Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:59

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885

Simulation Timestamp: 2023-10-16 08:59:48


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 10497.00 925.23 925.23
Net Site Energy 10497.00 925.23 925.23
Total Source Energy 21143.85 1863.67 1863.67
Net Source Energy 21143.85 1863.67 1863.67


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 772.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 268.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 766.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 242.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1745.01 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 651.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 537.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 102.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 222.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.75 3247.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 62.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 4688.00 5809.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 772.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 268.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 766.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 242.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 959.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 14.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 8.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 32.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 537.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 102.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 222.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.75 3247.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 20.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 34.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 772.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 268.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 766.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 242.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1745.01 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 651.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 537.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 102.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 222.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 90.75 3247.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 62.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 88.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 88.01 354.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 236.29 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 413.21 512.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 88.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 88.01 354.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 236.29 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 413.21 512.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 4687.998 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 4687.998 100.00
     
Total On-Site and Utility Electric Sources 4687.998 100.00
Total Electricity End Uses 4687.998 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 1.45 0.05
Air to Air Heat Recovery for Heating 3121.81 99.95
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 3123.26 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.67
Time Setpoint Not Met During Occupied Cooling 524.33
Time Not Comfortable Based on Simple ASHRAE 55-2004 7427.33


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:59
RunPeriod RUNPERIOD 1
Weather File William R Fairchild WA USA TMY3 WMO#=727885
Latitude [deg] 48.12
Longitude [deg] -123.5
Elevation [m] 91.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 9.1389 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 13.3365 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 13.3365 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 9.2031 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 6.1031 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.8125 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 10.3656 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 8.7188 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 4.5531 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 4.5531 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 6.3938 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 4.5531 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.3656 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.3656 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 11.7219 4.65 2934.4875
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 6.3938 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 6.8557 7.07 41.0709
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 6.8557 7.07 41.0709
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 9.1389 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 13.3365 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 13.3365 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 9.2031 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 6.1031 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.8125 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 10.3656 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 8.7188 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 4.5531 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 4.5531 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 4.5531 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 4.5531 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 4.5531 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 4.5531 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 6.3938 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 4.5531 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 4.5531 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 4.5531 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 10.3656 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 10.3656 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 11.7219 4.65 2934.4875  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 6.3938 18.58 0.0000  
Total 11345.29             6.8557 3.54 41.0709  
Conditioned Total 11345.29             6.8557 3.54 41.0709  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 4.4542 8.82 37.1989
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 22-JUL-18:19 06-JAN-18:40 - - - - - - - - - - 13-JAN-21:00
Heating 0.00 157962.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 117506.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 50105.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 76444.94 104248.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 31760.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 27041.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 7409.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 4182.83 268895.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 2385.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 326774.97 531106.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 157962.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 117506.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 50105.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 46461.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 29272.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1456.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 30153.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 150.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 27041.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 7409.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 4182.83 268895.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 216.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 1088.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 1080.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 837.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 849.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2427.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 767.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5526.46 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2063.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1701.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 324.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 703.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 287.39 3520.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 196.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 14846.89 6296.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 73.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 74.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 213.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 67.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 487.11 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 149.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 28.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 62.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 310.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1308.64 555.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 73.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 74.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 213.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 67.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 487.11 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 149.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 28.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 62.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 310.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1308.64 555.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.53 0.595538 0.515000 1.30 1.00 0.500000 0.000640 0.000072 1.30 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.471024 0.108505 0.515000 0.242577 0.515000 0.500000 0.003511 0.000032 0.242577 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.237742 0.248941 0.515000 0.122437 0.663843 0.500000 0.001530 0.000013 0.122437 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.211478 0.591803 0.515000 0.108911 1.00 0.500000 0.000644 0.000018 0.108911 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.100951 0.715264 0.515000 0.051990 1.00 0.500000 0.000533 0.000010 0.051990 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.28 0.071927 0.515000 1.69 0.515000 0.500000 0.021020 0.000094 1.69 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.83 0.078761 0.515000 0.941009 0.515000 0.500000 0.004837 0.000095 0.941009 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 5.02 0.198622 0.515000 2.58 0.529659 0.500000 0.001918 0.000241 2.58 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.53 0.774347 0.515000 0.789383 1.00 0.500000 0.000492 0.000108 0.789383 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.12 0.119309 0.515000 1.09 0.515000 0.500000 0.003193 0.000097 1.09 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.22 0.113887 0.515000 1.14 0.515000 0.500000 0.003345 0.000100 1.14 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.27 0.062241 0.515000 1.17 0.515000 0.500000 0.011010 0.000067 1.17 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.811229 0.387115 0.515000 0.417783 1.00 0.500000 0.000984 0.000069 0.417783 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 8256.54 0.000072 174.09
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 3618.77 0.000032 83.59
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1431.81 0.000013 31.92
MECH_FLR_1 VAV BOX REHEAT COIL 2051.88 0.000018 49.59
STORAGE_FLR_1 VAV BOX REHEAT COIL 1179.31 0.000010 29.88
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 10740.11 0.000094 226.51
CAFE_FLR_1 VAV BOX REHEAT COIL 10827.15 0.000095 240.88
LOBBY_FLR_1 VAV BOX REHEAT COIL 27586.81 0.000241 608.32
ROOM_1_FLR_3 FAN COIL HEATING COIL 5214.33 0.000046 149.01
ROOM_2_FLR_3 FAN COIL HEATING COIL 5220.08 0.000046 149.18
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 29871.03 0.000261 853.63
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 29995.18 0.000262 857.17
ROOM_5_FLR_3 FAN COIL HEATING COIL 5202.13 0.000046 148.66
ROOM_6_FLR_3 FAN COIL HEATING COIL 5207.89 0.000046 148.83
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 12363.68 0.000108 288.00
ROOM_1_FLR_6 FAN COIL HEATING COIL 1615.51 0.000014 46.16
ROOM_2_FLR_6 FAN COIL HEATING COIL 1616.97 0.000014 46.21
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 7750.44 0.000068 221.48
BANQUET_FLR_6 VAV BOX REHEAT COIL 11065.50 0.000097 242.67
DINING_FLR_6 VAV BOX REHEAT COIL 11449.64 0.000100 250.76
KITCHEN_FLR_6 VAV BOX REHEAT COIL 7614.60 0.000067 160.83
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 7840.42 0.000069 189.34
VAV WITH REHEAT HEATING COIL 169799.33 0.001485 2897.26
FLR_3_DOAS HEATING COIL 15471.26 0.000135 263.98
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ZoneExhaust

User-Specified Maximum Flow Rate [m3/s]
LOBBY_FLR_1 EXHAUST FAN 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 1.17 0.000046 0.000461
ROOM_2_FLR_3 FAN COIL 1.04 0.000046 0.000410
ROOM_3_MULT19_FLR_3 FAN COIL 8.01 0.000261 0.003094
ROOM_4_MULT19_FLR_3 FAN COIL 4.76 0.000262 0.001986
ROOM_5_FLR_3 FAN COIL 1.06 0.000046 0.000417
ROOM_6_FLR_3 FAN COIL 0.947348 0.000046 0.000373
ROOM_1_FLR_6 FAN COIL 0.309034 0.000014 0.000121
ROOM_2_FLR_6 FAN COIL 0.271857 0.000014 0.000107
ROOM_3_MULT9_FLR_6 FAN COIL 1.70 0.000068 0.000675
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 1.17
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 1.04
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 8.01
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 4.76
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 1.06
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 0.947348
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.309034
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.271857
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.70
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008561 12.80 0.008500 0.000461 1.17  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008568 12.80 0.008500 0.000410 1.04  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008499 12.80 0.008499 0.003094 8.01  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008790 12.80 0.008500 0.001986 4.76  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008567 12.80 0.008500 0.000417 1.06  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008575 12.80 0.008500 0.000373 0.947348  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008558 12.80 0.008500 0.000121 0.309034  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008565 12.80 0.008500 0.000107 0.271857  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008596 12.80 0.008500 0.000675 1.70  
VAV WITH REHEAT COOLING COIL 25.24 6.70 0.008987 10.96 0.008500 0.015152 22.51 424222.09
FLR_3_DOAS COOLING COIL 26.40 6.70 0.008407 11.92 0.008407 0.001290 2.05 36112.10
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 11.66 11.66 22.64 11.66 22.51 22.51 0.300000 0.517800 22.51
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 22.51 11.66
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 11.66
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 22.51
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.015152 0.000031
VAV WITH REHEAT_HEATC_CONTROLLER 0.001485  
FLR_3_DOAS_COOLC_CONTROLLER 0.001290 0.000369
FLR_3_DOAS_HEATC_CONTROLLER 0.000135  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.024085 4963.10  
HEATSYS1 PUMP 0.003438 1035.39 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.003438 0.412566
COOLSYS1 0.024085 2.89
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 392990.38 392990.38 0.003438
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.024085 3436.12
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.024085 674325.42 674948.88 76.94
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 9.30 6.70 4.10 4.20 4.20 5.90 9.00 10.00 13.30 15.00 15.70 13.40


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 William R Fairchild WA USA TMY3 WMO#=727885 48.12 -123.50 -8.00 91.00 100237 1.1914


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 9.23 11.60 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 9.139 5.380 0.000 0.000 0.000 0.000 14.519 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 13.336 10.760 0.000 0.000 0.000 0.000 24.096 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 13.336 10.760 0.000 0.000 0.000 0.000 24.096 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 9.203 5.380 0.000 0.000 0.000 0.000 14.583 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 6.103 2.690 0.000 0.000 0.000 0.000 8.793 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.813 61.680 535.850 0.000 0.000 0.000 603.343 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 10.366 5.380 0.000 0.000 0.000 0.000 15.746 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 8.719 8.070 0.000 0.000 0.000 0.000 16.789 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 6.394 0.000 0.000 0.000 0.000 0.000 6.394 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 10.366 67.820 0.000 0.000 0.000 0.000 78.186 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 10.366 67.820 0.000 0.000 0.000 0.000 78.186 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 11.722 515.227 2419.260 0.000 0.000 0.000 2946.209 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 6.394 0.000 0.000 0.000 0.000 0.000 6.394 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 18084.325 9.139 169.807 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 18084.325
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 894.495 13.336 82.602 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 894.495
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 1035.829 13.336 82.602 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1035.829
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 1511.551 9.203 569.967 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1511.551
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 578.329 6.103 283.494 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 578.329
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 453.605 5.813 54.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 453.605
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1957.673 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1957.673
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 11405.759 8.719 27.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 11405.759
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 111.660 4.553 74.440 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.660
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 111.691 4.553 74.460 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.691
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 2489.757 6.394 118.803 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2489.757
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 111.691 4.553 74.460 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.691
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 3437.839 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3437.839
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 3437.839 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3437.839
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1210.923 11.722 54.453 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1210.923
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 2635.024 6.394 118.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2635.024


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 457.500 4.429 20.573 0.000 0.250 0.000 0.750 ReachInFreezer 457.500 457.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 285.000 2.759 12.816 0.000 0.250 0.000 0.750 ReachInRefrigerator 285.000 285.000


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.198 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.1864 0.900 0.900 0.770 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.1864 0.900 0.900 0.770 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 0.8226 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.107 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.174 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.031 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.097 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.8346
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.048
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.7359
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6841
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.8028
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.7445
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.312
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.312
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.312
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.312
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.1981135 1.1981135 1.1981135  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
21 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
22 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
23 0 21.357363 0.71091016E-01 5.4032014  
24 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
25 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
26 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
27 0 21.357363 0.71091016E-01 5.4032014  
28 9 -0.17638513E-14 0.32473881E-16 -0.15472737E-09 0.39084990E-16
29 8 0.22578286E-07 0.11136169E-12 0.38514655E-03 -0.25672286E-09
30 7 -0.12460867E-01 0.57383191E-08 -0.23401545E-01 0.14168460E-03
31 6 0.41130930 0.19934685E-05 0.47716306 -0.48180040E-02
32 5 -5.2487139 0.74343025E-04 -4.4802041 0.63904887E-01
33 4 33.260058 0.60748543E-03 21.592533 -0.42553784
34 3 -111.77343 0.13226915E-02 -55.924898 1.5231004
35 2 197.67353 0.74337769E-03 78.150831 -2.9093300
36 1 -171.36487 0.79295509E-04 -55.335031 2.7490988
37 0 57.057407 0.45097929E-06 15.545453  
38 9 -0.19728226E-15 0.38070760E-16 -0.14134637E-09 0.10329039E-17
39 8 0.20696804E-07 0.14765672E-12 0.36530744E-03 -0.23532978E-09
40 7 -0.11868633E-01 0.77667999E-08 -0.22548754E-01 0.13495068E-03
41 6 0.39521686 0.27204939E-05 0.46345169 -0.46283129E-02
42 5 -5.0916664 0.10217830E-03 -4.3748670 0.61957574E-01
43 4 32.565369 0.84029717E-03 21.180735 -0.41631434
44 3 -110.29532 0.18400486E-02 -55.110745 1.5017457
45 2 196.20849 0.10394005E-02 77.404245 -2.8860650
46 1 -170.82368 0.11139293E-03 -55.118150 2.7396138
47 0 57.057407 0.63685742E-06 15.581450  
48 9 0.13059652E-14 0.41030072E-16 -0.13816519E-09 -0.47111965E-17
49 8 0.20247126E-07 0.15597406E-12 0.36047671E-03 -0.23021680E-09
50 7 -0.11724123E-01 0.82470298E-08 -0.22340566E-01 0.13330755E-03
51 6 0.39128975 0.28947446E-05 0.46009809 -0.45820219E-02
52 5 -5.0533361 0.10891817E-03 -4.3490697 0.61482301E-01
53 4 32.395785 0.89717001E-03 21.079809 -0.41406279
54 3 -109.93440 0.19673976E-02 -54.911173 1.4965315
55 2 195.85064 0.11127485E-02 77.221372 -2.8803827
56 1 -170.69145 0.11939355E-03 -55.065279 2.7372963
57 0 57.057407 0.68346468E-06 15.590432  
58 9 -0.20590843E-15 0.37601014E-16 -0.14495918E-09 0.53749011E-17
59 8 0.21205398E-07 0.13808064E-12 0.37072834E-03 -0.24111267E-09
60 7 -0.12030653E-01 0.72214098E-08 -0.22782120E-01 0.13679291E-03
61 6 0.39961963 0.25236359E-05 0.46720788 -0.46802108E-02
62 5 -5.1346368 0.94596970E-04 -4.4037454 0.62490383E-01
63 4 32.755467 0.77656360E-03 21.293679 -0.41883826
64 3 -110.69986 0.16977958E-02 -55.334066 1.5075900
65 2 196.60952 0.95769584E-03 77.608945 -2.8924333
66 1 -170.97185 0.10250317E-03 -55.177451 2.7422106
67 0 57.057407 0.58520576E-06 15.571474  
68 9 -0.13316196E-15 0.35962645E-16 -0.14184186E-09 0.33595795E-17
69 8 0.20766565E-07 0.14634888E-12 0.36605364E-03 -0.23612300E-09
70 7 -0.11890945E-01 0.76921302E-08 -0.22580893E-01 0.13520437E-03
71 6 0.39582317 0.26934781E-05 0.46396918 -0.46354598E-02
72 5 -5.0975841 0.10113583E-03 -4.3788466 0.62030949E-01
73 4 32.591550 0.83151862E-03 21.196301 -0.41666193
74 3 -110.35104 0.18204263E-02 -55.141525 1.5025506
75 2 196.26372 0.10281160E-02 77.432455 -2.8869422
76 1 -170.84409 0.11016374E-03 -55.126315 2.7399715
77 0 57.057407 0.62970739E-06 15.580070  
78 7 -0.15963512E-14 -0.15187529E-16 -0.22427203E-13 0.56155309E-15
79 6 0.17983713E-10 0.23594901E-11 0.52322926E-09 -0.18637893E-10
80 5 -0.60139213E-07 0.11510628E-07 -0.21924491E-05 0.17161312E-06
81 4 0.62746279E-04 0.43399923E-05 0.17681060E-02 -0.28244642E-03
82 3 -0.90508353E-02 0.15320797E-03 -0.21560640 0.43341486E-01
83 2 0.12836503 0.66328859E-03 2.9007871 -0.61911613
84 1 -0.32478029 0.41934727E-03 -7.1379041 1.5697129
85 0 0.20664896 0.54311639E-05 4.4522013  
86 7 -0.22427203E-13 -0.15187529E-16 -0.15963512E-14 0.56155309E-15
87 6 0.52322926E-09 0.23594901E-11 0.17983713E-10 -0.18637893E-10
88 5 -0.21924491E-05 0.11510628E-07 -0.60139213E-07 0.17161312E-06
89 4 0.17681060E-02 0.43399923E-05 0.62746279E-04 -0.28244642E-03
90 3 -0.21560640 0.15320797E-03 -0.90508353E-02 0.43341486E-01
91 2 2.9007871 0.66328859E-03 0.12836503 -0.61911613
92 1 -7.1379041 0.41934727E-03 -0.32478029 1.5697129
93 0 4.4522013 0.54311639E-05 0.20664896  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
103 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
104 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
105 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
106 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
107 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
108 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
109 0 0.43108349 0.21254961E-04 60.838472  
110 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
111 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
112 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
113 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
114 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
115 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
116 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
117 0 0.43108349 0.21254961E-04 60.838472  
118 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
119 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
120 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
121 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
122 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
123 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
124 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
125 0 0.43108349 0.21254961E-04 60.838472  
126 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
127 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
128 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
129 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
130 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
131 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
132 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
133 0 0.43108349 0.21254961E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.3856_SHGC_0.4 37 1 VerySmooth 2.191 2.191 1.000 0.401    
2 RESWINDOW_U_0.3856_SHGC_0.4 38 1 VerySmooth 2.191 2.191 1.000 0.401    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   3.40174E-002 0.31435 0.47878 0.47878 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 0.11969 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   3.40174E-002 0.31435 0.47878 0.47878 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 0.11969 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 1.500
2 RACK2 1 0 Zone Air-Cooled 3.000


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 0.576 0.5074
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 0.263 2.9576E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 3.921E-002 5.846E-004 2.885E-004 0.531 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 1.513E-002 1.949E-004 5.306E-004 0.177 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 3.577E-002 2.178E-004 5.696E-004 0.198 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 2.064E-002 2.178E-004 4.726E-004 0.198 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 4.884E-002 6.258E-004 5.569E-004 0.569 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 8.667E-002 4.589E-004 2.527E-004 0.417 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.248 1.893E-004 3.620E-004 0.172 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 6.349E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 6.350E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 2.751E-002 7.066E-005 5.696E-004 8.345E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.164E-002 4.746E-004 2.589E-004 0.561 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 4.974E-002 4.815E-004 2.609E-004 0.569 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 4.868E-002 1.181E-004 9.784E-005 0.140 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1534
2 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 8.7758E-002
3 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1752
4 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 0.1021
5 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1020
6 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 4.1403E-002
7 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 4.2077E-002
8 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 1.3979E-002
9 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1746
10 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 0.1047
11 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.2002
12 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 0.1214
13 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1128
14 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 5.1573E-002
15 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 4.7248E-002
16 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 1.9114E-002
17 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 3.8477E-002
18 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 2.2231E-002
19 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.9646E-002
20 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.6836E-002
21 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.8209E-002
22 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.1255E-002
23 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 4.1419E-002
24 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.4687E-002
25 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 3.8477E-002
26 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 2.2231E-002
27 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.9646E-002
28 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.6836E-002
29 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.8209E-002
30 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.1255E-002
31 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 4.1419E-002
32 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.4687E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 34477.44919 34477.44919 2.53194 2.53194 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 23.30600 8.40224E-003 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 1445.39636 1445.39636 6.26193E-002 0.85446 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -4.30000 2.65759E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 6413.43447 6413.43447 0.47102 0.47102 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 26.17250 8.40672E-003 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 2352.87916 2352.87916 0.10193 0.10193 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3236.98049 3236.98049 0.23774 0.23774 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 26.21800 8.40679E-003 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 792.90836 792.90836 3.43508E-002 9.17347E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -4.30000 2.65759E-003 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 2880.00204 2880.00204 0.21148 0.21148 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 26.21800 8.40679E-003 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1483.69332 1483.69332 6.42772E-002 6.42772E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -4.30000 2.65759E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1374.78313 1374.78313 0.10095 0.10095 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 26.40000 8.40708E-003 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 908.06900 908.06900 3.93398E-002 5.77652E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -4.30000 2.65759E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 44674.12916 44674.12916 3.28072 3.28072 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 26.40000 8.40708E-003 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 1926.78408 1926.78408 8.34712E-002 8.34712E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 24859.39200 24859.39200 1.82720 1.82720 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 26.17250 8.40672E-003 188.86188 142.30000 0.67639 0.00000
14 CAFE_FLR_1 Heating 5915.88575 5915.88575 0.25629 0.67639 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 188.86188 142.30000 0.67639 0.00000
15 LOBBY_FLR_1 Cooling 68314.64494 68314.64494 5.01876 5.01876 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 26.24833 8.40684E-003 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 14098.50016 14098.50016 0.61078 1.89399 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -4.30000 2.65759E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 11862.93082 11862.93082 1.17392 1.17392 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 25.36867 8.40546E-003 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 5214.41596 5214.41596 0.22722 0.22722 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 10527.01545 10527.01545 1.04172 1.04172 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 25.12600 8.40508E-003 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 5220.17125 5220.17125 0.22747 0.22747 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 80991.20076 80991.20076 8.01427 8.01427 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 26.24833 8.40684E-003 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 29871.27642 29871.27642 1.30170 1.30170 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 48068.64656 48068.64656 4.75688 4.75688 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 26.40000 8.40708E-003 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 29995.42025 29995.42025 1.30711 1.30711 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 10703.56302 10703.56302 1.05919 1.05919 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 22.94200 8.40167E-003 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 5202.21801 5202.21801 0.22669 0.22669 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 9573.35790 9573.35790 0.94735 0.94735 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 21.65283 8.39969E-003 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 5207.97676 5207.97676 0.22694 0.22694 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 20872.43579 20872.43579 1.53278 1.53278 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 26.40000 8.40708E-003 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 8243.21779 8243.21779 0.35712 0.47476 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 3122.92819 3122.92819 0.30903 0.30903 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 25.36867 8.40546E-003 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 1615.53765 1615.53765 7.03984E-002 7.03984E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2747.23547 2747.23547 0.27186 0.27186 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 25.12600 8.40508E-003 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 1616.99625 1616.99625 7.04620E-002 7.04620E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 17197.56947 17197.56947 1.70185 1.70185 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 26.24833 8.40684E-003 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 7750.54326 7750.54326 0.33774 0.33774 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 28808.89515 28808.89515 2.11822 2.11822 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 26.40000 8.40708E-003 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 5370.48140 5370.48140 0.23266 1.18780 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 -4.30000 2.65759E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 30181.04500 30181.04500 2.21908 2.21908 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 26.40000 8.40708E-003 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 5483.45142 5483.45142 0.23756 1.18780 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:40:00 -4.30000 2.65759E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 30896.31832 30896.31832 2.27477 2.27477 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 25.58100 8.40579E-003 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 1523.97409 1523.97409 6.60118E-002 0.36735 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 23:30:00 -4.30000 2.65759E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 11046.88631 11046.88631 0.81123 0.81123 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 26.40000 8.40708E-003 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 5659.12603 5659.12603 0.24517 0.24517 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:50:00 -4.30000 2.65759E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 335137.00 22.51350 22.51350 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 183194.52 7.28687 7.28687 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:50:00
3 FLR_3_DOAS Cooling Sensible 33397.10 17.92299 2.05125 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 FLR_3_DOAS Heating Sensible 51569.06 3.99573 2.05125 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.53194
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.59554
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51500
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.30395
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.39757E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.22318E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.30395
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8256.54072
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.22318E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 174.09155
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.47102
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10850
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51500
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24258
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51500
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.51137E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.16586E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.24258
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3618.76870
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.16586E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 83.58860
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.23774
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24894
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51500
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12244
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.66384
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.53048E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.25261E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.12244
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1431.81013
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.25261E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 31.91949
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.21148
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.59180
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51500
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.10891
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.43796E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.79507E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.10891
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2051.87672
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.79507E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 49.59329
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.10095
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.71526
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51500
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.19897E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.32671E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.03172E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.19897E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1179.31387
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.03172E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 29.88030
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.28072
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.19275E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51500
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.68957
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51500
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.10196E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.39592E-005
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.68957
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10740.10829
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.39592E-005
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 226.51471
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.82720
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.87612E-002
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51500
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.94101
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51500
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.83740E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.47206E-005
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.94101
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10827.14632
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.47206E-005
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 240.88217
99 Fan:ZoneExhaust LOBBY_FLR_1 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.01876
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19862
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51500
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.58466
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52966
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.91821E-003
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.41341E-004
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.58466
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
110 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 27586.81294
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.41341E-004
113 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 608.31648
114 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
115 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.17392
116 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.17392
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.56172E-005
118 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.60913E-004
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68925
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56070E-003
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.60913E-004
125 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.17392
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5214.32837
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.56172E-005
128 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 149.01301
129 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
130 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.04172
131 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.04172
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.56676E-005
133 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.09860E-004
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68924
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56826E-003
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.09860E-004
140 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.04172
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5220.08356
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.56676E-005
143 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 149.17743
144 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
145 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 8.01427
146 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 8.01427
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.61325E-004
148 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.09417E-003
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68967
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.49866E-003
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.49866E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.09417E-003
155 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 8.01427
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 29871.03219
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.61325E-004
158 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 853.62761
159 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
160 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 4.75688
161 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 4.75688
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.62411E-004
163 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.98550E-003
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68871
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.78995E-003
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.98550E-003
170 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 4.75688
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 29995.17506
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.62411E-004
173 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 857.17438
174 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
175 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.05919
176 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.05919
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.55105E-005
178 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.16615E-004
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68924
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56722E-003
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.16615E-004
185 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.05919
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5202.13061
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.55105E-005
188 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 148.66452
189 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
190 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.94735
191 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.94735
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.55609E-005
193 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.73403E-004
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68923
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57483E-003
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.73403E-004
200 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.94735
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5207.88927
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.55609E-005
203 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 148.82904
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.53278
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.77435
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51500
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.78938
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.92028E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.08163E-004
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.78938
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
214 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12363.68446
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.08163E-004
217 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 288.00123
218 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
219 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.30903
220 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.30903
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.41332E-005
222 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.21237E-004
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68926
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.55773E-003
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.21237E-004
229 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.30903
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1615.51140
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.41332E-005
232 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 46.16491
233 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
234 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.27186
235 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.27186
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.41460E-005
237 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.06880E-004
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68925
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56549E-003
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.06880E-004
244 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.27186
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1616.96997
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.41460E-005
247 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 46.20658
248 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
249 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.70185
250 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.70185
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 6.78042E-005
252 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 6.74691E-004
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68902
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.59608E-003
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 6.74691E-004
259 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.70185
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 7750.44200
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.78042E-005
262 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 221.47510
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.11822
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11931
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51500
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.09088
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51500
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.19338E-003
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.68058E-005
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.09088
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
273 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11065.49692
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.68058E-005
276 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 242.66544
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.21908
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11389
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51500
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.14282
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51500
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.34543E-003
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.00166E-004
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.14282
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
287 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11449.63830
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.00166E-004
290 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 250.75888
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.27477
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.22411E-002
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51500
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.17151
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51500
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.10100E-002
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.66159E-005
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.17151
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
301 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7614.60167
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.66159E-005
304 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 160.82763
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.81123
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.38711
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51500
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.41778
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.84204E-004
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.85914E-005
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.41778
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
315 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7840.42414
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.85914E-005
318 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 189.33588
319 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 11.65749
320 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 11.65749
321 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 22.63589
322 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 11.65749
323 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 22.51350
324 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 22.51350
325 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
326 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.51780
327 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
328 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
329 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
333 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
334 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
335 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 22.51350
336 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
337 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 22.51350
338 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 11.66146
339 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 11.66146
340 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.23838
341 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.95895
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.98749E-003
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 424222.08502
346 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.51522E-002
347 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 22.51350
348 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 169799.33444
349 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.48548E-003
350 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 2897.25556
351 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 22.51350
352 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.51522E-002
353 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 3.14271E-005
354 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.48548E-003
355 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
356 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
357 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
358 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 26.40000
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.91985
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.40708E-003
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.40708E-003
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 36112.10278
364 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.28984E-003
365 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
366 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 15471.26131
367 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.35349E-004
368 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 263.98335
369 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
370 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.28984E-003
371 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 3.69186E-004
372 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.35349E-004
373 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 2.40853E-002
374 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 4963.09624
375 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 3.43805E-003
376 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.41257
377 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 3.43805E-003
378 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 1035.39007
379 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
380 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 392990.38133
381 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 392990.38000
382 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 3.43805E-003
383 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 2.40853E-002
384 PlantLoop COOLSYS1 Plant Loop Volume [m3] 2.89024
385 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 2.40853E-002
386 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 3436.11892
387 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 2.40853E-002
388 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 674325.42316
389 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 674948.88000
390 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 76.94417
391 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
392 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
393 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
394 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
395 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 8298.78
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 3635.48
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1438.66
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 2060.81
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1184.21
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 10795.04
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 10879.07
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 27720.33
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 5616.43
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 5622.62
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 32174.29
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 32307.98
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 5603.29
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 5609.49
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 12420.33
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 1740.03
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 1741.61
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 8347.81
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 11120.15
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 11506.25
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 7653.49
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 7874.60
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 129185.60
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 11770.74


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 19365.81 15655.08 3710.73 0.81 2207.40 22.39
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 17208.40 13903.66 3304.74 0.81 1961.09 19.89
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 130794.01 106190.63 24603.37 0.81 14943.07 151.56
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 81645.43 64994.04 16651.39 0.80 9255.64 93.88
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 17493.74 14135.23 3358.51 0.81 1993.66 20.22
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 15667.96 12653.22 3014.75 0.81 1785.22 18.11
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 5095.34 4119.87 975.47 0.81 580.84 5.89
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 4488.64 3627.34 861.30 0.81 511.57 5.19
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 28253.34 22783.30 5470.03 0.81 3217.42 32.63
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 530122.50 378206.22 151916.28 0.71 64938.97 658.65
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 45302.65 32936.56 12366.09 0.73 5220.86 52.95


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 3.93 13.40


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.419 0.394   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.419 0.394   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.419 0.394   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.419 0.394   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.198 1.198   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.107 0.950   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.107 0.950   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.107 0.950   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.107 0.950   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.097 0.942   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.097 0.942   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.097 0.942   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.097 0.942   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.097 0.942   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 2.0551379132E-002 2.8964065213E-002 Pass Pass 5.2400874343E-003 1.7653407302E-002 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 2.8829806734E-002 6.4658690637E-002 Pass Pass 5.7906656178E-002 8.7372628921E-002 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 2.9810465682E-002 3.5995120686E-002 Pass Pass 7.3066921342E-003 2.0255011016E-002 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 6.9324909869E-003 1.5056938119E-002 Pass Pass 2.8420590344E-002 5.6524546577E-002 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 7.5409017683E-004 3.7349670745E-003 Pass Pass 4.7671783222E-002 7.2088414107E-002 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 7.4304477531E-002 0.2178007391 Pass Pass 2.0586857566E-002 5.3166567144E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 5.9068202917E-002 9.1279623263E-002 Pass Pass 1.7820954914E-002 3.6901363216E-002 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 4.0366898230E-002 4.9938808521E-002 Pass Pass 7.8954365408E-003 1.8669536718E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 5.0078823689E-002 0.1830440626 Pass Pass 0.2941254208 1.2050246547 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 9.0319126954E-002 0.2847919494 Pass Pass 0.2279683563 0.9383230982 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 3.4056299937E-002 4.7536676068E-002 Pass Pass 1.6677822440E-002 3.4929307662E-002 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 3.0663536778E-002 0.1173990819 Pass Pass 2.6125108593 25.8137887365 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 5.6899337738E-002 0.1717142665 Pass Pass 0.1938123881 0.9677841122 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 8.0412831738E-002 0.2659634506 Pass Pass 0.2681048039 0.9115340188 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 5.1351037281E-003 1.3544855565E-002 Pass Pass 2.9539236252E-002 5.2937716861E-002 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 7.3844028724E-002 0.2574563229 Pass Pass 0.1924816323 0.8568944537 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 9.2883622283E-002 0.3355973437 Pass Pass 0.4398728892 1.9811896358 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 4.3069044552E-002 0.2099928870 Pass Pass 0.1212049433 0.2952573354 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 3.9223538785E-002 8.9270269656E-002 Pass Pass 1.2944067379E-002 3.8107560274E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 2.6246667811E-002 7.0433120575E-002 Pass Pass 1.4099129427E-002 4.0701890217E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 4.6980611491E-002 0.2024923806 Pass Pass 2.1543916320E-002 4.2200579966E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 7.1497759984E-003 2.3521220955E-002 Pass Pass 2.9749752373E-002 3.8853873197E-002 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3477.67 153.40 1962.21 8247.97 1612.44 15453.70



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB -4.30 0.00 -4.30 Wetbulb [C] 1.20 110.00
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 26.40 9.10 17.00 Wetbulb [C] 2.10 90.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 42.00 35      
Mar 0.00 0      
Apr 0.00 0      
May 40.00 22      
Jun 4.00 8      
Jul 5.00 4      
Aug 7.00 8      
Sep 17.00 10      
Oct 50.00 49      
Nov 69.00 59      
Dec 95.00 53      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.399 0.419 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.399 0.419 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.399 0.419 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.732 0.823 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.23 0.182 0.186 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.732 0.823 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.732 0.823 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.732 0.823 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.23 0.182 0.186 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 0.732 0.823 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.23 0.182 0.186 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.893 1.031 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.893 1.031 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.893 1.031 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.893 1.031 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.893 1.031 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.893 1.031 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.893 1.031 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.893 1.031 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.893 1.031 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.893 1.031 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 0.950 1.107 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 0.950 1.107 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 0.950 1.107 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 0.950 1.107 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.942 1.097 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.942 1.097 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 0.942 1.097 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.942 1.097 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.942 1.097 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.999 1.174 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.23 0.182 0.186 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.23 0.182 0.186 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.186 0.196 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.186 0.196 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.186 0.196 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.186 0.196 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.186 0.196 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.186 0.196 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.186 0.196 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.186 0.196 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.186 0.196 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.186 0.196 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.185 0.196 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.185 0.196 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.185 0.196 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.188 0.196 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   23.26 0.00 0.00 23.26 23.26 2.191 0.401 0.402             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   65.50 0.00 0.00 65.50 65.50 2.191 0.401 0.402             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   85.08 0.00 0.00 85.08 85.08 2.191 0.401 0.402             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.191 0.401 0.402             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.191 0.401 0.402             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.191 0.401 0.402             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.191 0.401 0.402             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   3.68 0.00 0.00 3.68 279.56 2.191 0.401 0.402             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   3.68 0.00 0.00 3.68 279.65 2.191 0.401 0.402             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.191 0.401 0.402             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.191 0.401 0.402             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.191 0.401 0.402             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.191 0.401 0.402             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   5.82 0.00 0.00 5.82 23.30 2.191 0.401 0.402             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   2.15 0.00 0.00 2.15 8.59 2.191 0.401 0.402             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   2.15 0.00 0.00 2.15 8.58 2.191 0.401 0.402             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   5.82 0.00 0.00 5.82 23.30 2.191 0.401 0.402             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.191 0.401 0.402             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 8.58 2.191 0.401 0.402             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.191 0.401 0.402             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 8.58 2.191 0.401 0.402             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   6.74 0.00 0.00 6.74 60.70 2.191 0.401 0.402             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   32.19 0.00 0.00 32.19 32.19 2.191 0.401 0.402             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   32.19 0.00 0.00 32.19 32.19 2.191 0.401 0.402             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.191 0.401 0.402             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   17.17 0.00 0.00 17.17 17.17 2.191 0.401 0.402             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.191 0.401 0.402             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   5.82 0.00 0.00 5.82 5.82 2.191 0.401 0.402             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   5.21 0.00 0.00 5.21 5.21 2.191 0.401 0.402             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   17.17 0.00 0.00 17.17 17.17 2.191 0.401 0.402             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.191 0.401 0.402                      
North Total or Average             432.95 2.191 0.401 0.402                      
Non-North Total or Average             780.84 2.191 0.401 0.402                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.016 1.198 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 9.1389 1978.83 18084.33 LightsWired LTG_SCH_BASEMENT 51.16 168.00 51.10 0.0000 Y 173.46
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 13.3365 67.07 894.50 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 8.61
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 13.3365 77.67 1035.83 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 9.97
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 9.2031 164.24 1511.55 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 16.63
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 6.1031 94.76 578.33 LightsWired LTG_SCH_STORAGE 25.68 168.00 25.65 0.0000 Y 2.78
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.8125 78.04 453.60 LightsWired LTG_SCH_LAUNDRY 51.36 168.00 51.30 0.0000 Y 4.37
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 10.3656 188.86 1957.67 LightsWired LTG_SCH_DINING 58.69 168.00 48.80 0.0000 Y 17.93
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 8.7188 1308.19 11405.76 LightsWired LTG_SCH_LOBBY 58.69 168.00 56.92 0.0000 Y 121.87
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 4.5531 156.09 710.69 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 4.5531 156.07 710.61 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 4.5531 1863.81 8486.17 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 76.02
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 4.5531 1864.32 8488.49 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 76.04
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 4.5531 156.09 710.69 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 4.5531 156.07 710.61 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 6.3938 1557.62 9959.03 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 109.60
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 4.5531 39.02 177.67 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.59
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 4.5531 39.02 177.65 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.59
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 4.5531 220.77 1005.22 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 9.00
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 10.3656 331.66 3437.84 LightsWired LTG_SCH_DINING 58.69 168.00 53.69 0.0000 Y 34.65
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 10.3656 331.66 3437.84 LightsWired LTG_SCH_DINING 58.69 168.00 53.69 0.0000 Y 34.65
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 11.7219 103.30 1210.92 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 13.33
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 6.3938 412.12 2635.02 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 29.00
Interior Lighting Total       6.8557 11345.29 77780.02               507.20


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.07 11405.76 798.40
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.00 11405.76 0.00
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.39 1957.67 763.49
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.00 1957.67 0.00
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3437.84 687.57
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.00 3437.84 0.00
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3437.84 687.57
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.00 3437.84 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 15448.40 AstronomicalClock -   83.54 83.54 242.26
Exterior Lighting Total 15448.40           242.26



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 392990.38 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 674948.88 2.96 675067.52 2.96 3.93 13.40


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12904.59 19365.81 15655.08 3710.73 0.81 - 2207.40 22.39
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11475.20 17208.40 13903.66 3304.74 0.81 - 1961.09 19.89
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 86630.13 130794.01 106190.63 24603.37 0.81 - 14943.07 151.56
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 55589.81 81645.43 64994.04 16651.39 0.80 - 9255.64 93.88
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11664.33 17493.74 14135.23 3358.51 0.81 - 1993.66 20.22
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10454.49 15667.96 12653.22 3014.75 0.81 - 1785.22 18.11
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3394.37 5095.34 4119.87 975.47 0.81 - 580.84 5.89
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2992.41 4488.64 3627.34 861.30 0.81 - 511.57 5.19
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 18889.91 28253.34 22783.30 5470.03 0.81 - 3217.42 32.63
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 424222.09 530122.50 378206.22 151916.28 0.71 - 64938.97 658.65
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 36112.10 45302.65 32936.56 12366.09 0.73 - 5220.86 52.95
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 8256.54 8298.78 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 3618.77 3635.48 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1431.81 1438.66 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2051.88 2060.81 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1179.31 1184.21 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 10740.11 10795.04 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 10827.15 10879.07 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 27586.81 27720.33 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5214.33 5616.43 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5220.08 5622.62 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 29871.03 32174.29 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 29995.18 32307.98 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5202.13 5603.29 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5207.89 5609.49 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 12363.68 12420.33 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1615.51 1740.03 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1616.97 1741.61 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 7750.44 8347.81 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 11065.50 11120.15 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 11449.64 11506.25 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 7614.60 7653.49 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 7840.42 7874.60 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 169799.33 129185.60 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 15471.26 11770.74 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.17 826.01 703.64 1.00 1.16 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.04 732.99 703.64 1.00 1.19 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 8.01 5639.13 703.64 1.00 0.94 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 4.76 3347.11 703.64 1.00 0.97 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.06 745.28 703.64 1.00 1.18 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.95 666.59 703.64 1.00 1.21 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.31 217.45 703.64 1.00 1.69 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.27 191.29 703.64 1.00 1.78 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.70 1197.49 703.64 1.00 1.09 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 22.51 50444.63 2240.64 1.00 1.11 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.024085 4963.10 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.003438 1035.39 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.024085 3436.12 142664.32 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.80 0.58 0.51
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.80 0.26 0.03



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 34477.45 34477.45 17.42 2.532 2.532 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 24.00 24.00 0.00920 23.31 0.00840 0.854 0.00
RETAIL_1_FLR_1 6413.43 6413.43 95.62 0.471 0.471 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 24.00 24.00 0.00887 26.17 0.00841 0.079 0.00
RETAIL_2_FLR_1 3236.98 3236.98 41.68 0.238 0.238 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 24.00 24.00 0.00936 26.22 0.00841 0.092 0.00
MECH_FLR_1 2880.00 2880.00 17.53 0.211 0.211 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 24.00 24.00 0.00870 26.22 0.00841 0.000 0.00
STORAGE_FLR_1 1374.78 1374.78 14.51 0.101 0.101 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 24.00 24.00 0.00882 26.40 0.00841 0.058 0.00
LAUNDRY_FLR_1 44674.13 44674.13 572.46 3.281 3.281 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 24.00 24.00 0.00854 26.40 0.00841 0.000 0.00
CAFE_FLR_1 24859.39 24859.39 131.63 1.827 1.827 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 24.00 23.99 0.00978 26.17 0.00841 0.676 0.00
LOBBY_FLR_1 68314.64 68314.64 52.22 5.019 5.019 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 24.00 23.99 0.00988 26.25 0.00841 1.894 0.00
ROOM_1_FLR_3 11862.93 11862.93 304.01 1.174 1.174 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 21.11 21.11 0.00856 25.37 0.00841 0.062 0.00
ROOM_2_FLR_3 10527.02 10527.02 269.80 1.042 1.042 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 21.11 21.11 0.00857 25.13 0.00841 0.062 0.00
ROOM_3_MULT19_FLR_3 80991.20 80991.20 3302.55 8.014 8.014 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 21.11 21.11 0.00850 26.25 0.00841 0.837 0.00
ROOM_4_MULT19_FLR_3 48068.65 48068.65 1959.54 4.757 4.757 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 21.11 21.11 0.00879 26.40 0.00841 0.837 0.00
ROOM_5_FLR_3 10703.56 10703.56 274.30 1.059 1.059 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 21.11 21.11 0.00857 22.94 0.00840 0.062 0.00
ROOM_6_FLR_3 9573.36 9573.36 245.36 0.947 0.947 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 21.11 21.11 0.00857 21.65 0.00840 0.062 0.00
CORRIDOR_FLR_3 20872.44 20872.44 53.60 1.533 1.533 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 24.00 24.00 0.00940 26.40 0.00841 0.475 0.00
ROOM_1_FLR_6 3122.93 3122.93 80.03 0.309 0.309 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 21.11 21.11 0.00856 25.37 0.00841 0.015 0.00
ROOM_2_FLR_6 2747.24 2747.24 70.41 0.272 0.272 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 21.11 21.11 0.00857 25.13 0.00841 0.015 0.00
ROOM_3_MULT9_FLR_6 17197.57 17197.57 701.07 1.702 1.702 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 21.11 21.11 0.00860 26.25 0.00841 0.099 0.00
BANQUET_FLR_6 28808.90 28808.90 86.86 2.118 2.118 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 24.00 23.98 0.01045 26.40 0.00841 1.188 0.00
DINING_FLR_6 30181.04 30181.04 91.00 2.219 2.219 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 24.00 23.99 0.01036 26.40 0.00841 1.188 0.00
KITCHEN_FLR_6 30896.32 30896.32 299.08 2.275 2.275 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 24.00 23.97 0.01007 25.58 0.00841 0.367 0.00
CORRIDOR_FLR_6 11046.89 11046.89 26.80 0.811 0.811 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 24.00 24.00 0.00895 26.40 0.00841 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 1445.40 1445.40 0.73 0.063 0.854 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00796 -4.30 0.00266 0.854 0.00
RETAIL_1_FLR_1 2352.88 2352.88 35.08 0.102 0.102 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.00 21.00 0.00749 -4.30 0.00266 0.079 0.00
RETAIL_2_FLR_1 792.91 792.91 10.21 0.034 0.092 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00743 -4.30 0.00266 0.092 0.00
MECH_FLR_1 1483.69 1483.69 9.03 0.064 0.064 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00730 -4.30 0.00266 0.000 0.00
STORAGE_FLR_1 908.07 908.07 9.58 0.039 0.058 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00733 -4.30 0.00266 0.058 0.00
LAUNDRY_FLR_1 1926.78 1926.78 24.69 0.083 0.083 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.00 21.00 0.00727 -4.30 0.00266 0.000 0.00
CAFE_FLR_1 5915.89 5915.89 31.32 0.256 0.676 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.00 21.00 0.00755 -4.30 0.00266 0.676 0.00
LOBBY_FLR_1 14098.50 14098.50 10.78 0.611 1.894 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00747 -4.30 0.00266 1.894 0.00
ROOM_1_FLR_3 5214.42 5214.42 133.63 0.227 0.227 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00748 -4.30 0.00266 0.062 0.00
ROOM_2_FLR_3 5220.17 5220.17 133.79 0.227 0.227 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00748 -4.30 0.00266 0.062 0.00
ROOM_3_MULT19_FLR_3 29871.28 29871.28 1218.05 1.302 1.302 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00751 -4.30 0.00266 0.837 0.00
ROOM_4_MULT19_FLR_3 29995.42 29995.42 1222.78 1.307 1.307 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00751 -4.30 0.00266 0.837 0.00
ROOM_5_FLR_3 5202.22 5202.22 133.31 0.227 0.227 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00747 -4.30 0.00266 0.062 0.00
ROOM_6_FLR_3 5207.98 5207.98 133.48 0.227 0.227 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00748 -4.30 0.00266 0.062 0.00
CORRIDOR_FLR_3 8243.22 8243.22 21.17 0.357 0.475 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.00 21.00 0.00759 -4.30 0.00266 0.475 0.00
ROOM_1_FLR_6 1615.54 1615.54 41.40 0.070 0.070 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00757 -4.30 0.00266 0.015 0.00
ROOM_2_FLR_6 1617.00 1617.00 41.44 0.070 0.070 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00757 -4.30 0.00266 0.015 0.00
ROOM_3_MULT9_FLR_6 7750.54 7750.54 315.95 0.338 0.338 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.11 21.11 0.00758 -4.30 0.00266 0.099 0.00
BANQUET_FLR_6 5370.48 5370.48 16.19 0.233 1.188 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 21.00 21.00 0.00767 -4.30 0.00266 1.188 0.00
DINING_FLR_6 5483.45 5483.45 16.53 0.238 1.188 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:40:00 21.00 21.00 0.00768 -4.30 0.00266 1.188 0.00
KITCHEN_FLR_6 1523.97 1523.97 14.75 0.066 0.367 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 23:30:00 21.00 21.00 0.00585 -4.30 0.00266 0.367 0.00
CORRIDOR_FLR_6 5659.13 5659.13 13.73 0.245 0.245 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:50:00 21.00 21.00 0.00773 -4.30 0.00266 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 22.51 22.51 7.29 7.29 22.5135 11.6575 22.5135 0.5178 0.3000
FLR_3_DOAS 17.92 2.05 4.00 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 8256.541 8256.541 1.303950 0.00007223 174.092 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8256.54 8256.54 1.303950 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00795701 50.8964 1445.40 0.00 8302.76 8302.76
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 3618.769 3618.769 0.242577 0.00003166 83.589 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 3618.77 3618.77 0.242577 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00749488 47.9770 2352.88 0.00 3638.15 3638.15
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1431.810 1431.810 0.122437 0.00001253 31.919 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1431.81 1431.81 0.122437 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00742925 47.5610 792.91 0.00 1439.58 1439.58
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 2051.877 2051.877 0.108911 0.00001795 49.593 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2051.88 2051.88 0.108911 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00729881 46.7357 1483.69 0.00 2062.58 2062.58
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1179.314 1179.314 0.051990 0.00001032 29.880 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1179.31 1179.31 0.051990 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00733400 46.9584 908.07 0.00 1185.37 1185.37
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10740.108 10740.108 1.689569 0.00009396 226.515 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 10740.11 10740.11 1.689569 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00726769 46.5395 1926.78 0.00 10800.23 10800.23
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 10827.146 10827.146 0.941009 0.00009472 240.882 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 10827.15 10827.15 0.941009 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00755078 48.3302 5915.89 0.00 10885.93 10885.93
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 27586.813 27586.813 2.584662 0.00024134 608.316 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 27586.81 27586.81 2.584662 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00747026 47.8204 14098.50 0.00 27737.13 27737.13
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 12904.586 -999.000 1.173915 0.00046091 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 unknown 8/21 16:40:00 12904.59 12717.12 1.173915 21.69 15.50 0.00856070 12.80 12.00 0.00850000 25.37 0.00840546 16.68 0.0000 21.11 0.00856070 54.3347 11862.93 0.00 13039.61 12627.38
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 5214.328 5214.328 0.227222 0.00004562 149.013 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 5214.33 5214.33 0.227222 21.11 14.31 0.00747598 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00747598 47.5325 5214.42 0.00 5621.18 5621.18
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 11475.201 -999.000 1.041718 0.00040986 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown 8/21 17:00:00 11475.20 11288.08 1.041718 21.69 15.51 0.00856826 12.80 12.00 0.00850000 25.13 0.00840508 16.59 0.0000 21.11 0.00856826 54.3820 10527.02 0.00 11595.14 11209.16
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 5220.084 5220.084 0.227473 0.00004567 149.177 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 5220.08 5220.08 0.227473 21.11 14.31 0.00747654 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00747654 47.5360 5220.17 0.00 5627.38 5627.38
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 86630.133 -999.000 8.014268 0.00309417 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 unknown 8/21 13:40:00 86630.13 86630.13 8.014268 21.69 15.45 0.00849866 12.80 12.00 0.00849866 26.25 0.00840684 16.99 0.0000 21.11 0.00849866 53.9451 80991.20 0.00 87559.57 86004.80
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 29871.032 29871.032 1.301698 0.00026132 853.628 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 29871.03 29871.03 1.301698 21.11 14.34 0.00751148 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00751148 47.7546 29871.28 0.00 32201.90 32201.90
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 55589.812 -999.000 4.756881 0.00198550 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 unknown 8/21 15:00:00 55589.81 51932.64 4.756881 21.69 15.70 0.00878995 12.80 12.00 0.00850000 26.40 0.00840708 17.04 0.0000 21.11 0.00878995 55.7705 48068.65 0.00 56153.14 51664.31
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 29995.175 29995.175 1.307108 0.00026241 857.174 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 29995.18 29995.18 1.307108 21.11 14.34 0.00751320 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00751320 47.7654 29995.42 0.00 32335.73 32335.73
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 11664.328 -999.000 1.059188 0.00041661 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 unknown 8/21 10:00:00 11664.33 11476.96 1.059188 21.69 15.51 0.00856722 12.80 12.00 0.00850000 22.94 0.00840167 15.82 0.0000 21.11 0.00856722 54.3756 10703.56 0.00 11786.26 11396.61
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 5202.131 5202.131 0.226691 0.00004551 148.665 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 5202.13 5202.13 0.226691 21.11 14.31 0.00747487 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00747487 47.5255 5202.22 0.00 5608.03 5608.03
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 10454.486 -999.000 0.947348 0.00037340 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 unknown 8/21 09:10:00 10454.49 10267.88 0.947348 21.69 15.52 0.00857483 12.80 12.00 0.00850000 21.65 0.00839969 15.35 0.0000 21.11 0.00857483 54.4232 9573.36 0.00 10563.65 10196.68
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 5207.889 5207.889 0.226942 0.00004556 148.829 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 5207.89 5207.89 0.226942 21.11 14.31 0.00747543 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00747543 47.5290 5207.98 0.00 5614.24 5614.24
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 12363.684 12363.684 0.789383 0.00010816 288.001 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 12363.68 12363.68 0.789383 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00758747 48.5613 8243.22 0.00 12429.73 12429.73
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 3394.369 -999.000 0.309034 0.00012124 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 unknown 8/21 16:40:00 3394.37 3347.44 0.309034 21.69 15.50 0.00855773 12.80 12.00 0.00850000 25.37 0.00840546 16.68 0.0000 21.11 0.00855773 54.3161 3122.93 0.00 3429.90 3323.73
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 1615.511 1615.511 0.070398 0.00001413 46.165 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 1615.51 1615.51 0.070398 21.11 14.39 0.00756892 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00756892 48.1163 1615.54 0.00 1741.56 1741.56
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2992.405 -999.000 0.271857 0.00010688 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown 8/21 17:00:00 2992.41 2945.56 0.271857 21.69 15.51 0.00856549 12.80 12.00 0.00850000 25.13 0.00840508 16.59 0.0000 21.11 0.00856549 54.3647 2747.24 0.00 3023.69 2924.89
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 1616.970 1616.970 0.070462 0.00001415 46.207 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 1616.97 1616.97 0.070462 21.11 14.39 0.00756931 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00756931 48.1187 1617.00 0.00 1743.13 1743.13
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 18889.911 -999.000 1.701853 0.00067469 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 unknown 8/21 13:40:00 18889.91 18459.17 1.701853 21.69 15.53 0.00859608 12.80 12.00 0.00850000 26.25 0.00840684 16.99 0.0000 21.11 0.00859608 54.5569 17197.57 0.00 19086.56 18334.52
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 7750.442 7750.442 0.337739 0.00006780 221.475 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 7750.44 7750.44 0.337739 21.11 14.41 0.00758489 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00758489 48.2163 7750.54 0.00 8355.19 8355.19
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 11065.497 11065.497 1.090883 0.00009681 242.665 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 11065.50 11065.50 1.090883 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00767464 49.1128 5370.48 0.00 11126.72 11126.72
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 11449.638 11449.638 1.142824 0.00010017 250.759 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:40:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:40:00 11449.64 11449.64 1.142824 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00768094 49.1527 5483.45 0.00 11513.00 11513.00
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 7614.602 7614.602 1.171506 0.00006662 160.828 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 23:30:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 23:30:00 7614.60 7614.60 1.171506 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00584758 37.5377 1523.97 0.00 7657.21 7657.21
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 7840.424 7840.424 0.417783 0.00006859 189.336 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:50:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:50:00 7840.42 7840.42 0.417783 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00772665 49.4414 5659.13 0.00 7881.32 7881.32
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 424222.085 -999.000 22.513504 0.01515223 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 424222.09 389847.36 22.513504 25.24 17.12 0.00898749 10.96 10.96 0.00850000 26.40 0.00840708 17.04 51.7976 23.99 0.00957607 50.9364 306277.48 0.00 427924.72 373177.13
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 169799.334 169799.334 6.754051 0.00148548 2897.256 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:50:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:50:00 169799.33 169799.33 6.754051 -4.30 -4.30 0.00265759 16.70 13.09 0.00800000 -4.30 0.00265759 -4.30 172.6587 21.02 0.00755070 48.2658 54676.09 0.00 156250.72 156250.72
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 36112.103 -999.000 2.051317 0.00128984 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 36112.10 36112.10 2.051317 26.40 17.04 0.00840708 11.92 11.55 0.00840708 26.40 0.00840708 17.04 99.9965 21.11 0.00860802 54.6306 181120.89 0.00 36425.73 35509.87
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 15471.261 15471.261 0.615395 0.00013535 263.983 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 15471.26 15471.26 0.615395 -4.30 -4.30 0.00265759 16.70 13.09 0.00800000 -4.30 0.00265759 -4.30 333.3216 21.11 0.00751281 47.7629 91694.56 0.00 14236.78 14236.78



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 8256.541 8256.541 1.303950 0.00007223 174.092 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 2.0595 2.100952 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 8256.54 8256.54 1.0000 1.55349007 1.303950 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.07222445 60.00 32.22 27.78 0.000 8256.54 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00795701 21.00 0.00795701 50.8964 1445.40 0.00 8302.76 8302.76 1.55349007 16.60 13.15 0.00800000 36934.7 21.84 15.17 0.00800000 42279.3
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 3618.769 3618.769 0.242577 0.00003166 83.589 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 0.9027 0.920829 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 3618.77 3618.77 1.0000 0.28899999 0.242577 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.03165534 60.00 32.22 27.78 0.000 3618.77 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00749488 21.00 0.00749488 47.9770 2352.88 0.00 3638.15 3638.15 0.28899999 16.60 13.15 0.00800000 36934.7 28.95 17.68 0.00800000 49523.5
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1431.810 1431.810 0.122437 0.00001253 31.919 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 0.3571 0.364337 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1431.81 1431.81 1.0000 0.14586801 0.122437 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.01252482 60.00 32.22 27.78 0.000 1431.81 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00742925 21.00 0.00742925 47.5610 792.91 0.00 1439.58 1439.58 0.14586801 16.60 13.15 0.00800000 36934.7 26.28 16.76 0.00800000 46803.8
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 2051.877 2051.877 0.108911 0.00001795 49.593 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 0.5118 0.522119 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2051.88 2051.88 1.0000 0.12975378 0.108911 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.01794888 60.00 32.22 27.78 0.000 2051.88 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00729881 21.00 0.00729881 46.7357 1483.69 0.00 2062.58 2062.58 0.12975378 16.60 13.15 0.00800000 36934.7 32.19 18.76 0.00800000 52830.8
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1179.314 1179.314 0.051990 0.00001032 29.880 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 0.2942 0.300087 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1179.31 1179.31 1.0000 0.06193913 0.051990 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.01031610 60.00 32.22 27.78 0.000 1179.31 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00733400 21.00 0.00733400 46.9584 908.07 0.00 1185.37 1185.37 0.06193913 16.60 13.15 0.00800000 36934.7 35.37 19.77 0.00800000 56072.4
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 10740.108 10740.108 1.689569 0.00009396 226.515 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 2.6790 2.732919 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 10740.11 10740.11 1.0000 2.01290542 1.689569 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.09394957 60.00 32.22 27.78 0.000 10740.11 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00726769 21.00 0.00726769 46.5395 1926.78 0.00 10800.23 10800.23 2.01290542 16.60 13.15 0.00800000 36934.7 21.86 15.17 0.00800000 42300.2
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 10827.146 10827.146 0.941009 0.00009472 240.882 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 2.7007 2.755066 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 10827.15 10827.15 1.0000 1.12109228 0.941009 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.09471094 60.00 32.22 27.78 0.000 10827.15 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00755078 21.00 0.00755078 48.3302 5915.89 0.00 10885.93 10885.93 1.12109228 16.60 13.15 0.00800000 36934.7 26.12 16.71 0.00800000 46644.8
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 27586.813 27586.813 2.584662 0.00024134 608.316 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 6.8812 7.019717 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 27586.81 27586.81 1.0000 3.07929401 2.584662 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.24131685 60.00 32.22 27.78 0.000 27586.81 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00747026 21.00 0.00747026 47.8204 14098.50 0.00 27737.13 27737.13 3.07929401 16.60 13.15 0.00800000 36934.7 25.43 16.47 0.00800000 45942.4
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 12904.586 -999.000 1.173915 0.00046091 -999.000 -999.0000 1.00000 1.00000 1020.7539 1004.8586 1.1914 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.173915 1.39856955   4197.9300 999.8980 24.08288474 13.37 6.70 6.67 674325.42 1.9137 1.913667 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 unknown unknown unknown 8/21 16:40:00 Sensible 12904.59 12717.12 1.0000 1.39856955 1.173915 21.69 15.50 0.00856070 43549.2 12.80 12.00 0.00850000 34322.2 0.46086630 6.70 13.37 6.67 0.000 12904.59 25.37 0.00840546 16.68 0.00000000 0.0000 21.11 0.00856070 21.11 0.00856070 54.3347 11862.93 0.00 13039.61 12627.38 1.39856955 21.69 15.61 0.00856070 43549.2 12.84 12.06 0.00844396 34225.7
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 5214.328 5214.328 0.227222 0.00004562 149.013 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.173915 1.39856955   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 1.3007 1.326834 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 5214.33 5214.33 1.0000 0.27070648 0.227222 21.11 14.31 0.00747598 40202.9 40.00 21.06 0.00800000 60796.0 0.04561257 60.00 32.22 27.78 0.000 5214.33 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00747598 21.11 0.00747598 47.5325 5214.42 0.00 5621.18 5621.18 0.27070648 16.60 12.64 0.00747598 35608.0 36.98 19.88 0.00747598 56372.9
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 11475.201 -999.000 1.041718 0.00040986 -999.000 -999.0000 1.00000 1.00000 1020.7680 1004.8586 1.1914 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.041718 1.24107411   4197.9300 999.8980 24.08288474 13.37 6.70 6.67 674325.42 1.7017 1.701699 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown unknown unknown 8/21 17:00:00 Sensible 11475.20 11288.08 1.0000 1.24107411 1.041718 21.69 15.51 0.00856826 43568.4 12.80 12.00 0.00850000 34322.2 0.40981813 6.70 13.37 6.67 0.000 11475.20 25.13 0.00840508 16.59 0.00000000 0.0000 21.11 0.00856826 21.11 0.00856826 54.3820 10527.02 0.00 11595.14 11209.16 1.24107411 21.69 15.62 0.00856826 43568.4 12.84 12.06 0.00844508 34225.6
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 5220.084 5220.084 0.227473 0.00004567 149.177 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.041718 1.24107411   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 1.3021 1.328298 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 5220.08 5220.08 1.0000 0.27100527 0.227473 21.11 14.31 0.00747654 40204.4 40.00 21.06 0.00800000 60796.0 0.04566291 60.00 32.22 27.78 0.000 5220.08 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00747654 21.11 0.00747654 47.5360 5220.17 0.00 5627.38 5627.38 0.27100527 16.60 12.64 0.00747654 35609.4 36.98 19.88 0.00747654 56374.3
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 86630.133 -999.000 8.014268 0.00309417 -999.000 -999.0000 1.00000 1.00000 1020.6386 1004.8586 1.1914 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 8.014268 9.54797491   4197.9300 999.8980 24.08288474 13.37 6.70 6.67 674325.42 12.8469 12.846693 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 unknown unknown unknown 8/21 13:40:00 Sensible 86630.13 86630.13 1.0000 9.54797491 8.014268 21.69 15.45 0.00849866 43392.0 12.80 12.00 0.00849866 34318.8 3.09385421 6.70 13.37 6.67 0.000 86630.13 26.25 0.00840684 16.99 0.00000000 0.0000 21.11 0.00849866 21.11 0.00849866 53.9451 80991.20 0.00 87559.57 86004.80 9.54797491 21.69 15.56 0.00849866 43392.0 12.86 12.06 0.00843417 34221.5
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 29871.032 29871.032 1.301698 0.00026132 853.628 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 8.014268 9.54797491   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 7.4510 7.600958 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 29871.03 29871.03 1.0000 1.55080706 1.301698 21.11 14.34 0.00751148 40293.5 40.00 21.06 0.00800000 60796.0 0.26129816 60.00 32.22 27.78 0.000 29871.03 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00751148 21.11 0.00751148 47.7546 29871.28 0.00 32201.90 32201.90 1.55080706 16.60 12.67 0.00751148 35697.9 36.98 19.90 0.00751148 56462.5
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 55589.812 -999.000 4.756881 0.00198550 -999.000 -999.0000 1.00000 1.00000 1021.1801 1004.8586 1.1914 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 4.756881 5.66721444   4197.9300 999.8980 24.08288474 13.37 6.70 6.67 674325.42 8.2438 8.243612 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 unknown unknown unknown 8/21 15:00:00 Sensible 55589.81 51932.64 1.0000 5.66721444 4.756881 21.69 15.70 0.00878995 44131.2 12.80 12.00 0.00850000 34322.2 1.98529964 6.70 13.37 6.67 0.000 55589.81 26.40 0.00840708 17.04 0.00000000 0.0000 21.11 0.00878995 21.11 0.00878995 55.7705 48068.65 0.00 56153.14 51664.31 5.66721444 21.69 15.81 0.00878995 44131.2 12.76 12.06 0.00847622 34222.8
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 29995.175 29995.175 1.307108 0.00026241 857.174 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 4.756881 5.66721444   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 7.4820 7.632547 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 29995.18 29995.18 1.0000 1.55725215 1.307108 21.11 14.34 0.00751320 40297.8 40.00 21.06 0.00800000 60796.0 0.26238411 60.00 32.22 27.78 0.000 29995.18 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00751320 21.11 0.00751320 47.7654 29995.42 0.00 32335.73 32335.73 1.55725215 16.60 12.68 0.00751320 35702.3 36.98 19.91 0.00751320 56466.9
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 11664.328 -999.000 1.059188 0.00041661 -999.000 -999.0000 1.00000 1.00000 1020.7660 1004.8586 1.1914 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.059188 1.26188720   4197.9300 999.8980 24.08288474 13.37 6.70 6.67 674325.42 1.7298 1.729745 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 unknown unknown unknown 8/21 10:00:00 Sensible 11664.33 11476.96 1.0000 1.26188720 1.059188 21.69 15.51 0.00856722 43565.8 12.80 12.00 0.00850000 34322.2 0.41657250 6.70 13.37 6.67 0.000 11664.33 22.94 0.00840167 15.82 0.00000000 0.0000 21.11 0.00856722 21.11 0.00856722 54.3756 10703.56 0.00 11786.26 11396.61 1.26188720 21.69 15.62 0.00856722 43565.8 12.84 12.06 0.00844492 34225.6
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 5202.131 5202.131 0.226691 0.00004551 148.665 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.059188 1.26188720   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 1.2976 1.323730 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 5202.13 5202.13 1.0000 0.27007322 0.226691 21.11 14.31 0.00747487 40200.1 40.00 21.06 0.00800000 60796.0 0.04550587 60.00 32.22 27.78 0.000 5202.13 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00747487 21.11 0.00747487 47.5255 5202.22 0.00 5608.03 5608.03 0.27007322 16.60 12.64 0.00747487 35605.2 36.98 19.88 0.00747487 56370.1
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 10454.486 -999.000 0.947348 0.00037340 -999.000 -999.0000 1.00000 1.00000 1020.7802 1004.8586 1.1914 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.947348 1.12864353   4197.9300 999.8980 24.08288474 13.37 6.70 6.67 674325.42 1.5504 1.550333 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 unknown unknown unknown 8/21 09:10:00 Sensible 10454.49 10267.88 1.0000 1.12864353 0.947348 21.69 15.52 0.00857483 43585.1 12.80 12.00 0.00850000 34322.2 0.37336496 6.70 13.37 6.67 0.000 10454.49 21.65 0.00839969 15.35 0.00000000 0.0000 21.11 0.00857483 21.11 0.00857483 54.4232 9573.36 0.00 10563.65 10196.68 1.12864353 21.69 15.62 0.00857483 43585.1 12.84 12.06 0.00844605 34225.5
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 5207.889 5207.889 0.226942 0.00004556 148.829 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.947348 1.12864353   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 1.2991 1.325195 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 5207.89 5207.89 1.0000 0.27037219 0.226942 21.11 14.31 0.00747543 40201.6 40.00 21.06 0.00800000 60796.0 0.04555624 60.00 32.22 27.78 0.000 5207.89 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00747543 21.11 0.00747543 47.5290 5207.98 0.00 5614.24 5614.24 0.27037219 16.60 12.64 0.00747543 35606.6 36.98 19.88 0.00747543 56371.5
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 12363.684 12363.684 0.789383 0.00010816 288.001 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 3.0840 3.146053 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 12363.68 12363.68 1.0000 0.94044904 0.789383 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.10815187 60.00 32.22 27.78 0.000 12363.68 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00758747 21.00 0.00758747 48.5613 8243.22 0.00 12429.73 12429.73 0.94044904 16.60 13.15 0.00800000 36934.7 29.56 17.89 0.00800000 50151.5
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 3394.369 -999.000 0.309034 0.00012124 -999.000 -999.0000 1.00000 1.00000 1020.7484 1004.8586 1.1914 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.309034 0.36817468   4197.9300 999.8980 24.08288474 13.37 6.70 6.67 674325.42 0.5034 0.503363 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 unknown unknown unknown 8/21 16:40:00 Sensible 3394.37 3347.44 1.0000 0.36817468 0.309034 21.69 15.50 0.00855773 43541.6 12.80 12.00 0.00850000 34322.2 0.12122435 6.70 13.37 6.67 0.000 3394.37 25.37 0.00840546 16.68 0.00000000 0.0000 21.11 0.00855773 21.11 0.00855773 54.3161 3122.93 0.00 3429.90 3323.73 0.36817468 21.69 15.61 0.00855773 43541.6 12.85 12.06 0.00844351 34225.7
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 1615.511 1615.511 0.070398 0.00001413 46.165 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.309034 0.36817468   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 0.4030 0.411082 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 1615.51 1615.51 1.0000 0.08387069 0.070398 21.11 14.39 0.00756892 40439.0 40.00 21.06 0.00800000 60796.0 0.01413176 60.00 32.22 27.78 0.000 1615.51 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00756892 21.11 0.00756892 48.1163 1615.54 0.00 1741.56 1741.56 0.08387069 16.60 12.73 0.00756892 35843.3 36.98 19.95 0.00756892 56608.2
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2992.405 -999.000 0.271857 0.00010688 -999.000 -999.0000 1.00000 1.00000 1020.7628 1004.8586 1.1914 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.271857 0.32388304   4197.9300 999.8980 24.08288474 13.37 6.70 6.67 674325.42 0.4438 0.443754 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown unknown unknown 8/21 17:00:00 Sensible 2992.41 2945.56 1.0000 0.32388304 0.271857 21.69 15.51 0.00856549 43561.3 12.80 12.00 0.00850000 34322.2 0.10686888 6.70 13.37 6.67 0.000 2992.41 25.13 0.00840508 16.59 0.00000000 0.0000 21.11 0.00856549 21.11 0.00856549 54.3647 2747.24 0.00 3023.69 2924.89 0.32388304 21.69 15.61 0.00856549 43561.3 12.84 12.06 0.00844467 34225.6
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 1616.970 1616.970 0.070462 0.00001415 46.207 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.271857 0.32388304   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 0.4033 0.411453 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 1616.97 1616.97 1.0000 0.08394642 0.070462 21.11 14.39 0.00756931 40440.0 40.00 21.06 0.00800000 60796.0 0.01414452 60.00 32.22 27.78 0.000 1616.97 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00756931 21.11 0.00756931 48.1187 1617.00 0.00 1743.13 1743.13 0.08394642 16.60 12.73 0.00756931 35844.3 36.98 19.95 0.00756931 56609.2
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 18889.911 -999.000 1.701853 0.00067469 -999.000 -999.0000 1.00000 1.00000 1020.8197 1004.8586 1.1914 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.701853 2.02754024   4197.9300 999.8980 24.08288474 13.37 6.70 6.67 674325.42 2.8013 2.801253 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 unknown unknown unknown 8/21 13:40:00 Sensible 18889.91 18459.17 1.0000 2.02754024 1.701853 21.69 15.53 0.00859608 43638.9 12.80 12.00 0.00850000 34322.2 0.67462244 6.70 13.37 6.67 0.000 18889.91 26.25 0.00840684 16.99 0.00000000 0.0000 21.11 0.00859608 21.11 0.00859608 54.5569 17197.57 0.00 19086.56 18334.52 2.02754024 21.69 15.64 0.00859608 43638.9 12.83 12.06 0.00844917 34225.2
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 7750.442 7750.442 0.337739 0.00006780 221.475 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.701853 2.02754024   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 1.9333 1.972171 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 7750.44 7750.44 1.0000 0.40237334 0.337739 21.11 14.41 0.00758489 40479.7 40.00 21.06 0.00800000 60796.0 0.06779733 60.00 32.22 27.78 0.000 7750.44 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00758489 21.11 0.00758489 48.2163 7750.54 0.00 8355.19 8355.19 0.40237334 16.60 12.75 0.00758489 35883.8 36.98 19.96 0.00758489 56648.5
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 11065.497 11065.497 1.090883 0.00009681 242.665 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 2.7602 2.815717 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 11065.50 11065.50 1.0000 1.29964727 1.090883 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.09679592 60.00 32.22 27.78 0.000 11065.50 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00767464 21.00 0.00767464 49.1128 5370.48 0.00 11126.72 11126.72 1.29964727 16.60 13.15 0.00800000 36934.7 25.00 16.31 0.00800000 45496.1
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 11449.638 11449.638 1.142824 0.00010017 250.759 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 2.8560 2.913465 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:40:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:40:00 Sensible 11449.64 11449.64 1.0000 1.36152837 1.142824 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.10015621 60.00 32.22 27.78 0.000 11449.64 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00768094 21.00 0.00768094 49.1527 5483.45 0.00 11513.00 11513.00 1.36152837 16.60 13.15 0.00800000 36934.7 24.89 16.28 0.00800000 45390.7
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 7614.602 7614.602 1.171506 0.00006662 160.828 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 1.8994 1.937605 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 23:30:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 23:30:00 Sensible 7614.60 7614.60 1.0000 1.39569989 1.171506 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.06660906 60.00 32.22 27.78 0.000 7614.60 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.32 0.00584758 21.00 0.00584758 37.5377 1523.97 0.00 7657.21 7657.21 1.39569989 16.60 13.15 0.00800000 36934.7 21.98 15.22 0.00800000 42421.0
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 7840.424 7840.424 0.417783 0.00006859 189.336 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 1.9557 1.995068 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:50:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:50:00 Sensible 7840.42 7840.42 1.0000 0.49773513 0.417783 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.06858445 60.00 32.22 27.78 0.000 7840.42 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00772665 21.00 0.00772665 49.4414 5659.13 0.00 7881.32 7881.32 0.49773513 16.60 13.15 0.00800000 36934.7 32.13 18.74 0.00800000 52769.1
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 424222.085 -999.000 22.513504 0.01515223 -999.000 -999.0000 1.00000 1.00000 1021.5473 1004.8586 1.1914 VAV WITH REHEAT FAN Fan:VariableVolume 22.513504 26.82195842   4197.9300 999.8980 24.08288474 13.37 6.70 6.67 674325.42 62.9106 62.910587 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 Sensible 424222.09 389847.36 1.0000 26.82195842 22.513504 25.24 17.12 0.00898749 48259.4 10.96 10.96 0.00850000 32443.1 15.15068427 6.70 13.37 6.67 50444.626 373777.46 26.40 0.00840708 17.04 11.66146000 51.7976 23.99 0.00961159 23.99 0.00957607 50.9364 306277.48 0.00 427924.72 373177.13 26.82195842 25.24 17.24 0.00898749 48259.4 11.62 11.28 0.00817832 32305.1
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 169799.334 169799.334 6.754051 0.00148548 2897.256 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 VAV WITH REHEAT FAN Fan:VariableVolume 22.513504 26.82195842   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 42.3546 43.206995 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:50:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 11:50:00 Sensible 169799.33 169799.33 1.0000 8.04658753 6.754051 -4.30 -4.30 0.00265759 2304.4 16.70 13.09 0.00800000 37036.7 1.48532712 60.00 32.22 27.78 0.000 169799.33 -4.30 0.00265759 -4.30 11.66146000 172.6587 20.96 0.00753089 21.02 0.00755070 48.2658 54676.09 0.00 156250.72 156250.72 8.04658753 2.80 0.02 0.00265759 9473.9 22.03 9.93 0.00265759 28892.1
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 36112.103 -999.000 2.051317 0.00128984 -999.000 -999.0000 1.00000 1.00000 1020.4683 1004.8586 1.1914 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.44379602   4197.9300 999.8980 24.08288474 13.37 6.70 6.67 674325.42 5.3553 5.355293 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 Sensible 36112.10 36112.10 1.0000 2.44388195 2.051317 26.40 17.04 0.00840708 47966.0 11.92 11.55 0.00840708 33189.4 1.28970906 6.70 13.37 6.67 2195.006 33917.10 26.40 0.00840708 17.04 2.05124512 99.9965 21.11 0.00860319 21.11 0.00860802 54.6306 181120.89 0.00 36425.73 35509.87 2.44388195 26.40 17.15 0.00840708 47966.0 12.16 11.59 0.00825857 33061.1
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 15471.261 15471.261 0.615395 0.00013535 263.983 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.44379602   4197.9300 999.8980 3.43770058 54.44 82.22 27.78 400899.47 3.8591 3.936804 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:10:00 Sensible 15471.26 15471.26 1.0000 0.73316458 0.615395 -4.30 -4.30 0.00265759 2304.4 16.70 13.09 0.00800000 37036.7 0.13533554 60.00 32.22 27.78 0.000 15471.26 -4.30 0.00265759 -4.30 2.05124512 333.3216 21.11 0.00751215 21.11 0.00751281 47.7629 91694.56 0.00 14236.78 14236.78 0.73316458 2.80 0.02 0.00265759 9473.9 22.03 9.93 0.00265759 28892.1



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 11.66 22.51 -      
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 18.33 7651.50 0.00
RETAIL_1_FLR_1 899.17 8061.83 472.50
RETAIL_2_FLR_1 245.00 7906.33 0.00
MECH_FLR_1 26.67 8704.00 26.67
STORAGE_FLR_1 66.67 8760.00 66.67
LAUNDRY_FLR_1 7277.33 3255.67 2589.67
CAFE_FLR_1 1006.00 7030.67 18.17
LOBBY_FLR_1 937.83 6480.67 13.67
ROOM_1_FLR_3 2139.83 8436.67 2069.67
ROOM_2_FLR_3 2759.00 8610.00 2744.67
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 912.17 8760.00 912.17
ROOM_5_FLR_3 2061.67 8332.33 2053.50
ROOM_6_FLR_3 2723.67 8625.17 2722.17
CORRIDOR_FLR_3 24.50 8750.00 24.50
ROOM_1_FLR_6 3042.83 8368.83 2917.17
ROOM_2_FLR_6 3540.17 8565.00 3505.17
ROOM_3_MULT9_FLR_6 1426.00 8221.17 1286.83
BANQUET_FLR_6 4056.67 1872.67 11.17
DINING_FLR_6 5645.17 778.67 7.00
KITCHEN_FLR_6 8417.33 6218.17 6186.17
CORRIDOR_FLR_6 96.17 8504.00 49.17
Facility 8755.67 8760.00 7427.33
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 245.33 0.00 245.33
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 6.67 0.00 6.67
ROOM_2_FLR_3 0.00 4.83 0.00 4.83
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.67 0.50 0.67 0.50
ROOM_5_FLR_3 0.00 2.83 0.00 2.83
ROOM_6_FLR_3 0.00 5.00 0.00 5.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 10.33 0.00 10.33
ROOM_2_FLR_6 0.00 7.67 0.00 7.67
ROOM_3_MULT9_FLR_6 0.00 4.00 0.00 4.00
BANQUET_FLR_6 0.00 38.33 0.00 38.33
DINING_FLR_6 0.00 53.00 0.00 53.00
KITCHEN_FLR_6 0.00 434.83 0.00 434.83
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 0.67 524.33 0.67 524.33
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.80 106.50 4826.41 0.922 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 3.068 0.139 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 1.342 0.046 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.561 0.052 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.464 0.052 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 21.278 0.149 0.000 0.000
CAFE_FLR_1 82.58 142.30 748.35 4.243 0.109 0.000 0.000
LOBBY_FLR_1 245.14 422.44 5183.56 1.695 0.045 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.472 0.180 0.000 0.027
ROOM_2_FLR_3 0.95 1.50 118.93 0.472 0.180 0.000 0.027
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.536 0.080 0.000 0.042
ROOM_5_FLR_3 0.95 1.50 118.94 0.472 0.180 0.000 0.027
ROOM_6_FLR_3 0.95 1.50 118.93 0.472 0.180 0.000 0.027
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.558 0.022 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.472 0.180 0.000 0.031
ROOM_2_FLR_6 0.95 1.50 118.93 0.472 0.180 0.000 0.031
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.536 0.146 0.000 0.049
BANQUET_FLR_6 145.01 249.90 1010.89 4.298 0.052 0.000 0.000
DINING_FLR_6 145.01 249.90 1010.89 4.687 0.052 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 20.011 0.150 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 1.114 0.036 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.80 106.50 4826.41 0.556 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 1.821 0.002 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 0.818 0.001 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.334 0.001 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.276 0.001 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 11.941 0.002 0.000 0.000
CAFE_FLR_1 82.58 142.30 748.35 2.626 0.002 0.000 0.000
LOBBY_FLR_1 245.14 422.44 5183.56 1.064 0.001 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.456 0.003 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.456 0.003 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.518 0.001 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.456 0.003 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.456 0.003 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.332 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.456 0.003 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.456 0.003 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.518 0.002 0.000 0.000
BANQUET_FLR_6 145.01 249.90 1010.89 2.234 0.001 0.000 0.000
DINING_FLR_6 145.01 249.90 1010.89 2.341 0.001 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 8.989 0.002 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 0.663 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.80 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.28 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.58 142.30 748.35 188.86 0.0000 0.676
LOBBY_FLR_1 VAV WITH REHEAT 245.14 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 145.01 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 145.01 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.39 1604.23 35184.81 11345.29 0.0000 137.584


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 38332515.61 0.00 38332515.61 0.00 38332515.61 26946214.98 5.83 0.83 8753.34 0.00
RETAIL_1_FLR_1 7071687.51 0.00 7071687.51 319403.00 7391090.52 2498216.28 0.00 0.00 8760.00 0.00
RETAIL_2_FLR_1 3565286.89 0.00 3565286.89 123289.96 3688576.86 2892943.94 164.08 75.51 8520.41 0.00
MECH_FLR_1 3160354.16 0.00 3160354.16 291384.23 3451738.39 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 1508602.64 0.00 1508602.64 168112.65 1676715.29 1821682.01 8760.00 0.00 0.00 0.00
LAUNDRY_FLR_1 56738298.65 0.00 56738298.65 397870.28 57136168.93 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 27438071.57 0.00 27438071.57 706058.42 28144129.99 21330615.53 106.13 23.86 8630.00 0.00
LOBBY_FLR_1 75696242.63 0.00 75696242.63 2017370.18 77713612.82 59728886.00 106.47 21.49 8632.05 0.00
ROOM_1_FLR_3 1946875.62 27944.71 1974820.33 185391.43 2160211.76 1946875.62 0.00 8310.83 449.17 0.00
ROOM_2_FLR_3 1946647.51 28012.81 1974660.33 185377.29 2160037.61 1946647.51 0.00 8310.83 449.17 0.00
ROOM_3_MULT19_FLR_3 26397887.27 31304.55 26429191.82 51726.29 26480918.11 26397887.27 0.00 8317.67 442.33 8760.00
ROOM_4_MULT19_FLR_3 26405105.73 27438.22 26432543.95 51740.43 26484284.38 26405105.73 0.00 8324.10 435.90 0.00
ROOM_5_FLR_3 1946875.62 27880.85 1974756.47 185391.43 2160147.90 1946875.62 0.00 8310.83 449.17 0.00
ROOM_6_FLR_3 1946647.51 27909.70 1974557.21 185377.29 2159934.50 1946647.51 0.00 8310.83 449.17 0.00
CORRIDOR_FLR_3 22905778.20 0.00 22905778.20 224175.54 23129953.74 14972100.18 2.65 0.31 8757.04 0.00
ROOM_1_FLR_6 486718.90 31698.75 518417.66 185430.49 703848.15 486718.90 0.00 8311.00 449.00 0.00
ROOM_2_FLR_6 486661.88 31823.40 518485.28 185416.35 703901.63 486661.88 0.00 8311.00 449.00 0.00
ROOM_3_MULT9_FLR_6 3126920.42 31559.80 3158480.22 94872.73 3253352.95 3126920.42 0.00 8311.00 449.00 0.00
BANQUET_FLR_6 37294058.82 0.00 37294058.82 452774.66 37746833.48 37458366.31 4945.70 326.89 3487.42 0.00
DINING_FLR_6 40656712.73 0.00 40656712.73 452774.66 41109487.39 37458366.31 3496.27 236.28 5027.46 0.00
KITCHEN_FLR_6 54085938.48 0.00 54085938.48 405338.30 54491276.78 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 12123900.76 0.00 12123900.76 396722.51 12520623.27 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.45E+10 5259003.45 0.45E+10 18682123.06 0.45E+10 0.43E+10 8760.00 8349.23 8760.00 8760.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.2155 0.0000 1.2155 0.0000 1.2155 0.8545 5.83 0.83 8753.34
RETAIL_1_FLR_1 0.2242 0.0000 0.2242 0.0101 0.2344 0.0792 0.00 0.00 8760.00
RETAIL_2_FLR_1 0.1131 0.0000 0.1131 0.0039 0.1170 0.0917 164.08 75.51 8520.41
MECH_FLR_1 0.1002 0.0000 0.1002 0.0092 0.1095 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0478 0.0000 0.0478 0.0053 0.0532 0.0578 8760.00 0.00 0.00
LAUNDRY_FLR_1 1.7992 0.0000 1.7992 0.0126 1.8118 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.8701 0.0000 0.8701 0.0224 0.8924 0.6764 106.13 23.86 8630.00
LOBBY_FLR_1 2.4003 0.0000 2.4003 0.0640 2.4643 1.8940 106.47 21.49 8632.05
ROOM_1_FLR_3 0.0617 0.0009 0.0626 0.0059 0.0685 0.0617 0.00 8310.83 449.17
ROOM_2_FLR_3 0.0617 0.0009 0.0626 0.0059 0.0685 0.0617 0.00 8310.83 449.17
ROOM_4_MULT19_FLR_3 0.8373 0.0009 0.8382 0.0016 0.8398 0.8373 0.00 8324.10 435.90
ROOM_5_FLR_3 0.0617 0.0009 0.0626 0.0059 0.0685 0.0617 0.00 8310.83 449.17
ROOM_6_FLR_3 0.0617 0.0009 0.0626 0.0059 0.0685 0.0617 0.00 8310.83 449.17
CORRIDOR_FLR_3 0.7263 0.0000 0.7263 0.0071 0.7334 0.4748 2.65 0.31 8757.04
ROOM_1_FLR_6 0.0154 0.0010 0.0164 0.0059 0.0223 0.0154 0.00 8311.00 449.00
ROOM_2_FLR_6 0.0154 0.0010 0.0164 0.0059 0.0223 0.0154 0.00 8311.00 449.00
ROOM_3_MULT9_FLR_6 0.0992 0.0010 0.1002 0.0030 0.1032 0.0992 0.00 8311.00 449.00
BANQUET_FLR_6 1.1826 0.0000 1.1826 0.0144 1.1969 1.1878 4945.70 326.89 3487.42
DINING_FLR_6 1.2892 0.0000 1.2892 0.0144 1.3036 1.1878 3496.27 236.28 5027.46
KITCHEN_FLR_6 1.7151 0.0000 1.7151 0.0129 1.7279 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.3844 0.0000 0.3844 0.0126 0.3970 0.1256 0.00 0.00 8760.00
Total Facility 79.7928 0.0913 79.8841 0.4677 80.3519 73.9670 8760.00 8349.23 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.54E+09 0.00 0.54E+09 0.22E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 91819351.87 265572.80 92084924.67 64690340.46 0.00 0.00 8760.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 17.1350 0.0000 17.1350 6.9969 0.00 0.00 8760.00
FLR_3_DOAS 2.9116 0.0084 2.9200 2.0513 0.00 0.00 8760.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 5823.92 2774.18 0.00 161.90 0.00 0.00 0.00 0.00 0.00
FLR_3_DOAS 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 16.5545 18.3947 0.0000 16.6390 0.0000 0.0000 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 2.9116 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1318
Defaulted Fields 1181
Fields with Defaults 4005
Autosized Fields 350
Autosizable Fields 402
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 4688.00 74036.38 17-JUN-04:40 326774.97 22-JUL-18:20
Electricity:Building 2518.68 32537.67 10-JUN-05:00 151906.32 02-JAN-20:10
Electricity:Zone:BASEMENT 323.72 3705.45 02-JAN-02:10 24299.15 02-JAN-20:10
Electricity:SpaceType:GENERAL 2511.59 32396.52 10-JUN-05:00 151664.99 02-JAN-20:10
InteriorLights:Electricity 766.57 6704.72 10-JUN-05:00 62892.57 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 173.46 1576.23 02-JAN-02:10 14185.34 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 766.57 6704.72 10-JUN-05:00 62892.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity 766.57 6704.72 10-JUN-05:00 62892.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 173.46 1576.23 02-JAN-02:10 14185.34 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 766.57 6704.72 10-JUN-05:00 62892.57 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 18.80 222.61 02-JAN-02:10 1390.02 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.61 78.27 02-JAN-02:10 704.41 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.61 78.27 02-JAN-02:10 704.41 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 21.77 257.78 02-JAN-02:10 1609.65 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.97 90.64 02-JAN-02:10 815.72 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.97 90.64 02-JAN-02:10 815.72 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 29.11 327.88 02-JAN-02:10 2199.84 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 16.64 151.16 02-JAN-02:10 1360.40 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 16.64 151.16 02-JAN-02:10 1360.40 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 6.38 76.28 02-JAN-02:10 469.87 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.78 25.30 02-JAN-02:10 227.72 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.78 25.30 02-JAN-02:10 227.72 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 72.30 1002.39 02-JAN-02:10 4930.01 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.37 39.69 02-JAN-02:10 357.21 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.37 39.69 02-JAN-02:10 357.21 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 32.27 322.63 10-JUN-05:00 2727.18 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 17.93 119.42 10-JUN-05:00 1761.91 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 17.93 119.42 10-JUN-05:00 1761.91 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 270.87 3198.76 10-JUN-05:00 20294.39 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 121.87 1087.35 10-JUN-05:00 10265.18 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 121.87 1087.35 10-JUN-05:00 10265.18 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 18.66 264.62 01-JAN-02:10 1227.54 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 18.66 264.59 01-JAN-02:10 1227.39 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 304.77 4565.05 01-JAN-02:10 20923.25 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 76.02 643.59 01-JAN-02:10 5851.22 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 76.02 643.59 01-JAN-02:10 5851.22 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 304.86 4566.30 01-JAN-02:10 20928.98 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 76.04 643.77 01-JAN-02:10 5852.82 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 76.04 643.77 01-JAN-02:10 5852.82 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 18.66 264.62 01-JAN-02:10 1227.54 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 18.66 264.59 01-JAN-02:10 1227.39 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 4.66 66.15 01-JAN-02:10 306.88 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.59 13.47 01-JAN-02:10 122.50 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.59 13.47 01-JAN-02:10 122.50 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 4.66 66.15 01-JAN-02:10 306.85 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.59 13.47 01-JAN-02:10 122.49 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.59 13.47 01-JAN-02:10 122.49 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 36.10 540.75 01-JAN-02:10 2478.43 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 9.00 76.24 01-JAN-02:10 693.10 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 9.00 76.24 01-JAN-02:10 693.10 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 210.50 2524.33 20-MAY-05:00 9841.96 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 34.65 275.03 20-MAY-05:00 3094.06 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 34.65 275.03 20-MAY-05:00 3094.06 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 210.50 2524.33 20-MAY-05:00 9841.96 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 34.65 275.03 20-MAY-05:00 3094.06 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 34.65 275.03 20-MAY-05:00 3094.06 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 454.16 6253.02 02-JAN-02:10 18944.06 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.33 121.09 02-JAN-02:10 1089.83 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.33 121.09 02-JAN-02:10 1089.83 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
InteriorEquipment:Electricity 1745.01 25691.80 02-JAN-02:10 89475.41 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1745.01 25691.80 02-JAN-02:10 89475.41 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 433.74 5990.78 01-JAN-00:10 16487.34 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
Refrigeration:Electricity 62.04 1117.41 10-JAN-23:30 3475.34 05-MAY-06:20
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 516.13 2595.78 02-MAY-01:30 131267.84 22-JUL-18:20
LowTempRefrigeration:Refrigeration:Electricity 20.49 0.00 01-JAN-11:10 2041.50 05-MAY-06:20
MedTempRefrigeration:Refrigeration:Electricity 34.46 969.23 11-JAN-04:10 1245.48 17-JAN-07:20
Fans:Electricity 537.27 12564.13 08-OCT-02:20 43740.55 07-APR-19:50
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 791.91 14503.29 13-AUG-01:20 47118.38 07-APR-19:50
ExteriorEquipment:Electricity 651.48 9618.58 02-JAN-02:20 39726.11 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 32.45 553.72 01-JUL-05:00 1868.65 25-JAN-21:10
ElectricityPurchased:Facility 4688.00 74036.38 17-JUN-04:40 326774.97 22-JUL-18:20
ElectricityPurchased:Plant 4688.00 74036.38 17-JUN-04:40 326774.97 22-JUL-18:20
Cogeneration:ElectricityPurchased 4688.00 74036.38 17-JUN-04:40 326774.97 22-JUL-18:20
General:Cogeneration:ElectricityPurchased 4688.00 74036.38 17-JUN-04:40 326774.97 22-JUL-18:20
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 4688.00 74036.38 17-JUN-04:40 326774.97 22-JUL-18:20
ElectricityNet:Plant 4688.00 74036.38 17-JUN-04:40 326774.97 22-JUL-18:20
Cogeneration:ElectricityNet 4688.00 74036.38 17-JUN-04:40 326774.97 22-JUL-18:20
General:Cogeneration:ElectricityNet 4688.00 74036.38 17-JUN-04:40 326774.97 22-JUL-18:20
General:Fans:Electricity 537.27 12564.13 08-OCT-02:20 43740.55 07-APR-19:50
ExteriorLights:Electricity 242.26 0.00 01-JAN-08:20 15448.40 01-JAN-00:10
General:ExteriorLights:Electricity 242.26 0.00 01-JAN-08:20 15448.40 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.91 18.80 01-JAN-00:10 188.00 01-JAN-07:10
HeatRecovery:Electricity 222.19 0.00 20-APR-15:20 9938.94 01-JAN-11:50
General:HeatRecovery:Electricity 222.19 0.00 20-APR-15:20 9938.94 01-JAN-11:50
WaterSystems:Electricity 90.75 1086.56 22-JUL-00:20 4738.77 22-NOV-07:10
Water Heater:WaterSystems:Electricity 90.75 1086.56 22-JUL-00:20 4738.77 22-NOV-07:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 268.11 0.00 01-JAN-00:10 117506.15 22-JUL-18:20
General:Cooling:Electricity 268.11 0.00 01-JAN-00:10 117506.15 22-JUL-18:20
Pumps:Electricity 102.32 47.91 02-APR-11:20 7592.53 25-JUN-18:10
General:Pumps:Electricity 102.32 47.91 02-APR-11:20 7592.53 25-JUN-18:10
WIRED_LTG_ELECTRICITY 26.98 0.00 01-JAN-00:10 2213.82 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 5809.00 29270.80 13-JUN-01:10 531106.15 06-JAN-18:40
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 4020.16 15908.90 13-SEP-10:10 426857.83 06-JAN-18:40
WaterSystems:NaturalGas 3247.83 15908.90 07-JAN-13:50 292900.99 17-MAR-20:30
Water Heater:WaterSystems:NaturalGas 3247.83 15908.90 07-JAN-13:50 292900.99 17-MAR-20:30
Heating:NaturalGas 772.33 0.00 25-MAR-13:00 183280.31 09-APR-22:30
Boiler:Heating:NaturalGas 772.33 0.00 25-MAR-13:00 183280.31 09-APR-22:30


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 773.12 0.00 01-JAN-00:10 489760.11 25-JUN-18:10
PlantLoopCoolingDemand:HVAC 773.12 0.00 01-JAN-00:10 489760.11 25-JUN-18:10
CoolingCoils:PlantLoopCoolingDemand 773.12 0.00 01-JAN-00:10 489760.11 25-JUN-18:10


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 13-JAN-22:00
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 13-JAN-22:00
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 13-JAN-22:00
Water Heater:WaterSystems:Water 5742.51 0.00 18-APR-00:20 0.00 02-JAN-19:10
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 13-JAN-22:00
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 13-JAN-22:00
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 13-JAN-22:00
Water Heater:WaterSystems:MainsWater 5742.51 0.00 18-APR-00:20 0.00 02-JAN-19:10
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 18-JAN-07:50
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 18-JAN-07:50


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 12646.91 144551.05 17-OCT-13:10 1923533.91 25-JUN-18:10
EnergyTransfer:Building 4787.43 47099.65 06-DEC-16:00 331106.76 22-JUL-18:20
EnergyTransfer:Zone:KITCHEN_FLR_6 707.01 7991.00 08-SEP-03:00 36417.63 23-JUL-10:50
Refrigeration:EnergyTransfer 183.80 4033.43 10-JAN-23:20 10745.76 17-JAN-07:20
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 91.90 2016.71 10-JAN-23:20 5372.88 17-JAN-07:20
General:Refrigeration:EnergyTransfer 91.90 2016.71 10-JAN-23:20 5372.88 17-JAN-07:20
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 91.90 2016.71 10-JAN-23:20 5372.88 17-JAN-07:20
EnergyTransfer:Plant 3417.56 16669.18 03-MAY-01:00 1145007.61 25-JUN-18:10
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.63 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 70.28 1857.69 11-JAN-04:10 2686.44 17-JAN-07:20
EnergyTransfer:Zone:BASEMENT 401.69 2077.73 04-APR-06:10 22250.77 20-NOV-20:50
Heating:EnergyTransfer 140.36 0.00 01-JAN-08:10 66611.96 30-DEC-16:10
Heating:EnergyTransfer:Zone:BASEMENT 0.02 0.00 01-JAN-00:10 640.64 30-MAY-24:00
General:Heating:EnergyTransfer 140.36 0.00 01-JAN-08:10 66611.96 30-DEC-16:10
General:Heating:EnergyTransfer:Zone:BASEMENT 0.02 0.00 01-JAN-00:10 640.64 30-MAY-24:00
Cooling:EnergyTransfer 4555.17 29029.01 13-DEC-10:50 327532.90 22-JUL-18:20
Cooling:EnergyTransfer:Zone:BASEMENT 401.67 2077.73 04-APR-06:10 22250.77 20-NOV-20:50
General:Cooling:EnergyTransfer 4555.17 29029.01 13-DEC-10:50 327532.90 22-JUL-18:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 401.67 2077.73 04-APR-06:10 22250.77 20-NOV-20:50
EnergyTransfer:Zone:RETAIL_1_FLR_1 36.79 0.08 30-JAN-05:40 4190.13 27-SEP-13:20
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.60 0.00 01-JAN-00:10 677.49 10-JAN-08:00
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.60 0.00 01-JAN-00:10 677.49 10-JAN-08:00
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 36.19 0.00 02-JAN-07:10 4190.13 27-SEP-13:20
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 36.19 0.00 02-JAN-07:10 4190.13 27-SEP-13:20
EnergyTransfer:Zone:RETAIL_2_FLR_1 33.00 57.53 06-DEC-16:00 1912.62 30-SEP-22:20
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.02 0.00 01-JAN-00:10 144.15 04-MAR-11:30
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.02 0.00 01-JAN-00:10 144.15 04-MAR-11:30
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 32.99 0.00 06-DEC-16:00 1912.62 30-SEP-22:20
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 32.99 0.00 06-DEC-16:00 1912.62 30-SEP-22:20
EnergyTransfer:Zone:MECH_FLR_1 25.27 1.05 11-JAN-04:50 1384.59 23-JUL-10:40
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.05 0.00 01-JAN-00:10 182.85 11-MAR-09:20
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.05 0.00 01-JAN-00:10 182.85 11-MAR-09:20
Cooling:EnergyTransfer:Zone:MECH_FLR_1 25.22 0.00 11-JAN-05:00 1384.59 23-JUL-10:40
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 25.22 0.00 11-JAN-05:00 1384.59 23-JUL-10:40
EnergyTransfer:Zone:STORAGE_FLR_1 10.68 0.02 08-JAN-14:10 653.26 23-JUL-10:40
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.08 0.00 01-JAN-00:10 186.26 12-JAN-15:00
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.08 0.00 01-JAN-00:10 186.26 12-JAN-15:00
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 10.60 0.00 03-JAN-10:20 653.26 23-JUL-10:40
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 10.60 0.00 03-JAN-10:20 653.26 23-JUL-10:40
EnergyTransfer:Zone:LAUNDRY_FLR_1 586.52 5285.08 03-JUN-04:00 38517.68 31-OCT-19:20
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.01 0.00 01-JAN-00:10 502.62 15-JUL-05:00
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.01 0.00 01-JAN-00:10 502.62 15-JUL-05:00
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 586.51 5285.08 03-JUN-04:00 38517.68 31-OCT-19:20
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 586.51 5285.08 03-JUN-04:00 38517.68 31-OCT-19:20
EnergyTransfer:Zone:CAFE_FLR_1 231.20 199.16 06-DEC-16:00 14622.48 27-SEP-13:10
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.18 0.00 01-JAN-00:10 1200.53 05-DEC-08:10
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.18 0.00 01-JAN-00:10 1200.53 05-DEC-08:10
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 231.01 0.00 06-DEC-16:00 14622.48 27-SEP-13:10
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 231.01 0.00 06-DEC-16:00 14622.48 27-SEP-13:10
EnergyTransfer:Zone:LOBBY_FLR_1 741.01 63.25 06-DEC-16:00 47948.11 19-JAN-01:40
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.19 0.00 01-JAN-00:10 2517.14 04-MAR-11:30
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.19 0.00 01-JAN-00:10 2517.14 04-MAR-11:30
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 740.82 0.00 13-DEC-10:50 47948.11 19-JAN-01:40
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 740.82 0.00 13-DEC-10:50 47948.11 19-JAN-01:40
EnergyTransfer:Zone:ROOM_1_FLR_3 50.42 0.10 04-OCT-07:00 11463.87 13-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 17.04 0.00 01-JAN-08:10 5046.89 27-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 17.04 0.00 01-JAN-08:10 5046.89 27-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 33.38 0.00 01-JAN-00:10 11463.87 13-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 33.38 0.00 01-JAN-00:10 11463.87 13-JUN-18:10
EnergyTransfer:Zone:ROOM_2_FLR_3 46.88 0.05 06-SEP-05:30 11152.49 13-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 20.96 0.00 01-JAN-08:10 5226.49 27-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 20.96 0.00 01-JAN-08:10 5226.49 27-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 25.92 0.00 01-JAN-00:10 11152.49 13-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 25.92 0.00 01-JAN-00:10 11152.49 13-JUN-18:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 308.31 0.75 21-DEC-03:40 60010.01 27-SEP-13:30
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 6.29 0.00 01-JAN-00:10 12138.17 17-DEC-04:40
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 6.29 0.00 01-JAN-00:10 12138.17 17-DEC-04:40
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 302.02 0.00 04-JAN-16:50 60010.01 27-SEP-13:30
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 302.02 0.00 04-JAN-16:50 60010.01 27-SEP-13:30
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 279.97 0.45 13-FEB-20:00 57197.97 22-JUL-18:20
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 26.38 0.00 01-JAN-07:30 39129.04 11-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 26.38 0.00 01-JAN-07:30 39129.04 11-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 253.60 0.00 01-JAN-00:10 57197.97 22-JUL-18:20
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 253.60 0.00 01-JAN-00:10 57197.97 22-JUL-18:20
EnergyTransfer:Zone:ROOM_5_FLR_3 50.92 0.12 29-MAY-00:20 10312.79 23-JUL-08:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 17.01 0.00 01-JAN-08:10 5011.39 27-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 17.01 0.00 01-JAN-08:10 5011.39 27-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 33.91 0.00 01-JAN-00:10 10312.79 23-JUL-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 33.91 0.00 01-JAN-00:10 10312.79 23-JUL-08:10
EnergyTransfer:Zone:ROOM_6_FLR_3 46.61 0.00 09-SEP-00:30 9800.17 22-JUL-08:10
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 20.81 0.00 01-JAN-08:10 5234.10 12-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 20.81 0.00 01-JAN-08:10 5234.10 12-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 25.80 0.00 01-JAN-00:10 9800.17 22-JUL-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 25.80 0.00 01-JAN-00:10 9800.17 22-JUL-08:10
EnergyTransfer:Zone:CORRIDOR_FLR_3 173.14 0.09 09-DEC-14:10 10111.60 02-OCT-23:20
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.51 0.00 01-JAN-00:10 2173.68 12-DEC-12:00
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.51 0.00 01-JAN-00:10 2173.68 12-DEC-12:00
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 172.63 0.00 03-JAN-12:40 10111.60 02-OCT-23:20
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 172.63 0.00 03-JAN-12:40 10111.60 02-OCT-23:20
EnergyTransfer:Zone:ROOM_1_FLR_6 14.68 0.05 16-OCT-13:40 3154.71 13-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 6.79 0.00 01-JAN-08:10 1625.97 27-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 6.79 0.00 01-JAN-08:10 1625.97 27-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 7.89 0.00 01-JAN-00:10 3154.71 13-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 7.89 0.00 01-JAN-00:10 3154.71 13-JUN-18:10
EnergyTransfer:Zone:ROOM_2_FLR_6 14.06 0.02 05-MAR-14:00 2936.36 13-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 8.12 0.00 01-JAN-08:10 1700.59 27-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 8.12 0.00 01-JAN-08:10 1700.59 27-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 5.94 0.00 01-JAN-00:10 2936.36 13-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 5.94 0.00 01-JAN-00:10 2936.36 13-JUN-18:10
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 73.03 0.17 30-MAY-04:20 17578.23 12-SEP-15:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 15.02 0.00 01-JAN-08:10 6735.55 27-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 15.02 0.00 01-JAN-08:10 6735.55 27-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 58.02 0.00 01-JAN-00:10 17578.23 12-SEP-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 58.02 0.00 01-JAN-00:10 17578.23 12-SEP-15:10
EnergyTransfer:Zone:BANQUET_FLR_6 413.45 2816.09 13-DEC-10:50 21941.44 05-MAY-23:00
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 100.67 08-NOV-08:00
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 100.67 08-NOV-08:00
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 413.45 2816.09 13-DEC-10:50 21941.44 05-MAY-23:00
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 413.45 2816.09 13-DEC-10:50 21941.44 05-MAY-23:00
EnergyTransfer:Zone:DINING_FLR_6 456.40 2633.96 13-DEC-10:50 23821.35 05-MAY-23:00
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 51.80 08-NOV-08:00
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 51.80 08-NOV-08:00
Cooling:EnergyTransfer:Zone:DINING_FLR_6 456.40 2633.96 13-DEC-10:50 23821.35 05-MAY-23:00
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 456.40 2633.96 13-DEC-10:50 23821.35 05-MAY-23:00
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 615.10 5843.86 08-SEP-03:00 31355.05 23-JUL-10:50
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 615.10 5843.86 08-SEP-03:00 31355.05 23-JUL-10:50
EnergyTransfer:Zone:CORRIDOR_FLR_6 86.37 0.36 28-DEC-07:20 5476.96 23-JUL-10:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.28 0.00 01-JAN-00:10 760.14 05-DEC-08:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.28 0.00 01-JAN-00:10 760.14 05-DEC-08:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 86.09 0.00 04-JAN-09:20 5476.96 23-JUL-10:40
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 86.09 0.00 04-JAN-09:20 5476.96 23-JUL-10:40
PlantLoopHeatingDemand:Facility 1343.92 10165.86 17-AUG-00:40 185180.42 01-FEB-07:30
PlantLoopHeatingDemand:Plant 798.38 10165.14 18-AUG-03:00 55880.14 15-FEB-07:30
WaterSystems:PlantLoopHeatingDemand 798.38 10165.14 18-AUG-03:00 55880.14 15-FEB-07:30
General:WaterSystems:PlantLoopHeatingDemand 798.38 10165.14 18-AUG-03:00 55880.14 15-FEB-07:30
EnergyTransfer:HVAC 4441.93 352.13 08-SEP-14:40 490432.20 25-JUN-18:10
HeatingCoils:EnergyTransfer 545.54 0.00 25-MAR-13:00 154693.09 04-DEC-16:50
PlantLoopHeatingDemand:HVAC 545.54 0.00 25-MAR-13:00 154693.09 04-DEC-16:50
HeatingCoils:PlantLoopHeatingDemand 545.54 0.00 25-MAR-13:00 154693.09 04-DEC-16:50
CoolingCoils:EnergyTransfer 773.12 0.00 01-JAN-00:10 489760.11 25-JUN-18:10
HeatRecoveryForHeating:EnergyTransfer 3121.81 0.00 20-APR-15:20 403226.81 12-JAN-00:10
HeatRecoveryForCooling:EnergyTransfer 1.45 0.00 01-JAN-00:10 29067.60 22-JUL-15:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 798.38 10165.14 18-AUG-03:00 55880.14 15-FEB-07:30
WaterUse:WaterSystems:EnergyTransfer 798.38 10165.14 18-AUG-03:00 55880.14 15-FEB-07:30
Boilers:EnergyTransfer 539.25 0.00 25-MAR-13:00 140424.35 04-DEC-16:50
Chillers:EnergyTransfer 859.96 0.00 01-JAN-00:10 496549.83 25-JUN-18:10
HeatRejection:EnergyTransfer 1128.07 0.00 01-JAN-00:10 611668.52 25-JUN-18:10
General:HeatRejection:EnergyTransfer 1128.07 0.00 01-JAN-00:10 611668.52 25-JUN-18:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.020 -401.672 0.000 0.000 138.659 173.462 150.255 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -60.725
RETAIL_1_FLR_1 0.000 0.000 0.601 -36.190 0.000 0.000 15.949 8.614 10.186 23.385 0.000 0.005 0.000 0.000 -11.558 0.000 -4.730 -6.261
RETAIL_2_FLR_1 0.000 0.000 0.019 -32.985 0.000 0.000 17.168 9.975 11.795 0.000 0.000 0.002 0.000 0.000 0.000 0.000 -1.984 -3.990
MECH_FLR_1 0.000 0.000 0.051 -25.224 0.000 0.000 3.773 16.635 12.471 0.000 0.000 0.006 0.000 0.000 0.000 0.000 -4.485 -3.227
STORAGE_FLR_1 0.000 0.000 0.080 -10.603 0.000 0.000 2.937 2.785 3.598 0.000 0.000 0.003 3.749 0.000 0.000 0.000 -2.548 -0.000
LAUNDRY_FLR_1 0.000 0.000 0.011 -586.506 0.000 0.000 11.225 4.368 658.131 0.000 0.000 0.008 0.000 0.000 0.000 0.000 -6.702 -80.536
CAFE_FLR_1 0.000 0.000 0.184 -231.014 0.000 0.000 199.409 17.932 14.341 64.942 0.000 0.011 0.000 0.000 -34.238 0.000 -11.065 -20.501
LOBBY_FLR_1 0.000 0.000 0.190 -740.824 0.000 0.000 563.255 121.868 148.998 85.307 0.000 0.031 0.000 0.000 -47.729 0.000 -33.415 -97.682
ROOM_1_FLR_3 22.222 -24.638 0.000 -13.922 0.000 0.000 9.759 6.366 12.292 43.869 0.000 0.026 0.000 0.000 -26.085 0.000 -11.415 -18.474
ROOM_2_FLR_3 26.623 -17.989 0.000 -13.601 0.000 0.000 9.788 6.366 12.291 30.476 0.000 0.026 0.000 0.000 -26.265 0.000 -11.289 -16.425
ROOM_3_MULT19_FLR_3 13.851 -105.848 0.000 -203.737 0.000 0.000 0.000 76.021 228.754 279.475 0.000 0.060 0.002 0.000 -145.064 0.000 -75.677 -67.836
ROOM_4_MULT19_FLR_3 70.783 -112.455 0.000 -185.548 0.000 0.000 185.841 76.042 228.817 73.712 0.000 0.262 0.000 0.000 -144.558 0.000 -66.337 -126.557
ROOM_5_FLR_3 22.093 -24.979 0.000 -14.019 0.000 0.000 9.750 6.366 12.292 44.309 0.000 0.026 0.000 0.000 -25.621 0.000 -11.445 -18.772
ROOM_6_FLR_3 26.400 -17.617 0.000 -13.769 0.000 0.000 9.774 6.366 12.291 30.646 0.000 0.026 0.000 0.000 -25.595 0.000 -11.342 -17.181
CORRIDOR_FLR_3 0.000 0.000 0.508 -172.635 0.000 0.000 119.795 109.603 0.000 39.467 0.000 0.015 0.000 0.000 -33.802 0.000 -13.788 -49.162
ROOM_1_FLR_6 8.298 -5.948 0.000 -3.448 0.000 0.000 2.443 1.592 3.073 10.918 0.000 0.006 0.000 0.000 -6.442 0.000 -2.872 -7.621
ROOM_2_FLR_6 9.786 -4.230 0.000 -3.370 0.000 0.000 2.450 1.591 3.073 7.585 0.000 0.007 0.000 0.000 -6.476 0.000 -2.842 -7.575
ROOM_3_MULT9_FLR_6 22.067 -42.187 0.000 -22.876 0.000 0.000 21.889 9.005 27.097 60.556 0.000 0.038 0.000 0.000 -30.560 0.000 -14.049 -30.978
BANQUET_FLR_6 0.000 0.000 0.000 -413.451 0.000 0.000 316.178 34.646 175.857 6.953 0.000 0.005 0.000 0.000 -19.943 0.000 -8.065 -92.178
DINING_FLR_6 0.000 0.000 0.000 -456.403 0.000 0.000 314.889 34.646 175.857 6.723 0.000 0.005 0.000 0.000 -20.498 0.000 -8.128 -47.089
KITCHEN_FLR_6 0.000 0.000 0.000 -615.091 0.000 0.000 28.298 13.327 550.372 20.651 0.000 0.004 23.322 0.000 -13.597 0.000 -7.286 -0.001
CORRIDOR_FLR_6 0.000 0.000 0.278 -86.091 0.000 0.000 31.971 28.999 0.000 19.454 0.000 0.005 26.549 0.000 -15.087 0.000 -6.078 -0.000
Total Facility 222.125 -355.890 1.942 -4282.979 0.000 0.000 2015.200 766.574 2451.839 848.426 0.000 0.576 53.622 0.000 -633.119 0.000 -315.542 -772.772


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 10-NOV-21:18 0.00 0.00 0.00 -36745.14 0.00 0.00 5924.53 12609.30 9581.50 0.00 0.00 0.00 8629.82 0.00 -0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 17-FEB-14:08 0.00 0.00 0.00 -4655.07 0.00 0.00 150.85 195.67 252.59 5996.60 0.00 0.00 0.00 0.00 -0.00 0.00 -221.81 -1718.83
RETAIL_2_FLR_1 30-SEP-22:15 0.00 0.00 0.00 -2648.87 0.00 0.00 613.11 271.91 334.29 0.00 0.00 0.00 1504.04 0.00 -0.00 0.00 -74.47 0.00
MECH_FLR_1 29-APR-00:50 0.00 0.00 0.00 -1919.41 0.00 0.00 182.12 302.31 265.09 0.00 0.00 0.00 1344.08 0.00 -0.00 0.00 -174.19 0.00
STORAGE_FLR_1 29-APR-00:50 0.00 0.00 0.00 -902.69 0.00 0.00 141.83 50.60 76.47 0.00 0.00 0.00 732.88 0.00 -0.00 0.00 -99.09 0.00
LAUNDRY_FLR_1 20-NOV-21:28 0.00 0.00 0.00 -51743.59 0.00 0.00 447.42 317.52 41967.83 0.00 0.00 0.00 9343.02 0.00 -0.00 0.00 -332.21 0.00
CAFE_FLR_1 08-SEP-04:03 0.00 0.00 0.00 -22899.36 0.00 0.00 9072.95 391.53 304.82 0.00 0.00 0.00 15524.51 0.00 -1979.34 0.00 -415.11 0.00
LOBBY_FLR_1 19-JAN-01:35 0.00 0.00 0.00 -74145.23 0.00 0.00 27344.12 1710.86 2639.27 0.00 0.00 0.00 46060.01 0.00 -2428.80 0.00 -1180.24 0.00
ROOM_1_FLR_3 21-MAY-15:02 0.00 -12324.40 0.00 -653.92 0.00 0.00 130.72 161.71 305.54 10301.27 0.00 0.00 2606.43 0.00 -0.00 0.00 -527.35 0.00
ROOM_2_FLR_3 13-JUN-18:02 0.00 -11291.46 0.00 -756.33 0.00 0.00 335.50 436.07 516.20 9186.93 0.00 32.11 1540.98 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 27-SEP-13:30 0.00 -49312.41 0.00 -10692.29 0.00 0.00 0.00 1638.34 5097.90 75397.05 0.00 0.00 0.00 0.00 -0.00 0.00 -270.75 -21857.83
ROOM_4_MULT19_FLR_3 13-JUN-18:02 0.00 -53115.28 0.00 -10258.41 0.00 0.00 6402.32 5209.05 9610.21 17612.00 0.00 444.16 24095.96 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 12-JUN-18:02 0.00 -11238.82 0.00 -723.45 0.00 0.00 335.50 436.12 516.26 1378.04 0.00 83.93 9212.42 0.00 -0.00 0.00 0.00 0.00
ROOM_6_FLR_3 14-AUG-15:02 0.00 -10251.42 0.00 -735.35 0.00 0.00 235.29 137.19 273.90 2319.90 0.00 68.30 7952.20 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 29-APR-00:50 0.00 0.00 0.00 -14075.34 0.00 0.00 5708.28 1991.81 0.00 0.00 0.00 0.00 8956.83 0.00 -2039.15 0.00 -542.43 0.00
ROOM_1_FLR_6 13-JUN-18:02 0.00 -3259.32 0.00 -188.01 0.00 0.00 83.87 109.03 129.07 2100.94 0.00 9.33 1015.09 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_6 13-JUN-18:02 0.00 -2930.54 0.00 -189.81 0.00 0.00 83.88 109.02 129.05 2280.17 0.00 7.35 510.89 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 12-SEP-15:02 0.00 -18125.50 0.00 -1205.44 0.00 0.00 529.40 194.07 603.86 10077.34 0.00 0.00 8207.32 0.00 -0.00 0.00 -281.06 0.00
BANQUET_FLR_6 29-APR-00:50 0.00 0.00 0.00 -38061.92 0.00 0.00 15644.73 687.57 2249.30 0.00 0.00 0.00 20851.59 0.00 -1082.51 0.00 -288.76 0.00
DINING_FLR_6 29-APR-00:50 0.00 0.00 0.00 -40904.24 0.00 0.00 15644.58 687.57 2249.30 0.00 0.00 0.00 23707.12 0.00 -1096.23 0.00 -288.10 0.00
KITCHEN_FLR_6 22-OCT-21:19 0.00 0.00 0.00 -38769.62 0.00 0.00 1234.04 605.46 16762.29 0.00 0.00 0.00 21254.62 0.00 -794.23 0.00 -292.57 0.00
CORRIDOR_FLR_6 29-APR-00:50 0.00 0.00 0.00 -7257.97 0.00 0.00 1539.85 527.00 0.00 0.00 0.00 0.00 6332.79 0.00 -906.31 0.00 -235.36 0.00
Total Facility 22-JUL-18:02 0.00 -140784.90 0.00 -207980.86 0.00 0.00 63889.82 50105.45 115172.27 65670.70 0.00 4332.44 49595.08 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 27-APR-24:00 0.00 0.00 1559.68 0.00 0.00 0.00 6996.80 3152.28 3193.83 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -14902.59
RETAIL_1_FLR_1 28-JAN-08:05 0.00 0.00 1993.29 0.00 0.00 0.00 447.60 313.07 360.84 0.00 0.00 0.00 0.00 0.00 -524.45 0.00 -170.12 -2420.24
RETAIL_2_FLR_1 08-NOV-08:00 0.00 0.00 343.54 0.00 0.00 0.00 392.18 453.18 501.43 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -72.27 -1618.05
MECH_FLR_1 17-FEB-14:09 0.00 0.00 755.32 0.00 0.00 0.00 43.84 377.89 309.27 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -170.60 -1315.72
STORAGE_FLR_1 28-JAN-08:05 0.00 0.00 466.60 0.00 0.00 0.00 84.31 101.21 127.45 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -90.65 -688.92
LAUNDRY_FLR_1 01-MAY-02:29 0.00 0.00 3126.73 0.00 0.00 0.00 606.29 39.69 9326.18 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -235.73 -12863.16
CAFE_FLR_1 28-JAN-08:05 0.00 0.00 4481.21 0.00 0.00 0.00 5880.67 783.07 508.04 0.00 0.00 0.00 0.00 0.00 -1527.99 0.00 -378.64 -9746.36
LOBBY_FLR_1 08-NOV-08:00 0.00 0.00 6412.63 0.00 0.00 0.00 13027.86 5303.68 6334.24 0.00 0.00 0.00 0.00 0.00 -1283.71 0.00 -1203.48 -28591.21
ROOM_1_FLR_3 10-JAN-09:01 8513.27 297.65 0.00 -297.65 0.00 0.00 108.88 215.61 453.05 749.01 0.00 0.00 0.00 0.00 -0.00 0.00 -691.84 -9347.97
ROOM_2_FLR_3 10-JAN-09:01 8437.62 292.75 0.00 -292.75 0.00 0.00 108.88 215.58 452.99 0.00 0.00 0.00 0.00 0.00 -1824.12 0.00 -689.86 -6701.10
ROOM_3_MULT19_FLR_3 17-DEC-04:40 12137.84 3428.76 0.00 -3428.76 0.00 0.00 0.00 643.59 3921.46 0.00 0.00 0.00 0.00 0.00 -11512.33 0.00 -2815.68 -2374.88
ROOM_4_MULT19_FLR_3 11-JAN-16:01 45174.94 3747.53 0.00 -3747.53 0.00 0.00 5582.29 1638.79 5099.29 0.00 0.00 0.00 0.00 0.00 -9527.62 0.00 -3340.18 -44627.50
ROOM_5_FLR_3 10-JAN-19:01 8361.75 297.23 0.00 -297.23 0.00 0.00 419.20 436.12 516.26 0.00 0.00 0.00 0.00 0.00 -2446.33 0.00 -726.60 -6560.40
ROOM_6_FLR_3 11-JAN-19:01 8282.14 292.48 0.00 -292.48 0.00 0.00 419.21 436.07 516.20 0.00 0.00 0.00 0.00 0.00 -2334.20 0.00 -722.95 -6596.46
CORRIDOR_FLR_3 28-JAN-08:05 0.00 0.00 6919.91 0.00 0.00 0.00 3464.47 3983.61 0.00 0.00 0.00 0.00 0.00 0.00 -1522.55 0.00 -484.66 -12360.78
ROOM_1_FLR_6 10-JAN-09:01 2557.47 75.61 0.00 -75.61 0.00 0.00 27.22 53.90 113.26 191.32 0.00 0.00 0.00 0.00 -0.00 0.00 -173.90 -2769.27
ROOM_2_FLR_6 10-JAN-09:01 2529.80 73.94 0.00 -73.94 0.00 0.00 27.22 53.90 113.25 0.00 0.00 0.00 0.00 0.00 -452.02 0.00 -173.23 -2098.92
ROOM_3_MULT9_FLR_6 16-DEC-16:11 12413.39 655.46 0.00 -655.46 0.00 0.00 332.94 228.73 673.54 0.00 0.00 0.00 0.00 0.00 -1517.95 0.00 -440.03 -11690.62
BANQUET_FLR_6 08-NOV-08:00 0.00 0.00 1006.69 0.00 0.00 0.00 7070.03 1489.73 6747.90 0.00 0.00 0.00 0.00 0.00 -800.11 0.00 -300.72 -15213.52
DINING_FLR_6 08-NOV-08:00 0.00 0.00 517.99 0.00 0.00 0.00 6952.23 1489.73 6747.90 0.00 0.00 0.00 0.00 0.00 -829.99 0.00 -304.19 -14573.68
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 28-JAN-08:05 0.00 0.00 4727.54 0.00 0.00 0.00 916.64 1054.01 0.00 0.00 0.00 0.00 0.00 0.00 -681.97 0.00 -215.47 -5800.75
Total Facility 30-DEC-16:01 15821.61 91736.38 1091.67 -91736.38 0.00 0.00 35687.08 17988.09 78718.24 0.00 0.00 0.00 0.00 0.00 -30688.12 0.00 -13382.18 -105236.38



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 22.6359 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 22.5135 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 11.6575 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.6575 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.000000 142.3000 0.003581 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.001045 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5319 2.5319 1.3040 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4710 0.4710 0.2426 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2377 0.2377 0.1224 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2115 0.2115 0.1089 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1010 0.1010 0.0520 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.2807 3.2807 1.6896 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.8272 1.8272 0.9410 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.0188 5.0188 2.5847 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5328 1.5328 0.7894 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1182 2.1182 1.0909 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2191 2.2191 1.1428 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2748 2.2748 1.1715 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8112 0.8112 0.4178 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 22.6359 22.5135 22.6359 11.6575 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3040 1.3040 1.3040 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2426 0.2426 0.2426 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1224 0.1224 0.1224 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1089 0.1089 0.1089 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0520 0.0520 0.0520 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6896 1.6896 1.6896 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9410 0.9410 0.9410 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5847 2.5847 2.5847 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7894 0.7894 0.7894 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0909 1.0909 1.0909 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1428 1.1428 1.1428 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1715 1.1715 1.1715 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4178 0.4178 0.4178 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 11.6575 11.6575 11.6575 11.6575 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.67
Number of hours cooling loads not met 524.33
Number of hours not met 525.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 772.33 183280.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 268.11 117506.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 766.57 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 242.26 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 959.56 59492.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 14.43 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 8.99 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 32.45 1868.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.91 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 537.27 43740.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 102.32 7592.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 222.19 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.75 4738.77 3247.83 292900.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 20.49 2041.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 34.46 1245.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1807.06 4688.00
Natural Gas 1788.84 5809.00
Additional 0.00 0.00
Total 3595.90 10497.00


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 67.57
Space Heating 0.00
Space Cooling 23.63
Fans (All) 47.36
Service Water Heating 8.00
Receptacle Equipment 153.81
Miscellaneous (All) 413.21
Subtotal 413.21


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 68.07
Service Water Heating 286.27
Miscellaneous (All) 512.02
Subtotal 512.02


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 7.30
Space Heating 7.36
Space Cooling 2.55
Fans (All) 5.12
Service Water Heating 31.81
Receptacle Equipment 33.67
Miscellaneous 12.20


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2667. 8760.
LTG_SCH_LOBBY 3061. 8760.
LTG_SCH_STORAGE 1339. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 2678. 8760.
LTG_SCH_GUESTROOM 2482. 8760.
LTG_SCH_CORRIDOR 3061. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3924. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 18.89 365 18.89 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 23.33 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8759.83 0.17 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8759.00 1.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8759.00 0.00 0.00 0.00 0.00
Max 8760.00 1.00 0.00 0.00 0.00
Average 8759.95 0.05 0.00 0.00 0.00
Sum 192718.83 1.17 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37202.17 0.83 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108260.17 8.83 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 8.83 0.00 0.00 0.00
Average 288886.61 0.44 0.00 0.00 0.00
Sum 6355505.33 9.67 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8758.17 1.83 0.00 0.00 0.00
LOBBY_FLR_1 8737.17 22.83 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8729.00 31.00 0.00 0.00 0.00
DINING_FLR_6 8750.83 9.17 0.00 0.00 0.00
KITCHEN_FLR_6 8758.17 1.83 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8729.00 0.00 0.00 0.00 0.00
Max 8760.00 31.00 0.00 0.00 0.00
Average 8756.97 3.03 0.00 0.00 0.00
Sum 192653.33 66.67 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710182.33 234.67 0.00 0.00 0.00
LOBBY_FLR_1 2106872.67 8556.33 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1238879.33 6835.67 0.00 0.00 0.00
DINING_FLR_6 1243753.33 1961.67 0.00 0.00 0.00
KITCHEN_FLR_6 108252.83 16.17 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2106872.67 8556.33 0.00 0.00 0.00
Average 288086.84 800.20 0.00 0.00 0.00
Sum 6337910.50 17604.50 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:59:48

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

For: Environment

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C

For: Environment

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES

For: Environment

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.332019E+11 28175.20 13-JAN-21:59 5.00 4.51 0.784582E+10 4862.81 31-JAN-22:19 7.00 5.39
February 0.293002E+11 26187.20 02-FEB-21:47 6.00 5.05 0.701106E+10 4838.92 06-FEB-22:19 5.33 5.33
March 0.315426E+11 24764.20 01-MAR-21:25 5.50 4.57 0.763489E+10 4828.77 09-MAR-22:10 5.92 4.10
April 0.314062E+11 24537.54 24-APR-23:32 6.80 4.81 0.735417E+10 4825.86 10-APR-22:10 6.80 4.81
May 0.323996E+11 23941.09 05-MAY-22:55 5.00 4.09 0.761241E+10 4804.58 03-MAY-21:40 5.00 4.09
June 0.324106E+11 21903.83 06-JUN-03:35 8.33 6.67 0.740193E+10 4781.76 06-JUN-21:49 8.00 6.23
July 0.346160E+11 22163.02 05-JUL-05:30 8.00 7.21 0.777786E+10 4836.96 19-JUL-21:19 14.00 12.84
August 0.353135E+11 21478.05 20-AUG-03:12 9.00 8.27 0.789684E+10 4837.04 09-AUG-21:10 9.00 8.27
September 0.352420E+11 33948.71 28-SEP-06:14 7.00 6.16 0.775920E+10 4867.65 20-SEP-00:40 7.00 6.16
October 0.364092E+11 35449.81 05-OCT-21:37 5.33 4.26 0.807254E+10 4950.51 25-OCT-04:19 7.67 7.31
November 0.350583E+11 36745.66 10-NOV-21:18 3.67 3.67 0.782469E+10 4931.75 14-NOV-00:40 8.00 8.00
December 0.347708E+11 36137.52 20-DEC-21:48 5.33 4.84 0.801052E+10 4860.32 04-DEC-22:49 5.33 4.84
                     
Annual Sum or Average 0.401671E+12         0.922019E+11        
Minimum of Months 0.293002E+11 21478.05   3.67 3.67 0.701106E+10 4781.76   5.00 4.09
Maximum of Months 0.364092E+11 36745.66   9.00 8.27 0.807254E+10 4950.51   14.00 12.84



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.138398E+10 3770.88 20-JAN-11:57 8.00 6.08 0.623319E+09 382.32 25-JAN-23:19 8.00 7.40
February 0.159387E+10 4655.15 17-FEB-14:08 6.00 3.06 0.565335E+09 373.18 21-FEB-00:10 6.00 4.59
March 0.146169E+10 3363.66 31-MAR-15:06 7.33 4.46 0.623492E+09 380.77 31-MAR-21:49 5.07 2.85
April 0.371262E+10 3856.22 29-APR-00:50 6.98 6.13 0.623550E+09 416.29 28-APR-21:30 6.98 6.13
May 0.374521E+10 3351.11 01-MAY-14:48 8.67 7.22 0.639369E+09 417.74 22-MAY-21:30 14.50 12.46
June 0.425549E+10 2835.36 13-JUN-10:33 22.00 15.85 0.624387E+09 427.33 13-JUN-21:30 14.00 12.84
July 0.479752E+10 3336.64 22-JUL-13:30 28.00 16.51 0.656386E+09 433.21 21-JUL-21:30 28.00 16.51
August 0.514998E+10 3367.57 19-AUG-13:10 20.67 15.34 0.667834E+09 435.63 14-AUG-21:30 20.67 15.34
September 0.485232E+10 4190.13 27-SEP-13:20 21.33 13.25 0.642994E+09 434.13 12-SEP-21:30 21.33 13.25
October 0.290908E+10 3786.37 07-OCT-13:10 17.00 9.32 0.634704E+09 408.34 05-OCT-21:19 17.00 9.32
November 0.158562E+10 3611.14 11-NOV-12:37 9.00 7.29 0.603116E+09 384.11 14-NOV-00:40 8.00 8.00
December 0.742505E+09 3647.56 18-DEC-12:07 8.00 5.60 0.620938E+09 368.25 04-DEC-23:10 8.00 5.60
                     
Annual Sum or Average 0.361899E+11         0.752542E+10        
Minimum of Months 0.742505E+09 2835.36   6.00 3.06 0.565335E+09 368.25   5.07 2.85
Maximum of Months 0.514998E+10 4655.15   28.00 16.51 0.667834E+09 435.63   28.00 16.51



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.244390E+10 1924.68 19-JAN-01:35 7.43 6.61 0.793619E+09 537.84 25-JAN-22:49 8.00 7.45
February 0.225538E+10 2007.14 17-FEB-14:08 6.00 3.06 0.726157E+09 533.36 27-FEB-22:10 4.83 4.83
March 0.250233E+10 1999.81 23-MAR-06:25 7.00 4.75 0.808700E+09 540.42 31-MAR-21:49 5.07 2.85
April 0.281382E+10 2319.01 29-APR-00:50 6.98 6.13 0.840788E+09 569.54 27-APR-21:10 6.98 6.13
May 0.292571E+10 2184.62 05-MAY-22:55 5.00 4.09 0.876033E+09 569.88 10-MAY-21:00 7.00 6.47
June 0.301513E+10 2006.17 06-JUN-03:35 8.33 6.67 0.867889E+09 569.53 13-JUN-23:19 12.67 12.30
July 0.321499E+10 1990.06 05-JUL-01:38 8.33 7.62 0.904874E+09 569.52 06-JUL-21:19 13.67 12.13
August 0.326090E+10 1984.25 20-AUG-03:12 9.00 8.27 0.917315E+09 569.53 14-AUG-21:30 9.00 8.27
September 0.305717E+10 2649.00 30-SEP-22:15 7.83 5.65 0.873734E+09 569.84 27-SEP-00:40 7.83 5.65
October 0.274883E+10 2636.07 05-OCT-21:18 5.67 4.44 0.846483E+09 570.42 06-OCT-21:30 6.50 4.88
November 0.243389E+10 1894.04 06-NOV-07:29 7.50 7.23 0.783327E+09 540.95 17-NOV-22:10 6.00 5.12
December 0.231321E+10 1929.74 12-DEC-11:57 6.00 4.59 0.776175E+09 509.95 20-DEC-22:19 4.67 4.35
                     
Annual Sum or Average 0.329853E+11         0.100151E+11        
Minimum of Months 0.225538E+10 1894.04   5.00 3.06 0.726157E+09 509.95   4.67 2.85
Maximum of Months 0.326090E+10 2649.00   9.00 8.27 0.917315E+09 570.42   13.67 12.30



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.150404E+10 1584.20 28-JAN-08:04 7.02 6.46 0.154305E+09 99.45 27-JAN-22:10 7.02 6.46
February 0.146596E+10 1486.92 01-FEB-18:50 6.00 6.00 0.139626E+09 98.53 27-FEB-22:10 4.83 4.83
March 0.182735E+10 1660.59 23-MAR-06:25 7.00 4.75 0.156953E+09 100.74 21-MAR-21:10 7.00 4.75
April 0.222928E+10 1919.43 29-APR-00:50 6.98 6.13 0.162646E+09 110.98 28-APR-21:10 6.98 6.13
May 0.237604E+10 1825.91 05-MAY-22:55 5.00 4.09 0.172154E+09 113.63 23-MAY-21:10 12.00 9.78
June 0.253892E+10 1699.86 06-JUN-03:35 8.33 6.67 0.175200E+09 118.82 13-JUN-21:10 14.00 12.84
July 0.272234E+10 1724.87 27-JUL-02:00 9.00 9.00 0.184571E+09 120.08 24-JUL-21:10 9.00 9.00
August 0.274416E+10 1715.59 20-AUG-03:12 9.00 8.27 0.186107E+09 118.55 17-AUG-21:10 9.00 8.27
September 0.251571E+10 1775.70 28-SEP-04:57 8.00 6.48 0.174351E+09 116.39 13-SEP-21:10 8.00 6.48
October 0.220181E+10 1830.69 01-OCT-00:47 7.43 6.28 0.165175E+09 109.11 02-OCT-21:49 8.00 6.98
November 0.178750E+10 1566.38 06-NOV-07:29 7.50 7.23 0.151796E+09 101.08 10-NOV-22:10 3.17 3.09
December 0.131041E+10 1383.74 05-DEC-19:04 6.17 5.65 0.153238E+09 96.55 20-DEC-22:10 4.83 4.43
                     
Annual Sum or Average 0.252235E+11         0.197612E+10        
Minimum of Months 0.131041E+10 1383.74   5.00 4.09 0.139626E+09 96.55   3.17 3.09
Maximum of Months 0.274416E+10 1919.43   9.00 9.00 0.186107E+09 120.08   14.00 12.84



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.470077E+09 736.55 19-JAN-01:35 7.43 6.61 0.117058E+09 72.35 25-JAN-22:49 8.00 7.45
February 0.479359E+09 653.04 04-FEB-15:12 8.33 6.25 0.105788E+09 71.36 07-FEB-23:10 6.83 6.83
March 0.681224E+09 768.72 23-MAR-06:25 7.00 4.75 0.118126E+09 72.67 31-MAR-21:49 5.07 2.85
April 0.102087E+10 902.70 29-APR-00:50 6.98 6.13 0.121533E+09 82.19 30-APR-23:10 11.87 8.94
May 0.109172E+10 847.84 05-MAY-22:55 5.00 4.09 0.128631E+09 83.04 23-MAY-22:10 11.83 9.72
June 0.117283E+10 802.96 06-JUN-03:35 8.33 6.67 0.131229E+09 86.96 13-JUN-22:10 13.83 12.78
July 0.126061E+10 814.37 27-JUL-02:00 9.00 9.00 0.138437E+09 87.70 24-JUL-21:40 9.00 9.00
August 0.127214E+10 805.95 20-AUG-03:12 9.00 8.27 0.139666E+09 86.64 17-AUG-21:40 9.00 8.27
September 0.116365E+10 839.08 28-SEP-04:57 8.00 6.48 0.130737E+09 85.07 13-SEP-21:40 8.00 6.48
October 0.990802E+09 856.93 01-OCT-00:47 7.43 6.28 0.123243E+09 79.73 02-OCT-21:49 8.00 6.98
November 0.685177E+09 729.47 06-NOV-07:29 7.50 7.23 0.114123E+09 72.76 10-NOV-23:10 3.83 3.45
December 0.314492E+09 593.75 22-DEC-18:52 5.00 4.08 0.116744E+09 69.91 20-DEC-22:19 5.00 4.08
                     
Annual Sum or Average 0.106029E+11         0.148531E+10        
Minimum of Months 0.314492E+09 593.75   5.00 4.08 0.105788E+09 69.91   3.83 2.85
Maximum of Months 0.127214E+10 902.70   9.00 9.00 0.139666E+09 87.70   13.83 12.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.480909E+11 50312.93 30-JAN-21:43 5.08 4.59 0.588213E+09 483.83 30-JAN-21:40 5.08 4.59
February 0.435673E+11 50854.25 21-FEB-21:53 4.00 4.00 0.532635E+09 456.25 26-FEB-22:10 6.00 6.00
March 0.486947E+11 51529.43 31-MAR-20:45 5.50 2.86 0.594022E+09 505.40 01-MAR-21:30 5.50 2.86
April 0.486947E+11 50079.03 19-APR-20:53 6.00 4.60 0.576028E+09 536.84 24-APR-21:40 7.00 4.89
May 0.504916E+11 48637.91 10-MAY-21:07 7.00 6.47 0.598648E+09 514.87 03-MAY-21:40 7.00 6.47
June 0.497517E+11 39721.32 06-JUN-20:03 8.83 7.36 0.574937E+09 453.52 06-JUN-21:49 8.00 6.23
July 0.515823E+11 40315.92 04-JUL-21:55 9.00 9.00 0.593142E+09 404.65 05-JUL-04:40 7.33 6.64
August 0.519743E+11 38262.26 14-AUG-20:00 20.70 12.26 0.594068E+09 387.74 03-AUG-04:19 20.70 12.26
September 0.495719E+11 47885.56 30-SEP-20:38 7.67 5.91 0.574512E+09 428.52 20-SEP-00:40 7.67 5.91
October 0.495040E+11 51386.22 05-OCT-20:48 5.83 4.52 0.596221E+09 480.89 30-OCT-21:10 6.00 6.00
November 0.469702E+11 51744.82 20-NOV-21:28 4.50 3.82 0.574174E+09 475.13 01-NOV-21:30 4.50 3.82
December 0.476139E+11 51269.38 20-DEC-21:44 5.33 4.84 0.587338E+09 439.07 14-DEC-21:30 5.33 4.84
                     
Annual Sum or Average 0.586508E+12         0.698394E+10        
Minimum of Months 0.435673E+11 38262.26   4.00 2.86 0.532635E+09 387.74   4.50 2.86
Maximum of Months 0.519743E+11 51744.82   20.70 12.26 0.598648E+09 536.84   20.70 12.26



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.161773E+11 16661.27 07-JAN-13:41 7.03 3.95 0.868532E+10 6190.40 24-JAN-01:10 7.05 6.52
February 0.155116E+11 19486.84 04-FEB-15:15 8.33 6.25 0.795646E+10 5884.08 27-FEB-22:19 4.67 4.67
March 0.162407E+11 13876.52 31-MAR-15:06 7.33 4.46 0.876456E+10 6084.40 31-MAR-21:49 5.07 2.85
April 0.207468E+11 17337.07 29-APR-00:50 6.98 6.13 0.918567E+10 6748.79 04-APR-23:30 6.98 6.13
May 0.208388E+11 16275.13 12-MAY-03:13 7.00 6.47 0.945914E+10 6569.38 09-MAY-23:40 7.00 6.47
June 0.213730E+11 14882.16 06-JUN-03:35 8.33 6.67 0.931644E+10 6753.69 03-JUN-04:10 8.33 6.67
July 0.229941E+11 15002.88 05-JUL-01:38 8.33 7.62 0.977642E+10 6460.31 21-JUL-22:10 16.83 13.34
August 0.239970E+11 14167.98 28-AUG-03:46 9.17 8.59 0.100246E+11 6460.80 14-AUG-22:10 9.17 8.59
September 0.233142E+11 22907.87 08-SEP-04:03 7.17 6.56 0.960820E+10 6632.83 28-SEP-03:00 7.00 6.01
October 0.193782E+11 15756.77 03-OCT-00:43 8.00 6.49 0.923880E+10 6545.05 25-OCT-04:19 7.67 7.31
November 0.160654E+11 14179.91 11-NOV-12:40 9.00 7.29 0.853883E+10 6218.70 14-NOV-00:40 8.00 8.00
December 0.143758E+11 14775.52 12-DEC-11:57 6.00 4.59 0.850533E+10 5661.91 04-DEC-23:10 6.00 4.59
                     
Annual Sum or Average 0.231013E+12         0.109060E+12        
Minimum of Months 0.143758E+11 13876.52   6.00 3.95 0.795646E+10 5661.91   4.67 2.85
Maximum of Months 0.239970E+11 22907.87   9.17 8.59 0.100246E+11 6753.69   16.83 13.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.558990E+11 74169.69 19-JAN-01:35 7.43 6.61 0.283050E+11 19205.24 25-JAN-22:49 8.00 7.45
February 0.514100E+11 44745.90 17-FEB-14:08 6.00 3.06 0.258712E+11 18972.79 06-FEB-22:19 6.00 3.06
March 0.566496E+11 43491.33 23-MAR-06:25 7.00 4.75 0.287696E+11 19132.93 31-MAR-21:49 5.07 2.85
April 0.629029E+11 62016.86 13-APR-21:26 6.50 4.42 0.295263E+11 20018.71 04-APR-23:30 6.50 4.42
May 0.651257E+11 68300.52 10-MAY-21:07 7.00 6.47 0.306266E+11 19846.84 09-MAY-23:40 7.00 6.47
June 0.665112E+11 56982.89 16-JUN-23:56 9.00 9.00 0.301701E+11 19974.84 03-JUN-04:10 9.00 9.00
July 0.708067E+11 53843.22 31-JUL-04:45 7.33 5.33 0.313434E+11 19608.44 31-JUL-04:30 7.33 5.33
August 0.722980E+11 42795.91 20-AUG-03:12 9.00 8.27 0.317854E+11 19547.23 03-AUG-04:19 9.00 8.27
September 0.684910E+11 63689.13 20-SEP-22:54 7.00 6.47 0.304772E+11 19956.14 28-SEP-03:00 7.00 6.01
October 0.619906E+11 68543.31 04-OCT-21:34 6.33 5.82 0.299489E+11 19681.06 03-OCT-02:49 6.33 5.82
November 0.552967E+11 69572.47 09-NOV-05:35 9.33 9.14 0.279111E+11 19201.75 17-NOV-22:10 6.00 5.12
December 0.534388E+11 42068.87 12-DEC-11:57 6.00 4.59 0.277365E+11 18262.40 04-DEC-23:10 6.00 4.59
                     
Annual Sum or Average 0.740820E+12         0.352471E+12        
Minimum of Months 0.514100E+11 42068.87   6.00 3.06 0.258712E+11 18262.40   5.07 2.85
Maximum of Months 0.722980E+11 74169.69   9.33 9.14 0.317854E+11 20018.71   9.00 9.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 71596400.17 2877.49 19-JAN-16:02 7.67 7.22 93822383.52 56.69 31-JAN-23:40 7.00 5.55
February 0.117188E+09 3142.83 17-FEB-16:01 5.83 3.30 85362004.81 56.69 01-FEB-04:00 5.83 3.30
March 0.100045E+09 2875.44 23-MAR-18:02 7.67 5.83 94404885.06 56.69 28-MAR-21:10 5.83 4.52
April 0.800776E+09 3221.54 27-APR-15:02 18.17 10.78 94407922.73 56.69 28-APR-21:49 11.17 8.47
May 0.951317E+09 3244.67 21-MAY-15:02 18.83 10.43 97620906.51 56.70 22-MAY-21:19 14.67 12.52
June 0.136886E+10 3206.65 12-JUN-18:02 25.67 17.63 95203852.84 56.70 13-JUN-22:10 13.83 12.78
July 0.166419E+10 3157.19 05-JUL-18:02 17.83 11.00 98401350.19 56.69 10-JUL-21:19 17.00 13.49
August 0.160410E+10 3220.61 24-AUG-15:02 20.17 11.50 98584619.30 56.69 17-AUG-21:10 20.17 11.50
September 0.119981E+10 3115.83 29-SEP-15:01 15.67 9.39 94995357.13 56.69 14-SEP-22:49 15.67 9.39
October 0.343420E+09 3234.49 07-OCT-15:02 18.83 10.03 95745855.29 56.69 05-OCT-21:10 18.83 10.03
November 78823954.85 3039.76 03-NOV-15:01 8.83 5.57 91088374.78 56.69 06-NOV-01:30 8.00 6.97
December 44333090.27 684.35 05-DEC-19:04 6.17 5.65 92906314.97 56.69 04-DEC-23:49 6.17 5.65
                     
Annual Sum or Average 0.834446E+10         0.113254E+10        
Minimum of Months 44333090.27 684.35   5.83 3.30 85362004.81 56.69   5.83 3.30
Maximum of Months 0.166419E+10 3244.67   25.67 17.63 98584619.30 56.70   20.17 13.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 47321380.00 879.71 19-JAN-16:02 7.67 7.22 92972604.73 56.69 13-JAN-22:10 7.67 7.22
February 68479246.09 2478.44 17-FEB-16:01 5.83 3.30 84371075.39 56.69 01-FEB-04:00 5.83 3.30
March 81440793.83 2534.98 23-MAR-18:02 7.67 5.83 93954519.69 56.69 08-MAR-22:10 7.67 5.83
April 0.538479E+09 2862.84 27-APR-15:02 18.17 10.78 93602417.35 56.69 28-APR-21:10 11.83 8.82
May 0.767962E+09 2899.65 21-MAY-15:02 18.83 10.43 97153603.52 56.69 22-MAY-21:10 14.83 12.59
June 0.122867E+10 3011.93 13-JUN-18:02 23.37 16.34 94983543.99 56.69 26-JUN-21:40 14.00 14.00
July 0.146257E+10 2868.90 09-JUL-15:02 21.00 15.38 98177045.50 56.69 19-JUL-21:10 14.00 12.84
August 0.125836E+10 2893.35 17-AUG-15:02 21.83 16.72 98198988.18 56.69 16-AUG-22:10 21.83 16.72
September 0.759666E+09 2896.60 24-SEP-15:02 22.00 15.41 94198925.74 56.69 12-SEP-22:49 22.00 15.41
October 0.180843E+09 2853.93 07-OCT-15:02 18.83 10.03 94809561.17 56.69 01-OCT-01:30 18.83 10.03
November 57259955.77 1152.31 10-NOV-16:02 10.33 8.12 90314189.20 56.69 17-NOV-23:00 6.00 5.49
December 29981733.04 553.09 02-DEC-09:04 7.00 6.47 92443962.53 56.69 04-DEC-22:40 7.00 7.00
                     
Annual Sum or Average 0.648104E+10         0.112518E+10        
Minimum of Months 29981733.04 553.09   5.83 3.30 84371075.39 56.69   5.83 3.30
Maximum of Months 0.146257E+10 3011.93   23.37 16.72 98198988.18 56.69   22.00 16.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.170251E+09 359.62 21-JAN-11:30 6.00 5.05 0.00 0.00 01-JAN-00:10 6.00 5.05
February 0.166968E+09 305.27 04-FEB-14:40 9.00 6.43 0.00 0.00 01-FEB-00:10 9.00 6.43
March 0.139337E+09 85.25 25-MAR-11:50 11.92 8.82 0.00 0.00 01-MAR-00:10 11.92 8.82
April 0.415344E+09 656.37 30-APR-12:50 22.00 13.22 0.00 0.00 01-APR-00:10 22.00 13.22
May 0.366607E+09 497.05 23-MAY-13:20 18.33 14.52 0.00 0.00 01-MAY-00:10 18.33 14.52
June 0.415325E+09 527.19 13-JUN-13:30 24.55 17.26 0.00 0.00 01-JUN-00:10 24.55 17.26
July 0.497296E+09 610.39 22-JUL-13:30 28.00 16.51 0.00 0.00 01-JUL-00:10 28.00 16.51
August 0.580810E+09 646.27 20-AUG-13:00 23.00 14.82 0.00 0.00 01-AUG-00:10 23.00 14.82
September 0.633371E+09 789.61 27-SEP-13:30 21.50 13.33 0.00 0.00 01-SEP-00:10 21.50 13.33
October 0.343432E+09 712.21 07-OCT-13:20 17.00 9.43 0.00 0.00 01-OCT-00:10 17.00 9.43
November 0.168512E+09 303.23 11-NOV-13:21 9.00 7.22 0.00 0.00 01-NOV-00:10 9.00 7.22
December 76697082.24 100.77 18-DEC-14:30 8.00 5.66 0.00 0.00 01-DEC-00:10 8.00 5.66
                     
Annual Sum or Average 0.397395E+10         0.00        
Minimum of Months 76697082.24 85.25   6.00 5.05 0.00 0.00   6.00 5.05
Maximum of Months 0.633371E+09 789.61   28.00 17.26 0.00 0.00   28.00 17.26



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 78232542.00 550.11 29-JAN-09:02 11.00 8.46 94374819.49 56.69 13-JAN-22:10 11.00 8.46
February 70928705.54 434.63 11-FEB-19:03 4.83 4.34 85405040.80 56.69 02-FEB-22:19 4.83 4.34
March 0.141526E+09 635.92 25-MAR-08:62 8.17 6.09 95242203.26 56.69 24-MAR-21:10 8.17 6.09
April 0.301203E+09 772.36 29-APR-18:02 19.67 12.19 93055319.90 56.69 25-APR-21:19 19.67 12.19
May 0.389966E+09 770.73 21-MAY-18:02 19.83 13.22 96512687.19 56.69 22-MAY-22:30 14.00 12.24
June 0.526304E+09 833.86 13-JUN-18:02 23.37 16.34 93997814.97 56.69 26-JUN-21:30 14.00 14.00
July 0.574019E+09 824.12 22-JUL-08:61 24.00 16.56 97050629.96 56.69 07-JUL-21:10 24.00 16.56
August 0.508375E+09 806.22 14-AUG-15:02 25.17 16.00 96811233.34 56.69 17-AUG-21:10 14.83 13.13
September 0.381921E+09 773.49 13-SEP-15:02 23.00 16.22 93258474.33 56.69 12-SEP-21:49 23.00 16.22
October 0.202185E+09 676.78 15-OCT-08:61 6.33 6.25 95468385.51 56.69 07-OCT-23:19 6.33 6.25
November 0.102439E+09 587.48 23-NOV-09:01 8.00 7.45 91685336.95 56.69 01-NOV-22:10 8.00 7.45
December 59709799.93 381.24 06-DEC-19:04 2.83 2.38 94095197.90 56.69 04-DEC-22:40 2.83 2.38
                     
Annual Sum or Average 0.333681E+10         0.112696E+10        
Minimum of Months 59709799.93 381.24   2.83 2.38 85405040.80 56.69   2.83 2.38
Maximum of Months 0.574019E+09 833.86   25.17 16.56 97050629.96 56.69   24.00 16.56



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 85015957.92 1131.38 21-JAN-16:02 5.75 4.88 93791167.75 56.69 31-JAN-23:40 7.00 5.55
February 0.101866E+09 2594.28 20-FEB-09:01 3.33 2.81 85260990.91 56.69 01-FEB-04:00 3.33 2.81
March 96646352.78 1561.47 20-MAR-15:02 10.83 7.32 94469921.76 56.69 08-MAR-22:10 10.83 7.32
April 0.899174E+09 2900.94 14-APR-08:61 9.17 5.49 94902852.15 56.69 28-APR-21:10 11.83 8.82
May 0.950106E+09 2906.23 21-MAY-15:02 18.83 10.43 98083570.20 56.69 11-MAY-21:10 18.83 10.43
June 0.127890E+10 2990.55 12-JUN-18:02 25.67 17.63 95410363.42 56.69 13-JUN-21:19 14.00 12.84
July 0.157059E+10 2905.98 22-JUL-08:61 24.00 16.56 98697326.39 56.69 21-JUL-21:10 24.00 16.56
August 0.166677E+10 2962.46 24-AUG-15:02 20.17 11.50 98778326.82 56.69 16-AUG-22:19 20.17 11.50
September 0.132660E+10 2866.54 11-SEP-08:62 18.17 15.03 95358010.39 56.69 13-SEP-00:10 14.17 12.90
October 0.362659E+09 2906.32 07-OCT-15:02 18.83 10.03 95922819.59 56.69 06-OCT-21:19 18.83 10.03
November 87399005.45 2541.59 03-NOV-15:01 8.83 5.57 91065145.34 56.69 15-NOV-02:39 10.00 8.24
December 52682594.82 856.07 20-DEC-09:04 5.50 5.00 92977181.21 56.69 04-DEC-23:49 5.50 5.00
                     
Annual Sum or Average 0.847841E+10         0.113472E+10        
Minimum of Months 52682594.82 856.07   3.33 2.81 85260990.91 56.69   3.33 2.81
Maximum of Months 0.166677E+10 2990.55   25.67 17.63 98778326.82 56.69   24.00 16.56



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 47874317.03 907.79 23-JAN-19:04 8.00 6.97 92969200.80 56.69 13-JAN-22:10 8.00 6.97
February 59876664.02 1097.36 20-FEB-09:01 3.33 2.81 84252161.37 56.69 01-FEB-04:00 3.33 2.81
March 75948063.90 1034.03 21-MAR-18:03 7.67 4.81 94024267.73 56.69 19-MAR-02:09 7.67 4.81
April 0.610467E+09 2616.98 14-APR-08:61 9.17 5.49 94285443.83 56.69 27-APR-21:19 8.67 7.11
May 0.754940E+09 2627.19 22-MAY-15:02 23.83 15.94 97754891.17 56.69 22-MAY-23:10 13.50 11.85
June 0.112890E+10 2733.41 13-JUN-15:02 26.08 17.81 95279233.83 56.69 26-JUN-21:10 14.00 14.00
July 0.135380E+10 2666.07 21-JUL-15:02 27.17 15.87 98610544.14 56.69 21-JUL-21:10 17.00 13.87
August 0.129545E+10 2746.68 14-AUG-15:02 25.17 16.00 98627214.11 56.69 16-AUG-22:10 15.83 14.71
September 0.843837E+09 2686.25 13-SEP-15:02 23.00 16.22 94967535.17 56.69 12-SEP-22:30 23.00 16.22
October 0.188977E+09 2462.11 07-OCT-15:02 18.83 10.03 95051736.88 56.69 01-OCT-02:00 18.83 10.03
November 58103745.68 917.78 19-NOV-09:03 4.50 2.66 90287650.50 56.69 24-NOV-04:10 9.17 9.07
December 31613642.02 777.41 11-DEC-09:04 3.50 2.91 92509568.24 56.69 04-DEC-22:40 3.50 2.91
                     
Annual Sum or Average 0.644980E+10         0.112862E+10        
Minimum of Months 31613642.02 777.41   3.33 2.66 84252161.37 56.69   3.33 2.81
Maximum of Months 0.135380E+10 2746.68   27.17 17.81 98627214.11 56.69   23.00 16.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.236338E+10 2793.03 19-JAN-01:35 7.43 6.61 0.120372E+10 742.10 25-JAN-22:49 8.00 7.45
February 0.243358E+10 3114.71 17-FEB-14:08 6.00 3.06 0.109045E+10 741.43 27-FEB-22:19 4.67 4.67
March 0.281465E+10 2891.36 23-MAR-06:25 7.00 4.75 0.121508E+10 748.38 31-MAR-21:49 5.07 2.85
April 0.407528E+10 3518.88 29-APR-00:50 6.98 6.13 0.128736E+10 868.86 30-APR-23:10 11.87 8.94
May 0.435872E+10 3312.70 05-MAY-22:55 5.00 4.09 0.136596E+10 868.84 23-MAY-21:40 12.00 9.78
June 0.459592E+10 3090.04 06-JUN-03:35 8.33 6.67 0.137769E+10 902.92 13-JUN-21:40 14.00 12.84
July 0.491097E+10 3156.56 27-JUL-02:00 9.00 9.00 0.144735E+10 920.10 24-JUL-21:40 9.00 9.00
August 0.497885E+10 3116.69 20-AUG-03:12 9.00 8.27 0.146501E+10 904.85 21-AUG-21:40 14.67 12.52
September 0.460167E+10 3268.02 28-SEP-04:57 8.00 6.48 0.138008E+10 895.85 13-SEP-21:40 8.00 6.48
October 0.369793E+10 3339.09 01-OCT-00:47 7.43 6.28 0.127889E+10 851.64 02-OCT-21:49 8.00 6.98
November 0.258750E+10 2723.75 06-NOV-07:29 7.50 7.23 0.116911E+10 738.70 17-NOV-22:10 6.00 5.12
December 0.174024E+10 2744.01 12-DEC-11:57 6.00 4.59 0.119973E+10 718.60 20-DEC-22:19 4.67 4.35
                     
Annual Sum or Average 0.431587E+11         0.154804E+11        
Minimum of Months 0.174024E+10 2723.75   5.00 3.06 0.109045E+10 718.60   4.67 2.85
Maximum of Months 0.497885E+10 3518.88   9.00 9.00 0.146501E+10 920.10   14.67 12.84



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 55670722.88 3023.14 19-JAN-16:02 7.67 7.22 93347950.77 56.69 13-JAN-22:10 7.67 7.22
February 0.106373E+09 3292.36 17-FEB-16:01 5.83 3.30 84916849.97 56.69 01-FEB-05:30 5.83 3.30
March 88987464.37 3058.73 23-MAR-18:02 7.67 5.83 93955712.53 56.69 28-MAR-21:10 5.83 4.52
April 0.792014E+09 3391.01 27-APR-15:02 18.17 10.78 94250764.92 56.69 28-APR-01:10 6.57 4.88
May 0.910200E+09 3410.57 21-MAY-15:02 18.83 10.43 97410196.05 56.69 22-MAY-21:10 14.83 12.59
June 0.131448E+10 3447.29 13-JUN-18:02 23.37 16.34 95091983.48 56.70 26-JUN-21:10 14.00 14.00
July 0.163323E+10 3307.93 05-JUL-18:02 17.83 11.00 98302498.29 56.70 21-JUL-21:30 17.00 13.72
August 0.151990E+10 3374.70 24-AUG-15:02 20.17 11.50 98471137.58 56.70 11-AUG-03:09 20.17 11.50
September 0.107883E+10 3258.72 20-SEP-15:02 16.17 11.17 94806711.24 56.69 12-SEP-22:49 16.17 11.17
October 0.296696E+09 3392.09 07-OCT-15:02 18.83 10.03 95298764.12 56.69 03-OCT-22:19 18.83 10.03
November 64566570.94 3140.60 03-NOV-15:01 8.83 5.57 90591079.31 56.69 24-NOV-04:10 9.17 9.07
December 28563339.13 677.43 05-DEC-19:04 6.17 5.65 92569352.60 56.69 04-DEC-22:40 6.17 5.65
                     
Annual Sum or Average 0.788950E+10         0.112901E+10        
Minimum of Months 28563339.13 677.43   5.83 3.30 84916849.97 56.69   5.83 3.30
Maximum of Months 0.163323E+10 3447.29   23.37 16.34 98471137.58 56.70   20.17 14.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 29591821.13 891.50 21-JAN-16:03 5.75 4.88 92613258.64 56.69 27-JAN-22:19 5.00 4.51
February 48893245.78 1878.23 27-FEB-16:01 8.00 6.56 83937870.29 56.69 02-FEB-22:19 8.00 6.56
March 69371783.99 2657.31 23-MAR-18:02 7.67 5.83 93486373.12 56.69 18-MAR-03:30 7.67 5.83
April 0.523323E+09 2986.16 27-APR-15:02 18.17 10.78 93420510.79 56.69 28-APR-21:40 11.33 8.56
May 0.719942E+09 3022.48 21-MAY-15:02 18.83 10.43 96936128.26 56.69 22-MAY-21:10 14.83 12.59
June 0.115867E+10 3120.31 13-JUN-18:02 23.37 16.34 94897880.93 56.70 13-JUN-21:49 14.00 12.84
July 0.141112E+10 2981.41 22-JUL-18:02 29.83 16.84 98100990.46 56.69 21-JUL-21:40 29.83 16.84
August 0.114423E+10 2998.13 24-AUG-15:02 20.17 11.50 98104515.52 56.70 26-AUG-03:49 14.83 13.64
September 0.632156E+09 3003.72 24-SEP-15:02 22.00 15.41 93944527.95 56.69 12-SEP-21:30 22.00 15.41
October 0.148540E+09 2956.44 07-OCT-15:02 18.83 10.03 94268345.28 56.69 01-OCT-02:30 18.83 10.03
November 39883401.45 1303.72 03-NOV-15:02 8.83 5.57 89858958.67 56.69 24-NOV-04:10 9.17 9.07
December 12392207.67 823.18 05-DEC-19:04 6.17 5.65 92274644.37 56.69 05-DEC-00:30 6.17 5.65
                     
Annual Sum or Average 0.593811E+10         0.112184E+10        
Minimum of Months 12392207.67 823.18   5.75 4.88 83937870.29 56.69   5.00 4.51
Maximum of Months 0.141112E+10 3120.31   29.83 16.84 98104515.52 56.70   29.83 16.84



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.191572E+09 1983.28 21-JAN-16:02 5.75 4.88 95347211.70 56.69 13-JAN-22:10 5.75 4.88
February 0.220553E+09 2067.55 17-FEB-16:01 5.83 3.30 86580208.19 56.69 21-FEB-22:10 4.17 4.17
March 0.112822E+09 1952.76 20-MAR-15:02 10.83 7.32 95326743.73 56.69 28-MAR-21:10 5.83 4.52
April 0.702341E+09 2089.03 27-APR-15:02 18.17 10.78 94823899.30 56.69 28-APR-21:40 11.33 8.56
May 0.597823E+09 2077.93 21-MAY-15:02 18.83 10.43 97749152.15 56.69 11-MAY-21:10 18.83 10.43
June 0.753681E+09 2110.01 12-JUN-18:02 25.67 17.63 95091260.60 56.69 13-JUN-21:10 14.00 12.84
July 0.952685E+09 2123.00 22-JUL-08:61 24.00 16.56 98310842.77 56.69 17-JUL-22:49 24.00 16.56
August 0.111019E+10 2041.57 10-AUG-15:02 20.67 15.35 98471559.05 56.70 17-AUG-21:10 14.83 13.13
September 0.108980E+10 2147.90 12-SEP-15:02 21.83 15.52 95217866.85 56.69 12-SEP-21:19 15.33 13.92
October 0.466268E+09 2127.90 07-OCT-15:02 18.83 10.03 96653339.36 56.69 06-OCT-21:40 18.83 10.03
November 0.163996E+09 2061.89 03-NOV-15:01 8.83 5.57 92391397.42 56.69 06-NOV-00:30 8.00 6.97
December 84442883.09 1906.45 18-DEC-16:01 5.17 3.90 94208478.77 56.69 04-DEC-22:40 5.17 3.90
                     
Annual Sum or Average 0.644618E+10         0.114017E+10        
Minimum of Months 84442883.09 1906.45   5.17 3.30 86580208.19 56.69   4.17 3.90
Maximum of Months 0.111019E+10 2147.90   25.67 17.63 98471559.05 56.70   24.00 16.56



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.310320E+11 31343.26 27-JAN-23:35 5.40 4.81 0.189054E+11 12487.28 25-JAN-23:19 5.40 4.81
February 0.283882E+11 31266.83 14-FEB-23:39 5.67 3.58 0.171467E+11 11934.09 07-FEB-23:10 5.67 3.58
March 0.327498E+11 31551.97 24-MAR-22:39 5.60 4.71 0.191586E+11 12407.95 20-MAR-00:20 5.60 4.71
April 0.347779E+11 38067.31 29-APR-00:50 6.98 6.13 0.186358E+11 13254.80 04-APR-23:30 6.98 6.13
May 0.369059E+11 34469.23 05-MAY-22:55 5.00 4.09 0.193069E+11 12693.58 17-MAY-00:30 7.00 6.47
June 0.380934E+11 31655.18 08-JUN-01:09 7.00 5.07 0.187239E+11 13399.92 03-JUN-04:10 7.00 5.07
July 0.400821E+11 30298.90 15-JUL-04:45 8.07 7.52 0.192811E+11 12678.03 05-JUL-04:40 8.07 7.52
August 0.397015E+11 29636.30 05-AUG-04:10 9.00 8.43 0.193463E+11 12348.41 03-AUG-04:19 9.00 8.43
September 0.362518E+11 31601.80 08-SEP-03:44 7.17 6.56 0.186403E+11 12920.87 28-SEP-03:00 7.00 6.01
October 0.339314E+11 36710.46 05-OCT-22:52 6.00 4.60 0.191412E+11 13366.58 25-OCT-04:19 7.67 7.31
November 0.310024E+11 30865.44 10-NOV-21:18 3.67 3.67 0.183738E+11 12787.18 24-NOV-00:40 8.00 8.00
December 0.305324E+11 30336.03 20-DEC-21:48 5.33 4.84 0.188700E+11 11612.01 04-DEC-23:10 5.33 4.84
                     
Annual Sum or Average 0.413449E+12         0.225530E+12        
Minimum of Months 0.283882E+11 29636.30   3.67 3.58 0.171467E+11 11612.01   5.33 3.58
Maximum of Months 0.400821E+11 38067.31   9.00 8.43 0.193463E+11 13399.92   9.00 8.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.347527E+11 32967.77 27-JAN-23:35 5.40 4.81 0.190976E+11 12623.32 25-JAN-23:19 5.40 4.81
February 0.317757E+11 32884.03 14-FEB-23:39 5.67 3.58 0.173151E+11 12010.41 07-FEB-23:10 5.67 3.58
March 0.366965E+11 33204.75 24-MAR-22:39 5.60 4.71 0.193051E+11 12481.98 20-MAR-00:20 5.60 4.71
April 0.384108E+11 40910.38 29-APR-00:50 6.98 6.13 0.187113E+11 13452.81 04-APR-23:30 6.98 6.13
May 0.405952E+11 37755.41 05-MAY-22:55 5.00 4.09 0.193724E+11 12774.25 17-MAY-00:30 7.00 6.47
June 0.414858E+11 33293.08 08-JUN-01:09 7.00 5.07 0.187550E+11 13486.47 03-JUN-04:10 7.00 5.07
July 0.434640E+11 31859.37 31-JUL-04:45 7.33 5.33 0.193046E+11 12736.84 05-JUL-04:40 7.33 5.33
August 0.430203E+11 31087.71 05-AUG-04:10 9.00 8.43 0.193732E+11 12396.92 03-AUG-04:19 9.00 8.43
September 0.395777E+11 33192.19 08-SEP-03:44 7.17 6.56 0.186901E+11 12984.11 28-SEP-03:00 7.00 6.01
October 0.377249E+11 40878.38 22-OCT-21:19 6.00 6.00 0.192664E+11 13461.75 25-OCT-04:19 7.67 7.31
November 0.346702E+11 32424.60 10-NOV-21:18 3.67 3.67 0.185494E+11 12906.02 24-NOV-00:40 8.00 8.00
December 0.342268E+11 32045.47 19-DEC-21:48 5.17 4.67 0.190787E+11 11640.29 04-DEC-23:10 5.17 4.67
                     
Annual Sum or Average 0.456401E+12         0.226819E+12        
Minimum of Months 0.317757E+11 31087.71   3.67 3.58 0.173151E+11 11640.29   5.17 3.58
Maximum of Months 0.434640E+11 40910.38   9.00 8.43 0.193732E+11 13486.47   9.00 8.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.488336E+11 35751.33 01-JAN-11:37 3.33 2.75 0.188224E+11 11377.23 18-JAN-17:00 8.00 6.97
February 0.445170E+11 36684.09 25-FEB-11:37 5.77 4.48 0.170045E+11 11413.69 03-FEB-18:40 5.77 4.48
March 0.499760E+11 36236.90 02-MAR-18:03 5.67 3.93 0.188462E+11 11511.67 04-MAR-18:40 5.33 3.40
April 0.518436E+11 35685.57 07-APR-06:41 6.67 3.49 0.182411E+11 11364.35 01-APR-17:30 6.67 3.49
May 0.538430E+11 35385.19 02-MAY-06:32 5.67 4.30 0.188580E+11 11351.48 13-MAY-17:10 11.42 9.41
June 0.536621E+11 34079.41 11-JUN-22:40 9.00 9.00 0.182396E+11 11319.66 10-JUN-17:19 9.00 9.00
July 0.560593E+11 32233.43 31-JUL-05:44 9.50 6.74 0.188448E+11 11319.68 22-JUL-17:19 9.50 6.74
August 0.561237E+11 31495.12 24-AUG-05:17 8.67 7.29 0.188515E+11 11319.69 19-AUG-17:19 8.67 7.29
September 0.530713E+11 34400.47 30-SEP-19:10 7.00 5.55 0.182326E+11 11329.95 30-SEP-17:00 7.00 5.55
October 0.513508E+11 38778.44 22-OCT-21:19 6.00 6.00 0.188477E+11 11495.43 28-OCT-17:49 8.83 8.47
November 0.477432E+11 36655.52 21-NOV-16:06 7.83 6.90 0.182299E+11 11433.56 18-NOV-18:40 7.83 6.90
December 0.480800E+11 37372.12 24-DEC-19:06 6.00 5.04 0.188192E+11 11503.81 16-DEC-18:40 6.00 5.04
                     
Annual Sum or Average 0.615104E+12         0.221838E+12        
Minimum of Months 0.445170E+11 31495.12   3.33 2.75 0.170045E+11 11319.66   5.33 3.40
Maximum of Months 0.561237E+11 38778.44   9.50 9.00 0.188580E+11 11511.67   11.42 9.41



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.408163E+10 5863.41 21-JAN-14:40 7.67 6.34 0.127156E+10 781.96 25-JAN-23:19 8.00 7.40
February 0.438231E+10 6793.11 17-FEB-14:08 6.00 3.06 0.115137E+10 782.04 27-FEB-22:19 4.67 4.67
March 0.554141E+10 6074.22 23-MAR-06:25 7.00 4.75 0.128203E+10 784.78 31-MAR-21:49 5.07 2.85
April 0.830684E+10 7258.17 29-APR-00:50 6.98 6.13 0.133112E+10 910.96 30-APR-23:10 11.87 8.94
May 0.892356E+10 6651.92 05-MAY-22:55 5.00 4.09 0.140258E+10 925.91 23-MAY-21:30 12.00 9.78
June 0.957669E+10 6243.70 01-JUN-01:22 8.15 6.63 0.142930E+10 968.58 13-JUN-21:30 14.00 12.84
July 0.103058E+11 6316.07 27-JUL-02:00 9.00 9.00 0.150831E+10 968.61 21-JUL-21:30 9.00 9.00
August 0.103292E+11 6275.05 20-AUG-03:12 9.00 8.27 0.151442E+10 949.36 14-AUG-21:30 9.00 8.27
September 0.932221E+10 6484.89 28-SEP-04:57 8.00 6.48 0.140262E+10 927.01 12-SEP-21:40 8.00 6.48
October 0.725799E+10 6625.61 01-OCT-00:47 7.43 6.28 0.131422E+10 850.87 02-OCT-21:49 8.00 6.98
November 0.498087E+10 5402.27 15-NOV-17:06 7.83 6.89 0.123283E+10 776.62 17-NOV-22:10 6.00 5.12
December 0.308250E+10 5439.93 18-DEC-12:07 8.00 5.60 0.126940E+10 752.66 04-DEC-22:19 8.00 5.60
                     
Annual Sum or Average 0.860910E+11         0.161098E+11        
Minimum of Months 0.308250E+10 5402.27   5.00 3.06 0.115137E+10 752.66   4.67 2.85
Maximum of Months 0.103292E+11 7258.17   9.00 9.00 0.151442E+10 968.61   14.00 12.84



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 565896.78 744.66 07-JAN-13:35 7.07
February 356429.10 869.44 04-FEB-16:00 7.00
March 3640996.26 1153.88 11-MAR-09:15 6.00
April 4349707.57 1559.67 27-APR-24:00 6.90
May 7440592.90 1525.66 01-MAY-02:29 7.15
June 2069176.39 1158.05 08-JUN-00:03 7.00
July 284382.25 556.13 31-JUL-04:42 7.33
August 0.00 0.00 01-AUG-00:05 11.43
September 237013.28 709.68 28-SEP-05:16 7.67
October 421916.04 1107.25 22-OCT-21:28 6.00
November 660419.75 1447.40 08-NOV-08:00 7.00
December 4938.13 82.30 17-DEC-10:49 6.33
         
Annual Sum or Average 20031468.46      
Minimum of Months 0.00 0.00   6.00
Maximum of Months 7440592.90 1559.67   11.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.109408E+09 1993.28 28-JAN-08:05 7.02
February 45373402.33 782.79 26-FEB-22:13 6.00
March 34634948.03 917.18 17-MAR-07:03 6.00
April 17136764.68 856.18 27-APR-24:00 6.90
May 29942511.84 922.51 10-MAY-23:46 7.00
June 9328828.46 824.59 08-JUN-00:03 7.00
July 4751841.05 823.82 15-JUL-04:55 8.00
August 1510790.29 530.03 24-AUG-05:16 8.67
September 10942122.67 872.55 28-SEP-05:16 7.67
October 29924050.77 1111.55 01-OCT-07:18 7.67
November 58126764.57 994.25 08-NOV-08:00 7.00
December 0.249617E+09 846.05 06-DEC-16:03 6.67
         
Annual Sum or Average 0.600698E+09      
Minimum of Months 1510790.29 530.03   6.00
Maximum of Months 0.249617E+09 1993.28   8.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1618302.57 308.92 28-JAN-08:07 7.02
February 1982190.48 251.72 12-FEB-10:45 5.67
March 3330344.16 288.30 04-MAR-11:30 6.50
April 1071100.71 235.50 10-APR-14:05 7.00
May 849537.00 189.42 18-MAY-05:39 7.33
June 213634.33 134.67 08-JUN-00:03 7.00
July 59663.77 80.31 31-JUL-04:42 7.33
August 0.00 0.00 01-AUG-00:05 11.43
September 348394.90 166.81 04-SEP-05:06 7.83
October 2411595.37 260.53 28-OCT-07:36 6.67
November 4024444.03 343.54 08-NOV-08:00 7.00
December 3477494.44 324.42 17-DEC-10:49 6.33
         
Annual Sum or Average 19386701.75      
Minimum of Months 0.00 0.00   5.67
Maximum of Months 4024444.03 343.54   11.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 4964533.56 366.84 23-JAN-07:58 7.00
February 4174211.49 755.33 17-FEB-14:09 6.00
March 6381770.03 365.71 11-MAR-09:15 6.00
April 3737770.94 299.94 11-APR-06:29 6.00
May 4922753.56 283.73 18-MAY-05:39 7.33
June 1221777.49 250.29 08-JUN-00:03 7.00
July 425349.13 191.75 31-JUL-04:42 7.33
August 28102.81 34.02 23-AUG-03:52 8.00
September 1446598.34 215.81 21-SEP-02:30 7.50
October 7476255.24 332.29 22-OCT-21:28 6.00
November 10123639.85 393.76 08-NOV-08:00 7.00
December 5662536.26 350.11 17-DEC-10:49 6.33
         
Annual Sum or Average 50565298.72      
Minimum of Months 28102.81 34.02   6.00
Maximum of Months 10123639.85 755.33   8.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 27288030.76 466.60 28-JAN-08:05 7.02
February 2670376.66 214.05 17-FEB-14:09 6.00
March 3859268.78 190.29 11-MAR-09:15 6.00
April 2553203.99 166.62 11-APR-06:29 6.00
May 3330978.56 152.13 18-MAY-05:39 7.33
June 824915.72 139.93 08-JUN-00:03 7.00
July 326681.45 104.49 31-JUL-04:42 7.33
August 32969.46 30.47 24-AUG-05:16 8.67
September 966439.99 114.63 21-SEP-02:30 7.50
October 4806994.36 188.17 22-OCT-21:28 6.00
November 8430057.06 211.92 08-NOV-08:00 7.00
December 24462690.64 306.94 13-DEC-10:53 7.00
         
Annual Sum or Average 79552607.42      
Minimum of Months 32969.46 30.47   6.00
Maximum of Months 27288030.76 466.60   8.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 22289.76 222.90 19-JAN-01:10 7.63
February 214608.13 1854.21 01-FEB-04:50 7.83
March 33439.50 557.32 18-MAR-03:20 8.60
April 516870.48 1112.13 24-APR-01:47 7.32
May 3425853.62 3126.43 01-MAY-02:29 7.15
June 1391967.25 1728.08 06-JUN-03:32 8.33
July 1358251.08 2800.03 15-JUL-04:55 8.00
August 211956.70 1683.66 23-AUG-03:52 8.00
September 1683931.65 1783.14 22-SEP-03:25 8.50
October 1578982.95 1995.64 21-OCT-03:28 7.50
November 841283.76 1851.07 25-NOV-05:03 7.83
December 0.00 0.00 01-DEC-00:03 4.00
         
Annual Sum or Average 11279434.88      
Minimum of Months 0.00 0.00   4.00
Maximum of Months 3425853.62 3126.43   8.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 15328435.67 4481.20 28-JAN-08:05 7.02
February 12824071.75 2577.77 22-FEB-07:26 6.50
March 29087827.36 2843.35 20-MAR-06:46 6.67
April 16376243.78 2933.73 11-APR-06:29 6.00
May 16299660.91 2710.40 04-MAY-06:10 7.33
June 1229455.03 875.69 08-JUN-00:03 7.00
July 1156059.10 972.35 09-JUL-04:24 9.00
August 47242.60 371.37 24-AUG-06:08 8.83
September 3548310.03 2012.54 04-SEP-05:06 7.83
October 28371499.34 3127.50 19-OCT-06:25 6.00
November 37234162.13 3664.64 08-NOV-08:00 7.00
December 22960679.47 2899.30 05-DEC-07:55 6.00
         
Annual Sum or Average 0.184464E+09      
Minimum of Months 47242.60 371.37   6.00
Maximum of Months 37234162.13 4481.20   9.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 17675379.32 5263.90 28-JAN-08:07 7.02
February 19774613.95 4690.10 01-FEB-11:15 7.33
March 42208858.51 5342.83 27-MAR-13:31 8.00
April 11631811.25 4280.54 10-APR-14:05 7.00
May 3372339.58 2545.17 04-MAY-06:10 7.33
June 238429.43 1589.53 08-JUN-00:03 7.00
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:05 11.43
September 898083.15 2020.33 04-SEP-05:06 7.83
October 17208302.44 4434.23 19-OCT-06:25 6.00
November 35925408.07 6412.69 08-NOV-08:00 7.00
December 41407041.95 4953.47 17-DEC-10:49 6.33
         
Annual Sum or Average 0.190340E+09      
Minimum of Months 0.00 0.00   6.00
Maximum of Months 42208858.51 6412.69   11.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.839858E+09 2128.32 10-JAN-09:01 -3.8
February 0.613548E+09 2107.46 01-FEB-16:01 7.00
March 0.578483E+09 2093.24 17-MAR-08:61 6.17
April 90906009.92 1960.01 10-APR-15:02 7.17
May 53417122.92 1984.22 17-MAY-08:61 8.17
June 2615497.55 693.38 18-JUN-08:03 13.17
July 2894738.91 737.74 07-JUL-15:04 15.83
August 1312758.05 785.94 26-AUG-15:04 17.00
September 9213151.23 667.70 03-SEP-08:03 14.00
October 0.267279E+09 2081.98 19-OCT-08:61 7.33
November 0.654371E+09 2125.06 30-NOV-19:01 4.83
December 0.114602E+10 2116.38 13-DEC-19:11 4.67
         
Annual Sum or Average 0.425992E+10      
Minimum of Months 1312758.05 667.70   -3.8
Maximum of Months 0.114602E+10 2128.32   17.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.106585E+10 2109.41 10-JAN-09:01 -3.8
February 0.797680E+09 2073.45 06-FEB-19:01 4.83
March 0.667076E+09 2054.86 17-MAR-08:61 6.17
April 0.137338E+09 1971.54 09-APR-08:61 8.00
May 64095252.75 1949.93 17-MAY-08:61 8.17
June 2539982.11 590.17 09-JUN-08:03 13.33
July 3071503.84 708.63 07-JUL-15:04 15.83
August 1367268.37 690.39 29-AUG-08:03 13.50
September 18209070.78 1060.26 07-SEP-08:62 12.33
October 0.368323E+09 2042.28 19-OCT-08:61 7.33
November 0.816115E+09 2083.21 30-NOV-19:01 4.83
December 0.129749E+10 2083.44 27-DEC-09:01 -0.7
         
Annual Sum or Average 0.523915E+10      
Minimum of Months 1367268.37 590.17   -3.8
Maximum of Months 0.129749E+10 2109.41   15.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 6983976.46 89.99 31-JAN-05:00 1.00
February 6361538.62 108.92 02-FEB-04:50 4.00
March 5478671.34 75.16 16-MAR-04:00 1.30
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:05 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:05 11.43
September 0.00 0.00 01-SEP-00:05 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 2637009.18 56.38 30-NOV-05:00 3.00
December 61247584.24 159.71 17-DEC-04:40 1.00
         
Annual Sum or Average 82708779.85      
Minimum of Months 0.00 0.00   1.00
Maximum of Months 61247584.24 159.71   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 99242346.22 594.40 11-JAN-16:01 -2.2
February 62813537.23 565.38 17-FEB-16:01 5.83
March 15318045.79 562.19 15-MAR-15:01 3.00
April 737019.79 533.32 10-APR-15:02 7.17
May 498902.85 218.45 02-MAY-08:03 9.00
June 138239.81 144.65 17-JUN-15:06 15.83
July 162847.05 180.97 13-JUL-08:06 14.50
August 239141.06 227.75 04-AUG-08:05 14.27
September 584900.59 302.73 29-SEP-15:03 15.67
October 1923870.41 546.74 27-OCT-15:01 9.00
November 41993545.14 573.02 29-NOV-16:01 3.83
December 0.123405E+09 577.68 30-DEC-16:01 1.83
         
Annual Sum or Average 0.347057E+09      
Minimum of Months 138239.81 144.65   -2.2
Maximum of Months 0.123405E+09 594.40   15.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.845102E+09 2090.44 10-JAN-19:01 -5.0
February 0.646335E+09 2068.46 01-FEB-16:01 7.00
March 0.585265E+09 2051.98 17-MAR-08:61 6.17
April 82877686.64 1977.36 10-APR-18:01 7.83
May 53595200.93 1554.47 04-MAY-08:62 9.00
June 4858369.15 533.92 29-JUN-08:05 12.83
July 1525166.36 806.79 07-JUL-15:04 15.83
August 526568.49 473.16 11-AUG-15:05 17.00
September 5327482.80 585.73 02-SEP-18:04 13.83
October 0.264926E+09 2040.82 19-OCT-08:61 7.33
November 0.657402E+09 2083.17 30-NOV-19:01 4.83
December 0.110429E+10 2077.43 27-DEC-09:01 -0.7
         
Annual Sum or Average 0.425203E+10      
Minimum of Months 526568.49 473.16   -5.0
Maximum of Months 0.110429E+10 2090.44   17.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.105923E+10 2070.53 11-JAN-19:01 -4.8
February 0.843621E+09 2034.78 06-FEB-19:01 4.83
March 0.672269E+09 2013.95 17-MAR-08:61 6.17
April 0.124016E+09 1943.80 10-APR-18:01 7.83
May 67333832.62 1691.24 04-MAY-08:62 9.00
June 5538237.15 481.85 17-JUN-08:05 12.00
July 1571891.27 717.11 07-JUL-15:04 15.83
August 742579.01 444.55 11-AUG-15:05 17.00
September 12076147.89 822.77 29-SEP-15:04 15.67
October 0.361876E+09 2001.53 19-OCT-08:61 7.33
November 0.811887E+09 2041.79 30-NOV-19:01 4.83
December 0.124315E+10 2045.11 27-DEC-09:01 -0.7
         
Annual Sum or Average 0.520331E+10      
Minimum of Months 742579.01 444.55   -4.8
Maximum of Months 0.124315E+10 2070.53   17.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 12975091.75 1729.99 28-JAN-08:05 7.02
February 8439511.57 668.75 26-FEB-22:13 6.00
March 13809103.77 720.53 11-MAR-09:15 6.00
April 7851097.75 634.46 11-APR-06:29 6.00
May 8651770.40 547.46 18-MAY-05:39 7.33
June 2101430.27 465.38 08-JUN-00:03 7.00
July 897128.31 328.03 31-JUL-04:42 7.33
August 22496.54 57.41 24-AUG-05:16 8.67
September 2653984.76 393.90 20-SEP-06:05 6.17
October 18375731.17 732.68 22-OCT-21:28 6.00
November 24840624.91 831.78 08-NOV-08:00 7.00
December 26392135.25 1469.72 12-DEC-12:00 6.00
         
Annual Sum or Average 0.127010E+09      
Minimum of Months 22496.54 57.41   6.00
Maximum of Months 26392135.25 1729.99   8.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.128137E+10 2557.47 10-JAN-09:01 -3.8
February 0.949623E+09 2537.30 06-FEB-19:01 4.83
March 0.915395E+09 2523.86 17-MAR-08:61 6.17
April 0.216341E+09 2413.63 09-APR-08:61 8.00
May 0.152276E+09 2401.94 17-MAY-08:61 8.17
June 14865836.49 866.18 24-JUN-08:03 14.00
July 18386370.17 796.93 15-JUL-08:03 13.17
August 3048733.99 798.51 26-AUG-15:04 17.00
September 50168786.50 1598.90 07-SEP-08:62 12.33
October 0.514433E+09 2515.64 19-OCT-08:61 7.33
November 0.102266E+10 2548.61 30-NOV-19:01 4.83
December 0.165323E+10 2545.62 13-DEC-19:11 4.67
         
Annual Sum or Average 0.679181E+10      
Minimum of Months 3048733.99 796.93   -3.8
Maximum of Months 0.165323E+10 2557.47   17.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.156173E+10 2529.81 10-JAN-09:01 -3.8
February 0.118011E+10 2478.76 06-FEB-19:01 4.83
March 0.102635E+10 2467.96 17-MAR-08:61 6.17
April 0.301601E+09 2384.56 09-APR-08:61 8.00
May 0.181942E+09 2369.07 06-MAY-08:61 8.17
June 17605054.70 639.21 18-JUN-08:03 13.17
July 19681409.77 779.50 15-JUL-08:03 13.17
August 5912209.70 725.57 13-AUG-08:03 14.17
September 93918082.81 2276.28 20-SEP-08:62 11.50
October 0.672889E+09 2468.77 15-OCT-08:61 6.33
November 0.122319E+10 2490.22 30-NOV-19:01 4.83
December 0.183988E+10 2495.80 27-DEC-09:01 -0.7
         
Annual Sum or Average 0.812482E+10      
Minimum of Months 5912209.70 639.21   -3.8
Maximum of Months 0.183988E+10 2529.81   14.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.316218E+09 1366.05 04-JAN-09:01 1.17
February 0.224058E+09 1358.04 01-FEB-16:01 7.00
March 0.242886E+09 1354.52 17-MAR-08:61 6.17
April 30033360.05 1266.25 10-APR-15:02 7.17
May 28225705.28 1246.43 17-MAY-08:61 8.17
June 3148902.59 486.61 03-JUN-15:04 16.17
July 1554056.84 528.10 28-JUL-18:04 13.83
August 846269.10 501.32 03-AUG-08:03 14.17
September 2288455.87 451.44 09-SEP-08:03 13.33
October 82488392.00 1349.16 19-OCT-08:61 7.33
November 0.227265E+09 1377.40 30-NOV-19:01 4.83
December 0.509732E+09 1379.26 16-DEC-16:11 7.67
         
Annual Sum or Average 0.166874E+10      
Minimum of Months 846269.10 451.44   1.17
Maximum of Months 0.509732E+09 1379.26   16.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 1.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:05 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:05 11.43
September 0.00 0.00 01-SEP-00:05 12.43
October 9364.60 87.12 22-OCT-21:28 6.00
November 108960.92 1006.74 08-NOV-08:00 7.00
December 0.00 0.00 01-DEC-00:03 4.00
         
Annual Sum or Average 118325.51      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 108960.92 1006.74   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 1.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:05 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:05 11.43
September 0.00 0.00 01-SEP-00:05 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 49796.17 518.01 08-NOV-08:00 7.00
December 0.00 0.00 01-DEC-00:03 4.00
         
Annual Sum or Average 49796.17      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 49796.17 518.01   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 1.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:05 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:05 11.43
September 0.00 0.00 01-SEP-00:05 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:05 6.57
December 0.00 0.00 01-DEC-00:03 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 30367905.46 4727.57 28-JAN-08:05 7.02
February 16884567.20 1397.63 26-FEB-22:13 6.00
March 26565326.76 1527.74 23-MAR-06:26 7.00
April 21830220.25 1413.84 11-APR-06:29 6.00
May 30272137.34 1366.92 18-MAY-05:39 7.33
June 8157245.04 1213.14 08-JUN-00:03 7.00
July 4089903.19 944.08 31-JUL-04:42 7.33
August 800378.77 501.01 24-AUG-05:16 8.67
September 12130626.78 1191.71 04-SEP-05:06 7.83
October 44048792.77 1621.96 22-OCT-21:28 6.00
November 48752595.27 1742.86 08-NOV-08:00 7.00
December 33777646.68 1699.48 13-DEC-10:53 7.00
         
Annual Sum or Average 0.277677E+09      
Minimum of Months 800378.77 501.01   6.00
Maximum of Months 48752595.27 4727.57   8.67



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.147273E+11 14185.34 02-JAN-20:10 0.127587E+11 10113.80 02-JAN-20:10
February 0.132974E+11 14185.34 01-FEB-20:10 0.115208E+11 10113.80 01-FEB-20:10
March 0.147727E+11 14185.34 01-MAR-20:10 0.127855E+11 10113.80 01-MAR-20:10
April 0.142280E+11 14185.34 03-APR-19:10 0.123314E+11 10113.80 03-APR-19:10
May 0.147528E+11 14185.34 01-MAY-19:10 0.127741E+11 10113.80 01-MAY-19:10
June 0.142932E+11 14185.34 01-JUN-19:10 0.123716E+11 10113.80 01-JUN-19:10
July 0.146876E+11 14185.34 03-JUL-19:10 0.127338E+11 10113.80 03-JUL-19:10
August 0.147784E+11 14185.34 01-AUG-19:10 0.127894E+11 10113.80 01-AUG-19:10
September 0.142337E+11 14185.34 01-SEP-19:10 0.123352E+11 10113.80 01-SEP-19:10
October 0.147216E+11 14185.34 02-OCT-19:10 0.127549E+11 10113.80 02-OCT-19:10
November 0.142819E+11 14185.34 01-NOV-19:10 0.123659E+11 10113.80 01-NOV-19:10
December 0.146876E+11 14185.34 01-DEC-20:10 0.127338E+11 10113.80 01-DEC-20:10
             
Annual Sum or Average 0.173462E+12     0.150255E+12    
Minimum of Months 0.132974E+11 14185.34   0.115208E+11 10113.80  
Maximum of Months 0.147784E+11 14185.34   0.127894E+11 10113.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.731324E+09 704.41 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.660319E+09 704.41 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.733578E+09 704.41 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.706528E+09 704.41 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.732592E+09 704.41 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.709769E+09 704.41 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.729351E+09 704.41 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.733860E+09 704.41 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.706810E+09 704.41 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.731042E+09 704.41 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.709205E+09 704.41 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.729351E+09 704.41 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.861373E+10     0.101856E+11    
Minimum of Months 0.660319E+09 704.41   0.780982E+09 685.60  
Maximum of Months 0.733860E+09 704.41   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.846876E+09 815.72 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.764651E+09 815.72 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.849486E+09 815.72 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.818162E+09 815.72 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.848344E+09 815.72 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.821915E+09 815.72 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.844592E+09 815.72 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.849812E+09 815.72 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.818489E+09 815.72 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.846549E+09 815.72 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.821262E+09 815.72 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.844592E+09 815.72 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.997473E+10     0.117950E+11    
Minimum of Months 0.764651E+09 815.72   0.904380E+09 793.93  
Maximum of Months 0.849812E+09 815.72   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.141236E+10 1360.40 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.127524E+10 1360.40 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.141672E+10 1360.40 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.136448E+10 1360.40 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.141481E+10 1360.40 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.137074E+10 1360.40 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.140855E+10 1360.40 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.141726E+10 1360.40 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.136502E+10 1360.40 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.141182E+10 1360.40 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.136965E+10 1360.40 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.140855E+10 1360.40 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.166352E+11     0.124712E+11    
Minimum of Months 0.127524E+10 1360.40   0.956227E+09 839.45  
Maximum of Months 0.141726E+10 1360.40   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.236418E+09 227.72 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.213464E+09 227.72 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.237147E+09 227.72 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.228402E+09 227.72 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.236828E+09 227.72 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.229450E+09 227.72 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.235780E+09 227.72 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.237238E+09 227.72 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.228493E+09 227.72 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.236327E+09 227.72 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.229268E+09 227.72 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.235780E+09 227.72 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.278459E+10     0.359760E+10    
Minimum of Months 0.213464E+09 227.72   0.275845E+09 242.16  
Maximum of Months 0.237238E+09 227.72   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.370859E+09 357.21 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.334852E+09 357.21 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.372002E+09 357.21 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.358285E+09 357.21 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.371502E+09 357.21 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.359929E+09 357.21 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.369859E+09 357.21 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.372145E+09 357.21 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.358428E+09 357.21 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.370717E+09 357.21 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.359643E+09 357.21 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.369859E+09 357.21 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.436808E+10     0.679355E+11    
Minimum of Months 0.334852E+09 357.21   0.520895E+10 4572.80  
Maximum of Months 0.372145E+09 357.21   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.164303E+10 1761.91 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.144635E+10 1761.91 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.155405E+10 1761.91 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.142686E+10 1761.91 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.140301E+10 1761.91 01-MAY-19:19 0.121917E+10 965.27 01-MAY-19:10
June 0.131931E+10 1761.91 01-JUN-19:30 0.118076E+10 965.27 01-JUN-19:10
July 0.137171E+10 1761.91 17-JUL-19:30 0.121533E+10 965.27 03-JUL-19:10
August 0.145249E+10 1761.91 01-AUG-19:30 0.122063E+10 965.27 01-AUG-19:10
September 0.147102E+10 1761.91 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.159722E+10 1761.91 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.158401E+10 1761.91 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.166292E+10 1761.91 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.179320E+11     0.143405E+11    
Minimum of Months 0.131931E+10 1761.91   0.109956E+10 965.27  
Maximum of Months 0.166292E+10 1761.91   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104691E+11 10265.18 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.941375E+10 10265.18 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.104095E+11 10265.18 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.994922E+10 10265.18 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.102405E+11 10265.18 01-MAY-19:19 0.126672E+11 10029.21 01-MAY-19:10
June 0.988088E+10 10265.18 01-JUN-19:19 0.122682E+11 10029.21 01-JUN-19:10
July 0.101688E+11 10265.18 17-JUL-19:19 0.126273E+11 10029.21 03-JUL-19:10
August 0.103060E+11 10265.18 01-AUG-19:30 0.126824E+11 10029.21 01-AUG-19:10
September 0.999882E+10 10265.18 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.104188E+11 10265.18 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.101444E+11 10265.18 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.104681E+11 10265.18 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.121868E+12     0.148998E+12    
Minimum of Months 0.941375E+10 10265.18   0.114244E+11 10029.21  
Maximum of Months 0.104691E+11 10265.18   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85091918.49 76.99 01-JAN-19:10 0.255708E+09 232.19 01-JAN-08:09
February 76846309.13 76.99 01-FEB-20:10 0.230956E+09 232.19 01-FEB-07:10
March 84415649.14 76.99 01-MAR-20:10 0.255355E+09 232.19 01-MAR-07:10
April 82445007.08 76.99 01-APR-18:10 0.247516E+09 232.19 01-APR-07:10
May 84753783.81 76.99 01-MAY-19:10 0.255532E+09 232.19 01-MAY-06:10
June 81790910.76 76.99 01-JUN-19:10 0.247163E+09 232.19 01-JUN-06:10
July 85418966.65 76.99 01-JUL-18:10 0.255885E+09 232.19 01-JUL-07:10
August 84415649.14 76.99 01-AUG-19:10 0.255355E+09 232.19 01-AUG-06:10
September 82467180.11 76.99 01-SEP-19:10 0.247516E+09 232.19 01-SEP-06:10
October 85080831.98 76.99 01-OCT-18:10 0.255708E+09 232.19 01-OCT-07:10
November 82117958.92 76.99 01-NOV-19:10 0.247340E+09 232.19 01-NOV-06:10
December 85430053.17 76.99 01-DEC-20:10 0.255885E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.100027E+10     0.300992E+10    
Minimum of Months 76846309.13 76.99   0.230956E+09 232.19  
Maximum of Months 85430053.17 76.99   0.255885E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85115186.72 77.01 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 76867322.62 77.01 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 84438732.44 77.01 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 82467551.52 77.01 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 84776959.58 77.01 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 81813276.33 77.01 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 85442324.32 77.01 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 84438732.44 77.01 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 82489730.61 77.01 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 85104097.18 77.01 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 82140413.93 77.01 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 85453413.86 77.01 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.100055E+10     0.301074E+10    
Minimum of Months 76867322.62 77.01   0.231020E+09 232.26  
Maximum of Months 85453413.86 77.01   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.232638E+10 2240.78 02-JAN-20:10 0.00 0.00
February 0.210051E+10 2240.78 01-FEB-20:10 0.00 0.00
March 0.233355E+10 2240.78 01-MAR-20:10 0.00 0.00
April 0.224750E+10 2240.78 03-APR-19:10 0.00 0.00
May 0.233041E+10 2240.78 01-MAY-19:10 0.00 0.00
June 0.225781E+10 2240.78 01-JUN-19:10 0.00 0.00
July 0.232011E+10 2240.78 03-JUL-19:10 0.00 0.00
August 0.233445E+10 2240.78 01-AUG-19:10 0.00 0.00
September 0.224840E+10 2240.78 01-SEP-19:10 0.00 0.00
October 0.232548E+10 2240.78 02-OCT-19:10 0.00 0.00
November 0.225602E+10 2240.78 01-NOV-19:10 0.00 0.00
December 0.232011E+10 2240.78 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.274007E+11     0.00 0.00
Minimum of Months 0.210051E+10 2240.78   0.00 0.00
Maximum of Months 0.233445E+10 2240.78   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85115186.72 77.01 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 76867322.62 77.01 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 84438732.44 77.01 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 82467551.52 77.01 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 84776959.58 77.01 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 81813276.33 77.01 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 85442324.32 77.01 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 84438732.44 77.01 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 82489730.61 77.01 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 85104097.18 77.01 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 82140413.93 77.01 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 85453413.86 77.01 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.100055E+10     0.301074E+10    
Minimum of Months 76867322.62 77.01   0.231020E+09 232.26  
Maximum of Months 85453413.86 77.01   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.306267E+10 3094.06 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.272729E+10 3094.06 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.297768E+10 3094.06 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.279769E+10 3094.06 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.282496E+10 3094.06 01-MAY-19:19 0.149358E+11 6747.90 01-MAY-06:10
June 0.269934E+10 3094.06 01-JUN-19:30 0.144540E+11 6747.90 01-JUN-06:10
July 0.278710E+10 3094.06 17-JUL-19:30 0.149358E+11 6747.90 01-JUL-06:10
August 0.287489E+10 3094.06 01-AUG-19:40 0.149358E+11 6747.90 01-AUG-06:10
September 0.284436E+10 3094.06 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.301413E+10 3094.06 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.295977E+10 3094.06 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.307587E+10 3094.06 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.346457E+11     0.175857E+12    
Minimum of Months 0.269934E+10 3094.06   0.134904E+11 6747.90  
Maximum of Months 0.307587E+10 3094.06   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.306267E+10 3094.06 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.272729E+10 3094.06 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.297768E+10 3094.06 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.279769E+10 3094.06 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.282496E+10 3094.06 01-MAY-19:19 0.149358E+11 6747.90 01-MAY-06:10
June 0.269934E+10 3094.06 01-JUN-19:30 0.144540E+11 6747.90 01-JUN-06:10
July 0.278710E+10 3094.06 17-JUL-19:30 0.149358E+11 6747.90 01-JUL-06:10
August 0.287489E+10 3094.06 01-AUG-19:40 0.149358E+11 6747.90 01-AUG-06:10
September 0.284436E+10 3094.06 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.301413E+10 3094.06 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.295977E+10 3094.06 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.307587E+10 3094.06 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.346457E+11     0.175857E+12    
Minimum of Months 0.269934E+10 3094.06   0.134904E+11 6747.90  
Maximum of Months 0.307587E+10 3094.06   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.113146E+10 1089.83 02-JAN-20:10 0.368383E+11 16487.34 01-JAN-07:10
February 0.102161E+10 1089.83 01-FEB-20:10 0.332733E+11 16487.34 01-FEB-07:10
March 0.113495E+10 1089.83 01-MAR-20:10 0.368383E+11 16487.34 01-MAR-07:10
April 0.109310E+10 1089.83 03-APR-19:10 0.356500E+11 16487.34 01-APR-06:10
May 0.113342E+10 1089.83 01-MAY-19:10 0.368383E+11 16487.34 01-MAY-06:10
June 0.109811E+10 1089.83 01-JUN-19:10 0.356500E+11 16487.34 01-JUN-06:10
July 0.112841E+10 1089.83 03-JUL-19:10 0.368383E+11 16487.34 01-JUL-06:10
August 0.113539E+10 1089.83 01-AUG-19:10 0.368383E+11 16487.34 01-AUG-06:10
September 0.109354E+10 1089.83 01-SEP-19:10 0.356500E+11 16487.34 01-SEP-06:10
October 0.113103E+10 1089.83 02-OCT-19:10 0.368383E+11 16487.34 01-OCT-06:10
November 0.109724E+10 1089.83 01-NOV-19:10 0.356500E+11 16487.34 01-NOV-06:10
December 0.112841E+10 1089.83 01-DEC-20:10 0.368383E+11 16487.34 01-DEC-07:10
             
Annual Sum or Average 0.133267E+11     0.433742E+12    
Minimum of Months 0.102161E+10 1089.83   0.332733E+11 16487.34  
Maximum of Months 0.113539E+10 1089.83   0.368383E+11 16487.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.246211E+10 2371.52 02-JAN-20:10 0.00 0.00
February 0.222306E+10 2371.52 01-FEB-20:10 0.00 0.00
March 0.246970E+10 2371.52 01-MAR-20:10 0.00 0.00
April 0.237864E+10 2371.52 03-APR-19:10 0.00 0.00
May 0.246638E+10 2371.52 01-MAY-19:10 0.00 0.00
June 0.238954E+10 2371.52 01-JUN-19:10 0.00 0.00
July 0.245547E+10 2371.52 03-JUL-19:10 0.00 0.00
August 0.247065E+10 2371.52 01-AUG-19:10 0.00 0.00
September 0.237958E+10 2371.52 01-SEP-19:10 0.00 0.00
October 0.246116E+10 2371.52 02-OCT-19:10 0.00 0.00
November 0.238765E+10 2371.52 01-NOV-19:10 0.00 0.00
December 0.245547E+10 2371.52 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.289994E+11     0.00 0.00
Minimum of Months 0.222306E+10 2371.52   0.00 0.00
Maximum of Months 0.247065E+10 2371.52   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.147273E+11 0.127587E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.132974E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.147727E+11 0.127855E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.142280E+11 0.123314E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.147528E+11 0.127741E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.142932E+11 0.123716E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.146876E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.147784E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.142337E+11 0.123352E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.147216E+11 0.127549E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.142819E+11 0.123659E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.146876E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.173462E+12 0.150255E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.132974E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.147784E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.731324E+09 0.864900E+09 0.00 0.00 0.00 0.00 0.00 0.568421E+09
February 0.179968E+10 0.660319E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.510220E+09
March 0.199990E+10 0.733578E+09 0.866718E+09 0.00 0.00 0.00 0.00 0.00 0.503863E+09
April 0.192973E+10 0.706528E+09 0.835931E+09 0.00 0.00 0.00 0.00 167937.01 0.400662E+09
May 0.199475E+10 0.732592E+09 0.865939E+09 0.00 0.00 0.00 0.00 6020.23 0.376094E+09
June 0.193394E+10 0.709769E+09 0.838659E+09 0.00 0.00 0.00 0.00 1090094.32 0.257494E+09
July 0.199054E+10 0.729351E+09 0.863211E+09 0.00 0.00 0.00 0.00 3550124.30 0.219721E+09
August 0.199896E+10 0.733860E+09 0.866978E+09 0.00 0.00 0.00 0.00 516295.92 0.201344E+09
September 0.192879E+10 0.706810E+09 0.836191E+09 0.00 0.00 0.00 0.00 0.00 0.265770E+09
October 0.199148E+10 0.731042E+09 0.864640E+09 0.00 0.00 0.00 0.00 0.00 0.395055E+09
November 0.192552E+10 0.709205E+09 0.838269E+09 0.00 0.00 0.00 0.00 0.00 0.466749E+09
December 0.199054E+10 0.729351E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.00 0.564814E+09
                   
Annual Sum or Average 0.234744E+11 0.861373E+10 0.101856E+11 0.00 0.00 0.00 0.00 5330471.77 0.473021E+10
Minimum of Months 0.179968E+10 0.660319E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.201344E+09
Maximum of Months 0.199990E+10 0.733860E+09 0.866978E+09 0.00 0.00 0.00 0.00 3550124.30 0.568421E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.846876E+09 0.100156E+10 0.00 0.00 0.00 0.00 0.00 0.228144E+09
February 0.208403E+10 0.764651E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 0.205410E+09
March 0.231589E+10 0.849486E+09 0.100366E+10 0.00 0.00 0.00 0.00 0.00 0.205722E+09
April 0.223463E+10 0.818162E+09 0.968011E+09 0.00 0.00 0.00 0.00 57832.61 0.168777E+09
May 0.230993E+10 0.848344E+09 0.100276E+10 0.00 0.00 0.00 0.00 19196.12 0.162153E+09
June 0.223950E+10 0.821915E+09 0.971170E+09 0.00 0.00 0.00 0.00 427686.28 0.117737E+09
July 0.230505E+10 0.844592E+09 0.999601E+09 0.00 0.00 0.00 0.00 1306597.98 0.102583E+09
August 0.231480E+10 0.849812E+09 0.100396E+10 0.00 0.00 0.00 0.00 249981.36 94429817.89
September 0.223354E+10 0.818489E+09 0.968312E+09 0.00 0.00 0.00 0.00 0.00 0.117207E+09
October 0.230614E+10 0.846549E+09 0.100126E+10 0.00 0.00 0.00 0.00 0.00 0.166024E+09
November 0.222975E+10 0.821262E+09 0.970719E+09 0.00 0.00 0.00 0.00 0.00 0.190880E+09
December 0.230505E+10 0.844592E+09 0.999601E+09 0.00 0.00 0.00 0.00 0.00 0.224920E+09
                   
Annual Sum or Average 0.271834E+11 0.997473E+10 0.117950E+11 0.00 0.00 0.00 0.00 2061294.35 0.198399E+10
Minimum of Months 0.208403E+10 0.764651E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 94429817.89
Maximum of Months 0.231589E+10 0.849812E+09 0.100396E+10 0.00 0.00 0.00 0.00 1306597.98 0.228144E+09



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.141236E+10 0.105898E+10 0.00 0.00 0.00 0.00 0.00 0.518628E+09
February 0.440737E+09 0.127524E+10 0.956227E+09 0.00 0.00 0.00 0.00 0.00 0.463996E+09
March 0.489771E+09 0.141672E+10 0.106120E+10 0.00 0.00 0.00 0.00 0.00 0.465318E+09
April 0.472586E+09 0.136448E+10 0.102351E+10 0.00 0.00 0.00 0.00 263660.35 0.376215E+09
May 0.488511E+09 0.141481E+10 0.106025E+10 0.00 0.00 0.00 0.00 113470.79 0.364532E+09
June 0.473617E+09 0.137074E+10 0.102685E+10 0.00 0.00 0.00 0.00 1212925.28 0.267953E+09
July 0.487480E+09 0.140855E+10 0.105691E+10 0.00 0.00 0.00 0.00 3206481.71 0.234452E+09
August 0.489542E+09 0.141726E+10 0.106152E+10 0.00 0.00 0.00 0.00 798932.69 0.213565E+09
September 0.472357E+09 0.136502E+10 0.102382E+10 0.00 0.00 0.00 0.00 39058.17 0.262456E+09
October 0.487709E+09 0.141182E+10 0.105866E+10 0.00 0.00 0.00 0.00 0.00 0.371834E+09
November 0.471555E+09 0.136965E+10 0.102637E+10 0.00 0.00 0.00 0.00 0.00 0.429974E+09
December 0.487480E+09 0.140855E+10 0.105691E+10 0.00 0.00 0.00 0.00 0.00 0.515741E+09
                   
Annual Sum or Average 0.574883E+10 0.166352E+11 0.124712E+11 0.00 0.00 0.00 0.00 5634528.98 0.448467E+10
Minimum of Months 0.440737E+09 0.127524E+10 0.956227E+09 0.00 0.00 0.00 0.00 0.00 0.213565E+09
Maximum of Months 0.489771E+09 0.141726E+10 0.106152E+10 0.00 0.00 0.00 0.00 3206481.71 0.518628E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.236418E+09 0.305485E+09 0.00 0.00 0.00 0.00 0.00 0.297435E+09
February 0.339028E+09 0.213464E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 0.266013E+09
March 0.376747E+09 0.237147E+09 0.306128E+09 0.00 0.00 0.00 0.00 0.00 0.265584E+09
April 0.363528E+09 0.228402E+09 0.295253E+09 0.00 0.00 0.00 0.00 158345.70 0.212820E+09
May 0.375778E+09 0.236828E+09 0.305852E+09 0.00 0.00 0.00 0.00 68235.36 0.205837E+09
June 0.364321E+09 0.229450E+09 0.296217E+09 0.00 0.00 0.00 0.00 729426.75 0.150624E+09
July 0.374985E+09 0.235780E+09 0.304889E+09 0.00 0.00 0.00 0.00 1906471.30 0.131396E+09
August 0.376571E+09 0.237238E+09 0.306219E+09 0.00 0.00 0.00 0.00 480838.27 0.119423E+09
September 0.363352E+09 0.228493E+09 0.295345E+09 0.00 0.00 0.00 0.00 25101.24 0.147614E+09
October 0.375161E+09 0.236327E+09 0.305393E+09 0.00 0.00 0.00 0.00 0.00 0.209892E+09
November 0.362735E+09 0.229268E+09 0.296079E+09 0.00 0.00 0.00 0.00 0.00 0.245005E+09
December 0.374985E+09 0.235780E+09 0.304889E+09 0.00 0.00 0.00 0.00 0.00 0.296415E+09
                   
Annual Sum or Average 0.442217E+10 0.278459E+10 0.359760E+10 0.00 0.00 0.00 0.00 3368418.62 0.254806E+10
Minimum of Months 0.339028E+09 0.213464E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 0.119423E+09
Maximum of Months 0.376747E+09 0.237238E+09 0.306219E+09 0.00 0.00 0.00 0.00 1906471.30 0.297435E+09



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.370859E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 0.00 0.786366E+09
February 0.139600E+10 0.334852E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.704813E+09
March 0.155131E+10 0.372002E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 0.00 0.711532E+09
April 0.149688E+10 0.358285E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 328725.26 0.561502E+09
May 0.154732E+10 0.371502E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 90714.18 0.539517E+09
June 0.150015E+10 0.359929E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 1674330.05 0.383861E+09
July 0.154405E+10 0.369859E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 4660054.67 0.329821E+09
August 0.155059E+10 0.372145E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 1170682.04 0.298603E+09
September 0.149615E+10 0.358428E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 116168.78 0.377804E+09
October 0.154478E+10 0.370717E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 0.00 0.564045E+09
November 0.149361E+10 0.359643E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 0.00 0.660411E+09
December 0.154405E+10 0.369859E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.00 0.783736E+09
                   
Annual Sum or Average 0.182090E+11 0.436808E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 8040674.99 0.670201E+10
Minimum of Months 0.139600E+10 0.334852E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.298603E+09
Maximum of Months 0.155131E+10 0.372145E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 4660054.67 0.786366E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.164303E+10 0.121771E+10 0.00 0.00 0.00 0.00 0.00 0.128695E+10
February 0.236489E+11 0.144635E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.116053E+10
March 0.262800E+11 0.155405E+10 0.122027E+10 0.00 0.00 0.00 0.00 0.00 0.114743E+10
April 0.253579E+11 0.142686E+10 0.117692E+10 0.00 0.00 0.00 0.00 303905.36 0.946287E+09
May 0.262123E+11 0.140301E+10 0.121917E+10 0.00 0.00 0.00 0.00 2970.99 0.895945E+09
June 0.254132E+11 0.131931E+10 0.118076E+10 0.00 0.00 0.00 0.00 2061762.98 0.635775E+09
July 0.261570E+11 0.137171E+10 0.121533E+10 0.00 0.00 0.00 0.00 7142627.77 0.553658E+09
August 0.262677E+11 0.145249E+10 0.122063E+10 0.00 0.00 0.00 0.00 1004964.60 0.517502E+09
September 0.253456E+11 0.147102E+10 0.117729E+10 0.00 0.00 0.00 0.00 0.00 0.655885E+09
October 0.261693E+11 0.159722E+10 0.121734E+10 0.00 0.00 0.00 0.00 0.00 0.926909E+09
November 0.253025E+11 0.158401E+10 0.118021E+10 0.00 0.00 0.00 0.00 0.00 0.106935E+10
December 0.261570E+11 0.166292E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.00 0.126900E+10
                   
Annual Sum or Average 0.308468E+12 0.179320E+11 0.143405E+11 0.00 0.00 0.00 0.00 10516231.69 0.110652E+11
Minimum of Months 0.236489E+11 0.131931E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.517502E+09
Maximum of Months 0.262800E+11 0.166292E+10 0.122063E+10 0.00 0.00 0.00 0.00 7142627.77 0.128695E+10



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.104691E+11 0.126520E+11 0.00 0.00 0.00 0.00 0.00 0.383298E+10
February 0.702046E+11 0.941375E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.345287E+10
March 0.780153E+11 0.104095E+11 0.126786E+11 0.00 0.00 0.00 0.00 0.00 0.345939E+10
April 0.752779E+11 0.994922E+10 0.122282E+11 0.00 0.00 0.00 0.00 852612.37 0.284007E+10
May 0.778146E+11 0.102405E+11 0.126672E+11 0.00 0.00 0.00 0.00 160573.53 0.272307E+10
June 0.754422E+11 0.988088E+10 0.122682E+11 0.00 0.00 0.00 0.00 6175729.19 0.198159E+10
July 0.776503E+11 0.101688E+11 0.126273E+11 0.00 0.00 0.00 0.00 20115357.34 0.173099E+10
August 0.779788E+11 0.103060E+11 0.126824E+11 0.00 0.00 0.00 0.00 3323176.09 0.160082E+10
September 0.752414E+11 0.999882E+10 0.122320E+11 0.00 0.00 0.00 0.00 0.00 0.198863E+10
October 0.776868E+11 0.104188E+11 0.126482E+11 0.00 0.00 0.00 0.00 0.00 0.280688E+10
November 0.751137E+11 0.101444E+11 0.122624E+11 0.00 0.00 0.00 0.00 0.00 0.321852E+10
December 0.776503E+11 0.104681E+11 0.126273E+11 0.00 0.00 0.00 0.00 0.00 0.377888E+10
                   
Annual Sum or Average 0.915726E+12 0.121868E+12 0.148998E+12 0.00 0.00 0.00 0.00 30627448.53 0.334147E+11
Minimum of Months 0.702046E+11 0.941375E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.160082E+10
Maximum of Months 0.780153E+11 0.104691E+11 0.126824E+11 0.00 0.00 0.00 0.00 20115357.34 0.383298E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.324558E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.292583E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.00 0.290255E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 216892.06 0.232696E+09
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 64620.00 0.220676E+09
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 965929.86 0.153495E+09
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 2574042.54 0.128248E+09
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 724311.36 0.114006E+09
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 238282.31 0.150081E+09
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.226528E+09
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 0.266661E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.320615E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 4784078.13 0.272040E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.114006E+09
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 2574042.54 0.324558E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.320915E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.288531E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.00 0.288340E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 223720.84 0.229400E+09
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 65094.41 0.218685E+09
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 964451.14 0.152525E+09
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 2600164.58 0.127343E+09
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 730266.38 0.112470E+09
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 251097.14 0.147078E+09
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.222830E+09
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 0.263406E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.318407E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 4834794.48 0.268993E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.112470E+09
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 2600164.58 0.320915E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 85091918.49 0.255708E+09 0.00 0.00 0.00 0.00 0.00 88753508.14
February 0.00 76846309.13 0.230956E+09 0.00 0.00 0.00 0.00 0.00 80789670.46
March 0.00 84415649.14 0.255355E+09 0.00 0.00 0.00 0.00 0.00 74938850.73
April 0.00 82445007.08 0.247516E+09 0.00 0.00 0.00 0.00 18502.89 70863452.67
May 0.00 84753783.81 0.255532E+09 0.00 0.00 0.00 0.00 2653.18 67834440.69
June 0.00 81790910.76 0.247163E+09 0.00 0.00 0.00 0.00 138793.58 50020780.49
July 0.00 85418966.65 0.255885E+09 0.00 0.00 0.00 0.00 506442.20 43397114.14
August 0.00 84415649.14 0.255355E+09 0.00 0.00 0.00 0.00 94350.92 39698524.38
September 0.00 82467180.11 0.247516E+09 0.00 0.00 0.00 0.00 0.00 49722897.47
October 0.00 85080831.98 0.255708E+09 0.00 0.00 0.00 0.00 0.00 66834848.93
November 0.00 82117958.92 0.247340E+09 0.00 0.00 0.00 0.00 0.00 72532011.41
December 0.00 85430053.17 0.255885E+09 0.00 0.00 0.00 0.00 0.00 82085274.36
                   
Annual Sum or Average 0.00 0.100027E+10 0.300992E+10 0.00 0.00 0.00 0.00 760742.77 0.787471E+09
Minimum of Months 0.00 76846309.13 0.230956E+09 0.00 0.00 0.00 0.00 0.00 39698524.38
Maximum of Months 0.00 85430053.17 0.255885E+09 0.00 0.00 0.00 0.00 506442.20 88753508.14



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 85115186.72 0.255778E+09 0.00 0.00 0.00 0.00 0.00 90953658.15
February 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 0.00 81559801.69
March 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 0.00 81790961.13
April 0.293479E+09 82467551.52 0.247584E+09 0.00 0.00 0.00 0.00 81983.51 63640620.71
May 0.303504E+09 84776959.58 0.255602E+09 0.00 0.00 0.00 0.00 29150.66 60504303.83
June 0.293842E+09 81813276.33 0.247231E+09 0.00 0.00 0.00 0.00 325706.81 41732404.46
July 0.303141E+09 85442324.32 0.255955E+09 0.00 0.00 0.00 0.00 812136.18 34616448.34
August 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 267211.34 30227645.12
September 0.293479E+09 82489730.61 0.247584E+09 0.00 0.00 0.00 0.00 92533.77 40217156.43
October 0.303322E+09 85104097.18 0.255778E+09 0.00 0.00 0.00 0.00 0.00 62819063.29
November 0.293661E+09 82140413.93 0.247408E+09 0.00 0.00 0.00 0.00 0.00 74874357.17
December 0.303141E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 0.00 90515239.33
                   
Annual Sum or Average 0.357224E+10 0.100055E+10 0.301074E+10 0.00 0.00 0.00 0.00 1608722.26 0.753452E+09
Minimum of Months 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 0.00 30227645.12
Maximum of Months 0.303685E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 812136.18 90953658.15



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.324501E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.292343E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.00 0.290801E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 236726.48 0.234827E+09
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 66279.19 0.222528E+09
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 980265.22 0.154359E+09
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 2556693.87 0.129258E+09
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 733036.89 0.114759E+09
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 252803.96 0.151384E+09
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.227330E+09
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 0.266582E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.320896E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 4825805.60 0.272957E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.114759E+09
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 2556693.87 0.324501E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.320958E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.288200E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.00 0.288931E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 239945.05 0.232656E+09
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 66381.87 0.221347E+09
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 981722.91 0.153900E+09
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 2557661.90 0.129012E+09
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 736448.45 0.114368E+09
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 258157.80 0.150225E+09
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.224075E+09
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 0.263302E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.318670E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 4840317.98 0.270564E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.114368E+09
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 2557661.90 0.320958E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.232638E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.397863E+09
February 0.348285E+10 0.210051E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.356257E+09
March 0.387034E+10 0.233355E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.355374E+09
April 0.373454E+10 0.224750E+10 0.00 0.00 0.00 0.00 0.00 129213.08 0.291503E+09
May 0.386038E+10 0.233041E+10 0.00 0.00 0.00 0.00 0.00 56201.39 0.283132E+09
June 0.374269E+10 0.225781E+10 0.00 0.00 0.00 0.00 0.00 781846.47 0.206557E+09
July 0.385223E+10 0.232011E+10 0.00 0.00 0.00 0.00 0.00 2348093.73 0.180235E+09
August 0.386853E+10 0.233445E+10 0.00 0.00 0.00 0.00 0.00 480107.65 0.165117E+09
September 0.373273E+10 0.224840E+10 0.00 0.00 0.00 0.00 0.00 535.20 0.204116E+09
October 0.385404E+10 0.232548E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.283223E+09
November 0.372639E+10 0.225602E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.327235E+09
December 0.385223E+10 0.232011E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.396321E+09
                   
Annual Sum or Average 0.454292E+11 0.274007E+11 0.00 0.00 0.00 0.00 0.00 3795997.52 0.344693E+10
Minimum of Months 0.348285E+10 0.210051E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.165117E+09
Maximum of Months 0.387034E+10 0.233445E+10 0.00 0.00 0.00 0.00 0.00 2348093.73 0.397863E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.323958E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.291998E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.00 0.289727E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 193816.45 0.233318E+09
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 58945.52 0.221158E+09
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 930930.81 0.154243E+09
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 2512103.10 0.129080E+09
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 697275.99 0.114801E+09
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 218262.41 0.150610E+09
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.226073E+09
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 0.265956E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.320521E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 4611334.28 0.272144E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.114801E+09
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 2512103.10 0.323958E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.320772E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.287979E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.00 0.287722E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 199308.43 0.229928E+09
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 60922.75 0.219149E+09
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 926424.81 0.153379E+09
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 2530696.98 0.128275E+09
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 707851.96 0.113374E+09
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 235904.00 0.147327E+09
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.221980E+09
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 0.262841E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.318991E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 4661108.93 0.269172E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.113374E+09
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 2530696.98 0.320772E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 85115186.72 0.255778E+09 0.00 0.00 0.00 0.00 0.00 0.169671E+09
February 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 0.00 0.152583E+09
March 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 0.00 0.150987E+09
April 0.293479E+09 82467551.52 0.247584E+09 0.00 0.00 0.00 0.00 115353.89 0.120579E+09
May 0.303504E+09 84776959.58 0.255602E+09 0.00 0.00 0.00 0.00 32233.40 0.113915E+09
June 0.293842E+09 81813276.33 0.247231E+09 0.00 0.00 0.00 0.00 485783.84 79010636.12
July 0.303141E+09 85442324.32 0.255955E+09 0.00 0.00 0.00 0.00 1292967.93 66121630.85
August 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 361431.00 58844916.56
September 0.293479E+09 82489730.61 0.247584E+09 0.00 0.00 0.00 0.00 111459.23 77767129.86
October 0.303322E+09 85104097.18 0.255778E+09 0.00 0.00 0.00 0.00 0.00 0.118120E+09
November 0.293661E+09 82140413.93 0.247408E+09 0.00 0.00 0.00 0.00 0.00 0.139537E+09
December 0.303141E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 0.00 0.167310E+09
                   
Annual Sum or Average 0.357224E+10 0.100055E+10 0.301074E+10 0.00 0.00 0.00 0.00 2399229.28 0.141445E+10
Minimum of Months 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 0.00 58844916.56
Maximum of Months 0.303685E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 1292967.93 0.169671E+09



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.306267E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.925225E+09
February 0.415303E+11 0.272729E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.831081E+09
March 0.461508E+11 0.297768E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.844444E+09
April 0.445315E+11 0.279769E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.678046E+09
May 0.460320E+11 0.282496E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.654450E+09
June 0.446286E+11 0.269934E+10 0.144540E+11 0.00 0.00 0.00 0.00 665265.82 0.479585E+09
July 0.459349E+11 0.278710E+10 0.149358E+11 0.00 0.00 0.00 0.00 3516389.76 0.419289E+09
August 0.461292E+11 0.287489E+10 0.149358E+11 0.00 0.00 0.00 0.00 498880.45 0.384332E+09
September 0.445099E+11 0.284436E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.470619E+09
October 0.459565E+11 0.301413E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.676362E+09
November 0.444343E+11 0.295977E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.780380E+09
December 0.459349E+11 0.307587E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.921278E+09
                   
Annual Sum or Average 0.541708E+12 0.346457E+11 0.175857E+12 0.00 0.00 0.00 0.00 4680536.04 0.806509E+10
Minimum of Months 0.415303E+11 0.269934E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.384332E+09
Maximum of Months 0.461508E+11 0.307587E+10 0.149358E+11 0.00 0.00 0.00 0.00 3516389.76 0.925225E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.306267E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.934108E+09
February 0.415303E+11 0.272729E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.838813E+09
March 0.461508E+11 0.297768E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.851785E+09
April 0.445315E+11 0.279769E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.682123E+09
May 0.460320E+11 0.282496E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.657954E+09
June 0.446286E+11 0.269934E+10 0.144540E+11 0.00 0.00 0.00 0.00 665247.72 0.481528E+09
July 0.459349E+11 0.278710E+10 0.149358E+11 0.00 0.00 0.00 0.00 3474847.24 0.420672E+09
August 0.461292E+11 0.287489E+10 0.149358E+11 0.00 0.00 0.00 0.00 498869.28 0.386151E+09
September 0.445099E+11 0.284436E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.473488E+09
October 0.459565E+11 0.301413E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.682530E+09
November 0.444343E+11 0.295977E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.788479E+09
December 0.459349E+11 0.307587E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.930623E+09
                   
Annual Sum or Average 0.541708E+12 0.346457E+11 0.175857E+12 0.00 0.00 0.00 0.00 4638964.25 0.812825E+10
Minimum of Months 0.415303E+11 0.269934E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.386151E+09
Maximum of Months 0.461508E+11 0.307587E+10 0.149358E+11 0.00 0.00 0.00 0.00 3474847.24 0.934108E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.113146E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.840857E+09
February 0.369574E+10 0.102161E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.753275E+09
March 0.410691E+10 0.113495E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.765877E+09
April 0.396281E+10 0.109310E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.610260E+09
May 0.409635E+10 0.113342E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.589474E+09
June 0.397146E+10 0.109811E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 600012.20 0.427493E+09
July 0.408770E+10 0.112841E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 3108725.90 0.372788E+09
August 0.410499E+10 0.113539E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 449046.74 0.342361E+09
September 0.396089E+10 0.109354E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.420666E+09
October 0.408962E+10 0.113103E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.613940E+09
November 0.395417E+10 0.109724E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.711546E+09
December 0.408770E+10 0.112841E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.837746E+09
                   
Annual Sum or Average 0.482060E+11 0.133267E+11 0.392709E+12 0.359593E+12 0.00 0.00 0.00 4157784.84 0.728628E+10
Minimum of Months 0.369574E+10 0.102161E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.342361E+09
Maximum of Months 0.410691E+10 0.113539E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 3108725.90 0.840857E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.246211E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.706559E+09
February 0.368610E+10 0.222306E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.632995E+09
March 0.409620E+10 0.246970E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.631212E+09
April 0.395248E+10 0.237864E+10 0.00 0.00 0.00 0.00 0.00 70536.35 0.512732E+09
May 0.408566E+10 0.246638E+10 0.00 0.00 0.00 0.00 0.00 9755.60 0.494568E+09
June 0.396110E+10 0.238954E+10 0.00 0.00 0.00 0.00 0.00 791240.97 0.362710E+09
July 0.407704E+10 0.245547E+10 0.00 0.00 0.00 0.00 0.00 3456339.74 0.317656E+09
August 0.409429E+10 0.247065E+10 0.00 0.00 0.00 0.00 0.00 575586.24 0.288214E+09
September 0.395056E+10 0.237958E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.351037E+09
October 0.407896E+10 0.246116E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.494777E+09
November 0.394385E+10 0.238765E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.581172E+09
December 0.407704E+10 0.245547E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.703956E+09
                   
Annual Sum or Average 0.480803E+11 0.289994E+11 0.00 0.00 0.00 0.00 0.00 4903458.90 0.607759E+10
Minimum of Months 0.368610E+10 0.222306E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.288214E+09
Maximum of Months 0.409620E+10 0.247065E+10 0.00 0.00 0.00 0.00 0.00 3456339.74 0.706559E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 14185.34 02-JAN-20:10 10113.80 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 14185.34 01-FEB-20:10 10113.80 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 14185.34 01-MAR-20:10 10113.80 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 14185.34 03-APR-19:10 10113.80 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 14185.34 01-MAY-19:10 10113.80 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 14185.34 01-JUN-19:10 10113.80 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 14185.34 03-JUL-19:10 10113.80 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 14185.34 01-AUG-19:10 10113.80 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 14185.34 01-SEP-19:10 10113.80 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 14185.34 02-OCT-19:10 10113.80 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 14185.34 01-NOV-19:10 10113.80 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 14185.34 01-DEC-20:10 10113.80 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   14185.34   10113.80   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   14185.34   10113.80   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 704.41 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 348.09 11-JAN-24:00
February 1169.53 01-FEB-00:10 704.41 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 322.53 17-FEB-07:00
March 1169.53 01-MAR-00:10 704.41 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 279.63 08-MAR-07:00
April 1169.53 01-APR-00:10 704.41 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 17.54 30-APR-18:00 265.40 08-APR-06:00
May 1169.53 01-MAY-00:10 704.41 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 2.97 22-MAY-15:00 240.87 06-MAY-05:00
June 1169.53 01-JUN-00:10 704.41 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 49.76 13-JUN-17:00 186.88 07-JUN-05:00
July 1169.53 01-JUL-00:10 704.41 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 79.05 22-JUL-18:00 177.73 31-JUL-05:00
August 1169.53 01-AUG-00:10 704.41 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 49.29 14-AUG-18:00 163.66 20-AUG-05:03
September 1169.53 01-SEP-00:10 704.41 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 200.65 21-SEP-06:00
October 1169.53 01-OCT-23:10 704.41 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 239.16 15-OCT-04:00
November 1169.53 01-NOV-00:10 704.41 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 297.47 29-NOV-02:00
December 1169.53 01-DEC-00:10 704.41 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 306.93 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   704.41   685.60   0.00 0.00 0.00 0.00 0.00   163.66  
Maximum of Months 1169.53   704.41   685.60   0.00 0.00 0.00 0.00 79.05   348.09  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 815.72 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 140.19 11-JAN-24:00
February 1354.32 01-FEB-00:10 815.72 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 128.20 17-FEB-21:00
March 1354.32 01-MAR-00:10 815.72 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 112.66 08-MAR-07:00
April 1354.32 01-APR-00:10 815.72 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 4.56 30-APR-17:00 109.50 08-APR-06:00
May 1354.32 01-MAY-00:10 815.72 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 4.87 22-MAY-15:00 99.58 06-MAY-05:00
June 1354.32 01-JUN-00:10 815.72 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 16.91 13-JUN-17:00 81.01 07-JUN-05:00
July 1354.32 01-JUL-00:10 815.72 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 26.94 22-JUL-18:00 78.56 31-JUL-04:53
August 1354.32 01-AUG-00:10 815.72 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 16.93 14-AUG-17:00 73.08 24-AUG-05:53
September 1354.32 01-SEP-00:10 815.72 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 88.42 20-SEP-24:00
October 1354.32 01-OCT-23:10 815.72 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 100.85 07-OCT-04:00
November 1354.32 01-NOV-00:10 815.72 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 119.36 29-NOV-02:00
December 1354.32 01-DEC-00:10 815.72 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 125.13 29-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   815.72   793.93   0.00 0.00 0.00 0.00 0.00   73.08  
Maximum of Months 1354.32   815.72   793.93   0.00 0.00 0.00 0.00 26.94   140.19  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 1360.40 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 317.53 11-JAN-24:00
February 286.42 01-FEB-00:10 1360.40 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 294.25 17-FEB-07:00
March 286.42 01-MAR-00:10 1360.40 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 255.60 08-MAR-07:00
April 286.42 01-APR-00:10 1360.40 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 17.13 30-APR-17:00 247.72 08-APR-06:00
May 286.42 01-MAY-00:10 1360.40 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 18.58 22-MAY-15:00 225.63 07-MAY-05:00
June 286.42 01-JUN-00:10 1360.40 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 43.89 13-JUN-17:00 182.57 07-JUN-05:00
July 286.42 01-JUL-00:10 1360.40 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 67.55 22-JUL-18:00 176.82 31-JUL-04:53
August 286.42 01-AUG-00:10 1360.40 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 45.38 14-AUG-17:00 166.66 24-AUG-05:53
September 286.42 01-SEP-00:10 1360.40 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 5.44 11-SEP-17:00 199.15 20-SEP-24:00
October 286.42 01-OCT-23:10 1360.40 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 226.77 07-OCT-04:00
November 286.42 01-NOV-00:10 1360.40 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 271.40 29-NOV-02:00
December 286.42 01-DEC-00:10 1360.40 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 283.02 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   1360.40   839.45   0.00 0.00 0.00 0.00 0.00   166.66  
Maximum of Months 286.42   1360.40   839.45   0.00 0.00 0.00 0.00 67.55   317.53  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 227.72 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 183.20 11-JAN-24:00
February 220.32 01-FEB-00:10 227.72 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 169.77 17-FEB-07:00
March 220.32 01-MAR-00:10 227.72 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 147.18 08-MAR-07:00
April 220.32 01-APR-00:10 227.72 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 9.71 30-APR-17:00 141.12 08-APR-06:00
May 220.32 01-MAY-00:10 227.72 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 10.95 22-MAY-15:00 128.61 07-MAY-05:00
June 220.32 01-JUN-00:10 227.72 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 25.37 13-JUN-17:00 104.08 07-JUN-05:00
July 220.32 01-JUL-00:10 227.72 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 39.93 22-JUL-18:00 100.71 31-JUL-04:53
August 220.32 01-AUG-00:10 227.72 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 26.16 14-AUG-17:00 94.37 20-AUG-05:00
September 220.32 01-SEP-00:10 227.72 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 3.18 11-SEP-17:00 113.18 20-SEP-24:00
October 220.32 01-OCT-23:10 227.72 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 129.96 07-OCT-04:00
November 220.32 01-NOV-00:10 227.72 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 156.58 29-NOV-02:00
December 220.32 01-DEC-00:10 227.72 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 161.54 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   227.72   242.16   0.00 0.00 0.00 0.00 0.00   94.37  
Maximum of Months 220.32   227.72   242.16   0.00 0.00 0.00 0.00 39.93   183.20  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 357.21 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 0.00 01-JAN-00:10 479.83 10-JAN-08:00
February 907.20 01-FEB-00:10 357.21 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 0.00 01-FEB-00:03 449.61 17-FEB-07:00
March 907.20 01-MAR-00:10 357.21 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 0.00 01-MAR-00:03 395.65 08-MAR-07:00
April 907.20 01-APR-00:10 357.21 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 38.23 30-APR-17:00 363.89 08-APR-06:00
May 907.20 01-MAY-00:10 357.21 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 18.02 22-MAY-15:20 341.64 17-MAY-06:15
June 907.20 01-JUN-00:10 357.21 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 71.88 13-JUN-17:00 288.61 06-JUN-22:55
July 907.20 01-JUL-00:10 357.21 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 100.55 21-JUL-17:00 286.76 31-JUL-05:03
August 907.20 01-AUG-00:10 357.21 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 71.36 14-AUG-17:00 259.47 20-AUG-05:25
September 907.20 01-SEP-00:10 357.21 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 12.83 11-SEP-17:00 321.89 20-SEP-06:05
October 907.20 01-OCT-23:10 357.21 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 0.00 01-OCT-00:10 343.20 05-OCT-21:33
November 907.20 01-NOV-00:10 357.21 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 0.00 01-NOV-00:05 401.71 28-NOV-23:00
December 907.20 01-DEC-00:10 357.21 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 0.00 01-DEC-00:03 430.10 29-DEC-21:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   357.21   4572.80   39726.58   0.00 0.00 0.00 0.00   259.47  
Maximum of Months 907.20   357.21   4572.80   39726.58   0.00 0.00 0.00 100.55   479.83  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 1761.91 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 795.17 11-JAN-24:00
February 15368.40 01-FEB-00:10 1761.91 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 714.32 18-FEB-02:00
March 15368.40 01-MAR-00:10 1761.91 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 620.69 08-MAR-07:00
April 15368.40 01-APR-00:10 1761.91 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 35.97 30-APR-18:00 615.70 08-APR-05:00
May 15368.40 01-MAY-00:10 1761.91 01-MAY-19:19 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 4.95 22-MAY-15:00 560.95 06-MAY-05:00
June 15368.40 01-JUN-00:10 1761.91 01-JUN-19:30 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 100.08 13-JUN-17:00 465.02 08-JUN-00:50
July 15368.40 01-JUL-00:10 1761.91 17-JUL-19:30 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 165.95 22-JUL-18:00 457.40 31-JUL-04:42
August 15368.40 01-AUG-00:10 1761.91 01-AUG-19:30 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 102.22 14-AUG-18:00 412.27 20-AUG-05:25
September 15368.40 01-SEP-00:10 1761.91 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 498.12 20-SEP-24:00
October 15368.40 01-OCT-23:10 1761.91 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 569.38 07-OCT-04:00
November 15368.40 01-NOV-00:10 1761.91 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 677.02 29-NOV-02:00
December 15368.40 01-DEC-00:10 1761.91 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 697.18 29-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   1761.91   965.27   0.00 0.00 0.00 0.00 0.00   412.27  
Maximum of Months 15368.40   1761.91   965.27   0.00 0.00 0.00 0.00 165.95   795.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 10265.18 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 2352.19 11-JAN-24:00
February 45622.98 01-FEB-00:10 10265.18 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 2137.63 17-FEB-07:00
March 45622.98 01-MAR-00:10 10265.18 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 1889.40 08-MAR-07:00
April 45622.98 01-APR-00:10 10265.18 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 73.70 30-APR-17:00 1845.71 08-APR-05:00
May 45622.98 01-MAY-00:10 10265.18 01-MAY-19:19 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 61.31 22-MAY-15:00 1688.16 06-MAY-05:00
June 45622.98 01-JUN-00:10 10265.18 01-JUN-19:19 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 273.96 13-JUN-17:00 1376.26 07-JUN-05:00
July 45622.98 01-JUL-00:10 10265.18 17-JUL-19:19 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 441.80 22-JUL-18:00 1330.11 31-JUL-05:00
August 45622.98 01-AUG-00:10 10265.18 01-AUG-19:30 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 267.07 14-AUG-17:00 1232.25 24-AUG-05:53
September 45622.98 01-SEP-00:10 10265.18 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 1491.25 20-SEP-24:00
October 45622.98 01-OCT-23:10 10265.18 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1702.78 07-OCT-04:00
November 45622.98 01-NOV-00:10 10265.18 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 2020.05 29-NOV-02:00
December 45622.98 01-DEC-00:10 10265.18 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 2096.78 29-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   10265.18   10029.21   0.00 0.00 0.00 0.00 0.00   1232.25  
Maximum of Months 45622.98   10265.18   10029.21   0.00 0.00 0.00 0.00 441.80   2352.19  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 203.17 11-JAN-24:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 188.35 17-FEB-07:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 163.44 08-MAR-07:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 19.19 30-APR-19:00 155.17 08-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 18.05 22-MAY-15:10 140.90 06-MAY-05:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 38.98 13-JUN-17:00 109.57 07-JUN-05:00
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 57.05 22-JUL-18:10 101.98 31-JUL-04:53
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 39.06 14-AUG-17:00 94.29 20-AUG-05:00
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 12.47 11-SEP-17:00 117.58 21-SEP-06:00
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 139.94 15-OCT-04:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 173.82 29-NOV-02:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 179.28 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 0.00   94.29  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 57.05   203.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 203.15 11-JAN-24:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 188.34 17-FEB-07:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 163.42 08-MAR-07:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 19.19 30-APR-19:00 155.16 08-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 18.05 22-MAY-15:10 140.89 06-MAY-05:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 38.98 13-JUN-17:00 109.56 07-JUN-05:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 55.10 22-JUL-18:10 101.98 31-JUL-04:53
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 39.06 14-AUG-17:00 94.28 20-AUG-05:00
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 12.48 11-SEP-17:00 117.57 21-SEP-06:00
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 139.93 15-OCT-04:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 173.81 29-NOV-02:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 179.27 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 0.00   94.28  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 55.10   203.15  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 76.99 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 55.26 11-JAN-24:00
February 0.00 01-FEB-00:10 76.99 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 51.60 17-FEB-21:00
March 0.00 01-MAR-00:10 76.99 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 41.03 08-MAR-07:00
April 0.00 01-APR-00:10 76.99 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 1.17 30-APR-19:00 43.79 08-APR-05:20
May 0.00 01-MAY-00:10 76.99 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 1.17 22-MAY-15:00 40.01 07-MAY-05:00
June 0.00 01-JUN-00:10 76.99 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 6.74 13-JUN-17:00 32.68 07-JUN-21:00
July 0.00 01-JUL-00:10 76.99 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 12.16 22-JUL-18:00 30.80 31-JUL-04:53
August 0.00 01-AUG-00:10 76.99 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 6.75 14-AUG-17:00 29.70 24-AUG-06:00
September 0.00 01-SEP-00:10 76.99 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 36.42 20-SEP-24:00
October 0.00 01-OCT-00:10 76.99 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 41.28 07-OCT-04:00
November 0.00 01-NOV-00:10 76.99 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 45.13 28-NOV-21:00
December 0.00 01-DEC-00:10 76.99 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 46.46 26-DEC-20:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   76.99   232.19   0.00 0.00 0.00 0.00 0.00   29.70  
Maximum of Months 0.00   76.99   232.19   0.00 0.00 0.00 0.00 12.16   55.26  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 77.01 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 56.70 11-JAN-24:00
February 180.00 01-FEB-00:10 77.01 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 52.57 17-FEB-07:00
March 180.00 01-MAR-00:10 77.01 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 45.61 08-MAR-07:00
April 180.00 01-APR-00:10 77.01 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 5.36 30-APR-19:00 43.31 08-APR-06:00
May 180.00 01-MAY-00:10 77.01 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 5.04 22-MAY-15:10 39.32 06-MAY-05:00
June 180.00 01-JUN-00:10 77.01 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 10.88 13-JUN-17:00 30.58 07-JUN-05:00
July 180.00 01-JUL-00:10 77.01 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 15.95 22-JUL-18:10 28.46 31-JUL-04:53
August 180.00 01-AUG-00:10 77.01 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 10.90 14-AUG-17:00 26.31 20-AUG-05:00
September 180.00 01-SEP-00:10 77.01 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 3.48 11-SEP-17:00 32.82 21-SEP-06:00
October 180.00 01-OCT-00:10 77.01 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 39.06 15-OCT-04:00
November 180.00 01-NOV-00:10 77.01 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 48.51 29-NOV-02:00
December 180.00 01-DEC-00:10 77.01 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 50.04 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 0.00   26.31  
Maximum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 15.95   56.70  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 203.17 11-JAN-24:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 188.36 17-FEB-07:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 163.44 08-MAR-07:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 19.20 30-APR-19:00 155.17 08-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 18.06 22-MAY-15:08 140.90 06-MAY-05:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 38.98 13-JUN-17:00 109.57 07-JUN-05:00
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 57.14 22-JUL-18:10 101.98 31-JUL-04:53
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 39.06 14-AUG-17:00 94.29 20-AUG-05:00
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 12.48 11-SEP-17:00 117.58 21-SEP-06:00
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 139.94 15-OCT-04:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 173.82 29-NOV-02:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 179.28 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 0.00   94.29  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 57.14   203.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 203.15 11-JAN-24:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 188.34 17-FEB-07:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 163.42 08-MAR-07:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 19.20 30-APR-19:00 155.16 08-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 18.06 22-MAY-15:10 140.89 06-MAY-05:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 38.97 13-JUN-17:00 109.56 07-JUN-05:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 57.13 22-JUL-18:08 101.98 31-JUL-04:55
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 39.06 14-AUG-17:00 94.28 20-AUG-05:00
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 12.47 13-SEP-15:10 117.57 21-SEP-06:00
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 139.93 15-OCT-04:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 173.81 29-NOV-02:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 179.27 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 0.00   94.28  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 57.13   203.15  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 2240.78 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 244.68 11-JAN-24:00
February 2263.36 01-FEB-00:10 2240.78 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 226.76 17-FEB-07:00
March 2263.36 01-MAR-00:10 2240.78 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 196.65 08-MAR-07:00
April 2263.36 01-APR-00:10 2240.78 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 8.86 30-APR-17:00 191.06 08-APR-05:00
May 2263.36 01-MAY-00:10 2240.78 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 11.29 22-MAY-15:00 175.40 07-MAY-05:00
June 2263.36 01-JUN-00:10 2240.78 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 31.56 13-JUN-17:00 141.50 07-JUN-05:00
July 2263.36 01-JUL-00:10 2240.78 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 51.46 22-JUL-18:00 136.97 31-JUL-04:53
August 2263.36 01-AUG-00:10 2240.78 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 32.07 14-AUG-17:00 128.24 23-AUG-03:54
September 2263.36 01-SEP-00:10 2240.78 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.89 11-SEP-17:00 154.07 20-SEP-24:00
October 2263.36 01-OCT-23:10 2240.78 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 177.96 07-OCT-04:00
November 2263.36 01-NOV-00:10 2240.78 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 209.19 29-NOV-02:00
December 2263.36 01-DEC-00:10 2240.78 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 215.80 29-DEC-21:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   2240.78   0.00 0.00 0.00 0.00 0.00 0.00   128.24  
Maximum of Months 2263.36   2240.78   0.00 0.00 0.00 0.00 0.00 51.46   244.68  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 203.66 11-JAN-24:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 188.84 17-FEB-07:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 163.91 08-MAR-07:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 18.78 30-APR-19:00 155.64 08-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 16.68 22-MAY-15:10 141.37 06-MAY-05:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 38.58 13-JUN-17:00 110.02 07-JUN-05:00
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 55.69 22-JUL-18:10 102.43 31-JUL-04:53
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 38.67 14-AUG-17:00 94.73 20-AUG-05:00
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 12.07 11-SEP-17:00 118.04 21-SEP-06:00
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 140.41 15-OCT-04:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 174.31 29-NOV-02:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 179.76 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 0.00   94.73  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 55.69   203.66  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 203.65 11-JAN-24:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 188.83 17-FEB-07:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 163.90 08-MAR-07:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 18.71 30-APR-19:00 155.63 08-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 17.62 22-MAY-15:10 141.36 06-MAY-05:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 38.57 13-JUN-17:00 110.01 07-JUN-05:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 54.59 22-JUL-18:10 102.43 31-JUL-04:53
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 38.67 14-AUG-17:00 94.73 20-AUG-05:00
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 12.07 13-SEP-15:10 118.03 21-SEP-06:00
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 140.40 15-OCT-04:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 174.29 29-NOV-02:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 179.74 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 0.00   94.73  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 54.59   203.65  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 77.01 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 104.20 11-JAN-24:00
February 180.00 01-FEB-00:10 77.01 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 96.62 17-FEB-07:00
March 180.00 01-MAR-00:10 77.01 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 83.86 08-MAR-07:00
April 180.00 01-APR-00:10 77.01 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 9.62 30-APR-19:00 79.63 08-APR-06:00
May 180.00 01-MAY-00:10 77.01 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 9.04 22-MAY-15:10 72.33 06-MAY-05:00
June 180.00 01-JUN-00:10 77.01 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 19.74 13-JUN-17:00 56.29 07-JUN-05:00
July 180.00 01-JUL-00:10 77.01 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 29.04 22-JUL-18:10 52.41 31-JUL-04:53
August 180.00 01-AUG-00:10 77.01 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 19.79 14-AUG-17:00 48.47 20-AUG-05:00
September 180.00 01-SEP-00:10 77.01 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 6.18 11-SEP-17:00 60.39 21-SEP-06:00
October 180.00 01-OCT-00:10 77.01 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 71.84 15-OCT-04:00
November 180.00 01-NOV-00:10 77.01 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 89.18 29-NOV-02:00
December 180.00 01-DEC-00:10 77.01 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 91.97 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 0.00   48.47  
Maximum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 29.04   104.20  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3094.06 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 549.97 11-JAN-24:00
February 26988.77 01-FEB-00:10 3094.06 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 513.85 17-FEB-07:00
March 26988.77 01-MAR-00:10 3094.06 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 452.20 08-MAR-07:00
April 26988.77 01-APR-00:10 3094.06 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 431.70 08-APR-06:00
May 26988.77 01-MAY-00:10 3094.06 01-MAY-19:19 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 396.99 06-MAY-05:00
June 26988.77 01-JUN-00:10 3094.06 01-JUN-19:30 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 47.22 13-JUN-17:00 325.82 08-JUN-00:50
July 26988.77 01-JUL-00:10 3094.06 17-JUL-19:30 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 94.82 22-JUL-18:00 313.52 05-JUL-05:20
August 26988.77 01-AUG-00:10 3094.06 01-AUG-19:40 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 47.34 14-AUG-17:00 290.28 20-AUG-05:03
September 26988.77 01-SEP-00:10 3094.06 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 339.50 21-SEP-06:00
October 26988.77 01-OCT-23:10 3094.06 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 393.12 07-OCT-04:00
November 26988.77 01-NOV-00:10 3094.06 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 478.48 29-NOV-02:00
December 26988.77 01-DEC-00:10 3094.06 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 491.22 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 0.00   290.28  
Maximum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 94.82   549.97  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3094.06 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 549.98 11-JAN-24:00
February 26988.77 01-FEB-00:10 3094.06 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 513.86 17-FEB-07:00
March 26988.77 01-MAR-00:10 3094.06 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 452.20 08-MAR-07:00
April 26988.77 01-APR-00:10 3094.06 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 431.70 08-APR-06:00
May 26988.77 01-MAY-00:10 3094.06 01-MAY-19:19 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 397.00 06-MAY-05:00
June 26988.77 01-JUN-00:10 3094.06 01-JUN-19:30 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 47.22 13-JUN-17:00 327.10 08-JUN-00:50
July 26988.77 01-JUL-00:10 3094.06 17-JUL-19:30 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 94.82 22-JUL-18:00 314.88 05-JUL-05:20
August 26988.77 01-AUG-00:10 3094.06 01-AUG-19:40 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 47.34 14-AUG-17:00 291.02 20-AUG-05:25
September 26988.77 01-SEP-00:10 3094.06 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 339.50 21-SEP-06:00
October 26988.77 01-OCT-23:10 3094.06 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 394.15 15-OCT-04:00
November 26988.77 01-NOV-00:10 3094.06 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 478.49 29-NOV-02:00
December 26988.77 01-DEC-00:10 3094.06 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 491.22 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 0.00   291.02  
Maximum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 94.82   549.98  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1089.83 02-JAN-20:10 14912.86 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 0.00 01-JAN-00:10 492.33 11-JAN-24:00
February 2401.70 01-FEB-00:10 1089.83 01-FEB-20:10 14912.86 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 0.00 01-FEB-00:03 459.94 17-FEB-07:00
March 2401.70 01-MAR-00:10 1089.83 01-MAR-20:10 14912.86 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 0.00 01-MAR-00:03 404.74 08-MAR-07:00
April 2401.70 01-APR-00:10 1089.83 03-APR-19:10 14912.86 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 0.00 01-APR-00:10 386.39 08-APR-06:00
May 2401.70 01-MAY-00:10 1089.83 01-MAY-19:10 14912.86 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 0.00 01-MAY-00:10 352.52 06-MAY-05:10
June 2401.70 01-JUN-00:10 1089.83 01-JUN-19:10 14912.86 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 42.45 13-JUN-17:00 306.51 08-JUN-06:00
July 2401.70 01-JUL-00:10 1089.83 03-JUL-19:10 14912.86 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 85.04 22-JUL-18:00 301.32 05-JUL-05:20
August 2401.70 01-AUG-00:10 1089.83 01-AUG-19:10 14912.86 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 42.57 14-AUG-17:00 279.10 20-AUG-05:25
September 2401.70 01-SEP-00:10 1089.83 01-SEP-19:10 14912.86 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 0.00 01-SEP-00:05 325.53 20-SEP-06:05
October 2401.70 01-OCT-23:10 1089.83 02-OCT-19:10 14912.86 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 0.00 01-OCT-00:10 348.70 06-OCT-07:30
November 2401.70 01-NOV-00:10 1089.83 01-NOV-19:10 14912.86 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 0.00 01-NOV-00:05 410.81 28-NOV-24:00
December 2401.70 01-DEC-00:10 1089.83 01-DEC-20:10 14912.86 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 0.00 01-DEC-00:03 439.64 29-DEC-21:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1089.83   14912.86   22492.83   0.00 0.00 0.00 0.00   279.10  
Maximum of Months 2401.70   1089.83   14912.86   22492.83   0.00 0.00 0.00 85.04   492.33  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 2371.52 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 433.96 11-JAN-24:00
February 2395.44 01-FEB-00:10 2371.52 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 402.27 17-FEB-07:00
March 2395.44 01-MAR-00:10 2371.52 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 348.95 08-MAR-07:00
April 2395.44 01-APR-00:10 2371.52 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 7.13 30-APR-18:00 331.27 08-APR-06:00
May 2395.44 01-MAY-00:10 2371.52 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 6.07 22-MAY-15:00 300.71 06-MAY-05:00
June 2395.44 01-JUN-00:10 2371.52 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 45.01 13-JUN-17:00 242.44 01-JUN-04:00
July 2395.44 01-JUL-00:10 2371.52 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 83.18 22-JUL-18:00 233.96 31-JUL-04:53
August 2395.44 01-AUG-00:10 2371.52 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 49.72 14-AUG-18:00 218.20 20-AUG-05:07
September 2395.44 01-SEP-00:10 2371.52 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 263.07 20-SEP-24:00
October 2395.44 01-OCT-23:10 2371.52 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 299.35 07-OCT-04:00
November 2395.44 01-NOV-00:10 2371.52 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 371.14 29-NOV-02:00
December 2395.44 01-DEC-00:10 2371.52 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 382.87 29-DEC-21:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   2371.52   0.00 0.00 0.00 0.00 0.00 0.00   218.20  
Maximum of Months 2395.44   2371.52   0.00 0.00 0.00 0.00 0.00 83.18   433.96  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 28175.20 13-JAN-21:59 102239.04 126092.96 95814.96 0.00 0.00 0.00 0.00 0.00 0.00
February 26187.20 02-FEB-21:47 102239.04 126092.96 95814.96 0.00 0.00 0.00 0.00 0.00 0.00
March 24764.20 01-MAR-21:25 20447.81 25218.59 19162.99 0.00 0.00 0.00 0.00 0.00 0.00
April 24537.54 24-APR-23:32 115018.92 31522.79 31938.32 0.00 0.00 0.00 0.00 0.00 0.00
May 23941.09 05-MAY-22:55 23003.78 9457.02 8516.89 0.00 0.00 0.00 0.00 0.00 0.00
June 21903.83 06-JUN-03:35 115018.92 15762.30 21292.21 0.00 0.00 0.00 0.00 0.00 0.00
July 22163.02 05-JUL-05:30 35783.66 25218.23 21292.21 0.00 0.00 0.00 0.00 0.00 0.00
August 21478.05 20-AUG-03:12 89459.16 31522.79 31938.32 0.00 0.00 0.00 0.00 0.00 0.00
September 33948.71 28-SEP-06:14 25559.76 39403.94 31938.32 0.00 0.00 0.00 0.00 0.00 0.00
October 35449.81 05-OCT-21:37 34505.68 28371.05 22356.82 0.00 0.00 0.00 0.00 0.00 0.00
November 36745.66 10-NOV-21:18 102239.04 126092.96 95814.96 0.00 0.00 0.00 0.00 0.00 0.00
December 36137.52 20-DEC-21:48 102239.04 126092.96 95814.96 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 21478.05   20447.81 9457.02 8516.89 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 36745.66   115018.92 126092.96 95814.96 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3770.88 20-JAN-11:57 779.69 587.01 757.77 0.00 0.00 0.00 0.00 0.00 187.88
February 4655.15 17-FEB-14:08 2598.96 1956.71 2525.91 0.00 0.00 0.00 0.00 0.00 221.81
March 3363.66 31-MAR-15:06 3248.70 978.35 1262.95 0.00 0.00 0.00 0.00 0.00 172.22
April 3856.22 29-APR-00:50 11695.32 1565.37 2165.06 0.00 0.00 0.00 0.00 0.00 173.35
May 3351.11 01-MAY-14:48 3898.44 1956.71 2525.91 0.00 0.00 0.00 0.00 0.00 169.46
June 2835.36 13-JUN-10:33 779.69 587.01 757.77 0.00 0.00 0.00 0.00 0.00 5.51
July 3336.64 22-JUL-13:30 389.84 195.67 252.59 0.00 0.00 0.00 0.00 45.75 0.00
August 3367.57 19-AUG-13:10 389.84 195.67 252.59 0.00 0.00 0.00 0.00 0.00 39.32
September 4190.13 27-SEP-13:20 259.90 195.67 252.59 0.00 0.00 0.00 0.00 0.00 31.27
October 3786.37 07-OCT-13:10 389.84 195.67 252.59 0.00 0.00 0.00 0.00 0.00 83.31
November 3611.14 11-NOV-12:37 3898.44 2348.05 2886.75 0.00 0.00 0.00 0.00 0.00 182.28
December 3647.56 18-DEC-12:07 779.69 587.01 757.77 0.00 0.00 0.00 0.00 0.00 183.38
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2835.36   259.90 195.67 252.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4655.15   11695.32 2348.05 2886.75 0.00 0.00 0.00 0.00 45.75 221.81



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1924.68 19-JAN-01:35 2708.64 271.91 417.86 0.00 0.00 0.00 0.00 0.00 71.82
February 2007.14 17-FEB-14:08 3009.60 2265.88 2925.01 0.00 0.00 0.00 0.00 0.00 75.35
March 1999.81 23-MAR-06:25 4815.36 3625.40 4011.44 0.00 0.00 0.00 0.00 0.00 74.00
April 2319.01 29-APR-00:50 13543.20 1812.70 2507.15 0.00 0.00 0.00 0.00 0.00 78.68
May 2184.62 05-MAY-22:55 2708.64 543.81 668.57 0.00 0.00 0.00 0.00 0.00 86.66
June 2006.17 06-JUN-03:35 13543.20 906.35 1671.43 0.00 0.00 0.00 0.00 0.00 68.70
July 1990.06 05-JUL-01:38 13543.20 906.35 1671.43 0.00 0.00 0.00 0.00 0.00 68.38
August 1984.25 20-AUG-03:12 10533.60 1812.70 2507.15 0.00 0.00 0.00 0.00 0.00 67.19
September 2649.00 30-SEP-22:15 2106.72 543.81 668.57 0.00 0.00 0.00 0.00 0.00 74.47
October 2636.07 05-OCT-21:18 6771.60 2719.05 2925.01 0.00 0.00 0.00 0.00 0.00 88.11
November 1894.04 06-NOV-07:29 6019.20 4531.75 5014.30 0.00 0.00 0.00 0.00 0.00 71.02
December 1929.74 12-DEC-11:57 902.88 679.76 877.50 0.00 0.00 0.00 0.00 0.00 71.90
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1894.04   902.88 271.91 417.86 0.00 0.00 0.00 0.00 0.00 67.19
Maximum of Months 2649.00   13543.20 4531.75 5014.30 0.00 0.00 0.00 0.00 0.00 88.11



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1584.20 28-JAN-08:04 1591.20 6046.21 4418.14 0.00 0.00 0.00 0.00 0.00 157.50
February 1486.92 01-FEB-18:50 1591.20 9069.31 6185.40 0.00 0.00 0.00 0.00 0.00 169.75
March 1660.59 23-MAR-06:25 1018.37 6046.21 4241.42 0.00 0.00 0.00 0.00 0.00 164.92
April 1919.43 29-APR-00:50 2864.16 3023.10 2650.88 0.00 0.00 0.00 0.00 0.00 174.19
May 1825.91 05-MAY-22:55 572.83 906.93 706.90 0.00 0.00 0.00 0.00 0.00 195.00
June 1699.86 06-JUN-03:35 2864.16 1511.55 1767.26 0.00 0.00 0.00 0.00 0.00 155.36
July 1724.87 27-JUL-02:00 1432.08 755.78 883.63 0.00 0.00 0.00 0.00 0.00 154.54
August 1715.59 20-AUG-03:12 2227.68 3023.10 2650.88 0.00 0.00 0.00 0.00 0.00 154.80
September 1775.70 28-SEP-04:57 2004.91 2116.17 1855.62 0.00 0.00 0.00 0.00 0.00 162.80
October 1830.69 01-OCT-00:47 668.30 1360.40 1060.35 0.00 0.00 0.00 0.00 0.00 168.32
November 1566.38 06-NOV-07:29 1272.96 7557.76 5301.77 0.00 0.00 0.00 0.00 0.00 158.00
December 1383.74 05-DEC-19:04 2227.68 12092.41 7952.65 0.00 0.00 0.00 0.00 0.00 165.50
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1383.74   572.83 755.78 706.90 0.00 0.00 0.00 0.00 0.00 154.54
Maximum of Months 1919.43   2864.16 12092.41 7952.65 0.00 0.00 0.00 0.00 0.00 195.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 736.55 19-JAN-01:35 440.64 75.91 127.45 0.00 0.00 0.00 0.00 0.00 89.72
February 653.04 04-FEB-15:12 734.40 632.58 892.16 0.00 0.00 0.00 0.00 0.00 82.01
March 768.72 23-MAR-06:25 783.36 1012.07 1223.53 0.00 0.00 0.00 0.00 0.00 92.65
April 902.70 29-APR-00:50 2203.20 506.04 764.71 0.00 0.00 0.00 0.00 0.00 99.09
May 847.84 05-MAY-22:55 440.64 151.81 203.92 0.00 0.00 0.00 0.00 0.00 110.00
June 802.96 06-JUN-03:35 2203.20 253.02 509.80 0.00 0.00 0.00 0.00 0.00 88.73
July 814.37 27-JUL-02:00 1101.60 126.51 254.90 0.00 0.00 0.00 0.00 0.00 88.21
August 805.95 20-AUG-03:12 1713.60 506.04 764.71 0.00 0.00 0.00 0.00 0.00 87.96
September 839.08 28-SEP-04:57 1542.24 354.23 535.30 0.00 0.00 0.00 0.00 0.00 93.02
October 856.93 01-OCT-00:47 514.08 227.72 305.88 0.00 0.00 0.00 0.00 0.00 95.35
November 729.47 06-NOV-07:29 979.20 1265.09 1529.41 0.00 0.00 0.00 0.00 0.00 89.27
December 593.75 22-DEC-18:52 734.40 910.87 1070.59 0.00 0.00 0.00 0.00 0.00 104.35
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 593.75   440.64 75.91 127.45 0.00 0.00 0.00 0.00 0.00 82.01
Maximum of Months 902.70   2203.20 1265.09 1529.41 0.00 0.00 0.00 0.00 0.00 110.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 50312.93 30-JAN-21:43 5644.80 2222.66 30324.89 263449.93 0.00 0.00 0.00 0.00 316.97
February 50854.25 21-FEB-21:53 8064.00 3175.23 43321.27 376357.04 0.00 0.00 0.00 0.00 321.00
March 51529.43 31-MAR-20:45 4838.40 1905.14 25992.76 225814.22 0.00 0.00 0.00 0.00 302.45
April 50079.03 19-APR-20:53 8064.00 3175.23 43321.27 376357.04 0.00 0.00 0.00 0.00 294.29
May 48637.91 10-MAY-21:07 9072.00 2381.43 33694.32 292722.14 0.00 0.00 0.00 0.00 278.68
June 39721.32 06-JUN-20:03 3225.60 1270.09 17328.51 150542.82 0.00 0.00 0.00 0.00 227.74
July 40315.92 04-JUL-21:55 8064.00 1984.52 28880.85 250904.69 0.00 0.00 0.00 0.00 233.59
August 38262.26 14-AUG-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 48.40
September 47885.56 30-SEP-20:38 4233.60 1667.00 23104.68 200723.75 0.00 0.00 0.00 0.00 261.57
October 51386.22 05-OCT-20:48 8064.00 3175.23 43321.27 376357.04 0.00 0.00 0.00 0.00 306.97
November 51744.82 20-NOV-21:28 4838.40 1905.14 25992.76 225814.22 0.00 0.00 0.00 0.00 332.21
December 51269.38 20-DEC-21:44 8064.00 3175.23 43321.27 376357.04 0.00 0.00 0.00 0.00 305.93
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 38262.26   705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 48.40
Maximum of Months 51744.82   9072.00 3175.23 43321.27 376357.04 0.00 0.00 0.00 0.00 332.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 16661.27 07-JAN-13:41 35859.60 2089.82 2489.39 0.00 0.00 0.00 0.00 0.00 458.56
February 19486.84 04-FEB-15:15 51228.00 2985.45 3556.27 0.00 0.00 0.00 0.00 0.00 421.71
March 13876.52 31-MAR-15:06 42690.00 1492.73 1778.13 0.00 0.00 0.00 0.00 0.00 400.16
April 17337.07 29-APR-00:50 153684.00 3915.35 3048.23 0.00 0.00 0.00 0.00 0.00 438.64
May 16275.13 12-MAY-03:13 46105.20 587.30 609.65 0.00 0.00 0.00 0.00 0.00 420.94
June 14882.16 06-JUN-03:35 153684.00 1957.67 2032.15 0.00 0.00 0.00 0.00 0.00 380.28
July 15002.88 05-JUL-01:38 153684.00 1957.67 2032.15 0.00 0.00 0.00 0.00 0.00 384.36
August 14167.98 28-AUG-03:46 153684.00 1957.67 2032.15 0.00 0.00 0.00 0.00 0.00 369.48
September 22907.87 08-SEP-04:03 61473.60 1566.14 1219.29 0.00 0.00 0.00 0.00 0.00 415.11
October 15756.77 03-OCT-00:43 46105.20 880.95 762.06 0.00 0.00 0.00 0.00 0.00 401.48
November 14179.91 11-NOV-12:40 51228.00 3582.54 4064.31 0.00 0.00 0.00 0.00 0.00 405.00
December 14775.52 12-DEC-11:57 10245.60 895.64 1066.88 0.00 0.00 0.00 0.00 0.00 410.40
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 13876.52   10245.60 587.30 609.65 0.00 0.00 0.00 0.00 0.00 369.48
Maximum of Months 22907.87   153684.00 3915.35 4064.31 0.00 0.00 0.00 0.00 0.00 458.56



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 74169.69 19-JAN-01:35 91245.96 3421.73 5278.53 0.00 0.00 0.00 0.00 0.00 1180.24
February 44745.90 17-FEB-14:08 101384.40 26518.39 36949.72 0.00 0.00 0.00 0.00 0.00 1292.64
March 43491.33 23-MAR-06:25 162215.04 45623.04 50673.90 0.00 0.00 0.00 0.00 0.00 1241.53
April 62016.86 13-APR-21:26 456229.80 68434.56 73899.43 0.00 0.00 0.00 0.00 0.00 1378.69
May 68300.52 10-MAY-21:07 456229.80 68434.56 73899.43 0.00 0.00 0.00 0.00 0.00 1331.97
June 56982.89 16-JUN-23:56 228114.90 11405.76 15835.59 0.00 0.00 0.00 0.00 0.00 1162.20
July 53843.22 31-JUL-04:45 182491.92 9124.61 12668.47 0.00 0.00 0.00 0.00 0.00 1306.20
August 42795.91 20-AUG-03:12 354845.40 22811.52 31671.19 0.00 0.00 0.00 0.00 0.00 1120.58
September 63689.13 20-SEP-22:54 456229.80 34217.28 42228.25 0.00 0.00 0.00 0.00 0.00 1334.75
October 68543.31 04-OCT-21:34 456229.80 68434.56 73899.43 0.00 0.00 0.00 0.00 0.00 1392.75
November 69572.47 09-NOV-05:35 91245.96 4562.30 6334.24 0.00 0.00 0.00 0.00 0.00 1027.78
December 42068.87 12-DEC-11:57 30415.32 7955.52 11084.92 0.00 0.00 0.00 0.00 0.00 1209.17
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 42068.87   30415.32 3421.73 5278.53 0.00 0.00 0.00 0.00 0.00 1027.78
Maximum of Months 74169.69   456229.80 68434.56 73899.43 0.00 0.00 0.00 0.00 0.00 1392.75



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2877.49 19-JAN-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 102.08
February 3142.83 17-FEB-16:01 972.00 343.01 684.84 0.00 0.00 0.00 0.00 0.00 122.60
March 2875.44 23-MAR-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 0.00 101.36
April 3221.54 27-APR-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 30.97
May 3244.67 21-MAY-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 0.00 26.48
June 3206.65 12-JUN-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 19.38 0.00
July 3157.19 05-JUL-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 0.00 32.50
August 3220.61 24-AUG-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 15.77
September 3115.83 29-SEP-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 0.00 48.27
October 3234.49 07-OCT-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 0.00 26.07
November 3039.76 03-NOV-15:01 972.00 343.01 684.84 0.00 0.00 0.00 0.00 0.00 97.94
December 684.35 05-DEC-19:04 1386.00 1090.30 1290.65 0.00 0.00 0.00 0.00 0.00 105.19
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 684.35   324.00 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3244.67   1386.00 1090.30 1290.65 0.00 0.00 0.00 0.00 19.38 122.60



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 879.71 19-JAN-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 97.04
February 2478.44 17-FEB-16:01 972.00 342.97 684.76 0.00 0.00 0.00 0.00 0.00 111.31
March 2534.98 23-MAR-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 0.00 99.83
April 2862.84 27-APR-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 30.63
May 2899.65 21-MAY-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 26.46
June 3011.93 13-JUN-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 3.06 0.00
July 2868.90 09-JUL-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 11.75
August 2893.35 17-AUG-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 6.15
September 2896.60 24-SEP-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 4.52
October 2853.93 07-OCT-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 25.30
November 1152.31 10-NOV-16:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 77.09
December 553.09 02-DEC-09:04 540.00 685.95 1632.88 0.00 0.00 0.00 0.00 0.00 101.40
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 553.09   324.00 205.78 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3011.93   972.00 685.95 1632.88 0.00 0.00 0.00 0.00 3.06 111.31



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 359.62 21-JAN-11:30 0.00 50.81 149.63 0.00 0.00 0.00 0.00 0.00 34.96
February 305.27 04-FEB-14:40 0.00 25.41 74.82 0.00 0.00 0.00 0.00 0.00 28.53
March 85.25 25-MAR-11:50 0.00 50.81 149.63 0.00 0.00 0.00 0.00 0.00 19.62
April 656.37 30-APR-12:50 0.00 25.41 74.82 0.00 0.00 0.00 0.00 0.00 2.60
May 497.05 23-MAY-13:20 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 9.68
June 527.19 13-JUN-13:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 2.20 0.00
July 610.39 22-JUL-13:30 0.00 25.41 74.82 0.00 0.00 0.00 0.00 8.56 0.00
August 646.27 20-AUG-13:00 0.00 25.41 74.82 0.00 0.00 0.00 0.00 0.00 0.72
September 789.61 27-SEP-13:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 3.56
October 712.21 07-OCT-13:20 0.00 25.41 74.82 0.00 0.00 0.00 0.00 0.00 12.29
November 303.23 11-NOV-13:21 0.00 254.07 748.17 0.00 0.00 0.00 0.00 0.00 28.67
December 100.77 18-DEC-14:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 30.20
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 85.25   0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 789.61   0.00 254.07 748.17 0.00 0.00 0.00 0.00 8.56 34.96



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 550.11 29-JAN-09:02 270.00 215.63 799.99 0.00 0.00 0.00 0.00 0.00 20.14
February 434.63 11-FEB-19:03 1170.00 770.11 1264.50 0.00 0.00 0.00 0.00 0.00 32.59
March 635.92 25-MAR-08:62 324.00 258.76 959.99 0.00 0.00 0.00 0.00 0.00 25.74
April 772.36 29-APR-18:02 702.00 462.06 758.70 0.00 0.00 0.00 0.00 0.00 4.35
May 770.73 21-MAY-18:02 702.00 462.06 758.70 0.00 0.00 0.00 0.00 0.00 3.96
June 833.86 13-JUN-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 0.85 0.00
July 824.12 22-JUL-08:61 378.00 301.88 1119.99 0.00 0.00 0.00 0.00 2.29 0.00
August 806.22 14-AUG-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 5.92 0.00
September 773.49 13-SEP-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 2.36 0.00
October 676.78 15-OCT-08:61 540.00 431.26 1599.98 0.00 0.00 0.00 0.00 0.00 29.97
November 587.48 23-NOV-09:01 540.00 431.26 1599.98 0.00 0.00 0.00 0.00 0.00 26.51
December 381.24 06-DEC-19:04 970.20 479.78 885.15 0.00 0.00 0.00 0.00 0.00 36.73
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 381.24   270.00 129.38 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 833.86   1170.00 770.11 1599.98 0.00 0.00 0.00 0.00 5.92 36.73



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1131.38 21-JAN-16:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 0.00 111.62
February 2594.28 20-FEB-09:01 378.00 480.22 1143.15 0.00 0.00 0.00 0.00 0.00 132.08
March 1561.47 20-MAR-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 73.74
April 2900.94 14-APR-08:61 360.00 539.02 1132.61 0.00 0.00 0.00 0.00 0.00 98.51
May 2906.23 21-MAY-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 0.00 25.66
June 2990.55 12-JUN-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 20.98 0.00
July 2905.98 22-JUL-08:61 378.00 480.22 1143.15 0.00 0.00 0.00 0.00 7.24 0.00
August 2962.46 24-AUG-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 16.52
September 2866.54 11-SEP-08:62 216.00 323.41 679.57 0.00 0.00 0.00 0.00 0.00 31.56
October 2906.32 07-OCT-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 0.00 25.45
November 2541.59 03-NOV-15:01 972.00 343.01 684.84 0.00 0.00 0.00 0.00 0.00 90.52
December 856.07 20-DEC-09:04 252.00 377.32 792.83 0.00 0.00 0.00 0.00 0.00 112.27
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 856.07   216.00 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2990.55   972.00 654.18 1143.15 0.00 0.00 0.00 0.00 20.98 132.08



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 907.79 23-JAN-19:04 1108.80 872.14 1032.40 0.00 0.00 0.00 0.00 0.00 93.42
February 1097.36 20-FEB-09:01 378.00 480.16 1143.02 0.00 0.00 0.00 0.00 0.00 128.39
March 1034.03 21-MAR-18:03 1386.00 1090.18 1290.50 0.00 0.00 0.00 0.00 0.00 97.02
April 2616.98 14-APR-08:61 360.00 538.96 1132.48 0.00 0.00 0.00 0.00 0.00 98.62
May 2627.19 22-MAY-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 7.92 0.00
June 2733.41 13-JUN-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 22.65 0.00
July 2666.07 21-JUL-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 29.94 0.00
August 2746.68 14-AUG-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 17.08 0.00
September 2686.25 13-SEP-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 2.71 0.00
October 2462.11 07-OCT-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 20.08
November 917.78 19-NOV-09:03 378.00 480.16 1143.02 0.00 0.00 0.00 0.00 0.00 122.24
December 777.41 11-DEC-09:04 252.00 377.27 792.74 0.00 0.00 0.00 0.00 0.00 127.63
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 777.41   252.00 205.78 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2746.68   1386.00 1090.18 1290.50 0.00 0.00 0.00 0.00 29.94 128.39



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2793.03 19-JAN-01:35 4526.71 746.93 0.00 0.00 0.00 0.00 0.00 0.00 119.77
February 3114.71 17-FEB-14:08 5029.68 6224.39 0.00 0.00 0.00 0.00 0.00 0.00 132.91
March 2891.36 23-MAR-06:25 8047.49 9959.03 0.00 0.00 0.00 0.00 0.00 0.00 122.82
April 3518.88 29-APR-00:50 22633.56 4979.51 0.00 0.00 0.00 0.00 0.00 0.00 135.61
May 3312.70 05-MAY-22:55 4526.71 1493.85 0.00 0.00 0.00 0.00 0.00 0.00 150.35
June 3090.04 06-JUN-03:35 22633.56 2489.76 0.00 0.00 0.00 0.00 0.00 0.00 120.05
July 3156.56 27-JUL-02:00 11316.78 1244.88 0.00 0.00 0.00 0.00 0.00 0.00 120.15
August 3116.69 20-AUG-03:12 17603.88 4979.51 0.00 0.00 0.00 0.00 0.00 0.00 119.58
September 3268.02 28-SEP-04:57 15843.49 3485.66 0.00 0.00 0.00 0.00 0.00 0.00 127.19
October 3339.09 01-OCT-00:47 5281.16 2240.78 0.00 0.00 0.00 0.00 0.00 0.00 130.47
November 2723.75 06-NOV-07:29 10059.36 12448.79 0.00 0.00 0.00 0.00 0.00 0.00 117.64
December 2744.01 12-DEC-11:57 1508.90 1867.32 0.00 0.00 0.00 0.00 0.00 0.00 128.85
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2723.75   1508.90 746.93 0.00 0.00 0.00 0.00 0.00 0.00 117.64
Maximum of Months 3518.88   22633.56 12448.79 0.00 0.00 0.00 0.00 0.00 0.00 150.35



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3023.14 19-JAN-16:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 102.73
February 3292.36 17-FEB-16:01 972.00 343.01 684.84 0.00 0.00 0.00 0.00 0.00 122.90
March 3058.73 23-MAR-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 0.00 103.13
April 3391.01 27-APR-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 31.53
May 3410.57 21-MAY-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 0.00 26.97
June 3447.29 13-JUN-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 3.03 0.00
July 3307.93 05-JUL-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 0.00 32.80
August 3374.70 24-AUG-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 16.08
September 3258.72 20-SEP-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 45.28
October 3392.09 07-OCT-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 0.00 26.42
November 3140.60 03-NOV-15:01 972.00 343.01 684.84 0.00 0.00 0.00 0.00 0.00 97.00
December 677.43 05-DEC-19:04 1386.00 1090.30 1290.65 0.00 0.00 0.00 0.00 0.00 105.63
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 677.43   324.00 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3447.29   1386.00 1090.30 1290.65 0.00 0.00 0.00 0.00 3.03 122.90



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 891.50 21-JAN-16:03 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 111.95
February 1878.23 27-FEB-16:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 0.00 98.48
March 2657.31 23-MAR-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 0.00 101.00
April 2986.16 27-APR-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 31.15
May 3022.48 21-MAY-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 26.95
June 3120.31 13-JUN-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 2.39 0.00
July 2981.41 22-JUL-18:02 702.00 734.94 774.30 0.00 0.00 0.00 0.00 44.66 0.00
August 2998.13 24-AUG-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 16.18
September 3003.72 24-SEP-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 4.79
October 2956.44 07-OCT-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 25.42
November 1303.72 03-NOV-15:02 972.00 342.97 684.76 0.00 0.00 0.00 0.00 0.00 89.74
December 823.18 05-DEC-19:04 1386.00 1090.18 1290.50 0.00 0.00 0.00 0.00 0.00 105.62
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 823.18   324.00 205.78 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3120.31   1386.00 1090.18 1290.50 0.00 0.00 0.00 0.00 44.66 111.95



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1983.28 21-JAN-16:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 0.00 62.29
February 2067.55 17-FEB-16:01 972.00 215.63 670.96 0.00 0.00 0.00 0.00 0.00 63.31
March 1952.76 20-MAR-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 0.00 42.30
April 2089.03 27-APR-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 0.00 15.94
May 2077.93 21-MAY-15:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 0.00 13.25
June 2110.01 12-JUN-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 10.85 0.00
July 2123.00 22-JUL-08:61 378.00 301.88 1119.99 0.00 0.00 0.00 0.00 5.27 0.00
August 2041.57 10-AUG-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 0.00 6.68
September 2147.90 12-SEP-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 0.00 3.69
October 2127.90 07-OCT-15:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 0.00 13.86
November 2061.89 03-NOV-15:01 972.00 215.63 670.96 0.00 0.00 0.00 0.00 0.00 52.15
December 1906.45 18-DEC-16:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 0.00 62.61
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1906.45   324.00 129.38 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2147.90   972.00 411.24 1119.99 0.00 0.00 0.00 0.00 10.85 63.31



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 31343.26 27-JAN-23:35 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 331.09
February 31266.83 14-FEB-23:39 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 323.29
March 31551.97 24-MAR-22:39 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 324.88
April 38067.31 29-APR-00:50 269887.68 6875.68 22493.01 0.00 0.00 0.00 0.00 0.00 288.76
May 34469.23 05-MAY-22:55 53977.54 2062.70 13495.81 0.00 0.00 0.00 0.00 0.00 310.21
June 31655.18 08-JUN-01:09 269887.68 3437.84 22493.01 0.00 0.00 0.00 0.00 0.00 300.78
July 30298.90 15-JUL-04:45 107955.07 1191.78 8997.20 0.00 0.00 0.00 0.00 0.00 285.79
August 29636.30 05-AUG-04:10 134943.84 1718.92 11246.50 0.00 0.00 0.00 0.00 0.00 265.16
September 31601.80 08-SEP-03:44 269887.68 3437.84 22493.01 0.00 0.00 0.00 0.00 0.00 296.92
October 36710.46 05-OCT-22:52 215910.14 8250.81 53983.22 0.00 0.00 0.00 0.00 0.00 309.48
November 30865.44 10-NOV-21:18 239900.16 27502.72 67479.03 0.00 0.00 0.00 0.00 0.00 364.11
December 30336.03 20-DEC-21:48 239900.16 27502.72 67479.03 0.00 0.00 0.00 0.00 0.00 330.54
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 29636.30   53977.54 1191.78 8997.20 0.00 0.00 0.00 0.00 0.00 265.16
Maximum of Months 38067.31   269887.68 27502.72 67479.03 0.00 0.00 0.00 0.00 0.00 364.11



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 32967.77 27-JAN-23:35 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 332.05
February 32884.03 14-FEB-23:39 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 324.22
March 33204.75 24-MAR-22:39 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 325.93
April 40910.38 29-APR-00:50 269887.68 6875.68 22493.01 0.00 0.00 0.00 0.00 0.00 288.10
May 37755.41 05-MAY-22:55 53977.54 2062.70 13495.81 0.00 0.00 0.00 0.00 0.00 308.51
June 33293.08 08-JUN-01:09 269887.68 3437.84 22493.01 0.00 0.00 0.00 0.00 0.00 301.70
July 31859.37 31-JUL-04:45 107955.07 2750.27 8997.20 0.00 0.00 0.00 0.00 0.00 303.14
August 31087.71 05-AUG-04:10 134943.84 1718.92 11246.50 0.00 0.00 0.00 0.00 0.00 265.47
September 33192.19 08-SEP-03:44 269887.68 3437.84 22493.01 0.00 0.00 0.00 0.00 0.00 297.54
October 40878.38 22-OCT-21:19 167930.11 12032.44 47235.32 0.00 0.00 0.00 0.00 0.00 321.53
November 32424.60 10-NOV-21:18 239900.16 27502.72 67479.03 0.00 0.00 0.00 0.00 0.00 364.80
December 32045.47 19-DEC-21:48 239900.16 27502.72 67479.03 0.00 0.00 0.00 0.00 0.00 331.61
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 31087.71   53977.54 1718.92 8997.20 0.00 0.00 0.00 0.00 0.00 265.47
Maximum of Months 40910.38   269887.68 27502.72 67479.03 0.00 0.00 0.00 0.00 0.00 364.80



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 35751.33 01-JAN-11:37 2401.70 1089.83 44738.57 56232.08 0.00 0.00 0.00 0.00 357.87
February 36684.09 25-FEB-11:37 8005.68 3027.31 149128.56 187440.26 0.00 0.00 0.00 0.00 298.93
March 36236.90 02-MAR-18:03 8005.68 4359.32 89477.13 134956.99 0.00 0.00 0.00 0.00 309.42
April 35685.57 07-APR-06:41 7471.97 4238.23 104389.99 78724.91 0.00 0.00 0.00 0.00 285.68
May 35385.19 02-MAY-06:32 10674.24 6054.62 149128.56 112464.16 0.00 0.00 0.00 0.00 307.35
June 34079.41 11-JUN-22:40 10674.24 1816.39 74564.28 18744.03 0.00 0.00 0.00 0.00 246.44
July 32233.43 31-JUL-05:44 18679.92 4843.69 125511.30 74976.11 0.00 0.00 0.00 0.00 234.30
August 31495.12 24-AUG-05:17 18679.92 4843.69 125511.30 74976.11 0.00 0.00 0.00 0.00 244.77
September 34400.47 30-SEP-19:10 8005.68 4238.23 74564.28 74976.11 0.00 0.00 0.00 0.00 285.97
October 38778.44 22-OCT-21:19 14943.94 4238.23 104389.99 52483.27 0.00 0.00 0.00 0.00 292.57
November 36655.52 21-NOV-16:06 9339.96 2119.12 104389.99 157449.82 0.00 0.00 0.00 0.00 248.34
December 37372.12 24-DEC-19:06 11207.95 5933.52 104389.99 104966.55 0.00 0.00 0.00 0.00 292.09
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 31495.12   2401.70 1089.83 44738.57 18744.03 0.00 0.00 0.00 0.00 234.30
Maximum of Months 38778.44   18679.92 6054.62 149128.56 187440.26 0.00 0.00 0.00 0.00 357.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5863.41 21-JAN-14:40 7984.80 6587.56 0.00 0.00 0.00 0.00 0.00 0.00 211.76
February 6793.11 17-FEB-14:08 5323.20 6587.56 0.00 0.00 0.00 0.00 0.00 0.00 242.37
March 6074.22 23-MAR-06:25 8517.12 10540.09 0.00 0.00 0.00 0.00 0.00 0.00 217.07
April 7258.17 29-APR-00:50 23954.40 5270.05 0.00 0.00 0.00 0.00 0.00 0.00 235.36
May 6651.92 05-MAY-22:55 4790.88 1581.01 0.00 0.00 0.00 0.00 0.00 0.00 256.06
June 6243.70 01-JUN-01:22 11977.20 1317.51 0.00 0.00 0.00 0.00 0.00 0.00 210.28
July 6316.07 27-JUL-02:00 11977.20 1317.51 0.00 0.00 0.00 0.00 0.00 0.00 202.84
August 6275.05 20-AUG-03:12 18631.20 5270.05 0.00 0.00 0.00 0.00 0.00 0.00 203.05
September 6484.89 28-SEP-04:57 16768.08 3689.03 0.00 0.00 0.00 0.00 0.00 0.00 213.20
October 6625.61 01-OCT-00:47 5589.36 2371.52 0.00 0.00 0.00 0.00 0.00 0.00 218.64
November 5402.27 15-NOV-17:06 13308.00 6587.56 0.00 0.00 0.00 0.00 0.00 0.00 203.79
December 5439.93 18-DEC-12:07 1596.96 1976.27 0.00 0.00 0.00 0.00 0.00 0.00 203.72
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 5402.27   1596.96 1317.51 0.00 0.00 0.00 0.00 0.00 0.00 202.84
Maximum of Months 7258.17   23954.40 10540.09 0.00 0.00 0.00 0.00 0.00 0.00 256.06



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.383484E+12 244361.40 30-JAN-20:49 0.548396E+12 531106.15 06-JAN-18:40
February 0.345213E+12 243790.03 27-FEB-20:00 0.479619E+12 510658.04 11-FEB-18:00
March 0.377589E+12 245886.58 23-MAR-19:19 0.524712E+12 504995.92 05-MAR-18:30
April 0.383767E+12 297131.56 30-APR-19:19 0.462802E+12 488068.09 25-APR-20:49
May 0.394436E+12 279537.74 22-MAY-19:49 0.481406E+12 475229.24 08-MAY-20:30
June 0.397356E+12 321534.90 12-JUN-18:10 0.435127E+12 389384.08 07-JUN-20:19
July 0.427151E+12 326774.97 22-JUL-18:19 0.434935E+12 354326.16 04-JUL-20:49
August 0.434471E+12 313562.68 14-AUG-18:10 0.428311E+12 351322.06 01-AUG-17:10
September 0.404338E+12 287485.46 11-SEP-19:10 0.430969E+12 385657.68 20-SEP-19:00
October 0.386420E+12 256712.79 05-OCT-19:10 0.498587E+12 452910.76 21-OCT-18:49
November 0.369232E+12 244854.10 09-NOV-20:00 0.520052E+12 502569.38 30-NOV-18:00
December 0.384542E+12 241704.02 11-DEC-20:10 0.564084E+12 493397.88 07-DEC-19:49
             
Annual Sum or Average 0.468800E+13     0.580900E+13    
Minimum of Months 0.345213E+12 241704.02   0.428311E+12 351322.06  
Maximum of Months 0.434471E+12 326774.97   0.564084E+12 531106.15  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.656005E+11 0.264816E+11 0.148212E+12 0.553311E+11 0.431450E+11 0.441400E+10 0.00 0.181212E+10 0.00 0.00 0.255457E+11 0.770472E+10 0.00
February 0.590822E+11 0.217915E+11 0.133859E+12 0.499765E+11 0.389030E+11 0.453583E+10 0.00 0.195837E+10 0.00 0.00 0.234101E+11 0.696225E+10 0.00
March 0.652499E+11 0.212076E+11 0.148223E+12 0.553338E+11 0.433561E+11 0.439559E+10 0.00 0.183772E+10 0.00 0.00 0.250307E+11 0.770311E+10 0.00
April 0.627738E+11 0.175741E+11 0.143397E+12 0.535454E+11 0.441575E+11 0.941924E+10 0.00 0.198249E+11 0.00 0.00 0.205386E+11 0.746498E+10 0.00
May 0.646465E+11 0.155720E+11 0.148223E+12 0.553317E+11 0.462714E+11 0.105108E+11 0.00 0.212741E+11 0.00 0.00 0.196205E+11 0.770444E+10 0.00
June 0.624155E+11 0.136904E+11 0.143446E+12 0.535478E+11 0.462504E+11 0.124880E+11 0.00 0.408216E+11 0.00 0.00 0.121037E+11 0.745699E+10 0.00
July 0.644555E+11 0.147563E+11 0.148174E+12 0.553287E+11 0.486114E+11 0.140689E+11 0.00 0.597735E+11 0.00 0.00 0.898309E+10 0.771275E+10 0.00
August 0.648513E+11 0.170087E+11 0.148234E+12 0.553334E+11 0.484627E+11 0.145974E+11 0.00 0.660302E+11 0.00 0.00 0.693520E+10 0.770451E+10 0.00
September 0.629771E+11 0.192425E+11 0.143408E+12 0.535457E+11 0.464391E+11 0.127416E+11 0.00 0.430694E+11 0.00 0.00 0.103221E+11 0.746656E+10 0.00
October 0.653931E+11 0.229131E+11 0.148201E+12 0.553308E+11 0.449572E+11 0.696348E+10 0.00 0.887147E+10 0.00 0.00 0.208012E+11 0.770305E+10 0.00
November 0.635026E+11 0.248225E+11 0.143462E+12 0.535470E+11 0.427403E+11 0.401031E+10 0.00 0.163283E+10 0.00 0.00 0.229776E+11 0.744899E+10 0.00
December 0.656257E+11 0.271954E+11 0.148174E+12 0.553298E+11 0.439758E+11 0.417548E+10 0.00 0.120170E+10 0.00 0.00 0.259178E+11 0.771290E+10 0.00
                           
Annual Sum or Average 0.766574E+12 0.242256E+12 0.174501E+13 0.651482E+12 0.537270E+12 0.102321E+12 0.00 0.268108E+12 0.00 0.00 0.222186E+12 0.907452E+11 0.00
Minimum of Months 0.590822E+11 0.136904E+11 0.133859E+12 0.499765E+11 0.389030E+11 0.401031E+10 0.00 0.120170E+10 0.00 0.00 0.693520E+10 0.696225E+10 0.00
Maximum of Months 0.656257E+11 0.271954E+11 0.148234E+12 0.553338E+11 0.486114E+11 0.145974E+11 0.00 0.660302E+11 0.00 0.00 0.259178E+11 0.771290E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.111858E+12 0.00 0.284620E+12 0.00 0.00
February 0.137204E+12 0.00 0.841144E+11 0.00 0.258301E+12 0.00 0.00
March 0.152024E+12 0.00 0.879373E+11 0.00 0.284751E+12 0.00 0.00
April 0.146956E+12 0.00 0.438820E+11 0.00 0.271964E+12 0.00 0.00
May 0.151978E+12 0.00 0.534315E+11 0.00 0.275996E+12 0.00 0.00
June 0.147114E+12 0.00 0.257947E+11 0.00 0.262219E+12 0.00 0.00
July 0.151820E+12 0.00 0.159868E+11 0.00 0.267128E+12 0.00 0.00
August 0.152039E+12 0.00 0.104763E+11 0.00 0.265796E+12 0.00 0.00
September 0.146971E+12 0.00 0.255301E+11 0.00 0.258468E+12 0.00 0.00
October 0.151903E+12 0.00 0.759046E+11 0.00 0.270779E+12 0.00 0.00
November 0.147091E+12 0.00 0.106047E+12 0.00 0.266914E+12 0.00 0.00
December 0.151820E+12 0.00 0.131368E+12 0.00 0.280896E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.772330E+12 0.00 0.324783E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 0.104763E+11 0.00 0.258301E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.131368E+12 0.00 0.284751E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 62892.57 02-JAN-20:10 15448.40 01-JAN-00:10 89475.41 02-JAN-07:10 39726.11 02-JAN-07:19 32266.91 27-JAN-22:40 4997.37 20-JAN-12:50 0.00 01-JAN-00:10
February 62892.57 01-FEB-20:10 15448.40 01-FEB-00:10 89475.41 01-FEB-07:10 39726.11 01-FEB-07:19 29995.31 02-FEB-21:40 5056.56 19-FEB-14:30 0.00 01-FEB-00:10
March 62892.57 01-MAR-20:10 15448.40 01-MAR-00:10 89475.41 01-MAR-07:10 39726.11 01-MAR-07:19 37738.84 24-MAR-21:19 4625.57 20-MAR-16:30 0.00 01-MAR-00:10
April 62892.57 03-APR-19:10 15448.40 01-APR-00:10 89475.41 03-APR-06:10 39726.11 10-APR-06:19 43740.55 07-APR-19:49 7320.56 28-APR-15:20 0.00 01-APR-00:10
May 62892.57 01-MAY-19:19 15448.40 01-MAY-00:10 89475.41 01-MAY-06:10 39724.77 01-MAY-06:19 38823.51 15-MAY-22:30 7257.67 21-MAY-18:10 0.00 01-MAY-00:10
June 62892.57 01-JUN-19:30 15448.40 01-JUN-00:10 89475.41 01-JUN-06:10 39724.33 01-JUN-06:19 30885.58 13-JUN-21:10 7592.53 25-JUN-18:10 0.00 01-JUN-00:10
July 62892.57 17-JUL-19:30 15448.40 01-JUL-00:10 89475.41 03-JUL-06:10 39724.33 03-JUL-06:19 30952.17 21-JUL-21:10 7410.62 22-JUL-18:10 0.00 01-JUL-00:10
August 62892.57 01-AUG-19:40 15448.40 01-AUG-00:10 89475.41 01-AUG-06:10 39725.67 15-AUG-06:19 31620.87 14-AUG-21:10 7525.70 14-AUG-18:10 0.00 01-AUG-00:10
September 62892.57 01-SEP-19:10 15448.40 01-SEP-00:10 89475.41 01-SEP-06:10 39726.11 18-SEP-06:19 32677.68 21-SEP-21:00 7400.59 25-SEP-16:30 0.00 01-SEP-00:10
October 62892.57 02-OCT-19:10 15448.40 01-OCT-00:10 89475.41 02-OCT-06:10 39726.11 02-OCT-06:19 37009.90 04-OCT-20:30 6558.72 07-OCT-15:09 0.00 01-OCT-00:10
November 62892.57 01-NOV-19:10 15448.40 01-NOV-00:10 89475.41 01-NOV-06:10 39726.11 01-NOV-06:19 31668.53 17-NOV-21:00 4817.16 11-NOV-13:30 0.00 01-NOV-00:10
December 62892.57 01-DEC-20:10 15448.40 01-DEC-00:10 89475.41 01-DEC-07:10 39726.11 01-DEC-07:19 29488.99 23-DEC-21:19 4412.30 18-DEC-10:50 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 62892.57   15448.40   89475.41   39724.33   29488.99   4412.30   0.00  
Maximum of Months 62892.57   15448.40   89475.41   39726.11   43740.55   7592.53   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 9395.03 21-JAN-10:00 0.00 0.00 9938.94 01-JAN-00:10 4738.32 24-JAN-19:00 0.00
February 10594.58 19-FEB-16:10 0.00 0.00 9938.94 01-FEB-00:20 4738.37 10-FEB-19:10 0.00
March 7724.17 20-MAR-18:10 0.00 0.00 9938.94 01-MAR-00:20 4738.48 09-MAR-07:19 0.00
April 85429.96 30-APR-18:10 0.00 0.00 9938.94 01-APR-00:10 4738.42 19-APR-18:10 0.00
May 81844.89 22-MAY-15:09 0.00 0.00 9938.94 01-MAY-00:10 4738.32 10-MAY-18:19 0.00
June 115118.69 25-JUN-18:10 0.00 0.00 9938.94 01-JUN-00:20 4738.32 05-JUN-18:10 0.00
July 117506.15 22-JUL-18:19 0.00 0.00 9938.94 01-JUL-00:10 4738.33 24-JUL-06:10 0.00
August 98398.49 14-AUG-18:10 0.00 0.00 9938.94 01-AUG-00:10 4738.16 28-AUG-18:10 0.00
September 82569.94 13-SEP-15:09 0.00 0.00 9938.94 01-SEP-00:10 4738.47 21-SEP-06:49 0.00
October 51135.23 07-OCT-15:09 0.00 0.00 9938.94 01-OCT-00:10 4738.68 02-OCT-18:40 0.00
November 10706.92 24-NOV-11:50 0.00 0.00 9938.94 01-NOV-00:10 4738.77 22-NOV-07:10 0.00
December 3217.52 08-DEC-10:00 0.00 0.00 9938.94 01-DEC-00:20 4738.27 26-DEC-19:10 0.00
                   
Annual Sum or Average     0.00 0.00         0.00
Minimum of Months 3217.52   0.00 0.00 9938.94   4738.16   0.00
Maximum of Months 117506.15   0.00 0.00 9938.94   4738.77   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 244361.40 30-JAN-20:49 62892.57 88772.42 15448.40 32159.77 23598.57 3792.57 0.00 1258.59 0.00
February 243790.03 27-FEB-20:00 62892.57 88772.42 15448.40 32159.77 22872.74 3962.53 0.00 1787.79 0.00
March 245886.58 23-MAR-19:19 62892.57 88772.42 15448.40 32159.77 23782.46 4140.39 0.00 2383.74 0.00
April 297131.56 30-APR-19:19 57527.06 87285.99 15448.40 32101.06 25167.12 7022.45 0.00 67096.30 0.00
May 279537.74 22-MAY-19:49 62892.57 88772.42 15448.40 32159.77 23902.46 6651.64 0.00 43232.86 0.00
June 321534.90 12-JUN-18:10 53571.31 79417.81 0.00 31835.81 25817.13 7356.77 0.00 106443.24 0.00
July 326774.97 22-JUL-18:19 50105.45 76444.94 0.00 31760.42 27041.08 7409.67 0.00 117506.15 0.00
August 313562.68 14-AUG-18:10 53571.31 79417.81 0.00 31835.81 25746.04 7525.70 0.00 98398.49 0.00
September 287485.46 11-SEP-19:10 62892.57 88772.42 15448.40 32151.31 24481.17 6873.55 0.00 50625.37 0.00
October 256712.79 05-OCT-19:10 62892.57 88772.42 15448.40 32151.31 28769.46 5222.30 0.00 9217.40 0.00
November 244854.10 09-NOV-20:00 62892.57 88772.42 15448.40 32159.77 23094.59 3974.87 0.00 2247.59 0.00
December 241704.02 11-DEC-20:10 62892.57 88772.42 15448.40 32151.31 21268.78 3737.48 0.00 1329.32 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 241704.02   50105.45 76444.94 0.00 31760.42 21268.78 3737.48 0.00 1258.59 0.00
Maximum of Months 326774.97   62892.57 88772.42 15448.40 32159.77 28769.46 7525.70 0.00 117506.15 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 161435.53 27-JAN-22:40 0.00 287206.29 26-JAN-18:30 0.00
February 104248.32 01-FEB-18:10 0.00 173168.07 17-FEB-15:20 0.00 287227.93 17-FEB-21:40 0.00
March 104248.32 01-MAR-18:10 0.00 172665.21 12-MAR-14:00 0.00 292900.99 17-MAR-20:30 0.00
April 104248.32 01-APR-17:10 0.00 183280.31 09-APR-22:30 0.00 284445.32 05-APR-20:49 0.00
May 104248.32 01-MAY-17:10 0.00 159447.46 30-MAY-04:10 0.00 280972.63 04-MAY-20:40 0.00
June 104248.32 01-JUN-17:10 0.00 124805.77 12-JUN-04:40 0.00 270056.17 02-JUN-20:00 0.00
July 104248.32 01-JUL-17:10 0.00 137715.93 06-JUL-03:49 0.00 249885.44 03-JUL-20:40 0.00
August 104248.32 01-AUG-17:10 0.00 107732.48 07-AUG-05:40 0.00 248189.32 30-AUG-20:49 0.00
September 104248.32 01-SEP-17:10 0.00 152123.32 08-SEP-04:00 0.00 251175.89 21-SEP-20:10 0.00
October 104248.32 02-OCT-17:10 0.00 178380.43 21-OCT-03:20 0.00 268708.32 30-OCT-20:00 0.00
November 104248.32 01-NOV-17:10 0.00 173845.64 26-NOV-10:20 0.00 288094.50 06-NOV-21:00 0.00
December 104248.32 01-DEC-18:10 0.00 183232.98 22-DEC-15:50 0.00 284584.21 28-DEC-21:40 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 107732.48   0.00 248189.32   0.00
Maximum of Months 104248.32   0.00 183280.31   0.00 292900.99   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 20.83 25.17 20.83 25.17
February 0.00 0.00 0.00 0.00 21.00 25.14 21.00 25.14
March 0.00 0.00 0.00 0.00 40.17 25.07 40.17 25.07
April 0.00 0.00 0.00 0.00 22.67 25.08 22.67 25.08
May 0.00 0.00 0.00 0.00 25.83 25.16 25.83 25.16
June 0.00 0.00 0.00 0.00 2.17 24.99 2.17 24.99
July 0.00 0.00 0.00 0.00 0.83 24.83 0.83 24.83
August 0.00 0.00 0.00 0.00 0.67 24.88 0.67 24.88
September 0.00 0.00 0.00 0.00 5.17 25.13 5.17 25.13
October 0.00 0.00 0.00 0.00 39.50 25.16 39.50 25.16
November 0.00 0.00 0.00 0.00 43.67 25.18 43.67 25.18
December 0.00 0.00 0.00 0.00 22.83 25.08 22.83 25.08
                 
Annual Sum or Average 0.00   0.00   245.33 25.13 245.33 25.13
Minimum of Months 0.00 0.00 0.00 0.00 0.67 24.83 0.67 24.83
Maximum of Months 0.00 0.00 0.00 0.00 43.67 25.18 43.67 25.18



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.50 21.89 1.50 21.89
May 0.00 0.00 0.00 0.00 0.50 21.75 0.50 21.75
June 0.00 0.00 0.00 0.00 0.83 21.72 0.83 21.72
July 0.00 0.00 0.00 0.00 1.00 21.75 1.00 21.75
August 0.00 0.00 0.00 0.00 1.00 21.73 1.00 21.73
September 0.00 0.00 0.00 0.00 1.50 21.80 1.50 21.80
October 0.00 0.00 0.00 0.00 0.33 21.74 0.33 21.74
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   6.67 21.79 6.67 21.79
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.50 21.89 1.50 21.89



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.83 21.84 0.83 21.84
May 0.00 0.00 0.00 0.00 0.67 21.76 0.67 21.76
June 0.00 0.00 0.00 0.00 1.67 21.77 1.67 21.77
July 0.00 0.00 0.00 0.00 1.67 21.76 1.67 21.76
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.83 21.78 4.83 21.78
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.67 21.84 1.67 21.84



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.50 20.38 0.50 20.38 0.00 20.38 0.00 20.38
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 21.75 0.17 21.75
July 0.00 0.00 0.00 0.00 0.33 21.75 0.33 21.75
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 20.54 0.17 20.54 0.00 20.54 0.00 20.54
                 
Annual Sum or Average 0.67 20.42 0.67 20.42 0.50 20.78 0.50 20.99
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.50 20.54 0.50 20.54 0.33 21.75 0.33 21.75



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 21.80 0.67 21.80
May 0.00 0.00 0.00 0.00 1.00 21.71 1.00 21.71
June 0.00 0.00 0.00 0.00 0.17 21.74 0.17 21.74
July 0.00 0.00 0.00 0.00 0.33 21.76 0.33 21.76
August 0.00 0.00 0.00 0.00 0.67 21.70 0.67 21.70
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.83 21.74 2.83 21.74
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.00 21.80 1.00 21.80



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.50 21.89 0.50 21.89
May 0.00 0.00 0.00 0.00 1.33 21.77 1.33 21.77
June 0.00 0.00 0.00 0.00 1.17 21.75 1.17 21.75
July 0.00 0.00 0.00 0.00 1.33 21.78 1.33 21.78
August 0.00 0.00 0.00 0.00 0.67 21.75 0.67 21.75
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   5.00 21.78 5.00 21.78
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.33 21.89 1.33 21.89



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.67 21.92 2.67 21.92
May 0.00 0.00 0.00 0.00 1.00 21.81 1.00 21.81
June 0.00 0.00 0.00 0.00 1.67 21.73 1.67 21.73
July 0.00 0.00 0.00 0.00 2.00 21.77 2.00 21.77
August 0.00 0.00 0.00 0.00 1.33 21.78 1.33 21.78
September 0.00 0.00 0.00 0.00 1.33 21.86 1.33 21.86
October 0.00 0.00 0.00 0.00 0.33 21.71 0.33 21.71
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   10.33 21.82 10.33 21.82
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.67 21.92 2.67 21.92



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.50 21.89 1.50 21.89
May 0.00 0.00 0.00 0.00 1.50 21.77 1.50 21.77
June 0.00 0.00 0.00 0.00 2.67 21.79 2.67 21.79
July 0.00 0.00 0.00 0.00 2.00 21.82 2.00 21.82
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   7.67 21.81 7.67 21.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.67 21.89 2.67 21.89



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.83 21.87 0.83 21.87
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.50 21.71 0.50 21.71
September 0.00 0.00 0.00 0.00 2.17 21.83 2.17 21.83
October 0.00 0.00 0.00 0.00 0.50 21.89 0.50 21.89
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.00 21.83 4.00 21.83
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.17 21.89 2.17 21.89



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.33 24.68 1.33 24.68
February 0.00 0.00 0.00 0.00 1.17 24.75 1.17 24.75
March 0.00 0.00 0.00 0.00 2.17 24.71 2.17 24.71
April 0.00 0.00 0.00 0.00 3.67 24.71 3.67 24.71
May 0.00 0.00 0.00 0.00 9.50 24.75 9.50 24.75
June 0.00 0.00 0.00 0.00 4.17 24.69 4.17 24.69
July 0.00 0.00 0.00 0.00 1.00 24.72 1.00 24.72
August 0.00 0.00 0.00 0.00 0.33 24.63 0.33 24.63
September 0.00 0.00 0.00 0.00 3.00 24.71 3.00 24.71
October 0.00 0.00 0.00 0.00 6.33 24.72 6.33 24.72
November 0.00 0.00 0.00 0.00 5.00 24.77 5.00 24.77
December 0.00 0.00 0.00 0.00 0.67 24.69 0.67 24.69
                 
Annual Sum or Average 0.00   0.00   38.33 24.73 38.33 24.73
Minimum of Months 0.00 0.00 0.00 0.00 0.33 24.63 0.33 24.63
Maximum of Months 0.00 0.00 0.00 0.00 9.50 24.77 9.50 24.77



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 2.33 24.71 2.33 24.71
February 0.00 0.00 0.00 0.00 1.67 24.77 1.67 24.77
March 0.00 0.00 0.00 0.00 4.00 24.73 4.00 24.73
April 0.00 0.00 0.00 0.00 5.00 24.77 5.00 24.77
May 0.00 0.00 0.00 0.00 11.00 24.78 11.00 24.78
June 0.00 0.00 0.00 0.00 4.50 24.73 4.50 24.73
July 0.00 0.00 0.00 0.00 1.33 24.72 1.33 24.72
August 0.00 0.00 0.00 0.00 0.50 24.63 0.50 24.63
September 0.00 0.00 0.00 0.00 3.67 24.72 3.67 24.72
October 0.00 0.00 0.00 0.00 9.17 24.73 9.17 24.73
November 0.00 0.00 0.00 0.00 8.67 24.75 8.67 24.75
December 0.00 0.00 0.00 0.00 1.17 24.76 1.17 24.76
                 
Annual Sum or Average 0.00   0.00   53.00 24.75 53.00 24.75
Minimum of Months 0.00 0.00 0.00 0.00 0.50 24.63 0.50 24.63
Maximum of Months 0.00 0.00 0.00 0.00 11.00 24.78 11.00 24.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 39.50 25.07 39.50 25.07
February 0.00 0.00 0.00 0.00 39.67 25.13 39.67 25.13
March 0.00 0.00 0.00 0.00 63.33 25.08 63.33 25.08
April 0.00 0.00 0.00 0.00 35.33 25.06 35.33 25.06
May 0.00 0.00 0.00 0.00 47.50 25.05 47.50 25.05
June 0.00 0.00 0.00 0.00 9.83 24.91 9.83 24.91
July 0.00 0.00 0.00 0.00 2.83 24.86 2.83 24.86
August 0.00 0.00 0.00 0.00 1.83 24.83 1.83 24.83
September 0.00 0.00 0.00 0.00 12.50 25.04 12.50 25.04
October 0.00 0.00 0.00 0.00 66.83 25.04 66.83 25.04
November 0.00 0.00 0.00 0.00 76.83 25.10 76.83 25.10
December 0.00 0.00 0.00 0.00 38.83 25.18 38.83 25.18
                 
Annual Sum or Average 0.00   0.00   434.83 25.08 434.83 25.08
Minimum of Months 0.00 0.00 0.00 0.00 1.83 24.83 1.83 24.83
Maximum of Months 0.00 0.00 0.00 0.00 76.83 25.18 76.83 25.18



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 735.67 23.39 0.00 23.39 0.00 23.39
February 671.67 23.27 0.00 23.27 0.00 23.27
March 744.00 23.05 0.00 23.05 0.00 23.05
April 720.00 23.03 0.00 23.03 0.00 23.03
May 744.00 23.04 0.00 23.04 0.00 23.04
June 710.33 23.07 0.00 23.07 0.00 23.07
July 648.00 23.21 1.00 23.21 0.00 23.21
August 579.00 23.29 5.83 23.29 0.00 23.29
September 446.17 23.46 9.33 23.47 0.00 23.47
October 453.67 23.58 2.17 23.58 0.00 23.58
November 500.33 23.66 0.00 23.66 0.00 23.66
December 698.67 23.61 0.00 23.61 0.00 23.61
             
Annual Sum or Average 7651.50 23.28 18.33 23.28 0.00 23.28
Minimum of Months 446.17 23.03 0.00 23.03 0.00 23.03
Maximum of Months 744.00 23.66 9.33 23.66 0.00 23.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 730.67 21.08 140.17 21.07 138.67 21.06
February 649.33 21.10 35.83 21.12 30.00 21.11
March 744.00 21.03 31.67 21.03 31.67 21.03
April 649.83 21.29 37.83 21.44 0.00 21.44
May 693.50 21.26 16.83 21.31 0.00 21.31
June 660.50 21.29 23.67 21.37 0.00 21.37
July 634.33 21.40 70.17 21.61 0.00 21.61
August 599.83 21.47 110.17 21.82 0.00 21.82
September 563.00 21.40 122.17 21.83 0.00 21.83
October 685.33 21.15 36.67 21.29 0.00 21.29
November 709.17 21.09 33.17 21.09 31.33 21.08
December 742.33 21.05 240.83 21.04 240.83 21.03
             
Annual Sum or Average 8061.83 21.21 899.17 21.32 472.50 21.30
Minimum of Months 563.00 21.03 16.83 21.03 0.00 21.03
Maximum of Months 744.00 21.47 240.83 21.83 240.83 21.83



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.80 0.00 21.80 0.00 21.80
February 672.00 21.91 0.00 21.91 0.00 21.91
March 744.00 21.90 0.00 21.90 0.00 21.90
April 689.33 22.61 0.00 22.61 0.00 22.61
May 694.67 22.65 3.83 22.66 0.00 22.66
June 590.00 22.78 32.67 22.84 0.00 22.84
July 505.50 22.81 90.67 22.98 0.00 22.98
August 510.33 22.95 75.00 23.08 0.00 23.08
September 562.17 22.90 42.83 22.98 0.00 22.98
October 730.33 22.39 0.00 22.39 0.00 22.39
November 720.00 21.98 0.00 21.98 0.00 21.98
December 744.00 21.59 0.00 21.59 0.00 21.59
             
Annual Sum or Average 7906.33 22.30 245.00 22.35 0.00 22.35
Minimum of Months 505.50 21.59 0.00 21.59 0.00 21.59
Maximum of Months 744.00 22.95 90.67 23.08 0.00 23.08



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.12 18.83 21.12 18.83 21.12
February 672.00 21.12 0.00 21.12 0.00 21.12
March 744.00 21.21 0.00 21.21 0.00 21.21
April 720.00 21.88 0.00 21.88 0.00 21.88
May 744.00 22.10 0.00 22.10 0.00 22.10
June 712.67 22.58 0.00 22.58 0.00 22.58
July 708.00 22.78 0.00 22.78 0.00 22.78
August 731.67 22.85 0.00 22.85 0.00 22.85
September 719.67 22.58 0.00 22.58 0.00 22.58
October 744.00 21.73 0.00 21.73 0.00 21.73
November 720.00 21.26 0.00 21.26 0.00 21.26
December 744.00 21.07 7.83 21.07 7.83 21.07
             
Annual Sum or Average 8704.00 21.85 26.67 21.85 26.67 21.85
Minimum of Months 672.00 21.07 0.00 21.07 0.00 21.07
Maximum of Months 744.00 22.85 18.83 22.85 18.83 22.85



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.02 48.17 21.02 48.17 21.02
February 672.00 21.02 0.00 21.02 0.00 21.02
March 744.00 21.05 0.00 21.05 0.00 21.05
April 720.00 21.63 0.00 21.63 0.00 21.63
May 744.00 21.85 0.00 21.85 0.00 21.85
June 720.00 22.35 0.00 22.35 0.00 22.35
July 744.00 22.59 0.00 22.59 0.00 22.59
August 744.00 22.64 0.00 22.64 0.00 22.64
September 720.00 22.35 0.00 22.35 0.00 22.35
October 744.00 21.46 0.00 21.46 0.00 21.46
November 720.00 21.08 0.00 21.08 0.00 21.08
December 744.00 21.00 18.50 21.00 18.50 21.00
             
Annual Sum or Average 8760.00 21.67 66.67 21.67 66.67 21.66
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 22.64 48.17 22.64 48.17 22.64



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 251.83 23.09 544.83 23.36 161.33 23.50
February 224.00 23.16 530.50 23.35 149.17 23.49
March 262.00 23.25 584.67 23.41 176.50 23.57
April 265.17 23.49 596.50 23.44 205.50 23.58
May 282.67 23.77 649.50 23.49 245.17 23.63
June 295.17 23.70 641.67 23.40 264.83 23.53
July 302.17 23.79 675.83 23.40 281.33 23.54
August 302.67 23.82 671.83 23.41 284.83 23.54
September 283.33 23.74 640.00 23.43 255.67 23.55
October 284.50 23.65 637.17 23.48 229.83 23.63
November 256.33 23.44 574.00 23.47 185.00 23.63
December 245.83 23.00 530.83 23.35 150.50 23.49
             
Annual Sum or Average 3255.67 23.51 7277.33 23.42 2589.67 23.56
Minimum of Months 224.00 23.00 530.50 23.35 149.17 23.49
Maximum of Months 302.67 23.82 675.83 23.49 284.83 23.63



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 714.00 21.46 13.83 21.49 0.83 21.49
February 630.17 21.55 24.00 21.63 0.00 21.63
March 743.17 21.48 0.00 21.48 0.00 21.48
April 573.67 22.11 71.33 22.29 0.00 22.29
May 620.83 22.09 58.00 22.21 0.00 22.21
June 558.00 22.20 96.17 22.37 8.83 22.38
July 405.50 22.15 186.67 22.55 0.33 22.55
August 335.67 22.32 242.17 22.84 2.00 22.84
September 376.00 22.30 234.33 22.83 0.00 22.83
October 645.50 21.87 61.50 22.03 0.00 22.03
November 695.67 21.59 11.00 21.62 0.00 21.62
December 732.50 21.30 7.00 21.30 6.17 21.30
             
Annual Sum or Average 7030.67 21.80 1006.00 22.02 18.17 22.02
Minimum of Months 335.67 21.30 0.00 21.30 0.00 21.30
Maximum of Months 743.17 22.32 242.17 22.84 8.83 22.84



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 743.50 22.27 0.00 22.27 0.00 22.27
February 672.00 22.39 0.00 22.39 0.00 22.39
March 744.00 22.35 0.00 22.35 0.00 22.35
April 584.50 22.88 4.67 22.89 0.00 22.89
May 561.83 22.83 32.83 22.89 0.00 22.89
June 375.00 22.82 139.50 23.11 8.17 23.12
July 280.00 22.84 258.00 23.35 0.17 23.35
August 182.50 22.86 302.67 23.50 0.83 23.50
September 248.50 22.95 199.33 23.36 4.50 23.37
October 627.67 22.68 0.83 22.69 0.00 22.69
November 717.17 22.44 0.00 22.44 0.00 22.44
December 744.00 22.06 0.00 22.06 0.00 22.06
             
Annual Sum or Average 6480.67 22.53 937.83 22.70 13.67 22.70
Minimum of Months 182.50 22.06 0.00 22.06 0.00 22.06
Maximum of Months 744.00 22.95 302.67 23.50 8.17 23.50



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.80 451.83 20.71 451.83 20.68
February 672.00 20.93 299.83 20.82 299.83 20.76
March 744.00 20.87 309.33 20.79 309.33 20.74
April 700.33 21.42 14.67 21.41 13.50 21.39
May 719.50 21.41 5.50 21.42 0.50 21.42
June 667.33 21.47 11.00 21.50 0.00 21.50
July 665.33 21.44 24.00 21.51 0.00 21.51
August 658.67 21.43 16.67 21.48 0.00 21.48
September 663.83 21.45 12.33 21.49 0.00 21.49
October 737.67 21.14 47.83 21.07 47.83 21.00
November 720.00 20.85 292.50 20.73 292.50 20.66
December 744.00 20.63 654.33 20.60 654.33 20.59
             
Annual Sum or Average 8436.67 21.14 2139.83 21.04 2069.67 20.96
Minimum of Months 658.67 20.63 5.50 20.60 0.00 20.59
Maximum of Months 744.00 21.47 654.33 21.51 654.33 21.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.61 564.50 20.55 564.50 20.53
February 672.00 20.70 478.33 20.63 478.33 20.60
March 744.00 20.77 436.00 20.70 436.00 20.66
April 714.83 21.28 26.33 21.26 26.33 21.23
May 732.17 21.34 1.83 21.34 0.67 21.34
June 686.83 21.47 6.00 21.48 0.00 21.48
July 696.33 21.47 7.17 21.49 0.00 21.49
August 706.00 21.47 0.00 21.47 0.00 21.47
September 705.83 21.39 0.00 21.39 0.00 21.39
October 744.00 20.96 91.83 20.85 91.83 20.77
November 720.00 20.67 426.17 20.57 426.17 20.52
December 744.00 20.52 720.83 20.51 720.83 20.51
             
Annual Sum or Average 8610.00 21.05 2759.00 20.91 2744.67 20.83
Minimum of Months 672.00 20.52 0.00 20.51 0.00 20.51
Maximum of Months 744.00 21.47 720.83 21.49 720.83 21.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.87 258.83 20.78 258.83 20.72
February 672.00 20.91 170.00 20.82 170.00 20.76
March 744.00 21.02 57.17 20.98 57.17 20.94
April 720.00 21.21 0.00 21.21 0.00 21.21
May 744.00 21.27 0.00 21.27 0.00 21.27
June 720.00 21.37 0.00 21.37 0.00 21.37
July 744.00 21.39 0.00 21.39 0.00 21.39
August 744.00 21.33 0.00 21.33 0.00 21.33
September 720.00 21.26 0.00 21.26 0.00 21.26
October 744.00 21.08 0.00 21.08 0.00 21.08
November 720.00 20.93 131.33 20.86 131.33 20.80
December 744.00 20.83 294.83 20.71 294.83 20.65
             
Annual Sum or Average 8760.00 21.12 912.17 21.06 912.17 21.01
Minimum of Months 672.00 20.83 0.00 20.71 0.00 20.65
Maximum of Months 744.00 21.39 294.83 21.39 294.83 21.39



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.80 445.00 20.71 445.00 20.67
February 672.00 20.92 316.17 20.83 316.17 20.78
March 744.00 20.90 298.17 20.82 298.17 20.78
April 697.17 21.53 10.33 21.52 10.33 21.51
May 712.17 21.49 0.17 21.49 0.00 21.49
June 653.00 21.48 0.83 21.48 0.00 21.48
July 642.17 21.43 3.83 21.44 0.00 21.44
August 626.50 21.38 1.17 21.38 0.00 21.38
September 633.33 21.44 2.17 21.45 0.00 21.45
October 744.00 21.20 44.00 21.13 44.00 21.07
November 720.00 20.84 300.83 20.73 300.83 20.67
December 744.00 20.65 639.00 20.61 639.00 20.60
             
Annual Sum or Average 8332.33 21.16 2061.67 21.04 2053.50 20.96
Minimum of Months 626.50 20.65 0.17 20.61 0.00 20.60
Maximum of Months 744.00 21.53 639.00 21.52 639.00 21.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.61 573.00 20.55 573.00 20.53
February 672.00 20.68 515.33 20.63 515.33 20.61
March 744.00 20.80 413.83 20.73 413.83 20.70
April 717.33 21.47 12.33 21.45 12.33 21.44
May 734.50 21.49 0.00 21.49 0.00 21.49
June 680.50 21.53 0.33 21.53 0.00 21.53
July 702.00 21.58 1.00 21.58 0.00 21.58
August 706.50 21.58 0.17 21.58 0.00 21.58
September 716.33 21.60 0.00 21.60 0.00 21.60
October 744.00 21.03 75.17 20.94 75.17 20.86
November 720.00 20.67 435.17 20.57 435.17 20.52
December 744.00 20.53 697.33 20.52 697.33 20.51
             
Annual Sum or Average 8625.17 21.13 2723.67 20.97 2722.17 20.88
Minimum of Months 672.00 20.53 0.00 20.52 0.00 20.51
Maximum of Months 744.00 21.60 697.33 21.60 697.33 21.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.03 13.17 21.03 13.17 21.03
February 672.00 21.05 0.00 21.05 0.00 21.05
March 744.00 21.06 0.00 21.06 0.00 21.06
April 720.00 21.93 0.00 21.93 0.00 21.93
May 744.00 22.18 0.00 22.18 0.00 22.18
June 720.00 22.57 0.00 22.57 0.00 22.57
July 734.00 22.77 0.00 22.77 0.00 22.77
August 744.00 22.87 0.00 22.87 0.00 22.87
September 720.00 22.64 0.00 22.64 0.00 22.64
October 744.00 21.56 0.00 21.56 0.00 21.56
November 720.00 21.06 0.00 21.06 0.00 21.06
December 744.00 21.01 11.33 21.01 11.33 21.01
             
Annual Sum or Average 8750.00 21.81 24.50 21.81 24.50 21.81
Minimum of Months 672.00 21.01 0.00 21.01 0.00 21.01
Maximum of Months 744.00 22.87 13.17 22.87 13.17 22.87



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.71 578.67 20.65 578.67 20.63
February 672.00 20.83 469.50 20.75 469.50 20.72
March 744.00 20.78 515.00 20.72 515.00 20.70
April 690.33 21.37 57.67 21.34 53.67 21.29
May 711.17 21.35 20.17 21.37 10.50 21.36
June 654.33 21.42 21.00 21.48 0.00 21.48
July 651.50 21.39 38.17 21.50 0.00 21.50
August 644.33 21.37 32.67 21.47 0.00 21.47
September 657.50 21.40 20.17 21.46 0.00 21.46
October 735.67 21.05 120.83 20.92 120.83 20.83
November 720.00 20.75 446.83 20.65 446.83 20.61
December 744.00 20.57 722.17 20.56 722.17 20.56
             
Annual Sum or Average 8368.83 21.07 3042.83 20.96 2917.17 20.88
Minimum of Months 644.33 20.57 20.17 20.56 0.00 20.56
Maximum of Months 744.00 21.42 722.17 21.50 722.17 21.50



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.54 684.00 20.52 684.00 20.51
February 672.00 20.60 606.17 20.58 606.17 20.57
March 744.00 20.68 599.33 20.63 599.33 20.61
April 711.00 21.24 95.00 21.19 95.00 21.14
May 728.00 21.29 19.33 21.29 15.50 21.27
June 677.50 21.43 10.33 21.46 0.00 21.46
July 682.00 21.43 17.67 21.47 0.00 21.47
August 695.33 21.43 3.00 21.44 0.00 21.44
September 703.17 21.34 3.00 21.33 2.83 21.33
October 744.00 20.86 219.17 20.71 219.17 20.62
November 720.00 20.58 539.33 20.51 539.33 20.48
December 744.00 20.49 743.83 20.49 743.83 20.49
             
Annual Sum or Average 8565.00 20.98 3540.17 20.85 3505.17 20.77
Minimum of Months 672.00 20.49 3.00 20.49 0.00 20.48
Maximum of Months 744.00 21.43 743.83 21.47 743.83 21.47



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 733.00 21.07 268.83 20.94 268.83 20.87
February 654.17 21.13 172.83 21.04 172.83 20.98
March 744.00 21.06 180.17 20.98 180.17 20.93
April 670.33 21.44 15.17 21.46 6.67 21.45
May 699.33 21.40 3.17 21.41 0.17 21.41
June 659.00 21.44 2.67 21.44 0.00 21.44
July 656.83 21.41 13.17 21.44 0.00 21.44
August 636.33 21.35 51.83 21.50 0.00 21.50
September 617.50 21.37 54.33 21.52 0.00 21.52
October 699.00 21.20 28.83 21.17 23.17 21.13
November 710.00 21.08 164.50 20.97 164.50 20.89
December 741.67 20.90 470.50 20.79 470.50 20.75
             
Annual Sum or Average 8221.17 21.23 1426.00 21.18 1286.83 21.11
Minimum of Months 617.50 20.90 2.67 20.79 0.00 20.75
Maximum of Months 744.00 21.44 470.50 21.52 470.50 21.52



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 370.67 23.10 42.33 23.19 0.00 23.19
February 298.00 23.14 53.00 23.28 0.00 23.28
March 247.83 23.15 68.50 23.34 0.00 23.34
April 80.17 23.26 244.00 23.83 0.00 23.83
May 39.67 23.13 480.50 23.94 0.00 23.94
June 10.00 23.77 667.33 23.96 7.33 23.96
July 1.00 24.00 721.83 23.96 1.00 23.96
August 0.50 23.99 724.33 23.94 0.50 23.94
September 11.33 23.31 592.17 23.94 2.33 23.94
October 149.67 23.04 316.50 23.71 0.00 23.71
November 281.83 23.06 131.83 23.38 0.00 23.38
December 382.00 23.06 14.33 23.10 0.00 23.10
             
Annual Sum or Average 1872.67 23.11 4056.67 23.70 11.17 23.70
Minimum of Months 0.50 23.04 14.33 23.10 0.00 23.10
Maximum of Months 382.00 24.00 724.33 23.96 7.33 23.96



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 182.33 23.09 202.17 23.58 0.00 23.58
February 128.17 23.21 200.67 23.70 0.00 23.70
March 94.00 23.23 305.00 23.83 0.00 23.83
April 3.33 23.16 459.50 24.01 0.00 24.01
May 0.00 0.00 646.00 24.01 0.00 24.01
June 7.00 24.00 709.00 23.99 7.00 23.99
July 0.00 0.00 743.83 23.99 0.00 23.99
August 0.00 0.00 740.67 23.97 0.00 23.97
September 0.00 0.00 681.00 23.97 0.00 23.97
October 24.00 23.04 516.67 23.96 0.00 23.96
November 117.50 23.12 288.00 23.77 0.00 23.77
December 222.33 23.13 152.67 23.49 0.00 23.49
             
Annual Sum or Average 778.67 23.15 5645.17 23.89 7.00 23.89
Minimum of Months 0.00 0.00 152.67 23.49 0.00 23.49
Maximum of Months 222.33 24.00 743.83 24.01 7.00 24.01



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 509.67 24.06 674.83 24.00 496.33 24.04
February 461.17 24.11 605.83 24.04 454.50 24.07
March 514.00 24.19 696.33 24.09 513.83 24.12
April 514.17 24.14 706.67 24.04 514.17 24.07
May 540.17 24.16 741.83 24.06 540.17 24.09
June 531.17 24.03 719.50 23.95 531.17 23.97
July 553.83 24.00 743.50 23.94 553.83 23.96
August 550.00 23.99 744.00 23.94 550.00 23.95
September 520.17 24.03 718.17 23.94 520.17 23.97
October 528.67 24.19 737.83 24.06 528.50 24.10
November 499.50 24.21 672.83 24.11 497.67 24.14
December 495.67 24.08 656.00 24.03 485.83 24.05
             
Annual Sum or Average 6218.17 24.10 8417.33 24.01 6186.17 24.04
Minimum of Months 461.17 23.99 605.83 23.94 454.50 23.95
Maximum of Months 553.83 24.21 744.00 24.11 553.83 24.14



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.03 34.83 21.03 34.83 21.03
February 672.00 21.06 0.00 21.06 0.00 21.06
March 744.00 21.06 0.00 21.06 0.00 21.06
April 716.67 21.79 0.00 21.79 0.00 21.79
May 737.83 21.95 0.00 21.95 0.00 21.95
June 674.83 22.39 10.33 22.41 0.00 22.41
July 642.67 22.57 25.17 22.62 0.00 22.62
August 664.67 22.62 10.33 22.64 0.00 22.64
September 699.33 22.28 1.17 22.29 0.00 22.29
October 744.00 21.35 0.00 21.35 0.00 21.35
November 720.00 21.05 0.00 21.05 0.00 21.05
December 744.00 21.01 14.33 21.01 14.33 21.01
             
Annual Sum or Average 8504.00 21.66 96.17 21.67 49.17 21.66
Minimum of Months 642.67 21.01 0.00 21.01 0.00 21.01
Maximum of Months 744.00 22.62 34.83 22.64 34.83 22.64



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.39215 34.89942 0.14750 5.59016
February 672.00000 23.26740 36.03083 0.12205 5.43295
March 744.00000 23.05379 35.81099 0.06532 5.22534
April 720.00000 23.03133 35.48697 0.05950 5.24120
May 744.00000 23.04212 40.94010 -0.9109 22.75464
June 720.00000 23.07474 48.35585 -0.8464 20.33352
July 744.00000 23.28996 49.72446 -0.7570 17.32063
August 744.00000 23.40386 49.61825 -0.7154 15.98892
September 720.00000 23.61515 45.47951 -0.6636 14.46068
October 744.00000 23.71131 40.79783 0.27614 6.67263
November 720.00000 23.74432 37.26585 0.25967 6.48994
December 744.00000 23.62886 33.95583 0.20448 5.96798
           
Annual Sum or Average 8760.00000 23.35517 40.72510 -0.2320 10.99455
Minimum of Months 672.00000 23.03133 33.95583 -0.9109 5.22534
Maximum of Months 744.00000 23.74432 49.72446 0.27614 22.75464



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.12065 37.09976 -0.4180 9.28926
February 672.00000 21.17970 38.04229 -0.3742 8.74616
March 744.00000 21.02877 37.61564 -0.4282 8.96779
April 720.00000 21.51969 36.38211 -0.2011 7.39503
May 744.00000 21.39631 42.64313 -1.3224 42.80748
June 720.00000 21.44596 50.81083 -1.2153 37.44572
July 744.00000 21.67260 52.30211 -1.1053 33.02271
August 744.00000 21.86720 52.00864 -1.0216 30.14166
September 720.00000 21.88695 47.98827 -1.0482 32.22786
October 744.00000 21.35012 44.54001 -0.2431 7.50050
November 720.00000 21.11953 40.91267 -0.3833 8.56500
December 744.00000 21.05295 36.70067 -0.4815 10.17173
           
Annual Sum or Average 8760.00000 21.38724 43.11838 -0.6891 19.76119
Minimum of Months 672.00000 21.02877 36.38211 -1.3224 7.39503
Maximum of Months 744.00000 21.88695 52.30211 -0.2011 42.80748



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.79533 38.42503 -0.2046 6.22988
February 672.00000 21.90580 39.23227 -0.1701 5.87955
March 744.00000 21.90217 38.58584 -0.1757 5.97221
April 720.00000 22.66384 36.86039 0.01911 5.46519
May 744.00000 22.72902 42.35403 -0.9511 24.87304
June 720.00000 22.95497 49.44345 -0.8164 19.71865
July 744.00000 23.09760 50.96904 -0.7508 17.65932
August 744.00000 23.20078 50.98179 -0.7131 16.17461
September 720.00000 23.08656 47.62421 -0.7789 18.43588
October 744.00000 22.41387 44.66645 -0.0019 5.39422
November 720.00000 21.98014 41.69579 -0.1378 5.73053
December 744.00000 21.58920 38.30434 -0.2626 6.70214
           
Annual Sum or Average 8760.00000 22.44519 43.28795 -0.4138 11.55700
Minimum of Months 672.00000 21.58920 36.86039 -0.9511 5.39422
Maximum of Months 744.00000 23.20078 50.98179 0.01911 24.87304



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.99764 31.84715 0.63678 16.33934
February 672.00000 23.02705 32.73334 0.65390 16.76527
March 744.00000 23.05607 32.01536 0.66475 17.26074
April 720.00000 23.08699 31.63252 0.70869 18.29689
May 744.00000 23.12609 36.98299 0.03489 10.38330
June 720.00000 23.04857 44.62006 0.08485 10.34274
July 744.00000 23.05616 46.57909 0.10872 10.23401
August 744.00000 23.04093 46.82118 0.11301 10.36083
September 720.00000 23.07300 43.07350 0.08037 10.18113
October 744.00000 23.10827 38.56671 0.73881 19.22572
November 720.00000 23.08790 35.01974 0.68692 17.84521
December 744.00000 22.98807 31.40601 0.62129 15.92801
           
Annual Sum or Average 8760.00000 23.05814 37.63748 0.42630 14.41396
Minimum of Months 672.00000 22.98807 31.40601 0.03489 10.18113
Maximum of Months 744.00000 23.12609 46.82118 0.73881 19.22572



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.53142 41.19534 -0.2217 6.84046
February 672.00000 21.67045 41.97106 -0.1634 6.48688
March 744.00000 21.48498 41.63660 -0.2275 6.39420
April 720.00000 22.37998 39.72168 0.07446 6.33696
May 744.00000 22.28277 45.63372 -0.9460 25.56969
June 720.00000 22.40759 53.19895 -0.8256 20.66478
July 744.00000 22.63109 54.59885 -0.7167 17.53298
August 744.00000 22.88233 54.21609 -0.6117 14.72572
September 720.00000 22.86944 50.45696 -0.6402 16.42071
October 744.00000 22.08640 47.75853 0.01147 6.28146
November 720.00000 21.64723 44.68370 -0.1658 6.28801
December 744.00000 21.33045 41.01055 -0.3087 7.47337
           
Annual Sum or Average 8760.00000 22.10140 46.36868 -0.3971 11.78713
Minimum of Months 672.00000 21.33045 39.72168 -0.9460 6.28146
Maximum of Months 744.00000 22.88233 54.59885 0.07446 25.56969



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.26727 40.49452 -0.0630 5.63153
February 672.00000 22.38855 41.25541 -0.0243 5.43724
March 744.00000 22.34517 40.71080 -0.0405 5.54219
April 720.00000 23.05408 39.11675 0.15423 5.93137
May 744.00000 23.06522 44.55123 -0.7871 18.83391
June 720.00000 23.23643 51.62865 -0.6650 14.92140
July 744.00000 23.36016 53.14928 -0.6018 13.22752
August 744.00000 23.47837 53.07958 -0.5556 11.86509
September 720.00000 23.44442 49.59150 -0.5958 12.99300
October 744.00000 22.84942 46.62453 0.14009 5.91626
November 720.00000 22.44756 43.70682 0.00480 5.53617
December 744.00000 22.05737 40.33306 -0.1256 5.83206
           
Annual Sum or Average 8760.00000 22.83416 45.37999 -0.2651 9.33152
Minimum of Months 672.00000 22.05737 39.11675 -0.7871 5.43724
Maximum of Months 744.00000 23.47837 53.14928 0.15423 18.83391



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.80016 41.34240 -0.5661 12.23203
February 672.00000 20.93061 41.98181 -0.5100 10.99145
March 744.00000 20.87109 42.16394 -0.5220 10.95749
April 720.00000 21.47558 41.05906 -0.2667 7.48894
May 744.00000 21.47455 47.26962 -1.3594 44.40316
June 720.00000 21.60576 53.66261 -1.2183 37.53692
July 744.00000 21.63791 54.30675 -1.1776 35.73540
August 744.00000 21.64671 54.81009 -1.1746 35.61709
September 720.00000 21.59740 52.60135 -1.2475 39.09803
October 744.00000 21.15996 50.09133 -0.3571 8.34927
November 720.00000 20.84809 46.18714 -0.5175 11.03756
December 744.00000 20.63343 41.19774 -0.6377 13.98316
           
Annual Sum or Average 8760.00000 21.22411 47.25324 -0.7984 22.36222
Minimum of Months 672.00000 20.63343 41.05906 -1.3594 7.48894
Maximum of Months 744.00000 21.64671 54.81009 -0.2667 44.40316



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.61275 41.77846 -0.6325 13.88393
February 672.00000 20.69782 42.50933 -0.5890 12.61616
March 744.00000 20.77202 42.38882 -0.5562 11.73202
April 720.00000 21.29585 41.44269 -0.3372 8.03452
May 744.00000 21.37031 47.55976 -1.4166 47.04263
June 720.00000 21.55291 53.90947 -1.2511 38.86596
July 744.00000 21.58847 54.68955 -1.2141 37.16112
August 744.00000 21.56382 55.64413 -1.2369 38.12830
September 720.00000 21.43042 53.63713 -1.3544 43.80887
October 744.00000 20.96494 50.60394 -0.4289 9.17713
November 720.00000 20.67415 46.61506 -0.5762 12.34756
December 744.00000 20.51987 41.47284 -0.6782 15.16157
           
Annual Sum or Average 8760.00000 21.08848 47.71686 -0.8579 24.07081
Minimum of Months 672.00000 20.51987 41.44269 -1.4166 8.03452
Maximum of Months 744.00000 21.58847 55.64413 -0.3372 47.04263



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.86909 40.07698 -0.5245 11.00905
February 672.00000 20.90998 40.98799 -0.5056 10.44606
March 744.00000 21.01708 40.82268 -0.4600 9.49647
April 720.00000 21.21428 40.43499 -0.3819 8.14622
May 744.00000 21.26624 46.59198 -1.5030 51.10355
June 720.00000 21.37452 53.04961 -1.3971 45.50202
July 744.00000 21.39218 54.21693 -1.3768 44.44372
August 744.00000 21.32547 54.86820 -1.4065 45.95270
September 720.00000 21.25863 52.61519 -1.4702 49.34864
October 744.00000 21.08276 48.94175 -0.3859 8.15263
November 720.00000 20.93483 44.88713 -0.4706 9.77842
December 744.00000 20.82687 39.70145 -0.5441 11.39773
           
Annual Sum or Average 8760.00000 21.12361 46.46326 -0.8712 25.49036
Minimum of Months 672.00000 20.82687 39.70145 -1.5030 8.14622
Maximum of Months 744.00000 21.39218 54.86820 -0.3819 51.10355



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.79713 41.34343 -0.5656 12.21199
February 672.00000 20.91669 41.99856 -0.5179 11.01661
March 744.00000 20.89975 42.09716 -0.5161 10.83894
April 720.00000 21.59023 40.87376 -0.2284 7.23783
May 744.00000 21.57187 46.95825 -1.3247 42.80013
June 720.00000 21.65251 53.45021 -1.2112 37.28879
July 744.00000 21.69252 54.16693 -1.1653 35.21606
August 744.00000 21.68648 54.38926 -1.1546 34.82437
September 720.00000 21.66828 52.26717 -1.2075 37.33534
October 744.00000 21.20213 49.98270 -0.3445 8.24079
November 720.00000 20.84347 46.19764 -0.5177 10.99884
December 744.00000 20.64799 41.15732 -0.6294 13.77037
           
Annual Sum or Average 8760.00000 21.26503 47.10293 -0.7840 21.88841
Minimum of Months 672.00000 20.64799 40.87376 -1.3247 7.23783
Maximum of Months 744.00000 21.69252 54.38926 -0.2284 42.80013



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.61484 41.77272 -0.6312 13.84794
February 672.00000 20.67863 42.54093 -0.5984 12.83084
March 744.00000 20.80306 42.31016 -0.5498 11.56469
April 720.00000 21.47261 41.08983 -0.2861 7.53268
May 744.00000 21.51068 47.12791 -1.3702 44.78400
June 720.00000 21.62781 53.62572 -1.2366 38.28207
July 744.00000 21.67980 54.46473 -1.1918 36.21891
August 744.00000 21.66568 54.95200 -1.1991 36.57827
September 720.00000 21.60437 52.86076 -1.2849 40.56916
October 744.00000 21.03062 50.42564 -0.4113 8.90235
November 720.00000 20.66818 46.62891 -0.5767 12.35381
December 744.00000 20.53355 41.43447 -0.6702 14.93950
           
Annual Sum or Average 8760.00000 21.15939 47.46416 -0.8357 23.26932
Minimum of Months 672.00000 20.53355 41.08983 -1.3702 7.53268
Maximum of Months 744.00000 21.67980 54.95200 -0.2861 44.78400



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.70569 42.01864 -0.6245 13.78248
February 672.00000 20.83345 42.71632 -0.5639 12.31465
March 744.00000 20.78056 42.86641 -0.5715 12.18940
April 720.00000 21.44858 41.44167 -0.2890 8.03047
May 744.00000 21.43831 47.71725 -1.3944 46.41312
June 720.00000 21.58770 54.44220 -1.2343 38.59163
July 744.00000 21.62496 55.17766 -1.1873 36.48395
August 744.00000 21.63008 55.73679 -1.1896 36.61883
September 720.00000 21.56644 53.49666 -1.2813 41.00520
October 744.00000 21.07365 50.82069 -0.4053 9.27124
November 720.00000 20.74742 46.88986 -0.5734 12.41995
December 744.00000 20.56521 41.83400 -0.6937 15.61175
           
Annual Sum or Average 8760.00000 21.16771 47.96023 -0.8361 23.63759
Minimum of Months 672.00000 20.56521 41.44167 -1.3944 8.03047
Maximum of Months 744.00000 21.63008 55.73679 -0.2890 46.41312



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.54173 42.43200 -0.6883 15.50579
February 672.00000 20.60257 43.26022 -0.6450 14.15758
March 744.00000 20.67673 43.11348 -0.6075 13.08718
April 720.00000 21.26393 41.84824 -0.3643 8.65089
May 744.00000 21.33318 48.02072 -1.4551 49.20971
June 720.00000 21.54098 54.69915 -1.2672 39.91074
July 744.00000 21.58133 55.64461 -1.2237 37.88446
August 744.00000 21.55293 56.65822 -1.2538 39.19561
September 720.00000 21.38374 54.62626 -1.3998 46.26737
October 744.00000 20.85772 51.40030 -0.4845 10.33691
November 720.00000 20.58089 47.31374 -0.6322 13.87224
December 744.00000 20.48700 42.03735 -0.7286 16.70427
           
Annual Sum or Average 8760.00000 21.03536 48.45045 -0.8977 25.47148
Minimum of Months 672.00000 20.48700 41.84824 -1.4551 8.65089
Maximum of Months 744.00000 21.58133 56.65822 -0.3643 49.20971



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.10230 41.96272 -0.4558 10.48260
February 672.00000 21.19297 42.66494 -0.4120 9.55977
March 744.00000 21.06157 43.15246 -0.4624 9.88427
April 720.00000 21.57487 42.42747 -0.2285 7.42340
May 744.00000 21.51640 48.53032 -1.3698 45.16247
June 720.00000 21.59669 54.37920 -1.2687 40.08732
July 744.00000 21.63217 54.98064 -1.2216 37.95952
August 744.00000 21.64088 54.69613 -1.1924 36.82196
September 720.00000 21.64302 52.57930 -1.2095 37.91449
October 744.00000 21.32693 50.97727 -0.2860 7.79925
November 720.00000 21.11084 47.15585 -0.4203 9.55377
December 744.00000 20.90266 41.78393 -0.5474 12.15023
           
Annual Sum or Average 8760.00000 21.35845 47.97112 -0.7588 22.15099
Minimum of Months 672.00000 20.90266 41.78393 -1.3698 7.42340
Maximum of Months 744.00000 21.64302 54.98064 -0.2285 45.16247



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.53434 40.55481 0.25585 6.87558
February 672.00000 23.60321 41.24917 0.28341 6.98467
March 744.00000 23.68856 40.18205 0.31350 7.33519
April 720.00000 23.85909 39.13957 0.38839 8.31044
May 744.00000 23.89511 43.98794 -0.4380 9.24235
June 720.00000 23.93661 50.66953 -0.3370 7.51924
July 744.00000 23.95460 52.37289 -0.3063 7.07308
August 744.00000 23.93360 52.70921 -0.3197 7.23347
September 720.00000 23.89050 49.69518 -0.3908 8.39158
October 744.00000 23.74775 46.23485 0.38339 8.29076
November 720.00000 23.61702 43.33623 0.30721 7.35710
December 744.00000 23.50715 40.19281 0.24023 6.67908
           
Annual Sum or Average 8760.00000 23.76460 45.05059 0.03005 7.60969
Minimum of Months 672.00000 23.50715 39.13957 -0.4380 6.67908
Maximum of Months 744.00000 23.95460 52.70921 0.38839 9.24235



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.72208 39.33640 0.34149 7.77592
February 672.00000 23.78546 40.04102 0.36745 7.99207
March 744.00000 23.84515 39.02108 0.39227 8.37551
April 720.00000 23.95000 38.20079 0.44716 9.27308
May 744.00000 23.97056 43.08827 -0.3591 7.82630
June 720.00000 23.98044 49.90385 -0.2735 6.66441
July 744.00000 23.98585 51.67093 -0.2492 6.38535
August 744.00000 23.97381 51.98076 -0.2605 6.48997
September 720.00000 23.95564 48.84492 -0.3199 7.27426
October 744.00000 23.88128 45.11259 0.45428 9.43989
November 720.00000 23.79496 42.13529 0.39040 8.42622
December 744.00000 23.70602 38.96787 0.32877 7.55338
           
Annual Sum or Average 8760.00000 23.87959 44.04989 0.10330 7.78672
Minimum of Months 672.00000 23.70602 38.20079 -0.3591 6.38535
Maximum of Months 744.00000 23.98585 51.98076 0.45428 9.43989



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.83308 37.90051 0.99132 28.23644
February 672.00000 23.85126 38.67780 1.01073 29.12157
March 744.00000 23.92749 38.04883 1.04024 30.21866
April 720.00000 23.94244 37.48338 1.11276 33.36475
May 744.00000 23.98249 42.50562 0.59080 17.50879
June 720.00000 23.89114 49.16267 0.64619 18.79390
July 744.00000 23.89412 50.88896 0.67767 19.42697
August 744.00000 23.89331 51.01132 0.67625 19.39469
September 720.00000 23.87634 47.84580 0.61378 18.04930
October 744.00000 23.95328 44.10045 1.11237 33.23490
November 720.00000 23.93619 41.11079 1.04794 30.57351
December 744.00000 23.81881 37.50857 0.96912 27.31098
           
Annual Sum or Average 8760.00000 23.90027 43.04644 0.87318 25.40855
Minimum of Months 672.00000 23.81881 37.48338 0.59080 17.50879
Maximum of Months 744.00000 23.98249 51.01132 1.11276 33.36475



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.02106 36.64762 -0.4413 9.12607
February 672.00000 21.01802 37.69723 -0.4318 8.91311
March 744.00000 21.05037 37.03126 -0.4222 8.75971
April 720.00000 21.62540 35.53367 -0.2780 6.84599
May 744.00000 21.84534 41.03224 -1.3101 40.99053
June 720.00000 22.34711 47.85202 -1.0916 30.39129
July 744.00000 22.59209 49.24449 -0.9968 26.37025
August 744.00000 22.64230 49.36466 -0.9797 25.38450
September 720.00000 22.34591 46.38490 -1.1019 30.82981
October 744.00000 21.46015 43.70492 -0.2722 6.68832
November 720.00000 21.08016 40.38837 -0.3951 8.32029
December 744.00000 21.00334 36.17842 -0.4558 9.36076
           
Annual Sum or Average 8760.00000 21.67265 41.77973 -0.6830 17.72130
Minimum of Months 672.00000 21.00334 35.53367 -1.3101 6.68832
Maximum of Months 744.00000 22.64230 49.36466 -0.2722 40.99053



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.03111 40.04643 -0.4299 8.90640
February 672.00000 21.04809 41.04340 -0.4152 8.61670
March 744.00000 21.06013 40.38932 -0.4152 8.62914
April 720.00000 21.93363 38.33573 -0.1992 6.14876
May 744.00000 22.17973 43.67261 -1.1986 35.44553
June 720.00000 22.57276 50.57737 -1.0152 27.01206
July 744.00000 22.78046 52.02876 -0.9318 23.75755
August 744.00000 22.86767 52.06721 -0.9013 22.28418
September 720.00000 22.63700 48.97155 -1.0024 26.50361
October 744.00000 21.56270 46.78738 -0.2452 6.61233
November 720.00000 21.06057 43.77114 -0.3981 8.34823
December 744.00000 21.00598 39.57858 -0.4481 9.21259
           
Annual Sum or Average 8760.00000 21.81531 44.79608 -0.6349 16.00528
Minimum of Months 672.00000 21.00598 38.33573 -1.1986 6.14876
Maximum of Months 744.00000 22.86767 52.06721 -0.1992 35.44553



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.03106 37.73884 -0.4271 8.88717
February 672.00000 21.05680 38.73722 -0.4061 8.49377
March 744.00000 21.05705 38.04394 -0.4034 8.43928
April 720.00000 21.80235 36.21987 -0.2031 6.41566
May 744.00000 21.96712 41.71545 -1.2214 36.96162
June 720.00000 22.45950 48.36339 -0.9979 26.80369
July 744.00000 22.70975 49.69871 -0.8977 22.97166
August 744.00000 22.71825 49.94962 -0.8942 22.51186
September 720.00000 22.31904 47.22982 -1.0572 29.34535
October 744.00000 21.34653 44.93676 -0.2766 6.82692
November 720.00000 21.05292 41.48579 -0.3898 8.22679
December 744.00000 21.00916 37.26949 -0.4463 9.18700
           
Annual Sum or Average 8760.00000 21.71400 42.63985 -0.6367 16.30389
Minimum of Months 672.00000 21.00916 36.21987 -1.2214 6.41566
Maximum of Months 744.00000 22.71825 49.94962 -0.2031 36.96162



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.12249 35.92172 -0.4055 8.54386
February 672.00000 21.12445 36.97144 -0.3958 8.33512
March 744.00000 21.21478 36.15395 -0.3745 8.03056
April 720.00000 21.87852 34.47069 -0.2142 6.23915
May 744.00000 22.10409 39.85543 -1.2165 36.37891
June 720.00000 22.58901 46.57699 -1.0014 26.55871
July 744.00000 22.82290 47.96909 -0.9096 22.96971
August 744.00000 22.86720 48.10311 -0.8942 22.10851
September 720.00000 22.57658 45.14695 -1.0160 27.12850
October 744.00000 21.72839 42.46846 -0.2051 6.06613
November 720.00000 21.26129 39.43547 -0.3442 7.60573
December 744.00000 21.06841 35.54118 -0.4262 8.84072
           
Annual Sum or Average 8760.00000 21.86691 40.74111 -0.6185 15.78202
Minimum of Months 672.00000 21.06841 34.47069 -1.2165 6.06613
Maximum of Months 744.00000 22.86720 48.10311 -0.2051 36.37891



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.181212E+10 14308.06 14-JAN-19:04 285.89 0.577421E+10 0.00 0.758633E+10 1.22 3.19 01-JAN-07:20 0.00 0.00
February 0.195837E+10 16370.32 27-FEB-16:04 306.09 0.624023E+10 0.00 0.819860E+10 1.45 3.19 02-FEB-21:10 0.00 0.00
March 0.183772E+10 15472.89 20-MAR-18:02 291.75 0.585564E+10 0.00 0.769336E+10 1.25 3.19 01-MAR-19:46 0.00 0.00
April 0.198249E+11 90203.27 30-APR-18:02 557.36 0.638362E+11 0.00 0.836611E+11 2.47 3.96 29-APR-18:03 0.00 0.00
May 0.212741E+11 87995.62 22-MAY-15:03 620.11 0.675910E+11 0.00 0.888651E+11 2.65 3.96 22-MAY-18:03 0.00 0.00
June 0.408216E+11 122316.44 25-JUN-18:03 687.81 0.132865E+12 0.00 0.173687E+12 3.03 4.37 26-JUN-18:03 0.00 0.00
July 0.597735E+11 124277.20 22-JUL-18:03 731.21 0.192139E+12 0.00 0.251912E+12 3.10 4.21 23-JUL-18:03 0.00 0.00
August 0.660302E+11 106721.99 14-AUG-18:03 742.50 0.209595E+12 0.00 0.275625E+12 3.13 4.13 17-AUG-18:03 0.00 0.00
September 0.430694E+11 89324.79 13-SEP-15:03 695.33 0.139166E+12 0.00 0.182235E+12 3.06 4.09 10-SEP-18:02 0.00 0.00
October 0.887147E+10 56262.61 07-OCT-15:02 435.72 0.278683E+11 0.00 0.367398E+11 1.86 3.66 07-OCT-15:02 0.00 0.00
November 0.163283E+10 13846.88 27-NOV-09:04 257.12 0.520033E+10 0.00 0.683316E+10 1.14 3.19 03-NOV-15:30 0.00 0.00
December 0.120170E+10 16670.55 12-DEC-09:04 268.23 0.382913E+10 0.00 0.503082E+10 1.15 3.19 01-DEC-16:30 0.00 0.00
                         
Annual Sum or Average 0.268108E+12     5879.13 0.859959E+12 0.00 0.112807E+13 2.13     0.00 0.00
Minimum of Months 0.120170E+10 13846.88   257.12 0.382913E+10 0.00 0.503082E+10 1.14 3.19   0.00 0.00
Maximum of Months 0.660302E+11 124277.20   742.50 0.209595E+12 0.00 0.275625E+12 3.13 4.37   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.786812E+11 0.00 743.35 212587.07 28-JAN-19:01 0.00 53.28 80.36 0.26 0.00 0.07 0.54 28-JAN-19:01
February 0.577889E+11 0.00 671.38 209731.63 11-FEB-19:02 0.00 54.03 80.33 0.22 0.00 0.06 0.53 11-FEB-19:02
March 0.596751E+11 0.00 743.18 195823.36 24-MAR-08:62 0.00 52.01 80.06 0.20 0.00 0.06 0.50 24-MAR-08:62
April 0.301826E+11 0.00 609.34 162322.30 07-APR-20:10 0.00 46.62 73.77 0.09 0.00 0.03 0.41 07-APR-20:10
May 0.378950E+11 0.00 617.31 141197.46 04-MAY-08:62 0.00 41.58 72.10 0.10 0.00 0.04 0.36 04-MAY-08:62
June 0.179549E+11 0.00 423.35 119325.45 02-JUN-02:62 0.00 35.57 60.34 0.04 0.00 0.02 0.30 02-JUN-02:62
July 0.110180E+11 0.00 327.86 116881.89 15-JUL-04:55 0.00 34.83 53.64 0.03 0.00 0.01 0.30 15-JUL-04:55
August 0.716423E+10 0.00 280.73 115564.39 23-AUG-03:52 0.00 36.86 52.71 0.02 0.00 0.01 0.29 23-AUG-03:52
September 0.178250E+11 0.00 388.84 118453.11 28-SEP-06:48 0.00 41.67 61.36 0.05 0.00 0.02 0.30 28-SEP-06:48
October 0.528115E+11 0.00 701.91 197334.45 30-OCT-08:61 0.00 48.82 77.94 0.16 0.00 0.05 0.50 30-OCT-08:61
November 0.745032E+11 0.00 718.87 204629.84 02-NOV-08:61 0.00 51.64 79.93 0.25 0.00 0.07 0.52 02-NOV-08:61
December 0.937484E+11 0.00 743.94 203362.30 22-DEC-16:01 0.00 52.63 80.39 0.31 0.00 0.09 0.52 22-DEC-16:01
                           
Annual Sum or Average 0.539248E+12 0.00 6970.06     0.00 45.75 71.03 0.14 0.00 0.04    
Minimum of Months 0.716423E+10 0.00 280.73 115564.39   0.00 34.83 52.71 0.02 0.00 0.01 0.29  
Maximum of Months 0.937484E+11 0.00 743.94 212587.07   0.00 54.03 80.39 0.31 0.00 0.09 0.54  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.360948E+09 0.00 176.58 0.360948E+09 0.00 0.00 0.00 0.00 34894.34 27-JAN-22:03 34894.34 27-JAN-22:03 0.00 0.00 0.00
February 0.319493E+09 0.00 198.34 0.319493E+09 0.00 0.00 0.00 0.00 20123.75 04-FEB-19:20 20123.75 04-FEB-19:20 0.00 0.00 0.00
March 0.330694E+09 0.00 155.98 0.330694E+09 0.00 0.00 0.00 0.00 32879.96 08-MAR-20:35 32879.96 08-MAR-20:35 0.00 0.00 0.00
April 0.154374E+11 0.00 171.52 0.154223E+11 0.00 0.00 0.00 0.00 187121.57 30-APR-18:10 187121.57 30-APR-18:10 0.00 0.00 0.00
May 0.156008E+11 0.00 187.97 0.156008E+11 0.00 0.00 0.00 0.00 161265.13 22-MAY-15:30 161265.13 22-MAY-15:30 0.00 0.00 0.00
June 0.493788E+11 0.00 298.92 0.468384E+11 0.00 0.00 0.00 0.00 336077.52 25-JUN-18:00 210259.93 12-JUN-18:10 0.00 0.00 0.00
July 0.848233E+11 0.00 422.47 0.835516E+11 0.00 0.00 0.00 0.00 232245.05 22-JUL-18:10 232245.05 22-JUL-18:10 0.00 0.00 0.00
August 0.987290E+11 0.00 477.58 0.974668E+11 0.00 0.00 0.00 0.00 212528.36 14-AUG-18:10 212528.36 14-AUG-18:10 0.00 0.00 0.00
September 0.507377E+11 0.00 344.00 0.503435E+11 0.00 0.00 0.00 0.00 159598.22 11-SEP-17:17 159598.22 11-SEP-17:17 0.00 0.00 0.00
October 0.286056E+10 0.00 131.91 0.286056E+10 0.00 0.00 0.00 0.00 71458.90 07-OCT-15:03 71458.90 07-OCT-15:03 0.00 0.00 0.00
November 0.349138E+09 0.00 129.19 0.349138E+09 0.00 0.00 0.00 0.00 27014.06 24-NOV-11:50 27014.06 24-NOV-11:50 0.00 0.00 0.00
December 0.396484E+09 0.00 238.18 0.396484E+09 0.00 0.00 0.00 0.00 23056.11 20-DEC-22:10 23056.11 20-DEC-22:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.319324E+12 0.00 2932.63 0.313841E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.319493E+09 0.00 129.19 0.319493E+09 0.00 0.00 0.00 0.00 20123.75   20123.75   0.00 0.00 0.00
Maximum of Months 0.987290E+11 0.00 477.58 0.974668E+11 0.00 0.00 0.00 0.00 336077.52   232245.05   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00
February 3613.89 0.00 0.02 3613.89 0.00 0.00 0.00 0.00 54.21 03-FEB-16:09 54.21 03-FEB-16:09 0.00 0.00 0.00
March 79458.00 0.00 0.19 79458.00 0.00 0.00 0.00 0.00 121.78 25-MAR-21:10 121.78 25-MAR-21:10 0.00 0.00 0.00
April 0.245803E+10 0.00 59.54 0.245615E+10 0.00 0.00 0.00 0.00 28194.89 30-APR-18:02 28194.89 30-APR-18:02 0.00 0.00 0.00
May 0.246120E+10 0.00 72.61 0.246120E+10 0.00 0.00 0.00 0.00 28053.87 22-MAY-15:00 28053.87 22-MAY-15:00 0.00 0.00 0.00
June 0.824314E+10 0.00 198.62 0.756366E+10 0.00 0.00 0.00 0.00 43677.86 25-JUN-18:00 29805.17 13-JUN-15:02 0.00 0.00 0.00
July 0.146576E+11 0.00 354.00 0.138663E+11 0.00 0.00 0.00 0.00 32333.62 23-JUL-16:00 31069.79 22-JUL-15:00 0.00 0.00 0.00
August 0.178130E+11 0.00 428.83 0.168728E+11 0.00 0.00 0.00 0.00 32326.30 17-AUG-15:00 28828.34 14-AUG-15:02 0.00 0.00 0.00
September 0.918905E+10 0.00 248.83 0.875968E+10 0.00 0.00 0.00 0.00 30819.96 10-SEP-15:02 27277.78 13-SEP-15:02 0.00 0.00 0.00
October 0.434600E+09 0.00 26.85 0.434600E+09 0.00 0.00 0.00 0.00 15106.35 07-OCT-15:00 15106.35 07-OCT-15:00 0.00 0.00 0.00
November 6967765.75 0.00 1.17 6967765.75 0.00 0.00 0.00 0.00 4050.01 24-NOV-12:00 4050.01 24-NOV-12:00 0.00 0.00 0.00
December 32372.43 0.00 0.17 32372.43 0.00 0.00 0.00 0.00 53.95 21-DEC-14:30 53.95 21-DEC-14:30 0.00 0.00 0.00
                               
Annual Sum or Average 0.552637E+11 0.00 1390.83 0.524214E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.178130E+11 0.00 428.83 0.168728E+11 0.00 0.00 0.00 0.00 43677.86   31069.79   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 28322137.19 0.00 6.81 26610512.77 0.00 0.00 0.00 0.00 13253.21 19-JAN-16:02 13253.21 19-JAN-16:02 0.00 0.00 0.00
February 0.177926E+09 0.00 32.29 0.167099E+09 0.00 0.00 0.00 0.00 13734.17 09-FEB-16:02 13734.17 09-FEB-16:02 0.00 0.00 0.00
March 91363090.54 0.00 19.43 89545570.39 0.00 0.00 0.00 0.00 13264.54 23-MAR-18:02 13264.54 23-MAR-18:02 0.00 0.00 0.00
April 0.253621E+10 0.00 334.04 0.221509E+10 0.00 0.00 0.00 0.00 14058.34 27-APR-15:02 14058.34 27-APR-15:02 0.00 0.00 0.00
May 0.309043E+10 0.00 387.32 0.233972E+10 0.00 0.00 0.00 0.00 14168.88 21-MAY-15:02 14168.88 21-MAY-15:02 0.00 0.00 0.00
June 0.478486E+10 0.00 559.31 0.306841E+10 0.00 0.00 0.00 0.00 14449.70 27-JUN-08:62 13776.27 08-JUN-18:02 0.00 0.00 0.00
July 0.611751E+10 0.00 596.96 0.388503E+10 0.00 0.00 0.00 0.00 14718.74 22-JUL-08:61 14041.26 05-JUL-18:02 0.00 0.00 0.00
August 0.573807E+10 0.00 647.62 0.344459E+10 0.00 0.00 0.00 0.00 14580.22 11-AUG-15:02 14321.16 24-AUG-15:02 0.00 0.00 0.00
September 0.408150E+10 0.00 517.56 0.257198E+10 0.00 0.00 0.00 0.00 14233.66 10-SEP-18:02 13800.13 20-SEP-15:02 0.00 0.00 0.00
October 0.897164E+09 0.00 143.23 0.702383E+09 0.00 0.00 0.00 0.00 14166.82 07-OCT-15:02 14166.82 07-OCT-15:02 0.00 0.00 0.00
November 41725306.50 0.00 9.23 38482919.75 0.00 0.00 0.00 0.00 13354.21 03-NOV-15:01 13354.21 03-NOV-15:01 0.00 0.00 0.00
December 1890089.82 0.00 1.34 1584545.54 0.00 0.00 0.00 0.00 2472.53 05-DEC-19:04 2187.98 26-DEC-16:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.275870E+11 0.00 3255.13 0.185505E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 1890089.82 0.00 1.34 1584545.54 0.00 0.00 0.00 0.00 2472.53   2187.98   0.00 0.00 0.00
Maximum of Months 0.611751E+10 0.00 647.62 0.388503E+10 0.00 0.00 0.00 0.00 14718.74   14321.16   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 5984395.86 0.00 2.17 4630674.40 0.00 0.00 0.00 0.00 3369.94 19-JAN-16:02 3369.94 19-JAN-16:02 0.00 0.00 0.00
February 42640901.02 0.00 13.39 37700575.21 0.00 0.00 0.00 0.00 11136.27 19-FEB-16:02 11136.27 19-FEB-16:02 0.00 0.00 0.00
March 49681255.74 0.00 12.05 47982014.27 0.00 0.00 0.00 0.00 11514.30 23-MAR-18:02 11514.30 23-MAR-18:02 0.00 0.00 0.00
April 0.155589E+10 0.00 218.15 0.135119E+10 0.00 0.00 0.00 0.00 12487.02 27-APR-15:02 12487.02 27-APR-15:02 0.00 0.00 0.00
May 0.237698E+10 0.00 320.99 0.181965E+10 0.00 0.00 0.00 0.00 12585.53 21-MAY-15:02 12585.53 21-MAY-15:02 0.00 0.00 0.00
June 0.419417E+10 0.00 518.90 0.275826E+10 0.00 0.00 0.00 0.00 12805.55 27-JUN-08:62 12614.44 13-JUN-18:02 0.00 0.00 0.00
July 0.524609E+10 0.00 554.95 0.338671E+10 0.00 0.00 0.00 0.00 13038.72 22-JUL-08:61 12472.07 05-JUL-18:02 0.00 0.00 0.00
August 0.422007E+10 0.00 576.40 0.249875E+10 0.00 0.00 0.00 0.00 12934.35 09-AUG-15:02 12720.50 24-AUG-15:02 0.00 0.00 0.00
September 0.225167E+10 0.00 384.24 0.135275E+10 0.00 0.00 0.00 0.00 12488.13 24-SEP-15:02 12488.13 24-SEP-15:02 0.00 0.00 0.00
October 0.335870E+09 0.00 60.13 0.282976E+09 0.00 0.00 0.00 0.00 12582.94 07-OCT-15:02 12582.94 07-OCT-15:02 0.00 0.00 0.00
November 7395862.10 0.00 2.64 5326322.17 0.00 0.00 0.00 0.00 4573.39 10-NOV-16:02 4573.39 10-NOV-16:02 0.00 0.00 0.00
December 2603157.88 0.00 1.84 2294364.00 0.00 0.00 0.00 0.00 1913.21 02-DEC-09:04 1001.62 02-DEC-09:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.202890E+11 0.00 2665.84 0.135482E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 2603157.88 0.00 1.84 2294364.00 0.00 0.00 0.00 0.00 1913.21   1001.62   0.00 0.00 0.00
Maximum of Months 0.524609E+10 0.00 576.40 0.338671E+10 0.00 0.00 0.00 0.00 13038.72   12720.50   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.623285E+09 0.00 22.03 0.623285E+09 0.00 0.00 0.00 0.00 20486.01 21-JAN-11:30 20486.01 21-JAN-11:30 0.00 0.00 0.00
February 0.464057E+09 0.00 21.62 0.457657E+09 0.00 0.00 0.00 0.00 16187.21 04-FEB-14:40 16187.21 04-FEB-14:40 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 0.00 01-MAR-00:03 0.00 0.00 0.00
April 0.133199E+11 0.00 260.63 0.131494E+11 0.00 0.00 0.00 0.00 40959.76 30-APR-12:50 40959.76 30-APR-12:50 0.00 0.00 0.00
May 0.873763E+10 0.00 249.18 0.676474E+10 0.00 0.00 0.00 0.00 31660.09 23-MAY-13:10 26815.25 11-MAY-13:20 0.00 0.00 0.00
June 0.117690E+11 0.00 352.86 0.548046E+10 0.00 0.00 0.00 0.00 32870.71 13-JUN-13:20 22615.83 13-JUN-13:20 0.00 0.00 0.00
July 0.169769E+11 0.00 416.10 0.864798E+10 0.00 0.00 0.00 0.00 38922.35 22-JUL-13:10 31745.38 22-JUL-13:30 0.00 0.00 0.00
August 0.233450E+11 0.00 440.05 0.145095E+11 0.00 0.00 0.00 0.00 43225.54 19-AUG-13:00 38225.36 20-AUG-12:50 0.00 0.00 0.00
September 0.291580E+11 0.00 445.77 0.214239E+11 0.00 0.00 0.00 0.00 53399.07 27-SEP-12:40 52146.72 25-SEP-13:50 0.00 0.00 0.00
October 0.934595E+10 0.00 151.07 0.913630E+10 0.00 0.00 0.00 0.00 48203.07 07-OCT-13:20 48203.07 07-OCT-13:20 0.00 0.00 0.00
November 0.227624E+09 0.00 10.68 0.227624E+09 0.00 0.00 0.00 0.00 16015.57 11-NOV-13:23 16015.57 11-NOV-13:23 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.113967E+12 0.00 2369.98 0.804207E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.291580E+11 0.00 445.77 0.214239E+11 0.00 0.00 0.00 0.00 53399.07   52146.72   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.280943E+09 0.00 35.33 0.138625E+09 0.00 0.00 0.00 0.00 41358.86 29-JAN-09:02 41358.86 29-JAN-09:02 0.00 0.00 0.00
February 0.188647E+09 0.00 23.53 0.115809E+09 0.00 0.00 0.00 0.00 29155.63 11-FEB-19:03 29155.63 11-FEB-19:03 0.00 0.00 0.00
March 0.151004E+10 0.00 133.23 0.117150E+10 0.00 0.00 0.00 0.00 47737.98 25-MAR-08:62 47737.98 25-MAR-08:62 0.00 0.00 0.00
April 0.950106E+10 0.00 356.37 0.820543E+10 0.00 0.00 0.00 0.00 55615.37 29-APR-18:02 55615.37 29-APR-18:02 0.00 0.00 0.00
May 0.153766E+11 0.00 456.48 0.113277E+11 0.00 0.00 0.00 0.00 55418.58 21-MAY-18:02 55418.58 21-MAY-18:02 0.00 0.00 0.00
June 0.275946E+11 0.00 506.83 0.185855E+11 0.00 0.00 0.00 0.00 61053.46 26-JUN-18:02 58739.49 13-JUN-18:02 0.00 0.00 0.00
July 0.312005E+11 0.00 525.57 0.206880E+11 0.00 0.00 0.00 0.00 58699.24 23-JUL-18:02 58089.71 22-JUL-15:02 0.00 0.00 0.00
August 0.251824E+11 0.00 524.98 0.150703E+11 0.00 0.00 0.00 0.00 57524.86 17-AUG-15:02 57408.55 14-AUG-15:02 0.00 0.00 0.00
September 0.151798E+11 0.00 488.32 0.850014E+10 0.00 0.00 0.00 0.00 56846.13 16-SEP-08:62 55032.07 13-SEP-15:02 0.00 0.00 0.00
October 0.340867E+10 0.00 234.03 0.175088E+10 0.00 0.00 0.00 0.00 52750.61 09-OCT-08:63 50729.05 06-OCT-18:02 0.00 0.00 0.00
November 0.665538E+09 0.00 72.64 0.267723E+09 0.00 0.00 0.00 0.00 43292.13 23-NOV-09:01 43292.13 23-NOV-09:01 0.00 0.00 0.00
December 71134449.63 0.00 3.82 67325489.27 0.00 0.00 0.00 0.00 24885.84 06-DEC-19:04 24885.84 06-DEC-19:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.130160E+12 0.00 3361.14 0.858890E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 71134449.63 0.00 3.82 67325489.27 0.00 0.00 0.00 0.00 24885.84   24885.84   0.00 0.00 0.00
Maximum of Months 0.312005E+11 0.00 525.57 0.206880E+11 0.00 0.00 0.00 0.00 61053.46   58739.49   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 67099034.24 0.00 17.92 57538430.73 0.00 0.00 0.00 0.00 4483.25 21-JAN-16:02 4483.25 21-JAN-16:02 0.00 0.00 0.00
February 0.111522E+09 0.00 25.24 99723181.64 0.00 0.00 0.00 0.00 11641.18 20-FEB-09:01 11641.18 20-FEB-09:01 0.00 0.00 0.00
March 61489842.29 0.00 23.54 58660910.75 0.00 0.00 0.00 0.00 6584.07 20-MAR-15:02 6584.07 20-MAR-15:02 0.00 0.00 0.00
April 0.290564E+10 0.00 386.12 0.254515E+10 0.00 0.00 0.00 0.00 12695.18 27-APR-15:02 12695.18 27-APR-15:02 0.00 0.00 0.00
May 0.307387E+10 0.00 430.52 0.226318E+10 0.00 0.00 0.00 0.00 12795.26 21-MAY-15:02 12795.26 21-MAY-15:02 0.00 0.00 0.00
June 0.443038E+10 0.00 558.62 0.275037E+10 0.00 0.00 0.00 0.00 13660.55 26-JUN-18:02 13058.50 12-JUN-18:02 0.00 0.00 0.00
July 0.570510E+10 0.00 631.77 0.350217E+10 0.00 0.00 0.00 0.00 12987.72 13-JUL-15:02 12522.94 16-JUL-18:02 0.00 0.00 0.00
August 0.604670E+10 0.00 668.09 0.370965E+10 0.00 0.00 0.00 0.00 13177.27 11-AUG-15:02 12932.83 24-AUG-15:02 0.00 0.00 0.00
September 0.461819E+10 0.00 564.86 0.295367E+10 0.00 0.00 0.00 0.00 12559.49 10-SEP-18:02 12479.95 11-SEP-18:02 0.00 0.00 0.00
October 0.966356E+09 0.00 154.52 0.733929E+09 0.00 0.00 0.00 0.00 12793.18 07-OCT-15:02 12793.18 07-OCT-15:02 0.00 0.00 0.00
November 63684638.48 0.00 18.93 48026076.34 0.00 0.00 0.00 0.00 11144.13 03-NOV-15:01 11144.13 03-NOV-15:01 0.00 0.00 0.00
December 16166679.79 0.00 8.54 15611219.57 0.00 0.00 0.00 0.00 3165.06 20-DEC-09:04 2997.38 03-DEC-09:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.280662E+11 0.00 3488.66 0.187377E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 16166679.79 0.00 8.54 15611219.57 0.00 0.00 0.00 0.00 3165.06   2997.38   0.00 0.00 0.00
Maximum of Months 0.604670E+10 0.00 668.09 0.370965E+10 0.00 0.00 0.00 0.00 13660.55   13058.50   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 6291432.26 0.00 2.58 4899381.93 0.00 0.00 0.00 0.00 3445.56 23-JAN-19:04 3158.56 21-JAN-09:03 0.00 0.00 0.00
February 17121347.77 0.00 8.54 14968425.63 0.00 0.00 0.00 0.00 4427.99 20-FEB-09:01 4427.99 20-FEB-09:01 0.00 0.00 0.00
March 24194173.56 0.00 8.42 23043627.66 0.00 0.00 0.00 0.00 3911.14 21-MAR-18:03 3911.14 21-MAR-18:03 0.00 0.00 0.00
April 0.176518E+10 0.00 277.85 0.151860E+10 0.00 0.00 0.00 0.00 11365.51 27-APR-15:02 11365.51 27-APR-15:02 0.00 0.00 0.00
May 0.229254E+10 0.00 351.65 0.169850E+10 0.00 0.00 0.00 0.00 11454.86 21-MAY-15:02 11454.86 21-MAY-15:02 0.00 0.00 0.00
June 0.380026E+10 0.00 510.02 0.242624E+10 0.00 0.00 0.00 0.00 12250.92 26-JUN-18:02 11650.72 12-JUN-18:02 0.00 0.00 0.00
July 0.476045E+10 0.00 606.95 0.297178E+10 0.00 0.00 0.00 0.00 11937.31 17-JUL-15:02 11401.21 21-JUL-15:02 0.00 0.00 0.00
August 0.441537E+10 0.00 639.83 0.265353E+10 0.00 0.00 0.00 0.00 11848.17 17-AUG-15:02 11776.50 14-AUG-15:02 0.00 0.00 0.00
September 0.259553E+10 0.00 438.23 0.159232E+10 0.00 0.00 0.00 0.00 11720.34 12-SEP-15:02 11576.70 13-SEP-15:02 0.00 0.00 0.00
October 0.332145E+09 0.00 73.29 0.249557E+09 0.00 0.00 0.00 0.00 10877.05 07-OCT-15:02 10877.05 07-OCT-15:02 0.00 0.00 0.00
November 9467391.58 0.00 3.79 7381350.43 0.00 0.00 0.00 0.00 3420.70 19-NOV-09:03 3420.70 19-NOV-09:03 0.00 0.00 0.00
December 3641760.28 0.00 1.73 3431144.60 0.00 0.00 0.00 0.00 2830.21 11-DEC-09:04 2830.21 11-DEC-09:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.200222E+11 0.00 2922.87 0.131643E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 3641760.28 0.00 1.73 3431144.60 0.00 0.00 0.00 0.00 2830.21   2830.21   0.00 0.00 0.00
Maximum of Months 0.476045E+10 0.00 639.83 0.297178E+10 0.00 0.00 0.00 0.00 12250.92   11776.50   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 6445606.12 0.00 5.02 5942575.46 0.00 0.00 0.00 0.00 3505.48 19-JAN-16:02 3505.48 19-JAN-16:02 0.00 0.00 0.00
February 46579099.17 0.00 28.61 43922238.45 0.00 0.00 0.00 0.00 3614.16 09-FEB-16:02 3614.16 09-FEB-16:02 0.00 0.00 0.00
March 21362763.67 0.00 15.81 20706987.50 0.00 0.00 0.00 0.00 3550.15 23-MAR-18:02 3550.15 23-MAR-18:02 0.00 0.00 0.00
April 0.654608E+09 0.00 273.81 0.586573E+09 0.00 0.00 0.00 0.00 3699.65 27-APR-15:02 3699.65 27-APR-15:02 0.00 0.00 0.00
May 0.765366E+09 0.00 320.15 0.607404E+09 0.00 0.00 0.00 0.00 3728.62 21-MAY-15:02 3728.62 21-MAY-15:02 0.00 0.00 0.00
June 0.116930E+10 0.00 469.35 0.788341E+09 0.00 0.00 0.00 0.00 3957.64 27-JUN-08:62 3672.41 13-JUN-18:02 0.00 0.00 0.00
July 0.151052E+10 0.00 560.44 0.995958E+09 0.00 0.00 0.00 0.00 3931.42 22-JUL-08:61 3694.85 05-JUL-18:02 0.00 0.00 0.00
August 0.135588E+10 0.00 587.72 0.850434E+09 0.00 0.00 0.00 0.00 3839.52 09-AUG-15:02 3768.73 24-AUG-15:02 0.00 0.00 0.00
September 0.924010E+09 0.00 420.42 0.613102E+09 0.00 0.00 0.00 0.00 3738.67 10-SEP-18:02 3631.48 20-SEP-15:02 0.00 0.00 0.00
October 0.199366E+09 0.00 102.27 0.165574E+09 0.00 0.00 0.00 0.00 3728.00 07-OCT-15:02 3728.00 07-OCT-15:02 0.00 0.00 0.00
November 9733252.38 0.00 6.90 8756093.75 0.00 0.00 0.00 0.00 3485.84 10-NOV-16:02 3485.84 10-NOV-16:02 0.00 0.00 0.00
December 196659.91 0.00 0.13 164680.32 0.00 0.00 0.00 0.00 609.52 05-DEC-19:04 569.56 26-DEC-16:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.666337E+10 0.00 2790.64 0.468688E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 196659.91 0.00 0.13 164680.32 0.00 0.00 0.00 0.00 609.52   569.56   0.00 0.00 0.00
Maximum of Months 0.151052E+10 0.00 587.72 0.995958E+09 0.00 0.00 0.00 0.00 3957.64   3768.73   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 1008732.70 0.00 0.67 700694.78 0.00 0.00 0.00 0.00 829.85 21-JAN-16:03 829.85 21-JAN-16:03 0.00 0.00 0.00
February 7466194.52 0.00 9.86 6189805.83 0.00 0.00 0.00 0.00 2119.99 27-FEB-16:01 2119.99 27-FEB-16:01 0.00 0.00 0.00
March 10611378.09 0.00 10.18 10061741.15 0.00 0.00 0.00 0.00 3035.69 23-MAR-18:02 3035.69 23-MAR-18:02 0.00 0.00 0.00
April 0.399037E+09 0.00 177.87 0.358204E+09 0.00 0.00 0.00 0.00 3257.65 27-APR-15:02 3257.65 27-APR-15:02 0.00 0.00 0.00
May 0.577346E+09 0.00 255.51 0.467583E+09 0.00 0.00 0.00 0.00 3283.28 21-MAY-15:02 3283.28 21-MAY-15:02 0.00 0.00 0.00
June 0.100750E+10 0.00 424.78 0.700641E+09 0.00 0.00 0.00 0.00 3481.84 27-JUN-08:62 3262.32 13-JUN-18:02 0.00 0.00 0.00
July 0.126828E+10 0.00 520.15 0.845978E+09 0.00 0.00 0.00 0.00 3456.82 22-JUL-08:61 3253.57 05-JUL-18:02 0.00 0.00 0.00
August 0.951941E+09 0.00 486.98 0.594068E+09 0.00 0.00 0.00 0.00 3383.53 11-AUG-18:02 3318.54 24-AUG-15:02 0.00 0.00 0.00
September 0.473463E+09 0.00 262.80 0.310415E+09 0.00 0.00 0.00 0.00 3259.45 10-SEP-18:02 3253.84 24-SEP-15:02 0.00 0.00 0.00
October 70545247.77 0.00 34.72 61148662.62 0.00 0.00 0.00 0.00 3282.55 07-OCT-15:02 3282.55 07-OCT-15:02 0.00 0.00 0.00
November 1929890.68 0.00 1.26 1408957.22 0.00 0.00 0.00 0.00 1282.05 03-NOV-15:02 1282.05 03-NOV-15:02 0.00 0.00 0.00
December 82757.57 0.00 0.03 56661.25 0.00 0.00 0.00 0.00 760.51 05-DEC-19:04 572.08 05-DEC-19:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.476921E+10 0.00 2184.82 0.335646E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 82757.57 0.00 0.03 56661.25 0.00 0.00 0.00 0.00 760.51   572.08   0.00 0.00 0.00
Maximum of Months 0.126828E+10 0.00 520.15 0.845978E+09 0.00 0.00 0.00 0.00 3481.84   3318.54   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.106210E+10 0.00 121.71 0.937039E+09 0.00 0.00 0.00 0.00 20007.23 21-JAN-16:02 20007.23 21-JAN-16:02 0.00 0.00 0.00
February 0.130561E+10 0.00 133.58 0.123866E+10 0.00 0.00 0.00 0.00 20005.59 09-FEB-16:02 20005.59 09-FEB-16:02 0.00 0.00 0.00
March 0.336381E+09 0.00 69.74 0.306221E+09 0.00 0.00 0.00 0.00 19999.15 20-MAR-15:02 19999.15 20-MAR-15:02 0.00 0.00 0.00
April 0.515479E+10 0.00 416.76 0.453885E+10 0.00 0.00 0.00 0.00 20476.59 27-APR-15:02 20476.59 27-APR-15:02 0.00 0.00 0.00
May 0.413383E+10 0.00 410.81 0.287254E+10 0.00 0.00 0.00 0.00 20637.92 21-MAY-15:02 20637.92 21-MAY-15:02 0.00 0.00 0.00
June 0.552551E+10 0.00 537.34 0.308120E+10 0.00 0.00 0.00 0.00 22312.28 26-JUN-18:02 20955.31 12-JUN-18:02 0.00 0.00 0.00
July 0.747323E+10 0.00 598.95 0.425015E+10 0.00 0.00 0.00 0.00 21240.01 23-JUL-18:02 21149.53 22-JUL-08:61 0.00 0.00 0.00
August 0.889892E+10 0.00 650.33 0.549221E+10 0.00 0.00 0.00 0.00 21553.98 11-AUG-15:02 20223.82 10-AUG-15:02 0.00 0.00 0.00
September 0.876312E+10 0.00 584.27 0.603337E+10 0.00 0.00 0.00 0.00 21122.69 10-SEP-18:02 20453.75 12-SEP-15:02 0.00 0.00 0.00
October 0.321597E+10 0.00 272.35 0.243969E+10 0.00 0.00 0.00 0.00 20636.26 07-OCT-15:02 20636.26 07-OCT-15:02 0.00 0.00 0.00
November 0.825487E+09 0.00 97.71 0.683202E+09 0.00 0.00 0.00 0.00 20010.36 11-NOV-16:02 20010.36 11-NOV-16:02 0.00 0.00 0.00
December 0.312739E+09 0.00 38.49 0.304826E+09 0.00 0.00 0.00 0.00 19381.28 18-DEC-16:01 19381.28 18-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.470077E+11 0.00 3932.03 0.321780E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.312739E+09 0.00 38.49 0.304826E+09 0.00 0.00 0.00 0.00 19381.28   19381.28   0.00 0.00 0.00
Maximum of Months 0.889892E+10 0.00 650.33 0.603337E+10 0.00 0.00 0.00 0.00 22312.28   21149.53   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 563.62 364.98 198.64 558.51 513.62 0.00 0.00 0.00
February 683.92 416.83 267.09 694.73 496.31 0.00 0.00 0.00
March 422.12 122.02 300.10 353.11 413.28 0.00 0.00 0.00
April 865.32 383.42 481.90 986.81 343.86 0.00 0.00 0.00
May 725.42 235.00 490.43 775.99 292.66 0.00 0.00 0.00
June 669.64 161.95 507.69 754.34 214.80 0.00 0.00 0.00
July 721.80 223.30 498.49 867.89 197.64 0.00 0.00 0.00
August 847.76 379.84 467.92 1061.41 218.05 0.00 0.00 0.00
September 1015.94 599.62 416.32 1249.76 286.81 0.00 0.00 0.00
October 677.90 390.83 287.07 745.63 381.91 0.00 0.00 0.00
November 489.54 297.70 191.84 488.57 467.37 0.00 0.00 0.00
December 388.47 249.10 139.37 373.60 579.38 0.00 0.00 0.00
                 
Annual Sum or Average 671.57 317.45 354.12 741.53 366.51 0.00 0.00 0.00
Minimum of Months 388.47 122.02 139.37 353.11 197.64 0.00 0.00 0.00
Maximum of Months 1015.94 599.62 507.69 1249.76 579.38 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1587.11 1027.75 559.36 1554.43 1487.26 0.00 0.00 0.00
February 1925.88 1173.78 752.10 1934.44 1443.47 0.00 0.00 0.00
March 1188.66 343.60 845.06 974.31 1204.38 0.00 0.00 0.00
April 2436.68 1079.69 1356.99 2743.68 1026.99 0.00 0.00 0.00
May 2042.74 661.73 1381.00 2147.17 882.99 0.00 0.00 0.00
June 1885.66 456.04 1429.61 2082.29 660.37 0.00 0.00 0.00
July 2032.53 628.81 1403.72 2402.00 610.50 0.00 0.00 0.00
August 2387.23 1069.59 1317.63 2950.08 677.50 0.00 0.00 0.00
September 2860.82 1688.48 1172.34 3483.39 875.70 0.00 0.00 0.00
October 1908.91 1100.54 808.37 2075.34 1138.23 0.00 0.00 0.00
November 1378.50 838.29 540.21 1358.35 1370.49 0.00 0.00 0.00
December 1093.90 701.44 392.46 1040.13 1671.83 0.00 0.00 0.00
                 
Annual Sum or Average 1891.09 893.91 997.17 2059.30 1085.69 0.00 0.00 0.00
Minimum of Months 1093.90 343.60 392.46 974.31 610.50 0.00 0.00 0.00
Maximum of Months 2860.82 1688.48 1429.61 3483.39 1671.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2061.74 1335.10 726.64 2039.08 2067.83 0.00 0.00 0.00
February 2501.82 1524.80 977.02 2541.31 1999.54 0.00 0.00 0.00
March 1544.14 446.36 1097.78 1263.87 1695.79 0.00 0.00 0.00
April 3165.39 1402.59 1762.80 3618.33 1420.84 0.00 0.00 0.00
May 2653.63 859.63 1794.00 2819.22 1236.05 0.00 0.00 0.00
June 2449.58 592.43 1857.15 2723.99 932.70 0.00 0.00 0.00
July 2640.37 816.86 1823.51 3152.04 856.95 0.00 0.00 0.00
August 3101.14 1389.46 1711.68 3887.88 937.50 0.00 0.00 0.00
September 3716.37 2193.43 1522.94 4593.55 1202.25 0.00 0.00 0.00
October 2479.78 1429.67 1050.12 2728.46 1592.99 0.00 0.00 0.00
November 1790.75 1088.99 701.76 1778.69 1919.85 0.00 0.00 0.00
December 1421.04 911.21 509.83 1359.70 2327.67 0.00 0.00 0.00
                 
Annual Sum or Average 2456.63 1161.25 1295.39 2705.07 1513.46 0.00 0.00 0.00
Minimum of Months 1421.04 446.36 509.83 1263.87 856.95 0.00 0.00 0.00
Maximum of Months 3716.37 2193.43 1857.15 4593.55 2327.67 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 111.44 72.16 39.27 112.95 100.60 0.00 0.00 0.00
February 135.22 82.42 52.81 139.60 98.04 0.00 0.00 0.00
March 83.46 24.13 59.33 71.20 81.60 0.00 0.00 0.00
April 171.09 75.81 95.28 196.29 68.81 0.00 0.00 0.00
May 143.43 46.46 96.97 152.43 59.57 0.00 0.00 0.00
June 132.40 32.02 100.38 147.12 43.53 0.00 0.00 0.00
July 142.71 44.15 98.56 170.76 39.22 0.00 0.00 0.00
August 167.62 75.10 92.52 210.98 42.29 0.00 0.00 0.00
September 200.87 118.55 82.32 249.61 55.99 0.00 0.00 0.00
October 134.03 77.27 56.76 149.68 74.89 0.00 0.00 0.00
November 96.79 58.86 37.93 98.41 91.29 0.00 0.00 0.00
December 76.81 49.25 27.56 75.46 114.02 0.00 0.00 0.00
                 
Annual Sum or Average 132.78 62.77 70.02 147.67 72.36 0.00 0.00 0.00
Minimum of Months 76.81 24.13 27.56 71.20 39.22 0.00 0.00 0.00
Maximum of Months 200.87 118.55 100.38 249.61 114.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.05 23.94 49.11 44.84 202.31 0.00 0.00 0.00
February 129.22 55.01 74.22 102.26 192.02 0.00 0.00 0.00
March 116.25 22.35 93.89 76.44 152.74 0.00 0.00 0.00
April 273.78 108.55 165.23 285.45 125.05 0.00 0.00 0.00
May 321.27 130.65 190.62 333.43 105.80 0.00 0.00 0.00
June 346.85 142.80 204.06 389.81 77.92 0.00 0.00 0.00
July 353.04 155.51 197.53 414.31 70.49 0.00 0.00 0.00
August 297.09 128.70 168.39 350.63 77.17 0.00 0.00 0.00
September 240.07 108.52 131.55 269.40 104.42 0.00 0.00 0.00
October 127.97 46.48 81.49 113.91 143.14 0.00 0.00 0.00
November 69.04 20.37 48.67 43.09 179.32 0.00 0.00 0.00
December 38.49 7.82 30.67 13.88 226.31 0.00 0.00 0.00
                 
Annual Sum or Average 199.05 79.25 119.80 203.47 137.79 0.00 0.00 0.00
Minimum of Months 38.49 7.82 30.67 13.88 70.49 0.00 0.00 0.00
Maximum of Months 353.04 155.51 204.06 414.31 226.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.53 0.00 19.53 2.35 111.25 0.00 0.00 0.00
February 30.49 0.00 30.49 6.37 104.82 0.00 0.00 0.00
March 42.20 0.00 42.20 17.54 84.14 0.00 0.00 0.00
April 68.95 0.46 68.49 48.46 66.66 0.00 0.00 0.00
May 86.20 4.40 81.81 60.90 53.38 0.00 0.00 0.00
June 94.97 5.94 89.03 84.92 39.57 0.00 0.00 0.00
July 90.30 5.31 84.99 86.51 35.61 0.00 0.00 0.00
August 71.09 1.33 69.76 67.10 39.52 0.00 0.00 0.00
September 53.92 0.03 53.89 44.41 55.96 0.00 0.00 0.00
October 34.53 0.00 34.53 17.44 77.01 0.00 0.00 0.00
November 20.75 0.00 20.75 3.61 96.65 0.00 0.00 0.00
December 14.13 0.00 14.13 0.31 121.61 0.00 0.00 0.00
                 
Annual Sum or Average 52.35 1.47 50.89 36.81 73.69 0.00 0.00 0.00
Minimum of Months 14.13 0.00 14.13 0.31 35.61 0.00 0.00 0.00
Maximum of Months 94.97 5.94 89.03 86.51 121.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.05 23.94 49.11 47.50 200.05 0.00 0.00 0.00
February 129.22 55.01 74.22 106.13 189.50 0.00 0.00 0.00
March 116.25 22.35 93.89 78.32 151.73 0.00 0.00 0.00
April 273.78 108.55 165.23 290.28 123.52 0.00 0.00 0.00
May 321.27 130.65 190.62 336.48 105.02 0.00 0.00 0.00
June 346.85 142.80 204.06 391.71 77.45 0.00 0.00 0.00
July 353.04 155.51 197.53 416.54 69.95 0.00 0.00 0.00
August 297.09 128.70 168.39 354.25 76.11 0.00 0.00 0.00
September 240.07 108.52 131.55 274.78 102.42 0.00 0.00 0.00
October 127.97 46.48 81.49 117.93 141.03 0.00 0.00 0.00
November 69.04 20.37 48.67 45.61 177.20 0.00 0.00 0.00
December 38.49 7.82 30.67 15.08 224.61 0.00 0.00 0.00
                 
Annual Sum or Average 199.05 79.25 119.80 206.55 136.29 0.00 0.00 0.00
Minimum of Months 38.49 7.82 30.67 15.08 69.95 0.00 0.00 0.00
Maximum of Months 353.04 155.51 204.06 416.54 224.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 89.13 57.72 31.41 88.90 81.35 0.00 0.00 0.00
February 108.16 65.92 42.24 110.53 79.73 0.00 0.00 0.00
March 66.76 19.30 47.46 58.04 61.92 0.00 0.00 0.00
April 136.84 60.64 76.21 154.58 60.15 0.00 0.00 0.00
May 114.72 37.16 77.56 119.79 52.42 0.00 0.00 0.00
June 105.90 25.61 80.29 115.62 39.67 0.00 0.00 0.00
July 114.15 35.31 78.83 134.53 36.27 0.00 0.00 0.00
August 134.07 60.07 74.00 166.56 39.51 0.00 0.00 0.00
September 160.66 94.82 65.84 196.70 51.66 0.00 0.00 0.00
October 107.20 61.81 45.40 117.65 64.75 0.00 0.00 0.00
November 77.42 47.08 30.34 77.79 73.75 0.00 0.00 0.00
December 61.43 39.39 22.04 60.53 86.44 0.00 0.00 0.00
                 
Annual Sum or Average 106.20 50.20 56.00 116.61 60.53 0.00 0.00 0.00
Minimum of Months 61.43 19.30 22.04 58.04 36.27 0.00 0.00 0.00
Maximum of Months 160.66 94.82 80.29 196.70 86.44 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.62 0.00 15.62 1.47 93.18 0.00 0.00 0.00
February 24.39 0.00 24.39 4.38 86.80 0.00 0.00 0.00
March 33.76 0.00 33.76 13.05 69.96 0.00 0.00 0.00
April 55.17 0.37 54.80 40.49 53.16 0.00 0.00 0.00
May 68.97 3.52 65.46 51.28 42.45 0.00 0.00 0.00
June 75.98 4.75 71.23 71.72 30.85 0.00 0.00 0.00
July 72.25 4.25 68.00 73.37 27.51 0.00 0.00 0.00
August 56.88 1.06 55.82 57.49 30.36 0.00 0.00 0.00
September 43.14 0.03 43.12 37.83 43.79 0.00 0.00 0.00
October 27.62 0.00 27.62 13.89 63.43 0.00 0.00 0.00
November 16.60 0.00 16.60 2.38 81.20 0.00 0.00 0.00
December 11.30 0.00 11.30 0.11 102.63 0.00 0.00 0.00
                 
Annual Sum or Average 41.89 1.17 40.71 30.76 60.31 0.00 0.00 0.00
Minimum of Months 11.30 0.00 11.30 0.11 27.51 0.00 0.00 0.00
Maximum of Months 75.98 4.75 71.23 73.37 102.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 74.10 29.51 44.59 43.48 199.04 0.00 0.00 0.00
February 111.90 41.69 70.20 74.03 187.61 0.00 0.00 0.00
March 116.26 22.93 93.33 75.18 151.15 0.00 0.00 0.00
April 311.45 146.03 165.42 328.76 119.74 0.00 0.00 0.00
May 327.92 143.03 184.89 338.01 102.39 0.00 0.00 0.00
June 324.49 129.63 194.86 358.20 75.53 0.00 0.00 0.00
July 331.18 140.68 190.50 381.96 67.88 0.00 0.00 0.00
August 314.61 150.61 163.99 371.23 73.64 0.00 0.00 0.00
September 282.45 150.08 132.37 320.55 100.35 0.00 0.00 0.00
October 137.38 57.45 79.93 123.74 140.54 0.00 0.00 0.00
November 71.10 24.19 46.91 41.55 175.04 0.00 0.00 0.00
December 52.88 19.79 33.09 26.61 219.63 0.00 0.00 0.00
                 
Annual Sum or Average 204.94 88.08 116.86 207.43 134.12 0.00 0.00 0.00
Minimum of Months 52.88 19.79 33.09 26.61 67.88 0.00 0.00 0.00
Maximum of Months 331.18 150.61 194.86 381.96 219.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 111.44 72.16 39.27 112.74 100.46 0.00 0.00 0.00
February 135.22 82.42 52.81 139.56 97.58 0.00 0.00 0.00
March 83.46 24.13 59.33 70.78 81.40 0.00 0.00 0.00
April 171.09 75.81 95.28 194.40 68.60 0.00 0.00 0.00
May 143.43 46.46 96.97 150.97 59.06 0.00 0.00 0.00
June 132.40 32.02 100.38 146.45 42.77 0.00 0.00 0.00
July 142.71 44.15 98.56 169.97 38.55 0.00 0.00 0.00
August 167.62 75.10 92.52 209.96 41.90 0.00 0.00 0.00
September 200.87 118.55 82.32 248.07 55.82 0.00 0.00 0.00
October 134.03 77.27 56.76 148.97 74.71 0.00 0.00 0.00
November 96.79 58.86 37.93 98.22 91.13 0.00 0.00 0.00
December 76.81 49.25 27.56 75.15 114.15 0.00 0.00 0.00
                 
Annual Sum or Average 132.78 62.77 70.02 146.89 72.05 0.00 0.00 0.00
Minimum of Months 76.81 24.13 27.56 70.78 38.55 0.00 0.00 0.00
Maximum of Months 200.87 118.55 100.38 248.07 114.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.53 0.00 19.53 2.17 111.00 0.00 0.00 0.00
February 30.49 0.00 30.49 6.06 104.16 0.00 0.00 0.00
March 42.20 0.00 42.20 17.14 83.96 0.00 0.00 0.00
April 68.95 0.46 68.49 46.25 66.66 0.00 0.00 0.00
May 86.20 4.40 81.81 59.24 53.04 0.00 0.00 0.00
June 94.97 5.94 89.03 84.16 39.02 0.00 0.00 0.00
July 90.30 5.31 84.99 85.53 35.10 0.00 0.00 0.00
August 71.09 1.33 69.76 65.56 39.18 0.00 0.00 0.00
September 53.92 0.03 53.89 42.28 56.03 0.00 0.00 0.00
October 34.53 0.00 34.53 16.68 76.88 0.00 0.00 0.00
November 20.75 0.00 20.75 3.42 96.37 0.00 0.00 0.00
December 14.13 0.00 14.13 0.26 121.60 0.00 0.00 0.00
                 
Annual Sum or Average 52.35 1.47 50.89 35.88 73.43 0.00 0.00 0.00
Minimum of Months 14.13 0.00 14.13 0.26 35.10 0.00 0.00 0.00
Maximum of Months 94.97 5.94 89.03 85.53 121.60 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 74.10 29.51 44.59 45.30 195.77 0.00 0.00 0.00
February 111.90 41.69 70.20 77.00 184.21 0.00 0.00 0.00
March 116.26 22.93 93.33 76.91 150.00 0.00 0.00 0.00
April 311.45 146.03 165.42 332.76 118.15 0.00 0.00 0.00
May 327.92 143.03 184.89 340.55 101.56 0.00 0.00 0.00
June 324.49 129.63 194.86 359.83 75.12 0.00 0.00 0.00
July 331.18 140.68 190.50 383.81 67.38 0.00 0.00 0.00
August 314.61 150.61 163.99 374.09 72.62 0.00 0.00 0.00
September 282.45 150.08 132.37 324.69 98.42 0.00 0.00 0.00
October 137.38 57.45 79.93 127.35 138.27 0.00 0.00 0.00
November 71.10 24.19 46.91 43.56 172.25 0.00 0.00 0.00
December 52.88 19.79 33.09 27.53 217.17 0.00 0.00 0.00
                 
Annual Sum or Average 204.94 88.08 116.86 209.93 132.33 0.00 0.00 0.00
Minimum of Months 52.88 19.79 33.09 27.53 67.38 0.00 0.00 0.00
Maximum of Months 331.18 150.61 194.86 383.81 217.17 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.73 0.00 24.73 1.86 152.79 0.00 0.00 0.00
February 38.61 0.00 38.61 5.80 141.88 0.00 0.00 0.00
March 53.44 0.00 53.44 19.96 113.16 0.00 0.00 0.00
April 87.32 0.58 86.74 60.73 90.04 0.00 0.00 0.00
May 109.17 5.57 103.61 76.52 73.38 0.00 0.00 0.00
June 120.27 7.52 112.75 107.76 55.63 0.00 0.00 0.00
July 114.35 6.73 107.63 109.09 50.91 0.00 0.00 0.00
August 90.03 1.68 88.35 83.75 57.42 0.00 0.00 0.00
September 68.29 0.04 68.25 54.05 79.71 0.00 0.00 0.00
October 43.73 0.00 43.73 19.76 106.21 0.00 0.00 0.00
November 26.27 0.00 26.27 3.18 132.94 0.00 0.00 0.00
December 17.89 0.00 17.89 0.08 168.22 0.00 0.00 0.00
                 
Annual Sum or Average 66.30 1.86 64.44 45.41 101.66 0.00 0.00 0.00
Minimum of Months 17.89 0.00 17.89 0.08 50.91 0.00 0.00 0.00
Maximum of Months 120.27 7.52 112.75 109.09 168.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.12 0.00 9.12 0.69 56.33 0.00 0.00 0.00
February 14.23 0.00 14.23 2.14 52.30 0.00 0.00 0.00
March 19.70 0.00 19.70 7.36 41.72 0.00 0.00 0.00
April 32.19 0.21 31.98 22.39 33.19 0.00 0.00 0.00
May 40.25 2.05 38.19 28.21 27.05 0.00 0.00 0.00
June 44.34 2.77 41.56 39.72 20.51 0.00 0.00 0.00
July 42.16 2.48 39.68 40.21 18.77 0.00 0.00 0.00
August 33.19 0.62 32.57 30.87 21.17 0.00 0.00 0.00
September 25.17 0.01 25.16 19.92 29.38 0.00 0.00 0.00
October 16.12 0.00 16.12 7.29 39.15 0.00 0.00 0.00
November 9.69 0.00 9.69 1.17 49.01 0.00 0.00 0.00
December 6.60 0.00 6.60 0.03 62.01 0.00 0.00 0.00
                 
Annual Sum or Average 24.44 0.68 23.76 16.74 37.48 0.00 0.00 0.00
Minimum of Months 6.60 0.00 6.60 0.03 18.77 0.00 0.00 0.00
Maximum of Months 44.34 2.77 41.56 40.21 62.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 52.00 33.67 18.33 52.25 49.60 0.00 0.00 0.00
February 63.09 38.45 24.64 65.05 47.90 0.00 0.00 0.00
March 38.94 11.26 27.69 32.67 40.04 0.00 0.00 0.00
April 79.83 35.37 44.46 92.42 33.75 0.00 0.00 0.00
May 66.92 21.68 45.24 71.66 29.88 0.00 0.00 0.00
June 61.78 14.94 46.84 69.26 22.43 0.00 0.00 0.00
July 66.59 20.60 45.99 80.16 20.58 0.00 0.00 0.00
August 78.21 35.04 43.17 98.85 22.31 0.00 0.00 0.00
September 93.72 55.32 38.41 116.81 28.77 0.00 0.00 0.00
October 62.54 36.06 26.48 69.88 37.37 0.00 0.00 0.00
November 45.16 27.46 17.70 45.65 45.33 0.00 0.00 0.00
December 35.84 22.98 12.86 34.69 57.08 0.00 0.00 0.00
                 
Annual Sum or Average 61.96 29.29 32.67 69.02 36.20 0.00 0.00 0.00
Minimum of Months 35.84 11.26 12.86 32.67 20.58 0.00 0.00 0.00
Maximum of Months 93.72 55.32 46.84 116.81 57.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 141.13 91.39 49.74 141.81 134.61 0.00 0.00 0.00
February 171.25 104.37 66.88 176.57 130.01 0.00 0.00 0.00
March 105.70 30.55 75.14 88.69 108.68 0.00 0.00 0.00
April 216.67 96.01 120.67 250.85 91.60 0.00 0.00 0.00
May 181.64 58.84 122.80 194.51 81.11 0.00 0.00 0.00
June 167.68 40.55 127.12 187.99 60.89 0.00 0.00 0.00
July 180.74 55.91 124.82 217.56 55.85 0.00 0.00 0.00
August 212.28 95.11 117.17 268.29 60.56 0.00 0.00 0.00
September 254.39 150.14 104.25 317.05 78.08 0.00 0.00 0.00
October 169.74 97.86 71.88 189.66 101.44 0.00 0.00 0.00
November 122.58 74.54 48.04 123.92 123.03 0.00 0.00 0.00
December 97.27 62.37 34.90 94.17 154.94 0.00 0.00 0.00
                 
Annual Sum or Average 168.16 79.49 88.67 187.32 98.25 0.00 0.00 0.00
Minimum of Months 97.27 30.55 34.90 88.69 55.85 0.00 0.00 0.00
Maximum of Months 254.39 150.14 127.12 317.05 154.94 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 111.44 72.16 39.27 113.24 99.21 0.00 0.00 0.00
February 135.22 82.42 52.81 139.65 97.09 0.00 0.00 0.00
March 83.46 24.13 59.33 71.40 80.47 0.00 0.00 0.00
April 171.09 75.81 95.28 195.25 68.19 0.00 0.00 0.00
May 143.43 46.46 96.97 151.41 59.22 0.00 0.00 0.00
June 132.40 32.02 100.38 145.94 43.24 0.00 0.00 0.00
July 142.71 44.15 98.56 169.50 38.92 0.00 0.00 0.00
August 167.62 75.10 92.52 209.85 41.74 0.00 0.00 0.00
September 200.87 118.55 82.32 248.68 55.25 0.00 0.00 0.00
October 134.03 77.27 56.76 149.62 73.72 0.00 0.00 0.00
November 96.79 58.86 37.93 98.55 90.03 0.00 0.00 0.00
December 76.81 49.25 27.56 75.61 112.92 0.00 0.00 0.00
                 
Annual Sum or Average 132.78 62.77 70.02 147.18 71.54 0.00 0.00 0.00
Minimum of Months 76.81 24.13 27.56 71.40 38.92 0.00 0.00 0.00
Maximum of Months 200.87 118.55 100.38 248.68 112.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.05 23.94 49.11 45.29 199.19 0.00 0.00 0.00
February 129.22 55.01 74.22 102.49 189.83 0.00 0.00 0.00
March 116.25 22.35 93.89 76.79 150.51 0.00 0.00 0.00
April 273.78 108.55 165.23 283.30 123.70 0.00 0.00 0.00
May 321.27 130.65 190.62 330.77 105.07 0.00 0.00 0.00
June 346.85 142.80 204.06 386.45 77.32 0.00 0.00 0.00
July 353.04 155.51 197.53 411.04 69.84 0.00 0.00 0.00
August 297.09 128.70 168.39 348.08 76.07 0.00 0.00 0.00
September 240.07 108.52 131.55 268.06 102.88 0.00 0.00 0.00
October 127.97 46.48 81.49 113.97 140.68 0.00 0.00 0.00
November 69.04 20.37 48.67 43.49 176.63 0.00 0.00 0.00
December 38.49 7.82 30.67 14.14 223.78 0.00 0.00 0.00
                 
Annual Sum or Average 199.05 79.25 119.80 202.33 136.03 0.00 0.00 0.00
Minimum of Months 38.49 7.82 30.67 14.14 69.84 0.00 0.00 0.00
Maximum of Months 353.04 155.51 204.06 411.04 223.78 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.53 0.00 19.53 2.55 109.51 0.00 0.00 0.00
February 30.49 0.00 30.49 6.63 103.47 0.00 0.00 0.00
March 42.20 0.00 42.20 17.89 82.85 0.00 0.00 0.00
April 68.95 0.46 68.49 47.93 65.88 0.00 0.00 0.00
May 86.20 4.40 81.81 60.22 52.93 0.00 0.00 0.00
June 94.97 5.94 89.03 83.86 39.24 0.00 0.00 0.00
July 90.30 5.31 84.99 85.53 35.28 0.00 0.00 0.00
August 71.09 1.33 69.76 66.54 38.92 0.00 0.00 0.00
September 53.92 0.03 53.89 44.49 54.95 0.00 0.00 0.00
October 34.53 0.00 34.53 17.89 75.49 0.00 0.00 0.00
November 20.75 0.00 20.75 3.87 95.00 0.00 0.00 0.00
December 14.13 0.00 14.13 0.36 120.12 0.00 0.00 0.00
                 
Annual Sum or Average 52.35 1.47 50.89 36.63 72.65 0.00 0.00 0.00
Minimum of Months 14.13 0.00 14.13 0.36 35.28 0.00 0.00 0.00
Maximum of Months 94.97 5.94 89.03 85.53 120.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.05 23.94 49.11 48.03 197.05 0.00 0.00 0.00
February 129.22 55.01 74.22 106.60 187.25 0.00 0.00 0.00
March 116.25 22.35 93.89 78.83 149.47 0.00 0.00 0.00
April 273.78 108.55 165.23 288.53 122.00 0.00 0.00 0.00
May 321.27 130.65 190.62 334.07 104.17 0.00 0.00 0.00
June 346.85 142.80 204.06 388.42 76.80 0.00 0.00 0.00
July 353.04 155.51 197.53 413.36 69.25 0.00 0.00 0.00
August 297.09 128.70 168.39 351.90 74.86 0.00 0.00 0.00
September 240.07 108.52 131.55 274.04 100.54 0.00 0.00 0.00
October 127.97 46.48 81.49 118.47 138.33 0.00 0.00 0.00
November 69.04 20.37 48.67 46.17 174.55 0.00 0.00 0.00
December 38.49 7.82 30.67 15.29 222.30 0.00 0.00 0.00
                 
Annual Sum or Average 199.05 79.25 119.80 205.64 134.46 0.00 0.00 0.00
Minimum of Months 38.49 7.82 30.67 15.29 69.25 0.00 0.00 0.00
Maximum of Months 353.04 155.51 204.06 413.36 222.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 163.43 105.83 57.60 160.48 151.67 0.00 0.00 0.00
February 198.32 120.87 77.45 199.68 148.02 0.00 0.00 0.00
March 122.40 35.38 87.02 100.95 121.60 0.00 0.00 0.00
April 250.92 111.18 139.74 283.66 101.11 0.00 0.00 0.00
May 210.35 68.14 142.21 221.29 86.87 0.00 0.00 0.00
June 194.18 46.96 147.22 215.50 62.51 0.00 0.00 0.00
July 209.30 64.75 144.55 250.04 56.16 0.00 0.00 0.00
August 245.83 110.14 135.68 307.63 60.91 0.00 0.00 0.00
September 294.59 173.87 120.72 361.97 82.38 0.00 0.00 0.00
October 196.57 113.33 83.24 215.20 112.34 0.00 0.00 0.00
November 141.95 86.32 55.63 140.07 138.33 0.00 0.00 0.00
December 112.65 72.23 40.41 107.23 172.58 0.00 0.00 0.00
                 
Annual Sum or Average 194.74 92.05 102.68 213.36 107.67 0.00 0.00 0.00
Minimum of Months 112.65 35.38 40.41 100.95 56.16 0.00 0.00 0.00
Maximum of Months 294.59 173.87 147.22 361.97 172.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 136.67 0.00 136.67 4.80 951.61 0.00 0.00 0.00
February 213.42 0.00 213.42 17.34 892.91 0.00 0.00 0.00
March 295.36 0.00 295.36 79.12 721.69 0.00 0.00 0.00
April 482.63 3.21 479.42 289.94 550.01 0.00 0.00 0.00
May 603.41 30.77 572.64 364.09 449.76 0.00 0.00 0.00
June 664.75 41.58 623.17 537.90 337.73 0.00 0.00 0.00
July 632.05 37.17 594.87 551.28 306.25 0.00 0.00 0.00
August 497.63 9.31 488.32 424.38 341.21 0.00 0.00 0.00
September 377.45 0.22 377.22 269.76 474.26 0.00 0.00 0.00
October 241.68 0.00 241.68 85.87 670.66 0.00 0.00 0.00
November 145.21 0.00 145.21 8.67 852.85 0.00 0.00 0.00
December 98.89 0.00 98.89 0.00 1054.96 0.00 0.00 0.00
                 
Annual Sum or Average 366.45 10.26 356.19 220.46 632.40 0.00 0.00 0.00
Minimum of Months 98.89 0.00 98.89 0.00 306.25 0.00 0.00 0.00
Maximum of Months 664.75 41.58 623.17 551.28 1054.96 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 136.67 0.00 136.67 3.52 980.89 0.00 0.00 0.00
February 213.42 0.00 213.42 13.93 920.07 0.00 0.00 0.00
March 295.36 0.00 295.36 71.25 742.74 0.00 0.00 0.00
April 482.63 3.21 479.42 279.12 562.22 0.00 0.00 0.00
May 603.41 30.77 572.64 351.20 459.38 0.00 0.00 0.00
June 664.75 41.58 623.17 526.14 344.78 0.00 0.00 0.00
July 632.05 37.17 594.87 540.46 312.60 0.00 0.00 0.00
August 497.63 9.31 488.32 414.64 348.88 0.00 0.00 0.00
September 377.45 0.22 377.22 260.53 485.01 0.00 0.00 0.00
October 241.68 0.00 241.68 78.57 690.38 0.00 0.00 0.00
November 145.21 0.00 145.21 6.54 881.33 0.00 0.00 0.00
December 98.89 0.00 98.89 0.00 1087.36 0.00 0.00 0.00
                 
Annual Sum or Average 366.45 10.26 356.19 213.18 650.00 0.00 0.00 0.00
Minimum of Months 98.89 0.00 98.89 0.00 312.60 0.00 0.00 0.00
Maximum of Months 664.75 41.58 623.17 540.46 1087.36 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.53 0.00 19.53 3.31 112.08 0.00 0.00 0.00
February 30.49 0.00 30.49 7.55 107.21 0.00 0.00 0.00
March 42.20 0.00 42.20 21.33 86.70 0.00 0.00 0.00
April 68.95 0.46 68.49 59.11 69.97 0.00 0.00 0.00
May 86.20 4.40 81.81 72.57 60.57 0.00 0.00 0.00
June 94.97 5.94 89.03 101.28 45.90 0.00 0.00 0.00
July 90.30 5.31 84.99 104.51 42.16 0.00 0.00 0.00
August 71.09 1.33 69.76 83.47 44.74 0.00 0.00 0.00
September 53.92 0.03 53.89 55.90 59.02 0.00 0.00 0.00
October 34.53 0.00 34.53 22.22 80.73 0.00 0.00 0.00
November 20.75 0.00 20.75 4.88 100.77 0.00 0.00 0.00
December 14.13 0.00 14.13 0.64 126.65 0.00 0.00 0.00
                 
Annual Sum or Average 52.35 1.47 50.89 44.92 77.90 0.00 0.00 0.00
Minimum of Months 14.13 0.00 14.13 0.64 42.16 0.00 0.00 0.00
Maximum of Months 94.97 5.94 89.03 104.51 126.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 148.18 59.02 89.17 99.55 399.70 0.00 0.00 0.00
February 223.78 83.38 140.39 163.69 383.24 0.00 0.00 0.00
March 232.50 45.86 186.64 172.47 313.50 0.00 0.00 0.00
April 622.85 292.03 330.82 720.25 252.84 0.00 0.00 0.00
May 655.80 286.04 369.76 733.18 229.80 0.00 0.00 0.00
June 648.94 259.24 389.70 785.24 174.45 0.00 0.00 0.00
July 662.31 281.33 380.98 839.39 159.20 0.00 0.00 0.00
August 629.17 301.20 327.96 818.26 166.55 0.00 0.00 0.00
September 564.86 300.14 264.72 707.44 212.33 0.00 0.00 0.00
October 274.74 114.89 159.85 279.88 293.76 0.00 0.00 0.00
November 142.19 48.38 93.81 95.24 363.41 0.00 0.00 0.00
December 105.76 39.58 66.18 59.98 457.28 0.00 0.00 0.00
                 
Annual Sum or Average 409.84 176.15 233.70 457.29 283.38 0.00 0.00 0.00
Minimum of Months 105.76 39.58 66.18 59.98 159.20 0.00 0.00 0.00
Maximum of Months 662.31 301.20 389.70 839.39 457.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 111.44 72.16 39.27 117.95 101.53 0.00 0.00 0.00
February 135.22 82.42 52.81 146.01 100.62 0.00 0.00 0.00
March 83.46 24.13 59.33 77.40 84.54 0.00 0.00 0.00
April 171.09 75.81 95.28 210.97 71.29 0.00 0.00 0.00
May 143.43 46.46 96.97 166.47 65.67 0.00 0.00 0.00
June 132.40 32.02 100.38 165.00 49.08 0.00 0.00 0.00
July 142.71 44.15 98.56 190.27 44.84 0.00 0.00 0.00
August 167.62 75.10 92.52 229.99 46.48 0.00 0.00 0.00
September 200.87 118.55 82.32 266.13 58.57 0.00 0.00 0.00
October 134.03 77.27 56.76 158.90 78.47 0.00 0.00 0.00
November 96.79 58.86 37.93 102.68 95.25 0.00 0.00 0.00
December 76.81 49.25 27.56 77.75 119.28 0.00 0.00 0.00
                 
Annual Sum or Average 132.78 62.77 70.02 158.94 76.19 0.00 0.00 0.00
Minimum of Months 76.81 24.13 27.56 77.40 44.84 0.00 0.00 0.00
Maximum of Months 200.87 118.55 100.38 266.13 119.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.73 0.00 24.73 1.48 154.97 0.00 0.00 0.00
February 38.61 0.00 38.61 4.76 144.28 0.00 0.00 0.00
March 53.44 0.00 53.44 18.43 114.82 0.00 0.00 0.00
April 87.32 0.58 86.74 57.41 90.09 0.00 0.00 0.00
May 109.17 5.57 103.61 73.15 73.36 0.00 0.00 0.00
June 120.27 7.52 112.75 103.62 56.15 0.00 0.00 0.00
July 114.35 6.73 107.63 104.74 51.56 0.00 0.00 0.00
August 90.03 1.68 88.35 80.33 57.63 0.00 0.00 0.00
September 68.29 0.04 68.25 51.87 78.85 0.00 0.00 0.00
October 43.73 0.00 43.73 18.51 106.42 0.00 0.00 0.00
November 26.27 0.00 26.27 2.59 135.48 0.00 0.00 0.00
December 17.89 0.00 17.89 0.04 171.12 0.00 0.00 0.00
                 
Annual Sum or Average 66.30 1.86 64.44 43.27 102.69 0.00 0.00 0.00
Minimum of Months 17.89 0.00 17.89 0.04 51.56 0.00 0.00 0.00
Maximum of Months 120.27 7.52 112.75 104.74 171.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.12 0.00 22.12 1.33 138.63 0.00 0.00 0.00
February 34.55 0.00 34.55 4.26 129.09 0.00 0.00 0.00
March 47.81 0.00 47.81 16.49 102.73 0.00 0.00 0.00
April 78.13 0.52 77.61 51.37 80.60 0.00 0.00 0.00
May 97.68 4.98 92.70 65.45 65.64 0.00 0.00 0.00
June 107.61 6.73 100.88 92.71 50.24 0.00 0.00 0.00
July 102.31 6.02 96.30 93.71 46.13 0.00 0.00 0.00
August 80.55 1.51 79.05 71.87 51.56 0.00 0.00 0.00
September 61.10 0.04 61.06 46.41 70.55 0.00 0.00 0.00
October 39.12 0.00 39.12 16.56 95.22 0.00 0.00 0.00
November 23.51 0.00 23.51 2.32 121.20 0.00 0.00 0.00
December 16.01 0.00 16.01 0.03 153.09 0.00 0.00 0.00
                 
Annual Sum or Average 59.32 1.66 57.66 38.72 91.88 0.00 0.00 0.00
Minimum of Months 16.01 0.00 16.01 0.03 46.13 0.00 0.00 0.00
Maximum of Months 107.61 6.73 100.88 93.71 153.09 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 416.03 269.40 146.62 413.14 401.61 0.00 0.00 0.00
February 504.83 307.68 197.15 513.64 389.27 0.00 0.00 0.00
March 311.58 90.07 221.51 255.02 325.29 0.00 0.00 0.00
April 638.73 283.02 355.71 728.27 270.80 0.00 0.00 0.00
May 535.46 173.46 362.00 562.76 239.94 0.00 0.00 0.00
June 494.29 119.54 374.75 541.83 181.81 0.00 0.00 0.00
July 532.79 164.83 367.96 628.06 167.34 0.00 0.00 0.00
August 625.76 280.37 345.39 779.31 179.59 0.00 0.00 0.00
September 749.91 442.60 307.31 925.78 228.45 0.00 0.00 0.00
October 500.38 288.48 211.90 553.51 300.40 0.00 0.00 0.00
November 361.34 219.74 141.60 360.31 369.69 0.00 0.00 0.00
December 286.74 183.87 102.88 274.31 465.13 0.00 0.00 0.00
                 
Annual Sum or Average 495.71 234.32 261.39 543.88 292.82 0.00 0.00 0.00
Minimum of Months 286.74 90.07 102.88 255.02 167.34 0.00 0.00 0.00
Maximum of Months 749.91 442.60 374.75 925.78 465.13 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.150959E+10 0.977552E+09 0.532037E+09 0.149593E+10 0.137568E+10
February 0.165454E+10 0.100840E+10 0.646136E+09 0.168069E+10 0.120067E+10
March 0.113060E+10 0.326821E+09 0.803783E+09 0.945760E+09 0.110694E+10
April 0.224291E+10 0.993833E+09 0.124907E+10 0.255782E+10 0.891277E+09
May 0.194297E+10 0.629412E+09 0.131355E+10 0.207840E+10 0.783853E+09
June 0.173570E+10 0.419778E+09 0.131592E+10 0.195525E+10 0.556759E+09
July 0.193326E+10 0.598097E+09 0.133516E+10 0.232455E+10 0.529367E+09
August 0.227063E+10 0.101735E+10 0.125328E+10 0.284287E+10 0.584015E+09
September 0.263332E+10 0.155420E+10 0.107911E+10 0.323937E+10 0.743422E+09
October 0.181568E+10 0.104679E+10 0.768888E+09 0.199710E+10 0.102291E+10
November 0.126888E+10 0.771630E+09 0.497246E+09 0.126637E+10 0.121143E+10
December 0.104048E+10 0.667184E+09 0.373294E+09 0.100066E+10 0.155180E+10
           
Annual Sum or Average 0.211785E+11 0.100111E+11 0.111675E+11 0.233848E+11 0.115581E+11
Minimum of Months 0.104048E+10 0.326821E+09 0.373294E+09 0.945760E+09 0.529367E+09
Maximum of Months 0.263332E+10 0.155420E+10 0.133516E+10 0.323937E+10 0.155180E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.425090E+10 0.275272E+10 0.149818E+10 0.416338E+10 0.398347E+10
February 0.465908E+10 0.283960E+10 0.181948E+10 0.467980E+10 0.349205E+10
March 0.318371E+10 0.920306E+09 0.226340E+10 0.260960E+10 0.322581E+10
April 0.631588E+10 0.279857E+10 0.351731E+10 0.711163E+10 0.266195E+10
May 0.547127E+10 0.177238E+10 0.369888E+10 0.575099E+10 0.236500E+10
June 0.488762E+10 0.118207E+10 0.370556E+10 0.539730E+10 0.171169E+10
July 0.544392E+10 0.168420E+10 0.375972E+10 0.643353E+10 0.163516E+10
August 0.639395E+10 0.286480E+10 0.352915E+10 0.790149E+10 0.181462E+10
September 0.741524E+10 0.437654E+10 0.303871E+10 0.902896E+10 0.226980E+10
October 0.511283E+10 0.294769E+10 0.216514E+10 0.555858E+10 0.304864E+10
November 0.357307E+10 0.217286E+10 0.140021E+10 0.352083E+10 0.355231E+10
December 0.292991E+10 0.187874E+10 0.105117E+10 0.278587E+10 0.447784E+10
           
Annual Sum or Average 0.596374E+11 0.281905E+11 0.314469E+11 0.649420E+11 0.342383E+11
Minimum of Months 0.292991E+10 0.920306E+09 0.105117E+10 0.260960E+10 0.163516E+10
Maximum of Months 0.741524E+10 0.437654E+10 0.375972E+10 0.902896E+10 0.447784E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.552217E+10 0.357594E+10 0.194622E+10 0.546148E+10 0.553848E+10
February 0.605241E+10 0.368880E+10 0.236360E+10 0.614793E+10 0.483728E+10
March 0.413581E+10 0.119553E+10 0.294029E+10 0.338514E+10 0.454200E+10
April 0.820468E+10 0.363550E+10 0.456918E+10 0.937870E+10 0.368281E+10
May 0.710749E+10 0.230242E+10 0.480506E+10 0.755101E+10 0.331063E+10
June 0.634930E+10 0.153557E+10 0.481373E+10 0.706057E+10 0.241756E+10
July 0.707196E+10 0.218787E+10 0.488409E+10 0.844241E+10 0.229525E+10
August 0.830611E+10 0.372154E+10 0.458457E+10 0.104133E+11 0.251100E+10
September 0.963282E+10 0.568537E+10 0.394745E+10 0.119065E+11 0.311623E+10
October 0.664185E+10 0.382922E+10 0.281264E+10 0.730790E+10 0.426665E+10
November 0.464162E+10 0.282267E+10 0.181896E+10 0.461037E+10 0.497624E+10
December 0.380613E+10 0.244060E+10 0.136553E+10 0.364183E+10 0.623443E+10
           
Annual Sum or Average 0.774723E+11 0.366210E+11 0.408513E+11 0.853071E+11 0.477285E+11
Minimum of Months 0.380613E+10 0.119553E+10 0.136553E+10 0.338514E+10 0.229525E+10
Maximum of Months 0.963282E+10 0.568537E+10 0.488409E+10 0.119065E+11 0.623443E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.298472E+09 0.193279E+09 0.105193E+09 0.302521E+09 0.269459E+09
February 0.327132E+09 0.199379E+09 0.127753E+09 0.337723E+09 0.237176E+09
March 0.223541E+09 64618063.64 0.158923E+09 0.190693E+09 0.218551E+09
April 0.443463E+09 0.196498E+09 0.246965E+09 0.508784E+09 0.178364E+09
May 0.384160E+09 0.124445E+09 0.259715E+09 0.408266E+09 0.159551E+09
June 0.343181E+09 82997281.99 0.260183E+09 0.381327E+09 0.112821E+09
July 0.382241E+09 0.118254E+09 0.263986E+09 0.457364E+09 0.105035E+09
August 0.448945E+09 0.201148E+09 0.247797E+09 0.565101E+09 0.113274E+09
September 0.520653E+09 0.307293E+09 0.213361E+09 0.646980E+09 0.145119E+09
October 0.358991E+09 0.206968E+09 0.152023E+09 0.400899E+09 0.200573E+09
November 0.250879E+09 0.152564E+09 98314557.38 0.255071E+09 0.236623E+09
December 0.205721E+09 0.131914E+09 73806852.46 0.202123E+09 0.305389E+09
           
Annual Sum or Average 0.418738E+10 0.197936E+10 0.220802E+10 0.465685E+10 0.228193E+10
Minimum of Months 0.205721E+09 64618063.64 73806852.46 0.190693E+09 0.105035E+09
Maximum of Months 0.520653E+09 0.307293E+09 0.263986E+09 0.646980E+09 0.305389E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.195660E+09 64128920.97 0.131532E+09 0.120110E+09 0.541879E+09
February 0.312615E+09 0.133073E+09 0.179541E+09 0.247397E+09 0.464524E+09
March 0.311355E+09 59870921.37 0.251484E+09 0.204730E+09 0.409107E+09
April 0.709636E+09 0.281355E+09 0.428281E+09 0.739878E+09 0.324132E+09
May 0.860491E+09 0.349933E+09 0.510558E+09 0.893066E+09 0.283384E+09
June 0.899047E+09 0.370125E+09 0.528922E+09 0.101040E+10 0.201958E+09
July 0.945570E+09 0.416516E+09 0.529053E+09 0.110968E+10 0.188798E+09
August 0.795714E+09 0.344711E+09 0.451003E+09 0.939117E+09 0.206705E+09
September 0.622261E+09 0.281272E+09 0.340989E+09 0.698282E+09 0.270662E+09
October 0.342754E+09 0.124483E+09 0.218272E+09 0.305100E+09 0.383399E+09
November 0.178958E+09 52801937.15 0.126156E+09 0.111686E+09 0.464805E+09
December 0.103093E+09 20956149.08 82136943.91 37168191.72 0.606136E+09
           
Annual Sum or Average 0.627716E+10 0.249923E+10 0.377793E+10 0.641661E+10 0.434549E+10
Minimum of Months 0.103093E+09 20956149.08 82136943.91 37168191.72 0.188798E+09
Maximum of Months 0.945570E+09 0.416516E+09 0.529053E+09 0.110968E+10 0.606136E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52296148.79 0.00 52296148.79 6296724.02 0.297973E+09
February 73759823.15 0.00 73759823.15 15419845.28 0.253569E+09
March 0.113018E+09 763.87 0.113017E+09 46988149.08 0.225369E+09
April 0.178718E+09 1187800.51 0.177530E+09 0.125598E+09 0.172791E+09
May 0.230890E+09 11774052.52 0.219116E+09 0.163126E+09 0.142986E+09
June 0.246156E+09 15397270.00 0.230758E+09 0.220101E+09 0.102562E+09
July 0.241849E+09 14224473.17 0.227624E+09 0.231706E+09 95377239.19
August 0.190413E+09 3560925.39 0.186852E+09 0.179709E+09 0.105853E+09
September 0.139769E+09 82607.68 0.139686E+09 0.115103E+09 0.145045E+09
October 92475413.30 0.00 92475413.30 46717644.85 0.206253E+09
November 53771554.59 0.00 53771554.59 9348331.82 0.250522E+09
December 37838893.74 0.00 37838893.74 830019.35 0.325719E+09
           
Annual Sum or Average 0.165095E+10 46227893.14 0.160473E+10 0.116095E+10 0.232402E+10
Minimum of Months 37838893.74 0.00 37838893.74 830019.35 95377239.19
Maximum of Months 0.246156E+09 15397270.00 0.230758E+09 0.231706E+09 0.325719E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.195660E+09 64128920.97 0.131532E+09 0.127222E+09 0.535807E+09
February 0.312615E+09 0.133073E+09 0.179541E+09 0.256751E+09 0.458437E+09
March 0.311355E+09 59870921.37 0.251484E+09 0.209761E+09 0.406389E+09
April 0.709636E+09 0.281355E+09 0.428281E+09 0.752414E+09 0.320154E+09
May 0.860491E+09 0.349933E+09 0.510558E+09 0.901230E+09 0.281277E+09
June 0.899047E+09 0.370125E+09 0.528922E+09 0.101531E+10 0.200752E+09
July 0.945570E+09 0.416516E+09 0.529053E+09 0.111565E+10 0.187356E+09
August 0.795714E+09 0.344711E+09 0.451003E+09 0.948833E+09 0.203856E+09
September 0.622261E+09 0.281272E+09 0.340989E+09 0.712240E+09 0.265461E+09
October 0.342754E+09 0.124483E+09 0.218272E+09 0.315853E+09 0.377747E+09
November 0.178958E+09 52801937.15 0.126156E+09 0.118209E+09 0.459304E+09
December 0.103093E+09 20956149.08 82136943.91 40402135.66 0.601593E+09
           
Annual Sum or Average 0.627716E+10 0.249923E+10 0.377793E+10 0.651388E+10 0.429813E+10
Minimum of Months 0.103093E+09 20956149.08 82136943.91 40402135.66 0.187356E+09
Maximum of Months 0.945570E+09 0.416516E+09 0.529053E+09 0.111565E+10 0.601593E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.238730E+09 0.154592E+09 84137898.18 0.238115E+09 0.217881E+09
February 0.261653E+09 0.159471E+09 0.102182E+09 0.267387E+09 0.192895E+09
March 0.178797E+09 51684172.32 0.127113E+09 0.155453E+09 0.165854E+09
April 0.354700E+09 0.157167E+09 0.197533E+09 0.400684E+09 0.155898E+09
May 0.307267E+09 99536592.27 0.207730E+09 0.320841E+09 0.140399E+09
June 0.274490E+09 66384623.48 0.208105E+09 0.299677E+09 0.102836E+09
July 0.305732E+09 94584426.86 0.211147E+09 0.360325E+09 97135144.51
August 0.359085E+09 0.160887E+09 0.198198E+09 0.446107E+09 0.105823E+09
September 0.416440E+09 0.245785E+09 0.170655E+09 0.509853E+09 0.133896E+09
October 0.287136E+09 0.165542E+09 0.121594E+09 0.315101E+09 0.173435E+09
November 0.200663E+09 0.122027E+09 78636007.32 0.201641E+09 0.191158E+09
December 0.164544E+09 0.105510E+09 59033741.75 0.162113E+09 0.231522E+09
           
Annual Sum or Average 0.334924E+10 0.158317E+10 0.176607E+10 0.367730E+10 0.190873E+10
Minimum of Months 0.164544E+09 51684172.32 59033741.75 0.155453E+09 97135144.51
Maximum of Months 0.416440E+09 0.245785E+09 0.211147E+09 0.509853E+09 0.231522E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 41842464.75 0.00 41842464.75 3931785.16 0.249568E+09
February 59015680.35 0.00 59015680.35 10606833.84 0.209993E+09
March 90426079.04 611.18 90425467.87 34948003.98 0.187369E+09
April 0.142993E+09 950366.37 0.142043E+09 0.104958E+09 0.137786E+09
May 0.184736E+09 9420490.59 0.175316E+09 0.137338E+09 0.113685E+09
June 0.196951E+09 12319448.80 0.184631E+09 0.185897E+09 79952757.98
July 0.193505E+09 11381086.97 0.182124E+09 0.196505E+09 73679290.55
August 0.152351E+09 2849117.93 0.149502E+09 0.153973E+09 81313166.67
September 0.111830E+09 66094.90 0.111764E+09 98067685.16 0.113497E+09
October 73990137.15 0.00 73990137.15 37209179.77 0.169892E+09
November 43022945.85 0.00 43022945.85 6174887.89 0.210466E+09
December 30275127.60 0.00 30275127.60 285269.90 0.274878E+09
           
Annual Sum or Average 0.132094E+10 36987216.73 0.128395E+10 0.969894E+09 0.190208E+10
Minimum of Months 30275127.60 0.00 30275127.60 285269.90 73679290.55
Maximum of Months 0.196951E+09 12319448.80 0.184631E+09 0.196505E+09 0.274878E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.198462E+09 79042420.23 0.119420E+09 0.116444E+09 0.533103E+09
February 0.270698E+09 0.100866E+09 0.169832E+09 0.179096E+09 0.453856E+09
March 0.311380E+09 61414734.22 0.249966E+09 0.201365E+09 0.404848E+09
April 0.807271E+09 0.378498E+09 0.428772E+09 0.852157E+09 0.310377E+09
May 0.878305E+09 0.383093E+09 0.495212E+09 0.905315E+09 0.274241E+09
June 0.841083E+09 0.335996E+09 0.505087E+09 0.928448E+09 0.195767E+09
July 0.887034E+09 0.376787E+09 0.510247E+09 0.102303E+10 0.181817E+09
August 0.842638E+09 0.403400E+09 0.439238E+09 0.994312E+09 0.197241E+09
September 0.732111E+09 0.389014E+09 0.343096E+09 0.830861E+09 0.260119E+09
October 0.367956E+09 0.153873E+09 0.214083E+09 0.331413E+09 0.376417E+09
November 0.184287E+09 62706204.31 0.121580E+09 0.107703E+09 0.453704E+09
December 0.141644E+09 53003264.31 88640916.87 71274387.96 0.588267E+09
           
Annual Sum or Average 0.646287E+10 0.277770E+10 0.368517E+10 0.654142E+10 0.422976E+10
Minimum of Months 0.141644E+09 53003264.31 88640916.87 71274387.96 0.181817E+09
Maximum of Months 0.887034E+09 0.403400E+09 0.510247E+09 0.102303E+10 0.588267E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.298472E+09 0.193279E+09 0.105193E+09 0.301959E+09 0.269062E+09
February 0.327132E+09 0.199379E+09 0.127753E+09 0.337628E+09 0.236070E+09
March 0.223541E+09 64618063.64 0.158923E+09 0.189588E+09 0.218021E+09
April 0.443463E+09 0.196498E+09 0.246965E+09 0.503885E+09 0.177821E+09
May 0.384160E+09 0.124445E+09 0.259715E+09 0.404363E+09 0.158194E+09
June 0.343181E+09 82997281.99 0.260183E+09 0.379603E+09 0.110852E+09
July 0.382241E+09 0.118254E+09 0.263986E+09 0.455241E+09 0.103249E+09
August 0.448945E+09 0.201148E+09 0.247797E+09 0.562345E+09 0.112215E+09
September 0.520653E+09 0.307293E+09 0.213361E+09 0.642987E+09 0.144682E+09
October 0.358991E+09 0.206968E+09 0.152023E+09 0.398992E+09 0.200094E+09
November 0.250879E+09 0.152564E+09 98314557.38 0.254590E+09 0.236211E+09
December 0.205721E+09 0.131914E+09 73806852.46 0.201278E+09 0.305748E+09
           
Annual Sum or Average 0.418738E+10 0.197936E+10 0.220802E+10 0.463246E+10 0.227222E+10
Minimum of Months 0.205721E+09 64618063.64 73806852.46 0.189588E+09 0.103249E+09
Maximum of Months 0.520653E+09 0.307293E+09 0.263986E+09 0.642987E+09 0.305748E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52296148.79 0.00 52296148.79 5810178.87 0.297316E+09
February 73759823.15 0.00 73759823.15 14664667.84 0.251992E+09
March 0.113018E+09 763.87 0.113017E+09 45905443.29 0.224890E+09
April 0.178718E+09 1187800.51 0.177530E+09 0.119878E+09 0.172776E+09
May 0.230890E+09 11774052.52 0.219116E+09 0.158677E+09 0.142065E+09
June 0.246156E+09 15397270.00 0.230758E+09 0.218139E+09 0.101128E+09
July 0.241849E+09 14224473.17 0.227624E+09 0.229074E+09 94002916.57
August 0.190413E+09 3560925.39 0.186852E+09 0.175603E+09 0.104947E+09
September 0.139769E+09 82607.68 0.139686E+09 0.109577E+09 0.145228E+09
October 92475413.30 0.00 92475413.30 44662549.32 0.205923E+09
November 53771554.59 0.00 53771554.59 8870192.24 0.249793E+09
December 37838893.74 0.00 37838893.74 683814.53 0.325701E+09
           
Annual Sum or Average 0.165095E+10 46227893.14 0.160473E+10 0.113155E+10 0.231576E+10
Minimum of Months 37838893.74 0.00 37838893.74 683814.53 94002916.57
Maximum of Months 0.246156E+09 15397270.00 0.230758E+09 0.229074E+09 0.325701E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.198462E+09 79042420.23 0.119420E+09 0.121340E+09 0.524338E+09
February 0.270698E+09 0.100866E+09 0.169832E+09 0.186277E+09 0.445650E+09
March 0.311380E+09 61414734.22 0.249966E+09 0.205990E+09 0.401760E+09
April 0.807271E+09 0.378498E+09 0.428772E+09 0.862520E+09 0.306252E+09
May 0.878305E+09 0.383093E+09 0.495212E+09 0.912126E+09 0.272020E+09
June 0.841083E+09 0.335996E+09 0.505087E+09 0.932675E+09 0.194717E+09
July 0.887034E+09 0.376787E+09 0.510247E+09 0.102801E+10 0.180466E+09
August 0.842638E+09 0.403400E+09 0.439238E+09 0.100196E+10 0.194496E+09
September 0.732111E+09 0.389014E+09 0.343096E+09 0.841589E+09 0.255101E+09
October 0.367956E+09 0.153873E+09 0.214083E+09 0.341103E+09 0.370329E+09
November 0.184287E+09 62706204.31 0.121580E+09 0.112895E+09 0.446479E+09
December 0.141644E+09 53003264.31 88640916.87 73747198.37 0.581671E+09
           
Annual Sum or Average 0.646287E+10 0.277770E+10 0.368517E+10 0.662023E+10 0.417328E+10
Minimum of Months 0.141644E+09 53003264.31 88640916.87 73747198.37 0.180466E+09
Maximum of Months 0.887034E+09 0.403400E+09 0.510247E+09 0.102801E+10 0.581671E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66229772.74 0.00 66229772.74 4977895.28 0.409244E+09
February 93412162.03 0.00 93412162.03 14033800.61 0.343234E+09
March 0.143130E+09 967.39 0.143129E+09 53462150.05 0.303090E+09
April 0.226335E+09 1504274.40 0.224831E+09 0.157413E+09 0.233375E+09
May 0.292407E+09 14911094.62 0.277496E+09 0.204945E+09 0.196543E+09
June 0.311741E+09 19499670.94 0.292241E+09 0.279314E+09 0.144184E+09
July 0.306286E+09 18014397.76 0.288272E+09 0.292176E+09 0.136363E+09
August 0.241146E+09 4509687.32 0.236636E+09 0.224304E+09 0.153782E+09
September 0.177008E+09 104617.41 0.176903E+09 0.140085E+09 0.206598E+09
October 0.117114E+09 0.00 0.117114E+09 52932488.19 0.284470E+09
November 68098281.09 0.00 68098281.09 8232143.31 0.344572E+09
December 47920571.43 0.00 47920571.43 201093.58 0.450567E+09
           
Annual Sum or Average 0.209083E+10 58544709.85 0.203228E+10 0.143208E+10 0.320602E+10
Minimum of Months 47920571.43 0.00 47920571.43 201093.58 0.136363E+09
Maximum of Months 0.311741E+09 19499670.94 0.292241E+09 0.292176E+09 0.450567E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 24415036.59 0.00 24415036.59 1835058.32 0.150864E+09
February 34435590.82 0.00 34435590.82 5173440.00 0.126530E+09
March 52763527.24 356.62 52763170.61 19708362.20 0.111732E+09
April 83436499.74 554537.83 82881961.91 58028871.81 86031737.77
May 0.107793E+09 5496846.90 0.102297E+09 75551118.68 72453707.87
June 0.114921E+09 7188386.13 0.107732E+09 0.102967E+09 53152255.68
July 0.112910E+09 6640852.93 0.106269E+09 0.107708E+09 50269000.16
August 88896459.85 1662457.48 87234002.37 82687868.91 56690514.60
September 65252479.21 38566.31 65213912.90 51641113.17 76160724.52
October 43173171.48 0.00 43173171.48 19513106.91 0.104868E+09
November 25103846.14 0.00 25103846.14 3034708.89 0.127024E+09
December 17665506.86 0.00 17665506.86 74131.42 0.166098E+09
           
Annual Sum or Average 0.770766E+09 21582004.20 0.749184E+09 0.527923E+09 0.118187E+10
Minimum of Months 17665506.86 0.00 17665506.86 74131.42 50269000.16
Maximum of Months 0.114921E+09 7188386.13 0.107732E+09 0.107708E+09 0.166098E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.139266E+09 90183137.34 49082764.60 0.139939E+09 0.132838E+09
February 0.152638E+09 93029421.80 59608931.11 0.157374E+09 0.115875E+09
March 0.104303E+09 30150528.10 74152630.13 87516027.11 0.107243E+09
April 0.206918E+09 91685143.13 0.115233E+09 0.239558E+09 87473797.54
May 0.179248E+09 58065761.49 0.121182E+09 0.191942E+09 80039303.52
June 0.160127E+09 38726197.32 0.121400E+09 0.179524E+09 58149212.18
July 0.178352E+09 55176861.55 0.123175E+09 0.214691E+09 55112551.34
August 0.209476E+09 93855004.78 0.115621E+09 0.264753E+09 59758173.36
September 0.242935E+09 0.143382E+09 99553201.59 0.302773E+09 74568073.83
October 0.167504E+09 96570534.75 70933434.58 0.187158E+09 0.100104E+09
November 0.117059E+09 71185959.25 45873176.30 0.118336E+09 0.117488E+09
December 95988358.37 61550378.44 34437979.94 92927039.86 0.152893E+09
           
Annual Sum or Average 0.195381E+10 0.923561E+09 0.103025E+10 0.217649E+10 0.114154E+10
Minimum of Months 95988358.37 30150528.10 34437979.94 87516027.11 55112551.34
Maximum of Months 0.242935E+09 0.143382E+09 0.123175E+09 0.302773E+09 0.152893E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.377996E+09 0.244775E+09 0.133221E+09 0.379822E+09 0.360551E+09
February 0.414292E+09 0.252501E+09 0.161791E+09 0.427147E+09 0.314510E+09
March 0.283100E+09 81834700.42 0.201265E+09 0.237536E+09 0.291080E+09
April 0.561618E+09 0.248852E+09 0.312766E+09 0.650208E+09 0.237422E+09
May 0.486515E+09 0.157602E+09 0.328912E+09 0.520971E+09 0.217243E+09
June 0.434616E+09 0.105111E+09 0.329506E+09 0.487265E+09 0.157829E+09
July 0.484084E+09 0.149761E+09 0.334322E+09 0.582714E+09 0.149587E+09
August 0.568561E+09 0.254742E+09 0.313819E+09 0.718595E+09 0.162196E+09
September 0.659375E+09 0.389167E+09 0.270208E+09 0.821788E+09 0.202393E+09
October 0.454640E+09 0.262112E+09 0.192528E+09 0.507984E+09 0.271704E+09
November 0.317722E+09 0.193213E+09 0.124509E+09 0.321189E+09 0.318886E+09
December 0.260532E+09 0.167060E+09 93471721.68 0.252223E+09 0.414984E+09
           
Annual Sum or Average 0.530305E+10 0.250673E+10 0.279632E+10 0.590744E+10 0.309838E+10
Minimum of Months 0.260532E+09 81834700.42 93471721.68 0.237536E+09 0.149587E+09
Maximum of Months 0.659375E+09 0.389167E+09 0.334322E+09 0.821788E+09 0.414984E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.298472E+09 0.193279E+09 0.105193E+09 0.303299E+09 0.265713E+09
February 0.327132E+09 0.199379E+09 0.127753E+09 0.337838E+09 0.234883E+09
March 0.223541E+09 64618063.64 0.158923E+09 0.191225E+09 0.215523E+09
April 0.443463E+09 0.196498E+09 0.246965E+09 0.506088E+09 0.176761E+09
May 0.384160E+09 0.124445E+09 0.259715E+09 0.405527E+09 0.158604E+09
June 0.343181E+09 82997281.99 0.260183E+09 0.378264E+09 0.112088E+09
July 0.382241E+09 0.118254E+09 0.263986E+09 0.454000E+09 0.104234E+09
August 0.448945E+09 0.201148E+09 0.247797E+09 0.562049E+09 0.111806E+09
September 0.520653E+09 0.307293E+09 0.213361E+09 0.644571E+09 0.143205E+09
October 0.358991E+09 0.206968E+09 0.152023E+09 0.400744E+09 0.197451E+09
November 0.250879E+09 0.152564E+09 98314557.38 0.255436E+09 0.233351E+09
December 0.205721E+09 0.131914E+09 73806852.46 0.202513E+09 0.302451E+09
           
Annual Sum or Average 0.418738E+10 0.197936E+10 0.220802E+10 0.464156E+10 0.225607E+10
Minimum of Months 0.205721E+09 64618063.64 73806852.46 0.191225E+09 0.104234E+09
Maximum of Months 0.520653E+09 0.307293E+09 0.263986E+09 0.644571E+09 0.302451E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.195660E+09 64128920.97 0.131532E+09 0.121318E+09 0.533511E+09
February 0.312615E+09 0.133073E+09 0.179541E+09 0.247947E+09 0.459241E+09
March 0.311355E+09 59870921.37 0.251484E+09 0.205677E+09 0.403135E+09
April 0.709636E+09 0.281355E+09 0.428281E+09 0.734304E+09 0.320623E+09
May 0.860491E+09 0.349933E+09 0.510558E+09 0.885942E+09 0.281415E+09
June 0.899047E+09 0.370125E+09 0.528922E+09 0.100168E+10 0.200403E+09
July 0.945570E+09 0.416516E+09 0.529053E+09 0.110093E+10 0.187069E+09
August 0.795714E+09 0.344711E+09 0.451003E+09 0.932292E+09 0.203745E+09
September 0.622261E+09 0.281272E+09 0.340989E+09 0.694821E+09 0.266656E+09
October 0.342754E+09 0.124483E+09 0.218272E+09 0.305264E+09 0.376795E+09
November 0.178958E+09 52801937.15 0.126156E+09 0.112733E+09 0.457837E+09
December 0.103093E+09 20956149.08 82136943.91 37864068.91 0.599361E+09
           
Annual Sum or Average 0.627716E+10 0.249923E+10 0.377793E+10 0.638077E+10 0.428979E+10
Minimum of Months 0.103093E+09 20956149.08 82136943.91 37864068.91 0.187069E+09
Maximum of Months 0.945570E+09 0.416516E+09 0.529053E+09 0.110093E+10 0.599361E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52296148.79 0.00 52296148.79 6827566.16 0.293312E+09
February 73759823.15 0.00 73759823.15 16047155.52 0.250308E+09
March 0.113018E+09 763.87 0.113017E+09 47921025.63 0.221919E+09
April 0.178718E+09 1187800.51 0.177530E+09 0.124232E+09 0.170772E+09
May 0.230890E+09 11774052.52 0.219116E+09 0.161296E+09 0.141766E+09
June 0.246156E+09 15397270.00 0.230758E+09 0.217363E+09 0.101718E+09
July 0.241849E+09 14224473.17 0.227624E+09 0.229091E+09 94489157.48
August 0.190413E+09 3560925.39 0.186852E+09 0.178215E+09 0.104245E+09
September 0.139769E+09 82607.68 0.139686E+09 0.115310E+09 0.142418E+09
October 92475413.30 0.00 92475413.30 47917617.39 0.202187E+09
November 53771554.59 0.00 53771554.59 10021822.49 0.246250E+09
December 37838893.74 0.00 37838893.74 965669.89 0.321722E+09
           
Annual Sum or Average 0.165095E+10 46227893.14 0.160473E+10 0.115521E+10 0.229111E+10
Minimum of Months 37838893.74 0.00 37838893.74 965669.89 94489157.48
Maximum of Months 0.246156E+09 15397270.00 0.230758E+09 0.229091E+09 0.321722E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.195660E+09 64128920.97 0.131532E+09 0.128649E+09 0.527778E+09
February 0.312615E+09 0.133073E+09 0.179541E+09 0.257898E+09 0.452995E+09
March 0.311355E+09 59870921.37 0.251484E+09 0.211125E+09 0.400333E+09
April 0.709636E+09 0.281355E+09 0.428281E+09 0.747883E+09 0.316226E+09
May 0.860491E+09 0.349933E+09 0.510558E+09 0.894769E+09 0.279017E+09
June 0.899047E+09 0.370125E+09 0.528922E+09 0.100679E+10 0.199074E+09
July 0.945570E+09 0.416516E+09 0.529053E+09 0.110715E+10 0.185484E+09
August 0.795714E+09 0.344711E+09 0.451003E+09 0.942537E+09 0.200516E+09
September 0.622261E+09 0.281272E+09 0.340989E+09 0.710308E+09 0.260597E+09
October 0.342754E+09 0.124483E+09 0.218272E+09 0.317309E+09 0.370510E+09
November 0.178958E+09 52801937.15 0.126156E+09 0.119679E+09 0.452426E+09
December 0.103093E+09 20956149.08 82136943.91 40950096.19 0.595409E+09
           
Annual Sum or Average 0.627716E+10 0.249923E+10 0.377793E+10 0.648504E+10 0.424036E+10
Minimum of Months 0.103093E+09 20956149.08 82136943.91 40950096.19 0.185484E+09
Maximum of Months 0.945570E+09 0.416516E+09 0.529053E+09 0.110715E+10 0.595409E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.437738E+09 0.283462E+09 0.154276E+09 0.429839E+09 0.406238E+09
February 0.479770E+09 0.292408E+09 0.187362E+09 0.483072E+09 0.358087E+09
March 0.327844E+09 94768591.74 0.233075E+09 0.270387E+09 0.325682E+09
April 0.650381E+09 0.288183E+09 0.362198E+09 0.735257E+09 0.262087E+09
May 0.563408E+09 0.182511E+09 0.380897E+09 0.592708E+09 0.232678E+09
June 0.503307E+09 0.121723E+09 0.381584E+09 0.558577E+09 0.162014E+09
July 0.560592E+09 0.173431E+09 0.387162E+09 0.669709E+09 0.150418E+09
August 0.658421E+09 0.295003E+09 0.363418E+09 0.823969E+09 0.163154E+09
September 0.763588E+09 0.450674E+09 0.312914E+09 0.938232E+09 0.213522E+09
October 0.526495E+09 0.303539E+09 0.222957E+09 0.576397E+09 0.300886E+09
November 0.367938E+09 0.223750E+09 0.144188E+09 0.363056E+09 0.358552E+09
December 0.301709E+09 0.193464E+09 0.108245E+09 0.287206E+09 0.462249E+09
           
Annual Sum or Average 0.614119E+10 0.290292E+10 0.323827E+10 0.672841E+10 0.339557E+10
Minimum of Months 0.301709E+09 94768591.74 0.108245E+09 0.270387E+09 0.150418E+09
Maximum of Months 0.763588E+09 0.450674E+09 0.387162E+09 0.938232E+09 0.462249E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.366059E+09 0.00 0.366059E+09 12861327.64 0.254879E+10
February 0.516299E+09 0.00 0.516299E+09 41955169.79 0.216012E+10
March 0.791093E+09 5346.90 0.791088E+09 0.211904E+09 0.193297E+10
April 0.125098E+10 8314288.68 0.124266E+10 0.751512E+09 0.142562E+10
May 0.161617E+10 82415246.22 0.153375E+10 0.975180E+09 0.120463E+10
June 0.172303E+10 0.107777E+09 0.161525E+10 0.139424E+10 0.875408E+09
July 0.169288E+10 99567541.14 0.159331E+10 0.147655E+10 0.820267E+09
August 0.133284E+10 24925533.69 0.130792E+10 0.113667E+10 0.913891E+09
September 0.978343E+09 578231.83 0.977764E+09 0.699218E+09 0.122928E+10
October 0.647303E+09 0.00 0.647303E+09 0.230006E+09 0.179629E+10
November 0.376387E+09 0.00 0.376387E+09 22484246.69 0.221059E+10
December 0.264862E+09 0.00 0.264862E+09 0.00 0.282560E+10
           
Annual Sum or Average 0.115562E+11 0.323583E+09 0.112327E+11 0.695258E+10 0.199435E+11
Minimum of Months 0.264862E+09 0.00 0.264862E+09 0.00 0.820267E+09
Maximum of Months 0.172303E+10 0.107777E+09 0.161525E+10 0.147655E+10 0.282560E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.366059E+09 0.00 0.366059E+09 9427335.86 0.262722E+10
February 0.516299E+09 0.00 0.516299E+09 33701779.66 0.222583E+10
March 0.791093E+09 5346.90 0.791088E+09 0.190840E+09 0.198936E+10
April 0.125098E+10 8314288.68 0.124266E+10 0.723466E+09 0.145726E+10
May 0.161617E+10 82415246.22 0.153375E+10 0.940664E+09 0.123040E+10
June 0.172303E+10 0.107777E+09 0.161525E+10 0.136375E+10 0.893670E+09
July 0.169288E+10 99567541.14 0.159331E+10 0.144758E+10 0.837262E+09
August 0.133284E+10 24925533.69 0.130792E+10 0.111057E+10 0.934428E+09
September 0.978343E+09 578231.83 0.977764E+09 0.675296E+09 0.125715E+10
October 0.647303E+09 0.00 0.647303E+09 0.210451E+09 0.184912E+10
November 0.376387E+09 0.00 0.376387E+09 16944439.92 0.228441E+10
December 0.264862E+09 0.00 0.264862E+09 0.00 0.291239E+10
           
Annual Sum or Average 0.115562E+11 0.323583E+09 0.112327E+11 0.672269E+10 0.204985E+11
Minimum of Months 0.264862E+09 0.00 0.264862E+09 0.00 0.837262E+09
Maximum of Months 0.172303E+10 0.107777E+09 0.161525E+10 0.144758E+10 0.291239E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52296148.79 0.00 52296148.79 8865975.38 0.300192E+09
February 73759823.15 0.00 73759823.15 18271543.35 0.259356E+09
March 0.113018E+09 763.87 0.113017E+09 57123246.29 0.232217E+09
April 0.178718E+09 1187800.51 0.177530E+09 0.153214E+09 0.181353E+09
May 0.230890E+09 11774052.52 0.219116E+09 0.194363E+09 0.162218E+09
June 0.246156E+09 15397270.00 0.230758E+09 0.262512E+09 0.118972E+09
July 0.241849E+09 14224473.17 0.227624E+09 0.279928E+09 0.112934E+09
August 0.190413E+09 3560925.39 0.186852E+09 0.223555E+09 0.119839E+09
September 0.139769E+09 82607.68 0.139686E+09 0.144880E+09 0.152978E+09
October 92475413.30 0.00 92475413.30 59501491.85 0.216216E+09
November 53771554.59 0.00 53771554.59 12655977.89 0.261196E+09
December 37838893.74 0.00 37838893.74 1709268.72 0.339219E+09
           
Annual Sum or Average 0.165095E+10 46227893.14 0.160473E+10 0.141658E+10 0.245669E+10
Minimum of Months 37838893.74 0.00 37838893.74 1709268.72 0.112934E+09
Maximum of Months 0.246156E+09 15397270.00 0.230758E+09 0.279928E+09 0.339219E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.396896E+09 0.158074E+09 0.238823E+09 0.266635E+09 0.107055E+10
February 0.541358E+09 0.201718E+09 0.339640E+09 0.395987E+09 0.927128E+09
March 0.622717E+09 0.122821E+09 0.499896E+09 0.461935E+09 0.839671E+09
April 0.161443E+10 0.756943E+09 0.857483E+09 0.186690E+10 0.655350E+09
May 0.175648E+10 0.766132E+09 0.990353E+09 0.196375E+10 0.615500E+09
June 0.168205E+10 0.671945E+09 0.101010E+10 0.203534E+10 0.452171E+09
July 0.177394E+10 0.753521E+09 0.102042E+10 0.224821E+10 0.426392E+09
August 0.168516E+10 0.806743E+09 0.878414E+09 0.219163E+10 0.446094E+09
September 0.146412E+10 0.777974E+09 0.686144E+09 0.183370E+10 0.550353E+09
October 0.735860E+09 0.307724E+09 0.428136E+09 0.749626E+09 0.786798E+09
November 0.368547E+09 0.125404E+09 0.243143E+09 0.246853E+09 0.941965E+09
December 0.283268E+09 0.105999E+09 0.177269E+09 0.160660E+09 0.122477E+10
           
Annual Sum or Average 0.129248E+11 0.555500E+10 0.736983E+10 0.144212E+11 0.893674E+10
Minimum of Months 0.283268E+09 0.105999E+09 0.177269E+09 0.160660E+09 0.426392E+09
Maximum of Months 0.177394E+10 0.806743E+09 0.102042E+10 0.224821E+10 0.122477E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.298472E+09 0.193279E+09 0.105193E+09 0.315910E+09 0.271938E+09
February 0.327132E+09 0.199379E+09 0.127753E+09 0.353228E+09 0.243430E+09
March 0.223541E+09 64618063.64 0.158923E+09 0.207318E+09 0.226445E+09
April 0.443463E+09 0.196498E+09 0.246965E+09 0.546847E+09 0.184776E+09
May 0.384160E+09 0.124445E+09 0.259715E+09 0.445862E+09 0.175878E+09
June 0.343181E+09 82997281.99 0.260183E+09 0.427672E+09 0.127226E+09
July 0.382241E+09 0.118254E+09 0.263986E+09 0.509608E+09 0.120092E+09
August 0.448945E+09 0.201148E+09 0.247797E+09 0.616010E+09 0.124480E+09
September 0.520653E+09 0.307293E+09 0.213361E+09 0.689801E+09 0.151809E+09
October 0.358991E+09 0.206968E+09 0.152023E+09 0.425611E+09 0.210182E+09
November 0.250879E+09 0.152564E+09 98314557.38 0.266144E+09 0.246880E+09
December 0.205721E+09 0.131914E+09 73806852.46 0.208237E+09 0.319469E+09
           
Annual Sum or Average 0.418738E+10 0.197936E+10 0.220802E+10 0.501225E+10 0.240260E+10
Minimum of Months 0.205721E+09 64618063.64 73806852.46 0.207318E+09 0.120092E+09
Maximum of Months 0.520653E+09 0.307293E+09 0.263986E+09 0.689801E+09 0.319469E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66229772.74 0.00 66229772.74 3969537.87 0.415077E+09
February 93412162.03 0.00 93412162.03 11514437.02 0.349050E+09
March 0.143130E+09 967.39 0.143129E+09 49359523.41 0.307537E+09
April 0.226335E+09 1504274.40 0.224831E+09 0.148809E+09 0.233516E+09
May 0.292407E+09 14911094.62 0.277496E+09 0.195931E+09 0.196492E+09
June 0.311741E+09 19499670.94 0.292241E+09 0.268592E+09 0.145538E+09
July 0.306286E+09 18014397.76 0.288272E+09 0.280526E+09 0.138090E+09
August 0.241146E+09 4509687.32 0.236636E+09 0.215153E+09 0.154358E+09
September 0.177008E+09 104617.41 0.176903E+09 0.134440E+09 0.204388E+09
October 0.117114E+09 0.00 0.117114E+09 49588466.35 0.285039E+09
November 68098281.09 0.00 68098281.09 6720417.87 0.351154E+09
December 47920571.43 0.00 47920571.43 95582.30 0.458341E+09
           
Annual Sum or Average 0.209083E+10 58544709.85 0.203228E+10 0.136470E+10 0.323858E+10
Minimum of Months 47920571.43 0.00 47920571.43 95582.30 0.138090E+09
Maximum of Months 0.311741E+09 19499670.94 0.292241E+09 0.280526E+09 0.458341E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 59256028.61 0.00 59256028.61 3551560.58 0.371297E+09
February 83576215.31 0.00 83576215.31 10302010.43 0.312295E+09
March 0.128059E+09 865.53 0.128058E+09 44162152.62 0.275155E+09
April 0.202503E+09 1345880.01 0.201157E+09 0.133140E+09 0.208928E+09
May 0.261618E+09 13341012.85 0.248277E+09 0.175301E+09 0.175802E+09
June 0.278916E+09 17446429.47 0.261469E+09 0.240310E+09 0.130213E+09
July 0.274036E+09 16117549.93 0.257918E+09 0.250988E+09 0.123549E+09
August 0.215754E+09 4034834.34 0.211720E+09 0.192498E+09 0.138104E+09
September 0.158370E+09 93601.59 0.158276E+09 0.120284E+09 0.182867E+09
October 0.104783E+09 0.00 0.104783E+09 44366988.74 0.255025E+09
November 60927790.11 0.00 60927790.11 6012783.33 0.314157E+09
December 42874716.83 0.00 42874716.83 85517.85 0.410029E+09
           
Annual Sum or Average 0.187067E+10 52380173.73 0.181829E+10 0.122100E+10 0.289742E+10
Minimum of Months 42874716.83 0.00 42874716.83 85517.85 0.123549E+09
Maximum of Months 0.278916E+09 17446429.47 0.261469E+09 0.250988E+09 0.410029E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111429E+10 0.721568E+09 0.392718E+09 0.110655E+10 0.107568E+10
February 0.122128E+10 0.744341E+09 0.476939E+09 0.124259E+10 0.941718E+09
March 0.834544E+09 0.241238E+09 0.593305E+09 0.683056E+09 0.871267E+09
April 0.165558E+10 0.733585E+09 0.921994E+09 0.188767E+10 0.701916E+09
May 0.143418E+10 0.464592E+09 0.969593E+09 0.150729E+10 0.642657E+09
June 0.128120E+10 0.309854E+09 0.971342E+09 0.140443E+10 0.471257E+09
July 0.142702E+10 0.441478E+09 0.985540E+09 0.168220E+10 0.448194E+09
August 0.167605E+10 0.750947E+09 0.925100E+09 0.208731E+10 0.481019E+09
September 0.194375E+10 0.114722E+10 0.796539E+09 0.239963E+10 0.592137E+09
October 0.134022E+10 0.772674E+09 0.567548E+09 0.148253E+10 0.804597E+09
November 0.936606E+09 0.569569E+09 0.367038E+09 0.933915E+09 0.958238E+09
December 0.768016E+09 0.492473E+09 0.275543E+09 0.734724E+09 0.124580E+10
           
Annual Sum or Average 0.156327E+11 0.738953E+10 0.824320E+10 0.171519E+11 0.923447E+10
Minimum of Months 0.768016E+09 0.241238E+09 0.275543E+09 0.683056E+09 0.448194E+09
Maximum of Months 0.194375E+10 0.114722E+10 0.985540E+09 0.239963E+10 0.124580E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 558.51 513.62 563.62 364.98 198.64 0.00 0.00
February 694.73 496.31 683.92 416.83 267.09 0.00 0.00
March 353.11 413.28 422.12 122.02 300.10 0.00 0.00
April 986.81 343.86 865.32 383.42 481.90 0.00 0.00
May 775.99 292.66 725.42 235.00 490.43 0.00 0.00
June 754.34 214.80 669.64 161.95 507.69 0.00 0.00
July 867.89 197.64 721.80 223.30 498.49 0.00 0.00
August 1061.41 218.05 847.76 379.84 467.92 0.00 0.00
September 1249.76 286.81 1015.94 599.62 416.32 0.00 0.00
October 745.63 381.91 677.90 390.83 287.07 0.00 0.00
November 488.57 467.37 489.54 297.70 191.84 0.00 0.00
December 373.60 579.38 388.47 249.10 139.37 0.00 0.00
               
Annual Sum or Average 741.53 366.51 671.57 317.45 354.12 0.00 0.00
Minimum of Months 353.11 197.64 388.47 122.02 139.37 0.00 0.00
Maximum of Months 1249.76 579.38 1015.94 599.62 507.69 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1554.43 1487.26 1587.11 1027.75 559.36 0.00 0.00
February 1934.44 1443.47 1925.88 1173.78 752.10 0.00 0.00
March 974.31 1204.38 1188.66 343.60 845.06 0.00 0.00
April 2743.68 1026.99 2436.68 1079.69 1356.99 0.00 0.00
May 2147.17 882.99 2042.74 661.73 1381.00 0.00 0.00
June 2082.29 660.37 1885.66 456.04 1429.61 0.00 0.00
July 2402.00 610.50 2032.53 628.81 1403.72 0.00 0.00
August 2950.08 677.50 2387.23 1069.59 1317.63 0.00 0.00
September 3483.39 875.70 2860.82 1688.48 1172.34 0.00 0.00
October 2075.34 1138.23 1908.91 1100.54 808.37 0.00 0.00
November 1358.35 1370.49 1378.50 838.29 540.21 0.00 0.00
December 1040.13 1671.83 1093.90 701.44 392.46 0.00 0.00
               
Annual Sum or Average 2059.30 1085.69 1891.09 893.91 997.17 0.00 0.00
Minimum of Months 974.31 610.50 1093.90 343.60 392.46 0.00 0.00
Maximum of Months 3483.39 1671.83 2860.82 1688.48 1429.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2039.08 2067.83 2061.74 1335.10 726.64 0.00 0.00
February 2541.31 1999.54 2501.82 1524.80 977.02 0.00 0.00
March 1263.87 1695.79 1544.14 446.36 1097.78 0.00 0.00
April 3618.33 1420.84 3165.39 1402.59 1762.80 0.00 0.00
May 2819.22 1236.05 2653.63 859.63 1794.00 0.00 0.00
June 2723.99 932.70 2449.58 592.43 1857.15 0.00 0.00
July 3152.04 856.95 2640.37 816.86 1823.51 0.00 0.00
August 3887.88 937.50 3101.14 1389.46 1711.68 0.00 0.00
September 4593.55 1202.25 3716.37 2193.43 1522.94 0.00 0.00
October 2728.46 1592.99 2479.78 1429.67 1050.12 0.00 0.00
November 1778.69 1919.85 1790.75 1088.99 701.76 0.00 0.00
December 1359.70 2327.67 1421.04 911.21 509.83 0.00 0.00
               
Annual Sum or Average 2705.07 1513.46 2456.63 1161.25 1295.39 0.00 0.00
Minimum of Months 1263.87 856.95 1421.04 446.36 509.83 0.00 0.00
Maximum of Months 4593.55 2327.67 3716.37 2193.43 1857.15 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 148.64 293.76 184.49 96.11 88.38 0.00 0.00
February 237.27 285.46 264.45 137.42 127.02 0.00 0.00
March 145.75 232.46 199.71 46.48 153.23 0.00 0.00
April 479.68 191.80 444.87 184.36 260.51 0.00 0.00
May 483.35 162.86 464.70 177.11 287.59 0.00 0.00
June 535.75 120.26 479.25 174.82 304.44 0.00 0.00
July 583.83 108.47 495.75 199.66 296.09 0.00 0.00
August 560.71 118.57 464.70 203.80 260.90 0.00 0.00
September 517.53 158.93 440.94 227.07 213.87 0.00 0.00
October 261.30 215.74 262.00 123.75 138.25 0.00 0.00
November 136.43 265.55 165.83 79.23 86.60 0.00 0.00
December 81.25 332.24 115.30 57.08 58.22 0.00 0.00
               
Annual Sum or Average 347.77 206.78 331.83 142.02 189.81 0.00 0.00
Minimum of Months 81.25 108.47 115.30 46.48 58.22 0.00 0.00
Maximum of Months 583.83 332.24 495.75 227.07 304.44 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 46.28 307.73 92.58 23.94 68.63 0.00 0.00
February 109.81 291.62 159.71 55.01 104.70 0.00 0.00
March 93.90 233.91 158.44 22.35 136.09 0.00 0.00
April 337.15 188.59 342.73 109.01 233.72 0.00 0.00
May 395.39 156.41 407.47 135.05 272.43 0.00 0.00
June 474.66 115.05 441.82 148.74 293.09 0.00 0.00
July 501.37 103.89 443.33 160.82 282.51 0.00 0.00
August 420.46 114.74 368.18 130.03 238.15 0.00 0.00
September 318.10 157.28 293.99 108.55 185.45 0.00 0.00
October 134.10 216.77 162.50 46.48 116.02 0.00 0.00
November 47.72 272.36 89.79 20.37 69.42 0.00 0.00
December 14.30 345.12 52.62 7.82 44.79 0.00 0.00
               
Annual Sum or Average 241.60 208.22 251.40 80.72 170.68 0.00 0.00
Minimum of Months 14.30 103.89 52.62 7.82 44.79 0.00 0.00
Maximum of Months 501.37 345.12 443.33 160.82 293.09 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 88.90 81.35 89.13 57.72 31.41 0.00 0.00
February 110.53 79.73 108.16 65.92 42.24 0.00 0.00
March 58.04 61.92 66.76 19.30 47.46 0.00 0.00
April 154.58 60.15 136.84 60.64 76.21 0.00 0.00
May 119.79 52.42 114.72 37.16 77.56 0.00 0.00
June 115.62 39.67 105.90 25.61 80.29 0.00 0.00
July 134.53 36.27 114.15 35.31 78.83 0.00 0.00
August 166.56 39.51 134.07 60.07 74.00 0.00 0.00
September 196.70 51.66 160.66 94.82 65.84 0.00 0.00
October 117.65 64.75 107.20 61.81 45.40 0.00 0.00
November 77.79 73.75 77.42 47.08 30.34 0.00 0.00
December 60.53 86.44 61.43 39.39 22.04 0.00 0.00
               
Annual Sum or Average 116.61 60.53 106.20 50.20 56.00 0.00 0.00
Minimum of Months 58.04 36.27 61.43 19.30 22.04 0.00 0.00
Maximum of Months 196.70 86.44 160.66 94.82 80.29 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1.47 93.18 15.62 0.00 15.62 0.00 0.00
February 4.38 86.80 24.39 0.00 24.39 0.00 0.00
March 13.05 69.96 33.76 0.00 33.76 0.00 0.00
April 40.49 53.16 55.17 0.37 54.80 0.00 0.00
May 51.28 42.45 68.97 3.52 65.46 0.00 0.00
June 71.72 30.85 75.98 4.75 71.23 0.00 0.00
July 73.37 27.51 72.25 4.25 68.00 0.00 0.00
August 57.49 30.36 56.88 1.06 55.82 0.00 0.00
September 37.83 43.79 43.14 0.03 43.12 0.00 0.00
October 13.89 63.43 27.62 0.00 27.62 0.00 0.00
November 2.38 81.20 16.60 0.00 16.60 0.00 0.00
December 0.11 102.63 11.30 0.00 11.30 0.00 0.00
               
Annual Sum or Average 30.76 60.31 41.89 1.17 40.71 0.00 0.00
Minimum of Months 0.11 27.51 11.30 0.00 11.30 0.00 0.00
Maximum of Months 73.37 102.63 75.98 4.75 71.23 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 148.95 292.23 185.53 101.67 83.86 0.00 0.00
February 209.57 281.16 247.12 124.11 123.01 0.00 0.00
March 144.36 230.95 199.72 47.06 152.66 0.00 0.00
April 519.02 184.21 482.54 221.84 260.70 0.00 0.00
May 485.24 157.72 471.35 189.49 281.86 0.00 0.00
June 502.71 116.36 456.89 161.65 295.24 0.00 0.00
July 550.10 104.61 473.89 184.83 289.07 0.00 0.00
August 578.91 113.26 482.22 225.71 256.51 0.00 0.00
September 566.02 153.57 483.32 268.64 214.68 0.00 0.00
October 271.36 213.90 271.41 134.72 136.69 0.00 0.00
November 137.04 263.43 167.89 83.05 84.84 0.00 0.00
December 98.37 330.40 129.69 69.04 60.65 0.00 0.00
               
Annual Sum or Average 351.25 203.11 337.72 150.85 186.87 0.00 0.00
Minimum of Months 98.37 104.61 129.69 47.06 60.65 0.00 0.00
Maximum of Months 578.91 330.40 483.32 268.64 295.24 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 42.25 301.55 93.62 29.51 64.11 0.00 0.00
February 78.73 284.04 142.39 41.69 100.69 0.00 0.00
March 91.86 231.77 158.45 22.93 135.52 0.00 0.00
April 375.55 181.35 380.40 146.48 233.91 0.00 0.00
May 397.73 152.54 414.13 147.43 266.70 0.00 0.00
June 442.85 113.00 419.46 135.57 283.89 0.00 0.00
July 468.28 101.41 421.48 145.99 275.49 0.00 0.00
August 438.70 110.85 385.70 151.94 233.76 0.00 0.00
September 363.57 151.06 336.37 150.11 186.26 0.00 0.00
October 141.36 212.48 171.91 57.45 114.46 0.00 0.00
November 43.57 265.21 91.84 24.19 67.65 0.00 0.00
December 23.17 334.15 67.01 19.79 47.22 0.00 0.00
               
Annual Sum or Average 242.94 202.90 257.29 89.55 167.74 0.00 0.00
Minimum of Months 23.17 101.41 67.01 19.79 47.22 0.00 0.00
Maximum of Months 468.28 334.15 421.48 151.94 283.89 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 178.96 375.69 226.97 125.06 101.91 0.00 0.00
February 240.44 362.97 287.19 142.83 144.36 0.00 0.00
March 146.44 301.35 217.78 41.81 175.97 0.00 0.00
April 426.00 248.19 416.01 132.17 283.84 0.00 0.00
May 366.86 207.39 397.98 88.14 309.84 0.00 0.00
June 400.92 155.64 394.06 65.79 328.27 0.00 0.00
July 443.59 142.68 403.83 85.72 318.11 0.00 0.00
August 480.68 160.37 413.71 132.46 281.25 0.00 0.00
September 506.82 214.93 441.58 205.51 236.06 0.00 0.00
October 283.42 281.01 292.13 133.92 158.21 0.00 0.00
November 165.20 341.58 203.70 102.01 101.69 0.00 0.00
December 116.11 429.40 157.60 85.35 72.24 0.00 0.00
               
Annual Sum or Average 312.87 267.97 320.85 111.31 209.54 0.00 0.00
Minimum of Months 116.11 142.68 157.60 41.81 72.24 0.00 0.00
Maximum of Months 506.82 429.40 441.58 205.51 328.27 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 149.64 289.50 184.49 96.11 88.38 0.00 0.00
February 237.73 282.51 264.45 137.42 127.02 0.00 0.00
March 146.33 229.13 199.71 46.48 153.23 0.00 0.00
April 476.46 189.80 444.87 184.36 260.51 0.00 0.00
May 479.60 161.71 464.70 177.11 287.59 0.00 0.00
June 531.16 119.33 479.25 174.82 304.44 0.00 0.00
July 579.26 107.47 495.75 199.66 296.09 0.00 0.00
August 556.98 116.87 464.70 203.80 260.90 0.00 0.00
September 515.31 156.69 440.94 227.07 213.87 0.00 0.00
October 261.43 212.23 262.00 123.75 138.25 0.00 0.00
November 137.15 261.78 165.83 79.23 86.60 0.00 0.00
December 81.89 328.84 115.30 57.08 58.22 0.00 0.00
               
Annual Sum or Average 346.21 204.26 331.83 142.02 189.81 0.00 0.00
Minimum of Months 81.89 107.47 115.30 46.48 58.22 0.00 0.00
Maximum of Months 579.26 328.84 495.75 227.07 304.44 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 47.12 303.09 92.58 23.94 68.63 0.00 0.00
February 110.61 288.09 159.71 55.01 104.70 0.00 0.00
March 94.77 230.38 158.44 22.35 136.09 0.00 0.00
April 334.83 186.25 342.73 109.01 233.72 0.00 0.00
May 392.29 155.11 407.47 135.05 272.43 0.00 0.00
June 470.34 114.11 441.82 148.74 293.09 0.00 0.00
July 497.25 102.89 443.33 160.82 282.51 0.00 0.00
August 417.53 112.87 368.18 130.03 238.15 0.00 0.00
September 317.41 154.37 293.99 108.55 185.45 0.00 0.00
October 135.10 212.56 162.50 46.48 116.02 0.00 0.00
November 48.64 268.15 89.79 20.37 69.42 0.00 0.00
December 14.61 341.38 52.62 7.82 44.79 0.00 0.00
               
Annual Sum or Average 240.53 205.37 251.40 80.72 170.68 0.00 0.00
Minimum of Months 14.61 102.89 52.62 7.82 44.79 0.00 0.00
Maximum of Months 497.25 341.38 443.33 160.82 293.09 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 160.48 151.67 163.43 105.83 57.60 0.00 0.00
February 199.68 148.02 198.32 120.87 77.45 0.00 0.00
March 100.95 121.60 122.40 35.38 87.02 0.00 0.00
April 283.66 101.11 250.92 111.18 139.74 0.00 0.00
May 221.29 86.87 210.35 68.14 142.21 0.00 0.00
June 215.50 62.51 194.18 46.96 147.22 0.00 0.00
July 250.04 56.16 209.30 64.75 144.55 0.00 0.00
August 307.63 60.91 245.83 110.14 135.68 0.00 0.00
September 361.97 82.38 294.59 173.87 120.72 0.00 0.00
October 215.20 112.34 196.57 113.33 83.24 0.00 0.00
November 140.07 138.33 141.95 86.32 55.63 0.00 0.00
December 107.23 172.58 112.65 72.23 40.41 0.00 0.00
               
Annual Sum or Average 213.36 107.67 194.74 92.05 102.68 0.00 0.00
Minimum of Months 100.95 56.16 112.65 35.38 40.41 0.00 0.00
Maximum of Months 361.97 172.58 294.59 173.87 147.22 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 4.80 951.61 136.67 0.00 136.67 0.00 0.00
February 17.34 892.91 213.42 0.00 213.42 0.00 0.00
March 79.12 721.69 295.36 0.00 295.36 0.00 0.00
April 289.94 550.01 482.63 3.21 479.42 0.00 0.00
May 364.09 449.76 603.41 30.77 572.64 0.00 0.00
June 537.90 337.73 664.75 41.58 623.17 0.00 0.00
July 551.28 306.25 632.05 37.17 594.87 0.00 0.00
August 424.38 341.21 497.63 9.31 488.32 0.00 0.00
September 269.76 474.26 377.45 0.22 377.22 0.00 0.00
October 85.87 670.66 241.68 0.00 241.68 0.00 0.00
November 8.67 852.85 145.21 0.00 145.21 0.00 0.00
December 0.00 1054.96 98.89 0.00 98.89 0.00 0.00
               
Annual Sum or Average 220.46 632.40 366.45 10.26 356.19 0.00 0.00
Minimum of Months 0.00 306.25 98.89 0.00 98.89 0.00 0.00
Maximum of Months 551.28 1054.96 664.75 41.58 623.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3.52 980.89 136.67 0.00 136.67 0.00 0.00
February 13.93 920.07 213.42 0.00 213.42 0.00 0.00
March 71.25 742.74 295.36 0.00 295.36 0.00 0.00
April 279.12 562.22 482.63 3.21 479.42 0.00 0.00
May 351.20 459.38 603.41 30.77 572.64 0.00 0.00
June 526.14 344.78 664.75 41.58 623.17 0.00 0.00
July 540.46 312.60 632.05 37.17 594.87 0.00 0.00
August 414.64 348.88 497.63 9.31 488.32 0.00 0.00
September 260.53 485.01 377.45 0.22 377.22 0.00 0.00
October 78.57 690.38 241.68 0.00 241.68 0.00 0.00
November 6.54 881.33 145.21 0.00 145.21 0.00 0.00
December 0.00 1087.36 98.89 0.00 98.89 0.00 0.00
               
Annual Sum or Average 213.18 650.00 366.45 10.26 356.19 0.00 0.00
Minimum of Months 0.00 312.60 98.89 0.00 98.89 0.00 0.00
Maximum of Months 540.46 1087.36 664.75 41.58 623.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 202.71 595.21 279.15 131.18 147.97 0.00 0.00
February 308.30 582.12 389.49 165.80 223.69 0.00 0.00
March 267.80 481.34 358.15 69.98 288.17 0.00 0.00
April 984.46 388.21 862.89 368.30 494.59 0.00 0.00
May 966.45 350.27 885.43 336.90 548.53 0.00 0.00
June 1048.23 266.15 876.31 297.20 579.11 0.00 0.00
July 1131.22 243.25 895.32 330.79 564.53 0.00 0.00
August 1129.22 255.27 867.87 377.63 490.24 0.00 0.00
September 1025.14 325.59 819.65 418.73 400.92 0.00 0.00
October 457.71 449.67 443.30 192.16 251.13 0.00 0.00
November 195.51 552.15 259.72 107.24 152.48 0.00 0.00
December 128.22 693.05 196.69 88.83 107.87 0.00 0.00
               
Annual Sum or Average 654.84 431.16 594.98 240.38 354.60 0.00 0.00
Minimum of Months 128.22 243.25 196.69 69.98 107.87 0.00 0.00
Maximum of Months 1131.22 693.05 895.32 418.73 579.11 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 388.97 668.24 462.88 269.40 193.48 0.00 0.00
February 508.18 648.17 577.99 307.68 270.31 0.00 0.00
March 286.27 539.17 412.83 90.07 322.76 0.00 0.00
April 836.43 440.89 804.17 284.12 520.05 0.00 0.00
May 694.28 371.86 742.31 184.01 558.31 0.00 0.00
June 730.96 280.99 722.16 133.80 588.37 0.00 0.00
July 820.08 258.60 749.45 177.57 571.88 0.00 0.00
August 929.65 286.92 796.35 283.56 512.79 0.00 0.00
September 1022.60 376.39 879.29 442.68 436.62 0.00 0.00
October 583.71 497.16 583.23 288.48 294.74 0.00 0.00
November 351.66 612.81 411.12 219.74 191.38 0.00 0.00
December 254.65 769.61 320.64 183.87 136.78 0.00 0.00
               
Annual Sum or Average 616.89 478.41 621.33 237.84 383.49 0.00 0.00
Minimum of Months 254.65 258.60 320.64 90.07 136.78 0.00 0.00
Maximum of Months 1022.60 769.61 879.29 442.68 588.37 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.149593E+10 0.137568E+10 0.150959E+10 0.977552E+09 0.532037E+09 0.00 0.00
February 0.168069E+10 0.120067E+10 0.165454E+10 0.100840E+10 0.646136E+09 0.00 0.00
March 0.945760E+09 0.110694E+10 0.113060E+10 0.326821E+09 0.803783E+09 0.00 0.00
April 0.255782E+10 0.891277E+09 0.224291E+10 0.993833E+09 0.124907E+10 0.00 0.00
May 0.207840E+10 0.783853E+09 0.194297E+10 0.629412E+09 0.131355E+10 0.00 0.00
June 0.195525E+10 0.556759E+09 0.173570E+10 0.419778E+09 0.131592E+10 0.00 0.00
July 0.232455E+10 0.529367E+09 0.193326E+10 0.598097E+09 0.133516E+10 0.00 0.00
August 0.284287E+10 0.584015E+09 0.227063E+10 0.101735E+10 0.125328E+10 0.00 0.00
September 0.323937E+10 0.743422E+09 0.263332E+10 0.155420E+10 0.107911E+10 0.00 0.00
October 0.199710E+10 0.102291E+10 0.181568E+10 0.104679E+10 0.768888E+09 0.00 0.00
November 0.126637E+10 0.121143E+10 0.126888E+10 0.771630E+09 0.497246E+09 0.00 0.00
December 0.100066E+10 0.155180E+10 0.104048E+10 0.667184E+09 0.373294E+09 0.00 0.00
               
Annual Sum or Average 0.233848E+11 0.115581E+11 0.211785E+11 0.100111E+11 0.111675E+11 0.00 0.00
Minimum of Months 0.945760E+09 0.529367E+09 0.104048E+10 0.326821E+09 0.373294E+09 0.00 0.00
Maximum of Months 0.323937E+10 0.155180E+10 0.263332E+10 0.155420E+10 0.133516E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.416338E+10 0.398347E+10 0.425090E+10 0.275272E+10 0.149818E+10 0.00 0.00
February 0.467980E+10 0.349205E+10 0.465908E+10 0.283960E+10 0.181948E+10 0.00 0.00
March 0.260960E+10 0.322581E+10 0.318371E+10 0.920306E+09 0.226340E+10 0.00 0.00
April 0.711163E+10 0.266195E+10 0.631588E+10 0.279857E+10 0.351731E+10 0.00 0.00
May 0.575099E+10 0.236500E+10 0.547127E+10 0.177238E+10 0.369888E+10 0.00 0.00
June 0.539730E+10 0.171169E+10 0.488762E+10 0.118207E+10 0.370556E+10 0.00 0.00
July 0.643353E+10 0.163516E+10 0.544392E+10 0.168420E+10 0.375972E+10 0.00 0.00
August 0.790149E+10 0.181462E+10 0.639395E+10 0.286480E+10 0.352915E+10 0.00 0.00
September 0.902896E+10 0.226980E+10 0.741524E+10 0.437654E+10 0.303871E+10 0.00 0.00
October 0.555858E+10 0.304864E+10 0.511283E+10 0.294769E+10 0.216514E+10 0.00 0.00
November 0.352083E+10 0.355231E+10 0.357307E+10 0.217286E+10 0.140021E+10 0.00 0.00
December 0.278587E+10 0.447784E+10 0.292991E+10 0.187874E+10 0.105117E+10 0.00 0.00
               
Annual Sum or Average 0.649420E+11 0.342383E+11 0.596374E+11 0.281905E+11 0.314469E+11 0.00 0.00
Minimum of Months 0.260960E+10 0.163516E+10 0.292991E+10 0.920306E+09 0.105117E+10 0.00 0.00
Maximum of Months 0.902896E+10 0.447784E+10 0.741524E+10 0.437654E+10 0.375972E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.546148E+10 0.553848E+10 0.552217E+10 0.357594E+10 0.194622E+10 0.00 0.00
February 0.614793E+10 0.483728E+10 0.605241E+10 0.368880E+10 0.236360E+10 0.00 0.00
March 0.338514E+10 0.454200E+10 0.413581E+10 0.119553E+10 0.294029E+10 0.00 0.00
April 0.937870E+10 0.368281E+10 0.820468E+10 0.363550E+10 0.456918E+10 0.00 0.00
May 0.755101E+10 0.331063E+10 0.710749E+10 0.230242E+10 0.480506E+10 0.00 0.00
June 0.706057E+10 0.241756E+10 0.634930E+10 0.153557E+10 0.481373E+10 0.00 0.00
July 0.844241E+10 0.229525E+10 0.707196E+10 0.218787E+10 0.488409E+10 0.00 0.00
August 0.104133E+11 0.251100E+10 0.830611E+10 0.372154E+10 0.458457E+10 0.00 0.00
September 0.119065E+11 0.311623E+10 0.963282E+10 0.568537E+10 0.394745E+10 0.00 0.00
October 0.730790E+10 0.426665E+10 0.664185E+10 0.382922E+10 0.281264E+10 0.00 0.00
November 0.461037E+10 0.497624E+10 0.464162E+10 0.282267E+10 0.181896E+10 0.00 0.00
December 0.364183E+10 0.623443E+10 0.380613E+10 0.244060E+10 0.136553E+10 0.00 0.00
               
Annual Sum or Average 0.853071E+11 0.477285E+11 0.774723E+11 0.366210E+11 0.408513E+11 0.00 0.00
Minimum of Months 0.338514E+10 0.229525E+10 0.380613E+10 0.119553E+10 0.136553E+10 0.00 0.00
Maximum of Months 0.119065E+11 0.623443E+10 0.963282E+10 0.568537E+10 0.488409E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.398110E+09 0.786818E+09 0.494133E+09 0.257408E+09 0.236725E+09 0.00 0.00
February 0.574002E+09 0.690581E+09 0.639747E+09 0.332452E+09 0.307294E+09 0.00 0.00
March 0.390386E+09 0.622621E+09 0.534896E+09 0.124489E+09 0.410407E+09 0.00 0.00
April 0.124332E+10 0.497151E+09 0.115310E+10 0.477853E+09 0.675246E+09 0.00 0.00
May 0.129460E+10 0.436199E+09 0.124465E+10 0.474379E+09 0.770273E+09 0.00 0.00
June 0.138867E+10 0.311720E+09 0.124223E+10 0.453123E+09 0.789105E+09 0.00 0.00
July 0.156374E+10 0.290530E+09 0.132781E+10 0.534771E+09 0.793040E+09 0.00 0.00
August 0.150181E+10 0.317567E+09 0.124466E+10 0.545860E+09 0.698800E+09 0.00 0.00
September 0.134143E+10 0.411954E+09 0.114291E+10 0.588565E+09 0.554349E+09 0.00 0.00
October 0.699869E+09 0.577841E+09 0.701746E+09 0.331451E+09 0.370295E+09 0.00 0.00
November 0.353633E+09 0.688303E+09 0.429837E+09 0.205366E+09 0.224470E+09 0.00 0.00
December 0.217627E+09 0.889860E+09 0.308814E+09 0.152870E+09 0.155944E+09 0.00 0.00
               
Annual Sum or Average 0.109672E+11 0.652115E+10 0.104645E+11 0.447859E+10 0.598595E+10 0.00 0.00
Minimum of Months 0.217627E+09 0.290530E+09 0.308814E+09 0.124489E+09 0.155944E+09 0.00 0.00
Maximum of Months 0.156374E+10 0.889860E+09 0.132781E+10 0.588565E+09 0.793040E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.123960E+09 0.824221E+09 0.247957E+09 64128920.97 0.183828E+09 0.00 0.00
February 0.265651E+09 0.705487E+09 0.386375E+09 0.133073E+09 0.253301E+09 0.00 0.00
March 0.251489E+09 0.626498E+09 0.424373E+09 59871685.24 0.364501E+09 0.00 0.00
April 0.873905E+09 0.488838E+09 0.888354E+09 0.282543E+09 0.605811E+09 0.00 0.00
May 0.105902E+10 0.418930E+09 0.109138E+10 0.361707E+09 0.729674E+09 0.00 0.00
June 0.123031E+10 0.298213E+09 0.114520E+10 0.385523E+09 0.759681E+09 0.00 0.00
July 0.134287E+10 0.278248E+09 0.118742E+10 0.430741E+09 0.756678E+09 0.00 0.00
August 0.112616E+10 0.307327E+09 0.986127E+09 0.348272E+09 0.637855E+09 0.00 0.00
September 0.824509E+09 0.407672E+09 0.762029E+09 0.281355E+09 0.480675E+09 0.00 0.00
October 0.359176E+09 0.580605E+09 0.435230E+09 0.124483E+09 0.310747E+09 0.00 0.00
November 0.123679E+09 0.705947E+09 0.232729E+09 52801937.15 0.179927E+09 0.00 0.00
December 38301090.77 0.924381E+09 0.140932E+09 20956149.08 0.119976E+09 0.00 0.00
               
Annual Sum or Average 0.761904E+10 0.656637E+10 0.792811E+10 0.254546E+10 0.538265E+10 0.00 0.00
Minimum of Months 38301090.77 0.278248E+09 0.140932E+09 20956149.08 0.119976E+09 0.00 0.00
Maximum of Months 0.134287E+10 0.924381E+09 0.118742E+10 0.430741E+09 0.759681E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.238115E+09 0.217881E+09 0.238730E+09 0.154592E+09 84137898.18 0.00 0.00
February 0.267387E+09 0.192895E+09 0.261653E+09 0.159471E+09 0.102182E+09 0.00 0.00
March 0.155453E+09 0.165854E+09 0.178797E+09 51684172.32 0.127113E+09 0.00 0.00
April 0.400684E+09 0.155898E+09 0.354700E+09 0.157167E+09 0.197533E+09 0.00 0.00
May 0.320841E+09 0.140399E+09 0.307267E+09 99536592.27 0.207730E+09 0.00 0.00
June 0.299677E+09 0.102836E+09 0.274490E+09 66384623.48 0.208105E+09 0.00 0.00
July 0.360325E+09 97135144.51 0.305732E+09 94584426.86 0.211147E+09 0.00 0.00
August 0.446107E+09 0.105823E+09 0.359085E+09 0.160887E+09 0.198198E+09 0.00 0.00
September 0.509853E+09 0.133896E+09 0.416440E+09 0.245785E+09 0.170655E+09 0.00 0.00
October 0.315101E+09 0.173435E+09 0.287136E+09 0.165542E+09 0.121594E+09 0.00 0.00
November 0.201641E+09 0.191158E+09 0.200663E+09 0.122027E+09 78636007.32 0.00 0.00
December 0.162113E+09 0.231522E+09 0.164544E+09 0.105510E+09 59033741.75 0.00 0.00
               
Annual Sum or Average 0.367730E+10 0.190873E+10 0.334924E+10 0.158317E+10 0.176607E+10 0.00 0.00
Minimum of Months 0.155453E+09 97135144.51 0.164544E+09 51684172.32 59033741.75 0.00 0.00
Maximum of Months 0.509853E+09 0.231522E+09 0.416440E+09 0.245785E+09 0.211147E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 3931785.16 0.249568E+09 41842464.75 0.00 41842464.75 0.00 0.00
February 10606833.84 0.209993E+09 59015680.35 0.00 59015680.35 0.00 0.00
March 34948003.98 0.187369E+09 90426079.04 611.18 90425467.87 0.00 0.00
April 0.104958E+09 0.137786E+09 0.142993E+09 950366.37 0.142043E+09 0.00 0.00
May 0.137338E+09 0.113685E+09 0.184736E+09 9420490.59 0.175316E+09 0.00 0.00
June 0.185897E+09 79952757.98 0.196951E+09 12319448.80 0.184631E+09 0.00 0.00
July 0.196505E+09 73679290.55 0.193505E+09 11381086.97 0.182124E+09 0.00 0.00
August 0.153973E+09 81313166.67 0.152351E+09 2849117.93 0.149502E+09 0.00 0.00
September 98067685.16 0.113497E+09 0.111830E+09 66094.90 0.111764E+09 0.00 0.00
October 37209179.77 0.169892E+09 73990137.15 0.00 73990137.15 0.00 0.00
November 6174887.89 0.210466E+09 43022945.85 0.00 43022945.85 0.00 0.00
December 285269.90 0.274878E+09 30275127.60 0.00 30275127.60 0.00 0.00
               
Annual Sum or Average 0.969894E+09 0.190208E+10 0.132094E+10 36987216.73 0.128395E+10 0.00 0.00
Minimum of Months 285269.90 73679290.55 30275127.60 0.00 30275127.60 0.00 0.00
Maximum of Months 0.196505E+09 0.274878E+09 0.196951E+09 12319448.80 0.184631E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.398938E+09 0.782700E+09 0.496934E+09 0.272321E+09 0.224613E+09 0.00 0.00
February 0.506989E+09 0.680191E+09 0.597830E+09 0.300245E+09 0.297585E+09 0.00 0.00
March 0.386659E+09 0.618575E+09 0.534921E+09 0.126033E+09 0.408888E+09 0.00 0.00
April 0.134531E+10 0.477466E+09 0.125073E+10 0.574996E+09 0.675737E+09 0.00 0.00
May 0.129968E+10 0.422434E+09 0.126247E+10 0.507539E+09 0.754926E+09 0.00 0.00
June 0.130303E+10 0.301595E+09 0.118426E+10 0.418994E+09 0.765270E+09 0.00 0.00
July 0.147340E+10 0.280190E+09 0.126927E+10 0.495041E+09 0.774234E+09 0.00 0.00
August 0.155056E+10 0.303362E+09 0.129158E+10 0.604548E+09 0.687035E+09 0.00 0.00
September 0.146711E+10 0.398066E+09 0.125276E+10 0.696307E+09 0.556457E+09 0.00 0.00
October 0.726815E+09 0.572921E+09 0.726948E+09 0.360841E+09 0.366107E+09 0.00 0.00
November 0.355199E+09 0.682821E+09 0.435166E+09 0.215271E+09 0.219895E+09 0.00 0.00
December 0.263475E+09 0.884938E+09 0.347365E+09 0.184917E+09 0.162448E+09 0.00 0.00
               
Annual Sum or Average 0.110772E+11 0.640526E+10 0.106502E+11 0.475705E+10 0.589319E+10 0.00 0.00
Minimum of Months 0.263475E+09 0.280190E+09 0.347365E+09 0.126033E+09 0.162448E+09 0.00 0.00
Maximum of Months 0.155056E+10 0.884938E+09 0.129158E+10 0.696307E+09 0.774234E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.113163E+09 0.807667E+09 0.250758E+09 79042420.23 0.171716E+09 0.00 0.00
February 0.190454E+09 0.687153E+09 0.344458E+09 0.100866E+09 0.243592E+09 0.00 0.00
March 0.246026E+09 0.620780E+09 0.424398E+09 61415498.09 0.362983E+09 0.00 0.00
April 0.973431E+09 0.470061E+09 0.985989E+09 0.379686E+09 0.606302E+09 0.00 0.00
May 0.106528E+10 0.408565E+09 0.110919E+10 0.394867E+09 0.714327E+09 0.00 0.00
June 0.114787E+10 0.292899E+09 0.108724E+10 0.351394E+09 0.735845E+09 0.00 0.00
July 0.125424E+10 0.271622E+09 0.112888E+10 0.391012E+09 0.737872E+09 0.00 0.00
August 0.117501E+10 0.296895E+09 0.103305E+10 0.406961E+09 0.626091E+09 0.00 0.00
September 0.942375E+09 0.391538E+09 0.871879E+09 0.389097E+09 0.482782E+09 0.00 0.00
October 0.378613E+09 0.569100E+09 0.460432E+09 0.153873E+09 0.306559E+09 0.00 0.00
November 0.112924E+09 0.687431E+09 0.238058E+09 62706204.31 0.175352E+09 0.00 0.00
December 62053385.57 0.894995E+09 0.179483E+09 53003264.31 0.126480E+09 0.00 0.00
               
Annual Sum or Average 0.766144E+10 0.639871E+10 0.811382E+10 0.282392E+10 0.528990E+10 0.00 0.00
Minimum of Months 62053385.57 0.271622E+09 0.179483E+09 53003264.31 0.126480E+09 0.00 0.00
Maximum of Months 0.125424E+10 0.894995E+09 0.112888E+10 0.406961E+09 0.737872E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.479316E+09 0.100624E+10 0.607907E+09 0.334959E+09 0.272948E+09 0.00 0.00
February 0.581671E+09 0.878092E+09 0.694778E+09 0.345530E+09 0.349248E+09 0.00 0.00
March 0.392223E+09 0.807145E+09 0.583296E+09 0.111987E+09 0.471310E+09 0.00 0.00
April 0.110420E+10 0.643297E+09 0.107831E+10 0.342596E+09 0.735711E+09 0.00 0.00
May 0.982596E+09 0.555465E+09 0.106596E+10 0.236076E+09 0.829887E+09 0.00 0.00
June 0.103918E+10 0.403421E+09 0.102140E+10 0.170525E+09 0.850879E+09 0.00 0.00
July 0.118812E+10 0.382162E+09 0.108163E+10 0.229593E+09 0.852038E+09 0.00 0.00
August 0.128745E+10 0.429535E+09 0.110808E+10 0.354769E+09 0.753311E+09 0.00 0.00
September 0.131368E+10 0.557109E+09 0.114457E+10 0.532692E+09 0.611878E+09 0.00 0.00
October 0.759100E+09 0.752659E+09 0.782431E+09 0.358683E+09 0.423749E+09 0.00 0.00
November 0.428195E+09 0.885371E+09 0.527984E+09 0.264399E+09 0.263584E+09 0.00 0.00
December 0.310987E+09 0.115010E+10 0.422106E+09 0.228611E+09 0.193496E+09 0.00 0.00
               
Annual Sum or Average 0.986671E+10 0.845060E+10 0.101185E+11 0.351042E+10 0.660804E+10 0.00 0.00
Minimum of Months 0.310987E+09 0.382162E+09 0.422106E+09 0.111987E+09 0.193496E+09 0.00 0.00
Maximum of Months 0.131368E+10 0.115010E+10 0.114457E+10 0.532692E+09 0.852038E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.400796E+09 0.775404E+09 0.494133E+09 0.257408E+09 0.236725E+09 0.00 0.00
February 0.575107E+09 0.683446E+09 0.639747E+09 0.332452E+09 0.307294E+09 0.00 0.00
March 0.391936E+09 0.613692E+09 0.534896E+09 0.124489E+09 0.410407E+09 0.00 0.00
April 0.123498E+10 0.491968E+09 0.115310E+10 0.477853E+09 0.675246E+09 0.00 0.00
May 0.128456E+10 0.433114E+09 0.124465E+10 0.474379E+09 0.770273E+09 0.00 0.00
June 0.137676E+10 0.309307E+09 0.124223E+10 0.453123E+09 0.789105E+09 0.00 0.00
July 0.155149E+10 0.287859E+09 0.132781E+10 0.534771E+09 0.793040E+09 0.00 0.00
August 0.149181E+10 0.313025E+09 0.124466E+10 0.545860E+09 0.698800E+09 0.00 0.00
September 0.133568E+10 0.406147E+09 0.114291E+10 0.588565E+09 0.554349E+09 0.00 0.00
October 0.700212E+09 0.568449E+09 0.701746E+09 0.331451E+09 0.370295E+09 0.00 0.00
November 0.355504E+09 0.678525E+09 0.429837E+09 0.205366E+09 0.224470E+09 0.00 0.00
December 0.219326E+09 0.880760E+09 0.308814E+09 0.152870E+09 0.155944E+09 0.00 0.00
               
Annual Sum or Average 0.109182E+11 0.644169E+10 0.104645E+11 0.447859E+10 0.598595E+10 0.00 0.00
Minimum of Months 0.219326E+09 0.287859E+09 0.308814E+09 0.124489E+09 0.155944E+09 0.00 0.00
Maximum of Months 0.155149E+10 0.880760E+09 0.132781E+10 0.588565E+09 0.793040E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.126195E+09 0.811808E+09 0.247957E+09 64128920.97 0.183828E+09 0.00 0.00
February 0.267585E+09 0.696943E+09 0.386375E+09 0.133073E+09 0.253301E+09 0.00 0.00
March 0.253838E+09 0.617043E+09 0.424373E+09 59871685.24 0.364501E+09 0.00 0.00
April 0.867884E+09 0.482768E+09 0.888354E+09 0.282543E+09 0.605811E+09 0.00 0.00
May 0.105072E+10 0.415437E+09 0.109138E+10 0.361707E+09 0.729674E+09 0.00 0.00
June 0.121913E+10 0.295771E+09 0.114520E+10 0.385523E+09 0.759681E+09 0.00 0.00
July 0.133184E+10 0.275575E+09 0.118742E+10 0.430741E+09 0.756678E+09 0.00 0.00
August 0.111830E+10 0.302309E+09 0.986127E+09 0.348272E+09 0.637855E+09 0.00 0.00
September 0.822736E+09 0.400133E+09 0.762029E+09 0.281355E+09 0.480675E+09 0.00 0.00
October 0.361848E+09 0.569317E+09 0.435230E+09 0.124483E+09 0.310747E+09 0.00 0.00
November 0.126070E+09 0.695044E+09 0.232729E+09 52801937.15 0.179927E+09 0.00 0.00
December 39126785.32 0.914343E+09 0.140932E+09 20956149.08 0.119976E+09 0.00 0.00
               
Annual Sum or Average 0.758527E+10 0.647649E+10 0.792811E+10 0.254546E+10 0.538265E+10 0.00 0.00
Minimum of Months 39126785.32 0.275575E+09 0.140932E+09 20956149.08 0.119976E+09 0.00 0.00
Maximum of Months 0.133184E+10 0.914343E+09 0.118742E+10 0.430741E+09 0.759681E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.429839E+09 0.406238E+09 0.437738E+09 0.283462E+09 0.154276E+09 0.00 0.00
February 0.483072E+09 0.358087E+09 0.479770E+09 0.292408E+09 0.187362E+09 0.00 0.00
March 0.270387E+09 0.325682E+09 0.327844E+09 94768591.74 0.233075E+09 0.00 0.00
April 0.735257E+09 0.262087E+09 0.650381E+09 0.288183E+09 0.362198E+09 0.00 0.00
May 0.592708E+09 0.232678E+09 0.563408E+09 0.182511E+09 0.380897E+09 0.00 0.00
June 0.558577E+09 0.162014E+09 0.503307E+09 0.121723E+09 0.381584E+09 0.00 0.00
July 0.669709E+09 0.150418E+09 0.560592E+09 0.173431E+09 0.387162E+09 0.00 0.00
August 0.823969E+09 0.163154E+09 0.658421E+09 0.295003E+09 0.363418E+09 0.00 0.00
September 0.938232E+09 0.213522E+09 0.763588E+09 0.450674E+09 0.312914E+09 0.00 0.00
October 0.576397E+09 0.300886E+09 0.526495E+09 0.303539E+09 0.222957E+09 0.00 0.00
November 0.363056E+09 0.358552E+09 0.367938E+09 0.223750E+09 0.144188E+09 0.00 0.00
December 0.287206E+09 0.462249E+09 0.301709E+09 0.193464E+09 0.108245E+09 0.00 0.00
               
Annual Sum or Average 0.672841E+10 0.339557E+10 0.614119E+10 0.290292E+10 0.323827E+10 0.00 0.00
Minimum of Months 0.270387E+09 0.150418E+09 0.301709E+09 94768591.74 0.108245E+09 0.00 0.00
Maximum of Months 0.938232E+09 0.462249E+09 0.763588E+09 0.450674E+09 0.387162E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 12861327.64 0.254879E+10 0.366059E+09 0.00 0.366059E+09 0.00 0.00
February 41955169.79 0.216012E+10 0.516299E+09 0.00 0.516299E+09 0.00 0.00
March 0.211904E+09 0.193297E+10 0.791093E+09 5346.90 0.791088E+09 0.00 0.00
April 0.751512E+09 0.142562E+10 0.125098E+10 8314288.68 0.124266E+10 0.00 0.00
May 0.975180E+09 0.120463E+10 0.161617E+10 82415246.22 0.153375E+10 0.00 0.00
June 0.139424E+10 0.875408E+09 0.172303E+10 0.107777E+09 0.161525E+10 0.00 0.00
July 0.147655E+10 0.820267E+09 0.169288E+10 99567541.14 0.159331E+10 0.00 0.00
August 0.113667E+10 0.913891E+09 0.133284E+10 24925533.69 0.130792E+10 0.00 0.00
September 0.699218E+09 0.122928E+10 0.978343E+09 578231.83 0.977764E+09 0.00 0.00
October 0.230006E+09 0.179629E+10 0.647303E+09 0.00 0.647303E+09 0.00 0.00
November 22484246.69 0.221059E+10 0.376387E+09 0.00 0.376387E+09 0.00 0.00
December 0.00 0.282560E+10 0.264862E+09 0.00 0.264862E+09 0.00 0.00
               
Annual Sum or Average 0.695258E+10 0.199435E+11 0.115562E+11 0.323583E+09 0.112327E+11 0.00 0.00
Minimum of Months 0.00 0.820267E+09 0.264862E+09 0.00 0.264862E+09 0.00 0.00
Maximum of Months 0.147655E+10 0.282560E+10 0.172303E+10 0.107777E+09 0.161525E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 9427335.86 0.262722E+10 0.366059E+09 0.00 0.366059E+09 0.00 0.00
February 33701779.66 0.222583E+10 0.516299E+09 0.00 0.516299E+09 0.00 0.00
March 0.190840E+09 0.198936E+10 0.791093E+09 5346.90 0.791088E+09 0.00 0.00
April 0.723466E+09 0.145726E+10 0.125098E+10 8314288.68 0.124266E+10 0.00 0.00
May 0.940664E+09 0.123040E+10 0.161617E+10 82415246.22 0.153375E+10 0.00 0.00
June 0.136375E+10 0.893670E+09 0.172303E+10 0.107777E+09 0.161525E+10 0.00 0.00
July 0.144758E+10 0.837262E+09 0.169288E+10 99567541.14 0.159331E+10 0.00 0.00
August 0.111057E+10 0.934428E+09 0.133284E+10 24925533.69 0.130792E+10 0.00 0.00
September 0.675296E+09 0.125715E+10 0.978343E+09 578231.83 0.977764E+09 0.00 0.00
October 0.210451E+09 0.184912E+10 0.647303E+09 0.00 0.647303E+09 0.00 0.00
November 16944439.92 0.228441E+10 0.376387E+09 0.00 0.376387E+09 0.00 0.00
December 0.00 0.291239E+10 0.264862E+09 0.00 0.264862E+09 0.00 0.00
               
Annual Sum or Average 0.672269E+10 0.204985E+11 0.115562E+11 0.323583E+09 0.112327E+11 0.00 0.00
Minimum of Months 0.00 0.837262E+09 0.264862E+09 0.00 0.264862E+09 0.00 0.00
Maximum of Months 0.144758E+10 0.291239E+10 0.172303E+10 0.107777E+09 0.161525E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.542934E+09 0.159420E+10 0.747665E+09 0.351352E+09 0.396312E+09 0.00 0.00
February 0.745848E+09 0.140827E+10 0.942249E+09 0.401097E+09 0.541152E+09 0.00 0.00
March 0.717266E+09 0.128922E+10 0.959275E+09 0.187440E+09 0.771835E+09 0.00 0.00
April 0.255173E+10 0.100625E+10 0.223661E+10 0.954629E+09 0.128198E+10 0.00 0.00
May 0.258855E+10 0.938176E+09 0.237153E+10 0.902352E+09 0.146918E+10 0.00 0.00
June 0.271702E+10 0.689865E+09 0.227138E+10 0.770339E+09 0.150104E+10 0.00 0.00
July 0.302986E+10 0.651528E+09 0.239803E+10 0.885999E+09 0.151203E+10 0.00 0.00
August 0.302450E+10 0.683718E+09 0.232452E+10 0.101145E+10 0.131306E+10 0.00 0.00
September 0.265716E+10 0.843919E+09 0.212454E+10 0.108535E+10 0.103919E+10 0.00 0.00
October 0.122594E+10 0.120440E+10 0.118733E+10 0.514692E+09 0.672635E+09 0.00 0.00
November 0.506773E+09 0.143116E+10 0.673197E+09 0.277968E+09 0.395230E+09 0.00 0.00
December 0.343429E+09 0.185628E+10 0.526828E+09 0.237913E+09 0.288915E+09 0.00 0.00
               
Annual Sum or Average 0.206510E+11 0.135970E+11 0.187632E+11 0.758058E+10 0.111826E+11 0.00 0.00
Minimum of Months 0.343429E+09 0.651528E+09 0.526828E+09 0.187440E+09 0.288915E+09 0.00 0.00
Maximum of Months 0.302986E+10 0.185628E+10 0.239803E+10 0.108535E+10 0.151203E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.104182E+10 0.178980E+10 0.123977E+10 0.721568E+09 0.518204E+09 0.00 0.00
February 0.122939E+10 0.156805E+10 0.139827E+10 0.744341E+09 0.653928E+09 0.00 0.00
March 0.766740E+09 0.144412E+10 0.110573E+10 0.241240E+09 0.864492E+09 0.00 0.00
April 0.216804E+10 0.114278E+10 0.208442E+10 0.736435E+09 0.134798E+10 0.00 0.00
May 0.185957E+10 0.996000E+09 0.198821E+10 0.492844E+09 0.149537E+10 0.00 0.00
June 0.189465E+10 0.728320E+09 0.187185E+10 0.346800E+09 0.152505E+10 0.00 0.00
July 0.219650E+10 0.692626E+09 0.200734E+10 0.475610E+09 0.153173E+10 0.00 0.00
August 0.248998E+10 0.768498E+09 0.213295E+10 0.759491E+09 0.137346E+10 0.00 0.00
September 0.265057E+10 0.975607E+09 0.227913E+10 0.114741E+10 0.113172E+10 0.00 0.00
October 0.156341E+10 0.133158E+10 0.156212E+10 0.772674E+09 0.789445E+09 0.00 0.00
November 0.911493E+09 0.158839E+10 0.106563E+10 0.569569E+09 0.496064E+09 0.00 0.00
December 0.682059E+09 0.206132E+10 0.858811E+09 0.492473E+09 0.366338E+09 0.00 0.00
               
Annual Sum or Average 0.194542E+11 0.150871E+11 0.195942E+11 0.750046E+10 0.120938E+11 0.00 0.00
Minimum of Months 0.682059E+09 0.692626E+09 0.858811E+09 0.241240E+09 0.366338E+09 0.00 0.00
Maximum of Months 0.265057E+10 0.206132E+10 0.227913E+10 0.114741E+10 0.153173E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 4.18 3.23 2.03 1.05 -4.0 28.28 62.93 0.00
February 4.25 3.55 2.74 1.60 -5.0 43.80 86.73 0.02
March 5.90 4.45 2.76 1.18 -1.9 68.95 35.00 0.00
April 8.96 6.24 3.38 1.56 -0.7 96.13 186.12 0.00
May 9.99 8.07 6.28 3.35 -0.9 110.92 199.68 0.02
June 13.31 11.27 9.70 3.33 3.35 121.69 199.28 0.00
July 15.02 12.39 10.49 3.21 4.49 111.91 220.83 0.00
August 15.65 12.75 10.65 2.92 3.95 91.47 211.91 0.00
September 13.43 11.01 9.10 2.64 1.43 68.72 198.32 0.01
October 9.33 8.03 6.81 1.97 -1.0 48.92 91.86 0.04
November 6.66 5.66 4.54 2.05 -2.3 30.27 53.24 0.04
December 4.10 3.14 1.95 2.36 -5.1 20.52 40.74 0.04
                 
Annual Sum or Average 9.26 7.50 5.89 2.27 -0.6 70.25 132.30 0.02
Minimum of Months 4.10 3.14 1.95 1.05 -5.1 20.52 35.00 0.00
Maximum of Months 15.65 12.75 10.65 3.35 4.49 121.69 220.83 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.00 29-JAN-05:00 9.37 5.00 3.60 8.35 0.00 0.00
February 11.00 07-FEB-14:00 9.86 9.00 2.10 6.35 138.00 225.00
March 14.00 25-MAR-12:00 11.22 9.00 2.60 7.35 287.00 93.00
April 24.00 30-APR-14:00 13.13 4.00 1.50 7.75 167.50 716.00
May 24.00 22-MAY-14:00 16.08 11.00 2.60 9.33 159.00 769.00
June 27.00 13-JUN-16:00 17.53 12.00 3.10 12.41 141.50 652.50
July 30.00 22-JUL-17:00 16.80 8.00 0.00 14.28 122.00 407.00
August 27.00 14-AUG-17:19 14.18 3.33 2.60 10.37 133.00 358.83
September 23.00 11-SEP-16:00 16.22 12.00 2.60 8.74 108.00 325.50
October 19.00 07-OCT-14:00 10.10 1.00 1.50 2.22 131.00 540.50
November 16.00 24-NOV-11:00 12.01 9.00 4.10 9.33 61.50 0.00
December 13.00 23-DEC-10:00 7.64 2.00 7.70 6.75 70.50 0.00
                 
Annual Sum or Average                
Minimum of Months 11.00   7.64 1.00 0.00 2.22 0.00 0.00
Maximum of Months 30.00   17.53 12.00 7.70 14.28 287.00 769.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -6.0 10-JAN-07:00 -7.0 -9.0 0.00 -20.0 0.00 0.00
February -4.0 17-FEB-06:00 -4.0 -4.0 0.00 -20.5 0.00 0.00
March -1.0 08-MAR-06:00 -1.4 -2.0 0.00 -14.4 17.50 184.50
April 0.00 08-APR-04:00 -0.9 -2.0 0.00 -12.7 0.00 0.00
May 2.00 06-MAY-04:00 1.57 1.00 3.60 -13.7 12.50 117.00
June 6.00 01-JUN-03:00 5.05 4.00 0.00 -9.2 0.00 0.00
July 7.00 05-JUL-04:00 6.47 6.00 3.10 -7.8 28.00 155.00
August 8.00 20-AUG-04:00 7.45 7.00 0.00 -6.6 0.00 0.00
September 5.00 20-SEP-03:00 5.00 5.00 2.60 -10.0 0.00 0.00
October 2.00 07-OCT-03:00 2.00 2.00 0.00 -13.4 0.00 0.00
November -2.0 29-NOV-01:00 -2.0 -2.0 3.10 -10.7 0.00 0.00
December -3.0 29-DEC-20:00 -4.5 -7.0 3.60 -20.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -6.0   -7.0 -9.0 0.00 -20.5 0.00 0.00
Maximum of Months 8.00   7.45 7.00 3.60 -6.6 28.00 184.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 12.44 29-JAN-04:00 13.00 12.00 0.00 9.13 0.00 0.00
February 9.86 07-FEB-14:00 11.00 9.00 2.10 6.35 138.00 225.00
March 12.00 19-MAR-11:00 12.00 12.00 2.60 8.15 131.00 0.00
April 15.39 28-APR-07:00 16.00 15.00 0.00 5.54 119.50 626.00
May 16.08 22-MAY-14:00 24.00 11.00 2.60 9.33 159.00 769.00
June 19.93 25-JUN-17:00 22.00 19.00 0.00 15.94 136.50 360.50
July 17.31 22-JUL-09:00 26.00 12.00 4.60 11.46 224.50 619.50
August 17.06 14-AUG-12:00 24.00 13.00 2.60 9.91 205.50 669.50
September 16.54 10-SEP-15:00 21.00 14.00 3.60 8.54 160.50 483.00
October 13.58 17-OCT-14:00 16.00 12.00 0.00 12.03 144.00 44.50
November 12.01 24-NOV-11:00 16.00 9.00 4.10 9.33 61.50 0.00
December 7.93 02-DEC-12:00 9.00 7.00 0.00 2.01 135.50 84.00
                 
Annual Sum or Average                
Minimum of Months 7.93   9.00 7.00 0.00 2.01 0.00 0.00
Maximum of Months 19.93   26.00 19.00 4.60 15.94 224.50 769.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 12.00 29-JAN-04:00 13.00 12.44 0.00 9.13 0.00 0.00
February 9.00 07-FEB-14:00 11.00 9.86 2.10 6.35 138.00 225.00
March 12.00 19-MAR-11:00 12.00 12.00 2.60 8.15 131.00 0.00
April 15.00 28-APR-07:00 16.00 15.39 0.00 5.54 119.50 626.00
May 12.00 23-MAY-07:00 17.00 13.95 3.10 5.13 112.00 719.50
June 19.00 25-JUN-17:00 22.00 19.93 0.00 15.94 136.50 360.50
July 14.00 17-JUL-17:00 18.00 15.45 3.60 9.91 120.00 0.00
August 16.00 08-AUG-12:00 18.00 16.70 1.50 11.46 154.00 0.00
September 14.00 10-SEP-15:00 21.00 16.54 3.60 8.54 160.50 483.00
October 13.00 17-OCT-18:00 13.00 13.00 2.60 9.33 0.00 0.00
November 12.00 08-NOV-14:00 12.00 12.00 0.00 8.15 93.00 106.00
December 7.00 02-DEC-11:00 8.00 7.45 3.10 1.16 144.50 146.50
                 
Annual Sum or Average                
Minimum of Months 7.00   8.00 7.45 0.00 1.16 0.00 0.00
Maximum of Months 19.00   22.00 19.93 3.60 15.94 160.50 719.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 10.33 8.85 0.00
February 18.00 13.00 16.00 10.00 14.79 0.00
March 18.00 13.00 16.00 10.33 17.09 0.00
April 18.00 13.00 16.00 11.26 40.86 0.00
May 18.00 13.00 16.00 12.54 47.73 0.00
June 18.00 13.00 16.00 13.82 50.98 0.00
July 18.00 13.00 16.00 14.77 51.67 0.00
August 18.00 13.00 16.00 15.12 44.67 0.00
September 18.00 13.00 16.00 14.78 34.25 0.00
October 18.00 13.00 16.00 13.84 17.71 0.00
November 18.00 13.00 16.00 12.55 9.34 0.00
December 18.00 13.00 16.00 11.27 6.14 0.00
             
Annual Sum or Average 18.00 13.00 16.00 12.57 28.73 0.00
Minimum of Months 18.00 13.00 16.00 10.00 6.14 0.00
Maximum of Months 18.00 13.00 16.00 15.12 51.67 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770462E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -161834963.7 81.21 0.00 0.00
February 0.696210E+10 -0.681598E+10 0.00 0.00 672.00 0.00 -146119057.1 81.21 0.00 0.00
March 0.770302E+10 -0.754147E+10 0.00 0.00 744.00 0.00 -161556883.9 81.21 0.00 0.00
April 0.746487E+10 -0.730858E+10 0.00 0.00 720.00 0.00 -156290831.0 81.21 0.00 0.00
May 0.770418E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -161389676.0 81.21 0.00 0.00
June 0.745699E+10 -0.730053E+10 0.00 0.00 720.00 0.00 -156462129.5 81.21 0.00 0.00
July 0.771251E+10 -0.755084E+10 0.00 0.00 744.00 0.00 -161672981.5 81.21 0.00 0.00
August 0.770447E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -161680911.1 81.21 0.00 0.00
September 0.746644E+10 -0.730994E+10 0.00 0.00 720.00 0.00 -156502756.7 81.21 0.00 0.00
October 0.770292E+10 -0.754144E+10 0.00 0.00 744.00 0.00 -161475695.9 81.21 0.00 0.00
November 0.744874E+10 -0.729243E+10 0.00 0.00 720.00 0.00 -156315230.2 81.21 0.00 0.00
December 0.771275E+10 -0.755086E+10 0.00 0.00 744.00 0.00 -161882399.5 81.21 0.00 0.00
                     
Annual Sum or Average 0.907436E+11 -0.888404E+11 0.00 0.00 8760.00 0.00 -0.190318E+10 81.21 0.00 0.00
Minimum of Months 0.696210E+10 -0.755086E+10 0.00 0.00 672.00 0.00 -161882399.5 81.21 0.00 0.00
Maximum of Months 0.771275E+10 -0.681598E+10 0.00 0.00 744.00 0.00 -146119057.1 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.121892E+12 -0.120147E+12 0.00 0.00 744.00 0.00 -0.174457E+10 81.27 0.00 0.00
February 0.110615E+12 -0.109036E+12 0.00 0.00 672.00 0.00 -0.157918E+10 81.27 0.00 0.00
March 0.121893E+12 -0.120139E+12 0.00 0.00 744.00 0.00 -0.175477E+10 81.27 0.00 0.00
April 0.116425E+12 -0.114726E+12 0.00 0.00 720.00 0.00 -0.169872E+10 81.27 0.00 0.00
May 0.118119E+12 -0.116364E+12 0.00 0.00 744.00 0.00 -0.175480E+10 81.26 0.00 0.00
June 0.112186E+12 -0.110489E+12 0.00 0.00 720.00 0.00 -0.169718E+10 81.26 0.00 0.00
July 0.114308E+12 -0.112561E+12 0.00 0.00 744.00 0.00 -0.174725E+10 81.26 0.00 0.00
August 0.113701E+12 -0.111957E+12 0.00 0.00 744.00 0.00 -0.174387E+10 81.26 0.00 0.00
September 0.110595E+12 -0.108913E+12 0.00 0.00 720.00 0.00 -0.168128E+10 81.25 0.00 0.00
October 0.115884E+12 -0.114150E+12 0.00 0.00 744.00 0.00 -0.173450E+10 81.26 0.00 0.00
November 0.114261E+12 -0.112583E+12 0.00 0.00 720.00 0.00 -0.167770E+10 81.26 0.00 0.00
December 0.120261E+12 -0.118524E+12 0.00 0.00 744.00 0.00 -0.173726E+10 81.26 0.00 0.00
                     
Annual Sum or Average 0.139014E+13 -0.136959E+13 0.00 0.00 8760.00 0.00 -0.205511E+11 81.26 0.00 0.00
Minimum of Months 0.110595E+12 -0.120147E+12 0.00 0.00 672.00 0.00 -0.175480E+10 81.25 0.00 0.00
Maximum of Months 0.121893E+12 -0.108913E+12 0.00 0.00 744.00 0.00 -0.157918E+10 81.27 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.725789E+11 -0.710917E+11 0.00 0.00 744.00 0.00 -0.148717E+10 58.98 0.00 0.00
February 0.660063E+11 -0.646584E+11 0.00 0.00 672.00 0.00 -0.134795E+10 58.98 0.00 0.00
March 0.726523E+11 -0.711510E+11 0.00 0.00 744.00 0.00 -0.150131E+10 58.99 0.00 0.00
April 0.689611E+11 -0.675073E+11 0.00 0.00 720.00 0.00 -0.145379E+10 58.99 0.00 0.00
May 0.694009E+11 -0.678990E+11 0.00 0.00 744.00 0.00 -0.150183E+10 58.99 0.00 0.00
June 0.653640E+11 -0.639119E+11 0.00 0.00 720.00 0.00 -0.145204E+10 58.98 0.00 0.00
July 0.660871E+11 -0.645957E+11 0.00 0.00 744.00 0.00 -0.149143E+10 58.98 0.00 0.00
August 0.656305E+11 -0.641439E+11 0.00 0.00 744.00 0.00 -0.148668E+10 58.98 0.00 0.00
September 0.639588E+11 -0.625287E+11 0.00 0.00 720.00 0.00 -0.143019E+10 58.98 0.00 0.00
October 0.674337E+11 -0.659599E+11 0.00 0.00 744.00 0.00 -0.147386E+10 58.98 0.00 0.00
November 0.670745E+11 -0.656494E+11 0.00 0.00 720.00 0.00 -0.142503E+10 58.99 0.00 0.00
December 0.711843E+11 -0.697070E+11 0.00 0.00 744.00 0.00 -0.147729E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.816332E+12 -0.798804E+12 0.00 0.00 8760.00 0.00 -0.175286E+11 58.98 0.00 0.00
Minimum of Months 0.639588E+11 -0.711510E+11 0.00 0.00 672.00 0.00 -0.150183E+10 58.98 0.00 0.00
Maximum of Months 0.726523E+11 -0.625287E+11 0.00 0.00 744.00 0.00 -0.134795E+10 58.99 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.93 0.93 01-JAN-08:39 3225.62 36.41 191.50 225.50 2598.93 37.36 192.00 182.83
February 217.00 0.93 0.93 01-FEB-11:39 4744.82 35.75 211.67 246.83 2080.91 31.79 192.50 208.83
March 215.50 0.93 0.93 01-MAR-11:39 3076.77 29.45 160.00 311.33 639.07 21.51 132.17 247.50
April 359.67 0.93 0.93 01-APR-06:49 1786.20 20.74 173.67 358.67 704.23 22.46 276.17 313.00
May 417.17 0.93 0.93 01-MAY-06:40 1432.98 20.25 129.50 412.00 563.64 21.96 289.17 345.00
June 410.67 0.93 0.93 01-JUN-05:30 1404.15 20.47 120.17 413.67 550.10 22.17 292.17 350.17
July 429.00 0.93 0.93 01-JUL-05:30 1372.59 20.33 127.83 422.00 547.81 22.04 306.33 360.00
August 396.33 0.93 0.93 01-AUG-05:49 1562.60 20.44 157.50 383.17 627.25 22.17 294.83 328.33
September 337.67 0.93 0.93 01-SEP-07:40 5376.00 27.11 206.67 331.17 752.33 22.59 262.50 286.83
October 234.00 0.93 0.93 01-OCT-06:49 6050.81 35.01 217.00 281.17 1048.48 25.26 189.50 227.83
November 171.33 0.93 0.93 01-NOV-11:39 3760.82 36.13 167.17 219.00 2744.92 36.38 165.33 161.50
December 131.67 0.93 0.93 02-DEC-08:39 3094.07 37.20 128.50 183.67 2489.22 38.15 128.67 122.33
                         
Annual Sum or Average 3515.67 0.93     2739.67 25.83 1991.17 3788.17 1022.04 25.09 2721.33 3134.17
Minimum of Months 131.67 0.93 0.93   1372.59 20.25 120.17 183.67 547.81 21.51 128.67 122.33
Maximum of Months 429.00 0.93 0.93   6050.81 37.20 217.00 422.00 2744.92 38.15 306.33 360.00



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.63 0.61 01-JAN-08:30 3543.39 36.48 191.67 234.50 2916.19 37.41 192.00 210.00
February 217.00 0.62 0.61 01-FEB-11:39 5106.16 35.83 212.00 254.17 2438.35 31.82 199.17 233.67
March 215.50 0.63 0.61 01-MAR-11:39 3315.46 29.73 160.17 323.83 876.88 21.97 173.50 286.50
April 359.67 0.63 0.61 01-APR-06:40 2126.33 21.03 175.33 367.17 1043.30 22.60 292.33 343.67
May 417.17 0.62 0.61 01-MAY-06:40 1693.99 20.74 161.00 424.00 823.74 22.27 320.17 391.83
June 410.67 0.62 0.61 01-JUN-05:10 1646.22 21.00 167.83 427.00 791.30 22.53 320.50 388.83
July 429.00 0.62 0.61 01-JUL-05:10 1627.51 20.81 172.67 435.67 801.88 22.35 336.33 401.67
August 396.33 0.63 0.61 01-AUG-05:40 1878.22 20.78 162.67 394.00 941.91 22.35 312.00 363.50
September 337.67 0.63 0.61 01-SEP-07:40 5783.64 27.36 204.33 339.67 1159.03 22.59 265.83 315.83
October 234.00 0.62 0.61 01-OCT-06:49 6431.97 35.15 217.00 290.50 1429.56 25.32 204.17 262.17
November 171.33 0.62 0.61 01-NOV-11:39 4087.82 36.20 167.33 232.00 3071.19 36.43 166.17 190.50
December 131.67 0.63 0.61 02-DEC-08:30 3412.97 37.27 128.50 197.00 2806.86 38.21 128.67 152.00
                         
Annual Sum or Average 3515.67 0.62     3047.42 26.14 2120.50 3919.50 1328.76 25.29 2910.83 3540.17
Minimum of Months 131.67 0.62 0.61   1627.51 20.74 128.50 197.00 791.30 21.97 128.67 152.00
Maximum of Months 429.00 0.63 0.61   6431.97 37.27 217.00 435.67 3071.19 38.21 336.33 401.67



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.83 0.80 01-JAN-09:20 352.90 13.97 0.00 204.17 164.22 17.38 0.00 49.67
February 217.00 0.82 0.80 01-FEB-11:39 460.13 15.51 0.00 235.67 212.90 18.81 0.00 128.33
March 215.50 0.81 0.80 01-MAR-11:39 589.73 16.06 0.00 312.67 246.62 19.16 1.67 201.50
April 359.67 0.81 0.80 01-APR-06:49 739.07 18.01 0.00 367.33 341.55 21.20 123.67 328.83
May 417.17 0.80 0.80 01-MAY-06:40 896.34 19.46 29.83 431.83 406.56 23.40 249.17 403.83
June 410.67 0.80 0.80 01-JUN-04:00 1024.70 20.39 49.50 435.50 467.63 23.86 270.00 406.00
July 429.00 0.80 0.80 01-JUL-04:49 943.01 20.53 61.33 445.00 437.66 23.51 272.50 417.00
August 396.33 0.81 0.80 01-AUG-05:19 743.59 18.29 6.67 398.33 350.97 21.49 163.67 361.17
September 337.67 0.81 0.80 01-SEP-07:40 581.34 17.20 0.00 332.67 287.85 20.46 22.33 278.00
October 234.00 0.81 0.80 01-OCT-07:10 510.88 16.17 0.00 272.50 241.26 19.44 0.00 168.67
November 171.33 0.82 0.80 01-NOV-11:39 387.14 14.61 0.00 201.17 180.70 17.96 0.00 67.17
December 131.67 0.83 0.80 02-DEC-08:00 325.97 13.80 0.00 161.50 155.02 17.25 0.00 26.83
                         
Annual Sum or Average 3515.67 0.81     705.67 17.78 147.33 3798.33 326.50 21.11 1103.00 2837.00
Minimum of Months 131.67 0.80 0.80   325.97 13.80 0.00 161.50 155.02 17.25 0.00 26.83
Maximum of Months 429.00 0.83 0.80   1024.70 20.53 61.33 445.00 467.63 23.86 272.50 417.00



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.83 0.80 01-JAN-09:20 352.90 13.97 0.00 204.17 164.22 17.38 0.00 49.67
February 217.00 0.82 0.80 01-FEB-11:39 460.13 15.51 0.00 235.67 212.90 18.81 0.00 128.33
March 215.50 0.81 0.80 01-MAR-11:39 589.73 16.06 0.00 312.67 246.62 19.16 1.67 201.50
April 359.67 0.81 0.80 01-APR-06:49 739.07 18.01 0.00 367.33 341.55 21.20 123.67 328.83
May 417.17 0.80 0.80 01-MAY-06:40 896.34 19.46 29.83 431.83 406.56 23.40 249.17 403.83
June 410.67 0.80 0.80 01-JUN-04:00 1024.70 20.39 49.50 435.50 467.63 23.86 270.00 406.00
July 429.00 0.80 0.80 01-JUL-04:49 943.01 20.53 61.33 445.00 437.66 23.51 272.50 417.00
August 396.33 0.81 0.80 01-AUG-05:19 743.59 18.29 6.67 398.33 350.97 21.49 163.67 361.17
September 337.67 0.81 0.80 01-SEP-07:40 581.34 17.20 0.00 332.67 287.85 20.46 22.33 278.00
October 234.00 0.81 0.80 01-OCT-07:10 510.88 16.17 0.00 272.50 241.26 19.44 0.00 168.67
November 171.33 0.82 0.80 01-NOV-11:39 387.14 14.61 0.00 201.17 180.70 17.96 0.00 67.17
December 131.67 0.83 0.80 02-DEC-08:00 325.97 13.80 0.00 161.50 155.02 17.25 0.00 26.83
                         
Annual Sum or Average 3515.67 0.81     705.67 17.78 147.33 3798.33 326.50 21.11 1103.00 2837.00
Minimum of Months 131.67 0.80 0.80   325.97 13.80 0.00 161.50 155.02 17.25 0.00 26.83
Maximum of Months 429.00 0.83 0.80   1024.70 20.53 61.33 445.00 467.63 23.86 272.50 417.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.230017E+11 128130.91 19-JAN-08:17 0.00 0.00 0.00 0.00 0.00
February 0.165884E+11 128572.54 08-FEB-07:47 0.00 0.00 0.00 0.00 0.00
March 0.253596E+11 128266.63 30-MAR-07:17 0.00 0.00 0.00 0.00 0.00
April 0.237419E+11 152499.97 07-APR-20:10 0.00 0.00 0.00 0.00 0.00
May 0.335609E+11 127876.65 06-MAY-22:25 0.00 0.00 0.00 0.00 0.00
June 0.168632E+11 121920.67 08-JUN-05:57 0.00 0.00 0.00 0.00 0.00
July 0.102801E+11 111490.46 31-JUL-04:42 0.00 0.00 0.00 0.00 0.00
August 0.676575E+10 100674.23 20-AUG-05:55 0.00 0.00 0.00 0.00 0.00
September 0.162099E+11 128552.60 21-SEP-06:16 0.00 0.00 0.00 0.00 0.00
October 0.364206E+11 125855.20 18-OCT-22:13 0.00 0.00 0.00 0.00 0.00
November 0.352362E+11 130065.21 11-NOV-08:55 0.00 0.00 0.00 0.00 0.00
December 0.168561E+11 122098.61 06-DEC-14:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.260884E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.676575E+10 100674.23   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.364206E+11 152499.97   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.307585E+10 3548.18 28-JAN-08:05 0.00 0.00 0.00 0.00 0.00
February 0.241417E+10 3094.11 01-FEB-18:50 0.00 0.00 0.00 0.00 0.00
March 0.284051E+10 2990.05 09-MAR-07:14 0.00 0.00 0.00 0.00 0.00
April 0.102281E+10 2951.41 06-APR-08:35 0.00 0.00 0.00 0.00 0.00
May 0.100962E+10 2986.04 14-MAY-05:25 0.00 0.00 0.00 0.00 0.00
June 0.534001E+09 2650.43 06-JUN-03:35 0.00 0.00 0.00 0.00 0.00
July 0.371134E+09 2746.14 02-JUL-04:17 0.00 0.00 0.00 0.00 0.00
August 0.233994E+09 2197.27 28-AUG-03:46 0.00 0.00 0.00 0.00 0.00
September 0.430871E+09 2702.50 04-SEP-05:17 0.00 0.00 0.00 0.00 0.00
October 0.175507E+10 3191.04 31-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 0.264054E+10 3051.28 21-NOV-16:06 0.00 0.00 0.00 0.00 0.00
December 0.376879E+10 3309.74 04-DEC-08:44 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.200974E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.233994E+09 2197.27   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.376879E+10 3548.18   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 24363533.52 581.32 13-JAN-13:31 0.00 0.00 0.00 0.00 0.00
February 6732318.58 438.68 26-FEB-15:50 0.00 0.00 0.00 0.00 0.00
March 4793460.36 397.55 05-MAR-15:13 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 231446.63 140.70 27-OCT-13:25 0.00 0.00 0.00 0.00 0.00
November 7745594.33 303.87 23-NOV-15:37 0.00 0.00 0.00 0.00 0.00
December 57136493.53 449.64 11-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.101003E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 57136493.53 581.32   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.454882E+09 982.71 13-JAN-13:31 0.00 0.00 0.00 0.00 0.00
February 0.296987E+09 1466.14 17-FEB-14:09 0.00 0.00 0.00 0.00 0.00
March 0.160829E+09 800.22 05-MAR-13:39 0.00 0.00 0.00 0.00 0.00
April 306002.72 256.43 01-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 1459342.95 214.41 28-OCT-16:15 0.00 0.00 0.00 0.00 0.00
November 0.142540E+09 897.12 17-NOV-16:38 0.00 0.00 0.00 0.00 0.00
December 0.614245E+09 937.57 19-DEC-17:35 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.167125E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.614245E+09 1466.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.472881E+09 810.34 28-JAN-08:05 0.00 0.00 0.00 0.00 0.00
February 0.346708E+09 553.44 17-FEB-14:09 0.00 0.00 0.00 0.00 0.00
March 0.241022E+09 529.91 05-MAR-18:42 0.00 0.00 0.00 0.00 0.00
April 3102769.18 218.99 01-APR-10:45 0.00 0.00 0.00 0.00 0.00
May 3288.76 5.48 17-MAY-15:00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 17047641.39 246.42 29-OCT-06:14 0.00 0.00 0.00 0.00 0.00
November 0.210250E+09 575.00 21-NOV-16:06 0.00 0.00 0.00 0.00 0.00
December 0.615036E+09 650.37 13-DEC-10:53 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.190605E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.615036E+09 810.34   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.143084E+09 3340.43 19-JAN-01:40 0.00 0.00 0.00 0.00 0.00
February 0.113567E+09 4565.39 03-FEB-12:05 0.00 0.00 0.00 0.00 0.00
March 0.117046E+09 5317.45 20-MAR-00:30 0.00 0.00 0.00 0.00 0.00
April 41578150.30 11310.17 18-APR-02:45 0.00 0.00 0.00 0.00 0.00
May 0.112895E+09 11295.85 31-MAY-02:65 0.00 0.00 0.00 0.00 0.00
June 0.201198E+09 11293.16 20-JUN-01:50 0.00 0.00 0.00 0.00 0.00
July 0.120190E+09 10853.36 27-JUL-02:00 0.00 0.00 0.00 0.00 0.00
August 76420059.83 9804.79 05-AUG-03:42 0.00 0.00 0.00 0.00 0.00
September 0.194933E+09 11337.56 08-SEP-02:50 0.00 0.00 0.00 0.00 0.00
October 0.146068E+09 8374.92 02-OCT-03:25 0.00 0.00 0.00 0.00 0.00
November 0.148952E+09 5068.23 06-NOV-04:38 0.00 0.00 0.00 0.00 0.00
December 0.163999E+09 4632.01 21-DEC-15:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.157993E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 41578150.30 3340.43   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.201198E+09 11337.56   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.201388E+10 10615.66 28-JAN-08:05 0.00 0.00 0.00 0.00 0.00
February 0.126957E+10 7903.02 01-FEB-18:50 0.00 0.00 0.00 0.00 0.00
March 0.176755E+10 7724.99 05-MAR-14:13 0.00 0.00 0.00 0.00 0.00
April 0.167510E+09 9343.85 06-APR-08:35 0.00 0.00 0.00 0.00 0.00
May 0.264616E+09 7673.15 03-MAY-08:49 0.00 0.00 0.00 0.00 0.00
June 61512361.87 5996.33 07-JUN-09:35 0.00 0.00 0.00 0.00 0.00
July 2273512.87 1365.17 08-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 12452645.78 2010.69 09-AUG-10:50 0.00 0.00 0.00 0.00 0.00
September 30431907.91 3476.48 08-SEP-10:35 0.00 0.00 0.00 0.00 0.00
October 0.939957E+09 9673.39 31-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 0.173851E+10 6854.54 01-NOV-11:23 0.00 0.00 0.00 0.00 0.00
December 0.305752E+10 8720.51 04-DEC-08:44 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.113258E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2273512.87 1365.17   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.305752E+10 10615.66   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.218233E+09 10228.86 13-JAN-13:31 0.00 0.00 0.00 0.00 0.00
February 33742061.58 7187.23 26-FEB-15:50 0.00 0.00 0.00 0.00 0.00
March 34724846.60 7094.95 05-MAR-15:13 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 11152541.19 3141.47 27-OCT-13:25 0.00 0.00 0.00 0.00 0.00
November 78999765.98 5935.41 23-NOV-15:37 0.00 0.00 0.00 0.00 0.00
December 0.550482E+09 7149.95 16-DEC-15:20 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.927334E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.550482E+09 10228.86   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.453722E+10 12122.63 28-JAN-08:05 0.00 0.00 0.00 0.00 0.00
February 0.288115E+10 7919.54 01-FEB-18:50 0.00 0.00 0.00 0.00 0.00
March 0.277722E+10 7495.41 05-MAR-18:17 0.00 0.00 0.00 0.00 0.00
April 18688750.99 2642.21 01-APR-08:53 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.788200E+09 8176.88 31-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 0.317835E+10 7598.95 23-NOV-16:53 0.00 0.00 0.00 0.00 0.00
December 0.690132E+10 11047.74 12-DEC-12:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.210822E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.690132E+10 12122.63   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.332160E+10 7489.13 28-JAN-08:05 0.00 0.00 0.00 0.00 0.00
February 0.230000E+10 4068.34 01-FEB-18:50 0.00 0.00 0.00 0.00 0.00
March 0.187561E+10 4297.37 23-MAR-06:26 0.00 0.00 0.00 0.00 0.00
April 0.156904E+09 3160.59 10-APR-06:22 0.00 0.00 0.00 0.00 0.00
May 20381155.06 2606.94 16-MAY-05:24 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.693450E+09 4310.22 31-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 0.216082E+10 3864.54 07-NOV-06:28 0.00 0.00 0.00 0.00 0.00
December 0.423326E+10 4892.42 04-DEC-08:44 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.147620E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.423326E+10 7489.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 458540.37 1528.47 18-APR-02:45 0.00 0.00 0.00 0.00 0.00
May 530389.80 1380.51 31-MAY-02:65 0.00 0.00 0.00 0.00 0.00
June 999396.50 2282.23 20-JUN-01:50 0.00 0.00 0.00 0.00 0.00
July 110319.05 919.33 27-JUL-02:00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 1388276.40 3166.02 08-SEP-02:50 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 3486922.11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1388276.40 3166.02   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.880954E+09 6337.17 10-JAN-08:10 0.00 0.00 0.00 0.00 0.00
February 0.323295E+09 4130.12 17-FEB-07:00 0.00 0.00 0.00 0.00 0.00
March 46657304.37 1905.21 08-MAR-07:00 0.00 0.00 0.00 0.00 0.00
April 20120.17 0.91 30-APR-08:08 0.00 0.00 0.00 0.00 0.00
May 14233.75 0.91 22-MAY-10:07 0.00 0.00 0.00 0.00 0.00
June 36599.22 0.92 21-JUN-08:10 0.00 0.00 0.00 0.00 0.00
July 68507.53 0.92 26-JUL-10:07 0.00 0.00 0.00 0.00 0.00
August 80210.62 0.92 16-AUG-19:40 0.00 0.00 0.00 0.00 0.00
September 42749.05 0.91 22-SEP-08:00 0.00 0.00 0.00 0.00 0.00
October 8237.89 0.87 06-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 78492326.62 2304.82 29-NOV-02:00 0.00 0.00 0.00 0.00 0.00
December 0.436298E+09 3427.96 29-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.176597E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 8237.89 0.87   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.880954E+09 6337.17   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.392466E+10 8859.65 11-JAN-19:01 0.00 0.00 0.00 0.00 0.00
February 0.294539E+10 8705.62 13-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.288243E+10 8677.56 15-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.625843E+09 8454.15 01-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 0.422788E+09 8337.04 05-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 36005010.32 2979.34 18-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 50009886.19 3189.25 07-JUL-15:04 0.00 0.00 0.00 0.00 0.00
August 8490770.49 3404.52 26-AUG-15:04 0.00 0.00 0.00 0.00 0.00
September 0.119385E+09 2912.36 03-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 0.153952E+10 8481.73 19-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.317470E+10 8717.14 29-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.514981E+10 8765.18 29-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.208790E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 8490770.49 2912.36   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.514981E+10 8859.65   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.485145E+10 8693.26 11-JAN-19:01 0.00 0.00 0.00 0.00 0.00
February 0.369689E+10 8579.74 17-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.325418E+10 8516.58 15-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.900703E+09 8319.37 01-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 0.513382E+09 8191.33 05-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 42124558.26 2625.00 09-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 53588370.58 3095.72 07-JUL-15:04 0.00 0.00 0.00 0.00 0.00
August 13362705.82 3047.50 26-AUG-15:04 0.00 0.00 0.00 0.00 0.00
September 0.222707E+09 4598.96 07-SEP-08:62 0.00 0.00 0.00 0.00 0.00
October 0.202201E+10 8351.40 23-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.383425E+10 8553.66 29-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.578868E+10 8600.67 29-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.251933E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 13362705.82 2625.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.578868E+10 8693.26   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.148478E+10 9543.46 31-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 0.101473E+10 10917.22 02-FEB-04:50 0.00 0.00 0.00 0.00 0.00
March 0.121786E+10 8466.01 16-MAR-04:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.641941E+09 7109.09 30-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.829973E+10 14618.04 17-DEC-04:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.126590E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.829973E+10 14618.04   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.156243E+11 47423.13 10-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.121532E+11 46246.94 17-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.634848E+10 45934.81 15-MAR-15:01 0.00 0.00 0.00 0.00 0.00
April 0.117167E+10 44809.72 10-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.395982E+09 21706.79 21-MAY-15:05 0.00 0.00 0.00 0.00 0.00
June 34246144.82 16098.13 17-JUN-15:06 0.00 0.00 0.00 0.00 0.00
July 35518841.15 18914.96 21-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 48958902.07 22108.96 04-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 0.134627E+09 27501.53 29-SEP-15:03 0.00 0.00 0.00 0.00 0.00
October 0.285329E+10 44930.13 23-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.973212E+10 46183.32 29-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.184405E+11 46555.12 29-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.669728E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 34246144.82 16098.13   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.184405E+11 47423.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.394582E+10 8693.56 11-JAN-19:01 0.00 0.00 0.00 0.00 0.00
February 0.308354E+10 8520.12 16-FEB-19:01 0.00 0.00 0.00 0.00 0.00
March 0.291411E+10 8511.07 15-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.578757E+09 8236.80 10-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.420313E+09 6626.52 04-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 64252888.31 2388.09 29-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 34535930.64 3459.07 07-JUL-15:04 0.00 0.00 0.00 0.00 0.00
August 6673594.12 2217.56 11-AUG-15:05 0.00 0.00 0.00 0.00 0.00
September 88668116.12 2596.61 02-SEP-18:04 0.00 0.00 0.00 0.00 0.00
October 0.153579E+10 8322.51 19-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.318732E+10 8553.93 29-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.499267E+10 8600.96 29-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.208524E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 6673594.12 2217.56   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.499267E+10 8693.56   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.484094E+10 8528.18 11-JAN-19:01 0.00 0.00 0.00 0.00 0.00
February 0.389526E+10 8380.41 13-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.329063E+10 8355.06 15-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.802671E+09 8103.39 10-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.515359E+09 7218.57 04-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 82608751.97 2205.22 17-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 41632484.27 3127.44 07-JUL-15:04 0.00 0.00 0.00 0.00 0.00
August 13641668.45 2124.55 11-AUG-15:05 0.00 0.00 0.00 0.00 0.00
September 0.182862E+09 3542.43 29-SEP-15:04 0.00 0.00 0.00 0.00 0.00
October 0.198667E+10 8169.68 19-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.382933E+10 8391.46 29-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.559368E+10 8437.46 29-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.250753E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 13641668.45 2124.55   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.559368E+10 8528.18   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.141930E+10 2670.14 11-JAN-19:01 0.00 0.00 0.00 0.00 0.00
February 0.107006E+10 2635.37 17-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.105211E+10 2616.22 13-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.301200E+09 2570.58 01-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 0.229009E+09 2534.04 05-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 45736298.09 916.35 24-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 39880817.30 850.77 15-JUL-08:03 0.00 0.00 0.00 0.00 0.00
August 13897095.00 865.36 26-AUG-15:04 0.00 0.00 0.00 0.00 0.00
September 97649988.79 1705.91 07-SEP-08:62 0.00 0.00 0.00 0.00 0.00
October 0.640836E+09 2576.62 19-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.115874E+10 2627.35 29-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.179106E+10 2641.72 29-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.785948E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 13897095.00 850.77   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.179106E+10 2670.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.170847E+10 2607.48 11-JAN-19:01 0.00 0.00 0.00 0.00 0.00
February 0.130811E+10 2573.63 17-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.116857E+10 2557.07 21-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.404942E+09 2517.38 01-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 0.269043E+09 2477.87 05-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 53639228.04 705.66 18-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 43190389.31 838.49 15-JUL-08:03 0.00 0.00 0.00 0.00 0.00
August 27410965.39 797.12 26-AUG-15:04 0.00 0.00 0.00 0.00 0.00
September 0.169628E+09 2456.64 20-SEP-08:62 0.00 0.00 0.00 0.00 0.00
October 0.814209E+09 2524.94 23-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.136667E+10 2565.81 29-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.198945E+10 2579.77 29-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.932333E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 27410965.39 705.66   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.198945E+10 2607.48   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.367230E+10 12988.29 10-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.271629E+10 12754.42 16-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.304984E+10 12810.20 15-MAR-15:01 0.00 0.00 0.00 0.00 0.00
April 0.612691E+09 12391.63 10-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.582118E+09 11837.06 17-MAY-08:61 0.00 0.00 0.00 0.00 0.00
June 97950541.08 4782.31 03-JUN-15:04 0.00 0.00 0.00 0.00 0.00
July 74514940.96 5100.98 28-JUL-18:04 0.00 0.00 0.00 0.00 0.00
August 14247229.66 4877.85 03-AUG-08:03 0.00 0.00 0.00 0.00 0.00
September 94033289.00 4453.36 09-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 0.130227E+10 12489.63 19-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.287881E+10 12865.42 29-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.552685E+10 12936.90 27-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.206219E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 14247229.66 4453.36   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.552685E+10 12988.29   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.360948E+09 0.360948E+09 34894.34 27-JAN-22:03 34894.34 0.01
February 0.00 0.00 0.319493E+09 0.319493E+09 20123.75 04-FEB-19:20 20123.75 0.02
March 0.00 0.00 0.330694E+09 0.330694E+09 32879.96 08-MAR-20:35 32879.96 0.01
April 0.00 0.00 0.154374E+11 0.154223E+11 187121.57 30-APR-18:10 187121.57 0.01
May 0.00 0.00 0.156008E+11 0.156008E+11 161265.13 22-MAY-15:30 161265.13 0.11
June 0.00 0.00 0.493788E+11 0.468384E+11 336077.52 25-JUN-18:00 149300.23 0.36
July 0.00 0.00 0.848233E+11 0.835516E+11 232245.05 22-JUL-18:10 232245.05 0.51
August 0.00 0.00 0.987290E+11 0.974668E+11 212528.36 14-AUG-18:10 212528.36 0.58
September 0.00 0.00 0.507377E+11 0.503435E+11 159598.22 11-SEP-17:17 159598.22 0.36
October 0.00 0.00 0.286056E+10 0.286056E+10 71458.90 07-OCT-15:03 71458.90 0.05
November 0.00 0.00 0.349138E+09 0.349138E+09 27014.06 24-NOV-11:50 27014.06 0.01
December 0.00 0.00 0.396484E+09 0.396484E+09 23056.11 20-DEC-22:10 23056.11 0.00
                 
Annual Sum or Average 0.00 0.00 0.319324E+12 0.313841E+12       0.17
Minimum of Months 0.00 0.00 0.319493E+09 0.319493E+09 20123.75   20123.75 0.00
Maximum of Months 0.00 0.00 0.987290E+11 0.974668E+11 336077.52   232245.05 0.58



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 3613.89 3613.89 54.21 03-FEB-16:09 54.21 0.00
March 0.00 0.00 79458.00 79458.00 121.78 25-MAR-21:10 121.78 0.00
April 0.00 0.00 0.245803E+10 0.245615E+10 28194.89 30-APR-18:02 28194.89 0.01
May 0.00 0.00 0.246120E+10 0.246120E+10 28053.87 22-MAY-15:00 28053.87 0.06
June 0.00 0.00 0.824314E+10 0.756366E+10 43677.86 25-JUN-18:00 19689.93 0.25
July 0.00 0.00 0.146576E+11 0.138663E+11 32333.62 23-JUL-16:00 24012.41 0.44
August 0.00 0.00 0.178130E+11 0.168728E+11 32326.30 17-AUG-15:00 24128.17 0.52
September 0.00 0.00 0.918905E+10 0.875968E+10 30819.96 10-SEP-15:02 24192.47 0.27
October 0.00 0.00 0.434600E+09 0.434600E+09 15106.35 07-OCT-15:00 15106.35 0.01
November 0.00 0.00 6967765.75 6967765.75 4050.01 24-NOV-12:00 4050.01 0.00
December 0.00 0.00 32372.43 32372.43 53.95 21-DEC-14:30 53.95 0.00
                 
Annual Sum or Average 0.00 0.00 0.552637E+11 0.524214E+11       0.13
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.178130E+11 0.168728E+11 43677.86   28194.89 0.52



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 28322137.19 26610512.77 13253.21 19-JAN-16:02 13253.21 0.00
February 0.00 0.00 0.177926E+09 0.167099E+09 13734.17 09-FEB-16:02 13734.17 0.01
March 0.00 0.00 91363090.54 89545570.39 13264.54 23-MAR-18:02 13264.54 0.00
April 0.00 0.00 0.253621E+10 0.221509E+10 14058.34 27-APR-15:02 14058.34 0.20
May 0.00 0.00 0.309043E+10 0.233972E+10 14168.88 21-MAY-15:02 14168.88 0.39
June 0.00 0.00 0.478486E+10 0.306841E+10 14449.70 27-JUN-08:62 11623.01 0.76
July 0.00 0.00 0.611751E+10 0.388503E+10 14718.74 22-JUL-08:61 13997.56 0.80
August 0.00 0.00 0.573807E+10 0.344459E+10 14580.22 11-AUG-15:02 12399.71 0.87
September 0.00 0.00 0.408150E+10 0.257198E+10 14233.66 10-SEP-18:02 13260.86 0.68
October 0.00 0.00 0.897164E+09 0.702383E+09 14166.82 07-OCT-15:02 14166.82 0.13
November 0.00 0.00 41725306.50 38482919.75 13354.21 03-NOV-15:01 13354.21 0.00
December 0.00 0.00 1890089.82 1584545.54 2472.53 05-DEC-19:04 1504.61 0.00
                 
Annual Sum or Average 0.00 0.00 0.275870E+11 0.185505E+11       0.32
Minimum of Months 0.00 0.00 1890089.82 1584545.54 2472.53   1504.61 0.00
Maximum of Months 0.00 0.00 0.611751E+10 0.388503E+10 14718.74   14168.88 0.87



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 5984395.86 4630674.40 3369.94 19-JAN-16:02 3369.94 0.00
February 0.00 0.00 42640901.02 37700575.21 11136.27 19-FEB-16:02 11136.27 0.00
March 0.00 0.00 49681255.74 47982014.27 11514.30 23-MAR-18:02 11514.30 0.00
April 0.00 0.00 0.155589E+10 0.135119E+10 12487.02 27-APR-15:02 12487.02 0.15
May 0.00 0.00 0.237698E+10 0.181965E+10 12585.53 21-MAY-15:02 12585.53 0.33
June 0.00 0.00 0.419417E+10 0.275826E+10 12805.55 27-JUN-08:62 10268.59 0.70
July 0.00 0.00 0.524609E+10 0.338671E+10 13038.72 22-JUL-08:61 12453.51 0.74
August 0.00 0.00 0.422007E+10 0.249875E+10 12934.35 09-AUG-15:02 11849.53 0.77
September 0.00 0.00 0.225167E+10 0.135275E+10 12488.13 24-SEP-15:02 12488.13 0.51
October 0.00 0.00 0.335870E+09 0.282976E+09 12582.94 07-OCT-15:02 12582.94 0.05
November 0.00 0.00 7395862.10 5326322.17 4573.39 10-NOV-16:02 4573.39 0.00
December 0.00 0.00 2603157.88 2294364.00 1913.21 02-DEC-09:04 1001.62 0.00
                 
Annual Sum or Average 0.00 0.00 0.202890E+11 0.135482E+11       0.27
Minimum of Months 0.00 0.00 2603157.88 2294364.00 1913.21   1001.62 0.00
Maximum of Months 0.00 0.00 0.524609E+10 0.338671E+10 13038.72   12585.53 0.77



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.623285E+09 0.623285E+09 20486.01 21-JAN-11:30 20486.01 0.00
February 0.00 0.00 0.464057E+09 0.457657E+09 16187.21 04-FEB-14:40 16187.21 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 0.00 0.00
April 0.00 0.00 0.133199E+11 0.131494E+11 40959.76 30-APR-12:50 40959.76 0.01
May 0.00 0.00 0.873763E+10 0.676474E+10 31660.09 23-MAY-13:10 22380.09 0.12
June 0.00 0.00 0.117690E+11 0.548046E+10 32870.71 13-JUN-13:20 22615.83 0.45
July 0.00 0.00 0.169769E+11 0.864798E+10 38922.35 22-JUL-13:10 31326.25 0.53
August 0.00 0.00 0.233450E+11 0.145095E+11 43225.54 19-AUG-13:00 37419.75 0.54
September 0.00 0.00 0.291580E+11 0.214239E+11 53399.07 27-SEP-12:40 46372.99 0.46
October 0.00 0.00 0.934595E+10 0.913630E+10 48203.07 07-OCT-13:20 48203.07 0.03
November 0.00 0.00 0.227624E+09 0.227624E+09 16015.57 11-NOV-13:23 16015.57 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.113967E+12 0.804207E+11       0.18
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.291580E+11 0.214239E+11 53399.07   48203.07 0.54



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.280943E+09 0.138625E+09 41358.86 29-JAN-09:02 41358.86 0.04
February 0.00 0.00 0.188647E+09 0.115809E+09 29155.63 11-FEB-19:03 29155.63 0.02
March 0.00 0.00 0.151004E+10 0.117150E+10 47737.98 25-MAR-08:62 47737.98 0.05
April 0.00 0.00 0.950106E+10 0.820543E+10 55615.37 29-APR-18:02 55615.37 0.19
May 0.00 0.00 0.153766E+11 0.113277E+11 55418.58 21-MAY-18:02 55418.58 0.46
June 0.00 0.00 0.275946E+11 0.185855E+11 61053.46 26-JUN-18:02 49056.65 0.68
July 0.00 0.00 0.312005E+11 0.206880E+11 58699.24 23-JUL-18:02 53862.55 0.70
August 0.00 0.00 0.251824E+11 0.150703E+11 57524.86 17-AUG-15:02 53437.82 0.70
September 0.00 0.00 0.151798E+11 0.850014E+10 56846.13 16-SEP-08:62 46221.06 0.64
October 0.00 0.00 0.340867E+10 0.175088E+10 52750.61 09-OCT-08:63 48810.07 0.25
November 0.00 0.00 0.665538E+09 0.267723E+09 43292.13 23-NOV-09:01 43292.13 0.08
December 0.00 0.00 71134449.63 67325489.27 24885.84 06-DEC-19:04 24885.84 0.00
                 
Annual Sum or Average 0.00 0.00 0.130160E+12 0.858890E+11       0.32
Minimum of Months 0.00 0.00 71134449.63 67325489.27 24885.84   24885.84 0.00
Maximum of Months 0.00 0.00 0.312005E+11 0.206880E+11 61053.46   55615.37 0.70



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 67099034.24 57538430.73 4483.25 21-JAN-16:02 4483.25 0.01
February 0.00 0.00 0.111522E+09 99723181.64 11641.18 20-FEB-09:01 11641.18 0.01
March 0.00 0.00 61489842.29 58660910.75 6584.07 20-MAR-15:02 6584.07 0.00
April 0.00 0.00 0.290564E+10 0.254515E+10 12695.18 27-APR-15:02 12695.18 0.22
May 0.00 0.00 0.307387E+10 0.226318E+10 12795.26 21-MAY-15:02 12795.26 0.44
June 0.00 0.00 0.443038E+10 0.275037E+10 13660.55 26-JUN-18:02 11439.41 0.75
July 0.00 0.00 0.570510E+10 0.350217E+10 12987.72 13-JUL-15:02 11993.79 0.84
August 0.00 0.00 0.604670E+10 0.370965E+10 13177.27 11-AUG-15:02 11285.50 0.89
September 0.00 0.00 0.461819E+10 0.295367E+10 12559.49 10-SEP-18:02 11833.89 0.75
October 0.00 0.00 0.966356E+09 0.733929E+09 12793.18 07-OCT-15:02 12793.18 0.14
November 0.00 0.00 63684638.48 48026076.34 11144.13 03-NOV-15:01 11144.13 0.01
December 0.00 0.00 16166679.79 15611219.57 3165.06 20-DEC-09:04 2436.37 0.00
                 
Annual Sum or Average 0.00 0.00 0.280662E+11 0.187377E+11       0.34
Minimum of Months 0.00 0.00 16166679.79 15611219.57 3165.06   2436.37 0.00
Maximum of Months 0.00 0.00 0.604670E+10 0.370965E+10 13660.55   12795.26 0.89



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 6291432.26 4899381.93 3445.56 23-JAN-19:04 2826.20 0.00
February 0.00 0.00 17121347.77 14968425.63 4427.99 20-FEB-09:01 4427.99 0.00
March 0.00 0.00 24194173.56 23043627.66 3911.14 21-MAR-18:03 3911.14 0.00
April 0.00 0.00 0.176518E+10 0.151860E+10 11365.51 27-APR-15:02 11365.51 0.18
May 0.00 0.00 0.229254E+10 0.169850E+10 11454.86 21-MAY-15:02 11454.86 0.37
June 0.00 0.00 0.380026E+10 0.242624E+10 12250.92 26-JUN-18:02 10230.68 0.69
July 0.00 0.00 0.476045E+10 0.297178E+10 11937.31 17-JUL-15:02 10812.69 0.81
August 0.00 0.00 0.441537E+10 0.265353E+10 11848.17 17-AUG-15:02 11056.91 0.86
September 0.00 0.00 0.259553E+10 0.159232E+10 11720.34 12-SEP-15:02 11098.95 0.59
October 0.00 0.00 0.332145E+09 0.249557E+09 10877.05 07-OCT-15:02 10877.05 0.07
November 0.00 0.00 9467391.58 7381350.43 3420.70 19-NOV-09:03 3420.70 0.00
December 0.00 0.00 3641760.28 3431144.60 2830.21 11-DEC-09:04 2830.21 0.00
                 
Annual Sum or Average 0.00 0.00 0.200222E+11 0.131643E+11       0.30
Minimum of Months 0.00 0.00 3641760.28 3431144.60 2830.21   2826.20 0.00
Maximum of Months 0.00 0.00 0.476045E+10 0.297178E+10 12250.92   11454.86 0.86



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 6445606.12 5942575.46 3505.48 19-JAN-16:02 3505.48 0.00
February 0.00 0.00 46579099.17 43922238.45 3614.16 09-FEB-16:02 3614.16 0.01
March 0.00 0.00 21362763.67 20706987.50 3550.15 23-MAR-18:02 3550.15 0.00
April 0.00 0.00 0.654608E+09 0.586573E+09 3699.65 27-APR-15:02 3699.65 0.15
May 0.00 0.00 0.765366E+09 0.607404E+09 3728.62 21-MAY-15:02 3728.62 0.31
June 0.00 0.00 0.116930E+10 0.788341E+09 3957.64 27-JUN-08:62 2873.81 0.64
July 0.00 0.00 0.151052E+10 0.995958E+09 3931.42 22-JUL-08:61 3649.96 0.75
August 0.00 0.00 0.135588E+10 0.850434E+09 3839.52 09-AUG-15:02 3505.93 0.79
September 0.00 0.00 0.924010E+09 0.613102E+09 3738.67 10-SEP-18:02 3493.51 0.55
October 0.00 0.00 0.199366E+09 0.165574E+09 3728.00 07-OCT-15:02 3728.00 0.09
November 0.00 0.00 9733252.38 8756093.75 3485.84 10-NOV-16:02 3485.84 0.00
December 0.00 0.00 196659.91 164680.32 609.52 05-DEC-19:04 354.32 0.00
                 
Annual Sum or Average 0.00 0.00 0.666337E+10 0.468688E+10       0.27
Minimum of Months 0.00 0.00 196659.91 164680.32 609.52   354.32 0.00
Maximum of Months 0.00 0.00 0.151052E+10 0.995958E+09 3957.64   3728.62 0.79



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 1008732.70 700694.78 829.85 21-JAN-16:03 829.85 0.00
February 0.00 0.00 7466194.52 6189805.83 2119.99 27-FEB-16:01 2119.99 0.00
March 0.00 0.00 10611378.09 10061741.15 3035.69 23-MAR-18:02 3035.69 0.00
April 0.00 0.00 0.399037E+09 0.358204E+09 3257.65 27-APR-15:02 3257.65 0.11
May 0.00 0.00 0.577346E+09 0.467583E+09 3283.28 21-MAY-15:02 3283.28 0.25
June 0.00 0.00 0.100750E+10 0.700641E+09 3481.84 27-JUN-08:62 2513.21 0.58
July 0.00 0.00 0.126828E+10 0.845978E+09 3456.82 22-JUL-08:61 3217.08 0.69
August 0.00 0.00 0.951941E+09 0.594068E+09 3383.53 11-AUG-18:02 2938.59 0.65
September 0.00 0.00 0.473463E+09 0.310415E+09 3259.45 10-SEP-18:02 2970.96 0.35
October 0.00 0.00 70545247.77 61148662.62 3282.55 07-OCT-15:02 3282.55 0.02
November 0.00 0.00 1929890.68 1408957.22 1282.05 03-NOV-15:02 1282.05 0.00
December 0.00 0.00 82757.57 56661.25 760.51 05-DEC-19:04 572.08 0.00
                 
Annual Sum or Average 0.00 0.00 0.476921E+10 0.335646E+10       0.22
Minimum of Months 0.00 0.00 82757.57 56661.25 760.51   572.08 0.00
Maximum of Months 0.00 0.00 0.126828E+10 0.845978E+09 3481.84   3283.28 0.69



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.106210E+10 0.937039E+09 20007.23 21-JAN-16:02 20007.23 0.06
February 0.00 0.00 0.130561E+10 0.123866E+10 20005.59 09-FEB-16:02 20005.59 0.03
March 0.00 0.00 0.336381E+09 0.306221E+09 19999.15 20-MAR-15:02 19999.15 0.02
April 0.00 0.00 0.515479E+10 0.453885E+10 20476.59 27-APR-15:02 20476.59 0.27
May 0.00 0.00 0.413383E+10 0.287254E+10 20637.92 21-MAY-15:02 20637.92 0.44
June 0.00 0.00 0.552551E+10 0.308120E+10 22312.28 26-JUN-18:02 18293.96 0.73
July 0.00 0.00 0.747323E+10 0.425015E+10 21240.01 23-JUL-18:02 19577.37 0.80
August 0.00 0.00 0.889892E+10 0.549221E+10 21553.98 11-AUG-15:02 18354.16 0.87
September 0.00 0.00 0.876312E+10 0.603337E+10 21122.69 10-SEP-18:02 19091.96 0.79
October 0.00 0.00 0.321597E+10 0.243969E+10 20636.26 07-OCT-15:02 20636.26 0.30
November 0.00 0.00 0.825487E+09 0.683202E+09 20010.36 11-NOV-16:02 20010.36 0.05
December 0.00 0.00 0.312739E+09 0.304826E+09 19381.28 18-DEC-16:01 19381.28 0.00
                 
Annual Sum or Average 0.00 0.00 0.470077E+11 0.321780E+11       0.36
Minimum of Months 0.00 0.00 0.312739E+09 0.304826E+09 19381.28   18293.96 0.00
Maximum of Months 0.00 0.00 0.889892E+10 0.603337E+10 22312.28   20637.92 0.87



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 29376.19 212587.07 28-JAN-19:01
February 0.00 0.00 01-FEB-00:03 23887.61 209731.63 11-FEB-19:02
March 0.00 0.00 01-MAR-00:03 22280.13 195823.36 24-MAR-08:62
April 0.00 0.00 01-APR-00:10 11644.53 162322.30 07-APR-20:10
May 0.00 0.00 01-MAY-00:10 14148.39 141197.46 04-MAY-08:62
June 0.00 0.00 01-JUN-00:05 6927.07 119325.45 02-JUN-02:62
July 0.00 0.00 01-JUL-00:10 4113.66 116881.89 15-JUL-04:55
August 0.00 0.00 01-AUG-00:05 2674.83 115564.39 23-AUG-03:52
September 0.00 0.00 01-SEP-00:05 6876.94 118453.11 28-SEP-06:48
October 0.00 0.00 01-OCT-00:10 19717.55 197334.45 30-OCT-08:61
November 0.00 0.00 01-NOV-00:05 28743.51 204629.84 02-NOV-08:61
December 0.00 0.00 01-DEC-00:03 35001.64 203362.30 22-DEC-16:01
             
Annual Sum or Average 0.00     17099.45    
Minimum of Months 0.00 0.00   2674.83 115564.39  
Maximum of Months 0.00 0.00   35001.64 212587.07  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 2155.84 45591.70 14-JAN-19:04 0.00 0.00 01-JAN-00:10
February 2579.46 52162.96 27-FEB-16:04 0.00 0.00 01-FEB-00:03
March 2186.25 49303.37 20-MAR-18:02 0.00 0.00 01-MAR-00:03
April 24628.18 346259.12 30-APR-18:02 0.00 0.00 01-APR-00:10
May 25235.59 337322.62 22-MAY-15:03 0.00 0.00 01-MAY-00:10
June 51259.72 530961.78 25-JUN-18:03 0.00 0.00 01-JUN-00:05
July 71736.37 421742.74 22-JUL-18:03 0.00 0.00 01-JUL-00:10
August 78253.69 391786.12 14-AUG-18:03 0.00 0.00 01-AUG-00:05
September 53690.43 353169.32 13-SEP-15:03 0.00 0.00 01-SEP-00:05
October 10404.84 205729.72 07-OCT-15:02 0.00 0.00 01-OCT-00:10
November 2006.30 44122.19 27-NOV-09:04 0.00 0.00 01-NOV-00:05
December 1429.63 53119.63 12-DEC-09:04 0.00 0.00 01-DEC-00:03
             
Annual Sum or Average 27269.13     0.00    
Minimum of Months 1429.63 44122.19   0.00 0.00  
Maximum of Months 78253.69 530961.78   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 28081.71 67034.34 28-JAN-08:33
February 0.00 0.00 01-FEB-00:03 28271.67 66637.72 07-FEB-21:31
March 0.00 0.00 01-MAR-00:03 28087.32 65153.25 18-MAR-07:26
April 0.00 0.00 01-APR-00:10 27559.30 67660.37 07-APR-06:51
May 0.00 0.00 01-MAY-00:10 26854.17 67159.76 09-MAY-06:11
June 0.00 0.00 01-JUN-00:05 26183.38 63646.51 08-JUN-06:51
July 0.00 0.00 01-JUL-00:10 25654.08 59053.09 03-JUL-06:33
August 0.00 0.00 01-AUG-00:05 25499.80 57821.05 24-AUG-06:06
September 0.00 0.00 01-SEP-00:05 25652.04 64079.85 21-SEP-06:41
October 0.00 0.00 01-OCT-00:10 26124.39 63426.96 13-OCT-06:05
November 0.00 0.00 01-NOV-00:05 26829.89 67407.83 22-NOV-07:41
December 0.00 0.00 01-DEC-00:03 27575.28 64219.06 20-DEC-21:01
             
Annual Sum or Average 0.00     26856.23    
Minimum of Months 0.00 0.00   25499.80 57821.05  
Maximum of Months 0.00 0.00   28271.67 67660.37  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.587890E+10 0.89 2194.93 01-JAN-00:10 0.89
February 0.530997E+10 0.88 2194.93 01-FEB-00:03 0.88
March 0.587890E+10 0.89 2194.93 01-MAR-00:03 0.88
April 0.568926E+10 0.89 2194.93 01-APR-00:10 0.89
May 0.587890E+10 0.88 2194.93 01-MAY-00:10 0.88
June 0.568926E+10 0.88 2194.93 01-JUN-00:05 0.88
July 0.587890E+10 0.88 2194.93 01-JUL-00:10 0.88
August 0.587890E+10 0.88 2194.93 01-AUG-00:05 0.88
September 0.568926E+10 0.88 2194.93 01-SEP-00:05 0.88
October 0.587890E+10 0.88 2194.93 01-OCT-00:10 0.88
November 0.568926E+10 0.88 2194.93 01-NOV-00:05 0.89
December 0.587890E+10 0.89 2194.93 01-DEC-00:03 0.88
           
Annual Sum or Average 0.692193E+11 0.88      
Minimum of Months 0.530997E+10 0.88 2194.93   0.88
Maximum of Months 0.587890E+10 0.89 2194.93   0.89



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.333350E+11 0.79 28931.40 25-JAN-23:10 1.30
February 0.302862E+11 0.80 26766.10 06-FEB-22:05 1.24
March 0.342480E+11 0.81 34139.04 24-MAR-21:20 1.45
April 0.343275E+11 0.82 39918.59 07-APR-19:50 1.60
May 0.361485E+11 0.83 39777.32 10-MAY-21:45 1.59
June 0.353726E+11 0.83 31312.05 11-JUN-22:02 1.36
July 0.368119E+11 0.83 31312.05 05-JUL-05:20 1.37
August 0.368135E+11 0.83 27807.97 20-AUG-05:55 1.27
September 0.353651E+11 0.83 41654.34 08-SEP-03:30 1.64
October 0.355904E+11 0.82 42281.96 05-OCT-21:05 1.65
November 0.337177E+11 0.81 35890.24 17-NOV-21:55 1.49
December 0.332647E+11 0.79 26344.80 02-DEC-08:43 1.23
           
Annual Sum or Average 0.415281E+12 0.82      
Minimum of Months 0.302862E+11 0.79 26344.80   1.23
Maximum of Months 0.368135E+11 0.83 42281.96   1.65



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.27 76.61 01-JAN-00:10 0.27
February 0.185347E+09 0.27 76.61 01-FEB-00:03 0.27
March 0.205205E+09 0.27 76.61 01-MAR-00:03 0.27
April 0.198586E+09 0.27 76.61 01-APR-00:10 0.27
May 0.205205E+09 0.27 76.61 01-MAY-00:10 0.27
June 0.198586E+09 0.27 76.61 01-JUN-00:05 0.27
July 0.205205E+09 0.27 76.61 01-JUL-00:10 0.27
August 0.205205E+09 0.27 76.61 01-AUG-00:05 0.27
September 0.198586E+09 0.27 76.61 01-SEP-00:05 0.27
October 0.205205E+09 0.27 76.61 01-OCT-00:10 0.27
November 0.198586E+09 0.27 76.61 01-NOV-00:05 0.27
December 0.205205E+09 0.27 76.61 01-DEC-00:03 0.27
           
Annual Sum or Average 0.241613E+10 0.27      
Minimum of Months 0.185347E+09 0.27 76.61   0.27
Maximum of Months 0.205205E+09 0.27 76.61   0.27



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:10 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:10 0.00
February 0.00 -0.0 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:10 0.00
June 0.00 -0.0 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 -0.0 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 -0.0 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:10 0.00
February 0.00 -0.0 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:10 0.00
June 0.00 -0.0 0.00 01-JUN-00:05 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.19 612.92 01-JAN-07:05 0.27
February 0.105030E+10 0.19 612.92 01-FEB-07:10 0.27
March 0.116283E+10 0.19 612.92 01-MAR-07:10 0.27
April 0.112532E+10 0.19 612.92 01-APR-06:10 0.27
May 0.116283E+10 0.19 612.92 01-MAY-06:05 0.27
June 0.112532E+10 0.19 612.92 01-JUN-06:03 0.27
July 0.116283E+10 0.19 612.92 01-JUL-06:10 0.27
August 0.116283E+10 0.19 612.92 01-AUG-06:05 0.27
September 0.112532E+10 0.19 612.92 01-SEP-06:05 0.27
October 0.116283E+10 0.19 612.92 01-OCT-06:03 0.27
November 0.112532E+10 0.19 612.92 01-NOV-06:05 0.27
December 0.116283E+10 0.19 612.92 01-DEC-07:10 0.27
           
Annual Sum or Average 0.136914E+11 0.19      
Minimum of Months 0.105030E+10 0.19 612.92   0.27
Maximum of Months 0.116283E+10 0.19 612.92   0.27



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.251910E+09 0.43 826.01 01-JAN-09:01 0.58
February 0.207347E+09 0.42 826.01 01-FEB-09:01 0.58
March 0.207439E+09 0.41 826.01 01-MAR-09:01 0.58
April 0.230077E+09 0.47 826.01 01-APR-08:62 0.58
May 0.246133E+09 0.46 826.01 01-MAY-15:02 0.58
June 0.302315E+09 0.48 826.01 01-JUN-15:02 0.58
July 0.369976E+09 0.50 826.01 01-JUL-15:02 0.58
August 0.343193E+09 0.51 826.01 01-AUG-15:02 0.58
September 0.269913E+09 0.49 826.01 01-SEP-15:02 0.58
October 0.187115E+09 0.43 826.01 01-OCT-15:02 0.58
November 0.218350E+09 0.42 826.01 01-NOV-08:61 0.58
December 0.308981E+09 0.47 826.01 01-DEC-09:01 0.58
           
Annual Sum or Average 0.314275E+10 0.46      
Minimum of Months 0.187115E+09 0.41 826.01   0.58
Maximum of Months 0.369976E+09 0.51 826.01   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.269857E+09 0.46 732.99 01-JAN-09:01 0.58
February 0.214614E+09 0.42 732.99 01-FEB-09:01 0.58
March 0.204593E+09 0.42 732.99 01-MAR-09:01 0.58
April 0.180957E+09 0.43 732.99 01-APR-08:62 0.58
May 0.204769E+09 0.44 732.99 01-MAY-15:02 0.58
June 0.268355E+09 0.46 732.99 01-JUN-15:02 0.58
July 0.320458E+09 0.47 732.99 01-JUL-15:02 0.58
August 0.257375E+09 0.46 732.99 01-AUG-15:02 0.58
September 0.169438E+09 0.44 732.99 01-SEP-15:02 0.58
October 0.165375E+09 0.41 732.99 01-OCT-15:02 0.58
November 0.226611E+09 0.43 732.99 01-NOV-08:61 0.58
December 0.311442E+09 0.50 732.99 01-DEC-09:01 0.58
           
Annual Sum or Average 0.279384E+10 0.45      
Minimum of Months 0.165375E+09 0.41 732.99   0.58
Maximum of Months 0.320458E+09 0.50 732.99   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.199586E+09 0.11 1081.20 21-JAN-11:30 0.58
February 0.130418E+09 0.07 911.12 04-FEB-14:40 0.58
March 0.131645E+09 0.08 672.85 16-MAR-04:00 0.58
April 0.741325E+09 0.21 1825.61 28-APR-12:00 0.58
May 0.546926E+09 0.19 1860.91 01-MAY-07:57 0.58
June 0.720799E+09 0.28 1368.89 13-JUN-13:20 0.58
July 0.943733E+09 0.32 1591.74 23-JUL-13:00 0.58
August 0.120885E+10 0.34 1860.91 03-AUG-07:13 0.58
September 0.162011E+10 0.36 3428.43 25-SEP-13:30 0.58
October 0.513598E+09 0.12 2750.26 07-OCT-13:20 0.58
November 87039497.51 0.05 903.91 11-NOV-13:23 0.58
December 0.735181E+09 0.32 948.99 17-DEC-04:40 0.58
           
Annual Sum or Average 0.757921E+10 0.21      
Minimum of Months 87039497.51 0.05 672.85   0.58
Maximum of Months 0.162011E+10 0.36 3428.43   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.874053E+09 0.41 3347.11 01-JAN-16:01 0.58
February 0.715047E+09 0.41 3347.11 01-FEB-09:01 0.58
March 0.558144E+09 0.41 3347.11 01-MAR-09:01 0.58
April 0.740887E+09 0.41 3347.11 01-APR-18:02 0.58
May 0.100311E+10 0.41 3347.11 01-MAY-15:02 0.58
June 0.158106E+10 0.41 3347.11 01-JUN-08:62 0.58
July 0.170148E+10 0.41 3347.11 01-JUL-08:62 0.58
August 0.134329E+10 0.41 3347.11 01-AUG-15:02 0.58
September 0.889593E+09 0.41 3347.11 01-SEP-15:02 0.58
October 0.489315E+09 0.41 3347.11 01-OCT-08:62 0.58
November 0.655556E+09 0.41 3347.11 01-NOV-08:61 0.58
December 0.985565E+09 0.41 3347.11 01-DEC-09:01 0.58
           
Annual Sum or Average 0.115371E+11 0.41      
Minimum of Months 0.489315E+09 0.41 3347.11   0.58
Maximum of Months 0.170148E+10 0.41 3347.11   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.235902E+09 0.43 745.28 01-JAN-16:01 0.58
February 0.193736E+09 0.42 745.28 01-FEB-09:01 0.58
March 0.191821E+09 0.41 745.28 01-MAR-09:01 0.58
April 0.241557E+09 0.49 745.28 01-APR-15:01 0.58
May 0.238037E+09 0.49 745.28 01-MAY-15:02 0.58
June 0.271719E+09 0.50 745.28 01-JUN-08:62 0.58
July 0.331134E+09 0.52 745.28 01-JUL-08:62 0.58
August 0.349031E+09 0.53 745.28 01-AUG-08:62 0.58
September 0.292884E+09 0.52 745.28 01-SEP-15:02 0.58
October 0.181667E+09 0.44 745.28 01-OCT-08:62 0.58
November 0.203876E+09 0.42 745.28 01-NOV-08:61 0.58
December 0.280342E+09 0.46 745.28 01-DEC-09:01 0.58
           
Annual Sum or Average 0.301171E+10 0.47      
Minimum of Months 0.181667E+09 0.41 745.28   0.58
Maximum of Months 0.349031E+09 0.53 745.28   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.252129E+09 0.46 666.59 01-JAN-09:01 0.58
February 0.206497E+09 0.43 666.59 01-FEB-09:01 0.58
March 0.191211E+09 0.42 666.59 01-MAR-09:01 0.58
April 0.179312E+09 0.45 666.59 03-APR-08:62 0.58
May 0.193259E+09 0.45 666.59 01-MAY-15:02 0.58
June 0.237632E+09 0.48 666.59 01-JUN-08:62 0.58
July 0.282302E+09 0.51 666.59 01-JUL-08:62 0.58
August 0.263640E+09 0.51 666.59 01-AUG-08:62 0.58
September 0.183117E+09 0.47 666.59 01-SEP-15:02 0.58
October 0.152732E+09 0.41 666.59 01-OCT-08:62 0.58
November 0.211651E+09 0.43 666.59 01-NOV-08:61 0.58
December 0.284579E+09 0.50 666.59 01-DEC-09:01 0.58
           
Annual Sum or Average 0.263806E+10 0.46      
Minimum of Months 0.152732E+09 0.41 666.59   0.58
Maximum of Months 0.284579E+09 0.51 666.59   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 77852485.32 0.46 217.45 01-JAN-09:01 0.58
February 63653856.35 0.45 217.45 01-FEB-09:01 0.58
March 63465141.15 0.43 217.45 01-MAR-09:01 0.58
April 66192556.63 0.47 217.45 01-APR-08:62 0.58
May 68512224.42 0.47 217.45 01-MAY-15:02 0.58
June 77951359.38 0.49 217.45 01-JUN-15:02 0.58
July 94421272.46 0.50 217.45 01-JUL-15:02 0.58
August 82902814.43 0.51 217.45 01-AUG-15:02 0.58
September 66935228.53 0.49 217.45 01-SEP-15:02 0.58
October 56482606.17 0.44 217.45 01-OCT-15:02 0.58
November 67609248.71 0.45 217.45 01-NOV-08:61 0.58
December 93550265.60 0.51 217.45 01-DEC-09:01 0.58
           
Annual Sum or Average 0.879529E+09 0.47      
Minimum of Months 56482606.17 0.43 217.45   0.58
Maximum of Months 94421272.46 0.51 217.45   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 82145867.41 0.50 191.29 01-JAN-09:01 0.58
February 65074145.81 0.47 191.29 01-FEB-09:01 0.58
March 61894150.29 0.43 191.29 01-MAR-09:01 0.58
April 53627618.63 0.43 191.29 01-APR-08:62 0.58
May 57307971.55 0.44 191.29 01-MAY-15:02 0.58
June 68680307.36 0.46 191.29 01-JUN-15:02 0.58
July 81393066.67 0.48 191.29 01-JUL-15:02 0.58
August 61226004.02 0.46 191.29 01-AUG-15:02 0.58
September 43761077.01 0.44 191.29 01-SEP-15:02 0.58
October 51806854.09 0.42 191.29 01-OCT-15:02 0.58
November 69456357.55 0.47 191.29 01-NOV-08:61 0.58
December 93564625.28 0.55 191.29 01-DEC-09:01 0.58
           
Annual Sum or Average 0.789938E+09 0.46      
Minimum of Months 43761077.01 0.42 191.29   0.58
Maximum of Months 93564625.28 0.55 191.29   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.319704E+09 0.45 1197.49 01-JAN-16:01 0.58
February 0.274796E+09 0.45 1197.49 01-FEB-09:01 0.58
March 0.251009E+09 0.42 1197.49 01-MAR-09:01 0.58
April 0.382912E+09 0.50 1197.49 01-APR-15:01 0.58
May 0.317926E+09 0.48 1197.49 01-MAY-15:02 0.58
June 0.336106E+09 0.49 1197.49 01-JUN-15:02 0.58
July 0.427732E+09 0.50 1197.49 01-JUL-08:62 0.58
August 0.492754E+09 0.51 1197.49 01-AUG-15:02 0.58
September 0.525084E+09 0.52 1197.49 01-SEP-15:02 0.58
October 0.321780E+09 0.46 1197.49 01-OCT-08:62 0.58
November 0.269314E+09 0.44 1197.49 01-NOV-08:61 0.58
December 0.370961E+09 0.46 1197.49 01-DEC-09:01 0.58
           
Annual Sum or Average 0.429008E+10 0.47      
Minimum of Months 0.251009E+09 0.42 1197.49   0.58
Maximum of Months 0.525084E+09 0.52 1197.49   0.58



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.587585E+09 0.528826E+09 666.74 22-JAN-19:02 600.06 600.06 38.83 1.12
February 0.461002E+09 0.414902E+09 685.66 01-FEB-09:03 617.10 617.10 43.30 1.18
March 0.461616E+09 0.415455E+09 668.60 01-MAR-16:02 601.74 601.74 45.35 1.12
April 0.210153E+09 0.189138E+09 620.46 10-APR-08:62 558.42 558.42 55.66 0.97
May 0.232284E+09 0.209056E+09 548.74 14-MAY-23:33 493.87 493.87 43.73 0.79
June 98904963.35 89014467.02 530.84 08-JUN-00:50 477.76 477.76 51.46 0.75
July 62990646.19 56691581.57 541.29 05-JUL-04:43 487.16 487.16 63.33 0.77
August 39630984.69 35667886.22 462.34 24-AUG-04:50 416.10 416.10 54.74 0.61
September 0.111803E+09 0.100622E+09 549.27 20-SEP-00:33 494.34 494.34 56.59 0.79
October 0.371631E+09 0.334468E+09 651.92 30-OCT-08:61 586.72 586.72 35.74 1.07
November 0.545896E+09 0.491306E+09 680.74 30-NOV-19:02 612.66 612.66 38.91 1.17
December 0.689923E+09 0.620931E+09 667.54 16-DEC-19:03 600.79 600.79 44.27 1.12
                 
Annual Sum or Average 0.387342E+10 0.348608E+10            
Minimum of Months 39630984.69 35667886.22 462.34   416.10 416.10 35.74 0.61
Maximum of Months 0.689923E+09 0.620931E+09 685.66   617.10 617.10 63.33 1.18



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.161622E+09 0.145460E+09 1555.18 21-JAN-16:02 1399.66 1399.66 8.40 2.75
February 0.172611E+09 0.155350E+09 1891.95 27-FEB-16:04 1702.75 1702.75 8.40 3.52
March 0.196678E+09 0.177010E+09 1950.63 20-MAR-18:02 1755.56 1755.56 8.40 3.66
April 0.219036E+10 0.197132E+10 3866.09 28-APR-15:20 3479.48 3479.48 7.73 13.75
May 0.247933E+10 0.223140E+10 3828.52 21-MAY-18:03 3445.67 3445.67 7.76 13.17
June 0.375666E+10 0.338099E+10 4154.56 25-JUN-18:03 3739.10 3739.10 7.48 18.19
July 0.483253E+10 0.434928E+10 3952.16 22-JUL-18:03 3556.94 3556.94 6.73 15.19
August 0.524468E+10 0.472022E+10 4085.58 14-AUG-18:03 3677.02 3677.02 6.76 17.31
September 0.390430E+10 0.351387E+10 3916.56 25-SEP-16:30 3524.91 3524.91 7.51 14.58
October 0.107369E+10 0.966320E+09 3342.51 07-OCT-15:02 3008.26 3008.26 7.90 8.69
November 0.159611E+09 0.143650E+09 1485.87 03-NOV-15:04 1337.28 1337.28 8.40 2.61
December 39189179.26 35270261.33 1414.94 20-DEC-09:04 1273.44 1273.44 8.40 2.46
                 
Annual Sum or Average 0.242113E+11 0.217901E+11            
Minimum of Months 39189179.26 35270261.33 1414.94   1273.44 1273.44 6.73 2.46
Maximum of Months 0.524468E+10 0.472022E+10 4154.56   3739.10 3739.10 8.40 18.19



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.353648E+10 0.318283E+10 3436.12 01-JAN-06:07 3092.51 3092.51 8.42 24.08
February 0.378632E+10 0.340769E+10 3436.12 01-FEB-00:15 3092.51 3092.51 8.40 24.08
March 0.360898E+10 0.324808E+10 3436.12 01-MAR-00:03 3092.51 3092.51 8.40 24.08
April 0.689455E+10 0.620509E+10 3436.12 01-APR-01:07 3092.51 3092.51 8.40 24.08
May 0.767084E+10 0.690375E+10 3436.12 01-MAY-00:10 3092.51 3092.51 8.60 24.08
June 0.850824E+10 0.765742E+10 3436.12 01-JUN-00:05 3092.51 3092.51 8.50 24.08
July 0.904507E+10 0.814056E+10 3436.12 01-JUL-00:10 3092.51 3092.51 8.48 24.08
August 0.918475E+10 0.826627E+10 3436.12 01-AUG-00:05 3092.51 3092.51 8.54 24.08
September 0.860129E+10 0.774116E+10 3436.12 01-SEP-00:05 3092.51 3092.51 8.53 24.08
October 0.538984E+10 0.485086E+10 3436.12 01-OCT-00:10 3092.51 3092.51 8.42 24.08
November 0.318063E+10 0.286257E+10 3436.12 01-NOV-00:10 3092.51 3092.51 8.40 24.08
December 0.331805E+10 0.298625E+10 3436.12 01-DEC-00:03 3092.51 3092.51 8.40 24.08
                 
Annual Sum or Average 0.727250E+11 0.654525E+11            
Minimum of Months 0.318063E+10 0.286257E+10 3436.12   3092.51 3092.51 8.40 24.08
Maximum of Months 0.918475E+10 0.826627E+10 3436.12   3092.51 3092.51 8.60 24.08



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:10 14.37 14.37 48.31 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:03 14.37 14.37 42.16 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:03 14.37 14.37 48.55 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 51.16 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:10 14.37 14.37 51.42 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:05 14.37 14.37 51.40 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 52.15 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:05 14.37 14.37 52.23 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:05 14.37 14.37 52.17 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 51.09 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:05 14.37 14.37 51.89 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:03 14.37 14.37 48.96 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 42.16 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 52.23 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 54.87 80.76 29376.19 212587.07 28-JAN-19:01
February 0.00 0.00 01-FEB-00:03 47.85 79.90 23887.61 209731.63 11-FEB-19:02
March 0.00 0.00 01-MAR-00:03 58.98 80.44 22280.13 195823.36 24-MAR-08:62
April 0.00 0.00 01-APR-00:10 62.07 80.37 11644.53 162322.30 07-APR-20:10
May 0.00 0.00 01-MAY-00:10 52.90 79.40 14148.39 141197.46 04-MAY-08:62
June 0.00 0.00 01-JUN-00:05 40.68 79.52 6927.07 119325.45 02-JUN-02:62
July 0.00 0.00 01-JUL-00:10 55.16 79.40 4113.66 116881.89 15-JUL-04:55
August 0.00 0.00 01-AUG-00:05 33.16 79.40 2674.83 115564.39 23-AUG-03:52
September 0.00 0.00 01-SEP-00:05 31.40 79.40 6876.94 118453.11 28-SEP-06:48
October 0.00 0.00 01-OCT-00:10 79.40 79.81 19717.55 197334.45 30-OCT-08:61
November 0.00 0.00 01-NOV-00:05 61.47 79.98 28743.51 204629.84 02-NOV-08:61
December 0.00 0.00 01-DEC-00:03 56.71 80.41 35001.64 203362.30 22-DEC-16:01
                 
Annual Sum or Average 0.00         17099.45    
Minimum of Months 0.00 0.00   31.40 79.40 2674.83 115564.39  
Maximum of Months 0.00 0.00   79.40 80.76 35001.64 212587.07  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 2155.84 45591.70 14-JAN-19:04 8.82 8.37 0.00 0.00 01-JAN-00:10
February 2579.46 52162.96 27-FEB-16:04 8.89 8.37 0.00 0.00 01-FEB-00:03
March 2186.25 49303.37 20-MAR-18:02 8.86 8.37 0.00 0.00 01-MAR-00:03
April 24628.18 346259.12 30-APR-18:02 10.54 7.11 0.00 0.00 01-APR-00:10
May 25235.59 337322.62 22-MAY-15:03 10.47 7.13 0.00 0.00 01-MAY-00:10
June 51259.72 530961.78 25-JUN-18:03 12.73 7.46 0.00 0.00 01-JUN-00:05
July 71736.37 421742.74 22-JUL-18:03 10.88 6.70 0.00 0.00 01-JUL-00:10
August 78253.69 391786.12 14-AUG-18:03 10.61 6.73 0.00 0.00 01-AUG-00:05
September 53690.43 353169.32 13-SEP-15:03 10.76 7.26 0.00 0.00 01-SEP-00:05
October 10404.84 205729.72 07-OCT-15:02 9.92 7.88 0.00 0.00 01-OCT-00:10
November 2006.30 44122.19 27-NOV-09:04 8.81 8.37 0.00 0.00 01-NOV-00:05
December 1429.63 53119.63 12-DEC-09:04 8.90 8.37 0.00 0.00 01-DEC-00:03
                 
Annual Sum or Average 27269.13         0.00    
Minimum of Months 1429.63 44122.19   8.81 6.70 0.00 0.00  
Maximum of Months 78253.69 530961.78   12.73 8.37 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 48.31 59.41 28081.71 67034.34 28-JAN-08:33
February 0.00 0.00 01-FEB-00:03 42.16 58.23 28271.67 66637.72 07-FEB-21:31
March 0.00 0.00 01-MAR-00:03 48.55 59.43 28087.32 65153.25 18-MAR-07:26
April 0.00 0.00 01-APR-00:10 51.16 58.45 27559.30 67660.37 07-APR-06:51
May 0.00 0.00 01-MAY-00:10 51.42 58.56 26854.17 67159.76 09-MAY-06:11
June 0.00 0.00 01-JUN-00:05 51.40 58.43 26183.38 63646.51 08-JUN-06:51
July 0.00 0.00 01-JUL-00:10 52.15 59.04 25654.08 59053.09 03-JUL-06:33
August 0.00 0.00 01-AUG-00:05 52.23 59.58 25499.80 57821.05 24-AUG-06:06
September 0.00 0.00 01-SEP-00:05 52.17 59.26 25652.04 64079.85 21-SEP-06:41
October 0.00 0.00 01-OCT-00:10 51.09 58.75 26124.39 63426.96 13-OCT-06:05
November 0.00 0.00 01-NOV-00:05 51.89 59.39 26829.89 67407.83 22-NOV-07:41
December 0.00 0.00 01-DEC-00:03 48.96 58.79 27575.28 64219.06 20-DEC-21:01
                 
Annual Sum or Average 0.00         26856.23    
Minimum of Months 0.00 0.00   42.16 58.23 25499.80 57821.05  
Maximum of Months 0.00 0.00   52.23 59.58 28271.67 67660.37  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.372637E+11 0.00 0.360948E+09 0.333350E+11 0.00 0.00
February 0.262510E+11 0.00 0.319493E+09 0.302862E+11 0.00 0.00
March 0.351789E+11 0.00 0.330694E+09 0.342480E+11 0.00 0.00
April 0.251532E+11 0.00 0.154374E+11 0.343275E+11 0.00 0.00
May 0.349690E+11 0.00 0.156008E+11 0.361485E+11 0.00 0.00
June 0.176609E+11 0.00 0.493788E+11 0.353726E+11 0.00 0.00
July 0.107738E+11 0.00 0.848233E+11 0.368119E+11 0.00 0.00
August 0.708862E+10 0.00 0.987290E+11 0.368135E+11 0.00 0.00
September 0.168676E+11 0.00 0.507377E+11 0.353651E+11 0.00 0.00
October 0.407733E+11 0.00 0.286056E+10 0.355904E+11 0.00 0.00
November 0.455429E+11 0.00 0.349138E+09 0.337177E+11 0.00 0.00
December 0.368179E+11 0.00 0.396484E+09 0.332647E+11 0.00 0.00
             
Annual Sum or Average 0.334341E+12 0.00 0.319324E+12 0.415281E+12 0.00 0.00
Minimum of Months 0.708862E+10 0.00 0.319493E+09 0.302862E+11 0.00 0.00
Maximum of Months 0.455429E+11 0.00 0.987290E+11 0.368135E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.880954E+09 0.00 0.00 0.587890E+10 0.00 0.00
February 0.323295E+09 0.00 3613.89 0.530997E+10 0.00 0.00
March 46657304.37 0.00 79458.00 0.587890E+10 0.00 0.00
April 20120.17 0.00 0.245803E+10 0.568926E+10 0.00 0.00
May 14233.75 0.00 0.246120E+10 0.587890E+10 0.00 0.00
June 36599.22 0.00 0.824314E+10 0.568926E+10 0.00 0.00
July 68507.53 0.00 0.146576E+11 0.587890E+10 0.00 0.00
August 80210.62 0.00 0.178130E+11 0.587890E+10 0.00 0.00
September 42749.05 0.00 0.918905E+10 0.568926E+10 0.00 0.00
October 8237.89 0.00 0.434600E+09 0.587890E+10 0.00 0.00
November 78492326.62 0.00 6967765.75 0.568926E+10 0.00 0.00
December 0.436298E+09 0.00 32372.43 0.587890E+10 0.00 0.00
             
Annual Sum or Average 0.176597E+10 0.00 0.552637E+11 0.692193E+11 0.00 0.00
Minimum of Months 8237.89 0.00 0.00 0.530997E+10 0.00 0.00
Maximum of Months 0.880954E+09 0.00 0.178130E+11 0.587890E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.333350E+11 0.361101E+09 0.372637E+11 0.428924E+12 0.00 0.00 0.00 0.00
February 0.302862E+11 0.319982E+09 0.262510E+11 0.391669E+12 0.00 0.00 0.00 0.00
March 0.342480E+11 0.330698E+09 0.351789E+11 0.347190E+12 0.00 0.00 0.00 0.00
April 0.343275E+11 0.154381E+11 0.251532E+11 0.204404E+12 0.00 0.00 0.00 0.00
May 0.361485E+11 0.156044E+11 0.349690E+11 0.150839E+12 0.00 0.00 0.00 0.00
June 0.353726E+11 0.493788E+11 0.176609E+11 0.504272E+11 89548480.57 0.00 0.00 0.00
July 0.368119E+11 0.848234E+11 0.107738E+11 0.284336E+11 0.345198E+09 0.00 0.00 0.00
August 0.368135E+11 0.987290E+11 0.708862E+10 0.210609E+11 0.00 0.00 0.00 0.00
September 0.353651E+11 0.507378E+11 0.168676E+11 0.550276E+11 0.00 0.00 0.00 0.00
October 0.355904E+11 0.286057E+10 0.407733E+11 0.169835E+12 0.00 0.00 0.00 0.00
November 0.337177E+11 0.349575E+09 0.455429E+11 0.287432E+12 0.00 0.00 0.00 0.00
December 0.332647E+11 0.396551E+09 0.368179E+11 0.444489E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.415281E+12 0.319330E+12 0.334341E+12 0.257973E+13 0.434747E+09 0.00 0.00 0.00
Minimum of Months 0.302862E+11 0.319982E+09 0.708862E+10 0.210609E+11 0.00 0.00 0.00 0.00
Maximum of Months 0.368135E+11 0.987290E+11 0.455429E+11 0.444489E+12 0.345198E+09 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.587890E+10 0.00 0.880954E+09 0.797516E+11 0.00 0.00 0.00 0.00
February 0.530997E+10 3613.89 0.323295E+09 0.723571E+11 0.00 0.00 0.00 0.00
March 0.587890E+10 79458.00 46657304.37 0.688351E+11 0.00 0.00 0.00 0.00
April 0.568926E+10 0.245803E+10 20120.17 0.456195E+11 0.00 0.00 0.00 0.00
May 0.587890E+10 0.246120E+10 14233.75 0.389594E+11 13751829.38 0.00 0.00 0.00
June 0.568926E+10 0.824314E+10 36599.22 0.171595E+11 0.338350E+09 0.00 0.00 0.00
July 0.587890E+10 0.146576E+11 68507.53 0.100637E+11 0.553901E+09 0.00 0.00 0.00
August 0.587890E+10 0.178130E+11 80210.62 0.707834E+10 69316573.73 0.00 0.00 0.00
September 0.568926E+10 0.918905E+10 42749.05 0.174022E+11 42466610.53 0.00 0.00 0.00
October 0.587890E+10 0.434600E+09 8237.89 0.426165E+11 0.00 0.00 0.00 0.00
November 0.568926E+10 6967765.75 78492326.62 0.606083E+11 0.00 0.00 0.00 0.00
December 0.587890E+10 32372.43 0.436298E+09 0.816287E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.692193E+11 0.552637E+11 0.176597E+10 0.542080E+12 0.101779E+10 0.00 0.00 0.00
Minimum of Months 0.530997E+10 0.00 8237.89 0.707834E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.178130E+11 0.880954E+09 0.816287E+11 0.553901E+09 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.333350E+11 0.372637E+11 0.360948E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.302862E+11 0.262510E+11 0.319493E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.342480E+11 0.351789E+11 0.330694E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.343275E+11 0.251532E+11 0.154374E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.361485E+11 0.349690E+11 0.156008E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.353726E+11 0.176609E+11 0.493788E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.368119E+11 0.107738E+11 0.848233E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.368135E+11 0.708862E+10 0.987290E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.353651E+11 0.168676E+11 0.507377E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.355904E+11 0.407733E+11 0.286056E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.337177E+11 0.455429E+11 0.349138E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.332647E+11 0.368179E+11 0.396484E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.415281E+12 0.334341E+12 0.319324E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.302862E+11 0.708862E+10 0.319493E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.368135E+11 0.455429E+11 0.987290E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.587890E+10 0.880954E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.530997E+10 0.323295E+09 3613.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.587890E+10 46657304.37 79458.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.568926E+10 20120.17 0.245803E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.587890E+10 14233.75 0.246120E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.568926E+10 36599.22 0.824314E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.587890E+10 68507.53 0.146576E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.587890E+10 80210.62 0.178130E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.568926E+10 42749.05 0.918905E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.587890E+10 8237.89 0.434600E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.568926E+10 78492326.62 6967765.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.587890E+10 0.436298E+09 32372.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.692193E+11 0.176597E+10 0.552637E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.530997E+10 8237.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.880954E+09 0.178130E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.339108E+11 0.00 0.00 12233490.72 0.00 0.00 0.128744E+11 0.00 0.91
February 0.339826E+11 0.00 0.00 6330631.60 0.00 0.00 0.775520E+10 0.00 0.90
March 0.422570E+11 0.00 0.00 2044747.37 0.00 0.00 0.459949E+10 0.00 0.89
April 0.428430E+11 0.00 0.00 1175052.82 0.00 0.00 0.370095E+10 0.00 0.89
May 0.450154E+11 0.00 0.00 1545512.74 0.00 0.00 0.403058E+10 0.00 0.89
June 0.383115E+11 0.00 0.00 2320189.55 40547720.48 0.00 0.568545E+10 0.00 0.92
July 0.320925E+11 0.00 0.00 6604482.14 122874.94 0.00 0.100450E+11 0.00 0.94
August 0.249788E+11 0.00 0.00 10647577.58 0.00 0.00 0.160152E+11 0.00 0.96
September 0.175424E+11 0.00 0.00 24960481.81 0.00 0.00 0.279203E+11 0.00 0.95
October 0.191157E+11 0.00 0.00 56016263.70 0.00 0.00 0.333286E+11 0.00 0.94
November 0.164298E+11 0.00 0.00 59234782.30 0.00 0.00 0.333745E+11 0.00 0.94
December 0.182366E+11 0.00 0.00 29610856.83 0.00 0.00 0.284864E+11 0.00 0.93
                   
Annual Sum or Average 0.364716E+12 0.00 0.00 0.212724E+09 40670595.43 0.00 0.187816E+12 0.00 0.92
Minimum of Months 0.164298E+11 0.00 0.00 1175052.82 0.00 0.00 0.370095E+10 0.00 0.89
Maximum of Months 0.450154E+11 0.00 0.00 59234782.30 40547720.48 0.00 0.333745E+11 0.00 0.96



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.670089E+10 0.00 0.00 110159.27 0.00 0.178193E+10 0.164554E+09 0.00 3.02
February 0.662173E+10 0.00 0.00 293673.66 0.00 0.895481E+09 0.243612E+09 0.00 3.03
March 0.806819E+10 0.00 0.00 0.00 0.00 0.646234E+09 0.00 0.00 2.99
April 0.793803E+10 0.00 0.00 975984.30 0.00 21191632.48 0.720835E+09 0.00 3.02
May 0.866100E+10 0.00 0.00 367741.32 0.00 30729354.02 0.432113E+09 0.00 2.99
June 0.789724E+10 0.00 0.00 331373.84 7543202.96 1023928.89 0.286733E+09 0.00 3.09
July 0.730682E+10 24114.05 0.00 843866.40 0.00 3963682.53 0.526249E+09 0.00 3.17
August 0.684114E+10 0.00 0.00 1748727.74 0.00 0.00 0.775829E+09 0.00 3.24
September 0.713438E+10 0.00 0.00 2549056.00 0.00 2527099.59 0.120665E+10 0.00 3.23
October 0.856655E+10 0.00 0.00 822014.07 0.00 64491542.43 0.643436E+09 0.00 3.02
November 0.788670E+10 0.00 0.00 119101.15 0.00 0.667486E+09 0.133690E+09 0.00 2.98
December 0.479415E+10 0.00 0.00 11651.77 0.00 0.361803E+10 31647740.63 0.00 3.04
                   
Annual Sum or Average 0.884168E+11 24114.05 0.00 8173349.52 7543202.96 0.773309E+10 0.516535E+10 0.00 3.07
Minimum of Months 0.479415E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.98
Maximum of Months 0.866100E+10 24114.05 0.00 2549056.00 7543202.96 0.361803E+10 0.120665E+10 0.00 3.24



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.436431E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.32
February 0.391324E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.32
March 0.439716E+10 0.00 0.00 76.86 0.00 0.00 1299155.78 0.00 1.31
April 0.383733E+10 0.00 0.00 384295.30 0.00 0.00 0.539861E+09 0.00 1.32
May 0.398010E+10 0.00 0.00 471751.26 0.00 0.00 0.636154E+09 0.00 1.31
June 0.310314E+10 490912.63 0.00 765446.76 3316395.54 0.00 0.104927E+10 0.00 1.36
July 0.257755E+10 11030.19 0.00 1211463.69 507.40 0.00 0.142603E+10 0.00 1.40
August 0.226793E+10 0.00 0.00 1289251.07 0.00 0.00 0.161281E+10 0.00 1.42
September 0.289141E+10 0.00 0.00 977042.92 0.00 0.00 0.130056E+10 0.00 1.38
October 0.437385E+10 0.00 0.00 299318.94 0.00 0.00 0.288315E+09 0.00 1.31
November 0.438397E+10 0.00 0.00 199.73 0.00 0.00 764983.84 0.00 1.30
December 0.426172E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.33
                   
Annual Sum or Average 0.443517E+11 501942.82 0.00 5398846.54 3316902.94 0.00 0.685507E+10 0.00 1.34
Minimum of Months 0.226793E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.30
Maximum of Months 0.439716E+10 490912.63 0.00 1289251.07 3316395.54 0.00 0.161281E+10 0.00 1.42



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.384694E+10 0.00 0.00 0.00 0.00 35235924.20 0.00 0.00 0.55
February 0.348072E+10 0.00 0.00 0.00 0.00 217715.21 0.00 0.00 0.55
March 0.391201E+10 0.00 0.00 0.00 0.00 546974.70 0.00 0.00 0.55
April 0.388654E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.55
May 0.409646E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.55
June 0.364695E+10 0.00 0.00 12887.37 3386709.85 0.00 28033130.47 0.00 0.57
July 0.338277E+10 0.00 0.00 84274.13 10263.01 0.00 0.135477E+09 0.00 0.58
August 0.334549E+10 0.00 0.00 19864.95 0.00 0.00 63168224.82 0.00 0.59
September 0.369236E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.58
October 0.414294E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.55
November 0.389998E+10 0.00 0.00 0.00 0.00 360870.57 0.00 0.00 0.55
December 0.378936E+10 0.00 0.00 0.00 0.00 1561664.61 0.00 0.00 0.56
                   
Annual Sum or Average 0.451225E+11 0.00 0.00 117026.45 3396972.86 37923149.29 0.226679E+09 0.00 0.56
Minimum of Months 0.334549E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.55
Maximum of Months 0.414294E+10 0.00 0.00 84274.13 3386709.85 35235924.20 0.135477E+09 0.00 0.59



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.157914E+10 0.00 0.00 0.00 0.00 0.274054E+09 0.00 0.00 0.46
February 0.164330E+10 0.00 0.00 0.00 0.00 18360589.16 0.00 0.00 0.46
March 0.185839E+10 0.00 0.00 0.00 0.00 9304083.81 0.00 0.00 0.45
April 0.185527E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.46
May 0.195548E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45
June 0.175429E+10 0.00 0.00 0.00 1616676.19 0.00 0.00 0.00 0.47
July 0.167938E+10 0.00 0.00 0.00 4899.14 0.00 0.00 0.00 0.48
August 0.162716E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.49
September 0.176258E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.48
October 0.197767E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45
November 0.182965E+10 0.00 0.00 0.00 0.00 32215687.73 0.00 0.00 0.45
December 0.155018E+10 0.00 0.00 0.00 0.00 0.259446E+09 0.00 0.00 0.46
                   
Annual Sum or Average 0.210725E+11 0.00 0.00 0.00 1621575.33 0.593381E+09 0.00 0.00 0.46
Minimum of Months 0.155018E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45
Maximum of Months 0.197767E+10 0.00 0.00 0.00 1616676.19 0.274054E+09 0.00 0.00 0.49



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.819983E+09 0.00 0.00 0.130052E+09 0.00 0.00 0.697467E+11 0.00 20.86
February 0.113024E+10 0.00 0.00 0.121836E+09 0.00 0.00 0.622782E+11 0.00 20.94
March 0.106660E+10 0.00 0.00 0.152121E+09 0.00 0.00 0.705964E+11 0.00 20.82
April 0.716287E+09 0.00 0.00 0.155063E+09 0.00 0.00 0.703961E+11 0.00 20.86
May 0.226192E+10 0.00 0.00 0.160074E+09 0.00 0.00 0.727521E+11 0.00 20.92
June 0.145429E+10 64995547.87 0.00 0.108100E+09 0.00 0.00 0.658350E+11 0.00 21.66
July 0.105785E+10 159212.89 0.00 0.108111E+09 0.00 0.00 0.631457E+11 0.00 22.13
August 0.610908E+09 0.00 0.00 0.103830E+09 0.00 0.00 0.621627E+11 0.00 22.65
September 0.154266E+10 0.00 0.00 0.109215E+09 0.00 0.00 0.665123E+11 0.00 21.91
October 0.154913E+10 0.00 0.00 0.168423E+09 0.00 0.00 0.741832E+11 0.00 20.84
November 0.174438E+10 0.00 0.00 0.167737E+09 0.00 0.00 0.696224E+11 0.00 20.75
December 0.675407E+09 0.00 0.00 0.125908E+09 0.00 0.00 0.680663E+11 0.00 20.96
                   
Annual Sum or Average 0.146296E+11 65154760.76 0.00 0.161047E+10 0.00 0.00 0.815297E+12 0.00 21.28
Minimum of Months 0.610908E+09 0.00 0.00 0.103830E+09 0.00 0.00 0.621627E+11 0.00 20.75
Maximum of Months 0.226192E+10 64995547.87 0.00 0.168423E+09 0.00 0.00 0.741832E+11 0.00 22.65



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.306168E+11 0.00 0.00 1556523.67 0.00 4800069.88 0.294703E+10 0.00 4.17
February 0.262410E+11 0.00 0.00 2785477.09 0.00 3887450.62 0.388587E+10 0.00 4.19
March 0.318405E+11 0.00 0.00 238717.71 0.00 1401208.55 0.196298E+10 0.00 4.13
April 0.180209E+11 0.00 0.00 10516211.19 0.00 0.00 0.156871E+11 0.00 4.18
May 0.219398E+11 0.00 0.00 7534323.04 0.00 3181284.40 0.135039E+11 0.00 4.15
June 0.157096E+11 18904871.37 0.00 8731283.37 10356813.23 0.00 0.160500E+11 0.00 4.28
July 0.124232E+11 91057.40 0.00 14179733.30 0.00 0.00 0.179667E+11 0.00 4.38
August 0.793825E+10 0.00 0.00 20052833.88 0.00 0.00 0.215930E+11 0.00 4.49
September 0.113744E+11 0.00 0.00 21574552.44 0.00 0.00 0.209914E+11 0.00 4.46
October 0.242841E+11 0.00 0.00 7861178.75 0.00 0.00 0.117409E+11 0.00 4.18
November 0.297920E+11 0.00 0.00 1744045.60 0.00 2743065.10 0.391670E+10 0.00 4.12
December 0.318687E+11 0.00 0.00 335878.10 0.00 7508237.05 0.881709E+09 0.00 4.20
                   
Annual Sum or Average 0.262049E+12 18995928.77 0.00 97110758.13 10356813.23 23521315.60 0.131127E+12 0.00 4.24
Minimum of Months 0.793825E+10 0.00 0.00 238717.71 0.00 0.00 0.881709E+09 0.00 4.12
Maximum of Months 0.318687E+11 18904871.37 0.00 21574552.44 10356813.23 7508237.05 0.215930E+11 0.00 4.49



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.846168E+11 0.00 0.00 2387563.33 0.00 0.00 0.753266E+10 0.00 1.66
February 0.730844E+11 0.00 0.00 2707927.03 0.00 0.00 0.952250E+10 0.00 1.66
March 0.827446E+11 0.00 0.00 3523460.57 0.00 0.00 0.101316E+11 0.00 1.64
April 0.515504E+11 0.00 0.00 35432231.26 0.00 0.00 0.414432E+11 0.00 1.66
May 0.570835E+11 0.00 0.00 42949676.23 0.00 0.00 0.415243E+11 0.00 1.67
June 0.382709E+11 11728959.71 0.00 48513361.15 68643844.10 0.00 0.503403E+11 0.00 1.73
July 0.296376E+11 232848.80 0.00 59110279.68 10711.22 0.00 0.559025E+11 0.00 1.78
August 0.188464E+11 0.00 0.00 68957979.78 0.00 0.00 0.645719E+11 0.00 1.81
September 0.275590E+11 0.00 0.00 68871375.75 0.00 0.00 0.625272E+11 0.00 1.76
October 0.652771E+11 0.00 0.00 30095933.46 0.00 0.00 0.337043E+11 0.00 1.66
November 0.807952E+11 0.00 0.00 4672920.07 0.00 0.00 0.118175E+11 0.00 1.64
December 0.867236E+11 0.00 0.00 607603.43 0.00 0.00 0.324122E+10 0.00 1.67
                   
Annual Sum or Average 0.696190E+12 11961808.51 0.00 0.367830E+09 68654555.33 0.00 0.392259E+12 0.00 1.69
Minimum of Months 0.188464E+11 0.00 0.00 607603.43 0.00 0.00 0.324122E+10 0.00 1.64
Maximum of Months 0.867236E+11 11728959.71 0.00 68957979.78 68643844.10 0.00 0.645719E+11 0.00 1.81



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.378634E+09 0.00 0.00 352466.24 0.00 0.112937E+10 34164977.01 0.00 0.47
February 0.362551E+09 0.00 0.00 1499903.35 0.00 0.943200E+09 0.102880E+09 0.00 0.47
March 0.402834E+09 0.00 0.00 611295.97 0.00 0.100929E+10 74129565.99 0.00 0.47
April 0.312339E+09 0.00 0.00 10549709.37 89770.19 0.423426E+09 0.919250E+09 0.00 0.47
May 0.330927E+09 162612.33 0.00 12379810.96 0.00 0.304647E+09 0.107337E+10 0.00 0.47
June 0.227356E+09 11305024.12 0.00 13750666.34 119915.91 22302571.91 0.124967E+10 0.00 0.47
July 0.183762E+09 6805423.24 1326.19 15384878.22 440795.86 35456219.88 0.114384E+10 2621.90 0.47
August 0.118054E+09 4390133.53 0.00 15216831.45 271973.60 1763647.62 0.116997E+10 0.00 0.47
September 0.210170E+09 2299999.58 0.00 11790149.34 28233.13 95427828.26 0.118870E+10 0.00 0.47
October 0.384140E+09 0.00 0.00 3897291.65 0.00 0.809655E+09 0.480221E+09 0.00 0.47
November 0.392040E+09 0.00 0.00 467680.52 0.00 0.105962E+10 43938791.87 0.00 0.47
December 0.279065E+09 0.00 0.00 50503.15 0.00 0.113242E+10 5093239.90 0.00 0.47
                   
Annual Sum or Average 0.358187E+10 24963192.80 1326.19 85951186.57 950688.70 0.696657E+10 0.748523E+10 2621.90 0.47
Minimum of Months 0.118054E+09 0.00 0.00 50503.15 0.00 1763647.62 5093239.90 0.00 0.47
Maximum of Months 0.402834E+09 11305024.12 1326.19 15384878.22 440795.86 0.113242E+10 0.124967E+10 2621.90 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.333317E+09 0.00 0.00 101198.76 0.00 0.120061E+10 8310208.51 0.00 0.47
February 0.374754E+09 0.00 0.00 414304.88 0.00 0.997165E+09 37631582.54 0.00 0.47
March 0.401307E+09 0.00 0.00 349274.41 0.00 0.103938E+10 45658314.03 0.00 0.47
April 0.420355E+09 0.00 0.00 6887609.37 89759.68 0.559623E+09 0.678504E+09 0.00 0.47
May 0.414929E+09 162593.28 0.00 9929256.02 0.00 0.362988E+09 0.933280E+09 0.00 0.47
June 0.291353E+09 11300253.18 0.00 12590754.48 123348.26 23823754.59 0.118513E+10 0.00 0.47
July 0.237520E+09 6639601.72 3148.62 13810693.09 605768.38 39330078.58 0.108762E+10 799.01 0.47
August 0.185114E+09 3600593.86 0.00 12069649.66 1060967.03 1739366.53 0.110593E+10 0.00 0.47
September 0.315145E+09 2282783.77 0.00 7213225.84 45176.15 0.180959E+09 0.100259E+10 0.00 0.47
October 0.455514E+09 0.00 0.00 1695145.72 0.00 0.990113E+09 0.230394E+09 0.00 0.47
November 0.382317E+09 0.00 0.00 126268.01 0.00 0.109932E+10 14124704.96 0.00 0.47
December 0.218760E+09 0.00 0.00 62344.69 0.00 0.119397E+10 3661721.77 0.00 0.47
                   
Annual Sum or Average 0.403039E+10 23985825.81 3148.62 65249724.93 1925019.49 0.768903E+10 0.633284E+10 799.01 0.47
Minimum of Months 0.185114E+09 0.00 0.00 62344.69 0.00 1739366.53 3661721.77 0.00 0.47
Maximum of Months 0.455514E+09 11300253.18 3148.62 13810693.09 1060967.03 0.120061E+10 0.118513E+10 799.01 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.183558E+11 0.00 0.00 5154875.04 0.00 0.164281E+10 0.911384E+09 0.00 0.53
February 0.171490E+11 0.00 0.00 4550405.49 0.00 0.109751E+10 0.869038E+09 0.00 0.54
March 0.187631E+11 0.00 0.00 0.00 0.00 0.139753E+10 0.00 0.00 0.53
April 0.134091E+11 145515.36 0.00 61653615.85 1071687.96 0.00 0.911283E+10 0.00 0.54
May 0.144191E+11 2204877.37 0.00 45232021.68 0.00 0.00 0.887531E+10 0.00 0.54
June 0.931188E+10 0.154912E+09 0.00 47774088.37 0.00 0.00 0.111563E+11 0.00 0.54
July 0.710876E+10 98305764.60 0.00 58722040.04 0.00 0.00 0.115230E+11 0.00 0.54
August 0.611545E+10 63213991.25 0.00 80382872.95 0.00 0.00 0.114989E+11 0.00 0.54
September 0.670724E+10 31568747.39 0.00 96146071.98 0.00 0.00 0.136178E+11 0.00 0.54
October 0.174211E+11 0.00 0.00 37387986.84 0.00 0.00 0.529251E+10 0.00 0.54
November 0.190281E+11 0.00 0.00 2240497.52 0.00 0.815741E+09 0.439225E+09 0.00 0.53
December 0.114335E+11 0.00 0.00 0.00 0.00 0.777471E+10 0.00 0.00 0.53
                   
Annual Sum or Average 0.159222E+12 0.350351E+09 0.00 0.439244E+09 1071687.96 0.127283E+11 0.732963E+11 0.00 0.54
Minimum of Months 0.611545E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.53
Maximum of Months 0.190281E+11 0.154912E+09 0.00 96146071.98 1071687.96 0.777471E+10 0.136178E+11 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.563450E+10 0.00 0.00 8646601.49 0.00 0.100097E+11 0.526805E+10 0.00 0.53
February 0.524788E+10 0.00 0.00 7882099.00 0.00 0.917052E+10 0.469905E+10 0.00 0.54
March 0.553004E+10 0.00 0.00 25708297.94 0.00 0.371283E+10 0.108976E+11 0.00 0.53
April 0.647565E+10 0.00 0.00 71016315.40 1217536.16 0.143433E+09 0.158996E+11 0.00 0.54
May 0.673179E+10 435300.28 0.00 0.100592E+09 1770180.02 53013311.29 0.164606E+11 0.00 0.53
June 0.535615E+10 80821507.19 0.00 0.103480E+09 74132793.30 16758368.94 0.150452E+11 0.00 0.54
July 0.448608E+10 58124404.14 0.00 0.103406E+09 40208242.00 17581027.77 0.140885E+11 0.00 0.54
August 0.352418E+10 14793838.74 0.00 83934355.08 48437438.26 21939753.77 0.140695E+11 0.00 0.54
September 0.486719E+10 20790709.74 229786.54 67942544.24 10553629.67 42568699.23 0.154491E+11 3253.86 0.54
October 0.634740E+10 0.00 0.00 43192446.30 0.00 0.289193E+09 0.160774E+11 0.00 0.54
November 0.552771E+10 0.00 0.00 19126158.07 0.00 0.633812E+10 0.840586E+10 0.00 0.53
December 0.505277E+10 0.00 0.00 4109524.86 0.00 0.115392E+11 0.261732E+10 0.00 0.54
                   
Annual Sum or Average 0.647814E+11 0.174966E+09 229786.54 0.639036E+09 0.176320E+09 0.413549E+11 0.138978E+12 3253.86 0.54
Minimum of Months 0.352418E+10 0.00 0.00 4109524.86 0.00 16758368.94 0.261732E+10 0.00 0.53
Maximum of Months 0.673179E+10 80821507.19 229786.54 0.103480E+09 74132793.30 0.115392E+11 0.164606E+11 3253.86 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.384347E+09 0.00 0.00 369910.72 0.00 0.110405E+10 53755636.67 0.00 0.47
February 0.384895E+09 0.00 0.00 802700.71 0.00 0.943923E+09 80510017.08 0.00 0.47
March 0.403429E+09 0.00 0.00 542317.88 0.00 0.100051E+10 82384599.45 0.00 0.47
April 0.232019E+09 89770.19 0.00 13252675.54 0.00 0.397735E+09 0.102256E+10 0.00 0.47
May 0.248760E+09 162612.33 0.00 13601173.84 0.00 0.304881E+09 0.115408E+10 0.00 0.47
June 0.179130E+09 10899449.65 0.00 13522111.19 525490.39 45488362.60 0.127494E+10 0.00 0.47
July 0.117528E+09 7014572.65 0.00 14968880.01 235594.54 19727870.45 0.122622E+10 0.00 0.47
August 83370984.71 4590298.81 0.00 16662258.36 71808.31 928170.70 0.120404E+10 0.00 0.47
September 0.136527E+09 2253820.83 0.00 14531839.05 74411.88 62751151.32 0.129228E+10 0.00 0.47
October 0.374277E+09 0.00 0.00 4269937.67 0.00 0.808046E+09 0.491320E+09 0.00 0.47
November 0.394435E+09 0.00 0.00 595455.83 0.00 0.104200E+10 59036365.79 0.00 0.47
December 0.285432E+09 0.00 0.00 142798.86 0.00 0.110632E+10 24728926.55 0.00 0.47
                   
Annual Sum or Average 0.322415E+10 25010524.46 0.00 93262059.67 907305.13 0.683636E+10 0.796586E+10 0.00 0.47
Minimum of Months 83370984.71 0.00 0.00 142798.86 0.00 928170.70 24728926.55 0.00 0.47
Maximum of Months 0.403429E+09 10899449.65 0.00 16662258.36 525490.39 0.110632E+10 0.129228E+10 0.00 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.325186E+09 0.00 0.00 106521.29 0.00 0.119825E+10 18792650.30 0.00 0.47
February 0.369086E+09 0.00 0.00 207679.29 0.00 0.100444E+10 36230991.07 0.00 0.47
March 0.401902E+09 0.00 0.00 262797.92 0.00 0.103657E+10 47963526.01 0.00 0.47
April 0.375470E+09 89759.68 0.00 8742785.93 0.00 0.500276E+09 0.780882E+09 0.00 0.47
May 0.366735E+09 162593.28 0.00 10783183.48 0.00 0.366980E+09 0.976626E+09 0.00 0.47
June 0.238676E+09 10843747.38 0.00 12171297.41 579854.06 53597741.67 0.120846E+10 0.00 0.47
July 0.135812E+09 6952213.39 0.00 13309374.31 297104.33 22814927.69 0.120634E+10 0.00 0.47
August 0.103331E+09 4578774.60 0.00 13292868.81 82786.29 4529720.95 0.118370E+10 0.00 0.47
September 0.238722E+09 2207613.11 0.00 9227084.70 120346.82 0.140581E+09 0.111738E+10 0.00 0.47
October 0.467945E+09 0.00 0.00 1666974.20 0.00 0.968684E+09 0.239420E+09 0.00 0.47
November 0.382525E+09 0.00 0.00 170611.29 0.00 0.108865E+10 24538167.34 0.00 0.47
December 0.225130E+09 0.00 0.00 72519.33 0.00 0.118634E+10 4917655.53 0.00 0.47
                   
Annual Sum or Average 0.363052E+10 24834701.43 0.00 70013697.95 1080091.50 0.757172E+10 0.684525E+10 0.00 0.47
Minimum of Months 0.103331E+09 0.00 0.00 72519.33 0.00 4529720.95 4917655.53 0.00 0.47
Maximum of Months 0.467945E+09 10843747.38 0.00 13309374.31 579854.06 0.119825E+10 0.120846E+10 0.00 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.276560E+11 0.00 0.00 0.00 0.00 0.481853E+09 0.00 0.00 0.55
February 0.252165E+11 0.00 0.00 0.00 0.00 13173494.17 0.00 0.00 0.55
March 0.283361E+11 0.00 0.00 0.00 0.00 21976125.11 0.00 0.00 0.54
April 0.281694E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.55
May 0.296909E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.55
June 0.266362E+11 0.00 0.00 0.00 24546706.56 0.00 0.00 0.00 0.57
July 0.254988E+11 0.00 0.00 0.00 74385.81 0.00 0.00 0.00 0.58
August 0.247060E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.59
September 0.267620E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.57
October 0.300263E+11 0.00 0.00 0.00 0.00 1510523.92 0.00 0.00 0.55
November 0.280812E+11 0.00 0.00 0.00 0.00 0.188280E+09 0.00 0.00 0.54
December 0.259474E+11 0.00 0.00 0.00 0.00 0.152903E+10 0.00 0.00 0.55
                   
Annual Sum or Average 0.326727E+12 0.00 0.00 0.00 24621092.37 0.223582E+10 0.00 0.00 0.56
Minimum of Months 0.247060E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.54
Maximum of Months 0.300263E+11 0.00 0.00 0.00 24546706.56 0.152903E+10 0.00 0.00 0.59



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 79251298.24 0.00 0.00 75615.17 0.00 0.302247E+09 4056423.52 0.00 0.47
February 82143820.84 0.00 0.00 363029.22 0.00 0.250697E+09 19329239.23 0.00 0.47
March 96543143.15 0.00 0.00 137882.15 0.00 0.262490E+09 12546550.43 0.00 0.47
April 76205212.24 0.00 0.00 2548993.61 22442.55 0.151599E+09 0.186038E+09 0.00 0.47
May 82170390.52 40653.08 0.00 2807515.74 0.00 0.132700E+09 0.212654E+09 0.00 0.47
June 55383046.57 2829264.56 0.00 3166342.60 26970.45 35497407.07 0.284223E+09 0.00 0.47
July 42912538.13 1704115.48 310.21 3684178.31 107439.30 32002750.69 0.266011E+09 676.81 0.47
August 29742786.46 1097614.79 0.00 3552312.24 67911.99 8708635.70 0.284247E+09 0.00 0.47
September 53257256.76 574999.90 0.00 2544172.14 7058.28 71980216.33 0.248741E+09 0.00 0.47
October 96701329.02 0.00 0.00 805223.37 0.00 0.243576E+09 78395528.24 0.00 0.47
November 88194480.26 0.00 0.00 102092.27 0.00 0.279765E+09 5954708.84 0.00 0.47
December 48964728.44 0.00 0.00 3178.24 0.00 0.305117E+09 71331.09 0.00 0.47
                   
Annual Sum or Average 0.831470E+09 6246647.81 310.21 19790535.06 231822.57 0.207638E+10 0.160227E+10 676.81 0.47
Minimum of Months 29742786.46 0.00 0.00 3178.24 0.00 8708635.70 71331.09 0.00 0.47
Maximum of Months 96701329.02 2829264.56 310.21 3684178.31 107439.30 0.305117E+09 0.284247E+09 676.81 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 56544916.47 0.00 0.00 14560.96 0.00 0.328148E+09 877929.52 0.00 0.47
February 73707438.80 0.00 0.00 77910.93 0.00 0.270586E+09 8120108.17 0.00 0.47
March 94313852.76 0.00 0.00 72089.06 0.00 0.269679E+09 7608443.54 0.00 0.47
April 0.103795E+09 0.00 0.00 1649377.47 22439.92 0.189854E+09 0.121044E+09 0.00 0.47
May 0.102892E+09 40648.32 0.00 2206570.98 0.00 0.150984E+09 0.174200E+09 0.00 0.47
June 69992476.74 2825814.16 0.00 2853517.66 30086.20 41482274.97 0.263897E+09 0.00 0.47
July 57314584.56 1673085.46 337.05 3260364.98 138257.06 34345659.63 0.249650E+09 649.86 0.47
August 44587646.23 989090.78 0.00 2720944.35 176299.44 18465287.09 0.260439E+09 0.00 0.47
September 79194738.32 572748.72 0.00 1452834.80 9241.26 0.122003E+09 0.173828E+09 0.00 0.47
October 0.112530E+09 0.00 0.00 327627.68 0.00 0.276667E+09 29904104.29 0.00 0.47
November 74138574.80 0.00 0.00 25746.48 0.00 0.298280E+09 1527898.05 0.00 0.47
December 24081127.15 0.00 0.00 1501.37 0.00 0.330018E+09 14178.49 0.00 0.47
                   
Annual Sum or Average 0.893092E+09 6101387.45 337.05 14663046.72 376323.88 0.233051E+10 0.129111E+10 649.86 0.47
Minimum of Months 24081127.15 0.00 0.00 1501.37 0.00 18465287.09 14178.49 0.00 0.47
Maximum of Months 0.112530E+09 2825814.16 337.05 3260364.98 176299.44 0.330018E+09 0.263897E+09 649.86 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.479603E+09 0.00 0.00 5511324.98 0.00 0.142747E+10 0.564887E+09 0.00 0.53
February 0.460764E+09 0.00 0.00 7940044.67 0.00 0.117071E+10 0.625430E+09 0.00 0.54
March 0.617301E+09 0.00 0.00 2610707.80 0.00 0.136244E+10 0.405746E+09 0.00 0.53
April 0.343826E+09 0.00 0.00 20842315.45 144181.91 0.469361E+09 0.184107E+10 0.00 0.54
May 0.455131E+09 261175.30 0.00 16706848.13 0.00 0.450256E+09 0.184257E+10 0.00 0.53
June 0.350721E+09 17582223.99 0.00 15664562.38 767627.38 60621812.82 0.200318E+10 0.00 0.54
July 0.278087E+09 10934882.96 2756.41 18273200.73 703431.39 36331203.92 0.188126E+10 3584.71 0.54
August 0.185015E+09 7282533.37 0.00 22219559.68 205381.01 3713984.18 0.188505E+10 0.00 0.54
September 0.242779E+09 3684426.91 0.00 23956339.05 54999.65 54573084.12 0.209766E+10 0.00 0.54
October 0.474231E+09 0.00 0.00 12883586.73 0.00 0.807956E+09 0.139986E+10 0.00 0.54
November 0.509897E+09 0.00 0.00 5305525.47 0.00 0.135637E+10 0.531292E+09 0.00 0.53
December 0.455945E+09 0.00 0.00 1623548.13 0.00 0.164427E+10 0.173430E+09 0.00 0.54
                   
Annual Sum or Average 0.485330E+10 39745242.52 2756.41 0.153538E+09 1875621.35 0.884407E+10 0.152514E+11 3584.71 0.54
Minimum of Months 0.185015E+09 0.00 0.00 1623548.13 0.00 3713984.18 0.173430E+09 0.00 0.53
Maximum of Months 0.617301E+09 17582223.99 2756.41 23956339.05 767627.38 0.164427E+10 0.209766E+10 3584.71 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.596093E+10 0.00 0.00 59862960.60 0.00 0.00 0.370414E+11 0.00 3.95
February 0.380643E+10 0.00 0.00 56678880.30 0.00 0.00 0.350186E+11 0.00 3.98
March 0.362147E+10 0.00 0.00 78042989.36 0.00 0.00 0.415318E+11 0.00 4.06
April 0.109515E+10 0.00 0.00 0.106310E+09 0.00 0.00 0.459740E+11 0.00 4.26
May 0.815389E+09 0.00 0.00 0.131620E+09 0.00 0.00 0.503530E+11 0.00 4.37
June 85628863.13 42111089.14 0.00 0.101669E+09 0.00 0.00 0.475543E+11 0.00 4.65
July 27911983.78 124970.15 0.00 0.100603E+09 0.00 0.00 0.463638E+11 0.00 4.82
August 36786587.93 0.00 0.00 91418087.23 0.00 0.00 0.449494E+11 0.00 4.85
September 0.292239E+09 0.00 0.00 93745915.15 0.00 0.00 0.460406E+11 0.00 4.53
October 0.277686E+10 0.00 0.00 0.105724E+09 0.00 0.00 0.460597E+11 0.00 4.14
November 0.490597E+10 0.00 0.00 86467106.53 0.00 0.00 0.398102E+11 0.00 4.02
December 0.610776E+10 0.00 0.00 53764880.35 0.00 0.00 0.355040E+11 0.00 3.94
                   
Annual Sum or Average 0.295325E+11 42236059.28 0.00 0.106591E+10 0.00 0.00 0.516201E+12 0.00 4.30
Minimum of Months 27911983.78 0.00 0.00 53764880.35 0.00 0.00 0.350186E+11 0.00 3.94
Maximum of Months 0.610776E+10 42111089.14 0.00 0.131620E+09 0.00 0.00 0.503530E+11 0.00 4.85



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.194042E+10 0.00 0.00 82450940.71 0.00 0.00 0.452494E+11 0.00 4.32
February 0.150359E+10 0.00 0.00 79326754.59 0.00 0.00 0.411682E+11 0.00 4.36
March 0.114620E+10 0.00 0.00 0.105731E+09 0.00 0.00 0.486515E+11 0.00 4.47
April 0.224025E+09 0.00 0.00 0.129506E+09 0.00 0.00 0.512775E+11 0.00 4.66
May 0.149599E+09 0.00 0.00 0.154745E+09 0.00 0.00 0.556600E+11 0.00 4.76
June 10405145.80 45701699.22 0.00 0.114631E+09 0.00 0.00 0.516039E+11 0.00 5.05
July 13045572.88 134710.71 0.00 0.112233E+09 0.00 0.00 0.500655E+11 0.00 5.21
August 2515519.06 0.00 0.00 0.102557E+09 0.00 0.00 0.484764E+11 0.00 5.23
September 35226565.03 0.00 0.00 0.107844E+09 0.00 0.00 0.502098E+11 0.00 4.91
October 0.734021E+09 0.00 0.00 0.133076E+09 0.00 0.00 0.527981E+11 0.00 4.53
November 0.173468E+10 0.00 0.00 0.117423E+09 0.00 0.00 0.473397E+11 0.00 4.39
December 0.219269E+10 0.00 0.00 75395425.17 0.00 0.00 0.434724E+11 0.00 4.31
                   
Annual Sum or Average 0.968643E+10 45836409.93 0.00 0.131492E+10 0.00 0.00 0.585972E+12 0.00 4.69
Minimum of Months 2515519.06 0.00 0.00 75395425.17 0.00 0.00 0.411682E+11 0.00 4.31
Maximum of Months 0.219269E+10 45701699.22 0.00 0.154745E+09 0.00 0.00 0.556600E+11 0.00 5.23



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 5481205.51 0.00 0.00 0.167127E+09 0.00 0.00 0.635821E+11 0.00 18.94
February 2761362.43 0.00 0.00 0.164916E+09 0.00 0.00 0.575024E+11 0.00 19.16
March 55887268.66 0.00 0.00 0.197538E+09 0.00 0.00 0.648602E+11 0.00 19.05
April 41790596.68 0.00 0.00 0.194650E+09 0.00 0.00 0.664845E+11 0.00 19.90
May 0.231238E+09 0.00 0.00 0.203824E+09 0.00 0.00 0.698693E+11 0.00 19.99
June 91612222.81 70640753.47 0.00 0.142992E+09 0.00 0.00 0.624620E+11 0.00 21.03
July 0.129078E+09 214044.05 0.00 0.140888E+09 0.00 0.00 0.594202E+11 0.00 21.63
August 22521284.55 0.00 0.00 0.135941E+09 0.00 0.00 0.571280E+11 0.00 22.00
September 0.175274E+09 0.00 0.00 0.141489E+09 0.00 0.00 0.623809E+11 0.00 21.23
October 0.222705E+09 0.00 0.00 0.198155E+09 0.00 0.00 0.690584E+11 0.00 19.39
November 0.131847E+09 0.00 0.00 0.214824E+09 0.00 0.00 0.639201E+11 0.00 18.83
December 0.00 0.00 0.00 0.157226E+09 0.00 0.00 0.614714E+11 0.00 18.93
                   
Annual Sum or Average 0.111020E+10 70854797.52 0.00 0.205957E+10 0.00 0.00 0.758139E+12 0.00 20.01
Minimum of Months 0.00 0.00 0.00 0.135941E+09 0.00 0.00 0.571280E+11 0.00 18.83
Maximum of Months 0.231238E+09 70640753.47 0.00 0.214824E+09 0.00 0.00 0.698693E+11 0.00 22.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.143902E+11 0.00 0.00 0.00 0.00 0.501797E+09 0.00 0.00 1.10
February 0.133014E+11 0.00 0.00 0.00 0.00 51459887.16 0.00 0.00 1.10
March 0.150046E+11 0.00 0.00 0.00 0.00 3958050.18 0.00 0.00 1.09
April 0.148436E+11 0.00 0.00 92994.91 0.00 0.00 65015059.51 0.00 1.09
May 0.156740E+11 0.00 0.00 20307.08 0.00 0.00 39939576.96 0.00 1.09
June 0.139164E+11 8393259.68 0.00 352291.94 4598149.40 0.00 0.180534E+09 0.00 1.13
July 0.128128E+11 44952.33 0.00 1179195.88 0.00 0.00 0.683410E+09 0.00 1.16
August 0.126237E+11 0.00 0.00 477140.87 0.00 0.00 0.451548E+09 0.00 1.18
September 0.140388E+11 0.00 0.00 113111.20 0.00 0.00 0.124916E+09 0.00 1.14
October 0.158920E+11 0.00 0.00 0.00 0.00 315203.59 0.00 0.00 1.09
November 0.149493E+11 0.00 0.00 0.00 0.00 12378567.51 0.00 0.00 1.09
December 0.140864E+11 0.00 0.00 0.00 0.00 0.455589E+09 0.00 0.00 1.11
                   
Annual Sum or Average 0.171533E+12 8438212.01 0.00 2235041.87 4598149.40 0.102550E+10 0.154536E+10 0.00 1.11
Minimum of Months 0.126237E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.09
Maximum of Months 0.158920E+11 8393259.68 0.00 1179195.88 4598149.40 0.501797E+09 0.683410E+09 0.00 1.18



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:59:48

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.817793E+11 0.173136E+11 0.225691E+12 0.905683E+12 0.610359E+11
February 0.131493E+12 0.156157E+11 0.201780E+12 0.822556E+12 0.539723E+11
March 0.168182E+12 0.157710E+11 0.204720E+12 0.832523E+12 0.586877E+11
April 0.422924E+12 0.129887E+11 0.159722E+12 0.698315E+12 0.119833E+12
May 0.550091E+12 0.124488E+11 0.156354E+12 0.671184E+12 0.129823E+12
June 0.556597E+12 0.919050E+10 0.116295E+12 0.512431E+12 0.199875E+12
July 0.557907E+12 0.830441E+10 0.102435E+12 0.468537E+12 0.274385E+12
August 0.447591E+12 0.799700E+10 0.946305E+11 0.447875E+12 0.295504E+12
September 0.327214E+12 0.927338E+10 0.113582E+12 0.520851E+12 0.208475E+12
October 0.149917E+12 0.127185E+11 0.166307E+12 0.689082E+12 0.845565E+11
November 0.610047E+11 0.145504E+11 0.193341E+12 0.771446E+12 0.640316E+11
December 0.229659E+11 0.172277E+11 0.227350E+12 0.907225E+12 0.622548E+11
           
Annual Sum or Average 0.347767E+13 0.153400E+12 0.196221E+13 0.824771E+13 0.161243E+13
Minimum of Months 0.229659E+11 0.799700E+10 0.946305E+11 0.447875E+12 0.539723E+11
Maximum of Months 0.557907E+12 0.173136E+11 0.227350E+12 0.907225E+12 0.295504E+12