Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:59

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880

Simulation Timestamp: 2023-10-16 09:00:00


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 12060.01 1063.00 1063.00
Net Site Energy 12060.01 1063.00 1063.00
Total Source Energy 28654.53 2525.68 2525.68
Net Source Energy 28654.53 2525.68 2525.68


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 127.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 2881.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 766.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 242.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1745.01 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 651.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 620.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 187.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 230.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.74 2663.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 62.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 7480.31 4579.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 127.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 2881.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 766.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 242.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 959.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 14.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 8.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 32.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 620.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 187.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 230.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.74 2663.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 20.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 35.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 127.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 2881.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 766.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 242.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1745.01 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 651.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 620.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 187.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 230.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 90.74 2663.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 62.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 89.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 333.20 245.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 237.13 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 659.33 403.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 89.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 333.20 245.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 237.13 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 659.33 403.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 7480.312 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 7480.312 100.00
     
Total On-Site and Utility Electric Sources 7480.312 100.00
Total Electricity End Uses 7480.312 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 2722.14 87.31
Air to Air Heat Recovery for Heating 395.55 12.69
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 3117.69 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 106.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 8266.33


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:59
RunPeriod RUNPERIOD 1
Weather File Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Latitude [deg] 27.85
Longitude [deg] -82.5
Elevation [m] 8.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 9.1389 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 13.3365 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 13.3365 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 9.2031 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 6.1031 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.8125 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 10.3656 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 8.7188 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 4.5531 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 4.5531 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 6.3938 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 4.5531 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.3656 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.3656 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 11.7219 4.65 2934.4875
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 6.3938 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 6.8557 7.07 41.0709
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 6.8557 7.07 41.0709
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 9.1389 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 13.3365 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 13.3365 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 9.2031 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 6.1031 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.8125 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 10.3656 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 8.7188 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 4.5531 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 4.5531 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 4.5531 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 4.5531 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 4.5531 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 4.5531 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 6.3938 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 4.5531 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 4.5531 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 4.5531 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 10.3656 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 10.3656 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 11.7219 4.65 2934.4875  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 6.3938 18.58 0.0000  
Total 11345.29             6.8557 3.54 41.0709  
Conditioned Total 11345.29             6.8557 3.54 41.0709  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 4.4542 8.82 37.1989
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 09-SEP-20:00 30-DEC-19:30 - - - - - - - - - - 06-JAN-21:30
Heating 0.00 113902.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 234503.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 52161.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 86164.46 83438.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 24483.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 34321.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 7709.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 4443.65 237245.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 2133.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 471307.42 434585.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 113902.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 234503.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 52161.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 56181.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 49984.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 33453.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1755.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 22615.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 112.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 34321.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 7709.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 4443.65 237245.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 216.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 824.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 1093.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 138.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 9126.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2428.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 768.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5526.46 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2063.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1965.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 593.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 731.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 287.39 2887.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 198.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 23690.15 4964.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 12.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 804.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 214.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 67.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 487.11 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 173.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 52.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 64.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 254.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2088.10 437.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 12.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 804.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 214.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 67.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 487.11 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 173.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 52.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 64.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 254.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2088.10 437.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.77 0.543737 0.536000 1.49 1.00 0.500000 0.000701 0.000069 1.49 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.332086 0.153901 0.536000 0.177998 0.536000 0.500000 0.002476 0.000025 0.177998 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.245742 0.240837 0.536000 0.131717 0.642232 0.500000 0.001582 0.000012 0.131717 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.244050 0.512817 0.536000 0.130811 1.00 0.500000 0.000743 0.000017 0.130811 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.117394 0.615077 0.536000 0.062923 1.00 0.500000 0.000619 0.000009 0.062923 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.28 0.072041 0.536000 1.76 0.536000 0.500000 0.020986 0.000095 1.76 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.39 0.103320 0.536000 0.746582 0.536000 0.500000 0.003688 0.000077 0.746582 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 4.56 0.218437 0.536000 2.45 0.582500 0.500000 0.001744 0.000214 2.45 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.41 0.844183 0.536000 0.753606 1.00 0.500000 0.000451 0.000096 0.753606 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.17 0.116568 0.536000 1.16 0.536000 0.500000 0.003268 0.000092 1.16 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.27 0.111269 0.536000 1.22 0.536000 0.500000 0.003424 0.000095 1.22 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.23 0.063441 0.536000 1.20 0.536000 0.500000 0.010802 0.000061 1.20 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.744097 0.422041 0.536000 0.398836 1.00 0.500000 0.000903 0.000059 0.398836 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 7841.71 0.000069 163.53
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 2874.32 0.000025 67.21
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1356.33 0.000012 29.76
MECH_FLR_1 VAV BOX REHEAT COIL 1921.31 0.000017 44.19
STORAGE_FLR_1 VAV BOX REHEAT COIL 1049.82 0.000009 24.70
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 10901.54 0.000095 229.44
CAFE_FLR_1 VAV BOX REHEAT COIL 8776.44 0.000077 195.54
LOBBY_FLR_1 VAV BOX REHEAT COIL 24405.05 0.000214 533.71
ROOM_1_FLR_3 FAN COIL HEATING COIL 4237.21 0.000037 121.07
ROOM_2_FLR_3 FAN COIL HEATING COIL 4235.20 0.000037 121.02
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 24643.65 0.000216 704.16
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 24615.17 0.000215 703.35
ROOM_5_FLR_3 FAN COIL HEATING COIL 4233.67 0.000037 120.97
ROOM_6_FLR_3 FAN COIL HEATING COIL 4231.66 0.000037 120.92
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 10961.28 0.000096 251.73
ROOM_1_FLR_6 FAN COIL HEATING COIL 1298.90 0.000011 37.11
ROOM_2_FLR_6 FAN COIL HEATING COIL 1298.79 0.000011 37.11
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 6264.80 0.000055 179.01
BANQUET_FLR_6 VAV BOX REHEAT COIL 10490.55 0.000092 227.17
DINING_FLR_6 VAV BOX REHEAT COIL 10872.35 0.000095 235.20
KITCHEN_FLR_6 VAV BOX REHEAT COIL 6944.45 0.000061 145.57
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 6696.72 0.000059 157.73
VAV WITH REHEAT HEATING COIL 95011.36 0.000831 1712.14
FLR_3_DOAS HEATING COIL 9002.65 0.000079 162.23
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ZoneExhaust

User-Specified Maximum Flow Rate [m3/s]
LOBBY_FLR_1 EXHAUST FAN 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 0.997593 0.000037 0.000415
ROOM_2_FLR_3 FAN COIL 0.970179 0.000037 0.000404
ROOM_3_MULT19_FLR_3 FAN COIL 5.62 0.000216 0.002287
ROOM_4_MULT19_FLR_3 FAN COIL 5.63 0.000215 0.002441
ROOM_5_FLR_3 FAN COIL 0.893382 0.000037 0.000374
ROOM_6_FLR_3 FAN COIL 0.871300 0.000037 0.000366
ROOM_1_FLR_6 FAN COIL 0.262976 0.000011 0.000109
ROOM_2_FLR_6 FAN COIL 0.255479 0.000011 0.000106
ROOM_3_MULT9_FLR_6 FAN COIL 1.18 0.000055 0.000499
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 0.997593
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 0.970179
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 5.62
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 5.63
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 0.893382
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 0.871300
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.262976
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.255479
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.18
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008740 12.80 0.008500 0.000415 0.997593  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008746 12.80 0.008500 0.000404 0.970179  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008657 12.80 0.008500 0.002287 5.62  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008902 12.80 0.008500 0.002441 5.63  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008768 12.80 0.008500 0.000374 0.893382  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008775 12.80 0.008500 0.000366 0.871300  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008728 12.80 0.008500 0.000109 0.262976  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008734 12.80 0.008500 0.000106 0.255479  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008801 12.80 0.008500 0.000499 1.18  
VAV WITH REHEAT COOLING COIL 29.33 6.70 0.013389 10.99 0.008500 0.029034 21.65 812870.41
FLR_3_DOAS COOLING COIL 33.90 6.70 0.016536 11.94 0.008500 0.003792 2.05 106169.29
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 11.67 11.67 21.77 11.67 21.65 21.65 0.300000 0.538883 21.65
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 21.65 11.66
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 11.66
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 21.65
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.029034 0.000016
VAV WITH REHEAT_HEATC_CONTROLLER 0.000831  
FLR_3_DOAS_COOLC_CONTROLLER 0.003792 0.000126
FLR_3_DOAS_HEATC_CONTROLLER 0.000079  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.039826 8206.57  
HEATSYS1 PUMP 0.002486 748.67 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.002486 0.298320
COOLSYS1 0.039826 4.78
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 284164.92 284164.92 0.002486
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.039826 5681.69
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.039826 1115009.42 1115610.00 127.18
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 24.20 18.90 15.70 13.60 15.50 17.10 21.20 26.90 27.60 27.90 27.40 26.20


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Tampa-MacDill AFB FL USA TMY3 WMO#=747880 27.85 -82.52 -5.00 8.00 101229 1.2032


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 21.85 14.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 9.139 5.380 0.000 0.000 0.000 0.000 14.519 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 13.336 10.760 0.000 0.000 0.000 0.000 24.096 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 13.336 10.760 0.000 0.000 0.000 0.000 24.096 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 9.203 5.380 0.000 0.000 0.000 0.000 14.583 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 6.103 2.690 0.000 0.000 0.000 0.000 8.793 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.813 61.680 535.850 0.000 0.000 0.000 603.343 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 10.366 5.380 0.000 0.000 0.000 0.000 15.746 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 8.719 8.070 0.000 0.000 0.000 0.000 16.789 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 6.394 0.000 0.000 0.000 0.000 0.000 6.394 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 10.366 67.820 0.000 0.000 0.000 0.000 78.186 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 10.366 67.820 0.000 0.000 0.000 0.000 78.186 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 11.722 515.227 2419.260 0.000 0.000 0.000 2946.209 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 6.394 0.000 0.000 0.000 0.000 0.000 6.394 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 18084.325 9.139 169.807 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 18084.325
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 894.495 13.336 82.602 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 894.495
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 1035.829 13.336 82.602 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1035.829
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 1511.551 9.203 569.967 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1511.551
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 578.329 6.103 283.494 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 578.329
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 453.605 5.813 54.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 453.605
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1957.673 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1957.673
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 11405.759 8.719 27.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 11405.759
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 111.660 4.553 74.440 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.660
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 111.691 4.553 74.460 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.691
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 2489.757 6.394 118.803 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2489.757
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 111.691 4.553 74.460 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.691
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 3437.839 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3437.839
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 3437.839 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3437.839
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1210.923 11.722 54.453 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1210.923
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 2635.024 6.394 118.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2635.024


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 457.500 4.429 20.573 0.000 0.250 0.000 0.750 ReachInFreezer 457.500 457.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 285.000 2.759 12.816 0.000 0.250 0.000 0.750 ReachInRefrigerator 285.000 285.000


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.464 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.198 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 1.287 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.608 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.684 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.370 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.442 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2887
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.8346
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.6100
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.4545
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.4264
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.5624
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.5260
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.4637404 3.4637404 3.4637404  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.1981135 1.1981135 1.1981135  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
21 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
22 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
23 0 21.361010 0.87247630E-01 5.4456762  
24 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
25 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
26 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
27 0 21.361010 0.87247630E-01 5.4456762  
28 9 0.16691074E-14 0.45207920E-16 -0.13282787E-09 -0.59403108E-17
29 8 0.19494068E-07 0.16957001E-12 0.35230437E-03 -0.22165426E-09
30 7 -0.11479370E-01 0.90467759E-08 -0.21987867E-01 0.13052461E-03
31 6 0.38463807 0.31869432E-05 0.45441076 -0.45036152E-02
32 5 -4.9884079 0.12028467E-03 -4.3052891 0.60677235E-01
33 4 32.108494 0.99355415E-03 20.908458 -0.41024850
34 3 -109.32288 0.21841230E-02 -54.572312 1.4876971
35 2 195.24423 0.12380226E-02 76.910992 -2.8707534
36 1 -170.46733 0.13310261E-03 -54.975783 2.7333683
37 0 57.057407 0.76355891E-06 15.605832  
38 9 0.14115123E-14 0.53960859E-16 -0.11739578E-09 -0.22900007E-17
39 8 0.17311930E-07 0.20639465E-12 0.32798840E-03 -0.19684260E-09
40 7 -0.10748946E-01 0.11327704E-07 -0.20934514E-01 0.12221941E-03
41 6 0.36478417 0.40360747E-05 0.43737925 -0.42695883E-02
42 5 -4.7945715 0.15382307E-03 -4.1739388 0.58273831E-01
43 4 31.250576 0.12816568E-02 20.393829 -0.39885853
44 3 -107.49604 0.28390629E-02 -53.554356 1.4613070
45 2 193.43186 0.16201491E-02 75.979619 -2.8419759
46 1 -169.79719 0.17527083E-03 -54.709122 2.7216233
47 0 57.057407 0.10123612E-05 15.653272  
48 9 0.65135446E-15 0.56204292E-16 -0.11372497E-09 -0.53489081E-17
49 8 0.16791160E-07 0.21454591E-12 0.32203280E-03 -0.19092129E-09
50 7 -0.10569524E-01 0.11862766E-07 -0.20675571E-01 0.12017931E-03
51 6 0.35990649 0.42391557E-05 0.43318136 -0.42120931E-02
52 5 -4.7469406 0.16196889E-03 -4.1415055 0.57683257E-01
53 4 31.039704 0.13525358E-02 20.266625 -0.39605902
54 3 -107.04684 0.30019179E-02 -53.302690 1.4548183
55 2 192.98603 0.17160237E-02 75.749609 -2.8348971
56 1 -169.63227 0.18593554E-03 -54.643729 2.7187328
57 0 57.057407 0.10758168E-05 15.665287  
58 9 0.10314710E-14 0.47183642E-16 -0.12881513E-09 -0.40099708E-17
59 8 0.18927665E-07 0.17950474E-12 0.34608657E-03 -0.21521408E-09
60 7 -0.11292911E-01 0.96443222E-08 -0.21719088E-01 0.12840450E-03
61 6 0.37957032 0.34070209E-05 0.45007157 -0.44438791E-02
62 5 -4.9389364 0.12890179E-03 -4.2718596 0.60063826E-01
63 4 31.889569 0.10670331E-02 20.777560 -0.40734193
64 3 -108.85680 0.23501275E-02 -54.313423 1.4809641
65 2 194.78196 0.13343675E-02 76.673975 -2.8634131
66 1 -170.29645 0.14368413E-03 -54.907648 2.7303734
67 0 57.057407 0.82565881E-06 15.617726  
68 9 0.86975537E-15 0.52023775E-16 -0.12536948E-09 -0.54620444E-17
69 8 0.18440443E-07 0.18784465E-12 0.34068694E-03 -0.20967419E-09
70 7 -0.11130813E-01 0.10155400E-07 -0.21485363E-01 0.12656138E-03
71 6 0.37516444 0.35965268E-05 0.44629465 -0.43919449E-02
72 5 -4.8959230 0.13636263E-03 -4.2427425 0.59530495E-01
73 4 31.699203 0.11309484E-02 20.663505 -0.40481456
74 3 -108.45147 0.24950915E-02 -54.087828 1.4751087
75 2 194.37988 0.14187814E-02 76.467519 -2.8570287
76 1 -170.14779 0.15298304E-03 -54.848449 2.7277680
77 0 57.057407 0.88039223E-06 15.628184  
78 7 -0.15963512E-14 -0.15187529E-16 -0.22427203E-13 0.56155309E-15
79 6 0.17983713E-10 0.23594901E-11 0.52322926E-09 -0.18637893E-10
80 5 -0.60139213E-07 0.11510628E-07 -0.21924491E-05 0.17161312E-06
81 4 0.62746279E-04 0.43399923E-05 0.17681060E-02 -0.28244642E-03
82 3 -0.90508353E-02 0.15320797E-03 -0.21560640 0.43341486E-01
83 2 0.12836503 0.66328859E-03 2.9007871 -0.61911613
84 1 -0.32478029 0.41934727E-03 -7.1379041 1.5697129
85 0 0.20664896 0.54311639E-05 4.4522013  
86 7 -0.22427203E-13 -0.15187529E-16 -0.15963512E-14 0.56155309E-15
87 6 0.52322926E-09 0.23594901E-11 0.17983713E-10 -0.18637893E-10
88 5 -0.21924491E-05 0.11510628E-07 -0.60139213E-07 0.17161312E-06
89 4 0.17681060E-02 0.43399923E-05 0.62746279E-04 -0.28244642E-03
90 3 -0.21560640 0.15320797E-03 -0.90508353E-02 0.43341486E-01
91 2 2.9007871 0.66328859E-03 0.12836503 -0.61911613
92 1 -7.1379041 0.41934727E-03 -0.32478029 1.5697129
93 0 4.4522013 0.54311639E-05 0.20664896  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
103 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
104 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
105 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
106 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
107 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
108 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
109 0 1.0055995 0.48413807E-04 60.838472  
110 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
111 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
112 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
113 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
114 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
115 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
116 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
117 0 1.0055995 0.48413807E-04 60.838472  
118 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
119 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
120 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
121 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
122 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
123 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
124 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
125 0 1.0055995 0.48413807E-04 60.838472  
126 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
127 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
128 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
129 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
130 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
131 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
132 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
133 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.5119_SHGC_0.25 37 1 VerySmooth 2.910 2.910 1.000 0.251    
2 RESWINDOW_U_0.5119_SHGC_0.25 38 1 VerySmooth 2.910 2.910 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   1.79780E-002 0.16139 0.60964 0.60964 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10364 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   1.79780E-002 0.16139 0.60964 0.60964 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10364 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 1.500
2 RACK2 1 0 Zone Air-Cooled 3.000


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 0.576 0.5074
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 0.263 2.9576E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 3.921E-002 5.846E-004 2.885E-004 0.531 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 1.513E-002 1.949E-004 5.306E-004 0.177 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 3.577E-002 2.178E-004 5.696E-004 0.198 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 2.064E-002 2.178E-004 4.726E-004 0.198 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 4.884E-002 6.258E-004 5.569E-004 0.569 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 8.667E-002 4.589E-004 2.527E-004 0.417 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.248 1.893E-004 3.620E-004 0.172 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 6.349E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 6.350E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 2.751E-002 7.066E-005 5.696E-004 8.345E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.164E-002 4.746E-004 2.589E-004 0.561 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 4.974E-002 4.815E-004 2.609E-004 0.569 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 4.868E-002 1.181E-004 9.784E-005 0.140 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 7.9383E-002
2 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 3.0965E-002
3 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 8.6910E-002
4 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 3.2378E-002
5 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 6.2349E-002
6 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 2.1734E-002
7 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 2.6511E-002
8 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 8.7811E-003
9 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 8.8163E-002
10 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 3.8604E-002
11 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 9.6456E-002
12 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 4.0466E-002
13 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 6.8809E-002
14 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 2.7805E-002
15 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 2.9789E-002
16 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 1.2036E-002
17 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.0093E-002
18 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.1312E-002
19 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.5624E-002
20 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 8.6155E-003
21 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.4825E-002
22 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 5.9174E-003
23 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.6108E-002
24 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 9.2309E-003
25 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.0093E-002
26 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.1312E-002
27 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.5624E-002
28 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 8.6155E-003
29 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.4825E-002
30 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 5.9174E-003
31 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.6108E-002
32 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 9.2309E-003


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 38136.02205 38136.02205 2.77316 2.77316 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 20:30:00 29.59450 1.65283E-002 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 0.85446   00:10:00 4.60000 5.25715E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 4565.97384 4565.97384 0.33209 0.33209 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 33.90000 1.65364E-002 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 1935.84713 1935.84713 8.30432E-002 8.30432E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4.60000 5.25715E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3378.92311 3378.92311 0.24574 0.24574 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 32.13567 1.65331E-002 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 661.88467 661.88467 2.83937E-002 9.17347E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4.60000 5.25715E-003 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 3356.36047 3356.36047 0.24405 0.24405 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 31.21400 1.65313E-002 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1231.73400 1231.73400 5.28392E-002 5.28392E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4.60000 5.25715E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1614.48054 1614.48054 0.11739 0.11739 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 33.21533 1.65351E-002 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 718.11366 718.11366 3.08058E-002 5.77652E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4.60000 5.25715E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 45041.57727 45041.57727 3.27553 3.27553 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 33.66300 1.65359E-002 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 1646.89854 1646.89854 7.06479E-002 7.06479E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4.60000 5.25715E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 19135.79629 19135.79629 1.39288 1.39288 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 33.90000 1.65364E-002 188.86188 142.30000 0.67639 0.00000
14 CAFE_FLR_1 Heating 4839.89282 4839.89282 0.20762 0.67639 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4.60000 5.25715E-003 188.86188 142.30000 0.67639 0.00000
15 LOBBY_FLR_1 Cooling 62730.24101 62730.24101 4.56349 4.56349 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 33.90000 1.65364E-002 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 11508.50565 11508.50565 0.49369 1.89399 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4.60000 5.25715E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 10179.86851 10179.86851 0.99759 0.99759 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 32.79400 1.65343E-002 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 4237.25496 4237.25496 0.18284 0.18284 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4.60000 5.25715E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 9900.10973 9900.10973 0.97018 0.97018 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 32.79400 1.65343E-002 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 4235.24479 4235.24479 0.18275 0.18275 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4.60000 5.25715E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 57361.57046 57361.57046 5.62070 5.62070 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 33.90000 1.65364E-002 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 24643.78403 24643.78403 1.06338 1.06338 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4.60000 5.25715E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 57445.96751 57445.96751 5.62940 5.62940 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 33.74200 1.65361E-002 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 24615.31048 24615.31048 1.06215 1.06215 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4.60000 5.25715E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 9116.42815 9116.42815 0.89338 0.89338 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:20:00 31.29300 1.65315E-002 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 4233.71740 4233.71740 0.18268 0.18268 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4.60000 5.25715E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 8891.07777 8891.07777 0.87130 0.87130 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 30.89800 1.65307E-002 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 4231.70653 4231.70653 0.18260 0.18260 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4.60000 5.25715E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 19334.96899 19334.96899 1.40598 1.40598 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 33.82100 1.65362E-002 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 6987.34051 6987.34051 0.29975 0.47476 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4.60000 5.25715E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 2683.52236 2683.52236 0.26298 0.26298 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 32.89933 1.65345E-002 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 1298.91103 1298.91103 5.60474E-002 5.60474E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4.60000 5.25715E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2607.01710 2607.01710 0.25548 0.25548 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 32.79400 1.65343E-002 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 1298.80831 1298.80831 5.60429E-002 5.60429E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4.60000 5.25715E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 12047.33369 12047.33369 1.18061 1.18061 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 33.90000 1.65364E-002 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 6264.85982 6264.85982 0.27033 0.27033 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4.60000 5.25715E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 29777.68796 29777.68796 2.16803 2.16803 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 33.90000 1.65364E-002 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 4362.32561 4362.32561 0.18714 1.18780 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4.60000 5.25715E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 31196.41791 31196.41791 2.27129 2.27129 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 33.90000 1.65364E-002 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 4452.29484 4452.29484 0.19099 1.18780 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:20:00 4.60000 5.25715E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 30609.80503 30609.80503 2.23175 2.23175 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 33.18900 1.65350E-002 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 670.01999 670.01999 2.87401E-002 0.36735 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 4.60000 5.25715E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 10232.77293 10232.77293 0.74410 0.74410 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 33.90000 1.65364E-002 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 4593.31909 4593.31909 0.19705 0.19705 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:20:00 4.60000 5.25715E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 432590.94 21.64901 21.64901 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 105264.74 7.19560 7.19560 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:20:00
3 FLR_3_DOAS Cooling Sensible 52327.60 16.05588 2.05125 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 FLR_3_DOAS Heating Sensible 30007.77 3.23882 2.05125 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.77316
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.54374
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.53600
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.48641
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.00706E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.86027E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.48641
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7841.70977
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.86027E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 163.52534
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.33209
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15390
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.53600
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.17800
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.53600
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.47562E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.51458E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.17800
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2874.32293
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.51458E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 67.20531
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.24574
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24084
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.53600
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13172
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.64223
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.58198E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.18658E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13172
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1356.33391
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.18658E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 29.75784
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.24405
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.51282
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.53600
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13081
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.42955E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.68084E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13081
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1921.30626
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.68084E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 44.19336
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.11739
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.61508
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.53600
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 6.29234E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.19435E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.18426E-006
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.29234E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1049.81734
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.18426E-006
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 24.69607
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.27553
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.20414E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.53600
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.75568
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.53600
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.09864E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.53714E-005
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.75568
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10901.54092
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.53714E-005
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 229.43884
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.39288
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10332
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.53600
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.74658
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.53600
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.68756E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.67801E-005
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.74658
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8776.43929
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.67801E-005
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 195.54034
99 Fan:ZoneExhaust LOBBY_FLR_1 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.56349
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21844
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.53600
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.44603
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.58250
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.74421E-003
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.13506E-004
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.44603
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
110 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 24405.04972
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.13506E-004
113 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 533.71281
114 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
115 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.99759
116 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.99759
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.70689E-005
118 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.14777E-004
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68254
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.73977E-003
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.14777E-004
125 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.99759
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4237.20616
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.70689E-005
128 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 121.07474
129 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
130 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.97018
131 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.97018
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.70513E-005
133 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.04047E-004
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68252
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.74608E-003
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.04047E-004
140 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.97018
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4235.19601
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.70513E-005
143 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 121.01731
144 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
145 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.62070
146 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 5.62070
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.15593E-004
148 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.28654E-003
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68343
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.65728E-003
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.28654E-003
155 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.62070
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 24643.64563
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.15593E-004
158 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 704.16313
159 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
160 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.62940
161 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 5.62940
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.15344E-004
163 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.44058E-003
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68252
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.90244E-003
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.44058E-003
170 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.62940
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 24615.17222
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.15344E-004
173 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 703.34969
174 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
175 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.89338
176 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.89338
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.70380E-005
178 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.74239E-004
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68249
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.76840E-003
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.74239E-004
185 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.89338
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4233.66864
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.70380E-005
188 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 120.97367
189 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
190 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.87130
191 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.87130
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.70204E-005
193 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.65610E-004
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68247
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.77493E-003
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.65610E-004
200 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.87130
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4231.65779
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.70204E-005
203 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 120.91622
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.40598
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.84418
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.53600
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.75361
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.51324E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.58940E-005
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.75361
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
214 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10961.27834
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.58940E-005
217 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 251.73044
218 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
219 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.26298
220 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.26298
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.13633E-005
222 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.08989E-004
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68256
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.72755E-003
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.08989E-004
229 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.26298
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1298.89646
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.13633E-005
232 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 37.11376
233 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
234 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.25548
235 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.25548
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.13624E-005
237 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.06064E-004
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68255
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.73409E-003
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.06064E-004
244 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.25548
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1298.79375
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.13624E-005
247 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 37.11083
248 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
249 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.18061
250 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.18061
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.48072E-005
252 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.98734E-004
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68242
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.80082E-003
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.98734E-004
259 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.18061
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6264.80329
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.48072E-005
262 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 179.00510
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.16803
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11657
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.53600
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.16206
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.53600
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.26847E-003
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.17759E-005
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.16206
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
273 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10490.55240
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.17759E-005
276 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 227.17119
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.27129
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11127
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.53600
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.21741
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.53600
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.42415E-003
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.51160E-005
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.21741
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
287 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10872.34578
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.51160E-005
290 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 235.20450
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.23175
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.34409E-002
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.53600
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.19622
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.53600
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.08018E-002
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.07531E-005
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.19622
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
301 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6944.45149
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.07531E-005
304 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 145.57230
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.74410
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.42204
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.53600
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.39884
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.02757E-004
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.85858E-005
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.39884
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
315 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6696.72215
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.85858E-005
318 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 157.72666
319 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 11.66629
320 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 11.66629
321 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 21.76547
322 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 11.66629
323 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 21.64901
324 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 21.64901
325 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
326 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.53888
327 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
328 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
329 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
333 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
334 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
335 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 21.64901
336 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
337 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.64901
338 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 11.66146
339 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 11.66146
340 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 29.32755
341 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.99148
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.33887E-002
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 812870.41485
346 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.90338E-002
347 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 21.64901
348 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 95011.36229
349 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.31201E-004
350 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1712.13903
351 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 21.64901
352 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 2.90338E-002
353 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 1.64012E-005
354 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 8.31201E-004
355 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
356 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
357 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
358 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 33.90000
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.94120
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.65364E-002
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 106169.29401
364 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.79212E-003
365 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
366 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 9002.64818
367 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 7.87591E-005
368 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 162.23097
369 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
370 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 3.79212E-003
371 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.25574E-004
372 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 7.87591E-005
373 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 3.98256E-002
374 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 8206.57038
375 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.48600E-003
376 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.29832
377 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.48600E-003
378 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 748.67363
379 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
380 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 284164.92074
381 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 284164.92000
382 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.48600E-003
383 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 3.98256E-002
384 PlantLoop COOLSYS1 Plant Loop Volume [m3] 4.77907
385 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 3.98256E-002
386 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 5681.68546
387 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 3.98256E-002
388 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1115009.41630
389 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1115610.00000
390 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 127.17954
391 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
392 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
393 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
394 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
395 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 7882.21
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 2887.41
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1362.92
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 1930.19
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1054.57
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 10957.35
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 8818.38
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 24525.68
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 4563.56
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 4561.39
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 26541.54
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 26510.88
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 4559.75
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 4557.58
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 11012.06
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 1398.91
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 1398.80
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 6747.18
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 10542.86
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 10926.60
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 6980.14
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 6727.00
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 80554.85
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 7632.84


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 16961.78 13592.36 3369.42 0.80 1898.13 19.25
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 16513.27 13227.63 3285.64 0.80 1847.72 18.74
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 94227.12 75912.76 18314.35 0.81 10561.30 107.12
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 98309.11 77993.71 20315.40 0.79 10972.14 111.29
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 15263.26 12209.08 3054.18 0.80 1707.18 17.32
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 14902.25 11915.42 2986.84 0.80 1666.61 16.90
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 4462.05 3578.47 883.58 0.80 499.44 5.07
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 4339.66 3478.86 860.80 0.80 485.69 4.93
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 20279.55 16188.75 4090.80 0.80 2266.98 22.99
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 663720.49 435353.26 228367.22 0.66 79291.39 804.22
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 67341.95 43306.32 24035.63 0.64 8019.03 81.33


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 3.93 13.40


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.940 0.824   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.198 1.198   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.608 1.296   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.608 1.296   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.608 1.296   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.608 1.296   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.442 1.186   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.442 1.186   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.442 1.186   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.442 1.186   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.442 1.186   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.9184408884E-002 2.4194260158E-002 Pass Pass 9.9895125821E-003 2.0955355867E-002 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 3.4588831679E-002 4.3899167260E-002 Pass Pass 1.6087205144E-002 1.7261400962E-002 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 2.1806045430E-002 2.7582854423E-002 Pass Pass 1.1071190978E-002 2.2207223274E-002 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 1.7196091581E-002 1.6703445717E-002 Pass Pass 1.0475207527E-002 2.2345602754E-002 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 1.0827481077E-002 1.0309012347E-002 Pass Pass 1.0188443109E-002 2.2493376891E-002 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 8.6492297384E-002 0.2203468118 Pass Pass 2.0628296342E-002 4.8351211949E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 1.7566132599E-002 3.9881728079E-002 Pass Pass 1.5388743674E-002 1.9460260489E-002 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 1.7223078325E-002 3.2475363873E-002 Pass Pass 1.5025020035E-002 2.4851188910E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 8.5749682622E-002 0.2911283448 Pass Pass 0.1435349708 0.5681051774 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 6.7136653569E-002 0.2291813397 Pass Pass 0.1075100253 0.3589855725 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 8.4262152616E-003 3.6434644234E-002 Pass Pass 2.9476686085E-002 3.8486828540E-002 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 3.5310144404E-002 0.1183211748 Pass Pass 7.5463237841E-002 0.2157102558 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 9.2321091991E-002 0.3215543247 Pass Pass 0.1288110989 0.4761813117 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 8.2345121002E-002 0.2776431577 Pass Pass 0.1299987086 0.4637114527 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 1.2326227551E-002 1.0390696029E-002 Pass Pass 9.7531893011E-003 2.0967318919E-002 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 7.9828576778E-002 0.2759544913 Pass Pass 0.1472643652 0.5603474334 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 5.9318775528E-002 0.2146851938 Pass Pass 0.1424190088 0.5088718964 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 9.2575687654E-002 0.3090616332 Pass Pass 0.1254345857 0.5491446037 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 1.8491197893E-002 4.7717673638E-002 Pass Pass 1.5620337958E-002 3.8870032778E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 1.4757114956E-002 4.2948248247E-002 Pass Pass 1.5202327255E-002 3.7510403132E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 1.5273447167E-002 4.0907276373E-002 Pass Pass 1.9737088520E-002 3.8949466335E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 2.2511969799E-002 1.8126331867E-002 Pass Pass 9.9847647449E-003 1.9345973783E-002 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3161.18 -48.7 -621.4 -2658.1 12625.01 12457.94



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 4.60 0.00 4.60 Wetbulb [C] 2.50 10.00
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 33.90 7.90 25.10 Wetbulb [C] 3.10 270.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 66.00 12      
Feb 66.00 22      
Mar 126.00 32      
Apr 206.00 19      
May 144.00 46      
Jun 99.00 30      
Jul 192.00 52      
Aug 240.00 34      
Sep 310.00 44      
Oct 34.00 10      
Nov 63.00 12      
Dec 35.00 24      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.845 0.940 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.079 1.287 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.079 1.287 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.079 1.287 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.079 1.287 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 1.079 1.287 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.55 0.221 0.228 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.137 1.370 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.137 1.370 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.137 1.370 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.137 1.370 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.137 1.370 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.137 1.370 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.137 1.370 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.137 1.370 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.137 1.370 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.137 1.370 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 1.296 1.608 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 1.296 1.608 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 1.296 1.608 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 1.296 1.608 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.186 1.442 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.186 1.442 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 1.186 1.442 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.186 1.442 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.186 1.442 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.345 1.684 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.55 0.221 0.228 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.55 0.221 0.228 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.186 0.196 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.186 0.196 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.186 0.196 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.186 0.196 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.186 0.196 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.186 0.196 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.186 0.196 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.186 0.196 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.186 0.196 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.186 0.196 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.185 0.196 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.185 0.196 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.185 0.196 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.188 0.196 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   23.26 0.00 0.00 23.26 23.26 2.910 0.251 0.251             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   65.50 0.00 0.00 65.50 65.50 2.910 0.251 0.251             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   85.08 0.00 0.00 85.08 85.08 2.910 0.251 0.251             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.910 0.251 0.251             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.910 0.251 0.251             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.910 0.251 0.251             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.910 0.251 0.251             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   3.68 0.00 0.00 3.68 279.56 2.910 0.251 0.251             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   3.68 0.00 0.00 3.68 279.65 2.910 0.251 0.251             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.910 0.251 0.251             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.910 0.251 0.251             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.910 0.251 0.251             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.910 0.251 0.251             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.910 0.251 0.251             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   2.15 0.00 0.00 2.15 8.59 2.910 0.251 0.251             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   2.15 0.00 0.00 2.15 8.58 2.910 0.251 0.251             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.910 0.251 0.251             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.910 0.251 0.251             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.910 0.251 0.251             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.910 0.251 0.251             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.910 0.251 0.251             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   6.74 0.00 0.00 6.74 60.70 2.910 0.251 0.251             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.910 0.251 0.251             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.910 0.251 0.251             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.910 0.251 0.251             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.910 0.251 0.251             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.910 0.251 0.251             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   5.82 0.00 0.00 5.82 5.82 2.910 0.251 0.251             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   5.21 0.00 0.00 5.21 5.21 2.910 0.251 0.251             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.910 0.251 0.251             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.910 0.251 0.251                      
North Total or Average             432.95 2.910 0.251 0.251                      
Non-North Total or Average             780.84 2.910 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.016 1.198 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 9.1389 1978.83 18084.33 LightsWired LTG_SCH_BASEMENT 51.16 168.00 51.10 0.0000 Y 173.46
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 13.3365 67.07 894.50 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 8.61
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 13.3365 77.67 1035.83 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 9.97
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 9.2031 164.24 1511.55 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 16.63
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 6.1031 94.76 578.33 LightsWired LTG_SCH_STORAGE 25.68 168.00 25.65 0.0000 Y 2.78
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.8125 78.04 453.60 LightsWired LTG_SCH_LAUNDRY 51.36 168.00 51.30 0.0000 Y 4.37
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 10.3656 188.86 1957.67 LightsWired LTG_SCH_DINING 58.69 168.00 49.00 0.0000 Y 18.01
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 8.7188 1308.19 11405.76 LightsWired LTG_SCH_LOBBY 58.69 168.00 56.97 0.0000 Y 121.98
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 4.5531 156.09 710.69 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 4.5531 156.07 710.61 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 4.5531 1863.81 8486.17 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 76.02
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 4.5531 1864.32 8488.49 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 76.04
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 4.5531 156.09 710.69 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 4.5531 156.07 710.61 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 6.3938 1557.62 9959.03 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 109.60
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 4.5531 39.02 177.67 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.59
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 4.5531 39.02 177.65 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.59
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 4.5531 220.77 1005.22 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 9.00
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 10.3656 331.66 3437.84 LightsWired LTG_SCH_DINING 58.69 168.00 53.84 0.0000 Y 34.74
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 10.3656 331.66 3437.84 LightsWired LTG_SCH_DINING 58.69 168.00 53.84 0.0000 Y 34.74
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 11.7219 103.30 1210.92 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 13.33
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 6.3938 412.12 2635.02 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 29.00
Interior Lighting Total       6.8557 11345.29 77780.02               507.58


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.07 11405.76 798.40
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.00 11405.76 0.00
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.39 1957.67 763.49
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.00 1957.67 0.00
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3437.84 687.57
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.00 3437.84 0.00
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3437.84 687.57
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.00 3437.84 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 15448.40 AstronomicalClock -   83.73 83.73 242.79
Exterior Lighting Total 15448.40           242.79



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 284164.92 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 1115610.00 2.96 1115806.10 2.96 3.93 13.40


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11612.86 16961.78 13592.36 3369.42 0.80 - 1898.13 19.25
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11312.45 16513.27 13227.63 3285.64 0.80 - 1847.72 18.74
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 64018.29 94227.12 75912.76 18314.35 0.81 - 10561.30 107.12
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 68331.06 98309.11 77993.71 20315.40 0.79 - 10972.14 111.29
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10477.89 15263.26 12209.08 3054.18 0.80 - 1707.18 17.32
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10236.29 14902.25 11915.42 2986.84 0.80 - 1666.61 16.90
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3051.45 4462.05 3578.47 883.58 0.80 - 499.44 5.07
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2969.57 4339.66 3478.86 860.80 0.80 - 485.69 4.93
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 13963.49 20279.55 16188.75 4090.80 0.80 - 2266.98 22.99
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 812870.41 663720.49 435353.26 228367.22 0.66 - 79291.39 804.22
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 106169.29 67341.95 43306.32 24035.63 0.64 - 8019.03 81.33
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 7841.71 7882.21 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2874.32 2887.41 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1356.33 1362.92 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1921.31 1930.19 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1049.82 1054.57 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 10901.54 10957.35 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 8776.44 8818.38 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 24405.05 24525.68 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 4237.21 4563.56 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 4235.20 4561.39 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 24643.65 26541.54 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 24615.17 26510.88 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 4233.67 4559.75 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 4231.66 4557.58 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 10961.28 11012.06 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1298.90 1398.91 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1298.79 1398.80 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 6264.80 6747.18 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 10490.55 10542.86 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 10872.35 10926.60 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 6944.45 6980.14 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 6696.72 6727.00 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 95011.36 80554.85 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 9002.65 7632.84 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.00 701.94 703.64 1.00 1.20 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.97 682.65 703.64 1.00 1.20 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 5.62 3954.93 703.64 1.00 0.96 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 5.63 3961.05 703.64 1.00 0.96 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.89 628.62 703.64 1.00 1.23 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:20:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.87 613.08 703.64 1.00 1.23 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.26 185.04 703.64 1.00 1.81 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.26 179.76 703.64 1.00 1.83 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.18 830.72 703.64 1.00 1.16 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 21.65 48507.61 2240.64 1.00 1.11 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.039826 8206.57 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.002486 748.67 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.039826 5681.69 142664.32 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.80 0.58 0.51
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.80 0.26 0.03



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 38136.02 38136.02 19.27 2.773 2.773 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 20:30:00 24.00 24.00 0.00913 29.59 0.01653 0.854 0.00
RETAIL_1_FLR_1 4565.97 4565.97 68.08 0.332 0.332 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 24.00 24.00 0.00924 33.90 0.01654 0.079 0.00
RETAIL_2_FLR_1 3378.92 3378.92 43.50 0.246 0.246 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 24.00 24.00 0.00944 32.14 0.01653 0.092 0.00
MECH_FLR_1 3356.36 3356.36 20.44 0.244 0.244 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 24.00 24.00 0.00894 31.21 0.01653 0.000 0.00
STORAGE_FLR_1 1614.48 1614.48 17.04 0.117 0.117 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 24.00 24.00 0.00909 33.22 0.01654 0.058 0.00
LAUNDRY_FLR_1 45041.58 45041.58 577.16 3.276 3.276 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 24.00 24.00 0.00857 33.66 0.01654 0.000 0.00
CAFE_FLR_1 19135.80 19135.80 101.32 1.393 1.393 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 24.00 23.99 0.01027 33.90 0.01654 0.676 0.00
LOBBY_FLR_1 62730.24 62730.24 47.95 4.563 4.563 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 24.00 23.99 0.01011 33.90 0.01654 1.894 0.00
ROOM_1_FLR_3 10179.87 10179.87 260.87 0.998 0.998 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 21.11 21.11 0.00874 32.79 0.01653 0.062 0.00
ROOM_2_FLR_3 9900.11 9900.11 253.74 0.970 0.970 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 21.11 21.11 0.00875 32.79 0.01653 0.062 0.00
ROOM_3_MULT19_FLR_3 57361.57 57361.57 2339.01 5.621 5.621 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 21.11 21.11 0.00866 33.90 0.01654 0.837 0.00
ROOM_4_MULT19_FLR_3 57445.97 57445.97 2341.81 5.629 5.629 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 21.11 21.11 0.00890 33.74 0.01654 0.837 0.00
ROOM_5_FLR_3 9116.43 9116.43 233.62 0.893 0.893 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:20:00 21.11 21.11 0.00877 31.29 0.01653 0.062 0.00
ROOM_6_FLR_3 8891.08 8891.08 227.87 0.871 0.871 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 21.11 21.11 0.00877 30.90 0.01653 0.062 0.00
CORRIDOR_FLR_3 19334.97 19334.97 49.65 1.406 1.406 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 24.00 24.00 0.00961 33.82 0.01654 0.475 0.00
ROOM_1_FLR_6 2683.52 2683.52 68.77 0.263 0.263 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 21.11 21.11 0.00873 32.90 0.01653 0.015 0.00
ROOM_2_FLR_6 2607.02 2607.02 66.82 0.255 0.255 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 21.11 21.11 0.00873 32.79 0.01653 0.015 0.00
ROOM_3_MULT9_FLR_6 12047.33 12047.33 491.12 1.181 1.181 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 21.11 21.11 0.00880 33.90 0.01654 0.099 0.00
BANQUET_FLR_6 29777.69 29777.69 89.78 2.168 2.168 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 24.00 23.98 0.01043 33.90 0.01654 1.188 0.00
DINING_FLR_6 31196.42 31196.42 94.06 2.271 2.271 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 24.00 23.98 0.01035 33.90 0.01654 1.188 0.00
KITCHEN_FLR_6 30609.81 30609.81 296.31 2.232 2.232 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 24.00 23.97 0.01013 33.19 0.01654 0.367 0.00
CORRIDOR_FLR_6 10232.77 10232.77 24.83 0.744 0.744 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 24.00 24.00 0.00911 33.90 0.01654 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 0.854   00:10:00 21.00 23.72 0.00526 4.60 0.00526 0.854 0.00
RETAIL_1_FLR_1 1935.85 1935.85 28.86 0.083 0.083 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00770 4.60 0.00526 0.079 0.00
RETAIL_2_FLR_1 661.88 661.88 8.52 0.028 0.092 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00766 4.60 0.00526 0.092 0.00
MECH_FLR_1 1231.73 1231.73 7.50 0.053 0.053 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00759 4.60 0.00526 0.000 0.00
STORAGE_FLR_1 718.11 718.11 7.58 0.031 0.058 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00759 4.60 0.00526 0.058 0.00
LAUNDRY_FLR_1 1646.90 1646.90 21.10 0.071 0.071 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00758 4.60 0.00526 0.000 0.00
CAFE_FLR_1 4839.89 4839.89 25.63 0.208 0.676 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00773 4.60 0.00526 0.676 0.00
LOBBY_FLR_1 11508.51 11508.51 8.80 0.494 1.894 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00768 4.60 0.00526 1.894 0.00
ROOM_1_FLR_3 4237.25 4237.25 108.59 0.183 0.183 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00768 4.60 0.00526 0.062 0.00
ROOM_2_FLR_3 4235.24 4235.24 108.55 0.183 0.183 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00768 4.60 0.00526 0.062 0.00
ROOM_3_MULT19_FLR_3 24643.78 24643.78 1004.89 1.063 1.063 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00771 4.60 0.00526 0.837 0.00
ROOM_4_MULT19_FLR_3 24615.31 24615.31 1003.46 1.062 1.062 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00771 4.60 0.00526 0.837 0.00
ROOM_5_FLR_3 4233.72 4233.72 108.50 0.183 0.183 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00768 4.60 0.00526 0.062 0.00
ROOM_6_FLR_3 4231.71 4231.71 108.46 0.183 0.183 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00768 4.60 0.00526 0.062 0.00
CORRIDOR_FLR_3 6987.34 6987.34 17.94 0.300 0.475 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00776 4.60 0.00526 0.475 0.00
ROOM_1_FLR_6 1298.91 1298.91 33.29 0.056 0.056 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00774 4.60 0.00526 0.015 0.00
ROOM_2_FLR_6 1298.81 1298.81 33.29 0.056 0.056 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00774 4.60 0.00526 0.015 0.00
ROOM_3_MULT9_FLR_6 6264.86 6264.86 255.39 0.270 0.270 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00775 4.60 0.00526 0.099 0.00
BANQUET_FLR_6 4362.33 4362.33 13.15 0.187 1.188 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00780 4.60 0.00526 1.188 0.00
DINING_FLR_6 4452.29 4452.29 13.42 0.191 1.188 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:20:00 21.00 21.00 0.00781 4.60 0.00526 1.188 0.00
KITCHEN_FLR_6 670.02 670.02 6.49 0.029 0.367 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 21.00 21.00 0.00518 4.60 0.00526 0.367 0.00
CORRIDOR_FLR_6 4593.32 4593.32 11.15 0.197 0.197 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:20:00 21.00 21.00 0.00783 4.60 0.00526 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 21.65 21.65 7.20 7.20 21.6490 11.6663 21.6490 0.5389 0.3000
FLR_3_DOAS 16.06 2.05 3.24 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 7841.710 7841.710 1.486412 0.00006860 163.525   1/21 00:10:00   1/21 00:10:00 7841.71 7841.71 1.486412 16.70 13.18 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00800000 51.6744 0.00 0.00 7885.78 7885.78
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 2874.323 2874.323 0.177998 0.00002515 67.205 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2874.32 2874.32 0.177998 16.70 13.18 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00769839 49.7508 1935.85 0.00 2889.66 2889.66
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1356.334 1356.334 0.131717 0.00001187 29.758 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1356.33 1356.33 0.131717 16.70 13.18 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00766424 49.5323 661.88 0.00 1363.74 1363.74
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 1921.306 1921.306 0.130811 0.00001681 44.193 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1921.31 1921.31 0.130811 16.70 13.18 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00758721 49.0405 1231.73 0.00 1931.61 1931.61
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1049.817 1049.817 0.062923 0.00000918 24.696 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1049.82 1049.82 0.062923 16.70 13.18 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00759086 49.0638 718.11 0.00 1055.41 1055.41
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10901.541 10901.541 1.755684 0.00009537 229.439 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 10901.54 10901.54 1.755684 16.70 13.18 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00757982 48.9938 1646.90 0.00 10962.61 10962.61
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 8776.439 8776.439 0.746582 0.00007678 195.540 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8776.44 8776.44 0.746582 16.70 13.18 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00772989 49.9517 4839.89 0.00 8824.06 8824.06
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 24405.050 24405.050 2.446033 0.00021351 533.713 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 24405.05 24405.05 2.446033 16.70 13.18 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00768173 49.6440 11508.51 0.00 24540.16 24540.16
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 11612.861 -999.000 0.997593 0.00041478 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown 8/21 17:00:00 11612.86 10964.55 0.997593 21.68 15.76 0.00873977 12.80 12.09 0.00850000 32.79 0.01653429 24.84 0.0000 21.11 0.00873977 56.0075 10179.87 0.00 11632.90 10826.34
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 4237.206 4237.206 0.182835 0.00003707 121.075 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4237.21 4237.21 0.182835 21.11 14.59 0.00768384 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.11 0.00768384 49.3206 4237.25 0.00 4567.84 4567.84
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 11312.451 -999.000 0.970179 0.00040405 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown 8/21 17:00:00 11312.45 10665.23 0.970179 21.68 15.76 0.00874608 12.80 12.09 0.00850000 32.79 0.01653429 24.84 0.0000 21.11 0.00874608 56.0474 9900.11 0.00 11331.94 10531.66
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 4235.196 4235.196 0.182749 0.00003705 121.017 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4235.20 4235.20 0.182749 21.11 14.59 0.00768373 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.11 0.00768373 49.3199 4235.24 0.00 4565.67 4565.67
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 64018.294 -999.000 5.620695 0.00228654 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 unknown 8/21 14:20:00 64018.29 61628.24 5.620695 21.68 15.68 0.00865728 12.80 12.09 0.00850000 33.90 0.01653638 25.13 0.0000 21.11 0.00865728 55.4834 57361.57 0.00 64131.24 60784.54
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 24643.646 24643.646 1.063383 0.00021559 704.163 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 24643.65 24643.65 1.063383 21.11 14.62 0.00770885 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.11 0.00770885 49.4786 24643.78 0.00 26566.68 26566.68
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 68331.064 -999.000 5.629403 0.00244058 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 unknown 8/21 15:20:00 68331.06 62161.88 5.629403 21.68 15.90 0.00890244 12.80 12.09 0.00850000 33.74 0.01653608 25.09 0.0000 21.11 0.00890244 57.0347 57445.97 0.00 68444.25 61503.87
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 24615.172 24615.172 1.062154 0.00021534 703.350 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 24615.17 24615.17 1.062154 21.11 14.62 0.00770848 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.11 0.00770848 49.4763 24615.31 0.00 26535.98 26535.98
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 10477.894 -999.000 0.893382 0.00037424 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:20:00 unknown 8/21 10:20:00 10477.89 9827.44 0.893382 21.68 15.78 0.00876840 12.80 12.09 0.00850000 31.29 0.01653147 24.45 0.0000 21.11 0.00876840 56.1885 9116.43 0.00 10495.84 9707.17
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 4233.669 4233.669 0.182683 0.00003704 120.974 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4233.67 4233.67 0.182683 21.11 14.59 0.00768361 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.11 0.00768361 49.3191 4233.72 0.00 4564.02 4564.02
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 10236.291 -999.000 0.871300 0.00036561 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 unknown 8/21 10:00:00 10236.29 9586.35 0.871300 21.68 15.79 0.00877493 12.80 12.09 0.00850000 30.90 0.01653072 24.35 0.0000 21.11 0.00877493 56.2298 8891.08 0.00 10253.79 9469.82
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 4231.658 4231.658 0.182596 0.00003702 120.916 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4231.66 4231.66 0.182596 21.11 14.59 0.00768350 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.11 0.00768350 49.3184 4231.71 0.00 4561.86 4561.86
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 10961.278 10961.278 0.753606 0.00009589 251.730 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 10961.28 10961.28 0.753606 16.70 13.18 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00775937 50.1394 6987.34 0.00 11020.10 11020.10
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 3051.450 -999.000 0.262976 0.00010899 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 unknown 8/21 16:50:00 3051.45 2889.32 0.262976 21.68 15.75 0.00872755 12.80 12.09 0.00850000 32.90 0.01653449 24.87 0.0000 21.11 0.00872755 55.9302 2683.52 0.00 3056.73 2852.44
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 1298.896 1298.896 0.056047 0.00001136 37.114 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1298.90 1298.90 0.056047 21.11 14.64 0.00773651 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.11 0.00773651 49.6545 1298.91 0.00 1400.25 1400.25
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2969.568 -999.000 0.255479 0.00010606 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown 8/21 17:00:00 2969.57 2807.50 0.255479 21.68 15.75 0.00873409 12.80 12.09 0.00850000 32.79 0.01653429 24.84 0.0000 21.11 0.00873409 55.9716 2607.02 0.00 2974.70 2771.90
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 1298.794 1298.794 0.056043 0.00001136 37.111 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1298.79 1298.79 0.056043 21.11 14.64 0.00773651 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.11 0.00773651 49.6545 1298.81 0.00 1400.14 1400.14
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 13963.494 -999.000 1.180607 0.00049873 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 unknown 8/21 14:20:00 13963.49 12999.17 1.180607 21.68 15.81 0.00880082 12.80 12.09 0.00850000 33.90 0.01653638 25.13 0.0000 21.11 0.00880082 56.3935 12047.33 0.00 13987.21 12845.40
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 6264.803 6264.803 0.270327 0.00005481 179.005 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 6264.80 6264.80 0.270327 21.11 14.65 0.00774735 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.11 0.00774735 49.7230 6264.86 0.00 6753.66 6753.66
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10490.552 10490.552 1.162063 0.00009178 227.171 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 10490.55 10490.55 1.162063 16.70 13.18 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00780220 50.4129 4362.33 0.00 10548.79 10548.79
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10872.346 10872.346 1.217410 0.00009512 235.204 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:20:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:20:00 10872.35 10872.35 1.217410 16.70 13.18 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00780586 50.4365 4452.29 0.00 10932.72 10932.72
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 6944.451 6944.451 1.196219 0.00006075 145.572 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 6944.45 6944.45 1.196219 16.70 13.18 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00518147 33.6247 670.02 0.00 6983.41 6983.41
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 6696.722 6696.722 0.398836 0.00005859 157.727 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:20:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:20:00 6696.72 6696.72 0.398836 16.70 13.18 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00783334 50.6117 4593.32 0.00 6732.38 6732.38
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 812870.415 -999.000 21.649013 0.02903385 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 812870.41 481013.33 21.649013 29.33 21.85 0.01338869 10.99 10.99 0.00850000 33.90 0.01653638 25.13 53.8660 23.99 0.00969823 52.0883 297513.62 0.00 814024.62 479669.86
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 95011.362 95011.362 6.494704 0.00083120 1712.139 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:20:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:20:00 95011.36 95011.36 6.494704 4.60 4.60 0.00525715 16.70 13.18 0.00800000 4.60 0.00525715 4.60 179.5534 21.68 0.00712261 44.2004 43213.65 0.00 97515.06 97515.06
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 106169.294 -999.000 2.051317 0.00379212 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 106169.29 55739.80 2.051317 33.90 25.13 0.01653638 11.94 11.73 0.00850000 33.90 0.01653638 25.13 99.9965 21.11 0.00878171 56.2709 163545.48 0.00 106307.96 56474.51
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 9002.648 9002.648 0.615395 0.00007876 162.231 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 9002.65 9002.65 0.615395 4.60 4.60 0.00525715 16.70 13.18 0.00800000 4.60 0.00525715 4.60 333.3216 21.11 0.00770881 49.4784 75059.60 0.00 9239.88 9239.88



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 7841.710 7841.710 1.486412 0.00006860 163.525 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 2.7051 2.759563   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 7841.71 7841.71 1.0000 1.78840119 1.486412 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.06859570 60.00 32.22 27.78 0.000 7841.71 4.60 0.00525715 4.60 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 51.6744 0.00 0.00 7885.78 7885.78 1.78840119 16.60 13.15 0.00800000 36934.7 20.92 14.82 0.00800000 41344.1
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 2874.323 2874.323 0.177998 0.00002515 67.205 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 0.9915 1.011498 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2874.32 2874.32 1.0000 0.21416135 0.177998 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.02514327 60.00 32.22 27.78 0.000 2874.32 4.60 0.00525715 4.60 0.00000000 0.0000 21.00 0.00769839 21.00 0.00769839 49.7508 1935.85 0.00 2889.66 2889.66 0.21416135 16.60 13.15 0.00800000 36934.7 29.83 17.98 0.00800000 50427.6
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1356.334 1356.334 0.131717 0.00001187 29.758 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 0.4679 0.477305 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1356.33 1356.33 1.0000 0.15847808 0.131717 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.01186459 60.00 32.22 27.78 0.000 1356.33 4.60 0.00525715 4.60 0.00000000 0.0000 21.00 0.00766424 21.00 0.00766424 49.5323 661.88 0.00 1363.74 1363.74 0.15847808 16.60 13.15 0.00800000 36934.7 25.04 16.33 0.00800000 45540.0
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 1921.306 1921.306 0.130811 0.00001681 44.193 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 0.6628 0.676124 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1921.31 1921.31 1.0000 0.15738754 0.130811 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.01680671 60.00 32.22 27.78 0.000 1921.31 4.60 0.00525715 4.60 0.00000000 0.0000 21.00 0.00758721 21.00 0.00758721 49.0405 1231.73 0.00 1931.61 1931.61 0.15738754 16.60 13.15 0.00800000 36934.7 28.64 17.58 0.00800000 49207.7
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1049.817 1049.817 0.062923 0.00000918 24.696 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 0.3622 0.369439 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1049.82 1049.82 1.0000 0.07570733 0.062923 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.00918332 60.00 32.22 27.78 0.000 1049.82 4.60 0.00525715 4.60 0.00000000 0.0000 21.00 0.00759086 21.00 0.00759086 49.0638 718.11 0.00 1055.41 1055.41 0.07570733 16.60 13.15 0.00800000 36934.7 30.27 18.13 0.00800000 50875.4
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 10901.541 10901.541 1.755684 0.00009537 229.439 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 3.7607 3.836343 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 10901.54 10901.54 1.0000 2.11238127 1.755684 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.09536171 60.00 32.22 27.78 0.000 10901.54 4.60 0.00525715 4.60 0.00000000 0.0000 21.00 0.00757982 21.00 0.00757982 48.9938 1646.90 0.00 10962.61 10962.61 2.11238127 16.60 13.15 0.00800000 36934.7 21.69 15.11 0.00800000 42124.4
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 8776.439 8776.439 0.746582 0.00007678 195.540 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 3.0276 3.088502 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 8776.44 8776.44 1.0000 0.89826321 0.746582 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.07677229 60.00 32.22 27.78 0.000 8776.44 4.60 0.00525715 4.60 0.00000000 0.0000 21.00 0.00772989 21.00 0.00772989 49.9517 4839.89 0.00 8824.06 8824.06 0.89826321 16.60 13.15 0.00800000 36934.7 26.23 16.75 0.00800000 46758.2
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 24405.050 24405.050 2.446033 0.00021351 533.713 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 8.4189 8.588340 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 24405.05 24405.05 1.0000 2.94298581 2.446033 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.21348424 60.00 32.22 27.78 0.000 24405.05 4.60 0.00525715 4.60 0.00000000 0.0000 21.00 0.00768173 21.00 0.00768173 49.6440 11508.51 0.00 24540.16 24540.16 2.94298581 16.60 13.15 0.00800000 36934.7 24.78 16.23 0.00800000 45273.3
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 11612.861 -999.000 0.997593 0.00041478 -999.000 -999.0000 1.00000 1.00000 1021.0868 1004.8586 1.2032 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.997593 1.20027124   4197.9300 999.8980 39.82149024 13.37 6.70 6.67 1115009.42 1.0415 1.041484 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown unknown unknown 8/21 17:00:00 Sensible 11612.86 10964.55 1.0000 1.20027124 0.997593 21.68 15.76 0.00873977 43997.4 12.80 12.09 0.00850000 34322.2 0.41473444 6.70 13.37 6.67 0.000 11612.86 32.79 0.01653429 24.84 0.00000000 0.0000 21.11 0.00873977 21.11 0.00873977 56.0075 10179.87 0.00 11632.90 10826.34 1.20027124 21.68 15.77 0.00873977 43997.4 12.85 12.09 0.00847362 34305.5
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 4237.206 4237.206 0.182835 0.00003707 121.075 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.997593 1.20027124   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 1.4617 1.491108 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 4237.21 4237.21 1.0000 0.21998156 0.182835 21.11 14.59 0.00768384 40731.2 40.00 21.17 0.00800000 60796.0 0.03706515 60.00 32.22 27.78 0.000 4237.21 4.60 0.00525715 4.60 0.00000000 0.0000 21.11 0.00768384 21.11 0.00768384 49.3206 4237.25 0.00 4567.84 4567.84 0.21998156 16.60 12.84 0.00768384 36134.3 36.97 20.03 0.00768384 56898.9
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 11312.451 -999.000 0.970179 0.00040405 -999.000 -999.0000 1.00000 1.00000 1021.0985 1004.8586 1.2032 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.970179 1.16728725   4197.9300 999.8980 39.82149024 13.37 6.70 6.67 1115009.42 1.0146 1.014542 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown unknown unknown 8/21 17:00:00 Sensible 11312.45 10665.23 1.0000 1.16728725 0.970179 21.68 15.76 0.00874608 44013.4 12.80 12.09 0.00850000 34322.2 0.40400576 6.70 13.37 6.67 0.000 11312.45 32.79 0.01653429 24.84 0.00000000 0.0000 21.11 0.00874608 21.11 0.00874608 56.0474 9900.11 0.00 11331.94 10531.66 1.16728725 21.68 15.77 0.00874608 44013.4 12.85 12.09 0.00847455 34305.5
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 4235.196 4235.196 0.182749 0.00003705 121.017 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.970179 1.16728725   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 1.4610 1.490401 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 4235.20 4235.20 1.0000 0.21987720 0.182749 21.11 14.59 0.00768373 40731.0 40.00 21.17 0.00800000 60796.0 0.03704756 60.00 32.22 27.78 0.000 4235.20 4.60 0.00525715 4.60 0.00000000 0.0000 21.11 0.00768373 21.11 0.00768373 49.3199 4235.24 0.00 4565.67 4565.67 0.21987720 16.60 12.84 0.00768373 36134.0 36.97 20.03 0.00768373 56898.6
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 64018.294 -999.000 5.620695 0.00228654 -999.000 -999.0000 1.00000 1.00000 1020.9334 1004.8586 1.2032 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.620695 6.76263431   4197.9300 999.8980 39.82149024 13.37 6.70 6.67 1115009.42 5.7415 5.741395 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 unknown unknown unknown 8/21 14:20:00 Sensible 64018.29 61628.24 1.0000 6.76263431 5.620695 21.68 15.68 0.00865728 43788.7 12.80 12.09 0.00850000 34322.2 2.28630917 6.70 13.37 6.67 0.000 64018.29 33.90 0.01653638 25.13 0.00000000 0.0000 21.11 0.00865728 21.11 0.00865728 55.4834 57361.57 0.00 64131.24 60784.54 6.76263431 21.68 15.69 0.00865728 43788.7 12.88 12.09 0.00846128 34305.5
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 24643.646 24643.646 1.063383 0.00021559 704.163 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.620695 6.76263431   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 8.5012 8.672304 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 24643.65 24643.65 1.0000 1.27942673 1.063383 21.11 14.62 0.00770885 40794.9 40.00 21.17 0.00800000 60796.0 0.21557137 60.00 32.22 27.78 0.000 24643.65 4.60 0.00525715 4.60 0.00000000 0.0000 21.11 0.00770885 21.11 0.00770885 49.4786 24643.78 0.00 26566.68 26566.68 1.27942673 16.60 12.87 0.00770885 36197.6 36.97 20.05 0.00770885 56962.1
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 68331.064 -999.000 5.629403 0.00244058 -999.000 -999.0000 1.00000 1.00000 1021.3892 1004.8586 1.2032 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.629403 6.77311091   4197.9300 999.8980 39.82149024 13.37 6.70 6.67 1115009.42 6.1283 6.128180 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 unknown unknown unknown 8/21 15:20:00 Sensible 68331.06 62161.88 1.0000 6.77311091 5.629403 21.68 15.90 0.00890244 44410.8 12.80 12.09 0.00850000 34322.2 2.44033272 6.70 13.37 6.67 0.000 68331.06 33.74 0.01653608 25.09 0.00000000 0.0000 21.11 0.00890244 21.11 0.00890244 57.0347 57445.97 0.00 68444.25 61503.87 6.77311091 21.68 15.91 0.00890244 44410.8 12.79 12.09 0.00849658 34305.5
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 24615.172 24615.172 1.062154 0.00021534 703.350 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.629403 6.77311091   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 8.4914 8.662284 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 24615.17 24615.17 1.0000 1.27794847 1.062154 21.11 14.62 0.00770848 40794.0 40.00 21.17 0.00800000 60796.0 0.21532230 60.00 32.22 27.78 0.000 24615.17 4.60 0.00525715 4.60 0.00000000 0.0000 21.11 0.00770848 21.11 0.00770848 49.4763 24615.31 0.00 26535.98 26535.98 1.27794847 16.60 12.87 0.00770848 36196.7 36.97 20.05 0.00770848 56961.2
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 10477.894 -999.000 0.893382 0.00037424 -999.000 -999.0000 1.00000 1.00000 1021.1400 1004.8586 1.2032 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.893382 1.07488791   4197.9300 999.8980 39.82149024 13.37 6.70 6.67 1115009.42 0.9397 0.939696 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:20:00 unknown unknown unknown 8/21 10:20:00 Sensible 10477.89 9827.44 1.0000 1.07488791 0.893382 21.68 15.78 0.00876840 44070.1 12.80 12.09 0.00850000 34322.2 0.37420093 6.70 13.37 6.67 0.000 10477.89 31.29 0.01653147 24.45 0.00000000 0.0000 21.11 0.00876840 21.11 0.00876840 56.1885 9116.43 0.00 10495.84 9707.17 1.07488791 21.68 15.79 0.00876840 44070.1 12.84 12.09 0.00847779 34305.5
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 4233.669 4233.669 0.182683 0.00003704 120.974 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.893382 1.07488791   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 1.4605 1.489863 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 4233.67 4233.67 1.0000 0.21979791 0.182683 21.11 14.59 0.00768361 40730.7 40.00 21.17 0.00800000 60796.0 0.03703420 60.00 32.22 27.78 0.000 4233.67 4.60 0.00525715 4.60 0.00000000 0.0000 21.11 0.00768361 21.11 0.00768361 49.3191 4233.72 0.00 4564.02 4564.02 0.21979791 16.60 12.84 0.00768361 36133.7 36.98 20.03 0.00768361 56898.3
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 10236.291 -999.000 0.871300 0.00036561 -999.000 -999.0000 1.00000 1.00000 1021.1522 1004.8586 1.2032 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.871300 1.04831877   4197.9300 999.8980 39.82149024 13.37 6.70 6.67 1115009.42 0.9180 0.918028 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 unknown unknown unknown 8/21 10:00:00 Sensible 10236.29 9586.35 1.0000 1.04831877 0.871300 21.68 15.79 0.00877493 44086.7 12.80 12.09 0.00850000 34322.2 0.36557247 6.70 13.37 6.67 0.000 10236.29 30.90 0.01653072 24.35 0.00000000 0.0000 21.11 0.00877493 21.11 0.00877493 56.2298 8891.08 0.00 10253.79 9469.82 1.04831877 21.68 15.80 0.00877493 44086.7 12.84 12.09 0.00847873 34305.5
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 4231.658 4231.658 0.182596 0.00003702 120.916 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.871300 1.04831877   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 1.4598 1.489156 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 4231.66 4231.66 1.0000 0.21969351 0.182596 21.11 14.59 0.00768350 40730.4 40.00 21.17 0.00800000 60796.0 0.03701661 60.00 32.22 27.78 0.000 4231.66 4.60 0.00525715 4.60 0.00000000 0.0000 21.11 0.00768350 21.11 0.00768350 49.3184 4231.71 0.00 4561.86 4561.86 0.21969351 16.60 12.84 0.00768350 36133.4 36.98 20.03 0.00768350 56898.1
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 10961.278 10961.278 0.753606 0.00009589 251.730 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 3.7813 3.857365 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 10961.28 10961.28 1.0000 0.90671332 0.753606 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.09588426 60.00 32.22 27.78 0.000 10961.28 4.60 0.00525715 4.60 0.00000000 0.0000 21.00 0.00775937 21.00 0.00775937 50.1394 6987.34 0.00 11020.10 11020.10 0.90671332 16.60 13.15 0.00800000 36934.7 28.52 17.54 0.00800000 49088.6
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 3051.450 -999.000 0.262976 0.00010899 -999.000 -999.0000 1.00000 1.00000 1021.0641 1004.8586 1.2032 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.262976 0.31640408   4197.9300 999.8980 39.82149024 13.37 6.70 6.67 1115009.42 0.2737 0.273665 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 unknown unknown unknown 8/21 16:50:00 Sensible 3051.45 2889.32 1.0000 0.31640408 0.262976 21.68 15.75 0.00872755 43966.4 12.80 12.09 0.00850000 34322.2 0.10897758 6.70 13.37 6.67 0.000 3051.45 32.90 0.01653449 24.87 0.00000000 0.0000 21.11 0.00872755 21.11 0.00872755 55.9302 2683.52 0.00 3056.73 2852.44 0.31640408 21.68 15.75 0.00872755 43966.4 12.85 12.09 0.00847182 34305.5
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 1298.896 1298.896 0.056047 0.00001136 37.114 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.262976 0.31640408   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 0.4481 0.457092 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1298.90 1298.90 1.0000 0.06743435 0.056047 21.11 14.64 0.00773651 40865.0 40.00 21.17 0.00800000 60796.0 0.01136215 60.00 32.22 27.78 0.000 1298.90 4.60 0.00525715 4.60 0.00000000 0.0000 21.11 0.00773651 21.11 0.00773651 49.6545 1298.91 0.00 1400.25 1400.25 0.06743435 16.60 12.89 0.00773651 36267.6 36.97 20.07 0.00773651 57032.3
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2969.568 -999.000 0.255479 0.00010606 -999.000 -999.0000 1.00000 1.00000 1021.0762 1004.8586 1.2032 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.255479 0.30738381   4197.9300 999.8980 39.82149024 13.37 6.70 6.67 1115009.42 0.2663 0.266322 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown unknown unknown 8/21 17:00:00 Sensible 2969.57 2807.50 1.0000 0.30738381 0.255479 21.68 15.75 0.00873409 43983.0 12.80 12.09 0.00850000 34322.2 0.10605330 6.70 13.37 6.67 0.000 2969.57 32.79 0.01653429 24.84 0.00000000 0.0000 21.11 0.00873409 21.11 0.00873409 55.9716 2607.02 0.00 2974.70 2771.90 0.30738381 21.68 15.76 0.00873409 43983.0 12.85 12.09 0.00847279 34305.5
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 1298.794 1298.794 0.056043 0.00001136 37.111 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.255479 0.30738381   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 0.4480 0.457056 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1298.79 1298.79 1.0000 0.06742902 0.056043 21.11 14.64 0.00773651 40865.0 40.00 21.17 0.00800000 60796.0 0.01136126 60.00 32.22 27.78 0.000 1298.79 4.60 0.00525715 4.60 0.00000000 0.0000 21.11 0.00773651 21.11 0.00773651 49.6545 1298.81 0.00 1400.14 1400.14 0.06742902 16.60 12.89 0.00773651 36267.6 36.97 20.07 0.00773651 57032.3
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 13963.494 -999.000 1.180607 0.00049873 -999.000 -999.0000 1.00000 1.00000 1021.2003 1004.8586 1.2032 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.180607 1.42046675   4197.9300 999.8980 39.82149024 13.37 6.70 6.67 1115009.42 1.2523 1.252297 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 unknown unknown unknown 8/21 14:20:00 Sensible 13963.49 12999.17 1.0000 1.42046675 1.180607 21.68 15.81 0.00880082 44152.4 12.80 12.09 0.00850000 34322.2 0.49868348 6.70 13.37 6.67 0.000 13963.49 33.90 0.01653638 25.13 0.00000000 0.0000 21.11 0.00880082 21.11 0.00880082 56.3935 12047.33 0.00 13987.21 12845.40 1.42046675 21.68 15.82 0.00880082 44152.4 12.83 12.09 0.00848245 34305.5
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 6264.803 6264.803 0.270327 0.00005481 179.005 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.180607 1.42046675   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 2.1611 2.204636 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 6264.80 6264.80 1.0000 0.32524856 0.270327 21.11 14.65 0.00774735 40892.6 40.00 21.17 0.00800000 60796.0 0.05480164 60.00 32.22 27.78 0.000 6264.80 4.60 0.00525715 4.60 0.00000000 0.0000 21.11 0.00774735 21.11 0.00774735 49.7230 6264.86 0.00 6753.66 6753.66 0.32524856 16.60 12.90 0.00774735 36295.1 36.97 20.08 0.00774735 57059.7
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 10490.552 10490.552 1.162063 0.00009178 227.171 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 3.6189 3.691713 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 10490.55 10490.55 1.0000 1.39815564 1.162063 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.09176657 60.00 32.22 27.78 0.000 10490.55 4.60 0.00525715 4.60 0.00000000 0.0000 21.00 0.00780220 21.00 0.00780220 50.4129 4362.33 0.00 10548.79 10548.79 1.39815564 16.60 13.15 0.00800000 36934.7 24.00 15.95 0.00800000 44479.5
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 10872.346 10872.346 1.217410 0.00009512 235.204 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 3.7506 3.826069 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:20:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:20:00 Sensible 10872.35 10872.35 1.0000 1.46474742 1.217410 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.09510632 60.00 32.22 27.78 0.000 10872.35 4.60 0.00525715 4.60 0.00000000 0.0000 21.00 0.00780586 21.00 0.00780586 50.4365 4452.29 0.00 10932.72 10932.72 1.46474742 16.60 13.15 0.00800000 36934.7 23.92 15.93 0.00800000 44398.6
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 6944.451 6944.451 1.196219 0.00006075 145.572 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 2.3956 2.443810 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 Sensible 6944.45 6944.45 1.0000 1.43925105 1.196219 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.06074689 60.00 32.22 27.78 0.000 6944.45 4.60 0.00525715 4.60 0.00000000 0.0000 18.92 0.00518147 21.00 0.00518147 33.6247 670.02 0.00 6983.41 6983.41 1.43925105 16.60 13.15 0.00800000 36934.7 21.36 14.99 0.00800000 41786.8
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 6696.722 6696.722 0.398836 0.00005859 157.727 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 2.3101 2.356632 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:20:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:20:00 Sensible 6696.72 6696.72 1.0000 0.47986613 0.398836 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.05857987 60.00 32.22 27.78 0.000 6696.72 4.60 0.00525715 4.60 0.00000000 0.0000 21.00 0.00783334 21.00 0.00783334 50.6117 4593.32 0.00 6732.38 6732.38 0.47986613 16.60 13.15 0.00800000 36934.7 30.36 18.16 0.00800000 50964.4
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 812870.415 -999.000 21.649013 0.02903385 -999.000 -999.0000 1.00000 1.00000 1029.7289 1004.8586 1.2032 VAV WITH REHEAT FAN Fan:VariableVolume 21.649013 26.04737550   4197.9300 999.8980 39.82149024 13.37 6.70 6.67 1115009.42 72.9026 72.902561 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 Sensible 812870.41 481013.33 1.0000 26.04737550 21.649013 29.33 21.85 0.01338869 63683.7 10.99 10.99 0.00850000 32476.3 29.03088604 6.70 13.37 6.67 48507.614 764362.80 33.90 0.01653638 25.13 11.66146000 53.8660 23.99 0.00971344 23.99 0.00969823 52.0883 297513.62 0.00 814024.62 479669.86 26.04737550 29.33 21.86 0.01338869 63683.7 11.44 11.33 0.00829934 32432.0
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 95011.362 95011.362 6.494704 0.00083120 1712.139 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 VAV WITH REHEAT FAN Fan:VariableVolume 21.649013 26.04737550   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 32.7757 33.435289 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:20:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:20:00 Sensible 95011.36 95011.36 1.0000 7.81421265 6.494704 4.60 4.60 0.00525715 17815.0 16.70 13.18 0.00800000 37036.7 0.83111605 60.00 32.22 27.78 0.000 95011.36 4.60 0.00525715 4.60 11.66146000 179.5534 18.39 0.00732256 21.68 0.00712261 44.2004 43213.65 0.00 97515.06 97515.06 7.81421265 2.80 2.80 0.00525715 15988.7 15.10 9.69 0.00525715 28467.9
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 106169.294 -999.000 2.051317 0.00379212 -999.000 -999.0000 1.00000 1.00000 1035.5803 1004.8586 1.2032 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.46799022   4197.9300 999.8980 39.82149024 13.37 6.70 6.67 1115009.42 9.5218 9.521829 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 Sensible 106169.29 55739.80 1.0000 2.46807700 2.051317 33.90 25.13 0.01653638 76462.7 11.94 11.73 0.00850000 33445.7 3.79173435 6.70 13.37 6.67 2195.006 103974.29 33.90 0.01653638 25.13 2.05124512 99.9965 21.11 0.00878512 21.11 0.00878171 56.2709 163545.48 0.00 106307.96 56474.51 2.46807700 33.90 25.14 0.01653638 76462.7 11.80 11.72 0.00853316 33389.5
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 9002.648 9002.648 0.615395 0.00007876 162.231 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.46799022   4197.9300 999.8980 2.48574509 54.44 82.22 27.78 289883.85 3.1056 3.168107 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 9002.65 9002.65 1.0000 0.74042310 0.615395 4.60 4.60 0.00525715 17815.0 16.70 13.18 0.00800000 37036.7 0.07875106 60.00 32.22 27.78 0.000 9002.65 4.60 0.00525715 4.60 2.05124512 333.3216 21.11 0.00770721 21.11 0.00770881 49.4784 75059.60 0.00 9239.88 9239.88 0.74042310 2.80 2.80 0.00525715 15988.7 15.10 9.69 0.00525715 28467.9



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 11.66 21.65 -      
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 2125.67 4663.17 0.00
RETAIL_1_FLR_1 4158.17 3510.50 37.17
RETAIL_2_FLR_1 4030.00 3108.33 12.67
MECH_FLR_1 2748.50 4397.83 0.00
STORAGE_FLR_1 1986.17 4791.67 4.50
LAUNDRY_FLR_1 8150.33 3577.17 3340.50
CAFE_FLR_1 6607.00 3914.00 2472.17
LOBBY_FLR_1 5840.00 3702.67 2057.83
ROOM_1_FLR_3 250.83 7707.83 158.50
ROOM_2_FLR_3 410.00 7894.17 364.50
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 223.33 8760.00 223.33
ROOM_5_FLR_3 153.00 7525.50 137.00
ROOM_6_FLR_3 319.67 7730.83 314.67
CORRIDOR_FLR_3 2599.33 5001.83 668.00
ROOM_1_FLR_6 679.17 7595.00 395.83
ROOM_2_FLR_6 870.33 7780.33 686.33
ROOM_3_MULT9_FLR_6 208.00 7638.50 109.00
BANQUET_FLR_6 7243.67 2662.83 2017.33
DINING_FLR_6 7690.83 2182.83 1853.33
KITCHEN_FLR_6 8610.33 6796.17 6770.67
CORRIDOR_FLR_6 3924.50 3961.50 6.50
Facility 8745.17 8760.00 8266.33
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 29.33 0.00 29.33
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 2.00 0.00 2.00
ROOM_2_FLR_3 0.00 0.50 0.00 0.50
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 32.67 0.00 32.67
ROOM_5_FLR_3 0.00 1.00 0.00 1.00
ROOM_6_FLR_3 0.00 0.83 0.00 0.83
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 6.50 0.00 6.50
ROOM_2_FLR_6 0.00 4.50 0.00 4.50
ROOM_3_MULT9_FLR_6 0.00 19.83 0.00 19.83
BANQUET_FLR_6 0.00 2.83 0.00 2.83
DINING_FLR_6 0.00 4.33 0.00 4.33
KITCHEN_FLR_6 0.00 42.50 0.00 42.50
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 0.00 106.00 0.00 106.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.80 106.50 4826.41 1.037 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 2.262 0.133 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 1.448 0.044 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.672 0.049 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.551 0.049 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 21.021 0.142 0.000 0.000
CAFE_FLR_1 82.58 142.30 748.35 3.507 0.104 0.000 0.000
LOBBY_FLR_1 245.14 422.44 5183.56 1.678 0.043 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.473 0.171 0.000 0.057
ROOM_2_FLR_3 0.95 1.50 118.93 0.473 0.171 0.000 0.058
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.537 0.076 0.000 0.092
ROOM_5_FLR_3 0.95 1.50 118.94 0.473 0.171 0.000 0.057
ROOM_6_FLR_3 0.95 1.50 118.93 0.473 0.171 0.000 0.058
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.525 0.021 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.473 0.171 0.000 0.066
ROOM_2_FLR_6 0.95 1.50 118.93 0.473 0.171 0.000 0.067
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.537 0.139 0.000 0.105
BANQUET_FLR_6 145.01 249.90 1010.89 4.638 0.050 0.000 0.000
DINING_FLR_6 145.01 249.90 1010.89 4.950 0.050 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 19.900 0.143 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 1.069 0.035 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.80 106.50 4826.41 0.679 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 1.377 0.002 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 0.888 0.001 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.414 0.001 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.345 0.001 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 12.791 0.002 0.000 0.000
CAFE_FLR_1 82.58 142.30 748.35 2.126 0.002 0.000 0.000
LOBBY_FLR_1 245.14 422.44 5183.56 1.095 0.001 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.456 0.003 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.455 0.003 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.519 0.001 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.458 0.003 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.457 0.003 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.327 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.456 0.003 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.455 0.003 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.519 0.002 0.000 0.000
BANQUET_FLR_6 145.01 249.90 1010.89 2.936 0.001 0.000 0.000
DINING_FLR_6 145.01 249.90 1010.89 3.224 0.001 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 8.569 0.002 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 0.654 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.80 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.28 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.58 142.30 748.35 188.86 0.0000 0.676
LOBBY_FLR_1 VAV WITH REHEAT 245.14 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 145.01 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 145.01 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.39 1604.23 35184.81 11345.29 0.0000 137.584


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 43005771.67 0.00 43005771.67 0.00 43005771.67 26946214.98 0.00 0.00 8760.00 0.00
RETAIL_1_FLR_1 5169566.01 0.00 5169566.01 302899.14 5472465.15 2498216.28 0.00 0.00 8760.00 0.00
RETAIL_2_FLR_1 3824289.43 0.00 3824289.43 116919.45 3941208.88 2892943.94 10.58 1.91 8747.51 0.00
MECH_FLR_1 3759992.68 0.00 3759992.68 276328.12 4036320.80 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 1780518.76 0.00 1780518.76 159426.11 1939944.86 1821682.01 4818.93 1049.15 2891.92 0.00
LAUNDRY_FLR_1 55918139.11 0.00 55918139.11 377311.94 56295451.05 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 22483606.73 0.00 22483606.73 669575.70 23153182.43 21330615.53 2560.11 739.28 5460.61 0.00
LOBBY_FLR_1 74530141.66 0.00 74530141.66 1913130.72 76443272.38 59728886.00 24.85 18.08 8717.07 0.00
ROOM_1_FLR_3 1946875.62 58367.79 2005243.41 175810.96 2181054.36 1946875.62 0.00 7651.89 1108.11 0.00
ROOM_2_FLR_3 1946647.51 59505.49 2006153.01 175797.54 2181950.55 1946647.51 0.00 7651.83 1108.17 0.00
ROOM_3_MULT19_FLR_3 26397887.27 62939.74 26460827.02 49053.23 26509880.24 26397887.27 0.00 7765.83 994.17 8760.00
ROOM_4_MULT19_FLR_3 26405105.73 59286.68 26464392.41 49066.64 26513459.05 26405105.73 0.00 7757.55 1002.45 0.00
ROOM_5_FLR_3 1946875.62 58466.75 2005342.37 175810.96 2181153.33 1946875.62 0.00 7651.83 1108.17 0.00
ROOM_6_FLR_3 1946647.51 59589.17 2006236.68 175797.54 2182034.22 1946647.51 0.00 7651.89 1108.11 0.00
CORRIDOR_FLR_3 21396850.80 0.00 21396850.80 212590.82 21609441.62 14972100.18 1.96 2.33 8755.71 0.00
ROOM_1_FLR_6 486718.90 67337.93 554056.83 175846.43 729903.27 486718.90 0.00 7648.67 1111.33 0.00
ROOM_2_FLR_6 486661.88 69009.63 555671.51 175833.02 731504.52 486661.88 0.00 7648.67 1111.33 0.00
ROOM_3_MULT9_FLR_6 3126920.42 67530.69 3194451.10 89969.19 3284420.30 3126920.42 0.00 7648.83 1111.17 0.00
BANQUET_FLR_6 40115027.01 0.00 40115027.01 429372.80 40544399.81 37458366.31 3658.75 388.30 4712.95 0.00
DINING_FLR_6 42813225.91 0.00 42813225.91 429372.80 43242598.70 37458366.31 1559.15 286.52 6914.33 0.00
KITCHEN_FLR_6 53644638.40 0.00 53644638.40 384388.20 54029026.60 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 11539410.44 0.00 11539410.44 376217.72 11915628.16 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.45E+10 10977048.84 0.45E+10 17716686.34 0.45E+10 0.43E+10 7000.25 7993.51 8760.00 8760.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.3637 0.0000 1.3637 0.0000 1.3637 0.8545 0.00 0.00 8760.00
RETAIL_1_FLR_1 0.1639 0.0000 0.1639 0.0096 0.1735 0.0792 0.00 0.00 8760.00
RETAIL_2_FLR_1 0.1213 0.0000 0.1213 0.0037 0.1250 0.0917 10.58 1.91 8747.51
MECH_FLR_1 0.1192 0.0000 0.1192 0.0088 0.1280 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0565 0.0000 0.0565 0.0051 0.0615 0.0578 4818.93 1049.15 2891.92
LAUNDRY_FLR_1 1.7732 0.0000 1.7732 0.0120 1.7851 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.7130 0.0000 0.7130 0.0212 0.7342 0.6764 2560.11 739.28 5460.61
LOBBY_FLR_1 2.3633 0.0000 2.3633 0.0607 2.4240 1.8940 24.85 18.08 8717.07
ROOM_1_FLR_3 0.0617 0.0019 0.0636 0.0056 0.0692 0.0617 0.00 7651.89 1108.11
ROOM_2_FLR_3 0.0617 0.0019 0.0636 0.0056 0.0692 0.0617 0.00 7651.83 1108.17
ROOM_4_MULT19_FLR_3 0.8373 0.0019 0.8392 0.0016 0.8407 0.8373 0.00 7757.55 1002.45
ROOM_5_FLR_3 0.0617 0.0019 0.0636 0.0056 0.0692 0.0617 0.00 7651.83 1108.17
ROOM_6_FLR_3 0.0617 0.0019 0.0636 0.0056 0.0692 0.0617 0.00 7651.89 1108.11
CORRIDOR_FLR_3 0.6785 0.0000 0.6785 0.0067 0.6852 0.4748 1.96 2.33 8755.71
ROOM_1_FLR_6 0.0154 0.0021 0.0176 0.0056 0.0231 0.0154 0.00 7648.67 1111.33
ROOM_2_FLR_6 0.0154 0.0022 0.0176 0.0056 0.0232 0.0154 0.00 7648.67 1111.33
ROOM_3_MULT9_FLR_6 0.0992 0.0021 0.1013 0.0029 0.1041 0.0992 0.00 7648.83 1111.17
BANQUET_FLR_6 1.2720 0.0000 1.2720 0.0136 1.2857 1.1878 3658.75 388.30 4712.95
DINING_FLR_6 1.3576 0.0000 1.3576 0.0136 1.3712 1.1878 1559.15 286.52 6914.33
KITCHEN_FLR_6 1.7011 0.0000 1.7011 0.0122 1.7132 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.3659 0.0000 0.3659 0.0119 0.3778 0.1256 0.00 0.00 8760.00
Total Facility 79.6304 0.1964 79.8268 0.4436 80.2704 73.9670 7000.25 7993.51 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.55E+09 0.00 0.55E+09 0.22E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 93646421.35 562033.87 94208455.22 64690340.46 0.00 0.00 8760.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 17.4433 0.0000 17.4433 6.9969 0.00 0.00 8760.00
FLR_3_DOAS 2.9695 0.0178 2.9873 2.0513 0.00 0.00 8760.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 6444.87 2315.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLR_3_DOAS 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 16.8835 19.0089 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 2.9695 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1318
Defaulted Fields 1181
Fields with Defaults 4005
Autosized Fields 350
Autosizable Fields 402
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 7480.31 76098.63 23-MAR-01:30 471307.42 09-SEP-21:00
Electricity:Building 2519.06 32804.76 02-JAN-02:10 151906.32 02-JAN-20:10
Electricity:Zone:BASEMENT 323.72 3705.45 02-JAN-02:10 24299.15 02-JAN-20:10
Electricity:SpaceType:GENERAL 2511.97 32663.61 02-JAN-02:10 151664.99 02-JAN-20:10
InteriorLights:Electricity 766.96 6971.81 02-JAN-02:10 62892.57 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 173.46 1576.23 02-JAN-02:10 14185.34 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 766.96 6971.81 02-JAN-02:10 62892.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity 766.96 6971.81 02-JAN-02:10 62892.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 173.46 1576.23 02-JAN-02:10 14185.34 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 766.96 6971.81 02-JAN-02:10 62892.57 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 18.80 222.61 02-JAN-02:10 1390.02 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.61 78.27 02-JAN-02:10 704.41 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.61 78.27 02-JAN-02:10 704.41 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 21.77 257.78 02-JAN-02:10 1609.65 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.97 90.64 02-JAN-02:10 815.72 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.97 90.64 02-JAN-02:10 815.72 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 29.11 327.88 02-JAN-02:10 2199.84 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 16.64 151.16 02-JAN-02:10 1360.40 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 16.64 151.16 02-JAN-02:10 1360.40 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 6.38 76.28 02-JAN-02:10 469.87 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.78 25.30 02-JAN-02:10 227.72 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.78 25.30 02-JAN-02:10 227.72 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 72.30 1002.39 02-JAN-02:10 4930.01 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.37 39.69 02-JAN-02:10 357.21 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.37 39.69 02-JAN-02:10 357.21 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 32.35 398.98 02-JAN-02:10 2727.18 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 18.01 195.77 02-JAN-02:10 1761.91 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 18.01 195.77 02-JAN-02:10 1761.91 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 270.98 3251.99 02-JAN-02:10 20294.39 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 121.98 1140.58 02-JAN-02:10 10265.18 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 121.98 1140.58 02-JAN-02:10 10265.18 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 18.66 264.62 01-JAN-02:10 1227.54 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 18.66 264.59 01-JAN-02:10 1227.39 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 304.77 4565.05 01-JAN-02:10 20923.25 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 76.02 643.59 01-JAN-02:10 5851.22 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 76.02 643.59 01-JAN-02:10 5851.22 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 304.86 4566.30 01-JAN-02:10 20928.98 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 76.04 643.77 01-JAN-02:10 5852.82 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 76.04 643.77 01-JAN-02:10 5852.82 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 18.66 264.62 01-JAN-02:10 1227.54 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 18.66 264.59 01-JAN-02:10 1227.39 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 4.66 66.15 01-JAN-02:10 306.88 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.59 13.47 01-JAN-02:10 122.50 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.59 13.47 01-JAN-02:10 122.50 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 4.66 66.15 01-JAN-02:10 306.85 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.59 13.47 01-JAN-02:10 122.49 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.59 13.47 01-JAN-02:10 122.49 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 36.10 540.75 01-JAN-02:10 2478.43 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 9.00 76.24 01-JAN-02:10 693.10 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 9.00 76.24 01-JAN-02:10 693.10 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 210.60 2593.08 02-JAN-02:10 9841.96 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 34.74 343.78 02-JAN-02:10 3094.06 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 34.74 343.78 02-JAN-02:10 3094.06 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 210.60 2593.08 02-JAN-02:10 9841.96 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 34.74 343.78 02-JAN-02:10 3094.06 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 34.74 343.78 02-JAN-02:10 3094.06 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 454.16 6253.02 02-JAN-02:10 18944.06 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.33 121.09 02-JAN-02:10 1089.83 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.33 121.09 02-JAN-02:10 1089.83 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
InteriorEquipment:Electricity 1745.01 25691.80 02-JAN-02:10 89475.41 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1745.01 25691.80 02-JAN-02:10 89475.41 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 433.74 5990.78 01-JAN-00:10 16487.34 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
Refrigeration:Electricity 62.82 1119.63 04-FEB-23:30 3357.78 21-MAR-06:10
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 3215.54 2582.97 18-DEC-02:20 250578.16 10-SEP-15:10
LowTempRefrigeration:Refrigeration:Electricity 20.56 0.00 01-JAN-11:10 1973.11 21-MAR-06:10
MedTempRefrigeration:Refrigeration:Electricity 35.17 958.05 23-NOV-04:20 1223.64 23-JAN-07:40
Fans:Electricity 620.46 12931.84 23-MAR-00:40 43376.30 05-OCT-21:10
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 883.88 13687.12 24-DEC-05:10 54531.94 05-OCT-21:10
ExteriorEquipment:Electricity 651.48 9618.58 02-JAN-02:20 39726.11 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 32.45 553.78 13-JAN-04:40 1868.65 02-JAN-21:10
ElectricityPurchased:Facility 7480.31 76098.63 23-MAR-01:30 471307.42 09-SEP-21:00
ElectricityPurchased:Plant 7480.31 76098.63 23-MAR-01:30 471307.42 09-SEP-21:00
Cogeneration:ElectricityPurchased 7480.31 76098.63 23-MAR-01:30 471307.42 09-SEP-21:00
General:Cogeneration:ElectricityPurchased 7480.31 76098.63 23-MAR-01:30 471307.42 09-SEP-21:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 7480.31 76098.63 23-MAR-01:30 471307.42 09-SEP-21:00
ElectricityNet:Plant 7480.31 76098.63 23-MAR-01:30 471307.42 09-SEP-21:00
Cogeneration:ElectricityNet 7480.31 76098.63 23-MAR-01:30 471307.42 09-SEP-21:00
General:Cogeneration:ElectricityNet 7480.31 76098.63 23-MAR-01:30 471307.42 09-SEP-21:00
General:Fans:Electricity 620.46 12931.84 23-MAR-00:40 43376.30 05-OCT-21:10
ExteriorLights:Electricity 242.79 0.00 01-JAN-07:30 15448.40 01-JAN-00:10
General:ExteriorLights:Electricity 242.79 0.00 01-JAN-07:30 15448.40 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.91 18.80 01-JAN-00:10 188.00 01-JAN-07:10
HeatRecovery:Electricity 230.97 0.00 01-JAN-00:10 9938.94 03-JAN-09:30
General:HeatRecovery:Electricity 230.97 0.00 01-JAN-00:10 9938.94 03-JAN-09:30
WaterSystems:Electricity 90.74 1086.56 27-JUL-00:20 4738.75 31-AUG-18:10
Water Heater:WaterSystems:Electricity 90.74 1086.56 27-JUL-00:20 4738.75 31-AUG-18:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 2881.81 0.00 03-JAN-04:50 239091.22 10-SEP-15:10
General:Cooling:Electricity 2881.81 0.00 03-JAN-04:50 239091.22 10-SEP-15:10
Pumps:Electricity 187.26 47.91 12-JAN-08:10 7976.37 23-OCT-20:50
General:Pumps:Electricity 187.26 47.91 12-JAN-08:10 7976.37 23-OCT-20:50
WIRED_LTG_ELECTRICITY 27.00 0.00 01-JAN-00:10 2213.82 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 4579.69 29270.80 02-JAN-02:10 434585.77 30-DEC-19:30
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 2790.85 15908.90 04-MAY-10:10 363967.44 08-MAR-23:10
WaterSystems:NaturalGas 2663.34 15908.90 09-JAN-10:40 245943.06 17-FEB-19:00
Water Heater:WaterSystems:NaturalGas 2663.34 15908.90 09-JAN-10:40 245943.06 17-FEB-19:00
Heating:NaturalGas 127.52 0.00 01-JAN-00:10 146434.37 15-NOV-04:40
Boiler:Heating:NaturalGas 127.52 0.00 01-JAN-00:10 146434.37 15-NOV-04:40


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 9348.80 0.00 03-JAN-04:50 695354.81 09-AUG-18:10
PlantLoopCoolingDemand:HVAC 9348.80 0.00 03-JAN-04:50 695354.81 09-AUG-18:10
CoolingCoils:PlantLoopCoolingDemand 9348.80 0.00 03-JAN-04:50 695354.81 09-AUG-18:10


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 06-JAN-21:30
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 06-JAN-21:30
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 06-JAN-21:30
Water Heater:WaterSystems:Water 5742.51 0.00 11-JAN-01:20 0.00 02-JAN-19:20
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 06-JAN-21:30
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 06-JAN-21:30
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 06-JAN-21:30
Water Heater:WaterSystems:MainsWater 5742.51 0.00 11-JAN-01:20 0.00 02-JAN-19:20
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 06-JAN-08:00
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 06-JAN-08:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 41461.08 140245.74 10-MAR-11:30 2995371.26 10-SEP-15:20
EnergyTransfer:Building 6249.31 75464.15 21-MAR-03:40 351822.07 28-JUN-18:20
EnergyTransfer:Zone:KITCHEN_FLR_6 751.42 10229.90 11-JAN-01:30 36452.83 10-SEP-10:50
Refrigeration:EnergyTransfer 188.27 4047.27 04-FEB-23:30 10433.44 21-MAR-06:10
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 94.14 2023.63 04-FEB-23:30 5216.72 21-MAR-06:10
General:Refrigeration:EnergyTransfer 94.14 2023.63 04-FEB-23:30 5216.72 21-MAR-06:10
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 94.14 2023.63 04-FEB-23:30 5216.72 21-MAR-06:10
EnergyTransfer:Plant 22658.11 12567.90 23-MAR-02:40 1658432.10 09-SEP-21:00
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.73 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 72.40 1824.14 23-NOV-04:20 2620.91 23-JAN-07:40
EnergyTransfer:Zone:BASEMENT 482.19 3845.27 21-MAR-03:40 25206.82 13-JAN-22:50
Heating:EnergyTransfer 15.07 0.00 01-JAN-00:10 39404.55 21-DEC-09:10
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 1.49 11-MAR-07:20
General:Heating:EnergyTransfer 15.07 0.00 01-JAN-00:10 39404.55 21-DEC-09:10
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 1.49 11-MAR-07:20
Cooling:EnergyTransfer 6140.11 66598.32 21-MAR-03:40 348212.53 28-JUN-18:20
Cooling:EnergyTransfer:Zone:BASEMENT 482.19 3845.27 21-MAR-03:40 25206.82 13-JAN-22:50
General:Cooling:EnergyTransfer 6140.11 66598.32 21-MAR-03:40 348212.53 28-JUN-18:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 482.19 3845.27 21-MAR-03:40 25206.82 13-JAN-22:50
EnergyTransfer:Zone:RETAIL_1_FLR_1 54.34 1.29 21-DEC-08:50 4038.21 16-DEC-13:30
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.03 0.00 01-JAN-00:10 635.79 05-FEB-07:00
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.03 0.00 01-JAN-00:10 635.79 05-FEB-07:00
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 54.32 0.00 05-JAN-07:10 4038.21 16-DEC-13:30
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 54.32 0.00 05-JAN-07:10 4038.21 16-DEC-13:30
EnergyTransfer:Zone:RETAIL_2_FLR_1 43.48 349.91 21-MAR-03:40 2374.63 30-AUG-21:00
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 36.86 12-MAR-06:20
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 36.86 12-MAR-06:20
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 43.48 349.91 21-MAR-03:40 2374.63 30-AUG-21:00
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 43.48 349.91 21-MAR-03:40 2374.63 30-AUG-21:00
EnergyTransfer:Zone:MECH_FLR_1 40.84 176.32 21-MAR-03:40 2564.04 19-JUL-20:00
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 113.81 06-FEB-09:00
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 113.81 06-FEB-09:00
Cooling:EnergyTransfer:Zone:MECH_FLR_1 40.84 176.32 21-MAR-03:40 2564.04 19-JUL-20:00
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 40.84 176.32 21-MAR-03:40 2564.04 19-JUL-20:00
EnergyTransfer:Zone:STORAGE_FLR_1 18.91 79.73 21-MAR-03:40 1018.05 07-JUL-21:00
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 68.25 06-FEB-09:00
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 68.25 06-FEB-09:00
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 18.91 78.67 21-MAR-03:40 1018.05 07-JUL-21:00
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 18.91 78.67 21-MAR-03:40 1018.05 07-JUL-21:00
EnergyTransfer:Zone:LAUNDRY_FLR_1 619.61 6976.77 21-MAR-03:40 39225.39 07-JUL-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 619.61 6976.77 21-MAR-03:40 39225.39 07-JUL-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 619.61 6976.77 21-MAR-03:40 39225.39 07-JUL-20:00
EnergyTransfer:Zone:CAFE_FLR_1 261.23 2618.27 11-MAR-13:10 14238.98 10-DEC-13:00
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 212.95 11-MAR-07:20
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 212.95 11-MAR-07:20
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 261.23 2618.27 11-MAR-13:10 14238.98 10-DEC-13:00
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 261.23 2618.27 11-MAR-13:10 14238.98 10-DEC-13:00
EnergyTransfer:Zone:LOBBY_FLR_1 877.49 9053.38 10-JAN-11:30 44128.75 05-OCT-21:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 75.86 11-MAR-07:20
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 75.86 11-MAR-07:20
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 877.49 9053.38 10-JAN-11:30 44128.75 05-OCT-21:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 877.49 9053.38 10-JAN-11:30 44128.75 05-OCT-21:10
EnergyTransfer:Zone:ROOM_1_FLR_3 88.58 0.20 03-MAR-03:20 11189.20 10-SEP-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 1.56 0.00 01-JAN-00:10 3997.29 05-FEB-09:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 1.56 0.00 01-JAN-00:10 3997.29 05-FEB-09:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 87.02 0.00 03-JAN-03:50 11189.20 10-SEP-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 87.02 0.00 03-JAN-03:50 11189.20 10-SEP-15:10
EnergyTransfer:Zone:ROOM_2_FLR_3 80.65 0.15 05-FEB-13:00 10712.57 10-SEP-15:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 2.69 0.00 01-JAN-00:10 4812.23 05-FEB-09:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 2.69 0.00 01-JAN-00:10 4812.23 05-FEB-09:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 77.96 0.00 03-JAN-02:50 10712.57 10-SEP-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 77.96 0.00 03-JAN-02:50 10712.57 10-SEP-15:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 584.99 3831.65 12-MAR-05:00 55157.78 10-DEC-14:30
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 584.99 3831.65 12-MAR-05:00 55157.78 10-DEC-14:30
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 584.99 3831.65 12-MAR-05:00 55157.78 10-DEC-14:30
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 626.11 1.54 11-MAR-05:50 66278.51 28-JUN-18:20
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 3.06 0.00 01-JAN-00:10 22039.01 05-FEB-16:10
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 3.06 0.00 01-JAN-00:10 22039.01 05-FEB-16:10
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 623.05 0.00 04-JAN-03:00 66278.51 28-JUN-18:20
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 623.05 0.00 04-JAN-03:00 66278.51 28-JUN-18:20
EnergyTransfer:Zone:ROOM_5_FLR_3 89.16 0.03 26-NOV-04:30 9813.35 10-SEP-15:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 1.61 0.00 01-JAN-00:10 3728.11 21-DEC-09:10
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 1.61 0.00 01-JAN-00:10 3728.11 21-DEC-09:10
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 87.55 0.00 03-JAN-03:30 9813.35 10-SEP-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 87.55 0.00 03-JAN-03:30 9813.35 10-SEP-15:10
EnergyTransfer:Zone:ROOM_6_FLR_3 81.15 0.03 17-NOV-04:20 9552.60 29-MAY-08:10
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 2.73 0.00 01-JAN-00:10 4153.89 20-DEC-19:10
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 2.73 0.00 01-JAN-00:10 4153.89 20-DEC-19:10
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 78.42 0.00 03-JAN-02:30 9552.60 29-MAY-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 78.42 0.00 03-JAN-02:30 9552.60 29-MAY-08:10
EnergyTransfer:Zone:CORRIDOR_FLR_3 236.13 1251.03 21-MAR-03:40 12050.49 24-AUG-20:10
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.01 0.00 01-JAN-00:10 569.94 12-MAR-06:50
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.01 0.00 01-JAN-00:10 569.94 12-MAR-06:50
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 236.12 1251.03 21-MAR-03:40 12050.49 24-AUG-20:10
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 236.12 1251.03 21-MAR-03:40 12050.49 24-AUG-20:10
EnergyTransfer:Zone:ROOM_1_FLR_6 22.26 0.01 20-FEB-05:00 2982.40 05-OCT-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 0.87 0.00 01-JAN-00:10 1203.95 05-FEB-07:00
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 0.87 0.00 01-JAN-00:10 1203.95 05-FEB-07:00
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 21.38 0.00 03-JAN-01:50 2982.40 05-OCT-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 21.38 0.00 03-JAN-01:50 2982.40 05-OCT-15:10
EnergyTransfer:Zone:ROOM_2_FLR_6 20.50 0.03 14-JAN-20:20 2873.11 10-SEP-15:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 1.39 0.00 01-JAN-00:10 1481.91 05-FEB-09:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 1.39 0.00 01-JAN-00:10 1481.91 05-FEB-09:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 19.12 0.00 03-JAN-01:00 2873.11 10-SEP-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 19.12 0.00 03-JAN-01:00 2873.11 10-SEP-15:10
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 133.53 0.29 28-JAN-03:00 14194.48 10-DEC-16:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 1.10 0.00 01-JAN-00:10 5257.95 11-MAR-16:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 1.10 0.00 01-JAN-00:10 5257.95 11-MAR-16:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 132.43 0.00 03-JAN-04:30 14194.48 10-DEC-16:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 132.43 0.00 03-JAN-04:30 14194.48 10-DEC-16:10
EnergyTransfer:Zone:BANQUET_FLR_6 488.04 5097.31 10-JAN-11:30 24015.81 07-JUL-21:20
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 488.04 5097.31 10-JAN-11:30 24015.81 07-JUL-21:20
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 488.04 5097.31 10-JAN-11:30 24015.81 07-JUL-21:20
EnergyTransfer:Zone:DINING_FLR_6 523.12 5912.67 10-JAN-11:30 25179.16 07-JUL-21:20
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 523.12 5912.67 10-JAN-11:30 25179.16 07-JUL-21:20
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 523.12 5912.67 10-JAN-11:30 25179.16 07-JUL-21:20
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 657.29 7580.63 31-DEC-04:10 31376.02 10-SEP-10:50
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 657.29 7580.63 31-DEC-04:10 31376.02 10-SEP-10:50
EnergyTransfer:Zone:CORRIDOR_FLR_6 125.57 4.77 05-FEB-05:00 7409.46 10-SEP-12:00
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.02 0.00 01-JAN-00:10 428.97 06-FEB-09:00
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.02 0.00 01-JAN-00:10 428.97 06-FEB-09:00
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 125.55 0.00 05-FEB-05:00 7409.46 10-SEP-12:00
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 125.55 0.00 05-FEB-05:00 7409.46 10-SEP-12:00
PlantLoopHeatingDemand:Facility 668.43 6646.69 22-JUL-00:30 136851.39 11-JAN-07:10
PlantLoopHeatingDemand:Plant 581.26 6646.69 22-JUL-00:30 43983.86 24-JAN-08:00
WaterSystems:PlantLoopHeatingDemand 581.26 6646.69 22-JUL-00:30 43983.86 24-JAN-08:00
General:WaterSystems:PlantLoopHeatingDemand 581.26 6646.69 22-JUL-00:30 43983.86 24-JAN-08:00
EnergyTransfer:HVAC 12553.65 67.53 21-MAR-14:30 1014068.55 10-SEP-15:20
HeatingCoils:EnergyTransfer 87.17 0.00 01-JAN-00:10 105435.23 05-FEB-19:10
PlantLoopHeatingDemand:HVAC 87.17 0.00 01-JAN-00:10 105435.23 05-FEB-19:10
HeatingCoils:PlantLoopHeatingDemand 87.17 0.00 01-JAN-00:10 105435.23 05-FEB-19:10
CoolingCoils:EnergyTransfer 9348.80 0.00 03-JAN-04:50 695354.81 09-AUG-18:10
HeatRecoveryForHeating:EnergyTransfer 395.55 0.00 01-JAN-00:10 365527.20 05-FEB-07:00
HeatRecoveryForCooling:EnergyTransfer 2722.14 0.00 01-JAN-00:10 343424.65 10-SEP-12:20
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 581.26 6646.69 22-JUL-00:30 43983.86 24-JAN-08:00
WaterUse:WaterSystems:EnergyTransfer 581.26 6646.69 22-JUL-00:30 43983.86 24-JAN-08:00
Boilers:EnergyTransfer 86.14 0.00 01-JAN-00:10 103114.93 20-DEC-01:10
Chillers:EnergyTransfer 9507.38 0.00 03-JAN-04:50 703707.87 09-AUG-18:10
HeatRejection:EnergyTransfer 12389.19 0.00 03-JAN-04:50 938088.96 10-SEP-15:20
General:HeatRejection:EnergyTransfer 12389.19 0.00 03-JAN-04:50 938088.96 10-SEP-15:20



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -482.194 0.000 0.000 139.512 173.462 150.255 0.000 0.000 0.000 18.965 0.000 0.000 0.000 0.000 -0.004
RETAIL_1_FLR_1 0.000 0.000 0.028 -54.316 0.000 0.000 14.632 8.614 10.186 21.695 0.000 0.710 4.656 0.000 -5.054 0.000 -1.150 -0.000
RETAIL_2_FLR_1 0.000 0.000 0.000 -43.481 0.000 0.000 16.302 9.975 11.795 0.000 0.000 0.269 5.641 0.000 0.000 0.000 -0.501 -0.000
MECH_FLR_1 0.000 0.000 0.003 -40.837 0.000 0.000 3.535 16.635 12.471 0.000 0.000 0.636 8.624 0.000 0.000 0.000 -1.067 0.000
STORAGE_FLR_1 0.000 0.000 0.002 -18.905 0.000 0.000 2.737 2.785 3.598 0.000 0.000 0.372 10.012 0.000 0.000 0.000 -0.601 0.000
LAUNDRY_FLR_1 0.000 0.000 0.000 -619.618 0.000 0.000 11.264 4.368 658.131 0.000 0.000 1.025 0.000 0.000 0.000 0.000 -1.612 -53.558
CAFE_FLR_1 0.000 0.000 0.001 -261.234 0.000 0.000 182.931 18.006 14.341 60.145 0.000 1.499 3.373 0.000 -16.075 0.000 -2.985 -0.001
LOBBY_FLR_1 0.000 0.000 0.000 -877.497 0.000 0.000 539.601 121.983 148.998 80.271 0.000 4.271 12.266 0.000 -21.179 0.000 -8.713 -0.001
ROOM_1_FLR_3 2.546 -68.720 0.000 -19.284 0.000 0.000 9.656 6.366 12.292 47.336 0.000 2.592 19.966 0.000 -9.795 0.000 -2.956 -0.000
ROOM_2_FLR_3 4.131 -60.323 0.000 -19.083 0.000 0.000 9.676 6.366 12.291 37.792 0.000 2.614 19.370 0.000 -9.947 0.000 -2.887 -0.000
ROOM_3_MULT19_FLR_3 0.000 -273.575 0.000 -311.415 0.000 0.000 0.000 76.021 228.754 265.903 0.000 9.201 105.787 0.000 -64.097 0.000 -36.581 0.000
ROOM_4_MULT19_FLR_3 12.832 -378.296 0.000 -254.504 0.000 0.000 184.489 76.042 228.817 134.912 0.000 16.842 54.557 0.000 -53.039 0.000 -22.652 -0.004
ROOM_5_FLR_3 2.602 -69.181 0.000 -19.361 0.000 0.000 9.648 6.366 12.292 47.846 0.000 2.583 19.703 0.000 -9.513 0.000 -2.986 -0.001
ROOM_6_FLR_3 4.179 -60.705 0.000 -19.162 0.000 0.000 9.669 6.366 12.291 38.075 0.000 2.600 19.045 0.000 -9.444 0.000 -2.913 -0.001
CORRIDOR_FLR_3 0.000 0.000 0.012 -236.123 0.000 0.000 110.915 109.603 0.000 43.365 0.000 1.887 0.001 0.000 -14.227 0.000 -3.409 -12.023
ROOM_1_FLR_6 1.241 -16.939 0.000 -4.807 0.000 0.000 2.416 1.592 3.073 11.766 0.000 0.647 4.165 0.000 -2.396 0.000 -0.756 -0.000
ROOM_2_FLR_6 1.884 -14.862 0.000 -4.754 0.000 0.000 2.421 1.591 3.073 9.411 0.000 0.653 3.743 0.000 -2.422 0.000 -0.738 -0.000
ROOM_3_MULT9_FLR_6 2.091 -102.293 0.000 -31.129 0.000 0.000 21.704 9.005 27.097 60.019 0.000 3.177 25.828 0.000 -11.199 0.000 -4.300 -0.002
BANQUET_FLR_6 0.000 0.000 0.000 -488.046 0.000 0.000 315.221 34.744 175.857 12.047 0.000 0.866 0.000 0.000 -9.256 0.000 -2.062 -39.372
DINING_FLR_6 0.000 0.000 0.000 -523.127 0.000 0.000 314.667 34.744 175.857 11.758 0.000 0.859 0.000 0.000 -9.626 0.000 -2.083 -3.049
KITCHEN_FLR_6 0.000 0.000 0.000 -657.276 0.000 0.000 28.177 13.327 550.372 21.553 0.000 0.768 52.008 0.000 -7.069 0.000 -1.859 0.000
CORRIDOR_FLR_6 0.000 0.000 0.017 -125.549 0.000 0.000 29.582 28.999 0.000 20.211 0.000 0.799 53.810 0.000 -6.410 0.000 -1.460 0.000
Total Facility 31.507 -1044.894 0.064 -5111.703 0.000 0.000 1958.754 766.959 2451.839 924.103 0.000 54.870 441.522 0.000 -260.747 0.000 -104.271 -108.017


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 15-NOV-06:54 0.00 0.00 0.00 -39613.44 0.00 0.00 5175.64 6304.56 5323.05 0.00 0.00 0.00 22810.19 0.00 -0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 16-DEC-13:30 0.00 0.00 0.00 -4037.96 0.00 0.00 225.91 195.67 252.59 4725.54 0.00 40.78 0.00 0.00 -0.00 0.00 0.00 -1402.53
RETAIL_2_FLR_1 30-AUG-21:00 0.00 0.00 0.00 -2374.74 0.00 0.00 697.61 725.08 752.15 0.00 0.00 23.68 176.22 0.00 -0.00 0.00 0.00 0.00
MECH_FLR_1 19-JUL-20:00 0.00 0.00 0.00 -2564.08 0.00 0.00 129.09 1360.40 839.45 0.00 0.00 51.94 183.22 0.00 -0.00 0.00 0.00 0.00
STORAGE_FLR_1 08-MAR-23:15 0.00 0.00 0.00 -1045.11 0.00 0.00 141.51 75.91 101.96 0.00 0.00 0.00 834.28 0.00 -0.00 0.00 -108.55 0.00
LAUNDRY_FLR_1 06-JAN-21:47 0.00 0.00 0.00 -51490.72 0.00 0.00 408.40 317.52 41967.83 0.00 0.00 0.00 9097.79 0.00 -0.00 0.00 -300.83 0.00
CAFE_FLR_1 18-DEC-00:13 0.00 0.00 0.00 -16137.23 0.00 0.00 9001.49 391.53 304.82 0.00 0.00 0.00 9689.70 0.00 -2809.36 0.00 -440.96 0.00
LOBBY_FLR_1 18-DEC-00:35 0.00 0.00 0.00 -63890.34 0.00 0.00 26350.52 2281.15 3167.12 0.00 0.00 0.00 37337.19 0.00 -3870.28 0.00 -1375.36 0.00
ROOM_1_FLR_3 28-JUN-15:02 0.00 -11425.03 0.00 -755.84 0.00 0.00 235.28 137.21 273.93 6604.67 0.00 278.73 4651.05 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_3 05-JUN-15:02 0.00 -11137.50 0.00 -754.45 0.00 0.00 235.28 137.19 273.90 6320.27 0.00 235.86 4689.45 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 10-DEC-14:30 0.00 -44332.53 0.00 -10824.64 0.00 0.00 0.00 1930.94 5686.12 52402.13 0.00 590.49 0.00 0.00 -0.00 0.00 0.00 -5452.51
ROOM_4_MULT19_FLR_3 13-JUN-18:02 0.00 -65482.05 0.00 -10403.85 0.00 0.00 6374.49 5209.05 9610.21 10921.07 0.00 1219.97 42551.13 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 18-JUL-15:02 0.00 -10265.39 0.00 -756.86 0.00 0.00 235.27 137.21 273.93 3223.08 0.00 318.84 6833.92 0.00 -0.00 0.00 0.00 0.00
ROOM_6_FLR_3 18-JUL-15:02 0.00 -10055.44 0.00 -757.80 0.00 0.00 235.28 137.19 273.90 3201.60 0.00 318.46 6646.81 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 08-MAR-23:15 0.00 0.00 0.00 -13047.88 0.00 0.00 5633.58 2987.71 0.00 0.00 0.00 0.00 7928.79 0.00 -2901.99 0.00 -600.21 0.00
ROOM_1_FLR_6 05-OCT-15:02 0.00 -3017.10 0.00 -191.17 0.00 0.00 58.82 34.30 68.48 2012.16 0.00 70.69 963.80 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_6 10-SEP-15:02 0.00 -2918.99 0.00 -191.21 0.00 0.00 32.68 40.42 76.38 1715.53 0.00 81.77 1163.42 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 10-DEC-16:02 0.00 -13908.96 0.00 -1238.87 0.00 0.00 294.09 228.73 673.54 6424.69 0.00 112.13 7414.65 0.00 -0.00 0.00 0.00 0.00
BANQUET_FLR_6 20-JAN-23:40 0.00 0.00 0.00 -31636.64 0.00 0.00 15643.65 1031.35 6747.90 0.00 0.00 0.00 9975.63 0.00 -1456.30 0.00 -305.59 0.00
DINING_FLR_6 20-JAN-23:40 0.00 0.00 0.00 -33275.45 0.00 0.00 15643.28 1031.35 6747.90 0.00 0.00 0.00 11639.20 0.00 -1479.79 0.00 -306.49 0.00
KITCHEN_FLR_6 09-JAN-19:10 0.00 0.00 0.00 -33968.63 0.00 0.00 1081.50 968.74 21760.70 0.00 0.00 0.00 11757.45 0.00 -1292.99 0.00 -306.77 0.00
CORRIDOR_FLR_6 10-SEP-12:00 0.00 0.00 0.00 -7409.28 0.00 0.00 462.69 790.51 0.00 2915.49 0.00 156.58 3084.01 0.00 -0.00 0.00 0.00 0.00
Total Facility 05-OCT-18:02 0.00 -151009.12 0.00 -227984.22 0.00 0.00 73729.02 55920.94 122326.88 16865.08 0.00 5348.59 104802.83 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 11-MAR-07:16 0.00 0.00 13.43 0.00 0.00 0.00 4014.16 4728.51 4258.44 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -13014.54
RETAIL_1_FLR_1 06-FEB-08:59 0.00 0.00 1580.28 0.00 0.00 0.00 358.04 313.07 360.84 1266.95 0.00 0.00 0.00 0.00 -0.00 0.00 -174.64 -3704.55
RETAIL_2_FLR_1 12-MAR-06:20 0.00 0.00 166.14 0.00 0.00 0.00 712.87 362.54 417.86 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -71.56 -1587.84
MECH_FLR_1 06-FEB-08:59 0.00 0.00 1022.78 0.00 0.00 0.00 87.68 604.62 441.81 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -159.27 -1997.63
STORAGE_FLR_1 06-FEB-08:59 0.00 0.00 615.71 0.00 0.00 0.00 67.45 101.21 127.45 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -91.85 -819.97
LAUNDRY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 30-DEC-08:33 0.00 0.00 1061.22 0.00 0.00 0.00 5830.35 477.67 508.04 0.00 0.00 0.00 0.00 0.00 -666.94 0.00 -408.40 -6801.93
LOBBY_FLR_1 12-MAR-06:20 0.00 0.00 459.91 0.00 0.00 0.00 22990.75 4562.30 5278.53 0.00 0.00 0.00 0.00 0.00 -3402.79 0.00 -1240.46 -28648.24
ROOM_1_FLR_3 05-JAN-09:01 6879.30 363.93 0.00 -363.93 0.00 0.00 104.22 215.61 453.05 1084.00 0.00 0.00 0.00 0.00 -0.00 0.00 -404.27 -8331.90
ROOM_2_FLR_3 05-JAN-09:01 7034.38 286.28 0.00 -286.28 0.00 0.00 108.79 215.58 452.99 0.00 0.00 0.00 0.00 0.00 -955.84 0.00 -374.27 -6481.63
ROOM_3_MULT19_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 05-JAN-09:01 37955.05 5058.24 0.00 -5058.24 0.00 0.00 1951.81 2575.24 8433.45 0.00 0.00 0.00 0.00 0.00 -5808.77 0.00 -2162.87 -42943.90
ROOM_5_FLR_3 11-MAR-09:01 6609.87 362.44 0.00 -362.44 0.00 0.00 156.60 274.41 653.23 0.00 0.00 0.00 0.00 0.00 -782.13 0.00 -402.49 -6509.49
ROOM_6_FLR_3 04-JAN-19:01 6684.84 335.93 0.00 -335.93 0.00 0.00 407.28 436.07 516.20 0.00 0.00 0.00 0.00 0.00 -2063.07 0.00 -440.21 -5541.11
CORRIDOR_FLR_3 12-MAR-06:20 0.00 0.00 1620.35 0.00 0.00 0.00 4850.24 3983.61 0.00 0.00 0.00 0.00 0.00 0.00 -2455.83 0.00 -496.43 -7501.95
ROOM_1_FLR_6 05-JAN-09:01 2089.29 75.39 0.00 -75.39 0.00 0.00 27.06 53.90 113.26 292.14 0.00 0.00 0.00 0.00 -0.00 0.00 -95.49 -2480.17
ROOM_2_FLR_6 05-JAN-09:01 2103.34 71.61 0.00 -71.61 0.00 0.00 27.22 53.90 113.25 0.00 0.00 0.00 0.00 0.00 -227.17 0.00 -94.02 -1976.51
ROOM_3_MULT9_FLR_6 20-DEC-09:02 9467.44 551.89 0.00 -551.89 0.00 0.00 239.42 304.96 998.70 2801.47 0.00 0.00 0.00 0.00 -0.00 0.00 -614.99 -13197.01
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 06-FEB-08:59 0.00 0.00 3941.77 0.00 0.00 0.00 733.34 1054.01 0.00 641.04 0.00 0.00 0.00 0.00 -0.00 0.00 -218.43 -6151.72
Total Facility 20-DEC-09:02 -33759.88 118334.14 0.00 -118334.14 0.00 0.00 23032.49 26712.50 88432.23 28429.87 0.00 0.00 0.00 0.00 -12205.87 0.00 -14118.82 -106522.51



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 21.7655 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 21.6490 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 11.6663 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.6663 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.000000 142.3000 0.003581 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.001045 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.7732 2.7732 1.4864 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3321 0.3321 0.1780 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2457 0.2457 0.1317 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2441 0.2441 0.1308 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1174 0.1174 0.0629 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.2755 3.2755 1.7557 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3929 1.3929 0.7466 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.5635 4.5635 2.4460 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4060 1.4060 0.7536 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1680 2.1680 1.1621 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2713 2.2713 1.2174 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2318 2.2318 1.1962 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7441 0.7441 0.3988 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 21.7655 21.6490 21.7655 11.6663 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4864 1.4864 1.4864 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1780 0.1780 0.1780 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1317 0.1317 0.1317 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1308 0.1308 0.1308 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0629 0.0629 0.0629 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7557 1.7557 1.7557 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7466 0.7466 0.7466 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4460 2.4460 2.4460 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7536 0.7536 0.7536 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1621 1.1621 1.1621 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2174 1.2174 1.2174 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1962 1.1962 1.1962 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3988 0.3988 0.3988 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 11.6663 11.6663 11.6663 11.6663 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 106.00
Number of hours not met 106.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 127.52 146434.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 2881.81 239091.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 766.96 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 242.79 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 959.56 59492.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 14.43 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 8.99 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 32.45 1868.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.91 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 620.46 43376.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 187.26 7976.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 230.97 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.74 4738.75 2663.34 245943.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 20.56 1973.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 35.17 1223.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1807.84 7480.31
Natural Gas 1788.84 4579.69
Additional 0.00 0.00
Total 3596.67 12060.01


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 67.60
Space Heating 0.00
Space Cooling 254.01
Fans (All) 54.69
Service Water Heating 8.00
Receptacle Equipment 153.81
Miscellaneous (All) 659.33
Subtotal 659.33


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 11.24
Service Water Heating 234.75
Miscellaneous (All) 403.66
Subtotal 403.66


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 6.36
Space Heating 1.06
Space Cooling 23.90
Fans (All) 5.14
Service Water Heating 22.84
Receptacle Equipment 29.30
Miscellaneous 11.40


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2667. 8760.
LTG_SCH_LOBBY 3061. 8760.
LTG_SCH_STORAGE 1339. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 2678. 8760.
LTG_SCH_GUESTROOM 2482. 8760.
LTG_SCH_CORRIDOR 3061. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3924. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 18.89 365 18.89 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 23.33 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8760.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 8760.00 0.00 0.00 0.00 0.00
Sum 192720.00 0.00 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 0.00 0.00 0.00 0.00
Average 288887.05 0.00 0.00 0.00 0.00
Sum 6355515.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8276.83 483.17 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 6171.17 2588.83 0.00 0.00 0.00
LOBBY_FLR_1 6419.33 2340.67 0.00 0.00 0.00
ROOM_1_FLR_3 8759.33 0.67 0.00 0.00 0.00
ROOM_2_FLR_3 8759.50 0.50 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8747.83 12.17 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8759.17 0.83 0.00 0.00 0.00
ROOM_5_FLR_3 8759.50 0.50 0.00 0.00 0.00
ROOM_6_FLR_3 8759.33 0.67 0.00 0.00 0.00
CORRIDOR_FLR_3 8133.17 626.83 0.00 0.00 0.00
ROOM_1_FLR_6 8758.67 1.33 0.00 0.00 0.00
ROOM_2_FLR_6 8758.17 1.83 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8757.83 2.17 0.00 0.00 0.00
BANQUET_FLR_6 6292.67 2467.33 0.00 0.00 0.00
DINING_FLR_6 6510.00 2250.00 0.00 0.00 0.00
KITCHEN_FLR_6 8377.00 383.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 6171.17 0.00 0.00 0.00 0.00
Max 8760.00 2588.83 0.00 0.00 0.00
Average 8252.70 507.30 0.00 0.00 0.00
Sum 181559.50 11160.50 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 53972.67 5183.33 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 405246.17 305170.83 0.00 0.00 0.00
LOBBY_FLR_1 1312644.50 802784.50 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 89686.00 10672.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 747553.17 498161.83 0.00 0.00 0.00
DINING_FLR_6 783777.50 461937.50 0.00 0.00 0.00
KITCHEN_FLR_6 105324.67 2944.33 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 1312644.50 802784.50 0.00 0.00 0.00
Average 194030.03 94857.02 0.00 0.00 0.00
Sum 4268660.67 2086854.33 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:00

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

For: Environment

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A

For: Environment

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA

For: Environment

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.416542E+11 39064.24 06-JAN-22:40 6.00 5.49 0.806543E+10 4899.61 11-JAN-01:39 9.67 7.64
February 0.342713E+11 25658.23 06-FEB-08:58 7.20 3.08 0.692547E+10 4837.02 02-FEB-22:19 7.20 3.08
March 0.356520E+11 26363.70 08-MAR-23:15 5.87 1.20 0.733310E+10 4688.43 01-MAR-22:10 5.87 1.20
April 0.334783E+11 18101.74 11-APR-05:50 8.77 7.22 0.680449E+10 4387.85 03-APR-22:10 8.77 7.22
May 0.363240E+11 17034.72 28-MAY-10:33 30.73 24.05 0.714499E+10 4472.98 26-MAY-21:19 30.73 24.05
June 0.364495E+11 17446.27 28-JUN-18:10 32.02 24.80 0.707729E+10 4548.40 07-JUN-22:10 32.02 24.80
July 0.403349E+11 18621.77 16-JUL-10:33 30.77 25.98 0.768166E+10 4837.01 14-JUL-21:19 30.77 25.98
August 0.452002E+11 23275.10 16-AUG-21:00 20.40 20.40 0.815903E+10 4837.07 09-AUG-21:19 20.40 20.40
September 0.445451E+11 23948.76 13-SEP-21:00 23.70 22.33 0.791220E+10 4837.07 20-SEP-21:19 23.87 21.31
October 0.463655E+11 29201.00 28-OCT-07:59 10.00 6.23 0.818121E+10 4837.17 05-OCT-00:30 10.00 6.23
November 0.440181E+11 39615.74 15-NOV-06:54 7.70 5.16 0.791219E+10 4934.14 16-NOV-05:00 9.40 7.22
December 0.438984E+11 38677.73 25-DEC-21:59 7.50 4.99 0.815275E+10 4960.62 29-DEC-23:10 7.67 7.67
                     
Annual Sum or Average 0.482192E+12         0.913498E+11        
Minimum of Months 0.334783E+11 17034.72   5.87 1.20 0.680449E+10 4387.85   5.87 1.20
Maximum of Months 0.463655E+11 39615.74   32.02 25.98 0.818121E+10 4960.62   32.02 25.98



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.372051E+10 3906.38 01-JAN-13:00 25.00 18.55 0.685268E+09 489.46 19-JAN-22:30 21.00 21.00
February 0.352128E+10 3064.04 27-FEB-14:00 25.50 19.91 0.629154E+09 480.21 27-FEB-22:30 19.10 18.33
March 0.364702E+10 2742.76 08-MAR-23:15 5.87 1.20 0.693764E+09 477.87 06-MAR-22:30 5.87 1.20
April 0.413821E+10 2349.83 22-APR-13:40 30.13 20.59 0.699665E+09 491.81 21-APR-21:40 30.13 20.59
May 0.491304E+10 2487.22 04-MAY-18:20 29.07 23.40 0.785202E+09 491.82 11-MAY-21:19 27.43 20.93
June 0.488857E+10 2623.38 28-JUN-18:13 31.83 24.61 0.772626E+09 491.82 13-JUN-23:19 31.83 24.61
July 0.514249E+10 2702.07 19-JUL-18:03 29.90 23.96 0.799722E+09 491.82 07-JUL-23:19 29.90 23.96
August 0.522764E+10 2831.36 31-AUG-13:30 31.90 24.83 0.806888E+09 491.82 03-AUG-21:19 31.90 24.83
September 0.502529E+10 3619.26 10-SEP-12:00 35.20 27.76 0.768394E+09 491.82 22-SEP-21:19 26.60 21.18
October 0.544364E+10 3798.83 07-OCT-12:40 32.33 26.58 0.789416E+09 491.83 02-OCT-21:19 32.33 26.58
November 0.456417E+10 3751.78 06-NOV-13:30 27.75 20.95 0.709217E+09 491.82 06-NOV-22:19 22.80 19.34
December 0.408427E+10 4038.21 16-DEC-13:30 27.50 21.97 0.702596E+09 491.81 15-DEC-22:19 27.50 21.97
                     
Annual Sum or Average 0.543161E+11         0.884191E+10        
Minimum of Months 0.352128E+10 2349.83   5.87 1.20 0.629154E+09 477.87   5.87 1.20
Maximum of Months 0.544364E+10 4038.21   35.20 27.76 0.806888E+09 491.83   32.33 26.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.316553E+10 2255.88 04-JAN-20:28 4.00 1.68 0.872538E+09 569.54 20-JAN-00:20 21.00 21.00
February 0.294801E+10 2132.00 13-FEB-23:30 7.05 4.53 0.797379E+09 569.54 28-FEB-00:20 19.40 18.62
March 0.326549E+10 2363.70 08-MAR-23:15 5.87 1.20 0.888849E+09 569.53 07-MAR-22:19 5.87 1.20
April 0.345417E+10 2074.22 21-APR-21:00 25.50 20.23 0.889682E+09 569.54 23-APR-23:19 20.97 20.31
May 0.395347E+10 2256.55 04-MAY-21:00 24.40 21.68 0.949335E+09 569.54 14-MAY-23:19 24.40 22.09
June 0.395214E+10 2326.05 13-JUN-20:10 30.03 21.76 0.925752E+09 569.54 18-JUN-23:19 25.00 23.90
July 0.409931E+10 2361.16 07-JUL-21:00 29.40 24.96 0.954339E+09 569.54 31-JUL-23:19 25.40 24.02
August 0.411594E+10 2374.63 30-AUG-21:00 29.30 22.51 0.960097E+09 569.54 16-AUG-23:19 29.30 22.51
September 0.386967E+10 2255.94 10-SEP-20:00 28.50 25.08 0.922048E+09 569.54 19-SEP-23:19 22.90 21.31
October 0.395105E+10 2353.52 05-OCT-21:00 27.00 24.12 0.948494E+09 569.56 05-OCT-00:30 27.00 24.12
November 0.340721E+10 2315.31 12-NOV-07:37 7.20 4.19 0.886103E+09 569.54 05-NOV-23:19 7.20 4.19
December 0.329889E+10 2183.89 06-DEC-01:02 8.33 6.68 0.887107E+09 569.63 18-DEC-00:40 6.67 3.05
                     
Annual Sum or Average 0.434809E+11         0.108817E+11        
Minimum of Months 0.294801E+10 2074.22   4.00 1.20 0.797379E+09 569.53   5.87 1.20
Maximum of Months 0.411594E+10 2374.63   30.03 25.08 0.960097E+09 569.63   29.30 24.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.268981E+10 2058.86 04-JAN-20:28 4.00 1.68 0.165952E+09 115.22 19-JAN-22:10 21.00 21.00
February 0.252414E+10 1914.77 13-FEB-23:30 7.05 4.53 0.153511E+09 115.93 28-FEB-22:10 18.72 18.64
March 0.290654E+10 2228.77 08-MAR-23:15 5.87 1.20 0.173935E+09 116.77 30-MAR-21:19 18.80 18.47
April 0.319815E+10 1712.64 28-APR-20:00 23.30 22.57 0.179456E+09 120.45 27-APR-21:19 23.30 22.57
May 0.387444E+10 2191.04 30-MAY-20:00 25.60 21.66 0.200141E+09 120.45 11-MAY-21:19 25.60 21.66
June 0.397479E+10 2499.90 28-JUN-20:00 29.40 24.14 0.196305E+09 120.45 08-JUN-21:19 29.40 24.14
July 0.416417E+10 2564.04 19-JUL-20:00 28.90 24.51 0.202608E+09 120.45 20-JUL-21:19 25.60 23.50
August 0.407838E+10 2450.28 21-AUG-20:00 29.10 23.04 0.203152E+09 120.45 03-AUG-21:19 29.10 23.04
September 0.374718E+10 2425.52 10-SEP-20:00 28.50 25.08 0.193772E+09 120.45 07-SEP-21:19 28.50 25.08
October 0.372812E+10 2327.19 06-OCT-20:00 27.00 26.21 0.196887E+09 120.45 16-OCT-21:19 21.00 19.20
November 0.307164E+10 2203.97 12-NOV-07:37 7.20 4.19 0.175513E+09 120.45 02-NOV-21:19 7.20 4.19
December 0.287986E+10 1993.13 06-DEC-01:02 8.33 6.68 0.172545E+09 120.45 15-DEC-22:10 22.83 21.99
                     
Annual Sum or Average 0.408372E+11         0.221378E+10        
Minimum of Months 0.252414E+10 1712.64   4.00 1.20 0.153511E+09 115.22   7.20 4.19
Maximum of Months 0.416417E+10 2564.04   29.40 26.21 0.203152E+09 120.45   29.40 25.08



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.125526E+10 951.81 04-JAN-20:28 4.00 1.68 0.125612E+09 85.32 19-JAN-23:10 21.00 21.00
February 0.117513E+10 900.61 13-FEB-23:30 7.05 4.53 0.116276E+09 85.45 28-FEB-22:40 18.47 18.18
March 0.135502E+10 1045.08 08-MAR-23:15 5.87 1.20 0.131559E+09 86.03 30-MAR-22:10 18.78 18.48
April 0.150665E+10 784.81 23-APR-10:33 26.43 20.52 0.135667E+09 90.26 28-APR-21:40 23.87 23.13
May 0.178655E+10 836.11 29-MAY-10:33 29.63 23.21 0.152630E+09 92.66 11-MAY-21:19 29.63 23.21
June 0.181056E+10 970.82 28-JUN-20:40 28.67 24.24 0.150426E+09 92.66 13-JUN-23:19 28.67 24.24
July 0.190068E+10 1018.05 07-JUL-21:00 29.40 24.96 0.155358E+09 92.66 18-JUL-23:19 28.30 24.28
August 0.185839E+10 963.30 24-AUG-20:00 32.00 24.63 0.155699E+09 92.66 03-AUG-21:19 32.00 24.63
September 0.173104E+10 969.38 10-SEP-20:00 28.50 25.08 0.147899E+09 92.65 11-SEP-23:19 26.47 23.33
October 0.173010E+10 885.04 06-OCT-21:00 27.00 26.21 0.149998E+09 92.66 12-OCT-22:30 25.00 20.82
November 0.144975E+10 1043.06 12-NOV-07:37 7.20 4.19 0.132928E+09 90.35 03-NOV-21:40 7.20 4.19
December 0.134595E+10 948.59 06-DEC-01:02 8.33 6.68 0.130642E+09 88.95 15-DEC-22:40 22.33 21.13
                     
Annual Sum or Average 0.189051E+11         0.168469E+10        
Minimum of Months 0.117513E+10 784.81   4.00 1.20 0.116276E+09 85.32   7.20 4.19
Maximum of Months 0.190068E+10 1045.08   32.00 26.21 0.155699E+09 92.66   32.00 24.63



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.501555E+11 51493.28 06-JAN-21:47 6.17 5.66 0.586152E+09 458.05 06-JAN-22:10 6.00 5.49
February 0.457641E+11 48728.76 17-FEB-19:30 5.50 3.17 0.528651E+09 424.74 16-FEB-22:00 5.50 3.17
March 0.512338E+11 48979.09 09-MAR-21:57 6.60 2.73 0.588402E+09 485.53 09-MAR-22:00 6.70 2.98
April 0.507936E+11 38607.34 21-APR-20:00 23.80 20.03 0.570264E+09 381.68 25-APR-21:19 21.63 20.21
May 0.541143E+11 39036.39 03-MAY-20:00 28.30 22.17 0.592583E+09 381.71 12-MAY-21:10 26.60 22.01
June 0.527662E+11 39183.14 13-JUN-20:00 30.60 21.74 0.574506E+09 381.71 16-JUN-21:10 27.12 24.23
July 0.543735E+11 39225.39 07-JUL-20:00 29.40 24.64 0.592942E+09 381.72 21-JUL-21:10 28.30 24.97
August 0.543648E+11 39072.55 02-AUG-20:00 27.90 21.66 0.593900E+09 381.76 29-AUG-21:10 27.63 22.99
September 0.519896E+11 38824.07 01-SEP-20:00 23.90 22.40 0.572643E+09 381.75 05-SEP-21:10 26.12 22.72
October 0.533630E+11 38894.08 05-OCT-20:00 27.00 24.12 0.591414E+09 381.78 24-OCT-21:10 26.83 26.05
November 0.501707E+11 38498.34 02-NOV-20:00 25.00 23.33 0.568775E+09 382.27 15-NOV-22:10 8.92 5.67
December 0.505230E+11 48310.18 29-DEC-20:06 8.83 8.27 0.584886E+09 481.76 29-DEC-23:10 7.67 7.67
                     
Annual Sum or Average 0.619612E+12         0.694512E+10        
Minimum of Months 0.457641E+11 38498.34   5.50 2.73 0.528651E+09 381.68   5.50 2.98
Maximum of Months 0.543735E+11 51493.28   30.60 24.64 0.593900E+09 485.53   28.30 26.05



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.199387E+11 13996.24 01-JAN-13:00 25.00 18.55 0.103203E+11 6567.64 11-JAN-01:39 9.67 7.64
February 0.182862E+11 12158.46 13-FEB-23:30 7.05 4.53 0.939219E+10 6521.99 13-FEB-00:00 7.05 4.53
March 0.194335E+11 15153.08 08-MAR-23:05 5.98 1.26 0.103545E+11 6634.60 21-MAR-03:49 9.87 6.98
April 0.200019E+11 10816.15 21-APR-21:10 25.42 20.26 0.102308E+11 6462.06 03-APR-23:19 25.42 20.26
May 0.229427E+11 11582.03 03-MAY-21:10 28.12 22.18 0.108097E+11 6461.99 14-MAY-23:19 24.40 22.09
June 0.226264E+11 11667.57 28-JUN-21:10 28.22 24.33 0.105097E+11 6462.00 10-JUN-01:19 28.22 24.33
July 0.236722E+11 12062.52 07-JUL-21:10 29.22 24.98 0.108321E+11 6461.96 11-JUL-23:19 24.07 22.73
August 0.239896E+11 12338.30 24-AUG-21:10 29.58 23.94 0.109124E+11 6462.00 16-AUG-23:19 29.58 23.94
September 0.230525E+11 12104.71 10-SEP-12:00 35.20 27.76 0.105255E+11 6462.01 19-SEP-23:19 22.90 21.31
October 0.246062E+11 13204.28 05-OCT-15:03 33.67 23.96 0.108768E+11 6462.30 05-OCT-00:20 33.67 23.96
November 0.217326E+11 13584.58 11-NOV-11:00 26.10 21.82 0.103644E+11 6628.11 15-NOV-02:30 9.40 7.34
December 0.209489E+11 16143.57 18-DEC-00:13 7.33 4.14 0.104093E+11 6492.38 18-DEC-00:40 6.67 3.05
                     
Annual Sum or Average 0.261232E+12         0.125538E+12        
Minimum of Months 0.182862E+11 10816.15   5.98 1.26 0.939219E+10 6461.96   6.67 3.05
Maximum of Months 0.246062E+11 16143.57   35.20 27.76 0.109124E+11 6634.60   33.67 24.33



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.648189E+11 61447.11 25-JAN-22:58 8.00 5.68 0.311379E+11 19347.52 03-JAN-23:40 8.00 5.68
February 0.599273E+11 59474.74 16-FEB-22:47 6.78 1.99 0.282579E+11 19276.24 16-FEB-22:40 6.78 1.99
March 0.661351E+11 61221.40 08-MAR-22:33 6.63 1.70 0.313867E+11 19526.95 20-MAR-23:40 9.27 7.69
April 0.687582E+11 38875.23 28-APR-21:10 23.82 23.08 0.308387E+11 19185.38 17-APR-23:19 23.82 23.08
May 0.792556E+11 41317.45 25-MAY-21:10 27.70 24.65 0.322659E+11 19185.25 14-MAY-23:19 27.70 24.65
June 0.787124E+11 42677.92 28-JUN-21:10 28.22 24.33 0.313376E+11 19185.23 18-JUN-23:19 28.22 24.33
July 0.819605E+11 43478.99 07-JUL-21:10 29.22 24.98 0.322912E+11 19185.21 31-JUL-23:19 25.40 24.02
August 0.823132E+11 43656.72 24-AUG-21:10 29.58 23.94 0.324730E+11 19185.27 16-AUG-23:19 29.58 23.94
September 0.780193E+11 42267.23 11-SEP-21:10 25.77 22.42 0.313250E+11 19185.26 19-SEP-23:19 22.90 21.31
October 0.801890E+11 44128.75 05-OCT-21:10 27.17 24.16 0.323831E+11 19185.69 05-OCT-00:30 27.17 24.16
November 0.697302E+11 46666.03 12-NOV-07:34 7.20 4.19 0.309997E+11 19613.90 15-NOV-02:30 9.40 7.34
December 0.676687E+11 63905.50 18-DEC-00:35 6.67 3.05 0.314289E+11 19484.40 18-DEC-00:30 6.67 3.05
                     
Annual Sum or Average 0.877488E+12         0.376126E+12        
Minimum of Months 0.599273E+11 38875.23   6.63 1.70 0.282579E+11 19185.21   6.67 1.99
Maximum of Months 0.823132E+11 63905.50   29.58 24.98 0.324730E+11 19613.90   29.58 24.65



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.743433E+09 2918.95 18-JAN-16:02 24.50 20.23 97178797.84 56.69 19-JAN-00:10 17.08 17.07
February 0.899825E+09 2955.21 23-FEB-16:02 23.93 19.67 88048337.31 56.69 27-FEB-22:19 19.00 18.23
March 0.105041E+10 2972.28 25-MAR-15:02 25.72 19.09 97569689.73 56.69 06-MAR-22:10 25.72 19.09
April 0.166823E+10 3011.09 21-APR-18:02 28.57 20.26 95274469.11 56.70 30-APR-00:10 25.30 22.31
May 0.245393E+10 3036.02 25-MAY-15:02 32.80 24.05 99037019.63 56.70 01-MAY-22:00 32.80 24.05
June 0.256251E+10 3045.02 28-JUN-15:02 33.30 25.80 95917077.86 56.70 16-JUN-02:20 33.30 25.80
July 0.265053E+10 3032.16 06-JUL-15:02 33.03 25.41 99026218.24 56.70 07-JUL-21:10 29.22 24.98
August 0.263788E+10 3029.00 18-AUG-15:02 31.68 25.13 99109492.64 56.70 30-AUG-21:10 29.17 22.55
September 0.237175E+10 3029.17 17-SEP-15:02 31.70 25.72 95769339.77 56.70 03-SEP-00:20 31.70 25.72
October 0.233474E+10 3043.48 06-OCT-15:02 30.17 26.23 98828958.05 56.70 10-OCT-23:40 24.00 22.15
November 0.137584E+10 2998.80 03-NOV-15:02 27.62 23.83 95142837.68 56.70 07-NOV-23:30 23.90 22.91
December 0.100559E+10 3036.62 14-DEC-16:02 26.83 22.74 97398237.31 56.69 15-DEC-23:10 22.00 20.57
                     
Annual Sum or Average 0.217546E+11         0.115830E+10        
Minimum of Months 0.743433E+09 2918.95   23.93 19.09 88048337.31 56.69   17.08 17.07
Maximum of Months 0.265053E+10 3045.02   33.30 26.23 99109492.64 56.70   33.30 25.80



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.448385E+09 2806.95 01-JAN-16:02 24.83 18.70 95824105.70 56.69 18-JAN-22:00 18.00 18.00
February 0.613798E+09 2848.77 27-FEB-16:02 25.32 20.49 87129986.28 56.69 27-FEB-00:49 25.32 20.49
March 0.846669E+09 2868.76 24-MAR-15:02 26.10 16.63 97068192.55 56.69 01-MAR-00:49 26.10 16.63
April 0.154049E+10 2943.08 21-APR-18:02 28.57 20.26 95108254.60 56.70 29-APR-23:00 25.50 22.43
May 0.243319E+10 2963.52 04-MAY-18:02 29.53 23.53 99044993.58 56.70 01-MAY-23:10 29.53 23.53
June 0.259281E+10 2972.80 05-JUN-15:02 31.70 25.04 95937150.97 56.70 12-JUN-21:10 27.80 21.35
July 0.265816E+10 2959.59 06-JUL-15:02 33.03 25.41 99038088.61 56.70 18-JUL-21:10 28.90 23.28
August 0.256215E+10 2965.21 01-AUG-15:02 33.80 25.02 99102638.04 56.70 03-AUG-02:09 26.17 22.86
September 0.220627E+10 2970.56 09-SEP-15:02 34.10 26.05 95729678.24 56.70 04-SEP-03:09 34.10 26.05
October 0.199477E+10 2963.97 07-OCT-15:02 31.95 25.42 98619733.32 56.70 12-OCT-23:10 24.92 20.85
November 0.948500E+09 2924.52 06-NOV-16:02 28.02 20.18 94363867.70 56.70 02-NOV-21:30 28.02 20.18
December 0.645659E+09 2896.67 15-DEC-16:02 28.00 21.24 96338296.77 56.69 15-DEC-22:10 22.83 21.99
                     
Annual Sum or Average 0.194909E+11         0.115330E+10        
Minimum of Months 0.448385E+09 2806.95   24.83 16.63 87129986.28 56.69   18.00 16.63
Maximum of Months 0.265816E+10 2972.80   34.10 26.05 99102638.04 56.70   34.10 26.05



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.505038E+09 718.30 01-JAN-14:00 26.00 17.88 0.00 0.00 01-JAN-00:10 26.00 17.88
February 0.457332E+09 575.48 27-FEB-14:30 25.80 20.17 0.00 0.00 01-FEB-00:10 25.80 20.17
March 0.419924E+09 494.23 05-MAR-13:30 27.70 18.32 0.00 0.00 01-MAR-00:10 27.70 18.32
April 0.484991E+09 403.95 22-APR-13:40 30.13 20.59 0.00 0.00 01-APR-00:10 30.13 20.59
May 0.704343E+09 405.59 04-MAY-16:20 32.43 21.45 0.00 0.00 01-MAY-00:10 32.43 21.45
June 0.700855E+09 405.63 28-JUN-17:15 32.60 24.82 0.00 0.00 01-JUN-00:10 32.60 24.82
July 0.756596E+09 436.08 19-JUL-17:12 32.20 25.05 0.00 0.00 01-JUL-00:10 32.20 25.05
August 0.784897E+09 472.09 31-AUG-13:30 31.90 24.83 0.00 0.00 01-AUG-00:10 31.90 24.83
September 0.767131E+09 600.64 10-SEP-13:30 35.40 27.53 0.00 0.00 01-SEP-00:10 35.40 27.53
October 0.854209E+09 640.02 13-OCT-13:30 32.60 23.24 0.00 0.00 01-OCT-00:10 32.60 23.24
November 0.677015E+09 688.74 06-NOV-14:00 28.30 21.15 0.00 0.00 01-NOV-00:10 28.30 21.15
December 0.584938E+09 725.76 10-DEC-14:30 27.50 20.13 0.00 0.00 01-DEC-00:10 27.50 20.13
                     
Annual Sum or Average 0.769727E+10         0.00        
Minimum of Months 0.419924E+09 403.95   25.80 17.88 0.00 0.00   25.80 17.88
Maximum of Months 0.854209E+09 725.76   35.40 27.53 0.00 0.00   35.40 27.53



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.266567E+09 881.16 02-JAN-16:02 26.00 18.38 95543661.79 56.69 02-JAN-02:09 26.00 18.38
February 0.316641E+09 881.90 25-FEB-16:02 26.70 19.01 86577364.23 56.69 26-FEB-01:39 15.67 15.34
March 0.441518E+09 927.79 26-MAR-18:02 23.43 19.62 96384042.85 56.69 30-MAR-22:19 18.77 18.48
April 0.643397E+09 968.12 22-APR-18:02 27.83 21.97 93983104.67 56.69 21-APR-23:10 27.83 21.97
May 0.970546E+09 990.77 11-MAY-18:02 30.92 21.33 98316847.00 56.69 11-MAY-21:30 27.25 20.86
June 0.100584E+10 998.51 13-JUN-18:02 31.60 21.55 95390751.54 56.69 08-JUN-21:30 31.60 21.55
July 0.104751E+10 977.60 25-JUL-18:02 30.55 24.53 98450262.26 56.69 18-JUL-22:19 30.55 24.53
August 0.996917E+09 986.39 21-AUG-18:02 31.67 22.43 98431494.97 56.69 30-AUG-21:30 28.90 22.61
September 0.885618E+09 979.33 06-SEP-18:02 29.43 22.92 94873743.01 56.69 22-SEP-21:10 26.60 21.18
October 0.800293E+09 983.41 05-OCT-18:02 31.33 22.75 97625014.96 56.69 05-OCT-21:19 27.33 24.19
November 0.471019E+09 938.19 01-NOV-18:02 27.05 22.83 93336773.65 56.69 01-NOV-22:40 24.87 22.71
December 0.352117E+09 898.84 15-DEC-16:02 28.00 21.24 95841067.45 56.69 11-DEC-22:40 28.00 21.24
                     
Annual Sum or Average 0.819798E+10         0.114475E+10        
Minimum of Months 0.266567E+09 881.16   23.43 18.38 86577364.23 56.69   15.67 15.34
Maximum of Months 0.104751E+10 998.51   31.67 24.53 98450262.26 56.69   31.60 24.53



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.698570E+09 2669.11 01-JAN-16:02 24.83 18.70 97426670.38 56.69 02-JAN-03:39 16.67 16.05
February 0.829422E+09 2637.20 27-FEB-16:02 25.32 20.49 88247402.88 56.69 27-FEB-22:10 18.90 18.13
March 0.108590E+10 2686.39 24-MAR-15:02 26.10 16.63 97865818.84 56.69 29-MAR-21:10 21.10 19.57
April 0.163808E+10 2743.32 17-APR-15:02 25.50 14.14 95504463.65 56.69 30-APR-00:30 24.90 22.08
May 0.258465E+10 2753.90 19-MAY-15:02 31.38 23.47 99151138.99 56.70 03-MAY-21:10 31.38 23.47
June 0.264151E+10 2732.70 30-JUN-15:02 33.22 23.09 96008425.79 56.70 13-JUN-21:10 33.22 23.09
July 0.278160E+10 2755.42 18-JUL-15:02 34.90 25.68 99096996.91 56.70 07-JUL-21:30 34.90 25.68
August 0.266942E+10 2743.35 03-AUG-15:02 35.08 24.84 99174828.30 56.70 02-AUG-21:10 35.08 24.84
September 0.237555E+10 2742.22 03-SEP-15:02 32.62 24.63 95843948.42 56.69 04-SEP-04:40 26.73 23.39
October 0.230678E+10 2738.75 02-OCT-15:02 29.00 21.73 98905975.33 56.70 05-OCT-21:10 27.17 24.16
November 0.136482E+10 2711.78 06-NOV-16:02 28.02 20.18 95389320.28 56.69 01-NOV-21:19 28.02 20.18
December 0.912119E+09 2729.03 10-DEC-16:02 26.67 20.14 97497001.10 56.69 27-DEC-23:10 17.00 15.74
                     
Annual Sum or Average 0.218884E+11         0.116011E+10        
Minimum of Months 0.698570E+09 2637.20   24.83 14.14 88247402.88 56.69   16.67 15.74
Maximum of Months 0.278160E+10 2755.42   35.08 25.68 99174828.30 56.70   35.08 25.68



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.403037E+09 2459.40 01-JAN-16:02 24.83 18.70 95972573.37 56.69 02-JAN-03:09 16.17 15.56
February 0.540752E+09 2416.21 26-FEB-16:02 25.32 19.91 87282974.15 56.69 24-FEB-23:40 25.32 19.91
March 0.872144E+09 2602.39 24-MAR-15:02 26.10 16.63 97426621.29 56.69 31-MAR-00:30 18.10 18.05
April 0.150276E+10 2681.32 17-APR-15:02 25.50 14.14 95413242.74 56.69 20-APR-21:49 21.43 18.46
May 0.256363E+10 2685.64 03-MAY-15:02 32.70 22.01 99152884.53 56.70 03-MAY-21:10 28.12 22.18
June 0.267237E+10 2672.38 20-JUN-15:02 32.02 25.60 96012308.95 56.70 15-JUN-21:10 32.02 25.60
July 0.278921E+10 2703.17 18-JUL-15:02 34.90 25.68 99100415.93 56.70 18-JUL-21:19 28.90 23.53
August 0.259284E+10 2672.83 03-AUG-15:02 35.08 24.84 99172729.86 56.70 30-AUG-21:10 29.17 22.55
September 0.220758E+10 2683.23 10-SEP-15:02 35.38 27.24 95820358.79 56.69 04-SEP-03:49 35.38 27.24
October 0.196106E+10 2641.16 05-OCT-15:02 33.67 23.96 98725254.31 56.69 03-OCT-22:30 33.67 23.96
November 0.940559E+09 2512.46 05-NOV-18:02 24.82 19.45 94533164.24 56.69 02-NOV-22:10 24.82 19.45
December 0.559390E+09 2462.24 09-DEC-16:02 26.83 18.71 96308040.40 56.69 15-DEC-00:10 20.00 20.00
                     
Annual Sum or Average 0.196053E+11         0.115492E+10        
Minimum of Months 0.403037E+09 2416.21   24.82 14.14 87282974.15 56.69   16.17 15.56
Maximum of Months 0.278921E+10 2703.17   35.38 27.24 99172729.86 56.70   35.38 27.24



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.411530E+10 3051.93 04-JAN-20:28 4.00 1.68 0.135160E+10 904.57 02-JAN-00:20 4.00 1.68
February 0.383222E+10 2842.94 13-FEB-23:30 7.05 4.53 0.123825E+10 908.45 28-FEB-22:40 18.47 18.18
March 0.434180E+10 3261.87 08-MAR-23:15 5.87 1.20 0.139634E+10 897.84 07-MAR-22:40 5.87 1.20
April 0.467073E+10 2403.19 29-APR-10:33 29.60 23.18 0.142946E+10 943.19 28-APR-21:49 29.60 23.18
May 0.546856E+10 2561.52 10-MAY-21:00 28.30 21.15 0.158757E+10 951.84 11-MAY-23:19 25.40 20.54
June 0.548083E+10 2976.61 16-JUN-18:03 30.50 24.54 0.155373E+10 951.84 13-JUN-23:19 30.50 24.54
July 0.573164E+10 3003.47 07-JUL-20:10 29.40 24.69 0.160231E+10 951.84 08-JUL-01:19 26.50 24.22
August 0.565747E+10 3012.62 24-AUG-20:10 31.58 24.53 0.160755E+10 951.84 03-AUG-23:19 31.58 24.53
September 0.532939E+10 2978.05 10-SEP-20:10 28.45 24.95 0.154050E+10 951.84 12-SEP-23:19 23.13 21.62
October 0.544827E+10 2953.22 13-OCT-20:10 27.92 23.03 0.157575E+10 951.84 09-OCT-23:19 27.92 23.03
November 0.459683E+10 3233.53 12-NOV-07:37 7.20 4.19 0.142166E+10 951.82 07-NOV-22:40 7.20 4.19
December 0.435748E+10 2971.24 06-DEC-01:02 8.33 6.68 0.139571E+10 931.99 15-DEC-22:40 22.33 21.13
                     
Annual Sum or Average 0.590305E+11         0.177004E+11        
Minimum of Months 0.383222E+10 2403.19   4.00 1.20 0.123825E+10 897.84   4.00 1.20
Maximum of Months 0.573164E+10 3261.87   31.58 24.95 0.160755E+10 951.84   31.58 24.54



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.651598E+09 3081.24 18-JAN-16:02 24.50 20.23 96802510.95 56.69 16-JAN-02:49 24.50 20.23
February 0.822209E+09 3079.81 01-FEB-16:02 24.22 19.68 87810378.24 56.69 27-FEB-00:40 17.67 17.42
March 0.977262E+09 3094.19 03-MAR-16:02 22.62 11.29 97339242.33 56.69 16-MAR-21:40 16.10 15.15
April 0.163084E+10 3148.80 25-APR-15:02 27.62 22.48 95185346.16 56.70 21-APR-22:00 27.62 22.48
May 0.249662E+10 3153.70 29-MAY-18:02 29.22 23.47 99001572.19 56.70 08-MAY-21:49 29.22 23.47
June 0.263535E+10 3186.86 15-JUN-18:02 30.22 24.78 95890032.68 56.70 29-JUN-02:09 26.52 24.63
July 0.271180E+10 3179.31 16-JUL-15:02 31.70 25.48 99000497.59 56.70 02-JUL-23:00 31.70 25.48
August 0.268079E+10 3155.46 09-AUG-15:02 31.28 25.35 99066159.17 56.70 29-AUG-23:00 26.50 23.51
September 0.236789E+10 3177.17 10-SEP-15:02 35.38 27.24 95717450.25 56.70 11-SEP-22:00 26.50 23.37
October 0.227314E+10 3208.21 05-OCT-15:02 33.67 23.96 98718495.39 56.70 13-OCT-23:00 26.00 23.18
November 0.123431E+10 3127.21 03-NOV-15:02 27.62 23.83 94948150.75 56.70 02-NOV-21:49 27.62 23.83
December 0.899416E+09 3137.85 14-DEC-16:02 26.83 22.74 97066785.61 56.69 01-DEC-02:49 26.83 22.74
                     
Annual Sum or Average 0.213812E+11         0.115655E+10        
Minimum of Months 0.651598E+09 3079.81   22.62 11.29 87810378.24 56.69   16.10 15.15
Maximum of Months 0.271180E+10 3208.21   35.38 27.24 99066159.17 56.70   31.70 25.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.381164E+09 2951.53 01-JAN-16:02 24.83 18.70 95361202.95 56.69 17-JAN-03:39 17.00 17.00
February 0.536338E+09 3018.39 27-FEB-16:02 25.32 20.49 86870328.35 56.69 02-FEB-05:00 25.32 20.49
March 0.768753E+09 3007.32 24-MAR-15:02 26.10 16.63 96833288.67 56.69 24-MAR-21:00 18.80 14.75
April 0.149533E+10 3079.44 23-APR-15:02 28.62 21.65 95029563.53 56.70 21-APR-22:30 28.62 21.65
May 0.247455E+10 3099.07 06-MAY-15:02 31.60 23.98 99010709.59 56.70 29-MAY-01:10 25.92 22.94
June 0.266675E+10 3096.01 16-JUN-18:02 30.50 24.54 95912502.97 56.70 16-JUN-00:00 30.50 24.54
July 0.271997E+10 3109.62 18-JUL-18:02 32.43 25.88 99013905.77 56.70 07-JUL-21:10 32.43 25.88
August 0.260151E+10 3105.73 09-AUG-15:02 31.28 25.35 99059207.21 56.70 02-AUG-00:40 31.28 25.35
September 0.219468E+10 3110.20 10-SEP-15:02 35.38 27.24 95676253.77 56.70 21-SEP-22:10 24.80 21.05
October 0.191991E+10 3094.56 08-OCT-15:02 31.00 25.66 98480486.82 56.70 10-OCT-21:40 24.33 21.94
November 0.806259E+09 3015.70 06-NOV-16:02 28.02 20.18 94079341.83 56.69 25-NOV-00:00 16.90 14.55
December 0.553271E+09 3061.33 15-DEC-16:02 28.00 21.24 95918258.71 56.69 01-DEC-00:49 28.00 21.24
                     
Annual Sum or Average 0.191185E+11         0.115125E+10        
Minimum of Months 0.381164E+09 2951.53   24.83 16.63 86870328.35 56.69   16.90 14.55
Maximum of Months 0.271997E+10 3110.20   35.38 27.24 99059207.21 56.70   32.43 25.88



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.846068E+09 1650.24 01-JAN-16:02 24.83 18.70 98106628.70 56.69 02-JAN-01:49 17.17 15.90
February 0.822247E+09 1612.11 28-FEB-16:02 24.30 20.31 88666877.22 56.69 28-FEB-00:10 24.30 20.31
March 0.775270E+09 1625.61 03-MAR-16:02 22.62 11.29 97771816.02 56.69 29-MAR-21:40 21.10 19.57
April 0.970771E+09 1647.07 14-APR-15:02 29.90 21.90 95172772.88 56.69 29-APR-23:00 25.50 22.43
May 0.141336E+10 1652.69 02-MAY-15:02 32.80 23.13 98949269.66 56.70 03-MAY-21:10 28.12 22.18
June 0.142495E+10 1635.70 13-JUN-15:02 33.72 21.38 95828594.53 56.70 28-JUN-21:10 28.22 24.33
July 0.152162E+10 1655.41 07-JUL-15:02 34.90 23.91 98943411.54 56.70 10-JUL-21:10 28.22 25.34
August 0.156339E+10 1657.07 03-AUG-15:02 35.08 24.84 99034609.63 56.70 24-AUG-21:49 29.92 24.12
September 0.149885E+10 1652.67 23-SEP-15:02 28.72 24.17 95735379.45 56.70 11-SEP-21:10 28.72 24.17
October 0.162508E+10 1671.58 15-OCT-15:02 30.00 23.64 98899981.97 56.70 04-OCT-21:40 30.00 23.64
November 0.123789E+10 1675.50 06-NOV-16:02 28.02 20.18 95505851.16 56.69 07-NOV-22:10 24.88 23.63
December 0.101501E+10 1683.06 10-DEC-16:02 26.67 20.14 98115320.96 56.69 15-DEC-00:10 20.00 20.00
                     
Annual Sum or Average 0.147145E+11         0.116073E+10        
Minimum of Months 0.775270E+09 1612.11   22.62 11.29 88666877.22 56.69   17.17 15.90
Maximum of Months 0.162508E+10 1683.06   35.08 24.84 99034609.63 56.70   30.00 25.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.350277E+11 31639.25 20-JAN-23:40 7.20 5.46 0.190106E+11 12524.73 11-JAN-01:39 7.20 5.46
February 0.328785E+11 31247.40 13-FEB-23:47 7.08 4.64 0.172386E+11 12051.35 13-FEB-00:49 7.08 4.64
March 0.376812E+11 31151.45 09-MAR-23:13 6.63 2.98 0.192253E+11 12804.42 21-MAR-03:49 9.87 6.98
April 0.397765E+11 24774.79 11-APR-05:43 8.77 7.22 0.186563E+11 11602.78 11-APR-04:40 8.77 7.22
May 0.453997E+11 23445.39 25-MAY-21:20 27.60 24.44 0.193385E+11 11365.20 19-MAY-21:19 27.60 24.44
June 0.450017E+11 23780.15 28-JUN-21:20 28.13 24.38 0.187542E+11 11369.12 06-JUN-21:19 28.13 24.38
July 0.464139E+11 24015.81 07-JUL-21:20 29.03 25.00 0.193032E+11 11363.47 20-JUL-21:19 25.60 23.50
August 0.459140E+11 23796.42 24-AUG-21:20 29.67 23.99 0.193811E+11 11374.09 15-AUG-21:19 29.67 23.99
September 0.431542E+11 22819.82 05-SEP-21:20 26.13 22.73 0.186935E+11 11374.13 12-SEP-21:19 23.37 21.67
October 0.430609E+11 23230.77 05-OCT-21:20 27.33 24.19 0.192767E+11 11535.13 28-OCT-03:00 11.00 5.69
November 0.373336E+11 30606.25 12-NOV-07:34 7.20 4.19 0.185496E+11 12255.99 15-NOV-02:30 9.40 7.34
December 0.363990E+11 30986.61 05-DEC-23:48 8.17 6.59 0.190591E+11 12331.14 29-DEC-23:10 7.67 7.67
                     
Annual Sum or Average 0.488041E+12         0.226487E+12        
Minimum of Months 0.328785E+11 22819.82   6.63 2.98 0.172386E+11 11363.47   7.08 4.64
Maximum of Months 0.464139E+11 31639.25   29.67 25.00 0.193811E+11 12804.42   29.67 24.44



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.383536E+11 33277.69 20-JAN-23:40 7.20 5.46 0.191378E+11 12610.90 11-JAN-01:39 7.20 5.46
February 0.358588E+11 32932.74 13-FEB-23:47 7.08 4.64 0.173337E+11 12120.39 13-FEB-00:49 7.08 4.64
March 0.410238E+11 32888.64 09-MAR-23:13 6.63 2.98 0.193062E+11 12871.09 21-MAR-03:49 9.87 6.98
April 0.428004E+11 27173.94 11-APR-05:43 8.77 7.22 0.186896E+11 11633.15 11-APR-04:40 8.77 7.22
May 0.481729E+11 24648.75 25-MAY-21:20 27.60 24.44 0.193466E+11 11374.71 19-MAY-21:19 27.60 24.44
June 0.476570E+11 24953.86 28-JUN-21:20 28.13 24.38 0.187585E+11 11381.46 06-JUN-21:19 28.13 24.38
July 0.491408E+11 25179.16 07-JUL-21:20 29.03 25.00 0.193076E+11 11371.08 11-JUL-21:19 23.17 22.27
August 0.486266E+11 24973.66 24-AUG-21:20 29.67 23.99 0.193880E+11 11386.67 15-AUG-21:19 29.67 23.99
September 0.457907E+11 24018.95 05-SEP-21:20 26.13 22.73 0.187039E+11 11383.19 12-SEP-21:19 23.37 21.67
October 0.458073E+11 24591.14 28-OCT-03:54 11.00 5.69 0.192962E+11 11540.59 28-OCT-03:00 11.00 5.69
November 0.403038E+11 32143.56 12-NOV-07:34 7.20 4.19 0.186084E+11 12315.93 15-NOV-02:30 9.40 7.34
December 0.395854E+11 32517.47 05-DEC-23:48 8.17 6.59 0.191638E+11 12431.57 29-DEC-23:10 7.67 7.67
                     
Annual Sum or Average 0.523121E+12         0.227040E+12        
Minimum of Months 0.358588E+11 24018.95   6.63 2.98 0.173337E+11 11371.08   7.08 4.64
Maximum of Months 0.491408E+11 33277.69   29.67 25.00 0.193880E+11 12871.09   29.67 24.44



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.515866E+11 33969.86 09-JAN-19:10 6.00 3.01 0.188264E+11 11390.23 21-JAN-18:40 7.33 4.75
February 0.475512E+11 33491.35 17-FEB-18:33 6.43 3.62 0.170093E+11 11319.62 04-FEB-18:19 6.43 3.62
March 0.533623E+11 32680.60 09-MAR-21:57 6.60 2.73 0.188455E+11 11332.25 11-MAR-18:10 12.80 10.38
April 0.540155E+11 32106.68 11-APR-06:29 10.00 8.56 0.182448E+11 11319.65 22-APR-17:19 29.77 21.51
May 0.584409E+11 30966.11 29-MAY-10:40 29.63 23.21 0.188658E+11 11319.61 06-MAY-17:19 29.63 23.21
June 0.571341E+11 30887.31 17-JUN-10:50 31.60 25.15 0.182613E+11 11319.68 10-JUN-17:19 31.60 25.15
July 0.589840E+11 31135.23 23-JUL-10:40 30.77 25.99 0.188645E+11 11319.67 22-JUL-17:19 30.77 25.99
August 0.585964E+11 30687.14 06-AUG-10:50 30.83 26.52 0.188708E+11 11319.61 12-AUG-17:19 25.00 23.98
September 0.559232E+11 31376.02 10-SEP-10:50 34.28 27.62 0.182550E+11 11319.67 09-SEP-17:19 34.28 27.62
October 0.569165E+11 32950.27 28-OCT-07:59 10.00 6.23 0.188570E+11 11319.67 07-OCT-17:19 10.00 6.23
November 0.524467E+11 33387.49 12-NOV-08:53 8.30 4.40 0.182302E+11 11319.66 25-NOV-18:19 18.37 14.08
December 0.523293E+11 33922.52 20-DEC-16:13 7.67 3.55 0.188282E+11 11328.66 30-DEC-18:19 7.00 4.37
                     
Annual Sum or Average 0.657287E+12         0.221959E+12        
Minimum of Months 0.475512E+11 30687.14   6.00 2.73 0.170093E+11 11319.61   6.43 3.62
Maximum of Months 0.589840E+11 33969.86   34.28 27.62 0.188708E+11 11390.23   34.28 27.62



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.804219E+10 5954.04 04-JAN-20:28 4.00 1.68 0.137895E+10 948.13 02-JAN-00:10 4.00 1.68
February 0.769159E+10 5682.40 13-FEB-23:30 7.05 4.53 0.128118E+10 947.94 28-FEB-22:30 18.55 18.33
March 0.882391E+10 6542.97 08-MAR-23:15 5.87 1.20 0.144928E+10 945.00 29-MAR-21:40 21.10 19.57
April 0.991690E+10 5548.11 28-APR-15:03 33.12 23.52 0.150573E+10 1007.38 28-APR-21:40 23.87 23.13
May 0.120891E+11 6534.70 04-MAY-15:30 32.80 21.80 0.168328E+10 1007.39 11-MAY-21:19 27.43 20.93
June 0.123316E+11 6675.57 14-JUN-14:10 34.72 24.33 0.164536E+10 1007.39 08-JUN-21:19 34.72 24.33
July 0.128072E+11 7108.72 22-JUL-17:12 34.27 26.43 0.169602E+10 1007.39 07-JUL-23:19 34.27 26.43
August 0.125585E+11 6750.49 30-AUG-15:50 35.70 23.57 0.170049E+10 1007.39 03-AUG-21:19 35.70 23.57
September 0.115755E+11 7409.46 10-SEP-12:00 35.20 27.76 0.162433E+10 1007.39 21-SEP-21:19 25.33 21.22
October 0.116281E+11 7113.63 07-OCT-13:00 33.00 26.99 0.164659E+10 1007.39 04-OCT-21:19 33.00 26.99
November 0.942843E+10 6486.39 12-NOV-07:37 7.20 4.19 0.145721E+10 1006.77 07-NOV-22:40 7.20 4.19
December 0.865567E+10 5876.73 06-DEC-01:02 8.33 6.68 0.142951E+10 990.81 15-DEC-22:40 22.33 21.13
                     
Annual Sum or Average 0.125549E+12         0.184979E+11        
Minimum of Months 0.769159E+10 5548.11   4.00 1.20 0.128118E+10 945.00   4.00 1.68
Maximum of Months 0.128072E+11 7409.46   35.70 27.76 0.170049E+10 1007.39   35.70 26.99



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 17.00
February 0.00 0.00 01-FEB-00:03 18.20
March 895.01 13.43 11-MAR-07:16 6.97
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:05 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:05 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:05 21.63
December 0.00 0.00 01-DEC-00:03 14.12
         
Annual Sum or Average 895.01      
Minimum of Months 0.00 0.00   6.97
Maximum of Months 895.01 13.43   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 2919021.59 422.92 22-JAN-07:17 7.67
February 11217160.21 1580.30 06-FEB-08:59 7.20
March 5333511.86 395.41 12-MAR-06:20 7.00
April 14109.94 130.27 11-APR-05:42 8.77
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:05 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:05 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 70984.48 151.67 28-OCT-06:20 10.00
November 1349959.00 408.95 15-NOV-06:03 7.70
December 7112735.62 445.94 20-DEC-07:30 1.50
         
Annual Sum or Average 28017482.70      
Minimum of Months 0.00 0.00   1.50
Maximum of Months 11217160.21 1580.30   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 37740.92 115.23 22-JAN-07:17 7.67
February 7685.86 49.77 04-FEB-08:08 6.60
March 92367.35 166.14 12-MAR-06:20 7.00
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:05 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:05 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 569.27 9.49 23-NOV-06:55 8.00
December 34320.46 119.71 30-DEC-08:45 6.83
         
Annual Sum or Average 172683.86      
Minimum of Months 0.00 0.00   6.60
Maximum of Months 92367.35 166.14   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1133978.33 279.13 22-JAN-07:17 7.67
February 419738.73 1022.79 06-FEB-08:59 7.20
March 633648.58 286.54 12-MAR-06:20 7.00
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:05 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:05 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 265116.37 157.33 15-NOV-06:03 7.70
December 809271.57 226.00 30-DEC-08:45 6.83
         
Annual Sum or Average 3261753.58      
Minimum of Months 0.00 0.00   6.83
Maximum of Months 1133978.33 1022.79   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 780200.98 149.19 22-JAN-07:17 7.67
February 291266.81 615.72 06-FEB-08:59 7.20
March 398156.21 140.48 12-MAR-06:20 7.00
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:05 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:05 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 180221.99 83.75 15-NOV-06:03 7.70
December 511866.49 126.00 30-DEC-08:45 6.83
         
Annual Sum or Average 2161712.48      
Minimum of Months 0.00 0.00   6.83
Maximum of Months 780200.98 615.72   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 17.00
February 0.00 0.00 01-FEB-00:03 18.20
March 0.00 0.00 01-MAR-00:03 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:05 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:05 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:05 21.63
December 0.00 0.00 01-DEC-00:03 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 246491.14 554.54 22-JAN-07:17 7.67
February 236780.96 616.91 04-FEB-08:08 6.60
March 593241.00 946.42 11-MAR-07:16 6.97
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:05 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:05 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 18183.05 178.39 15-NOV-07:20 7.90
December 273018.63 1061.20 30-DEC-08:33 6.67
         
Annual Sum or Average 1367714.77      
Minimum of Months 0.00 0.00   6.60
Maximum of Months 593241.00 1061.20   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 17.00
February 0.00 0.00 01-FEB-00:03 18.20
March 75592.61 459.91 12-MAR-06:20 7.00
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:05 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:05 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:05 21.63
December 34905.56 282.02 21-DEC-09:29 7.00
         
Annual Sum or Average 110498.17      
Minimum of Months 0.00 0.00   7.00
Maximum of Months 75592.61 459.91   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.121074E+09 1719.83 05-JAN-09:01 6.50
February 90299245.91 1712.46 05-FEB-09:02 -0.3
March 75858197.08 1687.94 11-MAR-09:01 6.52
April 898325.41 702.89 23-APR-08:05 22.57
May 813340.03 645.83 21-MAY-08:05 26.10
June 342234.91 515.36 01-JUN-08:05 26.97
July 322763.06 571.08 15-JUL-08:05 28.07
August 440064.90 549.73 18-AUG-08:05 26.88
September 670839.55 719.90 16-SEP-08:05 24.58
October 773839.37 574.79 22-OCT-08:05 23.50
November 3179174.48 669.86 23-NOV-09:03 10.67
December 94961154.08 1697.07 20-DEC-09:02 2.17
         
Annual Sum or Average 0.389633E+09      
Minimum of Months 322763.06 515.36   -0.3
Maximum of Months 0.121074E+09 1719.83   28.07



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.241667E+09 1758.60 05-JAN-09:01 6.50
February 0.148598E+09 1731.11 05-FEB-09:02 -0.3
March 97805965.38 1685.99 12-MAR-08:61 9.18
April 980876.63 749.38 23-APR-08:05 22.57
May 541760.69 624.07 22-MAY-08:05 26.78
June 129832.29 530.82 01-JUN-08:05 26.97
July 218208.35 580.78 12-JUL-08:05 27.77
August 365576.08 484.11 18-AUG-08:05 26.88
September 724659.24 733.15 16-SEP-08:05 24.58
October 1037372.63 673.41 15-OCT-08:05 23.00
November 14874723.10 1620.11 15-NOV-09:01 10.27
December 0.164744E+09 1704.06 20-DEC-09:02 2.17
         
Annual Sum or Average 0.671689E+09      
Minimum of Months 129832.29 484.11   -0.3
Maximum of Months 0.241667E+09 1758.60   27.77



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 17.00
February 0.00 0.00 01-FEB-00:03 18.20
March 0.00 0.00 01-MAR-00:03 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:05 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:05 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:05 21.63
December 0.00 0.00 01-DEC-00:03 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 14706770.63 499.41 05-JAN-09:01 6.50
February 12801137.40 488.17 05-FEB-09:02 -0.3
March 2269620.01 480.21 09-MAR-09:02 4.18
April 270422.70 182.56 01-APR-15:05 19.12
May 62339.71 180.36 23-MAY-08:06 25.18
June 85138.70 109.71 21-JUN-08:07 27.48
July 55490.32 96.85 10-JUL-08:07 29.08
August 17806.08 67.52 03-AUG-08:07 28.58
September 74476.39 130.78 30-SEP-18:07 24.53
October 162598.15 214.74 27-OCT-15:04 17.83
November 562071.98 320.07 12-NOV-16:03 16.33
December 9235134.26 488.88 20-DEC-09:02 2.17
         
Annual Sum or Average 40303006.32      
Minimum of Months 17806.08 67.52   -0.3
Maximum of Months 14706770.63 499.41   29.08



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.127903E+09 1635.02 04-JAN-19:01 5.00
February 88662229.96 1609.52 04-FEB-19:02 4.80
March 73941625.03 1652.49 11-MAR-09:01 6.52
April 321463.38 484.91 11-APR-18:05 21.87
May 31971.79 175.41 22-MAY-08:05 26.78
June 0.00 0.00 01-JUN-00:05 22.93
July 30758.42 307.58 14-JUL-08:05 23.90
August 57612.90 316.56 17-AUG-08:05 25.18
September 54318.80 314.51 29-SEP-08:05 24.68
October 247260.84 404.95 17-OCT-18:05 20.58
November 3796859.81 617.56 25-NOV-09:04 15.50
December 0.107644E+09 1650.95 21-DEC-09:02 6.33
         
Annual Sum or Average 0.402691E+09      
Minimum of Months 0.00 0.00   4.80
Maximum of Months 0.127903E+09 1652.49   26.78



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.244737E+09 1671.21 04-JAN-19:01 5.00
February 0.144361E+09 1623.93 04-FEB-19:02 4.80
March 93855327.37 1647.23 11-MAR-09:01 6.52
April 535622.41 709.92 03-APR-18:05 24.17
May 20898.67 144.07 23-MAY-08:06 25.18
June 0.00 0.00 01-JUN-00:05 22.93
July 14587.90 145.88 14-JUL-08:05 23.90
August 43147.20 253.26 17-AUG-08:05 25.18
September 62776.52 330.17 29-SEP-08:05 24.68
October 742579.90 755.72 27-OCT-15:04 17.83
November 16353251.20 789.05 23-NOV-16:03 17.00
December 0.181876E+09 1655.71 21-DEC-09:02 6.33
         
Annual Sum or Average 0.682603E+09      
Minimum of Months 0.00 0.00   4.80
Maximum of Months 0.244737E+09 1671.21   25.18



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1132184.37 311.04 11-JAN-07:00 8.00
February 274482.76 220.85 07-FEB-06:58 7.70
March 709436.66 405.09 12-MAR-06:20 7.00
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:05 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:05 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 126265.93 136.90 23-NOV-06:55 8.00
December 840461.81 334.47 30-DEC-08:45 6.83
         
Annual Sum or Average 3082831.53      
Minimum of Months 0.00 0.00   6.83
Maximum of Months 1132184.37 405.09   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.279481E+09 2089.29 05-JAN-09:01 6.50
February 0.181957E+09 2057.16 05-FEB-09:02 -0.3
March 0.163556E+09 2036.71 12-MAR-08:61 9.18
April 2373719.13 1005.82 11-APR-08:62 14.18
May 1390429.33 653.17 21-MAY-08:05 26.10
June 899581.29 584.08 27-JUN-08:05 27.38
July 634917.53 612.40 25-JUL-08:05 27.80
August 1124059.67 673.97 12-AUG-08:05 26.37
September 1000130.09 607.74 16-SEP-08:05 24.58
October 2620488.98 663.03 28-OCT-08:62 10.43
November 26972187.88 1933.07 15-NOV-09:01 10.27
December 0.212668E+09 2035.36 20-DEC-09:02 2.17
         
Annual Sum or Average 0.874677E+09      
Minimum of Months 634917.53 584.08   -0.3
Maximum of Months 0.279481E+09 2089.29   27.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.478883E+09 2103.34 05-JAN-09:01 6.50
February 0.279396E+09 2073.50 05-FEB-09:02 -0.3
March 0.201680E+09 2033.52 12-MAR-08:61 9.18
April 4427664.10 1368.55 11-APR-08:62 14.18
May 1167325.01 673.18 21-MAY-08:05 26.10
June 463446.06 486.55 27-JUN-08:05 27.38
July 357656.12 607.40 25-JUL-08:05 27.80
August 964035.06 597.50 12-AUG-08:05 26.37
September 1027142.95 615.48 09-SEP-08:05 26.78
October 6167953.15 1334.28 28-OCT-08:62 10.43
November 69933740.16 1961.88 15-NOV-09:01 10.27
December 0.340785E+09 2037.75 20-DEC-09:02 2.17
         
Annual Sum or Average 0.138525E+10      
Minimum of Months 357656.12 486.55   -0.3
Maximum of Months 0.478883E+09 2103.34   27.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 28362564.92 789.02 13-JAN-09:02 8.17
February 27383897.59 1038.74 05-FEB-09:02 -0.3
March 35861548.93 1051.21 11-MAR-16:01 10.68
April 390491.43 322.44 11-APR-18:05 21.87
May 440402.80 388.13 22-MAY-08:05 26.78
June 255184.01 374.41 09-JUN-08:05 25.55
July 171018.98 352.47 13-JUL-08:05 25.00
August 276221.06 384.74 15-AUG-08:05 25.60
September 318963.08 324.08 29-SEP-08:05 24.68
October 175718.69 329.68 25-OCT-08:05 25.00
November 105184.30 170.96 22-NOV-09:05 13.58
December 28033394.89 1051.95 20-DEC-09:02 2.17
         
Annual Sum or Average 0.121775E+09      
Minimum of Months 105184.30 170.96   -0.3
Maximum of Months 35861548.93 1051.95   26.78



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 17.00
February 0.00 0.00 01-FEB-00:03 18.20
March 0.00 0.00 01-MAR-00:03 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:05 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:05 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:05 21.63
December 0.00 0.00 01-DEC-00:03 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 17.00
February 0.00 0.00 01-FEB-00:03 18.20
March 0.00 0.00 01-MAR-00:03 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:05 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:05 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:05 21.63
December 0.00 0.00 01-DEC-00:03 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 17.00
February 0.00 0.00 01-FEB-00:03 18.20
March 0.00 0.00 01-MAR-00:03 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:05 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:05 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:05 21.63
December 0.00 0.00 01-DEC-00:03 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 4927191.23 955.38 22-JAN-07:17 7.67
February 3478936.32 3941.84 06-FEB-08:59 7.20
March 2747288.51 882.00 12-MAR-06:20 7.00
April 2364.89 39.41 11-APR-05:42 8.77
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:05 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:05 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 1937721.87 715.72 23-NOV-06:55 8.00
December 3819091.38 968.94 30-DEC-18:17 7.00
         
Annual Sum or Average 16912594.20      
Minimum of Months 0.00 0.00   7.00
Maximum of Months 4927191.23 3941.84   25.13



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.147273E+11 14185.34 02-JAN-20:10 0.127587E+11 10113.80 02-JAN-20:10
February 0.132974E+11 14185.34 01-FEB-20:10 0.115208E+11 10113.80 01-FEB-20:10
March 0.147727E+11 14185.34 01-MAR-20:10 0.127855E+11 10113.80 01-MAR-20:10
April 0.142280E+11 14185.34 03-APR-19:10 0.123314E+11 10113.80 03-APR-19:10
May 0.147528E+11 14185.34 01-MAY-19:10 0.127741E+11 10113.80 01-MAY-19:10
June 0.142932E+11 14185.34 01-JUN-19:10 0.123716E+11 10113.80 01-JUN-19:10
July 0.146876E+11 14185.34 03-JUL-19:10 0.127338E+11 10113.80 03-JUL-19:10
August 0.147784E+11 14185.34 01-AUG-19:10 0.127894E+11 10113.80 01-AUG-19:10
September 0.142337E+11 14185.34 01-SEP-19:10 0.123352E+11 10113.80 01-SEP-19:10
October 0.147216E+11 14185.34 02-OCT-19:10 0.127549E+11 10113.80 02-OCT-19:10
November 0.142819E+11 14185.34 01-NOV-19:10 0.123659E+11 10113.80 01-NOV-19:10
December 0.146876E+11 14185.34 01-DEC-20:10 0.127338E+11 10113.80 01-DEC-20:10
             
Annual Sum or Average 0.173462E+12     0.150255E+12    
Minimum of Months 0.132974E+11 14185.34   0.115208E+11 10113.80  
Maximum of Months 0.147784E+11 14185.34   0.127894E+11 10113.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.731324E+09 704.41 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.660319E+09 704.41 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.733578E+09 704.41 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.706528E+09 704.41 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.732592E+09 704.41 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.709769E+09 704.41 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.729351E+09 704.41 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.733860E+09 704.41 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.706810E+09 704.41 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.731042E+09 704.41 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.709205E+09 704.41 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.729351E+09 704.41 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.861373E+10     0.101856E+11    
Minimum of Months 0.660319E+09 704.41   0.780982E+09 685.60  
Maximum of Months 0.733860E+09 704.41   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.846876E+09 815.72 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.764651E+09 815.72 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.849486E+09 815.72 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.818162E+09 815.72 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.848344E+09 815.72 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.821915E+09 815.72 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.844592E+09 815.72 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.849812E+09 815.72 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.818489E+09 815.72 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.846549E+09 815.72 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.821262E+09 815.72 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.844592E+09 815.72 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.997473E+10     0.117950E+11    
Minimum of Months 0.764651E+09 815.72   0.904380E+09 793.93  
Maximum of Months 0.849812E+09 815.72   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.141236E+10 1360.40 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.127524E+10 1360.40 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.141672E+10 1360.40 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.136448E+10 1360.40 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.141481E+10 1360.40 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.137074E+10 1360.40 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.140855E+10 1360.40 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.141726E+10 1360.40 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.136502E+10 1360.40 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.141182E+10 1360.40 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.136965E+10 1360.40 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.140855E+10 1360.40 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.166352E+11     0.124712E+11    
Minimum of Months 0.127524E+10 1360.40   0.956227E+09 839.45  
Maximum of Months 0.141726E+10 1360.40   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.236418E+09 227.72 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.213464E+09 227.72 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.237147E+09 227.72 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.228402E+09 227.72 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.236828E+09 227.72 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.229450E+09 227.72 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.235780E+09 227.72 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.237238E+09 227.72 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.228493E+09 227.72 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.236327E+09 227.72 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.229268E+09 227.72 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.235780E+09 227.72 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.278459E+10     0.359760E+10    
Minimum of Months 0.213464E+09 227.72   0.275845E+09 242.16  
Maximum of Months 0.237238E+09 227.72   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.370859E+09 357.21 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.334852E+09 357.21 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.372002E+09 357.21 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.358285E+09 357.21 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.371502E+09 357.21 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.359929E+09 357.21 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.369859E+09 357.21 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.372145E+09 357.21 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.358428E+09 357.21 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.370717E+09 357.21 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.359643E+09 357.21 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.369859E+09 357.21 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.436808E+10     0.679355E+11    
Minimum of Months 0.334852E+09 357.21   0.520895E+10 4572.80  
Maximum of Months 0.372145E+09 357.21   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.158756E+10 1761.91 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.141889E+10 1761.91 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.154500E+10 1761.91 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.146201E+10 1761.91 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.147281E+10 1761.91 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.141056E+10 1761.91 01-JUN-19:10 0.118076E+10 965.27 01-JUN-19:10
July 0.145130E+10 1761.91 03-JUL-19:19 0.121533E+10 965.27 03-JUL-19:10
August 0.149847E+10 1761.91 01-AUG-19:10 0.122063E+10 965.27 01-AUG-19:10
September 0.147865E+10 1761.91 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.155914E+10 1761.91 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.152967E+10 1761.91 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.159194E+10 1761.91 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.180060E+11     0.143405E+11    
Minimum of Months 0.141056E+10 1761.91   0.109956E+10 965.27  
Maximum of Months 0.159194E+10 1761.91   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104087E+11 10265.18 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.938580E+10 10265.18 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.104013E+11 10265.18 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.999145E+10 10265.18 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.103248E+11 10265.18 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.998433E+10 10265.18 01-JUN-19:10 0.122682E+11 10029.21 01-JUN-19:10
July 0.102612E+11 10265.18 03-JUL-19:10 0.126273E+11 10029.21 03-JUL-19:10
August 0.103576E+11 10265.18 01-AUG-19:10 0.126824E+11 10029.21 01-AUG-19:10
September 0.100097E+11 10265.18 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.103816E+11 10265.18 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.100856E+11 10265.18 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.103904E+11 10265.18 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.121983E+12     0.148998E+12    
Minimum of Months 0.938580E+10 10265.18   0.114244E+11 10029.21  
Maximum of Months 0.104087E+11 10265.18   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85091918.49 76.99 01-JAN-19:10 0.255708E+09 232.19 01-JAN-08:09
February 76846309.13 76.99 01-FEB-20:10 0.230956E+09 232.19 01-FEB-07:10
March 84415649.14 76.99 01-MAR-20:10 0.255355E+09 232.19 01-MAR-07:10
April 82445007.08 76.99 01-APR-18:10 0.247516E+09 232.19 01-APR-07:10
May 84753783.81 76.99 01-MAY-19:10 0.255532E+09 232.19 01-MAY-06:10
June 81790910.76 76.99 01-JUN-19:10 0.247163E+09 232.19 01-JUN-06:10
July 85418966.65 76.99 01-JUL-18:10 0.255885E+09 232.19 01-JUL-07:10
August 84415649.14 76.99 01-AUG-19:10 0.255355E+09 232.19 01-AUG-06:10
September 82467180.11 76.99 01-SEP-19:10 0.247516E+09 232.19 01-SEP-06:10
October 85080831.98 76.99 01-OCT-18:10 0.255708E+09 232.19 01-OCT-07:10
November 82117958.92 76.99 01-NOV-19:10 0.247340E+09 232.19 01-NOV-06:10
December 85430053.17 76.99 01-DEC-20:10 0.255885E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.100027E+10     0.300992E+10    
Minimum of Months 76846309.13 76.99   0.230956E+09 232.19  
Maximum of Months 85430053.17 76.99   0.255885E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85115186.72 77.01 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 76867322.62 77.01 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 84438732.44 77.01 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 82467551.52 77.01 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 84776959.58 77.01 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 81813276.33 77.01 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 85442324.32 77.01 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 84438732.44 77.01 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 82489730.61 77.01 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 85104097.18 77.01 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 82140413.93 77.01 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 85453413.86 77.01 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.100055E+10     0.301074E+10    
Minimum of Months 76867322.62 77.01   0.231020E+09 232.26  
Maximum of Months 85453413.86 77.01   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.232638E+10 2240.78 02-JAN-20:10 0.00 0.00
February 0.210051E+10 2240.78 01-FEB-20:10 0.00 0.00
March 0.233355E+10 2240.78 01-MAR-20:10 0.00 0.00
April 0.224750E+10 2240.78 03-APR-19:10 0.00 0.00
May 0.233041E+10 2240.78 01-MAY-19:10 0.00 0.00
June 0.225781E+10 2240.78 01-JUN-19:10 0.00 0.00
July 0.232011E+10 2240.78 03-JUL-19:10 0.00 0.00
August 0.233445E+10 2240.78 01-AUG-19:10 0.00 0.00
September 0.224840E+10 2240.78 01-SEP-19:10 0.00 0.00
October 0.232548E+10 2240.78 02-OCT-19:10 0.00 0.00
November 0.225602E+10 2240.78 01-NOV-19:10 0.00 0.00
December 0.232011E+10 2240.78 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.274007E+11     0.00 0.00
Minimum of Months 0.210051E+10 2240.78   0.00 0.00
Maximum of Months 0.233445E+10 2240.78   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85115186.72 77.01 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 76867322.62 77.01 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 84438732.44 77.01 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 82467551.52 77.01 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 84776959.58 77.01 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 81813276.33 77.01 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 85442324.32 77.01 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 84438732.44 77.01 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 82489730.61 77.01 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 85104097.18 77.01 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 82140413.93 77.01 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 85453413.86 77.01 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.100055E+10     0.301074E+10    
Minimum of Months 76867322.62 77.01   0.231020E+09 232.26  
Maximum of Months 85453413.86 77.01   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.301764E+10 3094.06 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.270888E+10 3094.06 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.297280E+10 3094.06 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.283022E+10 3094.06 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.288736E+10 3094.06 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.277980E+10 3094.06 01-JUN-19:19 0.144540E+11 6747.90 01-JUN-06:10
July 0.286108E+10 3094.06 03-JUL-19:19 0.149358E+11 6747.90 01-JUL-06:10
August 0.291822E+10 3094.06 01-AUG-19:19 0.149358E+11 6747.90 01-AUG-06:10
September 0.285000E+10 3094.06 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.298329E+10 3094.06 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.291988E+10 3094.06 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.301472E+10 3094.06 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.347439E+11     0.175857E+12    
Minimum of Months 0.270888E+10 3094.06   0.134904E+11 6747.90  
Maximum of Months 0.301764E+10 3094.06   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.301764E+10 3094.06 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.270888E+10 3094.06 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.297280E+10 3094.06 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.283022E+10 3094.06 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.288736E+10 3094.06 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.277980E+10 3094.06 01-JUN-19:19 0.144540E+11 6747.90 01-JUN-06:10
July 0.286108E+10 3094.06 03-JUL-19:19 0.149358E+11 6747.90 01-JUL-06:10
August 0.291822E+10 3094.06 01-AUG-19:19 0.149358E+11 6747.90 01-AUG-06:10
September 0.285000E+10 3094.06 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.298329E+10 3094.06 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.291988E+10 3094.06 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.301472E+10 3094.06 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.347439E+11     0.175857E+12    
Minimum of Months 0.270888E+10 3094.06   0.134904E+11 6747.90  
Maximum of Months 0.301764E+10 3094.06   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.113146E+10 1089.83 02-JAN-20:10 0.368383E+11 16487.34 01-JAN-07:10
February 0.102161E+10 1089.83 01-FEB-20:10 0.332733E+11 16487.34 01-FEB-07:10
March 0.113495E+10 1089.83 01-MAR-20:10 0.368383E+11 16487.34 01-MAR-07:10
April 0.109310E+10 1089.83 03-APR-19:10 0.356500E+11 16487.34 01-APR-06:10
May 0.113342E+10 1089.83 01-MAY-19:10 0.368383E+11 16487.34 01-MAY-06:10
June 0.109811E+10 1089.83 01-JUN-19:10 0.356500E+11 16487.34 01-JUN-06:10
July 0.112841E+10 1089.83 03-JUL-19:10 0.368383E+11 16487.34 01-JUL-06:10
August 0.113539E+10 1089.83 01-AUG-19:10 0.368383E+11 16487.34 01-AUG-06:10
September 0.109354E+10 1089.83 01-SEP-19:10 0.356500E+11 16487.34 01-SEP-06:10
October 0.113103E+10 1089.83 02-OCT-19:10 0.368383E+11 16487.34 01-OCT-06:10
November 0.109724E+10 1089.83 01-NOV-19:10 0.356500E+11 16487.34 01-NOV-06:10
December 0.112841E+10 1089.83 01-DEC-20:10 0.368383E+11 16487.34 01-DEC-07:10
             
Annual Sum or Average 0.133267E+11     0.433742E+12    
Minimum of Months 0.102161E+10 1089.83   0.332733E+11 16487.34  
Maximum of Months 0.113539E+10 1089.83   0.368383E+11 16487.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.246211E+10 2371.52 02-JAN-20:10 0.00 0.00
February 0.222306E+10 2371.52 01-FEB-20:10 0.00 0.00
March 0.246970E+10 2371.52 01-MAR-20:10 0.00 0.00
April 0.237864E+10 2371.52 03-APR-19:10 0.00 0.00
May 0.246638E+10 2371.52 01-MAY-19:10 0.00 0.00
June 0.238954E+10 2371.52 01-JUN-19:10 0.00 0.00
July 0.245547E+10 2371.52 03-JUL-19:10 0.00 0.00
August 0.247065E+10 2371.52 01-AUG-19:10 0.00 0.00
September 0.237958E+10 2371.52 01-SEP-19:10 0.00 0.00
October 0.246116E+10 2371.52 02-OCT-19:10 0.00 0.00
November 0.238765E+10 2371.52 01-NOV-19:10 0.00 0.00
December 0.245547E+10 2371.52 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.289994E+11     0.00 0.00
Minimum of Months 0.222306E+10 2371.52   0.00 0.00
Maximum of Months 0.247065E+10 2371.52   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.147273E+11 0.127587E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.132974E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.147727E+11 0.127855E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.142280E+11 0.123314E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.147528E+11 0.127741E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.142932E+11 0.123716E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.146876E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.147784E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.142337E+11 0.123352E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.147216E+11 0.127549E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.142819E+11 0.123659E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.146876E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.173462E+12 0.150255E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.132974E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.147784E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.731324E+09 0.864900E+09 0.00 0.00 0.00 0.00 2396793.11 0.287939E+09
February 0.179968E+10 0.660319E+09 0.780982E+09 0.00 0.00 0.00 0.00 3159994.12 0.206305E+09
March 0.199990E+10 0.733578E+09 0.866718E+09 0.00 0.00 0.00 0.00 9982896.12 0.175721E+09
April 0.192973E+10 0.706528E+09 0.835931E+09 0.00 0.00 0.00 0.00 30063779.19 70307216.87
May 0.199475E+10 0.732592E+09 0.865939E+09 0.00 0.00 0.00 0.00 0.112487E+09 565036.63
June 0.193394E+10 0.709769E+09 0.838659E+09 0.00 0.00 0.00 0.00 0.125362E+09 745303.54
July 0.199054E+10 0.729351E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.137365E+09 73955.74
August 0.199896E+10 0.733860E+09 0.866978E+09 0.00 0.00 0.00 0.00 0.121482E+09 1637932.05
September 0.192879E+10 0.706810E+09 0.836191E+09 0.00 0.00 0.00 0.00 85997483.67 2673738.10
October 0.199148E+10 0.731042E+09 0.864640E+09 0.00 0.00 0.00 0.00 61786809.36 38482087.79
November 0.192552E+10 0.709205E+09 0.838269E+09 0.00 0.00 0.00 0.00 12992567.24 0.136946E+09
December 0.199054E+10 0.729351E+09 0.863211E+09 0.00 0.00 0.00 0.00 6887022.28 0.228753E+09
                   
Annual Sum or Average 0.234744E+11 0.861373E+10 0.101856E+11 0.00 0.00 0.00 0.00 0.709963E+09 0.115015E+10
Minimum of Months 0.179968E+10 0.660319E+09 0.780982E+09 0.00 0.00 0.00 0.00 2396793.11 73955.74
Maximum of Months 0.199990E+10 0.733860E+09 0.866978E+09 0.00 0.00 0.00 0.00 0.137365E+09 0.287939E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.846876E+09 0.100156E+10 0.00 0.00 0.00 0.00 1440240.80 0.119121E+09
February 0.208403E+10 0.764651E+09 0.904380E+09 0.00 0.00 0.00 0.00 2206247.87 87193074.10
March 0.231589E+10 0.849486E+09 0.100366E+10 0.00 0.00 0.00 0.00 4880255.85 78277460.93
April 0.223463E+10 0.818162E+09 0.968011E+09 0.00 0.00 0.00 0.00 11841776.96 36460863.01
May 0.230993E+10 0.848344E+09 0.100276E+10 0.00 0.00 0.00 0.00 40386834.62 1087595.63
June 0.223950E+10 0.821915E+09 0.971170E+09 0.00 0.00 0.00 0.00 46208553.40 915808.84
July 0.230505E+10 0.844592E+09 0.999601E+09 0.00 0.00 0.00 0.00 50584286.16 59790.87
August 0.231480E+10 0.849812E+09 0.100396E+10 0.00 0.00 0.00 0.00 45449092.22 1212762.52
September 0.223354E+10 0.818489E+09 0.968312E+09 0.00 0.00 0.00 0.00 31798757.32 2331467.24
October 0.230614E+10 0.846549E+09 0.100126E+10 0.00 0.00 0.00 0.00 24792196.72 18511697.51
November 0.222975E+10 0.821262E+09 0.970719E+09 0.00 0.00 0.00 0.00 6029814.39 59421854.54
December 0.230505E+10 0.844592E+09 0.999601E+09 0.00 0.00 0.00 0.00 3554771.80 96167272.65
                   
Annual Sum or Average 0.271834E+11 0.997473E+10 0.117950E+11 0.00 0.00 0.00 0.00 0.269173E+09 0.500761E+09
Minimum of Months 0.208403E+10 0.764651E+09 0.904380E+09 0.00 0.00 0.00 0.00 1440240.80 59790.87
Maximum of Months 0.231589E+10 0.849812E+09 0.100396E+10 0.00 0.00 0.00 0.00 50584286.16 0.119121E+09



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.141236E+10 0.105898E+10 0.00 0.00 0.00 0.00 4813984.27 0.254033E+09
February 0.440737E+09 0.127524E+10 0.956227E+09 0.00 0.00 0.00 0.00 7189869.11 0.185216E+09
March 0.489771E+09 0.141672E+10 0.106120E+10 0.00 0.00 0.00 0.00 13971972.84 0.167661E+09
April 0.472586E+09 0.136448E+10 0.102351E+10 0.00 0.00 0.00 0.00 29704301.78 76909439.81
May 0.488511E+09 0.141481E+10 0.106025E+10 0.00 0.00 0.00 0.00 93490880.00 2061048.96
June 0.473617E+09 0.137074E+10 0.102685E+10 0.00 0.00 0.00 0.00 0.105732E+09 1881587.42
July 0.487480E+09 0.140855E+10 0.105691E+10 0.00 0.00 0.00 0.00 0.116035E+09 162561.55
August 0.489542E+09 0.141726E+10 0.106152E+10 0.00 0.00 0.00 0.00 0.104893E+09 2665113.94
September 0.472357E+09 0.136502E+10 0.102382E+10 0.00 0.00 0.00 0.00 74395198.56 4788145.73
October 0.487709E+09 0.141182E+10 0.105866E+10 0.00 0.00 0.00 0.00 59391476.35 40481440.93
November 0.471555E+09 0.136965E+10 0.102637E+10 0.00 0.00 0.00 0.00 16415244.83 0.125351E+09
December 0.487480E+09 0.140855E+10 0.105691E+10 0.00 0.00 0.00 0.00 10114936.50 0.206257E+09
                   
Annual Sum or Average 0.574883E+10 0.166352E+11 0.124712E+11 0.00 0.00 0.00 0.00 0.636147E+09 0.106747E+10
Minimum of Months 0.440737E+09 0.127524E+10 0.956227E+09 0.00 0.00 0.00 0.00 4813984.27 162561.55
Maximum of Months 0.489771E+09 0.141726E+10 0.106152E+10 0.00 0.00 0.00 0.00 0.116035E+09 0.254033E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.236418E+09 0.305485E+09 0.00 0.00 0.00 0.00 2763829.74 0.144285E+09
February 0.339028E+09 0.213464E+09 0.275845E+09 0.00 0.00 0.00 0.00 4140037.48 0.104889E+09
March 0.376747E+09 0.237147E+09 0.306128E+09 0.00 0.00 0.00 0.00 8140236.32 94370834.85
April 0.363528E+09 0.228402E+09 0.295253E+09 0.00 0.00 0.00 0.00 17593087.89 42322900.19
May 0.375778E+09 0.236828E+09 0.305852E+09 0.00 0.00 0.00 0.00 55204326.29 1026245.72
June 0.364321E+09 0.229450E+09 0.296217E+09 0.00 0.00 0.00 0.00 61557442.77 998414.48
July 0.374985E+09 0.235780E+09 0.304889E+09 0.00 0.00 0.00 0.00 67470307.22 75992.00
August 0.376571E+09 0.237238E+09 0.306219E+09 0.00 0.00 0.00 0.00 61090776.01 1422643.91
September 0.363352E+09 0.228493E+09 0.295345E+09 0.00 0.00 0.00 0.00 43814801.34 2423757.75
October 0.375161E+09 0.236327E+09 0.305393E+09 0.00 0.00 0.00 0.00 34843011.28 22383576.24
November 0.362735E+09 0.229268E+09 0.296079E+09 0.00 0.00 0.00 0.00 9712413.74 70367764.23
December 0.374985E+09 0.235780E+09 0.304889E+09 0.00 0.00 0.00 0.00 5850189.59 0.116732E+09
                   
Annual Sum or Average 0.442217E+10 0.278459E+10 0.359760E+10 0.00 0.00 0.00 0.00 0.372180E+09 0.601299E+09
Minimum of Months 0.339028E+09 0.213464E+09 0.275845E+09 0.00 0.00 0.00 0.00 2763829.74 75992.00
Maximum of Months 0.376747E+09 0.237238E+09 0.306219E+09 0.00 0.00 0.00 0.00 67470307.22 0.144285E+09



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.370859E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 5764722.49 0.394294E+09
February 0.139600E+10 0.334852E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 8856381.23 0.286504E+09
March 0.155131E+10 0.372002E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 16991202.09 0.257969E+09
April 0.149688E+10 0.358285E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 41802081.78 0.110951E+09
May 0.154732E+10 0.371502E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 0.152166E+09 1561365.78
June 0.150015E+10 0.359929E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 0.173371E+09 1365078.63
July 0.154405E+10 0.369859E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.190373E+09 190833.76
August 0.155059E+10 0.372145E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.173801E+09 2616338.31
September 0.149615E+10 0.358428E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 0.125620E+09 4864803.26
October 0.154478E+10 0.370717E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 98441173.74 53216308.42
November 0.149361E+10 0.359643E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 23634305.08 0.185032E+09
December 0.154405E+10 0.369859E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 13829594.41 0.313403E+09
                   
Annual Sum or Average 0.182090E+11 0.436808E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 0.102465E+10 0.161197E+10
Minimum of Months 0.139600E+10 0.334852E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 5764722.49 190833.76
Maximum of Months 0.155131E+10 0.372145E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.190373E+09 0.394294E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.158756E+10 0.121771E+10 0.00 0.00 0.00 0.00 5056901.62 0.716057E+09
February 0.236489E+11 0.141889E+10 0.109956E+10 0.00 0.00 0.00 0.00 6755049.87 0.523411E+09
March 0.262800E+11 0.154500E+10 0.122027E+10 0.00 0.00 0.00 0.00 20265043.55 0.458302E+09
April 0.253579E+11 0.146201E+10 0.117692E+10 0.00 0.00 0.00 0.00 62920405.81 0.210628E+09
May 0.262123E+11 0.147281E+10 0.121917E+10 0.00 0.00 0.00 0.00 0.231739E+09 6663516.08
June 0.254132E+11 0.141056E+10 0.118076E+10 0.00 0.00 0.00 0.00 0.267467E+09 5513880.69
July 0.261570E+11 0.145130E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.291856E+09 433638.12
August 0.262677E+11 0.149847E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.260030E+09 7162579.97
September 0.253456E+11 0.147865E+10 0.117729E+10 0.00 0.00 0.00 0.00 0.177591E+09 13523066.86
October 0.261693E+11 0.155914E+10 0.121734E+10 0.00 0.00 0.00 0.00 0.132172E+09 0.107783E+09
November 0.253025E+11 0.152967E+10 0.118021E+10 0.00 0.00 0.00 0.00 27349658.88 0.360684E+09
December 0.261570E+11 0.159194E+10 0.121533E+10 0.00 0.00 0.00 0.00 15334678.04 0.575233E+09
                   
Annual Sum or Average 0.308468E+12 0.180060E+11 0.143405E+11 0.00 0.00 0.00 0.00 0.149854E+10 0.298539E+10
Minimum of Months 0.236489E+11 0.141056E+10 0.109956E+10 0.00 0.00 0.00 0.00 5056901.62 433638.12
Maximum of Months 0.262800E+11 0.159194E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.291856E+09 0.716057E+09



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.104087E+11 0.126520E+11 0.00 0.00 0.00 0.00 17513469.32 0.206342E+10
February 0.702046E+11 0.938580E+10 0.114244E+11 0.00 0.00 0.00 0.00 28242935.12 0.151461E+10
March 0.780153E+11 0.104013E+11 0.126786E+11 0.00 0.00 0.00 0.00 67915582.08 0.136165E+10
April 0.752779E+11 0.999145E+10 0.122282E+11 0.00 0.00 0.00 0.00 0.183752E+09 0.640649E+09
May 0.778146E+11 0.103248E+11 0.126672E+11 0.00 0.00 0.00 0.00 0.645272E+09 20322437.70
June 0.754422E+11 0.998433E+10 0.122682E+11 0.00 0.00 0.00 0.00 0.748556E+09 16727607.28
July 0.776503E+11 0.102612E+11 0.126273E+11 0.00 0.00 0.00 0.00 0.818859E+09 1335784.98
August 0.779788E+11 0.103576E+11 0.126824E+11 0.00 0.00 0.00 0.00 0.735458E+09 21358002.62
September 0.752414E+11 0.100097E+11 0.122320E+11 0.00 0.00 0.00 0.00 0.504684E+09 42187900.53
October 0.776868E+11 0.103816E+11 0.126482E+11 0.00 0.00 0.00 0.00 0.387580E+09 0.319702E+09
November 0.751137E+11 0.100856E+11 0.122624E+11 0.00 0.00 0.00 0.00 85005394.37 0.104019E+10
December 0.776503E+11 0.103904E+11 0.126273E+11 0.00 0.00 0.00 0.00 47767017.10 0.167041E+10
                   
Annual Sum or Average 0.915726E+12 0.121983E+12 0.148998E+12 0.00 0.00 0.00 0.00 0.427061E+10 0.871257E+10
Minimum of Months 0.702046E+11 0.938580E+10 0.114244E+11 0.00 0.00 0.00 0.00 17513469.32 1335784.98
Maximum of Months 0.780153E+11 0.104087E+11 0.126824E+11 0.00 0.00 0.00 0.00 0.818859E+09 0.206342E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 2693123.07 0.155602E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 3911624.95 0.109286E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 8761730.24 93894274.82
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 24106887.82 33147273.01
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 92691900.08 5995.46
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.101671E+09 18382.27
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.111161E+09 17967.01
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.102265E+09 97514.78
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 78438998.60 302661.12
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 60328956.80 15969774.44
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 14144669.15 65547103.36
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 7273709.90 0.120052E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.607449E+09 0.593941E+09
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 2693123.07 5995.46
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.111161E+09 0.155602E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 3086799.49 0.150850E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 4464716.16 0.106354E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 9312915.47 92465364.21
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 24390100.31 32763854.01
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 92668369.72 5995.65
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.101605E+09 18382.94
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.111118E+09 17945.73
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.102286E+09 97362.73
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 78571129.44 298011.22
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 60728143.49 15611691.51
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 14973594.43 63619146.58
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 7874668.89 0.116722E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.611078E+09 0.578823E+09
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 3086799.49 5995.65
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.111118E+09 0.150850E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 85091918.49 0.255708E+09 0.00 0.00 0.00 0.00 435480.45 51272303.34
February 0.00 76846309.13 0.230956E+09 0.00 0.00 0.00 0.00 718959.49 37204386.17
March 0.00 84415649.14 0.255355E+09 0.00 0.00 0.00 0.00 1549986.82 31798516.71
April 0.00 82445007.08 0.247516E+09 0.00 0.00 0.00 0.00 4463539.51 14598582.92
May 0.00 84753783.81 0.255532E+09 0.00 0.00 0.00 0.00 17898794.25 188809.69
June 0.00 81790910.76 0.247163E+09 0.00 0.00 0.00 0.00 20748984.66 215064.89
July 0.00 85418966.65 0.255885E+09 0.00 0.00 0.00 0.00 22930393.16 15331.84
August 0.00 84415649.14 0.255355E+09 0.00 0.00 0.00 0.00 20681120.97 303803.52
September 0.00 82467180.11 0.247516E+09 0.00 0.00 0.00 0.00 14472255.32 580866.43
October 0.00 85080831.98 0.255708E+09 0.00 0.00 0.00 0.00 11285909.08 7134781.89
November 0.00 82117958.92 0.247340E+09 0.00 0.00 0.00 0.00 2404970.22 24911813.80
December 0.00 85430053.17 0.255885E+09 0.00 0.00 0.00 0.00 1343314.94 40660811.26
                   
Annual Sum or Average 0.00 0.100027E+10 0.300992E+10 0.00 0.00 0.00 0.00 0.118934E+09 0.208885E+09
Minimum of Months 0.00 76846309.13 0.230956E+09 0.00 0.00 0.00 0.00 435480.45 15331.84
Maximum of Months 0.00 85430053.17 0.255885E+09 0.00 0.00 0.00 0.00 22930393.16 51272303.34



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 85115186.72 0.255778E+09 0.00 0.00 0.00 0.00 1200488.73 42126379.23
February 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 1710910.26 29607013.03
March 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 3167095.27 25793131.06
April 0.293479E+09 82467551.52 0.247584E+09 0.00 0.00 0.00 0.00 7548906.78 8867519.11
May 0.303504E+09 84776959.58 0.255602E+09 0.00 0.00 0.00 0.00 26510759.80 65.79
June 0.293842E+09 81813276.33 0.247231E+09 0.00 0.00 0.00 0.00 28837790.17 4371.45
July 0.303141E+09 85442324.32 0.255955E+09 0.00 0.00 0.00 0.00 31504393.23 244.97
August 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 29139145.59 23161.28
September 0.293479E+09 82489730.61 0.247584E+09 0.00 0.00 0.00 0.00 22678339.84 74851.31
October 0.303322E+09 85104097.18 0.255778E+09 0.00 0.00 0.00 0.00 17749124.06 4255728.86
November 0.293661E+09 82140413.93 0.247408E+09 0.00 0.00 0.00 0.00 4861098.86 17398973.29
December 0.303141E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 2661502.08 32532132.95
                   
Annual Sum or Average 0.357224E+10 0.100055E+10 0.301074E+10 0.00 0.00 0.00 0.00 0.177570E+09 0.160684E+09
Minimum of Months 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 1200488.73 65.79
Maximum of Months 0.303685E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 31504393.23 42126379.23



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 2659632.03 0.156592E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 3849276.24 0.110110E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 8571095.43 95112131.39
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 23853186.80 33879163.50
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 92326312.84 6000.56
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.101362E+09 18382.79
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.110885E+09 19910.97
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.102036E+09 94924.03
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 78218306.20 323382.90
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 60193777.06 16149468.09
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 14065607.58 66260826.89
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 7246243.81 0.120440E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.605267E+09 0.599007E+09
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 2659632.03 6000.56
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.110885E+09 0.156592E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 3051405.56 0.151604E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 4234337.72 0.107001E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 8735655.78 93710349.34
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 23904361.36 33655024.53
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 92306645.54 6002.40
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.101323E+09 18383.80
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.110852E+09 19929.44
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.102037E+09 94710.15
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 78286982.00 318963.94
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 60431765.76 15791261.25
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 14696990.71 63947394.33
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 7888964.10 0.116740E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.607750E+09 0.582907E+09
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 3051405.56 6002.40
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.110852E+09 0.151604E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.232638E+10 0.00 0.00 0.00 0.00 0.00 2978481.27 0.203204E+09
February 0.348285E+10 0.210051E+10 0.00 0.00 0.00 0.00 0.00 4461475.67 0.147084E+09
March 0.387034E+10 0.233355E+10 0.00 0.00 0.00 0.00 0.00 9270791.38 0.132500E+09
April 0.373454E+10 0.224750E+10 0.00 0.00 0.00 0.00 0.00 21155873.18 60627650.70
May 0.386038E+10 0.233041E+10 0.00 0.00 0.00 0.00 0.00 70201054.42 1752628.33
June 0.374269E+10 0.225781E+10 0.00 0.00 0.00 0.00 0.00 80265411.18 1552171.69
July 0.385223E+10 0.232011E+10 0.00 0.00 0.00 0.00 0.00 88278454.75 168921.13
August 0.386853E+10 0.233445E+10 0.00 0.00 0.00 0.00 0.00 79576942.73 2112519.42
September 0.373273E+10 0.224840E+10 0.00 0.00 0.00 0.00 0.00 55201972.62 4066723.40
October 0.385404E+10 0.232548E+10 0.00 0.00 0.00 0.00 0.00 42938148.45 32775805.68
November 0.372639E+10 0.225602E+10 0.00 0.00 0.00 0.00 0.00 10900321.37 0.101879E+09
December 0.385223E+10 0.232011E+10 0.00 0.00 0.00 0.00 0.00 6641875.36 0.164449E+09
                   
Annual Sum or Average 0.454292E+11 0.274007E+11 0.00 0.00 0.00 0.00 0.00 0.471871E+09 0.852173E+09
Minimum of Months 0.348285E+10 0.210051E+10 0.00 0.00 0.00 0.00 0.00 2978481.27 168921.13
Maximum of Months 0.387034E+10 0.233445E+10 0.00 0.00 0.00 0.00 0.00 88278454.75 0.203204E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 2615497.66 0.155364E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 3790170.73 0.109383E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 8528197.47 93980057.26
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 23626080.44 33513706.64
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 91691860.24 7712.92
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.100687E+09 26099.49
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.110143E+09 23681.78
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.101304E+09 110143.01
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 77536752.62 313703.04
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 59591487.73 15994292.67
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 13863097.83 65808111.78
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 7110550.29 0.119904E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.600488E+09 0.594429E+09
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 2615497.66 7712.92
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.110143E+09 0.155364E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 3036666.33 0.150273E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 4302849.89 0.106309E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 9026866.62 92471165.29
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 23856162.91 33124859.10
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 91663623.29 7711.38
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.100613E+09 26095.28
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.110095E+09 23627.92
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.101324E+09 109984.75
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 77676396.08 309691.62
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 60037462.42 15582391.47
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 14779798.81 63623084.36
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 7754732.31 0.116265E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.604166E+09 0.578126E+09
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 3036666.33 7711.38
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.110095E+09 0.150273E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 85115186.72 0.255778E+09 0.00 0.00 0.00 0.00 1274909.18 81735592.37
February 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 1886149.29 57494601.01
March 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 4296493.83 48967008.83
April 0.293479E+09 82467551.52 0.247584E+09 0.00 0.00 0.00 0.00 12116630.24 17238470.30
May 0.303504E+09 84776959.58 0.255602E+09 0.00 0.00 0.00 0.00 47014897.69 3944.91
June 0.293842E+09 81813276.33 0.247231E+09 0.00 0.00 0.00 0.00 51638785.93 13354.20
July 0.303141E+09 85442324.32 0.255955E+09 0.00 0.00 0.00 0.00 56450082.95 8759.25
August 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 51890685.47 54855.13
September 0.293479E+09 82489730.61 0.247584E+09 0.00 0.00 0.00 0.00 39643376.55 160105.34
October 0.303322E+09 85104097.18 0.255778E+09 0.00 0.00 0.00 0.00 30339440.29 8341753.11
November 0.293661E+09 82140413.93 0.247408E+09 0.00 0.00 0.00 0.00 6982693.87 34407191.04
December 0.303141E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 3562201.00 63098074.55
                   
Annual Sum or Average 0.357224E+10 0.100055E+10 0.301074E+10 0.00 0.00 0.00 0.00 0.307096E+09 0.311524E+09
Minimum of Months 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 1274909.18 3944.91
Maximum of Months 0.303685E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 56450082.95 81735592.37



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.301764E+10 0.149358E+11 0.00 0.00 0.00 0.00 3007429.65 0.482853E+09
February 0.415303E+11 0.270888E+10 0.134904E+11 0.00 0.00 0.00 0.00 4800453.93 0.358175E+09
March 0.461508E+11 0.297280E+10 0.149358E+11 0.00 0.00 0.00 0.00 10684186.30 0.327600E+09
April 0.445315E+11 0.283022E+10 0.144540E+11 0.00 0.00 0.00 0.00 32098706.94 0.156121E+09
May 0.460320E+11 0.288736E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.129006E+09 5399943.84
June 0.446286E+11 0.277980E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.153362E+09 4268209.14
July 0.459349E+11 0.286108E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.169712E+09 738905.66
August 0.461292E+11 0.291822E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.152406E+09 5407778.06
September 0.445099E+11 0.285000E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.102794E+09 11262803.75
October 0.459565E+11 0.298329E+10 0.149358E+11 0.00 0.00 0.00 0.00 81195462.52 75889205.76
November 0.444343E+11 0.291988E+10 0.144540E+11 0.00 0.00 0.00 0.00 16945166.07 0.242516E+09
December 0.459349E+11 0.301472E+10 0.149358E+11 0.00 0.00 0.00 0.00 9811987.63 0.391547E+09
                   
Annual Sum or Average 0.541708E+12 0.347439E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.865825E+09 0.206178E+10
Minimum of Months 0.415303E+11 0.270888E+10 0.134904E+11 0.00 0.00 0.00 0.00 3007429.65 738905.66
Maximum of Months 0.461508E+11 0.301764E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.169712E+09 0.482853E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.301764E+10 0.149358E+11 0.00 0.00 0.00 0.00 2585543.04 0.488341E+09
February 0.415303E+11 0.270888E+10 0.134904E+11 0.00 0.00 0.00 0.00 4312477.66 0.362233E+09
March 0.461508E+11 0.297280E+10 0.149358E+11 0.00 0.00 0.00 0.00 9938180.71 0.331087E+09
April 0.445315E+11 0.283022E+10 0.144540E+11 0.00 0.00 0.00 0.00 31320159.28 0.157406E+09
May 0.460320E+11 0.288736E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.128480E+09 5412986.21
June 0.446286E+11 0.277980E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.153085E+09 4271598.11
July 0.459349E+11 0.286108E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.169477E+09 786817.08
August 0.461292E+11 0.291822E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.151951E+09 5409695.35
September 0.445099E+11 0.285000E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.102156E+09 11333763.18
October 0.459565E+11 0.298329E+10 0.149358E+11 0.00 0.00 0.00 0.00 80461596.71 76376420.45
November 0.444343E+11 0.291988E+10 0.144540E+11 0.00 0.00 0.00 0.00 16146172.23 0.244826E+09
December 0.459349E+11 0.301472E+10 0.149358E+11 0.00 0.00 0.00 0.00 9256016.55 0.395886E+09
                   
Annual Sum or Average 0.541708E+12 0.347439E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.859169E+09 0.208337E+10
Minimum of Months 0.415303E+11 0.270888E+10 0.134904E+11 0.00 0.00 0.00 0.00 2585543.04 786817.08
Maximum of Months 0.461508E+11 0.301764E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.169477E+09 0.488341E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.113146E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 1940699.40 0.438583E+09
February 0.369574E+10 0.102161E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 3528156.67 0.324032E+09
March 0.410691E+10 0.113495E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 8344899.50 0.296247E+09
April 0.396281E+10 0.109310E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 27385255.09 0.138937E+09
May 0.409635E+10 0.113342E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.115513E+09 4447132.16
June 0.397146E+10 0.109811E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.137481E+09 3490015.83
July 0.408770E+10 0.112841E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.152285E+09 673618.79
August 0.410499E+10 0.113539E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.136417E+09 4554588.87
September 0.396089E+10 0.109354E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 91726641.84 9612306.70
October 0.408962E+10 0.113103E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 71689275.18 67195848.20
November 0.395417E+10 0.109724E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 13822202.35 0.217236E+09
December 0.408770E+10 0.112841E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 7845032.00 0.354350E+09
                   
Annual Sum or Average 0.482060E+11 0.133267E+11 0.392709E+12 0.359593E+12 0.00 0.00 0.00 0.767979E+09 0.185936E+10
Minimum of Months 0.369574E+10 0.102161E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 1940699.40 673618.79
Maximum of Months 0.410691E+10 0.113539E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.152285E+09 0.438583E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.246211E+10 0.00 0.00 0.00 0.00 0.00 4078376.25 0.348983E+09
February 0.368610E+10 0.222306E+10 0.00 0.00 0.00 0.00 0.00 5959219.39 0.254928E+09
March 0.409620E+10 0.246970E+10 0.00 0.00 0.00 0.00 0.00 13821031.25 0.228612E+09
April 0.395248E+10 0.237864E+10 0.00 0.00 0.00 0.00 0.00 32918900.01 0.105313E+09
May 0.408566E+10 0.246638E+10 0.00 0.00 0.00 0.00 0.00 0.118819E+09 2763846.91
June 0.396110E+10 0.238954E+10 0.00 0.00 0.00 0.00 0.00 0.137406E+09 2516359.36
July 0.407704E+10 0.245547E+10 0.00 0.00 0.00 0.00 0.00 0.152362E+09 406462.54
August 0.409429E+10 0.247065E+10 0.00 0.00 0.00 0.00 0.00 0.136925E+09 3568556.98
September 0.395056E+10 0.237958E+10 0.00 0.00 0.00 0.00 0.00 94908690.02 6726467.09
October 0.407896E+10 0.246116E+10 0.00 0.00 0.00 0.00 0.00 73685628.72 54130260.03
November 0.394385E+10 0.238765E+10 0.00 0.00 0.00 0.00 0.00 17698881.70 0.171094E+09
December 0.407704E+10 0.245547E+10 0.00 0.00 0.00 0.00 0.00 10127932.37 0.281241E+09
                   
Annual Sum or Average 0.480803E+11 0.289994E+11 0.00 0.00 0.00 0.00 0.00 0.798712E+09 0.146028E+10
Minimum of Months 0.368610E+10 0.222306E+10 0.00 0.00 0.00 0.00 0.00 4078376.25 406462.54
Maximum of Months 0.409620E+10 0.247065E+10 0.00 0.00 0.00 0.00 0.00 0.152362E+09 0.348983E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 14185.34 02-JAN-20:10 10113.80 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 14185.34 01-FEB-20:10 10113.80 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 14185.34 01-MAR-20:10 10113.80 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 14185.34 03-APR-19:10 10113.80 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 14185.34 01-MAY-19:10 10113.80 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 14185.34 01-JUN-19:10 10113.80 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 14185.34 03-JUL-19:10 10113.80 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 14185.34 01-AUG-19:10 10113.80 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 14185.34 01-SEP-19:10 10113.80 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 14185.34 02-OCT-19:10 10113.80 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 14185.34 01-NOV-19:10 10113.80 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 14185.34 01-DEC-20:10 10113.80 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   14185.34   10113.80   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   14185.34   10113.80   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 704.41 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 44.58 02-JAN-15:00 269.72 05-JAN-06:00
February 1169.53 01-FEB-00:10 704.41 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 49.70 02-FEB-13:00 322.14 05-FEB-07:50
March 1169.53 01-MAR-00:10 704.41 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 72.36 30-MAR-13:00 256.41 09-MAR-07:00
April 1169.53 01-APR-00:10 704.41 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 106.13 28-APR-15:00 158.74 11-APR-06:00
May 1169.53 01-MAY-00:10 704.41 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 117.57 28-MAY-16:00 23.23 07-MAY-01:00
June 1169.53 01-JUN-00:10 704.41 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 124.98 14-JUN-14:00 22.88 07-JUN-02:00
July 1169.53 01-JUL-00:10 704.41 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 137.42 22-JUL-16:00 14.89 11-JUL-20:00
August 1169.53 01-AUG-00:10 704.41 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 139.01 30-AUG-16:00 37.02 16-AUG-21:00
September 1169.53 01-SEP-00:10 704.41 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 140.25 09-SEP-17:00 49.13 07-SEP-20:00
October 1169.53 01-OCT-23:10 704.41 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 113.89 05-OCT-15:00 141.68 28-OCT-06:05
November 1169.53 01-NOV-00:10 704.41 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 71.60 01-NOV-14:00 186.85 12-NOV-08:00
December 1169.53 01-DEC-00:10 704.41 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 69.60 13-DEC-15:00 270.48 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   704.41   685.60   0.00 0.00 0.00 0.00 44.58   14.89  
Maximum of Months 1169.53   704.41   685.60   0.00 0.00 0.00 0.00 140.25   322.14  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 815.72 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 18.86 16-JAN-15:00 109.89 05-JAN-06:00
February 1354.32 01-FEB-00:10 815.72 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 24.39 02-FEB-13:00 127.99 05-FEB-08:00
March 1354.32 01-MAR-00:10 815.72 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 31.47 26-MAR-14:00 106.55 09-MAR-07:00
April 1354.32 01-APR-00:10 815.72 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 43.62 28-APR-15:00 70.69 11-APR-06:00
May 1354.32 01-MAY-00:10 815.72 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 47.61 28-MAY-16:00 13.38 07-MAY-01:00
June 1354.32 01-JUN-00:10 815.72 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 50.28 14-JUN-14:00 14.45 07-JUN-02:00
July 1354.32 01-JUL-00:10 815.72 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 55.82 22-JUL-16:00 8.26 11-JUL-20:00
August 1354.32 01-AUG-00:10 815.72 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 54.99 30-AUG-16:00 17.54 25-AUG-24:00
September 1354.32 01-SEP-00:10 815.72 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 55.93 09-SEP-17:00 22.20 07-SEP-20:00
October 1354.32 01-OCT-23:10 815.72 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 45.03 05-OCT-15:00 63.63 28-OCT-06:10
November 1354.32 01-NOV-00:10 815.72 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 31.35 01-NOV-14:00 78.83 12-NOV-07:20
December 1354.32 01-DEC-00:10 815.72 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 30.60 13-DEC-15:00 108.70 21-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   815.72   793.93   0.00 0.00 0.00 0.00 18.86   8.26  
Maximum of Months 1354.32   815.72   793.93   0.00 0.00 0.00 0.00 55.93   127.99  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 1360.40 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 54.38 16-JAN-15:00 247.21 05-JAN-08:00
February 286.42 01-FEB-00:10 1360.40 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 61.40 02-FEB-13:00 293.85 05-FEB-08:00
March 286.42 01-MAR-00:10 1360.40 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 79.32 26-MAR-14:00 242.29 09-MAR-07:00
April 286.42 01-APR-00:10 1360.40 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 104.20 28-APR-15:00 158.54 11-APR-06:00
May 286.42 01-MAY-00:10 1360.40 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 109.84 28-MAY-16:00 30.27 07-MAY-01:00
June 286.42 01-JUN-00:10 1360.40 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 115.15 14-JUN-14:00 32.04 07-JUN-02:00
July 286.42 01-JUL-00:10 1360.40 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 128.32 22-JUL-16:00 19.53 11-JUL-20:00
August 286.42 01-AUG-00:10 1360.40 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 130.23 30-AUG-16:00 40.07 25-AUG-24:00
September 286.42 01-SEP-00:10 1360.40 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 131.84 09-SEP-17:00 52.48 07-SEP-20:00
October 286.42 01-OCT-23:10 1360.40 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 107.30 05-OCT-15:00 145.45 28-OCT-06:10
November 286.42 01-NOV-00:10 1360.40 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 74.69 01-NOV-14:00 178.61 12-NOV-07:20
December 286.42 01-DEC-00:10 1360.40 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 74.84 13-DEC-15:00 246.71 21-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   1360.40   839.45   0.00 0.00 0.00 0.00 54.38   19.53  
Maximum of Months 286.42   1360.40   839.45   0.00 0.00 0.00 0.00 131.84   293.85  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 227.72 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 30.85 16-JAN-15:00 141.95 05-JAN-08:00
February 220.32 01-FEB-00:10 227.72 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 35.44 02-FEB-13:00 169.53 05-FEB-08:00
March 220.32 01-MAR-00:10 227.72 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 45.42 26-MAR-14:00 138.15 09-MAR-06:30
April 220.32 01-APR-00:10 227.72 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 60.24 28-APR-15:00 89.98 11-APR-06:00
May 220.32 01-MAY-00:10 227.72 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 62.98 28-MAY-16:00 16.31 07-MAY-01:00
June 220.32 01-JUN-00:10 227.72 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 66.48 14-JUN-14:00 18.26 07-JUN-02:00
July 220.32 01-JUL-00:10 227.72 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 73.57 22-JUL-16:00 10.74 11-JUL-20:00
August 220.32 01-AUG-00:10 227.72 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 74.80 30-AUG-16:00 22.58 25-AUG-24:00
September 220.32 01-SEP-00:10 227.72 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 75.70 09-SEP-17:00 29.17 07-SEP-20:00
October 220.32 01-OCT-23:10 227.72 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 61.69 05-OCT-15:00 82.67 28-OCT-06:10
November 220.32 01-NOV-00:10 227.72 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 43.17 01-NOV-14:00 101.49 12-NOV-07:20
December 220.32 01-DEC-00:10 227.72 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 43.28 13-DEC-15:00 142.34 21-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   227.72   242.16   0.00 0.00 0.00 0.00 30.85   10.74  
Maximum of Months 220.32   227.72   242.16   0.00 0.00 0.00 0.00 75.70   169.53  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 357.21 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 68.93 16-JAN-15:00 383.89 05-JAN-08:00
February 907.20 01-FEB-00:10 357.21 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 85.33 02-FEB-13:00 449.71 05-FEB-08:00
March 907.20 01-MAR-00:10 357.21 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 109.76 26-MAR-14:00 366.99 09-MAR-07:00
April 907.20 01-APR-00:10 357.21 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 152.28 28-APR-15:20 245.14 11-APR-05:49
May 907.20 01-MAY-00:10 357.21 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 178.31 28-MAY-16:00 43.01 07-MAY-01:00
June 907.20 01-JUN-00:10 357.21 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 172.85 11-JUN-17:00 42.80 07-JUN-06:00
July 907.20 01-JUL-00:10 357.21 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 201.33 22-JUL-16:00 26.67 11-JUL-20:00
August 907.20 01-AUG-00:10 357.21 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 201.40 30-AUG-16:00 53.65 16-AUG-21:00
September 907.20 01-SEP-00:10 357.21 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 206.67 09-SEP-17:00 71.66 07-SEP-20:00
October 907.20 01-OCT-23:10 357.21 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 160.91 05-OCT-15:00 227.55 28-OCT-07:57
November 907.20 01-NOV-00:10 357.21 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 106.81 02-NOV-13:00 293.87 15-NOV-06:45
December 907.20 01-DEC-00:10 357.21 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 103.31 13-DEC-15:00 381.56 21-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   357.21   4572.80   39726.58   0.00 0.00 0.00 68.93   26.67  
Maximum of Months 907.20   357.21   4572.80   39726.58   0.00 0.00 0.00 206.67   449.71  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 1761.91 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 104.37 02-JAN-15:00 637.91 05-JAN-06:00
February 15368.40 01-FEB-00:10 1761.91 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 109.89 02-FEB-13:00 721.94 05-FEB-08:00
March 15368.40 01-MAR-00:10 1761.91 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 162.79 30-MAR-13:00 611.29 09-MAR-06:00
April 15368.40 01-APR-00:10 1761.91 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 235.09 28-APR-15:00 397.16 11-APR-06:00
May 15368.40 01-MAY-00:10 1761.91 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 267.42 28-MAY-16:00 75.65 07-MAY-01:00
June 15368.40 01-JUN-00:10 1761.91 01-JUN-19:10 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 286.24 14-JUN-14:00 89.25 07-JUN-02:00
July 15368.40 01-JUL-00:10 1761.91 03-JUL-19:19 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 312.94 22-JUL-16:00 47.21 11-JUL-20:00
August 15368.40 01-AUG-00:10 1761.91 01-AUG-19:10 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 307.33 30-AUG-16:00 100.36 25-AUG-24:00
September 15368.40 01-SEP-00:10 1761.91 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 310.07 09-SEP-17:00 124.57 07-SEP-20:00
October 15368.40 01-OCT-23:10 1761.91 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 251.78 05-OCT-15:00 368.60 28-OCT-05:00
November 15368.40 01-NOV-00:10 1761.91 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 164.78 01-NOV-14:00 457.45 12-NOV-07:34
December 15368.40 01-DEC-00:10 1761.91 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 153.87 13-DEC-15:00 632.05 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   1761.91   965.27   0.00 0.00 0.00 0.00 104.37   47.21  
Maximum of Months 15368.40   1761.91   965.27   0.00 0.00 0.00 0.00 312.94   721.94  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 10265.18 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 294.33 02-JAN-15:00 1877.39 05-JAN-06:00
February 45622.98 01-FEB-00:10 10265.18 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 357.30 02-FEB-13:00 2161.29 05-FEB-08:00
March 45622.98 01-MAR-00:10 10265.18 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 490.37 26-MAR-14:00 1810.39 09-MAR-06:00
April 45622.98 01-APR-00:10 10265.18 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 709.55 28-APR-15:00 1200.29 11-APR-06:00
May 45622.98 01-MAY-00:10 10265.18 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 776.46 28-MAY-16:00 218.93 07-MAY-01:00
June 45622.98 01-JUN-00:10 10265.18 01-JUN-19:10 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 829.31 14-JUN-14:00 255.20 07-JUN-02:00
July 45622.98 01-JUL-00:10 10265.18 03-JUL-19:10 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 913.13 22-JUL-16:00 135.06 11-JUL-20:00
August 45622.98 01-AUG-00:10 10265.18 01-AUG-19:10 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 887.49 30-AUG-16:00 286.93 25-AUG-24:00
September 45622.98 01-SEP-00:10 10265.18 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 901.51 09-SEP-17:00 363.23 07-SEP-20:00
October 45622.98 01-OCT-23:10 10265.18 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 719.35 05-OCT-15:00 1087.97 28-OCT-05:00
November 45622.98 01-NOV-00:10 10265.18 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 495.33 01-NOV-14:00 1331.71 12-NOV-07:33
December 45622.98 01-DEC-00:10 10265.18 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 467.54 13-DEC-15:00 1856.45 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   10265.18   10029.21   0.00 0.00 0.00 0.00 294.33   135.06  
Maximum of Months 45622.98   10265.18   10029.21   0.00 0.00 0.00 0.00 913.13   2161.29  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 32.88 02-JAN-16:10 157.67 05-JAN-08:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 40.90 25-FEB-17:00 188.13 05-FEB-08:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 48.16 27-MAR-15:08 149.97 09-MAR-07:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 79.30 28-APR-15:10 93.21 11-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 84.46 28-MAY-16:00 3.96 31-MAY-13:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 84.30 10-JUN-16:00 3.96 01-JUN-13:00
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 98.52 22-JUL-16:00 3.98 12-JUL-15:00
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 99.35 30-AUG-16:00 12.27 16-AUG-18:00
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 100.08 09-SEP-17:00 29.05 07-SEP-18:00
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 82.62 05-OCT-15:10 83.41 28-OCT-08:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 54.76 02-NOV-15:10 102.98 12-NOV-08:10
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 50.81 13-DEC-16:10 158.11 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 32.88   3.96  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 100.08   188.13  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 32.88 02-JAN-16:40 157.66 05-JAN-06:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 40.89 25-FEB-17:00 188.11 05-FEB-08:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 48.15 27-MAR-15:08 149.96 09-MAR-07:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 79.29 28-APR-15:10 93.20 11-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 84.46 28-MAY-16:00 3.96 31-MAY-13:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 84.29 10-JUN-16:00 3.96 01-JUN-13:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 98.51 22-JUL-16:00 3.98 12-JUL-15:00
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 99.34 30-AUG-16:00 12.27 16-AUG-18:00
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 100.08 09-SEP-17:00 28.59 07-SEP-18:00
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 82.80 05-OCT-15:10 80.92 28-OCT-08:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 54.76 02-NOV-15:10 101.33 12-NOV-08:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 50.81 13-DEC-16:08 158.10 21-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 32.88   3.96  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 100.08   188.11  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 76.99 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 6.84 02-JAN-15:00 46.11 05-JAN-08:00
February 0.00 01-FEB-00:10 76.99 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 9.22 02-FEB-13:00 51.08 05-FEB-08:00
March 0.00 01-MAR-00:10 76.99 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 12.40 26-MAR-14:00 43.16 09-MAR-07:20
April 0.00 01-APR-00:10 76.99 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 18.34 28-APR-15:00 28.59 11-APR-06:00
May 0.00 01-MAY-00:10 76.99 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 19.49 07-MAY-14:00 4.41 07-MAY-01:00
June 0.00 01-JUN-00:10 76.99 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 21.39 14-JUN-14:00 4.87 07-JUN-02:00
July 0.00 01-JUL-00:10 76.99 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 23.40 22-JUL-16:00 2.27 11-JUL-20:00
August 0.00 01-AUG-00:10 76.99 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 23.65 30-AUG-16:00 6.15 25-AUG-24:00
September 0.00 01-SEP-00:10 76.99 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 23.85 09-SEP-17:00 8.10 07-SEP-18:00
October 0.00 01-OCT-00:10 76.99 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 19.59 05-OCT-15:00 27.00 28-OCT-07:53
November 0.00 01-NOV-00:10 76.99 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 12.41 01-NOV-14:00 32.78 12-NOV-08:00
December 0.00 01-DEC-00:10 76.99 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 12.44 13-DEC-15:00 43.43 21-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   76.99   232.19   0.00 0.00 0.00 0.00 6.84   2.27  
Maximum of Months 0.00   76.99   232.19   0.00 0.00 0.00 0.00 23.85   51.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 77.01 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 9.72 16-JAN-15:00 44.00 05-JAN-08:00
February 180.00 01-FEB-00:10 77.01 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 11.97 02-FEB-13:00 52.50 05-FEB-08:00
March 180.00 01-MAR-00:10 77.01 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 13.58 26-MAR-14:00 41.85 09-MAR-07:00
April 180.00 01-APR-00:10 77.01 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 22.13 28-APR-15:10 26.01 11-APR-06:00
May 180.00 01-MAY-00:10 77.01 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 23.57 28-MAY-16:00 0.11 07-MAY-01:00
June 180.00 01-JUN-00:10 77.01 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 23.53 10-JUN-16:00 1.07 07-JUN-02:00
July 180.00 01-JUL-00:10 77.01 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 27.49 22-JUL-16:00 0.39 12-JUL-15:00
August 180.00 01-AUG-00:10 77.01 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 27.73 30-AUG-16:00 2.64 16-AUG-18:00
September 180.00 01-SEP-00:10 77.01 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 27.93 09-SEP-17:00 6.52 07-SEP-18:00
October 180.00 01-OCT-00:10 77.01 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 23.11 05-OCT-15:10 24.34 28-OCT-08:00
November 180.00 01-NOV-00:10 77.01 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 15.28 02-NOV-15:08 28.71 12-NOV-08:10
December 180.00 01-DEC-00:10 77.01 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 14.32 13-DEC-15:00 44.13 21-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 9.72   0.11  
Maximum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 27.93   52.50  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 32.88 02-JAN-16:40 157.67 05-JAN-08:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 40.90 25-FEB-17:00 188.13 05-FEB-08:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 48.16 27-MAR-15:08 149.97 09-MAR-07:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 79.30 28-APR-15:10 93.21 11-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 84.46 28-MAY-16:00 3.96 31-MAY-13:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 84.29 10-JUN-16:00 3.96 01-JUN-13:00
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 98.52 22-JUL-16:00 3.98 13-JUL-11:00
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 99.35 30-AUG-16:00 12.27 16-AUG-18:00
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 100.08 09-SEP-17:00 29.05 07-SEP-18:00
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 82.81 05-OCT-15:10 90.29 28-OCT-08:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 54.76 02-NOV-15:10 112.20 12-NOV-08:20
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 50.81 13-DEC-16:10 158.11 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 32.88   3.96  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 100.08   188.13  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 32.88 02-JAN-16:40 157.66 05-JAN-08:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 40.90 25-FEB-17:00 188.11 05-FEB-07:50
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 48.15 27-MAR-15:08 149.96 09-MAR-07:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 79.29 28-APR-15:10 93.20 11-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 84.46 28-MAY-16:00 3.96 31-MAY-13:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 84.29 10-JUN-16:00 3.96 01-JUN-13:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 98.51 22-JUL-16:00 3.98 13-JUL-11:00
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 99.34 30-AUG-16:00 12.27 16-AUG-18:00
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 100.07 09-SEP-17:00 29.04 07-SEP-18:00
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 82.80 05-OCT-15:10 87.90 28-OCT-08:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 54.76 02-NOV-15:10 109.25 12-NOV-08:40
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 50.81 13-DEC-16:10 158.10 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 32.88   3.96  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 100.07   188.11  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 2240.78 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 37.36 16-JAN-15:00 196.72 05-JAN-06:00
February 2263.36 01-FEB-00:10 2240.78 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 45.21 02-FEB-13:00 228.55 05-FEB-08:00
March 2263.36 01-MAR-00:10 2240.78 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 58.09 26-MAR-14:00 190.74 09-MAR-06:00
April 2263.36 01-APR-00:10 2240.78 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 77.91 28-APR-15:00 123.36 11-APR-06:00
May 2263.36 01-MAY-00:10 2240.78 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 82.30 28-MAY-16:00 23.03 07-MAY-01:00
June 2263.36 01-JUN-00:10 2240.78 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 88.51 14-JUN-14:00 26.21 07-JUN-02:00
July 2263.36 01-JUL-00:10 2240.78 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 97.23 22-JUL-16:00 15.38 11-JUL-20:00
August 2263.36 01-AUG-00:10 2240.78 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 97.62 30-AUG-16:00 31.75 25-AUG-24:00
September 2263.36 01-SEP-00:10 2240.78 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 99.42 09-SEP-17:00 39.77 07-SEP-20:00
October 2263.36 01-OCT-23:10 2240.78 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 79.59 05-OCT-15:00 114.01 28-OCT-06:10
November 2263.36 01-NOV-00:10 2240.78 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 55.88 01-NOV-14:00 139.55 12-NOV-07:34
December 2263.36 01-DEC-00:10 2240.78 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 54.97 13-DEC-15:00 193.46 21-DEC-05:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   2240.78   0.00 0.00 0.00 0.00 0.00 37.36   15.38  
Maximum of Months 2263.36   2240.78   0.00 0.00 0.00 0.00 0.00 99.42   228.55  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 32.48 02-JAN-16:10 158.15 05-JAN-08:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 40.50 25-FEB-17:00 188.62 05-FEB-08:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 47.76 27-MAR-15:08 150.44 09-MAR-07:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 78.91 28-APR-15:10 93.66 11-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 84.08 28-MAY-16:00 4.37 31-MAY-13:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 83.92 10-JUN-16:00 4.37 01-JUN-13:00
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 98.14 22-JUL-16:00 4.39 12-JUL-15:00
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 98.97 30-AUG-16:00 12.69 16-AUG-18:00
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 99.71 09-SEP-17:00 28.98 07-SEP-18:00
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 81.36 05-OCT-15:10 81.06 28-OCT-07:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 54.37 02-NOV-15:10 101.79 12-NOV-08:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 50.42 13-DEC-16:10 158.59 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 32.48   4.37  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 99.71   188.62  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 32.48 02-JAN-16:08 158.13 05-JAN-06:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 40.50 25-FEB-17:00 188.61 05-FEB-08:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 47.76 27-MAR-15:08 150.44 09-MAR-07:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 78.91 28-APR-15:10 93.65 11-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 84.08 28-MAY-16:00 4.37 31-MAY-13:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 83.91 10-JUN-16:00 4.36 01-JUN-13:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 98.14 22-JUL-16:00 4.39 12-JUL-15:00
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 98.97 30-AUG-16:00 12.69 16-AUG-18:00
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 99.70 09-SEP-17:00 28.19 07-SEP-18:00
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 82.41 05-OCT-15:10 81.05 28-OCT-07:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 54.37 02-NOV-15:10 101.78 12-NOV-08:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 50.41 13-DEC-16:10 158.58 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 32.48   4.36  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 99.70   188.61  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 77.01 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 16.62 02-JAN-16:08 80.91 05-JAN-06:00
February 180.00 01-FEB-00:10 77.01 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 20.72 25-FEB-17:00 96.51 05-FEB-07:20
March 180.00 01-MAR-00:10 77.01 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 24.44 27-MAR-15:10 76.97 09-MAR-07:00
April 180.00 01-APR-00:10 77.01 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 40.38 28-APR-15:10 47.92 11-APR-06:00
May 180.00 01-MAY-00:10 77.01 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 43.02 28-MAY-16:00 2.24 31-MAY-13:00
June 180.00 01-JUN-00:10 77.01 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 42.94 10-JUN-16:00 2.23 01-JUN-13:00
July 180.00 01-JUL-00:10 77.01 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 50.21 22-JUL-16:00 2.25 12-JUL-15:00
August 180.00 01-AUG-00:10 77.01 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 50.64 30-AUG-16:00 6.49 16-AUG-18:00
September 180.00 01-SEP-00:10 77.01 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 51.02 09-SEP-17:00 14.39 07-SEP-18:00
October 180.00 01-OCT-00:10 77.01 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 40.10 05-OCT-15:10 44.44 28-OCT-08:00
November 180.00 01-NOV-00:10 77.01 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 25.89 01-NOV-15:10 56.08 12-NOV-09:00
December 180.00 01-DEC-00:10 77.01 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 25.76 13-DEC-16:10 81.14 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 16.62   2.23  
Maximum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 51.02   96.51  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3094.06 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 55.10 16-JAN-15:00 437.27 05-JAN-06:00
February 26988.77 01-FEB-00:10 3094.06 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 78.97 02-FEB-13:00 510.76 05-FEB-08:00
March 26988.77 01-MAR-00:10 3094.06 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 96.65 26-MAR-14:00 420.03 09-MAR-07:00
April 26988.77 01-APR-00:10 3094.06 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 148.81 28-APR-15:00 279.83 11-APR-06:00
May 26988.77 01-MAY-00:10 3094.06 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 158.84 07-MAY-14:00 50.82 07-MAY-01:00
June 26988.77 01-JUN-00:10 3094.06 01-JUN-19:19 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 175.53 14-JUN-14:00 58.94 07-JUN-02:00
July 26988.77 01-JUL-00:10 3094.06 03-JUL-19:19 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 193.17 22-JUL-16:00 31.98 11-JUL-20:00
August 26988.77 01-AUG-00:10 3094.06 01-AUG-19:19 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 195.46 30-AUG-16:00 66.07 25-AUG-24:00
September 26988.77 01-SEP-00:10 3094.06 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 197.21 09-SEP-17:00 83.22 07-SEP-18:00
October 26988.77 01-OCT-23:10 3094.06 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 159.82 05-OCT-15:00 257.80 28-OCT-06:05
November 26988.77 01-NOV-00:10 3094.06 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 98.77 02-NOV-13:00 308.23 12-NOV-07:05
December 26988.77 01-DEC-00:10 3094.06 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 99.68 13-DEC-15:00 437.25 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 55.10   31.98  
Maximum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 197.21   510.76  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3094.06 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 51.28 02-JAN-15:00 438.64 05-JAN-06:00
February 26988.77 01-FEB-00:10 3094.06 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 75.25 02-FEB-13:00 514.53 05-FEB-08:00
March 26988.77 01-MAR-00:10 3094.06 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 96.65 26-MAR-14:00 420.04 09-MAR-07:00
April 26988.77 01-APR-00:10 3094.06 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 148.81 28-APR-15:00 279.84 11-APR-06:00
May 26988.77 01-MAY-00:10 3094.06 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 158.84 07-MAY-14:00 50.82 07-MAY-01:00
June 26988.77 01-JUN-00:10 3094.06 01-JUN-19:19 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 175.53 14-JUN-14:00 58.94 07-JUN-02:00
July 26988.77 01-JUL-00:10 3094.06 03-JUL-19:19 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 193.17 22-JUL-16:00 31.98 11-JUL-20:00
August 26988.77 01-AUG-00:10 3094.06 01-AUG-19:19 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 195.45 30-AUG-16:00 66.07 25-AUG-24:00
September 26988.77 01-SEP-00:10 3094.06 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 197.21 09-SEP-17:00 83.23 07-SEP-18:00
October 26988.77 01-OCT-23:10 3094.06 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 159.82 05-OCT-15:00 258.76 28-OCT-06:05
November 26988.77 01-NOV-00:10 3094.06 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 96.73 01-NOV-14:00 308.71 12-NOV-07:05
December 26988.77 01-DEC-00:10 3094.06 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 97.00 13-DEC-15:00 439.87 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 51.28   31.98  
Maximum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 197.21   514.53  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1089.83 02-JAN-20:10 14912.86 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 42.95 16-JAN-15:00 392.60 05-JAN-08:00
February 2401.70 01-FEB-00:10 1089.83 01-FEB-20:10 14912.86 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 61.75 02-FEB-13:00 460.62 05-FEB-07:10
March 2401.70 01-MAR-00:10 1089.83 01-MAR-20:10 14912.86 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 86.63 26-MAR-14:00 375.94 09-MAR-07:00
April 2401.70 01-APR-00:10 1089.83 03-APR-19:10 14912.86 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 133.35 28-APR-15:00 255.84 11-APR-05:42
May 2401.70 01-MAY-00:10 1089.83 01-MAY-19:10 14912.86 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 142.31 07-MAY-14:00 43.22 07-MAY-01:00
June 2401.70 01-JUN-00:10 1089.83 01-JUN-19:10 14912.86 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 157.25 14-JUN-14:00 45.20 07-JUN-05:05
July 2401.70 01-JUL-00:10 1089.83 03-JUL-19:10 14912.86 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 173.12 22-JUL-16:00 28.53 11-JUL-20:00
August 2401.70 01-AUG-00:10 1089.83 01-AUG-19:10 14912.86 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 175.15 30-AUG-16:00 59.17 25-AUG-24:00
September 2401.70 01-SEP-00:10 1089.83 01-SEP-19:10 14912.86 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 176.72 09-SEP-17:00 74.39 07-SEP-20:00
October 2401.70 01-OCT-23:10 1089.83 02-OCT-19:10 14912.86 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 143.20 05-OCT-15:00 248.48 28-OCT-06:05
November 2401.70 01-NOV-00:10 1089.83 01-NOV-19:10 14912.86 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 86.71 02-NOV-13:00 298.11 15-NOV-06:45
December 2401.70 01-DEC-00:10 1089.83 01-DEC-20:10 14912.86 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 86.94 13-DEC-15:00 393.71 21-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1089.83   14912.86   22492.83   0.00 0.00 0.00 42.95   28.53  
Maximum of Months 2401.70   1089.83   14912.86   22492.83   0.00 0.00 0.00 176.72   460.62  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 2371.52 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 56.13 16-JAN-15:00 336.60 05-JAN-08:00
February 2395.44 01-FEB-00:10 2371.52 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 73.38 02-FEB-13:00 401.77 05-FEB-08:00
March 2395.44 01-MAR-00:10 2371.52 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 92.17 26-MAR-14:00 320.37 09-MAR-06:00
April 2395.44 01-APR-00:10 2371.52 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 130.36 28-APR-15:00 207.85 11-APR-06:00
May 2395.44 01-MAY-00:10 2371.52 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 139.16 07-MAY-14:00 38.76 07-MAY-01:00
June 2395.44 01-JUN-00:10 2371.52 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 153.78 14-JUN-14:00 43.68 07-JUN-02:00
July 2395.44 01-JUL-00:10 2371.52 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 169.23 22-JUL-16:00 27.08 11-JUL-20:00
August 2395.44 01-AUG-00:10 2371.52 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 171.21 30-AUG-16:00 54.88 25-AUG-24:00
September 2395.44 01-SEP-00:10 2371.52 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 172.75 09-SEP-17:00 69.14 07-SEP-20:00
October 2395.44 01-OCT-23:10 2371.52 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 140.01 05-OCT-15:00 190.28 28-OCT-06:10
November 2395.44 01-NOV-00:10 2371.52 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 92.77 01-NOV-14:00 237.72 12-NOV-07:34
December 2395.44 01-DEC-00:10 2371.52 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 90.36 13-DEC-15:00 337.53 21-DEC-07:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   2371.52   0.00 0.00 0.00 0.00 0.00 56.13   27.08  
Maximum of Months 2395.44   2371.52   0.00 0.00 0.00 0.00 0.00 172.75   401.77  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 39064.24 06-JAN-22:40 23003.78 18914.03 14904.55 0.00 0.00 0.00 0.00 0.00 0.00
February 25658.23 06-FEB-08:58 51119.52 63045.57 53230.53 0.00 0.00 0.00 0.00 0.00 0.00
March 26363.70 08-MAR-23:15 23003.78 9457.02 8516.89 0.00 0.00 0.00 0.00 0.00 0.00
April 18101.74 11-APR-05:50 89459.16 63045.57 53230.53 0.00 0.00 0.00 0.00 0.00 0.00
May 17034.72 28-MAY-10:33 11501.89 14185.53 12775.33 0.00 0.00 0.00 0.00 0.00 0.00
June 17446.27 28-JUN-18:10 53675.50 75655.77 57488.97 0.00 0.00 0.00 0.00 0.00 0.00
July 18621.77 16-JUL-10:33 11501.89 14185.53 12775.33 0.00 0.00 0.00 0.00 0.00 0.00
August 23275.10 16-AUG-21:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
September 23948.76 13-SEP-21:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
October 29201.00 28-OCT-07:59 44729.58 44131.90 37261.37 0.00 0.00 0.00 0.00 0.00 0.00
November 39615.74 15-NOV-06:54 44729.58 31522.79 26615.27 0.00 0.00 0.00 0.00 0.00 0.00
December 38677.73 25-DEC-21:59 102239.04 94570.17 74522.74 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17034.72   10223.90 9457.02 8516.89 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 39615.74   102239.04 94570.17 74522.74 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3906.38 01-JAN-13:00 389.84 234.80 288.68 0.00 0.00 0.00 0.00 11.74 0.00
February 3064.04 27-FEB-14:00 259.90 195.67 252.59 0.00 0.00 0.00 0.00 17.53 0.00
March 2742.76 08-MAR-23:15 2339.06 469.61 577.35 0.00 0.00 0.00 0.00 0.00 193.84
April 2349.83 22-APR-13:40 389.84 195.67 252.59 0.00 0.00 0.00 0.00 71.02 0.00
May 2487.22 04-MAY-18:20 1819.27 1252.29 1299.04 0.00 0.00 0.00 0.00 58.65 0.00
June 2623.38 28-JUN-18:13 2728.91 1878.44 1948.56 0.00 0.00 0.00 0.00 89.91 0.00
July 2702.07 19-JUL-18:03 5457.82 3756.88 3897.11 0.00 0.00 0.00 0.00 68.25 0.00
August 2831.36 31-AUG-13:30 259.90 195.67 252.59 0.00 0.00 0.00 0.00 90.94 0.00
September 3619.26 10-SEP-12:00 389.84 234.80 288.68 0.00 0.00 0.00 0.00 127.24 0.00
October 3798.83 07-OCT-12:40 389.84 195.67 252.59 0.00 0.00 0.00 0.00 95.65 0.00
November 3751.78 06-NOV-13:30 259.90 195.67 252.59 0.00 0.00 0.00 0.00 43.72 0.00
December 4038.21 16-DEC-13:30 389.84 195.67 252.59 0.00 0.00 0.00 0.00 40.78 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2349.83   259.90 195.67 252.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4038.21   5457.82 3756.88 3897.11 0.00 0.00 0.00 0.00 127.24 193.84



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2255.88 04-JAN-20:28 10533.60 8157.15 7939.31 0.00 0.00 0.00 0.00 0.00 93.08
February 2132.00 13-FEB-23:30 4062.96 815.72 1002.86 0.00 0.00 0.00 0.00 0.00 77.08
March 2363.70 08-MAR-23:15 2708.64 543.81 668.57 0.00 0.00 0.00 0.00 0.00 84.89
April 2074.22 21-APR-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 6.81 0.00
May 2256.55 04-MAY-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 1.81 0.00
June 2326.05 13-JUN-20:10 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 26.86 0.00
July 2361.16 07-JUL-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 24.19 0.00
August 2374.63 30-AUG-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 23.68 0.00
September 2255.94 10-SEP-20:00 902.88 725.08 752.15 0.00 0.00 0.00 0.00 20.18 0.00
October 2353.52 05-OCT-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 13.51 0.00
November 2315.31 12-NOV-07:37 9480.24 3262.86 3760.73 0.00 0.00 0.00 0.00 0.00 78.02
December 2183.89 06-DEC-01:02 6771.60 679.76 1044.65 0.00 0.00 0.00 0.00 0.00 70.10
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2074.22   902.88 543.81 668.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2374.63   10533.60 8157.15 7939.31 0.00 0.00 0.00 0.00 26.86 93.08



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2058.86 04-JAN-20:28 2227.68 13603.96 8394.47 0.00 0.00 0.00 0.00 0.00 207.10
February 1914.77 13-FEB-23:30 859.25 1360.40 1060.35 0.00 0.00 0.00 0.00 0.00 168.00
March 2228.77 08-MAR-23:15 572.83 906.93 706.90 0.00 0.00 0.00 0.00 0.00 192.26
April 1712.64 28-APR-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 0.00 7.59
May 2191.04 30-MAY-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 17.01 0.00
June 2499.90 28-JUN-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 57.03 0.00
July 2564.04 19-JUL-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 51.94 0.00
August 2450.28 21-AUG-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 53.89 0.00
September 2425.52 10-SEP-20:00 190.94 1209.24 795.27 0.00 0.00 0.00 0.00 47.68 0.00
October 2327.19 06-OCT-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 31.92 0.00
November 2203.97 12-NOV-07:37 2004.91 5441.59 3976.33 0.00 0.00 0.00 0.00 0.00 177.72
December 1993.13 06-DEC-01:02 1432.08 1133.66 1104.54 0.00 0.00 0.00 0.00 0.00 153.51
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1712.64   190.94 906.93 706.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2564.04   2227.68 13603.96 8394.47 0.00 0.00 0.00 0.00 57.03 207.10



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 951.81 04-JAN-20:28 1713.60 2277.17 2421.57 0.00 0.00 0.00 0.00 0.00 116.12
February 900.61 13-FEB-23:30 660.96 227.72 305.88 0.00 0.00 0.00 0.00 0.00 95.16
March 1045.08 08-MAR-23:15 440.64 151.81 203.92 0.00 0.00 0.00 0.00 0.00 108.55
April 784.81 23-APR-10:33 220.32 227.72 305.88 0.00 0.00 0.00 0.00 21.08 0.00
May 836.11 29-MAY-10:33 220.32 227.72 305.88 0.00 0.00 0.00 0.00 36.90 0.00
June 970.82 28-JUN-20:40 195.84 202.41 229.41 0.00 0.00 0.00 0.00 28.52 0.00
July 1018.05 07-JUL-21:00 195.84 202.41 229.41 0.00 0.00 0.00 0.00 32.97 0.00
August 963.30 24-AUG-20:00 171.36 227.72 242.16 0.00 0.00 0.00 0.00 48.38 0.00
September 969.38 10-SEP-20:00 146.88 202.41 229.41 0.00 0.00 0.00 0.00 27.51 0.00
October 885.04 06-OCT-21:00 195.84 202.41 229.41 0.00 0.00 0.00 0.00 18.40 0.00
November 1043.06 12-NOV-07:37 1542.24 910.87 1147.06 0.00 0.00 0.00 0.00 0.00 101.03
December 948.59 06-DEC-01:02 1101.60 189.78 318.63 0.00 0.00 0.00 0.00 0.00 87.69
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 784.81   146.88 151.81 203.92 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1045.08   1713.60 2277.17 2421.57 0.00 0.00 0.00 0.00 48.38 116.12



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 51493.28 06-JAN-21:47 4838.40 1905.14 25992.76 225814.22 0.00 0.00 0.00 0.00 300.83
February 48728.76 17-FEB-19:30 4233.60 1905.14 25992.76 225814.22 0.00 0.00 0.00 0.00 303.24
March 48979.09 09-MAR-21:57 3225.60 1270.09 17328.51 150542.82 0.00 0.00 0.00 0.00 295.90
April 38607.34 21-APR-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 3.00
May 39036.39 03-MAY-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 62.13 0.00
June 39183.14 13-JUN-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 94.62 0.00
July 39225.39 07-JUL-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 78.03 0.00
August 39072.55 02-AUG-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 56.47 0.00
September 38824.07 01-SEP-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 1.52
October 38894.08 05-OCT-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 43.56 0.00
November 38498.34 02-NOV-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 14.61 0.00
December 48310.18 29-DEC-20:06 5644.80 2857.71 36582.41 317812.61 0.00 0.00 0.00 0.00 242.63
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 38498.34   705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 51493.28   5644.80 2857.71 36582.41 317812.61 0.00 0.00 0.00 94.62 303.24



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 13996.24 01-JAN-13:00 5122.80 358.25 406.43 0.00 0.00 0.00 0.00 25.99 0.00
February 12158.46 13-FEB-23:30 46105.20 1761.91 1219.29 0.00 0.00 0.00 0.00 0.00 442.72
March 15153.08 08-MAR-23:05 30736.80 1174.60 812.86 0.00 0.00 0.00 0.00 0.00 462.61
April 10816.15 21-APR-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 36.92 0.00
May 11582.03 03-MAY-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 105.72 0.00
June 11667.57 28-JUN-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 108.53 0.00
July 12062.52 07-JUL-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 134.00 0.00
August 12338.30 24-AUG-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 143.03 0.00
September 12104.71 10-SEP-12:00 5122.80 358.25 406.43 0.00 0.00 0.00 0.00 281.29 0.00
October 13204.28 05-OCT-15:03 51228.00 1791.27 2133.76 0.00 0.00 0.00 0.00 243.63 0.00
November 13584.58 11-NOV-11:00 8538.00 358.25 406.43 0.00 0.00 0.00 0.00 54.38 0.00
December 16143.57 18-DEC-00:13 92210.40 2349.21 1828.94 0.00 0.00 0.00 0.00 0.00 440.96
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 10816.15   5122.80 358.25 406.43 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16143.57   92210.40 2349.21 2133.76 0.00 0.00 0.00 0.00 281.29 462.61



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 61447.11 25-JAN-22:58 456229.80 68434.56 73899.43 0.00 0.00 0.00 0.00 0.00 1267.50
February 59474.74 16-FEB-22:47 456229.80 68434.56 73899.43 0.00 0.00 0.00 0.00 0.00 1359.70
March 61221.40 08-MAR-22:33 456229.80 68434.56 73899.43 0.00 0.00 0.00 0.00 0.00 1381.63
April 38875.23 28-APR-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 13.79
May 41317.45 25-MAY-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 271.38 0.00
June 42677.92 28-JUN-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 309.92 0.00
July 43478.99 07-JUL-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 382.68 0.00
August 43656.72 24-AUG-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 408.51 0.00
September 42267.23 11-SEP-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 130.91 0.00
October 44128.75 05-OCT-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 233.31 0.00
November 46666.03 12-NOV-07:34 319360.86 38186.48 47506.78 0.00 0.00 0.00 0.00 0.00 1327.34
December 63905.50 18-DEC-00:35 182491.92 9124.61 12668.47 0.00 0.00 0.00 0.00 0.00 1375.36
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 38875.23   45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 63905.50   456229.80 68434.56 73899.43 0.00 0.00 0.00 0.00 408.51 1381.63



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2918.95 18-JAN-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 12.04 0.00
February 2955.21 23-FEB-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 8.23 0.00
March 2972.28 25-MAR-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 20.49 0.00
April 3011.09 21-APR-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 39.33 0.00
May 3036.02 25-MAY-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 66.46 0.00
June 3045.02 28-JUN-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 69.68 0.00
July 3032.16 06-JUL-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 67.96 0.00
August 3029.00 18-AUG-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 59.38 0.00
September 3029.17 17-SEP-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 59.15 0.00
October 3043.48 06-OCT-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 49.28 0.00
November 2998.80 03-NOV-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 32.86 0.00
December 3036.62 14-DEC-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 27.84 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2918.95   324.00 205.81 410.90 0.00 0.00 0.00 0.00 8.23 0.00
Maximum of Months 3045.02   831.60 654.18 774.39 0.00 0.00 0.00 0.00 69.68 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2806.95 01-JAN-16:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 14.84 0.00
February 2848.77 27-FEB-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 17.55 0.00
March 2868.76 24-MAR-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 23.83 0.00
April 2943.08 21-APR-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 39.32 0.00
May 2963.52 04-MAY-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 45.22 0.00
June 2972.80 05-JUN-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 58.97 0.00
July 2959.59 06-JUL-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 67.79 0.00
August 2965.21 01-AUG-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 72.80 0.00
September 2970.56 09-SEP-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 74.57 0.00
October 2963.97 07-OCT-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 60.75 0.00
November 2924.52 06-NOV-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 35.67 0.00
December 2896.67 15-DEC-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 35.82 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2806.95   324.00 205.78 410.85 0.00 0.00 0.00 0.00 14.84 0.00
Maximum of Months 2972.80   831.60 654.11 774.30 0.00 0.00 0.00 0.00 74.57 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 718.30 01-JAN-14:00 0.00 25.41 74.82 0.00 0.00 0.00 0.00 4.98 0.00
February 575.48 27-FEB-14:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 4.59 0.00
March 494.23 05-MAR-13:30 0.00 25.41 74.82 0.00 0.00 0.00 0.00 8.17 0.00
April 403.95 22-APR-13:40 0.00 25.41 74.82 0.00 0.00 0.00 0.00 12.67 0.00
May 405.59 04-MAY-16:20 0.00 21.56 131.58 0.00 0.00 0.00 0.00 16.77 0.00
June 405.63 28-JUN-17:15 0.00 206.33 526.30 0.00 0.00 0.00 0.00 17.10 0.00
July 436.08 19-JUL-17:12 0.00 206.33 526.30 0.00 0.00 0.00 0.00 16.41 0.00
August 472.09 31-AUG-13:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 15.89 0.00
September 600.64 10-SEP-13:30 0.00 25.41 74.82 0.00 0.00 0.00 0.00 22.12 0.00
October 640.02 13-OCT-13:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 17.05 0.00
November 688.74 06-NOV-14:00 0.00 21.56 67.08 0.00 0.00 0.00 0.00 9.28 0.00
December 725.76 10-DEC-14:30 0.00 25.41 74.82 0.00 0.00 0.00 0.00 7.77 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 403.95   0.00 21.56 67.08 0.00 0.00 0.00 0.00 4.59 0.00
Maximum of Months 725.76   0.00 206.33 526.30 0.00 0.00 0.00 0.00 22.12 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 881.16 02-JAN-16:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 8.19 0.00
February 881.90 25-FEB-16:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 9.24 0.00
March 927.79 26-MAR-18:02 702.00 462.06 758.70 0.00 0.00 0.00 0.00 2.08 0.00
April 968.12 22-APR-18:02 702.00 462.06 758.70 0.00 0.00 0.00 0.00 9.72 0.00
May 990.77 11-MAY-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 14.92 0.00
June 998.51 13-JUN-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 16.05 0.00
July 977.60 25-JUL-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 14.23 0.00
August 986.39 21-AUG-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 16.22 0.00
September 979.33 06-SEP-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 12.20 0.00
October 983.41 05-OCT-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 15.65 0.00
November 938.19 01-NOV-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 8.93 0.00
December 898.84 15-DEC-16:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 11.20 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 881.16   324.00 129.38 402.58 0.00 0.00 0.00 0.00 2.08 0.00
Maximum of Months 998.51   831.60 462.06 758.70 0.00 0.00 0.00 0.00 16.22 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2669.11 01-JAN-16:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 14.40 0.00
February 2637.20 27-FEB-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 17.65 0.00
March 2686.39 24-MAR-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 23.46 0.00
April 2743.32 17-APR-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 19.86 0.00
May 2753.90 19-MAY-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 57.27 0.00
June 2732.70 30-JUN-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 68.86 0.00
July 2755.42 18-JUL-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 79.71 0.00
August 2743.35 03-AUG-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 80.90 0.00
September 2742.22 03-SEP-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 65.13 0.00
October 2738.75 02-OCT-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 42.08 0.00
November 2711.78 06-NOV-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 35.56 0.00
December 2729.03 10-DEC-16:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 26.77 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2637.20   324.00 205.81 410.90 0.00 0.00 0.00 0.00 14.40 0.00
Maximum of Months 2755.42   583.20 242.57 458.31 0.00 0.00 0.00 0.00 80.90 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2459.40 01-JAN-16:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 15.16 0.00
February 2416.21 26-FEB-16:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 18.34 0.00
March 2602.39 24-MAR-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 23.94 0.00
April 2681.32 17-APR-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 19.88 0.00
May 2685.64 03-MAY-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 65.86 0.00
June 2672.38 20-JUN-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 61.16 0.00
July 2703.17 18-JUL-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 79.62 0.00
August 2672.83 03-AUG-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 80.84 0.00
September 2683.23 10-SEP-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 82.67 0.00
October 2641.16 05-OCT-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 72.03 0.00
November 2512.46 05-NOV-18:02 702.00 734.94 774.30 0.00 0.00 0.00 0.00 16.19 0.00
December 2462.24 09-DEC-16:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 28.66 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2416.21   324.00 205.78 410.85 0.00 0.00 0.00 0.00 15.16 0.00
Maximum of Months 2703.17   702.00 734.94 774.30 0.00 0.00 0.00 0.00 82.67 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3051.93 04-JAN-20:28 17603.88 22407.82 0.00 0.00 0.00 0.00 0.00 0.00 162.94
February 2842.94 13-FEB-23:30 6790.07 2240.78 0.00 0.00 0.00 0.00 0.00 0.00 132.72
March 3261.87 08-MAR-23:15 4526.71 1493.85 0.00 0.00 0.00 0.00 0.00 0.00 150.05
April 2403.19 29-APR-10:33 2263.36 1867.32 0.00 0.00 0.00 0.00 0.00 50.46 0.00
May 2561.52 10-MAY-21:00 2011.87 1991.81 0.00 0.00 0.00 0.00 0.00 34.78 0.00
June 2976.61 16-JUN-18:03 10562.33 11950.84 0.00 0.00 0.00 0.00 0.00 52.17 0.00
July 3003.47 07-JUL-20:10 2011.87 1991.81 0.00 0.00 0.00 0.00 0.00 43.62 0.00
August 3012.62 24-AUG-20:10 2011.87 1991.81 0.00 0.00 0.00 0.00 0.00 60.89 0.00
September 2978.05 10-SEP-20:10 2011.87 1493.85 0.00 0.00 0.00 0.00 0.00 35.93 0.00
October 2953.22 13-OCT-20:10 2011.87 1991.81 0.00 0.00 0.00 0.00 0.00 31.50 0.00
November 3233.53 12-NOV-07:37 15843.49 8963.13 0.00 0.00 0.00 0.00 0.00 0.00 139.09
December 2971.24 06-DEC-01:02 11316.78 1867.32 0.00 0.00 0.00 0.00 0.00 0.00 122.08
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2403.19   2011.87 1493.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3261.87   17603.88 22407.82 0.00 0.00 0.00 0.00 0.00 60.89 162.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3081.24 18-JAN-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 11.76 0.00
February 3079.81 01-FEB-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 10.14 0.00
March 3094.19 03-MAR-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.22
April 3148.80 25-APR-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 32.44 0.00
May 3153.70 29-MAY-18:02 702.00 735.03 774.39 0.00 0.00 0.00 0.00 43.10 0.00
June 3186.86 15-JUN-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 49.50 0.00
July 3179.31 16-JUL-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 59.22 0.00
August 3155.46 09-AUG-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 56.43 0.00
September 3177.17 10-SEP-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 81.44 0.00
October 3208.21 05-OCT-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 70.69 0.00
November 3127.21 03-NOV-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 32.46 0.00
December 3137.85 14-DEC-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 27.38 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3079.81   324.00 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3208.21   831.60 735.03 774.39 0.00 0.00 0.00 0.00 81.44 0.22



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2951.53 01-JAN-16:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 14.59 0.00
February 3018.39 27-FEB-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 17.25 0.00
March 3007.32 24-MAR-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 23.48 0.00
April 3079.44 23-APR-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 39.25 0.00
May 3099.07 06-MAY-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 58.47 0.00
June 3096.01 16-JUN-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 51.11 0.00
July 3109.62 18-JUL-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 63.56 0.00
August 3105.73 09-AUG-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 56.45 0.00
September 3110.20 10-SEP-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 81.77 0.00
October 3094.56 08-OCT-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 54.62 0.00
November 3015.70 06-NOV-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 35.21 0.00
December 3061.33 15-DEC-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 35.54 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2951.53   324.00 205.78 410.85 0.00 0.00 0.00 0.00 14.59 0.00
Maximum of Months 3110.20   831.60 654.11 774.30 0.00 0.00 0.00 0.00 81.77 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1650.24 01-JAN-16:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 6.13 0.00
February 1612.11 28-FEB-16:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 4.91 0.00
March 1625.61 03-MAR-16:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 0.00 0.67
April 1647.07 14-APR-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 24.08 0.00
May 1652.69 02-MAY-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 33.68 0.00
June 1635.70 13-JUN-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 36.71 0.00
July 1655.41 07-JUL-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 40.57 0.00
August 1657.07 03-AUG-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 41.08 0.00
September 1652.67 23-SEP-15:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 20.10 0.00
October 1671.58 15-OCT-15:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 24.03 0.00
November 1675.50 06-NOV-16:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 17.10 0.00
December 1683.06 10-DEC-16:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 12.46 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1612.11   324.00 129.38 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1683.06   583.20 152.48 449.03 0.00 0.00 0.00 0.00 41.08 0.67



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 31639.25 20-JAN-23:40 215910.14 8250.81 53983.22 0.00 0.00 0.00 0.00 0.00 305.59
February 31247.40 13-FEB-23:47 107955.07 4125.41 26991.61 0.00 0.00 0.00 0.00 0.00 305.13
March 31151.45 09-MAR-23:13 188921.38 7219.46 47235.32 0.00 0.00 0.00 0.00 0.00 315.65
April 24774.79 11-APR-05:43 209912.64 13751.36 56232.52 0.00 0.00 0.00 0.00 0.00 271.25
May 23445.39 25-MAY-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 57.60 0.00
June 23780.15 28-JUN-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 66.51 0.00
July 24015.81 07-JUL-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 81.27 0.00
August 23796.42 24-AUG-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 91.34 0.00
September 22819.82 05-SEP-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 33.64 0.00
October 23230.77 05-OCT-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 53.40 0.00
November 30606.25 12-NOV-07:34 188921.38 10726.06 60731.12 0.00 0.00 0.00 0.00 0.00 300.92
December 30986.61 05-DEC-23:48 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 283.41
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 22819.82   26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 31639.25   269887.68 13751.36 67479.03 0.00 0.00 0.00 0.00 91.34 315.65



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 33277.69 20-JAN-23:40 215910.14 8250.81 53983.22 0.00 0.00 0.00 0.00 0.00 306.49
February 32932.74 13-FEB-23:47 107955.07 4125.41 26991.61 0.00 0.00 0.00 0.00 0.00 306.44
March 32888.64 09-MAR-23:13 188921.38 7219.46 47235.32 0.00 0.00 0.00 0.00 0.00 317.34
April 27173.94 11-APR-05:43 209912.64 13751.36 56232.52 0.00 0.00 0.00 0.00 0.00 271.29
May 24648.75 25-MAY-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 57.56 0.00
June 24953.86 28-JUN-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 66.48 0.00
July 25179.16 07-JUL-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 81.26 0.00
August 24973.66 24-AUG-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 91.31 0.00
September 24018.95 05-SEP-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 33.58 0.00
October 24591.14 28-OCT-03:54 134943.84 1718.92 11246.50 0.00 0.00 0.00 0.00 0.00 230.71
November 32143.56 12-NOV-07:34 188921.38 10726.06 60731.12 0.00 0.00 0.00 0.00 0.00 301.46
December 32517.47 05-DEC-23:48 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 283.83
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 24018.95   26988.77 1718.92 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 33277.69   269887.68 13751.36 67479.03 0.00 0.00 0.00 0.00 91.31 317.34



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 33969.86 09-JAN-19:10 11207.95 5812.43 89477.13 89971.33 0.00 0.00 0.00 0.00 306.77
February 33491.35 17-FEB-18:33 9339.96 5085.88 104389.99 157449.82 0.00 0.00 0.00 0.00 296.82
March 32680.60 09-MAR-21:57 8539.39 3874.95 59651.42 44985.66 0.00 0.00 0.00 0.00 292.36
April 32106.68 11-APR-06:29 8539.39 4843.69 119302.85 89971.33 0.00 0.00 0.00 0.00 228.51
May 30966.11 29-MAY-10:40 2401.70 1089.83 44738.57 56232.08 0.00 0.00 0.00 80.44 0.00
June 30887.31 17-JUN-10:50 1601.14 605.46 29825.71 37488.05 0.00 0.00 0.00 108.85 0.00
July 31135.23 23-JUL-10:40 2401.70 1089.83 44738.57 56232.08 0.00 0.00 0.00 96.03 0.00
August 30687.14 06-AUG-10:50 800.57 363.28 14912.86 18744.03 0.00 0.00 0.00 99.08 0.00
September 31376.02 10-SEP-10:50 800.57 363.28 14912.86 18744.03 0.00 0.00 0.00 144.09 0.00
October 32950.27 28-OCT-07:59 9339.96 3390.59 104389.99 104966.55 0.00 0.00 0.00 0.00 231.21
November 33387.49 12-NOV-08:53 8005.68 2906.22 89477.13 89971.33 0.00 0.00 0.00 0.00 260.77
December 33922.52 20-DEC-16:13 9339.96 2119.12 104389.99 157449.82 0.00 0.00 0.00 0.00 266.54
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 30687.14   800.57 363.28 14912.86 18744.03 0.00 0.00 0.00 0.00 0.00
Maximum of Months 33969.86   11207.95 5812.43 119302.85 157449.82 0.00 0.00 0.00 144.09 306.77



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5954.04 04-JAN-20:28 18631.20 23715.21 0.00 0.00 0.00 0.00 0.00 0.00 272.94
February 5682.40 13-FEB-23:30 7186.32 2371.52 0.00 0.00 0.00 0.00 0.00 0.00 225.14
March 6542.97 08-MAR-23:15 4790.88 1581.01 0.00 0.00 0.00 0.00 0.00 0.00 255.10
April 5548.11 28-APR-15:03 7984.80 3952.54 0.00 0.00 0.00 0.00 0.00 127.86 0.00
May 6534.70 04-MAY-15:30 1330.80 658.76 0.00 0.00 0.00 0.00 0.00 123.43 0.00
June 6675.57 14-JUN-14:10 798.48 658.76 0.00 0.00 0.00 0.00 0.00 149.95 0.00
July 7108.72 22-JUL-17:12 6387.84 6324.06 0.00 0.00 0.00 0.00 0.00 144.06 0.00
August 6750.49 30-AUG-15:50 1330.80 658.76 0.00 0.00 0.00 0.00 0.00 163.11 0.00
September 7409.46 10-SEP-12:00 798.48 790.51 0.00 0.00 0.00 0.00 0.00 156.58 0.00
October 7113.63 07-OCT-13:00 798.48 658.76 0.00 0.00 0.00 0.00 0.00 126.55 0.00
November 6486.39 12-NOV-07:37 16768.08 9486.09 0.00 0.00 0.00 0.00 0.00 0.00 236.06
December 5876.73 06-DEC-01:02 11977.20 1976.27 0.00 0.00 0.00 0.00 0.00 0.00 204.06
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 5548.11   798.48 658.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7409.46   18631.20 23715.21 0.00 0.00 0.00 0.00 0.00 163.11 272.94



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.454021E+12 384723.39 19-JAN-20:00 0.436911E+12 427607.81 21-JAN-19:10
February 0.434423E+12 370637.48 02-FEB-20:49 0.379603E+12 431778.05 05-FEB-19:19
March 0.494708E+12 386693.62 07-MAR-20:10 0.411805E+12 393190.44 08-MAR-23:10
April 0.567195E+12 412418.73 28-APR-19:00 0.370354E+12 333242.41 05-APR-17:30
May 0.748307E+12 433026.30 25-MAY-19:19 0.371401E+12 318007.94 01-MAY-17:19
June 0.744886E+12 441660.32 27-JUN-19:30 0.351931E+12 315117.52 01-JUN-17:19
July 0.797886E+12 449387.53 10-JUL-19:30 0.359533E+12 313090.73 03-JUL-17:10
August 0.785120E+12 455688.58 24-AUG-19:00 0.360981E+12 313883.70 31-AUG-17:19
September 0.743270E+12 471307.42 09-SEP-20:00 0.354882E+12 316194.41 29-SEP-17:00
October 0.694455E+12 446800.46 06-OCT-19:00 0.376948E+12 319635.48 24-OCT-17:19
November 0.522649E+12 425643.02 03-NOV-19:40 0.383686E+12 377341.82 15-NOV-18:10
December 0.493391E+12 409864.39 15-DEC-20:00 0.421658E+12 434585.77 30-DEC-19:30
             
Annual Sum or Average 0.748031E+13     0.457969E+13    
Minimum of Months 0.434423E+12 370637.48   0.351931E+12 313090.73  
Maximum of Months 0.797886E+12 471307.42   0.436911E+12 434585.77  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.653946E+11 0.233209E+11 0.148212E+12 0.553309E+11 0.462511E+11 0.130559E+11 0.00 0.742339E+11 0.00 0.00 0.152306E+11 0.770473E+10 0.00
February 0.589900E+11 0.201416E+11 0.133859E+12 0.499764E+11 0.420208E+11 0.125587E+11 0.00 0.935277E+11 0.00 0.00 0.115972E+11 0.696222E+10 0.00
March 0.652229E+11 0.209110E+11 0.148223E+12 0.553338E+11 0.469104E+11 0.139024E+11 0.00 0.118668E+12 0.00 0.00 0.125282E+11 0.770319E+10 0.00
April 0.629163E+11 0.188903E+11 0.143397E+12 0.535455E+11 0.480876E+11 0.156409E+11 0.00 0.198204E+12 0.00 0.00 0.138849E+11 0.746512E+10 0.00
May 0.649254E+11 0.183064E+11 0.148223E+12 0.553320E+11 0.559047E+11 0.171395E+11 0.00 0.348799E+12 0.00 0.00 0.266022E+11 0.770431E+10 0.00
June 0.627711E+11 0.170550E+11 0.143446E+12 0.535482E+11 0.557988E+11 0.167988E+11 0.00 0.357291E+12 0.00 0.00 0.255192E+11 0.745693E+10 0.00
July 0.647755E+11 0.179727E+11 0.148174E+12 0.553291E+11 0.580245E+11 0.176717E+11 0.00 0.396262E+12 0.00 0.00 0.266185E+11 0.771250E+10 0.00
August 0.650356E+11 0.189552E+11 0.148234E+12 0.553336E+11 0.585385E+11 0.175686E+11 0.00 0.381943E+12 0.00 0.00 0.264341E+11 0.770433E+10 0.00
September 0.630069E+11 0.196689E+11 0.143408E+12 0.535457E+11 0.553786E+11 0.169219E+11 0.00 0.353012E+12 0.00 0.00 0.256607E+11 0.746634E+10 0.00
October 0.652562E+11 0.217359E+11 0.148201E+12 0.553307E+11 0.567069E+11 0.169803E+11 0.00 0.296737E+12 0.00 0.00 0.204505E+11 0.770298E+10 0.00
November 0.633096E+11 0.222086E+11 0.143462E+12 0.535468E+11 0.488039E+11 0.152677E+11 0.00 0.152334E+12 0.00 0.00 0.111306E+11 0.744914E+10 0.00
December 0.653548E+11 0.236268E+11 0.148174E+12 0.553296E+11 0.480363E+11 0.137510E+11 0.00 0.110798E+12 0.00 0.00 0.153112E+11 0.771282E+10 0.00
                           
Annual Sum or Average 0.766959E+12 0.242793E+12 0.174501E+13 0.651482E+12 0.620462E+12 0.187257E+12 0.00 0.288181E+13 0.00 0.00 0.230968E+12 0.907446E+11 0.00
Minimum of Months 0.589900E+11 0.170550E+11 0.133859E+12 0.499764E+11 0.420208E+11 0.125587E+11 0.00 0.742339E+11 0.00 0.00 0.111306E+11 0.696222E+10 0.00
Maximum of Months 0.653946E+11 0.236268E+11 0.148234E+12 0.553338E+11 0.585385E+11 0.176717E+11 0.00 0.396262E+12 0.00 0.00 0.266185E+11 0.771282E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.402779E+11 0.00 0.244715E+12 0.00 0.00
February 0.137204E+12 0.00 0.224546E+11 0.00 0.219945E+12 0.00 0.00
March 0.152024E+12 0.00 0.218484E+11 0.00 0.237933E+12 0.00 0.00
April 0.146956E+12 0.00 0.178040E+10 0.00 0.221618E+12 0.00 0.00
May 0.151978E+12 0.00 58176270.06 0.00 0.219364E+12 0.00 0.00
June 0.147114E+12 0.00 46580690.64 0.00 0.204771E+12 0.00 0.00
July 0.151820E+12 0.00 35055451.75 0.00 0.207678E+12 0.00 0.00
August 0.152039E+12 0.00 39596477.60 0.00 0.208903E+12 0.00 0.00
September 0.146971E+12 0.00 58221844.65 0.00 0.207853E+12 0.00 0.00
October 0.151903E+12 0.00 0.133069E+10 0.00 0.223714E+12 0.00 0.00
November 0.147091E+12 0.00 0.107733E+11 0.00 0.225821E+12 0.00 0.00
December 0.151820E+12 0.00 0.288163E+11 0.00 0.241021E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.127519E+12 0.00 0.266334E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 35055451.75 0.00 0.204771E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.402779E+11 0.00 0.244715E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 62892.57 02-JAN-20:10 15448.40 01-JAN-00:10 89475.41 02-JAN-07:10 39726.11 02-JAN-07:19 36930.65 06-JAN-22:19 7326.52 19-JAN-20:00 0.00 01-JAN-00:10
February 62892.57 01-FEB-20:10 15448.40 01-FEB-00:10 89475.41 01-FEB-07:10 39726.11 01-FEB-07:19 31334.84 27-FEB-22:10 6986.76 02-FEB-21:00 0.00 01-FEB-00:10
March 62892.57 01-MAR-20:10 15448.40 01-MAR-00:10 89475.41 01-MAR-07:10 39726.11 01-MAR-07:19 35993.82 08-MAR-23:10 7093.93 07-MAR-19:10 0.00 01-MAR-00:10
April 62892.57 03-APR-19:10 15448.40 01-APR-00:10 89475.41 03-APR-06:10 39726.11 03-APR-06:19 34531.73 28-APR-21:10 7640.03 28-APR-20:00 0.00 01-APR-00:10
May 62892.57 01-MAY-19:10 15448.40 01-MAY-00:10 89475.41 01-MAY-06:10 39725.67 19-MAY-06:19 37222.43 10-MAY-21:10 7719.18 19-MAY-20:30 0.00 01-MAY-00:10
June 62892.57 01-JUN-19:19 15448.40 01-JUN-00:10 89475.41 01-JUN-06:10 39725.51 07-JUN-06:19 38513.91 28-JUN-21:10 7693.42 29-JUN-18:10 0.00 01-JUN-00:10
July 62892.57 03-JUL-19:19 15448.40 01-JUL-00:10 89475.41 03-JUL-06:10 39725.67 26-JUL-06:19 39202.49 19-JUL-21:10 7765.80 05-JUL-18:10 0.00 01-JUL-00:10
August 62892.57 01-AUG-19:19 15448.40 01-AUG-00:10 89475.41 01-AUG-06:10 39726.11 07-AUG-06:19 41916.69 24-AUG-21:10 7866.02 09-AUG-20:19 0.00 01-AUG-00:10
September 62892.57 01-SEP-19:10 15448.40 01-SEP-00:10 89475.41 01-SEP-06:10 39726.11 01-SEP-06:19 41986.41 12-SEP-21:10 7848.91 01-SEP-18:19 0.00 01-SEP-00:10
October 62892.57 02-OCT-19:10 15448.40 01-OCT-00:10 89475.41 02-OCT-06:10 39726.11 02-OCT-06:19 43376.30 05-OCT-21:10 7976.37 23-OCT-20:49 0.00 01-OCT-00:10
November 62892.57 01-NOV-19:10 15448.40 01-NOV-00:10 89475.41 01-NOV-06:10 39726.11 01-NOV-06:19 39423.20 07-NOV-22:10 7876.55 03-NOV-19:00 0.00 01-NOV-00:10
December 62892.57 01-DEC-20:10 15448.40 01-DEC-00:10 89475.41 01-DEC-07:10 39726.11 01-DEC-07:19 38597.43 18-DEC-22:30 7496.89 15-DEC-20:00 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 62892.57   15448.40   89475.41   39725.51   31334.84   6986.76   0.00  
Maximum of Months 62892.57   15448.40   89475.41   39726.11   43376.30   7976.37   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 139339.76 19-JAN-19:10 0.00 0.00 9938.94 01-JAN-11:50 4738.63 11-JAN-19:10 0.00
February 130031.09 02-FEB-19:10 0.00 0.00 9938.94 01-FEB-13:30 4738.60 27-FEB-19:10 0.00
March 147235.00 07-MAR-19:10 0.00 0.00 9938.94 01-MAR-08:30 4738.48 14-MAR-06:19 0.00
April 185116.74 28-APR-15:00 0.00 0.00 9938.94 02-APR-01:30 4738.16 10-APR-18:10 0.00
May 188967.62 25-MAY-18:10 0.00 0.00 9938.94 01-MAY-00:10 4738.06 01-MAY-06:10 0.00
June 207820.32 28-JUN-18:10 0.00 0.00 9938.94 01-JUN-00:10 4738.46 29-JUN-18:10 0.00
July 229255.76 22-JUL-16:10 0.00 0.00 9938.94 01-JUL-00:10 4738.73 27-JUL-18:10 0.00
August 220872.22 24-AUG-18:10 0.00 0.00 9938.94 01-AUG-00:10 4738.75 31-AUG-18:10 0.00
September 239091.22 10-SEP-15:09 0.00 0.00 9938.94 01-SEP-00:10 4737.74 06-SEP-18:19 0.00
October 202310.44 06-OCT-15:20 0.00 0.00 9938.94 01-OCT-00:10 4738.13 02-OCT-06:10 0.00
November 171563.65 02-NOV-15:09 0.00 0.00 9938.94 01-NOV-01:00 4738.51 27-NOV-19:10 0.00
December 157263.56 15-DEC-21:19 0.00 0.00 9938.94 01-DEC-00:00 4738.58 20-DEC-19:10 0.00
                   
Annual Sum or Average     0.00 0.00         0.00
Minimum of Months 130031.09   0.00 0.00 9938.94   4737.74   0.00
Maximum of Months 239091.22   0.00 0.00 9938.94   4738.75   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 384723.39 19-JAN-20:00 62892.57 88772.42 15448.40 32159.77 28096.26 7326.52 0.00 135128.88 0.00
February 370637.48 02-FEB-20:49 62892.57 88772.42 15448.40 32159.77 26102.10 6912.78 0.00 123641.33 0.00
March 386693.62 07-MAR-20:10 62892.57 88772.42 15448.40 32151.31 27838.63 7005.37 0.00 137180.56 0.00
April 412418.73 28-APR-19:00 62892.57 88772.42 15448.40 32159.77 29138.33 7573.26 0.00 160770.54 0.00
May 433026.30 25-MAY-19:19 62892.57 88772.42 15448.40 32159.27 30206.58 7181.45 0.00 180271.60 0.00
June 441660.32 27-JUN-19:30 62892.57 88772.42 15448.40 32159.77 32838.79 7317.17 0.00 186647.56 0.00
July 449387.53 10-JUL-19:30 62892.57 88772.42 15448.40 32159.77 31534.74 7646.16 0.00 194501.63 0.00
August 455688.58 24-AUG-19:00 62892.57 88772.42 15448.40 32159.77 33867.77 7494.77 0.00 199185.81 0.00
September 471307.42 09-SEP-20:00 52161.37 86164.46 15448.40 24483.08 34321.32 7709.57 0.00 234503.27 0.00
October 446800.46 06-OCT-19:00 62892.57 88772.42 15448.40 32159.77 35670.66 7748.91 0.00 188486.67 0.00
November 425643.02 03-NOV-19:40 62892.57 88772.42 15448.40 32159.77 31533.75 7862.13 0.00 171062.71 0.00
December 409864.39 15-DEC-20:00 62892.57 88772.42 15448.40 32159.77 30856.01 7496.89 0.00 156445.30 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 370637.48   52161.37 86164.46 15448.40 24483.08 26102.10 6912.78 0.00 123641.33 0.00
Maximum of Months 471307.42   62892.57 88772.42 15448.40 32159.77 35670.66 7862.13 0.00 234503.27 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 142976.55 28-JAN-01:49 0.00 245512.95 10-JAN-21:30 0.00
February 104248.32 01-FEB-18:10 0.00 143425.07 04-FEB-05:19 0.00 245943.06 17-FEB-18:00 0.00
March 104248.32 01-MAR-18:10 0.00 140019.97 22-MAR-04:49 0.00 243431.62 01-MAR-21:00 0.00
April 104248.32 01-APR-17:10 0.00 71980.33 11-APR-05:40 0.00 229917.98 01-APR-21:00 0.00
May 104248.32 01-MAY-17:10 0.00 6810.78 23-MAY-08:09 0.00 214257.18 01-MAY-20:19 0.00
June 104248.32 01-JUN-17:10 0.00 4959.10 09-JUN-08:09 0.00 211234.69 01-JUN-20:19 0.00
July 104248.32 01-JUL-17:10 0.00 5039.04 14-JUL-08:09 0.00 209079.84 05-JUL-20:40 0.00
August 104248.32 01-AUG-17:10 0.00 4647.54 17-AUG-08:09 0.00 210038.63 31-AUG-20:49 0.00
September 104248.32 01-SEP-17:10 0.00 4901.18 08-SEP-08:09 0.00 212478.59 29-SEP-20:49 0.00
October 104248.32 02-OCT-17:10 0.00 90783.19 28-OCT-06:49 0.00 219011.66 31-OCT-18:00 0.00
November 104248.32 01-NOV-17:10 0.00 146434.37 15-NOV-04:40 0.00 240553.48 30-NOV-19:19 0.00
December 104248.32 01-DEC-18:10 0.00 135907.53 20-DEC-00:40 0.00 243709.77 26-DEC-21:30 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 4647.54   0.00 209079.84   0.00
Maximum of Months 104248.32   0.00 146434.37   0.00 245943.06   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 13.17 25.08 13.17 25.08
February 0.00 0.00 0.00 0.00 3.83 24.87 3.83 24.87
March 0.00 0.00 0.00 0.00 6.33 25.20 6.33 25.20
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 1.00 25.08 1.00 25.08
December 0.00 0.00 0.00 0.00 5.00 25.02 5.00 25.02
                 
Annual Sum or Average 0.00   0.00   29.33 25.07 29.33 25.07
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 13.17 25.20 13.17 25.20



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.17 21.73 0.17 21.73
September 0.00 0.00 0.00 0.00 0.33 21.79 0.33 21.79
October 0.00 0.00 0.00 0.00 1.17 21.78 1.17 21.78
November 0.00 0.00 0.00 0.00 0.17 21.76 0.17 21.76
December 0.00 0.00 0.00 0.00 0.17 21.73 0.17 21.73
                 
Annual Sum or Average 0.00   0.00   2.00 21.77 2.00 21.77
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.17 21.79 1.17 21.79



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 21.71 0.17 21.71
July 0.00 0.00 0.00 0.00 0.17 21.70 0.17 21.70
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.17 21.73 0.17 21.73
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.50 21.71 0.50 21.71
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 21.73 0.17 21.73



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 5.00 21.70 5.00 21.70
June 0.00 0.00 0.00 0.00 8.33 21.73 8.33 21.73
July 0.00 0.00 0.00 0.00 8.50 21.75 8.50 21.75
August 0.00 0.00 0.00 0.00 7.00 21.72 7.00 21.72
September 0.00 0.00 0.00 0.00 2.67 21.70 2.67 21.70
October 0.00 0.00 0.00 0.00 1.17 21.70 1.17 21.70
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   32.67 21.72 32.67 21.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 8.50 21.75 8.50 21.75



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 21.67 0.17 21.67
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.33 21.71 0.33 21.71
October 0.00 0.00 0.00 0.00 0.17 21.67 0.17 21.67
November 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1.00 21.69 1.00 21.69
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.33 21.71 0.33 21.71



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.33 21.70 0.33 21.70
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.33 21.71 0.33 21.71
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.17 21.71 0.17 21.71
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.83 21.71 0.83 21.71
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.33 21.71 0.33 21.71



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.17 21.70 0.17 21.70
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 21.70 0.33 21.70
May 0.00 0.00 0.00 0.00 0.50 21.73 0.50 21.73
June 0.00 0.00 0.00 0.00 0.67 21.72 0.67 21.72
July 0.00 0.00 0.00 0.00 0.83 21.73 0.83 21.73
August 0.00 0.00 0.00 0.00 0.67 21.73 0.67 21.73
September 0.00 0.00 0.00 0.00 1.50 21.75 1.50 21.75
October 0.00 0.00 0.00 0.00 1.50 21.79 1.50 21.79
November 0.00 0.00 0.00 0.00 0.17 21.84 0.17 21.84
December 0.00 0.00 0.00 0.00 0.17 21.67 0.17 21.67
                 
Annual Sum or Average 0.00   0.00   6.50 21.75 6.50 21.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.50 21.84 1.50 21.84



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
May 0.00 0.00 0.00 0.00 0.83 21.71 0.83 21.71
June 0.00 0.00 0.00 0.00 1.67 21.73 1.67 21.73
July 0.00 0.00 0.00 0.00 1.00 21.75 1.00 21.75
August 0.00 0.00 0.00 0.00 0.50 21.72 0.50 21.72
September 0.00 0.00 0.00 0.00 0.17 21.87 0.17 21.87
October 0.00 0.00 0.00 0.00 0.17 21.71 0.17 21.71
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.50 21.73 4.50 21.73
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.67 21.87 1.67 21.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.83 21.89 1.83 21.89
February 0.00 0.00 0.00 0.00 2.00 21.77 2.00 21.77
March 0.00 0.00 0.00 0.00 0.67 21.75 0.67 21.75
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.83 21.71 0.83 21.71
September 0.00 0.00 0.00 0.00 2.33 21.81 2.33 21.81
October 0.00 0.00 0.00 0.00 5.83 21.90 5.83 21.90
November 0.00 0.00 0.00 0.00 3.00 21.87 3.00 21.87
December 0.00 0.00 0.00 0.00 3.33 21.90 3.33 21.90
                 
Annual Sum or Average 0.00   0.00   19.83 21.86 19.83 21.86
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.83 21.90 5.83 21.90



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.83 24.65 0.83 24.65
February 0.00 0.00 0.00 0.00 0.17 24.98 0.17 24.98
March 0.00 0.00 0.00 0.00 1.17 24.76 1.17 24.76
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.67 24.65 0.67 24.65
                 
Annual Sum or Average 0.00   0.00   2.83 24.71 2.83 24.71
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.17 24.98 1.17 24.98



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.00 24.70 1.00 24.70
February 0.00 0.00 0.00 0.00 0.50 24.75 0.50 24.75
March 0.00 0.00 0.00 0.00 1.67 24.76 1.67 24.76
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.17 24.58 0.17 24.58
December 0.00 0.00 0.00 0.00 1.00 24.67 1.00 24.67
                 
Annual Sum or Average 0.00   0.00   4.33 24.71 4.33 24.71
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.67 24.76 1.67 24.76



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 12.33 25.05 12.33 25.05
February 0.00 0.00 0.00 0.00 7.83 24.84 7.83 24.84
March 0.00 0.00 0.00 0.00 10.17 24.97 10.17 24.97
April 0.00 0.00 0.00 0.00 1.33 24.81 1.33 24.81
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.50 24.79 0.50 24.79
November 0.00 0.00 0.00 0.00 3.33 24.86 3.33 24.86
December 0.00 0.00 0.00 0.00 7.00 24.89 7.00 24.89
                 
Annual Sum or Average 0.00   0.00   42.50 24.94 42.50 24.94
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 12.33 25.05 12.33 25.05



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 325.33 23.61 126.67 23.68 0.00 23.68
February 589.17 23.07 19.00 23.09 0.00 23.09
March 741.33 22.63 0.00 22.63 0.00 22.63
April 720.00 22.24 0.00 22.24 0.00 22.24
May 744.00 22.39 0.00 22.39 0.00 22.39
June 720.00 22.61 0.00 22.61 0.00 22.61
July 507.67 22.99 9.50 23.00 0.00 23.00
August 20.67 23.14 465.67 23.92 0.00 23.92
September 0.50 23.30 504.50 23.96 0.00 23.96
October 37.00 23.84 460.00 23.96 0.00 23.96
November 89.00 23.81 325.33 23.93 0.00 23.93
December 168.50 23.72 215.00 23.85 0.00 23.85
             
Annual Sum or Average 4663.17 22.77 2125.67 23.14 0.00 23.14
Minimum of Months 0.50 22.24 0.00 22.24 0.00 22.24
Maximum of Months 744.00 23.84 504.50 23.96 0.00 23.96



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 574.67 21.73 103.17 22.03 4.33 22.02
February 485.17 21.76 147.17 22.16 15.83 22.13
March 589.67 21.74 98.17 21.98 10.00 21.96
April 492.33 22.06 144.83 22.41 0.00 22.41
May 109.50 22.63 424.00 23.41 0.00 23.41
June 55.17 22.64 550.33 23.53 0.00 23.53
July 42.17 22.58 607.67 23.59 0.00 23.59
August 31.50 22.68 634.83 23.64 0.00 23.64
September 83.17 22.61 511.17 23.55 0.00 23.55
October 146.17 22.29 524.50 23.46 0.00 23.46
November 401.17 22.12 229.50 22.74 0.00 22.74
December 499.83 21.74 182.83 22.27 7.00 22.26
             
Annual Sum or Average 3510.50 21.93 4158.17 22.88 37.17 22.87
Minimum of Months 31.50 21.73 98.17 21.98 0.00 21.96
Maximum of Months 589.67 22.68 634.83 23.64 15.83 23.64



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 603.33 22.55 65.83 22.67 0.00 22.67
February 453.67 22.50 108.00 22.75 0.00 22.75
March 525.67 22.53 116.83 22.76 0.00 22.76
April 338.00 22.77 234.83 23.20 0.00 23.20
May 73.00 22.93 481.83 23.73 0.00 23.73
June 35.83 22.94 509.17 23.82 0.00 23.82
July 30.83 22.95 562.50 23.82 0.83 23.82
August 14.33 23.14 576.00 23.85 3.00 23.85
September 34.67 23.00 538.00 23.79 2.17 23.79
October 113.67 23.06 493.17 23.70 6.67 23.70
November 384.00 22.92 199.83 23.22 0.00 23.22
December 501.33 22.58 144.00 22.84 0.00 22.84
             
Annual Sum or Average 3108.33 22.66 4030.00 23.33 12.67 23.33
Minimum of Months 14.33 22.50 65.83 22.67 0.00 22.67
Maximum of Months 603.33 23.14 576.00 23.85 6.67 23.85



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 741.67 21.77 0.00 21.77 0.00 21.77
February 663.33 21.97 0.00 21.97 0.00 21.97
March 726.00 22.14 0.00 22.14 0.00 22.14
April 600.50 22.70 19.50 22.74 0.00 22.74
May 46.83 23.17 361.67 23.79 0.00 23.79
June 11.33 23.21 513.67 23.89 0.00 23.89
July 14.00 23.19 608.17 23.90 0.00 23.90
August 0.33 23.28 557.00 23.90 0.00 23.90
September 34.83 23.20 379.00 23.82 0.00 23.82
October 222.33 22.98 286.00 23.48 0.00 23.48
November 630.67 22.53 18.67 22.57 0.00 22.57
December 706.00 22.07 4.83 22.09 0.00 22.09
             
Annual Sum or Average 4397.83 22.24 2748.50 22.88 0.00 22.88
Minimum of Months 0.33 21.77 0.00 21.77 0.00 21.77
Maximum of Months 741.67 23.28 608.17 23.90 0.00 23.90



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.64 0.00 21.64 0.00 21.64
February 672.00 21.86 4.50 21.86 4.50 21.85
March 744.00 22.03 0.00 22.03 0.00 22.03
April 688.83 22.66 0.00 22.66 0.00 22.66
May 102.00 23.23 167.00 23.61 0.00 23.61
June 25.83 23.28 415.00 23.85 0.00 23.85
July 29.00 23.22 536.83 23.87 0.00 23.87
August 4.50 23.30 461.33 23.87 0.00 23.87
September 80.67 23.24 223.67 23.69 0.00 23.69
October 277.33 22.97 177.83 23.31 0.00 23.31
November 686.33 22.48 0.00 22.48 0.00 22.48
December 737.17 22.01 0.00 22.01 0.00 22.01
             
Annual Sum or Average 4791.67 22.21 1986.17 22.70 4.50 22.70
Minimum of Months 4.50 21.64 0.00 21.64 0.00 21.64
Maximum of Months 744.00 23.30 536.83 23.87 4.50 23.87



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 275.50 23.45 618.67 23.31 217.17 23.46
February 261.50 23.57 564.50 23.31 220.33 23.46
March 290.00 23.60 636.83 23.32 248.50 23.47
April 291.83 23.89 679.33 23.31 282.83 23.46
May 318.17 23.96 738.83 23.30 318.17 23.45
June 310.67 23.95 718.50 23.29 310.67 23.44
July 322.17 23.95 741.67 23.30 322.17 23.45
August 320.17 23.96 742.67 23.29 320.17 23.45
September 306.00 23.96 715.00 23.30 306.00 23.45
October 309.17 23.90 722.83 23.31 301.33 23.46
November 288.67 23.70 651.33 23.32 260.50 23.47
December 283.33 23.49 620.17 23.30 232.67 23.45
             
Annual Sum or Average 3577.17 23.79 8150.33 23.30 3340.50 23.45
Minimum of Months 261.50 23.45 564.50 23.29 217.17 23.44
Maximum of Months 322.17 23.96 742.67 23.32 322.17 23.47



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 394.67 22.91 304.83 23.30 83.50 23.36
February 383.00 23.05 362.00 23.42 144.83 23.49
March 457.67 22.80 340.33 23.20 141.83 23.30
April 381.50 23.29 445.33 23.51 211.00 23.59
May 297.83 23.94 711.67 23.74 294.83 23.79
June 277.17 23.97 700.17 23.76 276.50 23.80
July 295.00 23.96 725.00 23.78 292.67 23.83
August 282.17 23.97 734.33 23.81 282.17 23.85
September 285.00 23.96 709.17 23.82 285.00 23.86
October 259.50 23.79 670.33 23.86 220.50 23.88
November 236.17 23.51 527.67 23.74 136.50 23.77
December 364.33 22.92 376.17 23.39 102.83 23.46
             
Annual Sum or Average 3914.00 23.43 6607.00 23.64 2472.17 23.69
Minimum of Months 236.17 22.80 304.83 23.20 83.50 23.30
Maximum of Months 457.67 23.97 734.33 23.86 294.83 23.88



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 468.50 23.11 194.33 23.32 69.00 23.38
February 413.83 23.22 291.17 23.45 124.33 23.52
March 452.67 23.08 266.67 23.36 121.83 23.44
April 335.50 23.43 401.67 23.66 180.50 23.72
May 251.33 23.98 624.67 23.87 249.17 23.89
June 229.67 23.98 635.17 23.86 227.67 23.89
July 239.50 23.99 681.50 23.86 238.00 23.89
August 233.33 24.00 706.00 23.86 233.33 23.89
September 235.00 23.99 684.33 23.86 235.00 23.89
October 213.33 23.87 640.33 23.87 179.50 23.89
November 238.33 23.58 407.67 23.76 109.83 23.79
December 391.67 23.16 306.50 23.46 89.67 23.52
             
Annual Sum or Average 3702.67 23.51 5840.00 23.71 2057.83 23.75
Minimum of Months 213.33 23.08 194.33 23.32 69.00 23.38
Maximum of Months 468.50 24.00 706.00 23.87 249.17 23.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 723.83 21.38 32.83 21.37 31.83 21.35
February 636.33 21.38 50.17 21.35 49.00 21.32
March 712.50 21.37 39.00 21.34 38.83 21.30
April 662.33 21.49 1.67 21.49 0.83 21.49
May 618.50 21.40 5.17 21.41 0.00 21.41
June 583.67 21.36 10.50 21.39 0.00 21.39
July 598.67 21.34 12.83 21.39 0.00 21.39
August 596.00 21.33 11.00 21.37 0.00 21.37
September 587.33 21.36 20.83 21.42 1.67 21.43
October 622.67 21.38 20.33 21.45 0.17 21.45
November 666.50 21.49 8.17 21.51 0.50 21.51
December 699.50 21.36 38.33 21.34 35.67 21.31
             
Annual Sum or Average 7707.83 21.39 250.83 21.40 158.50 21.39
Minimum of Months 583.67 21.33 1.67 21.34 0.00 21.30
Maximum of Months 723.83 21.49 50.17 21.51 49.00 21.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 737.67 21.15 116.33 21.07 116.33 21.02
February 657.00 21.24 89.67 21.17 89.67 21.12
March 731.83 21.32 67.00 21.26 67.00 21.21
April 677.00 21.49 0.83 21.49 0.67 21.49
May 623.83 21.41 3.83 21.43 0.00 21.43
June 581.83 21.36 10.67 21.39 0.00 21.39
July 598.17 21.34 11.67 21.38 0.00 21.38
August 603.00 21.35 5.00 21.37 0.00 21.37
September 604.50 21.40 11.67 21.44 2.50 21.44
October 655.00 21.43 6.17 21.45 1.17 21.45
November 697.83 21.42 1.50 21.42 1.50 21.42
December 726.50 21.22 85.67 21.15 85.67 21.09
             
Annual Sum or Average 7894.17 21.34 410.00 21.32 364.50 21.29
Minimum of Months 581.83 21.15 0.83 21.07 0.00 21.02
Maximum of Months 737.67 21.49 116.33 21.49 116.33 21.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.10 74.00 21.06 74.00 21.03
February 672.00 21.16 71.83 21.13 71.83 21.11
March 744.00 21.23 21.00 21.23 21.00 21.22
April 720.00 21.39 0.83 21.39 0.83 21.39
May 744.00 21.59 0.00 21.59 0.00 21.59
June 720.00 21.63 0.00 21.63 0.00 21.63
July 744.00 21.63 0.00 21.63 0.00 21.63
August 744.00 21.61 0.33 21.61 0.33 21.61
September 720.00 21.56 5.67 21.56 5.67 21.56
October 744.00 21.48 3.00 21.48 3.00 21.49
November 720.00 21.27 0.67 21.27 0.67 21.27
December 744.00 21.16 46.00 21.14 46.00 21.12
             
Annual Sum or Average 8760.00 21.40 223.33 21.39 223.33 21.38
Minimum of Months 672.00 21.10 0.00 21.06 0.00 21.03
Maximum of Months 744.00 21.63 74.00 21.63 74.00 21.63



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 727.33 21.45 25.67 21.43 25.50 21.42
February 633.67 21.43 40.17 21.41 40.17 21.39
March 698.83 21.41 31.50 21.39 31.50 21.36
April 643.50 21.49 0.67 21.50 0.67 21.50
May 576.67 21.28 0.67 21.28 0.00 21.28
June 546.83 21.25 0.00 21.25 0.00 21.25
July 567.17 21.25 3.00 21.26 0.00 21.26
August 572.17 21.27 0.17 21.27 0.00 21.27
September 570.17 21.31 7.67 21.34 1.67 21.34
October 612.67 21.37 5.33 21.39 0.17 21.39
November 672.50 21.55 1.00 21.56 0.33 21.56
December 704.00 21.39 37.17 21.37 37.00 21.34
             
Annual Sum or Average 7525.50 21.38 153.00 21.38 137.00 21.37
Minimum of Months 546.83 21.25 0.00 21.25 0.00 21.25
Maximum of Months 727.33 21.55 40.17 21.56 40.17 21.56



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.20 99.50 21.16 99.50 21.12
February 671.83 21.33 82.67 21.28 82.67 21.23
March 727.17 21.40 41.83 21.37 41.83 21.34
April 663.33 21.53 0.67 21.53 0.67 21.53
May 576.00 21.28 0.67 21.28 0.00 21.28
June 543.83 21.24 0.33 21.24 0.00 21.24
July 566.33 21.25 2.50 21.26 0.00 21.26
August 573.83 21.27 0.00 21.27 0.00 21.27
September 583.83 21.36 3.67 21.37 2.17 21.37
October 637.17 21.41 1.00 21.41 1.00 21.41
November 702.00 21.46 1.33 21.46 1.33 21.46
December 741.50 21.26 85.50 21.19 85.50 21.14
             
Annual Sum or Average 7730.83 21.34 319.67 21.32 314.67 21.30
Minimum of Months 543.83 21.20 0.00 21.16 0.00 21.12
Maximum of Months 744.00 21.53 99.50 21.53 99.50 21.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 740.67 22.09 1.50 22.09 1.50 22.10
February 671.33 22.22 0.33 22.22 0.33 22.22
March 744.00 22.35 4.33 22.35 4.33 22.36
April 644.67 22.88 31.00 22.90 27.50 22.91
May 142.50 23.60 308.67 23.76 99.50 23.75
June 105.67 23.81 437.67 23.88 100.83 23.87
July 117.17 23.83 536.67 23.90 109.67 23.89
August 115.17 23.83 484.00 23.88 114.00 23.88
September 134.00 23.67 389.50 23.82 109.00 23.81
October 253.67 23.36 352.67 23.68 61.50 23.69
November 620.67 22.84 41.17 22.88 28.00 22.90
December 712.33 22.36 11.83 22.37 11.83 22.39
             
Annual Sum or Average 5001.83 22.65 2599.33 23.06 668.00 23.12
Minimum of Months 105.67 22.09 0.33 22.09 0.33 22.10
Maximum of Months 744.00 23.83 536.67 23.90 114.00 23.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 719.67 21.30 114.17 21.26 110.00 21.22
February 630.67 21.32 94.67 21.28 88.33 21.24
March 701.00 21.30 86.50 21.23 85.17 21.18
April 643.33 21.42 15.50 21.46 4.67 21.46
May 602.17 21.34 29.67 21.44 0.00 21.44
June 568.17 21.30 37.00 21.43 0.00 21.43
July 588.33 21.31 47.83 21.46 0.00 21.46
August 587.00 21.30 45.83 21.44 0.83 21.45
September 578.83 21.33 42.17 21.46 4.17 21.46
October 616.83 21.35 40.50 21.46 4.00 21.47
November 661.33 21.45 20.50 21.49 6.50 21.49
December 697.67 21.29 104.83 21.26 92.17 21.21
             
Annual Sum or Average 7595.00 21.33 679.17 21.38 395.83 21.36
Minimum of Months 568.17 21.29 15.50 21.23 0.00 21.18
Maximum of Months 719.67 21.45 114.17 21.49 110.00 21.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 735.50 21.05 235.67 20.96 235.67 20.90
February 652.33 21.17 149.33 21.08 149.33 21.03
March 720.67 21.24 102.67 21.16 102.67 21.10
April 660.33 21.43 9.67 21.45 4.83 21.45
May 604.33 21.35 24.83 21.43 0.00 21.43
June 566.67 21.30 36.50 21.43 0.00 21.43
July 587.33 21.31 45.67 21.45 0.00 21.45
August 592.00 21.31 32.50 21.42 0.00 21.42
September 595.00 21.36 30.50 21.45 5.83 21.45
October 647.33 21.38 22.00 21.43 7.50 21.44
November 695.00 21.36 28.67 21.34 28.17 21.33
December 723.83 21.13 152.33 21.03 152.33 20.96
             
Annual Sum or Average 7780.33 21.28 870.33 21.28 686.33 21.23
Minimum of Months 566.67 21.05 9.67 20.96 0.00 20.90
Maximum of Months 735.50 21.43 235.67 21.45 235.67 21.45



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 688.83 21.47 24.33 21.48 15.17 21.48
February 599.67 21.41 30.17 21.41 26.00 21.40
March 692.50 21.38 37.83 21.35 37.83 21.32
April 663.67 21.48 3.00 21.49 3.00 21.49
May 650.83 21.48 0.00 21.48 0.00 21.48
June 615.17 21.44 0.00 21.44 0.00 21.44
July 629.83 21.43 0.00 21.43 0.00 21.43
August 620.83 21.40 0.67 21.40 0.67 21.40
September 599.17 21.39 9.50 21.42 4.00 21.42
October 607.33 21.35 34.83 21.46 3.17 21.47
November 616.00 21.41 25.17 21.49 1.50 21.49
December 654.67 21.37 42.50 21.43 17.67 21.43
             
Annual Sum or Average 7638.50 21.42 208.00 21.44 109.00 21.44
Minimum of Months 599.17 21.35 0.00 21.35 0.00 21.32
Maximum of Months 692.50 21.48 42.50 21.49 37.83 21.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 277.67 23.35 357.17 23.65 87.50 23.69
February 262.50 23.58 416.00 23.77 136.67 23.81
March 234.00 23.55 463.33 23.80 122.67 23.83
April 189.33 23.94 663.67 23.93 176.83 23.94
May 226.83 24.00 744.00 23.98 226.83 23.98
June 213.33 24.00 720.00 23.99 213.33 23.99
July 222.00 24.00 744.00 23.99 222.00 23.99
August 221.33 24.00 744.00 23.98 221.33 23.99
September 222.33 24.00 720.00 23.97 222.33 23.98
October 182.33 23.97 701.83 23.95 175.67 23.96
November 172.17 23.76 543.83 23.87 114.50 23.89
December 239.00 23.41 425.83 23.74 97.67 23.77
             
Annual Sum or Average 2662.83 23.77 7243.67 23.90 2017.33 23.92
Minimum of Months 172.17 23.35 357.17 23.65 87.50 23.69
Maximum of Months 277.67 24.00 744.00 23.99 226.83 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 184.17 23.47 463.00 23.80 72.50 23.82
February 184.17 23.72 460.00 23.87 117.17 23.89
March 162.83 23.72 559.33 23.90 108.33 23.91
April 161.17 23.98 691.00 23.97 158.50 23.97
May 214.00 24.00 744.00 23.99 214.00 23.99
June 202.67 24.00 720.00 23.99 202.67 23.99
July 209.17 24.00 744.00 23.99 209.17 23.99
August 209.33 24.00 744.00 23.99 209.33 23.99
September 209.83 24.00 720.00 23.99 209.83 23.99
October 165.83 23.99 712.50 23.97 165.17 23.98
November 120.00 23.89 605.50 23.93 101.83 23.94
December 159.67 23.56 527.50 23.85 84.83 23.87
             
Annual Sum or Average 2182.83 23.87 7690.83 23.95 1853.33 23.95
Minimum of Months 120.00 23.47 460.00 23.80 72.50 23.82
Maximum of Months 214.00 24.00 744.00 23.99 214.00 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 531.17 24.03 695.50 23.97 524.17 23.99
February 492.00 23.99 641.50 23.94 482.00 23.96
March 549.00 24.01 725.17 23.95 546.00 23.97
April 551.33 24.00 720.00 23.95 551.33 23.96
May 604.83 23.99 744.00 23.98 604.83 23.98
June 591.83 23.99 720.00 23.98 591.83 23.98
July 618.67 23.99 744.00 23.98 618.67 23.99
August 611.00 23.99 744.00 23.98 611.00 23.99
September 583.50 23.99 720.00 23.98 583.50 23.98
October 585.67 23.99 741.67 23.97 585.67 23.97
November 535.17 24.00 706.50 23.94 535.00 23.96
December 542.00 23.99 708.00 23.94 536.67 23.96
             
Annual Sum or Average 6796.17 24.00 8610.33 23.96 6770.67 23.98
Minimum of Months 492.00 23.99 641.50 23.94 482.00 23.96
Maximum of Months 618.67 24.03 744.00 23.98 618.67 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 719.00 21.76 5.17 21.77 0.00 21.77
February 630.00 21.98 13.83 21.99 6.50 21.98
March 712.33 22.16 0.00 22.16 0.00 22.16
April 486.00 22.66 98.67 22.86 0.00 22.86
May 8.17 23.09 625.17 23.84 0.00 23.84
June 0.00 0.00 677.50 23.90 0.00 23.90
July 2.50 23.17 704.00 23.91 0.00 23.91
August 0.00 0.00 696.17 23.89 0.00 23.89
September 7.67 23.13 556.83 23.84 0.00 23.84
October 175.00 22.80 454.83 23.57 0.00 23.57
November 566.50 22.45 65.33 22.60 0.00 22.60
December 654.33 21.97 27.00 22.04 0.00 22.04
             
Annual Sum or Average 3961.50 22.16 3924.50 23.01 6.50 23.01
Minimum of Months 0.00 0.00 0.00 21.77 0.00 21.77
Maximum of Months 719.00 23.17 704.00 23.91 6.50 23.91



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.70860 43.98712 0.31283 7.24801
February 672.00000 23.13721 49.09547 0.19345 6.08530
March 744.00000 22.63591 49.60343 0.06392 5.34101
April 720.00000 22.24482 58.79657 0.01940 5.22521
May 744.00000 22.39449 62.71023 -0.9779 25.40121
June 720.00000 22.60839 61.64480 -0.9041 22.46908
July 744.00000 23.15963 59.95104 -0.7101 15.85515
August 744.00000 23.78497 57.89847 -0.4860 10.07949
September 720.00000 23.85077 57.84278 -0.4589 9.51631
October 744.00000 23.87201 54.52444 0.43874 9.11932
November 720.00000 23.88105 48.76504 0.39903 8.49180
December 744.00000 23.83972 45.87703 0.36460 7.95886
           
Annual Sum or Average 8760.00000 23.26205 54.23905 -0.1472 11.10289
Minimum of Months 672.00000 22.24482 43.98712 -0.9779 5.22521
Maximum of Months 744.00000 23.88105 62.71023 0.43874 25.40121



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.16057 47.09036 0.01522 7.26003
February 672.00000 22.27306 50.55821 0.07247 7.64896
March 744.00000 22.09522 50.29129 0.01356 7.15778
April 720.00000 22.47981 57.82351 0.18389 6.93997
May 744.00000 23.29030 60.59710 -0.4929 10.67328
June 720.00000 23.44467 59.90780 -0.4352 9.44806
July 744.00000 23.50963 60.25353 -0.4046 8.93680
August 744.00000 23.56749 59.92755 -0.3815 8.55471
September 720.00000 23.45415 60.42738 -0.4185 9.49720
October 744.00000 23.42732 56.31773 0.46248 10.64582
November 720.00000 22.81333 51.47557 0.24664 8.09932
December 744.00000 22.37244 49.07145 0.09409 8.01035
           
Annual Sum or Average 8760.00000 22.91100 55.32788 -0.0881 8.58112
Minimum of Months 672.00000 22.09522 47.09036 -0.4929 6.93997
Maximum of Months 744.00000 23.56749 60.59710 0.46248 10.67328



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.73703 47.23002 0.11547 6.14919
February 672.00000 22.84080 50.59891 0.16773 6.75039
March 744.00000 22.83926 49.89245 0.16151 6.65960
April 720.00000 23.23364 56.84126 0.31650 7.67514
May 744.00000 23.60925 60.26403 -0.4723 10.00363
June 720.00000 23.68187 59.71075 -0.4434 9.40710
July 744.00000 23.71144 59.97516 -0.4301 9.14018
August 744.00000 23.73107 59.89761 -0.4226 8.96684
September 720.00000 23.68072 60.31834 -0.4420 9.38004
October 744.00000 23.64130 56.81909 0.43630 9.32583
November 720.00000 23.26382 51.76257 0.29082 7.32331
December 744.00000 22.91490 49.26991 0.17857 6.74163
           
Annual Sum or Average 8760.00000 23.32618 55.23165 -0.0468 8.13472
Minimum of Months 672.00000 22.73703 47.23002 -0.4723 6.14919
Maximum of Months 744.00000 23.73107 60.31834 0.43630 10.00363



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.94748 42.66375 0.73741 19.38659
February 672.00000 22.92611 46.40955 0.76713 20.29391
March 744.00000 22.93664 45.55651 0.77481 20.50973
April 720.00000 22.96477 53.36580 0.86088 23.09081
May 744.00000 22.99943 57.60709 0.22863 11.00399
June 720.00000 22.99506 57.32412 0.23737 11.13977
July 744.00000 23.01332 57.46694 0.24320 11.00686
August 744.00000 23.00108 57.61105 0.23585 11.09398
September 720.00000 23.00103 57.85579 0.22143 10.92627
October 744.00000 23.00467 54.36412 0.89639 24.24040
November 720.00000 22.98073 48.29264 0.81800 21.68303
December 744.00000 22.92603 45.13477 0.75650 19.91054
           
Annual Sum or Average 8760.00000 22.97498 51.99219 0.56347 17.00038
Minimum of Months 672.00000 22.92603 42.66375 0.22143 10.92627
Maximum of Months 744.00000 23.01332 57.85579 0.89639 24.24040



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.25233 50.41808 0.34126 8.73749
February 672.00000 23.30631 53.73728 0.38297 9.69478
March 744.00000 23.09108 53.60611 0.31281 8.80209
April 720.00000 23.33385 60.87368 0.44394 9.83736
May 744.00000 23.60978 64.19157 -0.3056 7.30198
June 720.00000 23.64366 63.76240 -0.2868 7.01355
July 744.00000 23.68184 63.91480 -0.2649 6.77099
August 744.00000 23.73902 63.67036 -0.2401 6.48287
September 720.00000 23.75191 63.85169 -0.2364 6.55785
October 744.00000 23.80878 59.93616 0.62273 13.64532
November 720.00000 23.66592 54.80120 0.51624 11.27996
December 744.00000 23.32789 52.46750 0.38885 9.85157
           
Annual Sum or Average 8760.00000 23.51855 58.78810 0.13792 8.82596
Minimum of Months 672.00000 23.09108 50.41808 -0.3056 6.48287
Maximum of Months 744.00000 23.80878 64.19157 0.62273 13.64532



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.31578 49.47169 0.28647 7.39934
February 672.00000 23.35354 52.86066 0.32351 8.07316
March 744.00000 23.29104 52.28647 0.30201 7.86720
April 720.00000 23.50966 59.33330 0.41878 9.14934
May 744.00000 23.70090 62.71488 -0.3874 8.42208
June 720.00000 23.73058 62.23678 -0.3719 8.15212
July 744.00000 23.75810 62.43097 -0.3577 7.90685
August 744.00000 23.78054 62.35381 -0.3492 7.73376
September 720.00000 23.78370 62.63121 -0.3510 7.78009
October 744.00000 23.81539 59.05978 0.52342 10.96657
November 720.00000 23.67694 53.94725 0.42987 9.23839
December 744.00000 23.43386 51.47135 0.33829 8.21118
           
Annual Sum or Average 8760.00000 23.59696 57.58359 0.06538 8.40921
Minimum of Months 672.00000 23.29104 49.47169 -0.3874 7.39934
Maximum of Months 744.00000 23.81539 62.71488 0.52342 10.96657



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.43547 50.77918 -0.2324 7.10108
February 672.00000 21.48675 52.87037 -0.1843 6.92339
March 744.00000 21.45601 52.69831 -0.1892 6.87661
April 720.00000 21.63430 56.65057 -0.0642 5.92980
May 744.00000 21.72276 56.44955 -1.0695 30.58847
June 720.00000 21.73023 55.88648 -1.0519 29.85216
July 744.00000 21.73118 56.48853 -1.0473 29.65961
August 744.00000 21.72953 56.49814 -1.0488 29.74683
September 720.00000 21.72039 57.55589 -1.0617 30.34718
October 744.00000 21.69980 55.00446 -0.0134 5.96420
November 720.00000 21.62825 53.66990 -0.1028 6.16339
December 744.00000 21.47400 52.22158 -0.1926 6.98055
           
Annual Sum or Average 8760.00000 21.62119 54.73312 -0.5238 16.40293
Minimum of Months 672.00000 21.43547 50.77918 -1.0695 5.92980
Maximum of Months 744.00000 21.73118 57.55589 -0.0134 30.58847



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.16373 52.23404 -0.3314 8.21042
February 672.00000 21.28228 54.62863 -0.2591 7.58420
March 744.00000 21.35016 53.54398 -0.2301 7.14282
April 720.00000 21.59700 57.12460 -0.0810 5.92250
May 744.00000 21.72366 56.48884 -1.0710 30.63435
June 720.00000 21.73361 55.80735 -1.0482 29.68843
July 744.00000 21.73309 56.51465 -1.0457 29.58288
August 744.00000 21.72797 56.75077 -1.0553 29.98313
September 720.00000 21.71226 58.19655 -1.0779 30.96010
October 744.00000 21.65861 56.19689 -0.0413 5.90336
November 720.00000 21.47536 55.52161 -0.1685 6.37069
December 744.00000 21.26546 53.90747 -0.2733 7.66093
           
Annual Sum or Average 8760.00000 21.53631 55.57217 -0.5589 16.69387
Minimum of Months 672.00000 21.16373 52.23404 -1.0779 5.90336
Maximum of Months 744.00000 21.73361 58.19655 -0.0413 30.96010



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.10014 51.19464 -0.3608 8.11884
February 672.00000 21.16318 53.91767 -0.3135 7.51295
March 744.00000 21.23452 52.46648 -0.2901 7.13498
April 720.00000 21.39059 57.28410 -0.1936 6.07880
May 744.00000 21.59498 56.79169 -1.2369 37.69483
June 720.00000 21.63480 56.33488 -1.2150 36.74292
July 744.00000 21.63483 56.75094 -1.2109 36.57429
August 744.00000 21.61001 57.17350 -1.2254 37.20082
September 720.00000 21.55737 58.69647 -1.2463 38.11761
October 744.00000 21.48099 56.70083 -0.1588 5.91988
November 720.00000 21.26552 54.92583 -0.2608 6.68859
December 744.00000 21.16404 53.11709 -0.3192 7.53118
           
Annual Sum or Average 8760.00000 21.40390 55.44379 -0.6716 19.68389
Minimum of Months 672.00000 21.10014 51.19464 -1.2463 5.91988
Maximum of Months 744.00000 21.63483 58.69647 -0.1588 38.11761



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.48907 50.63721 -0.2235 6.98283
February 672.00000 21.53823 53.01637 -0.1758 6.81071
March 744.00000 21.53104 52.12708 -0.1700 6.80803
April 720.00000 21.68909 56.23110 -0.0537 5.96716
May 744.00000 21.74288 55.99226 -1.0511 29.90283
June 720.00000 21.74785 55.61193 -1.0380 29.35206
July 744.00000 21.74653 56.14239 -1.0306 29.04965
August 744.00000 21.74203 56.33783 -1.0413 29.49978
September 720.00000 21.73408 57.36182 -1.0566 30.18256
October 744.00000 21.71675 54.97307 -0.0109 5.98776
November 720.00000 21.67180 53.48046 -0.0931 6.12517
December 744.00000 21.49581 52.39045 -0.1945 6.96683
           
Annual Sum or Average 8760.00000 21.65409 54.52500 -0.5138 16.19353
Minimum of Months 672.00000 21.48907 50.63721 -1.0566 5.96716
Maximum of Months 744.00000 21.74785 57.36182 -0.0109 30.18256



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.20469 52.07441 -0.3256 8.00143
February 672.00000 21.33342 54.56969 -0.2522 7.37690
March 744.00000 21.44777 52.79526 -0.2071 7.00239
April 720.00000 21.67377 56.61038 -0.0665 5.94973
May 744.00000 21.74358 56.08462 -1.0524 29.94192
June 720.00000 21.74964 55.59112 -1.0345 29.20463
July 744.00000 21.74788 56.21261 -1.0290 28.97810
August 744.00000 21.74153 56.58563 -1.0475 29.72181
September 720.00000 21.72958 57.99683 -1.0716 30.74833
October 744.00000 21.68442 56.09672 -0.0372 5.92998
November 720.00000 21.50857 55.08915 -0.1619 6.26409
December 744.00000 21.26511 54.07684 -0.2807 7.65544
           
Annual Sum or Average 8760.00000 21.57005 55.31037 -0.5492 16.45403
Minimum of Months 672.00000 21.20469 52.07441 -1.0716 5.92998
Maximum of Months 744.00000 21.74964 57.99683 -0.0372 30.74833



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.36613 51.98221 -0.2700 7.73389
February 672.00000 21.43950 54.30803 -0.2079 7.39974
March 744.00000 21.41316 53.91920 -0.2101 7.32669
April 720.00000 21.62227 57.98019 -0.0644 6.06433
May 744.00000 21.71958 57.13553 -1.0612 30.39854
June 720.00000 21.72865 56.31723 -1.0408 29.57502
July 744.00000 21.72952 56.89785 -1.0378 29.42282
August 744.00000 21.72494 57.09580 -1.0413 29.59723
September 720.00000 21.71379 58.50241 -1.0585 30.36106
October 744.00000 21.68271 56.03679 -0.0174 6.08308
November 720.00000 21.59848 55.05980 -0.1203 6.40262
December 744.00000 21.41458 53.48682 -0.2240 7.52773
           
Annual Sum or Average 8760.00000 21.59663 55.72491 -0.5317 16.54815
Minimum of Months 672.00000 21.36613 51.98221 -1.0612 6.06433
Maximum of Months 744.00000 21.72952 58.50241 -0.0174 30.39854



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.07499 53.58801 -0.3764 9.16454
February 672.00000 21.22903 56.22145 -0.2870 8.21166
March 744.00000 21.30595 54.82927 -0.2529 7.65353
April 720.00000 21.58769 58.49853 -0.0813 6.05993
May 744.00000 21.72074 57.12494 -1.0629 30.45252
June 720.00000 21.73247 56.20207 -1.0370 29.41470
July 744.00000 21.73169 56.90747 -1.0361 29.34610
August 744.00000 21.72340 57.33173 -1.0481 29.83674
September 720.00000 21.70528 59.25136 -1.0748 30.96073
October 744.00000 21.63610 57.36416 -0.0472 6.03114
November 720.00000 21.42648 57.08422 -0.1942 6.73315
December 744.00000 21.18721 55.31476 -0.3128 8.43059
           
Annual Sum or Average 8760.00000 21.50617 56.63440 -0.5695 16.91329
Minimum of Months 672.00000 21.07499 53.58801 -1.0748 6.03114
Maximum of Months 744.00000 21.73247 59.25136 -0.0472 30.96073



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.60297 50.34319 -0.1597 6.76624
February 672.00000 21.61884 52.23378 -0.1363 6.70830
March 744.00000 21.51156 52.68202 -0.1805 6.89967
April 720.00000 21.62896 57.31248 -0.0919 6.05916
May 744.00000 21.70852 56.85188 -1.1228 32.94017
June 720.00000 21.71477 56.44882 -1.1136 32.54938
July 744.00000 21.71865 56.77485 -1.1030 32.08541
August 744.00000 21.71830 56.72466 -1.0975 31.90085
September 720.00000 21.71675 57.56611 -1.0942 31.84735
October 744.00000 21.71524 54.86465 -0.0168 6.09993
November 720.00000 21.68977 52.89288 -0.0692 6.26845
December 744.00000 21.60226 51.78283 -0.1342 6.78934
           
Annual Sum or Average 8760.00000 21.66230 54.71206 -0.5291 17.30820
Minimum of Months 672.00000 21.51156 50.34319 -1.1228 6.05916
Maximum of Months 744.00000 21.71865 57.56611 -0.0168 32.94017



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.65651 49.84279 0.39751 9.00305
February 672.00000 23.72334 52.97327 0.45206 10.00875
March 744.00000 23.76735 51.86026 0.47002 10.22565
April 720.00000 23.90113 58.48324 0.58826 12.50326
May 744.00000 23.97693 61.79827 -0.1576 5.54618
June 720.00000 23.98513 61.36805 -0.1422 5.44404
July 744.00000 23.98550 61.59104 -0.1409 5.43717
August 744.00000 23.97948 61.75388 -0.1503 5.49632
September 720.00000 23.96806 62.15295 -0.1688 5.65098
October 744.00000 23.93488 59.18017 0.62376 13.35814
November 720.00000 23.82859 54.31837 0.51357 10.92859
December 744.00000 23.70915 51.83752 0.44058 9.75426
           
Annual Sum or Average 8760.00000 23.86862 57.27866 0.22564 8.60136
Minimum of Months 672.00000 23.65651 49.84279 -0.1688 5.43717
Maximum of Months 744.00000 23.98550 62.15295 0.62376 13.35814



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.78415 48.86610 0.46187 10.01334
February 672.00000 23.83236 52.05457 0.51103 11.05444
March 744.00000 23.85969 50.99584 0.52480 11.23764
April 720.00000 23.94846 57.79702 0.62876 13.49401
May 744.00000 23.98918 61.32595 -0.1174 5.30933
June 720.00000 23.99172 60.93313 -0.1046 5.24895
July 744.00000 23.99191 61.15187 -0.1037 5.24424
August 744.00000 23.98984 61.30083 -0.1117 5.28076
September 720.00000 23.98460 61.65941 -0.1276 5.38295
October 744.00000 23.96209 58.63606 0.65539 14.18380
November 720.00000 23.89936 53.54728 0.55991 11.90103
December 744.00000 23.81520 50.94830 0.49779 10.73032
           
Annual Sum or Average 8760.00000 23.92105 56.61810 0.27129 9.07484
Minimum of Months 672.00000 23.78415 48.86610 -0.1276 5.24424
Maximum of Months 744.00000 23.99191 61.65941 0.65539 14.18380



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.83009 47.58292 1.10447 33.03987
February 672.00000 23.83647 50.75412 1.14835 34.94542
March 744.00000 23.87082 49.90224 1.16578 35.48670
April 720.00000 23.91576 56.75137 1.27126 40.07256
May 744.00000 23.96692 60.47151 0.82351 22.48796
June 720.00000 23.97188 60.16716 0.83999 23.07775
July 744.00000 23.97699 60.34959 0.84361 23.08104
August 744.00000 23.97304 60.45930 0.82995 22.62481
September 720.00000 23.96385 60.72033 0.80602 21.83582
October 744.00000 23.94206 57.65906 1.30610 41.67138
November 720.00000 23.86863 52.39059 1.19923 36.93385
December 744.00000 23.82665 49.70146 1.13218 34.14814
           
Annual Sum or Average 8760.00000 23.91235 55.59427 1.03842 30.75290
Minimum of Months 672.00000 23.82665 47.58292 0.80602 21.83582
Maximum of Months 744.00000 23.97699 60.72033 1.30610 41.67138



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.64305 47.07879 -0.1955 6.71165
February 672.00000 21.86466 50.52582 -0.1182 6.40258
March 744.00000 22.02838 49.29881 -0.0840 6.14958
April 720.00000 22.69178 56.09975 0.12858 5.80723
May 744.00000 23.57490 59.01061 -0.5706 11.91934
June 720.00000 23.75915 58.26284 -0.5069 10.46528
July 744.00000 23.80409 58.87182 -0.4854 10.02537
August 744.00000 23.77200 58.81103 -0.4990 10.26665
September 720.00000 23.60592 59.51414 -0.5541 11.56814
October 744.00000 23.41010 55.90364 0.31514 7.48066
November 720.00000 22.52607 51.23887 0.05617 5.75020
December 744.00000 22.01994 48.86440 -0.0883 6.34968
           
Annual Sum or Average 8760.00000 22.89733 54.46905 -0.2176 8.25476
Minimum of Months 672.00000 21.64305 47.07879 -0.5706 5.75020
Maximum of Months 744.00000 23.80409 59.51414 0.31514 11.91934



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.09860 49.59758 -0.0897 5.81535
February 672.00000 22.22258 53.08867 -0.0353 5.91904
March 744.00000 22.34792 52.00587 -0.0106 5.81739
April 720.00000 22.94937 58.62061 0.18505 6.08676
May 744.00000 23.70557 61.19176 -0.5441 11.26359
June 720.00000 23.81304 60.55960 -0.5078 10.43907
July 744.00000 23.84176 60.84941 -0.4947 10.16813
August 744.00000 23.82540 60.91972 -0.5012 10.28910
September 720.00000 23.75423 61.36126 -0.5238 10.83537
October 744.00000 23.65780 57.92646 0.36706 8.08279
November 720.00000 22.94468 53.55151 0.15186 5.97250
December 744.00000 22.41154 51.37250 0.00196 5.99407
           
Annual Sum or Average 8760.00000 23.13594 56.76448 -0.1678 8.07147
Minimum of Months 672.00000 22.09860 49.59758 -0.5441 5.81535
Maximum of Months 744.00000 23.84176 61.36126 0.36706 11.26359



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.81416 47.65816 -0.1347 6.52109
February 672.00000 22.07489 50.80556 -0.0454 6.43346
March 744.00000 22.21253 49.63920 -0.0159 6.25332
April 720.00000 22.96028 55.87998 0.22225 6.68002
May 744.00000 23.77842 58.02907 -0.4518 9.38226
June 720.00000 23.87257 57.41418 -0.4148 8.67368
July 744.00000 23.88557 57.74040 -0.4073 8.53846
August 744.00000 23.86310 57.84647 -0.4177 8.72096
September 720.00000 23.75720 58.45296 -0.4571 9.52746
October 744.00000 23.56191 55.36397 0.38401 8.62590
November 720.00000 22.69349 51.46136 0.12309 6.22367
December 744.00000 22.15641 49.33769 -0.0333 6.57024
           
Annual Sum or Average 8760.00000 23.05764 54.14486 -0.1382 7.68839
Minimum of Months 672.00000 21.81416 47.65816 -0.4571 6.22367
Maximum of Months 744.00000 23.88557 58.45296 0.38401 9.52746



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.77328 46.21730 -0.1587 6.48457
February 672.00000 21.99084 49.60012 -0.0817 6.31669
March 744.00000 22.17102 48.32184 -0.0432 6.09351
April 720.00000 22.84554 54.94301 0.17301 6.13394
May 744.00000 23.66141 57.75690 -0.5243 10.88661
June 720.00000 23.79947 57.10439 -0.4734 9.78657
July 744.00000 23.83692 57.62858 -0.4550 9.42427
August 744.00000 23.81358 57.58314 -0.4658 9.61181
September 720.00000 23.68278 58.21824 -0.5117 10.63882
October 744.00000 23.50239 54.74266 0.34679 7.90099
November 720.00000 22.65937 50.21799 0.09505 5.91507
December 744.00000 22.15230 47.92486 -0.0503 6.28769
           
Annual Sum or Average 8760.00000 22.99615 53.36643 -0.1799 7.96842
Minimum of Months 672.00000 21.77328 46.21730 -0.5243 5.91507
Maximum of Months 744.00000 23.83692 58.21824 0.34679 10.88661



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.742339E+11 151879.88 19-JAN-19:03 609.57 0.234079E+12 0.00 0.308313E+12 2.56 4.11 19-JAN-21:40 0.00 0.00
February 0.935277E+11 144137.48 02-FEB-19:03 586.47 0.293351E+12 0.00 0.386878E+12 2.71 4.04 02-FEB-19:03 0.00 0.00
March 0.118668E+12 160221.70 07-MAR-19:03 646.12 0.375722E+12 0.00 0.494390E+12 2.70 4.07 07-MAR-19:03 0.00 0.00
April 0.198204E+12 185116.74 28-APR-16:00 717.42 0.636012E+12 0.00 0.834215E+12 3.12 4.01 06-APR-18:03 0.00 0.00
May 0.348799E+12 196862.72 01-MAY-15:03 744.00 0.114899E+13 0.00 0.149779E+13 3.30 4.04 19-MAY-19:20 0.00 0.00
June 0.357291E+12 214668.17 28-JUN-18:05 720.00 0.117069E+13 0.00 0.152798E+13 3.28 4.00 06-JUN-20:00 0.00 0.00
July 0.396262E+12 229255.76 22-JUL-16:10 744.00 0.131462E+13 0.00 0.171088E+13 3.33 4.00 11-JUL-20:50 0.00 0.00
August 0.381943E+12 230699.89 24-AUG-18:03 744.00 0.127425E+13 0.00 0.165619E+13 3.35 4.18 16-AUG-18:03 0.00 0.00
September 0.353012E+12 245003.23 09-SEP-18:03 720.00 0.120659E+13 0.00 0.155960E+13 3.43 4.20 07-SEP-18:03 0.00 0.00
October 0.296737E+12 208376.44 07-OCT-08:03 742.92 0.993118E+12 0.00 0.128986E+13 3.28 4.15 21-OCT-18:03 0.00 0.00
November 0.152334E+12 180820.31 02-NOV-15:03 704.83 0.493673E+12 0.00 0.646007E+12 3.06 4.08 11-NOV-19:03 0.00 0.00
December 0.110798E+12 157263.56 15-DEC-21:20 635.21 0.366298E+12 0.00 0.477095E+12 2.72 4.13 14-DEC-19:03 0.00 0.00
                         
Annual Sum or Average 0.288181E+13     8314.53 0.950738E+13 0.00 0.123892E+14 3.07     0.00 0.00
Minimum of Months 0.742339E+11 144137.48   586.47 0.234079E+12 0.00 0.308313E+12 2.56 4.00   0.00 0.00
Maximum of Months 0.396262E+12 245003.23   744.00 0.131462E+13 0.00 0.171088E+13 3.43 4.20   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.272285E+11 0.00 475.14 138535.34 21-JAN-19:02 0.00 54.58 71.47 0.09 0.00 0.04 0.49 21-JAN-19:02
February 0.151055E+11 0.00 332.34 113336.61 04-FEB-09:02 0.00 54.33 66.75 0.06 0.00 0.02 0.40 04-FEB-09:02
March 0.147368E+11 0.00 304.73 117945.61 12-MAR-08:02 0.00 57.33 68.21 0.05 0.00 0.02 0.42 12-MAR-08:02
April 0.112600E+10 0.00 71.05 73603.23 11-APR-05:49 0.00 48.54 51.84 0.00 0.00 0.00 0.26 11-APR-05:49
May 35566494.21 0.00 2.17 24505.83 01-MAY-08:05 0.00 56.28 56.35 0.00 0.00 0.00 0.09 01-MAY-08:05
June 27983506.95 0.00 1.25 13638.67 21-JUN-08:07 0.00 56.77 56.81 0.00 0.00 0.00 0.05 21-JUN-08:07
July 21217883.36 0.00 0.94 19745.34 14-JUL-08:05 0.00 56.47 56.50 0.00 0.00 0.00 0.07 14-JUL-08:05
August 23955757.29 0.00 1.28 17769.71 17-AUG-08:05 0.00 57.33 57.37 0.00 0.00 0.00 0.06 17-AUG-08:05
September 35406897.62 0.00 1.39 19049.68 08-SEP-08:05 0.00 58.57 58.61 0.00 0.00 0.00 0.07 08-SEP-08:05
October 0.902603E+09 0.00 35.41 70689.66 28-OCT-06:20 0.00 56.73 58.09 0.00 0.00 0.00 0.25 28-OCT-06:20
November 0.734939E+10 0.00 214.50 100964.74 12-NOV-08:63 0.00 57.41 64.92 0.02 0.00 0.01 0.36 12-NOV-08:63
December 0.195498E+11 0.00 401.08 131835.05 30-DEC-16:02 0.00 56.09 69.51 0.06 0.00 0.03 0.46 30-DEC-16:02
                           
Annual Sum or Average 0.861428E+11 0.00 1841.29     0.00 55.89 61.36 0.02 0.00 0.01    
Minimum of Months 21217883.36 0.00 0.94 13638.67   0.00 48.54 51.84 0.00 0.00 0.00 0.05  
Maximum of Months 0.272285E+11 0.00 475.14 138535.34   0.00 58.57 71.47 0.09 0.00 0.04 0.49  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.150064E+12 0.00 400.45 0.914167E+11 0.00 0.00 0.00 0.00 400414.13 19-JAN-22:00 194317.40 01-JAN-14:00 0.00 0.00 0.00
February 0.195572E+12 0.00 452.41 0.115807E+12 0.00 0.00 0.00 0.00 366034.69 02-FEB-22:00 185581.99 26-FEB-11:33 0.00 0.00 0.00
March 0.259171E+12 0.00 537.56 0.167162E+12 0.00 0.00 0.00 0.00 408874.19 07-MAR-20:00 227049.85 24-MAR-17:10 0.00 0.00 0.00
April 0.450998E+12 0.00 667.30 0.279947E+12 0.00 0.00 0.00 0.00 503604.72 28-APR-21:00 222631.42 18-APR-13:40 0.00 0.00 0.00
May 0.845706E+12 0.00 744.00 0.483209E+12 0.00 0.00 0.00 0.00 505307.65 19-MAY-20:30 259619.99 25-MAY-19:10 0.00 0.00 0.00
June 0.859748E+12 0.00 720.00 0.486952E+12 0.00 0.00 0.00 0.00 552888.70 29-JUN-22:00 269889.82 28-JUN-18:05 0.00 0.00 0.00
July 0.974225E+12 0.00 744.00 0.512778E+12 0.00 0.00 0.00 0.00 486978.86 22-JUL-10:33 271193.28 07-JUL-19:10 0.00 0.00 0.00
August 0.942656E+12 0.00 744.00 0.507113E+12 0.00 0.00 0.00 0.00 534199.18 09-AUG-20:20 289650.23 24-AUG-20:10 0.00 0.00 0.00
September 0.897075E+12 0.00 720.00 0.464315E+12 0.00 0.00 0.00 0.00 512252.87 09-SEP-21:00 288184.56 09-SEP-21:00 0.00 0.00 0.00
October 0.714975E+12 0.00 715.75 0.410419E+12 0.00 0.00 0.00 0.00 542942.11 23-OCT-20:50 266552.28 05-OCT-18:20 0.00 0.00 0.00
November 0.337237E+12 0.00 595.11 0.212749E+12 0.00 0.00 0.00 0.00 529079.14 03-NOV-19:20 234299.32 02-NOV-20:10 0.00 0.00 0.00
December 0.247057E+12 0.00 467.70 0.143001E+12 0.00 0.00 0.00 0.00 470669.52 15-DEC-22:00 209764.29 15-DEC-22:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.687448E+13 0.00 7508.27 0.387487E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.150064E+12 0.00 400.45 0.914167E+11 0.00 0.00 0.00 0.00 366034.69   185581.99   0.00 0.00 0.00
Maximum of Months 0.974225E+12 0.00 744.00 0.512778E+12 0.00 0.00 0.00 0.00 552888.70   289650.23   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.303380E+11 0.00 329.33 0.176038E+11 0.00 0.00 0.00 0.00 66456.58 20-JAN-03:00 30014.70 02-JAN-15:00 0.00 0.00 0.00
February 0.386865E+11 0.00 419.67 0.220218E+11 0.00 0.00 0.00 0.00 62715.68 02-FEB-23:00 30816.16 02-FEB-13:00 0.00 0.00 0.00
March 0.513335E+11 0.00 507.00 0.315313E+11 0.00 0.00 0.00 0.00 68410.67 07-MAR-19:02 32505.70 26-MAR-14:00 0.00 0.00 0.00
April 0.852135E+11 0.00 664.83 0.510933E+11 0.00 0.00 0.00 0.00 72709.38 24-APR-09:40 35209.70 28-APR-15:00 0.00 0.00 0.00
May 0.133116E+12 0.00 744.00 0.785760E+11 0.00 0.00 0.00 0.00 68049.66 31-MAY-13:00 35737.28 07-MAY-14:00 0.00 0.00 0.00
June 0.133945E+12 0.00 720.00 0.773648E+11 0.00 0.00 0.00 0.00 67058.15 27-JUN-15:00 36445.35 14-JUN-14:00 0.00 0.00 0.00
July 0.150941E+12 0.00 744.00 0.807724E+11 0.00 0.00 0.00 0.00 67618.10 22-JUL-11:00 36839.18 22-JUL-15:02 0.00 0.00 0.00
August 0.145052E+12 0.00 744.00 0.796453E+11 0.00 0.00 0.00 0.00 74811.01 09-AUG-05:40 36593.03 03-AUG-15:02 0.00 0.00 0.00
September 0.138064E+12 0.00 720.00 0.748120E+11 0.00 0.00 0.00 0.00 75162.02 26-SEP-08:00 37328.19 10-SEP-14:00 0.00 0.00 0.00
October 0.113915E+12 0.00 713.50 0.669701E+11 0.00 0.00 0.00 0.00 84131.07 22-OCT-08:00 35833.62 05-OCT-15:00 0.00 0.00 0.00
November 0.608934E+11 0.00 577.17 0.384690E+11 0.00 0.00 0.00 0.00 79982.23 03-NOV-07:40 32783.36 01-NOV-14:00 0.00 0.00 0.00
December 0.479885E+11 0.00 410.33 0.266710E+11 0.00 0.00 0.00 0.00 75610.67 15-DEC-09:04 32363.60 13-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.112949E+13 0.00 7293.83 0.645531E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.303380E+11 0.00 329.33 0.176038E+11 0.00 0.00 0.00 0.00 62715.68   30014.70   0.00 0.00 0.00
Maximum of Months 0.150941E+12 0.00 744.00 0.807724E+11 0.00 0.00 0.00 0.00 84131.07   37328.19   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.245299E+10 0.00 348.65 0.136671E+10 0.00 0.00 0.00 0.00 15405.01 19-JAN-19:02 12419.00 18-JAN-16:02 0.00 0.00 0.00
February 0.322402E+10 0.00 402.71 0.170909E+10 0.00 0.00 0.00 0.00 15096.94 02-FEB-19:02 12570.41 23-FEB-16:02 0.00 0.00 0.00
March 0.371550E+10 0.00 454.83 0.206023E+10 0.00 0.00 0.00 0.00 16313.07 07-MAR-19:02 12723.98 03-MAR-16:02 0.00 0.00 0.00
April 0.644210E+10 0.00 609.58 0.366624E+10 0.00 0.00 0.00 0.00 15523.50 28-APR-08:62 13057.33 17-APR-15:02 0.00 0.00 0.00
May 0.103960E+11 0.00 693.16 0.619190E+10 0.00 0.00 0.00 0.00 15337.50 22-MAY-15:02 12855.75 25-MAY-15:02 0.00 0.00 0.00
June 0.109559E+11 0.00 678.31 0.674502E+10 0.00 0.00 0.00 0.00 14953.68 19-JUN-08:62 12873.17 05-JUN-15:02 0.00 0.00 0.00
July 0.115435E+11 0.00 701.39 0.701946E+10 0.00 0.00 0.00 0.00 15406.54 15-JUL-08:62 12825.78 23-JUL-15:02 0.00 0.00 0.00
August 0.114280E+11 0.00 699.61 0.693005E+10 0.00 0.00 0.00 0.00 15629.71 29-AUG-08:62 12823.80 26-AUG-15:02 0.00 0.00 0.00
September 0.102778E+11 0.00 669.13 0.601090E+10 0.00 0.00 0.00 0.00 17057.87 05-SEP-08:62 12735.09 17-SEP-15:02 0.00 0.00 0.00
October 0.970978E+10 0.00 676.43 0.597245E+10 0.00 0.00 0.00 0.00 15870.35 22-OCT-08:62 12855.33 24-OCT-15:02 0.00 0.00 0.00
November 0.506816E+10 0.00 579.59 0.288507E+10 0.00 0.00 0.00 0.00 15863.30 02-NOV-08:62 12719.43 03-NOV-15:02 0.00 0.00 0.00
December 0.359237E+10 0.00 431.62 0.201168E+10 0.00 0.00 0.00 0.00 15786.38 12-DEC-09:02 12862.05 14-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.888061E+11 0.00 6945.00 0.525688E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.245299E+10 0.00 348.65 0.136671E+10 0.00 0.00 0.00 0.00 14953.68   12419.00   0.00 0.00 0.00
Maximum of Months 0.115435E+11 0.00 701.39 0.701946E+10 0.00 0.00 0.00 0.00 17057.87   13057.33   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.129560E+10 0.00 211.88 0.598324E+09 0.00 0.00 0.00 0.00 14924.69 19-JAN-19:02 12017.48 01-JAN-16:02 0.00 0.00 0.00
February 0.199250E+10 0.00 298.28 0.924384E+09 0.00 0.00 0.00 0.00 13950.72 02-FEB-16:02 12100.22 25-FEB-16:02 0.00 0.00 0.00
March 0.283019E+10 0.00 395.06 0.146120E+10 0.00 0.00 0.00 0.00 15762.10 07-MAR-19:02 12383.91 03-MAR-16:02 0.00 0.00 0.00
April 0.586303E+10 0.00 581.66 0.328906E+10 0.00 0.00 0.00 0.00 15106.66 28-APR-08:62 12708.34 17-APR-15:02 0.00 0.00 0.00
May 0.103004E+11 0.00 693.83 0.618840E+10 0.00 0.00 0.00 0.00 14926.59 22-MAY-15:02 12499.60 19-MAY-15:02 0.00 0.00 0.00
June 0.110990E+11 0.00 681.57 0.696523E+10 0.00 0.00 0.00 0.00 14524.72 06-JUN-08:62 12519.06 05-JUN-15:02 0.00 0.00 0.00
July 0.115759E+11 0.00 702.19 0.711453E+10 0.00 0.00 0.00 0.00 14911.45 15-JUL-08:62 12489.67 23-JUL-15:02 0.00 0.00 0.00
August 0.110783E+11 0.00 697.33 0.670057E+10 0.00 0.00 0.00 0.00 14900.63 29-AUG-08:62 12464.55 01-AUG-15:02 0.00 0.00 0.00
September 0.952174E+10 0.00 660.67 0.545487E+10 0.00 0.00 0.00 0.00 16838.65 05-SEP-08:62 12481.42 09-SEP-15:02 0.00 0.00 0.00
October 0.818220E+10 0.00 642.60 0.474670E+10 0.00 0.00 0.00 0.00 15695.32 22-OCT-08:62 12465.82 01-OCT-15:02 0.00 0.00 0.00
November 0.317693E+10 0.00 461.20 0.156240E+10 0.00 0.00 0.00 0.00 15283.50 02-NOV-08:62 12393.69 06-NOV-16:02 0.00 0.00 0.00
December 0.208113E+10 0.00 299.48 0.981980E+09 0.00 0.00 0.00 0.00 15345.67 12-DEC-09:02 12315.78 15-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.789969E+11 0.00 6325.74 0.459877E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.129560E+10 0.00 211.88 0.598324E+09 0.00 0.00 0.00 0.00 13950.72   12017.48   0.00 0.00 0.00
Maximum of Months 0.115759E+11 0.00 702.19 0.711453E+10 0.00 0.00 0.00 0.00 16838.65   12708.34   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.179845E+11 0.00 382.46 0.130108E+11 0.00 0.00 0.00 0.00 47841.27 01-JAN-14:00 40469.31 01-JAN-14:00 0.00 0.00 0.00
February 0.164022E+11 0.00 340.08 0.102082E+11 0.00 0.00 0.00 0.00 38902.33 27-FEB-15:50 31328.59 24-FEB-12:50 0.00 0.00 0.00
March 0.104892E+11 0.00 271.54 0.520028E+10 0.00 0.00 0.00 0.00 32243.48 06-MAR-13:10 24940.02 05-MAR-13:30 0.00 0.00 0.00
April 0.131914E+11 0.00 389.17 0.542975E+10 0.00 0.00 0.00 0.00 23463.91 22-APR-13:30 14439.74 22-APR-13:40 0.00 0.00 0.00
May 0.294625E+11 0.00 693.47 0.124258E+11 0.00 0.00 0.00 0.00 26780.01 05-MAY-07:00 14651.00 04-MAY-16:20 0.00 0.00 0.00
June 0.302850E+11 0.00 689.58 0.129562E+11 0.00 0.00 0.00 0.00 24680.94 28-JUN-17:20 14757.84 28-JUN-17:20 0.00 0.00 0.00
July 0.346643E+11 0.00 723.75 0.154419E+11 0.00 0.00 0.00 0.00 27319.13 19-JUL-17:20 17990.66 19-JUL-17:20 0.00 0.00 0.00
August 0.375072E+11 0.00 725.54 0.178198E+11 0.00 0.00 0.00 0.00 30558.92 31-AUG-13:30 22234.73 31-AUG-13:30 0.00 0.00 0.00
September 0.376694E+11 0.00 680.33 0.189586E+11 0.00 0.00 0.00 0.00 40282.72 10-SEP-16:00 31177.01 24-SEP-13:00 0.00 0.00 0.00
October 0.441847E+11 0.00 664.56 0.268437E+11 0.00 0.00 0.00 0.00 42854.28 07-OCT-13:00 31300.84 09-OCT-10:50 0.00 0.00 0.00
November 0.307745E+11 0.00 514.64 0.207902E+11 0.00 0.00 0.00 0.00 45829.99 06-NOV-14:00 36618.72 06-NOV-14:00 0.00 0.00 0.00
December 0.242843E+11 0.00 412.35 0.166864E+11 0.00 0.00 0.00 0.00 49576.34 16-DEC-13:30 41315.74 10-DEC-14:30 0.00 0.00 0.00
                               
Annual Sum or Average 0.326899E+12 0.00 6487.47 0.175772E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.104892E+11 0.00 271.54 0.520028E+10 0.00 0.00 0.00 0.00 23463.91   14439.74   0.00 0.00 0.00
Maximum of Months 0.441847E+11 0.00 725.54 0.268437E+11 0.00 0.00 0.00 0.00 49576.34   41315.74   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.961707E+10 0.00 260.47 0.401087E+10 0.00 0.00 0.00 0.00 89047.85 19-JAN-19:02 64672.92 02-JAN-16:02 0.00 0.00 0.00
February 0.139436E+11 0.00 331.79 0.597838E+10 0.00 0.00 0.00 0.00 83052.40 02-FEB-19:02 64654.34 25-FEB-16:02 0.00 0.00 0.00
March 0.214973E+11 0.00 421.73 0.113024E+11 0.00 0.00 0.00 0.00 95041.24 07-MAR-19:02 67841.33 26-MAR-18:02 0.00 0.00 0.00
April 0.376262E+11 0.00 508.09 0.210330E+11 0.00 0.00 0.00 0.00 88339.08 28-APR-08:62 70688.22 22-APR-18:02 0.00 0.00 0.00
May 0.655466E+11 0.00 551.88 0.432583E+11 0.00 0.00 0.00 0.00 83558.78 27-MAY-15:02 72023.36 11-MAY-18:02 0.00 0.00 0.00
June 0.690815E+11 0.00 561.89 0.474776E+11 0.00 0.00 0.00 0.00 84550.42 07-JUN-08:62 72363.57 13-JUN-18:02 0.00 0.00 0.00
July 0.726342E+11 0.00 587.78 0.495076E+11 0.00 0.00 0.00 0.00 90490.74 12-JUL-18:02 71086.11 04-JUL-08:62 0.00 0.00 0.00
August 0.687616E+11 0.00 565.78 0.458597E+11 0.00 0.00 0.00 0.00 87266.79 27-AUG-08:62 71651.11 30-AUG-18:02 0.00 0.00 0.00
September 0.609131E+11 0.00 519.92 0.374097E+11 0.00 0.00 0.00 0.00 102548.73 05-SEP-08:62 71171.54 06-SEP-18:02 0.00 0.00 0.00
October 0.508961E+11 0.00 529.55 0.311464E+11 0.00 0.00 0.00 0.00 93177.59 22-OCT-08:62 71482.49 05-OCT-18:02 0.00 0.00 0.00
November 0.226216E+11 0.00 464.13 0.113970E+11 0.00 0.00 0.00 0.00 90146.66 01-NOV-08:62 68611.73 01-NOV-18:02 0.00 0.00 0.00
December 0.147480E+11 0.00 350.99 0.708317E+10 0.00 0.00 0.00 0.00 91386.91 12-DEC-09:02 65647.08 15-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.507887E+12 0.00 5653.98 0.315464E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.961707E+10 0.00 260.47 0.401087E+10 0.00 0.00 0.00 0.00 83052.40   64654.34   0.00 0.00 0.00
Maximum of Months 0.726342E+11 0.00 587.78 0.495076E+11 0.00 0.00 0.00 0.00 102548.73   72363.57   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.225435E+10 0.00 336.51 0.123898E+10 0.00 0.00 0.00 0.00 13932.07 19-JAN-19:02 11268.97 01-JAN-16:02 0.00 0.00 0.00
February 0.288799E+10 0.00 405.29 0.147999E+10 0.00 0.00 0.00 0.00 13586.81 02-FEB-19:02 11151.96 27-FEB-16:02 0.00 0.00 0.00
March 0.390543E+10 0.00 480.92 0.220050E+10 0.00 0.00 0.00 0.00 14659.49 07-MAR-19:02 11434.84 03-MAR-16:02 0.00 0.00 0.00
April 0.635130E+10 0.00 645.44 0.359219E+10 0.00 0.00 0.00 0.00 13884.75 28-APR-08:62 11734.45 17-APR-15:02 0.00 0.00 0.00
May 0.110161E+11 0.00 714.20 0.683346E+10 0.00 0.00 0.00 0.00 13772.82 22-MAY-15:02 11549.86 19-MAY-15:02 0.00 0.00 0.00
June 0.113391E+11 0.00 696.17 0.713437E+10 0.00 0.00 0.00 0.00 13166.65 02-JUN-08:62 11459.35 30-JUN-15:02 0.00 0.00 0.00
July 0.121572E+11 0.00 717.50 0.770256E+10 0.00 0.00 0.00 0.00 13588.72 12-JUL-18:02 11501.17 18-JUL-15:02 0.00 0.00 0.00
August 0.116001E+11 0.00 713.89 0.719375E+10 0.00 0.00 0.00 0.00 13527.87 29-AUG-08:62 11478.39 19-AUG-15:02 0.00 0.00 0.00
September 0.103296E+11 0.00 681.13 0.617297E+10 0.00 0.00 0.00 0.00 15380.48 05-SEP-08:62 11464.36 03-SEP-15:02 0.00 0.00 0.00
October 0.962152E+10 0.00 692.19 0.599322E+10 0.00 0.00 0.00 0.00 14317.32 22-OCT-08:62 11517.09 02-OCT-15:02 0.00 0.00 0.00
November 0.504960E+10 0.00 594.06 0.292474E+10 0.00 0.00 0.00 0.00 14064.85 02-NOV-08:62 11409.65 06-NOV-16:02 0.00 0.00 0.00
December 0.318738E+10 0.00 420.04 0.173247E+10 0.00 0.00 0.00 0.00 14192.58 12-DEC-09:02 11520.33 10-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.896997E+11 0.00 7097.34 0.541992E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.225435E+10 0.00 336.51 0.123898E+10 0.00 0.00 0.00 0.00 13166.65   11151.96   0.00 0.00 0.00
Maximum of Months 0.121572E+11 0.00 717.50 0.770256E+10 0.00 0.00 0.00 0.00 15380.48   11734.45   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.108851E+10 0.00 206.64 0.456250E+09 0.00 0.00 0.00 0.00 13528.90 19-JAN-09:02 10524.21 01-JAN-16:02 0.00 0.00 0.00
February 0.165014E+10 0.00 291.43 0.738880E+09 0.00 0.00 0.00 0.00 13232.62 24-FEB-09:02 10344.78 26-FEB-16:02 0.00 0.00 0.00
March 0.297779E+10 0.00 414.09 0.157753E+10 0.00 0.00 0.00 0.00 14298.14 07-MAR-19:02 11139.29 24-MAR-15:02 0.00 0.00 0.00
April 0.573706E+10 0.00 608.32 0.320049E+10 0.00 0.00 0.00 0.00 13583.41 28-APR-08:62 11453.49 17-APR-15:02 0.00 0.00 0.00
May 0.109154E+11 0.00 714.28 0.680405E+10 0.00 0.00 0.00 0.00 13444.04 22-MAY-15:02 11250.56 03-MAY-15:02 0.00 0.00 0.00
June 0.114806E+11 0.00 697.90 0.734495E+10 0.00 0.00 0.00 0.00 13144.94 07-JUN-08:62 11160.43 30-JUN-15:02 0.00 0.00 0.00
July 0.121818E+11 0.00 718.42 0.778177E+10 0.00 0.00 0.00 0.00 13162.24 12-JUL-18:02 11246.45 18-JUL-15:02 0.00 0.00 0.00
August 0.112471E+11 0.00 712.61 0.693181E+10 0.00 0.00 0.00 0.00 13190.45 16-AUG-18:02 11171.98 21-AUG-15:02 0.00 0.00 0.00
September 0.956250E+10 0.00 676.52 0.554958E+10 0.00 0.00 0.00 0.00 15229.13 05-SEP-08:62 11154.30 10-SEP-15:02 0.00 0.00 0.00
October 0.806815E+10 0.00 653.31 0.469821E+10 0.00 0.00 0.00 0.00 14219.08 22-OCT-08:62 11090.93 11-OCT-15:02 0.00 0.00 0.00
November 0.317894E+10 0.00 456.68 0.161136E+10 0.00 0.00 0.00 0.00 13860.08 02-NOV-08:62 10808.36 05-NOV-18:02 0.00 0.00 0.00
December 0.169884E+10 0.00 279.79 0.762774E+09 0.00 0.00 0.00 0.00 13837.40 12-DEC-09:02 10554.99 09-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.797868E+11 0.00 6429.99 0.474577E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.108851E+10 0.00 206.64 0.456250E+09 0.00 0.00 0.00 0.00 13144.94   10344.78   0.00 0.00 0.00
Maximum of Months 0.121818E+11 0.00 718.42 0.778177E+10 0.00 0.00 0.00 0.00 15229.13   11453.49   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.539117E+09 0.00 277.53 0.299675E+09 0.00 0.00 0.00 0.00 4163.95 19-JAN-19:02 3293.52 18-JAN-16:02 0.00 0.00 0.00
February 0.733649E+09 0.00 347.38 0.394158E+09 0.00 0.00 0.00 0.00 4069.22 02-FEB-19:02 3306.89 01-FEB-16:02 0.00 0.00 0.00
March 0.866155E+09 0.00 408.63 0.480114E+09 0.00 0.00 0.00 0.00 4398.59 07-MAR-19:02 3349.12 03-MAR-16:02 0.00 0.00 0.00
April 0.157229E+10 0.00 582.93 0.895115E+09 0.00 0.00 0.00 0.00 4230.79 28-APR-08:62 3436.87 17-APR-15:02 0.00 0.00 0.00
May 0.265378E+10 0.00 692.03 0.155169E+10 0.00 0.00 0.00 0.00 4155.17 14-MAY-08:62 3361.65 10-MAY-18:02 0.00 0.00 0.00
June 0.282906E+10 0.00 678.12 0.172362E+10 0.00 0.00 0.00 0.00 4056.46 01-JUN-08:62 3381.56 02-JUN-15:02 0.00 0.00 0.00
July 0.296520E+10 0.00 700.50 0.178055E+10 0.00 0.00 0.00 0.00 4219.39 15-JUL-08:62 3373.62 16-JUL-15:02 0.00 0.00 0.00
August 0.291649E+10 0.00 697.65 0.173868E+10 0.00 0.00 0.00 0.00 4269.64 29-AUG-08:62 3358.57 03-AUG-18:02 0.00 0.00 0.00
September 0.257559E+10 0.00 666.72 0.146821E+10 0.00 0.00 0.00 0.00 4676.86 05-SEP-08:62 3374.15 22-SEP-18:02 0.00 0.00 0.00
October 0.236822E+10 0.00 658.70 0.141353E+10 0.00 0.00 0.00 0.00 4367.68 21-OCT-08:62 3370.62 23-OCT-15:02 0.00 0.00 0.00
November 0.112492E+10 0.00 512.58 0.625795E+09 0.00 0.00 0.00 0.00 4326.38 02-NOV-08:62 3328.16 03-NOV-15:02 0.00 0.00 0.00
December 0.805156E+09 0.00 364.56 0.444856E+09 0.00 0.00 0.00 0.00 4230.42 15-DEC-09:02 3334.17 14-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.219496E+11 0.00 6587.33 0.128160E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.539117E+09 0.00 277.53 0.299675E+09 0.00 0.00 0.00 0.00 4056.46   3293.52   0.00 0.00 0.00
Maximum of Months 0.296520E+10 0.00 700.50 0.178055E+10 0.00 0.00 0.00 0.00 4676.86   3436.87   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.266247E+09 0.00 176.56 0.123162E+09 0.00 0.00 0.00 0.00 4002.94 19-JAN-19:02 3176.95 01-JAN-16:02 0.00 0.00 0.00
February 0.425670E+09 0.00 254.57 0.201752E+09 0.00 0.00 0.00 0.00 3735.78 02-FEB-19:02 3217.94 27-FEB-16:02 0.00 0.00 0.00
March 0.642004E+09 0.00 348.59 0.330178E+09 0.00 0.00 0.00 0.00 4241.80 07-MAR-19:02 3256.26 03-MAR-16:02 0.00 0.00 0.00
April 0.142063E+10 0.00 552.45 0.797293E+09 0.00 0.00 0.00 0.00 4115.23 28-APR-08:62 3341.59 17-APR-15:02 0.00 0.00 0.00
May 0.262927E+10 0.00 692.74 0.155327E+10 0.00 0.00 0.00 0.00 4022.28 14-MAY-08:62 3289.34 14-MAY-18:02 0.00 0.00 0.00
June 0.286764E+10 0.00 680.44 0.178365E+10 0.00 0.00 0.00 0.00 3967.06 06-JUN-08:62 3290.76 07-JUN-18:02 0.00 0.00 0.00
July 0.297425E+10 0.00 701.44 0.180460E+10 0.00 0.00 0.00 0.00 4073.21 15-JUL-08:62 3279.44 16-JUL-15:02 0.00 0.00 0.00
August 0.282577E+10 0.00 695.93 0.167695E+10 0.00 0.00 0.00 0.00 4091.63 27-AUG-08:62 3286.10 09-AUG-15:02 0.00 0.00 0.00
September 0.237654E+10 0.00 660.08 0.131145E+10 0.00 0.00 0.00 0.00 4610.33 05-SEP-08:62 3285.91 19-SEP-15:02 0.00 0.00 0.00
October 0.197165E+10 0.00 622.04 0.110191E+10 0.00 0.00 0.00 0.00 4322.93 22-OCT-08:62 3277.73 09-OCT-15:02 0.00 0.00 0.00
November 0.664214E+09 0.00 366.10 0.319865E+09 0.00 0.00 0.00 0.00 4165.29 02-NOV-08:62 3211.48 09-NOV-16:02 0.00 0.00 0.00
December 0.446131E+09 0.00 234.90 0.205086E+09 0.00 0.00 0.00 0.00 4124.27 15-DEC-09:02 3269.03 15-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.195100E+11 0.00 5985.82 0.112092E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.266247E+09 0.00 176.56 0.123162E+09 0.00 0.00 0.00 0.00 3735.78   3176.95   0.00 0.00 0.00
Maximum of Months 0.297425E+10 0.00 701.44 0.180460E+10 0.00 0.00 0.00 0.00 4610.33   3341.59   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.684473E+10 0.00 502.21 0.484624E+10 0.00 0.00 0.00 0.00 19170.75 19-JAN-19:02 15047.05 16-JAN-16:02 0.00 0.00 0.00
February 0.687982E+10 0.00 496.33 0.440290E+10 0.00 0.00 0.00 0.00 19242.61 02-FEB-19:02 14918.00 28-FEB-16:02 0.00 0.00 0.00
March 0.619789E+10 0.00 496.35 0.376465E+10 0.00 0.00 0.00 0.00 20597.92 07-MAR-19:02 15172.74 03-MAR-16:02 0.00 0.00 0.00
April 0.804406E+10 0.00 608.60 0.447212E+10 0.00 0.00 0.00 0.00 19144.54 15-APR-08:62 15268.02 14-APR-15:02 0.00 0.00 0.00
May 0.129331E+11 0.00 679.42 0.773967E+10 0.00 0.00 0.00 0.00 18060.24 05-MAY-08:62 15317.93 03-MAY-15:02 0.00 0.00 0.00
June 0.131165E+11 0.00 662.96 0.795307E+10 0.00 0.00 0.00 0.00 17716.40 06-JUN-08:62 15185.53 12-JUN-15:02 0.00 0.00 0.00
July 0.142597E+11 0.00 686.94 0.872908E+10 0.00 0.00 0.00 0.00 18701.13 12-JUL-18:02 15298.55 07-JUL-15:02 0.00 0.00 0.00
August 0.146961E+11 0.00 686.73 0.912311E+10 0.00 0.00 0.00 0.00 18951.77 29-AUG-08:62 15285.62 03-AUG-15:02 0.00 0.00 0.00
September 0.142398E+11 0.00 664.31 0.872830E+10 0.00 0.00 0.00 0.00 21662.44 05-SEP-08:62 15343.02 23-SEP-15:02 0.00 0.00 0.00
October 0.149329E+11 0.00 687.45 0.999961E+10 0.00 0.00 0.00 0.00 19800.30 22-OCT-08:62 15315.74 25-OCT-15:02 0.00 0.00 0.00
November 0.106228E+11 0.00 633.89 0.726677E+10 0.00 0.00 0.00 0.00 19669.83 02-NOV-08:62 15205.59 06-NOV-16:02 0.00 0.00 0.00
December 0.852436E+10 0.00 539.14 0.588631E+10 0.00 0.00 0.00 0.00 19813.65 12-DEC-09:02 15264.89 10-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.131292E+12 0.00 7344.31 0.829118E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.619789E+10 0.00 496.33 0.376465E+10 0.00 0.00 0.00 0.00 17716.40   14918.00   0.00 0.00 0.00
Maximum of Months 0.149329E+11 0.00 687.45 0.999961E+10 0.00 0.00 0.00 0.00 21662.44   15343.02   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 645.66 460.71 184.95 934.32 377.21 0.00 0.00 0.00
February 581.06 374.73 206.33 861.40 317.67 0.00 0.00 0.00
March 379.44 174.62 204.82 587.30 272.43 0.00 0.00 0.00
April 276.94 65.02 211.92 484.06 162.20 0.00 0.00 0.00
May 213.02 10.50 202.52 469.02 31.84 0.00 0.00 0.00
June 208.71 1.82 206.89 467.95 26.11 0.00 0.00 0.00
July 218.21 3.57 214.63 490.29 12.69 0.00 0.00 0.00
August 252.61 26.20 226.42 559.58 25.56 0.00 0.00 0.00
September 309.75 82.46 227.29 627.97 42.12 0.00 0.00 0.00
October 473.93 244.51 229.42 866.32 99.17 0.00 0.00 0.00
November 615.06 425.21 189.84 967.46 237.77 0.00 0.00 0.00
December 631.09 453.55 177.54 949.77 327.93 0.00 0.00 0.00
                 
Annual Sum or Average 399.50 192.63 206.86 687.94 160.25 0.00 0.00 0.00
Minimum of Months 208.71 1.82 177.54 467.95 12.69 0.00 0.00 0.00
Maximum of Months 645.66 460.71 229.42 967.46 377.21 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1818.13 1297.33 520.80 2579.90 1174.28 0.00 0.00 0.00
February 1636.24 1055.22 581.02 2375.87 994.94 0.00 0.00 0.00
March 1068.48 491.72 576.75 1612.19 869.13 0.00 0.00 0.00
April 779.83 183.09 596.75 1326.69 530.50 0.00 0.00 0.00
May 599.86 29.56 570.29 1297.30 112.00 0.00 0.00 0.00
June 587.72 5.14 582.58 1306.83 90.53 0.00 0.00 0.00
July 614.46 10.07 604.39 1368.42 49.43 0.00 0.00 0.00
August 711.34 73.76 637.57 1564.54 87.74 0.00 0.00 0.00
September 872.23 232.20 640.04 1750.66 146.71 0.00 0.00 0.00
October 1334.55 688.53 646.02 2415.89 315.64 0.00 0.00 0.00
November 1731.95 1197.37 534.59 2682.82 751.29 0.00 0.00 0.00
December 1777.12 1277.17 499.95 2632.42 1024.78 0.00 0.00 0.00
                 
Annual Sum or Average 1124.96 542.45 582.51 1907.19 509.73 0.00 0.00 0.00
Minimum of Months 587.72 5.14 499.95 1297.30 49.43 0.00 0.00 0.00
Maximum of Months 1818.13 1297.33 646.02 2682.82 1174.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2361.86 1685.31 676.55 3438.28 1556.95 0.00 0.00 0.00
February 2125.57 1370.79 754.78 3171.07 1319.41 0.00 0.00 0.00
March 1388.01 638.78 749.24 2147.26 1171.71 0.00 0.00 0.00
April 1013.05 237.84 775.21 1766.88 709.29 0.00 0.00 0.00
May 779.25 38.40 740.84 1734.55 140.84 0.00 0.00 0.00
June 763.48 6.67 756.81 1748.71 113.84 0.00 0.00 0.00
July 798.22 13.08 785.14 1834.48 60.92 0.00 0.00 0.00
August 924.07 95.82 828.24 2097.78 107.82 0.00 0.00 0.00
September 1133.08 301.64 831.44 2342.12 180.21 0.00 0.00 0.00
October 1733.66 894.44 839.22 3227.40 400.43 0.00 0.00 0.00
November 2249.91 1555.45 694.46 3573.50 978.74 0.00 0.00 0.00
December 2308.58 1659.12 649.46 3498.65 1358.77 0.00 0.00 0.00
                 
Annual Sum or Average 1461.38 704.67 756.71 2545.36 671.58 0.00 0.00 0.00
Minimum of Months 763.48 6.67 649.46 1734.55 60.92 0.00 0.00 0.00
Maximum of Months 2361.86 1685.31 839.22 3573.50 1556.95 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 127.66 91.09 36.57 188.04 71.08 0.00 0.00 0.00
February 114.89 74.09 40.80 173.72 58.85 0.00 0.00 0.00
March 75.02 34.53 40.50 118.04 50.00 0.00 0.00 0.00
April 54.76 12.86 41.90 98.46 26.73 0.00 0.00 0.00
May 42.12 2.08 40.04 104.84 1.52 0.00 0.00 0.00
June 41.27 0.36 40.91 106.35 1.02 0.00 0.00 0.00
July 43.14 0.71 42.44 113.88 0.13 0.00 0.00 0.00
August 49.95 5.18 44.77 126.32 0.89 0.00 0.00 0.00
September 61.24 16.30 44.94 136.27 1.52 0.00 0.00 0.00
October 93.70 48.34 45.36 181.99 12.06 0.00 0.00 0.00
November 121.61 84.07 37.54 196.99 39.84 0.00 0.00 0.00
December 124.78 89.68 35.10 191.72 59.52 0.00 0.00 0.00
                 
Annual Sum or Average 78.99 38.09 40.90 144.59 26.77 0.00 0.00 0.00
Minimum of Months 41.27 0.36 35.10 98.46 0.13 0.00 0.00 0.00
Maximum of Months 127.66 91.09 45.36 196.99 71.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 112.76 60.97 51.79 146.87 145.15 0.00 0.00 0.00
February 127.97 64.88 63.09 175.70 118.26 0.00 0.00 0.00
March 125.46 55.35 70.11 182.00 95.04 0.00 0.00 0.00
April 155.98 71.67 84.31 262.16 48.53 0.00 0.00 0.00
May 130.05 42.41 87.64 284.80 2.77 0.00 0.00 0.00
June 144.32 50.64 93.68 319.62 1.86 0.00 0.00 0.00
July 131.55 36.38 95.17 303.64 0.23 0.00 0.00 0.00
August 132.94 40.42 92.52 299.68 1.62 0.00 0.00 0.00
September 122.70 42.09 80.60 258.53 2.70 0.00 0.00 0.00
October 125.90 54.55 71.35 246.34 23.30 0.00 0.00 0.00
November 107.62 54.07 53.55 165.70 80.72 0.00 0.00 0.00
December 103.17 54.70 48.47 144.01 118.37 0.00 0.00 0.00
                 
Annual Sum or Average 126.62 52.22 74.41 232.68 52.90 0.00 0.00 0.00
Minimum of Months 103.17 36.38 48.47 144.01 0.23 0.00 0.00 0.00
Maximum of Months 155.98 71.67 95.17 319.62 145.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.05 0.00 22.05 18.55 78.54 0.00 0.00 0.00
February 26.02 0.00 26.02 25.03 64.31 0.00 0.00 0.00
March 30.19 0.00 30.19 36.18 51.46 0.00 0.00 0.00
April 35.76 0.24 35.52 57.17 25.98 0.00 0.00 0.00
May 40.38 1.48 38.90 100.43 1.52 0.00 0.00 0.00
June 45.92 3.22 42.70 116.13 1.00 0.00 0.00 0.00
July 44.58 1.72 42.85 116.60 0.13 0.00 0.00 0.00
August 40.01 0.40 39.61 104.86 0.87 0.00 0.00 0.00
September 34.46 0.01 34.45 83.45 1.44 0.00 0.00 0.00
October 29.93 0.00 29.93 67.35 12.21 0.00 0.00 0.00
November 22.72 0.00 22.72 29.91 42.62 0.00 0.00 0.00
December 20.50 0.00 20.50 20.63 63.47 0.00 0.00 0.00
                 
Annual Sum or Average 32.74 0.59 32.15 64.94 28.46 0.00 0.00 0.00
Minimum of Months 20.50 0.00 20.50 18.55 0.13 0.00 0.00 0.00
Maximum of Months 45.92 3.22 42.85 116.60 78.54 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 112.76 60.97 51.79 153.58 140.33 0.00 0.00 0.00
February 127.97 64.88 63.09 181.57 114.79 0.00 0.00 0.00
March 125.46 55.35 70.11 185.47 93.32 0.00 0.00 0.00
April 155.98 71.67 84.31 263.81 47.89 0.00 0.00 0.00
May 130.05 42.41 87.64 284.97 2.75 0.00 0.00 0.00
June 144.32 50.64 93.68 319.29 1.87 0.00 0.00 0.00
July 131.55 36.38 95.17 303.54 0.23 0.00 0.00 0.00
August 132.94 40.42 92.52 300.42 1.58 0.00 0.00 0.00
September 122.70 42.09 80.60 260.29 2.52 0.00 0.00 0.00
October 125.90 54.55 71.35 249.99 22.44 0.00 0.00 0.00
November 107.62 54.07 53.55 171.16 77.56 0.00 0.00 0.00
December 103.17 54.70 48.47 149.86 114.21 0.00 0.00 0.00
                 
Annual Sum or Average 126.62 52.22 74.41 235.57 51.31 0.00 0.00 0.00
Minimum of Months 103.17 36.38 48.47 149.86 0.23 0.00 0.00 0.00
Maximum of Months 155.98 71.67 95.17 319.29 140.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 102.11 72.86 29.25 145.30 66.74 0.00 0.00 0.00
February 91.89 59.26 32.63 134.53 55.58 0.00 0.00 0.00
March 60.01 27.62 32.39 91.53 46.95 0.00 0.00 0.00
April 43.80 10.28 33.51 76.25 27.52 0.00 0.00 0.00
May 33.69 1.66 32.03 78.37 3.54 0.00 0.00 0.00
June 33.01 0.29 32.72 79.79 2.58 0.00 0.00 0.00
July 34.51 0.57 33.94 84.56 0.98 0.00 0.00 0.00
August 39.95 4.14 35.81 95.03 2.42 0.00 0.00 0.00
September 48.98 13.04 35.94 103.86 4.61 0.00 0.00 0.00
October 74.95 38.67 36.28 140.70 14.38 0.00 0.00 0.00
November 97.27 67.24 30.02 153.48 40.35 0.00 0.00 0.00
December 99.80 71.73 28.08 149.22 57.05 0.00 0.00 0.00
                 
Annual Sum or Average 63.18 30.46 32.71 110.94 26.74 0.00 0.00 0.00
Minimum of Months 33.01 0.29 28.08 76.25 0.98 0.00 0.00 0.00
Maximum of Months 102.11 72.86 36.28 153.48 66.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 17.64 0.00 17.64 15.80 62.93 0.00 0.00 0.00
February 20.82 0.00 20.82 21.84 50.91 0.00 0.00 0.00
March 24.15 0.00 24.15 31.18 40.53 0.00 0.00 0.00
April 28.61 0.19 28.42 49.89 18.95 0.00 0.00 0.00
May 32.31 1.18 31.13 86.66 0.66 0.00 0.00 0.00
June 36.74 2.58 34.17 99.59 0.47 0.00 0.00 0.00
July 35.66 1.38 34.29 100.13 0.03 0.00 0.00 0.00
August 32.01 0.32 31.69 90.73 0.39 0.00 0.00 0.00
September 27.57 0.01 27.57 73.16 0.60 0.00 0.00 0.00
October 23.95 0.00 23.95 59.47 8.63 0.00 0.00 0.00
November 18.18 0.00 18.18 26.52 32.54 0.00 0.00 0.00
December 16.40 0.00 16.40 17.96 50.53 0.00 0.00 0.00
                 
Annual Sum or Average 26.20 0.47 25.73 56.29 22.13 0.00 0.00 0.00
Minimum of Months 16.40 0.00 16.40 15.80 0.03 0.00 0.00 0.00
Maximum of Months 36.74 2.58 34.29 100.13 62.93 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 105.82 53.83 52.00 128.19 138.52 0.00 0.00 0.00
February 118.19 57.06 61.13 153.18 112.05 0.00 0.00 0.00
March 139.19 67.20 71.99 198.75 90.04 0.00 0.00 0.00
April 152.53 68.93 83.60 253.13 46.39 0.00 0.00 0.00
May 157.13 68.21 88.92 328.64 2.74 0.00 0.00 0.00
June 159.06 63.02 96.04 344.99 1.70 0.00 0.00 0.00
July 153.54 56.21 97.34 341.67 0.23 0.00 0.00 0.00
August 141.57 48.72 92.86 312.83 1.57 0.00 0.00 0.00
September 125.23 43.03 82.19 262.23 2.66 0.00 0.00 0.00
October 123.93 52.34 71.60 240.23 21.82 0.00 0.00 0.00
November 109.49 55.74 53.75 161.94 75.70 0.00 0.00 0.00
December 86.38 39.18 47.20 111.69 115.08 0.00 0.00 0.00
                 
Annual Sum or Average 131.05 56.10 74.95 236.93 50.41 0.00 0.00 0.00
Minimum of Months 86.38 39.18 47.20 111.69 0.23 0.00 0.00 0.00
Maximum of Months 159.06 68.93 97.34 344.99 138.52 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 127.66 91.09 36.57 187.16 70.53 0.00 0.00 0.00
February 114.89 74.09 40.80 172.86 58.20 0.00 0.00 0.00
March 75.02 34.53 40.50 116.59 49.72 0.00 0.00 0.00
April 54.76 12.86 41.90 97.48 26.32 0.00 0.00 0.00
May 42.12 2.08 40.04 103.80 1.48 0.00 0.00 0.00
June 41.27 0.36 40.91 105.65 0.96 0.00 0.00 0.00
July 43.14 0.71 42.44 113.02 0.12 0.00 0.00 0.00
August 49.95 5.18 44.77 125.92 0.85 0.00 0.00 0.00
September 61.24 16.30 44.94 135.98 1.44 0.00 0.00 0.00
October 93.70 48.34 45.36 181.64 11.77 0.00 0.00 0.00
November 121.61 84.07 37.54 196.16 39.49 0.00 0.00 0.00
December 124.78 89.68 35.10 191.46 58.85 0.00 0.00 0.00
                 
Annual Sum or Average 78.99 38.09 40.90 143.85 26.49 0.00 0.00 0.00
Minimum of Months 41.27 0.36 35.10 97.48 0.12 0.00 0.00 0.00
Maximum of Months 127.66 91.09 45.36 196.16 70.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.05 0.00 22.05 17.89 78.15 0.00 0.00 0.00
February 26.02 0.00 26.02 24.36 63.83 0.00 0.00 0.00
March 30.19 0.00 30.19 34.75 51.39 0.00 0.00 0.00
April 35.76 0.24 35.52 56.04 25.61 0.00 0.00 0.00
May 40.38 1.48 38.90 99.38 1.48 0.00 0.00 0.00
June 45.92 3.22 42.70 115.44 0.94 0.00 0.00 0.00
July 44.58 1.72 42.85 115.75 0.12 0.00 0.00 0.00
August 40.01 0.40 39.61 104.43 0.83 0.00 0.00 0.00
September 34.46 0.01 34.45 83.11 1.36 0.00 0.00 0.00
October 29.93 0.00 29.93 66.88 11.92 0.00 0.00 0.00
November 22.72 0.00 22.72 29.12 42.30 0.00 0.00 0.00
December 20.50 0.00 20.50 20.35 62.75 0.00 0.00 0.00
                 
Annual Sum or Average 32.74 0.59 32.15 64.21 28.22 0.00 0.00 0.00
Minimum of Months 20.50 0.00 20.50 17.89 0.12 0.00 0.00 0.00
Maximum of Months 45.92 3.22 42.85 115.75 78.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 105.82 53.83 52.00 134.00 132.65 0.00 0.00 0.00
February 118.19 57.06 61.13 158.46 107.91 0.00 0.00 0.00
March 139.19 67.20 71.99 201.83 88.27 0.00 0.00 0.00
April 152.53 68.93 83.60 254.45 45.76 0.00 0.00 0.00
May 157.13 68.21 88.92 328.83 2.71 0.00 0.00 0.00
June 159.06 63.02 96.04 344.70 1.71 0.00 0.00 0.00
July 153.54 56.21 97.34 341.59 0.23 0.00 0.00 0.00
August 141.57 48.72 92.86 313.55 1.53 0.00 0.00 0.00
September 125.23 43.03 82.19 263.92 2.49 0.00 0.00 0.00
October 123.93 52.34 71.60 243.76 20.94 0.00 0.00 0.00
November 109.49 55.74 53.75 167.18 72.22 0.00 0.00 0.00
December 86.38 39.18 47.20 117.07 110.19 0.00 0.00 0.00
                 
Annual Sum or Average 131.05 56.10 74.95 239.57 48.60 0.00 0.00 0.00
Minimum of Months 86.38 39.18 47.20 117.07 0.23 0.00 0.00 0.00
Maximum of Months 159.06 68.93 97.34 344.70 132.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 27.93 0.00 27.93 21.20 112.92 0.00 0.00 0.00
February 32.95 0.00 32.95 30.06 92.35 0.00 0.00 0.00
March 38.23 0.00 38.23 44.48 75.57 0.00 0.00 0.00
April 45.29 0.31 44.98 70.96 41.35 0.00 0.00 0.00
May 51.14 1.87 49.27 117.31 6.49 0.00 0.00 0.00
June 58.16 4.08 54.08 136.52 5.13 0.00 0.00 0.00
July 56.45 2.18 54.27 134.50 2.28 0.00 0.00 0.00
August 50.67 0.51 50.17 120.81 4.73 0.00 0.00 0.00
September 43.65 0.01 43.63 96.06 8.46 0.00 0.00 0.00
October 37.90 0.00 37.90 76.52 24.35 0.00 0.00 0.00
November 28.78 0.00 28.78 34.29 67.07 0.00 0.00 0.00
December 25.96 0.00 25.96 23.42 94.35 0.00 0.00 0.00
                 
Annual Sum or Average 41.47 0.75 40.72 75.79 44.35 0.00 0.00 0.00
Minimum of Months 25.96 0.00 25.96 21.20 2.28 0.00 0.00 0.00
Maximum of Months 58.16 4.08 54.27 136.52 112.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.30 0.00 10.30 7.81 41.63 0.00 0.00 0.00
February 12.15 0.00 12.15 11.08 34.05 0.00 0.00 0.00
March 14.09 0.00 14.09 16.40 27.86 0.00 0.00 0.00
April 16.70 0.11 16.58 26.16 15.24 0.00 0.00 0.00
May 18.85 0.69 18.16 43.25 2.39 0.00 0.00 0.00
June 21.44 1.50 19.94 50.33 1.89 0.00 0.00 0.00
July 20.81 0.80 20.01 49.58 0.84 0.00 0.00 0.00
August 18.68 0.19 18.49 44.54 1.74 0.00 0.00 0.00
September 16.09 0.00 16.09 35.41 3.12 0.00 0.00 0.00
October 13.97 0.00 13.97 28.21 8.98 0.00 0.00 0.00
November 10.61 0.00 10.61 12.64 24.72 0.00 0.00 0.00
December 9.57 0.00 9.57 8.63 34.78 0.00 0.00 0.00
                 
Annual Sum or Average 15.29 0.28 15.01 27.94 16.35 0.00 0.00 0.00
Minimum of Months 9.57 0.00 9.57 7.81 0.84 0.00 0.00 0.00
Maximum of Months 21.44 1.50 20.01 50.33 41.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 59.56 42.50 17.06 87.85 36.11 0.00 0.00 0.00
February 53.61 34.57 19.04 81.31 30.09 0.00 0.00 0.00
March 35.01 16.11 18.90 55.16 26.55 0.00 0.00 0.00
April 25.55 6.00 19.55 45.78 15.47 0.00 0.00 0.00
May 19.65 0.97 18.68 45.36 2.44 0.00 0.00 0.00
June 19.25 0.17 19.09 45.71 1.95 0.00 0.00 0.00
July 20.13 0.33 19.80 48.25 0.84 0.00 0.00 0.00
August 23.30 2.42 20.89 54.69 1.76 0.00 0.00 0.00
September 28.58 7.61 20.97 60.38 3.12 0.00 0.00 0.00
October 43.72 22.56 21.16 82.35 8.59 0.00 0.00 0.00
November 56.74 39.23 17.51 91.42 22.17 0.00 0.00 0.00
December 58.22 41.84 16.38 89.36 31.26 0.00 0.00 0.00
                 
Annual Sum or Average 36.86 17.77 19.08 65.56 14.95 0.00 0.00 0.00
Minimum of Months 19.25 0.17 16.38 45.36 0.84 0.00 0.00 0.00
Maximum of Months 59.56 42.50 21.16 91.42 36.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 161.67 115.36 46.31 238.44 98.02 0.00 0.00 0.00
February 145.50 93.83 51.67 220.71 81.68 0.00 0.00 0.00
March 95.01 43.72 51.29 149.71 72.06 0.00 0.00 0.00
April 69.34 16.28 53.06 124.25 42.00 0.00 0.00 0.00
May 53.34 2.63 50.71 123.12 6.61 0.00 0.00 0.00
June 52.26 0.46 51.80 124.08 5.28 0.00 0.00 0.00
July 54.64 0.90 53.74 130.96 2.27 0.00 0.00 0.00
August 63.25 6.56 56.69 148.43 4.79 0.00 0.00 0.00
September 77.56 20.65 56.91 163.89 8.47 0.00 0.00 0.00
October 118.67 61.23 57.45 223.51 23.32 0.00 0.00 0.00
November 154.01 106.47 47.54 248.14 60.16 0.00 0.00 0.00
December 158.02 113.57 44.46 242.55 84.86 0.00 0.00 0.00
                 
Annual Sum or Average 100.03 48.23 51.80 177.94 40.59 0.00 0.00 0.00
Minimum of Months 52.26 0.46 44.46 123.12 2.27 0.00 0.00 0.00
Maximum of Months 161.67 115.36 57.45 248.14 98.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 127.66 91.09 36.57 186.87 70.06 0.00 0.00 0.00
February 114.89 74.09 40.80 172.40 57.96 0.00 0.00 0.00
March 75.02 34.53 40.50 116.99 49.05 0.00 0.00 0.00
April 54.76 12.86 41.90 97.40 26.06 0.00 0.00 0.00
May 42.12 2.08 40.04 104.48 1.32 0.00 0.00 0.00
June 41.27 0.36 40.91 105.90 0.88 0.00 0.00 0.00
July 43.14 0.71 42.44 113.71 0.10 0.00 0.00 0.00
August 49.95 5.18 44.77 125.94 0.78 0.00 0.00 0.00
September 61.24 16.30 44.94 135.81 1.34 0.00 0.00 0.00
October 93.70 48.34 45.36 180.97 11.56 0.00 0.00 0.00
November 121.61 84.07 37.54 195.87 38.84 0.00 0.00 0.00
December 124.78 89.68 35.10 190.58 58.39 0.00 0.00 0.00
                 
Annual Sum or Average 78.99 38.09 40.90 143.79 26.21 0.00 0.00 0.00
Minimum of Months 41.27 0.36 35.10 97.40 0.10 0.00 0.00 0.00
Maximum of Months 127.66 91.09 45.36 195.87 70.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 112.76 60.97 51.79 145.52 142.80 0.00 0.00 0.00
February 127.97 64.88 63.09 173.88 116.33 0.00 0.00 0.00
March 125.46 55.35 70.11 180.11 93.15 0.00 0.00 0.00
April 155.98 71.67 84.31 259.36 47.20 0.00 0.00 0.00
May 130.05 42.41 87.64 283.41 2.42 0.00 0.00 0.00
June 144.32 50.64 93.68 317.87 1.61 0.00 0.00 0.00
July 131.55 36.38 95.17 302.40 0.18 0.00 0.00 0.00
August 132.94 40.42 92.52 298.53 1.41 0.00 0.00 0.00
September 122.70 42.09 80.60 257.73 2.36 0.00 0.00 0.00
October 125.90 54.55 71.35 245.33 22.27 0.00 0.00 0.00
November 107.62 54.07 53.55 164.63 78.50 0.00 0.00 0.00
December 103.17 54.70 48.47 142.93 115.95 0.00 0.00 0.00
                 
Annual Sum or Average 126.62 52.22 74.41 231.24 51.70 0.00 0.00 0.00
Minimum of Months 103.17 36.38 48.47 142.93 0.18 0.00 0.00 0.00
Maximum of Months 155.98 71.67 95.17 317.87 142.80 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.05 0.00 22.05 18.85 77.07 0.00 0.00 0.00
February 26.02 0.00 26.02 25.07 63.11 0.00 0.00 0.00
March 30.19 0.00 30.19 36.07 50.45 0.00 0.00 0.00
April 35.76 0.24 35.52 56.57 25.29 0.00 0.00 0.00
May 40.38 1.48 38.90 100.11 1.33 0.00 0.00 0.00
June 45.92 3.22 42.70 115.63 0.84 0.00 0.00 0.00
July 44.58 1.72 42.85 116.28 0.11 0.00 0.00 0.00
August 40.01 0.40 39.61 104.79 0.76 0.00 0.00 0.00
September 34.46 0.01 34.45 83.60 1.25 0.00 0.00 0.00
October 29.93 0.00 29.93 67.61 11.58 0.00 0.00 0.00
November 22.72 0.00 22.72 30.23 41.19 0.00 0.00 0.00
December 20.50 0.00 20.50 20.94 61.96 0.00 0.00 0.00
                 
Annual Sum or Average 32.74 0.59 32.15 64.90 27.74 0.00 0.00 0.00
Minimum of Months 20.50 0.00 20.50 18.85 0.11 0.00 0.00 0.00
Maximum of Months 45.92 3.22 42.85 116.28 77.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 112.76 60.97 51.79 153.03 137.62 0.00 0.00 0.00
February 127.97 64.88 63.09 180.32 112.56 0.00 0.00 0.00
March 125.46 55.35 70.11 183.85 91.28 0.00 0.00 0.00
April 155.98 71.67 84.31 261.07 46.50 0.00 0.00 0.00
May 130.05 42.41 87.64 283.59 2.39 0.00 0.00 0.00
June 144.32 50.64 93.68 317.53 1.62 0.00 0.00 0.00
July 131.55 36.38 95.17 302.29 0.19 0.00 0.00 0.00
August 132.94 40.42 92.52 299.30 1.37 0.00 0.00 0.00
September 122.70 42.09 80.60 259.60 2.19 0.00 0.00 0.00
October 125.90 54.55 71.35 249.30 21.32 0.00 0.00 0.00
November 107.62 54.07 53.55 170.82 74.83 0.00 0.00 0.00
December 103.17 54.70 48.47 149.52 111.32 0.00 0.00 0.00
                 
Annual Sum or Average 126.62 52.22 74.41 234.43 49.96 0.00 0.00 0.00
Minimum of Months 103.17 36.38 48.47 149.52 0.19 0.00 0.00 0.00
Maximum of Months 155.98 71.67 95.17 317.53 137.62 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 187.22 133.59 53.63 267.73 107.42 0.00 0.00 0.00
February 168.49 108.66 59.83 248.25 87.86 0.00 0.00 0.00
March 110.03 50.64 59.39 169.89 73.20 0.00 0.00 0.00
April 80.30 18.85 61.45 144.79 36.86 0.00 0.00 0.00
May 61.77 3.04 58.73 158.27 1.46 0.00 0.00 0.00
June 60.52 0.53 59.99 161.53 0.99 0.00 0.00 0.00
July 63.27 1.04 62.24 172.65 0.09 0.00 0.00 0.00
August 73.25 7.60 65.65 189.71 0.92 0.00 0.00 0.00
September 89.82 23.91 65.91 202.25 1.61 0.00 0.00 0.00
October 137.43 70.90 66.52 265.87 16.95 0.00 0.00 0.00
November 178.35 123.30 55.05 283.88 59.14 0.00 0.00 0.00
December 183.00 131.52 51.48 274.58 89.75 0.00 0.00 0.00
                 
Annual Sum or Average 115.84 55.86 59.98 211.46 39.46 0.00 0.00 0.00
Minimum of Months 60.52 0.53 51.48 144.79 0.09 0.00 0.00 0.00
Maximum of Months 187.22 133.59 66.52 283.88 107.42 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 154.36 0.00 154.36 90.50 726.21 0.00 0.00 0.00
February 182.11 0.00 182.11 132.33 601.63 0.00 0.00 0.00
March 211.29 0.00 211.29 201.47 504.17 0.00 0.00 0.00
April 250.31 1.69 248.62 341.94 278.29 0.00 0.00 0.00
May 282.66 10.34 272.32 602.77 54.33 0.00 0.00 0.00
June 321.43 22.53 298.90 713.60 43.31 0.00 0.00 0.00
July 312.01 12.05 299.96 699.89 22.85 0.00 0.00 0.00
August 280.07 2.79 277.28 627.19 40.48 0.00 0.00 0.00
September 241.23 0.07 241.17 495.96 69.86 0.00 0.00 0.00
October 209.50 0.00 209.50 392.60 162.85 0.00 0.00 0.00
November 159.04 0.00 159.04 163.16 426.38 0.00 0.00 0.00
December 143.50 0.00 143.50 104.67 609.90 0.00 0.00 0.00
                 
Annual Sum or Average 229.19 4.14 225.06 382.02 293.49 0.00 0.00 0.00
Minimum of Months 143.50 0.00 143.50 90.50 22.85 0.00 0.00 0.00
Maximum of Months 321.43 22.53 299.96 713.60 726.21 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 154.36 0.00 154.36 83.70 750.79 0.00 0.00 0.00
February 182.11 0.00 182.11 123.93 622.15 0.00 0.00 0.00
March 211.29 0.00 211.29 191.22 521.78 0.00 0.00 0.00
April 250.31 1.69 248.62 331.36 288.78 0.00 0.00 0.00
May 282.66 10.34 272.32 592.70 59.42 0.00 0.00 0.00
June 321.43 22.53 298.90 703.94 47.65 0.00 0.00 0.00
July 312.01 12.05 299.96 689.14 26.06 0.00 0.00 0.00
August 280.07 2.79 277.28 616.95 44.82 0.00 0.00 0.00
September 241.23 0.07 241.17 486.74 76.31 0.00 0.00 0.00
October 209.50 0.00 209.50 383.23 170.87 0.00 0.00 0.00
November 159.04 0.00 159.04 154.91 441.50 0.00 0.00 0.00
December 143.50 0.00 143.50 98.04 631.62 0.00 0.00 0.00
                 
Annual Sum or Average 229.19 4.14 225.06 372.83 305.24 0.00 0.00 0.00
Minimum of Months 143.50 0.00 143.50 83.70 26.06 0.00 0.00 0.00
Maximum of Months 321.43 22.53 299.96 703.94 750.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.05 0.00 22.05 16.13 101.62 0.00 0.00 0.00
February 26.02 0.00 26.02 23.81 83.81 0.00 0.00 0.00
March 30.19 0.00 30.19 34.47 72.18 0.00 0.00 0.00
April 35.76 0.24 35.52 59.44 40.01 0.00 0.00 0.00
May 40.38 1.48 38.90 101.13 10.62 0.00 0.00 0.00
June 45.92 3.22 42.70 119.05 9.11 0.00 0.00 0.00
July 44.58 1.72 42.85 116.04 5.78 0.00 0.00 0.00
August 40.01 0.40 39.61 104.39 8.33 0.00 0.00 0.00
September 34.46 0.01 34.45 84.33 12.51 0.00 0.00 0.00
October 29.93 0.00 29.93 66.71 25.01 0.00 0.00 0.00
November 22.72 0.00 22.72 29.94 58.11 0.00 0.00 0.00
December 20.50 0.00 20.50 19.21 84.55 0.00 0.00 0.00
                 
Annual Sum or Average 32.74 0.59 32.15 64.80 42.44 0.00 0.00 0.00
Minimum of Months 20.50 0.00 20.50 16.13 5.78 0.00 0.00 0.00
Maximum of Months 45.92 3.22 42.85 119.05 101.62 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 211.63 107.64 103.99 255.98 345.19 0.00 0.00 0.00
February 236.37 114.11 122.25 310.37 284.64 0.00 0.00 0.00
March 278.36 134.40 143.96 399.38 249.96 0.00 0.00 0.00
April 305.04 137.86 167.18 520.53 144.97 0.00 0.00 0.00
May 314.23 136.42 177.82 660.72 40.30 0.00 0.00 0.00
June 318.09 126.02 192.07 700.64 34.65 0.00 0.00 0.00
July 307.06 112.41 194.66 681.75 22.33 0.00 0.00 0.00
August 283.12 97.42 185.70 623.99 31.22 0.00 0.00 0.00
September 250.43 86.06 164.37 529.99 46.98 0.00 0.00 0.00
October 247.85 104.66 143.18 484.19 90.34 0.00 0.00 0.00
November 218.96 111.47 107.49 335.43 200.59 0.00 0.00 0.00
December 172.74 78.36 94.39 225.92 296.28 0.00 0.00 0.00
                 
Annual Sum or Average 262.08 112.19 149.89 478.30 148.30 0.00 0.00 0.00
Minimum of Months 172.74 78.36 94.39 225.92 22.33 0.00 0.00 0.00
Maximum of Months 318.09 137.86 194.66 700.64 345.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 127.66 91.09 36.57 187.85 87.85 0.00 0.00 0.00
February 114.89 74.09 40.80 174.40 73.69 0.00 0.00 0.00
March 75.02 34.53 40.50 117.91 68.33 0.00 0.00 0.00
April 54.76 12.86 41.90 101.65 40.41 0.00 0.00 0.00
May 42.12 2.08 40.04 105.54 10.71 0.00 0.00 0.00
June 41.27 0.36 40.91 109.50 9.28 0.00 0.00 0.00
July 43.14 0.71 42.44 112.90 5.91 0.00 0.00 0.00
August 49.95 5.18 44.77 126.15 8.40 0.00 0.00 0.00
September 61.24 16.30 44.94 138.25 12.49 0.00 0.00 0.00
October 93.70 48.34 45.36 184.31 23.87 0.00 0.00 0.00
November 121.61 84.07 37.54 200.71 52.86 0.00 0.00 0.00
December 124.78 89.68 35.10 193.24 75.85 0.00 0.00 0.00
                 
Annual Sum or Average 78.99 38.09 40.90 145.89 38.97 0.00 0.00 0.00
Minimum of Months 41.27 0.36 35.10 101.65 5.91 0.00 0.00 0.00
Maximum of Months 127.66 91.09 45.36 200.71 87.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 27.93 0.00 27.93 19.50 113.02 0.00 0.00 0.00
February 32.95 0.00 32.95 27.57 93.34 0.00 0.00 0.00
March 38.23 0.00 38.23 41.63 76.59 0.00 0.00 0.00
April 45.29 0.31 44.98 66.67 43.07 0.00 0.00 0.00
May 51.14 1.87 49.27 111.51 8.08 0.00 0.00 0.00
June 58.16 4.08 54.08 130.59 6.56 0.00 0.00 0.00
July 56.45 2.18 54.27 128.30 3.23 0.00 0.00 0.00
August 50.67 0.51 50.17 115.12 5.98 0.00 0.00 0.00
September 43.65 0.01 43.63 91.53 10.25 0.00 0.00 0.00
October 37.90 0.00 37.90 72.70 25.43 0.00 0.00 0.00
November 28.78 0.00 28.78 32.21 67.08 0.00 0.00 0.00
December 25.96 0.00 25.96 21.53 94.64 0.00 0.00 0.00
                 
Annual Sum or Average 41.47 0.75 40.72 71.84 45.37 0.00 0.00 0.00
Minimum of Months 25.96 0.00 25.96 19.50 3.23 0.00 0.00 0.00
Maximum of Months 58.16 4.08 54.27 130.59 113.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.99 0.00 24.99 17.45 101.11 0.00 0.00 0.00
February 29.48 0.00 29.48 24.67 83.51 0.00 0.00 0.00
March 34.20 0.00 34.20 37.25 68.52 0.00 0.00 0.00
April 40.52 0.27 40.25 59.65 38.54 0.00 0.00 0.00
May 45.76 1.67 44.08 99.77 7.23 0.00 0.00 0.00
June 52.03 3.65 48.38 116.84 5.87 0.00 0.00 0.00
July 50.51 1.95 48.56 114.79 2.89 0.00 0.00 0.00
August 45.34 0.45 44.89 102.99 5.35 0.00 0.00 0.00
September 39.05 0.01 39.04 81.89 9.17 0.00 0.00 0.00
October 33.91 0.00 33.91 65.04 22.75 0.00 0.00 0.00
November 25.75 0.00 25.75 28.82 60.01 0.00 0.00 0.00
December 23.23 0.00 23.23 19.26 84.67 0.00 0.00 0.00
                 
Annual Sum or Average 37.10 0.67 36.43 64.27 40.59 0.00 0.00 0.00
Minimum of Months 23.23 0.00 23.23 17.45 2.89 0.00 0.00 0.00
Maximum of Months 52.03 3.65 48.56 116.84 101.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 476.59 340.07 136.52 691.59 288.29 0.00 0.00 0.00
February 428.91 276.60 152.30 637.23 242.60 0.00 0.00 0.00
March 280.08 128.90 151.19 429.29 215.24 0.00 0.00 0.00
April 204.42 47.99 156.43 352.01 129.33 0.00 0.00 0.00
May 157.24 7.75 149.49 345.54 24.47 0.00 0.00 0.00
June 154.06 1.35 152.71 348.33 20.12 0.00 0.00 0.00
July 161.07 2.64 158.43 367.77 9.54 0.00 0.00 0.00
August 186.46 19.34 167.13 419.71 18.08 0.00 0.00 0.00
September 228.64 60.87 167.77 467.80 30.44 0.00 0.00 0.00
October 349.83 180.48 169.34 643.82 72.15 0.00 0.00 0.00
November 454.00 313.86 140.13 720.92 177.43 0.00 0.00 0.00
December 465.84 334.78 131.05 703.93 250.17 0.00 0.00 0.00
                 
Annual Sum or Average 294.88 142.19 152.69 510.04 122.54 0.00 0.00 0.00
Minimum of Months 154.06 1.35 131.05 345.54 9.54 0.00 0.00 0.00
Maximum of Months 476.59 340.07 169.34 720.92 288.29 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.172933E+10 0.123397E+10 0.495365E+09 0.250249E+10 0.101032E+10
February 0.140571E+10 0.906552E+09 0.499159E+09 0.208391E+10 0.768512E+09
March 0.101629E+10 0.467708E+09 0.548584E+09 0.157303E+10 0.729668E+09
April 0.717818E+09 0.168526E+09 0.549292E+09 0.125469E+10 0.420410E+09
May 0.570558E+09 28119162.44 0.542439E+09 0.125622E+10 85275377.09
June 0.540982E+09 4729371.35 0.536253E+09 0.121293E+10 67682349.53
July 0.584448E+09 9574678.74 0.574873E+09 0.131320E+10 33986326.05
August 0.676594E+09 70161886.99 0.606432E+09 0.149878E+10 68456273.70
September 0.802870E+09 0.213732E+09 0.589137E+09 0.162769E+10 0.109180E+09
October 0.126937E+10 0.654902E+09 0.614467E+09 0.232035E+10 0.265614E+09
November 0.159422E+10 0.110215E+10 0.492075E+09 0.250765E+10 0.616293E+09
December 0.169032E+10 0.121479E+10 0.475529E+09 0.254386E+10 0.878318E+09
           
Annual Sum or Average 0.125985E+11 0.607491E+10 0.652360E+10 0.216948E+11 0.505371E+10
Minimum of Months 0.540982E+09 4729371.35 0.475529E+09 0.121293E+10 33986326.05
Maximum of Months 0.172933E+10 0.123397E+10 0.614467E+09 0.254386E+10 0.101032E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.486969E+10 0.347477E+10 0.139491E+10 0.691001E+10 0.314519E+10
February 0.395839E+10 0.255279E+10 0.140560E+10 0.574771E+10 0.240697E+10
March 0.286181E+10 0.131704E+10 0.154478E+10 0.431808E+10 0.232789E+10
April 0.202133E+10 0.474557E+09 0.154677E+10 0.343879E+10 0.137505E+10
May 0.160665E+10 79181707.42 0.152747E+10 0.347469E+10 0.299990E+09
June 0.152337E+10 13317597.88 0.151005E+10 0.338729E+10 0.234653E+09
July 0.164577E+10 26961664.04 0.161880E+10 0.366519E+10 0.132389E+09
August 0.190524E+10 0.197571E+09 0.170767E+10 0.419047E+10 0.235006E+09
September 0.226083E+10 0.601855E+09 0.165897E+10 0.453772E+10 0.380265E+09
October 0.357446E+10 0.184416E+10 0.173030E+10 0.647071E+10 0.845406E+09
November 0.448923E+10 0.310358E+10 0.138565E+10 0.695386E+10 0.194734E+10
December 0.475984E+10 0.342078E+10 0.133906E+10 0.705068E+10 0.274476E+10
           
Annual Sum or Average 0.354766E+11 0.171066E+11 0.183700E+11 0.601452E+11 0.160749E+11
Minimum of Months 0.152337E+10 13317597.88 0.133906E+10 0.338729E+10 0.132389E+09
Maximum of Months 0.486969E+10 0.347477E+10 0.173030E+10 0.705068E+10 0.314519E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.632600E+10 0.451393E+10 0.181207E+10 0.920908E+10 0.417015E+10
February 0.514217E+10 0.331622E+10 0.182595E+10 0.767146E+10 0.319193E+10
March 0.371766E+10 0.171090E+10 0.200675E+10 0.575122E+10 0.313830E+10
April 0.262582E+10 0.616477E+09 0.200934E+10 0.457975E+10 0.183848E+10
May 0.208713E+10 0.102862E+09 0.198427E+10 0.464581E+10 0.377229E+09
June 0.197894E+10 17300317.56 0.196164E+10 0.453267E+10 0.295068E+09
July 0.213794E+10 35024735.99 0.210292E+10 0.491347E+10 0.163167E+09
August 0.247502E+10 0.256656E+09 0.221836E+10 0.561870E+10 0.288794E+09
September 0.293694E+10 0.781844E+09 0.215510E+10 0.607077E+10 0.467098E+09
October 0.464342E+10 0.239567E+10 0.224775E+10 0.864427E+10 0.107250E+10
November 0.583176E+10 0.403172E+10 0.180004E+10 0.926252E+10 0.253689E+10
December 0.618330E+10 0.444379E+10 0.173951E+10 0.937079E+10 0.363933E+10
           
Annual Sum or Average 0.460861E+11 0.222224E+11 0.238637E+11 0.802705E+11 0.211789E+11
Minimum of Months 0.197894E+10 17300317.56 0.173951E+10 0.453267E+10 0.163167E+09
Maximum of Months 0.632600E+10 0.451393E+10 0.224775E+10 0.937079E+10 0.417015E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.341920E+09 0.243977E+09 97942916.32 0.503637E+09 0.190388E+09
February 0.277934E+09 0.179241E+09 98693157.69 0.420252E+09 0.142377E+09
March 0.200939E+09 92473951.93 0.108466E+09 0.316166E+09 0.133926E+09
April 0.141926E+09 33320435.70 0.108606E+09 0.255196E+09 69279703.06
May 0.112810E+09 5559641.36 0.107251E+09 0.280792E+09 4080781.72
June 0.106963E+09 935077.94 0.106028E+09 0.275665E+09 2637896.41
July 0.115557E+09 1893078.43 0.113664E+09 0.305005E+09 348243.20
August 0.133775E+09 13872210.08 0.119903E+09 0.338329E+09 2376761.73
September 0.158742E+09 42258503.18 0.116484E+09 0.353208E+09 3933080.92
October 0.250977E+09 0.129485E+09 0.121492E+09 0.487455E+09 32310252.41
November 0.315206E+09 0.217914E+09 97292499.50 0.510597E+09 0.103265E+09
December 0.334207E+09 0.240186E+09 94020957.94 0.513500E+09 0.159430E+09
           
Annual Sum or Average 0.249096E+10 0.120111E+10 0.128984E+10 0.455980E+10 0.844353E+09
Minimum of Months 0.106963E+09 935077.94 94020957.94 0.255196E+09 348243.20
Maximum of Months 0.341920E+09 0.243977E+09 0.121492E+09 0.513500E+09 0.190388E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.302011E+09 0.163309E+09 0.138702E+09 0.393388E+09 0.388774E+09
February 0.309574E+09 0.156958E+09 0.152616E+09 0.425065E+09 0.286104E+09
March 0.336028E+09 0.148239E+09 0.187789E+09 0.487470E+09 0.254567E+09
April 0.404297E+09 0.185778E+09 0.218519E+09 0.679531E+09 0.125799E+09
May 0.348326E+09 0.113586E+09 0.234741E+09 0.762805E+09 7427871.15
June 0.374077E+09 0.131254E+09 0.242823E+09 0.828448E+09 4827152.56
July 0.352346E+09 97440319.81 0.254905E+09 0.813259E+09 618064.13
August 0.356060E+09 0.108256E+09 0.247804E+09 0.802663E+09 4328334.19
September 0.318033E+09 0.109105E+09 0.208928E+09 0.670121E+09 6996183.61
October 0.337210E+09 0.146094E+09 0.191115E+09 0.659810E+09 62414018.61
November 0.278951E+09 0.140148E+09 0.138803E+09 0.429505E+09 0.209231E+09
December 0.276332E+09 0.146515E+09 0.129817E+09 0.385717E+09 0.317034E+09
           
Annual Sum or Average 0.399324E+10 0.164668E+10 0.234656E+10 0.733778E+10 0.166812E+10
Minimum of Months 0.276332E+09 97440319.81 0.129817E+09 0.385717E+09 618064.13
Maximum of Months 0.404297E+09 0.185778E+09 0.254905E+09 0.828448E+09 0.388774E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 59064732.87 0.00 59064732.87 49679875.00 0.210356E+09
February 62938698.60 0.00 62938698.60 60542417.26 0.155572E+09
March 80850503.85 1139.98 80849363.87 96913680.82 0.137838E+09
April 92690358.85 625600.74 92064758.11 0.148174E+09 67339394.39
May 0.108156E+09 3956129.12 0.104200E+09 0.268979E+09 4082862.85
June 0.119027E+09 8343704.90 0.110683E+09 0.301010E+09 2581268.44
July 0.119390E+09 4610866.93 0.114779E+09 0.312304E+09 356468.99
August 0.107169E+09 1068424.11 0.106100E+09 0.280861E+09 2322412.33
September 89327845.69 24135.93 89303709.75 0.216298E+09 3721861.86
October 80164044.51 0.00 80164044.51 0.180386E+09 32708548.15
November 58894225.14 0.00 58894225.14 77537248.85 0.110480E+09
December 54907382.60 0.00 54907382.60 55247934.10 0.170003E+09
           
Annual Sum or Average 0.103258E+10 18630001.72 0.101395E+10 0.204793E+10 0.897363E+09
Minimum of Months 54907382.60 0.00 54907382.60 49679875.00 356468.99
Maximum of Months 0.119390E+09 8343704.90 0.114779E+09 0.312304E+09 0.210356E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.302011E+09 0.163309E+09 0.138702E+09 0.411356E+09 0.375848E+09
February 0.309574E+09 0.156958E+09 0.152616E+09 0.439265E+09 0.277689E+09
March 0.336028E+09 0.148239E+09 0.187789E+09 0.496766E+09 0.249951E+09
April 0.404297E+09 0.185778E+09 0.218519E+09 0.683785E+09 0.124135E+09
May 0.348326E+09 0.113586E+09 0.234741E+09 0.763272E+09 7360572.25
June 0.374077E+09 0.131254E+09 0.242823E+09 0.827606E+09 4857106.25
July 0.352346E+09 97440319.81 0.254905E+09 0.813008E+09 623399.36
August 0.356060E+09 0.108256E+09 0.247804E+09 0.804644E+09 4222226.90
September 0.318033E+09 0.109105E+09 0.208928E+09 0.674677E+09 6541657.68
October 0.337210E+09 0.146094E+09 0.191115E+09 0.669566E+09 60099241.43
November 0.278951E+09 0.140148E+09 0.138803E+09 0.443649E+09 0.201032E+09
December 0.276332E+09 0.146515E+09 0.129817E+09 0.401388E+09 0.305900E+09
           
Annual Sum or Average 0.399324E+10 0.164668E+10 0.234656E+10 0.742898E+10 0.161826E+10
Minimum of Months 0.276332E+09 97440319.81 0.129817E+09 0.401388E+09 623399.36
Maximum of Months 0.404297E+09 0.185778E+09 0.254905E+09 0.827606E+09 0.375848E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.273481E+09 0.195142E+09 78338753.59 0.389166E+09 0.178756E+09
February 0.222303E+09 0.143364E+09 78938827.35 0.325466E+09 0.134449E+09
March 0.160720E+09 73964452.01 86755164.61 0.245145E+09 0.125741E+09
April 0.113518E+09 26651048.39 86867256.30 0.197646E+09 71332129.43
May 90230318.66 4446828.73 85783489.92 0.209916E+09 9470070.67
June 85553156.98 747913.61 84805243.37 0.206822E+09 6681581.60
July 92426905.32 1514161.62 90912743.70 0.226481E+09 2621003.30
August 0.106999E+09 11095561.45 95903455.93 0.254531E+09 6471315.67
September 0.126968E+09 33800080.62 93168340.15 0.269211E+09 11954641.05
October 0.200742E+09 0.103568E+09 97173925.57 0.376853E+09 38509518.11
November 0.252115E+09 0.174296E+09 77818523.59 0.397815E+09 0.104592E+09
December 0.267312E+09 0.192110E+09 75201810.74 0.399676E+09 0.152800E+09
           
Annual Sum or Average 0.199237E+10 0.960701E+09 0.103167E+10 0.349873E+10 0.843379E+09
Minimum of Months 85553156.98 747913.61 75201810.74 0.197646E+09 2621003.30
Maximum of Months 0.273481E+09 0.195142E+09 97173925.57 0.399676E+09 0.178756E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 47258049.79 0.00 47258049.79 42328186.26 0.168543E+09
February 50357633.19 0.00 50357633.19 52830146.47 0.123166E+09
March 64688976.83 912.10 64688064.73 83515857.58 0.108569E+09
April 74162116.39 500546.93 73661569.45 0.129303E+09 49110530.31
May 86536623.53 3165322.82 83371300.70 0.232099E+09 1780216.97
June 95234062.94 6675848.73 88558214.21 0.258142E+09 1215857.45
July 95524586.07 3689182.50 91835403.57 0.268178E+09 85688.65
August 85746315.80 854852.59 84891463.21 0.243001E+09 1052208.85
September 71471749.28 19311.31 71452437.97 0.189628E+09 1545868.92
October 64139736.56 0.00 64139736.56 0.159281E+09 23122335.19
November 47121625.53 0.00 47121625.53 68738282.36 84346997.50
December 43931728.71 0.00 43931728.71 48117314.90 0.135346E+09
           
Annual Sum or Average 0.826173E+09 14905976.99 0.811267E+09 0.177516E+10 0.697883E+09
Minimum of Months 43931728.71 0.00 43931728.71 42328186.26 85688.65
Maximum of Months 95524586.07 6675848.73 91835403.57 0.268178E+09 0.168543E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.283436E+09 0.144167E+09 0.139269E+09 0.343337E+09 0.371022E+09
February 0.285931E+09 0.138041E+09 0.147890E+09 0.370575E+09 0.271060E+09
March 0.372801E+09 0.179996E+09 0.192805E+09 0.532341E+09 0.241157E+09
April 0.395355E+09 0.178674E+09 0.216681E+09 0.656113E+09 0.120254E+09
May 0.420851E+09 0.182701E+09 0.238150E+09 0.880239E+09 7325621.62
June 0.412280E+09 0.163335E+09 0.248945E+09 0.894211E+09 4412408.73
July 0.411249E+09 0.150546E+09 0.260703E+09 0.915118E+09 613610.11
August 0.379185E+09 0.130480E+09 0.248705E+09 0.837895E+09 4201654.64
September 0.324584E+09 0.111540E+09 0.213045E+09 0.679691E+09 6895542.60
October 0.331940E+09 0.140177E+09 0.191763E+09 0.643426E+09 58432043.59
November 0.283787E+09 0.144470E+09 0.139318E+09 0.419742E+09 0.196218E+09
December 0.231353E+09 0.104941E+09 0.126412E+09 0.299161E+09 0.308233E+09
           
Annual Sum or Average 0.413275E+10 0.176907E+10 0.236369E+10 0.747185E+10 0.158983E+10
Minimum of Months 0.231353E+09 0.104941E+09 0.126412E+09 0.299161E+09 613610.11
Maximum of Months 0.420851E+09 0.182701E+09 0.260703E+09 0.915118E+09 0.371022E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.341920E+09 0.243977E+09 97942916.32 0.501279E+09 0.188919E+09
February 0.277934E+09 0.179241E+09 98693157.69 0.418178E+09 0.140809E+09
March 0.200939E+09 92473951.93 0.108466E+09 0.312283E+09 0.133172E+09
April 0.141926E+09 33320435.70 0.108606E+09 0.252675E+09 68212403.35
May 0.112810E+09 5559641.36 0.107251E+09 0.278022E+09 3957417.81
June 0.106963E+09 935077.94 0.106028E+09 0.273850E+09 2480353.03
July 0.115557E+09 1893078.43 0.113664E+09 0.302726E+09 325019.59
August 0.133775E+09 13872210.08 0.119903E+09 0.337259E+09 2265568.37
September 0.158742E+09 42258503.18 0.116484E+09 0.352465E+09 3725610.81
October 0.250977E+09 0.129485E+09 0.121492E+09 0.486518E+09 31523484.44
November 0.315206E+09 0.217914E+09 97292499.50 0.508441E+09 0.102368E+09
December 0.334207E+09 0.240186E+09 94020957.94 0.512805E+09 0.157634E+09
           
Annual Sum or Average 0.249096E+10 0.120111E+10 0.128984E+10 0.453650E+10 0.835392E+09
Minimum of Months 0.106963E+09 935077.94 94020957.94 0.252675E+09 325019.59
Maximum of Months 0.341920E+09 0.243977E+09 0.121492E+09 0.512805E+09 0.188919E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 59064732.87 0.00 59064732.87 47928564.64 0.209320E+09
February 62938698.60 0.00 62938698.60 58939725.49 0.154423E+09
March 80850503.85 1139.98 80849363.87 93074937.44 0.137653E+09
April 92690358.85 625600.74 92064758.11 0.145265E+09 66372213.20
May 0.108156E+09 3956129.12 0.104200E+09 0.266183E+09 3964008.48
June 0.119027E+09 8343704.90 0.110683E+09 0.299210E+09 2432233.55
July 0.119390E+09 4610866.93 0.114779E+09 0.310024E+09 333160.77
August 0.107169E+09 1068424.11 0.106100E+09 0.279714E+09 2213335.99
September 89327845.69 24135.93 89303709.75 0.215422E+09 3530641.68
October 80164044.51 0.00 80164044.51 0.179128E+09 31930507.21
November 58894225.14 0.00 58894225.14 75487019.67 0.109630E+09
December 54907382.60 0.00 54907382.60 54497819.57 0.168067E+09
           
Annual Sum or Average 0.103258E+10 18630001.72 0.101395E+10 0.202487E+10 0.889869E+09
Minimum of Months 54907382.60 0.00 54907382.60 47928564.64 333160.77
Maximum of Months 0.119390E+09 8343704.90 0.114779E+09 0.310024E+09 0.209320E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.283436E+09 0.144167E+09 0.139269E+09 0.358900E+09 0.355294E+09
February 0.285931E+09 0.138041E+09 0.147890E+09 0.383337E+09 0.261055E+09
March 0.372801E+09 0.179996E+09 0.192805E+09 0.540568E+09 0.236409E+09
April 0.395355E+09 0.178674E+09 0.216681E+09 0.659535E+09 0.118607E+09
May 0.420851E+09 0.182701E+09 0.238150E+09 0.880733E+09 7265423.13
June 0.412280E+09 0.163335E+09 0.248945E+09 0.893474E+09 4444385.06
July 0.411249E+09 0.150546E+09 0.260703E+09 0.914921E+09 619205.11
August 0.379185E+09 0.130480E+09 0.248705E+09 0.839817E+09 4099908.79
September 0.324584E+09 0.111540E+09 0.213045E+09 0.684083E+09 6453058.21
October 0.331940E+09 0.140177E+09 0.191763E+09 0.652881E+09 56073437.36
November 0.283787E+09 0.144470E+09 0.139318E+09 0.433342E+09 0.187184E+09
December 0.231353E+09 0.104941E+09 0.126412E+09 0.313562E+09 0.295127E+09
           
Annual Sum or Average 0.413275E+10 0.176907E+10 0.236369E+10 0.755515E+10 0.153263E+10
Minimum of Months 0.231353E+09 0.104941E+09 0.126412E+09 0.313562E+09 619205.11
Maximum of Months 0.420851E+09 0.182701E+09 0.260703E+09 0.914921E+09 0.355294E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 74801757.40 0.00 74801757.40 56776729.43 0.302458E+09
February 79707890.57 0.00 79707890.57 72713086.76 0.223420E+09
March 0.102392E+09 1443.71 0.102391E+09 0.119143E+09 0.202406E+09
April 0.117386E+09 792283.86 0.116594E+09 0.183920E+09 0.107189E+09
May 0.136973E+09 5010187.92 0.131963E+09 0.314201E+09 17385894.48
June 0.150740E+09 10566775.80 0.140173E+09 0.353870E+09 13295027.21
July 0.151200E+09 5839372.04 0.145360E+09 0.360251E+09 6108040.25
August 0.135722E+09 1353091.72 0.134369E+09 0.323580E+09 12673540.80
September 0.113128E+09 30566.64 0.113098E+09 0.248989E+09 21938523.70
October 0.101523E+09 0.00 0.101523E+09 0.204948E+09 65219591.72
November 74585820.12 0.00 74585820.12 88868062.69 0.173838E+09
December 69536735.60 0.00 69536735.60 62721376.60 0.252699E+09
           
Annual Sum or Average 0.130770E+10 23593721.69 0.128410E+10 0.238998E+10 0.139863E+10
Minimum of Months 69536735.60 0.00 69536735.60 56776729.43 6108040.25
Maximum of Months 0.151200E+09 10566775.80 0.145360E+09 0.360251E+09 0.302458E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27575025.07 0.00 27575025.07 20930253.41 0.111498E+09
February 29383628.91 0.00 29383628.91 26805054.59 82361885.56
March 37745953.68 532.21 37745421.47 43921049.66 74615222.51
April 43273521.19 292068.64 42981452.55 67800644.14 39514395.61
May 50494033.81 1846962.72 48647071.09 0.115828E+09 6409160.60
June 55568981.06 3895351.10 51673629.96 0.130451E+09 4901097.53
July 55738501.02 2152634.32 53585866.70 0.132803E+09 2251676.55
August 50032890.03 498805.64 49534084.40 0.119285E+09 4671991.91
September 41703694.66 11268.13 41692426.53 91787611.75 8087448.24
October 37425472.53 0.00 37425472.53 75552227.74 24042642.04
November 27495421.65 0.00 27495421.65 32760447.65 64083952.47
December 25634120.03 0.00 25634120.03 23121696.50 93155368.73
           
Annual Sum or Average 0.482071E+09 8697622.75 0.473374E+09 0.881046E+09 0.515593E+09
Minimum of Months 25634120.03 0.00 25634120.03 20930253.41 2251676.55
Maximum of Months 55738501.02 3895351.10 53585866.70 0.132803E+09 0.111498E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.159538E+09 0.113839E+09 45699770.07 0.235290E+09 96722401.99
February 0.129683E+09 83633086.99 46049829.68 0.196717E+09 72797860.66
March 93757548.97 43147973.33 50609575.64 0.147738E+09 71106306.19
April 66222146.59 15547181.03 50674965.56 0.118654E+09 40109543.61
May 52636844.82 2594106.25 50042738.57 0.121499E+09 6526419.90
June 49908371.32 436303.60 49472067.73 0.118489E+09 5044031.39
July 53918247.72 883302.77 53034944.95 0.129233E+09 2244257.53
August 62419048.92 6472717.32 55946331.60 0.146472E+09 4727251.85
September 74068419.14 19717647.30 54350771.85 0.156516E+09 8086873.08
October 0.117105E+09 60417350.15 56687473.98 0.220558E+09 23008558.00
November 0.147074E+09 0.101678E+09 45396288.21 0.236968E+09 57453919.09
December 0.155939E+09 0.112070E+09 43869800.10 0.239346E+09 83735862.22
           
Annual Sum or Average 0.116227E+10 0.560435E+09 0.601835E+09 0.206748E+10 0.471563E+09
Minimum of Months 49908371.32 436303.60 43869800.10 0.118489E+09 2244257.53
Maximum of Months 0.159538E+09 0.113839E+09 56687473.98 0.239346E+09 96722401.99



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.433020E+09 0.308981E+09 0.124039E+09 0.638626E+09 0.262524E+09
February 0.351986E+09 0.226997E+09 0.124989E+09 0.533930E+09 0.197588E+09
March 0.254477E+09 0.117112E+09 0.137365E+09 0.400991E+09 0.192997E+09
April 0.179740E+09 42198229.41 0.137542E+09 0.322051E+09 0.108866E+09
May 0.142867E+09 7040934.98 0.135826E+09 0.329774E+09 17714038.56
June 0.135462E+09 1184217.21 0.134277E+09 0.321604E+09 13690532.93
July 0.146345E+09 2397464.39 0.143948E+09 0.350764E+09 6091373.99
August 0.169418E+09 17568278.77 0.151850E+09 0.397555E+09 12830770.26
September 0.201037E+09 53517727.92 0.147519E+09 0.424815E+09 21949427.68
October 0.317846E+09 0.163985E+09 0.153861E+09 0.598638E+09 62449932.71
November 0.399189E+09 0.275974E+09 0.123215E+09 0.643180E+09 0.155942E+09
December 0.423251E+09 0.304180E+09 0.119072E+09 0.649633E+09 0.227276E+09
           
Annual Sum or Average 0.315464E+10 0.152114E+10 0.163350E+10 0.561156E+10 0.127992E+10
Minimum of Months 0.135462E+09 1184217.21 0.119072E+09 0.321604E+09 6091373.99
Maximum of Months 0.433020E+09 0.308981E+09 0.153861E+09 0.649633E+09 0.262524E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.341920E+09 0.243977E+09 97942916.32 0.500509E+09 0.187659E+09
February 0.277934E+09 0.179241E+09 98693157.69 0.417067E+09 0.140216E+09
March 0.200939E+09 92473951.93 0.108466E+09 0.313346E+09 0.131368E+09
April 0.141926E+09 33320435.70 0.108606E+09 0.252462E+09 67542301.37
May 0.112810E+09 5559641.36 0.107251E+09 0.279838E+09 3545417.21
June 0.106963E+09 935077.94 0.106028E+09 0.274500E+09 2275335.54
July 0.115557E+09 1893078.43 0.113664E+09 0.304568E+09 274769.75
August 0.133775E+09 13872210.08 0.119903E+09 0.337325E+09 2079864.72
September 0.158742E+09 42258503.18 0.116484E+09 0.352030E+09 3466694.01
October 0.250977E+09 0.129485E+09 0.121492E+09 0.484716E+09 30950927.68
November 0.315206E+09 0.217914E+09 97292499.50 0.507699E+09 0.100686E+09
December 0.334207E+09 0.240186E+09 94020957.94 0.510449E+09 0.156381E+09
           
Annual Sum or Average 0.249096E+10 0.120111E+10 0.128984E+10 0.453451E+10 0.826444E+09
Minimum of Months 0.106963E+09 935077.94 94020957.94 0.252462E+09 274769.75
Maximum of Months 0.341920E+09 0.243977E+09 0.121492E+09 0.510449E+09 0.187659E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.302011E+09 0.163309E+09 0.138702E+09 0.389769E+09 0.382478E+09
February 0.309574E+09 0.156958E+09 0.152616E+09 0.420649E+09 0.281432E+09
March 0.336028E+09 0.148239E+09 0.187789E+09 0.482397E+09 0.249498E+09
April 0.404297E+09 0.185778E+09 0.218519E+09 0.672263E+09 0.122348E+09
May 0.348326E+09 0.113586E+09 0.234741E+09 0.759097E+09 6470397.30
June 0.374077E+09 0.131254E+09 0.242823E+09 0.823921E+09 4162248.74
July 0.352346E+09 97440319.81 0.254905E+09 0.809945E+09 489550.53
August 0.356060E+09 0.108256E+09 0.247804E+09 0.799570E+09 3763677.99
September 0.318033E+09 0.109105E+09 0.208928E+09 0.668037E+09 6125057.07
October 0.337210E+09 0.146094E+09 0.191115E+09 0.657097E+09 59652736.50
November 0.278951E+09 0.140148E+09 0.138803E+09 0.426711E+09 0.203485E+09
December 0.276332E+09 0.146515E+09 0.129817E+09 0.382821E+09 0.310561E+09
           
Annual Sum or Average 0.399324E+10 0.164668E+10 0.234656E+10 0.729228E+10 0.163047E+10
Minimum of Months 0.276332E+09 97440319.81 0.129817E+09 0.382821E+09 489550.53
Maximum of Months 0.404297E+09 0.185778E+09 0.254905E+09 0.823921E+09 0.382478E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 59064732.87 0.00 59064732.87 50500555.46 0.206412E+09
February 62938698.60 0.00 62938698.60 60641614.54 0.152687E+09
March 80850503.85 1139.98 80849363.87 96610646.59 0.135112E+09
April 92690358.85 625600.74 92064758.11 0.146618E+09 65564196.33
May 0.108156E+09 3956129.12 0.104200E+09 0.268135E+09 3558856.23
June 0.119027E+09 8343704.90 0.110683E+09 0.299726E+09 2182599.23
July 0.119390E+09 4610866.93 0.114779E+09 0.311431E+09 287986.13
August 0.107169E+09 1068424.11 0.106100E+09 0.280669E+09 2040896.57
September 89327845.69 24135.93 89303709.75 0.216685E+09 3248807.08
October 80164044.51 0.00 80164044.51 0.181074E+09 31021570.02
November 58894225.14 0.00 58894225.14 78367245.18 0.106755E+09
December 54907382.60 0.00 54907382.60 56094822.71 0.165948E+09
           
Annual Sum or Average 0.103258E+10 18630001.72 0.101395E+10 0.204655E+10 0.874820E+09
Minimum of Months 54907382.60 0.00 54907382.60 50500555.46 287986.13
Maximum of Months 0.119390E+09 8343704.90 0.114779E+09 0.311431E+09 0.206412E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.302011E+09 0.163309E+09 0.138702E+09 0.409868E+09 0.368596E+09
February 0.309574E+09 0.156958E+09 0.152616E+09 0.436224E+09 0.272303E+09
March 0.336028E+09 0.148239E+09 0.187789E+09 0.492413E+09 0.244475E+09
April 0.404297E+09 0.185778E+09 0.218519E+09 0.676687E+09 0.120533E+09
May 0.348326E+09 0.113586E+09 0.234741E+09 0.759575E+09 6405371.43
June 0.374077E+09 0.131254E+09 0.242823E+09 0.823033E+09 4190572.49
July 0.352346E+09 97440319.81 0.254905E+09 0.809665E+09 495700.04
August 0.356060E+09 0.108256E+09 0.247804E+09 0.801637E+09 3664560.92
September 0.318033E+09 0.109105E+09 0.208928E+09 0.672873E+09 5684694.91
October 0.337210E+09 0.146094E+09 0.191115E+09 0.667728E+09 57107443.89
November 0.278951E+09 0.140148E+09 0.138803E+09 0.442761E+09 0.193956E+09
December 0.276332E+09 0.146515E+09 0.129817E+09 0.400478E+09 0.298159E+09
           
Annual Sum or Average 0.399324E+10 0.164668E+10 0.234656E+10 0.739294E+10 0.157557E+10
Minimum of Months 0.276332E+09 97440319.81 0.129817E+09 0.400478E+09 495700.04
Maximum of Months 0.404297E+09 0.185778E+09 0.254905E+09 0.823033E+09 0.368596E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.501458E+09 0.357815E+09 0.143643E+09 0.717096E+09 0.287726E+09
February 0.407617E+09 0.262874E+09 0.144743E+09 0.600573E+09 0.212540E+09
March 0.294697E+09 0.135622E+09 0.159075E+09 0.455037E+09 0.196053E+09
April 0.208148E+09 48867616.73 0.159281E+09 0.375299E+09 95550774.41
May 0.165447E+09 8153747.61 0.157293E+09 0.423912E+09 3897678.54
June 0.156871E+09 1371381.54 0.155500E+09 0.418698E+09 2573081.75
July 0.169475E+09 2776381.20 0.166698E+09 0.462427E+09 232803.02
August 0.196194E+09 20344927.40 0.175849E+09 0.508116E+09 2452439.59
September 0.232811E+09 61976150.48 0.170834E+09 0.524230E+09 4171919.14
October 0.368082E+09 0.189903E+09 0.178179E+09 0.712095E+09 45409365.87
November 0.462280E+09 0.319591E+09 0.142689E+09 0.735825E+09 0.153280E+09
December 0.490146E+09 0.352255E+09 0.137891E+09 0.735426E+09 0.240390E+09
           
Annual Sum or Average 0.365323E+10 0.176155E+10 0.189168E+10 0.666873E+10 0.124428E+10
Minimum of Months 0.156871E+09 1371381.54 0.137891E+09 0.375299E+09 232803.02
Maximum of Months 0.501458E+09 0.357815E+09 0.178179E+09 0.735825E+09 0.287726E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.413437E+09 0.00 0.413437E+09 0.242392E+09 0.194509E+10
February 0.440554E+09 0.00 0.440554E+09 0.320125E+09 0.145546E+10
March 0.565932E+09 7979.55 0.565924E+09 0.539611E+09 0.135037E+10
April 0.648808E+09 4379039.32 0.644429E+09 0.886311E+09 0.721332E+09
May 0.757066E+09 27691855.05 0.729375E+09 0.161445E+10 0.145521E+09
June 0.833156E+09 58403722.31 0.774752E+09 0.184965E+10 0.112260E+09
July 0.835698E+09 32274846.14 0.803423E+09 0.187459E+10 61210842.31
August 0.750152E+09 7478685.52 0.742674E+09 0.167985E+10 0.108426E+09
September 0.625271E+09 168945.14 0.625102E+09 0.128554E+10 0.181065E+09
October 0.561127E+09 0.00 0.561127E+09 0.105154E+10 0.436165E+09
November 0.412244E+09 0.00 0.412244E+09 0.422911E+09 0.110519E+10
December 0.384337E+09 0.00 0.384337E+09 0.280352E+09 0.163355E+10
           
Annual Sum or Average 0.722778E+10 0.130405E+09 0.709738E+10 0.120473E+11 0.925564E+10
Minimum of Months 0.384337E+09 0.00 0.384337E+09 0.242392E+09 61210842.31
Maximum of Months 0.835698E+09 58403722.31 0.803423E+09 0.187459E+10 0.194509E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.413437E+09 0.00 0.413437E+09 0.224189E+09 0.201092E+10
February 0.440554E+09 0.00 0.440554E+09 0.299819E+09 0.150510E+10
March 0.565932E+09 7979.55 0.565924E+09 0.512154E+09 0.139754E+10
April 0.648808E+09 4379039.32 0.644429E+09 0.858875E+09 0.748522E+09
May 0.757066E+09 27691855.05 0.729375E+09 0.158750E+10 0.159138E+09
June 0.833156E+09 58403722.31 0.774752E+09 0.182462E+10 0.123508E+09
July 0.835698E+09 32274846.14 0.803423E+09 0.184579E+10 69791333.76
August 0.750152E+09 7478685.52 0.742674E+09 0.165245E+10 0.120053E+09
September 0.625271E+09 168945.14 0.625102E+09 0.126163E+10 0.197803E+09
October 0.561127E+09 0.00 0.561127E+09 0.102645E+10 0.457652E+09
November 0.412244E+09 0.00 0.412244E+09 0.401533E+09 0.114438E+10
December 0.384337E+09 0.00 0.384337E+09 0.262589E+09 0.169173E+10
           
Annual Sum or Average 0.722778E+10 0.130405E+09 0.709738E+10 0.117576E+11 0.962614E+10
Minimum of Months 0.384337E+09 0.00 0.384337E+09 0.224189E+09 69791333.76
Maximum of Months 0.835698E+09 58403722.31 0.803423E+09 0.184579E+10 0.201092E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 59064732.87 0.00 59064732.87 43203683.76 0.272186E+09
February 62938698.60 0.00 62938698.60 57601737.25 0.202751E+09
March 80850503.85 1139.98 80849363.87 92333380.38 0.193322E+09
April 92690358.85 625600.74 92064758.11 0.154079E+09 0.103711E+09
May 0.108156E+09 3956129.12 0.104200E+09 0.270865E+09 28436974.69
June 0.119027E+09 8343704.90 0.110683E+09 0.308585E+09 23609809.35
July 0.119390E+09 4610866.93 0.114779E+09 0.310814E+09 15491073.75
August 0.107169E+09 1068424.11 0.106100E+09 0.279591E+09 22324423.27
September 89327845.69 24135.93 89303709.75 0.218591E+09 32415719.87
October 80164044.51 0.00 80164044.51 0.178677E+09 66984086.05
November 58894225.14 0.00 58894225.14 77610783.99 0.150619E+09
December 54907382.60 0.00 54907382.60 51461898.07 0.226448E+09
           
Annual Sum or Average 0.103258E+10 18630001.72 0.101395E+10 0.204341E+10 0.133830E+10
Minimum of Months 54907382.60 0.00 54907382.60 43203683.76 15491073.75
Maximum of Months 0.119390E+09 8343704.90 0.114779E+09 0.310814E+09 0.272186E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.566831E+09 0.288314E+09 0.278517E+09 0.685603E+09 0.924545E+09
February 0.571821E+09 0.276062E+09 0.295759E+09 0.750837E+09 0.688597E+09
March 0.745549E+09 0.359965E+09 0.385583E+09 0.106971E+10 0.669483E+09
April 0.790655E+09 0.357323E+09 0.433331E+09 0.134922E+10 0.375774E+09
May 0.841642E+09 0.365375E+09 0.476267E+09 0.176968E+10 0.107942E+09
June 0.824502E+09 0.326648E+09 0.497854E+09 0.181606E+10 89815749.35
July 0.822440E+09 0.301071E+09 0.521369E+09 0.182600E+10 59811343.42
August 0.758316E+09 0.260941E+09 0.497375E+09 0.167130E+10 83614213.95
September 0.649122E+09 0.223063E+09 0.426059E+09 0.137372E+10 0.121769E+09
October 0.663833E+09 0.280334E+09 0.383498E+09 0.129686E+10 0.241954E+09
November 0.567535E+09 0.288919E+09 0.278615E+09 0.869426E+09 0.519923E+09
December 0.462673E+09 0.209866E+09 0.252806E+09 0.605105E+09 0.793552E+09
           
Annual Sum or Average 0.826492E+10 0.353788E+10 0.472703E+10 0.150835E+11 0.467678E+10
Minimum of Months 0.462673E+09 0.209866E+09 0.252806E+09 0.605105E+09 59811343.42
Maximum of Months 0.841642E+09 0.365375E+09 0.521369E+09 0.182600E+10 0.924545E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.341920E+09 0.243977E+09 97942916.32 0.503141E+09 0.235298E+09
February 0.277934E+09 0.179241E+09 98693157.69 0.421913E+09 0.178280E+09
March 0.200939E+09 92473951.93 0.108466E+09 0.315805E+09 0.183010E+09
April 0.141926E+09 33320435.70 0.108606E+09 0.263483E+09 0.104738E+09
May 0.112810E+09 5559641.36 0.107251E+09 0.282689E+09 28695187.06
June 0.106963E+09 935077.94 0.106028E+09 0.283816E+09 24049023.83
July 0.115557E+09 1893078.43 0.113664E+09 0.302384E+09 15819412.37
August 0.133775E+09 13872210.08 0.119903E+09 0.337878E+09 22505983.68
September 0.158742E+09 42258503.18 0.116484E+09 0.358356E+09 32370466.97
October 0.250977E+09 0.129485E+09 0.121492E+09 0.493651E+09 63920707.76
November 0.315206E+09 0.217914E+09 97292499.50 0.520236E+09 0.137011E+09
December 0.334207E+09 0.240186E+09 94020957.94 0.517584E+09 0.203162E+09
           
Annual Sum or Average 0.249096E+10 0.120111E+10 0.128984E+10 0.460094E+10 0.122886E+10
Minimum of Months 0.106963E+09 935077.94 94020957.94 0.263483E+09 15819412.37
Maximum of Months 0.341920E+09 0.243977E+09 0.121492E+09 0.520236E+09 0.235298E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 74801757.40 0.00 74801757.40 52234944.87 0.302705E+09
February 79707890.57 0.00 79707890.57 66699000.15 0.225804E+09
March 0.102392E+09 1443.71 0.102391E+09 0.111511E+09 0.205133E+09
April 0.117386E+09 792283.86 0.116594E+09 0.172804E+09 0.111649E+09
May 0.136973E+09 5010187.92 0.131963E+09 0.298661E+09 21652619.81
June 0.150740E+09 10566775.80 0.140173E+09 0.338493E+09 17010620.82
July 0.151200E+09 5839372.04 0.145360E+09 0.343631E+09 8652386.27
August 0.135722E+09 1353091.72 0.134369E+09 0.308324E+09 16012985.39
September 0.113128E+09 30566.64 0.113098E+09 0.237243E+09 26562576.07
October 0.101523E+09 0.00 0.101523E+09 0.194711E+09 68114435.16
November 74585820.12 0.00 74585820.12 83483137.11 0.173867E+09
December 69536735.60 0.00 69536735.60 57661554.20 0.253476E+09
           
Annual Sum or Average 0.130770E+10 23593721.69 0.128410E+10 0.226546E+10 0.143064E+10
Minimum of Months 69536735.60 0.00 69536735.60 52234944.87 8652386.27
Maximum of Months 0.151200E+09 10566775.80 0.145360E+09 0.343631E+09 0.302705E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66925415.77 0.00 66925415.77 46734803.09 0.270823E+09
February 71314951.70 0.00 71314951.70 59675848.16 0.202028E+09
March 91610565.60 1291.69 91609273.91 99769358.66 0.183533E+09
April 0.105026E+09 708859.37 0.104317E+09 0.154608E+09 99893218.69
May 0.122551E+09 4482634.11 0.118068E+09 0.267213E+09 19372680.99
June 0.134868E+09 9454134.35 0.125413E+09 0.302851E+09 15219466.90
July 0.135279E+09 5224508.29 0.130055E+09 0.307448E+09 7741322.78
August 0.121431E+09 1210616.29 0.120221E+09 0.275859E+09 14326878.70
September 0.101216E+09 27348.09 0.101189E+09 0.212263E+09 23765637.45
October 90832748.20 0.00 90832748.20 0.174209E+09 60942382.86
November 66732215.87 0.00 66732215.87 74692679.09 0.155559E+09
December 62214780.81 0.00 62214780.81 51590011.01 0.226782E+09
           
Annual Sum or Average 0.117000E+10 21109392.19 0.114889E+10 0.202691E+10 0.127999E+10
Minimum of Months 62214780.81 0.00 62214780.81 46734803.09 7741322.78
Maximum of Months 0.135279E+09 9454134.35 0.130055E+09 0.307448E+09 0.270823E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.127649E+10 0.910837E+09 0.365650E+09 0.185237E+10 0.772162E+09
February 0.103761E+10 0.669160E+09 0.368451E+09 0.154158E+10 0.586890E+09
March 0.750167E+09 0.345233E+09 0.404934E+09 0.114981E+10 0.576509E+09
April 0.529852E+09 0.124395E+09 0.405457E+09 0.912412E+09 0.335213E+09
May 0.421155E+09 20755797.87 0.400399E+09 0.925488E+09 65553324.09
June 0.399324E+09 3490924.59 0.395833E+09 0.902869E+09 52144857.46
July 0.431407E+09 7067425.89 0.424340E+09 0.985031E+09 25552454.43
August 0.499423E+09 51789093.93 0.447634E+09 0.112416E+10 48431840.08
September 0.592632E+09 0.157764E+09 0.434868E+09 0.121253E+10 78888692.69
October 0.936972E+09 0.483407E+09 0.453564E+09 0.172441E+10 0.193245E+09
November 0.117676E+10 0.813536E+09 0.363222E+09 0.186863E+10 0.459900E+09
December 0.124769E+10 0.896684E+09 0.351008E+09 0.188541E+10 0.670062E+09
           
Annual Sum or Average 0.929948E+10 0.448412E+10 0.481536E+10 0.160847E+11 0.386455E+10
Minimum of Months 0.399324E+09 3490924.59 0.351008E+09 0.902869E+09 25552454.43
Maximum of Months 0.127649E+10 0.910837E+09 0.453564E+09 0.188541E+10 0.772162E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 934.32 377.21 645.66 460.71 184.95 0.00 0.00
February 861.40 317.67 581.06 374.73 206.33 0.00 0.00
March 587.30 272.43 379.44 174.62 204.82 0.00 0.00
April 484.06 162.20 276.94 65.02 211.92 0.00 0.00
May 469.02 31.84 213.02 10.50 202.52 0.00 0.00
June 467.95 26.11 208.71 1.82 206.89 0.00 0.00
July 490.29 12.69 218.21 3.57 214.63 0.00 0.00
August 559.58 25.56 252.61 26.20 226.42 0.00 0.00
September 627.97 42.12 309.75 82.46 227.29 0.00 0.00
October 866.32 99.17 473.93 244.51 229.42 0.00 0.00
November 967.46 237.77 615.06 425.21 189.84 0.00 0.00
December 949.77 327.93 631.09 453.55 177.54 0.00 0.00
               
Annual Sum or Average 687.94 160.25 399.50 192.63 206.86 0.00 0.00
Minimum of Months 467.95 12.69 208.71 1.82 177.54 0.00 0.00
Maximum of Months 967.46 377.21 645.66 460.71 229.42 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2579.90 1174.28 1818.13 1297.33 520.80 0.00 0.00
February 2375.87 994.94 1636.24 1055.22 581.02 0.00 0.00
March 1612.19 869.13 1068.48 491.72 576.75 0.00 0.00
April 1326.69 530.50 779.83 183.09 596.75 0.00 0.00
May 1297.30 112.00 599.86 29.56 570.29 0.00 0.00
June 1306.83 90.53 587.72 5.14 582.58 0.00 0.00
July 1368.42 49.43 614.46 10.07 604.39 0.00 0.00
August 1564.54 87.74 711.34 73.76 637.57 0.00 0.00
September 1750.66 146.71 872.23 232.20 640.04 0.00 0.00
October 2415.89 315.64 1334.55 688.53 646.02 0.00 0.00
November 2682.82 751.29 1731.95 1197.37 534.59 0.00 0.00
December 2632.42 1024.78 1777.12 1277.17 499.95 0.00 0.00
               
Annual Sum or Average 1907.19 509.73 1124.96 542.45 582.51 0.00 0.00
Minimum of Months 1297.30 49.43 587.72 5.14 499.95 0.00 0.00
Maximum of Months 2682.82 1174.28 1818.13 1297.33 646.02 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3438.28 1556.95 2361.86 1685.31 676.55 0.00 0.00
February 3171.07 1319.41 2125.57 1370.79 754.78 0.00 0.00
March 2147.26 1171.71 1388.01 638.78 749.24 0.00 0.00
April 1766.88 709.29 1013.05 237.84 775.21 0.00 0.00
May 1734.55 140.84 779.25 38.40 740.84 0.00 0.00
June 1748.71 113.84 763.48 6.67 756.81 0.00 0.00
July 1834.48 60.92 798.22 13.08 785.14 0.00 0.00
August 2097.78 107.82 924.07 95.82 828.24 0.00 0.00
September 2342.12 180.21 1133.08 301.64 831.44 0.00 0.00
October 3227.40 400.43 1733.66 894.44 839.22 0.00 0.00
November 3573.50 978.74 2249.91 1555.45 694.46 0.00 0.00
December 3498.65 1358.77 2308.58 1659.12 649.46 0.00 0.00
               
Annual Sum or Average 2545.36 671.58 1461.38 704.67 756.71 0.00 0.00
Minimum of Months 1734.55 60.92 763.48 6.67 649.46 0.00 0.00
Maximum of Months 3573.50 1556.95 2361.86 1685.31 839.22 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 327.00 208.32 240.42 152.06 88.35 0.00 0.00
February 344.22 171.92 242.85 138.97 103.88 0.00 0.00
March 298.40 143.41 200.48 89.87 110.61 0.00 0.00
April 360.00 74.64 210.73 84.53 126.21 0.00 0.00
May 389.63 4.30 172.17 44.48 127.68 0.00 0.00
June 425.97 2.88 185.59 51.00 134.59 0.00 0.00
July 417.51 0.36 174.69 37.09 137.61 0.00 0.00
August 425.99 2.49 182.88 45.60 137.29 0.00 0.00
September 394.77 4.18 183.94 58.40 125.54 0.00 0.00
October 428.02 35.04 219.60 102.89 116.71 0.00 0.00
November 358.88 116.75 229.23 138.14 91.09 0.00 0.00
December 330.84 173.01 227.95 144.38 83.57 0.00 0.00
               
Annual Sum or Average 375.25 77.65 205.61 90.30 115.31 0.00 0.00
Minimum of Months 298.40 0.36 172.17 37.09 83.57 0.00 0.00
Maximum of Months 428.02 208.32 242.85 152.06 137.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 168.67 215.40 134.81 60.97 73.84 0.00 0.00
February 204.11 176.60 153.98 64.88 89.10 0.00 0.00
March 220.43 143.56 155.64 55.35 100.30 0.00 0.00
April 320.46 73.36 191.74 71.92 119.82 0.00 0.00
May 385.38 4.25 170.43 43.89 126.55 0.00 0.00
June 435.40 2.85 190.24 53.86 136.38 0.00 0.00
July 420.14 0.37 176.13 38.10 138.02 0.00 0.00
August 405.28 2.44 172.95 40.82 132.13 0.00 0.00
September 343.71 3.93 157.16 42.10 115.06 0.00 0.00
October 317.16 34.48 155.83 54.55 101.28 0.00 0.00
November 200.04 119.15 130.34 54.07 76.27 0.00 0.00
December 168.36 175.55 123.67 54.70 68.97 0.00 0.00
               
Annual Sum or Average 299.59 78.85 159.37 52.81 106.56 0.00 0.00
Minimum of Months 168.36 0.37 123.67 38.10 68.97 0.00 0.00
Maximum of Months 435.40 215.40 191.74 71.92 138.02 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 145.30 66.74 102.11 72.86 29.25 0.00 0.00
February 134.53 55.58 91.89 59.26 32.63 0.00 0.00
March 91.53 46.95 60.01 27.62 32.39 0.00 0.00
April 76.25 27.52 43.80 10.28 33.51 0.00 0.00
May 78.37 3.54 33.69 1.66 32.03 0.00 0.00
June 79.79 2.58 33.01 0.29 32.72 0.00 0.00
July 84.56 0.98 34.51 0.57 33.94 0.00 0.00
August 95.03 2.42 39.95 4.14 35.81 0.00 0.00
September 103.86 4.61 48.98 13.04 35.94 0.00 0.00
October 140.70 14.38 74.95 38.67 36.28 0.00 0.00
November 153.48 40.35 97.27 67.24 30.02 0.00 0.00
December 149.22 57.05 99.80 71.73 28.08 0.00 0.00
               
Annual Sum or Average 110.94 26.74 63.18 30.46 32.71 0.00 0.00
Minimum of Months 76.25 0.98 33.01 0.29 28.08 0.00 0.00
Maximum of Months 153.48 66.74 102.11 72.86 36.28 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 15.80 62.93 17.64 0.00 17.64 0.00 0.00
February 21.84 50.91 20.82 0.00 20.82 0.00 0.00
March 31.18 40.53 24.15 0.00 24.15 0.00 0.00
April 49.89 18.95 28.61 0.19 28.42 0.00 0.00
May 86.66 0.66 32.31 1.18 31.13 0.00 0.00
June 99.59 0.47 36.74 2.58 34.17 0.00 0.00
July 100.13 0.03 35.66 1.38 34.29 0.00 0.00
August 90.73 0.39 32.01 0.32 31.69 0.00 0.00
September 73.16 0.60 27.57 0.01 27.57 0.00 0.00
October 59.47 8.63 23.95 0.00 23.95 0.00 0.00
November 26.52 32.54 18.18 0.00 18.18 0.00 0.00
December 17.96 50.53 16.40 0.00 16.40 0.00 0.00
               
Annual Sum or Average 56.29 22.13 26.20 0.47 25.73 0.00 0.00
Minimum of Months 15.80 0.03 16.40 0.00 16.40 0.00 0.00
Maximum of Months 100.13 62.93 36.74 2.58 34.29 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 309.83 203.54 233.48 144.92 88.56 0.00 0.00
February 322.51 166.72 233.08 131.15 101.93 0.00 0.00
March 313.26 137.67 214.21 101.73 112.48 0.00 0.00
April 349.21 71.31 207.28 81.79 125.50 0.00 0.00
May 432.43 4.20 199.25 70.29 128.96 0.00 0.00
June 450.62 2.64 200.33 63.38 136.95 0.00 0.00
July 454.69 0.35 196.69 56.91 139.77 0.00 0.00
August 438.75 2.41 191.52 53.89 137.62 0.00 0.00
September 398.20 4.09 186.47 59.34 127.13 0.00 0.00
October 421.62 33.33 217.64 100.68 116.96 0.00 0.00
November 356.43 113.53 231.09 139.81 91.28 0.00 0.00
December 299.69 170.47 211.16 128.86 82.30 0.00 0.00
               
Annual Sum or Average 379.29 75.41 210.04 94.18 115.85 0.00 0.00
Minimum of Months 299.69 0.35 186.47 53.89 82.30 0.00 0.00
Maximum of Months 454.69 203.54 233.48 144.92 139.77 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 145.62 204.53 127.88 53.83 74.05 0.00 0.00
February 177.62 166.54 144.21 57.06 87.15 0.00 0.00
March 233.08 136.16 169.37 67.20 102.17 0.00 0.00
April 309.38 70.25 188.29 69.17 119.11 0.00 0.00
May 428.21 4.19 197.51 69.69 127.82 0.00 0.00
June 460.14 2.65 204.98 66.23 138.75 0.00 0.00
July 457.34 0.36 198.12 57.93 140.19 0.00 0.00
August 417.98 2.36 181.58 49.11 132.47 0.00 0.00
September 347.02 3.84 159.69 43.04 116.65 0.00 0.00
October 310.05 32.27 153.86 52.34 101.53 0.00 0.00
November 192.81 111.01 132.21 55.74 76.47 0.00 0.00
December 134.04 169.55 106.88 39.18 67.70 0.00 0.00
               
Annual Sum or Average 301.83 74.87 163.79 56.69 107.10 0.00 0.00
Minimum of Months 134.04 0.36 106.88 39.18 67.70 0.00 0.00
Maximum of Months 460.14 204.53 204.98 69.69 140.19 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 340.85 274.23 259.46 157.86 101.60 0.00 0.00
February 334.25 229.25 244.20 128.40 115.79 0.00 0.00
March 264.15 200.43 182.34 59.84 122.50 0.00 0.00
April 267.01 113.94 156.88 22.70 134.18 0.00 0.00
May 328.87 17.77 142.99 6.16 136.83 0.00 0.00
June 356.51 14.11 151.11 6.20 144.91 0.00 0.00
July 363.25 6.19 152.03 4.21 147.82 0.00 0.00
August 368.44 13.00 155.91 9.67 146.24 0.00 0.00
September 355.75 23.17 165.87 28.27 137.60 0.00 0.00
October 410.03 64.68 214.27 83.78 130.49 0.00 0.00
November 380.13 167.76 250.13 145.70 104.43 0.00 0.00
December 354.62 235.91 251.78 155.41 96.37 0.00 0.00
               
Annual Sum or Average 343.77 112.79 193.64 67.03 126.61 0.00 0.00
Minimum of Months 264.15 6.19 142.99 4.21 96.37 0.00 0.00
Maximum of Months 410.03 274.23 259.46 157.86 147.82 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 324.90 205.37 240.42 152.06 88.35 0.00 0.00
February 341.27 169.29 242.85 138.97 103.88 0.00 0.00
March 295.48 140.59 200.48 89.87 110.61 0.00 0.00
April 356.12 72.62 210.73 84.53 126.21 0.00 0.00
May 387.89 3.74 172.17 44.48 127.68 0.00 0.00
June 423.77 2.48 185.59 51.00 134.59 0.00 0.00
July 416.11 0.28 174.69 37.09 137.61 0.00 0.00
August 424.46 2.17 182.88 45.60 137.29 0.00 0.00
September 393.51 3.66 183.94 58.40 125.54 0.00 0.00
October 426.00 33.53 219.60 102.89 116.71 0.00 0.00
November 356.90 113.76 229.23 138.14 91.09 0.00 0.00
December 328.89 169.72 227.95 144.38 83.57 0.00 0.00
               
Annual Sum or Average 373.10 75.98 205.61 90.30 115.31 0.00 0.00
Minimum of Months 295.48 0.28 172.17 37.09 83.57 0.00 0.00
Maximum of Months 426.00 205.37 242.85 152.06 137.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 168.57 211.37 134.81 60.97 73.84 0.00 0.00
February 202.95 173.24 153.98 64.88 89.10 0.00 0.00
March 218.69 140.49 155.64 55.35 100.30 0.00 0.00
April 317.09 71.26 191.74 71.92 119.82 0.00 0.00
May 383.69 3.71 170.43 43.89 126.55 0.00 0.00
June 433.14 2.44 190.24 53.86 136.38 0.00 0.00
July 418.57 0.29 176.13 38.10 138.02 0.00 0.00
August 404.08 2.13 172.95 40.82 132.13 0.00 0.00
September 343.16 3.42 157.16 42.10 115.06 0.00 0.00
October 316.74 32.74 155.83 54.55 101.28 0.00 0.00
November 200.04 115.00 130.34 54.07 76.27 0.00 0.00
December 168.42 171.24 123.67 54.70 68.97 0.00 0.00
               
Annual Sum or Average 298.43 76.81 159.37 52.81 106.56 0.00 0.00
Minimum of Months 168.42 0.29 123.67 38.10 68.97 0.00 0.00
Maximum of Months 433.14 211.37 191.74 71.92 138.02 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 267.73 107.42 187.22 133.59 53.63 0.00 0.00
February 248.25 87.86 168.49 108.66 59.83 0.00 0.00
March 169.89 73.20 110.03 50.64 59.39 0.00 0.00
April 144.79 36.86 80.30 18.85 61.45 0.00 0.00
May 158.27 1.46 61.77 3.04 58.73 0.00 0.00
June 161.53 0.99 60.52 0.53 59.99 0.00 0.00
July 172.65 0.09 63.27 1.04 62.24 0.00 0.00
August 189.71 0.92 73.25 7.60 65.65 0.00 0.00
September 202.25 1.61 89.82 23.91 65.91 0.00 0.00
October 265.87 16.95 137.43 70.90 66.52 0.00 0.00
November 283.88 59.14 178.35 123.30 55.05 0.00 0.00
December 274.58 89.75 183.00 131.52 51.48 0.00 0.00
               
Annual Sum or Average 211.46 39.46 115.84 55.86 59.98 0.00 0.00
Minimum of Months 144.79 0.09 60.52 0.53 51.48 0.00 0.00
Maximum of Months 283.88 107.42 187.22 133.59 66.52 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 90.50 726.21 154.36 0.00 154.36 0.00 0.00
February 132.33 601.63 182.11 0.00 182.11 0.00 0.00
March 201.47 504.17 211.29 0.00 211.29 0.00 0.00
April 341.94 278.29 250.31 1.69 248.62 0.00 0.00
May 602.77 54.33 282.66 10.34 272.32 0.00 0.00
June 713.60 43.31 321.43 22.53 298.90 0.00 0.00
July 699.89 22.85 312.01 12.05 299.96 0.00 0.00
August 627.19 40.48 280.07 2.79 277.28 0.00 0.00
September 495.96 69.86 241.23 0.07 241.17 0.00 0.00
October 392.60 162.85 209.50 0.00 209.50 0.00 0.00
November 163.16 426.38 159.04 0.00 159.04 0.00 0.00
December 104.67 609.90 143.50 0.00 143.50 0.00 0.00
               
Annual Sum or Average 382.02 293.49 229.19 4.14 225.06 0.00 0.00
Minimum of Months 90.50 22.85 143.50 0.00 143.50 0.00 0.00
Maximum of Months 713.60 726.21 321.43 22.53 299.96 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 83.70 750.79 154.36 0.00 154.36 0.00 0.00
February 123.93 622.15 182.11 0.00 182.11 0.00 0.00
March 191.22 521.78 211.29 0.00 211.29 0.00 0.00
April 331.36 288.78 250.31 1.69 248.62 0.00 0.00
May 592.70 59.42 282.66 10.34 272.32 0.00 0.00
June 703.94 47.65 321.43 22.53 298.90 0.00 0.00
July 689.14 26.06 312.01 12.05 299.96 0.00 0.00
August 616.95 44.82 280.07 2.79 277.28 0.00 0.00
September 486.74 76.31 241.23 0.07 241.17 0.00 0.00
October 383.23 170.87 209.50 0.00 209.50 0.00 0.00
November 154.91 441.50 159.04 0.00 159.04 0.00 0.00
December 98.04 631.62 143.50 0.00 143.50 0.00 0.00
               
Annual Sum or Average 372.83 305.24 229.19 4.14 225.06 0.00 0.00
Minimum of Months 83.70 26.06 143.50 0.00 143.50 0.00 0.00
Maximum of Months 703.94 750.79 321.43 22.53 299.96 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 438.80 513.50 361.34 198.73 162.61 0.00 0.00
February 493.94 427.50 377.27 188.20 189.07 0.00 0.00
March 544.55 383.25 383.56 168.92 214.64 0.00 0.00
April 678.58 222.35 395.55 150.95 244.60 0.00 0.00
May 867.32 61.55 396.73 139.97 256.76 0.00 0.00
June 929.05 52.90 405.28 129.60 275.68 0.00 0.00
July 910.64 33.97 394.78 114.84 279.95 0.00 0.00
August 854.35 47.77 373.08 103.00 270.08 0.00 0.00
September 752.43 71.83 346.14 102.37 243.77 0.00 0.00
October 734.02 138.02 371.48 153.01 218.47 0.00 0.00
November 559.24 304.72 363.29 195.54 167.75 0.00 0.00
December 425.91 444.21 318.02 168.03 149.99 0.00 0.00
               
Annual Sum or Average 683.43 224.15 373.81 150.86 222.95 0.00 0.00
Minimum of Months 425.91 33.97 318.02 102.37 149.99 0.00 0.00
Maximum of Months 929.05 513.50 405.28 198.73 279.95 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 707.01 480.89 529.50 340.07 189.43 0.00 0.00
February 675.72 405.70 491.33 276.60 214.73 0.00 0.00
March 505.53 357.71 352.51 128.90 223.62 0.00 0.00
April 478.06 210.67 290.23 48.57 241.65 0.00 0.00
May 556.43 39.42 254.14 11.29 242.84 0.00 0.00
June 595.44 32.23 264.25 9.07 255.18 0.00 0.00
July 610.74 15.55 268.03 6.77 261.26 0.00 0.00
August 637.76 29.35 282.47 20.29 262.18 0.00 0.00
September 641.21 49.84 311.33 60.89 250.45 0.00 0.00
October 780.70 119.47 421.64 180.48 241.16 0.00 0.00
November 772.43 295.01 508.52 313.86 194.65 0.00 0.00
December 730.68 415.44 515.03 334.78 180.24 0.00 0.00
               
Annual Sum or Average 640.90 203.25 373.45 143.61 229.84 0.00 0.00
Minimum of Months 478.06 15.55 254.14 6.77 180.24 0.00 0.00
Maximum of Months 780.70 480.89 529.50 340.07 262.18 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.250249E+10 0.101032E+10 0.172933E+10 0.123397E+10 0.495365E+09 0.00 0.00
February 0.208391E+10 0.768512E+09 0.140571E+10 0.906552E+09 0.499159E+09 0.00 0.00
March 0.157303E+10 0.729668E+09 0.101629E+10 0.467708E+09 0.548584E+09 0.00 0.00
April 0.125469E+10 0.420410E+09 0.717818E+09 0.168526E+09 0.549292E+09 0.00 0.00
May 0.125622E+10 85275377.09 0.570558E+09 28119162.44 0.542439E+09 0.00 0.00
June 0.121293E+10 67682349.53 0.540982E+09 4729371.35 0.536253E+09 0.00 0.00
July 0.131320E+10 33986326.05 0.584448E+09 9574678.74 0.574873E+09 0.00 0.00
August 0.149878E+10 68456273.70 0.676594E+09 70161886.99 0.606432E+09 0.00 0.00
September 0.162769E+10 0.109180E+09 0.802870E+09 0.213732E+09 0.589137E+09 0.00 0.00
October 0.232035E+10 0.265614E+09 0.126937E+10 0.654902E+09 0.614467E+09 0.00 0.00
November 0.250765E+10 0.616293E+09 0.159422E+10 0.110215E+10 0.492075E+09 0.00 0.00
December 0.254386E+10 0.878318E+09 0.169032E+10 0.121479E+10 0.475529E+09 0.00 0.00
               
Annual Sum or Average 0.216948E+11 0.505371E+10 0.125985E+11 0.607491E+10 0.652360E+10 0.00 0.00
Minimum of Months 0.121293E+10 33986326.05 0.540982E+09 4729371.35 0.475529E+09 0.00 0.00
Maximum of Months 0.254386E+10 0.101032E+10 0.172933E+10 0.123397E+10 0.614467E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.691001E+10 0.314519E+10 0.486969E+10 0.347477E+10 0.139491E+10 0.00 0.00
February 0.574771E+10 0.240697E+10 0.395839E+10 0.255279E+10 0.140560E+10 0.00 0.00
March 0.431808E+10 0.232789E+10 0.286181E+10 0.131704E+10 0.154478E+10 0.00 0.00
April 0.343879E+10 0.137505E+10 0.202133E+10 0.474557E+09 0.154677E+10 0.00 0.00
May 0.347469E+10 0.299990E+09 0.160665E+10 79181707.42 0.152747E+10 0.00 0.00
June 0.338729E+10 0.234653E+09 0.152337E+10 13317597.88 0.151005E+10 0.00 0.00
July 0.366519E+10 0.132389E+09 0.164577E+10 26961664.04 0.161880E+10 0.00 0.00
August 0.419047E+10 0.235006E+09 0.190524E+10 0.197571E+09 0.170767E+10 0.00 0.00
September 0.453772E+10 0.380265E+09 0.226083E+10 0.601855E+09 0.165897E+10 0.00 0.00
October 0.647071E+10 0.845406E+09 0.357446E+10 0.184416E+10 0.173030E+10 0.00 0.00
November 0.695386E+10 0.194734E+10 0.448923E+10 0.310358E+10 0.138565E+10 0.00 0.00
December 0.705068E+10 0.274476E+10 0.475984E+10 0.342078E+10 0.133906E+10 0.00 0.00
               
Annual Sum or Average 0.601452E+11 0.160749E+11 0.354766E+11 0.171066E+11 0.183700E+11 0.00 0.00
Minimum of Months 0.338729E+10 0.132389E+09 0.152337E+10 13317597.88 0.133906E+10 0.00 0.00
Maximum of Months 0.705068E+10 0.314519E+10 0.486969E+10 0.347477E+10 0.173030E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.920908E+10 0.417015E+10 0.632600E+10 0.451393E+10 0.181207E+10 0.00 0.00
February 0.767146E+10 0.319193E+10 0.514217E+10 0.331622E+10 0.182595E+10 0.00 0.00
March 0.575122E+10 0.313830E+10 0.371766E+10 0.171090E+10 0.200675E+10 0.00 0.00
April 0.457975E+10 0.183848E+10 0.262582E+10 0.616477E+09 0.200934E+10 0.00 0.00
May 0.464581E+10 0.377229E+09 0.208713E+10 0.102862E+09 0.198427E+10 0.00 0.00
June 0.453267E+10 0.295068E+09 0.197894E+10 17300317.56 0.196164E+10 0.00 0.00
July 0.491347E+10 0.163167E+09 0.213794E+10 35024735.99 0.210292E+10 0.00 0.00
August 0.561870E+10 0.288794E+09 0.247502E+10 0.256656E+09 0.221836E+10 0.00 0.00
September 0.607077E+10 0.467098E+09 0.293694E+10 0.781844E+09 0.215510E+10 0.00 0.00
October 0.864427E+10 0.107250E+10 0.464342E+10 0.239567E+10 0.224775E+10 0.00 0.00
November 0.926252E+10 0.253689E+10 0.583176E+10 0.403172E+10 0.180004E+10 0.00 0.00
December 0.937079E+10 0.363933E+10 0.618330E+10 0.444379E+10 0.173951E+10 0.00 0.00
               
Annual Sum or Average 0.802705E+11 0.211789E+11 0.460861E+11 0.222224E+11 0.238637E+11 0.00 0.00
Minimum of Months 0.453267E+10 0.163167E+09 0.197894E+10 17300317.56 0.173951E+10 0.00 0.00
Maximum of Months 0.937079E+10 0.417015E+10 0.632600E+10 0.451393E+10 0.224775E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.875832E+09 0.557969E+09 0.643931E+09 0.407286E+09 0.236645E+09 0.00 0.00
February 0.832739E+09 0.415902E+09 0.587508E+09 0.336199E+09 0.251309E+09 0.00 0.00
March 0.799244E+09 0.384101E+09 0.536967E+09 0.240713E+09 0.296254E+09 0.00 0.00
April 0.933122E+09 0.193475E+09 0.546223E+09 0.219099E+09 0.327124E+09 0.00 0.00
May 0.104359E+10 11505007.55 0.461137E+09 0.119145E+09 0.341991E+09 0.00 0.00
June 0.110411E+10 7463287.41 0.481040E+09 0.132189E+09 0.348851E+09 0.00 0.00
July 0.111826E+10 965543.93 0.467902E+09 99333398.24 0.368569E+09 0.00 0.00
August 0.114097E+10 6679549.64 0.489836E+09 0.122129E+09 0.367707E+09 0.00 0.00
September 0.102324E+10 10844417.08 0.476775E+09 0.151364E+09 0.325411E+09 0.00 0.00
October 0.114640E+10 93863859.06 0.588187E+09 0.275580E+09 0.312607E+09 0.00 0.00
November 0.930225E+09 0.302619E+09 0.594157E+09 0.358062E+09 0.236095E+09 0.00 0.00
December 0.886134E+09 0.463380E+09 0.610538E+09 0.386700E+09 0.223838E+09 0.00 0.00
               
Annual Sum or Average 0.118339E+11 0.244877E+10 0.648420E+10 0.284780E+10 0.363640E+10 0.00 0.00
Minimum of Months 0.799244E+09 965543.93 0.461137E+09 99333398.24 0.223838E+09 0.00 0.00
Maximum of Months 0.114640E+10 0.557969E+09 0.643931E+09 0.407286E+09 0.368569E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.451755E+09 0.576923E+09 0.361076E+09 0.163309E+09 0.197767E+09 0.00 0.00
February 0.493782E+09 0.427236E+09 0.372513E+09 0.156958E+09 0.215555E+09 0.00 0.00
March 0.590408E+09 0.384517E+09 0.416878E+09 0.148240E+09 0.268638E+09 0.00 0.00
April 0.830625E+09 0.190140E+09 0.496987E+09 0.186404E+09 0.310584E+09 0.00 0.00
May 0.103220E+10 11391321.45 0.456483E+09 0.117542E+09 0.338941E+09 0.00 0.00
June 0.112855E+10 7375293.03 0.493104E+09 0.139598E+09 0.353506E+09 0.00 0.00
July 0.112531E+10 979224.21 0.471736E+09 0.102051E+09 0.369684E+09 0.00 0.00
August 0.108550E+10 6535456.95 0.463229E+09 0.109325E+09 0.353904E+09 0.00 0.00
September 0.890900E+09 10188077.32 0.407361E+09 0.109129E+09 0.298231E+09 0.00 0.00
October 0.849488E+09 92343702.63 0.417374E+09 0.146094E+09 0.271279E+09 0.00 0.00
November 0.518514E+09 0.308840E+09 0.337845E+09 0.140148E+09 0.197697E+09 0.00 0.00
December 0.450933E+09 0.470200E+09 0.331239E+09 0.146515E+09 0.184724E+09 0.00 0.00
               
Annual Sum or Average 0.944796E+10 0.248667E+10 0.502582E+10 0.166531E+10 0.336051E+10 0.00 0.00
Minimum of Months 0.450933E+09 979224.21 0.331239E+09 0.102051E+09 0.184724E+09 0.00 0.00
Maximum of Months 0.112855E+10 0.576923E+09 0.496987E+09 0.186404E+09 0.369684E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.389166E+09 0.178756E+09 0.273481E+09 0.195142E+09 78338753.59 0.00 0.00
February 0.325466E+09 0.134449E+09 0.222303E+09 0.143364E+09 78938827.35 0.00 0.00
March 0.245145E+09 0.125741E+09 0.160720E+09 73964452.01 86755164.61 0.00 0.00
April 0.197646E+09 71332129.43 0.113518E+09 26651048.39 86867256.30 0.00 0.00
May 0.209916E+09 9470070.67 90230318.66 4446828.73 85783489.92 0.00 0.00
June 0.206822E+09 6681581.60 85553156.98 747913.61 84805243.37 0.00 0.00
July 0.226481E+09 2621003.30 92426905.32 1514161.62 90912743.70 0.00 0.00
August 0.254531E+09 6471315.67 0.106999E+09 11095561.45 95903455.93 0.00 0.00
September 0.269211E+09 11954641.05 0.126968E+09 33800080.62 93168340.15 0.00 0.00
October 0.376853E+09 38509518.11 0.200742E+09 0.103568E+09 97173925.57 0.00 0.00
November 0.397815E+09 0.104592E+09 0.252115E+09 0.174296E+09 77818523.59 0.00 0.00
December 0.399676E+09 0.152800E+09 0.267312E+09 0.192110E+09 75201810.74 0.00 0.00
               
Annual Sum or Average 0.349873E+10 0.843379E+09 0.199237E+10 0.960701E+09 0.103167E+10 0.00 0.00
Minimum of Months 0.197646E+09 2621003.30 85553156.98 747913.61 75201810.74 0.00 0.00
Maximum of Months 0.399676E+09 0.178756E+09 0.273481E+09 0.195142E+09 97173925.57 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 42328186.26 0.168543E+09 47258049.79 0.00 47258049.79 0.00 0.00
February 52830146.47 0.123166E+09 50357633.19 0.00 50357633.19 0.00 0.00
March 83515857.58 0.108569E+09 64688976.83 912.10 64688064.73 0.00 0.00
April 0.129303E+09 49110530.31 74162116.39 500546.93 73661569.45 0.00 0.00
May 0.232099E+09 1780216.97 86536623.53 3165322.82 83371300.70 0.00 0.00
June 0.258142E+09 1215857.45 95234062.94 6675848.73 88558214.21 0.00 0.00
July 0.268178E+09 85688.65 95524586.07 3689182.50 91835403.57 0.00 0.00
August 0.243001E+09 1052208.85 85746315.80 854852.59 84891463.21 0.00 0.00
September 0.189628E+09 1545868.92 71471749.28 19311.31 71452437.97 0.00 0.00
October 0.159281E+09 23122335.19 64139736.56 0.00 64139736.56 0.00 0.00
November 68738282.36 84346997.50 47121625.53 0.00 47121625.53 0.00 0.00
December 48117314.90 0.135346E+09 43931728.71 0.00 43931728.71 0.00 0.00
               
Annual Sum or Average 0.177516E+10 0.697883E+09 0.826173E+09 14905976.99 0.811267E+09 0.00 0.00
Minimum of Months 42328186.26 85688.65 43931728.71 0.00 43931728.71 0.00 0.00
Maximum of Months 0.268178E+09 0.168543E+09 95524586.07 6675848.73 91835403.57 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.829839E+09 0.545164E+09 0.625355E+09 0.388144E+09 0.237212E+09 0.00 0.00
February 0.780207E+09 0.403323E+09 0.563865E+09 0.317282E+09 0.246583E+09 0.00 0.00
March 0.839023E+09 0.368727E+09 0.573740E+09 0.272469E+09 0.301271E+09 0.00 0.00
April 0.905150E+09 0.184828E+09 0.537282E+09 0.211995E+09 0.325287E+09 0.00 0.00
May 0.115822E+10 11245347.26 0.533661E+09 0.188260E+09 0.345401E+09 0.00 0.00
June 0.116800E+10 6834782.78 0.519243E+09 0.164270E+09 0.354972E+09 0.00 0.00
July 0.121784E+10 938490.86 0.526806E+09 0.152439E+09 0.374367E+09 0.00 0.00
August 0.117515E+10 6461065.94 0.512960E+09 0.144352E+09 0.368608E+09 0.00 0.00
September 0.103213E+10 10595485.49 0.483326E+09 0.153798E+09 0.329528E+09 0.00 0.00
October 0.112927E+10 89278548.73 0.582917E+09 0.269662E+09 0.313254E+09 0.00 0.00
November 0.923866E+09 0.294269E+09 0.598994E+09 0.362383E+09 0.236610E+09 0.00 0.00
December 0.802680E+09 0.456581E+09 0.565559E+09 0.345126E+09 0.220433E+09 0.00 0.00
               
Annual Sum or Average 0.119614E+11 0.237825E+10 0.662371E+10 0.297018E+10 0.365353E+10 0.00 0.00
Minimum of Months 0.780207E+09 938490.86 0.483326E+09 0.144352E+09 0.220433E+09 0.00 0.00
Maximum of Months 0.121784E+10 0.545164E+09 0.625355E+09 0.388144E+09 0.374367E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.390025E+09 0.547810E+09 0.342501E+09 0.144167E+09 0.198333E+09 0.00 0.00
February 0.429700E+09 0.402900E+09 0.348869E+09 0.138041E+09 0.210829E+09 0.00 0.00
March 0.624269E+09 0.364688E+09 0.453651E+09 0.179997E+09 0.273655E+09 0.00 0.00
April 0.801904E+09 0.182082E+09 0.488046E+09 0.179300E+09 0.308746E+09 0.00 0.00
May 0.114691E+10 11222518.50 0.529008E+09 0.186657E+09 0.342351E+09 0.00 0.00
June 0.119267E+10 6866693.01 0.531307E+09 0.171679E+09 0.359628E+09 0.00 0.00
July 0.122494E+10 951947.65 0.530639E+09 0.155157E+09 0.375482E+09 0.00 0.00
August 0.111953E+10 6310762.72 0.486354E+09 0.131548E+09 0.354805E+09 0.00 0.00
September 0.899480E+09 9959832.26 0.413912E+09 0.111564E+09 0.302348E+09 0.00 0.00
October 0.830442E+09 86437424.02 0.412104E+09 0.140177E+09 0.271927E+09 0.00 0.00
November 0.499764E+09 0.287750E+09 0.342682E+09 0.144470E+09 0.198212E+09 0.00 0.00
December 0.359002E+09 0.454136E+09 0.286260E+09 0.104941E+09 0.181319E+09 0.00 0.00
               
Annual Sum or Average 0.951864E+10 0.236111E+10 0.516533E+10 0.178770E+10 0.337763E+10 0.00 0.00
Minimum of Months 0.359002E+09 951947.65 0.286260E+09 0.104941E+09 0.181319E+09 0.00 0.00
Maximum of Months 0.122494E+10 0.547810E+09 0.531307E+09 0.186657E+09 0.375482E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.912929E+09 0.734509E+09 0.694935E+09 0.422819E+09 0.272115E+09 0.00 0.00
February 0.808610E+09 0.554613E+09 0.590760E+09 0.310630E+09 0.280130E+09 0.00 0.00
March 0.707493E+09 0.536825E+09 0.488373E+09 0.160262E+09 0.328110E+09 0.00 0.00
April 0.692080E+09 0.295333E+09 0.406623E+09 58829762.94 0.347793E+09 0.00 0.00
May 0.880853E+09 47586640.98 0.382971E+09 16492191.88 0.366479E+09 0.00 0.00
June 0.924061E+09 36578407.45 0.391679E+09 16082647.71 0.375596E+09 0.00 0.00
July 0.972934E+09 16578605.54 0.407202E+09 11272773.52 0.395929E+09 0.00 0.00
August 0.986817E+09 34827903.14 0.417592E+09 25892893.45 0.391699E+09 0.00 0.00
September 0.922094E+09 60048453.54 0.429937E+09 73277209.98 0.356660E+09 0.00 0.00
October 0.109822E+10 0.173244E+09 0.573899E+09 0.224402E+09 0.349497E+09 0.00 0.00
November 0.985295E+09 0.434836E+09 0.648344E+09 0.377651E+09 0.270692E+09 0.00 0.00
December 0.949804E+09 0.631849E+09 0.674362E+09 0.416250E+09 0.258112E+09 0.00 0.00
               
Annual Sum or Average 0.108412E+11 0.355683E+10 0.610668E+10 0.211386E+10 0.399281E+10 0.00 0.00
Minimum of Months 0.692080E+09 16578605.54 0.382971E+09 11272773.52 0.258112E+09 0.00 0.00
Maximum of Months 0.109822E+10 0.734509E+09 0.694935E+09 0.422819E+09 0.395929E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.870205E+09 0.550064E+09 0.643931E+09 0.407286E+09 0.236645E+09 0.00 0.00
February 0.825606E+09 0.409537E+09 0.587508E+09 0.336199E+09 0.251309E+09 0.00 0.00
March 0.791425E+09 0.376548E+09 0.536967E+09 0.240713E+09 0.296254E+09 0.00 0.00
April 0.923064E+09 0.188229E+09 0.546223E+09 0.219099E+09 0.327124E+09 0.00 0.00
May 0.103893E+10 10008043.82 0.461137E+09 0.119145E+09 0.341991E+09 0.00 0.00
June 0.109842E+10 6436395.45 0.481040E+09 0.132189E+09 0.348851E+09 0.00 0.00
July 0.111451E+10 762653.75 0.467902E+09 99333398.24 0.368569E+09 0.00 0.00
August 0.113686E+10 5812480.32 0.489836E+09 0.122129E+09 0.367707E+09 0.00 0.00
September 0.101997E+10 9498519.58 0.476775E+09 0.151364E+09 0.325411E+09 0.00 0.00
October 0.114101E+10 89797880.92 0.588187E+09 0.275580E+09 0.312607E+09 0.00 0.00
November 0.925096E+09 0.294858E+09 0.594157E+09 0.358062E+09 0.236095E+09 0.00 0.00
December 0.880904E+09 0.454576E+09 0.610538E+09 0.386700E+09 0.223838E+09 0.00 0.00
               
Annual Sum or Average 0.117660E+11 0.239613E+10 0.648420E+10 0.284780E+10 0.363640E+10 0.00 0.00
Minimum of Months 0.791425E+09 762653.75 0.461137E+09 99333398.24 0.223838E+09 0.00 0.00
Maximum of Months 0.114101E+10 0.550064E+09 0.643931E+09 0.407286E+09 0.368569E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.451491E+09 0.566131E+09 0.361076E+09 0.163309E+09 0.197767E+09 0.00 0.00
February 0.490977E+09 0.419102E+09 0.372513E+09 0.156958E+09 0.215555E+09 0.00 0.00
March 0.585733E+09 0.376296E+09 0.416878E+09 0.148240E+09 0.268638E+09 0.00 0.00
April 0.821909E+09 0.184701E+09 0.496987E+09 0.186404E+09 0.310584E+09 0.00 0.00
May 0.102767E+10 9923748.52 0.456483E+09 0.117542E+09 0.338941E+09 0.00 0.00
June 0.112271E+10 6324505.49 0.493104E+09 0.139598E+09 0.353506E+09 0.00 0.00
July 0.112110E+10 782629.23 0.471736E+09 0.102051E+09 0.369684E+09 0.00 0.00
August 0.108229E+10 5693665.68 0.463229E+09 0.109325E+09 0.353904E+09 0.00 0.00
September 0.889479E+09 8854943.46 0.407361E+09 0.109129E+09 0.298231E+09 0.00 0.00
October 0.848352E+09 87678362.73 0.417374E+09 0.146094E+09 0.271279E+09 0.00 0.00
November 0.518494E+09 0.298077E+09 0.337845E+09 0.140148E+09 0.197697E+09 0.00 0.00
December 0.451107E+09 0.458641E+09 0.331239E+09 0.146515E+09 0.184724E+09 0.00 0.00
               
Annual Sum or Average 0.941131E+10 0.242221E+10 0.502582E+10 0.166531E+10 0.336051E+10 0.00 0.00
Minimum of Months 0.451107E+09 782629.23 0.331239E+09 0.102051E+09 0.184724E+09 0.00 0.00
Maximum of Months 0.112271E+10 0.566131E+09 0.496987E+09 0.186404E+09 0.369684E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.717096E+09 0.287726E+09 0.501458E+09 0.357815E+09 0.143643E+09 0.00 0.00
February 0.600573E+09 0.212540E+09 0.407617E+09 0.262874E+09 0.144743E+09 0.00 0.00
March 0.455037E+09 0.196053E+09 0.294697E+09 0.135622E+09 0.159075E+09 0.00 0.00
April 0.375299E+09 95550774.41 0.208148E+09 48867616.73 0.159281E+09 0.00 0.00
May 0.423912E+09 3897678.54 0.165447E+09 8153747.61 0.157293E+09 0.00 0.00
June 0.418698E+09 2573081.75 0.156871E+09 1371381.54 0.155500E+09 0.00 0.00
July 0.462427E+09 232803.02 0.169475E+09 2776381.20 0.166698E+09 0.00 0.00
August 0.508116E+09 2452439.59 0.196194E+09 20344927.40 0.175849E+09 0.00 0.00
September 0.524230E+09 4171919.14 0.232811E+09 61976150.48 0.170834E+09 0.00 0.00
October 0.712095E+09 45409365.87 0.368082E+09 0.189903E+09 0.178179E+09 0.00 0.00
November 0.735825E+09 0.153280E+09 0.462280E+09 0.319591E+09 0.142689E+09 0.00 0.00
December 0.735426E+09 0.240390E+09 0.490146E+09 0.352255E+09 0.137891E+09 0.00 0.00
               
Annual Sum or Average 0.666873E+10 0.124428E+10 0.365323E+10 0.176155E+10 0.189168E+10 0.00 0.00
Minimum of Months 0.375299E+09 232803.02 0.156871E+09 1371381.54 0.137891E+09 0.00 0.00
Maximum of Months 0.735825E+09 0.287726E+09 0.501458E+09 0.357815E+09 0.178179E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.242392E+09 0.194509E+10 0.413437E+09 0.00 0.413437E+09 0.00 0.00
February 0.320125E+09 0.145546E+10 0.440554E+09 0.00 0.440554E+09 0.00 0.00
March 0.539611E+09 0.135037E+10 0.565932E+09 7979.55 0.565924E+09 0.00 0.00
April 0.886311E+09 0.721332E+09 0.648808E+09 4379039.32 0.644429E+09 0.00 0.00
May 0.161445E+10 0.145521E+09 0.757066E+09 27691855.05 0.729375E+09 0.00 0.00
June 0.184965E+10 0.112260E+09 0.833156E+09 58403722.31 0.774752E+09 0.00 0.00
July 0.187459E+10 61210842.31 0.835698E+09 32274846.14 0.803423E+09 0.00 0.00
August 0.167985E+10 0.108426E+09 0.750152E+09 7478685.52 0.742674E+09 0.00 0.00
September 0.128554E+10 0.181065E+09 0.625271E+09 168945.14 0.625102E+09 0.00 0.00
October 0.105154E+10 0.436165E+09 0.561127E+09 0.00 0.561127E+09 0.00 0.00
November 0.422911E+09 0.110519E+10 0.412244E+09 0.00 0.412244E+09 0.00 0.00
December 0.280352E+09 0.163355E+10 0.384337E+09 0.00 0.384337E+09 0.00 0.00
               
Annual Sum or Average 0.120473E+11 0.925564E+10 0.722778E+10 0.130405E+09 0.709738E+10 0.00 0.00
Minimum of Months 0.242392E+09 61210842.31 0.384337E+09 0.00 0.384337E+09 0.00 0.00
Maximum of Months 0.187459E+10 0.194509E+10 0.835698E+09 58403722.31 0.803423E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.224189E+09 0.201092E+10 0.413437E+09 0.00 0.413437E+09 0.00 0.00
February 0.299819E+09 0.150510E+10 0.440554E+09 0.00 0.440554E+09 0.00 0.00
March 0.512154E+09 0.139754E+10 0.565932E+09 7979.55 0.565924E+09 0.00 0.00
April 0.858875E+09 0.748522E+09 0.648808E+09 4379039.32 0.644429E+09 0.00 0.00
May 0.158750E+10 0.159138E+09 0.757066E+09 27691855.05 0.729375E+09 0.00 0.00
June 0.182462E+10 0.123508E+09 0.833156E+09 58403722.31 0.774752E+09 0.00 0.00
July 0.184579E+10 69791333.76 0.835698E+09 32274846.14 0.803423E+09 0.00 0.00
August 0.165245E+10 0.120053E+09 0.750152E+09 7478685.52 0.742674E+09 0.00 0.00
September 0.126163E+10 0.197803E+09 0.625271E+09 168945.14 0.625102E+09 0.00 0.00
October 0.102645E+10 0.457652E+09 0.561127E+09 0.00 0.561127E+09 0.00 0.00
November 0.401533E+09 0.114438E+10 0.412244E+09 0.00 0.412244E+09 0.00 0.00
December 0.262589E+09 0.169173E+10 0.384337E+09 0.00 0.384337E+09 0.00 0.00
               
Annual Sum or Average 0.117576E+11 0.962614E+10 0.722778E+10 0.130405E+09 0.709738E+10 0.00 0.00
Minimum of Months 0.224189E+09 69791333.76 0.384337E+09 0.00 0.384337E+09 0.00 0.00
Maximum of Months 0.184579E+10 0.201092E+10 0.835698E+09 58403722.31 0.803423E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.117529E+10 0.137537E+10 0.967816E+09 0.532291E+09 0.435525E+09 0.00 0.00
February 0.119493E+10 0.103421E+10 0.912694E+09 0.455303E+09 0.457391E+09 0.00 0.00
March 0.145853E+10 0.102650E+10 0.102734E+10 0.452441E+09 0.574898E+09 0.00 0.00
April 0.175888E+10 0.576320E+09 0.102527E+10 0.391269E+09 0.634002E+09 0.00 0.00
May 0.232303E+10 0.164868E+09 0.106261E+10 0.374891E+09 0.687718E+09 0.00 0.00
June 0.240811E+10 0.137118E+09 0.105049E+10 0.335926E+09 0.714565E+09 0.00 0.00
July 0.243907E+10 90989766.31 0.105739E+10 0.307575E+09 0.749812E+09 0.00 0.00
August 0.228828E+10 0.127959E+09 0.999260E+09 0.275882E+09 0.723378E+09 0.00 0.00
September 0.195031E+10 0.186192E+09 0.897192E+09 0.265346E+09 0.631846E+09 0.00 0.00
October 0.196601E+10 0.369685E+09 0.994974E+09 0.409820E+09 0.585154E+09 0.00 0.00
November 0.144954E+10 0.789821E+09 0.941635E+09 0.506833E+09 0.434802E+09 0.00 0.00
December 0.114075E+10 0.118976E+10 0.851786E+09 0.450052E+09 0.401735E+09 0.00 0.00
               
Annual Sum or Average 0.215527E+11 0.706880E+10 0.117885E+11 0.475763E+10 0.703082E+10 0.00 0.00
Minimum of Months 0.114075E+10 90989766.31 0.851786E+09 0.265346E+09 0.401735E+09 0.00 0.00
Maximum of Months 0.243907E+10 0.137537E+10 0.106261E+10 0.532291E+09 0.749812E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.189365E+10 0.128801E+10 0.141821E+10 0.910837E+09 0.507377E+09 0.00 0.00
February 0.163469E+10 0.981457E+09 0.118863E+10 0.669160E+09 0.519474E+09 0.00 0.00
March 0.135401E+10 0.958093E+09 0.944170E+09 0.345236E+09 0.598934E+09 0.00 0.00
April 0.123914E+10 0.546068E+09 0.752265E+09 0.125896E+09 0.626369E+09 0.00 0.00
May 0.149035E+10 0.105571E+09 0.680678E+09 30248619.90 0.650430E+09 0.00 0.00
June 0.154337E+10 83530269.15 0.684931E+09 23511834.74 0.661419E+09 0.00 0.00
July 0.163582E+10 41655079.69 0.717886E+09 18131306.22 0.699755E+09 0.00 0.00
August 0.170818E+10 78611984.37 0.756577E+09 54352801.94 0.702224E+09 0.00 0.00
September 0.166202E+10 0.129195E+09 0.806976E+09 0.157821E+09 0.649154E+09 0.00 0.00
October 0.209102E+10 0.319996E+09 0.112933E+10 0.483407E+09 0.645920E+09 0.00 0.00
November 0.200215E+10 0.764670E+09 0.131808E+10 0.813536E+09 0.504540E+09 0.00 0.00
December 0.195704E+10 0.111271E+10 0.137944E+10 0.896684E+09 0.482760E+09 0.00 0.00
               
Annual Sum or Average 0.202115E+11 0.640956E+10 0.117772E+11 0.452882E+10 0.724836E+10 0.00 0.00
Minimum of Months 0.123914E+10 41655079.69 0.680678E+09 18131306.22 0.482760E+09 0.00 0.00
Maximum of Months 0.209102E+10 0.128801E+10 0.141821E+10 0.910837E+09 0.702224E+09 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 13.57 11.02 8.64 3.24 3.13 48.31 209.17 0.01
February 15.49 12.82 10.40 2.82 4.36 58.07 218.23 0.02
March 17.07 13.58 10.72 3.68 7.24 76.61 186.08 0.03
April 21.23 17.54 15.23 2.65 11.47 90.28 216.86 0.02
May 26.90 22.82 21.10 3.11 19.64 106.10 173.47 0.04
June 27.61 23.37 21.62 2.44 19.77 115.40 187.69 0.03
July 27.94 24.58 23.34 2.53 20.70 123.49 154.05 0.05
August 27.43 23.90 22.52 3.20 20.40 118.51 145.78 0.03
September 26.23 23.37 22.24 3.39 19.02 101.73 135.58 0.05
October 24.23 20.47 18.40 4.11 16.60 78.24 178.15 0.01
November 18.91 15.31 12.62 2.63 7.99 49.56 205.43 0.01
December 15.68 12.88 10.53 3.17 6.01 45.08 191.18 0.02
                 
Annual Sum or Average 21.89 18.50 16.48 3.09 13.08 84.44 183.16 0.03
Minimum of Months 13.57 11.02 8.64 2.44 3.13 45.08 135.58 0.01
Maximum of Months 27.94 24.58 23.34 4.11 20.70 123.49 218.23 0.05



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 27.00 02-JAN-14:00 18.67 14.00 1.50 17.75 146.50 0.00
February 28.30 02-FEB-12:00 20.78 17.20 6.60 17.93 127.50 748.50
March 30.00 26-MAR-13:00 19.88 14.40 3.00 19.52 288.50 548.00
April 33.30 28-APR-14:00 23.06 18.80 4.10 23.15 150.50 762.50
May 33.90 07-MAY-13:00 23.76 19.40 4.10 23.15 287.50 507.50
June 35.00 14-JUN-13:00 23.95 19.40 2.10 24.16 194.50 712.50
July 36.10 21-JUL-15:00 25.96 22.20 1.50 26.65 216.00 245.00
August 36.30 30-AUG-15:00 23.74 18.50 2.40 25.33 116.00 698.50
September 36.40 09-SEP-16:00 26.65 23.40 4.40 26.48 114.00 401.50
October 34.00 05-OCT-14:00 24.05 20.00 2.60 29.55 169.50 606.00
November 30.00 01-NOV-13:00 25.01 23.30 2.00 26.48 216.50 118.00
December 30.00 13-DEC-14:00 21.84 18.00 3.10 20.92 101.50 682.50
                 
Annual Sum or Average                
Minimum of Months 27.00   18.67 14.00 1.50 17.75 101.50 0.00
Maximum of Months 36.40   26.65 23.40 6.60 29.55 288.50 762.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 0.00 05-JAN-05:00 -0.0 -0.0 2.10 -16.0 0.00 0.00
February -3.4 05-FEB-07:10 -5.4 -9.4 4.68 -21.3 0.00 0.00
March 1.10 09-MAR-05:00 -2.1 -7.3 3.60 -14.4 0.00 0.00
April 8.30 11-APR-05:00 6.95 5.50 0.00 -6.9 0.00 0.00
May 21.10 07-MAY-00:00 19.58 18.90 0.00 11.46 0.00 0.00
June 20.60 07-JUN-01:00 18.00 16.70 3.60 10.50 0.00 0.00
July 22.20 11-JUL-19:00 21.37 21.10 2.10 20.22 0.00 0.00
August 20.20 25-AUG-23:00 20.20 20.20 5.30 11.84 0.00 0.00
September 19.20 07-SEP-17:00 19.20 19.20 2.50 16.85 35.00 7.00
October 10.00 28-OCT-04:00 5.56 0.00 3.60 -0.1 0.00 0.00
November 7.20 12-NOV-07:49 4.12 0.18 4.60 -9.0 36.00 517.00
December 0.00 21-DEC-04:00 -0.9 -2.0 2.10 -16.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -3.4   -5.4 -9.4 0.00 -21.3 0.00 0.00
Maximum of Months 22.20   21.37 21.10 5.30 20.22 36.00 517.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 22.11 31-JAN-12:00 25.00 21.00 5.70 20.92 336.50 96.00
February 21.49 24-FEB-12:00 27.70 18.80 4.10 17.75 165.00 746.50
March 22.77 30-MAR-12:00 29.40 20.00 2.50 27.14 340.00 0.00
April 25.55 28-APR-15:00 32.20 23.30 3.60 22.47 156.00 575.50
May 25.84 27-MAY-13:00 31.70 23.90 3.10 22.13 168.50 735.50
June 26.52 29-JUN-16:00 29.40 25.60 1.50 26.32 164.00 36.00
July 27.17 22-JUL-10:00 32.20 25.60 2.10 21.96 191.00 719.50
August 27.24 07-AUG-12:00 31.00 26.00 3.10 27.95 473.00 200.00
September 27.79 10-SEP-12:00 35.00 25.50 2.90 24.66 239.50 662.00
October 28.18 07-OCT-07:00 29.00 28.00 2.60 21.09 95.00 500.50
November 25.01 01-NOV-13:00 30.00 23.30 2.00 26.48 216.50 118.00
December 24.12 12-DEC-13:00 27.00 23.00 2.10 19.17 160.50 599.50
                 
Annual Sum or Average                
Minimum of Months 21.49   25.00 18.80 1.50 17.75 95.00 0.00
Maximum of Months 28.18   35.00 28.00 5.70 27.95 473.00 746.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 21.00 31-JAN-12:00 25.00 22.11 5.70 20.92 336.50 96.00
February 20.20 02-FEB-22:00 21.50 20.56 4.80 14.65 0.00 0.00
March 21.10 07-MAR-08:00 23.30 21.69 2.00 13.91 126.00 566.50
April 23.30 28-APR-15:00 32.20 25.55 3.60 22.47 156.00 575.50
May 24.40 26-MAY-08:20 27.07 25.09 3.10 23.71 252.67 47.33
June 25.60 29-JUN-14:00 27.20 26.00 5.10 24.16 335.00 238.00
July 25.60 02-JUL-05:00 26.10 25.71 2.60 19.52 30.50 8.50
August 26.60 09-AUG-18:00 26.60 26.60 1.90 19.52 26.00 23.00
September 25.50 10-SEP-12:00 35.00 27.79 2.90 24.66 239.50 662.00
October 28.00 07-OCT-07:00 29.00 28.18 2.60 21.09 95.00 500.50
November 23.80 01-NOV-10:00 26.10 24.39 2.00 22.64 228.50 113.00
December 23.00 12-DEC-13:00 27.00 24.12 2.10 19.17 160.50 599.50
                 
Annual Sum or Average                
Minimum of Months 20.20   21.50 20.56 1.90 13.91 0.00 0.00
Maximum of Months 28.00   35.00 28.18 5.70 24.66 336.50 662.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 20.46 29.60 0.00
February 18.00 13.00 16.00 20.78 36.65 0.00
March 18.00 13.00 16.00 22.23 38.94 0.00
April 18.00 13.00 16.00 24.49 49.11 0.00
May 18.00 13.00 16.00 26.95 46.95 0.00
June 18.00 13.00 16.00 28.93 51.71 0.00
July 18.00 13.00 16.00 29.89 48.43 0.00
August 18.00 13.00 16.00 29.58 45.50 0.00
September 18.00 13.00 16.00 28.08 39.22 0.00
October 18.00 13.00 16.00 25.80 37.51 0.00
November 18.00 13.00 16.00 23.35 31.26 0.00
December 18.00 13.00 16.00 21.40 27.18 0.00
             
Annual Sum or Average 18.00 13.00 16.00 25.18 40.17 0.00
Minimum of Months 18.00 13.00 16.00 20.46 27.18 0.00
Maximum of Months 18.00 13.00 16.00 29.89 51.71 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770464E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -161845479.3 81.21 0.00 0.00
February 0.696214E+10 -0.681597E+10 0.00 0.00 672.00 0.00 -146169087.7 81.21 0.00 0.00
March 0.770320E+10 -0.754146E+10 0.00 0.00 744.00 0.00 -161733737.0 81.21 0.00 0.00
April 0.746498E+10 -0.730858E+10 0.00 0.00 720.00 0.00 -156405231.0 81.21 0.00 0.00
May 0.770427E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -161481279.8 81.21 0.00 0.00
June 0.745679E+10 -0.730053E+10 0.00 0.00 720.00 0.00 -156259135.2 81.21 0.00 0.00
July 0.771230E+10 -0.755085E+10 0.00 0.00 744.00 0.00 -161453324.8 81.21 0.00 0.00
August 0.770427E+10 -0.754280E+10 0.00 0.00 744.00 0.00 -161464532.0 81.21 0.00 0.00
September 0.746621E+10 -0.730993E+10 0.00 0.00 720.00 0.00 -156279862.0 81.21 0.00 0.00
October 0.770298E+10 -0.754143E+10 0.00 0.00 744.00 0.00 -161549229.7 81.21 0.00 0.00
November 0.744896E+10 -0.729243E+10 0.00 0.00 720.00 0.00 -156528298.9 81.21 0.00 0.00
December 0.771272E+10 -0.755086E+10 0.00 0.00 744.00 0.00 -161858034.3 81.21 0.00 0.00
                     
Annual Sum or Average 0.907435E+11 -0.888404E+11 0.00 0.00 8760.00 0.00 -0.190303E+10 81.21 0.00 0.00
Minimum of Months 0.696214E+10 -0.755086E+10 0.00 0.00 672.00 0.00 -161858034.3 81.21 0.00 0.00
Maximum of Months 0.771272E+10 -0.681597E+10 0.00 0.00 744.00 0.00 -146169087.7 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.104643E+12 -0.102908E+12 0.00 0.00 744.00 0.00 -0.173419E+10 81.24 0.00 0.00
February 0.940377E+11 -0.924556E+11 0.00 0.00 672.00 0.00 -0.158208E+10 81.25 0.00 0.00
March 0.101671E+12 -0.999042E+11 0.00 0.00 744.00 0.00 -0.176672E+10 81.25 0.00 0.00
April 0.946865E+11 -0.929655E+11 0.00 0.00 720.00 0.00 -0.172097E+10 81.24 0.00 0.00
May 0.936819E+11 -0.919079E+11 0.00 0.00 744.00 0.00 -0.177395E+10 81.25 0.00 0.00
June 0.874074E+11 -0.856969E+11 0.00 0.00 720.00 0.00 -0.171053E+10 81.25 0.00 0.00
July 0.886658E+11 -0.869152E+11 0.00 0.00 744.00 0.00 -0.175058E+10 81.24 0.00 0.00
August 0.891768E+11 -0.874449E+11 0.00 0.00 744.00 0.00 -0.173196E+10 81.24 0.00 0.00
September 0.887584E+11 -0.870844E+11 0.00 0.00 720.00 0.00 -0.167405E+10 81.24 0.00 0.00
October 0.955863E+11 -0.938571E+11 0.00 0.00 744.00 0.00 -0.172916E+10 81.24 0.00 0.00
November 0.965182E+11 -0.948448E+11 0.00 0.00 720.00 0.00 -0.167335E+10 81.25 0.00 0.00
December 0.103045E+12 -0.101314E+12 0.00 0.00 744.00 0.00 -0.173036E+10 81.25 0.00 0.00
                     
Annual Sum or Average 0.113788E+13 -0.111730E+13 0.00 0.00 8760.00 0.00 -0.205779E+11 81.24 0.00 0.00
Minimum of Months 0.874074E+11 -0.102908E+12 0.00 0.00 672.00 0.00 -0.177395E+10 81.24 0.00 0.00
Maximum of Months 0.104643E+12 -0.856969E+11 0.00 0.00 744.00 0.00 -0.158208E+10 81.25 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.577553E+11 -0.562815E+11 0.00 0.00 744.00 0.00 -0.147381E+10 58.98 0.00 0.00
February 0.517737E+11 -0.504210E+11 0.00 0.00 672.00 0.00 -0.135274E+10 58.98 0.00 0.00
March 0.552585E+11 -0.537399E+11 0.00 0.00 744.00 0.00 -0.151861E+10 58.98 0.00 0.00
April 0.502555E+11 -0.487701E+11 0.00 0.00 720.00 0.00 -0.148540E+10 58.98 0.00 0.00
May 0.483441E+11 -0.468155E+11 0.00 0.00 744.00 0.00 -0.152861E+10 58.98 0.00 0.00
June 0.439882E+11 -0.425176E+11 0.00 0.00 720.00 0.00 -0.147058E+10 58.98 0.00 0.00
July 0.439745E+11 -0.424780E+11 0.00 0.00 744.00 0.00 -0.149656E+10 58.98 0.00 0.00
August 0.444501E+11 -0.429797E+11 0.00 0.00 744.00 0.00 -0.147042E+10 58.98 0.00 0.00
September 0.451168E+11 -0.436964E+11 0.00 0.00 720.00 0.00 -0.142036E+10 58.98 0.00 0.00
October 0.499371E+11 -0.484703E+11 0.00 0.00 744.00 0.00 -0.146685E+10 58.98 0.00 0.00
November 0.517914E+11 -0.503722E+11 0.00 0.00 720.00 0.00 -0.141927E+10 58.98 0.00 0.00
December 0.563732E+11 -0.549049E+11 0.00 0.00 744.00 0.00 -0.146832E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.599019E+12 -0.581447E+12 0.00 0.00 8760.00 0.00 -0.175715E+11 58.98 0.00 0.00
Minimum of Months 0.439745E+11 -0.562815E+11 0.00 0.00 672.00 0.00 -0.152861E+10 58.98 0.00 0.00
Maximum of Months 0.577553E+11 -0.424780E+11 0.00 0.00 744.00 0.00 -0.135274E+10 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.93 0.93 01-JAN-07:49 6395.29 36.84 300.83 296.67 647.40 25.46 193.00 272.50
February 295.50 0.93 0.93 01-FEB-11:39 2422.32 27.34 151.17 279.50 499.71 21.97 154.17 246.33
March 296.00 0.93 0.93 02-MAR-12:39 984.89 19.63 5.50 319.50 393.18 21.17 148.50 247.67
April 347.33 0.94 0.93 01-APR-07:19 778.80 18.61 0.00 323.17 318.26 20.35 128.00 235.00
May 353.67 0.93 0.93 01-MAY-06:00 716.86 18.58 0.00 347.17 290.61 20.34 99.67 233.50
June 394.00 0.94 0.93 01-JUN-06:40 673.85 18.20 0.00 348.67 274.61 19.96 84.83 232.83
July 390.00 0.93 0.93 01-JUL-06:40 754.33 18.44 0.00 359.00 299.16 20.18 121.67 251.67
August 380.83 0.94 0.93 01-AUG-06:49 886.79 18.63 0.00 345.83 344.04 20.35 162.17 270.33
September 342.17 0.94 0.93 01-SEP-06:00 1055.71 18.81 0.00 317.17 403.59 20.54 163.00 255.33
October 330.00 0.93 0.93 01-OCT-06:00 1512.25 22.14 58.67 313.50 514.10 21.72 216.67 271.83
November 308.00 0.93 0.93 01-NOV-07:40 5412.04 34.29 265.00 289.00 594.83 24.18 182.00 265.50
December 282.83 0.93 0.93 01-DEC-07:49 6501.39 37.49 279.17 284.33 780.31 26.17 177.83 258.83
                         
Annual Sum or Average 4027.67 0.93     2175.01 23.49 1060.33 3823.50 432.97 21.69 1831.50 3041.33
Minimum of Months 282.83 0.93 0.93   673.85 18.20 0.00 279.50 274.61 19.96 84.83 232.83
Maximum of Months 394.00 0.94 0.93   6501.39 37.49 300.83 359.00 780.31 26.17 216.67 272.50



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.63 0.61 01-JAN-07:49 6734.76 36.91 301.33 301.67 984.61 25.27 179.50 288.33
February 295.50 0.62 0.61 01-FEB-11:39 2721.12 27.34 152.50 286.67 797.92 22.06 144.67 268.33
March 296.00 0.63 0.61 02-MAR-12:39 1199.43 20.14 14.67 331.50 607.95 21.50 168.17 297.67
April 347.33 0.64 0.61 01-APR-07:10 925.90 19.39 4.50 336.17 464.92 20.91 184.17 300.83
May 353.67 0.63 0.61 01-MAY-06:40 834.86 19.50 1.67 369.00 408.19 21.02 186.67 317.83
June 394.00 0.63 0.61 01-JUN-06:19 784.81 19.15 0.00 366.00 385.18 20.68 197.17 318.67
July 390.00 0.62 0.61 01-JUL-06:19 872.27 19.38 0.83 376.33 416.66 20.90 203.33 329.00
August 380.83 0.63 0.61 01-AUG-06:40 1023.38 19.50 3.50 357.50 480.10 21.00 228.67 321.67
September 342.17 0.63 0.61 01-SEP-06:49 1224.08 19.58 20.00 327.33 571.28 21.10 208.17 296.50
October 330.00 0.62 0.61 01-OCT-06:00 1766.82 22.46 75.83 321.67 767.93 21.99 226.67 297.33
November 308.00 0.63 0.61 01-NOV-07:30 5731.46 34.33 265.67 295.00 912.64 24.10 168.17 281.17
December 282.83 0.63 0.61 01-DEC-07:40 6862.55 37.55 279.50 289.83 1138.12 25.95 163.33 273.83
                         
Annual Sum or Average 4027.67 0.63     2381.80 24.05 1120.00 3958.67 638.87 22.07 2258.67 3591.17
Minimum of Months 282.83 0.62 0.61   784.81 19.15 0.00 286.67 385.18 20.68 144.67 268.33
Maximum of Months 394.00 0.64 0.61   6862.55 37.55 301.33 376.33 1138.12 25.95 228.67 329.00



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.83 0.80 01-JAN-08:30 296.90 14.03 0.00 254.17 152.69 17.52 0.00 49.83
February 295.50 0.82 0.80 01-FEB-11:39 339.84 15.05 0.00 252.17 174.65 18.48 0.00 84.50
March 296.00 0.81 0.80 02-MAR-12:39 407.55 16.01 0.00 315.33 199.57 19.27 0.00 154.17
April 347.33 0.81 0.80 01-APR-07:19 501.76 16.44 0.00 334.33 236.29 19.64 11.33 236.33
May 353.67 0.81 0.80 01-MAY-06:40 646.02 17.21 0.00 376.17 289.49 21.20 78.00 314.50
June 394.00 0.81 0.80 01-JUN-06:10 755.92 17.16 0.00 376.83 318.58 22.72 136.00 340.50
July 390.00 0.81 0.80 01-JUL-06:10 759.87 18.03 18.67 383.67 319.09 21.66 118.00 334.17
August 380.83 0.81 0.80 01-AUG-06:40 654.16 16.91 0.00 358.83 285.45 20.28 39.00 312.67
September 342.17 0.81 0.80 01-SEP-06:00 536.10 16.23 0.00 321.00 239.02 19.39 0.67 235.83
October 330.00 0.81 0.80 01-OCT-07:10 439.47 15.97 0.00 304.33 211.02 19.24 0.00 180.50
November 308.00 0.83 0.80 01-NOV-08:09 300.73 14.34 0.00 245.00 156.05 17.82 0.00 49.83
December 282.83 0.83 0.80 01-DEC-08:20 295.37 14.09 0.00 246.00 153.99 17.61 0.00 37.67
                         
Annual Sum or Average 4027.67 0.81     512.21 16.08 18.67 3767.83 234.32 19.72 383.00 2330.50
Minimum of Months 282.83 0.81 0.80   295.37 14.03 0.00 245.00 152.69 17.52 0.00 37.67
Maximum of Months 394.00 0.83 0.80   759.87 18.03 18.67 383.67 319.09 22.72 136.00 340.50



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.83 0.80 01-JAN-08:30 296.90 14.03 0.00 254.17 152.69 17.52 0.00 49.83
February 295.50 0.82 0.80 01-FEB-11:39 339.84 15.05 0.00 252.17 174.65 18.48 0.00 84.50
March 296.00 0.81 0.80 02-MAR-12:39 407.55 16.01 0.00 315.33 199.57 19.27 0.00 154.17
April 347.33 0.81 0.80 01-APR-07:19 501.76 16.44 0.00 334.33 236.29 19.64 11.33 236.33
May 353.67 0.81 0.80 01-MAY-06:40 646.02 17.21 0.00 376.17 289.49 21.20 78.00 314.50
June 394.00 0.81 0.80 01-JUN-06:10 755.92 17.16 0.00 376.83 318.58 22.72 136.00 340.50
July 390.00 0.81 0.80 01-JUL-06:10 759.87 18.03 18.67 383.67 319.09 21.66 117.83 334.17
August 380.83 0.81 0.80 01-AUG-06:40 654.16 16.91 0.00 358.83 285.45 20.28 39.00 312.67
September 342.17 0.81 0.80 01-SEP-06:00 536.10 16.23 0.00 321.00 239.02 19.39 0.67 235.83
October 330.00 0.81 0.80 01-OCT-07:10 439.47 15.97 0.00 304.33 211.02 19.24 0.00 180.50
November 308.00 0.83 0.80 01-NOV-08:09 300.73 14.34 0.00 245.00 156.05 17.82 0.00 49.83
December 282.83 0.83 0.80 01-DEC-08:20 295.37 14.09 0.00 246.00 153.99 17.61 0.00 37.67
                         
Annual Sum or Average 4027.67 0.81     512.21 16.08 18.67 3767.83 234.32 19.72 382.83 2330.50
Minimum of Months 282.83 0.81 0.80   295.37 14.03 0.00 245.00 152.69 17.52 0.00 37.67
Maximum of Months 394.00 0.83 0.80   759.87 18.03 18.67 383.67 319.09 22.72 136.00 340.50



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.164854E+11 89377.86 23-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.818090E+10 89893.92 04-FEB-08:08 0.00 0.00 0.00 0.00 0.00
March 0.980118E+10 106825.60 08-MAR-23:05 0.00 0.00 0.00 0.00 0.00
April 0.979144E+09 75226.64 11-APR-05:46 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.790052E+09 70755.73 28-OCT-05:50 0.00 0.00 0.00 0.00 0.00
November 0.639623E+10 103861.72 12-NOV-08:63 0.00 0.00 0.00 0.00 0.00
December 0.118766E+11 108153.18 18-DEC-00:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.545095E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.164854E+11 108153.18   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.317709E+09 1760.33 09-JAN-05:05 0.00 0.00 0.00 0.00 0.00
February 0.242514E+09 2753.25 06-FEB-08:59 0.00 0.00 0.00 0.00 0.00
March 0.341604E+09 2186.91 12-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 13549188.93 871.55 11-APR-06:30 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 1859331.34 1007.82 28-OCT-05:42 0.00 0.00 0.00 0.00 0.00
November 17419589.47 1310.80 16-NOV-06:30 0.00 0.00 0.00 0.00 0.00
December 0.295074E+09 1853.58 30-DEC-02:20 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.122973E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.341604E+09 2753.25   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 543249.69 199.94 11-MAR-16:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 37075.90 82.77 21-DEC-11:37 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 580325.59     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 543249.69 199.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 24806278.35 667.32 10-JAN-11:47 0.00 0.00 0.00 0.00 0.00
February 43677887.73 1883.72 06-FEB-08:59 0.00 0.00 0.00 0.00 0.00
March 30391569.78 852.02 12-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 30747084.88 670.03 21-DEC-11:37 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.129623E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 43677887.73 1883.72   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 24077580.13 561.93 05-JAN-09:28 0.00 0.00 0.00 0.00 0.00
February 36772436.86 1029.22 06-FEB-08:59 0.00 0.00 0.00 0.00 0.00
March 28562571.04 542.38 12-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 27123868.77 466.95 30-DEC-18:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.116536E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 36772436.86 1029.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.185762E+09 7072.18 09-JAN-05:05 0.00 0.00 0.00 0.00 0.00
February 0.116092E+09 3277.95 14-FEB-04:50 0.00 0.00 0.00 0.00 0.00
March 95411353.85 5867.39 03-MAR-04:13 0.00 0.00 0.00 0.00 0.00
April 14874740.28 3339.79 11-APR-04:03 0.00 0.00 0.00 0.00 0.00
May 233863.17 145.42 01-MAY-04:00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 9167436.44 2283.55 28-OCT-03:30 0.00 0.00 0.00 0.00 0.00
November 79728710.00 8399.94 15-NOV-02:23 0.00 0.00 0.00 0.00 0.00
December 0.161689E+09 8534.07 30-DEC-02:20 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.662959E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.185762E+09 8534.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 8602915.75 1248.58 13-JAN-11:37 0.00 0.00 0.00 0.00 0.00
February 1574623.18 699.90 06-FEB-07:15 0.00 0.00 0.00 0.00 0.00
March 82420350.92 2924.43 10-MAR-10:08 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 59452714.71 2597.84 21-DEC-09:24 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.152051E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 82420350.92 2924.43   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 30300.43 50.50 06-FEB-07:30 0.00 0.00 0.00 0.00 0.00
March 11055081.37 3879.16 12-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 11085381.80     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 11055081.37 3879.16   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.293825E+09 3518.08 05-JAN-09:28 0.00 0.00 0.00 0.00 0.00
February 0.242833E+09 6565.32 06-FEB-08:59 0.00 0.00 0.00 0.00 0.00
March 0.189960E+09 3780.41 12-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 152430.90 508.10 16-NOV-06:30 0.00 0.00 0.00 0.00 0.00
December 0.234132E+09 3837.34 30-DEC-18:17 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.960902E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.293825E+09 6565.32   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 7446.32 0.56 08-JAN-11:15 0.00 0.00 0.00 0.00 0.00
February 43688253.01 2930.67 05-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 10569.66 0.56 16-MAR-08:08 0.00 0.00 0.00 0.00 0.00
April 10637.62 0.56 24-APR-03:05 0.00 0.00 0.00 0.00 0.00
May 8819.24 0.55 28-MAY-18:10 0.00 0.00 0.00 0.00 0.00
June 10101.55 0.56 20-JUN-24:00 0.00 0.00 0.00 0.00 0.00
July 9613.97 0.55 12-JUL-03:05 0.00 0.00 0.00 0.00 0.00
August 8531.70 0.56 04-AUG-14:20 0.00 0.00 0.00 0.00 0.00
September 10906.87 0.56 30-SEP-22:30 0.00 0.00 0.00 0.00 0.00
October 15797.38 0.56 18-OCT-05:50 0.00 0.00 0.00 0.00 0.00
November 37319.76 39.06 18-NOV-12:10 0.00 0.00 0.00 0.00 0.00
December 5801.86 0.55 31-DEC-18:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 43823798.94     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5801.86 0.55   0.00 0.00 0.00 0.00 0.00
Maximum of Months 43688253.01 2930.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.745477E+09 7010.82 05-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.508436E+09 7162.84 05-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.456061E+09 6997.56 09-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 6292309.27 3237.11 23-APR-08:05 0.00 0.00 0.00 0.00 0.00
May 4552532.28 3015.13 21-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 2205625.58 2521.96 01-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 1714458.40 2718.96 15-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 2775216.07 2649.91 18-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 3864265.63 3300.30 16-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 6707564.13 2744.34 22-OCT-08:05 0.00 0.00 0.00 0.00 0.00
November 51567484.62 2924.60 23-NOV-09:03 0.00 0.00 0.00 0.00 0.00
December 0.574480E+09 7115.37 20-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.236413E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1714458.40 2521.96   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.745477E+09 7162.84   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.133960E+10 7092.13 05-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.810304E+09 7146.00 05-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.573950E+09 7016.27 09-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 10184852.02 3420.50 23-APR-08:05 0.00 0.00 0.00 0.00 0.00
May 3131959.30 2937.70 22-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 818382.70 2573.57 01-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 1217789.08 2769.27 12-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 2214465.38 2401.50 01-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 4081894.99 3356.92 16-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 10889373.92 3129.62 15-OCT-08:05 0.00 0.00 0.00 0.00 0.00
November 0.154647E+09 6735.06 15-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.944454E+09 7088.24 20-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.385550E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 818382.70 2401.50   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.133960E+10 7146.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.454882E+10 40338.50 05-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.278502E+10 40462.22 05-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.126930E+10 40028.93 09-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 59558531.62 20339.10 01-APR-15:05 0.00 0.00 0.00 0.00 0.00
May 17595883.94 21152.95 23-MAY-08:06 0.00 0.00 0.00 0.00 0.00
June 19949061.66 15977.26 21-JUN-08:07 0.00 0.00 0.00 0.00 0.00
July 14321211.40 15038.66 10-JUL-08:07 0.00 0.00 0.00 0.00 0.00
August 10470515.67 12909.09 03-AUG-08:07 0.00 0.00 0.00 0.00 0.00
September 21217919.90 17522.53 30-SEP-18:07 0.00 0.00 0.00 0.00 0.00
October 45058621.36 22113.36 27-OCT-15:04 0.00 0.00 0.00 0.00 0.00
November 0.329593E+09 29157.85 12-NOV-16:03 0.00 0.00 0.00 0.00 0.00
December 0.276568E+10 40324.13 20-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.118866E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 10470515.67 12909.09   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.454882E+10 40462.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.775956E+09 6729.69 09-JAN-19:02 0.00 0.00 0.00 0.00 0.00
February 0.499024E+09 6804.18 04-FEB-19:02 0.00 0.00 0.00 0.00 0.00
March 0.446964E+09 6805.48 11-MAR-16:01 0.00 0.00 0.00 0.00 0.00
April 6024368.50 2401.14 11-APR-18:05 0.00 0.00 0.00 0.00 0.00
May 245106.13 1212.61 22-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 173491.52 1734.92 14-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 331002.61 1766.49 17-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 387307.70 1757.11 29-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 4732450.85 2096.89 17-OCT-18:05 0.00 0.00 0.00 0.00 0.00
November 57307779.84 2731.39 25-NOV-09:04 0.00 0.00 0.00 0.00 0.00
December 0.638785E+09 6942.14 20-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.242993E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.775956E+09 6942.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.135687E+10 6805.36 04-JAN-19:01 0.00 0.00 0.00 0.00 0.00
February 0.793036E+09 6861.00 05-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.558087E+09 6782.30 11-MAR-16:01 0.00 0.00 0.00 0.00 0.00
April 12682622.87 3274.41 03-APR-18:05 0.00 0.00 0.00 0.00 0.00
May 203699.54 1123.97 23-MAY-08:06 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 111420.73 1114.21 14-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 275764.43 1524.21 17-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 420402.39 1821.70 29-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 13447778.89 3349.92 27-OCT-15:04 0.00 0.00 0.00 0.00 0.00
November 0.158539E+09 3448.75 23-NOV-16:03 0.00 0.00 0.00 0.00 0.00
December 0.102556E+10 6944.85 20-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.391922E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.135687E+10 6944.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.362391E+09 2127.82 05-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.232520E+09 2147.99 05-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.214748E+09 2120.05 09-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 10325503.01 1095.33 11-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 1779493.01 763.47 21-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 1178309.86 696.92 27-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 871011.70 724.63 25-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 1488915.89 783.26 12-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 1400582.69 722.93 16-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 7186389.62 754.44 28-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 52602216.87 2024.90 15-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.278009E+09 2130.70 20-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.116450E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 871011.70 696.92   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.362391E+09 2147.99   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.579136E+09 2121.80 05-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.347591E+09 2137.10 05-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.262875E+09 2117.56 09-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 15557697.41 1467.37 11-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 1532663.19 783.29 21-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 696462.43 602.75 27-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 535457.95 720.20 25-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 1307578.64 709.36 12-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 1425953.03 727.53 09-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 13899545.96 1450.06 28-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.120661E+09 2038.04 16-NOV-09:02 0.00 0.00 0.00 0.00 0.00
December 0.431149E+09 2119.92 20-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.177637E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 535457.95 602.75   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.579136E+09 2137.10   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.510599E+09 7679.54 13-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.405204E+09 10005.07 05-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.540181E+09 9900.27 09-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 13167358.33 3667.36 11-APR-18:05 0.00 0.00 0.00 0.00 0.00
May 5724297.91 4270.33 22-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 3694841.06 4154.51 09-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 2432649.18 3970.24 13-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 3778164.50 4245.54 15-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 4301019.94 3724.78 29-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 5730806.87 3771.64 25-OCT-08:05 0.00 0.00 0.00 0.00 0.00
November 18922614.74 2365.08 01-NOV-08:06 0.00 0.00 0.00 0.00 0.00
December 0.440593E+09 10058.58 20-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.195433E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2432649.18 2365.08   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.540181E+09 10058.58   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.150064E+12 0.914167E+11 400414.13 19-JAN-22:00 173304.93 0.39
February 0.00 0.00 0.195572E+12 0.115807E+12 366034.69 02-FEB-22:00 172693.70 0.58
March 0.00 0.00 0.259171E+12 0.167162E+12 408874.19 07-MAR-20:00 179546.33 0.56
April 0.00 0.00 0.450998E+12 0.279947E+12 503604.72 28-APR-21:00 212409.16 0.86
May 0.00 0.00 0.845706E+12 0.483209E+12 505307.65 19-MAY-20:30 219470.22 1.00
June 0.00 0.00 0.859748E+12 0.486952E+12 552888.70 29-JUN-22:00 220290.38 1.00
July 0.00 0.00 0.974225E+12 0.512778E+12 486978.86 22-JUL-10:33 228666.15 1.00
August 0.00 0.00 0.942656E+12 0.507113E+12 534199.18 09-AUG-20:20 226176.21 1.00
September 0.00 0.00 0.897075E+12 0.464315E+12 512252.87 09-SEP-21:00 288184.56 1.00
October 0.00 0.00 0.714975E+12 0.410419E+12 542942.11 23-OCT-20:50 228938.25 0.90
November 0.00 0.00 0.337237E+12 0.212749E+12 529079.14 03-NOV-19:20 219001.53 0.72
December 0.00 0.00 0.247057E+12 0.143001E+12 470669.52 15-DEC-22:00 209764.29 0.51
                 
Annual Sum or Average 0.00 0.00 0.687448E+13 0.387487E+13       0.79
Minimum of Months 0.00 0.00 0.150064E+12 0.914167E+11 366034.69   172693.70 0.39
Maximum of Months 0.00 0.00 0.974225E+12 0.512778E+12 552888.70   288184.56 1.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.303380E+11 0.176038E+11 66456.58 20-JAN-03:00 23148.69 0.38
February 0.00 0.00 0.386865E+11 0.220218E+11 62715.68 02-FEB-23:00 24388.57 0.58
March 0.00 0.00 0.513335E+11 0.315313E+11 68410.67 07-MAR-19:02 27466.88 0.57
April 0.00 0.00 0.852135E+11 0.510933E+11 72709.38 24-APR-09:40 25220.71 0.86
May 0.00 0.00 0.133116E+12 0.785760E+11 68049.66 31-MAY-13:00 27716.85 1.00
June 0.00 0.00 0.133945E+12 0.773648E+11 67058.15 27-JUN-15:00 34219.48 1.00
July 0.00 0.00 0.150941E+12 0.807724E+11 67618.10 22-JUL-11:00 34472.89 1.00
August 0.00 0.00 0.145052E+12 0.796453E+11 74811.01 09-AUG-05:40 25743.99 1.00
September 0.00 0.00 0.138064E+12 0.748120E+11 75162.02 26-SEP-08:00 27521.11 1.00
October 0.00 0.00 0.113915E+12 0.669701E+11 84131.07 22-OCT-08:00 28355.40 0.91
November 0.00 0.00 0.608934E+11 0.384690E+11 79982.23 03-NOV-07:40 27221.33 0.71
December 0.00 0.00 0.479885E+11 0.266710E+11 75610.67 15-DEC-09:04 26591.11 0.49
                 
Annual Sum or Average 0.00 0.00 0.112949E+13 0.645531E+12       0.79
Minimum of Months 0.00 0.00 0.303380E+11 0.176038E+11 62715.68   23148.69 0.38
Maximum of Months 0.00 0.00 0.150941E+12 0.807724E+11 84131.07   34472.89 1.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.245299E+10 0.136671E+10 15405.01 19-JAN-19:02 10472.00 0.39
February 0.00 0.00 0.322402E+10 0.170909E+10 15096.94 02-FEB-19:02 10444.79 0.56
March 0.00 0.00 0.371550E+10 0.206023E+10 16313.07 07-MAR-19:02 10017.36 0.54
April 0.00 0.00 0.644210E+10 0.366624E+10 15523.50 28-APR-08:62 10749.43 0.82
May 0.00 0.00 0.103960E+11 0.619190E+10 15337.50 22-MAY-15:02 11009.93 0.93
June 0.00 0.00 0.109559E+11 0.674502E+10 14953.68 19-JUN-08:62 11576.68 0.94
July 0.00 0.00 0.115435E+11 0.701946E+10 15406.54 15-JUL-08:62 11317.03 0.94
August 0.00 0.00 0.114280E+11 0.693005E+10 15629.71 29-AUG-08:62 10854.28 0.94
September 0.00 0.00 0.102778E+11 0.601090E+10 17057.87 05-SEP-08:62 9594.05 0.93
October 0.00 0.00 0.970978E+10 0.597245E+10 15870.35 22-OCT-08:62 10155.91 0.88
November 0.00 0.00 0.506816E+10 0.288507E+10 15863.30 02-NOV-08:62 10121.76 0.71
December 0.00 0.00 0.359237E+10 0.201168E+10 15786.38 12-DEC-09:02 9032.67 0.51
                 
Annual Sum or Average 0.00 0.00 0.888061E+11 0.525688E+11       0.76
Minimum of Months 0.00 0.00 0.245299E+10 0.136671E+10 14953.68   9032.67 0.39
Maximum of Months 0.00 0.00 0.115435E+11 0.701946E+10 17057.87   11576.68 0.94



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.129560E+10 0.598324E+09 14924.69 19-JAN-19:02 9812.65 0.26
February 0.00 0.00 0.199250E+10 0.924384E+09 13950.72 02-FEB-16:02 11251.90 0.43
March 0.00 0.00 0.283019E+10 0.146120E+10 15762.10 07-MAR-19:02 9593.91 0.47
April 0.00 0.00 0.586303E+10 0.328906E+10 15106.66 28-APR-08:62 10420.91 0.79
May 0.00 0.00 0.103004E+11 0.618840E+10 14926.59 22-MAY-15:02 10718.16 0.93
June 0.00 0.00 0.110990E+11 0.696523E+10 14524.72 06-JUN-08:62 10875.41 0.95
July 0.00 0.00 0.115759E+11 0.711453E+10 14911.45 15-JUL-08:62 11064.54 0.94
August 0.00 0.00 0.110783E+11 0.670057E+10 14900.63 29-AUG-08:62 10706.54 0.94
September 0.00 0.00 0.952174E+10 0.545487E+10 16838.65 05-SEP-08:62 9164.53 0.92
October 0.00 0.00 0.818220E+10 0.474670E+10 15695.32 22-OCT-08:62 9639.49 0.83
November 0.00 0.00 0.317693E+10 0.156240E+10 15283.50 02-NOV-08:62 9584.85 0.59
December 0.00 0.00 0.208113E+10 0.981980E+09 15345.67 12-DEC-09:02 8676.13 0.38
                 
Annual Sum or Average 0.00 0.00 0.789969E+11 0.459877E+11       0.70
Minimum of Months 0.00 0.00 0.129560E+10 0.598324E+09 13950.72   8676.13 0.26
Maximum of Months 0.00 0.00 0.115759E+11 0.711453E+10 16838.65   11251.90 0.95



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.179845E+11 0.130108E+11 47841.27 01-JAN-14:00 40469.31 0.32
February 0.00 0.00 0.164022E+11 0.102082E+11 38902.33 27-FEB-15:50 30724.82 0.42
March 0.00 0.00 0.104892E+11 0.520028E+10 32243.48 06-MAR-13:10 24327.83 0.32
April 0.00 0.00 0.131914E+11 0.542975E+10 23463.91 22-APR-13:30 14423.44 0.51
May 0.00 0.00 0.294625E+11 0.124258E+11 26780.01 05-MAY-07:00 10253.66 0.93
June 0.00 0.00 0.302850E+11 0.129562E+11 24680.94 28-JUN-17:20 14757.84 0.96
July 0.00 0.00 0.346643E+11 0.154419E+11 27319.13 19-JUL-17:20 17990.66 0.97
August 0.00 0.00 0.375072E+11 0.178198E+11 30558.92 31-AUG-13:30 22234.73 0.98
September 0.00 0.00 0.376694E+11 0.189586E+11 40282.72 10-SEP-16:00 30556.58 0.94
October 0.00 0.00 0.441847E+11 0.268437E+11 42854.28 07-OCT-13:00 30734.18 0.84
November 0.00 0.00 0.307745E+11 0.207902E+11 45829.99 06-NOV-14:00 36618.72 0.58
December 0.00 0.00 0.242843E+11 0.166864E+11 49576.34 16-DEC-13:30 41308.08 0.42
                 
Annual Sum or Average 0.00 0.00 0.326899E+12 0.175772E+12       0.68
Minimum of Months 0.00 0.00 0.104892E+11 0.520028E+10 23463.91   10253.66 0.32
Maximum of Months 0.00 0.00 0.441847E+11 0.268437E+11 49576.34   41308.08 0.98



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.961707E+10 0.401087E+10 89047.85 19-JAN-19:02 53359.27 0.31
February 0.00 0.00 0.139436E+11 0.597838E+10 83052.40 02-FEB-19:02 56805.51 0.45
March 0.00 0.00 0.214973E+11 0.113024E+11 95041.24 07-MAR-19:02 52600.77 0.48
April 0.00 0.00 0.376262E+11 0.210330E+11 88339.08 28-APR-08:62 57200.88 0.68
May 0.00 0.00 0.655466E+11 0.432583E+11 83558.78 27-MAY-15:02 68158.97 0.74
June 0.00 0.00 0.690815E+11 0.474776E+11 84550.42 07-JUN-08:62 59007.87 0.78
July 0.00 0.00 0.726342E+11 0.495076E+11 90490.74 12-JUL-18:02 61547.91 0.79
August 0.00 0.00 0.687616E+11 0.458597E+11 87266.79 27-AUG-08:62 64756.41 0.76
September 0.00 0.00 0.609131E+11 0.374097E+11 102548.73 05-SEP-08:62 49724.86 0.72
October 0.00 0.00 0.508961E+11 0.311464E+11 93177.59 22-OCT-08:62 56479.03 0.67
November 0.00 0.00 0.226216E+11 0.113970E+11 90146.66 01-NOV-08:62 54489.10 0.57
December 0.00 0.00 0.147480E+11 0.708317E+10 91386.91 12-DEC-09:02 50095.70 0.42
                 
Annual Sum or Average 0.00 0.00 0.507887E+12 0.315464E+12       0.62
Minimum of Months 0.00 0.00 0.961707E+10 0.401087E+10 83052.40   49724.86 0.31
Maximum of Months 0.00 0.00 0.726342E+11 0.495076E+11 102548.73   68158.97 0.79



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.225435E+10 0.123898E+10 13932.07 19-JAN-19:02 9369.44 0.38
February 0.00 0.00 0.288799E+10 0.147999E+10 13586.81 02-FEB-19:02 9308.02 0.56
March 0.00 0.00 0.390543E+10 0.220050E+10 14659.49 07-MAR-19:02 9015.63 0.57
April 0.00 0.00 0.635130E+10 0.359219E+10 13884.75 28-APR-08:62 9832.36 0.86
May 0.00 0.00 0.110161E+11 0.683346E+10 13772.82 22-MAY-15:02 9908.43 0.96
June 0.00 0.00 0.113391E+11 0.713437E+10 13166.65 02-JUN-08:62 10527.63 0.97
July 0.00 0.00 0.121572E+11 0.770256E+10 13588.72 12-JUL-18:02 9888.40 0.96
August 0.00 0.00 0.116001E+11 0.719375E+10 13527.87 29-AUG-08:62 10174.19 0.96
September 0.00 0.00 0.103296E+11 0.617297E+10 15380.48 05-SEP-08:62 8750.57 0.95
October 0.00 0.00 0.962152E+10 0.599322E+10 14317.32 22-OCT-08:62 9339.06 0.89
November 0.00 0.00 0.504960E+10 0.292474E+10 14064.85 02-NOV-08:62 9659.25 0.73
December 0.00 0.00 0.318738E+10 0.173247E+10 14192.58 12-DEC-09:02 8101.34 0.50
                 
Annual Sum or Average 0.00 0.00 0.896997E+11 0.541992E+11       0.77
Minimum of Months 0.00 0.00 0.225435E+10 0.123898E+10 13166.65   8101.34 0.38
Maximum of Months 0.00 0.00 0.121572E+11 0.770256E+10 15380.48   10527.63 0.97



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.108851E+10 0.456250E+09 13528.90 19-JAN-09:02 9066.51 0.26
February 0.00 0.00 0.165014E+10 0.738880E+09 13232.62 24-FEB-09:02 9119.44 0.42
March 0.00 0.00 0.297779E+10 0.157753E+10 14298.14 07-MAR-19:02 8782.87 0.50
April 0.00 0.00 0.573706E+10 0.320049E+10 13583.41 28-APR-08:62 9580.80 0.82
May 0.00 0.00 0.109154E+11 0.680405E+10 13444.04 22-MAY-15:02 9672.34 0.96
June 0.00 0.00 0.114806E+11 0.734495E+10 13144.94 07-JUN-08:62 9613.74 0.97
July 0.00 0.00 0.121818E+11 0.778177E+10 13162.24 12-JUL-18:02 9710.87 0.97
August 0.00 0.00 0.112471E+11 0.693181E+10 13190.45 16-AUG-18:02 9349.65 0.96
September 0.00 0.00 0.956250E+10 0.554958E+10 15229.13 05-SEP-08:62 8383.67 0.94
October 0.00 0.00 0.806815E+10 0.469821E+10 14219.08 22-OCT-08:62 8918.97 0.85
November 0.00 0.00 0.317894E+10 0.161136E+10 13860.08 02-NOV-08:62 9352.95 0.58
December 0.00 0.00 0.169884E+10 0.762774E+09 13837.40 12-DEC-09:02 7801.97 0.36
                 
Annual Sum or Average 0.00 0.00 0.797868E+11 0.474577E+11       0.72
Minimum of Months 0.00 0.00 0.108851E+10 0.456250E+09 13144.94   7801.97 0.26
Maximum of Months 0.00 0.00 0.121818E+11 0.778177E+10 15229.13   9710.87 0.97



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.539117E+09 0.299675E+09 4163.95 19-JAN-19:02 2691.27 0.33
February 0.00 0.00 0.733649E+09 0.394158E+09 4069.22 02-FEB-19:02 2669.37 0.49
March 0.00 0.00 0.866155E+09 0.480114E+09 4398.59 07-MAR-19:02 2557.22 0.48
April 0.00 0.00 0.157229E+10 0.895115E+09 4230.79 28-APR-08:62 2688.68 0.79
May 0.00 0.00 0.265378E+10 0.155169E+10 4155.17 14-MAY-08:62 2894.93 0.93
June 0.00 0.00 0.282906E+10 0.172362E+10 4056.46 01-JUN-08:62 2856.49 0.94
July 0.00 0.00 0.296520E+10 0.178055E+10 4219.39 15-JUL-08:62 2880.90 0.94
August 0.00 0.00 0.291649E+10 0.173868E+10 4269.64 29-AUG-08:62 2688.53 0.94
September 0.00 0.00 0.257559E+10 0.146821E+10 4676.86 05-SEP-08:62 2343.61 0.93
October 0.00 0.00 0.236822E+10 0.141353E+10 4367.68 21-OCT-08:62 2705.84 0.86
November 0.00 0.00 0.112492E+10 0.625795E+09 4326.38 02-NOV-08:62 2501.85 0.64
December 0.00 0.00 0.805156E+09 0.444856E+09 4230.42 15-DEC-09:02 2387.31 0.44
                 
Annual Sum or Average 0.00 0.00 0.219496E+11 0.128160E+11       0.73
Minimum of Months 0.00 0.00 0.539117E+09 0.299675E+09 4056.46   2343.61 0.33
Maximum of Months 0.00 0.00 0.296520E+10 0.178055E+10 4676.86   2894.93 0.94



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.266247E+09 0.123162E+09 4002.94 19-JAN-19:02 2505.51 0.22
February 0.00 0.00 0.425670E+09 0.201752E+09 3735.78 02-FEB-19:02 2611.96 0.37
March 0.00 0.00 0.642004E+09 0.330178E+09 4241.80 07-MAR-19:02 2439.58 0.42
April 0.00 0.00 0.142063E+10 0.797293E+09 4115.23 28-APR-08:62 2601.52 0.75
May 0.00 0.00 0.262927E+10 0.155327E+10 4022.28 14-MAY-08:62 2826.28 0.93
June 0.00 0.00 0.286764E+10 0.178365E+10 3967.06 06-JUN-08:62 2764.35 0.95
July 0.00 0.00 0.297425E+10 0.180460E+10 4073.21 15-JUL-08:62 2819.70 0.94
August 0.00 0.00 0.282577E+10 0.167695E+10 4091.63 27-AUG-08:62 2813.21 0.94
September 0.00 0.00 0.237654E+10 0.131145E+10 4610.33 05-SEP-08:62 2233.18 0.92
October 0.00 0.00 0.197165E+10 0.110191E+10 4322.93 22-OCT-08:62 2350.72 0.81
November 0.00 0.00 0.664214E+09 0.319865E+09 4165.29 02-NOV-08:62 2363.72 0.48
December 0.00 0.00 0.446131E+09 0.205086E+09 4124.27 15-DEC-09:02 2243.56 0.30
                 
Annual Sum or Average 0.00 0.00 0.195100E+11 0.112092E+11       0.67
Minimum of Months 0.00 0.00 0.266247E+09 0.123162E+09 3735.78   2233.18 0.22
Maximum of Months 0.00 0.00 0.297425E+10 0.180460E+10 4610.33   2826.28 0.95



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.684473E+10 0.484624E+10 19170.75 19-JAN-19:02 12048.02 0.51
February 0.00 0.00 0.687982E+10 0.440290E+10 19242.61 02-FEB-19:02 12013.57 0.64
March 0.00 0.00 0.619789E+10 0.376465E+10 20597.92 07-MAR-19:02 11300.36 0.57
April 0.00 0.00 0.804406E+10 0.447212E+10 19144.54 15-APR-08:62 11898.95 0.82
May 0.00 0.00 0.129331E+11 0.773967E+10 18060.24 05-MAY-08:62 12883.01 0.91
June 0.00 0.00 0.131165E+11 0.795307E+10 17716.40 06-JUN-08:62 12936.97 0.92
July 0.00 0.00 0.142597E+11 0.872908E+10 18701.13 12-JUL-18:02 12744.56 0.92
August 0.00 0.00 0.146961E+11 0.912311E+10 18951.77 29-AUG-08:62 12413.35 0.92
September 0.00 0.00 0.142398E+11 0.872830E+10 21662.44 05-SEP-08:62 10477.96 0.92
October 0.00 0.00 0.149329E+11 0.999961E+10 19800.30 22-OCT-08:62 11906.23 0.89
November 0.00 0.00 0.106228E+11 0.726677E+10 19669.83 02-NOV-08:62 12001.80 0.76
December 0.00 0.00 0.852436E+10 0.588631E+10 19813.65 12-DEC-09:02 10234.39 0.61
                 
Annual Sum or Average 0.00 0.00 0.131292E+12 0.829118E+11       0.78
Minimum of Months 0.00 0.00 0.619789E+10 0.376465E+10 17716.40   10234.39 0.51
Maximum of Months 0.00 0.00 0.149329E+11 0.999961E+10 21662.44   12936.97 0.92



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 10165.95 138535.34 21-JAN-19:02
February 0.00 0.00 01-FEB-00:03 6244.00 113336.61 04-FEB-09:02
March 0.00 0.00 01-MAR-00:03 5502.10 117945.61 12-MAR-08:02
April 0.00 0.00 01-APR-00:10 434.41 73603.23 11-APR-05:49
May 0.00 0.00 01-MAY-00:05 13.28 24505.83 01-MAY-08:05
June 0.00 0.00 01-JUN-00:05 10.80 13638.67 21-JUN-08:07
July 0.00 0.00 01-JUL-00:10 7.92 19745.34 14-JUL-08:05
August 0.00 0.00 01-AUG-00:05 8.95 17769.71 17-AUG-08:05
September 0.00 0.00 01-SEP-00:05 13.66 19049.68 08-SEP-08:05
October 0.00 0.00 01-OCT-00:10 337.00 70689.66 28-OCT-06:20
November 0.00 0.00 01-NOV-00:05 2835.41 100964.74 12-NOV-08:63
December 0.00 0.00 01-DEC-00:03 7299.08 131835.05 30-DEC-16:02
             
Annual Sum or Average 0.00     2731.57    
Minimum of Months 0.00 0.00   7.92 13638.67  
Maximum of Months 0.00 0.00   10165.95 138535.34  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 87395.08 623680.47 19-JAN-19:03 0.00 0.00 01-JAN-00:10
February 121259.33 582279.06 02-FEB-19:03 0.00 0.00 01-FEB-00:03
March 140278.42 651894.05 07-MAR-19:03 0.00 0.00 01-MAR-00:03
April 245374.86 672284.76 28-APR-21:00 0.00 0.00 01-APR-00:10
May 428984.20 690620.72 19-MAY-20:30 0.00 0.00 01-MAY-00:05
June 451655.02 707936.91 29-JUN-18:03 0.00 0.00 01-JUN-00:05
July 490821.07 714060.47 18-JUL-18:05 0.00 0.00 01-JUL-00:10
August 475748.87 740804.08 09-AUG-18:03 0.00 0.00 01-AUG-00:05
September 465503.61 729373.61 01-SEP-18:05 0.00 0.00 01-SEP-00:05
October 370787.92 723016.80 07-OCT-08:03 0.00 0.00 01-OCT-00:10
November 190460.16 684600.50 03-NOV-19:50 0.00 0.00 01-NOV-00:05
December 136759.84 634011.38 15-DEC-19:02 0.00 0.00 01-DEC-00:03
             
Annual Sum or Average 301477.01     0.00    
Minimum of Months 87395.08 582279.06   0.00 0.00  
Maximum of Months 490821.07 740804.08   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 22558.61 54603.32 07-JAN-08:41
February 0.00 0.00 01-FEB-00:03 22400.77 51475.74 17-FEB-18:51
March 0.00 0.00 01-MAR-00:03 21621.76 53668.46 10-MAR-07:11
April 0.00 0.00 01-APR-00:10 20394.82 44902.73 03-APR-06:10
May 0.00 0.00 01-MAY-00:05 19066.43 39352.97 01-MAY-07:00
June 0.00 0.00 01-JUN-00:05 17994.65 36690.62 01-JUN-07:00
July 0.00 0.00 01-JUL-00:10 17451.84 34950.40 03-JUL-07:00
August 0.00 0.00 01-AUG-00:05 17638.69 35696.87 31-AUG-06:50
September 0.00 0.00 01-SEP-00:05 18447.48 37814.22 29-SEP-06:10
October 0.00 0.00 01-OCT-00:10 19682.18 47312.78 28-OCT-07:51
November 0.00 0.00 01-NOV-00:05 20996.31 47891.62 22-NOV-07:24
December 0.00 0.00 01-DEC-00:03 22044.87 53980.73 22-DEC-07:01
             
Annual Sum or Average 0.00     20011.55    
Minimum of Months 0.00 0.00   17451.84 34950.40  
Maximum of Months 0.00 0.00   22558.61 54603.32  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.587890E+10 0.87 2194.93 01-JAN-00:10 0.87
February 0.530997E+10 0.87 2194.93 01-FEB-00:03 0.87
March 0.587890E+10 0.87 2194.93 01-MAR-00:03 0.87
April 0.568926E+10 0.87 2194.93 01-APR-00:10 0.87
May 0.587890E+10 0.87 2194.93 01-MAY-00:05 0.87
June 0.568926E+10 0.87 2194.93 01-JUN-00:05 0.87
July 0.587890E+10 0.87 2194.93 01-JUL-00:10 0.87
August 0.587890E+10 0.87 2194.93 01-AUG-00:05 0.87
September 0.568926E+10 0.87 2194.93 01-SEP-00:05 0.87
October 0.587890E+10 0.87 2194.93 01-OCT-00:10 0.87
November 0.568926E+10 0.87 2194.93 01-NOV-00:05 0.87
December 0.587890E+10 0.87 2194.93 01-DEC-00:03 0.87
           
Annual Sum or Average 0.692193E+11 0.87      
Minimum of Months 0.530997E+10 0.87 2194.93   0.87
Maximum of Months 0.587890E+10 0.87 2194.93   0.87



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.361242E+11 0.84 41418.25 06-JAN-22:15 1.66
February 0.327278E+11 0.84 34172.39 13-FEB-22:55 1.47
March 0.367606E+11 0.84 34410.17 08-MAR-23:05 1.48
April 0.370150E+11 0.86 28097.55 28-APR-21:10 1.29
May 0.417068E+11 0.90 30212.92 05-MAY-21:10 1.35
June 0.414379E+11 0.92 30967.11 28-JUN-21:10 1.37
July 0.430103E+11 0.92 31636.14 19-JUL-21:10 1.39
August 0.437794E+11 0.93 34499.24 30-AUG-21:10 1.47
September 0.416000E+11 0.92 35057.50 12-SEP-21:10 1.48
October 0.427967E+11 0.91 36157.75 13-OCT-21:10 1.51
November 0.377575E+11 0.87 40789.28 12-NOV-08:63 1.65
December 0.373843E+11 0.85 41418.25 18-DEC-00:25 1.66
           
Annual Sum or Average 0.472100E+12 0.88      
Minimum of Months 0.327278E+11 0.84 28097.55   1.29
Maximum of Months 0.437794E+11 0.93 41418.25   1.66



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.26 76.61 01-JAN-00:10 0.26
February 0.185347E+09 0.26 76.61 01-FEB-00:03 0.26
March 0.205205E+09 0.26 76.61 01-MAR-00:03 0.26
April 0.198586E+09 0.26 76.61 01-APR-00:10 0.26
May 0.205205E+09 0.26 76.61 01-MAY-00:05 0.26
June 0.198586E+09 0.26 76.61 01-JUN-00:05 0.26
July 0.205205E+09 0.26 76.61 01-JUL-00:10 0.26
August 0.205205E+09 0.26 76.61 01-AUG-00:05 0.26
September 0.198586E+09 0.26 76.61 01-SEP-00:05 0.26
October 0.205205E+09 0.26 76.61 01-OCT-00:10 0.26
November 0.198586E+09 0.26 76.61 01-NOV-00:05 0.26
December 0.205205E+09 0.26 76.61 01-DEC-00:03 0.26
           
Annual Sum or Average 0.241613E+10 0.26      
Minimum of Months 0.185347E+09 0.26 76.61   0.26
Maximum of Months 0.205205E+09 0.26 76.61   0.26



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:10 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:10 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:10 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 -0.0 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:05 0.00
September 0.00 -0.0 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:05 0.00
December 0.00 -0.0 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.19 612.92 01-JAN-07:05 0.26
February 0.105030E+10 0.19 612.92 01-FEB-07:05 0.26
March 0.116283E+10 0.19 612.92 01-MAR-07:05 0.26
April 0.112532E+10 0.19 612.92 01-APR-06:05 0.26
May 0.116283E+10 0.19 612.92 01-MAY-06:05 0.26
June 0.112532E+10 0.19 612.92 01-JUN-06:05 0.26
July 0.116283E+10 0.19 612.92 01-JUL-06:10 0.26
August 0.116283E+10 0.19 612.92 01-AUG-06:05 0.26
September 0.112532E+10 0.19 612.92 01-SEP-06:05 0.26
October 0.116283E+10 0.19 612.92 01-OCT-06:10 0.26
November 0.112532E+10 0.19 612.92 01-NOV-06:05 0.26
December 0.116283E+10 0.19 612.92 01-DEC-07:05 0.26
           
Annual Sum or Average 0.136914E+11 0.19      
Minimum of Months 0.105030E+10 0.19 612.92   0.26
Maximum of Months 0.116283E+10 0.19 612.92   0.26



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.189604E+09 0.45 701.94 01-JAN-09:02 0.57
February 0.201990E+09 0.46 701.94 01-FEB-16:02 0.57
March 0.227655E+09 0.46 701.94 02-MAR-16:02 0.57
April 0.316457E+09 0.49 701.94 01-APR-08:62 0.57
May 0.463855E+09 0.53 701.94 01-MAY-08:62 0.57
June 0.492168E+09 0.54 701.94 01-JUN-08:62 0.57
July 0.505861E+09 0.54 701.94 01-JUL-08:62 0.57
August 0.504023E+09 0.54 701.94 01-AUG-08:62 0.57
September 0.451796E+09 0.53 701.94 01-SEP-08:62 0.57
October 0.446448E+09 0.52 701.94 01-OCT-08:62 0.57
November 0.258738E+09 0.50 701.94 01-NOV-08:62 0.57
December 0.225298E+09 0.47 701.94 01-DEC-09:02 0.57
           
Annual Sum or Average 0.428389E+10 0.50      
Minimum of Months 0.189604E+09 0.45 701.94   0.57
Maximum of Months 0.505861E+09 0.54 701.94   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.163375E+09 0.42 682.65 01-JAN-09:02 0.57
February 0.159048E+09 0.43 682.65 01-FEB-16:02 0.57
March 0.188440E+09 0.44 682.65 02-MAR-16:02 0.57
April 0.287372E+09 0.47 682.65 01-APR-08:62 0.57
May 0.460449E+09 0.53 682.65 01-MAY-08:62 0.57
June 0.500141E+09 0.54 682.65 01-JUN-08:62 0.57
July 0.510338E+09 0.54 682.65 01-JUL-08:62 0.57
August 0.488924E+09 0.54 682.65 01-AUG-08:62 0.57
September 0.414757E+09 0.53 682.65 01-SEP-08:62 0.57
October 0.370905E+09 0.50 682.65 01-OCT-08:62 0.57
November 0.174046E+09 0.45 682.65 01-NOV-08:62 0.57
December 0.172417E+09 0.43 682.65 01-DEC-16:02 0.57
           
Annual Sum or Average 0.389021E+10 0.48      
Minimum of Months 0.159048E+09 0.42 682.65   0.57
Maximum of Months 0.510338E+09 0.54 682.65   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.880553E+09 0.30 2293.43 01-JAN-14:00 0.57
February 0.743689E+09 0.29 1805.76 27-FEB-14:30 0.57
March 0.482910E+09 0.21 1166.94 06-MAR-14:10 0.57
April 0.613194E+09 0.31 906.70 22-APR-13:40 0.57
May 0.127023E+10 0.53 914.20 04-MAY-16:20 0.57
June 0.129521E+10 0.55 920.72 28-JUN-17:20 0.57
July 0.144485E+10 0.56 1006.79 19-JUL-17:20 0.57
August 0.153532E+10 0.56 1109.07 31-AUG-13:30 0.57
September 0.151691E+10 0.54 1909.67 10-SEP-13:30 0.57
October 0.184905E+10 0.51 2107.78 26-OCT-14:00 0.58
November 0.142269E+10 0.41 2187.05 06-NOV-14:00 0.57
December 0.114655E+10 0.32 2501.12 17-DEC-14:50 0.57
           
Annual Sum or Average 0.142011E+11 0.42      
Minimum of Months 0.482910E+09 0.21 906.70   0.57
Maximum of Months 0.184905E+10 0.56 2501.12   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.832481E+09 0.41 3961.05 01-JAN-09:02 0.57
February 0.862300E+09 0.41 3961.05 01-FEB-16:02 0.57
March 0.113341E+10 0.41 3961.05 02-MAR-19:03 0.57
April 0.172917E+10 0.41 3961.05 01-APR-08:62 0.57
May 0.295790E+10 0.43 3961.05 01-MAY-08:62 0.57
June 0.318395E+10 0.45 3961.05 01-JUN-08:62 0.57
July 0.332830E+10 0.45 3961.05 01-JUL-08:62 0.57
August 0.306896E+10 0.44 3961.05 01-AUG-08:62 0.57
September 0.266501E+10 0.41 3961.05 01-SEP-08:62 0.57
October 0.228574E+10 0.41 3961.05 01-OCT-08:62 0.57
November 0.111173E+10 0.41 3961.05 01-NOV-08:62 0.57
December 0.930398E+09 0.41 3961.05 01-DEC-09:02 0.57
           
Annual Sum or Average 0.240893E+11 0.42      
Minimum of Months 0.832481E+09 0.41 3961.05   0.57
Maximum of Months 0.332830E+10 0.45 3961.05   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.173043E+09 0.44 628.62 01-JAN-09:02 0.57
February 0.180541E+09 0.46 628.62 01-FEB-16:02 0.57
March 0.228713E+09 0.48 628.62 02-MAR-16:02 0.57
April 0.305208E+09 0.52 628.62 01-APR-08:62 0.57
May 0.495749E+09 0.55 628.62 01-MAY-08:62 0.57
June 0.513101E+09 0.55 628.62 01-JUN-08:62 0.57
July 0.540727E+09 0.55 628.62 01-JUL-08:62 0.57
August 0.513476E+09 0.55 628.62 01-AUG-08:62 0.57
September 0.452983E+09 0.54 628.62 01-SEP-08:62 0.57
October 0.440928E+09 0.54 628.62 01-OCT-08:62 0.57
November 0.258185E+09 0.51 628.62 01-NOV-08:62 0.57
December 0.203897E+09 0.47 628.62 01-DEC-09:02 0.57
           
Annual Sum or Average 0.430655E+10 0.51      
Minimum of Months 0.173043E+09 0.44 628.62   0.57
Maximum of Months 0.540727E+09 0.55 628.62   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.144130E+09 0.41 613.08 01-JAN-09:02 0.57
February 0.132681E+09 0.42 613.08 01-FEB-16:02 0.57
March 0.186174E+09 0.45 613.08 03-MAR-09:02 0.57
April 0.274100E+09 0.50 613.08 01-APR-08:62 0.57
May 0.493357E+09 0.55 613.08 01-MAY-08:62 0.57
June 0.522218E+09 0.55 613.08 01-JUN-08:62 0.57
July 0.546532E+09 0.55 613.08 01-JUL-08:62 0.57
August 0.498264E+09 0.55 613.08 01-AUG-08:62 0.57
September 0.416368E+09 0.54 613.08 01-SEP-08:62 0.57
October 0.365543E+09 0.51 613.08 01-OCT-08:62 0.57
November 0.168796E+09 0.44 613.08 01-NOV-08:62 0.57
December 0.150459E+09 0.42 613.08 01-DEC-09:02 0.57
           
Annual Sum or Average 0.389862E+10 0.49      
Minimum of Months 0.132681E+09 0.41 613.08   0.57
Maximum of Months 0.546532E+09 0.55 613.08   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 51969902.80 0.44 185.04 01-JAN-09:02 0.57
February 52222244.58 0.46 185.04 01-FEB-16:02 0.57
March 59079420.36 0.46 185.04 02-MAR-16:02 0.57
April 79006224.95 0.49 185.04 01-APR-08:62 0.57
May 0.119355E+09 0.53 185.04 01-MAY-08:62 0.57
June 0.127571E+09 0.54 185.04 01-JUN-08:62 0.57
July 0.130278E+09 0.54 185.04 01-JUL-08:62 0.57
August 0.128949E+09 0.54 185.04 01-AUG-08:62 0.57
September 0.113550E+09 0.53 185.04 01-SEP-08:62 0.57
October 0.109649E+09 0.52 185.04 01-OCT-08:62 0.57
November 60697751.86 0.49 185.04 01-NOV-08:62 0.57
December 58373473.50 0.47 185.04 01-DEC-16:02 0.57
           
Annual Sum or Average 0.109070E+10 0.50      
Minimum of Months 51969902.80 0.44 185.04   0.57
Maximum of Months 0.130278E+09 0.54 185.04   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 47971518.34 0.42 179.76 01-JAN-16:02 0.57
February 42774535.96 0.43 179.76 01-FEB-16:02 0.57
March 49902653.96 0.44 179.76 02-MAR-16:02 0.57
April 71680543.20 0.48 179.76 01-APR-08:62 0.57
May 0.118161E+09 0.53 179.76 01-MAY-08:62 0.57
June 0.129502E+09 0.54 179.76 01-JUN-08:62 0.57
July 0.131476E+09 0.54 179.76 01-JUL-08:62 0.57
August 0.124918E+09 0.54 179.76 01-AUG-08:62 0.57
September 0.104367E+09 0.53 179.76 01-SEP-08:62 0.57
October 90472342.95 0.50 179.76 01-OCT-08:62 0.57
November 42454254.33 0.44 179.76 01-NOV-08:62 0.57
December 48531108.13 0.44 179.76 01-DEC-16:02 0.57
           
Annual Sum or Average 0.100221E+10 0.49      
Minimum of Months 42454254.33 0.42 179.76   0.57
Maximum of Months 0.131476E+09 0.54 179.76   0.57



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.396841E+09 0.50 830.72 01-JAN-09:02 0.57
February 0.372152E+09 0.50 830.72 01-FEB-16:02 0.57
March 0.346620E+09 0.48 830.72 02-MAR-16:02 0.57
April 0.383241E+09 0.49 830.72 01-APR-08:62 0.57
May 0.571872E+09 0.52 830.72 01-MAY-08:62 0.57
June 0.583831E+09 0.53 830.72 01-JUN-08:62 0.57
July 0.628991E+09 0.53 830.72 01-JUL-08:62 0.57
August 0.649306E+09 0.53 830.72 01-AUG-08:62 0.57
September 0.629719E+09 0.53 830.72 01-SEP-08:62 0.57
October 0.704551E+09 0.53 830.72 01-OCT-08:62 0.57
November 0.535864E+09 0.52 830.72 01-NOV-08:62 0.57
December 0.469124E+09 0.50 830.72 01-DEC-09:02 0.57
           
Annual Sum or Average 0.627211E+10 0.51      
Minimum of Months 0.346620E+09 0.48 830.72   0.57
Maximum of Months 0.704551E+09 0.53 830.72   0.57



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.197161E+09 0.177445E+09 491.81 09-JAN-19:02 442.63 442.63 66.50 0.83
February 0.113173E+09 0.101856E+09 502.53 06-FEB-09:02 452.27 452.27 49.11 0.88
March 0.104233E+09 93809985.03 484.21 12-MAR-06:38 435.79 435.79 46.65 0.81
April 7341885.45 6607696.90 348.44 11-APR-05:42 313.60 313.60 42.58 0.47
May 342395.78 308156.21 205.01 23-MAY-08:06 184.51 184.51 56.40 0.24
June 277720.98 249948.88 127.78 21-JUN-08:07 115.00 115.00 56.11 0.14
July 206345.57 185711.01 180.47 14-JUL-08:05 162.43 162.43 56.47 0.21
August 243360.62 219024.56 169.92 17-AUG-08:05 152.92 152.92 57.29 0.19
September 372018.60 334816.74 193.68 08-SEP-08:05 174.32 174.32 58.99 0.22
October 5263880.80 4737492.72 325.19 28-OCT-05:45 292.67 292.67 40.39 0.43
November 49347961.07 44413164.96 427.46 15-NOV-05:48 384.72 384.72 51.39 0.64
December 0.143291E+09 0.128962E+09 478.34 30-DEC-19:01 430.51 430.51 42.57 0.79
                 
Annual Sum or Average 0.621254E+09 0.559129E+09            
Minimum of Months 206345.57 185711.01 127.78   115.00 115.00 40.39 0.14
Maximum of Months 0.197161E+09 0.177445E+09 502.53   452.27 452.27 66.50 0.88



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.262270E+09 0.236043E+09 1596.93 19-JAN-21:00 1437.24 1437.24 7.58 20.36
February 0.333816E+09 0.300434E+09 1376.32 02-FEB-19:02 1238.69 1238.69 7.41 19.10
March 0.454108E+09 0.408697E+09 1553.80 18-MAR-18:02 1398.42 1398.42 7.26 20.12
April 0.835338E+09 0.751805E+09 1910.44 28-APR-21:00 1719.39 1719.39 7.17 21.97
May 0.179302E+10 0.161371E+10 1989.59 19-MAY-20:30 1790.63 1790.63 7.16 22.35
June 0.194744E+10 0.175270E+10 2118.76 29-JUN-18:05 1906.89 1906.89 6.73 22.95
July 0.232540E+10 0.209286E+10 2130.17 05-JUL-18:05 1917.15 1917.15 6.73 23.00
August 0.222226E+10 0.200003E+10 2206.74 09-AUG-18:03 1986.06 1986.06 6.73 23.34
September 0.207039E+10 0.186335E+10 2245.17 01-SEP-18:05 2020.65 2020.65 7.19 23.51
October 0.165101E+10 0.148591E+10 2246.78 23-OCT-20:50 2022.10 2022.10 7.17 23.52
November 0.677495E+09 0.609746E+09 2146.95 03-NOV-20:00 1932.26 1932.26 7.21 23.08
December 0.486870E+09 0.438183E+09 1767.30 15-DEC-21:00 1590.57 1590.57 7.29 21.26
                 
Annual Sum or Average 0.150594E+11 0.135535E+11            
Minimum of Months 0.262270E+09 0.236043E+09 1376.32   1238.69 1238.69 6.73 19.10
Maximum of Months 0.232540E+10 0.209286E+10 2246.78   2022.10 2022.10 7.58 23.52



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.124682E+11 0.112214E+11 5681.69 01-JAN-00:10 5113.52 5113.52 9.07 39.82
February 0.119958E+11 0.107962E+11 5681.69 01-FEB-00:03 5113.52 5113.52 9.35 39.82
March 0.132157E+11 0.118941E+11 5681.69 01-MAR-00:03 5113.52 5113.52 9.14 39.82
April 0.146741E+11 0.132067E+11 5681.69 01-APR-00:10 5113.52 5113.52 9.53 39.82
May 0.152178E+11 0.136960E+11 5681.69 01-MAY-00:05 5113.52 5113.52 8.97 39.82
June 0.147269E+11 0.132542E+11 5681.69 01-JUN-00:05 5113.52 5113.52 9.75 39.82
July 0.152178E+11 0.136960E+11 5681.69 01-JUL-00:10 5113.52 5113.52 9.48 39.82
August 0.152178E+11 0.136960E+11 5681.69 01-AUG-00:05 5113.52 5113.52 9.39 39.82
September 0.147269E+11 0.132542E+11 5681.69 01-SEP-00:05 5113.52 5113.52 9.67 39.82
October 0.151957E+11 0.136761E+11 5681.69 01-OCT-00:10 5113.52 5113.52 9.55 39.82
November 0.144167E+11 0.129750E+11 5681.69 01-NOV-00:05 5113.52 5113.52 9.85 39.82
December 0.129925E+11 0.116933E+11 5681.69 01-DEC-00:03 5113.52 5113.52 8.51 39.82
                 
Annual Sum or Average 0.170066E+12 0.153059E+12            
Minimum of Months 0.119958E+11 0.107962E+11 5681.69   5113.52 5113.52 8.51 39.82
Maximum of Months 0.152178E+11 0.136960E+11 5681.69   5113.52 5113.52 9.85 39.82



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:10 14.37 14.37 50.66 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:03 14.37 14.37 50.90 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:03 14.37 14.37 50.97 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 53.65 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:05 14.37 14.37 53.82 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:05 14.37 14.37 54.04 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 54.74 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:05 14.37 14.37 54.41 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:05 14.37 14.37 53.82 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 53.19 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:05 14.37 14.37 53.47 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:03 14.37 14.37 50.99 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 50.66 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 54.74 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 59.86 59.86 10165.95 138535.34 21-JAN-19:02
February 0.00 0.00 01-FEB-00:03 55.94 55.94 6244.00 113336.61 04-FEB-09:02
March 0.00 0.00 01-MAR-00:03 44.79 44.79 5502.10 117945.61 12-MAR-08:02
April 0.00 0.00 01-APR-00:10 60.47 60.47 434.41 73603.23 11-APR-05:49
May 0.00 0.00 01-MAY-00:05 55.14 55.14 13.28 24505.83 01-MAY-08:05
June 0.00 0.00 01-JUN-00:05 56.75 56.75 10.80 13638.67 21-JUN-08:07
July 0.00 0.00 01-JUL-00:10 56.41 56.41 7.92 19745.34 14-JUL-08:05
August 0.00 0.00 01-AUG-00:05 56.56 56.56 8.95 17769.71 17-AUG-08:05
September 0.00 0.00 01-SEP-00:05 59.14 59.14 13.66 19049.68 08-SEP-08:05
October 0.00 0.00 01-OCT-00:10 57.16 57.16 337.00 70689.66 28-OCT-06:20
November 0.00 0.00 01-NOV-00:05 61.48 61.48 2835.41 100964.74 12-NOV-08:63
December 0.00 0.00 01-DEC-00:03 57.04 57.04 7299.08 131835.05 30-DEC-16:02
                 
Annual Sum or Average 0.00         2731.57    
Minimum of Months 0.00 0.00   44.79 44.79 7.92 13638.67  
Maximum of Months 0.00 0.00   61.48 61.48 10165.95 138535.34  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 87395.08 623680.47 19-JAN-19:03 11.15 7.41 0.00 0.00 01-JAN-00:10
February 121259.33 582279.06 02-FEB-19:03 10.88 7.39 0.00 0.00 01-FEB-00:03
March 140278.42 651894.05 07-MAR-19:03 11.21 7.30 0.00 0.00 01-MAR-00:03
April 245374.86 672284.76 28-APR-21:00 11.17 7.14 0.00 0.00 01-APR-00:10
May 428984.20 690620.72 19-MAY-20:30 11.27 7.13 0.00 0.00 01-MAY-00:05
June 451655.02 707936.91 29-JUN-18:03 10.94 6.70 0.00 0.00 01-JUN-00:05
July 490821.07 714060.47 18-JUL-18:05 10.98 6.70 0.00 0.00 01-JUL-00:10
August 475748.87 740804.08 09-AUG-18:03 11.14 6.70 0.00 0.00 01-AUG-00:05
September 465503.61 729373.61 01-SEP-18:05 11.53 7.16 0.00 0.00 01-SEP-00:05
October 370787.92 723016.80 07-OCT-08:03 11.03 6.70 0.00 0.00 01-OCT-00:10
November 190460.16 684600.50 03-NOV-19:50 11.27 7.17 0.00 0.00 01-NOV-00:05
December 136759.84 634011.38 15-DEC-19:02 11.08 7.28 0.00 0.00 01-DEC-00:03
                 
Annual Sum or Average 301477.01         0.00    
Minimum of Months 87395.08 582279.06   10.88 6.70 0.00 0.00  
Maximum of Months 490821.07 740804.08   11.53 7.41 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 50.66 59.53 22558.61 54603.32 07-JAN-08:41
February 0.00 0.00 01-FEB-00:03 50.90 59.78 22400.77 51475.74 17-FEB-18:51
March 0.00 0.00 01-MAR-00:03 50.97 58.77 21621.76 53668.46 10-MAR-07:11
April 0.00 0.00 01-APR-00:10 53.65 59.21 20394.82 44902.73 03-APR-06:10
May 0.00 0.00 01-MAY-00:05 53.82 59.00 19066.43 39352.97 01-MAY-07:00
June 0.00 0.00 01-JUN-00:05 54.04 58.81 17994.65 36690.62 01-JUN-07:00
July 0.00 0.00 01-JUL-00:10 54.74 59.41 17451.84 34950.40 03-JUL-07:00
August 0.00 0.00 01-AUG-00:05 54.41 58.90 17638.69 35696.87 31-AUG-06:50
September 0.00 0.00 01-SEP-00:05 53.82 58.58 18447.48 37814.22 29-SEP-06:10
October 0.00 0.00 01-OCT-00:10 53.19 58.56 19682.18 47312.78 28-OCT-07:51
November 0.00 0.00 01-NOV-00:05 53.47 59.27 20996.31 47891.62 22-NOV-07:24
December 0.00 0.00 01-DEC-00:03 50.99 58.54 22044.87 53980.73 22-DEC-07:01
                 
Annual Sum or Average 0.00         20011.55    
Minimum of Months 0.00 0.00   50.66 58.54 17451.84 34950.40  
Maximum of Months 0.00 0.00   54.74 59.78 22558.61 54603.32  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.173402E+11 0.00 0.150064E+12 0.361242E+11 0.00 0.00
February 0.886440E+10 0.00 0.195572E+12 0.327278E+11 0.00 0.00
March 0.105811E+11 0.00 0.259171E+12 0.367606E+11 0.00 0.00
April 0.100757E+10 0.00 0.450998E+12 0.370150E+11 0.00 0.00
May 233863.17 0.00 0.845706E+12 0.417068E+11 0.00 0.00
June 0.00 0.00 0.859748E+12 0.414379E+11 0.00 0.00
July 0.00 0.00 0.974225E+12 0.430103E+11 0.00 0.00
August 0.00 0.00 0.942656E+12 0.437794E+11 0.00 0.00
September 0.00 0.00 0.897075E+12 0.416000E+11 0.00 0.00
October 0.801078E+09 0.00 0.714975E+12 0.427967E+11 0.00 0.00
November 0.649353E+10 0.00 0.337237E+12 0.377575E+11 0.00 0.00
December 0.126849E+11 0.00 0.247057E+12 0.373843E+11 0.00 0.00
             
Annual Sum or Average 0.577730E+11 0.00 0.687448E+13 0.472100E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.150064E+12 0.327278E+11 0.00 0.00
Maximum of Months 0.173402E+11 0.00 0.974225E+12 0.437794E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 7446.32 0.00 0.303380E+11 0.587890E+10 0.00 0.00
February 43688253.01 0.00 0.386865E+11 0.530997E+10 0.00 0.00
March 10569.66 0.00 0.513335E+11 0.587890E+10 0.00 0.00
April 10637.62 0.00 0.852135E+11 0.568926E+10 0.00 0.00
May 8819.24 0.00 0.133116E+12 0.587890E+10 0.00 0.00
June 10101.55 0.00 0.133945E+12 0.568926E+10 0.00 0.00
July 9613.97 0.00 0.150941E+12 0.587890E+10 0.00 0.00
August 8531.70 0.00 0.145052E+12 0.587890E+10 0.00 0.00
September 10906.87 0.00 0.138064E+12 0.568926E+10 0.00 0.00
October 15797.38 0.00 0.113915E+12 0.587890E+10 0.00 0.00
November 37319.76 0.00 0.608934E+11 0.568926E+10 0.00 0.00
December 5801.86 0.00 0.479885E+11 0.587890E+10 0.00 0.00
             
Annual Sum or Average 43823798.94 0.00 0.112949E+13 0.692193E+11 0.00 0.00
Minimum of Months 5801.86 0.00 0.303380E+11 0.530997E+10 0.00 0.00
Maximum of Months 43688253.01 0.00 0.150941E+12 0.587890E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.361242E+11 0.150064E+12 0.173402E+11 0.112517E+12 0.656036E+10 0.00 0.00 0.00
February 0.327278E+11 0.195572E+12 0.886440E+10 0.688231E+11 0.113905E+11 0.00 0.00 0.00
March 0.367606E+11 0.259171E+12 0.105811E+11 0.453378E+11 0.224177E+11 0.00 0.00 0.00
April 0.370150E+11 0.450998E+12 0.100757E+10 0.320117E+10 0.532802E+11 0.00 0.00 0.00
May 0.417068E+11 0.845706E+12 233863.17 0.00 0.295617E+12 0.00 0.00 0.00
June 0.414379E+11 0.859748E+12 0.00 0.00 0.340252E+12 0.00 0.00 0.00
July 0.430103E+11 0.974225E+12 0.00 0.00 0.442917E+12 0.00 0.00 0.00
August 0.437794E+11 0.942656E+12 0.00 0.00 0.372372E+12 0.00 0.00 0.00
September 0.416000E+11 0.897075E+12 0.00 0.00 0.290934E+12 0.00 0.00 0.00
October 0.427967E+11 0.714975E+12 0.801078E+09 0.146737E+10 0.203977E+12 0.00 0.00 0.00
November 0.377575E+11 0.337237E+12 0.649353E+10 0.156714E+11 0.419081E+11 0.00 0.00 0.00
December 0.373843E+11 0.247057E+12 0.126849E+11 0.741065E+11 0.185823E+11 0.00 0.00 0.00
                 
Annual Sum or Average 0.472100E+12 0.687448E+13 0.577730E+11 0.321125E+12 0.210021E+13 0.00 0.00 0.00
Minimum of Months 0.327278E+11 0.150064E+12 0.00 0.00 0.656036E+10 0.00 0.00 0.00
Maximum of Months 0.437794E+11 0.974225E+12 0.173402E+11 0.112517E+12 0.442917E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.587890E+10 0.303380E+11 7446.32 0.248011E+11 0.311001E+10 0.00 0.00 0.00
February 0.530997E+10 0.386865E+11 43688253.01 0.143581E+11 0.482506E+10 0.00 0.00 0.00
March 0.587890E+10 0.513335E+11 10569.66 0.111649E+11 0.790735E+10 0.00 0.00 0.00
April 0.568926E+10 0.852135E+11 10637.62 0.956976E+09 0.200062E+11 0.00 0.00 0.00
May 0.587890E+10 0.133116E+12 8819.24 0.00 0.891145E+11 0.00 0.00 0.00
June 0.568926E+10 0.133945E+12 10101.55 0.00 0.954496E+11 0.00 0.00 0.00
July 0.587890E+10 0.150941E+12 9613.97 0.00 0.116926E+12 0.00 0.00 0.00
August 0.587890E+10 0.145052E+12 8531.70 0.00 0.104832E+12 0.00 0.00 0.00
September 0.568926E+10 0.138064E+12 10906.87 0.00 0.912038E+11 0.00 0.00 0.00
October 0.587890E+10 0.113915E+12 15797.38 0.598135E+09 0.643942E+11 0.00 0.00 0.00
November 0.568926E+10 0.608934E+11 37319.76 0.513425E+10 0.167063E+11 0.00 0.00 0.00
December 0.587890E+10 0.479885E+11 5801.86 0.174103E+11 0.745889E+10 0.00 0.00 0.00
                 
Annual Sum or Average 0.692193E+11 0.112949E+13 43823798.94 0.744238E+11 0.621934E+12 0.00 0.00 0.00
Minimum of Months 0.530997E+10 0.303380E+11 5801.86 0.00 0.311001E+10 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.150941E+12 43688253.01 0.248011E+11 0.116926E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.361242E+11 0.173402E+11 0.150064E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.327278E+11 0.886440E+10 0.195572E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.367606E+11 0.105811E+11 0.259171E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.370150E+11 0.100757E+10 0.450998E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.417068E+11 233863.17 0.845706E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.414379E+11 0.00 0.859748E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.430103E+11 0.00 0.974225E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.437794E+11 0.00 0.942656E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.416000E+11 0.00 0.897075E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.427967E+11 0.801078E+09 0.714975E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.377575E+11 0.649353E+10 0.337237E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.373843E+11 0.126849E+11 0.247057E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.472100E+12 0.577730E+11 0.687448E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.327278E+11 0.00 0.150064E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.437794E+11 0.173402E+11 0.974225E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.587890E+10 7446.32 0.303380E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.530997E+10 43688253.01 0.386865E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.587890E+10 10569.66 0.513335E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.568926E+10 10637.62 0.852135E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.587890E+10 8819.24 0.133116E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.568926E+10 10101.55 0.133945E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.587890E+10 9613.97 0.150941E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.587890E+10 8531.70 0.145052E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.568926E+10 10906.87 0.138064E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.587890E+10 15797.38 0.113915E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.568926E+10 37319.76 0.608934E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.587890E+10 5801.86 0.479885E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.692193E+11 43823798.94 0.112949E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.530997E+10 5801.86 0.303380E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 43688253.01 0.150941E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.977561E+10 0.817527E+09 0.00 44888302.83 0.121915E+10 0.00 0.345568E+11 0.00 1.09
February 0.258376E+11 0.188926E+09 0.00 4109500.59 0.193296E+10 0.00 0.574681E+10 0.00 1.08
March 0.315176E+11 0.00 0.00 118041.35 0.426635E+10 0.00 0.537843E+09 0.00 1.07
April 0.157073E+11 0.00 0.00 0.00 0.989805E+10 0.00 0.00 0.00 1.05
May 0.00 0.00 0.00 0.00 0.310618E+11 0.00 0.00 0.00 0.96
June 92258728.16 0.00 0.00 0.00 0.330040E+11 0.00 0.00 0.00 0.95
July 0.00 0.659487E+10 0.00 0.00 0.358118E+11 0.00 0.00 0.00 0.95
August 0.00 0.340134E+11 0.00 293876.13 0.603555E+10 0.00 70938938.87 0.00 0.98
September 0.00 0.356258E+11 0.00 0.00 0.312229E+10 0.00 0.00 0.00 1.01
October 76732499.96 0.243078E+11 0.00 21203764.02 0.170725E+10 0.00 0.982152E+10 0.00 1.06
November 0.549689E+09 0.784692E+10 0.00 56333263.17 0.530929E+09 0.00 0.301914E+11 0.00 1.15
December 0.223661E+10 0.534535E+10 0.00 57739768.93 0.549515E+09 0.00 0.367414E+11 0.00 1.11
                   
Annual Sum or Average 0.857934E+11 0.114741E+12 0.00 0.184687E+09 0.129140E+12 0.00 0.117667E+12 0.00 1.04
Minimum of Months 0.00 0.00 0.00 0.00 0.530929E+09 0.00 0.00 0.00 0.95
Maximum of Months 0.315176E+11 0.356258E+11 0.00 57739768.93 0.358118E+11 0.00 0.367414E+11 0.00 1.15



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.449534E+10 0.157997E+09 0.00 995997.46 99803942.04 27244501.11 0.592991E+09 0.00 2.34
February 0.340599E+10 0.251342E+09 0.00 544158.04 35259346.16 75406669.92 0.303266E+09 0.00 2.38
March 0.360975E+10 0.269580E+09 0.00 318694.06 0.250093E+09 91725725.22 0.136993E+09 0.00 2.33
April 0.184808E+10 0.592892E+09 0.00 41116.82 0.597368E+09 0.00 32826105.55 0.00 2.28
May 0.00 0.242825E+10 0.00 0.00 0.131292E+10 0.00 0.00 0.00 2.11
June 10051429.66 0.321024E+10 0.00 917.15 0.777161E+09 0.00 995651.96 0.00 2.09
July 0.00 0.434043E+10 0.00 0.00 0.835374E+09 0.00 0.00 0.00 2.10
August 5723181.63 0.405216E+10 0.00 2188.08 0.723034E+09 0.00 2804772.28 0.00 2.13
September 0.00 0.365493E+10 0.00 0.00 0.999489E+09 0.00 0.00 0.00 2.18
October 0.896323E+09 0.304764E+10 0.00 589490.66 0.334402E+09 0.00 0.185770E+09 0.00 2.37
November 0.276998E+10 0.801880E+09 0.00 1756981.29 0.275220E+09 0.00 0.636813E+09 0.00 2.45
December 0.373059E+10 0.479892E+09 0.00 1376731.67 0.276498E+09 79119459.60 0.572056E+09 0.00 2.39
                   
Annual Sum or Average 0.207718E+11 0.232872E+11 0.00 5626275.24 0.651663E+10 0.273496E+09 0.246451E+10 0.00 2.26
Minimum of Months 0.00 0.157997E+09 0.00 0.00 35259346.16 0.00 0.00 0.00 2.09
Maximum of Months 0.449534E+10 0.434043E+10 0.00 1756981.29 0.131292E+10 91725725.22 0.636813E+09 0.00 2.45



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.318382E+10 59618848.11 0.00 437786.76 0.119648E+09 0.00 0.593523E+09 0.00 1.47
February 0.219868E+10 45991531.84 0.00 682511.22 0.143510E+09 0.00 0.605140E+09 0.00 1.50
March 0.224626E+10 0.109123E+09 0.00 614428.90 0.271510E+09 0.00 0.598217E+09 0.00 1.49
April 0.863383E+09 0.505773E+09 0.00 658217.07 0.404049E+09 0.00 0.532081E+09 0.00 1.48
May 0.00 0.190868E+10 0.00 0.00 0.960886E+09 0.00 0.00 0.00 1.40
June 221338.54 0.236608E+10 0.00 34890.14 0.731569E+09 0.00 7937498.68 0.00 1.41
July 0.00 0.320900E+10 0.00 0.00 0.776602E+09 0.00 0.00 0.00 1.41
August 0.00 0.302361E+10 0.00 24362.29 0.608430E+09 0.00 6287890.29 0.00 1.41
September 0.00 0.268737E+10 0.00 0.00 0.734616E+09 0.00 0.00 0.00 1.40
October 0.324084E+09 0.198950E+10 0.00 660586.02 0.317957E+09 0.00 0.489056E+09 0.00 1.45
November 0.163629E+10 0.487534E+09 0.00 819248.89 0.239064E+09 0.00 0.852791E+09 0.00 1.49
December 0.259209E+10 0.302448E+09 0.00 479132.92 0.214160E+09 0.00 0.620013E+09 0.00 1.47
                   
Annual Sum or Average 0.130448E+11 0.166947E+11 0.00 4411164.20 0.552200E+10 0.00 0.430505E+10 0.00 1.45
Minimum of Months 0.00 45991531.84 0.00 0.00 0.119648E+09 0.00 0.00 0.00 1.40
Maximum of Months 0.318382E+10 0.320900E+10 0.00 819248.89 0.960886E+09 0.00 0.852791E+09 0.00 1.50



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.374743E+10 0.00 0.00 0.00 0.174757E+09 0.00 0.00 0.00 0.69
February 0.277885E+10 95034.76 0.00 0.00 0.186562E+09 99767.59 0.00 0.00 0.70
March 0.281868E+10 331689.50 0.00 550.47 0.375127E+09 0.00 2365053.52 0.00 0.69
April 0.138032E+10 0.120673E+09 0.00 1885.52 0.752895E+09 0.00 1993053.41 0.00 0.69
May 0.00 0.126704E+10 0.00 0.00 0.154377E+10 0.00 0.00 0.00 0.65
June 5208046.62 0.237155E+10 0.00 5379.44 0.717982E+09 0.00 2905767.09 0.00 0.66
July 0.00 0.331685E+10 0.00 0.00 0.685544E+09 0.00 0.00 0.00 0.66
August 120636.24 0.275978E+10 0.00 18251.34 0.822799E+09 0.00 6129928.34 0.00 0.65
September 0.00 0.179388E+10 0.00 0.00 0.154055E+10 0.00 0.00 0.00 0.64
October 0.703609E+09 0.121882E+10 0.00 139320.31 0.101064E+10 0.00 91547142.60 0.00 0.66
November 0.244365E+10 95844386.86 0.00 8384.63 0.600203E+09 0.00 19654674.96 0.00 0.69
December 0.318535E+10 55683033.19 0.00 147.22 0.442013E+09 0.00 40379.69 0.00 0.68
                   
Annual Sum or Average 0.170632E+11 0.130005E+11 0.00 173918.92 0.885284E+10 99767.59 0.124636E+09 0.00 0.67
Minimum of Months 0.00 0.00 0.00 0.00 0.174757E+09 0.00 0.00 0.00 0.64
Maximum of Months 0.374743E+10 0.331685E+10 0.00 139320.31 0.154377E+10 99767.59 91547142.60 0.00 0.70



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.180247E+10 0.00 0.00 0.00 84062543.52 134925.65 0.00 0.00 0.57
February 0.133649E+10 0.00 0.00 0.00 89786785.15 253225.38 0.00 0.00 0.58
March 0.135699E+10 0.00 0.00 0.00 0.180605E+09 0.00 0.00 0.00 0.58
April 0.664928E+09 6189777.91 0.00 0.00 0.412818E+09 0.00 0.00 0.00 0.57
May 0.00 0.297963E+09 0.00 0.00 0.101860E+10 0.00 0.00 0.00 0.52
June 3553240.92 0.873605E+09 0.00 327.70 0.547956E+09 0.00 351965.48 0.00 0.53
July 0.00 0.133175E+10 0.00 0.00 0.511393E+09 0.00 0.00 0.00 0.53
August 98902.15 0.101575E+10 0.00 4462.73 0.637556E+09 0.00 2912091.69 0.00 0.52
September 0.00 0.541346E+09 0.00 0.00 0.102194E+10 0.00 0.00 0.00 0.52
October 0.373358E+09 0.387035E+09 0.00 6102.30 0.658061E+09 0.00 8090243.27 0.00 0.54
November 0.118491E+10 7469698.71 0.00 0.00 0.326046E+09 0.00 0.00 0.00 0.58
December 0.153225E+10 0.00 0.00 0.00 0.239404E+09 0.00 0.00 0.00 0.57
                   
Annual Sum or Average 0.825505E+10 0.446110E+10 0.00 10892.73 0.572823E+10 388151.03 11354300.44 0.00 0.55
Minimum of Months 0.00 0.00 0.00 0.00 84062543.52 0.00 0.00 0.00 0.52
Maximum of Months 0.180247E+10 0.133175E+10 0.00 6102.30 0.102194E+10 253225.38 8090243.27 0.00 0.58



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.571967E+09 0.271887E+10 0.00 0.106304E+09 839943.41 0.00 0.573907E+11 0.00 21.99
February 0.435868E+09 0.271164E+10 0.00 78776504.85 3824160.10 0.00 0.421702E+11 0.00 22.54
March 0.817531E+09 0.570248E+10 0.00 82590588.52 4757071.89 0.00 0.429357E+11 0.00 22.40
April 93235169.85 0.134777E+11 0.00 46948594.06 17001974.96 0.00 0.211525E+11 0.00 21.99
May 0.00 0.416287E+11 0.00 0.00 49915093.76 0.00 0.00 0.00 19.95
June 0.00 0.442948E+11 0.00 409056.17 47985877.51 0.00 0.108590E+09 0.00 19.80
July 0.00 0.566394E+11 0.00 0.00 80615099.28 0.00 0.00 0.00 19.66
August 0.00 0.516340E+11 0.00 286052.83 54374780.19 0.00 83851032.83 0.00 19.65
September 0.00 0.489959E+11 0.00 0.00 69435640.33 0.00 0.00 0.00 19.79
October 43893759.22 0.325954E+11 0.00 24354287.82 46083301.47 0.00 0.119231E+11 0.00 20.57
November 0.500268E+09 0.105625E+11 0.00 68416660.52 9067963.42 0.00 0.375536E+11 0.00 22.25
December 0.833442E+09 0.763134E+10 0.00 81717297.09 2767885.53 0.00 0.486301E+11 0.00 21.81
                   
Annual Sum or Average 0.329620E+10 0.318593E+12 0.00 0.489803E+09 0.386669E+09 0.00 0.261948E+12 0.00 21.02
Minimum of Months 0.00 0.271164E+10 0.00 0.00 839943.41 0.00 0.00 0.00 19.65
Maximum of Months 0.833442E+09 0.566394E+11 0.00 0.106304E+09 80615099.28 0.00 0.573907E+11 0.00 22.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.578953E+10 0.923154E+09 0.00 20053286.81 0.179585E+09 0.00 0.159106E+11 0.00 3.56
February 0.473463E+10 0.114892E+10 0.00 15938586.34 23291450.27 0.00 0.113052E+11 0.00 3.61
March 0.633880E+10 0.183638E+10 0.00 14032660.61 0.367729E+09 0.00 0.989487E+10 0.00 3.54
April 0.149211E+10 0.435955E+10 0.00 9778166.84 0.833221E+09 0.00 0.645832E+10 0.00 3.50
May 0.00 0.149327E+11 0.00 0.00 0.159436E+10 0.00 0.00 0.00 3.35
June 0.00 0.163976E+11 0.00 368716.98 0.130969E+10 0.00 49737282.27 0.00 3.35
July 0.00 0.213825E+11 0.00 0.00 0.151567E+10 0.00 0.00 0.00 3.37
August 0.00 0.197870E+11 0.00 178633.00 0.121401E+10 0.00 35851721.63 0.00 3.39
September 0.00 0.192240E+11 0.00 0.00 0.953871E+09 0.00 0.00 0.00 3.42
October 0.711594E+09 0.141259E+11 0.00 8060401.10 0.169996E+09 0.00 0.399675E+10 0.00 3.65
November 0.148271E+10 0.439068E+10 0.00 22383722.43 0.211943E+09 0.00 0.130743E+11 0.00 3.73
December 0.516063E+10 0.284560E+10 0.00 18240016.64 0.347292E+09 0.00 0.133897E+11 0.00 3.63
                   
Annual Sum or Average 0.257100E+11 0.121354E+12 0.00 0.109034E+09 0.872066E+10 0.00 0.741154E+11 0.00 3.51
Minimum of Months 0.00 0.923154E+09 0.00 0.00 23291450.27 0.00 0.00 0.00 3.35
Maximum of Months 0.633880E+10 0.213825E+11 0.00 22383722.43 0.159436E+10 0.00 0.159106E+11 0.00 3.73



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.322048E+11 0.228236E+10 0.00 46551784.24 0.119091E+10 0.00 0.388897E+11 0.00 1.66
February 0.226668E+11 0.269291E+10 0.00 42879705.57 0.890406E+09 0.00 0.302873E+11 0.00 1.70
March 0.234743E+11 0.435794E+10 0.00 45939650.48 0.288720E+10 0.00 0.303106E+11 0.00 1.69
April 0.531615E+10 0.126253E+11 0.00 37913759.79 0.493636E+10 0.00 0.213094E+11 0.00 1.70
May 0.00 0.462349E+11 0.00 0.00 0.996449E+10 0.00 0.00 0.00 1.65
June 0.00 0.519263E+11 0.00 1351759.78 0.859049E+10 0.00 0.176995E+09 0.00 1.66
July 0.00 0.697587E+11 0.00 0.00 0.830353E+10 0.00 0.00 0.00 1.66
August 0.00 0.648009E+11 0.00 654626.10 0.641838E+10 0.00 0.129980E+09 0.00 1.66
September 0.00 0.616292E+11 0.00 0.00 0.579188E+10 0.00 0.00 0.00 1.66
October 0.191866E+10 0.437428E+11 0.00 25979662.17 0.197325E+10 0.00 0.141652E+11 0.00 1.71
November 0.717916E+10 0.128763E+11 0.00 55961507.51 0.149440E+10 0.00 0.407801E+11 0.00 1.73
December 0.238674E+11 0.842418E+10 0.00 43595666.27 0.165424E+10 0.00 0.368359E+11 0.00 1.67
                   
Annual Sum or Average 0.116627E+12 0.381352E+12 0.00 0.300828E+09 0.540955E+11 0.00 0.212885E+12 0.00 1.68
Minimum of Months 0.00 0.228236E+10 0.00 0.00 0.890406E+09 0.00 0.00 0.00 1.65
Maximum of Months 0.322048E+11 0.697587E+11 0.00 55961507.51 0.996449E+10 0.00 0.407801E+11 0.00 1.73



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.258379E+09 0.137473E+09 256356.58 4156443.39 28725832.52 0.445811E+09 0.517331E+09 5063.70 0.47
February 0.176178E+09 0.180667E+09 165285.17 3538127.31 22261110.83 0.251806E+09 0.427547E+09 3713.49 0.47
March 0.183717E+09 0.319959E+09 306182.24 4056932.88 30397588.56 0.235139E+09 0.453992E+09 10106.76 0.47
April 50551369.42 0.645723E+09 527008.47 3237725.62 54632279.06 663493.94 0.297533E+09 18832.17 0.47
May 0.00 0.152055E+10 1271334.34 0.00 94248007.85 0.00 0.00 31557.97 0.47
June 0.00 0.165156E+10 1017543.22 0.00 85664283.47 0.00 0.00 13000.62 0.47
July 0.00 0.204111E+10 584076.95 0.00 0.107752E+09 0.00 0.00 12591.69 0.47
August 0.00 0.186479E+10 1021211.62 0.00 98637699.80 0.00 0.00 16936.70 0.47
September 0.00 0.164497E+10 1081938.67 0.00 0.100321E+09 0.00 0.00 26205.70 0.47
October 27917071.37 0.125275E+10 699396.87 2063419.91 62114341.50 468937.16 0.173835E+09 21467.24 0.47
November 93396357.92 0.452661E+09 282970.89 5388360.87 38467652.58 33775491.87 0.601997E+09 8695.80 0.47
December 0.198282E+09 0.379841E+09 372003.62 3944347.04 40487004.98 0.314938E+09 0.522695E+09 7695.28 0.47
                   
Annual Sum or Average 0.988421E+09 0.120921E+11 7585308.63 26385357.01 0.763708E+09 0.128260E+10 0.299493E+10 175867.12 0.47
Minimum of Months 0.00 0.137473E+09 165285.17 0.00 22261110.83 0.00 0.00 3713.49 0.47
Maximum of Months 0.258379E+09 0.204111E+10 1271334.34 5388360.87 0.107752E+09 0.445811E+09 0.601997E+09 31557.97 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.291557E+09 0.122505E+09 429042.75 1644493.77 43496459.22 0.665975E+09 0.266357E+09 9596.70 0.47
February 0.190252E+09 0.155043E+09 297901.81 1883952.21 47721816.68 0.345768E+09 0.321065E+09 11427.98 0.47
March 0.196959E+09 0.302657E+09 343201.13 2860061.01 47617524.40 0.286310E+09 0.390674E+09 14235.98 0.47
April 53856545.30 0.635388E+09 524947.94 2848722.40 64884874.52 739303.43 0.294500E+09 21136.37 0.47
May 0.00 0.152130E+10 987637.80 0.00 93597814.23 0.00 0.00 20895.62 0.47
June 0.00 0.165764E+10 114000.21 0.00 80299930.96 0.00 0.00 5038.47 0.47
July 0.00 0.204374E+10 426189.31 0.00 0.105036E+09 0.00 0.00 8445.55 0.47
August 0.00 0.186031E+10 725523.10 0.00 0.103181E+09 0.00 0.00 14203.85 0.47
September 0.00 0.163051E+10 1260465.00 0.00 0.114396E+09 0.00 0.00 28174.20 0.47
October 30424588.48 0.122292E+10 798488.41 1622398.03 91680488.93 3142390.14 0.169071E+09 31495.13 0.47
November 0.123421E+09 0.427874E+09 484269.78 2906163.98 62983901.26 0.123523E+09 0.484621E+09 19808.76 0.47
December 0.225380E+09 0.360986E+09 586648.96 1687846.53 59070415.28 0.475710E+09 0.336960E+09 15384.61 0.47
                   
Annual Sum or Average 0.111185E+10 0.119409E+11 6978316.20 15453637.92 0.913965E+09 0.190117E+10 0.226325E+10 199843.23 0.47
Minimum of Months 0.00 0.122505E+09 114000.21 0.00 43496459.22 0.00 0.00 5038.47 0.47
Maximum of Months 0.291557E+09 0.204374E+10 1260465.00 2906163.98 0.114396E+09 0.665975E+09 0.484621E+09 31495.13 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.841602E+10 0.207258E+10 0.00 47508988.10 0.184461E+09 0.00 0.815556E+10 0.00 0.54
February 0.679432E+10 0.269023E+10 0.00 24495284.14 63586654.31 0.00 0.482939E+10 0.00 0.54
March 0.958939E+10 0.439290E+10 0.00 13266460.32 0.361919E+09 0.00 0.228740E+10 0.00 0.54
April 0.339495E+10 0.868820E+10 0.00 7104553.52 0.815390E+09 0.00 0.137055E+10 0.00 0.54
May 0.00 0.218377E+11 0.00 0.00 75151911.87 0.00 0.00 0.00 0.54
June 0.00 0.234861E+11 0.00 0.00 83115002.71 0.00 0.00 0.00 0.54
July 0.00 0.291258E+11 0.00 0.00 19016967.08 0.00 0.00 0.00 0.54
August 0.00 0.266163E+11 0.00 0.00 20007174.20 0.00 0.00 0.00 0.54
September 0.00 0.236519E+11 0.00 0.00 27736660.58 0.00 0.00 0.00 0.54
October 0.972408E+09 0.178377E+11 0.00 12284702.58 467887.87 0.00 0.178522E+10 0.00 0.54
November 0.344571E+10 0.663266E+10 0.00 48422817.75 30552507.97 0.00 0.646580E+10 0.00 0.54
December 0.784219E+10 0.555126E+10 0.00 40861217.71 0.153161E+09 0.00 0.621651E+10 0.00 0.54
                   
Annual Sum or Average 0.404550E+11 0.172583E+12 0.00 0.193944E+09 0.183456E+10 0.00 0.311104E+11 0.00 0.54
Minimum of Months 0.00 0.207258E+10 0.00 0.00 467887.87 0.00 0.00 0.00 0.54
Maximum of Months 0.958939E+10 0.291258E+11 0.00 48422817.75 0.815390E+09 0.00 0.815556E+10 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.396513E+10 0.143435E+10 5883363.18 22972056.74 0.817362E+09 0.316704E+10 0.946849E+10 67588.32 0.53
February 0.264275E+10 0.157329E+10 7763365.03 23851301.95 0.117338E+10 0.158292E+10 0.740187E+10 140807.88 0.54
March 0.271529E+10 0.334688E+10 3356166.64 33981744.29 0.140582E+10 0.620726E+09 0.852330E+10 57782.29 0.54
April 0.822346E+09 0.714503E+10 8615752.17 25464837.13 0.235245E+10 7199104.59 0.391890E+10 93302.45 0.54
May 0.00 0.176061E+11 7688676.51 0.00 0.430501E+10 0.00 0.00 43955.60 0.54
June 0.00 0.200438E+11 13978568.50 0.00 0.351785E+10 0.00 0.00 63896.54 0.54
July 0.00 0.247196E+11 12145185.07 0.00 0.442095E+10 0.00 0.00 41275.28 0.54
August 0.00 0.218366E+11 5911572.86 0.00 0.480112E+10 0.00 0.00 13391.41 0.54
September 0.00 0.182283E+11 8604976.48 0.00 0.544911E+10 0.00 0.00 54877.71 0.54
October 0.438643E+09 0.136546E+11 9662771.44 15417407.24 0.417876E+10 2659760.09 0.231395E+10 74648.53 0.54
November 0.182523E+10 0.469767E+10 7605696.72 32131916.75 0.195968E+10 36968627.42 0.806833E+10 85444.68 0.54
December 0.316970E+10 0.416413E+10 3324431.40 23561877.61 0.153847E+10 0.156199E+10 0.934817E+10 46887.01 0.53
                   
Annual Sum or Average 0.155791E+11 0.138450E+12 94540525.99 0.177381E+09 0.359200E+11 0.697950E+10 0.490430E+11 783857.72 0.54
Minimum of Months 0.00 0.143435E+10 3324431.40 0.00 0.817362E+09 0.00 0.00 13391.41 0.53
Maximum of Months 0.396513E+10 0.247196E+11 13978568.50 33981744.29 0.544911E+10 0.316704E+10 0.946849E+10 140807.88 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.260279E+09 0.138726E+09 166164.61 4220649.15 27564365.51 0.450073E+09 0.511105E+09 3190.27 0.47
February 0.177308E+09 0.182615E+09 52903.66 3534774.25 20426089.86 0.237001E+09 0.441225E+09 3888.93 0.47
March 0.171123E+09 0.331704E+09 50793.22 4172190.39 18917038.48 0.237680E+09 0.463930E+09 1126.01 0.47
April 28740998.09 0.661230E+09 211811.49 3417860.40 39455873.17 409099.53 0.319417E+09 3732.81 0.47
May 0.00 0.155934E+10 144850.39 0.00 56617008.79 0.00 0.00 1119.75 0.47
June 0.00 0.168879E+10 0.00 0.00 49466818.21 0.00 0.00 0.00 0.47
July 0.00 0.208299E+10 47361.04 0.00 66428319.08 0.00 0.00 1199.13 0.47
August 0.00 0.189602E+10 120705.93 0.00 68317830.30 0.00 0.00 2227.36 0.47
September 0.00 0.167188E+10 140849.61 0.00 74374147.19 0.00 0.00 1961.02 0.47
October 22422312.79 0.126826E+10 194001.94 2077723.96 47133291.47 201968.63 0.179583E+09 4122.43 0.47
November 77804305.61 0.458940E+09 188525.45 6060994.60 32286067.62 44163895.71 0.606528E+09 5494.44 0.47
December 0.198246E+09 0.379846E+09 475940.70 3788514.03 40378757.52 0.341190E+09 0.496635E+09 6591.20 0.47
                   
Annual Sum or Average 0.935923E+09 0.123203E+11 1793908.05 27272706.79 0.541366E+09 0.131072E+10 0.301842E+10 34653.35 0.47
Minimum of Months 0.00 0.138726E+09 0.00 0.00 18917038.48 0.00 0.00 0.00 0.47
Maximum of Months 0.260279E+09 0.208299E+10 475940.70 6060994.60 74374147.19 0.450073E+09 0.606528E+09 6591.20 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.292228E+09 0.123036E+09 454157.29 1466709.53 42936219.66 0.646134E+09 0.285705E+09 13435.17 0.47
February 0.194830E+09 0.154571E+09 402497.19 1754068.26 48085493.15 0.336712E+09 0.325672E+09 14686.38 0.47
March 0.195860E+09 0.323987E+09 170299.73 2840216.12 26470142.38 0.276829E+09 0.401273E+09 4549.14 0.47
April 37156290.78 0.656203E+09 210449.27 2934276.29 44398116.52 886574.30 0.310967E+09 7544.76 0.47
May 0.00 0.155981E+10 145291.68 0.00 55953139.63 0.00 0.00 661.36 0.47
June 0.00 0.169114E+10 0.00 0.00 46910217.12 0.00 0.00 0.00 0.47
July 0.00 0.208517E+10 48006.35 0.00 63991764.31 0.00 0.00 548.13 0.47
August 0.00 0.189366E+10 121272.25 0.00 70447260.68 0.00 0.00 1646.63 0.47
September 0.00 0.166345E+10 140516.40 0.00 82606084.30 0.00 0.00 2277.50 0.47
October 31208902.91 0.125070E+10 278265.08 1589478.24 64441207.65 6529515.57 0.164933E+09 9876.51 0.47
November 0.134188E+09 0.439220E+09 247338.40 3219273.83 51887261.10 0.115726E+09 0.481338E+09 7991.04 0.47
December 0.232399E+09 0.358972E+09 726023.37 1410046.75 60943613.96 0.472200E+09 0.333729E+09 16864.64 0.47
                   
Annual Sum or Average 0.111787E+10 0.121999E+11 2944117.02 15214069.01 0.659071E+09 0.185502E+10 0.230362E+10 80081.28 0.47
Minimum of Months 0.00 0.123036E+09 0.00 0.00 26470142.38 0.00 0.00 0.00 0.47
Maximum of Months 0.292228E+09 0.208517E+10 726023.37 3219273.83 82606084.30 0.646134E+09 0.481338E+09 16864.64 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.215890E+11 0.00 0.00 0.00 0.100678E+10 0.00 0.00 0.00 0.54
February 0.160096E+11 0.00 0.00 0.00 0.107534E+10 0.00 0.00 0.00 0.55
March 0.162521E+11 0.00 0.00 0.00 0.216303E+10 0.00 0.00 0.00 0.55
April 0.796355E+10 0.327548E+09 0.00 0.00 0.469073E+10 0.00 0.00 0.00 0.54
May 0.00 0.610662E+10 0.00 0.00 0.973366E+10 0.00 0.00 0.00 0.50
June 26523261.92 0.114893E+11 0.00 34195.83 0.559949E+10 0.00 20217403.49 0.00 0.50
July 0.00 0.166626E+11 0.00 0.00 0.545105E+10 0.00 0.00 0.00 0.50
August 6562658.01 0.136067E+11 0.00 26657.22 0.634266E+10 0.00 29525479.58 0.00 0.50
September 0.00 0.105186E+11 0.00 0.00 0.835450E+10 0.00 0.00 0.00 0.50
October 0.406076E+10 0.831605E+10 0.00 629194.73 0.448665E+10 0.00 0.509819E+09 0.00 0.52
November 0.141912E+11 0.559411E+09 0.00 0.00 0.343640E+10 0.00 0.00 0.00 0.55
December 0.183511E+11 87219768.46 0.00 0.00 0.278002E+10 0.00 0.00 0.00 0.54
                   
Annual Sum or Average 0.984504E+11 0.676740E+11 0.00 690047.78 0.551203E+11 0.00 0.559562E+09 0.00 0.52
Minimum of Months 0.00 0.00 0.00 0.00 0.100678E+10 0.00 0.00 0.00 0.50
Maximum of Months 0.215890E+11 0.166626E+11 0.00 629194.73 0.973366E+10 0.00 0.509819E+09 0.00 0.55



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 66984022.80 34246968.95 54159.89 792036.61 7312799.93 0.150802E+09 87840948.79 1010.58 0.47
February 44171796.14 45299367.66 35871.48 691703.51 5438041.14 86704825.27 83198957.42 1106.07 0.47
March 44733202.04 80202621.29 68226.69 852572.97 7395399.01 88838058.99 84802532.03 2047.01 0.47
April 12446564.41 0.160610E+09 107465.12 680297.30 14502578.83 6757186.42 68112303.61 5384.04 0.47
May 0.00 0.379287E+09 463504.96 0.00 24260732.99 0.00 0.00 13617.89 0.47
June 0.00 0.412900E+09 325273.79 0.00 21330611.31 0.00 0.00 8803.50 0.47
July 0.00 0.509798E+09 347779.80 0.00 27213302.17 0.00 0.00 6184.72 0.47
August 0.00 0.464067E+09 492614.32 0.00 26544243.21 0.00 0.00 11001.08 0.47
September 0.00 0.409742E+09 413792.14 0.00 26433764.46 0.00 0.00 9813.19 0.47
October 7387668.74 0.311543E+09 237421.53 401797.62 17108691.30 3976393.83 39305292.23 7276.56 0.47
November 24517657.02 0.112722E+09 103949.91 1044418.54 10025986.69 37551513.50 0.120526E+09 3131.59 0.47
December 49994121.14 94669534.65 98680.88 748011.43 10406200.08 0.114213E+09 95009831.83 2502.06 0.47
                   
Annual Sum or Average 0.250235E+09 0.301509E+10 2748740.52 5210837.99 0.197972E+09 0.488843E+09 0.578796E+09 71878.28 0.47
Minimum of Months 0.00 34246968.95 35871.48 0.00 5438041.14 0.00 0.00 1010.58 0.47
Maximum of Months 66984022.80 0.509798E+09 492614.32 1044418.54 27213302.17 0.150802E+09 0.120526E+09 13617.89 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 71835946.87 30549231.07 322735.89 280302.85 10734342.02 0.195053E+09 39213869.43 3754.56 0.47
February 45999752.37 39788369.07 78932.03 321887.39 10897925.12 0.121413E+09 47007140.15 3211.17 0.47
March 47394735.63 76522926.09 92646.61 567384.13 11038750.39 0.103398E+09 67840227.53 3699.28 0.47
April 13402789.30 0.158647E+09 107396.38 582614.42 16445332.86 11888460.54 62112177.42 5516.46 0.47
May 0.00 0.379766E+09 414448.78 0.00 23786074.19 0.00 0.00 11386.78 0.47
June 0.00 0.414203E+09 272035.92 0.00 20034117.47 0.00 0.00 4461.27 0.47
July 0.00 0.510652E+09 213052.45 0.00 26433866.19 0.00 0.00 3478.39 0.47
August 0.00 0.462958E+09 451156.03 0.00 27638929.91 0.00 0.00 9402.27 0.47
September 0.00 0.406326E+09 447896.65 0.00 29764824.21 0.00 0.00 10062.70 0.48
October 7866867.26 0.304462E+09 270052.95 297608.52 24117943.52 10341819.79 32558873.13 8423.52 0.47
November 31767656.94 0.106886E+09 174616.39 488874.58 15773755.92 73885967.26 77475291.60 5726.85 0.47
December 54674429.87 90036052.60 222137.06 274830.04 14900288.85 0.160359E+09 44626279.43 6116.16 0.47
                   
Annual Sum or Average 0.272942E+09 0.298080E+10 3067107.15 2813501.94 0.231566E+09 0.676340E+09 0.370834E+09 75239.41 0.47
Minimum of Months 0.00 30549231.07 78932.03 0.00 10734342.02 0.00 0.00 3211.17 0.47
Maximum of Months 71835946.87 0.510652E+09 451156.03 582614.42 29764824.21 0.195053E+09 77475291.60 11386.78 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.233671E+09 0.229383E+09 159135.99 14452484.89 37811959.22 0.361999E+09 0.135846E+10 473.78 0.54
February 0.179160E+09 0.304019E+09 36402.34 9196254.50 22143169.27 0.217352E+09 0.974063E+09 916.68 0.54
March 0.257670E+09 0.522178E+09 225467.41 7086977.85 40815076.58 0.304869E+09 0.838791E+09 5719.09 0.54
April 68890791.14 0.102100E+10 615975.76 4078124.04 0.104100E+09 1205346.54 0.491157E+09 12318.89 0.54
May 0.00 0.240389E+10 1707446.53 0.00 0.190015E+09 0.00 0.00 38515.12 0.54
June 0.00 0.260583E+10 1263290.43 0.00 0.184741E+09 0.00 0.00 22165.31 0.54
July 0.00 0.322602E+10 948240.63 0.00 0.225313E+09 0.00 0.00 14972.61 0.54
August 0.00 0.295000E+10 1307703.46 0.00 0.203831E+09 0.00 0.00 24322.11 0.54
September 0.00 0.262882E+10 1176535.97 0.00 0.174903E+09 0.00 0.00 27978.54 0.54
October 37409453.47 0.202317E+10 386160.26 3357648.36 89430213.11 694726.86 0.286644E+09 3790.06 0.54
November 0.108563E+09 0.745132E+09 203447.70 13045530.15 43941491.69 3390753.03 0.105479E+10 3397.03 0.54
December 0.219087E+09 0.624320E+09 435549.16 11976032.73 50949392.76 0.249402E+09 0.118968E+10 2714.49 0.54
                   
Annual Sum or Average 0.110445E+10 0.192838E+11 8465355.64 63193052.51 0.136800E+10 0.113891E+10 0.619359E+10 157283.70 0.54
Minimum of Months 0.00 0.229383E+09 36402.34 0.00 22143169.27 0.00 0.00 473.78 0.54
Maximum of Months 0.257670E+09 0.322602E+10 1707446.53 14452484.89 0.225313E+09 0.361999E+09 0.135846E+10 38515.12 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.226321E+10 0.174365E+10 0.00 62713916.38 12785236.85 0.00 0.347737E+11 0.00 4.39
February 0.142141E+10 0.177056E+10 0.00 52645230.85 14178451.95 0.00 0.266550E+11 0.00 4.58
March 0.109815E+10 0.375721E+10 0.00 61384002.86 9031167.87 0.00 0.282586E+11 0.00 4.65
April 77963364.74 0.960604E+10 0.00 39218491.07 2084751.50 0.00 0.152489E+11 0.00 4.82
May 0.00 0.310339E+11 0.00 0.00 0.00 0.00 0.00 0.00 4.70
June 0.00 0.334672E+11 0.00 795650.05 0.00 0.00 0.103482E+09 0.00 4.75
July 0.00 0.429525E+11 0.00 0.00 0.00 0.00 0.00 0.00 4.72
August 0.00 0.387256E+11 0.00 351270.73 0.00 0.00 69096474.12 0.00 4.67
September 0.00 0.363697E+11 0.00 0.00 0.00 0.00 0.00 0.00 4.62
October 6835965.43 0.241277E+11 0.00 20990498.85 4574758.10 0.00 0.878643E+10 0.00 4.66
November 0.325271E+09 0.748039E+10 0.00 51852749.49 5236061.70 0.00 0.254847E+11 0.00 4.66
December 0.205186E+10 0.516549E+10 0.00 53093258.05 7601005.48 0.00 0.298460E+11 0.00 4.44
                   
Annual Sum or Average 0.724470E+10 0.236200E+12 0.00 0.343045E+09 55491433.45 0.00 0.169226E+12 0.00 4.64
Minimum of Months 0.00 0.174365E+10 0.00 0.00 0.00 0.00 0.00 0.00 4.39
Maximum of Months 0.226321E+10 0.429525E+11 0.00 62713916.38 14178451.95 0.00 0.347737E+11 0.00 4.82



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.147076E+10 0.188511E+10 0.00 76894172.70 0.00 0.00 0.386591E+11 0.00 4.74
February 0.664397E+09 0.191240E+10 0.00 63005908.53 0.00 0.00 0.297029E+11 0.00 4.93
March 0.434835E+09 0.404986E+10 0.00 72286971.14 0.00 0.00 0.313188E+11 0.00 5.02
April 4632508.13 0.102558E+11 0.00 44259485.89 0.00 0.00 0.164730E+11 0.00 5.17
May 0.00 0.329591E+11 0.00 0.00 0.00 0.00 0.00 0.00 4.99
June 0.00 0.354988E+11 0.00 832834.65 0.00 0.00 0.108287E+09 0.00 5.02
July 0.00 0.455546E+11 0.00 0.00 0.00 0.00 0.00 0.00 4.99
August 0.00 0.410681E+11 0.00 368272.71 0.00 0.00 72477889.90 0.00 4.94
September 0.00 0.385980E+11 0.00 0.00 0.00 0.00 0.00 0.00 4.89
October 0.00 0.255918E+11 0.00 23300816.81 0.00 0.00 0.937772E+10 0.00 4.95
November 0.122802E+09 0.797271E+10 0.00 60174622.69 18857.38 0.00 0.276643E+11 0.00 4.99
December 0.111236E+10 0.551471E+10 0.00 64230983.85 619559.47 0.00 0.333589E+11 0.00 4.78
                   
Annual Sum or Average 0.380978E+10 0.250861E+12 0.00 0.405354E+09 638416.85 0.00 0.186735E+12 0.00 4.95
Minimum of Months 0.00 0.188511E+10 0.00 0.00 0.00 0.00 0.00 0.00 4.74
Maximum of Months 0.147076E+10 0.455546E+11 0.00 76894172.70 619559.47 0.00 0.386591E+11 0.00 5.17



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 35567401.16 0.283870E+10 0.00 0.124255E+09 0.00 0.00 0.502129E+11 0.00 20.12
February 44580621.12 0.312148E+10 0.00 94513135.90 0.00 0.00 0.366172E+11 0.00 20.69
March 0.186092E+09 0.610097E+10 0.00 98205050.47 0.00 0.00 0.372756E+11 0.00 20.66
April 0.00 0.134787E+11 0.00 56476740.07 0.00 0.00 0.180956E+11 0.00 20.77
May 0.00 0.421494E+11 0.00 0.00 0.00 0.00 0.00 0.00 19.37
June 0.00 0.451522E+11 0.00 559787.10 0.00 0.00 74398355.66 0.00 19.27
July 0.00 0.579788E+11 0.00 0.00 0.00 0.00 0.00 0.00 19.19
August 0.00 0.525808E+11 0.00 294643.66 0.00 0.00 59932891.11 0.00 19.10
September 0.00 0.494669E+11 0.00 0.00 0.00 0.00 0.00 0.00 19.17
October 0.00 0.329566E+11 0.00 29503862.52 0.00 0.00 0.103014E+11 0.00 19.68
November 16831137.84 0.105438E+11 0.00 83855357.89 0.00 0.00 0.328508E+11 0.00 20.77
December 61803922.55 0.766891E+10 0.00 0.100855E+09 0.00 0.00 0.428660E+11 0.00 20.09
                   
Annual Sum or Average 0.344875E+09 0.324037E+12 0.00 0.588518E+09 0.00 0.00 0.228354E+12 0.00 19.90
Minimum of Months 0.00 0.283870E+10 0.00 0.00 0.00 0.00 0.00 0.00 19.10
Maximum of Months 0.186092E+09 0.579788E+11 0.00 0.124255E+09 0.00 0.00 0.502129E+11 0.00 20.77



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.114095E+11 22000271.01 0.00 6375.48 0.510862E+09 309890.09 15894831.66 0.00 1.08
February 0.842166E+10 87849107.85 0.00 0.00 0.481259E+09 51203500.00 0.00 0.00 1.10
March 0.859988E+10 6734857.74 0.00 0.00 0.113802E+10 1324150.34 0.00 0.00 1.10
April 0.421349E+10 0.120180E+10 0.00 3720.03 0.147150E+10 0.00 1104853.19 0.00 1.09
May 0.00 0.723888E+10 0.00 0.00 0.145313E+10 0.00 0.00 0.00 1.03
June 14957070.44 0.910914E+10 0.00 17054.59 0.539150E+09 0.00 9780856.86 0.00 1.06
July 0.00 0.117341E+11 0.00 0.00 0.695570E+09 0.00 0.00 0.00 1.06
August 626885.06 0.102610E+11 0.00 19378.93 0.859983E+09 0.00 18467017.53 0.00 1.04
September 0.00 0.842892E+10 0.00 0.00 0.191411E+10 0.00 0.00 0.00 1.03
October 0.214119E+10 0.594760E+10 0.00 521114.48 0.107510E+10 0.00 0.277214E+09 0.00 1.06
November 0.750319E+10 0.887012E+09 0.00 6192.79 0.124597E+10 0.00 7310955.04 0.00 1.09
December 0.963785E+10 0.404292E+09 0.00 44997.59 0.111584E+10 12009005.72 62178361.76 0.00 1.08
                   
Annual Sum or Average 0.519423E+11 0.553293E+11 0.00 618833.88 0.125005E+11 64846546.14 0.391951E+09 0.00 1.07
Minimum of Months 0.00 6734857.74 0.00 0.00 0.481259E+09 0.00 0.00 0.00 1.03
Maximum of Months 0.114095E+11 0.117341E+11 0.00 521114.48 0.191411E+10 51203500.00 0.277214E+09 0.00 1.10



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:00:00

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.220382E+12 0.845888E+10 0.103553E+12 0.465213E+12 0.339486E+12
February 0.237650E+12 0.562326E+10 0.694712E+11 0.312170E+12 0.409654E+12
March 0.285086E+12 0.455479E+10 0.586618E+11 0.261799E+12 0.519161E+12
April 0.303892E+12 -755429679.8 -0.498242E+10 -0.222887E+11 0.850059E+12
May 0.308692E+12 -0.114849E+11 -0.143716E+12 -0.639337E+12 0.151381E+13
June 0.302729E+12 -0.125104E+11 -0.160773E+12 -0.705742E+12 0.154368E+13
July 0.315816E+12 -0.159427E+11 -0.207583E+12 -0.906710E+12 0.172689E+13
August 0.294035E+12 -0.143198E+11 -0.184303E+12 -0.795656E+12 0.167215E+13
September 0.251020E+12 -0.128410E+11 -0.157984E+12 -0.689600E+12 0.157494E+13
October 0.264247E+12 -0.741032E+10 -0.926179E+11 -0.395389E+12 0.130608E+13
November 0.183805E+12 0.224836E+10 0.269814E+11 0.137824E+12 0.665177E+12
December 0.193824E+12 0.567038E+10 0.718914E+11 0.319505E+12 0.503792E+12
           
Annual Sum or Average 0.316118E+13 -0.487089E+11 -0.621401E+12 -0.265821E+13 0.126249E+14
Minimum of Months 0.183805E+12 -0.159427E+11 -0.207583E+12 -0.906710E+12 0.339486E+12
Maximum of Months 0.315816E+12 0.845888E+10 0.103553E+12 0.465213E+12 0.172689E+13