1.1479 | 34.21983 |
September | 720.00000 | 21.71502 | 49.71374 | -1.1395 | 34.17830 |
October | 744.00000 | 21.66026 | 46.05166 | -0.1235 | 6.48880 |
November | 720.00000 | 21.56228 | 32.91198 | -0.2814 | 8.05848 |
December | 744.00000 | 21.51542 | 29.68900 | -0.3641 | 9.01423 |
Annual Sum or Average | 8760.00000 | 21.62738 | 38.53066 | -0.6654 | 19.71154 |
Minimum of Months | 672.00000 | 21.51123 | 26.95294 | -1.2878 | 6.48880 |
Maximum of Months | 744.00000 | 21.71803 | 52.02970 | -0.1235 | 40.81054 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.58185 | 29.52214 | -0.0139 | 5.66613 |
February | 672.00000 | 22.75516 | 26.17317 | 0.02343 | 5.64368 |
March | 744.00000 | 22.95374 | 24.59057 | 0.08149 | 5.68703 |
April | 720.00000 | 23.33485 | 27.35031 | 0.23803 | 6.67006 |
May | 744.00000 | 23.53226 | 37.46774 | -0.4945 | 10.79241 |
June | 720.00000 | 23.64859 | 45.60376 | -0.3584 | 8.13698 |
July | 744.00000 | 23.64724 | 59.85963 | -0.2650 | 6.78783 |
August | 744.00000 | 23.58686 | 56.79158 | -0.3226 | 7.59417 |
September | 720.00000 | 23.49424 | 54.07931 | -0.3994 | 8.95289 |
October | 744.00000 | 23.26722 | 45.35883 | 0.33538 | 7.92651 |
November | 720.00000 | 22.83902 | 29.92019 | 0.07613 | 5.75981 |
December | 744.00000 | 22.48992 | 27.25381 | -0.0609 | 5.69413 |
Annual Sum or Average | 8760.00000 | 23.17939 | 38.76063 | -0.0975 | 7.11838 |
Minimum of Months | 672.00000 | 22.48992 | 24.59057 | -0.4945 | 5.64368 |
Maximum of Months | 744.00000 | 23.64859 | 59.85963 | 0.33538 | 10.79241 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.97169 | 29.00535 | 0.10775 | 5.82594 |
February | 672.00000 | 23.11022 | 25.74653 | 0.13482 | 5.91194 |
March | 744.00000 | 23.27308 | 24.19612 | 0.18274 | 6.12730 |
April | 720.00000 | 23.54402 | 26.92186 | 0.30925 | 7.37233 |
May | 744.00000 | 23.69199 | 36.94220 | -0.4109 | 9.06440 |
June | 720.00000 | 23.79044 | 45.06015 | -0.2806 | 6.97004 |
July | 744.00000 | 23.78787 | 59.19463 | -0.1877 | 5.92688 |
August | 744.00000 | 23.73269 | 56.13523 | -0.2441 | 6.51885 |
September | 720.00000 | 23.65711 | 53.41527 | -0.3160 | 7.54584 |
October | 744.00000 | 23.47902 | 44.74177 | 0.40574 | 8.91132 |
November | 720.00000 | 23.15568 | 29.46431 | 0.17555 | 6.16691 |
December | 744.00000 | 22.89862 | 26.78724 | 0.06638 | 5.64958 |
Annual Sum or Average | 8760.00000 | 23.42572 | 38.22967 | -0.0057 | 6.83819 |
Minimum of Months | 672.00000 | 22.89862 | 24.19612 | -0.4109 | 5.64958 |
Maximum of Months | 744.00000 | 23.79044 | 59.19463 | 0.40574 | 9.06440 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 24.08403 | 28.06723 | 0.98748 | 27.13749 |
February | 672.00000 | 24.05382 | 24.97588 | 0.98586 | 27.05062 |
March | 744.00000 | 24.02842 | 23.50921 | 0.99687 | 27.52293 |
April | 720.00000 | 24.00347 | 26.29664 | 1.07679 | 31.09929 |
May | 744.00000 | 23.99176 | 36.17855 | 0.64379 | 17.70079 |
June | 720.00000 | 23.99235 | 44.33461 | 0.75563 | 20.50118 |
July | 744.00000 | 23.99301 | 57.95409 | 0.84331 | 23.07553 |
August | 744.00000 | 23.99308 | 54.77367 | 0.80210 | 21.81218 |
September | 720.00000 | 23.99214 | 51.83756 | 0.75518 | 20.49818 |
October | 744.00000 | 23.99205 | 43.08713 | 1.17491 | 35.32737 |
November | 720.00000 | 24.04768 | 28.45935 | 1.01627 | 28.34492 |
December | 744.00000 | 24.08478 | 26.01312 | 0.96121 | 26.08262 |
Annual Sum or Average | 8760.00000 | 24.02125 | 37.21710 | 0.91622 | 25.50452 |
Minimum of Months | 672.00000 | 23.99176 | 23.50921 | 0.64379 | 17.70079 |
Maximum of Months | 744.00000 | 24.08478 | 57.95409 | 1.17491 | 35.32737 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.08560 | 25.73984 | -0.4630 | 9.55980 |
February | 672.00000 | 21.24189 | 22.10646 | -0.4414 | 9.19132 |
March | 744.00000 | 21.44252 | 20.33313 | -0.3989 | 8.47241 |
April | 720.00000 | 22.27866 | 22.76459 | -0.1768 | 5.97554 |
May | 744.00000 | 22.96220 | 32.67492 | -0.9449 | 24.35674 |
June | 720.00000 | 23.47493 | 40.51289 | -0.7134 | 15.92538 |
July | 744.00000 | 23.46675 | 55.49163 | -0.6153 | 13.05406 |
August | 744.00000 | 23.30611 | 52.29477 | -0.6944 | 15.34317 |
September | 720.00000 | 23.05198 | 49.90680 | -0.7983 | 18.78026 |
October | 744.00000 | 22.43435 | 41.57616 | -0.0182 | 5.35675 |
November | 720.00000 | 21.53425 | 25.81107 | -0.3444 | 7.76491 |
December | 744.00000 | 21.04479 | 23.15310 | -0.4944 | 10.15064 |
Annual Sum or Average | 8760.00000 | 22.28214 | 34.46030 | -0.5092 | 12.01600 |
Minimum of Months | 672.00000 | 21.04479 | 20.33313 | -0.9449 | 5.35675 |
Maximum of Months | 744.00000 | 23.47493 | 55.49163 | -0.0182 | 24.35674 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.78704 | 29.31592 | -0.3031 | 7.08241 |
February | 672.00000 | 22.14367 | 25.63699 | -0.2382 | 6.34286 |
March | 744.00000 | 22.46488 | 23.89696 | -0.1703 | 5.78343 |
April | 720.00000 | 23.35386 | 26.13289 | 0.06172 | 5.34944 |
May | 744.00000 | 23.84354 | 35.42615 | -0.6831 | 15.13025 |
June | 720.00000 | 23.97698 | 43.25333 | -0.5715 | 11.96164 |
July | 744.00000 | 23.97810 | 57.59942 | -0.4732 | 9.68770 |
August | 744.00000 | 23.94462 | 54.36436 | -0.5102 | 10.49482 |
September | 720.00000 | 23.93673 | 51.55798 | -0.5341 | 11.12945 |
October | 744.00000 | 23.55939 | 43.61776 | 0.23210 | 6.34208 |
November | 720.00000 | 22.67468 | 28.89896 | -0.0867 | 5.59921 |
December | 744.00000 | 21.56393 | 27.04189 | -0.3717 | 7.96807 |
Annual Sum or Average | 8760.00000 | 23.10596 | 37.32128 | -0.3048 | 8.59163 |
Minimum of Months | 672.00000 | 21.56393 | 23.89696 | -0.6831 | 5.34944 |
Maximum of Months | 744.00000 | 23.97810 | 57.59942 | 0.23210 | 15.13025 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.67520 | 27.74434 | -0.3285 | 7.54600 |
February | 672.00000 | 22.14559 | 23.95165 | -0.2346 | 6.57367 |
March | 744.00000 | 22.59303 | 22.04663 | -0.1346 | 5.84539 |
April | 720.00000 | 23.64354 | 23.73217 | 0.14683 | 5.88684 |
May | 744.00000 | 23.94557 | 33.09060 | -0.5990 | 12.86544 |
June | 720.00000 | 23.99882 | 40.89065 | -0.4916 | 10.18976 |
July | 744.00000 | 23.99954 | 55.06346 | -0.3938 | 8.24290 |
August | 744.00000 | 23.99391 | 51.83649 | -0.4280 | 8.87660 |
September | 720.00000 | 23.95597 | 49.25779 | -0.4728 | 9.92033 |
October | 744.00000 | 23.67803 | 41.34625 | 0.27781 | 6.93682 |
November | 720.00000 | 22.58186 | 27.25982 | -0.1048 | 6.08545 |
December | 744.00000 | 21.46991 | 25.45104 | -0.3974 | 8.47504 |
Annual Sum or Average | 8760.00000 | 23.14382 | 35.22960 | -0.2640 | 8.13416 |
Minimum of Months | 672.00000 | 21.46991 | 22.04663 | -0.5990 | 5.84539 |
Maximum of Months | 744.00000 | 23.99954 | 55.06346 | 0.27781 | 12.86544 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.95561 | 24.64162 | -0.2761 | 6.82139 |
February | 672.00000 | 22.25488 | 21.04342 | -0.2265 | 6.37161 |
March | 744.00000 | 22.60650 | 19.26196 | -0.1527 | 5.78555 |
April | 720.00000 | 23.52737 | 21.28497 | 0.08783 | 5.50276 |
May | 744.00000 | 23.93672 | 30.76992 | -0.6441 | 14.02085 |
June | 720.00000 | 23.99815 | 39.12697 | -0.5384 | 11.19954 |
July | 744.00000 | 23.99952 | 53.70075 | -0.4370 | 8.99806 |
August | 744.00000 | 23.98963 | 50.17265 | -0.4748 | 9.75667 |
September | 720.00000 | 23.97276 | 47.35783 | -0.5123 | 10.67489 |
October | 744.00000 | 23.63451 | 38.98956 | 0.23723 | 6.44806 |
November | 720.00000 | 22.66262 | 24.37366 | -0.1053 | 5.72344 |
December | 744.00000 | 21.74566 | 22.40306 | -0.3406 | 7.62896 |
Annual Sum or Average | 8760.00000 | 23.19418 | 32.85382 | -0.2825 | 8.25937 |
Minimum of Months | 672.00000 | 21.74566 | 19.26196 | -0.6441 | 5.50276 |
Maximum of Months | 744.00000 | 23.99952 | 53.70075 | 0.23723 | 14.02085 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.113613E+11 | 58737.52 | 03-JAN-16:03 | 480.40 | 0.350771E+11 | 0.00 | 0.464384E+11 | 2.04 | 3.28 | 12-JAN-16:03 | 0.00 | 0.00 |
February | 0.238075E+11 | 84700.05 | 20-FEB-16:01 | 506.59 | 0.714686E+11 | 0.00 | 0.952761E+11 | 2.35 | 3.70 | 21-FEB-16:01 | 0.00 | 0.00 |
March | 0.403665E+11 | 93030.81 | 14-MAR-18:01 | 608.48 | 0.120319E+12 | 0.00 | 0.160686E+12 | 2.52 | 3.92 | 15-MAR-18:02 | 0.00 | 0.00 |
April | 0.108445E+12 | 131748.74 | 21-APR-15:03 | 705.14 | 0.332665E+12 | 0.00 | 0.441110E+12 | 3.00 | 3.91 | 12-APR-18:01 | 0.00 | 0.00 |
May | 0.175666E+12 | 143480.54 | 19-MAY-18:05 | 743.57 | 0.541329E+12 | 0.00 | 0.716995E+12 | 3.06 | 3.88 | 01-MAY-18:02 | 0.00 | 0.00 |
June | 0.231373E+12 | 183740.12 | 14-JUN-18:03 | 720.00 | 0.700633E+12 | 0.00 | 0.932006E+12 | 3.04 | 3.96 | 19-JUN-18:03 | 0.00 | 0.00 |
July | 0.270882E+12 | 177175.59 | 26-JUL-18:03 | 744.00 | 0.897443E+12 | 0.00 | 0.116833E+13 | 3.33 | 4.51 | 18-JUL-21:00 | 0.00 | 0.00 |
August | 0.234206E+12 | 168689.95 | 04-AUG-18:03 | 744.00 | 0.751003E+12 | 0.00 | 0.985209E+12 | 3.20 | 4.29 | 16-AUG-18:02 | 0.00 | 0.00 |
September | 0.190406E+12 | 146096.90 | 20-SEP-15:03 | 720.00 | 0.631108E+12 | 0.00 | 0.821514E+12 | 3.27 | 4.45 | 23-SEP-18:03 | 0.00 | 0.00 |
October | 0.107001E+12 | 145936.19 | 04-OCT-18:03 | 735.64 | 0.342939E+12 | 0.00 | 0.449941E+12 | 3.11 | 4.23 | 03-OCT-21:00 | 0.00 | 0.00 |
November | 0.327012E+11 | 89121.44 | 09-NOV-16:01 | 553.52 | 0.993361E+11 | 0.00 | 0.132037E+12 | 2.39 | 3.95 | 08-NOV-19:01 | 0.00 | 0.00 |
December | 0.862815E+10 | 33154.39 | 23-DEC-15:00 | 468.44 | 0.269385E+11 | 0.00 | 0.355666E+11 | 1.99 | 3.19 | 02-DEC-06:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.143484E+13 | 7729.77 | 0.455026E+13 | 0.00 | 0.598510E+13 | 2.78 | 0.00 | 0.00 | ||||
Minimum of Months | 0.862815E+10 | 33154.39 | 468.44 | 0.269385E+11 | 0.00 | 0.355666E+11 | 1.99 | 3.19 | 0.00 | 0.00 | ||
Maximum of Months | 0.270882E+12 | 183740.12 | 744.00 | 0.897443E+12 | 0.00 | 0.116833E+13 | 3.33 | 4.51 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.483451E+11 | 0.00 | 710.74 | 207629.42 | 17-JAN-09:01 | 0.00 | 55.49 | 79.01 | 0.18 | 0.00 | 0.04 | 0.51 | 17-JAN-09:01 |
February | 0.285141E+11 | 0.00 | 566.17 | 149433.58 | 17-FEB-09:01 | 0.00 | 55.39 | 75.89 | 0.12 | 0.00 | 0.03 | 0.37 | 17-FEB-09:01 |
March | 0.184266E+11 | 0.00 | 463.44 | 121670.79 | 31-MAR-04:00 | 0.00 | 54.87 | 69.63 | 0.07 | 0.00 | 0.02 | 0.30 | 31-MAR-04:00 |
April | 0.572989E+10 | 0.00 | 138.65 | 126183.98 | 13-APR-04:53 | 0.00 | 45.09 | 51.32 | 0.02 | 0.00 | 0.01 | 0.31 | 13-APR-04:53 |
May | 0.411772E+09 | 0.00 | 20.69 | 78417.52 | 02-MAY-18:04 | 0.00 | 49.34 | 50.30 | 0.00 | 0.00 | 0.00 | 0.19 | 02-MAY-18:04 |
June | 48509449.36 | 0.00 | 1.65 | 23758.49 | 01-JUN-08:04 | 0.00 | 59.82 | 59.86 | 0.00 | 0.00 | 0.00 | 0.06 | 01-JUN-08:04 |
July | 45608288.07 | 0.00 | 2.37 | 21751.99 | 05-JUL-08:05 | 0.00 | 62.44 | 62.49 | 0.00 | 0.00 | 0.00 | 0.05 | 05-JUL-08:05 |
August | 58231720.29 | 0.00 | 2.40 | 36268.08 | 24-AUG-08:04 | 0.00 | 61.60 | 61.65 | 0.00 | 0.00 | 0.00 | 0.09 | 24-AUG-08:04 |
September | 0.513054E+09 | 0.00 | 17.29 | 46455.89 | 25-SEP-05:10 | 0.00 | 56.29 | 57.13 | 0.00 | 0.00 | 0.00 | 0.11 | 25-SEP-05:10 |
October | 0.276710E+10 | 0.00 | 168.95 | 79268.89 | 25-OCT-05:10 | 0.00 | 51.61 | 58.10 | 0.01 | 0.00 | 0.00 | 0.19 | 25-OCT-05:10 |
November | 0.268639E+11 | 0.00 | 531.66 | 151510.14 | 26-NOV-16:01 | 0.00 | 57.77 | 74.44 | 0.10 | 0.00 | 0.03 | 0.37 | 26-NOV-16:01 |
December | 0.512090E+11 | 0.00 | 721.32 | 158292.18 | 02-DEC-19:05 | 0.00 | 55.42 | 79.34 | 0.19 | 0.00 | 0.05 | 0.39 | 02-DEC-19:05 |
Annual Sum or Average | 0.182933E+12 | 0.00 | 3345.33 | 0.00 | 55.43 | 64.89 | 0.06 | 0.00 | 0.01 | ||||
Minimum of Months | 45608288.07 | 0.00 | 1.65 | 21751.99 | 0.00 | 45.09 | 50.30 | 0.00 | 0.00 | 0.00 | 0.05 | ||
Maximum of Months | 0.512090E+11 | 0.00 | 721.32 | 207629.42 | 0.00 | 62.44 | 79.34 | 0.19 | 0.00 | 0.05 | 0.51 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.716861E+10 | 0.00 | 175.53 | 0.716861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93651.60 | 03-JAN-17:00 | 93651.60 | 03-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.347043E+11 | 0.00 | 247.95 | 0.347043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 128540.56 | 20-FEB-16:20 | 128540.56 | 20-FEB-16:20 | 0.00 | 0.00 | 0.00 |
March | 0.702420E+11 | 0.00 | 351.30 | 0.702420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 165916.23 | 14-MAR-17:13 | 165916.23 | 14-MAR-17:13 | 0.00 | 0.00 | 0.00 |
April | 0.215062E+12 | 0.00 | 570.21 | 0.215062E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 228369.22 | 19-APR-21:00 | 228369.22 | 19-APR-21:00 | 0.00 | 0.00 | 0.00 |
May | 0.357119E+12 | 0.00 | 714.78 | 0.355312E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 257953.19 | 19-MAY-20:10 | 257953.19 | 19-MAY-20:10 | 0.00 | 0.00 | 0.00 |
June | 0.463005E+12 | 0.00 | 720.00 | 0.457562E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 304214.02 | 19-JUN-18:07 | 287067.60 | 05-JUN-20:10 | 0.00 | 0.00 | 0.00 |
July | 0.618069E+12 | 0.00 | 744.00 | 0.481303E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 472231.72 | 18-JUL-20:50 | 287535.40 | 25-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.504514E+12 | 0.00 | 744.00 | 0.450042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 467350.66 | 01-AUG-20:50 | 294023.67 | 04-AUG-20:10 | 0.00 | 0.00 | 0.00 |
September | 0.412748E+12 | 0.00 | 696.01 | 0.354800E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 346303.91 | 09-SEP-20:00 | 259810.54 | 19-SEP-18:20 | 0.00 | 0.00 | 0.00 |
October | 0.204981E+12 | 0.00 | 551.31 | 0.195856E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 395164.94 | 03-OCT-20:00 | 247317.98 | 04-OCT-20:10 | 0.00 | 0.00 | 0.00 |
November | 0.433069E+11 | 0.00 | 292.74 | 0.433069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152247.78 | 03-NOV-16:00 | 152247.78 | 03-NOV-16:00 | 0.00 | 0.00 | 0.00 |
December | 0.436754E+10 | 0.00 | 186.95 | 0.436754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52907.71 | 23-DEC-15:00 | 52907.71 | 23-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293529E+13 | 0.00 | 5994.78 | 0.266972E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.436754E+10 | 0.00 | 175.53 | 0.436754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52907.71 | 52907.71 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.618069E+12 | 0.00 | 744.00 | 0.481303E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 472231.72 | 294023.67 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.122870E+10 | 0.00 | 63.75 | 0.122870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18651.05 | 03-JAN-15:00 | 18651.05 | 03-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.618797E+10 | 0.00 | 159.53 | 0.618797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23693.24 | 20-FEB-16:00 | 23693.24 | 20-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.122343E+11 | 0.00 | 278.02 | 0.122343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24657.75 | 22-MAR-13:00 | 24657.75 | 22-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.348126E+11 | 0.00 | 548.56 | 0.348126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29774.81 | 21-APR-15:00 | 29774.81 | 21-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.557264E+11 | 0.00 | 713.33 | 0.546336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34982.72 | 24-MAY-13:00 | 31559.35 | 21-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 0.679277E+11 | 0.00 | 720.00 | 0.656138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40511.58 | 27-JUN-24:00 | 33168.57 | 15-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.903037E+11 | 0.00 | 744.00 | 0.685052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55414.96 | 21-JUL-08:00 | 33162.18 | 02-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.760520E+11 | 0.00 | 744.00 | 0.648652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47992.63 | 02-AUG-03:50 | 32198.70 | 08-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.649768E+11 | 0.00 | 692.83 | 0.520160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47427.38 | 22-SEP-02:00 | 30656.69 | 19-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.332051E+11 | 0.00 | 534.83 | 0.304518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42555.84 | 03-OCT-20:40 | 30238.31 | 03-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.750498E+10 | 0.00 | 211.42 | 0.750498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24036.88 | 08-NOV-15:00 | 24036.88 | 08-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.724517E+09 | 0.00 | 54.21 | 0.724517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11238.19 | 10-DEC-15:00 | 11238.19 | 10-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.450885E+12 | 0.00 | 5464.49 | 0.398779E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.724517E+09 | 0.00 | 54.21 | 0.724517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11238.19 | 11238.19 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.903037E+11 | 0.00 | 744.00 | 0.685052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55414.96 | 33168.57 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.671030E+09 | 0.00 | 160.75 | 0.670438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14474.63 | 03-JAN-16:01 | 14474.63 | 03-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.110388E+10 | 0.00 | 217.85 | 0.110256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14890.92 | 20-FEB-16:01 | 14890.92 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.212310E+10 | 0.00 | 363.72 | 0.211888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15048.49 | 21-MAR-15:01 | 15048.49 | 21-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.528641E+10 | 0.00 | 591.23 | 0.494931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15387.69 | 19-APR-18:01 | 15387.69 | 19-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.833939E+10 | 0.00 | 682.97 | 0.704930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15388.05 | 20-MAY-18:01 | 15388.05 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.106356E+11 | 0.00 | 682.64 | 0.828857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15385.19 | 17-JUN-15:02 | 15385.19 | 17-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.115254E+11 | 0.00 | 706.39 | 0.737916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17009.89 | 20-JUL-08:61 | 14315.18 | 11-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.104753E+11 | 0.00 | 695.48 | 0.681315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15794.40 | 02-AUG-08:61 | 14174.61 | 11-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.949976E+10 | 0.00 | 674.15 | 0.630370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15800.63 | 09-SEP-08:61 | 15385.93 | 11-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.602678E+10 | 0.00 | 640.32 | 0.435033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15305.24 | 21-OCT-15:01 | 15305.24 | 21-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.212641E+10 | 0.00 | 358.77 | 0.200685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14930.59 | 09-NOV-16:01 | 14930.59 | 09-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.369382E+09 | 0.00 | 110.18 | 0.369382E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14069.01 | 23-DEC-16:01 | 14069.01 | 23-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.681824E+11 | 0.00 | 5884.45 | 0.514016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.369382E+09 | 0.00 | 110.18 | 0.369382E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14069.01 | 14069.01 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.115254E+11 | 0.00 | 706.39 | 0.828857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17009.89 | 15388.05 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.131543E+09 | 0.00 | 38.26 | 0.130999E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13985.84 | 12-JAN-16:01 | 13985.84 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.368761E+09 | 0.00 | 99.85 | 0.368091E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14777.23 | 20-FEB-16:01 | 14777.23 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.123588E+10 | 0.00 | 245.64 | 0.123317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14934.58 | 21-MAR-15:01 | 14934.58 | 21-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.451657E+10 | 0.00 | 549.83 | 0.420757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15270.26 | 19-APR-18:01 | 15270.26 | 19-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.812970E+10 | 0.00 | 675.31 | 0.685950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15271.49 | 20-MAY-18:01 | 15271.49 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.107027E+11 | 0.00 | 683.99 | 0.838306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15268.60 | 17-JUN-15:02 | 15268.60 | 17-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.114724E+11 | 0.00 | 707.08 | 0.738141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16518.49 | 08-JUL-08:61 | 14141.31 | 11-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.988001E+10 | 0.00 | 688.04 | 0.631301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15765.98 | 02-AUG-08:61 | 14092.94 | 18-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.798041E+10 | 0.00 | 653.37 | 0.495802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15608.10 | 09-SEP-08:61 | 15269.11 | 11-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.406955E+10 | 0.00 | 558.47 | 0.271128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15188.88 | 21-OCT-15:01 | 15188.88 | 21-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.690078E+09 | 0.00 | 185.46 | 0.633956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14818.10 | 09-NOV-16:01 | 14818.10 | 09-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 52500207.29 | 0.00 | 16.77 | 52500207.29 | 0.00 | 0.00 | 0.00 | 0.00 | 13314.87 | 16-DEC-16:02 | 13314.87 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.592300E+11 | 0.00 | 5102.07 | 0.432326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 52500207.29 | 0.00 | 16.77 | 52500207.29 | 0.00 | 0.00 | 0.00 | 0.00 | 13314.87 | 13314.87 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.114724E+11 | 0.00 | 707.08 | 0.838306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16518.49 | 15271.49 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.129405E+11 | 0.00 | 291.70 | 0.129405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36097.79 | 12-JAN-14:30 | 36097.79 | 12-JAN-14:30 | 0.00 | 0.00 | 0.00 |
February | 0.122174E+11 | 0.00 | 271.52 | 0.122174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33506.84 | 07-FEB-13:40 | 33506.84 | 07-FEB-13:40 | 0.00 | 0.00 | 0.00 |
March | 0.844895E+10 | 0.00 | 263.17 | 0.844895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25257.35 | 16-MAR-13:30 | 25257.35 | 16-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.149179E+11 | 0.00 | 424.83 | 0.143412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24186.74 | 04-APR-13:30 | 24186.74 | 04-APR-13:30 | 0.00 | 0.00 | 0.00 |
May | 0.204865E+11 | 0.00 | 559.21 | 0.166138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20983.79 | 19-MAY-17:20 | 20671.11 | 19-MAY-20:20 | 0.00 | 0.00 | 0.00 |
June | 0.305562E+11 | 0.00 | 672.84 | 0.217467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25309.39 | 15-JUN-17:13 | 25309.39 | 15-JUN-17:13 | 0.00 | 0.00 | 0.00 |
July | 0.356368E+11 | 0.00 | 719.67 | 0.157876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27910.78 | 26-JUL-17:20 | 18936.68 | 26-JUL-17:20 | 0.00 | 0.00 | 0.00 |
August | 0.352593E+11 | 0.00 | 682.67 | 0.186574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30610.73 | 29-AUG-13:20 | 29522.79 | 27-AUG-13:40 | 0.00 | 0.00 | 0.00 |
September | 0.403219E+11 | 0.00 | 672.08 | 0.264905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39123.09 | 20-SEP-15:02 | 34878.53 | 18-SEP-12:40 | 0.00 | 0.00 | 0.00 |
October | 0.338967E+11 | 0.00 | 564.53 | 0.275361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44065.97 | 22-OCT-13:20 | 41305.54 | 29-OCT-13:10 | 0.00 | 0.00 | 0.00 |
November | 0.230354E+11 | 0.00 | 370.55 | 0.227344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40218.59 | 09-NOV-13:50 | 40218.59 | 09-NOV-13:50 | 0.00 | 0.00 | 0.00 |
December | 0.990409E+10 | 0.00 | 252.48 | 0.990409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30365.89 | 16-DEC-14:10 | 30365.89 | 16-DEC-14:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.277622E+12 | 0.00 | 5745.25 | 0.207419E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.844895E+10 | 0.00 | 252.48 | 0.844895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20983.79 | 18936.68 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.403219E+11 | 0.00 | 719.67 | 0.275361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44065.97 | 41305.54 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.104106E+10 | 0.00 | 91.72 | 0.100813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52497.96 | 15-JAN-09:01 | 47194.05 | 15-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.297821E+10 | 0.00 | 191.32 | 0.279047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77279.99 | 20-FEB-09:01 | 77279.99 | 20-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.813544E+10 | 0.00 | 348.77 | 0.795461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84187.57 | 21-MAR-18:01 | 84187.57 | 21-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.255835E+11 | 0.00 | 493.80 | 0.241104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94232.94 | 21-APR-18:01 | 94232.94 | 21-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.458559E+11 | 0.00 | 542.66 | 0.387127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94325.56 | 20-MAY-18:01 | 94325.56 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.617328E+11 | 0.00 | 577.74 | 0.490262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94339.11 | 06-JUN-15:02 | 94339.11 | 06-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.695542E+11 | 0.00 | 589.54 | 0.451298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104574.26 | 08-JUL-08:61 | 87732.60 | 26-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.581977E+11 | 0.00 | 558.45 | 0.371416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95961.01 | 02-AUG-08:61 | 87989.35 | 04-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.440525E+11 | 0.00 | 509.02 | 0.271598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95012.57 | 23-SEP-08:61 | 92404.10 | 11-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.244524E+11 | 0.00 | 518.64 | 0.154547E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89606.94 | 03-OCT-18:02 | 86948.54 | 21-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.408310E+10 | 0.00 | 232.86 | 0.351030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81213.16 | 08-NOV-19:01 | 81213.16 | 08-NOV-19:01 | 0.00 | 0.00 | 0.00 |
December | 0.686038E+09 | 0.00 | 62.24 | 0.686038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66057.82 | 09-DEC-09:02 | 66057.82 | 09-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.346353E+12 | 0.00 | 4716.77 | 0.252685E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.686038E+09 | 0.00 | 62.24 | 0.686038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52497.96 | 47194.05 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.695542E+11 | 0.00 | 589.54 | 0.490262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104574.26 | 94339.11 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.599809E+09 | 0.00 | 140.63 | 0.596618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12497.15 | 12-JAN-16:01 | 12497.15 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.125603E+10 | 0.00 | 255.08 | 0.124417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12982.40 | 20-FEB-16:01 | 12982.40 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.216217E+10 | 0.00 | 404.34 | 0.215637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13120.39 | 21-MAR-15:01 | 13120.39 | 21-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.554281E+10 | 0.00 | 634.86 | 0.521033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13416.25 | 27-APR-18:01 | 13416.25 | 27-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.848276E+10 | 0.00 | 718.06 | 0.721765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13415.84 | 09-MAY-18:01 | 13415.84 | 09-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.108921E+11 | 0.00 | 704.90 | 0.860525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13414.48 | 17-JUN-15:02 | 13414.48 | 17-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.117779E+11 | 0.00 | 724.87 | 0.764782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14539.09 | 19-JUL-08:62 | 12440.29 | 18-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.106839E+11 | 0.00 | 717.83 | 0.707298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13274.96 | 18-AUG-08:62 | 12410.03 | 08-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.953444E+10 | 0.00 | 695.32 | 0.634253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13414.80 | 11-SEP-18:01 | 13414.80 | 11-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.561140E+10 | 0.00 | 638.70 | 0.408191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13343.94 | 21-OCT-15:01 | 13343.94 | 21-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.200246E+10 | 0.00 | 367.69 | 0.191424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13017.35 | 09-NOV-16:01 | 13017.35 | 09-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.416595E+09 | 0.00 | 108.98 | 0.416595E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12106.53 | 16-DEC-09:02 | 12106.53 | 16-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.689624E+11 | 0.00 | 6111.28 | 0.525065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.416595E+09 | 0.00 | 108.98 | 0.416595E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12106.53 | 12106.53 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.117779E+11 | 0.00 | 724.87 | 0.860525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14539.09 | 13416.25 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 66604105.40 | 0.00 | 30.41 | 65894318.75 | 0.00 | 0.00 | 0.00 | 0.00 | 10246.66 | 04-JAN-09:02 | 10246.66 | 04-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.435069E+09 | 0.00 | 115.54 | 0.425738E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12459.22 | 21-FEB-16:01 | 12459.22 | 21-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.121903E+10 | 0.00 | 268.03 | 0.121532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12952.42 | 22-MAR-15:01 | 12952.42 | 22-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.471166E+10 | 0.00 | 595.70 | 0.440141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13307.96 | 27-APR-18:01 | 13307.96 | 27-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.825733E+10 | 0.00 | 717.59 | 0.700053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13307.54 | 09-MAY-18:01 | 13307.54 | 09-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.109533E+11 | 0.00 | 705.46 | 0.868780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13306.23 | 17-JUN-15:02 | 13306.23 | 17-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.117174E+11 | 0.00 | 724.90 | 0.763290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14375.65 | 19-JUL-08:62 | 12267.50 | 21-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.100750E+11 | 0.00 | 713.00 | 0.650388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13245.32 | 16-AUG-15:02 | 12371.12 | 08-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.799423E+10 | 0.00 | 686.43 | 0.501261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13306.38 | 11-SEP-18:01 | 13306.38 | 11-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.360864E+10 | 0.00 | 535.84 | 0.244157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13235.82 | 21-OCT-15:01 | 13235.82 | 21-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.632305E+09 | 0.00 | 161.38 | 0.591539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12625.58 | 09-NOV-16:01 | 12625.58 | 09-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 47021796.35 | 0.00 | 18.38 | 47021796.35 | 0.00 | 0.00 | 0.00 | 0.00 | 11256.06 | 09-DEC-09:02 | 11256.06 | 09-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.597176E+11 | 0.00 | 5272.66 | 0.440262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 47021796.35 | 0.00 | 18.38 | 47021796.35 | 0.00 | 0.00 | 0.00 | 0.00 | 10246.66 | 10246.66 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.117174E+11 | 0.00 | 724.90 | 0.868780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14375.65 | 13307.96 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.123977E+09 | 0.00 | 94.12 | 0.123824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3848.79 | 03-JAN-16:01 | 3848.79 | 03-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.218500E+09 | 0.00 | 149.48 | 0.218313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3959.53 | 20-FEB-16:01 | 3959.53 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.432427E+09 | 0.00 | 258.83 | 0.432389E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4001.44 | 21-MAR-15:01 | 4001.44 | 21-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.120958E+10 | 0.00 | 537.09 | 0.112591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4091.51 | 19-APR-18:01 | 4091.51 | 19-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.201804E+10 | 0.00 | 672.58 | 0.167916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4091.68 | 20-MAY-18:01 | 4091.68 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.273804E+10 | 0.00 | 681.07 | 0.211493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4090.98 | 17-JUN-15:02 | 4090.98 | 17-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.296315E+10 | 0.00 | 703.83 | 0.187179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4689.66 | 20-JUL-08:61 | 3793.34 | 18-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.264212E+10 | 0.00 | 694.40 | 0.170211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4316.95 | 02-AUG-08:61 | 3788.92 | 26-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.230778E+10 | 0.00 | 666.05 | 0.149588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4337.65 | 09-SEP-08:61 | 4091.09 | 11-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.130232E+10 | 0.00 | 550.54 | 0.932957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4069.74 | 21-OCT-15:01 | 4069.74 | 21-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.393475E+09 | 0.00 | 258.56 | 0.374931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3970.08 | 09-NOV-16:01 | 3970.08 | 09-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 68596471.03 | 0.00 | 61.45 | 68596471.03 | 0.00 | 0.00 | 0.00 | 0.00 | 3740.98 | 23-DEC-16:01 | 3740.98 | 23-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164180E+11 | 0.00 | 5327.99 | 0.121408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 68596471.03 | 0.00 | 61.45 | 68596471.03 | 0.00 | 0.00 | 0.00 | 0.00 | 3740.98 | 3740.98 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.296315E+10 | 0.00 | 703.83 | 0.211493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4689.66 | 4091.68 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 19453280.16 | 0.00 | 22.32 | 19308246.28 | 0.00 | 0.00 | 0.00 | 0.00 | 3669.60 | 12-JAN-16:01 | 3669.60 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 63847607.68 | 0.00 | 52.98 | 63727887.10 | 0.00 | 0.00 | 0.00 | 0.00 | 3924.17 | 20-FEB-16:01 | 3924.17 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.234176E+09 | 0.00 | 164.33 | 0.234133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3965.90 | 21-MAR-15:01 | 3965.90 | 21-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.101414E+10 | 0.00 | 494.67 | 0.939172E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4055.30 | 19-APR-18:01 | 4055.30 | 19-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.196328E+10 | 0.00 | 665.83 | 0.162926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4055.38 | 20-MAY-18:01 | 4055.38 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.275526E+10 | 0.00 | 682.92 | 0.213764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4054.67 | 17-JUN-15:02 | 4054.67 | 17-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.294932E+10 | 0.00 | 705.10 | 0.186731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4560.54 | 08-JUL-08:61 | 3768.07 | 18-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.248524E+10 | 0.00 | 687.38 | 0.156596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4316.69 | 02-AUG-08:61 | 3759.37 | 26-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.190710E+10 | 0.00 | 645.74 | 0.115134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4273.28 | 23-SEP-08:61 | 4054.89 | 11-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.817569E+09 | 0.00 | 434.34 | 0.542648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4033.50 | 21-OCT-15:01 | 4033.50 | 21-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.107922E+09 | 0.00 | 93.54 | 0.100690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3934.91 | 09-NOV-16:01 | 3934.91 | 09-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 8203954.65 | 0.00 | 9.80 | 8203954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 3444.38 | 16-DEC-16:02 | 3444.38 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143255E+11 | 0.00 | 4658.94 | 0.102594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8203954.65 | 0.00 | 9.80 | 8203954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 3444.38 | 3444.38 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.294932E+10 | 0.00 | 705.10 | 0.213764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4560.54 | 4055.38 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.396812E+10 | 0.00 | 360.59 | 0.395843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17001.46 | 03-JAN-16:01 | 17001.46 | 03-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.398326E+10 | 0.00 | 378.94 | 0.396888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17490.48 | 20-FEB-16:01 | 17490.48 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.384131E+10 | 0.00 | 439.02 | 0.382890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17675.70 | 21-MAR-15:01 | 17675.70 | 21-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.622106E+10 | 0.00 | 581.43 | 0.577389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18067.01 | 21-APR-18:01 | 18067.01 | 21-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.858777E+10 | 0.00 | 667.69 | 0.693302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18070.33 | 12-MAY-15:02 | 18070.33 | 12-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.116712E+11 | 0.00 | 670.14 | 0.867014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18068.67 | 11-JUN-18:01 | 18068.67 | 11-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.135021E+11 | 0.00 | 693.57 | 0.818210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20926.61 | 20-JUL-08:61 | 16788.34 | 26-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.129933E+11 | 0.00 | 688.40 | 0.829040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18902.72 | 02-AUG-08:61 | 16764.87 | 18-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.131179E+11 | 0.00 | 673.58 | 0.899396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19046.99 | 09-SEP-08:61 | 18067.88 | 30-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.103338E+11 | 0.00 | 648.36 | 0.809790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17976.73 | 21-OCT-15:01 | 17976.73 | 21-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.625146E+10 | 0.00 | 450.97 | 0.605658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17534.77 | 09-NOV-16:01 | 17534.77 | 09-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.354599E+10 | 0.00 | 335.12 | 0.354579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16559.95 | 10-DEC-16:01 | 16559.95 | 10-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.980173E+11 | 0.00 | 6587.81 | 0.763000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.354599E+10 | 0.00 | 335.12 | 0.354579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16559.95 | 16559.95 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.135021E+11 | 0.00 | 693.57 | 0.899396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20926.61 | 18070.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 706.15 | 535.07 | 171.08 | 936.90 | 526.87 | 0.00 | 0.00 | 0.00 |
February | 664.38 | 471.17 | 193.21 | 899.09 | 470.98 | 0.00 | 0.00 | 0.00 |
March | 519.74 | 294.46 | 225.28 | 722.65 | 414.77 | 0.00 | 0.00 | 0.00 |
April | 362.15 | 135.95 | 226.20 | 570.90 | 253.53 | 0.00 | 0.00 | 0.00 |
May | 257.00 | 37.69 | 219.31 | 454.65 | 145.71 | 0.00 | 0.00 | 0.00 |
June | 219.82 | 13.83 | 205.99 | 484.63 | 68.67 | 0.00 | 0.00 | 0.00 |
July | 223.23 | 19.79 | 203.44 | 493.07 | 52.25 | 0.00 | 0.00 | 0.00 |
August | 281.79 | 71.59 | 210.20 | 579.52 | 78.82 | 0.00 | 0.00 | 0.00 |
September | 446.25 | 231.85 | 214.40 | 827.70 | 166.54 | 0.00 | 0.00 | 0.00 |
October | 612.55 | 416.17 | 196.38 | 965.68 | 273.03 | 0.00 | 0.00 | 0.00 |
November | 737.24 | 563.91 | 173.33 | 1026.16 | 450.35 | 0.00 | 0.00 | 0.00 |
December | 724.95 | 544.65 | 180.31 | 942.51 | 563.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 478.50 | 276.88 | 201.63 | 740.82 | 287.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 219.82 | 13.83 | 171.08 | 454.65 | 52.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 737.24 | 563.91 | 226.20 | 1026.16 | 563.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1988.48 | 1506.73 | 481.75 | 2631.95 | 1514.06 | 0.00 | 0.00 | 0.00 |
February | 1870.85 | 1326.79 | 544.06 | 2528.06 | 1342.97 | 0.00 | 0.00 | 0.00 |
March | 1463.55 | 829.18 | 634.37 | 2049.72 | 1168.12 | 0.00 | 0.00 | 0.00 |
April | 1019.80 | 382.82 | 636.98 | 1648.81 | 688.96 | 0.00 | 0.00 | 0.00 |
May | 723.68 | 106.13 | 617.55 | 1346.07 | 384.20 | 0.00 | 0.00 | 0.00 |
June | 618.99 | 38.95 | 580.04 | 1429.59 | 179.07 | 0.00 | 0.00 | 0.00 |
July | 628.60 | 55.73 | 572.87 | 1449.74 | 133.55 | 0.00 | 0.00 | 0.00 |
August | 793.51 | 201.60 | 591.90 | 1679.22 | 208.36 | 0.00 | 0.00 | 0.00 |
September | 1256.61 | 652.87 | 603.74 | 2350.75 | 450.04 | 0.00 | 0.00 | 0.00 |
October | 1724.89 | 1171.91 | 552.99 | 2729.66 | 753.87 | 0.00 | 0.00 | 0.00 |
November | 2076.02 | 1587.93 | 488.09 | 2877.82 | 1276.61 | 0.00 | 0.00 | 0.00 |
December | 2041.42 | 1533.69 | 507.73 | 2645.50 | 1618.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1347.44 | 779.68 | 567.76 | 2110.91 | 807.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 618.99 | 38.95 | 481.75 | 1346.07 | 133.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2076.02 | 1587.93 | 636.98 | 2877.82 | 1618.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2583.15 | 1957.32 | 625.82 | 3473.40 | 2080.95 | 0.00 | 0.00 | 0.00 |
February | 2430.34 | 1723.58 | 706.76 | 3336.16 | 1849.02 | 0.00 | 0.00 | 0.00 |
March | 1901.24 | 1077.15 | 824.09 | 2691.88 | 1622.84 | 0.00 | 0.00 | 0.00 |
April | 1324.78 | 497.31 | 827.47 | 2157.31 | 964.80 | 0.00 | 0.00 | 0.00 |
May | 940.11 | 137.87 | 802.24 | 1743.19 | 538.11 | 0.00 | 0.00 | 0.00 |
June | 804.10 | 50.59 | 753.51 | 1865.14 | 243.97 | 0.00 | 0.00 | 0.00 |
July | 816.59 | 72.40 | 744.19 | 1892.59 | 182.42 | 0.00 | 0.00 | 0.00 |
August | 1030.81 | 261.90 | 768.91 | 2207.31 | 281.11 | 0.00 | 0.00 | 0.00 |
September | 1632.41 | 848.12 | 784.29 | 3110.07 | 600.14 | 0.00 | 0.00 | 0.00 |
October | 2240.73 | 1522.37 | 718.36 | 3601.92 | 1024.88 | 0.00 | 0.00 | 0.00 |
November | 2696.87 | 2062.81 | 634.06 | 3801.65 | 1748.72 | 0.00 | 0.00 | 0.00 |
December | 2651.92 | 1992.35 | 659.58 | 3487.65 | 2224.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1750.40 | 1012.84 | 737.56 | 2776.64 | 1109.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 804.10 | 50.59 | 625.82 | 1743.19 | 182.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2696.87 | 2062.81 | 827.47 | 3801.65 | 2224.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 189.57 | 99.44 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 182.26 | 87.41 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 146.28 | 76.12 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 118.71 | 40.70 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 99.97 | 19.23 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 111.48 | 6.72 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 112.62 | 3.80 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 127.64 | 7.58 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 172.30 | 22.33 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 197.58 | 43.68 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 208.08 | 81.83 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 191.78 | 107.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 154.65 | 49.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 99.97 | 3.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 208.08 | 107.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 114.60 | 205.39 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 139.65 | 180.25 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 213.32 | 147.44 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 294.22 | 75.12 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 361.44 | 35.56 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 408.04 | 12.47 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 367.99 | 6.88 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 338.71 | 14.04 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 318.07 | 42.21 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 233.75 | 85.60 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 154.17 | 169.33 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 102.62 | 225.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 254.38 | 99.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 102.62 | 6.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 408.04 | 225.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 4.64 | 110.65 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 12.21 | 96.66 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 24.55 | 79.59 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 49.54 | 39.27 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 83.78 | 17.76 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 118.02 | 6.47 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 110.18 | 3.62 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 86.70 | 7.22 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 62.47 | 22.07 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 33.04 | 45.17 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 8.90 | 91.14 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 3.32 | 122.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 49.98 | 53.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 3.32 | 3.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 118.02 | 122.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 121.21 | 199.06 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 146.11 | 175.21 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 218.52 | 144.71 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 296.77 | 74.23 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 362.02 | 35.41 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 407.88 | 12.48 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 368.10 | 6.86 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 339.96 | 13.81 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 320.99 | 41.14 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 238.48 | 83.17 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 160.47 | 164.30 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 109.09 | 219.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 257.95 | 97.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 109.09 | 6.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 407.88 | 219.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.67 | 84.62 | 27.06 | 146.83 | 89.20 | 0.00 | 0.00 | 0.00 |
February | 105.07 | 74.51 | 30.55 | 141.11 | 79.40 | 0.00 | 0.00 | 0.00 |
March | 82.19 | 46.57 | 35.63 | 113.38 | 68.18 | 0.00 | 0.00 | 0.00 |
April | 57.27 | 21.50 | 35.77 | 92.64 | 38.61 | 0.00 | 0.00 | 0.00 |
May | 40.64 | 5.96 | 34.68 | 77.73 | 19.86 | 0.00 | 0.00 | 0.00 |
June | 34.76 | 2.19 | 32.58 | 86.17 | 8.05 | 0.00 | 0.00 | 0.00 |
July | 35.30 | 3.13 | 32.17 | 86.57 | 5.59 | 0.00 | 0.00 | 0.00 |
August | 44.56 | 11.32 | 33.24 | 98.89 | 9.55 | 0.00 | 0.00 | 0.00 |
September | 70.57 | 36.67 | 33.91 | 135.67 | 23.22 | 0.00 | 0.00 | 0.00 |
October | 96.87 | 65.81 | 31.06 | 154.76 | 42.29 | 0.00 | 0.00 | 0.00 |
November | 116.59 | 89.18 | 27.41 | 162.46 | 74.20 | 0.00 | 0.00 | 0.00 |
December | 114.65 | 86.13 | 28.51 | 148.19 | 95.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 43.79 | 31.89 | 120.21 | 45.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.76 | 2.19 | 27.06 | 77.73 | 5.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 116.59 | 89.18 | 35.77 | 162.46 | 95.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.32 | 0.00 | 16.32 | 3.62 | 90.39 | 0.00 | 0.00 | 0.00 |
February | 19.93 | 0.00 | 19.93 | 10.40 | 78.15 | 0.00 | 0.00 | 0.00 |
March | 26.09 | 0.00 | 26.09 | 21.37 | 63.04 | 0.00 | 0.00 | 0.00 |
April | 30.29 | 0.39 | 29.91 | 43.83 | 29.66 | 0.00 | 0.00 | 0.00 |
May | 35.78 | 2.64 | 33.15 | 72.80 | 12.63 | 0.00 | 0.00 | 0.00 |
June | 38.05 | 4.74 | 33.31 | 101.15 | 4.15 | 0.00 | 0.00 | 0.00 |
July | 35.16 | 3.45 | 31.71 | 94.69 | 2.07 | 0.00 | 0.00 | 0.00 |
August | 29.73 | 0.71 | 29.03 | 75.55 | 4.62 | 0.00 | 0.00 | 0.00 |
September | 25.87 | 0.03 | 25.84 | 55.18 | 15.53 | 0.00 | 0.00 | 0.00 |
October | 21.44 | 0.00 | 21.44 | 29.73 | 34.10 | 0.00 | 0.00 | 0.00 |
November | 17.31 | 0.00 | 17.31 | 8.11 | 72.40 | 0.00 | 0.00 | 0.00 |
December | 16.19 | 0.00 | 16.19 | 2.46 | 100.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.04 | 1.00 | 25.04 | 43.41 | 42.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.19 | 0.00 | 16.19 | 2.46 | 2.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.05 | 4.74 | 33.31 | 101.15 | 100.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.70 | 55.11 | 46.60 | 95.67 | 194.75 | 0.00 | 0.00 | 0.00 |
February | 136.50 | 77.83 | 58.67 | 153.15 | 167.70 | 0.00 | 0.00 | 0.00 |
March | 168.25 | 92.64 | 75.61 | 208.89 | 135.81 | 0.00 | 0.00 | 0.00 |
April | 202.82 | 112.49 | 90.33 | 310.16 | 67.96 | 0.00 | 0.00 | 0.00 |
May | 209.08 | 113.58 | 95.50 | 367.85 | 32.33 | 0.00 | 0.00 | 0.00 |
June | 209.17 | 116.31 | 92.86 | 425.66 | 11.62 | 0.00 | 0.00 | 0.00 |
July | 187.70 | 98.13 | 89.57 | 387.06 | 6.61 | 0.00 | 0.00 | 0.00 |
August | 178.80 | 91.56 | 87.24 | 352.65 | 13.18 | 0.00 | 0.00 | 0.00 |
September | 177.40 | 101.30 | 76.10 | 317.17 | 38.57 | 0.00 | 0.00 | 0.00 |
October | 135.78 | 73.14 | 62.64 | 201.20 | 80.17 | 0.00 | 0.00 | 0.00 |
November | 121.58 | 70.62 | 50.96 | 134.18 | 157.79 | 0.00 | 0.00 | 0.00 |
December | 101.78 | 53.93 | 47.85 | 91.42 | 213.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.90 | 88.01 | 72.89 | 254.11 | 93.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.70 | 53.93 | 46.60 | 91.42 | 6.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.17 | 116.31 | 95.50 | 425.66 | 213.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 188.94 | 98.86 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 180.59 | 87.22 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 144.51 | 75.64 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 117.12 | 40.60 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 98.90 | 19.03 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 110.64 | 6.54 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 111.91 | 3.66 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 127.01 | 7.44 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 171.61 | 22.01 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 197.07 | 42.92 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 207.22 | 81.20 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 191.10 | 107.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 153.69 | 49.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 98.90 | 3.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 207.22 | 107.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 4.33 | 110.31 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 11.39 | 97.20 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 23.27 | 79.76 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 47.81 | 39.34 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 82.56 | 17.47 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 117.26 | 6.30 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 109.52 | 3.49 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 85.98 | 7.07 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 61.66 | 21.86 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 32.34 | 44.58 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 8.46 | 90.51 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 2.99 | 122.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 49.17 | 53.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 2.99 | 3.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 117.26 | 122.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.70 | 55.11 | 46.60 | 100.85 | 186.73 | 0.00 | 0.00 | 0.00 |
February | 136.50 | 77.83 | 58.67 | 159.00 | 161.99 | 0.00 | 0.00 | 0.00 |
March | 168.25 | 92.64 | 75.61 | 213.58 | 132.88 | 0.00 | 0.00 | 0.00 |
April | 202.82 | 112.49 | 90.33 | 312.25 | 67.14 | 0.00 | 0.00 | 0.00 |
May | 209.08 | 113.58 | 95.50 | 368.35 | 32.20 | 0.00 | 0.00 | 0.00 |
June | 209.17 | 116.31 | 92.86 | 425.61 | 11.63 | 0.00 | 0.00 | 0.00 |
July | 187.70 | 98.13 | 89.57 | 387.24 | 6.60 | 0.00 | 0.00 | 0.00 |
August | 178.80 | 91.56 | 87.24 | 353.83 | 12.98 | 0.00 | 0.00 | 0.00 |
September | 177.40 | 101.30 | 76.10 | 319.86 | 37.59 | 0.00 | 0.00 | 0.00 |
October | 135.78 | 73.14 | 62.64 | 205.45 | 77.76 | 0.00 | 0.00 | 0.00 |
November | 121.58 | 70.62 | 50.96 | 140.23 | 151.68 | 0.00 | 0.00 | 0.00 |
December | 101.78 | 53.93 | 47.85 | 95.73 | 204.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.90 | 88.01 | 72.89 | 257.17 | 89.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.70 | 53.93 | 46.60 | 95.73 | 6.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.17 | 116.31 | 95.50 | 425.61 | 204.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.83 | 0.00 | 25.83 | 3.57 | 156.83 | 0.00 | 0.00 | 0.00 |
February | 31.55 | 0.00 | 31.55 | 12.62 | 138.16 | 0.00 | 0.00 | 0.00 |
March | 41.29 | 0.00 | 41.29 | 28.24 | 113.65 | 0.00 | 0.00 | 0.00 |
April | 47.95 | 0.61 | 47.34 | 59.14 | 61.61 | 0.00 | 0.00 | 0.00 |
May | 56.64 | 4.17 | 52.47 | 99.53 | 31.73 | 0.00 | 0.00 | 0.00 |
June | 60.23 | 7.51 | 52.73 | 140.82 | 13.85 | 0.00 | 0.00 | 0.00 |
July | 55.65 | 5.46 | 50.19 | 130.16 | 9.96 | 0.00 | 0.00 | 0.00 |
August | 47.06 | 1.12 | 45.94 | 101.27 | 16.36 | 0.00 | 0.00 | 0.00 |
September | 40.94 | 0.05 | 40.89 | 73.62 | 39.56 | 0.00 | 0.00 | 0.00 |
October | 33.94 | 0.00 | 33.94 | 36.69 | 72.54 | 0.00 | 0.00 | 0.00 |
November | 27.40 | 0.00 | 27.40 | 7.92 | 134.40 | 0.00 | 0.00 | 0.00 |
December | 25.63 | 0.00 | 25.63 | 2.50 | 171.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.22 | 1.58 | 39.64 | 58.24 | 79.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.63 | 0.00 | 25.63 | 2.50 | 9.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.23 | 7.51 | 52.73 | 140.82 | 171.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.52 | 0.00 | 9.52 | 1.32 | 57.81 | 0.00 | 0.00 | 0.00 |
February | 11.63 | 0.00 | 11.63 | 4.65 | 50.93 | 0.00 | 0.00 | 0.00 |
March | 15.22 | 0.00 | 15.22 | 10.41 | 41.90 | 0.00 | 0.00 | 0.00 |
April | 17.68 | 0.23 | 17.45 | 21.80 | 22.71 | 0.00 | 0.00 | 0.00 |
May | 20.88 | 1.54 | 19.34 | 36.69 | 11.70 | 0.00 | 0.00 | 0.00 |
June | 22.20 | 2.77 | 19.44 | 51.91 | 5.10 | 0.00 | 0.00 | 0.00 |
July | 20.51 | 2.01 | 18.50 | 47.98 | 3.67 | 0.00 | 0.00 | 0.00 |
August | 17.35 | 0.41 | 16.94 | 37.33 | 6.03 | 0.00 | 0.00 | 0.00 |
September | 15.09 | 0.02 | 15.07 | 27.14 | 14.58 | 0.00 | 0.00 | 0.00 |
October | 12.51 | 0.00 | 12.51 | 13.53 | 26.74 | 0.00 | 0.00 | 0.00 |
November | 10.10 | 0.00 | 10.10 | 2.92 | 49.55 | 0.00 | 0.00 | 0.00 |
December | 9.45 | 0.00 | 9.45 | 0.92 | 63.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.20 | 0.58 | 14.61 | 21.47 | 29.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.45 | 0.00 | 9.45 | 0.92 | 3.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.20 | 2.77 | 19.44 | 51.91 | 63.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.15 | 49.36 | 15.78 | 88.27 | 49.82 | 0.00 | 0.00 | 0.00 |
February | 61.29 | 43.47 | 17.82 | 84.70 | 44.44 | 0.00 | 0.00 | 0.00 |
March | 47.95 | 27.17 | 20.78 | 67.89 | 39.10 | 0.00 | 0.00 | 0.00 |
April | 33.41 | 12.54 | 20.87 | 54.51 | 23.11 | 0.00 | 0.00 | 0.00 |
May | 23.71 | 3.48 | 20.23 | 44.55 | 12.61 | 0.00 | 0.00 | 0.00 |
June | 20.28 | 1.28 | 19.00 | 48.91 | 5.36 | 0.00 | 0.00 | 0.00 |
July | 20.59 | 1.83 | 18.77 | 49.22 | 3.88 | 0.00 | 0.00 | 0.00 |
August | 26.00 | 6.60 | 19.39 | 56.77 | 6.28 | 0.00 | 0.00 | 0.00 |
September | 41.17 | 21.39 | 19.78 | 78.82 | 14.38 | 0.00 | 0.00 | 0.00 |
October | 56.51 | 38.39 | 18.12 | 90.86 | 25.01 | 0.00 | 0.00 | 0.00 |
November | 68.01 | 52.02 | 15.99 | 96.31 | 42.70 | 0.00 | 0.00 | 0.00 |
December | 66.88 | 50.25 | 16.63 | 89.25 | 53.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.14 | 25.54 | 18.60 | 70.74 | 26.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.28 | 1.28 | 15.78 | 44.55 | 3.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.01 | 52.02 | 20.87 | 96.31 | 53.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 176.82 | 133.98 | 42.84 | 239.59 | 135.22 | 0.00 | 0.00 | 0.00 |
February | 166.36 | 117.98 | 48.38 | 229.90 | 120.62 | 0.00 | 0.00 | 0.00 |
March | 130.14 | 73.73 | 56.41 | 184.26 | 106.13 | 0.00 | 0.00 | 0.00 |
April | 90.68 | 34.04 | 56.64 | 147.96 | 62.72 | 0.00 | 0.00 | 0.00 |
May | 64.35 | 9.44 | 54.91 | 120.93 | 34.22 | 0.00 | 0.00 | 0.00 |
June | 55.04 | 3.46 | 51.58 | 132.74 | 14.55 | 0.00 | 0.00 | 0.00 |
July | 55.90 | 4.96 | 50.94 | 133.58 | 10.52 | 0.00 | 0.00 | 0.00 |
August | 70.56 | 17.93 | 52.63 | 154.09 | 17.04 | 0.00 | 0.00 | 0.00 |
September | 111.74 | 58.05 | 53.69 | 213.93 | 39.04 | 0.00 | 0.00 | 0.00 |
October | 153.38 | 104.21 | 49.17 | 246.62 | 67.89 | 0.00 | 0.00 | 0.00 |
November | 184.60 | 141.20 | 43.40 | 261.40 | 115.89 | 0.00 | 0.00 | 0.00 |
December | 181.53 | 136.38 | 45.15 | 242.24 | 144.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.82 | 69.33 | 50.49 | 192.00 | 72.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 55.04 | 3.46 | 42.84 | 120.93 | 10.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 184.60 | 141.20 | 56.64 | 261.40 | 144.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 188.93 | 97.91 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 181.60 | 85.84 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 145.52 | 74.70 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 118.03 | 39.47 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 99.90 | 18.28 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 111.64 | 6.26 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 112.45 | 3.48 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 127.22 | 7.08 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 171.24 | 21.46 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 196.60 | 42.45 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 207.51 | 80.12 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 191.54 | 106.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 154.15 | 48.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 99.90 | 3.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 207.51 | 106.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 114.26 | 201.77 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 139.15 | 176.57 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 212.14 | 144.28 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 292.56 | 72.72 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 359.67 | 33.74 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 406.55 | 11.66 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 366.44 | 6.29 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 337.24 | 13.11 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 316.27 | 40.55 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 232.80 | 82.89 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 153.74 | 165.23 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 102.71 | 221.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 253.30 | 97.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 102.71 | 6.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 406.55 | 221.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 5.13 | 108.44 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 12.83 | 94.44 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 25.21 | 77.73 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 49.77 | 37.99 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 83.90 | 16.87 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 117.92 | 6.06 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 109.94 | 3.33 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 86.71 | 6.74 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 62.35 | 21.16 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 33.55 | 43.55 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 9.63 | 88.54 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 3.73 | 119.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 50.25 | 51.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 3.73 | 3.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 117.92 | 119.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 121.68 | 195.29 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 146.42 | 171.28 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 218.04 | 141.27 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 295.34 | 71.75 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 360.29 | 33.59 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 406.37 | 11.67 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 366.55 | 6.27 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 338.55 | 12.88 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 319.40 | 39.40 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 238.19 | 80.07 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 161.18 | 159.53 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 109.89 | 215.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 257.31 | 94.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 109.89 | 6.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 406.37 | 215.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 204.76 | 155.16 | 49.61 | 269.03 | 150.76 | 0.00 | 0.00 | 0.00 |
February | 192.65 | 136.63 | 56.02 | 259.50 | 131.42 | 0.00 | 0.00 | 0.00 |
March | 150.71 | 85.38 | 65.33 | 209.51 | 111.58 | 0.00 | 0.00 | 0.00 |
April | 105.01 | 39.42 | 65.59 | 174.21 | 56.95 | 0.00 | 0.00 | 0.00 |
May | 74.52 | 10.93 | 63.59 | 151.45 | 25.36 | 0.00 | 0.00 | 0.00 |
June | 63.74 | 4.01 | 59.73 | 170.72 | 8.16 | 0.00 | 0.00 | 0.00 |
July | 64.73 | 5.74 | 58.99 | 171.15 | 4.34 | 0.00 | 0.00 | 0.00 |
August | 81.71 | 20.76 | 60.95 | 191.19 | 9.57 | 0.00 | 0.00 | 0.00 |
September | 129.40 | 67.23 | 62.17 | 252.83 | 30.49 | 0.00 | 0.00 | 0.00 |
October | 177.62 | 120.68 | 56.94 | 286.47 | 63.13 | 0.00 | 0.00 | 0.00 |
November | 213.78 | 163.52 | 50.26 | 298.62 | 122.20 | 0.00 | 0.00 | 0.00 |
December | 210.22 | 157.93 | 52.28 | 271.85 | 163.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 138.75 | 80.29 | 58.47 | 225.28 | 72.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.74 | 4.01 | 49.61 | 151.45 | 4.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 213.78 | 163.52 | 65.59 | 298.62 | 163.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.78 | 0.00 | 142.78 | 15.55 | 919.78 | 0.00 | 0.00 | 0.00 |
February | 174.35 | 0.00 | 174.35 | 63.66 | 805.89 | 0.00 | 0.00 | 0.00 |
March | 228.22 | 0.01 | 228.21 | 144.98 | 666.27 | 0.00 | 0.00 | 0.00 |
April | 265.01 | 3.38 | 261.64 | 320.23 | 358.11 | 0.00 | 0.00 | 0.00 |
May | 313.05 | 23.07 | 289.98 | 548.04 | 184.19 | 0.00 | 0.00 | 0.00 |
June | 332.91 | 41.48 | 291.42 | 774.30 | 84.43 | 0.00 | 0.00 | 0.00 |
July | 307.56 | 30.17 | 277.39 | 714.65 | 63.43 | 0.00 | 0.00 | 0.00 |
August | 260.12 | 6.19 | 253.93 | 560.71 | 99.09 | 0.00 | 0.00 | 0.00 |
September | 226.30 | 0.29 | 226.02 | 415.58 | 220.82 | 0.00 | 0.00 | 0.00 |
October | 187.59 | 0.00 | 187.59 | 207.93 | 406.55 | 0.00 | 0.00 | 0.00 |
November | 151.44 | 0.00 | 151.44 | 43.82 | 759.69 | 0.00 | 0.00 | 0.00 |
December | 141.68 | 0.00 | 141.68 | 10.85 | 1001.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.84 | 8.76 | 219.09 | 319.68 | 462.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.68 | 0.00 | 141.68 | 10.85 | 63.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.91 | 41.48 | 291.42 | 774.30 | 1001.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.78 | 0.00 | 142.78 | 11.54 | 961.27 | 0.00 | 0.00 | 0.00 |
February | 174.35 | 0.00 | 174.35 | 55.99 | 839.97 | 0.00 | 0.00 | 0.00 |
March | 228.22 | 0.01 | 228.21 | 132.95 | 692.95 | 0.00 | 0.00 | 0.00 |
April | 265.01 | 3.38 | 261.64 | 305.80 | 371.72 | 0.00 | 0.00 | 0.00 |
May | 313.05 | 23.07 | 289.98 | 531.44 | 191.63 | 0.00 | 0.00 | 0.00 |
June | 332.91 | 41.48 | 291.42 | 756.62 | 88.94 | 0.00 | 0.00 | 0.00 |
July | 307.56 | 30.17 | 277.39 | 697.28 | 67.96 | 0.00 | 0.00 | 0.00 |
August | 260.12 | 6.19 | 253.93 | 544.14 | 104.67 | 0.00 | 0.00 | 0.00 |
September | 226.30 | 0.29 | 226.02 | 402.26 | 230.13 | 0.00 | 0.00 | 0.00 |
October | 187.59 | 0.00 | 187.59 | 197.07 | 422.59 | 0.00 | 0.00 | 0.00 |
November | 151.44 | 0.00 | 151.44 | 37.50 | 790.32 | 0.00 | 0.00 | 0.00 |
December | 141.68 | 0.00 | 141.68 | 8.15 | 1045.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.84 | 8.76 | 219.09 | 308.04 | 482.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.68 | 0.00 | 141.68 | 8.15 | 67.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.91 | 41.48 | 291.42 | 756.62 | 1045.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 2.54 | 134.14 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 10.71 | 117.25 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 23.23 | 97.31 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 53.86 | 53.06 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 90.22 | 29.40 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 125.88 | 15.00 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 118.20 | 12.01 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 95.00 | 16.85 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 72.49 | 32.18 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 36.94 | 58.20 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 8.18 | 109.26 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 1.94 | 144.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 53.49 | 68.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 1.94 | 12.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 125.88 | 144.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.40 | 110.21 | 93.19 | 190.34 | 455.85 | 0.00 | 0.00 | 0.00 |
February | 272.98 | 155.65 | 117.32 | 313.82 | 395.30 | 0.00 | 0.00 | 0.00 |
March | 336.47 | 185.26 | 151.21 | 428.31 | 327.86 | 0.00 | 0.00 | 0.00 |
April | 405.62 | 224.97 | 180.65 | 647.17 | 184.88 | 0.00 | 0.00 | 0.00 |
May | 418.14 | 227.15 | 190.99 | 764.41 | 108.70 | 0.00 | 0.00 | 0.00 |
June | 418.31 | 232.60 | 185.71 | 881.15 | 56.06 | 0.00 | 0.00 | 0.00 |
July | 375.38 | 196.25 | 179.13 | 804.21 | 45.48 | 0.00 | 0.00 | 0.00 |
August | 357.58 | 183.11 | 174.47 | 739.63 | 62.93 | 0.00 | 0.00 | 0.00 |
September | 354.77 | 202.59 | 152.18 | 680.23 | 114.99 | 0.00 | 0.00 | 0.00 |
October | 271.54 | 146.27 | 125.28 | 428.27 | 206.50 | 0.00 | 0.00 | 0.00 |
November | 243.14 | 141.22 | 101.92 | 277.01 | 368.85 | 0.00 | 0.00 | 0.00 |
December | 203.55 | 107.86 | 95.69 | 183.15 | 489.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 321.77 | 176.00 | 145.77 | 528.88 | 234.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 203.40 | 107.86 | 93.19 | 183.15 | 45.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.31 | 232.60 | 190.99 | 881.15 | 489.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 190.25 | 116.52 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 183.55 | 103.40 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 147.73 | 90.79 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 123.66 | 53.75 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 105.86 | 30.94 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 118.78 | 15.29 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 120.36 | 12.28 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 136.56 | 17.19 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 183.76 | 31.97 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 204.77 | 55.26 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 211.71 | 95.53 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 192.63 | 123.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 159.78 | 61.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 105.86 | 12.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 211.71 | 123.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.83 | 0.00 | 25.83 | 2.80 | 158.24 | 0.00 | 0.00 | 0.00 |
February | 31.55 | 0.00 | 31.55 | 10.95 | 139.91 | 0.00 | 0.00 | 0.00 |
March | 41.29 | 0.00 | 41.29 | 25.43 | 116.01 | 0.00 | 0.00 | 0.00 |
April | 47.95 | 0.61 | 47.34 | 54.55 | 64.45 | 0.00 | 0.00 | 0.00 |
May | 56.64 | 4.17 | 52.47 | 95.35 | 33.21 | 0.00 | 0.00 | 0.00 |
June | 60.23 | 7.51 | 52.73 | 136.50 | 14.96 | 0.00 | 0.00 | 0.00 |
July | 55.65 | 5.46 | 50.19 | 125.57 | 11.20 | 0.00 | 0.00 | 0.00 |
August | 47.06 | 1.12 | 45.94 | 97.06 | 17.86 | 0.00 | 0.00 | 0.00 |
September | 40.94 | 0.05 | 40.89 | 70.35 | 41.22 | 0.00 | 0.00 | 0.00 |
October | 33.94 | 0.00 | 33.94 | 33.62 | 75.04 | 0.00 | 0.00 | 0.00 |
November | 27.40 | 0.00 | 27.40 | 6.51 | 135.23 | 0.00 | 0.00 | 0.00 |
December | 25.63 | 0.00 | 25.63 | 2.07 | 172.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.22 | 1.58 | 39.64 | 55.30 | 81.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.63 | 0.00 | 25.63 | 2.07 | 11.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.23 | 7.51 | 52.73 | 136.50 | 172.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.11 | 0.00 | 23.11 | 2.51 | 141.58 | 0.00 | 0.00 | 0.00 |
February | 28.22 | 0.00 | 28.22 | 9.80 | 125.18 | 0.00 | 0.00 | 0.00 |
March | 36.94 | 0.00 | 36.94 | 22.75 | 103.80 | 0.00 | 0.00 | 0.00 |
April | 42.90 | 0.55 | 42.35 | 48.80 | 57.67 | 0.00 | 0.00 | 0.00 |
May | 50.68 | 3.73 | 46.94 | 85.31 | 29.72 | 0.00 | 0.00 | 0.00 |
June | 53.89 | 6.72 | 47.17 | 122.13 | 13.38 | 0.00 | 0.00 | 0.00 |
July | 49.79 | 4.88 | 44.90 | 112.35 | 10.02 | 0.00 | 0.00 | 0.00 |
August | 42.11 | 1.00 | 41.11 | 86.84 | 15.98 | 0.00 | 0.00 | 0.00 |
September | 36.63 | 0.05 | 36.59 | 62.94 | 36.88 | 0.00 | 0.00 | 0.00 |
October | 30.37 | 0.00 | 30.37 | 30.08 | 67.14 | 0.00 | 0.00 | 0.00 |
November | 24.51 | 0.00 | 24.51 | 5.83 | 120.99 | 0.00 | 0.00 | 0.00 |
December | 22.93 | 0.00 | 22.93 | 1.85 | 154.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.88 | 1.42 | 35.46 | 49.47 | 72.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.93 | 0.00 | 22.93 | 1.85 | 10.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.89 | 6.72 | 47.17 | 122.13 | 154.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 521.24 | 394.96 | 126.28 | 695.59 | 399.84 | 0.00 | 0.00 | 0.00 |
February | 490.41 | 347.79 | 142.61 | 665.47 | 359.23 | 0.00 | 0.00 | 0.00 |
March | 383.64 | 217.35 | 166.29 | 528.32 | 318.72 | 0.00 | 0.00 | 0.00 |
April | 267.32 | 100.35 | 166.97 | 419.30 | 193.45 | 0.00 | 0.00 | 0.00 |
May | 189.70 | 27.82 | 161.88 | 343.83 | 105.74 | 0.00 | 0.00 | 0.00 |
June | 162.26 | 10.21 | 152.05 | 379.33 | 46.31 | 0.00 | 0.00 | 0.00 |
July | 164.78 | 14.61 | 150.17 | 380.51 | 35.00 | 0.00 | 0.00 | 0.00 |
August | 208.00 | 52.85 | 155.16 | 440.66 | 55.01 | 0.00 | 0.00 | 0.00 |
September | 329.40 | 171.14 | 158.26 | 617.99 | 120.00 | 0.00 | 0.00 | 0.00 |
October | 452.15 | 307.19 | 144.96 | 712.46 | 206.68 | 0.00 | 0.00 | 0.00 |
November | 544.19 | 416.24 | 127.94 | 759.61 | 342.06 | 0.00 | 0.00 | 0.00 |
December | 535.12 | 402.02 | 133.09 | 704.64 | 425.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 353.20 | 204.38 | 148.83 | 553.17 | 216.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.26 | 10.21 | 126.28 | 343.83 | 35.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 544.19 | 416.24 | 166.97 | 759.61 | 425.75 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189136E+10 | 0.143314E+10 | 0.458222E+09 | 0.250939E+10 | 0.141116E+10 |
February | 0.160727E+10 | 0.113986E+10 | 0.467406E+09 | 0.217508E+10 | 0.113939E+10 |
March | 0.139207E+10 | 0.788679E+09 | 0.603391E+09 | 0.193554E+10 | 0.111093E+10 |
April | 0.938702E+09 | 0.352379E+09 | 0.586322E+09 | 0.147978E+10 | 0.657155E+09 |
May | 0.688337E+09 | 0.100947E+09 | 0.587390E+09 | 0.121775E+10 | 0.390267E+09 |
June | 0.569764E+09 | 35850177.24 | 0.533914E+09 | 0.125617E+10 | 0.177994E+09 |
July | 0.597898E+09 | 53010019.83 | 0.544888E+09 | 0.132064E+10 | 0.139959E+09 |
August | 0.754750E+09 | 0.191758E+09 | 0.562992E+09 | 0.155219E+10 | 0.211114E+09 |
September | 0.115668E+10 | 0.600953E+09 | 0.555729E+09 | 0.214540E+10 | 0.431669E+09 |
October | 0.164065E+10 | 0.111467E+10 | 0.525978E+09 | 0.258648E+10 | 0.731275E+09 |
November | 0.191093E+10 | 0.146165E+10 | 0.449279E+09 | 0.265980E+10 | 0.116730E+10 |
December | 0.194172E+10 | 0.145878E+10 | 0.482936E+09 | 0.252443E+10 | 0.150861E+10 |
Annual Sum or Average | 0.150901E+11 | 0.873168E+10 | 0.635845E+10 | 0.233626E+11 | 0.907682E+10 |
Minimum of Months | 0.569764E+09 | 35850177.24 | 0.449279E+09 | 0.121775E+10 | 0.139959E+09 |
Maximum of Months | 0.194172E+10 | 0.146165E+10 | 0.603391E+09 | 0.265980E+10 | 0.150861E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.532594E+10 | 0.403562E+10 | 0.129032E+10 | 0.704941E+10 | 0.405525E+10 |
February | 0.452597E+10 | 0.320978E+10 | 0.131618E+10 | 0.611588E+10 | 0.324890E+10 |
March | 0.391998E+10 | 0.222087E+10 | 0.169911E+10 | 0.548997E+10 | 0.312870E+10 |
April | 0.264332E+10 | 0.992277E+09 | 0.165105E+10 | 0.427372E+10 | 0.178579E+10 |
May | 0.193831E+10 | 0.284261E+09 | 0.165405E+10 | 0.360530E+10 | 0.102903E+10 |
June | 0.160442E+10 | 0.100952E+09 | 0.150347E+10 | 0.370550E+10 | 0.464145E+09 |
July | 0.168364E+10 | 0.149273E+09 | 0.153437E+10 | 0.388299E+10 | 0.357712E+09 |
August | 0.212533E+10 | 0.539978E+09 | 0.158535E+10 | 0.449762E+10 | 0.558074E+09 |
September | 0.325714E+10 | 0.169224E+10 | 0.156490E+10 | 0.609315E+10 | 0.116649E+10 |
October | 0.461996E+10 | 0.313884E+10 | 0.148112E+10 | 0.731112E+10 | 0.201917E+10 |
November | 0.538106E+10 | 0.411592E+10 | 0.126514E+10 | 0.745931E+10 | 0.330898E+10 |
December | 0.546774E+10 | 0.410783E+10 | 0.135992E+10 | 0.708571E+10 | 0.433442E+10 |
Annual Sum or Average | 0.424928E+11 | 0.245878E+11 | 0.179050E+11 | 0.665697E+11 | 0.254567E+11 |
Minimum of Months | 0.160442E+10 | 0.100952E+09 | 0.126514E+10 | 0.360530E+10 | 0.357712E+09 |
Maximum of Months | 0.546774E+10 | 0.411592E+10 | 0.169911E+10 | 0.745931E+10 | 0.433442E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.691870E+10 | 0.524250E+10 | 0.167620E+10 | 0.930317E+10 | 0.557361E+10 |
February | 0.587949E+10 | 0.416969E+10 | 0.170980E+10 | 0.807084E+10 | 0.447315E+10 |
March | 0.509227E+10 | 0.288503E+10 | 0.220724E+10 | 0.720993E+10 | 0.434662E+10 |
April | 0.343383E+10 | 0.128902E+10 | 0.214480E+10 | 0.559174E+10 | 0.250076E+10 |
May | 0.251798E+10 | 0.369271E+09 | 0.214871E+10 | 0.466897E+10 | 0.144128E+10 |
June | 0.208423E+10 | 0.131142E+09 | 0.195309E+10 | 0.483444E+10 | 0.632373E+09 |
July | 0.218715E+10 | 0.193914E+09 | 0.199323E+10 | 0.506911E+10 | 0.488592E+09 |
August | 0.276092E+10 | 0.701462E+09 | 0.205946E+10 | 0.591205E+10 | 0.752937E+09 |
September | 0.423121E+10 | 0.219832E+10 | 0.203289E+10 | 0.806130E+10 | 0.155556E+10 |
October | 0.600158E+10 | 0.407753E+10 | 0.192406E+10 | 0.964740E+10 | 0.274504E+10 |
November | 0.699030E+10 | 0.534681E+10 | 0.164349E+10 | 0.985387E+10 | 0.453269E+10 |
December | 0.710291E+10 | 0.533630E+10 | 0.176661E+10 | 0.934133E+10 | 0.595922E+10 |
Annual Sum or Average | 0.552006E+11 | 0.319410E+11 | 0.232596E+11 | 0.875641E+11 | 0.350018E+11 |
Minimum of Months | 0.208423E+10 | 0.131142E+09 | 0.164349E+10 | 0.466897E+10 | 0.488592E+09 |
Maximum of Months | 0.710291E+10 | 0.534681E+10 | 0.220724E+10 | 0.985387E+10 | 0.595922E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.507741E+09 | 0.266349E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.440913E+09 | 0.211471E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.391786E+09 | 0.203876E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.307699E+09 | 0.105505E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.267753E+09 | 51514406.61 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.288968E+09 | 17426584.73 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.301650E+09 | 10183568.87 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.341864E+09 | 20314018.77 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.446598E+09 | 57872508.02 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.529194E+09 | 0.116997E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.539335E+09 | 0.212108E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.513656E+09 | 0.288157E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.487716E+10 | 0.156177E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.267753E+09 | 10183568.87 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.539335E+09 | 0.288157E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.306955E+09 | 0.550118E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.337852E+09 | 0.436052E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.571344E+09 | 0.394911E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.762617E+09 | 0.194700E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.968072E+09 | 95233568.32 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.105763E+10 | 32325466.60 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.985635E+09 | 18423872.51 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.907192E+09 | 37594331.37 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.824439E+09 | 0.109403E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.626085E+09 | 0.229283E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.399598E+09 | 0.438902E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.274846E+09 | 0.605087E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.802227E+10 | 0.314203E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.274846E+09 | 18423872.51 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.105763E+10 | 0.605087E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 12421868.40 | 0.296352E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 29536830.79 | 0.233851E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 65748081.69 | 0.213179E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.128418E+09 | 0.101790E+09 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.224383E+09 | 47562107.32 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.305909E+09 | 16775183.22 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.295095E+09 | 9703668.62 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.232211E+09 | 19343785.47 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.161925E+09 | 57198856.07 |
October | 71778804.06 | 0.00 | 71778804.06 | 88506373.86 | 0.120989E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 23073994.77 | 0.236231E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 8892105.27 | 0.327041E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.157612E+10 | 0.168002E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 8892105.27 | 9703668.62 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.305909E+09 | 0.327041E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.324640E+09 | 0.533154E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.353461E+09 | 0.423861E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.585277E+09 | 0.387586E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.769231E+09 | 0.192404E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.969636E+09 | 94853032.86 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.105723E+10 | 32349550.86 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.985932E+09 | 18361922.52 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.910536E+09 | 36993339.15 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.832012E+09 | 0.106636E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.638757E+09 | 0.222758E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.415927E+09 | 0.425856E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.292178E+09 | 0.587356E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.813481E+10 | 0.306217E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.292178E+09 | 18361922.52 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.105723E+10 | 0.587356E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.299104E+09 | 0.226640E+09 | 72464826.42 | 0.393281E+09 | 0.238915E+09 |
February | 0.254178E+09 | 0.180261E+09 | 73917324.87 | 0.341381E+09 | 0.192079E+09 |
March | 0.220146E+09 | 0.124724E+09 | 95422629.83 | 0.303670E+09 | 0.182619E+09 |
April | 0.148450E+09 | 55726088.50 | 92723544.22 | 0.240119E+09 | 0.100087E+09 |
May | 0.108857E+09 | 15964013.69 | 92892545.85 | 0.208191E+09 | 53205808.91 |
June | 90105188.78 | 5669429.11 | 84435759.67 | 0.223350E+09 | 20874701.66 |
July | 94554156.30 | 8383125.91 | 86171030.39 | 0.231874E+09 | 14970905.08 |
August | 0.119359E+09 | 30325060.49 | 89033931.16 | 0.264859E+09 | 25565559.15 |
September | 0.182921E+09 | 95036114.58 | 87885276.20 | 0.351662E+09 | 60178026.66 |
October | 0.259457E+09 | 0.176276E+09 | 83180150.54 | 0.414509E+09 | 0.113262E+09 |
November | 0.302200E+09 | 0.231149E+09 | 71050625.13 | 0.421086E+09 | 0.192333E+09 |
December | 0.307068E+09 | 0.230695E+09 | 76373138.43 | 0.396914E+09 | 0.255217E+09 |
Annual Sum or Average | 0.238640E+10 | 0.138085E+10 | 0.100555E+10 | 0.379090E+10 | 0.144931E+10 |
Minimum of Months | 90105188.78 | 5669429.11 | 71050625.13 | 0.208191E+09 | 14970905.08 |
Maximum of Months | 0.307068E+09 | 0.231149E+09 | 95422629.83 | 0.421086E+09 | 0.255217E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 43713969.60 | 0.00 | 43713969.60 | 9704887.14 | 0.242102E+09 |
February | 48213648.10 | 0.00 | 48213648.10 | 25149655.52 | 0.189063E+09 |
March | 69870982.94 | 2765.95 | 69868216.99 | 57242008.37 | 0.168837E+09 |
April | 78518344.10 | 1000279.47 | 77518064.63 | 0.113607E+09 | 76890738.99 |
May | 95843144.60 | 7063304.15 | 88779840.45 | 0.194994E+09 | 33815363.02 |
June | 98633813.54 | 12290815.53 | 86342998.01 | 0.262173E+09 | 10763610.52 |
July | 94160895.41 | 9236150.10 | 84924745.31 | 0.253615E+09 | 5540435.89 |
August | 79637162.39 | 1894638.37 | 77742524.03 | 0.202349E+09 | 12371518.69 |
September | 67049393.63 | 84739.01 | 66964654.62 | 0.143021E+09 | 40258526.93 |
October | 57430655.00 | 0.00 | 57430655.00 | 79631418.21 | 91335854.75 |
November | 44867884.08 | 0.00 | 44867884.08 | 21019159.04 | 0.187666E+09 |
December | 43375413.74 | 0.00 | 43375413.74 | 6596807.47 | 0.268970E+09 |
Annual Sum or Average | 0.821315E+09 | 31572692.58 | 0.789743E+09 | 0.136910E+10 | 0.132761E+10 |
Minimum of Months | 43375413.74 | 0.00 | 43375413.74 | 6596807.47 | 5540435.89 |
Maximum of Months | 98633813.54 | 12290815.53 | 88779840.45 | 0.262173E+09 | 0.268970E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272406E+09 | 0.147604E+09 | 0.124803E+09 | 0.256244E+09 | 0.521623E+09 |
February | 0.330219E+09 | 0.188293E+09 | 0.141926E+09 | 0.370504E+09 | 0.405697E+09 |
March | 0.450634E+09 | 0.248122E+09 | 0.202511E+09 | 0.559493E+09 | 0.363758E+09 |
April | 0.525720E+09 | 0.291582E+09 | 0.234138E+09 | 0.803938E+09 | 0.176161E+09 |
May | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.985239E+09 | 86594933.85 |
June | 0.542173E+09 | 0.301473E+09 | 0.240700E+09 | 0.110332E+10 | 30112166.56 |
July | 0.502747E+09 | 0.262839E+09 | 0.239908E+09 | 0.103671E+10 | 17707067.77 |
August | 0.478911E+09 | 0.245239E+09 | 0.233671E+09 | 0.944537E+09 | 35313887.83 |
September | 0.459814E+09 | 0.262571E+09 | 0.197243E+09 | 0.822109E+09 | 99960538.69 |
October | 0.363675E+09 | 0.195894E+09 | 0.167781E+09 | 0.538890E+09 | 0.214731E+09 |
November | 0.315129E+09 | 0.183035E+09 | 0.132093E+09 | 0.347790E+09 | 0.408979E+09 |
December | 0.272612E+09 | 0.144459E+09 | 0.128153E+09 | 0.244865E+09 | 0.572080E+09 |
Annual Sum or Average | 0.507405E+10 | 0.277533E+10 | 0.229871E+10 | 0.801364E+10 | 0.293272E+10 |
Minimum of Months | 0.272406E+09 | 0.144459E+09 | 0.124803E+09 | 0.244865E+09 | 17707067.77 |
Maximum of Months | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.110332E+10 | 0.572080E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.506055E+09 | 0.264789E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.436884E+09 | 0.210999E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.387047E+09 | 0.202598E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.303584E+09 | 0.105246E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.264901E+09 | 50975257.25 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.286783E+09 | 16946456.22 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.299741E+09 | 9792206.14 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.340184E+09 | 19929786.28 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.444813E+09 | 57051968.73 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.527820E+09 | 0.114954E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.537120E+09 | 0.210473E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.511840E+09 | 0.287099E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.484677E+10 | 0.155085E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.264901E+09 | 9792206.14 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.537120E+09 | 0.287099E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 11609827.60 | 0.295466E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 27550196.64 | 0.235157E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 62331413.29 | 0.213639E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.123936E+09 | 0.101963E+09 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.221127E+09 | 46802687.52 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.303941E+09 | 16322502.51 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.293325E+09 | 9352811.58 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.230295E+09 | 18929448.73 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.159823E+09 | 56651205.92 |
October | 71778804.06 | 0.00 | 71778804.06 | 86617353.48 | 0.119400E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 21922540.94 | 0.234593E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 8005493.69 | 0.326969E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.155048E+10 | 0.167525E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 8005493.69 | 9352811.58 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.303941E+09 | 0.326969E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272406E+09 | 0.147604E+09 | 0.124803E+09 | 0.270117E+09 | 0.500126E+09 |
February | 0.330219E+09 | 0.188293E+09 | 0.141926E+09 | 0.384642E+09 | 0.391880E+09 |
March | 0.450634E+09 | 0.248122E+09 | 0.202511E+09 | 0.572053E+09 | 0.355915E+09 |
April | 0.525720E+09 | 0.291582E+09 | 0.234138E+09 | 0.809343E+09 | 0.174015E+09 |
May | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.986592E+09 | 86250809.28 |
June | 0.542173E+09 | 0.301473E+09 | 0.240700E+09 | 0.110318E+10 | 30153063.12 |
July | 0.502747E+09 | 0.262839E+09 | 0.239908E+09 | 0.103718E+10 | 17668027.97 |
August | 0.478911E+09 | 0.245239E+09 | 0.233671E+09 | 0.947686E+09 | 34756074.04 |
September | 0.459814E+09 | 0.262571E+09 | 0.197243E+09 | 0.829086E+09 | 97423093.94 |
October | 0.363675E+09 | 0.195894E+09 | 0.167781E+09 | 0.550277E+09 | 0.208269E+09 |
November | 0.315129E+09 | 0.183035E+09 | 0.132093E+09 | 0.363468E+09 | 0.393143E+09 |
December | 0.272612E+09 | 0.144459E+09 | 0.128153E+09 | 0.256395E+09 | 0.548394E+09 |
Annual Sum or Average | 0.507405E+10 | 0.277533E+10 | 0.229871E+10 | 0.811001E+10 | 0.283799E+10 |
Minimum of Months | 0.272406E+09 | 0.144459E+09 | 0.124803E+09 | 0.256395E+09 | 17668027.97 |
Maximum of Months | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.110318E+10 | 0.548394E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69192058.57 | 0.00 | 69192058.57 | 9565454.92 | 0.420050E+09 |
February | 76314313.11 | 0.00 | 76314313.11 | 30541023.28 | 0.334231E+09 |
March | 0.110594E+09 | 4378.05 | 0.110590E+09 | 75639160.96 | 0.304399E+09 |
April | 0.124282E+09 | 1583278.67 | 0.122698E+09 | 0.153283E+09 | 0.159685E+09 |
May | 0.151704E+09 | 11180054.31 | 0.140524E+09 | 0.266572E+09 | 84990722.68 |
June | 0.156121E+09 | 19454349.17 | 0.136667E+09 | 0.365013E+09 | 35891140.84 |
July | 0.149041E+09 | 14619313.80 | 0.134422E+09 | 0.348611E+09 | 26664166.16 |
August | 0.126053E+09 | 2998902.41 | 0.123054E+09 | 0.271241E+09 | 43820155.46 |
September | 0.106128E+09 | 134127.98 | 0.105994E+09 | 0.190819E+09 | 0.102528E+09 |
October | 90903326.35 | 0.00 | 90903326.35 | 98279750.95 | 0.194289E+09 |
November | 71018516.32 | 0.00 | 71018516.32 | 20523835.28 | 0.348362E+09 |
December | 68656180.07 | 0.00 | 68656180.07 | 6688806.42 | 0.458598E+09 |
Annual Sum or Average | 0.130001E+10 | 49974404.39 | 0.125003E+10 | 0.183678E+10 | 0.251351E+10 |
Minimum of Months | 68656180.07 | 0.00 | 68656180.07 | 6688806.42 | 26664166.16 |
Maximum of Months | 0.156121E+09 | 19454349.17 | 0.140524E+09 | 0.365013E+09 | 0.458598E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25507057.81 | 0.00 | 25507057.81 | 3526222.76 | 0.154848E+09 |
February | 28132615.74 | 0.00 | 28132615.74 | 11258685.79 | 0.123211E+09 |
March | 40769649.09 | 1613.93 | 40768035.16 | 27883726.70 | 0.112214E+09 |
April | 45815375.73 | 583662.08 | 45231713.65 | 56506401.72 | 58866454.03 |
May | 55924379.60 | 4121430.95 | 51802948.65 | 98269390.27 | 31331099.57 |
June | 57552732.16 | 7171678.64 | 50381053.51 | 0.134559E+09 | 13230960.65 |
July | 54942788.87 | 5389284.40 | 49553504.47 | 0.128512E+09 | 9829515.72 |
August | 46468205.09 | 1105519.60 | 45362685.49 | 99990754.53 | 16153923.75 |
September | 39123254.53 | 49445.13 | 39073809.41 | 70343907.66 | 37796099.84 |
October | 33510730.10 | 0.00 | 33510730.10 | 36229985.64 | 71622965.64 |
November | 26180365.76 | 0.00 | 26180365.76 | 7565935.51 | 0.128421E+09 |
December | 25309510.80 | 0.00 | 25309510.80 | 2465771.01 | 0.169058E+09 |
Annual Sum or Average | 0.479237E+09 | 18422634.73 | 0.460814E+09 | 0.677112E+09 | 0.926583E+09 |
Minimum of Months | 25309510.80 | 0.00 | 25309510.80 | 2465771.01 | 9829515.72 |
Maximum of Months | 57552732.16 | 7171678.64 | 51802948.65 | 0.134559E+09 | 0.169058E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174486E+09 | 0.132213E+09 | 42273150.31 | 0.236427E+09 | 0.133435E+09 |
February | 0.148278E+09 | 0.105157E+09 | 43120481.20 | 0.204912E+09 | 0.107509E+09 |
March | 0.128425E+09 | 72758842.37 | 55665836.43 | 0.181827E+09 | 0.104727E+09 |
April | 86599719.45 | 32508424.18 | 54091295.27 | 0.141298E+09 | 59897867.18 |
May | 63502666.49 | 9312782.27 | 54189884.22 | 0.119333E+09 | 33768480.89 |
June | 52563848.94 | 3307323.58 | 49256525.36 | 0.126763E+09 | 13893355.04 |
July | 55159202.88 | 4890388.33 | 50268814.55 | 0.131818E+09 | 10382875.26 |
August | 69629375.31 | 17690456.23 | 51938919.07 | 0.152053E+09 | 16818835.74 |
September | 0.106709E+09 | 55440358.52 | 51268838.62 | 0.204296E+09 | 37278411.91 |
October | 0.151357E+09 | 0.102833E+09 | 48524052.02 | 0.243366E+09 | 66990388.39 |
November | 0.176291E+09 | 0.134843E+09 | 41448160.50 | 0.249633E+09 | 0.110671E+09 |
December | 0.179131E+09 | 0.134578E+09 | 44553106.94 | 0.239043E+09 | 0.142509E+09 |
Annual Sum or Average | 0.139213E+10 | 0.805533E+09 | 0.586599E+09 | 0.223077E+10 | 0.837882E+09 |
Minimum of Months | 52563848.94 | 3307323.58 | 41448160.50 | 0.119333E+09 | 10382875.26 |
Maximum of Months | 0.179131E+09 | 0.134843E+09 | 55665836.43 | 0.249633E+09 | 0.142509E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.473590E+09 | 0.358852E+09 | 0.114738E+09 | 0.641710E+09 | 0.362170E+09 |
February | 0.402456E+09 | 0.285418E+09 | 0.117038E+09 | 0.556172E+09 | 0.291802E+09 |
March | 0.348571E+09 | 0.197482E+09 | 0.151088E+09 | 0.493517E+09 | 0.284250E+09 |
April | 0.235049E+09 | 88234512.68 | 0.146815E+09 | 0.383511E+09 | 0.162575E+09 |
May | 0.172359E+09 | 25276795.96 | 0.147082E+09 | 0.323894E+09 | 91654564.32 |
June | 0.142669E+09 | 8976752.69 | 0.133692E+09 | 0.344061E+09 | 37709407.39 |
July | 0.149713E+09 | 13273514.24 | 0.136440E+09 | 0.357782E+09 | 28181247.22 |
August | 0.188988E+09 | 48015516.72 | 0.140973E+09 | 0.412702E+09 | 45649760.42 |
September | 0.289631E+09 | 0.150476E+09 | 0.139154E+09 | 0.554500E+09 | 0.101181E+09 |
October | 0.410813E+09 | 0.279109E+09 | 0.131704E+09 | 0.660546E+09 | 0.181826E+09 |
November | 0.478491E+09 | 0.365992E+09 | 0.112499E+09 | 0.677555E+09 | 0.300385E+09 |
December | 0.486199E+09 | 0.365273E+09 | 0.120926E+09 | 0.648811E+09 | 0.386798E+09 |
Annual Sum or Average | 0.377853E+10 | 0.218638E+10 | 0.159215E+10 | 0.605476E+10 | 0.227418E+10 |
Minimum of Months | 0.142669E+09 | 8976752.69 | 0.112499E+09 | 0.323894E+09 | 28181247.22 |
Maximum of Months | 0.486199E+09 | 0.365992E+09 | 0.151088E+09 | 0.677555E+09 | 0.386798E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.506036E+09 | 0.262253E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.439328E+09 | 0.207666E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.389768E+09 | 0.200071E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.305938E+09 | 0.102315E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.267565E+09 | 48965892.10 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.289364E+09 | 16221336.17 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.301197E+09 | 9329347.43 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.340751E+09 | 18963078.21 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.443851E+09 | 55634141.39 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.526586E+09 | 0.113699E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.537865E+09 | 0.207668E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.513026E+09 | 0.283932E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.486127E+10 | 0.152672E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.267565E+09 | 9329347.43 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.537865E+09 | 0.283932E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.306041E+09 | 0.540412E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.336628E+09 | 0.427167E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.568204E+09 | 0.386447E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.758314E+09 | 0.188498E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.963343E+09 | 90376873.33 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.105378E+10 | 30214174.68 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.981477E+09 | 16856551.28 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.903255E+09 | 35114544.10 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.819775E+09 | 0.105094E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.623530E+09 | 0.222019E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.398489E+09 | 0.428267E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.275093E+09 | 0.594330E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.798793E+10 | 0.306480E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.275093E+09 | 16856551.28 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.105378E+10 | 0.594330E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 13742770.96 | 0.290437E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 31042023.31 | 0.228480E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 67524240.43 | 0.208189E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.129003E+09 | 98474028.52 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.224727E+09 | 45189351.82 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.305657E+09 | 15702236.74 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.294474E+09 | 8908853.40 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.232250E+09 | 18056047.58 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.161611E+09 | 54847168.69 |
October | 71778804.06 | 0.00 | 71778804.06 | 89847157.74 | 0.116647E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 24971360.77 | 0.229505E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 9991618.04 | 0.320766E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.158484E+10 | 0.163520E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 9991618.04 | 8908853.40 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.305657E+09 | 0.320766E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.325895E+09 | 0.523061E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.354227E+09 | 0.414358E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.583995E+09 | 0.378390E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.765525E+09 | 0.185965E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.965013E+09 | 89980165.84 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.105331E+10 | 30245131.82 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.981760E+09 | 16800496.29 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.906760E+09 | 34491453.24 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.827888E+09 | 0.102115E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.637965E+09 | 0.214455E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.417790E+09 | 0.413497E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.294318E+09 | 0.576676E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.811444E+10 | 0.298003E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.294318E+09 | 16800496.29 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.105331E+10 | 0.576676E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.548441E+09 | 0.415568E+09 | 0.132872E+09 | 0.720569E+09 | 0.403784E+09 |
February | 0.466063E+09 | 0.330528E+09 | 0.135536E+09 | 0.627784E+09 | 0.317924E+09 |
March | 0.403662E+09 | 0.228694E+09 | 0.174968E+09 | 0.561162E+09 | 0.298844E+09 |
April | 0.272199E+09 | 0.102180E+09 | 0.170019E+09 | 0.451546E+09 | 0.147621E+09 |
May | 0.199600E+09 | 29271767.90 | 0.170329E+09 | 0.405650E+09 | 67913909.06 |
June | 0.165218E+09 | 10395519.34 | 0.154822E+09 | 0.442496E+09 | 21139273.72 |
July | 0.173375E+09 | 15371379.69 | 0.158004E+09 | 0.458421E+09 | 11630592.27 |
August | 0.218858E+09 | 55604320.39 | 0.163253E+09 | 0.512087E+09 | 25637620.15 |
September | 0.335406E+09 | 0.174259E+09 | 0.161147E+09 | 0.655344E+09 | 79030791.30 |
October | 0.475742E+09 | 0.323222E+09 | 0.152520E+09 | 0.767294E+09 | 0.169082E+09 |
November | 0.554116E+09 | 0.423837E+09 | 0.130279E+09 | 0.774017E+09 | 0.316754E+09 |
December | 0.563043E+09 | 0.423004E+09 | 0.140039E+09 | 0.728111E+09 | 0.436943E+09 |
Annual Sum or Average | 0.437572E+10 | 0.253194E+10 | 0.184379E+10 | 0.710448E+10 | 0.229630E+10 |
Minimum of Months | 0.165218E+09 | 10395519.34 | 0.130279E+09 | 0.405650E+09 | 11630592.27 |
Maximum of Months | 0.563043E+09 | 0.423837E+09 | 0.174968E+09 | 0.774017E+09 | 0.436943E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382432E+09 | 0.00 | 0.382432E+09 | 41661808.54 | 0.246355E+10 |
February | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.154004E+09 | 0.194960E+10 |
March | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.388310E+09 | 0.178455E+10 |
April | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.830028E+09 | 0.928219E+09 |
May | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.146786E+10 | 0.493323E+09 |
June | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.200698E+10 | 0.218844E+09 |
July | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.191411E+10 | 0.169889E+09 |
August | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.150180E+10 | 0.265407E+09 |
September | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.107719E+10 | 0.572372E+09 |
October | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.556930E+09 | 0.108891E+10 |
November | 0.392527E+09 | 0.00 | 0.392527E+09 | 0.113576E+09 | 0.196912E+10 |
December | 0.379470E+09 | 0.00 | 0.379470E+09 | 29062726.31 | 0.268136E+10 |
Annual Sum or Average | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.100815E+11 | 0.145851E+11 |
Minimum of Months | 0.379470E+09 | 0.00 | 0.379470E+09 | 29062726.31 | 0.169889E+09 |
Maximum of Months | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.200698E+10 | 0.268136E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382432E+09 | 0.00 | 0.382432E+09 | 30903013.88 | 0.257468E+10 |
February | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.135454E+09 | 0.203207E+10 |
March | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.356098E+09 | 0.185600E+10 |
April | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.792637E+09 | 0.963510E+09 |
May | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.142342E+10 | 0.513253E+09 |
June | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.196115E+10 | 0.230532E+09 |
July | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.186761E+10 | 0.182017E+09 |
August | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.145742E+10 | 0.280342E+09 |
September | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.104267E+10 | 0.596488E+09 |
October | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.527825E+09 | 0.113186E+10 |
November | 0.392527E+09 | 0.00 | 0.392527E+09 | 97200265.02 | 0.204852E+10 |
December | 0.379470E+09 | 0.00 | 0.379470E+09 | 21840316.58 | 0.279947E+10 |
Annual Sum or Average | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.971423E+10 | 0.152087E+11 |
Minimum of Months | 0.379470E+09 | 0.00 | 0.379470E+09 | 21840316.58 | 0.182017E+09 |
Maximum of Months | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.196115E+10 | 0.279947E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 6800242.32 | 0.359279E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 25917023.51 | 0.283648E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 62218215.57 | 0.260639E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.139615E+09 | 0.137535E+09 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.241650E+09 | 78742534.01 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.326282E+09 | 38871726.78 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.316583E+09 | 32175785.05 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.254452E+09 | 45137728.11 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.187902E+09 | 83399872.24 |
October | 71778804.06 | 0.00 | 71778804.06 | 98930622.02 | 0.155894E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 21210061.52 | 0.283197E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 5183467.49 | 0.388123E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.168674E+10 | 0.214664E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 5183467.49 | 32175785.05 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.326282E+09 | 0.388123E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.544774E+09 | 0.295186E+09 | 0.249587E+09 | 0.509796E+09 | 0.122095E+10 |
February | 0.660391E+09 | 0.376560E+09 | 0.283831E+09 | 0.759187E+09 | 0.956303E+09 |
March | 0.901204E+09 | 0.496210E+09 | 0.404994E+09 | 0.114718E+10 | 0.878129E+09 |
April | 0.105137E+10 | 0.583122E+09 | 0.468243E+09 | 0.167747E+10 | 0.479207E+09 |
May | 0.111994E+10 | 0.608399E+09 | 0.511536E+09 | 0.204738E+10 | 0.291138E+09 |
June | 0.108427E+10 | 0.602903E+09 | 0.481366E+09 | 0.228394E+10 | 0.145300E+09 |
July | 0.100542E+10 | 0.525641E+09 | 0.479782E+09 | 0.215399E+10 | 0.121804E+09 |
August | 0.957753E+09 | 0.490444E+09 | 0.467309E+09 | 0.198102E+10 | 0.168551E+09 |
September | 0.919563E+09 | 0.525105E+09 | 0.394458E+09 | 0.176316E+10 | 0.298053E+09 |
October | 0.727299E+09 | 0.391760E+09 | 0.335538E+09 | 0.114708E+10 | 0.553093E+09 |
November | 0.630213E+09 | 0.366045E+09 | 0.264168E+09 | 0.718007E+09 | 0.956062E+09 |
December | 0.545185E+09 | 0.288898E+09 | 0.256287E+09 | 0.490549E+09 | 0.131178E+10 |
Annual Sum or Average | 0.101474E+11 | 0.555027E+10 | 0.459710E+10 | 0.166788E+11 | 0.738036E+10 |
Minimum of Months | 0.544774E+09 | 0.288898E+09 | 0.249587E+09 | 0.490549E+09 | 0.121804E+09 |
Maximum of Months | 0.111994E+10 | 0.608399E+09 | 0.511536E+09 | 0.228394E+10 | 0.131178E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.509553E+09 | 0.312079E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.444037E+09 | 0.250133E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.395675E+09 | 0.243169E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.320524E+09 | 0.139322E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.283542E+09 | 82865139.31 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.307877E+09 | 39639236.20 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.322361E+09 | 32890216.07 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.365770E+09 | 46045506.34 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.476308E+09 | 82874209.88 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.548456E+09 | 0.148000E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.548758E+09 | 0.247622E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.515933E+09 | 0.330385E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.503880E+10 | 0.195502E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.283542E+09 | 32890216.07 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.548758E+09 | 0.330385E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69192058.57 | 0.00 | 69192058.57 | 7500575.96 | 0.423834E+09 |
February | 76314313.11 | 0.00 | 76314313.11 | 26496962.82 | 0.338472E+09 |
March | 0.110594E+09 | 4378.05 | 0.110590E+09 | 68106369.76 | 0.310726E+09 |
April | 0.124282E+09 | 1583278.67 | 0.122698E+09 | 0.141381E+09 | 0.167059E+09 |
May | 0.151704E+09 | 11180054.31 | 0.140524E+09 | 0.255393E+09 | 88955912.52 |
June | 0.156121E+09 | 19454349.17 | 0.136667E+09 | 0.353807E+09 | 38767769.72 |
July | 0.149041E+09 | 14619313.80 | 0.134422E+09 | 0.336334E+09 | 29996852.84 |
August | 0.126053E+09 | 2998902.41 | 0.123054E+09 | 0.259977E+09 | 47847435.53 |
September | 0.106128E+09 | 134127.98 | 0.105994E+09 | 0.182344E+09 | 0.106830E+09 |
October | 90903326.35 | 0.00 | 90903326.35 | 90053583.81 | 0.200990E+09 |
November | 71018516.32 | 0.00 | 71018516.32 | 16875369.93 | 0.350515E+09 |
December | 68656180.07 | 0.00 | 68656180.07 | 5551930.38 | 0.461853E+09 |
Annual Sum or Average | 0.130001E+10 | 49974404.39 | 0.125003E+10 | 0.174382E+10 | 0.256585E+10 |
Minimum of Months | 68656180.07 | 0.00 | 68656180.07 | 5551930.38 | 29996852.84 |
Maximum of Months | 0.156121E+09 | 19454349.17 | 0.140524E+09 | 0.353807E+09 | 0.461853E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61906396.97 | 0.00 | 61906396.97 | 6710793.73 | 0.379206E+09 |
February | 68278705.09 | 0.00 | 68278705.09 | 23706933.03 | 0.302832E+09 |
March | 98949165.36 | 3917.06 | 98945248.31 | 60935027.08 | 0.278008E+09 |
April | 0.111195E+09 | 1416565.43 | 0.109779E+09 | 0.126495E+09 | 0.149469E+09 |
May | 0.135730E+09 | 10002836.96 | 0.125727E+09 | 0.228501E+09 | 79589191.98 |
June | 0.139682E+09 | 17405879.91 | 0.122276E+09 | 0.316552E+09 | 34685670.46 |
July | 0.133348E+09 | 13079955.45 | 0.120268E+09 | 0.300919E+09 | 26838297.90 |
August | 0.112780E+09 | 2683129.35 | 0.110097E+09 | 0.232603E+09 | 42809281.86 |
September | 94953316.23 | 120004.81 | 94833311.42 | 0.163144E+09 | 95581113.97 |
October | 81331550.52 | 0.00 | 81331550.52 | 80571282.64 | 0.179827E+09 |
November | 63540535.64 | 0.00 | 63540535.64 | 15098457.41 | 0.313606E+09 |
December | 61426944.44 | 0.00 | 61426944.44 | 4967333.15 | 0.413204E+09 |
Annual Sum or Average | 0.116312E+10 | 44712288.96 | 0.111841E+10 | 0.156020E+10 | 0.229566E+10 |
Minimum of Months | 61426944.44 | 0.00 | 61426944.44 | 4967333.15 | 26838297.90 |
Maximum of Months | 0.139682E+09 | 17405879.91 | 0.125727E+09 | 0.316552E+09 | 0.413204E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139608E+10 | 0.105785E+10 | 0.338233E+09 | 0.186307E+10 | 0.107094E+10 |
February | 0.118639E+10 | 0.841376E+09 | 0.345013E+09 | 0.160991E+10 | 0.869045E+09 |
March | 0.102754E+10 | 0.582153E+09 | 0.445390E+09 | 0.141505E+10 | 0.853657E+09 |
April | 0.692896E+09 | 0.260104E+09 | 0.432792E+09 | 0.108683E+10 | 0.501434E+09 |
May | 0.508093E+09 | 74512840.84 | 0.433581E+09 | 0.920904E+09 | 0.283218E+09 |
June | 0.420571E+09 | 26462346.95 | 0.394108E+09 | 0.983226E+09 | 0.120030E+09 |
July | 0.441336E+09 | 39128663.92 | 0.402208E+09 | 0.101917E+10 | 93741152.14 |
August | 0.557114E+09 | 0.141544E+09 | 0.415570E+09 | 0.118027E+10 | 0.147350E+09 |
September | 0.853795E+09 | 0.443586E+09 | 0.410209E+09 | 0.160183E+10 | 0.311028E+09 |
October | 0.121103E+10 | 0.822779E+09 | 0.388248E+09 | 0.190826E+10 | 0.553585E+09 |
November | 0.141053E+10 | 0.107890E+10 | 0.331632E+09 | 0.196891E+10 | 0.886609E+09 |
December | 0.143326E+10 | 0.107678E+10 | 0.356475E+09 | 0.188730E+10 | 0.114033E+10 |
Annual Sum or Average | 0.111386E+11 | 0.644518E+10 | 0.469346E+10 | 0.174447E+11 | 0.683097E+10 |
Minimum of Months | 0.420571E+09 | 26462346.95 | 0.331632E+09 | 0.920904E+09 | 93741152.14 |
Maximum of Months | 0.143326E+10 | 0.107890E+10 | 0.445390E+09 | 0.196891E+10 | 0.114033E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 936.90 | 526.87 | 706.15 | 535.07 | 171.08 | 0.00 | 0.00 |
February | 899.09 | 470.98 | 664.38 | 471.17 | 193.21 | 0.00 | 0.00 |
March | 722.65 | 414.77 | 519.74 | 294.46 | 225.28 | 0.00 | 0.00 |
April | 570.90 | 253.53 | 362.15 | 135.95 | 226.20 | 0.00 | 0.00 |
May | 454.65 | 145.71 | 257.00 | 37.69 | 219.31 | 0.00 | 0.00 |
June | 484.63 | 68.67 | 219.82 | 13.83 | 205.99 | 0.00 | 0.00 |
July | 493.07 | 52.25 | 223.23 | 19.79 | 203.44 | 0.00 | 0.00 |
August | 579.52 | 78.82 | 281.79 | 71.59 | 210.20 | 0.00 | 0.00 |
September | 827.70 | 166.54 | 446.25 | 231.85 | 214.40 | 0.00 | 0.00 |
October | 965.68 | 273.03 | 612.55 | 416.17 | 196.38 | 0.00 | 0.00 |
November | 1026.16 | 450.35 | 737.24 | 563.91 | 173.33 | 0.00 | 0.00 |
December | 942.51 | 563.25 | 724.95 | 544.65 | 180.31 | 0.00 | 0.00 |
Annual Sum or Average | 740.82 | 287.82 | 478.50 | 276.88 | 201.63 | 0.00 | 0.00 |
Minimum of Months | 454.65 | 52.25 | 219.82 | 13.83 | 171.08 | 0.00 | 0.00 |
Maximum of Months | 1026.16 | 563.25 | 737.24 | 563.91 | 226.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2631.95 | 1514.06 | 1988.48 | 1506.73 | 481.75 | 0.00 | 0.00 |
February | 2528.06 | 1342.97 | 1870.85 | 1326.79 | 544.06 | 0.00 | 0.00 |
March | 2049.72 | 1168.12 | 1463.55 | 829.18 | 634.37 | 0.00 | 0.00 |
April | 1648.81 | 688.96 | 1019.80 | 382.82 | 636.98 | 0.00 | 0.00 |
May | 1346.07 | 384.20 | 723.68 | 106.13 | 617.55 | 0.00 | 0.00 |
June | 1429.59 | 179.07 | 618.99 | 38.95 | 580.04 | 0.00 | 0.00 |
July | 1449.74 | 133.55 | 628.60 | 55.73 | 572.87 | 0.00 | 0.00 |
August | 1679.22 | 208.36 | 793.51 | 201.60 | 591.90 | 0.00 | 0.00 |
September | 2350.75 | 450.04 | 1256.61 | 652.87 | 603.74 | 0.00 | 0.00 |
October | 2729.66 | 753.87 | 1724.89 | 1171.91 | 552.99 | 0.00 | 0.00 |
November | 2877.82 | 1276.61 | 2076.02 | 1587.93 | 488.09 | 0.00 | 0.00 |
December | 2645.50 | 1618.29 | 2041.42 | 1533.69 | 507.73 | 0.00 | 0.00 |
Annual Sum or Average | 2110.91 | 807.23 | 1347.44 | 779.68 | 567.76 | 0.00 | 0.00 |
Minimum of Months | 1346.07 | 133.55 | 618.99 | 38.95 | 481.75 | 0.00 | 0.00 |
Maximum of Months | 2877.82 | 1618.29 | 2076.02 | 1587.93 | 636.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3473.40 | 2080.95 | 2583.15 | 1957.32 | 625.82 | 0.00 | 0.00 |
February | 3336.16 | 1849.02 | 2430.34 | 1723.58 | 706.76 | 0.00 | 0.00 |
March | 2691.88 | 1622.84 | 1901.24 | 1077.15 | 824.09 | 0.00 | 0.00 |
April | 2157.31 | 964.80 | 1324.78 | 497.31 | 827.47 | 0.00 | 0.00 |
May | 1743.19 | 538.11 | 940.11 | 137.87 | 802.24 | 0.00 | 0.00 |
June | 1865.14 | 243.97 | 804.10 | 50.59 | 753.51 | 0.00 | 0.00 |
July | 1892.59 | 182.42 | 816.59 | 72.40 | 744.19 | 0.00 | 0.00 |
August | 2207.31 | 281.11 | 1030.81 | 261.90 | 768.91 | 0.00 | 0.00 |
September | 3110.07 | 600.14 | 1632.41 | 848.12 | 784.29 | 0.00 | 0.00 |
October | 3601.92 | 1024.88 | 2240.73 | 1522.37 | 718.36 | 0.00 | 0.00 |
November | 3801.65 | 1748.72 | 2696.87 | 2062.81 | 634.06 | 0.00 | 0.00 |
December | 3487.65 | 2224.92 | 2651.92 | 1992.35 | 659.58 | 0.00 | 0.00 |
Annual Sum or Average | 2776.64 | 1109.90 | 1750.40 | 1012.84 | 737.56 | 0.00 | 0.00 |
Minimum of Months | 1743.19 | 182.42 | 804.10 | 50.59 | 625.82 | 0.00 | 0.00 |
Maximum of Months | 3801.65 | 2224.92 | 2696.87 | 2062.81 | 827.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 289.82 | 290.48 | 247.02 | 166.33 | 80.69 | 0.00 | 0.00 |
February | 310.95 | 256.70 | 252.26 | 157.31 | 94.95 | 0.00 | 0.00 |
March | 355.14 | 219.11 | 267.73 | 146.67 | 121.05 | 0.00 | 0.00 |
April | 411.95 | 114.84 | 260.91 | 128.99 | 131.92 | 0.00 | 0.00 |
May | 461.33 | 54.71 | 255.11 | 116.78 | 138.32 | 0.00 | 0.00 |
June | 519.52 | 19.19 | 242.25 | 109.47 | 132.78 | 0.00 | 0.00 |
July | 480.55 | 10.61 | 220.68 | 91.63 | 129.05 | 0.00 | 0.00 |
August | 466.30 | 21.57 | 226.65 | 101.24 | 125.41 | 0.00 | 0.00 |
September | 490.15 | 64.32 | 263.72 | 143.81 | 119.91 | 0.00 | 0.00 |
October | 429.15 | 127.10 | 272.32 | 170.80 | 101.51 | 0.00 | 0.00 |
November | 351.71 | 240.63 | 271.93 | 188.26 | 83.67 | 0.00 | 0.00 |
December | 276.75 | 315.86 | 245.09 | 162.93 | 82.16 | 0.00 | 0.00 |
Annual Sum or Average | 403.94 | 144.06 | 252.05 | 140.19 | 111.87 | 0.00 | 0.00 |
Minimum of Months | 276.75 | 10.61 | 220.68 | 91.63 | 80.69 | 0.00 | 0.00 |
Maximum of Months | 519.52 | 315.86 | 272.32 | 188.26 | 138.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 121.69 | 305.55 | 127.80 | 60.54 | 67.26 | 0.00 | 0.00 |
February | 155.19 | 268.75 | 145.81 | 64.15 | 81.66 | 0.00 | 0.00 |
March | 240.83 | 222.06 | 197.57 | 88.46 | 109.11 | 0.00 | 0.00 |
April | 345.65 | 112.83 | 227.17 | 102.60 | 124.57 | 0.00 | 0.00 |
May | 445.08 | 52.45 | 249.02 | 112.63 | 136.39 | 0.00 | 0.00 |
June | 525.60 | 18.66 | 246.35 | 112.66 | 133.68 | 0.00 | 0.00 |
July | 478.10 | 10.30 | 220.48 | 92.03 | 128.45 | 0.00 | 0.00 |
August | 426.49 | 20.87 | 208.10 | 87.97 | 120.13 | 0.00 | 0.00 |
September | 383.42 | 63.17 | 207.82 | 98.01 | 109.81 | 0.00 | 0.00 |
October | 270.96 | 127.77 | 178.00 | 88.52 | 89.48 | 0.00 | 0.00 |
November | 166.21 | 252.28 | 147.80 | 76.76 | 71.03 | 0.00 | 0.00 |
December | 107.54 | 336.53 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Annual Sum or Average | 306.25 | 148.70 | 190.00 | 86.70 | 103.30 | 0.00 | 0.00 |
Minimum of Months | 107.54 | 10.30 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Maximum of Months | 525.60 | 336.53 | 249.02 | 112.66 | 136.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 146.83 | 89.20 | 111.67 | 84.62 | 27.06 | 0.00 | 0.00 |
February | 141.11 | 79.40 | 105.07 | 74.51 | 30.55 | 0.00 | 0.00 |
March | 113.38 | 68.18 | 82.19 | 46.57 | 35.63 | 0.00 | 0.00 |
April | 92.64 | 38.61 | 57.27 | 21.50 | 35.77 | 0.00 | 0.00 |
May | 77.73 | 19.86 | 40.64 | 5.96 | 34.68 | 0.00 | 0.00 |
June | 86.17 | 8.05 | 34.76 | 2.19 | 32.58 | 0.00 | 0.00 |
July | 86.57 | 5.59 | 35.30 | 3.13 | 32.17 | 0.00 | 0.00 |
August | 98.89 | 9.55 | 44.56 | 11.32 | 33.24 | 0.00 | 0.00 |
September | 135.67 | 23.22 | 70.57 | 36.67 | 33.91 | 0.00 | 0.00 |
October | 154.76 | 42.29 | 96.87 | 65.81 | 31.06 | 0.00 | 0.00 |
November | 162.46 | 74.20 | 116.59 | 89.18 | 27.41 | 0.00 | 0.00 |
December | 148.19 | 95.29 | 114.65 | 86.13 | 28.51 | 0.00 | 0.00 |
Annual Sum or Average | 120.21 | 45.96 | 75.67 | 43.79 | 31.89 | 0.00 | 0.00 |
Minimum of Months | 77.73 | 5.59 | 34.76 | 2.19 | 27.06 | 0.00 | 0.00 |
Maximum of Months | 162.46 | 95.29 | 116.59 | 89.18 | 35.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.62 | 90.39 | 16.32 | 0.00 | 16.32 | 0.00 | 0.00 |
February | 10.40 | 78.15 | 19.93 | 0.00 | 19.93 | 0.00 | 0.00 |
March | 21.37 | 63.04 | 26.09 | 0.00 | 26.09 | 0.00 | 0.00 |
April | 43.83 | 29.66 | 30.29 | 0.39 | 29.91 | 0.00 | 0.00 |
May | 72.80 | 12.63 | 35.78 | 2.64 | 33.15 | 0.00 | 0.00 |
June | 101.15 | 4.15 | 38.05 | 4.74 | 33.31 | 0.00 | 0.00 |
July | 94.69 | 2.07 | 35.16 | 3.45 | 31.71 | 0.00 | 0.00 |
August | 75.55 | 4.62 | 29.73 | 0.71 | 29.03 | 0.00 | 0.00 |
September | 55.18 | 15.53 | 25.87 | 0.03 | 25.84 | 0.00 | 0.00 |
October | 29.73 | 34.10 | 21.44 | 0.00 | 21.44 | 0.00 | 0.00 |
November | 8.11 | 72.40 | 17.31 | 0.00 | 17.31 | 0.00 | 0.00 |
December | 2.46 | 100.42 | 16.19 | 0.00 | 16.19 | 0.00 | 0.00 |
Annual Sum or Average | 43.41 | 42.10 | 26.04 | 1.00 | 25.04 | 0.00 | 0.00 |
Minimum of Months | 2.46 | 2.07 | 16.19 | 0.00 | 16.19 | 0.00 | 0.00 |
Maximum of Months | 101.15 | 100.42 | 38.05 | 4.74 | 33.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 276.12 | 285.12 | 241.32 | 160.90 | 80.42 | 0.00 | 0.00 |
February | 328.20 | 249.37 | 267.86 | 170.99 | 96.87 | 0.00 | 0.00 |
March | 348.61 | 206.66 | 271.01 | 150.86 | 120.15 | 0.00 | 0.00 |
April | 423.15 | 104.44 | 274.43 | 139.37 | 135.06 | 0.00 | 0.00 |
May | 465.00 | 49.61 | 259.90 | 121.04 | 138.86 | 0.00 | 0.00 |
June | 536.01 | 17.86 | 252.63 | 119.04 | 133.59 | 0.00 | 0.00 |
July | 498.85 | 10.14 | 231.84 | 102.05 | 129.80 | 0.00 | 0.00 |
August | 479.28 | 20.25 | 234.52 | 105.72 | 128.80 | 0.00 | 0.00 |
September | 487.40 | 59.19 | 265.63 | 147.14 | 118.49 | 0.00 | 0.00 |
October | 397.34 | 122.16 | 256.89 | 155.42 | 101.47 | 0.00 | 0.00 |
November | 335.98 | 233.56 | 267.34 | 182.11 | 85.23 | 0.00 | 0.00 |
December | 271.20 | 309.46 | 245.12 | 161.62 | 83.50 | 0.00 | 0.00 |
Annual Sum or Average | 404.09 | 138.46 | 255.51 | 142.75 | 112.76 | 0.00 | 0.00 |
Minimum of Months | 271.20 | 10.14 | 231.84 | 102.05 | 80.42 | 0.00 | 0.00 |
Maximum of Months | 536.01 | 309.46 | 274.43 | 182.11 | 138.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 95.91 | 287.77 | 122.10 | 55.11 | 66.99 | 0.00 | 0.00 |
February | 160.41 | 249.22 | 161.41 | 77.83 | 83.58 | 0.00 | 0.00 |
March | 229.00 | 204.80 | 200.85 | 92.64 | 108.21 | 0.00 | 0.00 |
April | 356.60 | 103.02 | 240.68 | 112.98 | 127.71 | 0.00 | 0.00 |
May | 450.57 | 49.33 | 253.81 | 116.88 | 136.93 | 0.00 | 0.00 |
June | 542.85 | 17.91 | 256.73 | 122.24 | 134.50 | 0.00 | 0.00 |
July | 496.70 | 10.04 | 231.64 | 102.44 | 129.20 | 0.00 | 0.00 |
August | 439.71 | 19.95 | 215.97 | 92.45 | 123.52 | 0.00 | 0.00 |
September | 379.86 | 57.78 | 209.73 | 101.34 | 108.39 | 0.00 | 0.00 |
October | 234.93 | 119.47 | 162.58 | 73.14 | 89.44 | 0.00 | 0.00 |
November | 140.23 | 233.73 | 143.21 | 70.62 | 72.60 | 0.00 | 0.00 |
December | 87.57 | 315.68 | 122.02 | 53.93 | 68.09 | 0.00 | 0.00 |
Annual Sum or Average | 301.77 | 138.55 | 193.45 | 89.26 | 104.19 | 0.00 | 0.00 |
Minimum of Months | 87.57 | 10.04 | 122.02 | 53.93 | 66.99 | 0.00 | 0.00 |
Maximum of Months | 542.85 | 315.68 | 256.73 | 122.24 | 136.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 309.39 | 376.33 | 277.32 | 183.34 | 93.98 | 0.00 | 0.00 |
February | 315.08 | 337.35 | 270.83 | 161.45 | 109.38 | 0.00 | 0.00 |
March | 285.32 | 295.30 | 234.60 | 100.90 | 133.70 | 0.00 | 0.00 |
April | 282.91 | 169.64 | 189.72 | 47.42 | 142.30 | 0.00 | 0.00 |
May | 300.63 | 89.19 | 165.58 | 18.63 | 146.95 | 0.00 | 0.00 |
June | 373.76 | 38.24 | 157.76 | 15.01 | 142.75 | 0.00 | 0.00 |
July | 360.37 | 27.47 | 152.65 | 14.25 | 138.40 | 0.00 | 0.00 |
August | 349.15 | 45.40 | 160.97 | 26.06 | 134.90 | 0.00 | 0.00 |
September | 393.16 | 107.22 | 208.95 | 79.51 | 129.43 | 0.00 | 0.00 |
October | 384.08 | 188.56 | 256.34 | 142.60 | 113.74 | 0.00 | 0.00 |
November | 350.47 | 324.45 | 290.12 | 193.22 | 96.89 | 0.00 | 0.00 |
December | 305.43 | 402.49 | 283.49 | 186.62 | 96.87 | 0.00 | 0.00 |
Annual Sum or Average | 334.13 | 199.45 | 220.38 | 97.04 | 123.34 | 0.00 | 0.00 |
Minimum of Months | 282.91 | 27.47 | 152.65 | 14.25 | 93.98 | 0.00 | 0.00 |
Maximum of Months | 393.16 | 402.49 | 290.12 | 193.22 | 146.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 289.53 | 286.01 | 247.02 | 166.33 | 80.69 | 0.00 | 0.00 |
February | 310.33 | 251.99 | 252.26 | 157.31 | 94.95 | 0.00 | 0.00 |
March | 353.44 | 214.75 | 267.73 | 146.67 | 121.05 | 0.00 | 0.00 |
April | 409.64 | 111.25 | 260.91 | 128.99 | 131.92 | 0.00 | 0.00 |
May | 459.49 | 51.95 | 255.11 | 116.78 | 138.32 | 0.00 | 0.00 |
June | 518.19 | 17.91 | 242.25 | 109.47 | 132.78 | 0.00 | 0.00 |
July | 478.83 | 9.71 | 220.68 | 91.63 | 129.05 | 0.00 | 0.00 |
August | 464.41 | 20.14 | 226.65 | 101.24 | 125.41 | 0.00 | 0.00 |
September | 487.32 | 61.82 | 263.72 | 143.81 | 119.91 | 0.00 | 0.00 |
October | 427.46 | 123.40 | 272.32 | 170.80 | 101.51 | 0.00 | 0.00 |
November | 351.35 | 235.45 | 271.93 | 188.26 | 83.67 | 0.00 | 0.00 |
December | 277.43 | 311.09 | 245.09 | 162.93 | 82.16 | 0.00 | 0.00 |
Annual Sum or Average | 402.61 | 140.76 | 252.05 | 140.19 | 111.87 | 0.00 | 0.00 |
Minimum of Months | 277.43 | 9.71 | 220.68 | 91.63 | 80.69 | 0.00 | 0.00 |
Maximum of Months | 518.19 | 311.09 | 272.32 | 188.26 | 138.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 122.96 | 299.88 | 127.80 | 60.54 | 67.26 | 0.00 | 0.00 |
February | 156.33 | 262.80 | 145.81 | 64.15 | 81.66 | 0.00 | 0.00 |
March | 241.11 | 216.86 | 197.57 | 88.46 | 109.11 | 0.00 | 0.00 |
April | 344.45 | 109.07 | 227.17 | 102.60 | 124.57 | 0.00 | 0.00 |
May | 443.51 | 49.78 | 249.02 | 112.63 | 136.39 | 0.00 | 0.00 |
June | 524.02 | 17.46 | 246.35 | 112.66 | 133.68 | 0.00 | 0.00 |
July | 476.33 | 9.44 | 220.48 | 92.03 | 128.45 | 0.00 | 0.00 |
August | 425.11 | 19.47 | 208.10 | 87.97 | 120.13 | 0.00 | 0.00 |
September | 381.71 | 60.52 | 207.82 | 98.01 | 109.81 | 0.00 | 0.00 |
October | 271.18 | 123.07 | 178.00 | 88.52 | 89.48 | 0.00 | 0.00 |
November | 167.90 | 245.15 | 147.80 | 76.76 | 71.03 | 0.00 | 0.00 |
December | 109.16 | 330.61 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Annual Sum or Average | 306.00 | 144.79 | 190.00 | 86.70 | 103.30 | 0.00 | 0.00 |
Minimum of Months | 109.16 | 9.44 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Maximum of Months | 524.02 | 330.61 | 249.02 | 112.66 | 136.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 269.03 | 150.76 | 204.76 | 155.16 | 49.61 | 0.00 | 0.00 |
February | 259.50 | 131.42 | 192.65 | 136.63 | 56.02 | 0.00 | 0.00 |
March | 209.51 | 111.58 | 150.71 | 85.38 | 65.33 | 0.00 | 0.00 |
April | 174.21 | 56.95 | 105.01 | 39.42 | 65.59 | 0.00 | 0.00 |
May | 151.45 | 25.36 | 74.52 | 10.93 | 63.59 | 0.00 | 0.00 |
June | 170.72 | 8.16 | 63.74 | 4.01 | 59.73 | 0.00 | 0.00 |
July | 171.15 | 4.34 | 64.73 | 5.74 | 58.99 | 0.00 | 0.00 |
August | 191.19 | 9.57 | 81.71 | 20.76 | 60.95 | 0.00 | 0.00 |
September | 252.83 | 30.49 | 129.40 | 67.23 | 62.17 | 0.00 | 0.00 |
October | 286.47 | 63.13 | 177.62 | 120.68 | 56.94 | 0.00 | 0.00 |
November | 298.62 | 122.20 | 213.78 | 163.52 | 50.26 | 0.00 | 0.00 |
December | 271.85 | 163.14 | 210.22 | 157.93 | 52.28 | 0.00 | 0.00 |
Annual Sum or Average | 225.28 | 72.82 | 138.75 | 80.29 | 58.47 | 0.00 | 0.00 |
Minimum of Months | 151.45 | 4.34 | 63.74 | 4.01 | 49.61 | 0.00 | 0.00 |
Maximum of Months | 298.62 | 163.14 | 213.78 | 163.52 | 65.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 15.55 | 919.78 | 142.78 | 0.00 | 142.78 | 0.00 | 0.00 |
February | 63.66 | 805.89 | 174.35 | 0.00 | 174.35 | 0.00 | 0.00 |
March | 144.98 | 666.27 | 228.22 | 0.01 | 228.21 | 0.00 | 0.00 |
April | 320.23 | 358.11 | 265.01 | 3.38 | 261.64 | 0.00 | 0.00 |
May | 548.04 | 184.19 | 313.05 | 23.07 | 289.98 | 0.00 | 0.00 |
June | 774.30 | 84.43 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
July | 714.65 | 63.43 | 307.56 | 30.17 | 277.39 | 0.00 | 0.00 |
August | 560.71 | 99.09 | 260.12 | 6.19 | 253.93 | 0.00 | 0.00 |
September | 415.58 | 220.82 | 226.30 | 0.29 | 226.02 | 0.00 | 0.00 |
October | 207.93 | 406.55 | 187.59 | 0.00 | 187.59 | 0.00 | 0.00 |
November | 43.82 | 759.69 | 151.44 | 0.00 | 151.44 | 0.00 | 0.00 |
December | 10.85 | 1001.11 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Annual Sum or Average | 319.68 | 462.49 | 227.84 | 8.76 | 219.09 | 0.00 | 0.00 |
Minimum of Months | 10.85 | 63.43 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Maximum of Months | 774.30 | 1001.11 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11.54 | 961.27 | 142.78 | 0.00 | 142.78 | 0.00 | 0.00 |
February | 55.99 | 839.97 | 174.35 | 0.00 | 174.35 | 0.00 | 0.00 |
March | 132.95 | 692.95 | 228.22 | 0.01 | 228.21 | 0.00 | 0.00 |
April | 305.80 | 371.72 | 265.01 | 3.38 | 261.64 | 0.00 | 0.00 |
May | 531.44 | 191.63 | 313.05 | 23.07 | 289.98 | 0.00 | 0.00 |
June | 756.62 | 88.94 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
July | 697.28 | 67.96 | 307.56 | 30.17 | 277.39 | 0.00 | 0.00 |
August | 544.14 | 104.67 | 260.12 | 6.19 | 253.93 | 0.00 | 0.00 |
September | 402.26 | 230.13 | 226.30 | 0.29 | 226.02 | 0.00 | 0.00 |
October | 197.07 | 422.59 | 187.59 | 0.00 | 187.59 | 0.00 | 0.00 |
November | 37.50 | 790.32 | 151.44 | 0.00 | 151.44 | 0.00 | 0.00 |
December | 8.15 | 1045.20 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Annual Sum or Average | 308.04 | 482.27 | 227.84 | 8.76 | 219.09 | 0.00 | 0.00 |
Minimum of Months | 8.15 | 67.96 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Maximum of Months | 756.62 | 1045.20 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 353.43 | 676.82 | 363.41 | 216.00 | 147.41 | 0.00 | 0.00 |
February | 486.22 | 594.08 | 429.25 | 248.81 | 180.43 | 0.00 | 0.00 |
March | 584.65 | 501.34 | 471.84 | 243.48 | 228.35 | 0.00 | 0.00 |
April | 817.08 | 284.07 | 515.08 | 252.33 | 262.75 | 0.00 | 0.00 |
May | 958.04 | 166.59 | 513.67 | 237.90 | 275.77 | 0.00 | 0.00 |
June | 1125.40 | 85.94 | 509.34 | 241.26 | 268.07 | 0.00 | 0.00 |
July | 1042.54 | 69.55 | 463.46 | 204.47 | 258.98 | 0.00 | 0.00 |
August | 970.63 | 96.41 | 450.46 | 198.15 | 252.31 | 0.00 | 0.00 |
September | 933.76 | 176.41 | 475.33 | 248.47 | 226.86 | 0.00 | 0.00 |
October | 665.98 | 315.97 | 419.45 | 228.55 | 190.90 | 0.00 | 0.00 |
November | 478.40 | 555.13 | 410.54 | 252.72 | 157.82 | 0.00 | 0.00 |
December | 339.46 | 719.77 | 367.13 | 215.55 | 151.58 | 0.00 | 0.00 |
Annual Sum or Average | 730.44 | 352.39 | 448.93 | 231.99 | 216.94 | 0.00 | 0.00 |
Minimum of Months | 339.46 | 69.55 | 363.41 | 198.15 | 147.41 | 0.00 | 0.00 |
Maximum of Months | 1125.40 | 719.77 | 515.08 | 252.72 | 275.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 665.63 | 664.40 | 570.18 | 394.96 | 175.23 | 0.00 | 0.00 |
February | 660.72 | 598.81 | 550.17 | 347.79 | 202.38 | 0.00 | 0.00 |
March | 567.72 | 529.75 | 461.88 | 217.35 | 244.52 | 0.00 | 0.00 |
April | 521.84 | 314.76 | 358.17 | 101.51 | 256.66 | 0.00 | 0.00 |
May | 522.61 | 166.79 | 297.02 | 35.73 | 261.29 | 0.00 | 0.00 |
June | 636.67 | 73.36 | 276.38 | 24.43 | 251.95 | 0.00 | 0.00 |
July | 617.31 | 55.09 | 270.21 | 24.95 | 245.26 | 0.00 | 0.00 |
August | 623.96 | 88.25 | 297.17 | 54.97 | 242.20 | 0.00 | 0.00 |
September | 750.74 | 197.55 | 406.97 | 171.23 | 235.74 | 0.00 | 0.00 |
October | 770.41 | 343.11 | 516.45 | 307.19 | 209.26 | 0.00 | 0.00 |
November | 744.55 | 570.88 | 596.10 | 416.24 | 179.86 | 0.00 | 0.00 |
December | 664.23 | 708.12 | 583.68 | 402.02 | 181.66 | 0.00 | 0.00 |
Annual Sum or Average | 645.21 | 358.04 | 431.31 | 207.38 | 223.93 | 0.00 | 0.00 |
Minimum of Months | 521.84 | 55.09 | 270.21 | 24.43 | 175.23 | 0.00 | 0.00 |
Maximum of Months | 770.41 | 708.12 | 596.10 | 416.24 | 261.29 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.250939E+10 | 0.141116E+10 | 0.189136E+10 | 0.143314E+10 | 0.458222E+09 | 0.00 | 0.00 |
February | 0.217508E+10 | 0.113939E+10 | 0.160727E+10 | 0.113986E+10 | 0.467406E+09 | 0.00 | 0.00 |
March | 0.193554E+10 | 0.111093E+10 | 0.139207E+10 | 0.788679E+09 | 0.603391E+09 | 0.00 | 0.00 |
April | 0.147978E+10 | 0.657155E+09 | 0.938702E+09 | 0.352379E+09 | 0.586322E+09 | 0.00 | 0.00 |
May | 0.121775E+10 | 0.390267E+09 | 0.688337E+09 | 0.100947E+09 | 0.587390E+09 | 0.00 | 0.00 |
June | 0.125617E+10 | 0.177994E+09 | 0.569764E+09 | 35850177.24 | 0.533914E+09 | 0.00 | 0.00 |
July | 0.132064E+10 | 0.139959E+09 | 0.597898E+09 | 53010019.83 | 0.544888E+09 | 0.00 | 0.00 |
August | 0.155219E+10 | 0.211114E+09 | 0.754750E+09 | 0.191758E+09 | 0.562992E+09 | 0.00 | 0.00 |
September | 0.214540E+10 | 0.431669E+09 | 0.115668E+10 | 0.600953E+09 | 0.555729E+09 | 0.00 | 0.00 |
October | 0.258648E+10 | 0.731275E+09 | 0.164065E+10 | 0.111467E+10 | 0.525978E+09 | 0.00 | 0.00 |
November | 0.265980E+10 | 0.116730E+10 | 0.191093E+10 | 0.146165E+10 | 0.449279E+09 | 0.00 | 0.00 |
December | 0.252443E+10 | 0.150861E+10 | 0.194172E+10 | 0.145878E+10 | 0.482936E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.233626E+11 | 0.907682E+10 | 0.150901E+11 | 0.873168E+10 | 0.635845E+10 | 0.00 | 0.00 |
Minimum of Months | 0.121775E+10 | 0.139959E+09 | 0.569764E+09 | 35850177.24 | 0.449279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.265980E+10 | 0.150861E+10 | 0.194172E+10 | 0.146165E+10 | 0.603391E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.704941E+10 | 0.405525E+10 | 0.532594E+10 | 0.403562E+10 | 0.129032E+10 | 0.00 | 0.00 |
February | 0.611588E+10 | 0.324890E+10 | 0.452597E+10 | 0.320978E+10 | 0.131618E+10 | 0.00 | 0.00 |
March | 0.548997E+10 | 0.312870E+10 | 0.391998E+10 | 0.222087E+10 | 0.169911E+10 | 0.00 | 0.00 |
April | 0.427372E+10 | 0.178579E+10 | 0.264332E+10 | 0.992277E+09 | 0.165105E+10 | 0.00 | 0.00 |
May | 0.360530E+10 | 0.102903E+10 | 0.193831E+10 | 0.284261E+09 | 0.165405E+10 | 0.00 | 0.00 |
June | 0.370550E+10 | 0.464145E+09 | 0.160442E+10 | 0.100952E+09 | 0.150347E+10 | 0.00 | 0.00 |
July | 0.388299E+10 | 0.357712E+09 | 0.168364E+10 | 0.149273E+09 | 0.153437E+10 | 0.00 | 0.00 |
August | 0.449762E+10 | 0.558074E+09 | 0.212533E+10 | 0.539978E+09 | 0.158535E+10 | 0.00 | 0.00 |
September | 0.609315E+10 | 0.116649E+10 | 0.325714E+10 | 0.169224E+10 | 0.156490E+10 | 0.00 | 0.00 |
October | 0.731112E+10 | 0.201917E+10 | 0.461996E+10 | 0.313884E+10 | 0.148112E+10 | 0.00 | 0.00 |
November | 0.745931E+10 | 0.330898E+10 | 0.538106E+10 | 0.411592E+10 | 0.126514E+10 | 0.00 | 0.00 |
December | 0.708571E+10 | 0.433442E+10 | 0.546774E+10 | 0.410783E+10 | 0.135992E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.665697E+11 | 0.254567E+11 | 0.424928E+11 | 0.245878E+11 | 0.179050E+11 | 0.00 | 0.00 |
Minimum of Months | 0.360530E+10 | 0.357712E+09 | 0.160442E+10 | 0.100952E+09 | 0.126514E+10 | 0.00 | 0.00 |
Maximum of Months | 0.745931E+10 | 0.433442E+10 | 0.546774E+10 | 0.411592E+10 | 0.169911E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.930317E+10 | 0.557361E+10 | 0.691870E+10 | 0.524250E+10 | 0.167620E+10 | 0.00 | 0.00 |
February | 0.807084E+10 | 0.447315E+10 | 0.587949E+10 | 0.416969E+10 | 0.170980E+10 | 0.00 | 0.00 |
March | 0.720993E+10 | 0.434662E+10 | 0.509227E+10 | 0.288503E+10 | 0.220724E+10 | 0.00 | 0.00 |
April | 0.559174E+10 | 0.250076E+10 | 0.343383E+10 | 0.128902E+10 | 0.214480E+10 | 0.00 | 0.00 |
May | 0.466897E+10 | 0.144128E+10 | 0.251798E+10 | 0.369271E+09 | 0.214871E+10 | 0.00 | 0.00 |
June | 0.483444E+10 | 0.632373E+09 | 0.208423E+10 | 0.131142E+09 | 0.195309E+10 | 0.00 | 0.00 |
July | 0.506911E+10 | 0.488592E+09 | 0.218715E+10 | 0.193914E+09 | 0.199323E+10 | 0.00 | 0.00 |
August | 0.591205E+10 | 0.752937E+09 | 0.276092E+10 | 0.701462E+09 | 0.205946E+10 | 0.00 | 0.00 |
September | 0.806130E+10 | 0.155556E+10 | 0.423121E+10 | 0.219832E+10 | 0.203289E+10 | 0.00 | 0.00 |
October | 0.964740E+10 | 0.274504E+10 | 0.600158E+10 | 0.407753E+10 | 0.192406E+10 | 0.00 | 0.00 |
November | 0.985387E+10 | 0.453269E+10 | 0.699030E+10 | 0.534681E+10 | 0.164349E+10 | 0.00 | 0.00 |
December | 0.934133E+10 | 0.595922E+10 | 0.710291E+10 | 0.533630E+10 | 0.176661E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.875641E+11 | 0.350018E+11 | 0.552006E+11 | 0.319410E+11 | 0.232596E+11 | 0.00 | 0.00 |
Minimum of Months | 0.466897E+10 | 0.488592E+09 | 0.208423E+10 | 0.131142E+09 | 0.164349E+10 | 0.00 | 0.00 |
Maximum of Months | 0.985387E+10 | 0.595922E+10 | 0.710291E+10 | 0.534681E+10 | 0.220724E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.776259E+09 | 0.778030E+09 | 0.661628E+09 | 0.445502E+09 | 0.216126E+09 | 0.00 | 0.00 |
February | 0.752251E+09 | 0.621010E+09 | 0.610259E+09 | 0.380562E+09 | 0.229697E+09 | 0.00 | 0.00 |
March | 0.951207E+09 | 0.586863E+09 | 0.717083E+09 | 0.392853E+09 | 0.324229E+09 | 0.00 | 0.00 |
April | 0.106778E+10 | 0.297671E+09 | 0.676285E+09 | 0.334351E+09 | 0.341935E+09 | 0.00 | 0.00 |
May | 0.123562E+10 | 0.146544E+09 | 0.683278E+09 | 0.312791E+09 | 0.370487E+09 | 0.00 | 0.00 |
June | 0.134660E+10 | 49748918.05 | 0.627908E+09 | 0.283748E+09 | 0.344161E+09 | 0.00 | 0.00 |
July | 0.128711E+10 | 28430516.15 | 0.591061E+09 | 0.245426E+09 | 0.345635E+09 | 0.00 | 0.00 |
August | 0.124893E+10 | 57782774.39 | 0.607067E+09 | 0.271168E+09 | 0.335899E+09 | 0.00 | 0.00 |
September | 0.127048E+10 | 0.166714E+09 | 0.683569E+09 | 0.372750E+09 | 0.310819E+09 | 0.00 | 0.00 |
October | 0.114943E+10 | 0.340432E+09 | 0.729374E+09 | 0.457483E+09 | 0.271891E+09 | 0.00 | 0.00 |
November | 0.911627E+09 | 0.623704E+09 | 0.704840E+09 | 0.487965E+09 | 0.216875E+09 | 0.00 | 0.00 |
December | 0.741250E+09 | 0.845993E+09 | 0.656450E+09 | 0.436397E+09 | 0.220053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127385E+11 | 0.454292E+10 | 0.794880E+10 | 0.442100E+10 | 0.352781E+10 | 0.00 | 0.00 |
Minimum of Months | 0.741250E+09 | 28430516.15 | 0.591061E+09 | 0.245426E+09 | 0.216126E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134660E+10 | 0.845993E+09 | 0.729374E+09 | 0.487965E+09 | 0.370487E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.325933E+09 | 0.818377E+09 | 0.342309E+09 | 0.162146E+09 | 0.180162E+09 | 0.00 | 0.00 |
February | 0.375434E+09 | 0.650148E+09 | 0.352733E+09 | 0.155192E+09 | 0.197541E+09 | 0.00 | 0.00 |
March | 0.645038E+09 | 0.594778E+09 | 0.529172E+09 | 0.236921E+09 | 0.292251E+09 | 0.00 | 0.00 |
April | 0.895915E+09 | 0.292461E+09 | 0.588821E+09 | 0.265930E+09 | 0.322892E+09 | 0.00 | 0.00 |
May | 0.119209E+10 | 0.140485E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
June | 0.136237E+10 | 48355265.45 | 0.638530E+09 | 0.292021E+09 | 0.346509E+09 | 0.00 | 0.00 |
July | 0.128054E+10 | 27579189.67 | 0.590530E+09 | 0.246488E+09 | 0.344041E+09 | 0.00 | 0.00 |
August | 0.114231E+10 | 55904784.10 | 0.557372E+09 | 0.235622E+09 | 0.321750E+09 | 0.00 | 0.00 |
September | 0.993830E+09 | 0.163728E+09 | 0.538673E+09 | 0.254037E+09 | 0.284635E+09 | 0.00 | 0.00 |
October | 0.725734E+09 | 0.342219E+09 | 0.476768E+09 | 0.237094E+09 | 0.239674E+09 | 0.00 | 0.00 |
November | 0.430813E+09 | 0.653899E+09 | 0.383093E+09 | 0.198972E+09 | 0.184121E+09 | 0.00 | 0.00 |
December | 0.288045E+09 | 0.901373E+09 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.965806E+10 | 0.468931E+10 | 0.599172E+10 | 0.273405E+10 | 0.325767E+10 | 0.00 | 0.00 |
Minimum of Months | 0.288045E+09 | 27579189.67 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Maximum of Months | 0.136237E+10 | 0.901373E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.393281E+09 | 0.238915E+09 | 0.299104E+09 | 0.226640E+09 | 72464826.42 | 0.00 | 0.00 |
February | 0.341381E+09 | 0.192079E+09 | 0.254178E+09 | 0.180261E+09 | 73917324.87 | 0.00 | 0.00 |
March | 0.303670E+09 | 0.182619E+09 | 0.220146E+09 | 0.124724E+09 | 95422629.83 | 0.00 | 0.00 |
April | 0.240119E+09 | 0.100087E+09 | 0.148450E+09 | 55726088.50 | 92723544.22 | 0.00 | 0.00 |
May | 0.208191E+09 | 53205808.91 | 0.108857E+09 | 15964013.69 | 92892545.85 | 0.00 | 0.00 |
June | 0.223350E+09 | 20874701.66 | 90105188.78 | 5669429.11 | 84435759.67 | 0.00 | 0.00 |
July | 0.231874E+09 | 14970905.08 | 94554156.30 | 8383125.91 | 86171030.39 | 0.00 | 0.00 |
August | 0.264859E+09 | 25565559.15 | 0.119359E+09 | 30325060.49 | 89033931.16 | 0.00 | 0.00 |
September | 0.351662E+09 | 60178026.66 | 0.182921E+09 | 95036114.58 | 87885276.20 | 0.00 | 0.00 |
October | 0.414509E+09 | 0.113262E+09 | 0.259457E+09 | 0.176276E+09 | 83180150.54 | 0.00 | 0.00 |
November | 0.421086E+09 | 0.192333E+09 | 0.302200E+09 | 0.231149E+09 | 71050625.13 | 0.00 | 0.00 |
December | 0.396914E+09 | 0.255217E+09 | 0.307068E+09 | 0.230695E+09 | 76373138.43 | 0.00 | 0.00 |
Annual Sum or Average | 0.379090E+10 | 0.144931E+10 | 0.238640E+10 | 0.138085E+10 | 0.100555E+10 | 0.00 | 0.00 |
Minimum of Months | 0.208191E+09 | 14970905.08 | 90105188.78 | 5669429.11 | 71050625.13 | 0.00 | 0.00 |
Maximum of Months | 0.421086E+09 | 0.255217E+09 | 0.307068E+09 | 0.231149E+09 | 95422629.83 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 9704887.14 | 0.242102E+09 | 43713969.60 | 0.00 | 43713969.60 | 0.00 | 0.00 |
February | 25149655.52 | 0.189063E+09 | 48213648.10 | 0.00 | 48213648.10 | 0.00 | 0.00 |
March | 57242008.37 | 0.168837E+09 | 69870982.94 | 2765.95 | 69868216.99 | 0.00 | 0.00 |
April | 0.113607E+09 | 76890738.99 | 78518344.10 | 1000279.47 | 77518064.63 | 0.00 | 0.00 |
May | 0.194994E+09 | 33815363.02 | 95843144.60 | 7063304.15 | 88779840.45 | 0.00 | 0.00 |
June | 0.262173E+09 | 10763610.52 | 98633813.54 | 12290815.53 | 86342998.01 | 0.00 | 0.00 |
July | 0.253615E+09 | 5540435.89 | 94160895.41 | 9236150.10 | 84924745.31 | 0.00 | 0.00 |
August | 0.202349E+09 | 12371518.69 | 79637162.39 | 1894638.37 | 77742524.03 | 0.00 | 0.00 |
September | 0.143021E+09 | 40258526.93 | 67049393.63 | 84739.01 | 66964654.62 | 0.00 | 0.00 |
October | 79631418.21 | 91335854.75 | 57430655.00 | 0.00 | 57430655.00 | 0.00 | 0.00 |
November | 21019159.04 | 0.187666E+09 | 44867884.08 | 0.00 | 44867884.08 | 0.00 | 0.00 |
December | 6596807.47 | 0.268970E+09 | 43375413.74 | 0.00 | 43375413.74 | 0.00 | 0.00 |
Annual Sum or Average | 0.136910E+10 | 0.132761E+10 | 0.821315E+09 | 31572692.58 | 0.789743E+09 | 0.00 | 0.00 |
Minimum of Months | 6596807.47 | 5540435.89 | 43375413.74 | 0.00 | 43375413.74 | 0.00 | 0.00 |
Maximum of Months | 0.262173E+09 | 0.268970E+09 | 98633813.54 | 12290815.53 | 88779840.45 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.739557E+09 | 0.763670E+09 | 0.646361E+09 | 0.430960E+09 | 0.215402E+09 | 0.00 | 0.00 |
February | 0.793970E+09 | 0.603279E+09 | 0.648005E+09 | 0.413664E+09 | 0.234341E+09 | 0.00 | 0.00 |
March | 0.933706E+09 | 0.553521E+09 | 0.725871E+09 | 0.404058E+09 | 0.321813E+09 | 0.00 | 0.00 |
April | 0.109681E+10 | 0.270697E+09 | 0.711319E+09 | 0.361253E+09 | 0.350066E+09 | 0.00 | 0.00 |
May | 0.124545E+10 | 0.132877E+09 | 0.696105E+09 | 0.324180E+09 | 0.371925E+09 | 0.00 | 0.00 |
June | 0.138933E+10 | 46286543.03 | 0.654827E+09 | 0.308561E+09 | 0.346266E+09 | 0.00 | 0.00 |
July | 0.133613E+10 | 27172157.28 | 0.620963E+09 | 0.273320E+09 | 0.347643E+09 | 0.00 | 0.00 |
August | 0.128370E+10 | 54224434.96 | 0.628139E+09 | 0.283153E+09 | 0.344986E+09 | 0.00 | 0.00 |
September | 0.126334E+10 | 0.153429E+09 | 0.688511E+09 | 0.381390E+09 | 0.307121E+09 | 0.00 | 0.00 |
October | 0.106423E+10 | 0.327204E+09 | 0.688060E+09 | 0.416283E+09 | 0.271777E+09 | 0.00 | 0.00 |
November | 0.870850E+09 | 0.605392E+09 | 0.692953E+09 | 0.472029E+09 | 0.220924E+09 | 0.00 | 0.00 |
December | 0.726383E+09 | 0.828858E+09 | 0.656523E+09 | 0.432885E+09 | 0.223638E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127435E+11 | 0.436661E+10 | 0.805764E+10 | 0.450174E+10 | 0.355590E+10 | 0.00 | 0.00 |
Minimum of Months | 0.726383E+09 | 27172157.28 | 0.620963E+09 | 0.273320E+09 | 0.215402E+09 | 0.00 | 0.00 |
Maximum of Months | 0.138933E+10 | 0.828858E+09 | 0.725871E+09 | 0.472029E+09 | 0.371925E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.256895E+09 | 0.770761E+09 | 0.327041E+09 | 0.147604E+09 | 0.179438E+09 | 0.00 | 0.00 |
February | 0.388060E+09 | 0.602905E+09 | 0.390478E+09 | 0.188293E+09 | 0.202185E+09 | 0.00 | 0.00 |
March | 0.613362E+09 | 0.548531E+09 | 0.537961E+09 | 0.248126E+09 | 0.289835E+09 | 0.00 | 0.00 |
April | 0.924319E+09 | 0.267017E+09 | 0.623855E+09 | 0.292832E+09 | 0.331023E+09 | 0.00 | 0.00 |
May | 0.120680E+10 | 0.132132E+09 | 0.679796E+09 | 0.313049E+09 | 0.366746E+09 | 0.00 | 0.00 |
June | 0.140707E+10 | 46428480.83 | 0.665449E+09 | 0.316834E+09 | 0.348614E+09 | 0.00 | 0.00 |
July | 0.133036E+10 | 26879439.03 | 0.620433E+09 | 0.274383E+09 | 0.346050E+09 | 0.00 | 0.00 |
August | 0.117773E+10 | 53434268.12 | 0.578444E+09 | 0.247607E+09 | 0.330837E+09 | 0.00 | 0.00 |
September | 0.984605E+09 | 0.149770E+09 | 0.543615E+09 | 0.262677E+09 | 0.280938E+09 | 0.00 | 0.00 |
October | 0.629225E+09 | 0.319999E+09 | 0.435454E+09 | 0.195894E+09 | 0.239560E+09 | 0.00 | 0.00 |
November | 0.363488E+09 | 0.605834E+09 | 0.371206E+09 | 0.183035E+09 | 0.188171E+09 | 0.00 | 0.00 |
December | 0.234549E+09 | 0.845511E+09 | 0.326824E+09 | 0.144459E+09 | 0.182365E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.951646E+10 | 0.436920E+10 | 0.610055E+10 | 0.281479E+10 | 0.328576E+10 | 0.00 | 0.00 |
Minimum of Months | 0.234549E+09 | 26879439.03 | 0.326824E+09 | 0.144459E+09 | 0.179438E+09 | 0.00 | 0.00 |
Maximum of Months | 0.140707E+10 | 0.845511E+09 | 0.679796E+09 | 0.316834E+09 | 0.366746E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.828680E+09 | 0.100795E+10 | 0.742775E+09 | 0.491065E+09 | 0.251710E+09 | 0.00 | 0.00 |
February | 0.762252E+09 | 0.816123E+09 | 0.655180E+09 | 0.390575E+09 | 0.264605E+09 | 0.00 | 0.00 |
March | 0.764202E+09 | 0.790925E+09 | 0.628360E+09 | 0.270247E+09 | 0.358112E+09 | 0.00 | 0.00 |
April | 0.733292E+09 | 0.439718E+09 | 0.491746E+09 | 0.122910E+09 | 0.368836E+09 | 0.00 | 0.00 |
May | 0.805209E+09 | 0.238886E+09 | 0.443490E+09 | 49891063.49 | 0.393599E+09 | 0.00 | 0.00 |
June | 0.968785E+09 | 99113426.61 | 0.408907E+09 | 38910104.08 | 0.369997E+09 | 0.00 | 0.00 |
July | 0.965228E+09 | 73562860.60 | 0.408857E+09 | 38172500.78 | 0.370684E+09 | 0.00 | 0.00 |
August | 0.935157E+09 | 0.121612E+09 | 0.431139E+09 | 69810394.97 | 0.361328E+09 | 0.00 | 0.00 |
September | 0.101908E+10 | 0.277904E+09 | 0.541591E+09 | 0.206100E+09 | 0.335491E+09 | 0.00 | 0.00 |
October | 0.102873E+10 | 0.505037E+09 | 0.686584E+09 | 0.381942E+09 | 0.304642E+09 | 0.00 | 0.00 |
November | 0.908410E+09 | 0.840971E+09 | 0.751982E+09 | 0.500836E+09 | 0.251146E+09 | 0.00 | 0.00 |
December | 0.818070E+09 | 0.107802E+10 | 0.759297E+09 | 0.499852E+09 | 0.259445E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105371E+11 | 0.628983E+10 | 0.694991E+10 | 0.306031E+10 | 0.388960E+10 | 0.00 | 0.00 |
Minimum of Months | 0.733292E+09 | 73562860.60 | 0.408857E+09 | 38172500.78 | 0.251146E+09 | 0.00 | 0.00 |
Maximum of Months | 0.102873E+10 | 0.107802E+10 | 0.759297E+09 | 0.500836E+09 | 0.393599E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.775470E+09 | 0.766057E+09 | 0.661628E+09 | 0.445502E+09 | 0.216126E+09 | 0.00 | 0.00 |
February | 0.750741E+09 | 0.609619E+09 | 0.610259E+09 | 0.380562E+09 | 0.229697E+09 | 0.00 | 0.00 |
March | 0.946653E+09 | 0.575199E+09 | 0.717083E+09 | 0.392853E+09 | 0.324229E+09 | 0.00 | 0.00 |
April | 0.106179E+10 | 0.288353E+09 | 0.676285E+09 | 0.334351E+09 | 0.341935E+09 | 0.00 | 0.00 |
May | 0.123070E+10 | 0.139131E+09 | 0.683278E+09 | 0.312791E+09 | 0.370487E+09 | 0.00 | 0.00 |
June | 0.134314E+10 | 46430323.45 | 0.627908E+09 | 0.283748E+09 | 0.344161E+09 | 0.00 | 0.00 |
July | 0.128249E+10 | 26002006.78 | 0.591061E+09 | 0.245426E+09 | 0.345635E+09 | 0.00 | 0.00 |
August | 0.124388E+10 | 53947434.65 | 0.607067E+09 | 0.271168E+09 | 0.335899E+09 | 0.00 | 0.00 |
September | 0.126312E+10 | 0.160226E+09 | 0.683569E+09 | 0.372750E+09 | 0.310819E+09 | 0.00 | 0.00 |
October | 0.114491E+10 | 0.330513E+09 | 0.729374E+09 | 0.457483E+09 | 0.271891E+09 | 0.00 | 0.00 |
November | 0.910701E+09 | 0.610284E+09 | 0.704840E+09 | 0.487965E+09 | 0.216875E+09 | 0.00 | 0.00 |
December | 0.743081E+09 | 0.833225E+09 | 0.656450E+09 | 0.436397E+09 | 0.220053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126967E+11 | 0.443899E+10 | 0.794880E+10 | 0.442100E+10 | 0.352781E+10 | 0.00 | 0.00 |
Minimum of Months | 0.743081E+09 | 26002006.78 | 0.591061E+09 | 0.245426E+09 | 0.216126E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134314E+10 | 0.833225E+09 | 0.729374E+09 | 0.487965E+09 | 0.370487E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.329339E+09 | 0.803200E+09 | 0.342309E+09 | 0.162146E+09 | 0.180162E+09 | 0.00 | 0.00 |
February | 0.378198E+09 | 0.635768E+09 | 0.352733E+09 | 0.155192E+09 | 0.197541E+09 | 0.00 | 0.00 |
March | 0.645790E+09 | 0.580849E+09 | 0.529172E+09 | 0.236921E+09 | 0.292251E+09 | 0.00 | 0.00 |
April | 0.892811E+09 | 0.282722E+09 | 0.588821E+09 | 0.265930E+09 | 0.322892E+09 | 0.00 | 0.00 |
May | 0.118790E+10 | 0.133330E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
June | 0.135827E+10 | 45250194.73 | 0.638530E+09 | 0.292021E+09 | 0.346509E+09 | 0.00 | 0.00 |
July | 0.127580E+10 | 25272364.24 | 0.590530E+09 | 0.246488E+09 | 0.344041E+09 | 0.00 | 0.00 |
August | 0.113860E+10 | 52141229.08 | 0.557372E+09 | 0.235622E+09 | 0.321750E+09 | 0.00 | 0.00 |
September | 0.989393E+09 | 0.156857E+09 | 0.538673E+09 | 0.254037E+09 | 0.284635E+09 | 0.00 | 0.00 |
October | 0.726336E+09 | 0.329625E+09 | 0.476768E+09 | 0.237094E+09 | 0.239674E+09 | 0.00 | 0.00 |
November | 0.435186E+09 | 0.635427E+09 | 0.383093E+09 | 0.198972E+09 | 0.184121E+09 | 0.00 | 0.00 |
December | 0.292380E+09 | 0.885512E+09 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.965000E+10 | 0.456595E+10 | 0.599172E+10 | 0.273405E+10 | 0.325767E+10 | 0.00 | 0.00 |
Minimum of Months | 0.292380E+09 | 25272364.24 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Maximum of Months | 0.135827E+10 | 0.885512E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.720569E+09 | 0.403784E+09 | 0.548441E+09 | 0.415568E+09 | 0.132872E+09 | 0.00 | 0.00 |
February | 0.627784E+09 | 0.317924E+09 | 0.466063E+09 | 0.330528E+09 | 0.135536E+09 | 0.00 | 0.00 |
March | 0.561162E+09 | 0.298844E+09 | 0.403662E+09 | 0.228694E+09 | 0.174968E+09 | 0.00 | 0.00 |
April | 0.451546E+09 | 0.147621E+09 | 0.272199E+09 | 0.102180E+09 | 0.170019E+09 | 0.00 | 0.00 |
May | 0.405650E+09 | 67913909.06 | 0.199600E+09 | 29271767.90 | 0.170329E+09 | 0.00 | 0.00 |
June | 0.442496E+09 | 21139273.72 | 0.165218E+09 | 10395519.34 | 0.154822E+09 | 0.00 | 0.00 |
July | 0.458421E+09 | 11630592.27 | 0.173375E+09 | 15371379.69 | 0.158004E+09 | 0.00 | 0.00 |
August | 0.512087E+09 | 25637620.15 | 0.218858E+09 | 55604320.39 | 0.163253E+09 | 0.00 | 0.00 |
September | 0.655344E+09 | 79030791.30 | 0.335406E+09 | 0.174259E+09 | 0.161147E+09 | 0.00 | 0.00 |
October | 0.767294E+09 | 0.169082E+09 | 0.475742E+09 | 0.323222E+09 | 0.152520E+09 | 0.00 | 0.00 |
November | 0.774017E+09 | 0.316754E+09 | 0.554116E+09 | 0.423837E+09 | 0.130279E+09 | 0.00 | 0.00 |
December | 0.728111E+09 | 0.436943E+09 | 0.563043E+09 | 0.423004E+09 | 0.140039E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.710448E+10 | 0.229630E+10 | 0.437572E+10 | 0.253194E+10 | 0.184379E+10 | 0.00 | 0.00 |
Minimum of Months | 0.405650E+09 | 11630592.27 | 0.165218E+09 | 10395519.34 | 0.130279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.774017E+09 | 0.436943E+09 | 0.563043E+09 | 0.423837E+09 | 0.174968E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 41661808.54 | 0.246355E+10 | 0.382432E+09 | 0.00 | 0.382432E+09 | 0.00 | 0.00 |
February | 0.154004E+09 | 0.194960E+10 | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.00 | 0.00 |
March | 0.388310E+09 | 0.178455E+10 | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.00 | 0.00 |
April | 0.830028E+09 | 0.928219E+09 | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.00 | 0.00 |
May | 0.146786E+10 | 0.493323E+09 | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.00 | 0.00 |
June | 0.200698E+10 | 0.218844E+09 | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.00 | 0.00 |
July | 0.191411E+10 | 0.169889E+09 | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.00 | 0.00 |
August | 0.150180E+10 | 0.265407E+09 | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.00 | 0.00 |
September | 0.107719E+10 | 0.572372E+09 | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.00 | 0.00 |
October | 0.556930E+09 | 0.108891E+10 | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.00 | 0.00 |
November | 0.113576E+09 | 0.196912E+10 | 0.392527E+09 | 0.00 | 0.392527E+09 | 0.00 | 0.00 |
December | 29062726.31 | 0.268136E+10 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100815E+11 | 0.145851E+11 | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.00 | 0.00 |
Minimum of Months | 29062726.31 | 0.169889E+09 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Maximum of Months | 0.200698E+10 | 0.268136E+10 | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 30903013.88 | 0.257468E+10 | 0.382432E+09 | 0.00 | 0.382432E+09 | 0.00 | 0.00 |
February | 0.135454E+09 | 0.203207E+10 | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.00 | 0.00 |
March | 0.356098E+09 | 0.185600E+10 | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.00 | 0.00 |
April | 0.792637E+09 | 0.963510E+09 | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.00 | 0.00 |
May | 0.142342E+10 | 0.513253E+09 | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.00 | 0.00 |
June | 0.196115E+10 | 0.230532E+09 | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.00 | 0.00 |
July | 0.186761E+10 | 0.182017E+09 | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.00 | 0.00 |
August | 0.145742E+10 | 0.280342E+09 | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.00 | 0.00 |
September | 0.104267E+10 | 0.596488E+09 | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.00 | 0.00 |
October | 0.527825E+09 | 0.113186E+10 | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.00 | 0.00 |
November | 97200265.02 | 0.204852E+10 | 0.392527E+09 | 0.00 | 0.392527E+09 | 0.00 | 0.00 |
December | 21840316.58 | 0.279947E+10 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.971423E+10 | 0.152087E+11 | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.00 | 0.00 |
Minimum of Months | 21840316.58 | 0.182017E+09 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Maximum of Months | 0.196115E+10 | 0.279947E+10 | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.946634E+09 | 0.181279E+10 | 0.973364E+09 | 0.578542E+09 | 0.394822E+09 | 0.00 | 0.00 |
February | 0.117627E+10 | 0.143721E+10 | 0.103844E+10 | 0.601931E+09 | 0.436505E+09 | 0.00 | 0.00 |
March | 0.156593E+10 | 0.134279E+10 | 0.126377E+10 | 0.652149E+09 | 0.611620E+09 | 0.00 | 0.00 |
April | 0.211786E+10 | 0.736322E+09 | 0.133510E+10 | 0.654044E+09 | 0.681055E+09 | 0.00 | 0.00 |
May | 0.256602E+10 | 0.446186E+09 | 0.137582E+10 | 0.637186E+09 | 0.738635E+09 | 0.00 | 0.00 |
June | 0.291704E+10 | 0.222751E+09 | 0.132020E+10 | 0.625352E+09 | 0.694846E+09 | 0.00 | 0.00 |
July | 0.279234E+10 | 0.186271E+09 | 0.124132E+10 | 0.547666E+09 | 0.693659E+09 | 0.00 | 0.00 |
August | 0.259972E+10 | 0.258221E+09 | 0.120652E+10 | 0.530726E+09 | 0.675789E+09 | 0.00 | 0.00 |
September | 0.242029E+10 | 0.457255E+09 | 0.123206E+10 | 0.644030E+09 | 0.588031E+09 | 0.00 | 0.00 |
October | 0.178376E+10 | 0.846285E+09 | 0.112346E+10 | 0.612150E+09 | 0.511313E+09 | 0.00 | 0.00 |
November | 0.124000E+10 | 0.143891E+10 | 0.106411E+10 | 0.655039E+09 | 0.409076E+09 | 0.00 | 0.00 |
December | 0.909223E+09 | 0.192784E+10 | 0.983308E+09 | 0.577324E+09 | 0.405984E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.230351E+11 | 0.111128E+11 | 0.141575E+11 | 0.731614E+10 | 0.684134E+10 | 0.00 | 0.00 |
Minimum of Months | 0.909223E+09 | 0.186271E+09 | 0.973364E+09 | 0.530726E+09 | 0.394822E+09 | 0.00 | 0.00 |
Maximum of Months | 0.291704E+10 | 0.192784E+10 | 0.137582E+10 | 0.655039E+09 | 0.738635E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.178283E+10 | 0.177953E+10 | 0.152718E+10 | 0.105785E+10 | 0.469332E+09 | 0.00 | 0.00 |
February | 0.159840E+10 | 0.144863E+10 | 0.133098E+10 | 0.841376E+09 | 0.489606E+09 | 0.00 | 0.00 |
March | 0.152058E+10 | 0.141888E+10 | 0.123709E+10 | 0.582162E+09 | 0.654925E+09 | 0.00 | 0.00 |
April | 0.135260E+10 | 0.815852E+09 | 0.928373E+09 | 0.263104E+09 | 0.665269E+09 | 0.00 | 0.00 |
May | 0.139975E+10 | 0.446720E+09 | 0.795528E+09 | 95695732.11 | 0.699832E+09 | 0.00 | 0.00 |
June | 0.165026E+10 | 0.190155E+09 | 0.716374E+09 | 63322576.03 | 0.653051E+09 | 0.00 | 0.00 |
July | 0.165340E+10 | 0.147552E+09 | 0.723725E+09 | 66827933.17 | 0.656897E+09 | 0.00 | 0.00 |
August | 0.167122E+10 | 0.236379E+09 | 0.795946E+09 | 0.147226E+09 | 0.648721E+09 | 0.00 | 0.00 |
September | 0.194592E+10 | 0.512051E+09 | 0.105488E+10 | 0.443840E+09 | 0.611036E+09 | 0.00 | 0.00 |
October | 0.206345E+10 | 0.918973E+09 | 0.138326E+10 | 0.822779E+09 | 0.560482E+09 | 0.00 | 0.00 |
November | 0.192987E+10 | 0.147972E+10 | 0.154509E+10 | 0.107890E+10 | 0.466191E+09 | 0.00 | 0.00 |
December | 0.177906E+10 | 0.189663E+10 | 0.156334E+10 | 0.107678E+10 | 0.486559E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.203474E+11 | 0.112911E+11 | 0.136018E+11 | 0.653986E+10 | 0.706190E+10 | 0.00 | 0.00 |
Minimum of Months | 0.135260E+10 | 0.147552E+09 | 0.716374E+09 | 63322576.03 | 0.466191E+09 | 0.00 | 0.00 |
Maximum of Months | 0.206345E+10 | 0.189663E+10 | 0.156334E+10 | 0.107890E+10 | 0.699832E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770391E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161132060.0 | 81.21 | 0.00 | 0.00 |
February | 0.696159E+10 | -0.681597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -145621119.2 | 81.21 | 0.00 | 0.00 |
March | 0.770276E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161297839.2 | 81.21 | 0.00 | 0.00 |
April | 0.746476E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156170683.9 | 81.21 | 0.00 | 0.00 |
May | 0.770421E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161411697.3 | 81.21 | 0.00 | 0.00 |
June | 0.745674E+10 | -0.730054E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156203483.3 | 81.21 | 0.00 | 0.00 |
July | 0.771226E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161408303.2 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161408201.7 | 81.21 | 0.00 | 0.00 |
September | 0.746614E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156204007.7 | 81.21 | 0.00 | 0.00 |
October | 0.770285E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161412206.8 | 81.21 | 0.00 | 0.00 |
November | 0.744846E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156034980.2 | 81.21 | 0.00 | 0.00 |
December | 0.771199E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161128706.2 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907399E+11 | -0.888405E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.189943E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696159E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161412206.8 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771226E+10 | -0.681597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -145621119.2 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.113621E+12 | -0.111892E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172854E+10 | 81.25 | 0.00 | 0.00 |
February | 0.102573E+12 | -0.100997E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.157524E+10 | 81.25 | 0.00 | 0.00 |
March | 0.110873E+12 | -0.109106E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176721E+10 | 81.26 | 0.00 | 0.00 |
April | 0.102672E+12 | -0.100964E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170773E+10 | 81.25 | 0.00 | 0.00 |
May | 0.100552E+12 | -0.987971E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175489E+10 | 81.25 | 0.00 | 0.00 |
June | 0.926529E+11 | -0.909639E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.168894E+10 | 81.24 | 0.00 | 0.00 |
July | 0.929599E+11 | -0.912303E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172956E+10 | 81.24 | 0.00 | 0.00 |
August | 0.929797E+11 | -0.912535E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172619E+10 | 81.24 | 0.00 | 0.00 |
September | 0.926945E+11 | -0.910246E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.166982E+10 | 81.24 | 0.00 | 0.00 |
October | 0.100608E+12 | -0.988823E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172551E+10 | 81.24 | 0.00 | 0.00 |
November | 0.102716E+12 | -0.101046E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.166990E+10 | 81.25 | 0.00 | 0.00 |
December | 0.110894E+12 | -0.109168E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172573E+10 | 81.25 | 0.00 | 0.00 |
Annual Sum or Average | 0.121579E+13 | -0.119533E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.204693E+11 | 81.25 | 0.00 | 0.00 |
Minimum of Months | 0.926529E+11 | -0.111892E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.176721E+10 | 81.24 | 0.00 | 0.00 |
Maximum of Months | 0.113621E+12 | -0.909639E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157524E+10 | 81.26 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.654904E+11 | -0.640247E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146564E+10 | 58.98 | 0.00 | 0.00 |
February | 0.591275E+11 | -0.577844E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.134309E+10 | 58.98 | 0.00 | 0.00 |
March | 0.631989E+11 | -0.616799E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151899E+10 | 58.98 | 0.00 | 0.00 |
April | 0.571383E+11 | -0.556717E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.146664E+10 | 58.98 | 0.00 | 0.00 |
May | 0.542652E+11 | -0.527630E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150218E+10 | 58.98 | 0.00 | 0.00 |
June | 0.485081E+11 | -0.470672E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.144090E+10 | 58.98 | 0.00 | 0.00 |
July | 0.476711E+11 | -0.462039E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146720E+10 | 58.98 | 0.00 | 0.00 |
August | 0.477338E+11 | -0.462712E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146257E+10 | 58.98 | 0.00 | 0.00 |
September | 0.485126E+11 | -0.470981E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141447E+10 | 58.98 | 0.00 | 0.00 |
October | 0.542673E+11 | -0.528057E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146166E+10 | 58.98 | 0.00 | 0.00 |
November | 0.571356E+11 | -0.557211E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141450E+10 | 58.98 | 0.00 | 0.00 |
December | 0.631361E+11 | -0.616740E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146201E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.666185E+12 | -0.648765E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.174199E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.476711E+11 | -0.640247E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.151899E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.654904E+11 | -0.462039E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.134309E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.93 | 0.93 | 01-JAN-07:00 | 7206.50 | 38.27 | 274.17 | 278.00 | 949.80 | 26.84 | 164.83 | 257.17 |
February | 268.33 | 0.93 | 0.93 | 01-FEB-07:49 | 5842.96 | 33.62 | 210.83 | 270.83 | 596.94 | 23.71 | 144.50 | 237.17 |
March | 351.83 | 0.93 | 0.93 | 01-MAR-06:00 | 1032.16 | 19.53 | 12.00 | 317.83 | 398.13 | 20.87 | 123.83 | 242.50 |
April | 373.83 | 0.94 | 0.93 | 01-APR-06:49 | 746.19 | 19.06 | 0.00 | 335.17 | 316.76 | 20.82 | 122.83 | 235.50 |
May | 408.83 | 0.94 | 0.93 | 01-MAY-06:10 | 624.18 | 18.70 | 0.00 | 359.00 | 269.25 | 20.45 | 85.17 | 234.33 |
June | 398.00 | 0.94 | 0.93 | 01-JUN-06:19 | 547.31 | 18.62 | 0.00 | 349.50 | 242.61 | 20.43 | 37.33 | 166.67 |
July | 400.17 | 0.94 | 0.93 | 01-JUL-06:19 | 599.84 | 18.49 | 0.00 | 356.67 | 257.08 | 20.27 | 73.83 | 184.33 |
August | 377.83 | 0.94 | 0.93 | 01-AUG-06:19 | 702.43 | 18.82 | 0.00 | 346.00 | 297.01 | 20.57 | 125.67 | 230.33 |
September | 365.83 | 0.94 | 0.93 | 01-SEP-07:10 | 806.86 | 18.93 | 0.00 | 314.83 | 341.27 | 20.72 | 128.67 | 224.33 |
October | 318.83 | 0.93 | 0.93 | 01-OCT-06:49 | 2910.30 | 26.00 | 124.83 | 312.50 | 466.70 | 21.79 | 115.83 | 273.00 |
November | 295.83 | 0.93 | 0.93 | 01-NOV-12:39 | 7457.25 | 37.43 | 288.17 | 288.17 | 727.39 | 25.69 | 136.67 | 266.67 |
December | 289.50 | 0.93 | 0.93 | 01-DEC-07:10 | 6497.88 | 37.79 | 284.33 | 276.50 | 1060.41 | 27.46 | 184.33 | 266.50 |
Annual Sum or Average | 4125.67 | 0.93 | 2543.52 | 24.34 | 1194.33 | 3805.00 | 460.33 | 22.15 | 1443.50 | 2818.50 | ||
Minimum of Months | 268.33 | 0.93 | 0.93 | 547.31 | 18.49 | 0.00 | 270.83 | 242.61 | 20.27 | 37.33 | 166.67 | |
Maximum of Months | 408.83 | 0.94 | 0.93 | 7457.25 | 38.27 | 288.17 | 359.00 | 1060.41 | 27.46 | 184.33 | 273.00 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.62 | 0.61 | 01-JAN-07:00 | 7610.17 | 38.33 | 274.50 | 284.33 | 1352.56 | 26.47 | 156.83 | 270.50 |
February | 268.33 | 0.62 | 0.61 | 01-FEB-07:40 | 6205.02 | 33.63 | 210.83 | 278.67 | 958.55 | 23.49 | 138.50 | 257.00 |
March | 351.83 | 0.63 | 0.61 | 01-MAR-06:00 | 1286.02 | 19.88 | 20.67 | 333.83 | 651.44 | 21.06 | 143.67 | 302.50 |
April | 373.83 | 0.63 | 0.61 | 01-APR-06:40 | 920.68 | 19.70 | 7.67 | 350.50 | 490.82 | 21.24 | 177.00 | 312.67 |
May | 408.83 | 0.63 | 0.61 | 01-MAY-05:00 | 752.17 | 19.52 | 0.17 | 376.50 | 396.87 | 21.05 | 208.83 | 340.50 |
June | 398.00 | 0.63 | 0.61 | 01-JUN-06:10 | 661.81 | 19.52 | 0.00 | 369.83 | 356.78 | 21.09 | 144.50 | 331.67 |
July | 400.17 | 0.63 | 0.61 | 01-JUL-06:10 | 716.11 | 19.37 | 0.00 | 377.00 | 372.99 | 20.91 | 169.33 | 327.50 |
August | 377.83 | 0.63 | 0.61 | 01-AUG-05:00 | 847.90 | 19.58 | 1.50 | 362.33 | 442.08 | 21.11 | 183.17 | 318.00 |
September | 365.83 | 0.63 | 0.61 | 01-SEP-06:30 | 1017.82 | 19.43 | 8.50 | 333.50 | 551.77 | 21.02 | 148.83 | 296.50 |
October | 318.83 | 0.62 | 0.61 | 01-OCT-06:49 | 3229.67 | 26.08 | 127.17 | 317.50 | 785.09 | 21.76 | 130.50 | 300.00 |
November | 295.83 | 0.62 | 0.61 | 01-NOV-12:39 | 7834.17 | 37.51 | 288.17 | 293.83 | 1104.66 | 25.34 | 129.83 | 280.83 |
December | 289.50 | 0.62 | 0.61 | 01-DEC-06:00 | 6887.49 | 37.85 | 284.50 | 281.83 | 1451.83 | 27.17 | 168.83 | 274.83 |
Annual Sum or Average | 4125.67 | 0.63 | 2777.70 | 24.81 | 1223.67 | 3959.67 | 694.22 | 22.38 | 1899.83 | 3612.50 | ||
Minimum of Months | 268.33 | 0.62 | 0.61 | 661.81 | 19.37 | 0.00 | 278.67 | 356.78 | 20.91 | 129.83 | 257.00 | |
Maximum of Months | 408.83 | 0.63 | 0.61 | 7834.17 | 38.33 | 288.17 | 377.00 | 1451.83 | 27.17 | 208.83 | 340.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.83 | 0.80 | 01-JAN-08:20 | 282.51 | 14.00 | 0.00 | 221.33 | 148.80 | 17.64 | 0.00 | 33.83 |
February | 268.33 | 0.82 | 0.80 | 01-FEB-08:30 | 319.80 | 14.70 | 0.00 | 229.33 | 166.71 | 18.22 | 0.00 | 66.17 |
March | 351.83 | 0.82 | 0.80 | 01-MAR-07:19 | 383.61 | 15.50 | 0.00 | 301.00 | 188.13 | 18.82 | 0.00 | 130.50 |
April | 373.83 | 0.81 | 0.80 | 01-APR-06:40 | 462.52 | 16.65 | 0.00 | 353.33 | 221.28 | 19.90 | 9.17 | 208.50 |
May | 408.83 | 0.81 | 0.80 | 01-MAY-05:49 | 601.05 | 17.37 | 5.33 | 388.67 | 257.13 | 20.48 | 73.50 | 350.33 |
June | 398.00 | 0.80 | 0.80 | 01-JUN-05:49 | 649.91 | 20.42 | 82.83 | 384.33 | 274.53 | 20.93 | 76.83 | 347.83 |
July | 400.17 | 0.81 | 0.80 | 01-JUL-05:49 | 620.53 | 18.61 | 39.33 | 395.67 | 292.41 | 21.45 | 78.33 | 323.17 |
August | 377.83 | 0.81 | 0.80 | 01-AUG-05:49 | 511.22 | 16.84 | 0.00 | 367.67 | 242.84 | 20.10 | 26.17 | 279.17 |
September | 365.83 | 0.81 | 0.80 | 01-SEP-06:10 | 377.61 | 15.82 | 0.00 | 317.67 | 190.57 | 19.13 | 0.00 | 140.33 |
October | 318.83 | 0.82 | 0.80 | 01-OCT-07:10 | 337.61 | 15.04 | 0.00 | 284.67 | 173.22 | 18.47 | 0.00 | 75.17 |
November | 295.83 | 0.83 | 0.80 | 01-NOV-12:39 | 269.97 | 14.03 | 0.00 | 230.33 | 143.33 | 17.64 | 0.00 | 14.50 |
December | 289.50 | 0.83 | 0.80 | 01-DEC-07:49 | 289.86 | 14.04 | 0.00 | 231.00 | 150.74 | 17.64 | 0.00 | 26.33 |
Annual Sum or Average | 4125.67 | 0.81 | 442.92 | 16.32 | 127.50 | 3705.00 | 210.63 | 19.37 | 264.00 | 1995.83 | ||
Minimum of Months | 268.33 | 0.80 | 0.80 | 269.97 | 14.00 | 0.00 | 221.33 | 143.33 | 17.64 | 0.00 | 14.50 | |
Maximum of Months | 408.83 | 0.83 | 0.80 | 649.91 | 20.42 | 82.83 | 395.67 | 292.41 | 21.45 | 78.33 | 350.33 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.83 | 0.80 | 01-JAN-08:20 | 282.51 | 14.00 | 0.00 | 221.33 | 148.80 | 17.64 | 0.00 | 33.83 |
February | 268.33 | 0.82 | 0.80 | 01-FEB-08:30 | 319.80 | 14.70 | 0.00 | 229.33 | 166.71 | 18.22 | 0.00 | 66.17 |
March | 351.83 | 0.82 | 0.80 | 01-MAR-07:19 | 383.61 | 15.50 | 0.00 | 301.00 | 188.13 | 18.82 | 0.00 | 130.50 |
April | 373.83 | 0.81 | 0.80 | 01-APR-06:40 | 462.52 | 16.65 | 0.00 | 353.33 | 221.28 | 19.90 | 9.17 | 208.50 |
May | 408.83 | 0.81 | 0.80 | 01-MAY-05:49 | 601.05 | 17.37 | 5.33 | 388.67 | 257.13 | 20.48 | 73.50 | 350.33 |
June | 398.00 | 0.80 | 0.80 | 01-JUN-05:49 | 649.91 | 20.42 | 82.83 | 384.33 | 274.53 | 20.93 | 76.83 | 347.83 |
July | 400.17 | 0.81 | 0.80 | 01-JUL-05:49 | 620.53 | 18.61 | 39.33 | 395.67 | 292.41 | 21.45 | 78.33 | 323.17 |
August | 377.83 | 0.81 | 0.80 | 01-AUG-05:49 | 511.22 | 16.84 | 0.00 | 367.67 | 242.84 | 20.10 | 26.17 | 279.17 |
September | 365.83 | 0.81 | 0.80 | 01-SEP-06:10 | 377.61 | 15.82 | 0.00 | 317.67 | 190.57 | 19.13 | 0.00 | 140.33 |
October | 318.83 | 0.82 | 0.80 | 01-OCT-07:10 | 337.61 | 15.04 | 0.00 | 284.67 | 173.22 | 18.47 | 0.00 | 75.17 |
November | 295.83 | 0.83 | 0.80 | 01-NOV-12:39 | 269.97 | 14.03 | 0.00 | 230.33 | 143.33 | 17.64 | 0.00 | 14.50 |
December | 289.50 | 0.83 | 0.80 | 01-DEC-07:49 | 289.86 | 14.04 | 0.00 | 231.00 | 150.74 | 17.64 | 0.00 | 26.33 |
Annual Sum or Average | 4125.67 | 0.81 | 442.92 | 16.32 | 127.50 | 3705.00 | 210.63 | 19.37 | 264.00 | 1995.83 | ||
Minimum of Months | 268.33 | 0.80 | 0.80 | 269.97 | 14.00 | 0.00 | 221.33 | 143.33 | 17.64 | 0.00 | 14.50 | |
Maximum of Months | 408.83 | 0.83 | 0.80 | 649.91 | 20.42 | 82.83 | 395.67 | 292.41 | 21.45 | 78.33 | 350.33 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.267111E+11 | 150503.22 | 09-JAN-23:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156889E+11 | 127213.93 | 24-FEB-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119959E+11 | 128923.39 | 13-MAR-03:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.506861E+10 | 127472.10 | 13-APR-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.313832E+09 | 41315.69 | 02-MAY-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.448287E+09 | 48612.52 | 25-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.242664E+10 | 102499.65 | 25-OCT-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166087E+11 | 149086.72 | 18-NOV-04:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.217781E+11 | 133193.50 | 21-DEC-23:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101040E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.267111E+11 | 150503.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.185694E+09 | 969.31 | 27-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 86835953.87 | 915.56 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 51083670.29 | 831.23 | 02-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39470.94 | 99.78 | 12-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 90656966.42 | 1254.66 | 27-NOV-11:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.314284E+09 | 1473.36 | 27-DEC-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.728594E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.314284E+09 | 1473.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 262946.07 | 93.80 | 15-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 143062.11 | 406.04 | 27-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 406008.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 262946.07 | 406.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 99139.92 | 62.93 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16173727.66 | 761.63 | 27-DEC-12:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16272867.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16173727.66 | 761.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.224087E+09 | 715.03 | 11-JAN-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106089E+09 | 606.75 | 03-FEB-09:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 40353440.12 | 545.08 | 02-MAR-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 58890202.89 | 805.04 | 27-NOV-11:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.380684E+09 | 1022.42 | 27-DEC-12:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.810104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.380684E+09 | 1022.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 697156.31 | 2451.69 | 02-JAN-00:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 697156.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 697156.31 | 2451.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.289750E+09 | 6147.32 | 14-JAN-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112818E+09 | 3419.57 | 27-FEB-09:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 85294454.05 | 4737.37 | 27-MAR-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6098932.08 | 2353.29 | 11-APR-08:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 218560.25 | 259.71 | 16-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3561414.26 | 1125.09 | 14-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.212640E+09 | 6949.77 | 27-NOV-11:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.272622E+09 | 9290.52 | 03-DEC-11:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.983003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.289750E+09 | 9290.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2501517.39 | 1520.59 | 15-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2501517.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2501517.39 | 1520.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 14094029.93 | 1264.15 | 17-JAN-11:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175453E+09 | 4932.89 | 03-DEC-11:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.175453E+09 | 4932.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.179402E+09 | 2095.45 | 27-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 90991115.21 | 2197.45 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29019497.08 | 1541.18 | 02-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 81484594.09 | 2011.28 | 27-NOV-11:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.593488E+09 | 2812.66 | 27-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.974385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.593488E+09 | 2812.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 12130231.83 | 3387.63 | 23-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5990384.97 | 1912.23 | 01-FEB-11:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3571646.11 | 3636.74 | 02-MAR-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6244617.37 | 7356.88 | 27-NOV-11:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24230081.35 | 8434.23 | 19-DEC-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52166961.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24230081.35 | 8434.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 69943.19 | 233.14 | 23-JAN-11:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 582539.43 | 837.51 | 02-MAR-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2193678.73 | 3914.83 | 27-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2846161.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2193678.73 | 3914.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 48888398.20 | 2447.72 | 27-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 71253799.96 | 2914.84 | 03-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34408146.74 | 2447.73 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33259.54 | 0.50 | 30-APR-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 48666.88 | 0.50 | 13-MAY-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 50726.14 | 0.51 | 08-JUN-02:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15400.64 | 0.51 | 12-JUL-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31376.35 | 0.51 | 11-AUG-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20445.35 | 0.50 | 21-SEP-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29792.77 | 0.50 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4826319.49 | 678.04 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205105E+09 | 3422.98 | 27-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.364712E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 15400.64 | 0.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.205105E+09 | 3422.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.164341E+10 | 9568.32 | 27-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101161E+10 | 9499.84 | 02-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.557949E+09 | 9523.04 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 56283918.63 | 5930.77 | 11-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4563122.11 | 3481.65 | 28-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4127699.85 | 2879.01 | 25-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4354082.16 | 3103.80 | 21-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4757677.97 | 3397.91 | 12-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4557210.23 | 3226.74 | 16-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11710817.74 | 3198.75 | 15-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.756288E+09 | 9426.84 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.218576E+10 | 9619.18 | 27-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.624536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4127699.85 | 2879.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.218576E+10 | 9619.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.270264E+10 | 9612.52 | 27-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167743E+10 | 9582.22 | 10-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.857862E+09 | 9550.46 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78771629.65 | 6907.79 | 11-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4440477.25 | 3246.55 | 06-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3700423.72 | 2712.46 | 30-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4018910.19 | 3529.91 | 21-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5134014.69 | 3413.28 | 12-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5559323.78 | 3509.05 | 10-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27310656.35 | 3093.43 | 28-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126804E+10 | 9456.74 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.347584E+10 | 9596.10 | 27-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3700423.72 | 2712.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.347584E+10 | 9612.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 502779.05 | 720.15 | 27-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 502779.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 502779.05 | 720.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.936228E+10 | 55057.05 | 27-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.546752E+10 | 54726.72 | 03-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.219175E+10 | 54422.06 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217617E+09 | 32453.03 | 10-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 63049408.75 | 34561.85 | 07-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24936769.49 | 19713.69 | 03-JUN-18:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 26290029.64 | 27635.35 | 05-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 37128042.96 | 32113.21 | 24-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 56302695.82 | 31512.73 | 21-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120005E+09 | 29070.28 | 31-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.422571E+10 | 53820.16 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128133E+11 | 54940.66 | 27-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.346059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 24936769.49 | 19713.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.128133E+11 | 55057.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.172939E+10 | 8978.77 | 26-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.951498E+09 | 8846.01 | 27-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.564359E+09 | 9155.72 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52408445.49 | 2901.79 | 11-APR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1737748.32 | 2469.84 | 02-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 66084.46 | 660.84 | 29-JUN-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 330369.21 | 847.37 | 07-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1348763.26 | 2963.69 | 17-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 390667.88 | 2451.05 | 24-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24612976.59 | 2997.61 | 07-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.819723E+09 | 9101.36 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221014E+10 | 9261.26 | 26-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.635600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 66084.46 | 660.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.221014E+10 | 9261.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.277024E+10 | 9091.10 | 26-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151712E+10 | 8990.38 | 01-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.824225E+09 | 9192.20 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 72651431.39 | 3531.49 | 18-APR-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2087754.50 | 3018.49 | 02-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22093.52 | 220.94 | 29-JUN-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 266957.04 | 654.74 | 07-JUL-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1585410.73 | 3426.53 | 17-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1155399.29 | 2181.84 | 30-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 58118681.52 | 3360.92 | 24-OCT-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130643E+10 | 9105.82 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344553E+10 | 9261.17 | 26-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.999943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 22093.52 | 220.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.344553E+10 | 9261.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.746539E+09 | 2882.53 | 27-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.503094E+09 | 2870.98 | 10-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.326170E+09 | 2863.99 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52835060.80 | 2768.08 | 11-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2818464.01 | 802.09 | 10-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1019963.47 | 733.95 | 04-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1304130.15 | 888.69 | 18-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1479380.92 | 849.61 | 23-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1867936.78 | 724.61 | 03-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31957936.12 | 903.63 | 06-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.406471E+09 | 2836.18 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.929321E+09 | 2877.70 | 27-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.300488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1019963.47 | 724.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.929321E+09 | 2882.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.111230E+10 | 2875.70 | 27-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.744454E+09 | 2866.67 | 10-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.447127E+09 | 2857.19 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 66115037.86 | 2766.39 | 11-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2932851.24 | 855.23 | 27-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 989069.66 | 723.22 | 04-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1239161.89 | 845.03 | 18-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1558113.34 | 787.47 | 23-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3111659.77 | 810.97 | 23-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 64191254.12 | 2497.37 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.643088E+09 | 2829.45 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135353E+10 | 2870.86 | 27-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.444064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 989069.66 | 723.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135353E+10 | 2875.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131043E+10 | 12969.27 | 14-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.857639E+09 | 11368.62 | 27-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.664063E+09 | 13320.37 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136067E+09 | 8487.58 | 11-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13481259.16 | 4621.62 | 05-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8762695.56 | 4886.32 | 19-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7489244.03 | 4855.43 | 10-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7796623.01 | 4866.93 | 11-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4343399.16 | 4087.97 | 19-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21860723.44 | 4457.88 | 14-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.753099E+09 | 13184.91 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175080E+10 | 13388.60 | 26-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.553584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4343399.16 | 4087.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.175080E+10 | 13388.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.716861E+10 | 0.716861E+10 | 93651.60 | 03-JAN-17:00 | 93651.60 | 0.00 |
February | 0.00 | 0.00 | 0.347043E+11 | 0.347043E+11 | 128540.56 | 20-FEB-16:20 | 128540.56 | 0.00 |
March | 0.00 | 0.00 | 0.702420E+11 | 0.702420E+11 | 165916.23 | 14-MAR-17:13 | 165916.23 | 0.00 |
April | 0.00 | 0.00 | 0.215062E+12 | 0.215062E+12 | 228369.22 | 19-APR-21:00 | 228369.22 | 0.06 |
May | 0.00 | 0.00 | 0.357119E+12 | 0.355312E+12 | 257953.19 | 19-MAY-20:10 | 257953.19 | 0.37 |
June | 0.00 | 0.00 | 0.463005E+12 | 0.457562E+12 | 304214.02 | 19-JUN-18:07 | 211860.42 | 0.68 |
July | 0.00 | 0.00 | 0.618069E+12 | 0.481303E+12 | 472231.72 | 18-JUL-20:50 | 160634.94 | 1.00 |
August | 0.00 | 0.00 | 0.504514E+12 | 0.450042E+12 | 467350.66 | 01-AUG-20:50 | 217572.10 | 0.97 |
September | 0.00 | 0.00 | 0.412748E+12 | 0.354800E+12 | 346303.91 | 09-SEP-20:00 | 190090.30 | 0.81 |
October | 0.00 | 0.00 | 0.204981E+12 | 0.195856E+12 | 395164.94 | 03-OCT-20:00 | 214577.20 | 0.41 |
November | 0.00 | 0.00 | 0.433069E+11 | 0.433069E+11 | 152247.78 | 03-NOV-16:00 | 152247.78 | 0.03 |
December | 0.00 | 0.00 | 0.436754E+10 | 0.436754E+10 | 52907.71 | 23-DEC-15:00 | 52907.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.293529E+13 | 0.266972E+13 | 0.36 | |||
Minimum of Months | 0.00 | 0.00 | 0.436754E+10 | 0.436754E+10 | 52907.71 | 52907.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.618069E+12 | 0.481303E+12 | 472231.72 | 257953.19 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.122870E+10 | 0.122870E+10 | 18651.05 | 03-JAN-15:00 | 18651.05 | 0.00 |
February | 0.00 | 0.00 | 0.618797E+10 | 0.618797E+10 | 23693.24 | 20-FEB-16:00 | 23693.24 | 0.00 |
March | 0.00 | 0.00 | 0.122343E+11 | 0.122343E+11 | 24657.75 | 22-MAR-13:00 | 24657.75 | 0.00 |
April | 0.00 | 0.00 | 0.348126E+11 | 0.348126E+11 | 29774.81 | 21-APR-15:00 | 29774.81 | 0.05 |
May | 0.00 | 0.00 | 0.557264E+11 | 0.546336E+11 | 34982.72 | 24-MAY-13:00 | 27324.60 | 0.28 |
June | 0.00 | 0.00 | 0.679277E+11 | 0.656138E+11 | 40511.58 | 27-JUN-24:00 | 20042.19 | 0.58 |
July | 0.00 | 0.00 | 0.903037E+11 | 0.685052E+11 | 55414.96 | 21-JUL-08:00 | 18921.20 | 1.00 |
August | 0.00 | 0.00 | 0.760520E+11 | 0.648652E+11 | 47992.63 | 02-AUG-03:50 | 20101.26 | 0.95 |
September | 0.00 | 0.00 | 0.649768E+11 | 0.520160E+11 | 47427.38 | 22-SEP-02:00 | 17001.66 | 0.79 |
October | 0.00 | 0.00 | 0.332051E+11 | 0.304518E+11 | 42555.84 | 03-OCT-20:40 | 21350.30 | 0.41 |
November | 0.00 | 0.00 | 0.750498E+10 | 0.750498E+10 | 24036.88 | 08-NOV-15:00 | 24036.88 | 0.02 |
December | 0.00 | 0.00 | 0.724517E+09 | 0.724517E+09 | 11238.19 | 10-DEC-15:00 | 11238.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.450885E+12 | 0.398779E+12 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 0.724517E+09 | 0.724517E+09 | 11238.19 | 11238.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.903037E+11 | 0.685052E+11 | 55414.96 | 29774.81 | 1.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.671030E+09 | 0.670438E+09 | 14474.63 | 03-JAN-16:01 | 14474.63 | 0.00 |
February | 0.00 | 0.00 | 0.110388E+10 | 0.110256E+10 | 14890.92 | 20-FEB-16:01 | 14890.92 | 0.00 |
March | 0.00 | 0.00 | 0.212310E+10 | 0.211888E+10 | 15048.49 | 21-MAR-15:01 | 15048.49 | 0.01 |
April | 0.00 | 0.00 | 0.528641E+10 | 0.494931E+10 | 15387.69 | 19-APR-18:01 | 15387.69 | 0.14 |
May | 0.00 | 0.00 | 0.833939E+10 | 0.704930E+10 | 15388.05 | 20-MAY-18:01 | 15388.05 | 0.40 |
June | 0.00 | 0.00 | 0.106356E+11 | 0.828857E+10 | 15385.19 | 17-JUN-15:02 | 15385.19 | 0.70 |
July | 0.00 | 0.00 | 0.115254E+11 | 0.737916E+10 | 17009.89 | 20-JUL-08:61 | 11749.60 | 0.95 |
August | 0.00 | 0.00 | 0.104753E+11 | 0.681315E+10 | 15794.40 | 02-AUG-08:61 | 12714.78 | 0.93 |
September | 0.00 | 0.00 | 0.949976E+10 | 0.630370E+10 | 15800.63 | 09-SEP-08:61 | 12262.88 | 0.87 |
October | 0.00 | 0.00 | 0.602678E+10 | 0.435033E+10 | 15305.24 | 21-OCT-15:01 | 15305.24 | 0.56 |
November | 0.00 | 0.00 | 0.212641E+10 | 0.200685E+10 | 14930.59 | 09-NOV-16:01 | 14930.59 | 0.07 |
December | 0.00 | 0.00 | 0.369382E+09 | 0.369382E+09 | 14069.01 | 23-DEC-16:01 | 14069.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.681824E+11 | 0.514016E+11 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 0.369382E+09 | 0.369382E+09 | 14069.01 | 11749.60 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.115254E+11 | 0.828857E+10 | 17009.89 | 15388.05 | 0.95 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.131543E+09 | 0.130999E+09 | 13985.84 | 12-JAN-16:01 | 13985.84 | 0.00 |
February | 0.00 | 0.00 | 0.368761E+09 | 0.368091E+09 | 14777.23 | 20-FEB-16:01 | 14777.23 | 0.00 |
March | 0.00 | 0.00 | 0.123588E+10 | 0.123317E+10 | 14934.58 | 21-MAR-15:01 | 14934.58 | 0.00 |
April | 0.00 | 0.00 | 0.451657E+10 | 0.420757E+10 | 15270.26 | 19-APR-18:01 | 15270.26 | 0.13 |
May | 0.00 | 0.00 | 0.812970E+10 | 0.685950E+10 | 15271.49 | 20-MAY-18:01 | 15271.49 | 0.40 |
June | 0.00 | 0.00 | 0.107027E+11 | 0.838306E+10 | 15268.60 | 17-JUN-15:02 | 15268.60 | 0.70 |
July | 0.00 | 0.00 | 0.114724E+11 | 0.738141E+10 | 16518.49 | 08-JUL-08:61 | 12133.18 | 0.95 |
August | 0.00 | 0.00 | 0.988001E+10 | 0.631301E+10 | 15765.98 | 02-AUG-08:61 | 12566.41 | 0.92 |
September | 0.00 | 0.00 | 0.798041E+10 | 0.495802E+10 | 15608.10 | 09-SEP-08:61 | 12209.68 | 0.84 |
October | 0.00 | 0.00 | 0.406955E+10 | 0.271128E+10 | 15188.88 | 21-OCT-15:01 | 15188.88 | 0.50 |
November | 0.00 | 0.00 | 0.690078E+09 | 0.633956E+09 | 14818.10 | 09-NOV-16:01 | 14818.10 | 0.04 |
December | 0.00 | 0.00 | 52500207.29 | 52500207.29 | 13314.87 | 16-DEC-16:02 | 13314.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.592300E+11 | 0.432326E+11 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 52500207.29 | 52500207.29 | 13314.87 | 12133.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.114724E+11 | 0.838306E+10 | 16518.49 | 15271.49 | 0.95 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.129405E+11 | 0.129405E+11 | 36097.79 | 12-JAN-14:30 | 36097.79 | 0.00 |
February | 0.00 | 0.00 | 0.122174E+11 | 0.122174E+11 | 33506.84 | 07-FEB-13:40 | 33506.84 | 0.00 |
March | 0.00 | 0.00 | 0.844895E+10 | 0.844895E+10 | 25257.35 | 16-MAR-13:30 | 25257.35 | 0.00 |
April | 0.00 | 0.00 | 0.149179E+11 | 0.143412E+11 | 24186.74 | 04-APR-13:30 | 24186.74 | 0.04 |
May | 0.00 | 0.00 | 0.204865E+11 | 0.166138E+11 | 20983.79 | 19-MAY-17:20 | 13742.21 | 0.23 |
June | 0.00 | 0.00 | 0.305562E+11 | 0.217467E+11 | 25309.39 | 15-JUN-17:13 | 25309.39 | 0.53 |
July | 0.00 | 0.00 | 0.356368E+11 | 0.157876E+11 | 27910.78 | 26-JUL-17:20 | 18936.68 | 0.97 |
August | 0.00 | 0.00 | 0.352593E+11 | 0.186574E+11 | 30610.73 | 29-AUG-13:20 | 21886.54 | 0.88 |
September | 0.00 | 0.00 | 0.403219E+11 | 0.264905E+11 | 39123.09 | 20-SEP-15:02 | 33495.76 | 0.77 |
October | 0.00 | 0.00 | 0.338967E+11 | 0.275361E+11 | 44065.97 | 22-OCT-13:20 | 39376.11 | 0.38 |
November | 0.00 | 0.00 | 0.230354E+11 | 0.227344E+11 | 40218.59 | 09-NOV-13:50 | 40218.59 | 0.03 |
December | 0.00 | 0.00 | 0.990409E+10 | 0.990409E+10 | 30365.89 | 16-DEC-14:10 | 30365.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.277622E+12 | 0.207419E+12 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 0.844895E+10 | 0.844895E+10 | 20983.79 | 13742.21 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.403219E+11 | 0.275361E+11 | 44065.97 | 40218.59 | 0.97 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.104106E+10 | 0.100813E+10 | 52497.96 | 15-JAN-09:01 | 47194.05 | 0.01 |
February | 0.00 | 0.00 | 0.297821E+10 | 0.279047E+10 | 77279.99 | 20-FEB-09:01 | 77279.99 | 0.03 |
March | 0.00 | 0.00 | 0.813544E+10 | 0.795461E+10 | 84187.57 | 21-MAR-18:01 | 84187.57 | 0.02 |
April | 0.00 | 0.00 | 0.255835E+11 | 0.241104E+11 | 94232.94 | 21-APR-18:01 | 94232.94 | 0.09 |
May | 0.00 | 0.00 | 0.458559E+11 | 0.387127E+11 | 94325.56 | 20-MAY-18:01 | 94325.56 | 0.31 |
June | 0.00 | 0.00 | 0.617328E+11 | 0.490262E+11 | 94339.11 | 06-JUN-15:02 | 94339.11 | 0.57 |
July | 0.00 | 0.00 | 0.695542E+11 | 0.451298E+11 | 104574.26 | 08-JUL-08:61 | 74424.13 | 0.79 |
August | 0.00 | 0.00 | 0.581977E+11 | 0.371416E+11 | 95961.01 | 02-AUG-08:61 | 74834.31 | 0.75 |
September | 0.00 | 0.00 | 0.440525E+11 | 0.271598E+11 | 95012.57 | 23-SEP-08:61 | 77653.86 | 0.63 |
October | 0.00 | 0.00 | 0.244524E+11 | 0.154547E+11 | 89606.94 | 03-OCT-18:02 | 81404.23 | 0.45 |
November | 0.00 | 0.00 | 0.408310E+10 | 0.351030E+10 | 81213.16 | 08-NOV-19:01 | 81213.16 | 0.06 |
December | 0.00 | 0.00 | 0.686038E+09 | 0.686038E+09 | 66057.82 | 09-DEC-09:02 | 66057.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.346353E+12 | 0.252685E+12 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.686038E+09 | 0.686038E+09 | 52497.96 | 47194.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.695542E+11 | 0.490262E+11 | 104574.26 | 94339.11 | 0.79 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.599809E+09 | 0.596618E+09 | 12497.15 | 12-JAN-16:01 | 12497.15 | 0.00 |
February | 0.00 | 0.00 | 0.125603E+10 | 0.124417E+10 | 12982.40 | 20-FEB-16:01 | 12982.40 | 0.01 |
March | 0.00 | 0.00 | 0.216217E+10 | 0.215637E+10 | 13120.39 | 21-MAR-15:01 | 13120.39 | 0.01 |
April | 0.00 | 0.00 | 0.554281E+10 | 0.521033E+10 | 13416.25 | 27-APR-18:01 | 13416.25 | 0.15 |
May | 0.00 | 0.00 | 0.848276E+10 | 0.721765E+10 | 13415.84 | 09-MAY-18:01 | 13415.84 | 0.42 |
June | 0.00 | 0.00 | 0.108921E+11 | 0.860525E+10 | 13414.48 | 17-JUN-15:02 | 13414.48 | 0.73 |
July | 0.00 | 0.00 | 0.117779E+11 | 0.764782E+10 | 14539.09 | 19-JUL-08:62 | 9310.29 | 0.97 |
August | 0.00 | 0.00 | 0.106839E+11 | 0.707298E+10 | 13274.96 | 18-AUG-08:62 | 10888.52 | 0.96 |
September | 0.00 | 0.00 | 0.953444E+10 | 0.634253E+10 | 13414.80 | 11-SEP-18:01 | 13414.80 | 0.90 |
October | 0.00 | 0.00 | 0.561140E+10 | 0.408191E+10 | 13343.94 | 21-OCT-15:01 | 13343.94 | 0.56 |
November | 0.00 | 0.00 | 0.200246E+10 | 0.191424E+10 | 13017.35 | 09-NOV-16:01 | 13017.35 | 0.06 |
December | 0.00 | 0.00 | 0.416595E+09 | 0.416595E+09 | 12106.53 | 16-DEC-09:02 | 12106.53 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.689624E+11 | 0.525065E+11 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 0.416595E+09 | 0.416595E+09 | 12106.53 | 9310.29 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.117779E+11 | 0.860525E+10 | 14539.09 | 13416.25 | 0.97 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 66604105.40 | 65894318.75 | 10246.66 | 04-JAN-09:02 | 10246.66 | 0.00 |
February | 0.00 | 0.00 | 0.435069E+09 | 0.425738E+09 | 12459.22 | 21-FEB-16:01 | 12459.22 | 0.01 |
March | 0.00 | 0.00 | 0.121903E+10 | 0.121532E+10 | 12952.42 | 22-MAR-15:01 | 12952.42 | 0.01 |
April | 0.00 | 0.00 | 0.471166E+10 | 0.440141E+10 | 13307.96 | 27-APR-18:01 | 13307.96 | 0.14 |
May | 0.00 | 0.00 | 0.825733E+10 | 0.700053E+10 | 13307.54 | 09-MAY-18:01 | 13307.54 | 0.42 |
June | 0.00 | 0.00 | 0.109533E+11 | 0.868780E+10 | 13306.23 | 17-JUN-15:02 | 13306.23 | 0.73 |
July | 0.00 | 0.00 | 0.117174E+11 | 0.763290E+10 | 14375.65 | 19-JUL-08:62 | 9251.62 | 0.97 |
August | 0.00 | 0.00 | 0.100750E+11 | 0.650388E+10 | 13245.32 | 16-AUG-15:02 | 11547.91 | 0.96 |
September | 0.00 | 0.00 | 0.799423E+10 | 0.501261E+10 | 13306.38 | 11-SEP-18:01 | 13306.38 | 0.88 |
October | 0.00 | 0.00 | 0.360864E+10 | 0.244157E+10 | 13235.82 | 21-OCT-15:01 | 13235.82 | 0.49 |
November | 0.00 | 0.00 | 0.632305E+09 | 0.591539E+09 | 12625.58 | 09-NOV-16:01 | 12625.58 | 0.03 |
December | 0.00 | 0.00 | 47021796.35 | 47021796.35 | 11256.06 | 09-DEC-09:02 | 11256.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.597176E+11 | 0.440262E+11 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 47021796.35 | 47021796.35 | 10246.66 | 9251.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.117174E+11 | 0.868780E+10 | 14375.65 | 13307.96 | 0.97 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.123977E+09 | 0.123824E+09 | 3848.79 | 03-JAN-16:01 | 3848.79 | 0.00 |
February | 0.00 | 0.00 | 0.218500E+09 | 0.218313E+09 | 3959.53 | 20-FEB-16:01 | 3959.53 | 0.00 |
March | 0.00 | 0.00 | 0.432427E+09 | 0.432389E+09 | 4001.44 | 21-MAR-15:01 | 4001.44 | 0.00 |
April | 0.00 | 0.00 | 0.120958E+10 | 0.112591E+10 | 4091.51 | 19-APR-18:01 | 4091.51 | 0.14 |
May | 0.00 | 0.00 | 0.201804E+10 | 0.167916E+10 | 4091.68 | 20-MAY-18:01 | 4091.68 | 0.41 |
June | 0.00 | 0.00 | 0.273804E+10 | 0.211493E+10 | 4090.98 | 17-JUN-15:02 | 4090.98 | 0.70 |
July | 0.00 | 0.00 | 0.296315E+10 | 0.187179E+10 | 4689.66 | 20-JUL-08:61 | 2995.83 | 0.95 |
August | 0.00 | 0.00 | 0.264212E+10 | 0.170211E+10 | 4316.95 | 02-AUG-08:61 | 3263.67 | 0.93 |
September | 0.00 | 0.00 | 0.230778E+10 | 0.149588E+10 | 4337.65 | 09-SEP-08:61 | 3115.94 | 0.87 |
October | 0.00 | 0.00 | 0.130232E+10 | 0.932957E+09 | 4069.74 | 21-OCT-15:01 | 4069.74 | 0.48 |
November | 0.00 | 0.00 | 0.393475E+09 | 0.374931E+09 | 3970.08 | 09-NOV-16:01 | 3970.08 | 0.04 |
December | 0.00 | 0.00 | 68596471.03 | 68596471.03 | 3740.98 | 23-DEC-16:01 | 3740.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.164180E+11 | 0.121408E+11 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 68596471.03 | 68596471.03 | 3740.98 | 2995.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.296315E+10 | 0.211493E+10 | 4689.66 | 4091.68 | 0.95 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 19453280.16 | 19308246.28 | 3669.60 | 12-JAN-16:01 | 3669.60 | 0.00 |
February | 0.00 | 0.00 | 63847607.68 | 63727887.10 | 3924.17 | 20-FEB-16:01 | 3924.17 | 0.00 |
March | 0.00 | 0.00 | 0.234176E+09 | 0.234133E+09 | 3965.90 | 21-MAR-15:01 | 3965.90 | 0.00 |
April | 0.00 | 0.00 | 0.101414E+10 | 0.939172E+09 | 4055.30 | 19-APR-18:01 | 4055.30 | 0.13 |
May | 0.00 | 0.00 | 0.196328E+10 | 0.162926E+10 | 4055.38 | 20-MAY-18:01 | 4055.38 | 0.41 |
June | 0.00 | 0.00 | 0.275526E+10 | 0.213764E+10 | 4054.67 | 17-JUN-15:02 | 4054.67 | 0.70 |
July | 0.00 | 0.00 | 0.294932E+10 | 0.186731E+10 | 4560.54 | 08-JUL-08:61 | 3114.25 | 0.95 |
August | 0.00 | 0.00 | 0.248524E+10 | 0.156596E+10 | 4316.69 | 02-AUG-08:61 | 3224.56 | 0.92 |
September | 0.00 | 0.00 | 0.190710E+10 | 0.115134E+10 | 4273.28 | 23-SEP-08:61 | 3250.60 | 0.84 |
October | 0.00 | 0.00 | 0.817569E+09 | 0.542648E+09 | 4033.50 | 21-OCT-15:01 | 4033.50 | 0.40 |
November | 0.00 | 0.00 | 0.107922E+09 | 0.100690E+09 | 3934.91 | 09-NOV-16:01 | 3934.91 | 0.02 |
December | 0.00 | 0.00 | 8203954.65 | 8203954.65 | 3444.38 | 16-DEC-16:02 | 3444.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143255E+11 | 0.102594E+11 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 8203954.65 | 8203954.65 | 3444.38 | 3114.25 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.294932E+10 | 0.213764E+10 | 4560.54 | 4055.38 | 0.95 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.396812E+10 | 0.395843E+10 | 17001.46 | 03-JAN-16:01 | 17001.46 | 0.01 |
February | 0.00 | 0.00 | 0.398326E+10 | 0.396888E+10 | 17490.48 | 20-FEB-16:01 | 17490.48 | 0.01 |
March | 0.00 | 0.00 | 0.384131E+10 | 0.382890E+10 | 17675.70 | 21-MAR-15:01 | 17675.70 | 0.01 |
April | 0.00 | 0.00 | 0.622106E+10 | 0.577389E+10 | 18067.01 | 21-APR-18:01 | 18067.01 | 0.15 |
May | 0.00 | 0.00 | 0.858777E+10 | 0.693302E+10 | 18070.33 | 12-MAY-15:02 | 18070.33 | 0.42 |
June | 0.00 | 0.00 | 0.116712E+11 | 0.867014E+10 | 18068.67 | 11-JUN-18:01 | 18068.67 | 0.70 |
July | 0.00 | 0.00 | 0.135021E+11 | 0.818210E+10 | 20926.61 | 20-JUL-08:61 | 12856.85 | 0.93 |
August | 0.00 | 0.00 | 0.129933E+11 | 0.829040E+10 | 18902.72 | 02-AUG-08:61 | 14451.73 | 0.93 |
September | 0.00 | 0.00 | 0.131179E+11 | 0.899396E+10 | 19046.99 | 09-SEP-08:61 | 14157.05 | 0.87 |
October | 0.00 | 0.00 | 0.103338E+11 | 0.809790E+10 | 17976.73 | 21-OCT-15:01 | 17976.73 | 0.58 |
November | 0.00 | 0.00 | 0.625146E+10 | 0.605658E+10 | 17534.77 | 09-NOV-16:01 | 17534.77 | 0.09 |
December | 0.00 | 0.00 | 0.354599E+10 | 0.354579E+10 | 16559.95 | 10-DEC-16:01 | 16559.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.980173E+11 | 0.763000E+11 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 0.354599E+10 | 0.354579E+10 | 16559.95 | 12856.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.135021E+11 | 0.899396E+10 | 20926.61 | 18070.33 | 0.93 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 18050.00 | 207629.42 | 17-JAN-09:01 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 11786.58 | 149433.58 | 17-FEB-09:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 6879.71 | 121670.79 | 31-MAR-04:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2210.61 | 126183.98 | 13-APR-04:53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 153.75 | 78417.52 | 02-MAY-18:04 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.72 | 23758.49 | 01-JUN-08:04 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 17.03 | 21751.99 | 05-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 21.74 | 36268.08 | 24-AUG-08:04 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 197.94 | 46455.89 | 25-SEP-05:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1033.12 | 79268.89 | 25-OCT-05:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10364.14 | 151510.14 | 26-NOV-16:01 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 19119.25 | 158292.18 | 02-DEC-19:05 |
Annual Sum or Average | 0.00 | 5800.76 | ||||
Minimum of Months | 0.00 | 0.00 | 17.03 | 21751.99 | ||
Maximum of Months | 0.00 | 0.00 | 19119.25 | 207629.42 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 13096.28 | 191318.58 | 03-JAN-16:03 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 29542.23 | 312525.30 | 20-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 44922.07 | 357836.17 | 14-MAR-18:01 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 128342.83 | 432476.62 | 19-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 202109.21 | 446198.98 | 15-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 270306.07 | 526157.01 | 18-JUN-18:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 335066.90 | 629435.00 | 18-JUL-20:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 280392.31 | 594876.37 | 01-AUG-20:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 243483.05 | 510544.37 | 22-SEP-08:61 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 128038.85 | 532061.36 | 03-OCT-20:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 38324.10 | 334455.76 | 09-NOV-16:01 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 10057.67 | 96231.98 | 23-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 144287.80 | 0.00 | ||||
Minimum of Months | 10057.67 | 96231.98 | 0.00 | 0.00 | ||
Maximum of Months | 335066.90 | 629435.00 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25402.54 | 63640.46 | 25-JAN-07:01 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 25416.60 | 62862.44 | 24-FEB-07:51 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 24577.96 | 56141.27 | 13-MAR-06:25 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23041.97 | 52370.67 | 13-APR-06:24 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 21279.74 | 44499.86 | 01-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 19745.25 | 40781.93 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18838.55 | 38088.58 | 03-JUL-06:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18864.24 | 38237.03 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19752.80 | 43158.93 | 25-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21280.51 | 49130.40 | 25-OCT-06:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 23022.73 | 56909.33 | 21-NOV-07:31 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 24528.32 | 58382.95 | 10-DEC-08:11 |
Annual Sum or Average | 0.00 | 22127.33 | ||||
Minimum of Months | 0.00 | 0.00 | 18838.55 | 38088.58 | ||
Maximum of Months | 0.00 | 0.00 | 25416.60 | 63640.46 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 1.01 | 2194.93 | 01-JAN-00:05 | 1.01 |
February | 0.530997E+10 | 1.01 | 2194.93 | 01-FEB-00:05 | 1.01 |
March | 0.587890E+10 | 1.01 | 2194.93 | 01-MAR-00:10 | 1.01 |
April | 0.568926E+10 | 1.01 | 2194.93 | 01-APR-00:10 | 1.02 |
May | 0.587890E+10 | 1.01 | 2194.93 | 01-MAY-00:10 | 1.01 |
June | 0.568926E+10 | 1.01 | 2194.93 | 01-JUN-00:10 | 1.01 |
July | 0.587890E+10 | 1.00 | 2194.93 | 01-JUL-00:10 | 1.00 |
August | 0.587890E+10 | 1.00 | 2194.93 | 01-AUG-00:10 | 1.00 |
September | 0.568926E+10 | 1.00 | 2194.93 | 01-SEP-00:10 | 1.00 |
October | 0.587890E+10 | 1.01 | 2194.93 | 01-OCT-00:10 | 1.01 |
November | 0.568926E+10 | 1.01 | 2194.93 | 01-NOV-00:10 | 1.01 |
December | 0.587890E+10 | 1.01 | 2194.93 | 01-DEC-00:05 | 1.01 |
Annual Sum or Average | 0.692193E+11 | 1.01 | |||
Minimum of Months | 0.530997E+10 | 1.00 | 2194.93 | 1.00 | |
Maximum of Months | 0.587890E+10 | 1.01 | 2194.93 | 1.02 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.373875E+11 | 0.91 | 43728.93 | 09-JAN-22:45 | 1.82 |
February | 0.329253E+11 | 0.90 | 44052.41 | 08-FEB-21:40 | 1.83 |
March | 0.366613E+11 | 0.91 | 33552.02 | 17-MAR-21:27 | 1.54 |
April | 0.376419E+11 | 0.94 | 34542.94 | 22-APR-05:15 | 1.57 |
May | 0.419622E+11 | 0.97 | 34988.72 | 31-MAY-21:10 | 1.57 |
June | 0.445456E+11 | 1.02 | 37699.29 | 15-JUN-21:10 | 1.65 |
July | 0.467919E+11 | 1.02 | 40046.31 | 26-JUL-21:10 | 1.70 |
August | 0.475880E+11 | 1.03 | 42560.53 | 07-AUG-21:10 | 1.77 |
September | 0.455316E+11 | 1.03 | 42767.10 | 22-SEP-21:10 | 1.77 |
October | 0.433921E+11 | 0.99 | 42196.05 | 05-OCT-21:10 | 1.76 |
November | 0.391589E+11 | 0.95 | 43551.85 | 18-NOV-04:25 | 1.82 |
December | 0.383637E+11 | 0.93 | 44329.05 | 06-DEC-22:55 | 1.84 |
Annual Sum or Average | 0.491950E+12 | 0.97 | |||
Minimum of Months | 0.329253E+11 | 0.90 | 33552.02 | 1.54 | |
Maximum of Months | 0.475880E+11 | 1.03 | 44329.05 | 1.84 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.31 | 76.61 | 01-JAN-00:05 | 0.31 |
February | 0.185347E+09 | 0.31 | 76.61 | 01-FEB-00:05 | 0.31 |
March | 0.205205E+09 | 0.31 | 76.61 | 01-MAR-00:10 | 0.31 |
April | 0.198586E+09 | 0.31 | 76.61 | 01-APR-00:10 | 0.31 |
May | 0.205205E+09 | 0.31 | 76.61 | 01-MAY-00:10 | 0.31 |
June | 0.198586E+09 | 0.30 | 76.61 | 01-JUN-00:10 | 0.31 |
July | 0.205205E+09 | 0.30 | 76.61 | 01-JUL-00:10 | 0.30 |
August | 0.205205E+09 | 0.30 | 76.61 | 01-AUG-00:10 | 0.30 |
September | 0.198586E+09 | 0.30 | 76.61 | 01-SEP-00:10 | 0.30 |
October | 0.205205E+09 | 0.30 | 76.61 | 01-OCT-00:10 | 0.31 |
November | 0.198586E+09 | 0.31 | 76.61 | 01-NOV-00:10 | 0.31 |
December | 0.205205E+09 | 0.31 | 76.61 | 01-DEC-00:05 | 0.31 |
Annual Sum or Average | 0.241613E+10 | 0.31 | |||
Minimum of Months | 0.185347E+09 | 0.30 | 76.61 | 0.30 | |
Maximum of Months | 0.205205E+09 | 0.31 | 76.61 | 0.31 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.22 | 612.92 | 01-JAN-07:03 | 0.30 |
February | 0.105030E+10 | 0.22 | 612.92 | 01-FEB-07:05 | 0.31 |
March | 0.116283E+10 | 0.22 | 612.92 | 01-MAR-07:05 | 0.31 |
April | 0.112532E+10 | 0.22 | 612.92 | 01-APR-06:05 | 0.31 |
May | 0.116283E+10 | 0.22 | 612.92 | 01-MAY-06:05 | 0.31 |
June | 0.112532E+10 | 0.22 | 612.92 | 01-JUN-06:05 | 0.31 |
July | 0.116283E+10 | 0.21 | 612.92 | 01-JUL-06:05 | 0.30 |
August | 0.116283E+10 | 0.21 | 612.92 | 01-AUG-06:05 | 0.30 |
September | 0.112532E+10 | 0.21 | 612.92 | 01-SEP-06:05 | 0.30 |
October | 0.116283E+10 | 0.22 | 612.92 | 01-OCT-06:10 | 0.31 |
November | 0.112532E+10 | 0.22 | 612.92 | 01-NOV-06:10 | 0.30 |
December | 0.116283E+10 | 0.22 | 612.92 | 01-DEC-07:01 | 0.31 |
Annual Sum or Average | 0.136914E+11 | 0.22 | |||
Minimum of Months | 0.105030E+10 | 0.21 | 612.92 | 0.30 | |
Maximum of Months | 0.116283E+10 | 0.22 | 612.92 | 0.31 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.165503E+09 | 0.50 | 806.14 | 01-JAN-16:02 | 0.66 |
February | 0.148239E+09 | 0.51 | 806.14 | 01-FEB-09:01 | 0.66 |
March | 0.181015E+09 | 0.53 | 806.14 | 01-MAR-09:01 | 0.66 |
April | 0.310336E+09 | 0.58 | 806.14 | 01-APR-15:01 | 0.66 |
May | 0.452199E+09 | 0.61 | 806.14 | 01-MAY-15:01 | 0.67 |
June | 0.560091E+09 | 0.63 | 806.14 | 01-JUN-08:61 | 0.66 |
July | 0.550914E+09 | 0.63 | 806.14 | 01-JUL-08:62 | 0.66 |
August | 0.523339E+09 | 0.62 | 806.14 | 01-AUG-08:61 | 0.66 |
September | 0.479059E+09 | 0.62 | 806.14 | 01-SEP-08:62 | 0.66 |
October | 0.334101E+09 | 0.58 | 806.14 | 01-OCT-08:62 | 0.66 |
November | 0.191278E+09 | 0.54 | 806.14 | 02-NOV-15:02 | 0.66 |
December | 0.174495E+09 | 0.49 | 806.14 | 01-DEC-16:01 | 0.66 |
Annual Sum or Average | 0.407057E+10 | 0.57 | |||
Minimum of Months | 0.148239E+09 | 0.49 | 806.14 | 0.66 | |
Maximum of Months | 0.560091E+09 | 0.63 | 806.14 | 0.67 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.189970E+09 | 0.47 | 800.01 | 01-JAN-16:02 | 0.66 |
February | 0.143895E+09 | 0.48 | 800.01 | 01-FEB-09:01 | 0.66 |
March | 0.148275E+09 | 0.49 | 800.01 | 01-MAR-09:01 | 0.66 |
April | 0.271593E+09 | 0.55 | 800.01 | 01-APR-15:01 | 0.66 |
May | 0.441908E+09 | 0.60 | 800.01 | 01-MAY-15:01 | 0.67 |
June | 0.566301E+09 | 0.63 | 800.01 | 01-JUN-08:61 | 0.66 |
July | 0.549087E+09 | 0.63 | 800.01 | 01-JUL-08:62 | 0.66 |
August | 0.491751E+09 | 0.61 | 800.01 | 01-AUG-08:61 | 0.66 |
September | 0.401854E+09 | 0.60 | 800.01 | 01-SEP-08:62 | 0.66 |
October | 0.232173E+09 | 0.53 | 800.01 | 01-OCT-08:62 | 0.66 |
November | 0.142048E+09 | 0.49 | 800.01 | 02-NOV-15:02 | 0.66 |
December | 0.220033E+09 | 0.48 | 800.01 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.379889E+10 | 0.55 | |||
Minimum of Months | 0.142048E+09 | 0.47 | 800.01 | 0.66 | |
Maximum of Months | 0.566301E+09 | 0.63 | 800.01 | 0.67 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.681260E+09 | 0.26 | 1954.34 | 12-JAN-14:30 | 0.66 |
February | 0.621786E+09 | 0.27 | 1462.97 | 07-FEB-13:40 | 0.67 |
March | 0.457031E+09 | 0.24 | 1122.33 | 16-MAR-13:30 | 0.67 |
April | 0.771044E+09 | 0.39 | 1047.12 | 04-APR-13:30 | 0.67 |
May | 0.102602E+10 | 0.50 | 998.41 | 19-MAY-20:10 | 0.66 |
June | 0.145223E+10 | 0.62 | 1094.54 | 08-JUN-17:12 | 0.66 |
July | 0.152923E+10 | 0.64 | 1102.79 | 26-JUL-17:20 | 0.66 |
August | 0.156097E+10 | 0.61 | 1239.02 | 27-AUG-13:40 | 0.66 |
September | 0.177638E+10 | 0.62 | 2242.15 | 17-SEP-13:40 | 0.66 |
October | 0.165783E+10 | 0.50 | 2636.61 | 29-OCT-12:30 | 0.66 |
November | 0.117216E+10 | 0.34 | 2079.44 | 10-NOV-13:20 | 0.66 |
December | 0.525533E+09 | 0.23 | 1396.44 | 16-DEC-14:10 | 0.67 |
Annual Sum or Average | 0.132315E+11 | 0.43 | |||
Minimum of Months | 0.457031E+09 | 0.23 | 998.41 | 0.66 | |
Maximum of Months | 0.177638E+10 | 0.64 | 2636.61 | 0.67 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.831092E+09 | 0.47 | 4879.01 | 02-JAN-09:01 | 0.66 |
February | 0.666360E+09 | 0.47 | 4879.01 | 01-FEB-09:01 | 0.66 |
March | 0.763948E+09 | 0.47 | 4879.01 | 01-MAR-16:01 | 0.67 |
April | 0.147878E+10 | 0.47 | 4879.01 | 01-APR-08:62 | 0.67 |
May | 0.250865E+10 | 0.48 | 4879.01 | 01-MAY-15:01 | 0.67 |
June | 0.327061E+10 | 0.53 | 4879.01 | 01-JUN-08:61 | 0.66 |
July | 0.329982E+10 | 0.52 | 4879.01 | 01-JUL-08:62 | 0.66 |
August | 0.281720E+10 | 0.50 | 4879.01 | 01-AUG-08:61 | 0.66 |
September | 0.211957E+10 | 0.47 | 4879.01 | 01-SEP-08:62 | 0.66 |
October | 0.134171E+10 | 0.47 | 4879.01 | 01-OCT-08:62 | 0.66 |
November | 0.677109E+09 | 0.47 | 4879.01 | 08-NOV-19:01 | 0.66 |
December | 0.989103E+09 | 0.47 | 4879.01 | 01-DEC-16:01 | 0.67 |
Annual Sum or Average | 0.207640E+11 | 0.48 | |||
Minimum of Months | 0.666360E+09 | 0.47 | 4879.01 | 0.66 | |
Maximum of Months | 0.329982E+10 | 0.53 | 4879.01 | 0.67 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.152169E+09 | 0.48 | 702.52 | 01-JAN-16:02 | 0.66 |
February | 0.144851E+09 | 0.52 | 702.52 | 03-FEB-16:01 | 0.67 |
March | 0.176808E+09 | 0.55 | 702.52 | 01-MAR-09:01 | 0.66 |
April | 0.322023E+09 | 0.62 | 702.52 | 01-APR-08:62 | 0.66 |
May | 0.462263E+09 | 0.64 | 702.52 | 01-MAY-08:62 | 0.67 |
June | 0.577343E+09 | 0.65 | 702.52 | 01-JUN-08:61 | 0.66 |
July | 0.569633E+09 | 0.64 | 702.52 | 01-JUL-08:62 | 0.66 |
August | 0.530518E+09 | 0.64 | 702.52 | 01-AUG-08:61 | 0.66 |
September | 0.481739E+09 | 0.64 | 702.52 | 01-SEP-08:62 | 0.66 |
October | 0.314820E+09 | 0.59 | 702.52 | 01-OCT-08:62 | 0.66 |
November | 0.182810E+09 | 0.56 | 702.52 | 02-NOV-15:02 | 0.66 |
December | 0.161603E+09 | 0.47 | 702.52 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.407658E+10 | 0.58 | |||
Minimum of Months | 0.144851E+09 | 0.47 | 702.52 | 0.66 | |
Maximum of Months | 0.577343E+09 | 0.65 | 702.52 | 0.67 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.171676E+09 | 0.47 | 696.83 | 05-JAN-16:01 | 0.67 |
February | 0.127355E+09 | 0.47 | 696.83 | 01-FEB-16:02 | 0.67 |
March | 0.136740E+09 | 0.47 | 696.83 | 01-MAR-16:01 | 0.67 |
April | 0.278741E+09 | 0.59 | 696.83 | 01-APR-08:62 | 0.66 |
May | 0.452523E+09 | 0.64 | 696.83 | 01-MAY-08:62 | 0.67 |
June | 0.582980E+09 | 0.65 | 696.83 | 01-JUN-08:61 | 0.66 |
July | 0.568413E+09 | 0.64 | 696.83 | 01-JUL-08:62 | 0.66 |
August | 0.500896E+09 | 0.63 | 696.83 | 01-AUG-08:61 | 0.66 |
September | 0.399832E+09 | 0.63 | 696.83 | 01-SEP-08:62 | 0.66 |
October | 0.207256E+09 | 0.53 | 696.83 | 01-OCT-08:62 | 0.66 |
November | 0.129944E+09 | 0.47 | 696.83 | 03-NOV-08:62 | 0.66 |
December | 0.197138E+09 | 0.48 | 696.83 | 02-DEC-16:01 | 0.67 |
Annual Sum or Average | 0.375349E+10 | 0.56 | |||
Minimum of Months | 0.127355E+09 | 0.47 | 696.83 | 0.66 | |
Maximum of Months | 0.582980E+09 | 0.65 | 696.83 | 0.67 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 53361073.07 | 0.50 | 214.40 | 01-JAN-16:02 | 0.66 |
February | 45611969.03 | 0.51 | 214.40 | 01-FEB-09:01 | 0.66 |
March | 49595419.05 | 0.52 | 214.40 | 01-MAR-09:01 | 0.66 |
April | 74401069.33 | 0.58 | 214.40 | 01-APR-15:01 | 0.66 |
May | 0.110663E+09 | 0.61 | 214.40 | 01-MAY-15:01 | 0.67 |
June | 0.145772E+09 | 0.63 | 214.40 | 01-JUN-08:61 | 0.66 |
July | 0.143378E+09 | 0.62 | 214.40 | 01-JUL-08:62 | 0.66 |
August | 0.133104E+09 | 0.62 | 214.40 | 01-AUG-08:61 | 0.66 |
September | 0.117858E+09 | 0.61 | 214.40 | 01-SEP-08:62 | 0.66 |
October | 75554380.00 | 0.57 | 214.40 | 01-OCT-08:62 | 0.66 |
November | 50895255.91 | 0.54 | 214.40 | 02-NOV-08:62 | 0.66 |
December | 57631266.88 | 0.49 | 214.40 | 02-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.105783E+10 | 0.57 | |||
Minimum of Months | 45611969.03 | 0.49 | 214.40 | 0.66 | |
Maximum of Months | 0.145772E+09 | 0.63 | 214.40 | 0.67 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 63458911.31 | 0.50 | 212.49 | 01-JAN-09:02 | 0.66 |
February | 47850289.74 | 0.48 | 212.49 | 01-FEB-09:01 | 0.66 |
March | 44324421.07 | 0.48 | 212.49 | 01-MAR-09:01 | 0.66 |
April | 64748214.52 | 0.55 | 212.49 | 01-APR-15:01 | 0.66 |
May | 0.108127E+09 | 0.60 | 212.49 | 01-MAY-15:01 | 0.67 |
June | 0.147304E+09 | 0.63 | 212.49 | 01-JUN-08:61 | 0.66 |
July | 0.143110E+09 | 0.63 | 212.49 | 01-JUL-08:62 | 0.66 |
August | 0.124907E+09 | 0.61 | 212.49 | 01-AUG-08:61 | 0.66 |
September | 97469965.77 | 0.60 | 212.49 | 01-SEP-08:62 | 0.66 |
October | 51841072.63 | 0.52 | 212.49 | 01-OCT-15:02 | 0.66 |
November | 46946955.52 | 0.49 | 212.49 | 02-NOV-08:62 | 0.66 |
December | 72040824.60 | 0.51 | 212.49 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.101213E+10 | 0.55 | |||
Minimum of Months | 44324421.07 | 0.48 | 212.49 | 0.66 | |
Maximum of Months | 0.147304E+09 | 0.63 | 212.49 | 0.67 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.316855E+09 | 0.57 | 941.53 | 01-JAN-16:02 | 0.66 |
February | 0.287819E+09 | 0.57 | 941.53 | 01-FEB-16:02 | 0.67 |
March | 0.276185E+09 | 0.56 | 941.53 | 01-MAR-16:01 | 0.67 |
April | 0.364705E+09 | 0.59 | 941.53 | 01-APR-15:01 | 0.66 |
May | 0.467782E+09 | 0.60 | 941.53 | 01-MAY-15:01 | 0.67 |
June | 0.606893E+09 | 0.62 | 941.53 | 01-JUN-08:61 | 0.66 |
July | 0.630030E+09 | 0.61 | 941.53 | 01-JUL-08:62 | 0.66 |
August | 0.630223E+09 | 0.61 | 941.53 | 01-AUG-08:61 | 0.66 |
September | 0.661254E+09 | 0.62 | 941.53 | 01-SEP-08:62 | 0.66 |
October | 0.567603E+09 | 0.60 | 941.53 | 01-OCT-08:62 | 0.66 |
November | 0.407948E+09 | 0.58 | 941.53 | 02-NOV-15:02 | 0.66 |
December | 0.313715E+09 | 0.56 | 941.53 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.553101E+10 | 0.59 | |||
Minimum of Months | 0.276185E+09 | 0.56 | 941.53 | 0.66 | |
Maximum of Months | 0.661254E+09 | 0.62 | 941.53 | 0.67 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.410068E+09 | 0.369062E+09 | 695.75 | 09-JAN-09:01 | 626.18 | 626.18 | 56.45 | 1.16 |
February | 0.249937E+09 | 0.224943E+09 | 646.47 | 16-FEB-00:13 | 581.82 | 581.82 | 48.35 | 1.01 |
March | 0.166167E+09 | 0.149550E+09 | 594.79 | 05-MAR-04:33 | 535.31 | 535.31 | 54.53 | 0.87 |
April | 37937027.69 | 34143324.92 | 609.79 | 13-APR-04:53 | 548.81 | 548.81 | 47.23 | 0.91 |
May | 2525310.50 | 2272779.45 | 351.57 | 02-MAY-18:04 | 316.41 | 316.41 | 35.51 | 0.43 |
June | 558713.40 | 502842.06 | 262.29 | 30-JUN-08:04 | 236.06 | 236.06 | 61.94 | 0.30 |
July | 612388.47 | 551149.62 | 251.77 | 05-JUL-08:05 | 226.59 | 226.59 | 61.18 | 0.29 |
August | 726291.35 | 653662.21 | 368.33 | 24-AUG-08:04 | 331.50 | 331.50 | 60.05 | 0.45 |
September | 3033619.56 | 2730257.61 | 318.27 | 21-SEP-08:04 | 286.44 | 286.44 | 58.96 | 0.38 |
October | 20532065.36 | 18478858.82 | 505.73 | 25-OCT-03:10 | 455.15 | 455.15 | 64.30 | 0.68 |
November | 0.233943E+09 | 0.210549E+09 | 649.65 | 26-NOV-23:25 | 584.68 | 584.68 | 49.70 | 1.02 |
December | 0.443344E+09 | 0.399010E+09 | 636.07 | 14-DEC-24:00 | 572.46 | 572.46 | 48.21 | 0.98 |
Annual Sum or Average | 0.156938E+10 | 0.141245E+10 | ||||||
Minimum of Months | 558713.40 | 502842.06 | 251.77 | 226.59 | 226.59 | 35.51 | 0.29 | |
Maximum of Months | 0.443344E+09 | 0.399010E+09 | 695.75 | 626.18 | 626.18 | 64.30 | 1.16 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.108575E+10 | 0.977172E+09 | 3128.96 | 12-JAN-16:03 | 2816.07 | 2816.07 | 7.92 | 6.78 |
February | 0.165626E+10 | 0.149064E+10 | 3752.28 | 20-FEB-16:01 | 3377.05 | 3377.05 | 7.25 | 9.48 |
March | 0.251442E+10 | 0.226298E+10 | 3807.62 | 14-MAR-18:01 | 3426.85 | 3426.85 | 7.26 | 9.79 |
April | 0.549792E+10 | 0.494813E+10 | 4397.79 | 28-APR-18:03 | 3958.01 | 3958.01 | 6.73 | 15.09 |
May | 0.799454E+10 | 0.719508E+10 | 4498.39 | 19-MAY-18:05 | 4048.55 | 4048.55 | 6.73 | 16.69 |
June | 0.935289E+10 | 0.841760E+10 | 4632.79 | 05-JUN-18:03 | 4169.51 | 4169.51 | 6.73 | 18.94 |
July | 0.103500E+11 | 0.931503E+10 | 4639.84 | 18-JUL-20:50 | 4175.85 | 4175.85 | 7.59 | 19.05 |
August | 0.984386E+10 | 0.885947E+10 | 4597.38 | 01-AUG-21:00 | 4137.64 | 4137.64 | 7.38 | 18.37 |
September | 0.883920E+10 | 0.795528E+10 | 4558.93 | 18-SEP-19:10 | 4103.04 | 4103.04 | 6.73 | 17.73 |
October | 0.601657E+10 | 0.541491E+10 | 4497.73 | 03-OCT-20:00 | 4047.96 | 4047.96 | 7.24 | 16.68 |
November | 0.239202E+10 | 0.215282E+10 | 4194.29 | 03-NOV-15:50 | 3774.86 | 3774.86 | 7.17 | 12.65 |
December | 0.851704E+09 | 0.766533E+09 | 2426.68 | 16-DEC-16:03 | 2184.01 | 2184.01 | 8.40 | 4.67 |
Annual Sum or Average | 0.663952E+11 | 0.597557E+11 | ||||||
Minimum of Months | 0.851704E+09 | 0.766533E+09 | 2426.68 | 2184.01 | 2184.01 | 6.73 | 4.67 | |
Maximum of Months | 0.103500E+11 | 0.931503E+10 | 4639.84 | 4175.85 | 4175.85 | 8.40 | 19.05 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.683248E+10 | 0.614924E+10 | 3950.69 | 01-JAN-00:05 | 3555.62 | 3555.62 | 8.41 | 27.69 |
February | 0.720496E+10 | 0.648446E+10 | 3950.69 | 01-FEB-04:10 | 3555.62 | 3555.62 | 8.40 | 27.69 |
March | 0.865409E+10 | 0.778868E+10 | 3950.69 | 01-MAR-04:10 | 3555.62 | 3555.62 | 8.40 | 27.69 |
April | 0.100289E+11 | 0.902601E+10 | 3950.69 | 01-APR-00:10 | 3555.62 | 3555.62 | 8.43 | 27.69 |
May | 0.105754E+11 | 0.951783E+10 | 3950.69 | 01-MAY-00:10 | 3555.62 | 3555.62 | 8.85 | 27.69 |
June | 0.102402E+11 | 0.921617E+10 | 3950.69 | 01-JUN-00:10 | 3555.62 | 3555.62 | 8.99 | 27.69 |
July | 0.105815E+11 | 0.952337E+10 | 3950.69 | 01-JUL-00:10 | 3555.62 | 3555.62 | 8.94 | 27.69 |
August | 0.105815E+11 | 0.952337E+10 | 3950.69 | 01-AUG-00:10 | 3555.62 | 3555.62 | 9.29 | 27.69 |
September | 0.102402E+11 | 0.921617E+10 | 3950.69 | 01-SEP-00:10 | 3555.62 | 3555.62 | 9.11 | 27.69 |
October | 0.104626E+11 | 0.941635E+10 | 3950.69 | 01-OCT-00:10 | 3555.62 | 3555.62 | 8.79 | 27.69 |
November | 0.787238E+10 | 0.708514E+10 | 3950.69 | 01-NOV-00:10 | 3555.62 | 3555.62 | 8.47 | 27.69 |
December | 0.666235E+10 | 0.599611E+10 | 3950.69 | 01-DEC-04:33 | 3555.62 | 3555.62 | 8.42 | 27.69 |
Annual Sum or Average | 0.109937E+12 | 0.989429E+11 | ||||||
Minimum of Months | 0.666235E+10 | 0.599611E+10 | 3950.69 | 3555.62 | 3555.62 | 8.40 | 27.69 | |
Maximum of Months | 0.105815E+11 | 0.952337E+10 | 3950.69 | 3555.62 | 3555.62 | 9.29 | 27.69 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 34.18 | 0.08 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 49.49 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:10 | 14.37 | 14.37 | 50.01 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.72 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 53.52 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 53.43 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.52 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 53.87 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 54.38 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.17 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 52.89 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 50.07 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 34.18 | 0.08 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.38 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 53.47 | 79.95 | 18050.00 | 207629.42 | 17-JAN-09:01 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 45.95 | 80.00 | 11786.58 | 149433.58 | 17-FEB-09:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 52.43 | 79.85 | 6879.71 | 121670.79 | 31-MAR-04:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.02 | 79.40 | 2210.61 | 126183.98 | 13-APR-04:53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 47.26 | 47.26 | 153.75 | 78417.52 | 02-MAY-18:04 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 55.55 | 55.55 | 18.72 | 23758.49 | 01-JUN-08:04 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 61.66 | 61.66 | 17.03 | 21751.99 | 05-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 62.77 | 62.77 | 21.74 | 36268.08 | 24-AUG-08:04 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 60.59 | 60.59 | 197.94 | 46455.89 | 25-SEP-05:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 52.80 | 52.80 | 1033.12 | 79268.89 | 25-OCT-05:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 64.30 | 79.40 | 10364.14 | 151510.14 | 26-NOV-16:01 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 64.92 | 79.58 | 19119.25 | 158292.18 | 02-DEC-19:05 |
Annual Sum or Average | 0.00 | 5800.76 | ||||||
Minimum of Months | 0.00 | 0.00 | 45.95 | 47.26 | 17.03 | 21751.99 | ||
Maximum of Months | 0.00 | 0.00 | 64.92 | 80.00 | 19119.25 | 207629.42 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 13096.28 | 191318.58 | 03-JAN-16:03 | 9.34 | 7.69 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 29542.23 | 312525.30 | 20-FEB-16:01 | 9.93 | 7.24 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 44922.07 | 357836.17 | 14-MAR-18:01 | 10.35 | 7.27 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 128342.83 | 432476.62 | 19-APR-18:03 | 10.43 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 202109.21 | 446198.98 | 15-MAY-18:03 | 10.55 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 270306.07 | 526157.01 | 18-JUN-18:02 | 11.24 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 335066.90 | 629435.00 | 18-JUL-20:50 | 13.01 | 7.58 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 280392.31 | 594876.37 | 01-AUG-20:50 | 12.34 | 7.21 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 243483.05 | 510544.37 | 22-SEP-08:61 | 11.64 | 7.24 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 128038.85 | 532061.36 | 03-OCT-20:00 | 11.80 | 7.21 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 38324.10 | 334455.76 | 09-NOV-16:01 | 10.11 | 7.22 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 10057.67 | 96231.98 | 23-DEC-15:00 | 8.79 | 7.96 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 144287.80 | 0.00 | ||||||
Minimum of Months | 10057.67 | 96231.98 | 8.79 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 335066.90 | 629435.00 | 13.01 | 7.96 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 34.18 | 59.85 | 25402.54 | 63640.46 | 25-JAN-07:01 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 49.49 | 59.75 | 25416.60 | 62862.44 | 24-FEB-07:51 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 50.01 | 58.74 | 24577.96 | 56141.27 | 13-MAR-06:25 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.72 | 58.99 | 23041.97 | 52370.67 | 13-APR-06:24 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 53.52 | 59.64 | 21279.74 | 44499.86 | 01-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 53.43 | 58.61 | 19745.25 | 40781.93 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.52 | 58.33 | 18838.55 | 38088.58 | 03-JUL-06:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 53.87 | 58.56 | 18864.24 | 38237.03 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 54.38 | 59.65 | 19752.80 | 43158.93 | 25-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.17 | 59.24 | 21280.51 | 49130.40 | 25-OCT-06:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 52.89 | 58.69 | 23022.73 | 56909.33 | 21-NOV-07:31 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 50.07 | 58.32 | 24528.32 | 58382.95 | 10-DEC-08:11 |
Annual Sum or Average | 0.00 | 22127.33 | ||||||
Minimum of Months | 0.00 | 0.00 | 34.18 | 58.32 | 18838.55 | 38088.58 | ||
Maximum of Months | 0.00 | 0.00 | 54.38 | 59.85 | 25416.60 | 63640.46 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.276199E+11 | 0.00 | 0.716861E+10 | 0.373875E+11 | 0.00 | 0.00 |
February | 0.160916E+11 | 0.00 | 0.347043E+11 | 0.329253E+11 | 0.00 | 0.00 |
March | 0.122058E+11 | 0.00 | 0.702420E+11 | 0.366613E+11 | 0.00 | 0.00 |
April | 0.507475E+10 | 0.00 | 0.215062E+12 | 0.376419E+11 | 0.00 | 0.00 |
May | 0.313832E+09 | 0.00 | 0.357119E+12 | 0.419622E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.463005E+12 | 0.445456E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.618069E+12 | 0.467919E+11 | 0.00 | 0.00 |
August | 218560.25 | 0.00 | 0.504514E+12 | 0.475880E+11 | 0.00 | 0.00 |
September | 0.448287E+09 | 0.00 | 0.412748E+12 | 0.455316E+11 | 0.00 | 0.00 |
October | 0.243020E+10 | 0.00 | 0.204981E+12 | 0.433921E+11 | 0.00 | 0.00 |
November | 0.170586E+11 | 0.00 | 0.433069E+11 | 0.391589E+11 | 0.00 | 0.00 |
December | 0.235573E+11 | 0.00 | 0.436754E+10 | 0.383637E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.104800E+12 | 0.00 | 0.293529E+13 | 0.491950E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.436754E+10 | 0.329253E+11 | 0.00 | 0.00 |
Maximum of Months | 0.276199E+11 | 0.00 | 0.618069E+12 | 0.475880E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 48888398.20 | 0.00 | 0.122870E+10 | 0.587890E+10 | 0.00 | 0.00 |
February | 71253799.96 | 0.00 | 0.618797E+10 | 0.530997E+10 | 0.00 | 0.00 |
March | 34408146.74 | 0.00 | 0.122343E+11 | 0.587890E+10 | 0.00 | 0.00 |
April | 33259.54 | 0.00 | 0.348126E+11 | 0.568926E+10 | 0.00 | 0.00 |
May | 48666.88 | 0.00 | 0.557264E+11 | 0.587890E+10 | 0.00 | 0.00 |
June | 50726.14 | 0.00 | 0.679277E+11 | 0.568926E+10 | 0.00 | 0.00 |
July | 15400.64 | 0.00 | 0.903037E+11 | 0.587890E+10 | 0.00 | 0.00 |
August | 31376.35 | 0.00 | 0.760520E+11 | 0.587890E+10 | 0.00 | 0.00 |
September | 20445.35 | 0.00 | 0.649768E+11 | 0.568926E+10 | 0.00 | 0.00 |
October | 29792.77 | 0.00 | 0.332051E+11 | 0.587890E+10 | 0.00 | 0.00 |
November | 4826319.49 | 0.00 | 0.750498E+10 | 0.568926E+10 | 0.00 | 0.00 |
December | 0.205105E+09 | 0.00 | 0.724517E+09 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.364712E+09 | 0.00 | 0.450885E+12 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 15400.64 | 0.00 | 0.724517E+09 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 0.205105E+09 | 0.00 | 0.903037E+11 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.373875E+11 | 0.716957E+10 | 0.276199E+11 | 0.187478E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.329253E+11 | 0.347046E+11 | 0.160916E+11 | 0.141144E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366613E+11 | 0.702429E+11 | 0.122058E+11 | 0.109662E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.376419E+11 | 0.215062E+12 | 0.507475E+10 | 0.275858E+11 | 0.399386E+10 | 0.00 | 0.00 | 0.00 |
May | 0.419622E+11 | 0.357119E+12 | 0.313832E+09 | 0.192558E+11 | 0.177776E+11 | 0.00 | 0.00 | 0.00 |
June | 0.445456E+11 | 0.463005E+12 | 0.00 | 0.218571E+11 | 0.440077E+11 | 0.00 | 0.00 | 0.00 |
July | 0.467919E+11 | 0.618069E+12 | 0.00 | 0.910899E+10 | 0.775526E+11 | 0.00 | 0.00 | 0.00 |
August | 0.475880E+11 | 0.504514E+12 | 218560.25 | 0.110843E+11 | 0.375240E+11 | 0.00 | 0.00 | 0.00 |
September | 0.455316E+11 | 0.412748E+12 | 0.448287E+09 | 0.729694E+10 | 0.212880E+11 | 0.00 | 0.00 | 0.00 |
October | 0.433921E+11 | 0.204981E+12 | 0.243020E+10 | 0.160286E+11 | 0.367142E+10 | 0.00 | 0.00 | 0.00 |
November | 0.391589E+11 | 0.433080E+11 | 0.170586E+11 | 0.108101E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.383637E+11 | 0.436754E+10 | 0.235573E+11 | 0.238882E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.491950E+12 | 0.293529E+13 | 0.104800E+12 | 0.897485E+12 | 0.205815E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.329253E+11 | 0.436754E+10 | 0.00 | 0.729694E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.475880E+11 | 0.618069E+12 | 0.276199E+11 | 0.238882E+12 | 0.775526E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.122870E+10 | 48888398.20 | 0.456477E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.618797E+10 | 71253799.96 | 0.319895E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.122343E+11 | 34408146.74 | 0.251290E+11 | 37001735.09 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.348126E+11 | 33259.54 | 0.663288E+10 | 0.249123E+10 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.557264E+11 | 48666.88 | 0.170914E+10 | 0.941032E+10 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.679277E+11 | 50726.14 | 0.428313E+09 | 0.200745E+11 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.903037E+11 | 15400.64 | 0.00 | 0.416160E+11 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.760520E+11 | 31376.35 | 0.106620E+09 | 0.259490E+11 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.649768E+11 | 20445.35 | 0.943559E+09 | 0.154394E+11 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.332051E+11 | 29792.77 | 0.528014E+10 | 0.383007E+10 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.750498E+10 | 4826319.49 | 0.293229E+11 | 36576506.12 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.724517E+09 | 0.205105E+09 | 0.539185E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.450885E+12 | 0.364712E+09 | 0.201108E+12 | 0.118884E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.724517E+09 | 15400.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.903037E+11 | 0.205105E+09 | 0.539185E+11 | 0.416160E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.373875E+11 | 0.276199E+11 | 0.716861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.329253E+11 | 0.160916E+11 | 0.347043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366613E+11 | 0.122058E+11 | 0.702420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.376419E+11 | 0.507475E+10 | 0.215062E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.419622E+11 | 0.313832E+09 | 0.357119E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.445456E+11 | 0.00 | 0.463005E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.467919E+11 | 0.00 | 0.618069E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.475880E+11 | 218560.25 | 0.504514E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.455316E+11 | 0.448287E+09 | 0.412748E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.433921E+11 | 0.243020E+10 | 0.204981E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.391589E+11 | 0.170586E+11 | 0.433069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.383637E+11 | 0.235573E+11 | 0.436754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.491950E+12 | 0.104800E+12 | 0.293529E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.329253E+11 | 0.00 | 0.436754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.475880E+11 | 0.276199E+11 | 0.618069E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 48888398.20 | 0.122870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 71253799.96 | 0.618797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 34408146.74 | 0.122343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 33259.54 | 0.348126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 48666.88 | 0.557264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 50726.14 | 0.679277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 15400.64 | 0.903037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 31376.35 | 0.760520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 20445.35 | 0.649768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 29792.77 | 0.332051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 4826319.49 | 0.750498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.205105E+09 | 0.724517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.364712E+09 | 0.450885E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 15400.64 | 0.724517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.205105E+09 | 0.903037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.254338E+10 | 0.00 | 0.00 | 82082051.81 | 0.00 | 0.00 | 0.469358E+11 | 0.00 | 0.94 |
February | 0.251113E+11 | 0.00 | 0.00 | 11869076.15 | 0.00 | 0.00 | 0.109644E+11 | 0.00 | 0.86 |
March | 0.362358E+11 | 0.00 | 0.00 | 199738.27 | 0.00 | 0.00 | 0.395490E+09 | 0.00 | 0.87 |
April | 0.242422E+11 | 0.00 | 0.00 | 716.20 | 76862464.00 | 0.00 | 37259397.14 | 0.00 | 0.87 |
May | 0.140616E+11 | 0.00 | 0.00 | 1694057.24 | 0.450919E+09 | 0.00 | 0.113419E+10 | 0.00 | 0.83 |
June | 0.555414E+10 | 54185277.25 | 0.00 | 6389537.65 | 0.132409E+10 | 0.00 | 0.231033E+10 | 0.00 | 0.78 |
July | 55469267.97 | 0.651536E+10 | 0.00 | 18789985.58 | 0.501649E+09 | 0.00 | 0.229434E+10 | 0.00 | 0.85 |
August | 16461.22 | 0.212915E+10 | 0.00 | 55791048.94 | 16362510.38 | 0.00 | 0.931049E+10 | 0.00 | 1.01 |
September | 0.00 | 0.148897E+10 | 0.00 | 70461841.05 | 0.00 | 0.00 | 0.184624E+11 | 0.00 | 1.22 |
October | 0.00 | 0.246584E+09 | 0.00 | 94602097.36 | 0.00 | 0.00 | 0.417752E+11 | 0.00 | 1.29 |
November | 8308593.37 | 0.00 | 0.00 | 0.118019E+09 | 0.00 | 0.00 | 0.562900E+11 | 0.00 | 1.19 |
December | 91044543.09 | 0.00 | 0.00 | 0.122570E+09 | 0.00 | 0.00 | 0.560685E+11 | 0.00 | 1.05 |
Annual Sum or Average | 0.107903E+12 | 0.104342E+11 | 0.00 | 0.582469E+09 | 0.236988E+10 | 0.00 | 0.245978E+12 | 0.00 | 0.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 716.20 | 0.00 | 0.00 | 37259397.14 | 0.00 | 0.78 |
Maximum of Months | 0.362358E+11 | 0.651536E+10 | 0.00 | 0.122570E+09 | 0.132409E+10 | 0.00 | 0.562900E+11 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.294498E+10 | 0.00 | 0.00 | 2319214.50 | 0.00 | 57978865.80 | 0.134101E+10 | 0.00 | 1.56 |
February | 0.239782E+10 | 0.00 | 0.00 | 2453451.54 | 0.00 | 20620574.79 | 0.118749E+10 | 0.00 | 1.67 |
March | 0.242356E+10 | 0.00 | 0.00 | 2414110.95 | 0.00 | 25674015.99 | 0.109752E+10 | 0.00 | 1.62 |
April | 0.117455E+10 | 13844696.72 | 0.00 | 4629208.92 | 0.00 | 0.00 | 0.120415E+10 | 0.00 | 1.75 |
May | 0.352295E+09 | 72217135.75 | 0.00 | 5687779.54 | 0.00 | 0.00 | 0.120887E+10 | 0.00 | 1.82 |
June | 3027127.31 | 0.242467E+09 | 0.00 | 5691730.30 | 0.00 | 0.00 | 0.897207E+09 | 0.00 | 2.00 |
July | 1355969.77 | 0.896569E+09 | 0.00 | 2360837.33 | 1274480.19 | 0.00 | 0.252174E+09 | 0.00 | 1.99 |
August | 37595925.28 | 0.297670E+09 | 0.00 | 5476602.40 | 195375.69 | 0.00 | 0.734476E+09 | 0.00 | 2.06 |
September | 0.140144E+09 | 0.217884E+09 | 0.00 | 6152016.95 | 87442.74 | 0.00 | 0.119986E+10 | 0.00 | 2.28 |
October | 0.104208E+10 | 39764616.27 | 0.00 | 6842254.76 | 0.00 | 0.00 | 0.204264E+10 | 0.00 | 2.22 |
November | 0.209801E+10 | 0.00 | 0.00 | 4447091.78 | 0.00 | 39348895.12 | 0.213698E+10 | 0.00 | 1.88 |
December | 0.289824E+10 | 0.00 | 0.00 | 2010175.72 | 0.00 | 0.232141E+09 | 0.106658E+10 | 0.00 | 1.49 |
Annual Sum or Average | 0.155137E+11 | 0.178042E+10 | 0.00 | 50484474.69 | 1557298.62 | 0.375764E+09 | 0.143690E+11 | 0.00 | 1.86 |
Minimum of Months | 1355969.77 | 0.00 | 0.00 | 2010175.72 | 0.00 | 0.00 | 0.252174E+09 | 0.00 | 1.49 |
Maximum of Months | 0.294498E+10 | 0.896569E+09 | 0.00 | 6842254.76 | 1274480.19 | 0.232141E+09 | 0.213698E+10 | 0.00 | 2.28 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.387675E+10 | 0.00 | 0.00 | 479877.30 | 0.00 | 0.00 | 0.686731E+09 | 0.00 | 1.37 |
February | 0.292241E+10 | 0.00 | 0.00 | 659441.90 | 0.00 | 0.00 | 0.926408E+09 | 0.00 | 1.44 |
March | 0.254221E+10 | 0.00 | 0.00 | 1137505.23 | 0.00 | 0.00 | 0.143124E+10 | 0.00 | 1.48 |
April | 0.745705E+09 | 4527053.50 | 0.00 | 2951696.56 | 3725111.10 | 0.00 | 0.197909E+10 | 0.00 | 1.54 |
May | 0.100394E+09 | 40653566.96 | 0.00 | 4854889.94 | 7829513.58 | 0.00 | 0.171029E+10 | 0.00 | 1.56 |
June | 6656369.42 | 0.149718E+09 | 0.00 | 5008028.72 | 4399726.12 | 0.00 | 0.998086E+09 | 0.00 | 1.54 |
July | 231371.06 | 0.723791E+09 | 0.00 | 2381699.95 | 33742031.79 | 0.00 | 0.274762E+09 | 0.00 | 1.51 |
August | 18119699.66 | 0.208321E+09 | 0.00 | 4527746.63 | 8294546.36 | 0.00 | 0.836512E+09 | 0.00 | 1.55 |
September | 26151831.88 | 0.129810E+09 | 0.00 | 4781765.89 | 6946809.80 | 0.00 | 0.144949E+10 | 0.00 | 1.63 |
October | 0.653829E+09 | 20736229.70 | 0.00 | 3631439.21 | 1680235.77 | 0.00 | 0.250010E+10 | 0.00 | 1.60 |
November | 0.254750E+10 | 0.00 | 0.00 | 1373573.00 | 0.00 | 0.00 | 0.163100E+10 | 0.00 | 1.43 |
December | 0.403466E+10 | 0.00 | 0.00 | 202900.81 | 0.00 | 0.00 | 0.443930E+09 | 0.00 | 1.35 |
Annual Sum or Average | 0.174746E+11 | 0.127756E+10 | 0.00 | 31990565.13 | 66617974.52 | 0.00 | 0.148676E+11 | 0.00 | 1.50 |
Minimum of Months | 231371.06 | 0.00 | 0.00 | 202900.81 | 0.00 | 0.00 | 0.274762E+09 | 0.00 | 1.35 |
Maximum of Months | 0.403466E+10 | 0.723791E+09 | 0.00 | 5008028.72 | 33742031.79 | 0.00 | 0.250010E+10 | 0.00 | 1.63 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.293199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
February | 0.246273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
March | 0.246764E+10 | 0.00 | 0.00 | 35483.32 | 0.00 | 0.00 | 63349419.29 | 0.00 | 0.45 |
April | 0.113803E+10 | 3172911.53 | 0.00 | 1304737.95 | 2136932.41 | 0.00 | 0.616264E+09 | 0.00 | 0.47 |
May | 0.173303E+09 | 32901302.94 | 0.00 | 4708501.21 | 3018414.12 | 0.00 | 0.116540E+10 | 0.00 | 0.56 |
June | 467512.55 | 0.146017E+09 | 0.00 | 5241501.35 | 6042.86 | 0.00 | 0.868053E+09 | 0.00 | 0.66 |
July | 0.00 | 0.673587E+09 | 0.00 | 2230527.07 | 0.00 | 0.00 | 0.240906E+09 | 0.00 | 0.65 |
August | 8325510.73 | 0.191487E+09 | 0.00 | 4475204.73 | 151543.69 | 0.00 | 0.674471E+09 | 0.00 | 0.62 |
September | 57206677.91 | 0.106837E+09 | 0.00 | 4001778.33 | 86995.48 | 0.00 | 0.100234E+10 | 0.00 | 0.59 |
October | 0.122824E+10 | 17028905.76 | 0.00 | 1611185.80 | 782779.48 | 0.00 | 0.801312E+09 | 0.00 | 0.50 |
November | 0.256052E+10 | 0.00 | 0.00 | 68742.57 | 0.00 | 0.00 | 91704363.55 | 0.00 | 0.43 |
December | 0.288030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.159088E+11 | 0.117103E+10 | 0.00 | 23677662.32 | 6182708.03 | 0.00 | 0.552379E+10 | 0.00 | 0.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.293199E+10 | 0.673587E+09 | 0.00 | 5241501.35 | 3018414.12 | 0.00 | 0.116540E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.286759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 519961.91 | 0.00 | 0.00 | 0.70 |
February | 0.240847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 606860.62 | 0.00 | 0.00 | 0.73 |
March | 0.247546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 |
April | 0.164074E+10 | 0.00 | 0.00 | 0.00 | 5194155.67 | 0.00 | 0.00 | 0.00 | 0.75 |
May | 0.101845E+10 | 0.00 | 0.00 | 10985.30 | 30471857.43 | 0.00 | 8543951.36 | 0.00 | 0.72 |
June | 0.395636E+09 | 18813551.80 | 0.00 | 410979.13 | 74313337.62 | 0.00 | 0.135132E+09 | 0.00 | 0.68 |
July | 0.100720E+09 | 48982724.72 | 0.00 | 198530.27 | 0.377779E+09 | 0.00 | 43417965.86 | 0.00 | 0.67 |
August | 0.438136E+09 | 17244027.71 | 0.00 | 119021.03 | 0.104608E+09 | 0.00 | 30990828.61 | 0.00 | 0.69 |
September | 0.811096E+09 | 520484.33 | 0.00 | 4842.45 | 80163620.76 | 0.00 | 1594101.80 | 0.00 | 0.73 |
October | 0.186910E+10 | 0.00 | 0.00 | 0.00 | 12528102.25 | 0.00 | 0.00 | 0.00 | 0.77 |
November | 0.258880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 915390.58 | 0.00 | 0.00 | 0.72 |
December | 0.279139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26160582.36 | 0.00 | 0.00 | 0.69 |
Annual Sum or Average | 0.194056E+11 | 85560788.57 | 0.00 | 744358.18 | 0.685058E+09 | 28202795.46 | 0.219679E+09 | 0.00 | 0.72 |
Minimum of Months | 0.100720E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
Maximum of Months | 0.286759E+10 | 48982724.72 | 0.00 | 410979.13 | 0.377779E+09 | 26160582.36 | 0.135132E+09 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 9763101.43 | 0.00 | 0.00 | 0.159029E+09 | 0.00 | 0.00 | 0.678745E+11 | 0.00 | 19.81 |
February | 8689014.31 | 0.00 | 0.00 | 0.125851E+09 | 0.00 | 0.00 | 0.577973E+11 | 0.00 | 21.03 |
March | 12179159.08 | 0.00 | 0.00 | 0.128808E+09 | 0.00 | 0.00 | 0.597175E+11 | 0.00 | 21.90 |
April | 7398540.44 | 0.102062E+09 | 0.00 | 0.116698E+09 | 0.00 | 0.00 | 0.385239E+11 | 0.00 | 21.99 |
May | 0.00 | 0.585258E+09 | 0.00 | 0.103111E+09 | 0.00 | 0.00 | 0.234124E+11 | 0.00 | 20.97 |
June | 0.00 | 0.197812E+10 | 0.00 | 76785851.73 | 0.00 | 0.00 | 0.114477E+11 | 0.00 | 19.33 |
July | 0.00 | 0.102534E+11 | 0.00 | 28770832.26 | 0.00 | 0.00 | 0.292302E+10 | 0.00 | 18.97 |
August | 0.00 | 0.295424E+10 | 0.00 | 73292860.56 | 0.00 | 0.00 | 0.101506E+11 | 0.00 | 19.80 |
September | 0.00 | 0.182168E+10 | 0.00 | 82003237.78 | 0.00 | 0.00 | 0.185992E+11 | 0.00 | 21.27 |
October | 0.00 | 0.323676E+09 | 0.00 | 0.108601E+09 | 0.00 | 0.00 | 0.443503E+11 | 0.00 | 22.51 |
November | 23943556.07 | 0.00 | 0.00 | 0.135568E+09 | 0.00 | 0.00 | 0.626174E+11 | 0.00 | 20.83 |
December | 8921672.39 | 0.00 | 0.00 | 0.160751E+09 | 0.00 | 0.00 | 0.666830E+11 | 0.00 | 19.36 |
Annual Sum or Average | 70895043.72 | 0.180184E+11 | 0.00 | 0.129927E+10 | 0.00 | 0.00 | 0.464097E+12 | 0.00 | 20.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 28770832.26 | 0.00 | 0.00 | 0.292302E+10 | 0.00 | 18.97 |
Maximum of Months | 23943556.07 | 0.102534E+11 | 0.00 | 0.160751E+09 | 0.00 | 0.00 | 0.678745E+11 | 0.00 | 22.51 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.161362E+11 | 0.00 | 0.00 | 10196493.34 | 0.00 | 0.00 | 0.175316E+11 | 0.00 | 4.17 |
February | 0.121222E+11 | 0.00 | 0.00 | 10680006.73 | 0.00 | 0.00 | 0.161443E+11 | 0.00 | 4.36 |
March | 0.117089E+11 | 0.00 | 0.00 | 10176936.77 | 0.00 | 0.00 | 0.172679E+11 | 0.00 | 4.45 |
April | 0.578889E+10 | 59858973.49 | 0.00 | 14821933.94 | 958367.97 | 0.00 | 0.134319E+11 | 0.00 | 4.44 |
May | 0.183587E+10 | 0.309425E+09 | 0.00 | 17394254.78 | 47363861.09 | 0.00 | 0.102222E+11 | 0.00 | 4.28 |
June | 0.396267E+09 | 0.988337E+09 | 0.00 | 19110948.70 | 0.102288E+09 | 0.00 | 0.594102E+10 | 0.00 | 4.05 |
July | 28451589.21 | 0.418183E+10 | 0.00 | 10972956.55 | 0.845164E+09 | 0.00 | 0.169784E+10 | 0.00 | 3.99 |
August | 0.510820E+09 | 0.130264E+10 | 0.00 | 19136211.65 | 0.139001E+09 | 0.00 | 0.507216E+10 | 0.00 | 4.14 |
September | 0.752890E+09 | 0.885673E+09 | 0.00 | 23161623.06 | 75485112.17 | 0.00 | 0.888810E+10 | 0.00 | 4.42 |
October | 0.408899E+10 | 0.142292E+09 | 0.00 | 26974572.78 | 14037241.23 | 0.00 | 0.180005E+11 | 0.00 | 4.65 |
November | 0.101267E+11 | 0.00 | 0.00 | 19854337.88 | 0.00 | 570800.73 | 0.204719E+11 | 0.00 | 4.36 |
December | 0.184157E+11 | 0.00 | 0.00 | 7748977.42 | 0.00 | 702043.71 | 0.146317E+11 | 0.00 | 4.09 |
Annual Sum or Average | 0.819118E+11 | 0.787006E+10 | 0.00 | 0.190229E+09 | 0.122430E+10 | 1272844.45 | 0.149301E+12 | 0.00 | 4.28 |
Minimum of Months | 28451589.21 | 0.00 | 0.00 | 7748977.42 | 0.00 | 0.00 | 0.169784E+10 | 0.00 | 3.99 |
Maximum of Months | 0.184157E+11 | 0.418183E+10 | 0.00 | 26974572.78 | 0.845164E+09 | 702043.71 | 0.204719E+11 | 0.00 | 4.65 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.517363E+11 | 0.00 | 0.00 | 33178458.00 | 0.00 | 0.00 | 0.429921E+11 | 0.00 | 1.70 |
February | 0.357320E+11 | 0.00 | 0.00 | 36165523.57 | 0.00 | 0.00 | 0.442005E+11 | 0.00 | 1.78 |
March | 0.328140E+11 | 0.00 | 0.00 | 43261411.12 | 0.00 | 0.00 | 0.495388E+11 | 0.00 | 1.83 |
April | 0.116304E+11 | 0.121475E+09 | 0.00 | 67958575.83 | 48728484.43 | 0.00 | 0.451213E+11 | 0.00 | 1.89 |
May | 0.254606E+10 | 0.758389E+09 | 0.00 | 86002204.66 | 0.240311E+09 | 0.00 | 0.352895E+11 | 0.00 | 1.90 |
June | 0.350325E+09 | 0.284429E+10 | 0.00 | 87729590.01 | 0.254512E+09 | 0.00 | 0.207266E+11 | 0.00 | 1.85 |
July | 15491195.98 | 0.139492E+11 | 0.00 | 46605286.81 | 0.139684E+10 | 0.00 | 0.583230E+10 | 0.00 | 1.82 |
August | 0.558933E+09 | 0.404793E+10 | 0.00 | 82764297.39 | 0.313733E+09 | 0.00 | 0.176362E+11 | 0.00 | 1.88 |
September | 0.610864E+09 | 0.258052E+10 | 0.00 | 90877340.63 | 0.193705E+09 | 0.00 | 0.303810E+11 | 0.00 | 1.98 |
October | 0.806232E+10 | 0.424141E+09 | 0.00 | 93756521.60 | 24201767.26 | 0.00 | 0.581922E+11 | 0.00 | 1.98 |
November | 0.252510E+11 | 0.00 | 0.00 | 59144498.16 | 0.00 | 0.00 | 0.618914E+11 | 0.00 | 1.78 |
December | 0.578780E+11 | 0.00 | 0.00 | 23763902.12 | 0.00 | 0.00 | 0.347634E+11 | 0.00 | 1.66 |
Annual Sum or Average | 0.227186E+12 | 0.247260E+11 | 0.00 | 0.751208E+09 | 0.247203E+10 | 0.00 | 0.446565E+12 | 0.00 | 1.84 |
Minimum of Months | 15491195.98 | 0.00 | 0.00 | 23763902.12 | 0.00 | 0.00 | 0.583230E+10 | 0.00 | 1.66 |
Maximum of Months | 0.578780E+11 | 0.139492E+11 | 0.00 | 93756521.60 | 0.139684E+10 | 0.00 | 0.618914E+11 | 0.00 | 1.98 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.371703E+09 | 0.00 | 0.00 | 2972234.47 | 0.00 | 0.751799E+09 | 0.433723E+09 | 0.00 | 0.47 |
February | 0.290662E+09 | 0.00 | 0.00 | 3816912.27 | 0.00 | 0.494340E+09 | 0.521240E+09 | 0.00 | 0.47 |
March | 0.258402E+09 | 44307.74 | 0.00 | 6529413.88 | 0.00 | 0.341251E+09 | 0.725134E+09 | 0.00 | 0.47 |
April | 0.107736E+09 | 15323151.95 | 6017.82 | 10020518.28 | 667074.12 | 40144836.03 | 0.649140E+09 | 1728.45 | 0.47 |
May | 28838921.36 | 83960235.59 | 11368.89 | 8314545.56 | 4406113.28 | 346663.61 | 0.368705E+09 | 12390.02 | 0.47 |
June | 2243382.32 | 0.179169E+09 | 61982.91 | 4149433.52 | 7765546.63 | 22047.27 | 75911469.04 | 24063.60 | 0.47 |
July | 0.00 | 0.764838E+09 | 518583.67 | 24296.83 | 37152532.10 | 0.00 | 126824.83 | 38716.06 | 0.47 |
August | 2795379.25 | 0.384412E+09 | 247259.69 | 1689660.04 | 22112929.38 | 50038.85 | 33582252.19 | 35799.78 | 0.47 |
September | 15711090.49 | 0.353371E+09 | 222467.20 | 4942835.51 | 17420831.77 | 199482.35 | 0.208722E+09 | 30001.39 | 0.48 |
October | 0.111065E+09 | 71321501.98 | 70104.92 | 9692884.88 | 4042287.10 | 2128827.36 | 0.750921E+09 | 3098.04 | 0.47 |
November | 0.240907E+09 | 614842.14 | 0.00 | 6586203.14 | 0.00 | 0.386325E+09 | 0.752923E+09 | 0.00 | 0.47 |
December | 0.386277E+09 | 0.00 | 0.00 | 2127473.72 | 0.00 | 0.835520E+09 | 0.338819E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.181634E+10 | 0.185305E+10 | 1137785.09 | 60866412.09 | 93567314.38 | 0.285213E+10 | 0.485895E+10 | 145797.33 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 24296.83 | 0.00 | 0.00 | 126824.83 | 0.00 | 0.47 |
Maximum of Months | 0.386277E+09 | 0.764838E+09 | 518583.67 | 10020518.28 | 37152532.10 | 0.835520E+09 | 0.752923E+09 | 38716.06 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.431234E+09 | 0.00 | 0.00 | 819814.23 | 0.00 | 0.993856E+09 | 0.134104E+09 | 0.00 | 0.47 |
February | 0.339736E+09 | 0.00 | 0.00 | 1539849.80 | 0.00 | 0.714021E+09 | 0.254608E+09 | 0.00 | 0.47 |
March | 0.299652E+09 | 44152.10 | 0.00 | 4171048.77 | 0.00 | 0.484061E+09 | 0.543278E+09 | 150.44 | 0.47 |
April | 0.119794E+09 | 14525029.84 | 6515.06 | 8884578.15 | 1462244.28 | 57605246.44 | 0.620662E+09 | 2308.76 | 0.47 |
May | 30377289.01 | 83443990.08 | 12326.68 | 8178290.95 | 4912005.37 | 349733.90 | 0.367252E+09 | 11429.43 | 0.47 |
June | 2176618.60 | 0.179234E+09 | 55538.84 | 4203952.31 | 7686814.64 | 22044.69 | 75914070.82 | 21568.21 | 0.47 |
July | 0.00 | 0.765900E+09 | 504459.27 | 24946.06 | 36014045.97 | 0.00 | 126157.89 | 35449.29 | 0.47 |
August | 2801356.86 | 0.381538E+09 | 245357.66 | 1625444.90 | 24939594.44 | 50032.99 | 33636029.57 | 37668.65 | 0.47 |
September | 17865341.98 | 0.349015E+09 | 218513.80 | 4126724.39 | 21737724.88 | 305157.45 | 0.207251E+09 | 30463.32 | 0.48 |
October | 0.151378E+09 | 64379351.97 | 82815.60 | 6587913.59 | 10959046.88 | 10174078.34 | 0.705565E+09 | 6939.05 | 0.47 |
November | 0.317002E+09 | 444669.84 | 0.00 | 2774820.83 | 170100.27 | 0.615269E+09 | 0.451532E+09 | 0.00 | 0.47 |
December | 0.425120E+09 | 0.00 | 0.00 | 448315.64 | 0.00 | 0.106723E+10 | 69765282.57 | 0.00 | 0.47 |
Annual Sum or Average | 0.213714E+10 | 0.183852E+10 | 1125526.92 | 43385699.63 | 0.107882E+09 | 0.394294E+10 | 0.346369E+10 | 145977.15 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 24946.06 | 0.00 | 0.00 | 126157.89 | 0.00 | 0.47 |
Maximum of Months | 0.431234E+09 | 0.765900E+09 | 504459.27 | 8884578.15 | 36014045.97 | 0.106723E+10 | 0.705565E+09 | 37668.65 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120365E+11 | 0.00 | 0.00 | 52305234.36 | 0.00 | 0.00 | 0.906603E+10 | 0.00 | 0.54 |
February | 0.964700E+10 | 0.00 | 0.00 | 47271774.40 | 0.00 | 0.00 | 0.806895E+10 | 0.00 | 0.54 |
March | 0.112459E+11 | 600773.22 | 0.00 | 36050919.81 | 0.00 | 0.00 | 0.676947E+10 | 0.00 | 0.54 |
April | 0.528988E+10 | 0.216918E+09 | 0.00 | 46974087.44 | 0.00 | 0.00 | 0.560589E+10 | 0.00 | 0.54 |
May | 0.180266E+10 | 0.119849E+10 | 0.00 | 35408690.02 | 0.00 | 0.00 | 0.366971E+10 | 0.00 | 0.54 |
June | 0.111665E+09 | 0.253583E+10 | 0.00 | 20998994.92 | 0.00 | 0.00 | 0.983607E+09 | 0.00 | 0.54 |
July | 721850.41 | 0.108818E+11 | 0.00 | 66571.86 | 0.00 | 0.00 | 1260651.88 | 0.00 | 0.54 |
August | 58828609.09 | 0.550898E+10 | 0.00 | 8502667.21 | 6975392.05 | 0.00 | 0.449506E+09 | 0.00 | 0.54 |
September | 0.284351E+09 | 0.502632E+10 | 0.00 | 31676441.26 | 4718165.86 | 0.00 | 0.279681E+10 | 0.00 | 0.54 |
October | 0.287380E+10 | 0.102286E+10 | 0.00 | 76437073.92 | 0.00 | 0.00 | 0.889781E+10 | 0.00 | 0.54 |
November | 0.826974E+10 | 8336707.97 | 0.00 | 79009680.14 | 0.00 | 0.00 | 0.104542E+11 | 0.00 | 0.54 |
December | 0.127726E+11 | 0.00 | 0.00 | 45147276.04 | 0.00 | 0.00 | 0.837164E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.643937E+11 | 0.264002E+11 | 0.00 | 0.479849E+09 | 11693557.91 | 0.00 | 0.651349E+11 | 0.00 | 0.54 |
Minimum of Months | 721850.41 | 0.00 | 0.00 | 66571.86 | 0.00 | 0.00 | 1260651.88 | 0.00 | 0.53 |
Maximum of Months | 0.127726E+11 | 0.108818E+11 | 0.00 | 79009680.14 | 6975392.05 | 0.00 | 0.104542E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.593868E+10 | 0.00 | 0.00 | 13015296.64 | 0.00 | 0.737877E+10 | 0.783018E+10 | 0.00 | 0.53 |
February | 0.469959E+10 | 0.00 | 0.00 | 20234920.45 | 0.00 | 0.377195E+10 | 0.927631E+10 | 0.00 | 0.53 |
March | 0.429882E+10 | 600937.50 | 0.00 | 39634606.62 | 0.00 | 0.114526E+10 | 0.125727E+11 | 0.00 | 0.54 |
April | 0.195291E+10 | 0.101500E+09 | 680568.70 | 70646570.46 | 0.114647E+09 | 52200786.01 | 0.886998E+10 | 149685.36 | 0.54 |
May | 0.485823E+09 | 0.797401E+09 | 2042992.15 | 66157757.88 | 0.399129E+09 | 1844509.25 | 0.495546E+10 | 245723.32 | 0.54 |
June | 38834632.34 | 0.213856E+10 | 1476869.55 | 33915985.14 | 0.396436E+09 | 274946.45 | 0.104355E+10 | 45921.00 | 0.54 |
July | 0.00 | 0.930467E+10 | 5153098.40 | 256623.69 | 0.157489E+10 | 0.00 | 1793010.77 | 84432.04 | 0.54 |
August | 39013791.47 | 0.438256E+10 | 2498456.54 | 14541387.53 | 0.113223E+10 | 483050.51 | 0.462940E+09 | 168932.28 | 0.54 |
September | 0.313859E+09 | 0.387096E+10 | 3763236.10 | 30561689.79 | 0.115746E+10 | 2771724.25 | 0.276650E+10 | 228340.74 | 0.54 |
October | 0.227883E+10 | 0.641128E+09 | 1469885.51 | 51286241.85 | 0.380475E+09 | 29410764.88 | 0.949176E+10 | 64054.97 | 0.54 |
November | 0.465934E+10 | 1226321.42 | 31834.41 | 24584179.58 | 7067994.99 | 0.303531E+10 | 0.110889E+11 | 12836.82 | 0.53 |
December | 0.600414E+10 | 0.00 | 0.00 | 9263242.30 | 0.00 | 0.949471E+10 | 0.568707E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.307098E+11 | 0.212386E+11 | 17116941.36 | 0.374099E+09 | 0.516235E+10 | 0.249130E+11 | 0.740471E+11 | 999926.53 | 0.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 256623.69 | 0.00 | 0.00 | 1793010.77 | 0.00 | 0.53 |
Maximum of Months | 0.600414E+10 | 0.930467E+10 | 5153098.40 | 70646570.46 | 0.157489E+10 | 0.949471E+10 | 0.125727E+11 | 245723.32 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.410740E+09 | 0.00 | 0.00 | 3039313.49 | 0.00 | 0.747148E+09 | 0.399269E+09 | 0.00 | 0.47 |
February | 0.272545E+09 | 0.00 | 0.00 | 4985549.51 | 0.00 | 0.456661E+09 | 0.575867E+09 | 0.00 | 0.47 |
March | 0.198434E+09 | 44157.28 | 0.00 | 7194108.11 | 0.00 | 0.330739E+09 | 0.794950E+09 | 150.46 | 0.47 |
April | 55669842.67 | 15599499.26 | 8070.49 | 11814444.98 | 386696.43 | 35576987.44 | 0.703979E+09 | 3706.17 | 0.47 |
May | 8543054.20 | 84951367.31 | 36405.04 | 9799150.24 | 3397012.90 | 58584.79 | 0.387804E+09 | 5322.52 | 0.47 |
June | 1036898.91 | 0.182834E+09 | 12485.71 | 4730866.77 | 4173407.59 | 0.00 | 76558566.46 | 163.23 | 0.47 |
July | 0.00 | 0.782201E+09 | 79495.72 | 31453.62 | 20266000.68 | 0.00 | 119668.04 | 664.12 | 0.47 |
August | 1752573.56 | 0.394447E+09 | 99464.11 | 1922617.03 | 12255575.26 | 47115.50 | 34395024.24 | 6783.65 | 0.47 |
September | 7353804.61 | 0.361891E+09 | 24372.92 | 5414932.98 | 9128931.81 | 21015.06 | 0.216786E+09 | 40.75 | 0.48 |
October | 88114248.99 | 71849625.03 | 71570.53 | 9988612.65 | 3512583.77 | 10591697.08 | 0.765113E+09 | 3212.71 | 0.47 |
November | 0.209804E+09 | 614842.14 | 0.00 | 7407191.72 | 0.00 | 0.408293E+09 | 0.761237E+09 | 0.00 | 0.47 |
December | 0.432465E+09 | 0.00 | 0.00 | 2450088.19 | 0.00 | 0.807124E+09 | 0.320704E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.168646E+10 | 0.189443E+10 | 331864.52 | 68778329.29 | 53120208.43 | 0.279626E+10 | 0.503678E+10 | 20043.61 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 31453.62 | 0.00 | 0.00 | 119668.04 | 0.00 | 0.47 |
Maximum of Months | 0.432465E+09 | 0.782201E+09 | 99464.11 | 11814444.98 | 20266000.68 | 0.807124E+09 | 0.794950E+09 | 6783.65 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.437814E+09 | 0.00 | 0.00 | 575189.08 | 0.00 | 0.986343E+09 | 0.135282E+09 | 0.00 | 0.47 |
February | 0.343337E+09 | 0.00 | 0.00 | 2013663.16 | 0.00 | 0.632963E+09 | 0.331591E+09 | 0.00 | 0.47 |
March | 0.305366E+09 | 44152.10 | 0.00 | 4367120.26 | 0.00 | 0.442520E+09 | 0.578908E+09 | 150.44 | 0.47 |
April | 78267941.07 | 15496030.74 | 28708.52 | 10470362.90 | 460982.23 | 52943367.92 | 0.665265E+09 | 10376.45 | 0.47 |
May | 9011087.65 | 84975625.49 | 45851.00 | 9653725.46 | 3352044.85 | 58980.10 | 0.387434E+09 | 6230.24 | 0.47 |
June | 993915.07 | 0.182931E+09 | 0.00 | 4801625.89 | 4067261.19 | 0.00 | 76521145.46 | 0.00 | 0.47 |
July | 0.00 | 0.782000E+09 | 88194.89 | 32014.75 | 20365066.07 | 0.00 | 119089.20 | 259.62 | 0.47 |
August | 1752368.22 | 0.393069E+09 | 100788.41 | 1857362.40 | 13581794.54 | 47109.98 | 34456023.73 | 8770.47 | 0.47 |
September | 9352253.69 | 0.359576E+09 | 73305.71 | 4504105.09 | 11350412.89 | 32298.21 | 0.215660E+09 | 1980.62 | 0.48 |
October | 0.125451E+09 | 67785823.15 | 128819.61 | 6596010.14 | 7499552.65 | 21637593.97 | 0.720021E+09 | 13958.09 | 0.47 |
November | 0.340681E+09 | 90275.58 | 2319.02 | 2777431.92 | 521069.49 | 0.588128E+09 | 0.454992E+09 | 1106.02 | 0.47 |
December | 0.429259E+09 | 0.00 | 0.00 | 430665.81 | 0.00 | 0.103651E+10 | 96365047.78 | 0.00 | 0.47 |
Annual Sum or Average | 0.208128E+10 | 0.188597E+10 | 467987.15 | 48079276.85 | 61198183.90 | 0.376118E+10 | 0.369661E+10 | 42831.95 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 32014.75 | 0.00 | 0.00 | 119089.20 | 0.00 | 0.47 |
Maximum of Months | 0.437814E+09 | 0.782000E+09 | 128819.61 | 10470362.90 | 20365066.07 | 0.103651E+10 | 0.720021E+09 | 13958.09 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.235399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
February | 0.197723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
March | 0.203171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
April | 0.124195E+11 | 11415476.67 | 0.00 | 2015021.29 | 31215217.46 | 0.00 | 0.106978E+10 | 0.00 | 0.49 |
May | 0.270111E+10 | 0.221656E+09 | 0.00 | 18602478.48 | 38973163.35 | 0.00 | 0.615804E+10 | 0.00 | 0.51 |
June | 95438171.51 | 0.921006E+09 | 0.00 | 26081540.59 | 8426167.42 | 0.00 | 0.494245E+10 | 0.00 | 0.53 |
July | 3878865.33 | 0.380910E+10 | 0.00 | 12121251.43 | 0.180307E+09 | 0.00 | 0.138041E+10 | 0.00 | 0.52 |
August | 0.484945E+09 | 0.113071E+10 | 0.00 | 21244716.44 | 46488147.95 | 0.00 | 0.374086E+10 | 0.00 | 0.52 |
September | 0.111068E+10 | 0.702420E+09 | 0.00 | 21029917.15 | 30985488.86 | 0.00 | 0.604773E+10 | 0.00 | 0.54 |
October | 0.115709E+11 | 0.106652E+09 | 0.00 | 6809158.42 | 14364388.88 | 0.00 | 0.388939E+10 | 0.00 | 0.51 |
November | 0.212549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
December | 0.231243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 492106.53 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.136395E+12 | 0.690295E+10 | 0.00 | 0.107904E+09 | 0.350759E+09 | 492106.53 | 0.272287E+11 | 0.00 | 0.50 |
Minimum of Months | 3878865.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.235399E+11 | 0.380910E+10 | 0.00 | 26081540.59 | 0.180307E+09 | 492106.53 | 0.615804E+10 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 94515804.08 | 0.00 | 0.00 | 558923.22 | 0.00 | 0.230485E+09 | 64489493.29 | 0.00 | 0.47 |
February | 76289495.72 | 0.00 | 0.00 | 746970.30 | 0.00 | 0.174243E+09 | 76234962.53 | 0.00 | 0.47 |
March | 67276183.15 | 11076.94 | 0.00 | 1336713.16 | 0.00 | 0.146168E+09 | 0.118048E+09 | 0.00 | 0.47 |
April | 28579770.20 | 3828313.26 | 1617.36 | 2181217.60 | 169243.26 | 29146960.30 | 0.141852E+09 | 319.21 | 0.47 |
May | 7596555.96 | 20941518.39 | 1477.48 | 1833553.83 | 1152296.94 | 650786.71 | 91470417.00 | 2234.13 | 0.47 |
June | 596280.52 | 44863558.77 | 14582.15 | 962998.84 | 1871523.93 | 10479.96 | 19011823.71 | 5367.77 | 0.47 |
July | 0.00 | 0.191003E+09 | 144418.59 | 4690.57 | 9477556.47 | 0.00 | 33089.84 | 12102.39 | 0.47 |
August | 701783.62 | 95847592.22 | 70147.54 | 365929.18 | 5775323.59 | 10803.30 | 8450816.48 | 9040.37 | 0.47 |
September | 3977523.56 | 87954098.37 | 47168.26 | 1074659.84 | 4753494.34 | 235798.78 | 52105863.04 | 6431.79 | 0.48 |
October | 30895894.84 | 17695540.20 | 12308.17 | 1960505.42 | 1150432.26 | 24644987.74 | 0.160950E+09 | 967.38 | 0.47 |
November | 62754138.69 | 153710.53 | 0.00 | 1232486.57 | 0.00 | 0.149853E+09 | 0.132845E+09 | 0.00 | 0.47 |
December | 97726604.88 | 0.00 | 0.00 | 399015.30 | 0.00 | 0.246303E+09 | 46256928.31 | 0.00 | 0.47 |
Annual Sum or Average | 0.470910E+09 | 0.462298E+09 | 291719.56 | 12657663.83 | 24349870.81 | 0.100175E+10 | 0.911749E+09 | 36463.03 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 4690.57 | 0.00 | 0.00 | 33089.84 | 0.00 | 0.47 |
Maximum of Months | 97726604.88 | 0.191003E+09 | 144418.59 | 2181217.60 | 9477556.47 | 0.246303E+09 | 0.160950E+09 | 12102.39 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 98018273.39 | 0.00 | 0.00 | 135936.10 | 0.00 | 0.275184E+09 | 16664771.01 | 0.00 | 0.47 |
February | 82114793.60 | 0.00 | 0.00 | 279800.72 | 0.00 | 0.213269E+09 | 31813068.67 | 0.00 | 0.47 |
March | 75555928.77 | 11038.03 | 36.15 | 812470.94 | 0.00 | 0.177738E+09 | 78683878.54 | 1.47 | 0.47 |
April | 31302695.17 | 3661281.51 | 1523.62 | 1903572.63 | 335806.64 | 35868546.45 | 0.132662E+09 | 412.72 | 0.47 |
May | 7805043.56 | 20852964.47 | 1323.42 | 1798925.03 | 1238262.25 | 1335221.32 | 90600225.37 | 2387.76 | 0.47 |
June | 572148.53 | 44823813.32 | 14039.31 | 976653.90 | 1906411.83 | 6947.68 | 19023421.49 | 5290.13 | 0.47 |
July | 0.00 | 0.191181E+09 | 142657.43 | 4805.74 | 9278076.99 | 0.00 | 32970.24 | 11501.32 | 0.47 |
August | 707627.06 | 95130903.26 | 69632.57 | 350045.41 | 6480105.94 | 10802.04 | 8459741.57 | 9546.06 | 0.47 |
September | 4546146.44 | 86921982.66 | 37585.28 | 866406.12 | 5784930.91 | 1727651.48 | 50246916.66 | 5825.58 | 0.48 |
October | 38597287.40 | 16078424.92 | 23188.31 | 1211156.73 | 2752613.36 | 49596023.26 | 0.129022E+09 | 2811.78 | 0.47 |
November | 78626836.19 | 99737.76 | 0.00 | 468648.07 | 53954.76 | 0.216168E+09 | 51380766.72 | 0.00 | 0.47 |
December | 94612973.83 | 0.00 | 0.00 | 80197.40 | 0.00 | 0.287391E+09 | 8555724.42 | 0.00 | 0.47 |
Annual Sum or Average | 0.512460E+09 | 0.458761E+09 | 289986.08 | 8888618.80 | 27830162.68 | 0.125830E+10 | 0.617145E+09 | 37776.81 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 4805.74 | 0.00 | 0.00 | 32970.24 | 0.00 | 0.47 |
Maximum of Months | 98018273.39 | 0.191181E+09 | 142657.43 | 1903572.63 | 9278076.99 | 0.287391E+09 | 0.132662E+09 | 11501.32 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.345913E+09 | 0.00 | 0.00 | 14423545.69 | 0.00 | 0.732011E+09 | 0.141352E+10 | 0.00 | 0.54 |
February | 0.275896E+09 | 0.00 | 0.00 | 12830453.39 | 0.00 | 0.505693E+09 | 0.130970E+10 | 0.00 | 0.54 |
March | 0.309035E+09 | 71163.65 | 0.00 | 11550383.46 | 0.00 | 0.411362E+09 | 0.140631E+10 | 0.00 | 0.54 |
April | 0.157170E+09 | 24658448.15 | 11453.87 | 12208224.36 | 1022078.75 | 99243123.86 | 0.102758E+10 | 2719.93 | 0.54 |
May | 46339265.86 | 0.131269E+09 | 76240.08 | 9480345.11 | 10595933.80 | 2997025.71 | 0.593599E+09 | 23750.55 | 0.54 |
June | 4146745.59 | 0.283277E+09 | 130109.31 | 4907527.10 | 16917701.73 | 44640.55 | 0.123127E+09 | 52275.97 | 0.54 |
July | 0.00 | 0.121230E+10 | 868820.03 | 28848.96 | 75753193.42 | 0.00 | 213870.91 | 62922.39 | 0.54 |
August | 4508601.37 | 0.611800E+09 | 518756.49 | 2170087.84 | 41007767.01 | 83074.50 | 54459331.90 | 57748.53 | 0.54 |
September | 25299628.23 | 0.568896E+09 | 254040.77 | 6844940.30 | 26770400.22 | 207385.98 | 0.336374E+09 | 22660.02 | 0.54 |
October | 0.162605E+09 | 0.116580E+09 | 66642.37 | 16965541.83 | 4510138.96 | 2208183.89 | 0.122166E+10 | 4732.44 | 0.54 |
November | 0.273557E+09 | 987511.69 | 0.00 | 18404035.81 | 0.00 | 0.426150E+09 | 0.150916E+10 | 0.00 | 0.53 |
December | 0.348665E+09 | 0.00 | 0.00 | 14523613.12 | 0.00 | 0.836535E+09 | 0.131023E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.195314E+10 | 0.294984E+10 | 1926062.92 | 0.124338E+09 | 0.176577E+09 | 0.301653E+10 | 0.103059E+11 | 226809.83 | 0.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 28848.96 | 0.00 | 0.00 | 213870.91 | 0.00 | 0.53 |
Maximum of Months | 0.348665E+09 | 0.121230E+10 | 868820.03 | 18404035.81 | 75753193.42 | 0.836535E+09 | 0.150916E+10 | 62922.39 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.207009E+11 | 0.00 | 0.00 | 31053505.84 | 0.00 | 0.00 | 0.385711E+11 | 0.00 | 5.43 |
February | 0.120036E+11 | 0.00 | 0.00 | 30999709.95 | 0.00 | 0.00 | 0.378741E+11 | 0.00 | 5.68 |
March | 0.844912E+10 | 0.00 | 0.00 | 39951322.92 | 0.00 | 0.00 | 0.430041E+11 | 0.00 | 5.84 |
April | 0.173616E+10 | 0.105701E+09 | 0.00 | 53162231.18 | 1036378.49 | 0.00 | 0.330942E+11 | 0.00 | 5.95 |
May | 0.324789E+09 | 0.605814E+09 | 0.00 | 59289718.19 | 20366040.84 | 0.00 | 0.221919E+11 | 0.00 | 5.85 |
June | 71730827.81 | 0.189024E+10 | 0.00 | 53963891.73 | 30319067.40 | 0.00 | 0.120108E+11 | 0.00 | 5.57 |
July | 2609342.84 | 0.899364E+10 | 0.00 | 26188793.26 | 0.216447E+09 | 0.00 | 0.328317E+10 | 0.00 | 5.47 |
August | 89570082.91 | 0.254352E+10 | 0.00 | 48461827.92 | 73273938.42 | 0.00 | 0.103091E+11 | 0.00 | 5.63 |
September | 0.266243E+09 | 0.159921E+10 | 0.00 | 46984933.64 | 86099586.03 | 0.00 | 0.172555E+11 | 0.00 | 5.87 |
October | 0.172026E+10 | 0.248568E+09 | 0.00 | 48058005.03 | 14640195.65 | 0.00 | 0.375446E+11 | 0.00 | 6.01 |
November | 0.116632E+11 | 0.00 | 0.00 | 35095602.07 | 0.00 | 0.00 | 0.419845E+11 | 0.00 | 5.60 |
December | 0.206400E+11 | 0.00 | 0.00 | 27285160.85 | 0.00 | 0.00 | 0.374413E+11 | 0.00 | 5.32 |
Annual Sum or Average | 0.776682E+11 | 0.159867E+11 | 0.00 | 0.500495E+09 | 0.442183E+09 | 0.00 | 0.334564E+12 | 0.00 | 5.69 |
Minimum of Months | 2609342.84 | 0.00 | 0.00 | 26188793.26 | 0.00 | 0.00 | 0.328317E+10 | 0.00 | 5.32 |
Maximum of Months | 0.207009E+11 | 0.899364E+10 | 0.00 | 59289718.19 | 0.216447E+09 | 0.00 | 0.430041E+11 | 0.00 | 6.01 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110819E+11 | 0.00 | 0.00 | 48190303.43 | 0.00 | 0.00 | 0.487581E+11 | 0.00 | 5.48 |
February | 0.638001E+10 | 0.00 | 0.00 | 45518655.03 | 0.00 | 0.00 | 0.441364E+11 | 0.00 | 5.74 |
March | 0.380641E+10 | 0.00 | 0.00 | 55687812.99 | 0.00 | 0.00 | 0.485176E+11 | 0.00 | 5.93 |
April | 0.826980E+09 | 0.106731E+09 | 0.00 | 67652253.73 | 16840.61 | 0.00 | 0.350164E+11 | 0.00 | 6.10 |
May | 0.156033E+09 | 0.621947E+09 | 0.00 | 70927555.72 | 4440929.61 | 0.00 | 0.232818E+11 | 0.00 | 6.03 |
June | 13948576.73 | 0.192227E+10 | 0.00 | 61434217.11 | 13495325.91 | 0.00 | 0.125865E+11 | 0.00 | 5.75 |
July | 188311.95 | 0.937081E+10 | 0.00 | 28497659.97 | 59229565.01 | 0.00 | 0.343609E+10 | 0.00 | 5.64 |
August | 30371613.71 | 0.263004E+10 | 0.00 | 56229189.47 | 35982979.17 | 0.00 | 0.107936E+11 | 0.00 | 5.81 |
September | 0.114106E+09 | 0.165471E+10 | 0.00 | 55690743.24 | 47889939.64 | 0.00 | 0.180870E+11 | 0.00 | 6.04 |
October | 0.717039E+09 | 0.259658E+09 | 0.00 | 60152624.45 | 8286718.63 | 0.00 | 0.394256E+11 | 0.00 | 6.14 |
November | 0.584614E+10 | 0.00 | 0.00 | 49130133.72 | 0.00 | 0.00 | 0.484342E+11 | 0.00 | 5.66 |
December | 0.128720E+11 | 0.00 | 0.00 | 43109614.49 | 0.00 | 0.00 | 0.456467E+11 | 0.00 | 5.36 |
Annual Sum or Average | 0.418451E+11 | 0.165662E+11 | 0.00 | 0.642221E+09 | 0.169342E+09 | 0.00 | 0.378120E+12 | 0.00 | 5.81 |
Minimum of Months | 188311.95 | 0.00 | 0.00 | 28497659.97 | 0.00 | 0.00 | 0.343609E+10 | 0.00 | 5.36 |
Maximum of Months | 0.128720E+11 | 0.937081E+10 | 0.00 | 70927555.72 | 59229565.01 | 0.00 | 0.487581E+11 | 0.00 | 6.14 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2628210.68 | 0.00 | 0.00 | 0.162188E+09 | 0.00 | 0.00 | 0.667512E+11 | 0.00 | 19.96 |
February | 0.00 | 0.00 | 0.00 | 0.129803E+09 | 0.00 | 0.00 | 0.563107E+11 | 0.00 | 21.41 |
March | 1262069.07 | 0.00 | 0.00 | 0.134876E+09 | 0.00 | 0.00 | 0.576505E+11 | 0.00 | 22.43 |
April | 0.00 | 0.157569E+09 | 0.00 | 0.125142E+09 | 0.00 | 0.00 | 0.372316E+11 | 0.00 | 22.96 |
May | 0.00 | 0.925803E+09 | 0.00 | 0.106302E+09 | 0.00 | 0.00 | 0.223560E+11 | 0.00 | 22.36 |
June | 0.00 | 0.283083E+10 | 0.00 | 78638850.55 | 0.00 | 0.00 | 0.113035E+11 | 0.00 | 21.12 |
July | 0.00 | 0.119678E+11 | 0.00 | 28296853.91 | 0.00 | 0.00 | 0.288729E+10 | 0.00 | 20.85 |
August | 0.00 | 0.354172E+10 | 0.00 | 76472126.47 | 0.00 | 0.00 | 0.101005E+11 | 0.00 | 21.49 |
September | 0.00 | 0.237801E+10 | 0.00 | 84665712.04 | 0.00 | 0.00 | 0.177127E+11 | 0.00 | 22.54 |
October | 0.00 | 0.375977E+09 | 0.00 | 0.116461E+09 | 0.00 | 0.00 | 0.431307E+11 | 0.00 | 23.40 |
November | 779378.61 | 0.00 | 0.00 | 0.143775E+09 | 0.00 | 0.00 | 0.608722E+11 | 0.00 | 21.27 |
December | 0.00 | 0.00 | 0.00 | 0.167293E+09 | 0.00 | 0.00 | 0.655310E+11 | 0.00 | 19.46 |
Annual Sum or Average | 4669658.36 | 0.221777E+11 | 0.00 | 0.135391E+10 | 0.00 | 0.00 | 0.451838E+12 | 0.00 | 21.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 28296853.91 | 0.00 | 0.00 | 0.288729E+10 | 0.00 | 19.46 |
Maximum of Months | 2628210.68 | 0.119678E+11 | 0.00 | 0.167293E+09 | 0.00 | 0.00 | 0.667512E+11 | 0.00 | 23.40 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.879052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66327541.92 | 0.00 | 0.00 | 0.65 |
February | 0.736302E+10 | 0.00 | 0.00 | 5943.41 | 0.00 | 70359816.75 | 5937470.85 | 0.00 | 0.68 |
March | 0.753227E+10 | 0.00 | 0.00 | 154277.40 | 0.00 | 2032644.82 | 0.109881E+09 | 0.00 | 0.70 |
April | 0.294216E+10 | 26153868.38 | 0.00 | 8065238.48 | 134325.02 | 0.00 | 0.232792E+10 | 0.00 | 0.79 |
May | 0.513985E+09 | 0.176261E+09 | 0.00 | 14706968.71 | 0.00 | 0.00 | 0.317258E+10 | 0.00 | 0.93 |
June | 0.00 | 0.618156E+09 | 0.00 | 15047252.85 | 0.00 | 0.00 | 0.229759E+10 | 0.00 | 1.08 |
July | 0.00 | 0.228280E+10 | 0.00 | 6077492.15 | 0.00 | 0.00 | 0.641629E+09 | 0.00 | 1.07 |
August | 11096122.57 | 0.712969E+09 | 0.00 | 13574747.55 | 0.00 | 0.00 | 0.185479E+10 | 0.00 | 1.04 |
September | 0.384216E+09 | 0.447934E+09 | 0.00 | 12385565.18 | 27405.70 | 0.00 | 0.254056E+10 | 0.00 | 1.00 |
October | 0.326424E+10 | 72139632.11 | 0.00 | 8742373.98 | 0.00 | 0.00 | 0.278950E+10 | 0.00 | 0.83 |
November | 0.759872E+10 | 0.00 | 0.00 | 692609.05 | 0.00 | 596923.65 | 0.416127E+09 | 0.00 | 0.67 |
December | 0.830866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392038E+09 | 0.00 | 0.00 | 0.64 |
Annual Sum or Average | 0.467089E+11 | 0.433641E+10 | 0.00 | 79452468.77 | 161730.71 | 0.531355E+09 | 0.161565E+11 | 0.00 | 0.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
Maximum of Months | 0.879052E+10 | 0.228280E+10 | 0.00 | 15047252.85 | 134325.02 | 0.392038E+09 | 0.317258E+10 | 0.00 | 1.08 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:00:07
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.191977E+12 | 0.125798E+11 | 0.147065E+12 | 0.687118E+12 | 0.886772E+11 |
February | 0.199263E+12 | 0.101327E+11 | 0.112997E+12 | 0.555986E+12 | 0.124724E+12 |
March | 0.319238E+12 | 0.967552E+10 | 0.105203E+12 | 0.534734E+12 | 0.186000E+12 |
April | 0.331034E+12 | 0.523688E+10 | 0.551719E+11 | 0.300672E+12 | 0.458486E+12 |
May | 0.362838E+12 | 0.260567E+10 | 0.269484E+11 | 0.163637E+12 | 0.731651E+12 |
June | 0.344683E+12 | 0.259727E+09 | -239365059.4 | 0.357336E+11 | 0.946522E+12 |
July | 0.333635E+12 | -0.345416E+10 | -0.383202E+11 | -0.164160E+12 | 0.118343E+13 |
August | 0.303577E+12 | -509141480.1 | -0.152646E+10 | 0.805422E+09 | 0.100010E+13 |
September | 0.259798E+12 | 0.106262E+10 | 0.134542E+11 | 0.937570E+11 | 0.836146E+12 |
October | 0.244553E+12 | 0.536940E+10 | 0.597133E+11 | 0.336684E+12 | 0.465928E+12 |
November | 0.188828E+12 | 0.102463E+11 | 0.114817E+12 | 0.572403E+12 | 0.161728E+12 |
December | 0.155575E+12 | 0.136553E+11 | 0.158663E+12 | 0.738985E+12 | 0.792107E+11 |
Annual Sum or Average | 0.323500E+13 | 0.668605E+11 | 0.753947E+12 | 0.385636E+13 | 0.626261E+13 |
Minimum of Months | 0.155575E+12 | -0.345416E+10 | -0.383202E+11 | -0.164160E+12 | 0.792107E+11 |
Maximum of Months | 0.362838E+12 | 0.136553E+11 | 0.158663E+12 | 0.738985E+12 | 0.118343E+13 |