Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280

Simulation Timestamp: 2023-10-16 08:58:50


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 11483.95 1012.22 1012.22
Net Site Energy 11483.95 1012.22 1012.22
Total Source Energy 23167.13 2042.01 2042.01
Net Source Energy 23167.13 2042.01 2042.01


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 1287.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 718.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 766.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 242.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1745.01 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 651.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 556.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 104.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 208.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.75 3262.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 61.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 5145.72 6338.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 1287.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 718.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 766.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 242.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 959.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 14.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 8.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 32.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 556.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 104.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 208.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.75 3262.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 20.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 34.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 1287.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 718.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 766.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 242.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1745.01 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 651.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 556.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 104.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 208.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 90.75 3262.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 61.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 88.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 129.57 400.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 235.05 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 453.56 558.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 88.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 129.57 400.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 235.05 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 453.56 558.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 5145.717 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 5145.717 100.00
     
Total On-Site and Utility Electric Sources 5145.717 100.00
Total Electricity End Uses 5145.717 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 154.50 3.75
Air to Air Heat Recovery for Heating 3967.40 96.25
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 4121.90 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.50
Time Setpoint Not Met During Occupied Cooling 280.17
Time Not Comfortable Based on Simple ASHRAE 55-2004 8008.33


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58
RunPeriod RUNPERIOD 1
Weather File Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Latitude [deg] 42.93
Longitude [deg] -78.7
Elevation [m] 215.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 9.1389 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 13.3365 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 13.3365 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 9.2031 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 6.1031 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.8125 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 10.3656 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 8.7188 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 4.5531 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 4.5531 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 6.3938 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 4.5531 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.3656 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.3656 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 11.7219 4.65 2934.4875
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 6.3938 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 6.8557 7.07 41.0709
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 6.8557 7.07 41.0709
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 9.1389 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 13.3365 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 13.3365 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 9.2031 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 6.1031 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.8125 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 10.3656 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 8.7188 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 4.5531 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 4.5531 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 4.5531 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 4.5531 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 4.5531 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 4.5531 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 6.3938 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 4.5531 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 4.5531 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 4.5531 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 10.3656 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 10.3656 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 11.7219 4.65 2934.4875  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 6.3938 18.58 0.0000  
Total 11345.29             6.8557 3.54 41.0709  
Conditioned Total 11345.29             6.8557 3.54 41.0709  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 4.4542 8.82 37.1989
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 20-JUL-19:49 06-FEB-17:00 - - - - - - - - - - 17-JAN-21:40
Heating 0.00 286586.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 155497.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 88772.42 89612.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 32159.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 30508.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 6481.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 4003.15 265355.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 2398.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 408101.44 641554.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 286586.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 155497.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 58789.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 14636.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1856.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 30153.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 150.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 30508.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 6481.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 4003.15 265355.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 241.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 1061.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 1095.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 1395.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 2274.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2427.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 768.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5526.46 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2063.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1762.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 330.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 660.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 287.40 3536.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 195.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 16296.49 6870.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 122.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 200.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 213.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 67.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 487.11 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 155.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 29.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 58.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 311.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1436.41 605.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 122.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 200.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 213.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 67.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 487.11 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 155.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 29.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 58.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 311.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1436.41 605.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.53 0.596507 0.521000 1.32 1.00 0.500000 0.000639 0.000072 1.32 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.398238 0.128336 0.521000 0.207482 0.521000 0.500000 0.002969 0.000039 0.207482 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.239039 0.247590 0.521000 0.124539 0.660240 0.500000 0.001539 0.000016 0.124539 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.227898 0.549164 0.521000 0.118735 1.00 0.500000 0.000694 0.000024 0.118735 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.109647 0.658537 0.521000 0.057126 1.00 0.500000 0.000579 0.000014 0.057758 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.34 0.070728 0.521000 1.74 0.521000 0.500000 0.021376 0.000103 1.74 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.61 0.089155 0.521000 0.840989 0.521000 0.500000 0.004273 0.000113 0.840989 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 4.84 0.205848 0.521000 2.52 0.548927 0.500000 0.001851 0.000291 2.52 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.50 0.789575 0.521000 0.783178 1.00 0.500000 0.000483 0.000142 0.783178 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.20 0.115091 0.521000 1.14 0.521000 0.500000 0.003310 0.000118 1.14 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.30 0.109770 0.521000 1.20 0.521000 0.500000 0.003471 0.000122 1.20 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.31 0.061174 0.521000 1.21 0.521000 0.500000 0.011202 0.000082 1.21 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.770192 0.407741 0.521000 0.401270 1.00 0.500000 0.000934 0.000087 0.401270 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 8265.43 0.000072 174.34
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 4483.19 0.000039 112.52
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1772.63 0.000016 40.73
MECH_FLR_1 VAV BOX REHEAT COIL 2756.09 0.000024 70.61
STORAGE_FLR_1 VAV BOX REHEAT COIL 1610.64 0.000014 43.96
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 11741.50 0.000103 248.88
CAFE_FLR_1 VAV BOX REHEAT COIL 12880.69 0.000113 299.64
LOBBY_FLR_1 VAV BOX REHEAT COIL 33259.82 0.000291 755.19
ROOM_1_FLR_3 FAN COIL HEATING COIL 7844.75 0.000069 224.18
ROOM_2_FLR_3 FAN COIL HEATING COIL 7844.27 0.000069 224.17
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 44778.87 0.000392 1279.63
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 44791.71 0.000392 1279.99
ROOM_5_FLR_3 FAN COIL HEATING COIL 7817.23 0.000068 223.39
ROOM_6_FLR_3 FAN COIL HEATING COIL 7816.75 0.000068 223.38
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 16220.80 0.000142 402.54
ROOM_1_FLR_6 FAN COIL HEATING COIL 2379.12 0.000021 67.98
ROOM_2_FLR_6 FAN COIL HEATING COIL 2378.96 0.000021 67.98
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 11377.44 0.000100 325.11
BANQUET_FLR_6 VAV BOX REHEAT COIL 13491.74 0.000118 301.66
DINING_FLR_6 VAV BOX REHEAT COIL 13935.55 0.000122 310.99
KITCHEN_FLR_6 VAV BOX REHEAT COIL 9342.04 0.000082 200.06
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 9946.69 0.000087 260.16
VAV WITH REHEAT HEATING COIL 259908.04 0.002274 4086.35
FLR_3_DOAS HEATING COIL 23955.95 0.000210 376.64
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ZoneExhaust

User-Specified Maximum Flow Rate [m3/s]
LOBBY_FLR_1 EXHAUST FAN 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 1.15 0.000069 0.000458
ROOM_2_FLR_3 FAN COIL 1.11 0.000069 0.000443
ROOM_3_MULT19_FLR_3 FAN COIL 6.66 0.000392 0.002593
ROOM_4_MULT19_FLR_3 FAN COIL 5.57 0.000392 0.002330
ROOM_5_FLR_3 FAN COIL 1.04 0.000068 0.000416
ROOM_6_FLR_3 FAN COIL 1.01 0.000068 0.000403
ROOM_1_FLR_6 FAN COIL 0.301105 0.000021 0.000119
ROOM_2_FLR_6 FAN COIL 0.289981 0.000021 0.000115
ROOM_3_MULT9_FLR_6 FAN COIL 1.39 0.000100 0.000559
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 1.15
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 1.11
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 6.66
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 5.57
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 1.04
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 1.01
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.301105
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.289981
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.39
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.70 6.70 0.008654 12.80 0.008500 0.000458 1.15  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.70 6.70 0.008659 12.80 0.008500 0.000443 1.11  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.70 6.70 0.008582 12.80 0.008500 0.002593 6.66  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.70 6.70 0.008852 12.80 0.008500 0.002330 5.57  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.70 6.70 0.008671 12.80 0.008500 0.000416 1.04  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.70 6.70 0.008677 12.80 0.008500 0.000403 1.01  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.70 6.70 0.008648 12.80 0.008500 0.000119 0.301105  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.70 6.70 0.008653 12.80 0.008500 0.000115 0.289981  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.70 6.70 0.008706 12.80 0.008500 0.000559 1.39  
VAV WITH REHEAT COOLING COIL 27.30 6.70 0.011614 10.94 0.008500 0.022992 22.26 643701.88
FLR_3_DOAS COOLING COIL 30.30 6.70 0.013367 11.91 0.008500 0.002684 2.05 75158.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 11.66 11.66 22.38 11.66 22.26 22.26 0.300000 0.523955 22.26
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 22.26 11.66
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 11.66
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 22.26
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.022992 0.000021
VAV WITH REHEAT_HEATC_CONTROLLER 0.002274  
FLR_3_DOAS_COOLC_CONTROLLER 0.002684 0.000177
FLR_3_DOAS_HEATC_CONTROLLER 0.000210  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.033113 6823.32  
HEATSYS1 PUMP 0.004904 1476.98 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.004904 0.588525
COOLSYS1 0.033113 3.97
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 560599.92 560599.92 0.004904
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.033113 4724.01
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.033113 927070.14 927684.88 105.76
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 9.70 6.00 -2.20 -3.40 -4.20 2.70 7.50 13.70 18.60 22.00 20.70 16.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 42.93 -78.73 -5.00 215.00 98769 1.1739


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 8.97 26.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 9.139 5.380 0.000 0.000 0.000 0.000 14.519 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 13.336 10.760 0.000 0.000 0.000 0.000 24.096 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 13.336 10.760 0.000 0.000 0.000 0.000 24.096 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 9.203 5.380 0.000 0.000 0.000 0.000 14.583 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 6.103 2.690 0.000 0.000 0.000 0.000 8.793 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.813 61.680 535.850 0.000 0.000 0.000 603.343 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 10.366 5.380 0.000 0.000 0.000 0.000 15.746 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 8.719 8.070 0.000 0.000 0.000 0.000 16.789 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 6.394 0.000 0.000 0.000 0.000 0.000 6.394 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 10.366 67.820 0.000 0.000 0.000 0.000 78.186 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 10.366 67.820 0.000 0.000 0.000 0.000 78.186 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 11.722 515.227 2419.260 0.000 0.000 0.000 2946.209 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 6.394 0.000 0.000 0.000 0.000 0.000 6.394 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 18084.325 9.139 169.807 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 18084.325
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 894.495 13.336 82.602 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 894.495
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 1035.829 13.336 82.602 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1035.829
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 1511.551 9.203 569.967 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1511.551
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 578.329 6.103 283.494 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 578.329
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 453.605 5.813 54.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 453.605
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1957.673 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1957.673
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 11405.759 8.719 27.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 11405.759
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 111.660 4.553 74.440 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.660
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 111.691 4.553 74.460 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.691
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 2489.757 6.394 118.803 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2489.757
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 111.691 4.553 74.460 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.691
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 3437.839 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3437.839
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 3437.839 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3437.839
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1210.923 11.722 54.453 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1210.923
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 2635.024 6.394 118.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2635.024


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 457.500 4.429 20.573 0.000 0.250 0.000 0.750 ReachInFreezer 457.500 457.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 285.000 2.759 12.816 0.000 0.250 0.000 0.750 ReachInRefrigerator 285.000 285.000


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.198 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.1864 0.900 0.900 0.770 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.1864 0.900 0.900 0.770 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 0.8226 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.107 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.174 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.031 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.097 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.8346
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.048
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.7359
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6841
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.8028
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.7445
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.312
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.312
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.312
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.312
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.1981135 1.1981135 1.1981135  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
21 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
22 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
23 0 21.357363 0.71091016E-01 5.4032014  
24 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
25 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
26 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
27 0 21.357363 0.71091016E-01 5.4032014  
28 9 -0.17638513E-14 0.32473881E-16 -0.15472737E-09 0.39084990E-16
29 8 0.22578286E-07 0.11136169E-12 0.38514655E-03 -0.25672286E-09
30 7 -0.12460867E-01 0.57383191E-08 -0.23401545E-01 0.14168460E-03
31 6 0.41130930 0.19934685E-05 0.47716306 -0.48180040E-02
32 5 -5.2487139 0.74343025E-04 -4.4802041 0.63904887E-01
33 4 33.260058 0.60748543E-03 21.592533 -0.42553784
34 3 -111.77343 0.13226915E-02 -55.924898 1.5231004
35 2 197.67353 0.74337769E-03 78.150831 -2.9093300
36 1 -171.36487 0.79295509E-04 -55.335031 2.7490988
37 0 57.057407 0.45097929E-06 15.545453  
38 9 -0.19728226E-15 0.38070760E-16 -0.14134637E-09 0.10329039E-17
39 8 0.20696804E-07 0.14765672E-12 0.36530744E-03 -0.23532978E-09
40 7 -0.11868633E-01 0.77667999E-08 -0.22548754E-01 0.13495068E-03
41 6 0.39521686 0.27204939E-05 0.46345169 -0.46283129E-02
42 5 -5.0916664 0.10217830E-03 -4.3748670 0.61957574E-01
43 4 32.565369 0.84029717E-03 21.180735 -0.41631434
44 3 -110.29532 0.18400486E-02 -55.110745 1.5017457
45 2 196.20849 0.10394005E-02 77.404245 -2.8860650
46 1 -170.82368 0.11139293E-03 -55.118150 2.7396138
47 0 57.057407 0.63685742E-06 15.581450  
48 9 0.13059652E-14 0.41030072E-16 -0.13816519E-09 -0.47111965E-17
49 8 0.20247126E-07 0.15597406E-12 0.36047671E-03 -0.23021680E-09
50 7 -0.11724123E-01 0.82470298E-08 -0.22340566E-01 0.13330755E-03
51 6 0.39128975 0.28947446E-05 0.46009809 -0.45820219E-02
52 5 -5.0533361 0.10891817E-03 -4.3490697 0.61482301E-01
53 4 32.395785 0.89717001E-03 21.079809 -0.41406279
54 3 -109.93440 0.19673976E-02 -54.911173 1.4965315
55 2 195.85064 0.11127485E-02 77.221372 -2.8803827
56 1 -170.69145 0.11939355E-03 -55.065279 2.7372963
57 0 57.057407 0.68346468E-06 15.590432  
58 9 -0.20590843E-15 0.37601014E-16 -0.14495918E-09 0.53749011E-17
59 8 0.21205398E-07 0.13808064E-12 0.37072834E-03 -0.24111267E-09
60 7 -0.12030653E-01 0.72214098E-08 -0.22782120E-01 0.13679291E-03
61 6 0.39961963 0.25236359E-05 0.46720788 -0.46802108E-02
62 5 -5.1346368 0.94596970E-04 -4.4037454 0.62490383E-01
63 4 32.755467 0.77656360E-03 21.293679 -0.41883826
64 3 -110.69986 0.16977958E-02 -55.334066 1.5075900
65 2 196.60952 0.95769584E-03 77.608945 -2.8924333
66 1 -170.97185 0.10250317E-03 -55.177451 2.7422106
67 0 57.057407 0.58520576E-06 15.571474  
68 9 -0.13316196E-15 0.35962645E-16 -0.14184186E-09 0.33595795E-17
69 8 0.20766565E-07 0.14634888E-12 0.36605364E-03 -0.23612300E-09
70 7 -0.11890945E-01 0.76921302E-08 -0.22580893E-01 0.13520437E-03
71 6 0.39582317 0.26934781E-05 0.46396918 -0.46354598E-02
72 5 -5.0975841 0.10113583E-03 -4.3788466 0.62030949E-01
73 4 32.591550 0.83151862E-03 21.196301 -0.41666193
74 3 -110.35104 0.18204263E-02 -55.141525 1.5025506
75 2 196.26372 0.10281160E-02 77.432455 -2.8869422
76 1 -170.84409 0.11016374E-03 -55.126315 2.7399715
77 0 57.057407 0.62970739E-06 15.580070  
78 7 -0.15963512E-14 -0.15187529E-16 -0.22427203E-13 0.56155309E-15
79 6 0.17983713E-10 0.23594901E-11 0.52322926E-09 -0.18637893E-10
80 5 -0.60139213E-07 0.11510628E-07 -0.21924491E-05 0.17161312E-06
81 4 0.62746279E-04 0.43399923E-05 0.17681060E-02 -0.28244642E-03
82 3 -0.90508353E-02 0.15320797E-03 -0.21560640 0.43341486E-01
83 2 0.12836503 0.66328859E-03 2.9007871 -0.61911613
84 1 -0.32478029 0.41934727E-03 -7.1379041 1.5697129
85 0 0.20664896 0.54311639E-05 4.4522013  
86 7 -0.22427203E-13 -0.15187529E-16 -0.15963512E-14 0.56155309E-15
87 6 0.52322926E-09 0.23594901E-11 0.17983713E-10 -0.18637893E-10
88 5 -0.21924491E-05 0.11510628E-07 -0.60139213E-07 0.17161312E-06
89 4 0.17681060E-02 0.43399923E-05 0.62746279E-04 -0.28244642E-03
90 3 -0.21560640 0.15320797E-03 -0.90508353E-02 0.43341486E-01
91 2 2.9007871 0.66328859E-03 0.12836503 -0.61911613
92 1 -7.1379041 0.41934727E-03 -0.32478029 1.5697129
93 0 4.4522013 0.54311639E-05 0.20664896  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
103 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
104 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
105 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
106 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
107 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
108 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
109 0 0.43108349 0.21254961E-04 60.838472  
110 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
111 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
112 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
113 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
114 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
115 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
116 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
117 0 0.43108349 0.21254961E-04 60.838472  
118 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
119 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
120 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
121 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
122 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
123 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
124 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
125 0 0.43108349 0.21254961E-04 60.838472  
126 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
127 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
128 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
129 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
130 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
131 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
132 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
133 0 0.43108349 0.21254961E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.3856_SHGC_0.4 37 1 VerySmooth 2.191 2.191 1.000 0.401    
2 RESWINDOW_U_0.3856_SHGC_0.4 38 1 VerySmooth 2.191 2.191 1.000 0.401    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   3.40174E-002 0.31435 0.47878 0.47878 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 0.11969 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   3.40174E-002 0.31435 0.47878 0.47878 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 0.11969 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 1.500
2 RACK2 1 0 Zone Air-Cooled 3.000


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 0.576 0.5074
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 0.263 2.9576E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 3.921E-002 5.846E-004 2.885E-004 0.531 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 1.513E-002 1.949E-004 5.306E-004 0.177 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 3.577E-002 2.178E-004 5.696E-004 0.198 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 2.064E-002 2.178E-004 4.726E-004 0.198 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 4.884E-002 6.258E-004 5.569E-004 0.569 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 8.667E-002 4.589E-004 2.527E-004 0.417 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.248 1.893E-004 3.620E-004 0.172 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 6.349E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 6.350E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 2.751E-002 7.066E-005 5.696E-004 8.345E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.164E-002 4.746E-004 2.589E-004 0.561 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 4.974E-002 4.815E-004 2.609E-004 0.569 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 4.868E-002 1.181E-004 9.784E-005 0.140 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1502
2 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 7.6775E-002
3 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1700
4 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 8.7122E-002
5 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1046
6 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 4.1030E-002
7 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 4.2077E-002
8 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 1.3979E-002
9 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1701
10 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 9.2237E-002
11 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1930
12 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 0.1043
13 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1157
14 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 5.1273E-002
15 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 4.7248E-002
16 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 1.9114E-002
17 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 3.6170E-002
18 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 2.0860E-002
19 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.7822E-002
20 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.5752E-002
21 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.6722E-002
22 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.0690E-002
23 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 4.1419E-002
24 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.4687E-002
25 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 3.6170E-002
26 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 2.0860E-002
27 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.7822E-002
28 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.5752E-002
29 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.6722E-002
30 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.0690E-002
31 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 4.1419E-002
32 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.4687E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 33917.35009 33917.35009 2.52783 2.52783 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:40:00 25.99100 1.33593E-002 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 1486.84097 1486.84097 6.53722E-002 0.85446 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -16.30000 9.24091E-004 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 5342.64741 5342.64741 0.39824 0.39824 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 30.06750 1.33665E-002 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 3416.34716 3416.34716 0.15020 0.15020 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -16.30000 9.24091E-004 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3206.90824 3206.90824 0.23904 0.23904 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 29.92800 1.33663E-002 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 1132.28241 1132.28241 4.97818E-002 9.17347E-002 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -16.30000 9.24091E-004 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 3058.08897 3058.08897 0.22790 0.22790 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 29.83500 1.33661E-002 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 2145.73009 2145.73009 9.43386E-002 9.43386E-002 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -16.30000 9.24091E-004 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1471.30564 1471.30564 0.10965 0.10965 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 30.20700 1.33668E-002 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 1313.70975 1313.70975 5.77583E-002 5.77652E-002 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -16.30000 9.24091E-004 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 44764.17795 44764.17795 3.33635 3.33635 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 30.30000 1.33670E-002 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 2807.54133 2807.54133 0.12343 0.12343 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -16.30000 9.24091E-004 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 21637.95235 21637.95235 1.61418 1.61418 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 30.06750 1.33665E-002 188.86188 142.30000 0.67639 0.00000
14 CAFE_FLR_1 Heating 8555.87898 8555.87898 0.37615 0.67639 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -16.30000 9.24091E-004 188.86188 142.30000 0.67639 0.00000
15 LOBBY_FLR_1 Cooling 64949.51755 64949.51755 4.84260 4.84260 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 30.14500 1.33667E-002 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 20286.12379 20286.12379 0.89190 1.89399 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -16.30000 9.24091E-004 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 11491.77131 11491.77131 1.15416 1.15416 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 28.99800 1.33646E-002 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 7845.05315 7845.05315 0.34692 0.34692 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -16.30000 9.24091E-004 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 11099.25016 11099.25016 1.11474 1.11474 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 28.84300 1.33644E-002 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 7844.57635 7844.57635 0.34690 0.34690 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -16.30000 9.24091E-004 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 66295.66916 66295.66916 6.65780 6.65780 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 30.14500 1.33667E-002 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 44779.71794 44779.71794 1.98032 1.98032 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -16.30000 9.24091E-004 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 55467.88916 55467.88916 5.57086 5.57086 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 30.20700 1.33668E-002 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 44792.55590 44792.55590 1.98089 1.98089 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -16.30000 9.24091E-004 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 10383.98432 10383.98432 1.04290 1.04290 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 26.76600 1.33607E-002 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 7817.53030 7817.53030 0.34570 0.34570 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -16.30000 9.24091E-004 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 10036.80669 10036.80669 1.00803 1.00803 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 25.97550 1.33593E-002 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 7817.05447 7817.05447 0.34568 0.34568 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -16.30000 9.24091E-004 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 20169.89060 20169.89060 1.50322 1.50322 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 30.30000 1.33670E-002 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 12192.47827 12192.47827 0.53606 0.53606 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -16.30000 9.24091E-004 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 2998.05112 2998.05112 0.30110 0.30110 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 28.99800 1.33646E-002 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 2379.21129 2379.21129 0.10521 0.10521 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -16.30000 9.24091E-004 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2887.29269 2887.29269 0.28998 0.28998 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 28.84300 1.33644E-002 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 2379.04893 2379.04893 0.10521 0.10521 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -16.30000 9.24091E-004 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 13808.35465 13808.35465 1.38684 1.38684 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 30.14500 1.33667E-002 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 11377.77615 11377.77615 0.50315 0.50315 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -16.30000 9.24091E-004 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 29426.65654 29426.65654 2.19585 2.19585 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 30.30000 1.33670E-002 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 7606.79131 7606.79131 0.33444 1.18780 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -16.30000 9.24091E-004 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 30853.68388 30853.68388 2.30230 2.30230 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 30.30000 1.33670E-002 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 7765.44695 7765.44695 0.34141 1.18780 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:50:00 -16.30000 9.24091E-004 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 30973.21561 30973.21561 2.31447 2.31447 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 29.46300 1.33655E-002 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 3151.27496 3151.27496 0.13853 0.36735 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 -16.30000 9.24091E-004 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 10334.29942 10334.29942 0.77019 0.77019 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 30.30000 1.33670E-002 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 7882.37917 7882.37917 0.34656 0.34656 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:50:00 -16.30000 9.24091E-004 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 380534.70 22.25559 22.25559 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 294599.96 7.56786 7.56786 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00
3 FLR_3_DOAS Cooling Sensible 42344.89 17.26984 2.05125 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 FLR_3_DOAS Heating Sensible 79850.37 6.05999 2.05125 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.52783
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.59651
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52100
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.31700
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.38719E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.23096E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.31700
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8265.42789
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.23096E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 174.34429
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.39824
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12834
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52100
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20748
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52100
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.96876E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.92209E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.20748
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4483.18704
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.92209E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 112.51781
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.23904
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24759
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52100
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12454
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.66024
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.53883E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.55078E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.12454
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1772.63336
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.55078E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 40.72865
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.22790
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.54916
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52100
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.11873
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.93782E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.41115E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.11873
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2756.09087
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.41115E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 70.61246
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.10965
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.65854
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52100
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.71261E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.78555E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.40906E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.77583E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1610.63795
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.40906E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 43.95506
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.33635
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.07281E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52100
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.73824
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52100
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.13760E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.02720E-004
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.73824
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11741.50195
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.02720E-004
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 248.88330
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.61418
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 8.91552E-002
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52100
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.84099
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52100
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.27345E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.12686E-004
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.84099
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12880.68886
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.12686E-004
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 299.63963
99 Fan:ZoneExhaust LOBBY_FLR_1 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.84260
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20585
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52100
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.52299
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54893
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.85088E-003
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.90971E-004
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.52299
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
110 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 33259.82005
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.90971E-004
113 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 755.19465
114 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
115 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.15416
116 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.15416
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 6.86293E-005
118 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.58361E-004
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69724
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.65377E-003
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.58361E-004
125 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.15416
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 7844.75003
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.86293E-005
128 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 224.17901
129 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
130 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.11474
131 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.11474
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 6.86251E-005
133 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.43320E-004
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69723
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.65896E-003
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.43320E-004
140 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.11474
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 7844.27325
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.86251E-005
143 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 224.16539
144 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
145 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 6.65780
146 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 6.65780
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.91745E-004
148 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.59338E-003
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69794
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.58203E-003
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.59338E-003
155 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 6.65780
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 44778.87387
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.91745E-004
158 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 1279.62615
159 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
160 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.57086
161 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 5.57086
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.91857E-004
163 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.32982E-003
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69699
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.85168E-003
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.32982E-003
170 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.57086
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 44791.71157
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.91857E-004
173 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 1279.99300
174 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
175 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.04290
176 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.04290
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 6.83885E-005
178 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.16070E-004
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69721
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.67082E-003
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.16070E-004
185 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.04290
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 7817.22813
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.83885E-005
188 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 223.39273
189 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
190 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.00803
191 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.00803
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 6.83844E-005
193 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.02785E-004
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69719
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.67665E-003
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.02785E-004
200 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.00803
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 7816.75232
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.83844E-005
203 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 223.37913
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.50322
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.78957
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52100
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.78318
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.82538E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.41907E-004
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.78318
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
214 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16220.79595
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.41907E-004
217 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 402.53831
218 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
219 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.30110
220 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.30110
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.08136E-005
222 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.19381E-004
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69725
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.64756E-003
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.19381E-004
229 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.30110
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 2379.12281
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.08136E-005
232 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 67.98481
233 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
234 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.28998
235 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.28998
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.08122E-005
237 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.15137E-004
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69724
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.65295E-003
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.15137E-004
244 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.28998
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 2378.96045
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.08122E-005
247 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 67.98017
248 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
249 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.38684
250 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.38684
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 9.95348E-005
252 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 5.58518E-004
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69706
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.70629E-003
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.58518E-004
259 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.38684
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 11377.43615
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.95348E-005
262 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 325.11472
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.19585
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11509
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52100
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.14404
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52100
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.31042E-003
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.18032E-004
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.14404
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
273 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13491.74199
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.18032E-004
276 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 301.66353
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.30230
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10977
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52100
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.19950
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52100
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.47091E-003
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.21914E-004
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.19950
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
287 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13935.55286
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.21914E-004
290 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 310.98895
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.31447
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.11735E-002
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52100
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.20584
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52100
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.12022E-002
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.17283E-005
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.20584
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
301 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9342.04283
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.17283E-005
304 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 200.06447
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.77019
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.40774
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52100
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.40127
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.34416E-004
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.70180E-005
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.40127
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
315 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9946.69237
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.70180E-005
318 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 260.15891
319 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 11.66093
320 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 11.66093
321 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 22.38182
322 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 11.66093
323 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 22.25559
324 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 22.25559
325 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
326 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.52396
327 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
328 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
329 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
333 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
334 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
335 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 22.25559
336 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
337 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 22.25559
338 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 11.66146
339 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 11.66146
340 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.29602
341 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.94047
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.16136E-002
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 643701.88389
346 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.29915E-002
347 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 22.25559
348 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 259908.04170
349 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.27379E-003
350 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 4086.35067
351 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 22.25559
352 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 2.29915E-002
353 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 2.07116E-005
354 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.27379E-003
355 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
356 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
357 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
358 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 30.30000
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.91477
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.33670E-002
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 75158.60084
364 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.68449E-003
365 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
366 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 23955.95238
367 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.09577E-004
368 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 376.64253
369 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
370 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 2.68449E-003
371 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.77386E-004
372 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.09577E-004
373 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 3.31128E-002
374 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 6823.32025
375 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 4.90437E-003
376 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.58852
377 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 4.90437E-003
378 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 1476.98166
379 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
380 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 560599.91665
381 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 560599.92000
382 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 4.90437E-003
383 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 3.31128E-002
384 PlantLoop COOLSYS1 Plant Loop Volume [m3] 3.97354
385 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 3.31128E-002
386 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 4724.01475
387 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 3.31128E-002
388 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 927070.13797
389 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 927684.88000
390 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 105.75608
391 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
392 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
393 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
394 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
395 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 8307.76
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 4502.09
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1780.89
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 2767.49
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1616.79
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 11801.37
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 12940.03
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 33416.60
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 8449.81
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 8449.29
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 48232.49
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 48246.31
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 8420.17
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 8419.65
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 16289.94
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 2562.55
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 2562.38
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 12254.60
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 13556.31
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 14002.37
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 9389.24
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 9986.34
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 173851.09
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 16024.01


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 19399.42 15472.59 3926.82 0.80 2260.20 22.92
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 18753.66 14952.13 3801.53 0.80 2184.61 22.16
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 110507.49 88588.17 21919.32 0.80 12905.02 130.89
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 96789.93 76179.89 20610.05 0.79 11213.96 113.74
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 17581.15 14005.71 3575.44 0.80 2047.27 20.76
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 17010.42 13545.57 3464.85 0.80 1980.46 20.09
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 5055.59 4034.00 1021.60 0.80 589.14 5.98
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 4873.39 3887.14 986.25 0.80 567.81 5.76
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 23521.56 18692.33 4829.24 0.79 2736.08 27.75
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 631006.82 417140.96 213865.86 0.66 76293.68 773.81
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 61333.89 39815.52 21518.37 0.65 7074.24 71.75


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 3.93 13.40


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.419 0.394   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.419 0.394   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.419 0.394   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.419 0.394   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.198 1.198   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.823 0.732   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.031 0.893   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.107 0.950   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.107 0.950   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.107 0.950   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.107 0.950   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.097 0.942   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.097 0.942   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.097 0.942   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.097 0.942   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.097 0.942   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.174 0.999   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.8709780959E-002 2.2854166310E-002 Pass Pass 3.6214659760E-003 8.8959517200E-003 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 2.0577186260E-003 1.5077035177E-003 Pass Pass 5.7270097930E-002 9.9640363055E-002 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 1.4196971826E-002 2.2040556410E-002 Pass Pass 1.8463439935E-002 5.3166969496E-002 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 4.9671625868E-004 3.7946650433E-004 Pass Pass 0.1035321362 0.1725608769 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 5.0182587001E-004 3.8818158411E-004 Pass Pass 0.4589042648 4.4512476399 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 7.1272229516E-002 0.2154541928 Pass Pass 1.9291300312E-002 5.2087505501E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 6.6704146156E-003 2.2646130701E-002 Pass Pass 4.2682487346E-002 0.1210356409 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 2.3839843520E-002 4.1376633819E-002 Pass Pass 1.4504744868E-002 3.9982266970E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 9.2646689239E-002 0.3330988286 Pass Pass 0.7022848172 5.8311255404 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 9.2630605946E-002 0.3339164953 Pass Pass 0.3287925969 1.7732974232 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 3.1765825753E-005 5.2291072542E-005 Pass Pass 0.1405762511 0.6443937619 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 4.6845466484E-002 0.1648660910 Pass Pass 0.1354545255 0.3935465908 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 9.2640033072E-002 0.3312214628 Pass Pass 0.5747956085 4.3398263521 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 9.2633381996E-002 0.3319327327 Pass Pass 0.2895485954 1.4554999854 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 4.3240032145E-004 3.3787234102E-004 Pass Pass 0.1180120613 0.3472742782 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 9.2631805092E-002 0.3532487204 Pass Pass 0.1337586116 0.4576981491 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 9.2630620031E-002 0.3543156716 Pass Pass 0.1271062971 0.4118793510 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 9.2052583951E-002 0.3239316615 Pass Pass 0.2806610366 1.1689317655 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 4.4663467165E-002 7.8944104100E-002 Pass Pass 9.7833247053E-003 2.6584015611E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 3.4596512763E-002 6.5670453366E-002 Pass Pass 1.0505064284E-002 3.2554056114E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 3.0274832384E-002 9.1921828340E-002 Pass Pass 2.1710855779E-002 4.1881179409E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 7.5546126746E-004 5.7059891898E-004 Pass Pass 0.3449737206 0.9119478763 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 4406.56 147.65 1851.02 7777.71 3658.69 17841.64



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB -16.30 0.00 -16.30 Wetbulb [C] 5.10 270.00
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 30.30 9.30 21.80 Wetbulb [C] 5.70 240.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 44.00 33      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 67.00 33      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.399 0.419 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.399 0.419 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.399 0.419 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.732 0.823 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.23 0.182 0.186 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.732 0.823 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.732 0.823 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.732 0.823 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.23 0.182 0.186 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 0.732 0.823 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 0.732 0.823 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.23 0.182 0.186 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.893 1.031 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.893 1.031 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.893 1.031 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.893 1.031 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.893 1.031 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.893 1.031 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.893 1.031 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.893 1.031 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.893 1.031 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.893 1.031 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 0.950 1.107 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 0.950 1.107 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 0.950 1.107 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 0.950 1.107 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.942 1.097 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.942 1.097 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 0.942 1.097 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.942 1.097 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.942 1.097 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.999 1.174 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 0.999 1.174 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.23 0.182 0.186 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.23 0.182 0.186 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.186 0.196 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.186 0.196 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.186 0.196 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.186 0.196 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.186 0.196 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.186 0.196 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.186 0.196 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.186 0.196 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.186 0.196 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.186 0.196 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.185 0.196 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.185 0.196 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.185 0.196 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.188 0.196 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   23.26 0.00 0.00 23.26 23.26 2.191 0.401 0.402             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   65.50 0.00 0.00 65.50 65.50 2.191 0.401 0.402             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   85.08 0.00 0.00 85.08 85.08 2.191 0.401 0.402             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.191 0.401 0.402             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.191 0.401 0.402             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.191 0.401 0.402             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.191 0.401 0.402             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   3.68 0.00 0.00 3.68 279.56 2.191 0.401 0.402             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   3.68 0.00 0.00 3.68 279.65 2.191 0.401 0.402             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.191 0.401 0.402             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.191 0.401 0.402             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.191 0.401 0.402             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.191 0.401 0.402             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   5.82 0.00 0.00 5.82 23.30 2.191 0.401 0.402             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   2.15 0.00 0.00 2.15 8.59 2.191 0.401 0.402             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   2.15 0.00 0.00 2.15 8.58 2.191 0.401 0.402             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   5.82 0.00 0.00 5.82 23.30 2.191 0.401 0.402             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.191 0.401 0.402             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 8.58 2.191 0.401 0.402             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.191 0.401 0.402             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 8.58 2.191 0.401 0.402             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   6.74 0.00 0.00 6.74 60.70 2.191 0.401 0.402             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   32.19 0.00 0.00 32.19 32.19 2.191 0.401 0.402             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   32.19 0.00 0.00 32.19 32.19 2.191 0.401 0.402             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.191 0.401 0.402             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   17.17 0.00 0.00 17.17 17.17 2.191 0.401 0.402             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.191 0.401 0.402             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   5.82 0.00 0.00 5.82 5.82 2.191 0.401 0.402             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   5.21 0.00 0.00 5.21 5.21 2.191 0.401 0.402             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   17.17 0.00 0.00 17.17 17.17 2.191 0.401 0.402             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.191 0.401 0.402                      
North Total or Average             432.95 2.191 0.401 0.402                      
Non-North Total or Average             780.84 2.191 0.401 0.402                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.016 1.198 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 9.1389 1978.83 18084.33 LightsWired LTG_SCH_BASEMENT 51.16 168.00 51.10 0.0000 Y 173.46
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 13.3365 67.07 894.50 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 8.61
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 13.3365 77.67 1035.83 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 9.97
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 9.2031 164.24 1511.55 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 16.63
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 6.1031 94.76 578.33 LightsWired LTG_SCH_STORAGE 25.68 168.00 25.65 0.0000 Y 2.78
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.8125 78.04 453.60 LightsWired LTG_SCH_LAUNDRY 51.36 168.00 51.30 0.0000 Y 4.37
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 10.3656 188.86 1957.67 LightsWired LTG_SCH_DINING 58.69 168.00 48.64 0.0000 Y 17.87
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 8.7188 1308.19 11405.76 LightsWired LTG_SCH_LOBBY 58.69 168.00 56.90 0.0000 Y 121.83
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 4.5531 156.09 710.69 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 4.5531 156.07 710.61 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 4.5531 1863.81 8486.17 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 76.02
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 4.5531 1864.32 8488.49 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 76.04
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 4.5531 156.09 710.69 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 4.5531 156.07 710.61 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 6.3938 1557.62 9959.03 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 109.60
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 4.5531 39.02 177.67 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.59
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 4.5531 39.02 177.65 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.59
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 4.5531 220.77 1005.22 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 9.00
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 10.3656 331.66 3437.84 LightsWired LTG_SCH_DINING 58.69 168.00 53.59 0.0000 Y 34.58
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 10.3656 331.66 3437.84 LightsWired LTG_SCH_DINING 58.69 168.00 53.59 0.0000 Y 34.58
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 11.7219 103.30 1210.92 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 13.33
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 6.3938 412.12 2635.02 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 29.00
Interior Lighting Total       6.8557 11345.29 77780.02               506.97


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.07 11405.76 798.40
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.00 11405.76 0.00
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.39 1957.67 763.49
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.00 1957.67 0.00
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3437.84 687.57
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.00 3437.84 0.00
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3437.84 687.57
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.00 3437.84 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 15448.40 AstronomicalClock -   83.67 83.67 242.63
Exterior Lighting Total 15448.40           242.63



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 560599.92 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 927684.88 2.96 927847.94 2.96 3.93 13.40


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12833.12 19399.42 15472.59 3926.82 0.80 - 2260.20 22.92
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12412.02 18753.66 14952.13 3801.53 0.80 - 2184.61 22.16
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 72608.97 110507.49 88588.17 21919.32 0.80 - 12905.02 130.89
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 65229.93 96789.93 76179.89 20610.05 0.79 - 11213.96 113.74
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11649.07 17581.15 14005.71 3575.44 0.80 - 2047.27 20.76
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11277.12 17010.42 13545.57 3464.85 0.80 - 1980.46 20.09
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3342.42 5055.59 4034.00 1021.60 0.80 - 589.14 5.98
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3223.60 4873.39 3887.14 986.25 0.80 - 567.81 5.76
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 15637.30 23521.56 18692.33 4829.24 0.79 - 2736.08 27.75
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 643701.88 631006.82 417140.96 213865.86 0.66 - 76293.68 773.81
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 75158.60 61333.89 39815.52 21518.37 0.65 - 7074.24 71.75
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 8265.43 8307.76 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 4483.19 4502.09 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1772.63 1780.89 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2756.09 2767.49 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1610.64 1616.79 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 11741.50 11801.37 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 12880.69 12940.03 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 33259.82 33416.60 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 7844.75 8449.81 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 7844.27 8449.29 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 44778.87 48232.49 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 44791.71 48246.31 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 7817.23 8420.17 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 7816.75 8419.65 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 16220.80 16289.94 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 2379.12 2562.55 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 2378.96 2562.38 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 11377.44 12254.60 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 13491.74 13556.31 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 13935.55 14002.37 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 9342.04 9389.24 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 9946.69 9986.34 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 259908.04 173851.09 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 23955.95 16024.01 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.15 812.11 703.64 1.00 1.16 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.11 784.37 703.64 1.00 1.17 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 6.66 4684.67 703.64 1.00 0.95 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 5.57 3919.86 703.64 1.00 0.96 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.04 733.82 703.64 1.00 1.19 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.01 709.29 703.64 1.00 1.19 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.30 211.87 703.64 1.00 1.71 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.29 204.04 703.64 1.00 1.74 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.39 975.83 703.64 1.00 1.13 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 22.26 49866.73 2240.64 1.00 1.11 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.033113 6823.32 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.004904 1476.98 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.033113 4724.01 142664.32 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.80 0.58 0.51
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.80 0.26 0.03



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 33917.35 33917.35 17.14 2.528 2.528 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:40:00 24.00 24.00 0.00921 25.99 0.01336 0.854 0.00
RETAIL_1_FLR_1 5342.65 5342.65 79.66 0.398 0.398 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 24.00 24.00 0.00906 30.07 0.01337 0.079 0.00
RETAIL_2_FLR_1 3206.91 3206.91 41.29 0.239 0.239 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 24.00 24.00 0.00944 29.93 0.01337 0.092 0.00
MECH_FLR_1 3058.09 3058.09 18.62 0.228 0.228 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 24.00 24.00 0.00886 29.84 0.01337 0.000 0.00
STORAGE_FLR_1 1471.31 1471.31 15.53 0.110 0.110 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 24.00 0.00901 30.21 0.01337 0.058 0.00
LAUNDRY_FLR_1 44764.18 44764.18 573.61 3.336 3.336 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 24.00 0.00856 30.30 0.01337 0.000 0.00
CAFE_FLR_1 21637.95 21637.95 114.57 1.614 1.614 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 24.00 23.99 0.01003 30.07 0.01337 0.676 0.00
LOBBY_FLR_1 64949.52 64949.52 49.65 4.843 4.843 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 24.00 23.99 0.01001 30.14 0.01337 1.894 0.00
ROOM_1_FLR_3 11491.77 11491.77 294.49 1.154 1.154 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 21.11 21.11 0.00865 29.00 0.01336 0.062 0.00
ROOM_2_FLR_3 11099.25 11099.25 284.47 1.115 1.115 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 21.11 21.11 0.00866 28.84 0.01336 0.062 0.00
ROOM_3_MULT19_FLR_3 66295.67 66295.67 2703.31 6.658 6.658 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 21.11 21.11 0.00858 30.14 0.01337 0.837 0.00
ROOM_4_MULT19_FLR_3 55467.89 55467.89 2261.18 5.571 5.571 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 21.11 21.11 0.00885 30.21 0.01337 0.837 0.00
ROOM_5_FLR_3 10383.98 10383.98 266.11 1.043 1.043 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 21.11 21.11 0.00867 26.77 0.01336 0.062 0.00
ROOM_6_FLR_3 10036.81 10036.81 257.24 1.008 1.008 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 21.11 21.11 0.00868 25.98 0.01336 0.062 0.00
CORRIDOR_FLR_3 20169.89 20169.89 51.80 1.503 1.503 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 24.00 0.00952 30.30 0.01337 0.475 0.00
ROOM_1_FLR_6 2998.05 2998.05 76.83 0.301 0.301 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 21.11 21.11 0.00865 29.00 0.01336 0.015 0.00
ROOM_2_FLR_6 2887.29 2887.29 74.00 0.290 0.290 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 21.11 21.11 0.00865 28.84 0.01336 0.015 0.00
ROOM_3_MULT9_FLR_6 13808.35 13808.35 562.90 1.387 1.387 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 21.11 21.11 0.00871 30.14 0.01337 0.099 0.00
BANQUET_FLR_6 29426.66 29426.66 88.73 2.196 2.196 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 23.98 0.01044 30.30 0.01337 1.188 0.00
DINING_FLR_6 30853.68 30853.68 93.03 2.302 2.302 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 23.98 0.01035 30.30 0.01337 1.188 0.00
KITCHEN_FLR_6 30973.22 30973.22 299.82 2.314 2.314 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 24.00 23.97 0.01009 29.46 0.01337 0.367 0.00
CORRIDOR_FLR_6 10334.30 10334.30 25.08 0.770 0.770 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 24.00 24.00 0.00905 30.30 0.01337 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 1486.84 1486.84 0.75 0.065 0.854 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00796 -16.30 0.00092 0.854 0.00
RETAIL_1_FLR_1 3416.35 3416.35 50.94 0.150 0.150 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.00 21.00 0.00751 -16.30 0.00092 0.079 0.00
RETAIL_2_FLR_1 1132.28 1132.28 14.58 0.050 0.092 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.00 21.00 0.00744 -16.30 0.00092 0.092 0.00
MECH_FLR_1 2145.73 2145.73 13.06 0.094 0.094 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.00 21.00 0.00731 -16.30 0.00092 0.000 0.00
STORAGE_FLR_1 1313.71 1313.71 13.86 0.058 0.058 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.00 21.00 0.00735 -16.30 0.00092 0.058 0.00
LAUNDRY_FLR_1 2807.54 2807.54 35.98 0.123 0.123 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.00 21.00 0.00728 -16.30 0.00092 0.000 0.00
CAFE_FLR_1 8555.88 8555.88 45.30 0.376 0.676 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.00 21.00 0.00756 -16.30 0.00092 0.676 0.00
LOBBY_FLR_1 20286.12 20286.12 15.51 0.892 1.894 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.00 21.00 0.00748 -16.30 0.00092 1.894 0.00
ROOM_1_FLR_3 7845.05 7845.05 201.04 0.347 0.347 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00751 -16.30 0.00092 0.062 0.00
ROOM_2_FLR_3 7844.58 7844.58 201.05 0.347 0.347 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00751 -16.30 0.00092 0.062 0.00
ROOM_3_MULT19_FLR_3 44779.72 44779.72 1825.97 1.980 1.980 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00754 -16.30 0.00092 0.837 0.00
ROOM_4_MULT19_FLR_3 44792.56 44792.56 1825.99 1.981 1.981 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00754 -16.30 0.00092 0.837 0.00
ROOM_5_FLR_3 7817.53 7817.53 200.34 0.346 0.346 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00751 -16.30 0.00092 0.062 0.00
ROOM_6_FLR_3 7817.05 7817.05 200.35 0.346 0.346 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00751 -16.30 0.00092 0.062 0.00
CORRIDOR_FLR_3 12192.48 12192.48 31.31 0.536 0.536 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.00 21.00 0.00761 -16.30 0.00092 0.475 0.00
ROOM_1_FLR_6 2379.21 2379.21 60.97 0.105 0.105 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00759 -16.30 0.00092 0.015 0.00
ROOM_2_FLR_6 2379.05 2379.05 60.97 0.105 0.105 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00759 -16.30 0.00092 0.015 0.00
ROOM_3_MULT9_FLR_6 11377.78 11377.78 463.82 0.503 0.503 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00760 -16.30 0.00092 0.099 0.00
BANQUET_FLR_6 7606.79 7606.79 22.94 0.334 1.188 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.00 21.00 0.00768 -16.30 0.00092 1.188 0.00
DINING_FLR_6 7765.45 7765.45 23.41 0.341 1.188 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:50:00 21.00 21.00 0.00769 -16.30 0.00092 1.188 0.00
KITCHEN_FLR_6 3151.27 3151.27 30.50 0.139 0.367 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 21.00 21.00 0.00697 -16.30 0.00092 0.367 0.00
CORRIDOR_FLR_6 7882.38 7882.38 19.13 0.347 0.347 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:50:00 21.00 21.00 0.00773 -16.30 0.00092 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 22.26 22.26 7.57 7.57 22.2556 11.6609 22.2556 0.5240 0.3000
FLR_3_DOAS 17.27 2.05 6.06 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 8265.428 8265.428 1.317001 0.00007231 174.344 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8265.43 8265.43 1.317001 16.70 12.95 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00795865 50.1612 1486.84 0.00 8311.69 8311.69
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 4483.187 4483.187 0.207482 0.00003922 112.518 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 4483.19 4483.19 0.207482 16.70 12.95 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00751014 47.3704 3416.35 0.00 4506.27 4506.27
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1772.633 1772.633 0.124539 0.00001551 40.729 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 1772.63 1772.63 0.124539 16.70 12.95 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00743589 46.9062 1132.28 0.00 1782.14 1782.14
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 2756.091 2756.091 0.118735 0.00002411 70.612 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 2756.09 2756.09 0.118735 16.70 12.95 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00731005 46.1217 2145.73 0.00 2770.21 2770.21
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1610.638 1610.638 0.057758 0.00001409 43.955 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 1610.64 1610.64 0.057758 16.70 12.95 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00734616 46.3468 1313.71 0.00 1618.63 1618.63
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 11741.502 11741.502 1.738238 0.00010272 248.883 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 11741.50 11741.50 1.738238 16.70 12.95 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00728305 45.9547 2807.54 0.00 11807.12 11807.12
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 12880.689 12880.689 0.840989 0.00011269 299.640 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 12880.69 12880.69 0.840989 16.70 12.95 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00756408 47.7061 8555.88 0.00 12949.52 12949.52
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 33259.820 33259.820 2.522994 0.00029097 755.195 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 33259.82 33259.82 2.522994 16.70 12.95 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00748122 47.1887 20286.12 0.00 33439.01 33439.01
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 12833.121 -999.000 1.154159 0.00045836 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown 7/21 17:00:00 12833.12 12380.92 1.154159 21.70 15.44 0.00865377 12.80 11.87 0.00850000 29.00 0.01336465 21.45 0.0000 21.11 0.00865377 54.1148 11491.77 0.00 13142.88 12451.75
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 7844.750 7844.750 0.346921 0.00006863 224.179 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 7844.75 7844.75 0.346921 21.11 14.20 0.00750779 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.11 0.00750779 47.0344 7845.05 0.00 8456.79 8456.79
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 12412.024 -999.000 1.114738 0.00044332 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 unknown 7/21 17:10:00 12412.02 11960.45 1.114738 21.70 15.44 0.00865896 12.80 11.87 0.00850000 28.84 0.01336437 21.41 0.0000 21.11 0.00865896 54.1468 11099.25 0.00 12711.41 12028.90
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 7844.273 7844.273 0.346900 0.00006863 224.165 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 7844.27 7844.27 0.346900 21.11 14.20 0.00750780 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.11 0.00750780 47.0344 7844.58 0.00 8456.27 8456.27
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 72608.968 -999.000 6.657805 0.00259338 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 unknown 7/21 13:40:00 72608.97 71221.36 6.657805 21.70 15.38 0.00858203 12.80 11.87 0.00850000 30.14 0.01336669 21.78 0.0000 21.11 0.00858203 53.6703 66295.67 0.00 74378.39 71627.03
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 44778.874 44778.874 1.980324 0.00039175 1279.626 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 44778.87 44778.87 1.980324 21.11 14.23 0.00754059 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.11 0.00754059 47.2359 44779.72 0.00 48272.88 48272.88
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 65229.928 -999.000 5.570855 0.00232982 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 unknown 7/21 15:10:00 65229.93 60201.09 5.570855 21.70 15.61 0.00885168 12.80 11.87 0.00850000 30.21 0.01336679 21.80 0.0000 21.11 0.00885168 55.3352 55467.89 0.00 66764.57 60550.97
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 44791.712 44791.712 1.980892 0.00039186 1279.993 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 44791.71 44791.71 1.980892 21.11 14.23 0.00754059 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.11 0.00754059 47.2359 44792.56 0.00 48286.72 48286.72
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 11649.067 -999.000 1.042902 0.00041607 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown 7/21 10:00:00 11649.07 11194.84 1.042902 21.70 15.46 0.00867082 12.80 11.87 0.00850000 26.77 0.01336069 20.80 0.0000 21.11 0.00867082 54.2200 10383.98 0.00 11929.61 11258.96
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 7817.228 7817.228 0.345704 0.00006839 223.393 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 7817.23 7817.23 0.345704 21.11 14.19 0.00750618 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.11 0.00750618 47.0244 7817.53 0.00 8427.12 8427.12
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 11277.115 -999.000 1.008035 0.00040278 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 unknown 7/21 09:30:00 11277.12 10822.99 1.008035 21.70 15.46 0.00867665 12.80 11.87 0.00850000 25.98 0.01335930 20.56 0.0000 21.11 0.00867665 54.2560 10036.81 0.00 11548.49 10885.01
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 7816.752 7816.752 0.345683 0.00006838 223.379 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 7816.75 7816.75 0.345683 21.11 14.19 0.00750618 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.11 0.00750618 47.0244 7817.05 0.00 8426.61 8426.61
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 16220.796 16220.796 0.783178 0.00014191 402.538 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 16220.80 16220.80 0.783178 16.70 12.95 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00760887 47.9837 12192.48 0.00 16304.60 16304.60
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 3342.418 -999.000 0.301105 0.00011938 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown 7/21 17:00:00 3342.42 3229.23 0.301105 21.70 15.43 0.00864756 12.80 11.87 0.00850000 29.00 0.01336465 21.45 0.0000 21.11 0.00864756 54.0765 2998.05 0.00 3423.16 3247.70
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 2379.123 2379.123 0.105213 0.00002081 67.985 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 2379.12 2379.12 0.105213 21.11 14.27 0.00758915 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.11 0.00758915 47.5379 2379.21 0.00 2564.74 2564.74
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 3223.596 -999.000 0.289981 0.00011514 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 unknown 7/21 17:10:00 3223.60 3110.59 0.289981 21.70 15.44 0.00865295 12.80 11.87 0.00850000 28.84 0.01336437 21.41 0.0000 21.11 0.00865295 54.1098 2887.29 0.00 3301.41 3128.39
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2378.960 2378.960 0.105205 0.00002081 67.980 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 2378.96 2378.96 0.105205 21.11 14.27 0.00758915 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.11 0.00758915 47.5379 2379.05 0.00 2564.56 2564.56
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 15637.304 -999.000 1.386842 0.00055852 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 unknown 7/21 13:40:00 15637.30 14906.89 1.386842 21.70 15.49 0.00870629 12.80 11.87 0.00850000 30.14 0.01336669 21.78 0.0000 21.11 0.00870629 54.4391 13808.35 0.00 16012.15 14992.50
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 11377.436 11377.436 0.503153 0.00009953 325.115 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 11377.44 11377.44 0.503153 21.11 14.28 0.00760354 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.11 0.00760354 47.6265 11377.78 0.00 12265.13 12265.13
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 13491.742 13491.742 1.144039 0.00011803 301.664 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 13491.74 13491.74 1.144039 16.70 12.95 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00768008 48.4278 7606.79 0.00 13564.85 13564.85
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 13935.553 13935.553 1.199500 0.00012191 310.989 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:50:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:50:00 13935.55 13935.55 1.199500 16.70 12.95 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00768633 48.4672 7765.45 0.00 14011.12 14011.12
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 9342.043 9342.043 1.205839 0.00008173 200.064 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 9342.04 9342.04 1.205839 16.70 12.95 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00696941 44.0038 3151.27 0.00 9394.08 9394.08
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 9946.692 9946.692 0.401270 0.00008702 260.159 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:50:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:50:00 9946.69 9946.69 0.401270 16.70 12.95 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00772759 48.7237 7882.38 0.00 9996.64 9996.64
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 643701.884 -999.000 22.255590 0.02299154 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 643701.88 433747.87 22.255590 27.30 19.69 0.01161357 10.94 10.94 0.00850000 30.30 0.01336696 21.83 52.3979 23.99 0.00965544 50.6013 298389.52 0.00 653588.40 428493.43
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 259908.042 259908.042 6.676677 0.00227379 4086.351 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 259908.04 259908.04 6.676677 -16.30 -16.30 0.00092409 16.70 12.95 0.00800000 -16.30 0.00092409 -16.30 174.6596 21.01 0.00756583 47.7000 78558.74 0.00 210183.58 210183.58
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 75158.601 -999.000 2.051317 0.00268449 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 75158.60 45858.12 2.051317 30.30 21.83 0.01336696 11.91 11.51 0.00850000 30.30 0.01336696 21.83 99.9965 21.11 0.00870763 54.4459 171957.27 0.00 76128.50 46083.04
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 23955.952 23955.952 0.615395 0.00020958 376.643 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 23955.95 23955.95 0.615395 -16.30 -16.30 0.00092409 16.70 12.95 0.00800000 -16.30 0.00092409 -16.30 333.3216 21.11 0.00754094 47.2381 137032.52 0.00 19372.81 19372.81



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 8265.428 8265.428 1.317001 0.00007231 174.344 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 1.4453 1.474390 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 8265.43 8265.43 1.0000 1.54606042 1.317001 16.70 12.95 0.00800000 37036.7 40.00 20.89 0.00800000 60796.0 0.07230219 60.00 32.22 27.78 0.000 8265.43 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.00 0.00795865 21.00 0.00795865 50.1612 1486.84 0.00 8311.69 8311.69 1.54606042 16.60 13.15 0.00800000 36934.7 21.87 15.18 0.00800000 42310.8
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 4483.187 4483.187 0.207482 0.00003922 112.518 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 0.7839 0.799712 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 4483.19 4483.19 1.0000 0.24356849 0.207482 16.70 12.95 0.00800000 37036.7 40.00 20.89 0.00800000 60796.0 0.03921688 60.00 32.22 27.78 0.000 4483.19 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.00 0.00751014 21.00 0.00751014 47.3704 3416.35 0.00 4506.27 4506.27 0.24356849 16.60 13.15 0.00800000 36934.7 34.74 19.58 0.00800000 55435.8
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1772.633 1772.633 0.124539 0.00001551 40.729 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 0.3100 0.316203 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 1772.63 1772.63 1.0000 0.14619985 0.124539 16.70 12.95 0.00800000 37036.7 40.00 20.89 0.00800000 60796.0 0.01550619 60.00 32.22 27.78 0.000 1772.63 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.00 0.00743589 21.00 0.00743589 46.9062 1132.28 0.00 1782.14 1782.14 0.14619985 16.60 13.15 0.00800000 36934.7 28.55 17.55 0.00800000 49124.5
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 2756.091 2756.091 0.118735 0.00002411 70.612 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 0.4819 0.491632 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 2756.09 2756.09 1.0000 0.13938580 0.118735 16.70 12.95 0.00800000 37036.7 40.00 20.89 0.00800000 60796.0 0.02410903 60.00 32.22 27.78 0.000 2756.09 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.00 0.00731005 21.00 0.00731005 46.1217 2145.73 0.00 2770.21 2770.21 0.13938580 16.60 13.15 0.00800000 36934.7 36.09 20.00 0.00800000 56809.1
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1610.638 1610.638 0.057758 0.00001409 43.955 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 0.2816 0.287306 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 1610.64 1610.64 1.0000 0.06780389 0.057758 16.70 12.95 0.00800000 37036.7 40.00 20.89 0.00800000 60796.0 0.01408913 60.00 32.22 27.78 0.000 1610.64 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.00 0.00734616 21.00 0.00734616 46.3468 1313.71 0.00 1618.63 1618.63 0.06780389 16.60 13.15 0.00800000 36934.7 40.01 21.19 0.00800000 60806.9
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 11741.502 11741.502 1.738238 0.00010272 248.883 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 2.0531 2.094453 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 11741.50 11741.50 1.0000 2.04056137 1.738238 16.70 12.95 0.00800000 37036.7 40.00 20.89 0.00800000 60796.0 0.10270930 60.00 32.22 27.78 0.000 11741.50 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.00 0.00728305 21.00 0.00728305 45.9547 2807.54 0.00 11807.12 11807.12 2.04056137 16.60 13.15 0.00800000 36934.7 22.27 15.33 0.00800000 42720.9
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 12880.689 12880.689 0.840989 0.00011269 299.640 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 2.2523 2.297662 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 12880.69 12880.69 1.0000 0.98725791 0.840989 16.70 12.95 0.00800000 37036.7 40.00 20.89 0.00800000 60796.0 0.11267439 60.00 32.22 27.78 0.000 12880.69 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.00 0.00756408 21.00 0.00756408 47.7061 8555.88 0.00 12949.52 12949.52 0.98725791 16.60 13.15 0.00800000 36934.7 29.46 17.86 0.00800000 50051.4
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 33259.820 33259.820 2.522994 0.00029097 755.195 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 5.8159 5.932898 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 33259.82 33259.82 1.0000 2.96180706 2.522994 16.70 12.95 0.00800000 37036.7 40.00 20.89 0.00800000 60796.0 0.29094173 60.00 32.22 27.78 0.000 33259.82 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.00 0.00748122 21.00 0.00748122 47.1887 20286.12 0.00 33439.01 33439.01 2.96180706 16.60 13.15 0.00800000 36934.7 27.67 17.25 0.00800000 48224.8
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 12833.121 -999.000 1.154159 0.00045836 -999.000 -999.0000 1.00000 1.00000 1020.9269 1004.8586 1.1739 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.154159 1.35489649   4197.9300 999.8980 33.10941945 13.37 6.70 6.67 927070.14 1.3843 1.384241 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown unknown unknown 7/21 17:00:00 Sensible 12833.12 12380.92 1.0000 1.35489649 1.154159 21.70 15.44 0.00865377 43793.9 12.80 11.87 0.00850000 34322.2 0.45831403 6.70 13.37 6.67 0.000 12833.12 29.00 0.01336465 21.45 0.00000000 0.0000 21.11 0.00865377 21.11 0.00865377 54.1148 11491.77 0.00 13142.88 12451.75 1.35489649 21.70 15.70 0.00865377 43793.9 12.70 12.01 0.00845172 34093.6
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 7844.750 7844.750 0.346921 0.00006863 224.179 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.154159 1.35489649   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 1.3717 1.399349 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 7844.75 7844.75 1.0000 0.40725901 0.346921 21.11 14.20 0.00750779 40283.4 40.00 20.89 0.00800000 60796.0 0.06862229 60.00 32.22 27.78 0.000 7844.75 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.11 0.00750779 21.11 0.00750779 47.0344 7845.05 0.00 8456.79 8456.79 0.40725901 16.60 12.67 0.00750779 35688.6 36.98 19.90 0.00750779 56453.7
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 12412.024 -999.000 1.114738 0.00044332 -999.000 -999.0000 1.00000 1.00000 1020.9366 1004.8586 1.1739 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.114738 1.30861889   4197.9300 999.8980 33.10941945 13.37 6.70 6.67 927070.14 1.3388 1.338819 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 unknown unknown unknown 7/21 17:10:00 Sensible 12412.02 11960.45 1.0000 1.30861889 1.114738 21.70 15.44 0.00865896 43807.0 12.80 11.87 0.00850000 34322.2 0.44327524 6.70 13.37 6.67 0.000 12412.02 28.84 0.01336437 21.41 0.00000000 0.0000 21.11 0.00865896 21.11 0.00865896 54.1468 11099.25 0.00 12711.41 12028.90 1.30861889 21.70 15.70 0.00865896 43807.0 12.69 12.01 0.00845236 34093.4
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 7844.273 7844.273 0.346900 0.00006863 224.165 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.114738 1.30861889   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 1.3717 1.399264 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 7844.27 7844.27 1.0000 0.40723426 0.346900 21.11 14.20 0.00750780 40283.4 40.00 20.89 0.00800000 60796.0 0.06861812 60.00 32.22 27.78 0.000 7844.27 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.11 0.00750780 21.11 0.00750780 47.0344 7844.58 0.00 8456.27 8456.27 0.40723426 16.60 12.67 0.00750780 35688.6 36.98 19.90 0.00750780 56453.7
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 72608.968 -999.000 6.657805 0.00259338 -999.000 -999.0000 1.00000 1.00000 1020.7936 1004.8586 1.1739 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.657805 7.81576553   4197.9300 999.8980 33.10941945 13.37 6.70 6.67 927070.14 7.8321 7.831944 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 unknown unknown unknown 7/21 13:40:00 Sensible 72608.97 71221.36 1.0000 7.81576553 6.657805 21.70 15.38 0.00858203 43612.3 12.80 11.87 0.00850000 34322.2 2.59311110 6.70 13.37 6.67 0.000 72608.97 30.14 0.01336669 21.78 0.00000000 0.0000 21.11 0.00858203 21.11 0.00858203 53.6703 66295.67 0.00 74378.39 71627.03 7.81576553 21.70 15.63 0.00858203 43612.3 12.72 12.01 0.00844259 34095.8
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 44778.874 44778.874 1.980324 0.00039175 1279.626 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.657805 7.81576553   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 7.8301 7.987670 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 44778.87 44778.87 1.0000 2.32475241 1.980324 21.11 14.23 0.00754059 40367.2 40.00 20.89 0.00800000 60796.0 0.39170516 60.00 32.22 27.78 0.000 44778.87 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.11 0.00754059 21.11 0.00754059 47.2359 44779.72 0.00 48272.88 48272.88 2.32475241 16.60 12.70 0.00754059 35771.6 36.98 19.93 0.00754059 56536.3
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 65229.928 -999.000 5.570855 0.00232982 -999.000 -999.0000 1.00000 1.00000 1021.2948 1004.8586 1.1739 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.570855 6.53976802   4197.9300 999.8980 33.10941945 13.37 6.70 6.67 927070.14 7.0361 7.036006 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 unknown unknown unknown 7/21 15:10:00 Sensible 65229.93 60201.09 1.0000 6.53976802 5.570855 21.70 15.61 0.00885168 44296.5 12.80 11.87 0.00850000 34322.2 2.32958071 6.70 13.37 6.67 0.000 65229.93 30.21 0.01336679 21.80 0.00000000 0.0000 21.11 0.00885168 21.11 0.00885168 55.3352 55467.89 0.00 66764.57 60550.97 6.53976802 21.70 15.87 0.00885168 44296.5 12.63 12.01 0.00847531 34087.5
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 44791.712 44791.712 1.980892 0.00039186 1279.993 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.570855 6.53976802   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 7.8323 7.989960 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 44791.71 44791.71 1.0000 2.32541890 1.980892 21.11 14.23 0.00754059 40367.2 40.00 20.89 0.00800000 60796.0 0.39181746 60.00 32.22 27.78 0.000 44791.71 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.11 0.00754059 21.11 0.00754059 47.2359 44792.56 0.00 48286.72 48286.72 2.32541890 16.60 12.70 0.00754059 35771.6 36.98 19.93 0.00754059 56536.3
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 11649.067 -999.000 1.042902 0.00041607 -999.000 -999.0000 1.00000 1.00000 1020.9586 1004.8586 1.1739 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.042902 1.22428907   4197.9300 999.8980 33.10941945 13.37 6.70 6.67 927070.14 1.2565 1.256523 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown unknown unknown 7/21 10:00:00 Sensible 11649.07 11194.84 1.0000 1.22428907 1.042902 21.70 15.46 0.00867082 43837.2 12.80 11.87 0.00850000 34322.2 0.41602748 6.70 13.37 6.67 0.000 11649.07 26.77 0.01336069 20.80 0.00000000 0.0000 21.11 0.00867082 21.11 0.00867082 54.2200 10383.98 0.00 11929.61 11258.96 1.22428907 21.70 15.71 0.00867082 43837.2 12.69 12.01 0.00845384 34093.0
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 7817.228 7817.228 0.345704 0.00006839 223.393 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.042902 1.22428907   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 1.3669 1.394440 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 7817.23 7817.23 1.0000 0.40583022 0.345704 21.11 14.19 0.00750618 40279.3 40.00 20.89 0.00800000 60796.0 0.06838155 60.00 32.22 27.78 0.000 7817.23 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.11 0.00750618 21.11 0.00750618 47.0244 7817.53 0.00 8427.12 8427.12 0.40583022 16.60 12.67 0.00750618 35684.5 36.98 19.90 0.00750618 56449.6
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 11277.115 -999.000 1.008035 0.00040278 -999.000 -999.0000 1.00000 1.00000 1020.9695 1004.8586 1.1739 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.008035 1.18335723   4197.9300 999.8980 33.10941945 13.37 6.70 6.67 927070.14 1.2164 1.216403 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 unknown unknown unknown 7/21 09:30:00 Sensible 11277.12 10822.99 1.0000 1.18335723 1.008035 21.70 15.46 0.00867665 43852.0 12.80 11.87 0.00850000 34322.2 0.40274381 6.70 13.37 6.67 0.000 11277.12 25.98 0.01335930 20.56 0.00000000 0.0000 21.11 0.00867665 21.11 0.00867665 54.2560 10036.81 0.00 11548.49 10885.01 1.18335723 21.70 15.72 0.00867665 43852.0 12.69 12.01 0.00845456 34092.9
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 7816.752 7816.752 0.345683 0.00006838 223.379 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.008035 1.18335723   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 1.3668 1.394355 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 7816.75 7816.75 1.0000 0.40580551 0.345683 21.11 14.19 0.00750618 40279.3 40.00 20.89 0.00800000 60796.0 0.06837738 60.00 32.22 27.78 0.000 7816.75 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.11 0.00750618 21.11 0.00750618 47.0244 7817.05 0.00 8426.61 8426.61 0.40580551 16.60 12.67 0.00750618 35684.5 36.98 19.90 0.00750618 56449.6
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 16220.796 16220.796 0.783178 0.00014191 402.538 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 2.8364 2.893471 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 16220.80 16220.80 1.0000 0.91939259 0.783178 16.70 12.95 0.00800000 37036.7 40.00 20.89 0.00800000 60796.0 0.14189212 60.00 32.22 27.78 0.000 16220.80 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.00 0.00760887 21.00 0.00760887 47.9837 12192.48 0.00 16304.60 16304.60 0.91939259 16.60 13.15 0.00800000 36934.7 33.99 19.34 0.00800000 54668.8
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 3342.418 -999.000 0.301105 0.00011938 -999.000 -999.0000 1.00000 1.00000 1020.9154 1004.8586 1.1739 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.301105 0.35347431   4197.9300 999.8980 33.10941945 13.37 6.70 6.67 927070.14 0.3605 0.360529 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown unknown unknown 7/21 17:00:00 Sensible 3342.42 3229.23 1.0000 0.35347431 0.301105 21.70 15.43 0.00864756 43778.1 12.80 11.87 0.00850000 34322.2 0.11936901 6.70 13.37 6.67 0.000 3342.42 29.00 0.01336465 21.45 0.00000000 0.0000 21.11 0.00864756 21.11 0.00864756 54.0765 2998.05 0.00 3423.16 3247.70 0.35347431 21.70 15.69 0.00864756 43778.1 12.70 12.01 0.00845094 34093.8
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 2379.123 2379.123 0.105213 0.00002081 67.985 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.301105 0.35347431   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 0.4160 0.424389 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 2379.12 2379.12 1.0000 0.12351183 0.105213 21.11 14.27 0.00758915 40490.0 40.00 20.89 0.00800000 60796.0 0.02081148 60.00 32.22 27.78 0.000 2379.12 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.11 0.00758915 21.11 0.00758915 47.5379 2379.21 0.00 2564.74 2564.74 0.12351183 16.60 12.75 0.00758915 35894.5 36.98 19.96 0.00758915 56659.7
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 3223.596 -999.000 0.289981 0.00011514 -999.000 -999.0000 1.00000 1.00000 1020.9254 1004.8586 1.1739 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.289981 0.34041607   4197.9300 999.8980 33.10941945 13.37 6.70 6.67 927070.14 0.3477 0.347712 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 unknown unknown unknown 7/21 17:10:00 Sensible 3223.60 3110.59 1.0000 0.34041607 0.289981 21.70 15.44 0.00865295 43791.8 12.80 11.87 0.00850000 34322.2 0.11512550 6.70 13.37 6.67 0.000 3223.60 28.84 0.01336437 21.41 0.00000000 0.0000 21.11 0.00865295 21.11 0.00865295 54.1098 2887.29 0.00 3301.41 3128.39 0.34041607 21.70 15.69 0.00865295 43791.8 12.70 12.01 0.00845161 34093.6
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2378.960 2378.960 0.105205 0.00002081 67.980 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.289981 0.34041607   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 0.4160 0.424360 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 2378.96 2378.96 1.0000 0.12350340 0.105205 21.11 14.27 0.00758915 40490.0 40.00 20.89 0.00800000 60796.0 0.02081006 60.00 32.22 27.78 0.000 2378.96 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.11 0.00758915 21.11 0.00758915 47.5379 2379.05 0.00 2564.56 2564.56 0.12350340 16.60 12.75 0.00758915 35894.6 36.98 19.96 0.00758915 56659.7
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 15637.304 -999.000 1.386842 0.00055852 -999.000 -999.0000 1.00000 1.00000 1021.0245 1004.8586 1.1739 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.386842 1.62804896   4197.9300 999.8980 33.10941945 13.37 6.70 6.67 927070.14 1.6867 1.686713 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 unknown unknown unknown 7/21 13:40:00 Sensible 15637.30 14906.89 1.0000 1.62804896 1.386842 21.70 15.49 0.00870629 43927.1 12.80 11.87 0.00850000 34322.2 0.55846086 6.70 13.37 6.67 0.000 15637.30 30.14 0.01336669 21.78 0.00000000 0.0000 21.11 0.00870629 21.11 0.00870629 54.4391 13808.35 0.00 16012.15 14992.50 1.62804896 21.70 15.74 0.00870629 43927.1 12.68 12.01 0.00845820 34092.0
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 11377.436 11377.436 0.503153 0.00009953 325.115 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.386842 1.62804896   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 1.9895 2.029511 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 11377.44 11377.44 1.0000 0.59066369 0.503153 21.11 14.28 0.00760354 40526.8 40.00 20.89 0.00800000 60796.0 0.09952462 60.00 32.22 27.78 0.000 11377.44 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.11 0.00760354 21.11 0.00760354 47.6265 11377.78 0.00 12265.13 12265.13 0.59066369 16.60 12.76 0.00760354 35931.0 36.98 19.97 0.00760354 56696.0
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 13491.742 13491.742 1.144039 0.00011803 301.664 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 2.3592 2.406661 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 13491.74 13491.74 1.0000 1.34301674 1.144039 16.70 12.95 0.00800000 37036.7 40.00 20.89 0.00800000 60796.0 0.11801960 60.00 32.22 27.78 0.000 13491.74 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.00 0.00768008 21.00 0.00768008 48.4278 7606.79 0.00 13564.85 13564.85 1.34301674 16.60 13.15 0.00800000 36934.7 26.51 16.84 0.00800000 47035.0
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 13935.553 13935.553 1.199500 0.00012191 310.989 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 2.4368 2.485829 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:50:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:50:00 Sensible 13935.55 13935.55 1.0000 1.40812371 1.199500 16.70 12.95 0.00800000 37036.7 40.00 20.89 0.00800000 60796.0 0.12190186 60.00 32.22 27.78 0.000 13935.55 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.00 0.00768633 21.00 0.00768633 48.4672 7765.45 0.00 14011.12 14011.12 1.40812371 16.60 13.15 0.00800000 36934.7 26.36 16.79 0.00800000 46884.9
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 9342.043 9342.043 1.205839 0.00008173 200.064 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 1.6336 1.666437 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 Sensible 9342.04 9342.04 1.0000 1.41556440 1.205839 16.70 12.95 0.00800000 37036.7 40.00 20.89 0.00800000 60796.0 0.08171993 60.00 32.22 27.78 0.000 9342.04 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.68 0.00696941 21.00 0.00696941 44.0038 3151.27 0.00 9394.08 9394.08 1.41556440 16.60 13.15 0.00800000 36934.7 23.11 15.63 0.00800000 43571.0
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 9946.692 9946.692 0.401270 0.00008702 260.159 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 1.7393 1.774294 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:50:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:50:00 Sensible 9946.69 9946.69 1.0000 0.47106107 0.401270 16.70 12.95 0.00800000 37036.7 40.00 20.89 0.00800000 60796.0 0.08700913 60.00 32.22 27.78 0.000 9946.69 -16.30 0.00092409 -16.30 0.00000000 0.0000 21.00 0.00772759 21.00 0.00772759 48.7237 7882.38 0.00 9996.64 9996.64 0.47106107 16.60 13.15 0.00800000 36934.7 37.41 20.40 0.00800000 58156.3
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 643701.884 -999.000 22.255590 0.02299154 -999.000 -999.0000 1.00000 1.00000 1026.4290 1004.8586 1.1739 VAV WITH REHEAT FAN Fan:VariableVolume 22.255590 26.12640009   4197.9300 999.8980 33.10941945 13.37 6.70 6.67 927070.14 69.4340 69.434000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 Sensible 643701.88 433747.87 1.0000 26.12640009 22.255590 27.30 19.69 0.01161357 57062.3 10.94 10.94 0.00850000 32424.3 22.98919445 6.70 13.37 6.67 49866.733 593835.15 30.30 0.01336696 21.83 11.66146000 52.3979 23.99 0.00968317 23.99 0.00965544 50.6013 298389.52 0.00 653588.40 428493.43 26.12640009 27.30 19.98 0.01161357 57062.3 11.32 11.17 0.00819736 32045.9
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 259908.042 259908.042 6.676677 0.00227379 4086.351 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 VAV WITH REHEAT FAN Fan:VariableVolume 22.255590 26.12640009   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 45.4478 46.362483 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 259908.04 259908.04 1.0000 7.83792003 6.676677 -16.30 -16.30 0.00092409 -14095.8 16.70 12.95 0.00800000 37036.7 2.27355698 60.00 32.22 27.78 0.000 259908.04 -16.30 0.00092409 -16.30 11.66146000 174.6596 20.99 0.00757079 21.01 0.00756583 47.7000 78558.74 0.00 210183.58 210183.58 7.83792003 2.80 -2.91 0.00092409 5129.5 29.44 11.28 0.00092409 31945.7
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 75158.601 -999.000 2.051317 0.00268449 -999.000 -999.0000 1.00000 1.00000 1029.6885 1004.8586 1.1739 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.40800857   4197.9300 999.8980 33.10941945 13.37 6.70 6.67 927070.14 8.1071 8.107111 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 Sensible 75158.60 45858.12 1.0000 2.40809323 2.051317 30.30 21.83 0.01336696 64629.5 11.91 11.51 0.00850000 33418.7 2.68421723 6.70 13.37 6.67 2195.006 72963.59 30.30 0.01336696 21.83 2.05124512 99.9965 21.11 0.00870727 21.11 0.00870763 54.4459 171957.27 0.00 76128.50 46083.04 2.40809323 30.30 22.13 0.01336696 64629.5 11.72 11.57 0.00842116 33015.9
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 23955.952 23955.952 0.615395 0.00020958 376.643 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.40800857   4197.9300 999.8980 4.90387233 54.44 82.22 27.78 571882.21 4.1890 4.273271 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 23955.95 23955.95 1.0000 0.72242797 0.615395 -16.30 -16.30 0.00092409 -14095.8 16.70 12.95 0.00800000 37036.7 0.20955574 60.00 32.22 27.78 0.000 23955.95 -16.30 0.00092409 -16.30 2.05124512 333.3216 21.11 0.00753982 21.11 0.00754094 47.2381 137032.52 0.00 19372.81 19372.81 0.72242797 2.80 -2.91 0.00092409 5129.5 29.44 11.28 0.00092409 31945.7



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 11.66 22.26 -      
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 446.00 6700.50 0.50
RETAIL_1_FLR_1 2812.00 7482.50 2015.67
RETAIL_2_FLR_1 1358.83 7005.00 484.50
MECH_FLR_1 1535.33 7753.67 1222.00
STORAGE_FLR_1 1593.17 8234.17 1523.33
LAUNDRY_FLR_1 6701.33 3436.33 2550.00
CAFE_FLR_1 2978.50 6316.50 1248.50
LOBBY_FLR_1 2166.00 6081.33 619.67
ROOM_1_FLR_3 3302.00 8318.00 3198.33
ROOM_2_FLR_3 3619.67 8457.00 3565.50
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 2740.67 8760.00 2740.67
ROOM_5_FLR_3 3163.33 8241.33 3130.17
ROOM_6_FLR_3 3492.00 8383.00 3476.33
CORRIDOR_FLR_3 1577.50 7935.00 1389.67
ROOM_1_FLR_6 3812.00 8266.50 3649.17
ROOM_2_FLR_6 4089.83 8406.83 3996.83
ROOM_3_MULT9_FLR_6 2794.00 8286.00 2737.67
BANQUET_FLR_6 3859.17 3766.00 621.33
DINING_FLR_6 4591.33 2693.00 560.33
KITCHEN_FLR_6 8020.67 6398.17 6009.33
CORRIDOR_FLR_6 2155.33 7310.17 1351.83
Facility 8756.00 8760.00 8008.33
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 136.00 0.00 136.00
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.17 0.00 0.17
ROOM_1_FLR_3 0.00 5.50 0.00 5.50
ROOM_2_FLR_3 0.00 2.33 0.00 2.33
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.50 2.67 0.50 2.67
ROOM_5_FLR_3 0.00 2.67 0.00 2.67
ROOM_6_FLR_3 0.00 2.83 0.00 2.83
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 8.50 0.00 8.50
ROOM_2_FLR_6 0.00 3.67 0.00 3.67
ROOM_3_MULT9_FLR_6 0.00 7.50 0.00 7.50
BANQUET_FLR_6 0.00 18.83 0.00 18.83
DINING_FLR_6 0.00 26.83 0.00 26.83
KITCHEN_FLR_6 0.00 220.50 0.00 220.50
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 0.50 280.17 0.50 280.17
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.79 106.50 4826.41 0.964 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 2.680 0.139 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 1.398 0.046 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.623 0.052 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.518 0.052 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 22.154 0.149 0.000 0.000
CAFE_FLR_1 82.56 142.30 748.35 3.891 0.110 0.000 0.000
LOBBY_FLR_1 245.09 422.44 5183.56 1.716 0.045 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.472 0.180 0.000 0.062
ROOM_2_FLR_3 0.95 1.50 118.93 0.472 0.180 0.000 0.061
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.536 0.080 0.000 0.096
ROOM_5_FLR_3 0.95 1.50 118.94 0.472 0.180 0.000 0.063
ROOM_6_FLR_3 0.95 1.50 118.93 0.472 0.180 0.000 0.061
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.563 0.022 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.472 0.180 0.000 0.076
ROOM_2_FLR_6 0.95 1.50 118.93 0.472 0.180 0.000 0.073
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.537 0.147 0.000 0.120
BANQUET_FLR_6 144.99 249.90 1010.89 4.530 0.052 0.000 0.000
DINING_FLR_6 144.99 249.90 1010.89 4.885 0.052 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 20.564 0.150 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 1.093 0.037 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.79 106.50 4826.41 0.569 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 1.584 0.002 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 0.826 0.001 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.370 0.001 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.308 0.001 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 12.214 0.002 0.000 0.000
CAFE_FLR_1 82.56 142.30 748.35 2.377 0.002 0.000 0.000
LOBBY_FLR_1 245.09 422.44 5183.56 1.034 0.001 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.452 0.003 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.452 0.003 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.513 0.001 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.453 0.003 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.452 0.003 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.335 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.452 0.003 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.452 0.003 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.515 0.002 0.000 0.000
BANQUET_FLR_6 144.99 249.90 1010.89 2.370 0.001 0.000 0.000
DINING_FLR_6 144.99 249.90 1010.89 2.486 0.001 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 8.152 0.002 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 0.648 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.79 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.28 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.56 142.30 748.35 188.86 0.0000 0.676
LOBBY_FLR_1 VAV WITH REHEAT 245.09 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 144.99 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 144.99 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.25 1604.23 35184.81 11345.29 0.0000 137.584


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 40014174.98 0.00 40014174.98 0.00 40014174.98 26946214.98 8.09 3.28 8748.63 0.00
RETAIL_1_FLR_1 6160348.13 0.00 6160348.13 319496.36 6479844.49 2498216.28 0.00 0.00 8760.00 0.00
RETAIL_2_FLR_1 3709866.56 0.00 3709866.56 123326.00 3833192.56 2892943.94 123.95 28.69 8607.36 0.00
MECH_FLR_1 3505070.24 0.00 3505070.24 291469.39 3796539.64 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 1682111.57 0.00 1682111.57 168161.79 1850273.36 1821682.01 8756.83 0.17 3.00 0.00
LAUNDRY_FLR_1 58996819.30 0.00 58996819.30 397986.57 59394805.87 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 25079739.16 0.00 25079739.16 706264.79 25786003.95 21330615.53 540.49 179.21 8040.30 0.00
LOBBY_FLR_1 76479820.45 0.00 76479820.45 2017959.82 78497780.27 59728886.00 109.20 49.27 8601.52 0.00
ROOM_1_FLR_3 1946875.62 64015.20 2010890.82 185445.70 2196336.52 1946875.62 0.00 7939.83 820.17 0.00
ROOM_2_FLR_3 1946647.51 62233.95 2008881.47 185431.55 2194313.02 1946647.51 0.00 7939.83 820.17 0.00
ROOM_3_MULT19_FLR_3 26397887.27 67316.53 26465203.80 51741.43 26516945.23 26397887.27 0.00 7947.50 812.50 8760.00
ROOM_4_MULT19_FLR_3 26405105.73 61885.36 26466991.08 51755.58 26518746.66 26405105.73 0.00 7951.96 808.04 0.00
ROOM_5_FLR_3 1946875.62 64105.57 2010981.19 185445.70 2196426.89 1946875.62 0.00 7939.83 820.17 0.00
ROOM_6_FLR_3 1946647.51 62311.96 2008959.47 185431.55 2194391.02 1946647.51 0.00 7939.83 820.17 0.00
CORRIDOR_FLR_3 23071783.52 0.00 23071783.52 224241.16 23296024.69 14972100.18 3.02 1.52 8755.45 0.00
ROOM_1_FLR_6 486718.90 77724.19 564443.09 185484.89 749927.98 486718.90 0.00 7938.83 821.17 0.00
ROOM_2_FLR_6 486661.88 75362.08 562023.96 185470.74 747494.70 486661.88 0.00 7938.83 821.17 0.00
ROOM_3_MULT9_FLR_6 3126920.42 77647.63 3204568.05 94900.56 3299468.61 3126920.42 0.00 7938.83 821.17 0.00
BANQUET_FLR_6 39247749.70 0.00 39247749.70 452907.49 39700657.19 37458366.31 5014.36 249.10 3496.53 0.00
DINING_FLR_6 42311450.04 0.00 42311450.04 452907.49 42764357.53 37458366.31 2809.99 1038.59 4911.42 0.00
KITCHEN_FLR_6 55500584.86 0.00 55500584.86 405457.21 55906042.06 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 11862378.92 0.00 11862378.92 396838.89 12259217.81 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.45E+10 11681924.95 0.45E+10 18687591.97 0.46E+10 0.43E+10 8756.83 7990.16 8760.00 8760.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.2688 0.0000 1.2688 0.0000 1.2688 0.8545 8.09 3.28 8748.63
RETAIL_1_FLR_1 0.1953 0.0000 0.1953 0.0101 0.2055 0.0792 0.00 0.00 8760.00
RETAIL_2_FLR_1 0.1176 0.0000 0.1176 0.0039 0.1215 0.0917 123.95 28.69 8607.36
MECH_FLR_1 0.1111 0.0000 0.1111 0.0092 0.1204 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0533 0.0000 0.0533 0.0053 0.0587 0.0578 8756.83 0.17 3.00
LAUNDRY_FLR_1 1.8708 0.0000 1.8708 0.0126 1.8834 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.7953 0.0000 0.7953 0.0224 0.8177 0.6764 540.49 179.21 8040.30
LOBBY_FLR_1 2.4252 0.0000 2.4252 0.0640 2.4891 1.8940 109.20 49.27 8601.52
ROOM_1_FLR_3 0.0617 0.0020 0.0638 0.0059 0.0696 0.0617 0.00 7939.83 820.17
ROOM_2_FLR_3 0.0617 0.0020 0.0637 0.0059 0.0696 0.0617 0.00 7939.83 820.17
ROOM_4_MULT19_FLR_3 0.8373 0.0020 0.8393 0.0016 0.8409 0.8373 0.00 7951.96 808.04
ROOM_5_FLR_3 0.0617 0.0020 0.0638 0.0059 0.0696 0.0617 0.00 7939.83 820.17
ROOM_6_FLR_3 0.0617 0.0020 0.0637 0.0059 0.0696 0.0617 0.00 7939.83 820.17
CORRIDOR_FLR_3 0.7316 0.0000 0.7316 0.0071 0.7387 0.4748 3.02 1.52 8755.45
ROOM_1_FLR_6 0.0154 0.0025 0.0179 0.0059 0.0238 0.0154 0.00 7938.83 821.17
ROOM_2_FLR_6 0.0154 0.0024 0.0178 0.0059 0.0237 0.0154 0.00 7938.83 821.17
ROOM_3_MULT9_FLR_6 0.0992 0.0025 0.1016 0.0030 0.1046 0.0992 0.00 7938.83 821.17
BANQUET_FLR_6 1.2445 0.0000 1.2445 0.0144 1.2589 1.1878 5014.36 249.10 3496.53
DINING_FLR_6 1.3417 0.0000 1.3417 0.0144 1.3560 1.1878 2809.99 1038.59 4911.42
KITCHEN_FLR_6 1.7599 0.0000 1.7599 0.0129 1.7728 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.3762 0.0000 0.3762 0.0126 0.3887 0.1256 0.00 0.00 8760.00
Total Facility 80.0320 0.2082 80.2402 0.4679 80.7081 73.9670 8756.83 7990.16 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.53E+09 0.00 0.53E+09 0.22E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 89149799.71 612602.47 89762402.18 64690340.46 0.00 0.00 8760.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 16.9395 0.0000 16.9395 6.9969 0.00 0.00 8760.00
FLR_3_DOAS 2.8269 0.0194 2.8463 2.0513 0.00 0.00 8760.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 5272.27 3077.90 0.00 409.82 0.00 0.00 0.00 0.00 0.00
FLR_3_DOAS 0.00 6808.84 1951.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 16.0715 18.5490 0.0000 16.1023 0.0000 0.0000 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 2.8273 2.8271 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1318
Defaulted Fields 1181
Fields with Defaults 4005
Autosized Fields 350
Autosizable Fields 402
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 5145.72 76636.13 13-MAY-05:00 408101.44 20-JUL-19:50
Electricity:Building 2518.45 32589.73 03-JUN-05:00 151906.32 02-JAN-20:10
Electricity:Zone:BASEMENT 323.72 3705.45 02-JAN-02:10 24299.15 02-JAN-20:10
Electricity:SpaceType:GENERAL 2511.36 32448.58 03-JUN-05:00 151664.99 02-JAN-20:10
InteriorLights:Electricity 766.35 6756.79 03-JUN-05:00 62892.57 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 173.46 1576.23 02-JAN-02:10 14185.34 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 766.35 6756.79 03-JUN-05:00 62892.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity 766.35 6756.79 03-JUN-05:00 62892.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 173.46 1576.23 02-JAN-02:10 14185.34 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 766.35 6756.79 03-JUN-05:00 62892.57 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 18.80 222.61 02-JAN-02:10 1390.02 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.61 78.27 02-JAN-02:10 704.41 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.61 78.27 02-JAN-02:10 704.41 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 21.77 257.78 02-JAN-02:10 1609.65 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.97 90.64 02-JAN-02:10 815.72 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.97 90.64 02-JAN-02:10 815.72 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 29.11 327.88 02-JAN-02:10 2199.84 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 16.64 151.16 02-JAN-02:10 1360.40 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 16.64 151.16 02-JAN-02:10 1360.40 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 6.38 76.28 02-JAN-02:10 469.87 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.78 25.30 02-JAN-02:10 227.72 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.78 25.30 02-JAN-02:10 227.72 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 72.30 1002.39 02-JAN-02:10 4930.01 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.37 39.69 02-JAN-02:10 357.21 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.37 39.69 02-JAN-02:10 357.21 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 32.22 348.08 03-JUN-05:00 2727.18 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 17.87 144.87 03-JUN-05:00 1761.91 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 17.87 144.87 03-JUN-05:00 1761.91 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 270.83 3225.37 20-MAY-05:00 20294.39 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 121.83 1113.96 20-MAY-05:00 10265.18 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 121.83 1113.96 20-MAY-05:00 10265.18 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 18.66 264.62 01-JAN-02:10 1227.54 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 18.66 264.59 01-JAN-02:10 1227.39 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 304.77 4565.05 01-JAN-02:10 20923.25 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 76.02 643.59 01-JAN-02:10 5851.22 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 76.02 643.59 01-JAN-02:10 5851.22 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 304.86 4566.30 01-JAN-02:10 20928.98 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 76.04 643.77 01-JAN-02:10 5852.82 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 76.04 643.77 01-JAN-02:10 5852.82 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 18.66 264.62 01-JAN-02:10 1227.54 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 18.66 264.59 01-JAN-02:10 1227.39 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 4.66 66.15 01-JAN-02:10 306.88 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.59 13.47 01-JAN-02:10 122.50 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.59 13.47 01-JAN-02:10 122.50 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 4.66 66.15 01-JAN-02:10 306.85 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.59 13.47 01-JAN-02:10 122.49 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.59 13.47 01-JAN-02:10 122.49 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 36.10 540.75 01-JAN-02:10 2478.43 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 9.00 76.24 01-JAN-02:10 693.10 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 9.00 76.24 01-JAN-02:10 693.10 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 210.44 2524.33 03-JUN-05:00 9841.96 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 34.58 275.03 03-JUN-05:00 3094.06 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 34.58 275.03 03-JUN-05:00 3094.06 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 210.44 2524.33 03-JUN-05:00 9841.96 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 34.58 275.03 03-JUN-05:00 3094.06 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 34.58 275.03 03-JUN-05:00 3094.06 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 454.16 6253.02 02-JAN-02:10 18944.06 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.33 121.09 02-JAN-02:10 1089.83 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.33 121.09 02-JAN-02:10 1089.83 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
InteriorEquipment:Electricity 1745.01 25691.80 02-JAN-02:10 89475.41 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1745.01 25691.80 02-JAN-02:10 89475.41 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 433.74 5990.78 01-JAN-00:10 16487.34 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
Refrigeration:Electricity 61.79 1114.64 06-FEB-23:30 3445.63 05-SEP-06:20
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 968.11 2604.15 08-MAY-01:50 181612.53 21-JUL-20:30
LowTempRefrigeration:Refrigeration:Electricity 20.43 0.00 01-JAN-11:10 2027.53 01-APR-22:40
MedTempRefrigeration:Refrigeration:Electricity 34.27 934.50 07-FEB-04:10 1245.48 25-APR-07:40
Fans:Electricity 556.64 12674.19 11-OCT-01:20 40814.17 04-SEP-05:50
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 797.50 13632.47 05-NOV-04:10 48988.08 10-AUG-21:10
ExteriorEquipment:Electricity 651.48 9618.58 02-JAN-02:20 39726.11 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 32.45 553.74 10-JUN-05:00 1868.65 14-FEB-21:10
ElectricityPurchased:Facility 5145.72 76636.13 13-MAY-05:00 408101.44 20-JUL-19:50
ElectricityPurchased:Plant 5145.72 76636.13 13-MAY-05:00 408101.44 20-JUL-19:50
Cogeneration:ElectricityPurchased 5145.72 76636.13 13-MAY-05:00 408101.44 20-JUL-19:50
General:Cogeneration:ElectricityPurchased 5145.72 76636.13 13-MAY-05:00 408101.44 20-JUL-19:50
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 5145.72 76636.13 13-MAY-05:00 408101.44 20-JUL-19:50
ElectricityNet:Plant 5145.72 76636.13 13-MAY-05:00 408101.44 20-JUL-19:50
Cogeneration:ElectricityNet 5145.72 76636.13 13-MAY-05:00 408101.44 20-JUL-19:50
General:Cogeneration:ElectricityNet 5145.72 76636.13 13-MAY-05:00 408101.44 20-JUL-19:50
General:Fans:Electricity 556.64 12674.19 11-OCT-01:20 40814.17 04-SEP-05:50
ExteriorLights:Electricity 242.63 0.00 01-JAN-08:00 15448.40 01-JAN-00:10
General:ExteriorLights:Electricity 242.63 0.00 01-JAN-08:00 15448.40 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.91 18.80 01-JAN-00:10 188.00 01-JAN-07:10
HeatRecovery:Electricity 208.41 0.00 12-MAR-12:40 9938.94 11-JAN-19:10
General:HeatRecovery:Electricity 208.41 0.00 12-MAR-12:40 9938.94 11-JAN-19:10
WaterSystems:Electricity 90.75 1086.56 24-MAY-00:30 4738.64 30-OCT-18:10
Water Heater:WaterSystems:Electricity 90.75 1086.56 24-MAY-00:30 4738.64 30-OCT-18:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 718.15 0.00 01-JAN-00:10 168402.56 21-JUL-20:30
General:Cooling:Electricity 718.15 0.00 01-JAN-00:10 168402.56 21-JUL-20:30
Pumps:Electricity 104.51 47.91 16-MAR-07:20 7356.33 21-JUL-20:20
General:Pumps:Electricity 104.51 47.91 16-MAR-07:20 7356.33 21-JUL-20:20
WIRED_LTG_ELECTRICITY 26.98 0.00 01-JAN-00:10 2213.82 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 6338.23 29270.80 16-MAR-01:10 641554.11 06-FEB-18:00
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 4549.40 15908.90 11-JUN-10:10 555266.43 06-FEB-24:00
WaterSystems:NaturalGas 3262.21 15908.90 02-JAN-16:10 299708.18 16-MAR-17:50
Water Heater:WaterSystems:NaturalGas 3262.21 15908.90 02-JAN-16:10 299708.18 16-MAR-17:50
Heating:NaturalGas 1287.19 0.00 14-MAR-10:10 351311.48 06-FEB-09:10
Boiler:Heating:NaturalGas 1287.19 0.00 14-MAR-10:10 351311.48 06-FEB-09:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 2280.03 0.00 01-JAN-00:10 697147.28 21-JUL-20:30
PlantLoopCoolingDemand:HVAC 2280.03 0.00 01-JAN-00:10 697147.28 21-JUL-20:30
CoolingCoils:PlantLoopCoolingDemand 2280.03 0.00 01-JAN-00:10 697147.28 21-JUL-20:30


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 17-JAN-21:40
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 17-JAN-21:40
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 17-JAN-21:40
Water Heater:WaterSystems:Water 5742.51 0.00 23-MAR-00:30 0.00 02-JAN-19:10
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 17-JAN-21:40
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 17-JAN-21:40
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 17-JAN-21:40
Water Heater:WaterSystems:MainsWater 5742.51 0.00 23-MAR-00:30 0.00 02-JAN-19:10
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 17-JAN-07:20
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 17-JAN-07:20


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 19614.87 143601.59 12-MAR-14:00 2635937.18 21-JUL-20:30
EnergyTransfer:Building 4997.79 61874.88 06-JUN-03:40 329561.03 09-AUG-18:10
EnergyTransfer:Zone:KITCHEN_FLR_6 701.45 9042.31 04-SEP-02:50 36491.03 16-JUL-10:40
Refrigeration:EnergyTransfer 182.57 3985.20 07-FEB-04:00 10682.04 05-SEP-06:20
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 91.29 1992.60 07-FEB-04:00 5341.02 05-SEP-06:20
General:Refrigeration:EnergyTransfer 91.29 1992.60 07-FEB-04:00 5341.02 05-SEP-06:20
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 91.29 1992.60 07-FEB-04:00 5341.02 05-SEP-06:20
EnergyTransfer:Plant 7274.41 16706.79 10-OCT-01:30 1612582.86 21-JUL-20:30
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.59 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 69.69 1753.50 07-FEB-04:10 2686.44 25-APR-07:40
EnergyTransfer:Zone:BASEMENT 403.19 1398.26 06-JUN-03:40 27237.63 17-OCT-18:50
Heating:EnergyTransfer 335.51 0.00 11-JAN-18:10 126636.20 06-FEB-09:10
Heating:EnergyTransfer:Zone:BASEMENT 0.02 0.00 01-JAN-00:10 1451.53 03-MAY-02:20
General:Heating:EnergyTransfer 335.51 0.00 11-JAN-18:10 126636.20 06-FEB-09:10
General:Heating:EnergyTransfer:Zone:BASEMENT 0.02 0.00 01-JAN-00:10 1451.53 03-MAY-02:20
Cooling:EnergyTransfer 4570.99 48678.60 17-JAN-05:40 325937.40 09-AUG-18:10
Cooling:EnergyTransfer:Zone:BASEMENT 403.17 1176.54 06-JUN-03:40 27237.63 17-OCT-18:50
General:Cooling:EnergyTransfer 4570.99 48678.60 17-JAN-05:40 325937.40 09-AUG-18:10
General:Cooling:EnergyTransfer:Zone:BASEMENT 403.17 1176.54 06-JUN-03:40 27237.63 17-OCT-18:50
EnergyTransfer:Zone:RETAIL_1_FLR_1 37.42 0.00 15-APR-06:20 4404.20 21-SEP-13:00
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 3.37 0.00 02-JAN-21:10 1904.52 07-FEB-07:10
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 3.37 0.00 02-JAN-21:10 1904.52 07-FEB-07:10
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 34.05 0.00 01-JAN-00:10 4404.20 21-SEP-13:00
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 34.05 0.00 01-JAN-00:10 4404.20 21-SEP-13:00
EnergyTransfer:Zone:RETAIL_2_FLR_1 32.67 27.50 06-FEB-13:30 2117.97 10-AUG-21:00
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 198.71 20-NOV-18:00
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 198.71 20-NOV-18:00
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 32.67 27.50 06-FEB-13:30 2117.97 10-AUG-21:00
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 32.67 27.50 06-FEB-13:30 2117.97 10-AUG-21:00
EnergyTransfer:Zone:MECH_FLR_1 24.98 0.02 08-MAR-12:10 2120.02 21-JUL-20:00
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.86 0.00 01-JAN-00:10 809.48 07-FEB-05:00
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.86 0.00 01-JAN-00:10 809.48 07-FEB-05:00
Cooling:EnergyTransfer:Zone:MECH_FLR_1 24.11 0.00 01-JAN-13:10 2120.02 21-JUL-20:00
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 24.11 0.00 01-JAN-13:10 2120.02 21-JUL-20:00
EnergyTransfer:Zone:STORAGE_FLR_1 11.62 0.04 20-FEB-04:20 763.88 21-JUL-21:00
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 1.38 0.00 01-JAN-20:20 624.95 07-FEB-10:40
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 1.38 0.00 01-JAN-20:20 624.95 07-FEB-10:40
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 10.24 0.00 01-JAN-00:10 763.88 21-JUL-21:00
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 10.24 0.00 01-JAN-00:10 763.88 21-JUL-21:00
EnergyTransfer:Zone:LAUNDRY_FLR_1 585.67 5464.83 06-JUN-03:40 38791.36 21-JUL-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 588.13 14-OCT-02:20
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 588.13 14-OCT-02:20
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 585.67 5464.83 06-JUN-03:40 38791.36 21-JUL-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 585.67 5464.83 06-JUN-03:40 38791.36 21-JUL-20:00
EnergyTransfer:Zone:CAFE_FLR_1 214.45 5.21 09-JAN-09:40 15210.13 11-OCT-12:30
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.05 0.00 01-JAN-00:10 1924.26 06-FEB-09:20
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.05 0.00 01-JAN-00:10 1924.26 06-FEB-09:20
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 214.40 0.00 09-JAN-09:10 15210.13 11-OCT-12:30
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 214.40 0.00 09-JAN-09:10 15210.13 11-OCT-12:30
EnergyTransfer:Zone:LOBBY_FLR_1 727.62 4153.71 06-FEB-11:30 41543.36 20-JUL-21:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.03 0.00 01-JAN-00:10 3119.41 20-NOV-18:00
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.03 0.00 01-JAN-00:10 3119.41 20-NOV-18:00
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 727.60 4153.71 06-FEB-11:30 41543.36 20-JUL-21:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 727.60 4153.71 06-FEB-11:30 41543.36 20-JUL-21:10
EnergyTransfer:Zone:ROOM_1_FLR_3 70.02 0.07 25-APR-02:40 11797.21 10-AUG-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 29.22 0.00 01-JAN-08:10 7764.10 06-FEB-09:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 29.22 0.00 01-JAN-08:10 7764.10 06-FEB-09:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 40.80 0.00 01-JAN-00:10 11797.21 10-AUG-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 40.80 0.00 01-JAN-00:10 11797.21 10-AUG-15:10
EnergyTransfer:Zone:ROOM_2_FLR_3 69.17 0.12 22-APR-08:40 11373.01 10-JUL-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 33.85 0.00 01-JAN-08:10 7891.16 06-FEB-09:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 33.85 0.00 01-JAN-08:10 7891.16 06-FEB-09:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 35.32 0.00 01-JAN-00:10 11373.01 10-JUL-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 35.32 0.00 01-JAN-00:10 11373.01 10-JUL-18:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 335.98 0.38 23-NOV-15:10 59464.72 21-SEP-13:00
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 48.43 0.00 01-JAN-09:00 29633.10 07-FEB-05:00
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 48.43 0.00 01-JAN-09:00 29633.10 07-FEB-05:00
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 287.54 0.00 01-JAN-00:10 59464.72 21-SEP-13:00
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 287.54 0.00 01-JAN-00:10 59464.72 21-SEP-13:00
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 400.50 4.53 18-FEB-09:20 64578.62 21-JUL-15:20
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 94.83 0.00 01-JAN-08:10 49147.78 07-FEB-09:10
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 94.83 0.00 01-JAN-08:10 49147.78 07-FEB-09:10
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 305.67 0.00 01-JAN-00:10 64578.62 21-JUL-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 305.67 0.00 01-JAN-00:10 64578.62 21-JUL-15:20
EnergyTransfer:Zone:ROOM_5_FLR_3 69.44 0.10 11-OCT-03:20 10286.05 05-AUG-08:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 28.81 0.00 01-JAN-08:10 7750.12 06-FEB-19:10
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 28.81 0.00 01-JAN-08:10 7750.12 06-FEB-19:10
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 40.63 0.00 01-JAN-00:10 10286.05 05-AUG-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 40.63 0.00 01-JAN-00:10 10286.05 05-AUG-08:10
EnergyTransfer:Zone:ROOM_6_FLR_3 68.14 0.02 16-NOV-10:20 10130.37 04-JUL-08:10
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 33.31 0.00 01-JAN-08:10 8053.34 06-FEB-19:10
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 33.31 0.00 01-JAN-08:10 8053.34 06-FEB-19:10
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 34.82 0.00 01-JAN-00:10 10130.37 04-JUL-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 34.82 0.00 01-JAN-00:10 10130.37 04-JUL-08:10
EnergyTransfer:Zone:CORRIDOR_FLR_3 160.61 0.21 10-FEB-09:30 11196.36 21-JUL-19:10
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 2.94 0.00 01-JAN-00:10 4554.34 06-FEB-09:20
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 2.94 0.00 01-JAN-00:10 4554.34 06-FEB-09:20
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 157.68 0.00 01-JAN-11:10 11196.36 21-JUL-19:10
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 157.68 0.00 01-JAN-11:10 11196.36 21-JUL-19:10
EnergyTransfer:Zone:ROOM_1_FLR_6 20.35 0.08 09-MAY-01:20 3153.02 10-AUG-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 10.59 0.00 01-JAN-08:10 2436.51 06-FEB-09:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 10.59 0.00 01-JAN-08:10 2436.51 06-FEB-09:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 9.75 0.00 01-JAN-00:10 3153.02 10-AUG-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 9.75 0.00 01-JAN-00:10 3153.02 10-AUG-15:10
EnergyTransfer:Zone:ROOM_2_FLR_6 20.42 0.01 19-SEP-02:30 3069.88 10-JUL-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 12.06 0.00 01-JAN-08:10 2467.58 06-FEB-09:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 12.06 0.00 01-JAN-08:10 2467.58 06-FEB-09:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 8.36 0.00 01-JAN-00:10 3069.88 10-JUL-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 8.36 0.00 01-JAN-00:10 3069.88 10-JUL-18:10
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 92.70 0.49 27-JAN-18:40 16061.42 21-SEP-15:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 31.74 0.00 01-JAN-08:10 10424.63 06-FEB-09:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 31.74 0.00 01-JAN-08:10 10424.63 06-FEB-09:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 60.96 0.00 01-JAN-00:10 16061.42 21-SEP-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 60.96 0.00 01-JAN-00:10 16061.42 21-SEP-15:10
EnergyTransfer:Zone:BANQUET_FLR_6 415.77 5045.26 14-OCT-06:50 23161.02 20-JUL-21:20
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 332.23 07-OCT-06:40
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 332.23 07-OCT-06:40
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 415.77 5045.26 14-OCT-06:50 23161.02 20-JUL-21:20
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 415.77 5045.26 14-OCT-06:50 23161.02 20-JUL-21:20
EnergyTransfer:Zone:DINING_FLR_6 455.13 5814.97 14-OCT-06:50 24336.63 20-JUL-21:20
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 267.23 07-OCT-06:40
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 267.23 07-OCT-06:40
Cooling:EnergyTransfer:Zone:DINING_FLR_6 455.12 5814.97 14-OCT-06:50 24336.63 20-JUL-21:20
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 455.12 5814.97 14-OCT-06:50 24336.63 20-JUL-21:20
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 224.35 14-OCT-02:20
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 224.35 14-OCT-02:20
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 610.17 6638.57 04-SEP-02:50 31402.64 16-JUL-10:40
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 610.17 6638.57 04-SEP-02:50 31402.64 16-JUL-10:40
EnergyTransfer:Zone:CORRIDOR_FLR_6 80.49 0.24 08-FEB-21:40 6662.09 21-JUL-13:30
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 4.00 0.00 01-JAN-00:10 3528.24 07-FEB-07:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 4.00 0.00 01-JAN-00:10 3528.24 07-FEB-07:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 76.49 0.00 01-JAN-01:40 6662.09 21-JUL-13:30
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 76.49 0.00 01-JAN-01:40 6662.09 21-JUL-13:30
PlantLoopHeatingDemand:Facility 1743.69 9469.07 18-AUG-01:20 323079.53 06-FEB-09:10
PlantLoopHeatingDemand:Plant 802.94 9469.07 18-AUG-01:20 59808.81 15-FEB-08:00
WaterSystems:PlantLoopHeatingDemand 802.94 9469.07 18-AUG-01:20 59808.81 15-FEB-08:00
General:WaterSystems:PlantLoopHeatingDemand 802.94 9469.07 18-AUG-01:20 59808.81 15-FEB-08:00
EnergyTransfer:HVAC 7342.67 59.33 25-SEP-07:50 773279.55 20-JUL-21:00
HeatingCoils:EnergyTransfer 940.74 0.00 14-MAR-10:10 288639.45 06-FEB-09:10
PlantLoopHeatingDemand:HVAC 940.74 0.00 14-MAR-10:10 288639.45 06-FEB-09:10
HeatingCoils:PlantLoopHeatingDemand 940.74 0.00 14-MAR-10:10 288639.45 06-FEB-09:10
CoolingCoils:EnergyTransfer 2280.03 0.00 01-JAN-00:10 697147.28 21-JUL-20:30
HeatRecoveryForHeating:EnergyTransfer 3967.40 0.00 12-MAR-12:40 542214.32 11-DEC-06:00
HeatRecoveryForCooling:EnergyTransfer 154.50 0.00 01-JAN-00:10 229797.72 21-JUL-02:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 802.94 9469.07 18-AUG-01:20 59808.81 15-FEB-08:00
WaterUse:WaterSystems:EnergyTransfer 802.94 9469.07 18-AUG-01:20 59808.81 15-FEB-08:00
Boilers:EnergyTransfer 930.83 0.00 14-MAR-10:10 288829.10 06-FEB-09:10
Chillers:EnergyTransfer 2365.60 0.00 01-JAN-00:10 701928.47 21-JUL-20:30
HeatRejection:EnergyTransfer 3083.74 0.00 01-JAN-00:10 870331.03 21-JUL-20:30
General:HeatRejection:EnergyTransfer 3083.74 0.00 01-JAN-00:10 870331.03 21-JUL-20:30



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.020 -403.173 0.000 0.000 139.601 173.462 150.255 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -60.166
RETAIL_1_FLR_1 0.000 0.000 3.369 -34.051 0.000 0.000 15.694 8.614 10.186 21.965 0.000 0.069 0.000 0.000 -12.181 0.000 -5.021 -8.643
RETAIL_2_FLR_1 0.000 0.000 0.003 -32.670 0.000 0.000 17.166 9.975 11.795 0.000 0.000 0.026 0.000 0.000 0.000 0.000 -2.052 -4.244
MECH_FLR_1 0.000 0.000 0.862 -24.115 0.000 0.000 3.744 16.635 12.471 0.000 0.000 0.065 0.000 0.000 0.000 0.000 -4.694 -4.968
STORAGE_FLR_1 0.000 0.000 1.381 -10.243 0.000 0.000 2.906 2.785 3.598 0.000 0.000 0.039 2.217 0.000 0.000 0.000 -2.682 -0.000
LAUNDRY_FLR_1 0.000 0.000 0.005 -585.670 0.000 0.000 11.266 4.368 658.131 0.000 0.000 0.105 0.000 0.000 0.000 0.000 -6.905 -81.300
CAFE_FLR_1 0.000 0.000 0.052 -214.401 0.000 0.000 195.313 17.875 14.341 60.848 0.000 0.138 0.000 0.000 -36.170 0.000 -11.719 -26.276
LOBBY_FLR_1 0.000 0.000 0.026 -727.604 0.000 0.000 562.579 121.831 148.998 80.276 0.000 0.405 0.000 0.000 -49.508 0.000 -34.539 -102.465
ROOM_1_FLR_3 34.348 -31.256 0.000 -14.670 0.000 0.000 9.767 6.366 12.292 43.339 0.000 0.376 0.000 0.000 -27.970 0.000 -12.046 -20.547
ROOM_2_FLR_3 39.424 -26.438 0.000 -14.448 0.000 0.000 9.787 6.366 12.291 31.907 0.000 0.378 0.000 0.000 -28.907 0.000 -11.930 -18.431
ROOM_3_MULT19_FLR_3 69.557 -99.709 0.000 -208.956 0.000 0.000 0.000 76.021 228.754 262.813 0.000 0.954 0.000 0.000 -150.733 0.000 -82.543 -96.159
ROOM_4_MULT19_FLR_3 147.547 -162.074 0.000 -196.300 0.000 0.000 185.917 76.042 228.817 86.004 0.000 3.797 0.000 0.000 -162.501 0.000 -71.416 -135.833
ROOM_5_FLR_3 33.892 -30.957 0.000 -14.755 0.000 0.000 9.760 6.366 12.292 43.187 0.000 0.377 0.000 0.000 -27.483 0.000 -12.082 -20.598
ROOM_6_FLR_3 38.836 -25.781 0.000 -14.563 0.000 0.000 9.778 6.366 12.291 31.484 0.000 0.377 0.000 0.000 -28.178 0.000 -11.973 -18.637
CORRIDOR_FLR_3 0.000 0.000 2.937 -157.677 0.000 0.000 118.569 109.603 0.000 38.053 0.000 0.180 0.000 0.000 -36.732 0.000 -14.456 -60.478
ROOM_1_FLR_6 12.035 -7.553 0.000 -3.640 0.000 0.000 2.445 1.592 3.073 10.774 0.000 0.098 0.000 0.000 -6.957 0.000 -3.046 -8.821
ROOM_2_FLR_6 13.597 -6.313 0.000 -3.589 0.000 0.000 2.449 1.591 3.073 7.940 0.000 0.098 0.000 0.000 -7.188 0.000 -3.016 -8.643
ROOM_3_MULT9_FLR_6 38.968 -44.189 0.000 -23.996 0.000 0.000 21.923 9.005 27.097 56.790 0.000 0.603 0.000 0.000 -32.526 0.000 -15.047 -38.629
BANQUET_FLR_6 0.000 0.000 0.002 -415.774 0.000 0.000 318.313 34.581 175.857 8.414 0.000 0.072 0.000 0.000 -22.300 0.000 -8.204 -90.960
DINING_FLR_6 0.000 0.000 0.001 -455.128 0.000 0.000 316.519 34.581 175.857 8.212 0.000 0.071 0.000 0.000 -22.930 0.000 -8.278 -48.906
KITCHEN_FLR_6 0.000 0.000 0.001 -610.152 0.000 0.000 28.435 13.327 550.372 20.268 0.000 0.064 20.323 0.000 -15.189 0.000 -7.447 -0.000
CORRIDOR_FLR_6 0.000 0.000 3.998 -76.491 0.000 0.000 31.488 28.999 0.000 18.458 0.000 0.068 16.354 0.000 -16.474 0.000 -6.400 -0.000
Total Facility 428.204 -434.268 12.657 -4242.063 0.000 0.000 2013.420 766.350 2451.839 830.733 0.000 8.361 38.894 0.000 -683.927 0.000 -335.495 -854.705


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 03-NOV-18:57 0.00 0.00 0.00 -35702.61 0.00 0.00 5149.41 12609.30 9581.50 0.00 0.00 0.00 8362.41 0.00 -0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 17-OCT-13:14 0.00 0.00 0.00 -4544.31 0.00 0.00 151.19 195.67 252.59 6354.86 0.00 0.00 0.00 0.00 -0.00 0.00 -194.33 -2215.67
RETAIL_2_FLR_1 14-OCT-07:59 0.00 0.00 0.00 -2204.92 0.00 0.00 473.34 362.54 417.86 0.00 0.00 0.00 1029.04 0.00 -0.00 0.00 -77.86 0.00
MECH_FLR_1 21-JUL-20:00 0.00 0.00 0.00 -2120.07 0.00 0.00 129.08 1360.40 839.45 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -7.38 -201.48
STORAGE_FLR_1 14-OCT-07:59 0.00 0.00 0.00 -959.79 0.00 0.00 80.37 101.21 127.45 0.00 0.00 0.00 752.18 0.00 -0.00 0.00 -101.42 0.00
LAUNDRY_FLR_1 06-NOV-21:28 0.00 0.00 0.00 -52484.61 0.00 0.00 459.21 317.52 41967.83 0.00 0.00 0.00 10058.31 0.00 -0.00 0.00 -318.26 0.00
CAFE_FLR_1 31-OCT-23:20 0.00 0.00 0.00 -18707.41 0.00 0.00 9275.91 391.53 304.82 0.00 0.00 0.00 11388.47 0.00 -2188.74 0.00 -464.58 0.00
LOBBY_FLR_1 31-OCT-23:40 0.00 0.00 0.00 -64446.37 0.00 0.00 26700.08 2281.15 3167.12 0.00 0.00 0.00 36576.02 0.00 -2938.39 0.00 -1339.61 0.00
ROOM_1_FLR_3 30-JUN-18:02 0.00 -12920.76 0.00 -724.80 0.00 0.00 335.48 436.12 516.26 7083.53 0.00 44.94 5229.22 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_3 30-JUN-18:02 0.00 -12531.87 0.00 -727.10 0.00 0.00 335.49 436.07 516.20 7747.86 0.00 41.51 4181.84 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 21-SEP-13:00 0.00 -48899.62 0.00 -10563.99 0.00 0.00 0.00 1638.34 5097.90 75532.82 0.00 229.22 0.00 0.00 -0.00 0.00 0.00 -23034.67
ROOM_4_MULT19_FLR_3 09-AUG-18:02 0.00 -65430.43 0.00 -10091.97 0.00 0.00 6374.81 5209.05 9610.21 9086.09 0.00 809.67 44432.57 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 23-MAY-15:02 0.00 -11611.77 0.00 -714.82 0.00 0.00 235.29 137.21 273.93 3001.98 0.00 234.87 8443.32 0.00 -0.00 0.00 0.00 0.00
ROOM_6_FLR_3 23-MAY-15:02 0.00 -11219.19 0.00 -713.91 0.00 0.00 235.29 137.19 273.90 2654.88 0.00 236.82 8395.02 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 14-OCT-07:59 0.00 0.00 0.00 -13018.59 0.00 0.00 3332.84 3983.61 0.00 0.00 0.00 0.00 7327.37 0.00 -1088.53 0.00 -536.69 0.00
ROOM_1_FLR_6 30-JUN-18:02 0.00 -3366.77 0.00 -181.10 0.00 0.00 83.87 109.03 129.07 1757.90 0.00 11.68 1456.33 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_6 30-JUN-18:02 0.00 -3256.65 0.00 -181.71 0.00 0.00 83.87 109.02 129.05 1922.77 0.00 10.61 1183.04 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 23-MAY-15:02 0.00 -15654.08 0.00 -1158.19 0.00 0.00 529.40 194.07 603.86 4223.32 0.00 544.07 10717.55 0.00 -0.00 0.00 0.00 0.00
BANQUET_FLR_6 20-APR-22:20 0.00 0.00 0.00 -36717.52 0.00 0.00 15633.83 1031.35 6747.90 0.00 0.00 0.00 14727.42 0.00 -1124.22 0.00 -298.77 0.00
DINING_FLR_6 20-APR-22:20 0.00 0.00 0.00 -38773.50 0.00 0.00 15631.10 1031.35 6747.90 0.00 0.00 0.00 16808.40 0.00 -1144.69 0.00 -300.56 0.00
KITCHEN_FLR_6 29-OCT-16:14 0.00 0.00 0.00 -37988.79 0.00 0.00 657.34 242.18 26759.11 0.00 0.00 0.00 10816.14 0.00 -230.93 0.00 -255.06 0.00
CORRIDOR_FLR_6 21-JUL-13:30 0.00 0.00 0.00 -6662.83 0.00 0.00 308.45 658.76 0.00 3340.09 0.00 98.00 2257.53 0.00 -0.00 0.00 0.00 0.00
Total Facility 09-AUG-18:02 0.00 -155190.47 0.00 -211807.64 0.00 0.00 74200.99 53571.31 122326.88 37999.95 0.00 3569.81 75329.18 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 14-OCT-02:20 0.00 0.00 3598.68 0.00 0.00 0.00 6733.70 1576.23 2129.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -14037.84
RETAIL_1_FLR_1 14-OCT-08:00 0.00 0.00 3057.07 0.00 0.00 0.00 447.52 313.07 360.84 0.00 0.00 0.00 0.00 0.00 -312.34 0.00 -181.37 -3684.79
RETAIL_2_FLR_1 20-NOV-17:55 0.00 0.00 397.42 0.00 0.00 0.00 506.83 226.59 292.50 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -72.68 -1350.66
MECH_FLR_1 07-FEB-05:00 0.00 0.00 809.50 0.00 0.00 0.00 197.28 151.16 176.73 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -446.39 -888.27
STORAGE_FLR_1 07-FEB-11:03 0.00 0.00 624.95 0.00 0.00 0.00 33.72 63.26 89.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -236.14 -575.01
LAUNDRY_FLR_1 05-SEP-03:03 0.00 0.00 4687.42 0.00 0.00 0.00 606.12 39.69 9326.18 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -238.02 -14421.39
CAFE_FLR_1 14-OCT-07:24 0.00 0.00 2760.56 0.00 0.00 0.00 5609.58 477.67 508.04 0.00 0.00 0.00 0.00 0.00 -1443.27 0.00 -428.70 -7483.87
LOBBY_FLR_1 14-OCT-02:20 0.00 0.00 6782.96 0.00 0.00 0.00 26942.88 1140.58 2111.41 0.00 0.00 0.00 0.00 0.00 -2654.96 0.00 -1298.46 -33024.40
ROOM_1_FLR_3 07-FEB-09:01 11900.90 298.20 0.00 -298.20 0.00 0.00 108.89 215.61 453.05 0.00 0.00 0.00 0.00 0.00 -635.15 0.00 -1081.74 -10961.55
ROOM_2_FLR_3 07-FEB-09:01 11882.52 294.14 0.00 -294.14 0.00 0.00 108.89 215.58 452.99 0.00 0.00 0.00 0.00 0.00 -2061.37 0.00 -1079.96 -9518.65
ROOM_3_MULT19_FLR_3 07-FEB-05:00 29633.14 3356.87 0.00 -3356.87 0.00 0.00 0.00 643.59 3921.46 0.00 0.00 0.00 0.00 0.00 -19291.11 0.00 -5682.04 -9225.04
ROOM_4_MULT19_FLR_3 06-FEB-16:01 65261.12 3730.17 0.00 -3730.17 0.00 0.00 5585.72 1638.79 5099.29 0.00 0.00 0.00 0.00 0.00 -13779.01 0.00 -5317.51 -58488.40
ROOM_5_FLR_3 28-DEC-19:01 11578.70 298.68 0.00 -298.68 0.00 0.00 419.21 436.12 516.26 0.00 0.00 0.00 0.00 0.00 -2976.01 0.00 -870.14 -9104.14
ROOM_6_FLR_3 06-FEB-16:01 11593.73 291.80 0.00 -291.80 0.00 0.00 293.99 137.19 273.90 0.00 0.00 0.00 0.00 0.00 -2453.85 0.00 -1009.72 -8835.24
CORRIDOR_FLR_3 06-FEB-09:03 0.00 0.00 4606.91 0.00 0.00 0.00 1385.71 3983.61 0.00 0.00 0.00 0.00 0.00 0.00 -3553.66 0.00 -1341.63 -5080.94
ROOM_1_FLR_6 07-FEB-09:01 3485.17 75.16 0.00 -75.16 0.00 0.00 27.22 53.90 113.26 0.00 0.00 0.00 0.00 0.00 -166.67 0.00 -271.21 -3241.68
ROOM_2_FLR_6 07-FEB-09:01 3472.76 74.11 0.00 -74.11 0.00 0.00 27.22 53.90 113.25 0.00 0.00 0.00 0.00 0.00 -519.60 0.00 -270.75 -2876.78
ROOM_3_MULT9_FLR_6 06-FEB-09:02 16334.36 486.34 0.00 -486.34 0.00 0.00 244.99 304.96 998.70 0.00 0.00 0.00 0.00 0.00 -3100.39 0.00 -1231.19 -13551.44
BANQUET_FLR_6 07-OCT-06:34 0.00 0.00 1588.79 0.00 0.00 0.00 8556.39 1031.35 6747.90 0.00 0.00 0.00 0.00 0.00 -1018.74 0.00 -296.95 -16608.74
DINING_FLR_6 02-OCT-05:25 0.00 0.00 2378.00 0.00 0.00 0.00 12179.86 1375.14 5623.25 0.00 0.00 0.00 0.00 0.00 -1029.72 0.00 -298.96 -20227.58
KITCHEN_FLR_6 14-OCT-02:20 0.00 0.00 1570.95 0.00 0.00 0.00 1489.36 121.09 5415.98 0.00 0.00 0.00 0.00 0.00 -882.76 0.00 -264.64 -7449.98
CORRIDOR_FLR_6 07-FEB-07:10 0.00 0.00 3540.02 0.00 0.00 0.00 733.29 1317.51 0.00 0.00 0.00 0.00 0.00 0.00 -2149.10 0.00 -626.29 -2815.43
Total Facility 06-FEB-09:02 85055.33 78024.34 12065.86 -78024.34 0.00 0.00 24072.60 26712.50 88432.23 0.00 0.00 0.00 0.00 0.00 -62775.13 0.00 -27242.50 -146320.89



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 22.3818 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 22.2556 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 11.6609 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.6609 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.000000 142.3000 0.003581 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.001045 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5278 2.5278 1.3170 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3982 0.3982 0.2075 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2390 0.2390 0.1245 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2279 0.2279 0.1187 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1096 0.1096 0.0571 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.3363 3.3363 1.7382 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6142 1.6142 0.8410 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.8426 4.8426 2.5230 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5032 1.5032 0.7832 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1959 2.1959 1.1440 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.3023 2.3023 1.1995 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.3145 2.3145 1.2058 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7702 0.7702 0.4013 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 22.3818 22.2556 22.3818 11.6609 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3170 1.3170 1.3170 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2075 0.2075 0.2075 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1245 0.1245 0.1245 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1187 0.1187 0.1187 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0571 0.0571 0.0571 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7382 1.7382 1.7382 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8410 0.8410 0.8410 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5230 2.5230 2.5230 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7832 0.7832 0.7832 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1440 1.1440 1.1440 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1995 1.1995 1.1995 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2058 1.2058 1.2058 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4013 0.4013 0.4013 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 11.6609 11.6609 11.6609 11.6609 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.50
Number of hours cooling loads not met 280.17
Number of hours not met 280.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 1287.19 351311.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 718.15 168402.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 766.35 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 242.63 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 959.56 59492.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 14.43 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 8.99 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 32.45 1868.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.91 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 556.64 40814.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 104.51 7356.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 208.41 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.75 4738.64 3262.21 299708.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 20.43 2027.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 34.27 1245.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1806.80 5145.72
Natural Gas 1788.84 6338.23
Additional 0.00 0.00
Total 3595.64 11483.95


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 67.55
Space Heating 0.00
Space Cooling 63.30
Fans (All) 49.06
Service Water Heating 8.00
Receptacle Equipment 153.81
Miscellaneous (All) 453.56
Subtotal 453.56


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 113.46
Service Water Heating 287.54
Miscellaneous (All) 558.67
Subtotal 558.67


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 6.67
Space Heating 11.21
Space Cooling 6.25
Fans (All) 4.85
Service Water Heating 29.20
Receptacle Equipment 30.77
Miscellaneous 11.05


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2667. 8760.
LTG_SCH_LOBBY 3061. 8760.
LTG_SCH_STORAGE 1339. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 2678. 8760.
LTG_SCH_GUESTROOM 2482. 8760.
LTG_SCH_CORRIDOR 3061. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3924. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 18.89 365 18.89 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 23.33 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8759.83 0.17 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8759.33 0.67 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8759.33 0.00 0.00 0.00 0.00
Max 8760.00 0.67 0.00 0.00 0.00
Average 8759.96 0.04 0.00 0.00 0.00
Sum 192719.17 0.83 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37202.00 1.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108262.67 6.33 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 6.33 0.00 0.00 0.00
Average 288886.71 0.33 0.00 0.00 0.00
Sum 6355507.67 7.33 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8715.17 44.83 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8261.67 498.33 0.00 0.00 0.00
LOBBY_FLR_1 8250.67 509.33 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8757.50 2.50 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8747.33 12.67 0.00 0.00 0.00
ROOM_1_FLR_6 8759.50 0.50 0.00 0.00 0.00
ROOM_2_FLR_6 8759.67 0.33 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8758.50 1.50 0.00 0.00 0.00
BANQUET_FLR_6 8197.33 562.67 0.00 0.00 0.00
DINING_FLR_6 8263.83 496.17 0.00 0.00 0.00
KITCHEN_FLR_6 8722.83 37.17 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8197.33 0.00 0.00 0.00 0.00
Max 8760.00 562.67 0.00 0.00 0.00
Average 8661.55 98.45 0.00 0.00 0.00
Sum 190554.00 2166.00 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 58672.83 483.17 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 649430.33 60986.67 0.00 0.00 0.00
LOBBY_FLR_1 1936645.50 178783.50 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100136.67 221.33 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1130373.50 115341.50 0.00 0.00 0.00
DINING_FLR_6 1142619.50 103095.50 0.00 0.00 0.00
KITCHEN_FLR_6 107976.83 292.17 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 1936645.50 178783.50 0.00 0.00 0.00
Average 268014.14 20872.90 0.00 0.00 0.00
Sum 5896311.17 459203.83 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:50

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

For: Environment

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A

For: Environment

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO

For: Environment

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.327974E+11 20981.29 17-JAN-21:44 4.40 3.47 0.783350E+10 4837.00 17-JAN-22:19 4.40 3.43
February 0.286355E+11 18243.87 19-FEB-11:36 5.20 1.65 0.692512E+10 4836.89 01-FEB-22:10 5.20 1.65
March 0.296126E+11 21794.05 12-MAR-06:42 6.02 6.02 0.731889E+10 4707.15 29-MAR-21:10 4.40 2.30
April 0.282532E+11 21414.59 23-APR-21:27 6.95 3.60 0.697289E+10 4710.91 11-APR-21:10 6.95 3.60
May 0.296960E+11 20375.25 02-MAY-23:56 8.90 5.12 0.715289E+10 4492.65 01-MAY-21:10 8.90 5.12
June 0.314004E+11 20694.70 04-JUN-02:43 8.48 5.97 0.722180E+10 4677.16 14-JUN-21:19 12.57 7.74
July 0.345568E+11 15988.08 16-JUL-10:33 28.50 22.06 0.768609E+10 4829.75 28-JUL-21:19 21.10 19.80
August 0.369917E+11 18736.87 31-AUG-21:00 13.90 11.74 0.803818E+10 4837.15 08-AUG-21:49 13.90 11.74
September 0.376857E+11 35373.65 30-SEP-05:35 7.20 6.12 0.789784E+10 4918.99 30-SEP-02:00 7.20 6.12
October 0.400042E+11 35620.85 26-OCT-22:50 6.78 5.71 0.819805E+10 4949.28 31-OCT-22:40 7.13 5.02
November 0.375831E+11 35702.72 03-NOV-18:57 5.00 2.83 0.792369E+10 4909.32 10-NOV-05:00 10.00 6.51
December 0.359548E+11 34234.80 13-DEC-20:47 4.32 3.84 0.809124E+10 4855.71 01-DEC-22:10 4.32 3.84
                     
Annual Sum or Average 0.403172E+12         0.912602E+11        
Minimum of Months 0.282532E+11 15988.08   4.32 1.65 0.692512E+10 4492.65   4.32 1.65
Maximum of Months 0.400042E+11 35702.72   28.50 22.06 0.819805E+10 4949.28   21.10 19.80



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.444192E+09 2426.98 15-JAN-11:34 3.87 2.17 0.620958E+09 375.11 17-JAN-05:49 7.30 2.93
February 0.457985E+09 2436.32 17-FEB-11:36 4.23 1.19 0.561726E+09 371.68 14-FEB-22:00 4.23 1.19
March 0.197635E+10 3146.06 15-MAR-13:30 25.55 15.84 0.634400E+09 437.75 15-MAR-21:30 17.80 13.45
April 0.259493E+10 3034.95 11-APR-14:12 8.67 5.31 0.617471E+09 406.41 07-APR-21:30 8.67 5.31
May 0.381502E+10 2522.71 22-MAY-23:32 10.20 7.93 0.654374E+09 434.57 23-MAY-21:30 20.60 13.34
June 0.456830E+10 2751.17 13-JUN-06:12 8.70 7.91 0.679604E+09 468.52 27-JUN-21:30 21.95 20.56
July 0.526471E+10 3306.30 21-JUL-13:30 31.15 21.91 0.737296E+09 486.30 19-JUL-21:30 31.15 21.91
August 0.526295E+10 3637.61 18-AUG-13:30 29.70 20.75 0.733409E+09 489.86 10-AUG-21:30 29.70 20.75
September 0.453222E+10 4404.20 21-SEP-13:00 25.00 16.50 0.668446E+09 473.44 21-SEP-21:30 17.75 15.84
October 0.311730E+10 4544.38 17-OCT-13:14 8.17 2.81 0.645603E+09 452.57 11-OCT-21:30 8.17 2.81
November 0.162839E+10 3696.92 03-NOV-12:40 8.53 4.68 0.605767E+09 386.95 03-NOV-22:19 6.10 2.71
December 0.388490E+09 2507.67 16-DEC-11:40 3.87 1.42 0.621294E+09 367.25 01-DEC-22:10 3.87 1.42
                     
Annual Sum or Average 0.340508E+11         0.778035E+10        
Minimum of Months 0.388490E+09 2426.98   3.87 1.19 0.561726E+09 367.25   3.87 1.19
Maximum of Months 0.526471E+10 4544.38   31.15 21.91 0.737296E+09 489.86   31.15 21.91



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.194840E+10 1507.58 17-JAN-21:58 4.40 3.43 0.746446E+09 501.04 17-JAN-22:10 4.40 3.43
February 0.174934E+10 1513.32 15-FEB-00:30 7.50 3.24 0.674615E+09 509.53 22-FEB-23:19 6.47 5.58
March 0.250414E+10 1941.69 12-MAR-06:42 6.02 6.02 0.808989E+09 569.51 15-MAR-21:40 17.43 13.33
April 0.262442E+10 2109.09 23-APR-21:27 6.95 3.60 0.817600E+09 569.50 21-APR-21:40 6.95 3.60
May 0.300389E+10 1970.29 02-MAY-23:56 8.90 5.12 0.889284E+09 569.57 26-MAY-21:10 14.72 11.23
June 0.326366E+10 2023.22 04-JUN-02:43 8.48 5.97 0.900931E+09 579.46 06-JUN-03:49 6.78 6.53
July 0.361393E+10 2092.10 19-JUL-21:00 26.70 22.02 0.944579E+09 569.55 13-JUL-23:40 26.70 22.02
August 0.357150E+10 2117.97 10-AUG-21:00 26.10 18.56 0.946042E+09 569.56 08-AUG-21:49 26.10 18.56
September 0.314313E+10 2090.52 03-SEP-02:62 8.22 7.46 0.888291E+09 569.55 07-SEP-21:19 18.90 14.02
October 0.280353E+10 2205.00 14-OCT-07:59 6.10 5.58 0.860734E+09 569.53 12-OCT-21:10 6.10 5.58
November 0.244995E+10 1926.30 03-NOV-20:49 5.60 2.90 0.788243E+09 555.75 01-NOV-21:19 5.60 2.90
December 0.199356E+10 1531.33 01-DEC-21:47 6.10 3.37 0.751769E+09 515.27 01-DEC-22:10 6.02 3.25
                     
Annual Sum or Average 0.326694E+11         0.100175E+11        
Minimum of Months 0.174934E+10 1507.58   4.40 2.90 0.674615E+09 501.04   4.40 2.90
Maximum of Months 0.361393E+10 2205.00   26.70 22.02 0.946042E+09 579.46   26.70 22.02



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.496619E+09 1277.43 17-JAN-21:58 4.40 3.43 0.151894E+09 94.76 17-JAN-22:10 4.40 3.43
February 0.404978E+09 1227.84 22-FEB-23:00 7.20 6.11 0.137301E+09 93.28 22-FEB-22:10 7.20 6.11
March 0.139646E+10 1727.17 12-MAR-06:42 6.02 6.02 0.157209E+09 111.22 15-MAR-21:19 18.17 13.56
April 0.205213E+10 1842.93 23-APR-21:27 6.95 3.60 0.155859E+09 104.41 21-APR-21:40 6.95 3.60
May 0.262143E+10 1760.72 27-MAY-04:55 8.30 6.35 0.174907E+09 113.11 23-MAY-21:19 8.30 6.35
June 0.292987E+10 1887.23 04-JUN-02:43 8.48 5.97 0.183627E+09 120.46 19-JUN-21:10 18.90 15.17
July 0.330813E+10 2120.02 21-JUL-20:00 23.30 21.68 0.196836E+09 120.45 24-JUL-21:19 20.93 17.61
August 0.322896E+10 1822.05 10-AUG-21:00 26.10 18.56 0.196222E+09 120.46 08-AUG-21:00 26.10 18.56
September 0.279410E+10 1904.95 03-SEP-02:62 8.22 7.46 0.179182E+09 120.42 15-SEP-21:19 21.50 20.31
October 0.237530E+10 2038.48 14-OCT-07:59 6.10 5.58 0.167147E+09 111.17 12-OCT-21:10 6.10 5.58
November 0.183062E+10 1632.50 03-NOV-20:49 5.60 2.90 0.152133E+09 103.62 27-NOV-22:00 6.10 5.06
December 0.676012E+09 1296.41 01-DEC-21:47 6.10 3.37 0.152114E+09 97.54 01-DEC-22:10 6.02 3.25
                     
Annual Sum or Average 0.241146E+11         0.200443E+10        
Minimum of Months 0.404978E+09 1227.84   4.40 2.90 0.137301E+09 93.28   4.40 3.25
Maximum of Months 0.330813E+10 2120.02   26.10 21.68 0.196836E+09 120.46   26.10 20.31



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 48758358.68 577.97 17-JAN-21:58 4.40 3.43 0.116691E+09 69.47 17-JAN-05:49 4.40 3.43
February 35274459.16 564.99 22-FEB-23:00 7.20 6.11 0.105502E+09 69.09 22-FEB-23:19 6.47 5.58
March 0.469739E+09 723.19 17-MAR-17:03 6.10 3.86 0.119436E+09 81.72 15-MAR-21:49 6.10 3.86
April 0.875217E+09 859.35 23-APR-21:27 6.95 3.60 0.117177E+09 77.59 09-APR-23:49 6.95 3.60
May 0.122021E+10 839.52 27-MAY-04:55 8.30 6.35 0.131174E+09 83.32 23-MAY-22:10 8.30 6.35
June 0.136959E+10 892.97 04-JUN-02:43 8.48 5.97 0.138196E+09 90.68 27-JUN-21:49 21.78 20.28
July 0.153433E+10 763.88 21-JUL-21:00 22.80 21.20 0.148961E+09 92.66 21-JUL-23:19 22.80 21.20
August 0.150262E+10 719.25 10-AUG-10:33 28.53 20.68 0.148154E+09 92.50 10-AUG-22:10 25.03 19.46
September 0.130685E+10 898.68 03-SEP-02:62 8.22 7.46 0.134688E+09 88.48 15-SEP-22:10 21.10 19.98
October 0.107875E+10 959.80 14-OCT-07:59 6.10 5.58 0.125155E+09 81.54 12-OCT-22:10 6.10 5.58
November 0.696497E+09 776.53 06-NOV-05:05 8.90 6.96 0.114814E+09 75.45 27-NOV-22:00 6.10 5.06
December 0.104716E+09 582.87 01-DEC-21:47 6.10 3.37 0.116708E+09 70.43 01-DEC-22:10 6.02 3.25
                     
Annual Sum or Average 0.102425E+11         0.151666E+10        
Minimum of Months 35274459.16 564.99   4.40 3.37 0.105502E+09 69.09   4.40 3.25
Maximum of Months 0.153433E+10 959.80   28.53 21.20 0.148961E+09 92.66   25.03 21.20



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.463775E+11 48379.95 17-JAN-21:44 4.40 3.47 0.576971E+09 390.08 17-JAN-22:10 4.40 3.43
February 0.418288E+11 48716.43 14-FEB-20:26 4.70 0.80 0.521048E+09 450.45 14-FEB-22:00 7.20 2.78
March 0.483455E+11 48431.07 09-MAR-20:54 6.10 6.10 0.588245E+09 513.73 17-MAR-21:00 5.00 2.82
April 0.478666E+11 50584.66 21-APR-20:49 6.88 3.45 0.574129E+09 524.40 03-APR-22:19 6.88 3.45
May 0.510389E+11 50793.72 06-MAY-21:28 7.25 5.73 0.595697E+09 414.99 01-MAY-21:10 7.25 5.73
June 0.507845E+11 38543.49 27-JUN-20:00 23.90 21.99 0.576904E+09 431.53 06-JUN-03:49 23.90 21.99
July 0.530802E+11 38791.36 21-JUL-20:00 23.30 21.68 0.594344E+09 381.75 06-JUL-21:10 23.30 21.68
August 0.530129E+11 38720.81 10-AUG-20:00 25.60 18.99 0.595260E+09 381.75 03-AUG-21:10 25.60 18.99
September 0.500014E+11 41960.12 06-SEP-06:47 7.02 5.98 0.575039E+09 385.86 30-SEP-02:00 7.80 6.37
October 0.498097E+11 49725.35 17-OCT-19:24 3.35 1.45 0.594559E+09 459.10 31-OCT-22:40 7.13 5.02
November 0.470589E+11 52483.10 06-NOV-21:28 5.00 2.74 0.572303E+09 456.79 27-NOV-22:49 6.20 5.15
December 0.464639E+11 49526.77 13-DEC-20:47 4.32 3.84 0.578154E+09 435.56 13-DEC-21:10 4.40 3.92
                     
Annual Sum or Average 0.585669E+12         0.694265E+10        
Minimum of Months 0.418288E+11 38543.49   3.35 0.80 0.521048E+09 381.75   4.40 2.78
Maximum of Months 0.530802E+11 52483.10   25.60 21.99 0.595697E+09 524.40   25.60 21.99



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.119472E+11 10668.88 15-JAN-11:34 3.87 2.17 0.842629E+10 6388.42 17-JAN-05:49 7.30 2.93
February 0.110374E+11 11040.41 15-FEB-00:30 7.50 3.24 0.762421E+10 6366.17 15-FEB-00:49 7.30 3.10
March 0.168176E+11 14939.76 08-MAR-13:23 6.40 0.66 0.923888E+10 6461.52 15-MAR-23:19 17.20 13.28
April 0.174797E+11 13984.50 23-APR-21:27 6.95 3.60 0.924433E+10 6686.70 06-APR-22:49 6.95 3.60
May 0.200837E+11 14284.11 09-MAY-00:55 8.30 3.72 0.100154E+11 6795.97 23-MAY-04:30 7.20 5.41
June 0.214074E+11 12968.16 06-JUN-02:04 7.70 7.44 0.101343E+11 6918.33 06-JUN-03:49 6.78 6.53
July 0.237395E+11 11672.46 20-JUL-21:10 25.50 24.00 0.106502E+11 6462.03 11-JUL-04:19 25.50 24.00
August 0.237947E+11 12764.00 17-AUG-15:03 28.90 16.32 0.106869E+11 6462.02 12-AUG-01:19 28.90 16.32
September 0.217068E+11 15072.61 21-SEP-14:10 25.68 16.62 0.100657E+11 6666.17 06-SEP-01:19 25.68 16.62
October 0.191536E+11 18710.04 31-OCT-23:20 6.87 4.91 0.973094E+10 6828.84 31-OCT-22:40 6.87 4.91
November 0.154795E+11 14710.86 03-NOV-12:40 8.53 4.68 0.887726E+10 6406.99 04-NOV-04:40 10.00 7.97
December 0.117511E+11 10907.25 16-DEC-11:40 3.87 1.42 0.846140E+10 6235.23 01-DEC-04:00 3.87 1.42
                     
Annual Sum or Average 0.214398E+12         0.113156E+12        
Minimum of Months 0.110374E+11 10668.88   3.87 0.66 0.762421E+10 6235.23   3.87 1.42
Maximum of Months 0.237947E+11 18710.04   28.90 24.00 0.106869E+11 6918.33   28.90 24.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.478433E+11 32449.71 17-JAN-21:58 4.40 3.43 0.268358E+11 18929.01 17-JAN-05:49 4.40 3.43
February 0.432079E+11 33988.00 15-FEB-00:30 7.50 3.24 0.242234E+11 18898.81 15-FEB-00:49 7.30 3.10
March 0.561083E+11 46777.63 29-MAR-21:00 4.40 2.30 0.291047E+11 19750.62 17-MAR-21:00 4.40 2.30
April 0.575851E+11 59795.74 20-APR-22:30 6.95 4.44 0.291557E+11 19837.52 03-APR-22:19 6.95 4.44
May 0.653616E+11 61158.08 23-MAY-04:22 7.20 5.41 0.313007E+11 20166.46 23-MAY-04:30 7.20 5.41
June 0.701144E+11 63477.84 06-JUN-03:42 6.78 6.53 0.310072E+11 20715.51 06-JUN-03:49 6.78 6.53
July 0.772126E+11 41543.36 20-JUL-21:10 25.50 24.00 0.321747E+11 19300.64 06-JUL-04:49 25.50 24.00
August 0.767154E+11 41416.07 10-AUG-21:10 26.02 18.64 0.323263E+11 19395.02 04-AUG-04:30 26.02 18.64
September 0.687517E+11 57539.39 06-SEP-01:37 8.17 7.50 0.309073E+11 19744.73 06-SEP-03:49 6.78 6.00
October 0.619975E+11 64454.80 31-OCT-23:40 6.73 4.84 0.307132E+11 19857.44 31-OCT-22:40 6.73 4.84
November 0.545018E+11 57688.17 27-NOV-23:07 5.92 4.92 0.283866E+11 19340.09 27-NOV-22:49 5.92 4.92
December 0.481985E+11 33032.92 01-DEC-21:47 6.10 3.37 0.270115E+11 18888.66 01-DEC-04:00 6.10 3.37
                     
Annual Sum or Average 0.727598E+12         0.353147E+12        
Minimum of Months 0.432079E+11 32449.71   4.40 2.30 0.242234E+11 18888.66   4.40 2.30
Maximum of Months 0.772126E+11 64454.80   26.02 24.00 0.323263E+11 20715.51   26.02 24.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 27567019.95 2826.04 15-JAN-16:01 4.82 1.15 92581303.49 56.69 06-JAN-04:19 4.82 1.15
February 34564245.33 2975.03 28-FEB-16:01 0.40 -2.4 83750352.24 56.69 22-FEB-23:10 0.40 -2.4
March 0.226746E+09 3137.88 15-MAR-15:02 25.50 16.19 94958629.97 56.69 15-MAR-22:10 16.78 13.11
April 0.433885E+09 3158.07 19-APR-15:01 17.20 9.68 93226762.14 56.69 07-APR-21:40 17.20 9.68
May 0.106274E+10 3381.97 23-MAY-15:02 23.90 13.35 97944010.57 56.69 26-MAY-21:00 13.30 11.08
June 0.194083E+10 3411.40 30-JUN-18:02 23.12 12.20 95575387.35 56.70 12-JUN-21:40 23.12 12.20
July 0.242414E+10 3372.47 16-JUL-15:02 29.60 21.92 98842108.45 56.70 19-JUL-22:49 26.70 22.07
August 0.219914E+10 3366.68 13-AUG-18:02 26.52 22.29 98803555.00 56.70 16-AUG-21:00 20.00 15.24
September 0.133887E+10 3354.21 19-SEP-15:02 20.92 13.26 95049622.69 56.70 21-SEP-21:30 17.75 15.84
October 0.392723E+09 3115.69 25-OCT-15:01 18.22 9.29 95996818.54 56.69 11-OCT-21:30 18.22 9.29
November 92447185.41 2999.55 03-NOV-15:02 9.82 5.39 91166408.31 56.69 27-NOV-04:19 17.40 11.98
December 26091727.83 938.05 20-DEC-19:04 3.80 2.01 92570205.24 56.69 01-DEC-03:30 3.80 2.01
                     
Annual Sum or Average 0.101998E+11         0.113047E+10        
Minimum of Months 26091727.83 938.05   0.40 -2.4 83750352.24 56.69   0.40 -2.4
Maximum of Months 0.242414E+10 3411.40   29.60 22.29 98842108.45 56.70   26.70 22.07



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 12559339.88 964.40 11-JAN-16:04 11.60 10.09 92349825.27 56.69 17-JAN-05:19 7.60 3.05
February 14712785.83 888.22 22-FEB-16:03 10.78 5.11 83474222.26 56.69 15-FEB-01:30 10.78 5.11
March 0.136668E+09 3041.97 15-MAR-15:02 25.50 16.19 93986158.50 56.69 15-MAR-21:40 17.43 13.33
April 0.306977E+09 3021.86 19-APR-15:01 17.20 9.68 92551463.65 56.69 07-APR-21:19 17.20 9.68
May 0.921436E+09 3270.85 23-MAY-15:02 23.90 13.35 97594188.54 56.69 26-MAY-21:49 13.58 11.12
June 0.183989E+10 3314.75 30-JUN-18:02 23.12 12.20 95486670.80 56.70 19-JUN-22:10 23.12 12.20
July 0.228259E+10 3282.93 11-JUL-15:02 26.42 21.15 98817768.73 56.70 19-JUL-22:40 26.70 22.12
August 0.197111E+10 3248.17 14-AUG-18:02 25.92 21.74 98718167.01 56.70 18-AUG-21:49 21.88 17.75
September 0.103491E+10 3225.90 16-SEP-15:02 26.70 19.57 94616817.38 56.69 07-SEP-21:10 26.70 19.57
October 0.231679E+09 2856.85 12-OCT-15:01 18.30 15.17 95059961.49 56.69 12-OCT-21:00 14.40 13.72
November 60282976.77 1511.53 15-NOV-16:01 11.32 6.61 90407733.23 56.69 10-NOV-02:49 11.32 6.61
December 16177117.08 959.50 14-DEC-19:04 3.72 3.72 92311524.71 56.69 01-DEC-03:30 3.72 3.72
                     
Annual Sum or Average 0.882898E+10         0.112537E+10        
Minimum of Months 12559339.88 888.22   3.72 3.72 83474222.26 56.69   3.72 3.05
Maximum of Months 0.228259E+10 3314.75   26.70 21.74 98817768.73 56.70   26.70 22.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 41903408.62 93.88 15-JAN-15:30 5.30 1.42 0.00 0.00 01-JAN-00:10 5.30 1.42
February 40048707.84 90.22 28-FEB-15:30 0.30 -2.5 0.00 0.00 01-FEB-00:10 0.30 -2.5
March 0.186930E+09 463.99 15-MAR-13:30 25.55 15.84 0.00 0.00 01-MAR-00:10 25.55 15.84
April 0.233603E+09 395.48 22-APR-13:10 14.60 6.58 0.00 0.00 01-APR-00:10 14.60 6.58
May 0.346200E+09 382.96 27-MAY-13:00 21.70 12.35 0.00 0.00 01-MAY-00:10 21.70 12.35
June 0.497169E+09 500.05 27-JUN-13:00 30.60 23.75 0.00 0.00 01-JUN-00:10 30.60 23.75
July 0.690236E+09 571.61 21-JUL-13:30 31.15 21.91 0.00 0.00 01-JUL-00:10 31.15 21.91
August 0.682224E+09 638.65 18-AUG-13:30 29.70 20.75 0.00 0.00 01-AUG-00:10 29.70 20.75
September 0.549464E+09 782.43 21-SEP-13:00 25.00 16.50 0.00 0.00 01-SEP-00:10 25.00 16.50
October 0.319851E+09 757.32 11-OCT-12:30 21.95 13.79 0.00 0.00 01-OCT-00:10 21.95 13.79
November 0.162509E+09 373.74 01-NOV-11:50 11.02 6.22 0.00 0.00 01-NOV-00:10 11.02 6.22
December 33332232.15 96.10 17-DEC-13:40 2.20 0.48 0.00 0.00 01-DEC-00:10 2.20 0.48
                     
Annual Sum or Average 0.378347E+10         0.00        
Minimum of Months 33332232.15 90.22   0.30 -2.5 0.00 0.00   0.30 -2.5
Maximum of Months 0.690236E+09 782.43   31.15 23.75 0.00 0.00   31.15 23.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 39318287.82 470.16 19-JAN-19:04 0.60 -0.1 93375083.86 56.69 17-JAN-04:49 0.60 -0.1
February 38047341.55 471.61 17-FEB-19:04 0.50 -0.1 84407497.69 56.69 22-FEB-23:10 6.83 5.85
March 0.129739E+09 880.69 15-MAR-15:02 25.50 16.19 94665153.97 56.69 15-MAR-21:49 17.07 13.21
April 0.211459E+09 820.74 07-APR-15:01 18.22 9.77 92579243.26 56.69 07-APR-21:49 15.18 10.17
May 0.453422E+09 955.60 23-MAY-18:02 22.70 13.24 96708909.55 56.69 26-MAY-21:30 14.15 11.19
June 0.685926E+09 979.74 30-JUN-18:02 23.12 12.20 94411045.18 56.69 19-JUN-21:30 23.12 12.20
July 0.845421E+09 974.89 14-JUL-18:02 27.52 18.39 97838735.78 56.69 03-JUL-21:10 27.52 18.39
August 0.747836E+09 993.71 09-AUG-18:02 28.72 18.28 97674397.67 56.69 04-AUG-21:10 28.72 18.28
September 0.492328E+09 923.22 16-SEP-18:02 24.82 19.37 93607610.62 56.69 21-SEP-21:30 17.75 15.84
October 0.231698E+09 773.47 12-OCT-15:01 18.30 15.17 95563456.99 56.69 25-OCT-21:49 12.38 11.65
November 0.104580E+09 550.11 26-NOV-09:02 10.78 7.93 91666311.70 56.69 27-NOV-04:10 17.30 11.94
December 42143909.21 512.95 13-DEC-19:04 3.90 3.43 93460945.44 56.69 25-DEC-00:10 6.10 4.90
                     
Annual Sum or Average 0.402192E+10         0.112596E+10        
Minimum of Months 38047341.55 470.16   0.50 -0.1 84407497.69 56.69   0.60 -0.1
Maximum of Months 0.845421E+09 993.71   28.72 19.37 97838735.78 56.69   28.72 18.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 27051813.11 964.34 10-JAN-09:04 -9.0 -10.4 92602717.83 56.69 13-JAN-04:19 -7.8 -9.2
February 36388260.06 1206.90 28-FEB-09:01 -7.2 -8.1 83781289.14 56.69 07-FEB-04:19 -7.2 -8.1
March 0.221160E+09 2885.32 15-MAR-15:02 25.50 16.19 95023226.69 56.69 15-MAR-21:49 17.07 13.21
April 0.459559E+09 2878.85 07-APR-15:01 18.22 9.77 93530353.38 56.69 07-APR-21:40 15.37 10.24
May 0.105766E+10 3081.69 23-MAY-15:02 23.90 13.35 98217160.74 56.69 26-MAY-21:19 14.43 11.21
June 0.184080E+10 3075.96 12-JUN-08:61 25.28 18.91 95761780.16 56.69 20-JUN-22:10 21.42 15.33
July 0.241240E+10 3056.39 19-JUL-15:02 30.92 22.81 99032606.63 56.70 19-JUL-22:00 26.70 22.02
August 0.217293E+10 3064.43 13-AUG-15:02 29.90 23.27 99020141.49 56.70 18-AUG-22:40 21.70 17.67
September 0.137552E+10 3043.13 16-SEP-15:02 26.70 19.57 95226938.45 56.69 21-SEP-21:10 18.12 16.07
October 0.418226E+09 2771.51 31-OCT-15:02 13.98 10.66 96262710.23 56.69 11-OCT-21:19 13.98 10.66
November 0.108713E+09 2546.62 03-NOV-15:02 9.82 5.39 91196535.95 56.69 27-NOV-04:19 17.40 11.98
December 27680959.73 1259.55 17-DEC-09:03 0.60 -0.9 92556711.21 56.69 01-DEC-03:30 0.60 -0.9
                     
Annual Sum or Average 0.101581E+11         0.113221E+10        
Minimum of Months 27051813.11 964.34   -9.0 -10.4 83781289.14 56.69   -7.8 -9.2
Maximum of Months 0.241240E+10 3081.69   30.92 23.27 99032606.63 56.70   26.70 22.02



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 13157291.95 938.59 21-JAN-09:04 -2.0 -3.9 92361340.55 56.69 17-JAN-05:19 -2.0 -3.9
February 15975865.15 891.01 15-FEB-09:04 6.70 4.64 83469189.32 56.69 15-FEB-01:30 6.70 4.64
March 0.137913E+09 2786.97 15-MAR-15:02 25.50 16.19 94017379.14 56.69 15-MAR-21:10 18.53 13.66
April 0.321919E+09 2756.09 21-APR-08:61 7.67 4.60 92941160.88 56.69 07-APR-21:40 7.67 4.60
May 0.900651E+09 2983.32 23-MAY-15:02 23.90 13.35 98043751.72 56.69 16-MAY-21:49 23.90 13.35
June 0.173253E+10 2977.57 12-JUN-08:61 25.28 18.91 95744371.75 56.69 20-JUN-22:10 21.42 15.33
July 0.226711E+10 2974.95 18-JUL-15:02 27.57 19.74 99022997.06 56.70 19-JUL-22:40 26.70 22.12
August 0.193826E+10 2975.05 18-AUG-15:02 29.90 20.94 98976434.77 56.70 10-AUG-22:00 29.90 20.94
September 0.105308E+10 2874.25 19-SEP-15:02 20.92 13.26 94967263.32 56.69 08-SEP-23:10 20.92 13.26
October 0.244115E+09 2430.96 22-OCT-15:02 21.60 14.51 95332222.33 56.69 12-OCT-21:19 21.60 14.51
November 65518186.54 1780.65 06-NOV-09:01 7.30 3.68 90457954.07 56.69 27-NOV-04:19 17.40 11.98
December 15390693.99 944.77 04-DEC-09:04 -2.1 -3.8 92322858.60 56.69 01-DEC-03:30 -2.1 -3.8
                     
Annual Sum or Average 0.870562E+10         0.112766E+10        
Minimum of Months 13157291.95 891.01   -2.1 -3.9 83469189.32 56.69   -2.1 -3.9
Maximum of Months 0.226711E+10 2983.32   29.90 20.94 99022997.06 56.70   29.90 22.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.769751E+09 1993.29 17-JAN-21:58 4.40 3.43 0.119887E+10 723.41 17-JAN-05:49 4.40 3.43
February 0.754545E+09 2101.03 15-FEB-00:30 7.50 3.24 0.108419E+10 729.08 22-FEB-23:19 6.47 5.58
March 0.266656E+10 2497.03 17-MAR-17:03 6.10 3.86 0.122990E+10 823.81 15-MAR-21:40 6.10 3.86
April 0.346388E+10 3043.03 23-APR-21:27 6.95 3.60 0.123281E+10 815.45 24-APR-21:40 6.47 5.18
May 0.437200E+10 2946.62 27-MAY-04:55 8.30 6.35 0.138778E+10 878.63 23-MAY-22:10 8.30 6.35
June 0.486412E+10 3107.36 04-JUN-02:43 8.48 5.97 0.145644E+10 950.53 29-JUN-21:40 20.37 18.86
July 0.542940E+10 2947.35 21-JUL-18:05 28.62 21.70 0.156265E+10 951.84 19-JUL-23:19 28.62 21.70
August 0.532720E+10 2605.39 10-AUG-18:40 26.13 19.82 0.155703E+10 951.85 08-AUG-21:00 26.13 19.82
September 0.462773E+10 3134.66 03-SEP-02:62 8.22 7.46 0.141466E+10 926.54 21-SEP-21:40 17.57 15.72
October 0.375087E+10 3254.70 14-OCT-07:59 6.10 5.58 0.128670E+10 835.29 11-OCT-21:49 6.10 5.58
November 0.253554E+10 2613.73 06-NOV-05:05 8.90 6.96 0.117676E+10 772.22 01-NOV-21:19 8.90 6.96
December 0.857467E+09 1994.49 24-DEC-21:42 6.60 3.90 0.119901E+10 720.75 01-DEC-04:00 6.60 3.90
                     
Annual Sum or Average 0.394191E+11         0.157868E+11        
Minimum of Months 0.754545E+09 1993.29   4.40 3.24 0.108419E+10 720.75   4.40 3.43
Maximum of Months 0.542940E+10 3254.70   28.62 21.70 0.156265E+10 951.85   28.62 21.70



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 16493283.18 2896.85 15-JAN-16:01 4.82 1.15 92412089.82 56.69 17-JAN-05:19 7.60 3.05
February 23926733.52 3001.94 28-FEB-16:01 0.40 -2.4 83569388.78 56.69 15-FEB-01:30 0.40 -2.4
March 0.201000E+09 3237.51 14-MAR-15:02 24.32 16.47 94467270.28 56.69 15-MAR-21:30 17.80 13.45
April 0.412375E+09 3282.04 19-APR-15:01 17.20 9.68 92873902.91 56.69 07-APR-21:49 17.20 9.68
May 0.995157E+09 3519.90 23-MAY-15:02 23.90 13.35 97762579.25 56.69 26-MAY-21:40 13.87 11.16
June 0.190126E+10 3547.89 30-JUN-18:02 23.12 12.20 95487219.66 56.70 20-JUN-21:49 23.12 12.20
July 0.241816E+10 3476.01 20-JUL-15:02 28.98 23.62 98772048.27 56.70 14-JUL-21:40 28.98 23.62
August 0.214561E+10 3477.94 13-AUG-18:02 26.52 22.29 98701848.05 56.70 10-AUG-22:40 26.52 22.29
September 0.121850E+10 3484.78 19-SEP-15:02 20.92 13.26 94849439.36 56.69 07-SEP-21:10 20.92 13.26
October 0.332514E+09 3198.01 25-OCT-15:01 18.22 9.29 95511947.37 56.69 23-OCT-03:39 18.22 9.29
November 69669340.63 3127.32 15-NOV-16:01 11.32 6.61 90724469.80 56.69 10-NOV-05:19 11.32 6.61
December 17607448.08 1087.15 01-DEC-16:04 7.20 5.30 92393932.02 56.69 01-DEC-03:30 7.20 5.30
                     
Annual Sum or Average 0.975228E+10         0.112753E+10        
Minimum of Months 16493283.18 1087.15   0.40 -2.4 83569388.78 56.69   0.40 -2.4
Maximum of Months 0.241816E+10 3547.89   28.98 23.62 98772048.27 56.70   28.98 23.62



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 7967343.76 961.87 15-JAN-16:03 4.82 1.15 92304082.39 56.69 17-JAN-05:19 7.60 3.05
February 9727630.04 1268.75 18-FEB-16:03 2.02 -0.3 83400451.29 56.69 14-FEB-23:00 2.02 -0.3
March 0.110025E+09 3158.35 15-MAR-15:02 25.50 16.19 93637080.09 56.69 22-MAR-22:49 8.48 6.50
April 0.283122E+09 3128.08 07-APR-15:01 18.22 9.77 92188255.24 56.69 07-APR-21:19 15.73 10.39
May 0.847234E+09 3394.52 23-MAY-15:02 23.90 13.35 97419015.21 56.69 23-MAY-21:10 20.60 13.34
June 0.179270E+10 3438.37 30-JUN-18:02 23.12 12.20 95410821.88 56.70 20-JUN-21:49 23.12 12.20
July 0.226896E+10 3382.02 10-JUL-18:02 26.93 18.82 98752416.58 56.70 31-JUL-21:00 22.30 19.03
August 0.190458E+10 3392.96 13-AUG-18:02 26.52 22.29 98605098.48 56.70 14-AUG-21:40 24.07 21.35
September 0.900423E+09 3369.85 16-SEP-15:02 26.70 19.57 94388284.25 56.69 23-SEP-03:39 13.90 11.53
October 0.181840E+09 2944.35 12-OCT-15:01 18.30 15.17 94509368.41 56.69 11-OCT-21:30 18.30 15.17
November 43385246.71 1511.45 14-NOV-19:03 6.42 4.86 90011585.71 56.69 04-NOV-04:49 6.42 4.86
December 10488075.22 1165.00 01-DEC-16:04 7.20 5.30 92230755.95 56.69 01-DEC-03:30 7.20 5.30
                     
Annual Sum or Average 0.836045E+10         0.112286E+10        
Minimum of Months 7967343.76 961.87   2.02 -0.3 83400451.29 56.69   2.02 -0.3
Maximum of Months 0.226896E+10 3438.37   26.93 22.29 98752416.58 56.70   24.07 21.35



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 59255063.74 1698.86 15-JAN-16:01 4.82 1.15 93705234.72 56.69 17-JAN-05:19 7.60 3.05
February 59443136.87 1695.67 28-FEB-16:01 0.40 -2.4 84596694.51 56.69 22-FEB-23:10 0.40 -2.4
March 0.274308E+09 1790.56 15-MAR-18:01 23.43 15.50 96141818.23 56.69 15-MAR-21:19 18.17 13.56
April 0.351173E+09 1749.96 07-APR-15:01 18.22 9.77 93589469.18 56.69 07-APR-21:19 15.73 10.39
May 0.618276E+09 1868.10 23-MAY-15:02 23.90 13.35 97822834.70 56.69 26-MAY-21:49 13.58 11.12
June 0.986118E+09 1840.11 26-JUN-15:02 27.88 20.67 95329649.14 56.69 20-JUN-21:00 27.88 20.67
July 0.135516E+10 1852.13 20-JUL-15:02 28.98 23.62 98726016.89 56.69 19-JUL-23:10 28.98 23.62
August 0.131848E+10 1855.25 09-AUG-18:02 28.72 18.28 98711791.43 56.69 18-AUG-22:49 21.70 17.67
September 0.100342E+10 1856.75 21-SEP-15:02 26.10 16.73 95133302.88 56.69 21-SEP-22:49 16.78 14.53
October 0.495994E+09 1739.82 25-OCT-15:01 18.22 9.29 96867909.47 56.69 11-OCT-21:49 18.22 9.29
November 0.193456E+09 1705.53 03-NOV-15:02 9.82 5.39 92340979.41 56.69 01-NOV-21:10 9.82 5.39
December 57834167.57 1679.07 04-DEC-16:01 -0.9 -3.5 93436187.44 56.69 25-DEC-00:10 6.10 4.90
                     
Annual Sum or Average 0.677291E+10         0.113640E+10        
Minimum of Months 57834167.57 1679.07   -0.9 -3.5 84596694.51 56.69   0.40 -2.4
Maximum of Months 0.135516E+10 1868.10   28.98 23.62 98726016.89 56.69   28.98 23.62



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.281897E+11 23627.66 17-JAN-06:13 7.20 3.01 0.183149E+11 12911.58 17-JAN-05:49 7.20 3.01
February 0.254651E+11 29891.34 14-FEB-23:45 7.70 3.33 0.165529E+11 12021.03 15-FEB-01:10 7.12 3.12
March 0.315380E+11 32669.26 30-MAR-22:37 6.70 5.87 0.188810E+11 12579.84 17-MAR-21:00 6.70 5.87
April 0.331766E+11 36721.04 20-APR-22:20 6.87 4.69 0.185230E+11 13159.27 03-APR-22:19 6.87 4.69
May 0.381366E+11 31999.26 06-MAY-05:43 7.12 5.76 0.192863E+11 12914.38 23-MAY-04:30 7.20 5.41
June 0.405970E+11 32053.14 14-JUN-02:52 7.20 5.16 0.187429E+11 13666.47 06-JUN-03:49 7.20 5.16
July 0.438923E+11 23161.02 20-JUL-21:20 25.40 23.97 0.192973E+11 11428.74 06-JUL-02:00 25.40 23.97
August 0.427818E+11 22876.90 10-AUG-21:20 25.93 18.71 0.193680E+11 11415.89 04-AUG-01:49 25.93 18.71
September 0.379171E+11 31207.17 30-SEP-05:35 7.20 6.12 0.186455E+11 12471.40 30-SEP-02:00 7.20 6.12
October 0.345082E+11 31399.43 21-OCT-02:35 8.13 6.10 0.190994E+11 12519.34 31-OCT-22:40 7.13 5.02
November 0.309911E+11 31863.96 03-NOV-22:31 6.10 2.71 0.182993E+11 12401.49 06-NOV-02:00 8.90 6.70
December 0.285769E+11 30142.54 01-DEC-23:15 5.40 3.08 0.183839E+11 11650.79 01-DEC-23:30 5.30 3.01
                     
Annual Sum or Average 0.415770E+12         0.223395E+12        
Minimum of Months 0.254651E+11 22876.90   5.40 2.71 0.165529E+11 11415.89   5.30 3.01
Maximum of Months 0.438923E+11 36721.04   25.93 23.97 0.193680E+11 13666.47   25.93 23.97



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.313871E+11 27887.67 17-JAN-06:18 7.20 3.01 0.186632E+11 13047.53 17-JAN-05:49 7.20 3.01
February 0.283515E+11 32569.66 15-FEB-00:30 7.50 3.24 0.168797E+11 12155.22 14-FEB-23:30 7.50 3.24
March 0.350894E+11 34534.34 30-MAR-22:37 6.70 5.87 0.191001E+11 12673.33 17-MAR-21:00 6.70 5.87
April 0.368133E+11 38776.73 20-APR-22:20 6.87 4.69 0.186452E+11 13301.36 03-APR-22:19 6.87 4.69
May 0.416788E+11 33639.60 06-MAY-05:43 7.12 5.76 0.193437E+11 12982.54 23-MAY-04:30 7.20 5.41
June 0.436561E+11 33646.01 14-JUN-02:52 7.20 5.16 0.187628E+11 13740.67 06-JUN-03:49 7.20 5.16
July 0.467892E+11 24336.63 20-JUL-21:20 25.40 23.97 0.193056E+11 11431.05 06-JUL-02:00 25.40 23.97
August 0.457203E+11 24091.97 10-AUG-21:20 25.93 18.71 0.193825E+11 11418.20 04-AUG-01:49 25.93 18.71
September 0.410528E+11 33202.37 05-SEP-02:19 7.60 6.85 0.186860E+11 12542.94 30-SEP-02:00 7.80 6.37
October 0.381835E+11 33724.85 02-OCT-05:32 7.20 6.89 0.192259E+11 12608.89 31-OCT-22:40 7.13 5.02
November 0.345582E+11 33636.23 03-NOV-22:31 6.10 2.71 0.184847E+11 12478.60 06-NOV-02:00 8.90 6.70
December 0.318438E+11 31782.23 01-DEC-23:15 5.40 3.08 0.187095E+11 11735.03 01-DEC-23:30 5.30 3.01
                     
Annual Sum or Average 0.455124E+12         0.225189E+12        
Minimum of Months 0.283515E+11 24091.97   5.40 2.71 0.168797E+11 11418.20   5.30 3.01
Maximum of Months 0.467892E+11 38776.73   25.93 23.97 0.193825E+11 13740.67   25.93 23.97



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.456203E+11 35314.13 17-JAN-11:38 6.30 4.09 0.187798E+11 11319.69 28-JAN-18:19 -6.7 -8.3
February 0.413496E+11 35949.75 19-FEB-11:36 5.20 1.65 0.169612E+11 11319.65 25-FEB-18:19 -6.3 -7.5
March 0.492321E+11 37370.92 17-MAR-17:03 6.10 3.86 0.188194E+11 11380.52 11-MAR-18:00 6.10 3.86
April 0.499739E+11 36042.13 04-APR-10:36 5.40 4.63 0.182314E+11 11481.62 01-APR-17:30 5.40 4.63
May 0.544412E+11 34463.74 06-MAY-21:28 7.25 5.73 0.188476E+11 11325.38 06-MAY-17:00 7.25 5.73
June 0.551996E+11 33727.62 06-JUN-06:20 8.13 7.23 0.182539E+11 11319.68 10-JUN-17:19 21.47 13.06
July 0.583821E+11 31437.35 16-JUL-10:40 28.50 22.06 0.188588E+11 11319.68 08-JUL-17:19 28.50 22.06
August 0.576067E+11 31352.15 10-AUG-10:40 28.53 20.68 0.188632E+11 11319.68 12-AUG-17:19 24.43 16.84
September 0.535185E+11 34727.78 06-SEP-06:56 7.20 6.12 0.182421E+11 11319.65 16-SEP-17:19 25.73 19.64
October 0.515436E+11 37993.14 29-OCT-16:14 7.23 5.10 0.188409E+11 11478.01 28-OCT-17:40 7.23 5.10
November 0.475001E+11 36281.51 08-NOV-18:28 6.10 5.58 0.182180E+11 11399.60 25-NOV-18:40 9.60 3.98
December 0.457974E+11 34258.19 01-DEC-18:47 6.70 4.71 0.187847E+11 11319.68 09-DEC-18:19 -7.6 -7.9
                     
Annual Sum or Average 0.610165E+12         0.221701E+12        
Minimum of Months 0.413496E+11 31352.15   5.20 1.65 0.169612E+11 11319.65   -7.6 -8.3
Maximum of Months 0.583821E+11 37993.14   28.53 22.06 0.188632E+11 11481.62   28.50 22.06



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.839396E+09 4060.18 17-JAN-21:58 4.40 3.43 0.126887E+10 768.38 17-JAN-05:49 4.40 3.43
February 0.849844E+09 4258.30 15-FEB-00:30 7.50 3.24 0.114726E+10 763.98 22-FEB-23:19 6.47 5.58
March 0.446561E+10 5086.76 17-MAR-17:03 6.10 3.86 0.129986E+10 904.64 15-MAR-21:30 6.10 3.86
April 0.663767E+10 6153.11 23-APR-21:27 6.95 3.60 0.129020E+10 858.68 09-APR-23:49 6.95 3.60
May 0.888052E+10 5808.13 27-MAY-04:55 8.30 6.35 0.144922E+10 931.63 23-MAY-21:40 8.30 6.35
June 0.100235E+11 6152.76 04-JUN-02:43 8.48 5.97 0.153468E+10 1007.39 29-JUN-21:40 20.37 18.86
July 0.114479E+11 6662.09 21-JUL-13:30 31.15 21.91 0.165179E+10 1007.39 27-JUL-21:19 19.80 19.16
August 0.110792E+11 6294.86 09-AUG-15:03 29.40 18.17 0.163218E+10 1007.42 08-AUG-21:49 29.40 18.17
September 0.930051E+10 6163.14 03-SEP-02:62 8.22 7.46 0.146615E+10 971.11 21-SEP-21:30 17.75 15.84
October 0.719300E+10 6476.01 14-OCT-07:59 6.10 5.58 0.134211E+10 890.02 11-OCT-21:40 6.10 5.58
November 0.464466E+10 5271.67 13-NOV-08:32 7.43 5.94 0.124069E+10 809.39 27-NOV-22:00 6.10 5.06
December 0.112949E+10 4086.44 01-DEC-18:38 6.70 4.73 0.126903E+10 755.48 01-DEC-04:40 6.70 4.73
                     
Annual Sum or Average 0.764912E+11         0.165920E+11        
Minimum of Months 0.839396E+09 4060.18   4.40 3.24 0.114726E+10 755.48   4.40 3.43
Maximum of Months 0.114479E+11 6662.09   31.15 21.91 0.165179E+10 1007.42   29.40 19.16



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -1.0
February 0.00 0.00 01-FEB-00:03 -3.3
March 834058.23 2215.78 23-MAR-00:13 7.93
April 4271645.88 3179.14 27-APR-00:58 7.20
May 6110845.07 2903.07 03-MAY-02:15 7.03
June 620056.07 1050.90 06-JUN-02:62 7.70
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 2506601.85 1951.11 30-SEP-05:53 7.20
October 4291995.51 3598.63 14-OCT-02:20 7.20
November 1655025.15 3201.35 19-NOV-23:22 5.85
December 0.00 0.00 01-DEC-00:03 4.95
         
Annual Sum or Average 20290227.75      
Minimum of Months 0.00 0.00   -3.3
Maximum of Months 6110845.07 3598.63   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.105742E+10 1501.58 04-JAN-07:50 -13.2
February 0.948559E+09 1911.06 07-FEB-07:15 -16.3
March 0.190107E+09 1091.01 05-MAR-06:00 -11.1
April 31966846.89 918.42 27-APR-00:58 7.20
May 10202464.82 811.92 01-MAY-23:40 7.97
June 3167874.10 596.70 14-JUN-00:17 8.13
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 6012206.62 925.67 30-SEP-05:43 7.20
October 23879599.78 3057.17 14-OCT-08:00 6.10
November 86997910.77 1001.52 19-NOV-23:22 5.85
December 0.101071E+10 1573.89 11-DEC-07:10 -16.4
         
Annual Sum or Average 0.336902E+10      
Minimum of Months 0.00 0.00   -16.4
Maximum of Months 0.105742E+10 3057.17   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 43228.51 66.56 17-JAN-04:38 7.60
February 44575.72 136.92 15-FEB-09:36 6.70
March 209043.65 201.57 23-MAR-00:13 7.93
April 335780.53 378.71 02-APR-11:13 6.50
May 285066.12 214.81 03-MAY-02:15 7.03
June 10989.85 31.53 14-JUN-00:17 8.13
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 427470.52 263.09 30-SEP-05:43 7.20
October 994818.00 345.53 16-OCT-15:23 7.20
November 727297.51 397.41 20-NOV-17:55 6.10
December 98288.56 147.88 14-DEC-07:17 6.10
         
Annual Sum or Average 3176558.97      
Minimum of Months 0.00 0.00   6.10
Maximum of Months 994818.00 397.41   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.266120E+09 527.74 31-JAN-15:00 -11.1
February 0.290949E+09 809.48 07-FEB-05:00 -15.6
March 48411074.46 438.77 07-MAR-05:00 -13.3
April 2754754.46 478.07 02-APR-11:13 6.50
May 1171169.93 375.52 03-MAY-02:15 7.03
June 107070.41 138.76 06-JUN-02:62 7.70
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 903813.70 404.75 30-SEP-03:35 7.40
October 4111831.09 453.57 16-OCT-15:23 7.20
November 3285507.40 537.37 19-NOV-23:22 5.85
December 0.244007E+09 680.50 11-DEC-05:00 -17.2
         
Annual Sum or Average 0.861822E+09      
Minimum of Months 0.00 0.00   -17.2
Maximum of Months 0.290949E+09 809.48   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.442257E+09 493.91 31-JAN-18:00 -12.2
February 0.443308E+09 624.95 07-FEB-11:03 -13.0
March 0.103097E+09 368.32 07-MAR-05:00 -13.3
April 3946710.26 235.77 02-APR-11:13 6.50
May 881340.14 195.28 03-MAY-02:15 7.03
June 71575.36 86.21 14-JUN-00:17 8.13
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 542233.61 209.17 30-SEP-03:35 7.40
October 2790179.73 233.28 31-OCT-23:19 6.87
November 7434746.18 282.93 19-NOV-23:22 5.85
December 0.376394E+09 547.47 11-DEC-10:05 -13.1
         
Annual Sum or Average 0.138072E+10      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.443308E+09 624.95   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 81048.57 754.38 17-JAN-04:38 7.60
February 0.00 0.00 01-FEB-00:03 -3.3
March 0.00 0.00 01-MAR-00:03 -4.9
April 294256.76 2421.10 27-APR-00:58 7.20
May 152395.24 569.27 27-MAY-03:59 7.20
June 57374.38 241.34 06-JUN-03:30 6.95
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 1819917.86 4686.67 05-SEP-03:03 7.12
October 2064579.20 4116.94 14-OCT-02:20 7.20
November 94061.67 777.81 17-NOV-00:18 7.03
December 68420.10 665.21 01-DEC-03:20 7.70
         
Annual Sum or Average 4632053.78      
Minimum of Months 0.00 0.00   -4.9
Maximum of Months 2064579.20 4686.67   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1862696.04 646.20 17-JAN-08:06 6.78
February 26744027.43 1926.83 06-FEB-09:10 -15.0
March 2271016.90 1082.77 31-MAR-07:24 6.10
April 1876032.61 2227.19 02-APR-11:13 6.50
May 1033287.73 1053.90 06-MAY-21:27 7.25
June 0.00 0.00 01-JUN-00:05 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 1768194.44 1792.66 30-SEP-05:43 7.20
October 6292031.78 2760.59 14-OCT-07:24 6.40
November 5975695.40 2475.16 20-NOV-17:55 6.10
December 4048944.28 1298.64 14-DEC-07:17 6.10
         
Annual Sum or Average 51871926.61      
Minimum of Months 0.00 0.00   -15.0
Maximum of Months 26744027.43 2760.59   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -1.0
February 330877.65 2048.46 15-FEB-09:36 6.70
March 286324.10 1010.26 23-MAR-00:13 7.93
April 2032505.04 6088.78 02-APR-11:13 6.50
May 1994410.95 2535.34 03-MAY-02:15 7.03
June 0.00 0.00 01-JUN-00:05 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 4073128.83 3115.54 30-SEP-05:43 7.20
October 10505045.93 6783.11 14-OCT-02:20 7.20
November 6690530.57 6238.83 20-NOV-17:55 6.10
December 297906.07 997.74 14-DEC-07:17 6.10
         
Annual Sum or Average 26210729.14      
Minimum of Months 0.00 0.00   -1.0
Maximum of Months 10505045.93 6783.11   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.185894E+10 2959.04 31-JAN-09:01 -11.7
February 0.163173E+10 2975.24 07-FEB-09:01 -15.3
March 0.744037E+09 2923.46 07-MAR-09:01 -9.0
April 0.275050E+09 2879.01 16-APR-08:61 -2.9
May 15903164.86 1179.89 12-MAY-08:62 10.10
June 966680.24 721.23 09-JUN-08:03 14.18
July 545190.74 440.25 13-JUL-08:04 18.17
August 874462.83 453.24 31-AUG-08:03 13.90
September 9254659.43 1252.98 29-SEP-08:62 10.68
October 0.260556E+09 2845.87 17-OCT-08:61 -0.0
November 0.709649E+09 2894.35 17-NOV-19:01 5.68
December 0.179748E+10 2964.71 28-DEC-19:01 -9.4
         
Annual Sum or Average 0.730499E+10      
Minimum of Months 545190.74 440.25   -15.3
Maximum of Months 0.185894E+10 2975.24   18.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.210965E+10 2953.89 31-JAN-09:01 -11.7
February 0.183974E+10 2970.64 07-FEB-09:01 -15.3
March 0.952629E+09 2936.38 07-MAR-09:01 -9.0
April 0.336789E+09 2861.77 16-APR-08:61 -2.9
May 20072001.51 1220.98 12-MAY-08:62 10.10
June 905396.21 718.70 09-JUN-08:03 14.18
July 553795.07 445.03 09-JUL-08:05 20.68
August 1008188.01 487.22 05-AUG-08:05 21.65
September 11069869.97 1379.34 29-SEP-08:62 10.68
October 0.348716E+09 2855.76 17-OCT-08:61 -0.0
November 0.852979E+09 2879.53 17-NOV-19:01 5.68
December 0.198937E+10 2955.26 10-DEC-19:01 -13.5
         
Annual Sum or Average 0.846348E+10      
Minimum of Months 553795.07 445.03   -15.3
Maximum of Months 0.210965E+10 2970.64   21.65



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.207935E+09 321.60 24-JAN-06:00 -12.2
February 0.192801E+09 389.91 07-FEB-05:00 -15.6
March 7273590.67 120.52 21-MAR-04:00 -2.2
April 1545789.71 80.97 17-APR-05:00 -3.9
May 0.00 0.00 01-MAY-00:05 6.67
June 0.00 0.00 01-JUN-00:05 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 0.00 0.00 01-SEP-00:05 14.65
October 0.00 0.00 01-OCT-00:10 14.42
November 14604611.73 172.66 24-NOV-06:00 -3.9
December 0.213142E+09 326.57 10-DEC-06:00 -13.3
         
Annual Sum or Average 0.637302E+09      
Minimum of Months 0.00 0.00   -15.6
Maximum of Months 0.213142E+09 389.91   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.359871E+09 857.40 31-JAN-16:01 -12.1
February 0.325329E+09 858.70 06-FEB-16:01 -13.4
March 0.155679E+09 855.75 06-MAR-16:01 -6.8
April 11961315.02 804.61 17-APR-08:61 -0.8
May 828111.98 472.06 29-MAY-15:04 16.28
June 227392.93 364.91 09-JUN-15:04 17.12
July 77057.05 130.61 04-JUL-18:07 25.92
August 114864.59 163.59 31-AUG-15:04 16.70
September 454006.27 327.64 10-SEP-15:04 17.30
October 10554812.91 806.59 17-OCT-08:61 -0.0
November 60167996.16 811.92 24-NOV-09:01 -1.5
December 0.322557E+09 858.31 10-DEC-16:01 -10.8
         
Annual Sum or Average 0.124782E+10      
Minimum of Months 77057.05 130.61   -13.4
Maximum of Months 0.359871E+09 858.70   25.92



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.180113E+10 2891.50 31-JAN-16:01 -12.1
February 0.158900E+10 2891.81 06-FEB-16:01 -13.4
March 0.758195E+09 2859.16 06-MAR-19:01 -9.5
April 0.272138E+09 2790.51 16-APR-08:61 -2.9
May 22006781.40 1078.93 12-MAY-08:62 10.10
June 924763.87 399.56 07-JUN-15:05 18.30
July 144956.99 367.69 26-JUL-08:05 22.38
August 317218.26 454.63 24-AUG-18:05 22.43
September 9489700.78 1198.78 29-SEP-08:62 10.68
October 0.253529E+09 2750.25 23-OCT-18:01 4.32
November 0.705507E+09 2820.29 17-NOV-19:01 5.68
December 0.179051E+10 2894.67 28-DEC-19:01 -9.4
         
Annual Sum or Average 0.720289E+10      
Minimum of Months 144956.99 367.69   -13.4
Maximum of Months 0.180113E+10 2894.67   22.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.204412E+10 2884.66 31-JAN-16:01 -12.1
February 0.178888E+10 2898.43 06-FEB-16:01 -13.4
March 0.970071E+09 2858.56 06-MAR-19:01 -9.5
April 0.330890E+09 2773.24 16-APR-08:61 -2.9
May 27305170.22 1111.98 12-MAY-08:62 10.10
June 1148828.27 497.27 05-JUN-15:04 17.30
July 101376.80 378.25 26-JUL-08:05 22.38
August 395431.77 827.89 31-AUG-15:04 16.70
September 11910200.71 1327.58 29-SEP-08:62 10.68
October 0.330695E+09 2743.20 24-OCT-18:01 5.32
November 0.840798E+09 2804.34 17-NOV-19:01 5.68
December 0.198188E+10 2888.59 11-DEC-16:01 -9.3
         
Annual Sum or Average 0.832820E+10      
Minimum of Months 101376.80 378.25   -13.4
Maximum of Months 0.204412E+10 2898.43   22.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.234414E+09 715.18 29-JAN-16:00 -5.6
February 0.203413E+09 1151.76 06-FEB-09:03 -15.0
March 5726635.00 673.18 23-MAR-00:13 7.93
April 5422364.64 802.25 02-APR-11:13 6.50
May 1916340.95 629.46 03-MAY-02:15 7.03
June 149485.76 214.58 14-JUN-00:17 8.13
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 1587786.70 685.54 30-SEP-03:35 7.40
October 10139344.17 802.81 20-OCT-23:38 7.97
November 9412371.84 958.29 19-NOV-23:22 5.85
December 0.262170E+09 932.89 11-DEC-09:03 -13.8
         
Annual Sum or Average 0.734351E+09      
Minimum of Months 0.00 0.00   -15.0
Maximum of Months 0.262170E+09 1151.76   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.256368E+10 3465.00 31-JAN-09:01 -11.7
February 0.225244E+10 3485.18 07-FEB-09:01 -15.3
March 0.112991E+10 3412.18 07-MAR-09:01 -9.0
April 0.491716E+09 3359.39 16-APR-08:61 -2.9
May 70790707.01 2129.11 12-MAY-08:62 10.10
June 5356048.83 635.97 27-JUN-08:04 25.28
July 579456.38 566.70 06-JUL-08:04 15.97
August 1116943.55 726.81 31-AUG-18:04 14.90
September 27642641.58 2187.32 29-SEP-08:62 10.68
October 0.483252E+09 3332.91 17-OCT-08:61 -0.0
November 0.109172E+10 3353.42 17-NOV-19:01 5.68
December 0.247645E+10 3472.70 28-DEC-19:01 -9.4
         
Annual Sum or Average 0.105947E+11      
Minimum of Months 579456.38 566.70   -15.3
Maximum of Months 0.256368E+10 3485.18   25.28



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.285504E+10 3452.20 31-JAN-09:01 -11.7
February 0.249681E+10 3472.77 07-FEB-09:01 -15.3
March 0.139476E+10 3427.67 07-MAR-09:01 -9.0
April 0.579338E+09 3333.21 16-APR-08:61 -2.9
May 84055565.93 2436.28 08-MAY-08:61 7.38
June 5228478.56 645.99 23-JUN-08:04 15.10
July 526793.38 615.97 06-JUL-08:04 15.97
August 1315462.58 795.85 31-AUG-15:04 16.70
September 40050561.74 2316.05 29-SEP-08:62 10.68
October 0.618967E+09 3325.11 17-OCT-08:61 -0.0
November 0.127990E+10 3339.61 24-NOV-09:01 -1.5
December 0.269966E+10 3457.76 10-DEC-19:01 -13.5
         
Annual Sum or Average 0.120556E+11      
Minimum of Months 526793.38 615.97   -15.3
Maximum of Months 0.285504E+10 3472.77   16.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.907980E+09 1814.27 03-JAN-16:01 -6.2
February 0.826690E+09 1814.95 06-FEB-09:02 -15.0
March 0.319607E+09 1783.25 24-MAR-08:61 -4.3
April 0.134600E+09 1756.41 16-APR-08:61 -2.9
May 11353730.60 701.62 29-MAY-15:04 16.28
June 1084537.30 495.38 12-JUN-08:04 25.28
July 357990.62 339.49 20-JUL-08:05 26.28
August 402224.96 317.42 31-AUG-08:03 13.90
September 3295274.77 537.67 29-SEP-08:62 10.68
October 95321026.96 1716.42 24-OCT-08:61 2.30
November 0.305827E+09 1761.23 23-NOV-19:01 -0.6
December 0.920079E+09 1810.89 09-DEC-19:01 -8.4
         
Annual Sum or Average 0.352660E+10      
Minimum of Months 357990.62 317.42   -15.0
Maximum of Months 0.920079E+09 1814.95   26.28



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -1.0
February 0.00 0.00 01-FEB-00:03 -3.3
March 0.00 0.00 01-MAR-00:03 -4.9
April 121386.90 706.49 27-APR-00:58 7.20
May 10829.12 162.44 06-MAY-21:27 7.25
June 0.00 0.00 01-JUN-00:05 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 212139.61 1385.13 05-SEP-03:03 7.12
October 1073460.76 1588.76 07-OCT-06:34 6.87
November 185177.25 902.84 19-NOV-23:22 5.85
December 0.00 0.00 01-DEC-00:03 4.95
         
Annual Sum or Average 1602993.63      
Minimum of Months 0.00 0.00   -4.9
Maximum of Months 1073460.76 1588.76   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -1.0
February 0.00 0.00 01-FEB-00:03 -3.3
March 0.00 0.00 01-MAR-00:03 -4.9
April 52105.91 694.75 27-APR-00:58 7.20
May 4376.37 65.65 06-MAY-21:27 7.25
June 0.00 0.00 01-JUN-00:05 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 207135.51 1380.34 05-SEP-03:03 7.12
October 944488.04 2378.06 02-OCT-05:25 7.20
November 113716.51 621.42 17-NOV-00:18 7.03
December 0.00 0.00 01-DEC-00:03 4.95
         
Annual Sum or Average 1321822.34      
Minimum of Months 0.00 0.00   -4.9
Maximum of Months 944488.04 2378.06   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 -1.0
February 0.00 0.00 01-FEB-00:03 -3.3
March 0.00 0.00 01-MAR-00:03 -4.9
April 55357.11 738.09 27-APR-00:58 7.20
May 0.00 0.00 01-MAY-00:05 6.67
June 0.00 0.00 01-JUN-00:05 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 87628.55 1022.33 05-SEP-01:26 8.05
October 411369.92 1570.42 14-OCT-02:20 7.20
November 14382.76 215.74 17-NOV-00:18 7.03
December 0.00 0.00 01-DEC-00:03 4.95
         
Annual Sum or Average 568738.35      
Minimum of Months 0.00 0.00   -4.9
Maximum of Months 411369.92 1570.42   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.126635E+10 2486.94 10-JAN-07:10 -11.4
February 0.120431E+10 3540.45 07-FEB-07:10 -16.5
March 0.223690E+09 2015.41 07-MAR-07:05 -12.9
April 16052689.96 1507.12 02-APR-11:13 6.50
May 6745257.12 1368.64 03-MAY-02:15 7.03
June 619080.08 625.16 14-JUN-00:17 8.13
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 5245831.44 1601.60 30-SEP-05:43 7.20
October 25100430.76 1787.78 02-OCT-05:25 7.20
November 23753371.27 1951.28 19-NOV-23:22 5.85
December 0.122647E+10 3174.40 11-DEC-07:10 -16.4
         
Annual Sum or Average 0.399834E+10      
Minimum of Months 0.00 0.00   -16.5
Maximum of Months 0.126635E+10 3540.45   18.85



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.147273E+11 14185.34 02-JAN-20:10 0.127587E+11 10113.80 02-JAN-20:10
February 0.132974E+11 14185.34 01-FEB-20:10 0.115208E+11 10113.80 01-FEB-20:10
March 0.147727E+11 14185.34 01-MAR-20:10 0.127855E+11 10113.80 01-MAR-20:10
April 0.142280E+11 14185.34 03-APR-19:10 0.123314E+11 10113.80 03-APR-19:10
May 0.147528E+11 14185.34 01-MAY-19:10 0.127741E+11 10113.80 01-MAY-19:10
June 0.142932E+11 14185.34 01-JUN-19:10 0.123716E+11 10113.80 01-JUN-19:10
July 0.146876E+11 14185.34 03-JUL-19:10 0.127338E+11 10113.80 03-JUL-19:10
August 0.147784E+11 14185.34 01-AUG-19:10 0.127894E+11 10113.80 01-AUG-19:10
September 0.142337E+11 14185.34 01-SEP-19:10 0.123352E+11 10113.80 01-SEP-19:10
October 0.147216E+11 14185.34 02-OCT-19:10 0.127549E+11 10113.80 02-OCT-19:10
November 0.142819E+11 14185.34 01-NOV-19:10 0.123659E+11 10113.80 01-NOV-19:10
December 0.146876E+11 14185.34 01-DEC-20:10 0.127338E+11 10113.80 01-DEC-20:10
             
Annual Sum or Average 0.173462E+12     0.150255E+12    
Minimum of Months 0.132974E+11 14185.34   0.115208E+11 10113.80  
Maximum of Months 0.147784E+11 14185.34   0.127894E+11 10113.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.731324E+09 704.41 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.660319E+09 704.41 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.733578E+09 704.41 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.706528E+09 704.41 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.732592E+09 704.41 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.709769E+09 704.41 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.729351E+09 704.41 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.733860E+09 704.41 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.706810E+09 704.41 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.731042E+09 704.41 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.709205E+09 704.41 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.729351E+09 704.41 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.861373E+10     0.101856E+11    
Minimum of Months 0.660319E+09 704.41   0.780982E+09 685.60  
Maximum of Months 0.733860E+09 704.41   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.846876E+09 815.72 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.764651E+09 815.72 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.849486E+09 815.72 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.818162E+09 815.72 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.848344E+09 815.72 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.821915E+09 815.72 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.844592E+09 815.72 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.849812E+09 815.72 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.818489E+09 815.72 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.846549E+09 815.72 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.821262E+09 815.72 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.844592E+09 815.72 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.997473E+10     0.117950E+11    
Minimum of Months 0.764651E+09 815.72   0.904380E+09 793.93  
Maximum of Months 0.849812E+09 815.72   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.141236E+10 1360.40 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.127524E+10 1360.40 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.141672E+10 1360.40 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.136448E+10 1360.40 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.141481E+10 1360.40 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.137074E+10 1360.40 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.140855E+10 1360.40 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.141726E+10 1360.40 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.136502E+10 1360.40 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.141182E+10 1360.40 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.136965E+10 1360.40 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.140855E+10 1360.40 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.166352E+11     0.124712E+11    
Minimum of Months 0.127524E+10 1360.40   0.956227E+09 839.45  
Maximum of Months 0.141726E+10 1360.40   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.236418E+09 227.72 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.213464E+09 227.72 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.237147E+09 227.72 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.228402E+09 227.72 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.236828E+09 227.72 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.229450E+09 227.72 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.235780E+09 227.72 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.237238E+09 227.72 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.228493E+09 227.72 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.236327E+09 227.72 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.229268E+09 227.72 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.235780E+09 227.72 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.278459E+10     0.359760E+10    
Minimum of Months 0.213464E+09 227.72   0.275845E+09 242.16  
Maximum of Months 0.237238E+09 227.72   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.370859E+09 357.21 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.334852E+09 357.21 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.372002E+09 357.21 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.358285E+09 357.21 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.371502E+09 357.21 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.359929E+09 357.21 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.369859E+09 357.21 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.372145E+09 357.21 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.358428E+09 357.21 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.370717E+09 357.21 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.359643E+09 357.21 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.369859E+09 357.21 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.436808E+10     0.679355E+11    
Minimum of Months 0.334852E+09 357.21   0.520895E+10 4572.80  
Maximum of Months 0.372145E+09 357.21   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.161557E+10 1761.91 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.143474E+10 1761.91 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.153994E+10 1761.91 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.142722E+10 1761.91 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.142775E+10 1761.91 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.135638E+10 1761.91 01-JUN-19:30 0.118076E+10 965.27 01-JUN-19:10
July 0.140255E+10 1761.91 03-JUL-19:40 0.121533E+10 965.27 03-JUL-19:10
August 0.144829E+10 1761.91 01-AUG-19:30 0.122063E+10 965.27 01-AUG-19:10
September 0.146684E+10 1761.91 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.157509E+10 1761.91 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.156287E+10 1761.91 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.161745E+10 1761.91 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.178747E+11     0.143405E+11    
Minimum of Months 0.135638E+10 1761.91   0.109956E+10 965.27  
Maximum of Months 0.161745E+10 1761.91   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104410E+11 10265.18 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.940155E+10 10265.18 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.103913E+11 10265.18 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.995663E+10 10265.18 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.102741E+11 10265.18 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.992156E+10 10265.18 01-JUN-19:30 0.122682E+11 10029.21 01-JUN-19:10
July 0.102028E+11 10265.18 03-JUL-19:30 0.126273E+11 10029.21 03-JUL-19:10
August 0.103061E+11 10265.18 01-AUG-19:19 0.126824E+11 10029.21 01-AUG-19:10
September 0.999817E+10 10265.18 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.103967E+11 10265.18 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.101215E+11 10265.18 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.104198E+11 10265.18 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.121831E+12     0.148998E+12    
Minimum of Months 0.940155E+10 10265.18   0.114244E+11 10029.21  
Maximum of Months 0.104410E+11 10265.18   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85091918.49 76.99 01-JAN-19:10 0.255708E+09 232.19 01-JAN-08:09
February 76846309.13 76.99 01-FEB-20:10 0.230956E+09 232.19 01-FEB-07:10
March 84415649.14 76.99 01-MAR-20:10 0.255355E+09 232.19 01-MAR-07:10
April 82445007.08 76.99 01-APR-18:10 0.247516E+09 232.19 01-APR-07:10
May 84753783.81 76.99 01-MAY-19:10 0.255532E+09 232.19 01-MAY-06:10
June 81790910.76 76.99 01-JUN-19:10 0.247163E+09 232.19 01-JUN-06:10
July 85418966.65 76.99 01-JUL-18:10 0.255885E+09 232.19 01-JUL-07:10
August 84415649.14 76.99 01-AUG-19:10 0.255355E+09 232.19 01-AUG-06:10
September 82467180.11 76.99 01-SEP-19:10 0.247516E+09 232.19 01-SEP-06:10
October 85080831.98 76.99 01-OCT-18:10 0.255708E+09 232.19 01-OCT-07:10
November 82117958.92 76.99 01-NOV-19:10 0.247340E+09 232.19 01-NOV-06:10
December 85430053.17 76.99 01-DEC-20:10 0.255885E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.100027E+10     0.300992E+10    
Minimum of Months 76846309.13 76.99   0.230956E+09 232.19  
Maximum of Months 85430053.17 76.99   0.255885E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85115186.72 77.01 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 76867322.62 77.01 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 84438732.44 77.01 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 82467551.52 77.01 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 84776959.58 77.01 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 81813276.33 77.01 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 85442324.32 77.01 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 84438732.44 77.01 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 82489730.61 77.01 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 85104097.18 77.01 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 82140413.93 77.01 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 85453413.86 77.01 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.100055E+10     0.301074E+10    
Minimum of Months 76867322.62 77.01   0.231020E+09 232.26  
Maximum of Months 85453413.86 77.01   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.232638E+10 2240.78 02-JAN-20:10 0.00 0.00
February 0.210051E+10 2240.78 01-FEB-20:10 0.00 0.00
March 0.233355E+10 2240.78 01-MAR-20:10 0.00 0.00
April 0.224750E+10 2240.78 03-APR-19:10 0.00 0.00
May 0.233041E+10 2240.78 01-MAY-19:10 0.00 0.00
June 0.225781E+10 2240.78 01-JUN-19:10 0.00 0.00
July 0.232011E+10 2240.78 03-JUL-19:10 0.00 0.00
August 0.233445E+10 2240.78 01-AUG-19:10 0.00 0.00
September 0.224840E+10 2240.78 01-SEP-19:10 0.00 0.00
October 0.232548E+10 2240.78 02-OCT-19:10 0.00 0.00
November 0.225602E+10 2240.78 01-NOV-19:10 0.00 0.00
December 0.232011E+10 2240.78 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.274007E+11     0.00 0.00
Minimum of Months 0.210051E+10 2240.78   0.00 0.00
Maximum of Months 0.233445E+10 2240.78   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85115186.72 77.01 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 76867322.62 77.01 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 84438732.44 77.01 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 82467551.52 77.01 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 84776959.58 77.01 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 81813276.33 77.01 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 85442324.32 77.01 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 84438732.44 77.01 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 82489730.61 77.01 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 85104097.18 77.01 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 82140413.93 77.01 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 85453413.86 77.01 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.100055E+10     0.301074E+10    
Minimum of Months 76867322.62 77.01   0.231020E+09 232.26  
Maximum of Months 85453413.86 77.01   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.303348E+10 3094.06 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.271413E+10 3094.06 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.296450E+10 3094.06 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.279902E+10 3094.06 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.284864E+10 3094.06 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.273006E+10 3094.06 01-JUN-19:40 0.144540E+11 6747.90 01-JUN-06:10
July 0.281470E+10 3094.06 03-JUL-19:40 0.149358E+11 6747.90 01-JUL-06:10
August 0.287161E+10 3094.06 01-AUG-19:30 0.149358E+11 6747.90 01-AUG-06:10
September 0.283990E+10 3094.06 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.299489E+10 3094.06 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.293871E+10 3094.06 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.303112E+10 3094.06 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.345807E+11     0.175857E+12    
Minimum of Months 0.271413E+10 3094.06   0.134904E+11 6747.90  
Maximum of Months 0.303348E+10 3094.06   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.303348E+10 3094.06 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.271413E+10 3094.06 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.296450E+10 3094.06 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.279902E+10 3094.06 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.284864E+10 3094.06 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.273006E+10 3094.06 01-JUN-19:40 0.144540E+11 6747.90 01-JUN-06:10
July 0.281470E+10 3094.06 03-JUL-19:40 0.149358E+11 6747.90 01-JUL-06:10
August 0.287161E+10 3094.06 01-AUG-19:30 0.149358E+11 6747.90 01-AUG-06:10
September 0.283990E+10 3094.06 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.299489E+10 3094.06 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.293871E+10 3094.06 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.303112E+10 3094.06 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.345807E+11     0.175857E+12    
Minimum of Months 0.271413E+10 3094.06   0.134904E+11 6747.90  
Maximum of Months 0.303348E+10 3094.06   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.113146E+10 1089.83 02-JAN-20:10 0.368383E+11 16487.34 01-JAN-07:10
February 0.102161E+10 1089.83 01-FEB-20:10 0.332733E+11 16487.34 01-FEB-07:10
March 0.113495E+10 1089.83 01-MAR-20:10 0.368383E+11 16487.34 01-MAR-07:10
April 0.109310E+10 1089.83 03-APR-19:10 0.356500E+11 16487.34 01-APR-06:10
May 0.113342E+10 1089.83 01-MAY-19:10 0.368383E+11 16487.34 01-MAY-06:10
June 0.109811E+10 1089.83 01-JUN-19:10 0.356500E+11 16487.34 01-JUN-06:10
July 0.112841E+10 1089.83 03-JUL-19:10 0.368383E+11 16487.34 01-JUL-06:10
August 0.113539E+10 1089.83 01-AUG-19:10 0.368383E+11 16487.34 01-AUG-06:10
September 0.109354E+10 1089.83 01-SEP-19:10 0.356500E+11 16487.34 01-SEP-06:10
October 0.113103E+10 1089.83 02-OCT-19:10 0.368383E+11 16487.34 01-OCT-06:10
November 0.109724E+10 1089.83 01-NOV-19:10 0.356500E+11 16487.34 01-NOV-06:10
December 0.112841E+10 1089.83 01-DEC-20:10 0.368383E+11 16487.34 01-DEC-07:10
             
Annual Sum or Average 0.133267E+11     0.433742E+12    
Minimum of Months 0.102161E+10 1089.83   0.332733E+11 16487.34  
Maximum of Months 0.113539E+10 1089.83   0.368383E+11 16487.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.246211E+10 2371.52 02-JAN-20:10 0.00 0.00
February 0.222306E+10 2371.52 01-FEB-20:10 0.00 0.00
March 0.246970E+10 2371.52 01-MAR-20:10 0.00 0.00
April 0.237864E+10 2371.52 03-APR-19:10 0.00 0.00
May 0.246638E+10 2371.52 01-MAY-19:10 0.00 0.00
June 0.238954E+10 2371.52 01-JUN-19:10 0.00 0.00
July 0.245547E+10 2371.52 03-JUL-19:10 0.00 0.00
August 0.247065E+10 2371.52 01-AUG-19:10 0.00 0.00
September 0.237958E+10 2371.52 01-SEP-19:10 0.00 0.00
October 0.246116E+10 2371.52 02-OCT-19:10 0.00 0.00
November 0.238765E+10 2371.52 01-NOV-19:10 0.00 0.00
December 0.245547E+10 2371.52 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.289994E+11     0.00 0.00
Minimum of Months 0.222306E+10 2371.52   0.00 0.00
Maximum of Months 0.247065E+10 2371.52   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.147273E+11 0.127587E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.132974E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.147727E+11 0.127855E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.142280E+11 0.123314E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.147528E+11 0.127741E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.142932E+11 0.123716E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.146876E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.147784E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.142337E+11 0.123352E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.147216E+11 0.127549E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.142819E+11 0.123659E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.146876E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.173462E+12 0.150255E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.132974E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.147784E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.731324E+09 0.864900E+09 0.00 0.00 0.00 0.00 0.00 0.830589E+09
February 0.179968E+10 0.660319E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.778574E+09
March 0.199990E+10 0.733578E+09 0.866718E+09 0.00 0.00 0.00 0.00 746865.25 0.628505E+09
April 0.192973E+10 0.706528E+09 0.835931E+09 0.00 0.00 0.00 0.00 0.00 0.438166E+09
May 0.199475E+10 0.732592E+09 0.865939E+09 0.00 0.00 0.00 0.00 778335.34 0.253257E+09
June 0.193394E+10 0.709769E+09 0.838659E+09 0.00 0.00 0.00 0.00 13476867.53 0.125692E+09
July 0.199054E+10 0.729351E+09 0.863211E+09 0.00 0.00 0.00 0.00 29870205.84 54438682.68
August 0.199896E+10 0.733860E+09 0.866978E+09 0.00 0.00 0.00 0.00 21735741.27 85819424.99
September 0.192879E+10 0.706810E+09 0.836191E+09 0.00 0.00 0.00 0.00 2508268.97 0.176728E+09
October 0.199148E+10 0.731042E+09 0.864640E+09 0.00 0.00 0.00 0.00 0.00 0.383674E+09
November 0.192552E+10 0.709205E+09 0.838269E+09 0.00 0.00 0.00 0.00 0.00 0.480970E+09
December 0.199054E+10 0.729351E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.00 0.784337E+09
                   
Annual Sum or Average 0.234744E+11 0.861373E+10 0.101856E+11 0.00 0.00 0.00 0.00 69116284.20 0.502075E+10
Minimum of Months 0.179968E+10 0.660319E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 54438682.68
Maximum of Months 0.199990E+10 0.733860E+09 0.866978E+09 0.00 0.00 0.00 0.00 29870205.84 0.830589E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.846876E+09 0.100156E+10 0.00 0.00 0.00 0.00 0.00 0.323454E+09
February 0.208403E+10 0.764651E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 0.302948E+09
March 0.231589E+10 0.849486E+09 0.100366E+10 0.00 0.00 0.00 0.00 456166.71 0.250658E+09
April 0.223463E+10 0.818162E+09 0.968011E+09 0.00 0.00 0.00 0.00 0.00 0.181172E+09
May 0.230993E+10 0.848344E+09 0.100276E+10 0.00 0.00 0.00 0.00 397797.23 0.113471E+09
June 0.223950E+10 0.821915E+09 0.971170E+09 0.00 0.00 0.00 0.00 4721817.74 61045376.76
July 0.230505E+10 0.844592E+09 0.999601E+09 0.00 0.00 0.00 0.00 11242607.70 30452659.39
August 0.231480E+10 0.849812E+09 0.100396E+10 0.00 0.00 0.00 0.00 8662891.86 43916532.15
September 0.223354E+10 0.818489E+09 0.968312E+09 0.00 0.00 0.00 0.00 961799.07 80931316.64
October 0.230614E+10 0.846549E+09 0.100126E+10 0.00 0.00 0.00 0.00 0.00 0.161589E+09
November 0.222975E+10 0.821262E+09 0.970719E+09 0.00 0.00 0.00 0.00 0.00 0.196033E+09
December 0.230505E+10 0.844592E+09 0.999601E+09 0.00 0.00 0.00 0.00 0.00 0.306255E+09
                   
Annual Sum or Average 0.271834E+11 0.997473E+10 0.117950E+11 0.00 0.00 0.00 0.00 26443080.31 0.205193E+10
Minimum of Months 0.208403E+10 0.764651E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 30452659.39
Maximum of Months 0.231589E+10 0.849812E+09 0.100396E+10 0.00 0.00 0.00 0.00 11242607.70 0.323454E+09



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.141236E+10 0.105898E+10 0.00 0.00 0.00 0.00 0.00 0.756376E+09
February 0.440737E+09 0.127524E+10 0.956227E+09 0.00 0.00 0.00 0.00 0.00 0.708770E+09
March 0.489771E+09 0.141672E+10 0.106120E+10 0.00 0.00 0.00 0.00 1430995.66 0.572590E+09
April 0.472586E+09 0.136448E+10 0.102351E+10 0.00 0.00 0.00 0.00 0.00 0.402710E+09
May 0.488511E+09 0.141481E+10 0.106025E+10 0.00 0.00 0.00 0.00 1321131.05 0.250548E+09
June 0.473617E+09 0.137074E+10 0.102685E+10 0.00 0.00 0.00 0.00 11862863.26 0.136892E+09
July 0.487480E+09 0.140855E+10 0.105691E+10 0.00 0.00 0.00 0.00 26457564.74 69489170.93
August 0.489542E+09 0.141726E+10 0.106152E+10 0.00 0.00 0.00 0.00 20917888.02 0.100464E+09
September 0.472357E+09 0.136502E+10 0.102382E+10 0.00 0.00 0.00 0.00 2713965.59 0.180384E+09
October 0.487709E+09 0.141182E+10 0.105866E+10 0.00 0.00 0.00 0.00 12988.56 0.359972E+09
November 0.471555E+09 0.136965E+10 0.102637E+10 0.00 0.00 0.00 0.00 0.00 0.441597E+09
December 0.487480E+09 0.140855E+10 0.105691E+10 0.00 0.00 0.00 0.00 0.00 0.714367E+09
                   
Annual Sum or Average 0.574883E+10 0.166352E+11 0.124712E+11 0.00 0.00 0.00 0.00 64717396.87 0.469416E+10
Minimum of Months 0.440737E+09 0.127524E+10 0.956227E+09 0.00 0.00 0.00 0.00 0.00 69489170.93
Maximum of Months 0.489771E+09 0.141726E+10 0.106152E+10 0.00 0.00 0.00 0.00 26457564.74 0.756376E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.236418E+09 0.305485E+09 0.00 0.00 0.00 0.00 0.00 0.436238E+09
February 0.339028E+09 0.213464E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 0.408810E+09
March 0.376747E+09 0.237147E+09 0.306128E+09 0.00 0.00 0.00 0.00 843966.23 0.328741E+09
April 0.363528E+09 0.228402E+09 0.295253E+09 0.00 0.00 0.00 0.00 0.00 0.229264E+09
May 0.375778E+09 0.236828E+09 0.305852E+09 0.00 0.00 0.00 0.00 791877.14 0.140773E+09
June 0.364321E+09 0.229450E+09 0.296217E+09 0.00 0.00 0.00 0.00 7204602.12 76093220.70
July 0.374985E+09 0.235780E+09 0.304889E+09 0.00 0.00 0.00 0.00 15827366.23 38085131.45
August 0.376571E+09 0.237238E+09 0.306219E+09 0.00 0.00 0.00 0.00 12537111.29 55511095.07
September 0.363352E+09 0.228493E+09 0.295345E+09 0.00 0.00 0.00 0.00 1684239.37 0.100764E+09
October 0.375161E+09 0.236327E+09 0.305393E+09 0.00 0.00 0.00 0.00 9323.68 0.203612E+09
November 0.362735E+09 0.229268E+09 0.296079E+09 0.00 0.00 0.00 0.00 0.00 0.252308E+09
December 0.374985E+09 0.235780E+09 0.304889E+09 0.00 0.00 0.00 0.00 0.00 0.411849E+09
                   
Annual Sum or Average 0.442217E+10 0.278459E+10 0.359760E+10 0.00 0.00 0.00 0.00 38898486.05 0.268205E+10
Minimum of Months 0.339028E+09 0.213464E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 38085131.45
Maximum of Months 0.376747E+09 0.237238E+09 0.306219E+09 0.00 0.00 0.00 0.00 15827366.23 0.436238E+09



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.370859E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 0.00 0.110739E+10
February 0.139600E+10 0.334852E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.103496E+10
March 0.155131E+10 0.372002E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 1344703.54 0.851863E+09
April 0.149688E+10 0.358285E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 0.00 0.611449E+09
May 0.154732E+10 0.371502E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 1476289.02 0.374237E+09
June 0.150015E+10 0.359929E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 17943944.12 0.188760E+09
July 0.154405E+10 0.369859E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 44691268.87 86342655.23
August 0.155059E+10 0.372145E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 34866449.67 0.129130E+09
September 0.149615E+10 0.358428E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 4524728.82 0.255841E+09
October 0.154478E+10 0.370717E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 0.00 0.542517E+09
November 0.149361E+10 0.359643E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 0.00 0.672335E+09
December 0.154405E+10 0.369859E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.00 0.104989E+10
                   
Annual Sum or Average 0.182090E+11 0.436808E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 0.104847E+09 0.690471E+10
Minimum of Months 0.139600E+10 0.334852E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 86342655.23
Maximum of Months 0.155131E+10 0.372145E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 44691268.87 0.110739E+10



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.161557E+10 0.121771E+10 0.00 0.00 0.00 0.00 0.00 0.185301E+10
February 0.236489E+11 0.143474E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.173631E+10
March 0.262800E+11 0.153994E+10 0.122027E+10 0.00 0.00 0.00 0.00 1293172.66 0.144471E+10
April 0.253579E+11 0.142722E+10 0.117692E+10 0.00 0.00 0.00 0.00 0.00 0.103686E+10
May 0.262123E+11 0.142775E+10 0.121917E+10 0.00 0.00 0.00 0.00 1204072.50 0.643279E+09
June 0.254132E+11 0.135638E+10 0.118076E+10 0.00 0.00 0.00 0.00 25402629.89 0.340423E+09
July 0.261570E+11 0.140255E+10 0.121533E+10 0.00 0.00 0.00 0.00 60825559.82 0.165951E+09
August 0.262677E+11 0.144829E+10 0.122063E+10 0.00 0.00 0.00 0.00 45015010.89 0.242832E+09
September 0.253456E+11 0.146684E+10 0.117729E+10 0.00 0.00 0.00 0.00 3879296.33 0.462404E+09
October 0.261693E+11 0.157509E+10 0.121734E+10 0.00 0.00 0.00 0.00 0.00 0.922731E+09
November 0.253025E+11 0.156287E+10 0.118021E+10 0.00 0.00 0.00 0.00 0.00 0.111821E+10
December 0.261570E+11 0.161745E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.00 0.175181E+10
                   
Annual Sum or Average 0.308468E+12 0.178747E+11 0.143405E+11 0.00 0.00 0.00 0.00 0.137620E+09 0.117185E+11
Minimum of Months 0.236489E+11 0.135638E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.165951E+09
Maximum of Months 0.262800E+11 0.161745E+10 0.122063E+10 0.00 0.00 0.00 0.00 60825559.82 0.185301E+10



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.104410E+11 0.126520E+11 0.00 0.00 0.00 0.00 0.00 0.539609E+10
February 0.702046E+11 0.940155E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.504912E+10
March 0.780153E+11 0.103913E+11 0.126786E+11 0.00 0.00 0.00 0.00 5456984.34 0.422396E+10
April 0.752779E+11 0.995663E+10 0.122282E+11 0.00 0.00 0.00 0.00 0.00 0.306743E+10
May 0.778146E+11 0.102741E+11 0.126672E+11 0.00 0.00 0.00 0.00 4993709.08 0.193762E+10
June 0.754422E+11 0.992156E+10 0.122682E+11 0.00 0.00 0.00 0.00 72362609.48 0.103419E+10
July 0.776503E+11 0.102028E+11 0.126273E+11 0.00 0.00 0.00 0.00 0.176869E+09 0.514284E+09
August 0.779788E+11 0.103061E+11 0.126824E+11 0.00 0.00 0.00 0.00 0.132982E+09 0.740180E+09
September 0.752414E+11 0.999817E+10 0.122320E+11 0.00 0.00 0.00 0.00 11889188.61 0.138539E+10
October 0.776868E+11 0.103967E+11 0.126482E+11 0.00 0.00 0.00 0.00 0.00 0.275528E+10
November 0.751137E+11 0.101215E+11 0.122624E+11 0.00 0.00 0.00 0.00 0.00 0.332289E+10
December 0.776503E+11 0.104198E+11 0.126273E+11 0.00 0.00 0.00 0.00 0.00 0.511270E+10
                   
Annual Sum or Average 0.915726E+12 0.121831E+12 0.148998E+12 0.00 0.00 0.00 0.00 0.404553E+09 0.345391E+11
Minimum of Months 0.702046E+11 0.940155E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.514284E+09
Maximum of Months 0.780153E+11 0.104410E+11 0.126824E+11 0.00 0.00 0.00 0.00 0.176869E+09 0.539609E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.472989E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.444062E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 679754.57 0.359885E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.00 0.252701E+09
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 956491.94 0.146772E+09
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 11735087.35 67553911.15
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 27898631.55 23828925.88
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 20725295.30 40686809.40
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 3328302.11 95006279.80
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 32802.31 0.218103E+09
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 0.274071E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.446332E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 65356365.14 0.284199E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 23828925.88
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 27898631.55 0.472989E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.471881E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.442736E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 830019.15 0.355782E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.00 0.249937E+09
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 976911.02 0.145332E+09
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 11767923.36 67180839.67
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 27970743.71 23776260.27
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 20850285.89 40480457.37
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 3475526.31 93534470.36
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 35346.33 0.214348E+09
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 0.270974E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.445184E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 65906755.78 0.282115E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 23776260.27
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 27970743.71 0.471881E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 85091918.49 0.255708E+09 0.00 0.00 0.00 0.00 0.00 0.124154E+09
February 0.00 76846309.13 0.230956E+09 0.00 0.00 0.00 0.00 0.00 0.116621E+09
March 0.00 84415649.14 0.255355E+09 0.00 0.00 0.00 0.00 115941.70 98930254.69
April 0.00 82445007.08 0.247516E+09 0.00 0.00 0.00 0.00 0.00 71925119.06
May 0.00 84753783.81 0.255532E+09 0.00 0.00 0.00 0.00 100332.06 47117531.22
June 0.00 81790910.76 0.247163E+09 0.00 0.00 0.00 0.00 1843638.45 24614220.23
July 0.00 85418966.65 0.255885E+09 0.00 0.00 0.00 0.00 4859523.52 11651683.74
August 0.00 84415649.14 0.255355E+09 0.00 0.00 0.00 0.00 3725164.36 17344261.25
September 0.00 82467180.11 0.247516E+09 0.00 0.00 0.00 0.00 386357.85 33561678.59
October 0.00 85080831.98 0.255708E+09 0.00 0.00 0.00 0.00 0.00 66102330.14
November 0.00 82117958.92 0.247340E+09 0.00 0.00 0.00 0.00 0.00 74557953.11
December 0.00 85430053.17 0.255885E+09 0.00 0.00 0.00 0.00 0.00 0.116544E+09
                   
Annual Sum or Average 0.00 0.100027E+10 0.300992E+10 0.00 0.00 0.00 0.00 11030957.94 0.803125E+09
Minimum of Months 0.00 76846309.13 0.230956E+09 0.00 0.00 0.00 0.00 0.00 11651683.74
Maximum of Months 0.00 85430053.17 0.255885E+09 0.00 0.00 0.00 0.00 4859523.52 0.124154E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 85115186.72 0.255778E+09 0.00 0.00 0.00 0.00 0.00 0.132669E+09
February 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 0.00 0.124479E+09
March 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 280272.30 0.100101E+09
April 0.293479E+09 82467551.52 0.247584E+09 0.00 0.00 0.00 0.00 0.00 69912921.38
May 0.303504E+09 84776959.58 0.255602E+09 0.00 0.00 0.00 0.00 337906.17 39886008.55
June 0.293842E+09 81813276.33 0.247231E+09 0.00 0.00 0.00 0.00 3585554.60 18087167.15
July 0.303141E+09 85442324.32 0.255955E+09 0.00 0.00 0.00 0.00 8347135.95 6309090.49
August 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 6418603.69 10937593.48
September 0.293479E+09 82489730.61 0.247584E+09 0.00 0.00 0.00 0.00 1194353.45 25426935.11
October 0.303322E+09 85104097.18 0.255778E+09 0.00 0.00 0.00 0.00 25484.31 60320618.81
November 0.293661E+09 82140413.93 0.247408E+09 0.00 0.00 0.00 0.00 0.00 76850369.29
December 0.303141E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 0.00 0.125336E+09
                   
Annual Sum or Average 0.357224E+10 0.100055E+10 0.301074E+10 0.00 0.00 0.00 0.00 20189310.47 0.790315E+09
Minimum of Months 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 0.00 6309090.49
Maximum of Months 0.303685E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 8347135.95 0.132669E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.473124E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.444340E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 665155.72 0.360847E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.00 0.254416E+09
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 961595.98 0.148018E+09
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 11717055.24 68196365.01
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 27865331.09 24330628.57
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 20730692.35 41299146.91
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 3327820.21 95702125.10
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 34197.05 0.219327E+09
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 0.274159E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.446251E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 65301847.63 0.285001E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 24330628.57
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 27865331.09 0.473124E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.471950E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.442774E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 718227.04 0.356503E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.00 0.252169E+09
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 963093.47 0.147392E+09
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 11724567.94 68140129.55
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 27882342.71 24317977.37
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 20767478.84 41198930.07
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 3348980.38 94937670.17
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 34997.83 0.215811E+09
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 0.271156E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.445208E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 65439688.20 0.283156E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 24317977.37
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 27882342.71 0.471950E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.232638E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.582746E+09
February 0.348285E+10 0.210051E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.546106E+09
March 0.387034E+10 0.233355E+10 0.00 0.00 0.00 0.00 0.00 1097008.06 0.439730E+09
April 0.373454E+10 0.224750E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.311453E+09
May 0.386038E+10 0.233041E+10 0.00 0.00 0.00 0.00 0.00 768131.50 0.195001E+09
June 0.374269E+10 0.225781E+10 0.00 0.00 0.00 0.00 0.00 8287271.47 0.106821E+09
July 0.385223E+10 0.232011E+10 0.00 0.00 0.00 0.00 0.00 18767623.84 54372861.23
August 0.386853E+10 0.233445E+10 0.00 0.00 0.00 0.00 0.00 14301289.87 77951911.80
September 0.373273E+10 0.224840E+10 0.00 0.00 0.00 0.00 0.00 1795994.34 0.139916E+09
October 0.385404E+10 0.232548E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.272713E+09
November 0.372639E+10 0.225602E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.336982E+09
December 0.385223E+10 0.232011E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.550213E+09
                   
Annual Sum or Average 0.454292E+11 0.274007E+11 0.00 0.00 0.00 0.00 0.00 45017319.09 0.361401E+10
Minimum of Months 0.348285E+10 0.210051E+10 0.00 0.00 0.00 0.00 0.00 0.00 54372861.23
Maximum of Months 0.387034E+10 0.233445E+10 0.00 0.00 0.00 0.00 0.00 18767623.84 0.582746E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.473475E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.444380E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 658999.67 0.359070E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.00 0.252525E+09
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 918120.89 0.147298E+09
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 11446522.59 68075003.96
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 27346909.06 24188918.68
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 20296638.08 41063600.92
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 3216676.41 95368500.62
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 28607.50 0.217491E+09
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 0.273587E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.446856E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 63912474.19 0.284338E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 24188918.68
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 27346909.06 0.473475E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.472923E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.443566E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 799801.89 0.355629E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.00 0.249703E+09
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 926667.46 0.145874E+09
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 11477127.01 67750404.83
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 27409928.01 24145576.59
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 20426563.66 40842119.45
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 3361759.50 93783642.58
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 32384.28 0.213447E+09
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 0.270651E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.446090E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 64434231.80 0.282440E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 24145576.59
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 27409928.01 0.472923E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 85115186.72 0.255778E+09 0.00 0.00 0.00 0.00 0.00 0.245189E+09
February 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 0.00 0.229724E+09
March 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 326465.97 0.187347E+09
April 0.293479E+09 82467551.52 0.247584E+09 0.00 0.00 0.00 0.00 0.00 0.130833E+09
May 0.303504E+09 84776959.58 0.255602E+09 0.00 0.00 0.00 0.00 471595.64 75690259.57
June 0.293842E+09 81813276.33 0.247231E+09 0.00 0.00 0.00 0.00 5904335.86 34709530.63
July 0.303141E+09 85442324.32 0.255955E+09 0.00 0.00 0.00 0.00 14032157.67 12331246.80
August 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 10408030.78 21051153.29
September 0.293479E+09 82489730.61 0.247584E+09 0.00 0.00 0.00 0.00 1629019.60 49303417.34
October 0.303322E+09 85104097.18 0.255778E+09 0.00 0.00 0.00 0.00 9987.13 0.113801E+09
November 0.293661E+09 82140413.93 0.247408E+09 0.00 0.00 0.00 0.00 0.00 0.142990E+09
December 0.303141E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 0.00 0.230834E+09
                   
Annual Sum or Average 0.357224E+10 0.100055E+10 0.301074E+10 0.00 0.00 0.00 0.00 32781592.65 0.147381E+10
Minimum of Months 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 0.00 12331246.80
Maximum of Months 0.303685E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 14032157.67 0.245189E+09



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.303348E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.127924E+10
February 0.415303E+11 0.271413E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.119581E+10
March 0.461508E+11 0.296450E+10 0.149358E+11 0.00 0.00 0.00 0.00 673468.51 0.997364E+09
April 0.445315E+11 0.279902E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.730538E+09
May 0.460320E+11 0.284864E+10 0.149358E+11 0.00 0.00 0.00 0.00 480917.18 0.465407E+09
June 0.446286E+11 0.273006E+10 0.144540E+11 0.00 0.00 0.00 0.00 11486362.87 0.248459E+09
July 0.459349E+11 0.281470E+10 0.149358E+11 0.00 0.00 0.00 0.00 32530053.43 0.124786E+09
August 0.461292E+11 0.287161E+10 0.149358E+11 0.00 0.00 0.00 0.00 24823439.41 0.176864E+09
September 0.445099E+11 0.283990E+10 0.144540E+11 0.00 0.00 0.00 0.00 1966340.57 0.328127E+09
October 0.459565E+11 0.299489E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.650264E+09
November 0.444343E+11 0.293871E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.792277E+09
December 0.459349E+11 0.303112E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.121510E+10
                   
Annual Sum or Average 0.541708E+12 0.345807E+11 0.175857E+12 0.00 0.00 0.00 0.00 71960581.97 0.820424E+10
Minimum of Months 0.415303E+11 0.271413E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.124786E+09
Maximum of Months 0.461508E+11 0.303348E+10 0.149358E+11 0.00 0.00 0.00 0.00 32530053.43 0.127924E+10



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.303348E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.129208E+10
February 0.415303E+11 0.271413E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.120773E+10
March 0.461508E+11 0.296450E+10 0.149358E+11 0.00 0.00 0.00 0.00 564080.17 0.100654E+10
April 0.445315E+11 0.279902E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.736476E+09
May 0.460320E+11 0.284864E+10 0.149358E+11 0.00 0.00 0.00 0.00 471588.79 0.468595E+09
June 0.446286E+11 0.273006E+10 0.144540E+11 0.00 0.00 0.00 0.00 11363710.26 0.249597E+09
July 0.459349E+11 0.281470E+10 0.149358E+11 0.00 0.00 0.00 0.00 32337663.46 0.125131E+09
August 0.461292E+11 0.287161E+10 0.149358E+11 0.00 0.00 0.00 0.00 24616210.55 0.177630E+09
September 0.445099E+11 0.283990E+10 0.144540E+11 0.00 0.00 0.00 0.00 1878954.09 0.330384E+09
October 0.459565E+11 0.299489E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.656312E+09
November 0.444343E+11 0.293871E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.800433E+09
December 0.459349E+11 0.303112E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.122728E+10
                   
Annual Sum or Average 0.541708E+12 0.345807E+11 0.175857E+12 0.00 0.00 0.00 0.00 71232207.33 0.827819E+10
Minimum of Months 0.415303E+11 0.271413E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.125131E+09
Maximum of Months 0.461508E+11 0.303348E+10 0.149358E+11 0.00 0.00 0.00 0.00 32337663.46 0.129208E+10



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.113146E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.116797E+10
February 0.369574E+10 0.102161E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.109029E+10
March 0.410691E+10 0.113495E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 466373.08 0.905859E+09
April 0.396281E+10 0.109310E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.660469E+09
May 0.409635E+10 0.113342E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 425168.35 0.417740E+09
June 0.397146E+10 0.109811E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 10169051.82 0.221913E+09
July 0.408770E+10 0.112841E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 28951344.55 0.110551E+09
August 0.410499E+10 0.113539E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 21973162.14 0.157315E+09
September 0.396089E+10 0.109354E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 1670816.75 0.294389E+09
October 0.408962E+10 0.113103E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.590299E+09
November 0.395417E+10 0.109724E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.721065E+09
December 0.408770E+10 0.112841E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.110922E+10
                   
Annual Sum or Average 0.482060E+11 0.133267E+11 0.392709E+12 0.359593E+12 0.00 0.00 0.00 63655916.70 0.744709E+10
Minimum of Months 0.369574E+10 0.102161E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.110551E+09
Maximum of Months 0.410691E+10 0.113539E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 28951344.55 0.116797E+10



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.246211E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.103383E+10
February 0.368610E+10 0.222306E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.968701E+09
March 0.409620E+10 0.246970E+10 0.00 0.00 0.00 0.00 0.00 1365209.47 0.780465E+09
April 0.395248E+10 0.237864E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.551769E+09
May 0.408566E+10 0.246638E+10 0.00 0.00 0.00 0.00 0.00 898814.76 0.344511E+09
June 0.396110E+10 0.238954E+10 0.00 0.00 0.00 0.00 0.00 11978204.26 0.189351E+09
July 0.407704E+10 0.245547E+10 0.00 0.00 0.00 0.00 0.00 29218789.67 96316255.74
August 0.409429E+10 0.247065E+10 0.00 0.00 0.00 0.00 0.00 22607361.79 0.135823E+09
September 0.395056E+10 0.237958E+10 0.00 0.00 0.00 0.00 0.00 2310910.16 0.243326E+09
October 0.407896E+10 0.246116E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.481476E+09
November 0.394385E+10 0.238765E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.598420E+09
December 0.407704E+10 0.245547E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.976258E+09
                   
Annual Sum or Average 0.480803E+11 0.289994E+11 0.00 0.00 0.00 0.00 0.00 68379290.11 0.640025E+10
Minimum of Months 0.368610E+10 0.222306E+10 0.00 0.00 0.00 0.00 0.00 0.00 96316255.74
Maximum of Months 0.409620E+10 0.247065E+10 0.00 0.00 0.00 0.00 0.00 29218789.67 0.103383E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 14185.34 02-JAN-20:10 10113.80 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 14185.34 01-FEB-20:10 10113.80 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 14185.34 01-MAR-20:10 10113.80 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 14185.34 03-APR-19:10 10113.80 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 14185.34 01-MAY-19:10 10113.80 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 14185.34 01-JUN-19:10 10113.80 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 14185.34 03-JUL-19:10 10113.80 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 14185.34 01-AUG-19:10 10113.80 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 14185.34 01-SEP-19:10 10113.80 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 14185.34 02-OCT-19:10 10113.80 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 14185.34 01-NOV-19:10 10113.80 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 14185.34 01-DEC-20:10 10113.80 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   14185.34   10113.80   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   14185.34   10113.80   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 704.41 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 460.78 31-JAN-02:00
February 1169.53 01-FEB-00:10 704.41 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 505.68 07-FEB-07:00
March 1169.53 01-MAR-00:10 704.41 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 26.15 15-MAR-17:00 461.83 07-MAR-05:50
April 1169.53 01-APR-00:10 704.41 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 324.90 17-APR-06:00
May 1169.53 01-MAY-00:10 704.41 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 30.69 10-MAY-15:00 239.11 01-MAY-05:40
June 1169.53 01-JUN-00:10 704.41 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 73.85 27-JUN-13:00 186.55 06-JUN-03:40
July 1169.53 01-JUL-00:10 704.41 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 86.04 21-JUL-14:00 116.18 06-JUL-04:54
August 1169.53 01-AUG-00:10 704.41 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 73.91 10-AUG-14:00 127.67 01-AUG-04:55
September 1169.53 01-SEP-00:10 704.41 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 36.30 16-SEP-13:00 189.38 05-SEP-06:10
October 1169.53 01-OCT-23:10 704.41 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 303.93 17-OCT-06:30
November 1169.53 01-NOV-00:10 704.41 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 316.06 24-NOV-06:00
December 1169.53 01-DEC-00:10 704.41 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 541.42 11-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   704.41   685.60   0.00 0.00 0.00 0.00 0.00   116.18  
Maximum of Months 1169.53   704.41   685.60   0.00 0.00 0.00 0.00 86.04   541.42  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 815.72 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 177.93 31-JAN-02:00
February 1354.32 01-FEB-00:10 815.72 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 195.18 07-FEB-07:00
March 1354.32 01-MAR-00:10 815.72 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 14.64 15-MAR-14:00 179.28 07-MAR-05:40
April 1354.32 01-APR-00:10 815.72 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 128.38 17-APR-06:00
May 1354.32 01-MAY-00:10 815.72 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 15.45 10-MAY-14:00 99.83 01-MAY-06:00
June 1354.32 01-JUN-00:10 815.72 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 32.16 27-JUN-13:00 81.42 06-JUN-03:40
July 1354.32 01-JUL-00:10 815.72 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 34.70 21-JUL-14:00 55.02 03-JUL-04:20
August 1354.32 01-AUG-00:10 815.72 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 30.58 10-AUG-14:00 58.79 01-AUG-04:55
September 1354.32 01-SEP-00:10 815.72 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 17.25 16-SEP-13:00 82.70 05-SEP-06:10
October 1354.32 01-OCT-23:10 815.72 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 122.57 17-OCT-06:00
November 1354.32 01-NOV-00:10 815.72 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 123.84 24-NOV-06:00
December 1354.32 01-DEC-00:10 815.72 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 208.98 11-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   815.72   793.93   0.00 0.00 0.00 0.00 0.00   55.02  
Maximum of Months 1354.32   815.72   793.93   0.00 0.00 0.00 0.00 34.70   208.98  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 1360.40 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 420.34 31-JAN-02:00
February 286.42 01-FEB-00:10 1360.40 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 461.31 07-FEB-07:00
March 286.42 01-MAR-00:10 1360.40 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 40.98 15-MAR-14:00 421.27 07-MAR-06:40
April 286.42 01-APR-00:10 1360.40 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 296.38 17-APR-06:00
May 286.42 01-MAY-00:10 1360.40 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 41.67 10-MAY-14:00 226.47 01-MAY-06:00
June 286.42 01-JUN-00:10 1360.40 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 75.83 12-JUN-14:00 179.75 06-JUN-03:40
July 286.42 01-JUL-00:10 1360.40 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 79.87 21-JUL-14:00 125.35 06-JUL-04:54
August 286.42 01-AUG-00:10 1360.40 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 72.40 10-AUG-14:00 134.82 01-AUG-06:00
September 286.42 01-SEP-00:10 1360.40 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 41.47 16-SEP-13:00 184.82 05-SEP-06:10
October 286.42 01-OCT-23:10 1360.40 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 2.19 11-OCT-13:00 278.43 17-OCT-06:50
November 286.42 01-NOV-00:10 1360.40 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 288.30 24-NOV-06:00
December 286.42 01-DEC-00:10 1360.40 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 493.89 11-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   1360.40   839.45   0.00 0.00 0.00 0.00 0.00   125.35  
Maximum of Months 286.42   1360.40   839.45   0.00 0.00 0.00 0.00 79.87   493.89  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 227.72 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 242.51 31-JAN-02:00
February 220.32 01-FEB-00:10 227.72 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 266.14 07-FEB-07:00
March 220.32 01-MAR-00:10 227.72 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 23.85 15-MAR-14:00 243.05 07-MAR-06:00
April 220.32 01-APR-00:10 227.72 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 171.00 17-APR-06:00
May 220.32 01-MAY-00:10 227.72 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 24.29 10-MAY-14:00 128.90 01-MAY-06:00
June 220.32 01-JUN-00:10 227.72 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 43.99 12-JUN-14:00 102.24 06-JUN-03:40
July 220.32 01-JUL-00:10 227.72 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 46.14 21-JUL-14:00 71.37 06-JUL-04:56
August 220.32 01-AUG-00:10 227.72 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 41.94 10-AUG-14:00 76.69 01-AUG-04:55
September 220.32 01-SEP-00:10 227.72 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 24.17 16-SEP-13:00 104.81 05-SEP-06:00
October 220.32 01-OCT-23:10 227.72 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 1.46 11-OCT-13:00 159.95 17-OCT-06:50
November 220.32 01-NOV-00:10 227.72 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 166.33 24-NOV-06:00
December 220.32 01-DEC-00:10 227.72 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 284.95 11-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   227.72   242.16   0.00 0.00 0.00 0.00 0.00   71.37  
Maximum of Months 220.32   227.72   242.16   0.00 0.00 0.00 0.00 46.14   284.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 357.21 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 0.00 01-JAN-00:05 613.80 04-JAN-08:00
February 907.20 01-FEB-00:10 357.21 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 0.00 01-FEB-00:03 675.19 07-FEB-07:10
March 907.20 01-MAR-00:10 357.21 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 43.38 15-MAR-14:00 622.47 07-MAR-07:00
April 907.20 01-APR-00:10 357.21 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 0.00 01-APR-00:10 451.81 17-APR-06:00
May 907.20 01-MAY-00:10 357.21 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 54.79 14-MAY-15:20 343.96 01-MAY-06:00
June 907.20 01-JUN-00:10 357.21 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 111.01 27-JUN-13:00 280.63 06-JUN-03:40
July 907.20 01-JUL-00:10 357.21 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 126.69 16-JUL-16:00 176.63 06-JUL-05:20
August 907.20 01-AUG-00:10 357.21 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 112.93 13-AUG-15:20 194.10 03-AUG-05:30
September 907.20 01-SEP-00:10 357.21 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 64.95 16-SEP-13:00 312.52 05-SEP-06:10
October 907.20 01-OCT-23:10 357.21 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 0.00 01-OCT-00:10 426.23 17-OCT-07:00
November 907.20 01-NOV-00:10 357.21 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 0.00 01-NOV-00:10 431.06 24-NOV-06:20
December 907.20 01-DEC-00:10 357.21 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 0.00 01-DEC-00:03 701.86 11-DEC-06:10
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   357.21   4572.80   39726.58   0.00 0.00 0.00 0.00   176.63  
Maximum of Months 907.20   357.21   4572.80   39726.58   0.00 0.00 0.00 126.69   701.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 1761.91 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1018.94 31-JAN-02:00
February 15368.40 01-FEB-00:10 1761.91 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 1117.91 07-FEB-07:00
March 15368.40 01-MAR-00:10 1761.91 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 52.74 15-MAR-14:00 1026.56 07-MAR-05:20
April 15368.40 01-APR-00:10 1761.91 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 718.25 17-APR-06:00
May 15368.40 01-MAY-00:10 1761.91 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 63.42 14-MAY-15:00 568.06 01-MAY-05:00
June 15368.40 01-JUN-00:10 1761.91 01-JUN-19:30 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 163.28 27-JUN-13:00 481.27 06-JUN-03:40
July 15368.40 01-JUL-00:10 1761.91 03-JUL-19:40 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 190.22 21-JUL-14:00 318.38 06-JUL-04:54
August 15368.40 01-AUG-00:10 1761.91 01-AUG-19:30 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 163.40 10-AUG-14:00 334.55 01-AUG-04:55
September 15368.40 01-SEP-00:10 1761.91 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 80.28 16-SEP-13:00 469.86 06-SEP-03:43
October 15368.40 01-OCT-23:10 1761.91 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 698.67 17-OCT-04:20
November 15368.40 01-NOV-00:10 1761.91 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 709.50 24-NOV-06:00
December 15368.40 01-DEC-00:10 1761.91 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 1196.86 11-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   1761.91   965.27   0.00 0.00 0.00 0.00 0.00   318.38  
Maximum of Months 15368.40   1761.91   965.27   0.00 0.00 0.00 0.00 190.22   1196.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 10265.18 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2987.56 31-JAN-02:00
February 45622.98 01-FEB-00:10 10265.18 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 3207.43 07-FEB-07:00
March 45622.98 01-MAR-00:10 10265.18 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 193.88 15-MAR-14:00 3013.29 07-MAR-05:40
April 45622.98 01-APR-00:10 10265.18 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2152.98 17-APR-06:00
May 45622.98 01-MAY-00:10 10265.18 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 222.13 10-MAY-14:00 1694.83 01-MAY-05:00
June 45622.98 01-JUN-00:10 10265.18 01-JUN-19:30 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 509.86 27-JUN-13:00 1382.48 06-JUN-03:40
July 45622.98 01-JUL-00:10 10265.18 03-JUL-19:30 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 559.73 21-JUL-14:00 933.42 03-JUL-04:50
August 45622.98 01-AUG-00:10 10265.18 01-AUG-19:19 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 482.10 10-AUG-14:00 981.48 01-AUG-04:55
September 45622.98 01-SEP-00:10 10265.18 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 243.46 16-SEP-13:00 1375.99 06-SEP-05:00
October 45622.98 01-OCT-23:10 10265.18 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 2075.68 17-OCT-04:40
November 45622.98 01-NOV-00:10 10265.18 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2105.47 24-NOV-06:00
December 45622.98 01-DEC-00:10 10265.18 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 3472.90 11-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   10265.18   10029.21   0.00 0.00 0.00 0.00 0.00   933.42  
Maximum of Months 45622.98   10265.18   10029.21   0.00 0.00 0.00 0.00 559.73   3472.90  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 268.61 31-JAN-02:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 294.69 07-FEB-07:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 28.71 15-MAR-15:08 269.23 07-MAR-06:06
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 189.71 17-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 31.11 14-MAY-15:10 139.88 01-MAY-06:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 55.60 12-JUN-15:10 102.63 10-JUN-05:00
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 63.58 19-JUL-15:10 65.73 03-JUL-04:07
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 57.09 13-AUG-15:10 70.52 03-AUG-05:37
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 36.55 16-SEP-15:10 107.55 05-SEP-06:00
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 6.41 11-OCT-15:10 177.51 17-OCT-06:15
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 184.56 24-NOV-06:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 315.45 11-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 0.00   65.73  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 63.58   315.45  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 268.59 31-JAN-02:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 294.67 07-FEB-07:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 28.70 15-MAR-15:10 269.20 07-MAR-06:06
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 189.70 17-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 31.10 14-MAY-15:08 139.87 01-MAY-06:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 55.59 12-JUN-15:10 102.62 10-JUN-05:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 63.58 19-JUL-15:10 65.73 03-JUL-04:07
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 57.09 13-AUG-15:10 70.52 03-AUG-05:37
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 36.55 16-SEP-15:10 107.54 05-SEP-06:00
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 6.41 11-OCT-15:10 177.50 17-OCT-07:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 184.54 24-NOV-06:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 315.42 11-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 0.00   65.73  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 63.58   315.42  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 76.99 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 70.20 31-JAN-02:00
February 0.00 01-FEB-00:10 76.99 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 77.40 07-FEB-07:00
March 0.00 01-MAR-00:10 76.99 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 5.01 15-MAR-14:00 70.27 07-MAR-06:06
April 0.00 01-APR-00:10 76.99 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 48.33 17-APR-06:00
May 0.00 01-MAY-00:10 76.99 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 4.96 14-MAY-15:00 38.87 01-MAY-06:00
June 0.00 01-JUN-00:10 76.99 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 13.09 27-JUN-13:00 30.88 04-JUN-05:00
July 0.00 01-JUL-00:10 76.99 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 15.06 21-JUL-14:00 22.05 03-JUL-05:20
August 0.00 01-AUG-00:10 76.99 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 13.10 10-AUG-14:00 24.00 02-AUG-06:00
September 0.00 01-SEP-00:10 76.99 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 7.03 16-SEP-13:00 33.59 05-SEP-06:00
October 0.00 01-OCT-00:10 76.99 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 48.52 17-OCT-07:00
November 0.00 01-NOV-00:10 76.99 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 46.93 24-NOV-06:00
December 0.00 01-DEC-00:10 76.99 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 83.13 11-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   76.99   232.19   0.00 0.00 0.00 0.00 0.00   22.05  
Maximum of Months 0.00   76.99   232.19   0.00 0.00 0.00 0.00 15.06   83.13  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 77.01 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 74.97 31-JAN-02:00
February 180.00 01-FEB-00:10 77.01 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 82.24 07-FEB-07:00
March 180.00 01-MAR-00:10 77.01 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 8.01 15-MAR-15:10 75.14 07-MAR-06:10
April 180.00 01-APR-00:10 77.01 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 52.95 17-APR-06:00
May 180.00 01-MAY-00:10 77.01 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 8.68 14-MAY-15:08 39.04 01-MAY-06:00
June 180.00 01-JUN-00:10 77.01 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 15.52 12-JUN-15:10 28.64 10-JUN-05:00
July 180.00 01-JUL-00:10 77.01 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 17.74 19-JUL-15:10 18.34 03-JUL-04:10
August 180.00 01-AUG-00:10 77.01 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 15.94 13-AUG-15:10 19.68 03-AUG-05:20
September 180.00 01-SEP-00:10 77.01 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 10.20 16-SEP-15:10 30.01 05-SEP-06:00
October 180.00 01-OCT-00:10 77.01 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 1.79 11-OCT-15:10 49.54 17-OCT-07:00
November 180.00 01-NOV-00:10 77.01 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 51.51 24-NOV-06:00
December 180.00 01-DEC-00:10 77.01 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 88.04 11-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 0.00   18.34  
Maximum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 17.74   88.04  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 268.61 31-JAN-02:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 294.69 07-FEB-07:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 28.71 15-MAR-15:08 269.23 07-MAR-06:06
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 189.71 17-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 31.11 14-MAY-15:10 139.88 01-MAY-06:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 55.60 12-JUN-15:10 102.63 10-JUN-05:00
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 63.58 19-JUL-15:10 65.73 03-JUL-04:50
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 57.10 13-AUG-15:10 73.37 31-AUG-07:20
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 36.55 16-SEP-15:08 107.55 05-SEP-06:00
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 6.42 11-OCT-15:10 177.52 17-OCT-07:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 184.56 24-NOV-06:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 315.45 11-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 0.00   65.73  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 63.58   315.45  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 268.59 31-JAN-02:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 294.67 07-FEB-07:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 28.70 15-MAR-15:08 269.20 07-MAR-06:06
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 189.69 17-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 31.10 14-MAY-15:08 139.87 01-MAY-06:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 55.60 12-JUN-15:10 102.63 10-JUN-05:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 63.58 19-JUL-15:08 65.72 03-JUL-04:07
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 57.09 13-AUG-15:08 73.16 31-AUG-07:20
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 36.55 16-SEP-15:10 107.54 05-SEP-06:00
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 6.41 11-OCT-15:08 177.50 17-OCT-07:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 184.54 24-NOV-06:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 315.42 11-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 0.00   65.72  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 63.58   315.42  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 2240.78 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 323.79 31-JAN-02:00
February 2263.36 01-FEB-00:10 2240.78 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 355.31 07-FEB-07:00
March 2263.36 01-MAR-00:10 2240.78 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 31.06 15-MAR-14:00 324.51 07-MAR-06:30
April 2263.36 01-APR-00:10 2240.78 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 228.41 17-APR-06:00
May 2263.36 01-MAY-00:10 2240.78 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 28.63 10-MAY-14:00 173.13 01-MAY-05:00
June 2263.36 01-JUN-00:10 2240.78 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 56.09 12-JUN-14:00 139.72 06-JUN-03:40
July 2263.36 01-JUL-00:10 2240.78 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 60.05 21-JUL-14:00 97.75 03-JUL-04:10
August 2263.36 01-AUG-00:10 2240.78 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 52.31 10-AUG-14:00 104.67 01-AUG-04:55
September 2263.36 01-SEP-00:10 2240.78 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 30.35 16-SEP-13:00 142.93 05-SEP-06:00
October 2263.36 01-OCT-23:10 2240.78 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 213.67 17-OCT-07:00
November 2263.36 01-NOV-00:10 2240.78 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 222.20 24-NOV-06:00
December 2263.36 01-DEC-00:10 2240.78 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 380.39 11-DEC-06:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   2240.78   0.00 0.00 0.00 0.00 0.00 0.00   97.75  
Maximum of Months 2263.36   2240.78   0.00 0.00 0.00 0.00 0.00 60.05   380.39  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 269.13 31-JAN-02:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 295.21 07-FEB-07:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 28.32 15-MAR-15:10 269.75 07-MAR-06:06
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 190.19 17-APR-06:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 30.72 14-MAY-15:10 140.33 01-MAY-06:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 55.22 12-JUN-15:10 103.08 10-JUN-05:00
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 63.20 19-JUL-15:10 66.16 03-JUL-04:07
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 56.71 13-AUG-15:10 70.95 03-AUG-05:37
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 36.17 16-SEP-15:10 107.99 05-SEP-06:00
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 6.00 11-OCT-15:10 178.00 17-OCT-07:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 185.04 24-NOV-06:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 315.99 11-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 0.00   66.16  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 63.20   315.99  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 269.11 31-JAN-02:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 295.19 07-FEB-07:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 28.32 15-MAR-15:07 269.73 07-MAR-06:06
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 190.18 17-APR-06:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 30.72 14-MAY-15:10 140.32 01-MAY-06:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 55.22 12-JUN-15:10 103.07 10-JUN-05:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 63.20 19-JUL-15:10 66.15 03-JUL-04:10
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 56.71 13-AUG-15:10 70.95 03-AUG-05:12
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 36.16 16-SEP-15:10 107.98 05-SEP-06:00
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 6.02 11-OCT-15:08 177.98 17-OCT-06:15
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 185.02 24-NOV-06:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 315.96 11-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 0.00   66.15  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 63.20   315.96  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 77.01 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 137.70 31-JAN-02:00
February 180.00 01-FEB-00:10 77.01 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 151.05 07-FEB-07:00
March 180.00 01-MAR-00:10 77.01 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 14.49 15-MAR-15:10 138.01 07-MAR-06:10
April 180.00 01-APR-00:10 77.01 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 97.31 17-APR-06:00
May 180.00 01-MAY-00:10 77.01 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 15.72 14-MAY-15:10 71.80 01-MAY-06:00
June 180.00 01-JUN-00:10 77.01 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 28.26 12-JUN-15:10 52.74 10-JUN-05:00
July 180.00 01-JUL-00:10 77.01 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 32.34 19-JUL-15:10 33.85 03-JUL-04:07
August 180.00 01-AUG-00:10 77.01 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 29.02 13-AUG-15:10 36.30 03-AUG-05:15
September 180.00 01-SEP-00:10 77.01 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 18.50 16-SEP-15:10 55.25 05-SEP-06:00
October 180.00 01-OCT-00:10 77.01 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 1.66 11-OCT-16:40 91.07 17-OCT-06:50
November 180.00 01-NOV-00:10 77.01 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 94.67 24-NOV-06:00
December 180.00 01-DEC-00:10 77.01 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 161.67 11-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 0.00   33.85  
Maximum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 32.34   161.67  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3094.06 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 700.97 31-JAN-02:00
February 26988.77 01-FEB-00:10 3094.06 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 756.99 07-FEB-07:00
March 26988.77 01-MAR-00:10 3094.06 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 34.44 15-MAR-14:00 703.03 07-MAR-05:30
April 26988.77 01-APR-00:10 3094.06 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 515.61 17-APR-06:00
May 26988.77 01-MAY-00:10 3094.06 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 32.01 10-MAY-14:00 393.35 01-MAY-05:10
June 26988.77 01-JUN-00:10 3094.06 01-JUN-19:40 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 103.08 27-JUN-13:00 333.67 06-JUN-03:40
July 26988.77 01-JUL-00:10 3094.06 03-JUL-19:40 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 120.37 21-JUL-14:00 210.54 03-JUL-04:10
August 26988.77 01-AUG-00:10 3094.06 01-AUG-19:30 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 103.17 10-AUG-14:00 223.12 01-AUG-04:55
September 26988.77 01-SEP-00:10 3094.06 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 49.84 16-SEP-13:00 331.81 05-SEP-06:10
October 26988.77 01-OCT-23:10 3094.06 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 486.81 17-OCT-06:00
November 26988.77 01-NOV-00:10 3094.06 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 503.36 24-NOV-06:00
December 26988.77 01-DEC-00:10 3094.06 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 810.74 11-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 0.00   210.54  
Maximum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 120.37   810.74  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3094.06 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 705.72 31-JAN-02:00
February 26988.77 01-FEB-00:10 3094.06 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 762.15 07-FEB-07:00
March 26988.77 01-MAR-00:10 3094.06 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 32.18 15-MAR-14:00 707.23 07-MAR-05:40
April 26988.77 01-APR-00:10 3094.06 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 516.71 17-APR-06:00
May 26988.77 01-MAY-00:10 3094.06 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 31.85 14-MAY-15:00 393.35 01-MAY-05:10
June 26988.77 01-JUN-00:10 3094.06 01-JUN-19:40 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 103.08 27-JUN-13:00 334.77 06-JUN-03:40
July 26988.77 01-JUL-00:10 3094.06 03-JUL-19:40 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 120.37 21-JUL-14:00 210.54 03-JUL-04:10
August 26988.77 01-AUG-00:10 3094.06 01-AUG-19:30 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 103.17 10-AUG-14:00 223.19 01-AUG-04:55
September 26988.77 01-SEP-00:10 3094.06 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 49.84 16-SEP-13:00 333.89 05-SEP-06:10
October 26988.77 01-OCT-23:10 3094.06 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 486.82 17-OCT-06:00
November 26988.77 01-NOV-00:10 3094.06 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 503.68 24-NOV-06:00
December 26988.77 01-DEC-00:10 3094.06 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 814.99 11-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 0.00   210.54  
Maximum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 120.37   814.99  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1089.83 02-JAN-20:10 14912.86 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 0.00 01-JAN-00:05 626.89 04-JAN-08:00
February 2401.70 01-FEB-00:10 1089.83 01-FEB-20:10 14912.86 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 0.00 01-FEB-00:03 694.33 07-FEB-07:00
March 2401.70 01-MAR-00:10 1089.83 01-MAR-20:10 14912.86 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 28.92 15-MAR-14:00 638.96 07-MAR-06:10
April 2401.70 01-APR-00:10 1089.83 03-APR-19:10 14912.86 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 0.00 01-APR-00:10 462.48 17-APR-06:00
May 2401.70 01-MAY-00:10 1089.83 01-MAY-19:10 14912.86 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 28.64 14-MAY-15:00 352.08 01-MAY-05:10
June 2401.70 01-JUN-00:10 1089.83 01-JUN-19:10 14912.86 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 92.42 27-JUN-13:00 315.56 06-JUN-03:40
July 2401.70 01-JUL-00:10 1089.83 03-JUL-19:10 14912.86 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 107.86 21-JUL-14:00 192.24 06-JUL-04:43
August 2401.70 01-AUG-00:10 1089.83 01-AUG-19:10 14912.86 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 92.46 10-AUG-14:00 201.62 01-AUG-04:55
September 2401.70 01-SEP-00:10 1089.83 01-SEP-19:10 14912.86 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 44.75 16-SEP-13:00 330.57 05-SEP-06:10
October 2401.70 01-OCT-23:10 1089.83 02-OCT-19:10 14912.86 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 0.00 01-OCT-00:10 435.77 17-OCT-06:15
November 2401.70 01-NOV-00:10 1089.83 01-NOV-19:10 14912.86 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 0.00 01-NOV-00:10 449.19 24-NOV-06:10
December 2401.70 01-DEC-00:10 1089.83 01-DEC-20:10 14912.86 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 0.00 01-DEC-00:03 719.23 11-DEC-06:20
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1089.83   14912.86   22492.83   0.00 0.00 0.00 0.00   192.24  
Maximum of Months 2401.70   1089.83   14912.86   22492.83   0.00 0.00 0.00 107.86   719.23  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 2371.52 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 574.00 31-JAN-02:00
February 2395.44 01-FEB-00:10 2371.52 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 629.80 07-FEB-07:00
March 2395.44 01-MAR-00:10 2371.52 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 41.60 15-MAR-14:00 575.31 07-MAR-05:30
April 2395.44 01-APR-00:10 2371.52 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 405.16 17-APR-06:00
May 2395.44 01-MAY-00:10 2371.52 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 40.04 10-MAY-15:00 299.10 01-MAY-05:00
June 2395.44 01-JUN-00:10 2371.52 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 90.31 27-JUN-13:00 244.09 06-JUN-03:40
July 2395.44 01-JUL-00:10 2371.52 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 105.45 21-JUL-14:00 167.95 06-JUL-04:54
August 2395.44 01-AUG-00:10 2371.52 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 90.38 10-AUG-14:00 180.18 01-AUG-04:55
September 2395.44 01-SEP-00:10 2371.52 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 45.66 16-SEP-13:00 244.81 05-SEP-06:10
October 2395.44 01-OCT-23:10 2371.52 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 379.10 17-OCT-06:50
November 2395.44 01-NOV-00:10 2371.52 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 394.17 24-NOV-06:00
December 2395.44 01-DEC-00:10 2371.52 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 674.23 11-DEC-06:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   2371.52   0.00 0.00 0.00 0.00 0.00 0.00   167.95  
Maximum of Months 2395.44   2371.52   0.00 0.00 0.00 0.00 0.00 105.45   674.23  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 20981.29 17-JAN-21:44 92015.14 113483.66 86233.46 0.00 0.00 0.00 0.00 0.00 0.00
February 18243.87 19-FEB-11:36 38339.64 47285.09 42584.43 0.00 0.00 0.00 0.00 0.00 0.00
March 21794.05 12-MAR-06:42 80513.24 56741.02 47907.48 0.00 0.00 0.00 0.00 0.00 0.00
April 21414.59 23-APR-21:27 92015.14 70927.09 57488.97 0.00 0.00 0.00 0.00 0.00 0.00
May 20375.25 02-MAY-23:56 92015.14 25218.23 25550.66 0.00 0.00 0.00 0.00 0.00 0.00
June 20694.70 04-JUN-02:43 26837.75 9456.84 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
July 15988.08 16-JUL-10:33 11501.89 14185.53 12775.33 0.00 0.00 0.00 0.00 0.00 0.00
August 18736.87 31-AUG-21:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
September 35373.65 30-SEP-05:35 35783.66 18914.03 17033.77 0.00 0.00 0.00 0.00 0.00 0.00
October 35620.85 26-OCT-22:50 23003.78 9457.02 8516.89 0.00 0.00 0.00 0.00 0.00 0.00
November 35702.72 03-NOV-18:57 26837.75 37827.89 28744.49 0.00 0.00 0.00 0.00 0.00 0.00
December 34234.80 13-DEC-20:47 89459.16 141853.45 101138.01 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 15988.08   10223.90 9456.84 8516.89 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 35702.72   92015.14 141853.45 101138.01 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2426.98 15-JAN-11:34 3898.44 2348.05 2886.75 0.00 0.00 0.00 0.00 0.00 233.10
February 2436.32 17-FEB-11:36 2598.96 1956.71 2525.91 0.00 0.00 0.00 0.00 0.00 226.85
March 3146.06 15-MAR-13:30 259.90 195.67 252.59 0.00 0.00 0.00 0.00 17.63 0.00
April 3034.95 11-APR-14:12 1949.22 978.35 1262.95 0.00 0.00 0.00 0.00 0.00 177.26
May 2522.71 22-MAY-23:32 7017.19 939.22 1299.04 0.00 0.00 0.00 0.00 0.00 132.17
June 2751.17 13-JUN-06:12 2079.17 1565.37 1732.05 0.00 0.00 0.00 0.00 0.00 153.52
July 3306.30 21-JUL-13:30 259.90 195.67 252.59 0.00 0.00 0.00 0.00 80.05 0.00
August 3637.61 18-AUG-13:30 259.90 195.67 252.59 0.00 0.00 0.00 0.00 64.09 0.00
September 4404.20 21-SEP-13:00 259.90 195.67 252.59 0.00 0.00 0.00 0.00 11.46 0.00
October 4544.38 17-OCT-13:14 2598.96 1956.71 2525.91 0.00 0.00 0.00 0.00 0.00 194.33
November 3696.92 03-NOV-12:40 519.79 391.34 505.18 0.00 0.00 0.00 0.00 0.00 187.23
December 2507.67 16-DEC-11:40 1559.38 782.68 1010.36 0.00 0.00 0.00 0.00 0.00 235.74
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2426.98   259.90 195.67 252.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4544.38   7017.19 2348.05 2886.75 0.00 0.00 0.00 0.00 80.05 235.74



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1507.58 17-JAN-21:58 6019.20 3625.40 3760.73 0.00 0.00 0.00 0.00 0.00 86.76
February 1513.32 15-FEB-00:30 10834.56 1450.16 2005.72 0.00 0.00 0.00 0.00 0.00 68.31
March 1941.69 12-MAR-06:42 9480.24 3262.86 3760.73 0.00 0.00 0.00 0.00 0.00 74.98
April 2109.09 23-APR-21:27 10834.56 4078.58 4512.87 0.00 0.00 0.00 0.00 0.00 76.41
May 1970.29 02-MAY-23:56 10834.56 1450.16 2005.72 0.00 0.00 0.00 0.00 0.00 65.56
June 2023.22 04-JUN-02:43 3160.08 543.81 752.15 0.00 0.00 0.00 0.00 0.00 67.85
July 2092.10 19-JUL-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 11.85 0.00
August 2117.97 10-AUG-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 9.21 0.00
September 2090.52 03-SEP-02:62 5266.80 906.35 1253.58 0.00 0.00 0.00 0.00 0.00 71.73
October 2205.00 14-OCT-07:59 7524.00 3625.40 4178.59 0.00 0.00 0.00 0.00 0.00 77.86
November 1926.30 03-NOV-20:49 12038.40 7250.80 7521.46 0.00 0.00 0.00 0.00 0.00 83.62
December 1531.33 01-DEC-21:47 4815.36 2900.32 3008.58 0.00 0.00 0.00 0.00 0.00 78.56
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1507.58   1203.84 543.81 752.15 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2205.00   12038.40 7250.80 7521.46 0.00 0.00 0.00 0.00 11.85 86.76



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1277.43 17-JAN-21:58 1272.96 6046.21 3976.33 0.00 0.00 0.00 0.00 0.00 192.56
February 1227.84 22-FEB-23:00 1718.50 5441.59 3711.24 0.00 0.00 0.00 0.00 0.00 155.01
March 1727.17 12-MAR-06:42 2004.91 5441.59 3976.33 0.00 0.00 0.00 0.00 0.00 167.67
April 1842.93 23-APR-21:27 2291.33 6801.98 4771.59 0.00 0.00 0.00 0.00 0.00 167.76
May 1760.72 27-MAY-04:55 572.83 302.31 353.45 0.00 0.00 0.00 0.00 0.00 156.45
June 1887.23 04-JUN-02:43 668.30 906.93 795.27 0.00 0.00 0.00 0.00 0.00 157.35
July 2120.02 21-JUL-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 0.00 7.38
August 1822.05 10-AUG-21:00 254.59 1209.24 795.27 0.00 0.00 0.00 0.00 21.75 0.00
September 1904.95 03-SEP-02:62 1113.84 1511.55 1325.44 0.00 0.00 0.00 0.00 0.00 162.85
October 2038.48 14-OCT-07:59 1591.20 6046.21 4418.14 0.00 0.00 0.00 0.00 0.00 179.22
November 1632.50 03-NOV-20:49 2545.92 12092.41 7952.65 0.00 0.00 0.00 0.00 0.00 181.89
December 1296.41 01-DEC-21:47 1018.37 4836.96 3181.06 0.00 0.00 0.00 0.00 0.00 173.13
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1227.84   222.77 302.31 353.45 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2120.02   2545.92 12092.41 7952.65 0.00 0.00 0.00 0.00 21.75 192.56



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 577.97 17-JAN-21:58 979.20 1012.07 1147.06 0.00 0.00 0.00 0.00 0.00 107.62
February 564.99 22-FEB-23:00 1321.92 910.87 1070.59 0.00 0.00 0.00 0.00 0.00 87.05
March 723.19 17-MAR-17:03 1224.00 1518.11 1784.32 0.00 0.00 0.00 0.00 0.00 98.41
April 859.35 23-APR-21:27 1762.56 1138.58 1376.47 0.00 0.00 0.00 0.00 0.00 94.22
May 839.52 27-MAY-04:55 440.64 50.60 101.96 0.00 0.00 0.00 0.00 0.00 89.53
June 892.97 04-JUN-02:43 514.08 151.81 229.41 0.00 0.00 0.00 0.00 0.00 89.37
July 763.88 21-JUL-21:00 195.84 202.41 229.41 0.00 0.00 0.00 0.00 0.00 7.29
August 719.25 10-AUG-10:33 146.88 189.77 267.65 0.00 0.00 0.00 0.00 31.25 0.00
September 898.68 03-SEP-02:62 856.80 253.02 382.35 0.00 0.00 0.00 0.00 0.00 92.26
October 959.80 14-OCT-07:59 1224.00 1012.07 1274.51 0.00 0.00 0.00 0.00 0.00 101.42
November 776.53 06-NOV-05:05 440.64 101.21 152.94 0.00 0.00 0.00 0.00 0.00 79.06
December 582.87 01-DEC-21:47 783.36 809.66 917.65 0.00 0.00 0.00 0.00 0.00 96.07
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 564.99   146.88 50.60 101.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 959.80   1762.56 1518.11 1784.32 0.00 0.00 0.00 0.00 31.25 107.62



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 48379.95 17-JAN-21:44 7257.60 2857.71 38989.14 338721.34 0.00 0.00 0.00 0.00 311.66
February 48716.43 14-FEB-20:26 7056.00 3572.14 45728.01 397265.76 0.00 0.00 0.00 0.00 305.85
March 48431.07 09-MAR-20:54 5644.80 2857.71 36582.41 317812.61 0.00 0.00 0.00 0.00 285.41
April 50584.66 21-APR-20:49 5644.80 2222.66 30324.89 263449.93 0.00 0.00 0.00 0.00 279.60
May 50793.72 06-MAY-21:28 6350.40 2143.28 30324.89 263449.93 0.00 0.00 0.00 0.00 276.33
June 38543.49 27-JUN-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 1.47
July 38791.36 21-JUL-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 10.09
August 38720.81 10-AUG-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 22.67 0.00
September 41960.12 06-SEP-06:47 3225.60 1587.62 23104.68 200723.75 0.00 0.00 0.00 0.00 264.51
October 49725.35 17-OCT-19:24 7056.00 3572.14 45728.01 397265.76 0.00 0.00 0.00 0.00 340.06
November 52483.10 06-NOV-21:28 4032.00 1587.62 21660.63 188178.52 0.00 0.00 0.00 0.00 318.26
December 49526.77 13-DEC-20:47 7056.00 3572.14 45728.01 397265.76 0.00 0.00 0.00 0.00 317.74
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 38543.49   705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 52483.10   7257.60 3572.14 45728.01 397265.76 0.00 0.00 0.00 22.67 340.06



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 10668.88 15-JAN-11:34 51228.00 3582.54 4064.31 0.00 0.00 0.00 0.00 0.00 537.78
February 11040.41 15-FEB-00:30 122947.20 3132.28 2438.58 0.00 0.00 0.00 0.00 0.00 412.26
March 14939.76 08-MAR-13:23 34152.00 2985.45 3556.27 0.00 0.00 0.00 0.00 0.00 481.16
April 13984.50 23-APR-21:27 122947.20 8809.53 5486.82 0.00 0.00 0.00 0.00 0.00 430.05
May 14284.11 09-MAY-00:55 61473.60 1174.60 1016.08 0.00 0.00 0.00 0.00 0.00 423.51
June 12968.16 06-JUN-02:04 76842.00 978.84 1016.08 0.00 0.00 0.00 0.00 0.00 438.07
July 11672.46 20-JUL-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 37.91 0.00
August 12764.00 17-AUG-15:03 51228.00 1791.27 2133.76 0.00 0.00 0.00 0.00 122.46 0.00
September 15072.61 21-SEP-14:10 5122.80 298.55 355.63 0.00 0.00 0.00 0.00 42.59 0.00
October 18710.04 31-OCT-23:20 153684.00 3915.35 3048.23 0.00 0.00 0.00 0.00 0.00 464.58
November 14710.86 03-NOV-12:40 6830.40 597.09 711.25 0.00 0.00 0.00 0.00 0.00 415.30
December 10907.25 16-DEC-11:40 20491.20 1194.18 1422.51 0.00 0.00 0.00 0.00 0.00 541.06
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 10668.88   5122.80 298.55 355.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18710.04   153684.00 8809.53 5486.82 0.00 0.00 0.00 0.00 122.46 541.06



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 32449.71 17-JAN-21:58 202768.80 45623.04 47506.78 0.00 0.00 0.00 0.00 0.00 1467.41
February 33988.00 15-FEB-00:30 364983.84 18249.22 25336.95 0.00 0.00 0.00 0.00 0.00 1199.74
March 46777.63 29-MAR-21:00 81107.52 18249.22 19002.71 0.00 0.00 0.00 0.00 0.00 1537.96
April 59795.74 20-APR-22:30 456229.80 34217.28 42228.25 0.00 0.00 0.00 0.00 0.00 1309.35
May 61158.08 23-MAY-04:22 273737.88 13686.91 19002.71 0.00 0.00 0.00 0.00 0.00 1298.21
June 63477.84 06-JUN-03:42 228114.90 5702.88 10557.06 0.00 0.00 0.00 0.00 0.00 1327.53
July 41543.36 20-JUL-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 108.16 0.00
August 41416.07 10-AUG-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 144.77 0.00
September 57539.39 06-SEP-01:37 136868.94 3421.73 6334.24 0.00 0.00 0.00 0.00 0.00 1215.14
October 64454.80 31-OCT-23:40 182491.92 9124.61 12668.47 0.00 0.00 0.00 0.00 0.00 1339.61
November 57688.17 27-NOV-23:07 136868.94 10265.18 12668.47 0.00 0.00 0.00 0.00 0.00 1380.52
December 33032.92 01-DEC-21:47 162215.04 36498.43 38005.42 0.00 0.00 0.00 0.00 0.00 1334.97
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 32449.71   45622.98 3421.73 6334.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 64454.80   456229.80 45623.04 47506.78 0.00 0.00 0.00 0.00 144.77 1537.96



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2826.04 15-JAN-16:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 0.00 120.55
February 2975.03 28-FEB-16:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 0.00 157.41
March 3137.88 15-MAR-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 19.88 0.00
April 3158.07 19-APR-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 0.00 37.06
May 3381.97 23-MAY-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 9.03 0.00
June 3411.40 30-JUN-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 2.86 0.00
July 3372.47 16-JUL-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 45.26 0.00
August 3366.68 13-AUG-18:02 702.00 735.03 774.39 0.00 0.00 0.00 0.00 25.90 0.00
September 3354.21 19-SEP-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 12.24
October 3115.69 25-OCT-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 0.00 28.01
November 2999.55 03-NOV-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 87.38
December 938.05 20-DEC-19:04 970.20 763.21 903.46 0.00 0.00 0.00 0.00 0.00 122.80
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 938.05   324.00 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3411.40   970.20 763.21 903.46 0.00 0.00 0.00 0.00 45.26 157.41



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 964.40 11-JAN-16:04 680.40 240.08 479.33 0.00 0.00 0.00 0.00 0.00 65.05
February 888.22 22-FEB-16:03 680.40 240.08 479.33 0.00 0.00 0.00 0.00 0.00 70.71
March 3041.97 15-MAR-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 20.28 0.00
April 3021.86 19-APR-15:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 0.00 36.36
May 3270.85 23-MAY-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 9.10 0.00
June 3314.75 30-JUN-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 2.64 0.00
July 3282.93 11-JUL-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 24.71 0.00
August 3248.17 14-AUG-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 21.63 0.00
September 3225.90 16-SEP-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 26.92 0.00
October 2856.85 12-OCT-15:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 0.00 28.78
November 1511.53 15-NOV-16:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 0.00 68.86
December 959.50 14-DEC-19:04 970.20 763.12 903.35 0.00 0.00 0.00 0.00 0.00 123.33
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 888.22   324.00 205.78 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3314.75   970.20 763.12 903.35 0.00 0.00 0.00 0.00 26.92 123.33



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 93.88 15-JAN-15:30 0.00 25.41 74.82 0.00 0.00 0.00 0.00 0.00 34.84
February 90.22 28-FEB-15:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 44.61
March 463.99 15-MAR-13:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 4.01 0.00
April 395.48 22-APR-13:10 0.00 25.41 74.82 0.00 0.00 0.00 0.00 0.00 16.74
May 382.96 27-MAY-13:00 0.00 25.41 74.82 0.00 0.00 0.00 0.00 0.00 3.17
June 500.05 27-JUN-13:00 0.00 21.56 67.08 0.00 0.00 0.00 0.00 13.09 0.00
July 571.61 21-JUL-13:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 14.10 0.00
August 638.65 18-AUG-13:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 11.52 0.00
September 782.43 21-SEP-13:00 0.00 21.56 67.08 0.00 0.00 0.00 0.00 3.02 0.00
October 757.32 11-OCT-12:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 2.67
November 373.74 01-NOV-11:50 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 23.79
December 96.10 17-DEC-13:40 0.00 25.41 74.82 0.00 0.00 0.00 0.00 0.00 41.46
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 90.22   0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 782.43   0.00 25.41 74.82 0.00 0.00 0.00 0.00 14.10 44.61



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 470.16 19-JAN-19:04 970.20 479.78 885.15 0.00 0.00 0.00 0.00 0.00 41.66
February 471.61 17-FEB-19:04 970.20 479.78 885.15 0.00 0.00 0.00 0.00 0.00 41.75
March 880.69 15-MAR-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 6.59 0.00
April 820.74 07-APR-15:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 0.00 5.85
May 955.60 23-MAY-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 0.50 0.00
June 979.74 30-JUN-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 0.73 0.00
July 974.89 14-JUL-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 8.54 0.00
August 993.71 09-AUG-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 10.65 0.00
September 923.22 16-SEP-18:02 702.00 462.06 758.70 0.00 0.00 0.00 0.00 4.37 0.00
October 773.47 12-OCT-15:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 0.00 5.89
November 550.11 26-NOV-09:02 270.00 215.63 799.99 0.00 0.00 0.00 0.00 0.00 20.12
December 512.95 13-DEC-19:04 970.20 479.78 885.15 0.00 0.00 0.00 0.00 0.00 34.35
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 470.16   270.00 129.38 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 993.71   970.20 479.78 885.15 0.00 0.00 0.00 0.00 10.65 41.75



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 964.34 10-JAN-09:04 252.00 377.32 792.83 0.00 0.00 0.00 0.00 0.00 228.62
February 1206.90 28-FEB-09:01 252.00 377.32 792.83 0.00 0.00 0.00 0.00 0.00 211.33
March 2885.32 15-MAR-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 19.55 0.00
April 2878.85 07-APR-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 0.00 29.20
May 3081.69 23-MAY-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 9.00 0.00
June 3075.96 12-JUN-08:61 252.00 377.32 792.83 0.00 0.00 0.00 0.00 16.20 0.00
July 3056.39 19-JUL-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 53.69 0.00
August 3064.43 13-AUG-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 47.22 0.00
September 3043.13 16-SEP-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 26.92 0.00
October 2771.51 31-OCT-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 59.01
November 2546.62 03-NOV-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 81.23
December 1259.55 17-DEC-09:03 378.00 480.22 1143.15 0.00 0.00 0.00 0.00 0.00 148.62
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 964.34   252.00 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3081.69   680.40 480.22 1143.15 0.00 0.00 0.00 0.00 53.69 228.62



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 938.59 21-JAN-09:04 378.00 480.16 1143.02 0.00 0.00 0.00 0.00 0.00 168.77
February 891.01 15-FEB-09:04 252.00 377.27 792.74 0.00 0.00 0.00 0.00 0.00 100.10
March 2786.97 15-MAR-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 19.92 0.00
April 2756.09 21-APR-08:61 288.00 431.17 905.99 0.00 0.00 0.00 0.00 0.00 106.17
May 2983.32 23-MAY-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 9.07 0.00
June 2977.57 12-JUN-08:61 252.00 377.27 792.74 0.00 0.00 0.00 0.00 16.01 0.00
July 2974.95 18-JUL-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 32.45 0.00
August 2975.05 18-AUG-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 47.30 0.00
September 2874.25 19-SEP-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 0.00 10.39
October 2430.96 22-OCT-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 0.00 2.43
November 1780.65 06-NOV-09:01 252.00 377.27 792.74 0.00 0.00 0.00 0.00 0.00 97.12
December 944.77 04-DEC-09:04 252.00 377.27 792.74 0.00 0.00 0.00 0.00 0.00 168.91
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 891.01   252.00 205.78 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2983.32   583.20 480.16 1143.02 0.00 0.00 0.00 0.00 47.30 168.91



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1993.29 17-JAN-21:58 10059.36 9959.03 0.00 0.00 0.00 0.00 0.00 0.00 144.24
February 2101.03 15-FEB-00:30 18106.85 3983.61 0.00 0.00 0.00 0.00 0.00 0.00 114.61
March 2497.03 17-MAR-17:03 12574.20 14938.54 0.00 0.00 0.00 0.00 0.00 0.00 132.18
April 3043.03 23-APR-21:27 18106.85 11203.91 0.00 0.00 0.00 0.00 0.00 0.00 129.42
May 2946.62 27-MAY-04:55 4526.71 497.95 0.00 0.00 0.00 0.00 0.00 0.00 122.10
June 3107.36 04-JUN-02:43 5281.16 1493.85 0.00 0.00 0.00 0.00 0.00 0.00 121.07
July 2947.35 21-JUL-18:05 10562.33 11950.84 0.00 0.00 0.00 0.00 0.00 36.21 0.00
August 2605.39 10-AUG-18:40 1760.39 1991.81 0.00 0.00 0.00 0.00 0.00 16.67 0.00
September 3134.66 03-SEP-02:62 8801.94 2489.76 0.00 0.00 0.00 0.00 0.00 0.00 125.23
October 3254.70 14-OCT-07:59 12574.20 9959.03 0.00 0.00 0.00 0.00 0.00 0.00 134.17
November 2613.73 06-NOV-05:05 4526.71 995.90 0.00 0.00 0.00 0.00 0.00 0.00 103.94
December 1994.49 24-DEC-21:42 20118.72 14938.54 0.00 0.00 0.00 0.00 0.00 0.00 121.29
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1993.29   1760.39 497.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3254.70   20118.72 14938.54 0.00 0.00 0.00 0.00 0.00 36.21 144.24



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2896.85 15-JAN-16:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 0.00 119.80
February 3001.94 28-FEB-16:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 0.00 155.18
March 3237.51 14-MAR-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 12.43 0.00
April 3282.04 19-APR-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 0.00 37.39
May 3519.90 23-MAY-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 8.61 0.00
June 3547.89 30-JUN-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 2.48 0.00
July 3476.01 20-JUL-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 41.67 0.00
August 3477.94 13-AUG-18:02 702.00 735.03 774.39 0.00 0.00 0.00 0.00 25.52 0.00
September 3484.78 19-SEP-15:02 583.20 205.81 410.90 0.00 0.00 0.00 0.00 0.00 12.55
October 3198.01 25-OCT-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 0.00 27.41
November 3127.32 15-NOV-16:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 0.00 77.59
December 1087.15 01-DEC-16:04 777.60 274.41 547.87 0.00 0.00 0.00 0.00 0.00 97.11
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1087.15   378.00 205.81 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3547.89   831.60 735.03 774.39 0.00 0.00 0.00 0.00 41.67 155.18



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 961.87 15-JAN-16:03 378.00 282.96 534.64 0.00 0.00 0.00 0.00 0.00 117.80
February 1268.75 18-FEB-16:03 378.00 282.96 534.64 0.00 0.00 0.00 0.00 0.00 138.65
March 3158.35 15-MAR-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 19.87 0.00
April 3128.08 07-APR-15:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 0.00 28.63
May 3394.52 23-MAY-15:02 583.20 205.78 410.85 0.00 0.00 0.00 0.00 8.69 0.00
June 3438.37 30-JUN-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 2.25 0.00
July 3382.02 10-JUL-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 26.36 0.00
August 3392.96 13-AUG-18:02 702.00 734.94 774.30 0.00 0.00 0.00 0.00 25.50 0.00
September 3369.85 16-SEP-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 26.65 0.00
October 2944.35 12-OCT-15:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 0.00 28.88
November 1511.45 14-NOV-19:03 1386.00 1090.18 1290.50 0.00 0.00 0.00 0.00 0.00 105.04
December 1165.00 01-DEC-16:04 777.60 274.38 547.81 0.00 0.00 0.00 0.00 0.00 97.10
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 961.87   324.00 205.78 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3438.37   1386.00 1090.18 1290.50 0.00 0.00 0.00 0.00 26.65 138.65



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1698.86 15-JAN-16:01 378.00 177.90 523.86 0.00 0.00 0.00 0.00 0.00 65.98
February 1695.67 28-FEB-16:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 0.00 82.49
March 1790.56 15-MAR-18:01 970.20 479.78 885.15 0.00 0.00 0.00 0.00 2.50 0.00
April 1749.96 07-APR-15:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 0.00 15.53
May 1868.10 23-MAY-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 4.12 0.00
June 1840.11 26-JUN-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 17.23 0.00
July 1852.13 20-JUL-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 20.83 0.00
August 1855.25 09-AUG-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 20.21 0.00
September 1856.75 21-SEP-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 10.28 0.00
October 1739.82 25-OCT-15:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 0.00 15.18
November 1705.53 03-NOV-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 0.00 46.18
December 1679.07 04-DEC-16:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 0.00 87.28
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1679.07   378.00 129.38 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1868.10   970.20 479.78 885.15 0.00 0.00 0.00 0.00 20.83 87.28



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 23627.66 17-JAN-06:13 188921.38 12376.22 50609.27 0.00 0.00 0.00 0.00 0.00 291.12
February 29891.34 14-FEB-23:45 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 279.57
March 32669.26 30-MAR-22:37 80966.30 3094.06 20243.71 0.00 0.00 0.00 0.00 0.00 304.52
April 36721.04 20-APR-22:20 215910.14 8250.81 53983.22 0.00 0.00 0.00 0.00 0.00 298.77
May 31999.26 06-MAY-05:43 209912.64 8250.81 56232.52 0.00 0.00 0.00 0.00 0.00 292.54
June 32053.14 14-JUN-02:52 161932.61 2062.70 13495.81 0.00 0.00 0.00 0.00 0.00 292.44
July 23161.02 20-JUL-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 21.01 0.00
August 22876.90 10-AUG-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 29.50 0.00
September 31207.17 30-SEP-05:35 83965.06 4125.41 22493.01 0.00 0.00 0.00 0.00 0.00 294.47
October 31399.43 21-OCT-02:35 107955.07 1375.14 8997.20 0.00 0.00 0.00 0.00 0.00 278.34
November 31863.96 03-NOV-22:31 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 310.20
December 30142.54 01-DEC-23:15 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 321.81
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 22876.90   26988.77 1375.14 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 36721.04   269887.68 12376.22 67479.03 0.00 0.00 0.00 0.00 29.50 321.81



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 27887.67 17-JAN-06:18 188921.38 12376.22 50609.27 0.00 0.00 0.00 0.00 0.00 291.23
February 32569.66 15-FEB-00:30 215910.14 5500.54 17994.41 0.00 0.00 0.00 0.00 0.00 280.89
March 34534.34 30-MAR-22:37 80966.30 3094.06 20243.71 0.00 0.00 0.00 0.00 0.00 306.36
April 38776.73 20-APR-22:20 215910.14 8250.81 53983.22 0.00 0.00 0.00 0.00 0.00 300.56
May 33639.60 06-MAY-05:43 209912.64 8250.81 56232.52 0.00 0.00 0.00 0.00 0.00 293.14
June 33646.01 14-JUN-02:52 161932.61 2062.70 13495.81 0.00 0.00 0.00 0.00 0.00 292.73
July 24336.63 20-JUL-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 20.98 0.00
August 24091.97 10-AUG-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 29.45 0.00
September 33202.37 05-SEP-02:19 188921.38 2406.49 15745.11 0.00 0.00 0.00 0.00 0.00 288.36
October 33724.85 02-OCT-05:32 209912.64 13751.36 56232.52 0.00 0.00 0.00 0.00 0.00 284.55
November 33636.23 03-NOV-22:31 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 311.68
December 31782.23 01-DEC-23:15 269887.68 10313.52 67479.03 0.00 0.00 0.00 0.00 0.00 323.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 24091.97   26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38776.73   269887.68 13751.36 67479.03 0.00 0.00 0.00 0.00 29.45 323.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 35314.13 17-JAN-11:38 5337.12 3027.31 149128.56 187440.26 0.00 0.00 0.00 0.00 280.59
February 35949.75 19-FEB-11:36 8005.68 3632.77 149128.56 187440.26 0.00 0.00 0.00 0.00 297.41
March 37370.92 17-MAR-17:03 13342.80 7265.54 149128.56 224928.32 0.00 0.00 0.00 0.00 282.96
April 36042.13 04-APR-10:36 5337.12 3027.31 149128.56 187440.26 0.00 0.00 0.00 0.00 290.78
May 34463.74 06-MAY-21:28 16811.93 6538.99 134215.70 67478.50 0.00 0.00 0.00 0.00 278.26
June 33727.62 06-JUN-06:20 6404.54 3632.77 89477.13 67478.50 0.00 0.00 0.00 0.00 256.33
July 31437.35 16-JUL-10:40 2401.70 1089.83 44738.57 56232.08 0.00 0.00 0.00 61.49 0.00
August 31352.15 10-AUG-10:40 1601.14 908.19 44738.57 56232.08 0.00 0.00 0.00 62.56 0.00
September 34727.78 06-SEP-06:56 10674.24 6054.62 149128.56 112464.16 0.00 0.00 0.00 0.00 266.15
October 37993.14 29-OCT-16:14 5337.12 1210.92 74564.28 112464.16 0.00 0.00 0.00 0.00 255.06
November 36281.51 08-NOV-18:28 12008.52 6538.99 134215.70 202435.49 0.00 0.00 0.00 0.00 293.46
December 34258.19 01-DEC-18:47 12008.52 6538.99 134215.70 202435.49 0.00 0.00 0.00 0.00 279.48
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 31352.15   1601.14 908.19 44738.57 56232.08 0.00 0.00 0.00 0.00 0.00
Maximum of Months 37993.14   16811.93 7265.54 149128.56 224928.32 0.00 0.00 0.00 62.56 297.41



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4060.18 17-JAN-21:58 10646.40 10540.09 0.00 0.00 0.00 0.00 0.00 0.00 255.47
February 4258.30 15-FEB-00:30 19163.52 4216.04 0.00 0.00 0.00 0.00 0.00 0.00 202.29
March 5086.76 17-MAR-17:03 13308.00 15810.14 0.00 0.00 0.00 0.00 0.00 0.00 234.04
April 6153.11 23-APR-21:27 19163.52 11857.61 0.00 0.00 0.00 0.00 0.00 0.00 227.47
May 5808.13 27-MAY-04:55 4790.88 527.00 0.00 0.00 0.00 0.00 0.00 0.00 209.88
June 6152.76 04-JUN-02:43 5589.36 1581.01 0.00 0.00 0.00 0.00 0.00 0.00 208.57
July 6662.09 21-JUL-13:30 532.32 658.76 0.00 0.00 0.00 0.00 0.00 98.00 0.00
August 6294.86 09-AUG-15:03 7984.80 3952.54 0.00 0.00 0.00 0.00 0.00 74.23 0.00
September 6163.14 03-SEP-02:62 9315.60 2635.02 0.00 0.00 0.00 0.00 0.00 0.00 214.44
October 6476.01 14-OCT-07:59 13308.00 10540.09 0.00 0.00 0.00 0.00 0.00 0.00 232.41
November 5271.67 13-NOV-08:32 5323.20 5270.05 0.00 0.00 0.00 0.00 0.00 0.00 205.31
December 4086.44 01-DEC-18:38 6654.00 7905.07 0.00 0.00 0.00 0.00 0.00 0.00 214.42
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4060.18   532.32 527.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6662.09   19163.52 15810.14 0.00 0.00 0.00 0.00 0.00 98.00 255.47



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.381220E+12 242827.03 19-JAN-20:00 0.755131E+12 608139.25 31-JAN-17:49
February 0.342285E+12 242931.22 22-FEB-20:40 0.695306E+12 641554.11 06-FEB-17:00
March 0.386760E+12 305201.83 15-MAR-19:49 0.589814E+12 551627.86 06-MAR-19:10
April 0.372501E+12 261165.19 07-APR-19:00 0.486506E+12 453356.60 11-APR-20:49
May 0.413372E+12 306848.60 23-MAY-19:40 0.459513E+12 414567.57 11-MAY-17:49
June 0.493196E+12 402484.01 27-JUN-19:00 0.412363E+12 352703.04 05-JUN-17:10
July 0.597484E+12 408101.44 20-JUL-19:49 0.410040E+12 350342.45 03-JUL-17:40
August 0.551962E+12 380415.75 14-AUG-19:30 0.408206E+12 349398.81 31-AUG-17:10
September 0.453740E+12 376256.76 15-SEP-19:00 0.409429E+12 377120.51 28-SEP-16:00
October 0.395155E+12 274579.26 11-OCT-18:10 0.479047E+12 445216.66 17-OCT-18:40
November 0.374669E+12 250328.24 06-NOV-20:19 0.510569E+12 454807.44 20-NOV-18:00
December 0.383374E+12 245831.08 13-DEC-20:00 0.722312E+12 592438.05 10-DEC-17:00
             
Annual Sum or Average 0.514572E+13     0.633823E+13    
Minimum of Months 0.342285E+12 242827.03   0.408206E+12 349398.81  
Maximum of Months 0.597484E+12 408101.44   0.755131E+12 641554.11  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.654865E+11 0.254806E+11 0.148212E+12 0.553310E+11 0.438621E+11 0.303746E+10 0.00 0.552380E+09 0.00 0.00 0.264002E+11 0.770530E+10 0.00
February 0.590321E+11 0.212632E+11 0.133859E+12 0.499764E+11 0.395381E+11 0.262438E+10 0.00 0.472330E+09 0.00 0.00 0.239061E+11 0.696284E+10 0.00
March 0.651913E+11 0.211241E+11 0.148223E+12 0.553337E+11 0.436119E+11 0.621824E+10 0.00 0.992227E+10 0.00 0.00 0.242253E+11 0.770358E+10 0.00
April 0.627842E+11 0.180005E+11 0.143397E+12 0.535454E+11 0.431538E+11 0.818239E+10 0.00 0.100293E+11 0.00 0.00 0.208847E+11 0.746515E+10 0.00
May 0.647521E+11 0.164525E+11 0.148223E+12 0.553318E+11 0.471975E+11 0.120880E+11 0.00 0.452953E+11 0.00 0.00 0.110629E+11 0.770460E+10 0.00
June 0.625547E+11 0.148861E+11 0.143446E+12 0.535479E+11 0.495608E+11 0.130310E+11 0.00 0.135094E+12 0.00 0.00 0.846545E+10 0.745686E+10 0.00
July 0.645756E+11 0.157944E+11 0.148174E+12 0.553289E+11 0.538643E+11 0.141171E+11 0.00 0.222114E+12 0.00 0.00 0.104698E+11 0.771258E+10 0.00
August 0.648407E+11 0.176390E+11 0.148234E+12 0.553334E+11 0.531341E+11 0.137672E+11 0.00 0.176870E+12 0.00 0.00 0.909632E+10 0.770439E+10 0.00
September 0.629634E+11 0.193908E+11 0.143408E+12 0.535457E+11 0.483060E+11 0.124480E+11 0.00 0.937598E+11 0.00 0.00 0.730348E+10 0.746645E+10 0.00
October 0.653105E+11 0.225423E+11 0.148201E+12 0.553308E+11 0.465421E+11 0.888857E+10 0.00 0.176643E+11 0.00 0.00 0.177089E+11 0.770307E+10 0.00
November 0.634164E+11 0.239883E+11 0.143462E+12 0.535469E+11 0.434626E+11 0.633343E+10 0.00 0.554350E+10 0.00 0.00 0.224191E+11 0.744922E+10 0.00
December 0.654425E+11 0.260645E+11 0.148174E+12 0.553297E+11 0.444022E+11 0.377768E+10 0.00 0.828814E+09 0.00 0.00 0.264714E+11 0.771338E+10 0.00
                           
Annual Sum or Average 0.766350E+12 0.242626E+12 0.174501E+13 0.651482E+12 0.556635E+12 0.104513E+12 0.00 0.718146E+12 0.00 0.00 0.208414E+12 0.907474E+11 0.00
Minimum of Months 0.590321E+11 0.148861E+11 0.133859E+12 0.499764E+11 0.395381E+11 0.262438E+10 0.00 0.472330E+09 0.00 0.00 0.730348E+10 0.696284E+10 0.00
Maximum of Months 0.654865E+11 0.260645E+11 0.148234E+12 0.553337E+11 0.538643E+11 0.141171E+11 0.00 0.222114E+12 0.00 0.00 0.264714E+11 0.771338E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.306047E+12 0.00 0.297165E+12 0.00 0.00
February 0.137204E+12 0.00 0.287223E+12 0.00 0.270879E+12 0.00 0.00
March 0.152024E+12 0.00 0.140314E+12 0.00 0.297476E+12 0.00 0.00
April 0.146956E+12 0.00 0.601296E+11 0.00 0.279421E+12 0.00 0.00
May 0.151978E+12 0.00 0.301167E+11 0.00 0.277417E+12 0.00 0.00
June 0.147114E+12 0.00 0.775283E+10 0.00 0.257497E+12 0.00 0.00
July 0.151820E+12 0.00 0.630389E+09 0.00 0.257589E+12 0.00 0.00
August 0.152039E+12 0.00 0.176063E+10 0.00 0.254407E+12 0.00 0.00
September 0.146971E+12 0.00 0.134808E+11 0.00 0.248977E+12 0.00 0.00
October 0.151903E+12 0.00 0.616887E+11 0.00 0.265456E+12 0.00 0.00
November 0.147091E+12 0.00 0.956652E+11 0.00 0.267812E+12 0.00 0.00
December 0.151820E+12 0.00 0.282379E+12 0.00 0.288112E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.128719E+13 0.00 0.326221E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 0.630389E+09 0.00 0.248977E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.306047E+12 0.00 0.297476E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 62892.57 02-JAN-20:10 15448.40 01-JAN-00:10 89475.41 02-JAN-07:10 39726.11 02-JAN-07:19 23173.27 17-JAN-19:19 5412.07 12-JAN-10:30 0.00 01-JAN-00:10
February 62892.57 01-FEB-20:10 15448.40 01-FEB-00:10 89475.41 01-FEB-07:10 39726.11 01-FEB-07:19 24240.87 14-FEB-23:30 5449.25 08-FEB-16:30 0.00 01-FEB-00:10
March 62892.57 01-MAR-20:10 15448.40 01-MAR-00:10 89475.41 01-MAR-07:10 39726.11 13-MAR-06:19 34503.25 22-MAR-23:49 5444.79 07-MAR-09:09 0.00 01-MAR-00:10
April 62892.57 03-APR-19:10 15448.40 01-APR-00:10 89475.41 03-APR-06:10 39725.67 10-APR-06:19 31101.90 11-APR-20:19 5338.79 05-APR-14:09 0.00 01-APR-00:10
May 62892.57 01-MAY-19:10 15448.40 01-MAY-00:10 89475.41 01-MAY-06:10 39725.08 12-MAY-06:19 30985.45 06-MAY-21:00 5588.46 23-MAY-20:49 0.00 01-MAY-00:10
June 62892.57 01-JUN-19:40 15448.40 01-JUN-00:10 89475.41 01-JUN-06:10 39724.77 26-JUN-06:19 38759.22 13-JUN-23:49 7204.04 27-JUN-20:30 0.00 01-JUN-00:10
July 62892.57 03-JUL-19:40 15448.40 01-JUL-00:10 89475.41 03-JUL-06:10 39725.08 21-JUL-06:19 37198.81 21-JUL-21:10 7356.33 21-JUL-20:19 0.00 01-JUL-00:10
August 62892.57 01-AUG-19:30 15448.40 01-AUG-00:10 89475.41 01-AUG-06:10 39725.67 28-AUG-06:19 37833.67 18-AUG-21:10 6594.26 26-AUG-18:10 0.00 01-AUG-00:10
September 62892.57 01-SEP-19:10 15448.40 01-SEP-00:10 89475.41 01-SEP-06:10 39726.11 18-SEP-06:19 40814.17 04-SEP-05:49 6604.68 15-SEP-20:30 0.00 01-SEP-00:10
October 62892.57 02-OCT-19:10 15448.40 01-OCT-00:10 89475.41 02-OCT-06:10 39726.11 02-OCT-06:19 34925.19 26-OCT-22:49 5420.02 11-OCT-15:30 0.00 01-OCT-00:10
November 62892.57 01-NOV-19:10 15448.40 01-NOV-00:10 89475.41 01-NOV-06:10 39726.11 01-NOV-06:19 36661.15 27-NOV-22:49 5458.78 01-NOV-08:50 0.00 01-NOV-00:10
December 62892.57 01-DEC-20:10 15448.40 01-DEC-00:10 89475.41 01-DEC-07:10 39726.11 01-DEC-07:19 28160.91 01-DEC-19:40 5501.15 11-DEC-16:30 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 62892.57   15448.40   89475.41   39724.77   23173.27   5338.79   0.00  
Maximum of Months 62892.57   15448.40   89475.41   39726.11   40814.17   7356.33   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 4446.38 15-JAN-16:10 0.00 0.00 9938.94 01-JAN-00:10 4738.29 03-JAN-07:19 0.00
February 5131.03 28-FEB-16:19 0.00 0.00 9938.94 01-FEB-00:20 4738.49 06-FEB-19:10 0.00
March 89029.78 15-MAR-15:09 0.00 0.00 9938.94 01-MAR-00:20 4738.50 31-MAR-06:49 0.00
April 54774.55 08-APR-12:00 0.00 0.00 9938.94 01-APR-00:10 4738.60 19-APR-18:10 0.00
May 96340.74 10-MAY-15:09 0.00 0.00 9938.94 01-MAY-00:10 4738.43 31-MAY-18:10 0.00
June 162157.45 27-JUN-20:30 0.00 0.00 9938.94 01-JUN-13:00 4738.13 12-JUN-06:10 0.00
July 168402.56 21-JUL-20:30 0.00 0.00 9938.94 01-JUL-13:39 4738.33 10-JUL-06:10 0.00
August 157998.71 13-AUG-15:20 0.00 0.00 9938.94 01-AUG-03:49 4738.11 21-AUG-06:10 0.00
September 137845.06 15-SEP-20:30 0.00 0.00 9938.94 01-SEP-23:19 4738.37 11-SEP-18:10 0.00
October 78928.43 11-OCT-15:09 0.00 0.00 9938.94 01-OCT-00:10 4738.64 30-OCT-18:10 0.00
November 38054.37 16-NOV-12:30 0.00 0.00 9938.94 01-NOV-00:10 4738.23 02-NOV-18:00 0.00
December 3934.63 15-DEC-19:10 0.00 0.00 9938.94 01-DEC-00:20 4738.40 18-DEC-19:10 0.00
                   
Annual Sum or Average     0.00 0.00         0.00
Minimum of Months 3934.63   0.00 0.00 9938.94   4738.11   0.00
Maximum of Months 168402.56   0.00 0.00 9938.94   4738.64   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 242827.03 19-JAN-20:00 62892.57 88772.42 15448.40 32159.77 20727.19 5165.20 0.00 1358.35 0.00
February 242931.22 22-FEB-20:40 62892.57 88772.42 15448.40 32159.77 20903.57 4954.98 0.00 1456.06 0.00
March 305201.83 15-MAR-19:49 62892.57 88772.42 15448.40 32159.77 24923.91 5280.21 0.00 69421.86 0.00
April 261165.19 07-APR-19:00 62892.57 88772.42 15448.40 32159.77 21557.83 4831.97 0.00 30102.10 0.00
May 306848.60 23-MAY-19:40 62892.57 88772.42 15448.40 32159.77 25094.98 5122.42 0.00 71695.83 0.00
June 402484.01 27-JUN-19:00 62892.57 88772.42 15448.40 32159.77 29592.16 6822.82 0.00 151303.69 0.00
July 408101.44 20-JUL-19:49 62892.57 88772.42 15448.40 32159.77 30508.13 6481.89 0.00 155497.22 0.00
August 380415.75 14-AUG-19:30 62892.57 88772.42 15448.40 32159.77 29184.07 6109.29 0.00 129415.92 0.00
September 376256.76 15-SEP-19:00 62892.57 88772.42 15448.40 32159.77 28429.57 6513.06 0.00 134680.23 0.00
October 274579.26 11-OCT-18:10 55920.94 79417.81 15448.40 31837.63 23164.52 5196.68 0.00 56546.76 0.00
November 250328.24 06-NOV-20:19 62892.57 88772.42 15448.40 32159.77 27420.09 5033.70 0.00 2388.28 0.00
December 245831.08 13-DEC-20:00 62892.57 88772.42 15448.40 32159.77 26802.51 2888.99 0.00 999.67 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 242827.03   55920.94 79417.81 15448.40 31837.63 20727.19 2888.99 0.00 999.67 0.00
Maximum of Months 408101.44   62892.57 88772.42 15448.40 32159.77 30508.13 6822.82 0.00 155497.22 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 284466.19 31-JAN-09:09 0.00 296575.86 31-JAN-21:19 0.00
February 104248.32 01-FEB-18:10 0.00 351311.48 06-FEB-09:09 0.00 297088.91 15-FEB-21:49 0.00
March 104248.32 01-MAR-18:10 0.00 215157.96 07-MAR-09:09 0.00 299708.18 16-MAR-17:49 0.00
April 104248.32 01-APR-17:10 0.00 144828.35 16-APR-08:09 0.00 293236.21 11-APR-20:40 0.00
May 104248.32 01-MAY-17:10 0.00 109338.04 02-MAY-00:40 0.00 284637.64 02-MAY-20:19 0.00
June 104248.32 01-JUN-17:10 0.00 170139.83 13-JUN-23:49 0.00 256039.83 02-JUN-20:30 0.00
July 104248.32 01-JUL-17:10 0.00 36366.00 03-JUL-05:10 0.00 246797.49 03-JUL-20:40 0.00
August 104248.32 01-AUG-17:10 0.00 52157.69 03-AUG-04:00 0.00 245833.35 02-AUG-20:40 0.00
September 104248.32 01-SEP-17:10 0.00 132785.44 04-SEP-05:49 0.00 246757.19 29-SEP-20:30 0.00
October 104248.32 02-OCT-17:10 0.00 168333.64 19-OCT-04:40 0.00 257750.19 13-OCT-20:30 0.00
November 104248.32 01-NOV-17:10 0.00 172491.66 13-NOV-16:00 0.00 284074.29 29-NOV-21:30 0.00
December 104248.32 01-DEC-18:10 0.00 322095.67 11-DEC-09:09 0.00 291726.85 28-DEC-21:49 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 36366.00   0.00 245833.35   0.00
Maximum of Months 104248.32   0.00 351311.48   0.00 299708.18   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 2.00 24.93 2.00 24.93
February 0.00 0.00 0.00 0.00 1.83 24.76 1.83 24.76
March 0.00 0.00 0.00 0.00 18.50 25.15 18.50 25.15
April 0.00 0.00 0.00 0.00 29.67 25.01 29.67 25.01
May 0.00 0.00 0.00 0.00 11.33 24.91 11.33 24.91
June 0.00 0.00 0.00 0.00 3.17 24.81 3.17 24.81
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 4.33 24.95 4.33 24.95
October 0.00 0.00 0.00 0.00 27.67 25.02 27.67 25.02
November 0.00 0.00 0.00 0.00 33.33 25.00 33.33 25.00
December 0.00 0.00 0.00 0.00 4.17 25.25 4.17 25.25
                 
Annual Sum or Average 0.00   0.00   136.00 25.01 136.00 25.01
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 33.33 25.25 33.33 25.25



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 24.59 0.17 24.59
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.17 24.59 0.17 24.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 24.59 0.17 24.59



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.76 0.17 21.76
May 0.00 0.00 0.00 0.00 0.33 21.69 0.33 21.69
June 0.00 0.00 0.00 0.00 0.83 21.77 0.83 21.77
July 0.00 0.00 0.00 0.00 0.50 21.83 0.50 21.83
August 0.00 0.00 0.00 0.00 2.33 21.75 2.33 21.75
September 0.00 0.00 0.00 0.00 1.17 21.87 1.17 21.87
October 0.00 0.00 0.00 0.00 0.17 21.67 0.17 21.67
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   5.50 21.78 5.50 21.78
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.33 21.87 2.33 21.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
June 0.00 0.00 0.00 0.00 0.83 21.78 0.83 21.78
July 0.00 0.00 0.00 0.00 0.83 21.77 0.83 21.77
August 0.00 0.00 0.00 0.00 0.33 21.71 0.33 21.71
September 0.00 0.00 0.00 0.00 0.17 21.67 0.17 21.67
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.33 21.75 2.33 21.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.83 21.78 0.83 21.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 20.55 0.17 20.55 0.00 20.55 0.00 20.55
February 0.17 20.53 0.17 20.53 0.00 20.53 0.00 20.53
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.67 21.72 0.67 21.72
July 0.00 0.00 0.00 0.00 1.33 21.72 1.33 21.72
August 0.00 0.00 0.00 0.00 0.67 21.67 0.67 21.67
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 20.53 0.17 20.53 0.00 20.53 0.00 20.53
                 
Annual Sum or Average 0.50 20.54 0.50 20.54 2.67 21.39 2.67 21.52
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 20.55 0.17 20.55 1.33 21.72 1.33 21.72



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.50 21.74 0.50 21.74
June 0.00 0.00 0.00 0.00 1.00 21.73 1.00 21.73
July 0.00 0.00 0.00 0.00 0.67 21.70 0.67 21.70
August 0.00 0.00 0.00 0.00 0.50 21.71 0.50 21.71
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.67 21.72 2.67 21.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.00 21.74 1.00 21.74



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.50 21.77 0.50 21.77
June 0.00 0.00 0.00 0.00 1.00 21.78 1.00 21.78
July 0.00 0.00 0.00 0.00 0.83 21.74 0.83 21.74
August 0.00 0.00 0.00 0.00 0.50 21.73 0.50 21.73
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.83 21.76 2.83 21.76
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.00 21.78 1.00 21.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.80 0.17 21.80
May 0.00 0.00 0.00 0.00 0.33 21.69 0.33 21.69
June 0.00 0.00 0.00 0.00 1.50 21.77 1.50 21.77
July 0.00 0.00 0.00 0.00 1.67 21.75 1.67 21.75
August 0.00 0.00 0.00 0.00 3.17 21.80 3.17 21.80
September 0.00 0.00 0.00 0.00 1.50 21.87 1.50 21.87
October 0.00 0.00 0.00 0.00 0.17 21.70 0.17 21.70
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   8.50 21.79 8.50 21.79
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.17 21.87 3.17 21.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 21.72 0.17 21.72
June 0.00 0.00 0.00 0.00 1.33 21.78 1.33 21.78
July 0.00 0.00 0.00 0.00 1.17 21.81 1.17 21.81
August 0.00 0.00 0.00 0.00 1.00 21.73 1.00 21.73
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.67 21.77 3.67 21.77
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.33 21.81 1.33 21.81



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.78 0.17 21.78
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 21.72 0.17 21.72
July 0.00 0.00 0.00 0.00 0.17 21.73 0.17 21.73
August 0.00 0.00 0.00 0.00 2.83 21.78 2.83 21.78
September 0.00 0.00 0.00 0.00 3.00 21.94 3.00 21.94
October 0.00 0.00 0.00 0.00 1.17 21.88 1.17 21.88
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   7.50 21.86 7.50 21.86
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.00 21.94 3.00 21.94



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 25.15 0.17 25.15
February 0.00 0.00 0.00 0.00 0.17 24.69 0.17 24.69
March 0.00 0.00 0.00 0.00 1.00 24.70 1.00 24.70
April 0.00 0.00 0.00 0.00 3.00 24.76 3.00 24.76
May 0.00 0.00 0.00 0.00 4.33 24.74 4.33 24.74
June 0.00 0.00 0.00 0.00 1.83 24.85 1.83 24.85
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 2.33 24.73 2.33 24.73
October 0.00 0.00 0.00 0.00 4.17 24.71 4.17 24.71
November 0.00 0.00 0.00 0.00 1.67 24.75 1.67 24.75
December 0.00 0.00 0.00 0.00 0.17 24.56 0.17 24.56
                 
Annual Sum or Average 0.00   0.00   18.83 24.75 18.83 24.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 4.33 25.15 4.33 25.15



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 25.26 0.17 25.26
February 0.00 0.00 0.00 0.00 0.83 24.62 0.83 24.62
March 0.00 0.00 0.00 0.00 1.50 24.73 1.50 24.73
April 0.00 0.00 0.00 0.00 4.17 24.79 4.17 24.79
May 0.00 0.00 0.00 0.00 6.33 24.72 6.33 24.72
June 0.00 0.00 0.00 0.00 2.17 24.84 2.17 24.84
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 2.83 24.75 2.83 24.75
October 0.00 0.00 0.00 0.00 5.83 24.74 5.83 24.74
November 0.00 0.00 0.00 0.00 2.83 24.75 2.83 24.75
December 0.00 0.00 0.00 0.00 0.17 24.61 0.17 24.61
                 
Annual Sum or Average 0.00   0.00   26.83 24.75 26.83 24.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.33 25.26 6.33 25.26



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 3.00 25.13 3.00 25.13
February 0.00 0.00 0.00 0.00 1.83 24.93 1.83 24.93
March 0.00 0.00 0.00 0.00 25.17 25.09 25.17 25.09
April 0.00 0.00 0.00 0.00 45.33 25.09 45.33 25.09
May 0.00 0.00 0.00 0.00 25.00 25.05 25.00 25.05
June 0.00 0.00 0.00 0.00 9.17 25.03 9.17 25.03
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 9.83 25.05 9.83 25.05
October 0.00 0.00 0.00 0.00 54.67 25.14 54.67 25.14
November 0.00 0.00 0.00 0.00 41.83 25.09 41.83 25.09
December 0.00 0.00 0.00 0.00 4.67 25.10 4.67 25.10
                 
Annual Sum or Average 0.00   0.00   220.50 25.10 220.50 25.10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 54.67 25.14 54.67 25.14



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 23.37 0.00 23.37 0.00 23.37
February 672.00 23.13 0.00 23.13 0.00 23.13
March 744.00 22.62 0.00 22.62 0.00 22.62
April 720.00 22.49 0.00 22.49 0.00 22.49
May 744.00 22.41 0.00 22.41 0.00 22.41
June 717.17 22.81 0.00 22.81 0.00 22.81
July 586.33 23.04 4.17 23.05 0.00 23.05
August 273.50 23.29 201.50 23.53 0.00 23.53
September 137.17 23.57 206.67 23.80 0.50 23.81
October 228.33 23.78 33.67 23.81 0.00 23.81
November 430.50 23.85 0.00 23.85 0.00 23.85
December 703.50 23.73 0.00 23.73 0.00 23.73
             
Annual Sum or Average 6700.50 23.06 446.00 23.11 0.50 23.11
Minimum of Months 137.17 22.41 0.00 22.41 0.00 22.41
Maximum of Months 744.00 23.85 206.67 23.85 0.50 23.85



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 741.50 21.04 597.83 21.02 597.83 21.02
February 669.50 21.05 499.67 21.03 499.67 21.02
March 718.00 21.21 201.83 21.19 194.00 21.15
April 685.50 21.27 26.33 21.26 24.50 21.25
May 688.83 21.48 10.83 21.51 0.00 21.51
June 536.00 21.90 103.67 22.16 0.00 22.16
July 365.00 22.16 265.83 22.76 0.00 22.76
August 415.33 22.05 235.83 22.64 0.00 22.64
September 540.50 21.72 124.00 22.11 0.00 22.11
October 679.50 21.29 53.67 21.45 10.00 21.44
November 703.17 21.12 142.50 21.11 139.67 21.10
December 739.67 21.04 550.00 21.02 550.00 21.02
             
Annual Sum or Average 7482.50 21.37 2812.00 21.48 2015.67 21.40
Minimum of Months 365.00 21.04 10.83 21.02 0.00 21.02
Maximum of Months 741.50 22.16 597.83 22.76 597.83 22.76



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.27 100.50 21.24 100.50 21.21
February 672.00 21.27 54.67 21.25 54.67 21.23
March 730.83 21.88 1.83 21.89 0.00 21.89
April 719.67 22.37 0.00 22.37 0.00 22.37
May 680.83 22.80 2.83 22.81 0.00 22.81
June 398.50 23.08 205.83 23.34 50.83 23.37
July 204.17 23.41 438.00 23.70 101.17 23.72
August 225.33 23.23 349.50 23.61 69.50 23.63
September 458.00 22.99 131.83 23.17 38.50 23.19
October 707.67 22.53 4.50 22.53 0.00 22.53
November 720.00 22.04 0.00 22.04 0.00 22.04
December 744.00 21.33 69.33 21.30 69.33 21.28
             
Annual Sum or Average 7005.00 22.15 1358.83 22.35 484.50 22.35
Minimum of Months 204.17 21.27 0.00 21.24 0.00 21.21
Maximum of Months 744.00 23.41 438.00 23.70 101.17 23.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.01 408.83 21.01 408.83 21.00
February 672.00 21.01 371.33 21.00 371.33 21.00
March 744.00 21.25 169.33 21.20 169.33 21.17
April 720.00 21.48 4.00 21.48 4.00 21.47
May 744.00 22.26 0.00 22.26 0.00 22.26
June 581.17 22.93 26.83 22.98 0.00 22.98
July 268.17 23.18 191.67 23.47 0.00 23.47
August 410.50 23.20 87.67 23.33 0.00 23.33
September 661.83 22.78 7.17 22.79 0.00 22.79
October 744.00 21.84 0.00 21.84 0.00 21.84
November 720.00 21.28 0.00 21.28 0.00 21.28
December 744.00 21.02 268.50 21.01 268.50 21.01
             
Annual Sum or Average 7753.67 21.79 1535.33 21.76 1222.00 21.67
Minimum of Months 268.17 21.01 0.00 21.00 0.00 21.00
Maximum of Months 744.00 23.20 408.83 23.47 408.83 23.47



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 478.83 21.00 478.83 21.00
February 672.00 21.00 459.50 21.00 459.50 21.00
March 744.00 21.15 237.17 21.11 237.17 21.09
April 720.00 21.29 13.00 21.29 13.00 21.28
May 744.00 22.04 0.00 22.04 0.00 22.04
June 685.50 22.83 0.00 22.83 0.00 22.83
July 434.33 23.16 61.50 23.24 0.00 23.24
August 578.50 23.15 8.33 23.16 0.00 23.16
September 703.83 22.62 0.00 22.62 0.00 22.62
October 744.00 21.60 0.00 21.60 0.00 21.60
November 720.00 21.13 7.33 21.13 7.33 21.13
December 744.00 21.00 327.50 21.00 327.50 21.00
             
Annual Sum or Average 8234.17 21.75 1593.17 21.65 1523.33 21.56
Minimum of Months 434.33 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 23.16 478.83 23.24 478.83 23.24



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 308.00 22.49 362.50 23.17 125.17 23.30
February 272.83 22.46 318.67 23.16 111.50 23.30
March 273.50 23.02 473.67 23.37 167.50 23.52
April 267.83 23.35 573.33 23.41 192.33 23.56
May 283.67 23.70 648.00 23.43 250.33 23.56
June 288.00 23.94 683.17 23.39 282.83 23.52
July 317.67 23.96 730.50 23.35 317.50 23.49
August 309.00 23.97 717.00 23.37 308.33 23.51
September 290.33 23.89 667.33 23.42 278.83 23.55
October 273.67 23.57 616.00 23.48 221.00 23.61
November 245.67 23.26 523.33 23.45 165.67 23.59
December 306.17 22.54 387.83 23.18 129.00 23.32
             
Annual Sum or Average 3436.33 23.35 6701.33 23.36 2550.00 23.50
Minimum of Months 245.67 22.46 318.67 23.16 111.50 23.30
Maximum of Months 317.67 23.97 730.50 23.48 317.50 23.61



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 736.83 21.26 221.17 21.21 218.50 21.17
February 661.83 21.25 168.50 21.21 165.50 21.18
March 652.33 21.84 56.00 21.96 9.67 21.96
April 626.83 22.18 37.17 22.28 0.00 22.28
May 527.67 22.55 101.50 22.71 15.00 22.73
June 327.33 23.08 403.33 23.37 134.67 23.44
July 281.00 23.64 655.67 23.64 250.67 23.67
August 220.33 23.35 590.83 23.62 149.50 23.66
September 308.50 22.83 402.50 23.33 104.17 23.37
October 562.33 22.20 123.83 22.49 8.17 22.51
November 678.83 21.88 20.50 21.94 0.33 21.94
December 732.67 21.27 197.50 21.23 192.33 21.19
             
Annual Sum or Average 6316.50 22.02 2978.50 22.38 1248.50 22.40
Minimum of Months 220.33 21.25 20.50 21.21 0.00 21.17
Maximum of Months 736.83 23.64 655.67 23.64 250.67 23.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.76 5.67 21.75 5.67 21.75
February 672.00 21.75 13.83 21.73 13.83 21.72
March 691.33 22.41 31.50 22.47 3.50 22.48
April 641.00 22.77 1.83 22.77 0.00 22.77
May 451.17 22.97 83.50 23.11 14.83 23.12
June 276.17 23.41 360.00 23.66 119.67 23.71
July 249.83 23.90 636.50 23.83 231.00 23.86
August 170.00 23.71 590.17 23.81 128.67 23.84
September 222.17 23.35 362.50 23.67 95.83 23.71
October 524.00 22.86 79.33 23.00 5.50 23.01
November 695.67 22.58 0.00 22.58 0.00 22.58
December 744.00 21.81 1.17 21.81 1.17 21.81
             
Annual Sum or Average 6081.33 22.50 2166.00 22.84 619.67 22.91
Minimum of Months 170.00 21.75 0.00 21.73 0.00 21.72
Maximum of Months 744.00 23.90 636.50 23.83 231.00 23.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.54 734.00 20.54 734.00 20.54
February 672.00 20.58 657.17 20.57 657.17 20.56
March 740.83 20.97 404.17 20.89 404.17 20.84
April 719.00 21.24 123.17 21.17 123.17 21.11
May 718.83 21.47 1.17 21.47 0.00 21.47
June 632.00 21.45 21.33 21.51 1.00 21.51
July 604.67 21.34 41.33 21.47 1.50 21.47
August 624.33 21.38 35.50 21.48 0.33 21.48
September 660.67 21.45 7.00 21.47 0.17 21.47
October 737.67 21.20 124.33 21.14 124.00 21.09
November 720.00 20.86 428.67 20.78 428.67 20.74
December 744.00 20.55 724.17 20.55 724.17 20.54
             
Annual Sum or Average 8318.00 21.07 3302.00 20.96 3198.33 20.88
Minimum of Months 604.67 20.54 1.17 20.54 0.00 20.54
Maximum of Months 744.00 21.47 734.00 21.51 734.00 21.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.49 742.50 20.49 742.50 20.49
February 672.00 20.50 668.33 20.50 668.33 20.50
March 744.00 20.76 491.83 20.68 491.83 20.65
April 720.00 21.09 171.83 21.00 171.83 20.94
May 731.50 21.42 0.00 21.42 0.00 21.42
June 649.33 21.47 15.17 21.51 1.00 21.51
July 629.00 21.41 24.83 21.48 1.17 21.48
August 660.17 21.46 16.50 21.50 0.33 21.50
September 699.50 21.46 0.33 21.46 0.17 21.46
October 743.50 21.01 210.83 20.92 210.83 20.87
November 720.00 20.69 537.50 20.64 537.50 20.62
December 744.00 20.50 740.00 20.50 740.00 20.49
             
Annual Sum or Average 8457.00 21.01 3619.67 20.88 3565.50 20.80
Minimum of Months 629.00 20.49 0.00 20.49 0.00 20.49
Maximum of Months 744.00 21.47 742.50 21.51 742.50 21.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.67 686.17 20.65 686.17 20.64
February 672.00 20.69 623.67 20.67 623.67 20.67
March 744.00 20.90 439.67 20.84 439.67 20.81
April 720.00 21.12 64.00 21.09 64.00 21.07
May 744.00 21.31 0.00 21.31 0.00 21.31
June 720.00 21.45 1.67 21.46 1.67 21.46
July 744.00 21.53 4.50 21.53 4.50 21.54
August 744.00 21.48 2.00 21.48 2.00 21.48
September 720.00 21.33 0.33 21.33 0.33 21.33
October 744.00 21.10 41.83 21.08 41.83 21.05
November 720.00 20.93 275.83 20.87 275.83 20.83
December 744.00 20.70 601.00 20.66 601.00 20.64
             
Annual Sum or Average 8760.00 21.10 2740.67 21.00 2740.67 20.93
Minimum of Months 672.00 20.67 0.00 20.65 0.00 20.64
Maximum of Months 744.00 21.53 686.17 21.53 686.17 21.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.55 726.00 20.54 726.00 20.54
February 672.00 20.59 647.00 20.58 647.00 20.58
March 739.17 21.02 380.67 20.94 380.67 20.90
April 719.83 21.34 110.00 21.27 110.00 21.22
May 721.50 21.55 0.00 21.55 0.00 21.55
June 617.83 21.45 5.00 21.46 0.50 21.46
July 578.00 21.28 15.17 21.33 1.17 21.34
August 605.17 21.35 14.50 21.40 0.50 21.40
September 640.50 21.43 0.83 21.44 0.17 21.44
October 739.33 21.27 112.83 21.21 112.83 21.16
November 720.00 20.87 428.33 20.78 428.33 20.74
December 744.00 20.55 723.00 20.54 723.00 20.54
             
Annual Sum or Average 8241.33 21.09 3163.33 20.96 3130.17 20.89
Minimum of Months 578.00 20.55 0.00 20.54 0.00 20.54
Maximum of Months 744.00 21.55 726.00 21.55 726.00 21.55



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.49 741.33 20.49 741.33 20.49
February 672.00 20.50 668.00 20.50 668.00 20.50
March 744.00 20.81 477.83 20.73 477.83 20.69
April 720.00 21.22 148.50 21.14 148.50 21.09
May 741.33 21.56 0.00 21.56 0.00 21.56
June 641.50 21.51 4.50 21.52 0.50 21.52
July 584.83 21.30 8.83 21.33 0.83 21.34
August 623.83 21.40 3.83 21.41 0.50 21.41
September 703.50 21.56 0.67 21.56 0.33 21.56
October 744.00 21.09 177.17 21.02 177.17 20.98
November 720.00 20.70 525.17 20.65 525.17 20.63
December 744.00 20.50 736.17 20.50 736.17 20.49
             
Annual Sum or Average 8383.00 21.04 3492.00 20.90 3476.33 20.82
Minimum of Months 584.83 20.49 0.00 20.49 0.00 20.49
Maximum of Months 744.00 21.56 741.33 21.56 741.33 21.56



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 410.50 21.00 410.50 21.00
February 672.00 21.00 337.17 21.00 337.17 21.00
March 744.00 21.17 114.83 21.15 114.83 21.13
April 720.00 21.51 0.00 21.51 0.00 21.51
May 744.00 22.33 0.00 22.33 0.00 22.33
June 634.83 23.07 55.17 23.10 42.17 23.11
July 314.33 23.43 213.50 23.57 100.83 23.58
August 443.83 23.32 131.00 23.40 68.83 23.41
September 710.00 22.86 32.17 22.87 32.17 22.87
October 744.00 21.62 0.00 21.62 0.00 21.62
November 720.00 21.12 2.33 21.12 2.33 21.11
December 744.00 21.00 280.83 21.00 280.83 21.00
             
Annual Sum or Average 7935.00 21.81 1577.50 21.80 1389.67 21.75
Minimum of Months 314.33 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 23.43 410.50 23.57 410.50 23.58



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.50 739.83 20.50 739.83 20.50
February 672.00 20.53 661.50 20.52 661.50 20.52
March 739.67 20.86 505.67 20.79 505.67 20.75
April 716.83 21.16 219.17 21.06 219.17 20.99
May 711.33 21.42 8.67 21.42 5.17 21.42
June 620.00 21.40 39.00 21.50 6.17 21.50
July 595.83 21.30 71.33 21.51 7.17 21.52
August 614.67 21.33 54.50 21.49 5.17 21.49
September 652.00 21.39 27.67 21.42 15.83 21.41
October 736.17 21.10 222.17 21.01 221.00 20.94
November 720.00 20.77 527.17 20.71 527.17 20.68
December 744.00 20.52 735.33 20.51 735.33 20.51
             
Annual Sum or Average 8266.50 21.01 3812.00 20.91 3649.17 20.83
Minimum of Months 595.83 20.50 8.67 20.50 5.17 20.50
Maximum of Months 744.00 21.42 739.83 21.51 739.83 21.52



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.48 744.00 20.48 744.00 20.48
February 672.00 20.48 670.67 20.48 670.67 20.48
March 744.00 20.69 575.67 20.63 575.67 20.60
April 720.00 21.02 295.83 20.91 295.83 20.85
May 726.50 21.38 10.50 21.38 9.33 21.37
June 638.83 21.43 29.17 21.50 6.00 21.50
July 615.17 21.36 46.83 21.49 6.33 21.50
August 645.67 21.40 34.17 21.48 7.00 21.49
September 693.17 21.40 24.67 21.39 23.67 21.38
October 743.50 20.90 310.67 20.80 310.67 20.74
November 720.00 20.61 606.00 20.58 606.00 20.57
December 744.00 20.48 741.67 20.48 741.67 20.48
             
Annual Sum or Average 8406.83 20.95 4089.83 20.84 3996.83 20.76
Minimum of Months 615.17 20.48 10.50 20.48 6.00 20.48
Maximum of Months 744.00 21.43 744.00 21.50 744.00 21.50



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.80 658.33 20.73 658.33 20.71
February 672.00 20.79 597.83 20.73 597.83 20.71
March 736.33 21.22 305.33 21.12 304.67 21.06
April 713.17 21.33 107.17 21.26 107.17 21.21
May 718.83 21.48 0.17 21.48 0.17 21.48
June 649.50 21.46 4.50 21.46 4.50 21.47
July 625.00 21.38 14.00 21.41 8.33 21.42
August 632.17 21.38 25.50 21.45 4.00 21.46
September 626.50 21.38 21.33 21.44 1.67 21.44
October 706.33 21.28 80.33 21.27 71.50 21.24
November 718.17 21.09 319.33 20.96 319.33 20.90
December 744.00 20.74 660.17 20.68 660.17 20.66
             
Annual Sum or Average 8286.00 21.18 2794.00 21.08 2737.67 21.00
Minimum of Months 625.00 20.74 0.17 20.68 0.17 20.66
Maximum of Months 744.00 21.48 660.17 21.48 660.17 21.48



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 673.17 22.98 0.00 22.98 0.00 22.98
February 611.83 22.99 0.17 23.00 0.00 23.00
March 460.00 23.17 120.67 23.34 2.17 23.34
April 202.33 23.16 153.17 23.53 0.00 23.53
May 60.67 23.45 466.33 23.92 16.50 23.92
June 123.17 23.98 666.33 23.98 120.33 23.98
July 231.33 24.00 743.50 23.98 231.33 23.98
August 136.33 24.00 740.33 23.97 136.33 23.97
September 110.50 23.93 639.50 23.95 102.33 23.95
October 192.50 23.17 272.33 23.66 12.33 23.67
November 345.00 23.11 55.83 23.23 0.00 23.23
December 619.17 22.96 1.00 22.96 0.00 22.96
             
Annual Sum or Average 3766.00 23.20 3859.17 23.59 621.33 23.62
Minimum of Months 60.67 22.96 0.00 22.96 0.00 22.96
Maximum of Months 673.17 24.00 743.50 23.98 231.33 23.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 543.50 23.11 5.67 23.12 0.00 23.12
February 485.50 23.12 5.50 23.13 0.00 23.13
March 298.00 23.21 194.00 23.51 0.83 23.52
April 74.17 23.19 321.67 23.87 0.00 23.87
May 14.83 23.92 579.00 23.99 13.00 23.99
June 109.50 23.99 706.17 23.99 109.33 23.99
July 215.33 24.00 744.00 23.99 215.33 23.99
August 122.67 24.00 744.00 23.98 122.67 23.99
September 93.00 24.00 696.17 23.97 93.00 23.98
October 77.00 23.24 401.83 23.87 6.17 23.88
November 201.17 23.17 167.50 23.55 0.00 23.55
December 458.33 23.03 25.83 23.08 0.00 23.08
             
Annual Sum or Average 2693.00 23.30 4591.33 23.74 560.33 23.75
Minimum of Months 14.83 23.03 5.50 23.08 0.00 23.08
Maximum of Months 543.50 24.00 744.00 23.99 215.33 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 520.83 23.59 579.67 23.79 408.50 23.84
February 481.33 23.58 522.83 23.78 378.17 23.84
March 544.33 23.87 638.67 23.94 485.83 23.98
April 508.00 24.12 670.33 24.05 502.83 24.07
May 543.67 24.05 737.67 23.98 543.67 24.00
June 552.83 24.01 719.50 23.98 552.83 23.99
July 593.00 23.99 744.00 23.97 593.00 23.98
August 578.83 23.99 744.00 23.96 578.83 23.97
September 536.17 24.02 719.83 23.96 536.17 23.98
October 527.83 24.14 708.00 24.05 526.17 24.08
November 500.67 24.07 641.33 24.03 483.33 24.06
December 510.67 23.67 594.83 23.82 420.00 23.87
             
Annual Sum or Average 6398.17 23.93 8020.67 23.95 6009.33 23.98
Minimum of Months 481.33 23.58 522.83 23.78 378.17 23.84
Maximum of Months 593.00 24.14 744.00 24.05 593.00 24.08



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 457.33 21.00 457.33 21.00
February 672.00 21.00 417.17 21.00 417.17 21.00
March 744.00 21.18 150.17 21.15 150.17 21.13
April 720.00 21.47 0.00 21.47 0.00 21.47
May 742.33 22.27 0.00 22.27 0.00 22.27
June 437.00 22.86 110.33 23.06 0.00 23.06
July 118.83 23.08 424.33 23.69 0.00 23.69
August 288.33 23.02 250.67 23.42 0.00 23.42
September 635.67 22.62 18.17 22.65 0.00 22.65
October 744.00 21.53 0.00 21.53 0.00 21.53
November 720.00 21.11 2.33 21.11 2.33 21.11
December 744.00 21.00 324.83 21.00 324.83 21.00
             
Annual Sum or Average 7310.17 21.63 2155.33 21.73 1351.83 21.63
Minimum of Months 118.83 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 23.08 457.33 23.69 457.33 23.69



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.37170 23.09588 0.06251 5.23873
February 672.00000 23.13398 23.52396 0.00471 5.17562
March 744.00000 22.61709 31.39237 -0.0754 5.35931
April 720.00000 22.49138 35.08416 -0.0849 5.35481
May 744.00000 22.40708 41.05936 -1.1388 32.52258
June 720.00000 22.81493 51.69695 -0.9188 23.14897
July 744.00000 23.16075 58.67480 -0.7431 16.88479
August 744.00000 23.60276 54.21242 -0.6074 12.97440
September 720.00000 23.83028 48.61578 -0.5565 11.68921
October 744.00000 23.91249 37.09911 0.31105 7.09856
November 720.00000 23.90382 30.94687 0.26321 6.50340
December 744.00000 23.74492 25.61747 0.17988 5.79551
           
Annual Sum or Average 8760.00000 23.25009 38.50597 -0.2771 11.52849
Minimum of Months 672.00000 22.40708 23.09588 -1.1388 5.17562
Maximum of Months 744.00000 23.91249 58.67480 0.31105 32.52258



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.05241 23.77473 -0.5981 12.92141
February 672.00000 21.06161 24.00791 -0.5868 12.70084
March 744.00000 21.29308 31.72674 -0.3748 9.26375
April 720.00000 21.37777 35.55047 -0.2951 7.88907
May 744.00000 21.61816 41.28787 -1.2523 39.23015
June 720.00000 22.25345 51.77121 -0.9134 24.80315
July 744.00000 22.77593 58.91996 -0.6570 15.92701
August 744.00000 22.68669 55.80160 -0.7092 18.09052
September 720.00000 22.18262 52.03702 -0.9411 26.95687
October 744.00000 21.50927 40.87267 -0.2125 7.62444
November 720.00000 21.18462 34.22647 -0.4045 9.22398
December 744.00000 21.05636 27.44009 -0.5799 12.50112
           
Annual Sum or Average 8760.00000 21.67514 39.87482 -0.6273 16.44966
Minimum of Months 672.00000 21.05241 23.77473 -1.2523 7.62444
Maximum of Months 744.00000 22.77593 58.91996 -0.2125 39.23015



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.27220 25.83571 -0.4260 9.04902
February 672.00000 21.26836 26.06682 -0.4256 9.04534
March 744.00000 21.91393 32.83685 -0.2040 6.75600
April 720.00000 22.36973 35.95489 -0.0686 5.63925
May 744.00000 22.88431 40.83301 -0.9054 22.95585
June 720.00000 23.35541 50.95494 -0.6535 14.71790
July 744.00000 23.58259 58.24534 -0.5119 10.85803
August 744.00000 23.55009 55.21309 -0.5461 11.68117
September 720.00000 23.25213 51.21910 -0.6938 15.82745
October 744.00000 22.58716 40.83591 0.02029 5.58634
November 720.00000 22.03996 34.98300 -0.1628 6.03206
December 744.00000 21.33007 29.33828 -0.3901 8.49907
           
Annual Sum or Average 8760.00000 22.45688 40.27538 -0.4141 10.56635
Minimum of Months 672.00000 21.26836 25.83571 -0.9054 5.58634
Maximum of Months 744.00000 23.58259 58.24534 0.02029 22.95585



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.77876 19.95117 0.47036 12.58501
February 672.00000 22.77050 20.18569 0.46922 12.60731
March 744.00000 22.94589 27.09254 0.59992 15.75310
April 720.00000 23.05456 30.42001 0.67204 17.36935
May 744.00000 23.08428 35.92880 0.02649 10.03593
June 720.00000 23.06507 47.29867 0.13802 10.38531
July 744.00000 23.05499 55.40700 0.20839 10.73201
August 744.00000 23.04796 52.27394 0.18048 10.66147
September 720.00000 23.07415 47.19706 0.11874 10.28824
October 744.00000 23.10578 35.40620 0.72323 18.70068
November 720.00000 23.04772 29.00190 0.64003 16.48411
December 744.00000 22.80199 23.19907 0.49906 13.20248
           
Annual Sum or Average 8760.00000 22.98693 35.36918 0.39493 13.23454
Minimum of Months 672.00000 22.77050 19.95117 0.02649 10.03593
Maximum of Months 744.00000 23.10578 55.40700 0.72323 18.70068



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.28118 28.91563 -0.4299 9.50856
February 672.00000 21.29029 29.13219 -0.4188 9.39280
March 744.00000 22.05703 35.96341 -0.1046 6.88107
April 720.00000 22.36347 39.22427 0.01178 6.17977
May 744.00000 22.80921 44.23848 -0.7874 19.43979
June 720.00000 23.24571 54.48877 -0.5161 11.80794
July 744.00000 23.51311 61.66239 -0.3369 8.10482
August 744.00000 23.49407 58.63062 -0.3652 8.92596
September 720.00000 23.26293 54.39550 -0.5077 12.30426
October 744.00000 22.55503 44.04797 0.10721 6.91346
November 720.00000 21.97814 38.25967 -0.1297 6.59660
December 744.00000 21.30202 32.44236 -0.4088 9.22540
           
Annual Sum or Average 8760.00000 22.43561 43.53335 -0.3235 9.61267
Minimum of Months 672.00000 21.28118 28.91563 -0.7874 6.17977
Maximum of Months 744.00000 23.51311 61.66239 0.10721 19.43979



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.75671 28.42957 -0.2864 7.23475
February 672.00000 21.74528 28.64892 -0.2872 7.23856
March 744.00000 22.50461 35.19025 -0.0337 5.95391
April 720.00000 22.88896 38.24825 0.08820 5.75400
May 744.00000 23.29448 43.05740 -0.7183 16.56026
June 720.00000 23.56443 53.23021 -0.5243 11.36454
July 744.00000 23.70036 60.46971 -0.4076 8.74916
August 744.00000 23.70396 57.41088 -0.4294 9.17333
September 720.00000 23.58830 53.19243 -0.5210 11.23365
October 744.00000 23.13155 42.89343 0.18792 6.36300
November 720.00000 22.61802 37.22569 0.00432 5.69532
December 744.00000 21.81035 31.80965 -0.2523 6.97043
           
Annual Sum or Average 8760.00000 22.86472 42.56481 -0.2651 8.53495
Minimum of Months 672.00000 21.74528 28.42957 -0.7183 5.69532
Maximum of Months 744.00000 23.70396 60.46971 0.18792 16.56026



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.54391 26.90684 -0.7792 18.32168
February 672.00000 20.57611 26.93606 -0.7625 17.77772
March 744.00000 20.98329 34.99187 -0.5248 11.70378
April 720.00000 21.24491 39.74508 -0.3812 8.88963
May 744.00000 21.53427 45.51149 -1.3346 43.07659
June 720.00000 21.67573 52.16932 -1.1445 34.14731
July 744.00000 21.70789 55.99252 -1.0723 30.94270
August 744.00000 21.68620 55.40798 -1.1052 32.42482
September 720.00000 21.60416 54.90933 -1.2186 37.59748
October 744.00000 21.21676 46.01802 -0.3568 8.48227
November 720.00000 20.86440 38.68202 -0.5557 12.11009
December 744.00000 20.55470 30.77767 -0.7535 17.53292
           
Annual Sum or Average 8760.00000 21.18588 42.41967 -0.8331 22.78668
Minimum of Months 672.00000 20.54391 26.90684 -1.3346 8.48227
Maximum of Months 744.00000 21.70789 55.99252 -0.3568 43.07659



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.48903 27.00553 -0.8140 19.54973
February 672.00000 20.50219 27.05977 -0.8008 19.05409
March 744.00000 20.76442 35.36766 -0.6022 13.62727
April 720.00000 21.09286 40.04887 -0.4353 9.63770
May 744.00000 21.45500 45.74485 -1.3776 45.03334
June 720.00000 21.65291 52.34992 -1.1623 34.81339
July 744.00000 21.70087 56.34782 -1.0869 31.44192
August 744.00000 21.66788 56.01229 -1.1315 33.39661
September 720.00000 21.51271 55.76349 -1.2817 40.27165
October 744.00000 21.01556 46.56275 -0.4286 9.43492
November 720.00000 20.69485 39.04490 -0.6139 13.40703
December 744.00000 20.49698 30.88933 -0.7837 18.55161
           
Annual Sum or Average 8760.00000 21.09026 42.76637 -0.8772 24.05344
Minimum of Months 672.00000 20.48903 27.00553 -1.3776 9.43492
Maximum of Months 744.00000 21.70087 56.34782 -0.4286 45.03334



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.66655 25.59527 -0.6874 15.41181
February 672.00000 20.68686 25.64547 -0.6809 15.14016
March 744.00000 20.90256 33.88423 -0.5449 11.86464
April 720.00000 21.12068 38.85532 -0.4310 9.07034
May 744.00000 21.30823 44.46185 -1.4871 50.27092
June 720.00000 21.45472 52.46788 -1.3440 42.89018
July 744.00000 21.52638 57.43371 -1.2713 39.27008
August 744.00000 21.47568 56.28035 -1.3110 41.18946
September 720.00000 21.32759 54.63844 -1.4119 46.29854
October 744.00000 21.10461 45.11133 -0.3964 8.47262
November 720.00000 20.93297 37.48397 -0.5136 10.71914
December 744.00000 20.69815 29.39949 -0.6546 14.47616
           
Annual Sum or Average 8760.00000 21.10262 41.85916 -0.8959 25.48739
Minimum of Months 672.00000 20.66655 25.59527 -1.4871 8.47262
Maximum of Months 744.00000 21.52638 57.43371 -0.3964 50.27092



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.55061 26.88634 -0.7724 18.09128
February 672.00000 20.59115 26.90687 -0.7546 17.50738
March 744.00000 21.03353 34.84516 -0.5146 11.45558
April 720.00000 21.33898 39.59369 -0.3558 8.60201
May 744.00000 21.60130 45.33934 -1.3114 42.05752
June 720.00000 21.71277 52.11136 -1.1395 34.00527
July 744.00000 21.73738 55.73064 -1.0621 30.59665
August 744.00000 21.71939 55.12442 -1.0955 32.07767
September 720.00000 21.64304 54.52020 -1.2018 36.90338
October 744.00000 21.28184 45.82952 -0.3381 8.27217
November 720.00000 20.86930 38.65977 -0.5522 12.04609
December 744.00000 20.55055 30.77651 -0.7535 17.54906
           
Annual Sum or Average 8760.00000 21.22243 42.27516 -0.8216 22.46577
Minimum of Months 672.00000 20.55055 26.88634 -1.3114 8.27217
Maximum of Months 744.00000 21.73738 55.73064 -0.3381 42.05752



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.49246 26.99072 -0.8081 19.35303
February 672.00000 20.50384 27.04456 -0.7957 18.87914
March 744.00000 20.80809 35.20408 -0.5935 13.39211
April 720.00000 21.21603 39.83248 -0.4041 9.13601
May 744.00000 21.56770 45.43642 -1.3422 43.39519
June 720.00000 21.70940 52.28208 -1.1518 34.43807
July 744.00000 21.73570 56.14470 -1.0748 31.01909
August 744.00000 21.71189 55.63831 -1.1189 32.93342
September 720.00000 21.59884 55.07787 -1.2519 38.97341
October 744.00000 21.09369 46.35852 -0.4067 9.01568
November 720.00000 20.70486 39.01139 -0.6092 13.32591
December 744.00000 20.49817 30.88301 -0.7831 18.56070
           
Annual Sum or Average 8760.00000 21.14005 42.57449 -0.8623 23.56867
Minimum of Months 672.00000 20.49246 26.99072 -1.3422 9.01568
Maximum of Months 744.00000 21.73570 56.14470 -0.4041 43.39519



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.50370 27.21195 -0.8405 20.45630
February 672.00000 20.52838 27.25589 -0.8243 19.88189
March 744.00000 20.87877 35.51584 -0.5828 13.24524
April 720.00000 21.17290 40.25640 -0.4216 9.80354
May 744.00000 21.50389 46.08636 -1.3631 44.70461
June 720.00000 21.66190 53.05350 -1.1518 34.71625
July 744.00000 21.69943 57.16473 -1.0703 31.06908
August 744.00000 21.67127 56.70273 -1.1110 32.91788
September 720.00000 21.57048 56.25758 -1.2452 39.09463
October 744.00000 21.12257 46.77698 -0.4053 9.44462
November 720.00000 20.77484 39.24760 -0.6117 13.56774
December 744.00000 20.51675 31.13699 -0.8123 19.51691
           
Annual Sum or Average 8760.00000 21.13695 43.13995 -0.8705 24.06617
Minimum of Months 672.00000 20.50370 27.21195 -1.3631 9.44462
Maximum of Months 744.00000 21.69943 57.16473 -0.4053 44.70461



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.47719 27.27509 -0.8701 21.57704
February 672.00000 20.48351 27.34063 -0.8579 21.08182
March 744.00000 20.69391 35.86786 -0.6555 15.18955
April 720.00000 21.01754 40.58242 -0.4783 10.64965
May 744.00000 21.42625 46.33195 -1.4076 46.71928
June 720.00000 21.64199 53.24505 -1.1692 35.35660
July 744.00000 21.69344 57.53928 -1.0850 31.55062
August 744.00000 21.65184 57.39831 -1.1385 33.91253
September 720.00000 21.47277 57.14862 -1.3142 42.04666
October 744.00000 20.90561 47.37773 -0.4830 10.63994
November 720.00000 20.61377 39.61071 -0.6695 14.99189
December 744.00000 20.47863 31.22201 -0.8391 20.49444
           
Annual Sum or Average 8760.00000 21.04946 43.49732 -0.9145 25.38143
Minimum of Months 672.00000 20.47719 27.27509 -1.4076 10.63994
Maximum of Months 744.00000 21.69344 57.53928 -0.4783 46.71928



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.79660 28.02162 -0.6868 15.83891
February 672.00000 20.79047 28.04550 -0.6847 15.68434
March 744.00000 21.24557 35.88959 -0.4385 10.26674
April 720.00000 21.34823 40.92906 -0.3542 8.68428
May 744.00000 21.53833 46.22041 -1.3672 44.86297
June 720.00000 21.64299 53.23409 -1.2187 37.63138
July 744.00000 21.69011 57.00058 -1.1309 33.60390
August 744.00000 21.67311 55.77582 -1.1495 34.55649
September 720.00000 21.62848 54.61981 -1.2157 37.82203
October 744.00000 21.38624 46.54398 -0.2898 7.90799
November 720.00000 21.09876 39.60153 -0.4686 10.73562
December 744.00000 20.73739 31.78850 -0.6844 15.80452
           
Annual Sum or Average 8760.00000 21.30075 43.21990 -0.8084 22.83137
Minimum of Months 672.00000 20.73739 28.02162 -1.3672 7.90799
Maximum of Months 744.00000 21.69011 57.00058 -0.2898 44.86297



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.07609 29.51038 0.03378 5.99986
February 672.00000 23.08482 29.74002 0.03790 5.93207
March 744.00000 23.45654 35.64632 0.21100 6.88362
April 720.00000 23.73332 38.03258 0.32831 7.58721
May 744.00000 23.88678 42.46212 -0.4327 9.20748
June 720.00000 23.95542 52.52869 -0.2785 6.86575
July 744.00000 23.97725 59.89094 -0.1899 5.81305
August 744.00000 23.96009 57.14136 -0.2332 6.23601
September 720.00000 23.90026 53.03485 -0.3374 7.66322
October 744.00000 23.72249 42.88272 0.36111 8.11002
November 720.00000 23.55293 37.30527 0.25035 6.79163
December 744.00000 23.13085 32.53404 0.07180 6.14870
           
Annual Sum or Average 8760.00000 23.62232 42.63525 -0.0153 6.94162
Minimum of Months 672.00000 23.07609 29.51038 -0.4327 5.81305
Maximum of Months 744.00000 23.97725 59.89094 0.36111 9.20748



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.34347 28.54256 0.13745 6.15198
February 672.00000 23.35915 28.77841 0.14327 6.12187
March 744.00000 23.65227 34.61629 0.29679 7.56091
April 720.00000 23.86723 37.03362 0.39870 8.53826
May 744.00000 23.95802 41.66661 -0.3582 7.87380
June 720.00000 23.98472 51.92888 -0.2260 6.26604
July 744.00000 23.98955 59.39740 -0.1476 5.50571
August 744.00000 23.98214 56.59617 -0.1865 5.80523
September 720.00000 23.95463 52.29903 -0.2738 6.77157
October 744.00000 23.85463 41.87917 0.43027 9.12850
November 720.00000 23.73547 36.21542 0.33378 7.64838
December 744.00000 23.38622 31.51263 0.17277 6.43338
           
Annual Sum or Average 8760.00000 23.75746 41.78258 0.05942 6.98735
Minimum of Months 672.00000 23.34347 28.54256 -0.3582 5.50571
Maximum of Months 744.00000 23.98955 59.39740 0.43027 9.12850



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.60588 27.03230 0.79720 21.52200
February 672.00000 23.59392 27.21257 0.79928 21.73940
March 744.00000 23.76847 33.34195 0.95410 27.33331
April 720.00000 23.89846 36.26076 1.05275 30.84297
May 744.00000 23.91540 41.03514 0.57191 16.58422
June 720.00000 23.94547 51.14829 0.72132 20.08043
July 744.00000 23.95266 58.48923 0.81020 22.57170
August 744.00000 23.94144 55.66352 0.76402 21.20604
September 720.00000 23.92023 51.30401 0.66307 18.52651
October 744.00000 23.92290 40.97136 1.08679 32.13191
November 720.00000 23.84998 35.24360 0.98176 27.87771
December 744.00000 23.63219 29.97576 0.82559 22.40963
           
Annual Sum or Average 8760.00000 23.83003 40.71901 0.83576 23.57549
Minimum of Months 672.00000 23.59392 27.03230 0.57191 16.58422
Maximum of Months 744.00000 23.95266 58.48923 1.08679 32.13191



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00024 22.79824 -0.5639 11.72699
February 672.00000 21.00022 22.98549 -0.5653 11.74949
March 744.00000 21.15152 30.73466 -0.4459 9.67577
April 720.00000 21.29188 34.63344 -0.3705 8.09075
May 744.00000 22.03727 39.31783 -1.2509 38.00635
June 720.00000 22.86153 49.40199 -0.8962 22.50664
July 744.00000 23.34239 56.59656 -0.6781 14.91690
August 744.00000 23.24106 53.41234 -0.7356 16.63716
September 720.00000 22.63550 49.86352 -0.9730 25.48306
October 744.00000 21.60407 39.71591 -0.2561 6.77386
November 720.00000 21.13497 33.31789 -0.4220 8.86315
December 744.00000 21.00116 26.48840 -0.5367 11.11413
           
Annual Sum or Average 8760.00000 21.86420 38.35913 -0.6415 15.48405
Minimum of Months 672.00000 21.00022 22.79824 -1.2509 6.77386
Maximum of Months 744.00000 23.34239 56.59656 -0.2561 38.00635



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00084 26.44944 -0.5395 11.14085
February 672.00000 21.00244 26.63119 -0.5359 11.05300
March 744.00000 21.16785 34.33083 -0.4236 9.14185
April 720.00000 21.51142 37.73688 -0.3131 7.31196
May 744.00000 22.33471 42.15986 -1.1569 33.42797
June 720.00000 23.13263 52.01378 -0.8093 19.23675
July 744.00000 23.57325 58.82949 -0.6050 12.82630
August 744.00000 23.48958 55.94981 -0.6553 14.26575
September 720.00000 22.87223 52.61435 -0.8981 22.45849
October 744.00000 21.61500 43.19330 -0.2521 6.69076
November 720.00000 21.11557 36.84511 -0.4251 8.87523
December 744.00000 21.00169 30.09382 -0.5183 10.67984
           
Annual Sum or Average 8760.00000 21.99094 41.48816 -0.5946 13.94337
Minimum of Months 672.00000 21.00084 26.44944 -1.1569 6.69076
Maximum of Months 744.00000 23.57325 58.82949 -0.2521 33.42797



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00188 24.17081 -0.5588 11.61380
February 672.00000 21.00208 24.39549 -0.5558 11.53502
March 744.00000 21.17927 32.01748 -0.4192 9.26519
April 720.00000 21.46913 35.54930 -0.3056 7.31728
May 744.00000 22.27590 39.90684 -1.1293 32.41888
June 720.00000 23.15733 49.37851 -0.7455 17.59406
July 744.00000 23.62294 56.13863 -0.5254 11.13598
August 744.00000 23.44820 53.52133 -0.6091 13.34385
September 720.00000 22.72648 50.53570 -0.8966 22.86281
October 744.00000 21.52904 40.99136 -0.2542 6.84779
November 720.00000 21.10948 34.58906 -0.4189 8.80719
December 744.00000 21.00322 27.84018 -0.5346 11.07708
           
Annual Sum or Average 8760.00000 21.96659 39.16941 -0.5795 13.66356
Minimum of Months 672.00000 21.00188 24.17081 -1.1293 6.84779
Maximum of Months 744.00000 23.62294 56.13863 -0.2542 32.41888



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00881 22.33902 -0.5417 11.21480
February 672.00000 21.00736 22.54450 -0.5435 11.24285
March 744.00000 21.24670 30.07184 -0.4113 9.16994
April 720.00000 21.47885 33.76982 -0.3194 7.44693
May 744.00000 22.26466 38.27292 -1.1659 33.94472
June 720.00000 23.06456 48.20341 -0.8166 19.69037
July 744.00000 23.49993 55.34879 -0.6116 13.12671
August 744.00000 23.41849 52.20356 -0.6629 14.52347
September 720.00000 22.84802 48.65739 -0.8913 22.35128
October 744.00000 21.84322 38.64537 -0.1946 6.24106
November 720.00000 21.28447 32.55075 -0.3772 8.18652
December 744.00000 21.01863 26.01470 -0.5135 10.60964
           
Annual Sum or Average 8760.00000 22.00492 37.46978 -0.5877 13.99669
Minimum of Months 672.00000 21.00736 22.33902 -1.1659 6.24106
Maximum of Months 744.00000 23.49993 55.34879 -0.1946 33.94472



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.552380E+09 21129.45 18-JAN-19:04 89.29 0.176012E+10 0.00 0.231250E+10 0.38 3.19 07-JAN-07:00 0.00 0.00
February 0.472330E+09 16225.18 15-FEB-19:04 73.39 0.150504E+10 0.00 0.197737E+10 0.35 3.19 01-FEB-03:00 0.00 0.00
March 0.992227E+10 99238.70 15-MAR-15:03 315.83 0.295016E+11 0.00 0.394238E+11 1.34 3.60 15-MAR-18:03 0.00 0.00
April 0.100293E+11 63206.15 08-APR-15:03 452.43 0.308480E+11 0.00 0.408773E+11 1.98 3.19 02-APR-19:50 0.00 0.00
May 0.452953E+11 107987.20 10-MAY-15:03 687.58 0.135009E+12 0.00 0.180305E+12 2.85 3.64 23-MAY-18:03 0.00 0.00
June 0.135094E+12 162157.45 27-JUN-20:30 717.79 0.439903E+12 0.00 0.574997E+12 3.15 4.21 27-JUN-21:00 0.00 0.00
July 0.222114E+12 175933.45 20-JUL-18:03 744.00 0.765316E+12 0.00 0.987431E+12 3.35 4.27 05-JUL-18:03 0.00 0.00
August 0.176870E+12 163430.33 13-AUG-15:03 743.00 0.585260E+12 0.00 0.762130E+12 3.21 4.30 28-AUG-18:03 0.00 0.00
September 0.937598E+11 140139.50 15-SEP-18:03 695.27 0.303938E+12 0.00 0.397698E+12 3.03 4.26 14-SEP-18:02 0.00 0.00
October 0.176643E+11 85742.24 11-OCT-15:02 492.13 0.530428E+11 0.00 0.707071E+11 2.07 3.51 11-OCT-15:02 0.00 0.00
November 0.554350E+10 39283.85 05-NOV-15:02 330.47 0.168739E+11 0.00 0.224174E+11 1.45 3.19 01-NOV-13:10 0.00 0.00
December 0.828814E+09 22057.59 15-DEC-19:04 136.16 0.264028E+10 0.00 0.346909E+10 0.58 3.19 02-DEC-09:06 0.00 0.00
                         
Annual Sum or Average 0.718146E+12     5477.34 0.236560E+13 0.00 0.308374E+13 1.99     0.00 0.00
Minimum of Months 0.472330E+09 16225.18   73.39 0.150504E+10 0.00 0.197737E+10 0.35 3.19   0.00 0.00
Maximum of Months 0.222114E+12 175933.45   744.00 0.765316E+12 0.00 0.987431E+12 3.35 4.30   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.228428E+12 0.00 744.00 264865.87 31-JAN-09:03 0.00 51.39 81.52 0.67 0.00 0.15 0.47 31-JAN-09:03
February 0.214856E+12 0.00 672.00 314014.86 06-FEB-09:03 0.00 50.35 81.60 0.68 0.00 0.16 0.56 06-FEB-09:03
March 0.978490E+11 0.00 703.29 234932.53 04-MAR-09:01 0.00 52.49 79.58 0.30 0.00 0.07 0.42 04-MAR-09:01
April 0.396798E+11 0.00 630.66 201386.61 14-APR-15:01 0.00 50.83 75.34 0.14 0.00 0.03 0.36 14-APR-15:01
May 0.202844E+11 0.00 379.12 139608.24 07-MAY-23:30 0.00 42.26 60.78 0.05 0.00 0.01 0.25 07-MAY-23:30
June 0.534768E+10 0.00 111.56 132475.05 13-JUN-23:50 0.00 37.59 43.91 0.01 0.00 0.00 0.24 13-JUN-23:50
July 0.413944E+09 0.00 22.72 34250.17 04-JUL-18:07 0.00 47.19 48.38 0.00 0.00 0.00 0.06 04-JUL-18:07
August 0.113140E+10 0.00 46.00 65270.08 31-AUG-15:04 0.00 46.97 49.25 0.00 0.00 0.00 0.12 31-AUG-15:04
September 0.915261E+10 0.00 235.04 133782.87 30-SEP-03:35 0.00 45.79 56.75 0.02 0.00 0.01 0.24 30-SEP-03:35
October 0.409117E+11 0.00 628.73 189613.35 26-OCT-15:01 0.00 52.85 75.63 0.14 0.00 0.03 0.34 26-OCT-15:01
November 0.635626E+11 0.00 703.36 214358.42 13-NOV-16:01 0.00 56.15 79.82 0.25 0.00 0.04 0.38 13-NOV-16:01
December 0.209216E+12 0.00 744.00 292394.51 11-DEC-09:03 0.00 53.24 81.30 0.64 0.00 0.14 0.52 11-DEC-09:03
                           
Annual Sum or Average 0.930833E+12 0.00 5620.48     0.00 48.93 67.75 0.24 0.00 0.05    
Minimum of Months 0.413944E+09 0.00 22.72 34250.17   0.00 37.59 43.91 0.00 0.00 0.00 0.06  
Maximum of Months 0.228428E+12 0.00 744.00 314014.86   0.00 56.15 81.60 0.68 0.00 0.16 0.56  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.115572E+09 0.00 66.52 0.115572E+09 0.00 0.00 0.00 0.00 16960.16 17-JAN-21:47 16960.16 17-JAN-21:47 0.00 0.00 0.00
February 68941029.73 0.00 46.55 68941029.73 0.00 0.00 0.00 0.00 12923.43 14-FEB-21:07 12923.43 14-FEB-21:07 0.00 0.00 0.00
March 0.147386E+11 0.00 149.49 0.144763E+11 0.00 0.00 0.00 0.00 204644.29 14-MAR-10:45 183165.30 15-MAR-18:03 0.00 0.00 0.00
April 0.835226E+10 0.00 200.28 0.835226E+10 0.00 0.00 0.00 0.00 103120.40 08-APR-13:00 103120.40 08-APR-13:00 0.00 0.00 0.00
May 0.678803E+11 0.00 393.32 0.667084E+11 0.00 0.00 0.00 0.00 186664.54 10-MAY-15:30 167935.03 23-MAY-18:03 0.00 0.00 0.00
June 0.279509E+12 0.00 590.06 0.205812E+12 0.00 0.00 0.00 0.00 498552.28 27-JUN-20:30 213786.47 27-JUN-18:20 0.00 0.00 0.00
July 0.519091E+12 0.00 715.18 0.330091E+12 0.00 0.00 0.00 0.00 532232.45 21-JUL-20:10 245681.74 20-JUL-19:10 0.00 0.00 0.00
August 0.381635E+12 0.00 682.86 0.277839E+12 0.00 0.00 0.00 0.00 474674.86 14-AUG-21:50 239462.76 10-AUG-21:00 0.00 0.00 0.00
September 0.184696E+12 0.00 509.04 0.136716E+12 0.00 0.00 0.00 0.00 433138.52 15-SEP-20:20 201306.24 16-SEP-21:00 0.00 0.00 0.00
October 0.227375E+11 0.00 253.26 0.227375E+11 0.00 0.00 0.00 0.00 132221.82 11-OCT-15:10 132221.82 11-OCT-15:10 0.00 0.00 0.00
November 0.740054E+10 0.00 213.21 0.740054E+10 0.00 0.00 0.00 0.00 78292.29 05-NOV-10:50 78292.29 05-NOV-10:50 0.00 0.00 0.00
December 0.211801E+09 0.00 110.48 0.211801E+09 0.00 0.00 0.00 0.00 17303.53 13-DEC-21:19 17303.53 13-DEC-21:19 0.00 0.00 0.00
                               
Annual Sum or Average 0.148644E+13 0.00 3930.25 0.107053E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 68941029.73 0.00 46.55 68941029.73 0.00 0.00 0.00 0.00 12923.43   12923.43   0.00 0.00 0.00
Maximum of Months 0.519091E+12 0.00 715.18 0.330091E+12 0.00 0.00 0.00 0.00 532232.45   245681.74   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 0.00 0.00
March 0.281633E+10 0.00 50.33 0.264764E+10 0.00 0.00 0.00 0.00 37606.15 14-MAR-10:50 28864.38 15-MAR-14:00 0.00 0.00 0.00
April 0.133318E+10 0.00 63.77 0.133318E+10 0.00 0.00 0.00 0.00 22527.05 08-APR-13:00 22527.05 08-APR-13:00 0.00 0.00 0.00
May 0.125841E+11 0.00 311.06 0.120189E+11 0.00 0.00 0.00 0.00 34286.96 14-MAY-12:20 29320.12 14-MAY-15:00 0.00 0.00 0.00
June 0.515262E+11 0.00 569.33 0.364595E+11 0.00 0.00 0.00 0.00 62279.57 27-JUN-21:30 32702.12 27-JUN-13:00 0.00 0.00 0.00
July 0.918421E+11 0.00 710.83 0.574545E+11 0.00 0.00 0.00 0.00 70129.18 15-JUL-12:10 33439.37 21-JUL-14:00 0.00 0.00 0.00
August 0.679416E+11 0.00 666.67 0.482534E+11 0.00 0.00 0.00 0.00 64880.70 26-AUG-17:40 32510.39 13-AUG-15:00 0.00 0.00 0.00
September 0.354053E+11 0.00 477.50 0.247654E+11 0.00 0.00 0.00 0.00 62121.65 15-SEP-20:30 30215.24 16-SEP-14:00 0.00 0.00 0.00
October 0.405337E+10 0.00 141.31 0.405223E+10 0.00 0.00 0.00 0.00 25256.43 11-OCT-15:00 25256.43 11-OCT-15:00 0.00 0.00 0.00
November 0.150209E+10 0.00 58.58 0.150209E+10 0.00 0.00 0.00 0.00 16476.56 05-NOV-14:00 16476.56 05-NOV-14:00 0.00 0.00 0.00
December 1785398.26 0.00 1.00 1785398.26 0.00 0.00 0.00 0.00 966.69 01-DEC-11:00 966.69 01-DEC-11:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.269006E+12 0.00 3050.38 0.188489E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.918421E+11 0.00 710.83 0.574545E+11 0.00 0.00 0.00 0.00 70129.18   33439.37   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 12338819.31 0.00 1.99 12251657.46 0.00 0.00 0.00 0.00 12829.87 15-JAN-16:01 12829.87 15-JAN-16:01 0.00 0.00 0.00
February 28959213.40 0.00 4.86 28878906.39 0.00 0.00 0.00 0.00 13404.21 28-FEB-16:01 13404.21 28-FEB-16:01 0.00 0.00 0.00
March 0.517008E+09 0.00 87.55 0.366422E+09 0.00 0.00 0.00 0.00 15068.68 14-MAR-15:02 13876.31 15-MAR-15:02 0.00 0.00 0.00
April 0.121319E+10 0.00 183.28 0.110345E+10 0.00 0.00 0.00 0.00 14027.89 07-APR-15:01 14027.89 07-APR-15:01 0.00 0.00 0.00
May 0.341210E+10 0.00 469.19 0.260475E+10 0.00 0.00 0.00 0.00 14772.84 23-MAY-15:02 14772.84 23-MAY-15:02 0.00 0.00 0.00
June 0.748758E+10 0.00 633.99 0.483977E+10 0.00 0.00 0.00 0.00 18162.18 18-JUN-08:62 14684.80 30-JUN-18:02 0.00 0.00 0.00
July 0.998108E+10 0.00 686.89 0.596458E+10 0.00 0.00 0.00 0.00 17970.68 28-JUL-18:02 14610.36 16-JUL-15:02 0.00 0.00 0.00
August 0.867070E+10 0.00 672.19 0.526808E+10 0.00 0.00 0.00 0.00 17609.76 15-AUG-08:62 14647.02 13-AUG-18:02 0.00 0.00 0.00
September 0.474400E+10 0.00 574.09 0.271724E+10 0.00 0.00 0.00 0.00 17065.15 17-SEP-08:62 14401.75 19-SEP-15:02 0.00 0.00 0.00
October 0.977280E+09 0.00 198.84 0.606365E+09 0.00 0.00 0.00 0.00 14024.72 25-OCT-15:01 14024.72 25-OCT-15:01 0.00 0.00 0.00
November 68868752.78 0.00 23.05 59398054.84 0.00 0.00 0.00 0.00 13679.23 03-NOV-15:02 13679.23 03-NOV-15:02 0.00 0.00 0.00
December 10349057.77 0.00 1.47 10109321.02 0.00 0.00 0.00 0.00 3492.99 20-DEC-19:04 3492.99 20-DEC-19:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.371234E+11 0.00 3537.38 0.235813E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 10349057.77 0.00 1.47 10109321.02 0.00 0.00 0.00 0.00 3492.99   3492.99   0.00 0.00 0.00
Maximum of Months 0.998108E+10 0.00 686.89 0.596458E+10 0.00 0.00 0.00 0.00 18162.18   14772.84   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 6266170.23 0.00 0.99 6157605.45 0.00 0.00 0.00 0.00 3602.85 11-JAN-16:04 3490.15 15-JAN-16:03 0.00 0.00 0.00
February 6103321.25 0.00 1.69 6028062.57 0.00 0.00 0.00 0.00 3323.60 22-FEB-16:03 3323.60 22-FEB-16:03 0.00 0.00 0.00
March 0.242723E+09 0.00 57.82 0.141863E+09 0.00 0.00 0.00 0.00 14454.99 14-MAR-15:02 13509.22 15-MAR-15:02 0.00 0.00 0.00
April 0.762010E+09 0.00 124.37 0.686379E+09 0.00 0.00 0.00 0.00 13444.58 07-APR-15:01 13444.58 07-APR-15:01 0.00 0.00 0.00
May 0.284500E+10 0.00 420.54 0.215222E+10 0.00 0.00 0.00 0.00 14680.77 10-MAY-15:02 14276.84 23-MAY-15:02 0.00 0.00 0.00
June 0.704732E+10 0.00 611.09 0.455348E+10 0.00 0.00 0.00 0.00 17518.26 18-JUN-08:62 14202.83 26-JUN-15:02 0.00 0.00 0.00
July 0.934252E+10 0.00 677.00 0.553669E+10 0.00 0.00 0.00 0.00 17202.67 17-JUL-08:62 14171.78 11-JUL-15:02 0.00 0.00 0.00
August 0.764419E+10 0.00 654.72 0.450410E+10 0.00 0.00 0.00 0.00 16995.54 14-AUG-08:62 14125.37 18-AUG-18:02 0.00 0.00 0.00
September 0.341577E+10 0.00 499.34 0.182969E+10 0.00 0.00 0.00 0.00 16474.22 17-SEP-08:62 13982.08 16-SEP-15:02 0.00 0.00 0.00
October 0.423276E+09 0.00 112.94 0.240613E+09 0.00 0.00 0.00 0.00 13724.73 12-OCT-15:01 12795.00 31-OCT-15:02 0.00 0.00 0.00
November 22846919.63 0.00 4.97 20733616.11 0.00 0.00 0.00 0.00 6326.70 15-NOV-16:01 6326.70 15-NOV-16:01 0.00 0.00 0.00
December 7848661.18 0.00 1.21 7619767.45 0.00 0.00 0.00 0.00 3580.92 14-DEC-19:04 3580.92 14-DEC-19:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.317659E+11 0.00 3166.69 0.196856E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 6103321.25 0.00 0.99 6028062.57 0.00 0.00 0.00 0.00 3323.60   3323.60   0.00 0.00 0.00
Maximum of Months 0.934252E+10 0.00 677.00 0.553669E+10 0.00 0.00 0.00 0.00 17518.26   14276.84   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 0.00 0.00
March 0.596365E+09 0.00 25.67 0.320758E+09 0.00 0.00 0.00 0.00 27170.83 15-MAR-13:30 18823.90 15-MAR-13:30 0.00 0.00 0.00
April 0.231918E+10 0.00 77.23 0.222755E+10 0.00 0.00 0.00 0.00 23407.25 22-APR-13:10 23407.25 22-APR-13:10 0.00 0.00 0.00
May 0.601759E+10 0.00 207.76 0.504718E+10 0.00 0.00 0.00 0.00 20831.27 14-MAY-13:50 20056.44 05-MAY-13:30 0.00 0.00 0.00
June 0.161774E+11 0.00 403.27 0.846166E+10 0.00 0.00 0.00 0.00 33319.40 27-JUN-13:00 23006.45 27-JUN-13:00 0.00 0.00 0.00
July 0.304798E+11 0.00 583.96 0.146578E+11 0.00 0.00 0.00 0.00 38552.65 21-JUL-13:30 32020.72 21-JUL-13:30 0.00 0.00 0.00
August 0.296715E+11 0.00 567.99 0.166405E+11 0.00 0.00 0.00 0.00 44988.83 18-AUG-14:40 37970.59 17-AUG-13:50 0.00 0.00 0.00
September 0.213188E+11 0.00 413.45 0.144826E+11 0.00 0.00 0.00 0.00 52400.99 21-SEP-13:00 44166.73 19-SEP-12:50 0.00 0.00 0.00
October 0.627878E+10 0.00 126.50 0.513906E+10 0.00 0.00 0.00 0.00 49974.35 11-OCT-12:30 47768.14 11-OCT-12:30 0.00 0.00 0.00
November 0.602310E+09 0.00 17.63 0.602310E+09 0.00 0.00 0.00 0.00 21674.04 01-NOV-11:50 21674.04 01-NOV-11:50 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.113462E+12 0.00 2423.44 0.675794E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.304798E+11 0.00 583.96 0.166405E+11 0.00 0.00 0.00 0.00 52400.99   47768.14   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 49562040.89 0.00 1.10 49463997.10 0.00 0.00 0.00 0.00 32095.42 19-JAN-19:04 32095.42 19-JAN-19:04 0.00 0.00 0.00
February 44372993.94 0.00 1.50 44372993.94 0.00 0.00 0.00 0.00 32238.27 17-FEB-19:04 32238.27 17-FEB-19:04 0.00 0.00 0.00
March 0.316572E+10 0.00 110.43 0.171259E+10 0.00 0.00 0.00 0.00 68213.53 14-MAR-15:02 64561.17 15-MAR-15:02 0.00 0.00 0.00
April 0.518356E+10 0.00 253.80 0.390761E+10 0.00 0.00 0.00 0.00 62974.34 09-APR-15:02 62974.34 09-APR-15:02 0.00 0.00 0.00
May 0.199365E+11 0.00 500.01 0.145293E+11 0.00 0.00 0.00 0.00 72871.94 14-MAY-15:02 70114.19 23-MAY-18:02 0.00 0.00 0.00
June 0.415136E+11 0.00 510.94 0.276845E+11 0.00 0.00 0.00 0.00 91716.32 18-JUN-08:62 71745.64 30-JUN-18:02 0.00 0.00 0.00
July 0.562684E+11 0.00 534.21 0.356216E+11 0.00 0.00 0.00 0.00 90121.68 17-JUL-08:62 71136.69 14-JUL-18:02 0.00 0.00 0.00
August 0.463100E+11 0.00 526.89 0.287139E+11 0.00 0.00 0.00 0.00 91400.69 26-AUG-18:02 72555.72 09-AUG-18:02 0.00 0.00 0.00
September 0.250598E+11 0.00 499.67 0.134095E+11 0.00 0.00 0.00 0.00 85006.03 17-SEP-08:62 67570.75 16-SEP-18:02 0.00 0.00 0.00
October 0.585599E+10 0.00 283.94 0.284167E+10 0.00 0.00 0.00 0.00 70506.15 01-OCT-08:62 60175.46 28-OCT-08:62 0.00 0.00 0.00
November 0.104888E+10 0.00 84.09 0.659028E+09 0.00 0.00 0.00 0.00 39955.16 26-NOV-09:02 39955.16 26-NOV-09:02 0.00 0.00 0.00
December 77605113.89 0.00 2.99 72905999.02 0.00 0.00 0.00 0.00 35487.70 13-DEC-19:04 35487.70 13-DEC-19:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.204514E+12 0.00 3309.57 0.129247E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 44372993.94 0.00 1.10 44372993.94 0.00 0.00 0.00 0.00 32095.42   32095.42   0.00 0.00 0.00
Maximum of Months 0.562684E+11 0.00 534.21 0.356216E+11 0.00 0.00 0.00 0.00 91716.32   72555.72   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 8175224.09 0.00 1.49 8088967.39 0.00 0.00 0.00 0.00 3606.79 10-JAN-09:04 3606.79 10-JAN-09:04 0.00 0.00 0.00
February 25101141.10 0.00 5.47 25044595.25 0.00 0.00 0.00 0.00 4916.89 28-FEB-09:01 4916.89 28-FEB-09:01 0.00 0.00 0.00
March 0.480267E+09 0.00 94.08 0.317740E+09 0.00 0.00 0.00 0.00 13554.52 14-MAR-15:02 12602.20 15-MAR-15:02 0.00 0.00 0.00
April 0.129032E+10 0.00 215.98 0.117413E+10 0.00 0.00 0.00 0.00 12701.75 07-APR-15:01 12701.75 07-APR-15:01 0.00 0.00 0.00
May 0.338943E+10 0.00 505.34 0.253990E+10 0.00 0.00 0.00 0.00 13705.86 10-MAY-15:02 13376.33 23-MAY-15:02 0.00 0.00 0.00
June 0.708097E+10 0.00 651.90 0.445697E+10 0.00 0.00 0.00 0.00 15404.44 17-JUN-08:62 13295.45 30-JUN-18:02 0.00 0.00 0.00
July 0.999328E+10 0.00 708.68 0.598079E+10 0.00 0.00 0.00 0.00 16320.38 28-JUL-18:02 13127.67 25-JUL-18:02 0.00 0.00 0.00
August 0.859883E+10 0.00 692.79 0.520946E+10 0.00 0.00 0.00 0.00 16026.95 26-AUG-18:02 13181.85 05-AUG-18:02 0.00 0.00 0.00
September 0.493521E+10 0.00 584.68 0.286590E+10 0.00 0.00 0.00 0.00 15449.92 17-SEP-08:62 13135.95 16-SEP-15:02 0.00 0.00 0.00
October 0.105794E+10 0.00 224.15 0.663958E+09 0.00 0.00 0.00 0.00 12820.65 12-OCT-15:01 12400.95 31-OCT-15:02 0.00 0.00 0.00
November 0.124053E+09 0.00 31.99 0.103389E+09 0.00 0.00 0.00 0.00 11560.80 03-NOV-15:02 11560.80 03-NOV-15:02 0.00 0.00 0.00
December 12074805.59 0.00 5.37 11925898.84 0.00 0.00 0.00 0.00 4916.48 17-DEC-09:03 4916.48 17-DEC-09:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.369956E+11 0.00 3721.93 0.233573E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 8175224.09 0.00 1.49 8088967.39 0.00 0.00 0.00 0.00 3606.79   3606.79   0.00 0.00 0.00
Maximum of Months 0.999328E+10 0.00 708.68 0.598079E+10 0.00 0.00 0.00 0.00 16320.38   13376.33   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 4697593.00 0.00 0.91 4586584.91 0.00 0.00 0.00 0.00 3496.47 21-JAN-09:04 3496.47 21-JAN-09:04 0.00 0.00 0.00
February 5409281.64 0.00 1.19 5347381.04 0.00 0.00 0.00 0.00 3297.07 15-FEB-09:04 3297.07 15-FEB-09:04 0.00 0.00 0.00
March 0.233756E+09 0.00 56.83 0.122720E+09 0.00 0.00 0.00 0.00 13067.95 14-MAR-15:02 12221.99 15-MAR-15:02 0.00 0.00 0.00
April 0.781225E+09 0.00 141.92 0.695776E+09 0.00 0.00 0.00 0.00 11990.40 21-APR-08:61 11990.40 21-APR-08:61 0.00 0.00 0.00
May 0.275011E+10 0.00 450.94 0.203738E+10 0.00 0.00 0.00 0.00 13659.25 14-MAY-15:02 12938.08 23-MAY-15:02 0.00 0.00 0.00
June 0.660410E+10 0.00 645.83 0.414618E+10 0.00 0.00 0.00 0.00 14758.75 17-JUN-08:62 12859.91 30-JUN-18:02 0.00 0.00 0.00
July 0.932329E+10 0.00 706.86 0.549792E+10 0.00 0.00 0.00 0.00 15571.39 05-JUL-18:02 12803.53 10-JUL-15:02 0.00 0.00 0.00
August 0.754755E+10 0.00 684.90 0.439242E+10 0.00 0.00 0.00 0.00 15611.53 26-AUG-18:02 12763.36 18-AUG-15:02 0.00 0.00 0.00
September 0.354310E+10 0.00 530.74 0.189049E+10 0.00 0.00 0.00 0.00 14929.23 17-SEP-08:62 12613.00 19-SEP-15:02 0.00 0.00 0.00
October 0.427982E+09 0.00 124.94 0.232448E+09 0.00 0.00 0.00 0.00 11979.34 12-OCT-15:01 10745.28 22-OCT-15:02 0.00 0.00 0.00
November 34060870.73 0.00 12.29 25646251.84 0.00 0.00 0.00 0.00 8031.84 06-NOV-09:01 8031.84 06-NOV-09:01 0.00 0.00 0.00
December 5207989.35 0.00 0.99 5087570.53 0.00 0.00 0.00 0.00 3526.36 04-DEC-09:04 3526.36 04-DEC-09:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.312605E+11 0.00 3358.37 0.190560E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 4697593.00 0.00 0.91 4586584.91 0.00 0.00 0.00 0.00 3297.07   3297.07   0.00 0.00 0.00
Maximum of Months 0.932329E+10 0.00 706.86 0.549792E+10 0.00 0.00 0.00 0.00 15611.53   12938.08   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 2892273.62 0.00 1.90 2865029.07 0.00 0.00 0.00 0.00 3310.26 15-JAN-16:01 3310.26 15-JAN-16:01 0.00 0.00 0.00
February 6507927.61 0.00 4.41 6487150.63 0.00 0.00 0.00 0.00 3408.62 28-FEB-16:01 3408.62 28-FEB-16:01 0.00 0.00 0.00
March 0.118792E+09 0.00 73.23 84618099.68 0.00 0.00 0.00 0.00 3885.40 14-MAR-15:02 3632.49 14-MAR-15:02 0.00 0.00 0.00
April 0.303185E+09 0.00 149.00 0.279627E+09 0.00 0.00 0.00 0.00 3656.97 07-APR-15:01 3656.97 07-APR-15:01 0.00 0.00 0.00
May 0.814642E+09 0.00 389.46 0.645296E+09 0.00 0.00 0.00 0.00 3851.09 23-MAY-15:02 3851.09 23-MAY-15:02 0.00 0.00 0.00
June 0.183819E+10 0.00 610.34 0.119356E+10 0.00 0.00 0.00 0.00 4919.77 18-JUN-08:62 3827.79 30-JUN-18:02 0.00 0.00 0.00
July 0.249014E+10 0.00 687.33 0.148522E+10 0.00 0.00 0.00 0.00 4863.24 16-JUL-08:62 3801.82 20-JUL-15:02 0.00 0.00 0.00
August 0.210660E+10 0.00 664.35 0.128978E+10 0.00 0.00 0.00 0.00 4782.11 15-AUG-08:62 3794.03 13-AUG-18:02 0.00 0.00 0.00
September 0.107423E+10 0.00 492.27 0.638548E+09 0.00 0.00 0.00 0.00 4584.55 17-SEP-08:62 3754.37 19-SEP-15:02 0.00 0.00 0.00
October 0.211217E+09 0.00 143.18 0.140601E+09 0.00 0.00 0.00 0.00 3632.13 25-OCT-15:01 3632.13 25-OCT-15:01 0.00 0.00 0.00
November 14562687.65 0.00 11.23 13470541.12 0.00 0.00 0.00 0.00 3549.64 15-NOV-16:01 3549.64 15-NOV-16:01 0.00 0.00 0.00
December 2438969.37 0.00 1.47 2374799.67 0.00 0.00 0.00 0.00 1031.47 01-DEC-16:04 883.36 01-DEC-16:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.898340E+10 0.00 3228.15 0.578245E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 2438969.37 0.00 1.47 2374799.67 0.00 0.00 0.00 0.00 1031.47   883.36   0.00 0.00 0.00
Maximum of Months 0.249014E+10 0.00 687.33 0.148522E+10 0.00 0.00 0.00 0.00 4919.77   3851.09   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 1566641.96 0.00 0.95 1545843.59 0.00 0.00 0.00 0.00 890.73 15-JAN-16:03 890.73 15-JAN-16:03 0.00 0.00 0.00
February 1948716.20 0.00 1.15 1928779.44 0.00 0.00 0.00 0.00 1224.35 18-FEB-16:03 1224.35 18-FEB-16:03 0.00 0.00 0.00
March 51653339.60 0.00 45.78 29939873.28 0.00 0.00 0.00 0.00 3791.53 14-MAR-15:02 3513.27 15-MAR-15:02 0.00 0.00 0.00
April 0.184494E+09 0.00 104.72 0.168885E+09 0.00 0.00 0.00 0.00 3518.21 07-APR-15:01 3518.21 07-APR-15:01 0.00 0.00 0.00
May 0.665340E+09 0.00 346.95 0.526039E+09 0.00 0.00 0.00 0.00 3733.03 10-MAY-15:02 3711.32 23-MAY-15:02 0.00 0.00 0.00
June 0.171916E+10 0.00 591.45 0.111163E+10 0.00 0.00 0.00 0.00 4730.62 18-JUN-08:62 3688.73 30-JUN-18:02 0.00 0.00 0.00
July 0.232124E+10 0.00 679.26 0.136674E+10 0.00 0.00 0.00 0.00 4687.19 16-JUL-08:62 3654.45 16-JUL-15:02 0.00 0.00 0.00
August 0.183387E+10 0.00 647.39 0.108002E+10 0.00 0.00 0.00 0.00 4582.68 14-AUG-08:62 3689.70 13-AUG-18:02 0.00 0.00 0.00
September 0.734469E+09 0.00 400.58 0.417330E+09 0.00 0.00 0.00 0.00 4414.70 17-SEP-08:62 3664.32 16-SEP-15:02 0.00 0.00 0.00
October 79899933.02 0.00 70.25 49742647.76 0.00 0.00 0.00 0.00 3572.86 12-OCT-15:01 3292.74 12-OCT-15:01 0.00 0.00 0.00
November 5682575.50 0.00 2.87 5094365.92 0.00 0.00 0.00 0.00 1505.73 14-NOV-19:03 1489.74 09-NOV-16:03 0.00 0.00 0.00
December 2141116.00 0.00 1.23 2084402.85 0.00 0.00 0.00 0.00 1111.88 01-DEC-16:04 1037.58 01-DEC-16:04 0.00 0.00 0.00
                               
Annual Sum or Average 0.760146E+10 0.00 2892.60 0.476098E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 1566641.96 0.00 0.95 1545843.59 0.00 0.00 0.00 0.00 890.73   890.73   0.00 0.00 0.00
Maximum of Months 0.232124E+10 0.00 679.26 0.136674E+10 0.00 0.00 0.00 0.00 4730.62   3711.32   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.191586E+09 0.00 25.01 0.191386E+09 0.00 0.00 0.00 0.00 16539.81 15-JAN-16:01 16539.81 15-JAN-16:01 0.00 0.00 0.00
February 0.193530E+09 0.00 26.64 0.193428E+09 0.00 0.00 0.00 0.00 16539.56 18-FEB-16:01 16539.56 18-FEB-16:01 0.00 0.00 0.00
March 0.168955E+10 0.00 180.05 0.139067E+10 0.00 0.00 0.00 0.00 17155.06 15-MAR-18:01 17155.06 15-MAR-18:01 0.00 0.00 0.00
April 0.219097E+10 0.00 250.38 0.198372E+10 0.00 0.00 0.00 0.00 16964.89 07-APR-15:01 16964.89 07-APR-15:01 0.00 0.00 0.00
May 0.411481E+10 0.00 469.28 0.304045E+10 0.00 0.00 0.00 0.00 17865.18 23-MAY-15:02 17865.18 23-MAY-15:02 0.00 0.00 0.00
June 0.809114E+10 0.00 607.38 0.475706E+10 0.00 0.00 0.00 0.00 22606.73 18-JUN-08:62 17751.52 30-JUN-18:02 0.00 0.00 0.00
July 0.122312E+11 0.00 676.28 0.706971E+10 0.00 0.00 0.00 0.00 23063.99 28-JUL-18:02 17581.68 20-JUL-15:02 0.00 0.00 0.00
August 0.114392E+11 0.00 667.65 0.704966E+10 0.00 0.00 0.00 0.00 22917.30 26-AUG-18:02 17739.60 09-AUG-18:02 0.00 0.00 0.00
September 0.814433E+10 0.00 592.26 0.520446E+10 0.00 0.00 0.00 0.00 21310.58 17-SEP-08:62 17187.13 21-SEP-18:02 0.00 0.00 0.00
October 0.337814E+10 0.00 329.61 0.253936E+10 0.00 0.00 0.00 0.00 17705.40 01-OCT-08:62 16961.74 25-OCT-15:01 0.00 0.00 0.00
November 0.100271E+10 0.00 142.71 0.874004E+09 0.00 0.00 0.00 0.00 16546.11 15-NOV-16:01 16546.11 15-NOV-16:01 0.00 0.00 0.00
December 0.219539E+09 0.00 28.16 0.219208E+09 0.00 0.00 0.00 0.00 16537.85 16-DEC-16:01 16537.85 16-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.528866E+11 0.00 3995.42 0.345131E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.191586E+09 0.00 25.01 0.191386E+09 0.00 0.00 0.00 0.00 16537.85   16537.85   0.00 0.00 0.00
Maximum of Months 0.122312E+11 0.00 676.28 0.706971E+10 0.00 0.00 0.00 0.00 23063.99   17865.18   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 596.33 348.27 248.06 474.98 726.64 0.00 0.00 0.00
February 675.32 322.98 352.34 531.42 707.69 0.00 0.00 0.00
March 829.82 466.21 363.61 810.16 504.68 0.00 0.00 0.00
April 686.32 273.63 412.68 707.84 381.12 0.00 0.00 0.00
May 605.21 178.41 426.80 692.55 233.60 0.00 0.00 0.00
June 582.55 121.98 460.57 740.00 143.08 0.00 0.00 0.00
July 592.12 140.27 451.85 825.51 92.14 0.00 0.00 0.00
August 663.03 210.39 452.63 900.05 125.95 0.00 0.00 0.00
September 776.09 376.65 399.45 970.50 210.02 0.00 0.00 0.00
October 746.32 426.70 319.63 809.77 351.59 0.00 0.00 0.00
November 535.33 302.89 232.44 507.30 470.49 0.00 0.00 0.00
December 498.65 258.46 240.18 376.57 708.38 0.00 0.00 0.00
                 
Annual Sum or Average 648.75 285.45 363.30 696.51 386.27 0.00 0.00 0.00
Minimum of Months 498.65 121.98 232.44 376.57 92.14 0.00 0.00 0.00
Maximum of Months 829.82 466.21 460.57 970.50 726.64 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1679.21 980.69 698.52 1319.15 2080.96 0.00 0.00 0.00
February 1901.67 909.50 992.17 1474.80 2024.87 0.00 0.00 0.00
March 2336.72 1312.81 1023.90 2247.26 1487.14 0.00 0.00 0.00
April 1932.62 770.53 1162.09 1956.11 1151.70 0.00 0.00 0.00
May 1704.23 502.40 1201.83 1903.11 737.98 0.00 0.00 0.00
June 1640.41 343.49 1296.92 2040.53 458.42 0.00 0.00 0.00
July 1667.37 395.00 1272.37 2291.04 296.63 0.00 0.00 0.00
August 1867.04 592.46 1274.59 2503.04 401.99 0.00 0.00 0.00
September 2185.43 1060.61 1124.82 2695.18 668.25 0.00 0.00 0.00
October 2101.60 1201.55 900.05 2244.73 1075.08 0.00 0.00 0.00
November 1507.47 852.93 654.54 1402.45 1401.98 0.00 0.00 0.00
December 1404.16 727.82 676.34 1044.48 2034.10 0.00 0.00 0.00
                 
Annual Sum or Average 1826.84 803.80 1023.04 1929.48 1146.95 0.00 0.00 0.00
Minimum of Months 1404.16 343.49 654.54 1044.48 296.63 0.00 0.00 0.00
Maximum of Months 2336.72 1312.81 1296.92 2695.18 2080.96 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2181.39 1273.98 907.42 1733.12 2847.03 0.00 0.00 0.00
February 2470.38 1181.49 1288.89 1939.46 2765.22 0.00 0.00 0.00
March 3035.53 1705.42 1330.11 2969.37 2026.54 0.00 0.00 0.00
April 2510.59 1000.96 1509.63 2579.52 1580.70 0.00 0.00 0.00
May 2213.90 652.65 1561.25 2509.44 1017.17 0.00 0.00 0.00
June 2130.99 446.21 1684.78 2697.06 622.41 0.00 0.00 0.00
July 2166.01 513.13 1652.89 3037.01 395.78 0.00 0.00 0.00
August 2425.40 769.64 1655.76 3313.58 536.20 0.00 0.00 0.00
September 2839.00 1377.79 1461.21 3560.68 905.34 0.00 0.00 0.00
October 2730.10 1560.88 1169.21 2951.95 1480.51 0.00 0.00 0.00
November 1958.28 1108.00 850.28 1841.39 1943.29 0.00 0.00 0.00
December 1824.08 945.47 878.60 1371.25 2794.40 0.00 0.00 0.00
                 
Annual Sum or Average 2373.16 1044.18 1328.98 2545.54 1569.88 0.00 0.00 0.00
Minimum of Months 1824.08 446.21 850.28 1371.25 395.78 0.00 0.00 0.00
Maximum of Months 3035.53 1705.42 1684.78 3560.68 2847.03 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 117.90 68.86 49.05 94.81 147.47 0.00 0.00 0.00
February 133.52 63.86 69.66 105.05 145.02 0.00 0.00 0.00
March 164.07 92.18 71.89 160.63 102.06 0.00 0.00 0.00
April 135.70 54.10 81.60 139.64 77.43 0.00 0.00 0.00
May 119.66 35.28 84.39 135.81 46.53 0.00 0.00 0.00
June 115.18 24.12 91.06 146.63 25.98 0.00 0.00 0.00
July 117.07 27.73 89.34 167.02 14.48 0.00 0.00 0.00
August 131.09 41.60 89.49 181.13 20.72 0.00 0.00 0.00
September 153.45 74.47 78.98 194.02 38.94 0.00 0.00 0.00
October 147.56 84.37 63.20 161.44 68.97 0.00 0.00 0.00
November 105.84 59.89 45.96 101.48 93.46 0.00 0.00 0.00
December 98.59 51.10 47.49 74.84 144.03 0.00 0.00 0.00
                 
Annual Sum or Average 128.27 56.44 71.83 138.74 76.73 0.00 0.00 0.00
Minimum of Months 98.59 24.12 45.96 74.84 14.48 0.00 0.00 0.00
Maximum of Months 164.07 92.18 91.06 194.02 147.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 80.51 18.98 61.53 21.30 307.06 0.00 0.00 0.00
February 130.74 33.86 96.88 53.84 290.41 0.00 0.00 0.00
March 204.69 87.90 116.78 161.15 197.52 0.00 0.00 0.00
April 249.53 102.23 147.31 234.76 139.32 0.00 0.00 0.00
May 294.70 133.32 161.37 327.75 84.01 0.00 0.00 0.00
June 355.12 166.87 188.25 444.15 47.34 0.00 0.00 0.00
July 317.43 138.95 178.48 428.31 26.88 0.00 0.00 0.00
August 286.95 121.63 165.32 378.02 38.44 0.00 0.00 0.00
September 225.59 97.31 128.28 265.37 72.28 0.00 0.00 0.00
October 146.90 52.03 94.86 129.96 133.51 0.00 0.00 0.00
November 86.55 24.83 61.73 50.84 184.44 0.00 0.00 0.00
December 74.89 16.14 58.76 19.90 294.75 0.00 0.00 0.00
                 
Annual Sum or Average 204.80 83.08 121.73 210.46 150.63 0.00 0.00 0.00
Minimum of Months 74.89 16.14 58.76 19.90 26.88 0.00 0.00 0.00
Maximum of Months 355.12 166.87 188.25 444.15 307.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 27.38 0.00 27.38 0.11 172.04 0.00 0.00 0.00
February 41.72 0.00 41.72 2.21 163.08 0.00 0.00 0.00
March 50.60 0.00 50.60 17.53 112.35 0.00 0.00 0.00
April 64.61 0.36 64.25 36.43 75.97 0.00 0.00 0.00
May 74.85 3.11 71.74 63.20 42.60 0.00 0.00 0.00
June 90.29 7.82 82.47 103.05 23.56 0.00 0.00 0.00
July 84.10 5.84 78.26 112.73 13.31 0.00 0.00 0.00
August 72.74 1.43 71.31 91.82 19.60 0.00 0.00 0.00
September 55.08 0.03 55.05 54.29 38.60 0.00 0.00 0.00
October 41.14 0.00 41.14 22.71 72.45 0.00 0.00 0.00
November 27.65 0.00 27.65 6.56 100.24 0.00 0.00 0.00
December 25.63 0.00 25.63 0.40 164.32 0.00 0.00 0.00
                 
Annual Sum or Average 54.70 1.56 53.15 42.84 82.78 0.00 0.00 0.00
Minimum of Months 25.63 0.00 25.63 0.11 13.31 0.00 0.00 0.00
Maximum of Months 90.29 7.82 82.47 112.73 172.04 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 80.51 18.98 61.53 22.45 304.95 0.00 0.00 0.00
February 130.74 33.86 96.88 55.80 288.62 0.00 0.00 0.00
March 204.69 87.90 116.78 165.64 194.79 0.00 0.00 0.00
April 249.53 102.23 147.31 238.47 138.02 0.00 0.00 0.00
May 294.70 133.32 161.37 330.10 83.41 0.00 0.00 0.00
June 355.12 166.87 188.25 445.35 47.07 0.00 0.00 0.00
July 317.43 138.95 178.48 429.50 26.60 0.00 0.00 0.00
August 286.95 121.63 165.32 379.91 37.95 0.00 0.00 0.00
September 225.59 97.31 128.28 268.96 71.10 0.00 0.00 0.00
October 146.90 52.03 94.86 134.38 131.42 0.00 0.00 0.00
November 86.55 24.83 61.73 53.73 182.28 0.00 0.00 0.00
December 74.89 16.14 58.76 21.04 293.03 0.00 0.00 0.00
                 
Annual Sum or Average 204.80 83.08 121.73 212.96 149.24 0.00 0.00 0.00
Minimum of Months 74.89 16.14 58.76 21.04 26.60 0.00 0.00 0.00
Maximum of Months 355.12 166.87 188.25 445.35 304.95 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 94.30 55.08 39.23 75.73 113.12 0.00 0.00 0.00
February 106.80 51.08 55.72 84.49 110.96 0.00 0.00 0.00
March 131.23 73.73 57.50 127.35 82.07 0.00 0.00 0.00
April 108.54 43.27 65.26 110.76 63.93 0.00 0.00 0.00
May 95.71 28.21 67.50 106.78 42.01 0.00 0.00 0.00
June 92.13 19.29 72.84 115.78 24.92 0.00 0.00 0.00
July 93.64 22.18 71.46 131.47 15.36 0.00 0.00 0.00
August 104.85 33.27 71.58 142.93 21.36 0.00 0.00 0.00
September 122.73 59.56 63.17 152.56 37.41 0.00 0.00 0.00
October 118.03 67.48 50.55 125.96 61.20 0.00 0.00 0.00
November 84.66 47.90 36.76 80.22 75.47 0.00 0.00 0.00
December 78.86 40.87 37.98 60.04 109.92 0.00 0.00 0.00
                 
Annual Sum or Average 102.60 45.14 57.45 109.65 62.89 0.00 0.00 0.00
Minimum of Months 78.86 19.29 36.76 60.04 15.36 0.00 0.00 0.00
Maximum of Months 131.23 73.73 72.84 152.56 113.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 21.91 0.00 21.91 0.02 143.49 0.00 0.00 0.00
February 33.38 0.00 33.38 1.31 135.54 0.00 0.00 0.00
March 40.49 0.00 40.49 13.57 91.86 0.00 0.00 0.00
April 51.70 0.29 51.40 29.74 61.40 0.00 0.00 0.00
May 59.89 2.49 57.40 53.54 33.57 0.00 0.00 0.00
June 72.24 6.26 65.98 87.26 17.55 0.00 0.00 0.00
July 67.28 4.67 62.61 95.28 9.32 0.00 0.00 0.00
August 58.20 1.14 57.05 78.04 14.29 0.00 0.00 0.00
September 44.07 0.02 44.05 46.20 29.76 0.00 0.00 0.00
October 32.92 0.00 32.92 18.12 59.42 0.00 0.00 0.00
November 22.12 0.00 22.12 4.75 84.08 0.00 0.00 0.00
December 20.51 0.00 20.51 0.21 137.36 0.00 0.00 0.00
                 
Annual Sum or Average 43.77 1.25 42.52 35.88 67.80 0.00 0.00 0.00
Minimum of Months 20.51 0.00 20.51 0.02 9.32 0.00 0.00 0.00
Maximum of Months 72.24 6.26 65.98 95.28 143.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 93.49 30.11 63.38 33.23 297.57 0.00 0.00 0.00
February 138.03 41.81 96.22 60.44 281.65 0.00 0.00 0.00
March 198.05 83.29 114.76 151.81 193.70 0.00 0.00 0.00
April 260.70 115.16 145.55 244.66 134.43 0.00 0.00 0.00
May 292.09 129.23 162.86 322.50 80.20 0.00 0.00 0.00
June 325.94 143.91 182.03 404.15 44.01 0.00 0.00 0.00
July 313.03 137.64 175.38 421.32 24.51 0.00 0.00 0.00
August 282.73 118.43 164.30 370.55 36.18 0.00 0.00 0.00
September 235.52 104.48 131.04 276.95 69.25 0.00 0.00 0.00
October 159.73 65.99 93.75 143.38 129.80 0.00 0.00 0.00
November 90.55 29.00 61.56 54.68 181.16 0.00 0.00 0.00
December 72.95 15.11 57.84 16.93 291.16 0.00 0.00 0.00
                 
Annual Sum or Average 205.54 84.71 120.82 209.20 146.30 0.00 0.00 0.00
Minimum of Months 72.95 15.11 57.84 16.93 24.51 0.00 0.00 0.00
Maximum of Months 325.94 143.91 182.03 421.32 297.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 117.90 68.86 49.05 94.41 147.51 0.00 0.00 0.00
February 133.52 63.86 69.66 104.55 144.96 0.00 0.00 0.00
March 164.07 92.18 71.89 159.64 101.45 0.00 0.00 0.00
April 135.70 54.10 81.60 138.16 77.01 0.00 0.00 0.00
May 119.66 35.28 84.39 134.71 46.02 0.00 0.00 0.00
June 115.18 24.12 91.06 146.08 25.36 0.00 0.00 0.00
July 117.07 27.73 89.34 166.37 14.09 0.00 0.00 0.00
August 131.09 41.60 89.49 180.60 20.43 0.00 0.00 0.00
September 153.45 74.47 78.98 193.11 38.58 0.00 0.00 0.00
October 147.56 84.37 63.20 160.46 68.84 0.00 0.00 0.00
November 105.84 59.89 45.96 101.19 93.39 0.00 0.00 0.00
December 98.59 51.10 47.49 74.73 143.96 0.00 0.00 0.00
                 
Annual Sum or Average 128.27 56.44 71.83 138.03 76.44 0.00 0.00 0.00
Minimum of Months 98.59 24.12 45.96 74.73 14.09 0.00 0.00 0.00
Maximum of Months 164.07 92.18 91.06 193.11 147.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 27.38 0.00 27.38 0.10 172.23 0.00 0.00 0.00
February 41.72 0.00 41.72 2.11 163.21 0.00 0.00 0.00
March 50.60 0.00 50.60 16.89 112.03 0.00 0.00 0.00
April 64.61 0.36 64.25 35.07 75.89 0.00 0.00 0.00
May 74.85 3.11 71.74 62.00 42.34 0.00 0.00 0.00
June 90.29 7.82 82.47 102.42 23.04 0.00 0.00 0.00
July 84.10 5.84 78.26 112.06 12.98 0.00 0.00 0.00
August 72.74 1.43 71.31 91.16 19.30 0.00 0.00 0.00
September 55.08 0.03 55.05 53.06 38.33 0.00 0.00 0.00
October 41.14 0.00 41.14 21.79 72.43 0.00 0.00 0.00
November 27.65 0.00 27.65 6.29 100.18 0.00 0.00 0.00
December 25.63 0.00 25.63 0.38 164.38 0.00 0.00 0.00
                 
Annual Sum or Average 54.70 1.56 53.15 42.19 82.63 0.00 0.00 0.00
Minimum of Months 25.63 0.00 25.63 0.10 12.98 0.00 0.00 0.00
Maximum of Months 90.29 7.82 82.47 112.06 172.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 93.49 30.11 63.38 34.12 294.92 0.00 0.00 0.00
February 138.03 41.81 96.22 62.13 279.37 0.00 0.00 0.00
March 198.05 83.29 114.76 155.14 189.72 0.00 0.00 0.00
April 260.70 115.16 145.55 247.88 132.98 0.00 0.00 0.00
May 292.09 129.23 162.86 324.32 79.59 0.00 0.00 0.00
June 325.94 143.91 182.03 405.17 43.77 0.00 0.00 0.00
July 313.03 137.64 175.38 422.48 24.28 0.00 0.00 0.00
August 282.73 118.43 164.30 372.30 35.70 0.00 0.00 0.00
September 235.52 104.48 131.04 279.88 68.06 0.00 0.00 0.00
October 159.73 65.99 93.75 147.41 127.54 0.00 0.00 0.00
November 90.55 29.00 61.56 56.93 178.42 0.00 0.00 0.00
December 72.95 15.11 57.84 17.47 288.88 0.00 0.00 0.00
                 
Annual Sum or Average 205.54 84.71 120.82 211.25 144.60 0.00 0.00 0.00
Minimum of Months 72.95 15.11 57.84 17.47 24.28 0.00 0.00 0.00
Maximum of Months 325.94 143.91 182.03 422.48 294.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 34.68 0.00 34.68 0.00 235.56 0.00 0.00 0.00
February 52.84 0.00 52.84 1.37 222.08 0.00 0.00 0.00
March 64.08 0.00 64.08 20.17 151.17 0.00 0.00 0.00
April 81.83 0.46 81.36 45.11 101.92 0.00 0.00 0.00
May 94.80 3.94 90.86 80.12 59.92 0.00 0.00 0.00
June 114.35 9.91 104.44 129.48 35.89 0.00 0.00 0.00
July 106.50 7.40 99.11 139.04 23.09 0.00 0.00 0.00
August 92.12 1.81 90.31 113.21 32.73 0.00 0.00 0.00
September 69.76 0.04 69.72 66.68 57.78 0.00 0.00 0.00
October 52.10 0.00 52.10 26.47 100.04 0.00 0.00 0.00
November 35.01 0.00 35.01 6.73 138.08 0.00 0.00 0.00
December 32.46 0.00 32.46 0.25 225.22 0.00 0.00 0.00
                 
Annual Sum or Average 69.28 1.97 67.31 52.70 114.76 0.00 0.00 0.00
Minimum of Months 32.46 0.00 32.46 0.00 23.09 0.00 0.00 0.00
Maximum of Months 114.35 9.91 104.44 139.04 235.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 12.78 0.00 12.78 0.00 86.84 0.00 0.00 0.00
February 19.48 0.00 19.48 0.50 81.87 0.00 0.00 0.00
March 23.62 0.00 23.62 7.44 55.73 0.00 0.00 0.00
April 30.16 0.17 29.99 16.63 37.57 0.00 0.00 0.00
May 34.95 1.45 33.49 29.53 22.09 0.00 0.00 0.00
June 42.15 3.65 38.50 47.73 13.23 0.00 0.00 0.00
July 39.26 2.73 36.53 51.25 8.51 0.00 0.00 0.00
August 33.96 0.67 33.29 41.73 12.07 0.00 0.00 0.00
September 25.72 0.01 25.70 24.58 21.30 0.00 0.00 0.00
October 19.21 0.00 19.21 9.76 36.88 0.00 0.00 0.00
November 12.91 0.00 12.91 2.48 50.90 0.00 0.00 0.00
December 11.97 0.00 11.97 0.09 83.03 0.00 0.00 0.00
                 
Annual Sum or Average 25.54 0.73 24.81 19.43 42.31 0.00 0.00 0.00
Minimum of Months 11.97 0.00 11.97 0.00 8.51 0.00 0.00 0.00
Maximum of Months 42.15 3.65 38.50 51.25 86.84 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 55.01 32.13 22.88 42.99 73.08 0.00 0.00 0.00
February 62.30 29.80 32.51 47.59 71.43 0.00 0.00 0.00
March 76.55 43.01 33.54 74.78 49.61 0.00 0.00 0.00
April 63.32 25.24 38.07 65.55 37.80 0.00 0.00 0.00
May 55.83 16.46 39.37 63.93 23.83 0.00 0.00 0.00
June 53.74 11.25 42.49 68.49 14.58 0.00 0.00 0.00
July 54.63 12.94 41.69 76.97 9.24 0.00 0.00 0.00
August 61.17 19.41 41.76 83.91 12.65 0.00 0.00 0.00
September 71.60 34.75 36.85 90.48 21.10 0.00 0.00 0.00
October 68.85 39.36 29.49 75.43 34.43 0.00 0.00 0.00
November 49.39 27.94 21.44 46.97 46.48 0.00 0.00 0.00
December 46.00 23.84 22.16 33.88 71.68 0.00 0.00 0.00
                 
Annual Sum or Average 59.85 26.33 33.52 64.34 38.65 0.00 0.00 0.00
Minimum of Months 46.00 11.25 21.44 33.88 9.24 0.00 0.00 0.00
Maximum of Months 76.55 43.01 42.49 90.48 73.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 149.32 87.20 62.11 116.69 198.36 0.00 0.00 0.00
February 169.10 80.87 88.23 129.16 193.89 0.00 0.00 0.00
March 207.78 116.74 91.05 202.96 134.65 0.00 0.00 0.00
April 171.85 68.52 103.34 177.90 102.60 0.00 0.00 0.00
May 151.54 44.67 106.87 173.52 64.67 0.00 0.00 0.00
June 145.87 30.54 115.33 185.90 39.58 0.00 0.00 0.00
July 148.27 35.12 113.14 208.90 25.08 0.00 0.00 0.00
August 166.02 52.68 113.34 227.75 34.32 0.00 0.00 0.00
September 194.33 94.31 100.02 245.59 57.27 0.00 0.00 0.00
October 186.88 106.84 80.03 204.73 93.44 0.00 0.00 0.00
November 134.05 75.84 58.20 127.48 126.15 0.00 0.00 0.00
December 124.86 64.72 60.14 91.95 194.54 0.00 0.00 0.00
                 
Annual Sum or Average 162.45 71.47 90.97 174.64 104.92 0.00 0.00 0.00
Minimum of Months 124.86 30.54 58.20 91.95 25.08 0.00 0.00 0.00
Maximum of Months 207.78 116.74 115.33 245.59 198.36 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 117.90 68.86 49.05 94.46 147.37 0.00 0.00 0.00
February 133.52 63.86 69.66 104.34 145.23 0.00 0.00 0.00
March 164.07 92.18 71.89 159.97 101.75 0.00 0.00 0.00
April 135.70 54.10 81.60 138.81 77.11 0.00 0.00 0.00
May 119.66 35.28 84.39 134.74 46.09 0.00 0.00 0.00
June 115.18 24.12 91.06 145.43 25.55 0.00 0.00 0.00
July 117.07 27.73 89.34 165.88 14.04 0.00 0.00 0.00
August 131.09 41.60 89.49 180.05 20.19 0.00 0.00 0.00
September 153.45 74.47 78.98 193.11 38.22 0.00 0.00 0.00
October 147.56 84.37 63.20 160.99 68.19 0.00 0.00 0.00
November 105.84 59.89 45.96 101.29 92.75 0.00 0.00 0.00
December 98.59 51.10 47.49 74.45 144.02 0.00 0.00 0.00
                 
Annual Sum or Average 128.27 56.44 71.83 137.99 76.35 0.00 0.00 0.00
Minimum of Months 98.59 24.12 45.96 74.45 14.04 0.00 0.00 0.00
Maximum of Months 164.07 92.18 91.06 193.11 147.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 80.51 18.98 61.53 21.26 307.18 0.00 0.00 0.00
February 130.74 33.86 96.88 53.46 290.90 0.00 0.00 0.00
March 204.69 87.90 116.78 160.38 196.80 0.00 0.00 0.00
April 249.53 102.23 147.31 233.16 138.52 0.00 0.00 0.00
May 294.70 133.32 161.37 325.40 83.06 0.00 0.00 0.00
June 355.12 166.87 188.25 440.95 46.51 0.00 0.00 0.00
July 317.43 138.95 178.48 425.69 26.05 0.00 0.00 0.00
August 286.95 121.63 165.32 375.97 37.44 0.00 0.00 0.00
September 225.59 97.31 128.28 263.98 70.81 0.00 0.00 0.00
October 146.90 52.03 94.86 129.76 131.91 0.00 0.00 0.00
November 86.55 24.83 61.73 51.07 182.86 0.00 0.00 0.00
December 74.89 16.14 58.76 19.82 294.80 0.00 0.00 0.00
                 
Annual Sum or Average 204.80 83.08 121.73 209.26 149.86 0.00 0.00 0.00
Minimum of Months 74.89 16.14 58.76 19.82 26.05 0.00 0.00 0.00
Maximum of Months 355.12 166.87 188.25 440.95 307.18 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 27.38 0.00 27.38 0.11 172.00 0.00 0.00 0.00
February 41.72 0.00 41.72 2.21 163.04 0.00 0.00 0.00
March 50.60 0.00 50.60 17.63 111.97 0.00 0.00 0.00
April 64.61 0.36 64.25 36.41 75.49 0.00 0.00 0.00
May 74.85 3.11 71.74 62.79 42.08 0.00 0.00 0.00
June 90.29 7.82 82.47 102.29 23.19 0.00 0.00 0.00
July 84.10 5.84 78.26 112.09 12.94 0.00 0.00 0.00
August 72.74 1.43 71.31 91.41 19.10 0.00 0.00 0.00
September 55.08 0.03 55.05 54.25 37.75 0.00 0.00 0.00
October 41.14 0.00 41.14 23.16 71.41 0.00 0.00 0.00
November 27.65 0.00 27.65 6.83 99.17 0.00 0.00 0.00
December 25.63 0.00 25.63 0.41 164.04 0.00 0.00 0.00
                 
Annual Sum or Average 54.70 1.56 53.15 42.71 82.28 0.00 0.00 0.00
Minimum of Months 25.63 0.00 25.63 0.11 12.94 0.00 0.00 0.00
Maximum of Months 90.29 7.82 82.47 112.09 172.00 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 80.51 18.98 61.53 22.34 305.24 0.00 0.00 0.00
February 130.74 33.86 96.88 55.32 289.20 0.00 0.00 0.00
March 204.69 87.90 116.78 164.90 194.20 0.00 0.00 0.00
April 249.53 102.23 147.31 237.16 137.13 0.00 0.00 0.00
May 294.70 133.32 161.37 327.90 82.39 0.00 0.00 0.00
June 355.12 166.87 188.25 442.18 46.23 0.00 0.00 0.00
July 317.43 138.95 178.48 426.92 25.77 0.00 0.00 0.00
August 286.95 121.63 165.32 377.98 36.91 0.00 0.00 0.00
September 225.59 97.31 128.28 267.92 69.45 0.00 0.00 0.00
October 146.90 52.03 94.86 134.66 129.60 0.00 0.00 0.00
November 86.55 24.83 61.73 54.12 180.73 0.00 0.00 0.00
December 74.89 16.14 58.76 20.92 293.17 0.00 0.00 0.00
                 
Annual Sum or Average 204.80 83.08 121.73 211.87 148.46 0.00 0.00 0.00
Minimum of Months 74.89 16.14 58.76 20.92 25.77 0.00 0.00 0.00
Maximum of Months 355.12 166.87 188.25 442.18 305.24 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 172.92 100.99 71.93 132.97 223.09 0.00 0.00 0.00
February 195.83 93.66 102.17 147.51 219.12 0.00 0.00 0.00
March 240.62 135.19 105.44 228.09 153.47 0.00 0.00 0.00
April 199.01 79.35 119.67 200.51 114.68 0.00 0.00 0.00
May 175.50 51.73 123.76 197.91 67.13 0.00 0.00 0.00
June 168.92 35.37 133.55 216.45 35.94 0.00 0.00 0.00
July 171.70 40.68 131.02 246.40 19.38 0.00 0.00 0.00
August 192.26 61.01 131.25 265.92 28.78 0.00 0.00 0.00
September 225.05 109.22 115.83 281.85 56.50 0.00 0.00 0.00
October 216.41 123.73 92.68 231.13 103.84 0.00 0.00 0.00
November 155.23 87.83 67.40 143.72 142.14 0.00 0.00 0.00
December 144.59 74.95 69.65 104.89 217.72 0.00 0.00 0.00
                 
Annual Sum or Average 188.12 82.77 105.35 200.09 114.60 0.00 0.00 0.00
Minimum of Months 144.59 35.37 67.40 104.89 19.38 0.00 0.00 0.00
Maximum of Months 240.62 135.19 133.55 281.85 223.09 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 191.67 0.00 191.67 0.00 1420.47 0.00 0.00 0.00
February 292.03 0.00 292.03 3.78 1342.97 0.00 0.00 0.00
March 354.19 0.01 354.19 87.87 939.91 0.00 0.00 0.00
April 452.26 2.55 449.71 205.11 649.48 0.00 0.00 0.00
May 523.95 21.77 502.18 390.39 375.37 0.00 0.00 0.00
June 632.02 54.76 577.26 672.60 217.85 0.00 0.00 0.00
July 588.64 40.87 547.77 740.54 137.47 0.00 0.00 0.00
August 509.14 10.01 499.13 600.88 193.75 0.00 0.00 0.00
September 385.55 0.22 385.33 339.72 352.13 0.00 0.00 0.00
October 287.99 0.00 287.99 116.04 640.75 0.00 0.00 0.00
November 193.52 0.00 193.52 24.23 886.99 0.00 0.00 0.00
December 179.40 0.00 179.40 0.69 1366.82 0.00 0.00 0.00
                 
Annual Sum or Average 382.91 10.90 372.01 266.81 707.14 0.00 0.00 0.00
Minimum of Months 179.40 0.00 179.40 0.00 137.47 0.00 0.00 0.00
Maximum of Months 632.02 54.76 577.26 740.54 1420.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 191.67 0.00 191.67 0.00 1458.50 0.00 0.00 0.00
February 292.03 0.00 292.03 2.65 1380.46 0.00 0.00 0.00
March 354.19 0.01 354.19 81.73 966.20 0.00 0.00 0.00
April 452.26 2.55 449.71 194.29 666.64 0.00 0.00 0.00
May 523.95 21.77 502.18 378.47 385.03 0.00 0.00 0.00
June 632.02 54.76 577.26 662.46 223.68 0.00 0.00 0.00
July 588.64 40.87 547.77 732.14 142.04 0.00 0.00 0.00
August 509.14 10.01 499.13 592.76 199.76 0.00 0.00 0.00
September 385.55 0.22 385.33 331.10 362.15 0.00 0.00 0.00
October 287.99 0.00 287.99 107.84 659.86 0.00 0.00 0.00
November 193.52 0.00 193.52 21.45 916.23 0.00 0.00 0.00
December 179.40 0.00 179.40 0.52 1404.11 0.00 0.00 0.00
                 
Annual Sum or Average 382.91 10.90 372.01 260.41 727.11 0.00 0.00 0.00
Minimum of Months 179.40 0.00 179.40 0.00 142.04 0.00 0.00 0.00
Maximum of Months 632.02 54.76 577.26 732.14 1458.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 27.38 0.00 27.38 0.10 182.48 0.00 0.00 0.00
February 41.72 0.00 41.72 1.74 172.89 0.00 0.00 0.00
March 50.60 0.00 50.60 18.98 119.77 0.00 0.00 0.00
April 64.61 0.36 64.25 41.73 83.42 0.00 0.00 0.00
May 74.85 3.11 71.74 75.57 49.30 0.00 0.00 0.00
June 90.29 7.82 82.47 121.15 30.03 0.00 0.00 0.00
July 84.10 5.84 78.26 133.17 19.12 0.00 0.00 0.00
August 72.74 1.43 71.31 110.96 25.40 0.00 0.00 0.00
September 55.08 0.03 55.05 67.10 43.54 0.00 0.00 0.00
October 41.14 0.00 41.14 26.39 78.99 0.00 0.00 0.00
November 27.65 0.00 27.65 7.18 109.15 0.00 0.00 0.00
December 25.63 0.00 25.63 0.41 175.15 0.00 0.00 0.00
                 
Annual Sum or Average 54.70 1.56 53.15 50.68 90.36 0.00 0.00 0.00
Minimum of Months 25.63 0.00 25.63 0.10 19.12 0.00 0.00 0.00
Maximum of Months 90.29 7.82 82.47 133.17 182.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 186.96 60.21 126.75 68.82 626.94 0.00 0.00 0.00
February 276.03 83.61 192.42 124.27 596.59 0.00 0.00 0.00
March 396.08 166.56 229.51 321.58 410.57 0.00 0.00 0.00
April 521.37 230.30 291.07 524.44 297.39 0.00 0.00 0.00
May 584.14 258.44 325.70 700.04 185.49 0.00 0.00 0.00
June 651.84 287.81 364.03 880.44 112.91 0.00 0.00 0.00
July 626.01 275.27 350.74 923.99 71.76 0.00 0.00 0.00
August 565.42 236.84 328.58 818.85 94.92 0.00 0.00 0.00
September 471.01 208.94 262.07 616.53 157.89 0.00 0.00 0.00
October 319.44 131.96 187.48 316.36 281.23 0.00 0.00 0.00
November 181.09 57.99 123.11 118.89 391.95 0.00 0.00 0.00
December 145.88 30.22 115.66 35.54 620.44 0.00 0.00 0.00
                 
Annual Sum or Average 411.04 169.42 241.63 455.97 319.29 0.00 0.00 0.00
Minimum of Months 145.88 30.22 115.66 35.54 71.76 0.00 0.00 0.00
Maximum of Months 651.84 287.81 364.03 923.99 626.94 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 117.90 68.86 49.05 94.82 155.97 0.00 0.00 0.00
February 133.52 63.86 69.66 104.27 153.97 0.00 0.00 0.00
March 164.07 92.18 71.89 165.34 108.53 0.00 0.00 0.00
April 135.70 54.10 81.60 147.25 84.47 0.00 0.00 0.00
May 119.66 35.28 84.39 148.65 52.68 0.00 0.00 0.00
June 115.18 24.12 91.06 164.45 32.10 0.00 0.00 0.00
July 117.07 27.73 89.34 187.20 20.12 0.00 0.00 0.00
August 131.09 41.60 89.49 200.78 26.14 0.00 0.00 0.00
September 153.45 74.47 78.98 209.52 43.58 0.00 0.00 0.00
October 147.56 84.37 63.20 169.12 75.37 0.00 0.00 0.00
November 105.84 59.89 45.96 104.14 102.22 0.00 0.00 0.00
December 98.59 51.10 47.49 74.51 153.97 0.00 0.00 0.00
                 
Annual Sum or Average 128.27 56.44 71.83 147.76 83.72 0.00 0.00 0.00
Minimum of Months 98.59 24.12 45.96 74.51 20.12 0.00 0.00 0.00
Maximum of Months 164.07 92.18 91.06 209.52 155.97 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 34.68 0.00 34.68 0.00 239.71 0.00 0.00 0.00
February 52.84 0.00 52.84 1.06 225.90 0.00 0.00 0.00
March 64.08 0.00 64.08 18.57 154.36 0.00 0.00 0.00
April 81.83 0.46 81.36 42.32 103.68 0.00 0.00 0.00
May 94.80 3.94 90.86 76.61 60.84 0.00 0.00 0.00
June 114.35 9.91 104.44 125.01 37.09 0.00 0.00 0.00
July 106.50 7.40 99.11 134.40 24.38 0.00 0.00 0.00
August 92.12 1.81 90.31 109.59 33.89 0.00 0.00 0.00
September 69.76 0.04 69.72 63.99 58.34 0.00 0.00 0.00
October 52.10 0.00 52.10 24.50 101.80 0.00 0.00 0.00
November 35.01 0.00 35.01 5.93 141.37 0.00 0.00 0.00
December 32.46 0.00 32.46 0.21 229.13 0.00 0.00 0.00
                 
Annual Sum or Average 69.28 1.97 67.31 50.49 117.01 0.00 0.00 0.00
Minimum of Months 32.46 0.00 32.46 0.00 24.38 0.00 0.00 0.00
Maximum of Months 114.35 9.91 104.44 134.40 239.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 31.03 0.00 31.03 0.00 214.47 0.00 0.00 0.00
February 47.27 0.00 47.27 0.95 202.11 0.00 0.00 0.00
March 57.34 0.00 57.33 16.61 138.11 0.00 0.00 0.00
April 73.21 0.41 72.80 37.87 92.76 0.00 0.00 0.00
May 84.81 3.52 81.29 68.54 54.44 0.00 0.00 0.00
June 102.31 8.86 93.44 111.84 33.18 0.00 0.00 0.00
July 95.29 6.62 88.67 120.25 21.81 0.00 0.00 0.00
August 82.42 1.62 80.80 98.05 30.32 0.00 0.00 0.00
September 62.41 0.04 62.38 57.26 52.20 0.00 0.00 0.00
October 46.62 0.00 46.62 21.92 91.08 0.00 0.00 0.00
November 31.33 0.00 31.33 5.31 126.48 0.00 0.00 0.00
December 29.04 0.00 29.04 0.18 204.99 0.00 0.00 0.00
                 
Annual Sum or Average 61.98 1.76 60.22 45.17 104.68 0.00 0.00 0.00
Minimum of Months 29.04 0.00 29.04 0.00 21.81 0.00 0.00 0.00
Maximum of Months 102.31 8.86 93.44 120.25 214.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 440.17 257.07 183.10 338.22 594.14 0.00 0.00 0.00
February 498.48 238.41 260.08 372.52 580.98 0.00 0.00 0.00
March 612.52 344.13 268.40 586.91 404.15 0.00 0.00 0.00
April 506.60 201.98 304.62 512.78 308.19 0.00 0.00 0.00
May 446.73 131.69 315.04 499.21 194.50 0.00 0.00 0.00
June 430.00 90.04 339.96 533.40 120.74 0.00 0.00 0.00
July 437.07 103.54 333.53 600.46 78.17 0.00 0.00 0.00
August 489.41 155.30 334.11 658.53 104.92 0.00 0.00 0.00
September 572.87 278.02 294.85 713.40 170.88 0.00 0.00 0.00
October 550.89 314.96 235.93 593.46 280.26 0.00 0.00 0.00
November 395.15 223.58 171.57 368.63 380.90 0.00 0.00 0.00
December 368.07 190.78 177.29 265.71 584.10 0.00 0.00 0.00
                 
Annual Sum or Average 478.87 210.70 268.17 504.37 315.44 0.00 0.00 0.00
Minimum of Months 368.07 90.04 171.57 265.71 78.17 0.00 0.00 0.00
Maximum of Months 612.52 344.13 339.96 713.40 594.14 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.159720E+10 0.932795E+09 0.664402E+09 0.127218E+10 0.194623E+10
February 0.163375E+10 0.781360E+09 0.852386E+09 0.128562E+10 0.171204E+10
March 0.222259E+10 0.124869E+10 0.973896E+09 0.216995E+10 0.135174E+10
April 0.177893E+10 0.709253E+09 0.106968E+10 0.183473E+10 0.987865E+09
May 0.162100E+10 0.477862E+09 0.114314E+10 0.185493E+10 0.625677E+09
June 0.150996E+10 0.316175E+09 0.119379E+10 0.191809E+10 0.370867E+09
July 0.158594E+10 0.375708E+09 0.121023E+10 0.221104E+10 0.246777E+09
August 0.177586E+10 0.563521E+09 0.121233E+10 0.241069E+10 0.337344E+09
September 0.201164E+10 0.976267E+09 0.103537E+10 0.251553E+10 0.544378E+09
October 0.199895E+10 0.114287E+10 0.856089E+09 0.216889E+10 0.941699E+09
November 0.138759E+10 0.785100E+09 0.602486E+09 0.131493E+10 0.121951E+10
December 0.133558E+10 0.692268E+09 0.643307E+09 0.100860E+10 0.189732E+10
           
Annual Sum or Average 0.204590E+11 0.900187E+10 0.114571E+11 0.219652E+11 0.121814E+11
Minimum of Months 0.133558E+10 0.316175E+09 0.602486E+09 0.100860E+10 0.246777E+09
Maximum of Months 0.222259E+10 0.124869E+10 0.121233E+10 0.251553E+10 0.194623E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.449760E+10 0.262669E+10 0.187091E+10 0.353321E+10 0.557366E+10
February 0.460052E+10 0.220026E+10 0.240026E+10 0.356784E+10 0.489856E+10
March 0.625866E+10 0.351624E+10 0.274243E+10 0.601905E+10 0.398314E+10
April 0.500936E+10 0.199721E+10 0.301215E+10 0.507024E+10 0.298521E+10
May 0.456462E+10 0.134563E+10 0.321899E+10 0.509729E+10 0.197662E+10
June 0.425196E+10 0.890329E+09 0.336163E+10 0.528905E+10 0.118824E+10
July 0.446589E+10 0.105797E+10 0.340793E+10 0.613632E+10 0.794505E+09
August 0.500069E+10 0.158684E+10 0.341385E+10 0.670413E+10 0.107669E+10
September 0.566464E+10 0.274910E+10 0.291553E+10 0.698590E+10 0.173209E+10
October 0.562892E+10 0.321823E+10 0.241069E+10 0.601228E+10 0.287948E+10
November 0.390735E+10 0.221079E+10 0.169656E+10 0.363514E+10 0.363393E+10
December 0.376089E+10 0.194938E+10 0.181151E+10 0.279753E+10 0.544812E+10
           
Annual Sum or Average 0.576111E+11 0.253487E+11 0.322624E+11 0.608480E+11 0.361702E+11
Minimum of Months 0.376089E+10 0.890329E+09 0.169656E+10 0.279753E+10 0.794505E+09
Maximum of Months 0.625866E+10 0.351624E+10 0.341385E+10 0.698590E+10 0.557366E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.584264E+10 0.341222E+10 0.243042E+10 0.464200E+10 0.762548E+10
February 0.597634E+10 0.285826E+10 0.311808E+10 0.469195E+10 0.668962E+10
March 0.813036E+10 0.456779E+10 0.356257E+10 0.795317E+10 0.542789E+10
April 0.650744E+10 0.259449E+10 0.391295E+10 0.668612E+10 0.409718E+10
May 0.592970E+10 0.174805E+10 0.418166E+10 0.672129E+10 0.272439E+10
June 0.552353E+10 0.115659E+10 0.436694E+10 0.699079E+10 0.161329E+10
July 0.580145E+10 0.137436E+10 0.442709E+10 0.813433E+10 0.106006E+10
August 0.649618E+10 0.206139E+10 0.443479E+10 0.887510E+10 0.143616E+10
September 0.735869E+10 0.357124E+10 0.378744E+10 0.922928E+10 0.234663E+10
October 0.731229E+10 0.418067E+10 0.313162E+10 0.790649E+10 0.396540E+10
November 0.507587E+10 0.287194E+10 0.220393E+10 0.477289E+10 0.503700E+10
December 0.488561E+10 0.253236E+10 0.235326E+10 0.367275E+10 0.748452E+10
           
Annual Sum or Average 0.748401E+11 0.329294E+11 0.419107E+11 0.802761E+11 0.495076E+11
Minimum of Months 0.488561E+10 0.115659E+10 0.220393E+10 0.367275E+10 0.106006E+10
Maximum of Months 0.813036E+10 0.456779E+10 0.443479E+10 0.922928E+10 0.762548E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.315794E+09 0.184430E+09 0.131364E+09 0.253933E+09 0.394980E+09
February 0.323021E+09 0.154488E+09 0.168532E+09 0.254136E+09 0.350836E+09
March 0.439445E+09 0.246888E+09 0.192557E+09 0.430242E+09 0.273366E+09
April 0.351727E+09 0.140232E+09 0.211496E+09 0.361959E+09 0.200695E+09
May 0.320501E+09 94481581.13 0.226020E+09 0.363742E+09 0.124634E+09
June 0.298548E+09 62513323.98 0.236035E+09 0.380055E+09 67336624.08
July 0.313569E+09 74283889.35 0.239286E+09 0.447334E+09 38778338.40
August 0.351119E+09 0.111418E+09 0.239702E+09 0.485126E+09 55509429.84
September 0.397737E+09 0.193025E+09 0.204712E+09 0.502892E+09 0.100930E+09
October 0.395229E+09 0.225964E+09 0.169265E+09 0.432402E+09 0.184741E+09
November 0.274350E+09 0.155228E+09 0.119122E+09 0.263031E+09 0.242239E+09
December 0.264067E+09 0.136873E+09 0.127193E+09 0.200440E+09 0.385772E+09
           
Annual Sum or Average 0.404511E+10 0.177982E+10 0.226528E+10 0.437529E+10 0.241982E+10
Minimum of Months 0.264067E+09 62513323.98 0.119122E+09 0.200440E+09 38778338.40
Maximum of Months 0.439445E+09 0.246888E+09 0.239702E+09 0.502892E+09 0.394980E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.215644E+09 50829651.37 0.164814E+09 57041335.66 0.822429E+09
February 0.316288E+09 81920195.30 0.234368E+09 0.130240E+09 0.702566E+09
March 0.548232E+09 0.235439E+09 0.312792E+09 0.431617E+09 0.529024E+09
April 0.646790E+09 0.264971E+09 0.381819E+09 0.608491E+09 0.361105E+09
May 0.789316E+09 0.357097E+09 0.432219E+09 0.877846E+09 0.225014E+09
June 0.920469E+09 0.432527E+09 0.487942E+09 0.115123E+10 0.122718E+09
July 0.850202E+09 0.372165E+09 0.478037E+09 0.114719E+10 71986306.79
August 0.768575E+09 0.325787E+09 0.442787E+09 0.101250E+10 0.102957E+09
September 0.584733E+09 0.252239E+09 0.332495E+09 0.687828E+09 0.187358E+09
October 0.393455E+09 0.139370E+09 0.254085E+09 0.348084E+09 0.357584E+09
November 0.224342E+09 64348474.66 0.159993E+09 0.131777E+09 0.478077E+09
December 0.200590E+09 43216876.22 0.157373E+09 53289281.34 0.789467E+09
           
Annual Sum or Average 0.645864E+10 0.261991E+10 0.383873E+10 0.663714E+10 0.475029E+10
Minimum of Months 0.200590E+09 43216876.22 0.157373E+09 53289281.34 71986306.79
Maximum of Months 0.920469E+09 0.432527E+09 0.487942E+09 0.115123E+10 0.822429E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 73340618.97 0.00 73340618.97 302216.86 0.460787E+09
February 0.100930E+09 0.00 0.100930E+09 5357356.75 0.394513E+09
March 0.135530E+09 1952.44 0.135528E+09 46963723.88 0.300931E+09
April 0.167471E+09 944079.53 0.166527E+09 94417355.36 0.196921E+09
May 0.200485E+09 8329113.51 0.192156E+09 0.169287E+09 0.114096E+09
June 0.234036E+09 20276941.55 0.213759E+09 0.267103E+09 61058223.37
July 0.225240E+09 15640458.54 0.209600E+09 0.301941E+09 35652261.86
August 0.194820E+09 3831298.71 0.190988E+09 0.245935E+09 52500867.03
September 0.142770E+09 80807.65 0.142689E+09 0.140708E+09 0.100042E+09
October 0.110196E+09 0.00 0.110196E+09 60830888.62 0.194040E+09
November 71659934.96 0.00 71659934.96 17015536.05 0.259818E+09
December 68644588.40 0.00 68644588.40 1063008.05 0.440107E+09
           
Annual Sum or Average 0.172512E+10 49104651.93 0.167602E+10 0.135092E+10 0.261047E+10
Minimum of Months 68644588.40 0.00 68644588.40 302216.86 35652261.86
Maximum of Months 0.234036E+09 20276941.55 0.213759E+09 0.301941E+09 0.460787E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.215644E+09 50829651.37 0.164814E+09 60116970.23 0.816779E+09
February 0.316288E+09 81920195.30 0.234368E+09 0.134996E+09 0.698239E+09
March 0.548232E+09 0.235439E+09 0.312792E+09 0.443655E+09 0.521738E+09
April 0.646790E+09 0.264971E+09 0.381819E+09 0.618127E+09 0.357738E+09
May 0.789316E+09 0.357097E+09 0.432219E+09 0.884135E+09 0.223403E+09
June 0.920469E+09 0.432527E+09 0.487942E+09 0.115434E+10 0.122015E+09
July 0.850202E+09 0.372165E+09 0.478037E+09 0.115037E+10 71254796.92
August 0.768575E+09 0.325787E+09 0.442787E+09 0.101756E+10 0.101647E+09
September 0.584733E+09 0.252239E+09 0.332495E+09 0.697146E+09 0.184304E+09
October 0.393455E+09 0.139370E+09 0.254085E+09 0.359926E+09 0.351995E+09
November 0.224342E+09 64348474.66 0.159993E+09 0.139256E+09 0.472473E+09
December 0.200590E+09 43216876.22 0.157373E+09 56350216.78 0.784840E+09
           
Annual Sum or Average 0.645864E+10 0.261991E+10 0.383873E+10 0.671599E+10 0.470643E+10
Minimum of Months 0.200590E+09 43216876.22 0.157373E+09 56350216.78 71254796.92
Maximum of Months 0.920469E+09 0.432527E+09 0.487942E+09 0.115434E+10 0.816779E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.252585E+09 0.147514E+09 0.105071E+09 0.202846E+09 0.302978E+09
February 0.258365E+09 0.123566E+09 0.134799E+09 0.204399E+09 0.268438E+09
March 0.351486E+09 0.197471E+09 0.154015E+09 0.341096E+09 0.219821E+09
April 0.281326E+09 0.112163E+09 0.169163E+09 0.287081E+09 0.165718E+09
May 0.256350E+09 75570236.02 0.180780E+09 0.286012E+09 0.112528E+09
June 0.238791E+09 50000715.39 0.188790E+09 0.300112E+09 64582734.22
July 0.250806E+09 59415295.38 0.191390E+09 0.352137E+09 41151440.32
August 0.280840E+09 89116452.96 0.191723E+09 0.382823E+09 57199662.71
September 0.318126E+09 0.154389E+09 0.163737E+09 0.395442E+09 96962163.70
October 0.316120E+09 0.180735E+09 0.135385E+09 0.337384E+09 0.163919E+09
November 0.219436E+09 0.124158E+09 95278945.50 0.207920E+09 0.195629E+09
December 0.211211E+09 0.109477E+09 0.101735E+09 0.160813E+09 0.294397E+09
           
Annual Sum or Average 0.323544E+10 0.142358E+10 0.181187E+10 0.345807E+10 0.198332E+10
Minimum of Months 0.211211E+09 50000715.39 95278945.50 0.160813E+09 41151440.32
Maximum of Months 0.351486E+09 0.197471E+09 0.191723E+09 0.395442E+09 0.302978E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 58680272.54 0.00 58680272.54 49772.54 0.384328E+09
February 80754467.07 0.00 80754467.07 3172756.36 0.327886E+09
March 0.108439E+09 1562.16 0.108437E+09 36356386.28 0.246026E+09
April 0.133995E+09 755363.74 0.133239E+09 77081112.86 0.159158E+09
May 0.160409E+09 6664174.06 0.153745E+09 0.143388E+09 89916080.00
June 0.187254E+09 16223703.50 0.171030E+09 0.226183E+09 45484553.64
July 0.180216E+09 12514025.41 0.167702E+09 0.255203E+09 24972130.91
August 0.155876E+09 3065445.26 0.152811E+09 0.209030E+09 38276202.24
September 0.114231E+09 64654.69 0.114166E+09 0.119746E+09 77140679.45
October 88168115.16 0.00 88168115.16 48544431.66 0.159145E+09
November 57335547.11 0.00 57335547.11 12311471.01 0.217927E+09
December 54922950.10 0.00 54922950.10 571803.25 0.367913E+09
           
Annual Sum or Average 0.138028E+10 39288928.82 0.134099E+10 0.113164E+10 0.213817E+10
Minimum of Months 54922950.10 0.00 54922950.10 49772.54 24972130.91
Maximum of Months 0.187254E+09 16223703.50 0.171030E+09 0.255203E+09 0.384328E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.250400E+09 80644929.94 0.169755E+09 89002058.58 0.797005E+09
February 0.333910E+09 0.101147E+09 0.232763E+09 0.146209E+09 0.681379E+09
March 0.530463E+09 0.223077E+09 0.307386E+09 0.406620E+09 0.518817E+09
April 0.675747E+09 0.298488E+09 0.377259E+09 0.634160E+09 0.348438E+09
May 0.782340E+09 0.346132E+09 0.436208E+09 0.863791E+09 0.214795E+09
June 0.844841E+09 0.373023E+09 0.471818E+09 0.104755E+10 0.114071E+09
July 0.838413E+09 0.368664E+09 0.469749E+09 0.112847E+10 65636023.89
August 0.757266E+09 0.317200E+09 0.440066E+09 0.992475E+09 96898193.34
September 0.610474E+09 0.270807E+09 0.339666E+09 0.717859E+09 0.179491E+09
October 0.427828E+09 0.176737E+09 0.251091E+09 0.384023E+09 0.347652E+09
November 0.234713E+09 75156906.30 0.159556E+09 0.141741E+09 0.469560E+09
December 0.195383E+09 40475388.60 0.154907E+09 45343900.95 0.779854E+09
           
Annual Sum or Average 0.648178E+10 0.267155E+10 0.381023E+10 0.659724E+10 0.461360E+10
Minimum of Months 0.195383E+09 40475388.60 0.154907E+09 45343900.95 65636023.89
Maximum of Months 0.844841E+09 0.373023E+09 0.471818E+09 0.112847E+10 0.797005E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.315794E+09 0.184430E+09 0.131364E+09 0.252875E+09 0.395093E+09
February 0.323021E+09 0.154488E+09 0.168532E+09 0.252932E+09 0.350679E+09
March 0.439445E+09 0.246888E+09 0.192557E+09 0.427569E+09 0.271725E+09
April 0.351727E+09 0.140232E+09 0.211496E+09 0.358100E+09 0.199607E+09
May 0.320501E+09 94481581.13 0.226020E+09 0.360806E+09 0.123248E+09
June 0.298548E+09 62513323.98 0.236035E+09 0.378636E+09 65730231.02
July 0.313569E+09 74283889.35 0.239286E+09 0.445609E+09 37726006.03
August 0.351119E+09 0.111418E+09 0.239702E+09 0.483724E+09 54711086.67
September 0.397737E+09 0.193025E+09 0.204712E+09 0.500537E+09 99994977.95
October 0.395229E+09 0.225964E+09 0.169265E+09 0.429766E+09 0.184379E+09
November 0.274350E+09 0.155228E+09 0.119122E+09 0.262276E+09 0.242064E+09
December 0.264067E+09 0.136873E+09 0.127193E+09 0.200165E+09 0.385574E+09
           
Annual Sum or Average 0.404511E+10 0.177982E+10 0.226528E+10 0.435299E+10 0.241053E+10
Minimum of Months 0.264067E+09 62513323.98 0.119122E+09 0.200165E+09 37726006.03
Maximum of Months 0.439445E+09 0.246888E+09 0.239702E+09 0.500537E+09 0.395093E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 73340618.97 0.00 73340618.97 262059.54 0.461304E+09
February 0.100930E+09 0.00 0.100930E+09 5103953.83 0.394841E+09
March 0.135530E+09 1952.44 0.135528E+09 45244245.39 0.300056E+09
April 0.167471E+09 944079.53 0.166527E+09 90892135.17 0.196719E+09
May 0.200485E+09 8329113.51 0.192156E+09 0.166055E+09 0.113399E+09
June 0.234036E+09 20276941.55 0.213759E+09 0.265480E+09 59730260.77
July 0.225240E+09 15640458.54 0.209600E+09 0.300139E+09 34759157.12
August 0.194820E+09 3831298.71 0.190988E+09 0.244162E+09 51686818.55
September 0.142770E+09 80807.65 0.142689E+09 0.137532E+09 99364019.74
October 0.110196E+09 0.00 0.110196E+09 58357508.17 0.193987E+09
November 71659934.96 0.00 71659934.96 16302251.22 0.259672E+09
December 68644588.40 0.00 68644588.40 1029644.86 0.440262E+09
           
Annual Sum or Average 0.172512E+10 49104651.93 0.167602E+10 0.133056E+10 0.260578E+10
Minimum of Months 68644588.40 0.00 68644588.40 262059.54 34759157.12
Maximum of Months 0.234036E+09 20276941.55 0.213759E+09 0.300139E+09 0.461304E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.250400E+09 80644929.94 0.169755E+09 91383713.37 0.789924E+09
February 0.333910E+09 0.101147E+09 0.232763E+09 0.150310E+09 0.675841E+09
March 0.530463E+09 0.223077E+09 0.307386E+09 0.415525E+09 0.508142E+09
April 0.675747E+09 0.298488E+09 0.377259E+09 0.642501E+09 0.344694E+09
May 0.782340E+09 0.346132E+09 0.436208E+09 0.868665E+09 0.213175E+09
June 0.844841E+09 0.373023E+09 0.471818E+09 0.105019E+10 0.113452E+09
July 0.838413E+09 0.368664E+09 0.469749E+09 0.113157E+10 65032032.44
August 0.757266E+09 0.317200E+09 0.440066E+09 0.997161E+09 95626745.97
September 0.610474E+09 0.270807E+09 0.339666E+09 0.725449E+09 0.176410E+09
October 0.427828E+09 0.176737E+09 0.251091E+09 0.394823E+09 0.341602E+09
November 0.234713E+09 75156906.30 0.159556E+09 0.147564E+09 0.462471E+09
December 0.195383E+09 40475388.60 0.154907E+09 46790617.26 0.773738E+09
           
Annual Sum or Average 0.648178E+10 0.267155E+10 0.381023E+10 0.666193E+10 0.456011E+10
Minimum of Months 0.195383E+09 40475388.60 0.154907E+09 46790617.26 65032032.44
Maximum of Months 0.844841E+09 0.373023E+09 0.471818E+09 0.113157E+10 0.789924E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 92881266.38 0.00 92881266.38 3012.38 0.630928E+09
February 0.127821E+09 0.00 0.127821E+09 3312886.56 0.537254E+09
March 0.171640E+09 2472.65 0.171638E+09 54024092.00 0.404899E+09
April 0.212092E+09 1195617.16 0.210896E+09 0.116925E+09 0.264188E+09
May 0.253902E+09 10548296.72 0.243353E+09 0.214587E+09 0.160477E+09
June 0.296392E+09 25679467.07 0.270713E+09 0.335619E+09 93024441.54
July 0.285252E+09 19807653.88 0.265445E+09 0.372395E+09 61838497.38
August 0.246727E+09 4852098.08 0.241875E+09 0.303217E+09 87666654.16
September 0.180809E+09 102337.78 0.180706E+09 0.172824E+09 0.149776E+09
October 0.139556E+09 0.00 0.139556E+09 70898008.67 0.267953E+09
November 90752786.13 0.00 90752786.13 17435716.06 0.357916E+09
December 86934039.98 0.00 86934039.98 671224.03 0.603231E+09
           
Annual Sum or Average 0.218476E+10 62187943.33 0.212257E+10 0.166191E+10 0.361915E+10
Minimum of Months 86934039.98 0.00 86934039.98 3012.38 61838497.38
Maximum of Months 0.296392E+09 25679467.07 0.270713E+09 0.372395E+09 0.630928E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 34239880.70 0.00 34239880.70 1110.49 0.232586E+09
February 47120151.26 0.00 47120151.26 1221267.16 0.198054E+09
March 63273774.58 911.52 63272863.06 19915517.27 0.149262E+09
April 78185830.84 440753.99 77745076.85 43103391.92 97390710.12
May 93598659.99 3888538.94 89710121.05 79105670.49 59158508.83
June 0.109262E+09 9466514.87 99795880.07 0.123723E+09 34292660.99
July 0.105156E+09 7301921.39 97853952.68 0.137280E+09 22796230.67
August 90953723.42 1788684.26 89165039.16 0.111778E+09 32317558.71
September 66653531.46 37725.94 66615805.51 63710004.14 55213592.41
October 51446007.55 0.00 51446007.55 26135941.65 98778841.51
November 33455234.75 0.00 33455234.75 6427526.90 0.131943E+09
December 32047486.79 0.00 32047486.79 247440.97 0.222376E+09
           
Annual Sum or Average 0.805393E+09 22925050.91 0.782467E+09 0.612650E+09 0.133417E+10
Minimum of Months 32047486.79 0.00 32047486.79 1110.49 22796230.67
Maximum of Months 0.109262E+09 9466514.87 99795880.07 0.137280E+09 0.232586E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.147348E+09 86054147.46 61294084.35 0.115155E+09 0.195745E+09
February 0.150720E+09 72083624.15 78636460.40 0.115120E+09 0.172814E+09
March 0.205043E+09 0.115197E+09 89846464.09 0.200284E+09 0.132876E+09
April 0.164115E+09 65431478.38 98683063.95 0.169894E+09 97985009.71
May 0.149545E+09 44084725.03 0.105460E+09 0.171232E+09 63815868.36
June 0.139301E+09 29168465.06 0.110133E+09 0.177528E+09 37797750.25
July 0.146310E+09 34660563.43 0.111650E+09 0.206145E+09 24753248.25
August 0.163831E+09 51987059.07 0.111844E+09 0.224745E+09 33869857.22
September 0.185582E+09 90064572.61 95517803.10 0.234529E+09 54693066.14
October 0.184412E+09 0.105434E+09 78978190.99 0.202031E+09 92207622.76
November 0.128011E+09 72428664.45 55582016.60 0.121741E+09 0.120473E+09
December 0.123212E+09 63864534.36 59347945.65 90733492.31 0.191977E+09
           
Annual Sum or Average 0.188743E+10 0.830459E+09 0.105697E+10 0.202914E+10 0.121901E+10
Minimum of Months 0.123212E+09 29168465.06 55582016.60 90733492.31 24753248.25
Maximum of Months 0.205043E+09 0.115197E+09 0.111844E+09 0.234529E+09 0.195745E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.399933E+09 0.233569E+09 0.166365E+09 0.312555E+09 0.531293E+09
February 0.409085E+09 0.195650E+09 0.213435E+09 0.312460E+09 0.469053E+09
March 0.556530E+09 0.312668E+09 0.243862E+09 0.543613E+09 0.360651E+09
April 0.445440E+09 0.177594E+09 0.267846E+09 0.461127E+09 0.265951E+09
May 0.405895E+09 0.119655E+09 0.286240E+09 0.464758E+09 0.173209E+09
June 0.378092E+09 79169180.44 0.298923E+09 0.481846E+09 0.102591E+09
July 0.397116E+09 94075858.80 0.303040E+09 0.559520E+09 67185378.91
August 0.444670E+09 0.141104E+09 0.303567E+09 0.610003E+09 91929720.42
September 0.503709E+09 0.244454E+09 0.259255E+09 0.636561E+09 0.148448E+09
October 0.500532E+09 0.286169E+09 0.214363E+09 0.548352E+09 0.250270E+09
November 0.347447E+09 0.196586E+09 0.150861E+09 0.330431E+09 0.326990E+09
December 0.334424E+09 0.173341E+09 0.161082E+09 0.246269E+09 0.521065E+09
           
Annual Sum or Average 0.512287E+10 0.225403E+10 0.286884E+10 0.550750E+10 0.330864E+10
Minimum of Months 0.334424E+09 79169180.44 0.150861E+09 0.246269E+09 67185378.91
Maximum of Months 0.556530E+09 0.312668E+09 0.303567E+09 0.636561E+09 0.531293E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.315794E+09 0.184430E+09 0.131364E+09 0.253005E+09 0.394724E+09
February 0.323021E+09 0.154488E+09 0.168532E+09 0.252426E+09 0.351328E+09
March 0.439445E+09 0.246888E+09 0.192557E+09 0.428475E+09 0.272519E+09
April 0.351727E+09 0.140232E+09 0.211496E+09 0.359791E+09 0.199877E+09
May 0.320501E+09 94481581.13 0.226020E+09 0.360880E+09 0.123448E+09
June 0.298548E+09 62513323.98 0.236035E+09 0.376962E+09 66226283.36
July 0.313569E+09 74283889.35 0.239286E+09 0.444306E+09 37616984.40
August 0.351119E+09 0.111418E+09 0.239702E+09 0.482236E+09 54085760.73
September 0.397737E+09 0.193025E+09 0.204712E+09 0.500538E+09 99056189.80
October 0.395229E+09 0.225964E+09 0.169265E+09 0.431191E+09 0.182646E+09
November 0.274350E+09 0.155228E+09 0.119122E+09 0.262547E+09 0.240402E+09
December 0.264067E+09 0.136873E+09 0.127193E+09 0.199404E+09 0.385752E+09
           
Annual Sum or Average 0.404511E+10 0.177982E+10 0.226528E+10 0.435176E+10 0.240768E+10
Minimum of Months 0.264067E+09 62513323.98 0.119122E+09 0.199404E+09 37616984.40
Maximum of Months 0.439445E+09 0.246888E+09 0.239702E+09 0.500538E+09 0.394724E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.215644E+09 50829651.37 0.164814E+09 56941668.34 0.822759E+09
February 0.316288E+09 81920195.30 0.234368E+09 0.129326E+09 0.703738E+09
March 0.548232E+09 0.235439E+09 0.312792E+09 0.429572E+09 0.527116E+09
April 0.646790E+09 0.264971E+09 0.381819E+09 0.604349E+09 0.359039E+09
May 0.789316E+09 0.357097E+09 0.432219E+09 0.871564E+09 0.222465E+09
June 0.920469E+09 0.432527E+09 0.487942E+09 0.114293E+10 0.120548E+09
July 0.850202E+09 0.372165E+09 0.478037E+09 0.114018E+10 69769548.14
August 0.768575E+09 0.325787E+09 0.442787E+09 0.100699E+10 0.100270E+09
September 0.584733E+09 0.252239E+09 0.332495E+09 0.684235E+09 0.183536E+09
October 0.393455E+09 0.139370E+09 0.254085E+09 0.347541E+09 0.353297E+09
November 0.224342E+09 64348474.66 0.159993E+09 0.132382E+09 0.473963E+09
December 0.200590E+09 43216876.22 0.157373E+09 53095000.21 0.789600E+09
           
Annual Sum or Average 0.645864E+10 0.261991E+10 0.383873E+10 0.659910E+10 0.472610E+10
Minimum of Months 0.200590E+09 43216876.22 0.157373E+09 53095000.21 69769548.14
Maximum of Months 0.920469E+09 0.432527E+09 0.487942E+09 0.114293E+10 0.822759E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 73340618.97 0.00 73340618.97 306625.99 0.460673E+09
February 0.100930E+09 0.00 0.100930E+09 5344491.69 0.394438E+09
March 0.135530E+09 1952.44 0.135528E+09 47224339.31 0.299891E+09
April 0.167471E+09 944079.53 0.166527E+09 94373878.41 0.195671E+09
May 0.200485E+09 8329113.51 0.192156E+09 0.168175E+09 0.112695E+09
June 0.234036E+09 20276941.55 0.213759E+09 0.265127E+09 60097414.53
July 0.225240E+09 15640458.54 0.209600E+09 0.300231E+09 34663193.53
August 0.194820E+09 3831298.71 0.190988E+09 0.244831E+09 51160163.73
September 0.142770E+09 80807.65 0.142689E+09 0.140609E+09 97853487.51
October 0.110196E+09 0.00 0.110196E+09 62022811.39 0.191273E+09
November 71659934.96 0.00 71659934.96 17693336.80 0.257042E+09
December 68644588.40 0.00 68644588.40 1103902.63 0.439367E+09
           
Annual Sum or Average 0.172512E+10 49104651.93 0.167602E+10 0.134704E+10 0.259482E+10
Minimum of Months 68644588.40 0.00 68644588.40 306625.99 34663193.53
Maximum of Months 0.234036E+09 20276941.55 0.213759E+09 0.300231E+09 0.460673E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.215644E+09 50829651.37 0.164814E+09 59837719.31 0.817567E+09
February 0.316288E+09 81920195.30 0.234368E+09 0.133833E+09 0.699629E+09
March 0.548232E+09 0.235439E+09 0.312792E+09 0.441660E+09 0.520143E+09
April 0.646790E+09 0.264971E+09 0.381819E+09 0.614714E+09 0.355446E+09
May 0.789316E+09 0.357097E+09 0.432219E+09 0.878240E+09 0.220681E+09
June 0.920469E+09 0.432527E+09 0.487942E+09 0.114613E+10 0.119832E+09
July 0.850202E+09 0.372165E+09 0.478037E+09 0.114347E+10 69029996.32
August 0.768575E+09 0.325787E+09 0.442787E+09 0.101238E+10 98849117.69
September 0.584733E+09 0.252239E+09 0.332495E+09 0.694455E+09 0.180022E+09
October 0.393455E+09 0.139370E+09 0.254085E+09 0.360666E+09 0.347115E+09
November 0.224342E+09 64348474.66 0.159993E+09 0.140270E+09 0.468443E+09
December 0.200590E+09 43216876.22 0.157373E+09 56024822.46 0.785232E+09
           
Annual Sum or Average 0.645864E+10 0.261991E+10 0.383873E+10 0.668168E+10 0.468199E+10
Minimum of Months 0.200590E+09 43216876.22 0.157373E+09 56024822.46 69029996.32
Maximum of Months 0.920469E+09 0.432527E+09 0.487942E+09 0.114613E+10 0.817567E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.463142E+09 0.270484E+09 0.192658E+09 0.356135E+09 0.597524E+09
February 0.473741E+09 0.226572E+09 0.247169E+09 0.356865E+09 0.530102E+09
March 0.644489E+09 0.362085E+09 0.282404E+09 0.610917E+09 0.411049E+09
April 0.515842E+09 0.205663E+09 0.310179E+09 0.519727E+09 0.297248E+09
May 0.470046E+09 0.138566E+09 0.331480E+09 0.530081E+09 0.179801E+09
June 0.437850E+09 91681789.03 0.346168E+09 0.561050E+09 93161085.66
July 0.459880E+09 0.108944E+09 0.350935E+09 0.659954E+09 51920415.03
August 0.514950E+09 0.163405E+09 0.351545E+09 0.712237E+09 77078482.33
September 0.583319E+09 0.283089E+09 0.300230E+09 0.730550E+09 0.146439E+09
October 0.579641E+09 0.331398E+09 0.248243E+09 0.619049E+09 0.278136E+09
November 0.402361E+09 0.227656E+09 0.174704E+09 0.372531E+09 0.368440E+09
December 0.387279E+09 0.200738E+09 0.186541E+09 0.280937E+09 0.583139E+09
           
Annual Sum or Average 0.593254E+10 0.261028E+10 0.332226E+10 0.631003E+10 0.361404E+10
Minimum of Months 0.387279E+09 91681789.03 0.174704E+09 0.280937E+09 51920415.03
Maximum of Months 0.644489E+09 0.362085E+09 0.351545E+09 0.730550E+09 0.597524E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.513365E+09 0.00 0.513365E+09 0.00 0.380460E+10
February 0.706481E+09 0.00 0.706481E+09 9147366.80 0.324892E+10
March 0.948675E+09 13666.58 0.948662E+09 0.235361E+09 0.251745E+10
April 0.117225E+10 6608306.45 0.116565E+10 0.531653E+09 0.168344E+10
May 0.140334E+10 58301586.40 0.134504E+10 0.104563E+10 0.100539E+10
June 0.163819E+10 0.141933E+09 0.149626E+10 0.174338E+10 0.564666E+09
July 0.157662E+10 0.109479E+09 0.146714E+10 0.198346E+10 0.368195E+09
August 0.136369E+10 26818075.25 0.133687E+10 0.160941E+10 0.518952E+09
September 0.999349E+09 565632.09 0.998783E+09 0.880548E+09 0.912714E+09
October 0.771340E+09 0.00 0.771340E+09 0.310813E+09 0.171619E+10
November 0.501601E+09 0.00 0.501601E+09 62808665.49 0.229907E+10
December 0.480494E+09 0.00 0.480494E+09 1847219.50 0.366090E+10
           
Annual Sum or Average 0.120754E+11 0.343720E+09 0.117317E+11 0.841406E+10 0.223005E+11
Minimum of Months 0.480494E+09 0.00 0.480494E+09 0.00 0.368195E+09
Maximum of Months 0.163819E+10 0.141933E+09 0.149626E+10 0.198346E+10 0.380460E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.513365E+09 0.00 0.513365E+09 0.00 0.390644E+10
February 0.706481E+09 0.00 0.706481E+09 6405423.21 0.333961E+10
March 0.948675E+09 13666.58 0.948662E+09 0.218915E+09 0.258787E+10
April 0.117225E+10 6608306.45 0.116565E+10 0.503596E+09 0.172793E+10
May 0.140334E+10 58301586.40 0.134504E+10 0.101371E+10 0.103125E+10
June 0.163819E+10 0.141933E+09 0.149626E+10 0.171711E+10 0.579766E+09
July 0.157662E+10 0.109479E+09 0.146714E+10 0.196095E+10 0.380437E+09
August 0.136369E+10 26818075.25 0.133687E+10 0.158766E+10 0.535047E+09
September 0.999349E+09 565632.09 0.998783E+09 0.858207E+09 0.938697E+09
October 0.771340E+09 0.00 0.771340E+09 0.288834E+09 0.176738E+10
November 0.501601E+09 0.00 0.501601E+09 55604843.39 0.237487E+10
December 0.480494E+09 0.00 0.480494E+09 1379999.43 0.376077E+10
           
Annual Sum or Average 0.120754E+11 0.343720E+09 0.117317E+11 0.821236E+10 0.229301E+11
Minimum of Months 0.480494E+09 0.00 0.480494E+09 0.00 0.380437E+09
Maximum of Months 0.163819E+10 0.141933E+09 0.149626E+10 0.196095E+10 0.390644E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 73340618.97 0.00 73340618.97 265340.79 0.488749E+09
February 0.100930E+09 0.00 0.100930E+09 4204159.11 0.418248E+09
March 0.135530E+09 1952.44 0.135528E+09 50835779.12 0.320792E+09
April 0.167471E+09 944079.53 0.166527E+09 0.108171E+09 0.216236E+09
May 0.200485E+09 8329113.51 0.192156E+09 0.202416E+09 0.132048E+09
June 0.234036E+09 20276941.55 0.213759E+09 0.314020E+09 77837237.03
July 0.225240E+09 15640458.54 0.209600E+09 0.356683E+09 51220129.03
August 0.194820E+09 3831298.71 0.190988E+09 0.297203E+09 68044593.45
September 0.142770E+09 80807.65 0.142689E+09 0.173919E+09 0.112863E+09
October 0.110196E+09 0.00 0.110196E+09 70682349.49 0.211577E+09
November 71659934.96 0.00 71659934.96 18611435.91 0.282922E+09
December 68644588.40 0.00 68644588.40 1097808.90 0.469124E+09
           
Annual Sum or Average 0.172512E+10 49104651.93 0.167602E+10 0.159811E+10 0.284966E+10
Minimum of Months 68644588.40 0.00 68644588.40 265340.79 51220129.03
Maximum of Months 0.234036E+09 20276941.55 0.213759E+09 0.356683E+09 0.488749E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.500765E+09 0.161278E+09 0.339486E+09 0.184322E+09 0.167920E+10
February 0.667773E+09 0.202279E+09 0.465494E+09 0.300630E+09 0.144327E+10
March 0.106085E+10 0.446122E+09 0.614728E+09 0.861319E+09 0.109968E+10
April 0.135140E+10 0.596933E+09 0.754464E+09 0.135935E+10 0.770838E+09
May 0.156457E+10 0.692215E+09 0.872355E+09 0.187499E+10 0.496823E+09
June 0.168956E+10 0.745994E+09 0.943569E+09 0.228211E+10 0.292652E+09
July 0.167671E+10 0.737276E+09 0.939431E+09 0.247480E+10 0.192198E+09
August 0.151442E+10 0.634355E+09 0.880069E+09 0.219320E+10 0.254233E+09
September 0.122086E+10 0.541576E+09 0.679284E+09 0.159805E+10 0.409248E+09
October 0.855596E+09 0.353449E+09 0.502147E+09 0.847336E+09 0.753237E+09
November 0.469393E+09 0.150303E+09 0.319090E+09 0.308168E+09 0.101592E+10
December 0.390738E+09 80945028.68 0.309793E+09 95177344.08 0.166177E+10
           
Annual Sum or Average 0.129626E+11 0.534273E+10 0.761991E+10 0.143795E+11 0.100691E+11
Minimum of Months 0.390738E+09 80945028.68 0.309793E+09 95177344.08 0.192198E+09
Maximum of Months 0.168956E+10 0.745994E+09 0.943569E+09 0.247480E+10 0.167920E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.315794E+09 0.184430E+09 0.131364E+09 0.253953E+09 0.417737E+09
February 0.323021E+09 0.154488E+09 0.168532E+09 0.252241E+09 0.372490E+09
March 0.439445E+09 0.246888E+09 0.192557E+09 0.442850E+09 0.290696E+09
April 0.351727E+09 0.140232E+09 0.211496E+09 0.381660E+09 0.218953E+09
May 0.320501E+09 94481581.13 0.226020E+09 0.398152E+09 0.141087E+09
June 0.298548E+09 62513323.98 0.236035E+09 0.426247E+09 83191562.61
July 0.313569E+09 74283889.35 0.239286E+09 0.501396E+09 53894161.12
August 0.351119E+09 0.111418E+09 0.239702E+09 0.537760E+09 70015882.07
September 0.397737E+09 0.193025E+09 0.204712E+09 0.543088E+09 0.112955E+09
October 0.395229E+09 0.225964E+09 0.169265E+09 0.452966E+09 0.201873E+09
November 0.274350E+09 0.155228E+09 0.119122E+09 0.269935E+09 0.264964E+09
December 0.264067E+09 0.136873E+09 0.127193E+09 0.199564E+09 0.412395E+09
           
Annual Sum or Average 0.404511E+10 0.177982E+10 0.226528E+10 0.465981E+10 0.264025E+10
Minimum of Months 0.264067E+09 62513323.98 0.119122E+09 0.199564E+09 53894161.12
Maximum of Months 0.439445E+09 0.246888E+09 0.239702E+09 0.543088E+09 0.417737E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 92881266.38 0.00 92881266.38 0.00 0.642045E+09
February 0.127821E+09 0.00 0.127821E+09 2571668.43 0.546490E+09
March 0.171640E+09 2472.65 0.171638E+09 49735189.27 0.413436E+09
April 0.212092E+09 1195617.16 0.210896E+09 0.109705E+09 0.268737E+09
May 0.253902E+09 10548296.72 0.243353E+09 0.205183E+09 0.162967E+09
June 0.296392E+09 25679467.07 0.270713E+09 0.324014E+09 96132595.30
July 0.285252E+09 19807653.88 0.265445E+09 0.359984E+09 65304685.54
August 0.246727E+09 4852098.08 0.241875E+09 0.293513E+09 90768795.82
September 0.180809E+09 102337.78 0.180706E+09 0.165875E+09 0.151212E+09
October 0.139556E+09 0.00 0.139556E+09 65629694.13 0.272671E+09
November 90752786.13 0.00 90752786.13 15370193.90 0.366431E+09
December 86934039.98 0.00 86934039.98 550715.50 0.613690E+09
           
Annual Sum or Average 0.218476E+10 62187943.33 0.212257E+10 0.159213E+10 0.368988E+10
Minimum of Months 86934039.98 0.00 86934039.98 0.00 65304685.54
Maximum of Months 0.296392E+09 25679467.07 0.270713E+09 0.359984E+09 0.642045E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 83101220.96 0.00 83101220.96 0.00 0.574425E+09
February 0.114362E+09 0.00 0.114362E+09 2300881.49 0.488949E+09
March 0.153567E+09 2212.29 0.153565E+09 44498262.29 0.369903E+09
April 0.189759E+09 1069723.20 0.188690E+09 98153481.72 0.240440E+09
May 0.227167E+09 9437601.04 0.217729E+09 0.183578E+09 0.145807E+09
June 0.265183E+09 22975516.49 0.242208E+09 0.289896E+09 86010197.26
July 0.255216E+09 17721982.98 0.237494E+09 0.322079E+09 58428349.59
August 0.220747E+09 4341190.53 0.216406E+09 0.262607E+09 81211185.54
September 0.161770E+09 91562.00 0.161679E+09 0.148409E+09 0.135290E+09
October 0.124861E+09 0.00 0.124861E+09 58719136.01 0.243961E+09
November 81196861.61 0.00 81196861.61 13751770.72 0.327841E+09
December 77780214.96 0.00 77780214.96 492727.24 0.549058E+09
           
Annual Sum or Average 0.195471E+10 55639788.53 0.189907E+10 0.142448E+10 0.330132E+10
Minimum of Months 77780214.96 0.00 77780214.96 0.00 58428349.59
Maximum of Months 0.265183E+09 22975516.49 0.242208E+09 0.322079E+09 0.574425E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.117895E+10 0.688531E+09 0.490422E+09 0.905876E+09 0.159136E+10
February 0.120593E+10 0.576751E+09 0.629181E+09 0.901207E+09 0.140551E+10
March 0.164058E+10 0.921706E+09 0.718874E+09 0.157198E+10 0.108249E+10
April 0.131310E+10 0.523526E+09 0.789577E+09 0.132913E+10 0.798838E+09
May 0.119653E+10 0.352728E+09 0.843799E+09 0.133709E+10 0.520958E+09
June 0.111457E+10 0.233381E+09 0.881188E+09 0.138258E+10 0.312967E+09
July 0.117065E+10 0.277324E+09 0.893324E+09 0.160826E+10 0.209371E+09
August 0.131083E+10 0.415956E+09 0.894877E+09 0.176381E+10 0.281005E+09
September 0.148487E+10 0.720619E+09 0.764251E+09 0.184914E+10 0.442933E+09
October 0.147551E+10 0.843591E+09 0.631915E+09 0.158953E+10 0.750651E+09
November 0.102423E+10 0.579512E+09 0.444719E+09 0.955496E+09 0.987292E+09
December 0.985840E+09 0.510989E+09 0.474851E+09 0.711682E+09 0.156446E+10
           
Annual Sum or Average 0.151016E+11 0.664461E+10 0.845698E+10 0.159058E+11 0.994783E+10
Minimum of Months 0.985840E+09 0.233381E+09 0.444719E+09 0.711682E+09 0.209371E+09
Maximum of Months 0.164058E+10 0.921706E+09 0.894877E+09 0.184914E+10 0.159136E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 474.98 726.64 596.33 348.27 248.06 0.00 0.00
February 531.42 707.69 675.32 322.98 352.34 0.00 0.00
March 810.16 504.68 829.82 466.21 363.61 0.00 0.00
April 707.84 381.12 686.32 273.63 412.68 0.00 0.00
May 692.55 233.60 605.21 178.41 426.80 0.00 0.00
June 740.00 143.08 582.55 121.98 460.57 0.00 0.00
July 825.51 92.14 592.12 140.27 451.85 0.00 0.00
August 900.05 125.95 663.03 210.39 452.63 0.00 0.00
September 970.50 210.02 776.09 376.65 399.45 0.00 0.00
October 809.77 351.59 746.32 426.70 319.63 0.00 0.00
November 507.30 470.49 535.33 302.89 232.44 0.00 0.00
December 376.57 708.38 498.65 258.46 240.18 0.00 0.00
               
Annual Sum or Average 696.51 386.27 648.75 285.45 363.30 0.00 0.00
Minimum of Months 376.57 92.14 498.65 121.98 232.44 0.00 0.00
Maximum of Months 970.50 726.64 829.82 466.21 460.57 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1319.15 2080.96 1679.21 980.69 698.52 0.00 0.00
February 1474.80 2024.87 1901.67 909.50 992.17 0.00 0.00
March 2247.26 1487.14 2336.72 1312.81 1023.90 0.00 0.00
April 1956.11 1151.70 1932.62 770.53 1162.09 0.00 0.00
May 1903.11 737.98 1704.23 502.40 1201.83 0.00 0.00
June 2040.53 458.42 1640.41 343.49 1296.92 0.00 0.00
July 2291.04 296.63 1667.37 395.00 1272.37 0.00 0.00
August 2503.04 401.99 1867.04 592.46 1274.59 0.00 0.00
September 2695.18 668.25 2185.43 1060.61 1124.82 0.00 0.00
October 2244.73 1075.08 2101.60 1201.55 900.05 0.00 0.00
November 1402.45 1401.98 1507.47 852.93 654.54 0.00 0.00
December 1044.48 2034.10 1404.16 727.82 676.34 0.00 0.00
               
Annual Sum or Average 1929.48 1146.95 1826.84 803.80 1023.04 0.00 0.00
Minimum of Months 1044.48 296.63 1404.16 343.49 654.54 0.00 0.00
Maximum of Months 2695.18 2080.96 2336.72 1312.81 1296.92 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1733.12 2847.03 2181.39 1273.98 907.42 0.00 0.00
February 1939.46 2765.22 2470.38 1181.49 1288.89 0.00 0.00
March 2969.37 2026.54 3035.53 1705.42 1330.11 0.00 0.00
April 2579.52 1580.70 2510.59 1000.96 1509.63 0.00 0.00
May 2509.44 1017.17 2213.90 652.65 1561.25 0.00 0.00
June 2697.06 622.41 2130.99 446.21 1684.78 0.00 0.00
July 3037.01 395.78 2166.01 513.13 1652.89 0.00 0.00
August 3313.58 536.20 2425.40 769.64 1655.76 0.00 0.00
September 3560.68 905.34 2839.00 1377.79 1461.21 0.00 0.00
October 2951.95 1480.51 2730.10 1560.88 1169.21 0.00 0.00
November 1841.39 1943.29 1958.28 1108.00 850.28 0.00 0.00
December 1371.25 2794.40 1824.08 945.47 878.60 0.00 0.00
               
Annual Sum or Average 2545.54 1569.88 2373.16 1044.18 1328.98 0.00 0.00
Minimum of Months 1371.25 395.78 1824.08 446.21 850.28 0.00 0.00
Maximum of Months 3560.68 2847.03 3035.53 1705.42 1684.78 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 97.34 435.76 198.42 87.84 110.58 0.00 0.00
February 146.70 423.24 264.26 97.72 166.54 0.00 0.00
March 311.54 289.34 368.76 180.08 188.68 0.00 0.00
April 371.09 213.43 385.23 156.33 228.90 0.00 0.00
May 462.23 129.22 414.36 168.60 245.76 0.00 0.00
June 590.18 72.73 470.30 190.99 279.31 0.00 0.00
July 595.25 41.28 434.50 166.68 267.82 0.00 0.00
August 559.04 59.06 418.05 163.23 254.81 0.00 0.00
September 458.52 110.36 379.04 171.78 207.26 0.00 0.00
October 288.20 199.28 294.46 136.40 158.06 0.00 0.00
November 147.54 273.12 192.40 84.71 107.68 0.00 0.00
December 82.39 426.44 173.48 67.24 106.25 0.00 0.00
               
Annual Sum or Average 343.57 221.73 333.07 139.51 193.56 0.00 0.00
Minimum of Months 82.39 41.28 173.48 67.24 106.25 0.00 0.00
Maximum of Months 595.25 435.76 470.30 190.99 279.31 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 17.51 471.94 107.89 18.98 88.92 0.00 0.00
February 51.83 445.52 172.46 33.86 138.60 0.00 0.00
March 175.82 299.79 255.29 87.90 167.38 0.00 0.00
April 272.50 211.59 314.14 102.59 211.55 0.00 0.00
May 392.32 125.03 369.55 136.43 233.11 0.00 0.00
June 546.51 68.74 445.41 174.69 270.72 0.00 0.00
July 541.03 38.71 401.52 144.79 256.73 0.00 0.00
August 471.18 57.00 359.69 123.07 236.62 0.00 0.00
September 322.63 109.09 280.67 97.35 183.33 0.00 0.00
October 155.54 202.31 188.04 52.03 136.01 0.00 0.00
November 58.14 280.37 114.20 24.83 89.37 0.00 0.00
December 16.86 452.77 100.52 16.14 84.39 0.00 0.00
               
Annual Sum or Average 252.94 229.16 259.51 84.63 174.87 0.00 0.00
Minimum of Months 16.86 38.71 100.52 16.14 84.39 0.00 0.00
Maximum of Months 546.51 471.94 445.41 174.69 270.72 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 75.73 113.12 94.30 55.08 39.23 0.00 0.00
February 84.49 110.96 106.80 51.08 55.72 0.00 0.00
March 127.35 82.07 131.23 73.73 57.50 0.00 0.00
April 110.76 63.93 108.54 43.27 65.26 0.00 0.00
May 106.78 42.01 95.71 28.21 67.50 0.00 0.00
June 115.78 24.92 92.13 19.29 72.84 0.00 0.00
July 131.47 15.36 93.64 22.18 71.46 0.00 0.00
August 142.93 21.36 104.85 33.27 71.58 0.00 0.00
September 152.56 37.41 122.73 59.56 63.17 0.00 0.00
October 125.96 61.20 118.03 67.48 50.55 0.00 0.00
November 80.22 75.47 84.66 47.90 36.76 0.00 0.00
December 60.04 109.92 78.86 40.87 37.98 0.00 0.00
               
Annual Sum or Average 109.65 62.89 102.60 45.14 57.45 0.00 0.00
Minimum of Months 60.04 15.36 78.86 19.29 36.76 0.00 0.00
Maximum of Months 152.56 113.12 131.23 73.73 72.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.02 143.49 21.91 0.00 21.91 0.00 0.00
February 1.31 135.54 33.38 0.00 33.38 0.00 0.00
March 13.57 91.86 40.49 0.00 40.49 0.00 0.00
April 29.74 61.40 51.70 0.29 51.40 0.00 0.00
May 53.54 33.57 59.89 2.49 57.40 0.00 0.00
June 87.26 17.55 72.24 6.26 65.98 0.00 0.00
July 95.28 9.32 67.28 4.67 62.61 0.00 0.00
August 78.04 14.29 58.20 1.14 57.05 0.00 0.00
September 46.20 29.76 44.07 0.02 44.05 0.00 0.00
October 18.12 59.42 32.92 0.00 32.92 0.00 0.00
November 4.75 84.08 22.12 0.00 22.12 0.00 0.00
December 0.21 137.36 20.51 0.00 20.51 0.00 0.00
               
Annual Sum or Average 35.88 67.80 43.77 1.25 42.52 0.00 0.00
Minimum of Months 0.02 9.32 20.51 0.00 20.51 0.00 0.00
Maximum of Months 95.28 143.49 72.24 6.26 65.98 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 115.22 432.65 211.39 98.97 112.43 0.00 0.00
February 156.77 418.39 271.55 105.67 165.88 0.00 0.00
March 302.55 286.26 362.12 175.46 186.66 0.00 0.00
April 378.76 207.38 396.40 169.26 227.14 0.00 0.00
May 454.53 123.53 411.75 164.51 247.25 0.00 0.00
June 548.54 67.68 441.12 168.03 273.09 0.00 0.00
July 586.75 37.65 430.10 165.38 264.72 0.00 0.00
August 550.17 55.63 413.82 160.03 253.80 0.00 0.00
September 468.57 106.34 388.97 178.95 210.02 0.00 0.00
October 302.13 196.94 307.29 150.35 156.94 0.00 0.00
November 152.48 271.15 196.40 88.88 107.51 0.00 0.00
December 79.73 423.19 171.54 66.21 105.32 0.00 0.00
               
Annual Sum or Average 342.37 217.87 333.81 141.15 192.65 0.00 0.00
Minimum of Months 79.73 37.65 171.54 66.21 105.32 0.00 0.00
Maximum of Months 586.75 432.65 441.12 178.95 273.09 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 25.21 458.14 120.87 30.11 90.76 0.00 0.00
February 55.17 433.50 179.75 41.81 137.94 0.00 0.00
March 163.40 293.12 248.65 83.29 165.37 0.00 0.00
April 278.73 204.67 325.32 115.52 209.79 0.00 0.00
May 384.90 120.50 366.95 132.34 234.60 0.00 0.00
June 506.87 66.10 416.23 151.74 264.50 0.00 0.00
July 534.43 37.15 397.12 143.48 253.64 0.00 0.00
August 463.22 54.76 355.47 119.86 235.61 0.00 0.00
September 331.13 104.59 290.60 104.51 186.09 0.00 0.00
October 165.92 196.69 200.88 65.99 134.89 0.00 0.00
November 60.14 275.52 118.20 29.00 89.20 0.00 0.00
December 12.91 448.31 98.58 15.11 83.46 0.00 0.00
               
Annual Sum or Average 249.59 223.38 260.24 86.27 173.97 0.00 0.00
Minimum of Months 12.91 37.15 98.58 15.11 83.46 0.00 0.00
Maximum of Months 534.43 458.14 416.23 151.74 264.50 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 129.06 563.21 251.79 119.33 132.46 0.00 0.00
February 157.22 547.87 303.71 110.67 193.04 0.00 0.00
March 290.50 376.32 372.05 159.75 212.30 0.00 0.00
April 304.26 278.98 347.16 94.39 252.77 0.00 0.00
May 345.03 168.42 337.12 66.52 270.60 0.00 0.00
June 428.16 99.84 356.11 55.36 300.76 0.00 0.00
July 474.27 64.03 348.65 58.19 290.47 0.00 0.00
August 465.70 90.86 353.26 74.57 278.69 0.00 0.00
September 426.91 157.04 361.40 129.11 232.29 0.00 0.00
October 311.66 260.06 327.04 146.21 180.83 0.00 0.00
November 174.75 352.71 231.35 103.79 127.57 0.00 0.00
December 102.58 550.88 215.28 88.56 126.72 0.00 0.00
               
Annual Sum or Average 301.66 291.19 317.11 100.51 216.60 0.00 0.00
Minimum of Months 102.58 64.03 215.28 55.36 126.72 0.00 0.00
Maximum of Months 474.27 563.21 372.05 159.75 300.76 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 97.01 435.85 198.42 87.84 110.58 0.00 0.00
February 145.53 423.85 264.26 97.72 166.54 0.00 0.00
March 310.15 288.34 368.76 180.08 188.68 0.00 0.00
April 368.63 212.30 385.23 156.33 228.90 0.00 0.00
May 458.76 127.77 414.36 168.60 245.76 0.00 0.00
June 585.76 71.44 470.30 190.99 279.31 0.00 0.00
July 591.50 40.01 434.50 166.68 267.82 0.00 0.00
August 555.90 57.52 418.05 163.23 254.81 0.00 0.00
September 456.24 108.17 379.04 171.78 207.26 0.00 0.00
October 287.66 197.01 294.46 136.40 158.06 0.00 0.00
November 147.72 270.96 192.40 84.71 107.68 0.00 0.00
December 81.91 426.47 173.48 67.24 106.25 0.00 0.00
               
Annual Sum or Average 341.63 220.59 333.07 139.51 193.56 0.00 0.00
Minimum of Months 81.91 40.01 173.48 67.24 106.25 0.00 0.00
Maximum of Months 591.50 435.85 470.30 190.99 279.31 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 17.46 472.25 107.89 18.98 88.92 0.00 0.00
February 51.42 446.14 172.46 33.86 138.60 0.00 0.00
March 175.20 298.84 255.29 87.90 167.38 0.00 0.00
April 271.14 210.19 314.14 102.59 211.55 0.00 0.00
May 389.71 123.49 369.55 136.43 233.11 0.00 0.00
June 542.63 67.59 445.41 174.69 270.72 0.00 0.00
July 537.87 37.56 401.52 144.79 256.73 0.00 0.00
August 468.84 55.46 359.69 123.07 236.62 0.00 0.00
September 321.54 106.57 280.67 97.35 183.33 0.00 0.00
October 156.28 199.48 188.04 52.03 136.01 0.00 0.00
November 58.87 277.82 114.20 24.83 89.37 0.00 0.00
December 16.82 452.70 100.52 16.14 84.39 0.00 0.00
               
Annual Sum or Average 251.76 227.92 259.51 84.63 174.87 0.00 0.00
Minimum of Months 16.82 37.56 100.52 16.14 84.39 0.00 0.00
Maximum of Months 542.63 472.25 445.41 174.69 270.72 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 132.97 223.09 172.92 100.99 71.93 0.00 0.00
February 147.51 219.12 195.83 93.66 102.17 0.00 0.00
March 228.09 153.47 240.62 135.19 105.44 0.00 0.00
April 200.51 114.68 199.01 79.35 119.67 0.00 0.00
May 197.91 67.13 175.50 51.73 123.76 0.00 0.00
June 216.45 35.94 168.92 35.37 133.55 0.00 0.00
July 246.40 19.38 171.70 40.68 131.02 0.00 0.00
August 265.92 28.78 192.26 61.01 131.25 0.00 0.00
September 281.85 56.50 225.05 109.22 115.83 0.00 0.00
October 231.13 103.84 216.41 123.73 92.68 0.00 0.00
November 143.72 142.14 155.23 87.83 67.40 0.00 0.00
December 104.89 217.72 144.59 74.95 69.65 0.00 0.00
               
Annual Sum or Average 200.09 114.60 188.12 82.77 105.35 0.00 0.00
Minimum of Months 104.89 19.38 144.59 35.37 67.40 0.00 0.00
Maximum of Months 281.85 223.09 240.62 135.19 133.55 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 1420.47 191.67 0.00 191.67 0.00 0.00
February 3.78 1342.97 292.03 0.00 292.03 0.00 0.00
March 87.87 939.91 354.19 0.01 354.19 0.00 0.00
April 205.11 649.48 452.26 2.55 449.71 0.00 0.00
May 390.39 375.37 523.95 21.77 502.18 0.00 0.00
June 672.60 217.85 632.02 54.76 577.26 0.00 0.00
July 740.54 137.47 588.64 40.87 547.77 0.00 0.00
August 600.88 193.75 509.14 10.01 499.13 0.00 0.00
September 339.72 352.13 385.55 0.22 385.33 0.00 0.00
October 116.04 640.75 287.99 0.00 287.99 0.00 0.00
November 24.23 886.99 193.52 0.00 193.52 0.00 0.00
December 0.69 1366.82 179.40 0.00 179.40 0.00 0.00
               
Annual Sum or Average 266.81 707.14 382.91 10.90 372.01 0.00 0.00
Minimum of Months 0.00 137.47 179.40 0.00 179.40 0.00 0.00
Maximum of Months 740.54 1420.47 632.02 54.76 577.26 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 1458.50 191.67 0.00 191.67 0.00 0.00
February 2.65 1380.46 292.03 0.00 292.03 0.00 0.00
March 81.73 966.20 354.19 0.01 354.19 0.00 0.00
April 194.29 666.64 452.26 2.55 449.71 0.00 0.00
May 378.47 385.03 523.95 21.77 502.18 0.00 0.00
June 662.46 223.68 632.02 54.76 577.26 0.00 0.00
July 732.14 142.04 588.64 40.87 547.77 0.00 0.00
August 592.76 199.76 509.14 10.01 499.13 0.00 0.00
September 331.10 362.15 385.55 0.22 385.33 0.00 0.00
October 107.84 659.86 287.99 0.00 287.99 0.00 0.00
November 21.45 916.23 193.52 0.00 193.52 0.00 0.00
December 0.52 1404.11 179.40 0.00 179.40 0.00 0.00
               
Annual Sum or Average 260.41 727.11 382.91 10.90 372.01 0.00 0.00
Minimum of Months 0.00 142.04 179.40 0.00 179.40 0.00 0.00
Maximum of Months 732.14 1458.50 632.02 54.76 577.26 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 129.04 930.69 332.25 129.07 203.18 0.00 0.00
February 205.23 898.41 451.27 147.47 303.80 0.00 0.00
March 483.64 616.61 610.75 258.74 352.01 0.00 0.00
April 706.24 458.11 721.68 284.76 436.92 0.00 0.00
May 920.45 283.66 778.66 296.83 481.83 0.00 0.00
June 1163.60 172.59 857.31 319.75 537.56 0.00 0.00
July 1243.41 110.06 827.18 308.84 518.34 0.00 0.00
August 1129.72 145.59 769.25 279.87 489.38 0.00 0.00
September 890.76 242.61 679.54 283.44 396.10 0.00 0.00
October 507.30 431.03 508.15 216.33 291.82 0.00 0.00
November 221.20 594.31 314.58 117.87 196.71 0.00 0.00
December 82.47 921.57 270.10 81.32 188.78 0.00 0.00
               
Annual Sum or Average 642.68 481.64 594.02 227.41 366.60 0.00 0.00
Minimum of Months 82.47 110.06 270.10 81.32 188.78 0.00 0.00
Maximum of Months 1243.41 930.69 857.31 319.75 537.56 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 292.13 1002.23 505.88 257.07 248.81 0.00 0.00
February 341.54 976.00 598.59 238.41 360.19 0.00 0.00
March 599.05 673.58 733.94 344.13 389.81 0.00 0.00
April 591.46 503.12 661.63 202.85 458.78 0.00 0.00
May 640.43 305.86 626.34 139.16 487.19 0.00 0.00
June 763.47 184.24 646.66 108.81 537.85 0.00 0.00
July 851.29 120.55 638.86 117.55 521.31 0.00 0.00
August 864.55 167.52 663.94 158.73 505.21 0.00 0.00
September 834.02 280.78 705.03 278.09 426.94 0.00 0.00
October 632.50 465.76 649.61 314.96 334.65 0.00 0.00
November 365.87 634.76 461.49 223.58 237.91 0.00 0.00
December 230.49 982.61 429.57 190.78 238.79 0.00 0.00
               
Annual Sum or Average 585.29 522.40 610.13 214.44 395.69 0.00 0.00
Minimum of Months 230.49 120.55 429.57 108.81 237.91 0.00 0.00
Maximum of Months 864.55 1002.23 733.94 344.13 537.85 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.127218E+10 0.194623E+10 0.159720E+10 0.932795E+09 0.664402E+09 0.00 0.00
February 0.128562E+10 0.171204E+10 0.163375E+10 0.781360E+09 0.852386E+09 0.00 0.00
March 0.216995E+10 0.135174E+10 0.222259E+10 0.124869E+10 0.973896E+09 0.00 0.00
April 0.183473E+10 0.987865E+09 0.177893E+10 0.709253E+09 0.106968E+10 0.00 0.00
May 0.185493E+10 0.625677E+09 0.162100E+10 0.477862E+09 0.114314E+10 0.00 0.00
June 0.191809E+10 0.370867E+09 0.150996E+10 0.316175E+09 0.119379E+10 0.00 0.00
July 0.221104E+10 0.246777E+09 0.158594E+10 0.375708E+09 0.121023E+10 0.00 0.00
August 0.241069E+10 0.337344E+09 0.177586E+10 0.563521E+09 0.121233E+10 0.00 0.00
September 0.251553E+10 0.544378E+09 0.201164E+10 0.976267E+09 0.103537E+10 0.00 0.00
October 0.216889E+10 0.941699E+09 0.199895E+10 0.114287E+10 0.856089E+09 0.00 0.00
November 0.131493E+10 0.121951E+10 0.138759E+10 0.785100E+09 0.602486E+09 0.00 0.00
December 0.100860E+10 0.189732E+10 0.133558E+10 0.692268E+09 0.643307E+09 0.00 0.00
               
Annual Sum or Average 0.219652E+11 0.121814E+11 0.204590E+11 0.900187E+10 0.114571E+11 0.00 0.00
Minimum of Months 0.100860E+10 0.246777E+09 0.133558E+10 0.316175E+09 0.602486E+09 0.00 0.00
Maximum of Months 0.251553E+10 0.194623E+10 0.222259E+10 0.124869E+10 0.121233E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.353321E+10 0.557366E+10 0.449760E+10 0.262669E+10 0.187091E+10 0.00 0.00
February 0.356784E+10 0.489856E+10 0.460052E+10 0.220026E+10 0.240026E+10 0.00 0.00
March 0.601905E+10 0.398314E+10 0.625866E+10 0.351624E+10 0.274243E+10 0.00 0.00
April 0.507024E+10 0.298521E+10 0.500936E+10 0.199721E+10 0.301215E+10 0.00 0.00
May 0.509729E+10 0.197662E+10 0.456462E+10 0.134563E+10 0.321899E+10 0.00 0.00
June 0.528905E+10 0.118824E+10 0.425196E+10 0.890329E+09 0.336163E+10 0.00 0.00
July 0.613632E+10 0.794505E+09 0.446589E+10 0.105797E+10 0.340793E+10 0.00 0.00
August 0.670413E+10 0.107669E+10 0.500069E+10 0.158684E+10 0.341385E+10 0.00 0.00
September 0.698590E+10 0.173209E+10 0.566464E+10 0.274910E+10 0.291553E+10 0.00 0.00
October 0.601228E+10 0.287948E+10 0.562892E+10 0.321823E+10 0.241069E+10 0.00 0.00
November 0.363514E+10 0.363393E+10 0.390735E+10 0.221079E+10 0.169656E+10 0.00 0.00
December 0.279753E+10 0.544812E+10 0.376089E+10 0.194938E+10 0.181151E+10 0.00 0.00
               
Annual Sum or Average 0.608480E+11 0.361702E+11 0.576111E+11 0.253487E+11 0.322624E+11 0.00 0.00
Minimum of Months 0.279753E+10 0.794505E+09 0.376089E+10 0.890329E+09 0.169656E+10 0.00 0.00
Maximum of Months 0.698590E+10 0.557366E+10 0.625866E+10 0.351624E+10 0.341385E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.464200E+10 0.762548E+10 0.584264E+10 0.341222E+10 0.243042E+10 0.00 0.00
February 0.469195E+10 0.668962E+10 0.597634E+10 0.285826E+10 0.311808E+10 0.00 0.00
March 0.795317E+10 0.542789E+10 0.813036E+10 0.456779E+10 0.356257E+10 0.00 0.00
April 0.668612E+10 0.409718E+10 0.650744E+10 0.259449E+10 0.391295E+10 0.00 0.00
May 0.672129E+10 0.272439E+10 0.592970E+10 0.174805E+10 0.418166E+10 0.00 0.00
June 0.699079E+10 0.161329E+10 0.552353E+10 0.115659E+10 0.436694E+10 0.00 0.00
July 0.813433E+10 0.106006E+10 0.580145E+10 0.137436E+10 0.442709E+10 0.00 0.00
August 0.887510E+10 0.143616E+10 0.649618E+10 0.206139E+10 0.443479E+10 0.00 0.00
September 0.922928E+10 0.234663E+10 0.735869E+10 0.357124E+10 0.378744E+10 0.00 0.00
October 0.790649E+10 0.396540E+10 0.731229E+10 0.418067E+10 0.313162E+10 0.00 0.00
November 0.477289E+10 0.503700E+10 0.507587E+10 0.287194E+10 0.220393E+10 0.00 0.00
December 0.367275E+10 0.748452E+10 0.488561E+10 0.253236E+10 0.235326E+10 0.00 0.00
               
Annual Sum or Average 0.802761E+11 0.495076E+11 0.748401E+11 0.329294E+11 0.419107E+11 0.00 0.00
Minimum of Months 0.367275E+10 0.106006E+10 0.488561E+10 0.115659E+10 0.220393E+10 0.00 0.00
Maximum of Months 0.922928E+10 0.762548E+10 0.813036E+10 0.456779E+10 0.443479E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.260704E+09 0.116714E+10 0.531438E+09 0.235259E+09 0.296178E+09 0.00 0.00
February 0.354887E+09 0.102391E+10 0.639309E+09 0.236409E+09 0.402900E+09 0.00 0.00
March 0.834428E+09 0.774960E+09 0.987677E+09 0.482327E+09 0.505350E+09 0.00 0.00
April 0.961872E+09 0.553223E+09 0.998518E+09 0.405203E+09 0.593315E+09 0.00 0.00
May 0.123804E+10 0.346101E+09 0.110982E+10 0.451579E+09 0.658239E+09 0.00 0.00
June 0.152974E+10 0.188509E+09 0.121902E+10 0.495040E+09 0.723977E+09 0.00 0.00
July 0.159432E+10 0.110561E+09 0.116377E+10 0.446448E+09 0.717323E+09 0.00 0.00
August 0.149734E+10 0.158187E+09 0.111969E+10 0.437205E+09 0.682489E+09 0.00 0.00
September 0.118849E+10 0.286056E+09 0.982470E+09 0.445263E+09 0.537207E+09 0.00 0.00
October 0.771906E+09 0.533746E+09 0.788684E+09 0.365334E+09 0.423349E+09 0.00 0.00
November 0.382419E+09 0.707927E+09 0.498692E+09 0.219576E+09 0.279116E+09 0.00 0.00
December 0.220665E+09 0.114218E+10 0.464657E+09 0.180090E+09 0.284567E+09 0.00 0.00
               
Annual Sum or Average 0.108348E+11 0.699250E+10 0.105037E+11 0.439973E+10 0.610401E+10 0.00 0.00
Minimum of Months 0.220665E+09 0.110561E+09 0.464657E+09 0.180090E+09 0.279116E+09 0.00 0.00
Maximum of Months 0.159432E+10 0.116714E+10 0.121902E+10 0.495040E+09 0.723977E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 46891272.31 0.126404E+10 0.288984E+09 50829651.37 0.238155E+09 0.00 0.00
February 0.125393E+09 0.107779E+10 0.417218E+09 81920195.30 0.335298E+09 0.00 0.00
March 0.470915E+09 0.802965E+09 0.683762E+09 0.235441E+09 0.448321E+09 0.00 0.00
April 0.706329E+09 0.548444E+09 0.814262E+09 0.265915E+09 0.548347E+09 0.00 0.00
May 0.105079E+10 0.334867E+09 0.989801E+09 0.365426E+09 0.624375E+09 0.00 0.00
June 0.141656E+10 0.178183E+09 0.115451E+10 0.452804E+09 0.701701E+09 0.00 0.00
July 0.144910E+10 0.103688E+09 0.107544E+10 0.387805E+09 0.687637E+09 0.00 0.00
August 0.126202E+10 0.152669E+09 0.963394E+09 0.329618E+09 0.633776E+09 0.00 0.00
September 0.836263E+09 0.282754E+09 0.727503E+09 0.252319E+09 0.475183E+09 0.00 0.00
October 0.416592E+09 0.541869E+09 0.503650E+09 0.139370E+09 0.364280E+09 0.00 0.00
November 0.150693E+09 0.726713E+09 0.296002E+09 64348474.66 0.231653E+09 0.00 0.00
December 45153242.67 0.121269E+10 0.269235E+09 43216876.22 0.226018E+09 0.00 0.00
               
Annual Sum or Average 0.797669E+10 0.722667E+10 0.818376E+10 0.266902E+10 0.551474E+10 0.00 0.00
Minimum of Months 45153242.67 0.103688E+09 0.269235E+09 43216876.22 0.226018E+09 0.00 0.00
Maximum of Months 0.144910E+10 0.126404E+10 0.115451E+10 0.452804E+09 0.701701E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.202846E+09 0.302978E+09 0.252585E+09 0.147514E+09 0.105071E+09 0.00 0.00
February 0.204399E+09 0.268438E+09 0.258365E+09 0.123566E+09 0.134799E+09 0.00 0.00
March 0.341096E+09 0.219821E+09 0.351486E+09 0.197471E+09 0.154015E+09 0.00 0.00
April 0.287081E+09 0.165718E+09 0.281326E+09 0.112163E+09 0.169163E+09 0.00 0.00
May 0.286012E+09 0.112528E+09 0.256350E+09 75570236.02 0.180780E+09 0.00 0.00
June 0.300112E+09 64582734.22 0.238791E+09 50000715.39 0.188790E+09 0.00 0.00
July 0.352137E+09 41151440.32 0.250806E+09 59415295.38 0.191390E+09 0.00 0.00
August 0.382823E+09 57199662.71 0.280840E+09 89116452.96 0.191723E+09 0.00 0.00
September 0.395442E+09 96962163.70 0.318126E+09 0.154389E+09 0.163737E+09 0.00 0.00
October 0.337384E+09 0.163919E+09 0.316120E+09 0.180735E+09 0.135385E+09 0.00 0.00
November 0.207920E+09 0.195629E+09 0.219436E+09 0.124158E+09 95278945.50 0.00 0.00
December 0.160813E+09 0.294397E+09 0.211211E+09 0.109477E+09 0.101735E+09 0.00 0.00
               
Annual Sum or Average 0.345807E+10 0.198332E+10 0.323544E+10 0.142358E+10 0.181187E+10 0.00 0.00
Minimum of Months 0.160813E+09 41151440.32 0.211211E+09 50000715.39 95278945.50 0.00 0.00
Maximum of Months 0.395442E+09 0.302978E+09 0.351486E+09 0.197471E+09 0.191723E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 49772.54 0.384328E+09 58680272.54 0.00 58680272.54 0.00 0.00
February 3172756.36 0.327886E+09 80754467.07 0.00 80754467.07 0.00 0.00
March 36356386.28 0.246026E+09 0.108439E+09 1562.16 0.108437E+09 0.00 0.00
April 77081112.86 0.159158E+09 0.133995E+09 755363.74 0.133239E+09 0.00 0.00
May 0.143388E+09 89916080.00 0.160409E+09 6664174.06 0.153745E+09 0.00 0.00
June 0.226183E+09 45484553.64 0.187254E+09 16223703.50 0.171030E+09 0.00 0.00
July 0.255203E+09 24972130.91 0.180216E+09 12514025.41 0.167702E+09 0.00 0.00
August 0.209030E+09 38276202.24 0.155876E+09 3065445.26 0.152811E+09 0.00 0.00
September 0.119746E+09 77140679.45 0.114231E+09 64654.69 0.114166E+09 0.00 0.00
October 48544431.66 0.159145E+09 88168115.16 0.00 88168115.16 0.00 0.00
November 12311471.01 0.217927E+09 57335547.11 0.00 57335547.11 0.00 0.00
December 571803.25 0.367913E+09 54922950.10 0.00 54922950.10 0.00 0.00
               
Annual Sum or Average 0.113164E+10 0.213817E+10 0.138028E+10 39288928.82 0.134099E+10 0.00 0.00
Minimum of Months 49772.54 24972130.91 54922950.10 0.00 54922950.10 0.00 0.00
Maximum of Months 0.255203E+09 0.384328E+09 0.187254E+09 16223703.50 0.171030E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.308598E+09 0.115882E+10 0.566194E+09 0.265075E+09 0.301120E+09 0.00 0.00
February 0.379260E+09 0.101218E+10 0.656931E+09 0.255635E+09 0.401296E+09 0.00 0.00
March 0.810355E+09 0.766708E+09 0.969908E+09 0.469965E+09 0.499943E+09 0.00 0.00
April 0.981746E+09 0.537532E+09 0.102747E+10 0.438719E+09 0.588755E+09 0.00 0.00
May 0.121742E+10 0.330863E+09 0.110284E+10 0.440614E+09 0.662228E+09 0.00 0.00
June 0.142182E+10 0.175436E+09 0.114339E+10 0.435537E+09 0.707853E+09 0.00 0.00
July 0.157155E+10 0.100830E+09 0.115198E+10 0.442948E+09 0.709035E+09 0.00 0.00
August 0.147358E+10 0.148990E+09 0.110838E+10 0.428618E+09 0.679767E+09 0.00 0.00
September 0.121454E+10 0.275631E+09 0.100821E+10 0.463832E+09 0.544378E+09 0.00 0.00
October 0.809235E+09 0.527477E+09 0.823057E+09 0.402701E+09 0.420356E+09 0.00 0.00
November 0.395216E+09 0.702823E+09 0.509063E+09 0.230385E+09 0.278679E+09 0.00 0.00
December 0.213546E+09 0.113347E+10 0.459449E+09 0.177349E+09 0.282101E+09 0.00 0.00
               
Annual Sum or Average 0.107969E+11 0.687075E+10 0.105269E+11 0.445138E+10 0.607551E+10 0.00 0.00
Minimum of Months 0.213546E+09 0.100830E+09 0.459449E+09 0.177349E+09 0.278679E+09 0.00 0.00
Maximum of Months 0.157155E+10 0.115882E+10 0.115198E+10 0.469965E+09 0.709035E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 67512274.20 0.122709E+10 0.323741E+09 80644929.94 0.243096E+09 0.00 0.00
February 0.133463E+09 0.104873E+10 0.434840E+09 0.101147E+09 0.333693E+09 0.00 0.00
March 0.437662E+09 0.785091E+09 0.665993E+09 0.223079E+09 0.442914E+09 0.00 0.00
April 0.722480E+09 0.530501E+09 0.843218E+09 0.299432E+09 0.543786E+09 0.00 0.00
May 0.103090E+10 0.322759E+09 0.982826E+09 0.354461E+09 0.628364E+09 0.00 0.00
June 0.131381E+10 0.171328E+09 0.107888E+10 0.393300E+09 0.685577E+09 0.00 0.00
July 0.143142E+10 99501822.84 0.106365E+10 0.384305E+09 0.679349E+09 0.00 0.00
August 0.124069E+10 0.146676E+09 0.952085E+09 0.321032E+09 0.631054E+09 0.00 0.00
September 0.858299E+09 0.271092E+09 0.753243E+09 0.270888E+09 0.482355E+09 0.00 0.00
October 0.444402E+09 0.526810E+09 0.538024E+09 0.176737E+09 0.361287E+09 0.00 0.00
November 0.155882E+09 0.714158E+09 0.306373E+09 75156906.30 0.231216E+09 0.00 0.00
December 34580007.17 0.120076E+10 0.264027E+09 40475388.60 0.223552E+09 0.00 0.00
               
Annual Sum or Average 0.787110E+10 0.704450E+10 0.820690E+10 0.272066E+10 0.548624E+10 0.00 0.00
Minimum of Months 34580007.17 99501822.84 0.264027E+09 40475388.60 0.223552E+09 0.00 0.00
Maximum of Months 0.143142E+10 0.122709E+10 0.107888E+10 0.393300E+09 0.685577E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.345676E+09 0.150851E+10 0.674403E+09 0.319623E+09 0.354780E+09 0.00 0.00
February 0.380354E+09 0.132541E+10 0.734746E+09 0.267733E+09 0.467013E+09 0.00 0.00
March 0.778079E+09 0.100793E+10 0.996487E+09 0.427868E+09 0.568619E+09 0.00 0.00
April 0.788648E+09 0.723114E+09 0.899833E+09 0.244662E+09 0.655170E+09 0.00 0.00
May 0.924124E+09 0.451103E+09 0.902940E+09 0.178177E+09 0.724763E+09 0.00 0.00
June 0.110979E+10 0.258778E+09 0.923048E+09 0.143484E+09 0.779565E+09 0.00 0.00
July 0.127027E+10 0.171507E+09 0.933835E+09 0.155846E+09 0.777989E+09 0.00 0.00
August 0.124732E+10 0.243363E+09 0.946182E+09 0.199731E+09 0.746450E+09 0.00 0.00
September 0.110655E+10 0.407054E+09 0.936753E+09 0.334658E+09 0.602095E+09 0.00 0.00
October 0.834755E+09 0.696548E+09 0.875946E+09 0.391603E+09 0.484343E+09 0.00 0.00
November 0.452942E+09 0.914228E+09 0.599666E+09 0.269015E+09 0.330651E+09 0.00 0.00
December 0.274758E+09 0.147548E+10 0.576618E+09 0.237206E+09 0.339412E+09 0.00 0.00
               
Annual Sum or Average 0.951327E+10 0.918304E+10 0.100005E+11 0.316961E+10 0.683085E+10 0.00 0.00
Minimum of Months 0.274758E+09 0.171507E+09 0.576618E+09 0.143484E+09 0.330651E+09 0.00 0.00
Maximum of Months 0.127027E+10 0.150851E+10 0.996487E+09 0.427868E+09 0.779565E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.259836E+09 0.116737E+10 0.531438E+09 0.235259E+09 0.296178E+09 0.00 0.00
February 0.352063E+09 0.102538E+10 0.639309E+09 0.236409E+09 0.402900E+09 0.00 0.00
March 0.830709E+09 0.772296E+09 0.987677E+09 0.482327E+09 0.505350E+09 0.00 0.00
April 0.955498E+09 0.550275E+09 0.998518E+09 0.405203E+09 0.593315E+09 0.00 0.00
May 0.122874E+10 0.342214E+09 0.110982E+10 0.451579E+09 0.658239E+09 0.00 0.00
June 0.151828E+10 0.185164E+09 0.121902E+10 0.495040E+09 0.723977E+09 0.00 0.00
July 0.158427E+10 0.107171E+09 0.116377E+10 0.446448E+09 0.717323E+09 0.00 0.00
August 0.148892E+10 0.154052E+09 0.111969E+10 0.437205E+09 0.682489E+09 0.00 0.00
September 0.118257E+10 0.280386E+09 0.982470E+09 0.445263E+09 0.537207E+09 0.00 0.00
October 0.770470E+09 0.527681E+09 0.788684E+09 0.365334E+09 0.423349E+09 0.00 0.00
November 0.382883E+09 0.702319E+09 0.498692E+09 0.219576E+09 0.279116E+09 0.00 0.00
December 0.219398E+09 0.114225E+10 0.464657E+09 0.180090E+09 0.284567E+09 0.00 0.00
               
Annual Sum or Average 0.107736E+11 0.695656E+10 0.105037E+11 0.439973E+10 0.610401E+10 0.00 0.00
Minimum of Months 0.219398E+09 0.107171E+09 0.464657E+09 0.180090E+09 0.279116E+09 0.00 0.00
Maximum of Months 0.158427E+10 0.116737E+10 0.121902E+10 0.495040E+09 0.723977E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 46769585.58 0.126487E+10 0.288984E+09 50829651.37 0.238155E+09 0.00 0.00
February 0.124406E+09 0.107930E+10 0.417218E+09 81920195.30 0.335298E+09 0.00 0.00
March 0.469261E+09 0.800411E+09 0.683762E+09 0.235441E+09 0.448321E+09 0.00 0.00
April 0.702782E+09 0.544812E+09 0.814262E+09 0.265915E+09 0.548347E+09 0.00 0.00
May 0.104380E+10 0.330762E+09 0.989801E+09 0.365426E+09 0.624375E+09 0.00 0.00
June 0.140650E+10 0.175180E+09 0.115451E+10 0.452804E+09 0.701701E+09 0.00 0.00
July 0.144062E+10 0.100607E+09 0.107544E+10 0.387805E+09 0.687637E+09 0.00 0.00
August 0.125575E+10 0.148548E+09 0.963394E+09 0.329618E+09 0.633776E+09 0.00 0.00
September 0.833429E+09 0.276240E+09 0.727503E+09 0.252319E+09 0.475183E+09 0.00 0.00
October 0.418576E+09 0.534275E+09 0.503650E+09 0.139370E+09 0.364280E+09 0.00 0.00
November 0.152580E+09 0.720102E+09 0.296002E+09 64348474.66 0.231653E+09 0.00 0.00
December 45039295.76 0.121251E+10 0.269235E+09 43216876.22 0.226018E+09 0.00 0.00
               
Annual Sum or Average 0.793951E+10 0.718761E+10 0.818376E+10 0.266902E+10 0.551474E+10 0.00 0.00
Minimum of Months 45039295.76 0.100607E+09 0.269235E+09 43216876.22 0.226018E+09 0.00 0.00
Maximum of Months 0.144062E+10 0.126487E+10 0.115451E+10 0.452804E+09 0.701701E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.356135E+09 0.597524E+09 0.463142E+09 0.270484E+09 0.192658E+09 0.00 0.00
February 0.356865E+09 0.530102E+09 0.473741E+09 0.226572E+09 0.247169E+09 0.00 0.00
March 0.610917E+09 0.411049E+09 0.644489E+09 0.362085E+09 0.282404E+09 0.00 0.00
April 0.519727E+09 0.297248E+09 0.515842E+09 0.205663E+09 0.310179E+09 0.00 0.00
May 0.530081E+09 0.179801E+09 0.470046E+09 0.138566E+09 0.331480E+09 0.00 0.00
June 0.561050E+09 93161085.66 0.437850E+09 91681789.03 0.346168E+09 0.00 0.00
July 0.659954E+09 51920415.03 0.459880E+09 0.108944E+09 0.350935E+09 0.00 0.00
August 0.712237E+09 77078482.33 0.514950E+09 0.163405E+09 0.351545E+09 0.00 0.00
September 0.730550E+09 0.146439E+09 0.583319E+09 0.283089E+09 0.300230E+09 0.00 0.00
October 0.619049E+09 0.278136E+09 0.579641E+09 0.331398E+09 0.248243E+09 0.00 0.00
November 0.372531E+09 0.368440E+09 0.402361E+09 0.227656E+09 0.174704E+09 0.00 0.00
December 0.280937E+09 0.583139E+09 0.387279E+09 0.200738E+09 0.186541E+09 0.00 0.00
               
Annual Sum or Average 0.631003E+10 0.361404E+10 0.593254E+10 0.261028E+10 0.332226E+10 0.00 0.00
Minimum of Months 0.280937E+09 51920415.03 0.387279E+09 91681789.03 0.174704E+09 0.00 0.00
Maximum of Months 0.730550E+09 0.597524E+09 0.644489E+09 0.362085E+09 0.351545E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.380460E+10 0.513365E+09 0.00 0.513365E+09 0.00 0.00
February 9147366.80 0.324892E+10 0.706481E+09 0.00 0.706481E+09 0.00 0.00
March 0.235361E+09 0.251745E+10 0.948675E+09 13666.58 0.948662E+09 0.00 0.00
April 0.531653E+09 0.168344E+10 0.117225E+10 6608306.45 0.116565E+10 0.00 0.00
May 0.104563E+10 0.100539E+10 0.140334E+10 58301586.40 0.134504E+10 0.00 0.00
June 0.174338E+10 0.564666E+09 0.163819E+10 0.141933E+09 0.149626E+10 0.00 0.00
July 0.198346E+10 0.368195E+09 0.157662E+10 0.109479E+09 0.146714E+10 0.00 0.00
August 0.160941E+10 0.518952E+09 0.136369E+10 26818075.25 0.133687E+10 0.00 0.00
September 0.880548E+09 0.912714E+09 0.999349E+09 565632.09 0.998783E+09 0.00 0.00
October 0.310813E+09 0.171619E+10 0.771340E+09 0.00 0.771340E+09 0.00 0.00
November 62808665.49 0.229907E+10 0.501601E+09 0.00 0.501601E+09 0.00 0.00
December 1847219.50 0.366090E+10 0.480494E+09 0.00 0.480494E+09 0.00 0.00
               
Annual Sum or Average 0.841406E+10 0.223005E+11 0.120754E+11 0.343720E+09 0.117317E+11 0.00 0.00
Minimum of Months 0.00 0.368195E+09 0.480494E+09 0.00 0.480494E+09 0.00 0.00
Maximum of Months 0.198346E+10 0.380460E+10 0.163819E+10 0.141933E+09 0.149626E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.390644E+10 0.513365E+09 0.00 0.513365E+09 0.00 0.00
February 6405423.21 0.333961E+10 0.706481E+09 0.00 0.706481E+09 0.00 0.00
March 0.218915E+09 0.258787E+10 0.948675E+09 13666.58 0.948662E+09 0.00 0.00
April 0.503596E+09 0.172793E+10 0.117225E+10 6608306.45 0.116565E+10 0.00 0.00
May 0.101371E+10 0.103125E+10 0.140334E+10 58301586.40 0.134504E+10 0.00 0.00
June 0.171711E+10 0.579766E+09 0.163819E+10 0.141933E+09 0.149626E+10 0.00 0.00
July 0.196095E+10 0.380437E+09 0.157662E+10 0.109479E+09 0.146714E+10 0.00 0.00
August 0.158766E+10 0.535047E+09 0.136369E+10 26818075.25 0.133687E+10 0.00 0.00
September 0.858207E+09 0.938697E+09 0.999349E+09 565632.09 0.998783E+09 0.00 0.00
October 0.288834E+09 0.176738E+10 0.771340E+09 0.00 0.771340E+09 0.00 0.00
November 55604843.39 0.237487E+10 0.501601E+09 0.00 0.501601E+09 0.00 0.00
December 1379999.43 0.376077E+10 0.480494E+09 0.00 0.480494E+09 0.00 0.00
               
Annual Sum or Average 0.821236E+10 0.229301E+11 0.120754E+11 0.343720E+09 0.117317E+11 0.00 0.00
Minimum of Months 0.00 0.380437E+09 0.480494E+09 0.00 0.480494E+09 0.00 0.00
Maximum of Months 0.196095E+10 0.390644E+10 0.163819E+10 0.141933E+09 0.149626E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.345618E+09 0.249277E+10 0.889900E+09 0.345708E+09 0.544191E+09 0.00 0.00
February 0.496500E+09 0.217343E+10 0.109172E+10 0.356767E+09 0.734956E+09 0.00 0.00
March 0.129538E+10 0.165154E+10 0.163583E+10 0.693012E+09 0.942813E+09 0.00 0.00
April 0.183058E+10 0.118743E+10 0.187060E+10 0.738109E+09 0.113249E+10 0.00 0.00
May 0.246535E+10 0.759748E+09 0.208556E+10 0.795026E+09 0.129053E+10 0.00 0.00
June 0.301606E+10 0.447362E+09 0.222215E+10 0.828784E+09 0.139336E+10 0.00 0.00
July 0.333036E+10 0.294792E+09 0.221552E+10 0.827200E+09 0.138832E+10 0.00 0.00
August 0.302583E+10 0.389959E+09 0.206036E+10 0.749604E+09 0.131076E+10 0.00 0.00
September 0.230884E+10 0.628848E+09 0.176137E+10 0.734682E+09 0.102668E+10 0.00 0.00
October 0.135876E+10 0.115446E+10 0.136102E+10 0.579413E+09 0.781607E+09 0.00 0.00
November 0.573352E+09 0.154045E+10 0.815403E+09 0.305531E+09 0.509872E+09 0.00 0.00
December 0.220878E+09 0.246833E+10 0.723449E+09 0.217818E+09 0.505631E+09 0.00 0.00
               
Annual Sum or Average 0.202675E+11 0.151891E+11 0.187329E+11 0.717166E+10 0.115612E+11 0.00 0.00
Minimum of Months 0.220878E+09 0.294792E+09 0.723449E+09 0.217818E+09 0.505631E+09 0.00 0.00
Maximum of Months 0.333036E+10 0.249277E+10 0.222215E+10 0.828784E+09 0.139336E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.782429E+09 0.268438E+10 0.135494E+10 0.688531E+09 0.666405E+09 0.00 0.00
February 0.826265E+09 0.236113E+10 0.144812E+10 0.576751E+09 0.871364E+09 0.00 0.00
March 0.160450E+10 0.180412E+10 0.196579E+10 0.921711E+09 0.104408E+10 0.00 0.00
April 0.153306E+10 0.130408E+10 0.171495E+10 0.525792E+09 0.118916E+10 0.00 0.00
May 0.171533E+10 0.819208E+09 0.167760E+10 0.372714E+09 0.130488E+10 0.00 0.00
June 0.197893E+10 0.477544E+09 0.167614E+10 0.282036E+09 0.139411E+10 0.00 0.00
July 0.228011E+10 0.322883E+09 0.171112E+10 0.314854E+09 0.139626E+10 0.00 0.00
August 0.231562E+10 0.448676E+09 0.177831E+10 0.425149E+09 0.135316E+10 0.00 0.00
September 0.216178E+10 0.727792E+09 0.182745E+10 0.720813E+09 0.110664E+10 0.00 0.00
October 0.169409E+10 0.124750E+10 0.173992E+10 0.843591E+09 0.896332E+09 0.00 0.00
November 0.948341E+09 0.164529E+10 0.119618E+10 0.579512E+09 0.616669E+09 0.00 0.00
December 0.617334E+09 0.263182E+10 0.115055E+10 0.510989E+09 0.639565E+09 0.00 0.00
               
Annual Sum or Average 0.184578E+11 0.164744E+11 0.192411E+11 0.676244E+10 0.124786E+11 0.00 0.00
Minimum of Months 0.617334E+09 0.322883E+09 0.115055E+10 0.282036E+09 0.616669E+09 0.00 0.00
Maximum of Months 0.231562E+10 0.268438E+10 0.196579E+10 0.921711E+09 0.139626E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January -3.4 -4.9 -8.7 5.96 -14.4 41.15 62.17 0.00
February -4.2 -5.4 -8.1 6.66 -15.1 65.72 71.39 0.00
March 2.67 0.66 -2.8 5.20 -8.9 69.76 141.76 0.00
April 7.47 4.95 1.92 5.29 -2.7 89.32 159.79 0.00
May 13.73 9.66 5.81 4.79 3.34 93.75 203.34 0.03
June 18.63 14.47 11.49 5.10 8.69 105.42 236.95 0.00
July 22.03 18.19 16.11 4.43 13.39 102.98 214.28 0.00
August 20.69 16.39 13.72 4.23 11.88 99.24 178.64 0.00
September 16.55 13.42 11.22 4.10 7.08 75.66 154.97 0.03
October 9.73 7.36 4.97 4.79 0.13 58.70 104.01 0.00
November 6.03 3.70 0.77 5.87 -3.2 41.19 58.47 0.00
December -2.2 -3.2 -5.3 6.59 -12.0 40.52 44.30 0.00
                 
Annual Sum or Average 9.05 6.33 3.49 5.24 -0.9 73.64 136.19 0.01
Minimum of Months -4.2 -5.4 -8.7 4.10 -15.1 40.52 44.30 0.00
Maximum of Months 22.03 18.19 16.11 6.66 13.39 105.42 236.95 0.03



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 11.70 11-JAN-15:00 10.14 8.90 13.40 7.15 65.50 1.00
February 12.80 22-FEB-17:00 6.18 -2.2 14.90 3.48 0.00 0.00
March 26.10 15-MAR-13:00 16.06 9.40 6.70 14.65 249.50 400.00
April 21.10 08-APR-12:00 13.43 7.80 8.20 11.46 330.00 283.50
May 26.10 10-MAY-13:00 17.84 13.30 5.20 13.35 258.50 457.00
June 30.60 12-JUN-13:00 20.23 15.00 8.20 17.93 252.00 572.00
July 31.70 21-JUL-13:00 21.73 17.20 5.20 22.47 330.00 231.00
August 30.60 10-AUG-13:00 20.24 15.00 5.70 19.70 220.50 635.00
September 27.20 16-SEP-13:09 19.53 15.68 8.80 17.30 207.00 564.67
October 22.20 11-OCT-12:00 14.14 8.30 6.20 6.95 121.00 665.00
November 19.40 05-NOV-13:00 13.85 10.00 12.40 14.84 133.00 3.50
December 15.00 01-DEC-10:00 12.41 10.60 12.90 10.69 56.50 11.50
                 
Annual Sum or Average                
Minimum of Months 11.70   6.18 -2.2 5.20 3.48 0.00 0.00
Maximum of Months 31.70   21.73 17.20 14.90 22.47 330.00 665.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -13.9 31-JAN-01:00 -14.5 -17.2 1.50 -25.9 0.00 0.00
February -16.7 07-FEB-06:00 -17.3 -20.6 6.20 -35.1 0.00 0.00
March -13.3 07-MAR-05:19 -13.9 -16.7 2.43 -32.2 0.00 0.00
April -4.4 17-APR-05:00 -5.4 -7.8 2.10 -20.5 35.00 151.50
May 1.70 01-MAY-04:00 0.96 0.00 0.00 -14.2 0.00 0.00
June 6.70 04-JUN-04:00 5.40 3.90 2.10 -7.3 20.00 104.00
July 11.70 03-JUL-03:00 11.07 10.60 2.10 -1.2 0.00 0.00
August 11.10 01-AUG-04:00 10.75 10.60 2.10 -0.8 0.00 0.00
September 6.10 05-SEP-05:00 5.59 5.00 2.10 -6.2 24.50 41.00
October -2.8 17-OCT-04:10 -3.2 -4.0 2.18 -19.4 0.00 0.00
November -3.9 24-NOV-05:00 -4.5 -5.6 2.10 -18.1 0.00 0.00
December -18.9 11-DEC-05:00 -19.4 -23.3 2.10 -35.1 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -18.9   -19.4 -23.3 0.00 -35.1 0.00 0.00
Maximum of Months 11.70   11.07 10.60 6.20 -0.8 35.00 151.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.21 11-JAN-17:00 11.10 9.40 10.30 6.55 0.00 0.00
February 6.89 01-FEB-03:00 7.20 6.70 3.60 2.22 0.00 0.00
March 17.83 14-MAR-12:00 25.00 13.90 6.20 14.10 197.00 562.50
April 13.78 08-APR-13:00 20.60 8.90 10.30 9.72 268.50 325.50
May 18.19 10-MAY-14:00 26.10 13.90 5.20 16.85 273.00 238.00
June 23.75 27-JUN-12:00 30.60 21.10 9.30 21.09 304.00 606.00
July 24.79 21-JUL-01:00 28.90 23.30 8.80 27.46 0.00 0.00
August 23.42 13-AUG-15:00 29.40 21.10 9.80 19.87 212.00 276.00
September 21.17 15-SEP-11:00 26.10 18.90 3.60 16.30 204.00 464.50
October 15.23 12-OCT-14:00 18.30 13.30 10.30 9.13 148.00 367.50
November 13.96 05-NOV-14:00 18.30 11.10 11.30 14.10 72.00 6.00
December 12.41 01-DEC-10:00 15.00 10.60 12.90 10.69 56.50 11.50
                 
Annual Sum or Average                
Minimum of Months 6.89   7.20 6.70 3.60 2.22 0.00 0.00
Maximum of Months 24.79   30.60 23.30 12.90 27.46 304.00 606.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 9.40 11-JAN-13:00 10.00 9.66 12.90 5.54 95.50 2.00
February 6.70 01-FEB-04:10 7.20 6.89 3.52 2.22 0.00 0.00
March 15.00 14-MAR-10:20 20.33 16.97 4.80 10.50 159.17 592.83
April 11.10 08-APR-21:00 13.90 12.23 12.90 9.72 0.00 0.00
May 15.60 17-MAY-12:00 16.70 15.97 6.70 13.54 184.00 0.00
June 21.70 27-JUN-14:00 25.60 22.78 8.20 16.85 255.50 530.00
July 23.30 20-JUL-20:00 25.60 24.03 4.60 24.16 0.00 0.00
August 21.70 14-AUG-03:20 23.70 22.19 5.00 21.90 0.00 0.00
September 20.00 15-SEP-18:00 21.70 20.51 0.00 19.52 0.00 0.00
October 14.40 01-OCT-07:19 14.60 14.50 3.77 10.56 67.50 30.17
November 11.70 05-NOV-15:00 12.80 12.14 7.20 8.74 28.00 4.50
December 11.10 01-DEC-12:00 13.90 12.22 10.30 6.35 158.00 84.50
                 
Annual Sum or Average                
Minimum of Months 6.70   7.20 6.89 0.00 2.22 0.00 0.00
Maximum of Months 23.30   25.60 24.03 12.90 24.16 255.50 592.83



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 7.32 12.49 0.00
February 18.00 13.00 16.00 6.57 19.26 0.00
March 18.00 13.00 16.00 7.29 28.63 0.00
April 18.00 13.00 16.00 9.34 37.44 0.00
May 18.00 13.00 16.00 12.19 46.60 0.00
June 18.00 13.00 16.00 15.07 54.01 0.00
July 18.00 13.00 16.00 17.20 50.29 0.00
August 18.00 13.00 16.00 18.01 43.20 0.00
September 18.00 13.00 16.00 17.27 32.93 0.00
October 18.00 13.00 16.00 15.18 21.28 0.00
November 18.00 13.00 16.00 12.32 12.54 0.00
December 18.00 13.00 16.00 9.45 10.96 0.00
             
Annual Sum or Average 18.00 13.00 16.00 12.30 30.86 0.00
Minimum of Months 18.00 13.00 16.00 6.57 10.96 0.00
Maximum of Months 18.00 13.00 16.00 18.01 54.01 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770526E+10 -0.754278E+10 0.00 0.00 744.00 0.00 -162481851.0 81.21 0.00 0.00
February 0.696275E+10 -0.681596E+10 0.00 0.00 672.00 0.00 -146787928.8 81.21 0.00 0.00
March 0.770347E+10 -0.754147E+10 0.00 0.00 744.00 0.00 -162005502.1 81.21 0.00 0.00
April 0.746502E+10 -0.730860E+10 0.00 0.00 720.00 0.00 -156414287.7 81.21 0.00 0.00
May 0.770439E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -161601845.7 81.21 0.00 0.00
June 0.745685E+10 -0.730052E+10 0.00 0.00 720.00 0.00 -156323635.6 81.21 0.00 0.00
July 0.771236E+10 -0.755084E+10 0.00 0.00 744.00 0.00 -161519609.4 81.21 0.00 0.00
August 0.770435E+10 -0.754280E+10 0.00 0.00 744.00 0.00 -161549930.9 81.21 0.00 0.00
September 0.746632E+10 -0.730992E+10 0.00 0.00 720.00 0.00 -156392114.8 81.21 0.00 0.00
October 0.770301E+10 -0.754144E+10 0.00 0.00 744.00 0.00 -161566244.1 81.21 0.00 0.00
November 0.744898E+10 -0.729243E+10 0.00 0.00 720.00 0.00 -156548650.7 81.21 0.00 0.00
December 0.771326E+10 -0.755085E+10 0.00 0.00 744.00 0.00 -162409538.5 81.21 0.00 0.00
                     
Annual Sum or Average 0.907460E+11 -0.888404E+11 0.00 0.00 8760.00 0.00 -0.190560E+10 81.21 0.00 0.00
Minimum of Months 0.696275E+10 -0.755085E+10 0.00 0.00 672.00 0.00 -162481851.0 81.21 0.00 0.00
Maximum of Months 0.771326E+10 -0.681596E+10 0.00 0.00 744.00 0.00 -146787928.8 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.127574E+12 -0.125826E+12 0.00 0.00 744.00 0.00 -0.174824E+10 81.37 0.00 0.00
February 0.116176E+12 -0.114591E+12 0.00 0.00 672.00 0.00 -0.158450E+10 81.33 0.00 0.00
March 0.127667E+12 -0.125896E+12 0.00 0.00 744.00 0.00 -0.177112E+10 81.38 0.00 0.00
April 0.119663E+12 -0.117948E+12 0.00 0.00 720.00 0.00 -0.171492E+10 81.28 0.00 0.00
May 0.118736E+12 -0.116961E+12 0.00 0.00 744.00 0.00 -0.177419E+10 81.27 0.00 0.00
June 0.110145E+12 -0.108441E+12 0.00 0.00 720.00 0.00 -0.170461E+10 81.25 0.00 0.00
July 0.110186E+12 -0.108435E+12 0.00 0.00 744.00 0.00 -0.175107E+10 81.25 0.00 0.00
August 0.108790E+12 -0.107053E+12 0.00 0.00 744.00 0.00 -0.173751E+10 81.25 0.00 0.00
September 0.106497E+12 -0.104822E+12 0.00 0.00 720.00 0.00 -0.167496E+10 81.25 0.00 0.00
October 0.113593E+12 -0.111865E+12 0.00 0.00 744.00 0.00 -0.172833E+10 81.25 0.00 0.00
November 0.114645E+12 -0.112972E+12 0.00 0.00 720.00 0.00 -0.167303E+10 81.26 0.00 0.00
December 0.123413E+12 -0.121678E+12 0.00 0.00 744.00 0.00 -0.173412E+10 81.28 0.00 0.00
                     
Annual Sum or Average 0.139709E+13 -0.137649E+13 0.00 0.00 8760.00 0.00 -0.205966E+11 81.28 0.00 0.00
Minimum of Months 0.106497E+12 -0.125896E+12 0.00 0.00 672.00 0.00 -0.177419E+10 81.25 0.00 0.00
Maximum of Months 0.127667E+12 -0.104822E+12 0.00 0.00 744.00 0.00 -0.158450E+10 81.38 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.769759E+11 -0.754878E+11 0.00 0.00 744.00 0.00 -0.148804E+10 58.98 0.00 0.00
February 0.705405E+11 -0.691874E+11 0.00 0.00 672.00 0.00 -0.135302E+10 58.98 0.00 0.00
March 0.771252E+11 -0.756056E+11 0.00 0.00 744.00 0.00 -0.151958E+10 58.99 0.00 0.00
April 0.717035E+11 -0.702279E+11 0.00 0.00 720.00 0.00 -0.147563E+10 58.99 0.00 0.00
May 0.699381E+11 -0.684098E+11 0.00 0.00 744.00 0.00 -0.152836E+10 58.98 0.00 0.00
June 0.636118E+11 -0.621493E+11 0.00 0.00 720.00 0.00 -0.146252E+10 58.98 0.00 0.00
July 0.625387E+11 -0.610420E+11 0.00 0.00 744.00 0.00 -0.149677E+10 58.98 0.00 0.00
August 0.613914E+11 -0.599132E+11 0.00 0.00 744.00 0.00 -0.147828E+10 58.98 0.00 0.00
September 0.604251E+11 -0.590037E+11 0.00 0.00 720.00 0.00 -0.142143E+10 58.98 0.00 0.00
October 0.654623E+11 -0.639969E+11 0.00 0.00 744.00 0.00 -0.146542E+10 58.98 0.00 0.00
November 0.673990E+11 -0.659805E+11 0.00 0.00 720.00 0.00 -0.141850E+10 58.98 0.00 0.00
December 0.738411E+11 -0.723687E+11 0.00 0.00 744.00 0.00 -0.147242E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.820953E+12 -0.803373E+12 0.00 0.00 8760.00 0.00 -0.175800E+11 58.98 0.00 0.00
Minimum of Months 0.604251E+11 -0.756056E+11 0.00 0.00 672.00 0.00 -0.152836E+10 58.98 0.00 0.00
Maximum of Months 0.771252E+11 -0.590037E+11 0.00 0.00 744.00 0.00 -0.135302E+10 58.99 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.93 0.93 01-JAN-08:39 3634.60 32.78 237.83 251.83 2410.08 32.37 239.50 216.33
February 262.50 0.93 0.93 01-FEB-09:09 4614.41 32.83 248.67 257.83 931.82 25.54 224.67 230.00
March 339.33 0.93 0.93 01-MAR-07:19 4639.74 27.00 196.50 327.50 653.51 21.95 232.33 278.00
April 371.17 0.93 0.93 01-APR-06:49 1411.14 19.84 78.17 347.83 548.52 21.56 235.17 289.33
May 332.17 0.93 0.93 01-MAY-06:10 1243.41 20.14 70.33 386.50 508.37 21.89 247.00 307.67
June 430.67 0.93 0.93 01-JUN-05:49 1144.38 19.81 67.17 394.50 462.70 21.54 286.67 324.33
July 439.00 0.93 0.93 01-JUL-05:49 1204.77 19.72 87.33 402.33 480.11 21.46 281.67 325.83
August 406.00 0.93 0.93 01-AUG-05:00 1450.54 20.13 111.33 378.67 565.04 21.85 283.83 316.17
September 289.17 0.93 0.93 01-SEP-07:40 1824.04 21.36 129.33 326.33 707.98 22.57 233.33 275.17
October 314.33 0.93 0.93 01-OCT-06:00 5473.74 32.38 279.83 301.17 742.05 22.78 208.00 268.33
November 258.33 0.93 0.93 01-NOV-07:30 3460.69 32.68 242.17 244.33 1382.59 29.01 216.00 210.33
December 230.67 0.93 0.93 01-DEC-07:00 3037.29 31.55 212.83 240.67 2243.96 32.56 219.83 197.33
                         
Annual Sum or Average 3928.50 0.93     2571.78 24.85 1961.50 3859.50 866.99 23.91 2908.00 3238.83
Minimum of Months 230.67 0.93 0.93   1144.38 19.72 67.17 240.67 462.70 21.46 208.00 197.33
Maximum of Months 439.00 0.93 0.93   5473.74 32.83 279.83 402.33 2410.08 32.56 286.67 325.83



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.62 0.61 01-JAN-08:39 3936.81 32.92 238.67 262.83 2710.78 32.48 241.67 236.50
February 262.50 0.62 0.61 01-FEB-08:50 4938.88 32.94 249.17 265.33 1253.48 25.66 231.67 246.33
March 339.33 0.62 0.61 01-MAR-07:10 4986.77 27.26 207.67 337.33 999.45 22.09 223.67 307.50
April 371.17 0.62 0.61 01-APR-06:40 1676.75 20.33 110.83 361.33 813.23 21.88 250.50 329.00
May 332.17 0.62 0.61 01-MAY-05:00 1495.58 20.61 110.67 404.17 759.82 22.18 265.50 358.67
June 430.67 0.62 0.61 01-JUN-05:40 1352.47 20.42 133.67 410.67 670.10 21.97 310.00 372.17
July 439.00 0.63 0.61 01-JUL-05:30 1419.52 20.33 142.50 415.83 694.13 21.88 309.17 375.33
August 406.00 0.62 0.61 01-AUG-05:49 1703.24 20.64 154.83 393.50 816.81 22.18 302.83 355.83
September 289.17 0.62 0.61 01-SEP-07:40 2182.97 21.56 124.33 337.83 1065.73 22.66 253.00 307.33
October 314.33 0.62 0.61 01-OCT-06:00 5804.79 32.57 281.33 311.00 1073.05 22.97 214.83 287.17
November 258.33 0.62 0.61 01-NOV-07:19 3727.07 32.78 243.17 255.33 1650.26 29.14 224.00 229.50
December 230.67 0.62 0.61 01-DEC-07:49 3308.39 31.69 215.17 251.83 2513.75 32.69 221.33 222.83
                         
Annual Sum or Average 3928.50 0.62     2848.75 25.21 2212.00 4007.00 1143.10 24.16 3048.17 3628.17
Minimum of Months 230.67 0.62 0.61   1352.47 20.33 110.67 251.83 670.10 21.88 214.83 222.83
Maximum of Months 439.00 0.63 0.61   5804.79 32.94 281.33 415.83 2710.78 32.69 310.00 375.33



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.81 0.80 01-JAN-08:50 441.28 15.11 0.00 235.17 192.87 18.39 0.00 116.00
February 262.50 0.81 0.80 01-FEB-09:09 581.15 16.18 0.00 250.67 250.04 19.35 0.33 184.83
March 339.33 0.81 0.80 01-MAR-07:40 590.85 16.73 0.00 325.67 266.68 19.95 0.17 256.17
April 371.17 0.81 0.80 01-APR-06:49 688.84 17.35 0.00 360.00 306.42 20.51 68.50 310.00
May 332.17 0.80 0.80 01-MAY-05:40 792.24 18.57 8.67 410.33 371.70 22.33 188.67 363.00
June 430.67 0.80 0.80 01-JUN-05:40 930.84 20.92 71.83 421.17 424.98 22.78 261.33 393.00
July 439.00 0.81 0.80 01-JUL-04:00 887.55 20.46 67.00 425.67 402.63 22.56 253.33 391.33
August 406.00 0.80 0.80 01-AUG-05:49 780.73 18.16 5.33 396.00 359.65 21.33 163.17 357.50
September 289.17 0.81 0.80 01-SEP-07:40 623.56 17.52 0.00 330.83 302.68 20.74 49.33 269.33
October 314.33 0.81 0.80 01-OCT-06:00 529.13 16.07 0.00 292.50 236.12 19.32 0.00 203.33
November 258.33 0.81 0.80 01-NOV-07:40 431.80 14.80 0.00 231.00 187.06 18.01 0.00 112.17
December 230.67 0.81 0.80 01-DEC-08:30 451.45 15.09 0.00 225.67 192.50 18.32 0.00 103.50
                         
Annual Sum or Average 3928.50 0.81     675.65 17.61 152.83 3904.67 306.18 20.59 984.83 3060.17
Minimum of Months 230.67 0.80 0.80   431.80 14.80 0.00 225.67 187.06 18.01 0.00 103.50
Maximum of Months 439.00 0.81 0.80   930.84 20.92 71.83 425.67 424.98 22.78 261.33 393.00



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.81 0.80 01-JAN-08:50 441.28 15.11 0.00 235.17 192.87 18.39 0.00 116.00
February 262.50 0.81 0.80 01-FEB-09:09 581.15 16.18 0.00 250.67 250.04 19.35 0.33 184.83
March 339.33 0.81 0.80 01-MAR-07:40 590.85 16.73 0.00 325.67 266.68 19.95 0.17 256.17
April 371.17 0.81 0.80 01-APR-06:49 688.84 17.35 0.00 360.00 306.42 20.51 68.50 310.00
May 332.17 0.80 0.80 01-MAY-05:40 792.24 18.57 8.67 410.33 371.70 22.33 188.67 363.00
June 430.67 0.80 0.80 01-JUN-05:40 930.84 20.92 71.83 421.17 424.98 22.78 261.50 393.00
July 439.00 0.81 0.80 01-JUL-04:00 887.55 20.46 67.00 425.67 402.63 22.56 253.33 391.33
August 406.00 0.80 0.80 01-AUG-05:49 780.73 18.16 5.33 396.00 359.65 21.33 163.17 357.50
September 289.17 0.81 0.80 01-SEP-07:40 623.56 17.52 0.00 330.83 302.68 20.74 49.33 269.33
October 314.33 0.81 0.80 01-OCT-06:00 529.13 16.07 0.00 292.50 236.12 19.32 0.00 203.33
November 258.33 0.81 0.80 01-NOV-07:40 431.80 14.80 0.00 231.00 187.06 18.01 0.00 112.17
December 230.67 0.81 0.80 01-DEC-08:30 451.45 15.09 0.00 225.67 192.50 18.32 0.00 103.50
                         
Annual Sum or Average 3928.50 0.81     675.65 17.61 152.83 3904.67 306.18 20.59 985.00 3060.17
Minimum of Months 230.67 0.80 0.80   431.80 14.80 0.00 225.67 187.06 18.01 0.00 103.50
Maximum of Months 439.00 0.81 0.80   930.84 20.92 71.83 425.67 424.98 22.78 261.50 393.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.810947E+11 100023.81 04-JAN-08:10 0.00 0.00 0.00 0.00 0.00
February 0.817499E+11 118722.33 07-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.423040E+11 142878.00 12-MAR-07:36 0.00 0.00 0.00 0.00 0.00
April 0.228005E+11 158562.17 03-APR-22:18 0.00 0.00 0.00 0.00 0.00
May 0.182825E+11 153602.39 02-MAY-00:33 0.00 0.00 0.00 0.00 0.00
June 0.516103E+10 142709.79 13-JUN-23:50 0.00 0.00 0.00 0.00 0.00
July 0.348171E+09 28646.41 03-JUL-04:30 0.00 0.00 0.00 0.00 0.00
August 0.109579E+10 34917.90 03-AUG-05:00 0.00 0.00 0.00 0.00 0.00
September 0.835363E+10 147165.73 30-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.266256E+11 158625.85 14-OCT-02:14 0.00 0.00 0.00 0.00 0.00
November 0.205354E+11 154039.00 19-NOV-23:58 0.00 0.00 0.00 0.00 0.00
December 0.673993E+11 153048.34 14-DEC-07:43 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.375751E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.348171E+09 28646.41   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.817499E+11 158625.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.422601E+10 2827.48 04-JAN-07:40 0.00 0.00 0.00 0.00 0.00
February 0.376007E+10 3237.40 07-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.200905E+10 2754.24 12-MAR-06:42 0.00 0.00 0.00 0.00 0.00
April 0.117217E+10 1937.53 29-APR-06:08 0.00 0.00 0.00 0.00 0.00
May 0.345710E+09 2131.06 02-MAY-23:56 0.00 0.00 0.00 0.00 0.00
June 30533626.00 1538.41 15-JUN-02:15 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 7690858.12 955.08 31-AUG-05:08 0.00 0.00 0.00 0.00 0.00
September 0.111576E+09 2022.81 30-SEP-01:35 0.00 0.00 0.00 0.00 0.00
October 0.958469E+09 4403.36 14-OCT-08:00 0.00 0.00 0.00 0.00 0.00
November 0.201093E+10 2311.65 19-NOV-16:43 0.00 0.00 0.00 0.00 0.00
December 0.423329E+10 2898.50 11-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.188655E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.423329E+10 4403.36   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.310320E+09 629.94 29-JAN-16:00 0.00 0.00 0.00 0.00 0.00
February 0.289902E+09 768.68 06-FEB-13:30 0.00 0.00 0.00 0.00 0.00
March 18492793.41 311.82 20-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 1229819.89 258.26 17-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 12046656.02 265.44 23-NOV-16:00 0.00 0.00 0.00 0.00 0.00
December 0.285738E+09 642.62 11-DEC-10:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.917729E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.310320E+09 768.68   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.182085E+10 1286.03 31-JAN-13:20 0.00 0.00 0.00 0.00 0.00
February 0.173875E+10 1569.97 07-FEB-04:50 0.00 0.00 0.00 0.00 0.00
March 0.800168E+09 1199.48 07-MAR-05:00 0.00 0.00 0.00 0.00 0.00
April 0.123398E+09 872.48 18-APR-10:34 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 11970117.57 439.26 30-OCT-09:34 0.00 0.00 0.00 0.00 0.00
November 0.239267E+09 751.39 24-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.162056E+10 1440.87 11-DEC-04:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.635496E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.182085E+10 1569.97   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.137877E+10 859.08 31-JAN-18:00 0.00 0.00 0.00 0.00 0.00
February 0.129816E+10 989.40 07-FEB-11:10 0.00 0.00 0.00 0.00 0.00
March 0.649558E+09 734.28 07-MAR-05:00 0.00 0.00 0.00 0.00 0.00
April 0.141194E+09 535.70 18-APR-10:34 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 27119325.50 496.31 29-OCT-15:05 0.00 0.00 0.00 0.00 0.00
November 0.278919E+09 564.98 19-NOV-16:43 0.00 0.00 0.00 0.00 0.00
December 0.125594E+10 912.11 11-DEC-10:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.502966E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137877E+10 989.40   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.379742E+09 2838.22 17-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 0.367906E+09 2711.53 07-FEB-04:50 0.00 0.00 0.00 0.00 0.00
March 0.243231E+09 5223.87 17-MAR-01:10 0.00 0.00 0.00 0.00 0.00
April 98915927.38 6665.20 28-APR-01:43 0.00 0.00 0.00 0.00 0.00
May 0.159872E+09 11147.13 27-MAY-04:55 0.00 0.00 0.00 0.00 0.00
June 46106355.87 10146.54 10-JUN-02:55 0.00 0.00 0.00 0.00 0.00
July 3216982.29 2806.35 13-JUL-03:35 0.00 0.00 0.00 0.00 0.00
August 5922402.50 1629.98 03-AUG-04:00 0.00 0.00 0.00 0.00 0.00
September 73604787.81 10583.93 12-SEP-02:55 0.00 0.00 0.00 0.00 0.00
October 0.168216E+09 10710.54 02-OCT-03:25 0.00 0.00 0.00 0.00 0.00
November 0.144344E+09 11251.37 10-NOV-04:55 0.00 0.00 0.00 0.00 0.00
December 0.361705E+09 2711.52 11-DEC-05:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.205278E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3216982.29 1629.98   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.379742E+09 11251.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.334368E+10 5671.96 25-JAN-09:20 0.00 0.00 0.00 0.00 0.00
February 0.282456E+10 7300.36 06-FEB-09:05 0.00 0.00 0.00 0.00 0.00
March 0.687023E+09 4556.10 17-MAR-08:03 0.00 0.00 0.00 0.00 0.00
April 0.296880E+09 4633.10 11-APR-10:33 0.00 0.00 0.00 0.00 0.00
May 43494465.05 2661.11 12-MAY-11:55 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 88936.58 148.23 31-AUG-10:50 0.00 0.00 0.00 0.00 0.00
September 16818608.54 2262.10 29-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 0.175199E+09 3699.63 23-OCT-08:33 0.00 0.00 0.00 0.00 0.00
November 0.105695E+10 5136.64 20-NOV-09:10 0.00 0.00 0.00 0.00 0.00
December 0.358778E+10 6240.86 11-DEC-09:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.120325E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.358778E+10 7300.36   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.186741E+10 9594.21 29-JAN-16:00 0.00 0.00 0.00 0.00 0.00
February 0.162006E+10 12025.88 06-FEB-12:00 0.00 0.00 0.00 0.00 0.00
March 24077361.43 2655.56 20-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 39148105.68 2729.13 30-NOV-15:00 0.00 0.00 0.00 0.00 0.00
December 0.189965E+10 9215.33 12-DEC-14:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.545034E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189965E+10 12025.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.113723E+11 7869.29 29-JAN-16:00 0.00 0.00 0.00 0.00 0.00
February 0.100079E+11 9603.22 06-FEB-09:03 0.00 0.00 0.00 0.00 0.00
March 0.334107E+10 7190.15 12-MAR-06:42 0.00 0.00 0.00 0.00 0.00
April 0.592657E+09 5042.20 18-APR-10:34 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.202599E+09 6610.49 29-OCT-15:05 0.00 0.00 0.00 0.00 0.00
November 0.312968E+10 7714.24 19-NOV-16:43 0.00 0.00 0.00 0.00 0.00
December 0.111182E+11 8729.81 11-DEC-09:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.397644E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.113723E+11 9603.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.735022E+10 5050.73 10-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.660950E+10 6099.42 07-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.293347E+10 4582.79 07-MAR-07:05 0.00 0.00 0.00 0.00 0.00
April 0.712023E+09 3023.23 17-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 113876.02 183.09 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.486078E+09 3030.23 29-OCT-16:03 0.00 0.00 0.00 0.00 0.00
November 0.214824E+10 3344.65 19-NOV-18:49 0.00 0.00 0.00 0.00 0.00
December 0.701373E+10 5734.78 11-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.272534E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.735022E+10 6099.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 57544.81 63.85 06-FEB-15:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 57544.81     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 57544.81 63.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 52548.75 87.58 07-FEB-04:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 622434.64 1278.00 13-MAY-02:35 0.00 0.00 0.00 0.00 0.00
June 528370.77 1470.17 10-JUN-02:55 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 697750.94 1208.35 30-SEP-01:35 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 515329.12 1717.76 06-NOV-03:45 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2416434.22     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 697750.94 1717.76   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.113159E+11 12551.79 30-JAN-19:00 0.00 0.00 0.00 0.00 0.00
February 0.116272E+11 14692.08 07-FEB-09:00 0.00 0.00 0.00 0.00 0.00
March 0.411552E+10 10790.38 07-MAR-05:30 0.00 0.00 0.00 0.00 0.00
April 0.335629E+09 4318.30 17-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 11034.83 0.44 29-MAY-10:10 0.00 0.00 0.00 0.00 0.00
June 20994.11 0.43 27-JUN-01:10 0.00 0.00 0.00 0.00 0.00
July 23061.03 0.43 06-JUL-10:10 0.00 0.00 0.00 0.00 0.00
August 23500.52 0.43 19-AUG-08:08 0.00 0.00 0.00 0.00 0.00
September 15215.30 0.43 26-SEP-15:40 0.00 0.00 0.00 0.00 0.00
October 71013783.45 2533.56 17-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.444457E+09 3959.74 24-NOV-06:00 0.00 0.00 0.00 0.00 0.00
December 0.939327E+10 14862.09 11-DEC-06:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.373031E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 11034.83 0.43   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.116272E+11 14862.09   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.799653E+10 12323.04 08-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.702552E+10 12323.35 03-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.346252E+10 12322.52 05-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.149772E+10 12192.90 16-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.185992E+09 5151.43 12-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 9594276.35 3128.78 09-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 3397863.68 2145.15 22-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 5530279.63 2137.16 05-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 71770195.06 5455.75 29-SEP-08:62 0.00 0.00 0.00 0.00 0.00
October 0.142794E+10 12097.13 17-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.338952E+10 12147.56 24-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.776298E+10 12323.51 07-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.328390E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3397863.68 2137.16   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.799653E+10 12323.51   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.901387E+10 12224.75 08-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.787805E+10 12224.97 03-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.433542E+10 12224.18 05-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.179206E+10 12095.90 16-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.225955E+09 5322.79 12-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 9526524.65 3123.43 09-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 3493433.19 2242.84 09-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 6208648.51 2424.71 05-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 98293035.33 5985.58 29-SEP-08:62 0.00 0.00 0.00 0.00 0.00
October 0.185681E+10 12039.62 17-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.399794E+10 12050.75 24-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.853706E+10 12225.12 07-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.377547E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3493433.19 2242.84   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.901387E+10 12225.12   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.211253E+11 26757.08 24-JAN-06:00 0.00 0.00 0.00 0.00 0.00
February 0.192839E+11 31821.61 07-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.107009E+10 11899.52 21-MAR-04:00 0.00 0.00 0.00 0.00 0.00
April 0.247663E+09 8991.55 17-APR-05:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.224877E+10 15744.46 24-NOV-06:00 0.00 0.00 0.00 0.00 0.00
December 0.220223E+11 27127.58 10-DEC-06:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.659980E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.220223E+11 31821.61   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.367612E+11 67545.77 23-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.330901E+11 67549.36 07-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.185906E+11 67541.54 06-MAR-16:01 0.00 0.00 0.00 0.00 0.00
April 0.403264E+10 65140.31 17-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.198323E+09 40277.63 29-MAY-15:04 0.00 0.00 0.00 0.00 0.00
June 40130298.55 32872.97 09-JUN-15:04 0.00 0.00 0.00 0.00 0.00
July 22947848.92 17469.05 04-JUL-18:07 0.00 0.00 0.00 0.00 0.00
August 28846927.95 19926.07 18-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 0.106400E+09 30289.51 10-SEP-15:04 0.00 0.00 0.00 0.00 0.00
October 0.358904E+10 65204.37 17-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.111848E+11 65458.54 24-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.339112E+11 67551.39 09-DEC-16:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.141556E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 22947848.92 17469.05   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.367612E+11 67551.39   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.779252E+10 12000.71 08-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.687103E+10 12001.00 03-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.352213E+10 11998.21 06-MAR-19:01 0.00 0.00 0.00 0.00 0.00
April 0.148191E+10 11812.08 16-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.213610E+09 4730.65 12-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 16980610.75 1997.07 07-JUN-15:05 0.00 0.00 0.00 0.00 0.00
July 1172796.06 1963.69 26-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 2164179.61 2296.14 24-AUG-18:05 0.00 0.00 0.00 0.00 0.00
September 78056264.76 5227.98 29-SEP-08:62 0.00 0.00 0.00 0.00 0.00
October 0.138988E+10 11573.11 24-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.337321E+10 11830.08 24-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.775077E+10 12001.21 07-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.324934E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1172796.06 1963.69   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.779252E+10 12001.21   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.877780E+10 11899.81 08-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.769541E+10 11900.13 03-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.440900E+10 11897.21 06-MAR-19:01 0.00 0.00 0.00 0.00 0.00
April 0.175993E+10 11721.65 16-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.257957E+09 4867.83 12-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 19940674.74 2318.15 05-JUN-15:04 0.00 0.00 0.00 0.00 0.00
July 843625.54 2007.55 26-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 2720503.37 3597.74 31-AUG-15:04 0.00 0.00 0.00 0.00 0.00
September 0.111941E+09 5765.59 29-SEP-08:62 0.00 0.00 0.00 0.00 0.00
October 0.176966E+10 11503.89 24-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.395465E+10 11730.84 24-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.852959E+10 11900.33 07-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.372894E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 843625.54 2007.55   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.877780E+10 11900.33   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.269573E+10 3604.77 08-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.237005E+10 3604.85 03-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.125133E+10 3604.58 05-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.601304E+09 3566.96 16-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.128043E+09 2338.34 12-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 13263673.26 746.19 27-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 894664.12 636.97 06-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 3111019.79 784.86 31-AUG-18:04 0.00 0.00 0.00 0.00 0.00
September 56300733.48 2403.31 29-SEP-08:62 0.00 0.00 0.00 0.00 0.00
October 0.596405E+09 3550.37 17-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.123351E+10 3553.64 24-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.260995E+10 3604.94 07-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.115599E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 894664.12 636.97   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.269573E+10 3604.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.298668E+10 3569.84 08-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.261674E+10 3569.94 03-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.152837E+10 3569.64 05-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.697148E+09 3532.43 16-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.146605E+09 2529.66 08-MAY-08:61 0.00 0.00 0.00 0.00 0.00
June 13039221.26 709.15 23-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 830077.35 684.68 06-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 3518349.56 865.45 31-AUG-15:04 0.00 0.00 0.00 0.00 0.00
September 79988124.20 2546.56 29-SEP-08:62 0.00 0.00 0.00 0.00 0.00
October 0.746213E+09 3516.02 17-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.142700E+10 3519.24 24-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.283379E+10 3569.98 07-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.130799E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 830077.35 684.68   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.298668E+10 3569.98   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.914053E+10 17071.90 12-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.828339E+10 17072.51 03-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.361904E+10 16967.24 24-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.179673E+10 16779.47 16-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 0.320225E+09 6741.72 29-MAY-15:04 0.00 0.00 0.00 0.00 0.00
June 46576710.58 5195.25 12-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 5383868.00 3840.30 20-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 6677661.90 3606.12 14-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 76394236.35 5464.84 29-SEP-08:62 0.00 0.00 0.00 0.00 0.00
October 0.132439E+10 16457.53 24-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.350886E+10 16792.26 24-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.926564E+10 17072.81 07-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.373938E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5383868.00 3606.12   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.926564E+10 17072.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.115572E+09 0.115572E+09 16960.16 17-JAN-21:47 16960.16 0.00
February 0.00 0.00 68941029.73 68941029.73 12923.43 14-FEB-21:07 12923.43 0.00
March 0.00 0.00 0.147386E+11 0.144763E+11 204644.29 14-MAR-10:45 139667.03 0.07
April 0.00 0.00 0.835226E+10 0.835226E+10 103120.40 08-APR-13:00 103120.40 0.03
May 0.00 0.00 0.678803E+11 0.667084E+11 186664.54 10-MAY-15:30 161627.18 0.24
June 0.00 0.00 0.279509E+12 0.205812E+12 498552.28 27-JUN-20:30 195877.05 0.66
July 0.00 0.00 0.519091E+12 0.330091E+12 532232.45 21-JUL-20:10 210291.07 0.95
August 0.00 0.00 0.381635E+12 0.277839E+12 474674.86 14-AUG-21:50 214154.13 0.90
September 0.00 0.00 0.184696E+12 0.136716E+12 433138.52 15-SEP-20:20 175471.51 0.57
October 0.00 0.00 0.227375E+11 0.227375E+11 132221.82 11-OCT-15:10 132221.82 0.16
November 0.00 0.00 0.740054E+10 0.740054E+10 78292.29 05-NOV-10:50 78292.29 0.05
December 0.00 0.00 0.211801E+09 0.211801E+09 17303.53 13-DEC-21:19 17303.53 0.00
                 
Annual Sum or Average 0.00 0.00 0.148644E+13 0.107053E+13       0.31
Minimum of Months 0.00 0.00 68941029.73 68941029.73 12923.43   12923.43 0.00
Maximum of Months 0.00 0.00 0.519091E+12 0.330091E+12 532232.45   214154.13 0.95



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 0.281633E+10 0.264764E+10 37606.15 14-MAR-10:50 24258.84 0.06
April 0.00 0.00 0.133318E+10 0.133318E+10 22527.05 08-APR-13:00 22527.05 0.02
May 0.00 0.00 0.125841E+11 0.120189E+11 34286.96 14-MAY-12:20 26765.57 0.21
June 0.00 0.00 0.515262E+11 0.364595E+11 62279.57 27-JUN-21:30 24976.81 0.65
July 0.00 0.00 0.918421E+11 0.574545E+11 70129.18 15-JUL-12:10 26810.70 0.94
August 0.00 0.00 0.679416E+11 0.482534E+11 64880.70 26-AUG-17:40 27503.48 0.88
September 0.00 0.00 0.354053E+11 0.247654E+11 62121.65 15-SEP-20:30 24974.47 0.55
October 0.00 0.00 0.405337E+10 0.405223E+10 25256.43 11-OCT-15:00 25256.43 0.13
November 0.00 0.00 0.150209E+10 0.150209E+10 16476.56 05-NOV-14:00 16476.56 0.05
December 0.00 0.00 1785398.26 1785398.26 966.69 01-DEC-11:00 966.69 0.00
                 
Annual Sum or Average 0.00 0.00 0.269006E+12 0.188489E+12       0.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.918421E+11 0.574545E+11 70129.18   27503.48 0.94



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 12338819.31 12251657.46 12829.87 15-JAN-16:01 12829.87 0.00
February 0.00 0.00 28959213.40 28878906.39 13404.21 28-FEB-16:01 13404.21 0.00
March 0.00 0.00 0.517008E+09 0.366422E+09 15068.68 14-MAR-15:02 13842.42 0.07
April 0.00 0.00 0.121319E+10 0.110345E+10 14027.89 07-APR-15:01 14027.89 0.08
May 0.00 0.00 0.341210E+10 0.260475E+10 14772.84 23-MAY-15:02 14772.84 0.39
June 0.00 0.00 0.748758E+10 0.483977E+10 18162.18 18-JUN-08:62 12057.14 0.77
July 0.00 0.00 0.998108E+10 0.596458E+10 17970.68 28-JUL-18:02 11720.68 0.92
August 0.00 0.00 0.867070E+10 0.526808E+10 17609.76 15-AUG-08:62 12303.54 0.90
September 0.00 0.00 0.474400E+10 0.271724E+10 17065.15 17-SEP-08:62 11718.26 0.78
October 0.00 0.00 0.977280E+09 0.606365E+09 14024.72 25-OCT-15:01 14024.72 0.22
November 0.00 0.00 68868752.78 59398054.84 13679.23 03-NOV-15:02 13679.23 0.01
December 0.00 0.00 10349057.77 10109321.02 3492.99 20-DEC-19:04 3492.99 0.00
                 
Annual Sum or Average 0.00 0.00 0.371234E+11 0.235813E+11       0.35
Minimum of Months 0.00 0.00 10349057.77 10109321.02 3492.99   3492.99 0.00
Maximum of Months 0.00 0.00 0.998108E+10 0.596458E+10 18162.18   14772.84 0.92



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 6266170.23 6157605.45 3602.85 11-JAN-16:04 2840.43 0.00
February 0.00 0.00 6103321.25 6028062.57 3323.60 22-FEB-16:03 3323.60 0.00
March 0.00 0.00 0.242723E+09 0.141863E+09 14454.99 14-MAR-15:02 13025.49 0.05
April 0.00 0.00 0.762010E+09 0.686379E+09 13444.58 07-APR-15:01 13444.58 0.06
May 0.00 0.00 0.284500E+10 0.215222E+10 14680.77 10-MAY-15:02 13618.93 0.36
June 0.00 0.00 0.704732E+10 0.455348E+10 17518.26 18-JUN-08:62 11676.12 0.74
July 0.00 0.00 0.934252E+10 0.553669E+10 17202.67 17-JUL-08:62 11771.09 0.91
August 0.00 0.00 0.764419E+10 0.450410E+10 16995.54 14-AUG-08:62 11973.26 0.88
September 0.00 0.00 0.341577E+10 0.182969E+10 16474.22 17-SEP-08:62 11222.95 0.68
October 0.00 0.00 0.423276E+09 0.240613E+09 13724.73 12-OCT-15:01 12678.82 0.13
November 0.00 0.00 22846919.63 20733616.11 6326.70 15-NOV-16:01 6326.70 0.00
December 0.00 0.00 7848661.18 7619767.45 3580.92 14-DEC-19:04 3580.92 0.00
                 
Annual Sum or Average 0.00 0.00 0.317659E+11 0.196856E+11       0.32
Minimum of Months 0.00 0.00 6103321.25 6028062.57 3323.60   2840.43 0.00
Maximum of Months 0.00 0.00 0.934252E+10 0.553669E+10 17518.26   13618.93 0.91



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 0.596365E+09 0.320758E+09 27170.83 15-MAR-13:30 18823.90 0.02
April 0.00 0.00 0.231918E+10 0.222755E+10 23407.25 22-APR-13:10 23407.25 0.01
May 0.00 0.00 0.601759E+10 0.504718E+10 20831.27 14-MAY-13:50 10888.38 0.08
June 0.00 0.00 0.161774E+11 0.846166E+10 33319.40 27-JUN-13:00 23006.45 0.45
July 0.00 0.00 0.304798E+11 0.146578E+11 38552.65 21-JUL-13:30 32020.72 0.77
August 0.00 0.00 0.296715E+11 0.166405E+11 44988.83 18-AUG-14:40 35899.58 0.75
September 0.00 0.00 0.213188E+11 0.144826E+11 52400.99 21-SEP-13:00 43595.44 0.46
October 0.00 0.00 0.627878E+10 0.513906E+10 49974.35 11-OCT-12:30 47768.14 0.09
November 0.00 0.00 0.602310E+09 0.602310E+09 21674.04 01-NOV-11:50 21674.04 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.113462E+12 0.675794E+11       0.22
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.304798E+11 0.166405E+11 52400.99   47768.14 0.77



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 49562040.89 49463997.10 32095.42 19-JAN-19:04 32095.42 0.00
February 0.00 0.00 44372993.94 44372993.94 32238.27 17-FEB-19:04 32238.27 0.00
March 0.00 0.00 0.316572E+10 0.171259E+10 68213.53 14-MAR-15:02 62337.46 0.13
April 0.00 0.00 0.518356E+10 0.390761E+10 62974.34 09-APR-15:02 62974.34 0.15
May 0.00 0.00 0.199365E+11 0.145293E+11 72871.94 14-MAY-15:02 66557.13 0.41
June 0.00 0.00 0.415136E+11 0.276845E+11 91716.32 18-JUN-08:62 58900.55 0.60
July 0.00 0.00 0.562684E+11 0.356216E+11 90121.68 17-JUL-08:62 56898.93 0.71
August 0.00 0.00 0.463100E+11 0.287139E+11 91400.69 26-AUG-18:02 54408.99 0.71
September 0.00 0.00 0.250598E+11 0.134095E+11 85006.03 17-SEP-08:62 55763.90 0.67
October 0.00 0.00 0.585599E+10 0.284167E+10 70506.15 01-OCT-08:62 55451.24 0.30
November 0.00 0.00 0.104888E+10 0.659028E+09 39955.16 26-NOV-09:02 39955.16 0.05
December 0.00 0.00 77605113.89 72905999.02 35487.70 13-DEC-19:04 35487.70 0.00
                 
Annual Sum or Average 0.00 0.00 0.204514E+12 0.129247E+12       0.31
Minimum of Months 0.00 0.00 44372993.94 44372993.94 32095.42   32095.42 0.00
Maximum of Months 0.00 0.00 0.562684E+11 0.356216E+11 91716.32   66557.13 0.71



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 8175224.09 8088967.39 3606.79 10-JAN-09:04 3606.79 0.00
February 0.00 0.00 25101141.10 25044595.25 4916.89 28-FEB-09:01 4916.89 0.00
March 0.00 0.00 0.480267E+09 0.317740E+09 13554.52 14-MAR-15:02 12585.06 0.08
April 0.00 0.00 0.129032E+10 0.117413E+10 12701.75 07-APR-15:01 12701.75 0.08
May 0.00 0.00 0.338943E+10 0.253990E+10 13705.86 10-MAY-15:02 12787.30 0.42
June 0.00 0.00 0.708097E+10 0.445697E+10 15404.44 17-JUN-08:62 11159.62 0.80
July 0.00 0.00 0.999328E+10 0.598079E+10 16320.38 28-JUL-18:02 10592.31 0.95
August 0.00 0.00 0.859883E+10 0.520946E+10 16026.95 26-AUG-18:02 10872.19 0.93
September 0.00 0.00 0.493521E+10 0.286590E+10 15449.92 17-SEP-08:62 10580.14 0.80
October 0.00 0.00 0.105794E+10 0.663958E+09 12820.65 12-OCT-15:01 11900.43 0.24
November 0.00 0.00 0.124053E+09 0.103389E+09 11560.80 03-NOV-15:02 11560.80 0.01
December 0.00 0.00 12074805.59 11925898.84 4916.48 17-DEC-09:03 4916.48 0.00
                 
Annual Sum or Average 0.00 0.00 0.369956E+11 0.233573E+11       0.36
Minimum of Months 0.00 0.00 8175224.09 8088967.39 3606.79   3606.79 0.00
Maximum of Months 0.00 0.00 0.999328E+10 0.598079E+10 16320.38   12787.30 0.95



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 4697593.00 4586584.91 3496.47 21-JAN-09:04 3496.47 0.00
February 0.00 0.00 5409281.64 5347381.04 3297.07 15-FEB-09:04 3297.07 0.00
March 0.00 0.00 0.233756E+09 0.122720E+09 13067.95 14-MAR-15:02 11860.63 0.06
April 0.00 0.00 0.781225E+09 0.695776E+09 11990.40 21-APR-08:61 11990.40 0.07
May 0.00 0.00 0.275011E+10 0.203738E+10 13659.25 14-MAY-15:02 12150.07 0.40
June 0.00 0.00 0.660410E+10 0.414618E+10 14758.75 17-JUN-08:62 10878.08 0.79
July 0.00 0.00 0.932329E+10 0.549792E+10 15571.39 05-JUL-18:02 10286.87 0.95
August 0.00 0.00 0.754755E+10 0.439242E+10 15611.53 26-AUG-18:02 10453.59 0.92
September 0.00 0.00 0.354310E+10 0.189049E+10 14929.23 17-SEP-08:62 10142.47 0.72
October 0.00 0.00 0.427982E+09 0.232448E+09 11979.34 12-OCT-15:01 10744.86 0.15
November 0.00 0.00 34060870.73 25646251.84 8031.84 06-NOV-09:01 8031.84 0.01
December 0.00 0.00 5207989.35 5087570.53 3526.36 04-DEC-09:04 3526.36 0.00
                 
Annual Sum or Average 0.00 0.00 0.312605E+11 0.190560E+11       0.34
Minimum of Months 0.00 0.00 4697593.00 4586584.91 3297.07   3297.07 0.00
Maximum of Months 0.00 0.00 0.932329E+10 0.549792E+10 15611.53   12150.07 0.95



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 2892273.62 2865029.07 3310.26 15-JAN-16:01 3310.26 0.00
February 0.00 0.00 6507927.61 6487150.63 3408.62 28-FEB-16:01 3408.62 0.00
March 0.00 0.00 0.118792E+09 84618099.68 3885.40 14-MAR-15:02 3632.49 0.06
April 0.00 0.00 0.303185E+09 0.279627E+09 3656.97 07-APR-15:01 3656.97 0.06
May 0.00 0.00 0.814642E+09 0.645296E+09 3851.09 23-MAY-15:02 3851.09 0.32
June 0.00 0.00 0.183819E+10 0.119356E+10 4919.77 18-JUN-08:62 3030.06 0.76
July 0.00 0.00 0.249014E+10 0.148522E+10 4863.24 16-JUL-08:62 3067.43 0.92
August 0.00 0.00 0.210660E+10 0.128978E+10 4782.11 15-AUG-08:62 3090.31 0.89
September 0.00 0.00 0.107423E+10 0.638548E+09 4584.55 17-SEP-08:62 2892.79 0.66
October 0.00 0.00 0.211217E+09 0.140601E+09 3632.13 25-OCT-15:01 3632.13 0.16
November 0.00 0.00 14562687.65 13470541.12 3549.64 15-NOV-16:01 3549.64 0.00
December 0.00 0.00 2438969.37 2374799.67 1031.47 01-DEC-16:04 883.36 0.00
                 
Annual Sum or Average 0.00 0.00 0.898340E+10 0.578245E+10       0.32
Minimum of Months 0.00 0.00 2438969.37 2374799.67 1031.47   883.36 0.00
Maximum of Months 0.00 0.00 0.249014E+10 0.148522E+10 4919.77   3851.09 0.92



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 1566641.96 1545843.59 890.73 15-JAN-16:03 890.73 0.00
February 0.00 0.00 1948716.20 1928779.44 1224.35 18-FEB-16:03 1224.35 0.00
March 0.00 0.00 51653339.60 29939873.28 3791.53 14-MAR-15:02 3433.09 0.05
April 0.00 0.00 0.184494E+09 0.168885E+09 3518.21 07-APR-15:01 3518.21 0.05
May 0.00 0.00 0.665340E+09 0.526039E+09 3733.03 10-MAY-15:02 3586.91 0.29
June 0.00 0.00 0.171916E+10 0.111163E+10 4730.62 18-JUN-08:62 2927.33 0.74
July 0.00 0.00 0.232124E+10 0.136674E+10 4687.19 16-JUL-08:62 2956.55 0.91
August 0.00 0.00 0.183387E+10 0.108002E+10 4582.68 14-AUG-08:62 2952.67 0.87
September 0.00 0.00 0.734469E+09 0.417330E+09 4414.70 17-SEP-08:62 2760.43 0.54
October 0.00 0.00 79899933.02 49742647.76 3572.86 12-OCT-15:01 3292.74 0.08
November 0.00 0.00 5682575.50 5094365.92 1505.73 14-NOV-19:03 1326.48 0.00
December 0.00 0.00 2141116.00 2084402.85 1111.88 01-DEC-16:04 1037.58 0.00
                 
Annual Sum or Average 0.00 0.00 0.760146E+10 0.476098E+10       0.30
Minimum of Months 0.00 0.00 1566641.96 1545843.59 890.73   890.73 0.00
Maximum of Months 0.00 0.00 0.232124E+10 0.136674E+10 4730.62   3586.91 0.91



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.191586E+09 0.191386E+09 16539.81 15-JAN-16:01 16539.81 0.00
February 0.00 0.00 0.193530E+09 0.193428E+09 16539.56 18-FEB-16:01 16539.56 0.00
March 0.00 0.00 0.168955E+10 0.139067E+10 17155.06 15-MAR-18:01 17155.06 0.09
April 0.00 0.00 0.219097E+10 0.198372E+10 16964.89 07-APR-15:01 16964.89 0.11
May 0.00 0.00 0.411481E+10 0.304045E+10 17865.18 23-MAY-15:02 17865.18 0.39
June 0.00 0.00 0.809114E+10 0.475706E+10 22606.73 18-JUN-08:62 14227.79 0.75
July 0.00 0.00 0.122312E+11 0.706971E+10 23063.99 28-JUL-18:02 13409.55 0.91
August 0.00 0.00 0.114392E+11 0.704966E+10 22917.30 26-AUG-18:02 13638.50 0.90
September 0.00 0.00 0.814433E+10 0.520446E+10 21310.58 17-SEP-08:62 13730.06 0.81
October 0.00 0.00 0.337814E+10 0.253936E+10 17705.40 01-OCT-08:62 13232.97 0.32
November 0.00 0.00 0.100271E+10 0.874004E+09 16546.11 15-NOV-16:01 16546.11 0.07
December 0.00 0.00 0.219539E+09 0.219208E+09 16537.85 16-DEC-16:01 16537.85 0.00
                 
Annual Sum or Average 0.00 0.00 0.528866E+11 0.345131E+11       0.36
Minimum of Months 0.00 0.00 0.191586E+09 0.191386E+09 16537.85   13232.97 0.00
Maximum of Months 0.00 0.00 0.122312E+11 0.706971E+10 23063.99   17865.18 0.91



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 85285.12 264865.87 31-JAN-09:03
February 0.00 0.00 01-FEB-00:03 88812.93 314014.86 06-FEB-09:03
March 0.00 0.00 01-MAR-00:03 36532.64 234932.53 04-MAR-09:01
April 0.00 0.00 01-APR-00:10 15308.56 201386.61 14-APR-15:01
May 0.00 0.00 01-MAY-00:05 7573.34 139608.24 07-MAY-23:30
June 0.00 0.00 01-JUN-00:05 2063.15 132475.05 13-JUN-23:50
July 0.00 0.00 01-JUL-00:10 154.55 34250.17 04-JUL-18:07
August 0.00 0.00 01-AUG-00:05 422.42 65270.08 31-AUG-15:04
September 0.00 0.00 01-SEP-00:05 3531.10 133782.87 30-SEP-03:35
October 0.00 0.00 01-OCT-00:10 15274.67 189613.35 26-OCT-15:01
November 0.00 0.00 01-NOV-00:10 24522.60 214358.42 13-NOV-16:01
December 0.00 0.00 01-DEC-00:03 78112.31 292394.51 11-DEC-09:03
             
Annual Sum or Average 0.00     29516.52    
Minimum of Months 0.00 0.00   154.55 34250.17  
Maximum of Months 0.00 0.00   88812.93 314014.86  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 657.15 67327.63 18-JAN-19:04 0.00 0.00 01-JAN-00:05
February 622.12 51700.47 15-FEB-19:04 0.00 0.00 01-FEB-00:03
March 11014.62 352338.35 15-MAR-18:03 0.00 0.00 01-MAR-00:03
April 11901.25 191790.02 08-APR-15:03 0.00 0.00 01-APR-00:10
May 50406.71 371995.24 10-MAY-15:03 0.00 0.00 01-MAY-00:05
June 169715.71 673347.09 27-JUN-20:30 0.00 0.00 01-JUN-00:05
July 285736.35 701928.47 21-JUL-20:30 0.00 0.00 01-JUL-00:10
August 218511.13 664619.67 26-AUG-18:03 0.00 0.00 01-AUG-00:05
September 117260.01 585901.72 15-SEP-18:03 0.00 0.00 01-SEP-00:05
October 19803.91 301119.10 11-OCT-15:02 0.00 0.00 01-OCT-00:10
November 6510.01 116292.90 05-NOV-15:02 0.00 0.00 01-NOV-00:10
December 985.77 70285.10 15-DEC-19:04 0.00 0.00 01-DEC-00:03
             
Annual Sum or Average 75012.64     0.00    
Minimum of Months 622.12 51700.47   0.00 0.00  
Maximum of Months 285736.35 701928.47   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 29745.76 61110.99 31-JAN-07:20
February 0.00 0.00 01-FEB-00:03 30159.95 61326.90 14-FEB-07:20
March 0.00 0.00 01-MAR-00:03 29781.15 71185.66 17-MAR-06:36
April 0.00 0.00 01-APR-00:10 28632.61 66970.66 20-APR-20:31
May 0.00 0.00 01-MAY-00:05 27078.55 63165.12 04-MAY-06:54
June 0.00 0.00 01-JUN-00:05 25535.03 58010.28 06-JUN-06:03
July 0.00 0.00 01-JUL-00:10 24357.34 53382.41 06-JUL-06:05
August 0.00 0.00 01-AUG-00:05 23934.70 51687.80 03-AUG-06:05
September 0.00 0.00 01-SEP-00:05 24315.02 55210.30 06-SEP-06:51
October 0.00 0.00 01-OCT-00:10 25422.57 62071.72 14-OCT-07:51
November 0.00 0.00 01-NOV-00:10 26998.49 63055.12 13-NOV-21:01
December 0.00 0.00 01-DEC-00:03 28583.38 61664.98 14-DEC-07:35
             
Annual Sum or Average 0.00     27027.18    
Minimum of Months 0.00 0.00   23934.70 51687.80  
Maximum of Months 0.00 0.00   30159.95 71185.66  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.587890E+10 0.90 2194.93 01-JAN-00:05 0.90
February 0.530997E+10 0.90 2194.93 01-FEB-00:03 0.90
March 0.587890E+10 0.90 2194.93 01-MAR-00:03 0.90
April 0.568926E+10 0.90 2194.93 01-APR-00:10 0.90
May 0.587890E+10 0.90 2194.93 01-MAY-00:05 0.90
June 0.568926E+10 0.89 2194.93 01-JUN-00:05 0.89
July 0.587890E+10 0.89 2194.93 01-JUL-00:10 0.89
August 0.587890E+10 0.89 2194.93 01-AUG-00:05 0.89
September 0.568926E+10 0.89 2194.93 01-SEP-00:05 0.89
October 0.587890E+10 0.90 2194.93 01-OCT-00:10 0.89
November 0.568926E+10 0.90 2194.93 01-NOV-00:10 0.90
December 0.587890E+10 0.90 2194.93 01-DEC-00:03 0.90
           
Annual Sum or Average 0.692193E+11 0.90      
Minimum of Months 0.530997E+10 0.89 2194.93   0.89
Maximum of Months 0.587890E+10 0.90 2194.93   0.90



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.319605E+11 0.80 27028.96 17-JAN-21:33 1.28
February 0.288578E+11 0.80 25335.79 14-FEB-23:25 1.23
March 0.339534E+11 0.82 35296.33 22-MAR-23:35 1.51
April 0.343311E+11 0.84 35296.33 22-APR-23:17 1.52
May 0.371375E+11 0.86 35300.33 23-MAY-04:20 1.51
June 0.375314E+11 0.88 35853.34 06-JUN-03:40 1.52
July 0.399414E+11 0.89 30069.42 21-JUL-21:10 1.35
August 0.398833E+11 0.89 31328.67 18-AUG-21:10 1.39
September 0.373623E+11 0.87 38250.38 04-SEP-06:00 1.58
October 0.373251E+11 0.86 41517.98 07-OCT-04:15 1.67
November 0.343872E+11 0.84 41517.98 03-NOV-22:05 1.67
December 0.325359E+11 0.80 27028.96 01-DEC-04:27 1.27
           
Annual Sum or Average 0.425207E+12 0.84      
Minimum of Months 0.288578E+11 0.80 25335.79   1.23
Maximum of Months 0.399414E+11 0.89 41517.98   1.67



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.27 76.61 01-JAN-00:05 0.27
February 0.185347E+09 0.27 76.61 01-FEB-00:03 0.27
March 0.205205E+09 0.27 76.61 01-MAR-00:03 0.27
April 0.198586E+09 0.27 76.61 01-APR-00:10 0.27
May 0.205205E+09 0.27 76.61 01-MAY-00:05 0.27
June 0.198586E+09 0.27 76.61 01-JUN-00:05 0.27
July 0.205205E+09 0.27 76.61 01-JUL-00:10 0.27
August 0.205205E+09 0.27 76.61 01-AUG-00:05 0.27
September 0.198586E+09 0.27 76.61 01-SEP-00:05 0.27
October 0.205205E+09 0.27 76.61 01-OCT-00:10 0.27
November 0.198586E+09 0.27 76.61 01-NOV-00:10 0.27
December 0.205205E+09 0.27 76.61 01-DEC-00:03 0.27
           
Annual Sum or Average 0.241613E+10 0.27      
Minimum of Months 0.185347E+09 0.27 76.61   0.27
Maximum of Months 0.205205E+09 0.27 76.61   0.27



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 -0.0 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 -0.0 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00
June 0.00 -0.0 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:10 0.00
December 0.00 -0.0 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.19 612.92 01-JAN-07:05 0.27
February 0.105030E+10 0.19 612.92 01-FEB-07:05 0.27
March 0.116283E+10 0.19 612.92 01-MAR-07:05 0.27
April 0.112532E+10 0.19 612.92 01-APR-06:05 0.27
May 0.116283E+10 0.19 612.92 01-MAY-06:05 0.27
June 0.112532E+10 0.19 612.92 01-JUN-06:05 0.27
July 0.116283E+10 0.19 612.92 01-JUL-06:05 0.27
August 0.116283E+10 0.19 612.92 01-AUG-06:03 0.27
September 0.112532E+10 0.19 612.92 01-SEP-06:05 0.27
October 0.116283E+10 0.19 612.92 01-OCT-06:10 0.27
November 0.112532E+10 0.19 612.92 01-NOV-06:05 0.27
December 0.116283E+10 0.19 612.92 01-DEC-07:05 0.27
           
Annual Sum or Average 0.136914E+11 0.19      
Minimum of Months 0.105030E+10 0.19 612.92   0.27
Maximum of Months 0.116283E+10 0.19 612.92   0.27



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.354201E+09 0.53 812.11 01-JAN-09:01 0.59
February 0.311506E+09 0.52 812.11 01-FEB-09:01 0.59
March 0.211986E+09 0.43 812.11 01-MAR-09:01 0.59
April 0.177642E+09 0.44 812.11 01-APR-08:61 0.59
May 0.236404E+09 0.47 812.11 01-MAY-15:02 0.59
June 0.406618E+09 0.52 812.11 01-JUN-15:02 0.59
July 0.488517E+09 0.54 812.11 01-JUL-08:62 0.59
August 0.448049E+09 0.53 812.11 01-AUG-08:62 0.59
September 0.281486E+09 0.50 812.11 01-SEP-15:02 0.59
October 0.158807E+09 0.44 812.11 02-OCT-15:02 0.59
November 0.192752E+09 0.44 812.11 01-NOV-08:61 0.59
December 0.348815E+09 0.53 812.11 01-DEC-09:01 0.59
           
Annual Sum or Average 0.361678E+10 0.49      
Minimum of Months 0.158807E+09 0.43 812.11   0.59
Maximum of Months 0.488517E+09 0.54 812.11   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.382611E+09 0.56 784.37 01-JAN-09:01 0.59
February 0.334647E+09 0.55 784.37 01-FEB-09:01 0.59
March 0.227069E+09 0.46 784.37 01-MAR-09:01 0.59
April 0.160776E+09 0.43 784.37 01-APR-08:61 0.59
May 0.204718E+09 0.45 784.37 01-MAY-15:02 0.59
June 0.383474E+09 0.51 784.37 01-JUN-15:02 0.59
July 0.459360E+09 0.53 784.37 01-JUL-08:62 0.59
August 0.394565E+09 0.52 784.37 01-AUG-08:62 0.59
September 0.209921E+09 0.46 784.37 01-SEP-15:02 0.59
October 0.144557E+09 0.42 784.37 02-OCT-15:02 0.59
November 0.211562E+09 0.46 784.37 01-NOV-08:61 0.59
December 0.367984E+09 0.55 784.37 01-DEC-09:01 0.59
           
Annual Sum or Average 0.348124E+10 0.49      
Minimum of Months 0.144557E+09 0.42 784.37   0.59
Maximum of Months 0.459360E+09 0.56 784.37   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.111805E+10 0.44 1042.91 24-JAN-06:00 0.59
February 0.100165E+10 0.44 1168.37 07-FEB-05:00 0.59
March 0.110584E+09 0.07 1126.32 15-MAR-13:30 0.59
April 0.159754E+09 0.08 1136.21 22-APR-13:10 0.59
May 0.361318E+09 0.16 997.98 05-MAY-13:30 0.59
June 0.800060E+09 0.33 1240.10 27-JUN-13:00 0.59
July 0.133451E+10 0.46 1441.97 21-JUL-13:30 0.59
August 0.135619E+10 0.45 2312.05 17-AUG-13:30 0.59
September 0.110254E+10 0.34 2740.52 20-SEP-13:30 0.59
October 0.359096E+09 0.10 2955.39 11-OCT-12:30 0.59
November 0.193869E+09 0.12 1069.96 01-NOV-11:50 0.59
December 0.118805E+10 0.48 1052.21 10-DEC-06:00 0.59
           
Annual Sum or Average 0.908568E+10 0.29      
Minimum of Months 0.110584E+09 0.07 997.98   0.59
Maximum of Months 0.135619E+10 0.48 2955.39   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.152302E+10 0.45 3919.86 01-JAN-09:01 0.59
February 0.136053E+10 0.43 3919.86 01-FEB-09:01 0.59
March 0.104254E+10 0.42 3919.86 01-MAR-09:01 0.59
April 0.641996E+09 0.42 3919.86 03-APR-08:61 0.59
May 0.118809E+10 0.42 3919.86 01-MAY-15:02 0.59
June 0.208092E+10 0.42 3919.86 01-JUN-08:62 0.59
July 0.264764E+10 0.42 3919.86 01-JUL-08:62 0.59
August 0.222918E+10 0.42 3919.86 01-AUG-08:62 0.59
September 0.128382E+10 0.42 3919.86 01-SEP-15:02 0.59
October 0.644555E+09 0.42 3919.86 01-OCT-08:62 0.58
November 0.716724E+09 0.42 3919.86 02-NOV-08:61 0.59
December 0.144098E+10 0.45 3919.86 01-DEC-16:01 0.59
           
Annual Sum or Average 0.168000E+11 0.42      
Minimum of Months 0.641996E+09 0.42 3919.86   0.58
Maximum of Months 0.264764E+10 0.45 3919.86   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.324275E+09 0.52 733.82 01-JAN-09:01 0.59
February 0.285286E+09 0.51 733.82 01-FEB-09:01 0.59
March 0.198548E+09 0.43 733.82 01-MAR-09:01 0.59
April 0.173362E+09 0.46 733.82 03-APR-08:61 0.59
May 0.233200E+09 0.51 733.82 01-MAY-08:62 0.59
June 0.376199E+09 0.54 733.82 01-JUN-08:62 0.59
July 0.481767E+09 0.56 733.82 01-JUL-08:62 0.59
August 0.429676E+09 0.55 733.82 01-AUG-08:62 0.59
September 0.279508E+09 0.52 733.82 01-SEP-15:02 0.59
October 0.154007E+09 0.45 733.82 02-OCT-15:02 0.59
November 0.182392E+09 0.44 733.82 02-NOV-08:61 0.59
December 0.325784E+09 0.53 733.82 01-DEC-09:01 0.59
           
Annual Sum or Average 0.344400E+10 0.50      
Minimum of Months 0.154007E+09 0.43 733.82   0.59
Maximum of Months 0.481767E+09 0.56 733.82   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.351616E+09 0.56 709.29 01-JAN-09:01 0.59
February 0.307281E+09 0.55 709.29 01-FEB-09:01 0.59
March 0.213186E+09 0.45 709.29 01-MAR-16:01 0.59
April 0.152715E+09 0.43 709.29 02-APR-18:01 0.59
May 0.198604E+09 0.48 709.29 01-MAY-08:62 0.59
June 0.353931E+09 0.54 709.29 01-JUN-08:62 0.59
July 0.453774E+09 0.56 709.29 01-JUL-08:62 0.59
August 0.379097E+09 0.54 709.29 01-AUG-08:62 0.59
September 0.208562E+09 0.49 709.29 01-SEP-15:02 0.59
October 0.132138E+09 0.42 709.29 03-OCT-15:02 0.59
November 0.196701E+09 0.46 709.29 01-NOV-08:61 0.59
December 0.344356E+09 0.55 709.29 01-DEC-09:01 0.59
           
Annual Sum or Average 0.329196E+10 0.50      
Minimum of Months 0.132138E+09 0.42 709.29   0.59
Maximum of Months 0.453774E+09 0.56 709.29   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.105768E+09 0.56 211.87 01-JAN-09:01 0.59
February 92860631.56 0.54 211.87 01-FEB-09:01 0.59
March 63616617.52 0.45 211.87 01-MAR-09:01 0.59
April 52734670.02 0.45 211.87 01-APR-08:61 0.59
May 61512430.32 0.48 211.87 01-MAY-15:02 0.59
June 0.102169E+09 0.52 211.87 01-JUN-15:02 0.59
July 0.123548E+09 0.54 211.87 01-JUL-08:62 0.58
August 0.110585E+09 0.53 211.87 01-AUG-08:62 0.59
September 67296345.68 0.50 211.87 01-SEP-15:02 0.59
October 46936638.34 0.44 211.87 02-OCT-15:02 0.59
November 60424298.34 0.47 211.87 01-NOV-08:61 0.59
December 0.103631E+09 0.55 211.87 01-DEC-09:01 0.59
           
Annual Sum or Average 0.991083E+09 0.50      
Minimum of Months 46936638.34 0.44 211.87   0.58
Maximum of Months 0.123548E+09 0.56 211.87   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.112187E+09 0.57 204.04 01-JAN-09:01 0.59
February 98394466.23 0.57 204.04 01-FEB-09:01 0.59
March 68812808.46 0.49 204.04 01-MAR-09:01 0.59
April 48475794.55 0.44 204.04 01-APR-08:61 0.59
May 53472845.64 0.45 204.04 01-MAY-15:02 0.59
June 95991760.24 0.51 204.04 01-JUN-15:02 0.59
July 0.115734E+09 0.54 204.04 01-JUL-08:62 0.58
August 97093700.38 0.52 204.04 01-AUG-08:62 0.59
September 49557515.95 0.46 204.04 01-SEP-15:02 0.59
October 44543131.01 0.43 204.04 02-OCT-15:02 0.59
November 65757192.70 0.49 204.04 01-NOV-08:61 0.59
December 0.108030E+09 0.57 204.04 01-DEC-09:01 0.59
           
Annual Sum or Average 0.958050E+09 0.50      
Minimum of Months 44543131.01 0.43 204.04   0.58
Maximum of Months 0.115734E+09 0.57 204.04   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.382934E+09 0.49 975.83 01-JAN-09:01 0.59
February 0.342437E+09 0.47 975.83 01-FEB-09:01 0.59
March 0.275246E+09 0.46 975.83 01-MAR-16:01 0.59
April 0.242095E+09 0.47 975.83 01-APR-15:02 0.59
May 0.275705E+09 0.49 975.83 01-MAY-15:02 0.59
June 0.416913E+09 0.52 975.83 01-JUN-15:02 0.59
July 0.571104E+09 0.53 975.83 01-JUL-08:62 0.59
August 0.559406E+09 0.53 975.83 01-AUG-08:62 0.59
September 0.447862E+09 0.51 975.83 01-SEP-15:02 0.59
October 0.285389E+09 0.47 975.83 01-OCT-08:62 0.58
November 0.242068E+09 0.45 975.83 01-NOV-15:02 0.59
December 0.391704E+09 0.50 975.83 01-DEC-09:01 0.59
           
Annual Sum or Average 0.443286E+10 0.49      
Minimum of Months 0.242068E+09 0.45 975.83   0.58
Maximum of Months 0.571104E+09 0.53 975.83   0.59



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.139039E+10 0.125135E+10 936.76 31-JAN-09:01 843.09 843.09 42.31 1.54
February 0.126022E+10 0.113420E+10 1012.76 06-FEB-09:02 911.49 911.49 42.38 1.83
March 0.690623E+09 0.621560E+09 795.51 05-MAR-07:03 715.96 715.96 50.12 1.15
April 0.340778E+09 0.306700E+09 719.12 03-APR-22:18 647.21 647.21 43.96 0.99
May 0.125462E+09 0.112916E+09 688.05 07-MAY-06:40 619.24 619.24 61.77 0.92
June 30442084.92 27397876.43 654.58 14-JUN-02:13 589.12 589.12 47.87 0.87
July 2502752.78 2252477.50 231.14 26-JUL-08:05 208.02 208.02 55.01 0.25
August 6724370.83 6051933.75 311.69 31-AUG-15:04 280.52 280.52 35.10 0.35
September 57827111.62 52044400.46 725.13 30-SEP-03:35 652.62 652.62 47.90 1.00
October 0.336558E+09 0.302902E+09 782.11 18-OCT-08:35 703.90 703.90 56.43 1.12
November 0.581628E+09 0.523465E+09 823.51 19-NOV-23:30 741.16 741.16 57.13 1.22
December 0.133352E+10 0.120017E+10 979.74 11-DEC-09:02 881.77 881.77 42.11 1.70
                 
Annual Sum or Average 0.615668E+10 0.554101E+10            
Minimum of Months 2502752.78 2252477.50 231.14   208.02 208.02 35.10 0.25
Maximum of Months 0.139039E+10 0.125135E+10 1012.76   911.49 911.49 61.77 1.83



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 205650.41 185085.37 62.52 18-JAN-19:04 56.27 56.27 8.40 3.93
February 222995.34 200695.80 60.31 19-FEB-19:04 54.28 54.28 8.40 3.85
March 28173368.02 25356031.22 653.88 15-MAR-18:03 588.49 588.49 7.20 12.42
April 23281731.69 20953558.52 376.69 08-APR-15:03 339.02 339.02 7.86 9.66
May 0.140887E+09 0.126798E+09 816.54 23-MAY-20:50 734.89 734.89 7.63 13.71
June 0.669261E+09 0.602335E+09 2432.12 27-JUN-20:30 2188.90 2188.90 7.27 21.82
July 0.133345E+10 0.120010E+10 2584.41 21-JUL-20:20 2325.97 2325.97 7.27 22.37
August 0.996329E+09 0.896696E+09 2073.98 26-AUG-18:03 1866.58 1866.58 7.33 20.43
September 0.441867E+09 0.397681E+09 1832.76 15-SEP-20:30 1649.49 1649.49 7.44 19.40
October 54252554.69 48827299.22 746.98 11-OCT-15:02 672.28 672.28 7.41 13.18
November 7518194.88 6766375.39 138.92 27-NOV-09:04 125.03 125.03 8.28 5.96
December 279894.30 251904.87 63.80 15-DEC-19:04 57.42 57.42 8.40 3.97
                 
Annual Sum or Average 0.369573E+10 0.332616E+10            
Minimum of Months 205650.41 185085.37 60.31   54.28 54.28 7.20 3.85
Maximum of Months 0.133345E+10 0.120010E+10 2584.41   2325.97 2325.97 8.40 22.37



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.151855E+10 0.136669E+10 4724.01 01-JAN-06:20 4251.61 4251.61 8.40 33.11
February 0.124804E+10 0.112324E+10 4724.01 01-FEB-03:00 4251.61 4251.61 8.40 33.11
March 0.537113E+10 0.483402E+10 4724.01 01-MAR-09:01 4251.61 4251.61 8.43 33.11
April 0.769416E+10 0.692474E+10 4724.01 01-APR-01:07 4251.61 4251.61 8.40 33.11
May 0.116933E+11 0.105240E+11 4724.01 01-MAY-00:05 4251.61 4251.61 8.43 33.11
June 0.122071E+11 0.109864E+11 4724.01 01-JUN-00:05 4251.61 4251.61 8.66 33.11
July 0.126528E+11 0.113875E+11 4724.01 01-JUL-00:10 4251.61 4251.61 8.70 33.11
August 0.126358E+11 0.113722E+11 4724.01 01-AUG-00:05 4251.61 4251.61 9.15 33.11
September 0.118242E+11 0.106417E+11 4724.01 01-SEP-00:05 4251.61 4251.61 8.50 33.11
October 0.836945E+10 0.753250E+10 4724.01 01-OCT-00:10 4251.61 4251.61 8.45 33.11
November 0.562011E+10 0.505810E+10 4724.01 01-NOV-00:10 4251.61 4251.61 8.41 33.11
December 0.231556E+10 0.208401E+10 4724.01 01-DEC-00:03 4251.61 4251.61 8.40 33.11
                 
Annual Sum or Average 0.931502E+11 0.838352E+11            
Minimum of Months 0.124804E+10 0.112324E+10 4724.01   4251.61 4251.61 8.40 33.11
Maximum of Months 0.126528E+11 0.113875E+11 4724.01   4251.61 4251.61 9.15 33.11



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:05 14.37 14.37 47.51 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:03 14.37 14.37 47.46 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:03 14.37 14.37 47.86 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 51.27 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:05 14.37 14.37 51.38 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:05 14.37 14.37 51.48 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 52.17 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:05 14.37 14.37 52.70 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:05 14.37 14.37 52.63 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 51.42 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:10 14.37 14.37 51.59 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:03 14.37 14.37 48.77 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 47.46 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 52.70 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 56.19 81.25 85285.12 264865.87 31-JAN-09:03
February 0.00 0.00 01-FEB-00:03 53.23 81.64 88812.93 314014.86 06-FEB-09:03
March 0.00 0.00 01-MAR-00:03 51.97 81.91 36532.64 234932.53 04-MAR-09:01
April 0.00 0.00 01-APR-00:10 65.82 80.39 15308.56 201386.61 14-APR-15:01
May 0.00 0.00 01-MAY-00:05 53.81 79.96 7573.34 139608.24 07-MAY-23:30
June 0.00 0.00 01-JUN-00:05 41.36 41.36 2063.15 132475.05 13-JUN-23:50
July 0.00 0.00 01-JUL-00:10 36.07 36.07 154.55 34250.17 04-JUL-18:07
August 0.00 0.00 01-AUG-00:05 58.52 58.52 422.42 65270.08 31-AUG-15:04
September 0.00 0.00 01-SEP-00:05 37.80 79.40 3531.10 133782.87 30-SEP-03:35
October 0.00 0.00 01-OCT-00:10 49.40 79.40 15274.67 189613.35 26-OCT-15:01
November 0.00 0.00 01-NOV-00:10 61.51 79.98 24522.60 214358.42 13-NOV-16:01
December 0.00 0.00 01-DEC-00:03 61.89 80.25 78112.31 292394.51 11-DEC-09:03
                 
Annual Sum or Average 0.00         29516.52    
Minimum of Months 0.00 0.00   36.07 36.07 154.55 34250.17  
Maximum of Months 0.00 0.00   65.82 81.91 88812.93 314014.86  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 657.15 67327.63 18-JAN-19:04 8.86 8.37 0.00 0.00 01-JAN-00:05
February 622.12 51700.47 15-FEB-19:04 8.74 8.37 0.00 0.00 01-FEB-00:03
March 11014.62 352338.35 15-MAR-18:03 9.73 7.19 0.00 0.00 01-MAR-00:03
April 11901.25 191790.02 08-APR-15:03 9.22 7.84 0.00 0.00 01-APR-00:10
May 50406.71 371995.24 10-MAY-15:03 9.51 6.83 0.00 0.00 01-MAY-00:05
June 169715.71 673347.09 27-JUN-20:30 12.10 7.25 0.00 0.00 01-JUN-00:05
July 285736.35 701928.47 21-JUL-20:30 12.31 7.25 0.00 0.00 01-JUL-00:10
August 218511.13 664619.67 26-AUG-18:03 12.09 7.30 0.00 0.00 01-AUG-00:05
September 117260.01 585901.72 15-SEP-18:03 11.61 7.39 0.00 0.00 01-SEP-00:05
October 19803.91 301119.10 11-OCT-15:02 9.56 7.39 0.00 0.00 01-OCT-00:10
November 6510.01 116292.90 05-NOV-15:02 8.94 8.10 0.00 0.00 01-NOV-00:10
December 985.77 70285.10 15-DEC-19:04 8.88 8.37 0.00 0.00 01-DEC-00:03
                 
Annual Sum or Average 75012.64         0.00    
Minimum of Months 622.12 51700.47   8.74 6.83 0.00 0.00  
Maximum of Months 285736.35 701928.47   12.31 8.37 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 47.51 59.68 29745.76 61110.99 31-JAN-07:20
February 0.00 0.00 01-FEB-00:03 47.46 58.17 30159.95 61326.90 14-FEB-07:20
March 0.00 0.00 01-MAR-00:03 47.86 59.10 29781.15 71185.66 17-MAR-06:36
April 0.00 0.00 01-APR-00:10 51.27 59.28 28632.61 66970.66 20-APR-20:31
May 0.00 0.00 01-MAY-00:05 51.38 58.98 27078.55 63165.12 04-MAY-06:54
June 0.00 0.00 01-JUN-00:05 51.48 58.64 25535.03 58010.28 06-JUN-06:03
July 0.00 0.00 01-JUL-00:10 52.17 58.60 24357.34 53382.41 06-JUL-06:05
August 0.00 0.00 01-AUG-00:05 52.70 59.67 23934.70 51687.80 03-AUG-06:05
September 0.00 0.00 01-SEP-00:05 52.63 59.20 24315.02 55210.30 06-SEP-06:51
October 0.00 0.00 01-OCT-00:10 51.42 58.62 25422.57 62071.72 14-OCT-07:51
November 0.00 0.00 01-NOV-00:10 51.59 58.36 26998.49 63055.12 13-NOV-21:01
December 0.00 0.00 01-DEC-00:03 48.77 59.15 28583.38 61664.98 14-DEC-07:35
                 
Annual Sum or Average 0.00         27027.18    
Minimum of Months 0.00 0.00   47.46 58.17 23934.70 51687.80  
Maximum of Months 0.00 0.00   52.70 59.68 30159.95 71185.66  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.113144E+12 0.00 0.115572E+09 0.319605E+11 0.00 0.00
February 0.110267E+12 0.00 68941029.73 0.288578E+11 0.00 0.00
March 0.530101E+11 0.00 0.147386E+11 0.339534E+11 0.00 0.00
April 0.259389E+11 0.00 0.835226E+10 0.343311E+11 0.00 0.00
May 0.188323E+11 0.00 0.678803E+11 0.371375E+11 0.00 0.00
June 0.523820E+10 0.00 0.279509E+12 0.375314E+11 0.00 0.00
July 0.351388E+09 0.00 0.519091E+12 0.399414E+11 0.00 0.00
August 0.110949E+10 0.00 0.381635E+12 0.398833E+11 0.00 0.00
September 0.855633E+10 0.00 0.184696E+12 0.373623E+11 0.00 0.00
October 0.286553E+11 0.00 0.227375E+11 0.373251E+11 0.00 0.00
November 0.295954E+11 0.00 0.740054E+10 0.343872E+11 0.00 0.00
December 0.987760E+11 0.00 0.211801E+09 0.325359E+11 0.00 0.00
             
Annual Sum or Average 0.493474E+12 0.00 0.148644E+13 0.425207E+12 0.00 0.00
Minimum of Months 0.351388E+09 0.00 68941029.73 0.288578E+11 0.00 0.00
Maximum of Months 0.113144E+12 0.00 0.519091E+12 0.399414E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.113159E+11 0.00 0.00 0.587890E+10 0.00 0.00
February 0.116272E+11 0.00 0.00 0.530997E+10 0.00 0.00
March 0.411552E+10 0.00 0.281633E+10 0.587890E+10 0.00 0.00
April 0.335629E+09 0.00 0.133318E+10 0.568926E+10 0.00 0.00
May 11034.83 0.00 0.125841E+11 0.587890E+10 0.00 0.00
June 20994.11 0.00 0.515262E+11 0.568926E+10 0.00 0.00
July 23061.03 0.00 0.918421E+11 0.587890E+10 0.00 0.00
August 23500.52 0.00 0.679416E+11 0.587890E+10 0.00 0.00
September 15215.30 0.00 0.354053E+11 0.568926E+10 0.00 0.00
October 71013783.45 0.00 0.405337E+10 0.587890E+10 0.00 0.00
November 0.444457E+09 0.00 0.150209E+10 0.568926E+10 0.00 0.00
December 0.939327E+10 0.00 1785398.26 0.587890E+10 0.00 0.00
             
Annual Sum or Average 0.373031E+11 0.00 0.269006E+12 0.692193E+11 0.00 0.00
Minimum of Months 11034.83 0.00 0.00 0.530997E+10 0.00 0.00
Maximum of Months 0.116272E+11 0.00 0.918421E+11 0.587890E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.319605E+11 0.115572E+09 0.113144E+12 0.679194E+12 0.00 0.00 0.00 0.00
February 0.288578E+11 68941029.73 0.110267E+12 0.633677E+12 0.00 0.00 0.00 0.00
March 0.339534E+11 0.147386E+11 0.530101E+11 0.476014E+12 44947769.14 0.00 0.00 0.00
April 0.343311E+11 0.835231E+10 0.259389E+11 0.270829E+12 0.00 0.00 0.00 0.00
May 0.371375E+11 0.678803E+11 0.188323E+11 0.642496E+11 0.136191E+09 0.00 0.00 0.00
June 0.375314E+11 0.279509E+12 0.523820E+10 0.196831E+11 0.185848E+11 0.00 0.00 0.00
July 0.399414E+11 0.519091E+12 0.351388E+09 0.241266E+10 0.566991E+11 0.00 0.00 0.00
August 0.398833E+11 0.381635E+12 0.110949E+10 0.568504E+10 0.271911E+11 0.00 0.00 0.00
September 0.373623E+11 0.184696E+12 0.855633E+10 0.275951E+11 0.348890E+10 0.00 0.00 0.00
October 0.373251E+11 0.227375E+11 0.286553E+11 0.184667E+12 0.00 0.00 0.00 0.00
November 0.343872E+11 0.740054E+10 0.295954E+11 0.334855E+12 0.00 0.00 0.00 0.00
December 0.325359E+11 0.211801E+09 0.987760E+11 0.642015E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.425207E+12 0.148644E+13 0.493474E+12 0.334088E+13 0.106145E+12 0.00 0.00 0.00
Minimum of Months 0.288578E+11 68941029.73 0.351388E+09 0.241266E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.399414E+11 0.519091E+12 0.113144E+12 0.679194E+12 0.566991E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.587890E+10 0.00 0.113159E+11 0.119695E+12 0.00 0.00 0.00 0.00
February 0.530997E+10 0.00 0.116272E+11 0.111444E+12 0.00 0.00 0.00 0.00
March 0.587890E+10 0.281633E+10 0.411552E+10 0.868715E+11 0.189152E+09 0.00 0.00 0.00
April 0.568926E+10 0.133318E+10 0.335629E+09 0.545927E+11 0.00 0.00 0.00 0.00
May 0.587890E+10 0.125841E+11 11034.83 0.180773E+11 0.296867E+09 0.00 0.00 0.00
June 0.568926E+10 0.515262E+11 20994.11 0.520934E+10 0.843043E+10 0.00 0.00 0.00
July 0.587890E+10 0.918421E+11 23061.03 0.536800E+09 0.237131E+11 0.00 0.00 0.00
August 0.587890E+10 0.679416E+11 23500.52 0.126941E+10 0.130888E+11 0.00 0.00 0.00
September 0.568926E+10 0.354053E+11 15215.30 0.812023E+10 0.263275E+10 0.00 0.00 0.00
October 0.587890E+10 0.405337E+10 71013783.45 0.420604E+11 52779.65 0.00 0.00 0.00
November 0.568926E+10 0.150209E+10 0.444457E+09 0.651249E+11 0.00 0.00 0.00 0.00
December 0.587890E+10 1785398.26 0.939327E+10 0.113522E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.692193E+11 0.269006E+12 0.373031E+11 0.626523E+12 0.483511E+11 0.00 0.00 0.00
Minimum of Months 0.530997E+10 0.00 11034.83 0.536800E+09 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.918421E+11 0.116272E+11 0.119695E+12 0.237131E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.319605E+11 0.113144E+12 0.115572E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.288578E+11 0.110267E+12 68941029.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.339534E+11 0.530101E+11 0.147386E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.343311E+11 0.259389E+11 0.835226E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.371375E+11 0.188323E+11 0.678803E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.375314E+11 0.523820E+10 0.279509E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.399414E+11 0.351388E+09 0.519091E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.398833E+11 0.110949E+10 0.381635E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.373623E+11 0.855633E+10 0.184696E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.373251E+11 0.286553E+11 0.227375E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.343872E+11 0.295954E+11 0.740054E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.325359E+11 0.987760E+11 0.211801E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.425207E+12 0.493474E+12 0.148644E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.288578E+11 0.351388E+09 68941029.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.399414E+11 0.113144E+12 0.519091E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.587890E+10 0.113159E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.530997E+10 0.116272E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.587890E+10 0.411552E+10 0.281633E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.568926E+10 0.335629E+09 0.133318E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.587890E+10 11034.83 0.125841E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.568926E+10 20994.11 0.515262E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.587890E+10 23061.03 0.918421E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.587890E+10 23500.52 0.679416E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.568926E+10 15215.30 0.354053E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.587890E+10 71013783.45 0.405337E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.568926E+10 0.444457E+09 0.150209E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.587890E+10 0.939327E+10 1785398.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.692193E+11 0.373031E+11 0.269006E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.530997E+10 11034.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.116272E+11 0.918421E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.383967E+11 0.00 0.00 9219253.08 0.00 0.00 0.133365E+11 0.00 0.93
February 0.404448E+11 0.00 0.00 3127226.56 0.00 0.00 0.690276E+10 0.00 0.93
March 0.470612E+11 0.00 0.00 92829.50 2588063.22 0.00 0.444998E+09 0.00 0.91
April 0.456670E+11 0.00 0.00 2938.60 0.00 0.00 7703568.04 0.00 0.91
May 0.428834E+11 0.00 0.00 0.00 937632.13 0.00 0.00 0.00 0.94
June 0.238511E+11 28005313.46 0.00 279197.45 0.279688E+10 0.00 0.131075E+10 0.00 0.96
July 0.105759E+11 0.156621E+10 0.00 1651557.64 0.771512E+10 0.00 0.126010E+10 0.00 0.95
August 0.466444E+10 0.187354E+10 0.00 18500643.51 0.232015E+10 0.00 0.152738E+11 0.00 0.98
September 0.297011E+10 0.151312E+10 0.00 52998553.73 0.173511E+09 0.00 0.328682E+11 0.00 1.04
October 0.279370E+10 0.00 0.00 0.103969E+09 0.00 0.00 0.519340E+11 0.00 1.04
November 0.298010E+10 0.00 0.00 0.100445E+09 0.00 0.00 0.480827E+11 0.00 1.01
December 0.148695E+11 0.00 0.00 40498943.78 0.00 0.00 0.380441E+11 0.00 0.97
                   
Annual Sum or Average 0.277158E+12 0.498087E+10 0.00 0.330785E+09 0.130092E+11 0.00 0.209466E+12 0.00 0.96
Minimum of Months 0.279370E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.91
Maximum of Months 0.470612E+11 0.187354E+10 0.00 0.103969E+09 0.771512E+10 0.00 0.519340E+11 0.00 1.04



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.207512E+10 0.00 0.00 27523.28 0.00 0.600420E+10 48346989.84 0.00 2.63
February 0.209856E+10 0.00 0.00 37595.51 0.00 0.529054E+10 70438352.18 0.00 2.64
March 0.559733E+10 235880.31 0.00 308729.84 171982.98 0.161183E+10 0.277596E+09 0.00 2.60
April 0.654431E+10 0.00 0.00 319734.47 0.00 0.312348E+09 0.342034E+09 0.00 2.60
May 0.641909E+10 147755.42 0.00 343372.34 0.00 746188.53 0.335731E+09 0.00 2.68
June 0.368182E+10 0.216720E+09 0.00 435538.49 0.233475E+09 0.00 0.282144E+09 0.00 2.75
July 0.163775E+10 0.881979E+09 0.00 592749.30 0.614580E+09 0.00 0.226784E+09 0.00 2.76
August 0.260136E+10 0.410311E+09 0.00 1715728.90 0.262081E+09 0.00 0.491328E+09 0.00 2.81
September 0.446016E+10 94819528.72 0.00 1948932.68 0.156358E+09 5878285.76 0.801477E+09 0.00 2.83
October 0.678063E+10 0.00 0.00 1280779.60 0.00 0.192237E+09 0.592665E+09 0.00 2.65
November 0.572032E+10 0.00 0.00 286934.83 0.00 0.118648E+10 0.195191E+09 0.00 2.59
December 0.193505E+10 0.00 0.00 43761.31 0.00 0.595215E+10 60449110.01 0.00 2.63
                   
Annual Sum or Average 0.495515E+11 0.160421E+10 0.00 7341380.54 0.126667E+10 0.205564E+11 0.372418E+10 0.00 2.68
Minimum of Months 0.163775E+10 0.00 0.00 27523.28 0.00 0.00 48346989.84 0.00 2.59
Maximum of Months 0.678063E+10 0.881979E+09 0.00 1948932.68 0.614580E+09 0.600420E+10 0.801477E+09 0.00 2.83



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.487858E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.37
February 0.447755E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.37
March 0.437817E+10 0.00 0.00 82348.26 244734.59 0.00 0.114873E+09 0.00 1.35
April 0.406487E+10 0.00 0.00 122024.97 0.00 0.00 0.254725E+09 0.00 1.35
May 0.317158E+10 0.00 0.00 610825.03 88665.15 0.00 0.888025E+09 0.00 1.40
June 0.113623E+10 0.146241E+09 0.00 1613513.16 0.132700E+09 0.00 0.128108E+10 0.00 1.46
July 0.196714E+09 0.650148E+09 0.00 1609499.85 0.281205E+09 0.00 0.955442E+09 0.00 1.48
August 0.431989E+09 0.268171E+09 0.00 2317819.07 0.139102E+09 0.00 0.148643E+10 0.00 1.49
September 0.187769E+10 63506172.17 0.00 1231752.60 88202057.20 0.00 0.128110E+10 0.00 1.45
October 0.400238E+10 0.00 0.00 279053.07 0.00 0.00 0.484791E+09 0.00 1.35
November 0.421141E+10 0.00 0.00 10815.39 0.00 0.00 46281467.84 0.00 1.34
December 0.477053E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.37
                   
Annual Sum or Average 0.375977E+11 0.112807E+10 0.00 7877651.40 0.641542E+09 0.00 0.679274E+10 0.00 1.40
Minimum of Months 0.196714E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.34
Maximum of Months 0.487858E+10 0.650148E+09 0.00 2317819.07 0.281205E+09 0.00 0.148643E+10 0.00 1.49



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.243563E+10 0.00 0.00 0.00 0.00 0.221557E+10 0.00 0.00 0.62
February 0.203091E+10 0.00 0.00 0.00 0.00 0.223795E+10 0.00 0.00 0.62
March 0.369145E+10 0.00 0.00 0.00 233328.04 0.591503E+09 0.00 0.00 0.60
April 0.411782E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.61
May 0.386617E+10 0.00 0.00 0.00 84532.66 0.00 0.00 0.00 0.63
June 0.216015E+10 46130466.25 0.00 159466.47 0.211749E+09 0.00 0.109441E+09 0.00 0.64
July 0.895163E+09 0.394838E+09 0.00 353142.08 0.475155E+09 0.00 0.174103E+09 0.00 0.65
August 0.143213E+10 0.115790E+09 0.00 532661.42 0.259379E+09 0.00 0.341324E+09 0.00 0.65
September 0.289818E+10 22261517.13 0.00 38962.24 0.118922E+09 0.00 75118044.70 0.00 0.64
October 0.427455E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.61
November 0.405926E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.60
December 0.278108E+10 0.00 0.00 0.00 0.00 0.176711E+10 0.00 0.00 0.62
                   
Annual Sum or Average 0.346425E+11 0.579020E+09 0.00 1084232.23 0.106552E+10 0.681214E+10 0.699986E+09 0.00 0.62
Minimum of Months 0.895163E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.60
Maximum of Months 0.427455E+10 0.394838E+09 0.00 532661.42 0.475155E+09 0.223795E+10 0.341324E+09 0.00 0.65



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.382403E+09 0.00 0.00 0.00 0.00 0.185540E+10 0.00 0.00 0.51
February 0.312658E+09 0.00 0.00 0.00 0.00 0.174119E+10 0.00 0.00 0.51
March 0.141616E+10 0.00 0.00 0.00 112259.55 0.644471E+09 0.00 0.00 0.50
April 0.193398E+10 0.00 0.00 0.00 0.00 47197264.01 0.00 0.00 0.51
May 0.186011E+10 0.00 0.00 0.00 40670.63 0.00 0.00 0.00 0.52
June 0.109143E+10 5469398.90 0.00 0.00 0.117062E+09 0.00 0.00 0.00 0.54
July 0.509681E+09 0.102257E+09 0.00 2120.83 0.302504E+09 0.00 3783584.55 0.00 0.53
August 0.830485E+09 13648981.81 0.00 19567.82 0.164523E+09 0.00 18131784.89 0.00 0.53
September 0.143054E+10 0.00 0.00 0.00 67909554.81 0.00 0.00 0.00 0.54
October 0.205659E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.51
November 0.185169E+10 0.00 0.00 0.00 0.00 0.101314E+09 0.00 0.00 0.50
December 0.696702E+09 0.00 0.00 0.00 0.00 0.149154E+10 0.00 0.00 0.51
                   
Annual Sum or Average 0.143724E+11 0.121375E+09 0.00 21688.65 0.652152E+09 0.588111E+10 21915369.44 0.00 0.52
Minimum of Months 0.312658E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.50
Maximum of Months 0.205659E+10 0.102257E+09 0.00 19567.82 0.302504E+09 0.185540E+10 18131784.89 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.104916E+10 0.00 0.00 95952197.14 0.00 0.00 0.770515E+11 0.00 21.60
February 0.909401E+09 0.00 0.00 84989975.96 0.00 0.00 0.706323E+11 0.00 21.63
March 0.123094E+10 3415844.42 0.00 0.124190E+09 0.00 0.00 0.719833E+11 0.00 21.57
April 0.113988E+10 0.00 0.00 0.149554E+09 0.00 0.00 0.700290E+11 0.00 21.76
May 0.185859E+10 1237529.84 0.00 0.118042E+09 0.00 0.00 0.651625E+11 0.00 22.66
June 0.616898E+09 0.441673E+10 0.00 83173947.99 3011218.77 0.00 0.378333E+11 0.00 23.11
July 57529689.37 0.144014E+11 0.00 48879102.98 10374965.08 0.00 0.173771E+11 0.00 22.66
August 50310272.67 0.645209E+10 0.00 72426114.03 10192286.47 0.00 0.294515E+11 0.00 22.88
September 0.722836E+09 0.251474E+10 0.00 89968325.84 142192.15 0.00 0.501439E+11 0.00 23.14
October 0.167250E+10 0.00 0.00 0.140757E+09 0.00 0.00 0.720322E+11 0.00 21.81
November 0.116533E+10 0.00 0.00 0.150506E+09 0.00 0.00 0.688137E+11 0.00 21.48
December 0.950713E+09 0.00 0.00 98572656.69 0.00 0.00 0.753171E+11 0.00 21.53
                   
Annual Sum or Average 0.114241E+11 0.277896E+11 0.00 0.125701E+10 23720662.47 0.00 0.705827E+12 0.00 22.15
Minimum of Months 50310272.67 0.00 0.00 48879102.98 0.00 0.00 0.173771E+11 0.00 21.48
Maximum of Months 0.185859E+10 0.144014E+11 0.00 0.150506E+09 10374965.08 0.00 0.770515E+11 0.00 23.14



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.318474E+11 0.00 0.00 411221.41 0.00 0.142031E+09 0.958979E+09 0.00 3.80
February 0.285438E+11 0.00 0.00 590355.87 0.00 0.497999E+09 0.119999E+10 0.00 3.81
March 0.219079E+11 1632194.01 0.00 6012445.15 22907.57 0.00 0.848305E+10 0.00 3.76
April 0.165869E+11 0.00 0.00 8503181.76 0.00 0.00 0.126620E+11 0.00 3.77
May 0.103374E+11 600799.51 0.00 14600203.31 0.00 0.00 0.171668E+11 0.00 3.90
June 0.385417E+10 0.161150E+10 0.00 17779384.57 0.218769E+09 0.00 0.123202E+11 0.00 4.01
July 0.797207E+09 0.553265E+10 0.00 14786271.81 0.626215E+09 0.00 0.684789E+10 0.00 4.05
August 0.185777E+10 0.251126E+10 0.00 23095227.75 0.233855E+09 0.00 0.108580E+11 0.00 4.10
September 0.506625E+10 0.811337E+09 0.00 23754149.31 0.212885E+09 0.00 0.164167E+11 0.00 4.12
October 0.160052E+11 0.00 0.00 15457488.38 0.00 0.00 0.147615E+11 0.00 3.84
November 0.214631E+11 0.00 0.00 5144439.28 0.00 0.00 0.738392E+10 0.00 3.74
December 0.310606E+11 0.00 0.00 698082.07 0.00 0.107035E+09 0.105636E+10 0.00 3.80
                   
Annual Sum or Average 0.189328E+12 0.104690E+11 0.00 0.130832E+09 0.129175E+10 0.747065E+09 0.110115E+12 0.00 3.89
Minimum of Months 0.797207E+09 0.00 0.00 411221.41 0.00 0.00 0.958979E+09 0.00 3.74
Maximum of Months 0.318474E+11 0.553265E+10 0.00 23754149.31 0.626215E+09 0.497999E+09 0.171668E+11 0.00 4.12



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.983602E+11 0.00 0.00 54375.33 0.00 0.00 0.472996E+09 0.00 1.65
February 0.897666E+11 0.00 0.00 310844.17 0.00 0.00 0.941997E+09 0.00 1.65
March 0.745585E+11 0.00 0.00 12042367.60 4957984.72 0.00 0.167608E+11 0.00 1.63
April 0.558171E+11 0.00 0.00 34109861.17 0.00 0.00 0.323472E+11 0.00 1.64
May 0.336202E+11 667018.95 0.00 67061251.71 1129214.51 0.00 0.505707E+11 0.00 1.72
June 0.111386E+11 0.454755E+10 0.00 71448193.54 0.116291E+10 0.00 0.401204E+11 0.00 1.83
July 0.163420E+10 0.165707E+11 0.00 54105580.87 0.280084E+10 0.00 0.232182E+11 0.00 1.86
August 0.434948E+10 0.740238E+10 0.00 78063200.08 0.111255E+10 0.00 0.368547E+11 0.00 1.87
September 0.135840E+11 0.236128E+10 0.00 77491957.78 0.818778E+09 0.00 0.528863E+11 0.00 1.81
October 0.479751E+11 0.00 0.00 45358961.78 0.00 0.00 0.441747E+11 0.00 1.65
November 0.660943E+11 0.00 0.00 15601056.71 0.00 0.00 0.203940E+11 0.00 1.62
December 0.955472E+11 0.00 0.00 245182.17 0.00 0.00 0.109689E+10 0.00 1.65
                   
Annual Sum or Average 0.592446E+12 0.308826E+11 0.00 0.455893E+09 0.590117E+10 0.00 0.319839E+12 0.00 1.72
Minimum of Months 0.163420E+10 0.00 0.00 54375.33 0.00 0.00 0.472996E+09 0.00 1.62
Maximum of Months 0.983602E+11 0.165707E+11 0.00 78063200.08 0.280084E+10 0.00 0.528863E+11 0.00 1.87



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.188245E+09 0.00 0.00 153106.18 0.00 0.149946E+10 4638365.93 0.00 0.47
February 0.195287E+09 0.00 0.00 254718.19 0.00 0.135945E+10 12963567.36 0.00 0.47
March 0.398429E+09 1690899.76 354.39 2048840.70 756216.97 0.983535E+09 0.199244E+09 956.64 0.47
April 0.366049E+09 0.00 0.00 5877045.07 0.00 0.663729E+09 0.533428E+09 0.00 0.47
May 0.267417E+09 4904075.89 0.00 10582480.98 462975.51 0.141236E+09 0.104460E+10 0.00 0.47
June 90095825.33 0.243799E+09 220164.92 9567864.68 16792434.67 4259682.15 0.602168E+09 12020.61 0.47
July 13468539.29 0.713230E+09 513725.61 3353880.92 41712262.35 141075.12 0.189339E+09 17505.79 0.48
August 45282140.18 0.370201E+09 376784.51 6825558.79 18377833.87 574304.52 0.392614E+09 19169.01 0.47
September 0.144100E+09 0.162112E+09 282412.64 9275100.25 15215506.11 48895582.25 0.826224E+09 14906.82 0.47
October 0.403135E+09 43868.80 0.00 3673322.23 0.00 0.642787E+09 0.558950E+09 0.00 0.47
November 0.355654E+09 0.00 0.00 660482.25 0.00 0.983126E+09 0.114577E+09 0.00 0.47
December 0.170848E+09 0.00 0.00 140859.26 0.00 0.145959E+10 3234815.91 0.00 0.47
                   
Annual Sum or Average 0.263801E+10 0.149598E+10 1393442.08 52413259.51 93317229.48 0.778679E+10 0.448198E+10 64558.88 0.47
Minimum of Months 13468539.29 0.00 0.00 140859.26 0.00 141075.12 3234815.91 0.00 0.47
Maximum of Months 0.403135E+09 0.713230E+09 513725.61 10582480.98 41712262.35 0.149946E+10 0.104460E+10 19169.01 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 90041041.33 0.00 0.00 85701.26 0.00 0.160014E+10 2034397.33 0.00 0.47
February 99408804.16 0.00 0.00 88611.24 0.00 0.146241E+10 5863323.33 0.00 0.47
March 0.327384E+09 781361.27 3761.31 914120.98 1661152.68 0.110757E+10 0.147202E+09 1865.62 0.47
April 0.410398E+09 0.00 0.00 3859087.18 0.00 0.750541E+09 0.404101E+09 0.00 0.47
May 0.322626E+09 4303625.47 0.00 9053976.12 1062797.09 0.168334E+09 0.963652E+09 0.00 0.47
June 0.114315E+09 0.241045E+09 153762.78 9123087.18 19583081.22 3382949.75 0.579188E+09 10941.97 0.47
July 15212557.27 0.706888E+09 452597.39 3253818.37 48026124.93 47386.46 0.187765E+09 18784.70 0.48
August 50256279.84 0.365612E+09 391178.27 6155839.80 22903844.48 614518.42 0.388218E+09 22180.27 0.47
September 0.190477E+09 0.150458E+09 345520.64 6787271.28 26785048.94 57120729.85 0.773988E+09 16207.09 0.47
October 0.438245E+09 2941.97 0.00 1820818.23 40921.69 0.786271E+09 0.382019E+09 0.00 0.47
November 0.336002E+09 0.00 0.00 284746.54 0.00 0.107716E+10 40401442.99 0.00 0.47
December 0.111699E+09 0.00 0.00 107338.65 0.00 0.151942E+10 2400287.96 0.00 0.47
                   
Annual Sum or Average 0.250606E+10 0.146909E+10 1346820.39 41534416.81 0.120063E+09 0.853301E+10 0.387683E+10 69979.66 0.47
Minimum of Months 15212557.27 0.00 0.00 85701.26 0.00 47386.46 2034397.33 0.00 0.47
Maximum of Months 0.438245E+09 0.706888E+09 452597.39 9123087.18 48026124.93 0.160014E+10 0.963652E+09 22180.27 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.702697E+10 0.00 0.00 0.00 0.00 0.159218E+11 0.00 0.00 0.53
February 0.670274E+10 0.00 0.00 0.00 0.00 0.145573E+11 0.00 0.00 0.53
March 0.192754E+11 23140771.84 0.00 2503639.38 10057712.55 0.134389E+10 0.845701E+09 0.00 0.53
April 0.182629E+11 0.00 0.00 11647553.86 0.00 0.331328E+09 0.266951E+10 0.00 0.54
May 0.131639E+11 72687579.11 0.00 27443863.92 84824.23 0.00 0.665702E+10 0.00 0.54
June 0.485550E+10 0.340404E+10 0.00 27872068.74 0.132493E+09 0.00 0.469059E+10 0.00 0.54
July 0.108429E+10 0.101082E+11 0.00 12438994.57 0.135358E+09 0.00 0.170055E+10 0.00 0.54
August 0.162973E+10 0.512110E+10 0.00 36951213.08 0.153051E+09 0.00 0.437114E+10 0.00 0.54
September 0.586035E+10 0.235428E+10 0.00 52430665.20 54154299.77 0.00 0.803268E+10 0.00 0.54
October 0.168803E+11 594821.52 0.00 25959976.03 0.00 0.00 0.490415E+10 0.00 0.54
November 0.167045E+11 0.00 0.00 4414001.43 0.00 0.222197E+10 0.784313E+09 0.00 0.53
December 0.543321E+10 0.00 0.00 0.00 0.00 0.167198E+11 0.00 0.00 0.53
                   
Annual Sum or Average 0.116880E+12 0.210840E+11 0.00 0.201662E+09 0.485199E+09 0.510961E+11 0.346557E+11 0.00 0.54
Minimum of Months 0.108429E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.53
Maximum of Months 0.192754E+11 0.101082E+11 0.00 52430665.20 0.153051E+09 0.167198E+11 0.803268E+10 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.552029E+10 0.00 0.00 1253062.42 0.00 0.169932E+11 0.440266E+09 0.00 0.53
February 0.529946E+10 0.00 0.00 863442.36 0.00 0.156605E+11 0.305068E+09 0.00 0.53
March 0.563649E+10 7669083.20 0.00 18813554.10 25538479.25 0.102956E+11 0.552252E+10 0.00 0.53
April 0.599027E+10 0.00 0.00 46647868.30 0.00 0.239230E+10 0.128520E+11 0.00 0.54
May 0.530721E+10 27314625.43 0.00 86312130.39 45477677.39 71575401.21 0.143887E+11 0.00 0.54
June 0.221238E+10 0.255126E+10 1283563.93 68583044.28 0.984920E+09 11154876.70 0.728447E+10 38302.05 0.54
July 0.292800E+09 0.753699E+10 3005844.35 26872209.50 0.270630E+10 313388.01 0.247806E+10 45887.55 0.54
August 0.909336E+09 0.396367E+10 3070513.40 49402563.46 0.130881E+10 4486581.70 0.507625E+10 49504.08 0.54
September 0.318747E+10 0.148712E+10 2157677.54 59698960.13 0.919792E+09 33454505.93 0.106686E+11 23939.33 0.54
October 0.602243E+10 39906.01 0.00 42737239.07 555078.16 0.206128E+10 0.136899E+11 0.00 0.54
November 0.525044E+10 0.00 0.00 16587118.72 0.00 0.760317E+10 0.685036E+10 0.00 0.54
December 0.524000E+10 0.00 0.00 1953515.26 0.00 0.162304E+11 0.686743E+09 0.00 0.54
                   
Annual Sum or Average 0.508686E+11 0.155741E+11 9517599.22 0.419725E+09 0.599139E+10 0.713575E+11 0.802429E+11 157633.00 0.54
Minimum of Months 0.292800E+09 0.00 0.00 863442.36 0.00 313388.01 0.305068E+09 0.00 0.53
Maximum of Months 0.602243E+10 0.753699E+10 3070513.40 86312130.39 0.270630E+10 0.169932E+11 0.143887E+11 49504.08 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.195263E+09 0.00 0.00 114051.41 0.00 0.149220E+10 4918616.49 0.00 0.47
February 0.209352E+09 0.00 0.00 180462.57 0.00 0.133614E+10 22285277.66 0.00 0.47
March 0.409595E+09 2238250.09 283.24 1482865.14 208866.64 0.971836E+09 0.200343E+09 1027.78 0.47
April 0.323182E+09 0.00 0.00 6519457.56 0.00 0.649850E+09 0.589531E+09 0.00 0.47
May 0.188173E+09 5157837.44 0.00 11454402.42 209213.96 0.154261E+09 0.110995E+10 0.00 0.47
June 48219539.19 0.247360E+09 56736.59 10336613.60 13402854.37 10386586.35 0.637149E+09 3742.41 0.47
July 3302014.54 0.722743E+09 223535.82 4426587.57 32501681.06 0.00 0.198574E+09 5519.83 0.48
August 30706008.84 0.373330E+09 161578.29 8028558.01 15475375.02 337735.42 0.406224E+09 7863.98 0.47
September 0.112104E+09 0.165043E+09 274345.15 10125557.62 12298989.19 48439473.75 0.857825E+09 9205.18 0.47
October 0.384949E+09 43868.80 0.00 4368434.24 0.00 0.627897E+09 0.591330E+09 0.00 0.47
November 0.358215E+09 0.00 0.00 893582.60 0.00 0.962077E+09 0.132832E+09 0.00 0.47
December 0.170379E+09 0.00 0.00 124657.92 0.00 0.145017E+10 13141521.16 0.00 0.47
                   
Annual Sum or Average 0.243344E+10 0.151592E+10 716479.09 58055230.67 74096980.23 0.770359E+10 0.476410E+10 27359.18 0.47
Minimum of Months 3302014.54 0.00 0.00 114051.41 0.00 0.00 4918616.49 0.00 0.47
Maximum of Months 0.409595E+09 0.722743E+09 274345.15 11454402.42 32501681.06 0.149220E+10 0.110995E+10 9205.18 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 97718372.59 0.00 0.00 68344.57 0.00 0.159249E+10 2021463.71 0.00 0.47
February 0.124113E+09 0.00 0.00 77605.79 0.00 0.143821E+10 5366656.02 0.00 0.47
March 0.354498E+09 904685.85 2874.68 751145.35 1537828.10 0.108706E+10 0.140766E+09 2752.25 0.47
April 0.402659E+09 0.00 0.00 4230830.14 0.00 0.740357E+09 0.421651E+09 0.00 0.47
May 0.251196E+09 5109181.17 14664.71 9715929.48 242173.54 0.184296E+09 0.101846E+10 403.14 0.47
June 56402696.48 0.246972E+09 56399.42 9867795.40 13760847.06 12086195.97 0.627652E+09 4072.50 0.47
July 3223284.41 0.720370E+09 159067.62 4343184.39 34851933.78 0.00 0.198712E+09 3902.35 0.48
August 34482064.07 0.370600E+09 195276.70 7292099.37 18124556.73 337695.85 0.403132E+09 9283.46 0.47
September 0.138018E+09 0.160504E+09 288790.07 7426839.51 16798395.30 67528988.86 0.815400E+09 13472.85 0.47
October 0.443067E+09 2448.27 0.00 2056452.61 40921.69 0.749362E+09 0.413872E+09 493.70 0.47
November 0.321521E+09 0.00 0.00 382303.22 0.00 0.106805E+10 63891531.83 0.00 0.47
December 0.110271E+09 0.00 0.00 74659.76 0.00 0.152017E+10 3104550.94 0.00 0.47
                   
Annual Sum or Average 0.233717E+10 0.150446E+10 717073.19 46287189.60 85356656.21 0.845996E+10 0.411403E+10 34380.26 0.47
Minimum of Months 3223284.41 0.00 0.00 68344.57 0.00 0.00 2021463.71 0.00 0.47
Maximum of Months 0.443067E+09 0.720370E+09 288790.07 9867795.40 34851933.78 0.159249E+10 0.101846E+10 13472.85 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.195843E+11 0.00 0.00 0.00 0.00 0.110951E+11 0.00 0.00 0.56
February 0.185446E+11 0.00 0.00 0.00 0.00 0.961293E+10 0.00 0.00 0.56
March 0.279667E+11 0.00 0.00 0.00 1539038.27 0.283733E+09 0.00 0.00 0.55
April 0.271613E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.55
May 0.255014E+11 0.00 0.00 0.00 557579.78 0.00 0.00 0.00 0.57
June 0.147534E+11 0.192346E+09 0.00 280842.97 0.148752E+10 0.00 0.209457E+09 0.00 0.58
July 0.619270E+10 0.241910E+10 0.00 1049589.58 0.317322E+10 0.00 0.845713E+09 0.00 0.58
August 0.952991E+10 0.826452E+09 0.00 3219779.20 0.162196E+10 0.00 0.211585E+10 0.00 0.58
September 0.195942E+11 0.00 0.00 922.11 0.931016E+09 0.00 17956567.68 0.00 0.58
October 0.281951E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.55
November 0.265377E+11 0.00 0.00 0.00 0.00 0.237325E+09 0.00 0.00 0.55
December 0.184154E+11 0.00 0.00 0.00 0.00 0.115846E+11 0.00 0.00 0.56
                   
Annual Sum or Average 0.241977E+12 0.343790E+10 0.00 4551133.86 0.721581E+10 0.328137E+11 0.318898E+10 0.00 0.56
Minimum of Months 0.619270E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.55
Maximum of Months 0.281951E+11 0.241910E+10 0.00 3219779.20 0.317322E+10 0.115846E+11 0.211585E+10 0.00 0.58



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 25961151.21 0.00 0.00 35809.62 0.00 0.396015E+09 1113213.43 0.00 0.47
February 30412847.00 0.00 0.00 57048.17 0.00 0.358604E+09 2914491.74 0.00 0.47
March 89900307.48 410749.69 0.00 438821.59 201357.25 0.267930E+09 37545296.17 0.00 0.47
April 88709568.27 0.00 0.00 1363860.66 0.00 0.199746E+09 0.102451E+09 0.00 0.47
May 65604240.94 1226018.97 0.00 2371085.30 115743.88 86898251.29 0.211086E+09 0.00 0.47
June 23428083.04 60721576.97 48823.43 2150282.42 4432335.71 10218608.33 0.140726E+09 3110.44 0.47
July 3371115.65 0.177491E+09 115659.23 736282.62 11257987.70 44965.72 47423335.68 3726.38 0.48
August 11870107.26 92311720.92 88976.89 1518888.27 4840028.13 1706815.09 96228296.53 3017.44 0.47
September 36921417.41 40312515.20 63752.07 1972536.21 4027246.16 35444790.49 0.182785E+09 2779.34 0.47
October 0.101279E+09 10967.20 0.00 762237.85 0.00 0.206205E+09 93890564.96 0.00 0.47
November 72391683.12 0.00 0.00 134963.53 0.00 0.275941E+09 15036602.88 0.00 0.47
December 27719964.21 0.00 0.00 33212.99 0.00 0.379972E+09 728040.75 0.00 0.47
                   
Annual Sum or Average 0.577569E+09 0.372485E+09 317211.63 11575029.22 24874698.83 0.221873E+10 0.931927E+09 12633.60 0.47
Minimum of Months 3371115.65 0.00 0.00 33212.99 0.00 44965.72 728040.75 0.00 0.47
Maximum of Months 0.101279E+09 0.177491E+09 115659.23 2371085.30 11257987.70 0.396015E+09 0.211086E+09 3726.38 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 12548211.15 0.00 0.00 21099.91 0.00 0.410078E+09 428280.78 0.00 0.47
February 15100268.23 0.00 0.00 26386.82 0.00 0.376048E+09 767876.31 0.00 0.47
March 62609671.14 206417.55 0.00 183800.54 405289.96 0.307487E+09 25487535.16 327.72 0.47
April 98930457.71 0.00 0.00 869868.72 0.00 0.221491E+09 70933212.27 0.00 0.47
May 79743033.66 1124753.07 0.00 1997759.59 216852.58 97575672.61 0.186600E+09 0.00 0.47
June 28482351.81 60170192.67 49193.20 2026301.49 4976086.28 9992661.01 0.136001E+09 2734.59 0.47
July 3642690.47 0.176171E+09 125698.38 709746.13 12546586.07 39387.36 47177832.86 3513.46 0.48
August 12788231.54 91185527.34 95103.43 1346362.29 5948136.25 2050483.60 95125986.47 3582.84 0.47
September 47571719.96 37724500.17 87275.04 1356061.84 6586157.82 52133971.02 0.156032E+09 3156.89 0.47
October 0.108387E+09 735.49 0.00 345395.97 10230.42 0.240576E+09 52780023.21 0.00 0.47
November 60662975.29 0.00 0.00 66800.36 0.00 0.299419E+09 3313347.37 0.00 0.47
December 16174537.64 0.00 0.00 28990.15 0.00 0.391604E+09 597916.51 0.00 0.47
                   
Annual Sum or Average 0.546641E+09 0.366583E+09 357270.04 8978573.81 30689339.38 0.240849E+10 0.775245E+09 13315.50 0.47
Minimum of Months 3642690.47 0.00 0.00 21099.91 0.00 39387.36 428280.78 0.00 0.47
Maximum of Months 0.108387E+09 0.176171E+09 125698.38 2026301.49 12546586.07 0.410078E+09 0.186600E+09 3582.84 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.451820E+09 0.00 0.00 934593.15 0.00 0.214933E+10 0.116278E+09 0.00 0.53
February 0.477748E+09 0.00 0.00 989438.28 0.00 0.192816E+10 0.111428E+09 0.00 0.53
March 0.500696E+09 3459058.91 0.00 5998659.43 473415.59 0.132898E+10 0.707228E+09 0.00 0.53
April 0.490393E+09 0.00 0.00 10665470.88 0.00 0.899049E+09 0.112003E+10 0.00 0.54
May 0.369059E+09 8189611.63 0.00 12851875.49 430529.49 0.235452E+09 0.173374E+10 0.00 0.54
June 0.154838E+09 0.382345E+09 221608.84 9812113.54 36330319.54 23175360.05 0.946244E+09 17140.02 0.54
July 21406240.90 0.112610E+10 628914.54 3859053.54 86628359.36 296247.37 0.305786E+09 25770.38 0.54
August 74197610.55 0.591568E+09 332254.67 8960166.32 32825246.11 728043.81 0.631315E+09 16224.99 0.54
September 0.208128E+09 0.263728E+09 190350.86 15078835.57 21362036.91 53241158.28 0.137544E+10 7798.08 0.54
October 0.517406E+09 70458.65 0.00 12646066.44 0.00 0.708039E+09 0.134543E+10 0.00 0.54
November 0.477008E+09 0.00 0.00 5580491.75 0.00 0.119187E+10 0.660874E+09 0.00 0.54
December 0.399271E+09 0.00 0.00 1021383.45 0.00 0.210239E+10 0.121416E+09 0.00 0.54
                   
Annual Sum or Average 0.414197E+10 0.237546E+10 1373128.91 88398147.84 0.178050E+09 0.106207E+11 0.917521E+10 66933.47 0.54
Minimum of Months 21406240.90 0.00 0.00 934593.15 0.00 296247.37 0.111428E+09 0.00 0.53
Maximum of Months 0.517406E+09 0.112610E+10 628914.54 15078835.57 86628359.36 0.214933E+10 0.173374E+10 25770.38 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.141286E+11 0.00 0.00 31345252.31 0.00 0.00 0.318691E+11 0.00 3.95
February 0.134987E+11 0.00 0.00 28252737.64 0.00 0.00 0.286709E+11 0.00 3.95
March 0.728577E+10 1486254.57 0.00 59736024.35 761919.04 0.00 0.378784E+11 0.00 4.13
April 0.232747E+10 0.00 0.00 95223072.14 0.00 0.00 0.437809E+11 0.00 4.34
May 0.427751E+09 848658.00 0.00 0.108383E+09 0.00 0.00 0.461943E+11 0.00 4.78
June 33324211.79 0.306861E+10 0.00 79644859.23 0.00 0.00 0.292288E+11 0.00 5.21
July 0.00 0.104330E+11 0.00 47253100.29 0.00 0.00 0.144315E+11 0.00 5.30
August 2861780.38 0.452176E+10 0.00 66430925.01 0.00 0.00 0.231257E+11 0.00 5.22
September 0.150835E+09 0.165970E+10 0.00 79075297.65 387600.89 0.00 0.359787E+11 0.00 4.95
October 0.276183E+10 0.00 0.00 90045396.67 0.00 0.00 0.453552E+11 0.00 4.36
November 0.515595E+10 0.00 0.00 73282596.44 0.00 0.00 0.385060E+11 0.00 4.16
December 0.130584E+11 0.00 0.00 36145556.06 0.00 0.00 0.322311E+11 0.00 3.97
                   
Annual Sum or Average 0.588315E+11 0.196854E+11 0.00 0.794818E+09 1149519.92 0.00 0.407251E+12 0.00 4.53
Minimum of Months 0.00 0.00 0.00 28252737.64 0.00 0.00 0.144315E+11 0.00 3.95
Maximum of Months 0.141286E+11 0.104330E+11 0.00 0.108383E+09 761919.04 0.00 0.461943E+11 0.00 5.30



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.983864E+10 0.00 0.00 44502320.26 0.00 0.00 0.395605E+11 0.00 4.24
February 0.778725E+10 0.00 0.00 39735387.62 0.00 0.00 0.374536E+11 0.00 4.24
March 0.305726E+10 2357160.91 0.00 79594637.87 0.00 0.00 0.460622E+11 0.00 4.48
April 0.102106E+10 0.00 0.00 0.118188E+09 0.00 0.00 0.494279E+11 0.00 4.74
May 53759600.01 948047.40 0.00 0.124672E+09 0.00 0.00 0.504836E+11 0.00 5.18
June 8432451.19 0.329634E+10 0.00 87717457.89 0.00 0.00 0.313084E+11 0.00 5.58
July 0.00 0.111309E+11 0.00 51103997.90 0.00 0.00 0.152908E+11 0.00 5.64
August 0.00 0.484134E+10 0.00 72522246.53 0.00 0.00 0.245766E+11 0.00 5.56
September 25624904.46 0.179018E+10 0.00 89598845.27 0.00 0.00 0.388868E+11 0.00 5.33
October 0.116480E+10 0.00 0.00 0.113374E+09 0.00 0.00 0.513534E+11 0.00 4.76
November 0.197119E+10 0.00 0.00 97920541.72 0.00 0.00 0.457860E+11 0.00 4.54
December 0.789004E+10 0.00 0.00 49935623.43 0.00 0.00 0.408820E+11 0.00 4.28
                   
Annual Sum or Average 0.328181E+11 0.210620E+11 0.00 0.968865E+09 0.00 0.00 0.471072E+12 0.00 4.89
Minimum of Months 0.00 0.00 0.00 39735387.62 0.00 0.00 0.152908E+11 0.00 4.24
Maximum of Months 0.983864E+10 0.111309E+11 0.00 0.124672E+09 0.00 0.00 0.513534E+11 0.00 5.64



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 28218250.25 0.00 0.00 0.115950E+09 0.00 0.00 0.681695E+11 0.00 18.81
February 57305757.91 0.00 0.00 0.101924E+09 0.00 0.00 0.627152E+11 0.00 18.91
March 10290005.83 4542735.30 0.00 0.160406E+09 0.00 0.00 0.655044E+11 0.00 19.56
April 4335822.51 0.00 0.00 0.190491E+09 0.00 0.00 0.651878E+11 0.00 20.27
May 84467078.12 1630368.58 0.00 0.155706E+09 0.00 0.00 0.615154E+11 0.00 21.69
June 32777102.57 0.472368E+10 0.00 0.106319E+09 0.00 0.00 0.347658E+11 0.00 22.37
July 0.00 0.151849E+11 0.00 61172055.69 0.00 0.00 0.150483E+11 0.00 22.20
August 0.00 0.680124E+10 0.00 91648450.58 0.00 0.00 0.259716E+11 0.00 22.15
September 21908787.69 0.263606E+10 0.00 0.116445E+09 0.00 0.00 0.462676E+11 0.00 22.18
October 59729310.51 0.00 0.00 0.189013E+09 0.00 0.00 0.669307E+11 0.00 20.22
November 44078640.69 0.00 0.00 0.180853E+09 0.00 0.00 0.623692E+11 0.00 19.49
December 53676076.35 0.00 0.00 0.115498E+09 0.00 0.00 0.665841E+11 0.00 18.83
                   
Annual Sum or Average 0.396787E+09 0.293521E+11 0.00 0.158542E+10 0.00 0.00 0.641030E+12 0.00 20.56
Minimum of Months 0.00 0.00 0.00 61172055.69 0.00 0.00 0.150483E+11 0.00 18.81
Maximum of Months 84467078.12 0.151849E+11 0.00 0.190491E+09 0.00 0.00 0.681695E+11 0.00 22.37



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.642132E+10 0.00 0.00 0.00 0.00 0.929764E+10 0.00 0.00 1.08
February 0.578259E+10 0.00 0.00 0.00 0.00 0.864423E+10 0.00 0.00 1.08
March 0.123752E+11 0.00 0.00 0.00 788543.46 0.209920E+10 0.00 0.00 1.06
April 0.138339E+11 0.00 0.00 0.00 0.00 82535877.88 0.00 0.00 1.06
May 0.130659E+11 0.00 0.00 0.00 285682.23 0.00 0.00 0.00 1.10
June 0.695415E+10 0.473065E+09 0.00 1349826.73 0.398453E+09 0.00 0.712545E+09 0.00 1.13
July 0.269824E+10 0.246898E+10 0.00 2768939.60 0.506536E+09 0.00 0.907091E+09 0.00 1.15
August 0.461506E+10 0.100082E+10 0.00 4518336.39 0.279404E+09 0.00 0.135717E+10 0.00 1.14
September 0.979968E+10 0.110977E+09 0.00 414876.06 0.366168E+09 0.00 0.248684E+09 0.00 1.13
October 0.144461E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.06
November 0.134792E+11 0.00 0.00 0.00 0.00 0.239284E+09 0.00 0.00 1.06
December 0.704337E+10 0.00 0.00 0.00 0.00 0.832744E+10 0.00 0.00 1.08
                   
Annual Sum or Average 0.110515E+12 0.405385E+10 0.00 9051978.79 0.155164E+10 0.286903E+11 0.322550E+10 0.00 1.09
Minimum of Months 0.269824E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.06
Maximum of Months 0.144461E+11 0.246898E+10 0.00 4518336.39 0.506536E+09 0.929764E+10 0.135717E+10 0.00 1.15



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:58:50

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.157920E+12 0.236646E+11 0.293538E+12 0.119506E+13 0.962387E+11
February 0.254103E+12 0.220224E+11 0.270970E+12 0.110808E+13 0.886872E+11
March 0.380983E+12 0.188003E+11 0.231883E+12 0.960451E+12 0.101539E+12
April 0.459750E+12 0.140823E+11 0.176551E+12 0.744362E+12 0.836286E+11
May 0.575468E+12 0.947593E+10 0.114260E+12 0.510967E+12 0.210362E+12
June 0.640497E+12 0.362775E+10 0.440775E+11 0.223870E+12 0.594111E+12
July 0.579845E+12 -0.183157E+10 -0.166573E+11 -0.574347E+11 0.100346E+13
August 0.487219E+12 0.151202E+10 0.217137E+11 0.121043E+12 0.778491E+12
September 0.361235E+12 0.591262E+10 0.732040E+11 0.345629E+12 0.418950E+12
October 0.240282E+12 0.127084E+11 0.160974E+12 0.680518E+12 0.114241E+12
November 0.126562E+12 0.151518E+11 0.196531E+12 0.797891E+12 0.761202E+11
December 0.142694E+12 0.225236E+11 0.283978E+12 0.114713E+13 0.928558E+11
           
Annual Sum or Average 0.440656E+13 0.147650E+12 0.185102E+13 0.777757E+13 0.365868E+13
Minimum of Months 0.126562E+12 -0.183157E+10 -0.166573E+11 -0.574347E+11 0.761202E+11
Maximum of Months 0.640497E+12 0.236646E+11 0.293538E+12 0.119506E+13 0.100346E+13