Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:59

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860

Simulation Timestamp: 2023-10-16 08:59:43


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 11319.41 997.72 997.72
Net Site Energy 11319.41 997.72 997.72
Total Source Energy 24082.56 2122.69 2122.69
Net Source Energy 24082.56 2122.69 2122.69


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 761.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1189.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 766.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 242.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1745.01 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 651.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 571.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 129.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 222.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.75 3097.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 62.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 5670.82 5648.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 761.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 1189.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 766.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 242.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 959.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 14.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 8.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 32.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 571.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 129.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 222.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.75 3097.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 20.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 34.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 761.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 1189.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 766.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 242.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1745.01 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 651.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 571.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 129.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 222.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 90.75 3097.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 62.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 88.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 174.60 340.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 236.29 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 499.84 497.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 88.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 174.60 340.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 236.29 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 499.84 497.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 5670.823 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 5670.823 100.00
     
Total On-Site and Utility Electric Sources 5670.823 100.00
Total Electricity End Uses 5670.823 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 555.57 15.95
Air to Air Heat Recovery for Heating 2928.16 84.05
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 3483.73 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 2.50
Time Setpoint Not Met During Occupied Cooling 310.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 8133.83


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:59
RunPeriod RUNPERIOD 1
Weather File New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Latitude [deg] 40.65
Longitude [deg] -73.8
Elevation [m] 5.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 9.1389 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 13.3365 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 13.3365 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 9.2031 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 6.1031 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.8125 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 10.3656 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 8.7188 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 4.5531 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 4.5531 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 6.3938 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 4.5531 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.3656 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.3656 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 11.7219 4.65 2934.4875
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 6.3938 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 6.8557 7.07 41.0709
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 6.8557 7.07 41.0709
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 9.1389 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 13.3365 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 13.3365 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 9.2031 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 6.1031 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.8125 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 10.3656 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 8.7188 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 4.5531 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 4.5531 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 4.5531 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 4.5531 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 4.5531 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 4.5531 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 6.3938 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 4.5531 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 4.5531 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 4.5531 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 10.3656 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 10.3656 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 11.7219 4.65 2934.4875  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 6.3938 18.58 0.0000  
Total 11345.29             6.8557 3.54 41.0709  
Conditioned Total 11345.29             6.8557 3.54 41.0709  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 4.4542 8.82 37.1989
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 04-AUG-19:10 05-FEB-19:10 - - - - - - - - - - 12-JAN-21:19
Heating 0.00 209264.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 199615.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 88772.42 83438.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 32150.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 33670.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 7013.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 3529.80 267304.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 1873.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 454905.91 560006.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 209264.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 199615.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 58789.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 49984.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 33453.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1846.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 30153.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 150.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 33670.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 7013.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 3529.80 267304.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 241.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 536.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 1096.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 825.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 3766.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2427.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 768.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5526.46 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2063.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1810.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 409.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 703.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 287.39 3358.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 196.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 17959.50 6123.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 72.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 331.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 213.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 67.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 487.11 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 159.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 36.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 62.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 296.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1582.99 539.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 72.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 331.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 213.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 67.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 487.11 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 159.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 36.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 62.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 296.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1582.99 539.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.52 0.599008 0.528000 1.33 1.00 0.500000 0.000636 0.000061 1.33 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.388518 0.131547 0.528000 0.205138 0.528000 0.500000 0.002896 0.000036 0.205138 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.240329 0.246261 0.528000 0.126894 0.656697 0.500000 0.001547 0.000015 0.126894 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.233530 0.535921 0.528000 0.123304 1.00 0.500000 0.000711 0.000023 0.123304 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.113177 0.637997 0.528000 0.059757 1.00 0.500000 0.000597 0.000013 0.059757 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.26 0.072292 0.528000 1.72 0.528000 0.500000 0.020914 0.000102 1.72 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.57 0.091791 0.528000 0.827817 0.528000 0.500000 0.004151 0.000104 0.827817 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 4.76 0.209364 0.528000 2.51 0.558304 0.500000 0.001820 0.000275 2.51 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.50 0.789112 0.528000 0.794166 1.00 0.500000 0.000483 0.000132 0.794166 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.18 0.116121 0.528000 1.15 0.528000 0.500000 0.003281 0.000111 1.15 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.28 0.110807 0.528000 1.20 0.528000 0.500000 0.003438 0.000115 1.20 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.27 0.062385 0.528000 1.20 0.528000 0.500000 0.010985 0.000077 1.20 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.774596 0.405423 0.528000 0.408987 1.00 0.500000 0.000940 0.000079 0.408987 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 7014.41 0.000061 146.27
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 4102.09 0.000036 100.29
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1721.57 0.000015 39.11
MECH_FLR_1 VAV BOX REHEAT COIL 2604.15 0.000023 64.53
STORAGE_FLR_1 VAV BOX REHEAT COIL 1495.16 0.000013 38.91
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 11674.17 0.000102 247.08
CAFE_FLR_1 VAV BOX REHEAT COIL 11909.29 0.000104 273.01
LOBBY_FLR_1 VAV BOX REHEAT COIL 31385.41 0.000275 704.72
ROOM_1_FLR_3 FAN COIL HEATING COIL 6925.28 0.000061 197.91
ROOM_2_FLR_3 FAN COIL HEATING COIL 6944.49 0.000061 198.45
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 39426.23 0.000345 1126.68
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 39798.13 0.000348 1137.30
ROOM_5_FLR_3 FAN COIL HEATING COIL 6886.18 0.000060 196.79
ROOM_6_FLR_3 FAN COIL HEATING COIL 6905.40 0.000060 197.34
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 15090.80 0.000132 364.61
ROOM_1_FLR_6 FAN COIL HEATING COIL 2085.98 0.000018 59.61
ROOM_2_FLR_6 FAN COIL HEATING COIL 2092.41 0.000018 59.79
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 9911.65 0.000087 283.23
BANQUET_FLR_6 VAV BOX REHEAT COIL 12730.98 0.000111 281.61
DINING_FLR_6 VAV BOX REHEAT COIL 13167.56 0.000115 290.82
KITCHEN_FLR_6 VAV BOX REHEAT COIL 8850.44 0.000077 188.47
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 9028.71 0.000079 226.38
VAV WITH REHEAT HEATING COIL 218405.54 0.001911 3604.87
FLR_3_DOAS HEATING COIL 20393.42 0.000178 336.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ZoneExhaust

User-Specified Maximum Flow Rate [m3/s]
LOBBY_FLR_1 EXHAUST FAN 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 1.14 0.000061 0.000465
ROOM_2_FLR_3 FAN COIL 1.10 0.000061 0.000451
ROOM_3_MULT19_FLR_3 FAN COIL 6.53 0.000345 0.002614
ROOM_4_MULT19_FLR_3 FAN COIL 5.76 0.000348 0.002464
ROOM_5_FLR_3 FAN COIL 1.04 0.000060 0.000425
ROOM_6_FLR_3 FAN COIL 1.01 0.000060 0.000414
ROOM_1_FLR_6 FAN COIL 0.299295 0.000018 0.000122
ROOM_2_FLR_6 FAN COIL 0.289526 0.000018 0.000118
ROOM_3_MULT9_FLR_6 FAN COIL 1.37 0.000087 0.000566
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 1.14
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 1.10
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 6.53
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 5.76
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 1.04
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 1.01
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.299295
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.289526
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.37
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008667 12.80 0.008500 0.000465 1.14  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008672 12.80 0.008500 0.000451 1.10  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008596 12.80 0.008500 0.002614 6.53  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008848 12.80 0.008500 0.002464 5.76  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008684 12.80 0.008500 0.000425 1.04  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008690 12.80 0.008500 0.000414 1.01  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008659 12.80 0.008500 0.000122 0.299295  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008665 12.80 0.008500 0.000118 0.289526  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008719 12.80 0.008500 0.000566 1.37  
VAV WITH REHEAT COOLING COIL 28.30 6.70 0.012038 10.99 0.008500 0.025218 21.97 706034.18
FLR_3_DOAS COOLING COIL 32.10 6.70 0.014120 11.94 0.008500 0.003084 2.05 86334.71
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 11.66 11.66 22.09 11.66 21.97 21.97 0.300000 0.530948 21.97
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 21.97 11.66
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 11.66
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 21.97
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.025218 0.000019
VAV WITH REHEAT_HEATC_CONTROLLER 0.001911  
FLR_3_DOAS_COOLC_CONTROLLER 0.003084 0.000154
FLR_3_DOAS_HEATC_CONTROLLER 0.000178  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.035941 7406.11  
HEATSYS1 PUMP 0.004292 1292.42 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.004292 0.514985
COOLSYS1 0.035941 4.31
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 490549.46 490549.46 0.004292
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.035941 5127.50
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.035941 1006252.25 1006860.85 114.78
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 14.00 7.30 3.30 1.20 -0.20 5.60 10.90 16.10 21.70 25.00 24.80 19.90


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 40.65 -73.80 -5.00 5.00 101265 1.2036


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 12.47 25.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 9.139 5.380 0.000 0.000 0.000 0.000 14.519 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 13.336 10.760 0.000 0.000 0.000 0.000 24.096 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 13.336 10.760 0.000 0.000 0.000 0.000 24.096 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 9.203 5.380 0.000 0.000 0.000 0.000 14.583 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 6.103 2.690 0.000 0.000 0.000 0.000 8.793 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.813 61.680 535.850 0.000 0.000 0.000 603.343 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 10.366 5.380 0.000 0.000 0.000 0.000 15.746 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 8.719 8.070 0.000 0.000 0.000 0.000 16.789 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 6.394 0.000 0.000 0.000 0.000 0.000 6.394 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 10.366 67.820 0.000 0.000 0.000 0.000 78.186 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 10.366 67.820 0.000 0.000 0.000 0.000 78.186 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 11.722 515.227 2419.260 0.000 0.000 0.000 2946.209 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 6.394 0.000 0.000 0.000 0.000 0.000 6.394 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 18084.325 9.139 169.807 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 18084.325
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 894.495 13.336 82.602 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 894.495
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 1035.829 13.336 82.602 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1035.829
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 1511.551 9.203 569.967 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1511.551
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 578.329 6.103 283.494 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 578.329
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 453.605 5.813 54.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 453.605
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1957.673 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1957.673
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 11405.759 8.719 27.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 11405.759
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 111.660 4.553 74.440 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.660
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 111.691 4.553 74.460 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.691
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 2489.757 6.394 118.803 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2489.757
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 111.691 4.553 74.460 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.691
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 3437.839 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3437.839
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 3437.839 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3437.839
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1210.923 11.722 54.453 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1210.923
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 2635.024 6.394 118.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2635.024


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 457.500 4.429 20.573 0.000 0.250 0.000 0.750 ReachInFreezer 457.500 457.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 285.000 2.759 12.816 0.000 0.250 0.000 0.750 ReachInRefrigerator 285.000 285.000


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.464 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.198 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.1864 0.900 0.900 0.770 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.1864 0.900 0.900 0.770 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 0.9242 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.217 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.286 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.107 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.174 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2887
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.8346
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.9147
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.6546
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6103
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.7359
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6841
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.312
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.312
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.312
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.312
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.4637404 3.4637404 3.4637404  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.1981135 1.1981135 1.1981135  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
21 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
22 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
23 0 21.357363 0.71091016E-01 5.4032014  
24 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
25 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
26 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
27 0 21.357363 0.71091016E-01 5.4032014  
28 9 -0.28612306E-14 0.35438919E-16 -0.14997333E-09 0.48037931E-16
29 8 0.21910456E-07 0.12451452E-12 0.37817107E-03 -0.24912943E-09
30 7 -0.12252860E-01 0.64616398E-08 -0.23102096E-01 0.13931948E-03
31 6 0.40565756 0.22511349E-05 0.47235308 -0.47513834E-02
32 5 -5.1935619 0.84157732E-04 -4.4432762 0.63221026E-01
33 4 33.016121 0.68920660E-03 21.448225 -0.42229901
34 3 -111.25447 0.15035857E-02 -55.639617 1.5156026
35 2 197.15924 0.84653085E-03 77.889127 -2.9011628
36 1 -171.17492 0.90445513E-04 -55.258822 2.7457697
37 0 57.057407 0.51539406E-06 15.557951  
38 9 0.12430042E-14 0.43603463E-16 -0.13615479E-09 -0.52742981E-17
39 8 0.19963588E-07 0.16114398E-12 0.35741204E-03 -0.22699287E-09
40 7 -0.11632381E-01 0.85488282E-08 -0.22208377E-01 0.13226440E-03
41 6 0.38879653 0.30047059E-05 0.45796739 -0.45526330E-02
42 5 -5.0290001 0.11318598E-03 -4.3326723 0.61180550E-01
43 4 32.288109 0.93328928E-03 21.015642 -0.41263319
44 3 -109.70522 0.20484795E-02 -54.784283 1.4932205
45 2 195.62339 0.11595496E-02 77.105128 -2.8767741
46 1 -170.60747 0.12450863E-03 -55.031726 2.7358244
47 0 57.057407 0.71328115E-06 15.596176  
48 9 0.10418955E-14 0.45554749E-16 -0.13285794E-09 -0.34221686E-17
49 8 0.19498290E-07 0.16949498E-12 0.35235048E-03 -0.22170227E-09
50 7 -0.11480752E-01 0.90423087E-08 -0.21989859E-01 0.13054032E-03
51 6 0.38467563 0.31853038E-05 0.45444290 -0.45040579E-02
52 5 -4.9887746 0.12022067E-03 -4.3055366 0.60681782E-01
53 4 32.110117 0.99300969E-03 20.909427 -0.41027004
54 3 -109.32633 0.21828955E-02 -54.574228 1.4877470
55 2 195.24766 0.12373115E-02 76.912747 -2.8708078
56 1 -170.46860 0.13302463E-03 -54.976289 2.7333905
57 0 57.057407 0.76310210E-06 15.605744  
58 9 -0.19728226E-15 0.38070760E-16 -0.14134637E-09 0.10329039E-17
59 8 0.20696804E-07 0.14765672E-12 0.36530744E-03 -0.23532978E-09
60 7 -0.11868633E-01 0.77667999E-08 -0.22548754E-01 0.13495068E-03
61 6 0.39521686 0.27204939E-05 0.46345169 -0.46283129E-02
62 5 -5.0916664 0.10217830E-03 -4.3748670 0.61957574E-01
63 4 32.565369 0.84029717E-03 21.180735 -0.41631434
64 3 -110.29532 0.18400486E-02 -55.110745 1.5017457
65 2 196.20849 0.10394005E-02 77.404245 -2.8860650
66 1 -170.82368 0.11139293E-03 -55.118150 2.7396138
67 0 57.057407 0.63685742E-06 15.581450  
68 9 0.13059652E-14 0.41030072E-16 -0.13816519E-09 -0.47111965E-17
69 8 0.20247126E-07 0.15597406E-12 0.36047671E-03 -0.23021680E-09
70 7 -0.11724123E-01 0.82470298E-08 -0.22340566E-01 0.13330755E-03
71 6 0.39128975 0.28947446E-05 0.46009809 -0.45820219E-02
72 5 -5.0533361 0.10891817E-03 -4.3490697 0.61482301E-01
73 4 32.395785 0.89717001E-03 21.079809 -0.41406279
74 3 -109.93440 0.19673976E-02 -54.911173 1.4965315
75 2 195.85064 0.11127485E-02 77.221372 -2.8803827
76 1 -170.69145 0.11939355E-03 -55.065279 2.7372963
77 0 57.057407 0.68346468E-06 15.590432  
78 7 -0.15963512E-14 -0.15187529E-16 -0.22427203E-13 0.56155309E-15
79 6 0.17983713E-10 0.23594901E-11 0.52322926E-09 -0.18637893E-10
80 5 -0.60139213E-07 0.11510628E-07 -0.21924491E-05 0.17161312E-06
81 4 0.62746279E-04 0.43399923E-05 0.17681060E-02 -0.28244642E-03
82 3 -0.90508353E-02 0.15320797E-03 -0.21560640 0.43341486E-01
83 2 0.12836503 0.66328859E-03 2.9007871 -0.61911613
84 1 -0.32478029 0.41934727E-03 -7.1379041 1.5697129
85 0 0.20664896 0.54311639E-05 4.4522013  
86 7 -0.22427203E-13 -0.15187529E-16 -0.15963512E-14 0.56155309E-15
87 6 0.52322926E-09 0.23594901E-11 0.17983713E-10 -0.18637893E-10
88 5 -0.21924491E-05 0.11510628E-07 -0.60139213E-07 0.17161312E-06
89 4 0.17681060E-02 0.43399923E-05 0.62746279E-04 -0.28244642E-03
90 3 -0.21560640 0.15320797E-03 -0.90508353E-02 0.43341486E-01
91 2 2.9007871 0.66328859E-03 0.12836503 -0.61911613
92 1 -7.1379041 0.41934727E-03 -0.32478029 1.5697129
93 0 4.4522013 0.54311639E-05 0.20664896  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
103 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
104 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
105 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
106 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
107 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
108 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
109 0 0.43108349 0.21254961E-04 60.838472  
110 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
111 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
112 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
113 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
114 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
115 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
116 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
117 0 0.43108349 0.21254961E-04 60.838472  
118 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
119 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
120 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
121 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
122 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
123 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
124 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
125 0 0.43108349 0.21254961E-04 60.838472  
126 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
127 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
128 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
129 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
130 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
131 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
132 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
133 0 0.43108349 0.21254961E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.3856_SHGC_0.4 37 1 VerySmooth 2.191 2.191 1.000 0.401    
2 RESWINDOW_U_0.3856_SHGC_0.4 38 1 VerySmooth 2.191 2.191 1.000 0.401    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   3.40174E-002 0.31435 0.47878 0.47878 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 0.11969 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   3.40174E-002 0.31435 0.47878 0.47878 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 0.11969 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 1.500
2 RACK2 1 0 Zone Air-Cooled 3.000


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 0.576 0.5074
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 0.263 2.9576E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 3.921E-002 5.846E-004 2.885E-004 0.531 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 1.513E-002 1.949E-004 5.306E-004 0.177 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 3.577E-002 2.178E-004 5.696E-004 0.198 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 2.064E-002 2.178E-004 4.726E-004 0.198 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 4.884E-002 6.258E-004 5.569E-004 0.569 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 8.667E-002 4.589E-004 2.527E-004 0.417 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.248 1.893E-004 3.620E-004 0.172 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 6.349E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 6.350E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 2.751E-002 7.066E-005 5.696E-004 8.345E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.164E-002 4.746E-004 2.589E-004 0.561 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 4.974E-002 4.815E-004 2.609E-004 0.569 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 4.868E-002 1.181E-004 9.784E-005 0.140 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1437
2 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 7.1011E-002
3 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1609
4 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 7.9327E-002
5 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1049
6 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 4.0551E-002
7 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 4.2077E-002
8 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 1.3979E-002
9 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1633
10 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 8.6041E-002
11 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1834
12 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 9.5907E-002
13 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1161
14 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 5.0830E-002
15 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 4.7248E-002
16 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 1.9114E-002
17 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 3.4931E-002
18 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 2.0129E-002
19 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.6801E-002
20 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.5154E-002
21 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.5863E-002
22 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.0352E-002
23 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 4.1419E-002
24 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.4687E-002
25 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 3.4931E-002
26 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 2.0129E-002
27 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.6801E-002
28 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.5154E-002
29 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.5863E-002
30 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.0352E-002
31 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 4.1419E-002
32 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.4687E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 34629.43520 34629.43520 2.51728 2.51728 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 28.94267 1.41140E-002 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 0.85446 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -10.70000 1.50390E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 5343.95247 5343.95247 0.38852 0.38852 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 31.79167 1.41191E-002 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 3020.74513 3020.74513 0.12953 0.12953 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3305.70335 3305.70335 0.24033 0.24033 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 31.73000 1.41190E-002 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 1052.62825 1052.62825 4.51389E-002 9.17347E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 3212.84884 3212.84884 0.23353 0.23353 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 31.45867 1.41185E-002 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1954.30633 1954.30633 8.38043E-002 8.38043E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1557.05127 1557.05127 0.11318 0.11318 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 32.02600 1.41195E-002 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 1180.20718 1180.20718 5.06095E-002 5.77652E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 44902.36231 44902.36231 3.26417 3.26417 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 32.10000 1.41196E-002 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 2592.61910 2592.61910 0.11117 0.11117 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 21548.00079 21548.00079 1.56784 1.56784 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 31.79167 1.41191E-002 188.86188 142.30000 0.67639 0.00000
14 CAFE_FLR_1 Heating 7544.96757 7544.96757 0.32353 0.67639 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 188.86188 142.30000 0.67639 0.00000
15 LOBBY_FLR_1 Cooling 65473.02007 65473.02007 4.76127 4.76127 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 31.85333 1.41192E-002 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 18132.10487 18132.10487 0.77754 1.89399 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 11633.21607 11633.21607 1.13957 1.13957 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 31.36000 1.41183E-002 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 6925.54997 6925.54997 0.29871 0.29871 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -10.70000 1.50390E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 11276.96711 11276.96711 1.10468 1.10468 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 31.26133 1.41181E-002 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 6944.75921 6944.75921 0.29954 0.29954 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -10.70000 1.50390E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 66672.54881 66672.54881 6.53063 6.53063 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 31.85333 1.41192E-002 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 39426.74952 39426.74952 1.70061 1.70061 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 58807.60389 58807.60389 5.76070 5.76070 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 32.10000 1.41196E-002 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 39798.65659 39798.65659 1.71665 1.71665 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 10598.29248 10598.29248 1.03820 1.03820 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 28.86867 1.41138E-002 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 6886.44083 6886.44083 0.29703 0.29703 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -10.70000 1.50390E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 10288.15957 10288.15957 1.00782 1.00782 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 28.44933 1.41131E-002 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 6905.66647 6905.66647 0.29786 0.29786 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -10.70000 1.50390E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 20691.81162 20691.81162 1.50410 1.50410 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 32.10000 1.41196E-002 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 10902.84151 10902.84151 0.46754 0.47476 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 3055.32523 3055.32523 0.29930 0.29930 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 31.36000 1.41183E-002 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 2086.05700 2086.05700 8.99762E-002 8.99762E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -10.70000 1.50390E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2955.59954 2955.59954 0.28953 0.28953 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 31.26133 1.41181E-002 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 2092.48648 2092.48648 9.02535E-002 9.02535E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -10.70000 1.50390E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 13968.14424 13968.14424 1.36832 1.36832 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 31.85333 1.41192E-002 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 9911.94272 9911.94272 0.42753 0.42753 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -10.70000 1.50390E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 29903.24138 29903.24138 2.17637 2.17637 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 32.10000 1.41196E-002 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 6670.78827 6670.78827 0.28606 1.18780 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 31337.93064 31337.93064 2.28075 2.28075 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 32.10000 1.41196E-002 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 6816.63662 6816.63662 0.29231 1.18780 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 31140.20697 31140.20697 2.26954 2.26954 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 31.43400 1.41184E-002 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 2545.68237 2545.68237 0.10915 0.36735 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 -10.70000 1.50390E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 10656.07318 10656.07318 0.77460 0.77460 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 31.97667 1.41194E-002 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 6871.55890 6871.55890 0.29467 0.29467 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 411394.29 21.96881 21.96881 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 245598.38 7.41122 7.41122 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00
3 FLR_3_DOAS Cooling Sensible 47880.67 17.42703 2.05125 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 FLR_3_DOAS Heating Sensible 67975.66 5.21818 2.05125 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.51728
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.59901
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.32912
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.36051E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.13651E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.32912
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7014.40575
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.13651E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 146.27334
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.38852
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13155
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20514
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52800
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.89631E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.58869E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.20514
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4102.09207
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.58869E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 100.28749
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.24033
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24626
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12689
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.65670
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.54714E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.50610E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.12689
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1721.56908
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.50610E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 39.11164
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.23353
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.53592
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12330
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.10926E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.27823E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.12330
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2604.15424
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.27823E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 64.53463
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.11318
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.63800
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.97574E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.97181E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.30803E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.97574E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1495.16344
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.30803E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 38.90705
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.26417
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.22921E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.72348
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52800
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.09136E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.02131E-004
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.72348
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11674.16877
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.02131E-004
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 247.07997
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.56784
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.17907E-002
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.82782
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52800
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.15075E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.04188E-004
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.82782
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11909.28942
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.04188E-004
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 273.00688
99 Fan:ZoneExhaust LOBBY_FLR_1 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.76127
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20936
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.51395
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.55830
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.81980E-003
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.74573E-004
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.51395
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
110 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 31385.41485
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.74573E-004
113 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 704.71792
114 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
115 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.13957
116 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.13957
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 6.05854E-005
118 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.64928E-004
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68268
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.66703E-003
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.64928E-004
125 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.13957
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6925.28435
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.05854E-005
128 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 197.90598
129 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
130 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.10468
131 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.10468
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 6.07535E-005
133 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.51328E-004
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68267
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.67231E-003
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.51328E-004
140 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.10468
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6944.49289
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.07535E-005
143 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 198.45475
144 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
145 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 6.53063
146 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 6.53063
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.44918E-004
148 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.61383E-003
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68341
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.59586E-003
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.61383E-003
155 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 6.53063
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 39426.22660
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.44918E-004
158 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 1126.67507
159 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
160 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.76070
161 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 5.76070
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.48171E-004
163 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.46429E-003
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68250
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.84827E-003
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.46429E-003
170 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.76070
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 39798.12925
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.48171E-004
173 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 1137.30017
174 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
175 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.03820
176 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.03820
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 6.02433E-005
178 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.25498E-004
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68264
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.68406E-003
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.25498E-004
185 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.03820
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6886.17659
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.02433E-005
188 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 196.78869
189 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
190 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.00782
191 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.00782
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 6.04115E-005
193 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.13667E-004
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68263
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.68969E-003
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.13667E-004
200 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.00782
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6905.40154
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.04115E-005
203 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 197.33793
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.50410
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.78911
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.79417
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.82821E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.32021E-004
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.79417
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
214 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15090.80323
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.32021E-004
217 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 364.60674
218 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
219 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.29930
220 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.29930
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.82491E-005
222 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.21853E-004
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68269
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.65924E-003
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.21853E-004
229 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.29930
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 2085.97937
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.82491E-005
232 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 59.60884
233 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
234 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.28953
235 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.28953
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.83053E-005
237 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.18045E-004
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68269
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.66458E-003
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.18045E-004
244 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.28953
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 2092.40863
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.83053E-005
247 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 59.79252
248 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
249 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.36832
250 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.36832
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 8.67114E-005
252 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 5.65971E-004
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68252
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.71872E-003
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.65971E-004
259 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.36832
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 9911.64573
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.67114E-005
262 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 283.23301
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.17637
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11612
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.14912
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52800
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.28105E-003
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.11376E-004
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.14912
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
273 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12730.97710
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.11376E-004
276 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 281.60773
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.28075
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11081
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.20424
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52800
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.43841E-003
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.15196E-004
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.20424
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
287 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13167.56468
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.15196E-004
290 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 290.82146
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.26954
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.23846E-002
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.19832
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52800
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.09847E-002
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.74275E-005
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.19832
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
301 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8850.44420
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.74275E-005
304 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 188.47129
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.77460
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.40542
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.40899
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.39760E-004
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.89871E-005
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.40899
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
315 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9028.70722
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.89871E-005
318 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 226.38194
319 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 11.66429
320 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 11.66429
321 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 22.09146
322 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 11.66429
323 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 21.96881
324 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 21.96881
325 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
326 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.53095
327 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
328 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
329 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
333 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
334 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
335 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 21.96881
336 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
337 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.96881
338 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 11.66146
339 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 11.66146
340 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 28.29868
341 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.98770
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.20376E-002
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 706034.17619
346 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.52179E-002
347 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 21.96881
348 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 218405.54126
349 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.91071E-003
350 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 3604.86608
351 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 21.96881
352 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 2.52179E-002
353 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 1.88830E-005
354 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.91071E-003
355 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
356 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
357 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
358 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 32.10000
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.93776
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.41196E-002
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 86334.70852
364 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.08368E-003
365 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
366 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 20393.41537
367 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.78410E-004
368 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 336.60104
369 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
370 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 3.08368E-003
371 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.54423E-004
372 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.78410E-004
373 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 3.59410E-002
374 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 7406.10776
375 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 4.29154E-003
376 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.51498
377 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 4.29154E-003
378 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 1292.42358
379 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
380 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 490549.45562
381 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 490549.46000
382 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 4.29154E-003
383 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 3.59410E-002
384 PlantLoop COOLSYS1 Plant Loop Volume [m3] 4.31292
385 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 3.59410E-002
386 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 5127.49819
387 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 3.59410E-002
388 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1006252.24764
389 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1006860.85000
390 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 114.78214
391 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
392 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
393 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
394 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
395 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 7050.63
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 4119.67
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1729.63
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 2615.15
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1501.07
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 11733.62
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 11964.56
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 31534.20
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 7459.11
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 7479.80
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 42464.95
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 42865.45
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 7417.00
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 7437.70
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 15156.30
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 2246.71
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 2253.64
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 10675.35
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 12792.28
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 13231.07
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 8895.25
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 9066.39
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 154769.05
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 14451.42


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 19136.07 15414.87 3721.20 0.81 2144.51 21.75
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 18567.10 14951.35 3615.75 0.81 2080.53 21.10
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 108303.29 87656.57 20646.72 0.81 12155.23 123.29
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 99728.81 79418.93 20309.88 0.80 11140.13 112.99
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 17485.21 14069.33 3415.88 0.80 1958.84 19.87
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 16990.04 13665.88 3324.16 0.80 1903.16 19.30
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 5019.06 4045.12 973.93 0.81 562.56 5.71
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 4859.75 3915.35 944.40 0.81 544.64 5.52
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 23182.44 18611.74 4570.70 0.80 2595.36 26.32
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 639749.20 426343.79 213405.41 0.67 75479.46 765.55
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 63544.84 41523.88 22020.96 0.65 7288.25 73.92


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 3.93 13.40


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.419 0.394   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.419 0.394   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.419 0.394   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.419 0.394   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.198 1.198   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.107 0.950   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.107 0.950   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.107 0.950   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.107 0.950   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.107 0.950   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.107 0.950   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.107 0.950   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.107 0.950   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.107 0.950   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.107 0.950   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.217 1.029   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.217 1.029   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.217 1.029   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.217 1.029   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.174 0.999   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.174 0.999   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.174 0.999   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.174 0.999   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.174 0.999   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.286 1.078   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.286 1.078   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.286 1.078   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.286 1.078   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.286 1.078   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.286 1.078   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.286 1.078   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.286 1.078   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.8409640912E-002 2.2691035847E-002 Pass Pass 3.1324036862E-003 7.3786200161E-003 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 8.4863837027E-003 2.4393785013E-002 Pass Pass 0.2765834562 1.4373182880 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 5.9363975531E-003 1.4862572296E-002 Pass Pass 3.0109355795E-002 6.4334203665E-002 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 5.8304774838E-004 4.4176458791E-004 Pass Pass 9.2348667478E-002 0.2094307715 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 5.2057468753E-004 4.1041634330E-004 Pass Pass 2.3207899507E-002 3.3198148942E-002 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 7.8140841725E-002 0.2280562792 Pass Pass 1.9421927407E-002 5.1722191879E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 3.6906940804E-002 8.0008112813E-002 Pass Pass 5.2316182814E-002 0.1008342073 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 2.9814174962E-002 4.1950745281E-002 Pass Pass 1.8886665374E-002 4.0015751356E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 9.5831681791E-002 0.3290211173 Pass Pass 0.3492258996 1.4218093591 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 9.2661594706E-002 0.3426967519 Pass Pass 0.1130947555 0.3297190520 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 2.8322939971E-002 4.9839203132E-002 Pass Pass 0.2383904674 0.8951027667 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 6.9670783595E-002 0.2181016067 Pass Pass 0.2555529857 1.6051438202 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 7.9828711517E-002 0.2792653374 Pass Pass 4.2134981320 47.4848546204 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 8.6858960480E-002 0.3126008231 Pass Pass 0.2585267455 1.1515236594 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 4.2564719632E-004 3.3352551622E-004 Pass Pass 0.4301483826 1.8750295763 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 9.2660941401E-002 0.3495662724 Pass Pass 0.1767333555 0.7925694993 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 9.2665602114E-002 0.3598680058 Pass Pass 0.1192853048 0.4470646557 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 8.1632337414E-002 0.2406659481 Pass Pass 0.2226694490 0.8572105047 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 5.4039627495E-002 9.7142904995E-002 Pass Pass 8.2502347555E-003 1.9334748276E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 4.8576603835E-002 8.6135766502E-002 Pass Pass 8.3091290631E-003 1.9848598625E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 3.6908375663E-002 0.1184031384 Pass Pass 2.2386848780E-002 4.0263245156E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 8.4501530631E-004 6.2267910039E-004 Pass Pass 0.2268129804 1.0082150535 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 4411.28 100.10 1292.28 5392.19 5625.83 16821.67



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB -10.70 0.00 -10.70 Wetbulb [C] 7.50 320.00
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 32.10 7.40 23.10 Wetbulb [C] 5.60 230.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 172.00 59      
Feb 49.00 37      
Mar 40.00 38      
Apr 70.00 48      
May 70.00 36      
Jun 25.00 15      
Jul 64.00 20      
Aug 2.00 4      
Sep 73.00 32      
Oct 7.00 8      
Nov 88.00 34      
Dec 62.00 39      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.399 0.419 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.399 0.419 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.399 0.419 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.812 0.924 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.812 0.924 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.23 0.182 0.186 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.812 0.924 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.812 0.924 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.812 0.924 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.812 0.924 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.812 0.924 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.812 0.924 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.812 0.924 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.23 0.182 0.186 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 0.812 0.924 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 0.812 0.924 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 0.812 0.924 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 0.812 0.924 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.23 0.182 0.186 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.950 1.107 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.950 1.107 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.950 1.107 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.950 1.107 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.950 1.107 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.950 1.107 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.950 1.107 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.950 1.107 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.950 1.107 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.950 1.107 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 1.029 1.217 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 1.029 1.217 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 1.029 1.217 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 1.029 1.217 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.999 1.174 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.999 1.174 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 0.999 1.174 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.999 1.174 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.999 1.174 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.078 1.286 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.078 1.286 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.078 1.286 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.078 1.286 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 1.078 1.286 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 1.078 1.286 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 1.078 1.286 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 1.078 1.286 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.23 0.182 0.186 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.23 0.182 0.186 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.186 0.196 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.186 0.196 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.186 0.196 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.186 0.196 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.186 0.196 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.186 0.196 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.186 0.196 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.186 0.196 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.186 0.196 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.186 0.196 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.185 0.196 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.185 0.196 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.185 0.196 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.188 0.196 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   23.26 0.00 0.00 23.26 23.26 2.191 0.401 0.402             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   65.50 0.00 0.00 65.50 65.50 2.191 0.401 0.402             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   85.08 0.00 0.00 85.08 85.08 2.191 0.401 0.402             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.191 0.401 0.402             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.191 0.401 0.402             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.191 0.401 0.402             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.191 0.401 0.402             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   3.68 0.00 0.00 3.68 279.56 2.191 0.401 0.402             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   3.68 0.00 0.00 3.68 279.65 2.191 0.401 0.402             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.191 0.401 0.402             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.191 0.401 0.402             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.191 0.401 0.402             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.191 0.401 0.402             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   5.82 0.00 0.00 5.82 23.30 2.191 0.401 0.402             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   2.15 0.00 0.00 2.15 8.59 2.191 0.401 0.402             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   2.15 0.00 0.00 2.15 8.58 2.191 0.401 0.402             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   5.82 0.00 0.00 5.82 23.30 2.191 0.401 0.402             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.191 0.401 0.402             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 8.58 2.191 0.401 0.402             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.191 0.401 0.402             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 8.58 2.191 0.401 0.402             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   6.74 0.00 0.00 6.74 60.70 2.191 0.401 0.402             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   32.19 0.00 0.00 32.19 32.19 2.191 0.401 0.402             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   32.19 0.00 0.00 32.19 32.19 2.191 0.401 0.402             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.191 0.401 0.402             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   17.17 0.00 0.00 17.17 17.17 2.191 0.401 0.402             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.191 0.401 0.402             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   5.82 0.00 0.00 5.82 5.82 2.191 0.401 0.402             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   5.21 0.00 0.00 5.21 5.21 2.191 0.401 0.402             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   17.17 0.00 0.00 17.17 17.17 2.191 0.401 0.402             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.191 0.401 0.402                      
North Total or Average             432.95 2.191 0.401 0.402                      
Non-North Total or Average             780.84 2.191 0.401 0.402                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.016 1.198 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 9.1389 1978.83 18084.33 LightsWired LTG_SCH_BASEMENT 51.16 168.00 51.10 0.0000 Y 173.46
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 13.3365 67.07 894.50 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 8.61
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 13.3365 77.67 1035.83 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 9.97
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 9.2031 164.24 1511.55 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 16.63
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 6.1031 94.76 578.33 LightsWired LTG_SCH_STORAGE 25.68 168.00 25.65 0.0000 Y 2.78
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.8125 78.04 453.60 LightsWired LTG_SCH_LAUNDRY 51.36 168.00 51.30 0.0000 Y 4.37
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 10.3656 188.86 1957.67 LightsWired LTG_SCH_DINING 58.69 168.00 48.78 0.0000 Y 17.93
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 8.7188 1308.19 11405.76 LightsWired LTG_SCH_LOBBY 58.69 168.00 56.92 0.0000 Y 121.86
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 4.5531 156.09 710.69 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 4.5531 156.07 710.61 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 4.5531 1863.81 8486.17 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 76.02
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 4.5531 1864.32 8488.49 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 76.04
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 4.5531 156.09 710.69 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 4.5531 156.07 710.61 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 6.3938 1557.62 9959.03 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 109.60
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 4.5531 39.02 177.67 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.59
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 4.5531 39.02 177.65 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.59
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 4.5531 220.77 1005.22 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 9.00
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 10.3656 331.66 3437.84 LightsWired LTG_SCH_DINING 58.69 168.00 53.67 0.0000 Y 34.63
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 10.3656 331.66 3437.84 LightsWired LTG_SCH_DINING 58.69 168.00 53.67 0.0000 Y 34.63
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 11.7219 103.30 1210.92 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 13.33
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 6.3938 412.12 2635.02 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 29.00
Interior Lighting Total       6.8557 11345.29 77780.02               507.17


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.07 11405.76 798.40
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.00 11405.76 0.00
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.39 1957.67 763.49
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.00 1957.67 0.00
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3437.84 687.57
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.00 3437.84 0.00
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3437.84 687.57
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.00 3437.84 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 15448.40 AstronomicalClock -   83.64 83.64 242.55
Exterior Lighting Total 15448.40           242.55



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 490549.46 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 1006860.85 2.96 1007037.83 2.96 3.93 13.40


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 13017.00 19136.07 15414.87 3721.20 0.81 - 2144.51 21.75
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12636.23 18567.10 14951.35 3615.75 0.81 - 2080.53 21.10
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 73181.76 108303.29 87656.57 20646.72 0.81 - 12155.23 123.29
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 68994.93 99728.81 79418.93 20309.88 0.80 - 11140.13 112.99
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11913.04 17485.21 14069.33 3415.88 0.80 - 1958.84 19.87
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11581.78 16990.04 13665.88 3324.16 0.80 - 1903.16 19.30
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3411.64 5019.06 4045.12 973.93 0.81 - 562.56 5.71
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3305.01 4859.75 3915.35 944.40 0.81 - 544.64 5.52
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 15845.97 23182.44 18611.74 4570.70 0.80 - 2595.36 26.32
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 706034.18 639749.20 426343.79 213405.41 0.67 - 75479.46 765.55
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 86334.71 63544.84 41523.88 22020.96 0.65 - 7288.25 73.92
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 7014.41 7050.63 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 4102.09 4119.67 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1721.57 1729.63 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2604.15 2615.15 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1495.16 1501.07 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 11674.17 11733.62 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 11909.29 11964.56 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 31385.41 31534.20 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 6925.28 7459.11 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 6944.49 7479.80 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 39426.23 42464.95 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 39798.13 42865.45 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 6886.18 7417.00 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 6905.40 7437.70 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 15090.80 15156.30 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 2085.98 2246.71 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 2092.41 2253.64 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 9911.65 10675.35 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 12730.98 12792.28 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 13167.56 13231.07 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 8850.44 8895.25 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 9028.71 9066.39 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 218405.54 154769.05 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 20393.42 14451.42 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.14 801.85 703.64 1.00 1.17 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.10 777.29 703.64 1.00 1.17 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 6.53 4595.19 703.64 1.00 0.95 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 5.76 4053.44 703.64 1.00 0.96 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.04 730.51 703.64 1.00 1.19 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.01 709.14 703.64 1.00 1.19 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.30 210.60 703.64 1.00 1.71 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.29 203.72 703.64 1.00 1.74 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.37 962.80 703.64 1.00 1.13 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 21.97 49224.16 2240.64 1.00 1.11 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.035941 7406.11 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.004292 1292.42 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.035941 5127.50 142664.32 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.80 0.58 0.51
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.80 0.26 0.03



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 34629.44 34629.44 17.50 2.517 2.517 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 24.00 24.00 0.00920 28.94 0.01411 0.854 0.00
RETAIL_1_FLR_1 5343.95 5343.95 79.68 0.389 0.389 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 24.00 24.00 0.00908 31.79 0.01412 0.079 0.00
RETAIL_2_FLR_1 3305.70 3305.70 42.56 0.240 0.240 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 24.00 24.00 0.00943 31.73 0.01412 0.092 0.00
MECH_FLR_1 3212.85 3212.85 19.56 0.234 0.234 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 24.00 24.00 0.00888 31.46 0.01412 0.000 0.00
STORAGE_FLR_1 1557.05 1557.05 16.43 0.113 0.113 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 24.00 0.00902 32.03 0.01412 0.058 0.00
LAUNDRY_FLR_1 44902.36 44902.36 575.38 3.264 3.264 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 24.00 0.00856 32.10 0.01412 0.000 0.00
CAFE_FLR_1 21548.00 21548.00 114.09 1.568 1.568 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 24.00 23.99 0.01004 31.79 0.01412 0.676 0.00
LOBBY_FLR_1 65473.02 65473.02 50.05 4.761 4.761 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 24.00 23.99 0.01001 31.85 0.01412 1.894 0.00
ROOM_1_FLR_3 11633.22 11633.22 298.12 1.140 1.140 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 21.11 21.11 0.00867 31.36 0.01412 0.062 0.00
ROOM_2_FLR_3 11276.97 11276.97 289.02 1.105 1.105 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 21.11 21.11 0.00867 31.26 0.01412 0.062 0.00
ROOM_3_MULT19_FLR_3 66672.55 66672.55 2718.68 6.531 6.531 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 21.11 21.11 0.00860 31.85 0.01412 0.837 0.00
ROOM_4_MULT19_FLR_3 58807.60 58807.60 2397.32 5.761 5.761 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 21.11 21.11 0.00885 32.10 0.01412 0.837 0.00
ROOM_5_FLR_3 10598.29 10598.29 271.60 1.038 1.038 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 21.11 21.11 0.00868 28.87 0.01411 0.062 0.00
ROOM_6_FLR_3 10288.16 10288.16 263.68 1.008 1.008 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 21.11 21.11 0.00869 28.45 0.01411 0.062 0.00
CORRIDOR_FLR_3 20691.81 20691.81 53.14 1.504 1.504 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 24.00 24.00 0.00950 32.10 0.01412 0.475 0.00
ROOM_1_FLR_6 3055.33 3055.33 78.30 0.299 0.299 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 21.11 21.11 0.00866 31.36 0.01412 0.015 0.00
ROOM_2_FLR_6 2955.60 2955.60 75.75 0.290 0.290 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 21.11 21.11 0.00866 31.26 0.01412 0.015 0.00
ROOM_3_MULT9_FLR_6 13968.14 13968.14 569.42 1.368 1.368 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 21.11 21.11 0.00872 31.85 0.01412 0.099 0.00
BANQUET_FLR_6 29903.24 29903.24 90.16 2.176 2.176 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 24.00 23.98 0.01041 32.10 0.01412 1.188 0.00
DINING_FLR_6 31337.93 31337.93 94.49 2.281 2.281 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 24.00 23.99 0.01032 32.10 0.01412 1.188 0.00
KITCHEN_FLR_6 31140.21 31140.21 301.44 2.270 2.270 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 24.00 23.97 0.01008 31.43 0.01412 0.367 0.00
CORRIDOR_FLR_6 10656.07 10656.07 25.86 0.775 0.775 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 24.00 24.00 0.00905 31.98 0.01412 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 0.854 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.58 0.00150 -10.70 0.00150 0.854 0.00
RETAIL_1_FLR_1 3020.75 3020.75 45.04 0.130 0.130 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00749 -10.70 0.00150 0.079 0.00
RETAIL_2_FLR_1 1052.63 1052.63 13.55 0.045 0.092 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00745 -10.70 0.00150 0.092 0.00
MECH_FLR_1 1954.31 1954.31 11.90 0.084 0.084 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00731 -10.70 0.00150 0.000 0.00
STORAGE_FLR_1 1180.21 1180.21 12.45 0.051 0.058 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00734 -10.70 0.00150 0.058 0.00
LAUNDRY_FLR_1 2592.62 2592.62 33.22 0.111 0.111 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00729 -10.70 0.00150 0.000 0.00
CAFE_FLR_1 7544.97 7544.97 39.95 0.324 0.676 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00755 -10.70 0.00150 0.676 0.00
LOBBY_FLR_1 18132.10 18132.10 13.86 0.778 1.894 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00747 -10.70 0.00150 1.894 0.00
ROOM_1_FLR_3 6925.55 6925.55 177.48 0.299 0.299 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00749 -10.70 0.00150 0.062 0.00
ROOM_2_FLR_3 6944.76 6944.76 177.99 0.300 0.300 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00749 -10.70 0.00150 0.062 0.00
ROOM_3_MULT19_FLR_3 39426.75 39426.75 1607.69 1.701 1.701 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.11 21.11 0.00752 -10.70 0.00150 0.837 0.00
ROOM_4_MULT19_FLR_3 39798.66 39798.66 1622.41 1.717 1.717 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.11 21.11 0.00753 -10.70 0.00150 0.837 0.00
ROOM_5_FLR_3 6886.44 6886.44 176.48 0.297 0.297 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00749 -10.70 0.00150 0.062 0.00
ROOM_6_FLR_3 6905.67 6905.67 176.99 0.298 0.298 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00749 -10.70 0.00150 0.062 0.00
CORRIDOR_FLR_3 10902.84 10902.84 28.00 0.468 0.475 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00760 -10.70 0.00150 0.475 0.00
ROOM_1_FLR_6 2086.06 2086.06 53.46 0.090 0.090 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00757 -10.70 0.00150 0.015 0.00
ROOM_2_FLR_6 2092.49 2092.49 53.63 0.090 0.090 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00757 -10.70 0.00150 0.015 0.00
ROOM_3_MULT9_FLR_6 9911.94 9911.94 404.07 0.428 0.428 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00758 -10.70 0.00150 0.099 0.00
BANQUET_FLR_6 6670.79 6670.79 20.11 0.286 1.188 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00767 -10.70 0.00150 1.188 0.00
DINING_FLR_6 6816.64 6816.64 20.55 0.292 1.188 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00767 -10.70 0.00150 1.188 0.00
KITCHEN_FLR_6 2545.68 2545.68 24.64 0.109 0.367 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 21.00 21.00 0.00673 -10.70 0.00150 0.367 0.00
CORRIDOR_FLR_6 6871.56 6871.56 16.67 0.295 0.295 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00771 -10.70 0.00150 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 21.97 21.97 7.41 7.41 21.9688 11.6643 21.9688 0.5309 0.3000
FLR_3_DOAS 17.43 2.05 5.22 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 7014.406 7014.406 1.329122 0.00006137 146.273 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 7014.41 7014.41 1.329122 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00800000 51.6928 0.00 0.00 7053.83 7053.83
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 4102.092 4102.092 0.205138 0.00003589 100.287 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 4102.09 4102.09 0.205138 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00749491 48.4711 3020.75 0.00 4123.39 4123.39
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1721.569 1721.569 0.126894 0.00001506 39.112 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 1721.57 1721.57 0.126894 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00744508 48.1507 1052.63 0.00 1730.84 1730.84
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 2604.154 2604.154 0.123304 0.00002278 64.535 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 2604.15 2604.15 0.123304 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00730966 47.2852 1954.31 0.00 2617.61 2617.61
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1495.163 1495.163 0.059757 0.00001308 38.907 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 1495.16 1495.16 0.059757 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00733734 47.4622 1180.21 0.00 1502.68 1502.68
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 11674.169 11674.169 1.723482 0.00010213 247.080 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 11674.17 11674.17 1.723482 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00729176 47.1727 2592.62 0.00 11739.44 11739.44
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 11909.289 11909.289 0.827817 0.00010419 273.007 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 11909.29 11909.29 0.827817 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00754895 48.8158 7544.97 0.00 11973.24 11973.24
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 31385.415 31385.415 2.513950 0.00027457 704.718 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 31385.41 31385.41 2.513950 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00747062 48.3139 18132.10 0.00 31555.21 31555.21
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 13017.001 -999.000 1.139574 0.00046493 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 unknown 7/21 16:30:00 13017.00 12501.80 1.139574 21.68 15.70 0.00866703 12.80 12.09 0.00850000 31.36 0.01411830 22.93 0.0000 21.11 0.00866703 55.5666 11633.22 0.00 13038.53 12331.29
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 6925.284 6925.284 0.298714 0.00006059 197.906 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 6925.28 6925.28 0.298714 21.11 14.42 0.00749178 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00749178 48.1206 6925.55 0.00 7465.62 7465.62
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 12636.230 -999.000 1.104677 0.00045133 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown 7/21 16:40:00 12636.23 12120.92 1.104677 21.68 15.70 0.00867231 12.80 12.09 0.00850000 31.26 0.01411813 22.90 0.0000 21.11 0.00867231 55.6000 11276.97 0.00 12657.09 11956.47
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 6944.493 6944.493 0.299542 0.00006075 198.455 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 6944.49 6944.49 0.299542 21.11 14.42 0.00749311 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00749311 48.1291 6944.76 0.00 7486.33 7486.33
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 73181.758 -999.000 6.530630 0.00261383 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 unknown 7/21 13:20:00 73181.76 71490.99 6.530630 21.68 15.63 0.00859586 12.80 12.09 0.00850000 31.85 0.01411920 23.06 0.0000 21.11 0.00859586 55.1143 66672.55 0.00 73305.31 70446.21
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 39426.227 39426.227 1.700612 0.00034492 1126.675 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 39426.23 39426.23 1.700612 21.11 14.45 0.00752418 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00752418 48.3260 39426.75 0.00 42502.48 42502.48
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 68994.926 -999.000 5.760697 0.00246429 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 unknown 7/21 15:00:00 68994.93 63535.34 5.760697 21.68 15.85 0.00884827 12.80 12.09 0.00850000 32.10 0.01411964 23.13 0.0000 21.11 0.00884827 56.7122 58807.60 0.00 69103.54 62817.72
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 39798.129 39798.129 1.716653 0.00034817 1137.300 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 39798.13 39798.13 1.716653 21.11 14.45 0.00752818 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00752818 48.3514 39798.66 0.00 42903.40 42903.40
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 11913.040 -999.000 1.038197 0.00042550 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 unknown 7/21 09:40:00 11913.04 11395.54 1.038197 21.68 15.71 0.00868406 12.80 12.09 0.00850000 28.87 0.01411382 22.22 0.0000 21.11 0.00868406 55.6743 10598.29 0.00 11932.64 11242.73
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 6886.177 6886.177 0.297027 0.00006024 196.789 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 6886.18 6886.18 0.297027 21.11 14.42 0.00748912 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00748912 48.1038 6886.44 0.00 7423.46 7423.46
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 11581.782 -999.000 1.007817 0.00041367 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 unknown 7/21 09:20:00 11581.78 11063.97 1.007817 21.68 15.72 0.00868969 12.80 12.09 0.00850000 28.45 0.01411307 22.10 0.0000 21.11 0.00868969 55.7099 10288.16 0.00 11600.81 10916.44
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 6905.402 6905.402 0.297856 0.00006041 197.338 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 6905.40 6905.40 0.297856 21.11 14.42 0.00749046 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00749046 48.1123 6905.67 0.00 7444.19 7444.19
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 15090.803 15090.803 0.794166 0.00013202 364.607 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 15090.80 15090.80 0.794166 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00760020 49.1412 10902.84 0.00 15169.51 15169.51
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 3411.637 -999.000 0.299295 0.00012185 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 unknown 7/21 16:30:00 3411.64 3282.66 0.299295 21.68 15.69 0.00865924 12.80 12.09 0.00850000 31.36 0.01411830 22.93 0.0000 21.11 0.00865924 55.5173 3055.33 0.00 3417.29 3237.55
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 2085.979 2085.979 0.089976 0.00001825 59.609 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 2085.98 2085.98 0.089976 21.11 14.50 0.00757241 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00757241 48.6324 2086.06 0.00 2248.74 2248.74
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 3305.010 -999.000 0.289526 0.00011805 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown 7/21 16:40:00 3305.01 3176.04 0.289526 21.68 15.69 0.00866458 12.80 12.09 0.00850000 31.26 0.01411813 22.90 0.0000 21.11 0.00866458 55.5511 2955.60 0.00 3310.48 3132.62
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2092.409 2092.409 0.090254 0.00001831 59.793 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 2092.41 2092.41 0.090254 21.11 14.50 0.00757367 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00757367 48.6404 2092.49 0.00 2255.67 2255.67
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 15845.974 -999.000 1.368317 0.00056597 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 unknown 7/21 13:20:00 15845.97 15034.61 1.368317 21.68 15.74 0.00871872 12.80 12.09 0.00850000 31.85 0.01411920 23.06 0.0000 21.11 0.00871872 55.8938 13968.14 0.00 15871.80 14839.91
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 9911.646 9911.646 0.427530 0.00008671 283.233 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 9911.65 9911.65 0.427530 21.11 14.51 0.00758478 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00758478 48.7104 9911.94 0.00 10685.01 10685.01
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 12730.977 12730.977 1.149122 0.00011138 281.608 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 12730.98 12730.98 1.149122 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00766649 49.5653 6670.79 0.00 12800.26 12800.26
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 13167.565 13167.565 1.204237 0.00011520 290.821 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 13167.56 13167.56 1.204237 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00767327 49.6086 6816.64 0.00 13239.27 13239.27
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 8850.444 8850.444 1.198317 0.00007743 188.471 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 8850.44 8850.44 1.198317 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00672999 43.5829 2545.68 0.00 8899.83 8899.83
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 9028.707 9028.707 0.408987 0.00007899 226.382 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 9028.71 9028.71 0.408987 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00771413 49.8691 6871.56 0.00 9075.21 9075.21
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 706034.176 -999.000 21.968809 0.02521790 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 706034.18 461536.13 21.968809 28.30 20.59 0.01203759 10.99 10.99 0.00850000 32.10 0.01411964 23.13 53.0819 23.99 0.00964747 51.8377 301721.33 0.00 706838.37 456317.62
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 218405.541 218405.541 6.590643 0.00191071 3604.866 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 218405.54 218405.54 6.590643 -10.70 -10.70 0.00150390 16.70 13.18 0.00800000 -10.70 0.00150390 -10.70 176.9396 21.11 0.00651826 41.9440 68907.78 0.00 187135.77 187135.77
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 86334.709 -999.000 2.051317 0.00308368 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 86334.71 51162.86 2.051317 32.10 23.13 0.01411964 11.94 11.74 0.00850000 32.10 0.01411964 23.13 99.9965 21.11 0.00871743 55.8841 177906.93 0.00 86433.83 51479.65
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 20393.415 20393.415 0.615395 0.00017841 336.601 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 20393.42 20393.42 0.615395 -10.70 -10.70 0.00150390 16.70 13.18 0.00800000 -10.70 0.00150390 -10.70 333.3216 21.11 0.00752643 48.3395 120977.96 0.00 17473.63 17473.63



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 7014.406 7014.406 1.329122 0.00006137 146.273 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 1.4017 1.429908 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 7014.41 7014.41 1.0000 1.59972403 1.329122 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.06135882 60.00 32.22 27.78 0.000 7014.41 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 51.6928 0.00 0.00 7053.83 7053.83 1.59972403 16.60 13.15 0.00800000 36934.7 20.92 14.82 0.00800000 41344.1
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 4102.092 4102.092 0.205138 0.00003589 100.287 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 0.8197 0.836224 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 4102.09 4102.09 1.0000 0.24690267 0.205138 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.03588323 60.00 32.22 27.78 0.000 4102.09 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00749491 21.00 0.00749491 48.4711 3020.75 0.00 4123.39 4123.39 0.24690267 16.60 13.15 0.00800000 36934.7 32.98 19.01 0.00800000 53635.2
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1721.569 1721.569 0.126894 0.00001506 39.112 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 0.3440 0.350947 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 1721.57 1721.57 1.0000 0.15272844 0.126894 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.01505950 60.00 32.22 27.78 0.000 1721.57 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00744508 21.00 0.00744508 48.1507 1052.63 0.00 1730.84 1730.84 0.15272844 16.60 13.15 0.00800000 36934.7 27.71 17.26 0.00800000 48267.5
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 2604.154 2604.154 0.123304 0.00002278 64.535 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 0.5204 0.530865 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 2604.15 2604.15 1.0000 0.14840763 0.123304 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.02277995 60.00 32.22 27.78 0.000 2604.15 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00730966 21.00 0.00730966 47.2852 1954.31 0.00 2617.61 2617.61 0.14840763 16.60 13.15 0.00800000 36934.7 33.90 19.31 0.00800000 54572.7
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1495.163 1495.163 0.059757 0.00001308 38.907 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 0.2988 0.304794 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 1495.16 1495.16 1.0000 0.07192375 0.059757 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.01307901 60.00 32.22 27.78 0.000 1495.16 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00733734 21.00 0.00733734 47.4622 1180.21 0.00 1502.68 1502.68 0.07192375 16.60 13.15 0.00800000 36934.7 37.09 20.31 0.00800000 57827.5
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 11674.169 11674.169 1.723482 0.00010213 247.080 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 2.3329 2.379815 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 11674.17 11674.17 1.0000 2.07437451 1.723482 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.10212030 60.00 32.22 27.78 0.000 11674.17 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00729176 21.00 0.00729176 47.1727 2592.62 0.00 11739.44 11739.44 2.07437451 16.60 13.15 0.00800000 36934.7 22.15 15.28 0.00800000 42594.0
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 11909.289 11909.289 0.827817 0.00010419 273.007 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 2.3798 2.427745 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 11909.29 11909.29 1.0000 0.99635667 0.827817 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.10417703 60.00 32.22 27.78 0.000 11909.29 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00754895 21.00 0.00754895 48.8158 7544.97 0.00 11973.24 11973.24 0.99635667 16.60 13.15 0.00800000 36934.7 28.38 17.49 0.00800000 48951.8
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 31385.415 31385.415 2.513950 0.00027457 704.718 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 6.2718 6.398012 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 31385.41 31385.41 1.0000 3.02577785 2.513950 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.27454529 60.00 32.22 27.78 0.000 31385.41 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00747062 21.00 0.00747062 48.3139 18132.10 0.00 31555.21 31555.21 3.02577785 16.60 13.15 0.00800000 36934.7 26.83 16.96 0.00800000 47363.5
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 13017.001 -999.000 1.139574 0.00046493 -999.000 -999.0000 1.00000 1.00000 1020.9516 1004.8586 1.2036 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.139574 1.37158554   4197.9300 999.8980 35.93733243 13.37 6.70 6.67 1006252.25 1.2936 1.293588 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 unknown unknown unknown 7/21 16:30:00 Sensible 13017.00 12501.80 1.0000 1.37158554 1.139574 21.68 15.70 0.00866703 43812.7 12.80 12.09 0.00850000 34322.2 0.46488102 6.70 13.37 6.67 0.000 13017.00 31.36 0.01411830 22.93 0.00000000 0.0000 21.11 0.00866703 21.11 0.00866703 55.5666 11633.22 0.00 13038.53 12331.29 1.37158554 21.68 15.70 0.00866703 43812.7 12.88 12.09 0.00846281 34306.5
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 6925.284 6925.284 0.298714 0.00006059 197.906 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.139574 1.37158554   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 1.3839 1.411740 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 6925.28 6925.28 1.0000 0.35953050 0.298714 21.11 14.42 0.00749178 40243.0 40.00 21.18 0.00800000 60796.0 0.06057923 60.00 32.22 27.78 0.000 6925.28 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00749178 21.11 0.00749178 48.1206 6925.55 0.00 7465.62 7465.62 0.35953050 16.60 12.65 0.00749178 35648.0 36.98 19.89 0.00749178 56412.9
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 12636.230 -999.000 1.104677 0.00045133 -999.000 -999.0000 1.00000 1.00000 1020.9614 1004.8586 1.2036 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.104677 1.32958387   4197.9300 999.8980 35.93733243 13.37 6.70 6.67 1006252.25 1.2558 1.255748 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown unknown unknown 7/21 16:40:00 Sensible 12636.23 12120.92 1.0000 1.32958387 1.104677 21.68 15.70 0.00867231 43826.1 12.80 12.09 0.00850000 34322.2 0.45128238 6.70 13.37 6.67 0.000 12636.23 31.26 0.01411813 22.90 0.00000000 0.0000 21.11 0.00867231 21.11 0.00867231 55.6000 11276.97 0.00 12657.09 11956.47 1.32958387 21.68 15.71 0.00867231 43826.1 12.87 12.09 0.00846361 34306.5
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 6944.493 6944.493 0.299542 0.00006075 198.455 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.104677 1.32958387   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 1.3877 1.415656 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 6944.49 6944.49 1.0000 0.36052772 0.299542 21.11 14.42 0.00749311 40246.4 40.00 21.18 0.00800000 60796.0 0.06074726 60.00 32.22 27.78 0.000 6944.49 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00749311 21.11 0.00749311 48.1291 6944.76 0.00 7486.33 7486.33 0.36052772 16.60 12.66 0.00749311 35651.4 36.98 19.89 0.00749311 56416.3
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 73181.758 -999.000 6.530630 0.00261383 -999.000 -999.0000 1.00000 1.00000 1020.8193 1004.8586 1.2036 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.530630 7.86023347   4197.9300 999.8980 35.93733243 13.37 6.70 6.67 1006252.25 7.2727 7.272569 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 unknown unknown unknown 7/21 13:20:00 Sensible 73181.76 71490.99 1.0000 7.86023347 6.530630 21.68 15.63 0.00859586 43632.6 12.80 12.09 0.00850000 34322.2 2.61356740 6.70 13.37 6.67 0.000 73181.76 31.85 0.01411920 23.06 0.00000000 0.0000 21.11 0.00859586 21.11 0.00859586 55.1143 66672.55 0.00 73305.31 70446.21 7.86023347 21.68 15.64 0.00859586 43632.6 12.90 12.09 0.00845180 34306.5
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 39426.227 39426.227 1.700612 0.00034492 1126.675 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.530630 7.86023347   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 7.8786 8.037156 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 39426.23 39426.23 1.0000 2.04684781 1.700612 21.11 14.45 0.00752418 40325.4 40.00 21.18 0.00800000 60796.0 0.34488264 60.00 32.22 27.78 0.000 39426.23 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00752418 21.11 0.00752418 48.3260 39426.75 0.00 42502.48 42502.48 2.04684781 16.60 12.69 0.00752418 35730.0 36.98 19.91 0.00752418 56494.9
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 68994.926 -999.000 5.760697 0.00246429 -999.000 -999.0000 1.00000 1.00000 1021.2885 1004.8586 1.2036 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.760697 6.93354637   4197.9300 999.8980 35.93733243 13.37 6.70 6.67 1006252.25 6.8566 6.856495 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 unknown unknown unknown 7/21 15:00:00 Sensible 68994.93 63535.34 1.0000 6.93354637 5.760697 21.68 15.85 0.00884827 44273.1 12.80 12.09 0.00850000 34322.2 2.46404148 6.70 13.37 6.67 0.000 68994.93 32.10 0.01411964 23.13 0.00000000 0.0000 21.11 0.00884827 21.11 0.00884827 56.7122 58807.60 0.00 69103.54 62817.72 6.93354637 21.68 15.86 0.00884827 44273.1 12.81 12.09 0.00848919 34306.5
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 39798.129 39798.129 1.716653 0.00034817 1137.300 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.760697 6.93354637   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 7.9529 8.112970 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 39798.13 39798.13 1.0000 2.06615547 1.716653 21.11 14.45 0.00752818 40335.6 40.00 21.18 0.00800000 60796.0 0.34813588 60.00 32.22 27.78 0.000 39798.13 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00752818 21.11 0.00752818 48.3514 39798.66 0.00 42903.40 42903.40 2.06615547 16.60 12.69 0.00752818 35740.2 36.98 19.92 0.00752818 56505.0
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 11913.040 -999.000 1.038197 0.00042550 -999.000 -999.0000 1.00000 1.00000 1020.9832 1004.8586 1.2036 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.038197 1.24956820   4197.9300 999.8980 35.93733243 13.37 6.70 6.67 1006252.25 1.1839 1.183880 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 unknown unknown unknown 7/21 09:40:00 Sensible 11913.04 11395.54 1.0000 1.24956820 1.038197 21.68 15.71 0.00868406 43855.9 12.80 12.09 0.00850000 34322.2 0.42545482 6.70 13.37 6.67 0.000 11913.04 28.87 0.01411382 22.22 0.00000000 0.0000 21.11 0.00868406 21.11 0.00868406 55.6743 10598.29 0.00 11932.64 11242.73 1.24956820 21.68 15.72 0.00868406 43855.9 12.87 12.09 0.00846538 34306.5
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 6886.177 6886.177 0.297027 0.00006024 196.789 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.038197 1.24956820   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 1.3761 1.403768 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 6886.18 6886.18 1.0000 0.35750020 0.297027 21.11 14.42 0.00748912 40236.2 40.00 21.18 0.00800000 60796.0 0.06023713 60.00 32.22 27.78 0.000 6886.18 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00748912 21.11 0.00748912 48.1038 6886.44 0.00 7423.46 7423.46 0.35750020 16.60 12.65 0.00748912 35641.3 36.98 19.89 0.00748912 56406.2
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 11581.782 -999.000 1.007817 0.00041367 -999.000 -999.0000 1.00000 1.00000 1020.9937 1004.8586 1.2036 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.007817 1.21300331   4197.9300 999.8980 35.93733243 13.37 6.70 6.67 1006252.25 1.1510 1.150960 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 unknown unknown unknown 7/21 09:20:00 Sensible 11581.78 11063.97 1.0000 1.21300331 1.007817 21.68 15.72 0.00868969 43870.2 12.80 12.09 0.00850000 34322.2 0.41362448 6.70 13.37 6.67 0.000 11581.78 28.45 0.01411307 22.10 0.00000000 0.0000 21.11 0.00868969 21.11 0.00868969 55.7099 10288.16 0.00 11600.81 10916.44 1.21300331 21.68 15.72 0.00868969 43870.2 12.87 12.09 0.00846623 34306.5
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 6905.402 6905.402 0.297856 0.00006041 197.338 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.007817 1.21300331   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 1.3799 1.407687 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 6905.40 6905.40 1.0000 0.35849827 0.297856 21.11 14.42 0.00749046 40239.6 40.00 21.18 0.00800000 60796.0 0.06040530 60.00 32.22 27.78 0.000 6905.40 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00749046 21.11 0.00749046 48.1123 6905.67 0.00 7444.19 7444.19 0.35849827 16.60 12.65 0.00749046 35644.7 36.98 19.89 0.00749046 56409.6
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 15090.803 15090.803 0.794166 0.00013202 364.607 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 3.0156 3.076306 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 15090.80 15090.80 1.0000 0.95585458 0.794166 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.13200746 60.00 32.22 27.78 0.000 15090.80 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00760020 21.00 0.00760020 49.1412 10902.84 0.00 15169.51 15169.51 0.95585458 16.60 13.15 0.00800000 36934.7 32.16 18.75 0.00800000 52804.8
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 3411.637 -999.000 0.299295 0.00012185 -999.000 -999.0000 1.00000 1.00000 1020.9371 1004.8586 1.2036 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.299295 0.36023023   4197.9300 999.8980 35.93733243 13.37 6.70 6.67 1006252.25 0.3390 0.339038 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 unknown unknown unknown 7/21 16:30:00 Sensible 3411.64 3282.66 1.0000 0.36023023 0.299295 21.68 15.69 0.00865924 43792.9 12.80 12.09 0.00850000 34322.2 0.12184105 6.70 13.37 6.67 0.000 3411.64 31.36 0.01411830 22.93 0.00000000 0.0000 21.11 0.00865924 21.11 0.00865924 55.5173 3055.33 0.00 3417.29 3237.55 0.36023023 21.68 15.69 0.00865924 43792.9 12.88 12.09 0.00846162 34306.5
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 2085.979 2085.979 0.089976 0.00001825 59.609 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.299295 0.36023023   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 0.4168 0.425233 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 2085.98 2085.98 1.0000 0.10829493 0.089976 21.11 14.50 0.00757241 40447.8 40.00 21.18 0.00800000 60796.0 0.01824720 60.00 32.22 27.78 0.000 2085.98 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00757241 21.11 0.00757241 48.6324 2086.06 0.00 2248.74 2248.74 0.10829493 16.60 12.73 0.00757241 35852.2 36.98 19.95 0.00757241 56617.1
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 3305.010 -999.000 0.289526 0.00011805 -999.000 -999.0000 1.00000 1.00000 1020.9470 1004.8586 1.2036 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.289526 0.34847260   4197.9300 999.8980 35.93733243 13.37 6.70 6.67 1006252.25 0.3284 0.328441 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown unknown unknown 7/21 16:40:00 Sensible 3305.01 3176.04 1.0000 0.34847260 0.289526 21.68 15.69 0.00866458 43806.5 12.80 12.09 0.00850000 34322.2 0.11803305 6.70 13.37 6.67 0.000 3305.01 31.26 0.01411813 22.90 0.00000000 0.0000 21.11 0.00866458 21.11 0.00866458 55.5511 2955.60 0.00 3310.48 3132.62 0.34847260 21.68 15.70 0.00866458 43806.5 12.88 12.09 0.00846243 34306.5
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2092.409 2092.409 0.090254 0.00001831 59.793 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.289526 0.34847260   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 0.4181 0.426544 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 2092.41 2092.41 1.0000 0.10862871 0.090254 21.11 14.50 0.00757367 40451.0 40.00 21.18 0.00800000 60796.0 0.01830344 60.00 32.22 27.78 0.000 2092.41 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00757367 21.11 0.00757367 48.6404 2092.49 0.00 2255.67 2255.67 0.10862871 16.60 12.73 0.00757367 35855.4 36.98 19.95 0.00757367 56620.3
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 15845.974 -999.000 1.368317 0.00056597 -999.000 -999.0000 1.00000 1.00000 1021.0477 1004.8586 1.2036 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.368317 1.64690000   4197.9300 999.8980 35.93733243 13.37 6.70 6.67 1006252.25 1.5748 1.574722 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 unknown unknown unknown 7/21 13:20:00 Sensible 15845.97 15034.61 1.0000 1.64690000 1.368317 21.68 15.74 0.00871872 43943.9 12.80 12.09 0.00850000 34322.2 0.56591316 6.70 13.37 6.67 0.000 15845.97 31.85 0.01411920 23.06 0.00000000 0.0000 21.11 0.00871872 21.11 0.00871872 55.8938 13968.14 0.00 15871.80 14839.91 1.64690000 21.68 15.75 0.00871872 43943.9 12.86 12.09 0.00847057 34306.5
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 9911.646 9911.646 0.427530 0.00008671 283.233 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.368317 1.64690000   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 1.9807 2.020519 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 9911.65 9911.65 1.0000 0.51457278 0.427530 21.11 14.51 0.00758478 40479.3 40.00 21.18 0.00800000 60796.0 0.08670256 60.00 32.22 27.78 0.000 9911.65 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00758478 21.11 0.00758478 48.7104 9911.94 0.00 10685.01 10685.01 0.51457278 16.60 12.75 0.00758478 35883.5 36.98 19.96 0.00758478 56648.3
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 12730.977 12730.977 1.149122 0.00011138 281.608 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 2.5440 2.595248 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 12730.98 12730.98 1.0000 1.38307756 1.149122 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.11136478 60.00 32.22 27.78 0.000 12730.98 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00766649 21.00 0.00766649 49.5653 6670.79 0.00 12800.26 12800.26 1.38307756 16.60 13.15 0.00800000 36934.7 25.68 16.55 0.00800000 46189.6
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 13167.565 13167.565 1.204237 0.00011520 290.821 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 2.6313 2.684248 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 13167.56 13167.56 1.0000 1.44941302 1.204237 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.11518385 60.00 32.22 27.78 0.000 13167.56 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00767327 21.00 0.00767327 49.6086 6816.64 0.00 13239.27 13239.27 1.44941302 16.60 13.15 0.00800000 36934.7 25.56 16.51 0.00800000 46069.0
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 8850.444 8850.444 1.198317 0.00007743 188.471 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 1.7686 1.804190 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 Sensible 8850.44 8850.44 1.0000 1.44228774 1.198317 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.07741965 60.00 32.22 27.78 0.000 8850.44 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.60 0.00672999 21.00 0.00672999 43.5829 2545.68 0.00 8899.83 8899.83 1.44228774 16.60 13.15 0.00800000 36934.7 22.65 15.46 0.00800000 43105.4
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 9028.707 9028.707 0.408987 0.00007899 226.382 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 1.8042 1.840529 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 9028.71 9028.71 1.0000 0.49225458 0.408987 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.07897901 60.00 32.22 27.78 0.000 9028.71 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00771413 21.00 0.00771413 49.8691 6871.56 0.00 9075.21 9075.21 0.49225458 16.60 13.15 0.00800000 36934.7 34.68 19.56 0.00800000 55370.7
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 706034.176 -999.000 21.968809 0.02521790 -999.000 -999.0000 1.00000 1.00000 1027.2173 1004.8586 1.2036 VAV WITH REHEAT FAN Fan:VariableVolume 21.968809 26.44154855   4197.9300 999.8980 35.93733243 13.37 6.70 6.67 1006252.25 70.1647 70.164730 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 Sensible 706034.18 461536.13 1.0000 26.44154855 21.968809 28.30 20.59 0.01203759 59174.2 10.99 10.99 0.00850000 32472.5 25.21533240 6.70 13.37 6.67 49224.162 656810.01 32.10 0.01411964 23.13 11.66146000 53.0819 23.99 0.00967707 23.99 0.00964747 51.8377 301721.33 0.00 706838.37 456317.62 26.44154855 28.30 20.60 0.01203759 59174.2 11.50 11.33 0.00828132 32442.1
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 218405.541 218405.541 6.590643 0.00191071 3604.866 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 VAV WITH REHEAT FAN Fan:VariableVolume 21.968809 26.44154855   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 43.6443 44.522635 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 218405.54 218405.54 1.0000 7.93246457 6.590643 -10.70 -10.70 0.00150390 -7020.5 16.70 13.18 0.00800000 37036.7 1.91051204 60.00 32.22 27.78 0.000 218405.54 -10.70 0.00150390 -10.70 11.66146000 176.9396 18.56 0.00683037 21.11 0.00651826 41.9440 68907.78 0.00 187135.77 187135.77 7.93246457 2.80 -1.97 0.00150390 6582.5 26.21 10.51 0.00150390 30173.7
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 86334.709 -999.000 2.051317 0.00308368 -999.000 -999.0000 1.00000 1.00000 1031.0877 1004.8586 1.2036 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.46886833   4197.9300 999.8980 35.93733243 13.37 6.70 6.67 1006252.25 8.5798 8.579828 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 Sensible 86334.71 51162.86 1.0000 2.46895513 2.051317 32.10 23.13 0.01411964 68410.3 11.94 11.74 0.00850000 33442.2 3.08336118 6.70 13.37 6.67 2195.006 84139.70 32.10 0.01411964 23.13 2.05124512 99.9965 21.11 0.00871680 21.11 0.00871743 55.8841 177906.93 0.00 86433.83 51479.65 2.46895513 32.10 23.14 0.01411964 68410.3 11.88 11.73 0.00850831 33402.0
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 20393.415 20393.415 0.615395 0.00017841 336.601 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.46886833   4197.9300 999.8980 4.29110285 54.44 82.22 27.78 500421.96 4.0752 4.157260 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 20393.42 20393.42 1.0000 0.74068654 0.615395 -10.70 -10.70 0.00150390 -7020.5 16.70 13.18 0.00800000 37036.7 0.17839229 60.00 32.22 27.78 0.000 20393.42 -10.70 0.00150390 -10.70 2.05124512 333.3216 21.11 0.00752458 21.11 0.00752643 48.3395 120977.96 0.00 17473.63 17473.63 0.74068654 2.80 -1.97 0.00150390 6582.5 26.21 10.51 0.00150390 30173.7



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 11.66 21.97 -      
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 830.83 6342.33 0.00
RETAIL_1_FLR_1 2625.67 6551.33 1152.67
RETAIL_2_FLR_1 1855.00 6078.67 128.00
MECH_FLR_1 1355.33 6982.17 659.17
STORAGE_FLR_1 1187.83 7473.67 887.83
LAUNDRY_FLR_1 6854.33 3429.00 2641.33
CAFE_FLR_1 3536.00 5623.50 1130.33
LOBBY_FLR_1 2931.67 5698.33 865.17
ROOM_1_FLR_3 2628.67 8109.83 2416.67
ROOM_2_FLR_3 3082.17 8274.50 2955.17
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 2211.00 8760.00 2211.00
ROOM_5_FLR_3 2455.50 8033.33 2358.33
ROOM_6_FLR_3 2897.00 8215.83 2871.83
CORRIDOR_FLR_3 1305.33 6992.00 635.50
ROOM_1_FLR_6 3275.00 8049.67 2962.33
ROOM_2_FLR_6 3630.00 8205.33 3437.83
ROOM_3_MULT9_FLR_6 1950.50 8045.17 1748.83
BANQUET_FLR_6 4385.17 3487.17 857.67
DINING_FLR_6 5052.00 2450.00 768.00
KITCHEN_FLR_6 8111.67 6520.17 6241.50
CORRIDOR_FLR_6 2168.50 6501.50 679.67
Facility 8758.50 8760.00 8133.83
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 142.17 0.00 142.17
CAFE_FLR_1 0.00 0.50 0.00 0.50
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 11.17 0.00 11.17
ROOM_2_FLR_3 0.00 5.83 0.00 5.83
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 2.50 10.00 2.50 10.00
ROOM_5_FLR_3 0.00 3.50 0.00 3.50
ROOM_6_FLR_3 0.00 3.50 0.00 3.50
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 15.50 0.00 15.50
ROOM_2_FLR_6 0.00 8.00 0.00 8.00
ROOM_3_MULT9_FLR_6 0.00 9.83 0.00 9.83
BANQUET_FLR_6 0.00 21.17 0.00 21.17
DINING_FLR_6 0.00 28.83 0.00 28.83
KITCHEN_FLR_6 0.00 237.50 0.00 237.50
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 2.50 310.50 2.50 310.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.79 106.50 4826.41 0.965 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 2.654 0.137 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 1.411 0.046 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.640 0.051 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.535 0.051 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 21.491 0.147 0.000 0.000
CAFE_FLR_1 82.56 142.30 748.35 3.843 0.108 0.000 0.000
LOBBY_FLR_1 245.09 422.44 5183.56 1.699 0.045 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.472 0.177 0.000 0.065
ROOM_2_FLR_3 0.95 1.50 118.93 0.472 0.177 0.000 0.063
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.536 0.079 0.000 0.100
ROOM_5_FLR_3 0.95 1.50 118.94 0.472 0.178 0.000 0.065
ROOM_6_FLR_3 0.95 1.50 118.93 0.472 0.177 0.000 0.063
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.565 0.022 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.472 0.178 0.000 0.079
ROOM_2_FLR_6 0.95 1.50 118.93 0.472 0.177 0.000 0.077
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.537 0.145 0.000 0.126
BANQUET_FLR_6 144.99 249.90 1010.89 4.499 0.052 0.000 0.000
DINING_FLR_6 144.99 249.90 1010.89 4.839 0.052 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 20.112 0.148 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 1.109 0.036 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.79 106.50 4826.41 0.589 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 1.563 0.002 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 0.839 0.001 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.384 0.001 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.322 0.001 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 11.643 0.002 0.000 0.000
CAFE_FLR_1 82.56 142.30 748.35 2.300 0.002 0.000 0.000
LOBBY_FLR_1 245.09 422.44 5183.56 1.037 0.001 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.453 0.003 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.452 0.003 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.514 0.001 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.454 0.003 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.452 0.003 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.339 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.453 0.003 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.452 0.003 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.516 0.002 0.000 0.000
BANQUET_FLR_6 144.99 249.90 1010.89 2.765 0.001 0.000 0.000
DINING_FLR_6 144.99 249.90 1010.89 3.028 0.001 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 7.975 0.002 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 0.658 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.79 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.28 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.56 142.30 748.35 188.86 0.0000 0.676
LOBBY_FLR_1 VAV WITH REHEAT 245.09 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 144.99 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 144.99 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.25 1604.23 35184.81 11345.29 0.0000 137.584


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 40053317.57 0.00 40053317.57 0.00 40053317.57 26946214.98 2.73 2.19 8755.08 0.00
RETAIL_1_FLR_1 6096370.29 0.00 6096370.29 315162.19 6411532.47 2498216.28 0.00 0.00 8760.00 0.00
RETAIL_2_FLR_1 3743198.29 0.00 3743198.29 121653.00 3864851.29 2892943.94 78.13 16.54 8665.33 0.00
MECH_FLR_1 3601474.47 0.00 3601474.47 287515.42 3888989.90 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 1736431.62 0.00 1736431.62 165880.56 1902312.19 1821682.01 5416.36 447.81 2895.83 0.00
LAUNDRY_FLR_1 57257952.50 0.00 57257952.50 392587.63 57650540.13 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 24751228.53 0.00 24751228.53 696683.85 25447912.38 21330615.53 740.36 202.72 7816.92 0.00
LOBBY_FLR_1 75699269.51 0.00 75699269.51 1990584.90 77689854.40 59728886.00 85.71 28.88 8645.41 0.00
ROOM_1_FLR_3 1946875.62 66743.16 2013618.78 182929.66 2196548.44 1946875.62 0.00 7864.33 895.67 0.00
ROOM_2_FLR_3 1946647.51 64776.25 2011423.76 182915.70 2194339.47 1946647.51 0.00 7864.33 895.67 0.00
ROOM_3_MULT19_FLR_3 26397887.27 69939.60 26467826.88 51039.43 26518866.30 26397887.27 0.00 7879.17 880.83 8760.00
ROOM_4_MULT19_FLR_3 26405105.73 64485.06 26469590.79 51053.38 26520644.18 26405105.73 0.00 7891.35 868.65 0.00
ROOM_5_FLR_3 1946875.62 66809.53 2013685.15 182929.66 2196614.81 1946875.62 0.00 7864.33 895.67 0.00
ROOM_6_FLR_3 1946647.51 64825.78 2011473.29 182915.70 2194388.99 1946647.51 0.00 7864.33 895.67 0.00
CORRIDOR_FLR_3 23133824.93 0.00 23133824.93 221198.76 23355023.69 14972100.18 1.44 0.92 8757.65 0.00
ROOM_1_FLR_6 486718.90 81257.65 567976.55 182967.83 750944.38 486718.90 0.00 7861.17 898.83 0.00
ROOM_2_FLR_6 486661.88 78683.38 565345.26 182953.87 748299.13 486661.88 0.00 7861.17 898.83 0.00
ROOM_3_MULT9_FLR_6 3126920.42 81221.33 3208141.74 93612.75 3301754.49 3126920.42 0.00 7861.36 898.64 0.00
BANQUET_FLR_6 38983179.72 0.00 38983179.72 446761.45 39429941.17 37458366.31 4799.61 342.25 3618.14 0.00
DINING_FLR_6 41927083.45 0.00 41927083.45 446761.45 42373844.90 37458366.31 2740.94 236.74 5782.33 0.00
KITCHEN_FLR_6 54298244.60 0.00 54298244.60 399955.08 54698199.68 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 12030340.02 0.00 12030340.02 391453.71 12421793.73 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.45E+10 12159826.70 0.45E+10 18434047.20 0.46E+10 0.43E+10 6839.89 7989.81 8760.00 8760.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.2701 0.0000 1.2701 0.0000 1.2701 0.8545 2.73 2.19 8755.08
RETAIL_1_FLR_1 0.1933 0.0000 0.1933 0.0100 0.2033 0.0792 0.00 0.00 8760.00
RETAIL_2_FLR_1 0.1187 0.0000 0.1187 0.0039 0.1226 0.0917 78.13 16.54 8665.33
MECH_FLR_1 0.1142 0.0000 0.1142 0.0091 0.1233 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0551 0.0000 0.0551 0.0053 0.0603 0.0578 5416.36 447.81 2895.83
LAUNDRY_FLR_1 1.8156 0.0000 1.8156 0.0124 1.8281 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.7849 0.0000 0.7849 0.0221 0.8069 0.6764 740.36 202.72 7816.92
LOBBY_FLR_1 2.4004 0.0000 2.4004 0.0631 2.4635 1.8940 85.71 28.88 8645.41
ROOM_1_FLR_3 0.0617 0.0021 0.0639 0.0058 0.0697 0.0617 0.00 7864.33 895.67
ROOM_2_FLR_3 0.0617 0.0021 0.0638 0.0058 0.0696 0.0617 0.00 7864.33 895.67
ROOM_4_MULT19_FLR_3 0.8373 0.0020 0.8393 0.0016 0.8410 0.8373 0.00 7891.35 868.65
ROOM_5_FLR_3 0.0617 0.0021 0.0639 0.0058 0.0697 0.0617 0.00 7864.33 895.67
ROOM_6_FLR_3 0.0617 0.0021 0.0638 0.0058 0.0696 0.0617 0.00 7864.33 895.67
CORRIDOR_FLR_3 0.7336 0.0000 0.7336 0.0070 0.7406 0.4748 1.44 0.92 8757.65
ROOM_1_FLR_6 0.0154 0.0026 0.0180 0.0058 0.0238 0.0154 0.00 7861.17 898.83
ROOM_2_FLR_6 0.0154 0.0025 0.0179 0.0058 0.0237 0.0154 0.00 7861.17 898.83
ROOM_3_MULT9_FLR_6 0.0992 0.0026 0.1017 0.0030 0.1047 0.0992 0.00 7861.36 898.64
BANQUET_FLR_6 1.2361 0.0000 1.2361 0.0142 1.2503 1.1878 4799.61 342.25 3618.14
DINING_FLR_6 1.3295 0.0000 1.3295 0.0142 1.3437 1.1878 2740.94 236.74 5782.33
KITCHEN_FLR_6 1.7218 0.0000 1.7218 0.0127 1.7345 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.3815 0.0000 0.3815 0.0124 0.3939 0.1256 0.00 0.00 8760.00
Total Facility 79.9012 0.2170 80.1183 0.4615 80.5798 73.9670 6839.89 7989.81 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.56E+09 0.00 0.56E+09 0.22E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 93713071.71 638741.74 94351813.45 64690340.46 0.00 0.00 8760.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 17.6102 0.0000 17.6102 6.9969 0.00 0.00 8760.00
FLR_3_DOAS 2.9716 0.0203 2.9919 2.0513 0.00 0.00 8760.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 6116.93 2643.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLR_3_DOAS 0.00 7732.59 1027.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 16.8958 19.2700 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 2.9718 2.9728 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1318
Defaulted Fields 1181
Fields with Defaults 4005
Autosized Fields 350
Autosizable Fields 402
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 5670.82 75716.98 06-APR-02:40 454905.91 04-AUG-19:10
Electricity:Building 2518.65 32537.67 20-MAY-05:00 151906.32 02-JAN-20:10
Electricity:Zone:BASEMENT 323.72 3705.45 02-JAN-02:10 24299.15 02-JAN-20:10
Electricity:SpaceType:GENERAL 2511.55 32396.52 20-MAY-05:00 151664.99 02-JAN-20:10
InteriorLights:Electricity 766.54 6704.72 20-MAY-05:00 62892.57 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 173.46 1576.23 02-JAN-02:10 14185.34 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 766.54 6704.72 20-MAY-05:00 62892.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity 766.54 6704.72 20-MAY-05:00 62892.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 173.46 1576.23 02-JAN-02:10 14185.34 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 766.54 6704.72 20-MAY-05:00 62892.57 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 18.80 222.61 02-JAN-02:10 1390.02 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.61 78.27 02-JAN-02:10 704.41 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.61 78.27 02-JAN-02:10 704.41 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 21.77 257.78 02-JAN-02:10 1609.65 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.97 90.64 02-JAN-02:10 815.72 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.97 90.64 02-JAN-02:10 815.72 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 29.11 327.88 02-JAN-02:10 2199.84 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 16.64 151.16 02-JAN-02:10 1360.40 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 16.64 151.16 02-JAN-02:10 1360.40 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 6.38 76.28 02-JAN-02:10 469.87 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.78 25.30 02-JAN-02:10 227.72 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.78 25.30 02-JAN-02:10 227.72 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 72.30 1002.39 02-JAN-02:10 4930.01 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.37 39.69 02-JAN-02:10 357.21 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.37 39.69 02-JAN-02:10 357.21 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 32.27 322.63 20-MAY-05:00 2727.18 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 17.93 119.42 20-MAY-05:00 1761.91 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 17.93 119.42 20-MAY-05:00 1761.91 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 270.86 3198.76 20-MAY-05:00 20294.39 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 121.86 1087.35 20-MAY-05:00 10265.18 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 121.86 1087.35 20-MAY-05:00 10265.18 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 18.66 264.62 01-JAN-02:10 1227.54 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 18.66 264.59 01-JAN-02:10 1227.39 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 304.77 4565.05 01-JAN-02:10 20923.25 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 76.02 643.59 01-JAN-02:10 5851.22 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 76.02 643.59 01-JAN-02:10 5851.22 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 304.86 4566.30 01-JAN-02:10 20928.98 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 76.04 643.77 01-JAN-02:10 5852.82 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 76.04 643.77 01-JAN-02:10 5852.82 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 18.66 264.62 01-JAN-02:10 1227.54 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 18.66 264.59 01-JAN-02:10 1227.39 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 4.66 66.15 01-JAN-02:10 306.88 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.59 13.47 01-JAN-02:10 122.50 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.59 13.47 01-JAN-02:10 122.50 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 4.66 66.15 01-JAN-02:10 306.85 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.59 13.47 01-JAN-02:10 122.49 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.59 13.47 01-JAN-02:10 122.49 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 36.10 540.75 01-JAN-02:10 2478.43 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 9.00 76.24 01-JAN-02:10 693.10 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 9.00 76.24 01-JAN-02:10 693.10 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 210.49 2524.33 20-MAY-05:00 9841.96 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 34.64 275.03 20-MAY-05:00 3094.06 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 34.64 275.03 20-MAY-05:00 3094.06 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 210.49 2524.33 20-MAY-05:00 9841.96 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 34.64 275.03 20-MAY-05:00 3094.06 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 34.64 275.03 20-MAY-05:00 3094.06 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 454.16 6253.02 02-JAN-02:10 18944.06 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.33 121.09 02-JAN-02:10 1089.83 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.33 121.09 02-JAN-02:10 1089.83 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
InteriorEquipment:Electricity 1745.01 25691.80 02-JAN-02:10 89475.41 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1745.01 25691.80 02-JAN-02:10 89475.41 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 433.74 5990.78 01-JAN-00:10 16487.34 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
Refrigeration:Electricity 62.02 1114.64 11-FEB-23:30 3479.68 31-OCT-06:20
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 1464.15 2579.68 12-APR-00:30 214576.24 16-AUG-15:20
LowTempRefrigeration:Refrigeration:Electricity 20.46 0.00 01-JAN-11:10 2049.73 31-OCT-06:20
MedTempRefrigeration:Refrigeration:Electricity 34.47 934.38 06-FEB-04:10 1245.48 12-MAR-09:00
Fans:Electricity 571.72 12846.55 05-NOV-03:00 44313.79 19-JAN-21:40
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 826.44 14278.91 22-OCT-01:40 51046.35 07-SEP-21:10
ExteriorEquipment:Electricity 651.48 9618.58 02-JAN-02:20 39726.11 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 32.45 553.73 10-JUN-05:00 1868.65 23-MAR-20:10
ElectricityPurchased:Facility 5670.82 75716.98 06-APR-02:40 454905.91 04-AUG-19:10
ElectricityPurchased:Plant 5670.82 75716.98 06-APR-02:40 454905.91 04-AUG-19:10
Cogeneration:ElectricityPurchased 5670.82 75716.98 06-APR-02:40 454905.91 04-AUG-19:10
General:Cogeneration:ElectricityPurchased 5670.82 75716.98 06-APR-02:40 454905.91 04-AUG-19:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 5670.82 75716.98 06-APR-02:40 454905.91 04-AUG-19:10
ElectricityNet:Plant 5670.82 75716.98 06-APR-02:40 454905.91 04-AUG-19:10
Cogeneration:ElectricityNet 5670.82 75716.98 06-APR-02:40 454905.91 04-AUG-19:10
General:Cogeneration:ElectricityNet 5670.82 75716.98 06-APR-02:40 454905.91 04-AUG-19:10
General:Fans:Electricity 571.72 12846.55 05-NOV-03:00 44313.79 19-JAN-21:40
ExteriorLights:Electricity 242.55 0.00 01-JAN-07:30 15448.40 01-JAN-00:10
General:ExteriorLights:Electricity 242.55 0.00 01-JAN-07:30 15448.40 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.91 18.80 01-JAN-00:10 188.00 01-JAN-07:10
HeatRecovery:Electricity 222.27 0.00 02-MAR-15:40 9938.94 03-JAN-18:20
General:HeatRecovery:Electricity 222.27 0.00 02-MAR-15:40 9938.94 03-JAN-18:20
WaterSystems:Electricity 90.75 1086.57 13-SEP-00:30 4738.56 10-NOV-19:10
Water Heater:WaterSystems:Electricity 90.75 1086.57 13-SEP-00:30 4738.56 10-NOV-19:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 1189.20 0.00 01-JAN-00:10 203778.65 16-AUG-15:20
General:Cooling:Electricity 1189.20 0.00 01-JAN-00:10 203778.65 16-AUG-15:20
Pumps:Electricity 129.27 47.91 10-MAY-07:10 7648.61 24-JUN-18:10
General:Pumps:Electricity 129.27 47.91 10-MAY-07:10 7648.61 24-JUN-18:10
WIRED_LTG_ELECTRICITY 26.98 0.00 01-JAN-00:10 2213.82 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 5648.58 29270.80 07-APR-01:20 560006.54 05-FEB-19:10
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 3859.75 15908.90 20-JUN-10:10 494940.87 05-FEB-24:00
WaterSystems:NaturalGas 3097.94 15908.90 01-JAN-16:10 297324.00 03-MAR-21:20
Water Heater:WaterSystems:NaturalGas 3097.94 15908.90 01-JAN-16:10 297324.00 03-MAR-21:20
Heating:NaturalGas 761.81 0.00 02-MAR-15:30 259652.49 06-FEB-09:10
Boiler:Heating:NaturalGas 761.81 0.00 02-MAR-15:30 259652.49 06-FEB-09:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 3880.89 -61.72 12-MAR-00:20 682996.29 24-JUN-18:10
PlantLoopCoolingDemand:HVAC 3880.89 -61.72 12-MAR-00:20 682996.29 24-JUN-18:10
CoolingCoils:PlantLoopCoolingDemand 3880.89 -61.72 12-MAR-00:20 682996.29 24-JUN-18:10


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 12-JAN-21:20
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 12-JAN-21:20
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 12-JAN-21:20
Water Heater:WaterSystems:Water 5742.51 0.00 04-MAR-01:10 0.00 02-JAN-19:10
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 12-JAN-21:20
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 12-JAN-21:20
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 12-JAN-21:20
Water Heater:WaterSystems:MainsWater 5742.51 0.00 04-MAR-01:10 0.00 02-JAN-19:10
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 18-JAN-08:00
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 18-JAN-08:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 23790.21 142913.07 30-APR-14:10 2771323.15 16-AUG-15:20
EnergyTransfer:Building 5346.77 56325.73 08-DEC-15:40 353778.18 19-JUN-18:20
EnergyTransfer:Zone:KITCHEN_FLR_6 717.29 8692.40 14-MAY-01:20 36697.45 09-JUL-10:40
Refrigeration:EnergyTransfer 183.85 3986.66 06-FEB-04:00 10705.13 31-OCT-06:20
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 91.92 1993.33 06-FEB-04:00 5352.56 31-OCT-06:20
General:Refrigeration:EnergyTransfer 91.92 1993.33 06-FEB-04:00 5352.56 31-OCT-06:20
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 91.92 1993.33 06-FEB-04:00 5352.56 31-OCT-06:20
EnergyTransfer:Plant 10537.64 14434.07 08-OCT-00:50 1580134.43 24-JUN-18:10
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.62 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 70.30 1753.13 06-FEB-04:10 2686.44 12-MAR-09:00
EnergyTransfer:Zone:BASEMENT 426.88 1998.96 12-MAR-08:50 25176.57 17-NOV-20:40
Heating:EnergyTransfer 186.17 0.00 03-JAN-18:30 112923.02 14-JAN-16:10
Heating:EnergyTransfer:Zone:BASEMENT 0.04 0.00 01-JAN-00:10 947.95 27-OCT-22:30
General:Heating:EnergyTransfer 186.17 0.00 03-JAN-18:30 112923.02 14-JAN-16:10
General:Heating:EnergyTransfer:Zone:BASEMENT 0.04 0.00 01-JAN-00:10 947.95 27-OCT-22:30
Cooling:EnergyTransfer 5068.67 49485.58 08-DEC-15:40 350169.15 19-JUN-18:20
Cooling:EnergyTransfer:Zone:BASEMENT 426.84 1850.75 12-MAR-08:50 25176.57 17-NOV-20:40
General:Cooling:EnergyTransfer 5068.67 49485.58 08-DEC-15:40 350169.15 19-JUN-18:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 426.84 1850.75 12-MAR-08:50 25176.57 17-NOV-20:40
EnergyTransfer:Zone:RETAIL_1_FLR_1 43.80 0.11 21-FEB-17:20 4470.45 04-OCT-12:10
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 1.27 0.00 01-JAN-08:30 1433.94 02-JAN-07:10
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 1.27 0.00 01-JAN-08:30 1433.94 02-JAN-07:10
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 42.53 0.00 01-JAN-00:10 4470.45 04-OCT-12:10
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 42.53 0.00 01-JAN-00:10 4470.45 04-OCT-12:10
EnergyTransfer:Zone:RETAIL_2_FLR_1 35.99 168.62 31-OCT-06:10 2272.90 04-AUG-21:00
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.01 0.00 01-JAN-00:10 180.98 25-DEC-05:50
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.01 0.00 01-JAN-00:10 180.98 25-DEC-05:50
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 35.98 87.73 08-DEC-15:40 2272.90 04-AUG-21:00
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 35.98 87.73 08-DEC-15:40 2272.90 04-AUG-21:00
EnergyTransfer:Zone:MECH_FLR_1 28.63 0.05 01-FEB-03:10 2247.29 17-AUG-20:00
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.29 0.00 01-JAN-19:10 616.01 02-JAN-04:50
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.29 0.00 01-JAN-19:10 616.01 02-JAN-04:50
Cooling:EnergyTransfer:Zone:MECH_FLR_1 28.34 0.00 01-JAN-00:10 2247.29 17-AUG-20:00
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 28.34 0.00 01-JAN-00:10 2247.29 17-AUG-20:00
EnergyTransfer:Zone:STORAGE_FLR_1 12.81 0.04 26-JAN-17:00 874.09 04-AUG-21:00
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.52 0.00 03-JAN-18:30 478.83 02-JAN-05:00
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.52 0.00 03-JAN-18:30 478.83 02-JAN-05:00
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 12.29 0.00 01-JAN-00:10 874.09 04-AUG-21:00
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 12.29 0.00 01-JAN-00:10 874.09 04-AUG-21:00
EnergyTransfer:Zone:LAUNDRY_FLR_1 592.96 5745.10 01-MAY-02:30 39016.04 04-AUG-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.01 0.00 01-JAN-00:10 652.85 27-MAR-03:50
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.01 0.00 01-JAN-00:10 652.85 27-MAR-03:50
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 592.95 5745.10 01-MAY-02:30 39016.04 04-AUG-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 592.95 5745.10 01-MAY-02:30 39016.04 04-AUG-20:00
EnergyTransfer:Zone:CAFE_FLR_1 239.49 17.60 14-JAN-13:50 15303.21 30-SEP-12:40
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.06 0.00 01-JAN-00:10 913.21 15-JAN-11:30
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.06 0.00 01-JAN-00:10 913.21 15-JAN-11:30
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 239.43 0.00 08-JAN-13:50 15303.21 30-SEP-12:40
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 239.43 0.00 08-JAN-13:50 15303.21 30-SEP-12:40
EnergyTransfer:Zone:LOBBY_FLR_1 780.18 3361.23 12-MAR-08:50 43844.34 04-AUG-21:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.08 0.00 01-JAN-00:10 2496.36 15-JAN-11:30
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.08 0.00 01-JAN-00:10 2496.36 15-JAN-11:30
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 780.10 2861.76 08-DEC-15:40 43844.34 04-AUG-21:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 780.10 2861.76 08-DEC-15:40 43844.34 04-AUG-21:10
EnergyTransfer:Zone:ROOM_1_FLR_3 73.14 0.15 11-APR-05:00 12724.60 15-AUG-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 18.42 0.00 01-JAN-08:10 7101.11 14-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 18.42 0.00 01-JAN-08:10 7101.11 14-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 54.72 0.00 01-JAN-00:10 12724.60 15-AUG-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 54.72 0.00 01-JAN-00:10 12724.60 15-AUG-15:10
EnergyTransfer:Zone:ROOM_2_FLR_3 70.26 0.06 12-APR-00:20 12054.01 02-AUG-15:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 23.29 0.00 01-JAN-08:10 7210.48 06-FEB-09:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 23.29 0.00 01-JAN-08:10 7210.48 06-FEB-09:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 46.97 0.00 01-JAN-00:10 12054.01 02-AUG-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 46.97 0.00 01-JAN-00:10 12054.01 02-AUG-15:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 414.60 0.71 30-DEC-07:50 60539.24 04-OCT-12:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 10.85 0.00 01-JAN-08:10 19243.50 02-JAN-05:00
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 10.85 0.00 01-JAN-08:10 19243.50 02-JAN-05:00
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 403.75 0.00 01-JAN-00:10 60539.24 04-OCT-12:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 403.75 0.00 01-JAN-00:10 60539.24 04-OCT-12:10
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 432.68 0.47 01-APR-23:30 67798.37 10-JUL-15:20
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 56.45 0.00 01-JAN-08:10 46333.94 14-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 56.45 0.00 01-JAN-08:10 46333.94 14-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 376.23 0.00 01-JAN-00:10 67798.37 10-JUL-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 376.23 0.00 01-JAN-00:10 67798.37 10-JUL-15:20
EnergyTransfer:Zone:ROOM_5_FLR_3 72.54 0.14 01-JAN-10:00 11459.10 22-AUG-08:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 18.21 0.00 01-JAN-08:10 7150.83 14-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 18.21 0.00 01-JAN-08:10 7150.83 14-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 54.33 0.00 01-JAN-00:10 11459.10 22-AUG-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 54.33 0.00 01-JAN-00:10 11459.10 22-AUG-08:10
EnergyTransfer:Zone:ROOM_6_FLR_3 68.88 0.16 19-MAR-13:20 11230.77 14-JUL-08:10
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 22.78 0.00 01-JAN-08:10 7211.81 14-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 22.78 0.00 01-JAN-08:10 7211.81 14-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 46.10 0.00 01-JAN-00:10 11230.77 14-JUL-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 46.10 0.00 01-JAN-00:10 11230.77 14-JUL-08:10
EnergyTransfer:Zone:CORRIDOR_FLR_3 189.03 0.25 04-FEB-09:50 12482.13 18-AUG-18:20
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.78 0.00 01-JAN-00:30 3266.21 14-JAN-16:30
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.78 0.00 01-JAN-00:30 3266.21 14-JAN-16:30
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 188.25 0.00 01-JAN-00:10 12482.13 18-AUG-18:20
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 188.25 0.00 01-JAN-00:10 12482.13 18-AUG-18:20
EnergyTransfer:Zone:ROOM_1_FLR_6 20.30 0.04 23-FEB-14:00 3363.16 18-AUG-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 6.92 0.00 01-JAN-11:10 2254.10 14-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 6.92 0.00 01-JAN-11:10 2254.10 14-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 13.38 0.00 01-JAN-00:10 3363.16 18-AUG-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 13.38 0.00 01-JAN-00:10 3363.16 18-AUG-15:10
EnergyTransfer:Zone:ROOM_2_FLR_6 19.90 0.10 12-MAR-14:10 3207.31 13-JUL-15:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 8.51 0.00 03-JAN-08:10 2280.20 14-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 8.51 0.00 03-JAN-08:10 2280.20 14-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 11.40 0.00 01-JAN-00:10 3207.31 13-JUL-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 11.40 0.00 01-JAN-00:10 3207.31 13-JUL-15:10
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 102.94 0.07 20-FEB-00:10 15619.66 22-AUG-15:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 16.67 0.00 01-JAN-08:10 10685.32 14-JAN-16:20
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 16.67 0.00 01-JAN-08:10 10685.32 14-JAN-16:20
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 86.27 0.00 01-JAN-00:10 15619.66 22-AUG-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 86.27 0.00 01-JAN-00:10 15619.66 22-AUG-15:10
EnergyTransfer:Zone:BANQUET_FLR_6 435.73 2247.21 08-DEC-15:40 23825.34 04-AUG-21:20
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 118.05 31-OCT-06:20
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 118.05 31-OCT-06:20
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 435.73 2247.21 08-DEC-15:40 23825.34 04-AUG-21:20
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 435.73 2247.21 08-DEC-15:40 23825.34 04-AUG-21:20
EnergyTransfer:Zone:DINING_FLR_6 474.38 2811.63 08-DEC-15:40 24997.59 04-AUG-21:20
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 80.77 31-OCT-06:20
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 80.77 31-OCT-06:20
Cooling:EnergyTransfer:Zone:DINING_FLR_6 474.38 2811.63 08-DEC-15:40 24997.59 04-AUG-21:20
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 474.38 2811.63 08-DEC-15:40 24997.59 04-AUG-21:20
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 37.44 18-OCT-01:50
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 37.44 18-OCT-01:50
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 625.36 6298.53 14-MAY-01:20 31608.25 13-AUG-10:50
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 625.36 6298.53 14-MAY-01:20 31608.25 13-AUG-10:50
EnergyTransfer:Zone:CORRIDOR_FLR_6 94.36 0.09 18-MAR-05:30 7302.76 16-AUG-12:50
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 1.01 0.00 01-JAN-09:00 2521.16 02-JAN-07:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 1.01 0.00 01-JAN-09:00 2521.16 02-JAN-07:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 93.35 0.00 01-JAN-00:10 7302.76 16-AUG-12:50
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 93.35 0.00 01-JAN-00:10 7302.76 16-AUG-12:50
PlantLoopHeatingDemand:Facility 1283.90 8505.09 11-AUG-02:00 256465.62 06-FEB-07:10
PlantLoopHeatingDemand:Plant 742.72 8505.09 11-AUG-02:00 56503.94 06-FEB-07:10
WaterSystems:PlantLoopHeatingDemand 742.72 8505.09 11-AUG-02:00 56503.94 06-FEB-07:10
General:WaterSystems:PlantLoopHeatingDemand 742.72 8505.09 11-AUG-02:00 56503.94 06-FEB-07:10
EnergyTransfer:HVAC 7905.80 15.12 20-MAY-07:40 898507.18 16-AUG-15:20
HeatingCoils:EnergyTransfer 541.18 0.00 02-MAR-15:30 215528.89 14-JAN-16:10
PlantLoopHeatingDemand:HVAC 541.18 0.00 02-MAR-15:30 215528.89 14-JAN-16:10
HeatingCoils:PlantLoopHeatingDemand 541.18 0.00 02-MAR-15:30 215528.89 14-JAN-16:10
CoolingCoils:EnergyTransfer 3880.89 -61.72 12-MAR-00:20 682996.29 24-JUN-18:10
HeatRecoveryForHeating:EnergyTransfer 2928.16 0.00 02-MAR-15:40 487649.56 06-FEB-03:00
HeatRecoveryForCooling:EnergyTransfer 555.57 0.00 01-JAN-00:10 279121.09 08-JUL-12:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 742.72 8505.09 11-AUG-02:00 56503.94 06-FEB-07:10
WaterUse:WaterSystems:EnergyTransfer 742.72 8505.09 11-AUG-02:00 56503.94 06-FEB-07:10
Boilers:EnergyTransfer 535.18 0.00 02-MAR-15:30 211685.36 14-JAN-16:10
Chillers:EnergyTransfer 3989.31 0.00 01-JAN-00:10 691369.08 24-JUN-18:10
HeatRejection:EnergyTransfer 5178.51 0.00 01-JAN-00:10 861468.59 16-AUG-15:20
General:HeatRejection:EnergyTransfer 5178.51 0.00 01-JAN-00:10 861468.59 16-AUG-15:20



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.036 -426.843 0.000 0.000 138.765 173.462 150.255 0.000 0.000 0.000 0.001 0.000 0.000 0.000 0.000 -35.675
RETAIL_1_FLR_1 0.000 0.000 1.270 -42.526 0.000 0.000 15.476 8.614 10.186 27.367 0.000 0.176 0.000 0.000 -9.902 0.000 -3.934 -6.726
RETAIL_2_FLR_1 0.000 0.000 0.015 -35.979 0.000 0.000 17.007 9.975 11.795 0.000 0.000 0.065 0.000 0.000 0.000 0.000 -1.612 -1.264
MECH_FLR_1 0.000 0.000 0.288 -28.345 0.000 0.000 3.713 16.635 12.471 0.000 0.000 0.154 0.000 0.000 0.000 0.000 -3.643 -1.274
STORAGE_FLR_1 0.000 0.000 0.518 -12.290 0.000 0.000 2.879 2.785 3.598 0.000 0.000 0.092 4.499 0.000 0.000 0.000 -2.080 -0.000
LAUNDRY_FLR_1 0.000 0.000 0.006 -592.953 0.000 0.000 11.280 4.368 658.131 0.000 0.000 0.258 0.000 0.000 0.000 0.000 -5.425 -75.664
CAFE_FLR_1 0.000 0.000 0.062 -239.430 0.000 0.000 191.991 17.926 14.341 76.014 0.000 0.356 0.000 0.000 -29.754 0.000 -9.338 -22.168
LOBBY_FLR_1 0.000 0.000 0.085 -780.105 0.000 0.000 556.659 121.863 148.998 100.574 0.000 1.018 0.000 0.000 -40.439 0.000 -27.443 -81.210
ROOM_1_FLR_3 22.677 -42.919 0.000 -16.064 0.000 0.000 9.734 6.366 12.292 52.252 0.000 0.799 0.000 0.000 -22.089 0.000 -9.465 -13.583
ROOM_2_FLR_3 28.033 -35.944 0.000 -15.765 0.000 0.000 9.761 6.366 12.291 37.455 0.000 0.797 0.000 0.000 -22.683 0.000 -9.326 -10.985
ROOM_3_MULT19_FLR_3 18.190 -170.187 0.000 -240.910 0.000 0.000 0.000 76.021 228.754 329.047 0.000 2.334 0.001 0.000 -123.543 0.000 -70.083 -49.622
ROOM_4_MULT19_FLR_3 102.227 -208.728 0.000 -213.265 0.000 0.000 185.550 76.042 228.817 103.770 0.000 6.543 0.000 0.000 -126.987 0.000 -56.978 -96.992
ROOM_5_FLR_3 22.383 -42.376 0.000 -16.123 0.000 0.000 9.729 6.366 12.292 51.789 0.000 0.798 0.000 0.000 -21.801 0.000 -9.488 -13.568
ROOM_6_FLR_3 27.490 -34.965 0.000 -15.844 0.000 0.000 9.755 6.366 12.291 36.701 0.000 0.794 0.000 0.000 -22.119 0.000 -9.357 -11.111
CORRIDOR_FLR_3 0.000 0.000 0.782 -188.248 0.000 0.000 117.089 109.603 0.000 47.850 0.000 0.442 0.000 0.000 -29.236 0.000 -11.295 -46.989
ROOM_1_FLR_6 8.119 -10.586 0.000 -3.988 0.000 0.000 2.437 1.592 3.073 12.998 0.000 0.204 0.000 0.000 -5.468 0.000 -2.396 -5.984
ROOM_2_FLR_6 9.839 -8.813 0.000 -3.916 0.000 0.000 2.443 1.591 3.073 9.327 0.000 0.203 0.000 0.000 -5.613 0.000 -2.361 -5.773
ROOM_3_MULT9_FLR_6 22.313 -65.632 0.000 -26.275 0.000 0.000 21.840 9.005 27.097 71.514 0.000 1.141 0.000 0.000 -25.760 0.000 -12.013 -23.229
BANQUET_FLR_6 0.000 0.000 0.000 -435.736 0.000 0.000 317.546 34.635 175.857 10.250 0.000 0.198 0.000 0.000 -17.928 0.000 -6.525 -78.299
DINING_FLR_6 0.000 0.000 0.000 -474.381 0.000 0.000 316.067 34.635 175.857 10.038 0.000 0.197 0.000 0.000 -18.478 0.000 -6.588 -37.347
KITCHEN_FLR_6 0.000 0.000 0.000 -625.353 0.000 0.000 28.383 13.327 550.372 24.044 0.000 0.175 27.085 0.000 -12.109 0.000 -5.924 -0.000
CORRIDOR_FLR_6 0.000 0.000 1.010 -93.349 0.000 0.000 31.130 28.999 0.000 23.313 0.000 0.180 26.824 0.000 -13.117 0.000 -4.992 -0.000
Total Facility 261.270 -620.149 4.072 -4527.686 0.000 0.000 1999.234 766.542 2451.839 1024.303 0.000 16.925 58.410 0.000 -547.027 0.000 -270.267 -617.465


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 27-OCT-21:45 0.00 0.00 0.00 -38082.82 0.00 0.00 6664.74 9457.02 7452.27 0.00 0.00 0.00 14508.79 0.00 -0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 03-DEC-11:07 0.00 0.00 0.00 -5384.35 0.00 0.00 225.90 234.80 288.68 7056.06 0.00 0.00 0.00 0.00 -0.00 0.00 -221.44 -2199.65
RETAIL_2_FLR_1 26-OCT-22:05 0.00 0.00 0.00 -3009.01 0.00 0.00 785.25 271.91 334.29 0.00 0.00 0.00 1692.13 0.00 -0.00 0.00 -74.55 0.00
MECH_FLR_1 17-AUG-20:00 0.00 0.00 0.00 -2247.22 0.00 0.00 129.09 1360.40 839.45 0.00 0.00 51.44 0.00 0.00 -0.00 0.00 0.00 -133.15
STORAGE_FLR_1 26-OCT-22:30 0.00 0.00 0.00 -1012.55 0.00 0.00 140.24 75.91 101.96 0.00 0.00 0.00 791.73 0.00 -0.00 0.00 -97.29 0.00
LAUNDRY_FLR_1 29-NOV-21:50 0.00 0.00 0.00 -51652.13 0.00 0.00 426.20 317.52 41967.83 0.00 0.00 0.00 9272.68 0.00 -0.00 0.00 -332.11 0.00
CAFE_FLR_1 17-DEC-10:08 0.00 0.00 0.00 -22332.02 0.00 0.00 4893.32 358.25 406.43 17664.75 0.00 0.00 0.00 0.00 -0.00 0.00 -421.36 -569.37
LOBBY_FLR_1 21-OCT-05:42 0.00 0.00 0.00 -72507.62 0.00 0.00 20659.06 3421.73 4222.82 0.00 0.00 0.00 47875.99 0.00 -2546.34 0.00 -1125.64 0.00
ROOM_1_FLR_3 07-SEP-15:02 0.00 -13000.66 0.00 -760.95 0.00 0.00 235.28 137.21 273.93 11034.98 0.00 100.69 1979.52 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_3 12-AUG-15:02 0.00 -12445.70 0.00 -745.52 0.00 0.00 130.72 161.69 305.51 6131.10 0.00 161.25 6300.96 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 04-OCT-12:10 0.00 -49706.16 0.00 -10830.70 0.00 0.00 0.00 1638.34 5097.90 77444.25 0.00 162.05 0.00 0.00 -0.00 0.00 0.00 -23805.68
ROOM_4_MULT19_FLR_3 11-JUL-15:02 0.00 -66903.23 0.00 -10365.01 0.00 0.00 4470.52 1638.79 5099.29 16627.94 0.00 768.57 48663.14 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 01-AUG-08:62 0.00 -11695.47 0.00 -756.82 0.00 0.00 87.14 215.61 453.05 10722.17 0.00 112.50 861.83 0.00 -0.00 0.00 0.00 0.00
ROOM_6_FLR_3 02-AUG-08:62 0.00 -11514.39 0.00 -762.20 0.00 0.00 87.14 215.58 452.99 10865.97 0.00 151.26 503.63 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 26-OCT-22:30 0.00 0.00 0.00 -13788.10 0.00 0.00 5657.69 2987.71 0.00 0.00 0.00 0.00 7852.87 0.00 -2178.66 0.00 -531.51 0.00
ROOM_1_FLR_6 01-AUG-15:02 0.00 -3410.75 0.00 -190.68 0.00 0.00 58.82 34.30 68.48 2717.19 0.00 50.44 672.20 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_6 07-JUL-15:02 0.00 -3288.69 0.00 -189.98 0.00 0.00 58.82 34.30 68.48 2109.25 0.00 58.59 1149.25 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 18-AUG-15:02 0.00 -15841.34 0.00 -1224.55 0.00 0.00 529.38 194.07 603.86 6059.53 0.00 299.31 9379.74 0.00 -0.00 0.00 0.00 0.00
BANQUET_FLR_6 06-NOV-23:42 0.00 0.00 0.00 -38096.59 0.00 0.00 15626.30 1031.35 6747.90 0.00 0.00 0.00 16096.56 0.00 -1115.59 0.00 -289.93 0.00
DINING_FLR_6 19-JAN-23:50 0.00 0.00 0.00 -39377.34 0.00 0.00 15099.42 1031.35 6747.90 0.00 0.00 0.00 18089.40 0.00 -1258.67 0.00 -332.05 0.00
KITCHEN_FLR_6 30-NOV-13:52 0.00 0.00 0.00 -40148.67 0.00 0.00 278.82 302.73 21760.70 225.74 0.00 0.00 17847.44 0.00 -0.00 0.00 -266.77 0.00
CORRIDOR_FLR_6 16-AUG-12:50 0.00 0.00 0.00 -7302.98 0.00 0.00 308.46 658.76 0.00 4052.33 0.00 111.28 2172.15 0.00 -0.00 0.00 0.00 0.00
Total Facility 18-AUG-18:02 0.00 -157906.90 0.00 -221106.94 0.00 0.00 73984.50 54200.73 122326.88 25160.97 0.00 3990.57 99350.18 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 27-OCT-22:30 0.00 0.00 2843.99 0.00 0.00 0.00 6609.03 4728.51 4258.44 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -18439.97
RETAIL_1_FLR_1 02-JAN-07:10 0.00 0.00 1434.80 0.00 0.00 0.00 357.96 391.34 433.01 0.00 0.00 0.00 0.00 0.00 -1354.48 0.00 -443.71 -818.92
RETAIL_2_FLR_1 25-DEC-05:45 0.00 0.00 361.98 0.00 0.00 0.00 711.93 181.27 250.72 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -64.30 -1441.59
MECH_FLR_1 02-JAN-04:50 0.00 0.00 616.03 0.00 0.00 0.00 197.30 151.16 176.73 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -411.62 -729.59
STORAGE_FLR_1 30-NOV-13:53 0.00 0.00 653.51 0.00 0.00 0.00 33.66 63.26 89.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -93.51 -746.14
LAUNDRY_FLR_1 16-OCT-03:24 0.00 0.00 3200.12 0.00 0.00 0.00 618.28 39.69 9326.18 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -211.44 -12972.84
CAFE_FLR_1 13-NOV-08:23 0.00 0.00 2794.03 0.00 0.00 0.00 4628.35 477.67 508.04 0.00 0.00 0.00 0.00 0.00 -595.81 0.00 -417.21 -7395.07
LOBBY_FLR_1 13-NOV-08:23 0.00 0.00 5051.65 0.00 0.00 0.00 12861.81 4242.94 5278.53 0.00 0.00 0.00 0.00 0.00 -964.51 0.00 -1280.39 -25190.04
ROOM_1_FLR_3 06-FEB-19:01 10790.81 303.53 0.00 -303.53 0.00 0.00 419.21 436.12 516.26 0.00 0.00 0.00 0.00 0.00 -2836.85 0.00 -842.65 -8482.91
ROOM_2_FLR_3 06-FEB-09:01 10844.29 298.61 0.00 -298.61 0.00 0.00 108.88 215.58 452.99 0.00 0.00 0.00 0.00 0.00 -2044.47 0.00 -969.23 -8608.04
ROOM_3_MULT19_FLR_3 02-JAN-05:00 19243.68 3440.39 0.00 -3440.39 0.00 0.00 0.00 643.59 3921.46 0.00 0.00 0.00 0.00 0.00 -16735.07 0.00 -5222.11 -1851.55
ROOM_4_MULT19_FLR_3 06-FEB-16:01 60356.72 3809.18 0.00 -3809.18 0.00 0.00 5585.75 1638.79 5099.29 0.00 0.00 0.00 0.00 0.00 -12149.81 0.00 -4213.27 -56317.47
ROOM_5_FLR_3 14-JAN-16:02 10531.75 302.88 0.00 -302.88 0.00 0.00 163.33 161.71 305.54 0.00 0.00 0.00 0.00 0.00 -2410.89 0.00 -790.99 -7960.45
ROOM_6_FLR_3 02-JAN-16:01 10557.43 298.11 0.00 -298.11 0.00 0.00 293.99 137.19 273.90 0.00 0.00 0.00 0.00 0.00 -2185.52 0.00 -786.98 -8290.02
CORRIDOR_FLR_3 30-NOV-13:53 0.00 0.00 5707.07 0.00 0.00 0.00 1381.50 2489.76 0.00 2274.05 0.00 0.00 0.00 0.00 -0.00 0.00 -500.28 -11352.10
ROOM_1_FLR_6 06-FEB-19:01 3160.20 76.48 0.00 -76.48 0.00 0.00 104.80 109.03 129.07 0.00 0.00 0.00 0.00 0.00 -708.97 0.00 -211.40 -2582.72
ROOM_2_FLR_6 06-FEB-09:01 3170.44 75.22 0.00 -75.22 0.00 0.00 27.22 53.90 113.25 0.00 0.00 0.00 0.00 0.00 -514.75 0.00 -243.05 -2607.02
ROOM_3_MULT9_FLR_6 14-JAN-16:02 14824.03 485.57 0.00 -485.57 0.00 0.00 367.48 228.73 673.54 0.00 0.00 0.00 0.00 0.00 -2772.89 0.00 -912.58 -12408.30
BANQUET_FLR_6 27-OCT-21:47 0.00 0.00 555.21 0.00 0.00 0.00 15639.39 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 -1126.44 0.00 -302.85 -23575.91
DINING_FLR_6 27-OCT-21:47 0.00 0.00 468.92 0.00 0.00 0.00 15636.92 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 -1148.33 0.00 -303.57 -23464.56
KITCHEN_FLR_6 18-OCT-01:46 0.00 0.00 374.41 0.00 0.00 0.00 1507.34 121.09 5415.98 0.00 0.00 0.00 0.00 0.00 -919.48 0.00 -255.55 -6243.79
CORRIDOR_FLR_6 02-JAN-07:10 0.00 0.00 2522.84 0.00 0.00 0.00 733.32 1317.51 0.00 0.00 0.00 0.00 0.00 0.00 -1766.14 0.00 -552.88 -2254.65
Total Facility 14-JAN-16:02 66920.02 81424.58 7212.40 -81424.58 0.00 0.00 36286.90 17988.09 78718.24 0.00 0.00 0.00 0.00 0.00 -57235.68 0.00 -20291.30 -129598.67



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 22.0915 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 21.9688 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 11.6643 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.6643 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.000000 142.3000 0.003581 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.001045 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5173 2.5173 1.3291 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3885 0.3885 0.2051 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2403 0.2403 0.1269 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2335 0.2335 0.1233 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1132 0.1132 0.0598 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.2642 3.2642 1.7235 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5678 1.5678 0.8278 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.7613 4.7613 2.5140 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5041 1.5041 0.7942 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1764 2.1764 1.1491 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2808 2.2808 1.2042 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2695 2.2695 1.1983 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7746 0.7746 0.4090 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 22.0915 21.9688 22.0915 11.6643 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3291 1.3291 1.3291 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2051 0.2051 0.2051 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1269 0.1269 0.1269 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1233 0.1233 0.1233 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0598 0.0598 0.0598 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7235 1.7235 1.7235 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8278 0.8278 0.8278 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5140 2.5140 2.5140 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7942 0.7942 0.7942 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1491 1.1491 1.1491 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2042 1.2042 1.2042 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1983 1.1983 1.1983 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4090 0.4090 0.4090 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 11.6643 11.6643 11.6643 11.6643 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 2.50
Number of hours cooling loads not met 310.50
Number of hours not met 313.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 761.81 259652.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 1189.20 203778.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 766.54 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 242.55 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 959.56 59492.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 14.43 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 8.99 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 32.45 1868.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.91 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 571.72 44313.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 129.27 7648.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 222.27 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.75 4738.56 3097.94 297324.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 20.46 2049.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 34.47 1245.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1807.04 5670.82
Natural Gas 1788.84 5648.58
Additional 0.00 0.00
Total 3595.87 11319.41


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 67.56
Space Heating 0.00
Space Cooling 104.82
Fans (All) 50.39
Service Water Heating 8.00
Receptacle Equipment 153.81
Miscellaneous (All) 499.84
Subtotal 499.84


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 67.15
Service Water Heating 273.06
Miscellaneous (All) 497.88
Subtotal 497.88


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 6.77
Space Heating 6.73
Space Cooling 10.51
Fans (All) 5.05
Service Water Heating 28.17
Receptacle Equipment 31.22
Miscellaneous 11.55


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2667. 8760.
LTG_SCH_LOBBY 3061. 8760.
LTG_SCH_STORAGE 1339. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 2678. 8760.
LTG_SCH_GUESTROOM 2482. 8760.
LTG_SCH_CORRIDOR 3061. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3924. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 18.89 365 18.89 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 23.33 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8759.67 0.33 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8759.67 0.00 0.00 0.00 0.00
Max 8760.00 0.33 0.00 0.00 0.00
Average 8759.98 0.02 0.00 0.00 0.00
Sum 192719.67 0.33 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108265.83 3.17 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 3.17 0.00 0.00 0.00
Average 288886.90 0.14 0.00 0.00 0.00
Sum 6355511.83 3.17 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8606.17 153.83 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 7796.33 963.67 0.00 0.00 0.00
LOBBY_FLR_1 7800.50 959.50 0.00 0.00 0.00
ROOM_1_FLR_3 8758.83 1.17 0.00 0.00 0.00
ROOM_2_FLR_3 8758.67 1.33 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8730.67 29.33 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8758.33 1.67 0.00 0.00 0.00
ROOM_5_FLR_3 8759.17 0.83 0.00 0.00 0.00
ROOM_6_FLR_3 8759.00 1.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8704.50 55.50 0.00 0.00 0.00
ROOM_1_FLR_6 8756.67 3.33 0.00 0.00 0.00
ROOM_2_FLR_6 8756.67 3.33 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8753.50 6.50 0.00 0.00 0.00
BANQUET_FLR_6 7727.67 1032.33 0.00 0.00 0.00
DINING_FLR_6 7821.00 939.00 0.00 0.00 0.00
KITCHEN_FLR_6 8637.83 122.17 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 7727.67 0.00 0.00 0.00 0.00
Max 8760.00 1032.33 0.00 0.00 0.00
Average 8565.70 194.30 0.00 0.00 0.00
Sum 188445.50 4274.50 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 57507.33 1648.67 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 593817.50 116599.50 0.00 0.00 0.00
LOBBY_FLR_1 1780359.17 335069.83 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 99393.33 964.67 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1034418.17 211296.83 0.00 0.00 0.00
DINING_FLR_6 1051004.00 194711.00 0.00 0.00 0.00
KITCHEN_FLR_6 107351.67 917.33 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 1780359.17 335069.83 0.00 0.00 0.00
Average 249741.23 39145.81 0.00 0.00 0.00
Sum 5494307.17 861207.83 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:43

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

For: Environment

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A

For: Environment

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK

For: Environment

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.351118E+11 35196.04 19-JAN-20:10 4.32 1.34 0.794126E+10 4961.90 12-JAN-23:10 4.32 1.34
February 0.298318E+11 31136.11 01-FEB-20:38 5.60 3.16 0.696870E+10 4836.99 03-FEB-22:19 -0.9 -3.0
March 0.317861E+11 22296.35 04-MAR-00:46 7.98 5.94 0.757397E+10 4769.37 06-MAR-22:10 9.82 5.94
April 0.305831E+11 23040.62 12-APR-22:27 7.20 2.66 0.712060E+10 4712.54 14-APR-21:49 6.70 5.12
May 0.315908E+11 21676.78 14-MAY-01:02 8.80 7.21 0.723010E+10 4531.75 03-MAY-21:10 8.80 7.21
June 0.329413E+11 17414.25 22-JUN-18:10 28.72 17.28 0.726239E+10 4688.42 30-JUN-21:19 20.00 18.86
July 0.362767E+11 17905.30 11-JUL-18:08 26.73 16.72 0.776146E+10 4837.04 27-JUL-21:19 23.17 21.94
August 0.386415E+11 19218.40 25-AUG-21:00 22.80 14.70 0.804496E+10 4837.25 30-AUG-21:19 22.43 18.00
September 0.394788E+11 22914.88 24-SEP-05:17 10.40 8.71 0.790670E+10 4838.45 29-SEP-23:10 12.02 10.24
October 0.423717E+11 38083.22 27-OCT-21:45 7.20 3.64 0.820192E+10 4984.04 27-OCT-22:40 7.20 3.36
November 0.399289E+11 37019.61 12-NOV-23:40 6.10 4.78 0.793398E+10 5080.83 30-NOV-23:40 5.73 2.09
December 0.382984E+11 36005.90 20-DEC-20:21 5.00 1.74 0.815078E+10 4923.29 04-DEC-22:30 5.00 1.74
                     
Annual Sum or Average 0.426841E+12         0.920968E+11        
Minimum of Months 0.298318E+11 17414.25   4.32 1.34 0.696870E+10 4531.75   -0.9 -3.0
Maximum of Months 0.423717E+11 38083.22   28.72 17.28 0.820192E+10 5080.83   23.17 21.94



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.105760E+10 4309.33 17-JAN-12:30 9.70 5.27 0.624623E+09 388.92 19-JAN-22:00 5.60 1.07
February 0.134462E+10 3984.85 02-FEB-13:28 6.15 0.25 0.567801E+09 364.16 16-FEB-02:49 2.12 0.96
March 0.240104E+10 5327.76 29-MAR-13:31 7.80 5.42 0.639773E+09 410.48 24-MAR-21:40 7.80 5.42
April 0.302422E+10 3561.98 08-APR-12:30 23.60 16.18 0.627203E+09 458.02 07-APR-21:30 23.60 16.18
May 0.411561E+10 2938.37 14-MAY-01:02 8.80 7.21 0.663997E+09 462.61 31-MAY-21:30 20.25 17.49
June 0.490814E+10 3120.76 19-JUN-13:10 34.90 23.89 0.701618E+09 491.82 19-JUN-21:19 28.53 20.50
July 0.559689E+10 3322.29 08-JUL-12:00 32.20 26.10 0.758537E+09 491.82 10-JUL-21:19 27.03 20.02
August 0.614073E+10 4061.75 18-AUG-12:40 33.13 20.27 0.778468E+09 491.82 18-AUG-21:40 24.27 17.61
September 0.515618E+10 4457.72 01-SEP-13:47 31.02 17.52 0.698266E+09 491.81 01-SEP-21:10 26.60 18.09
October 0.496969E+10 4470.45 04-OCT-12:10 24.50 18.64 0.696547E+09 467.71 04-OCT-21:30 16.95 15.74
November 0.231769E+10 4683.14 18-NOV-11:01 6.78 3.82 0.613904E+09 417.53 03-NOV-21:30 6.78 3.82
December 0.149315E+10 5384.71 03-DEC-11:07 6.38 2.27 0.627924E+09 378.96 04-DEC-23:19 8.13 7.50
                     
Annual Sum or Average 0.425256E+11         0.799866E+10        
Minimum of Months 0.105760E+10 2938.37   6.15 0.25 0.567801E+09 364.16   2.12 0.96
Maximum of Months 0.614073E+10 5384.71   34.90 26.10 0.778468E+09 491.82   28.53 20.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.222184E+10 2001.30 19-JAN-23:50 5.60 1.07 0.760202E+09 544.36 19-JAN-22:00 5.60 1.07
February 0.208250E+10 2029.14 18-FEB-16:28 6.15 2.75 0.693511E+09 510.94 22-FEB-22:19 2.20 -1.0
March 0.265072E+10 2108.21 04-MAR-00:15 8.53 6.02 0.820677E+09 555.73 24-MAR-21:40 6.10 5.79
April 0.280657E+10 2254.22 12-APR-22:27 7.20 2.66 0.820807E+09 569.51 07-APR-21:30 7.20 2.66
May 0.318862E+10 2165.37 14-MAY-01:02 8.80 7.21 0.888871E+09 569.54 30-MAY-23:19 18.50 15.89
June 0.349039E+10 2193.43 19-JUN-21:00 28.90 20.74 0.907417E+09 569.54 09-JUN-21:19 28.90 20.74
July 0.383801E+10 2208.17 10-JUL-21:00 27.20 20.22 0.949562E+09 569.54 11-JUL-21:19 22.80 17.52
August 0.397749E+10 2272.90 04-AUG-21:00 32.20 23.82 0.959723E+09 569.67 18-AUG-02:09 25.60 18.92
September 0.343335E+10 2171.67 01-SEP-21:00 26.70 18.23 0.897888E+09 569.54 28-SEP-21:10 16.42 11.03
October 0.327482E+10 3009.21 26-OCT-22:05 7.70 3.58 0.905643E+09 569.53 04-OCT-23:19 7.70 3.58
November 0.258553E+10 2310.65 07-NOV-01:03 7.02 5.17 0.791481E+09 565.75 03-NOV-21:30 7.02 5.17
December 0.242936E+10 1911.46 03-DEC-23:05 6.60 3.13 0.780527E+09 527.27 04-DEC-22:00 8.30 7.50
                     
Annual Sum or Average 0.359792E+11         0.101763E+11        
Minimum of Months 0.208250E+10 1911.46   5.60 1.07 0.693511E+09 510.94   2.20 -1.0
Maximum of Months 0.397749E+10 3009.21   32.20 23.82 0.959723E+09 569.67   28.90 20.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.870848E+09 1726.09 19-JAN-23:50 5.60 1.07 0.152440E+09 98.24 18-JAN-22:10 5.60 1.07
February 0.768347E+09 1401.53 18-FEB-15:46 6.70 3.01 0.137653E+09 93.99 24-FEB-22:10 0.32 -3.7
March 0.178207E+10 1847.98 04-MAR-00:46 7.98 5.94 0.156571E+09 103.29 28-MAR-21:10 8.22 5.85
April 0.230746E+10 1992.30 12-APR-22:27 7.20 2.66 0.157889E+09 111.32 10-APR-21:10 7.20 2.66
May 0.287138E+10 1971.56 14-MAY-01:02 8.80 7.21 0.176831E+09 120.45 31-MAY-21:19 20.37 17.53
June 0.324444E+10 1967.22 19-JUN-21:00 28.90 20.74 0.187439E+09 120.45 20-JUN-21:19 20.93 17.07
July 0.363338E+10 2209.59 10-JUL-20:00 28.30 20.24 0.199240E+09 120.45 11-JUL-21:19 22.80 17.52
August 0.367460E+10 2247.29 17-AUG-20:00 28.90 22.33 0.200503E+09 120.46 30-AUG-21:19 22.43 18.00
September 0.313130E+10 1881.39 01-SEP-20:00 26.70 17.87 0.183554E+09 120.45 14-SEP-21:10 24.13 17.21
October 0.284189E+10 2139.19 26-OCT-22:30 7.50 3.36 0.176610E+09 116.61 05-OCT-21:10 7.50 3.36
November 0.190888E+10 2054.22 07-NOV-01:03 7.02 5.17 0.153854E+09 106.12 03-NOV-21:10 7.02 5.17
December 0.131016E+10 1650.08 03-DEC-23:05 6.60 3.13 0.152858E+09 96.62 04-DEC-22:00 8.30 7.50
                     
Annual Sum or Average 0.283448E+11         0.203544E+10        
Minimum of Months 0.768347E+09 1401.53   5.60 1.07 0.137653E+09 93.99   0.32 -3.7
Maximum of Months 0.367460E+10 2247.29   28.90 22.33 0.200503E+09 120.46   24.13 18.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.194010E+09 814.59 19-JAN-23:50 5.60 1.07 0.116756E+09 71.68 19-JAN-23:49 5.60 1.07
February 0.173555E+09 664.79 24-FEB-16:21 7.25 1.62 0.105503E+09 68.63 28-FEB-22:10 5.22 4.49
March 0.679148E+09 882.97 04-MAR-00:46 7.98 5.94 0.118648E+09 75.15 28-MAR-21:40 7.97 5.50
April 0.102704E+10 940.75 12-APR-22:27 7.20 2.66 0.119016E+09 81.55 10-APR-21:40 7.20 2.66
May 0.135275E+10 934.20 14-MAY-01:02 8.80 7.21 0.132997E+09 88.76 31-MAY-22:10 19.78 17.36
June 0.152676E+10 815.14 22-JUN-18:10 28.72 17.28 0.141590E+09 92.66 19-JUN-21:19 28.72 17.28
July 0.168763E+10 834.80 11-JUL-18:08 26.73 16.72 0.151580E+09 92.66 11-JUL-21:19 22.80 17.52
August 0.170316E+10 874.09 04-AUG-21:00 32.20 23.82 0.152697E+09 92.66 18-AUG-21:00 23.90 17.61
September 0.147691E+10 818.03 01-SEP-18:08 27.70 17.44 0.138606E+09 92.60 01-SEP-21:40 26.30 17.68
October 0.134215E+10 1012.55 26-OCT-22:30 7.50 3.36 0.133087E+09 85.94 05-OCT-22:10 7.50 3.36
November 0.774080E+09 979.73 07-NOV-01:03 7.02 5.17 0.116289E+09 77.89 03-NOV-22:10 7.02 5.17
December 0.352494E+09 779.49 03-DEC-23:05 6.60 3.13 0.116796E+09 70.94 04-DEC-22:00 8.30 7.50
                     
Annual Sum or Average 0.122897E+11         0.154357E+10        
Minimum of Months 0.173555E+09 664.79   5.60 1.07 0.105503E+09 68.63   5.22 1.07
Maximum of Months 0.170316E+10 1012.55   32.20 23.82 0.152697E+09 92.66   28.72 17.68



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.469486E+11 50707.70 03-JAN-20:46 5.87 5.03 0.578074E+09 502.61 19-JAN-23:10 5.60 1.07
February 0.424248E+11 50701.00 01-FEB-20:38 5.60 3.16 0.522180E+09 419.21 28-FEB-22:10 5.22 4.49
March 0.486605E+11 50495.57 20-MAR-19:27 4.70 4.11 0.590140E+09 446.54 20-MAR-21:19 5.00 4.51
April 0.482437E+11 50163.61 13-APR-19:15 5.00 4.66 0.569857E+09 518.86 19-APR-21:40 6.70 3.78
May 0.515070E+11 38626.70 01-MAY-20:20 9.40 5.24 0.591582E+09 415.42 01-MAY-02:39 9.40 5.24
June 0.512672E+11 38917.85 19-JUN-20:00 30.00 22.01 0.574053E+09 382.46 22-JUN-21:10 25.92 16.12
July 0.535536E+11 38870.02 10-JUL-20:00 28.30 20.24 0.593164E+09 381.70 11-JUL-21:19 22.80 17.52
August 0.539562E+11 39016.04 04-AUG-20:00 32.20 24.21 0.595144E+09 381.79 25-AUG-21:10 22.52 14.69
September 0.506930E+11 38752.39 01-SEP-20:00 26.70 17.87 0.572182E+09 388.22 01-SEP-21:10 26.60 18.09
October 0.510269E+11 51194.55 27-OCT-20:14 7.20 3.64 0.590367E+09 492.52 27-OCT-22:40 7.20 3.36
November 0.471800E+11 51648.83 29-NOV-21:50 4.27 3.67 0.570423E+09 485.99 30-NOV-23:40 5.73 2.09
December 0.474892E+11 51124.76 20-DEC-20:26 5.00 1.74 0.581611E+09 456.99 04-DEC-22:30 5.00 1.74
                     
Annual Sum or Average 0.592951E+12         0.692878E+10        
Minimum of Months 0.424248E+11 38626.70   4.27 1.74 0.522180E+09 381.70   5.00 1.07
Maximum of Months 0.539562E+11 51648.83   32.20 24.21 0.595144E+09 518.86   26.60 18.09



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.143534E+11 16682.81 17-JAN-12:30 9.70 5.27 0.875564E+10 6512.51 19-JAN-23:49 5.60 1.07
February 0.142941E+11 16885.66 02-FEB-13:28 6.15 0.25 0.805150E+10 5950.32 22-FEB-22:40 2.20 -0.9
March 0.178005E+11 21774.34 29-MAR-13:31 7.80 5.42 0.948781E+10 6580.01 27-MAR-00:49 7.80 5.42
April 0.184817E+11 14672.54 12-APR-22:27 7.20 2.66 0.938475E+10 6503.96 12-APR-23:10 7.12 2.93
May 0.207873E+11 13645.87 14-MAY-01:02 8.80 7.21 0.101110E+11 6727.33 01-MAY-02:39 8.80 7.21
June 0.223254E+11 12165.10 19-JUN-21:10 28.72 20.62 0.102718E+11 6462.04 26-JUN-04:19 20.60 16.81
July 0.247168E+11 11999.50 10-JUL-21:10 27.12 20.12 0.107523E+11 6462.02 11-JUL-04:19 19.80 15.19
August 0.264648E+11 13747.94 19-AUG-13:00 27.20 15.80 0.108897E+11 6465.09 18-AUG-02:09 27.20 15.80
September 0.234365E+11 15303.21 30-SEP-12:40 20.40 12.36 0.102318E+11 6466.59 29-SEP-23:10 20.40 12.36
October 0.236247E+11 17885.02 08-OCT-09:30 7.75 3.26 0.104475E+11 6750.80 16-OCT-03:49 8.40 7.79
November 0.172604E+11 20025.62 18-NOV-11:01 6.78 3.82 0.910283E+10 6584.07 09-NOV-03:09 6.78 3.82
December 0.158820E+11 22336.11 17-DEC-10:08 8.68 4.02 0.899025E+10 6232.49 04-DEC-00:10 8.68 4.02
                     
Annual Sum or Average 0.239428E+12         0.116477E+12        
Minimum of Months 0.142941E+11 11999.50   6.15 0.25 0.805150E+10 5950.32   2.20 -0.9
Maximum of Months 0.264648E+11 22336.11   28.72 20.62 0.108897E+11 6750.80   27.20 16.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.519169E+11 45976.30 19-JAN-22:50 5.60 1.07 0.275858E+11 19238.26 19-JAN-23:49 5.60 1.07
February 0.483557E+11 41669.74 18-FEB-16:28 6.15 2.75 0.252289E+11 18541.96 22-FEB-23:10 2.20 -0.8
March 0.581293E+11 60311.43 28-MAR-21:57 7.80 5.26 0.296471E+11 19387.02 27-MAR-00:49 7.80 5.26
April 0.604287E+11 65143.00 11-APR-21:49 8.48 1.29 0.292852E+11 19681.48 19-APR-21:40 6.70 3.78
May 0.678379E+11 52077.75 16-MAY-04:15 8.90 7.04 0.313543E+11 19786.48 01-MAY-02:39 8.90 7.04
June 0.734644E+11 42272.40 19-JUN-21:10 28.72 20.62 0.311354E+11 19185.33 04-JUN-23:19 28.72 20.62
July 0.805368E+11 42627.21 10-JUL-21:10 27.12 20.12 0.322582E+11 19185.26 23-JUL-23:19 21.47 20.57
August 0.830865E+11 43844.34 04-AUG-21:10 31.55 23.93 0.325412E+11 19191.03 18-AUG-02:09 25.60 18.92
September 0.733167E+11 42640.86 01-SEP-21:10 26.60 18.09 0.310766E+11 19194.09 29-SEP-23:10 12.02 10.24
October 0.710048E+11 72518.94 21-OCT-05:42 9.18 9.18 0.318360E+11 19972.44 16-OCT-03:49 9.18 9.18
November 0.571322E+11 65370.53 06-NOV-22:27 7.75 5.45 0.286964E+11 19471.13 07-NOV-01:10 7.02 5.17
December 0.548884E+11 45118.47 03-DEC-21:50 6.42 3.42 0.284226E+11 19062.12 04-DEC-22:40 8.13 7.50
                     
Annual Sum or Average 0.780098E+12         0.359068E+12        
Minimum of Months 0.483557E+11 41669.74   5.60 1.07 0.252289E+11 18541.96   2.20 -0.8
Maximum of Months 0.830865E+11 72518.94   31.55 23.93 0.325412E+11 19972.44   28.72 20.62



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 63233586.20 2997.06 19-JAN-16:01 8.22 2.84 93433940.93 56.69 12-JAN-22:00 8.22 2.84
February 87014900.32 3011.53 02-FEB-16:01 4.13 -2.3 84967886.53 56.69 28-FEB-22:10 5.22 4.49
March 0.312890E+09 3105.53 07-MAR-16:01 7.93 4.57 95743787.40 56.69 24-MAR-21:10 6.10 5.64
April 0.685279E+09 3272.28 10-APR-15:02 20.00 11.51 93541893.05 56.69 27-APR-22:10 14.50 12.87
May 0.133324E+10 3320.49 27-MAY-15:02 21.70 11.94 98119870.61 56.70 31-MAY-22:10 19.78 17.36
June 0.219582E+10 3353.35 15-JUN-15:02 26.52 22.45 95708280.06 56.70 22-JUN-22:49 24.50 15.64
July 0.271566E+10 3393.51 13-JUL-15:02 30.32 24.44 99004112.52 56.70 14-JUL-00:10 26.60 22.01
August 0.294559E+10 3433.14 21-AUG-15:02 30.40 23.80 99113515.81 56.70 17-AUG-23:10 30.40 23.80
September 0.183298E+10 3440.34 07-SEP-15:02 26.60 22.96 95318297.96 56.70 01-SEP-23:10 26.60 22.96
October 0.123558E+10 3098.24 04-OCT-15:02 23.72 19.12 97945728.23 56.69 04-OCT-00:10 23.72 19.12
November 0.197203E+09 3073.32 02-NOV-15:01 16.60 8.91 91984702.58 56.69 02-NOV-03:39 16.60 8.91
December 76140362.49 2977.34 17-DEC-16:01 9.82 4.16 93863428.75 56.69 25-DEC-05:49 8.22 8.02
                     
Annual Sum or Average 0.136806E+11         0.113875E+10        
Minimum of Months 63233586.20 2977.34   4.13 -2.3 84967886.53 56.69   5.22 2.84
Maximum of Months 0.294559E+10 3440.34   30.40 24.44 99113515.81 56.70   30.40 23.80



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 35621506.65 1748.28 17-JAN-16:02 9.45 4.59 92681884.31 56.69 03-JAN-04:19 9.45 4.59
February 40168069.86 2641.80 20-FEB-16:02 7.12 4.40 83937165.84 56.69 28-FEB-22:10 5.22 4.49
March 0.178216E+09 2986.36 07-MAR-16:01 7.93 4.57 94687237.18 56.69 04-MAR-04:19 7.93 4.57
April 0.515939E+09 3151.99 10-APR-15:02 20.00 11.51 93044280.81 56.69 27-APR-21:30 14.40 12.98
May 0.122049E+10 3222.78 27-MAY-15:02 21.70 11.94 97965746.80 56.70 31-MAY-22:10 19.78 17.36
June 0.210925E+10 3260.17 15-JUN-15:02 26.52 22.45 95681640.03 56.70 22-JUN-22:49 24.50 15.64
July 0.259727E+10 3282.58 07-JUL-18:02 27.12 23.24 98992419.72 56.70 14-JUL-00:10 26.60 22.01
August 0.264261E+10 3297.62 12-AUG-15:02 28.72 24.51 99048266.11 56.70 21-AUG-23:40 27.20 23.26
September 0.149556E+10 3208.28 07-SEP-15:02 26.60 22.96 95030275.22 56.70 14-SEP-21:19 23.87 17.02
October 0.769521E+09 3140.85 03-OCT-15:02 23.22 19.26 97047401.48 56.69 13-OCT-21:19 15.20 15.20
November 95919349.64 2932.76 03-NOV-15:02 16.83 10.88 90996828.17 56.69 17-NOV-00:00 8.30 7.75
December 41344578.25 1189.52 17-DEC-19:03 7.62 3.39 92783328.41 56.69 25-DEC-05:49 8.22 8.02
                     
Annual Sum or Average 0.117419E+11         0.113190E+10        
Minimum of Months 35621506.65 1189.52   7.12 3.39 83937165.84 56.69   5.22 4.49
Maximum of Months 0.264261E+10 3297.62   28.72 24.51 99048266.11 56.70   27.20 23.26



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.104506E+09 198.05 19-JAN-14:40 9.07 3.63 0.00 0.00 01-JAN-00:10 9.07 3.63
February 0.153722E+09 318.22 20-FEB-13:23 9.15 4.45 0.00 0.00 01-FEB-00:10 9.15 4.45
March 0.241108E+09 486.35 03-MAR-13:30 14.70 8.33 0.00 0.00 01-MAR-00:10 14.70 8.33
April 0.306861E+09 633.66 08-APR-12:30 23.60 16.18 0.00 0.00 01-APR-00:10 23.60 16.18
May 0.408525E+09 509.30 30-MAY-12:50 29.90 17.93 0.00 0.00 01-MAY-00:10 29.90 17.93
June 0.580188E+09 536.34 19-JUN-13:20 34.80 23.85 0.00 0.00 01-JUN-00:10 34.80 23.85
July 0.798393E+09 563.59 10-JUL-13:10 32.30 20.52 0.00 0.00 01-JUL-00:10 32.30 20.52
August 0.919617E+09 698.25 30-AUG-13:00 27.20 15.60 0.00 0.00 01-AUG-00:10 27.20 15.60
September 0.686650E+09 742.82 30-SEP-12:40 20.40 12.36 0.00 0.00 01-SEP-00:10 20.40 12.36
October 0.660289E+09 796.57 04-OCT-12:10 24.50 18.64 0.00 0.00 01-OCT-00:10 24.50 18.64
November 0.275369E+09 648.83 02-NOV-13:00 15.60 8.21 0.00 0.00 01-NOV-00:10 15.60 8.21
December 0.177328E+09 492.07 17-DEC-13:40 12.20 5.18 0.00 0.00 01-DEC-00:10 12.20 5.18
                     
Annual Sum or Average 0.531256E+10         0.00        
Minimum of Months 0.104506E+09 198.05   9.07 3.63 0.00 0.00   9.07 3.63
Maximum of Months 0.919617E+09 796.57   34.80 23.85 0.00 0.00   34.80 23.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 55080492.36 602.00 03-JAN-19:03 7.70 6.60 93836283.16 56.69 12-JAN-22:10 5.10 3.43
February 46105887.59 580.06 01-FEB-19:03 6.02 3.41 84723486.08 56.69 28-FEB-22:10 5.22 4.49
March 0.126525E+09 806.93 28-MAR-15:02 12.80 8.42 95031148.05 56.69 28-MAR-21:10 8.22 5.85
April 0.294948E+09 927.76 08-APR-15:02 20.95 14.84 92847133.12 56.69 07-APR-21:19 20.95 14.84
May 0.568400E+09 996.65 29-MAY-15:02 25.50 17.04 97109775.90 56.69 30-MAY-21:10 19.32 15.31
June 0.796407E+09 1011.01 20-JUN-15:02 26.93 17.32 94710978.00 56.69 19-JUN-22:10 26.93 17.32
July 0.965323E+09 1016.69 11-JUL-15:02 28.30 17.52 98303850.70 56.69 10-JUL-21:00 28.30 17.52
August 0.906293E+09 1015.23 22-AUG-15:02 29.90 17.46 98191683.53 56.69 17-AUG-21:40 29.90 17.46
September 0.622586E+09 993.14 01-SEP-15:02 30.22 17.51 93941217.41 56.69 01-SEP-21:10 26.60 18.09
October 0.367416E+09 890.25 04-OCT-15:02 23.72 19.12 96139805.94 56.69 02-OCT-22:49 23.72 19.12
November 0.143149E+09 807.11 05-NOV-08:62 9.08 6.32 91932706.62 56.69 08-NOV-22:10 11.78 11.28
December 58100455.09 466.82 29-DEC-19:04 5.50 5.21 94014584.55 56.69 25-DEC-05:49 5.50 5.21
                     
Annual Sum or Average 0.495033E+10         0.113078E+10        
Minimum of Months 46105887.59 466.82   5.50 3.41 84723486.08 56.69   5.10 3.43
Maximum of Months 0.965323E+09 1016.69   30.22 19.12 98303850.70 56.69   29.90 19.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 76032245.44 2446.74 19-JAN-09:01 4.97 3.19 93384772.84 56.69 03-JAN-04:19 4.97 3.19
February 96377224.86 2666.67 25-FEB-09:01 -2.0 -5.5 85021258.12 56.69 28-FEB-22:10 5.22 4.49
March 0.282743E+09 2854.21 07-MAR-09:01 6.38 2.56 95809224.31 56.69 24-MAR-21:10 6.10 5.64
April 0.693317E+09 2931.70 10-APR-15:02 20.00 11.51 93786680.74 56.69 06-APR-22:10 20.00 11.51
May 0.137670E+10 3003.40 31-MAY-08:62 23.17 18.85 98305162.99 56.70 31-MAY-21:00 19.90 17.35
June 0.207925E+10 3112.29 23-JUN-08:62 26.70 18.47 95779547.94 56.70 20-JUN-00:10 26.70 18.47
July 0.267386E+10 3082.24 13-JUL-15:02 30.32 24.44 99071325.27 56.70 10-JUL-01:10 30.32 24.44
August 0.291275E+10 3112.89 01-AUG-08:62 26.97 22.14 99207012.93 56.70 03-AUG-00:40 26.87 23.61
September 0.185099E+10 3101.04 07-SEP-15:02 26.60 22.96 95427768.24 56.70 14-SEP-21:30 23.60 16.82
October 0.118948E+10 2969.61 03-OCT-15:02 23.22 19.26 98147952.14 56.69 05-OCT-00:49 16.78 15.39
November 0.245961E+09 2807.85 02-NOV-15:01 16.60 8.91 92218420.56 56.69 03-NOV-21:10 12.80 10.17
December 0.105328E+09 2655.02 20-DEC-09:01 6.47 4.26 93879069.07 56.69 25-DEC-05:49 8.22 8.02
                     
Annual Sum or Average 0.135828E+11         0.114004E+10        
Minimum of Months 76032245.44 2446.74   -2.0 -5.5 85021258.12 56.69   4.97 3.19
Maximum of Months 0.291275E+10 3112.89   30.32 24.44 99207012.93 56.70   30.32 24.44



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 34204778.17 1106.98 26-JAN-09:03 0.87 -2.0 92667079.61 56.69 03-JAN-04:19 0.87 -2.0
February 40449930.97 2146.51 19-FEB-09:01 4.37 2.79 83960472.13 56.69 28-FEB-22:10 5.22 4.49
March 0.155143E+09 2683.05 03-MAR-09:02 10.78 6.54 94657750.78 56.69 04-MAR-04:19 7.40 6.71
April 0.514223E+09 2830.22 08-APR-15:02 20.95 14.84 93348110.74 56.69 07-APR-22:10 20.95 14.84
May 0.125397E+10 2985.42 31-MAY-15:02 25.82 19.50 98248910.62 56.70 31-MAY-21:49 20.02 17.39
June 0.198999E+10 3030.77 23-JUN-08:62 26.70 18.47 95774337.42 56.70 20-JUN-00:10 26.70 18.47
July 0.255459E+10 3043.27 14-JUL-08:62 27.98 20.73 99065149.96 56.70 13-JUL-23:40 27.98 20.73
August 0.260545E+10 3069.06 02-AUG-08:62 28.48 24.65 99193172.36 56.70 17-AUG-23:10 26.70 20.78
September 0.149960E+10 3018.60 01-SEP-08:61 26.20 19.61 95266805.90 56.70 01-SEP-22:00 26.10 16.86
October 0.712248E+09 2732.24 02-OCT-15:02 22.88 16.78 97285796.32 56.69 04-OCT-22:19 17.07 15.80
November 0.121928E+09 2452.06 06-NOV-09:02 7.98 4.28 91201203.73 56.69 17-NOV-00:00 8.30 7.75
December 43563056.49 1035.01 09-DEC-09:03 0.78 -0.9 92801260.34 56.69 25-DEC-05:49 8.22 8.02
                     
Annual Sum or Average 0.115254E+11         0.113347E+10        
Minimum of Months 34204778.17 1035.01   0.78 -2.0 83960472.13 56.69   0.87 -2.0
Maximum of Months 0.260545E+10 3069.06   28.48 24.65 99193172.36 56.70   27.98 20.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.158989E+10 2752.87 19-JAN-23:50 5.60 1.07 0.120112E+10 751.83 19-JAN-23:49 5.60 1.07
February 0.173113E+10 3028.69 18-FEB-16:28 6.15 2.75 0.108630E+10 725.44 22-FEB-22:40 2.20 -0.9
March 0.322689E+10 2988.01 04-MAR-00:46 7.98 5.94 0.123745E+10 783.54 28-MAR-21:40 7.97 5.50
April 0.384586E+10 3303.42 12-APR-22:27 7.20 2.66 0.125931E+10 862.25 10-APR-21:40 7.20 2.66
May 0.468405E+10 3175.12 14-MAY-01:02 8.80 7.21 0.140474E+10 931.08 31-MAY-21:40 20.13 17.44
June 0.523483E+10 2791.10 22-JUN-18:10 28.72 17.28 0.148807E+10 951.84 20-JUN-21:40 28.72 17.28
July 0.576598E+10 3062.38 10-JUL-18:13 29.63 20.43 0.158002E+10 951.85 11-JUL-21:19 22.80 17.52
August 0.594937E+10 3145.04 22-AUG-19:00 26.70 15.84 0.160009E+10 951.89 30-AUG-21:19 22.43 18.00
September 0.510791E+10 2808.28 01-SEP-18:08 27.70 17.44 0.146122E+10 951.83 06-SEP-21:19 22.60 20.77
October 0.475510E+10 3447.02 26-OCT-22:30 7.50 3.36 0.142676E+10 910.51 05-OCT-21:40 7.50 3.36
November 0.302774E+10 3350.37 07-NOV-01:03 7.02 5.17 0.120880E+10 823.08 03-NOV-21:49 7.02 5.17
December 0.214295E+10 2645.78 03-DEC-23:05 6.60 3.13 0.120303E+10 734.95 04-DEC-22:00 8.30 7.50
                     
Annual Sum or Average 0.470617E+11         0.161569E+11        
Minimum of Months 0.158989E+10 2645.78   5.60 1.07 0.108630E+10 725.44   2.20 -0.9
Maximum of Months 0.594937E+10 3447.02   29.63 20.43 0.160009E+10 951.89   28.72 20.77



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 51226360.50 3137.36 19-JAN-16:01 8.22 2.84 93045720.38 56.69 03-JAN-04:19 8.22 2.84
February 77488507.25 3140.42 02-FEB-16:01 4.13 -2.3 84584024.85 56.69 28-FEB-22:10 5.22 4.49
March 0.295212E+09 3248.98 07-MAR-16:01 7.93 4.57 95364856.75 56.69 24-MAR-21:10 6.10 5.64
April 0.657775E+09 3420.07 10-APR-15:02 20.00 11.51 93269849.70 56.69 07-APR-22:30 20.00 11.51
May 0.129083E+10 3476.98 27-MAY-15:02 21.70 11.94 97997941.75 56.70 30-MAY-21:30 19.15 15.12
June 0.219098E+10 3589.54 19-JUN-15:02 32.93 23.30 95647497.48 56.70 20-JUN-21:40 20.77 17.22
July 0.276540E+10 3569.84 07-JUL-15:02 31.73 23.66 98975994.69 56.70 13-JUL-22:00 27.20 23.27
August 0.298615E+10 3601.34 01-AUG-15:02 30.50 22.68 99079798.61 56.70 04-AUG-23:49 28.30 23.48
September 0.175592E+10 3556.16 07-SEP-15:02 26.60 22.96 95192281.39 56.70 01-SEP-22:10 26.60 22.96
October 0.109409E+10 3364.89 04-OCT-15:02 23.72 19.12 97671858.43 56.69 12-OCT-21:49 15.68 15.68
November 0.151812E+09 3205.02 02-NOV-15:01 16.60 8.91 91473650.54 56.69 02-NOV-02:39 16.60 8.91
December 61284774.87 3121.90 17-DEC-16:01 9.82 4.16 93401055.92 56.69 25-DEC-05:49 8.22 8.02
                     
Annual Sum or Average 0.133782E+11         0.113570E+10        
Minimum of Months 51226360.50 3121.90   4.13 -2.3 84584024.85 56.69   5.22 2.84
Maximum of Months 0.298615E+10 3601.34   32.93 23.66 99079798.61 56.70   28.30 23.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 21254829.93 1034.39 20-JAN-16:02 6.93 3.71 92456478.36 56.69 12-JAN-22:00 6.93 3.71
February 27350120.78 2184.20 20-FEB-16:02 7.12 4.40 83692945.14 56.69 28-FEB-22:10 5.22 4.49
March 0.157838E+09 3099.07 07-MAR-16:01 7.93 4.57 94293675.89 56.69 27-MAR-21:10 14.13 10.87
April 0.484093E+09 3284.36 10-APR-15:02 20.00 11.51 92764527.02 56.69 27-APR-21:10 14.40 13.08
May 0.116962E+10 3366.92 27-MAY-15:02 21.70 11.94 97860868.28 56.70 17-MAY-01:00 21.70 11.94
June 0.210048E+10 3362.85 02-JUN-15:02 22.20 12.50 95626181.69 56.70 19-JUN-23:40 25.17 21.12
July 0.264173E+10 3478.61 07-JUL-15:02 31.73 23.66 98965790.44 56.70 13-JUL-22:00 27.20 23.27
August 0.266740E+10 3477.21 04-AUG-15:02 31.02 25.38 99006525.37 56.70 21-AUG-22:40 27.40 23.29
September 0.139606E+10 3318.77 11-SEP-15:02 20.50 12.46 94895031.22 56.70 01-SEP-21:19 20.50 12.46
October 0.633008E+09 3289.54 03-OCT-15:02 23.22 19.26 96653420.93 56.69 19-OCT-21:30 13.30 11.74
November 70130543.68 3013.85 03-NOV-15:02 16.83 10.88 90524961.23 56.69 03-NOV-21:10 12.80 10.17
December 28457176.73 1166.15 08-DEC-16:03 5.92 1.77 92458287.20 56.69 05-DEC-02:49 5.92 1.77
                     
Annual Sum or Average 0.113974E+11         0.112920E+10        
Minimum of Months 21254829.93 1034.39   5.92 1.77 83692945.14 56.69   5.22 1.77
Maximum of Months 0.266740E+10 3478.61   31.73 25.38 99006525.37 56.70   27.40 23.29



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.158385E+09 1709.72 20-JAN-16:01 6.93 3.71 94846913.17 56.69 19-JAN-22:10 6.93 3.71
February 0.212831E+09 1693.98 02-FEB-16:01 4.13 -2.3 86570956.89 56.69 28-FEB-22:10 5.22 4.49
March 0.368655E+09 1713.89 07-MAR-16:01 7.93 4.57 96473868.29 56.69 15-MAR-21:10 9.82 3.29
April 0.504542E+09 1783.54 10-APR-15:02 20.00 11.51 93766446.88 56.69 07-APR-22:10 20.00 11.51
May 0.765961E+09 1804.61 27-MAY-15:02 21.70 11.94 97954413.01 56.69 31-MAY-21:40 20.13 17.44
June 0.118218E+10 1843.16 15-JUN-15:02 26.52 22.45 95504425.35 56.69 19-JUN-23:00 24.40 21.27
July 0.156123E+10 1845.88 16-JUL-15:02 30.50 21.72 98939873.36 56.70 20-JUL-22:00 26.10 24.12
August 0.177383E+10 1896.18 18-AUG-15:02 32.80 20.65 99046718.28 56.70 04-AUG-21:10 32.80 20.65
September 0.130543E+10 1863.40 06-SEP-15:02 26.02 20.15 95314469.23 56.70 02-SEP-00:00 26.02 20.15
October 0.115438E+10 1836.37 04-OCT-15:02 23.72 19.12 98269785.01 56.69 10-OCT-21:10 14.32 14.08
November 0.352419E+09 1718.75 02-NOV-15:01 16.60 8.91 93471869.07 56.69 02-NOV-21:30 12.25 6.94
December 0.245776E+09 1692.27 17-DEC-16:01 9.82 4.16 95449196.71 56.69 04-DEC-23:49 9.82 4.16
                     
Annual Sum or Average 0.958561E+10         0.114561E+10        
Minimum of Months 0.158385E+09 1692.27   4.13 -2.3 86570956.89 56.69   5.22 3.29
Maximum of Months 0.177383E+10 1896.18   32.80 22.45 99046718.28 56.70   32.80 24.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.297929E+11 37322.73 19-JAN-23:50 5.60 1.07 0.184545E+11 12561.08 12-JAN-23:10 5.60 1.07
February 0.267212E+11 27402.85 01-FEB-19:50 5.68 3.21 0.166879E+11 11430.97 28-FEB-22:10 5.22 4.49
March 0.327334E+11 33084.01 11-MAR-23:11 7.20 4.58 0.190280E+11 12740.16 27-MAR-00:49 8.90 8.54
April 0.345871E+11 34557.15 12-APR-22:27 7.20 2.66 0.185032E+11 12803.42 19-APR-21:40 6.70 3.78
May 0.396472E+11 30965.00 16-MAY-03:37 8.90 6.68 0.192791E+11 13234.28 01-MAY-02:39 8.90 6.68
June 0.422180E+11 23718.41 19-JUN-21:20 28.53 20.50 0.187422E+11 11390.78 03-JUN-04:10 28.53 20.50
July 0.454390E+11 23468.51 10-JUL-21:20 27.03 20.02 0.193050E+11 11371.15 25-JUL-21:19 22.60 20.76
August 0.451141E+11 23825.34 04-AUG-21:20 30.90 23.99 0.193798E+11 11381.72 15-AUG-21:19 24.03 21.25
September 0.399321E+11 24860.44 24-SEP-05:36 10.20 8.63 0.186612E+11 11629.27 29-SEP-03:30 11.95 8.45
October 0.373097E+11 36520.12 26-OCT-22:59 7.20 3.02 0.191664E+11 12777.13 27-OCT-22:40 7.20 3.36
November 0.316970E+11 38099.89 06-NOV-23:42 7.20 5.19 0.182683E+11 13451.73 30-NOV-23:40 5.73 2.09
December 0.305401E+11 30975.27 04-DEC-23:34 7.97 7.50 0.186859E+11 12335.99 04-DEC-23:19 7.97 7.50
                     
Annual Sum or Average 0.435732E+12         0.224162E+12        
Minimum of Months 0.267212E+11 23468.51   5.60 1.07 0.166879E+11 11371.15   5.22 1.07
Maximum of Months 0.454390E+11 38099.89   30.90 23.99 0.193798E+11 13451.73   28.53 21.25



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.331103E+11 39382.16 19-JAN-23:50 5.60 1.07 0.187681E+11 12710.09 12-JAN-23:10 5.60 1.07
February 0.296882E+11 31706.19 01-FEB-19:38 5.77 3.26 0.169650E+11 11455.69 28-FEB-22:10 5.22 4.49
March 0.363985E+11 34803.46 11-MAR-23:11 7.20 4.58 0.192035E+11 12851.00 27-MAR-00:49 8.90 8.54
April 0.381157E+11 37689.71 12-APR-22:27 7.20 2.66 0.186261E+11 12916.55 19-APR-21:40 6.70 3.78
May 0.431351E+11 32920.33 15-MAY-05:47 9.13 7.09 0.193228E+11 13334.68 01-MAY-02:39 9.13 7.09
June 0.451154E+11 24925.96 19-JUN-21:20 28.53 20.50 0.187547E+11 11392.41 03-JUN-04:10 28.53 20.50
July 0.482704E+11 24634.72 10-JUL-21:20 27.03 20.02 0.193086E+11 11382.25 25-JUL-21:19 22.60 20.76
August 0.479015E+11 24997.59 04-AUG-21:20 30.90 23.99 0.193872E+11 11390.04 15-AUG-21:19 24.03 21.25
September 0.428788E+11 27452.14 24-SEP-05:36 10.20 8.63 0.186886E+11 11641.19 29-SEP-03:30 11.95 8.45
October 0.405729E+11 37121.84 26-OCT-22:59 7.20 3.02 0.192453E+11 12851.37 27-OCT-22:40 7.20 3.36
November 0.351539E+11 36241.84 06-NOV-23:42 7.20 5.19 0.184537E+11 13581.99 30-NOV-23:40 5.73 2.09
December 0.340362E+11 32732.11 04-DEC-23:34 7.97 7.50 0.189174E+11 12444.52 04-DEC-23:19 7.97 7.50
                     
Annual Sum or Average 0.474377E+12         0.225641E+12        
Minimum of Months 0.296882E+11 24634.72   5.60 1.07 0.169650E+11 11382.25   5.22 1.07
Maximum of Months 0.482704E+11 39382.16   30.90 23.99 0.193872E+11 13581.99   28.53 21.25



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.470724E+11 38400.91 19-JAN-23:50 5.60 1.07 0.187901E+11 11474.73 21-JAN-18:40 7.20 6.67
February 0.427104E+11 37508.55 18-FEB-16:28 6.15 2.75 0.169691E+11 11341.87 16-FEB-18:40 6.15 2.75
March 0.500855E+11 36665.68 29-MAR-15:51 7.20 4.88 0.188312E+11 11430.24 04-MAR-18:49 7.20 4.88
April 0.508421E+11 35598.79 19-APR-09:21 8.05 3.80 0.182285E+11 11406.73 01-APR-17:40 8.05 3.80
May 0.554392E+11 32986.96 15-MAY-05:54 9.40 7.22 0.188462E+11 11319.66 13-MAY-17:19 9.40 7.22
June 0.559221E+11 32864.94 22-JUN-18:10 28.72 17.28 0.182548E+11 11319.69 17-JUN-17:19 28.72 17.28
July 0.590982E+11 32413.64 11-JUL-18:08 26.73 16.72 0.188615E+11 11319.69 01-JUL-17:19 26.73 16.72
August 0.593519E+11 34838.51 24-AUG-16:57 33.30 18.04 0.188694E+11 11319.69 19-AUG-17:19 33.30 18.04
September 0.547658E+11 31476.78 01-SEP-18:08 27.70 17.44 0.182433E+11 11319.66 02-SEP-17:19 22.93 18.77
October 0.539628E+11 35655.36 27-OCT-07:40 6.83 3.85 0.188387E+11 11472.66 28-OCT-17:30 8.85 2.90
November 0.482018E+11 40163.50 30-NOV-13:52 6.70 3.52 0.182168E+11 11548.04 18-NOV-18:00 6.70 3.52
December 0.479115E+11 36135.94 04-DEC-17:11 7.57 6.79 0.188029E+11 11442.49 16-DEC-18:00 6.70 2.70
                     
Annual Sum or Average 0.625364E+12         0.221752E+12        
Minimum of Months 0.427104E+11 31476.78   5.60 1.07 0.169691E+11 11319.66   6.15 2.70
Maximum of Months 0.593519E+11 40163.50   33.30 18.04 0.188694E+11 11548.04   33.30 18.77



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.243984E+10 5736.76 19-JAN-12:07 7.57 3.88 0.127018E+10 787.98 19-JAN-23:49 5.60 1.07
February 0.248928E+10 6291.45 18-FEB-16:28 6.15 2.75 0.114914E+10 747.18 28-FEB-22:10 5.22 4.49
March 0.584139E+10 6099.13 04-MAR-00:46 7.98 5.94 0.130223E+10 833.27 27-MAR-21:40 13.33 10.26
April 0.759312E+10 6496.83 12-APR-22:27 7.20 2.66 0.131712E+10 919.65 07-APR-21:30 7.20 2.66
May 0.967060E+10 6403.05 14-MAY-01:02 8.80 7.21 0.147578E+10 998.19 31-MAY-21:30 20.25 17.49
June 0.110323E+11 6746.65 19-JUN-14:10 34.22 23.63 0.157454E+10 1007.40 20-JUN-21:19 20.93 17.07
July 0.124961E+11 7130.15 08-JUL-12:00 32.20 26.10 0.167436E+10 1007.40 11-JUL-21:19 22.80 17.52
August 0.128369E+11 7302.76 16-AUG-12:50 31.93 25.44 0.168065E+10 1007.41 30-AUG-21:40 22.07 17.86
September 0.105316E+11 6681.40 01-SEP-14:10 31.02 17.36 0.152334E+10 1007.39 07-SEP-21:19 23.70 21.42
October 0.936682E+10 6812.62 26-OCT-22:30 7.50 3.36 0.145411E+10 955.55 05-OCT-21:40 7.50 3.36
November 0.560035E+10 6638.32 07-NOV-01:03 7.02 5.17 0.125687E+10 842.97 03-NOV-21:40 7.02 5.17
December 0.345014E+10 5329.29 03-DEC-23:05 6.60 3.13 0.127165E+10 773.12 04-DEC-22:00 8.30 7.50
                     
Annual Sum or Average 0.933484E+11         0.169500E+11        
Minimum of Months 0.243984E+10 5329.29   6.15 2.66 0.114914E+10 747.18   5.22 1.07
Maximum of Months 0.128369E+11 7302.76   34.22 26.10 0.168065E+10 1007.41   23.70 21.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 40848.68 408.49 19-JAN-23:48 5.60
February 1145626.16 1364.98 24-FEB-16:15 7.43
March 11917031.12 1951.84 20-MAR-15:07 6.20
April 13747559.98 1985.68 20-APR-06:19 6.70
May 7841370.04 1696.81 15-MAY-02:38 7.57
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 1157088.81 2843.86 27-OCT-22:30 7.20
November 516552.86 2351.61 07-NOV-00:43 7.20
December 5841.96 97.37 17-DEC-09:12 6.50
         
Annual Sum or Average 36371919.61      
Minimum of Months 0.00 0.00   5.60
Maximum of Months 13747559.98 2843.86   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.524379E+09 1435.11 02-JAN-07:10 -11.6
February 0.355748E+09 1370.39 06-FEB-05:00 -13.3
March 63607545.46 726.76 27-MAR-05:50 8.22
April 16270450.36 775.99 20-APR-06:19 6.70
May 4840605.19 661.91 15-MAY-02:38 7.57
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 25012.17 149.86 24-SEP-05:16 10.40
October 7426906.93 807.33 27-OCT-22:30 7.20
November 66175306.03 913.77 30-NOV-13:53 6.70
December 0.231111E+09 925.15 25-DEC-05:55 8.30
         
Annual Sum or Average 0.126958E+10      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.524379E+09 1435.11   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 705231.24 324.70 15-JAN-11:25 7.50
February 487323.57 319.48 19-FEB-09:45 6.23
March 3110423.80 276.94 20-MAR-15:07 6.20
April 2086952.66 360.31 02-APR-08:59 6.70
May 412922.00 99.17 02-MAY-03:50 8.30
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 841154.61 217.41 29-OCT-07:41 5.95
November 4838676.73 331.28 27-NOV-07:15 7.40
December 2058553.31 361.96 25-DEC-05:45 8.22
         
Annual Sum or Average 14541237.92      
Minimum of Months 0.00 0.00   5.95
Maximum of Months 4838676.73 361.96   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.115763E+09 616.01 02-JAN-04:50 -12.1
February 0.135161E+09 579.70 06-FEB-05:00 -13.3
March 9237302.18 429.27 12-MAR-08:40 7.07
April 5494087.02 439.12 02-APR-08:59 6.70
May 1705056.88 284.92 02-MAY-03:55 8.30
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 3043116.66 390.86 27-OCT-22:30 7.20
November 11634518.03 448.58 07-NOV-00:43 7.20
December 6088142.83 453.20 17-DEC-09:12 6.50
         
Annual Sum or Average 0.288126E+09      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.135161E+09 616.01   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.223987E+09 478.83 02-JAN-05:00 -12.2
February 0.213874E+09 466.67 06-FEB-10:05 -11.0
March 14369588.52 217.86 26-MAR-06:20 6.87
April 3183569.94 227.13 20-APR-06:19 6.70
May 953954.77 151.64 02-MAY-00:33 8.90
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 1818397.46 217.54 27-OCT-22:30 7.20
November 20676463.97 653.53 30-NOV-13:53 6.70
December 39001137.92 245.61 31-DEC-18:00 -5.0
         
Annual Sum or Average 0.517864E+09      
Minimum of Months 0.00 0.00   -12.2
Maximum of Months 0.223987E+09 653.53   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -9.6
February 0.00 0.00 01-FEB-00:03 -1.1
March 775170.67 2337.54 27-MAR-03:06 8.22
April 583845.65 2489.67 11-APR-02:06 8.03
May 571141.33 2423.82 15-MAY-02:38 7.57
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 890586.50 3199.48 16-OCT-03:24 8.60
November 2772866.14 3147.86 02-NOV-03:30 7.50
December 271993.46 1820.22 05-DEC-02:14 7.80
         
Annual Sum or Average 5865603.74      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 2772866.14 3199.48   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 8961524.73 2162.95 22-JAN-19:46 6.10
February 906714.71 1378.56 16-FEB-16:25 6.95
March 11466268.57 2053.95 06-MAR-07:10 8.58
April 11205370.96 2346.75 20-APR-06:19 6.70
May 563288.15 1214.03 01-MAY-06:30 8.60
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 3454959.93 1680.46 27-OCT-06:55 6.10
November 19024754.84 2794.02 13-NOV-08:23 6.40
December 6698770.01 2113.03 26-DEC-07:58 6.70
         
Annual Sum or Average 62281651.89      
Minimum of Months 0.00 0.00   6.10
Maximum of Months 19024754.84 2794.02   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 3716546.86 4992.73 15-JAN-11:25 7.50
February 4165410.90 4127.90 16-FEB-16:25 6.95
March 18747621.34 3613.57 25-MAR-14:35 7.20
April 13459305.97 4900.64 02-APR-08:59 6.70
May 59778.20 293.25 01-MAY-06:30 8.60
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 4042724.34 4987.23 27-OCT-22:30 7.20
November 25380805.99 5051.70 13-NOV-08:23 6.40
December 15204371.13 4293.77 25-DEC-05:45 8.22
         
Annual Sum or Average 84776564.72      
Minimum of Months 0.00 0.00   6.40
Maximum of Months 25380805.99 5051.70   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.129752E+10 2690.73 02-JAN-09:01 -10.3
February 0.106096E+10 2697.70 06-FEB-19:01 -8.2
March 0.467797E+09 2622.87 17-MAR-08:61 -1.1
April 0.187960E+09 2533.08 01-APR-08:61 5.18
May 6913881.28 795.33 29-MAY-08:04 24.27
June 655134.68 752.75 22-JUN-08:04 24.60
July 588495.37 471.35 27-JUL-08:05 24.60
August 618735.52 471.68 06-AUG-08:05 22.12
September 1185589.48 660.13 23-SEP-08:04 13.30
October 26329214.97 1424.25 27-OCT-08:61 7.48
November 0.544234E+09 2615.45 25-NOV-09:01 -0.3
December 0.100902E+10 2667.66 31-DEC-19:01 -5.7
         
Annual Sum or Average 0.460377E+10      
Minimum of Months 588495.37 471.35   -10.3
Maximum of Months 0.129752E+10 2697.70   24.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.154973E+10 2706.49 02-JAN-09:01 -10.3
February 0.137369E+10 2711.08 06-FEB-09:01 -12.0
March 0.615379E+09 2618.29 22-MAR-08:61 -2.0
April 0.222861E+09 2532.84 03-APR-08:61 5.68
May 7827004.72 767.52 30-MAY-08:04 25.18
June 664248.71 796.33 04-JUN-08:04 22.38
July 516645.33 522.01 27-JUL-08:05 24.60
August 686028.83 510.30 10-AUG-08:05 24.18
September 1763165.20 733.73 23-SEP-15:04 16.60
October 59426497.20 2527.64 27-OCT-08:61 7.48
November 0.715527E+09 2631.32 24-NOV-09:01 -1.5
December 0.127456E+10 2668.65 31-DEC-19:01 -5.7
         
Annual Sum or Average 0.582262E+10      
Minimum of Months 516645.33 510.30   -12.0
Maximum of Months 0.154973E+10 2711.08   25.18



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 83582087.97 253.20 02-JAN-05:00 -12.2
February 24889693.23 205.24 07-FEB-06:00 -9.4
March 2536155.22 107.42 01-MAR-06:00 3.90
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:05 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 743629.93 53.99 29-NOV-05:00 3.90
December 30948524.69 183.58 31-DEC-06:00 -1.7
         
Annual Sum or Average 0.142700E+09      
Minimum of Months 0.00 0.00   -12.2
Maximum of Months 83582087.97 253.20   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.235750E+09 792.96 02-JAN-16:01 -6.0
February 0.234877E+09 794.16 06-FEB-16:01 -7.1
March 52742906.16 759.21 16-MAR-15:01 0.68
April 3582236.93 721.78 03-APR-08:61 5.68
May 611998.84 405.50 03-MAY-15:07 15.92
June 100248.94 169.14 20-JUN-08:07 25.28
July 49202.84 93.17 14-JUL-08:07 27.98
August 120747.76 184.78 30-AUG-08:05 22.30
September 330765.23 245.56 24-SEP-15:05 17.70
October 1220545.33 465.02 21-OCT-18:03 17.12
November 58246714.86 763.39 24-NOV-16:01 1.20
December 0.155163E+09 777.49 31-DEC-16:01 -3.1
         
Annual Sum or Average 0.742796E+09      
Minimum of Months 49202.84 93.17   -7.1
Maximum of Months 0.235750E+09 794.16   27.98



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.128701E+10 2632.94 14-JAN-16:02 -6.1
February 0.103410E+10 2631.83 06-FEB-19:01 -8.2
March 0.498015E+09 2563.80 17-MAR-08:61 -1.1
April 0.191092E+09 2479.01 21-APR-15:01 7.30
May 7273324.44 700.64 05-MAY-15:04 18.12
June 334913.29 408.32 17-JUN-08:05 20.68
July 155635.07 455.02 31-JUL-08:05 25.68
August 45595.37 296.37 06-AUG-18:05 20.00
September 987323.15 641.89 23-SEP-08:04 13.30
October 28399682.31 837.94 31-OCT-15:02 13.30
November 0.510249E+09 2559.78 30-NOV-19:01 5.00
December 0.995587E+09 2614.10 31-DEC-19:01 -5.7
         
Annual Sum or Average 0.455325E+10      
Minimum of Months 45595.37 296.37   -8.2
Maximum of Months 0.128701E+10 2632.94   25.68



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.153050E+10 2639.35 02-JAN-16:01 -6.0
February 0.133357E+10 2636.98 06-FEB-16:01 -7.1
March 0.648117E+09 2557.08 17-MAR-08:61 -1.1
April 0.224405E+09 2476.65 01-APR-15:01 6.28
May 8334929.85 690.35 04-MAY-08:63 11.20
June 219425.82 416.80 17-JUN-08:05 20.68
July 125313.21 403.65 31-JUL-08:05 25.68
August 33884.19 278.15 06-AUG-18:05 20.00
September 1059005.87 629.15 23-SEP-15:04 16.60
October 60941812.48 1706.27 31-OCT-15:02 13.30
November 0.653353E+09 2563.46 30-NOV-19:01 5.00
December 0.123463E+10 2613.95 31-DEC-19:01 -5.7
         
Annual Sum or Average 0.569530E+10      
Minimum of Months 33884.19 278.15   -7.1
Maximum of Months 0.153050E+10 2639.35   25.68



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 81147408.39 816.55 14-JAN-16:30 -6.1
February 38135638.15 698.83 20-FEB-09:39 6.67
March 14556021.78 701.10 26-MAR-06:20 6.87
April 8623225.81 712.80 20-APR-06:19 6.70
May 2487384.03 428.62 02-MAY-03:55 8.30
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 4239777.19 607.78 27-OCT-22:30 7.20
November 19124037.29 1426.81 30-NOV-13:53 6.70
December 27244627.04 719.15 25-DEC-05:45 8.22
         
Annual Sum or Average 0.195558E+09      
Minimum of Months 0.00 0.00   -6.1
Maximum of Months 81147408.39 1426.81   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.183249E+10 3152.23 02-JAN-09:01 -10.3
February 0.153174E+10 3160.19 06-FEB-19:01 -8.2
March 0.752082E+09 3056.54 17-MAR-08:61 -1.1
April 0.341097E+09 2974.88 01-APR-08:61 5.18
May 27940851.22 1274.85 01-MAY-08:62 12.48
June 648598.07 750.53 26-JUN-08:04 24.08
July 702127.05 532.98 01-JUL-08:04 24.18
August 617605.32 483.79 27-AUG-08:05 23.07
September 4079250.81 910.04 23-SEP-15:04 16.60
October 92810020.04 2952.58 27-OCT-08:61 7.48
November 0.861578E+09 3061.79 30-NOV-19:01 5.00
December 0.147776E+10 3116.80 31-DEC-19:01 -5.7
         
Annual Sum or Average 0.692354E+10      
Minimum of Months 617605.32 483.79   -10.3
Maximum of Months 0.183249E+10 3160.19   24.18



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.213937E+10 3164.22 02-JAN-09:01 -10.3
February 0.190746E+10 3170.45 06-FEB-09:01 -12.0
March 0.946777E+09 3052.92 22-MAR-08:61 -2.0
April 0.394903E+09 2970.74 03-APR-08:61 5.68
May 30558605.14 1444.52 01-MAY-08:62 12.48
June 680086.15 739.19 22-JUN-08:04 24.60
July 663819.62 532.00 28-JUL-08:05 23.80
August 658592.54 482.27 27-AUG-08:05 23.07
September 5386667.41 916.15 23-SEP-15:04 16.60
October 0.170547E+09 2991.62 27-OCT-08:61 7.48
November 0.110095E+10 3064.63 24-NOV-09:01 -1.5
December 0.180907E+10 3120.98 31-DEC-19:01 -5.7
         
Annual Sum or Average 0.850702E+10      
Minimum of Months 658592.54 482.27   -12.0
Maximum of Months 0.213937E+10 3170.45   24.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.572067E+09 1647.11 14-JAN-16:02 -6.1
February 0.409078E+09 1629.63 06-FEB-19:01 -8.2
March 0.198072E+09 1600.22 17-MAR-08:61 -1.1
April 87793929.12 1546.92 21-APR-15:01 7.30
May 3091594.66 399.20 03-MAY-15:07 15.92
June 403503.69 528.94 22-JUN-08:04 24.60
July 431844.78 375.53 12-JUL-08:05 26.28
August 355965.21 365.12 01-AUG-08:05 26.97
September 319546.01 418.73 23-SEP-08:04 13.30
October 5386248.34 521.22 27-OCT-18:03 8.80
November 0.173188E+09 1571.64 25-NOV-09:01 -0.3
December 0.402527E+09 1603.88 11-DEC-16:01 1.10
         
Annual Sum or Average 0.185271E+10      
Minimum of Months 319546.01 365.12   -8.2
Maximum of Months 0.572067E+09 1647.11   26.97



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -9.6
February 0.00 0.00 01-FEB-00:03 -1.1
March 43048.55 274.57 02-MAR-08:34 7.03
April 20119.02 335.32 20-APR-06:19 6.70
May 0.00 0.00 01-MAY-00:05 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 118577.97 555.18 27-OCT-21:47 7.20
November 24691.08 411.52 13-NOV-08:23 6.40
December 27899.77 260.52 17-DEC-09:12 6.50
         
Annual Sum or Average 234336.39      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 118577.97 555.18   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -9.6
February 0.00 0.00 01-FEB-00:03 -1.1
March 0.00 0.00 01-MAR-00:03 5.52
April 8676.60 144.61 20-APR-06:19 6.70
May 0.00 0.00 01-MAY-00:05 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 78427.70 468.89 27-OCT-21:47 7.20
November 11754.25 195.90 13-NOV-08:23 6.40
December 0.00 0.00 01-DEC-00:03 5.97
         
Annual Sum or Average 98858.56      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 78427.70 468.89   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -9.6
February 0.00 0.00 01-FEB-00:03 -1.1
March 0.00 0.00 01-MAR-00:03 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:05 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 22463.35 374.39 18-OCT-01:46 7.80
November 2333.97 38.90 02-NOV-02:26 8.05
December 0.00 0.00 01-DEC-00:03 5.97
         
Annual Sum or Average 24797.32      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 22463.35 374.39   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.467220E+09 2523.12 02-JAN-07:10 -11.6
February 0.363164E+09 2462.73 06-FEB-07:10 -13.2
March 33420685.44 1488.78 26-MAR-06:20 6.87
April 19984310.94 1574.28 20-APR-06:19 6.70
May 6193781.55 994.89 02-MAY-04:13 8.30
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 255.97 3.41 24-SEP-05:16 10.40
October 13444869.63 1518.03 27-OCT-22:30 7.20
November 62109063.29 1617.10 07-NOV-00:43 7.20
December 44533376.20 1500.23 25-DEC-22:44 6.70
         
Annual Sum or Average 0.101007E+10      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.467220E+09 2523.12   23.90



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.147273E+11 14185.34 02-JAN-20:10 0.127587E+11 10113.80 02-JAN-20:10
February 0.132974E+11 14185.34 01-FEB-20:10 0.115208E+11 10113.80 01-FEB-20:10
March 0.147727E+11 14185.34 01-MAR-20:10 0.127855E+11 10113.80 01-MAR-20:10
April 0.142280E+11 14185.34 03-APR-19:10 0.123314E+11 10113.80 03-APR-19:10
May 0.147528E+11 14185.34 01-MAY-19:10 0.127741E+11 10113.80 01-MAY-19:10
June 0.142932E+11 14185.34 01-JUN-19:10 0.123716E+11 10113.80 01-JUN-19:10
July 0.146876E+11 14185.34 03-JUL-19:10 0.127338E+11 10113.80 03-JUL-19:10
August 0.147784E+11 14185.34 01-AUG-19:10 0.127894E+11 10113.80 01-AUG-19:10
September 0.142337E+11 14185.34 01-SEP-19:10 0.123352E+11 10113.80 01-SEP-19:10
October 0.147216E+11 14185.34 02-OCT-19:10 0.127549E+11 10113.80 02-OCT-19:10
November 0.142819E+11 14185.34 01-NOV-19:10 0.123659E+11 10113.80 01-NOV-19:10
December 0.146876E+11 14185.34 01-DEC-20:10 0.127338E+11 10113.80 01-DEC-20:10
             
Annual Sum or Average 0.173462E+12     0.150255E+12    
Minimum of Months 0.132974E+11 14185.34   0.115208E+11 10113.80  
Maximum of Months 0.147784E+11 14185.34   0.127894E+11 10113.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.731324E+09 704.41 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.660319E+09 704.41 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.733578E+09 704.41 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.706528E+09 704.41 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.732592E+09 704.41 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.709769E+09 704.41 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.729351E+09 704.41 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.733860E+09 704.41 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.706810E+09 704.41 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.731042E+09 704.41 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.709205E+09 704.41 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.729351E+09 704.41 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.861373E+10     0.101856E+11    
Minimum of Months 0.660319E+09 704.41   0.780982E+09 685.60  
Maximum of Months 0.733860E+09 704.41   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.846876E+09 815.72 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.764651E+09 815.72 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.849486E+09 815.72 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.818162E+09 815.72 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.848344E+09 815.72 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.821915E+09 815.72 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.844592E+09 815.72 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.849812E+09 815.72 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.818489E+09 815.72 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.846549E+09 815.72 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.821262E+09 815.72 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.844592E+09 815.72 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.997473E+10     0.117950E+11    
Minimum of Months 0.764651E+09 815.72   0.904380E+09 793.93  
Maximum of Months 0.849812E+09 815.72   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.141236E+10 1360.40 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.127524E+10 1360.40 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.141672E+10 1360.40 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.136448E+10 1360.40 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.141481E+10 1360.40 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.137074E+10 1360.40 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.140855E+10 1360.40 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.141726E+10 1360.40 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.136502E+10 1360.40 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.141182E+10 1360.40 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.136965E+10 1360.40 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.140855E+10 1360.40 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.166352E+11     0.124712E+11    
Minimum of Months 0.127524E+10 1360.40   0.956227E+09 839.45  
Maximum of Months 0.141726E+10 1360.40   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.236418E+09 227.72 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.213464E+09 227.72 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.237147E+09 227.72 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.228402E+09 227.72 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.236828E+09 227.72 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.229450E+09 227.72 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.235780E+09 227.72 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.237238E+09 227.72 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.228493E+09 227.72 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.236327E+09 227.72 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.229268E+09 227.72 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.235780E+09 227.72 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.278459E+10     0.359760E+10    
Minimum of Months 0.213464E+09 227.72   0.275845E+09 242.16  
Maximum of Months 0.237238E+09 227.72   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.370859E+09 357.21 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.334852E+09 357.21 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.372002E+09 357.21 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.358285E+09 357.21 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.371502E+09 357.21 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.359929E+09 357.21 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.369859E+09 357.21 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.372145E+09 357.21 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.358428E+09 357.21 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.370717E+09 357.21 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.359643E+09 357.21 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.369859E+09 357.21 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.436808E+10     0.679355E+11    
Minimum of Months 0.334852E+09 357.21   0.520895E+10 4572.80  
Maximum of Months 0.372145E+09 357.21   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.161485E+10 1761.91 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.142581E+10 1761.91 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.154426E+10 1761.91 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.144251E+10 1761.91 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.143957E+10 1761.91 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.137211E+10 1761.91 01-JUN-19:19 0.118076E+10 965.27 01-JUN-19:10
July 0.141436E+10 1761.91 03-JUL-19:19 0.121533E+10 965.27 03-JUL-19:10
August 0.147541E+10 1761.91 01-AUG-19:10 0.122063E+10 965.27 01-AUG-19:10
September 0.147004E+10 1761.91 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.157141E+10 1761.91 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.154685E+10 1761.91 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.160913E+10 1761.91 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.179263E+11     0.143405E+11    
Minimum of Months 0.137211E+10 1761.91   0.109956E+10 965.27  
Maximum of Months 0.161485E+10 1761.91   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104401E+11 10265.18 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.939242E+10 10265.18 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.103944E+11 10265.18 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.996917E+10 10265.18 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.102791E+11 10265.18 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.993906E+10 10265.18 01-JUN-19:10 0.122682E+11 10029.21 01-JUN-19:10
July 0.102179E+11 10265.18 03-JUL-19:19 0.126273E+11 10029.21 03-JUL-19:10
August 0.103290E+11 10265.18 01-AUG-19:10 0.126824E+11 10029.21 01-AUG-19:10
September 0.999889E+10 10265.18 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.103905E+11 10265.18 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.101030E+11 10265.18 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.104094E+11 10265.18 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.121863E+12     0.148998E+12    
Minimum of Months 0.939242E+10 10265.18   0.114244E+11 10029.21  
Maximum of Months 0.104401E+11 10265.18   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85091918.49 76.99 01-JAN-19:10 0.255708E+09 232.19 01-JAN-08:09
February 76846309.13 76.99 01-FEB-20:10 0.230956E+09 232.19 01-FEB-07:10
March 84415649.14 76.99 01-MAR-20:10 0.255355E+09 232.19 01-MAR-07:10
April 82445007.08 76.99 01-APR-18:10 0.247516E+09 232.19 01-APR-07:10
May 84753783.81 76.99 01-MAY-19:10 0.255532E+09 232.19 01-MAY-06:10
June 81790910.76 76.99 01-JUN-19:10 0.247163E+09 232.19 01-JUN-06:10
July 85418966.65 76.99 01-JUL-18:10 0.255885E+09 232.19 01-JUL-07:10
August 84415649.14 76.99 01-AUG-19:10 0.255355E+09 232.19 01-AUG-06:10
September 82467180.11 76.99 01-SEP-19:10 0.247516E+09 232.19 01-SEP-06:10
October 85080831.98 76.99 01-OCT-18:10 0.255708E+09 232.19 01-OCT-07:10
November 82117958.92 76.99 01-NOV-19:10 0.247340E+09 232.19 01-NOV-06:10
December 85430053.17 76.99 01-DEC-20:10 0.255885E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.100027E+10     0.300992E+10    
Minimum of Months 76846309.13 76.99   0.230956E+09 232.19  
Maximum of Months 85430053.17 76.99   0.255885E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85115186.72 77.01 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 76867322.62 77.01 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 84438732.44 77.01 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 82467551.52 77.01 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 84776959.58 77.01 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 81813276.33 77.01 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 85442324.32 77.01 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 84438732.44 77.01 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 82489730.61 77.01 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 85104097.18 77.01 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 82140413.93 77.01 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 85453413.86 77.01 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.100055E+10     0.301074E+10    
Minimum of Months 76867322.62 77.01   0.231020E+09 232.26  
Maximum of Months 85453413.86 77.01   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.232638E+10 2240.78 02-JAN-20:10 0.00 0.00
February 0.210051E+10 2240.78 01-FEB-20:10 0.00 0.00
March 0.233355E+10 2240.78 01-MAR-20:10 0.00 0.00
April 0.224750E+10 2240.78 03-APR-19:10 0.00 0.00
May 0.233041E+10 2240.78 01-MAY-19:10 0.00 0.00
June 0.225781E+10 2240.78 01-JUN-19:10 0.00 0.00
July 0.232011E+10 2240.78 03-JUL-19:10 0.00 0.00
August 0.233445E+10 2240.78 01-AUG-19:10 0.00 0.00
September 0.224840E+10 2240.78 01-SEP-19:10 0.00 0.00
October 0.232548E+10 2240.78 02-OCT-19:10 0.00 0.00
November 0.225602E+10 2240.78 01-NOV-19:10 0.00 0.00
December 0.232011E+10 2240.78 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.274007E+11     0.00 0.00
Minimum of Months 0.210051E+10 2240.78   0.00 0.00
Maximum of Months 0.233445E+10 2240.78   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85115186.72 77.01 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 76867322.62 77.01 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 84438732.44 77.01 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 82467551.52 77.01 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 84776959.58 77.01 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 81813276.33 77.01 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 85442324.32 77.01 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 84438732.44 77.01 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 82489730.61 77.01 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 85104097.18 77.01 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 82140413.93 77.01 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 85453413.86 77.01 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.100055E+10     0.301074E+10    
Minimum of Months 76867322.62 77.01   0.231020E+09 232.26  
Maximum of Months 85453413.86 77.01   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.303429E+10 3094.06 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.270887E+10 3094.06 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.296851E+10 3094.06 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.281177E+10 3094.06 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.285834E+10 3094.06 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.274883E+10 3094.06 01-JUN-19:19 0.144540E+11 6747.90 01-JUN-06:10
July 0.282901E+10 3094.06 03-JUL-19:30 0.149358E+11 6747.90 01-JUL-06:10
August 0.289613E+10 3094.06 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.284038E+10 3094.06 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.298860E+10 3094.06 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.292070E+10 3094.06 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.302980E+10 3094.06 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.346352E+11     0.175857E+12    
Minimum of Months 0.270887E+10 3094.06   0.134904E+11 6747.90  
Maximum of Months 0.303429E+10 3094.06   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.303429E+10 3094.06 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.270887E+10 3094.06 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.296851E+10 3094.06 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.281177E+10 3094.06 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.285834E+10 3094.06 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.274883E+10 3094.06 01-JUN-19:19 0.144540E+11 6747.90 01-JUN-06:10
July 0.282901E+10 3094.06 03-JUL-19:30 0.149358E+11 6747.90 01-JUL-06:10
August 0.289613E+10 3094.06 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.284038E+10 3094.06 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.298860E+10 3094.06 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.292070E+10 3094.06 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.302980E+10 3094.06 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.346352E+11     0.175857E+12    
Minimum of Months 0.270887E+10 3094.06   0.134904E+11 6747.90  
Maximum of Months 0.303429E+10 3094.06   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.113146E+10 1089.83 02-JAN-20:10 0.368383E+11 16487.34 01-JAN-07:10
February 0.102161E+10 1089.83 01-FEB-20:10 0.332733E+11 16487.34 01-FEB-07:10
March 0.113495E+10 1089.83 01-MAR-20:10 0.368383E+11 16487.34 01-MAR-07:10
April 0.109310E+10 1089.83 03-APR-19:10 0.356500E+11 16487.34 01-APR-06:10
May 0.113342E+10 1089.83 01-MAY-19:10 0.368383E+11 16487.34 01-MAY-06:10
June 0.109811E+10 1089.83 01-JUN-19:10 0.356500E+11 16487.34 01-JUN-06:10
July 0.112841E+10 1089.83 03-JUL-19:10 0.368383E+11 16487.34 01-JUL-06:10
August 0.113539E+10 1089.83 01-AUG-19:10 0.368383E+11 16487.34 01-AUG-06:10
September 0.109354E+10 1089.83 01-SEP-19:10 0.356500E+11 16487.34 01-SEP-06:10
October 0.113103E+10 1089.83 02-OCT-19:10 0.368383E+11 16487.34 01-OCT-06:10
November 0.109724E+10 1089.83 01-NOV-19:10 0.356500E+11 16487.34 01-NOV-06:10
December 0.112841E+10 1089.83 01-DEC-20:10 0.368383E+11 16487.34 01-DEC-07:10
             
Annual Sum or Average 0.133267E+11     0.433742E+12    
Minimum of Months 0.102161E+10 1089.83   0.332733E+11 16487.34  
Maximum of Months 0.113539E+10 1089.83   0.368383E+11 16487.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.246211E+10 2371.52 02-JAN-20:10 0.00 0.00
February 0.222306E+10 2371.52 01-FEB-20:10 0.00 0.00
March 0.246970E+10 2371.52 01-MAR-20:10 0.00 0.00
April 0.237864E+10 2371.52 03-APR-19:10 0.00 0.00
May 0.246638E+10 2371.52 01-MAY-19:10 0.00 0.00
June 0.238954E+10 2371.52 01-JUN-19:10 0.00 0.00
July 0.245547E+10 2371.52 03-JUL-19:10 0.00 0.00
August 0.247065E+10 2371.52 01-AUG-19:10 0.00 0.00
September 0.237958E+10 2371.52 01-SEP-19:10 0.00 0.00
October 0.246116E+10 2371.52 02-OCT-19:10 0.00 0.00
November 0.238765E+10 2371.52 01-NOV-19:10 0.00 0.00
December 0.245547E+10 2371.52 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.289994E+11     0.00 0.00
Minimum of Months 0.222306E+10 2371.52   0.00 0.00
Maximum of Months 0.247065E+10 2371.52   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.147273E+11 0.127587E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.132974E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.147727E+11 0.127855E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.142280E+11 0.123314E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.147528E+11 0.127741E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.142932E+11 0.123716E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.146876E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.147784E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.142337E+11 0.123352E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.147216E+11 0.127549E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.142819E+11 0.123659E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.146876E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.173462E+12 0.150255E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.132974E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.147784E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.731324E+09 0.864900E+09 0.00 0.00 0.00 0.00 0.00 0.689402E+09
February 0.179968E+10 0.660319E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.665242E+09
March 0.199990E+10 0.733578E+09 0.866718E+09 0.00 0.00 0.00 0.00 0.00 0.535681E+09
April 0.192973E+10 0.706528E+09 0.835931E+09 0.00 0.00 0.00 0.00 611204.45 0.341400E+09
May 0.199475E+10 0.732592E+09 0.865939E+09 0.00 0.00 0.00 0.00 4508869.53 0.191057E+09
June 0.193394E+10 0.709769E+09 0.838659E+09 0.00 0.00 0.00 0.00 25876377.51 53538936.08
July 0.199054E+10 0.729351E+09 0.863211E+09 0.00 0.00 0.00 0.00 67975699.52 6460497.32
August 0.199896E+10 0.733860E+09 0.866978E+09 0.00 0.00 0.00 0.00 66811184.94 21318761.41
September 0.192879E+10 0.706810E+09 0.836191E+09 0.00 0.00 0.00 0.00 10517506.68 93659730.75
October 0.199148E+10 0.731042E+09 0.864640E+09 0.00 0.00 0.00 0.00 143964.63 0.275496E+09
November 0.192552E+10 0.709205E+09 0.838269E+09 0.00 0.00 0.00 0.00 0.00 0.456562E+09
December 0.199054E+10 0.729351E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.00 0.604635E+09
                   
Annual Sum or Average 0.234744E+11 0.861373E+10 0.101856E+11 0.00 0.00 0.00 0.00 0.176445E+09 0.393445E+10
Minimum of Months 0.179968E+10 0.660319E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 6460497.32
Maximum of Months 0.199990E+10 0.733860E+09 0.866978E+09 0.00 0.00 0.00 0.00 67975699.52 0.689402E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.846876E+09 0.100156E+10 0.00 0.00 0.00 0.00 0.00 0.269416E+09
February 0.208403E+10 0.764651E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 0.259679E+09
March 0.231589E+10 0.849486E+09 0.100366E+10 0.00 0.00 0.00 0.00 0.00 0.215251E+09
April 0.223463E+10 0.818162E+09 0.968011E+09 0.00 0.00 0.00 0.00 374617.67 0.142802E+09
May 0.230993E+10 0.848344E+09 0.100276E+10 0.00 0.00 0.00 0.00 1918671.39 88182552.67
June 0.223950E+10 0.821915E+09 0.971170E+09 0.00 0.00 0.00 0.00 9551048.72 30785417.98
July 0.230505E+10 0.844592E+09 0.999601E+09 0.00 0.00 0.00 0.00 23378286.06 6926702.68
August 0.231480E+10 0.849812E+09 0.100396E+10 0.00 0.00 0.00 0.00 25046698.87 13029129.97
September 0.223354E+10 0.818489E+09 0.968312E+09 0.00 0.00 0.00 0.00 4147596.20 45940091.76
October 0.230614E+10 0.846549E+09 0.100126E+10 0.00 0.00 0.00 0.00 148940.83 0.116350E+09
November 0.222975E+10 0.821262E+09 0.970719E+09 0.00 0.00 0.00 0.00 0.00 0.185200E+09
December 0.230505E+10 0.844592E+09 0.999601E+09 0.00 0.00 0.00 0.00 0.00 0.238720E+09
                   
Annual Sum or Average 0.271834E+11 0.997473E+10 0.117950E+11 0.00 0.00 0.00 0.00 64565859.75 0.161228E+10
Minimum of Months 0.208403E+10 0.764651E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 6926702.68
Maximum of Months 0.231589E+10 0.849812E+09 0.100396E+10 0.00 0.00 0.00 0.00 25046698.87 0.269416E+09



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.141236E+10 0.105898E+10 0.00 0.00 0.00 0.00 0.00 0.624708E+09
February 0.440737E+09 0.127524E+10 0.956227E+09 0.00 0.00 0.00 0.00 0.00 0.600028E+09
March 0.489771E+09 0.141672E+10 0.106120E+10 0.00 0.00 0.00 0.00 22733.11 0.482401E+09
April 0.472586E+09 0.136448E+10 0.102351E+10 0.00 0.00 0.00 0.00 1369055.40 0.314214E+09
May 0.488511E+09 0.141481E+10 0.106025E+10 0.00 0.00 0.00 0.00 4961028.96 0.193508E+09
June 0.473617E+09 0.137074E+10 0.102685E+10 0.00 0.00 0.00 0.00 22707994.88 68206681.37
July 0.487480E+09 0.140855E+10 0.105691E+10 0.00 0.00 0.00 0.00 54432058.74 15002513.61
August 0.489542E+09 0.141726E+10 0.106152E+10 0.00 0.00 0.00 0.00 59718362.81 28990251.64
September 0.472357E+09 0.136502E+10 0.102382E+10 0.00 0.00 0.00 0.00 10497314.44 0.101102E+09
October 0.487709E+09 0.141182E+10 0.105866E+10 0.00 0.00 0.00 0.00 727716.94 0.252755E+09
November 0.471555E+09 0.136965E+10 0.102637E+10 0.00 0.00 0.00 0.00 0.00 0.416952E+09
December 0.487480E+09 0.140855E+10 0.105691E+10 0.00 0.00 0.00 0.00 0.00 0.545361E+09
                   
Annual Sum or Average 0.574883E+10 0.166352E+11 0.124712E+11 0.00 0.00 0.00 0.00 0.154436E+09 0.364323E+10
Minimum of Months 0.440737E+09 0.127524E+10 0.956227E+09 0.00 0.00 0.00 0.00 0.00 15002513.61
Maximum of Months 0.489771E+09 0.141726E+10 0.106152E+10 0.00 0.00 0.00 0.00 59718362.81 0.624708E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.236418E+09 0.305485E+09 0.00 0.00 0.00 0.00 0.00 0.359911E+09
February 0.339028E+09 0.213464E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 0.345791E+09
March 0.376747E+09 0.237147E+09 0.306128E+09 0.00 0.00 0.00 0.00 13228.14 0.276307E+09
April 0.363528E+09 0.228402E+09 0.295253E+09 0.00 0.00 0.00 0.00 803959.94 0.178500E+09
May 0.375778E+09 0.236828E+09 0.305852E+09 0.00 0.00 0.00 0.00 2945859.87 0.108322E+09
June 0.364321E+09 0.229450E+09 0.296217E+09 0.00 0.00 0.00 0.00 13559435.85 37063487.93
July 0.374985E+09 0.235780E+09 0.304889E+09 0.00 0.00 0.00 0.00 32334677.67 7779560.04
August 0.376571E+09 0.237238E+09 0.306219E+09 0.00 0.00 0.00 0.00 35104189.08 15731059.19
September 0.363352E+09 0.228493E+09 0.295345E+09 0.00 0.00 0.00 0.00 6341531.75 55804904.05
October 0.375161E+09 0.236327E+09 0.305393E+09 0.00 0.00 0.00 0.00 430181.28 0.142691E+09
November 0.362735E+09 0.229268E+09 0.296079E+09 0.00 0.00 0.00 0.00 0.00 0.238177E+09
December 0.374985E+09 0.235780E+09 0.304889E+09 0.00 0.00 0.00 0.00 0.00 0.313823E+09
                   
Annual Sum or Average 0.442217E+10 0.278459E+10 0.359760E+10 0.00 0.00 0.00 0.00 91533063.58 0.207990E+10
Minimum of Months 0.339028E+09 0.213464E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 7779560.04
Maximum of Months 0.376747E+09 0.237238E+09 0.306219E+09 0.00 0.00 0.00 0.00 35104189.08 0.359911E+09



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.370859E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 0.00 0.927937E+09
February 0.139600E+10 0.334852E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.887752E+09
March 0.155131E+10 0.372002E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 324.05 0.733307E+09
April 0.149688E+10 0.358285E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 1377803.14 0.483183E+09
May 0.154732E+10 0.371502E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 6982893.75 0.290281E+09
June 0.150015E+10 0.359929E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 36891669.60 88774759.43
July 0.154405E+10 0.369859E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 93161946.32 15312082.99
August 0.155059E+10 0.372145E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 99416422.93 32616559.27
September 0.149615E+10 0.358428E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 18971413.69 0.139571E+09
October 0.154478E+10 0.370717E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 955181.45 0.371213E+09
November 0.149361E+10 0.359643E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 0.00 0.634184E+09
December 0.154405E+10 0.369859E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.00 0.821220E+09
                   
Annual Sum or Average 0.182090E+11 0.436808E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 0.257758E+09 0.542535E+10
Minimum of Months 0.139600E+10 0.334852E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 15312082.99
Maximum of Months 0.155131E+10 0.372145E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 99416422.93 0.927937E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.161485E+10 0.121771E+10 0.00 0.00 0.00 0.00 0.00 0.155947E+10
February 0.236489E+11 0.142581E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.151059E+10
March 0.262800E+11 0.154426E+10 0.122027E+10 0.00 0.00 0.00 0.00 0.00 0.125168E+10
April 0.253579E+11 0.144251E+10 0.117692E+10 0.00 0.00 0.00 0.00 1211103.25 0.824081E+09
May 0.262123E+11 0.143957E+10 0.121917E+10 0.00 0.00 0.00 0.00 9026461.98 0.504043E+09
June 0.254132E+11 0.137211E+10 0.118076E+10 0.00 0.00 0.00 0.00 52012251.38 0.170135E+09
July 0.261570E+11 0.141436E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.133535E+09 37929728.20
August 0.262677E+11 0.147541E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.138495E+09 71704617.04
September 0.253456E+11 0.147004E+10 0.117729E+10 0.00 0.00 0.00 0.00 21142544.59 0.265027E+09
October 0.261693E+11 0.157141E+10 0.121734E+10 0.00 0.00 0.00 0.00 322555.16 0.684931E+09
November 0.253025E+11 0.154685E+10 0.118021E+10 0.00 0.00 0.00 0.00 0.00 0.107447E+10
December 0.261570E+11 0.160913E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.00 0.138385E+10
                   
Annual Sum or Average 0.308468E+12 0.179263E+11 0.143405E+11 0.00 0.00 0.00 0.00 0.355744E+09 0.933792E+10
Minimum of Months 0.236489E+11 0.137211E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 37929728.20
Maximum of Months 0.262800E+11 0.161485E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.138495E+09 0.155947E+10



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.104401E+11 0.126520E+11 0.00 0.00 0.00 0.00 0.00 0.454161E+10
February 0.702046E+11 0.939242E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.437832E+10
March 0.780153E+11 0.103944E+11 0.126786E+11 0.00 0.00 0.00 0.00 0.00 0.365835E+10
April 0.752779E+11 0.996917E+10 0.122282E+11 0.00 0.00 0.00 0.00 4612380.47 0.244255E+10
May 0.778146E+11 0.102791E+11 0.126672E+11 0.00 0.00 0.00 0.00 28115041.37 0.152741E+10
June 0.754422E+11 0.993906E+10 0.122682E+11 0.00 0.00 0.00 0.00 0.150074E+09 0.532119E+09
July 0.776503E+11 0.102179E+11 0.126273E+11 0.00 0.00 0.00 0.00 0.374129E+09 0.122745E+09
August 0.779788E+11 0.103290E+11 0.126824E+11 0.00 0.00 0.00 0.00 0.398652E+09 0.219767E+09
September 0.752414E+11 0.999889E+10 0.122320E+11 0.00 0.00 0.00 0.00 61192406.63 0.802832E+09
October 0.776868E+11 0.103905E+11 0.126482E+11 0.00 0.00 0.00 0.00 1268255.62 0.199851E+10
November 0.751137E+11 0.101030E+11 0.122624E+11 0.00 0.00 0.00 0.00 0.00 0.316827E+10
December 0.776503E+11 0.104094E+11 0.126273E+11 0.00 0.00 0.00 0.00 0.00 0.405041E+10
                   
Annual Sum or Average 0.915726E+12 0.121863E+12 0.148998E+12 0.00 0.00 0.00 0.00 0.101804E+10 0.274429E+11
Minimum of Months 0.702046E+11 0.939242E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.122745E+09
Maximum of Months 0.780153E+11 0.104401E+11 0.126824E+11 0.00 0.00 0.00 0.00 0.398652E+09 0.454161E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.392384E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.379535E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 17319.82 0.306157E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 728020.09 0.195433E+09
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 3793080.15 0.109365E+09
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 22567870.78 23989137.92
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 60483383.49 1214464.37
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 60848171.44 6783669.56
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 13000254.79 45384673.45
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 474363.63 0.146200E+09
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 0.259599E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.343448E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.161912E+09 0.220949E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 1214464.37
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 60848171.44 0.392384E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.388903E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.375030E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 17346.15 0.301646E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 787289.45 0.193350E+09
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 3814533.40 0.108718E+09
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 22608968.35 23909988.68
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 60533303.55 1210012.26
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 61033650.20 6735773.14
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 13160847.03 44499377.96
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 548050.98 0.142967E+09
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 0.255409E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.338897E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.162504E+09 0.218128E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 1210012.26
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 61033650.20 0.388903E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 85091918.49 0.255708E+09 0.00 0.00 0.00 0.00 0.00 0.103784E+09
February 0.00 76846309.13 0.230956E+09 0.00 0.00 0.00 0.00 0.00 0.104003E+09
March 0.00 84415649.14 0.255355E+09 0.00 0.00 0.00 0.00 0.00 86632660.54
April 0.00 82445007.08 0.247516E+09 0.00 0.00 0.00 0.00 122030.78 57606400.49
May 0.00 84753783.81 0.255532E+09 0.00 0.00 0.00 0.00 689783.21 36965031.84
June 0.00 81790910.76 0.247163E+09 0.00 0.00 0.00 0.00 3965840.74 11933957.23
July 0.00 85418966.65 0.255885E+09 0.00 0.00 0.00 0.00 10545904.78 2119898.45
August 0.00 84415649.14 0.255355E+09 0.00 0.00 0.00 0.00 11548446.44 4574850.87
September 0.00 82467180.11 0.247516E+09 0.00 0.00 0.00 0.00 1859007.88 18718252.60
October 0.00 85080831.98 0.255708E+09 0.00 0.00 0.00 0.00 46932.37 49012449.93
November 0.00 82117958.92 0.247340E+09 0.00 0.00 0.00 0.00 0.00 74476828.94
December 0.00 85430053.17 0.255885E+09 0.00 0.00 0.00 0.00 0.00 93456552.10
                   
Annual Sum or Average 0.00 0.100027E+10 0.300992E+10 0.00 0.00 0.00 0.00 28777946.19 0.643283E+09
Minimum of Months 0.00 76846309.13 0.230956E+09 0.00 0.00 0.00 0.00 0.00 2119898.45
Maximum of Months 0.00 85430053.17 0.255885E+09 0.00 0.00 0.00 0.00 11548446.44 0.104003E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 85115186.72 0.255778E+09 0.00 0.00 0.00 0.00 0.00 0.109678E+09
February 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 0.00 0.105413E+09
March 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 4843.07 84651823.64
April 0.293479E+09 82467551.52 0.247584E+09 0.00 0.00 0.00 0.00 279325.13 53890791.38
May 0.303504E+09 84776959.58 0.255602E+09 0.00 0.00 0.00 0.00 1178497.26 29681723.63
June 0.293842E+09 81813276.33 0.247231E+09 0.00 0.00 0.00 0.00 6736871.42 6217573.15
July 0.303141E+09 85442324.32 0.255955E+09 0.00 0.00 0.00 0.00 17451722.51 308436.06
August 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 17737844.97 1813905.71
September 0.293479E+09 82489730.61 0.247584E+09 0.00 0.00 0.00 0.00 4143749.98 11881147.07
October 0.303322E+09 85104097.18 0.255778E+09 0.00 0.00 0.00 0.00 284914.92 39122470.12
November 0.293661E+09 82140413.93 0.247408E+09 0.00 0.00 0.00 0.00 0.00 72148563.75
December 0.303141E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 0.00 95766023.45
                   
Annual Sum or Average 0.357224E+10 0.100055E+10 0.301074E+10 0.00 0.00 0.00 0.00 47817769.26 0.610574E+09
Minimum of Months 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 0.00 308436.06
Maximum of Months 0.303685E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 17737844.97 0.109678E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.392192E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.379714E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 17346.45 0.307129E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 729514.40 0.196661E+09
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 3774365.38 0.110113E+09
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 22484343.10 24171311.82
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 60307669.77 1236478.41
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 60776260.54 6975082.52
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 13003681.65 45782448.30
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 481972.16 0.147026E+09
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 0.260347E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.343405E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.161575E+09 0.221475E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 1236478.41
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 60776260.54 0.392192E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.388850E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.375059E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 17353.23 0.302445E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 735990.62 0.194989E+09
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 3776880.91 0.109899E+09
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 22490839.85 24148971.55
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 60317267.03 1232169.96
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 60828595.59 6962107.12
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 13062041.66 45325989.49
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 489177.23 0.144094E+09
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 0.256109E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.338815E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.161718E+09 0.218793E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 1232169.96
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 60828595.59 0.388850E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.232638E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.481226E+09
February 0.348285E+10 0.210051E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.462495E+09
March 0.387034E+10 0.233355E+10 0.00 0.00 0.00 0.00 0.00 7171.80 0.372558E+09
April 0.373454E+10 0.224750E+10 0.00 0.00 0.00 0.00 0.00 863095.94 0.245040E+09
May 0.386038E+10 0.233041E+10 0.00 0.00 0.00 0.00 0.00 3360146.76 0.151302E+09
June 0.374269E+10 0.225781E+10 0.00 0.00 0.00 0.00 0.00 16395209.09 53929184.49
July 0.385223E+10 0.232011E+10 0.00 0.00 0.00 0.00 0.00 39963275.87 11801299.79
August 0.386853E+10 0.233445E+10 0.00 0.00 0.00 0.00 0.00 42962935.57 23205373.36
September 0.373273E+10 0.224840E+10 0.00 0.00 0.00 0.00 0.00 6738829.93 79727427.39
October 0.385404E+10 0.232548E+10 0.00 0.00 0.00 0.00 0.00 307856.57 0.201317E+09
November 0.372639E+10 0.225602E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.321086E+09
December 0.385223E+10 0.232011E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.420086E+09
                   
Annual Sum or Average 0.454292E+11 0.274007E+11 0.00 0.00 0.00 0.00 0.00 0.110599E+09 0.282377E+10
Minimum of Months 0.348285E+10 0.210051E+10 0.00 0.00 0.00 0.00 0.00 0.00 11801299.79
Maximum of Months 0.387034E+10 0.233445E+10 0.00 0.00 0.00 0.00 0.00 42962935.57 0.481226E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.392026E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.379108E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 15354.17 0.305851E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 702678.23 0.195595E+09
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 3689974.70 0.110026E+09
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 22094723.35 24426796.46
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 59503686.24 1265355.08
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 59973380.50 6915103.31
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 12642078.12 45755355.49
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 446996.36 0.146454E+09
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 0.258879E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.342924E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.159069E+09 0.220923E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 1265355.08
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 59973380.50 0.392026E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.389248E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.375187E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 15382.50 0.301273E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 751197.80 0.193448E+09
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 3708002.31 0.109456E+09
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 22127106.09 24361064.05
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 59544572.71 1260271.93
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 60162062.68 6863093.06
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 12809558.96 44851892.93
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 525534.44 0.142723E+09
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 0.254784E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.338838E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.159643E+09 0.218229E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 1260271.93
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 60162062.68 0.389248E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 85115186.72 0.255778E+09 0.00 0.00 0.00 0.00 0.00 0.204371E+09
February 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 0.00 0.198033E+09
March 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 7867.90 0.158945E+09
April 0.293479E+09 82467551.52 0.247584E+09 0.00 0.00 0.00 0.00 358159.66 0.101174E+09
May 0.303504E+09 84776959.58 0.255602E+09 0.00 0.00 0.00 0.00 1902667.14 56366643.78
June 0.293842E+09 81813276.33 0.247231E+09 0.00 0.00 0.00 0.00 11352646.52 12347916.70
July 0.303141E+09 85442324.32 0.255955E+09 0.00 0.00 0.00 0.00 30514142.22 639627.77
August 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 30735835.08 3542922.21
September 0.293479E+09 82489730.61 0.247584E+09 0.00 0.00 0.00 0.00 6462194.59 23629787.99
October 0.303322E+09 85104097.18 0.255778E+09 0.00 0.00 0.00 0.00 215698.19 75926549.48
November 0.293661E+09 82140413.93 0.247408E+09 0.00 0.00 0.00 0.00 0.00 0.136260E+09
December 0.303141E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 0.00 0.179450E+09
                   
Annual Sum or Average 0.357224E+10 0.100055E+10 0.301074E+10 0.00 0.00 0.00 0.00 81549211.28 0.115069E+10
Minimum of Months 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 0.00 639627.77
Maximum of Months 0.303685E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 30735835.08 0.204371E+09



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.303429E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.108053E+10
February 0.415303E+11 0.270887E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.103224E+10
March 0.461508E+11 0.296851E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.867163E+09
April 0.445315E+11 0.281177E+10 0.144540E+11 0.00 0.00 0.00 0.00 771158.75 0.588298E+09
May 0.460320E+11 0.285834E+10 0.149358E+11 0.00 0.00 0.00 0.00 4606049.30 0.372159E+09
June 0.446286E+11 0.274883E+10 0.144540E+11 0.00 0.00 0.00 0.00 27322772.71 0.132128E+09
July 0.459349E+11 0.282901E+10 0.149358E+11 0.00 0.00 0.00 0.00 71899091.06 30555807.52
August 0.461292E+11 0.289613E+10 0.149358E+11 0.00 0.00 0.00 0.00 81807965.51 52599862.88
September 0.445099E+11 0.284038E+10 0.144540E+11 0.00 0.00 0.00 0.00 11669046.03 0.193338E+09
October 0.459565E+11 0.298860E+10 0.149358E+11 0.00 0.00 0.00 0.00 259719.63 0.462686E+09
November 0.444343E+11 0.292070E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.750666E+09
December 0.459349E+11 0.302980E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.962331E+09
                   
Annual Sum or Average 0.541708E+12 0.346352E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.198336E+09 0.652470E+10
Minimum of Months 0.415303E+11 0.270887E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 30555807.52
Maximum of Months 0.461508E+11 0.303429E+10 0.149358E+11 0.00 0.00 0.00 0.00 81807965.51 0.108053E+10



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.303429E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.109252E+10
February 0.415303E+11 0.270887E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.104278E+10
March 0.461508E+11 0.296851E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.875336E+09
April 0.445315E+11 0.281177E+10 0.144540E+11 0.00 0.00 0.00 0.00 715444.40 0.594056E+09
May 0.460320E+11 0.285834E+10 0.149358E+11 0.00 0.00 0.00 0.00 4567470.55 0.374801E+09
June 0.446286E+11 0.274883E+10 0.144540E+11 0.00 0.00 0.00 0.00 27161315.74 0.132820E+09
July 0.459349E+11 0.282901E+10 0.149358E+11 0.00 0.00 0.00 0.00 71709094.91 30589204.65
August 0.461292E+11 0.289613E+10 0.149358E+11 0.00 0.00 0.00 0.00 81419241.51 52706893.47
September 0.445099E+11 0.284038E+10 0.144540E+11 0.00 0.00 0.00 0.00 11469452.72 0.194843E+09
October 0.459565E+11 0.298860E+10 0.149358E+11 0.00 0.00 0.00 0.00 194094.59 0.466629E+09
November 0.444343E+11 0.292070E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.758718E+09
December 0.459349E+11 0.302980E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.972164E+09
                   
Annual Sum or Average 0.541708E+12 0.346352E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.197236E+09 0.658797E+10
Minimum of Months 0.415303E+11 0.270887E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 30589204.65
Maximum of Months 0.461508E+11 0.303429E+10 0.149358E+11 0.00 0.00 0.00 0.00 81419241.51 0.109252E+10



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.113146E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.987480E+09
February 0.369574E+10 0.102161E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.941499E+09
March 0.410691E+10 0.113495E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.788620E+09
April 0.396281E+10 0.109310E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 583727.01 0.532045E+09
May 0.409635E+10 0.113342E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 4019203.52 0.332941E+09
June 0.397146E+10 0.109811E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 23936559.39 0.116981E+09
July 0.408770E+10 0.112841E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 64296095.41 26353270.60
August 0.410499E+10 0.113539E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 72335309.63 46083550.30
September 0.396089E+10 0.109354E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 10056271.14 0.172206E+09
October 0.408962E+10 0.113103E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 109198.17 0.417410E+09
November 0.395417E+10 0.109724E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.684490E+09
December 0.408770E+10 0.112841E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.877566E+09
                   
Annual Sum or Average 0.482060E+11 0.133267E+11 0.392709E+12 0.359593E+12 0.00 0.00 0.00 0.175336E+09 0.592368E+10
Minimum of Months 0.369574E+10 0.102161E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 0.00 26353270.60
Maximum of Months 0.410691E+10 0.113539E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 72335309.63 0.987480E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.246211E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.854179E+09
February 0.368610E+10 0.222306E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.821200E+09
March 0.409620E+10 0.246970E+10 0.00 0.00 0.00 0.00 0.00 539.80 0.661669E+09
April 0.395248E+10 0.237864E+10 0.00 0.00 0.00 0.00 0.00 1053697.82 0.433561E+09
May 0.408566E+10 0.246638E+10 0.00 0.00 0.00 0.00 0.00 4533839.94 0.268771E+09
June 0.396110E+10 0.238954E+10 0.00 0.00 0.00 0.00 0.00 25254024.76 96501456.94
July 0.407704E+10 0.245547E+10 0.00 0.00 0.00 0.00 0.00 65362654.80 20612609.59
August 0.409429E+10 0.247065E+10 0.00 0.00 0.00 0.00 0.00 73001553.01 39020241.98
September 0.395056E+10 0.237958E+10 0.00 0.00 0.00 0.00 0.00 10778491.62 0.138605E+09
October 0.407896E+10 0.246116E+10 0.00 0.00 0.00 0.00 0.00 305180.14 0.345901E+09
November 0.394385E+10 0.238765E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.565685E+09
December 0.407704E+10 0.245547E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.746037E+09
                   
Annual Sum or Average 0.480803E+11 0.289994E+11 0.00 0.00 0.00 0.00 0.00 0.180290E+09 0.499174E+10
Minimum of Months 0.368610E+10 0.222306E+10 0.00 0.00 0.00 0.00 0.00 0.00 20612609.59
Maximum of Months 0.409620E+10 0.247065E+10 0.00 0.00 0.00 0.00 0.00 73001553.01 0.854179E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 14185.34 02-JAN-20:10 10113.80 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 14185.34 01-FEB-20:10 10113.80 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 14185.34 01-MAR-20:10 10113.80 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 14185.34 03-APR-19:10 10113.80 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 14185.34 01-MAY-19:10 10113.80 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 14185.34 01-JUN-19:10 10113.80 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 14185.34 03-JUL-19:10 10113.80 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 14185.34 01-AUG-19:10 10113.80 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 14185.34 01-SEP-19:10 10113.80 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 14185.34 02-OCT-19:10 10113.80 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 14185.34 01-NOV-19:10 10113.80 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 14185.34 01-DEC-20:10 10113.80 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   14185.34   10113.80   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   14185.34   10113.80   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 704.41 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 452.52 02-JAN-05:00
February 1169.53 01-FEB-00:10 704.41 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 464.93 06-FEB-03:00
March 1169.53 01-MAR-00:10 704.41 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 343.22 23-MAR-06:00
April 1169.53 01-APR-00:10 704.41 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 32.91 08-APR-10:00 242.07 03-APR-06:00
May 1169.53 01-MAY-00:10 704.41 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 69.45 30-MAY-13:00 187.97 01-MAY-05:00
June 1169.53 01-JUN-00:10 704.41 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 142.94 19-JUN-12:00 99.35 03-JUN-03:00
July 1169.53 01-JUL-00:10 704.41 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 112.65 07-JUL-12:00 40.98 01-JUL-23:00
August 1169.53 01-AUG-00:10 704.41 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 111.87 24-AUG-15:00 79.96 08-AUG-05:00
September 1169.53 01-SEP-00:10 704.41 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 80.75 01-SEP-14:00 139.19 30-SEP-01:00
October 1169.53 01-OCT-23:10 704.41 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 11.68 04-OCT-13:00 243.51 09-OCT-06:00
November 1169.53 01-NOV-00:10 704.41 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 334.28 24-NOV-07:00
December 1169.53 01-DEC-00:10 704.41 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 389.28 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   704.41   685.60   0.00 0.00 0.00 0.00 0.00   40.98  
Maximum of Months 1169.53   704.41   685.60   0.00 0.00 0.00 0.00 142.94   464.93  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 815.72 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 174.66 02-JAN-05:00
February 1354.32 01-FEB-00:10 815.72 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 179.45 06-FEB-03:00
March 1354.32 01-MAR-00:10 815.72 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 136.28 23-MAR-06:00
April 1354.32 01-APR-00:10 815.72 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 17.85 07-APR-13:00 97.79 03-APR-06:00
May 1354.32 01-MAY-00:10 815.72 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 31.24 30-MAY-13:00 78.96 01-MAY-05:00
June 1354.32 01-JUN-00:10 815.72 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 58.78 19-JUN-12:00 47.86 03-JUN-03:00
July 1354.32 01-JUL-00:10 815.72 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 46.20 07-JUL-12:00 24.03 02-JUL-03:00
August 1354.32 01-AUG-00:10 815.72 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 44.42 24-AUG-15:00 40.38 08-AUG-05:00
September 1354.32 01-SEP-00:10 815.72 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 32.19 01-SEP-14:00 62.47 30-SEP-01:00
October 1354.32 01-OCT-23:10 815.72 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 9.33 25-OCT-10:53 101.38 09-OCT-06:00
November 1354.32 01-NOV-00:10 815.72 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 130.81 24-NOV-07:00
December 1354.32 01-DEC-00:10 815.72 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 151.67 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   815.72   793.93   0.00 0.00 0.00 0.00 0.00   24.03  
Maximum of Months 1354.32   815.72   793.93   0.00 0.00 0.00 0.00 58.78   179.45  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 1360.40 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 412.79 02-JAN-05:00
February 286.42 01-FEB-00:10 1360.40 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 424.08 06-FEB-03:00
March 286.42 01-MAR-00:10 1360.40 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 10.32 27-MAR-16:00 313.10 23-MAR-06:00
April 286.42 01-APR-00:10 1360.40 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 51.24 07-APR-13:00 220.79 03-APR-06:00
May 286.42 01-MAY-00:10 1360.40 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 74.63 30-MAY-13:00 176.96 01-MAY-05:00
June 286.42 01-JUN-00:10 1360.40 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 137.85 19-JUN-12:00 107.05 03-JUN-03:00
July 286.42 01-JUL-00:10 1360.40 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 107.40 07-JUL-12:00 54.11 02-JUL-03:00
August 286.42 01-AUG-00:10 1360.40 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 107.07 24-AUG-16:00 91.98 08-AUG-05:00
September 286.42 01-SEP-00:10 1360.40 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 78.32 01-SEP-14:00 140.16 24-SEP-06:00
October 286.42 01-OCT-23:10 1360.40 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 25.62 25-OCT-10:53 229.74 09-OCT-06:00
November 286.42 01-NOV-00:10 1360.40 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 304.94 24-NOV-07:00
December 286.42 01-DEC-00:10 1360.40 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 355.13 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   1360.40   839.45   0.00 0.00 0.00 0.00 0.00   54.11  
Maximum of Months 286.42   1360.40   839.45   0.00 0.00 0.00 0.00 137.85   424.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 227.72 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 238.15 02-JAN-05:00
February 220.32 01-FEB-00:10 227.72 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 244.68 06-FEB-03:00
March 220.32 01-MAR-00:10 227.72 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 5.98 27-MAR-16:00 180.64 23-MAR-06:00
April 220.32 01-APR-00:10 227.72 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 29.48 07-APR-13:00 127.39 03-APR-06:00
May 220.32 01-MAY-00:10 227.72 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 43.14 30-MAY-13:00 101.16 01-MAY-05:00
June 220.32 01-JUN-00:10 227.72 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 79.47 19-JUN-12:00 61.05 03-JUN-03:00
July 220.32 01-JUL-00:10 227.72 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 61.95 07-JUL-12:00 30.16 02-JUL-03:00
August 220.32 01-AUG-00:10 227.72 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 61.47 24-AUG-16:00 52.31 08-AUG-05:00
September 220.32 01-SEP-00:10 227.72 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 45.26 01-SEP-14:00 79.33 24-SEP-06:00
October 220.32 01-OCT-23:10 227.72 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 14.92 25-OCT-10:53 131.14 09-OCT-04:00
November 220.32 01-NOV-00:10 227.72 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 175.93 24-NOV-07:00
December 220.32 01-DEC-00:10 227.72 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 204.89 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   227.72   242.16   0.00 0.00 0.00 0.00 0.00   30.16  
Maximum of Months 220.32   227.72   242.16   0.00 0.00 0.00 0.00 79.47   244.68  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 357.21 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 0.00 01-JAN-00:03 602.22 02-JAN-07:10
February 907.20 01-FEB-00:10 357.21 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 0.00 01-FEB-00:03 615.14 06-FEB-07:10
March 907.20 01-MAR-00:10 357.21 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 0.54 27-MAR-16:00 475.52 23-MAR-06:00
April 907.20 01-APR-00:10 357.21 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 58.59 07-APR-13:00 349.03 03-APR-06:00
May 907.20 01-MAY-00:10 357.21 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 108.08 30-MAY-10:50 293.95 01-MAY-06:05
June 907.20 01-JUN-00:10 357.21 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 203.65 19-JUN-12:00 152.38 02-JUN-06:00
July 907.20 01-JUL-00:10 357.21 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 166.66 07-JUL-10:50 76.05 01-JUL-23:20
August 907.20 01-AUG-00:10 357.21 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 166.25 24-AUG-16:00 129.79 08-AUG-05:10
September 907.20 01-SEP-00:10 357.21 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 114.40 01-SEP-14:20 212.74 24-SEP-05:34
October 907.20 01-OCT-23:10 357.21 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 45.81 25-OCT-10:50 357.01 31-OCT-06:10
November 907.20 01-NOV-00:10 357.21 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 0.00 01-NOV-00:05 463.42 24-NOV-07:10
December 907.20 01-DEC-00:10 357.21 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 0.00 01-DEC-00:03 524.77 31-DEC-23:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   357.21   4572.80   39726.58   0.00 0.00 0.00 0.00   76.05  
Maximum of Months 907.20   357.21   4572.80   39726.58   0.00 0.00 0.00 203.65   615.14  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 1761.91 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 1000.36 02-JAN-05:00
February 15368.40 01-FEB-00:10 1761.91 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 1027.76 06-FEB-03:00
March 15368.40 01-MAR-00:10 1761.91 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 784.54 23-MAR-04:20
April 15368.40 01-APR-00:10 1761.91 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 69.19 07-APR-13:00 557.43 01-APR-04:00
May 15368.40 01-MAY-00:10 1761.91 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 153.54 30-MAY-13:00 456.35 01-MAY-05:00
June 15368.40 01-JUN-00:10 1761.91 01-JUN-19:19 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 317.10 19-JUN-10:55 279.51 03-JUN-03:00
July 15368.40 01-JUL-00:10 1761.91 03-JUL-19:19 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 249.03 07-JUL-12:00 129.53 02-JUL-03:00
August 15368.40 01-AUG-00:10 1761.91 01-AUG-19:10 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 247.32 24-AUG-15:30 234.41 08-AUG-05:00
September 15368.40 01-SEP-00:10 1761.91 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 178.52 01-SEP-14:00 363.60 30-SEP-01:00
October 15368.40 01-OCT-23:10 1761.91 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 25.84 04-OCT-13:00 570.84 29-OCT-07:00
November 15368.40 01-NOV-00:10 1761.91 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 757.50 24-NOV-06:00
December 15368.40 01-DEC-00:10 1761.91 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 861.61 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   1761.91   965.27   0.00 0.00 0.00 0.00 0.00   129.53  
Maximum of Months 15368.40   1761.91   965.27   0.00 0.00 0.00 0.00 317.10   1027.76  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 10265.18 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 2907.27 02-JAN-05:00
February 45622.98 01-FEB-00:10 10265.18 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 3001.78 06-FEB-03:00
March 45622.98 01-MAR-00:10 10265.18 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 2306.84 23-MAR-04:40
April 45622.98 01-APR-00:10 10265.18 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 241.85 07-APR-13:00 1658.37 03-APR-06:00
May 45622.98 01-MAY-00:10 10265.18 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 488.89 30-MAY-13:00 1366.04 01-MAY-05:00
June 45622.98 01-JUN-00:10 10265.18 01-JUN-19:10 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 950.79 19-JUN-12:00 824.70 03-JUN-03:00
July 45622.98 01-JUL-00:10 10265.18 03-JUL-19:19 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 749.67 07-JUL-12:00 420.50 02-JUL-03:00
August 45622.98 01-AUG-00:10 10265.18 01-AUG-19:10 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 711.72 24-AUG-15:00 694.66 08-AUG-05:00
September 45622.98 01-SEP-00:10 10265.18 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 511.23 01-SEP-14:00 1053.09 30-SEP-01:00
October 45622.98 01-OCT-23:10 10265.18 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 111.57 25-OCT-10:53 1707.40 09-OCT-06:00
November 45622.98 01-NOV-00:10 10265.18 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 2229.00 24-NOV-06:00
December 45622.98 01-DEC-00:10 10265.18 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 2549.01 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   10265.18   10029.21   0.00 0.00 0.00 0.00 0.00   420.50  
Maximum of Months 45622.98   10265.18   10029.21   0.00 0.00 0.00 0.00 950.79   3001.78  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 263.84 02-JAN-05:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 271.01 06-FEB-03:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 7.17 27-MAR-16:00 200.38 23-MAR-06:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 33.43 08-APR-10:00 141.62 03-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 48.23 30-MAY-16:00 110.20 01-MAY-05:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 87.04 19-JUN-12:00 55.64 03-JUN-03:00
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 77.78 10-JUL-15:10 19.90 02-JUL-05:00
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 83.59 24-AUG-16:00 43.66 08-AUG-05:00
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 59.95 01-SEP-15:10 80.65 24-SEP-06:00
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 16.89 04-OCT-15:10 142.49 09-OCT-06:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 195.18 24-NOV-07:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 227.13 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 0.00   19.90  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 87.04   271.01  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 263.82 02-JAN-05:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 271.00 06-FEB-03:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 7.18 27-MAR-16:00 200.36 23-MAR-06:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 33.43 08-APR-10:00 141.61 03-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 48.23 30-MAY-16:00 110.19 01-MAY-05:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 87.03 19-JUN-12:00 55.64 03-JUN-03:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 77.80 10-JUL-15:10 19.90 02-JUL-05:00
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 83.58 24-AUG-15:50 43.66 08-AUG-05:00
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 60.00 01-SEP-15:10 80.64 24-SEP-06:00
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 17.47 04-OCT-15:10 142.47 09-OCT-06:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 195.17 24-NOV-07:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 227.10 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 0.00   19.90  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 87.03   271.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 76.99 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 68.71 02-JAN-05:00
February 0.00 01-FEB-00:10 76.99 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 70.82 06-FEB-03:00
March 0.00 01-MAR-00:10 76.99 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 53.42 23-MAR-06:00
April 0.00 01-APR-00:10 76.99 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 6.24 07-APR-13:00 38.26 12-APR-06:20
May 0.00 01-MAY-00:10 76.99 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 12.42 30-MAY-13:00 30.84 15-MAY-03:00
June 0.00 01-JUN-00:10 76.99 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 24.29 19-JUN-12:00 18.86 03-JUN-02:55
July 0.00 01-JUL-00:10 76.99 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 19.39 07-JUL-12:00 9.36 02-JUL-03:00
August 0.00 01-AUG-00:10 76.99 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 19.26 24-AUG-15:00 15.93 08-AUG-05:00
September 0.00 01-SEP-00:10 76.99 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 14.23 01-SEP-14:00 25.49 30-SEP-01:00
October 0.00 01-OCT-00:10 76.99 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 3.08 04-OCT-13:00 41.86 29-OCT-07:00
November 0.00 01-NOV-00:10 76.99 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 51.32 24-NOV-08:00
December 0.00 01-DEC-00:10 76.99 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 58.59 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   76.99   232.19   0.00 0.00 0.00 0.00 0.00   9.36  
Maximum of Months 0.00   76.99   232.19   0.00 0.00 0.00 0.00 24.29   70.82  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 77.01 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 73.63 02-JAN-05:00
February 180.00 01-FEB-00:10 77.01 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 75.64 06-FEB-03:00
March 180.00 01-MAR-00:10 77.01 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 2.00 27-MAR-16:00 55.92 23-MAR-06:00
April 180.00 01-APR-00:10 77.01 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 9.33 08-APR-10:00 39.52 03-APR-06:00
May 180.00 01-MAY-00:10 77.01 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 13.46 30-MAY-16:00 30.76 01-MAY-05:00
June 180.00 01-JUN-00:10 77.01 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 24.66 19-JUN-12:00 15.53 03-JUN-03:00
July 180.00 01-JUL-00:10 77.01 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 21.72 10-JUL-15:10 5.55 02-JUL-05:00
August 180.00 01-AUG-00:10 77.01 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 23.33 24-AUG-15:10 12.19 08-AUG-05:00
September 180.00 01-SEP-00:10 77.01 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 16.75 01-SEP-15:10 22.51 24-SEP-06:00
October 180.00 01-OCT-00:10 77.01 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 6.09 25-OCT-10:53 39.77 09-OCT-06:00
November 180.00 01-NOV-00:10 77.01 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 54.47 24-NOV-07:00
December 180.00 01-DEC-00:10 77.01 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 63.39 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 0.00   5.55  
Maximum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 24.66   75.64  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 263.84 02-JAN-05:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 271.02 06-FEB-03:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 7.18 27-MAR-16:00 200.38 23-MAR-06:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 33.42 08-APR-10:00 141.62 03-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 48.24 30-MAY-16:00 110.20 01-MAY-05:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 87.04 19-JUN-12:00 60.96 02-JUN-07:10
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 77.82 10-JUL-15:10 19.90 02-JUL-05:00
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 83.60 24-AUG-15:10 43.66 08-AUG-05:00
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 60.01 01-SEP-15:10 80.65 24-SEP-06:00
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 17.47 04-OCT-15:10 142.48 09-OCT-06:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 195.18 24-NOV-07:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 227.12 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 0.00   19.90  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 87.04   271.02  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 263.82 02-JAN-05:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 271.00 06-FEB-03:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 7.18 27-MAR-16:00 200.36 23-MAR-06:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 33.43 08-APR-10:00 141.61 03-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 48.24 30-MAY-15:50 110.19 01-MAY-05:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 87.03 19-JUN-12:00 60.95 02-JUN-07:10
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 77.81 10-JUL-15:10 19.90 02-JUL-05:00
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 83.59 24-AUG-15:10 43.66 08-AUG-05:00
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 60.01 01-SEP-15:10 80.64 24-SEP-06:00
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 17.47 04-OCT-15:10 142.48 09-OCT-06:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 195.17 24-NOV-07:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 227.11 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 0.00   19.90  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 87.03   271.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 2240.78 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 317.99 02-JAN-05:00
February 2263.36 01-FEB-00:10 2240.78 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 326.69 06-FEB-03:00
March 2263.36 01-MAR-00:10 2240.78 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 4.95 27-MAR-16:00 241.28 23-MAR-06:00
April 2263.36 01-APR-00:10 2240.78 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 35.41 07-APR-13:00 170.25 03-APR-06:00
May 2263.36 01-MAY-00:10 2240.78 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 54.55 30-MAY-13:00 137.65 01-MAY-05:00
June 2263.36 01-JUN-00:10 2240.78 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 104.47 19-JUN-12:00 85.41 03-JUN-03:00
July 2263.36 01-JUL-00:10 2240.78 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 80.74 07-JUL-12:00 41.99 02-JUL-03:00
August 2263.36 01-AUG-00:10 2240.78 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 78.17 24-AUG-15:00 71.89 08-AUG-05:00
September 2263.36 01-SEP-00:10 2240.78 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 56.33 01-SEP-14:00 107.48 30-SEP-01:00
October 2263.36 01-OCT-23:10 2240.78 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 16.90 25-OCT-10:53 180.98 09-OCT-04:00
November 2263.36 01-NOV-00:10 2240.78 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 235.00 24-NOV-07:00
December 2263.36 01-DEC-00:10 2240.78 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 273.63 31-DEC-24:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   2240.78   0.00 0.00 0.00 0.00 0.00 0.00   41.99  
Maximum of Months 2263.36   2240.78   0.00 0.00 0.00 0.00 0.00 104.47   326.69  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 264.38 02-JAN-05:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 271.54 06-FEB-03:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 6.77 27-MAR-16:00 200.87 23-MAR-06:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 33.03 08-APR-10:00 142.09 03-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 47.81 30-MAY-16:00 110.66 01-MAY-05:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 86.67 19-JUN-12:00 56.07 03-JUN-02:55
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 77.26 10-JUL-15:10 20.32 02-JUL-05:00
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 83.21 24-AUG-15:50 44.09 08-AUG-05:00
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 59.56 01-SEP-15:10 81.09 24-SEP-06:00
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 16.39 04-OCT-15:10 142.96 09-OCT-06:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 195.68 24-NOV-07:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 227.63 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 0.00   20.32  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 86.67   271.54  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 264.36 02-JAN-05:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 271.51 06-FEB-03:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 6.77 27-MAR-16:00 200.86 23-MAR-06:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 33.03 08-APR-10:00 142.08 03-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 47.80 30-MAY-16:00 110.65 01-MAY-05:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 86.66 19-JUN-12:00 56.07 03-JUN-03:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 77.24 10-JUL-15:10 20.31 02-JUL-05:00
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 83.20 24-AUG-16:00 44.09 08-AUG-05:00
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 59.61 01-SEP-15:10 81.09 24-SEP-06:00
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 17.06 04-OCT-15:10 142.95 09-OCT-06:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 195.67 24-NOV-07:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 227.62 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 0.00   20.31  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 86.66   271.51  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 77.01 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 135.26 02-JAN-05:00
February 180.00 01-FEB-00:10 77.01 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 138.93 06-FEB-03:00
March 180.00 01-MAR-00:10 77.01 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 3.46 27-MAR-16:00 102.78 23-MAR-06:00
April 180.00 01-APR-00:10 77.01 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 16.90 08-APR-10:00 72.70 03-APR-06:00
May 180.00 01-MAY-00:10 77.01 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 24.48 30-MAY-16:00 56.62 01-MAY-05:00
June 180.00 01-JUN-00:10 77.01 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 44.34 19-JUN-12:00 28.69 03-JUN-03:00
July 180.00 01-JUL-00:10 77.01 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 39.62 10-JUL-15:10 10.39 02-JUL-05:00
August 180.00 01-AUG-00:10 77.01 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 42.58 24-AUG-16:00 22.56 08-AUG-05:00
September 180.00 01-SEP-00:10 77.01 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 30.48 01-SEP-15:10 41.49 24-SEP-06:00
October 180.00 01-OCT-00:10 77.01 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 7.27 02-OCT-16:00 73.14 09-OCT-06:00
November 180.00 01-NOV-00:10 77.01 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 100.12 24-NOV-07:00
December 180.00 01-DEC-00:10 77.01 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 116.47 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 0.00   10.39  
Maximum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 44.34   138.93  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3094.06 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 686.67 02-JAN-05:00
February 26988.77 01-FEB-00:10 3094.06 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 704.09 06-FEB-03:00
March 26988.77 01-MAR-00:10 3094.06 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 541.78 23-MAR-04:30
April 26988.77 01-APR-00:10 3094.06 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 48.86 07-APR-13:00 399.59 03-APR-06:00
May 26988.77 01-MAY-00:10 3094.06 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 96.79 30-MAY-13:00 321.76 01-MAY-05:00
June 26988.77 01-JUN-00:10 3094.06 01-JUN-19:19 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 201.01 19-JUN-12:00 187.54 03-JUN-04:00
July 26988.77 01-JUL-00:10 3094.06 03-JUL-19:30 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 158.05 07-JUL-12:00 98.67 02-JUL-05:00
August 26988.77 01-AUG-00:10 3094.06 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 156.97 24-AUG-15:40 157.62 08-AUG-05:00
September 26988.77 01-SEP-00:10 3094.06 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 112.84 01-SEP-14:00 251.48 24-SEP-05:34
October 26988.77 01-OCT-23:10 3094.06 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 28.55 25-OCT-10:53 402.04 09-OCT-06:00
November 26988.77 01-NOV-00:10 3094.06 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 526.84 24-NOV-06:00
December 26988.77 01-DEC-00:10 3094.06 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 610.14 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 0.00   98.67  
Maximum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 201.01   704.09  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3094.06 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 690.87 02-JAN-05:00
February 26988.77 01-FEB-00:10 3094.06 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 708.36 06-FEB-03:00
March 26988.77 01-MAR-00:10 3094.06 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 544.42 23-MAR-06:00
April 26988.77 01-APR-00:10 3094.06 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 44.28 07-APR-13:00 399.59 03-APR-06:00
May 26988.77 01-MAY-00:10 3094.06 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 96.79 30-MAY-13:00 321.76 01-MAY-05:00
June 26988.77 01-JUN-00:10 3094.06 01-JUN-19:19 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 201.00 19-JUN-12:00 187.56 03-JUN-04:00
July 26988.77 01-JUL-00:10 3094.06 03-JUL-19:30 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 158.05 07-JUL-12:00 98.67 02-JUL-05:00
August 26988.77 01-AUG-00:10 3094.06 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 156.97 24-AUG-15:40 157.62 08-AUG-05:00
September 26988.77 01-SEP-00:10 3094.06 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 112.84 01-SEP-14:00 252.62 24-SEP-05:34
October 26988.77 01-OCT-23:10 3094.06 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 25.11 25-OCT-10:53 402.05 09-OCT-06:00
November 26988.77 01-NOV-00:10 3094.06 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 530.67 24-NOV-06:00
December 26988.77 01-DEC-00:10 3094.06 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 610.15 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 0.00   98.67  
Maximum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 201.00   708.36  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1089.83 02-JAN-20:10 14912.86 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 0.00 01-JAN-00:03 618.34 02-JAN-07:00
February 2401.70 01-FEB-00:10 1089.83 01-FEB-20:10 14912.86 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 0.00 01-FEB-00:03 630.97 06-FEB-07:00
March 2401.70 01-MAR-00:10 1089.83 01-MAR-20:10 14912.86 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 0.00 01-MAR-00:03 487.33 23-MAR-06:00
April 2401.70 01-APR-00:10 1089.83 03-APR-19:10 14912.86 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 38.35 07-APR-13:00 357.64 03-APR-06:00
May 2401.70 01-MAY-00:10 1089.83 01-MAY-19:10 14912.86 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 86.79 30-MAY-13:00 300.86 01-MAY-06:05
June 2401.70 01-JUN-00:10 1089.83 01-JUN-19:10 14912.86 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 180.11 19-JUN-12:00 166.60 03-JUN-05:00
July 2401.70 01-JUL-00:10 1089.83 03-JUL-19:10 14912.86 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 141.66 07-JUL-12:00 88.31 02-JUL-05:00
August 2401.70 01-AUG-00:10 1089.83 01-AUG-19:10 14912.86 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 140.71 24-AUG-15:40 141.11 08-AUG-05:00
September 2401.70 01-SEP-00:10 1089.83 01-SEP-19:10 14912.86 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 100.60 01-SEP-14:00 235.70 24-SEP-05:34
October 2401.70 01-OCT-23:10 1089.83 02-OCT-19:10 14912.86 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 13.46 04-OCT-13:00 367.46 31-OCT-06:10
November 2401.70 01-NOV-00:10 1089.83 01-NOV-19:10 14912.86 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 0.00 01-NOV-00:05 475.83 24-NOV-07:00
December 2401.70 01-DEC-00:10 1089.83 01-DEC-20:10 14912.86 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 0.00 01-DEC-00:03 546.19 31-DEC-24:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1089.83   14912.86   22492.83   0.00 0.00 0.00 0.00   88.31  
Maximum of Months 2401.70   1089.83   14912.86   22492.83   0.00 0.00 0.00 180.11   630.97  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 2371.52 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 563.75 02-JAN-05:00
February 2395.44 01-FEB-00:10 2371.52 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 579.12 06-FEB-03:00
March 2395.44 01-MAR-00:10 2371.52 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.90 27-MAR-16:00 427.97 23-MAR-06:00
April 2395.44 01-APR-00:10 2371.52 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 49.33 07-APR-13:00 302.25 03-APR-06:00
May 2395.44 01-MAY-00:10 2371.52 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 84.79 30-MAY-13:00 236.15 01-MAY-05:00
June 2395.44 01-JUN-00:10 2371.52 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 176.10 19-JUN-12:00 145.99 03-JUN-03:00
July 2395.44 01-JUL-00:10 2371.52 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 138.46 07-JUL-12:00 70.62 02-JUL-03:00
August 2395.44 01-AUG-00:10 2371.52 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 137.51 24-AUG-15:00 120.93 08-AUG-05:00
September 2395.44 01-SEP-00:10 2371.52 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 98.85 01-SEP-14:00 185.54 30-SEP-01:00
October 2395.44 01-OCT-23:10 2371.52 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 24.85 25-OCT-10:53 304.10 09-OCT-06:00
November 2395.44 01-NOV-00:10 2371.52 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 416.84 24-NOV-07:00
December 2395.44 01-DEC-00:10 2371.52 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 485.22 31-DEC-24:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   2371.52   0.00 0.00 0.00 0.00 0.00 0.00   70.62  
Maximum of Months 2395.44   2371.52   0.00 0.00 0.00 0.00 0.00 176.10   579.12  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 35196.04 19-JAN-20:10 17891.83 28370.69 20227.60 0.00 0.00 0.00 0.00 0.00 0.00
February 31136.11 01-FEB-20:38 80513.24 127668.10 91024.21 0.00 0.00 0.00 0.00 0.00 0.00
March 22296.35 04-MAR-00:46 92015.14 25218.23 25550.66 0.00 0.00 0.00 0.00 0.00 0.00
April 23040.62 12-APR-22:27 115018.92 47285.09 42584.43 0.00 0.00 0.00 0.00 0.00 0.00
May 21676.78 14-MAY-01:02 44729.58 15761.39 15969.16 0.00 0.00 0.00 0.00 0.00 0.00
June 17414.25 22-JUN-18:10 53675.50 75655.77 57488.97 0.00 0.00 0.00 0.00 0.00 0.00
July 17905.30 11-JUL-18:08 53675.50 75655.77 57488.97 0.00 0.00 0.00 0.00 0.00 0.00
August 19218.40 25-AUG-21:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
September 22914.88 24-SEP-05:17 71567.33 37828.07 34067.54 0.00 0.00 0.00 0.00 0.00 0.00
October 38083.22 27-OCT-21:45 115018.92 94570.17 74522.74 0.00 0.00 0.00 0.00 0.00 0.00
November 37019.61 12-NOV-23:40 102239.04 47285.09 42584.43 0.00 0.00 0.00 0.00 0.00 0.00
December 36005.90 20-DEC-20:21 62621.41 99297.41 70796.61 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17414.25   10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38083.22   115018.92 127668.10 91024.21 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4309.33 17-JAN-12:30 779.69 587.01 757.77 0.00 0.00 0.00 0.00 0.00 178.58
February 3984.85 02-FEB-13:28 2598.96 1956.71 2525.91 0.00 0.00 0.00 0.00 0.00 220.59
March 5327.76 29-MAR-13:31 1819.27 1369.70 1768.14 0.00 0.00 0.00 0.00 0.00 203.79
April 3561.98 08-APR-12:30 389.84 195.67 252.59 0.00 0.00 0.00 0.00 0.00 4.73
May 2938.37 14-MAY-01:02 4548.18 782.68 1082.53 0.00 0.00 0.00 0.00 0.00 154.79
June 3120.76 19-JUN-13:10 259.90 195.67 252.59 0.00 0.00 0.00 0.00 123.39 0.00
July 3322.29 08-JUL-12:00 389.84 195.67 252.59 0.00 0.00 0.00 0.00 94.12 0.00
August 4061.75 18-AUG-12:40 259.90 195.67 252.59 0.00 0.00 0.00 0.00 103.70 0.00
September 4457.72 01-SEP-13:47 779.69 587.01 757.77 0.00 0.00 0.00 0.00 79.69 0.00
October 4470.45 04-OCT-12:10 259.90 195.67 252.59 0.00 0.00 0.00 0.00 5.84 0.00
November 4683.14 18-NOV-11:01 2728.91 1369.70 1768.14 0.00 0.00 0.00 0.00 0.00 215.75
December 5384.71 03-DEC-11:07 2728.91 1643.63 2020.73 0.00 0.00 0.00 0.00 0.00 221.44
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2938.37   259.90 195.67 252.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5384.71   4548.18 1956.71 2525.91 0.00 0.00 0.00 0.00 123.39 221.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2001.30 19-JAN-23:50 8125.92 1631.43 2005.72 0.00 0.00 0.00 0.00 0.00 84.07
February 2029.14 18-FEB-16:28 2257.20 1132.94 1462.51 0.00 0.00 0.00 0.00 0.00 75.66
March 2108.21 04-MAR-00:15 8125.92 1087.62 1504.29 0.00 0.00 0.00 0.00 0.00 70.63
April 2254.22 12-APR-22:27 13543.20 2719.05 3342.87 0.00 0.00 0.00 0.00 0.00 79.62
May 2165.37 14-MAY-01:02 5266.80 906.35 1253.58 0.00 0.00 0.00 0.00 0.00 70.41
June 2193.43 19-JUN-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 21.89 0.00
July 2208.17 10-JUL-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 14.34 0.00
August 2272.90 04-AUG-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 36.16 0.00
September 2171.67 01-SEP-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 12.05 0.00
October 3009.21 26-OCT-22:05 2708.64 543.81 668.57 0.00 0.00 0.00 0.00 0.00 74.55
November 2310.65 07-NOV-01:03 5417.28 543.81 835.72 0.00 0.00 0.00 0.00 0.00 77.63
December 1911.46 03-DEC-23:05 2407.68 543.81 668.57 0.00 0.00 0.00 0.00 0.00 77.07
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1911.46   1203.84 543.81 668.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3009.21   13543.20 2719.05 3342.87 0.00 0.00 0.00 0.00 36.16 84.07



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1726.09 19-JAN-23:50 1718.50 2720.79 2120.71 0.00 0.00 0.00 0.00 0.00 182.34
February 1401.53 18-FEB-15:46 954.72 3778.88 3092.70 0.00 0.00 0.00 0.00 0.00 164.80
March 1847.98 04-MAR-00:46 2291.33 2418.48 2120.71 0.00 0.00 0.00 0.00 0.00 157.40
April 1992.30 12-APR-22:27 2864.16 4534.65 3534.51 0.00 0.00 0.00 0.00 0.00 173.34
May 1971.56 14-MAY-01:02 1113.84 1511.55 1325.44 0.00 0.00 0.00 0.00 0.00 156.74
June 1967.22 19-JUN-21:00 254.59 1209.24 795.27 0.00 0.00 0.00 0.00 51.72 0.00
July 2209.59 10-JUL-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 45.33 0.00
August 2247.29 17-AUG-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 51.44 0.00
September 1881.39 01-SEP-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 28.47 0.00
October 2139.19 26-OCT-22:30 2864.16 4534.65 3534.51 0.00 0.00 0.00 0.00 0.00 172.39
November 2054.22 07-NOV-01:03 1145.66 906.93 883.63 0.00 0.00 0.00 0.00 0.00 169.43
December 1650.08 03-DEC-23:05 509.18 906.93 706.90 0.00 0.00 0.00 0.00 0.00 166.77
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1401.53   222.77 906.93 706.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2247.29   2864.16 4534.65 3534.51 0.00 0.00 0.00 0.00 51.72 182.34



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 814.59 19-JAN-23:50 1321.92 455.43 611.77 0.00 0.00 0.00 0.00 0.00 103.20
February 664.79 24-FEB-16:21 856.80 442.80 624.51 0.00 0.00 0.00 0.00 0.00 89.83
March 882.97 04-MAR-00:46 1762.56 404.83 611.77 0.00 0.00 0.00 0.00 0.00 89.66
April 940.75 12-APR-22:27 2203.20 759.06 1019.61 0.00 0.00 0.00 0.00 0.00 97.72
May 934.20 14-MAY-01:02 856.80 253.02 382.35 0.00 0.00 0.00 0.00 0.00 88.52
June 815.14 22-JUN-18:10 1028.16 1214.49 1376.47 0.00 0.00 0.00 0.00 31.70 0.00
July 834.80 11-JUL-18:08 1028.16 1214.49 1376.47 0.00 0.00 0.00 0.00 17.96 0.00
August 874.09 04-AUG-21:00 195.84 202.41 229.41 0.00 0.00 0.00 0.00 49.30 0.00
September 818.03 01-SEP-18:08 1028.16 1214.49 1376.47 0.00 0.00 0.00 0.00 24.64 0.00
October 1012.55 26-OCT-22:30 2203.20 759.06 1019.61 0.00 0.00 0.00 0.00 0.00 97.29
November 979.73 07-NOV-01:03 881.28 151.82 254.90 0.00 0.00 0.00 0.00 0.00 96.32
December 779.49 03-DEC-23:05 391.68 151.81 203.92 0.00 0.00 0.00 0.00 0.00 94.40
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 664.79   195.84 151.81 203.92 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1012.55   2203.20 1214.49 1376.47 0.00 0.00 0.00 0.00 49.30 103.20



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 50707.70 03-JAN-20:46 7056.00 3572.14 45728.01 397265.76 0.00 0.00 0.00 0.00 300.88
February 50701.00 01-FEB-20:38 6350.40 3214.92 41155.21 357539.19 0.00 0.00 0.00 0.00 305.23
March 50495.57 20-MAR-19:27 7056.00 3572.14 45728.01 397265.76 0.00 0.00 0.00 0.00 310.00
April 50163.61 13-APR-19:15 7056.00 3572.14 45728.01 397265.76 0.00 0.00 0.00 0.00 310.10
May 38626.70 01-MAY-20:20 2419.20 952.57 12996.38 112907.11 0.00 0.00 0.00 0.00 232.26
June 38917.85 19-JUN-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 86.11 0.00
July 38870.02 10-JUL-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 61.90 0.00
August 39016.04 04-AUG-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 116.67 0.00
September 38752.39 01-SEP-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 33.38 0.00
October 51194.55 27-OCT-20:14 8064.00 3175.23 43321.27 376357.04 0.00 0.00 0.00 0.00 285.57
November 51648.83 29-NOV-21:50 8064.00 3175.23 43321.27 376357.04 0.00 0.00 0.00 0.00 332.11
December 51124.76 20-DEC-20:26 4939.20 2500.50 32009.60 278086.04 0.00 0.00 0.00 0.00 321.40
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 38626.70   705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 51648.83   8064.00 3572.14 45728.01 397265.76 0.00 0.00 0.00 116.67 332.11



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 16682.81 17-JAN-12:30 10245.60 895.64 1066.88 0.00 0.00 0.00 0.00 0.00 395.63
February 16885.66 02-FEB-13:28 34152.00 2985.45 3556.27 0.00 0.00 0.00 0.00 0.00 487.73
March 21774.34 29-MAR-13:31 23906.40 2089.82 2489.39 0.00 0.00 0.00 0.00 0.00 450.59
April 14672.54 12-APR-22:27 153684.00 5873.02 4064.31 0.00 0.00 0.00 0.00 0.00 453.97
May 13645.87 14-MAY-01:02 59766.00 1957.67 1524.12 0.00 0.00 0.00 0.00 0.00 389.70
June 12165.10 19-JUN-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 120.79 0.00
July 11999.50 10-JUL-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 80.09 0.00
August 13747.94 19-AUG-13:00 5122.80 298.55 355.63 0.00 0.00 0.00 0.00 85.66 0.00
September 15303.21 30-SEP-12:40 5122.80 298.55 355.63 0.00 0.00 0.00 0.00 0.00 95.63
October 17885.02 08-OCT-09:30 25614.00 1074.76 1219.29 0.00 0.00 0.00 0.00 0.00 454.97
November 20025.62 18-NOV-11:01 35859.60 2089.82 2489.39 0.00 0.00 0.00 0.00 0.00 480.15
December 22336.11 17-DEC-10:08 42690.00 1791.27 2032.15 0.00 0.00 0.00 0.00 0.00 421.36
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 11999.50   5122.80 298.55 355.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22336.11   153684.00 5873.02 4064.31 0.00 0.00 0.00 0.00 120.79 487.73



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 45976.30 19-JAN-22:50 91245.96 13686.91 14779.89 0.00 0.00 0.00 0.00 0.00 1456.82
February 41669.74 18-FEB-16:28 76038.30 13259.20 18474.86 0.00 0.00 0.00 0.00 0.00 1275.76
March 60311.43 28-MAR-21:57 364983.84 54747.65 59119.55 0.00 0.00 0.00 0.00 0.00 1291.74
April 65143.00 11-APR-21:49 456229.80 68434.56 73899.43 0.00 0.00 0.00 0.00 0.00 1227.11
May 52077.75 16-MAY-04:15 364983.84 18249.22 25336.95 0.00 0.00 0.00 0.00 0.00 1193.00
June 42272.40 19-JUN-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 344.97 0.00
July 42627.21 10-JUL-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 228.67 0.00
August 43844.34 04-AUG-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 546.00 0.00
September 42640.86 01-SEP-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 190.05 0.00
October 72518.94 21-OCT-05:42 212907.24 20530.37 25336.95 0.00 0.00 0.00 0.00 0.00 1125.64
November 65370.53 06-NOV-22:27 456229.80 68434.56 73899.43 0.00 0.00 0.00 0.00 0.00 1277.56
December 45118.47 03-DEC-21:50 162215.04 27373.82 29559.77 0.00 0.00 0.00 0.00 0.00 1343.42
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 41669.74   45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 72518.94   456229.80 68434.56 73899.43 0.00 0.00 0.00 0.00 546.00 1456.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2997.06 19-JAN-16:01 777.60 274.41 547.87 0.00 0.00 0.00 0.00 0.00 102.24
February 3011.53 02-FEB-16:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 0.00 133.11
March 3105.53 07-MAR-16:01 874.80 308.71 616.35 0.00 0.00 0.00 0.00 0.00 106.33
April 3272.28 10-APR-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 18.75
May 3320.49 27-MAY-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 0.00 6.77
June 3353.35 15-JUN-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 25.98 0.00
July 3393.51 13-JUL-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 49.73 0.00
August 3433.14 21-AUG-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 49.77 0.00
September 3440.34 07-SEP-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 25.17 0.00
October 3098.24 04-OCT-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 5.24 0.00
November 3073.32 02-NOV-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 0.00 41.85
December 2977.34 17-DEC-16:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 0.00 89.68
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2977.34   324.00 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3440.34   874.80 308.71 616.35 0.00 0.00 0.00 0.00 49.77 133.11



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1748.28 17-JAN-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 84.87
February 2641.80 20-FEB-16:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 101.86
March 2986.36 07-MAR-16:01 874.80 308.68 616.28 0.00 0.00 0.00 0.00 0.00 105.71
April 3151.99 10-APR-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 18.21
May 3222.78 27-MAY-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 6.69
June 3260.17 15-JUN-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 25.95 0.00
July 3282.58 07-JUL-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 30.00 0.00
August 3297.62 12-AUG-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 40.31 0.00
September 3208.28 07-SEP-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 25.49 0.00
October 3140.85 03-OCT-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 3.64 0.00
November 2932.76 03-NOV-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 38.82
December 1189.52 17-DEC-19:03 1170.00 1224.91 1290.50 0.00 0.00 0.00 0.00 0.00 97.27
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1189.52   324.00 205.78 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3297.62   1170.00 1224.91 1290.50 0.00 0.00 0.00 0.00 40.31 105.71



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 198.05 19-JAN-14:40 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 28.54
February 318.22 20-FEB-13:23 0.00 101.63 299.27 0.00 0.00 0.00 0.00 0.00 28.27
March 486.35 03-MAR-13:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 17.13
April 633.66 08-APR-12:30 0.00 25.41 74.82 0.00 0.00 0.00 0.00 0.42 0.00
May 509.30 30-MAY-12:50 0.00 21.56 67.08 0.00 0.00 0.00 0.00 12.24 0.00
June 536.34 19-JUN-13:20 0.00 21.56 67.08 0.00 0.00 0.00 0.00 20.95 0.00
July 563.59 10-JUL-13:10 0.00 21.56 67.08 0.00 0.00 0.00 0.00 16.50 0.00
August 698.25 30-AUG-13:00 0.00 21.56 67.08 0.00 0.00 0.00 0.00 7.20 0.00
September 742.82 30-SEP-12:40 0.00 25.41 74.82 0.00 0.00 0.00 0.00 0.00 5.79
October 796.57 04-OCT-12:10 0.00 21.56 67.08 0.00 0.00 0.00 0.00 2.13 0.00
November 648.83 02-NOV-13:00 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 15.24
December 492.07 17-DEC-13:40 0.00 50.81 149.63 0.00 0.00 0.00 0.00 0.00 21.98
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 198.05   0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 796.57   0.00 101.63 299.27 0.00 0.00 0.00 0.00 20.95 28.54



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 602.00 03-JAN-19:03 1386.00 685.40 1264.50 0.00 0.00 0.00 0.00 0.00 26.73
February 580.06 01-FEB-19:03 1386.00 685.40 1264.50 0.00 0.00 0.00 0.00 0.00 30.24
March 806.93 28-MAR-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 0.00 17.09
April 927.76 08-APR-15:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 0.00 2.39
May 996.65 29-MAY-15:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 5.03 0.00
June 1011.01 20-JUN-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 7.57 0.00
July 1016.69 11-JUL-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 10.11 0.00
August 1015.23 22-AUG-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 13.03 0.00
September 993.14 01-SEP-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 13.79 0.00
October 890.25 04-OCT-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 3.54 0.00
November 807.11 05-NOV-08:62 270.00 215.63 799.99 0.00 0.00 0.00 0.00 0.00 24.50
December 466.82 29-DEC-19:04 970.20 479.78 885.15 0.00 0.00 0.00 0.00 0.00 31.17
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 466.82   270.00 129.38 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1016.69   1386.00 685.40 1264.50 0.00 0.00 0.00 0.00 13.79 31.17



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2446.74 19-JAN-09:01 252.00 377.32 792.83 0.00 0.00 0.00 0.00 0.00 118.08
February 2666.67 25-FEB-09:01 378.00 480.22 1143.15 0.00 0.00 0.00 0.00 0.00 181.21
March 2854.21 07-MAR-09:01 360.00 539.02 1132.61 0.00 0.00 0.00 0.00 0.00 118.84
April 2931.70 10-APR-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 17.27
May 3003.40 31-MAY-08:62 216.00 323.41 679.57 0.00 0.00 0.00 0.00 2.25 0.00
June 3112.29 23-JUN-08:62 216.00 323.41 679.57 0.00 0.00 0.00 0.00 26.81 0.00
July 3082.24 13-JUL-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 50.83 0.00
August 3112.89 01-AUG-08:62 216.00 323.41 679.57 0.00 0.00 0.00 0.00 28.13 0.00
September 3101.04 07-SEP-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 26.50 0.00
October 2969.61 03-OCT-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 3.79 0.00
November 2807.85 02-NOV-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 0.00 41.61
December 2655.02 20-DEC-09:01 360.00 539.02 1132.61 0.00 0.00 0.00 0.00 0.00 111.44
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2446.74   216.00 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3112.89   680.40 539.02 1143.15 0.00 0.00 0.00 0.00 50.83 181.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1106.98 26-JAN-09:03 252.00 377.27 792.74 0.00 0.00 0.00 0.00 0.00 152.13
February 2146.51 19-FEB-09:01 378.00 480.16 1143.02 0.00 0.00 0.00 0.00 0.00 124.03
March 2683.05 03-MAR-09:02 216.00 323.38 679.49 0.00 0.00 0.00 0.00 0.00 84.25
April 2830.22 08-APR-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 11.07
May 2985.42 31-MAY-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 21.43 0.00
June 3030.77 23-JUN-08:62 216.00 323.38 679.49 0.00 0.00 0.00 0.00 26.64 0.00
July 3043.27 14-JUL-08:62 216.00 323.38 679.49 0.00 0.00 0.00 0.00 34.18 0.00
August 3069.06 02-AUG-08:62 216.00 323.38 679.49 0.00 0.00 0.00 0.00 37.82 0.00
September 3018.60 01-SEP-08:61 252.00 377.27 792.74 0.00 0.00 0.00 0.00 22.43 0.00
October 2732.24 02-OCT-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 3.08 0.00
November 2452.06 06-NOV-09:02 216.00 323.38 679.49 0.00 0.00 0.00 0.00 0.00 96.38
December 1035.01 09-DEC-09:03 378.00 480.16 1143.02 0.00 0.00 0.00 0.00 0.00 150.87
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1035.01   216.00 205.78 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3069.06   583.20 480.16 1143.02 0.00 0.00 0.00 0.00 37.82 152.13



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2752.87 19-JAN-23:50 13580.14 4481.56 0.00 0.00 0.00 0.00 0.00 0.00 139.55
February 3028.69 18-FEB-16:28 3772.26 3112.20 0.00 0.00 0.00 0.00 0.00 0.00 132.57
March 2988.01 04-MAR-00:46 18106.85 3983.61 0.00 0.00 0.00 0.00 0.00 0.00 121.74
April 3303.42 12-APR-22:27 22633.56 7469.27 0.00 0.00 0.00 0.00 0.00 0.00 137.07
May 3175.12 14-MAY-01:02 8801.94 2489.76 0.00 0.00 0.00 0.00 0.00 0.00 120.82
June 2791.10 22-JUN-18:10 10562.33 11950.84 0.00 0.00 0.00 0.00 0.00 39.28 0.00
July 3062.38 10-JUL-18:13 5281.16 5975.42 0.00 0.00 0.00 0.00 0.00 45.12 0.00
August 3145.04 22-AUG-19:00 3520.78 3983.61 0.00 0.00 0.00 0.00 0.00 21.87 0.00
September 2808.28 01-SEP-18:08 10562.33 11950.84 0.00 0.00 0.00 0.00 0.00 29.60 0.00
October 3447.02 26-OCT-22:30 22633.56 7469.27 0.00 0.00 0.00 0.00 0.00 0.00 132.88
November 3350.37 07-NOV-01:03 9053.42 1493.85 0.00 0.00 0.00 0.00 0.00 0.00 132.07
December 2645.78 03-DEC-23:05 4023.74 1493.85 0.00 0.00 0.00 0.00 0.00 0.00 128.16
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2645.78   3520.78 1493.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3447.02   22633.56 11950.84 0.00 0.00 0.00 0.00 0.00 45.12 139.55



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3137.36 19-JAN-16:01 777.60 274.41 547.87 0.00 0.00 0.00 0.00 0.00 102.71
February 3140.42 02-FEB-16:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 0.00 133.32
March 3248.98 07-MAR-16:01 874.80 308.71 616.35 0.00 0.00 0.00 0.00 0.00 106.72
April 3420.07 10-APR-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 19.06
May 3476.98 27-MAY-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 0.00 7.21
June 3589.54 19-JUN-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 66.62 0.00
July 3569.84 07-JUL-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 58.53 0.00
August 3601.34 01-AUG-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 50.44 0.00
September 3556.16 07-SEP-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 24.64 0.00
October 3364.89 04-OCT-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 5.01 0.00
November 3205.02 02-NOV-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 0.00 42.04
December 3121.90 17-DEC-16:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 0.00 90.36
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3121.90   324.00 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3601.34   874.80 308.71 616.35 0.00 0.00 0.00 0.00 66.62 133.32



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1034.39 20-JAN-16:02 972.00 342.97 684.76 0.00 0.00 0.00 0.00 0.00 103.53
February 2184.20 20-FEB-16:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 101.51
March 3099.07 07-MAR-16:01 874.80 308.68 616.28 0.00 0.00 0.00 0.00 0.00 105.62
April 3284.36 10-APR-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 18.47
May 3366.92 27-MAY-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 7.11
June 3362.85 02-JUN-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 3.35
July 3478.61 07-JUL-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 58.59 0.00
August 3477.21 04-AUG-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 54.15 0.00
September 3318.77 11-SEP-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 15.53
October 3289.54 03-OCT-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 3.36 0.00
November 3013.85 03-NOV-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 37.99
December 1166.15 08-DEC-16:03 680.40 240.08 479.33 0.00 0.00 0.00 0.00 0.00 110.94
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1034.39   324.00 205.78 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3478.61   972.00 342.97 684.76 0.00 0.00 0.00 0.00 58.59 110.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1709.72 20-JAN-16:01 972.00 215.63 670.96 0.00 0.00 0.00 0.00 0.00 59.33
February 1693.98 02-FEB-16:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 0.00 69.29
March 1713.89 07-MAR-16:01 874.80 194.07 603.86 0.00 0.00 0.00 0.00 0.00 55.00
April 1783.54 10-APR-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 0.00 9.67
May 1804.61 27-MAY-15:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 0.00 3.44
June 1843.16 15-JUN-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 12.98 0.00
July 1845.88 16-JUL-15:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 26.51 0.00
August 1896.18 18-AUG-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 33.26 0.00
September 1863.40 06-SEP-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 10.59 0.00
October 1836.37 04-OCT-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 2.28 0.00
November 1718.75 02-NOV-15:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 0.00 22.36
December 1692.27 17-DEC-16:01 378.00 177.90 523.86 0.00 0.00 0.00 0.00 0.00 47.44
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1692.27   324.00 129.38 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1896.18   972.00 215.63 670.96 0.00 0.00 0.00 0.00 33.26 69.29



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 37322.73 19-JAN-23:50 161932.61 6188.11 40487.42 0.00 0.00 0.00 0.00 0.00 330.24
February 27402.85 01-FEB-19:50 209912.64 27502.72 67479.03 0.00 0.00 0.00 0.00 0.00 322.58
March 33084.01 11-MAR-23:11 146938.85 7219.46 47235.32 0.00 0.00 0.00 0.00 0.00 302.52
April 34557.15 12-APR-22:27 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 297.13
May 30965.00 16-MAY-03:37 161932.61 2062.70 13495.81 0.00 0.00 0.00 0.00 0.00 273.09
June 23718.41 19-JUN-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 72.81 0.00
July 23468.51 10-JUL-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 48.26 0.00
August 23825.34 04-AUG-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 110.58 0.00
September 24860.44 24-SEP-05:36 104956.32 5156.76 28116.26 0.00 0.00 0.00 0.00 0.00 245.86
October 36520.12 26-OCT-22:59 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 289.07
November 38099.89 06-NOV-23:42 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 289.93
December 30975.27 04-DEC-23:34 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 284.85
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 23468.51   26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38099.89   269887.68 27502.72 67479.03 0.00 0.00 0.00 0.00 110.58 330.24



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 39382.16 19-JAN-23:50 161932.61 6188.11 40487.42 0.00 0.00 0.00 0.00 0.00 332.05
February 31706.19 01-FEB-19:38 209912.64 27502.72 67479.03 0.00 0.00 0.00 0.00 0.00 321.40
March 34803.46 11-MAR-23:11 146938.85 7219.46 47235.32 0.00 0.00 0.00 0.00 0.00 303.42
April 37689.71 12-APR-22:27 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 296.57
May 32920.33 15-MAY-05:47 62973.79 3300.33 16869.76 0.00 0.00 0.00 0.00 0.00 268.63
June 24925.96 19-JUN-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 72.78 0.00
July 24634.72 10-JUL-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 48.24 0.00
August 24997.59 04-AUG-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 110.56 0.00
September 27452.14 24-SEP-05:36 104956.32 5156.76 28116.26 0.00 0.00 0.00 0.00 0.00 246.04
October 37121.84 26-OCT-22:59 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 288.93
November 36241.84 06-NOV-23:42 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 291.65
December 32732.11 04-DEC-23:34 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 286.59
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 24634.72   26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 39382.16   269887.68 27502.72 67479.03 0.00 0.00 0.00 0.00 110.56 332.05



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 38400.91 19-JAN-23:50 14410.22 2179.66 89477.13 22492.83 0.00 0.00 0.00 0.00 301.65
February 37508.55 18-FEB-16:28 4002.84 1513.65 74564.28 112464.16 0.00 0.00 0.00 0.00 258.46
March 36665.68 29-MAR-15:51 9339.96 2119.12 104389.99 157449.82 0.00 0.00 0.00 0.00 288.36
April 35598.79 19-APR-09:21 3735.98 2119.12 104389.99 131208.19 0.00 0.00 0.00 0.00 243.51
May 32986.96 15-MAY-05:54 18679.92 4843.69 125511.30 74976.11 0.00 0.00 0.00 0.00 241.90
June 32864.94 22-JUN-18:10 11207.95 5812.43 89477.13 89971.33 0.00 0.00 0.00 65.29 0.00
July 32413.64 11-JUL-18:08 11207.95 5812.43 89477.13 89971.33 0.00 0.00 0.00 38.28 0.00
August 34838.51 24-AUG-16:57 5337.12 1210.92 59651.42 89971.33 0.00 0.00 0.00 119.63 0.00
September 31476.78 01-SEP-18:08 11207.95 5812.43 89477.13 89971.33 0.00 0.00 0.00 51.49 0.00
October 35655.36 27-OCT-07:40 8539.39 3874.95 119302.85 119961.77 0.00 0.00 0.00 0.00 283.23
November 40163.50 30-NOV-13:52 3202.27 1816.39 89477.13 89971.33 0.00 0.00 0.00 0.00 266.77
December 36135.94 04-DEC-17:11 9339.96 2119.12 104389.99 157449.82 0.00 0.00 0.00 0.00 270.96
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 31476.78   3202.27 1210.92 59651.42 22492.83 0.00 0.00 0.00 0.00 0.00
Maximum of Months 40163.50   18679.92 5812.43 125511.30 157449.82 0.00 0.00 0.00 119.63 301.65



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5736.76 19-JAN-12:07 5323.20 6587.56 0.00 0.00 0.00 0.00 0.00 0.00 213.71
February 6291.45 18-FEB-16:28 3992.40 3293.78 0.00 0.00 0.00 0.00 0.00 0.00 237.29
March 6099.13 04-MAR-00:46 19163.52 4216.04 0.00 0.00 0.00 0.00 0.00 0.00 214.74
April 6496.83 12-APR-22:27 23954.40 7905.07 0.00 0.00 0.00 0.00 0.00 0.00 233.82
May 6403.05 14-MAY-01:02 9315.60 2635.02 0.00 0.00 0.00 0.00 0.00 0.00 210.60
June 6746.65 19-JUN-14:10 798.48 658.76 0.00 0.00 0.00 0.00 0.00 142.52 0.00
July 7130.15 08-JUL-12:00 798.48 658.76 0.00 0.00 0.00 0.00 0.00 115.44 0.00
August 7302.76 16-AUG-12:50 532.32 658.76 0.00 0.00 0.00 0.00 0.00 111.28 0.00
September 6681.40 01-SEP-14:10 798.48 658.76 0.00 0.00 0.00 0.00 0.00 97.70 0.00
October 6812.62 26-OCT-22:30 23954.40 7905.07 0.00 0.00 0.00 0.00 0.00 0.00 227.35
November 6638.32 07-NOV-01:03 9581.76 1581.01 0.00 0.00 0.00 0.00 0.00 0.00 226.65
December 5329.29 03-DEC-23:05 4258.56 1581.01 0.00 0.00 0.00 0.00 0.00 0.00 224.07
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 5329.29   532.32 658.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7302.76   23954.40 7905.07 0.00 0.00 0.00 0.00 0.00 142.52 237.29



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.383214E+12 257030.83 19-JAN-20:10 0.633424E+12 552115.21 14-JAN-17:10
February 0.345694E+12 242843.52 22-FEB-20:19 0.564911E+12 560006.54 05-FEB-19:10
March 0.384867E+12 268662.09 27-MAR-18:10 0.522172E+12 460153.02 05-MAR-18:00
April 0.386132E+12 329039.52 07-APR-19:10 0.464783E+12 507412.10 01-APR-20:30
May 0.443119E+12 348131.01 31-MAY-19:19 0.425535E+12 351763.38 04-MAY-17:40
June 0.587270E+12 419870.13 19-JUN-19:30 0.388413E+12 352394.90 01-JUN-17:10
July 0.714879E+12 419134.24 20-JUL-19:30 0.392558E+12 348386.46 11-JUL-17:10
August 0.677975E+12 454905.91 04-AUG-19:10 0.391045E+12 350492.12 30-AUG-17:00
September 0.531760E+12 414171.56 13-SEP-19:00 0.384711E+12 347960.57 26-SEP-17:19
October 0.451829E+12 345415.26 05-OCT-19:10 0.429285E+12 391240.28 27-OCT-16:49
November 0.376675E+12 248502.09 07-NOV-20:49 0.494796E+12 433154.92 29-NOV-19:10
December 0.387409E+12 244560.10 18-DEC-20:10 0.556950E+12 520832.70 31-DEC-19:10
             
Annual Sum or Average 0.567082E+13     0.564858E+13    
Minimum of Months 0.345694E+12 242843.52   0.384711E+12 347960.57  
Maximum of Months 0.714879E+12 454905.91   0.633424E+12 560006.54  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.654865E+11 0.251006E+11 0.148212E+12 0.553310E+11 0.438231E+11 0.513403E+10 0.00 0.162124E+10 0.00 0.00 0.256175E+11 0.770508E+10 0.00
February 0.590035E+11 0.210500E+11 0.133859E+12 0.499764E+11 0.390134E+11 0.515526E+10 0.00 0.203932E+10 0.00 0.00 0.239727E+11 0.696282E+10 0.00
March 0.652066E+11 0.210778E+11 0.148223E+12 0.553337E+11 0.441630E+11 0.738505E+10 0.00 0.624398E+10 0.00 0.00 0.243038E+11 0.770329E+10 0.00
April 0.628376E+11 0.181673E+11 0.143397E+12 0.535455E+11 0.438299E+11 0.970644E+10 0.00 0.256396E+11 0.00 0.00 0.164646E+11 0.746526E+10 0.00
May 0.647884E+11 0.167955E+11 0.148223E+12 0.553319E+11 0.479710E+11 0.137228E+11 0.00 0.754869E+11 0.00 0.00 0.780028E+10 0.770467E+10 0.00
June 0.626255E+11 0.152105E+11 0.143446E+12 0.535480E+11 0.508598E+11 0.146754E+11 0.00 0.220917E+12 0.00 0.00 0.133494E+11 0.745684E+10 0.00
July 0.646311E+11 0.161837E+11 0.148174E+12 0.553289E+11 0.557770E+11 0.159983E+11 0.00 0.320858E+12 0.00 0.00 0.248716E+11 0.771256E+10 0.00
August 0.649397E+11 0.178707E+11 0.148234E+12 0.553335E+11 0.575501E+11 0.156882E+11 0.00 0.287349E+12 0.00 0.00 0.179484E+11 0.770429E+10 0.00
September 0.629683E+11 0.194186E+11 0.143408E+12 0.535457E+11 0.504823E+11 0.142782E+11 0.00 0.165822E+12 0.00 0.00 0.920946E+10 0.746645E+10 0.00
October 0.652880E+11 0.223847E+11 0.148201E+12 0.553307E+11 0.496513E+11 0.132388E+11 0.00 0.731971E+11 0.00 0.00 0.115469E+11 0.770317E+10 0.00
November 0.633458E+11 0.237009E+11 0.143462E+12 0.535468E+11 0.443463E+11 0.768113E+10 0.00 0.697494E+10 0.00 0.00 0.211105E+11 0.744912E+10 0.00
December 0.654211E+11 0.255918E+11 0.148174E+12 0.553297E+11 0.442511E+11 0.661037E+10 0.00 0.304899E+10 0.00 0.00 0.260790E+11 0.771321E+10 0.00
                           
Annual Sum or Average 0.766542E+12 0.242552E+12 0.174501E+13 0.651482E+12 0.571718E+12 0.129274E+12 0.00 0.118920E+13 0.00 0.00 0.222274E+12 0.907468E+11 0.00
Minimum of Months 0.590035E+11 0.152105E+11 0.133859E+12 0.499764E+11 0.390134E+11 0.513403E+10 0.00 0.162124E+10 0.00 0.00 0.780028E+10 0.696282E+10 0.00
Maximum of Months 0.654865E+11 0.255918E+11 0.148234E+12 0.553337E+11 0.575501E+11 0.159983E+11 0.00 0.320858E+12 0.00 0.00 0.260790E+11 0.771321E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.195695E+12 0.00 0.285810E+12 0.00 0.00
February 0.137204E+12 0.00 0.167721E+12 0.00 0.259987E+12 0.00 0.00
March 0.152024E+12 0.00 0.866544E+11 0.00 0.283494E+12 0.00 0.00
April 0.146956E+12 0.00 0.530593E+11 0.00 0.264768E+12 0.00 0.00
May 0.151978E+12 0.00 0.125408E+11 0.00 0.261016E+12 0.00 0.00
June 0.147114E+12 0.00 0.398180E+09 0.00 0.240901E+12 0.00 0.00
July 0.151820E+12 0.00 92785785.25 0.00 0.240645E+12 0.00 0.00
August 0.152039E+12 0.00 0.467698E+09 0.00 0.238539E+12 0.00 0.00
September 0.146971E+12 0.00 0.255879E+10 0.00 0.235181E+12 0.00 0.00
October 0.151903E+12 0.00 0.244168E+11 0.00 0.252965E+12 0.00 0.00
November 0.147091E+12 0.00 0.906633E+11 0.00 0.257041E+12 0.00 0.00
December 0.151820E+12 0.00 0.127540E+12 0.00 0.277590E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.761808E+12 0.00 0.309794E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 92785785.25 0.00 0.235181E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.195695E+12 0.00 0.285810E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 62892.57 02-JAN-20:10 15448.40 01-JAN-00:10 89475.41 02-JAN-07:10 39726.11 02-JAN-07:19 44313.79 19-JAN-21:40 5748.37 11-JAN-16:30 0.00 01-JAN-00:10
February 62892.57 01-FEB-20:10 15448.40 01-FEB-00:10 89475.41 01-FEB-07:10 39726.11 01-FEB-07:19 26701.78 20-FEB-15:09 5849.27 01-FEB-16:00 0.00 01-FEB-00:10
March 62892.57 01-MAR-20:10 15448.40 01-MAR-00:10 89475.41 01-MAR-07:10 39726.11 13-MAR-06:19 32007.54 07-MAR-20:30 5778.28 12-MAR-09:00 0.00 01-MAR-00:10
April 62892.57 03-APR-19:10 15448.40 01-APR-00:10 89475.41 03-APR-06:10 39725.08 18-APR-06:19 36645.99 17-APR-22:30 5988.16 07-APR-15:09 0.00 01-APR-00:10
May 62892.57 01-MAY-19:10 15448.40 01-MAY-00:10 89475.41 01-MAY-06:10 39725.08 04-MAY-06:19 33559.97 31-MAY-21:10 6450.80 31-MAY-18:10 0.00 01-MAY-00:10
June 62892.57 01-JUN-19:19 15448.40 01-JUN-00:10 89475.41 01-JUN-06:10 39724.49 16-JUN-06:19 35685.13 19-JUN-21:10 7648.61 24-JUN-18:10 0.00 01-JUN-00:10
July 62892.57 03-JUL-19:30 15448.40 01-JUL-00:10 89475.41 03-JUL-06:10 39724.92 24-JUL-06:19 37431.79 10-JUL-21:10 7478.12 05-JUL-19:10 0.00 01-JUL-00:10
August 62892.57 01-AUG-19:10 15448.40 01-AUG-00:10 89475.41 01-AUG-06:10 39724.92 16-AUG-06:19 40092.66 18-AUG-21:10 7418.06 11-AUG-20:00 0.00 01-AUG-00:10
September 62892.57 01-SEP-19:10 15448.40 01-SEP-00:10 89475.41 01-SEP-06:10 39725.67 27-SEP-06:19 40471.82 01-SEP-20:10 7363.74 07-SEP-19:00 0.00 01-SEP-00:10
October 62892.57 02-OCT-19:10 15448.40 01-OCT-00:10 89475.41 02-OCT-06:10 39726.11 06-OCT-06:19 35183.30 28-OCT-20:30 6286.07 05-OCT-15:30 0.00 01-OCT-00:10
November 62892.57 01-NOV-19:10 15448.40 01-NOV-00:10 89475.41 01-NOV-06:10 39726.11 01-NOV-06:19 33700.77 05-NOV-21:00 5807.90 01-NOV-06:49 0.00 01-NOV-00:10
December 62892.57 01-DEC-20:10 15448.40 01-DEC-00:10 89475.41 01-DEC-07:10 39726.11 01-DEC-07:19 36567.30 17-DEC-22:10 5839.50 20-DEC-16:40 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 62892.57   15448.40   89475.41   39724.49   26701.78   5748.37   0.00  
Maximum of Months 62892.57   15448.40   89475.41   39726.11   44313.79   7648.61   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 7373.56 17-JAN-16:10 0.00 0.00 9938.94 01-JAN-00:20 4738.31 03-JAN-19:40 0.00
February 10072.28 02-FEB-16:10 0.00 0.00 9938.94 01-FEB-00:20 4738.33 07-FEB-07:19 0.00
March 71617.71 27-MAR-15:00 0.00 0.00 9938.94 01-MAR-00:20 4738.50 10-MAR-19:10 0.00
April 103942.73 07-APR-15:09 0.00 0.00 9938.94 01-APR-00:10 4738.50 18-APR-06:19 0.00
May 120195.50 31-MAY-15:20 0.00 0.00 9938.94 01-MAY-00:20 4738.30 01-MAY-18:10 0.00
June 188096.86 19-JUN-18:10 0.00 0.00 9938.94 01-JUN-10:30 4738.09 05-JUN-18:10 0.00
July 180460.84 20-JUL-15:20 0.00 0.00 9938.94 01-JUL-06:00 4738.04 10-JUL-06:10 0.00
August 203778.65 16-AUG-15:20 0.00 0.00 9938.94 01-AUG-00:10 4738.01 07-AUG-06:10 0.00
September 164209.56 07-SEP-20:40 0.00 0.00 9938.94 01-SEP-00:10 4738.31 08-SEP-06:19 0.00
October 119526.77 04-OCT-15:09 0.00 0.00 9938.94 01-OCT-00:10 4738.33 30-OCT-18:10 0.00
November 46390.21 04-NOV-11:50 0.00 0.00 9938.94 01-NOV-00:10 4738.56 10-NOV-19:10 0.00
December 14071.44 17-DEC-14:30 0.00 0.00 9938.94 01-DEC-00:10 4738.32 04-DEC-19:10 0.00
                   
Annual Sum or Average     0.00 0.00         0.00
Minimum of Months 7373.56   0.00 0.00 9938.94   4738.01   0.00
Maximum of Months 203778.65   0.00 0.00 9938.94   4738.56   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 257030.83 19-JAN-20:10 62892.57 88772.42 15448.40 32151.31 34110.99 5617.48 0.00 1838.40 0.00
February 242843.52 22-FEB-20:19 62892.57 88772.42 15448.40 32159.77 20060.42 5370.69 0.00 1798.74 0.00
March 268662.09 27-MAR-18:10 55920.94 79417.81 15448.40 31836.58 20972.57 5393.22 0.00 52522.42 0.00
April 329039.52 07-APR-19:10 62892.57 88772.42 15448.40 32151.31 26488.88 5965.29 0.00 90059.03 0.00
May 348131.01 31-MAY-19:19 62892.57 88772.42 15448.40 32158.99 27719.80 6082.12 0.00 100562.95 0.00
June 419870.13 19-JUN-19:30 62892.57 88772.42 15448.40 32159.77 30724.18 6592.93 0.00 166856.77 0.00
July 419134.24 20-JUL-19:30 62892.57 88772.42 15448.40 32159.77 29641.61 7061.81 0.00 166922.73 0.00
August 454905.91 04-AUG-19:10 62892.57 88772.42 15448.40 32150.62 33670.79 7013.13 0.00 199615.47 0.00
September 414171.56 13-SEP-19:00 62892.57 88772.42 15448.40 32159.77 29589.02 7293.30 0.00 161861.30 0.00
October 345415.26 05-OCT-19:10 62892.57 88772.42 15448.40 32151.31 27175.26 6088.86 0.00 98424.51 0.00
November 248502.09 07-NOV-20:49 62892.57 88772.42 15448.40 32159.77 24591.17 5271.67 0.00 3869.75 0.00
December 244560.10 18-DEC-20:10 62892.57 88772.42 15448.40 32151.31 21753.26 5366.85 0.00 2011.36 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 242843.52   55920.94 79417.81 15448.40 31836.58 20060.42 5271.67 0.00 1798.74 0.00
Maximum of Months 454905.91   62892.57 88772.42 15448.40 32159.77 34110.99 7293.30 0.00 199615.47 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 257985.59 02-JAN-09:09 0.00 288372.64 24-JAN-21:19 0.00
February 104248.32 01-FEB-18:10 0.00 259652.49 06-FEB-09:09 0.00 288809.98 07-FEB-21:00 0.00
March 104248.32 01-MAR-18:10 0.00 156101.30 12-MAR-09:00 0.00 297324.00 03-MAR-21:19 0.00
April 104248.32 01-APR-17:10 0.00 189927.45 01-APR-20:30 0.00 280395.16 05-APR-20:00 0.00
May 104248.32 01-MAY-17:10 0.00 114516.12 15-MAY-02:49 0.00 249225.20 01-MAY-20:19 0.00
June 104248.32 01-JUN-17:10 0.00 19032.21 22-JUN-19:00 0.00 245727.48 01-JUN-20:30 0.00
July 104248.32 01-JUL-17:10 0.00 9686.38 15-JUL-08:09 0.00 243635.40 06-JUL-20:40 0.00
August 104248.32 01-AUG-17:10 0.00 24893.77 30-AUG-14:30 0.00 242922.91 22-AUG-20:49 0.00
September 104248.32 01-SEP-17:10 0.00 68622.33 30-SEP-05:19 0.00 244395.15 29-SEP-20:49 0.00
October 104248.32 02-OCT-17:10 0.00 138000.71 31-OCT-08:39 0.00 247160.95 27-OCT-17:49 0.00
November 104248.32 01-NOV-17:10 0.00 161147.49 28-NOV-12:00 0.00 261148.92 30-NOV-21:00 0.00
December 104248.32 01-DEC-18:10 0.00 191097.53 31-DEC-23:00 0.00 284026.06 29-DEC-21:30 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 9686.38   0.00 242922.91   0.00
Maximum of Months 104248.32   0.00 259652.49   0.00 297324.00   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 16.67 25.17 16.67 25.17
February 0.00 0.00 0.00 0.00 4.67 24.83 4.67 24.83
March 0.00 0.00 0.00 0.00 32.67 25.11 32.67 25.11
April 0.00 0.00 0.00 0.00 24.50 25.05 24.50 25.05
May 0.00 0.00 0.00 0.00 2.33 25.08 2.33 25.08
June 0.00 0.00 0.00 0.00 0.67 24.95 0.67 24.95
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.17 24.66 0.17 24.66
September 0.00 0.00 0.00 0.00 0.83 24.58 0.83 24.58
October 0.00 0.00 0.00 0.00 11.33 25.28 11.33 25.28
November 0.00 0.00 0.00 0.00 29.67 25.05 29.67 25.05
December 0.00 0.00 0.00 0.00 18.67 25.23 18.67 25.23
                 
Annual Sum or Average 0.00   0.00   142.17 25.11 142.17 25.11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 32.67 25.28 32.67 25.28



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.17 24.63 0.17 24.63
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.17 24.67 0.17 24.67
December 0.00 0.00 0.00 0.00 0.17 24.83 0.17 24.83
                 
Annual Sum or Average 0.00   0.00   0.50 24.71 0.50 24.71
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 24.83 0.17 24.83



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.81 0.17 21.81
May 0.00 0.00 0.00 0.00 1.00 21.81 1.00 21.81
June 0.00 0.00 0.00 0.00 1.50 21.75 1.50 21.75
July 0.00 0.00 0.00 0.00 1.33 21.74 1.33 21.74
August 0.00 0.00 0.00 0.00 4.33 21.84 4.33 21.84
September 0.00 0.00 0.00 0.00 2.17 21.84 2.17 21.84
October 0.00 0.00 0.00 0.00 0.67 21.81 0.67 21.81
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   11.17 21.81 11.17 21.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 4.33 21.84 4.33 21.84



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.67 21.78 0.67 21.78
June 0.00 0.00 0.00 0.00 1.17 21.74 1.17 21.74
July 0.00 0.00 0.00 0.00 1.33 21.71 1.33 21.71
August 0.00 0.00 0.00 0.00 2.33 21.78 2.33 21.78
September 0.00 0.00 0.00 0.00 0.33 21.73 0.33 21.73
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   5.83 21.75 5.83 21.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.33 21.78 2.33 21.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.33 20.51 1.33 20.51 0.00 20.51 0.00 20.51
February 1.17 20.52 1.17 20.52 0.00 20.52 0.00 20.52
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
June 0.00 0.00 0.00 0.00 1.83 21.71 1.83 21.71
July 0.00 0.00 0.00 0.00 5.17 21.72 5.17 21.72
August 0.00 0.00 0.00 0.00 2.83 21.73 2.83 21.73
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2.50 20.51 2.50 20.51 10.00 21.32 10.00 21.48
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.33 20.52 1.33 20.52 5.17 21.73 5.17 21.73



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.82 0.17 21.82
May 0.00 0.00 0.00 0.00 1.33 21.78 1.33 21.78
June 0.00 0.00 0.00 0.00 0.33 21.91 0.33 21.91
July 0.00 0.00 0.00 0.00 0.33 21.71 0.33 21.71
August 0.00 0.00 0.00 0.00 0.67 21.77 0.67 21.77
September 0.00 0.00 0.00 0.00 0.67 21.81 0.67 21.81
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.50 21.79 3.50 21.79
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.33 21.91 1.33 21.91



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.79 0.17 21.79
May 0.00 0.00 0.00 0.00 1.33 21.79 1.33 21.79
June 0.00 0.00 0.00 0.00 0.50 21.89 0.50 21.89
July 0.00 0.00 0.00 0.00 0.50 21.76 0.50 21.76
August 0.00 0.00 0.00 0.00 0.67 21.77 0.67 21.77
September 0.00 0.00 0.00 0.00 0.33 21.78 0.33 21.78
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.50 21.79 3.50 21.79
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.33 21.89 1.33 21.89



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.95 0.17 21.95
May 0.00 0.00 0.00 0.00 1.83 21.81 1.83 21.81
June 0.00 0.00 0.00 0.00 1.83 21.81 1.83 21.81
July 0.00 0.00 0.00 0.00 2.33 21.75 2.33 21.75
August 0.00 0.00 0.00 0.00 5.33 21.87 5.33 21.87
September 0.00 0.00 0.00 0.00 3.17 21.84 3.17 21.84
October 0.00 0.00 0.00 0.00 0.83 21.78 0.83 21.78
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   15.50 21.83 15.50 21.83
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.33 21.95 5.33 21.95



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.00 21.82 1.00 21.82
June 0.00 0.00 0.00 0.00 1.67 21.79 1.67 21.79
July 0.00 0.00 0.00 0.00 1.67 21.75 1.67 21.75
August 0.00 0.00 0.00 0.00 3.00 21.80 3.00 21.80
September 0.00 0.00 0.00 0.00 0.67 21.71 0.67 21.71
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   8.00 21.78 8.00 21.78
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.00 21.82 3.00 21.82



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 21.84 0.33 21.84
May 0.00 0.00 0.00 0.00 0.17 21.74 0.17 21.74
June 0.00 0.00 0.00 0.00 0.17 21.77 0.17 21.77
July 0.00 0.00 0.00 0.00 0.17 21.70 0.17 21.70
August 0.00 0.00 0.00 0.00 3.17 21.82 3.17 21.82
September 0.00 0.00 0.00 0.00 3.00 21.89 3.00 21.89
October 0.00 0.00 0.00 0.00 2.83 21.88 2.83 21.88
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   9.83 21.86 9.83 21.86
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.17 21.89 3.17 21.89



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.67 24.85 1.67 24.85
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 4.00 24.74 4.00 24.74
April 0.00 0.00 0.00 0.00 3.67 24.74 3.67 24.74
May 0.00 0.00 0.00 0.00 1.83 24.77 1.83 24.77
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 3.83 24.70 3.83 24.70
November 0.00 0.00 0.00 0.00 5.17 24.72 5.17 24.72
December 0.00 0.00 0.00 0.00 1.00 24.67 1.00 24.67
                 
Annual Sum or Average 0.00   0.00   21.17 24.74 21.17 24.74
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.17 24.85 5.17 24.85



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 2.00 24.86 2.00 24.86
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 6.00 24.76 6.00 24.76
April 0.00 0.00 0.00 0.00 5.33 24.76 5.33 24.76
May 0.00 0.00 0.00 0.00 1.83 24.86 1.83 24.86
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 4.33 24.75 4.33 24.75
November 0.00 0.00 0.00 0.00 7.17 24.74 7.17 24.74
December 0.00 0.00 0.00 0.00 2.17 24.69 2.17 24.69
                 
Annual Sum or Average 0.00   0.00   28.83 24.76 28.83 24.76
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 7.17 24.86 7.17 24.86



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 22.50 25.12 22.50 25.12
February 0.00 0.00 0.00 0.00 12.17 25.11 12.17 25.11
March 0.00 0.00 0.00 0.00 48.00 25.20 48.00 25.20
April 0.00 0.00 0.00 0.00 36.50 25.13 36.50 25.13
May 0.00 0.00 0.00 0.00 6.33 24.95 6.33 24.95
June 0.00 0.00 0.00 0.00 5.17 24.89 5.17 24.89
July 0.00 0.00 0.00 0.00 0.83 24.89 0.83 24.89
August 0.00 0.00 0.00 0.00 4.83 24.81 4.83 24.81
September 0.00 0.00 0.00 0.00 0.50 24.68 0.50 24.68
October 0.00 0.00 0.00 0.00 21.00 25.19 21.00 25.19
November 0.00 0.00 0.00 0.00 48.00 25.11 48.00 25.11
December 0.00 0.00 0.00 0.00 31.67 25.19 31.67 25.19
                 
Annual Sum or Average 0.00   0.00   237.50 25.13 237.50 25.13
Minimum of Months 0.00 0.00 0.00 0.00 0.50 24.68 0.50 24.68
Maximum of Months 0.00 0.00 0.00 0.00 48.00 25.20 48.00 25.20



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 725.17 23.51 0.00 23.51 0.00 23.51
February 672.00 23.20 0.00 23.20 0.00 23.20
March 744.00 22.97 0.00 22.97 0.00 22.97
April 720.00 22.70 0.00 22.70 0.00 22.70
May 744.00 22.51 0.00 22.51 0.00 22.51
June 703.67 22.86 0.00 22.86 0.00 22.86
July 443.33 23.04 20.67 23.08 0.00 23.08
August 254.00 23.26 260.67 23.57 0.00 23.57
September 105.50 23.63 286.17 23.87 0.00 23.87
October 240.00 23.90 243.33 23.93 0.00 23.93
November 335.33 23.87 20.00 23.88 0.00 23.88
December 655.33 23.82 0.00 23.82 0.00 23.82
             
Annual Sum or Average 6342.33 23.16 830.83 23.25 0.00 23.25
Minimum of Months 105.50 22.51 0.00 22.51 0.00 22.51
Maximum of Months 744.00 23.90 286.17 23.93 0.00 23.93



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 729.00 21.11 346.67 21.08 344.33 21.06
February 646.67 21.17 311.50 21.12 311.17 21.09
March 692.83 21.24 112.83 21.28 90.83 21.26
April 652.67 21.32 39.17 21.41 14.67 21.40
May 658.67 21.54 31.50 21.64 0.00 21.64
June 447.83 22.10 161.83 22.49 0.00 22.49
July 230.33 22.36 362.33 23.11 0.00 23.11
August 177.67 22.36 453.33 23.35 0.00 23.35
September 428.33 21.90 215.17 22.53 0.00 22.53
October 500.33 21.71 172.83 22.26 0.00 22.26
November 675.00 21.22 108.17 21.27 88.50 21.24
December 712.00 21.14 310.33 21.12 303.17 21.09
             
Annual Sum or Average 6551.33 21.45 2625.67 21.76 1152.67 21.67
Minimum of Months 177.67 21.11 31.50 21.08 0.00 21.06
Maximum of Months 729.00 22.36 453.33 23.35 344.33 23.35



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.42 39.17 21.40 39.17 21.38
February 672.00 21.51 34.50 21.49 34.50 21.47
March 744.00 22.06 0.00 22.06 0.00 22.06
April 684.00 22.34 7.17 22.36 0.00 22.36
May 619.83 22.73 45.67 22.80 1.33 22.81
June 229.00 23.01 314.33 23.47 9.50 23.48
July 67.33 23.31 518.67 23.78 26.50 23.78
August 42.00 23.22 539.17 23.83 7.00 23.83
September 309.17 22.95 243.17 23.34 7.33 23.35
October 507.50 22.93 110.50 23.08 0.00 23.08
November 715.83 22.09 0.00 22.09 0.00 22.09
December 744.00 21.67 2.67 21.66 2.67 21.66
             
Annual Sum or Average 6078.67 22.15 1855.00 22.52 128.00 22.51
Minimum of Months 42.00 21.42 0.00 21.40 0.00 21.38
Maximum of Months 744.00 23.31 539.17 23.83 39.17 23.83



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.03 246.67 21.02 246.67 21.02
February 672.00 21.02 271.67 21.02 271.67 21.01
March 744.00 21.20 43.00 21.19 43.00 21.18
April 720.00 21.60 0.00 21.60 0.00 21.60
May 730.17 22.35 2.17 22.35 0.00 22.35
June 423.17 23.04 74.67 23.17 0.00 23.17
July 74.17 23.19 307.00 23.74 0.00 23.74
August 151.33 23.34 276.00 23.71 0.00 23.71
September 520.83 22.90 36.33 22.97 0.00 22.97
October 738.50 22.38 0.00 22.38 0.00 22.38
November 720.00 21.40 32.83 21.38 32.83 21.36
December 744.00 21.05 65.00 21.05 65.00 21.05
             
Annual Sum or Average 6982.17 21.76 1355.33 21.88 659.17 21.82
Minimum of Months 74.17 21.02 0.00 21.02 0.00 21.01
Maximum of Months 744.00 23.34 307.00 23.74 271.67 23.74



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 302.83 21.00 302.83 21.00
February 672.00 21.00 335.50 21.00 335.50 21.00
March 744.00 21.09 65.33 21.08 65.33 21.08
April 720.00 21.43 2.33 21.43 2.33 21.43
May 742.17 22.17 0.00 22.17 0.00 22.17
June 570.83 23.00 6.67 23.01 0.00 23.01
July 175.00 23.24 129.00 23.49 0.00 23.49
August 275.67 23.33 164.33 23.53 0.00 23.53
September 622.00 22.83 0.00 22.83 0.00 22.83
October 744.00 22.20 0.00 22.20 0.00 22.20
November 720.00 21.25 53.00 21.24 53.00 21.22
December 744.00 21.01 128.83 21.01 128.83 21.01
             
Annual Sum or Average 7473.67 21.76 1187.83 21.75 887.83 21.68
Minimum of Months 175.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 23.33 335.50 23.53 335.50 23.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 306.83 22.59 397.33 23.20 135.00 23.36
February 257.83 22.51 336.83 23.20 112.17 23.34
March 270.67 23.14 506.67 23.41 171.67 23.57
April 268.50 23.37 560.50 23.38 199.50 23.53
May 286.67 23.72 661.50 23.37 259.17 23.50
June 299.17 23.92 691.83 23.34 292.67 23.48
July 319.67 23.96 739.50 23.32 319.67 23.47
August 316.17 23.96 730.50 23.33 316.00 23.48
September 293.83 23.84 670.50 23.36 279.33 23.50
October 285.00 23.64 626.83 23.40 244.83 23.54
November 264.17 23.21 519.83 23.41 175.50 23.56
December 260.50 22.77 412.50 23.34 135.83 23.48
             
Annual Sum or Average 3429.00 23.41 6854.33 23.34 2641.33 23.49
Minimum of Months 257.83 22.51 336.83 23.20 112.17 23.34
Maximum of Months 319.67 23.96 739.50 23.41 319.67 23.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 710.00 21.54 95.17 21.53 81.17 21.48
February 615.83 21.69 68.67 21.73 44.17 21.68
March 636.33 22.08 54.17 22.23 0.00 22.23
April 523.50 22.14 104.00 22.40 0.00 22.40
May 461.50 22.57 190.50 22.88 50.33 22.93
June 290.00 23.43 548.67 23.55 213.67 23.60
July 286.33 23.85 719.83 23.73 280.00 23.77
August 215.50 23.88 717.17 23.83 207.67 23.85
September 261.17 23.07 522.00 23.53 143.33 23.57
October 330.00 22.99 407.83 23.45 92.17 23.49
November 606.00 22.05 61.83 22.21 3.33 22.22
December 687.33 21.74 46.17 21.82 14.50 21.81
             
Annual Sum or Average 5623.50 22.30 3536.00 22.81 1130.33 22.89
Minimum of Months 215.50 21.54 46.17 21.53 0.00 21.48
Maximum of Months 710.00 23.88 719.83 23.83 280.00 23.85



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 22.03 6.83 22.02 6.83 22.02
February 672.00 22.18 0.17 22.18 0.17 22.18
March 703.17 22.63 0.00 22.63 0.00 22.63
April 564.83 22.73 56.83 22.83 0.00 22.83
May 415.67 22.97 173.33 23.23 45.83 23.28
June 257.67 23.70 492.00 23.78 188.00 23.82
July 244.50 23.99 690.17 23.85 244.17 23.88
August 176.17 24.00 698.50 23.89 176.17 23.91
September 217.67 23.52 468.33 23.76 128.83 23.79
October 318.50 23.40 322.33 23.62 71.50 23.65
November 640.83 22.65 23.17 22.69 3.67 22.70
December 743.33 22.34 0.00 22.34 0.00 22.34
             
Annual Sum or Average 5698.33 22.72 2931.67 23.10 865.17 23.18
Minimum of Months 176.17 22.03 0.00 22.02 0.00 22.02
Maximum of Months 744.00 24.00 698.50 23.89 244.17 23.91



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.73 624.67 20.68 624.67 20.67
February 672.00 20.86 558.33 20.80 558.33 20.78
March 744.00 21.12 266.17 21.01 266.17 20.95
April 701.17 21.27 74.83 21.21 73.50 21.15
May 701.17 21.46 5.00 21.47 0.00 21.47
June 602.50 21.39 35.17 21.49 1.50 21.50
July 588.17 21.32 60.00 21.50 1.67 21.51
August 578.33 21.29 71.17 21.51 0.50 21.52
September 631.17 21.42 27.17 21.49 3.33 21.49
October 683.33 21.42 24.50 21.47 5.33 21.46
November 720.00 21.05 289.00 20.95 289.00 20.89
December 744.00 20.83 592.67 20.77 592.67 20.75
             
Annual Sum or Average 8109.83 21.17 2628.67 21.10 2416.67 21.03
Minimum of Months 578.33 20.73 5.00 20.68 0.00 20.67
Maximum of Months 744.00 21.46 624.67 21.51 624.67 21.52



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.56 698.50 20.54 698.50 20.53
February 672.00 20.61 643.00 20.59 643.00 20.59
March 744.00 20.89 373.00 20.79 373.00 20.74
April 712.00 21.18 112.83 21.10 112.83 21.04
May 717.00 21.46 3.83 21.47 0.00 21.47
June 618.33 21.43 26.83 21.50 1.17 21.51
July 601.83 21.36 47.50 21.50 2.00 21.50
August 611.33 21.38 43.33 21.51 0.83 21.51
September 667.17 21.46 11.33 21.49 2.50 21.49
October 722.83 21.34 35.67 21.32 35.00 21.30
November 720.00 20.82 381.00 20.73 381.00 20.68
December 744.00 20.60 705.33 20.58 705.33 20.58
             
Annual Sum or Average 8274.50 21.08 3082.17 20.97 2955.17 20.89
Minimum of Months 601.83 20.56 3.83 20.54 0.00 20.53
Maximum of Months 744.00 21.46 705.33 21.51 705.33 21.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.76 544.83 20.72 544.83 20.70
February 672.00 20.76 581.33 20.73 581.33 20.72
March 744.00 20.98 279.50 20.93 279.50 20.90
April 720.00 21.18 24.00 21.17 24.00 21.16
May 744.00 21.38 0.00 21.38 0.00 21.38
June 720.00 21.51 7.83 21.52 7.83 21.53
July 744.00 21.61 5.83 21.62 5.83 21.63
August 744.00 21.57 2.00 21.57 2.00 21.57
September 720.00 21.39 4.50 21.39 4.50 21.40
October 744.00 21.22 4.83 21.22 4.83 21.22
November 720.00 20.99 204.00 20.93 204.00 20.89
December 744.00 20.81 552.33 20.77 552.33 20.76
             
Annual Sum or Average 8760.00 21.18 2211.00 21.09 2211.00 21.03
Minimum of Months 672.00 20.76 0.00 20.72 0.00 20.70
Maximum of Months 744.00 21.61 581.33 21.62 581.33 21.63



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.72 622.00 20.68 622.00 20.67
February 672.00 20.87 541.50 20.82 541.50 20.79
March 744.00 21.17 253.67 21.06 253.67 20.99
April 700.83 21.34 79.50 21.26 79.50 21.21
May 708.50 21.52 1.50 21.53 0.00 21.53
June 588.33 21.35 6.83 21.38 2.00 21.38
July 570.33 21.26 25.67 21.35 1.50 21.35
August 560.33 21.23 54.67 21.42 0.17 21.42
September 603.50 21.36 14.50 21.39 3.67 21.40
October 677.50 21.45 6.50 21.45 5.17 21.45
November 720.00 21.09 271.33 20.99 271.33 20.93
December 744.00 20.83 577.83 20.77 577.83 20.75
             
Annual Sum or Average 8033.33 21.17 2455.50 21.09 2358.33 21.02
Minimum of Months 560.33 20.72 1.50 20.68 0.00 20.67
Maximum of Months 744.00 21.52 622.00 21.53 622.00 21.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.56 689.17 20.53 689.17 20.53
February 672.00 20.61 640.83 20.60 640.83 20.59
March 744.00 20.93 355.67 20.85 355.67 20.81
April 715.67 21.29 104.83 21.20 104.83 21.14
May 717.83 21.53 1.50 21.54 0.00 21.54
June 608.83 21.42 4.50 21.43 1.83 21.44
July 572.83 21.27 11.33 21.31 1.50 21.31
August 569.83 21.26 9.67 21.30 0.50 21.30
September 667.83 21.52 5.00 21.52 3.00 21.52
October 739.00 21.45 36.83 21.43 36.83 21.41
November 720.00 20.86 348.17 20.76 348.17 20.71
December 744.00 20.59 689.50 20.57 689.50 20.57
             
Annual Sum or Average 8215.83 21.09 2897.00 20.97 2871.83 20.89
Minimum of Months 569.83 20.56 1.50 20.53 0.00 20.53
Maximum of Months 744.00 21.53 689.50 21.54 689.50 21.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.02 221.33 21.01 221.33 21.01
February 672.00 21.02 213.67 21.02 213.67 21.01
March 744.00 21.22 4.00 21.22 4.00 21.22
April 720.00 21.71 0.00 21.71 0.00 21.71
May 734.83 22.44 1.00 22.44 1.00 22.44
June 481.33 23.21 49.00 23.27 14.17 23.27
July 103.00 23.50 300.67 23.76 55.33 23.74
August 92.83 23.60 351.00 23.85 23.83 23.84
September 493.00 22.96 72.67 23.08 10.17 23.08
October 743.00 22.65 0.00 22.65 0.00 22.65
November 720.00 21.37 23.17 21.36 23.17 21.34
December 744.00 21.03 68.83 21.03 68.83 21.03
             
Annual Sum or Average 6992.00 21.83 1305.33 21.97 635.50 21.93
Minimum of Months 92.83 21.02 0.00 21.01 0.00 21.01
Maximum of Months 744.00 23.60 351.00 23.85 221.33 23.84



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.65 681.17 20.62 681.17 20.61
February 672.00 20.77 597.50 20.72 597.50 20.71
March 743.67 21.05 352.67 20.92 352.67 20.86
April 697.17 21.21 171.67 21.11 167.33 21.04
May 687.33 21.40 12.83 21.43 2.83 21.43
June 592.83 21.35 65.67 21.53 11.00 21.54
July 581.67 21.30 91.00 21.57 5.50 21.57
August 566.83 21.26 98.67 21.56 1.83 21.57
September 621.33 21.37 43.67 21.48 8.00 21.48
October 678.83 21.36 93.00 21.39 67.33 21.35
November 720.00 20.95 400.50 20.84 400.50 20.80
December 744.00 20.74 666.67 20.70 666.67 20.69
             
Annual Sum or Average 8049.67 21.10 3275.00 21.05 2962.33 20.97
Minimum of Months 566.83 20.65 12.83 20.62 1.83 20.61
Maximum of Months 744.00 21.40 681.17 21.57 681.17 21.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.51 719.67 20.50 719.67 20.50
February 672.00 20.55 655.83 20.54 655.83 20.54
March 744.00 20.81 474.33 20.72 474.33 20.68
April 708.67 21.12 215.50 21.02 215.33 20.95
May 703.17 21.41 10.83 21.43 3.83 21.43
June 605.50 21.38 50.00 21.51 10.00 21.52
July 589.50 21.32 73.00 21.53 6.33 21.54
August 595.67 21.33 65.17 21.52 2.00 21.53
September 657.83 21.41 19.83 21.45 7.33 21.45
October 721.00 21.26 128.50 21.21 125.83 21.17
November 720.00 20.73 480.67 20.65 480.67 20.62
December 744.00 20.53 736.67 20.53 736.67 20.53
             
Annual Sum or Average 8205.33 21.01 3630.00 20.92 3437.83 20.84
Minimum of Months 589.50 20.51 10.83 20.50 2.00 20.50
Maximum of Months 744.00 21.41 736.67 21.53 736.67 21.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 739.17 21.01 477.17 20.90 477.17 20.85
February 671.83 21.22 394.17 21.07 394.17 21.01
March 721.33 21.23 201.00 21.13 201.00 21.07
April 691.50 21.31 67.83 21.27 62.50 21.22
May 707.00 21.46 0.00 21.46 0.00 21.46
June 626.00 21.42 14.17 21.44 12.83 21.46
July 610.67 21.37 26.17 21.44 8.83 21.46
August 596.67 21.33 80.00 21.57 2.00 21.57
September 610.33 21.36 53.50 21.50 6.17 21.51
October 633.17 21.33 52.67 21.49 1.17 21.49
November 700.67 21.29 164.50 21.21 163.67 21.15
December 736.83 21.12 419.33 21.00 419.33 20.94
             
Annual Sum or Average 8045.17 21.28 1950.50 21.24 1748.83 21.17
Minimum of Months 596.67 21.01 0.00 20.90 0.00 20.85
Maximum of Months 739.17 21.46 477.17 21.57 477.17 21.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 582.50 22.97 12.50 22.99 0.00 22.99
February 554.33 23.04 0.00 23.04 0.00 23.04
March 355.17 23.13 79.67 23.30 0.00 23.30
April 152.50 23.13 283.50 23.68 0.00 23.68
May 65.83 23.80 601.83 23.93 50.00 23.93
June 182.00 24.00 708.67 23.97 182.00 23.98
July 227.33 24.00 744.00 23.99 227.33 23.99
August 174.67 24.00 743.17 23.98 174.67 23.98
September 129.50 24.00 670.50 23.95 129.50 23.96
October 195.33 23.61 426.00 23.81 89.33 23.83
November 342.33 23.07 108.33 23.30 4.83 23.30
December 525.67 23.09 7.00 23.11 0.00 23.11
             
Annual Sum or Average 3487.17 23.29 4385.17 23.67 857.67 23.70
Minimum of Months 65.83 22.97 0.00 22.99 0.00 22.99
Maximum of Months 582.50 24.00 744.00 23.99 227.33 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 432.17 23.06 53.00 23.17 0.00 23.17
February 426.67 23.15 13.17 23.17 0.00 23.17
March 186.83 23.11 222.00 23.61 0.00 23.61
April 60.67 23.21 419.67 23.88 0.00 23.88
May 41.17 24.00 685.50 23.96 41.17 23.97
June 165.00 24.00 715.83 23.99 165.00 23.99
July 211.50 24.00 744.00 23.99 211.50 23.99
August 160.00 24.00 744.00 23.99 160.00 23.99
September 116.50 24.00 701.67 23.97 116.50 23.97
October 105.33 23.77 484.00 23.91 71.00 23.92
November 196.50 23.14 227.00 23.61 2.83 23.61
December 347.67 23.10 42.17 23.20 0.00 23.20
             
Annual Sum or Average 2450.00 23.39 5052.00 23.79 768.00 23.81
Minimum of Months 41.17 23.06 13.17 23.17 0.00 23.17
Maximum of Months 432.17 24.00 744.00 23.99 211.50 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 535.17 23.74 598.67 23.87 451.67 23.92
February 493.67 23.70 531.33 23.86 404.83 23.91
March 529.50 24.07 657.33 24.05 503.83 24.08
April 512.67 24.10 677.33 24.01 511.67 24.04
May 554.33 24.01 743.83 23.94 554.33 23.96
June 562.83 24.00 720.00 23.97 562.83 23.98
July 602.67 23.99 744.00 23.98 602.67 23.98
August 597.67 24.01 744.00 23.99 597.67 24.00
September 547.83 24.00 719.83 23.95 547.83 23.96
October 542.17 24.06 716.83 23.99 542.00 24.01
November 513.67 24.05 648.83 24.02 491.33 24.05
December 528.00 23.89 609.67 23.96 470.83 24.00
             
Annual Sum or Average 6520.17 23.97 8111.67 23.97 6241.50 23.99
Minimum of Months 493.67 23.70 531.33 23.86 404.83 23.91
Maximum of Months 602.67 24.10 744.00 24.05 602.67 24.08



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.02 268.83 21.01 268.83 21.01
February 672.00 21.03 275.33 21.02 275.33 21.02
March 744.00 21.22 20.67 21.22 20.67 21.21
April 716.33 21.66 0.00 21.66 0.00 21.66
May 692.67 22.37 29.00 22.43 0.00 22.43
June 261.17 23.03 225.50 23.41 0.00 23.41
July 14.83 23.03 589.67 23.85 0.00 23.85
August 61.67 23.19 495.33 23.82 0.00 23.82
September 436.00 22.74 136.67 23.01 0.00 23.01
October 694.83 22.27 12.67 22.30 0.00 22.30
November 720.00 21.24 34.33 21.23 34.33 21.22
December 744.00 21.04 80.50 21.03 80.50 21.03
             
Annual Sum or Average 6501.50 21.64 2168.50 21.97 679.67 21.90
Minimum of Months 14.83 21.02 0.00 21.01 0.00 21.01
Maximum of Months 744.00 23.19 589.67 23.85 275.33 23.85



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.52642 27.54466 0.13716 5.57661
February 672.00000 23.20375 24.03746 0.02914 5.20003
March 744.00000 22.96987 32.89101 0.02643 5.24541
April 720.00000 22.70316 39.59675 0.00254 5.22123
May 744.00000 22.51496 48.05183 -1.0494 28.52350
June 720.00000 22.87297 57.53287 -0.8537 20.72368
July 744.00000 23.26157 60.05889 -0.6909 15.29094
August 744.00000 23.60807 56.12961 -0.5853 12.40063
September 720.00000 23.84319 51.14197 -0.5269 11.01683
October 744.00000 23.91667 42.67790 0.35755 7.89438
November 720.00000 23.92556 32.89853 0.28863 6.83731
December 744.00000 23.83951 26.92743 0.21860 6.08255
           
Annual Sum or Average 8760.00000 23.35014 41.72842 -0.2220 10.87947
Minimum of Months 672.00000 22.51496 24.03746 -1.0494 5.20003
Maximum of Months 744.00000 23.92556 60.05889 0.35755 28.52350



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.16809 29.22259 -0.4868 10.86773
February 672.00000 21.27123 24.56398 -0.4559 10.59896
March 744.00000 21.41376 34.04069 -0.3099 8.41757
April 720.00000 21.53707 40.55744 -0.2089 7.55638
May 744.00000 21.75574 48.76364 -1.1427 34.33590
June 720.00000 22.56702 57.71632 -0.7495 18.60145
July 744.00000 23.06526 60.48992 -0.5292 12.15441
August 744.00000 23.29453 56.39561 -0.4469 10.92899
September 720.00000 22.58320 53.86772 -0.7549 20.67813
October 744.00000 22.36481 45.21495 0.10804 7.97600
November 720.00000 21.38044 36.38306 -0.3080 8.38623
December 744.00000 21.25836 29.09330 -0.4328 10.08893
           
Annual Sum or Average 8760.00000 21.97689 43.13252 -0.4763 13.40080
Minimum of Months 672.00000 21.16809 24.56398 -1.1427 7.55638
Maximum of Months 744.00000 23.29453 60.48992 0.10804 34.33590



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.41957 30.97969 -0.3491 7.96178
February 672.00000 21.51344 26.41385 -0.3483 7.90890
March 744.00000 22.06276 34.98893 -0.1508 6.02586
April 720.00000 22.41386 40.81004 -0.0198 5.78487
May 744.00000 22.88858 47.90359 -0.8473 20.96806
June 720.00000 23.45066 56.78073 -0.5691 12.30835
July 744.00000 23.66092 60.02799 -0.4610 9.69698
August 744.00000 23.74406 56.64711 -0.4467 9.41327
September 720.00000 23.38613 53.46676 -0.6150 13.76258
October 744.00000 23.14161 45.56460 0.21003 6.57651
November 720.00000 22.10194 37.12319 -0.1281 6.04565
December 744.00000 21.66720 30.66352 -0.2831 7.01614
           
Annual Sum or Average 8760.00000 22.62762 43.54807 -0.3339 9.46825
Minimum of Months 672.00000 21.41957 26.41385 -0.8473 5.78487
Maximum of Months 744.00000 23.74406 60.02799 0.21003 20.96806



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.78900 24.90881 0.51416 13.70544
February 672.00000 22.80602 20.76621 0.49456 13.12854
March 744.00000 22.98334 29.18840 0.62613 16.32693
April 720.00000 22.96893 35.41960 0.68970 17.97000
May 744.00000 23.01061 43.14890 0.06208 10.31095
June 720.00000 23.01533 53.55174 0.17506 10.78722
July 744.00000 23.02851 57.33214 0.22377 10.85812
August 744.00000 23.02868 54.38790 0.21418 10.92513
September 720.00000 23.01492 50.08172 0.13803 10.60319
October 744.00000 23.02139 41.55247 0.76921 20.20467
November 720.00000 23.00751 31.23988 0.64640 16.75170
December 744.00000 22.88003 24.76952 0.54792 14.22548
           
Annual Sum or Average 8760.00000 22.96372 38.97034 0.42467 13.81978
Minimum of Months 672.00000 22.78900 20.76621 0.06208 10.31095
Maximum of Months 744.00000 23.02868 57.33214 0.76921 20.20467



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.63851 34.09724 -0.2697 7.74305
February 672.00000 21.85952 29.43355 -0.2135 7.41806
March 744.00000 22.32043 38.09600 -0.0125 6.47244
April 720.00000 22.51982 44.07100 0.09652 6.78934
May 744.00000 22.90455 51.43180 -0.6915 16.53761
June 720.00000 23.40098 60.38212 -0.4017 9.18149
July 744.00000 23.64217 63.31697 -0.2592 6.87605
August 744.00000 23.77485 59.69076 -0.2025 6.46945
September 720.00000 23.45339 56.58989 -0.3866 10.00732
October 744.00000 23.40911 48.22831 0.42354 10.24857
November 720.00000 22.29709 40.15012 -0.0072 6.59158
December 744.00000 21.89320 33.69205 -0.1835 7.09248
           
Annual Sum or Average 8760.00000 22.76513 46.69885 -0.1754 8.46418
Minimum of Months 672.00000 21.63851 29.43355 -0.6915 6.46945
Maximum of Months 744.00000 23.77485 63.31697 0.42354 16.53761



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.03418 33.42354 -0.1765 6.29542
February 672.00000 22.17590 28.95880 -0.1620 6.12359
March 744.00000 22.70247 37.30146 0.03217 5.65074
April 720.00000 22.94548 43.03093 0.14152 6.18180
May 744.00000 23.31670 50.06864 -0.6539 14.75390
June 720.00000 23.62830 59.03482 -0.4493 9.63897
July 744.00000 23.75044 62.24407 -0.3654 7.97907
August 744.00000 23.83341 58.91263 -0.3488 7.68052
September 720.00000 23.67983 55.51932 -0.4538 9.84079
October 744.00000 23.60470 47.60305 0.36747 8.35549
November 720.00000 22.77733 39.22079 0.06537 5.89642
December 744.00000 22.34546 33.01415 -0.0939 5.78168
           
Annual Sum or Average 8760.00000 23.07140 45.79347 -0.1749 7.86192
Minimum of Months 672.00000 22.03418 28.95880 -0.6539 5.65074
Maximum of Months 744.00000 23.83341 62.24407 0.36747 14.75390



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.73291 32.82515 -0.6607 14.82213
February 672.00000 20.85908 27.50920 -0.6419 14.40345
March 744.00000 21.12493 37.85444 -0.4477 10.07103
April 720.00000 21.32338 45.01862 -0.3058 8.09797
May 744.00000 21.56698 51.95537 -1.2567 39.29638
June 720.00000 21.69974 56.26797 -1.0871 31.59623
July 744.00000 21.73122 56.45298 -1.0370 29.50469
August 744.00000 21.73437 53.97734 -1.0289 29.31820
September 720.00000 21.65351 55.05151 -1.1487 34.45770
October 744.00000 21.57279 48.81738 -0.1560 6.76896
November 720.00000 21.04770 41.27688 -0.4695 10.43943
December 744.00000 20.83000 32.88155 -0.6175 13.60962
           
Annual Sum or Average 8760.00000 21.32568 45.08602 -0.7388 20.23605
Minimum of Months 672.00000 20.73291 27.50920 -1.2567 6.76896
Maximum of Months 744.00000 21.73437 56.45298 -0.1560 39.29638



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.55849 33.09369 -0.7257 16.68736
February 672.00000 20.60662 27.84801 -0.7357 16.95744
March 744.00000 20.89415 38.24842 -0.5291 11.49891
April 720.00000 21.20804 45.39222 -0.3508 8.50452
May 744.00000 21.53163 52.10638 -1.2808 40.30693
June 720.00000 21.69298 56.44663 -1.0976 31.96011
July 744.00000 21.72797 56.79679 -1.0475 29.84793
August 744.00000 21.72133 54.64047 -1.0585 30.34977
September 720.00000 21.59557 55.94570 -1.2007 36.54346
October 744.00000 21.39891 50.37497 -0.2329 7.11171
November 720.00000 20.82355 41.76918 -0.5495 12.02526
December 744.00000 20.59668 33.26039 -0.6995 15.74040
           
Annual Sum or Average 8760.00000 21.19971 45.59044 -0.7928 21.48943
Minimum of Months 672.00000 20.55849 27.84801 -1.2808 7.11171
Maximum of Months 744.00000 21.72797 56.79679 -0.2329 40.30693



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.76448 31.57265 -0.6162 13.41867
February 672.00000 20.75507 26.49253 -0.6494 14.23509
March 744.00000 20.97692 36.92807 -0.4992 10.44205
April 720.00000 21.17916 44.13613 -0.3723 8.17051
May 744.00000 21.38177 50.72387 -1.4046 45.94708
June 720.00000 21.51451 57.49845 -1.2762 39.52794
July 744.00000 21.61236 58.06445 -1.2218 37.04335
August 744.00000 21.56956 56.01823 -1.2574 38.69393
September 720.00000 21.39268 55.69016 -1.3594 43.62136
October 744.00000 21.22269 49.84086 -0.3137 7.38183
November 720.00000 20.98761 40.22375 -0.4763 10.05872
December 744.00000 20.81314 31.76133 -0.5959 12.69290
           
Annual Sum or Average 8760.00000 21.18337 45.01490 -0.8380 23.49083
Minimum of Months 672.00000 20.75507 26.49253 -1.4046 7.38183
Maximum of Months 744.00000 21.61236 58.06445 -0.3137 45.94708



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.72280 32.81954 -0.6604 14.75637
February 672.00000 20.86826 27.47590 -0.6355 14.12485
March 744.00000 21.17387 37.80140 -0.4413 9.96094
April 720.00000 21.38955 44.88082 -0.2887 8.00805
May 744.00000 21.60776 51.81624 -1.2379 38.48481
June 720.00000 21.71455 56.58341 -1.0907 31.72335
July 744.00000 21.74205 56.51572 -1.0354 29.44515
August 744.00000 21.74859 54.06159 -1.0246 29.14042
September 720.00000 21.67508 55.07442 -1.1381 34.00714
October 744.00000 21.61543 48.86357 -0.1486 6.73753
November 720.00000 21.08775 41.16080 -0.4516 10.15682
December 744.00000 20.82730 32.87471 -0.6136 13.46942
           
Annual Sum or Average 8760.00000 21.35039 45.08944 -0.7312 20.03888
Minimum of Months 672.00000 20.72280 27.47590 -1.2379 6.73753
Maximum of Months 744.00000 21.74859 56.58341 -0.1486 38.48481



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.55538 33.08325 -0.7245 16.67019
February 672.00000 20.60755 27.81647 -0.7311 16.80222
March 744.00000 20.93384 38.19153 -0.5248 11.26616
April 720.00000 21.29991 45.10276 -0.3290 8.29934
May 744.00000 21.59665 51.88392 -1.2554 39.18753
June 720.00000 21.71294 56.78174 -1.0997 32.02513
July 744.00000 21.74104 56.88304 -1.0451 29.76136
August 744.00000 21.74478 54.70815 -1.0513 30.06720
September 720.00000 21.64660 55.68226 -1.1827 35.74203
October 744.00000 21.46162 50.03086 -0.2235 7.00696
November 720.00000 20.86080 41.65415 -0.5312 11.61936
December 744.00000 20.59194 33.25034 -0.6959 15.68332
           
Annual Sum or Average 8760.00000 21.23288 45.51905 -0.7832 21.20538
Minimum of Months 672.00000 20.55538 27.81647 -1.2554 7.00696
Maximum of Months 744.00000 21.74478 56.88304 -0.2235 39.18753



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.65061 33.28086 -0.7215 16.65355
February 672.00000 20.77065 27.88095 -0.7042 16.25184
March 744.00000 21.04651 38.33463 -0.4933 11.18165
April 720.00000 21.27215 45.64543 -0.3353 8.78009
May 744.00000 21.54712 52.94370 -1.2707 40.22935
June 720.00000 21.69153 57.47311 -1.0843 31.69367
July 744.00000 21.72894 57.38726 -1.0275 29.32083
August 744.00000 21.73076 54.84623 -1.0216 29.29567
September 720.00000 21.63434 56.36846 -1.1603 35.23243
October 744.00000 21.52695 50.01927 -0.1831 7.20324
November 720.00000 20.94660 41.89114 -0.5258 11.75968
December 744.00000 20.73948 33.33378 -0.6778 15.30553
           
Annual Sum or Average 8760.00000 21.27671 45.88090 -0.7676 21.10661
Minimum of Months 672.00000 20.65061 27.88095 -1.2707 7.20324
Maximum of Months 744.00000 21.73076 57.47311 -0.1831 40.22935



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.51144 33.50900 -0.7812 18.50618
February 672.00000 20.55052 28.19964 -0.7936 18.87223
March 744.00000 20.81209 38.75480 -0.5781 12.79011
April 720.00000 21.15409 46.02771 -0.3827 9.24834
May 744.00000 21.51609 53.08411 -1.2947 41.21500
June 720.00000 21.68602 57.62739 -1.0948 32.04004
July 744.00000 21.72616 57.69489 -1.0383 29.65599
August 744.00000 21.71732 55.50344 -1.0526 30.32952
September 720.00000 21.57503 57.30209 -1.2156 37.43774
October 744.00000 21.32662 51.73282 -0.2700 7.74755
November 720.00000 20.72682 42.39669 -0.6079 13.52539
December 744.00000 20.52975 33.69220 -0.7571 17.56721
           
Annual Sum or Average 8760.00000 21.15616 46.39265 -0.8224 22.43322
Minimum of Months 672.00000 20.51144 28.19964 -1.2947 7.74755
Maximum of Months 744.00000 21.72616 57.69489 -0.2700 41.21500



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.02399 33.88599 -0.5517 12.57316
February 672.00000 21.21563 28.59469 -0.5060 11.78611
March 744.00000 21.29241 39.06264 -0.3848 9.34811
April 720.00000 21.38795 45.89440 -0.2917 8.04051
May 744.00000 21.55308 52.52065 -1.2998 41.44579
June 720.00000 21.66980 57.81093 -1.1506 34.39384
July 744.00000 21.72059 57.38708 -1.0903 31.79993
August 744.00000 21.72572 54.84501 -1.0725 31.34647
September 720.00000 21.65861 55.26941 -1.1529 34.96947
October 744.00000 21.62999 49.03830 -0.1184 6.85608
November 720.00000 21.34397 42.02940 -0.3553 8.80373
December 744.00000 21.14097 33.86784 -0.4948 11.43695
           
Annual Sum or Average 8760.00000 21.44805 45.94413 -0.7070 20.28833
Minimum of Months 672.00000 21.02399 28.59469 -1.2998 6.85608
Maximum of Months 744.00000 21.72572 57.81093 -0.1184 41.44579



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.19242 34.09626 0.11215 6.18785
February 672.00000 23.20504 30.11950 0.08753 6.01870
March 744.00000 23.56355 37.48468 0.26338 6.99035
April 720.00000 23.73441 42.64121 0.37623 8.37093
May 744.00000 23.89294 49.15882 -0.3602 7.99295
June 720.00000 23.96607 58.22877 -0.2106 6.04742
July 744.00000 23.98800 61.58252 -0.1524 5.50228
August 744.00000 23.97739 58.89836 -0.1810 5.75145
September 720.00000 23.92392 55.49277 -0.2794 6.87927
October 744.00000 23.80680 48.24153 0.45279 9.77816
November 720.00000 23.53831 39.40601 0.26943 7.13663
December 744.00000 23.35927 33.72316 0.15994 6.17867
           
Annual Sum or Average 8760.00000 23.68168 45.84974 0.04454 6.90790
Minimum of Months 672.00000 23.19242 30.11950 -0.3602 5.50228
Maximum of Months 744.00000 23.98800 61.58252 0.45279 9.77816



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.43937 33.06591 0.21026 6.64601
February 672.00000 23.44583 29.15447 0.18372 6.36350
March 744.00000 23.73495 36.41790 0.34296 7.84256
April 720.00000 23.86307 41.66830 0.44368 9.41314
May 744.00000 23.95150 48.37319 -0.2918 6.97697
June 720.00000 23.98570 57.68298 -0.1644 5.66984
July 744.00000 23.99304 61.12513 -0.1139 5.28862
August 744.00000 23.98854 58.42926 -0.1409 5.47457
September 720.00000 23.96276 54.84391 -0.2248 6.24667
October 744.00000 23.89334 47.41251 0.50523 10.74744
November 720.00000 23.71453 38.35607 0.34978 8.00614
December 744.00000 23.56578 32.64354 0.24844 6.74038
           
Annual Sum or Average 8760.00000 23.79679 45.02563 0.11188 7.12182
Minimum of Months 672.00000 23.43937 29.15447 -0.2918 5.28862
Maximum of Months 744.00000 23.99304 61.12513 0.50523 10.74744



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.65852 31.66660 0.86958 24.17447
February 672.00000 23.65225 27.74251 0.84868 23.50118
March 744.00000 23.85444 35.43397 1.00472 29.09698
April 720.00000 23.87129 40.89913 1.09346 32.59610
May 744.00000 23.89127 47.56939 0.63405 18.00069
June 720.00000 23.94693 56.81201 0.77816 21.62118
July 744.00000 23.96497 60.24229 0.84449 23.47079
August 744.00000 23.97543 57.52174 0.83573 23.39124
September 720.00000 23.91288 53.81657 0.71343 19.83418
October 744.00000 23.88812 46.35445 1.16224 35.50812
November 720.00000 23.84579 37.40665 1.00944 29.12857
December 744.00000 23.73840 31.37506 0.90448 25.08024
           
Annual Sum or Average 8760.00000 23.85117 43.99970 0.89181 25.46255
Minimum of Months 672.00000 23.65225 27.74251 0.63405 18.00069
Maximum of Months 744.00000 23.97543 60.24229 1.16224 35.50812



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00407 28.30132 -0.5154 10.68052
February 672.00000 21.00054 23.72132 -0.5418 11.21537
March 744.00000 21.09081 33.38641 -0.4341 9.08776
April 720.00000 21.43240 39.66965 -0.3016 7.36499
May 744.00000 22.17294 46.57817 -1.1530 33.44198
June 720.00000 23.11535 55.44035 -0.7621 17.62188
July 744.00000 23.53393 58.92921 -0.5893 12.39775
August 744.00000 23.56510 55.26638 -0.6019 12.79968
September 720.00000 22.92733 52.11107 -0.8494 20.90926
October 744.00000 22.20358 44.74040 -0.0689 5.72029
November 720.00000 21.25380 35.61879 -0.3777 8.28338
December 744.00000 21.00723 28.36741 -0.4979 10.22619
           
Annual Sum or Average 8760.00000 22.03230 41.95080 -0.5577 13.32711
Minimum of Months 672.00000 21.00054 23.72132 -1.1530 5.72029
Maximum of Months 744.00000 23.56510 58.92921 -0.0689 33.44198



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.01528 31.86563 -0.4918 10.15473
February 672.00000 21.02221 27.29196 -0.5099 10.49462
March 744.00000 21.22305 36.68867 -0.3915 8.36024
April 720.00000 21.71194 42.53516 -0.2318 6.61923
May 744.00000 22.45727 49.27405 -1.0659 29.49430
June 720.00000 23.36030 57.60033 -0.6884 15.21845
July 744.00000 23.69933 60.62349 -0.5445 11.28150
August 744.00000 23.79807 57.20356 -0.5304 10.98285
September 720.00000 23.20860 54.46464 -0.7621 18.07997
October 744.00000 22.65271 47.08644 0.03887 5.50864
November 720.00000 21.36646 38.85956 -0.3460 7.90026
December 744.00000 21.03285 31.85548 -0.4798 9.85444
           
Annual Sum or Average 8760.00000 22.21993 44.71365 -0.5001 12.00856
Minimum of Months 672.00000 21.01528 27.29196 -1.0659 5.50864
Maximum of Months 744.00000 23.79807 60.62349 0.03887 29.49430



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.01583 29.62811 -0.4987 10.33738
February 672.00000 21.03403 25.04209 -0.5151 10.65348
March 744.00000 21.22155 34.45618 -0.3806 8.27752
April 720.00000 21.66650 40.30892 -0.2196 6.73860
May 744.00000 22.46121 46.89268 -1.0117 27.55046
June 720.00000 23.42978 54.83480 -0.6023 13.11867
July 744.00000 23.77125 57.72879 -0.4502 9.39997
August 744.00000 23.76547 54.69585 -0.4693 9.87395
September 720.00000 23.11640 52.23580 -0.7342 17.50904
October 744.00000 22.34945 45.27417 -0.0040 5.97591
November 720.00000 21.24266 36.79363 -0.3638 8.09524
December 744.00000 21.03609 29.61427 -0.4792 9.86126
           
Annual Sum or Average 8760.00000 22.18318 42.39278 -0.4771 11.45675
Minimum of Months 672.00000 21.01583 25.04209 -1.0117 5.97591
Maximum of Months 744.00000 23.77125 57.72879 -0.0040 27.55046



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.03291 27.81534 -0.4925 10.21998
February 672.00000 21.02490 23.26489 -0.5209 10.76358
March 744.00000 21.20475 32.71339 -0.3981 8.53385
April 720.00000 21.59868 38.81232 -0.2553 6.89484
May 744.00000 22.37230 45.49685 -1.0759 30.00401
June 720.00000 23.28490 54.18166 -0.6924 15.52994
July 744.00000 23.64270 57.62753 -0.5381 11.20471
August 744.00000 23.66388 54.13000 -0.5528 11.60959
September 720.00000 23.09901 50.95365 -0.7794 18.54288
October 744.00000 22.38570 43.74443 -0.0199 5.64405
November 720.00000 21.39522 34.82794 -0.3359 7.75506
December 744.00000 21.05365 27.85889 -0.4736 9.74845
           
Annual Sum or Average 8760.00000 22.15360 41.05661 -0.5111 12.21635
Minimum of Months 672.00000 21.02490 23.26489 -1.0759 5.64405
Maximum of Months 744.00000 23.66388 57.62753 -0.0199 30.00401



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.162124E+10 15333.43 13-JAN-09:04 220.41 0.516597E+10 0.00 0.678721E+10 0.94 3.19 05-JAN-12:50 0.00 0.00
February 0.203932E+10 16601.19 16-FEB-09:04 230.26 0.649817E+10 0.00 0.853749E+10 1.09 3.19 02-FEB-12:43 0.00 0.00
March 0.624398E+10 74919.30 27-MAR-15:02 366.85 0.193101E+11 0.00 0.255541E+11 1.56 3.23 27-MAR-15:02 0.00 0.00
April 0.256396E+11 112668.82 07-APR-15:03 500.51 0.764888E+11 0.00 0.102128E+12 2.17 3.53 07-APR-18:03 0.00 0.00
May 0.754869E+11 127092.04 31-MAY-18:03 719.14 0.226108E+12 0.00 0.301595E+12 2.95 4.09 31-MAY-18:03 0.00 0.00
June 0.220917E+12 194312.14 19-JUN-18:03 720.00 0.751385E+12 0.00 0.972303E+12 3.31 4.20 24-JUN-18:03 0.00 0.00
July 0.320858E+12 188935.01 20-JUL-18:03 744.00 0.113257E+13 0.00 0.145343E+13 3.52 4.23 23-JUL-18:03 0.00 0.00
August 0.287349E+12 209420.06 16-AUG-15:03 744.00 0.961589E+12 0.00 0.124894E+13 3.29 4.19 06-AUG-18:02 0.00 0.00
September 0.165822E+12 164209.56 07-SEP-20:40 718.79 0.546447E+12 0.00 0.712269E+12 3.17 4.23 22-SEP-18:02 0.00 0.00
October 0.731971E+11 126761.44 04-OCT-15:03 688.33 0.232261E+12 0.00 0.305458E+12 2.90 4.17 05-OCT-18:02 0.00 0.00
November 0.697494E+10 46806.36 04-NOV-15:01 383.01 0.217679E+11 0.00 0.287428E+11 1.69 3.19 01-NOV-06:10 0.00 0.00
December 0.304899E+10 18310.07 17-DEC-16:04 312.38 0.971540E+10 0.00 0.127644E+11 1.34 3.19 01-DEC-16:06 0.00 0.00
                         
Annual Sum or Average 0.118920E+13     6347.69 0.398931E+13 0.00 0.517851E+13 2.33     0.00 0.00
Minimum of Months 0.162124E+10 15333.43   220.41 0.516597E+10 0.00 0.678721E+10 0.94 3.19   0.00 0.00
Maximum of Months 0.320858E+12 209420.06   744.00 0.113257E+13 0.00 0.145343E+13 3.52 4.23   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.142967E+12 0.00 744.00 244134.17 02-JAN-09:03 0.00 51.36 80.87 0.43 0.00 0.11 0.50 02-JAN-09:03
February 0.121360E+12 0.00 671.93 250248.53 06-FEB-09:01 0.00 52.31 81.06 0.40 0.00 0.10 0.51 06-FEB-09:01
March 0.581199E+11 0.00 725.08 188916.36 31-MAR-15:01 0.00 52.23 79.35 0.20 0.00 0.04 0.39 31-MAR-15:01
April 0.356546E+11 0.00 552.30 179631.66 21-APR-15:01 0.00 45.03 70.64 0.11 0.00 0.03 0.37 21-APR-15:01
May 0.847328E+10 0.00 294.09 121348.43 15-MAY-02:45 0.00 41.86 56.05 0.02 0.00 0.01 0.25 15-MAY-02:45
June 0.260198E+09 0.00 14.14 42838.50 06-JUN-15:05 0.00 48.25 48.97 0.00 0.00 0.00 0.09 06-JUN-15:05
July 57763819.46 0.00 2.54 22033.06 14-JUL-08:07 0.00 53.85 53.94 0.00 0.00 0.00 0.04 14-JUL-08:07
August 0.298431E+09 0.00 13.81 43179.12 30-AUG-08:05 0.00 48.13 48.74 0.00 0.00 0.00 0.09 30-AUG-08:05
September 0.168547E+10 0.00 112.44 58380.05 24-SEP-05:16 0.00 53.19 57.34 0.00 0.00 0.00 0.12 24-SEP-05:16
October 0.165279E+11 0.00 370.51 141585.99 26-OCT-23:27 0.00 48.14 64.19 0.05 0.00 0.01 0.29 26-OCT-23:27
November 0.619180E+11 0.00 687.15 203416.42 27-NOV-16:01 0.00 51.37 78.59 0.21 0.00 0.05 0.41 27-NOV-16:01
December 0.878531E+11 0.00 743.91 192608.75 04-DEC-19:01 0.00 54.19 80.52 0.31 0.00 0.07 0.39 04-DEC-19:01
                           
Annual Sum or Average 0.535176E+12 0.00 4931.90     0.00 49.98 66.60 0.14 0.00 0.03    
Minimum of Months 57763819.46 0.00 2.54 22033.06   0.00 41.86 48.74 0.00 0.00 0.00 0.04  
Maximum of Months 0.142967E+12 0.00 744.00 250248.53   0.00 54.19 81.06 0.43 0.00 0.11 0.51  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.227956E+09 0.00 138.31 0.227956E+09 0.00 0.00 0.00 0.00 28016.06 12-JAN-22:44 28016.06 12-JAN-22:44 0.00 0.00 0.00
February 0.207446E+09 0.00 123.71 0.207446E+09 0.00 0.00 0.00 0.00 14207.43 28-FEB-21:59 14207.43 28-FEB-21:59 0.00 0.00 0.00
March 0.355282E+10 0.00 153.29 0.352241E+10 0.00 0.00 0.00 0.00 130064.22 27-MAR-16:00 130064.22 27-MAR-16:00 0.00 0.00 0.00
April 0.341923E+11 0.00 252.63 0.339495E+11 0.00 0.00 0.00 0.00 210145.33 09-APR-10:50 205181.39 07-APR-17:04 0.00 0.00 0.00
May 0.126129E+12 0.00 486.96 0.108859E+12 0.00 0.00 0.00 0.00 291468.15 31-MAY-17:17 222435.02 29-MAY-12:25 0.00 0.00 0.00
June 0.519220E+12 0.00 707.92 0.312368E+12 0.00 0.00 0.00 0.00 471839.16 24-JUN-17:12 301944.59 22-JUN-18:20 0.00 0.00 0.00
July 0.817177E+12 0.00 744.00 0.447467E+12 0.00 0.00 0.00 0.00 489707.03 27-JUL-21:00 283289.18 11-JUL-18:03 0.00 0.00 0.00
August 0.666890E+12 0.00 744.00 0.440176E+12 0.00 0.00 0.00 0.00 505719.26 11-AUG-22:00 353485.27 24-AUG-18:30 0.00 0.00 0.00
September 0.362678E+12 0.00 652.35 0.251324E+12 0.00 0.00 0.00 0.00 479564.58 13-SEP-21:00 296392.49 01-SEP-20:30 0.00 0.00 0.00
October 0.125687E+12 0.00 410.24 0.811245E+11 0.00 0.00 0.00 0.00 287726.08 05-OCT-19:10 181628.31 25-OCT-10:33 0.00 0.00 0.00
November 0.359820E+10 0.00 164.09 0.330487E+10 0.00 0.00 0.00 0.00 63869.16 04-NOV-10:50 63869.16 04-NOV-10:50 0.00 0.00 0.00
December 0.459344E+09 0.00 206.18 0.459344E+09 0.00 0.00 0.00 0.00 30701.03 03-DEC-20:45 30701.03 03-DEC-20:45 0.00 0.00 0.00
                               
Annual Sum or Average 0.266002E+13 0.00 4783.68 0.168299E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.207446E+09 0.00 123.71 0.207446E+09 0.00 0.00 0.00 0.00 14207.43   14207.43   0.00 0.00 0.00
Maximum of Months 0.817177E+12 0.00 744.00 0.447467E+12 0.00 0.00 0.00 0.00 505719.26   353485.27   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 0.00 0.00
March 0.697382E+09 0.00 19.92 0.589145E+09 0.00 0.00 0.00 0.00 32906.47 27-MAR-13:00 25442.26 27-MAR-16:00 0.00 0.00 0.00
April 0.634269E+10 0.00 144.69 0.616737E+10 0.00 0.00 0.00 0.00 40374.02 09-APR-11:00 29723.00 07-APR-13:00 0.00 0.00 0.00
May 0.232123E+11 0.00 446.03 0.196119E+11 0.00 0.00 0.00 0.00 51821.69 31-MAY-17:06 32643.06 30-MAY-13:00 0.00 0.00 0.00
June 0.961906E+11 0.00 707.83 0.555096E+11 0.00 0.00 0.00 0.00 79002.93 24-JUN-17:25 37360.91 19-JUN-12:00 0.00 0.00 0.00
July 0.130865E+12 0.00 744.00 0.745834E+11 0.00 0.00 0.00 0.00 77079.99 23-JUL-14:20 35565.34 07-JUL-12:00 0.00 0.00 0.00
August 0.107294E+12 0.00 744.00 0.710766E+11 0.00 0.00 0.00 0.00 73614.51 06-AUG-07:17 35442.98 24-AUG-15:00 0.00 0.00 0.00
September 0.663363E+11 0.00 641.83 0.447544E+11 0.00 0.00 0.00 0.00 76059.89 22-SEP-17:30 33319.71 01-SEP-14:00 0.00 0.00 0.00
October 0.245200E+11 0.00 337.89 0.147924E+11 0.00 0.00 0.00 0.00 52292.02 24-OCT-14:00 28849.49 04-OCT-13:00 0.00 0.00 0.00
November 0.605095E+09 0.00 33.17 0.541138E+09 0.00 0.00 0.00 0.00 12351.77 10-NOV-08:00 10814.14 04-NOV-13:00 0.00 0.00 0.00
December 2300.65 0.00 0.02 2300.65 0.00 0.00 0.00 0.00 34.51 04-DEC-21:10 34.51 04-DEC-21:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.456064E+12 0.00 3819.38 0.287626E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.130865E+12 0.00 744.00 0.745834E+11 0.00 0.00 0.00 0.00 79002.93   37360.91   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 42773173.65 0.00 9.81 41754485.90 0.00 0.00 0.00 0.00 13495.69 17-JAN-16:02 13495.69 17-JAN-16:02 0.00 0.00 0.00
February 0.116071E+09 0.00 20.39 0.116007E+09 0.00 0.00 0.00 0.00 13498.30 20-FEB-16:02 13498.30 20-FEB-16:02 0.00 0.00 0.00
March 0.814529E+09 0.00 117.95 0.756171E+09 0.00 0.00 0.00 0.00 14380.44 27-MAR-15:02 13502.96 29-MAR-15:02 0.00 0.00 0.00
April 0.213957E+10 0.00 289.33 0.156050E+10 0.00 0.00 0.00 0.00 14069.37 10-APR-15:02 14069.37 10-APR-15:02 0.00 0.00 0.00
May 0.457448E+10 0.00 552.68 0.317833E+10 0.00 0.00 0.00 0.00 15534.62 18-MAY-15:02 14344.02 20-MAY-18:02 0.00 0.00 0.00
June 0.901664E+10 0.00 656.55 0.535116E+10 0.00 0.00 0.00 0.00 18881.22 27-JUN-08:62 14419.37 15-JUN-15:02 0.00 0.00 0.00
July 0.116257E+11 0.00 701.11 0.698409E+10 0.00 0.00 0.00 0.00 18931.26 30-JUL-08:62 14562.71 07-JUL-18:02 0.00 0.00 0.00
August 0.122018E+11 0.00 703.89 0.801563E+10 0.00 0.00 0.00 0.00 18177.60 27-AUG-08:62 14445.03 02-AUG-18:02 0.00 0.00 0.00
September 0.699127E+10 0.00 625.38 0.425074E+10 0.00 0.00 0.00 0.00 19228.94 22-SEP-18:02 14508.73 07-SEP-15:02 0.00 0.00 0.00
October 0.448725E+10 0.00 524.90 0.286025E+10 0.00 0.00 0.00 0.00 16562.04 05-OCT-18:02 13691.80 02-OCT-18:02 0.00 0.00 0.00
November 0.361447E+09 0.00 95.56 0.283646E+09 0.00 0.00 0.00 0.00 13696.27 03-NOV-15:02 13696.27 03-NOV-15:02 0.00 0.00 0.00
December 50638906.34 0.00 14.15 50096024.44 0.00 0.00 0.00 0.00 13434.86 17-DEC-16:01 13434.86 17-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.524221E+11 0.00 4311.68 0.334484E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 42773173.65 0.00 9.81 41754485.90 0.00 0.00 0.00 0.00 13434.86   13434.86   0.00 0.00 0.00
Maximum of Months 0.122018E+11 0.00 703.89 0.801563E+10 0.00 0.00 0.00 0.00 19228.94   14562.71   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 8835162.58 0.00 1.53 7858671.06 0.00 0.00 0.00 0.00 7460.77 17-JAN-16:02 7460.77 17-JAN-16:02 0.00 0.00 0.00
February 18847774.53 0.00 6.06 18771190.86 0.00 0.00 0.00 0.00 12121.39 20-FEB-16:02 12121.39 20-FEB-16:02 0.00 0.00 0.00
March 0.364371E+09 0.00 57.79 0.328886E+09 0.00 0.00 0.00 0.00 13522.11 27-MAR-15:02 13092.28 07-MAR-16:01 0.00 0.00 0.00
April 0.147966E+10 0.00 227.88 0.104669E+10 0.00 0.00 0.00 0.00 13646.92 10-APR-15:02 13646.92 10-APR-15:02 0.00 0.00 0.00
May 0.409612E+10 0.00 521.73 0.280103E+10 0.00 0.00 0.00 0.00 15027.43 18-MAY-15:02 13914.03 20-MAY-18:02 0.00 0.00 0.00
June 0.862299E+10 0.00 648.98 0.510424E+10 0.00 0.00 0.00 0.00 18286.21 27-JUN-08:62 13987.03 15-JUN-15:02 0.00 0.00 0.00
July 0.110843E+11 0.00 697.37 0.659705E+10 0.00 0.00 0.00 0.00 18380.73 30-JUL-08:62 14118.29 07-JUL-18:02 0.00 0.00 0.00
August 0.108497E+11 0.00 693.94 0.687075E+10 0.00 0.00 0.00 0.00 17679.79 27-AUG-08:62 14185.70 12-AUG-15:02 0.00 0.00 0.00
September 0.547440E+10 0.00 579.95 0.306363E+10 0.00 0.00 0.00 0.00 18637.62 22-SEP-18:02 14002.42 01-SEP-18:02 0.00 0.00 0.00
October 0.246441E+10 0.00 394.02 0.136717E+10 0.00 0.00 0.00 0.00 15492.37 05-OCT-18:02 13537.15 03-OCT-15:02 0.00 0.00 0.00
November 80861084.93 0.00 25.52 66294791.70 0.00 0.00 0.00 0.00 13285.58 03-NOV-15:02 13285.58 03-NOV-15:02 0.00 0.00 0.00
December 6128130.11 0.00 0.95 5630201.85 0.00 0.00 0.00 0.00 4554.49 17-DEC-19:03 4554.49 17-DEC-19:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.445506E+11 0.00 3855.72 0.272780E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 6128130.11 0.00 0.95 5630201.85 0.00 0.00 0.00 0.00 4554.49   4554.49   0.00 0.00 0.00
Maximum of Months 0.110843E+11 0.00 697.37 0.687075E+10 0.00 0.00 0.00 0.00 18637.62   14185.70   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.123189E+09 0.00 7.94 0.123189E+09 0.00 0.00 0.00 0.00 7563.27 19-JAN-14:40 7563.27 19-JAN-14:40 0.00 0.00 0.00
February 0.814508E+09 0.00 26.68 0.814508E+09 0.00 0.00 0.00 0.00 17093.77 20-FEB-13:23 17093.77 20-FEB-13:23 0.00 0.00 0.00
March 0.258465E+10 0.00 69.57 0.257064E+10 0.00 0.00 0.00 0.00 30352.29 03-MAR-13:30 30352.29 03-MAR-13:30 0.00 0.00 0.00
April 0.601189E+10 0.00 132.03 0.452566E+10 0.00 0.00 0.00 0.00 39540.94 08-APR-12:30 36068.39 07-APR-13:00 0.00 0.00 0.00
May 0.954621E+10 0.00 271.16 0.694827E+10 0.00 0.00 0.00 0.00 30973.35 31-MAY-12:30 23561.44 30-MAY-12:50 0.00 0.00 0.00
June 0.213051E+11 0.00 458.78 0.996113E+10 0.00 0.00 0.00 0.00 35298.71 19-JUN-12:50 27245.40 19-JUN-13:20 0.00 0.00 0.00
July 0.388565E+11 0.00 666.69 0.189783E+11 0.00 0.00 0.00 0.00 37812.58 08-JUL-12:10 30731.19 10-JUL-13:10 0.00 0.00 0.00
August 0.478974E+11 0.00 696.41 0.285532E+11 0.00 0.00 0.00 0.00 45562.27 16-AUG-14:50 37415.05 30-AUG-13:30 0.00 0.00 0.00
September 0.304814E+11 0.00 501.94 0.198099E+11 0.00 0.00 0.00 0.00 50077.34 30-SEP-12:30 48431.08 30-SEP-12:50 0.00 0.00 0.00
October 0.305560E+11 0.00 437.27 0.239748E+11 0.00 0.00 0.00 0.00 54513.71 04-OCT-12:00 49230.71 30-OCT-13:20 0.00 0.00 0.00
November 0.557547E+10 0.00 110.65 0.532256E+10 0.00 0.00 0.00 0.00 43745.13 02-NOV-12:50 43745.13 02-NOV-12:50 0.00 0.00 0.00
December 0.214862E+10 0.00 45.18 0.214862E+10 0.00 0.00 0.00 0.00 30820.04 17-DEC-13:40 30820.04 17-DEC-13:40 0.00 0.00 0.00
                               
Annual Sum or Average 0.195901E+12 0.00 3424.30 0.123731E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.123189E+09 0.00 7.94 0.123189E+09 0.00 0.00 0.00 0.00 7563.27   7563.27   0.00 0.00 0.00
Maximum of Months 0.478974E+11 0.00 696.41 0.285532E+11 0.00 0.00 0.00 0.00 54513.71   49230.71   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.120826E+09 0.00 9.00 79896470.38 0.00 0.00 0.00 0.00 43724.31 03-JAN-19:03 41427.88 03-JAN-19:03 0.00 0.00 0.00
February 54776754.09 0.00 1.53 54776754.09 0.00 0.00 0.00 0.00 40768.03 01-FEB-19:03 40768.03 01-FEB-19:03 0.00 0.00 0.00
March 0.152831E+10 0.00 100.95 0.109903E+10 0.00 0.00 0.00 0.00 62586.23 28-MAR-18:02 62586.23 28-MAR-18:02 0.00 0.00 0.00
April 0.999686E+10 0.00 329.23 0.625558E+10 0.00 0.00 0.00 0.00 68282.57 08-APR-15:02 68282.57 08-APR-15:02 0.00 0.00 0.00
May 0.298417E+11 0.00 522.50 0.203196E+11 0.00 0.00 0.00 0.00 81769.96 31-MAY-18:02 72889.82 29-MAY-15:02 0.00 0.00 0.00
June 0.529524E+11 0.00 519.74 0.325324E+11 0.00 0.00 0.00 0.00 100007.38 27-JUN-08:62 73694.59 20-JUN-15:02 0.00 0.00 0.00
July 0.668572E+11 0.00 564.41 0.426349E+11 0.00 0.00 0.00 0.00 100848.22 30-JUL-08:62 74218.87 11-JUL-15:02 0.00 0.00 0.00
August 0.585720E+11 0.00 552.91 0.378434E+11 0.00 0.00 0.00 0.00 95871.55 06-AUG-08:62 74232.65 22-AUG-15:02 0.00 0.00 0.00
September 0.353832E+11 0.00 506.78 0.201302E+11 0.00 0.00 0.00 0.00 102790.43 22-SEP-18:02 72819.62 01-SEP-18:02 0.00 0.00 0.00
October 0.151273E+11 0.00 435.97 0.750615E+10 0.00 0.00 0.00 0.00 80764.54 05-OCT-18:02 65144.70 04-OCT-15:02 0.00 0.00 0.00
November 0.215206E+10 0.00 145.23 0.133799E+10 0.00 0.00 0.00 0.00 63042.10 05-NOV-08:62 63042.10 05-NOV-08:62 0.00 0.00 0.00
December 0.116948E+09 0.00 6.48 0.107466E+09 0.00 0.00 0.00 0.00 31687.95 29-DEC-19:04 31687.95 29-DEC-19:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.272704E+12 0.00 3694.74 0.169901E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 54776754.09 0.00 1.53 54776754.09 0.00 0.00 0.00 0.00 31687.95   31687.95   0.00 0.00 0.00
Maximum of Months 0.668572E+11 0.00 564.41 0.426349E+11 0.00 0.00 0.00 0.00 102790.43   74232.65   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 81009770.63 0.00 17.25 80064473.08 0.00 0.00 0.00 0.00 10932.81 19-JAN-09:01 10932.81 19-JAN-09:01 0.00 0.00 0.00
February 0.127168E+09 0.00 25.57 0.127112E+09 0.00 0.00 0.00 0.00 11864.33 25-FEB-09:01 11864.33 25-FEB-09:01 0.00 0.00 0.00
March 0.671305E+09 0.00 121.65 0.634803E+09 0.00 0.00 0.00 0.00 12622.56 27-MAR-15:02 12336.09 03-MAR-09:02 0.00 0.00 0.00
April 0.215556E+10 0.00 314.89 0.153309E+10 0.00 0.00 0.00 0.00 12845.27 10-APR-15:02 12845.27 10-APR-15:02 0.00 0.00 0.00
May 0.477714E+10 0.00 565.24 0.337386E+10 0.00 0.00 0.00 0.00 14480.16 31-MAY-18:02 13095.38 20-MAY-18:02 0.00 0.00 0.00
June 0.849075E+10 0.00 666.66 0.496273E+10 0.00 0.00 0.00 0.00 16811.57 21-JUN-18:02 13274.37 23-JUN-08:62 0.00 0.00 0.00
July 0.114733E+11 0.00 713.30 0.686222E+10 0.00 0.00 0.00 0.00 17021.36 30-JUL-08:62 13154.56 13-JUL-15:02 0.00 0.00 0.00
August 0.120791E+11 0.00 721.38 0.790925E+10 0.00 0.00 0.00 0.00 16208.78 06-AUG-08:62 13211.00 02-AUG-15:02 0.00 0.00 0.00
September 0.706971E+10 0.00 641.82 0.433513E+10 0.00 0.00 0.00 0.00 17558.22 22-SEP-18:02 13282.84 07-SEP-15:02 0.00 0.00 0.00
October 0.429773E+10 0.00 536.61 0.271408E+10 0.00 0.00 0.00 0.00 14997.85 05-OCT-18:02 12777.14 03-OCT-15:02 0.00 0.00 0.00
November 0.535234E+09 0.00 115.65 0.437506E+09 0.00 0.00 0.00 0.00 12504.88 03-NOV-15:02 12504.88 03-NOV-15:02 0.00 0.00 0.00
December 0.145900E+09 0.00 29.25 0.141820E+09 0.00 0.00 0.00 0.00 11794.94 17-DEC-09:01 11794.94 17-DEC-09:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.519039E+11 0.00 4469.27 0.331117E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 81009770.63 0.00 17.25 80064473.08 0.00 0.00 0.00 0.00 10932.81   10932.81   0.00 0.00 0.00
Maximum of Months 0.120791E+11 0.00 721.38 0.790925E+10 0.00 0.00 0.00 0.00 17558.22   13282.84   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 9518493.76 0.00 3.15 8663992.49 0.00 0.00 0.00 0.00 4711.70 24-JAN-19:04 4213.35 26-JAN-09:03 0.00 0.00 0.00
February 18186644.54 0.00 6.57 18156523.46 0.00 0.00 0.00 0.00 9493.41 19-FEB-09:01 9493.41 19-FEB-09:01 0.00 0.00 0.00
March 0.252296E+09 0.00 53.75 0.233750E+09 0.00 0.00 0.00 0.00 11981.71 03-MAR-09:02 11981.71 03-MAR-09:02 0.00 0.00 0.00
April 0.144536E+10 0.00 251.57 0.990257E+09 0.00 0.00 0.00 0.00 12482.92 09-APR-15:02 12477.33 10-APR-15:02 0.00 0.00 0.00
May 0.425831E+10 0.00 547.97 0.295713E+10 0.00 0.00 0.00 0.00 13857.10 18-MAY-15:02 12789.55 31-MAY-15:02 0.00 0.00 0.00
June 0.807934E+10 0.00 663.69 0.470656E+10 0.00 0.00 0.00 0.00 16302.50 21-JUN-18:02 12975.69 07-JUN-18:02 0.00 0.00 0.00
July 0.109252E+11 0.00 712.16 0.644854E+10 0.00 0.00 0.00 0.00 16557.90 30-JUL-08:62 12915.51 07-JUL-15:02 0.00 0.00 0.00
August 0.107131E+11 0.00 717.62 0.667766E+10 0.00 0.00 0.00 0.00 16142.21 06-AUG-08:62 12830.38 13-AUG-08:62 0.00 0.00 0.00
September 0.550850E+10 0.00 614.67 0.313846E+10 0.00 0.00 0.00 0.00 17043.29 22-SEP-18:02 12974.82 01-SEP-18:02 0.00 0.00 0.00
October 0.223169E+10 0.00 383.44 0.123375E+10 0.00 0.00 0.00 0.00 14776.48 25-OCT-08:62 11997.93 02-OCT-15:02 0.00 0.00 0.00
November 0.157155E+09 0.00 43.00 0.116888E+09 0.00 0.00 0.00 0.00 10946.07 06-NOV-09:02 10946.07 06-NOV-09:02 0.00 0.00 0.00
December 11629740.17 0.00 5.02 11261315.91 0.00 0.00 0.00 0.00 3902.90 09-DEC-09:03 3902.90 09-DEC-09:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.436103E+11 0.00 4002.60 0.265411E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 9518493.76 0.00 3.15 8663992.49 0.00 0.00 0.00 0.00 3902.90   3902.90   0.00 0.00 0.00
Maximum of Months 0.109252E+11 0.00 717.62 0.667766E+10 0.00 0.00 0.00 0.00 17043.29   12975.69   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 11597952.98 0.00 7.95 11282813.33 0.00 0.00 0.00 0.00 3541.01 17-JAN-16:02 3541.01 17-JAN-16:02 0.00 0.00 0.00
February 29898443.97 0.00 18.29 29859265.87 0.00 0.00 0.00 0.00 3541.70 20-FEB-16:02 3541.70 20-FEB-16:02 0.00 0.00 0.00
March 0.203734E+09 0.00 99.08 0.189028E+09 0.00 0.00 0.00 0.00 3797.28 27-MAR-15:02 3543.92 29-MAR-18:02 0.00 0.00 0.00
April 0.526167E+09 0.00 249.42 0.397838E+09 0.00 0.00 0.00 0.00 3691.48 10-APR-15:02 3691.48 10-APR-15:02 0.00 0.00 0.00
May 0.111371E+10 0.00 495.03 0.803077E+09 0.00 0.00 0.00 0.00 4143.73 31-MAY-08:62 3763.42 20-MAY-18:02 0.00 0.00 0.00
June 0.225745E+10 0.00 655.59 0.133289E+10 0.00 0.00 0.00 0.00 5142.55 27-JUN-08:62 3822.97 19-JUN-15:02 0.00 0.00 0.00
July 0.297448E+10 0.00 700.57 0.177382E+10 0.00 0.00 0.00 0.00 5192.21 30-JUL-08:62 3789.70 07-JUL-18:02 0.00 0.00 0.00
August 0.309870E+10 0.00 702.45 0.201853E+10 0.00 0.00 0.00 0.00 4981.70 27-AUG-08:62 3810.67 03-AUG-15:02 0.00 0.00 0.00
September 0.167196E+10 0.00 584.25 0.101370E+10 0.00 0.00 0.00 0.00 5217.02 22-SEP-18:02 3826.58 14-SEP-18:02 0.00 0.00 0.00
October 0.990745E+09 0.00 439.71 0.636464E+09 0.00 0.00 0.00 0.00 4433.72 05-OCT-18:02 3592.81 02-OCT-18:02 0.00 0.00 0.00
November 67547344.21 0.00 61.56 55227836.72 0.00 0.00 0.00 0.00 3593.58 03-NOV-15:02 3593.58 03-NOV-15:02 0.00 0.00 0.00
December 11437305.67 0.00 8.39 11281907.28 0.00 0.00 0.00 0.00 3540.21 17-DEC-16:01 3540.21 17-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.129574E+11 0.00 4022.30 0.827300E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 11437305.67 0.00 7.95 11281907.28 0.00 0.00 0.00 0.00 3540.21   3540.21   0.00 0.00 0.00
Maximum of Months 0.309870E+10 0.00 702.45 0.201853E+10 0.00 0.00 0.00 0.00 5217.02   3826.58   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 2828151.59 0.00 1.62 2527977.89 0.00 0.00 0.00 0.00 1134.88 23-JAN-19:04 982.02 20-JAN-16:02 0.00 0.00 0.00
February 3468788.35 0.00 4.19 3432166.88 0.00 0.00 0.00 0.00 2467.47 20-FEB-16:02 2467.47 20-FEB-16:02 0.00 0.00 0.00
March 84507225.04 0.00 47.35 75442682.21 0.00 0.00 0.00 0.00 3546.50 27-MAR-15:02 3426.73 11-MAR-16:02 0.00 0.00 0.00
April 0.356736E+09 0.00 188.24 0.263281E+09 0.00 0.00 0.00 0.00 3591.99 16-APR-18:02 3591.99 16-APR-18:02 0.00 0.00 0.00
May 0.985549E+09 0.00 464.45 0.700930E+09 0.00 0.00 0.00 0.00 3989.40 31-MAY-08:62 3643.04 20-MAY-18:02 0.00 0.00 0.00
June 0.215412E+10 0.00 649.59 0.126552E+10 0.00 0.00 0.00 0.00 4973.87 27-JUN-08:62 3646.36 02-JUN-15:02 0.00 0.00 0.00
July 0.283332E+10 0.00 697.21 0.166990E+10 0.00 0.00 0.00 0.00 5030.61 30-JUL-08:62 3675.89 07-JUL-15:02 0.00 0.00 0.00
August 0.274168E+10 0.00 693.83 0.172027E+10 0.00 0.00 0.00 0.00 4813.87 27-AUG-08:62 3684.23 04-AUG-15:02 0.00 0.00 0.00
September 0.127207E+10 0.00 525.45 0.709840E+09 0.00 0.00 0.00 0.00 5046.91 22-SEP-18:02 3645.20 01-SEP-18:02 0.00 0.00 0.00
October 0.495607E+09 0.00 289.55 0.285122E+09 0.00 0.00 0.00 0.00 4141.58 05-OCT-18:02 3560.76 03-OCT-15:02 0.00 0.00 0.00
November 14855461.42 0.00 13.28 13146505.72 0.00 0.00 0.00 0.00 3449.67 03-NOV-15:02 3449.67 03-NOV-15:02 0.00 0.00 0.00
December 3176098.86 0.00 1.62 3040947.07 0.00 0.00 0.00 0.00 1115.01 08-DEC-16:03 1115.01 08-DEC-16:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.109479E+11 0.00 3576.38 0.671245E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 2828151.59 0.00 1.62 2527977.89 0.00 0.00 0.00 0.00 1115.01   982.02   0.00 0.00 0.00
Maximum of Months 0.283332E+10 0.00 697.21 0.172027E+10 0.00 0.00 0.00 0.00 5046.91   3684.23   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.876715E+09 0.00 89.34 0.875637E+09 0.00 0.00 0.00 0.00 16313.45 17-JAN-16:02 16313.45 17-JAN-16:02 0.00 0.00 0.00
February 0.129096E+10 0.00 137.82 0.129081E+10 0.00 0.00 0.00 0.00 16316.88 20-FEB-16:02 16316.88 20-FEB-16:02 0.00 0.00 0.00
March 0.244458E+10 0.00 222.22 0.230192E+10 0.00 0.00 0.00 0.00 17177.87 27-MAR-15:02 16325.10 28-MAR-15:02 0.00 0.00 0.00
April 0.347770E+10 0.00 333.88 0.260216E+10 0.00 0.00 0.00 0.00 17004.97 10-APR-15:02 17004.97 10-APR-15:02 0.00 0.00 0.00
May 0.548088E+10 0.00 545.96 0.370435E+10 0.00 0.00 0.00 0.00 20114.29 31-MAY-18:02 17344.91 10-MAY-18:02 0.00 0.00 0.00
June 0.105766E+11 0.00 637.66 0.583795E+10 0.00 0.00 0.00 0.00 24173.56 27-JUN-08:62 17645.67 22-JUN-18:02 0.00 0.00 0.00
July 0.146900E+11 0.00 690.34 0.863362E+10 0.00 0.00 0.00 0.00 24194.19 30-JUL-08:62 17532.67 16-JUL-15:02 0.00 0.00 0.00
August 0.160992E+11 0.00 699.65 0.105282E+11 0.00 0.00 0.00 0.00 23130.48 27-AUG-08:62 17620.92 18-AUG-15:02 0.00 0.00 0.00
September 0.112189E+11 0.00 633.86 0.726285E+10 0.00 0.00 0.00 0.00 24643.94 22-SEP-18:02 17381.28 01-SEP-18:02 0.00 0.00 0.00
October 0.982079E+10 0.00 592.24 0.724863E+10 0.00 0.00 0.00 0.00 20732.55 05-OCT-18:02 16937.57 05-OCT-15:02 0.00 0.00 0.00
November 0.227208E+10 0.00 224.51 0.197977E+10 0.00 0.00 0.00 0.00 16554.48 03-NOV-15:02 16554.48 03-NOV-15:02 0.00 0.00 0.00
December 0.156237E+10 0.00 136.88 0.155626E+10 0.00 0.00 0.00 0.00 16312.71 03-DEC-16:02 16312.71 03-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.798107E+11 0.00 4944.35 0.538221E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.876715E+09 0.00 89.34 0.875637E+09 0.00 0.00 0.00 0.00 16312.71   16312.71   0.00 0.00 0.00
Maximum of Months 0.160992E+11 0.00 699.65 0.105282E+11 0.00 0.00 0.00 0.00 24643.94   17645.67   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 701.21 460.14 241.07 679.60 627.85 0.00 0.00 0.00
February 927.98 616.76 311.22 916.07 621.23 0.00 0.00 0.00
March 822.19 452.60 369.58 859.05 441.64 0.00 0.00 0.00
April 654.44 264.77 389.67 720.61 311.18 0.00 0.00 0.00
May 562.08 115.08 447.01 670.77 178.61 0.00 0.00 0.00
June 530.75 81.78 448.97 721.13 85.70 0.00 0.00 0.00
July 552.24 93.21 459.04 820.57 36.90 0.00 0.00 0.00
August 739.68 272.86 466.82 1086.32 64.97 0.00 0.00 0.00
September 780.56 391.91 388.65 1029.02 137.01 0.00 0.00 0.00
October 1103.06 691.71 411.35 1343.67 282.19 0.00 0.00 0.00
November 763.80 458.18 305.62 801.95 436.38 0.00 0.00 0.00
December 757.58 538.07 219.51 763.09 564.69 0.00 0.00 0.00
                 
Annual Sum or Average 740.41 368.50 371.91 867.80 313.98 0.00 0.00 0.00
Minimum of Months 530.75 81.78 219.51 670.77 36.90 0.00 0.00 0.00
Maximum of Months 1103.06 691.71 466.82 1343.67 627.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1974.55 1295.73 678.82 1890.77 1822.60 0.00 0.00 0.00
February 2613.12 1736.75 876.37 2547.67 1808.21 0.00 0.00 0.00
March 2315.23 1274.50 1040.72 2386.24 1325.27 0.00 0.00 0.00
April 1842.86 745.58 1097.28 1992.38 952.97 0.00 0.00 0.00
May 1582.79 324.05 1258.74 1838.35 572.49 0.00 0.00 0.00
June 1494.54 230.28 1264.27 1992.65 283.86 0.00 0.00 0.00
July 1555.08 262.47 1292.62 2281.11 128.38 0.00 0.00 0.00
August 2082.88 768.36 1314.52 3034.84 204.25 0.00 0.00 0.00
September 2198.00 1103.59 1094.42 2864.23 442.71 0.00 0.00 0.00
October 3106.15 1947.82 1158.33 3746.46 872.22 0.00 0.00 0.00
November 2150.80 1290.21 860.60 2221.95 1309.40 0.00 0.00 0.00
December 2133.29 1515.17 618.12 2122.91 1658.03 0.00 0.00 0.00
                 
Annual Sum or Average 2084.94 1037.67 1047.27 2410.39 943.50 0.00 0.00 0.00
Minimum of Months 1494.54 230.28 618.12 1838.35 128.38 0.00 0.00 0.00
Maximum of Months 3106.15 1947.82 1314.52 3746.46 1822.60 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2565.06 1683.23 881.83 2496.08 2487.71 0.00 0.00 0.00
February 3394.59 2256.14 1138.45 3372.45 2449.35 0.00 0.00 0.00
March 3007.61 1655.65 1351.96 3157.90 1805.36 0.00 0.00 0.00
April 2393.98 968.55 1425.43 2633.62 1308.44 0.00 0.00 0.00
May 2056.14 420.96 1635.17 2426.84 788.81 0.00 0.00 0.00
June 1941.50 299.14 1642.35 2639.55 382.51 0.00 0.00 0.00
July 2020.14 340.96 1679.18 3031.05 168.59 0.00 0.00 0.00
August 2705.78 998.14 1707.64 4030.56 263.05 0.00 0.00 0.00
September 2855.33 1433.62 1421.71 3788.10 592.08 0.00 0.00 0.00
October 4035.07 2530.33 1504.74 4957.12 1160.34 0.00 0.00 0.00
November 2794.02 1676.05 1117.96 2929.67 1793.22 0.00 0.00 0.00
December 2771.26 1968.29 802.97 2800.32 2267.42 0.00 0.00 0.00
                 
Annual Sum or Average 2708.45 1347.99 1360.46 3189.19 1282.33 0.00 0.00 0.00
Minimum of Months 1941.50 299.14 802.97 2426.84 168.59 0.00 0.00 0.00
Maximum of Months 4035.07 2530.33 1707.64 4957.12 2487.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 138.64 90.98 47.66 135.49 125.55 0.00 0.00 0.00
February 183.48 121.94 61.53 182.58 124.54 0.00 0.00 0.00
March 162.56 89.49 73.07 170.31 88.61 0.00 0.00 0.00
April 129.39 52.35 77.04 142.51 62.04 0.00 0.00 0.00
May 111.13 22.75 88.38 131.85 34.78 0.00 0.00 0.00
June 104.94 16.17 88.77 144.94 13.39 0.00 0.00 0.00
July 109.19 18.43 90.76 168.95 3.40 0.00 0.00 0.00
August 146.25 53.95 92.30 222.58 8.03 0.00 0.00 0.00
September 154.33 77.49 76.84 207.05 22.66 0.00 0.00 0.00
October 218.09 136.76 81.33 268.58 52.30 0.00 0.00 0.00
November 151.02 90.59 60.43 160.46 85.77 0.00 0.00 0.00
December 149.79 106.39 43.40 152.75 111.92 0.00 0.00 0.00
                 
Annual Sum or Average 146.39 72.86 73.53 174.05 60.73 0.00 0.00 0.00
Minimum of Months 104.94 16.17 43.40 131.85 3.40 0.00 0.00 0.00
Maximum of Months 218.09 136.76 92.30 268.58 125.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 103.04 42.30 60.74 62.30 252.44 0.00 0.00 0.00
February 151.36 66.43 84.93 101.89 254.84 0.00 0.00 0.00
March 224.83 104.19 120.64 199.40 164.88 0.00 0.00 0.00
April 244.19 104.35 139.83 250.16 113.19 0.00 0.00 0.00
May 285.26 108.44 176.82 335.10 63.07 0.00 0.00 0.00
June 311.67 125.78 185.89 414.02 24.48 0.00 0.00 0.00
July 291.59 109.58 182.02 421.27 6.27 0.00 0.00 0.00
August 322.62 149.16 173.45 460.27 14.88 0.00 0.00 0.00
September 229.53 100.21 129.33 292.10 42.38 0.00 0.00 0.00
October 227.75 110.94 116.80 254.63 100.33 0.00 0.00 0.00
November 107.25 31.33 75.92 73.58 169.67 0.00 0.00 0.00
December 94.74 40.89 53.84 58.57 228.61 0.00 0.00 0.00
                 
Annual Sum or Average 216.61 91.35 125.26 244.62 118.83 0.00 0.00 0.00
Minimum of Months 94.74 31.33 53.84 58.57 6.27 0.00 0.00 0.00
Maximum of Months 322.62 149.16 185.89 460.27 254.84 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.67 0.00 26.67 2.23 139.87 0.00 0.00 0.00
February 36.50 0.00 36.50 4.36 142.77 0.00 0.00 0.00
March 50.63 0.00 50.63 20.12 92.25 0.00 0.00 0.00
April 60.93 0.25 60.68 41.73 60.97 0.00 0.00 0.00
May 81.04 2.97 78.07 81.73 32.37 0.00 0.00 0.00
June 85.49 4.55 80.95 111.30 12.64 0.00 0.00 0.00
July 82.98 3.24 79.74 125.83 3.30 0.00 0.00 0.00
August 73.38 0.98 72.41 110.32 7.63 0.00 0.00 0.00
September 55.25 0.03 55.22 64.42 22.35 0.00 0.00 0.00
October 47.78 0.00 47.78 38.71 53.54 0.00 0.00 0.00
November 33.51 0.00 33.51 11.57 91.93 0.00 0.00 0.00
December 23.27 0.00 23.27 1.56 126.01 0.00 0.00 0.00
                 
Annual Sum or Average 54.89 1.01 53.89 51.47 65.04 0.00 0.00 0.00
Minimum of Months 23.27 0.00 23.27 1.56 3.30 0.00 0.00 0.00
Maximum of Months 85.49 4.55 80.95 125.83 142.77 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 103.04 42.30 60.74 65.34 249.92 0.00 0.00 0.00
February 151.36 66.43 84.93 106.52 251.05 0.00 0.00 0.00
March 224.83 104.19 120.64 204.56 162.46 0.00 0.00 0.00
April 244.19 104.35 139.83 253.44 112.06 0.00 0.00 0.00
May 285.26 108.44 176.82 336.52 62.73 0.00 0.00 0.00
June 311.67 125.78 185.89 414.81 24.30 0.00 0.00 0.00
July 291.59 109.58 182.02 422.21 6.16 0.00 0.00 0.00
August 322.62 149.16 173.45 462.57 14.46 0.00 0.00 0.00
September 229.53 100.21 129.33 295.29 41.34 0.00 0.00 0.00
October 227.75 110.94 116.80 260.27 97.80 0.00 0.00 0.00
November 107.25 31.33 75.92 77.81 166.80 0.00 0.00 0.00
December 94.74 40.89 53.84 62.17 225.40 0.00 0.00 0.00
                 
Annual Sum or Average 216.61 91.35 125.26 247.80 117.13 0.00 0.00 0.00
Minimum of Months 94.74 31.33 53.84 62.17 6.16 0.00 0.00 0.00
Maximum of Months 322.62 149.16 185.89 462.57 251.05 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 110.89 72.77 38.12 107.99 97.62 0.00 0.00 0.00
February 146.75 97.54 49.22 144.36 100.62 0.00 0.00 0.00
March 130.02 71.58 58.45 135.04 73.71 0.00 0.00 0.00
April 103.50 41.87 61.62 112.77 52.83 0.00 0.00 0.00
May 88.89 18.20 70.69 103.50 32.23 0.00 0.00 0.00
June 83.93 12.93 71.00 114.17 14.53 0.00 0.00 0.00
July 87.33 14.74 72.59 132.30 5.44 0.00 0.00 0.00
August 116.97 43.15 73.82 175.56 9.45 0.00 0.00 0.00
September 123.44 61.98 61.46 163.16 23.54 0.00 0.00 0.00
October 174.44 109.39 65.05 211.81 49.24 0.00 0.00 0.00
November 120.79 72.46 48.33 125.74 72.78 0.00 0.00 0.00
December 119.81 85.09 34.71 120.68 89.93 0.00 0.00 0.00
                 
Annual Sum or Average 117.09 58.28 58.81 137.29 51.55 0.00 0.00 0.00
Minimum of Months 83.93 12.93 34.71 103.50 5.44 0.00 0.00 0.00
Maximum of Months 174.44 109.39 73.82 211.81 100.62 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 21.34 0.00 21.34 1.41 116.81 0.00 0.00 0.00
February 29.20 0.00 29.20 3.15 118.05 0.00 0.00 0.00
March 40.51 0.00 40.51 16.20 75.12 0.00 0.00 0.00
April 48.75 0.20 48.55 34.67 49.10 0.00 0.00 0.00
May 64.84 2.37 62.47 68.59 25.23 0.00 0.00 0.00
June 68.40 3.64 64.76 93.94 8.77 0.00 0.00 0.00
July 66.39 2.59 63.80 106.14 1.80 0.00 0.00 0.00
August 58.71 0.78 57.93 94.15 4.89 0.00 0.00 0.00
September 44.21 0.03 44.18 55.13 16.44 0.00 0.00 0.00
October 38.23 0.00 38.23 33.02 41.78 0.00 0.00 0.00
November 26.81 0.00 26.81 8.92 76.61 0.00 0.00 0.00
December 18.62 0.00 18.62 0.98 105.54 0.00 0.00 0.00
                 
Annual Sum or Average 43.92 0.81 43.11 43.30 52.98 0.00 0.00 0.00
Minimum of Months 18.62 0.00 18.62 0.98 1.80 0.00 0.00 0.00
Maximum of Months 68.40 3.64 64.76 106.14 118.05 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 103.76 41.46 62.31 61.21 248.22 0.00 0.00 0.00
February 161.10 75.02 86.08 108.85 245.76 0.00 0.00 0.00
March 206.88 87.92 118.96 177.65 165.46 0.00 0.00 0.00
April 247.65 108.70 138.95 251.93 109.87 0.00 0.00 0.00
May 298.99 119.15 179.84 351.91 61.14 0.00 0.00 0.00
June 277.63 100.56 177.07 369.21 23.36 0.00 0.00 0.00
July 278.48 100.26 178.22 404.93 5.93 0.00 0.00 0.00
August 314.15 141.73 172.42 448.64 13.95 0.00 0.00 0.00
September 235.00 105.87 129.14 298.24 40.71 0.00 0.00 0.00
October 212.30 96.10 116.20 233.72 97.73 0.00 0.00 0.00
November 131.49 50.53 80.96 103.84 165.61 0.00 0.00 0.00
December 102.80 48.51 54.30 66.90 223.02 0.00 0.00 0.00
                 
Annual Sum or Average 214.53 89.75 124.78 240.65 116.02 0.00 0.00 0.00
Minimum of Months 102.80 41.46 54.30 61.21 5.93 0.00 0.00 0.00
Maximum of Months 314.15 141.73 179.84 448.64 248.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 138.64 90.98 47.66 135.21 125.36 0.00 0.00 0.00
February 183.48 121.94 61.53 181.86 124.21 0.00 0.00 0.00
March 162.56 89.49 73.07 169.38 87.74 0.00 0.00 0.00
April 129.39 52.35 77.04 141.36 61.55 0.00 0.00 0.00
May 111.13 22.75 88.38 130.76 34.30 0.00 0.00 0.00
June 104.94 16.17 88.77 144.92 12.92 0.00 0.00 0.00
July 109.19 18.43 90.76 168.85 3.20 0.00 0.00 0.00
August 146.25 53.95 92.30 222.29 7.72 0.00 0.00 0.00
September 154.33 77.49 76.84 206.47 22.33 0.00 0.00 0.00
October 218.09 136.76 81.33 267.95 51.75 0.00 0.00 0.00
November 151.02 90.59 60.43 159.61 85.88 0.00 0.00 0.00
December 149.79 106.39 43.40 152.33 111.77 0.00 0.00 0.00
                 
Annual Sum or Average 146.39 72.86 73.53 173.46 60.37 0.00 0.00 0.00
Minimum of Months 104.94 16.17 43.40 130.76 3.20 0.00 0.00 0.00
Maximum of Months 218.09 136.76 92.30 267.95 125.36 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.67 0.00 26.67 2.05 139.83 0.00 0.00 0.00
February 36.50 0.00 36.50 4.09 142.70 0.00 0.00 0.00
March 50.63 0.00 50.63 19.27 91.41 0.00 0.00 0.00
April 60.93 0.25 60.68 40.50 60.64 0.00 0.00 0.00
May 81.04 2.97 78.07 80.57 32.02 0.00 0.00 0.00
June 85.49 4.55 80.95 111.28 12.23 0.00 0.00 0.00
July 82.98 3.24 79.74 125.71 3.11 0.00 0.00 0.00
August 73.38 0.98 72.41 109.92 7.33 0.00 0.00 0.00
September 55.25 0.03 55.22 63.60 22.06 0.00 0.00 0.00
October 47.78 0.00 47.78 37.73 52.84 0.00 0.00 0.00
November 33.51 0.00 33.51 10.94 92.14 0.00 0.00 0.00
December 23.27 0.00 23.27 1.37 125.95 0.00 0.00 0.00
                 
Annual Sum or Average 54.89 1.01 53.89 50.90 64.75 0.00 0.00 0.00
Minimum of Months 23.27 0.00 23.27 1.37 3.11 0.00 0.00 0.00
Maximum of Months 85.49 4.55 80.95 125.71 142.70 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 103.76 41.46 62.31 63.21 244.71 0.00 0.00 0.00
February 161.10 75.02 86.08 112.21 240.48 0.00 0.00 0.00
March 206.88 87.92 118.96 182.34 162.42 0.00 0.00 0.00
April 247.65 108.70 138.95 254.76 108.63 0.00 0.00 0.00
May 298.99 119.15 179.84 353.06 60.79 0.00 0.00 0.00
June 277.63 100.56 177.07 369.97 23.19 0.00 0.00 0.00
July 278.48 100.26 178.22 405.87 5.82 0.00 0.00 0.00
August 314.15 141.73 172.42 450.82 13.55 0.00 0.00 0.00
September 235.00 105.87 129.14 301.03 39.65 0.00 0.00 0.00
October 212.30 96.10 116.20 238.84 94.87 0.00 0.00 0.00
November 131.49 50.53 80.96 107.51 162.12 0.00 0.00 0.00
December 102.80 48.51 54.30 69.12 218.26 0.00 0.00 0.00
                 
Annual Sum or Average 214.53 89.75 124.78 243.29 113.85 0.00 0.00 0.00
Minimum of Months 102.80 41.46 54.30 63.21 5.82 0.00 0.00 0.00
Maximum of Months 314.15 141.73 179.84 450.82 244.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 33.78 0.00 33.78 1.66 191.93 0.00 0.00 0.00
February 46.23 0.00 46.23 4.13 194.41 0.00 0.00 0.00
March 64.12 0.00 64.12 23.86 123.81 0.00 0.00 0.00
April 77.16 0.32 76.84 52.56 83.08 0.00 0.00 0.00
May 102.63 3.76 98.87 103.70 46.12 0.00 0.00 0.00
June 108.27 5.76 102.51 138.90 22.13 0.00 0.00 0.00
July 105.09 4.10 100.99 154.27 9.15 0.00 0.00 0.00
August 92.93 1.23 91.70 134.37 15.40 0.00 0.00 0.00
September 69.98 0.04 69.94 78.71 36.74 0.00 0.00 0.00
October 60.51 0.00 60.51 46.48 77.86 0.00 0.00 0.00
November 42.44 0.00 42.44 12.51 127.65 0.00 0.00 0.00
December 29.46 0.00 29.46 1.13 173.98 0.00 0.00 0.00
                 
Annual Sum or Average 69.52 1.28 68.24 63.08 91.28 0.00 0.00 0.00
Minimum of Months 29.46 0.00 29.46 1.13 9.15 0.00 0.00 0.00
Maximum of Months 108.27 5.76 102.51 154.27 194.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 12.45 0.00 12.45 0.61 70.75 0.00 0.00 0.00
February 17.04 0.00 17.04 1.52 71.67 0.00 0.00 0.00
March 23.64 0.00 23.64 8.80 45.64 0.00 0.00 0.00
April 28.45 0.12 28.33 19.37 30.63 0.00 0.00 0.00
May 37.83 1.38 36.45 38.23 17.00 0.00 0.00 0.00
June 39.91 2.12 37.79 51.21 8.16 0.00 0.00 0.00
July 38.74 1.51 37.23 56.87 3.37 0.00 0.00 0.00
August 34.26 0.46 33.80 49.53 5.68 0.00 0.00 0.00
September 25.80 0.01 25.78 29.02 13.54 0.00 0.00 0.00
October 22.31 0.00 22.31 17.13 28.70 0.00 0.00 0.00
November 15.65 0.00 15.65 4.61 47.06 0.00 0.00 0.00
December 10.86 0.00 10.86 0.42 64.14 0.00 0.00 0.00
                 
Annual Sum or Average 25.63 0.47 25.16 23.26 33.65 0.00 0.00 0.00
Minimum of Months 10.86 0.00 10.86 0.42 3.37 0.00 0.00 0.00
Maximum of Months 39.91 2.12 37.79 56.87 71.67 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 64.69 42.45 22.24 62.74 62.16 0.00 0.00 0.00
February 85.61 56.90 28.71 84.95 60.98 0.00 0.00 0.00
March 75.85 41.75 34.10 80.01 43.14 0.00 0.00 0.00
April 60.37 24.43 35.95 67.05 30.73 0.00 0.00 0.00
May 51.85 10.62 41.24 61.98 18.15 0.00 0.00 0.00
June 48.96 7.54 41.42 67.14 8.61 0.00 0.00 0.00
July 50.95 8.60 42.35 77.17 3.44 0.00 0.00 0.00
August 68.24 25.17 43.07 102.41 5.84 0.00 0.00 0.00
September 72.01 36.16 35.85 96.20 13.40 0.00 0.00 0.00
October 101.76 63.81 37.95 125.69 27.25 0.00 0.00 0.00
November 70.46 42.27 28.19 74.61 42.68 0.00 0.00 0.00
December 69.89 49.64 20.25 71.00 55.35 0.00 0.00 0.00
                 
Annual Sum or Average 68.31 34.00 34.31 80.93 30.81 0.00 0.00 0.00
Minimum of Months 48.96 7.54 20.25 61.98 3.44 0.00 0.00 0.00
Maximum of Months 101.76 63.81 43.07 125.69 62.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 175.58 115.22 60.36 170.28 168.73 0.00 0.00 0.00
February 232.36 154.43 77.93 230.58 165.53 0.00 0.00 0.00
March 205.87 113.33 92.54 217.15 117.09 0.00 0.00 0.00
April 163.87 66.30 97.57 181.99 83.40 0.00 0.00 0.00
May 140.74 28.82 111.93 168.22 49.26 0.00 0.00 0.00
June 132.90 20.48 112.42 182.24 23.37 0.00 0.00 0.00
July 138.28 23.34 114.94 209.45 9.35 0.00 0.00 0.00
August 185.21 68.32 116.89 277.97 15.84 0.00 0.00 0.00
September 195.45 98.13 97.32 261.11 36.36 0.00 0.00 0.00
October 276.20 173.20 103.00 341.14 73.97 0.00 0.00 0.00
November 191.25 114.73 76.53 202.52 115.85 0.00 0.00 0.00
December 189.69 134.73 54.96 192.72 150.24 0.00 0.00 0.00
                 
Annual Sum or Average 185.40 92.27 93.13 219.66 83.62 0.00 0.00 0.00
Minimum of Months 132.90 20.48 54.96 168.22 9.35 0.00 0.00 0.00
Maximum of Months 276.20 173.20 116.89 341.14 168.73 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 138.64 90.98 47.66 135.13 124.85 0.00 0.00 0.00
February 183.48 121.94 61.53 181.98 123.98 0.00 0.00 0.00
March 162.56 89.49 73.07 169.39 88.19 0.00 0.00 0.00
April 129.39 52.35 77.04 141.55 61.56 0.00 0.00 0.00
May 111.13 22.75 88.38 130.66 34.42 0.00 0.00 0.00
June 104.94 16.17 88.77 143.84 12.98 0.00 0.00 0.00
July 109.19 18.43 90.76 168.01 3.11 0.00 0.00 0.00
August 146.25 53.95 92.30 221.48 7.60 0.00 0.00 0.00
September 154.33 77.49 76.84 205.98 21.99 0.00 0.00 0.00
October 218.09 136.76 81.33 267.37 51.39 0.00 0.00 0.00
November 151.02 90.59 60.43 160.19 84.75 0.00 0.00 0.00
December 149.79 106.39 43.40 152.49 111.03 0.00 0.00 0.00
                 
Annual Sum or Average 146.39 72.86 73.53 173.21 60.13 0.00 0.00 0.00
Minimum of Months 104.94 16.17 43.40 130.66 3.11 0.00 0.00 0.00
Maximum of Months 218.09 136.76 92.30 267.37 124.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 103.04 42.30 60.74 62.21 251.19 0.00 0.00 0.00
February 151.36 66.43 84.93 101.30 254.02 0.00 0.00 0.00
March 224.83 104.19 120.64 198.10 163.84 0.00 0.00 0.00
April 244.19 104.35 139.83 248.54 112.08 0.00 0.00 0.00
May 285.26 108.44 176.82 332.70 62.24 0.00 0.00 0.00
June 311.67 125.78 185.89 411.35 23.65 0.00 0.00 0.00
July 291.59 109.58 182.02 419.15 5.73 0.00 0.00 0.00
August 322.62 149.16 173.45 458.35 14.06 0.00 0.00 0.00
September 229.53 100.21 129.33 290.67 41.08 0.00 0.00 0.00
October 227.75 110.94 116.80 253.36 98.49 0.00 0.00 0.00
November 107.25 31.33 75.92 73.67 167.70 0.00 0.00 0.00
December 94.74 40.89 53.84 58.56 226.86 0.00 0.00 0.00
                 
Annual Sum or Average 216.61 91.35 125.26 243.34 117.65 0.00 0.00 0.00
Minimum of Months 94.74 31.33 53.84 58.56 5.73 0.00 0.00 0.00
Maximum of Months 322.62 149.16 185.89 458.35 254.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.67 0.00 26.67 2.31 139.19 0.00 0.00 0.00
February 36.50 0.00 36.50 4.45 142.39 0.00 0.00 0.00
March 50.63 0.00 50.63 20.21 91.74 0.00 0.00 0.00
April 60.93 0.25 60.68 41.65 60.37 0.00 0.00 0.00
May 81.04 2.97 78.07 80.97 32.00 0.00 0.00 0.00
June 85.49 4.55 80.95 110.59 12.24 0.00 0.00 0.00
July 82.98 3.24 79.74 125.25 3.05 0.00 0.00 0.00
August 73.38 0.98 72.41 110.03 7.21 0.00 0.00 0.00
September 55.25 0.03 55.22 64.27 21.64 0.00 0.00 0.00
October 47.78 0.00 47.78 39.04 52.37 0.00 0.00 0.00
November 33.51 0.00 33.51 11.91 90.66 0.00 0.00 0.00
December 23.27 0.00 23.27 1.67 124.92 0.00 0.00 0.00
                 
Annual Sum or Average 54.89 1.01 53.89 51.34 64.38 0.00 0.00 0.00
Minimum of Months 23.27 0.00 23.27 1.67 3.05 0.00 0.00 0.00
Maximum of Months 85.49 4.55 80.95 125.25 142.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 103.04 42.30 60.74 65.23 248.81 0.00 0.00 0.00
February 151.36 66.43 84.93 106.03 250.37 0.00 0.00 0.00
March 224.83 104.19 120.64 203.65 161.31 0.00 0.00 0.00
April 244.19 104.35 139.83 252.08 110.87 0.00 0.00 0.00
May 285.26 108.44 176.82 334.15 61.88 0.00 0.00 0.00
June 311.67 125.78 185.89 412.15 23.48 0.00 0.00 0.00
July 291.59 109.58 182.02 420.13 5.62 0.00 0.00 0.00
August 322.62 149.16 173.45 460.76 13.62 0.00 0.00 0.00
September 229.53 100.21 129.33 294.09 39.92 0.00 0.00 0.00
October 227.75 110.94 116.80 259.74 95.54 0.00 0.00 0.00
November 107.25 31.33 75.92 78.22 164.71 0.00 0.00 0.00
December 94.74 40.89 53.84 62.31 223.77 0.00 0.00 0.00
                 
Annual Sum or Average 216.61 91.35 125.26 246.71 115.91 0.00 0.00 0.00
Minimum of Months 94.74 31.33 53.84 62.31 5.62 0.00 0.00 0.00
Maximum of Months 322.62 149.16 185.89 460.76 250.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 203.33 133.43 69.90 192.02 190.09 0.00 0.00 0.00
February 269.09 178.84 90.24 258.94 189.12 0.00 0.00 0.00
March 238.41 131.24 107.17 243.99 132.95 0.00 0.00 0.00
April 189.77 76.78 112.99 205.69 91.38 0.00 0.00 0.00
May 162.99 33.37 129.62 192.84 49.74 0.00 0.00 0.00
June 153.90 23.71 130.19 214.50 17.71 0.00 0.00 0.00
July 160.14 27.03 133.11 250.38 3.82 0.00 0.00 0.00
August 214.49 79.12 135.36 328.05 10.27 0.00 0.00 0.00
September 226.34 113.64 112.70 301.81 32.18 0.00 0.00 0.00
October 319.86 200.58 119.28 388.68 77.40 0.00 0.00 0.00
November 221.48 132.86 88.62 228.58 130.87 0.00 0.00 0.00
December 219.68 156.02 63.65 216.95 170.16 0.00 0.00 0.00
                 
Annual Sum or Average 214.70 106.85 107.84 251.97 90.76 0.00 0.00 0.00
Minimum of Months 153.90 23.71 63.65 192.02 3.82 0.00 0.00 0.00
Maximum of Months 319.86 200.58 135.36 388.68 190.09 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 186.70 0.00 186.70 4.17 1177.81 0.00 0.00 0.00
February 255.50 0.00 255.50 14.31 1187.26 0.00 0.00 0.00
March 354.39 0.01 354.39 103.09 790.65 0.00 0.00 0.00
April 426.48 1.76 424.73 247.09 535.30 0.00 0.00 0.00
May 567.24 20.76 546.48 516.90 292.65 0.00 0.00 0.00
June 598.43 31.83 566.60 732.39 138.24 0.00 0.00 0.00
July 580.84 22.67 558.17 828.77 58.71 0.00 0.00 0.00
August 513.65 6.82 506.83 726.66 89.70 0.00 0.00 0.00
September 386.77 0.22 386.54 411.55 226.48 0.00 0.00 0.00
October 334.44 0.00 334.44 235.00 468.51 0.00 0.00 0.00
November 234.58 0.00 234.58 52.01 811.03 0.00 0.00 0.00
December 162.86 0.00 162.86 2.97 1087.28 0.00 0.00 0.00
                 
Annual Sum or Average 384.23 7.05 377.19 325.03 568.49 0.00 0.00 0.00
Minimum of Months 162.86 0.00 162.86 2.97 58.71 0.00 0.00 0.00
Maximum of Months 598.43 31.83 566.60 828.77 1187.26 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 186.70 0.00 186.70 2.83 1212.98 0.00 0.00 0.00
February 255.50 0.00 255.50 12.06 1220.76 0.00 0.00 0.00
March 354.39 0.01 354.39 95.36 813.89 0.00 0.00 0.00
April 426.48 1.76 424.73 236.39 551.55 0.00 0.00 0.00
May 567.24 20.76 546.48 505.08 300.96 0.00 0.00 0.00
June 598.43 31.83 566.60 723.60 143.67 0.00 0.00 0.00
July 580.84 22.67 558.17 821.04 62.77 0.00 0.00 0.00
August 513.65 6.82 506.83 718.70 93.95 0.00 0.00 0.00
September 386.77 0.22 386.54 403.51 234.72 0.00 0.00 0.00
October 334.44 0.00 334.44 226.51 481.41 0.00 0.00 0.00
November 234.58 0.00 234.58 47.12 837.28 0.00 0.00 0.00
December 162.86 0.00 162.86 2.17 1120.23 0.00 0.00 0.00
                 
Annual Sum or Average 384.23 7.05 377.19 318.30 585.95 0.00 0.00 0.00
Minimum of Months 162.86 0.00 162.86 2.17 62.77 0.00 0.00 0.00
Maximum of Months 598.43 31.83 566.60 821.04 1220.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.67 0.00 26.67 2.37 150.22 0.00 0.00 0.00
February 36.50 0.00 36.50 4.37 152.27 0.00 0.00 0.00
March 50.63 0.00 50.63 21.60 99.90 0.00 0.00 0.00
April 60.93 0.25 60.68 49.08 68.20 0.00 0.00 0.00
May 81.04 2.97 78.07 96.20 38.78 0.00 0.00 0.00
June 85.49 4.55 80.95 131.08 18.64 0.00 0.00 0.00
July 82.98 3.24 79.74 147.45 8.36 0.00 0.00 0.00
August 73.38 0.98 72.41 130.89 12.05 0.00 0.00 0.00
September 55.25 0.03 55.22 80.32 27.22 0.00 0.00 0.00
October 47.78 0.00 47.78 47.20 56.80 0.00 0.00 0.00
November 33.51 0.00 33.51 12.85 101.01 0.00 0.00 0.00
December 23.27 0.00 23.27 1.66 136.25 0.00 0.00 0.00
                 
Annual Sum or Average 54.89 1.01 53.89 60.80 72.02 0.00 0.00 0.00
Minimum of Months 23.27 0.00 23.27 1.66 8.36 0.00 0.00 0.00
Maximum of Months 85.49 4.55 80.95 147.45 152.27 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 207.51 82.91 124.60 129.51 527.42 0.00 0.00 0.00
February 322.18 150.03 172.15 228.64 513.88 0.00 0.00 0.00
March 413.73 175.83 237.90 377.01 358.59 0.00 0.00 0.00
April 495.27 217.38 277.89 543.65 246.67 0.00 0.00 0.00
May 597.93 238.28 359.65 762.17 145.96 0.00 0.00 0.00
June 555.22 201.11 354.12 812.50 70.06 0.00 0.00 0.00
July 556.92 200.50 356.42 891.77 31.51 0.00 0.00 0.00
August 628.26 283.45 344.82 979.28 45.09 0.00 0.00 0.00
September 469.97 211.72 258.25 665.51 100.00 0.00 0.00 0.00
October 424.58 192.19 232.39 518.07 206.24 0.00 0.00 0.00
November 262.97 101.05 161.91 226.22 354.60 0.00 0.00 0.00
December 205.59 97.01 108.58 142.51 472.43 0.00 0.00 0.00
                 
Annual Sum or Average 429.02 179.49 249.53 525.06 254.61 0.00 0.00 0.00
Minimum of Months 205.59 82.91 108.58 129.51 31.51 0.00 0.00 0.00
Maximum of Months 628.26 283.45 359.65 979.28 527.42 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 138.64 90.98 47.66 137.96 133.58 0.00 0.00 0.00
February 183.48 121.94 61.53 186.30 130.52 0.00 0.00 0.00
March 162.56 89.49 73.07 176.57 95.17 0.00 0.00 0.00
April 129.39 52.35 77.04 151.88 68.45 0.00 0.00 0.00
May 111.13 22.75 88.38 146.66 40.50 0.00 0.00 0.00
June 104.94 16.17 88.77 164.41 19.42 0.00 0.00 0.00
July 109.19 18.43 90.76 190.46 8.54 0.00 0.00 0.00
August 146.25 53.95 92.30 244.37 12.16 0.00 0.00 0.00
September 154.33 77.49 76.84 225.10 26.99 0.00 0.00 0.00
October 218.09 136.76 81.33 282.50 55.31 0.00 0.00 0.00
November 151.02 90.59 60.43 165.53 92.44 0.00 0.00 0.00
December 149.79 106.39 43.40 155.89 119.26 0.00 0.00 0.00
                 
Annual Sum or Average 146.39 72.86 73.53 185.73 66.50 0.00 0.00 0.00
Minimum of Months 104.94 16.17 43.40 137.96 8.54 0.00 0.00 0.00
Maximum of Months 218.09 136.76 92.30 282.50 133.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 33.78 0.00 33.78 1.28 195.51 0.00 0.00 0.00
February 46.23 0.00 46.23 3.46 198.32 0.00 0.00 0.00
March 64.12 0.00 64.12 21.64 126.43 0.00 0.00 0.00
April 77.16 0.32 76.84 49.66 84.42 0.00 0.00 0.00
May 102.63 3.76 98.87 99.50 47.33 0.00 0.00 0.00
June 108.27 5.76 102.51 134.19 23.58 0.00 0.00 0.00
July 105.09 4.10 100.99 149.47 10.60 0.00 0.00 0.00
August 92.93 1.23 91.70 130.45 16.27 0.00 0.00 0.00
September 69.98 0.04 69.94 75.73 37.73 0.00 0.00 0.00
October 60.51 0.00 60.51 44.53 77.31 0.00 0.00 0.00
November 42.44 0.00 42.44 11.47 129.59 0.00 0.00 0.00
December 29.46 0.00 29.46 0.87 177.74 0.00 0.00 0.00
                 
Annual Sum or Average 69.52 1.28 68.24 60.57 93.15 0.00 0.00 0.00
Minimum of Months 29.46 0.00 29.46 0.87 10.60 0.00 0.00 0.00
Maximum of Months 108.27 5.76 102.51 149.47 198.32 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.22 0.00 30.22 1.14 174.92 0.00 0.00 0.00
February 41.36 0.00 41.36 3.10 177.44 0.00 0.00 0.00
March 57.37 0.00 57.37 19.36 113.12 0.00 0.00 0.00
April 69.04 0.28 68.75 44.43 75.53 0.00 0.00 0.00
May 91.82 3.36 88.46 89.03 42.35 0.00 0.00 0.00
June 96.87 5.15 91.72 120.06 21.10 0.00 0.00 0.00
July 94.02 3.67 90.35 133.73 9.49 0.00 0.00 0.00
August 83.15 1.10 82.04 116.71 14.56 0.00 0.00 0.00
September 62.61 0.04 62.57 67.76 33.76 0.00 0.00 0.00
October 54.14 0.00 54.14 39.84 69.17 0.00 0.00 0.00
November 37.97 0.00 37.97 10.26 115.94 0.00 0.00 0.00
December 26.36 0.00 26.36 0.78 159.00 0.00 0.00 0.00
                 
Annual Sum or Average 62.20 1.14 61.06 54.19 83.34 0.00 0.00 0.00
Minimum of Months 26.36 0.00 26.36 0.78 9.49 0.00 0.00 0.00
Maximum of Months 96.87 5.15 91.72 133.73 177.44 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 517.59 339.65 177.94 494.88 505.10 0.00 0.00 0.00
February 684.98 455.25 229.72 670.33 494.92 0.00 0.00 0.00
March 606.89 334.08 272.80 628.94 352.21 0.00 0.00 0.00
April 483.07 195.44 287.63 524.83 250.61 0.00 0.00 0.00
May 414.90 84.94 329.95 482.24 149.65 0.00 0.00 0.00
June 391.77 60.36 331.40 521.96 73.80 0.00 0.00 0.00
July 407.63 68.80 338.83 601.76 31.98 0.00 0.00 0.00
August 545.99 201.41 344.58 805.22 49.42 0.00 0.00 0.00
September 576.16 289.28 286.88 758.01 110.31 0.00 0.00 0.00
October 814.21 510.58 303.63 995.35 216.76 0.00 0.00 0.00
November 563.79 338.20 225.59 589.40 345.83 0.00 0.00 0.00
December 559.20 397.17 162.03 560.61 450.39 0.00 0.00 0.00
                 
Annual Sum or Average 546.52 272.00 274.52 636.26 251.22 0.00 0.00 0.00
Minimum of Months 391.77 60.36 162.03 482.24 31.98 0.00 0.00 0.00
Maximum of Months 814.21 510.58 344.58 995.35 505.10 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.187811E+10 0.123244E+10 0.645669E+09 0.182023E+10 0.168163E+10
February 0.224496E+10 0.149206E+10 0.752897E+09 0.221617E+10 0.150288E+10
March 0.220215E+10 0.121226E+10 0.989890E+09 0.230088E+10 0.118290E+10
April 0.169631E+10 0.686285E+09 0.101002E+10 0.186783E+10 0.806577E+09
May 0.150549E+10 0.308226E+09 0.119726E+10 0.179658E+10 0.478379E+09
June 0.137569E+10 0.211965E+09 0.116373E+10 0.186916E+10 0.222137E+09
July 0.147913E+10 0.249647E+09 0.122948E+10 0.219781E+10 98823119.18
August 0.198115E+10 0.730828E+09 0.125032E+10 0.290961E+10 0.174012E+09
September 0.202321E+10 0.101583E+10 0.100738E+10 0.266721E+10 0.355119E+09
October 0.295444E+10 0.185269E+10 0.110176E+10 0.359887E+10 0.755806E+09
November 0.197976E+10 0.118761E+10 0.792159E+09 0.207865E+10 0.113109E+10
December 0.202909E+10 0.144117E+10 0.587926E+09 0.204387E+10 0.151246E+10
           
Annual Sum or Average 0.233495E+11 0.116210E+11 0.117285E+11 0.273669E+11 0.990181E+10
Minimum of Months 0.137569E+10 0.211965E+09 0.587926E+09 0.179658E+10 98823119.18
Maximum of Months 0.295444E+10 0.185269E+10 0.125032E+10 0.359887E+10 0.168163E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.528864E+10 0.347048E+10 0.181816E+10 0.506423E+10 0.488166E+10
February 0.632166E+10 0.420155E+10 0.212011E+10 0.616332E+10 0.437443E+10
March 0.620110E+10 0.341363E+10 0.278747E+10 0.639130E+10 0.354960E+10
April 0.477669E+10 0.193253E+10 0.284415E+10 0.516424E+10 0.247010E+10
May 0.423935E+10 0.867945E+09 0.337140E+10 0.492384E+10 0.153335E+10
June 0.387386E+10 0.596881E+09 0.327698E+10 0.516495E+10 0.735757E+09
July 0.416513E+10 0.702990E+09 0.346214E+10 0.610973E+10 0.343841E+09
August 0.557879E+10 0.205796E+10 0.352082E+10 0.812851E+10 0.547074E+09
September 0.569723E+10 0.286050E+10 0.283673E+10 0.742407E+10 0.114749E+10
October 0.831952E+10 0.521704E+10 0.310247E+10 0.100345E+11 0.233615E+10
November 0.557489E+10 0.334422E+10 0.223067E+10 0.575928E+10 0.339396E+10
December 0.571380E+10 0.405823E+10 0.165556E+10 0.568600E+10 0.444087E+10
           
Annual Sum or Average 0.657506E+11 0.327240E+11 0.330267E+11 0.760140E+11 0.297543E+11
Minimum of Months 0.387386E+10 0.596881E+09 0.165556E+10 0.492384E+10 0.343841E+09
Maximum of Months 0.831952E+10 0.521704E+10 0.352082E+10 0.100345E+11 0.488166E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.687025E+10 0.450835E+10 0.236190E+10 0.668550E+10 0.666308E+10
February 0.821220E+10 0.545806E+10 0.275414E+10 0.815862E+10 0.592547E+10
March 0.805558E+10 0.443450E+10 0.362108E+10 0.845812E+10 0.483547E+10
April 0.620519E+10 0.251047E+10 0.369472E+10 0.682635E+10 0.339148E+10
May 0.550715E+10 0.112751E+10 0.437965E+10 0.650006E+10 0.211276E+10
June 0.503236E+10 0.775382E+09 0.425698E+10 0.684172E+10 0.991455E+09
July 0.541074E+10 0.913224E+09 0.449752E+10 0.811838E+10 0.451539E+09
August 0.724716E+10 0.267341E+10 0.457375E+10 0.107954E+11 0.704559E+09
September 0.740102E+10 0.371595E+10 0.368507E+10 0.981876E+10 0.153466E+10
October 0.108075E+11 0.677724E+10 0.403029E+10 0.132772E+11 0.310787E+10
November 0.724209E+10 0.434433E+10 0.289776E+10 0.759371E+10 0.464802E+10
December 0.742255E+10 0.527188E+10 0.215067E+10 0.750037E+10 0.607307E+10
           
Annual Sum or Average 0.854138E+11 0.425103E+11 0.429035E+11 0.100574E+12 0.404394E+11
Minimum of Months 0.503236E+10 0.775382E+09 0.215067E+10 0.650006E+10 0.451539E+09
Maximum of Months 0.108075E+11 0.677724E+10 0.457375E+10 0.132772E+11 0.666308E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.371336E+09 0.243675E+09 0.127661E+09 0.362905E+09 0.336283E+09
February 0.443868E+09 0.295007E+09 0.148862E+09 0.441692E+09 0.301282E+09
March 0.435404E+09 0.239684E+09 0.195720E+09 0.456148E+09 0.237327E+09
April 0.335391E+09 0.135690E+09 0.199700E+09 0.369382E+09 0.160797E+09
May 0.297663E+09 60941606.69 0.236721E+09 0.353151E+09 93146835.19
June 0.272000E+09 41909203.44 0.230091E+09 0.375688E+09 34715035.74
July 0.292452E+09 49359538.74 0.243092E+09 0.452503E+09 9105150.51
August 0.391710E+09 0.144497E+09 0.247212E+09 0.596152E+09 21503058.71
September 0.400025E+09 0.200846E+09 0.199179E+09 0.536676E+09 58724013.72
October 0.584146E+09 0.366308E+09 0.217837E+09 0.719366E+09 0.140070E+09
November 0.391434E+09 0.234810E+09 0.156624E+09 0.415901E+09 0.222324E+09
December 0.401187E+09 0.284944E+09 0.116244E+09 0.409137E+09 0.299756E+09
           
Annual Sum or Average 0.461662E+10 0.229767E+10 0.231894E+10 0.548870E+10 0.191503E+10
Minimum of Months 0.272000E+09 41909203.44 0.116244E+09 0.353151E+09 9105150.51
Maximum of Months 0.584146E+09 0.366308E+09 0.247212E+09 0.719366E+09 0.336283E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.275986E+09 0.113300E+09 0.162686E+09 0.166864E+09 0.676130E+09
February 0.366176E+09 0.160704E+09 0.205472E+09 0.246503E+09 0.616511E+09
March 0.602184E+09 0.279066E+09 0.323119E+09 0.534067E+09 0.441625E+09
April 0.632930E+09 0.270479E+09 0.362451E+09 0.648406E+09 0.293379E+09
May 0.764046E+09 0.290443E+09 0.473603E+09 0.897535E+09 0.168918E+09
June 0.807850E+09 0.326026E+09 0.481824E+09 0.107315E+10 63439759.33
July 0.781005E+09 0.293491E+09 0.487514E+09 0.112832E+10 16796150.21
August 0.864094E+09 0.399519E+09 0.464575E+09 0.123280E+10 39857094.96
September 0.594954E+09 0.259739E+09 0.335215E+09 0.757111E+09 0.109861E+09
October 0.610005E+09 0.297155E+09 0.312850E+09 0.682002E+09 0.268725E+09
November 0.278002E+09 81216406.75 0.196786E+09 0.190713E+09 0.439787E+09
December 0.253740E+09 0.109532E+09 0.144208E+09 0.156881E+09 0.612315E+09
           
Annual Sum or Average 0.683097E+10 0.288067E+10 0.395030E+10 0.771434E+10 0.374735E+10
Minimum of Months 0.253740E+09 81216406.75 0.144208E+09 0.156881E+09 16796150.21
Maximum of Months 0.864094E+09 0.399519E+09 0.487514E+09 0.123280E+10 0.676130E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 71441120.58 0.00 71441120.58 5967491.99 0.374641E+09
February 88303223.66 0.00 88303223.66 10557105.63 0.345392E+09
March 0.135606E+09 2824.51 0.135604E+09 53881037.94 0.247082E+09
April 0.157926E+09 650731.43 0.157276E+09 0.108157E+09 0.158028E+09
May 0.217051E+09 7943454.65 0.209108E+09 0.218912E+09 86699783.75
June 0.221597E+09 11786401.62 0.209811E+09 0.288495E+09 32759229.80
July 0.222253E+09 8673946.39 0.213579E+09 0.337034E+09 8836045.39
August 0.196546E+09 2611506.30 0.193935E+09 0.295487E+09 20438986.45
September 0.143220E+09 83260.91 0.143137E+09 0.166977E+09 57932554.47
October 0.127973E+09 0.00 0.127973E+09 0.103669E+09 0.143412E+09
November 86865075.47 0.00 86865075.47 29985856.48 0.238270E+09
December 62315669.45 0.00 62315669.45 4165019.77 0.337513E+09
           
Annual Sum or Average 0.173110E+10 31752125.80 0.169935E+10 0.162329E+10 0.205101E+10
Minimum of Months 62315669.45 0.00 62315669.45 4165019.77 8836045.39
Maximum of Months 0.222253E+09 11786401.62 0.213579E+09 0.337034E+09 0.374641E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.275986E+09 0.113300E+09 0.162686E+09 0.175000E+09 0.669393E+09
February 0.366176E+09 0.160704E+09 0.205472E+09 0.257684E+09 0.607331E+09
March 0.602184E+09 0.279066E+09 0.323119E+09 0.547886E+09 0.435129E+09
April 0.632930E+09 0.270479E+09 0.362451E+09 0.656923E+09 0.290462E+09
May 0.764046E+09 0.290443E+09 0.473603E+09 0.901330E+09 0.168004E+09
June 0.807850E+09 0.326026E+09 0.481824E+09 0.107519E+10 62976002.70
July 0.781005E+09 0.293491E+09 0.487514E+09 0.113085E+10 16494007.00
August 0.864094E+09 0.399519E+09 0.464575E+09 0.123894E+10 38742029.36
September 0.594954E+09 0.259739E+09 0.335215E+09 0.765385E+09 0.107159E+09
October 0.610005E+09 0.297155E+09 0.312850E+09 0.697118E+09 0.261946E+09
November 0.278002E+09 81216406.75 0.196786E+09 0.201675E+09 0.432343E+09
December 0.253740E+09 0.109532E+09 0.144208E+09 0.166509E+09 0.603722E+09
           
Annual Sum or Average 0.683097E+10 0.288067E+10 0.395030E+10 0.781450E+10 0.369370E+10
Minimum of Months 0.253740E+09 81216406.75 0.144208E+09 0.166509E+09 16494007.00
Maximum of Months 0.864094E+09 0.399519E+09 0.487514E+09 0.123894E+10 0.669393E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.297010E+09 0.194901E+09 0.102108E+09 0.289244E+09 0.261477E+09
February 0.355024E+09 0.235958E+09 0.119066E+09 0.349229E+09 0.243422E+09
March 0.348254E+09 0.191709E+09 0.156545E+09 0.361686E+09 0.197435E+09
April 0.268259E+09 0.108531E+09 0.159729E+09 0.292304E+09 0.136938E+09
May 0.238083E+09 48743591.57 0.189339E+09 0.277222E+09 86334040.19
June 0.217557E+09 33520696.39 0.184036E+09 0.295916E+09 37667383.94
July 0.233915E+09 39479779.53 0.194435E+09 0.354339E+09 14581042.49
August 0.313305E+09 0.115575E+09 0.197731E+09 0.470218E+09 25307151.50
September 0.319956E+09 0.160645E+09 0.159311E+09 0.422922E+09 61007818.16
October 0.467223E+09 0.292988E+09 0.174235E+09 0.567322E+09 0.131883E+09
November 0.313085E+09 0.187811E+09 0.125275E+09 0.325928E+09 0.188638E+09
December 0.320886E+09 0.227910E+09 92976446.14 0.323239E+09 0.240881E+09
           
Annual Sum or Average 0.369256E+10 0.183777E+10 0.185479E+10 0.432957E+10 0.162557E+10
Minimum of Months 0.217557E+09 33520696.39 92976446.14 0.277222E+09 14581042.49
Maximum of Months 0.467223E+09 0.292988E+09 0.197731E+09 0.567322E+09 0.261477E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 57160472.40 0.00 57160472.40 3788975.13 0.312862E+09
February 70651943.00 0.00 70651943.00 7619990.17 0.285580E+09
March 0.108500E+09 2259.91 0.108497E+09 43383682.13 0.201212E+09
April 0.126358E+09 520654.15 0.125837E+09 89873410.25 0.127255E+09
May 0.173664E+09 6355606.08 0.167308E+09 0.183712E+09 67581883.40
June 0.177301E+09 9430371.18 0.167871E+09 0.243495E+09 22738375.97
July 0.177826E+09 6940076.94 0.170886E+09 0.284291E+09 4822951.90
August 0.157258E+09 2089481.97 0.155168E+09 0.252164E+09 13099673.25
September 0.114591E+09 66617.56 0.114525E+09 0.142890E+09 42613322.58
October 0.102392E+09 0.00 0.102392E+09 88452923.59 0.111895E+09
November 69501271.94 0.00 69501271.94 23112353.82 0.198561E+09
December 49859143.80 0.00 49859143.80 2616352.80 0.282667E+09
           
Annual Sum or Average 0.138506E+10 25405067.78 0.135966E+10 0.136540E+10 0.167089E+10
Minimum of Months 49859143.80 0.00 49859143.80 2616352.80 4822951.90
Maximum of Months 0.177826E+09 9430371.18 0.170886E+09 0.284291E+09 0.312862E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.277917E+09 0.111036E+09 0.166880E+09 0.163939E+09 0.664824E+09
February 0.389732E+09 0.181489E+09 0.208243E+09 0.263328E+09 0.594547E+09
March 0.554101E+09 0.235489E+09 0.318612E+09 0.475812E+09 0.443169E+09
April 0.641909E+09 0.281741E+09 0.360168E+09 0.653005E+09 0.284791E+09
May 0.800805E+09 0.319132E+09 0.481673E+09 0.942568E+09 0.163751E+09
June 0.719622E+09 0.260655E+09 0.458966E+09 0.956996E+09 60536965.87
July 0.745874E+09 0.268526E+09 0.477348E+09 0.108455E+10 15871570.64
August 0.841430E+09 0.379618E+09 0.461812E+09 0.120163E+10 37373538.15
September 0.609123E+09 0.274405E+09 0.334718E+09 0.773042E+09 0.105526E+09
October 0.568633E+09 0.257394E+09 0.311239E+09 0.625989E+09 0.261756E+09
November 0.340829E+09 0.130973E+09 0.209856E+09 0.269161E+09 0.429258E+09
December 0.275346E+09 0.129921E+09 0.145425E+09 0.179176E+09 0.597342E+09
           
Annual Sum or Average 0.676532E+10 0.283038E+10 0.393494E+10 0.758920E+10 0.365875E+10
Minimum of Months 0.275346E+09 0.111036E+09 0.145425E+09 0.163939E+09 15871570.64
Maximum of Months 0.841430E+09 0.379618E+09 0.481673E+09 0.120163E+10 0.664824E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.371336E+09 0.243675E+09 0.127661E+09 0.362157E+09 0.335764E+09
February 0.443868E+09 0.295007E+09 0.148862E+09 0.439956E+09 0.300484E+09
March 0.435404E+09 0.239684E+09 0.195720E+09 0.453674E+09 0.235012E+09
April 0.335391E+09 0.135690E+09 0.199700E+09 0.366410E+09 0.159528E+09
May 0.297663E+09 60941606.69 0.236721E+09 0.350238E+09 91863285.24
June 0.272000E+09 41909203.44 0.230091E+09 0.375633E+09 33494264.38
July 0.292452E+09 49359538.74 0.243092E+09 0.452256E+09 8570053.80
August 0.391710E+09 0.144497E+09 0.247212E+09 0.595391E+09 20678023.05
September 0.400025E+09 0.200846E+09 0.199179E+09 0.535165E+09 57871516.29
October 0.584146E+09 0.366308E+09 0.217837E+09 0.717682E+09 0.138612E+09
November 0.391434E+09 0.234810E+09 0.156624E+09 0.413702E+09 0.222601E+09
December 0.401187E+09 0.284944E+09 0.116244E+09 0.408007E+09 0.299365E+09
           
Annual Sum or Average 0.461662E+10 0.229767E+10 0.231894E+10 0.547027E+10 0.190385E+10
Minimum of Months 0.272000E+09 41909203.44 0.116244E+09 0.350238E+09 8570053.80
Maximum of Months 0.584146E+09 0.366308E+09 0.247212E+09 0.717682E+09 0.335764E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 71441120.58 0.00 71441120.58 5490725.15 0.374515E+09
February 88303223.66 0.00 88303223.66 9891443.37 0.345213E+09
March 0.135606E+09 2824.51 0.135604E+09 51605040.04 0.244837E+09
April 0.157926E+09 650731.43 0.157276E+09 0.104980E+09 0.157185E+09
May 0.217051E+09 7943454.65 0.209108E+09 0.215809E+09 85749098.29
June 0.221597E+09 11786401.62 0.209811E+09 0.288427E+09 31699766.35
July 0.222253E+09 8673946.39 0.213579E+09 0.336705E+09 8337590.82
August 0.196546E+09 2611506.30 0.193935E+09 0.294398E+09 19642592.02
September 0.143220E+09 83260.91 0.143137E+09 0.164852E+09 57186569.91
October 0.127973E+09 0.00 0.127973E+09 0.101051E+09 0.141529E+09
November 86865075.47 0.00 86865075.47 28368042.41 0.238819E+09
December 62315669.45 0.00 62315669.45 3671556.39 0.337336E+09
           
Annual Sum or Average 0.173110E+10 31752125.80 0.169935E+10 0.160525E+10 0.204205E+10
Minimum of Months 62315669.45 0.00 62315669.45 3671556.39 8337590.82
Maximum of Months 0.222253E+09 11786401.62 0.213579E+09 0.336705E+09 0.374515E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.277917E+09 0.111036E+09 0.166880E+09 0.169308E+09 0.655425E+09
February 0.389732E+09 0.181489E+09 0.208243E+09 0.271464E+09 0.581776E+09
March 0.554101E+09 0.235489E+09 0.318612E+09 0.488366E+09 0.435031E+09
April 0.641909E+09 0.281741E+09 0.360168E+09 0.660348E+09 0.281565E+09
May 0.800805E+09 0.319132E+09 0.481673E+09 0.945641E+09 0.162833E+09
June 0.719622E+09 0.260655E+09 0.458966E+09 0.958957E+09 60110630.48
July 0.745874E+09 0.268526E+09 0.477348E+09 0.108708E+10 15601648.25
August 0.841430E+09 0.379618E+09 0.461812E+09 0.120747E+10 36284108.36
September 0.609123E+09 0.274405E+09 0.334718E+09 0.780257E+09 0.102765E+09
October 0.568633E+09 0.257394E+09 0.311239E+09 0.639706E+09 0.254108E+09
November 0.340829E+09 0.130973E+09 0.209856E+09 0.278678E+09 0.420211E+09
December 0.275346E+09 0.129921E+09 0.145425E+09 0.185122E+09 0.584597E+09
           
Annual Sum or Average 0.676532E+10 0.283038E+10 0.393494E+10 0.767240E+10 0.359031E+10
Minimum of Months 0.275346E+09 0.111036E+09 0.145425E+09 0.169308E+09 15601648.25
Maximum of Months 0.841430E+09 0.379618E+09 0.481673E+09 0.120747E+10 0.655425E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 90475671.53 0.00 90475671.53 4454844.01 0.514057E+09
February 0.111830E+09 0.00 0.111830E+09 9981855.12 0.470320E+09
March 0.171737E+09 3577.06 0.171733E+09 63903544.73 0.331618E+09
April 0.200004E+09 824110.29 0.199180E+09 0.136228E+09 0.215336E+09
May 0.274881E+09 10059884.11 0.264822E+09 0.277762E+09 0.123521E+09
June 0.280639E+09 14926733.97 0.265712E+09 0.360034E+09 57354825.06
July 0.281470E+09 10985005.81 0.270485E+09 0.413187E+09 24514411.72
August 0.248914E+09 3307307.95 0.245606E+09 0.359897E+09 41243447.20
September 0.181379E+09 105444.69 0.181274E+09 0.204016E+09 95236599.99
October 0.162070E+09 0.00 0.162070E+09 0.124494E+09 0.208539E+09
November 0.110009E+09 0.00 0.110009E+09 32413948.66 0.330879E+09
December 78918863.46 0.00 78918863.46 3038009.83 0.465989E+09
           
Annual Sum or Average 0.219233E+10 40212063.88 0.215212E+10 0.198941E+10 0.287861E+10
Minimum of Months 78918863.46 0.00 78918863.46 3038009.83 24514411.72
Maximum of Months 0.281470E+09 14926733.97 0.270485E+09 0.413187E+09 0.514057E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 33353078.83 0.00 33353078.83 1642239.96 0.189503E+09
February 41225338.51 0.00 41225338.51 3679725.11 0.173379E+09
March 63309370.74 1318.65 63308052.09 23557492.62 0.122248E+09
April 73729728.02 303801.18 73425926.85 50219387.14 79381894.44
May 0.101333E+09 3708489.83 97624177.01 0.102395E+09 45534939.84
June 0.103455E+09 5502612.21 97952429.60 0.132724E+09 21143363.39
July 0.103761E+09 4049527.99 99711821.83 0.152318E+09 9037027.22
August 91759824.79 1219210.65 90540614.14 0.132673E+09 15204042.40
September 66863956.86 38871.28 66825085.58 75208592.04 35108154.19
October 59745607.08 0.00 59745607.08 45893512.25 76876089.20
November 40553923.09 0.00 40553923.09 11949123.63 0.121976E+09
December 29092760.85 0.00 29092760.85 1119936.22 0.171783E+09
           
Annual Sum or Average 0.808183E+09 14823831.80 0.793359E+09 0.733379E+09 0.106117E+10
Minimum of Months 29092760.85 0.00 29092760.85 1119936.22 9037027.22
Maximum of Months 0.103761E+09 5502612.21 99711821.83 0.152318E+09 0.189503E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.173264E+09 0.113698E+09 59565921.67 0.168031E+09 0.166502E+09
February 0.207107E+09 0.137649E+09 69458271.60 0.205522E+09 0.147535E+09
March 0.203158E+09 0.111836E+09 91322098.46 0.214286E+09 0.115541E+09
April 0.156492E+09 63312522.45 93179403.01 0.173798E+09 79641905.94
May 0.138888E+09 28435108.11 0.110453E+09 0.166002E+09 48606504.30
June 0.126914E+09 19554665.45 0.107360E+09 0.174033E+09 22321022.86
July 0.136457E+09 23030961.87 0.113426E+09 0.206683E+09 9222854.02
August 0.182770E+09 67421861.27 0.115348E+09 0.274302E+09 15630161.23
September 0.186650E+09 93714060.14 92935999.63 0.249352E+09 34726931.00
October 0.272560E+09 0.170918E+09 0.101642E+09 0.336643E+09 72994606.06
November 0.182642E+09 0.109561E+09 73080255.50 0.193399E+09 0.110638E+09
December 0.187192E+09 0.132954E+09 54238828.37 0.190180E+09 0.148261E+09
           
Annual Sum or Average 0.215409E+10 0.107208E+10 0.108201E+10 0.255223E+10 0.971621E+09
Minimum of Months 0.126914E+09 19554665.45 54238828.37 0.166002E+09 9222854.02
Maximum of Months 0.272560E+09 0.170918E+09 0.115348E+09 0.336643E+09 0.166502E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.470274E+09 0.308599E+09 0.161674E+09 0.456071E+09 0.451922E+09
February 0.562131E+09 0.373607E+09 0.188524E+09 0.557829E+09 0.400439E+09
March 0.551411E+09 0.303545E+09 0.247867E+09 0.581615E+09 0.313603E+09
April 0.424751E+09 0.171843E+09 0.252908E+09 0.471724E+09 0.216164E+09
May 0.376971E+09 77178699.67 0.299792E+09 0.450564E+09 0.131928E+09
June 0.344471E+09 53075361.84 0.291396E+09 0.472362E+09 60583821.72
July 0.370372E+09 62510741.40 0.307861E+09 0.560980E+09 25032712.30
August 0.496076E+09 0.182997E+09 0.313079E+09 0.744511E+09 42423454.66
September 0.506606E+09 0.254359E+09 0.252247E+09 0.676792E+09 94255993.96
October 0.739783E+09 0.463906E+09 0.275877E+09 0.913718E+09 0.198122E+09
November 0.495727E+09 0.297372E+09 0.198355E+09 0.524924E+09 0.300293E+09
December 0.508078E+09 0.360863E+09 0.147215E+09 0.516187E+09 0.402411E+09
           
Annual Sum or Average 0.584665E+10 0.290986E+10 0.293680E+10 0.692728E+10 0.263718E+10
Minimum of Months 0.344471E+09 53075361.84 0.147215E+09 0.450564E+09 25032712.30
Maximum of Months 0.739783E+09 0.463906E+09 0.313079E+09 0.913718E+09 0.451922E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.371336E+09 0.243675E+09 0.127661E+09 0.361929E+09 0.334402E+09
February 0.443868E+09 0.295007E+09 0.148862E+09 0.440252E+09 0.299931E+09
March 0.435404E+09 0.239684E+09 0.195720E+09 0.453690E+09 0.236210E+09
April 0.335391E+09 0.135690E+09 0.199700E+09 0.366885E+09 0.159571E+09
May 0.297663E+09 60941606.69 0.236721E+09 0.349950E+09 92192595.02
June 0.272000E+09 41909203.44 0.230091E+09 0.372825E+09 33641360.52
July 0.292452E+09 49359538.74 0.243092E+09 0.450000E+09 8327366.95
August 0.391710E+09 0.144497E+09 0.247212E+09 0.593200E+09 20345493.04
September 0.400025E+09 0.200846E+09 0.199179E+09 0.533897E+09 57008703.89
October 0.584146E+09 0.366308E+09 0.217837E+09 0.716112E+09 0.137656E+09
November 0.391434E+09 0.234810E+09 0.156624E+09 0.415207E+09 0.219667E+09
December 0.401187E+09 0.284944E+09 0.116244E+09 0.408433E+09 0.297390E+09
           
Annual Sum or Average 0.461662E+10 0.229767E+10 0.231894E+10 0.546238E+10 0.189634E+10
Minimum of Months 0.272000E+09 41909203.44 0.116244E+09 0.349950E+09 8327366.95
Maximum of Months 0.584146E+09 0.366308E+09 0.247212E+09 0.716112E+09 0.334402E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.275986E+09 0.113300E+09 0.162686E+09 0.166634E+09 0.672794E+09
February 0.366176E+09 0.160704E+09 0.205472E+09 0.245054E+09 0.614536E+09
March 0.602184E+09 0.279066E+09 0.323119E+09 0.530600E+09 0.438837E+09
April 0.632930E+09 0.270479E+09 0.362451E+09 0.644227E+09 0.290523E+09
May 0.764046E+09 0.290443E+09 0.473603E+09 0.891098E+09 0.166705E+09
June 0.807850E+09 0.326026E+09 0.481824E+09 0.106622E+10 61308946.25
July 0.781005E+09 0.293491E+09 0.487514E+09 0.112264E+10 15337710.14
August 0.864094E+09 0.399519E+09 0.464575E+09 0.122764E+10 37654263.42
September 0.594954E+09 0.259739E+09 0.335215E+09 0.753411E+09 0.106468E+09
October 0.610005E+09 0.297155E+09 0.312850E+09 0.678592E+09 0.263792E+09
November 0.278002E+09 81216406.75 0.196786E+09 0.190962E+09 0.434680E+09
December 0.253740E+09 0.109532E+09 0.144208E+09 0.156843E+09 0.607629E+09
           
Annual Sum or Average 0.683097E+10 0.288067E+10 0.395030E+10 0.767392E+10 0.371026E+10
Minimum of Months 0.253740E+09 81216406.75 0.144208E+09 0.156843E+09 15337710.14
Maximum of Months 0.864094E+09 0.399519E+09 0.487514E+09 0.122764E+10 0.672794E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 71441120.58 0.00 71441120.58 6192480.38 0.372820E+09
February 88303223.66 0.00 88303223.66 10770782.08 0.344476E+09
March 0.135606E+09 2824.51 0.135604E+09 54126533.93 0.245706E+09
April 0.157926E+09 650731.43 0.157276E+09 0.107948E+09 0.156485E+09
May 0.217051E+09 7943454.65 0.209108E+09 0.216875E+09 85710249.80
June 0.221597E+09 11786401.62 0.209811E+09 0.286638E+09 31735699.91
July 0.222253E+09 8673946.39 0.213579E+09 0.335481E+09 8162861.62
August 0.196546E+09 2611506.30 0.193935E+09 0.294711E+09 19316824.29
September 0.143220E+09 83260.91 0.143137E+09 0.166577E+09 56082094.17
October 0.127973E+09 0.00 0.127973E+09 0.104569E+09 0.140261E+09
November 86865075.47 0.00 86865075.47 30861812.13 0.234997E+09
December 62315669.45 0.00 62315669.45 4463079.65 0.334591E+09
           
Annual Sum or Average 0.173110E+10 31752125.80 0.169935E+10 0.161921E+10 0.203034E+10
Minimum of Months 62315669.45 0.00 62315669.45 4463079.65 8162861.62
Maximum of Months 0.222253E+09 11786401.62 0.213579E+09 0.335481E+09 0.372820E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.275986E+09 0.113300E+09 0.162686E+09 0.174706E+09 0.666413E+09
February 0.366176E+09 0.160704E+09 0.205472E+09 0.256512E+09 0.605691E+09
March 0.602184E+09 0.279066E+09 0.323119E+09 0.545457E+09 0.432044E+09
April 0.632930E+09 0.270479E+09 0.362451E+09 0.653387E+09 0.287373E+09
May 0.764046E+09 0.290443E+09 0.473603E+09 0.895000E+09 0.165738E+09
June 0.807850E+09 0.326026E+09 0.481824E+09 0.106830E+10 60861764.39
July 0.781005E+09 0.293491E+09 0.487514E+09 0.112526E+10 15049853.71
August 0.864094E+09 0.399519E+09 0.464575E+09 0.123410E+10 36475732.62
September 0.594954E+09 0.259739E+09 0.335215E+09 0.762272E+09 0.103472E+09
October 0.610005E+09 0.297155E+09 0.312850E+09 0.695698E+09 0.255892E+09
November 0.278002E+09 81216406.75 0.196786E+09 0.202736E+09 0.426928E+09
December 0.253740E+09 0.109532E+09 0.144208E+09 0.166893E+09 0.599349E+09
           
Annual Sum or Average 0.683097E+10 0.288067E+10 0.395030E+10 0.778032E+10 0.365529E+10
Minimum of Months 0.253740E+09 81216406.75 0.144208E+09 0.166893E+09 15049853.71
Maximum of Months 0.864094E+09 0.399519E+09 0.487514E+09 0.123410E+10 0.666413E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.544600E+09 0.357373E+09 0.187227E+09 0.514317E+09 0.509143E+09
February 0.650976E+09 0.432656E+09 0.218320E+09 0.626423E+09 0.457531E+09
March 0.638561E+09 0.351519E+09 0.287042E+09 0.653513E+09 0.356085E+09
April 0.491883E+09 0.199003E+09 0.292880E+09 0.533158E+09 0.236863E+09
May 0.436551E+09 89376714.80 0.347174E+09 0.516509E+09 0.133232E+09
June 0.398915E+09 61463868.89 0.337451E+09 0.555986E+09 45891613.01
July 0.428908E+09 72390500.62 0.356518E+09 0.670620E+09 10234254.94
August 0.574480E+09 0.211919E+09 0.362561E+09 0.878638E+09 27513527.85
September 0.586675E+09 0.294560E+09 0.292115E+09 0.782281E+09 83410388.13
October 0.856705E+09 0.537226E+09 0.319480E+09 0.104103E+10 0.207312E+09
November 0.574076E+09 0.344371E+09 0.229705E+09 0.592489E+09 0.339217E+09
December 0.588380E+09 0.417897E+09 0.170482E+09 0.581071E+09 0.455752E+09
           
Annual Sum or Average 0.677071E+10 0.336976E+10 0.340095E+10 0.794604E+10 0.286218E+10
Minimum of Months 0.398915E+09 61463868.89 0.170482E+09 0.514317E+09 10234254.94
Maximum of Months 0.856705E+09 0.537226E+09 0.362561E+09 0.104103E+10 0.509143E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.500069E+09 0.00 0.500069E+09 11159821.63 0.315464E+10
February 0.618099E+09 0.00 0.618099E+09 34614031.82 0.287222E+10
March 0.949209E+09 19770.80 0.949189E+09 0.276116E+09 0.211767E+10
April 0.110544E+10 4554947.47 0.110089E+10 0.640459E+09 0.138749E+10
May 0.151930E+10 55602076.65 0.146370E+10 0.138447E+10 0.783825E+09
June 0.155112E+10 82501686.62 0.146862E+10 0.189835E+10 0.358325E+09
July 0.155571E+10 60715325.16 0.149500E+10 0.221979E+10 0.157246E+09
August 0.137577E+10 18279851.73 0.135749E+10 0.194628E+10 0.240249E+09
September 0.100250E+10 582804.32 0.100192E+10 0.106673E+10 0.587043E+09
October 0.895777E+09 0.00 0.895777E+09 0.629417E+09 0.125487E+10
November 0.608032E+09 0.00 0.608032E+09 0.134807E+09 0.210220E+10
December 0.436193E+09 0.00 0.436193E+09 7950607.59 0.291218E+10
           
Annual Sum or Average 0.121172E+11 0.222256E+09 0.118950E+11 0.102501E+11 0.179279E+11
Minimum of Months 0.436193E+09 0.00 0.436193E+09 7950607.59 0.157246E+09
Maximum of Months 0.155571E+10 82501686.62 0.149500E+10 0.221979E+10 0.315464E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.500069E+09 0.00 0.500069E+09 7588443.67 0.324885E+10
February 0.618099E+09 0.00 0.618099E+09 29170304.40 0.295327E+10
March 0.949209E+09 19770.80 0.949189E+09 0.255415E+09 0.217993E+10
April 0.110544E+10 4554947.47 0.110089E+10 0.612733E+09 0.142963E+10
May 0.151930E+10 55602076.65 0.146370E+10 0.135279E+10 0.806096E+09
June 0.155112E+10 82501686.62 0.146862E+10 0.187558E+10 0.372397E+09
July 0.155571E+10 60715325.16 0.149500E+10 0.219908E+10 0.168115E+09
August 0.137577E+10 18279851.73 0.135749E+10 0.192498E+10 0.251630E+09
September 0.100250E+10 582804.32 0.100192E+10 0.104589E+10 0.608403E+09
October 0.895777E+09 0.00 0.895777E+09 0.606690E+09 0.128942E+10
November 0.608032E+09 0.00 0.608032E+09 0.122126E+09 0.217023E+10
December 0.436193E+09 0.00 0.436193E+09 5819826.30 0.300042E+10
           
Annual Sum or Average 0.121172E+11 0.222256E+09 0.118950E+11 0.100379E+11 0.184784E+11
Minimum of Months 0.436193E+09 0.00 0.436193E+09 5819826.30 0.168115E+09
Maximum of Months 0.155571E+10 82501686.62 0.149500E+10 0.219908E+10 0.324885E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 71441120.58 0.00 71441120.58 6337811.45 0.402352E+09
February 88303223.66 0.00 88303223.66 10575015.24 0.368363E+09
March 0.135606E+09 2824.51 0.135604E+09 57850519.88 0.267559E+09
April 0.157926E+09 650731.43 0.157276E+09 0.127219E+09 0.176768E+09
May 0.217051E+09 7943454.65 0.209108E+09 0.257671E+09 0.103876E+09
June 0.221597E+09 11786401.62 0.209811E+09 0.339746E+09 48310463.55
July 0.222253E+09 8673946.39 0.213579E+09 0.394942E+09 22398294.11
August 0.196546E+09 2611506.30 0.193935E+09 0.350586E+09 32268774.66
September 0.143220E+09 83260.91 0.143137E+09 0.208184E+09 70558887.20
October 0.127973E+09 0.00 0.127973E+09 0.126428E+09 0.152142E+09
November 86865075.47 0.00 86865075.47 33313897.58 0.261809E+09
December 62315669.45 0.00 62315669.45 4449316.77 0.364923E+09
           
Annual Sum or Average 0.173110E+10 31752125.80 0.169935E+10 0.191730E+10 0.227133E+10
Minimum of Months 62315669.45 0.00 62315669.45 4449316.77 22398294.11
Maximum of Months 0.222253E+09 11786401.62 0.213579E+09 0.394942E+09 0.402352E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.555794E+09 0.222057E+09 0.333737E+09 0.346890E+09 0.141264E+10
February 0.779409E+09 0.362953E+09 0.416456E+09 0.553114E+09 0.124317E+10
March 0.110812E+10 0.470944E+09 0.637179E+09 0.100978E+10 0.960451E+09
April 0.128373E+10 0.563442E+09 0.720285E+09 0.140913E+10 0.639369E+09
May 0.160150E+10 0.638219E+09 0.963277E+09 0.204141E+10 0.390935E+09
June 0.143914E+10 0.521274E+09 0.917867E+09 0.210601E+10 0.181606E+09
July 0.149164E+10 0.537013E+09 0.954629E+09 0.238850E+10 84396011.22
August 0.168274E+10 0.759182E+09 0.923559E+09 0.262290E+10 0.120776E+09
September 0.121816E+10 0.548771E+09 0.669389E+09 0.172500E+10 0.259190E+09
October 0.113718E+10 0.514751E+09 0.622434E+09 0.138760E+10 0.552381E+09
November 0.681609E+09 0.261927E+09 0.419682E+09 0.586371E+09 0.919122E+09
December 0.550653E+09 0.259823E+09 0.290830E+09 0.381709E+09 0.126535E+10
           
Annual Sum or Average 0.135297E+11 0.566036E+10 0.786932E+10 0.165584E+11 0.802939E+10
Minimum of Months 0.550653E+09 0.222057E+09 0.290830E+09 0.346890E+09 84396011.22
Maximum of Months 0.168274E+10 0.759182E+09 0.963277E+09 0.262290E+10 0.141264E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.371336E+09 0.243675E+09 0.127661E+09 0.369507E+09 0.357778E+09
February 0.443868E+09 0.295007E+09 0.148862E+09 0.450709E+09 0.315765E+09
March 0.435404E+09 0.239684E+09 0.195720E+09 0.472913E+09 0.254915E+09
April 0.335391E+09 0.135690E+09 0.199700E+09 0.393675E+09 0.177429E+09
May 0.297663E+09 60941606.69 0.236721E+09 0.392818E+09 0.108482E+09
June 0.272000E+09 41909203.44 0.230091E+09 0.426152E+09 50330085.64
July 0.292452E+09 49359538.74 0.243092E+09 0.510139E+09 22866013.12
August 0.391710E+09 0.144497E+09 0.247212E+09 0.654512E+09 32567645.11
September 0.400025E+09 0.200846E+09 0.199179E+09 0.583469E+09 69967500.89
October 0.584146E+09 0.366308E+09 0.217837E+09 0.756652E+09 0.148154E+09
November 0.391434E+09 0.234810E+09 0.156624E+09 0.429050E+09 0.239603E+09
December 0.401187E+09 0.284944E+09 0.116244E+09 0.417548E+09 0.319421E+09
           
Annual Sum or Average 0.461662E+10 0.229767E+10 0.231894E+10 0.585714E+10 0.209728E+10
Minimum of Months 0.272000E+09 41909203.44 0.116244E+09 0.369507E+09 22866013.12
Maximum of Months 0.584146E+09 0.366308E+09 0.247212E+09 0.756652E+09 0.357778E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 90475671.53 0.00 90475671.53 3424782.77 0.523655E+09
February 0.111830E+09 0.00 0.111830E+09 8382172.66 0.479776E+09
March 0.171737E+09 3577.06 0.171733E+09 57966995.61 0.338640E+09
April 0.200004E+09 824110.29 0.199180E+09 0.128721E+09 0.218820E+09
May 0.274881E+09 10059884.11 0.264822E+09 0.266508E+09 0.126769E+09
June 0.280639E+09 14926733.97 0.265712E+09 0.347814E+09 61118965.08
July 0.281470E+09 10985005.81 0.270485E+09 0.400337E+09 28403549.10
August 0.248914E+09 3307307.95 0.245606E+09 0.349398E+09 43581393.66
September 0.181379E+09 105444.69 0.181274E+09 0.196301E+09 97805645.92
October 0.162070E+09 0.00 0.162070E+09 0.119260E+09 0.207057E+09
November 0.110009E+09 0.00 0.110009E+09 29737998.85 0.335894E+09
December 78918863.46 0.00 78918863.46 2340593.72 0.476070E+09
           
Annual Sum or Average 0.219233E+10 40212063.88 0.215212E+10 0.191019E+10 0.293759E+10
Minimum of Months 78918863.46 0.00 78918863.46 2340593.72 28403549.10
Maximum of Months 0.281470E+09 14926733.97 0.270485E+09 0.400337E+09 0.523655E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80948926.13 0.00 80948926.13 3064166.12 0.468495E+09
February 0.100055E+09 0.00 0.100055E+09 7499561.64 0.429258E+09
March 0.153654E+09 3200.41 0.153651E+09 51863290.61 0.302982E+09
April 0.178944E+09 737334.60 0.178207E+09 0.115167E+09 0.195779E+09
May 0.245937E+09 9000616.43 0.236937E+09 0.238446E+09 0.113421E+09
June 0.251089E+09 13355005.44 0.237733E+09 0.311190E+09 54683369.63
July 0.251832E+09 9828326.32 0.242004E+09 0.358183E+09 25412763.00
August 0.222704E+09 2959060.95 0.219745E+09 0.312608E+09 38992438.04
September 0.162281E+09 94341.77 0.162186E+09 0.175632E+09 87507081.99
October 0.145004E+09 0.00 0.145004E+09 0.106702E+09 0.185255E+09
November 98425591.88 0.00 98425591.88 26606700.25 0.300522E+09
December 70609006.16 0.00 70609006.16 2094138.07 0.425877E+09
           
Annual Sum or Average 0.196148E+10 35977885.91 0.192551E+10 0.170906E+10 0.262818E+10
Minimum of Months 70609006.16 0.00 70609006.16 2094138.07 25412763.00
Maximum of Months 0.251832E+09 13355005.44 0.242004E+09 0.358183E+09 0.468495E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.138631E+10 0.909713E+09 0.476595E+09 0.132549E+10 0.135287E+10
February 0.165709E+10 0.110135E+10 0.555745E+09 0.162166E+10 0.119732E+10
March 0.162549E+10 0.894811E+09 0.730681E+09 0.168454E+10 0.943353E+09
April 0.125211E+10 0.506572E+09 0.745541E+09 0.136037E+10 0.649569E+09
May 0.111126E+10 0.227513E+09 0.883750E+09 0.129164E+10 0.400822E+09
June 0.101546E+10 0.156460E+09 0.858999E+09 0.135291E+10 0.191290E+09
July 0.109181E+10 0.184274E+09 0.907535E+09 0.161175E+10 85662839.27
August 0.146237E+10 0.539452E+09 0.922918E+09 0.215671E+10 0.132369E+09
September 0.149341E+10 0.749819E+09 0.743594E+09 0.196475E+10 0.285921E+09
October 0.218079E+10 0.136754E+10 0.813252E+09 0.266595E+10 0.580558E+09
November 0.146134E+10 0.876615E+09 0.584725E+09 0.152773E+10 0.896399E+09
December 0.149775E+10 0.106378E+10 0.433972E+09 0.150155E+10 0.120632E+10
           
Annual Sum or Average 0.172352E+11 0.857789E+10 0.865731E+10 0.200651E+11 0.792246E+10
Minimum of Months 0.101546E+10 0.156460E+09 0.433972E+09 0.129164E+10 85662839.27
Maximum of Months 0.218079E+10 0.136754E+10 0.922918E+09 0.266595E+10 0.135287E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 679.60 627.85 701.21 460.14 241.07 0.00 0.00
February 916.07 621.23 927.98 616.76 311.22 0.00 0.00
March 859.05 441.64 822.19 452.60 369.58 0.00 0.00
April 720.61 311.18 654.44 264.77 389.67 0.00 0.00
May 670.77 178.61 562.08 115.08 447.01 0.00 0.00
June 721.13 85.70 530.75 81.78 448.97 0.00 0.00
July 820.57 36.90 552.24 93.21 459.04 0.00 0.00
August 1086.32 64.97 739.68 272.86 466.82 0.00 0.00
September 1029.02 137.01 780.56 391.91 388.65 0.00 0.00
October 1343.67 282.19 1103.06 691.71 411.35 0.00 0.00
November 801.95 436.38 763.80 458.18 305.62 0.00 0.00
December 763.09 564.69 757.58 538.07 219.51 0.00 0.00
               
Annual Sum or Average 867.80 313.98 740.41 368.50 371.91 0.00 0.00
Minimum of Months 670.77 36.90 530.75 81.78 219.51 0.00 0.00
Maximum of Months 1343.67 627.85 1103.06 691.71 466.82 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1890.77 1822.60 1974.55 1295.73 678.82 0.00 0.00
February 2547.67 1808.21 2613.12 1736.75 876.37 0.00 0.00
March 2386.24 1325.27 2315.23 1274.50 1040.72 0.00 0.00
April 1992.38 952.97 1842.86 745.58 1097.28 0.00 0.00
May 1838.35 572.49 1582.79 324.05 1258.74 0.00 0.00
June 1992.65 283.86 1494.54 230.28 1264.27 0.00 0.00
July 2281.11 128.38 1555.08 262.47 1292.62 0.00 0.00
August 3034.84 204.25 2082.88 768.36 1314.52 0.00 0.00
September 2864.23 442.71 2198.00 1103.59 1094.42 0.00 0.00
October 3746.46 872.22 3106.15 1947.82 1158.33 0.00 0.00
November 2221.95 1309.40 2150.80 1290.21 860.60 0.00 0.00
December 2122.91 1658.03 2133.29 1515.17 618.12 0.00 0.00
               
Annual Sum or Average 2410.39 943.50 2084.94 1037.67 1047.27 0.00 0.00
Minimum of Months 1838.35 128.38 1494.54 230.28 618.12 0.00 0.00
Maximum of Months 3746.46 1822.60 3106.15 1947.82 1314.52 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2496.08 2487.71 2565.06 1683.23 881.83 0.00 0.00
February 3372.45 2449.35 3394.59 2256.14 1138.45 0.00 0.00
March 3157.90 1805.36 3007.61 1655.65 1351.96 0.00 0.00
April 2633.62 1308.44 2393.98 968.55 1425.43 0.00 0.00
May 2426.84 788.81 2056.14 420.96 1635.17 0.00 0.00
June 2639.55 382.51 1941.50 299.14 1642.35 0.00 0.00
July 3031.05 168.59 2020.14 340.96 1679.18 0.00 0.00
August 4030.56 263.05 2705.78 998.14 1707.64 0.00 0.00
September 3788.10 592.08 2855.33 1433.62 1421.71 0.00 0.00
October 4957.12 1160.34 4035.07 2530.33 1504.74 0.00 0.00
November 2929.67 1793.22 2794.02 1676.05 1117.96 0.00 0.00
December 2800.32 2267.42 2771.26 1968.29 802.97 0.00 0.00
               
Annual Sum or Average 3189.19 1282.33 2708.45 1347.99 1360.46 0.00 0.00
Minimum of Months 2426.84 168.59 1941.50 299.14 802.97 0.00 0.00
Maximum of Months 4957.12 2487.71 4035.07 2530.33 1707.64 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 186.17 366.37 241.68 133.28 108.40 0.00 0.00
February 268.89 363.80 334.84 188.37 146.47 0.00 0.00
March 364.98 248.76 387.39 193.68 193.71 0.00 0.00
April 390.83 173.39 373.58 156.70 216.88 0.00 0.00
May 465.96 96.85 396.40 131.19 265.20 0.00 0.00
June 558.73 37.63 416.61 141.95 274.66 0.00 0.00
July 590.20 9.66 400.78 128.01 272.78 0.00 0.00
August 682.82 22.88 468.86 203.11 265.75 0.00 0.00
September 498.79 64.69 383.87 177.69 206.17 0.00 0.00
October 521.87 151.29 445.84 247.71 198.14 0.00 0.00
November 228.88 250.29 258.27 121.92 136.35 0.00 0.00
December 199.13 328.33 244.52 147.28 97.24 0.00 0.00
               
Annual Sum or Average 414.22 175.11 363.00 164.20 198.80 0.00 0.00
Minimum of Months 186.17 9.66 241.68 121.92 97.24 0.00 0.00
Maximum of Months 682.82 366.37 468.86 247.71 274.66 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 62.46 384.70 129.71 42.30 87.41 0.00 0.00
February 104.05 386.99 187.86 66.43 121.44 0.00 0.00
March 219.62 249.66 275.46 104.19 171.27 0.00 0.00
April 293.79 171.65 305.11 104.60 200.51 0.00 0.00
May 417.35 94.20 366.30 111.40 254.89 0.00 0.00
June 525.71 36.53 397.16 130.33 266.83 0.00 0.00
July 547.97 9.38 374.57 112.82 261.76 0.00 0.00
August 572.81 22.01 396.00 150.14 245.86 0.00 0.00
September 359.47 63.45 284.79 100.24 184.55 0.00 0.00
October 297.78 150.14 275.53 110.94 164.58 0.00 0.00
November 87.20 256.55 140.77 31.33 109.43 0.00 0.00
December 58.74 346.43 118.00 40.89 77.11 0.00 0.00
               
Annual Sum or Average 296.92 179.82 271.50 92.35 179.15 0.00 0.00
Minimum of Months 58.74 9.38 118.00 31.33 77.11 0.00 0.00
Maximum of Months 572.81 386.99 397.16 150.14 266.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 107.99 97.62 110.89 72.77 38.12 0.00 0.00
February 144.36 100.62 146.75 97.54 49.22 0.00 0.00
March 135.04 73.71 130.02 71.58 58.45 0.00 0.00
April 112.77 52.83 103.50 41.87 61.62 0.00 0.00
May 103.50 32.23 88.89 18.20 70.69 0.00 0.00
June 114.17 14.53 83.93 12.93 71.00 0.00 0.00
July 132.30 5.44 87.33 14.74 72.59 0.00 0.00
August 175.56 9.45 116.97 43.15 73.82 0.00 0.00
September 163.16 23.54 123.44 61.98 61.46 0.00 0.00
October 211.81 49.24 174.44 109.39 65.05 0.00 0.00
November 125.74 72.78 120.79 72.46 48.33 0.00 0.00
December 120.68 89.93 119.81 85.09 34.71 0.00 0.00
               
Annual Sum or Average 137.29 51.55 117.09 58.28 58.81 0.00 0.00
Minimum of Months 103.50 5.44 83.93 12.93 34.71 0.00 0.00
Maximum of Months 211.81 100.62 174.44 109.39 73.82 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1.41 116.81 21.34 0.00 21.34 0.00 0.00
February 3.15 118.05 29.20 0.00 29.20 0.00 0.00
March 16.20 75.12 40.51 0.00 40.51 0.00 0.00
April 34.67 49.10 48.75 0.20 48.55 0.00 0.00
May 68.59 25.23 64.84 2.37 62.47 0.00 0.00
June 93.94 8.77 68.40 3.64 64.76 0.00 0.00
July 106.14 1.80 66.39 2.59 63.80 0.00 0.00
August 94.15 4.89 58.71 0.78 57.93 0.00 0.00
September 55.13 16.44 44.21 0.03 44.18 0.00 0.00
October 33.02 41.78 38.23 0.00 38.23 0.00 0.00
November 8.92 76.61 26.81 0.00 26.81 0.00 0.00
December 0.98 105.54 18.62 0.00 18.62 0.00 0.00
               
Annual Sum or Average 43.30 52.98 43.92 0.81 43.11 0.00 0.00
Minimum of Months 0.98 1.80 18.62 0.00 18.62 0.00 0.00
Maximum of Months 106.14 118.05 68.40 3.64 64.76 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 186.91 364.06 242.40 132.43 109.97 0.00 0.00
February 279.85 359.11 344.58 196.96 147.61 0.00 0.00
March 343.99 250.16 369.44 177.41 192.03 0.00 0.00
April 390.85 168.98 377.04 161.05 216.00 0.00 0.00
May 481.33 94.09 410.12 141.90 268.22 0.00 0.00
June 513.74 35.89 382.57 116.73 265.84 0.00 0.00
July 573.73 9.08 387.67 118.68 268.98 0.00 0.00
August 670.73 21.47 460.40 195.68 264.72 0.00 0.00
September 504.09 62.42 389.33 183.35 205.98 0.00 0.00
October 500.36 148.17 430.40 232.86 197.53 0.00 0.00
November 260.04 248.08 282.51 141.12 141.39 0.00 0.00
December 209.23 324.80 252.59 154.89 97.70 0.00 0.00
               
Annual Sum or Average 410.55 172.83 360.92 162.61 198.31 0.00 0.00
Minimum of Months 186.91 9.08 242.40 116.73 97.70 0.00 0.00
Maximum of Months 670.73 364.06 460.40 232.86 268.98 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 58.26 377.53 130.44 41.46 88.98 0.00 0.00
February 104.68 371.56 197.60 75.02 122.58 0.00 0.00
March 197.70 249.93 257.51 87.92 169.58 0.00 0.00
April 292.87 166.87 308.58 108.95 199.63 0.00 0.00
May 432.93 92.10 380.02 122.12 257.91 0.00 0.00
June 480.99 35.17 363.12 105.11 258.02 0.00 0.00
July 531.56 8.92 361.46 103.49 257.96 0.00 0.00
August 560.69 20.83 387.54 142.71 244.83 0.00 0.00
September 363.81 60.89 290.26 105.90 184.36 0.00 0.00
October 274.97 146.12 260.08 96.10 163.98 0.00 0.00
November 114.51 250.31 165.01 50.53 114.48 0.00 0.00
December 63.18 336.90 126.07 48.51 77.56 0.00 0.00
               
Annual Sum or Average 290.94 175.35 269.42 90.76 178.66 0.00 0.00
Minimum of Months 58.26 8.92 126.07 41.46 77.56 0.00 0.00
Maximum of Months 560.69 377.53 387.54 142.71 258.02 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 212.85 471.13 286.50 157.67 128.83 0.00 0.00
February 294.89 466.29 381.24 211.33 169.91 0.00 0.00
March 326.06 325.93 369.48 155.09 214.39 0.00 0.00
April 320.46 227.31 329.85 91.16 238.69 0.00 0.00
May 370.27 128.66 333.06 44.57 288.49 0.00 0.00
June 438.50 61.28 330.05 35.90 294.14 0.00 0.00
July 497.51 25.08 333.06 37.55 295.51 0.00 0.00
August 564.11 42.57 380.64 95.19 285.46 0.00 0.00
September 464.77 99.78 363.23 134.34 228.89 0.00 0.00
October 527.67 205.01 460.78 237.02 223.77 0.00 0.00
November 284.49 323.50 319.80 157.00 162.81 0.00 0.00
December 241.94 420.37 299.91 184.37 115.54 0.00 0.00
               
Annual Sum or Average 379.33 231.76 348.85 128.01 220.84 0.00 0.00
Minimum of Months 212.85 25.08 286.50 35.90 115.54 0.00 0.00
Maximum of Months 564.11 471.13 460.78 237.02 295.51 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 185.80 364.50 241.68 133.28 108.40 0.00 0.00
February 267.77 362.50 334.84 188.37 146.47 0.00 0.00
March 362.75 247.29 387.39 193.68 193.71 0.00 0.00
April 388.23 171.79 373.58 156.70 216.88 0.00 0.00
May 462.31 95.61 396.40 131.19 265.20 0.00 0.00
June 554.94 36.38 416.61 141.95 274.66 0.00 0.00
July 587.14 8.82 400.78 128.01 272.78 0.00 0.00
August 679.79 21.62 468.86 203.11 265.75 0.00 0.00
September 496.29 62.71 383.87 177.69 206.17 0.00 0.00
October 519.46 148.62 445.84 247.71 198.14 0.00 0.00
November 228.87 247.45 258.27 121.92 136.35 0.00 0.00
December 199.14 325.98 244.52 147.28 97.24 0.00 0.00
               
Annual Sum or Average 412.15 173.39 363.00 164.20 198.80 0.00 0.00
Minimum of Months 185.80 8.82 241.68 121.92 97.24 0.00 0.00
Maximum of Months 679.79 364.50 468.86 247.71 274.66 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 62.55 383.01 129.71 42.30 87.41 0.00 0.00
February 103.76 386.04 187.86 66.43 121.44 0.00 0.00
March 218.77 247.95 275.46 104.19 171.27 0.00 0.00
April 292.30 169.82 305.11 104.60 200.51 0.00 0.00
May 414.24 92.99 366.30 111.40 254.89 0.00 0.00
June 522.36 35.34 397.16 130.33 266.83 0.00 0.00
July 545.31 8.59 374.57 112.82 261.76 0.00 0.00
August 570.71 20.75 396.00 150.14 245.86 0.00 0.00
September 358.10 61.31 284.79 100.24 184.55 0.00 0.00
October 297.58 146.70 275.53 110.94 164.58 0.00 0.00
November 88.04 253.29 140.77 31.33 109.43 0.00 0.00
December 59.20 343.92 118.00 40.89 77.11 0.00 0.00
               
Annual Sum or Average 295.75 177.98 271.50 92.35 179.15 0.00 0.00
Minimum of Months 59.20 8.59 118.00 31.33 77.11 0.00 0.00
Maximum of Months 570.71 386.04 397.16 150.14 266.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 192.02 190.09 203.33 133.43 69.90 0.00 0.00
February 258.94 189.12 269.09 178.84 90.24 0.00 0.00
March 243.99 132.95 238.41 131.24 107.17 0.00 0.00
April 205.69 91.38 189.77 76.78 112.99 0.00 0.00
May 192.84 49.74 162.99 33.37 129.62 0.00 0.00
June 214.50 17.71 153.90 23.71 130.19 0.00 0.00
July 250.38 3.82 160.14 27.03 133.11 0.00 0.00
August 328.05 10.27 214.49 79.12 135.36 0.00 0.00
September 301.81 32.18 226.34 113.64 112.70 0.00 0.00
October 388.68 77.40 319.86 200.58 119.28 0.00 0.00
November 228.58 130.87 221.48 132.86 88.62 0.00 0.00
December 216.95 170.16 219.68 156.02 63.65 0.00 0.00
               
Annual Sum or Average 251.97 90.76 214.70 106.85 107.84 0.00 0.00
Minimum of Months 192.02 3.82 153.90 23.71 63.65 0.00 0.00
Maximum of Months 388.68 190.09 319.86 200.58 135.36 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 4.17 1177.81 186.70 0.00 186.70 0.00 0.00
February 14.31 1187.26 255.50 0.00 255.50 0.00 0.00
March 103.09 790.65 354.39 0.01 354.39 0.00 0.00
April 247.09 535.30 426.48 1.76 424.73 0.00 0.00
May 516.90 292.65 567.24 20.76 546.48 0.00 0.00
June 732.39 138.24 598.43 31.83 566.60 0.00 0.00
July 828.77 58.71 580.84 22.67 558.17 0.00 0.00
August 726.66 89.70 513.65 6.82 506.83 0.00 0.00
September 411.55 226.48 386.77 0.22 386.54 0.00 0.00
October 235.00 468.51 334.44 0.00 334.44 0.00 0.00
November 52.01 811.03 234.58 0.00 234.58 0.00 0.00
December 2.97 1087.28 162.86 0.00 162.86 0.00 0.00
               
Annual Sum or Average 325.03 568.49 384.23 7.05 377.19 0.00 0.00
Minimum of Months 2.97 58.71 162.86 0.00 162.86 0.00 0.00
Maximum of Months 828.77 1187.26 598.43 31.83 566.60 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2.83 1212.98 186.70 0.00 186.70 0.00 0.00
February 12.06 1220.76 255.50 0.00 255.50 0.00 0.00
March 95.36 813.89 354.39 0.01 354.39 0.00 0.00
April 236.39 551.55 426.48 1.76 424.73 0.00 0.00
May 505.08 300.96 567.24 20.76 546.48 0.00 0.00
June 723.60 143.67 598.43 31.83 566.60 0.00 0.00
July 821.04 62.77 580.84 22.67 558.17 0.00 0.00
August 718.70 93.95 513.65 6.82 506.83 0.00 0.00
September 403.51 234.72 386.77 0.22 386.54 0.00 0.00
October 226.51 481.41 334.44 0.00 334.44 0.00 0.00
November 47.12 837.28 234.58 0.00 234.58 0.00 0.00
December 2.17 1120.23 162.86 0.00 162.86 0.00 0.00
               
Annual Sum or Average 318.30 585.95 384.23 7.05 377.19 0.00 0.00
Minimum of Months 2.17 62.77 162.86 0.00 162.86 0.00 0.00
Maximum of Months 821.04 1220.76 598.43 31.83 566.60 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 243.32 784.71 372.82 173.88 198.94 0.00 0.00
February 387.58 764.94 542.15 271.97 270.18 0.00 0.00
March 568.54 547.02 626.92 265.32 361.60 0.00 0.00
April 740.23 378.94 685.59 269.98 415.61 0.00 0.00
May 1002.90 223.11 790.10 264.00 526.10 0.00 0.00
June 1107.25 107.38 745.66 221.82 523.83 0.00 0.00
July 1229.54 48.27 749.08 222.16 526.92 0.00 0.00
August 1354.36 69.11 847.89 338.37 509.52 0.00 0.00
September 969.96 153.24 679.55 289.24 390.32 0.00 0.00
October 845.52 316.10 690.45 328.95 361.50 0.00 0.00
November 394.90 538.34 447.50 191.64 255.85 0.00 0.00
December 274.01 701.87 378.64 203.39 175.25 0.00 0.00
               
Annual Sum or Average 762.43 383.98 630.31 253.35 376.95 0.00 0.00
Minimum of Months 243.32 48.27 372.82 173.88 175.25 0.00 0.00
Maximum of Months 1354.36 784.71 847.89 338.37 526.92 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 463.21 841.43 581.59 339.65 241.94 0.00 0.00
February 636.59 830.37 772.56 455.25 317.31 0.00 0.00
March 663.84 585.66 728.38 334.09 394.29 0.00 0.00
April 618.11 409.75 629.27 196.04 433.23 0.00 0.00
May 667.37 235.93 609.35 92.06 517.29 0.00 0.00
June 774.23 116.51 596.91 71.27 525.63 0.00 0.00
July 884.41 51.53 606.75 76.57 530.18 0.00 0.00
August 1052.04 79.90 722.07 203.75 518.32 0.00 0.00
September 901.07 181.37 708.75 289.36 419.39 0.00 0.00
October 1075.57 359.08 928.86 510.58 418.28 0.00 0.00
November 596.00 576.22 644.20 338.20 306.00 0.00 0.00
December 526.51 751.38 615.02 397.17 217.85 0.00 0.00
               
Annual Sum or Average 739.26 415.94 678.24 274.42 403.82 0.00 0.00
Minimum of Months 463.21 51.53 581.59 71.27 217.85 0.00 0.00
Maximum of Months 1075.57 841.43 928.86 510.58 530.18 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.182023E+10 0.168163E+10 0.187811E+10 0.123244E+10 0.645669E+09 0.00 0.00
February 0.221617E+10 0.150288E+10 0.224496E+10 0.149206E+10 0.752897E+09 0.00 0.00
March 0.230088E+10 0.118290E+10 0.220215E+10 0.121226E+10 0.989890E+09 0.00 0.00
April 0.186783E+10 0.806577E+09 0.169631E+10 0.686285E+09 0.101002E+10 0.00 0.00
May 0.179658E+10 0.478379E+09 0.150549E+10 0.308226E+09 0.119726E+10 0.00 0.00
June 0.186916E+10 0.222137E+09 0.137569E+10 0.211965E+09 0.116373E+10 0.00 0.00
July 0.219781E+10 98823119.18 0.147913E+10 0.249647E+09 0.122948E+10 0.00 0.00
August 0.290961E+10 0.174012E+09 0.198115E+10 0.730828E+09 0.125032E+10 0.00 0.00
September 0.266721E+10 0.355119E+09 0.202321E+10 0.101583E+10 0.100738E+10 0.00 0.00
October 0.359887E+10 0.755806E+09 0.295444E+10 0.185269E+10 0.110176E+10 0.00 0.00
November 0.207865E+10 0.113109E+10 0.197976E+10 0.118761E+10 0.792159E+09 0.00 0.00
December 0.204387E+10 0.151246E+10 0.202909E+10 0.144117E+10 0.587926E+09 0.00 0.00
               
Annual Sum or Average 0.273669E+11 0.990181E+10 0.233495E+11 0.116210E+11 0.117285E+11 0.00 0.00
Minimum of Months 0.179658E+10 98823119.18 0.137569E+10 0.211965E+09 0.587926E+09 0.00 0.00
Maximum of Months 0.359887E+10 0.168163E+10 0.295444E+10 0.185269E+10 0.125032E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.506423E+10 0.488166E+10 0.528864E+10 0.347048E+10 0.181816E+10 0.00 0.00
February 0.616332E+10 0.437443E+10 0.632166E+10 0.420155E+10 0.212011E+10 0.00 0.00
March 0.639130E+10 0.354960E+10 0.620110E+10 0.341363E+10 0.278747E+10 0.00 0.00
April 0.516424E+10 0.247010E+10 0.477669E+10 0.193253E+10 0.284415E+10 0.00 0.00
May 0.492384E+10 0.153335E+10 0.423935E+10 0.867945E+09 0.337140E+10 0.00 0.00
June 0.516495E+10 0.735757E+09 0.387386E+10 0.596881E+09 0.327698E+10 0.00 0.00
July 0.610973E+10 0.343841E+09 0.416513E+10 0.702990E+09 0.346214E+10 0.00 0.00
August 0.812851E+10 0.547074E+09 0.557879E+10 0.205796E+10 0.352082E+10 0.00 0.00
September 0.742407E+10 0.114749E+10 0.569723E+10 0.286050E+10 0.283673E+10 0.00 0.00
October 0.100345E+11 0.233615E+10 0.831952E+10 0.521704E+10 0.310247E+10 0.00 0.00
November 0.575928E+10 0.339396E+10 0.557489E+10 0.334422E+10 0.223067E+10 0.00 0.00
December 0.568600E+10 0.444087E+10 0.571380E+10 0.405823E+10 0.165556E+10 0.00 0.00
               
Annual Sum or Average 0.760140E+11 0.297543E+11 0.657506E+11 0.327240E+11 0.330267E+11 0.00 0.00
Minimum of Months 0.492384E+10 0.343841E+09 0.387386E+10 0.596881E+09 0.165556E+10 0.00 0.00
Maximum of Months 0.100345E+11 0.488166E+10 0.831952E+10 0.521704E+10 0.352082E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.668550E+10 0.666308E+10 0.687025E+10 0.450835E+10 0.236190E+10 0.00 0.00
February 0.815862E+10 0.592547E+10 0.821220E+10 0.545806E+10 0.275414E+10 0.00 0.00
March 0.845812E+10 0.483547E+10 0.805558E+10 0.443450E+10 0.362108E+10 0.00 0.00
April 0.682635E+10 0.339148E+10 0.620519E+10 0.251047E+10 0.369472E+10 0.00 0.00
May 0.650006E+10 0.211276E+10 0.550715E+10 0.112751E+10 0.437965E+10 0.00 0.00
June 0.684172E+10 0.991455E+09 0.503236E+10 0.775382E+09 0.425698E+10 0.00 0.00
July 0.811838E+10 0.451539E+09 0.541074E+10 0.913224E+09 0.449752E+10 0.00 0.00
August 0.107954E+11 0.704559E+09 0.724716E+10 0.267341E+10 0.457375E+10 0.00 0.00
September 0.981876E+10 0.153466E+10 0.740102E+10 0.371595E+10 0.368507E+10 0.00 0.00
October 0.132772E+11 0.310787E+10 0.108075E+11 0.677724E+10 0.403029E+10 0.00 0.00
November 0.759371E+10 0.464802E+10 0.724209E+10 0.434433E+10 0.289776E+10 0.00 0.00
December 0.750037E+10 0.607307E+10 0.742255E+10 0.527188E+10 0.215067E+10 0.00 0.00
               
Annual Sum or Average 0.100574E+12 0.404394E+11 0.854138E+11 0.425103E+11 0.429035E+11 0.00 0.00
Minimum of Months 0.650006E+10 0.451539E+09 0.503236E+10 0.775382E+09 0.215067E+10 0.00 0.00
Maximum of Months 0.132772E+11 0.666308E+10 0.108075E+11 0.677724E+10 0.457375E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.498635E+09 0.981280E+09 0.647322E+09 0.356975E+09 0.290347E+09 0.00 0.00
February 0.650507E+09 0.880105E+09 0.810044E+09 0.455710E+09 0.354334E+09 0.00 0.00
March 0.977554E+09 0.666291E+09 0.103759E+10 0.518749E+09 0.518839E+09 0.00 0.00
April 0.101304E+10 0.449425E+09 0.968321E+09 0.406169E+09 0.562152E+09 0.00 0.00
May 0.124803E+10 0.259413E+09 0.106171E+10 0.351385E+09 0.710324E+09 0.00 0.00
June 0.144823E+10 97547647.86 0.107985E+10 0.367935E+09 0.711915E+09 0.00 0.00
July 0.158078E+10 25863032.79 0.107346E+10 0.342851E+09 0.730606E+09 0.00 0.00
August 0.182887E+10 61284980.56 0.125580E+10 0.544016E+09 0.711787E+09 0.00 0.00
September 0.129287E+10 0.167667E+09 0.994979E+09 0.460585E+09 0.534394E+09 0.00 0.00
October 0.139778E+10 0.405208E+09 0.119415E+10 0.663463E+09 0.530687E+09 0.00 0.00
November 0.593266E+09 0.648764E+09 0.669436E+09 0.316026E+09 0.353410E+09 0.00 0.00
December 0.533354E+09 0.879407E+09 0.654927E+09 0.394476E+09 0.260452E+09 0.00 0.00
               
Annual Sum or Average 0.130629E+11 0.552226E+10 0.114476E+11 0.517834E+10 0.626925E+10 0.00 0.00
Minimum of Months 0.498635E+09 25863032.79 0.647322E+09 0.316026E+09 0.260452E+09 0.00 0.00
Maximum of Months 0.182887E+10 0.981280E+09 0.125580E+10 0.663463E+09 0.730606E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.167304E+09 0.103037E+10 0.347427E+09 0.113300E+09 0.234127E+09 0.00 0.00
February 0.251715E+09 0.936198E+09 0.454479E+09 0.160704E+09 0.293776E+09 0.00 0.00
March 0.588240E+09 0.668684E+09 0.737791E+09 0.279068E+09 0.458722E+09 0.00 0.00
April 0.761514E+09 0.444924E+09 0.790856E+09 0.271129E+09 0.519727E+09 0.00 0.00
May 0.111783E+10 0.252295E+09 0.981097E+09 0.298386E+09 0.682711E+09 0.00 0.00
June 0.136264E+10 94688361.77 0.102945E+10 0.337812E+09 0.691635E+09 0.00 0.00
July 0.146767E+10 25113175.44 0.100326E+10 0.302165E+09 0.701093E+09 0.00 0.00
August 0.153420E+10 58949605.53 0.106064E+10 0.402130E+09 0.658510E+09 0.00 0.00
September 0.931735E+09 0.164465E+09 0.738174E+09 0.259822E+09 0.478352E+09 0.00 0.00
October 0.797571E+09 0.402142E+09 0.737978E+09 0.297155E+09 0.440823E+09 0.00 0.00
November 0.226026E+09 0.664977E+09 0.364867E+09 81216406.75 0.283651E+09 0.00 0.00
December 0.157328E+09 0.927889E+09 0.316056E+09 0.109532E+09 0.206524E+09 0.00 0.00
               
Annual Sum or Average 0.936377E+10 0.567070E+10 0.856207E+10 0.291242E+10 0.564965E+10 0.00 0.00
Minimum of Months 0.157328E+09 25113175.44 0.316056E+09 81216406.75 0.206524E+09 0.00 0.00
Maximum of Months 0.153420E+10 0.103037E+10 0.106064E+10 0.402130E+09 0.701093E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.289244E+09 0.261477E+09 0.297010E+09 0.194901E+09 0.102108E+09 0.00 0.00
February 0.349229E+09 0.243422E+09 0.355024E+09 0.235958E+09 0.119066E+09 0.00 0.00
March 0.361686E+09 0.197435E+09 0.348254E+09 0.191709E+09 0.156545E+09 0.00 0.00
April 0.292304E+09 0.136938E+09 0.268259E+09 0.108531E+09 0.159729E+09 0.00 0.00
May 0.277222E+09 86334040.19 0.238083E+09 48743591.57 0.189339E+09 0.00 0.00
June 0.295916E+09 37667383.94 0.217557E+09 33520696.39 0.184036E+09 0.00 0.00
July 0.354339E+09 14581042.49 0.233915E+09 39479779.53 0.194435E+09 0.00 0.00
August 0.470218E+09 25307151.50 0.313305E+09 0.115575E+09 0.197731E+09 0.00 0.00
September 0.422922E+09 61007818.16 0.319956E+09 0.160645E+09 0.159311E+09 0.00 0.00
October 0.567322E+09 0.131883E+09 0.467223E+09 0.292988E+09 0.174235E+09 0.00 0.00
November 0.325928E+09 0.188638E+09 0.313085E+09 0.187811E+09 0.125275E+09 0.00 0.00
December 0.323239E+09 0.240881E+09 0.320886E+09 0.227910E+09 92976446.14 0.00 0.00
               
Annual Sum or Average 0.432957E+10 0.162557E+10 0.369256E+10 0.183777E+10 0.185479E+10 0.00 0.00
Minimum of Months 0.277222E+09 14581042.49 0.217557E+09 33520696.39 92976446.14 0.00 0.00
Maximum of Months 0.567322E+09 0.261477E+09 0.467223E+09 0.292988E+09 0.197731E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 3788975.13 0.312862E+09 57160472.40 0.00 57160472.40 0.00 0.00
February 7619990.17 0.285580E+09 70651943.00 0.00 70651943.00 0.00 0.00
March 43383682.13 0.201212E+09 0.108500E+09 2259.91 0.108497E+09 0.00 0.00
April 89873410.25 0.127255E+09 0.126358E+09 520654.15 0.125837E+09 0.00 0.00
May 0.183712E+09 67581883.40 0.173664E+09 6355606.08 0.167308E+09 0.00 0.00
June 0.243495E+09 22738375.97 0.177301E+09 9430371.18 0.167871E+09 0.00 0.00
July 0.284291E+09 4822951.90 0.177826E+09 6940076.94 0.170886E+09 0.00 0.00
August 0.252164E+09 13099673.25 0.157258E+09 2089481.97 0.155168E+09 0.00 0.00
September 0.142890E+09 42613322.58 0.114591E+09 66617.56 0.114525E+09 0.00 0.00
October 88452923.59 0.111895E+09 0.102392E+09 0.00 0.102392E+09 0.00 0.00
November 23112353.82 0.198561E+09 69501271.94 0.00 69501271.94 0.00 0.00
December 2616352.80 0.282667E+09 49859143.80 0.00 49859143.80 0.00 0.00
               
Annual Sum or Average 0.136540E+10 0.167089E+10 0.138506E+10 25405067.78 0.135966E+10 0.00 0.00
Minimum of Months 2616352.80 4822951.90 49859143.80 0.00 49859143.80 0.00 0.00
Maximum of Months 0.284291E+09 0.312862E+09 0.177826E+09 9430371.18 0.170886E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.500609E+09 0.975101E+09 0.649253E+09 0.354712E+09 0.294541E+09 0.00 0.00
February 0.677014E+09 0.868761E+09 0.833601E+09 0.476496E+09 0.357104E+09 0.00 0.00
March 0.921342E+09 0.670037E+09 0.989505E+09 0.475173E+09 0.514332E+09 0.00 0.00
April 0.101309E+10 0.437990E+09 0.977300E+09 0.417431E+09 0.559869E+09 0.00 0.00
May 0.128919E+10 0.252000E+09 0.109847E+10 0.380074E+09 0.718394E+09 0.00 0.00
June 0.133161E+10 93015259.66 0.991622E+09 0.302565E+09 0.689057E+09 0.00 0.00
July 0.153667E+10 24306682.24 0.103833E+10 0.317885E+09 0.720441E+09 0.00 0.00
August 0.179647E+10 57505440.00 0.123314E+10 0.524115E+09 0.709025E+09 0.00 0.00
September 0.130659E+10 0.161785E+09 0.100915E+10 0.475251E+09 0.533897E+09 0.00 0.00
October 0.134017E+10 0.396865E+09 0.115278E+10 0.623702E+09 0.529077E+09 0.00 0.00
November 0.674020E+09 0.643016E+09 0.732263E+09 0.365783E+09 0.366480E+09 0.00 0.00
December 0.560409E+09 0.869933E+09 0.676533E+09 0.414864E+09 0.261669E+09 0.00 0.00
               
Annual Sum or Average 0.129472E+11 0.545032E+10 0.113819E+11 0.512805E+10 0.625389E+10 0.00 0.00
Minimum of Months 0.500609E+09 24306682.24 0.649253E+09 0.302565E+09 0.261669E+09 0.00 0.00
Maximum of Months 0.179647E+10 0.975101E+09 0.123314E+10 0.623702E+09 0.720441E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.156033E+09 0.101117E+10 0.349358E+09 0.111036E+09 0.238322E+09 0.00 0.00
February 0.253246E+09 0.898880E+09 0.478035E+09 0.181489E+09 0.296546E+09 0.00 0.00
March 0.529513E+09 0.669409E+09 0.689708E+09 0.235492E+09 0.454216E+09 0.00 0.00
April 0.759107E+09 0.432528E+09 0.799836E+09 0.282392E+09 0.517444E+09 0.00 0.00
May 0.115955E+10 0.246680E+09 0.101786E+10 0.327076E+09 0.690780E+09 0.00 0.00
June 0.124672E+10 91147736.72 0.941219E+09 0.272442E+09 0.668777E+09 0.00 0.00
July 0.142374E+10 23893714.95 0.968127E+09 0.277199E+09 0.690928E+09 0.00 0.00
August 0.150174E+10 55795721.93 0.103798E+10 0.382230E+09 0.655747E+09 0.00 0.00
September 0.942986E+09 0.157829E+09 0.752343E+09 0.274488E+09 0.477855E+09 0.00 0.00
October 0.736484E+09 0.391365E+09 0.696606E+09 0.257394E+09 0.439212E+09 0.00 0.00
November 0.296812E+09 0.648796E+09 0.427694E+09 0.130973E+09 0.296721E+09 0.00 0.00
December 0.169220E+09 0.902359E+09 0.337662E+09 0.129921E+09 0.207741E+09 0.00 0.00
               
Annual Sum or Average 0.917515E+10 0.552986E+10 0.849642E+10 0.286213E+10 0.563429E+10 0.00 0.00
Minimum of Months 0.156033E+09 23893714.95 0.337662E+09 0.111036E+09 0.207741E+09 0.00 0.00
Maximum of Months 0.150174E+10 0.101117E+10 0.103798E+10 0.382230E+09 0.690928E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.570087E+09 0.126187E+10 0.767366E+09 0.422297E+09 0.345069E+09 0.00 0.00
February 0.713396E+09 0.112806E+10 0.922294E+09 0.511256E+09 0.411038E+09 0.00 0.00
March 0.873321E+09 0.872970E+09 0.989615E+09 0.415385E+09 0.574230E+09 0.00 0.00
April 0.830631E+09 0.589186E+09 0.854977E+09 0.236284E+09 0.618693E+09 0.00 0.00
May 0.991729E+09 0.344596E+09 0.892073E+09 0.119382E+09 0.772691E+09 0.00 0.00
June 0.113659E+10 0.158844E+09 0.855479E+09 93059373.46 0.762420E+09 0.00 0.00
July 0.133252E+10 67163543.92 0.892059E+09 0.100576E+09 0.791483E+09 0.00 0.00
August 0.151090E+10 0.114020E+09 0.101952E+10 0.254945E+09 0.764574E+09 0.00 0.00
September 0.120467E+10 0.258634E+09 0.941500E+09 0.348218E+09 0.593282E+09 0.00 0.00
October 0.141332E+10 0.549104E+09 0.123416E+10 0.634824E+09 0.599335E+09 0.00 0.00
November 0.737400E+09 0.838501E+09 0.828931E+09 0.406933E+09 0.421998E+09 0.00 0.00
December 0.648012E+09 0.112593E+10 0.803283E+09 0.493817E+09 0.309466E+09 0.00 0.00
               
Annual Sum or Average 0.119626E+11 0.730888E+10 0.110013E+11 0.403698E+10 0.696428E+10 0.00 0.00
Minimum of Months 0.570087E+09 67163543.92 0.767366E+09 93059373.46 0.309466E+09 0.00 0.00
Maximum of Months 0.151090E+10 0.126187E+10 0.123416E+10 0.634824E+09 0.791483E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.497634E+09 0.976267E+09 0.647322E+09 0.356975E+09 0.290347E+09 0.00 0.00
February 0.647800E+09 0.876960E+09 0.810044E+09 0.455710E+09 0.354334E+09 0.00 0.00
March 0.971597E+09 0.662355E+09 0.103759E+10 0.518749E+09 0.518839E+09 0.00 0.00
April 0.100629E+10 0.445268E+09 0.968321E+09 0.406169E+09 0.562152E+09 0.00 0.00
May 0.123824E+10 0.256092E+09 0.106171E+10 0.351385E+09 0.710324E+09 0.00 0.00
June 0.143840E+10 94305764.77 0.107985E+10 0.367935E+09 0.711915E+09 0.00 0.00
July 0.157260E+10 23621917.82 0.107346E+10 0.342851E+09 0.730606E+09 0.00 0.00
August 0.182076E+10 57913902.00 0.125580E+10 0.544016E+09 0.711787E+09 0.00 0.00
September 0.128639E+10 0.162557E+09 0.994979E+09 0.460585E+09 0.534394E+09 0.00 0.00
October 0.139133E+10 0.398074E+09 0.119415E+10 0.663463E+09 0.530687E+09 0.00 0.00
November 0.593224E+09 0.641401E+09 0.669436E+09 0.316026E+09 0.353410E+09 0.00 0.00
December 0.533371E+09 0.873114E+09 0.654927E+09 0.394476E+09 0.260452E+09 0.00 0.00
               
Annual Sum or Average 0.129976E+11 0.546793E+10 0.114476E+11 0.517834E+10 0.626925E+10 0.00 0.00
Minimum of Months 0.497634E+09 23621917.82 0.647322E+09 0.316026E+09 0.260452E+09 0.00 0.00
Maximum of Months 0.182076E+10 0.976267E+09 0.125580E+10 0.663463E+09 0.730606E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.167528E+09 0.102586E+10 0.347427E+09 0.113300E+09 0.234127E+09 0.00 0.00
February 0.251020E+09 0.933903E+09 0.454479E+09 0.160704E+09 0.293776E+09 0.00 0.00
March 0.585949E+09 0.664116E+09 0.737791E+09 0.279068E+09 0.458722E+09 0.00 0.00
April 0.757652E+09 0.440176E+09 0.790856E+09 0.271129E+09 0.519727E+09 0.00 0.00
May 0.110949E+10 0.249063E+09 0.981097E+09 0.298386E+09 0.682711E+09 0.00 0.00
June 0.135395E+10 91601831.34 0.102945E+10 0.337812E+09 0.691635E+09 0.00 0.00
July 0.146055E+10 23018343.46 0.100326E+10 0.302165E+09 0.701093E+09 0.00 0.00
August 0.152859E+10 55572598.04 0.106064E+10 0.402130E+09 0.658510E+09 0.00 0.00
September 0.928200E+09 0.158905E+09 0.738174E+09 0.259822E+09 0.478352E+09 0.00 0.00
October 0.797035E+09 0.392921E+09 0.737978E+09 0.297155E+09 0.440823E+09 0.00 0.00
November 0.228196E+09 0.656522E+09 0.364867E+09 81216406.75 0.283651E+09 0.00 0.00
December 0.158562E+09 0.921147E+09 0.316056E+09 0.109532E+09 0.206524E+09 0.00 0.00
               
Annual Sum or Average 0.932672E+10 0.561281E+10 0.856207E+10 0.291242E+10 0.564965E+10 0.00 0.00
Minimum of Months 0.158562E+09 23018343.46 0.316056E+09 81216406.75 0.206524E+09 0.00 0.00
Maximum of Months 0.152859E+10 0.102586E+10 0.106064E+10 0.402130E+09 0.701093E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.514317E+09 0.509143E+09 0.544600E+09 0.357373E+09 0.187227E+09 0.00 0.00
February 0.626423E+09 0.457531E+09 0.650976E+09 0.432656E+09 0.218320E+09 0.00 0.00
March 0.653513E+09 0.356085E+09 0.638561E+09 0.351519E+09 0.287042E+09 0.00 0.00
April 0.533158E+09 0.236863E+09 0.491883E+09 0.199003E+09 0.292880E+09 0.00 0.00
May 0.516509E+09 0.133232E+09 0.436551E+09 89376714.80 0.347174E+09 0.00 0.00
June 0.555986E+09 45891613.01 0.398915E+09 61463868.89 0.337451E+09 0.00 0.00
July 0.670620E+09 10234254.94 0.428908E+09 72390500.62 0.356518E+09 0.00 0.00
August 0.878638E+09 27513527.85 0.574480E+09 0.211919E+09 0.362561E+09 0.00 0.00
September 0.782281E+09 83410388.13 0.586675E+09 0.294560E+09 0.292115E+09 0.00 0.00
October 0.104103E+10 0.207312E+09 0.856705E+09 0.537226E+09 0.319480E+09 0.00 0.00
November 0.592489E+09 0.339217E+09 0.574076E+09 0.344371E+09 0.229705E+09 0.00 0.00
December 0.581071E+09 0.455752E+09 0.588380E+09 0.417897E+09 0.170482E+09 0.00 0.00
               
Annual Sum or Average 0.794604E+10 0.286218E+10 0.677071E+10 0.336976E+10 0.340095E+10 0.00 0.00
Minimum of Months 0.514317E+09 10234254.94 0.398915E+09 61463868.89 0.170482E+09 0.00 0.00
Maximum of Months 0.104103E+10 0.509143E+09 0.856705E+09 0.537226E+09 0.362561E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 11159821.63 0.315464E+10 0.500069E+09 0.00 0.500069E+09 0.00 0.00
February 34614031.82 0.287222E+10 0.618099E+09 0.00 0.618099E+09 0.00 0.00
March 0.276116E+09 0.211767E+10 0.949209E+09 19770.80 0.949189E+09 0.00 0.00
April 0.640459E+09 0.138749E+10 0.110544E+10 4554947.47 0.110089E+10 0.00 0.00
May 0.138447E+10 0.783825E+09 0.151930E+10 55602076.65 0.146370E+10 0.00 0.00
June 0.189835E+10 0.358325E+09 0.155112E+10 82501686.62 0.146862E+10 0.00 0.00
July 0.221979E+10 0.157246E+09 0.155571E+10 60715325.16 0.149500E+10 0.00 0.00
August 0.194628E+10 0.240249E+09 0.137577E+10 18279851.73 0.135749E+10 0.00 0.00
September 0.106673E+10 0.587043E+09 0.100250E+10 582804.32 0.100192E+10 0.00 0.00
October 0.629417E+09 0.125487E+10 0.895777E+09 0.00 0.895777E+09 0.00 0.00
November 0.134807E+09 0.210220E+10 0.608032E+09 0.00 0.608032E+09 0.00 0.00
December 7950607.59 0.291218E+10 0.436193E+09 0.00 0.436193E+09 0.00 0.00
               
Annual Sum or Average 0.102501E+11 0.179279E+11 0.121172E+11 0.222256E+09 0.118950E+11 0.00 0.00
Minimum of Months 7950607.59 0.157246E+09 0.436193E+09 0.00 0.436193E+09 0.00 0.00
Maximum of Months 0.221979E+10 0.315464E+10 0.155571E+10 82501686.62 0.149500E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 7588443.67 0.324885E+10 0.500069E+09 0.00 0.500069E+09 0.00 0.00
February 29170304.40 0.295327E+10 0.618099E+09 0.00 0.618099E+09 0.00 0.00
March 0.255415E+09 0.217993E+10 0.949209E+09 19770.80 0.949189E+09 0.00 0.00
April 0.612733E+09 0.142963E+10 0.110544E+10 4554947.47 0.110089E+10 0.00 0.00
May 0.135279E+10 0.806096E+09 0.151930E+10 55602076.65 0.146370E+10 0.00 0.00
June 0.187558E+10 0.372397E+09 0.155112E+10 82501686.62 0.146862E+10 0.00 0.00
July 0.219908E+10 0.168115E+09 0.155571E+10 60715325.16 0.149500E+10 0.00 0.00
August 0.192498E+10 0.251630E+09 0.137577E+10 18279851.73 0.135749E+10 0.00 0.00
September 0.104589E+10 0.608403E+09 0.100250E+10 582804.32 0.100192E+10 0.00 0.00
October 0.606690E+09 0.128942E+10 0.895777E+09 0.00 0.895777E+09 0.00 0.00
November 0.122126E+09 0.217023E+10 0.608032E+09 0.00 0.608032E+09 0.00 0.00
December 5819826.30 0.300042E+10 0.436193E+09 0.00 0.436193E+09 0.00 0.00
               
Annual Sum or Average 0.100379E+11 0.184784E+11 0.121172E+11 0.222256E+09 0.118950E+11 0.00 0.00
Minimum of Months 5819826.30 0.168115E+09 0.436193E+09 0.00 0.436193E+09 0.00 0.00
Maximum of Months 0.219908E+10 0.324885E+10 0.155571E+10 82501686.62 0.149500E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.651720E+09 0.210176E+10 0.998571E+09 0.465732E+09 0.532839E+09 0.00 0.00
February 0.937634E+09 0.185054E+10 0.131158E+10 0.657960E+09 0.653621E+09 0.00 0.00
March 0.152277E+10 0.146514E+10 0.167913E+10 0.710631E+09 0.968503E+09 0.00 0.00
April 0.191867E+10 0.982208E+09 0.177704E+10 0.699783E+09 0.107726E+10 0.00 0.00
May 0.268617E+10 0.597567E+09 0.211621E+10 0.707104E+09 0.140911E+10 0.00 0.00
June 0.287000E+10 0.278333E+09 0.193274E+10 0.574969E+09 0.135777E+10 0.00 0.00
July 0.329321E+10 0.129286E+09 0.200635E+10 0.595046E+09 0.141130E+10 0.00 0.00
August 0.362751E+10 0.185116E+09 0.227100E+10 0.906291E+09 0.136471E+10 0.00 0.00
September 0.251413E+10 0.397199E+09 0.176141E+10 0.749700E+09 0.101171E+10 0.00 0.00
October 0.226463E+10 0.846630E+09 0.184930E+10 0.881059E+09 0.968244E+09 0.00 0.00
November 0.102357E+10 0.139537E+10 0.115991E+10 0.496737E+09 0.663171E+09 0.00 0.00
December 0.733908E+09 0.187990E+10 0.101416E+10 0.544767E+09 0.469389E+09 0.00 0.00
               
Annual Sum or Average 0.240439E+11 0.121090E+11 0.198774E+11 0.798978E+10 0.118876E+11 0.00 0.00
Minimum of Months 0.651720E+09 0.129286E+09 0.998571E+09 0.465732E+09 0.469389E+09 0.00 0.00
Maximum of Months 0.362751E+10 0.210176E+10 0.227100E+10 0.906291E+09 0.141130E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.124065E+10 0.225370E+10 0.155773E+10 0.909713E+09 0.648020E+09 0.00 0.00
February 0.154003E+10 0.200883E+10 0.186898E+10 0.110135E+10 0.767631E+09 0.00 0.00
March 0.177804E+10 0.156864E+10 0.195088E+10 0.894818E+09 0.105606E+10 0.00 0.00
April 0.160215E+10 0.106206E+10 0.163106E+10 0.508134E+09 0.112293E+10 0.00 0.00
May 0.178749E+10 0.631912E+09 0.163208E+10 0.246574E+09 0.138551E+10 0.00 0.00
June 0.200682E+10 0.301993E+09 0.154719E+10 0.184741E+09 0.136244E+10 0.00 0.00
July 0.236880E+10 0.138008E+09 0.162511E+10 0.205087E+09 0.142002E+10 0.00 0.00
August 0.281778E+10 0.214008E+09 0.193399E+10 0.545718E+09 0.138827E+10 0.00 0.00
September 0.233557E+10 0.470117E+09 0.183707E+10 0.750019E+09 0.108705E+10 0.00 0.00
October 0.288081E+10 0.961772E+09 0.248786E+10 0.136754E+10 0.112033E+10 0.00 0.00
November 0.154483E+10 0.149357E+10 0.166978E+10 0.876615E+09 0.793160E+09 0.00 0.00
December 0.141021E+10 0.201250E+10 0.164728E+10 0.106378E+10 0.583500E+09 0.00 0.00
               
Annual Sum or Average 0.233132E+11 0.131171E+11 0.213890E+11 0.865408E+10 0.127349E+11 0.00 0.00
Minimum of Months 0.124065E+10 0.138008E+09 0.154719E+10 0.184741E+09 0.583500E+09 0.00 0.00
Maximum of Months 0.288081E+10 0.225370E+10 0.248786E+10 0.136754E+10 0.142002E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 1.17 -0.7 -4.4 5.65 -10.4 36.91 88.07 0.05
February -0.2 -2.6 -7.5 5.07 -13.4 46.98 136.68 0.04
March 5.59 3.43 0.29 5.58 -4.1 68.24 153.73 0.03
April 10.94 8.00 4.75 4.99 0.53 82.64 161.98 0.05
May 16.05 12.31 9.14 4.42 7.77 109.28 173.60 0.03
June 21.71 18.08 15.84 4.92 13.23 112.36 186.51 0.01
July 25.05 21.76 20.26 4.06 17.39 114.46 172.96 0.02
August 24.79 19.84 17.14 4.19 14.42 95.56 226.16 0.00
September 19.96 15.96 13.24 3.91 10.59 73.65 166.08 0.03
October 14.02 11.03 7.95 4.86 2.64 61.34 179.75 0.00
November 7.31 4.98 2.14 5.60 -4.0 48.23 90.71 0.03
December 3.33 0.91 -2.8 5.64 -8.5 30.23 98.59 0.04
                 
Annual Sum or Average 12.55 9.49 6.43 4.91 2.28 73.48 153.05 0.03
Minimum of Months -0.2 -2.6 -7.5 3.91 -13.4 30.23 88.07 0.00
Maximum of Months 25.05 21.76 20.26 5.65 17.39 114.46 226.16 0.05



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 12.20 24-JAN-12:20 11.81 11.50 1.00 8.15 93.67 0.00
February 10.00 20-FEB-11:00 4.36 -3.3 2.60 -3.9 151.50 540.00
March 22.20 27-MAR-15:00 16.34 12.80 6.70 11.65 136.50 590.00
April 26.70 07-APR-12:00 16.40 9.40 6.20 11.65 179.00 713.50
May 30.00 30-MAY-12:00 18.00 10.60 5.20 17.39 233.50 730.00
June 36.70 19-JUN-11:00 24.28 19.40 5.20 24.83 185.00 771.50
July 33.90 07-JUL-11:00 23.31 18.90 3.60 23.82 331.00 570.00
August 33.90 24-AUG-14:00 20.23 12.80 8.80 21.61 240.00 432.00
September 31.10 01-SEP-13:00 17.34 8.30 4.60 18.46 182.00 662.00
October 25.00 04-OCT-12:00 18.54 15.00 5.20 11.27 171.50 695.00
November 17.80 04-NOV-12:20 12.57 8.50 3.60 6.15 182.50 595.67
December 12.20 17-DEC-12:20 4.65 -6.1 4.27 -4.7 53.17 801.67
                 
Annual Sum or Average                
Minimum of Months 10.00   4.36 -6.1 1.00 -4.7 53.17 0.00
Maximum of Months 36.70   24.28 19.40 8.80 24.83 331.00 801.67



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -12.2 02-JAN-04:00 -13.6 -19.4 2.60 -30.7 0.00 0.00
February -13.9 06-FEB-02:00 -15.3 -22.8 7.20 -34.1 0.00 0.00
March -5.0 23-MAR-03:00 -7.6 -14.4 1.50 -23.9 0.00 0.00
April 2.20 01-APR-03:00 0.57 -1.7 3.10 -6.6 0.00 0.00
May 6.10 01-MAY-04:00 4.33 2.20 3.60 -9.7 25.50 0.00
June 13.30 03-JUN-02:00 9.35 5.60 4.60 -2.1 0.00 0.00
July 18.30 02-JUL-02:00 17.54 17.20 0.00 5.33 0.00 0.00
August 15.00 08-AUG-04:00 12.47 10.60 3.10 3.06 0.00 0.00
September 10.00 24-SEP-05:00 8.56 7.20 2.60 -3.4 18.50 158.50
October 2.20 09-OCT-03:00 1.71 1.10 0.00 -13.7 0.00 0.00
November -4.4 24-NOV-05:00 -6.2 -10.0 1.50 -19.7 0.00 0.00
December -8.3 31-DEC-23:00 -10.6 -18.9 9.30 -26.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -13.9   -15.3 -22.8 0.00 -34.1 0.00 0.00
Maximum of Months 18.30   17.54 17.20 9.30 5.33 25.50 158.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 11.93 24-JAN-11:00 12.20 11.70 1.50 8.15 103.00 0.00
February 6.67 28-FEB-09:00 7.20 6.10 4.10 2.01 101.50 0.00
March 16.99 27-MAR-12:00 20.60 15.00 3.60 10.50 295.50 565.50
April 17.70 09-APR-10:00 21.70 15.60 4.10 14.84 244.50 281.50
May 20.43 31-MAY-12:00 26.10 17.80 4.10 17.03 214.00 772.00
June 24.96 15-JUN-11:00 31.10 22.80 5.20 22.47 380.00 460.00
July 26.10 08-JUL-11:00 32.20 23.90 5.20 22.47 354.00 501.50
August 25.84 03-AUG-13:00 30.00 24.40 6.20 20.57 298.00 500.00
September 23.57 07-SEP-13:00 27.20 22.20 6.20 15.02 148.00 730.50
October 19.76 25-OCT-10:00 25.00 17.20 7.70 14.84 189.00 308.50
November 16.10 10-NOV-07:00 16.10 16.10 8.20 12.98 71.50 0.00
December 10.26 25-DEC-08:00 10.60 10.00 3.60 6.15 43.00 0.00
                 
Annual Sum or Average                
Minimum of Months 6.67   7.20 6.10 1.50 2.01 43.00 0.00
Maximum of Months 26.10   32.20 24.40 8.20 22.47 380.00 772.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 11.70 18-JAN-15:00 12.20 11.93 14.90 8.15 22.00 2.00
February 6.10 28-FEB-10:20 7.03 6.58 3.43 1.87 109.83 0.00
March 15.00 27-MAR-12:20 18.00 16.18 3.93 10.11 271.83 611.17
April 15.60 09-APR-10:00 21.70 17.70 4.10 14.84 244.50 281.50
May 18.00 18-MAY-09:00 18.00 18.00 4.60 15.39 265.50 12.00
June 22.80 15-JUN-11:00 31.10 24.96 5.20 22.47 380.00 460.00
July 24.40 09-JUL-07:00 27.20 25.17 2.10 15.39 195.00 504.00
August 25.00 03-AUG-19:00 26.10 25.32 5.70 19.35 0.00 0.00
September 22.20 07-SEP-13:00 27.20 23.57 6.20 15.02 148.00 730.50
October 18.30 05-OCT-18:00 19.40 18.62 7.70 6.55 0.00 0.00
November 16.10 10-NOV-07:00 16.10 16.10 8.20 12.98 71.50 0.00
December 10.00 25-DEC-08:00 10.60 10.26 3.60 6.15 43.00 0.00
                 
Annual Sum or Average                
Minimum of Months 6.10   7.03 6.58 2.10 1.87 0.00 0.00
Maximum of Months 25.00   31.10 25.32 14.90 22.47 380.00 730.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 10.03 13.58 0.00
February 18.00 13.00 16.00 9.54 21.42 0.00
March 18.00 13.00 16.00 10.65 30.29 0.00
April 18.00 13.00 16.00 13.15 37.02 0.00
May 18.00 13.00 16.00 16.36 45.86 0.00
June 18.00 13.00 16.00 19.42 49.74 0.00
July 18.00 13.00 16.00 21.50 48.12 0.00
August 18.00 13.00 16.00 22.05 49.54 0.00
September 18.00 13.00 16.00 20.89 34.71 0.00
October 18.00 13.00 16.00 18.36 29.93 0.00
November 18.00 13.00 16.00 15.14 17.00 0.00
December 18.00 13.00 16.00 12.10 12.41 0.00
             
Annual Sum or Average 18.00 13.00 16.00 15.80 32.53 0.00
Minimum of Months 18.00 13.00 16.00 9.54 12.41 0.00
Maximum of Months 18.00 13.00 16.00 22.05 49.74 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770511E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -162323089.7 81.21 0.00 0.00
February 0.696260E+10 -0.681596E+10 0.00 0.00 672.00 0.00 -146634554.5 81.21 0.00 0.00
March 0.770324E+10 -0.754148E+10 0.00 0.00 744.00 0.00 -161759541.7 81.21 0.00 0.00
April 0.746509E+10 -0.730859E+10 0.00 0.00 720.00 0.00 -156499009.9 81.21 0.00 0.00
May 0.770447E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -161680925.5 81.21 0.00 0.00
June 0.745685E+10 -0.730052E+10 0.00 0.00 720.00 0.00 -156323209.5 81.21 0.00 0.00
July 0.771233E+10 -0.755085E+10 0.00 0.00 744.00 0.00 -161486406.6 81.21 0.00 0.00
August 0.770426E+10 -0.754280E+10 0.00 0.00 744.00 0.00 -161452484.2 81.21 0.00 0.00
September 0.746634E+10 -0.730993E+10 0.00 0.00 720.00 0.00 -156414477.2 81.21 0.00 0.00
October 0.770312E+10 -0.754144E+10 0.00 0.00 744.00 0.00 -161687216.5 81.21 0.00 0.00
November 0.744899E+10 -0.729242E+10 0.00 0.00 720.00 0.00 -156569392.4 81.21 0.00 0.00
December 0.771297E+10 -0.755086E+10 0.00 0.00 744.00 0.00 -162103272.8 81.21 0.00 0.00
                     
Annual Sum or Average 0.907454E+11 -0.888404E+11 0.00 0.00 8760.00 0.00 -0.190493E+10 81.21 0.00 0.00
Minimum of Months 0.696260E+10 -0.755086E+10 0.00 0.00 672.00 0.00 -162323089.7 81.21 0.00 0.00
Maximum of Months 0.771297E+10 -0.681596E+10 0.00 0.00 744.00 0.00 -146634554.5 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.122409E+12 -0.120669E+12 0.00 0.00 744.00 0.00 -0.174051E+10 81.27 0.00 0.00
February 0.111344E+12 -0.109763E+12 0.00 0.00 672.00 0.00 -0.158092E+10 81.27 0.00 0.00
March 0.121352E+12 -0.119595E+12 0.00 0.00 744.00 0.00 -0.175716E+10 81.27 0.00 0.00
April 0.113316E+12 -0.111608E+12 0.00 0.00 720.00 0.00 -0.170810E+10 81.26 0.00 0.00
May 0.111635E+12 -0.109865E+12 0.00 0.00 744.00 0.00 -0.177047E+10 81.25 0.00 0.00
June 0.102994E+12 -0.101291E+12 0.00 0.00 720.00 0.00 -0.170304E+10 81.26 0.00 0.00
July 0.102882E+12 -0.101134E+12 0.00 0.00 744.00 0.00 -0.174786E+10 81.25 0.00 0.00
August 0.101948E+12 -0.100211E+12 0.00 0.00 744.00 0.00 -0.173707E+10 81.24 0.00 0.00
September 0.100547E+12 -0.988729E+11 0.00 0.00 720.00 0.00 -0.167440E+10 81.24 0.00 0.00
October 0.108194E+12 -0.106466E+12 0.00 0.00 744.00 0.00 -0.172806E+10 81.25 0.00 0.00
November 0.109993E+12 -0.108321E+12 0.00 0.00 720.00 0.00 -0.167218E+10 81.25 0.00 0.00
December 0.118843E+12 -0.117112E+12 0.00 0.00 744.00 0.00 -0.173081E+10 81.26 0.00 0.00
                     
Annual Sum or Average 0.132546E+13 -0.130491E+13 0.00 0.00 8760.00 0.00 -0.205506E+11 81.25 0.00 0.00
Minimum of Months 0.100547E+12 -0.120669E+12 0.00 0.00 672.00 0.00 -0.177047E+10 81.24 0.00 0.00
Maximum of Months 0.122409E+12 -0.988729E+11 0.00 0.00 744.00 0.00 -0.158092E+10 81.27 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.730145E+11 -0.715330E+11 0.00 0.00 744.00 0.00 -0.148155E+10 58.98 0.00 0.00
February 0.666208E+11 -0.652704E+11 0.00 0.00 672.00 0.00 -0.135034E+10 58.98 0.00 0.00
March 0.721896E+11 -0.706847E+11 0.00 0.00 744.00 0.00 -0.150481E+10 58.98 0.00 0.00
April 0.663049E+11 -0.648378E+11 0.00 0.00 720.00 0.00 -0.146705E+10 58.98 0.00 0.00
May 0.638333E+11 -0.623095E+11 0.00 0.00 744.00 0.00 -0.152378E+10 58.98 0.00 0.00
June 0.574448E+11 -0.559847E+11 0.00 0.00 720.00 0.00 -0.146008E+10 58.98 0.00 0.00
July 0.562410E+11 -0.547486E+11 0.00 0.00 744.00 0.00 -0.149248E+10 58.98 0.00 0.00
August 0.554849E+11 -0.540069E+11 0.00 0.00 744.00 0.00 -0.147798E+10 58.98 0.00 0.00
September 0.552932E+11 -0.538724E+11 0.00 0.00 720.00 0.00 -0.142082E+10 58.98 0.00 0.00
October 0.608114E+11 -0.593462E+11 0.00 0.00 744.00 0.00 -0.146522E+10 58.98 0.00 0.00
November 0.634053E+11 -0.619877E+11 0.00 0.00 720.00 0.00 -0.141760E+10 58.98 0.00 0.00
December 0.699672E+11 -0.684987E+11 0.00 0.00 744.00 0.00 -0.146847E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.760611E+12 -0.743081E+12 0.00 0.00 8760.00 0.00 -0.175302E+11 58.98 0.00 0.00
Minimum of Months 0.552932E+11 -0.715330E+11 0.00 0.00 672.00 0.00 -0.152378E+10 58.98 0.00 0.00
Maximum of Months 0.730145E+11 -0.538724E+11 0.00 0.00 744.00 0.00 -0.135034E+10 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.93 0.93 01-JAN-07:49 5752.10 37.03 197.00 248.83 2745.59 33.81 188.00 189.67
February 216.00 0.93 0.93 01-FEB-07:40 8418.83 37.65 208.33 260.00 1191.73 27.31 206.83 227.33
March 275.00 0.93 0.93 01-MAR-06:00 4067.36 25.80 163.50 328.83 736.97 22.68 209.67 263.67
April 261.17 0.93 0.93 01-APR-06:10 1445.62 20.50 84.83 345.67 588.98 22.24 203.33 281.50
May 372.00 0.93 0.93 01-MAY-05:40 1308.04 20.22 124.17 397.67 519.20 21.93 243.67 320.50
June 351.83 0.93 0.93 01-JUN-05:10 1240.43 20.13 92.17 387.67 500.41 21.87 250.33 321.67
July 365.17 0.93 0.93 01-JUL-05:19 1383.00 20.29 124.83 397.00 547.52 22.02 268.67 325.67
August 389.17 0.93 0.93 01-AUG-05:40 1480.96 20.57 155.50 375.17 599.15 22.29 308.00 325.17
September 285.33 0.93 0.93 01-SEP-05:00 1648.08 20.68 98.17 329.17 665.12 22.45 236.50 276.67
October 305.50 0.93 0.93 01-OCT-14:39 8133.96 35.73 284.00 310.17 1018.57 25.01 277.33 282.33
November 240.83 0.93 0.93 01-NOV-06:49 5706.93 36.47 235.00 260.17 1514.66 29.94 223.67 229.67
December 211.17 0.93 0.93 01-DEC-07:30 5342.60 38.01 208.00 248.83 4126.65 37.99 207.17 208.50
                         
Annual Sum or Average 3472.67 0.93     3433.74 26.38 1975.50 3889.17 1065.78 24.92 2823.17 3252.33
Minimum of Months 199.50 0.93 0.93   1240.43 20.13 84.83 248.83 500.41 21.87 188.00 189.67
Maximum of Months 389.17 0.93 0.93   8418.83 38.01 284.00 397.67 4126.65 37.99 308.00 325.67



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.62 0.61 01-JAN-07:40 6185.22 37.09 197.00 260.50 3179.37 33.77 190.17 220.83
February 216.00 0.62 0.61 01-FEB-07:40 8914.43 37.73 208.33 269.33 1686.90 27.00 195.50 246.67
March 275.00 0.62 0.61 01-MAR-06:49 4472.40 25.93 155.50 337.50 1140.36 22.70 221.33 307.50
April 261.17 0.62 0.61 01-APR-05:00 1758.70 20.81 91.33 358.17 901.28 22.39 240.33 320.67
May 372.00 0.62 0.61 01-MAY-05:40 1533.17 20.81 156.00 412.00 743.54 22.34 273.83 372.33
June 351.83 0.62 0.61 01-JUN-04:00 1455.71 20.73 155.33 404.83 714.97 22.28 283.83 362.00
July 365.17 0.62 0.61 01-JUL-05:10 1612.27 20.87 171.17 414.00 775.94 22.42 296.83 368.17
August 389.17 0.63 0.61 01-AUG-05:19 1770.11 20.95 183.50 385.00 887.46 22.51 321.33 358.67
September 285.33 0.62 0.61 01-SEP-05:00 2009.72 20.86 108.00 340.50 1025.77 22.49 236.83 308.00
October 305.50 0.62 0.61 01-OCT-14:39 8629.00 35.78 273.50 317.33 1512.06 24.86 283.67 300.00
November 240.83 0.62 0.61 01-NOV-06:49 6110.78 36.55 235.17 267.83 1914.92 29.86 229.17 250.33
December 211.17 0.63 0.61 01-DEC-07:30 5773.44 38.07 208.00 256.67 4555.57 38.00 204.67 233.67
                         
Annual Sum or Average 3472.67 0.62     3774.98 26.68 2142.83 4023.67 1405.92 25.05 2977.50 3648.83
Minimum of Months 199.50 0.62 0.61   1455.71 20.73 91.33 256.67 714.97 22.28 190.17 220.83
Maximum of Months 389.17 0.63 0.61   8914.43 38.07 273.50 414.00 4555.57 38.00 321.33 372.33



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.82 0.80 01-JAN-08:09 434.52 15.20 0.00 231.83 209.59 18.60 0.00 116.83
February 216.00 0.82 0.80 01-FEB-08:09 446.61 15.89 0.00 247.33 228.99 19.35 0.00 155.67
March 275.00 0.81 0.80 01-MAR-06:00 612.35 17.24 0.00 325.83 295.33 20.48 30.00 242.17
April 261.17 0.81 0.80 01-APR-06:10 674.70 17.83 0.00 356.67 325.40 21.05 87.83 300.83
May 372.00 0.80 0.80 01-MAY-05:40 926.59 18.52 0.00 418.17 413.94 22.41 250.83 373.67
June 351.83 0.80 0.80 01-JUN-04:00 1028.76 19.64 29.00 410.33 447.19 23.45 264.83 376.17
July 365.17 0.80 0.80 01-JUL-04:00 1033.92 18.58 0.00 419.83 446.06 23.09 271.67 377.17
August 389.17 0.81 0.80 01-AUG-05:10 819.58 18.27 0.00 387.83 379.21 21.49 226.00 356.17
September 285.33 0.81 0.80 01-SEP-05:00 618.25 17.45 0.00 334.17 302.12 20.70 53.67 271.67
October 305.50 0.81 0.80 01-OCT-14:39 559.22 17.01 0.00 302.17 286.58 20.37 0.17 246.33
November 240.83 0.81 0.80 01-NOV-06:00 488.27 15.75 0.00 248.83 228.94 19.07 0.00 156.17
December 211.17 0.83 0.80 01-DEC-07:00 344.08 14.30 0.00 219.50 172.97 17.86 0.00 73.83
                         
Annual Sum or Average 3472.67 0.81     710.81 17.43 29.00 3902.50 329.62 20.99 1185.00 3046.67
Minimum of Months 199.50 0.80 0.80   344.08 14.30 0.00 219.50 172.97 17.86 0.00 73.83
Maximum of Months 389.17 0.83 0.80   1033.92 19.64 29.00 419.83 447.19 23.45 271.67 377.17



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.82 0.80 01-JAN-08:09 434.52 15.20 0.00 231.83 209.59 18.60 0.00 116.83
February 216.00 0.82 0.80 01-FEB-08:09 446.61 15.89 0.00 247.33 228.99 19.35 0.00 155.67
March 275.00 0.81 0.80 01-MAR-06:00 612.35 17.24 0.00 325.83 295.33 20.48 30.00 242.17
April 261.17 0.81 0.80 01-APR-06:10 674.70 17.83 0.00 356.67 325.40 21.05 87.83 300.83
May 372.00 0.80 0.80 01-MAY-05:40 926.59 18.52 0.00 418.17 413.94 22.41 250.83 373.67
June 351.83 0.80 0.80 01-JUN-04:00 1028.76 19.64 29.00 410.33 447.19 23.45 264.83 376.17
July 365.17 0.80 0.80 01-JUL-04:00 1033.92 18.58 0.00 419.83 446.06 23.09 271.67 377.17
August 389.17 0.81 0.80 01-AUG-05:10 819.58 18.27 0.00 387.83 379.21 21.49 225.83 356.17
September 285.33 0.81 0.80 01-SEP-05:00 618.25 17.45 0.00 334.17 302.12 20.70 53.67 271.67
October 305.50 0.81 0.80 01-OCT-14:39 559.22 17.01 0.00 302.17 286.58 20.37 0.17 246.33
November 240.83 0.81 0.80 01-NOV-06:00 488.27 15.75 0.00 248.83 228.94 19.07 0.00 156.17
December 211.17 0.83 0.80 01-DEC-07:00 344.08 14.30 0.00 219.50 172.97 17.86 0.00 73.83
                         
Annual Sum or Average 3472.67 0.81     710.81 17.43 29.00 3902.50 329.62 20.99 1184.83 3046.67
Minimum of Months 199.50 0.80 0.80   344.08 14.30 0.00 219.50 172.97 17.86 0.00 73.83
Maximum of Months 389.17 0.83 0.80   1033.92 19.64 29.00 419.83 447.19 23.45 271.67 377.17



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.451206E+11 143711.29 19-JAN-22:40 0.00 0.00 0.00 0.00 0.00
February 0.419631E+11 141320.17 18-FEB-14:43 0.00 0.00 0.00 0.00 0.00
March 0.257380E+11 148754.29 05-MAR-07:53 0.00 0.00 0.00 0.00 0.00
April 0.244793E+11 151315.44 13-APR-19:10 0.00 0.00 0.00 0.00 0.00
May 0.743606E+10 122080.52 15-MAY-04:30 0.00 0.00 0.00 0.00 0.00
June 0.203912E+09 17085.42 01-JUN-13:47 0.00 0.00 0.00 0.00 0.00
July 17396389.89 12585.75 11-JUL-18:03 0.00 0.00 0.00 0.00 0.00
August 0.257035E+09 30117.18 24-AUG-18:50 0.00 0.00 0.00 0.00 0.00
September 0.148309E+10 58663.17 24-SEP-05:34 0.00 0.00 0.00 0.00 0.00
October 0.136507E+11 147684.13 26-OCT-23:27 0.00 0.00 0.00 0.00 0.00
November 0.293646E+11 148235.34 13-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.189447E+11 139206.66 04-DEC-08:45 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.208658E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 17396389.89 12585.75   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.451206E+11 151315.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.320753E+10 2777.67 02-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.244292E+10 2717.04 06-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.156621E+10 2318.77 27-MAR-04:10 0.00 0.00 0.00 0.00 0.00
April 0.984444E+09 2482.26 20-APR-08:04 0.00 0.00 0.00 0.00 0.00
May 0.259192E+09 1801.97 04-MAY-04:48 0.00 0.00 0.00 0.00 0.00
June 253567.20 82.65 07-JUN-04:00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 50355134.29 1516.93 24-SEP-05:30 0.00 0.00 0.00 0.00 0.00
October 0.164643E+09 2071.10 27-OCT-06:59 0.00 0.00 0.00 0.00 0.00
November 0.151000E+10 2410.80 14-NOV-20:31 0.00 0.00 0.00 0.00 0.00
December 0.253822E+10 2346.44 25-DEC-05:55 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.127238E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.320753E+10 2777.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.195545E+09 844.70 15-JAN-11:36 0.00 0.00 0.00 0.00 0.00
February 0.129595E+09 569.88 06-FEB-15:00 0.00 0.00 0.00 0.00 0.00
March 9127010.60 335.57 17-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 1913415.50 147.11 21-APR-14:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 13295696.98 370.98 28-NOV-14:40 0.00 0.00 0.00 0.00 0.00
December 73974024.84 458.42 12-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.423450E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.195545E+09 844.70   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.143481E+10 1425.52 02-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 0.133579E+10 1415.59 01-FEB-16:47 0.00 0.00 0.00 0.00 0.00
March 0.459499E+09 1311.31 23-MAR-16:47 0.00 0.00 0.00 0.00 0.00
April 99413085.77 1166.15 03-APR-09:43 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.344333E+09 910.04 24-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.876457E+09 1249.96 20-DEC-16:08 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.455031E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.143481E+10 1425.52   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.108559E+10 871.09 02-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 0.990224E+09 857.62 06-FEB-10:05 0.00 0.00 0.00 0.00 0.00
March 0.394866E+09 680.00 23-MAR-16:47 0.00 0.00 0.00 0.00 0.00
April 0.108553E+09 650.80 03-APR-09:43 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.306247E+09 1051.14 30-NOV-13:53 0.00 0.00 0.00 0.00 0.00
December 0.734203E+09 637.10 31-DEC-18:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.361969E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.108559E+10 1051.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.392495E+09 4253.37 24-JAN-04:35 0.00 0.00 0.00 0.00 0.00
February 0.361369E+09 5526.79 18-FEB-16:28 0.00 0.00 0.00 0.00 0.00
March 0.232537E+09 9144.40 28-MAR-02:38 0.00 0.00 0.00 0.00 0.00
April 0.161947E+09 9299.21 29-APR-04:50 0.00 0.00 0.00 0.00 0.00
May 73965705.13 7185.86 17-MAY-03:12 0.00 0.00 0.00 0.00 0.00
June 1810046.05 648.23 03-JUN-04:50 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 26780554.48 6336.44 30-SEP-03:25 0.00 0.00 0.00 0.00 0.00
October 0.112756E+09 9723.22 17-OCT-03:20 0.00 0.00 0.00 0.00 0.00
November 0.213916E+09 10466.88 09-NOV-02:35 0.00 0.00 0.00 0.00 0.00
December 0.300725E+09 3039.90 05-DEC-02:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.187830E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.392495E+09 10466.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.207649E+10 7394.74 15-JAN-11:36 0.00 0.00 0.00 0.00 0.00
February 0.109249E+10 5507.71 28-FEB-09:59 0.00 0.00 0.00 0.00 0.00
March 0.543898E+09 6585.54 04-MAR-16:05 0.00 0.00 0.00 0.00 0.00
April 0.296553E+09 5046.89 21-APR-10:37 0.00 0.00 0.00 0.00 0.00
May 39768712.39 1989.18 04-MAY-10:35 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 194643.02 269.98 26-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 3130999.69 927.68 31-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.449817E+09 4452.70 13-NOV-10:04 0.00 0.00 0.00 0.00 0.00
December 0.130555E+10 4985.07 11-DEC-14:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.580789E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.207649E+10 7394.74   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.111182E+10 10901.99 03-JAN-10:00 0.00 0.00 0.00 0.00 0.00
February 0.433842E+09 6668.21 27-FEB-14:50 0.00 0.00 0.00 0.00 0.00
March 25391456.53 3375.06 17-MAR-12:30 0.00 0.00 0.00 0.00 0.00
April 256935.62 284.84 21-APR-14:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 28608658.17 5391.71 28-NOV-14:45 0.00 0.00 0.00 0.00 0.00
December 0.344412E+09 6202.10 11-DEC-15:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.194433E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.111182E+10 10901.99   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.803073E+10 9383.63 15-JAN-11:39 0.00 0.00 0.00 0.00 0.00
February 0.591123E+10 7887.56 01-FEB-17:02 0.00 0.00 0.00 0.00 0.00
March 0.159045E+10 5429.39 17-MAR-12:30 0.00 0.00 0.00 0.00 0.00
April 0.420387E+09 4835.37 21-APR-14:39 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.234427E+10 10993.31 30-NOV-13:53 0.00 0.00 0.00 0.00 0.00
December 0.553713E+10 7485.51 20-DEC-16:08 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.238342E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.803073E+10 10993.31   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.526884E+10 5200.17 02-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.441666E+10 5139.95 06-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.162138E+10 3271.57 23-MAR-06:05 0.00 0.00 0.00 0.00 0.00
April 0.483439E+09 3838.42 20-APR-08:04 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 18901321.62 1126.83 29-OCT-05:00 0.00 0.00 0.00 0.00 0.00
November 0.170120E+10 3685.41 17-NOV-06:15 0.00 0.00 0.00 0.00 0.00
December 0.380499E+10 3824.23 20-DEC-16:08 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.173154E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.526884E+10 5200.17   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 185941.57 619.81 02-OCT-02:10 0.00 0.00 0.00 0.00 0.00
November 286129.74 953.77 09-NOV-02:35 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 472071.31     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 286129.74 953.77   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.472799E+10 11056.22 02-JAN-09:00 0.00 0.00 0.00 0.00 0.00
February 0.483628E+10 12245.64 06-FEB-09:00 0.00 0.00 0.00 0.00 0.00
March 0.539191E+09 4390.40 23-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 3170.73 0.39 25-APR-12:10 0.00 0.00 0.00 0.00 0.00
May 17171.13 0.39 26-MAY-17:00 0.00 0.00 0.00 0.00 0.00
June 21241.03 0.39 27-JUN-10:15 0.00 0.00 0.00 0.00 0.00
July 12464.12 0.39 20-JUL-04:40 0.00 0.00 0.00 0.00 0.00
August 21984.90 10.44 09-AUG-04:40 0.00 0.00 0.00 0.00 0.00
September 16076.36 0.39 18-SEP-07:20 0.00 0.00 0.00 0.00 0.00
October 23495.34 27.40 21-OCT-11:40 0.00 0.00 0.00 0.00 0.00
November 0.434607E+09 4401.19 24-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.903161E+09 7377.47 31-DEC-24:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.114414E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3170.73 0.39   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.483628E+10 12245.64   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.576450E+10 11205.43 14-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.475345E+10 11204.63 07-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.237140E+10 11022.52 22-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.106289E+10 10753.64 01-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 92758382.52 3608.33 29-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 4088106.50 3447.62 22-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 3811446.45 2361.73 27-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 3871087.06 2356.11 06-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 13068211.19 2901.89 23-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 0.216190E+09 6043.23 27-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.265947E+10 11011.29 25-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.462215E+10 11165.90 31-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.215676E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3811446.45 2356.11   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.576450E+10 11205.43   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.678757E+10 11158.53 14-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.601679E+10 11157.72 07-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.301119E+10 11013.99 22-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.124510E+10 10724.03 03-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.100954E+09 3506.63 30-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 4062819.51 3617.68 04-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 3391247.41 2559.94 27-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 4105766.73 2524.61 10-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 17921684.15 3187.91 23-SEP-15:04 0.00 0.00 0.00 0.00 0.00
October 0.426075E+09 10541.51 29-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.342057E+10 11012.41 24-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.570195E+10 11119.07 31-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.267397E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3391247.41 2524.61   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.678757E+10 11158.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.946168E+10 21751.32 02-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 0.307108E+10 18209.79 07-FEB-06:00 0.00 0.00 0.00 0.00 0.00
March 0.353112E+09 11005.35 01-MAR-06:00 0.00 0.00 0.00 0.00 0.00
April 32259049.39 2975.17 02-APR-05:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.189859E+09 7092.45 29-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.401922E+10 16610.67 31-DEC-06:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.171272E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.946168E+10 21751.32   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.270395E+11 62538.11 14-JAN-16:02 0.00 0.00 0.00 0.00 0.00
February 0.262231E+11 62633.94 06-FEB-16:01 0.00 0.00 0.00 0.00 0.00
March 0.102586E+11 60815.13 17-MAR-15:01 0.00 0.00 0.00 0.00 0.00
April 0.223597E+10 59067.39 03-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 93418546.47 35491.48 03-MAY-15:07 0.00 0.00 0.00 0.00 0.00
June 26129771.42 20506.47 20-JUN-08:07 0.00 0.00 0.00 0.00 0.00
July 14763752.54 14904.89 14-JUL-08:07 0.00 0.00 0.00 0.00 0.00
August 30821307.55 21586.66 30-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 67119227.34 24503.28 24-SEP-15:05 0.00 0.00 0.00 0.00 0.00
October 0.903567E+09 41247.86 21-OCT-18:03 0.00 0.00 0.00 0.00 0.00
November 0.955783E+10 60907.33 22-NOV-16:01 0.00 0.00 0.00 0.00 0.00
December 0.209892E+11 61840.73 31-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.974400E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 14763752.54 14904.89   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.270395E+11 62633.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.572446E+10 10939.10 14-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.464029E+10 10936.88 06-FEB-19:01 0.00 0.00 0.00 0.00 0.00
March 0.249591E+10 10758.87 17-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.106950E+10 10489.58 01-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.103131E+09 3169.36 05-MAY-15:04 0.00 0.00 0.00 0.00 0.00
June 2350812.79 2131.20 17-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 902282.40 2304.59 31-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 311282.30 1668.41 06-AUG-18:05 0.00 0.00 0.00 0.00 0.00
September 11109487.82 2835.76 23-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 0.236540E+09 3721.80 31-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.251017E+10 10749.84 25-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.455824E+10 10900.33 31-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.213529E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 311282.30 1668.41   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.572446E+10 10939.10   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.673488E+10 10891.37 14-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.587512E+10 10890.48 07-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.314864E+10 10712.08 17-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.123744E+10 10451.95 01-APR-15:01 0.00 0.00 0.00 0.00 0.00
May 0.115150E+09 3164.43 04-MAY-08:63 0.00 0.00 0.00 0.00 0.00
June 1876559.57 2166.57 17-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 769852.61 2107.48 31-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 239544.80 1601.32 06-AUG-18:05 0.00 0.00 0.00 0.00 0.00
September 13785499.77 2797.59 23-SEP-15:04 0.00 0.00 0.00 0.00 0.00
October 0.439918E+09 7351.56 31-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.316306E+10 10703.07 25-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.555806E+10 10852.76 31-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.262889E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 239544.80 1601.32   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.673488E+10 10891.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.197079E+10 3277.45 14-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.165315E+10 3277.20 07-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.881282E+09 3235.07 22-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.430090E+09 3173.15 01-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 60404155.30 1372.58 04-MAY-08:63 0.00 0.00 0.00 0.00 0.00
June 1233686.84 860.29 26-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 1103788.24 645.82 01-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 1031323.22 603.31 27-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 13036108.62 971.66 23-SEP-15:04 0.00 0.00 0.00 0.00 0.00
October 0.142036E+09 3091.24 27-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.991156E+09 3234.61 24-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.162046E+10 3265.78 31-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.776577E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1031323.22 603.31   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.197079E+10 3277.45   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.228383E+10 3260.34 14-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.203379E+10 3260.06 07-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.108439E+10 3218.18 22-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.494085E+09 3158.88 01-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 65138126.88 1545.87 01-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 1252861.82 851.76 22-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 1056708.90 651.11 28-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 1023943.93 603.96 27-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 20380275.78 980.46 23-SEP-15:04 0.00 0.00 0.00 0.00 0.00
October 0.244808E+09 3118.90 29-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.124466E+10 3217.73 24-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.195673E+10 3248.71 31-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.943114E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1023943.93 603.96   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.228383E+10 3260.34   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.606947E+10 15435.43 14-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.444326E+10 15432.67 06-FEB-19:01 0.00 0.00 0.00 0.00 0.00
March 0.249267E+10 15181.60 17-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.125425E+10 14778.94 21-APR-15:01 0.00 0.00 0.00 0.00 0.00
May 0.125537E+09 4104.38 03-MAY-15:07 0.00 0.00 0.00 0.00 0.00
June 6951275.61 5518.95 22-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 5639929.80 4171.08 12-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 4901540.46 4077.99 01-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 12725578.00 4218.73 23-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 0.157324E+09 5139.45 27-OCT-18:03 0.00 0.00 0.00 0.00 0.00
November 0.220542E+10 14999.52 25-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.449028E+10 15286.09 31-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.212684E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 4901540.46 4077.99   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.606947E+10 15435.43   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.227956E+09 0.227956E+09 28016.06 12-JAN-22:44 28016.06 0.01
February 0.00 0.00 0.207446E+09 0.207446E+09 14207.43 28-FEB-21:59 14207.43 0.00
March 0.00 0.00 0.355282E+10 0.352241E+10 130064.22 27-MAR-16:00 130064.22 0.03
April 0.00 0.00 0.341923E+11 0.339495E+11 210145.33 09-APR-10:50 140272.00 0.17
May 0.00 0.00 0.126129E+12 0.108859E+12 291468.15 31-MAY-17:17 164536.86 0.39
June 0.00 0.00 0.519220E+12 0.312368E+12 471839.16 24-JUN-17:12 175081.69 0.91
July 0.00 0.00 0.817177E+12 0.447467E+12 489707.03 27-JUL-21:00 216083.01 1.00
August 0.00 0.00 0.666890E+12 0.440176E+12 505719.26 11-AUG-22:00 216611.12 0.97
September 0.00 0.00 0.362678E+12 0.251324E+12 479564.58 13-SEP-21:00 219979.68 0.80
October 0.00 0.00 0.125687E+12 0.811245E+11 287726.08 05-OCT-19:10 145893.15 0.42
November 0.00 0.00 0.359820E+10 0.330487E+10 63869.16 04-NOV-10:50 63869.16 0.03
December 0.00 0.00 0.459344E+09 0.459344E+09 30701.03 03-DEC-20:45 30701.03 0.00
                 
Annual Sum or Average 0.00 0.00 0.266002E+13 0.168299E+13       0.40
Minimum of Months 0.00 0.00 0.207446E+09 0.207446E+09 14207.43   14207.43 0.00
Maximum of Months 0.00 0.00 0.817177E+12 0.447467E+12 505719.26   219979.68 1.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 0.697382E+09 0.589145E+09 32906.47 27-MAR-13:00 21433.80 0.02
April 0.00 0.00 0.634269E+10 0.616737E+10 40374.02 09-APR-11:00 24738.55 0.13
May 0.00 0.00 0.232123E+11 0.196119E+11 51821.69 31-MAY-17:06 27132.03 0.37
June 0.00 0.00 0.961906E+11 0.555096E+11 79002.93 24-JUN-17:25 27247.14 0.91
July 0.00 0.00 0.130865E+12 0.745834E+11 77079.99 23-JUL-14:20 28184.74 1.00
August 0.00 0.00 0.107294E+12 0.710766E+11 73614.51 06-AUG-07:17 27093.61 0.99
September 0.00 0.00 0.663363E+11 0.447544E+11 76059.89 22-SEP-17:30 26335.39 0.80
October 0.00 0.00 0.245200E+11 0.147924E+11 52292.02 24-OCT-14:00 26086.26 0.41
November 0.00 0.00 0.605095E+09 0.541138E+09 12351.77 10-NOV-08:00 4466.91 0.02
December 0.00 0.00 2300.65 2300.65 34.51 04-DEC-21:10 34.51 0.00
                 
Annual Sum or Average 0.00 0.00 0.456064E+12 0.287626E+12       0.39
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.130865E+12 0.745834E+11 79002.93   28184.74 1.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 42773173.65 41754485.90 13495.69 17-JAN-16:02 13495.69 0.00
February 0.00 0.00 0.116071E+09 0.116007E+09 13498.30 20-FEB-16:02 13498.30 0.00
March 0.00 0.00 0.814529E+09 0.756171E+09 14380.44 27-MAR-15:02 12847.47 0.03
April 0.00 0.00 0.213957E+10 0.156050E+10 14069.37 10-APR-15:02 14069.37 0.28
May 0.00 0.00 0.457448E+10 0.317833E+10 15534.62 18-MAY-15:02 11985.16 0.57
June 0.00 0.00 0.901664E+10 0.535116E+10 18881.22 27-JUN-08:62 11210.03 0.87
July 0.00 0.00 0.116257E+11 0.698409E+10 18931.26 30-JUL-08:62 11414.52 0.94
August 0.00 0.00 0.122018E+11 0.801563E+10 18177.60 27-AUG-08:62 11571.14 0.95
September 0.00 0.00 0.699127E+10 0.425074E+10 19228.94 22-SEP-18:02 9727.40 0.82
October 0.00 0.00 0.448725E+10 0.286025E+10 16562.04 05-OCT-18:02 11905.22 0.51
November 0.00 0.00 0.361447E+09 0.283646E+09 13696.27 03-NOV-15:02 13696.27 0.06
December 0.00 0.00 50638906.34 50096024.44 13434.86 17-DEC-16:01 13434.86 0.00
                 
Annual Sum or Average 0.00 0.00 0.524221E+11 0.334484E+11       0.42
Minimum of Months 0.00 0.00 42773173.65 41754485.90 13434.86   9727.40 0.00
Maximum of Months 0.00 0.00 0.122018E+11 0.801563E+10 19228.94   14069.37 0.95



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 8835162.58 7858671.06 7460.77 17-JAN-16:02 7460.77 0.00
February 0.00 0.00 18847774.53 18771190.86 12121.39 20-FEB-16:02 12121.39 0.00
March 0.00 0.00 0.364371E+09 0.328886E+09 13522.11 27-MAR-15:02 11823.21 0.02
April 0.00 0.00 0.147966E+10 0.104669E+10 13646.92 10-APR-15:02 13646.92 0.23
May 0.00 0.00 0.409612E+10 0.280103E+10 15027.43 18-MAY-15:02 11544.83 0.54
June 0.00 0.00 0.862299E+10 0.510424E+10 18286.21 27-JUN-08:62 10894.89 0.86
July 0.00 0.00 0.110843E+11 0.659705E+10 18380.73 30-JUL-08:62 11065.20 0.94
August 0.00 0.00 0.108497E+11 0.687075E+10 17679.79 27-AUG-08:62 11180.97 0.93
September 0.00 0.00 0.547440E+10 0.306363E+10 18637.62 22-SEP-18:02 9401.07 0.76
October 0.00 0.00 0.246441E+10 0.136717E+10 15492.37 05-OCT-18:02 11660.85 0.42
November 0.00 0.00 80861084.93 66294791.70 13285.58 03-NOV-15:02 13285.58 0.02
December 0.00 0.00 6128130.11 5630201.85 4554.49 17-DEC-19:03 4554.49 0.00
                 
Annual Sum or Average 0.00 0.00 0.445506E+11 0.272780E+11       0.40
Minimum of Months 0.00 0.00 6128130.11 5630201.85 4554.49   4554.49 0.00
Maximum of Months 0.00 0.00 0.110843E+11 0.687075E+10 18637.62   13646.92 0.94



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.123189E+09 0.123189E+09 7563.27 19-JAN-14:40 7563.27 0.00
February 0.00 0.00 0.814508E+09 0.814508E+09 17093.77 20-FEB-13:23 17093.77 0.00
March 0.00 0.00 0.258465E+10 0.257064E+10 30352.29 03-MAR-13:30 30352.29 0.00
April 0.00 0.00 0.601189E+10 0.452566E+10 39540.94 08-APR-12:30 28743.49 0.10
May 0.00 0.00 0.954621E+10 0.694827E+10 30973.35 31-MAY-12:30 21295.17 0.18
June 0.00 0.00 0.213051E+11 0.996113E+10 35298.71 19-JUN-12:50 27004.51 0.60
July 0.00 0.00 0.388565E+11 0.189783E+11 37812.58 08-JUL-12:10 29028.88 0.90
August 0.00 0.00 0.478974E+11 0.285532E+11 45562.27 16-AUG-14:50 34718.07 0.93
September 0.00 0.00 0.304814E+11 0.198099E+11 50077.34 30-SEP-12:30 44415.70 0.61
October 0.00 0.00 0.305560E+11 0.239748E+11 54513.71 04-OCT-12:00 46026.32 0.36
November 0.00 0.00 0.557547E+10 0.532256E+10 43745.13 02-NOV-12:50 43745.13 0.03
December 0.00 0.00 0.214862E+10 0.214862E+10 30820.04 17-DEC-13:40 30820.04 0.00
                 
Annual Sum or Average 0.00 0.00 0.195901E+12 0.123731E+12       0.31
Minimum of Months 0.00 0.00 0.123189E+09 0.123189E+09 7563.27   7563.27 0.00
Maximum of Months 0.00 0.00 0.478974E+11 0.285532E+11 54513.71   46026.32 0.93



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.120826E+09 79896470.38 43724.31 03-JAN-19:03 41427.88 0.01
February 0.00 0.00 54776754.09 54776754.09 40768.03 01-FEB-19:03 40768.03 0.00
March 0.00 0.00 0.152831E+10 0.109903E+10 62586.23 28-MAR-18:02 62586.23 0.06
April 0.00 0.00 0.999686E+10 0.625558E+10 68282.57 08-APR-15:02 68282.57 0.31
May 0.00 0.00 0.298417E+11 0.203196E+11 81769.96 31-MAY-18:02 64240.13 0.53
June 0.00 0.00 0.529524E+11 0.325324E+11 100007.38 27-JUN-08:62 53472.40 0.69
July 0.00 0.00 0.668572E+11 0.426349E+11 100848.22 30-JUL-08:62 56911.29 0.76
August 0.00 0.00 0.585720E+11 0.378434E+11 95871.55 06-AUG-08:62 55533.04 0.74
September 0.00 0.00 0.353832E+11 0.201302E+11 102790.43 22-SEP-18:02 47483.79 0.66
October 0.00 0.00 0.151273E+11 0.750615E+10 80764.54 05-OCT-18:02 54874.23 0.43
November 0.00 0.00 0.215206E+10 0.133799E+10 63042.10 05-NOV-08:62 63042.10 0.12
December 0.00 0.00 0.116948E+09 0.107466E+09 31687.95 29-DEC-19:04 31687.95 0.00
                 
Annual Sum or Average 0.00 0.00 0.272704E+12 0.169901E+12       0.36
Minimum of Months 0.00 0.00 54776754.09 54776754.09 31687.95   31687.95 0.00
Maximum of Months 0.00 0.00 0.668572E+11 0.426349E+11 102790.43   68282.57 0.76



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 81009770.63 80064473.08 10932.81 19-JAN-09:01 10932.81 0.00
February 0.00 0.00 0.127168E+09 0.127112E+09 11864.33 25-FEB-09:01 11864.33 0.00
March 0.00 0.00 0.671305E+09 0.634803E+09 12622.56 27-MAR-15:02 10929.56 0.03
April 0.00 0.00 0.215556E+10 0.153309E+10 12845.27 10-APR-15:02 12845.27 0.30
May 0.00 0.00 0.477714E+10 0.337386E+10 14480.16 31-MAY-18:02 11607.36 0.58
June 0.00 0.00 0.849075E+10 0.496273E+10 16811.57 21-JUN-18:02 10336.13 0.88
July 0.00 0.00 0.114733E+11 0.686222E+10 17021.36 30-JUL-08:62 10589.57 0.96
August 0.00 0.00 0.120791E+11 0.790925E+10 16208.78 06-AUG-08:62 10626.52 0.97
September 0.00 0.00 0.706971E+10 0.433513E+10 17558.22 22-SEP-18:02 8828.46 0.85
October 0.00 0.00 0.429773E+10 0.271408E+10 14997.85 05-OCT-18:02 10621.22 0.52
November 0.00 0.00 0.535234E+09 0.437506E+09 12504.88 03-NOV-15:02 12504.88 0.07
December 0.00 0.00 0.145900E+09 0.141820E+09 11794.94 17-DEC-09:01 11794.94 0.00
                 
Annual Sum or Average 0.00 0.00 0.519039E+11 0.331117E+11       0.43
Minimum of Months 0.00 0.00 81009770.63 80064473.08 10932.81   8828.46 0.00
Maximum of Months 0.00 0.00 0.120791E+11 0.790925E+10 17558.22   12845.27 0.97



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 9518493.76 8663992.49 4711.70 24-JAN-19:04 3527.17 0.00
February 0.00 0.00 18186644.54 18156523.46 9493.41 19-FEB-09:01 9493.41 0.00
March 0.00 0.00 0.252296E+09 0.233750E+09 11981.71 03-MAR-09:02 11981.71 0.01
April 0.00 0.00 0.144536E+10 0.990257E+09 12482.92 09-APR-15:02 11365.85 0.26
May 0.00 0.00 0.425831E+10 0.295713E+10 13857.10 18-MAY-15:02 10772.05 0.57
June 0.00 0.00 0.807934E+10 0.470656E+10 16302.50 21-JUN-18:02 10060.84 0.88
July 0.00 0.00 0.109252E+11 0.644854E+10 16557.90 30-JUL-08:62 10275.97 0.96
August 0.00 0.00 0.107131E+11 0.667766E+10 16142.21 06-AUG-08:62 10057.23 0.96
September 0.00 0.00 0.550850E+10 0.313846E+10 17043.29 22-SEP-18:02 8545.81 0.81
October 0.00 0.00 0.223169E+10 0.123375E+10 14776.48 25-OCT-08:62 10382.15 0.41
November 0.00 0.00 0.157155E+09 0.116888E+09 10946.07 06-NOV-09:02 10946.07 0.03
December 0.00 0.00 11629740.17 11261315.91 3902.90 09-DEC-09:03 3902.90 0.00
                 
Annual Sum or Average 0.00 0.00 0.436103E+11 0.265411E+11       0.41
Minimum of Months 0.00 0.00 9518493.76 8663992.49 3902.90   3527.17 0.00
Maximum of Months 0.00 0.00 0.109252E+11 0.667766E+10 17043.29   11981.71 0.96



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 11597952.98 11282813.33 3541.01 17-JAN-16:02 3541.01 0.00
February 0.00 0.00 29898443.97 29859265.87 3541.70 20-FEB-16:02 3541.70 0.00
March 0.00 0.00 0.203734E+09 0.189028E+09 3797.28 27-MAR-15:02 3410.93 0.03
April 0.00 0.00 0.526167E+09 0.397838E+09 3691.48 10-APR-15:02 3691.48 0.24
May 0.00 0.00 0.111371E+10 0.803077E+09 4143.73 31-MAY-08:62 3420.42 0.51
June 0.00 0.00 0.225745E+10 0.133289E+10 5142.55 27-JUN-08:62 2824.25 0.87
July 0.00 0.00 0.297448E+10 0.177382E+10 5192.21 30-JUL-08:62 2855.64 0.94
August 0.00 0.00 0.309870E+10 0.201853E+10 4981.70 27-AUG-08:62 2865.99 0.94
September 0.00 0.00 0.167196E+10 0.101370E+10 5217.02 22-SEP-18:02 2393.82 0.77
October 0.00 0.00 0.990745E+09 0.636464E+09 4433.72 05-OCT-18:02 3071.32 0.44
November 0.00 0.00 67547344.21 55227836.72 3593.58 03-NOV-15:02 3593.58 0.04
December 0.00 0.00 11437305.67 11281907.28 3540.21 17-DEC-16:01 3540.21 0.00
                 
Annual Sum or Average 0.00 0.00 0.129574E+11 0.827300E+10       0.40
Minimum of Months 0.00 0.00 11437305.67 11281907.28 3540.21   2393.82 0.00
Maximum of Months 0.00 0.00 0.309870E+10 0.201853E+10 5217.02   3691.48 0.94



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 2828151.59 2527977.89 1134.88 23-JAN-19:04 776.64 0.00
February 0.00 0.00 3468788.35 3432166.88 2467.47 20-FEB-16:02 2467.47 0.00
March 0.00 0.00 84507225.04 75442682.21 3546.50 27-MAR-15:02 3107.72 0.02
April 0.00 0.00 0.356736E+09 0.263281E+09 3591.99 16-APR-18:02 3591.99 0.19
May 0.00 0.00 0.985549E+09 0.700930E+09 3989.40 31-MAY-08:62 3323.86 0.48
June 0.00 0.00 0.215412E+10 0.126552E+10 4973.87 27-JUN-08:62 2737.53 0.86
July 0.00 0.00 0.283332E+10 0.166990E+10 5030.61 30-JUL-08:62 2762.36 0.94
August 0.00 0.00 0.274168E+10 0.172027E+10 4813.87 27-AUG-08:62 2733.15 0.93
September 0.00 0.00 0.127207E+10 0.709840E+09 5046.91 22-SEP-18:02 2306.91 0.69
October 0.00 0.00 0.495607E+09 0.285122E+09 4141.58 05-OCT-18:02 3009.11 0.32
November 0.00 0.00 14855461.42 13146505.72 3449.67 03-NOV-15:02 3449.67 0.01
December 0.00 0.00 3176098.86 3040947.07 1115.01 08-DEC-16:03 1115.01 0.00
                 
Annual Sum or Average 0.00 0.00 0.109479E+11 0.671245E+10       0.37
Minimum of Months 0.00 0.00 2828151.59 2527977.89 1115.01   776.64 0.00
Maximum of Months 0.00 0.00 0.283332E+10 0.172027E+10 5046.91   3591.99 0.94



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.876715E+09 0.875637E+09 16313.45 17-JAN-16:02 16313.45 0.00
February 0.00 0.00 0.129096E+10 0.129081E+10 16316.88 20-FEB-16:02 16316.88 0.00
March 0.00 0.00 0.244458E+10 0.230192E+10 17177.87 27-MAR-15:02 16008.76 0.06
April 0.00 0.00 0.347770E+10 0.260216E+10 17004.97 10-APR-15:02 17004.97 0.31
May 0.00 0.00 0.548088E+10 0.370435E+10 20114.29 31-MAY-18:02 14833.04 0.57
June 0.00 0.00 0.105766E+11 0.583795E+10 24173.56 27-JUN-08:62 12540.46 0.85
July 0.00 0.00 0.146900E+11 0.863362E+10 24194.19 30-JUL-08:62 13035.45 0.93
August 0.00 0.00 0.160992E+11 0.105282E+11 23130.48 27-AUG-08:62 13317.41 0.94
September 0.00 0.00 0.112189E+11 0.726285E+10 24643.94 22-SEP-18:02 10937.57 0.84
October 0.00 0.00 0.982079E+10 0.724863E+10 20732.55 05-OCT-18:02 13726.95 0.55
November 0.00 0.00 0.227208E+10 0.197977E+10 16554.48 03-NOV-15:02 16554.48 0.13
December 0.00 0.00 0.156237E+10 0.155626E+10 16312.71 03-DEC-16:02 16312.71 0.00
                 
Annual Sum or Average 0.00 0.00 0.798107E+11 0.538221E+11       0.43
Minimum of Months 0.00 0.00 0.876715E+09 0.875637E+09 16312.71   10937.57 0.00
Maximum of Months 0.00 0.00 0.160992E+11 0.105282E+11 24643.94   17004.97 0.94



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 53377.77 244134.17 02-JAN-09:03
February 0.00 0.00 01-FEB-00:03 50165.40 250248.53 06-FEB-09:01
March 0.00 0.00 01-MAR-00:03 21699.48 188916.36 31-MAR-15:01
April 0.00 0.00 01-APR-00:10 13755.62 179631.66 21-APR-15:01
May 0.00 0.00 01-MAY-00:05 3163.56 121348.43 15-MAY-02:45
June 0.00 0.00 01-JUN-00:05 100.39 42838.50 06-JUN-15:05
July 0.00 0.00 01-JUL-00:10 21.57 22033.06 14-JUL-08:07
August 0.00 0.00 01-AUG-00:05 111.42 43179.12 30-AUG-08:05
September 0.00 0.00 01-SEP-00:05 650.26 58380.05 24-SEP-05:16
October 0.00 0.00 01-OCT-00:10 6170.83 141585.99 26-OCT-23:27
November 0.00 0.00 01-NOV-00:05 23888.13 203416.42 27-NOV-16:01
December 0.00 0.00 01-DEC-00:03 32800.61 192608.75 04-DEC-19:01
             
Annual Sum or Average 0.00     16970.32    
Minimum of Months 0.00 0.00   21.57 22033.06  
Maximum of Months 0.00 0.00   53377.77 250248.53  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 1928.75 48858.99 13-JAN-09:04 0.00 0.00 01-JAN-00:03
February 2686.08 52898.63 16-FEB-09:04 0.00 0.00 01-FEB-00:03
March 7209.57 242235.07 27-MAR-15:02 0.00 0.00 01-MAR-00:03
April 29509.56 384848.35 07-APR-15:03 0.00 0.00 01-APR-00:10
May 84419.21 519182.81 31-MAY-18:03 0.00 0.00 01-MAY-00:05
June 289886.33 753327.34 24-JUN-18:03 0.00 0.00 01-JUN-00:05
July 422855.05 716524.30 14-JUL-18:03 0.00 0.00 01-JUL-00:10
August 359016.28 698936.02 04-AUG-18:03 0.00 0.00 01-AUG-00:05
September 210820.64 659088.70 22-SEP-18:02 0.00 0.00 01-SEP-00:05
October 86716.27 493398.93 05-OCT-15:03 0.00 0.00 01-OCT-00:10
November 8398.10 138801.50 04-NOV-15:01 0.00 0.00 01-NOV-00:05
December 3627.31 58343.85 17-DEC-16:04 0.00 0.00 01-DEC-00:03
             
Annual Sum or Average 126500.26     0.00    
Minimum of Months 1928.75 48858.99   0.00 0.00  
Maximum of Months 422855.05 753327.34   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 28260.05 61840.28 24-JAN-07:20
February 0.00 0.00 01-FEB-00:03 28541.20 64221.49 16-FEB-18:41
March 0.00 0.00 01-MAR-00:03 27934.38 65211.05 26-MAR-07:41
April 0.00 0.00 01-APR-00:10 26541.77 64141.31 13-APR-06:21
May 0.00 0.00 01-MAY-00:05 24818.45 56873.09 02-MAY-06:05
June 0.00 0.00 01-JUN-00:05 23174.66 48133.40 01-JUN-06:10
July 0.00 0.00 01-JUL-00:10 22020.11 44991.42 03-JUL-06:10
August 0.00 0.00 01-AUG-00:05 21739.19 45215.16 22-AUG-06:50
September 0.00 0.00 01-SEP-00:05 22357.33 49893.27 20-SEP-06:03
October 0.00 0.00 01-OCT-00:10 23700.37 56813.64 27-OCT-20:11
November 0.00 0.00 01-NOV-00:05 25447.27 59097.62 27-NOV-07:19
December 0.00 0.00 01-DEC-00:03 27134.22 64015.78 26-DEC-21:31
             
Annual Sum or Average 0.00     25119.44    
Minimum of Months 0.00 0.00   21739.19 44991.42  
Maximum of Months 0.00 0.00   28541.20 65211.05  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.587890E+10 0.88 2194.93 01-JAN-00:03 0.88
February 0.530997E+10 0.88 2194.93 01-FEB-00:03 0.88
March 0.587890E+10 0.88 2194.93 01-MAR-00:03 0.88
April 0.568926E+10 0.88 2194.93 01-APR-00:10 0.87
May 0.587890E+10 0.87 2194.93 01-MAY-00:05 0.87
June 0.568926E+10 0.87 2194.93 01-JUN-00:05 0.87
July 0.587890E+10 0.87 2194.93 01-JUL-00:10 0.87
August 0.587890E+10 0.87 2194.93 01-AUG-00:05 0.87
September 0.568926E+10 0.87 2194.93 01-SEP-00:05 0.87
October 0.587890E+10 0.87 2194.93 01-OCT-00:10 0.87
November 0.568926E+10 0.88 2194.93 01-NOV-00:05 0.87
December 0.587890E+10 0.88 2194.93 01-DEC-00:03 0.88
           
Annual Sum or Average 0.692193E+11 0.87      
Minimum of Months 0.530997E+10 0.87 2194.93   0.87
Maximum of Months 0.587890E+10 0.88 2194.93   0.88



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.330328E+11 0.79 40971.51 19-JAN-20:05 1.64
February 0.295480E+11 0.79 26933.30 01-FEB-19:37 1.26
March 0.348413E+11 0.82 34865.54 03-MAR-05:45 1.47
April 0.345567E+11 0.83 35417.67 11-APR-21:48 1.50
May 0.370209E+11 0.84 34865.54 16-MAY-04:35 1.47
June 0.380460E+11 0.87 28658.33 20-JUN-21:10 1.29
July 0.409099E+11 0.88 30354.91 10-JUL-21:10 1.34
August 0.422116E+11 0.90 34811.66 22-AUG-19:00 1.47
September 0.382746E+11 0.87 33648.52 07-SEP-21:10 1.43
October 0.384278E+11 0.86 40971.51 07-OCT-22:33 1.64
November 0.351837E+11 0.83 40971.51 05-NOV-21:55 1.63
December 0.340181E+11 0.81 39971.55 17-DEC-22:12 1.61
           
Annual Sum or Average 0.436071E+12 0.84      
Minimum of Months 0.295480E+11 0.79 26933.30   1.26
Maximum of Months 0.422116E+11 0.90 40971.51   1.64



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.27 76.61 01-JAN-00:03 0.27
February 0.185347E+09 0.27 76.61 01-FEB-00:03 0.27
March 0.205205E+09 0.27 76.61 01-MAR-00:03 0.27
April 0.198586E+09 0.27 76.61 01-APR-00:10 0.27
May 0.205205E+09 0.26 76.61 01-MAY-00:05 0.26
June 0.198586E+09 0.26 76.61 01-JUN-00:05 0.26
July 0.205205E+09 0.26 76.61 01-JUL-00:10 0.26
August 0.205205E+09 0.26 76.61 01-AUG-00:05 0.26
September 0.198586E+09 0.26 76.61 01-SEP-00:05 0.26
October 0.205205E+09 0.26 76.61 01-OCT-00:10 0.26
November 0.198586E+09 0.27 76.61 01-NOV-00:05 0.27
December 0.205205E+09 0.27 76.61 01-DEC-00:03 0.27
           
Annual Sum or Average 0.241613E+10 0.27      
Minimum of Months 0.185347E+09 0.26 76.61   0.26
Maximum of Months 0.205205E+09 0.27 76.61   0.27



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:03 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:03 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00
June 0.00 -0.0 0.00 01-JUN-00:05 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:05 0.00
September 0.00 -0.0 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:05 0.00
December 0.00 -0.0 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:03 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:05 0.00
September 0.00 -0.0 0.00 01-SEP-00:05 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:05 0.00
December 0.00 -0.0 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.19 612.92 01-JAN-07:03 0.27
February 0.105030E+10 0.19 612.92 01-FEB-07:05 0.27
March 0.116283E+10 0.19 612.92 01-MAR-07:05 0.27
April 0.112532E+10 0.19 612.92 01-APR-06:05 0.27
May 0.116283E+10 0.19 612.92 01-MAY-06:05 0.27
June 0.112532E+10 0.19 612.92 01-JUN-06:05 0.26
July 0.116283E+10 0.19 612.92 01-JUL-06:10 0.26
August 0.116283E+10 0.19 612.92 01-AUG-06:05 0.26
September 0.112532E+10 0.19 612.92 01-SEP-06:05 0.26
October 0.116283E+10 0.19 612.92 01-OCT-06:05 0.26
November 0.112532E+10 0.19 612.92 01-NOV-06:05 0.27
December 0.116283E+10 0.19 612.92 01-DEC-07:05 0.27
           
Annual Sum or Average 0.136914E+11 0.19      
Minimum of Months 0.105030E+10 0.19 612.92   0.26
Maximum of Months 0.116283E+10 0.19 612.92   0.27



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.286554E+09 0.46 801.85 01-JAN-09:01 0.58
February 0.244233E+09 0.45 801.85 01-FEB-09:01 0.58
March 0.196903E+09 0.43 801.85 01-MAR-16:02 0.58
April 0.207127E+09 0.45 801.85 01-APR-08:61 0.58
May 0.285804E+09 0.48 801.85 01-MAY-15:02 0.58
June 0.442531E+09 0.52 801.85 01-JUN-08:62 0.57
July 0.528957E+09 0.54 801.85 01-JUL-08:61 0.57
August 0.583747E+09 0.54 801.85 01-AUG-08:62 0.57
September 0.360539E+09 0.51 801.85 01-SEP-08:61 0.57
October 0.269247E+09 0.49 801.85 02-OCT-15:02 0.57
November 0.180695E+09 0.42 801.85 01-NOV-15:02 0.58
December 0.248017E+09 0.45 801.85 01-DEC-09:01 0.58
           
Annual Sum or Average 0.383435E+10 0.48      
Minimum of Months 0.180695E+09 0.42 801.85   0.57
Maximum of Months 0.583747E+09 0.54 801.85   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.316879E+09 0.49 777.29 01-JAN-09:01 0.58
February 0.280634E+09 0.48 777.29 01-FEB-09:01 0.58
March 0.194500E+09 0.42 777.29 01-MAR-09:02 0.58
April 0.176201E+09 0.43 777.29 01-APR-08:61 0.58
May 0.259316E+09 0.46 777.29 01-MAY-15:02 0.58
June 0.424471E+09 0.52 777.29 01-JUN-08:62 0.57
July 0.505386E+09 0.54 777.29 01-JUL-08:61 0.57
August 0.517864E+09 0.53 777.29 01-AUG-08:62 0.57
September 0.287011E+09 0.48 777.29 01-SEP-08:61 0.57
October 0.176325E+09 0.44 777.29 02-OCT-15:02 0.57
November 0.193698E+09 0.43 777.29 01-NOV-08:62 0.57
December 0.282895E+09 0.47 777.29 01-DEC-09:01 0.58
           
Annual Sum or Average 0.361518E+10 0.47      
Minimum of Months 0.176201E+09 0.42 777.29   0.57
Maximum of Months 0.517864E+09 0.54 777.29   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.569275E+09 0.26 932.55 02-JAN-05:00 0.58
February 0.243677E+09 0.13 893.11 20-FEB-13:23 0.58
March 0.172239E+09 0.07 1384.36 03-MAR-13:30 0.58
April 0.324906E+09 0.11 2265.19 07-APR-12:30 0.57
May 0.525645E+09 0.21 1226.89 30-MAY-12:50 0.57
June 0.957813E+09 0.36 1321.56 19-JUN-13:20 0.57
July 0.161190E+10 0.51 1394.76 10-JUL-13:10 0.57
August 0.210864E+10 0.54 2538.91 30-AUG-13:30 0.57
September 0.148210E+10 0.40 4090.13 30-SEP-12:40 0.57
October 0.156828E+10 0.34 2711.78 10-OCT-12:30 0.57
November 0.327154E+09 0.10 2527.60 04-NOV-13:10 0.57
December 0.380092E+09 0.17 1402.48 17-DEC-13:40 0.58
           
Annual Sum or Average 0.102717E+11 0.27      
Minimum of Months 0.172239E+09 0.07 893.11   0.57
Maximum of Months 0.210864E+10 0.54 4090.13   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.129288E+10 0.42 4053.44 01-JAN-09:01 0.58
February 0.122228E+10 0.42 4053.44 01-FEB-09:01 0.58
March 0.741043E+09 0.41 4053.44 03-MAR-19:02 0.58
April 0.793457E+09 0.41 4053.44 01-APR-15:01 0.58
May 0.160793E+10 0.41 4053.44 01-MAY-08:62 0.57
June 0.245583E+10 0.41 4053.44 01-JUN-08:62 0.57
July 0.303970E+10 0.43 4053.44 01-JUL-08:61 0.57
August 0.274548E+10 0.43 4053.44 01-AUG-08:62 0.57
September 0.168155E+10 0.41 4053.44 01-SEP-08:61 0.57
October 0.890382E+09 0.41 4053.44 01-OCT-08:62 0.57
November 0.717819E+09 0.41 4053.44 04-NOV-08:62 0.57
December 0.110217E+10 0.41 4053.44 01-DEC-09:01 0.58
           
Annual Sum or Average 0.182905E+11 0.41      
Minimum of Months 0.717819E+09 0.41 4053.44   0.57
Maximum of Months 0.303970E+10 0.43 4053.44   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.268632E+09 0.46 730.51 01-JAN-09:01 0.58
February 0.224295E+09 0.44 730.51 01-FEB-16:01 0.58
March 0.183734E+09 0.43 730.51 01-MAR-09:02 0.58
April 0.201627E+09 0.46 730.51 01-APR-08:61 0.58
May 0.294735E+09 0.50 730.51 01-MAY-08:62 0.57
June 0.413060E+09 0.53 730.51 01-JUN-08:62 0.57
July 0.519759E+09 0.55 730.51 01-JUL-08:61 0.57
August 0.574504E+09 0.56 730.51 01-AUG-08:62 0.57
September 0.365822E+09 0.52 730.51 01-SEP-08:61 0.57
October 0.259124E+09 0.50 730.51 02-OCT-08:62 0.57
November 0.173277E+09 0.42 730.51 01-NOV-08:62 0.57
December 0.234512E+09 0.44 730.51 01-DEC-16:01 0.58
           
Annual Sum or Average 0.371308E+10 0.48      
Minimum of Months 0.173277E+09 0.42 730.51   0.57
Maximum of Months 0.574504E+09 0.56 730.51   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.297225E+09 0.50 709.14 01-JAN-09:01 0.58
February 0.259299E+09 0.48 709.14 01-FEB-09:01 0.58
March 0.182801E+09 0.42 709.14 01-MAR-09:02 0.58
April 0.167247E+09 0.43 709.14 01-APR-08:61 0.58
May 0.266901E+09 0.49 709.14 01-MAY-08:62 0.57
June 0.394745E+09 0.53 709.14 01-JUN-08:62 0.57
July 0.496877E+09 0.55 709.14 01-JUL-08:61 0.57
August 0.508858E+09 0.55 709.14 01-AUG-08:62 0.57
September 0.286074E+09 0.50 709.14 01-SEP-08:61 0.57
October 0.158807E+09 0.44 709.14 02-OCT-08:62 0.57
November 0.176281E+09 0.43 709.14 04-NOV-08:62 0.57
December 0.260982E+09 0.48 709.14 01-DEC-09:01 0.58
           
Annual Sum or Average 0.345609E+10 0.48      
Minimum of Months 0.158807E+09 0.42 709.14   0.57
Maximum of Months 0.508858E+09 0.55 709.14   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 86591463.45 0.49 210.60 01-JAN-09:01 0.58
February 74244692.24 0.47 210.60 01-FEB-09:01 0.58
March 59365118.07 0.44 210.60 01-MAR-16:02 0.58
April 58039820.95 0.46 210.60 01-APR-08:61 0.58
May 72233235.92 0.48 210.60 01-MAY-15:02 0.58
June 0.111925E+09 0.52 210.60 01-JUN-08:62 0.57
July 0.136465E+09 0.54 210.60 01-JUL-08:61 0.57
August 0.149834E+09 0.54 210.60 01-AUG-08:62 0.57
September 87820754.04 0.50 210.60 01-SEP-08:61 0.57
October 65341866.40 0.48 210.60 02-OCT-15:02 0.57
November 55155960.45 0.44 210.60 01-NOV-08:62 0.57
December 75953953.47 0.47 210.60 01-DEC-09:01 0.58
           
Annual Sum or Average 0.103297E+10 0.49      
Minimum of Months 55155960.45 0.44 210.60   0.57
Maximum of Months 0.149834E+09 0.54 210.60   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 95310161.84 0.53 203.72 01-JAN-09:01 0.58
February 84159461.38 0.51 203.72 01-FEB-09:01 0.58
March 59018613.29 0.44 203.72 01-MAR-09:02 0.58
April 50542761.92 0.44 203.72 01-APR-08:61 0.58
May 65579738.22 0.47 203.72 01-MAY-15:02 0.58
June 0.107115E+09 0.52 203.72 01-JUN-08:62 0.57
July 0.130195E+09 0.54 203.72 01-JUL-08:61 0.57
August 0.132358E+09 0.53 203.72 01-AUG-08:62 0.57
September 68602678.05 0.48 203.72 01-SEP-08:61 0.57
October 44426481.67 0.43 203.72 02-OCT-15:02 0.57
November 60952680.77 0.46 203.72 01-NOV-08:62 0.57
December 86036994.60 0.51 203.72 01-DEC-09:01 0.58
           
Annual Sum or Average 0.984298E+09 0.49      
Minimum of Months 44426481.67 0.43 203.72   0.57
Maximum of Months 0.132358E+09 0.54 203.72   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.330040E+09 0.46 962.80 01-JAN-16:01 0.58
February 0.286956E+09 0.48 962.80 01-FEB-16:01 0.58
March 0.285134E+09 0.46 962.80 01-MAR-09:02 0.58
April 0.280964E+09 0.47 962.80 01-APR-08:61 0.58
May 0.324984E+09 0.48 962.80 01-MAY-15:02 0.58
June 0.493220E+09 0.51 962.80 01-JUN-08:62 0.57
July 0.650962E+09 0.53 962.80 01-JUL-08:61 0.57
August 0.770307E+09 0.54 962.80 01-AUG-08:62 0.57
September 0.574931E+09 0.51 962.80 01-SEP-08:61 0.57
October 0.544651E+09 0.51 962.80 02-OCT-08:62 0.57
November 0.264331E+09 0.45 962.80 01-NOV-15:02 0.58
December 0.315442E+09 0.47 962.80 01-DEC-19:01 0.58
           
Annual Sum or Average 0.512192E+10 0.49      
Minimum of Months 0.264331E+09 0.45 962.80   0.57
Maximum of Months 0.770307E+09 0.54 962.80   0.58



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.936310E+09 0.842679E+09 820.65 14-JAN-16:02 738.58 738.58 44.26 1.35
February 0.787135E+09 0.708422E+09 801.55 06-FEB-07:05 721.39 721.39 46.84 1.29
March 0.473750E+09 0.426375E+09 717.00 05-MAR-16:15 645.30 645.30 49.94 1.06
April 0.257812E+09 0.232030E+09 681.34 01-APR-21:25 613.21 613.21 49.36 0.98
May 53506128.73 48155515.86 568.57 02-MAY-03:25 511.72 511.72 43.57 0.75
June 1733481.07 1560132.96 242.01 06-JUN-15:05 217.81 217.81 41.35 0.27
July 504127.72 453714.95 185.33 24-JUL-08:06 166.80 166.80 56.35 0.20
August 2050868.46 1845781.62 288.82 30-AUG-08:05 259.94 259.94 47.84 0.33
September 10775930.63 9698337.56 322.97 26-SEP-15:05 290.68 290.68 59.64 0.37
October 0.121849E+09 0.109664E+09 679.94 28-OCT-00:03 611.94 611.94 52.13 0.97
November 0.473172E+09 0.425855E+09 734.07 26-NOV-04:20 660.66 660.66 67.65 1.09
December 0.712511E+09 0.641260E+09 738.10 04-DEC-09:13 664.29 664.29 45.12 1.11
                 
Annual Sum or Average 0.383111E+10 0.344800E+10            
Minimum of Months 504127.72 453714.95 185.33   166.80 166.80 41.35 0.20
Maximum of Months 0.936310E+09 0.842679E+09 820.65   738.58 738.58 67.65 1.35



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 845358.80 760822.92 42.08 18-JAN-16:04 37.87 37.87 8.40 3.27
February 1769905.33 1592914.79 48.98 16-FEB-09:04 44.08 44.08 8.40 3.56
March 11369454.77 10232509.29 316.70 27-MAR-18:02 285.03 285.03 7.91 9.30
April 85519406.81 76967466.13 923.45 07-APR-15:03 831.10 831.10 6.90 15.15
May 0.266262E+09 0.239636E+09 1389.58 31-MAY-18:03 1250.62 1250.62 7.50 18.09
June 0.125899E+10 0.113309E+10 2696.41 24-JUN-18:03 2426.77 2426.77 7.33 23.89
July 0.213595E+10 0.192235E+10 2356.96 26-JUL-18:03 2121.26 2121.26 7.41 22.60
August 0.182439E+10 0.164195E+10 2325.64 03-AUG-18:05 2093.08 2093.08 6.74 22.48
September 0.875036E+09 0.787532E+09 2188.33 07-SEP-20:00 1969.50 1969.50 7.15 21.91
October 0.282811E+09 0.254530E+09 1155.96 05-OCT-18:02 1040.36 1040.36 7.74 16.71
November 13713525.56 12342173.00 215.27 04-NOV-15:01 193.75 193.75 8.15 7.72
December 3231056.06 2907950.45 61.20 17-DEC-16:04 55.08 55.08 8.40 4.03
                 
Annual Sum or Average 0.675988E+10 0.608389E+10            
Minimum of Months 845358.80 760822.92 42.08   37.87 37.87 6.74 3.27
Maximum of Months 0.213595E+10 0.192235E+10 2696.41   2426.77 2426.77 8.40 23.89



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.406856E+10 0.366170E+10 5127.50 01-JAN-09:03 4614.75 4614.75 8.43 35.94
February 0.425046E+10 0.382541E+10 5127.50 01-FEB-00:03 4614.75 4614.75 8.40 35.94
March 0.677161E+10 0.609445E+10 5127.50 01-MAR-00:03 4614.75 4614.75 8.40 35.94
April 0.923893E+10 0.831504E+10 5127.50 01-APR-01:07 4614.75 4614.75 8.40 35.94
May 0.132747E+11 0.119472E+11 5127.50 01-MAY-00:05 4614.75 4614.75 8.43 35.94
June 0.132905E+11 0.119614E+11 5127.50 01-JUN-00:05 4614.75 4614.75 8.97 35.94
July 0.137335E+11 0.123601E+11 5127.50 01-JUL-00:10 4614.75 4614.75 9.69 35.94
August 0.137335E+11 0.123601E+11 5127.50 01-AUG-00:05 4614.75 4614.75 9.52 35.94
September 0.132682E+11 0.119414E+11 5127.50 01-SEP-00:05 4614.75 4614.75 9.48 35.94
October 0.127058E+11 0.114352E+11 5127.50 01-OCT-00:10 4614.75 4614.75 8.50 35.94
November 0.707007E+10 0.636306E+10 5127.50 01-NOV-03:16 4614.75 4614.75 8.41 35.94
December 0.576631E+10 0.518968E+10 5127.50 01-DEC-00:03 4614.75 4614.75 8.51 35.94
                 
Annual Sum or Average 0.117172E+12 0.105455E+12            
Minimum of Months 0.406856E+10 0.366170E+10 5127.50   4614.75 4614.75 8.40 35.94
Maximum of Months 0.137335E+11 0.123601E+11 5127.50   4614.75 4614.75 9.69 35.94



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:03 14.37 14.37 47.67 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:03 14.37 14.37 48.42 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:03 14.37 14.37 48.52 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 51.85 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:05 14.37 14.37 51.69 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:05 14.37 14.37 52.74 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 52.90 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:05 14.37 14.37 52.93 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:05 14.37 14.37 52.51 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 52.49 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:05 14.37 14.37 52.34 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:03 14.37 14.37 49.39 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 47.67 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 52.93 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 47.42 82.20 53377.77 244134.17 02-JAN-09:03
February 0.00 0.00 01-FEB-00:03 53.23 81.26 50165.40 250248.53 06-FEB-09:01
March 0.00 0.00 01-MAR-00:03 59.62 80.15 21699.48 188916.36 31-MAR-15:01
April 0.00 0.00 01-APR-00:10 62.50 80.20 13755.62 179631.66 21-APR-15:01
May 0.00 0.00 01-MAY-00:05 39.58 79.40 3163.56 121348.43 15-MAY-02:45
June 0.00 0.00 01-JUN-00:05 41.58 41.58 100.39 42838.50 06-JUN-15:05
July 0.00 0.00 01-JUL-00:10 49.90 49.90 21.57 22033.06 14-JUL-08:07
August 0.00 0.00 01-AUG-00:05 58.79 58.79 111.42 43179.12 30-AUG-08:05
September 0.00 0.00 01-SEP-00:05 57.19 57.19 650.26 58380.05 24-SEP-05:16
October 0.00 0.00 01-OCT-00:10 32.72 79.40 6170.83 141585.99 26-OCT-23:27
November 0.00 0.00 01-NOV-00:05 47.48 79.40 23888.13 203416.42 27-NOV-16:01
December 0.00 0.00 01-DEC-00:03 48.34 80.08 32800.61 192608.75 04-DEC-19:01
                 
Annual Sum or Average 0.00         16970.32    
Minimum of Months 0.00 0.00   32.72 41.58 21.57 22033.06  
Maximum of Months 0.00 0.00   62.50 82.20 53377.77 250248.53  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 1928.75 48858.99 13-JAN-09:04 8.69 8.37 0.00 0.00 01-JAN-00:03
February 2686.08 52898.63 16-FEB-09:04 8.72 8.37 0.00 0.00 01-FEB-00:03
March 7209.57 242235.07 27-MAR-15:02 9.34 7.73 0.00 0.00 01-MAR-00:03
April 29509.56 384848.35 07-APR-15:03 9.42 6.87 0.00 0.00 01-APR-00:10
May 84419.21 519182.81 31-MAY-18:03 10.93 7.48 0.00 0.00 01-MAY-00:05
June 289886.33 753327.34 24-JUN-18:03 12.31 7.30 0.00 0.00 01-JUN-00:05
July 422855.05 716524.30 14-JUL-18:03 12.06 7.30 0.00 0.00 01-JUL-00:10
August 359016.28 698936.02 04-AUG-18:03 11.34 6.70 0.00 0.00 01-AUG-00:05
September 210820.64 659088.70 22-SEP-18:02 11.81 7.43 0.00 0.00 01-SEP-00:05
October 86716.27 493398.93 05-OCT-15:03 10.67 7.39 0.00 0.00 01-OCT-00:10
November 8398.10 138801.50 04-NOV-15:01 9.04 8.11 0.00 0.00 01-NOV-00:05
December 3627.31 58343.85 17-DEC-16:04 8.76 8.37 0.00 0.00 01-DEC-00:03
                 
Annual Sum or Average 126500.26         0.00    
Minimum of Months 1928.75 48858.99   8.69 6.70 0.00 0.00  
Maximum of Months 422855.05 753327.34   12.31 8.37 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 47.67 59.79 28260.05 61840.28 24-JAN-07:20
February 0.00 0.00 01-FEB-00:03 48.42 58.72 28541.20 64221.49 16-FEB-18:41
March 0.00 0.00 01-MAR-00:03 48.52 58.94 27934.38 65211.05 26-MAR-07:41
April 0.00 0.00 01-APR-00:10 51.85 59.26 26541.77 64141.31 13-APR-06:21
May 0.00 0.00 01-MAY-00:05 51.69 58.49 24818.45 56873.09 02-MAY-06:05
June 0.00 0.00 01-JUN-00:05 52.74 59.75 23174.66 48133.40 01-JUN-06:10
July 0.00 0.00 01-JUL-00:10 52.90 58.67 22020.11 44991.42 03-JUL-06:10
August 0.00 0.00 01-AUG-00:05 52.93 58.61 21739.19 45215.16 22-AUG-06:50
September 0.00 0.00 01-SEP-00:05 52.51 58.16 22357.33 49893.27 20-SEP-06:03
October 0.00 0.00 01-OCT-00:10 52.49 59.55 23700.37 56813.64 27-OCT-20:11
November 0.00 0.00 01-NOV-00:05 52.34 58.91 25447.27 59097.62 27-NOV-07:19
December 0.00 0.00 01-DEC-00:03 49.39 59.22 27134.22 64015.78 26-DEC-21:31
                 
Annual Sum or Average 0.00         25119.44    
Minimum of Months 0.00 0.00   47.67 58.16 21739.19 44991.42  
Maximum of Months 0.00 0.00   52.93 59.79 28541.20 65211.05  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.679245E+11 0.00 0.227956E+09 0.330328E+11 0.00 0.00
February 0.590772E+11 0.00 0.207446E+09 0.295480E+11 0.00 0.00
March 0.321814E+11 0.00 0.355282E+10 0.348413E+11 0.00 0.00
April 0.270362E+11 0.00 0.341923E+11 0.345567E+11 0.00 0.00
May 0.780898E+10 0.00 0.126129E+12 0.370209E+11 0.00 0.00
June 0.205975E+09 0.00 0.519220E+12 0.380460E+11 0.00 0.00
July 17396389.89 0.00 0.817177E+12 0.409099E+11 0.00 0.00
August 0.257035E+09 0.00 0.666890E+12 0.422116E+11 0.00 0.00
September 0.156042E+10 0.00 0.362678E+12 0.382746E+11 0.00 0.00
October 0.139503E+11 0.00 0.125687E+12 0.384278E+11 0.00 0.00
November 0.362765E+11 0.00 0.359820E+10 0.351837E+11 0.00 0.00
December 0.344603E+11 0.00 0.459344E+09 0.340181E+11 0.00 0.00
             
Annual Sum or Average 0.280756E+12 0.00 0.266002E+13 0.436071E+12 0.00 0.00
Minimum of Months 17396389.89 0.00 0.207446E+09 0.295480E+11 0.00 0.00
Maximum of Months 0.679245E+11 0.00 0.817177E+12 0.422116E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.472799E+10 0.00 0.00 0.587890E+10 0.00 0.00
February 0.483628E+10 0.00 0.00 0.530997E+10 0.00 0.00
March 0.539191E+09 0.00 0.697382E+09 0.587890E+10 0.00 0.00
April 3170.73 0.00 0.634269E+10 0.568926E+10 0.00 0.00
May 17171.13 0.00 0.232123E+11 0.587890E+10 0.00 0.00
June 21241.03 0.00 0.961906E+11 0.568926E+10 0.00 0.00
July 12464.12 0.00 0.130865E+12 0.587890E+10 0.00 0.00
August 21984.90 0.00 0.107294E+12 0.587890E+10 0.00 0.00
September 16076.36 0.00 0.663363E+11 0.568926E+10 0.00 0.00
October 23495.34 0.00 0.245200E+11 0.587890E+10 0.00 0.00
November 0.434607E+09 0.00 0.605095E+09 0.568926E+10 0.00 0.00
December 0.903161E+09 0.00 2300.65 0.587890E+10 0.00 0.00
             
Annual Sum or Average 0.114414E+11 0.00 0.456064E+12 0.692193E+11 0.00 0.00
Minimum of Months 3170.73 0.00 0.00 0.530997E+10 0.00 0.00
Maximum of Months 0.483628E+10 0.00 0.130865E+12 0.587890E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.330328E+11 0.227956E+09 0.679245E+11 0.544395E+12 0.00 0.00 0.00 0.00
February 0.295480E+11 0.207447E+09 0.590772E+11 0.544316E+12 0.00 0.00 0.00 0.00
March 0.348413E+11 0.355316E+10 0.321814E+11 0.372526E+12 0.00 0.00 0.00 0.00
April 0.345567E+11 0.341924E+11 0.270362E+11 0.150063E+12 0.148108E+09 0.00 0.00 0.00
May 0.370209E+11 0.126129E+12 0.780898E+10 0.232786E+11 0.274233E+10 0.00 0.00 0.00
June 0.380460E+11 0.519220E+12 0.205975E+09 0.121927E+09 0.474842E+11 0.00 0.00 0.00
July 0.409099E+11 0.817177E+12 17396389.89 0.00 0.185054E+12 0.00 0.00 0.00
August 0.422116E+11 0.666890E+12 0.257035E+09 0.00 0.149522E+12 0.00 0.00 0.00
September 0.382746E+11 0.362678E+12 0.156042E+10 0.339044E+10 0.190039E+11 0.00 0.00 0.00
October 0.384278E+11 0.125688E+12 0.139503E+11 0.701619E+11 0.498861E+09 0.00 0.00 0.00
November 0.351837E+11 0.359820E+10 0.362765E+11 0.271267E+12 0.00 0.00 0.00 0.00
December 0.340181E+11 0.459345E+09 0.344603E+11 0.480351E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.436071E+12 0.266002E+13 0.280756E+12 0.245987E+13 0.404454E+12 0.00 0.00 0.00
Minimum of Months 0.295480E+11 0.207447E+09 17396389.89 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.422116E+11 0.817177E+12 0.679245E+11 0.544395E+12 0.185054E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.587890E+10 0.00 0.472799E+10 0.978969E+11 0.00 0.00 0.00 0.00
February 0.530997E+10 0.00 0.483628E+10 0.960321E+11 0.00 0.00 0.00 0.00
March 0.587890E+10 0.697382E+09 0.539191E+09 0.702677E+11 194869.44 0.00 0.00 0.00
April 0.568926E+10 0.634269E+10 3170.73 0.341716E+11 0.161524E+09 0.00 0.00 0.00
May 0.587890E+10 0.232123E+11 17171.13 0.728761E+10 0.136179E+10 0.00 0.00 0.00
June 0.568926E+10 0.961906E+11 21241.03 0.128936E+09 0.192307E+11 0.00 0.00 0.00
July 0.587890E+10 0.130865E+12 12464.12 29061.28 0.666868E+11 0.00 0.00 0.00
August 0.587890E+10 0.107294E+12 21984.90 88902343.20 0.511435E+11 0.00 0.00 0.00
September 0.568926E+10 0.663363E+11 16076.36 0.146367E+10 0.118721E+11 0.00 0.00 0.00
October 0.587890E+10 0.245200E+11 23495.34 0.178925E+11 0.663179E+09 0.00 0.00 0.00
November 0.568926E+10 0.605095E+09 0.434607E+09 0.560636E+11 0.00 0.00 0.00 0.00
December 0.587890E+10 2300.65 0.903161E+09 0.869951E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.692193E+11 0.456064E+12 0.114414E+11 0.468289E+12 0.151120E+12 0.00 0.00 0.00
Minimum of Months 0.530997E+10 0.00 3170.73 29061.28 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.130865E+12 0.483628E+10 0.978969E+11 0.666868E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.330328E+11 0.679245E+11 0.227956E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.295480E+11 0.590772E+11 0.207446E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.348413E+11 0.321814E+11 0.355282E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.345567E+11 0.270362E+11 0.341923E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.370209E+11 0.780898E+10 0.126129E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.380460E+11 0.205975E+09 0.519220E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.409099E+11 17396389.89 0.817177E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.422116E+11 0.257035E+09 0.666890E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.382746E+11 0.156042E+10 0.362678E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.384278E+11 0.139503E+11 0.125687E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.351837E+11 0.362765E+11 0.359820E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.340181E+11 0.344603E+11 0.459344E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.436071E+12 0.280756E+12 0.266002E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.295480E+11 17396389.89 0.207446E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.422116E+11 0.679245E+11 0.817177E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.587890E+10 0.472799E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.530997E+10 0.483628E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.587890E+10 0.539191E+09 0.697382E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.568926E+10 3170.73 0.634269E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.587890E+10 17171.13 0.232123E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.568926E+10 21241.03 0.961906E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.587890E+10 12464.12 0.130865E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.587890E+10 21984.90 0.107294E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.568926E+10 16076.36 0.663363E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.587890E+10 23495.34 0.245200E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.568926E+10 0.434607E+09 0.605095E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.587890E+10 0.903161E+09 2300.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.692193E+11 0.114414E+11 0.456064E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.530997E+10 3170.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.483628E+10 0.130865E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.272467E+11 0.00 0.00 23605185.09 0.00 0.00 0.234291E+11 0.00 0.95
February 0.365968E+11 0.00 0.00 5204941.31 0.00 0.00 0.853327E+10 0.00 0.94
March 0.448183E+11 0.00 0.00 963795.66 0.00 0.00 0.362255E+10 0.00 0.92
April 0.449798E+11 0.00 0.00 71020.12 6613760.25 0.00 0.283304E+09 0.00 0.93
May 0.381455E+11 0.00 0.00 0.00 0.222987E+09 0.00 0.00 0.00 0.97
June 0.100617E+11 0.538656E+09 0.00 211055.08 0.965981E+10 0.00 0.397116E+09 0.00 0.94
July 0.506465E+09 0.571257E+10 0.00 254259.05 0.193036E+11 0.00 57854585.23 0.00 0.87
August 0.597703E+09 0.739538E+10 0.00 11362311.29 0.801538E+10 0.00 0.583468E+10 0.00 0.92
September 0.775494E+09 0.522334E+10 0.00 41327837.50 0.537961E+09 0.00 0.221503E+11 0.00 1.03
October 0.106908E+10 0.348071E+09 0.00 93202830.70 45104347.27 0.00 0.453420E+11 0.00 1.08
November 0.239845E+10 0.00 0.00 0.117107E+09 0.00 0.00 0.534184E+11 0.00 1.05
December 0.630897E+10 0.00 0.00 69174528.50 0.00 0.00 0.451143E+11 0.00 0.99
                   
Annual Sum or Average 0.213505E+12 0.192180E+11 0.00 0.362484E+09 0.377915E+11 0.00 0.208183E+12 0.00 0.97
Minimum of Months 0.506465E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Maximum of Months 0.449798E+11 0.739538E+10 0.00 0.117107E+09 0.193036E+11 0.00 0.534184E+11 0.00 1.08



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.392604E+10 0.00 0.00 294831.65 0.00 0.351814E+10 0.232851E+09 0.00 2.59
February 0.399247E+10 0.00 0.00 578147.27 0.00 0.262362E+10 0.351950E+09 0.00 2.61
March 0.618508E+10 0.00 0.00 1024933.51 0.00 0.757753E+09 0.596149E+09 0.00 2.58
April 0.642173E+10 1386996.09 0.00 675211.50 103116.72 0.168228E+09 0.404177E+09 0.00 2.63
May 0.559473E+10 29213215.20 0.00 375409.22 6965484.55 460122.84 0.291848E+09 0.00 2.72
June 0.148124E+10 0.746787E+09 0.00 361467.48 0.840452E+09 0.00 0.132734E+09 0.00 2.64
July 65925377.50 0.234326E+10 0.00 68961.09 0.162469E+10 0.00 21142418.17 0.00 2.49
August 0.736467E+09 0.213710E+10 0.00 1198390.29 0.439755E+09 0.00 0.244086E+09 0.00 2.75
September 0.260465E+10 0.436509E+09 0.00 2365249.01 0.453255E+09 0.00 0.742888E+09 0.00 2.84
October 0.488618E+10 84268075.38 0.00 3450609.08 1331782.40 491965.92 0.154207E+10 0.00 2.85
November 0.634586E+10 0.00 0.00 826808.72 0.00 0.639685E+09 0.470601E+09 0.00 2.57
December 0.471651E+10 0.00 0.00 1011116.57 0.00 0.228040E+10 0.403131E+09 0.00 2.60
                   
Annual Sum or Average 0.469569E+11 0.577852E+10 0.00 12231135.39 0.336655E+10 0.998878E+10 0.543362E+10 0.00 2.65
Minimum of Months 65925377.50 0.00 0.00 68961.09 0.00 0.00 21142418.17 0.00 2.49
Maximum of Months 0.642173E+10 0.234326E+10 0.00 3450609.08 0.162469E+10 0.351814E+10 0.154207E+10 0.00 2.85



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.474020E+10 0.00 0.00 573.78 0.00 0.00 2466653.99 0.00 1.38
February 0.430346E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.39
March 0.449475E+10 0.00 0.00 39847.18 0.00 0.00 0.129256E+09 0.00 1.37
April 0.392820E+10 0.00 0.00 316025.60 631427.21 0.00 0.397012E+09 0.00 1.40
May 0.277763E+10 6719782.98 0.00 738767.67 14599608.88 0.00 0.874571E+09 0.00 1.46
June 0.338744E+09 0.574681E+09 0.00 1060247.65 0.429228E+09 0.00 0.679249E+09 0.00 1.45
July 2210246.15 0.198111E+10 0.00 294249.06 0.525270E+09 0.00 54278243.12 0.00 1.36
August 48892798.69 0.139917E+10 0.00 1601854.44 0.169343E+09 0.00 0.585385E+09 0.00 1.46
September 0.103223E+10 0.365213E+09 0.00 1377960.41 0.172391E+09 0.00 0.103038E+10 0.00 1.48
October 0.271668E+10 15221369.58 0.00 1120798.09 21996200.78 0.00 0.115523E+10 0.00 1.44
November 0.439023E+10 0.00 0.00 76267.41 0.00 0.00 0.193333E+09 0.00 1.37
December 0.454434E+10 0.00 0.00 63.81 0.00 0.00 933283.78 0.00 1.38
                   
Annual Sum or Average 0.333176E+11 0.434212E+10 0.00 6626655.11 0.133346E+10 0.00 0.510210E+10 0.00 1.41
Minimum of Months 2210246.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.36
Maximum of Months 0.474020E+10 0.198111E+10 0.00 1601854.44 0.525270E+09 0.00 0.115523E+10 0.00 1.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.345636E+10 0.00 0.00 0.00 0.00 0.115213E+10 0.00 0.00 0.63
February 0.303162E+10 0.00 0.00 0.00 0.00 0.115009E+10 0.00 0.00 0.64
March 0.447392E+10 0.00 0.00 0.00 0.00 19313989.85 0.00 0.00 0.63
April 0.419910E+10 0.00 0.00 0.00 613563.61 0.00 0.00 0.00 0.64
May 0.351898E+10 136399.75 0.00 41320.11 20550255.57 0.00 19778263.61 0.00 0.67
June 0.877859E+09 0.211635E+09 0.00 184825.69 0.743616E+09 0.00 94750933.09 0.00 0.65
July 16562423.34 0.112271E+10 0.00 140044.08 0.126402E+10 0.00 36782783.79 0.00 0.61
August 0.401752E+09 0.948735E+09 0.00 525952.79 0.525840E+09 0.00 0.193884E+09 0.00 0.64
September 0.185742E+10 94567603.67 0.00 207998.45 0.408548E+09 0.00 0.115297E+09 0.00 0.66
October 0.373856E+10 0.00 0.00 546.52 36024047.46 0.00 718565.48 0.00 0.65
November 0.441978E+10 0.00 0.00 0.00 0.00 34177251.62 0.00 0.00 0.63
December 0.437717E+10 0.00 0.00 0.00 0.00 39514282.30 0.00 0.00 0.63
                   
Annual Sum or Average 0.343691E+11 0.237779E+10 0.00 1100687.64 0.299921E+10 0.239523E+10 0.461211E+09 0.00 0.64
Minimum of Months 16562423.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.61
Maximum of Months 0.447392E+10 0.112271E+10 0.00 525952.79 0.126402E+10 0.115213E+10 0.193884E+09 0.00 0.67



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.104372E+10 0.00 0.00 0.00 0.00 0.118972E+10 0.00 0.00 0.53
February 0.915339E+09 0.00 0.00 0.00 0.00 0.111127E+10 0.00 0.00 0.54
March 0.201928E+10 0.00 0.00 0.00 0.00 0.158304E+09 0.00 0.00 0.53
April 0.203474E+10 0.00 0.00 0.00 297355.31 299013.06 0.00 0.00 0.54
May 0.171503E+10 0.00 0.00 0.00 10025507.75 0.00 0.00 0.00 0.56
June 0.464837E+09 21644016.50 0.00 15108.67 0.436895E+09 0.00 5385973.95 0.00 0.54
July 12425604.39 0.247227E+09 0.00 26669.93 0.878719E+09 0.00 12977408.09 0.00 0.50
August 0.254692E+09 0.310426E+09 0.00 75057.67 0.377770E+09 0.00 30752494.46 0.00 0.53
September 0.951506E+09 11052318.72 0.00 10008.77 0.230649E+09 0.00 3978399.68 0.00 0.55
October 0.181219E+10 0.00 0.00 0.00 17458567.43 0.00 0.00 0.00 0.55
November 0.199548E+10 0.00 0.00 0.00 0.00 0.163069E+09 0.00 0.00 0.53
December 0.171350E+10 0.00 0.00 0.00 0.00 0.426980E+09 0.00 0.00 0.53
                   
Annual Sum or Average 0.149327E+11 0.590349E+09 0.00 126845.04 0.195182E+10 0.304964E+10 53094276.19 0.00 0.54
Minimum of Months 12425604.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.50
Maximum of Months 0.203474E+10 0.310426E+09 0.00 75057.67 0.878719E+09 0.118972E+10 30752494.46 0.00 0.56



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.115600E+10 0.00 0.00 0.119290E+09 0.00 0.00 0.726910E+11 0.00 21.21
February 0.120959E+10 0.00 0.00 91764306.21 0.00 0.00 0.656639E+11 0.00 21.37
March 0.167828E+10 0.00 0.00 0.154112E+09 0.00 0.00 0.718261E+11 0.00 21.30
April 0.108956E+10 8576114.01 0.00 0.138253E+09 0.00 0.00 0.675802E+11 0.00 21.78
May 0.851072E+09 0.304972E+09 0.00 99119174.19 343656.18 0.00 0.567001E+11 0.00 22.74
June 5393020.11 0.151364E+11 0.00 43329880.83 16747778.16 0.00 0.155057E+11 0.00 21.75
July 0.00 0.371132E+11 0.00 4557698.84 40289976.60 0.00 0.779939E+09 0.00 19.90
August 4762834.86 0.226247E+11 0.00 32620049.40 19843787.24 0.00 0.901375E+10 0.00 20.93
September 0.191727E+09 0.818185E+10 0.00 65539752.56 1286741.46 0.00 0.313314E+11 0.00 22.25
October 0.701624E+09 0.521931E+09 0.00 0.114172E+09 0.00 0.00 0.596886E+11 0.00 22.25
November 0.164204E+10 0.00 0.00 0.144259E+09 0.00 0.00 0.708950E+11 0.00 21.21
December 0.118629E+10 0.00 0.00 0.122988E+09 0.00 0.00 0.700516E+11 0.00 21.23
                   
Annual Sum or Average 0.971634E+10 0.838916E+11 0.00 0.113001E+10 78511939.65 0.00 0.591727E+12 0.00 21.49
Minimum of Months 0.00 0.00 0.00 4557698.84 0.00 0.00 0.779939E+09 0.00 19.90
Maximum of Months 0.167828E+10 0.371132E+11 0.00 0.154112E+09 40289976.60 0.00 0.726910E+11 0.00 22.74



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.269682E+11 0.00 0.00 3257268.03 0.00 0.241219E+09 0.380885E+10 0.00 3.73
February 0.224308E+11 0.00 0.00 5871287.47 0.00 0.00 0.579097E+10 0.00 3.77
March 0.191274E+11 0.00 0.00 11825809.62 0.00 0.00 0.114617E+11 0.00 3.73
April 0.152387E+11 5623634.43 0.00 12114635.55 0.00 0.00 0.130612E+11 0.00 3.79
May 0.757063E+10 0.126571E+09 0.00 15152377.88 14653697.46 0.00 0.162311E+11 0.00 3.93
June 0.618039E+09 0.540971E+10 0.00 12071421.99 0.105063E+10 0.00 0.594238E+10 0.00 3.84
July 13585678.84 0.151648E+11 0.00 1932230.40 0.105222E+10 0.00 0.358611E+09 0.00 3.64
August 0.146753E+09 0.100502E+11 0.00 13784050.55 0.349212E+09 0.00 0.398271E+10 0.00 4.00
September 0.226921E+10 0.300663E+10 0.00 23009739.84 0.610812E+09 0.00 0.113564E+11 0.00 4.11
October 0.511354E+10 0.322025E+09 0.00 33914301.59 479265.04 0.00 0.211107E+11 0.00 4.12
November 0.191585E+11 0.00 0.00 10310401.34 0.00 0.00 0.110443E+11 0.00 3.71
December 0.235217E+11 0.00 0.00 7517697.39 0.00 0.00 0.648401E+10 0.00 3.76
                   
Annual Sum or Average 0.142177E+12 0.340855E+11 0.00 0.150761E+09 0.307801E+10 0.241219E+09 0.110633E+12 0.00 3.84
Minimum of Months 13585678.84 0.00 0.00 1932230.40 0.00 0.00 0.358611E+09 0.00 3.64
Maximum of Months 0.269682E+11 0.151648E+11 0.00 33914301.59 0.105222E+10 0.241219E+09 0.211107E+11 0.00 4.12



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.894717E+11 0.00 0.00 2017237.06 0.00 0.00 0.458667E+10 0.00 1.63
February 0.802304E+11 0.00 0.00 1308935.25 0.00 0.00 0.502619E+10 0.00 1.64
March 0.695864E+11 0.00 0.00 18653611.29 0.00 0.00 0.224116E+11 0.00 1.62
April 0.526019E+11 10276312.77 0.00 34916625.18 2233200.68 0.00 0.338867E+11 0.00 1.67
May 0.256964E+11 0.304705E+09 0.00 57392837.73 0.117679E+09 0.00 0.480092E+11 0.00 1.75
June 0.218263E+10 0.158603E+11 0.00 44254951.01 0.459828E+10 0.00 0.189433E+11 0.00 1.77
July 24338842.72 0.470678E+11 0.00 7402704.86 0.473583E+10 0.00 0.122078E+10 0.00 1.69
August 0.322954E+09 0.299076E+11 0.00 45057352.13 0.209433E+10 0.00 0.134286E+11 0.00 1.80
September 0.667063E+10 0.902956E+10 0.00 66914586.59 0.210312E+10 0.00 0.358700E+11 0.00 1.81
October 0.189130E+11 0.692674E+09 0.00 85662698.09 49401303.62 0.00 0.604086E+11 0.00 1.75
November 0.653485E+11 0.00 0.00 23081659.98 0.00 0.00 0.260130E+11 0.00 1.62
December 0.800521E+11 0.00 0.00 4084176.18 0.00 0.00 0.100488E+11 0.00 1.63
                   
Annual Sum or Average 0.491101E+12 0.102873E+12 0.00 0.390747E+09 0.137009E+11 0.00 0.279854E+12 0.00 1.70
Minimum of Months 24338842.72 0.00 0.00 1308935.25 0.00 0.00 0.122078E+10 0.00 1.62
Maximum of Months 0.894717E+11 0.470678E+11 0.00 85662698.09 0.473583E+10 0.00 0.604086E+11 0.00 1.81



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.312751E+09 0.00 0.00 494859.25 0.00 0.123599E+10 36379754.71 0.00 0.47
February 0.323696E+09 0.00 0.00 921087.18 0.00 0.111584E+10 71022571.08 0.00 0.47
March 0.380143E+09 81138.54 0.00 4593474.53 0.00 0.876607E+09 0.369223E+09 0.00 0.47
April 0.309256E+09 2290010.05 0.00 7139893.12 979987.09 0.498533E+09 0.684319E+09 0.00 0.47
May 0.183716E+09 28669821.00 29656.78 11132480.46 5342035.20 65244727.26 0.974720E+09 4534.08 0.47
June 12788305.10 0.721180E+09 383614.11 4470392.53 48215107.66 155643.47 0.195364E+09 15600.29 0.48
July 26656.78 0.140507E+10 1226636.56 112562.81 64206094.42 146.74 1813823.34 21993.82 0.47
August 4704232.42 0.985526E+09 675396.98 2717512.73 38754490.67 80212.04 75386967.02 19384.58 0.47
September 68493438.05 0.361708E+09 488555.28 6899151.15 43498215.38 6402270.81 0.472478E+09 12507.63 0.47
October 0.192397E+09 71204881.38 44939.22 9113954.64 5410952.21 0.147051E+09 0.924096E+09 1020.89 0.47
November 0.408108E+09 0.00 0.00 1634923.24 0.00 0.881372E+09 0.312719E+09 0.00 0.47
December 0.354434E+09 0.00 0.00 582276.70 0.00 0.113395E+10 59056428.28 0.00 0.47
                   
Annual Sum or Average 0.255051E+10 0.357573E+10 2848798.94 49812568.35 0.206407E+09 0.596122E+10 0.417658E+10 75041.29 0.47
Minimum of Months 26656.78 0.00 0.00 112562.81 0.00 146.74 1813823.34 0.00 0.47
Maximum of Months 0.408108E+09 0.140507E+10 1226636.56 11132480.46 64206094.42 0.123599E+10 0.974720E+09 21993.82 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.250186E+09 0.00 0.00 124262.41 0.00 0.132814E+10 6971182.43 0.00 0.47
February 0.254223E+09 0.00 0.00 212363.75 0.00 0.123417E+10 22698875.28 0.00 0.47
March 0.429775E+09 1077.85 0.00 2133443.97 80051.19 0.101239E+10 0.186082E+09 0.00 0.47
April 0.355856E+09 1435574.63 0.00 5132629.87 1834039.38 0.565936E+09 0.572147E+09 0.00 0.47
May 0.214389E+09 28169144.48 29585.56 10183878.04 5838726.74 70472893.54 0.939623E+09 4601.30 0.47
June 14644103.21 0.715519E+09 375593.97 4300281.56 53796135.40 102932.32 0.193706E+09 13936.65 0.48
July 26653.65 0.139843E+10 918485.91 113319.97 70977654.09 146.72 1812840.47 18964.05 0.47
August 5675425.59 0.975649E+09 612323.84 2375906.87 48570597.99 80202.64 74747677.46 23184.52 0.47
September 90225458.36 0.354922E+09 579920.36 5093459.58 50137139.10 7285651.27 0.451604E+09 20848.18 0.47
October 0.276772E+09 58591738.79 42527.31 5133664.11 18013517.29 0.282676E+09 0.707927E+09 5028.27 0.47
November 0.413528E+09 0.00 0.00 541533.94 0.00 0.104752E+10 0.142058E+09 0.00 0.47
December 0.307790E+09 0.00 0.00 92493.98 0.00 0.123726E+10 2699729.75 0.00 0.47
                   
Annual Sum or Average 0.261309E+10 0.353272E+10 2558436.94 35437238.05 0.249248E+09 0.678602E+10 0.330208E+10 86562.97 0.47
Minimum of Months 26653.65 0.00 0.00 92493.98 0.00 146.72 1812840.47 0.00 0.47
Maximum of Months 0.429775E+09 0.139843E+10 918485.91 10183878.04 70977654.09 0.132814E+10 0.939623E+09 23184.52 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.134212E+11 0.00 0.00 1311347.31 0.00 0.767761E+10 0.399338E+09 0.00 0.53
February 0.164697E+11 0.00 0.00 6134944.18 0.00 0.296896E+10 0.104948E+10 0.00 0.53
March 0.189000E+11 1100165.90 0.00 16564954.96 0.00 0.345252E+09 0.284716E+10 0.00 0.53
April 0.165427E+11 44338228.43 0.00 20322876.39 0.00 0.00 0.376542E+10 0.00 0.54
May 0.107996E+11 0.440897E+09 0.00 33074262.69 20736933.48 0.00 0.591025E+10 0.00 0.54
June 0.137743E+10 0.969709E+10 0.00 15156865.35 0.740629E+09 0.00 0.149249E+10 0.00 0.54
July 0.00 0.196543E+11 0.00 691818.26 0.284613E+09 0.00 25791681.73 0.00 0.54
August 0.192600E+09 0.138805E+11 0.00 17051259.91 17215079.38 0.00 0.914249E+09 0.00 0.54
September 0.297717E+10 0.536584E+10 0.00 46446645.69 0.135188E+09 0.00 0.449183E+10 0.00 0.54
October 0.624910E+10 0.101999E+10 0.00 81508424.60 19472083.02 0.00 0.109255E+11 0.00 0.54
November 0.171176E+11 0.00 0.00 24314879.51 0.00 0.189910E+09 0.441468E+10 0.00 0.54
December 0.157318E+11 0.00 0.00 14355373.12 0.00 0.355769E+10 0.168596E+10 0.00 0.54
                   
Annual Sum or Average 0.119779E+12 0.501041E+11 0.00 0.276934E+09 0.121785E+10 0.147394E+11 0.379221E+11 0.00 0.54
Minimum of Months 0.00 0.00 0.00 691818.26 0.00 0.00 25791681.73 0.00 0.53
Maximum of Months 0.189000E+11 0.196543E+11 0.00 81508424.60 0.740629E+09 0.767761E+10 0.109255E+11 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.560565E+10 0.00 0.00 4056399.21 0.00 0.139506E+11 0.194508E+10 0.00 0.53
February 0.554248E+10 0.00 0.00 1831746.36 0.00 0.135923E+11 0.136330E+10 0.00 0.53
March 0.621014E+10 14620.36 0.00 24664564.50 1085846.38 0.684424E+10 0.903603E+10 0.00 0.53
April 0.539657E+10 10324357.25 67027.48 55464668.40 33953031.41 0.112894E+10 0.137530E+11 5936.49 0.54
May 0.390529E+10 0.280290E+09 187766.58 89854283.94 0.181264E+09 39183467.56 0.127132E+11 18493.99 0.54
June 0.345556E+09 0.793239E+10 3021409.56 31966660.33 0.250512E+10 1252294.20 0.250709E+10 47537.13 0.54
July 1342130.99 0.167183E+11 5957708.97 1039467.75 0.322006E+10 0.00 24109143.12 36512.58 0.54
August 99511846.19 0.112823E+11 8537066.70 16896832.66 0.261069E+10 144712.47 0.100765E+10 69559.22 0.54
September 0.148733E+10 0.390638E+10 5305468.65 41818253.83 0.159081E+10 11283332.57 0.597707E+10 39627.99 0.54
October 0.431940E+10 0.485255E+09 2304008.11 50924153.73 0.552160E+09 0.231151E+09 0.126593E+11 30127.57 0.54
November 0.609370E+10 0.00 0.00 25704413.84 0.00 0.555339E+10 0.100797E+11 0.00 0.54
December 0.584248E+10 0.00 0.00 4239674.63 0.00 0.130278E+11 0.212095E+10 0.00 0.54
                   
Annual Sum or Average 0.448495E+11 0.406152E+11 25380456.06 0.348461E+09 0.106951E+11 0.543802E+11 0.731866E+11 247794.97 0.54
Minimum of Months 1342130.99 0.00 0.00 1039467.75 0.00 0.00 24109143.12 0.00 0.53
Maximum of Months 0.621014E+10 0.167183E+11 8537066.70 89854283.94 0.322006E+10 0.139506E+11 0.137530E+11 69559.22 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.329702E+09 0.00 0.00 599618.69 0.00 0.120738E+10 47929788.74 0.00 0.47
February 0.354689E+09 0.00 0.00 824418.12 0.00 0.106928E+10 86690113.31 0.00 0.47
March 0.368933E+09 1077.97 0.00 4080000.09 80060.57 0.888074E+09 0.369480E+09 0.00 0.47
April 0.272440E+09 2999778.45 0.00 7962215.60 270218.69 0.483071E+09 0.735775E+09 0.00 0.47
May 0.150303E+09 30445233.03 14563.42 12036871.72 3585606.24 72996582.75 0.999477E+09 644.39 0.47
June 6522095.58 0.726312E+09 193924.09 5048870.55 43280166.61 122237.03 0.201085E+09 8128.83 0.48
July 0.00 0.142072E+10 169395.58 163733.47 49627965.69 0.00 1789456.18 6095.01 0.47
August 1294966.30 0.998343E+09 34429.23 3116613.53 26595673.02 0.00 78477344.38 1769.85 0.47
September 51199258.54 0.364428E+09 425843.31 8040692.10 40845577.73 5746064.18 0.489287E+09 8243.64 0.47
October 0.147649E+09 72607889.29 35745.69 9943885.02 4016799.27 0.163944E+09 0.951122E+09 1359.46 0.47
November 0.399382E+09 0.00 0.00 2657465.78 0.00 0.833248E+09 0.368545E+09 0.00 0.47
December 0.366202E+09 0.00 0.00 961359.87 0.00 0.109726E+10 83598842.69 0.00 0.47
                   
Annual Sum or Average 0.244832E+10 0.361586E+10 873901.31 55435744.57 0.168302E+09 0.582111E+10 0.441326E+10 26241.18 0.47
Minimum of Months 0.00 0.00 0.00 163733.47 0.00 0.00 1789456.18 0.00 0.47
Maximum of Months 0.399382E+09 0.142072E+10 425843.31 12036871.72 49627965.69 0.120738E+10 0.999477E+09 8243.64 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.234472E+09 0.00 0.00 143530.37 0.00 0.133565E+10 15162883.25 0.00 0.47
February 0.259025E+09 0.00 0.00 206075.34 0.00 0.122259E+10 29483950.62 0.00 0.47
March 0.436698E+09 1077.85 0.00 1633365.02 80051.19 0.101243E+10 0.179616E+09 0.00 0.47
April 0.343117E+09 2663373.40 0.00 5598363.79 605893.47 0.553326E+09 0.597031E+09 347.14 0.47
May 0.156188E+09 29972069.51 14543.43 11003350.03 4054782.55 81378024.28 0.986099E+09 662.59 0.47
June 6709099.85 0.723502E+09 171011.76 4871410.67 46024873.13 82525.64 0.201090E+09 6117.14 0.48
July 0.00 0.141767E+10 170593.81 163734.72 52499251.25 0.00 1789226.10 4876.22 0.47
August 1589202.50 0.994122E+09 34893.61 2744618.08 30696858.06 0.00 78545391.98 1301.24 0.47
September 63753530.95 0.360079E+09 512769.62 6027165.89 45055959.91 5939592.79 0.478488E+09 11973.75 0.47
October 0.304281E+09 68728303.90 162266.74 5345101.01 7752375.91 0.280836E+09 0.682046E+09 9865.11 0.47
November 0.410340E+09 0.00 0.00 935043.22 0.00 0.994269E+09 0.198101E+09 0.00 0.47
December 0.295763E+09 0.00 0.00 191991.36 0.00 0.122396E+10 27919796.15 0.00 0.47
                   
Annual Sum or Average 0.251194E+10 0.359674E+10 1066078.98 38863749.50 0.186770E+09 0.671046E+10 0.347537E+10 35143.18 0.47
Minimum of Months 0.00 0.00 0.00 143530.37 0.00 0.00 1789226.10 0.00 0.47
Maximum of Months 0.436698E+09 0.141767E+10 512769.62 11003350.03 52499251.25 0.133565E+10 0.986099E+09 11973.75 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.256523E+11 0.00 0.00 0.00 0.00 0.402976E+10 0.00 0.00 0.56
February 0.243119E+11 0.00 0.00 0.00 0.00 0.262136E+10 0.00 0.00 0.56
March 0.289275E+11 0.00 0.00 0.00 0.00 12258454.02 0.00 0.00 0.55
April 0.270453E+11 0.00 0.00 0.00 3951802.24 0.00 0.00 0.00 0.57
May 0.227738E+11 0.00 0.00 14387.08 0.133237E+09 0.00 18568695.80 0.00 0.59
June 0.604385E+10 0.960711E+09 0.00 617776.57 0.513627E+10 0.00 0.205812E+09 0.00 0.57
July 0.116249E+09 0.725315E+10 0.00 787434.71 0.779761E+10 0.00 0.225455E+09 0.00 0.53
August 0.215365E+10 0.733763E+10 0.00 4055634.30 0.202904E+10 0.00 0.166311E+10 0.00 0.56
September 0.119619E+11 0.115044E+10 0.00 1185459.40 0.208364E+10 0.00 0.737016E+09 0.00 0.58
October 0.240837E+11 0.00 0.00 0.00 0.232021E+09 0.00 0.00 0.00 0.58
November 0.286591E+11 0.00 0.00 0.00 0.00 27728132.58 0.00 0.00 0.55
December 0.271733E+11 0.00 0.00 0.00 0.00 0.127339E+10 0.00 0.00 0.56
                   
Annual Sum or Average 0.228903E+12 0.167019E+11 0.00 6660692.06 0.174158E+11 0.796450E+10 0.284996E+10 0.00 0.56
Minimum of Months 0.116249E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.53
Maximum of Months 0.289275E+11 0.733763E+10 0.00 4055634.30 0.779761E+10 0.402976E+10 0.166311E+10 0.00 0.59



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 62977744.84 0.00 0.00 119038.72 0.00 0.327042E+09 6263967.02 0.00 0.47
February 69882999.71 0.00 0.00 226006.38 0.00 0.294311E+09 13449257.73 0.00 0.47
March 89737627.43 18306.49 0.00 1094833.53 1978.14 0.246971E+09 69838423.85 0.00 0.47
April 75117304.60 573486.59 0.00 1668402.00 244012.69 0.155671E+09 0.142356E+09 0.00 0.47
May 44688011.61 7220427.53 7480.91 2603433.24 1282536.53 41825888.03 0.219586E+09 1066.81 0.47
June 3274543.29 0.179596E+09 104266.52 1052979.26 12745010.87 58858.34 48808083.68 3818.89 0.48
July 9795.33 0.350919E+09 326414.36 24392.66 16377975.36 36.68 454072.74 6566.32 0.47
August 1327751.00 0.246188E+09 191683.27 631107.69 9859308.82 15581.78 18747790.58 5048.47 0.47
September 17156065.43 90240149.34 123146.89 1569676.95 11059161.40 4980851.69 0.114862E+09 4362.76 0.47
October 51925989.86 17760219.10 0.00 1821028.47 1405229.32 76091297.39 0.188326E+09 0.00 0.47
November 96438213.12 0.00 0.00 317828.79 0.00 0.251958E+09 52244082.40 0.00 0.47
December 76494343.10 0.00 0.00 135162.72 0.00 0.301683E+09 8691911.06 0.00 0.47
                   
Annual Sum or Average 0.589030E+09 0.892515E+09 752991.96 11263890.41 52975213.13 0.170061E+10 0.883627E+09 20863.24 0.47
Minimum of Months 9795.33 0.00 0.00 24392.66 0.00 36.68 454072.74 0.00 0.47
Maximum of Months 96438213.12 0.350919E+09 326414.36 2603433.24 16377975.36 0.327042E+09 0.219586E+09 6566.32 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 35931139.62 0.00 0.00 37379.73 0.00 0.358984E+09 1404247.38 0.00 0.47
February 45446198.84 0.00 0.00 47186.60 0.00 0.328184E+09 4148166.07 0.00 0.47
March 96962207.90 269.46 0.00 494545.74 20012.80 0.275116E+09 35020812.62 0.00 0.47
April 86102610.60 371219.91 0.00 1178681.34 446183.59 0.171485E+09 0.116002E+09 0.00 0.47
May 51685435.91 7115473.83 7470.62 2359742.70 1386493.97 44626565.42 0.209995E+09 1076.10 0.47
June 3609246.00 0.178437E+09 91837.97 1010643.37 13893576.38 63527.61 48504815.09 3670.69 0.48
July 9794.19 0.349447E+09 295735.38 24446.56 17837918.18 36.68 453962.78 6150.97 0.47
August 1437730.96 0.243646E+09 191018.28 542920.11 12371346.13 4620.63 18734531.45 5690.40 0.47
September 22076192.70 88440870.78 161787.52 1097306.18 12807081.33 10466959.05 0.104912E+09 5197.12 0.47
October 71568552.36 14760982.06 15662.94 945470.09 4384673.28 0.119051E+09 0.126563E+09 1884.64 0.47
November 87694617.85 0.00 0.00 108798.36 0.00 0.297840E+09 15268312.39 0.00 0.47
December 51529205.92 0.00 0.00 42169.89 0.00 0.334465E+09 923167.11 0.00 0.47
                   
Annual Sum or Average 0.554053E+09 0.882219E+09 763512.71 7889290.66 63147285.67 0.194029E+10 0.681930E+09 23669.92 0.47
Minimum of Months 9794.19 0.00 0.00 24446.56 0.00 36.68 453962.78 0.00 0.47
Maximum of Months 96962207.90 0.349447E+09 295735.38 2359742.70 17837918.18 0.358984E+09 0.209995E+09 6150.97 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.459472E+09 0.00 0.00 4607333.37 0.00 0.170139E+10 0.381219E+09 0.00 0.53
February 0.401241E+09 0.00 0.00 6773270.66 0.00 0.140934E+10 0.610263E+09 0.00 0.54
March 0.461819E+09 130318.43 0.00 12308119.23 0.00 0.111071E+10 0.103405E+10 0.00 0.53
April 0.437157E+09 4434136.12 0.00 11593019.35 817879.32 0.653601E+09 0.130562E+10 0.00 0.54
May 0.293536E+09 44979659.86 47534.46 13665524.40 9649721.47 60288153.00 0.161577E+10 5200.84 0.54
June 26281626.71 0.113732E+10 479353.02 5116042.29 98562704.73 261616.90 0.310088E+09 21721.16 0.54
July 62930.02 0.223144E+10 1313182.26 143657.23 0.129047E+09 235.68 2930238.61 35300.55 0.54
August 8252953.24 0.157365E+10 482942.77 3758232.59 72075314.81 128830.35 0.120990E+09 25069.16 0.54
September 0.103311E+09 0.579434E+09 400915.39 12181709.48 71775284.64 4694115.60 0.770044E+09 5474.19 0.54
October 0.223617E+09 0.117860E+09 37804.78 21056295.69 5227151.12 0.115861E+09 0.168351E+10 3051.81 0.54
November 0.492999E+09 0.00 0.00 9686650.23 0.00 0.100823E+10 0.106504E+10 0.00 0.54
December 0.442418E+09 0.00 0.00 8815683.07 0.00 0.142828E+10 0.606794E+09 0.00 0.54
                   
Annual Sum or Average 0.335017E+10 0.568925E+10 2761732.70 0.109706E+09 0.387155E+09 0.749279E+10 0.950632E+10 95817.72 0.54
Minimum of Months 62930.02 0.00 0.00 143657.23 0.00 235.68 2930238.61 0.00 0.53
Maximum of Months 0.492999E+09 0.223144E+10 1313182.26 21056295.69 0.129047E+09 0.170139E+10 0.168351E+10 35300.55 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.118616E+11 0.00 0.00 43257091.51 0.00 0.00 0.328863E+11 0.00 3.98
February 0.103072E+11 0.00 0.00 33033807.91 0.00 0.00 0.299349E+11 0.00 3.99
March 0.532038E+10 0.00 0.00 81972657.29 0.00 0.00 0.412654E+11 0.00 4.17
April 0.231610E+10 5912676.99 0.00 89233833.02 0.00 0.00 0.431329E+11 0.00 4.43
May 0.116280E+09 0.214074E+09 0.00 90021895.47 152194.84 0.00 0.412664E+11 0.00 4.91
June 0.00 0.110503E+11 0.00 42160950.39 0.00 0.00 0.122427E+11 0.00 5.04
July 0.00 0.283904E+11 0.00 4805032.65 0.00 0.00 0.693571E+09 0.00 4.77
August 0.00 0.170539E+11 0.00 31997567.24 0.00 0.00 0.765134E+10 0.00 4.95
September 33302249.03 0.581306E+10 0.00 57458623.83 0.00 0.00 0.231743E+11 0.00 4.93
October 0.101233E+10 0.346602E+09 0.00 84016956.37 5069721.65 0.00 0.402537E+11 0.00 4.61
November 0.590983E+10 0.00 0.00 77471354.66 0.00 0.00 0.402333E+11 0.00 4.16
December 0.906146E+10 0.00 0.00 49698407.17 0.00 0.00 0.342764E+11 0.00 4.02
                   
Annual Sum or Average 0.459385E+11 0.628743E+11 0.00 0.685128E+09 5221916.49 0.00 0.347011E+12 0.00 4.50
Minimum of Months 0.00 0.00 0.00 4805032.65 0.00 0.00 0.693571E+09 0.00 3.98
Maximum of Months 0.118616E+11 0.283904E+11 0.00 90021895.47 5069721.65 0.00 0.431329E+11 0.00 5.04



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.719432E+10 0.00 0.00 59926869.13 0.00 0.00 0.409952E+11 0.00 4.29
February 0.662317E+10 0.00 0.00 46778536.17 0.00 0.00 0.367180E+11 0.00 4.29
March 0.226417E+10 0.00 0.00 0.108182E+09 0.00 0.00 0.485704E+11 0.00 4.54
April 0.805596E+09 6393887.80 0.00 0.111335E+09 0.00 0.00 0.486420E+11 0.00 4.81
May 12928494.81 0.230616E+09 0.00 0.102134E+09 0.00 0.00 0.447430E+11 0.00 5.31
June 0.00 0.117957E+11 0.00 45670438.44 0.00 0.00 0.130269E+11 0.00 5.38
July 0.00 0.301709E+11 0.00 5077109.04 0.00 0.00 0.729112E+09 0.00 5.06
August 0.00 0.181116E+11 0.00 34454445.42 0.00 0.00 0.807365E+10 0.00 5.25
September 1647149.50 0.620072E+10 0.00 64077331.14 0.00 0.00 0.248852E+11 0.00 5.27
October 0.298857E+09 0.377115E+09 0.00 99038626.47 0.00 0.00 0.442104E+11 0.00 4.96
November 0.244396E+10 0.00 0.00 0.101598E+09 0.00 0.00 0.477358E+11 0.00 4.51
December 0.339700E+10 0.00 0.00 68771393.19 0.00 0.00 0.437210E+11 0.00 4.36
                   
Annual Sum or Average 0.230416E+11 0.668930E+11 0.00 0.847043E+09 0.00 0.00 0.402051E+12 0.00 4.84
Minimum of Months 0.00 0.00 0.00 5077109.04 0.00 0.00 0.729112E+09 0.00 4.29
Maximum of Months 0.719432E+10 0.301709E+11 0.00 0.111335E+09 0.00 0.00 0.486420E+11 0.00 5.38



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 37185826.17 0.00 0.00 0.147168E+09 0.00 0.00 0.650354E+11 0.00 18.70
February 22089806.36 0.00 0.00 0.124644E+09 0.00 0.00 0.593511E+11 0.00 18.95
March 39651122.76 0.00 0.00 0.200072E+09 0.00 0.00 0.663128E+11 0.00 19.39
April 40464280.72 11264844.79 0.00 0.175635E+09 0.00 0.00 0.621253E+11 0.00 20.30
May 38845820.02 0.380269E+09 0.00 0.127937E+09 0.00 0.00 0.520831E+11 0.00 21.83
June 0.00 0.159647E+11 0.00 54672527.69 0.00 0.00 0.135654E+11 0.00 21.17
July 0.00 0.377019E+11 0.00 4923060.98 0.00 0.00 0.655407E+09 0.00 19.72
August 0.00 0.236241E+11 0.00 40239177.66 0.00 0.00 0.767869E+10 0.00 20.55
September 2172050.35 0.824874E+10 0.00 84246285.18 0.00 0.00 0.284169E+11 0.00 21.48
October 81205672.00 0.659619E+09 0.00 0.144215E+09 0.00 0.00 0.548495E+11 0.00 20.96
November 0.108596E+09 0.00 0.00 0.182333E+09 0.00 0.00 0.651738E+11 0.00 19.29
December 17368645.33 0.00 0.00 0.157129E+09 0.00 0.00 0.632217E+11 0.00 18.94
                   
Annual Sum or Average 0.387579E+09 0.865906E+11 0.00 0.144321E+10 0.00 0.00 0.538469E+12 0.00 20.11
Minimum of Months 0.00 0.00 0.00 4923060.98 0.00 0.00 0.655407E+09 0.00 18.70
Maximum of Months 0.108596E+09 0.377019E+11 0.00 0.200072E+09 0.00 0.00 0.663128E+11 0.00 21.83



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.111717E+11 0.00 0.00 0.00 0.00 0.411425E+10 0.00 0.00 1.09
February 0.100749E+11 0.00 0.00 0.00 0.00 0.379549E+10 0.00 0.00 1.10
March 0.147390E+11 0.00 0.00 0.00 0.00 0.164645E+09 0.00 0.00 1.08
April 0.139122E+11 0.00 0.00 19592.68 2035134.64 0.00 15788949.17 0.00 1.10
May 0.116224E+11 64578226.35 0.00 238615.88 8562951.19 0.00 0.115187E+09 0.00 1.15
June 0.261348E+10 0.205671E+10 0.00 1277346.22 0.115570E+10 0.00 0.605370E+09 0.00 1.13
July 54738887.45 0.679203E+10 0.00 429363.95 0.136484E+10 0.00 0.119697E+09 0.00 1.08
August 0.123397E+10 0.484908E+10 0.00 2622443.80 0.376636E+09 0.00 0.720609E+09 0.00 1.15
September 0.585582E+10 0.848922E+09 0.00 1729350.00 0.850829E+09 0.00 0.684987E+09 0.00 1.15
October 0.123494E+11 55994792.63 0.00 45980.66 63493693.01 0.00 53435165.64 0.00 1.12
November 0.143795E+11 0.00 0.00 0.00 0.00 0.393867E+09 0.00 0.00 1.07
December 0.138569E+11 0.00 0.00 0.00 0.00 0.792817E+09 0.00 0.00 1.09
                   
Annual Sum or Average 0.111864E+12 0.146673E+11 0.00 6362693.19 0.382210E+10 0.926107E+10 0.231507E+10 0.00 1.11
Minimum of Months 54738887.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.07
Maximum of Months 0.147390E+11 0.679203E+10 0.00 2622443.80 0.136484E+10 0.411425E+10 0.720609E+09 0.00 1.15



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:59:43

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.141688E+12 0.202491E+11 0.253798E+12 0.103743E+13 0.784514E+11
February 0.233127E+12 0.193764E+11 0.240357E+12 0.993798E+12 0.708532E+11
March 0.417057E+12 0.165145E+11 0.208643E+12 0.862918E+12 0.776675E+11
April 0.444255E+12 0.113490E+11 0.144428E+12 0.608279E+12 0.140587E+12
May 0.572562E+12 0.723331E+10 0.886016E+11 0.404210E+12 0.322813E+12
June 0.568509E+12 -0.227527E+10 -0.171036E+11 -0.676713E+11 0.987834E+12
July 0.540581E+12 -0.962532E+10 -0.109368E+12 -0.488402E+12 0.146948E+13
August 0.515805E+12 -0.558824E+10 -0.685333E+11 -0.283944E+12 0.126554E+13
September 0.354700E+12 0.169621E+10 0.274823E+11 0.128387E+12 0.728301E+12
October 0.342086E+12 0.856249E+10 0.105015E+12 0.476980E+12 0.332032E+12
November 0.166805E+12 0.143391E+11 0.183493E+12 0.762881E+12 0.803258E+11
December 0.114099E+12 0.182674E+11 0.235464E+12 0.957195E+12 0.719396E+11
           
Annual Sum or Average 0.441128E+13 0.100099E+12 0.129228E+13 0.539207E+13 0.562582E+13
Minimum of Months 0.114099E+12 -0.962532E+10 -0.109368E+12 -0.488402E+12 0.708532E+11
Maximum of Months 0.572562E+12 0.202491E+11 0.253798E+12 0.103743E+13 0.146948E+13