Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:00

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745

Simulation Timestamp: 2023-10-16 09:00:32


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 11245.05 991.17 991.17
Net Site Energy 11245.05 991.17 991.17
Total Source Energy 25941.65 2286.56 2286.56
Net Source Energy 25941.65 2286.56 2286.56


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 182.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1978.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 767.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 242.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1745.01 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 651.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 660.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 212.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 191.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.74 2671.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 61.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 6602.02 4643.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 182.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 1978.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 767.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 242.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 959.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 14.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 8.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 32.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 660.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 212.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 191.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.74 2671.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 20.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 34.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 182.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 1978.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 767.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 242.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1745.01 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 651.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 660.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 212.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 191.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 90.74 2671.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 61.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 89.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 259.36 251.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 233.52 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 581.92 409.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 89.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 259.36 251.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 233.52 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 581.92 409.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 6602.022 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 6602.022 100.00
     
Total On-Site and Utility Electric Sources 6602.022 100.00
Total Electricity End Uses 6602.022 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 656.30 54.39
Air to Air Heat Recovery for Heating 550.38 45.61
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 1206.68 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 114.67
Time Not Comfortable Based on Simple ASHRAE 55-2004 7492.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:00
RunPeriod RUNPERIOD 1
Weather File Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Latitude [deg] 32.17
Longitude [deg] -110.9
Elevation [m] 809.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 9.1389 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 13.3365 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 13.3365 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 9.2031 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 6.1031 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.8125 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 10.3656 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 8.7188 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 4.5531 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 4.5531 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 6.3938 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 4.5531 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 4.5531 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.3656 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 10.3656 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 11.7219 4.65 2934.4875
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 6.3938 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 6.8557 7.07 41.0709
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 6.8557 7.07 41.0709
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 9.1389 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 13.3365 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 13.3365 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 9.2031 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 6.1031 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.8125 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 10.3656 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 8.7188 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 4.5531 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 4.5531 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 4.5531 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 4.5531 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 4.5531 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 4.5531 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 6.3938 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 4.5531 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 4.5531 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 4.5531 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 10.3656 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 10.3656 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 11.7219 4.65 2934.4875  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 6.3938 18.58 0.0000  
Total 11345.29             6.8557 3.54 41.0709  
Conditioned Total 11345.29             6.8557 3.54 41.0709  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 4.4542 8.82 37.1989
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 21-JUL-19:00 16-DEC-22:10 - - - - - - - - - - 04-DEC-21:40
Heating 0.00 130651.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 195956.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 88772.42 54264.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 32159.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 43756.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 9286.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 3763.50 243148.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 1870.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 463845.66 428064.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 130651.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 195956.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 58789.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 24992.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 29272.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1856.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 30153.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 150.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 43756.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 9286.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 3763.50 243148.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 241.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 535.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 1093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 197.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 6266.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2429.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 769.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5526.46 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2063.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2092.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 673.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 605.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 287.38 2896.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 195.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 20908.60 5033.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 17.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 552.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 214.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 67.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 487.11 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 184.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 59.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 53.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 255.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1842.93 443.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 17.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 552.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 214.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 67.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 487.11 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 181.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 184.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 59.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 53.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.33 255.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 17.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1842.93 443.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.93 0.514628 0.426000 1.25 1.00 0.500000 0.000740 0.000052 1.25 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.394890 0.129424 0.300000 0.118467 0.358520 0.500000 0.002944 0.000027 0.119564 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.284484 0.208039 0.471000 0.133992 0.554769 0.500000 0.001831 0.000013 0.133992 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.303025 0.413013 0.300000 0.090908 1.00 0.500000 0.000922 0.000018 0.090908 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.150373 0.480182 0.562000 0.084510 1.00 0.500000 0.000793 0.000012 0.084510 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.64 0.064739 0.300000 1.09 0.300000 0.500000 0.023353 0.000065 1.09 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.60 0.089959 0.618000 0.988656 0.618000 0.500000 0.004235 0.000096 0.988656 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 5.25 0.190004 0.528000 2.77 0.528000 0.500000 0.002005 0.000248 2.77 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.71 0.695492 0.407000 0.694574 1.00 0.500000 0.000548 0.000107 0.694574 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.49 0.101655 0.698000 1.74 0.698000 0.500000 0.003748 0.000122 1.74 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.60 0.097147 0.667000 1.74 0.667000 0.500000 0.003922 0.000123 1.74 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.51 0.056436 0.300000 0.752634 0.300000 0.500000 0.012143 0.000047 0.752634 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.889130 0.353198 0.300000 0.266739 0.941861 0.500000 0.001079 0.000062 0.274740 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 5983.05 0.000052 124.77
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 3105.02 0.000027 84.74
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1513.03 0.000013 33.95
MECH_FLR_1 VAV BOX REHEAT COIL 2099.48 0.000018 54.92
STORAGE_FLR_1 VAV BOX REHEAT COIL 1372.78 0.000012 32.74
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 7469.37 0.000065 159.28
CAFE_FLR_1 VAV BOX REHEAT COIL 10999.38 0.000096 246.35
LOBBY_FLR_1 VAV BOX REHEAT COIL 28354.99 0.000248 628.48
ROOM_1_FLR_3 FAN COIL HEATING COIL 5574.35 0.000049 159.30
ROOM_2_FLR_3 FAN COIL HEATING COIL 5578.91 0.000049 159.43
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 32041.76 0.000280 915.66
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 32145.82 0.000281 918.63
ROOM_5_FLR_3 FAN COIL HEATING COIL 5564.49 0.000049 159.02
ROOM_6_FLR_3 FAN COIL HEATING COIL 5569.05 0.000049 159.15
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 12282.38 0.000107 298.40
ROOM_1_FLR_6 FAN COIL HEATING COIL 1686.87 0.000015 48.20
ROOM_2_FLR_6 FAN COIL HEATING COIL 1687.41 0.000015 48.22
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 8101.10 0.000071 231.50
BANQUET_FLR_6 VAV BOX REHEAT COIL 13889.13 0.000122 300.09
DINING_FLR_6 VAV BOX REHEAT COIL 14006.53 0.000123 302.86
KITCHEN_FLR_6 VAV BOX REHEAT COIL 5373.31 0.000047 114.98
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 7135.32 0.000062 194.74
VAV WITH REHEAT HEATING COIL 131459.73 0.001150 2306.64
FLR_3_DOAS HEATING COIL 10951.44 0.000096 192.16
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ZoneExhaust

User-Specified Maximum Flow Rate [m3/s]
LOBBY_FLR_1 EXHAUST FAN 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 1.23 0.000049 0.000439
ROOM_2_FLR_3 FAN COIL 1.22 0.000049 0.000436
ROOM_3_MULT19_FLR_3 FAN COIL 6.76 0.000280 0.002408
ROOM_4_MULT19_FLR_3 FAN COIL 7.30 0.000281 0.002695
ROOM_5_FLR_3 FAN COIL 1.08 0.000049 0.000384
ROOM_6_FLR_3 FAN COIL 1.07 0.000049 0.000381
ROOM_1_FLR_6 FAN COIL 0.327138 0.000015 0.000117
ROOM_2_FLR_6 FAN COIL 0.324563 0.000015 0.000116
ROOM_3_MULT9_FLR_6 FAN COIL 1.43 0.000071 0.000516
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 1.23
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 1.22
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 6.76
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 7.30
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 1.08
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 1.07
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.327138
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.324563
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.43
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.74 6.70 0.008478 12.80 0.008478 0.000439 1.23  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.74 6.70 0.008478 12.80 0.008478 0.000436 1.22  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.74 6.70 0.008417 12.80 0.008417 0.002408 6.76  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.74 6.70 0.008630 12.80 0.008500 0.002695 7.30  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.74 6.70 0.008474 12.80 0.008474 0.000384 1.08  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.74 6.70 0.008474 12.80 0.008474 0.000381 1.07  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.74 6.70 0.008479 12.80 0.008479 0.000117 0.327138  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.74 6.70 0.008479 12.80 0.008479 0.000116 0.324563  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.74 6.70 0.008540 12.80 0.008500 0.000516 1.43  
VAV WITH REHEAT COOLING COIL 31.95 6.70 0.007701 10.79 0.007701 0.020736 24.62 580553.63
FLR_3_DOAS COOLING COIL 40.80 6.70 0.005631 11.84 0.005631 0.002355 2.05 65945.86
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 13.64 11.71 24.75 11.71 24.62 24.62 0.300000 0.475667 24.62
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 24.62 11.66
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 11.66
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 24.62
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.020736 0.000023
VAV WITH REHEAT_HEATC_CONTROLLER 0.001150  
FLR_3_DOAS_COOLC_CONTROLLER 0.002355 0.000202
FLR_3_DOAS_HEATC_CONTROLLER 0.000096  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.030582 6301.84  
HEATSYS1 PUMP 0.003096 932.52 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.003096 0.371576
COOLSYS1 0.030582 3.67
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 353944.71 353944.71 0.003096
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.030582 4362.97
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.030582 856217.24 856882.29 97.68
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 20.90 15.40 11.90 14.80 12.70 15.40 23.30 26.30 31.20 30.40 29.80 27.80


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 32.17 -110.88 -7.00 809.00 91976 1.0932


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 21.66 19.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 9.139 5.380 0.000 0.000 0.000 0.000 14.519 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 13.336 10.760 0.000 0.000 0.000 0.000 24.096 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 13.336 10.760 0.000 0.000 0.000 0.000 24.096 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 9.203 5.380 0.000 0.000 0.000 0.000 14.583 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 6.103 2.690 0.000 0.000 0.000 0.000 8.793 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.813 61.680 535.850 0.000 0.000 0.000 603.343 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 10.366 5.380 0.000 0.000 0.000 0.000 15.746 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 8.719 8.070 0.000 0.000 0.000 0.000 16.789 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 6.394 0.000 0.000 0.000 0.000 0.000 6.394 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 4.553 6.750 0.000 0.000 0.000 0.000 11.303 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 4.553 10.520 0.000 0.000 0.000 0.000 15.073 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 10.366 67.820 0.000 0.000 0.000 0.000 78.186 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 10.366 67.820 0.000 0.000 0.000 0.000 78.186 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 11.722 515.227 2419.260 0.000 0.000 0.000 2946.209 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 6.394 0.000 0.000 0.000 0.000 0.000 6.394 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 18084.325 9.139 169.807 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 18084.325
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 894.495 13.336 82.602 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 894.495
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 1035.829 13.336 82.602 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1035.829
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 1511.551 9.203 569.967 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1511.551
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 578.329 6.103 283.494 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 578.329
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 453.605 5.813 54.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 453.605
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1957.673 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1957.673
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 11405.759 8.719 27.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 11405.759
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 111.660 4.553 74.440 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.660
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 111.691 4.553 74.460 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.691
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 2489.757 6.394 118.803 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2489.757
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 177.672 4.553 118.448 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.672
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 177.651 4.553 118.434 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 177.651
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 111.691 4.553 74.460 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 111.691
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 3437.839 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3437.839
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 3437.839 10.366 13.757 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3437.839
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1210.923 11.722 54.453 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1210.923
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 2635.024 6.394 118.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2635.024


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 457.500 4.429 20.573 0.000 0.250 0.000 0.750 ReachInFreezer 457.500 457.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 285.000 2.759 12.816 0.000 0.250 0.000 0.750 ReachInRefrigerator 285.000 285.000


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.464 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.198 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 1.287 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.608 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.684 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.370 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.442 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2887
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.8346
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.6100
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.4545
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.4264
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.5624
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.5260
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.4637404 3.4637404 3.4637404  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.1981135 1.1981135 1.1981135  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
21 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
22 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
23 0 21.361010 0.87247630E-01 5.4456762  
24 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
25 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
26 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
27 0 21.361010 0.87247630E-01 5.4456762  
28 9 0.16691074E-14 0.45207920E-16 -0.13282787E-09 -0.59403108E-17
29 8 0.19494068E-07 0.16957001E-12 0.35230437E-03 -0.22165426E-09
30 7 -0.11479370E-01 0.90467759E-08 -0.21987867E-01 0.13052461E-03
31 6 0.38463807 0.31869432E-05 0.45441076 -0.45036152E-02
32 5 -4.9884079 0.12028467E-03 -4.3052891 0.60677235E-01
33 4 32.108494 0.99355415E-03 20.908458 -0.41024850
34 3 -109.32288 0.21841230E-02 -54.572312 1.4876971
35 2 195.24423 0.12380226E-02 76.910992 -2.8707534
36 1 -170.46733 0.13310261E-03 -54.975783 2.7333683
37 0 57.057407 0.76355891E-06 15.605832  
38 9 0.14115123E-14 0.53960859E-16 -0.11739578E-09 -0.22900007E-17
39 8 0.17311930E-07 0.20639465E-12 0.32798840E-03 -0.19684260E-09
40 7 -0.10748946E-01 0.11327704E-07 -0.20934514E-01 0.12221941E-03
41 6 0.36478417 0.40360747E-05 0.43737925 -0.42695883E-02
42 5 -4.7945715 0.15382307E-03 -4.1739388 0.58273831E-01
43 4 31.250576 0.12816568E-02 20.393829 -0.39885853
44 3 -107.49604 0.28390629E-02 -53.554356 1.4613070
45 2 193.43186 0.16201491E-02 75.979619 -2.8419759
46 1 -169.79719 0.17527083E-03 -54.709122 2.7216233
47 0 57.057407 0.10123612E-05 15.653272  
48 9 0.65135446E-15 0.56204292E-16 -0.11372497E-09 -0.53489081E-17
49 8 0.16791160E-07 0.21454591E-12 0.32203280E-03 -0.19092129E-09
50 7 -0.10569524E-01 0.11862766E-07 -0.20675571E-01 0.12017931E-03
51 6 0.35990649 0.42391557E-05 0.43318136 -0.42120931E-02
52 5 -4.7469406 0.16196889E-03 -4.1415055 0.57683257E-01
53 4 31.039704 0.13525358E-02 20.266625 -0.39605902
54 3 -107.04684 0.30019179E-02 -53.302690 1.4548183
55 2 192.98603 0.17160237E-02 75.749609 -2.8348971
56 1 -169.63227 0.18593554E-03 -54.643729 2.7187328
57 0 57.057407 0.10758168E-05 15.665287  
58 9 0.10314710E-14 0.47183642E-16 -0.12881513E-09 -0.40099708E-17
59 8 0.18927665E-07 0.17950474E-12 0.34608657E-03 -0.21521408E-09
60 7 -0.11292911E-01 0.96443222E-08 -0.21719088E-01 0.12840450E-03
61 6 0.37957032 0.34070209E-05 0.45007157 -0.44438791E-02
62 5 -4.9389364 0.12890179E-03 -4.2718596 0.60063826E-01
63 4 31.889569 0.10670331E-02 20.777560 -0.40734193
64 3 -108.85680 0.23501275E-02 -54.313423 1.4809641
65 2 194.78196 0.13343675E-02 76.673975 -2.8634131
66 1 -170.29645 0.14368413E-03 -54.907648 2.7303734
67 0 57.057407 0.82565881E-06 15.617726  
68 9 0.86975537E-15 0.52023775E-16 -0.12536948E-09 -0.54620444E-17
69 8 0.18440443E-07 0.18784465E-12 0.34068694E-03 -0.20967419E-09
70 7 -0.11130813E-01 0.10155400E-07 -0.21485363E-01 0.12656138E-03
71 6 0.37516444 0.35965268E-05 0.44629465 -0.43919449E-02
72 5 -4.8959230 0.13636263E-03 -4.2427425 0.59530495E-01
73 4 31.699203 0.11309484E-02 20.663505 -0.40481456
74 3 -108.45147 0.24950915E-02 -54.087828 1.4751087
75 2 194.37988 0.14187814E-02 76.467519 -2.8570287
76 1 -170.14779 0.15298304E-03 -54.848449 2.7277680
77 0 57.057407 0.88039223E-06 15.628184  
78 7 -0.15963512E-14 -0.15187529E-16 -0.22427203E-13 0.56155309E-15
79 6 0.17983713E-10 0.23594901E-11 0.52322926E-09 -0.18637893E-10
80 5 -0.60139213E-07 0.11510628E-07 -0.21924491E-05 0.17161312E-06
81 4 0.62746279E-04 0.43399923E-05 0.17681060E-02 -0.28244642E-03
82 3 -0.90508353E-02 0.15320797E-03 -0.21560640 0.43341486E-01
83 2 0.12836503 0.66328859E-03 2.9007871 -0.61911613
84 1 -0.32478029 0.41934727E-03 -7.1379041 1.5697129
85 0 0.20664896 0.54311639E-05 4.4522013  
86 7 -0.22427203E-13 -0.15187529E-16 -0.15963512E-14 0.56155309E-15
87 6 0.52322926E-09 0.23594901E-11 0.17983713E-10 -0.18637893E-10
88 5 -0.21924491E-05 0.11510628E-07 -0.60139213E-07 0.17161312E-06
89 4 0.17681060E-02 0.43399923E-05 0.62746279E-04 -0.28244642E-03
90 3 -0.21560640 0.15320797E-03 -0.90508353E-02 0.43341486E-01
91 2 2.9007871 0.66328859E-03 0.12836503 -0.61911613
92 1 -7.1379041 0.41934727E-03 -0.32478029 1.5697129
93 0 4.4522013 0.54311639E-05 0.20664896  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
103 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
104 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
105 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
106 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
107 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
108 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
109 0 1.0055995 0.48413807E-04 60.838472  
110 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
111 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
112 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
113 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
114 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
115 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
116 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
117 0 1.0055995 0.48413807E-04 60.838472  
118 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
119 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
120 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
121 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
122 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
123 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
124 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
125 0 1.0055995 0.48413807E-04 60.838472  
126 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
127 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
128 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
129 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
130 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
131 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
132 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
133 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.5119_SHGC_0.25 37 1 VerySmooth 2.910 2.910 1.000 0.251    
2 RESWINDOW_U_0.5119_SHGC_0.25 38 1 VerySmooth 2.910 2.910 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   1.79780E-002 0.16139 0.60964 0.60964 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10364 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   1.79780E-002 0.16139 0.60964 0.60964 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10364 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 1.500
2 RACK2 1 0 Zone Air-Cooled 3.000


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 0.576 0.5074
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 0.263 2.9576E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 7.058E-002 1.052E-003 5.193E-004 0.956 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 2.724E-002 3.507E-004 9.551E-004 0.319 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 6.438E-002 3.920E-004 1.025E-003 0.356 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 3.715E-002 3.920E-004 8.507E-004 0.356 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 8.791E-002 1.127E-003 1.002E-003 1.023 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 0.156 8.261E-004 4.549E-004 0.751 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.446 3.407E-004 6.517E-004 0.310 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 4.096E-002 1.050E-003 1.025E-003 1.240 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 4.095E-002 1.050E-003 1.025E-003 1.240 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 1.143E-002 4.660E-004 1.025E-003 0.550 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.143E-002 4.660E-004 1.025E-003 0.550 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 4.096E-002 1.050E-003 1.025E-003 1.240 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 4.095E-002 1.050E-003 1.025E-003 1.240 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 4.953E-002 1.272E-004 1.025E-003 0.150 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 4.096E-002 1.050E-003 5.186E-004 1.240 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 4.095E-002 1.050E-003 5.186E-004 1.240 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 2.096E-002 8.543E-004 4.660E-004 1.009 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 0.100 3.015E-004 2.330E-004 0.356 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 0.100 3.015E-004 2.330E-004 0.356 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 8.953E-002 8.667E-004 4.697E-004 1.024 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 8.763E-002 2.126E-004 1.761E-004 0.251 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 8.7310E-002
2 Clear Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 3.8709E-002
3 Clear Turbid Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 9.7087E-002
4 Clear Turbid Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 4.2189E-002
5 Intermediate Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 6.5660E-002
6 Intermediate Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 2.4295E-002
7 Overcast Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 2.6511E-002
8 Overcast Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 8.7811E-003
9 Clear Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 9.8430E-002
10 Clear Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 4.7382E-002
11 Clear Turbid Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1097
12 Clear Turbid Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 5.1591E-002
13 Intermediate Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 7.2656E-002
14 Intermediate Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 3.0684E-002
15 Overcast Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 2.9789E-002
16 Overcast Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 1.2036E-002
17 Clear Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.1147E-002
18 Clear Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.2078E-002
19 Clear Turbid Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.6306E-002
20 Clear Turbid Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 9.1307E-003
21 Intermediate Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.5594E-002
22 Intermediate Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 6.2294E-003
23 Overcast Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.6108E-002
24 Overcast Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 9.2309E-003
25 Clear Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.1147E-002
26 Clear Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.2078E-002
27 Clear Turbid Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.6306E-002
28 Clear Turbid Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 9.1307E-003
29 Intermediate Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.5594E-002
30 Intermediate Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 6.2294E-003
31 Overcast Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.6108E-002
32 Overcast Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 9.2309E-003


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 36609.91672 36609.91672 2.93001 2.93001 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 21:30:00 32.35450 5.61809E-003 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 0.85446   00:10:00 0.50000 4.31558E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 4933.90178 4933.90178 0.39489 0.39489 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 40.80000 5.63111E-003 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 2532.51288 2532.51288 0.11956 0.11956 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3554.24988 3554.24988 0.28448 0.28448 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 37.60800 5.62614E-003 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 871.43109 871.43109 4.11430E-002 9.17347E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 3786.74184 3786.74184 0.30303 0.30303 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 36.61050 5.62460E-003 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1664.27330 1664.27330 7.85753E-002 7.85753E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1879.12043 1879.12043 0.15037 0.15037 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 38.05133 5.62683E-003 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 968.19906 968.19906 4.57116E-002 5.77652E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 45546.09193 45546.09193 3.64498 3.64498 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 40.13500 5.63007E-003 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 2235.00215 2235.00215 0.10552 0.10552 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 19970.77361 19970.77361 1.59977 1.59977 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 40.80000 5.63111E-003 188.86188 142.30000 0.67639 0.00000
14 CAFE_FLR_1 Heating 6264.84996 6264.84996 0.29578 0.67639 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 188.86188 142.30000 0.67639 0.00000
15 LOBBY_FLR_1 Cooling 65527.92905 65527.92905 5.24641 5.24641 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 40.80000 5.63111E-003 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 15090.20488 15090.20488 0.71246 1.89399 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 11424.24333 11424.24333 1.23196 1.23196 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 39.11533 5.62848E-003 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 5574.49315 5574.49315 0.26472 0.26472 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 11342.92923 11342.92923 1.22319 1.22319 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 38.93800 5.62821E-003 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 5579.05193 5579.05193 0.26494 0.26494 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 62682.34837 62682.34837 6.75941 6.75941 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 40.80000 5.63111E-003 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 32042.15478 32042.15478 1.52168 1.52168 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 67673.90470 67673.90470 7.29826 7.29826 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 40.26800 5.63027E-003 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 32146.22281 32146.22281 1.52663 1.52663 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 9980.67707 9980.67707 1.07629 1.07629 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 36.74350 5.62481E-003 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 5564.62584 5564.62584 0.26426 0.26426 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 9911.31898 9911.31898 1.06881 1.06881 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 36.41100 5.62429E-003 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 5569.18721 5569.18721 0.26447 0.26447 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 21324.00817 21324.00817 1.70657 1.70657 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 40.40100 5.63048E-003 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 8955.58122 8955.58122 0.42283 0.47476 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 3033.62175 3033.62175 0.32714 0.32714 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 39.11533 5.62848E-003 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 1686.91035 1686.91035 8.01087E-002 8.01087E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 3009.74627 3009.74627 0.32456 0.32456 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 38.93800 5.62821E-003 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 1687.44823 1687.44823 8.01343E-002 8.01343E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 13289.02995 13289.02995 1.43311 1.43311 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 40.80000 5.63111E-003 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 8101.25970 8101.25970 0.38472 0.38472 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 31025.09526 31025.09526 2.48608 2.48608 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 40.66700 5.63090E-003 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 5576.86003 5576.86003 0.26330 1.18780 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 32465.20578 32465.20578 2.60144 2.60144 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 40.66700 5.63090E-003 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 5694.86988 5694.86988 0.26887 1.18780 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 0.50000 4.31558E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 31265.19337 31265.19337 2.50878 2.50878 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 39.60300 5.62924E-003 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 1778.28186 1778.28186 8.39469E-002 0.36735 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 0.50000 4.31558E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 11110.05808 11110.05808 0.88913 0.88913 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 40.80000 5.63111E-003 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 5819.14331 5819.14331 0.27474 0.27474 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 0.50000 4.31558E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 518010.32 24.62375 24.62375 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 131162.48 7.37042 7.37042 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
3 FLR_3_DOAS Cooling Sensible 63092.52 20.26729 2.05125 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 FLR_3_DOAS Heating Sensible 36503.53 4.65167 2.05125 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.93001
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.51463
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.42600
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.24819
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.40340E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.23423E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.24819
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5983.04768
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.23423E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 124.76615
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.39489
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12942
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.11847
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.35852
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.94381E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.71641E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.11956
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3105.02097
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.71641E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 84.73939
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.28448
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20804
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.47100
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13399
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.55477
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.83139E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.32366E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13399
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1513.02876
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.32366E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 33.95399
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.30303
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.41301
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 9.09075E-002
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.22489E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.83672E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.09075E-002
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2099.48023
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.83672E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 54.92150
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.15037
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.48018
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.56200
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.45099E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.93450E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.20097E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.45099E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1372.78174
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.20097E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 32.74049
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.64498
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.47393E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.09349
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.33535E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.53453E-005
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.09349
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7469.37098
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.53453E-005
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 159.27761
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.59977
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 8.99585E-002
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.61800
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.98866
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.61800
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.23528E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.62274E-005
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.98866
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10999.38444
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.62274E-005
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 246.35319
99 Fan:ZoneExhaust LOBBY_FLR_1 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.24641
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19000
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52800
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.77010
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52800
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.00522E-003
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.48062E-004
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.77010
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
110 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 28354.99217
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.48062E-004
113 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 628.47613
114 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
115 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.23196
116 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.23196
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.87669E-005
118 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.38985E-004
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.74179
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.47827E-003
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.47827E-003
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.38985E-004
125 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.23196
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5574.35247
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.87669E-005
128 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 159.30100
129 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
130 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.22319
131 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.22319
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.88067E-005
133 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.35860E-004
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.74179
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.47803E-003
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.47803E-003
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.35860E-004
140 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.22319
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5578.91114
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.88067E-005
143 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 159.43124
144 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
145 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 6.75941
146 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 6.75941
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.80315E-004
148 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.40836E-003
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.74197
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.41720E-003
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.41720E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.40836E-003
155 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 6.75941
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 32041.75602
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.80315E-004
158 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 915.65817
159 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
160 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 7.29826
161 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 7.29826
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.81226E-004
163 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.69455E-003
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.74108
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.62989E-003
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.69455E-003
170 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 7.29826
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 32145.82280
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.81226E-004
173 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 918.63142
174 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
175 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.07629
176 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.07629
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.86805E-005
178 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.83512E-004
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.74180
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.47403E-003
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.47403E-003
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.83512E-004
185 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.07629
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5564.48539
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.86805E-005
188 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 159.01910
189 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
190 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.06881
191 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.06881
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.87204E-005
193 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.80847E-004
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.74180
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.47374E-003
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.47374E-003
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.80847E-004
200 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.06881
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5569.04665
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.87204E-005
203 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 159.14941
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.70657
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.69549
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.40700
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.69457
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.47814E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.07452E-004
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.69457
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
214 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12282.38362
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.07452E-004
217 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 298.39666
218 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
219 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.32714
220 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.32714
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.47575E-005
222 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.16569E-004
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.74178
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.47948E-003
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.47948E-003
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.16569E-004
229 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.32714
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1686.86890
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.47575E-005
232 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 48.20421
233 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
234 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.32456
235 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.32456
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.47622E-005
237 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.15652E-004
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.74178
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.47924E-003
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.47924E-003
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.15652E-004
244 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.32456
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1687.40677
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.47622E-005
247 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 48.21958
248 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
249 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.43311
250 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.43311
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 7.08720E-005
252 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 5.16289E-004
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.74140
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.53960E-003
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.16289E-004
259 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.43311
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 8101.09931
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 7.08720E-005
262 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 231.49638
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.48608
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10166
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.69800
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.73528
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.69800
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.74796E-003
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.21508E-004
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.73528
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
273 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13889.13125
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.21508E-004
276 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 300.09240
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.60144
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.71475E-002
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.66700
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.73516
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.66700
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.92187E-003
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.22535E-004
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.73516
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
287 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14006.53390
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.22535E-004
290 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 302.86254
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.50878
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 5.64355E-002
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.75263
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.21426E-002
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.70081E-005
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.75263
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
301 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5373.30983
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.70081E-005
304 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 114.97548
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.88913
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.35320
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.26674
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.94186
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.07872E-003
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.24229E-005
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.27474
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
315 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7135.32249
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.24229E-005
318 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 194.73523
319 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 13.64465
320 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 11.71270
321 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 24.74594
322 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 11.71270
323 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 24.62375
324 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 24.62375
325 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
326 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.47567
327 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
328 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
329 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
333 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
334 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
335 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 24.62375
336 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
337 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 24.62375
338 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 11.66146
339 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 11.66146
340 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 31.95058
341 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.78890
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.70111E-003
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.70111E-003
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 580553.63269
346 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.07360E-002
347 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 24.62375
348 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 131459.72513
349 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.15007E-003
350 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 2306.64448
351 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 24.62375
352 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 2.07360E-002
353 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 2.29644E-005
354 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.15007E-003
355 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
356 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
357 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
358 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 40.80000
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.83593
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 5.63111E-003
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 5.63111E-003
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 65945.85541
364 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.35543E-003
365 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
366 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 10951.44367
367 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.58080E-005
368 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 192.15837
369 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
370 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 2.35543E-003
371 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 2.02167E-004
372 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 9.58080E-005
373 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 3.05821E-002
374 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 6301.83649
375 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 3.09646E-003
376 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.37158
377 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 3.09646E-003
378 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 932.51858
379 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
380 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 353944.70630
381 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 353944.71000
382 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 3.09646E-003
383 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 3.05821E-002
384 PlantLoop COOLSYS1 Plant Loop Volume [m3] 3.66985
385 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 3.05821E-002
386 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 4362.97395
387 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 3.05821E-002
388 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 856217.23839
389 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 856882.29000
390 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 97.68458
391 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
392 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
393 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
394 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
395 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 6014.20
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 3117.46
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1520.36
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 2108.19
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1379.12
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 7507.59
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 11052.76
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 28493.82
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 6005.31
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 6010.22
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 34518.74
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 34630.84
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 5994.68
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 5999.59
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 12337.37
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 1817.23
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 1817.81
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 8727.13
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 13959.50
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 14077.45
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 5400.73
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 7163.91
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 105874.89
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 8820.06


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 20452.85 15940.43 4512.42 0.78 2834.99 28.75
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 20307.76 15827.32 4480.44 0.78 2815.10 28.55
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 112916.66 87955.86 24960.80 0.78 15975.96 162.04
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 123710.41 95364.01 28346.40 0.77 16836.39 170.76
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 17876.07 13931.65 3944.42 0.78 2481.28 25.17
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 17752.37 13835.22 3917.16 0.78 2464.35 24.99
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 5430.44 4232.39 1198.05 0.78 752.42 7.63
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 5387.83 4199.17 1188.66 0.78 746.57 7.57
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 23911.30 18574.40 5336.90 0.78 3279.94 33.27
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 691902.64 436910.77 254991.88 0.63 102074.21 1035.29
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 54169.20 34464.63 19704.58 0.64 5364.64 54.41


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 3.93 13.40


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.940 0.824   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.198 1.198   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.608 1.296   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.608 1.296   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.608 1.296   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.608 1.296   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.442 1.186   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.442 1.186   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.442 1.186   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.442 1.186   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.442 1.186   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.5870025657E-002 3.9403928078E-002 Pass Pass 0.1586089121 0.6482313946 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 6.1690587794E-002 9.4286015701E-002 Pass Pass 0.1501569923 0.4861674759 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 5.1165753538E-002 7.8211811582E-002 Pass Pass 0.5131496989 5.0151811494 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 2.1374569249E-002 3.0482686118E-002 Pass Pass 8.7600617144E-002 0.2298133495 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 7.9274468454E-003 2.8350708541E-002 Pass Pass 0.2281849464 0.8873076284 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 0.1015813412 0.3039186944 Pass Pass 7.5691742165E-002 0.1755126795 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 0.1210480459 0.1938677546 Pass Pass 0.2620752198 1.8909865516 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 6.4111436125E-002 0.1026069261 Pass Pass 8.8798686487E-002 0.3010975417 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 5.2467607539E-002 0.1985462551 Pass Pass 0.1834745233 0.5171032881 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 7.8943439102E-002 0.2216090482 Pass Pass 0.6023768346 4.2360835153 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 2.9121815550E-002 4.1367202469E-002 Pass Pass 3.1021593254E-002 5.0964345997E-002 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 2.3435252907E-002 8.7449339045E-002 Pass Pass 0.2729522518 1.0593962792 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 3.1411209518E-002 0.1254177552 Pass Pass 0.1616985990 0.3487962461 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 4.5825381326E-002 0.1660287754 Pass Pass 1.8756917576 20.4688726318 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 2.0994519695E-002 2.8292463007E-002 Pass Pass 7.8829426183E-002 0.2470333155 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 6.5202597951E-002 0.2365116876 Pass Pass 0.3940310132 2.1170074561 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 8.8040231751E-002 0.2518515592 Pass Pass 1.0063075655 8.3318600982 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 6.2710390879E-002 0.2355196320 Pass Pass 0.2905417520 0.8252894857 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 0.1265146326 0.2559747069 Pass Pass 0.1011836135 0.3316047531 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 0.1202801705 0.2308416091 Pass Pass 9.7838667321E-002 0.3072891060 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 0.1254749616 0.3354765144 Pass Pass 9.2476124969E-002 0.2225837236 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 2.6398863445E-002 3.8219875134E-002 Pass Pass 0.1133025172 0.2224819034 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 2720.32 70.22 393.68 2424.78 8151.25 13760.25



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 0.50 0.00 0.50 Wetbulb [C] 2.10 140.00
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 40.80 13.30 18.50 Wetbulb [C] 4.80 310.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 3.00 2      
Feb 34.00 28      
Mar 40.00 18      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 81.00 18      
Aug 71.00 20      
Sep 27.00 12      
Oct 9.00 6      
Nov 35.00 14      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.845 0.940 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.079 1.287 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.079 1.287 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.079 1.287 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.079 1.287 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 1.079 1.287 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.55 0.221 0.228 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.137 1.370 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.137 1.370 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.137 1.370 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.137 1.370 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.137 1.370 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.137 1.370 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.137 1.370 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.137 1.370 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.137 1.370 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.137 1.370 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 1.296 1.608 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 1.296 1.608 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 1.296 1.608 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 1.296 1.608 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.186 1.442 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.186 1.442 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 1.186 1.442 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.186 1.442 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.186 1.442 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.345 1.684 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.55 0.221 0.228 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.55 0.221 0.228 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.186 0.196 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.186 0.196 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.186 0.196 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.186 0.196 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.186 0.196 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.186 0.196 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.186 0.196 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.186 0.196 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.186 0.196 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.186 0.196 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.185 0.196 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.185 0.196 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.185 0.196 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.188 0.196 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   23.26 0.00 0.00 23.26 23.26 2.910 0.251 0.251             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   65.50 0.00 0.00 65.50 65.50 2.910 0.251 0.251             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   85.08 0.00 0.00 85.08 85.08 2.910 0.251 0.251             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.910 0.251 0.251             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.910 0.251 0.251             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.910 0.251 0.251             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.910 0.251 0.251             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   3.68 0.00 0.00 3.68 279.56 2.910 0.251 0.251             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   3.68 0.00 0.00 3.68 279.65 2.910 0.251 0.251             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.910 0.251 0.251             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.910 0.251 0.251             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.910 0.251 0.251             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.910 0.251 0.251             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.910 0.251 0.251             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   2.15 0.00 0.00 2.15 8.59 2.910 0.251 0.251             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   2.15 0.00 0.00 2.15 8.58 2.910 0.251 0.251             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.910 0.251 0.251             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.910 0.251 0.251             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.910 0.251 0.251             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.910 0.251 0.251             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.910 0.251 0.251             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   6.74 0.00 0.00 6.74 60.70 2.910 0.251 0.251             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.910 0.251 0.251             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.910 0.251 0.251             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.910 0.251 0.251             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.910 0.251 0.251             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.910 0.251 0.251             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   5.82 0.00 0.00 5.82 5.82 2.910 0.251 0.251             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   5.21 0.00 0.00 5.21 5.21 2.910 0.251 0.251             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.910 0.251 0.251             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.910 0.251 0.251                      
North Total or Average             432.95 2.910 0.251 0.251                      
Non-North Total or Average             780.84 2.910 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.016 1.198 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 9.1389 1978.83 18084.33 LightsWired LTG_SCH_BASEMENT 51.16 168.00 51.10 0.0000 Y 173.46
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 13.3365 67.07 894.50 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 8.61
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 13.3365 77.67 1035.83 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 9.97
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 9.2031 164.24 1511.55 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 16.63
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 6.1031 94.76 578.33 LightsWired LTG_SCH_STORAGE 25.68 168.00 25.65 0.0000 Y 2.78
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.8125 78.04 453.60 LightsWired LTG_SCH_LAUNDRY 51.36 168.00 51.30 0.0000 Y 4.37
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 10.3656 188.86 1957.67 LightsWired LTG_SCH_DINING 58.69 168.00 49.02 0.0000 Y 18.01
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 8.7188 1308.19 11405.76 LightsWired LTG_SCH_LOBBY 58.69 168.00 56.97 0.0000 Y 121.97
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 4.5531 156.09 710.69 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 4.5531 156.07 710.61 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 4.5531 1863.81 8486.17 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 76.02
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 4.5531 1864.32 8488.49 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 76.04
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 4.5531 156.09 710.69 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 4.5531 156.07 710.61 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.37
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 6.3938 1557.62 9959.03 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 109.60
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 4.5531 39.02 177.67 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.59
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 4.5531 39.02 177.65 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.59
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 4.5531 220.77 1005.22 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 9.00
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 10.3656 331.66 3437.84 LightsWired LTG_SCH_DINING 58.69 168.00 53.97 0.0000 Y 34.83
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 10.3656 331.66 3437.84 LightsWired LTG_SCH_DINING 58.69 168.00 53.97 0.0000 Y 34.83
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 11.7219 103.30 1210.92 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 13.33
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 6.3938 412.12 2635.02 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 29.00
Interior Lighting Total       6.8557 11345.29 77780.02               507.76


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.07 11405.76 798.40
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Stepped 0.00 11405.76 0.00
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.39 1957.67 763.49
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Stepped 0.00 1957.67 0.00
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3437.84 687.57
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Stepped 0.00 3437.84 0.00
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.20 3437.84 687.57
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Stepped 0.00 3437.84 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 15448.40 AstronomicalClock -   83.79 83.79 242.97
Exterior Lighting Total 15448.40           242.97



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 353944.71 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 856882.29 2.96 857032.91 2.96 3.93 13.40


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12290.64 20452.85 15940.43 4512.42 0.78 - 2834.99 28.75
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12203.16 20307.76 15827.32 4480.44 0.78 - 2815.10 28.55
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 67429.05 112916.66 87955.86 24960.80 0.78 - 15975.96 162.04
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 75441.70 123710.41 95364.01 28346.40 0.77 - 16836.39 170.76
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10737.52 17876.07 13931.65 3944.42 0.78 - 2481.28 25.17
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10662.90 17752.37 13835.22 3917.16 0.78 - 2464.35 24.99
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3263.69 5430.44 4232.39 1198.05 0.78 - 752.42 7.63
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3238.01 5387.83 4199.17 1188.66 0.78 - 746.57 7.57
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 14455.00 23911.30 18574.40 5336.90 0.78 - 3279.94 33.27
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 580553.63 691902.64 436910.77 254991.88 0.63 - 102074.21 1035.29
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 65945.86 54169.20 34464.63 19704.58 0.64 - 5364.64 54.41
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 5983.05 6014.20 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 3105.02 3117.46 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1513.03 1520.36 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2099.48 2108.19 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1372.78 1379.12 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 7469.37 7507.59 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 10999.38 11052.76 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 28354.99 28493.82 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5574.35 6005.31 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5578.91 6010.22 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 32041.76 34518.74 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 32145.82 34630.84 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5564.49 5994.68 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5569.05 5999.59 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 12282.38 12337.37 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1686.87 1817.23 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1687.41 1817.81 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 8101.10 8727.13 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 13889.13 13959.50 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 14006.53 14077.45 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 5373.31 5400.73 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 7135.32 7163.91 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 131459.73 105874.89 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 10951.44 8820.06 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.23 866.85 703.64 1.00 1.15 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.22 860.68 703.64 1.00 1.15 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 6.76 4756.17 703.64 1.00 0.95 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 7.30 5135.32 703.64 1.00 0.95 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.08 757.32 703.64 1.00 1.18 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.07 752.05 703.64 1.00 1.18 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.33 230.19 703.64 1.00 1.65 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.32 228.37 703.64 1.00 1.66 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.43 1008.39 703.64 1.00 1.12 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 24.62 55172.92 2240.64 1.00 1.11 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.030582 6301.84 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.003096 932.52 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.030582 4362.97 142664.32 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.80 0.58 0.51
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.80 0.26 0.03



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 36609.92 36609.92 18.50 2.930 2.930 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 21:30:00 24.00 24.00 0.00916 32.35 0.00562 0.854 0.00
RETAIL_1_FLR_1 4933.90 4933.90 73.56 0.395 0.395 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 24.00 0.00886 40.80 0.00563 0.079 0.00
RETAIL_2_FLR_1 3554.25 3554.25 45.76 0.284 0.284 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 24.00 24.00 0.00922 37.61 0.00563 0.092 0.00
MECH_FLR_1 3786.74 3786.74 23.06 0.303 0.303 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 24.00 24.00 0.00852 36.61 0.00562 0.000 0.00
STORAGE_FLR_1 1879.12 1879.12 19.83 0.150 0.150 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 24.00 24.00 0.00858 38.05 0.00563 0.058 0.00
LAUNDRY_FLR_1 45546.09 45546.09 583.63 3.645 3.645 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 24.00 24.00 0.00853 40.13 0.00563 0.000 0.00
CAFE_FLR_1 19970.77 19970.77 105.74 1.600 1.600 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 23.99 0.01001 40.80 0.00563 0.676 0.00
LOBBY_FLR_1 65527.93 65527.93 50.09 5.246 5.246 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 23.99 0.00988 40.80 0.00563 1.894 0.00
ROOM_1_FLR_3 11424.24 11424.24 292.76 1.232 1.232 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 21.11 21.11 0.00848 39.12 0.00563 0.062 0.00
ROOM_2_FLR_3 11342.93 11342.93 290.71 1.223 1.223 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 21.11 21.11 0.00848 38.94 0.00563 0.062 0.00
ROOM_3_MULT19_FLR_3 62682.35 62682.35 2555.98 6.759 6.759 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 21.11 21.11 0.00842 40.80 0.00563 0.837 0.00
ROOM_4_MULT19_FLR_3 67673.90 67673.90 2758.76 7.298 7.298 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 21.11 21.11 0.00863 40.27 0.00563 0.837 0.00
ROOM_5_FLR_3 9980.68 9980.68 255.77 1.076 1.076 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 21.11 21.11 0.00847 36.74 0.00562 0.062 0.00
ROOM_6_FLR_3 9911.32 9911.32 254.02 1.069 1.069 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 21.11 21.11 0.00847 36.41 0.00562 0.062 0.00
CORRIDOR_FLR_3 21324.01 21324.01 54.76 1.707 1.707 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 24.00 24.00 0.00929 40.40 0.00563 0.475 0.00
ROOM_1_FLR_6 3033.62 3033.62 77.74 0.327 0.327 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 21.11 21.11 0.00848 39.12 0.00563 0.015 0.00
ROOM_2_FLR_6 3009.75 3009.75 77.14 0.325 0.325 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 21.11 21.11 0.00848 38.94 0.00563 0.015 0.00
ROOM_3_MULT9_FLR_6 13289.03 13289.03 541.73 1.433 1.433 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 21.11 21.11 0.00854 40.80 0.00563 0.099 0.00
BANQUET_FLR_6 31025.10 31025.10 93.55 2.486 2.486 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 23.98 0.01028 40.67 0.00563 1.188 0.00
DINING_FLR_6 32465.21 32465.21 97.89 2.601 2.601 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 23.98 0.01020 40.67 0.00563 1.188 0.00
KITCHEN_FLR_6 31265.19 31265.19 302.65 2.509 2.509 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 24.00 23.97 0.01002 39.60 0.00563 0.367 0.00
CORRIDOR_FLR_6 11110.06 11110.06 26.96 0.889 0.889 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 24.00 0.00888 40.80 0.00563 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 0.854   00:10:00 21.00 24.00 0.00849 0.50 0.00432 0.854 0.00
RETAIL_1_FLR_1 2532.51 2532.51 37.76 0.120 0.120 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00750 0.50 0.00432 0.079 0.00
RETAIL_2_FLR_1 871.43 871.43 11.22 0.041 0.092 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00745 0.50 0.00432 0.092 0.00
MECH_FLR_1 1664.27 1664.27 10.13 0.079 0.079 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00734 0.50 0.00432 0.000 0.00
STORAGE_FLR_1 968.20 968.20 10.22 0.046 0.058 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00735 0.50 0.00432 0.058 0.00
LAUNDRY_FLR_1 2235.00 2235.00 28.64 0.106 0.106 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00733 0.50 0.00432 0.000 0.00
CAFE_FLR_1 6264.85 6264.85 33.17 0.296 0.676 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00755 0.50 0.00432 0.676 0.00
LOBBY_FLR_1 15090.20 15090.20 11.54 0.712 1.894 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00747 0.50 0.00432 1.894 0.00
ROOM_1_FLR_3 5574.49 5574.49 142.86 0.265 0.265 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00748 0.50 0.00432 0.062 0.00
ROOM_2_FLR_3 5579.05 5579.05 142.99 0.265 0.265 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00748 0.50 0.00432 0.062 0.00
ROOM_3_MULT19_FLR_3 32042.15 32042.15 1306.57 1.522 1.522 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00751 0.50 0.00432 0.837 0.00
ROOM_4_MULT19_FLR_3 32146.22 32146.22 1310.46 1.527 1.527 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00752 0.50 0.00432 0.837 0.00
ROOM_5_FLR_3 5564.63 5564.63 142.60 0.264 0.264 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00748 0.50 0.00432 0.062 0.00
ROOM_6_FLR_3 5569.19 5569.19 142.74 0.264 0.264 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00748 0.50 0.00432 0.062 0.00
CORRIDOR_FLR_3 8955.58 8955.58 23.00 0.423 0.475 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00759 0.50 0.00432 0.475 0.00
ROOM_1_FLR_6 1686.91 1686.91 43.23 0.080 0.080 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00756 0.50 0.00432 0.015 0.00
ROOM_2_FLR_6 1687.45 1687.45 43.25 0.080 0.080 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00756 0.50 0.00432 0.015 0.00
ROOM_3_MULT9_FLR_6 8101.26 8101.26 330.25 0.385 0.385 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00757 0.50 0.00432 0.099 0.00
BANQUET_FLR_6 5576.86 5576.86 16.82 0.263 1.188 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00766 0.50 0.00432 1.188 0.00
DINING_FLR_6 5694.87 5694.87 17.17 0.269 1.188 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.00 21.00 0.00767 0.50 0.00432 1.188 0.00
KITCHEN_FLR_6 1778.28 1778.28 17.21 0.084 0.367 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 21.00 21.00 0.00647 0.50 0.00432 0.367 0.00
CORRIDOR_FLR_6 5819.14 5819.14 14.12 0.275 0.275 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.00 21.00 0.00771 0.50 0.00432 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 24.62 24.62 7.37 7.37 24.6237 11.7127 24.6237 0.4757 0.3000
FLR_3_DOAS 20.27 2.05 4.65 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 5983.048 5983.048 1.248186 0.00005234 124.766   12/21 00:10:00   12/21 00:10:00 5983.05 5983.05 1.248186 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00800000 46.9512 0.00 0.00 6016.67 6016.67
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 3105.021 3105.021 0.119564 0.00002716 84.739 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3105.02 3105.02 0.119564 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00750002 44.0536 2532.51 0.00 3120.42 3120.42
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1513.029 1513.029 0.133992 0.00001324 33.954 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1513.03 1513.03 0.133992 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00744822 43.7518 871.43 0.00 1521.22 1521.22
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 2099.480 2099.480 0.090908 0.00001837 54.921 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2099.48 2099.48 0.090908 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00734060 43.1271 1664.27 0.00 2110.02 2110.02
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1372.782 1372.782 0.084510 0.00001201 32.740 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1372.78 1372.78 0.084510 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00734509 43.1531 968.20 0.00 1380.07 1380.07
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 7469.371 7469.371 1.093495 0.00006535 159.278 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 7469.37 7469.37 1.093495 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00733159 43.0758 2235.00 0.00 7511.03 7511.03
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 10999.384 10999.384 0.988656 0.00009623 246.353 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 10999.38 10999.38 0.988656 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00754668 44.3240 6264.85 0.00 11058.95 11058.95
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 28354.992 28354.992 2.770104 0.00024806 628.476 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 28354.99 28354.99 2.770104 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00747428 43.9031 15090.20 0.00 28509.18 28509.18
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 12290.643 -999.000 1.231962 0.00043899 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 unknown 7/21 16:50:00 12290.64 12290.64 1.231962 21.74 14.59 0.00847827 12.80 11.21 0.00847827 39.12 0.00562848 18.06 0.0000 21.11 0.00847827 49.3821 11424.24 0.00 13524.54 13232.05
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 5574.352 5574.352 0.264724 0.00004877 159.301 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5574.35 5574.35 0.264724 21.11 13.48 0.00747915 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00747915 43.6342 5574.49 0.00 6009.28 6009.28
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 12203.158 -999.000 1.223193 0.00043586 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown 7/21 17:00:00 12203.16 12203.16 1.223193 21.74 14.59 0.00847803 12.80 11.21 0.00847803 38.94 0.00562821 18.00 0.0000 21.11 0.00847803 49.3807 11342.93 0.00 13428.32 13138.34
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 5578.911 5578.911 0.264940 0.00004881 159.431 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5578.91 5578.91 0.264940 21.11 13.48 0.00747955 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00747955 43.6366 5579.05 0.00 6014.19 6014.19
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 67429.052 -999.000 6.759412 0.00240836 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 unknown 7/21 14:30:00 67429.05 67429.05 6.759412 21.74 14.54 0.00841720 12.80 11.15 0.00841720 40.80 0.00563111 18.58 0.0000 21.11 0.00841720 49.0308 62682.35 0.00 74256.87 74256.87
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 32041.756 32041.756 1.521684 0.00028032 915.658 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 32041.76 32041.76 1.521684 21.11 13.51 0.00751429 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00751429 43.8357 32042.15 0.00 34541.96 34541.96
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 75441.697 -999.000 7.298255 0.00269455 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 unknown 7/21 15:40:00 75441.70 73394.59 7.298255 21.74 14.72 0.00862989 12.80 11.23 0.00850000 40.27 0.00563027 18.42 0.0000 21.11 0.00862989 50.2548 67673.90 0.00 82867.63 78375.83
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 32145.823 32145.823 1.526626 0.00028123 918.631 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 32145.82 32145.82 1.526626 21.11 13.51 0.00751554 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00751554 43.8429 32146.22 0.00 34654.15 34654.15
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 10737.518 -999.000 1.076290 0.00038351 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 unknown 7/21 10:30:00 10737.52 10737.52 1.076290 21.74 14.59 0.00847403 12.80 11.21 0.00847403 36.74 0.00562481 17.31 0.0000 21.11 0.00847403 49.3577 9980.68 0.00 11816.13 11567.50
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 5564.485 5564.485 0.264255 0.00004868 159.019 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5564.49 5564.49 0.264255 21.11 13.48 0.00747836 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00747836 43.6297 5564.63 0.00 5998.64 5998.64
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 10662.895 -999.000 1.068810 0.00038085 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 unknown 7/21 10:20:00 10662.90 10662.90 1.068810 21.74 14.59 0.00847374 12.80 11.21 0.00847374 36.41 0.00562429 17.20 0.0000 21.11 0.00847374 49.3560 9911.32 0.00 11734.05 11487.63
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 5569.047 5569.047 0.264472 0.00004872 159.149 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5569.05 5569.05 0.264472 21.11 13.48 0.00747876 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00747876 43.6320 5569.19 0.00 6003.56 6003.56
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 12282.384 12282.384 0.694574 0.00010745 298.397 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 12282.38 12282.38 0.694574 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00759153 44.5832 8955.58 0.00 12346.31 12346.31
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 3263.694 -999.000 0.327138 0.00011657 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 unknown 7/21 16:50:00 3263.69 3263.69 0.327138 21.74 14.59 0.00847948 12.80 11.21 0.00847948 39.12 0.00562848 18.06 0.0000 21.11 0.00847948 49.3890 3033.62 0.00 3591.29 3513.03
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 1686.869 1686.869 0.080109 0.00001476 48.204 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1686.87 1686.87 0.080109 21.11 13.55 0.00755879 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00755879 44.0933 1686.91 0.00 1818.48 1818.48
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 3238.007 -999.000 0.324563 0.00011565 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown 7/21 17:00:00 3238.01 3238.01 0.324563 21.74 14.59 0.00847924 12.80 11.21 0.00847924 38.94 0.00562821 18.00 0.0000 21.11 0.00847924 49.3877 3009.75 0.00 3563.04 3485.50
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 1687.407 1687.407 0.080134 0.00001476 48.220 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1687.41 1687.41 0.080134 21.11 13.55 0.00755894 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00755894 44.0942 1687.45 0.00 1819.06 1819.06
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 14455.001 -999.000 1.433110 0.00051629 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 unknown 7/21 14:30:00 14455.00 14333.13 1.433110 21.74 14.64 0.00853960 12.80 11.23 0.00850000 40.80 0.00563111 18.58 0.0000 21.11 0.00853960 49.7354 13289.03 0.00 15895.51 15357.23
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 8101.099 8101.099 0.384721 0.00007087 231.496 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 8101.10 8101.10 0.384721 21.11 13.57 0.00757486 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00757486 44.1855 8101.26 0.00 8733.19 8733.19
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 13889.131 13889.131 1.735282 0.00012151 300.092 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 13889.13 13889.13 1.735282 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00766179 44.9912 5576.86 0.00 13966.28 13966.28
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 14006.534 14006.534 1.735158 0.00012254 302.863 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 14006.53 14006.53 1.735158 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00766817 45.0283 5694.87 0.00 14084.32 14084.32
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 5373.310 5373.310 0.752634 0.00004701 114.975 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 5373.31 5373.31 0.752634 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00646765 38.0577 1778.28 0.00 5403.25 5403.25
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 7135.322 7135.322 0.274740 0.00006242 194.735 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 7135.32 7135.32 0.274740 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00771176 45.2809 5819.14 0.00 7170.71 7170.71
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 580553.633 -999.000 24.623749 0.02073603 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 580553.63 580553.63 24.623749 31.95 17.40 0.00770111 10.79 9.60 0.00770111 40.80 0.00563111 18.58 47.3586 23.99 0.00951785 46.4590 307475.36 0.00 619794.71 605025.79
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 131459.725 131459.725 7.387125 0.00115007 2306.644 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 131459.73 131459.73 7.387125 0.50 0.50 0.00431558 16.70 12.29 0.00800000 0.50 0.00431558 0.50 157.8620 21.56 0.00772561 43.8223 56823.14 0.00 128116.02 128116.02
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 65945.855 -999.000 2.051317 0.00235543 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 65945.86 65945.86 2.051317 40.80 18.58 0.00563111 11.84 7.85 0.00563111 40.80 0.00563111 18.58 99.9965 21.11 0.00852702 49.6629 187295.36 0.00 66000.58 66000.58
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 10951.444 10951.444 0.615395 0.00009581 192.158 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 10951.44 10951.44 0.615395 0.50 0.50 0.00431558 16.70 12.29 0.00800000 0.50 0.00431558 0.50 333.3216 21.11 0.00751518 43.8408 97951.35 0.00 10672.89 10672.89



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 5983.048 5983.048 1.248186 0.00005234 124.766 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 1.6570 1.690390   12/21 00:10:00 unknown unknown   12/21 00:10:00 Sensible 5983.05 5983.05 1.0000 1.36450977 1.248186 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.05233697 60.00 32.22 27.78 0.000 5983.05 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 46.9512 0.00 0.00 6016.67 6016.67 1.36450977 16.60 13.15 0.00800000 36934.7 20.92 14.82 0.00800000 41344.1
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 3105.021 3105.021 0.119564 0.00002716 84.739 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 0.8600 0.877262 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3105.02 3105.02 1.0000 0.13070618 0.119564 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.02716131 60.00 32.22 27.78 0.000 3105.02 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00750002 21.00 0.00750002 44.0536 2532.51 0.00 3120.42 3120.42 0.13070618 16.60 13.15 0.00800000 36934.7 40.01 21.19 0.00800000 60808.3
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1513.029 1513.029 0.133992 0.00001324 33.954 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 0.4190 0.427476 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1513.03 1513.03 1.0000 0.14647938 0.133992 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.01323529 60.00 32.22 27.78 0.000 1513.03 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00744822 21.00 0.00744822 43.7518 871.43 0.00 1521.22 1521.22 0.14647938 16.60 13.15 0.00800000 36934.7 26.78 16.94 0.00800000 47319.9
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 2099.480 2099.480 0.090908 0.00001837 54.921 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 0.5815 0.593166 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2099.48 2099.48 1.0000 0.09937956 0.090908 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.01836530 60.00 32.22 27.78 0.000 2099.48 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00734060 21.00 0.00734060 43.1271 1664.27 0.00 2110.02 2110.02 0.09937956 16.60 13.15 0.00800000 36934.7 37.42 20.41 0.00800000 58166.7
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1372.782 1372.782 0.084510 0.00001201 32.740 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 0.3802 0.387852 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1372.78 1372.78 1.0000 0.09238572 0.084510 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.01200847 60.00 32.22 27.78 0.000 1372.78 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00734509 21.00 0.00734509 43.1531 968.20 0.00 1380.07 1380.07 0.09238572 16.60 13.15 0.00800000 36934.7 31.25 18.45 0.00800000 51872.8
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 7469.371 7469.371 1.093495 0.00006535 159.278 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 2.0687 2.110321 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 7469.37 7469.37 1.0000 1.19540197 1.093495 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.06533865 60.00 32.22 27.78 0.000 7469.37 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00733159 21.00 0.00733159 43.0758 2235.00 0.00 7511.03 7511.03 1.19540197 16.60 13.15 0.00800000 36934.7 22.76 15.50 0.00800000 43218.0
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 10999.384 10999.384 0.988656 0.00009623 246.353 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 3.0463 3.107656 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 10999.38 10999.38 1.0000 1.08079343 0.988656 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.09621760 60.00 32.22 27.78 0.000 10999.38 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00754668 21.00 0.00754668 44.3240 6264.85 0.00 11058.95 11058.95 1.08079343 16.60 13.15 0.00800000 36934.7 26.63 16.89 0.00800000 47167.0
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 28354.992 28354.992 2.770104 0.00024806 628.476 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 7.8531 8.011136 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 28354.99 28354.99 1.0000 3.02826218 2.770104 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.24803654 60.00 32.22 27.78 0.000 28354.99 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00747428 21.00 0.00747428 43.9031 15090.20 0.00 28509.18 28509.18 3.02826218 16.60 13.15 0.00800000 36934.7 25.83 16.61 0.00800000 46349.1
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 12290.643 -999.000 1.231962 0.00043899 -999.000 -999.0000 1.00000 1.00000 1020.6007 1004.8586 1.0932 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.231962 1.34677333   4197.9300 999.8980 30.57897620 13.37 6.70 6.67 856217.24 1.4355 1.435432 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 unknown unknown unknown 7/21 16:50:00 Sensible 12290.64 12290.64 1.0000 1.34677333 1.231962 21.74 14.59 0.00847827 43393.3 12.80 11.21 0.00847827 34267.3 0.43894033 6.70 13.37 6.67 0.000 12290.64 39.12 0.00562848 18.06 0.00000000 0.0000 21.11 0.00847827 21.11 0.00847827 49.3821 11424.24 0.00 13524.54 13232.05 1.34677333 21.74 15.56 0.00847827 43393.3 12.12 11.71 0.00839221 33351.1
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 5574.352 5574.352 0.264724 0.00004877 159.301 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.231962 1.34677333   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 1.5439 1.574922 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5574.35 5574.35 1.0000 0.28939456 0.264724 21.11 13.48 0.00747915 40210.8 40.00 20.06 0.00800000 60796.0 0.04876189 60.00 32.22 27.78 0.000 5574.35 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00747915 21.11 0.00747915 43.6342 5574.49 0.00 6009.28 6009.28 0.28939456 16.60 12.64 0.00747915 35616.1 36.98 19.88 0.00747915 56381.0
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 12203.158 -999.000 1.223193 0.00043586 -999.000 -999.0000 1.00000 1.00000 1020.6002 1004.8586 1.0932 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.223193 1.33718740   4197.9300 999.8980 30.57897620 13.37 6.70 6.67 856217.24 1.4252 1.425214 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown unknown unknown 7/21 17:00:00 Sensible 12203.16 12203.16 1.0000 1.33718740 1.223193 21.74 14.59 0.00847803 43392.7 12.80 11.21 0.00847803 34266.7 0.43581592 6.70 13.37 6.67 0.000 12203.16 38.94 0.00562821 18.00 0.00000000 0.0000 21.11 0.00847803 21.11 0.00847803 49.3807 11342.93 0.00 13428.32 13138.34 1.33718740 21.74 15.56 0.00847803 43392.7 12.11 11.71 0.00839210 33350.5
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 5578.911 5578.911 0.264940 0.00004881 159.431 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.223193 1.33718740   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 1.5451 1.576210 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5578.91 5578.91 1.0000 0.28963122 0.264940 21.11 13.48 0.00747955 40211.8 40.00 20.06 0.00800000 60796.0 0.04880177 60.00 32.22 27.78 0.000 5578.91 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00747955 21.11 0.00747955 43.6366 5579.05 0.00 6014.19 6014.19 0.28963122 16.60 12.64 0.00747955 35617.1 36.98 19.88 0.00747955 56382.1
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 67429.052 -999.000 6.759412 0.00240836 -999.000 -999.0000 1.00000 1.00000 1020.4871 1004.8586 1.0932 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.759412 7.38935015   4197.9300 999.8980 30.57897620 13.37 6.70 6.67 856217.24 7.8752 7.875080 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 unknown unknown unknown 7/21 14:30:00 Sensible 67429.05 67429.05 1.0000 7.38935015 6.759412 21.74 14.54 0.00841720 43238.3 12.80 11.15 0.00841720 34113.1 2.40811886 6.70 13.37 6.67 0.000 67429.05 40.80 0.00563111 18.58 0.00000000 0.0000 21.11 0.00841720 21.11 0.00841720 49.0308 62682.35 0.00 74256.87 74256.87 7.38935015 21.74 15.50 0.00841720 43238.3 11.89 11.64 0.00841720 33189.1
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 32041.756 32041.756 1.521684 0.00028032 915.658 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.759412 7.38935015   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 8.8742 9.052758 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 32041.76 32041.76 1.0000 1.66349601 1.521684 21.11 13.51 0.00751429 40300.5 40.00 20.06 0.00800000 60796.0 0.28028666 60.00 32.22 27.78 0.000 32041.76 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00751429 21.11 0.00751429 43.8357 32042.15 0.00 34541.96 34541.96 1.66349601 16.60 12.68 0.00751429 35705.0 36.98 19.91 0.00751429 56469.7
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 75441.697 -999.000 7.298255 0.00269455 -999.000 -999.0000 1.00000 1.00000 1020.8825 1004.8586 1.0932 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 7.298255 7.97841033   4197.9300 999.8980 30.57897620 13.37 6.70 6.67 856217.24 8.8110 8.810882 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 unknown unknown unknown 7/21 15:40:00 Sensible 75441.70 73394.59 1.0000 7.97841033 7.298255 21.74 14.72 0.00862989 43777.9 12.80 11.23 0.00850000 34322.2 2.69427744 6.70 13.37 6.67 0.000 75441.70 40.27 0.00563027 18.42 0.00000000 0.0000 21.11 0.00862989 21.11 0.00862989 50.2548 67673.90 0.00 82867.63 78375.83 7.97841033 21.74 15.69 0.00862989 43777.9 12.12 11.72 0.00840679 33391.4
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 32145.823 32145.823 1.526626 0.00028123 918.631 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 7.298255 7.97841033   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 8.9030 9.082160 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 32145.82 32145.82 1.0000 1.66889878 1.526626 21.11 13.51 0.00751554 40303.7 40.00 20.06 0.00800000 60796.0 0.28119699 60.00 32.22 27.78 0.000 32145.82 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00751554 21.11 0.00751554 43.8429 32146.22 0.00 34654.15 34654.15 1.66889878 16.60 12.68 0.00751554 35708.2 36.98 19.91 0.00751554 56472.9
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 10737.518 -999.000 1.076290 0.00038351 -999.000 -999.0000 1.00000 1.00000 1020.5928 1004.8586 1.0932 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.076290 1.17659354   4197.9300 999.8980 30.57897620 13.37 6.70 6.67 856217.24 1.2541 1.254041 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 unknown unknown unknown 7/21 10:30:00 Sensible 10737.52 10737.52 1.0000 1.17659354 1.076290 21.74 14.59 0.00847403 43382.6 12.80 11.21 0.00847403 34256.6 0.38347299 6.70 13.37 6.67 0.000 10737.52 36.74 0.00562481 17.31 0.00000000 0.0000 21.11 0.00847403 21.11 0.00847403 49.3577 9980.68 0.00 11816.13 11567.50 1.17659354 21.74 15.55 0.00847403 43382.6 12.11 11.70 0.00839029 33339.9
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 5564.485 5564.485 0.264255 0.00004868 159.019 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.076290 1.17659354   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 1.5411 1.572134 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5564.49 5564.49 1.0000 0.28888231 0.264255 21.11 13.48 0.00747836 40208.8 40.00 20.06 0.00800000 60796.0 0.04867558 60.00 32.22 27.78 0.000 5564.49 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00747836 21.11 0.00747836 43.6297 5564.63 0.00 5998.64 5998.64 0.28888231 16.60 12.64 0.00747836 35614.0 36.98 19.88 0.00747836 56379.0
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 10662.895 -999.000 1.068810 0.00038085 -999.000 -999.0000 1.00000 1.00000 1020.5923 1004.8586 1.0932 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.068810 1.16841700   4197.9300 999.8980 30.57897620 13.37 6.70 6.67 856217.24 1.2453 1.245326 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 unknown unknown unknown 7/21 10:20:00 Sensible 10662.90 10662.90 1.0000 1.16841700 1.068810 21.74 14.59 0.00847374 43381.8 12.80 11.21 0.00847374 34255.9 0.38080795 6.70 13.37 6.67 0.000 10662.90 36.41 0.00562429 17.20 0.00000000 0.0000 21.11 0.00847374 21.11 0.00847374 49.3560 9911.32 0.00 11734.05 11487.63 1.16841700 21.74 15.55 0.00847374 43381.8 12.11 11.70 0.00839016 33339.1
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 5569.047 5569.047 0.264472 0.00004872 159.149 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.068810 1.16841700   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 1.5424 1.573423 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5569.05 5569.05 1.0000 0.28911910 0.264472 21.11 13.48 0.00747876 40209.8 40.00 20.06 0.00800000 60796.0 0.04871548 60.00 32.22 27.78 0.000 5569.05 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00747876 21.11 0.00747876 43.6320 5569.19 0.00 6003.56 6003.56 0.28911910 16.60 12.64 0.00747876 35615.1 36.98 19.88 0.00747876 56380.1
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 12282.384 12282.384 0.694574 0.00010745 298.397 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 3.4017 3.470142 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 12282.38 12282.38 1.0000 0.75930398 0.694574 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.10744069 60.00 32.22 27.78 0.000 12282.38 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00759153 21.00 0.00759153 44.5832 8955.58 0.00 12346.31 12346.31 0.75930398 16.60 13.15 0.00800000 36934.7 32.55 18.87 0.00800000 53194.8
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 3263.694 -999.000 0.327138 0.00011657 -999.000 -999.0000 1.00000 1.00000 1020.6029 1004.8586 1.0932 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.327138 0.35762556   4197.9300 999.8980 30.57897620 13.37 6.70 6.67 856217.24 0.3812 0.381169 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 unknown unknown unknown 7/21 16:50:00 Sensible 3263.69 3263.69 1.0000 0.35762556 0.327138 21.74 14.59 0.00847948 43396.4 12.80 11.21 0.00847948 34270.4 0.11655754 6.70 13.37 6.67 0.000 3263.69 39.12 0.00562848 18.06 0.00000000 0.0000 21.11 0.00847948 21.11 0.00847948 49.3890 3033.62 0.00 3591.29 3513.03 0.35762556 21.74 15.56 0.00847948 43396.4 12.12 11.71 0.00839275 33354.3
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 1686.869 1686.869 0.080109 0.00001476 48.204 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.327138 0.35762556   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 0.4672 0.476591 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1686.87 1686.87 1.0000 0.08757439 0.080109 21.11 13.55 0.00755879 40413.1 40.00 20.06 0.00800000 60796.0 0.01475596 60.00 32.22 27.78 0.000 1686.87 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00755879 21.11 0.00755879 44.0933 1686.91 0.00 1818.48 1818.48 0.08757439 16.60 12.72 0.00755879 35817.7 36.98 19.94 0.00755879 56582.7
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 3238.007 -999.000 0.324563 0.00011565 -999.000 -999.0000 1.00000 1.00000 1020.6025 1004.8586 1.0932 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.324563 0.35481094   4197.9300 999.8980 30.57897620 13.37 6.70 6.67 856217.24 0.3782 0.378169 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown unknown unknown 7/21 17:00:00 Sensible 3238.01 3238.01 1.0000 0.35481094 0.324563 21.74 14.59 0.00847924 43395.8 12.80 11.21 0.00847924 34269.8 0.11564015 6.70 13.37 6.67 0.000 3238.01 38.94 0.00562821 18.00 0.00000000 0.0000 21.11 0.00847924 21.11 0.00847924 49.3877 3009.75 0.00 3563.04 3485.50 0.35481094 21.74 15.56 0.00847924 43395.8 12.12 11.71 0.00839264 33353.7
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 1687.407 1687.407 0.080134 0.00001476 48.220 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.324563 0.35481094   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 0.4673 0.476743 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1687.41 1687.41 1.0000 0.08760232 0.080134 21.11 13.55 0.00755894 40413.5 40.00 20.06 0.00800000 60796.0 0.01476066 60.00 32.22 27.78 0.000 1687.41 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00755894 21.11 0.00755894 44.0942 1687.45 0.00 1819.06 1819.06 0.08760232 16.60 12.72 0.00755894 35818.1 36.98 19.94 0.00755894 56583.1
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 14455.001 -999.000 1.433110 0.00051629 -999.000 -999.0000 1.00000 1.00000 1020.7147 1004.8586 1.0932 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.433110 1.56666772   4197.9300 999.8980 30.57897620 13.37 6.70 6.67 856217.24 1.6882 1.688208 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 unknown unknown unknown 7/21 14:30:00 Sensible 14455.00 14333.13 1.0000 1.56666772 1.433110 21.74 14.64 0.00853960 43548.8 12.80 11.23 0.00850000 34322.2 0.51623682 6.70 13.37 6.67 0.000 14455.00 40.80 0.00563111 18.58 0.00000000 0.0000 21.11 0.00853960 21.11 0.00853960 49.7354 13289.03 0.00 15895.51 15357.23 1.56666772 21.74 15.61 0.00853960 43548.8 12.14 11.73 0.00840344 33402.7
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 8101.099 8101.099 0.384721 0.00007087 231.496 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.433110 1.56666772   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 2.2436 2.288804 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 8101.10 8101.10 1.0000 0.42057465 0.384721 21.11 13.57 0.00757486 40454.1 40.00 20.06 0.00800000 60796.0 0.07086472 60.00 32.22 27.78 0.000 8101.10 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00757486 21.11 0.00757486 44.1855 8101.26 0.00 8733.19 8733.19 0.42057465 16.60 12.74 0.00757486 35858.4 36.98 19.95 0.00757486 56623.2
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 13889.131 13889.131 1.735282 0.00012151 300.092 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 3.8467 3.924096 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 13889.13 13889.13 1.0000 1.89700072 1.735282 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.12149578 60.00 32.22 27.78 0.000 13889.13 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00766179 21.00 0.00766179 44.9912 5576.86 0.00 13966.28 13966.28 1.89700072 16.60 13.15 0.00800000 36934.7 23.82 15.89 0.00800000 44297.0
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 14006.534 14006.534 1.735158 0.00012254 302.863 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 3.8792 3.957266 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 14006.53 14006.53 1.0000 1.89686485 1.735158 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.12252277 60.00 32.22 27.78 0.000 14006.53 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00766817 21.00 0.00766817 45.0283 5694.87 0.00 14084.32 14084.32 1.89686485 16.60 13.15 0.00800000 36934.7 23.88 15.91 0.00800000 44359.8
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 5373.310 5373.310 0.752634 0.00004701 114.975 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 1.4882 1.518121 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 Sensible 5373.31 5373.31 1.0000 0.82277464 0.752634 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.04700326 60.00 32.22 27.78 0.000 5373.31 0.50 0.00431558 0.50 0.00000000 0.0000 20.42 0.00646765 21.00 0.00646765 38.0577 1778.28 0.00 5403.25 5403.25 0.82277464 16.60 13.15 0.00800000 36934.7 23.04 15.61 0.00800000 43501.8
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 7135.322 7135.322 0.274740 0.00006242 194.735 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 1.9762 2.015943 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 7135.32 7135.32 1.0000 0.30034434 0.274740 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.06241655 60.00 32.22 27.78 0.000 7135.32 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00771176 21.00 0.00771176 45.2809 5819.14 0.00 7170.71 7170.71 0.30034434 16.60 13.15 0.00800000 36934.7 40.01 21.19 0.00800000 60809.7
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 580553.633 -999.000 24.623749 0.02073603 -999.000 -999.0000 1.00000 1.00000 1019.1560 1004.8586 1.0932 VAV WITH REHEAT FAN Fan:VariableVolume 24.623749 26.91854002   4197.9300 999.8980 30.57897620 13.37 6.70 6.67 856217.24 67.8045 67.804478 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 Sensible 580553.63 580553.63 1.0000 26.91854002 24.623749 31.95 17.40 0.00770111 51822.6 10.79 9.60 0.00770111 30255.6 20.73391532 6.70 13.37 6.67 55172.923 525380.71 40.80 0.00563111 18.58 11.66146000 47.3586 23.99 0.00956338 23.99 0.00951785 46.4590 307475.36 0.00 619794.71 605025.79 26.91854002 31.95 18.44 0.00770111 51822.6 9.90 9.80 0.00748333 28797.8
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 131459.725 131459.725 7.387125 0.00115007 2306.644 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 VAV WITH REHEAT FAN Fan:VariableVolume 24.623749 26.91854002   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 36.4086 37.141317 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 131459.73 131459.73 1.0000 8.07556201 7.387125 0.50 0.50 0.00431558 11299.5 16.70 12.29 0.00800000 37036.7 1.14994970 60.00 32.22 27.78 0.000 131459.73 0.50 0.00431558 0.50 11.66146000 157.8620 18.53 0.00761824 21.56 0.00772561 43.8223 56823.14 0.00 128116.02 128116.02 8.07556201 2.80 2.38 0.00431558 13629.0 18.46 10.16 0.00431558 29493.7
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 65945.855 -999.000 2.051317 0.00235543 -999.000 -999.0000 1.00000 1.00000 1015.3079 1004.8586 1.0932 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.24240930   4197.9300 999.8980 30.57897620 13.37 6.70 6.67 856217.24 7.7020 7.702000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 Sensible 65945.86 65945.86 1.0000 2.24248814 2.051317 40.80 18.58 0.00563111 55507.6 11.84 7.85 0.00563111 26100.2 2.35519288 6.70 13.37 6.67 2195.006 63750.85 40.80 0.00563111 18.58 2.05124512 99.9965 21.11 0.00851626 21.11 0.00852702 49.6629 187295.36 0.00 66000.58 66000.58 2.24248814 40.80 19.66 0.00563111 55507.6 11.81 8.61 0.00563111 26075.8
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 10951.444 10951.444 0.615395 0.00009581 192.158 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.24240930   4197.9300 999.8980 3.09614682 54.44 82.22 27.78 361067.98 3.0331 3.094111 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 10951.44 10951.44 1.0000 0.67274644 0.615395 0.50 0.50 0.00431558 11299.5 16.70 12.29 0.00800000 37036.7 0.09579823 60.00 32.22 27.78 0.000 10951.44 0.50 0.00431558 0.50 2.05124512 333.3216 21.11 0.00751321 21.11 0.00751518 43.8408 97951.35 0.00 10672.89 10672.89 0.67274644 2.80 2.38 0.00431558 13629.0 18.46 10.16 0.00431558 29493.7



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 11.66 24.62 -      
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 2062.33 5632.33 513.50
RETAIL_1_FLR_1 3492.67 3685.67 601.33
RETAIL_2_FLR_1 2291.67 4981.33 635.00
MECH_FLR_1 1891.83 5647.17 126.17
STORAGE_FLR_1 1196.50 6750.67 250.50
LAUNDRY_FLR_1 8724.00 4256.67 4256.67
CAFE_FLR_1 3521.83 4638.33 928.83
LOBBY_FLR_1 2772.00 4526.17 945.67
ROOM_1_FLR_3 407.67 8101.00 301.00
ROOM_2_FLR_3 798.33 8227.83 732.67
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 675.50 8760.00 675.50
ROOM_5_FLR_3 411.83 7999.50 290.17
ROOM_6_FLR_3 707.50 8091.33 654.67
CORRIDOR_FLR_3 1843.33 6700.50 777.00
ROOM_1_FLR_6 966.00 7966.50 743.83
ROOM_2_FLR_6 1515.67 8102.00 1364.50
ROOM_3_MULT9_FLR_6 270.00 7956.00 183.33
BANQUET_FLR_6 3286.17 4551.67 942.83
DINING_FLR_6 4033.33 3471.67 927.50
KITCHEN_FLR_6 8748.50 6698.50 6698.50
CORRIDOR_FLR_6 2091.17 5308.83 498.50
Facility 8760.00 8760.00 7492.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 65.50 0.00 65.50
CAFE_FLR_1 0.00 0.17 0.00 0.17
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 12.67 0.00 12.67
ROOM_2_FLR_3 0.00 10.83 0.00 10.83
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 4.83 0.00 4.83
ROOM_5_FLR_3 0.00 8.00 0.00 8.00
ROOM_6_FLR_3 0.00 7.50 0.00 7.50
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 16.33 0.00 16.33
ROOM_2_FLR_6 0.00 15.00 0.00 15.00
ROOM_3_MULT9_FLR_6 0.00 19.17 0.00 19.17
BANQUET_FLR_6 0.00 2.33 0.00 2.33
DINING_FLR_6 0.00 4.67 0.00 4.67
KITCHEN_FLR_6 0.00 72.83 0.00 72.83
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 0.00 114.67 0.00 114.67
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.66 106.50 4826.41 1.001 0.000 0.000 0.000
RETAIL_1_FLR_1 6.27 10.83 265.76 2.043 0.241 0.000 0.000
RETAIL_2_FLR_1 7.26 12.54 307.76 1.505 0.080 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.568 0.090 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.712 0.089 0.000 0.000
LAUNDRY_FLR_1 4.86 8.40 309.22 19.767 0.258 0.000 0.000
CAFE_FLR_1 82.39 142.30 748.35 4.262 0.189 0.000 0.000
LOBBY_FLR_1 244.59 422.44 5183.56 1.824 0.078 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.474 0.310 0.000 0.052
ROOM_2_FLR_3 0.95 1.50 118.93 0.474 0.310 0.000 0.048
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.537 0.138 0.000 0.076
ROOM_5_FLR_3 0.95 1.50 118.94 0.474 0.310 0.000 0.052
ROOM_6_FLR_3 0.95 1.50 118.93 0.474 0.310 0.000 0.048
CORRIDOR_FLR_3 12.13 20.96 1186.91 0.514 0.038 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.474 0.310 0.000 0.060
ROOM_2_FLR_6 0.95 1.50 118.93 0.473 0.310 0.000 0.056
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.538 0.253 0.000 0.097
BANQUET_FLR_6 144.69 249.90 1010.89 5.585 0.090 0.000 0.000
DINING_FLR_6 144.69 249.90 1010.89 5.692 0.090 0.000 0.000
KITCHEN_FLR_6 12.88 22.24 314.87 20.878 0.259 0.000 0.000
CORRIDOR_FLR_6 12.84 22.18 1256.16 0.901 0.063 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.66 106.50 4826.41 0.528 0.000 0.000 0.000
RETAIL_1_FLR_1 6.27 10.83 265.76 0.836 0.004 0.000 0.000
RETAIL_2_FLR_1 7.26 12.54 307.76 0.846 0.001 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.262 0.002 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.420 0.002 0.000 0.000
LAUNDRY_FLR_1 4.86 8.40 309.22 7.268 0.004 0.000 0.000
CAFE_FLR_1 82.39 142.30 748.35 2.566 0.003 0.000 0.000
LOBBY_FLR_1 244.59 422.44 5183.56 1.092 0.001 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.464 0.005 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.463 0.005 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.526 0.002 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.464 0.005 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.464 0.005 0.000 0.000
CORRIDOR_FLR_3 12.13 20.96 1186.91 0.275 0.001 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.463 0.005 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.462 0.005 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.527 0.004 0.000 0.000
BANQUET_FLR_6 144.69 249.90 1010.89 3.499 0.002 0.000 0.000
DINING_FLR_6 144.69 249.90 1010.89 3.515 0.002 0.000 0.000
KITCHEN_FLR_6 12.88 22.24 314.87 4.918 0.004 0.000 0.000
CORRIDOR_FLR_6 12.84 22.18 1256.16 0.398 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.66 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.27 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.26 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.86 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.39 142.30 748.35 188.86 0.0000 0.676
LOBBY_FLR_1 VAV WITH REHEAT 244.59 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.13 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 144.69 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 144.69 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.88 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.84 22.18 1256.16 412.12 0.0000 0.126
Total Facility   871.60 1604.23 35184.81 11345.29 0.0000 137.584


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 41412831.81 0.00 41412831.81 0.00 41412831.81 26946214.98 225.67 42.37 8491.97 0.00
RETAIL_1_FLR_1 4658759.87 0.00 4658759.87 549390.10 5208149.96 2498216.28 33.77 5.34 8720.89 0.00
RETAIL_2_FLR_1 3972935.32 0.00 3972935.32 212065.27 4185000.59 2892943.94 38.38 21.19 8700.42 0.00
MECH_FLR_1 3174556.49 0.00 3174556.49 501196.32 3675752.81 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 2303930.01 0.00 2303930.01 289162.67 2593092.68 1821682.01 612.47 103.91 8043.62 0.00
LAUNDRY_FLR_1 52412269.56 0.00 52412269.56 684357.98 53096627.53 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 27376596.26 0.00 27376596.26 1214457.92 28591054.18 21330615.53 545.67 117.85 8096.48 0.00
LOBBY_FLR_1 81013259.30 0.00 81013259.30 3469983.66 84483242.97 59728886.00 31.51 20.29 8708.21 0.00
ROOM_1_FLR_3 1946875.62 53343.51 2000219.13 318881.11 2319100.24 1946875.62 0.00 7861.67 898.33 0.00
ROOM_2_FLR_3 1946647.51 49707.09 1996354.60 318856.78 2315211.38 1946647.51 0.00 7861.67 898.33 0.00
ROOM_3_MULT19_FLR_3 26397887.27 58650.10 26456537.38 88971.41 26545508.78 26397887.27 0.00 7878.67 881.33 8760.00
ROOM_4_MULT19_FLR_3 26405105.73 49478.33 26454584.06 88995.74 26543579.79 26405105.73 0.00 7909.23 850.77 0.00
ROOM_5_FLR_3 1946875.62 53497.32 2000372.94 318881.11 2319254.05 1946875.62 0.00 7861.67 898.33 0.00
ROOM_6_FLR_3 1946647.51 49886.96 1996534.47 318856.78 2315391.25 1946647.51 0.00 7861.67 898.33 0.00
CORRIDOR_FLR_3 20938661.23 0.00 20938661.23 385591.42 21324252.65 14972100.18 41.78 29.71 8688.51 0.00
ROOM_1_FLR_6 486718.90 62250.72 548969.62 318945.54 867915.16 486718.90 0.00 7861.67 898.33 0.00
ROOM_2_FLR_6 486661.88 57398.51 544060.39 318921.20 862981.59 486661.88 0.00 7861.67 898.33 0.00
ROOM_3_MULT9_FLR_6 3126920.42 62501.31 3189421.72 163183.70 3352605.42 3126920.42 0.00 7861.67 898.33 0.00
BANQUET_FLR_6 48439238.95 0.00 48439238.95 778784.84 49218023.79 37458366.31 271.85 131.89 8356.26 0.00
DINING_FLR_6 49322937.47 0.00 49322937.47 778784.84 50101722.31 37458366.31 72.16 66.89 8620.95 0.00
KITCHEN_FLR_6 56268582.80 0.00 56268582.80 697192.99 56965775.79 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 9702845.92 0.00 9702845.92 682373.60 10385219.51 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.45E+10 9725661.32 0.45E+10 32134041.92 0.46E+10 0.43E+10 763.38 7924.11 8760.00 8760.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.3132 0.0000 1.3132 0.0000 1.3132 0.8545 225.67 42.37 8491.97
RETAIL_1_FLR_1 0.1477 0.0000 0.1477 0.0174 0.1651 0.0792 33.77 5.34 8720.89
RETAIL_2_FLR_1 0.1260 0.0000 0.1260 0.0067 0.1327 0.0917 38.38 21.19 8700.42
MECH_FLR_1 0.1007 0.0000 0.1007 0.0159 0.1166 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0731 0.0000 0.0731 0.0092 0.0822 0.0578 612.47 103.91 8043.62
LAUNDRY_FLR_1 1.6620 0.0000 1.6620 0.0217 1.6837 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.8681 0.0000 0.8681 0.0385 0.9066 0.6764 545.67 117.85 8096.48
LOBBY_FLR_1 2.5689 0.0000 2.5689 0.1100 2.6789 1.8940 31.51 20.29 8708.21
ROOM_1_FLR_3 0.0617 0.0017 0.0634 0.0101 0.0735 0.0617 0.00 7861.67 898.33
ROOM_2_FLR_3 0.0617 0.0016 0.0633 0.0101 0.0734 0.0617 0.00 7861.67 898.33
ROOM_4_MULT19_FLR_3 0.8373 0.0016 0.8389 0.0028 0.8417 0.8373 0.00 7909.23 850.77
ROOM_5_FLR_3 0.0617 0.0017 0.0634 0.0101 0.0735 0.0617 0.00 7861.67 898.33
ROOM_6_FLR_3 0.0617 0.0016 0.0633 0.0101 0.0734 0.0617 0.00 7861.67 898.33
CORRIDOR_FLR_3 0.6640 0.0000 0.6640 0.0122 0.6762 0.4748 41.78 29.71 8688.51
ROOM_1_FLR_6 0.0154 0.0020 0.0174 0.0101 0.0275 0.0154 0.00 7861.67 898.33
ROOM_2_FLR_6 0.0154 0.0018 0.0173 0.0101 0.0274 0.0154 0.00 7861.67 898.33
ROOM_3_MULT9_FLR_6 0.0992 0.0020 0.1011 0.0052 0.1063 0.0992 0.00 7861.67 898.33
BANQUET_FLR_6 1.5360 0.0000 1.5360 0.0247 1.5607 1.1878 271.85 131.89 8356.26
DINING_FLR_6 1.5640 0.0000 1.5640 0.0247 1.5887 1.1878 72.16 66.89 8620.95
KITCHEN_FLR_6 1.7843 0.0000 1.7843 0.0221 1.8064 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.3077 0.0000 0.3077 0.0216 0.3293 0.1256 0.00 0.00 8760.00
Total Facility 80.2532 0.1671 80.4203 0.8045 81.2248 73.9670 763.38 7924.11 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.48E+09 0.00 0.48E+09 0.22E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 77309717.76 496713.84 77806431.61 64690340.46 0.00 0.00 8760.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 15.1966 0.0000 15.1966 6.9969 0.00 0.00 8760.00
FLR_3_DOAS 2.4515 0.0158 2.4672 2.0513 0.00 0.00 8760.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 5137.98 3622.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLR_3_DOAS 0.00 6701.63 2058.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 13.9390 16.9844 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 2.4517 2.4519 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1318
Defaulted Fields 1181
Fields with Defaults 4005
Autosized Fields 350
Autosizable Fields 402
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 6602.02 75104.82 13-JAN-03:00 463845.66 21-JUL-20:00
Electricity:Building 2519.24 32804.76 02-JAN-02:10 151906.32 02-JAN-20:10
Electricity:Zone:BASEMENT 323.72 3705.45 02-JAN-02:10 24299.15 02-JAN-20:10
Electricity:SpaceType:GENERAL 2512.15 32663.61 02-JAN-02:10 151664.99 02-JAN-20:10
InteriorLights:Electricity 767.13 6971.81 02-JAN-02:10 62892.57 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 173.46 1576.23 02-JAN-02:10 14185.34 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 767.13 6971.81 02-JAN-02:10 62892.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity 767.13 6971.81 02-JAN-02:10 62892.57 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 173.46 1576.23 02-JAN-02:10 14185.34 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 767.13 6971.81 02-JAN-02:10 62892.57 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 18.80 222.61 02-JAN-02:10 1390.02 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.61 78.27 02-JAN-02:10 704.41 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.61 78.27 02-JAN-02:10 704.41 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 21.77 257.78 02-JAN-02:10 1609.65 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.97 90.64 02-JAN-02:10 815.72 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.97 90.64 02-JAN-02:10 815.72 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 29.11 327.88 02-JAN-02:10 2199.84 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 16.64 151.16 02-JAN-02:10 1360.40 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 16.64 151.16 02-JAN-02:10 1360.40 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 6.38 76.28 02-JAN-02:10 469.87 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.78 25.30 02-JAN-02:10 227.72 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 2.78 25.30 02-JAN-02:10 227.72 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 72.30 1002.39 02-JAN-02:10 4930.01 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.37 39.69 02-JAN-02:10 357.21 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.37 39.69 02-JAN-02:10 357.21 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 32.36 398.98 02-JAN-02:10 2727.18 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 18.02 195.77 02-JAN-02:10 1761.91 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 18.02 195.77 02-JAN-02:10 1761.91 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 270.97 3251.99 02-JAN-02:10 20294.39 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 121.98 1140.58 02-JAN-02:10 10265.18 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 121.98 1140.58 02-JAN-02:10 10265.18 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 18.66 264.62 01-JAN-02:10 1227.54 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 18.66 264.59 01-JAN-02:10 1227.39 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 304.77 4565.05 01-JAN-02:10 20923.25 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 76.02 643.59 01-JAN-02:10 5851.22 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 76.02 643.59 01-JAN-02:10 5851.22 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 304.86 4566.30 01-JAN-02:10 20928.98 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 76.04 643.77 01-JAN-02:10 5852.82 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 76.04 643.77 01-JAN-02:10 5852.82 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 18.66 264.62 01-JAN-02:10 1227.54 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 6.37 53.90 01-JAN-02:10 490.02 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 18.66 264.59 01-JAN-02:10 1227.39 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 6.37 53.89 01-JAN-02:10 489.96 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 109.60 995.90 02-JAN-02:10 8963.13 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 4.66 66.15 01-JAN-02:10 306.88 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.59 13.47 01-JAN-02:10 122.50 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.59 13.47 01-JAN-02:10 122.50 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 4.66 66.15 01-JAN-02:10 306.85 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.59 13.47 01-JAN-02:10 122.49 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.59 13.47 01-JAN-02:10 122.49 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 36.10 540.75 01-JAN-02:10 2478.43 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 9.00 76.24 01-JAN-02:10 693.10 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 9.00 76.24 01-JAN-02:10 693.10 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 210.69 2593.08 02-JAN-02:10 9841.96 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 34.83 343.78 02-JAN-02:10 3094.06 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 34.83 343.78 02-JAN-02:10 3094.06 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 210.69 2593.08 02-JAN-02:10 9841.96 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 34.83 343.78 02-JAN-02:10 3094.06 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 34.83 343.78 02-JAN-02:10 3094.06 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 454.16 6253.02 02-JAN-02:10 18944.06 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.33 121.09 02-JAN-02:10 1089.83 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.33 121.09 02-JAN-02:10 1089.83 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 29.00 263.50 02-JAN-02:10 2371.52 02-JAN-20:10
InteriorEquipment:Electricity 1745.01 25691.80 02-JAN-02:10 89475.41 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1745.01 25691.80 02-JAN-02:10 89475.41 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 433.74 5990.78 01-JAN-00:10 16487.34 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 8.99 285.00 01-JAN-00:10 285.00 01-JAN-00:10
Refrigeration:Electricity 61.81 1114.46 10-APR-22:30 3355.50 03-FEB-07:30
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 2336.59 2611.09 13-OCT-02:00 233680.48 28-JUN-18:10
LowTempRefrigeration:Refrigeration:Electricity 20.50 0.00 01-JAN-11:10 1982.94 03-MAR-07:00
MedTempRefrigeration:Refrigeration:Electricity 34.21 985.03 18-DEC-24:00 1228.30 18-NOV-07:10
Fans:Electricity 660.66 12024.80 04-NOV-02:10 53347.46 08-SEP-21:20
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 884.19 12841.22 10-FEB-04:00 64491.44 08-SEP-21:20
ExteriorEquipment:Electricity 651.48 9618.58 02-JAN-02:20 39726.11 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 32.45 553.78 05-JAN-04:10 1868.65 02-JAN-21:10
ElectricityPurchased:Facility 6602.02 75104.82 13-JAN-03:00 463845.66 21-JUL-20:00
ElectricityPurchased:Plant 6602.02 75104.82 13-JAN-03:00 463845.66 21-JUL-20:00
Cogeneration:ElectricityPurchased 6602.02 75104.82 13-JAN-03:00 463845.66 21-JUL-20:00
General:Cogeneration:ElectricityPurchased 6602.02 75104.82 13-JAN-03:00 463845.66 21-JUL-20:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 6602.02 75104.82 13-JAN-03:00 463845.66 21-JUL-20:00
ElectricityNet:Plant 6602.02 75104.82 13-JAN-03:00 463845.66 21-JUL-20:00
Cogeneration:ElectricityNet 6602.02 75104.82 13-JAN-03:00 463845.66 21-JUL-20:00
General:Cogeneration:ElectricityNet 6602.02 75104.82 13-JAN-03:00 463845.66 21-JUL-20:00
General:Fans:Electricity 660.66 12024.80 04-NOV-02:10 53347.46 08-SEP-21:20
ExteriorLights:Electricity 242.97 0.00 01-JAN-07:30 15448.40 01-JAN-00:10
General:ExteriorLights:Electricity 242.97 0.00 01-JAN-07:30 15448.40 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.91 18.80 01-JAN-00:10 188.00 01-JAN-07:10
HeatRecovery:Electricity 191.08 0.00 01-JAN-14:30 9938.94 11-JAN-02:40
General:HeatRecovery:Electricity 191.08 0.00 01-JAN-14:30 9938.94 11-JAN-02:40
WaterSystems:Electricity 90.74 1086.55 20-NOV-04:00 4738.76 12-OCT-18:10
Water Heater:WaterSystems:Electricity 90.74 1086.55 20-NOV-04:00 4738.76 12-OCT-18:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 1978.53 0.00 01-JAN-00:40 217591.64 28-JUN-18:10
General:Cooling:Electricity 1978.53 0.00 01-JAN-00:40 217591.64 28-JUN-18:10
Pumps:Electricity 212.61 47.91 09-JAN-08:10 9630.15 28-JUN-18:50
General:Pumps:Electricity 212.61 47.91 09-JAN-08:10 9630.15 28-JUN-18:50
WIRED_LTG_ELECTRICITY 27.00 0.00 01-JAN-00:10 2213.82 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 4643.03 29270.80 11-MAR-02:10 428064.21 16-DEC-22:10
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 2854.19 15908.90 04-APR-10:10 373799.96 16-DEC-22:10
WaterSystems:NaturalGas 2671.65 15908.90 01-JAN-00:10 245388.03 25-JAN-21:20
Water Heater:WaterSystems:NaturalGas 2671.65 15908.90 01-JAN-00:10 245388.03 25-JAN-21:20
Heating:NaturalGas 182.54 0.00 02-JAN-19:20 176232.64 02-FEB-03:40
Boiler:Heating:NaturalGas 182.54 0.00 02-JAN-19:20 176232.64 02-FEB-03:40


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 5748.46 0.00 01-JAN-00:40 655993.18 10-SEP-20:40
PlantLoopCoolingDemand:HVAC 5748.46 0.00 01-JAN-00:40 655993.18 10-SEP-20:40
CoolingCoils:PlantLoopCoolingDemand 5748.46 0.00 01-JAN-00:40 655993.18 10-SEP-20:40


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 04-DEC-21:40
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 04-DEC-21:40
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 04-DEC-21:40
Water Heater:WaterSystems:Water 5742.51 0.00 10-JAN-02:20 0.00 02-JAN-19:10
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 04-DEC-21:40
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 04-DEC-21:40
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 04-DEC-21:40
Water Heater:WaterSystems:MainsWater 5742.51 0.00 10-JAN-02:20 0.00 02-JAN-19:10
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 02-JAN-07:20
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 02-JAN-07:20


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 28038.16 132816.47 12-FEB-15:30 2489956.66 10-SEP-20:40
EnergyTransfer:Building 6311.36 74123.34 05-DEC-09:20 403977.11 20-JUL-18:20
EnergyTransfer:Zone:KITCHEN_FLR_6 744.68 8824.40 11-JAN-04:00 36748.58 13-AUG-10:40
Refrigeration:EnergyTransfer 182.18 4015.04 26-MAR-22:10 10423.34 07-MAR-08:10
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 91.09 2007.52 26-MAR-22:10 5211.67 07-MAR-08:10
General:Refrigeration:EnergyTransfer 91.09 2007.52 26-MAR-22:10 5211.67 07-MAR-08:10
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 91.09 2007.52 26-MAR-22:10 5211.67 07-MAR-08:10
EnergyTransfer:Plant 14645.18 12632.81 28-OCT-02:50 1509533.65 10-SEP-20:40
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.57 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 69.52 1905.09 18-DEC-24:00 2634.89 18-NOV-07:10
EnergyTransfer:Zone:BASEMENT 463.29 4742.87 30-MAR-07:20 27111.66 08-SEP-21:00
Heating:EnergyTransfer 23.00 0.00 01-JAN-08:10 31734.95 07-DEC-06:00
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 212.81 25-MAR-03:40
General:Heating:EnergyTransfer 23.00 0.00 01-JAN-08:10 31734.95 07-DEC-06:00
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 212.81 25-MAR-03:40
Cooling:EnergyTransfer 6197.27 60617.03 05-DEC-09:20 401102.36 27-JUN-18:20
Cooling:EnergyTransfer:Zone:BASEMENT 463.29 4742.87 30-MAR-07:20 27111.66 08-SEP-21:00
General:Cooling:EnergyTransfer 6197.27 60617.03 05-DEC-09:20 401102.36 27-JUN-18:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 463.29 4742.87 30-MAR-07:20 27111.66 08-SEP-21:00
EnergyTransfer:Zone:RETAIL_1_FLR_1 52.66 2.82 27-MAR-04:00 4131.85 28-SEP-13:30
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.03 0.00 01-JAN-00:10 302.22 16-DEC-07:20
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.03 0.00 01-JAN-00:10 302.22 16-DEC-07:20
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 52.63 0.00 13-FEB-07:10 4131.85 28-SEP-13:30
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 52.63 0.00 13-FEB-07:10 4131.85 28-SEP-13:30
EnergyTransfer:Zone:RETAIL_2_FLR_1 43.66 203.89 05-DEC-09:20 2769.78 28-JUN-20:10
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 67.49 13-FEB-05:50
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 67.49 13-FEB-05:50
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 43.65 203.89 05-DEC-09:20 2769.78 28-JUN-20:10
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 43.65 203.89 05-DEC-09:20 2769.78 28-JUN-20:10
EnergyTransfer:Zone:MECH_FLR_1 35.52 56.37 05-DEC-09:20 3125.15 28-JUN-20:00
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.01 0.00 01-JAN-00:10 117.89 21-DEC-05:20
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.01 0.00 01-JAN-00:10 117.89 21-DEC-05:20
Cooling:EnergyTransfer:Zone:MECH_FLR_1 35.51 56.37 05-DEC-09:20 3125.15 28-JUN-20:00
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 35.51 56.37 05-DEC-09:20 3125.15 28-JUN-20:00
EnergyTransfer:Zone:STORAGE_FLR_1 21.58 0.30 07-DEC-06:10 1356.10 28-JUN-19:10
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.02 0.00 01-JAN-00:10 129.46 21-DEC-05:20
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.02 0.00 01-JAN-00:10 129.46 21-DEC-05:20
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 21.56 0.00 07-DEC-04:10 1356.10 28-JUN-19:10
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 21.56 0.00 07-DEC-04:10 1356.10 28-JUN-19:10
EnergyTransfer:Zone:LAUNDRY_FLR_1 610.54 6446.76 04-NOV-04:30 40402.89 28-JUN-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 610.54 6446.76 04-NOV-04:30 40402.89 28-JUN-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 610.54 6446.76 04-NOV-04:30 40402.89 28-JUN-20:00
EnergyTransfer:Zone:CAFE_FLR_1 281.63 1256.13 05-DEC-09:20 14242.59 01-NOV-15:10
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.04 0.00 01-JAN-00:10 535.78 27-DEC-07:10
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.04 0.00 01-JAN-00:10 535.78 27-DEC-07:10
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 281.59 1256.13 05-DEC-09:20 14242.59 01-NOV-15:10
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 281.59 1256.13 05-DEC-09:20 14242.59 01-NOV-15:10
EnergyTransfer:Zone:LOBBY_FLR_1 889.57 5269.04 05-DEC-09:20 48445.70 28-JUN-20:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.01 0.00 01-JAN-00:10 474.48 17-DEC-08:40
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.01 0.00 01-JAN-00:10 474.48 17-DEC-08:40
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 889.56 5269.04 05-DEC-09:20 48445.70 28-JUN-20:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 889.56 5269.04 05-DEC-09:20 48445.70 28-JUN-20:10
EnergyTransfer:Zone:ROOM_1_FLR_3 96.74 0.08 25-DEC-04:10 13273.33 27-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 2.18 0.00 01-JAN-08:10 2876.95 07-DEC-06:00
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 2.18 0.00 01-JAN-08:10 2876.95 07-DEC-06:00
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 94.56 0.00 01-JAN-00:10 13273.33 27-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 94.56 0.00 01-JAN-00:10 13273.33 27-JUN-18:10
EnergyTransfer:Zone:ROOM_2_FLR_3 87.45 0.18 12-MAR-01:50 13529.49 27-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 4.29 0.00 01-JAN-08:10 4449.35 07-DEC-09:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 4.29 0.00 01-JAN-08:10 4449.35 07-DEC-09:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 83.15 0.00 01-JAN-00:10 13529.49 27-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 83.15 0.00 01-JAN-00:10 13529.49 27-JUN-18:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 629.75 4009.67 13-FEB-06:00 55371.54 20-NOV-14:30
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 629.75 4009.67 13-FEB-06:00 55371.54 20-NOV-14:30
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 629.75 4009.67 13-FEB-06:00 55371.54 20-NOV-14:30
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 598.46 3.29 20-DEC-06:20 79312.54 27-JUN-18:30
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 5.19 0.00 01-JAN-08:10 24775.66 07-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 5.19 0.00 01-JAN-08:10 24775.66 07-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 593.27 0.00 01-JAN-00:10 79312.54 27-JUN-18:30
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 593.27 0.00 01-JAN-00:10 79312.54 27-JUN-18:30
EnergyTransfer:Zone:ROOM_5_FLR_3 99.57 0.03 25-JAN-04:30 10794.82 27-AUG-15:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 2.17 0.00 01-JAN-08:10 2902.12 07-DEC-06:00
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 2.17 0.00 01-JAN-08:10 2902.12 07-DEC-06:00
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 97.40 0.00 01-JAN-00:10 10794.82 27-AUG-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 97.40 0.00 01-JAN-00:10 10794.82 27-AUG-15:10
EnergyTransfer:Zone:ROOM_6_FLR_3 89.71 0.04 17-JAN-07:00 10889.36 19-JUN-08:10
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 4.04 0.00 01-JAN-08:10 3593.66 07-DEC-06:00
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 4.04 0.00 01-JAN-08:10 3593.66 07-DEC-06:00
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 85.67 0.00 01-JAN-00:10 10889.36 19-JUN-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 85.67 0.00 01-JAN-00:10 10889.36 19-JUN-08:10
EnergyTransfer:Zone:CORRIDOR_FLR_3 228.89 720.06 05-DEC-09:20 16638.36 28-JUN-19:10
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.07 0.00 01-JAN-00:10 756.21 21-DEC-05:20
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.07 0.00 01-JAN-00:10 756.21 21-DEC-05:20
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 228.82 720.06 05-DEC-09:20 16638.36 28-JUN-19:10
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 228.82 720.06 05-DEC-09:20 16638.36 28-JUN-19:10
EnergyTransfer:Zone:ROOM_1_FLR_6 24.59 0.00 12-MAR-09:00 3560.97 27-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 1.35 0.00 01-JAN-08:10 1066.64 07-DEC-09:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 1.35 0.00 01-JAN-08:10 1066.64 07-DEC-09:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 23.24 0.00 01-JAN-00:10 3560.97 27-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 23.24 0.00 01-JAN-00:10 3560.97 27-JUN-18:10
EnergyTransfer:Zone:ROOM_2_FLR_6 22.82 0.00 27-DEC-21:20 3625.50 27-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 2.28 0.00 01-JAN-08:10 1268.98 07-DEC-09:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 2.28 0.00 01-JAN-08:10 1268.98 07-DEC-09:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 20.54 0.00 01-JAN-00:10 3625.50 27-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 20.54 0.00 01-JAN-00:10 3625.50 27-JUN-18:10
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 142.61 0.06 18-DEC-08:00 16978.72 28-SEP-15:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 1.29 0.00 01-JAN-00:10 3216.34 27-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 1.29 0.00 01-JAN-00:10 3216.34 27-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 141.32 0.00 01-JAN-00:40 16978.72 28-SEP-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 141.32 0.00 01-JAN-00:40 16978.72 28-SEP-15:10
EnergyTransfer:Zone:BANQUET_FLR_6 506.41 3167.25 05-DEC-09:20 24844.64 28-JUN-21:20
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.01 0.00 01-JAN-00:10 343.18 10-DEC-05:30
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.01 0.00 01-JAN-00:10 343.18 10-DEC-05:30
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 506.40 3167.25 05-DEC-09:20 24844.64 28-JUN-21:20
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 506.40 3167.25 05-DEC-09:20 24844.64 28-JUN-21:20
EnergyTransfer:Zone:DINING_FLR_6 530.74 3962.00 05-DEC-09:20 26255.11 28-JUN-21:20
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 229.59 22-JAN-05:30
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 229.59 22-JAN-05:30
Cooling:EnergyTransfer:Zone:DINING_FLR_6 530.74 3962.00 05-DEC-09:20 26255.11 28-JUN-21:20
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 530.74 3962.00 05-DEC-09:20 26255.11 28-JUN-21:20
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 653.59 6061.89 21-DEC-05:20 31667.48 18-JUN-10:50
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 653.59 6061.89 21-DEC-05:20 31667.48 18-JUN-10:50
EnergyTransfer:Zone:CORRIDOR_FLR_6 110.50 9.08 07-DEC-06:10 8515.40 28-JUN-18:20
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.04 0.00 01-JAN-00:10 352.59 21-DEC-05:20
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.04 0.00 01-JAN-00:10 352.59 21-DEC-05:20
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 110.47 0.00 07-DEC-06:10 8515.40 28-JUN-18:20
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 110.47 0.00 07-DEC-06:10 8515.40 28-JUN-18:20
PlantLoopHeatingDemand:Facility 711.01 6300.23 26-JUL-03:00 162800.77 18-DEC-07:40
PlantLoopHeatingDemand:Plant 584.54 6300.23 26-JUL-03:00 46116.65 24-JAN-07:40
WaterSystems:PlantLoopHeatingDemand 584.54 6300.23 26-JUL-03:00 46116.65 24-JAN-07:40
General:WaterSystems:PlantLoopHeatingDemand 584.54 6300.23 26-JUL-03:00 46116.65 24-JAN-07:40
EnergyTransfer:HVAC 7081.61 90.02 24-MAR-14:50 759723.84 13-JUL-18:10
HeatingCoils:EnergyTransfer 126.47 0.00 02-JAN-19:20 123415.51 19-DEC-03:10
PlantLoopHeatingDemand:HVAC 126.47 0.00 02-JAN-19:20 123415.51 19-DEC-03:10
HeatingCoils:PlantLoopHeatingDemand 126.47 0.00 02-JAN-19:20 123415.51 19-DEC-03:10
CoolingCoils:EnergyTransfer 5748.46 0.00 01-JAN-00:40 655993.18 10-SEP-20:40
HeatRecoveryForHeating:EnergyTransfer 550.38 0.00 01-JAN-14:30 305360.76 07-DEC-05:00
HeatRecoveryForCooling:EnergyTransfer 656.30 0.00 01-JAN-00:10 206437.66 17-JUN-16:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 584.54 6300.23 26-JUL-03:00 46116.65 24-JAN-07:40
WaterUse:WaterSystems:EnergyTransfer 584.54 6300.23 26-JUL-03:00 46116.65 24-JAN-07:40
Boilers:EnergyTransfer 124.92 0.00 02-JAN-19:20 122507.04 19-DEC-03:10
Chillers:EnergyTransfer 5933.05 0.00 01-JAN-00:40 663077.76 10-SEP-20:40
HeatRejection:EnergyTransfer 7911.58 0.00 01-JAN-00:40 822951.02 10-SEP-20:40
General:HeatRejection:EnergyTransfer 7911.58 0.00 01-JAN-00:40 822951.02 10-SEP-20:40



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -463.289 0.000 0.000 135.321 173.462 150.255 0.000 0.000 0.000 4.250 0.000 0.000 0.000 0.000 -0.000
RETAIL_1_FLR_1 0.000 0.000 0.027 -52.630 0.000 0.000 14.152 8.614 10.186 25.974 0.000 1.598 2.486 0.000 -7.585 0.000 -2.820 -0.000
RETAIL_2_FLR_1 0.000 0.000 0.003 -43.654 0.000 0.000 16.171 9.975 11.795 0.000 0.000 0.634 6.193 0.000 0.000 0.000 -1.118 -0.000
MECH_FLR_1 0.000 0.000 0.012 -35.510 0.000 0.000 3.478 16.635 12.471 0.000 0.000 1.483 3.936 0.000 0.000 0.000 -2.504 -0.001
STORAGE_FLR_1 0.000 0.000 0.020 -21.564 0.000 0.000 2.794 2.785 3.598 0.000 0.000 0.925 12.718 0.000 0.000 0.000 -1.275 0.000
LAUNDRY_FLR_1 0.000 0.000 0.000 -610.543 0.000 0.000 10.570 4.368 658.131 0.000 0.000 1.989 0.000 0.000 0.000 0.000 -3.926 -60.589
CAFE_FLR_1 0.000 0.000 0.035 -281.592 0.000 0.000 187.847 18.015 14.341 73.873 0.000 3.833 10.960 0.000 -21.233 0.000 -6.080 -0.000
LOBBY_FLR_1 0.000 0.000 0.008 -889.570 0.000 0.000 541.365 121.976 148.998 97.636 0.000 10.504 16.741 0.000 -28.973 0.000 -18.684 -0.003
ROOM_1_FLR_3 3.650 -79.156 0.000 -16.874 0.000 0.000 9.658 6.366 12.292 57.601 0.000 5.101 21.960 0.000 -14.680 0.000 -5.918 -0.001
ROOM_2_FLR_3 6.494 -68.729 0.000 -16.626 0.000 0.000 9.684 6.366 12.291 45.036 0.000 5.122 21.043 0.000 -14.947 0.000 -5.733 -0.001
ROOM_3_MULT19_FLR_3 0.000 -356.791 0.000 -272.960 0.000 0.000 0.000 76.021 228.754 325.177 0.000 21.682 123.466 0.000 -90.670 0.000 -54.680 -0.007
ROOM_4_MULT19_FLR_3 19.499 -385.220 0.000 -222.357 0.000 0.000 184.505 76.042 228.817 142.107 0.000 28.811 43.056 0.000 -78.024 0.000 -37.233 -0.014
ROOM_5_FLR_3 3.602 -81.863 0.000 -16.976 0.000 0.000 9.646 6.366 12.292 59.317 0.000 5.089 22.510 0.000 -13.992 0.000 -5.992 -0.002
ROOM_6_FLR_3 6.077 -70.971 0.000 -16.732 0.000 0.000 9.674 6.366 12.291 46.209 0.000 5.106 21.511 0.000 -13.728 0.000 -5.802 -0.001
CORRIDOR_FLR_3 0.000 0.000 0.067 -228.822 0.000 0.000 109.654 109.603 0.000 50.435 0.000 4.517 0.002 0.000 -20.699 0.000 -7.834 -16.921
ROOM_1_FLR_6 1.880 -19.575 0.000 -4.201 0.000 0.000 2.417 1.592 3.073 14.364 0.000 1.269 4.258 0.000 -3.579 0.000 -1.498 -0.000
ROOM_2_FLR_6 2.992 -17.121 0.000 -4.131 0.000 0.000 2.424 1.591 3.073 11.260 0.000 1.275 3.703 0.000 -3.621 0.000 -1.445 -0.000
ROOM_3_MULT9_FLR_6 2.686 -115.440 0.000 -27.280 0.000 0.000 21.702 9.005 27.097 72.547 0.000 5.931 28.166 0.000 -16.608 0.000 -7.807 -0.001
BANQUET_FLR_6 0.000 0.000 0.006 -506.406 0.000 0.000 325.115 34.830 175.857 13.917 0.000 2.448 0.000 0.000 -11.708 0.000 -4.072 -29.988
DINING_FLR_6 0.000 0.000 0.002 -530.746 0.000 0.000 321.448 34.830 175.857 13.459 0.000 2.376 0.000 0.000 -12.211 0.000 -4.194 -0.822
KITCHEN_FLR_6 0.000 0.000 0.000 -653.582 0.000 0.000 27.932 13.327 550.372 26.592 0.000 1.997 46.933 0.000 -9.508 0.000 -4.063 -0.001
CORRIDOR_FLR_6 0.000 0.000 0.036 -110.469 0.000 0.000 28.975 28.999 0.000 23.957 0.000 1.956 39.429 0.000 -9.372 0.000 -3.512 -0.000
Total Facility 46.880 -1194.865 0.216 -5026.515 0.000 0.000 1974.533 767.133 2451.839 1099.461 0.000 113.645 433.320 0.000 -371.136 0.000 -186.190 -108.353


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 14-DEC-00:23 0.00 0.00 0.00 -40532.51 0.00 0.00 6664.24 3152.28 3193.83 0.00 0.00 0.00 27522.15 0.00 -0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 28-SEP-13:30 0.00 0.00 0.00 -4131.00 0.00 0.00 150.60 195.67 252.59 3915.55 0.00 223.40 0.00 0.00 -0.00 0.00 0.00 -606.81
RETAIL_2_FLR_1 28-JUN-20:10 0.00 0.00 0.00 -2769.44 0.00 0.00 697.62 725.08 752.15 0.00 0.00 89.55 505.04 0.00 -0.00 0.00 0.00 0.00
MECH_FLR_1 28-JUN-20:00 0.00 0.00 0.00 -3124.59 0.00 0.00 129.09 1360.40 839.45 0.00 0.00 216.98 578.68 0.00 -0.00 0.00 0.00 0.00
STORAGE_FLR_1 28-JUN-19:10 0.00 0.00 0.00 -1355.86 0.00 0.00 99.30 227.72 242.16 0.00 0.00 148.22 638.47 0.00 -0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 04-DEC-21:39 0.00 0.00 0.00 -48778.66 0.00 0.00 461.79 317.52 41967.83 0.00 0.00 0.00 6531.44 0.00 -0.00 0.00 -499.92 0.00
CAFE_FLR_1 30-JAN-05:38 0.00 0.00 0.00 -15979.77 0.00 0.00 9694.01 391.53 304.82 0.00 0.00 0.00 8948.09 0.00 -2659.07 0.00 -699.62 0.00
LOBBY_FLR_1 11-JAN-06:27 0.00 0.00 0.00 -73966.89 0.00 0.00 20562.78 4562.30 5278.53 0.00 0.00 0.00 48855.49 0.00 -3324.02 0.00 -1968.20 0.00
ROOM_1_FLR_3 28-SEP-15:01 0.00 -14489.79 0.00 -680.35 0.00 0.00 235.29 137.21 273.93 9068.23 0.00 628.11 4827.36 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_3 27-JUN-18:02 0.00 -14401.68 0.00 -679.74 0.00 0.00 335.50 436.07 516.20 8219.78 0.00 717.87 4856.01 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 20-NOV-14:30 0.00 -45608.46 0.00 -9760.04 0.00 0.00 0.00 1638.34 5097.90 56800.78 0.00 845.52 0.00 0.00 -0.00 0.00 0.00 -9014.04
ROOM_4_MULT19_FLR_3 27-JUN-18:02 0.00 -87454.19 0.00 -9280.52 0.00 0.00 6374.62 5209.05 9610.21 24223.13 0.00 3791.91 47525.79 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 19-JUN-08:61 0.00 -12675.39 0.00 -680.64 0.00 0.00 87.15 215.61 453.05 8105.23 0.00 363.16 4131.85 0.00 -0.00 0.00 0.00 0.00
ROOM_6_FLR_3 19-JUN-08:61 0.00 -12611.89 0.00 -681.97 0.00 0.00 87.15 215.58 452.99 8297.84 0.00 362.26 3878.04 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 28-JUN-19:10 0.00 0.00 0.00 -16635.72 0.00 0.00 4080.42 8963.13 0.00 3109.40 0.00 788.45 0.00 0.00 -0.00 0.00 0.00 -305.67
ROOM_1_FLR_6 28-SEP-15:01 0.00 -3846.97 0.00 -170.10 0.00 0.00 58.82 34.30 68.48 2251.89 0.00 156.43 1447.14 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_6 27-JUN-18:02 0.00 -3822.07 0.00 -170.00 0.00 0.00 83.88 109.02 129.05 2042.40 0.00 178.83 1448.89 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 28-SEP-15:01 0.00 -17155.35 0.00 -1112.29 0.00 0.00 529.41 194.07 603.86 7557.48 0.00 711.94 8670.88 0.00 -0.00 0.00 0.00 0.00
BANQUET_FLR_6 10-JAN-05:05 0.00 0.00 0.00 -33779.91 0.00 0.00 15215.98 687.57 2249.30 0.00 0.00 0.00 17414.85 0.00 -1371.18 0.00 -416.61 0.00
DINING_FLR_6 14-DEC-23:37 0.00 0.00 0.00 -34167.07 0.00 0.00 15798.20 1031.35 6747.90 0.00 0.00 0.00 12572.10 0.00 -1454.65 0.00 -527.83 0.00
KITCHEN_FLR_6 13-JAN-07:39 0.00 0.00 0.00 -36399.75 0.00 0.00 612.47 605.46 19261.50 57.86 0.00 0.00 16323.82 0.00 -0.00 0.00 -461.36 0.00
CORRIDOR_FLR_6 28-JUN-18:13 0.00 0.00 0.00 -8515.49 0.00 0.00 1079.60 2108.02 0.00 1782.98 0.00 372.53 3172.36 0.00 -0.00 0.00 0.00 0.00
Total Facility 27-JUN-18:02 0.00 -195535.58 0.00 -235756.70 0.00 0.00 74226.05 53571.31 122326.88 87010.27 0.00 17497.89 76659.89 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 25-MAR-03:33 0.00 0.00 638.44 0.00 0.00 0.00 6877.63 1576.23 2129.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -11221.52
RETAIL_1_FLR_1 13-FEB-05:43 0.00 0.00 373.48 0.00 0.00 0.00 802.37 156.54 216.51 0.00 0.00 0.00 0.00 0.00 -721.59 0.00 -267.36 -559.94
RETAIL_2_FLR_1 18-DEC-07:48 0.00 0.00 237.04 0.00 0.00 0.00 397.19 453.18 501.43 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -138.12 -1450.72
MECH_FLR_1 18-DEC-07:48 0.00 0.00 247.83 0.00 0.00 0.00 87.17 755.78 530.18 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -310.19 -1310.76
STORAGE_FLR_1 15-DEC-00:28 0.00 0.00 267.77 0.00 0.00 0.00 151.04 50.60 76.47 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -161.60 -384.29
LAUNDRY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 18-DEC-07:48 0.00 0.00 2538.31 0.00 0.00 0.00 4703.30 597.09 609.65 401.79 0.00 0.00 0.00 0.00 -0.00 0.00 -758.24 -8091.91
LOBBY_FLR_1 18-DEC-07:48 0.00 0.00 4043.46 0.00 0.00 0.00 13238.79 5303.68 6334.24 319.09 0.00 0.00 0.00 0.00 -0.00 0.00 -2296.41 -26942.84
ROOM_1_FLR_3 06-DEC-09:01 8437.17 341.51 0.00 -341.51 0.00 0.00 104.86 215.61 453.05 1409.35 0.00 0.00 0.00 0.00 -0.00 0.00 -664.06 -9955.98
ROOM_2_FLR_3 07-DEC-09:01 8681.01 277.32 0.00 -277.32 0.00 0.00 108.88 215.58 452.99 0.00 0.00 0.00 0.00 0.00 -982.87 0.00 -610.14 -7865.46
ROOM_3_MULT19_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 07-DEC-09:01 49097.88 4531.16 0.00 -4531.16 0.00 0.00 1970.52 2575.24 8433.45 0.00 0.00 0.00 0.00 0.00 -5950.67 0.00 -3444.39 -52682.03
ROOM_5_FLR_3 12-FEB-16:02 7996.99 354.28 0.00 -354.28 0.00 0.00 156.80 161.71 305.54 0.00 0.00 0.00 0.00 0.00 -287.97 0.00 -307.73 -8025.33
ROOM_6_FLR_3 07-DEC-16:01 8128.95 352.93 0.00 -352.93 0.00 0.00 281.21 137.19 273.90 0.00 0.00 0.00 0.00 0.00 -640.07 0.00 -632.12 -7549.07
CORRIDOR_FLR_3 13-FEB-05:43 0.00 0.00 1822.55 0.00 0.00 0.00 6051.21 1991.81 0.00 0.00 0.00 0.00 0.00 0.00 -2201.64 0.00 -780.14 -6883.78
ROOM_1_FLR_6 07-DEC-09:01 2520.33 72.09 0.00 -72.09 0.00 0.00 27.22 53.90 113.26 346.85 0.00 0.00 0.00 0.00 -0.00 0.00 -155.17 -2906.40
ROOM_2_FLR_6 07-DEC-09:01 2554.53 70.39 0.00 -70.39 0.00 0.00 27.22 53.90 113.25 0.00 0.00 0.00 0.00 0.00 -235.33 0.00 -153.99 -2359.57
ROOM_3_MULT9_FLR_6 27-MAR-08:61 11617.40 554.02 0.00 -554.02 0.00 0.00 235.15 304.96 998.70 131.29 0.00 0.00 0.00 0.00 -0.00 0.00 -584.78 -12702.71
BANQUET_FLR_6 06-DEC-08:39 0.00 0.00 2483.29 0.00 0.00 0.00 7987.49 1191.78 6747.90 0.00 0.00 0.00 0.00 0.00 -1017.03 0.00 -513.72 -16879.72
DINING_FLR_6 22-JAN-05:30 0.00 0.00 1836.87 0.00 0.00 0.00 12599.52 687.57 2249.30 0.00 0.00 0.00 0.00 0.00 -1414.14 0.00 -453.84 -15505.28
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 18-DEC-07:48 0.00 0.00 775.21 0.00 0.00 0.00 733.33 1317.51 0.00 0.00 0.00 0.00 0.00 0.00 -397.56 0.00 -420.86 -2007.63
Total Facility 27-MAR-08:61 -18470.80 115432.51 0.00 -115432.51 0.00 0.00 23442.91 26712.50 88432.23 11143.57 0.00 0.00 0.00 0.00 -7831.91 0.00 -13577.27 -109851.24



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 24.7459 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 24.6237 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 13.6446 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.7127 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.000000 142.3000 0.003581 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.001045 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.9300 2.9300 1.2482 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3949 0.3949 0.1185 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2845 0.2845 0.1340 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3030 0.3030 0.0909 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1504 0.1504 0.0845 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.6450 3.6450 1.0935 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5998 1.5998 0.9887 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.2464 5.2464 2.7701 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7066 1.7066 0.6946 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4861 2.4861 1.7353 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6014 2.6014 1.7352 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5088 2.5088 0.7526 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8891 0.8891 0.2667 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 24.7459 24.6237 24.7459 11.7127 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4650 1.4650 1.2482 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1974 0.1974 0.1185 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1422 0.1422 0.1340 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1515 0.1515 0.0909 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0845 0.0845 0.0845 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.8225 1.8225 1.0935 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9887 0.9887 0.9887 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.7701 2.7701 2.7701 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8533 0.8533 0.6946 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7353 1.7353 1.7353 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7352 1.7352 1.7352 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2544 1.2544 0.7526 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4446 0.4446 0.2667 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 13.6446 11.7127 11.7127 11.7127 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 114.67
Number of hours not met 114.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 182.54 176232.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 1978.53 217591.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 767.13 62892.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 242.97 15448.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 959.56 59492.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 14.43 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 8.99 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 32.45 1868.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.91 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 660.66 53347.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 212.61 9630.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 191.08 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.74 4738.76 2671.65 245388.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 20.50 1982.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 34.21 1228.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1806.82 6602.02
Natural Gas 1788.84 4643.03
Additional 0.00 0.00
Total 3595.66 11245.05


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 67.62
Space Heating 0.00
Space Cooling 174.39
Fans (All) 58.23
Service Water Heating 8.00
Receptacle Equipment 153.81
Miscellaneous (All) 581.92
Subtotal 581.92


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 16.09
Service Water Heating 235.49
Miscellaneous (All) 409.25
Subtotal 409.25


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 6.82
Space Heating 1.62
Space Cooling 17.59
Fans (All) 5.88
Service Water Heating 24.57
Receptacle Equipment 31.43
Miscellaneous 12.09


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2667. 8760.
LTG_SCH_LOBBY 3061. 8760.
LTG_SCH_STORAGE 1339. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 2678. 8760.
LTG_SCH_GUESTROOM 2482. 8760.
LTG_SCH_CORRIDOR 3061. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3924. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 18.89 365 18.89 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 23.33 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8760.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 8760.00 0.00 0.00 0.00 0.00
Sum 192720.00 0.00 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 0.00 0.00 0.00 0.00
Average 288887.05 0.00 0.00 0.00 0.00
Sum 6355515.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8740.83 19.17 0.00 0.00 0.00
RETAIL_2_FLR_1 8748.50 11.50 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8365.00 395.00 0.00 0.00 0.00
LOBBY_FLR_1 8364.67 395.33 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8651.33 108.67 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8330.67 429.33 0.00 0.00 0.00
DINING_FLR_6 8331.83 428.17 0.00 0.00 0.00
KITCHEN_FLR_6 8747.83 12.17 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8330.67 0.00 0.00 0.00 0.00
Max 8760.00 429.33 0.00 0.00 0.00
Average 8678.21 81.79 0.00 0.00 0.00
Sum 190920.67 1799.33 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50019.50 159.50 0.00 0.00 0.00
RETAIL_2_FLR_1 59029.50 126.50 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 661040.17 49376.83 0.00 0.00 0.00
LOBBY_FLR_1 1974141.83 141287.17 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 98585.67 1772.33 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1153694.33 92020.67 0.00 0.00 0.00
DINING_FLR_6 1154434.83 91280.17 0.00 0.00 0.00
KITCHEN_FLR_6 108181.33 87.67 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 1974141.83 141287.17 0.00 0.00 0.00
Average 271791.10 17095.95 0.00 0.00 0.00
Sum 5979404.17 376110.83 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:00:32

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

For: Environment

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B

For: Environment

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON

For: Environment

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.376561E+11 38637.81 12-JAN-06:34 5.33 4.82 0.820953E+10 4978.55 26-JAN-05:49 7.83 4.23
February 0.288369E+11 30315.24 01-FEB-06:55 5.00 3.59 0.728448E+10 4901.96 28-FEB-00:20 6.67 5.49
March 0.293740E+11 18717.39 13-MAR-04:40 6.27 5.44 0.782386E+10 4837.00 02-MAR-22:19 6.27 5.44
April 0.309956E+11 18578.47 21-APR-03:50 8.33 0.61 0.774172E+10 4837.08 11-APR-22:10 8.33 0.61
May 0.309036E+11 15114.33 01-MAY-21:00 24.00 9.32 0.783704E+10 4837.10 11-MAY-21:19 25.67 12.70
June 0.321277E+11 16703.60 22-JUN-21:00 31.00 14.48 0.776320E+10 4837.11 23-JUN-21:19 30.33 15.38
July 0.407046E+11 23098.70 14-JUL-21:00 28.00 20.32 0.820489E+10 4837.16 07-JUL-22:10 28.00 20.32
August 0.444376E+11 24801.09 24-AUG-21:00 30.00 12.33 0.826339E+10 4837.10 21-AUG-00:10 30.00 12.33
September 0.482709E+11 27111.66 08-SEP-21:00 32.20 19.39 0.797705E+10 4837.17 15-SEP-03:09 19.90 14.65
October 0.487882E+11 38759.07 25-OCT-05:30 6.00 0.93 0.823636E+10 5023.69 25-OCT-04:30 6.00 0.93
November 0.461885E+11 38841.79 05-NOV-06:40 6.00 2.55 0.796404E+10 5007.57 27-NOV-04:19 8.77 4.31
December 0.450022E+11 40533.31 14-DEC-00:23 5.00 2.11 0.823466E+10 5058.87 07-DEC-23:10 5.00 2.11
                     
Annual Sum or Average 0.463286E+12         0.955402E+11        
Minimum of Months 0.288369E+11 15114.33   5.00 0.61 0.728448E+10 4837.00   5.00 0.61
Maximum of Months 0.487882E+11 40533.31   32.20 20.32 0.826339E+10 5058.87   30.33 20.32



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.395479E+10 3777.40 14-JAN-13:40 26.67 10.98 0.764771E+09 491.82 25-JAN-22:19 12.33 6.47
February 0.232100E+10 2710.84 01-FEB-14:00 16.00 7.74 0.636642E+09 483.29 28-FEB-22:10 12.55 9.16
March 0.279698E+10 2977.15 18-MAR-13:40 26.27 12.12 0.739017E+09 491.82 23-MAR-21:00 13.80 7.85
April 0.444872E+10 3347.16 14-APR-14:10 34.17 14.15 0.791422E+09 491.86 15-APR-01:19 24.00 12.47
May 0.468689E+10 2905.81 31-MAY-18:15 35.33 13.34 0.830060E+09 491.86 10-MAY-23:10 35.33 13.34
June 0.580011E+10 3708.77 28-JUN-18:13 40.67 17.68 0.813201E+09 491.86 09-JUN-23:19 40.67 17.68
July 0.572087E+10 3421.69 21-JUL-18:30 38.00 19.28 0.836542E+09 491.85 01-JUL-00:10 38.00 19.28
August 0.585818E+10 3807.75 28-AUG-12:30 37.00 20.85 0.839401E+09 491.84 10-AUG-22:00 37.00 20.85
September 0.554641E+10 4131.85 28-SEP-13:30 36.10 16.03 0.809544E+09 491.84 07-SEP-21:30 36.10 16.03
October 0.474376E+10 4126.48 06-OCT-13:20 35.00 15.67 0.802789E+09 491.86 19-OCT-22:10 19.83 11.29
November 0.366002E+10 3968.22 20-NOV-13:40 26.67 11.57 0.739530E+09 491.82 15-NOV-22:10 26.67 11.57
December 0.309210E+10 3662.24 25-DEC-13:00 25.00 11.61 0.719081E+09 491.82 22-DEC-22:30 25.00 11.61
                     
Annual Sum or Average 0.526298E+11         0.932200E+10        
Minimum of Months 0.232100E+10 2710.84   16.00 7.74 0.636642E+09 483.29   12.33 6.47
Maximum of Months 0.585818E+10 4131.85   40.67 20.85 0.839401E+09 491.86   40.67 20.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.315560E+10 2222.30 30-JAN-05:38 7.33 2.10 0.913827E+09 570.47 12-JAN-22:30 7.33 2.10
February 0.259216E+10 2142.61 02-FEB-02:35 7.33 3.96 0.785456E+09 570.25 27-FEB-22:30 10.00 7.14
March 0.305641E+10 1924.06 13-MAR-04:40 6.27 5.44 0.899315E+09 569.55 22-MAR-21:10 13.35 7.10
April 0.373314E+10 2457.28 14-APR-20:10 30.67 13.61 0.927138E+09 569.57 16-APR-23:10 18.83 12.52
May 0.407897E+10 2414.92 31-MAY-20:10 30.67 11.82 0.965082E+09 569.57 26-MAY-03:09 30.67 11.82
June 0.449791E+10 2769.78 28-JUN-20:10 36.67 15.41 0.940086E+09 569.57 09-JUN-23:19 36.67 15.41
July 0.442496E+10 2613.25 20-JUL-20:10 35.17 18.52 0.966481E+09 569.55 01-JUL-00:10 35.17 18.52
August 0.440277E+10 2646.71 15-AUG-20:10 34.67 18.05 0.970128E+09 569.54 10-AUG-22:00 34.67 18.05
September 0.406551E+10 2597.82 07-SEP-21:00 33.30 19.43 0.935739E+09 569.55 15-SEP-03:09 19.90 14.65
October 0.364377E+10 2396.76 05-OCT-20:10 26.50 13.28 0.944448E+09 569.58 19-OCT-22:10 19.83 11.29
November 0.310015E+10 2063.41 01-NOV-20:10 20.50 13.68 0.887010E+09 569.53 14-NOV-22:00 13.00 13.00
December 0.290205E+10 2185.61 14-DEC-00:23 5.00 2.11 0.877686E+09 570.29 28-DEC-22:30 9.25 3.38
                     
Annual Sum or Average 0.436534E+11         0.110124E+11        
Minimum of Months 0.259216E+10 1924.06   5.00 2.10 0.785456E+09 569.53   7.33 2.10
Maximum of Months 0.449791E+10 2769.78   36.67 19.43 0.970128E+09 570.47   36.67 18.52



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.191296E+10 1420.98 30-JAN-05:38 7.33 2.10 0.179571E+09 118.24 27-JAN-22:10 7.33 2.10
February 0.162032E+10 1381.07 02-FEB-02:35 7.33 3.96 0.155611E+09 112.57 01-FEB-22:10 7.33 3.96
March 0.195042E+10 1298.93 17-MAR-21:00 21.60 12.64 0.181433E+09 120.46 22-MAR-21:10 13.35 7.10
April 0.272751E+10 2294.71 25-APR-20:00 28.00 14.61 0.195486E+09 120.46 25-APR-00:10 28.00 14.61
May 0.351019E+10 2450.64 31-MAY-20:00 31.00 11.94 0.205330E+09 120.46 10-MAY-23:19 31.00 11.94
June 0.471275E+10 3125.15 28-JUN-20:00 37.00 15.57 0.199180E+09 120.46 09-JUN-23:30 37.00 15.57
July 0.461937E+10 2978.72 21-JUL-20:00 37.00 20.84 0.205008E+09 120.46 07-JUL-22:10 37.00 20.84
August 0.432224E+10 2828.90 15-AUG-20:00 35.00 18.06 0.205842E+09 120.46 21-AUG-00:10 26.00 16.49
September 0.378627E+10 2695.58 08-SEP-20:00 33.80 19.77 0.198641E+09 120.46 20-SEP-21:19 27.20 17.73
October 0.268075E+10 2452.73 03-OCT-20:00 30.00 18.25 0.197069E+09 120.46 19-OCT-22:10 19.83 11.29
November 0.193719E+10 1393.93 02-NOV-20:00 21.00 15.83 0.177909E+09 120.45 02-NOV-22:10 19.83 16.01
December 0.173024E+10 1384.11 14-DEC-00:23 5.00 2.11 0.169574E+09 114.64 26-DEC-22:10 14.83 7.20
                     
Annual Sum or Average 0.355102E+11         0.227065E+10        
Minimum of Months 0.162032E+10 1298.93   5.00 2.10 0.155611E+09 112.57   7.33 2.10
Maximum of Months 0.471275E+10 3125.15   37.00 20.84 0.205842E+09 120.46   37.00 20.84



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.148689E+10 1232.31 30-JAN-05:38 7.33 2.10 0.124102E+09 78.22 27-JAN-22:30 7.33 2.10
February 0.120040E+10 1187.05 02-FEB-02:35 7.33 3.96 0.107912E+09 76.49 01-FEB-00:10 7.33 3.96
March 0.148281E+10 1011.56 02-MAR-05:27 7.15 6.47 0.124777E+09 82.42 17-MAR-21:40 20.87 12.09
April 0.185658E+10 1112.21 21-APR-03:50 8.33 0.61 0.136684E+09 90.43 14-APR-21:40 8.33 0.61
May 0.206328E+10 967.85 31-MAY-18:07 35.67 13.49 0.148111E+09 92.07 18-MAY-21:49 35.67 13.49
June 0.230870E+10 1356.10 28-JUN-19:10 39.50 16.83 0.151341E+09 92.66 09-JUN-23:40 39.50 16.83
July 0.230646E+10 1250.82 21-JUL-20:00 37.00 20.84 0.155084E+09 92.66 07-JUL-22:10 37.00 20.84
August 0.223395E+10 1146.66 15-AUG-20:00 35.00 18.06 0.154070E+09 92.66 14-AUG-23:49 35.00 18.06
September 0.207240E+10 1032.36 08-SEP-20:00 33.80 19.77 0.146362E+09 92.66 20-SEP-21:19 27.20 17.73
October 0.183846E+10 1169.05 12-OCT-04:42 7.17 3.07 0.137943E+09 92.66 03-OCT-21:40 7.17 3.07
November 0.151426E+10 1130.91 30-NOV-05:05 8.00 2.43 0.122058E+09 83.10 02-NOV-22:10 8.00 2.43
December 0.119971E+10 1188.78 14-DEC-00:23 5.00 2.11 0.119537E+09 76.38 26-DEC-22:40 14.33 6.96
                     
Annual Sum or Average 0.215639E+11         0.162798E+10        
Minimum of Months 0.119971E+10 967.85   5.00 0.61 0.107912E+09 76.38   7.17 0.61
Maximum of Months 0.230870E+10 1356.10   39.50 20.84 0.155084E+09 92.66   39.50 20.84



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.495011E+11 42080.81 12-JAN-07:04 5.17 4.58 0.646259E+09 458.80 11-JAN-05:30 5.17 4.58
February 0.439819E+11 42147.59 02-FEB-07:09 5.50 2.72 0.582901E+09 497.13 28-FEB-00:20 6.67 5.49
March 0.497441E+11 41396.38 30-MAR-06:33 5.17 2.04 0.648317E+09 427.39 07-MAR-05:19 5.17 2.04
April 0.509193E+11 39538.83 14-APR-20:00 31.00 13.66 0.629176E+09 382.38 19-APR-04:00 13.00 4.78
May 0.536387E+11 39633.74 09-MAY-20:00 31.00 13.10 0.650748E+09 381.79 11-MAY-21:10 25.83 12.78
June 0.535544E+11 40402.89 28-JUN-20:00 37.00 15.57 0.630919E+09 381.91 23-JUN-21:10 37.00 15.57
July 0.546181E+11 40201.72 21-JUL-20:00 37.00 20.84 0.649371E+09 381.88 07-JUL-21:10 37.00 20.84
August 0.545686E+11 40086.33 15-AUG-20:00 35.00 18.06 0.652148E+09 382.22 09-AUG-21:10 35.00 18.06
September 0.519052E+11 39908.61 08-SEP-20:00 33.80 19.77 0.629260E+09 381.90 19-SEP-21:10 28.02 15.82
October 0.515910E+11 39481.22 12-OCT-06:38 7.67 3.31 0.648235E+09 444.50 25-OCT-04:30 7.00 1.35
November 0.481569E+11 46138.40 23-NOV-21:29 4.00 -1.1 0.625148E+09 442.38 04-NOV-04:40 4.00 -1.1
December 0.483580E+11 48778.68 04-DEC-21:39 5.33 0.54 0.646425E+09 500.64 07-DEC-22:00 4.00 -2.3
                     
Annual Sum or Average 0.610537E+12         0.763891E+10        
Minimum of Months 0.439819E+11 39481.22   4.00 -1.1 0.582901E+09 381.79   4.00 -2.3
Maximum of Months 0.546181E+11 48778.68   37.00 20.84 0.652148E+09 500.64   37.00 20.84



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.231998E+11 15980.31 30-JAN-05:38 7.33 2.10 0.100600E+11 6586.78 11-JAN-01:00 7.33 2.10
February 0.178141E+11 14860.33 02-FEB-01:50 8.17 4.38 0.851870E+10 6467.40 03-FEB-00:20 8.00 3.09
March 0.203987E+11 12574.73 02-MAR-05:27 7.15 6.47 0.961655E+10 6547.37 14-MAR-04:00 7.70 6.56
April 0.232905E+11 13292.91 21-APR-03:50 8.33 0.61 0.100583E+11 6461.74 15-APR-01:19 8.33 0.61
May 0.242259E+11 11658.96 09-MAY-21:10 28.83 12.76 0.104385E+11 6461.51 10-MAY-23:10 25.83 15.07
June 0.258669E+11 13622.52 28-JUN-18:06 40.83 17.83 0.104062E+11 6461.69 05-JUN-04:10 40.83 17.83
July 0.264222E+11 13329.35 21-JUL-21:10 33.83 20.81 0.106794E+11 6461.35 01-JUL-00:10 33.83 20.81
August 0.267827E+11 13660.64 15-AUG-18:05 37.83 18.62 0.107630E+11 6461.19 20-AUG-23:30 26.50 16.19
September 0.257468E+11 14183.87 28-SEP-15:03 37.52 15.49 0.103975E+11 6461.13 06-SEP-21:30 37.52 15.49
October 0.247140E+11 14098.10 05-OCT-15:03 34.00 15.75 0.103839E+11 6461.64 07-OCT-01:00 25.00 14.77
November 0.219583E+11 14253.41 01-NOV-15:03 28.83 16.12 0.965745E+10 6460.84 01-NOV-21:10 18.00 13.11
December 0.211701E+11 15470.44 14-DEC-00:23 5.00 2.11 0.964193E+10 6608.44 30-DEC-00:40 5.33 1.33
                     
Annual Sum or Average 0.281590E+12         0.120621E+12        
Minimum of Months 0.178141E+11 11658.96   5.00 0.61 0.851870E+10 6460.84   5.33 0.61
Maximum of Months 0.267827E+11 15980.31   40.83 20.81 0.107630E+11 6608.44   40.83 20.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.675816E+11 73990.25 11-JAN-06:27 7.50 6.45 0.315053E+11 19908.85 11-JAN-01:00 7.50 6.45
February 0.560402E+11 55655.86 24-FEB-05:54 7.00 7.00 0.273843E+11 19550.23 28-FEB-00:20 6.67 5.49
March 0.646312E+11 56343.11 24-MAR-04:43 6.70 4.74 0.309270E+11 19600.98 14-MAR-04:00 6.70 4.74
April 0.741729E+11 43163.18 14-APR-21:10 28.67 13.19 0.311345E+11 19188.14 20-APR-04:40 13.00 5.28
May 0.798707E+11 42577.69 09-MAY-21:10 28.83 12.76 0.322825E+11 19185.76 26-MAY-03:09 21.00 13.54
June 0.859703E+11 48445.70 28-JUN-20:10 36.67 15.41 0.315194E+11 19185.25 05-JUN-04:10 36.67 15.41
July 0.872686E+11 47508.45 21-JUL-20:10 36.50 20.90 0.324250E+11 19184.79 01-JUL-00:10 36.50 20.90
August 0.869556E+11 46971.73 15-AUG-20:10 34.67 18.05 0.325774E+11 19184.37 10-AUG-22:00 34.67 18.05
September 0.823107E+11 46803.73 07-SEP-21:10 32.75 19.42 0.314573E+11 19184.58 15-SEP-03:09 19.90 14.65
October 0.758382E+11 70167.46 30-OCT-04:57 9.00 5.54 0.320716E+11 19445.11 25-OCT-04:10 9.00 5.54
November 0.658348E+11 43544.48 30-NOV-05:05 8.00 2.43 0.304591E+11 19633.35 04-NOV-04:40 8.00 2.43
December 0.630878E+11 56524.22 04-DEC-23:27 3.50 -0.8 0.306179E+11 19783.50 30-DEC-00:40 5.33 1.33
                     
Annual Sum or Average 0.889563E+12         0.374361E+12        
Minimum of Months 0.560402E+11 42577.69   3.50 -0.8 0.273843E+11 19184.37   5.33 1.33
Maximum of Months 0.872686E+11 73990.25   36.67 20.90 0.325774E+11 19908.85   36.67 20.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.100486E+10 3726.19 31-JAN-16:01 29.00 10.73 97925458.73 56.69 19-JAN-22:40 29.00 10.73
February 0.389383E+09 3516.04 22-FEB-16:01 20.83 11.61 87163594.68 56.69 21-FEB-22:19 20.83 11.61
March 0.825676E+09 3684.94 18-MAR-15:02 27.20 12.30 97556285.93 56.69 21-MAR-21:10 18.62 10.88
April 0.235502E+10 3772.61 14-APR-15:01 35.00 14.57 95574049.06 56.70 24-APR-23:30 26.50 13.00
May 0.279655E+10 3758.40 30-MAY-18:01 31.83 13.91 99016415.84 56.70 10-MAY-23:49 31.83 13.91
June 0.355455E+10 3784.51 27-JUN-18:02 39.83 15.83 96091595.54 56.70 29-JUN-22:10 33.83 15.97
July 0.326302E+10 3762.12 05-JUL-18:02 37.83 16.08 99087927.99 56.70 20-JUL-23:19 32.67 18.65
August 0.320104E+10 3775.55 27-AUG-15:02 40.00 18.27 99162043.83 56.70 11-AUG-21:00 40.00 18.27
September 0.279591E+10 3792.54 28-SEP-15:01 37.52 15.49 95830173.62 56.70 08-SEP-22:10 37.52 15.49
October 0.190424E+10 3784.39 06-OCT-15:01 35.00 14.90 98539702.71 56.70 03-OCT-00:30 35.00 14.90
November 0.101357E+10 3752.56 20-NOV-16:01 26.83 12.13 94728350.29 56.69 01-NOV-21:00 26.83 12.13
December 0.536315E+09 3660.65 25-DEC-16:02 25.67 11.87 97109516.64 56.69 26-DEC-22:19 14.67 7.12
                     
Annual Sum or Average 0.236401E+11         0.115779E+10        
Minimum of Months 0.389383E+09 3516.04   20.83 10.73 87163594.68 56.69   14.67 7.12
Maximum of Months 0.355455E+10 3792.54   40.00 18.27 99162043.83 56.70   40.00 18.65



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.485590E+09 3639.64 31-JAN-16:01 29.00 10.73 96505165.68 56.69 27-JAN-22:10 29.00 10.73
February 0.196466E+09 3445.19 22-FEB-16:01 20.83 11.61 86138019.32 56.69 21-FEB-22:30 20.83 11.61
March 0.611836E+09 3611.88 18-MAR-15:02 27.20 12.30 96842711.08 56.69 16-MAR-22:19 27.20 12.30
April 0.209948E+10 3738.40 25-APR-18:01 31.67 15.03 95473896.02 56.70 12-APR-23:10 31.67 15.03
May 0.272992E+10 3741.29 30-MAY-18:01 31.83 13.91 99023171.92 56.70 10-MAY-23:49 31.83 13.91
June 0.359259E+10 3770.32 27-JUN-18:02 39.83 15.83 96125782.08 56.70 19-JUN-21:10 39.83 15.83
July 0.325151E+10 3746.56 05-JUL-18:02 37.83 16.08 99100405.84 56.70 20-JUL-23:19 32.67 18.65
August 0.305270E+10 3736.16 25-AUG-18:02 38.67 17.09 99149726.42 56.70 11-AUG-21:40 38.67 17.09
September 0.253410E+10 3732.69 28-SEP-15:01 37.52 15.49 95785022.17 56.70 07-SEP-21:49 37.52 15.49
October 0.144778E+10 3719.53 06-OCT-15:01 35.00 14.90 97985109.79 56.70 03-OCT-23:49 35.00 14.90
November 0.567366E+09 3666.17 20-NOV-16:01 26.83 12.13 93667679.32 56.69 02-NOV-23:40 26.83 12.13
December 0.219299E+09 3554.71 25-DEC-16:02 25.67 11.87 95320451.52 56.69 21-DEC-04:10 25.67 11.87
                     
Annual Sum or Average 0.207886E+11         0.115112E+10        
Minimum of Months 0.196466E+09 3445.19   20.83 10.73 86138019.32 56.69   20.83 10.73
Maximum of Months 0.359259E+10 3770.32   39.83 17.09 99149726.42 56.70   39.83 18.65



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.689693E+09 692.43 14-JAN-13:50 26.83 10.99 0.00 0.00 01-JAN-00:10 26.83 10.99
February 0.320791E+09 533.39 01-FEB-15:30 15.50 6.96 0.00 0.00 01-FEB-00:10 15.50 6.96
March 0.367391E+09 512.74 18-MAR-14:30 26.65 12.20 0.00 0.00 01-MAR-00:10 26.65 12.20
April 0.672508E+09 540.34 14-APR-13:40 34.00 14.40 0.00 0.00 01-APR-00:10 34.00 14.40
May 0.696912E+09 451.74 09-MAY-17:17 34.67 14.40 0.00 0.00 01-MAY-00:10 34.67 14.40
June 0.879110E+09 556.09 28-JUN-17:13 41.67 18.88 0.00 0.00 01-JUN-00:10 41.67 18.88
July 0.893734E+09 529.12 21-JUL-19:10 37.83 19.56 0.00 0.00 01-JUL-00:10 37.83 19.56
August 0.931215E+09 617.82 27-AUG-14:00 40.00 18.27 0.00 0.00 01-AUG-00:10 40.00 18.27
September 0.915108E+09 692.01 28-SEP-13:40 36.47 16.05 0.00 0.00 01-SEP-00:10 36.47 16.05
October 0.787308E+09 706.78 18-OCT-13:50 30.83 12.20 0.00 0.00 01-OCT-00:10 30.83 12.20
November 0.594187E+09 728.57 20-NOV-14:30 27.00 11.68 0.00 0.00 01-NOV-00:10 27.00 11.68
December 0.538288E+09 686.94 25-DEC-13:40 25.67 11.87 0.00 0.00 01-DEC-00:10 25.67 11.87
                     
Annual Sum or Average 0.828625E+10         0.00        
Minimum of Months 0.320791E+09 451.74   15.50 6.96 0.00 0.00   15.50 6.96
Maximum of Months 0.931215E+09 728.57   41.67 19.56 0.00 0.00   41.67 19.56



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.246504E+09 1129.55 31-JAN-19:01 23.00 8.93 95624296.55 56.69 06-JAN-22:19 23.00 8.93
February 0.185109E+09 911.15 20-FEB-09:02 12.33 11.58 86287496.05 56.69 16-FEB-22:30 12.33 11.58
March 0.340031E+09 1211.57 15-MAR-18:01 26.55 12.82 96209918.23 56.69 06-MAR-00:30 26.55 12.82
April 0.707028E+09 1267.98 25-APR-18:01 31.67 15.03 94524028.74 56.69 24-APR-23:40 31.67 15.03
May 0.928264E+09 1269.49 30-MAY-18:01 31.83 13.91 98436031.26 56.69 22-MAY-23:10 31.83 13.91
June 0.119903E+10 1272.81 27-JUN-18:02 39.83 15.83 95802303.98 56.70 23-JUN-21:10 39.83 15.83
July 0.117196E+10 1270.15 07-JUL-18:02 36.83 15.93 98785676.36 56.69 07-JUL-21:10 32.00 15.37
August 0.107758E+10 1266.43 27-AUG-15:02 40.00 18.27 98735004.57 56.69 02-AUG-21:49 40.00 18.27
September 0.941845E+09 1269.39 18-SEP-18:01 34.12 16.15 95257541.64 56.69 06-SEP-21:40 34.12 16.15
October 0.577277E+09 1266.99 05-OCT-18:01 31.50 15.38 97005283.46 56.69 03-OCT-21:19 31.50 15.38
November 0.281836E+09 1139.14 20-NOV-16:01 26.83 12.13 92765553.52 56.69 02-NOV-21:10 26.83 12.13
December 0.149734E+09 975.20 23-DEC-09:02 14.67 5.62 95111275.85 56.69 12-DEC-22:00 14.67 5.62
                     
Annual Sum or Average 0.780620E+10         0.114454E+10        
Minimum of Months 0.149734E+09 911.15   12.33 5.62 86287496.05 56.69   12.33 5.62
Maximum of Months 0.119903E+10 1272.81   40.00 18.27 98785676.36 56.70   40.00 18.27



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.959050E+09 3267.06 31-JAN-16:01 29.00 10.73 98269640.92 56.69 19-JAN-22:40 29.00 10.73
February 0.442009E+09 3063.22 22-FEB-16:01 20.83 11.61 87672507.39 56.69 21-FEB-22:40 20.83 11.61
March 0.861305E+09 3242.19 18-MAR-15:02 27.20 12.30 98061539.56 56.69 16-MAR-23:30 27.20 12.30
April 0.238344E+10 3314.68 14-APR-15:01 35.00 14.57 95914077.59 56.69 25-APR-01:10 24.83 12.77
May 0.287587E+10 3318.34 18-MAY-08:61 27.33 12.53 99198528.91 56.69 11-MAY-00:10 27.33 12.53
June 0.363344E+10 3339.02 19-JUN-08:61 31.17 13.53 96062397.25 56.70 27-JUN-21:10 35.50 14.88
July 0.347298E+10 3319.28 01-JUL-08:61 27.50 10.46 99139180.64 56.70 21-JUL-00:30 31.50 18.29
August 0.337372E+10 3330.17 27-AUG-08:61 29.67 14.57 99231468.91 56.70 17-AUG-22:00 29.67 14.57
September 0.288641E+10 3334.45 28-SEP-15:01 37.52 15.49 95920154.96 56.70 07-SEP-22:40 37.52 15.49
October 0.196917E+10 3324.90 06-OCT-15:01 35.00 14.90 98837516.08 56.70 02-OCT-21:10 35.00 14.90
November 0.947412E+09 3273.66 20-NOV-16:01 26.83 12.13 94975851.15 56.70 02-NOV-21:10 26.83 12.13
December 0.546437E+09 3197.66 25-DEC-16:02 25.67 11.87 97442324.31 56.69 26-DEC-22:19 14.67 7.12
                     
Annual Sum or Average 0.243512E+11         0.116073E+10        
Minimum of Months 0.442009E+09 3063.22   20.83 10.46 87672507.39 56.69   14.67 7.12
Maximum of Months 0.363344E+10 3339.02   37.52 15.49 99231468.91 56.70   37.52 18.29



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.439311E+09 3188.04 31-JAN-16:01 29.00 10.73 96728298.16 56.69 19-JAN-22:10 29.00 10.73
February 0.227545E+09 2821.31 22-FEB-16:01 20.83 11.61 86575936.28 56.69 21-FEB-22:10 20.83 11.61
March 0.635826E+09 3203.87 15-MAR-15:01 28.30 12.89 97378897.88 56.69 22-MAR-21:10 13.35 7.10
April 0.211700E+10 3272.49 14-APR-15:01 35.00 14.57 95901876.62 56.69 25-APR-00:30 25.50 13.09
May 0.280701E+10 3299.57 18-MAY-08:61 27.33 12.53 99198496.29 56.69 29-MAY-23:10 24.83 13.80
June 0.367091E+10 3323.48 19-JUN-08:61 31.17 13.53 96076514.98 56.70 27-JUN-21:10 35.50 14.88
July 0.346066E+10 3303.73 01-JUL-08:61 27.50 10.46 99139677.26 56.70 31-JUL-23:10 30.52 18.25
August 0.322350E+10 3306.40 27-AUG-08:61 29.67 14.57 99227851.78 56.70 11-AUG-22:30 29.67 14.57
September 0.262058E+10 3282.02 28-SEP-15:01 37.52 15.49 95911232.49 56.70 08-SEP-22:19 37.52 15.49
October 0.149117E+10 3267.68 06-OCT-15:01 35.00 14.90 98431661.70 56.70 03-OCT-21:10 35.00 14.90
November 0.509417E+09 3188.91 20-NOV-16:01 26.83 12.13 93771967.87 56.69 03-NOV-00:10 26.83 12.13
December 0.214165E+09 2984.25 25-DEC-16:02 25.67 11.87 95459750.31 56.69 29-DEC-05:19 6.67 2.09
                     
Annual Sum or Average 0.214171E+11         0.115380E+10        
Minimum of Months 0.214165E+09 2821.31   20.83 10.46 86575936.28 56.69   6.67 2.09
Maximum of Months 0.367091E+10 3323.48   37.52 15.49 99227851.78 56.70   37.52 18.25



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.379529E+10 2812.72 30-JAN-05:38 7.33 2.10 0.144882E+10 920.50 31-JAN-22:40 13.83 4.56
February 0.312126E+10 2756.01 02-FEB-02:35 7.33 3.96 0.123261E+10 906.07 01-FEB-00:10 7.33 3.96
March 0.371117E+10 2441.21 13-MAR-04:40 6.27 5.44 0.142937E+10 923.52 17-MAR-21:40 20.87 12.09
April 0.462494E+10 3199.76 14-APR-18:15 33.00 13.86 0.153908E+10 951.86 25-APR-00:10 25.83 13.25
May 0.532898E+10 3270.32 31-MAY-18:30 35.00 13.18 0.161663E+10 951.88 10-MAY-23:30 35.00 13.18
June 0.643111E+10 4159.59 28-JUN-19:10 39.50 16.83 0.157384E+10 951.87 09-JUN-23:40 39.50 16.83
July 0.632544E+10 3819.18 21-JUL-19:10 37.83 19.56 0.161962E+10 951.87 07-JUL-22:10 37.83 19.56
August 0.619238E+10 3661.06 25-AUG-18:15 38.33 16.79 0.162539E+10 951.85 21-AUG-00:10 38.33 16.79
September 0.567618E+10 3547.23 08-SEP-18:15 35.90 20.02 0.156773E+10 951.86 20-SEP-21:19 27.20 17.73
October 0.475861E+10 3221.75 05-OCT-18:13 31.00 15.12 0.156566E+10 951.86 19-OCT-22:10 19.83 11.29
November 0.377627E+10 2588.25 30-NOV-05:05 8.00 2.43 0.142503E+10 949.34 02-NOV-21:40 8.00 2.43
December 0.346355E+10 2622.63 14-DEC-00:23 5.00 2.11 0.137183E+10 893.33 26-DEC-22:40 14.33 6.96
                     
Annual Sum or Average 0.572052E+11         0.180156E+11        
Minimum of Months 0.312126E+10 2441.21   5.00 2.10 0.123261E+10 893.33   7.33 2.43
Maximum of Months 0.643111E+10 4159.59   39.50 20.02 0.162539E+10 951.88   39.50 19.56



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.849227E+09 3931.14 31-JAN-16:01 29.00 10.73 97585789.93 56.69 18-JAN-22:10 29.00 10.73
February 0.312632E+09 3706.02 22-FEB-16:01 20.83 11.61 86751640.84 56.69 01-FEB-01:10 20.83 11.61
March 0.721681E+09 3894.52 18-MAR-15:02 27.20 12.30 97232441.05 56.69 19-MAR-03:39 11.23 7.96
April 0.229941E+10 3998.38 14-APR-15:01 35.00 14.57 95450574.10 56.70 11-APR-22:30 35.00 14.57
May 0.279817E+10 3981.25 07-MAY-15:01 35.17 13.95 98939729.02 56.70 10-MAY-22:00 26.00 15.12
June 0.371622E+10 4009.02 27-JUN-18:02 39.83 15.83 96103356.71 56.70 29-JUN-21:49 34.17 16.06
July 0.338911E+10 3981.48 05-JUL-18:02 37.83 16.08 99074892.12 56.70 11-JUL-21:40 31.00 19.81
August 0.330183E+10 4002.75 27-AUG-15:02 40.00 18.27 99139388.35 56.70 17-AUG-21:30 40.00 18.27
September 0.280856E+10 4017.08 28-SEP-15:01 37.52 15.49 95770336.64 56.70 06-SEP-21:10 37.52 15.49
October 0.176035E+10 4002.21 06-OCT-15:01 35.00 14.90 98306588.43 56.70 01-OCT-23:10 35.00 14.90
November 0.843652E+09 3967.99 20-NOV-16:01 26.83 12.13 94370169.51 56.69 02-NOV-22:00 26.83 12.13
December 0.442349E+09 3863.03 25-DEC-16:02 25.67 11.87 96668982.11 56.69 26-DEC-22:30 14.50 7.04
                     
Annual Sum or Average 0.232432E+11         0.115539E+10        
Minimum of Months 0.312632E+09 3706.02   20.83 10.73 86751640.84 56.69   11.23 7.04
Maximum of Months 0.371622E+10 4017.08   40.00 18.27 99139388.35 56.70   40.00 19.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.375918E+09 3826.24 31-JAN-16:01 29.00 10.73 95984400.18 56.69 26-JAN-05:40 29.00 10.73
February 0.152226E+09 3620.51 22-FEB-16:01 20.83 11.61 85633571.45 56.69 21-FEB-22:10 20.83 11.61
March 0.517937E+09 3810.61 18-MAR-15:02 27.20 12.30 96469234.21 56.69 22-MAR-02:20 15.67 9.94
April 0.203560E+10 3952.25 25-APR-18:01 31.67 15.03 95354319.67 56.70 11-APR-22:10 31.67 15.03
May 0.272939E+10 3950.93 30-MAY-18:01 31.83 13.91 98948852.61 56.70 10-MAY-22:49 31.83 13.91
June 0.375525E+10 3992.03 27-JUN-18:02 39.83 15.83 96142128.97 56.70 29-JUN-21:00 34.00 15.96
July 0.337685E+10 3962.87 05-JUL-18:02 37.83 16.08 99089300.10 56.70 20-JUL-22:40 33.00 18.53
August 0.314773E+10 3956.15 25-AUG-18:02 38.67 17.09 99118545.50 56.70 01-AUG-21:10 38.67 17.09
September 0.253695E+10 3948.59 28-SEP-15:01 37.52 15.49 95718321.14 56.70 07-SEP-21:30 37.52 15.49
October 0.130683E+10 3928.09 06-OCT-15:01 35.00 14.90 97678210.46 56.70 03-OCT-22:19 35.00 14.90
November 0.432901E+09 3863.64 20-NOV-16:01 26.83 12.13 93161113.93 56.70 22-NOV-01:19 14.33 7.48
December 0.172540E+09 3732.14 25-DEC-16:02 25.67 11.87 94719433.27 56.69 21-DEC-04:10 25.67 11.87
                     
Annual Sum or Average 0.205401E+11         0.114802E+10        
Minimum of Months 0.152226E+09 3620.51   20.83 10.73 85633571.45 56.69   14.33 7.48
Maximum of Months 0.375525E+10 3992.03   39.83 17.09 99118545.50 56.70   38.67 18.53



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.117379E+10 2010.56 31-JAN-16:01 29.00 10.73 98579522.48 56.69 26-JAN-22:19 29.00 10.73
February 0.506901E+09 1878.98 22-FEB-16:01 20.83 11.61 87996438.72 56.83 06-FEB-23:49 20.83 11.61
March 0.648869E+09 1985.33 18-MAR-15:02 27.20 12.30 97932587.78 56.69 16-MAR-22:10 27.20 12.30
April 0.132246E+10 2006.31 14-APR-15:01 35.00 14.57 95488379.17 56.69 19-APR-21:30 20.50 9.19
May 0.141488E+10 1985.78 07-MAY-15:01 35.17 13.95 98899230.80 56.69 10-MAY-23:30 25.50 14.96
June 0.180789E+10 1982.65 27-JUN-15:02 41.00 15.93 95945129.48 56.70 29-JUN-21:00 34.00 15.96
July 0.181994E+10 1975.20 07-JUL-15:02 37.00 15.61 99032260.43 56.70 24-JUL-21:40 31.00 18.54
August 0.187237E+10 2001.21 26-AUG-15:02 41.00 16.32 99124843.58 56.70 11-AUG-22:30 41.00 16.32
September 0.179190E+10 2029.74 28-SEP-15:01 37.52 15.49 95823528.40 56.70 08-SEP-22:00 37.52 15.49
October 0.144982E+10 2025.86 06-OCT-15:01 35.00 14.90 98710800.03 56.70 03-OCT-21:00 35.00 14.90
November 0.102910E+10 2021.11 20-NOV-16:01 26.83 12.13 95187655.67 56.69 02-NOV-22:19 26.83 12.13
December 0.864418E+09 1991.39 25-DEC-16:02 25.67 11.87 98203827.44 56.69 26-DEC-22:49 14.17 6.88
                     
Annual Sum or Average 0.157024E+11         0.116092E+10        
Minimum of Months 0.506901E+09 1878.98   20.83 10.73 87996438.72 56.69   14.17 6.88
Maximum of Months 0.187237E+10 2029.74   41.00 16.32 99124843.58 56.83   41.00 18.54



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.382182E+11 33791.94 10-JAN-05:05 8.00 6.84 0.177673E+11 12165.18 11-JAN-01:00 7.00 6.45
February 0.338226E+11 31904.40 24-FEB-05:54 7.00 7.00 0.159081E+11 12082.30 28-FEB-00:20 6.67 5.49
March 0.392117E+11 32267.07 24-MAR-04:43 6.70 4.74 0.180312E+11 12086.28 14-MAR-04:00 6.70 4.74
April 0.426160E+11 29430.07 21-APR-03:54 8.00 0.42 0.180944E+11 11346.64 15-APR-01:19 8.00 0.42
May 0.460978E+11 22865.87 09-MAY-21:10 28.83 12.76 0.189044E+11 11347.06 26-MAY-02:00 21.00 13.75
June 0.480914E+11 24844.64 28-JUN-21:20 34.33 14.34 0.184848E+11 11356.00 29-JUN-21:19 34.67 16.35
July 0.488680E+11 24361.85 21-JUL-21:10 33.83 20.81 0.189901E+11 11353.24 11-JUL-22:00 33.83 20.81
August 0.481468E+11 23835.65 10-AUG-21:10 33.33 18.08 0.190214E+11 11345.96 20-AUG-23:19 26.67 16.09
September 0.451602E+11 23589.71 07-SEP-21:10 32.75 19.42 0.182933E+11 11345.59 15-SEP-23:30 21.90 13.27
October 0.421391E+11 25816.82 12-OCT-04:42 7.17 3.07 0.183937E+11 12177.86 25-OCT-04:10 7.00 1.34
November 0.376062E+11 25232.52 30-NOV-05:05 8.00 2.43 0.173032E+11 12320.50 04-NOV-04:40 8.00 2.43
December 0.364239E+11 31224.53 14-DEC-23:37 6.00 1.03 0.174007E+11 12464.25 19-DEC-23:40 5.67 0.87
                     
Annual Sum or Average 0.506402E+12         0.216593E+12        
Minimum of Months 0.338226E+11 22865.87   6.00 0.42 0.159081E+11 11345.59   5.67 0.42
Maximum of Months 0.488680E+11 33791.94   34.33 20.81 0.190214E+11 12464.25   34.67 20.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.400946E+11 33422.31 09-JAN-23:55 8.00 7.43 0.182149E+11 12392.58 11-JAN-01:00 7.00 6.45
February 0.357327E+11 33994.67 24-FEB-05:54 7.00 7.00 0.163948E+11 12334.33 28-FEB-00:20 6.67 5.49
March 0.412780E+11 33919.77 24-MAR-04:43 6.70 4.74 0.184797E+11 12115.01 14-MAR-04:00 6.70 4.74
April 0.445757E+11 33246.64 21-APR-03:54 8.00 0.42 0.183310E+11 11421.41 28-APR-04:49 13.33 6.61
May 0.482473E+11 24223.83 09-MAY-21:10 28.83 12.76 0.190816E+11 11347.21 26-MAY-02:00 21.00 13.75
June 0.503191E+11 26255.11 28-JUN-21:20 34.33 14.34 0.186192E+11 11383.72 16-JUN-21:19 34.33 14.34
July 0.511123E+11 25745.56 21-JUL-21:10 33.83 20.81 0.191388E+11 11380.76 07-JUL-21:19 33.83 20.81
August 0.503298E+11 25199.47 10-AUG-21:10 33.33 18.08 0.191776E+11 11357.86 15-AUG-22:30 30.50 16.87
September 0.471904E+11 24937.72 07-SEP-21:10 32.75 19.42 0.184559E+11 11347.82 08-SEP-21:30 30.80 19.18
October 0.440291E+11 27337.25 25-OCT-04:40 7.00 1.35 0.186957E+11 12390.90 25-OCT-04:10 7.00 1.35
November 0.393861E+11 27641.91 08-NOV-03:30 8.00 2.81 0.177223E+11 12483.53 04-NOV-04:40 8.00 2.81
December 0.384472E+11 34171.80 14-DEC-23:37 6.00 1.03 0.179478E+11 12743.98 19-DEC-23:40 5.67 0.87
                     
Annual Sum or Average 0.530742E+12         0.220259E+12        
Minimum of Months 0.357327E+11 24223.83   6.00 0.42 0.163948E+11 11347.21   5.67 0.87
Maximum of Months 0.511123E+11 34171.80   34.33 20.81 0.191776E+11 12743.98   34.33 20.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.515866E+11 36405.13 13-JAN-07:39 6.67 4.41 0.188724E+11 11319.63 14-JAN-18:19 20.00 9.94
February 0.458161E+11 34465.36 28-FEB-07:13 5.67 4.84 0.170453E+11 11368.93 04-FEB-18:40 5.67 4.84
March 0.520867E+11 34857.39 31-MAR-06:53 5.50 1.22 0.188760E+11 11319.65 18-MAR-17:19 5.50 1.22
April 0.548620E+11 30564.23 30-APR-10:40 30.00 11.09 0.182623E+11 11319.75 15-APR-17:19 30.00 11.09
May 0.581250E+11 30788.78 07-MAY-10:40 30.00 12.89 0.188718E+11 11319.66 13-MAY-17:19 29.67 11.30
June 0.589734E+11 31667.48 18-JUN-10:50 35.67 17.76 0.182662E+11 11319.66 10-JUN-17:19 35.67 17.76
July 0.603524E+11 31667.26 22-JUL-10:40 35.67 19.48 0.188685E+11 11319.84 08-JUL-17:19 35.67 19.48
August 0.599956E+11 31708.56 13-AUG-10:40 33.67 21.36 0.188757E+11 11319.71 19-AUG-17:19 31.33 19.30
September 0.567852E+11 31427.60 09-SEP-10:35 33.43 20.70 0.182619E+11 11319.67 23-SEP-17:19 33.27 17.89
October 0.549436E+11 32601.45 25-OCT-08:07 8.50 2.37 0.188690E+11 11319.67 14-OCT-17:19 8.50 2.37
November 0.502170E+11 33754.42 24-NOV-08:15 7.67 0.28 0.182603E+11 11319.51 18-NOV-18:19 7.67 0.28
December 0.498468E+11 35437.30 29-DEC-08:10 6.83 2.24 0.188743E+11 11319.49 23-DEC-18:19 6.83 2.24
                     
Annual Sum or Average 0.653590E+12         0.222204E+12        
Minimum of Months 0.458161E+11 30564.23   5.50 0.28 0.170453E+11 11319.49   5.50 0.28
Maximum of Months 0.603524E+11 36405.13   35.67 21.36 0.188760E+11 11368.93   35.67 19.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.595610E+10 4201.26 30-JAN-05:38 7.33 2.10 0.154185E+10 988.87 31-JAN-22:30 14.05 4.75
February 0.487016E+10 4099.66 02-FEB-02:35 7.33 3.96 0.131006E+10 965.40 01-FEB-00:10 7.33 3.96
March 0.599548E+10 4521.25 18-MAR-15:00 27.20 12.54 0.153893E+10 1007.38 16-MAR-22:40 27.20 12.54
April 0.926215E+10 6911.28 14-APR-15:03 35.00 14.57 0.163816E+10 1007.42 16-APR-23:10 18.83 12.52
May 0.110669E+11 6657.88 31-MAY-18:15 35.33 13.34 0.171268E+10 1007.44 10-MAY-23:19 35.33 13.34
June 0.140628E+11 8515.73 28-JUN-18:13 40.67 17.68 0.166580E+10 1007.44 09-JUN-23:19 40.67 17.68
July 0.139317E+11 7781.02 20-JUL-18:17 38.33 19.15 0.171450E+10 1007.43 07-JUL-22:10 38.33 19.15
August 0.135055E+11 7718.78 26-AUG-14:50 40.83 16.32 0.172150E+10 1007.41 10-AUG-22:00 40.83 16.32
September 0.119708E+11 7723.24 07-SEP-15:03 37.28 19.77 0.166083E+10 1007.41 15-SEP-03:09 19.90 14.65
October 0.864445E+10 7204.97 02-OCT-13:10 34.17 19.45 0.165497E+10 1007.43 19-OCT-22:10 19.83 11.29
November 0.602791E+10 5151.44 01-NOV-15:03 28.83 16.12 0.151128E+10 1007.39 02-NOV-22:10 19.83 16.01
December 0.517399E+10 4012.14 14-DEC-00:23 5.00 2.11 0.143429E+10 967.16 26-DEC-22:30 14.50 7.04
                     
Annual Sum or Average 0.110468E+12         0.191049E+11        
Minimum of Months 0.487016E+10 4012.14   5.00 2.10 0.131006E+10 965.40   7.33 3.96
Maximum of Months 0.140628E+11 8515.73   40.83 19.77 0.172150E+10 1007.44   40.83 19.15



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 89044.72 538.69 26-JAN-04:50 7.17
February 10315.63 171.93 02-FEB-05:29 7.00
March 252285.50 638.43 25-MAR-03:33 7.17
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:10 9.20
         
Annual Sum or Average 351645.85      
Minimum of Months 0.00 0.00   7.00
Maximum of Months 252285.50 638.43   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 6040736.64 323.93 12-JAN-06:57 5.00
February 3147085.27 373.46 13-FEB-05:43 8.00
March 3387426.52 351.98 07-MAR-05:30 7.20
April 7147.20 119.12 21-APR-03:53 8.00
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 730721.01 284.71 26-OCT-04:07 7.00
November 2506533.19 326.30 05-NOV-05:56 6.00
December 10969401.55 351.60 30-DEC-07:29 5.50
         
Annual Sum or Average 26789051.38      
Minimum of Months 0.00 0.00   5.00
Maximum of Months 10969401.55 373.46   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 902815.50 148.08 01-JAN-09:17 6.10
February 658122.38 202.46 13-FEB-05:43 8.00
March 262409.61 143.56 07-MAR-05:30 7.20
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 72082.81 85.06 26-OCT-04:07 7.00
November 298180.41 122.23 18-NOV-06:17 6.00
December 1199459.68 237.05 18-DEC-07:48 4.67
         
Annual Sum or Average 3393070.39      
Minimum of Months 0.00 0.00   4.67
Maximum of Months 1199459.68 237.05   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 3617340.33 216.41 01-JAN-09:17 6.10
February 1705879.40 238.35 13-FEB-05:43 8.00
March 767020.10 181.31 07-MAR-05:30 7.20
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 217998.63 145.54 26-OCT-04:07 7.00
November 1087660.69 187.33 27-NOV-05:47 7.87
December 4124085.45 247.83 18-DEC-07:48 4.67
         
Annual Sum or Average 11519984.59      
Minimum of Months 0.00 0.00   4.67
Maximum of Months 4124085.45 247.83   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 5993538.67 266.36 26-JAN-04:50 7.17
February 2805511.58 267.40 13-FEB-05:43 8.00
March 1627953.47 241.09 07-MAR-05:30 7.20
April 4991.00 83.18 21-APR-03:53 8.00
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 519337.79 219.40 26-OCT-04:07 7.00
November 2231258.56 250.23 27-NOV-05:47 7.87
December 6330696.63 267.77 15-DEC-00:28 6.00
         
Annual Sum or Average 19513287.70      
Minimum of Months 0.00 0.00   6.00
Maximum of Months 6330696.63 267.77   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:01 4.27
February 0.00 0.00 01-FEB-00:10 11.90
March 0.00 0.00 01-MAR-00:05 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:10 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 11455661.66 1971.97 12-JAN-07:20 5.33
February 4859701.73 2362.46 02-FEB-07:20 6.00
March 1904394.61 2296.92 30-MAR-06:32 5.17
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 1589355.36 1966.44 25-OCT-06:30 5.00
November 5048493.76 1735.41 05-NOV-05:56 6.00
December 10557176.33 2538.34 18-DEC-07:48 4.67
         
Annual Sum or Average 35414783.45      
Minimum of Months 0.00 0.00   4.67
Maximum of Months 11455661.66 2538.34   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1970751.59 2381.60 26-JAN-04:50 7.17
February 1071250.32 2121.37 02-FEB-07:20 6.00
March 312450.29 2934.72 30-MAR-06:32 5.17
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 41756.17 556.75 25-OCT-06:30 5.00
November 614591.03 1450.87 05-NOV-05:56 6.00
December 3541685.98 4043.59 18-DEC-07:48 4.67
         
Annual Sum or Average 7552485.38      
Minimum of Months 0.00 0.00   4.67
Maximum of Months 3541685.98 4043.59   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 56891796.49 2104.63 01-JAN-09:01 5.90
February 0.123917E+09 2059.03 08-FEB-09:01 10.17
March 85310130.32 2101.61 26-MAR-08:61 7.75
April 1141297.70 805.71 17-APR-08:03 21.30
May 905624.02 742.44 01-MAY-08:03 19.50
June 193765.31 327.59 13-JUN-08:04 25.50
July 392143.18 698.31 29-JUL-08:04 26.33
August 492953.83 706.32 05-AUG-08:04 23.33
September 648573.75 789.66 04-SEP-08:04 23.08
October 9433172.82 1159.48 25-OCT-08:62 8.50
November 40208921.46 1467.12 24-NOV-09:01 9.00
December 0.225364E+09 2109.30 06-DEC-09:01 6.50
         
Annual Sum or Average 0.544899E+09      
Minimum of Months 193765.31 327.59   5.90
Maximum of Months 0.225364E+09 2109.30   26.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.154218E+09 2158.56 01-JAN-09:01 5.90
February 0.217059E+09 2109.35 09-FEB-09:01 8.50
March 0.126271E+09 2116.46 26-MAR-08:61 7.75
April 1313709.91 848.91 10-APR-08:03 22.50
May 918441.01 740.06 01-MAY-08:03 19.50
June 130577.54 267.94 13-JUN-08:04 25.50
July 361159.17 707.93 29-JUL-08:04 26.33
August 524947.55 677.26 05-AUG-08:04 23.33
September 906076.45 786.95 04-SEP-08:04 23.08
October 23571577.29 2055.11 25-OCT-08:62 8.50
November 0.102206E+09 2125.44 23-NOV-09:01 5.45
December 0.445813E+09 2170.22 07-DEC-09:01 6.67
         
Annual Sum or Average 0.107329E+10      
Minimum of Months 130577.54 267.94   5.45
Maximum of Months 0.445813E+09 2170.22   26.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:01 4.27
February 0.00 0.00 01-FEB-00:10 11.90
March 0.00 0.00 01-MAR-00:05 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:10 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 8728503.26 627.71 02-JAN-09:01 12.50
February 5377286.38 621.14 03-FEB-16:01 16.83
March 4388112.79 627.63 27-MAR-08:61 9.77
April 808615.11 385.10 26-APR-08:04 24.33
May 751713.14 416.38 26-MAY-08:04 24.50
June 51816.57 108.77 30-JUN-08:06 31.33
July 80471.63 314.22 27-JUL-08:05 25.33
August 159391.99 387.07 24-AUG-08:04 26.50
September 274999.23 342.30 29-SEP-08:04 26.65
October 958309.10 338.92 31-OCT-15:03 28.00
November 4965461.56 629.93 24-NOV-09:01 9.00
December 41743630.10 646.03 07-DEC-09:01 6.67
         
Annual Sum or Average 68288310.84      
Minimum of Months 51816.57 108.77   6.67
Maximum of Months 41743630.10 646.03   31.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 66787962.99 755.90 11-JAN-19:03 14.00
February 0.116862E+09 1999.25 12-FEB-16:02 14.00
March 79674962.65 1290.09 07-MAR-09:02 10.87
April 119819.93 644.51 29-APR-08:04 24.33
May 102897.82 620.47 26-MAY-08:04 24.50
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 31712.23 224.15 04-AUG-08:05 22.33
September 73677.98 337.55 03-SEP-08:05 20.18
October 7625747.47 556.62 30-OCT-18:04 20.67
November 47879579.60 963.13 25-NOV-16:03 17.00
December 0.222481E+09 1858.41 11-DEC-09:02 13.17
         
Annual Sum or Average 0.541640E+09      
Minimum of Months 0.00 0.00   10.87
Maximum of Months 0.222481E+09 1999.25   27.73



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.162786E+09 1991.28 01-JAN-16:02 15.03
February 0.185229E+09 2005.45 04-FEB-09:02 9.50
March 0.114179E+09 1641.97 07-MAR-09:02 10.87
April 229617.64 665.25 29-APR-08:04 24.33
May 98376.97 630.85 26-MAY-08:04 24.50
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 24424.45 233.94 04-AUG-08:05 22.33
September 85979.27 326.70 03-SEP-08:05 20.18
October 19463267.71 864.21 25-OCT-15:03 17.00
November 0.111842E+09 1519.41 23-NOV-19:03 8.83
December 0.416671E+09 2032.25 07-DEC-16:01 15.67
         
Annual Sum or Average 0.101061E+10      
Minimum of Months 0.00 0.00   8.83
Maximum of Months 0.416671E+09 2032.25   27.73



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 5098579.69 361.47 01-JAN-23:25 5.10
February 2504800.74 455.63 13-FEB-05:43 8.00
March 1267145.82 314.09 07-MAR-05:30 7.20
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 317001.24 198.97 26-OCT-04:07 7.00
November 1423021.62 266.36 18-NOV-04:35 7.00
December 6156854.00 454.47 18-DEC-07:48 4.67
         
Annual Sum or Average 16767403.10      
Minimum of Months 0.00 0.00   4.67
Maximum of Months 6156854.00 455.63   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.180805E+09 2505.47 01-JAN-09:01 5.90
February 0.302898E+09 2457.04 09-FEB-09:01 8.50
March 0.204503E+09 2504.75 26-MAR-08:61 7.75
April 3256056.30 863.87 24-APR-08:03 23.50
May 950506.42 910.65 13-MAY-08:03 21.17
June 182437.14 381.10 13-JUN-08:04 25.50
July 420150.41 583.73 18-JUL-08:04 27.17
August 469401.12 718.05 05-AUG-08:04 23.33
September 969437.72 706.79 30-SEP-08:04 26.05
October 49088893.91 2414.05 25-OCT-08:62 8.50
November 0.137426E+09 2474.76 23-NOV-09:01 5.45
December 0.466452E+09 2520.28 07-DEC-09:01 6.67
         
Annual Sum or Average 0.134742E+10      
Minimum of Months 182437.14 381.10   5.45
Maximum of Months 0.466452E+09 2520.28   27.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.371367E+09 2547.63 01-JAN-09:01 5.90
February 0.463560E+09 2501.51 09-FEB-09:01 8.50
March 0.276984E+09 2516.70 26-MAR-08:61 7.75
April 5091131.81 958.82 24-APR-08:03 23.50
May 981386.58 822.87 13-MAY-08:03 21.17
June 102466.35 319.46 13-JUN-08:04 25.50
July 384775.81 635.00 29-JUL-08:04 26.33
August 502010.30 760.49 05-AUG-08:04 23.33
September 1109639.96 761.20 30-SEP-08:04 26.05
October 87796516.64 2445.30 25-OCT-08:62 8.50
November 0.268908E+09 2534.74 23-NOV-09:01 5.45
December 0.803372E+09 2554.47 07-DEC-09:01 6.67
         
Annual Sum or Average 0.228016E+10      
Minimum of Months 102466.35 319.46   5.45
Maximum of Months 0.803372E+09 2554.47   26.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 8344244.80 254.68 02-JAN-09:03 12.50
February 33801882.42 1259.17 12-FEB-16:02 14.00
March 35903524.09 1290.83 27-MAR-08:61 9.77
April 753231.83 444.84 10-APR-08:03 22.50
May 697816.20 433.07 06-MAY-08:04 24.33
June 582950.08 439.65 21-JUN-08:04 27.50
July 539595.87 474.76 24-JUL-08:04 28.00
August 581932.95 462.13 17-AUG-08:04 28.33
September 377602.92 407.32 29-SEP-08:04 26.65
October 1795411.17 443.00 01-OCT-08:04 26.50
November 8827001.90 405.56 24-NOV-09:03 9.00
December 50697622.72 452.89 17-DEC-16:04 15.83
         
Annual Sum or Average 0.142903E+09      
Minimum of Months 377602.92 254.68   9.00
Maximum of Months 50697622.72 1290.83   28.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 2369780.85 2319.27 22-JAN-05:30 7.00
February 479582.86 1759.62 02-FEB-07:20 6.00
March 112685.48 1878.09 30-MAR-06:32 5.17
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 90247.34 1190.33 25-OCT-06:30 5.00
November 417092.37 874.92 05-NOV-05:06 6.83
December 3018692.25 2483.35 06-DEC-08:39 4.67
         
Annual Sum or Average 6488081.14      
Minimum of Months 0.00 0.00   4.67
Maximum of Months 3018692.25 2483.35   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 846091.58 1836.73 22-JAN-05:30 7.00
February 162908.47 1156.13 02-FEB-07:20 6.00
March 67022.41 1117.04 30-MAR-06:32 5.17
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 44117.08 588.23 25-OCT-06:30 5.00
November 65391.36 389.93 05-NOV-05:06 6.83
December 1006462.12 1671.14 06-DEC-08:39 4.67
         
Annual Sum or Average 2191993.02      
Minimum of Months 0.00 0.00   4.67
Maximum of Months 1006462.12 1836.73   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:01 4.27
February 0.00 0.00 01-FEB-00:10 11.90
March 0.00 0.00 01-MAR-00:05 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:10 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 10770467.93 631.26 04-JAN-05:53 7.00
February 5205014.83 752.94 13-FEB-05:43 8.00
March 2437600.04 580.53 30-MAR-06:32 5.17
April 1216.37 20.27 21-APR-03:53 8.00
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 848511.22 454.13 26-OCT-04:07 7.00
November 3637463.04 547.88 27-NOV-05:47 7.87
December 12844534.59 775.22 18-DEC-07:48 4.67
         
Annual Sum or Average 35744808.02      
Minimum of Months 0.00 0.00   4.67
Maximum of Months 12844534.59 775.22   29.40



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.147273E+11 14185.34 02-JAN-20:10 0.127587E+11 10113.80 02-JAN-20:10
February 0.132974E+11 14185.34 01-FEB-20:10 0.115208E+11 10113.80 01-FEB-20:10
March 0.147727E+11 14185.34 01-MAR-20:10 0.127855E+11 10113.80 01-MAR-20:10
April 0.142280E+11 14185.34 03-APR-19:10 0.123314E+11 10113.80 03-APR-19:10
May 0.147528E+11 14185.34 01-MAY-19:10 0.127741E+11 10113.80 01-MAY-19:10
June 0.142932E+11 14185.34 01-JUN-19:10 0.123716E+11 10113.80 01-JUN-19:10
July 0.146876E+11 14185.34 03-JUL-19:10 0.127338E+11 10113.80 03-JUL-19:10
August 0.147784E+11 14185.34 01-AUG-19:10 0.127894E+11 10113.80 01-AUG-19:10
September 0.142337E+11 14185.34 01-SEP-19:10 0.123352E+11 10113.80 01-SEP-19:10
October 0.147216E+11 14185.34 02-OCT-19:10 0.127549E+11 10113.80 02-OCT-19:10
November 0.142819E+11 14185.34 01-NOV-19:10 0.123659E+11 10113.80 01-NOV-19:10
December 0.146876E+11 14185.34 01-DEC-20:10 0.127338E+11 10113.80 01-DEC-20:10
             
Annual Sum or Average 0.173462E+12     0.150255E+12    
Minimum of Months 0.132974E+11 14185.34   0.115208E+11 10113.80  
Maximum of Months 0.147784E+11 14185.34   0.127894E+11 10113.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.731324E+09 704.41 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.660319E+09 704.41 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.733578E+09 704.41 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.706528E+09 704.41 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.732592E+09 704.41 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.709769E+09 704.41 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.729351E+09 704.41 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.733860E+09 704.41 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.706810E+09 704.41 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.731042E+09 704.41 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.709205E+09 704.41 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.729351E+09 704.41 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.861373E+10     0.101856E+11    
Minimum of Months 0.660319E+09 704.41   0.780982E+09 685.60  
Maximum of Months 0.733860E+09 704.41   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.846876E+09 815.72 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.764651E+09 815.72 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.849486E+09 815.72 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.818162E+09 815.72 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.848344E+09 815.72 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.821915E+09 815.72 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.844592E+09 815.72 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.849812E+09 815.72 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.818489E+09 815.72 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.846549E+09 815.72 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.821262E+09 815.72 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.844592E+09 815.72 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.997473E+10     0.117950E+11    
Minimum of Months 0.764651E+09 815.72   0.904380E+09 793.93  
Maximum of Months 0.849812E+09 815.72   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.141236E+10 1360.40 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.127524E+10 1360.40 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.141672E+10 1360.40 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.136448E+10 1360.40 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.141481E+10 1360.40 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.137074E+10 1360.40 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.140855E+10 1360.40 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.141726E+10 1360.40 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.136502E+10 1360.40 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.141182E+10 1360.40 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.136965E+10 1360.40 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.140855E+10 1360.40 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.166352E+11     0.124712E+11    
Minimum of Months 0.127524E+10 1360.40   0.956227E+09 839.45  
Maximum of Months 0.141726E+10 1360.40   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.236418E+09 227.72 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.213464E+09 227.72 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.237147E+09 227.72 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.228402E+09 227.72 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.236828E+09 227.72 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.229450E+09 227.72 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.235780E+09 227.72 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.237238E+09 227.72 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.228493E+09 227.72 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.236327E+09 227.72 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.229268E+09 227.72 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.235780E+09 227.72 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.278459E+10     0.359760E+10    
Minimum of Months 0.213464E+09 227.72   0.275845E+09 242.16  
Maximum of Months 0.237238E+09 227.72   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.370859E+09 357.21 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.334852E+09 357.21 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.372002E+09 357.21 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.358285E+09 357.21 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.371502E+09 357.21 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.359929E+09 357.21 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.369859E+09 357.21 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.372145E+09 357.21 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.358428E+09 357.21 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.370717E+09 357.21 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.359643E+09 357.21 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.369859E+09 357.21 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.436808E+10     0.679355E+11    
Minimum of Months 0.334852E+09 357.21   0.520895E+10 4572.80  
Maximum of Months 0.372145E+09 357.21   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.159294E+10 1761.91 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.143108E+10 1761.91 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.154290E+10 1761.91 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.145732E+10 1761.91 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.147737E+10 1761.91 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.139399E+10 1761.91 01-JUN-19:19 0.118076E+10 965.27 01-JUN-19:10
July 0.144497E+10 1761.91 03-JUL-19:19 0.121533E+10 965.27 03-JUL-19:10
August 0.150962E+10 1761.91 01-AUG-19:10 0.122063E+10 965.27 01-AUG-19:10
September 0.147581E+10 1761.91 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.155966E+10 1761.91 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.153501E+10 1761.91 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.159453E+10 1761.91 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.180152E+11     0.143405E+11    
Minimum of Months 0.139399E+10 1761.91   0.109956E+10 965.27  
Maximum of Months 0.159453E+10 1761.91   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104129E+11 10265.18 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.939735E+10 10265.18 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.103980E+11 10265.18 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.998436E+10 10265.18 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.103221E+11 10265.18 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.996525E+10 10265.18 01-JUN-19:19 0.122682E+11 10029.21 01-JUN-19:10
July 0.102538E+11 10265.18 03-JUL-19:19 0.126273E+11 10029.21 03-JUL-19:10
August 0.103718E+11 10265.18 01-AUG-19:10 0.126824E+11 10029.21 01-AUG-19:10
September 0.100094E+11 10265.18 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.103797E+11 10265.18 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.100899E+11 10265.18 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.103912E+11 10265.18 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.121976E+12     0.148998E+12    
Minimum of Months 0.939735E+10 10265.18   0.114244E+11 10029.21  
Maximum of Months 0.104129E+11 10265.18   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85091918.49 76.99 01-JAN-19:10 0.255708E+09 232.19 01-JAN-08:09
February 76846309.13 76.99 01-FEB-20:10 0.230956E+09 232.19 01-FEB-07:10
March 84415649.14 76.99 01-MAR-20:10 0.255355E+09 232.19 01-MAR-07:10
April 82445007.08 76.99 01-APR-18:10 0.247516E+09 232.19 01-APR-07:10
May 84753783.81 76.99 01-MAY-19:10 0.255532E+09 232.19 01-MAY-06:10
June 81790910.76 76.99 01-JUN-19:10 0.247163E+09 232.19 01-JUN-06:10
July 85418966.65 76.99 01-JUL-18:10 0.255885E+09 232.19 01-JUL-07:10
August 84415649.14 76.99 01-AUG-19:10 0.255355E+09 232.19 01-AUG-06:10
September 82467180.11 76.99 01-SEP-19:10 0.247516E+09 232.19 01-SEP-06:10
October 85080831.98 76.99 01-OCT-18:10 0.255708E+09 232.19 01-OCT-07:10
November 82117958.92 76.99 01-NOV-19:10 0.247340E+09 232.19 01-NOV-06:10
December 85430053.17 76.99 01-DEC-20:10 0.255885E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.100027E+10     0.300992E+10    
Minimum of Months 76846309.13 76.99   0.230956E+09 232.19  
Maximum of Months 85430053.17 76.99   0.255885E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85115186.72 77.01 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 76867322.62 77.01 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 84438732.44 77.01 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 82467551.52 77.01 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 84776959.58 77.01 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 81813276.33 77.01 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 85442324.32 77.01 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 84438732.44 77.01 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 82489730.61 77.01 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 85104097.18 77.01 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 82140413.93 77.01 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 85453413.86 77.01 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.100055E+10     0.301074E+10    
Minimum of Months 76867322.62 77.01   0.231020E+09 232.26  
Maximum of Months 85453413.86 77.01   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.232638E+10 2240.78 02-JAN-20:10 0.00 0.00
February 0.210051E+10 2240.78 01-FEB-20:10 0.00 0.00
March 0.233355E+10 2240.78 01-MAR-20:10 0.00 0.00
April 0.224750E+10 2240.78 03-APR-19:10 0.00 0.00
May 0.233041E+10 2240.78 01-MAY-19:10 0.00 0.00
June 0.225781E+10 2240.78 01-JUN-19:10 0.00 0.00
July 0.232011E+10 2240.78 03-JUL-19:10 0.00 0.00
August 0.233445E+10 2240.78 01-AUG-19:10 0.00 0.00
September 0.224840E+10 2240.78 01-SEP-19:10 0.00 0.00
October 0.232548E+10 2240.78 02-OCT-19:10 0.00 0.00
November 0.225602E+10 2240.78 01-NOV-19:10 0.00 0.00
December 0.232011E+10 2240.78 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.274007E+11     0.00 0.00
Minimum of Months 0.210051E+10 2240.78   0.00 0.00
Maximum of Months 0.233445E+10 2240.78   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135397E+09 122.50 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.122277E+09 122.50 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.134321E+09 122.50 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.131185E+09 122.50 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.134859E+09 122.50 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.130145E+09 122.50 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.135918E+09 122.50 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.134321E+09 122.50 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.131221E+09 122.50 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.135380E+09 122.50 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.130665E+09 122.50 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.135935E+09 122.50 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.159162E+10     0.307301E+10    
Minimum of Months 0.122277E+09 122.50   0.235798E+09 237.06  
Maximum of Months 0.135935E+09 122.50   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.135381E+09 122.49 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.122263E+09 122.49 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.134305E+09 122.49 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.131170E+09 122.49 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.134843E+09 122.49 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.130129E+09 122.49 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.135902E+09 122.49 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.134305E+09 122.49 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.131205E+09 122.49 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.135364E+09 122.49 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.130650E+09 122.49 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.135919E+09 122.49 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.159144E+10     0.307265E+10    
Minimum of Months 0.122263E+09 122.49   0.235770E+09 237.03  
Maximum of Months 0.135919E+09 122.49   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 85115186.72 77.01 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 76867322.62 77.01 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 84438732.44 77.01 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 82467551.52 77.01 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 84776959.58 77.01 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 81813276.33 77.01 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 85442324.32 77.01 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 84438732.44 77.01 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 82489730.61 77.01 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 85104097.18 77.01 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 82140413.93 77.01 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 85453413.86 77.01 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.100055E+10     0.301074E+10    
Minimum of Months 76867322.62 77.01   0.231020E+09 232.26  
Maximum of Months 85453413.86 77.01   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.304304E+10 3094.06 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.273166E+10 3094.06 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.297608E+10 3094.06 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.282542E+10 3094.06 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.288543E+10 3094.06 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.275467E+10 3094.06 01-JUN-19:19 0.144540E+11 6747.90 01-JUN-06:10
July 0.284709E+10 3094.06 03-JUL-19:30 0.149358E+11 6747.90 01-JUL-06:10
August 0.292786E+10 3094.06 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.284897E+10 3094.06 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.301378E+10 3094.06 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.293842E+10 3094.06 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.303738E+10 3094.06 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.348298E+11     0.175857E+12    
Minimum of Months 0.273166E+10 3094.06   0.134904E+11 6747.90  
Maximum of Months 0.304304E+10 3094.06   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.304304E+10 3094.06 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.273166E+10 3094.06 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.297608E+10 3094.06 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.282542E+10 3094.06 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.288543E+10 3094.06 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.275467E+10 3094.06 01-JUN-19:19 0.144540E+11 6747.90 01-JUN-06:10
July 0.284709E+10 3094.06 03-JUL-19:30 0.149358E+11 6747.90 01-JUL-06:10
August 0.292786E+10 3094.06 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.284897E+10 3094.06 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.301378E+10 3094.06 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.293842E+10 3094.06 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.303738E+10 3094.06 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.348298E+11     0.175857E+12    
Minimum of Months 0.273166E+10 3094.06   0.134904E+11 6747.90  
Maximum of Months 0.304304E+10 3094.06   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.113146E+10 1089.83 02-JAN-20:10 0.368383E+11 16487.34 01-JAN-07:10
February 0.102161E+10 1089.83 01-FEB-20:10 0.332733E+11 16487.34 01-FEB-07:10
March 0.113495E+10 1089.83 01-MAR-20:10 0.368383E+11 16487.34 01-MAR-07:10
April 0.109310E+10 1089.83 03-APR-19:10 0.356500E+11 16487.34 01-APR-06:10
May 0.113342E+10 1089.83 01-MAY-19:10 0.368383E+11 16487.34 01-MAY-06:10
June 0.109811E+10 1089.83 01-JUN-19:10 0.356500E+11 16487.34 01-JUN-06:10
July 0.112841E+10 1089.83 03-JUL-19:10 0.368383E+11 16487.34 01-JUL-06:10
August 0.113539E+10 1089.83 01-AUG-19:10 0.368383E+11 16487.34 01-AUG-06:10
September 0.109354E+10 1089.83 01-SEP-19:10 0.356500E+11 16487.34 01-SEP-06:10
October 0.113103E+10 1089.83 02-OCT-19:10 0.368383E+11 16487.34 01-OCT-06:10
November 0.109724E+10 1089.83 01-NOV-19:10 0.356500E+11 16487.34 01-NOV-06:10
December 0.112841E+10 1089.83 01-DEC-20:10 0.368383E+11 16487.34 01-DEC-07:10
             
Annual Sum or Average 0.133267E+11     0.433742E+12    
Minimum of Months 0.102161E+10 1089.83   0.332733E+11 16487.34  
Maximum of Months 0.113539E+10 1089.83   0.368383E+11 16487.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.246211E+10 2371.52 02-JAN-20:10 0.00 0.00
February 0.222306E+10 2371.52 01-FEB-20:10 0.00 0.00
March 0.246970E+10 2371.52 01-MAR-20:10 0.00 0.00
April 0.237864E+10 2371.52 03-APR-19:10 0.00 0.00
May 0.246638E+10 2371.52 01-MAY-19:10 0.00 0.00
June 0.238954E+10 2371.52 01-JUN-19:10 0.00 0.00
July 0.245547E+10 2371.52 03-JUL-19:10 0.00 0.00
August 0.247065E+10 2371.52 01-AUG-19:10 0.00 0.00
September 0.237958E+10 2371.52 01-SEP-19:10 0.00 0.00
October 0.246116E+10 2371.52 02-OCT-19:10 0.00 0.00
November 0.238765E+10 2371.52 01-NOV-19:10 0.00 0.00
December 0.245547E+10 2371.52 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.289994E+11     0.00 0.00
Minimum of Months 0.222306E+10 2371.52   0.00 0.00
Maximum of Months 0.247065E+10 2371.52   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.147273E+11 0.127587E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.132974E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.147727E+11 0.127855E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.142280E+11 0.123314E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.147528E+11 0.127741E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.142932E+11 0.123716E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.146876E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.147784E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.142337E+11 0.123352E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.147216E+11 0.127549E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.142819E+11 0.123659E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.146876E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.173462E+12 0.150255E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.132974E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.147784E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.731324E+09 0.864900E+09 0.00 0.00 0.00 0.00 4169483.99 0.456402E+09
February 0.179968E+10 0.660319E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.466116E+09
March 0.199990E+10 0.733578E+09 0.866718E+09 0.00 0.00 0.00 0.00 9655175.04 0.401698E+09
April 0.192973E+10 0.706528E+09 0.835931E+09 0.00 0.00 0.00 0.00 0.111264E+09 0.139290E+09
May 0.199475E+10 0.732592E+09 0.865939E+09 0.00 0.00 0.00 0.00 0.190354E+09 73026696.37
June 0.193394E+10 0.709769E+09 0.838659E+09 0.00 0.00 0.00 0.00 0.356652E+09 13335568.10
July 0.199054E+10 0.729351E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.328187E+09 8302633.26
August 0.199896E+10 0.733860E+09 0.866978E+09 0.00 0.00 0.00 0.00 0.302256E+09 12667101.21
September 0.192879E+10 0.706810E+09 0.836191E+09 0.00 0.00 0.00 0.00 0.209578E+09 27874603.49
October 0.199148E+10 0.731042E+09 0.864640E+09 0.00 0.00 0.00 0.00 77209875.55 0.226749E+09
November 0.192552E+10 0.709205E+09 0.838269E+09 0.00 0.00 0.00 0.00 7215153.84 0.409426E+09
December 0.199054E+10 0.729351E+09 0.863211E+09 0.00 0.00 0.00 0.00 1048198.68 0.585545E+09
                   
Annual Sum or Average 0.234744E+11 0.861373E+10 0.101856E+11 0.00 0.00 0.00 0.00 0.159759E+10 0.282043E+10
Minimum of Months 0.179968E+10 0.660319E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 8302633.26
Maximum of Months 0.199990E+10 0.733860E+09 0.866978E+09 0.00 0.00 0.00 0.00 0.356652E+09 0.585545E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.846876E+09 0.100156E+10 0.00 0.00 0.00 0.00 3024294.80 0.178222E+09
February 0.208403E+10 0.764651E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 0.185937E+09
March 0.231589E+10 0.849486E+09 0.100366E+10 0.00 0.00 0.00 0.00 5525871.73 0.161802E+09
April 0.223463E+10 0.818162E+09 0.968011E+09 0.00 0.00 0.00 0.00 45930866.02 56832321.43
May 0.230993E+10 0.848344E+09 0.100276E+10 0.00 0.00 0.00 0.00 76085487.56 29922504.33
June 0.223950E+10 0.821915E+09 0.971170E+09 0.00 0.00 0.00 0.00 0.138595E+09 5163921.69
July 0.230505E+10 0.844592E+09 0.999601E+09 0.00 0.00 0.00 0.00 0.128031E+09 3295839.76
August 0.231480E+10 0.849812E+09 0.100396E+10 0.00 0.00 0.00 0.00 0.118078E+09 5059055.68
September 0.223354E+10 0.818489E+09 0.968312E+09 0.00 0.00 0.00 0.00 82425280.48 10999838.83
October 0.230614E+10 0.846549E+09 0.100126E+10 0.00 0.00 0.00 0.00 31526728.51 89499551.40
November 0.222975E+10 0.821262E+09 0.970719E+09 0.00 0.00 0.00 0.00 3990644.13 0.161151E+09
December 0.230505E+10 0.844592E+09 0.999601E+09 0.00 0.00 0.00 0.00 965307.67 0.229794E+09
                   
Annual Sum or Average 0.271834E+11 0.997473E+10 0.117950E+11 0.00 0.00 0.00 0.00 0.634179E+09 0.111768E+10
Minimum of Months 0.208403E+10 0.764651E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 3295839.76
Maximum of Months 0.231589E+10 0.849812E+09 0.100396E+10 0.00 0.00 0.00 0.00 0.138595E+09 0.229794E+09



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.141236E+10 0.105898E+10 0.00 0.00 0.00 0.00 10197104.44 0.390972E+09
February 0.440737E+09 0.127524E+10 0.956227E+09 0.00 0.00 0.00 0.00 0.00 0.415176E+09
March 0.489771E+09 0.141672E+10 0.106120E+10 0.00 0.00 0.00 0.00 13398798.03 0.364170E+09
April 0.472586E+09 0.136448E+10 0.102351E+10 0.00 0.00 0.00 0.00 0.105450E+09 0.133068E+09
May 0.488511E+09 0.141481E+10 0.106025E+10 0.00 0.00 0.00 0.00 0.173709E+09 71108493.79
June 0.473617E+09 0.137074E+10 0.102685E+10 0.00 0.00 0.00 0.00 0.325351E+09 12211803.97
July 0.487480E+09 0.140855E+10 0.105691E+10 0.00 0.00 0.00 0.00 0.299355E+09 7833300.01
August 0.489542E+09 0.141726E+10 0.106152E+10 0.00 0.00 0.00 0.00 0.275746E+09 12138094.47
September 0.472357E+09 0.136502E+10 0.102382E+10 0.00 0.00 0.00 0.00 0.191215E+09 26314553.70
October 0.487709E+09 0.141182E+10 0.105866E+10 0.00 0.00 0.00 0.00 73659788.95 0.206806E+09
November 0.471555E+09 0.136965E+10 0.102637E+10 0.00 0.00 0.00 0.00 11212719.96 0.360290E+09
December 0.487480E+09 0.140855E+10 0.105691E+10 0.00 0.00 0.00 0.00 3609734.44 0.504127E+09
                   
Annual Sum or Average 0.574883E+10 0.166352E+11 0.124712E+11 0.00 0.00 0.00 0.00 0.148290E+10 0.250422E+10
Minimum of Months 0.440737E+09 0.127524E+10 0.956227E+09 0.00 0.00 0.00 0.00 0.00 7833300.01
Maximum of Months 0.489771E+09 0.141726E+10 0.106152E+10 0.00 0.00 0.00 0.00 0.325351E+09 0.504127E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.236418E+09 0.305485E+09 0.00 0.00 0.00 0.00 9352404.37 0.200716E+09
February 0.339028E+09 0.213464E+09 0.275845E+09 0.00 0.00 0.00 0.00 58436.66 0.215431E+09
March 0.376747E+09 0.237147E+09 0.306128E+09 0.00 0.00 0.00 0.00 11633860.39 0.184582E+09
April 0.363528E+09 0.228402E+09 0.295253E+09 0.00 0.00 0.00 0.00 74006757.58 63070385.59
May 0.375778E+09 0.236828E+09 0.305852E+09 0.00 0.00 0.00 0.00 0.112360E+09 33396054.53
June 0.364321E+09 0.229450E+09 0.296217E+09 0.00 0.00 0.00 0.00 0.190961E+09 6000877.30
July 0.374985E+09 0.235780E+09 0.304889E+09 0.00 0.00 0.00 0.00 0.177754E+09 3776606.68
August 0.376571E+09 0.237238E+09 0.306219E+09 0.00 0.00 0.00 0.00 0.166150E+09 5046805.81
September 0.363352E+09 0.228493E+09 0.295345E+09 0.00 0.00 0.00 0.00 0.119398E+09 11135488.91
October 0.375161E+09 0.236327E+09 0.305393E+09 0.00 0.00 0.00 0.00 50359525.73 0.100203E+09
November 0.362735E+09 0.229268E+09 0.296079E+09 0.00 0.00 0.00 0.00 9789601.11 0.181532E+09
December 0.374985E+09 0.235780E+09 0.304889E+09 0.00 0.00 0.00 0.00 3429950.22 0.270030E+09
                   
Annual Sum or Average 0.442217E+10 0.278459E+10 0.359760E+10 0.00 0.00 0.00 0.00 0.925253E+09 0.127492E+10
Minimum of Months 0.339028E+09 0.213464E+09 0.275845E+09 0.00 0.00 0.00 0.00 58436.66 3776606.68
Maximum of Months 0.376747E+09 0.237238E+09 0.306219E+09 0.00 0.00 0.00 0.00 0.190961E+09 0.270030E+09



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.370859E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 5193360.02 0.618829E+09
February 0.139600E+10 0.334852E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.676260E+09
March 0.155131E+10 0.372002E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 11731336.84 0.581146E+09
April 0.149688E+10 0.358285E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 0.138440E+09 0.188621E+09
May 0.154732E+10 0.371502E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 0.236896E+09 97268815.49
June 0.150015E+10 0.359929E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 0.444221E+09 16667829.09
July 0.154405E+10 0.369859E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.408729E+09 10689369.03
August 0.155059E+10 0.372145E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.376383E+09 16624691.08
September 0.149615E+10 0.358428E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 0.260995E+09 35924376.72
October 0.154478E+10 0.370717E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 96155682.60 0.307501E+09
November 0.149361E+10 0.359643E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 8703748.38 0.559732E+09
December 0.154405E+10 0.369859E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 1302803.21 0.816725E+09
                   
Annual Sum or Average 0.182090E+11 0.436808E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 0.198875E+10 0.392599E+10
Minimum of Months 0.139600E+10 0.334852E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 10689369.03
Maximum of Months 0.155131E+10 0.372145E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.444221E+09 0.816725E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.159294E+10 0.121771E+10 0.00 0.00 0.00 0.00 9745945.17 0.995059E+09
February 0.236489E+11 0.143108E+10 0.109956E+10 0.00 0.00 0.00 0.00 3814.11 0.102384E+10
March 0.262800E+11 0.154290E+10 0.122027E+10 0.00 0.00 0.00 0.00 33644895.34 0.859250E+09
April 0.253579E+11 0.145732E+10 0.117692E+10 0.00 0.00 0.00 0.00 0.282425E+09 0.285410E+09
May 0.262123E+11 0.147737E+10 0.121917E+10 0.00 0.00 0.00 0.00 0.484536E+09 0.145004E+09
June 0.254132E+11 0.139399E+10 0.118076E+10 0.00 0.00 0.00 0.00 0.837514E+09 25263452.11
July 0.261570E+11 0.144497E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.779294E+09 15482352.67
August 0.262677E+11 0.150962E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.710016E+09 22057340.24
September 0.253456E+11 0.147581E+10 0.117729E+10 0.00 0.00 0.00 0.00 0.493896E+09 51429929.55
October 0.261693E+11 0.155966E+10 0.121734E+10 0.00 0.00 0.00 0.00 0.179712E+09 0.476942E+09
November 0.253025E+11 0.153501E+10 0.118021E+10 0.00 0.00 0.00 0.00 19592597.43 0.884581E+09
December 0.261570E+11 0.159453E+10 0.121533E+10 0.00 0.00 0.00 0.00 2761454.27 0.129522E+10
                   
Annual Sum or Average 0.308468E+12 0.180152E+11 0.143405E+11 0.00 0.00 0.00 0.00 0.383314E+10 0.607954E+10
Minimum of Months 0.236489E+11 0.139399E+10 0.109956E+10 0.00 0.00 0.00 0.00 3814.11 15482352.67
Maximum of Months 0.262800E+11 0.159453E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.837514E+09 0.129522E+10



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.104129E+11 0.126520E+11 0.00 0.00 0.00 0.00 37844542.33 0.298799E+10
February 0.702046E+11 0.939735E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.313586E+10
March 0.780153E+11 0.103980E+11 0.126786E+11 0.00 0.00 0.00 0.00 88702962.70 0.270178E+10
April 0.752779E+11 0.998436E+10 0.122282E+11 0.00 0.00 0.00 0.00 0.770098E+09 0.923649E+09
May 0.778146E+11 0.103221E+11 0.126672E+11 0.00 0.00 0.00 0.00 0.128421E+10 0.483969E+09
June 0.754422E+11 0.996525E+10 0.122682E+11 0.00 0.00 0.00 0.00 0.230074E+10 84134852.70
July 0.776503E+11 0.102538E+11 0.126273E+11 0.00 0.00 0.00 0.00 0.212411E+10 53867117.81
August 0.779788E+11 0.103718E+11 0.126824E+11 0.00 0.00 0.00 0.00 0.195532E+10 82258032.93
September 0.752414E+11 0.100094E+11 0.122320E+11 0.00 0.00 0.00 0.00 0.136137E+10 0.178128E+09
October 0.776868E+11 0.103797E+11 0.126482E+11 0.00 0.00 0.00 0.00 0.510889E+09 0.148532E+10
November 0.751137E+11 0.100899E+11 0.122624E+11 0.00 0.00 0.00 0.00 58965790.76 0.269267E+10
December 0.776503E+11 0.103912E+11 0.126273E+11 0.00 0.00 0.00 0.00 11537954.61 0.387429E+10
                   
Annual Sum or Average 0.915726E+12 0.121976E+12 0.148998E+12 0.00 0.00 0.00 0.00 0.105038E+11 0.186839E+11
Minimum of Months 0.702046E+11 0.939735E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 53867117.81
Maximum of Months 0.780153E+11 0.104129E+11 0.126824E+11 0.00 0.00 0.00 0.00 0.230074E+10 0.387429E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 6171147.24 0.219087E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 4191.14 0.242643E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 10956836.29 0.200715E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 93982425.70 51779716.83
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 0.150917E+09 19566629.51
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.262318E+09 983522.24
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.251217E+09 781795.46
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.233837E+09 1007033.65
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.171986E+09 3403587.57
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 65852887.73 95178702.03
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 8305795.28 0.194613E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 1715091.54 0.304176E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.125726E+10 0.133394E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 4191.14 781795.46
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.262318E+09 0.304176E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 8249673.51 0.212646E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 12638.12 0.236099E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 11724471.78 0.196880E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 94362706.74 51520633.51
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 0.150934E+09 19590036.03
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.262181E+09 983424.07
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.251157E+09 781817.20
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.233908E+09 1003611.97
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.172215E+09 3370066.42
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 66744161.15 92644486.57
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 9462653.89 0.189551E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 2857760.71 0.294397E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.126381E+10 0.129947E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 12638.12 781817.20
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.262181E+09 0.294397E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 85091918.49 0.255708E+09 0.00 0.00 0.00 0.00 1105622.38 74021659.41
February 0.00 76846309.13 0.230956E+09 0.00 0.00 0.00 0.00 0.00 77640325.97
March 0.00 84415649.14 0.255355E+09 0.00 0.00 0.00 0.00 2009997.05 66115880.24
April 0.00 82445007.08 0.247516E+09 0.00 0.00 0.00 0.00 20460553.01 21411484.91
May 0.00 84753783.81 0.255532E+09 0.00 0.00 0.00 0.00 34093871.84 10515297.51
June 0.00 81790910.76 0.247163E+09 0.00 0.00 0.00 0.00 62012425.68 1525725.50
July 0.00 85418966.65 0.255885E+09 0.00 0.00 0.00 0.00 57846520.73 983647.99
August 0.00 84415649.14 0.255355E+09 0.00 0.00 0.00 0.00 53381877.86 1460423.60
September 0.00 82467180.11 0.247516E+09 0.00 0.00 0.00 0.00 37675843.27 3404949.17
October 0.00 85080831.98 0.255708E+09 0.00 0.00 0.00 0.00 14242326.31 35783816.68
November 0.00 82117958.92 0.247340E+09 0.00 0.00 0.00 0.00 1580872.13 66050206.90
December 0.00 85430053.17 0.255885E+09 0.00 0.00 0.00 0.00 299397.20 97353527.83
                   
Annual Sum or Average 0.00 0.100027E+10 0.300992E+10 0.00 0.00 0.00 0.00 0.284709E+09 0.456267E+09
Minimum of Months 0.00 76846309.13 0.230956E+09 0.00 0.00 0.00 0.00 0.00 983647.99
Maximum of Months 0.00 85430053.17 0.255885E+09 0.00 0.00 0.00 0.00 62012425.68 97353527.83



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 85115186.72 0.255778E+09 0.00 0.00 0.00 0.00 3442106.33 59006559.21
February 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 11010.79 66038491.56
March 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 3922048.36 54690428.08
April 0.293479E+09 82467551.52 0.247584E+09 0.00 0.00 0.00 0.00 27637459.71 14199038.25
May 0.303504E+09 84776959.58 0.255602E+09 0.00 0.00 0.00 0.00 43020298.06 5438102.95
June 0.293842E+09 81813276.33 0.247231E+09 0.00 0.00 0.00 0.00 73603030.68 274435.10
July 0.303141E+09 85442324.32 0.255955E+09 0.00 0.00 0.00 0.00 70535921.90 218158.94
August 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 65851080.88 263189.54
September 0.293479E+09 82489730.61 0.247584E+09 0.00 0.00 0.00 0.00 48807666.55 908493.22
October 0.303322E+09 85104097.18 0.255778E+09 0.00 0.00 0.00 0.00 19826162.42 25603826.15
November 0.293661E+09 82140413.93 0.247408E+09 0.00 0.00 0.00 0.00 3577616.04 52292756.07
December 0.303141E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 1254659.63 82136837.90
                   
Annual Sum or Average 0.357224E+10 0.100055E+10 0.301074E+10 0.00 0.00 0.00 0.00 0.361489E+09 0.361070E+09
Minimum of Months 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 11010.79 218158.94
Maximum of Months 0.303685E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 73603030.68 82136837.90



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 6171283.45 0.220939E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 4064.43 0.245630E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 10745772.37 0.203938E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 93714466.55 53019511.47
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 0.150428E+09 19946376.45
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.262022E+09 983651.75
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.250778E+09 786256.44
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.233463E+09 1077478.78
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.171734E+09 3607538.62
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 65797764.65 96763280.49
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 8238689.09 0.195835E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 1689926.41 0.305924E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.125479E+10 0.134845E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 4064.43 786256.44
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.262022E+09 0.305924E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 8251593.91 0.214267E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 4162.96 0.238946E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 11049576.31 0.200242E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 93773309.03 52976390.32
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 0.150424E+09 19948934.53
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.261931E+09 983607.70
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.250747E+09 786402.59
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.233481E+09 1072663.83
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.171816E+09 3594405.92
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 66232922.76 94987655.43
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 9351420.53 0.190145E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 2958537.34 0.295439E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.126002E+10 0.131339E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 4162.96 786402.59
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.261931E+09 0.295439E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.232638E+10 0.00 0.00 0.00 0.00 0.00 5449590.14 0.309383E+09
February 0.348285E+10 0.210051E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.322517E+09
March 0.387034E+10 0.233355E+10 0.00 0.00 0.00 0.00 0.00 9948779.07 0.281392E+09
April 0.373454E+10 0.224750E+10 0.00 0.00 0.00 0.00 0.00 80674274.49 0.101742E+09
May 0.386038E+10 0.233041E+10 0.00 0.00 0.00 0.00 0.00 0.133665E+09 54297400.07
June 0.374269E+10 0.225781E+10 0.00 0.00 0.00 0.00 0.00 0.249136E+09 9605267.49
July 0.385223E+10 0.232011E+10 0.00 0.00 0.00 0.00 0.00 0.229072E+09 6140597.35
August 0.386853E+10 0.233445E+10 0.00 0.00 0.00 0.00 0.00 0.211106E+09 9397021.69
September 0.373273E+10 0.224840E+10 0.00 0.00 0.00 0.00 0.00 0.146315E+09 20251230.76
October 0.385404E+10 0.232548E+10 0.00 0.00 0.00 0.00 0.00 54966932.93 0.161647E+09
November 0.372639E+10 0.225602E+10 0.00 0.00 0.00 0.00 0.00 7041830.20 0.283465E+09
December 0.385223E+10 0.232011E+10 0.00 0.00 0.00 0.00 0.00 1973925.71 0.398756E+09
                   
Annual Sum or Average 0.454292E+11 0.274007E+11 0.00 0.00 0.00 0.00 0.00 0.112935E+10 0.195859E+10
Minimum of Months 0.348285E+10 0.210051E+10 0.00 0.00 0.00 0.00 0.00 0.00 6140597.35
Maximum of Months 0.387034E+10 0.233445E+10 0.00 0.00 0.00 0.00 0.00 0.249136E+09 0.398756E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135397E+09 0.261068E+09 0.00 0.00 0.00 0.00 6019571.43 0.219140E+09
February 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 3464.01 0.242054E+09
March 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 10825451.13 0.200632E+09
April 0.293479E+09 0.131185E+09 0.252705E+09 0.00 0.00 0.00 0.00 93061699.90 52049539.19
May 0.303504E+09 0.134859E+09 0.260888E+09 0.00 0.00 0.00 0.00 0.149806E+09 19904950.19
June 0.293842E+09 0.130145E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.260715E+09 1043870.63
July 0.303141E+09 0.135918E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.249581E+09 824778.52
August 0.303685E+09 0.134321E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.232245E+09 1051178.19
September 0.293479E+09 0.131221E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.170596E+09 3447605.71
October 0.303322E+09 0.135380E+09 0.261068E+09 0.00 0.00 0.00 0.00 65217099.65 95173883.29
November 0.293661E+09 0.130665E+09 0.252524E+09 0.00 0.00 0.00 0.00 8215833.75 0.194564E+09
December 0.303141E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 1667170.83 0.303747E+09
                   
Annual Sum or Average 0.357224E+10 0.159162E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.124795E+10 0.133363E+10
Minimum of Months 0.273974E+09 0.122277E+09 0.235798E+09 0.00 0.00 0.00 0.00 3464.01 824778.52
Maximum of Months 0.303685E+09 0.135935E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.260715E+09 0.303747E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.135381E+09 0.261038E+09 0.00 0.00 0.00 0.00 8785582.50 0.212133E+09
February 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 20466.31 0.234871E+09
March 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 11665547.00 0.196522E+09
April 0.293479E+09 0.131170E+09 0.252675E+09 0.00 0.00 0.00 0.00 93409479.59 51779997.86
May 0.303504E+09 0.134843E+09 0.260857E+09 0.00 0.00 0.00 0.00 0.149808E+09 19925632.37
June 0.293842E+09 0.130129E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.260569E+09 1043757.85
July 0.303141E+09 0.135902E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.249517E+09 824720.87
August 0.303685E+09 0.134305E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.232334E+09 1047108.22
September 0.293479E+09 0.131205E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.170851E+09 3417718.71
October 0.303322E+09 0.135364E+09 0.261038E+09 0.00 0.00 0.00 0.00 66342273.63 92382130.17
November 0.293661E+09 0.130650E+09 0.252495E+09 0.00 0.00 0.00 0.00 9718261.15 0.188842E+09
December 0.303141E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 3114968.06 0.293119E+09
                   
Annual Sum or Average 0.357224E+10 0.159144E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.125613E+10 0.129591E+10
Minimum of Months 0.273974E+09 0.122263E+09 0.235770E+09 0.00 0.00 0.00 0.00 20466.31 824720.87
Maximum of Months 0.303685E+09 0.135919E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.260569E+09 0.293119E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 85115186.72 0.255778E+09 0.00 0.00 0.00 0.00 3015869.57 0.114531E+09
February 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 1543.74 0.127407E+09
March 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 5403053.11 0.104852E+09
April 0.293479E+09 82467551.52 0.247584E+09 0.00 0.00 0.00 0.00 47604814.76 26702214.11
May 0.303504E+09 84776959.58 0.255602E+09 0.00 0.00 0.00 0.00 76786831.65 10180141.04
June 0.293842E+09 81813276.33 0.247231E+09 0.00 0.00 0.00 0.00 0.133682E+09 533927.97
July 0.303141E+09 85442324.32 0.255955E+09 0.00 0.00 0.00 0.00 0.127815E+09 421901.92
August 0.303685E+09 84438732.44 0.255425E+09 0.00 0.00 0.00 0.00 0.118859E+09 537548.93
September 0.293479E+09 82489730.61 0.247584E+09 0.00 0.00 0.00 0.00 87182059.07 1798518.94
October 0.303322E+09 85104097.18 0.255778E+09 0.00 0.00 0.00 0.00 33213779.74 49713337.50
November 0.293661E+09 82140413.93 0.247408E+09 0.00 0.00 0.00 0.00 4044693.09 0.101450E+09
December 0.303141E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 817505.50 0.159397E+09
                   
Annual Sum or Average 0.357224E+10 0.100055E+10 0.301074E+10 0.00 0.00 0.00 0.00 0.638426E+09 0.697524E+09
Minimum of Months 0.273974E+09 76867322.62 0.231020E+09 0.00 0.00 0.00 0.00 1543.74 421901.92
Maximum of Months 0.303685E+09 85453413.86 0.255955E+09 0.00 0.00 0.00 0.00 0.133682E+09 0.159397E+09



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.304304E+10 0.149358E+11 0.00 0.00 0.00 0.00 17663587.31 0.637953E+09
February 0.415303E+11 0.273166E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.692120E+09
March 0.461508E+11 0.297608E+10 0.149358E+11 0.00 0.00 0.00 0.00 22523897.24 0.600666E+09
April 0.445315E+11 0.282542E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.182637E+09 0.204573E+09
May 0.460320E+11 0.288543E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.293620E+09 0.108737E+09
June 0.446286E+11 0.275467E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.521707E+09 19488178.39
July 0.459349E+11 0.284709E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.483191E+09 12468395.35
August 0.461292E+11 0.292786E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.449446E+09 18572575.36
September 0.445099E+11 0.284897E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.320113E+09 39729960.55
October 0.459565E+11 0.301378E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.130165E+09 0.320900E+09
November 0.444343E+11 0.293842E+10 0.144540E+11 0.00 0.00 0.00 0.00 20763050.36 0.578062E+09
December 0.459349E+11 0.303738E+10 0.149358E+11 0.00 0.00 0.00 0.00 5940955.67 0.838492E+09
                   
Annual Sum or Average 0.541708E+12 0.348298E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.244777E+10 0.407176E+10
Minimum of Months 0.415303E+11 0.273166E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 12468395.35
Maximum of Months 0.461508E+11 0.304304E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.521707E+09 0.838492E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.304304E+10 0.149358E+11 0.00 0.00 0.00 0.00 14664905.02 0.656711E+09
February 0.415303E+11 0.273166E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.715541E+09
March 0.461508E+11 0.297608E+10 0.149358E+11 0.00 0.00 0.00 0.00 19834782.38 0.620089E+09
April 0.445315E+11 0.282542E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.174067E+09 0.209325E+09
May 0.460320E+11 0.288543E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.284157E+09 0.110582E+09
June 0.446286E+11 0.275467E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.512717E+09 19778012.65
July 0.459349E+11 0.284709E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.473485E+09 12706003.49
August 0.461292E+11 0.292786E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.439749E+09 19224724.81
September 0.445099E+11 0.284897E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.310996E+09 40966568.35
October 0.459565E+11 0.301378E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.123940E+09 0.330484E+09
November 0.444343E+11 0.293842E+10 0.144540E+11 0.00 0.00 0.00 0.00 18085290.83 0.595702E+09
December 0.459349E+11 0.303738E+10 0.149358E+11 0.00 0.00 0.00 0.00 4714002.52 0.863350E+09
                   
Annual Sum or Average 0.541708E+12 0.348298E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.237641E+10 0.419446E+10
Minimum of Months 0.415303E+11 0.273166E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 12706003.49
Maximum of Months 0.461508E+11 0.304304E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.512717E+09 0.863350E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.113146E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 4982584.53 0.640183E+09
February 0.369574E+10 0.102161E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.698522E+09
March 0.410691E+10 0.113495E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 11442782.09 0.601007E+09
April 0.396281E+10 0.109310E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.138400E+09 0.195669E+09
May 0.409635E+10 0.113342E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.237710E+09 0.101508E+09
June 0.397146E+10 0.109811E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.447647E+09 17873272.10
July 0.408770E+10 0.112841E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.410955E+09 11530957.62
August 0.410499E+10 0.113539E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.378349E+09 17917705.10
September 0.396089E+10 0.109354E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 0.261657E+09 38274694.93
October 0.408962E+10 0.113103E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 96122325.03 0.318759E+09
November 0.395417E+10 0.109724E+10 0.322775E+11 0.295556E+11 0.00 0.00 0.00 8415541.26 0.578724E+09
December 0.408770E+10 0.112841E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 1224939.47 0.842569E+09
                   
Annual Sum or Average 0.482060E+11 0.133267E+11 0.392709E+12 0.359593E+12 0.00 0.00 0.00 0.199691E+10 0.406254E+10
Minimum of Months 0.369574E+10 0.102161E+10 0.301256E+11 0.275852E+11 0.00 0.00 0.00 0.00 11530957.62
Maximum of Months 0.410691E+10 0.113539E+10 0.333534E+11 0.305408E+11 0.00 0.00 0.00 0.447647E+09 0.842569E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.246211E+10 0.00 0.00 0.00 0.00 0.00 5380381.22 0.555948E+09
February 0.368610E+10 0.222306E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.580473E+09
March 0.409620E+10 0.246970E+10 0.00 0.00 0.00 0.00 0.00 12442767.47 0.510935E+09
April 0.395248E+10 0.237864E+10 0.00 0.00 0.00 0.00 0.00 0.135567E+09 0.182740E+09
May 0.408566E+10 0.246638E+10 0.00 0.00 0.00 0.00 0.00 0.232320E+09 97524282.65
June 0.396110E+10 0.238954E+10 0.00 0.00 0.00 0.00 0.00 0.437757E+09 17546820.12
July 0.407704E+10 0.245547E+10 0.00 0.00 0.00 0.00 0.00 0.401844E+09 11302371.98
August 0.409429E+10 0.247065E+10 0.00 0.00 0.00 0.00 0.00 0.369958E+09 17489583.08
September 0.395056E+10 0.237958E+10 0.00 0.00 0.00 0.00 0.00 0.255792E+09 37327803.31
October 0.407896E+10 0.246116E+10 0.00 0.00 0.00 0.00 0.00 94099779.71 0.287846E+09
November 0.394385E+10 0.238765E+10 0.00 0.00 0.00 0.00 0.00 8848129.31 0.507688E+09
December 0.407704E+10 0.245547E+10 0.00 0.00 0.00 0.00 0.00 1850675.04 0.705570E+09
                   
Annual Sum or Average 0.480803E+11 0.289994E+11 0.00 0.00 0.00 0.00 0.00 0.195586E+10 0.351239E+10
Minimum of Months 0.368610E+10 0.222306E+10 0.00 0.00 0.00 0.00 0.00 0.00 11302371.98
Maximum of Months 0.409620E+10 0.247065E+10 0.00 0.00 0.00 0.00 0.00 0.437757E+09 0.705570E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 14185.34 02-JAN-20:10 10113.80 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 14185.34 01-FEB-20:10 10113.80 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 14185.34 01-MAR-20:10 10113.80 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 14185.34 03-APR-19:10 10113.80 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 14185.34 01-MAY-19:10 10113.80 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 14185.34 01-JUN-19:10 10113.80 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 14185.34 03-JUL-19:10 10113.80 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 14185.34 01-AUG-19:10 10113.80 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 14185.34 01-SEP-19:10 10113.80 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 14185.34 02-OCT-19:10 10113.80 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 14185.34 01-NOV-19:10 10113.80 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 14185.34 01-DEC-20:10 10113.80 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   14185.34   10113.80   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   14185.34   10113.80   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 704.41 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 94.54 31-JAN-16:00 427.09 01-JAN-08:00
February 1169.53 01-FEB-00:10 704.41 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 346.02 01-FEB-07:30
March 1169.53 01-MAR-00:10 704.41 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 90.39 16-MAR-15:00 425.65 26-MAR-06:00
April 1169.53 01-APR-00:10 704.41 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 202.53 14-APR-16:00 286.95 21-APR-03:57
May 1169.53 01-MAY-00:10 704.41 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 238.26 31-MAY-17:00 218.78 01-MAY-04:00
June 1169.53 01-JUN-00:10 704.41 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 325.11 28-JUN-16:00 115.30 21-JUN-06:00
July 1169.53 01-JUL-00:10 704.41 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 292.68 19-JUL-13:00 117.48 01-JUL-06:00
August 1169.53 01-AUG-00:10 704.41 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 309.44 25-AUG-14:00 137.66 05-AUG-18:00
September 1169.53 01-SEP-00:10 704.41 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 262.26 08-SEP-15:00 130.07 22-SEP-06:00
October 1169.53 01-OCT-23:10 704.41 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 239.13 01-OCT-13:00 339.87 25-OCT-05:55
November 1169.53 01-NOV-00:10 704.41 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 94.14 01-NOV-15:00 438.25 23-NOV-06:40
December 1169.53 01-DEC-00:10 704.41 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 38.17 21-DEC-15:00 460.75 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   704.41   685.60   0.00 0.00 0.00 0.00 0.00   115.30  
Maximum of Months 1169.53   704.41   685.60   0.00 0.00 0.00 0.00 325.11   460.75  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 815.72 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 40.85 31-JAN-16:00 174.13 01-JAN-08:00
February 1354.32 01-FEB-00:10 815.72 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 146.21 01-FEB-07:30
March 1354.32 01-MAR-00:10 815.72 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 40.89 20-MAR-17:00 173.91 26-MAR-04:00
April 1354.32 01-APR-00:10 815.72 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 78.47 14-APR-15:00 122.32 21-APR-03:57
May 1354.32 01-MAY-00:10 815.72 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 92.51 15-MAY-17:00 91.44 01-MAY-04:00
June 1354.32 01-JUN-00:10 815.72 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 125.50 28-JUN-16:00 45.02 21-JUN-06:00
July 1354.32 01-JUL-00:10 815.72 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 114.87 19-JUL-13:00 45.35 01-JUL-06:00
August 1354.32 01-AUG-00:10 815.72 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 119.44 25-AUG-14:00 53.14 05-AUG-18:00
September 1354.32 01-SEP-00:10 815.72 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 101.23 08-SEP-15:00 55.87 22-SEP-06:00
October 1354.32 01-OCT-23:10 815.72 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 93.90 01-OCT-13:00 145.64 25-OCT-05:55
November 1354.32 01-NOV-00:10 815.72 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 38.53 01-NOV-15:00 183.51 23-NOV-06:30
December 1354.32 01-DEC-00:10 815.72 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 23.17 21-DEC-15:00 189.37 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   815.72   793.93   0.00 0.00 0.00 0.00 0.00   45.02  
Maximum of Months 1354.32   815.72   793.93   0.00 0.00 0.00 0.00 125.50   189.37  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 1360.40 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 105.82 31-JAN-16:30 389.61 01-JAN-08:00
February 286.42 01-FEB-00:10 1360.40 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 332.19 01-FEB-07:30
March 286.42 01-MAR-00:10 1360.40 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 96.57 16-MAR-15:30 401.61 26-MAR-04:00
April 286.42 01-APR-00:10 1360.40 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 184.76 14-APR-15:00 281.39 21-APR-04:10
May 286.42 01-MAY-00:10 1360.40 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 217.36 31-MAY-17:00 214.71 01-MAY-04:00
June 286.42 01-JUN-00:10 1360.40 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 296.59 28-JUN-16:00 106.42 21-JUN-06:00
July 286.42 01-JUL-00:10 1360.40 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 267.00 19-JUL-13:00 107.18 01-JUL-06:00
August 286.42 01-AUG-00:10 1360.40 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 282.29 25-AUG-14:00 125.60 05-AUG-18:00
September 286.42 01-SEP-00:10 1360.40 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 239.25 08-SEP-15:00 132.77 22-SEP-06:00
October 286.42 01-OCT-23:10 1360.40 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 218.15 01-OCT-13:00 335.81 25-OCT-05:55
November 286.42 01-NOV-00:10 1360.40 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 96.53 01-NOV-15:00 424.27 23-NOV-06:30
December 286.42 01-DEC-00:10 1360.40 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 69.09 21-DEC-15:00 431.16 05-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   1360.40   839.45   0.00 0.00 0.00 0.00 0.00   106.42  
Maximum of Months 286.42   1360.40   839.45   0.00 0.00 0.00 0.00 296.59   431.16  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 227.72 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 70.63 31-JAN-17:00 224.79 01-JAN-08:00
February 220.32 01-FEB-00:10 227.72 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 6.76 18-FEB-14:00 179.71 01-FEB-07:30
March 220.32 01-MAR-00:10 227.72 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 66.30 20-MAR-17:00 224.00 26-MAR-06:00
April 220.32 01-APR-00:10 227.72 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 114.54 14-APR-16:30 151.27 21-APR-03:57
May 220.32 01-MAY-00:10 227.72 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 133.43 15-MAY-17:00 113.35 01-MAY-04:00
June 220.32 01-JUN-00:10 227.72 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 171.50 16-JUN-16:00 57.86 21-JUN-06:00
July 220.32 01-JUL-00:10 227.72 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 156.30 19-JUL-13:00 59.90 01-JUL-06:00
August 220.32 01-AUG-00:10 227.72 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 165.74 25-AUG-16:40 64.03 05-AUG-18:00
September 220.32 01-SEP-00:10 227.72 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 140.29 08-SEP-16:00 67.39 22-SEP-06:00
October 220.32 01-OCT-23:10 227.72 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 130.33 01-OCT-13:00 181.69 25-OCT-05:55
November 220.32 01-NOV-00:10 227.72 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 65.86 01-NOV-15:00 232.63 23-NOV-06:00
December 220.32 01-DEC-00:10 227.72 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 47.27 21-DEC-15:00 242.50 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   227.72   242.16   0.00 0.00 0.00 0.00 6.76   57.86  
Maximum of Months 220.32   227.72   242.16   0.00 0.00 0.00 0.00 171.50   242.50  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 357.21 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 117.77 31-JAN-16:00 609.81 01-JAN-08:00
February 907.20 01-FEB-00:10 357.21 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 0.00 01-FEB-00:10 555.09 01-FEB-07:30
March 907.20 01-MAR-00:10 357.21 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 112.59 16-MAR-15:00 607.72 26-MAR-06:00
April 907.20 01-APR-00:10 357.21 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 252.28 14-APR-15:00 415.73 21-APR-03:53
May 907.20 01-MAY-00:10 357.21 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 296.78 31-MAY-17:00 296.72 01-MAY-04:00
June 907.20 01-JUN-00:10 357.21 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 404.96 28-JUN-16:00 145.31 21-JUN-06:00
July 907.20 01-JUL-00:10 357.21 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 364.58 19-JUL-13:00 146.35 01-JUL-06:00
August 907.20 01-AUG-00:10 357.21 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 385.45 25-AUG-14:00 171.49 05-AUG-18:00
September 907.20 01-SEP-00:10 357.21 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 326.69 08-SEP-15:00 181.28 22-SEP-06:00
October 907.20 01-OCT-23:10 357.21 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 297.89 01-OCT-13:00 539.04 25-OCT-06:30
November 907.20 01-NOV-00:10 357.21 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 117.31 01-NOV-15:00 623.84 23-NOV-06:10
December 907.20 01-DEC-00:10 357.21 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 47.55 21-DEC-15:00 652.09 05-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   357.21   4572.80   39726.58   0.00 0.00 0.00 0.00   145.31  
Maximum of Months 907.20   357.21   4572.80   39726.58   0.00 0.00 0.00 404.96   652.09  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 1761.91 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 209.06 31-JAN-17:00 966.01 01-JAN-08:00
February 15368.40 01-FEB-00:10 1761.91 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 4.37 18-FEB-16:00 798.20 01-FEB-05:10
March 15368.40 01-MAR-00:10 1761.91 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 245.02 20-MAR-17:00 941.10 26-MAR-06:00
April 15368.40 01-APR-00:10 1761.91 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 457.95 14-APR-17:00 679.91 21-APR-03:57
May 15368.40 01-MAY-00:10 1761.91 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 558.88 31-MAY-17:00 491.39 01-MAY-04:00
June 15368.40 01-JUN-00:10 1761.91 01-JUN-19:19 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 722.69 28-JUN-15:00 246.06 21-JUN-05:00
July 15368.40 01-JUL-00:10 1761.91 03-JUL-19:19 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 670.29 12-JUL-14:00 232.88 01-JUL-06:00
August 15368.40 01-AUG-00:10 1761.91 01-AUG-19:10 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 688.86 26-AUG-16:00 241.41 05-AUG-18:00
September 15368.40 01-SEP-00:10 1761.91 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 579.79 08-SEP-15:00 275.08 22-SEP-06:00
October 15368.40 01-OCT-23:10 1761.91 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 542.66 01-OCT-13:00 798.05 25-OCT-05:55
November 15368.40 01-NOV-00:10 1761.91 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 208.21 01-NOV-15:00 989.24 23-NOV-06:10
December 15368.40 01-DEC-00:10 1761.91 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 96.18 02-DEC-15:00 1061.49 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   1761.91   965.27   0.00 0.00 0.00 0.00 4.37   232.88  
Maximum of Months 15368.40   1761.91   965.27   0.00 0.00 0.00 0.00 722.69   1061.49  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 10265.18 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 632.73 31-JAN-16:00 2909.69 01-JAN-08:00
February 45622.98 01-FEB-00:10 10265.18 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2406.94 01-FEB-07:10
March 45622.98 01-MAR-00:10 10265.18 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 666.70 20-MAR-17:00 2884.15 26-MAR-05:40
April 45622.98 01-APR-00:10 10265.18 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 1300.61 14-APR-17:00 2039.92 21-APR-04:10
May 45622.98 01-MAY-00:10 10265.18 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 1549.41 15-MAY-17:00 1511.60 01-MAY-04:00
June 45622.98 01-JUN-00:10 10265.18 01-JUN-19:19 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 2055.27 28-JUN-15:00 736.59 21-JUN-06:00
July 45622.98 01-JUL-00:10 10265.18 03-JUL-19:19 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 1895.92 19-JUL-13:00 741.88 01-JUL-06:00
August 45622.98 01-AUG-00:10 10265.18 01-AUG-19:10 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 1969.57 26-AUG-16:00 848.57 05-AUG-18:00
September 45622.98 01-SEP-00:10 10265.18 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 1656.53 08-SEP-15:00 919.03 22-SEP-06:00
October 45622.98 01-OCT-23:10 10265.18 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 1548.98 01-OCT-13:00 2430.68 25-OCT-05:55
November 45622.98 01-NOV-00:10 10265.18 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 601.96 01-NOV-15:00 3031.63 23-NOV-06:30
December 45622.98 01-DEC-00:10 10265.18 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 331.64 21-DEC-15:00 3180.84 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   10265.18   10029.21   0.00 0.00 0.00 0.00 0.00   736.59  
Maximum of Months 45622.98   10265.18   10029.21   0.00 0.00 0.00 0.00 2055.27   3180.84  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 86.12 31-JAN-17:00 249.74 01-JAN-08:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 5.70 18-FEB-16:07 192.07 28-FEB-07:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 83.58 16-MAR-15:10 248.88 26-MAR-06:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 147.98 14-APR-16:00 154.25 21-APR-04:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 168.58 31-MAY-17:00 105.99 01-MAY-04:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 218.30 16-JUN-16:00 35.60 21-JUN-06:00
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 197.78 20-JUL-15:10 35.86 01-JUL-06:00
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 209.48 25-AUG-15:10 67.62 05-AUG-18:00
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 182.23 08-SEP-16:00 52.00 22-SEP-06:00
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 148.37 03-OCT-16:00 190.93 25-OCT-07:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 83.98 01-NOV-15:10 256.21 23-NOV-07:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 49.88 25-DEC-16:08 269.28 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 5.70   35.60  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 218.30   269.28  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 86.12 31-JAN-16:50 249.71 01-JAN-08:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 5.70 18-FEB-16:06 192.06 28-FEB-07:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 83.57 16-MAR-15:10 248.85 26-MAR-06:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 147.97 14-APR-16:00 154.24 21-APR-04:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 168.57 31-MAY-17:00 105.98 01-MAY-04:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 218.28 16-JUN-16:00 35.60 21-JUN-06:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 197.79 20-JUL-15:10 35.85 01-JUL-06:00
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 209.47 25-AUG-16:00 65.91 05-AUG-18:00
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 182.46 08-SEP-15:10 51.99 22-SEP-06:00
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 148.36 03-OCT-16:00 190.91 25-OCT-07:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 83.98 01-NOV-15:10 256.19 23-NOV-07:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 49.88 25-DEC-16:08 269.26 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 5.70   35.60  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 218.28   269.26  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 76.99 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 17.22 31-JAN-16:40 71.74 01-JAN-08:00
February 0.00 01-FEB-00:10 76.99 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 60.72 01-FEB-08:00
March 0.00 01-MAR-00:10 76.99 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 16.54 16-MAR-15:00 69.00 26-MAR-04:00
April 0.00 01-APR-00:10 76.99 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 34.66 14-APR-15:00 47.09 21-APR-03:51
May 0.00 01-MAY-00:10 76.99 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 40.44 31-MAY-17:00 35.64 01-MAY-04:00
June 0.00 01-JUN-00:10 76.99 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 54.48 28-JUN-16:00 16.91 21-JUN-05:00
July 0.00 01-JUL-00:10 76.99 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 49.25 19-JUL-13:00 16.21 01-JUL-06:00
August 0.00 01-AUG-00:10 76.99 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 51.95 25-AUG-14:00 19.88 05-AUG-18:00
September 0.00 01-SEP-00:10 76.99 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 44.33 08-SEP-15:00 19.75 22-SEP-06:00
October 0.00 01-OCT-00:10 76.99 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 40.58 01-OCT-14:00 58.58 25-OCT-07:00
November 0.00 01-NOV-00:10 76.99 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 17.15 01-NOV-15:00 73.56 23-NOV-06:20
December 0.00 01-DEC-00:10 76.99 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 8.11 21-DEC-15:00 76.87 05-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   76.99   232.19   0.00 0.00 0.00 0.00 0.00   16.21  
Maximum of Months 0.00   76.99   232.19   0.00 0.00 0.00 0.00 54.48   76.87  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 77.01 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 24.04 31-JAN-16:50 69.70 01-JAN-08:00
February 180.00 01-FEB-00:10 77.01 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 1.59 18-FEB-16:06 53.60 28-FEB-07:00
March 180.00 01-MAR-00:10 77.01 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 23.33 16-MAR-15:08 69.46 26-MAR-06:00
April 180.00 01-APR-00:10 77.01 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 41.30 14-APR-15:40 43.05 21-APR-03:51
May 180.00 01-MAY-00:10 77.01 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 47.05 31-MAY-17:00 29.58 01-MAY-04:00
June 180.00 01-JUN-00:10 77.01 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 60.98 28-JUN-16:00 9.94 21-JUN-06:00
July 180.00 01-JUL-00:10 77.01 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 55.21 20-JUL-15:10 10.01 01-JUL-06:00
August 180.00 01-AUG-00:10 77.01 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 58.46 25-AUG-15:10 16.24 05-AUG-18:00
September 180.00 01-SEP-00:10 77.01 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 50.93 08-SEP-15:10 14.51 22-SEP-06:00
October 180.00 01-OCT-00:10 77.01 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 41.41 03-OCT-16:00 53.29 25-OCT-07:00
November 180.00 01-NOV-00:10 77.01 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 23.44 01-NOV-15:08 71.51 23-NOV-07:00
December 180.00 01-DEC-00:10 77.01 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 15.41 21-DEC-15:00 75.15 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 1.59   9.94  
Maximum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 60.98   75.15  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 86.13 31-JAN-17:00 249.74 01-JAN-08:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 5.70 18-FEB-16:09 192.07 28-FEB-07:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 83.58 16-MAR-15:08 248.88 26-MAR-06:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 147.98 14-APR-15:09 154.25 21-APR-04:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 168.58 31-MAY-17:00 105.99 01-MAY-04:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 218.42 28-JUN-16:20 35.60 21-JUN-06:00
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 197.79 20-JUL-15:10 35.86 01-JUL-06:00
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 209.48 25-AUG-15:10 68.76 05-AUG-18:00
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 182.41 08-SEP-15:10 52.00 22-SEP-06:00
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 148.37 03-OCT-16:00 190.93 25-OCT-07:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 83.99 01-NOV-15:10 256.21 23-NOV-07:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 49.89 25-DEC-16:10 269.28 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 5.70   35.60  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 218.42   269.28  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 86.12 31-JAN-16:50 249.72 01-JAN-08:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 5.70 18-FEB-16:07 192.06 28-FEB-07:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 83.57 16-MAR-15:08 248.85 26-MAR-06:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 147.97 14-APR-16:00 154.24 21-APR-04:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 168.56 31-MAY-17:00 105.98 01-MAY-04:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 218.36 28-JUN-16:30 35.60 21-JUN-06:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 197.80 20-JUL-15:10 35.86 01-JUL-06:00
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 209.47 25-AUG-15:10 67.06 05-AUG-18:00
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 182.47 08-SEP-15:10 51.99 22-SEP-06:00
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 148.36 03-OCT-16:00 190.91 25-OCT-07:00
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 83.98 01-NOV-15:07 256.19 23-NOV-06:10
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 49.88 25-DEC-16:08 269.26 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 5.70   35.60  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 218.36   269.26  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 2240.78 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 72.28 31-JAN-16:00 303.75 01-JAN-08:00
February 2263.36 01-FEB-00:10 2240.78 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 257.65 01-FEB-07:30
March 2263.36 01-MAR-00:10 2240.78 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 74.09 16-MAR-15:00 314.41 26-MAR-04:00
April 2263.36 01-APR-00:10 2240.78 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 141.60 14-APR-15:00 219.83 21-APR-03:57
May 2263.36 01-MAY-00:10 2240.78 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 166.68 31-MAY-17:00 164.93 01-MAY-04:00
June 2263.36 01-JUN-00:10 2240.78 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 227.64 28-JUN-16:00 82.45 21-JUN-06:00
July 2263.36 01-JUL-00:10 2240.78 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 204.87 19-JUL-13:00 83.04 01-JUL-06:00
August 2263.36 01-AUG-00:10 2240.78 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 216.63 25-AUG-14:00 96.70 05-AUG-18:00
September 2263.36 01-SEP-00:10 2240.78 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 183.52 08-SEP-15:00 99.82 22-SEP-06:00
October 2263.36 01-OCT-23:10 2240.78 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 167.28 01-OCT-13:00 258.19 25-OCT-05:55
November 2263.36 01-NOV-00:10 2240.78 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 69.37 01-NOV-15:00 332.10 23-NOV-06:00
December 2263.36 01-DEC-00:10 2240.78 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 47.01 21-DEC-15:00 340.42 05-DEC-04:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   2240.78   0.00 0.00 0.00 0.00 0.00 0.00   82.45  
Maximum of Months 2263.36   2240.78   0.00 0.00 0.00 0.00 0.00 227.64   340.42  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.50 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 85.49 31-JAN-17:00 250.50 01-JAN-08:00
February 180.00 01-FEB-00:10 122.50 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 5.04 18-FEB-16:07 192.82 28-FEB-07:00
March 180.00 01-MAR-00:10 122.50 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 82.95 16-MAR-15:10 249.65 26-MAR-06:00
April 180.00 01-APR-00:10 122.50 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 147.37 14-APR-16:00 154.98 21-APR-04:00
May 180.00 01-MAY-00:10 122.50 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 167.98 31-MAY-17:00 106.70 01-MAY-04:00
June 180.00 01-JUN-00:10 122.50 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 217.72 16-JUN-16:00 36.28 21-JUN-06:00
July 180.00 01-JUL-00:10 122.50 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 195.74 20-JUL-15:10 36.54 01-JUL-06:00
August 180.00 01-AUG-00:10 122.50 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 208.89 25-AUG-15:10 66.11 05-AUG-18:00
September 180.00 01-SEP-00:10 122.50 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 181.50 08-SEP-16:00 52.68 22-SEP-06:00
October 180.00 01-OCT-00:10 122.50 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 147.76 03-OCT-16:00 191.67 25-OCT-07:00
November 180.00 01-NOV-00:10 122.50 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 83.35 01-NOV-15:10 256.98 23-NOV-07:00
December 180.00 01-DEC-00:10 122.50 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 49.24 25-DEC-16:08 270.06 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 5.04   36.28  
Maximum of Months 180.00   122.50   237.06   0.00 0.00 0.00 0.00 217.72   270.06  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 122.49 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 85.48 31-JAN-16:50 250.49 01-JAN-08:00
February 180.00 01-FEB-00:10 122.49 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 5.50 18-FEB-14:00 192.80 28-FEB-07:00
March 180.00 01-MAR-00:10 122.49 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 82.94 16-MAR-15:10 249.63 26-MAR-06:00
April 180.00 01-APR-00:10 122.49 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 147.36 14-APR-16:00 154.97 21-APR-04:00
May 180.00 01-MAY-00:10 122.49 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 167.97 31-MAY-17:00 106.69 01-MAY-04:00
June 180.00 01-JUN-00:10 122.49 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 217.70 16-JUN-16:00 36.28 21-JUN-06:00
July 180.00 01-JUL-00:10 122.49 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 196.32 20-JUL-15:10 36.54 01-JUL-06:00
August 180.00 01-AUG-00:10 122.49 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 208.87 25-AUG-15:10 64.15 05-AUG-18:00
September 180.00 01-SEP-00:10 122.49 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 181.80 08-SEP-15:10 52.68 22-SEP-06:00
October 180.00 01-OCT-00:10 122.49 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 147.75 03-OCT-16:00 191.65 25-OCT-06:43
November 180.00 01-NOV-00:10 122.49 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 83.35 01-NOV-15:10 256.96 23-NOV-07:00
December 180.00 01-DEC-00:10 122.49 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 49.24 25-DEC-16:07 270.04 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 5.50   36.28  
Maximum of Months 180.00   122.49   237.03   0.00 0.00 0.00 0.00 217.70   270.04  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 77.01 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 43.74 31-JAN-17:00 128.17 01-JAN-08:00
February 180.00 01-FEB-00:10 77.01 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 2.58 18-FEB-16:09 98.65 28-FEB-07:00
March 180.00 01-MAR-00:10 77.01 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 42.44 16-MAR-15:10 127.73 26-MAR-06:00
April 180.00 01-APR-00:10 77.01 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 75.40 14-APR-16:00 79.29 21-APR-03:53
May 180.00 01-MAY-00:10 77.01 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 85.94 31-MAY-17:00 54.59 01-MAY-04:00
June 180.00 01-JUN-00:10 77.01 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 111.48 28-JUN-16:10 18.56 21-JUN-06:00
July 180.00 01-JUL-00:10 77.01 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 100.89 20-JUL-15:10 18.69 01-JUL-06:00
August 180.00 01-AUG-00:10 77.01 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 106.88 25-AUG-16:30 32.84 05-AUG-18:00
September 180.00 01-SEP-00:10 77.01 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 92.95 08-SEP-15:50 26.96 22-SEP-06:00
October 180.00 01-OCT-00:10 77.01 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 75.59 03-OCT-16:00 98.06 25-OCT-07:00
November 180.00 01-NOV-00:10 77.01 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 39.66 01-NOV-15:10 131.48 23-NOV-06:20
December 180.00 01-DEC-00:10 77.01 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 25.19 25-DEC-16:10 138.17 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 2.58   18.56  
Maximum of Months 180.00   77.01   232.26   0.00 0.00 0.00 0.00 111.48   138.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3094.06 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 168.82 31-JAN-16:00 655.08 01-JAN-08:00
February 26988.77 01-FEB-00:10 3094.06 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 546.82 01-FEB-07:10
March 26988.77 01-MAR-00:10 3094.06 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 155.49 16-MAR-15:00 652.54 26-MAR-06:00
April 26988.77 01-APR-00:10 3094.06 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 303.11 14-APR-15:00 466.72 21-APR-03:53
May 26988.77 01-MAY-00:10 3094.06 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 347.49 15-MAY-17:00 338.24 01-MAY-04:00
June 26988.77 01-JUN-00:10 3094.06 01-JUN-19:19 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 467.77 28-JUN-15:00 168.05 21-JUN-06:00
July 26988.77 01-JUL-00:10 3094.06 03-JUL-19:30 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 434.86 19-JUL-13:00 169.26 01-JUL-06:00
August 26988.77 01-AUG-00:10 3094.06 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 456.08 26-AUG-16:00 182.70 05-AUG-18:00
September 26988.77 01-SEP-00:10 3094.06 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 385.53 08-SEP-15:00 206.70 22-SEP-06:00
October 26988.77 01-OCT-23:10 3094.06 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 361.99 01-OCT-13:00 557.39 25-OCT-05:50
November 26988.77 01-NOV-00:10 3094.06 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 164.29 01-NOV-15:00 674.38 23-NOV-06:30
December 26988.77 01-DEC-00:10 3094.06 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 109.12 21-DEC-15:00 708.94 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 0.00   168.05  
Maximum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 467.77   708.94  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3094.06 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 161.00 31-JAN-16:00 666.35 01-JAN-08:00
February 26988.77 01-FEB-00:10 3094.06 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 553.71 01-FEB-07:30
March 26988.77 01-MAR-00:10 3094.06 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 146.89 16-MAR-15:00 661.76 26-MAR-06:00
April 26988.77 01-APR-00:10 3094.06 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 295.89 14-APR-15:00 472.47 21-APR-03:53
May 26988.77 01-MAY-00:10 3094.06 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 339.05 15-MAY-17:00 342.04 01-MAY-04:00
June 26988.77 01-JUN-00:10 3094.06 01-JUN-19:19 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 460.23 28-JUN-15:00 168.05 21-JUN-06:00
July 26988.77 01-JUL-00:10 3094.06 03-JUL-19:30 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 427.31 19-JUL-13:00 169.26 01-JUL-06:00
August 26988.77 01-AUG-00:10 3094.06 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 447.93 26-AUG-16:00 191.32 05-AUG-18:00
September 26988.77 01-SEP-00:10 3094.06 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 378.32 08-SEP-15:00 209.03 22-SEP-06:00
October 26988.77 01-OCT-23:10 3094.06 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 354.18 01-OCT-13:00 561.56 25-OCT-05:50
November 26988.77 01-NOV-00:10 3094.06 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 156.73 01-NOV-15:00 681.69 23-NOV-07:00
December 26988.77 01-DEC-00:10 3094.06 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 98.74 21-DEC-15:00 717.45 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 0.00   168.05  
Maximum of Months 26988.77   3094.06   6747.90   0.00 0.00 0.00 0.00 460.23   717.45  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1089.83 02-JAN-20:10 14912.86 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 117.91 31-JAN-16:40 623.68 01-JAN-08:00
February 2401.70 01-FEB-00:10 1089.83 01-FEB-20:10 14912.86 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 0.00 01-FEB-00:10 563.95 01-FEB-07:30
March 2401.70 01-MAR-00:10 1089.83 01-MAR-20:10 14912.86 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 112.57 16-MAR-15:40 621.59 26-MAR-06:00
April 2401.70 01-APR-00:10 1089.83 03-APR-19:10 14912.86 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 255.03 14-APR-15:40 451.03 21-APR-03:53
May 2401.70 01-MAY-00:10 1089.83 01-MAY-19:10 14912.86 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 300.36 31-MAY-17:00 306.23 01-MAY-04:00
June 2401.70 01-JUN-00:10 1089.83 01-JUN-19:10 14912.86 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 410.58 28-JUN-16:00 150.34 21-JUN-06:00
July 2401.70 01-JUL-00:10 1089.83 03-JUL-19:10 14912.86 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 369.30 19-JUL-13:00 151.41 01-JUL-06:00
August 2401.70 01-AUG-00:10 1089.83 01-AUG-19:10 14912.86 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 390.55 25-AUG-14:00 176.87 05-AUG-18:00
September 2401.70 01-SEP-00:10 1089.83 01-SEP-19:10 14912.86 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 330.69 08-SEP-15:00 187.03 22-SEP-06:00
October 2401.70 01-OCT-23:10 1089.83 02-OCT-19:10 14912.86 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 301.36 01-OCT-13:00 539.28 25-OCT-05:50
November 2401.70 01-NOV-00:10 1089.83 01-NOV-19:10 14912.86 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 117.33 01-NOV-15:00 638.11 23-NOV-06:00
December 2401.70 01-DEC-00:10 1089.83 01-DEC-20:10 14912.86 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 46.20 21-DEC-15:00 666.99 05-DEC-04:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1089.83   14912.86   22492.83   0.00 0.00 0.00 0.00   150.34  
Maximum of Months 2401.70   1089.83   14912.86   22492.83   0.00 0.00 0.00 410.58   666.99  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 2371.52 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 115.02 31-JAN-16:00 533.09 01-JAN-08:00
February 2395.44 01-FEB-00:10 2371.52 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 448.29 01-FEB-05:05
March 2395.44 01-MAR-00:10 2371.52 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 109.88 16-MAR-15:00 536.65 26-MAR-04:00
April 2395.44 01-APR-00:10 2371.52 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 249.22 14-APR-15:00 379.77 21-APR-03:57
May 2395.44 01-MAY-00:10 2371.52 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 293.60 31-MAY-17:00 289.83 01-MAY-04:00
June 2395.44 01-JUN-00:10 2371.52 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 401.51 28-JUN-16:00 147.34 21-JUN-06:00
July 2395.44 01-JUL-00:10 2371.52 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 361.19 19-JUL-13:00 148.40 01-JUL-06:00
August 2395.44 01-AUG-00:10 2371.52 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 382.02 25-AUG-14:00 173.49 05-AUG-18:00
September 2395.44 01-SEP-00:10 2371.52 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 323.41 08-SEP-15:00 176.47 22-SEP-06:00
October 2395.44 01-OCT-23:10 2371.52 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 294.67 01-OCT-13:00 448.32 25-OCT-05:55
November 2395.44 01-NOV-00:10 2371.52 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 114.56 01-NOV-15:00 567.03 23-NOV-06:00
December 2395.44 01-DEC-00:10 2371.52 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 63.44 21-DEC-15:00 582.83 05-DEC-04:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   2371.52   0.00 0.00 0.00 0.00 0.00 0.00   147.34  
Maximum of Months 2395.44   2371.52   0.00 0.00 0.00 0.00 0.00 401.51   582.83  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 38637.81 12-JAN-06:34 44729.58 31522.79 26615.27 0.00 0.00 0.00 0.00 0.00 0.00
February 30315.24 01-FEB-06:55 89459.16 63045.57 53230.53 0.00 0.00 0.00 0.00 0.00 0.00
March 18717.39 13-MAR-04:40 23003.78 6304.56 6387.66 0.00 0.00 0.00 0.00 0.00 0.00
April 18578.47 21-APR-03:50 92015.14 12609.84 17033.77 0.00 0.00 0.00 0.00 0.00 0.00
May 15114.33 01-MAY-21:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
June 16703.60 22-JUN-21:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
July 23098.70 14-JUL-21:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
August 24801.09 24-AUG-21:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
September 27111.66 08-SEP-21:00 10223.90 12609.30 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
October 38759.07 25-OCT-05:30 17891.83 12609.11 10646.11 0.00 0.00 0.00 0.00 0.00 0.00
November 38841.79 05-NOV-06:40 17891.83 12609.11 10646.11 0.00 0.00 0.00 0.00 0.00 0.00
December 40533.31 14-DEC-00:23 115018.92 31522.79 31938.32 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 15114.33   10223.90 6304.56 6387.66 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 40533.31   115018.92 63045.57 53230.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3777.40 14-JAN-13:40 389.84 195.67 252.59 0.00 0.00 0.00 0.00 50.93 0.00
February 2710.84 01-FEB-14:00 259.90 195.67 252.59 0.00 0.00 0.00 0.00 0.00 157.44
March 2977.15 18-MAR-13:40 389.84 195.67 252.59 0.00 0.00 0.00 0.00 43.32 0.00
April 3347.16 14-APR-14:10 389.84 195.67 252.59 0.00 0.00 0.00 0.00 187.86 0.00
May 2905.81 31-MAY-18:15 1819.27 1252.29 1299.04 0.00 0.00 0.00 0.00 208.52 0.00
June 3708.77 28-JUN-18:13 2728.91 1878.44 1948.56 0.00 0.00 0.00 0.00 301.79 0.00
July 3421.69 21-JUL-18:30 909.64 626.15 649.52 0.00 0.00 0.00 0.00 256.14 0.00
August 3807.75 28-AUG-12:30 259.90 195.67 252.59 0.00 0.00 0.00 0.00 239.14 0.00
September 4131.85 28-SEP-13:30 259.90 195.67 252.59 0.00 0.00 0.00 0.00 223.40 0.00
October 4126.48 06-OCT-13:20 259.90 195.67 252.59 0.00 0.00 0.00 0.00 202.53 0.00
November 3968.22 20-NOV-13:40 259.90 195.67 252.59 0.00 0.00 0.00 0.00 50.61 0.00
December 3662.24 25-DEC-13:00 389.84 234.80 288.68 0.00 0.00 0.00 0.00 19.06 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2710.84   259.90 195.67 252.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4131.85   2728.91 1878.44 1948.56 0.00 0.00 0.00 0.00 301.79 157.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2222.30 30-JAN-05:38 13543.20 1812.70 2507.15 0.00 0.00 0.00 0.00 0.00 125.31
February 2142.61 02-FEB-02:35 2708.64 181.27 334.29 0.00 0.00 0.00 0.00 0.00 122.25
March 1924.06 13-MAR-04:40 2708.64 362.54 501.43 0.00 0.00 0.00 0.00 0.00 127.72
April 2457.28 14-APR-20:10 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 47.95 0.00
May 2414.92 31-MAY-20:10 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 48.04 0.00
June 2769.78 28-JUN-20:10 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 89.55 0.00
July 2613.25 20-JUL-20:10 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 79.66 0.00
August 2646.71 15-AUG-20:10 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 76.07 0.00
September 2597.82 07-SEP-21:00 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 66.93 0.00
October 2396.76 05-OCT-20:10 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 18.24 0.00
November 2063.41 01-NOV-20:10 1203.84 725.08 752.15 0.00 0.00 0.00 0.00 0.00 26.19
December 2185.61 14-DEC-00:23 13543.20 1812.70 2507.15 0.00 0.00 0.00 0.00 0.00 143.59
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1924.06   1203.84 181.27 334.29 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2769.78   13543.20 1812.70 2507.15 0.00 0.00 0.00 0.00 89.55 143.59



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1420.98 30-JAN-05:38 2864.16 3023.10 2650.88 0.00 0.00 0.00 0.00 0.00 280.60
February 1381.07 02-FEB-02:35 572.83 302.31 353.45 0.00 0.00 0.00 0.00 0.00 276.18
March 1298.93 17-MAR-21:00 254.59 1209.24 795.27 0.00 0.00 0.00 0.00 0.00 42.47
April 2294.71 25-APR-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 68.83 0.00
May 2450.64 31-MAY-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 119.06 0.00
June 3125.15 28-JUN-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 216.98 0.00
July 2978.72 21-JUL-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 217.80 0.00
August 2828.90 15-AUG-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 185.15 0.00
September 2695.58 08-SEP-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 166.06 0.00
October 2452.73 03-OCT-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 102.69 0.00
November 1393.93 02-NOV-20:00 222.77 1360.40 839.45 0.00 0.00 0.00 0.00 0.00 53.01
December 1384.11 14-DEC-00:23 2864.16 3023.10 2650.88 0.00 0.00 0.00 0.00 0.00 321.76
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1298.93   222.77 302.31 353.45 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3125.15   2864.16 3023.10 2650.88 0.00 0.00 0.00 0.00 217.80 321.76



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1232.31 30-JAN-05:38 2203.20 506.04 764.71 0.00 0.00 0.00 0.00 0.00 151.76
February 1187.05 02-FEB-02:35 440.64 50.60 101.96 0.00 0.00 0.00 0.00 0.00 148.30
March 1011.56 02-MAR-05:27 660.96 151.81 229.41 0.00 0.00 0.00 0.00 0.00 148.11
April 1112.21 21-APR-03:50 1762.56 202.41 407.84 0.00 0.00 0.00 0.00 0.00 145.57
May 967.85 31-MAY-18:07 1028.16 1214.49 1376.47 0.00 0.00 0.00 0.00 117.69 0.00
June 1356.10 28-JUN-19:10 171.36 227.72 242.16 0.00 0.00 0.00 0.00 148.22 0.00
July 1250.82 21-JUL-20:00 171.36 227.72 242.16 0.00 0.00 0.00 0.00 125.66 0.00
August 1146.66 15-AUG-20:00 171.36 227.72 242.16 0.00 0.00 0.00 0.00 106.82 0.00
September 1032.36 08-SEP-20:00 171.36 227.72 242.16 0.00 0.00 0.00 0.00 95.81 0.00
October 1169.05 12-OCT-04:42 1321.92 303.62 458.82 0.00 0.00 0.00 0.00 0.00 160.01
November 1130.91 30-NOV-05:05 440.64 101.21 152.94 0.00 0.00 0.00 0.00 0.00 139.46
December 1188.78 14-DEC-00:23 2203.20 506.04 764.71 0.00 0.00 0.00 0.00 0.00 174.39
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 967.85   171.36 50.60 101.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1356.10   2203.20 1214.49 1376.47 0.00 0.00 0.00 0.00 148.22 174.39



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 42080.81 12-JAN-07:04 4032.00 1984.52 28880.85 250904.69 0.00 0.00 0.00 0.00 491.73
February 42147.59 02-FEB-07:09 4032.00 1984.52 28880.85 250904.69 0.00 0.00 0.00 0.00 479.82
March 41396.38 30-MAR-06:33 4032.00 1984.52 28880.85 250904.69 0.00 0.00 0.00 0.00 489.95
April 39538.83 14-APR-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 162.25 0.00
May 39633.74 09-MAY-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 162.44 0.00
June 40402.89 28-JUN-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 296.31 0.00
July 40201.72 21-JUL-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 297.40 0.00
August 40086.33 15-AUG-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 252.76 0.00
September 39908.61 08-SEP-20:00 705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 226.68 0.00
October 39481.22 12-OCT-06:38 4032.00 1984.52 28880.85 250904.69 0.00 0.00 0.00 0.00 417.97
November 46138.40 23-NOV-21:29 8064.00 2381.43 33694.32 292722.14 0.00 0.00 0.00 0.00 515.38
December 48778.68 04-DEC-21:39 8064.00 3175.23 43321.27 376357.04 0.00 0.00 0.00 0.00 499.92
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 39481.22   705.60 357.21 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 48778.68   8064.00 3175.23 43321.27 376357.04 0.00 0.00 0.00 297.40 515.38



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 15980.31 30-JAN-05:38 153684.00 3915.35 3048.23 0.00 0.00 0.00 0.00 0.00 699.62
February 14860.33 02-FEB-01:50 107578.80 2055.56 1778.13 0.00 0.00 0.00 0.00 0.00 653.34
March 12574.73 02-MAR-05:27 46105.20 1174.60 914.47 0.00 0.00 0.00 0.00 0.00 650.88
April 13292.91 21-APR-03:50 122947.20 1566.14 1625.72 0.00 0.00 0.00 0.00 0.00 621.28
May 11658.96 09-MAY-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 200.84 0.00
June 13622.52 28-JUN-18:06 59766.00 4776.72 4572.35 0.00 0.00 0.00 0.00 673.51 0.00
July 13329.35 21-JUL-21:10 15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 403.93 0.00
August 13660.64 15-AUG-18:05 71719.20 6953.65 5486.82 0.00 0.00 0.00 0.00 559.71 0.00
September 14183.87 28-SEP-15:03 59766.00 2089.82 2489.39 0.00 0.00 0.00 0.00 548.10 0.00
October 14098.10 05-OCT-15:03 51228.00 1791.27 2133.76 0.00 0.00 0.00 0.00 408.88 0.00
November 14253.41 01-NOV-15:03 51228.00 1791.27 2133.76 0.00 0.00 0.00 0.00 201.29 0.00
December 15470.44 14-DEC-00:23 153684.00 3915.35 3048.23 0.00 0.00 0.00 0.00 0.00 794.46
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 11658.96   15368.40 1174.60 711.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15980.31   153684.00 6953.65 5486.82 0.00 0.00 0.00 0.00 673.51 794.46



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 73990.25 11-JAN-06:27 106453.62 13686.91 15835.59 0.00 0.00 0.00 0.00 0.00 1968.20
February 55655.86 24-FEB-05:54 228114.90 11405.76 15835.59 0.00 0.00 0.00 0.00 0.00 2172.11
March 56343.11 24-MAR-04:43 273737.88 13686.91 19002.71 0.00 0.00 0.00 0.00 0.00 2209.14
April 43163.18 14-APR-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 552.98 0.00
May 42577.69 09-MAY-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 573.59 0.00
June 48445.70 28-JUN-20:10 40553.76 9124.61 9501.36 0.00 0.00 0.00 0.00 1465.49 0.00
July 47508.45 21-JUL-20:10 40553.76 9124.61 9501.36 0.00 0.00 0.00 0.00 1452.82 0.00
August 46971.73 15-AUG-20:10 40553.76 9124.61 9501.36 0.00 0.00 0.00 0.00 1244.81 0.00
September 46803.73 07-SEP-21:10 45622.98 6843.46 7389.94 0.00 0.00 0.00 0.00 1032.21 0.00
October 70167.46 30-OCT-04:57 136868.94 6843.46 9501.36 0.00 0.00 0.00 0.00 0.00 1771.82
November 43544.48 30-NOV-05:05 91245.96 4562.30 6334.24 0.00 0.00 0.00 0.00 0.00 1937.35
December 56524.22 04-DEC-23:27 182491.92 13686.91 16891.30 0.00 0.00 0.00 0.00 0.00 2588.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 42577.69   40553.76 4562.30 6334.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 73990.25   273737.88 13686.91 19002.71 0.00 0.00 0.00 0.00 1465.49 2588.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3726.19 31-JAN-16:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 70.20 0.00
February 3516.04 22-FEB-16:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 0.00 19.32
March 3684.94 18-MAR-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 52.34 0.00
April 3772.61 14-APR-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 131.20 0.00
May 3758.40 30-MAY-18:01 970.20 763.21 903.46 0.00 0.00 0.00 0.00 99.17 0.00
June 3784.51 27-JUN-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 179.82 0.00
July 3762.12 05-JUL-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 161.14 0.00
August 3775.55 27-AUG-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 182.29 0.00
September 3792.54 28-SEP-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 157.03 0.00
October 3784.39 06-OCT-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 130.79 0.00
November 3752.56 20-NOV-16:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 45.88 0.00
December 3660.65 25-DEC-16:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 35.11 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3516.04   324.00 240.11 458.31 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3792.54   970.20 763.21 903.46 0.00 0.00 0.00 0.00 182.29 19.32



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3639.64 31-JAN-16:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 72.09 0.00
February 3445.19 22-FEB-16:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 0.00 17.85
March 3611.88 18-MAR-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 53.82 0.00
April 3738.40 25-APR-18:01 970.20 763.12 903.35 0.00 0.00 0.00 0.00 97.17 0.00
May 3741.29 30-MAY-18:01 970.20 763.12 903.35 0.00 0.00 0.00 0.00 98.91 0.00
June 3770.32 27-JUN-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 179.47 0.00
July 3746.56 05-JUL-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 160.83 0.00
August 3736.16 25-AUG-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 169.92 0.00
September 3732.69 28-SEP-15:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 158.03 0.00
October 3719.53 06-OCT-15:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 131.95 0.00
November 3666.17 20-NOV-16:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 47.76 0.00
December 3554.71 25-DEC-16:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 37.63 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3445.19   324.00 240.08 458.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3770.32   970.20 763.12 903.35 0.00 0.00 0.00 0.00 179.47 17.85



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 692.43 14-JAN-13:50 0.00 25.41 74.82 0.00 0.00 0.00 0.00 10.69 0.00
February 533.39 01-FEB-15:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 25.12
March 512.74 18-MAR-14:30 0.00 25.41 74.82 0.00 0.00 0.00 0.00 10.12 0.00
April 540.34 14-APR-13:40 0.00 21.56 67.08 0.00 0.00 0.00 0.00 31.84 0.00
May 451.74 09-MAY-17:17 0.00 206.33 526.30 0.00 0.00 0.00 0.00 33.70 0.00
June 556.09 28-JUN-17:13 0.00 154.75 394.73 0.00 0.00 0.00 0.00 53.48 0.00
July 529.12 21-JUL-19:10 0.00 76.99 170.27 0.00 0.00 0.00 0.00 42.86 0.00
August 617.82 27-AUG-14:00 0.00 25.41 74.82 0.00 0.00 0.00 0.00 48.97 0.00
September 692.01 28-SEP-13:40 0.00 21.56 67.08 0.00 0.00 0.00 0.00 39.09 0.00
October 706.78 18-OCT-13:50 0.00 21.56 67.08 0.00 0.00 0.00 0.00 22.68 0.00
November 728.57 20-NOV-14:30 0.00 21.56 67.08 0.00 0.00 0.00 0.00 11.13 0.00
December 686.94 25-DEC-13:40 0.00 25.41 74.82 0.00 0.00 0.00 0.00 7.06 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 451.74   0.00 21.56 67.08 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 728.57   0.00 206.33 526.30 0.00 0.00 0.00 0.00 53.48 25.12



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1129.55 31-JAN-19:01 970.20 479.78 885.15 0.00 0.00 0.00 0.00 4.33 0.00
February 911.15 20-FEB-09:02 324.00 258.76 959.99 0.00 0.00 0.00 0.00 0.00 28.93
March 1211.57 15-MAR-18:01 970.20 479.78 885.15 0.00 0.00 0.00 0.00 13.46 0.00
April 1267.98 25-APR-18:01 970.20 479.78 885.15 0.00 0.00 0.00 0.00 26.77 0.00
May 1269.49 30-MAY-18:01 970.20 479.78 885.15 0.00 0.00 0.00 0.00 27.24 0.00
June 1272.81 27-JUN-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 49.89 0.00
July 1270.15 07-JUL-18:02 831.60 411.24 758.70 0.00 0.00 0.00 0.00 41.66 0.00
August 1266.43 27-AUG-15:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 50.68 0.00
September 1269.39 18-SEP-18:01 970.20 479.78 885.15 0.00 0.00 0.00 0.00 34.01 0.00
October 1266.99 05-OCT-18:01 970.20 479.78 885.15 0.00 0.00 0.00 0.00 26.29 0.00
November 1139.14 20-NOV-16:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 16.90 0.00
December 975.20 23-DEC-09:02 324.00 258.76 959.99 0.00 0.00 0.00 0.00 0.00 21.13
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 911.15   324.00 150.94 449.03 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1272.81   970.20 479.78 959.99 0.00 0.00 0.00 0.00 50.68 28.93



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3267.06 31-JAN-16:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 70.60 0.00
February 3063.22 22-FEB-16:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 0.00 18.22
March 3242.19 18-MAR-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 52.34 0.00
April 3314.68 14-APR-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 131.36 0.00
May 3318.34 18-MAY-08:61 252.00 377.32 792.83 0.00 0.00 0.00 0.00 50.95 0.00
June 3339.02 19-JUN-08:61 252.00 377.32 792.83 0.00 0.00 0.00 0.00 90.79 0.00
July 3319.28 01-JUL-08:61 378.00 480.22 1143.15 0.00 0.00 0.00 0.00 52.57 0.00
August 3330.17 27-AUG-08:61 378.00 480.22 1143.15 0.00 0.00 0.00 0.00 75.49 0.00
September 3334.45 28-SEP-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 157.11 0.00
October 3324.90 06-OCT-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 130.95 0.00
November 3273.66 20-NOV-16:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 46.85 0.00
December 3197.66 25-DEC-16:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 35.93 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3063.22   252.00 240.11 458.31 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3339.02   680.40 480.22 1143.15 0.00 0.00 0.00 0.00 157.11 18.22



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3188.04 31-JAN-16:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 72.62 0.00
February 2821.31 22-FEB-16:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 0.00 7.00
March 3203.87 15-MAR-15:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 64.49 0.00
April 3272.49 14-APR-15:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 132.04 0.00
May 3299.57 18-MAY-08:61 252.00 377.27 792.74 0.00 0.00 0.00 0.00 50.84 0.00
June 3323.48 19-JUN-08:61 252.00 377.27 792.74 0.00 0.00 0.00 0.00 90.57 0.00
July 3303.73 01-JUL-08:61 378.00 480.16 1143.02 0.00 0.00 0.00 0.00 52.35 0.00
August 3306.40 27-AUG-08:61 378.00 480.16 1143.02 0.00 0.00 0.00 0.00 75.55 0.00
September 3282.02 28-SEP-15:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 158.13 0.00
October 3267.68 06-OCT-15:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 132.15 0.00
November 3188.91 20-NOV-16:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 49.07 0.00
December 2984.25 25-DEC-16:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 44.79 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2821.31   252.00 240.08 458.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3323.48   680.40 480.16 1143.02 0.00 0.00 0.00 0.00 158.13 7.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2812.72 30-JAN-05:38 22633.56 4979.51 0.00 0.00 0.00 0.00 0.00 0.00 223.29
February 2756.01 02-FEB-02:35 4526.71 497.95 0.00 0.00 0.00 0.00 0.00 0.00 221.31
March 2441.21 13-MAR-04:40 4526.71 995.90 0.00 0.00 0.00 0.00 0.00 0.00 228.85
April 3199.76 14-APR-18:15 3520.78 3983.61 0.00 0.00 0.00 0.00 0.00 116.33 0.00
May 3270.32 31-MAY-18:30 1760.39 1991.81 0.00 0.00 0.00 0.00 0.00 141.62 0.00
June 4159.59 28-JUN-19:10 1760.39 2240.78 0.00 0.00 0.00 0.00 0.00 197.11 0.00
July 3819.18 21-JUL-19:10 1760.39 2240.78 0.00 0.00 0.00 0.00 0.00 177.20 0.00
August 3661.06 25-AUG-18:15 3520.78 3983.61 0.00 0.00 0.00 0.00 0.00 183.88 0.00
September 3547.23 08-SEP-18:15 3520.78 3983.61 0.00 0.00 0.00 0.00 0.00 153.52 0.00
October 3221.75 05-OCT-18:13 5281.16 5975.42 0.00 0.00 0.00 0.00 0.00 91.09 0.00
November 2588.25 30-NOV-05:05 4526.71 995.90 0.00 0.00 0.00 0.00 0.00 0.00 205.71
December 2622.63 14-DEC-00:23 22633.56 4979.51 0.00 0.00 0.00 0.00 0.00 0.00 246.18
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2441.21   1760.39 497.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4159.59   22633.56 5975.42 0.00 0.00 0.00 0.00 0.00 197.11 246.18



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3931.14 31-JAN-16:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 70.02 0.00
February 3706.02 22-FEB-16:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 0.00 19.47
March 3894.52 18-MAR-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 51.95 0.00
April 3998.38 14-APR-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 130.52 0.00
May 3981.25 07-MAY-15:01 378.00 282.99 534.70 0.00 0.00 0.00 0.00 133.49 0.00
June 4009.02 27-JUN-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 179.21 0.00
July 3981.48 05-JUL-18:02 831.60 654.18 774.39 0.00 0.00 0.00 0.00 160.63 0.00
August 4002.75 27-AUG-15:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 181.60 0.00
September 4017.08 28-SEP-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 156.43 0.00
October 4002.21 06-OCT-15:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 130.36 0.00
November 3967.99 20-NOV-16:01 680.40 240.11 479.39 0.00 0.00 0.00 0.00 45.43 0.00
December 3863.03 25-DEC-16:02 324.00 242.57 458.31 0.00 0.00 0.00 0.00 34.88 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3706.02   324.00 240.11 458.31 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4017.08   831.60 654.18 774.39 0.00 0.00 0.00 0.00 181.60 19.47



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3826.24 31-JAN-16:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 72.22 0.00
February 3620.51 22-FEB-16:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 0.00 17.76
March 3810.61 18-MAR-15:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 53.53 0.00
April 3952.25 25-APR-18:01 970.20 763.12 903.35 0.00 0.00 0.00 0.00 96.67 0.00
May 3950.93 30-MAY-18:01 970.20 763.12 903.35 0.00 0.00 0.00 0.00 98.54 0.00
June 3992.03 27-JUN-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 178.83 0.00
July 3962.87 05-JUL-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 160.30 0.00
August 3956.15 25-AUG-18:02 831.60 654.11 774.30 0.00 0.00 0.00 0.00 169.27 0.00
September 3948.59 28-SEP-15:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 157.49 0.00
October 3928.09 06-OCT-15:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 131.59 0.00
November 3863.64 20-NOV-16:01 680.40 240.08 479.33 0.00 0.00 0.00 0.00 47.60 0.00
December 3732.14 25-DEC-16:02 324.00 242.54 458.26 0.00 0.00 0.00 0.00 37.86 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3620.51   324.00 240.08 458.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3992.03   970.20 763.12 903.35 0.00 0.00 0.00 0.00 178.83 17.76



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2010.56 31-JAN-16:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 34.16 0.00
February 1878.98 22-FEB-16:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 0.00 11.01
March 1985.33 18-MAR-15:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 25.11 0.00
April 2006.31 14-APR-15:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 66.25 0.00
May 1985.78 07-MAY-15:01 378.00 177.90 523.86 0.00 0.00 0.00 0.00 68.12 0.00
June 1982.65 27-JUN-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 98.11 0.00
July 1975.20 07-JUL-15:02 583.20 129.38 402.58 0.00 0.00 0.00 0.00 77.95 0.00
August 2001.21 26-AUG-15:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 97.82 0.00
September 2029.74 28-SEP-15:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 79.10 0.00
October 2025.86 06-OCT-15:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 65.66 0.00
November 2021.11 20-NOV-16:01 680.40 150.94 469.67 0.00 0.00 0.00 0.00 21.80 0.00
December 1991.39 25-DEC-16:02 324.00 152.48 449.03 0.00 0.00 0.00 0.00 15.73 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1878.98   324.00 129.38 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2029.74   680.40 177.90 523.86 0.00 0.00 0.00 0.00 98.11 11.01



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 33791.94 10-JAN-05:05 53977.54 1375.14 4498.60 0.00 0.00 0.00 0.00 0.00 416.61
February 31904.40 24-FEB-05:54 134943.84 3437.84 11246.50 0.00 0.00 0.00 0.00 0.00 493.60
March 32267.07 24-MAR-04:43 161932.61 4125.41 13495.81 0.00 0.00 0.00 0.00 0.00 501.42
April 29430.07 21-APR-03:54 269887.68 3437.84 22493.01 0.00 0.00 0.00 0.00 0.00 461.47
May 22865.87 09-MAY-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 126.11 0.00
June 24844.64 28-JUN-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 267.78 0.00
July 24361.85 21-JUL-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 256.36 0.00
August 23835.65 10-AUG-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 242.95 0.00
September 23589.71 07-SEP-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 229.04 0.00
October 25816.82 12-OCT-04:42 161932.61 4125.41 13495.81 0.00 0.00 0.00 0.00 0.00 459.43
November 25232.52 30-NOV-05:05 53977.54 1375.14 4498.60 0.00 0.00 0.00 0.00 0.00 407.38
December 31224.53 14-DEC-23:37 161932.61 6188.11 40487.42 0.00 0.00 0.00 0.00 0.00 523.19
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 22865.87   26988.77 1375.14 4498.60 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 33791.94   269887.68 6188.11 40487.42 0.00 0.00 0.00 0.00 267.78 523.19



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 33422.31 09-JAN-23:55 161932.61 6188.11 40487.42 0.00 0.00 0.00 0.00 0.00 469.06
February 33994.67 24-FEB-05:54 134943.84 3437.84 11246.50 0.00 0.00 0.00 0.00 0.00 495.39
March 33919.77 24-MAR-04:43 161932.61 4125.41 13495.81 0.00 0.00 0.00 0.00 0.00 503.01
April 33246.64 21-APR-03:54 269887.68 3437.84 22493.01 0.00 0.00 0.00 0.00 0.00 464.30
May 24223.83 09-MAY-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 126.10 0.00
June 26255.11 28-JUN-21:20 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 267.59 0.00
July 25745.56 21-JUL-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 256.36 0.00
August 25199.47 10-AUG-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 242.95 0.00
September 24937.72 07-SEP-21:10 26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 229.04 0.00
October 27337.25 25-OCT-04:40 134943.84 3437.84 11246.50 0.00 0.00 0.00 0.00 0.00 490.95
November 27641.91 08-NOV-03:30 188921.38 2406.49 15745.11 0.00 0.00 0.00 0.00 0.00 463.36
December 34171.80 14-DEC-23:37 161932.61 6188.11 40487.42 0.00 0.00 0.00 0.00 0.00 527.83
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 24223.83   26988.77 2062.70 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 34171.80   269887.68 6188.11 40487.42 0.00 0.00 0.00 0.00 267.59 527.83



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 36405.13 13-JAN-07:39 10674.24 6054.62 149128.56 112464.16 0.00 0.00 0.00 0.00 461.36
February 34465.36 28-FEB-07:13 10674.24 6054.62 149128.56 112464.16 0.00 0.00 0.00 0.00 486.94
March 34857.39 31-MAR-06:53 10674.24 6054.62 149128.56 112464.16 0.00 0.00 0.00 0.00 492.68
April 30564.23 30-APR-10:40 1601.14 726.55 29825.71 37488.05 0.00 0.00 0.00 140.85 0.00
May 30788.78 07-MAY-10:40 1601.14 726.55 29825.71 37488.05 0.00 0.00 0.00 141.41 0.00
June 31667.48 18-JUN-10:50 800.57 363.28 14912.86 18744.03 0.00 0.00 0.00 268.50 0.00
July 31667.26 22-JUL-10:40 1601.14 605.46 29825.71 37488.05 0.00 0.00 0.00 269.89 0.00
August 31708.56 13-AUG-10:40 1601.14 726.55 29825.71 37488.05 0.00 0.00 0.00 224.58 0.00
September 31427.60 09-SEP-10:35 1601.14 605.46 29825.71 37488.05 0.00 0.00 0.00 221.44 0.00
October 32601.45 25-OCT-08:07 3202.27 2906.22 89477.13 67478.50 0.00 0.00 0.00 0.00 407.90
November 33754.42 24-NOV-08:15 4269.70 1937.48 59651.42 59980.88 0.00 0.00 0.00 0.00 443.25
December 35437.30 29-DEC-08:10 10674.24 4843.69 149128.56 149952.21 0.00 0.00 0.00 0.00 452.57
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 30564.23   800.57 363.28 14912.86 18744.03 0.00 0.00 0.00 0.00 0.00
Maximum of Months 36405.13   10674.24 6054.62 149128.56 149952.21 0.00 0.00 0.00 269.89 492.68



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4201.26 30-JAN-05:38 23954.40 5270.05 0.00 0.00 0.00 0.00 0.00 0.00 386.85
February 4099.66 02-FEB-02:35 4790.88 527.00 0.00 0.00 0.00 0.00 0.00 0.00 382.07
March 4521.25 18-MAR-15:00 798.48 658.76 0.00 0.00 0.00 0.00 0.00 73.29 0.00
April 6911.28 14-APR-15:03 9315.60 4611.29 0.00 0.00 0.00 0.00 0.00 249.21 0.00
May 6657.88 31-MAY-18:15 3726.24 4216.04 0.00 0.00 0.00 0.00 0.00 256.66 0.00
June 8515.73 28-JUN-18:13 5589.36 6324.06 0.00 0.00 0.00 0.00 0.00 372.53 0.00
July 7781.02 20-JUL-18:17 5589.36 6324.06 0.00 0.00 0.00 0.00 0.00 323.60 0.00
August 7718.78 26-AUG-14:50 798.48 658.76 0.00 0.00 0.00 0.00 0.00 377.55 0.00
September 7723.24 07-SEP-15:03 7984.80 3952.54 0.00 0.00 0.00 0.00 0.00 301.20 0.00
October 7204.97 02-OCT-13:10 532.32 658.76 0.00 0.00 0.00 0.00 0.00 231.59 0.00
November 5151.44 01-NOV-15:03 7984.80 3952.54 0.00 0.00 0.00 0.00 0.00 110.70 0.00
December 4012.14 14-DEC-00:23 23954.40 5270.05 0.00 0.00 0.00 0.00 0.00 0.00 435.96
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4012.14   532.32 527.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8515.73   23954.40 6324.06 0.00 0.00 0.00 0.00 0.00 377.55 435.96



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.447920E+12 307407.43 31-JAN-19:10 0.438810E+12 388293.86 01-JAN-23:19
February 0.356173E+12 259268.36 09-FEB-20:10 0.399620E+12 365962.79 04-FEB-19:10
March 0.436696E+12 323507.21 16-MAR-19:10 0.420745E+12 348094.92 01-MAR-18:00
April 0.545196E+12 387513.31 14-APR-19:10 0.371317E+12 341913.71 04-APR-17:49
May 0.614088E+12 397545.59 31-MAY-19:19 0.370028E+12 318073.31 01-MAY-17:10
June 0.692032E+12 463255.60 28-JUN-19:30 0.347772E+12 314090.36 01-JUN-17:19
July 0.725894E+12 463845.66 21-JUL-19:00 0.353909E+12 311222.67 03-JUL-17:19
August 0.717101E+12 443689.54 15-AUG-19:10 0.355775E+12 312318.41 31-AUG-17:30
September 0.665211E+12 447125.95 08-SEP-19:10 0.351735E+12 315596.82 29-SEP-17:30
October 0.540332E+12 405716.76 02-OCT-19:10 0.383146E+12 327833.93 31-OCT-17:00
November 0.440941E+12 324007.21 01-NOV-18:10 0.398189E+12 360419.22 23-NOV-21:10
December 0.420437E+12 269219.38 26-DEC-20:10 0.451985E+12 428064.21 16-DEC-22:10
             
Annual Sum or Average 0.660202E+13     0.464303E+13    
Minimum of Months 0.356173E+12 259268.36   0.347772E+12 311222.67  
Maximum of Months 0.725894E+12 463845.66   0.451985E+12 428064.21  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.654550E+11 0.237936E+11 0.148212E+12 0.553310E+11 0.492966E+11 0.144854E+11 0.00 0.669564E+11 0.00 0.00 0.114693E+11 0.770423E+10 0.00
February 0.590593E+11 0.204104E+11 0.133859E+12 0.499765E+11 0.407491E+11 0.986001E+10 0.00 0.202171E+11 0.00 0.00 0.103155E+11 0.696182E+10 0.00
March 0.652240E+11 0.209851E+11 0.148223E+12 0.553337E+11 0.457684E+11 0.136876E+11 0.00 0.634706E+11 0.00 0.00 0.110632E+11 0.770284E+10 0.00
April 0.628949E+11 0.186586E+11 0.143397E+12 0.535455E+11 0.521232E+11 0.189825E+11 0.00 0.168650E+12 0.00 0.00 0.144581E+11 0.746489E+10 0.00
May 0.649233E+11 0.178614E+11 0.148223E+12 0.553320E+11 0.571170E+11 0.206721E+11 0.00 0.219507E+12 0.00 0.00 0.175537E+11 0.770425E+10 0.00
June 0.626852E+11 0.166935E+11 0.143446E+12 0.535481E+11 0.642709E+11 0.217601E+11 0.00 0.294511E+12 0.00 0.00 0.225853E+11 0.745687E+10 0.00
July 0.647338E+11 0.174721E+11 0.148174E+12 0.553290E+11 0.660041E+11 0.230338E+11 0.00 0.313251E+12 0.00 0.00 0.248830E+11 0.771240E+10 0.00
August 0.650802E+11 0.186400E+11 0.148234E+12 0.553337E+11 0.661980E+11 0.229816E+11 0.00 0.304193E+12 0.00 0.00 0.233971E+11 0.770434E+10 0.00
September 0.630017E+11 0.195762E+11 0.143408E+12 0.535457E+11 0.633041E+11 0.220723E+11 0.00 0.267705E+12 0.00 0.00 0.199663E+11 0.746623E+10 0.00
October 0.653158E+11 0.219491E+11 0.148201E+12 0.553308E+11 0.568804E+11 0.185814E+11 0.00 0.148991E+12 0.00 0.00 0.121388E+11 0.770290E+10 0.00
November 0.633563E+11 0.226813E+11 0.143462E+12 0.535469E+11 0.494485E+11 0.146538E+11 0.00 0.716623E+11 0.00 0.00 0.961927E+10 0.744868E+10 0.00
December 0.654034E+11 0.242478E+11 0.148174E+12 0.553297E+11 0.495019E+11 0.118381E+11 0.00 0.394144E+11 0.00 0.00 0.136258E+11 0.771236E+10 0.00
                           
Annual Sum or Average 0.767133E+12 0.242969E+12 0.174501E+13 0.651482E+12 0.660662E+12 0.212609E+12 0.00 0.197853E+13 0.00 0.00 0.191075E+12 0.907418E+11 0.00
Minimum of Months 0.590593E+11 0.166935E+11 0.133859E+12 0.499765E+11 0.407491E+11 0.986001E+10 0.00 0.202171E+11 0.00 0.00 0.961927E+10 0.696182E+10 0.00
Maximum of Months 0.654550E+11 0.242478E+11 0.148234E+12 0.553337E+11 0.661980E+11 0.230338E+11 0.00 0.313251E+12 0.00 0.00 0.248830E+11 0.771240E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.351067E+11 0.00 0.251785E+12 0.00 0.00
February 0.137204E+12 0.00 0.364043E+11 0.00 0.226012E+12 0.00 0.00
March 0.152024E+12 0.00 0.259984E+11 0.00 0.242723E+12 0.00 0.00
April 0.146956E+12 0.00 0.109238E+10 0.00 0.223269E+12 0.00 0.00
May 0.151978E+12 0.00 0.252381E+09 0.00 0.217797E+12 0.00 0.00
June 0.147114E+12 0.00 41559702.01 0.00 0.200616E+12 0.00 0.00
July 0.151820E+12 0.00 46735438.96 0.00 0.202042E+12 0.00 0.00
August 0.152039E+12 0.00 59776674.22 0.00 0.203676E+12 0.00 0.00
September 0.146971E+12 0.00 93382907.11 0.00 0.204671E+12 0.00 0.00
October 0.151903E+12 0.00 0.775115E+10 0.00 0.223492E+12 0.00 0.00
November 0.147091E+12 0.00 0.223025E+11 0.00 0.228795E+12 0.00 0.00
December 0.151820E+12 0.00 0.533921E+11 0.00 0.246772E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.182541E+12 0.00 0.267165E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 41559702.01 0.00 0.200616E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.533921E+11 0.00 0.251785E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 62892.57 02-JAN-20:10 15448.40 01-JAN-00:10 89475.41 02-JAN-07:10 39726.11 02-JAN-07:19 32420.53 22-JAN-07:49 8374.27 31-JAN-16:30 0.00 01-JAN-00:10
February 62892.57 01-FEB-20:10 15448.40 01-FEB-00:10 89475.41 01-FEB-07:10 39726.11 01-FEB-07:19 28267.60 24-FEB-05:49 7950.00 18-FEB-16:10 0.00 01-FEB-00:10
March 62892.57 01-MAR-20:10 15448.40 01-MAR-00:10 89475.41 01-MAR-07:10 39726.11 13-MAR-06:19 30295.92 17-MAR-21:10 9010.32 17-MAR-19:49 0.00 01-MAR-00:10
April 62892.57 03-APR-19:10 15448.40 01-APR-00:10 89475.41 03-APR-06:10 39726.11 03-APR-06:19 43317.75 14-APR-21:10 9231.51 25-APR-18:00 0.00 01-APR-00:10
May 62892.57 01-MAY-19:10 15448.40 01-MAY-00:10 89475.41 01-MAY-06:10 39726.11 26-MAY-06:19 41711.77 09-MAY-21:10 9096.40 29-MAY-20:49 0.00 01-MAY-00:10
June 62892.57 01-JUN-19:19 15448.40 01-JUN-00:10 89475.41 01-JUN-06:10 39724.80 01-JUN-06:19 51396.89 28-JUN-21:10 9630.15 28-JUN-18:49 0.00 01-JUN-00:10
July 62892.57 03-JUL-19:30 15448.40 01-JUL-00:10 89475.41 03-JUL-06:10 39725.67 14-JUL-06:19 50931.54 21-JUL-21:10 9407.34 07-JUL-20:00 0.00 01-JUL-00:10
August 62892.57 01-AUG-19:10 15448.40 01-AUG-00:10 89475.41 01-AUG-06:10 39726.11 04-AUG-06:19 51416.61 25-AUG-21:10 9478.37 27-AUG-18:10 0.00 01-AUG-00:10
September 62892.57 01-SEP-19:10 15448.40 01-SEP-00:10 89475.41 01-SEP-06:10 39726.11 01-SEP-06:19 53347.46 08-SEP-21:19 9462.34 10-SEP-19:19 0.00 01-SEP-00:10
October 62892.57 02-OCT-19:10 15448.40 01-OCT-00:10 89475.41 02-OCT-06:10 39726.11 02-OCT-06:19 50260.59 03-OCT-21:10 9399.98 05-OCT-19:19 0.00 01-OCT-00:10
November 62892.57 01-NOV-19:10 15448.40 01-NOV-00:10 89475.41 01-NOV-06:10 39726.11 01-NOV-06:19 36401.65 01-NOV-21:10 9186.86 01-NOV-18:10 0.00 01-NOV-00:10
December 62892.57 01-DEC-20:10 15448.40 01-DEC-00:10 89475.41 01-DEC-07:10 39726.11 01-DEC-07:19 35574.36 04-DEC-22:49 8155.15 26-DEC-16:40 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 62892.57   15448.40   89475.41   39724.80   28267.60   7950.00   0.00  
Maximum of Months 62892.57   15448.40   89475.41   39726.11   53347.46   9630.15   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 104100.10 31-JAN-16:10 0.00 0.00 9938.94 01-JAN-00:20 4738.72 12-JAN-19:10 0.00
February 62945.86 22-FEB-16:10 0.00 0.00 9938.94 01-FEB-00:10 4738.39 16-FEB-19:10 0.00
March 102433.91 16-MAR-15:09 0.00 0.00 9938.94 01-MAR-00:20 4738.52 31-MAR-06:19 0.00
April 148697.84 14-APR-18:10 0.00 0.00 9938.94 01-APR-04:19 4738.54 27-APR-18:10 0.00
May 161986.51 31-MAY-18:10 0.00 0.00 9938.94 01-MAY-03:20 4738.53 18-MAY-18:10 0.00
June 217591.64 28-JUN-18:10 0.00 0.00 9938.94 01-JUN-00:10 4738.74 01-JUN-18:10 0.00
July 198654.96 20-JUL-18:10 0.00 0.00 9938.94 01-JUL-00:10 4738.65 20-JUL-18:10 0.00
August 195071.93 25-AUG-15:09 0.00 0.00 9938.94 01-AUG-00:10 4738.66 03-AUG-18:10 0.00
September 184291.43 08-SEP-18:30 0.00 0.00 9938.94 01-SEP-00:10 4738.75 07-SEP-18:10 0.00
October 157330.29 02-OCT-18:10 0.00 0.00 9938.94 01-OCT-00:10 4738.76 12-OCT-18:10 0.00
November 112124.01 01-NOV-15:09 0.00 0.00 9938.94 01-NOV-10:20 4738.65 15-NOV-19:10 0.00
December 88919.44 25-DEC-16:10 0.00 0.00 9938.94 01-DEC-00:10 4738.62 28-DEC-19:10 0.00
                   
Annual Sum or Average     0.00 0.00         0.00
Minimum of Months 62945.86   0.00 0.00 9938.94   4738.39   0.00
Maximum of Months 217591.64   0.00 0.00 9938.94   4738.76   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 307407.43 31-JAN-19:10 55920.94 79417.81 15448.40 31837.63 26443.68 8223.99 0.00 82200.26 0.00
February 259268.36 09-FEB-20:10 62892.57 88772.42 15448.40 32151.31 22343.92 6018.47 0.00 25483.01 0.00
March 323507.21 16-MAR-19:10 62892.57 88772.42 15448.40 32151.31 25523.61 8449.70 0.00 82801.43 0.00
April 387513.31 14-APR-19:10 62892.57 88772.42 15448.40 32151.31 35687.38 8688.83 0.00 128543.58 0.00
May 397545.59 31-MAY-19:19 62892.57 88772.42 15448.40 32158.49 33752.96 8754.77 0.00 139640.74 0.00
June 463255.60 28-JUN-19:30 62892.57 88772.42 15448.40 32159.27 43205.43 9095.81 0.00 195759.96 0.00
July 463845.66 21-JUL-19:00 62892.57 88772.42 15448.40 32159.77 43756.81 9286.40 0.00 195956.36 0.00
August 443689.54 15-AUG-19:10 62892.57 88772.42 15448.40 32151.31 42869.70 9287.71 0.00 176786.54 0.00
September 447125.95 08-SEP-19:10 62892.57 88772.42 15448.40 32151.31 43381.79 9243.35 0.00 179877.36 0.00
October 405716.76 02-OCT-19:10 62892.57 88772.42 15448.40 32151.31 36738.48 9179.67 0.00 144151.40 0.00
November 324007.21 01-NOV-18:10 55920.94 79417.81 15448.40 31837.63 29246.39 9186.86 0.00 94715.63 0.00
December 269219.38 26-DEC-20:10 62892.57 88772.42 15448.40 32151.31 26414.31 6797.27 0.00 31255.54 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 259268.36   55920.94 79417.81 15448.40 31837.63 22343.92 6018.47 0.00 25483.01 0.00
Maximum of Months 463845.66   62892.57 88772.42 15448.40 32159.77 43756.81 9287.71 0.00 195956.36 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 169509.67 13-JAN-02:39 0.00 245388.03 25-JAN-21:19 0.00
February 104248.32 01-FEB-18:10 0.00 176232.64 02-FEB-03:39 0.00 245341.11 01-FEB-21:19 0.00
March 104248.32 01-MAR-18:10 0.00 172512.98 30-MAR-06:30 0.00 244509.35 01-MAR-21:40 0.00
April 104248.32 01-APR-17:10 0.00 70068.25 21-APR-03:30 0.00 237665.39 04-APR-17:49 0.00
May 104248.32 01-MAY-17:10 0.00 16247.84 01-MAY-04:10 0.00 214044.61 01-MAY-20:10 0.00
June 104248.32 01-JUN-17:10 0.00 3847.31 10-JUN-08:09 0.00 210227.16 01-JUN-20:19 0.00
July 104248.32 01-JUL-17:10 0.00 6120.01 27-JUL-08:09 0.00 207207.19 05-JUL-20:49 0.00
August 104248.32 01-AUG-17:10 0.00 6213.45 30-AUG-08:09 0.00 208475.31 31-AUG-20:49 0.00
September 104248.32 01-SEP-17:10 0.00 6234.40 21-SEP-08:09 0.00 211831.13 29-SEP-20:00 0.00
October 104248.32 02-OCT-17:10 0.00 159135.30 12-OCT-04:00 0.00 224133.60 31-OCT-20:19 0.00
November 104248.32 01-NOV-17:10 0.00 173145.29 04-NOV-06:30 0.00 243496.63 29-NOV-21:19 0.00
December 104248.32 01-DEC-18:10 0.00 174539.79 19-DEC-03:09 0.00 245140.62 07-DEC-21:10 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 3847.31   0.00 207207.19   0.00
Maximum of Months 104248.32   0.00 176232.64   0.00 245388.03   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 15.67 25.03 15.67 25.03
February 0.00 0.00 0.00 0.00 10.83 24.98 10.83 24.98
March 0.00 0.00 0.00 0.00 10.67 24.96 10.67 24.96
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 1.67 24.87 1.67 24.87
November 0.00 0.00 0.00 0.00 7.33 24.99 7.33 24.99
December 0.00 0.00 0.00 0.00 19.33 24.99 19.33 24.99
                 
Annual Sum or Average 0.00   0.00   65.50 24.99 65.50 24.99
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 19.33 25.03 19.33 25.03



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 24.70 0.17 24.70
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.17 24.70 0.17 24.70
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 24.70 0.17 24.70



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 6.00 21.94 6.00 21.94
July 0.00 0.00 0.00 0.00 1.50 21.79 1.50 21.79
August 0.00 0.00 0.00 0.00 2.50 21.80 2.50 21.80
September 0.00 0.00 0.00 0.00 1.33 21.91 1.33 21.91
October 0.00 0.00 0.00 0.00 1.33 21.85 1.33 21.85
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   12.67 21.88 12.67 21.88
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.00 21.94 6.00 21.94



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 7.83 21.94 7.83 21.94
July 0.00 0.00 0.00 0.00 1.50 21.78 1.50 21.78
August 0.00 0.00 0.00 0.00 0.83 21.86 0.83 21.86
September 0.00 0.00 0.00 0.00 0.50 21.76 0.50 21.76
October 0.00 0.00 0.00 0.00 0.17 21.77 0.17 21.77
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   10.83 21.90 10.83 21.90
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 7.83 21.94 7.83 21.94



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 2.67 21.87 2.67 21.87
July 0.00 0.00 0.00 0.00 1.17 21.71 1.17 21.71
August 0.00 0.00 0.00 0.00 0.17 21.84 0.17 21.84
September 0.00 0.00 0.00 0.00 0.83 21.69 0.83 21.69
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.83 21.80 4.83 21.80
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.67 21.87 2.67 21.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.75 0.17 21.75
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 4.50 21.87 4.50 21.87
July 0.00 0.00 0.00 0.00 1.33 21.74 1.33 21.74
August 0.00 0.00 0.00 0.00 0.83 21.79 0.83 21.79
September 0.00 0.00 0.00 0.00 0.83 21.75 0.83 21.75
October 0.00 0.00 0.00 0.00 0.33 21.83 0.33 21.83
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   8.00 21.82 8.00 21.82
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 4.50 21.87 4.50 21.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.70 0.17 21.70
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 5.50 21.89 5.50 21.89
July 0.00 0.00 0.00 0.00 1.33 21.74 1.33 21.74
August 0.00 0.00 0.00 0.00 0.33 21.79 0.33 21.79
September 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   7.50 21.85 7.50 21.85
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.50 21.89 5.50 21.89



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 8.83 22.00 8.83 22.00
July 0.00 0.00 0.00 0.00 1.50 21.87 1.50 21.87
August 0.00 0.00 0.00 0.00 3.17 21.85 3.17 21.85
September 0.00 0.00 0.00 0.00 1.50 21.95 1.50 21.95
October 0.00 0.00 0.00 0.00 1.33 21.94 1.33 21.94
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   16.33 21.95 16.33 21.95
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 8.83 22.00 8.83 22.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 9.83 22.05 9.83 22.05
July 0.00 0.00 0.00 0.00 1.67 21.84 1.67 21.84
August 0.00 0.00 0.00 0.00 2.67 21.79 2.67 21.79
September 0.00 0.00 0.00 0.00 0.67 21.80 0.67 21.80
October 0.00 0.00 0.00 0.00 0.17 21.81 0.17 21.81
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   15.00 21.96 15.00 21.96
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 9.83 22.05 9.83 22.05



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.50 22.00 0.50 22.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.33 21.77 0.33 21.77
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 2.17 21.82 2.17 21.82
July 0.00 0.00 0.00 0.00 1.17 21.72 1.17 21.72
August 0.00 0.00 0.00 0.00 4.17 21.87 4.17 21.87
September 0.00 0.00 0.00 0.00 5.00 21.91 5.00 21.91
October 0.00 0.00 0.00 0.00 4.33 21.97 4.33 21.97
November 0.00 0.00 0.00 0.00 1.17 21.85 1.17 21.85
December 0.00 0.00 0.00 0.00 0.33 21.68 0.33 21.68
                 
Annual Sum or Average 0.00   0.00   19.17 21.88 19.17 21.88
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.00 22.00 5.00 22.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.67 24.83 0.67 24.83
February 0.00 0.00 0.00 0.00 0.17 24.57 0.17 24.57
March 0.00 0.00 0.00 0.00 0.67 24.92 0.67 24.92
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.17 24.58 0.17 24.58
December 0.00 0.00 0.00 0.00 0.67 24.67 0.67 24.67
                 
Annual Sum or Average 0.00   0.00   2.33 24.77 2.33 24.77
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.67 24.92 0.67 24.92



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.50 24.74 1.50 24.74
February 0.00 0.00 0.00 0.00 0.33 24.71 0.33 24.71
March 0.00 0.00 0.00 0.00 1.00 24.87 1.00 24.87
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.17 24.57 0.17 24.57
November 0.00 0.00 0.00 0.00 0.67 24.64 0.67 24.64
December 0.00 0.00 0.00 0.00 1.00 24.72 1.00 24.72
                 
Annual Sum or Average 0.00   0.00   4.67 24.74 4.67 24.74
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.50 24.87 1.50 24.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 18.00 25.03 18.00 25.03
February 0.00 0.00 0.00 0.00 11.00 25.09 11.00 25.09
March 0.00 0.00 0.00 0.00 11.83 25.08 11.83 25.08
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 2.50 24.89 2.50 24.89
November 0.00 0.00 0.00 0.00 9.50 24.96 9.50 24.96
December 0.00 0.00 0.00 0.00 20.00 25.01 20.00 25.01
                 
Annual Sum or Average 0.00   0.00   72.83 25.03 72.83 25.03
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 20.00 25.09 20.00 25.09



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 547.50 23.93 12.83 23.93 0.00 23.93
February 418.50 23.59 39.67 23.62 0.00 23.62
March 724.67 23.29 0.00 23.29 0.00 23.29
April 705.83 23.57 0.00 23.57 0.00 23.57
May 744.00 23.34 0.00 23.34 0.00 23.34
June 611.67 23.53 5.00 23.53 0.00 23.53
July 277.67 23.94 517.17 23.95 173.67 23.96
August 222.50 24.00 618.50 23.99 173.33 23.99
September 115.67 24.00 541.50 24.00 115.67 24.00
October 280.00 24.00 157.00 24.00 21.67 24.00
November 344.33 24.00 164.00 24.00 29.17 24.00
December 640.00 24.00 6.67 24.00 0.00 24.00
             
Annual Sum or Average 5632.33 23.68 2062.33 23.76 513.50 23.77
Minimum of Months 115.67 23.29 0.00 23.29 0.00 23.29
Maximum of Months 744.00 24.00 618.50 24.00 173.67 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 393.67 22.56 129.83 22.91 0.83 22.91
February 537.33 21.98 48.33 22.14 0.00 22.14
March 551.33 22.32 54.83 22.45 4.50 22.44
April 250.00 23.31 132.17 23.55 0.00 23.55
May 196.50 23.63 60.17 23.72 0.00 23.72
June 11.17 23.97 467.17 24.00 0.00 24.00
July 182.17 23.98 656.33 23.99 161.83 23.99
August 181.00 23.94 694.17 23.98 181.00 23.97
September 151.83 23.96 675.33 23.98 150.17 23.98
October 275.67 22.97 298.33 23.50 25.67 23.52
November 405.17 22.61 191.50 22.93 48.67 22.90
December 549.83 22.22 84.50 22.32 28.67 22.26
             
Annual Sum or Average 3685.67 22.73 3492.67 23.32 601.33 23.35
Minimum of Months 11.17 21.98 48.33 22.14 0.00 22.14
Maximum of Months 551.33 23.98 694.17 24.00 181.00 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 633.83 23.13 5.50 23.13 0.00 23.13
February 622.00 22.59 4.83 22.60 0.00 22.60
March 636.00 22.82 0.83 22.82 0.00 22.82
April 387.17 23.57 20.50 23.59 0.00 23.59
May 336.17 23.69 10.33 23.70 0.00 23.70
June 56.67 23.68 208.83 23.92 0.00 23.92
July 225.83 23.97 578.67 23.95 189.33 23.95
August 211.50 23.97 625.00 23.94 206.67 23.95
September 163.17 23.97 589.00 23.94 162.33 23.94
October 408.50 23.37 154.50 23.53 30.33 23.55
November 571.00 23.14 93.67 23.20 46.33 23.20
December 729.50 22.80 0.00 22.80 0.00 22.80
             
Annual Sum or Average 4981.33 23.17 2291.67 23.41 635.00 23.45
Minimum of Months 56.67 22.59 0.00 22.60 0.00 22.60
Maximum of Months 729.50 23.97 625.00 23.95 206.67 23.95



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 743.83 22.56 0.00 22.56 0.00 22.56
February 672.00 22.13 0.00 22.13 0.00 22.13
March 739.67 22.58 0.00 22.58 0.00 22.58
April 609.67 23.76 0.00 23.76 0.00 23.76
May 587.33 23.99 0.00 23.99 0.00 23.99
June 140.00 24.00 57.67 24.00 0.00 24.00
July 88.50 24.00 550.33 24.00 23.50 24.00
August 69.33 24.00 618.50 24.00 18.67 24.00
September 42.00 24.00 509.67 24.00 39.50 24.00
October 527.33 23.35 107.50 23.46 2.83 23.46
November 683.50 22.75 23.00 22.77 16.50 22.77
December 744.00 22.00 25.17 21.97 25.17 21.94
             
Annual Sum or Average 5647.17 22.90 1891.83 23.16 126.17 23.16
Minimum of Months 42.00 22.00 0.00 21.97 0.00 21.94
Maximum of Months 744.00 24.00 618.50 24.00 39.50 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.55 10.83 21.54 10.83 21.53
February 672.00 21.17 0.00 21.17 0.00 21.17
March 744.00 21.53 19.67 21.52 19.67 21.50
April 719.50 22.77 0.00 22.77 0.00 22.77
May 742.50 23.26 0.00 23.26 0.00 23.26
June 380.83 23.72 37.50 23.74 0.00 23.74
July 165.83 23.70 412.67 23.80 32.17 23.80
August 167.17 23.47 361.00 23.70 17.00 23.69
September 308.17 23.34 187.67 23.47 39.00 23.46
October 642.67 22.39 38.83 22.46 3.50 22.47
November 720.00 21.70 12.83 21.70 12.83 21.69
December 744.00 21.21 115.50 21.18 115.50 21.16
             
Annual Sum or Average 6750.67 22.19 1196.50 22.38 250.50 22.36
Minimum of Months 165.83 21.17 0.00 21.17 0.00 21.16
Maximum of Months 744.00 23.72 412.67 23.80 115.50 23.80



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 212.50 24.06 738.50 24.00 212.50 24.01
February 252.17 24.04 669.67 23.98 252.17 23.99
March 248.83 24.04 739.50 23.99 248.83 24.00
April 242.00 24.00 719.67 24.00 242.00 24.00
May 269.50 24.00 744.00 24.00 269.50 24.00
June 435.33 24.00 720.00 24.00 435.33 24.00
July 616.67 24.00 744.00 24.00 616.67 24.00
August 645.33 24.00 744.00 24.00 645.33 24.00
September 580.17 24.00 720.00 24.00 580.17 24.00
October 325.33 24.01 743.83 23.99 325.33 23.99
November 262.50 24.02 715.67 23.98 262.50 23.99
December 166.33 24.12 725.17 24.02 166.33 24.03
             
Annual Sum or Average 4256.67 24.01 8724.00 24.00 4256.67 24.00
Minimum of Months 166.33 24.00 669.67 23.98 166.33 23.99
Maximum of Months 645.33 24.12 744.00 24.02 645.33 24.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 434.00 22.66 169.33 23.00 4.50 22.99
February 568.00 22.11 65.17 22.23 22.00 22.24
March 628.17 22.20 33.17 22.28 0.17 22.28
April 322.00 22.70 141.00 23.06 0.00 23.06
May 368.83 22.72 105.33 22.99 0.00 22.99
June 115.17 22.62 414.67 23.56 2.17 23.56
July 303.83 23.67 616.67 23.60 262.83 23.64
August 304.17 23.67 681.00 23.63 289.50 23.65
September 255.33 23.58 665.17 23.65 237.00 23.65
October 315.83 22.78 316.00 23.29 48.50 23.31
November 449.17 22.56 229.67 22.87 62.17 22.84
December 573.83 22.36 84.67 22.57 0.00 22.57
             
Annual Sum or Average 4638.33 22.68 3521.83 23.11 928.83 23.16
Minimum of Months 115.17 22.11 33.17 22.23 0.00 22.24
Maximum of Months 628.17 23.67 681.00 23.65 289.50 23.65



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 493.33 23.30 25.50 23.32 9.67 23.32
February 548.33 22.81 52.50 22.89 27.50 22.92
March 535.83 22.87 26.67 22.91 4.33 22.92
April 334.33 23.38 40.17 23.45 0.00 23.45
May 309.67 23.38 36.50 23.44 0.00 23.44
June 77.17 23.33 320.67 23.84 1.00 23.84
July 282.83 23.93 607.50 23.87 260.33 23.90
August 291.50 23.94 654.00 23.88 287.33 23.90
September 234.17 23.93 651.33 23.89 233.67 23.90
October 289.17 23.40 206.00 23.61 49.50 23.64
November 452.17 23.27 151.17 23.36 72.33 23.35
December 677.67 23.09 0.00 23.09 0.00 23.09
             
Annual Sum or Average 4526.17 23.29 2772.00 23.51 945.67 23.55
Minimum of Months 77.17 22.81 0.00 22.89 0.00 22.92
Maximum of Months 677.67 23.94 654.00 23.89 287.33 23.90



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 739.50 21.56 15.83 21.55 15.83 21.54
February 671.17 21.32 8.00 21.30 8.00 21.29
March 740.83 21.45 36.83 21.43 36.83 21.41
April 694.00 21.63 0.00 21.63 0.00 21.63
May 713.67 21.65 0.00 21.65 0.00 21.65
June 628.00 21.53 8.00 21.55 0.00 21.55
July 606.83 21.39 25.83 21.47 0.00 21.47
August 591.67 21.33 36.50 21.45 0.67 21.45
September 582.33 21.36 32.17 21.46 4.00 21.47
October 689.17 21.52 8.67 21.53 2.67 21.53
November 700.67 21.51 56.83 21.50 54.00 21.48
December 743.17 21.44 179.00 21.36 179.00 21.31
             
Annual Sum or Average 8101.00 21.48 407.67 21.49 301.00 21.47
Minimum of Months 582.33 21.32 0.00 21.30 0.00 21.29
Maximum of Months 743.17 21.65 179.00 21.65 179.00 21.65



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.30 67.00 21.26 67.00 21.22
February 672.00 21.08 40.00 21.04 40.00 21.01
March 744.00 21.31 79.50 21.27 79.50 21.23
April 708.17 21.64 0.00 21.64 0.00 21.64
May 719.33 21.67 0.00 21.67 0.00 21.67
June 628.83 21.54 9.00 21.57 0.00 21.57
July 610.00 21.40 21.50 21.47 0.00 21.47
August 606.17 21.38 25.00 21.45 0.83 21.46
September 618.17 21.46 15.33 21.50 4.50 21.51
October 716.83 21.47 20.50 21.46 20.33 21.44
November 716.33 21.34 122.67 21.30 122.67 21.26
December 744.00 21.09 397.83 21.01 397.83 20.98
             
Annual Sum or Average 8227.83 21.39 798.33 21.36 732.67 21.32
Minimum of Months 606.17 21.08 0.00 21.01 0.00 20.98
Maximum of Months 744.00 21.67 397.83 21.67 397.83 21.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.12 56.83 21.10 56.83 21.09
February 672.00 21.10 23.83 21.09 23.83 21.07
March 744.00 21.20 78.00 21.18 78.00 21.16
April 720.00 21.48 0.17 21.48 0.17 21.48
May 744.00 21.61 0.00 21.61 0.00 21.61
June 720.00 21.70 0.00 21.70 0.00 21.70
July 744.00 21.69 0.00 21.69 0.00 21.69
August 744.00 21.66 1.33 21.67 1.33 21.67
September 720.00 21.63 2.17 21.63 2.17 21.63
October 744.00 21.36 23.83 21.35 23.83 21.35
November 720.00 21.16 105.33 21.14 105.33 21.13
December 744.00 21.03 384.00 21.00 384.00 20.98
             
Annual Sum or Average 8760.00 21.40 675.50 21.37 675.50 21.34
Minimum of Months 672.00 21.03 0.00 21.00 0.00 20.98
Maximum of Months 744.00 21.70 384.00 21.70 384.00 21.70



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.63 17.00 21.62 17.00 21.61
February 672.00 21.42 10.67 21.41 10.67 21.39
March 741.17 21.57 30.00 21.55 30.00 21.53
April 698.50 21.70 0.00 21.70 0.00 21.70
May 736.17 21.73 0.00 21.73 0.00 21.73
June 579.50 21.39 7.00 21.41 0.00 21.41
July 571.83 21.29 33.50 21.40 0.00 21.40
August 554.17 21.22 46.83 21.38 0.33 21.38
September 558.67 21.29 30.50 21.40 2.00 21.40
October 687.17 21.57 6.17 21.59 0.00 21.59
November 712.33 21.59 64.33 21.55 64.33 21.52
December 744.00 21.50 165.83 21.43 165.83 21.37
             
Annual Sum or Average 7999.50 21.51 411.83 21.52 290.17 21.51
Minimum of Months 554.17 21.22 0.00 21.38 0.00 21.37
Maximum of Months 744.00 21.73 165.83 21.73 165.83 21.73



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.35 67.33 21.32 67.33 21.29
February 672.00 21.18 24.00 21.16 24.00 21.14
March 744.00 21.44 46.33 21.42 46.33 21.40
April 717.83 21.74 0.00 21.74 0.00 21.74
May 738.67 21.74 0.00 21.74 0.00 21.74
June 581.83 21.40 7.33 21.42 0.00 21.42
July 574.17 21.29 28.17 21.39 0.00 21.39
August 568.33 21.27 16.33 21.32 1.00 21.33
September 576.00 21.35 5.00 21.36 3.00 21.37
October 710.50 21.55 7.33 21.55 7.33 21.55
November 720.00 21.37 133.67 21.33 133.67 21.29
December 744.00 21.12 372.00 21.07 372.00 21.04
             
Annual Sum or Average 8091.33 21.41 707.50 21.39 654.67 21.36
Minimum of Months 568.33 21.12 0.00 21.07 0.00 21.04
Maximum of Months 744.00 21.74 372.00 21.74 372.00 21.74



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 22.81 0.00 22.81 0.00 22.81
February 672.00 22.18 3.50 22.18 3.50 22.17
March 744.00 22.59 0.00 22.59 0.00 22.59
April 665.67 23.73 0.00 23.73 0.00 23.73
May 700.83 23.94 0.00 23.94 0.00 23.94
June 287.00 24.00 34.17 24.00 0.00 24.00
July 332.83 23.99 532.33 23.99 221.83 23.99
August 321.17 23.98 608.00 23.98 248.17 23.98
September 223.50 23.97 493.83 23.98 205.67 23.97
October 564.17 23.49 107.67 23.57 36.00 23.59
November 701.33 22.96 63.83 22.95 61.83 22.94
December 744.00 22.27 0.00 22.27 0.00 22.27
             
Annual Sum or Average 6700.50 23.15 1843.33 23.32 777.00 23.37
Minimum of Months 223.50 22.18 0.00 22.18 0.00 22.17
Maximum of Months 744.00 24.00 608.00 24.00 248.17 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 738.33 21.51 69.83 21.46 69.83 21.42
February 670.83 21.23 62.67 21.17 62.67 21.11
March 737.83 21.39 84.83 21.34 84.83 21.30
April 675.50 21.57 9.33 21.56 9.33 21.55
May 693.50 21.59 0.00 21.59 0.00 21.59
June 590.33 21.43 20.17 21.49 0.00 21.49
July 589.00 21.33 57.67 21.51 0.00 21.51
August 577.67 21.29 72.33 21.52 1.67 21.52
September 570.67 21.31 63.83 21.50 9.00 21.51
October 682.67 21.46 51.17 21.48 36.67 21.45
November 698.17 21.44 148.33 21.39 144.00 21.34
December 742.00 21.37 325.83 21.25 325.83 21.19
             
Annual Sum or Average 7966.50 21.42 966.00 21.43 743.83 21.39
Minimum of Months 570.67 21.23 0.00 21.17 0.00 21.11
Maximum of Months 742.00 21.59 325.83 21.59 325.83 21.59



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.20 210.50 21.12 210.50 21.08
February 672.00 20.98 135.00 20.88 135.00 20.81
March 744.00 21.24 130.00 21.17 130.00 21.12
April 696.50 21.60 11.00 21.59 11.00 21.58
May 701.83 21.62 0.00 21.62 0.00 21.62
June 592.00 21.45 21.83 21.51 0.00 21.51
July 591.00 21.34 50.17 21.50 0.00 21.50
August 589.17 21.32 52.50 21.49 2.00 21.49
September 599.50 21.39 35.00 21.48 8.67 21.49
October 711.67 21.40 82.83 21.36 80.50 21.32
November 716.33 21.25 248.67 21.17 248.67 21.13
December 744.00 20.98 538.17 20.91 538.17 20.89
             
Annual Sum or Average 8102.00 21.31 1515.67 21.27 1364.50 21.22
Minimum of Months 589.17 20.98 0.00 20.88 0.00 20.81
Maximum of Months 744.00 21.62 538.17 21.62 538.17 21.62



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 655.33 21.45 2.50 21.45 2.50 21.45
February 640.50 21.40 4.33 21.39 4.33 21.38
March 730.00 21.52 41.00 21.49 41.00 21.46
April 692.00 21.61 7.17 21.61 7.17 21.60
May 744.00 21.70 0.00 21.70 0.00 21.70
June 675.83 21.63 0.00 21.63 0.00 21.63
July 633.17 21.45 0.00 21.45 0.00 21.45
August 602.17 21.36 14.50 21.40 2.17 21.41
September 581.50 21.35 47.00 21.49 4.50 21.50
October 648.00 21.45 21.33 21.51 0.00 21.51
November 651.50 21.46 57.00 21.47 46.50 21.45
December 702.00 21.52 75.17 21.48 75.17 21.45
             
Annual Sum or Average 7956.00 21.50 270.00 21.51 183.33 21.50
Minimum of Months 581.50 21.35 0.00 21.39 0.00 21.38
Maximum of Months 744.00 21.70 75.17 21.70 75.17 21.70



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 602.00 22.61 26.33 22.66 6.33 22.66
February 520.17 22.47 79.33 22.62 27.83 22.67
March 487.17 22.53 87.17 22.73 3.83 22.74
April 280.67 22.84 129.50 23.19 0.00 23.19
May 173.17 22.86 178.50 23.43 0.00 23.43
June 25.50 22.81 487.83 23.81 2.33 23.81
July 266.17 23.92 658.67 23.75 259.83 23.79
August 298.17 23.88 676.33 23.70 291.67 23.75
September 242.67 23.83 637.00 23.69 235.33 23.72
October 396.67 22.85 202.67 23.12 50.17 23.17
November 549.67 22.67 119.83 22.83 65.50 22.87
December 709.67 22.55 3.00 22.55 0.00 22.55
             
Annual Sum or Average 4551.67 22.85 3286.17 23.21 942.83 23.28
Minimum of Months 25.50 22.47 3.00 22.55 0.00 22.55
Maximum of Months 709.67 23.92 676.33 23.81 291.67 23.81



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 466.17 22.74 67.00 22.87 6.50 22.88
February 363.33 22.62 179.33 23.00 29.00 23.04
March 348.33 22.69 182.83 23.10 4.00 23.11
April 133.67 22.90 207.50 23.54 0.00 23.54
May 53.17 22.92 280.00 23.79 0.00 23.79
June 3.00 23.60 589.00 23.90 2.17 23.90
July 254.67 23.98 683.83 23.85 254.33 23.88
August 286.83 23.95 707.67 23.81 286.50 23.84
September 228.50 23.92 689.17 23.78 228.33 23.81
October 272.00 22.98 267.83 23.36 50.17 23.40
November 437.67 22.89 170.67 23.11 66.50 23.15
December 624.33 22.78 8.50 22.79 0.00 22.79
             
Annual Sum or Average 3471.67 23.04 4033.33 23.45 927.50 23.50
Minimum of Months 3.00 22.62 8.50 22.79 0.00 22.79
Maximum of Months 624.33 23.98 707.67 23.90 286.50 23.90



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 511.83 24.02 744.00 24.02 511.83 24.02
February 479.33 24.02 670.00 24.01 479.33 24.01
March 519.50 24.01 743.00 24.00 519.50 24.01
April 511.00 23.99 720.00 23.99 511.00 23.99
May 535.17 23.99 744.00 23.99 535.17 23.99
June 554.00 23.99 720.00 23.99 554.00 23.99
July 691.83 23.99 744.00 23.99 691.83 23.99
August 701.33 23.99 744.00 23.99 701.33 23.99
September 643.00 23.99 720.00 23.99 643.00 23.99
October 548.67 23.99 744.00 23.99 548.67 23.99
November 519.00 24.00 719.17 24.00 519.00 24.00
December 483.83 24.03 736.33 24.03 483.83 24.03
             
Annual Sum or Average 6698.50 24.00 8748.50 24.00 6698.50 24.00
Minimum of Months 479.33 23.99 670.00 23.99 479.33 23.99
Maximum of Months 701.33 24.03 744.00 24.03 701.33 24.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 22.95 0.00 22.95 0.00 22.95
February 672.00 22.28 0.00 22.28 0.00 22.28
March 695.33 22.73 0.00 22.73 0.00 22.73
April 459.33 23.77 0.00 23.77 0.00 23.77
May 335.83 23.93 1.67 23.93 0.00 23.93
June 51.00 24.00 118.33 24.00 0.00 24.00
July 172.00 24.00 578.83 24.00 136.50 24.00
August 177.50 23.99 633.67 24.00 153.83 24.00
September 131.83 24.00 546.17 24.00 131.83 24.00
October 477.17 23.43 135.00 23.55 22.67 23.57
November 648.83 22.99 67.17 23.02 43.33 23.02
December 744.00 22.24 10.33 22.22 10.33 22.20
             
Annual Sum or Average 5308.83 23.02 2091.17 23.29 498.50 23.32
Minimum of Months 51.00 22.24 0.00 22.22 0.00 22.20
Maximum of Months 744.00 24.00 633.67 24.00 153.83 24.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.94353 25.93477 0.23523 6.25580
February 672.00000 23.69164 39.31904 0.24704 6.43764
March 744.00000 23.30600 32.15278 0.09647 5.41297
April 720.00000 23.57952 23.68104 0.11308 5.45166
May 744.00000 23.34262 23.44041 -0.9299 23.52027
June 720.00000 23.57551 33.27054 -0.7752 17.94904
July 744.00000 23.93457 48.74092 -0.5128 10.77993
August 744.00000 23.98856 51.02720 -0.4650 9.64161
September 720.00000 23.99954 49.79708 -0.4495 9.33052
October 744.00000 23.99956 30.45716 0.31009 7.19458
November 720.00000 24.00032 29.95709 0.30398 7.13987
December 744.00000 24.00237 18.85450 0.22044 6.04586
           
Annual Sum or Average 8760.00000 23.78095 33.83821 -0.1362 9.61854
Minimum of Months 672.00000 23.30600 18.85450 -0.9299 5.41297
Maximum of Months 744.00000 24.00237 51.02720 0.31009 23.52027



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.22584 26.77659 0.15959 6.99540
February 672.00000 22.36280 42.02252 -0.0133 6.51507
March 744.00000 22.74459 32.46445 0.02982 6.60378
April 720.00000 23.75614 22.27873 0.27637 7.21082
May 744.00000 23.90007 21.43200 -0.5665 12.21047
June 720.00000 23.99864 30.47036 -0.4027 8.61191
July 744.00000 23.99348 47.77055 -0.2975 7.14491
August 744.00000 23.98546 50.47120 -0.2749 6.85654
September 720.00000 23.98032 49.89393 -0.2831 7.02312
October 744.00000 23.60652 31.34100 0.31012 8.41407
November 720.00000 23.19254 32.07843 0.17887 7.21601
December 744.00000 22.68098 20.55840 -0.0460 7.22955
           
Annual Sum or Average 8760.00000 23.45817 33.90004 -0.0782 7.68048
Minimum of Months 672.00000 22.36280 20.55840 -0.5665 6.51507
Maximum of Months 744.00000 23.99864 50.47120 0.31012 12.21047



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.24254 27.54867 0.11274 5.60030
February 672.00000 22.67768 41.76475 0.05414 5.47711
March 744.00000 22.97170 32.67450 0.07551 5.71937
April 720.00000 23.75316 23.16111 0.22986 6.34446
May 744.00000 23.85137 22.34547 -0.6411 13.85061
June 720.00000 23.94946 31.70253 -0.5165 10.75248
July 744.00000 23.92799 48.90909 -0.4161 8.86536
August 744.00000 23.92119 51.64572 -0.4007 8.52733
September 720.00000 23.91150 51.03096 -0.4158 8.78884
October 744.00000 23.61098 32.26587 0.25160 6.90060
November 720.00000 23.27772 32.57661 0.15673 6.03788
December 744.00000 22.81938 21.24526 -0.0403 5.49628
           
Annual Sum or Average 8760.00000 23.49707 34.68280 -0.1306 7.71185
Minimum of Months 672.00000 22.67768 21.24526 -0.6411 5.47711
Maximum of Months 744.00000 23.94946 51.64572 0.25160 13.85061



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.97130 22.45234 0.84241 20.88001
February 672.00000 23.95156 34.93887 0.90746 23.31982
March 744.00000 23.96076 27.01122 0.87436 22.03822
April 720.00000 23.99617 19.23266 0.88985 22.55616
May 744.00000 24.00025 18.71699 0.29698 8.62301
June 720.00000 24.00036 28.55863 0.41238 10.28074
July 744.00000 24.00016 45.29113 0.50918 12.12273
August 744.00000 24.00052 47.97319 0.52309 12.36239
September 720.00000 24.00059 47.18486 0.49435 11.76809
October 744.00000 23.98335 27.88242 0.92564 24.01695
November 720.00000 23.96570 27.39000 0.87997 22.35717
December 744.00000 23.97431 16.09548 0.77669 18.64453
           
Annual Sum or Average 8760.00000 23.98394 30.18460 0.69289 17.37299
Minimum of Months 672.00000 23.95156 16.09548 0.29698 8.62301
Maximum of Months 744.00000 24.00059 47.97319 0.92564 24.01695



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.09782 30.23250 0.22051 7.03533
February 672.00000 22.29523 45.05857 0.06105 5.90907
March 744.00000 22.38193 36.05938 0.03752 5.96540
April 720.00000 23.21826 26.59586 0.23742 6.92174
May 744.00000 23.18435 26.04526 -0.6892 15.89636
June 720.00000 23.49931 35.52754 -0.4674 10.32981
July 744.00000 23.48350 52.99507 -0.3597 8.44819
August 744.00000 23.55822 55.59176 -0.3099 7.70382
September 720.00000 23.60627 54.68148 -0.2982 7.61220
October 744.00000 23.31439 35.36772 0.33050 8.59157
November 720.00000 22.97421 35.66998 0.21752 7.15486
December 744.00000 22.67601 23.74799 0.04517 6.44122
           
Annual Sum or Average 8760.00000 23.11176 38.07429 -0.0824 8.18781
Minimum of Months 672.00000 22.29523 23.74799 -0.6892 5.90907
Maximum of Months 744.00000 23.60627 55.59176 0.33050 15.89636



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.49051 30.03350 0.21095 6.17332
February 672.00000 22.98411 43.89293 0.15972 5.95737
March 744.00000 23.13735 35.21961 0.14852 6.04106
April 720.00000 23.67330 25.96825 0.25045 6.56846
May 744.00000 23.71041 25.14268 -0.6386 13.89014
June 720.00000 23.83959 34.41508 -0.4991 10.49760
July 744.00000 23.83538 51.55809 -0.3878 8.48038
August 744.00000 23.84622 54.27540 -0.3671 8.03335
September 720.00000 23.86467 53.51918 -0.3695 8.04818
October 744.00000 23.68844 34.78051 0.31408 7.54067
November 720.00000 23.46896 35.07007 0.24086 6.64323
December 744.00000 23.16894 23.76439 0.07787 5.50756
           
Annual Sum or Average 8760.00000 23.56204 37.24981 -0.0733 7.79504
Minimum of Months 672.00000 22.98411 23.76439 -0.6386 5.50756
Maximum of Months 744.00000 23.86467 54.27540 0.31408 13.89014



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.57479 31.35848 -0.2797 7.52648
February 672.00000 21.31756 46.20666 -0.3104 7.52478
March 744.00000 21.46127 36.46182 -0.2957 7.56243
April 720.00000 21.69266 26.04459 -0.1858 6.70857
May 744.00000 21.72173 24.61847 -1.2348 38.18209
June 720.00000 21.75462 33.15837 -1.1007 32.05022
July 744.00000 21.74254 45.24108 -1.0665 30.52379
August 744.00000 21.73928 47.56156 -1.0589 30.27762
September 720.00000 21.73226 48.80436 -1.0761 31.02352
October 744.00000 21.65389 34.70554 -0.1770 6.81466
November 720.00000 21.56102 36.42985 -0.2476 7.26263
December 744.00000 21.44556 23.69193 -0.4070 9.38739
           
Annual Sum or Average 8760.00000 21.61814 36.10879 -0.6222 17.97411
Minimum of Months 672.00000 21.31756 23.69193 -1.2348 6.70857
Maximum of Months 744.00000 21.75462 48.80436 -0.1770 38.18209



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.29541 31.82787 -0.4017 8.85005
February 672.00000 21.08121 46.75580 -0.3984 8.58337
March 744.00000 21.30992 36.74391 -0.3546 8.20247
April 720.00000 21.67039 26.10071 -0.2107 6.80505
May 744.00000 21.72156 24.66089 -1.2413 38.43965
June 720.00000 21.75878 33.16989 -1.0954 31.79865
July 744.00000 21.74389 45.26745 -1.0669 30.50581
August 744.00000 21.73612 47.76422 -1.0728 30.79291
September 720.00000 21.72257 49.23430 -1.1037 32.08526
October 744.00000 21.54049 35.08270 -0.2399 7.22264
November 720.00000 21.35029 37.01715 -0.3431 8.21121
December 744.00000 21.08841 24.09927 -0.5448 11.71469
           
Annual Sum or Average 8760.00000 21.50368 36.39359 -0.6749 18.67100
Minimum of Months 672.00000 21.08121 24.09927 -1.2413 6.80505
Maximum of Months 744.00000 21.75878 49.23430 -0.2107 38.43965



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.11737 31.35610 -0.4710 9.74168
February 672.00000 21.09706 45.87662 -0.3956 8.41353
March 744.00000 21.19977 36.15165 -0.4063 8.64466
April 720.00000 21.48431 25.66410 -0.3537 7.96324
May 744.00000 21.60871 24.19690 -1.4372 47.83721
June 720.00000 21.70418 33.08021 -1.3075 41.34725
July 744.00000 21.69040 45.86789 -1.2447 38.28947
August 744.00000 21.66469 48.45971 -1.2530 38.66085
September 720.00000 21.62503 49.76491 -1.2725 39.52239
October 744.00000 21.36471 34.67173 -0.3461 8.00832
November 720.00000 21.15850 36.43303 -0.4219 9.04675
December 744.00000 21.02790 23.49530 -0.5593 11.67321
           
Annual Sum or Average 8760.00000 21.39660 36.17258 -0.7918 22.52188
Minimum of Months 672.00000 21.02790 23.49530 -1.4372 7.96324
Maximum of Months 744.00000 21.70418 49.76491 -0.3461 47.83721



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.63446 31.25468 -0.2682 7.42081
February 672.00000 21.42469 45.80133 -0.2782 7.28548
March 744.00000 21.57337 36.28124 -0.2635 7.28152
April 720.00000 21.74414 26.01743 -0.1679 6.66305
May 744.00000 21.75080 24.62934 -1.2126 37.23513
June 720.00000 21.76483 33.23076 -1.0857 31.52206
July 744.00000 21.75756 45.17721 -1.0398 29.52622
August 744.00000 21.75423 47.43522 -1.0356 29.40388
September 720.00000 21.74799 48.64402 -1.0609 30.44665
October 744.00000 21.70744 34.58605 -0.1576 6.74613
November 720.00000 21.60408 36.46420 -0.2420 7.18472
December 744.00000 21.50243 23.62004 -0.3909 9.07656
           
Annual Sum or Average 8760.00000 21.66524 36.01542 -0.6025 17.55037
Minimum of Months 672.00000 21.42469 23.62004 -1.2126 6.66305
Maximum of Months 744.00000 21.76483 48.64402 -0.1576 37.23513



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.34716 31.73527 -0.3920 8.56957
February 672.00000 21.18344 46.39360 -0.3654 8.06622
March 744.00000 21.44213 36.49966 -0.3182 7.71525
April 720.00000 21.74048 26.04867 -0.1885 6.72538
May 744.00000 21.75070 24.67418 -1.2192 37.49379
June 720.00000 21.76737 33.25175 -1.0811 31.30174
July 744.00000 21.75797 45.23591 -1.0404 29.51927
August 744.00000 21.75281 47.59248 -1.0491 29.89517
September 720.00000 21.74416 48.97631 -1.0867 31.42764
October 744.00000 21.63446 34.83256 -0.2121 6.99788
November 720.00000 21.37334 37.00873 -0.3421 8.06679
December 744.00000 21.11764 24.03525 -0.5337 11.29212
           
Annual Sum or Average 8760.00000 21.55284 36.27493 -0.6545 18.15746
Minimum of Months 672.00000 21.11764 24.03525 -1.2192 6.72538
Maximum of Months 744.00000 21.76737 48.97631 -0.1885 37.49379



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.52041 31.62878 -0.3230 8.24099
February 672.00000 21.23492 46.89655 -0.3595 8.37301
March 744.00000 21.40206 36.80233 -0.3334 8.22738
April 720.00000 21.67495 26.16814 -0.1956 7.00597
May 744.00000 21.71234 24.70614 -1.2375 38.55623
June 720.00000 21.75630 33.32988 -1.0813 31.49171
July 744.00000 21.74227 45.45497 -1.0510 30.08707
August 744.00000 21.73738 47.91423 -1.0464 30.00375
September 720.00000 21.72438 49.43506 -1.0735 31.12320
October 744.00000 21.61566 35.02499 -0.2033 7.26928
November 720.00000 21.50155 37.08251 -0.2888 7.91675
December 744.00000 21.37128 23.87537 -0.4607 10.54709
           
Annual Sum or Average 8760.00000 21.58476 36.44160 -0.6399 18.30537
Minimum of Months 672.00000 21.23492 23.87537 -1.2375 7.00597
Maximum of Months 744.00000 21.75630 49.43506 -0.1956 38.55623



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.19962 32.20015 -0.4602 9.99555
February 672.00000 20.97515 47.49768 -0.4559 9.73972
March 744.00000 21.23920 37.11659 -0.3973 9.01680
April 720.00000 21.65347 26.23845 -0.2211 7.10323
May 744.00000 21.71262 24.76454 -1.2439 38.79480
June 720.00000 21.76081 33.36763 -1.0755 31.22417
July 744.00000 21.74378 45.47765 -1.0513 30.06077
August 744.00000 21.73357 48.12080 -1.0608 30.51290
September 720.00000 21.71392 49.90069 -1.1018 32.18798
October 744.00000 21.48595 35.47198 -0.2726 7.82833
November 720.00000 21.25652 37.71747 -0.3972 9.21160
December 744.00000 20.97600 24.34034 -0.6113 13.42277
           
Annual Sum or Average 8760.00000 21.45660 36.76415 -0.6977 19.15921
Minimum of Months 672.00000 20.97515 24.34034 -1.2439 7.10323
Maximum of Months 744.00000 21.76081 49.90069 -0.2211 38.79480



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.67755 32.32711 -0.2051 7.23224
February 672.00000 21.48583 46.46024 -0.2439 7.19632
March 744.00000 21.55164 37.09940 -0.2731 7.53811
April 720.00000 21.68028 27.18860 -0.2215 7.14276
May 744.00000 21.70269 25.90124 -1.3156 42.14048
June 720.00000 21.73581 34.42010 -1.1929 36.23377
July 744.00000 21.73413 45.92095 -1.1290 33.33216
August 744.00000 21.73507 48.10713 -1.1078 32.52191
September 720.00000 21.73367 49.25524 -1.0999 32.26217
October 744.00000 21.69108 35.38027 -0.1581 6.93893
November 720.00000 21.63735 37.10116 -0.1986 7.08635
December 744.00000 21.62643 25.07372 -0.2995 8.31243
           
Annual Sum or Average 8760.00000 21.66710 36.94231 -0.6229 19.07329
Minimum of Months 672.00000 21.48583 25.07372 -1.3156 6.93893
Maximum of Months 744.00000 21.73581 49.25524 -0.1581 42.14048



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.82841 30.65327 0.09745 5.81143
February 672.00000 22.70979 44.11941 0.14645 6.13490
March 744.00000 22.92243 35.34016 0.16280 6.25723
April 720.00000 23.39191 26.51603 0.27262 6.95982
May 744.00000 23.53417 25.66357 -0.5526 11.91714
June 720.00000 23.66709 35.25129 -0.3932 8.68281
July 744.00000 23.64666 52.43078 -0.2939 7.30547
August 744.00000 23.59527 55.38654 -0.3034 7.39432
September 720.00000 23.54711 54.80184 -0.3428 7.99111
October 744.00000 23.20307 35.74473 0.26766 7.35211
November 720.00000 22.89767 35.69981 0.15593 6.38217
December 744.00000 22.60822 24.03309 -0.0207 5.61579
           
Annual Sum or Average 8760.00000 23.21499 37.91844 -0.0686 7.32469
Minimum of Months 672.00000 22.60822 24.03309 -0.5526 5.61579
Maximum of Months 744.00000 23.66709 55.38654 0.27262 11.91714



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.11747 30.22571 0.18802 6.26590
February 672.00000 23.05360 43.35045 0.25351 6.96343
March 744.00000 23.21809 34.80102 0.25653 6.94812
April 720.00000 23.58166 26.13899 0.33788 7.69753
May 744.00000 23.69228 25.28684 -0.4701 9.99266
June 720.00000 23.80367 34.81590 -0.3171 7.42637
July 744.00000 23.78706 51.84679 -0.2170 6.35033
August 744.00000 23.74107 54.75882 -0.2253 6.39359
September 720.00000 23.69683 54.17449 -0.2641 6.84165
October 744.00000 23.41804 35.28085 0.33851 8.11140
November 720.00000 23.17797 35.20931 0.24371 7.01684
December 744.00000 22.95253 23.70585 0.08613 5.68427
           
Annual Sum or Average 8760.00000 23.43843 37.41659 0.01582 7.14132
Minimum of Months 672.00000 22.95253 23.70585 -0.4701 5.68427
Maximum of Months 744.00000 23.80367 54.75882 0.33851 9.99266



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 24.01694 29.25451 1.03475 29.04958
February 672.00000 24.00549 41.37208 1.09658 31.64844
March 744.00000 23.99879 33.55311 1.06890 30.54520
April 720.00000 23.99121 25.65556 1.10447 32.33062
May 744.00000 23.99171 25.07608 0.59602 16.23260
June 720.00000 23.99260 34.56042 0.73300 19.85531
July 744.00000 23.99314 50.94116 0.82436 22.63593
August 744.00000 23.99325 53.57498 0.82925 22.78141
September 720.00000 23.99322 52.84659 0.78976 21.41162
October 744.00000 23.99191 34.23487 1.12708 33.33418
November 720.00000 24.00039 33.96644 1.06892 30.58896
December 744.00000 24.02741 23.27123 0.96389 26.15642
           
Annual Sum or Average 8760.00000 23.99968 36.48321 0.93523 26.34122
Minimum of Months 672.00000 23.99121 23.27123 0.59602 16.23260
Maximum of Months 744.00000 24.02741 53.57498 1.12708 33.33418



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.54780 26.63316 -0.3316 7.46956
February 672.00000 21.17275 41.84800 -0.3365 7.49521
March 744.00000 21.53093 31.85723 -0.3039 7.33818
April 720.00000 22.77136 21.14548 -0.0628 5.41891
May 744.00000 23.25568 19.93947 -0.9257 23.31526
June 720.00000 23.83195 29.07585 -0.6601 14.35455
July 744.00000 23.78211 46.81394 -0.5590 11.80774
August 744.00000 23.65945 49.86388 -0.5838 12.38551
September 720.00000 23.49261 49.61838 -0.6438 13.93887
October 744.00000 22.54868 30.75477 -0.0532 6.18519
November 720.00000 21.70184 31.92795 -0.2585 6.95608
December 744.00000 21.20808 19.50593 -0.4634 9.63466
           
Annual Sum or Average 8760.00000 22.54872 33.18135 -0.4329 10.55380
Minimum of Months 672.00000 21.17275 19.50593 -0.9257 5.41891
Maximum of Months 744.00000 23.83195 49.86388 -0.0532 23.31526



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.81244 29.38545 -0.0474 5.32337
February 672.00000 22.17555 44.00885 -0.1139 5.38438
March 744.00000 22.58941 34.52598 -0.0690 5.46093
April 720.00000 23.74884 24.50338 0.15339 5.72070
May 744.00000 23.93874 23.46875 -0.7252 16.13975
June 720.00000 23.99801 32.41391 -0.6259 13.29419
July 744.00000 23.99543 49.57837 -0.5121 10.67187
August 744.00000 23.98613 52.39495 -0.4979 10.29463
September 720.00000 23.97999 51.85059 -0.5065 10.47216
October 744.00000 23.60636 33.41315 0.18179 6.26419
November 720.00000 22.97824 34.33875 0.02646 5.39193
December 744.00000 22.26686 22.87305 -0.2215 6.35789
           
Annual Sum or Average 8760.00000 23.34555 36.00076 -0.2477 8.41924
Minimum of Months 672.00000 22.17555 22.87305 -0.7252 5.32337
Maximum of Months 744.00000 23.99801 52.39495 0.18179 16.13975



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.95127 27.43609 -0.0062 5.53814
February 672.00000 22.28237 42.01900 -0.0808 5.44614
March 744.00000 22.81228 32.32623 -0.0060 5.72361
April 720.00000 23.85119 22.25882 0.20886 6.14522
May 744.00000 23.96912 21.28528 -0.6538 14.10091
June 720.00000 23.99976 30.41694 -0.5392 11.18893
July 744.00000 23.99945 47.38666 -0.4282 9.02849
August 744.00000 23.99813 50.16860 -0.4151 8.72264
September 720.00000 23.99614 49.60492 -0.4318 9.01567
October 744.00000 23.62601 31.43988 0.20979 6.66064
November 720.00000 23.07612 32.27710 0.05979 5.85338
December 744.00000 22.23741 21.12866 -0.2234 6.77265
           
Annual Sum or Average 8760.00000 23.40550 33.91665 -0.1933 7.86725
Minimum of Months 672.00000 22.23741 21.12866 -0.6538 5.44614
Maximum of Months 744.00000 23.99976 50.16860 0.20979 14.10091



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.55944 25.21848 -0.1187 5.68657
February 672.00000 22.12661 39.64254 -0.1337 5.62715
March 744.00000 22.59002 30.02812 -0.0793 5.77698
April 720.00000 23.79597 19.96921 0.15826 5.77770
May 744.00000 23.99293 19.07193 -0.6897 15.06825
June 720.00000 23.99999 28.63449 -0.5830 12.22069
July 744.00000 23.99985 45.94936 -0.4700 9.81434
August 744.00000 23.99761 48.66595 -0.4610 9.56509
September 720.00000 23.99908 48.05851 -0.4739 9.81307
October 744.00000 23.53256 29.18676 0.15785 6.30800
November 720.00000 22.80175 30.06527 -0.0259 5.74180
December 744.00000 21.99669 18.65366 -0.2945 7.25101
           
Annual Sum or Average 8760.00000 23.28819 31.86799 -0.2523 8.24037
Minimum of Months 672.00000 21.99669 18.65366 -0.6897 5.62715
Maximum of Months 744.00000 23.99999 48.66595 0.15826 15.06825



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.669564E+11 125923.77 31-JAN-16:01 652.21 0.201367E+12 0.00 0.268323E+12 2.69 3.82 27-JAN-19:01 0.00 0.00
February 0.202171E+11 74365.32 18-FEB-16:01 498.77 0.602194E+11 0.00 0.804364E+11 2.30 3.50 22-FEB-16:01 0.00 0.00
March 0.634706E+11 120703.28 16-MAR-15:02 627.39 0.186606E+12 0.00 0.250076E+12 2.55 3.85 05-MAR-19:03 0.00 0.00
April 0.168650E+12 163857.71 14-APR-18:03 718.42 0.506347E+12 0.00 0.674997E+12 3.00 3.84 26-APR-18:03 0.00 0.00
May 0.219507E+12 177055.39 31-MAY-18:03 744.00 0.646282E+12 0.00 0.865789E+12 2.94 3.74 22-MAY-08:62 0.00 0.00
June 0.294511E+12 219466.45 28-JUN-18:06 720.00 0.832812E+12 0.00 0.112732E+13 2.87 3.59 13-JUN-08:61 0.00 0.00
July 0.313251E+12 205244.16 20-JUL-18:03 744.00 0.944965E+12 0.00 0.125822E+13 3.04 4.02 14-JUL-01:00 0.00 0.00
August 0.304193E+12 211530.24 25-AUG-18:03 744.00 0.921148E+12 0.00 0.122534E+13 3.06 4.14 28-AUG-17:00 0.00 0.00
September 0.267705E+12 194294.43 08-SEP-18:03 720.00 0.842070E+12 0.00 0.110978E+13 3.15 4.31 03-SEP-08:62 0.00 0.00
October 0.148991E+12 173301.72 02-OCT-18:03 717.08 0.456689E+12 0.00 0.605680E+12 2.95 3.88 23-OCT-18:01 0.00 0.00
November 0.716623E+11 124628.16 01-NOV-15:02 644.07 0.217265E+12 0.00 0.288927E+12 2.75 4.16 11-NOV-19:03 0.00 0.00
December 0.394144E+11 105059.33 25-DEC-16:02 568.52 0.117280E+12 0.00 0.156695E+12 2.36 3.65 24-DEC-16:01 0.00 0.00
                         
Annual Sum or Average 0.197853E+13     8098.46 0.593305E+13 0.00 0.791158E+13 2.81     0.00 0.00
Minimum of Months 0.202171E+11 74365.32   498.77 0.602194E+11 0.00 0.804364E+11 2.30 3.50   0.00 0.00
Maximum of Months 0.313251E+12 219466.45   744.00 0.944965E+12 0.00 0.125822E+13 3.15 4.31   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.242358E+11 0.00 446.59 125985.40 01-JAN-23:25 0.00 57.58 71.57 0.08 0.00 0.03 0.36 01-JAN-23:25
February 0.247348E+11 0.00 564.54 116799.26 02-FEB-03:40 0.00 57.46 75.94 0.10 0.00 0.03 0.33 02-FEB-03:40
March 0.177589E+11 0.00 407.01 121354.52 30-MAR-06:32 0.00 52.79 66.71 0.06 0.00 0.02 0.34 30-MAR-06:32
April 0.726025E+09 0.00 48.96 91916.92 21-APR-03:56 0.00 48.34 50.38 0.00 0.00 0.00 0.26 21-APR-03:56
May 0.168802E+09 0.00 7.57 43121.14 15-MAY-08:04 0.00 54.42 54.70 0.00 0.00 0.00 0.12 15-MAY-08:04
June 25873005.41 0.00 0.99 12704.33 30-JUN-08:06 0.00 58.90 58.93 0.00 0.00 0.00 0.04 30-JUN-08:06
July 29301677.67 0.00 1.43 24925.24 27-JUL-08:05 0.00 60.15 60.19 0.00 0.00 0.00 0.07 27-JUL-08:05
August 38462967.23 0.00 1.53 29949.04 24-AUG-08:04 0.00 59.96 60.00 0.00 0.00 0.00 0.08 24-AUG-08:04
September 59472129.31 0.00 1.92 29736.66 29-SEP-08:04 0.00 59.13 59.18 0.00 0.00 0.00 0.08 29-SEP-08:04
October 0.532236E+10 0.00 163.28 113264.46 25-OCT-06:30 0.00 56.79 62.21 0.02 0.00 0.01 0.32 25-OCT-06:30
November 0.151051E+11 0.00 382.27 122727.45 18-NOV-06:02 0.00 56.98 69.02 0.05 0.00 0.02 0.35 18-NOV-06:02
December 0.367170E+11 0.00 611.53 155439.89 17-DEC-09:01 0.00 57.57 76.29 0.13 0.00 0.04 0.44 17-DEC-09:01
                           
Annual Sum or Average 0.124922E+12 0.00 2637.63     0.00 56.68 63.71 0.04 0.00 0.01    
Minimum of Months 25873005.41 0.00 0.99 12704.33   0.00 48.34 50.38 0.00 0.00 0.00 0.04  
Maximum of Months 0.367170E+11 0.00 611.53 155439.89   0.00 60.15 76.29 0.13 0.00 0.04 0.44  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.111591E+12 0.00 402.02 0.111136E+12 0.00 0.00 0.00 0.00 182073.33 31-JAN-16:40 182073.33 31-JAN-16:40 0.00 0.00 0.00
February 0.273384E+11 0.00 242.29 0.273197E+11 0.00 0.00 0.00 0.00 112153.73 18-FEB-14:00 112153.73 18-FEB-14:00 0.00 0.00 0.00
March 0.119887E+12 0.00 443.40 0.119887E+12 0.00 0.00 0.00 0.00 199609.91 20-MAR-18:10 199609.91 20-MAR-18:10 0.00 0.00 0.00
April 0.327386E+12 0.00 665.28 0.327386E+12 0.00 0.00 0.00 0.00 268555.58 14-APR-20:10 268555.58 14-APR-20:10 0.00 0.00 0.00
May 0.425765E+12 0.00 735.42 0.425765E+12 0.00 0.00 0.00 0.00 280605.53 31-MAY-18:05 280605.53 31-MAY-18:05 0.00 0.00 0.00
June 0.544608E+12 0.00 720.00 0.543691E+12 0.00 0.00 0.00 0.00 350196.78 17-JUN-17:17 332997.86 28-JUN-18:17 0.00 0.00 0.00
July 0.633802E+12 0.00 744.00 0.555481E+12 0.00 0.00 0.00 0.00 421126.12 13-JUL-21:00 331148.69 21-JUL-20:10 0.00 0.00 0.00
August 0.616988E+12 0.00 744.00 0.546295E+12 0.00 0.00 0.00 0.00 452169.98 18-AUG-22:00 320731.92 15-AUG-19:20 0.00 0.00 0.00
September 0.565901E+12 0.00 720.00 0.489402E+12 0.00 0.00 0.00 0.00 482812.48 10-SEP-19:20 315081.08 08-SEP-20:10 0.00 0.00 0.00
October 0.290091E+12 0.00 613.68 0.281960E+12 0.00 0.00 0.00 0.00 347052.84 02-OCT-20:00 283415.26 03-OCT-20:10 0.00 0.00 0.00
November 0.128100E+12 0.00 433.91 0.113732E+12 0.00 0.00 0.00 0.00 207086.46 01-NOV-18:04 207086.46 01-NOV-18:04 0.00 0.00 0.00
December 0.605304E+11 0.00 316.92 0.605304E+11 0.00 0.00 0.00 0.00 162336.27 25-DEC-13:00 162336.27 25-DEC-13:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.385199E+13 0.00 6780.92 0.360258E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.273384E+11 0.00 242.29 0.273197E+11 0.00 0.00 0.00 0.00 112153.73   112153.73   0.00 0.00 0.00
Maximum of Months 0.633802E+12 0.00 744.00 0.555481E+12 0.00 0.00 0.00 0.00 482812.48   332997.86   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.198588E+11 0.00 362.42 0.197255E+11 0.00 0.00 0.00 0.00 28113.38 31-JAN-16:01 28113.38 31-JAN-16:01 0.00 0.00 0.00
February 0.520638E+10 0.00 212.17 0.520638E+10 0.00 0.00 0.00 0.00 23245.80 18-FEB-14:00 23245.80 18-FEB-14:00 0.00 0.00 0.00
March 0.212817E+11 0.00 408.00 0.212817E+11 0.00 0.00 0.00 0.00 28620.15 16-MAR-15:02 28620.15 16-MAR-15:02 0.00 0.00 0.00
April 0.506605E+11 0.00 662.50 0.506605E+11 0.00 0.00 0.00 0.00 32711.12 14-APR-15:00 32711.12 14-APR-15:00 0.00 0.00 0.00
May 0.642412E+11 0.00 735.50 0.642412E+11 0.00 0.00 0.00 0.00 33351.04 31-MAY-17:40 33351.04 31-MAY-17:40 0.00 0.00 0.00
June 0.748094E+11 0.00 720.00 0.747128E+11 0.00 0.00 0.00 0.00 41459.59 17-JUN-16:00 36620.64 28-JUN-17:20 0.00 0.00 0.00
July 0.886398E+11 0.00 744.00 0.766701E+11 0.00 0.00 0.00 0.00 50861.44 13-JUL-18:02 36037.45 19-JUL-14:00 0.00 0.00 0.00
August 0.877525E+11 0.00 744.00 0.756168E+11 0.00 0.00 0.00 0.00 53667.54 05-AUG-08:00 36153.45 25-AUG-15:02 0.00 0.00 0.00
September 0.820432E+11 0.00 720.00 0.691968E+11 0.00 0.00 0.00 0.00 57485.13 04-SEP-08:61 34872.36 08-SEP-15:00 0.00 0.00 0.00
October 0.443045E+11 0.00 603.18 0.428084E+11 0.00 0.00 0.00 0.00 45579.85 03-OCT-05:00 34109.33 01-OCT-13:00 0.00 0.00 0.00
November 0.227731E+11 0.00 407.33 0.196436E+11 0.00 0.00 0.00 0.00 43952.06 12-NOV-14:30 28787.30 01-NOV-15:00 0.00 0.00 0.00
December 0.111635E+11 0.00 250.39 0.111635E+11 0.00 0.00 0.00 0.00 26310.78 25-DEC-16:00 26310.78 25-DEC-16:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.572735E+12 0.00 6569.49 0.530927E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.520638E+10 0.00 212.17 0.520638E+10 0.00 0.00 0.00 0.00 23245.80   23245.80   0.00 0.00 0.00
Maximum of Months 0.886398E+11 0.00 744.00 0.766701E+11 0.00 0.00 0.00 0.00 57485.13   36620.64   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.318585E+10 0.00 439.11 0.305643E+10 0.00 0.00 0.00 0.00 16162.35 14-JAN-16:02 16162.35 14-JAN-16:02 0.00 0.00 0.00
February 0.997826E+09 0.00 203.62 0.835567E+09 0.00 0.00 0.00 0.00 15395.95 22-FEB-16:01 15395.95 22-FEB-16:01 0.00 0.00 0.00
March 0.245727E+10 0.00 384.17 0.215335E+10 0.00 0.00 0.00 0.00 16192.18 18-MAR-15:02 16192.18 18-MAR-15:02 0.00 0.00 0.00
April 0.845913E+10 0.00 663.89 0.832734E+10 0.00 0.00 0.00 0.00 16191.97 25-APR-18:01 16191.97 25-APR-18:01 0.00 0.00 0.00
May 0.101774E+11 0.00 701.03 0.101331E+11 0.00 0.00 0.00 0.00 16181.57 10-MAY-18:01 16181.57 10-MAY-18:01 0.00 0.00 0.00
June 0.134518E+11 0.00 696.14 0.128553E+11 0.00 0.00 0.00 0.00 16196.63 01-JUN-18:02 16196.63 01-JUN-18:02 0.00 0.00 0.00
July 0.132264E+11 0.00 715.00 0.973688E+10 0.00 0.00 0.00 0.00 17469.17 15-JUL-08:61 16185.87 03-JUL-18:02 0.00 0.00 0.00
August 0.129985E+11 0.00 711.65 0.931959E+10 0.00 0.00 0.00 0.00 17650.86 05-AUG-08:61 16197.08 27-AUG-15:02 0.00 0.00 0.00
September 0.112370E+11 0.00 682.54 0.768271E+10 0.00 0.00 0.00 0.00 18370.54 04-SEP-08:61 16196.29 27-SEP-18:01 0.00 0.00 0.00
October 0.685331E+10 0.00 604.42 0.574901E+10 0.00 0.00 0.00 0.00 16769.37 03-OCT-08:62 16189.99 20-OCT-15:02 0.00 0.00 0.00
November 0.329720E+10 0.00 458.99 0.272583E+10 0.00 0.00 0.00 0.00 16417.51 13-NOV-16:01 16172.89 20-NOV-16:01 0.00 0.00 0.00
December 0.148865E+10 0.00 267.88 0.148737E+10 0.00 0.00 0.00 0.00 16058.86 25-DEC-16:02 16058.86 25-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.878304E+11 0.00 6528.44 0.740625E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.997826E+09 0.00 203.62 0.835567E+09 0.00 0.00 0.00 0.00 15395.95   15395.95   0.00 0.00 0.00
Maximum of Months 0.134518E+11 0.00 715.00 0.128553E+11 0.00 0.00 0.00 0.00 18370.54   16197.08   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.121057E+10 0.00 232.59 0.117117E+10 0.00 0.00 0.00 0.00 16047.37 14-JAN-16:02 16047.37 14-JAN-16:02 0.00 0.00 0.00
February 0.352383E+09 0.00 92.24 0.311162E+09 0.00 0.00 0.00 0.00 15286.06 22-FEB-16:01 15286.06 22-FEB-16:01 0.00 0.00 0.00
March 0.164078E+10 0.00 300.19 0.145187E+10 0.00 0.00 0.00 0.00 16076.28 18-MAR-15:02 16076.28 18-MAR-15:02 0.00 0.00 0.00
April 0.739021E+10 0.00 641.25 0.726509E+10 0.00 0.00 0.00 0.00 16077.28 25-APR-18:01 16077.28 25-APR-18:01 0.00 0.00 0.00
May 0.989788E+10 0.00 699.40 0.985382E+10 0.00 0.00 0.00 0.00 16066.97 18-MAY-08:61 16066.97 18-MAY-08:61 0.00 0.00 0.00
June 0.136168E+11 0.00 697.75 0.130270E+11 0.00 0.00 0.00 0.00 16082.16 25-JUN-08:61 16082.16 25-JUN-08:61 0.00 0.00 0.00
July 0.131743E+11 0.00 715.99 0.971880E+10 0.00 0.00 0.00 0.00 17168.74 15-JUL-08:61 16071.16 03-JUL-18:02 0.00 0.00 0.00
August 0.123447E+11 0.00 709.18 0.870720E+10 0.00 0.00 0.00 0.00 17735.72 28-AUG-18:02 16082.06 27-AUG-15:02 0.00 0.00 0.00
September 0.100701E+11 0.00 674.97 0.660706E+10 0.00 0.00 0.00 0.00 18043.92 04-SEP-08:61 16081.49 27-SEP-18:01 0.00 0.00 0.00
October 0.496514E+10 0.00 522.54 0.396807E+10 0.00 0.00 0.00 0.00 16631.64 03-OCT-08:62 16074.12 20-OCT-15:02 0.00 0.00 0.00
November 0.153138E+10 0.00 303.70 0.115898E+10 0.00 0.00 0.00 0.00 16476.42 13-NOV-16:01 16057.95 20-NOV-16:01 0.00 0.00 0.00
December 0.386656E+09 0.00 90.07 0.386643E+09 0.00 0.00 0.00 0.00 15945.23 25-DEC-16:02 15945.23 25-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.765810E+11 0.00 5679.86 0.636268E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.352383E+09 0.00 90.07 0.311162E+09 0.00 0.00 0.00 0.00 15286.06   15286.06   0.00 0.00 0.00
Maximum of Months 0.136168E+11 0.00 715.99 0.130270E+11 0.00 0.00 0.00 0.00 18043.92   16082.16   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.330584E+11 0.00 471.88 0.327276E+11 0.00 0.00 0.00 0.00 45145.39 14-JAN-13:50 45145.39 14-JAN-13:50 0.00 0.00 0.00
February 0.834135E+10 0.00 193.49 0.795809E+10 0.00 0.00 0.00 0.00 35316.13 01-FEB-15:30 35316.13 01-FEB-15:30 0.00 0.00 0.00
March 0.808011E+10 0.00 234.84 0.777595E+10 0.00 0.00 0.00 0.00 30489.27 18-MAR-13:50 30453.73 18-MAR-14:30 0.00 0.00 0.00
April 0.290360E+11 0.00 557.21 0.290317E+11 0.00 0.00 0.00 0.00 32671.32 14-APR-13:40 32671.32 14-APR-13:40 0.00 0.00 0.00
May 0.290738E+11 0.00 617.08 0.290738E+11 0.00 0.00 0.00 0.00 25700.43 09-MAY-17:12 25700.43 09-MAY-17:12 0.00 0.00 0.00
June 0.436688E+11 0.00 711.58 0.417766E+11 0.00 0.00 0.00 0.00 34698.02 17-JUN-18:00 33176.85 28-JUN-19:10 0.00 0.00 0.00
July 0.464737E+11 0.00 731.33 0.291904E+11 0.00 0.00 0.00 0.00 33471.84 21-JUL-20:20 28731.16 07-JUL-17:13 0.00 0.00 0.00
August 0.496870E+11 0.00 725.56 0.318723E+11 0.00 0.00 0.00 0.00 42003.96 28-AUG-12:40 39197.27 27-AUG-14:00 0.00 0.00 0.00
September 0.496719E+11 0.00 698.08 0.341505E+11 0.00 0.00 0.00 0.00 45063.74 28-SEP-13:40 45063.74 28-SEP-13:40 0.00 0.00 0.00
October 0.389375E+11 0.00 582.69 0.339561E+11 0.00 0.00 0.00 0.00 46300.43 18-OCT-13:50 46300.43 18-OCT-13:50 0.00 0.00 0.00
November 0.264395E+11 0.00 420.06 0.246681E+11 0.00 0.00 0.00 0.00 47994.99 20-NOV-14:30 47994.99 20-NOV-14:30 0.00 0.00 0.00
December 0.225500E+11 0.00 382.40 0.225317E+11 0.00 0.00 0.00 0.00 44726.61 25-DEC-13:40 44726.61 25-DEC-13:40 0.00 0.00 0.00
                               
Annual Sum or Average 0.385018E+12 0.00 6326.22 0.324713E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.808011E+10 0.00 193.49 0.777595E+10 0.00 0.00 0.00 0.00 25700.43   25700.43   0.00 0.00 0.00
Maximum of Months 0.496870E+11 0.00 731.33 0.417766E+11 0.00 0.00 0.00 0.00 47994.99   47994.99   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.569310E+10 0.00 282.58 0.518570E+10 0.00 0.00 0.00 0.00 87479.22 27-JAN-16:01 87479.22 27-JAN-16:01 0.00 0.00 0.00
February 0.398629E+10 0.00 240.95 0.202577E+10 0.00 0.00 0.00 0.00 79923.10 18-FEB-09:02 73396.67 20-FEB-09:02 0.00 0.00 0.00
March 0.117544E+11 0.00 377.26 0.986548E+10 0.00 0.00 0.00 0.00 93212.72 15-MAR-18:01 93212.72 15-MAR-18:01 0.00 0.00 0.00
April 0.367336E+11 0.00 517.49 0.360688E+11 0.00 0.00 0.00 0.00 96908.64 25-APR-18:01 96908.64 25-APR-18:01 0.00 0.00 0.00
May 0.525062E+11 0.00 575.77 0.522484E+11 0.00 0.00 0.00 0.00 96843.06 10-MAY-18:01 96843.06 10-MAY-18:01 0.00 0.00 0.00
June 0.744244E+11 0.00 640.33 0.712008E+11 0.00 0.00 0.00 0.00 96947.28 03-JUN-08:61 96947.28 03-JUN-08:61 0.00 0.00 0.00
July 0.787533E+11 0.00 649.37 0.598968E+11 0.00 0.00 0.00 0.00 97419.23 09-JUL-08:61 96867.89 03-JUL-18:02 0.00 0.00 0.00
August 0.715695E+11 0.00 626.73 0.514060E+11 0.00 0.00 0.00 0.00 112511.59 28-AUG-18:02 96944.18 27-AUG-15:02 0.00 0.00 0.00
September 0.607458E+11 0.00 574.82 0.411093E+11 0.00 0.00 0.00 0.00 105034.57 04-SEP-08:61 96941.86 30-SEP-15:02 0.00 0.00 0.00
October 0.285439E+11 0.00 493.71 0.230561E+11 0.00 0.00 0.00 0.00 96941.78 05-OCT-18:01 96941.78 05-OCT-18:01 0.00 0.00 0.00
November 0.893234E+10 0.00 334.45 0.574244E+10 0.00 0.00 0.00 0.00 88218.44 20-NOV-16:01 88218.44 20-NOV-16:01 0.00 0.00 0.00
December 0.212456E+10 0.00 142.28 0.210124E+10 0.00 0.00 0.00 0.00 78586.50 23-DEC-09:02 78586.50 23-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.435767E+12 0.00 5455.74 0.359907E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.212456E+10 0.00 142.28 0.202577E+10 0.00 0.00 0.00 0.00 78586.50   73396.67   0.00 0.00 0.00
Maximum of Months 0.787533E+11 0.00 649.37 0.712008E+11 0.00 0.00 0.00 0.00 112511.59   96947.28   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.300043E+10 0.00 447.79 0.287421E+10 0.00 0.00 0.00 0.00 14127.94 14-JAN-16:02 14127.94 14-JAN-16:02 0.00 0.00 0.00
February 0.119198E+10 0.00 241.92 0.944717E+09 0.00 0.00 0.00 0.00 13457.26 22-FEB-16:01 13457.26 22-FEB-16:01 0.00 0.00 0.00
March 0.256296E+10 0.00 424.60 0.222209E+10 0.00 0.00 0.00 0.00 14154.34 18-MAR-15:02 14154.34 18-MAR-15:02 0.00 0.00 0.00
April 0.856871E+10 0.00 693.39 0.844488E+10 0.00 0.00 0.00 0.00 14154.55 25-APR-18:01 14154.55 25-APR-18:01 0.00 0.00 0.00
May 0.105066E+11 0.00 728.03 0.104674E+11 0.00 0.00 0.00 0.00 14144.93 18-MAY-08:61 14144.93 18-MAY-08:61 0.00 0.00 0.00
June 0.137799E+11 0.00 711.26 0.133100E+11 0.00 0.00 0.00 0.00 14158.39 01-JUN-18:02 14158.39 01-JUN-18:02 0.00 0.00 0.00
July 0.141206E+11 0.00 731.49 0.108024E+11 0.00 0.00 0.00 0.00 14559.61 09-JUL-08:61 14149.33 03-JUL-18:02 0.00 0.00 0.00
August 0.137421E+11 0.00 727.71 0.102492E+11 0.00 0.00 0.00 0.00 15244.45 04-AUG-08:62 14158.23 27-AUG-15:02 0.00 0.00 0.00
September 0.116497E+11 0.00 698.20 0.823825E+10 0.00 0.00 0.00 0.00 15338.04 03-SEP-15:02 14157.43 27-SEP-18:01 0.00 0.00 0.00
October 0.712733E+10 0.00 636.29 0.606386E+10 0.00 0.00 0.00 0.00 14158.70 05-OCT-18:01 14158.70 05-OCT-18:01 0.00 0.00 0.00
November 0.301200E+10 0.00 455.22 0.253165E+10 0.00 0.00 0.00 0.00 14137.30 20-NOV-16:01 14137.30 20-NOV-16:01 0.00 0.00 0.00
December 0.150789E+10 0.00 274.17 0.150014E+10 0.00 0.00 0.00 0.00 14037.71 25-DEC-16:02 14037.71 25-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.907702E+11 0.00 6770.07 0.776487E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.119198E+10 0.00 241.92 0.944717E+09 0.00 0.00 0.00 0.00 13457.26   13457.26   0.00 0.00 0.00
Maximum of Months 0.141206E+11 0.00 731.49 0.133100E+11 0.00 0.00 0.00 0.00 15338.04   14158.70   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.980001E+09 0.00 232.43 0.912336E+09 0.00 0.00 0.00 0.00 14024.96 31-JAN-16:01 14024.96 31-JAN-16:01 0.00 0.00 0.00
February 0.416123E+09 0.00 123.27 0.271522E+09 0.00 0.00 0.00 0.00 12502.41 22-FEB-16:01 12502.41 22-FEB-16:01 0.00 0.00 0.00
March 0.167905E+10 0.00 339.60 0.142803E+10 0.00 0.00 0.00 0.00 14055.31 18-MAR-15:02 14055.31 18-MAR-15:02 0.00 0.00 0.00
April 0.745111E+10 0.00 685.29 0.732987E+10 0.00 0.00 0.00 0.00 14056.83 25-APR-18:01 14056.83 25-APR-18:01 0.00 0.00 0.00
May 0.102191E+11 0.00 728.00 0.101800E+11 0.00 0.00 0.00 0.00 14047.43 18-MAY-08:61 14047.43 18-MAY-08:61 0.00 0.00 0.00
June 0.139427E+11 0.00 711.47 0.134842E+11 0.00 0.00 0.00 0.00 14061.39 20-JUN-18:02 14061.39 20-JUN-18:02 0.00 0.00 0.00
July 0.140619E+11 0.00 731.61 0.107524E+11 0.00 0.00 0.00 0.00 14407.84 09-JUL-08:61 14052.39 03-JUL-18:02 0.00 0.00 0.00
August 0.130875E+11 0.00 727.01 0.955559E+10 0.00 0.00 0.00 0.00 15424.95 28-AUG-18:02 14060.64 27-AUG-15:02 0.00 0.00 0.00
September 0.104763E+11 0.00 695.19 0.707363E+10 0.00 0.00 0.00 0.00 15382.60 03-SEP-15:02 14059.84 27-SEP-18:01 0.00 0.00 0.00
October 0.513203E+10 0.00 555.05 0.413438E+10 0.00 0.00 0.00 0.00 14061.32 05-OCT-18:01 14061.32 05-OCT-18:01 0.00 0.00 0.00
November 0.126828E+10 0.00 285.22 0.963572E+09 0.00 0.00 0.00 0.00 14039.10 20-NOV-16:01 14039.10 20-NOV-16:01 0.00 0.00 0.00
December 0.326451E+09 0.00 103.70 0.324345E+09 0.00 0.00 0.00 0.00 13392.13 25-DEC-16:02 13392.13 25-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.790405E+11 0.00 5917.84 0.664100E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.326451E+09 0.00 103.70 0.271522E+09 0.00 0.00 0.00 0.00 12502.41   12502.41   0.00 0.00 0.00
Maximum of Months 0.140619E+11 0.00 731.61 0.134842E+11 0.00 0.00 0.00 0.00 15424.95   14061.39   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.668588E+09 0.00 341.58 0.651825E+09 0.00 0.00 0.00 0.00 4291.11 14-JAN-16:02 4291.11 14-JAN-16:02 0.00 0.00 0.00
February 0.197808E+09 0.00 138.13 0.174850E+09 0.00 0.00 0.00 0.00 4087.64 22-FEB-16:01 4087.64 22-FEB-16:01 0.00 0.00 0.00
March 0.532917E+09 0.00 304.92 0.474895E+09 0.00 0.00 0.00 0.00 4299.10 18-MAR-15:02 4299.10 18-MAR-15:02 0.00 0.00 0.00
April 0.206197E+10 0.00 645.39 0.202866E+10 0.00 0.00 0.00 0.00 4298.94 25-APR-18:01 4298.94 25-APR-18:01 0.00 0.00 0.00
May 0.254770E+10 0.00 696.85 0.253538E+10 0.00 0.00 0.00 0.00 4296.15 10-MAY-18:01 4296.15 10-MAY-18:01 0.00 0.00 0.00
June 0.353714E+10 0.00 696.31 0.337068E+10 0.00 0.00 0.00 0.00 4300.31 23-JUN-08:61 4300.31 23-JUN-08:61 0.00 0.00 0.00
July 0.345025E+10 0.00 715.48 0.252889E+10 0.00 0.00 0.00 0.00 4763.26 15-JUL-08:61 4297.26 03-JUL-18:02 0.00 0.00 0.00
August 0.336392E+10 0.00 710.61 0.240055E+10 0.00 0.00 0.00 0.00 4821.78 05-AUG-08:61 4300.33 27-AUG-15:02 0.00 0.00 0.00
September 0.282153E+10 0.00 679.12 0.189386E+10 0.00 0.00 0.00 0.00 5061.59 04-SEP-08:61 4300.13 27-SEP-18:01 0.00 0.00 0.00
October 0.157760E+10 0.00 548.50 0.130245E+10 0.00 0.00 0.00 0.00 4608.30 03-OCT-08:62 4298.16 20-OCT-15:02 0.00 0.00 0.00
November 0.672990E+09 0.00 358.98 0.566229E+09 0.00 0.00 0.00 0.00 4399.61 13-NOV-16:01 4293.88 20-NOV-16:01 0.00 0.00 0.00
December 0.301949E+09 0.00 191.76 0.301949E+09 0.00 0.00 0.00 0.00 4263.62 25-DEC-16:02 4263.62 25-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.217344E+11 0.00 6027.62 0.182302E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.197808E+09 0.00 138.13 0.174850E+09 0.00 0.00 0.00 0.00 4087.64   4087.64   0.00 0.00 0.00
Maximum of Months 0.353714E+10 0.00 715.48 0.337068E+10 0.00 0.00 0.00 0.00 5061.59   4300.33   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.224364E+09 0.00 150.17 0.222246E+09 0.00 0.00 0.00 0.00 4257.25 14-JAN-16:02 4257.25 14-JAN-16:02 0.00 0.00 0.00
February 65767917.60 0.00 48.63 60179316.31 0.00 0.00 0.00 0.00 4055.27 22-FEB-16:01 4055.27 22-FEB-16:01 0.00 0.00 0.00
March 0.342457E+09 0.00 220.95 0.307900E+09 0.00 0.00 0.00 0.00 4265.22 18-MAR-15:02 4265.22 18-MAR-15:02 0.00 0.00 0.00
April 0.178731E+10 0.00 621.50 0.175653E+10 0.00 0.00 0.00 0.00 4265.25 25-APR-18:01 4265.25 25-APR-18:01 0.00 0.00 0.00
May 0.247560E+10 0.00 696.03 0.246332E+10 0.00 0.00 0.00 0.00 4262.50 08-MAY-08:61 4262.50 08-MAY-08:61 0.00 0.00 0.00
June 0.357859E+10 0.00 698.34 0.341114E+10 0.00 0.00 0.00 0.00 4266.67 23-JUN-08:61 4266.67 23-JUN-08:61 0.00 0.00 0.00
July 0.343686E+10 0.00 716.10 0.252138E+10 0.00 0.00 0.00 0.00 4679.31 15-JUL-08:61 4263.57 03-JUL-18:02 0.00 0.00 0.00
August 0.319431E+10 0.00 708.60 0.223722E+10 0.00 0.00 0.00 0.00 4810.03 28-AUG-18:02 4266.55 27-AUG-15:02 0.00 0.00 0.00
September 0.251876E+10 0.00 672.69 0.161683E+10 0.00 0.00 0.00 0.00 4959.40 04-SEP-08:61 4266.42 27-SEP-18:01 0.00 0.00 0.00
October 0.111220E+10 0.00 461.44 0.864799E+09 0.00 0.00 0.00 0.00 4539.69 03-OCT-08:62 4264.46 20-OCT-15:02 0.00 0.00 0.00
November 0.275237E+09 0.00 193.65 0.216389E+09 0.00 0.00 0.00 0.00 4321.42 13-NOV-16:01 4260.15 20-NOV-16:01 0.00 0.00 0.00
December 71618469.97 0.00 51.48 71586019.37 0.00 0.00 0.00 0.00 4230.17 25-DEC-16:02 4230.17 25-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.190831E+11 0.00 5239.57 0.157495E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 65767917.60 0.00 48.63 60179316.31 0.00 0.00 0.00 0.00 4055.27   4055.27   0.00 0.00 0.00
Maximum of Months 0.357859E+10 0.00 716.10 0.341114E+10 0.00 0.00 0.00 0.00 4959.40   4266.67   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.921552E+10 0.00 584.43 0.890466E+10 0.00 0.00 0.00 0.00 18831.10 14-JAN-16:02 18831.10 14-JAN-16:02 0.00 0.00 0.00
February 0.354369E+10 0.00 358.02 0.294074E+10 0.00 0.00 0.00 0.00 17934.76 22-FEB-16:01 17934.76 22-FEB-16:01 0.00 0.00 0.00
March 0.438053E+10 0.00 457.67 0.383740E+10 0.00 0.00 0.00 0.00 18863.86 18-MAR-15:02 18863.86 18-MAR-15:02 0.00 0.00 0.00
April 0.101656E+11 0.00 657.34 0.998560E+10 0.00 0.00 0.00 0.00 18864.30 25-APR-18:01 18864.30 25-APR-18:01 0.00 0.00 0.00
May 0.108225E+11 0.00 689.58 0.107603E+11 0.00 0.00 0.00 0.00 18851.84 10-MAY-18:01 18851.84 10-MAY-18:01 0.00 0.00 0.00
June 0.146313E+11 0.00 685.06 0.137855E+11 0.00 0.00 0.00 0.00 18866.69 19-JUN-15:02 18866.69 19-JUN-15:02 0.00 0.00 0.00
July 0.160928E+11 0.00 706.93 0.118393E+11 0.00 0.00 0.00 0.00 20104.31 15-JUL-08:61 18856.58 03-JUL-18:02 0.00 0.00 0.00
August 0.166863E+11 0.00 705.51 0.121795E+11 0.00 0.00 0.00 0.00 21028.35 05-AUG-08:61 18862.52 23-AUG-15:02 0.00 0.00 0.00
September 0.159186E+11 0.00 680.51 0.114454E+11 0.00 0.00 0.00 0.00 21845.36 04-SEP-08:61 18864.33 18-SEP-18:01 0.00 0.00 0.00
October 0.117827E+11 0.00 649.45 0.103328E+11 0.00 0.00 0.00 0.00 19575.81 03-OCT-08:62 18859.82 20-OCT-15:02 0.00 0.00 0.00
November 0.807520E+10 0.00 547.84 0.720237E+10 0.00 0.00 0.00 0.00 18974.70 13-NOV-16:01 18841.72 20-NOV-16:01 0.00 0.00 0.00
December 0.660210E+10 0.00 465.82 0.658636E+10 0.00 0.00 0.00 0.00 18708.77 25-DEC-16:02 18708.77 25-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.127917E+12 0.00 7188.16 0.109800E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.354369E+10 0.00 358.02 0.294074E+10 0.00 0.00 0.00 0.00 17934.76   17934.76   0.00 0.00 0.00
Maximum of Months 0.166863E+11 0.00 706.93 0.137855E+11 0.00 0.00 0.00 0.00 21845.36   18866.69   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 835.71 667.64 168.07 1276.01 426.31 0.00 0.00 0.00
February 521.47 349.59 171.87 718.49 395.83 0.00 0.00 0.00
March 431.69 218.75 212.94 643.10 364.13 0.00 0.00 0.00
April 378.88 156.07 222.81 719.38 210.12 0.00 0.00 0.00
May 253.16 44.04 209.12 533.08 143.32 0.00 0.00 0.00
June 214.28 16.35 197.94 609.65 53.83 0.00 0.00 0.00
July 217.14 20.65 196.50 600.49 36.59 0.00 0.00 0.00
August 268.51 75.62 192.88 690.12 49.17 0.00 0.00 0.00
September 381.40 161.20 220.20 821.64 74.33 0.00 0.00 0.00
October 612.22 423.82 188.40 1034.49 257.77 0.00 0.00 0.00
November 719.63 552.71 166.92 1086.76 382.77 0.00 0.00 0.00
December 778.28 616.61 161.67 1138.32 499.39 0.00 0.00 0.00
                 
Annual Sum or Average 467.74 275.23 192.51 823.63 240.53 0.00 0.00 0.00
Minimum of Months 214.28 16.35 161.67 533.08 36.59 0.00 0.00 0.00
Maximum of Months 835.71 667.64 222.81 1276.01 499.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2353.32 1880.03 473.29 3585.48 1203.61 0.00 0.00 0.00
February 1468.41 984.43 483.99 2025.34 1139.06 0.00 0.00 0.00
March 1215.60 615.98 599.62 1832.76 1026.40 0.00 0.00 0.00
April 1066.89 439.48 627.41 2061.23 568.43 0.00 0.00 0.00
May 712.87 124.01 588.87 1562.17 379.49 0.00 0.00 0.00
June 603.41 46.04 557.38 1770.51 140.92 0.00 0.00 0.00
July 611.46 58.14 553.32 1742.21 95.42 0.00 0.00 0.00
August 756.09 212.94 543.15 1979.59 129.26 0.00 0.00 0.00
September 1074.00 453.93 620.07 2339.01 200.25 0.00 0.00 0.00
October 1723.96 1193.45 530.51 2921.62 717.07 0.00 0.00 0.00
November 2026.44 1556.40 470.05 3059.54 1074.73 0.00 0.00 0.00
December 2191.58 1736.32 455.26 3195.22 1426.96 0.00 0.00 0.00
                 
Annual Sum or Average 1317.12 775.03 542.09 2342.49 673.28 0.00 0.00 0.00
Minimum of Months 603.41 46.04 455.26 1562.17 95.42 0.00 0.00 0.00
Maximum of Months 2353.32 1880.03 627.41 3585.48 1426.96 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3057.09 2442.27 614.83 4751.38 1620.60 0.00 0.00 0.00
February 1907.55 1278.83 628.73 2671.17 1588.07 0.00 0.00 0.00
March 1579.13 800.19 778.94 2402.49 1433.41 0.00 0.00 0.00
April 1385.95 570.91 815.04 2724.71 776.76 0.00 0.00 0.00
May 926.06 161.09 764.97 2043.78 522.50 0.00 0.00 0.00
June 783.87 59.80 724.06 2338.83 187.51 0.00 0.00 0.00
July 794.32 75.52 718.79 2299.19 127.86 0.00 0.00 0.00
August 982.21 276.63 705.58 2625.78 171.08 0.00 0.00 0.00
September 1395.19 589.68 805.51 3102.36 261.25 0.00 0.00 0.00
October 2239.52 1550.35 689.17 3869.43 967.52 0.00 0.00 0.00
November 2632.46 2021.85 610.62 4046.92 1463.18 0.00 0.00 0.00
December 2846.99 2255.58 591.41 4229.41 1937.91 0.00 0.00 0.00
                 
Annual Sum or Average 1711.02 1006.81 704.21 3096.01 918.72 0.00 0.00 0.00
Minimum of Months 783.87 59.80 591.41 2043.78 127.86 0.00 0.00 0.00
Maximum of Months 3057.09 2442.27 815.04 4751.38 1937.91 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 165.24 132.00 33.23 259.33 75.11 0.00 0.00 0.00
February 103.10 69.12 33.98 146.32 72.80 0.00 0.00 0.00
March 85.35 43.25 42.10 131.80 66.02 0.00 0.00 0.00
April 74.91 30.86 44.05 151.50 30.93 0.00 0.00 0.00
May 50.05 8.71 41.35 118.34 18.52 0.00 0.00 0.00
June 42.37 3.23 39.14 140.89 4.82 0.00 0.00 0.00
July 42.93 4.08 38.85 140.60 3.01 0.00 0.00 0.00
August 53.09 14.95 38.14 155.54 3.40 0.00 0.00 0.00
September 75.41 31.87 43.54 178.55 5.92 0.00 0.00 0.00
October 121.05 83.80 37.25 213.62 40.43 0.00 0.00 0.00
November 142.28 109.28 33.00 221.08 66.47 0.00 0.00 0.00
December 153.88 121.91 31.97 231.90 92.51 0.00 0.00 0.00
                 
Annual Sum or Average 92.48 54.42 38.06 174.37 39.87 0.00 0.00 0.00
Minimum of Months 42.37 3.23 31.97 118.34 3.01 0.00 0.00 0.00
Maximum of Months 165.24 132.00 44.05 259.33 92.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 127.00 79.12 47.88 186.40 154.76 0.00 0.00 0.00
February 102.87 49.92 52.94 122.78 147.19 0.00 0.00 0.00
March 136.12 65.10 71.02 192.91 125.93 0.00 0.00 0.00
April 208.46 118.98 89.48 374.47 57.45 0.00 0.00 0.00
May 209.22 117.24 91.97 408.23 34.26 0.00 0.00 0.00
June 221.79 130.41 91.37 504.17 8.71 0.00 0.00 0.00
July 161.33 75.18 86.15 396.71 5.50 0.00 0.00 0.00
August 154.44 77.66 76.78 370.71 6.23 0.00 0.00 0.00
September 134.39 56.51 77.89 306.11 11.15 0.00 0.00 0.00
October 138.07 79.18 58.89 239.24 80.83 0.00 0.00 0.00
November 126.39 76.26 50.13 183.24 136.19 0.00 0.00 0.00
December 101.41 57.49 43.91 132.74 191.99 0.00 0.00 0.00
                 
Annual Sum or Average 151.96 82.04 69.93 285.51 79.76 0.00 0.00 0.00
Minimum of Months 101.41 49.92 43.91 122.78 5.50 0.00 0.00 0.00
Maximum of Months 221.79 130.41 91.97 504.17 191.99 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.04 0.00 20.04 19.36 80.48 0.00 0.00 0.00
February 22.83 0.00 22.83 13.68 78.01 0.00 0.00 0.00
March 30.35 0.00 30.35 33.58 67.93 0.00 0.00 0.00
April 37.17 0.55 36.63 71.66 29.36 0.00 0.00 0.00
May 43.60 3.70 39.90 99.76 16.45 0.00 0.00 0.00
June 50.36 9.20 41.15 154.97 4.23 0.00 0.00 0.00
July 43.08 4.63 38.45 138.91 2.70 0.00 0.00 0.00
August 34.66 0.85 33.81 114.33 3.17 0.00 0.00 0.00
September 32.69 0.02 32.67 95.32 5.80 0.00 0.00 0.00
October 25.27 0.00 25.27 45.84 42.55 0.00 0.00 0.00
November 21.06 0.00 21.06 19.87 71.42 0.00 0.00 0.00
December 18.72 0.00 18.72 12.25 100.34 0.00 0.00 0.00
                 
Annual Sum or Average 31.68 1.58 30.10 68.56 41.73 0.00 0.00 0.00
Minimum of Months 18.72 0.00 18.72 12.25 2.70 0.00 0.00 0.00
Maximum of Months 50.36 9.20 41.15 154.97 100.34 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 127.00 79.12 47.88 194.39 149.24 0.00 0.00 0.00
February 102.87 49.92 52.94 128.20 142.94 0.00 0.00 0.00
March 136.12 65.10 71.02 197.47 123.75 0.00 0.00 0.00
April 208.46 118.98 89.48 376.99 56.61 0.00 0.00 0.00
May 209.22 117.24 91.97 408.82 34.10 0.00 0.00 0.00
June 221.79 130.41 91.37 503.81 8.72 0.00 0.00 0.00
July 161.33 75.18 86.15 396.84 5.50 0.00 0.00 0.00
August 154.44 77.66 76.78 372.08 6.11 0.00 0.00 0.00
September 134.39 56.51 77.89 308.67 10.78 0.00 0.00 0.00
October 138.07 79.18 58.89 244.58 78.37 0.00 0.00 0.00
November 126.39 76.26 50.13 189.68 131.66 0.00 0.00 0.00
December 101.41 57.49 43.91 140.72 185.44 0.00 0.00 0.00
                 
Annual Sum or Average 151.96 82.04 69.93 289.22 77.52 0.00 0.00 0.00
Minimum of Months 101.41 49.92 43.91 128.20 5.50 0.00 0.00 0.00
Maximum of Months 221.79 130.41 91.97 503.81 185.44 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 132.16 105.58 26.58 202.79 69.91 0.00 0.00 0.00
February 82.47 55.29 27.18 113.08 67.07 0.00 0.00 0.00
March 68.27 34.59 33.67 101.81 60.12 0.00 0.00 0.00
April 59.92 24.68 35.24 119.23 30.38 0.00 0.00 0.00
May 40.04 6.96 33.07 92.76 19.10 0.00 0.00 0.00
June 33.89 2.59 31.30 110.05 5.83 0.00 0.00 0.00
July 34.34 3.26 31.07 107.55 3.76 0.00 0.00 0.00
August 42.46 11.96 30.50 120.00 4.97 0.00 0.00 0.00
September 60.32 25.49 34.82 138.40 8.24 0.00 0.00 0.00
October 96.82 67.02 29.79 167.00 39.41 0.00 0.00 0.00
November 113.80 87.41 26.40 172.76 62.18 0.00 0.00 0.00
December 123.08 97.51 25.57 180.41 84.39 0.00 0.00 0.00
                 
Annual Sum or Average 73.97 43.53 30.44 135.68 37.83 0.00 0.00 0.00
Minimum of Months 33.89 2.59 25.57 92.76 3.76 0.00 0.00 0.00
Maximum of Months 132.16 105.58 35.24 202.79 84.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.03 0.00 16.03 17.30 63.48 0.00 0.00 0.00
February 18.27 0.00 18.27 11.54 63.32 0.00 0.00 0.00
March 24.29 0.00 24.28 28.80 53.69 0.00 0.00 0.00
April 29.74 0.44 29.30 63.31 21.41 0.00 0.00 0.00
May 34.89 2.96 31.92 86.42 11.48 0.00 0.00 0.00
June 40.29 7.36 32.93 132.37 2.47 0.00 0.00 0.00
July 34.47 3.70 30.76 118.67 1.69 0.00 0.00 0.00
August 27.73 0.68 27.05 98.81 1.88 0.00 0.00 0.00
September 26.15 0.02 26.14 82.61 3.61 0.00 0.00 0.00
October 20.22 0.00 20.22 40.63 32.34 0.00 0.00 0.00
November 16.85 0.00 16.85 17.91 55.84 0.00 0.00 0.00
December 14.98 0.00 14.98 10.42 80.91 0.00 0.00 0.00
                 
Annual Sum or Average 25.35 1.27 24.08 59.29 32.55 0.00 0.00 0.00
Minimum of Months 14.98 0.00 14.98 10.42 1.69 0.00 0.00 0.00
Maximum of Months 40.29 7.36 32.93 132.37 80.91 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 120.94 75.91 45.03 160.05 140.09 0.00 0.00 0.00
February 120.23 69.17 51.05 141.21 137.66 0.00 0.00 0.00
March 149.29 76.81 72.48 203.87 116.66 0.00 0.00 0.00
April 212.74 126.76 85.99 377.32 51.32 0.00 0.00 0.00
May 220.85 131.04 89.80 425.94 29.93 0.00 0.00 0.00
June 229.78 142.76 87.03 521.74 7.60 0.00 0.00 0.00
July 194.36 109.67 84.69 455.73 4.91 0.00 0.00 0.00
August 184.63 105.48 79.14 422.54 5.97 0.00 0.00 0.00
September 151.29 72.97 78.32 334.06 10.41 0.00 0.00 0.00
October 151.83 92.35 59.47 255.79 74.37 0.00 0.00 0.00
November 116.83 70.11 46.72 154.10 124.91 0.00 0.00 0.00
December 106.72 64.54 42.18 124.03 175.51 0.00 0.00 0.00
                 
Annual Sum or Average 163.49 94.92 68.57 298.79 73.02 0.00 0.00 0.00
Minimum of Months 106.72 64.54 42.18 124.03 4.91 0.00 0.00 0.00
Maximum of Months 229.78 142.76 89.80 521.74 175.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 165.24 132.00 33.23 258.26 74.50 0.00 0.00 0.00
February 103.10 69.12 33.98 144.56 72.84 0.00 0.00 0.00
March 85.35 43.25 42.10 129.88 65.84 0.00 0.00 0.00
April 74.91 30.86 44.05 150.47 30.79 0.00 0.00 0.00
May 50.05 8.71 41.35 117.30 18.31 0.00 0.00 0.00
June 42.37 3.23 39.14 140.10 4.60 0.00 0.00 0.00
July 42.93 4.08 38.85 139.29 2.94 0.00 0.00 0.00
August 53.09 14.95 38.14 154.44 3.40 0.00 0.00 0.00
September 75.41 31.87 43.54 177.80 5.87 0.00 0.00 0.00
October 121.05 83.80 37.25 212.24 40.15 0.00 0.00 0.00
November 142.28 109.28 33.00 220.28 65.76 0.00 0.00 0.00
December 153.88 121.91 31.97 230.76 92.21 0.00 0.00 0.00
                 
Annual Sum or Average 92.48 54.42 38.06 173.19 39.64 0.00 0.00 0.00
Minimum of Months 42.37 3.23 31.97 117.30 2.94 0.00 0.00 0.00
Maximum of Months 165.24 132.00 44.05 258.26 92.21 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.04 0.00 20.04 18.44 79.97 0.00 0.00 0.00
February 22.83 0.00 22.83 12.60 78.71 0.00 0.00 0.00
March 30.35 0.00 30.35 31.82 68.10 0.00 0.00 0.00
April 37.17 0.55 36.63 70.42 29.31 0.00 0.00 0.00
May 43.60 3.70 39.90 98.53 16.14 0.00 0.00 0.00
June 50.36 9.20 41.15 154.25 4.06 0.00 0.00 0.00
July 43.08 4.63 38.45 137.60 2.64 0.00 0.00 0.00
August 34.66 0.85 33.81 113.13 3.15 0.00 0.00 0.00
September 32.69 0.02 32.67 94.46 5.76 0.00 0.00 0.00
October 25.27 0.00 25.27 44.44 42.67 0.00 0.00 0.00
November 21.06 0.00 21.06 19.26 70.76 0.00 0.00 0.00
December 18.72 0.00 18.72 11.53 100.18 0.00 0.00 0.00
                 
Annual Sum or Average 31.68 1.58 30.10 67.47 41.64 0.00 0.00 0.00
Minimum of Months 18.72 0.00 18.72 11.53 2.64 0.00 0.00 0.00
Maximum of Months 50.36 9.20 41.15 154.25 100.18 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 120.94 75.91 45.03 168.28 134.54 0.00 0.00 0.00
February 120.23 69.17 51.05 146.55 133.42 0.00 0.00 0.00
March 149.29 76.81 72.48 208.07 114.47 0.00 0.00 0.00
April 212.74 126.76 85.99 379.56 50.58 0.00 0.00 0.00
May 220.85 131.04 89.80 426.53 29.79 0.00 0.00 0.00
June 229.78 142.76 87.03 521.48 7.63 0.00 0.00 0.00
July 194.36 109.67 84.69 455.90 4.91 0.00 0.00 0.00
August 184.63 105.48 79.14 423.86 5.86 0.00 0.00 0.00
September 151.29 72.97 78.32 336.49 10.07 0.00 0.00 0.00
October 151.83 92.35 59.47 260.62 72.07 0.00 0.00 0.00
November 116.83 70.11 46.72 160.62 120.08 0.00 0.00 0.00
December 106.72 64.54 42.18 131.74 168.31 0.00 0.00 0.00
                 
Annual Sum or Average 163.49 94.92 68.57 302.39 70.73 0.00 0.00 0.00
Minimum of Months 106.72 64.54 42.18 131.74 4.91 0.00 0.00 0.00
Maximum of Months 229.78 142.76 89.80 521.48 168.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.38 0.00 25.38 19.92 119.25 0.00 0.00 0.00
February 28.92 0.00 28.92 14.51 114.27 0.00 0.00 0.00
March 38.44 0.00 38.44 38.98 98.95 0.00 0.00 0.00
April 47.08 0.69 46.38 85.99 48.81 0.00 0.00 0.00
May 55.22 4.69 50.53 119.16 29.37 0.00 0.00 0.00
June 63.77 11.65 52.12 187.45 9.16 0.00 0.00 0.00
July 54.55 5.86 48.69 163.49 6.30 0.00 0.00 0.00
August 43.90 1.08 42.82 133.53 8.74 0.00 0.00 0.00
September 41.39 0.03 41.37 110.38 14.90 0.00 0.00 0.00
October 32.01 0.00 32.01 51.49 69.12 0.00 0.00 0.00
November 26.67 0.00 26.67 20.84 108.18 0.00 0.00 0.00
December 23.71 0.00 23.71 11.68 144.50 0.00 0.00 0.00
                 
Annual Sum or Average 40.13 2.00 38.12 80.09 64.09 0.00 0.00 0.00
Minimum of Months 23.71 0.00 23.71 11.68 6.30 0.00 0.00 0.00
Maximum of Months 63.77 11.65 52.12 187.45 144.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.36 0.00 9.36 7.34 43.96 0.00 0.00 0.00
February 10.66 0.00 10.66 5.35 42.12 0.00 0.00 0.00
March 14.17 0.00 14.17 14.37 36.48 0.00 0.00 0.00
April 17.35 0.26 17.10 31.70 17.99 0.00 0.00 0.00
May 20.36 1.73 18.63 43.93 10.83 0.00 0.00 0.00
June 23.51 4.30 19.21 69.10 3.37 0.00 0.00 0.00
July 20.11 2.16 17.95 60.27 2.32 0.00 0.00 0.00
August 16.18 0.40 15.78 49.22 3.22 0.00 0.00 0.00
September 15.26 0.01 15.25 40.69 5.49 0.00 0.00 0.00
October 11.80 0.00 11.80 18.98 25.48 0.00 0.00 0.00
November 9.83 0.00 9.83 7.68 39.88 0.00 0.00 0.00
December 8.74 0.00 8.74 4.31 53.27 0.00 0.00 0.00
                 
Annual Sum or Average 14.79 0.74 14.05 29.52 23.63 0.00 0.00 0.00
Minimum of Months 8.74 0.00 8.74 4.31 2.32 0.00 0.00 0.00
Maximum of Months 23.51 4.30 19.21 69.10 53.27 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.10 61.59 15.51 120.63 39.22 0.00 0.00 0.00
February 48.11 32.25 15.86 67.86 37.91 0.00 0.00 0.00
March 39.82 20.18 19.64 60.89 34.74 0.00 0.00 0.00
April 34.95 14.40 20.56 69.43 18.54 0.00 0.00 0.00
May 23.36 4.06 19.29 53.07 12.16 0.00 0.00 0.00
June 19.77 1.51 18.26 62.63 3.90 0.00 0.00 0.00
July 20.03 1.90 18.13 61.13 2.57 0.00 0.00 0.00
August 24.77 6.98 17.79 68.80 3.41 0.00 0.00 0.00
September 35.19 14.87 20.31 79.95 5.44 0.00 0.00 0.00
October 56.48 39.10 17.38 97.90 23.36 0.00 0.00 0.00
November 66.39 50.99 15.40 102.42 35.59 0.00 0.00 0.00
December 71.80 56.88 14.92 107.93 46.92 0.00 0.00 0.00
                 
Annual Sum or Average 43.15 25.39 17.76 79.49 21.92 0.00 0.00 0.00
Minimum of Months 19.77 1.51 14.92 53.07 2.57 0.00 0.00 0.00
Maximum of Months 77.10 61.59 20.56 120.63 46.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 209.26 167.17 42.09 327.40 106.44 0.00 0.00 0.00
February 130.57 87.54 43.04 184.18 102.91 0.00 0.00 0.00
March 108.09 54.77 53.32 165.26 94.28 0.00 0.00 0.00
April 94.87 39.08 55.79 188.45 50.32 0.00 0.00 0.00
May 63.39 11.03 52.36 144.05 33.00 0.00 0.00 0.00
June 53.66 4.09 49.56 169.99 10.58 0.00 0.00 0.00
July 54.37 5.17 49.20 165.92 6.98 0.00 0.00 0.00
August 67.23 18.94 48.30 186.73 9.26 0.00 0.00 0.00
September 95.50 40.36 55.14 217.01 14.77 0.00 0.00 0.00
October 153.30 106.12 47.17 265.73 63.41 0.00 0.00 0.00
November 180.19 138.40 41.80 277.98 96.60 0.00 0.00 0.00
December 194.88 154.40 40.48 292.95 127.34 0.00 0.00 0.00
                 
Annual Sum or Average 117.12 68.92 48.20 215.75 59.48 0.00 0.00 0.00
Minimum of Months 53.66 4.09 40.48 144.05 6.98 0.00 0.00 0.00
Maximum of Months 209.26 167.17 55.79 327.40 127.34 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 165.24 132.00 33.23 258.26 73.84 0.00 0.00 0.00
February 103.10 69.12 33.98 145.76 71.35 0.00 0.00 0.00
March 85.35 43.25 42.10 131.15 65.00 0.00 0.00 0.00
April 74.91 30.86 44.05 150.73 29.81 0.00 0.00 0.00
May 50.05 8.71 41.35 118.49 17.53 0.00 0.00 0.00
June 42.37 3.23 39.14 141.39 4.36 0.00 0.00 0.00
July 42.93 4.08 38.85 140.94 2.80 0.00 0.00 0.00
August 53.09 14.95 38.14 155.62 3.09 0.00 0.00 0.00
September 75.41 31.87 43.54 178.20 5.35 0.00 0.00 0.00
October 121.05 83.80 37.25 212.72 39.11 0.00 0.00 0.00
November 142.28 109.28 33.00 220.14 65.14 0.00 0.00 0.00
December 153.88 121.91 31.97 231.47 91.16 0.00 0.00 0.00
                 
Annual Sum or Average 92.48 54.42 38.06 173.98 38.92 0.00 0.00 0.00
Minimum of Months 42.37 3.23 31.97 118.49 2.80 0.00 0.00 0.00
Maximum of Months 165.24 132.00 44.05 258.26 91.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 127.00 79.12 47.88 185.60 151.23 0.00 0.00 0.00
February 102.87 49.92 52.94 122.01 143.62 0.00 0.00 0.00
March 136.12 65.10 71.02 191.91 123.48 0.00 0.00 0.00
April 208.46 118.98 89.48 372.08 55.33 0.00 0.00 0.00
May 209.22 117.24 91.97 406.64 32.52 0.00 0.00 0.00
June 221.79 130.41 91.37 502.64 7.99 0.00 0.00 0.00
July 161.33 75.18 86.15 395.93 5.17 0.00 0.00 0.00
August 154.44 77.66 76.78 370.03 5.73 0.00 0.00 0.00
September 134.39 56.51 77.89 305.58 10.21 0.00 0.00 0.00
October 138.07 79.18 58.89 238.49 77.90 0.00 0.00 0.00
November 126.39 76.26 50.13 182.37 132.79 0.00 0.00 0.00
December 101.41 57.49 43.91 132.44 188.08 0.00 0.00 0.00
                 
Annual Sum or Average 151.96 82.04 69.93 284.52 77.59 0.00 0.00 0.00
Minimum of Months 101.41 49.92 43.91 122.01 5.17 0.00 0.00 0.00
Maximum of Months 221.79 130.41 91.97 502.64 188.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.04 0.00 20.04 20.37 78.13 0.00 0.00 0.00
February 22.83 0.00 22.83 14.15 75.88 0.00 0.00 0.00
March 30.35 0.00 30.35 34.04 66.45 0.00 0.00 0.00
April 37.17 0.55 36.63 71.85 28.29 0.00 0.00 0.00
May 43.60 3.70 39.90 100.13 15.66 0.00 0.00 0.00
June 50.36 9.20 41.15 155.22 3.91 0.00 0.00 0.00
July 43.08 4.63 38.45 139.18 2.55 0.00 0.00 0.00
August 34.66 0.85 33.81 114.70 2.92 0.00 0.00 0.00
September 32.69 0.02 32.67 95.80 5.30 0.00 0.00 0.00
October 25.27 0.00 25.27 46.60 40.79 0.00 0.00 0.00
November 21.06 0.00 21.06 20.70 69.19 0.00 0.00 0.00
December 18.72 0.00 18.72 13.09 97.85 0.00 0.00 0.00
                 
Annual Sum or Average 31.68 1.58 30.10 69.08 40.44 0.00 0.00 0.00
Minimum of Months 18.72 0.00 18.72 13.09 2.55 0.00 0.00 0.00
Maximum of Months 50.36 9.20 41.15 155.22 97.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 127.00 79.12 47.88 194.80 144.89 0.00 0.00 0.00
February 102.87 49.92 52.94 128.13 138.98 0.00 0.00 0.00
March 136.12 65.10 71.02 196.97 121.04 0.00 0.00 0.00
April 208.46 118.98 89.48 374.73 54.45 0.00 0.00 0.00
May 209.22 117.24 91.97 407.24 32.36 0.00 0.00 0.00
June 221.79 130.41 91.37 502.25 8.00 0.00 0.00 0.00
July 161.33 75.18 86.15 396.05 5.17 0.00 0.00 0.00
August 154.44 77.66 76.78 371.46 5.61 0.00 0.00 0.00
September 134.39 56.51 77.89 308.27 9.84 0.00 0.00 0.00
October 138.07 79.18 58.89 244.47 75.12 0.00 0.00 0.00
November 126.39 76.26 50.13 189.85 127.59 0.00 0.00 0.00
December 101.41 57.49 43.91 141.49 181.01 0.00 0.00 0.00
                 
Annual Sum or Average 151.96 82.04 69.93 288.68 75.09 0.00 0.00 0.00
Minimum of Months 101.41 49.92 43.91 128.13 5.17 0.00 0.00 0.00
Maximum of Months 221.79 130.41 91.97 502.25 181.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 242.33 193.60 48.74 372.62 112.85 0.00 0.00 0.00
February 151.21 101.37 49.84 208.24 109.80 0.00 0.00 0.00
March 125.18 63.43 61.75 189.14 97.19 0.00 0.00 0.00
April 109.86 45.26 64.61 224.34 42.32 0.00 0.00 0.00
May 73.41 12.77 60.64 179.91 24.04 0.00 0.00 0.00
June 62.14 4.74 57.40 216.76 5.31 0.00 0.00 0.00
July 62.97 5.99 56.98 213.81 3.63 0.00 0.00 0.00
August 77.86 21.93 55.93 234.01 4.07 0.00 0.00 0.00
September 110.60 46.74 63.85 264.28 7.41 0.00 0.00 0.00
October 177.53 122.90 54.63 309.83 58.49 0.00 0.00 0.00
November 208.67 160.27 48.40 318.04 99.08 0.00 0.00 0.00
December 225.68 178.80 46.88 331.74 140.37 0.00 0.00 0.00
                 
Annual Sum or Average 135.63 79.81 55.82 255.61 58.51 0.00 0.00 0.00
Minimum of Months 62.14 4.74 46.88 179.91 3.63 0.00 0.00 0.00
Maximum of Months 242.33 193.60 64.61 372.62 140.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 140.27 0.00 140.27 113.19 677.14 0.00 0.00 0.00
February 159.84 0.00 159.84 71.33 680.00 0.00 0.00 0.00
March 212.46 0.01 212.45 203.34 586.89 0.00 0.00 0.00
April 260.20 3.83 256.37 479.16 279.86 0.00 0.00 0.00
May 305.21 25.92 279.29 660.52 170.49 0.00 0.00 0.00
June 352.47 64.40 288.07 1027.58 57.52 0.00 0.00 0.00
July 301.52 32.40 269.12 894.00 41.55 0.00 0.00 0.00
August 242.62 5.96 236.66 736.21 57.35 0.00 0.00 0.00
September 228.79 0.14 228.65 614.58 93.20 0.00 0.00 0.00
October 176.90 0.00 176.90 294.81 387.18 0.00 0.00 0.00
November 147.39 0.00 147.39 117.33 612.96 0.00 0.00 0.00
December 131.03 0.00 131.03 62.94 826.54 0.00 0.00 0.00
                 
Annual Sum or Average 221.78 11.08 210.70 441.29 371.25 0.00 0.00 0.00
Minimum of Months 131.03 0.00 131.03 62.94 41.55 0.00 0.00 0.00
Maximum of Months 352.47 64.40 288.07 1027.58 826.54 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 140.27 0.00 140.27 103.39 702.96 0.00 0.00 0.00
February 159.84 0.00 159.84 62.90 713.66 0.00 0.00 0.00
March 212.46 0.01 212.45 189.64 610.99 0.00 0.00 0.00
April 260.20 3.83 256.37 462.94 290.77 0.00 0.00 0.00
May 305.21 25.92 279.29 642.28 177.08 0.00 0.00 0.00
June 352.47 64.40 288.07 1007.53 60.64 0.00 0.00 0.00
July 301.52 32.40 269.12 873.72 44.67 0.00 0.00 0.00
August 242.62 5.96 236.66 717.22 61.92 0.00 0.00 0.00
September 228.79 0.14 228.65 597.06 99.51 0.00 0.00 0.00
October 176.90 0.00 176.90 281.84 403.12 0.00 0.00 0.00
November 147.39 0.00 147.39 107.77 638.06 0.00 0.00 0.00
December 131.03 0.00 131.03 55.12 859.76 0.00 0.00 0.00
                 
Annual Sum or Average 221.78 11.08 210.70 426.79 387.20 0.00 0.00 0.00
Minimum of Months 131.03 0.00 131.03 55.12 44.67 0.00 0.00 0.00
Maximum of Months 352.47 64.40 288.07 1007.53 859.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.04 0.00 20.04 17.80 101.48 0.00 0.00 0.00
February 22.83 0.00 22.83 10.80 103.30 0.00 0.00 0.00
March 30.35 0.00 30.35 31.18 89.28 0.00 0.00 0.00
April 37.17 0.55 36.63 74.97 43.58 0.00 0.00 0.00
May 43.60 3.70 39.90 103.52 28.61 0.00 0.00 0.00
June 50.36 9.20 41.15 156.92 11.53 0.00 0.00 0.00
July 43.08 4.63 38.45 137.23 8.85 0.00 0.00 0.00
August 34.66 0.85 33.81 114.92 11.58 0.00 0.00 0.00
September 32.69 0.02 32.67 96.84 16.85 0.00 0.00 0.00
October 25.27 0.00 25.27 46.36 59.28 0.00 0.00 0.00
November 21.06 0.00 21.06 18.52 91.97 0.00 0.00 0.00
December 18.72 0.00 18.72 10.18 122.95 0.00 0.00 0.00
                 
Annual Sum or Average 31.68 1.58 30.10 68.54 57.24 0.00 0.00 0.00
Minimum of Months 18.72 0.00 18.72 10.18 8.85 0.00 0.00 0.00
Maximum of Months 50.36 9.20 41.15 156.92 122.95 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 241.87 151.81 90.06 328.87 344.40 0.00 0.00 0.00
February 240.43 138.34 102.10 282.53 354.56 0.00 0.00 0.00
March 298.56 153.60 144.96 409.05 304.68 0.00 0.00 0.00
April 425.45 253.49 171.96 774.59 154.12 0.00 0.00 0.00
May 441.66 262.07 179.60 869.31 105.93 0.00 0.00 0.00
June 459.53 285.49 174.04 1050.24 43.16 0.00 0.00 0.00
July 388.70 219.32 169.38 908.28 32.97 0.00 0.00 0.00
August 369.23 210.95 158.27 851.70 43.37 0.00 0.00 0.00
September 302.56 145.93 156.63 679.04 61.77 0.00 0.00 0.00
October 303.63 184.69 118.94 526.16 204.17 0.00 0.00 0.00
November 233.65 140.21 93.44 314.67 315.49 0.00 0.00 0.00
December 213.43 129.08 84.35 252.59 415.57 0.00 0.00 0.00
                 
Annual Sum or Average 326.95 189.82 137.13 605.46 197.66 0.00 0.00 0.00
Minimum of Months 213.43 129.08 84.35 252.59 32.97 0.00 0.00 0.00
Maximum of Months 459.53 285.49 179.60 1050.24 415.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 165.24 132.00 33.23 262.06 91.69 0.00 0.00 0.00
February 103.10 69.12 33.98 145.45 93.55 0.00 0.00 0.00
March 85.35 43.25 42.10 131.33 85.37 0.00 0.00 0.00
April 74.91 30.86 44.05 155.86 44.73 0.00 0.00 0.00
May 50.05 8.71 41.35 122.47 30.98 0.00 0.00 0.00
June 42.37 3.23 39.14 142.65 12.33 0.00 0.00 0.00
July 42.93 4.08 38.85 139.22 9.26 0.00 0.00 0.00
August 53.09 14.95 38.14 156.99 11.80 0.00 0.00 0.00
September 75.41 31.87 43.54 181.19 16.81 0.00 0.00 0.00
October 121.05 83.80 37.25 216.73 54.98 0.00 0.00 0.00
November 142.28 109.28 33.00 223.23 83.29 0.00 0.00 0.00
December 153.88 121.91 31.97 233.51 109.33 0.00 0.00 0.00
                 
Annual Sum or Average 92.48 54.42 38.06 176.14 53.51 0.00 0.00 0.00
Minimum of Months 42.37 3.23 31.97 122.47 9.26 0.00 0.00 0.00
Maximum of Months 165.24 132.00 44.05 262.06 109.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.38 0.00 25.38 17.23 121.74 0.00 0.00 0.00
February 28.92 0.00 28.92 12.22 117.32 0.00 0.00 0.00
March 38.44 0.00 38.44 35.18 102.25 0.00 0.00 0.00
April 47.08 0.69 46.38 82.03 50.54 0.00 0.00 0.00
May 55.22 4.69 50.53 115.52 30.50 0.00 0.00 0.00
June 63.77 11.65 52.12 183.05 9.88 0.00 0.00 0.00
July 54.55 5.86 48.69 158.64 7.06 0.00 0.00 0.00
August 43.90 1.08 42.82 129.13 9.88 0.00 0.00 0.00
September 41.39 0.03 41.37 106.51 16.45 0.00 0.00 0.00
October 32.01 0.00 32.01 48.73 70.48 0.00 0.00 0.00
November 26.67 0.00 26.67 18.23 110.56 0.00 0.00 0.00
December 23.71 0.00 23.71 10.00 145.45 0.00 0.00 0.00
                 
Annual Sum or Average 40.13 2.00 38.12 76.67 65.80 0.00 0.00 0.00
Minimum of Months 23.71 0.00 23.71 10.00 7.06 0.00 0.00 0.00
Maximum of Months 63.77 11.65 52.12 183.05 145.45 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.71 0.00 22.71 15.42 108.91 0.00 0.00 0.00
February 25.87 0.00 25.87 10.94 104.96 0.00 0.00 0.00
March 34.39 0.00 34.39 31.48 91.48 0.00 0.00 0.00
April 42.12 0.62 41.50 73.39 45.22 0.00 0.00 0.00
May 49.41 4.20 45.21 103.36 27.28 0.00 0.00 0.00
June 57.06 10.43 46.63 163.78 8.84 0.00 0.00 0.00
July 48.81 5.24 43.56 141.94 6.32 0.00 0.00 0.00
August 39.27 0.96 38.31 115.53 8.84 0.00 0.00 0.00
September 37.04 0.02 37.01 95.29 14.72 0.00 0.00 0.00
October 28.64 0.00 28.64 43.60 63.06 0.00 0.00 0.00
November 23.86 0.00 23.86 16.31 98.91 0.00 0.00 0.00
December 21.21 0.00 21.21 8.95 130.12 0.00 0.00 0.00
                 
Annual Sum or Average 35.90 1.79 34.11 68.60 58.87 0.00 0.00 0.00
Minimum of Months 21.21 0.00 21.21 8.95 6.32 0.00 0.00 0.00
Maximum of Months 57.06 10.43 46.63 163.78 130.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 616.87 492.81 124.06 948.71 320.85 0.00 0.00 0.00
February 384.91 258.05 126.87 530.51 311.61 0.00 0.00 0.00
March 318.65 161.47 157.18 471.27 288.14 0.00 0.00 0.00
April 279.66 115.20 164.46 540.66 153.57 0.00 0.00 0.00
May 186.87 32.51 154.36 413.69 100.80 0.00 0.00 0.00
June 158.17 12.07 146.11 489.16 33.38 0.00 0.00 0.00
July 160.28 15.24 145.04 474.99 22.84 0.00 0.00 0.00
August 198.20 55.82 142.38 536.54 30.62 0.00 0.00 0.00
September 281.53 118.99 162.54 625.40 47.89 0.00 0.00 0.00
October 451.90 312.84 139.06 769.15 190.88 0.00 0.00 0.00
November 531.19 407.98 123.21 804.32 291.40 0.00 0.00 0.00
December 574.48 455.14 119.34 852.23 378.28 0.00 0.00 0.00
                 
Annual Sum or Average 345.26 203.16 142.10 622.20 180.32 0.00 0.00 0.00
Minimum of Months 158.17 12.07 119.34 413.69 22.84 0.00 0.00 0.00
Maximum of Months 616.87 492.81 164.46 948.71 378.28 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223838E+10 0.178821E+10 0.450171E+09 0.341766E+10 0.114183E+10
February 0.126153E+10 0.845731E+09 0.415798E+09 0.173817E+10 0.957597E+09
March 0.115623E+10 0.585894E+09 0.570335E+09 0.172247E+10 0.975281E+09
April 0.982044E+09 0.404532E+09 0.577512E+09 0.186463E+10 0.544638E+09
May 0.678057E+09 0.117952E+09 0.560105E+09 0.142779E+10 0.383879E+09
June 0.555427E+09 42376069.35 0.513050E+09 0.158022E+10 0.139526E+09
July 0.581591E+09 55297824.35 0.526293E+09 0.160834E+10 97997643.97
August 0.719166E+09 0.202544E+09 0.516622E+09 0.184841E+10 0.131700E+09
September 0.988595E+09 0.417832E+09 0.570763E+09 0.212968E+10 0.192662E+09
October 0.163976E+10 0.113516E+10 0.504604E+09 0.277078E+10 0.690407E+09
November 0.186529E+10 0.143263E+10 0.432667E+09 0.281688E+10 0.992144E+09
December 0.208454E+10 0.165152E+10 0.433026E+09 0.304886E+10 0.133758E+10
           
Annual Sum or Average 0.147506E+11 0.867966E+10 0.607095E+10 0.259739E+11 0.758524E+10
Minimum of Months 0.555427E+09 42376069.35 0.415798E+09 0.142779E+10 97997643.97
Maximum of Months 0.223838E+10 0.178821E+10 0.577512E+09 0.341766E+10 0.133758E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.630312E+10 0.503547E+10 0.126765E+10 0.960335E+10 0.322375E+10
February 0.355238E+10 0.238152E+10 0.117086E+10 0.489970E+10 0.275562E+10
March 0.325586E+10 0.164984E+10 0.160603E+10 0.490886E+10 0.274910E+10
April 0.276537E+10 0.113914E+10 0.162624E+10 0.534270E+10 0.147338E+10
May 0.190936E+10 0.332145E+09 0.157722E+10 0.418411E+10 0.101643E+10
June 0.156404E+10 0.119328E+09 0.144472E+10 0.458917E+10 0.365274E+09
July 0.163772E+10 0.155715E+09 0.148201E+10 0.466634E+10 0.255564E+09
August 0.202512E+10 0.570351E+09 0.145477E+10 0.530214E+10 0.346201E+09
September 0.278382E+10 0.117659E+10 0.160723E+10 0.606271E+10 0.519043E+09
October 0.461746E+10 0.319653E+10 0.142093E+10 0.782526E+10 0.192060E+10
November 0.525254E+10 0.403418E+10 0.121836E+10 0.793033E+10 0.278569E+10
December 0.586993E+10 0.465056E+10 0.121937E+10 0.855807E+10 0.382197E+10
           
Annual Sum or Average 0.415367E+11 0.244414E+11 0.170954E+11 0.738728E+11 0.212326E+11
Minimum of Months 0.156404E+10 0.119328E+09 0.117086E+10 0.418411E+10 0.255564E+09
Maximum of Months 0.630312E+10 0.503547E+10 0.162624E+10 0.960335E+10 0.382197E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.818812E+10 0.654136E+10 0.164675E+10 0.127261E+11 0.434062E+10
February 0.461475E+10 0.309374E+10 0.152101E+10 0.646210E+10 0.384186E+10
March 0.422955E+10 0.214323E+10 0.208632E+10 0.643483E+10 0.383924E+10
April 0.359238E+10 0.147980E+10 0.211257E+10 0.706244E+10 0.201336E+10
May 0.248037E+10 0.431476E+09 0.204890E+10 0.547407E+10 0.139946E+10
June 0.203178E+10 0.155014E+09 0.187677E+10 0.606224E+10 0.486018E+09
July 0.212749E+10 0.202283E+09 0.192521E+10 0.615815E+10 0.342447E+09
August 0.263075E+10 0.740919E+09 0.188983E+10 0.703290E+10 0.458220E+09
September 0.361634E+10 0.152845E+10 0.208788E+10 0.804133E+10 0.677155E+09
October 0.599834E+10 0.415247E+10 0.184587E+10 0.103639E+11 0.259141E+10
November 0.682335E+10 0.524063E+10 0.158272E+10 0.104896E+11 0.379255E+10
December 0.762538E+10 0.604134E+10 0.158404E+10 0.113280E+11 0.519051E+10
           
Annual Sum or Average 0.539586E+11 0.317507E+11 0.222079E+11 0.976357E+11 0.289729E+11
Minimum of Months 0.203178E+10 0.155014E+09 0.152101E+10 0.547407E+10 0.342447E+09
Maximum of Months 0.818812E+10 0.654136E+10 0.211257E+10 0.127261E+11 0.519051E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.442566E+09 0.353559E+09 89007348.67 0.694588E+09 0.201164E+09
February 0.249427E+09 0.167216E+09 82211105.16 0.353987E+09 0.176118E+09
March 0.228607E+09 0.115841E+09 0.112766E+09 0.353023E+09 0.176817E+09
April 0.194169E+09 79982898.78 0.114186E+09 0.392699E+09 80168706.92
May 0.134065E+09 23321164.89 0.110744E+09 0.316974E+09 49599685.70
June 0.109819E+09 8378476.71 0.101441E+09 0.365185E+09 12484660.77
July 0.114992E+09 10933329.61 0.104059E+09 0.376580E+09 8055521.87
August 0.142193E+09 40046470.60 0.102146E+09 0.416610E+09 9114212.22
September 0.195463E+09 82612529.72 0.112851E+09 0.462809E+09 15335304.51
October 0.324210E+09 0.224440E+09 99769849.61 0.572158E+09 0.108289E+09
November 0.368801E+09 0.283255E+09 85546508.11 0.573048E+09 0.172294E+09
December 0.412151E+09 0.326533E+09 85617432.54 0.621131E+09 0.247786E+09
           
Annual Sum or Average 0.291646E+10 0.171612E+10 0.120034E+10 0.549879E+10 0.125723E+10
Minimum of Months 0.109819E+09 8378476.71 82211105.16 0.316974E+09 8055521.87
Maximum of Months 0.442566E+09 0.353559E+09 0.114186E+09 0.694588E+09 0.247786E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.340154E+09 0.211926E+09 0.128229E+09 0.499258E+09 0.414521E+09
February 0.248858E+09 0.120775E+09 0.128083E+09 0.297025E+09 0.356074E+09
March 0.364588E+09 0.174372E+09 0.190216E+09 0.516678E+09 0.337300E+09
April 0.540336E+09 0.308393E+09 0.231943E+09 0.970630E+09 0.148900E+09
May 0.560366E+09 0.314023E+09 0.246343E+09 0.109341E+10 91760554.46
June 0.574867E+09 0.338034E+09 0.236833E+09 0.130681E+10 22588250.10
July 0.432114E+09 0.201359E+09 0.230755E+09 0.106255E+10 14738029.40
August 0.413642E+09 0.208000E+09 0.205642E+09 0.992920E+09 16685839.24
September 0.348351E+09 0.146469E+09 0.201882E+09 0.793438E+09 28909066.77
October 0.369811E+09 0.212073E+09 0.157738E+09 0.640789E+09 0.216499E+09
November 0.327596E+09 0.197665E+09 0.129932E+09 0.474955E+09 0.353002E+09
December 0.271608E+09 0.153993E+09 0.117616E+09 0.355537E+09 0.514238E+09
           
Annual Sum or Average 0.479229E+10 0.258708E+10 0.220521E+10 0.900400E+10 0.251521E+10
Minimum of Months 0.248858E+09 0.120775E+09 0.117616E+09 0.297025E+09 14738029.40
Maximum of Months 0.574867E+09 0.338034E+09 0.246343E+09 0.130681E+10 0.514238E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53674072.02 0.00 53674072.02 51864716.52 0.215564E+09
February 55241433.50 0.00 55241433.50 33093896.69 0.188729E+09
March 81295770.76 3216.16 81292554.60 89928196.49 0.181934E+09
April 96350800.51 1418628.78 94932171.74 0.185745E+09 76113789.11
May 0.116786E+09 9916509.70 0.106870E+09 0.267194E+09 44060318.92
June 0.130521E+09 23848337.92 0.106672E+09 0.401671E+09 10970161.75
July 0.115375E+09 12397170.40 0.102978E+09 0.372060E+09 7225550.85
August 92836668.46 2279405.50 90557262.96 0.306230E+09 8485874.30
September 84720382.40 52432.38 84667950.02 0.247080E+09 15026154.02
October 67690153.51 0.00 67690153.51 0.122765E+09 0.113962E+09
November 54578999.93 0.00 54578999.93 51506315.32 0.185125E+09
December 50136496.34 0.00 50136496.34 32820848.21 0.268758E+09
           
Annual Sum or Average 0.999207E+09 49915700.83 0.949291E+09 0.216196E+10 0.131595E+10
Minimum of Months 50136496.34 0.00 50136496.34 32820848.21 7225550.85
Maximum of Months 0.130521E+09 23848337.92 0.106870E+09 0.401671E+09 0.268758E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.340154E+09 0.211926E+09 0.128229E+09 0.520647E+09 0.399724E+09
February 0.248858E+09 0.120775E+09 0.128083E+09 0.310133E+09 0.345812E+09
March 0.364588E+09 0.174372E+09 0.190216E+09 0.528906E+09 0.331458E+09
April 0.540336E+09 0.308393E+09 0.231943E+09 0.977168E+09 0.146733E+09
May 0.560366E+09 0.314023E+09 0.246343E+09 0.109498E+10 91343107.88
June 0.574867E+09 0.338034E+09 0.236833E+09 0.130589E+10 22609655.49
July 0.432114E+09 0.201359E+09 0.230755E+09 0.106289E+10 14738559.99
August 0.413642E+09 0.208000E+09 0.205642E+09 0.996568E+09 16366553.46
September 0.348351E+09 0.146469E+09 0.201882E+09 0.800069E+09 27951842.40
October 0.369811E+09 0.212073E+09 0.157738E+09 0.655095E+09 0.209901E+09
November 0.327596E+09 0.197665E+09 0.129932E+09 0.491645E+09 0.341258E+09
December 0.271608E+09 0.153993E+09 0.117616E+09 0.376918E+09 0.496687E+09
           
Annual Sum or Average 0.479229E+10 0.258708E+10 0.220521E+10 0.912091E+10 0.244458E+10
Minimum of Months 0.248858E+09 0.120775E+09 0.117616E+09 0.310133E+09 14738559.99
Maximum of Months 0.574867E+09 0.338034E+09 0.246343E+09 0.130589E+10 0.496687E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.353983E+09 0.282791E+09 71191720.82 0.543155E+09 0.187258E+09
February 0.199502E+09 0.133746E+09 65755807.07 0.273561E+09 0.162250E+09
March 0.182850E+09 92654621.17 90194909.73 0.272688E+09 0.161023E+09
April 0.155304E+09 63973596.40 91330373.15 0.309056E+09 78736864.57
May 0.107231E+09 18653222.29 88577606.46 0.248435E+09 51168857.69
June 87837819.98 6701448.63 81136371.35 0.285248E+09 15109028.51
July 91975290.32 8744924.55 83230365.76 0.288066E+09 10060622.97
August 0.113732E+09 32030806.41 81700800.92 0.321405E+09 13308117.55
September 0.156339E+09 66076882.86 90262586.66 0.358740E+09 21359746.01
October 0.259316E+09 0.179516E+09 79800009.62 0.447296E+09 0.105557E+09
November 0.294982E+09 0.226559E+09 68423598.87 0.447797E+09 0.161168E+09
December 0.329655E+09 0.261175E+09 68480327.14 0.483204E+09 0.226026E+09
           
Annual Sum or Average 0.233271E+10 0.137262E+10 0.960084E+09 0.427865E+10 0.119302E+10
Minimum of Months 87837819.98 6701448.63 65755807.07 0.248435E+09 10060622.97
Maximum of Months 0.353983E+09 0.282791E+09 91330373.15 0.543155E+09 0.226026E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 42944949.46 0.00 42944949.46 46323909.69 0.170034E+09
February 44199004.85 0.00 44199004.85 27907259.34 0.153185E+09
March 65045237.58 2573.27 65042664.31 77131890.78 0.143792E+09
April 77090857.89 1135053.46 75955804.43 0.164098E+09 55483929.83
May 93441433.49 7934259.35 85507174.14 0.231469E+09 30738754.70
June 0.104430E+09 19081199.32 85349110.47 0.343104E+09 6399967.03
July 92312481.83 9919050.97 82393430.86 0.317857E+09 4532587.84
August 74279179.59 1823766.12 72455413.47 0.264664E+09 5046058.08
September 67785290.05 41951.47 67743338.59 0.214126E+09 9355002.92
October 54159300.98 0.00 54159300.98 0.108825E+09 86621851.76
November 43668987.75 0.00 43668987.75 46411450.87 0.144740E+09
December 40114513.77 0.00 40114513.77 27908009.96 0.216700E+09
           
Annual Sum or Average 0.799472E+09 39937853.95 0.759534E+09 0.186983E+10 0.102663E+10
Minimum of Months 40114513.77 0.00 40114513.77 27907259.34 4532587.84
Maximum of Months 0.104430E+09 19081199.32 85507174.14 0.343104E+09 0.216700E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.323939E+09 0.203319E+09 0.120620E+09 0.428670E+09 0.375219E+09
February 0.290851E+09 0.167343E+09 0.123508E+09 0.341605E+09 0.333029E+09
March 0.399855E+09 0.205717E+09 0.194139E+09 0.546047E+09 0.312465E+09
April 0.551427E+09 0.328551E+09 0.222876E+09 0.978013E+09 0.133030E+09
May 0.591518E+09 0.350985E+09 0.240533E+09 0.114083E+10 80174013.02
June 0.595597E+09 0.370022E+09 0.225575E+09 0.135235E+10 19689204.99
July 0.520577E+09 0.293732E+09 0.226845E+09 0.122063E+10 13141059.28
August 0.494504E+09 0.282527E+09 0.211977E+09 0.113173E+10 16000340.96
September 0.392148E+09 0.189135E+09 0.203013E+09 0.865871E+09 26993819.32
October 0.406651E+09 0.247359E+09 0.159292E+09 0.685109E+09 0.199180E+09
November 0.302834E+09 0.181731E+09 0.121103E+09 0.399432E+09 0.323775E+09
December 0.285842E+09 0.172873E+09 0.112970E+09 0.332198E+09 0.470092E+09
           
Annual Sum or Average 0.515574E+10 0.299329E+10 0.216245E+10 0.942249E+10 0.230279E+10
Minimum of Months 0.285842E+09 0.167343E+09 0.112970E+09 0.332198E+09 13141059.28
Maximum of Months 0.595597E+09 0.370022E+09 0.240533E+09 0.135235E+10 0.470092E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.442566E+09 0.353559E+09 89007348.67 0.691721E+09 0.199531E+09
February 0.249427E+09 0.167216E+09 82211105.16 0.349713E+09 0.176219E+09
March 0.228607E+09 0.115841E+09 0.112766E+09 0.347871E+09 0.176349E+09
April 0.194169E+09 79982898.78 0.114186E+09 0.390026E+09 79809975.50
May 0.134065E+09 23321164.89 0.110744E+09 0.314174E+09 49040578.70
June 0.109819E+09 8378476.71 0.101441E+09 0.363146E+09 11915226.43
July 0.114992E+09 10933329.61 0.104059E+09 0.373068E+09 7872624.76
August 0.142193E+09 40046470.60 0.102146E+09 0.413641E+09 9099968.64
September 0.195463E+09 82612529.72 0.112851E+09 0.460852E+09 15211300.02
October 0.324210E+09 0.224440E+09 99769849.61 0.568471E+09 0.107543E+09
November 0.368801E+09 0.283255E+09 85546508.11 0.570961E+09 0.170463E+09
December 0.412151E+09 0.326533E+09 85617432.54 0.618062E+09 0.246975E+09
           
Annual Sum or Average 0.291646E+10 0.171612E+10 0.120034E+10 0.546171E+10 0.125003E+10
Minimum of Months 0.109819E+09 8378476.71 82211105.16 0.314174E+09 7872624.76
Maximum of Months 0.442566E+09 0.353559E+09 0.114186E+09 0.691721E+09 0.246975E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53674072.02 0.00 53674072.02 49394843.70 0.214186E+09
February 55241433.50 0.00 55241433.50 30482447.20 0.190421E+09
March 81295770.76 3216.16 81292554.60 85238212.02 0.182391E+09
April 96350800.51 1418628.78 94932171.74 0.182538E+09 75982923.82
May 0.116786E+09 9916509.70 0.106870E+09 0.263903E+09 43219989.73
June 0.130521E+09 23848337.92 0.106672E+09 0.399804E+09 10519336.15
July 0.115375E+09 12397170.40 0.102978E+09 0.368554E+09 7062109.82
August 92836668.46 2279405.50 90557262.96 0.303008E+09 8440286.96
September 84720382.40 52432.38 84667950.02 0.244848E+09 14935511.56
October 67690153.51 0.00 67690153.51 0.119031E+09 0.114286E+09
November 54578999.93 0.00 54578999.93 49928479.78 0.183410E+09
December 50136496.34 0.00 50136496.34 30872787.78 0.268310E+09
           
Annual Sum or Average 0.999207E+09 49915700.83 0.949291E+09 0.212760E+10 0.131316E+10
Minimum of Months 50136496.34 0.00 50136496.34 30482447.20 7062109.82
Maximum of Months 0.130521E+09 23848337.92 0.106870E+09 0.399804E+09 0.268310E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.323939E+09 0.203319E+09 0.120620E+09 0.450708E+09 0.360358E+09
February 0.290851E+09 0.167343E+09 0.123508E+09 0.354535E+09 0.322765E+09
March 0.399855E+09 0.205717E+09 0.194139E+09 0.557298E+09 0.306584E+09
April 0.551427E+09 0.328551E+09 0.222876E+09 0.983816E+09 0.131099E+09
May 0.591518E+09 0.350985E+09 0.240533E+09 0.114242E+10 79797586.52
June 0.595597E+09 0.370022E+09 0.225575E+09 0.135167E+10 19780229.11
July 0.520577E+09 0.293732E+09 0.226845E+09 0.122108E+10 13157887.61
August 0.494504E+09 0.282527E+09 0.211977E+09 0.113526E+10 15689607.74
September 0.392148E+09 0.189135E+09 0.203013E+09 0.872178E+09 26100066.28
October 0.406651E+09 0.247359E+09 0.159292E+09 0.698044E+09 0.193032E+09
November 0.302834E+09 0.181731E+09 0.121103E+09 0.416331E+09 0.311248E+09
December 0.285842E+09 0.172873E+09 0.112970E+09 0.352863E+09 0.450797E+09
           
Annual Sum or Average 0.515574E+10 0.299329E+10 0.216245E+10 0.953620E+10 0.223041E+10
Minimum of Months 0.285842E+09 0.167343E+09 0.112970E+09 0.352863E+09 13157887.61
Maximum of Months 0.595597E+09 0.370022E+09 0.240533E+09 0.135167E+10 0.450797E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 67974825.56 0.00 67974825.56 53364146.18 0.319390E+09
February 69959789.98 0.00 69959789.98 35108050.15 0.276436E+09
March 0.102956E+09 4073.06 0.102952E+09 0.104409E+09 0.265027E+09
April 0.122022E+09 1796603.83 0.120226E+09 0.222889E+09 0.126526E+09
May 0.147902E+09 12558633.84 0.135344E+09 0.319151E+09 78677964.86
June 0.165296E+09 30202415.22 0.135094E+09 0.485882E+09 23729911.37
July 0.146116E+09 15700234.09 0.130415E+09 0.437897E+09 16874445.94
August 0.117572E+09 2886723.24 0.114685E+09 0.357648E+09 23406391.53
September 0.107293E+09 66402.30 0.107227E+09 0.286113E+09 38617127.68
October 85725308.41 0.00 85725308.41 0.137919E+09 0.185135E+09
November 69120859.66 0.00 69120859.66 54004444.72 0.280394E+09
December 63494709.17 0.00 63494709.17 31281807.22 0.387037E+09
           
Annual Sum or Average 0.126543E+10 63215085.59 0.120222E+10 0.252567E+10 0.202125E+10
Minimum of Months 63494709.17 0.00 63494709.17 31281807.22 16874445.94
Maximum of Months 0.165296E+09 30202415.22 0.135344E+09 0.485882E+09 0.387037E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 25058335.32 0.00 25058335.32 19672233.92 0.117740E+09
February 25790075.39 0.00 25790075.39 12942280.99 0.101906E+09
March 37953831.47 1501.50 37952329.97 38489376.02 97699960.88
April 44982438.94 662302.56 44320136.38 82165963.89 46642826.07
May 54522983.56 4629632.44 49893351.11 0.117652E+09 29003955.64
June 60934981.96 11133860.83 49801121.12 0.179116E+09 8747827.91
July 53864241.38 5787756.38 48076485.00 0.161427E+09 6220619.49
August 43341827.45 1064165.72 42277661.74 0.131844E+09 8628565.10
September 39552649.37 24478.64 39528170.73 0.105473E+09 14235872.27
October 31601898.29 0.00 31601898.29 50842577.34 68248500.12
November 25480810.94 0.00 25480810.94 19908274.47 0.103365E+09
December 23406778.91 0.00 23406778.91 11531769.42 0.142678E+09
           
Annual Sum or Average 0.466491E+09 23303698.08 0.443187E+09 0.931065E+09 0.745117E+09
Minimum of Months 23406778.91 0.00 23406778.91 11531769.42 6220619.49
Maximum of Months 60934981.96 11133860.83 49893351.11 0.179116E+09 0.142678E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.206500E+09 0.164969E+09 41530470.22 0.323084E+09 0.105039E+09
February 0.116382E+09 78022138.43 38359370.38 0.164159E+09 91722323.32
March 0.106667E+09 54051088.25 52616188.64 0.163079E+09 93035051.85
April 90598271.93 37319698.27 53278573.67 0.179966E+09 48052889.16
May 62554278.62 10881561.56 51672717.06 0.142151E+09 32562100.94
June 51241154.51 3909363.47 47331791.04 0.162340E+09 10100940.75
July 53654793.16 5101447.54 48553345.62 0.163733E+09 6887737.99
August 66346579.02 18685521.81 47661057.22 0.184268E+09 9134648.04
September 91202342.18 38546673.46 52655668.72 0.207238E+09 14107218.51
October 0.151275E+09 0.104723E+09 46552209.79 0.262221E+09 62575940.55
November 0.172081E+09 0.132165E+09 39915655.96 0.265463E+09 92248681.51
December 0.192308E+09 0.152359E+09 39948749.01 0.289087E+09 0.125664E+09
           
Annual Sum or Average 0.136081E+10 0.800734E+09 0.560076E+09 0.250679E+10 0.691131E+09
Minimum of Months 51241154.51 3909363.47 38359370.38 0.142151E+09 6887737.99
Maximum of Months 0.206500E+09 0.164969E+09 53278573.67 0.323084E+09 0.125664E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.560483E+09 0.447760E+09 0.112722E+09 0.876917E+09 0.285097E+09
February 0.315883E+09 0.211768E+09 0.104115E+09 0.445562E+09 0.248953E+09
March 0.289517E+09 0.146706E+09 0.142811E+09 0.442630E+09 0.252516E+09
April 0.245902E+09 0.101293E+09 0.144609E+09 0.488465E+09 0.130425E+09
May 0.169785E+09 29534783.85 0.140250E+09 0.385828E+09 88380202.39
June 0.139079E+09 10610812.10 0.128468E+09 0.440623E+09 27416019.29
July 0.145630E+09 13846372.09 0.131784E+09 0.444405E+09 18694729.76
August 0.180078E+09 50716328.22 0.129362E+09 0.500140E+09 24793303.23
September 0.247542E+09 0.104624E+09 0.142918E+09 0.562486E+09 38289876.60
October 0.410591E+09 0.284239E+09 0.126352E+09 0.711722E+09 0.169844E+09
November 0.467063E+09 0.358724E+09 0.108339E+09 0.720522E+09 0.250382E+09
December 0.521963E+09 0.413534E+09 0.108429E+09 0.784641E+09 0.341078E+09
           
Annual Sum or Average 0.369352E+10 0.217336E+10 0.152016E+10 0.680394E+10 0.187587E+10
Minimum of Months 0.139079E+09 10610812.10 0.104115E+09 0.385828E+09 18694729.76
Maximum of Months 0.560483E+09 0.447760E+09 0.144609E+09 0.876917E+09 0.341078E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.442566E+09 0.353559E+09 89007348.67 0.691723E+09 0.197778E+09
February 0.249427E+09 0.167216E+09 82211105.16 0.352616E+09 0.172608E+09
March 0.228607E+09 0.115841E+09 0.112766E+09 0.351279E+09 0.174105E+09
April 0.194169E+09 79982898.78 0.114186E+09 0.390680E+09 77258851.40
May 0.134065E+09 23321164.89 0.110744E+09 0.317353E+09 46964268.13
June 0.109819E+09 8378476.71 0.101441E+09 0.366482E+09 11295478.38
July 0.114992E+09 10933329.61 0.104059E+09 0.377481E+09 7506952.97
August 0.142193E+09 40046470.60 0.102146E+09 0.416825E+09 8273272.00
September 0.195463E+09 82612529.72 0.112851E+09 0.461904E+09 13879815.65
October 0.324210E+09 0.224440E+09 99769849.61 0.569758E+09 0.104740E+09
November 0.368801E+09 0.283255E+09 85546508.11 0.570602E+09 0.168834E+09
December 0.412151E+09 0.326533E+09 85617432.54 0.619957E+09 0.244161E+09
           
Annual Sum or Average 0.291646E+10 0.171612E+10 0.120034E+10 0.548666E+10 0.122740E+10
Minimum of Months 0.109819E+09 8378476.71 82211105.16 0.317353E+09 7506952.97
Maximum of Months 0.442566E+09 0.353559E+09 0.114186E+09 0.691723E+09 0.244161E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.340154E+09 0.211926E+09 0.128229E+09 0.497100E+09 0.405054E+09
February 0.248858E+09 0.120775E+09 0.128083E+09 0.295177E+09 0.347458E+09
March 0.364588E+09 0.174372E+09 0.190216E+09 0.514000E+09 0.330727E+09
April 0.540336E+09 0.308393E+09 0.231943E+09 0.964431E+09 0.143407E+09
May 0.560366E+09 0.314023E+09 0.246343E+09 0.108915E+10 87107626.74
June 0.574867E+09 0.338034E+09 0.236833E+09 0.130284E+10 20718226.15
July 0.432114E+09 0.201359E+09 0.230755E+09 0.106045E+10 13856639.96
August 0.413642E+09 0.208000E+09 0.205642E+09 0.991091E+09 15339120.73
September 0.348351E+09 0.146469E+09 0.201882E+09 0.792067E+09 26474668.79
October 0.369811E+09 0.212073E+09 0.157738E+09 0.638776E+09 0.208637E+09
November 0.327596E+09 0.197665E+09 0.129932E+09 0.472714E+09 0.344180E+09
December 0.271608E+09 0.153993E+09 0.117616E+09 0.354714E+09 0.503767E+09
           
Annual Sum or Average 0.479229E+10 0.258708E+10 0.220521E+10 0.897251E+10 0.244673E+10
Minimum of Months 0.248858E+09 0.120775E+09 0.117616E+09 0.295177E+09 13856639.96
Maximum of Months 0.574867E+09 0.338034E+09 0.246343E+09 0.130284E+10 0.503767E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53674072.02 0.00 53674072.02 54549203.70 0.209271E+09
February 55241433.50 0.00 55241433.50 34227566.79 0.183563E+09
March 81295770.76 3216.16 81292554.60 91168037.84 0.177967E+09
April 96350800.51 1418628.78 94932171.74 0.186224E+09 73329947.08
May 0.116786E+09 9916509.70 0.106870E+09 0.268185E+09 41947819.22
June 0.130521E+09 23848337.92 0.106672E+09 0.402327E+09 10132948.37
July 0.115375E+09 12397170.40 0.102978E+09 0.372769E+09 6818664.12
August 92836668.46 2279405.50 90557262.96 0.307202E+09 7817196.67
September 84720382.40 52432.38 84667950.02 0.248323E+09 13746381.15
October 67690153.51 0.00 67690153.51 0.124822E+09 0.109244E+09
November 54578999.93 0.00 54578999.93 53656697.10 0.179347E+09
December 50136496.34 0.00 50136496.34 35052229.69 0.262086E+09
           
Annual Sum or Average 0.999207E+09 49915700.83 0.949291E+09 0.217851E+10 0.127527E+10
Minimum of Months 50136496.34 0.00 50136496.34 34227566.79 6818664.12
Maximum of Months 0.130521E+09 23848337.92 0.106870E+09 0.402327E+09 0.262086E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.340154E+09 0.211926E+09 0.128229E+09 0.521762E+09 0.388076E+09
February 0.248858E+09 0.120775E+09 0.128083E+09 0.309979E+09 0.336230E+09
March 0.364588E+09 0.174372E+09 0.190216E+09 0.527571E+09 0.324206E+09
April 0.540336E+09 0.308393E+09 0.231943E+09 0.971300E+09 0.141133E+09
May 0.560366E+09 0.314023E+09 0.246343E+09 0.109074E+10 86677361.32
June 0.574867E+09 0.338034E+09 0.236833E+09 0.130183E+10 20742949.45
July 0.432114E+09 0.201359E+09 0.230755E+09 0.106078E+10 13856468.25
August 0.413642E+09 0.208000E+09 0.205642E+09 0.994912E+09 15023965.32
September 0.348351E+09 0.146469E+09 0.201882E+09 0.799047E+09 25498446.33
October 0.369811E+09 0.212073E+09 0.157738E+09 0.654782E+09 0.201212E+09
November 0.327596E+09 0.197665E+09 0.129932E+09 0.492099E+09 0.330709E+09
December 0.271608E+09 0.153993E+09 0.117616E+09 0.378978E+09 0.484817E+09
           
Annual Sum or Average 0.479229E+10 0.258708E+10 0.220521E+10 0.910379E+10 0.236818E+10
Minimum of Months 0.248858E+09 0.120775E+09 0.117616E+09 0.309979E+09 13856468.25
Maximum of Months 0.574867E+09 0.338034E+09 0.246343E+09 0.130183E+10 0.484817E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.649066E+09 0.518528E+09 0.130538E+09 0.998035E+09 0.302250E+09
February 0.365808E+09 0.245238E+09 0.120570E+09 0.503781E+09 0.265620E+09
March 0.335275E+09 0.169892E+09 0.165382E+09 0.506592E+09 0.260303E+09
April 0.284767E+09 0.117303E+09 0.167464E+09 0.581477E+09 0.109700E+09
May 0.196619E+09 34202726.45 0.162417E+09 0.481876E+09 64390982.68
June 0.161060E+09 12287840.18 0.148772E+09 0.561837E+09 13751561.98
July 0.168647E+09 16034777.14 0.152612E+09 0.572675E+09 9720758.27
August 0.208539E+09 58731992.40 0.149807E+09 0.626776E+09 10900776.70
September 0.286666E+09 0.121159E+09 0.165506E+09 0.685008E+09 19199784.28
October 0.475485E+09 0.329163E+09 0.146322E+09 0.829847E+09 0.156665E+09
November 0.540882E+09 0.415420E+09 0.125462E+09 0.824347E+09 0.256810E+09
December 0.604458E+09 0.478892E+09 0.125566E+09 0.888523E+09 0.375968E+09
           
Annual Sum or Average 0.427727E+10 0.251685E+10 0.176042E+10 0.806077E+10 0.184528E+10
Minimum of Months 0.161060E+09 12287840.18 0.120570E+09 0.481876E+09 9720758.27
Maximum of Months 0.649066E+09 0.518528E+09 0.167464E+09 0.998035E+09 0.375968E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.375704E+09 0.00 0.375704E+09 0.303179E+09 0.181364E+10
February 0.386675E+09 0.00 0.386675E+09 0.172561E+09 0.164507E+10
March 0.569049E+09 22512.27 0.569026E+09 0.544617E+09 0.157192E+10
April 0.674430E+09 9930025.34 0.664500E+09 0.124197E+10 0.725405E+09
May 0.817473E+09 69412938.91 0.748060E+09 0.176914E+10 0.456628E+09
June 0.913609E+09 0.166932E+09 0.746677E+09 0.266349E+10 0.149079E+09
July 0.807597E+09 86776906.14 0.720820E+09 0.239449E+10 0.111296E+09
August 0.649832E+09 15955234.21 0.633877E+09 0.197186E+10 0.153600E+09
September 0.593020E+09 367012.78 0.592653E+09 0.159299E+10 0.241582E+09
October 0.473813E+09 0.00 0.473813E+09 0.789627E+09 0.103701E+10
November 0.382039E+09 0.00 0.382039E+09 0.304130E+09 0.158879E+10
December 0.350942E+09 0.00 0.350942E+09 0.168571E+09 0.221379E+10
           
Annual Sum or Average 0.699418E+10 0.349397E+09 0.664479E+10 0.139166E+11 0.117078E+11
Minimum of Months 0.350942E+09 0.00 0.350942E+09 0.168571E+09 0.111296E+09
Maximum of Months 0.913609E+09 0.166932E+09 0.748060E+09 0.266349E+10 0.221379E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.375704E+09 0.00 0.375704E+09 0.276913E+09 0.188281E+10
February 0.386675E+09 0.00 0.386675E+09 0.152179E+09 0.172649E+10
March 0.569049E+09 22512.27 0.569026E+09 0.507919E+09 0.163647E+10
April 0.674430E+09 9930025.34 0.664500E+09 0.119995E+10 0.753678E+09
May 0.817473E+09 69412938.91 0.748060E+09 0.172028E+10 0.474286E+09
June 0.913609E+09 0.166932E+09 0.746677E+09 0.261152E+10 0.157191E+09
July 0.807597E+09 86776906.14 0.720820E+09 0.234018E+10 0.119648E+09
August 0.649832E+09 15955234.21 0.633877E+09 0.192099E+10 0.165858E+09
September 0.593020E+09 367012.78 0.592653E+09 0.154759E+10 0.257929E+09
October 0.473813E+09 0.00 0.473813E+09 0.754872E+09 0.107972E+10
November 0.382039E+09 0.00 0.382039E+09 0.279348E+09 0.165385E+10
December 0.350942E+09 0.00 0.350942E+09 0.147627E+09 0.230279E+10
           
Annual Sum or Average 0.699418E+10 0.349397E+09 0.664479E+10 0.134594E+11 0.122107E+11
Minimum of Months 0.350942E+09 0.00 0.350942E+09 0.147627E+09 0.119648E+09
Maximum of Months 0.913609E+09 0.166932E+09 0.748060E+09 0.261152E+10 0.230279E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53674072.02 0.00 53674072.02 47685500.87 0.271814E+09
February 55241433.50 0.00 55241433.50 26138134.98 0.249904E+09
March 81295770.76 3216.16 81292554.60 83507338.53 0.239140E+09
April 96350800.51 1418628.78 94932171.74 0.194328E+09 0.112952E+09
May 0.116786E+09 9916509.70 0.106870E+09 0.277257E+09 76632286.22
June 0.130521E+09 23848337.92 0.106672E+09 0.406742E+09 29874853.75
July 0.115375E+09 12397170.40 0.102978E+09 0.367554E+09 23705505.54
August 92836668.46 2279405.50 90557262.96 0.307815E+09 31020455.90
September 84720382.40 52432.38 84667950.02 0.251008E+09 43675469.89
October 67690153.51 0.00 67690153.51 0.124162E+09 0.158763E+09
November 54578999.93 0.00 54578999.93 48007473.91 0.238389E+09
December 50136496.34 0.00 50136496.34 27272461.54 0.329298E+09
           
Annual Sum or Average 0.999207E+09 49915700.83 0.949291E+09 0.216148E+10 0.180517E+10
Minimum of Months 50136496.34 0.00 50136496.34 26138134.98 23705505.54
Maximum of Months 0.130521E+09 23848337.92 0.106870E+09 0.406742E+09 0.329298E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.647832E+09 0.406608E+09 0.241223E+09 0.880853E+09 0.922432E+09
February 0.581660E+09 0.334662E+09 0.246998E+09 0.683493E+09 0.857740E+09
March 0.799654E+09 0.411405E+09 0.388250E+09 0.109559E+10 0.816045E+09
April 0.110278E+10 0.657056E+09 0.445720E+09 0.200773E+10 0.399485E+09
May 0.118295E+10 0.701920E+09 0.481032E+09 0.232835E+10 0.283728E+09
June 0.119111E+10 0.739991E+09 0.451119E+09 0.272222E+10 0.111873E+09
July 0.104108E+10 0.587423E+09 0.453658E+09 0.243274E+10 88308093.70
August 0.988937E+09 0.565014E+09 0.423923E+09 0.228118E+10 0.116170E+09
September 0.784240E+09 0.378243E+09 0.405997E+09 0.176006E+10 0.160100E+09
October 0.813243E+09 0.494683E+09 0.318561E+09 0.140926E+10 0.546852E+09
November 0.605626E+09 0.363437E+09 0.242189E+09 0.815624E+09 0.817762E+09
December 0.571644E+09 0.345721E+09 0.225923E+09 0.676545E+09 0.111306E+10
           
Annual Sum or Average 0.103108E+11 0.598616E+10 0.432459E+10 0.190936E+11 0.623356E+10
Minimum of Months 0.571644E+09 0.334662E+09 0.225923E+09 0.676545E+09 88308093.70
Maximum of Months 0.119111E+10 0.739991E+09 0.481032E+09 0.272222E+10 0.111306E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.442566E+09 0.353559E+09 89007348.67 0.701892E+09 0.245588E+09
February 0.249427E+09 0.167216E+09 82211105.16 0.351879E+09 0.226307E+09
March 0.228607E+09 0.115841E+09 0.112766E+09 0.351764E+09 0.228654E+09
April 0.194169E+09 79982898.78 0.114186E+09 0.403978E+09 0.115933E+09
May 0.134065E+09 23321164.89 0.110744E+09 0.328022E+09 82969643.85
June 0.109819E+09 8378476.71 0.101441E+09 0.369737E+09 31972005.61
July 0.114992E+09 10933329.61 0.104059E+09 0.372877E+09 24809066.13
August 0.142193E+09 40046470.60 0.102146E+09 0.420488E+09 31614811.35
September 0.195463E+09 82612529.72 0.112851E+09 0.469633E+09 43565979.54
October 0.324210E+09 0.224440E+09 99769849.61 0.580501E+09 0.147266E+09
November 0.368801E+09 0.283255E+09 85546508.11 0.578603E+09 0.215881E+09
December 0.412151E+09 0.326533E+09 85617432.54 0.625424E+09 0.292833E+09
           
Annual Sum or Average 0.291646E+10 0.171612E+10 0.120034E+10 0.555480E+10 0.168739E+10
Minimum of Months 0.109819E+09 8378476.71 82211105.16 0.328022E+09 24809066.13
Maximum of Months 0.442566E+09 0.353559E+09 0.114186E+09 0.701892E+09 0.292833E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 67974825.56 0.00 67974825.56 46150432.76 0.326079E+09
February 69959789.98 0.00 69959789.98 29572350.51 0.283811E+09
March 0.102956E+09 4073.06 0.102952E+09 94233347.35 0.273853E+09
April 0.122022E+09 1796603.83 0.120226E+09 0.212612E+09 0.131007E+09
May 0.147902E+09 12558633.84 0.135344E+09 0.309408E+09 81680407.87
June 0.165296E+09 30202415.22 0.135094E+09 0.474465E+09 25604475.97
July 0.146116E+09 15700234.09 0.130415E+09 0.424908E+09 18904752.30
August 0.117572E+09 2886723.24 0.114685E+09 0.345854E+09 26460204.73
September 0.107293E+09 66402.30 0.107227E+09 0.276067E+09 42633436.62
October 85725308.41 0.00 85725308.41 0.130519E+09 0.188773E+09
November 69120859.66 0.00 69120859.66 47242289.51 0.286566E+09
December 63494709.17 0.00 63494709.17 26791744.57 0.389587E+09
           
Annual Sum or Average 0.126543E+10 63215085.59 0.120222E+10 0.241782E+10 0.207496E+10
Minimum of Months 63494709.17 0.00 63494709.17 26791744.57 18904752.30
Maximum of Months 0.165296E+09 30202415.22 0.135344E+09 0.474465E+09 0.389587E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 60817333.99 0.00 60817333.99 41290967.06 0.291713E+09
February 62593289.17 0.00 62593289.17 26458494.05 0.253927E+09
March 92115091.26 3644.19 92111447.08 84310932.92 0.245018E+09
April 0.109174E+09 1607428.26 0.107566E+09 0.190225E+09 0.117213E+09
May 0.132329E+09 11236257.28 0.121093E+09 0.276828E+09 73079770.41
June 0.147891E+09 27022215.34 0.120869E+09 0.424505E+09 22908421.67
July 0.130730E+09 14047058.93 0.116683E+09 0.380167E+09 16914153.51
August 0.105192E+09 2582762.23 0.102609E+09 0.309437E+09 23674045.43
September 95995470.41 59410.39 95936060.02 0.246998E+09 38144297.28
October 76698758.25 0.00 76698758.25 0.116776E+09 0.168898E+09
November 61842695.04 0.00 61842695.04 42267855.42 0.256383E+09
December 56808956.88 0.00 56808956.88 23970675.38 0.348521E+09
           
Annual Sum or Average 0.113219E+10 56558776.60 0.107563E+10 0.216324E+10 0.185639E+10
Minimum of Months 56808956.88 0.00 56808956.88 23970675.38 16914153.51
Maximum of Months 0.147891E+09 27022215.34 0.121093E+09 0.424505E+09 0.348521E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.165223E+10 0.131994E+10 0.332291E+09 0.254104E+10 0.859354E+09
February 0.931184E+09 0.624266E+09 0.306919E+09 0.128340E+10 0.753842E+09
March 0.853459E+09 0.432470E+09 0.420989E+09 0.126224E+10 0.771744E+09
April 0.724889E+09 0.298600E+09 0.426289E+09 0.140138E+10 0.398057E+09
May 0.500505E+09 87064857.88 0.413440E+09 0.110803E+10 0.269994E+09
June 0.409987E+09 31279350.23 0.378708E+09 0.126789E+10 86512367.18
July 0.429299E+09 40817377.39 0.388482E+09 0.127220E+10 61180363.55
August 0.530848E+09 0.149505E+09 0.381343E+09 0.143706E+10 82001306.81
September 0.729722E+09 0.308417E+09 0.421305E+09 0.162105E+10 0.124120E+09
October 0.121037E+10 0.837901E+09 0.372471E+09 0.206010E+10 0.511246E+09
November 0.137684E+10 0.105747E+10 0.319371E+09 0.208479E+10 0.755315E+09
December 0.153868E+10 0.121905E+10 0.319635E+09 0.228260E+10 0.101319E+10
           
Annual Sum or Average 0.108880E+11 0.640678E+10 0.448124E+10 0.196218E+11 0.568656E+10
Minimum of Months 0.409987E+09 31279350.23 0.306919E+09 0.110803E+10 61180363.55
Maximum of Months 0.165223E+10 0.131994E+10 0.426289E+09 0.254104E+10 0.101319E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1276.01 426.31 835.71 667.64 168.07 0.00 0.00
February 718.49 395.83 521.47 349.59 171.87 0.00 0.00
March 643.10 364.13 431.69 218.75 212.94 0.00 0.00
April 719.38 210.12 378.88 156.07 222.81 0.00 0.00
May 533.08 143.32 253.16 44.04 209.12 0.00 0.00
June 609.65 53.83 214.28 16.35 197.94 0.00 0.00
July 600.49 36.59 217.14 20.65 196.50 0.00 0.00
August 690.12 49.17 268.51 75.62 192.88 0.00 0.00
September 821.64 74.33 381.40 161.20 220.20 0.00 0.00
October 1034.49 257.77 612.22 423.82 188.40 0.00 0.00
November 1086.76 382.77 719.63 552.71 166.92 0.00 0.00
December 1138.32 499.39 778.28 616.61 161.67 0.00 0.00
               
Annual Sum or Average 823.63 240.53 467.74 275.23 192.51 0.00 0.00
Minimum of Months 533.08 36.59 214.28 16.35 161.67 0.00 0.00
Maximum of Months 1276.01 499.39 835.71 667.64 222.81 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3585.48 1203.61 2353.32 1880.03 473.29 0.00 0.00
February 2025.34 1139.06 1468.41 984.43 483.99 0.00 0.00
March 1832.76 1026.40 1215.60 615.98 599.62 0.00 0.00
April 2061.23 568.43 1066.89 439.48 627.41 0.00 0.00
May 1562.17 379.49 712.87 124.01 588.87 0.00 0.00
June 1770.51 140.92 603.41 46.04 557.38 0.00 0.00
July 1742.21 95.42 611.46 58.14 553.32 0.00 0.00
August 1979.59 129.26 756.09 212.94 543.15 0.00 0.00
September 2339.01 200.25 1074.00 453.93 620.07 0.00 0.00
October 2921.62 717.07 1723.96 1193.45 530.51 0.00 0.00
November 3059.54 1074.73 2026.44 1556.40 470.05 0.00 0.00
December 3195.22 1426.96 2191.58 1736.32 455.26 0.00 0.00
               
Annual Sum or Average 2342.49 673.28 1317.12 775.03 542.09 0.00 0.00
Minimum of Months 1562.17 95.42 603.41 46.04 455.26 0.00 0.00
Maximum of Months 3585.48 1426.96 2353.32 1880.03 627.41 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 4751.38 1620.60 3057.09 2442.27 614.83 0.00 0.00
February 2671.17 1588.07 1907.55 1278.83 628.73 0.00 0.00
March 2402.49 1433.41 1579.13 800.19 778.94 0.00 0.00
April 2724.71 776.76 1385.95 570.91 815.04 0.00 0.00
May 2043.78 522.50 926.06 161.09 764.97 0.00 0.00
June 2338.83 187.51 783.87 59.80 724.06 0.00 0.00
July 2299.19 127.86 794.32 75.52 718.79 0.00 0.00
August 2625.78 171.08 982.21 276.63 705.58 0.00 0.00
September 3102.36 261.25 1395.19 589.68 805.51 0.00 0.00
October 3869.43 967.52 2239.52 1550.35 689.17 0.00 0.00
November 4046.92 1463.18 2632.46 2021.85 610.62 0.00 0.00
December 4229.41 1937.91 2846.99 2255.58 591.41 0.00 0.00
               
Annual Sum or Average 3096.01 918.72 1711.02 1006.81 704.21 0.00 0.00
Minimum of Months 2043.78 127.86 783.87 59.80 591.41 0.00 0.00
Maximum of Months 4751.38 1937.91 3057.09 2442.27 815.04 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 437.15 221.29 292.23 211.13 81.11 0.00 0.00
February 262.81 213.69 205.97 119.04 86.93 0.00 0.00
March 322.36 189.60 221.47 108.35 113.12 0.00 0.00
April 525.77 88.17 283.37 149.84 133.54 0.00 0.00
May 526.58 52.78 259.27 125.95 133.32 0.00 0.00
June 645.06 13.53 264.15 133.65 130.51 0.00 0.00
July 537.31 8.51 204.27 79.26 125.00 0.00 0.00
August 526.25 9.62 207.52 92.61 114.91 0.00 0.00
September 484.65 17.06 209.80 88.38 121.42 0.00 0.00
October 450.06 118.46 259.12 162.98 96.14 0.00 0.00
November 397.07 195.41 268.67 185.54 83.13 0.00 0.00
December 353.05 272.91 255.29 179.41 75.88 0.00 0.00
               
Annual Sum or Average 456.63 116.37 244.44 136.45 107.99 0.00 0.00
Minimum of Months 262.81 8.51 204.27 79.26 75.88 0.00 0.00
Maximum of Months 645.06 272.91 292.23 211.13 133.54 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 213.08 229.06 147.04 79.12 67.91 0.00 0.00
February 140.38 219.46 125.70 49.92 75.78 0.00 0.00
March 229.43 190.07 166.47 65.10 101.37 0.00 0.00
April 448.51 85.83 245.64 119.53 126.11 0.00 0.00
May 507.17 49.15 252.82 120.95 131.87 0.00 0.00
June 658.06 12.23 272.14 139.62 132.53 0.00 0.00
July 535.48 7.93 204.41 79.81 124.60 0.00 0.00
August 486.29 9.16 189.10 78.51 110.59 0.00 0.00
September 403.99 16.58 167.08 56.53 110.55 0.00 0.00
October 289.97 120.47 163.34 79.18 84.17 0.00 0.00
November 208.60 202.13 147.44 76.26 71.18 0.00 0.00
December 151.75 284.55 120.13 57.49 62.63 0.00 0.00
               
Annual Sum or Average 357.02 118.49 183.65 83.62 100.03 0.00 0.00
Minimum of Months 140.38 7.93 120.13 49.92 62.63 0.00 0.00
Maximum of Months 658.06 284.55 272.14 139.62 132.53 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 202.79 69.91 132.16 105.58 26.58 0.00 0.00
February 113.08 67.07 82.47 55.29 27.18 0.00 0.00
March 101.81 60.12 68.27 34.59 33.67 0.00 0.00
April 119.23 30.38 59.92 24.68 35.24 0.00 0.00
May 92.76 19.10 40.04 6.96 33.07 0.00 0.00
June 110.05 5.83 33.89 2.59 31.30 0.00 0.00
July 107.55 3.76 34.34 3.26 31.07 0.00 0.00
August 120.00 4.97 42.46 11.96 30.50 0.00 0.00
September 138.40 8.24 60.32 25.49 34.82 0.00 0.00
October 167.00 39.41 96.82 67.02 29.79 0.00 0.00
November 172.76 62.18 113.80 87.41 26.40 0.00 0.00
December 180.41 84.39 123.08 97.51 25.57 0.00 0.00
               
Annual Sum or Average 135.68 37.83 73.97 43.53 30.44 0.00 0.00
Minimum of Months 92.76 3.76 33.89 2.59 25.57 0.00 0.00
Maximum of Months 202.79 84.39 132.16 105.58 35.24 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 17.30 63.48 16.03 0.00 16.03 0.00 0.00
February 11.54 63.32 18.27 0.00 18.27 0.00 0.00
March 28.80 53.69 24.29 0.00 24.28 0.00 0.00
April 63.31 21.41 29.74 0.44 29.30 0.00 0.00
May 86.42 11.48 34.89 2.96 31.92 0.00 0.00
June 132.37 2.47 40.29 7.36 32.93 0.00 0.00
July 118.67 1.69 34.47 3.70 30.76 0.00 0.00
August 98.81 1.88 27.73 0.68 27.05 0.00 0.00
September 82.61 3.61 26.15 0.02 26.14 0.00 0.00
October 40.63 32.34 20.22 0.00 20.22 0.00 0.00
November 17.91 55.84 16.85 0.00 16.85 0.00 0.00
December 10.42 80.91 14.98 0.00 14.98 0.00 0.00
               
Annual Sum or Average 59.29 32.55 25.35 1.27 24.08 0.00 0.00
Minimum of Months 10.42 1.69 14.98 0.00 14.98 0.00 0.00
Maximum of Months 132.37 80.91 40.29 7.36 32.93 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 416.65 212.93 286.18 207.91 78.27 0.00 0.00
February 283.21 207.95 223.33 138.29 85.04 0.00 0.00
March 330.08 178.84 234.64 120.06 114.59 0.00 0.00
April 524.50 78.82 287.65 157.61 130.04 0.00 0.00
May 541.08 46.08 270.90 139.75 131.15 0.00 0.00
June 661.37 11.73 272.15 145.99 126.16 0.00 0.00
July 594.73 7.56 237.29 113.75 123.55 0.00 0.00
August 576.79 9.19 237.72 120.44 117.28 0.00 0.00
September 511.59 16.02 226.70 104.84 121.86 0.00 0.00
October 466.88 113.37 272.87 176.15 96.72 0.00 0.00
November 372.34 188.63 259.12 179.39 79.73 0.00 0.00
December 351.59 264.53 260.60 186.46 74.14 0.00 0.00
               
Annual Sum or Average 470.24 110.92 255.97 149.33 106.63 0.00 0.00
Minimum of Months 283.21 7.56 223.33 104.84 74.14 0.00 0.00
Maximum of Months 661.37 264.53 287.65 207.91 131.15 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 179.45 207.24 140.98 75.91 65.07 0.00 0.00
February 152.22 205.20 143.06 69.17 73.89 0.00 0.00
March 233.90 176.57 179.64 76.81 102.83 0.00 0.00
April 447.67 77.58 249.91 127.30 122.61 0.00 0.00
May 524.87 45.74 264.45 134.75 129.71 0.00 0.00
June 675.72 11.69 280.14 151.96 128.18 0.00 0.00
July 593.48 7.53 237.44 114.30 123.14 0.00 0.00
August 536.97 8.99 219.29 106.33 112.95 0.00 0.00
September 430.65 15.54 183.98 72.99 110.99 0.00 0.00
October 301.11 110.79 177.10 92.35 84.75 0.00 0.00
November 173.51 184.47 137.89 70.11 67.78 0.00 0.00
December 133.98 259.20 125.44 64.54 60.90 0.00 0.00
               
Annual Sum or Average 366.32 108.83 195.17 96.50 98.67 0.00 0.00
Minimum of Months 133.98 7.53 125.44 64.54 60.90 0.00 0.00
Maximum of Months 675.72 259.20 280.14 151.96 129.71 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 463.08 296.65 321.09 228.77 92.33 0.00 0.00
February 262.47 287.78 218.26 119.79 98.47 0.00 0.00
March 277.30 262.24 200.53 74.96 125.57 0.00 0.00
April 375.39 135.48 194.25 54.43 139.83 0.00 0.00
May 358.12 83.27 162.32 21.51 140.82 0.00 0.00
June 487.78 25.60 160.71 21.55 139.16 0.00 0.00
July 450.27 17.63 149.07 15.10 133.97 0.00 0.00
August 438.01 24.35 152.08 27.39 124.70 0.00 0.00
September 447.99 40.56 187.34 55.27 132.07 0.00 0.00
October 429.83 177.11 253.58 145.22 108.36 0.00 0.00
November 397.79 269.12 283.08 189.39 93.69 0.00 0.00
December 400.11 355.28 299.12 211.28 87.84 0.00 0.00
               
Annual Sum or Average 399.82 164.09 215.19 97.05 118.14 0.00 0.00
Minimum of Months 262.47 17.63 149.07 15.10 87.84 0.00 0.00
Maximum of Months 487.78 355.28 321.09 228.77 140.82 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 435.96 217.17 292.23 211.13 81.11 0.00 0.00
February 261.92 209.12 205.97 119.04 86.93 0.00 0.00
March 320.82 186.25 221.47 108.35 113.12 0.00 0.00
April 522.61 84.94 283.37 149.84 133.54 0.00 0.00
May 525.13 50.05 259.27 125.95 133.32 0.00 0.00
June 644.03 12.35 264.15 133.65 130.51 0.00 0.00
July 536.86 7.98 204.27 79.26 125.00 0.00 0.00
August 525.64 8.81 207.52 92.61 114.91 0.00 0.00
September 483.77 15.55 209.80 88.38 121.42 0.00 0.00
October 448.70 114.49 259.12 162.98 96.14 0.00 0.00
November 395.76 191.17 268.67 185.54 83.13 0.00 0.00
December 353.10 268.44 255.29 179.41 75.88 0.00 0.00
               
Annual Sum or Average 455.48 113.49 244.44 136.45 107.99 0.00 0.00
Minimum of Months 261.92 7.98 204.27 79.26 75.88 0.00 0.00
Maximum of Months 644.03 268.44 292.23 211.13 133.54 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 214.54 222.39 147.04 79.12 67.91 0.00 0.00
February 140.82 213.40 125.70 49.92 75.78 0.00 0.00
March 229.43 185.91 166.47 65.10 101.37 0.00 0.00
April 446.42 82.59 245.64 119.53 126.11 0.00 0.00
May 506.03 46.69 252.82 120.95 131.87 0.00 0.00
June 656.82 11.26 272.14 139.62 132.53 0.00 0.00
July 534.98 7.47 204.41 79.81 124.60 0.00 0.00
August 486.05 8.42 189.10 78.51 110.59 0.00 0.00
September 404.07 15.14 167.08 56.53 110.55 0.00 0.00
October 290.66 115.50 163.34 79.18 84.17 0.00 0.00
November 209.66 195.89 147.44 76.26 71.18 0.00 0.00
December 153.49 277.77 120.13 57.49 62.63 0.00 0.00
               
Annual Sum or Average 357.05 114.82 183.65 83.62 100.03 0.00 0.00
Minimum of Months 140.82 7.47 120.13 49.92 62.63 0.00 0.00
Maximum of Months 656.82 277.77 272.14 139.62 132.53 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 372.62 112.85 242.33 193.60 48.74 0.00 0.00
February 208.24 109.80 151.21 101.37 49.84 0.00 0.00
March 189.14 97.19 125.18 63.43 61.75 0.00 0.00
April 224.34 42.32 109.86 45.26 64.61 0.00 0.00
May 179.91 24.04 73.41 12.77 60.64 0.00 0.00
June 216.76 5.31 62.14 4.74 57.40 0.00 0.00
July 213.81 3.63 62.97 5.99 56.98 0.00 0.00
August 234.01 4.07 77.86 21.93 55.93 0.00 0.00
September 264.28 7.41 110.60 46.74 63.85 0.00 0.00
October 309.83 58.49 177.53 122.90 54.63 0.00 0.00
November 318.04 99.08 208.67 160.27 48.40 0.00 0.00
December 331.74 140.37 225.68 178.80 46.88 0.00 0.00
               
Annual Sum or Average 255.61 58.51 135.63 79.81 55.82 0.00 0.00
Minimum of Months 179.91 3.63 62.14 4.74 46.88 0.00 0.00
Maximum of Months 372.62 140.37 242.33 193.60 64.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 113.19 677.14 140.27 0.00 140.27 0.00 0.00
February 71.33 680.00 159.84 0.00 159.84 0.00 0.00
March 203.34 586.89 212.46 0.01 212.45 0.00 0.00
April 479.16 279.86 260.20 3.83 256.37 0.00 0.00
May 660.52 170.49 305.21 25.92 279.29 0.00 0.00
June 1027.58 57.52 352.47 64.40 288.07 0.00 0.00
July 894.00 41.55 301.52 32.40 269.12 0.00 0.00
August 736.21 57.35 242.62 5.96 236.66 0.00 0.00
September 614.58 93.20 228.79 0.14 228.65 0.00 0.00
October 294.81 387.18 176.90 0.00 176.90 0.00 0.00
November 117.33 612.96 147.39 0.00 147.39 0.00 0.00
December 62.94 826.54 131.03 0.00 131.03 0.00 0.00
               
Annual Sum or Average 441.29 371.25 221.78 11.08 210.70 0.00 0.00
Minimum of Months 62.94 41.55 131.03 0.00 131.03 0.00 0.00
Maximum of Months 1027.58 826.54 352.47 64.40 288.07 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 103.39 702.96 140.27 0.00 140.27 0.00 0.00
February 62.90 713.66 159.84 0.00 159.84 0.00 0.00
March 189.64 610.99 212.46 0.01 212.45 0.00 0.00
April 462.94 290.77 260.20 3.83 256.37 0.00 0.00
May 642.28 177.08 305.21 25.92 279.29 0.00 0.00
June 1007.53 60.64 352.47 64.40 288.07 0.00 0.00
July 873.72 44.67 301.52 32.40 269.12 0.00 0.00
August 717.22 61.92 242.62 5.96 236.66 0.00 0.00
September 597.06 99.51 228.79 0.14 228.65 0.00 0.00
October 281.84 403.12 176.90 0.00 176.90 0.00 0.00
November 107.77 638.06 147.39 0.00 147.39 0.00 0.00
December 55.12 859.76 131.03 0.00 131.03 0.00 0.00
               
Annual Sum or Average 426.79 387.20 221.78 11.08 210.70 0.00 0.00
Minimum of Months 55.12 44.67 131.03 0.00 131.03 0.00 0.00
Maximum of Months 1007.53 859.76 352.47 64.40 288.07 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 596.88 525.72 427.15 283.81 143.33 0.00 0.00
February 425.69 538.31 366.37 207.46 158.92 0.00 0.00
March 560.56 468.34 414.26 196.85 217.41 0.00 0.00
April 999.21 236.22 537.54 284.90 252.64 0.00 0.00
May 1092.33 162.56 535.32 274.48 260.84 0.00 0.00
June 1349.01 66.22 552.26 297.92 254.33 0.00 0.00
July 1184.23 50.59 474.70 228.03 246.68 0.00 0.00
August 1123.31 66.45 456.98 226.75 230.22 0.00 0.00
September 956.30 94.66 410.66 177.82 232.84 0.00 0.00
October 783.16 312.34 449.95 268.49 181.46 0.00 0.00
November 544.57 478.90 396.99 249.50 147.50 0.00 0.00
December 478.43 629.99 386.03 250.99 135.03 0.00 0.00
               
Annual Sum or Average 843.23 301.50 451.12 245.82 205.30 0.00 0.00
Minimum of Months 425.69 50.59 366.37 177.82 135.03 0.00 0.00
Maximum of Months 1349.01 629.99 552.26 297.92 260.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 962.77 532.91 664.96 492.81 172.15 0.00 0.00
February 538.95 519.17 439.71 258.05 181.66 0.00 0.00
March 534.37 478.30 391.48 161.47 230.01 0.00 0.00
April 695.78 249.05 368.86 116.51 252.35 0.00 0.00
May 628.97 154.99 291.49 41.39 250.10 0.00 0.00
June 833.14 49.25 279.00 34.15 244.86 0.00 0.00
July 774.43 35.08 263.64 26.35 237.30 0.00 0.00
August 780.61 48.75 281.37 57.86 223.51 0.00 0.00
September 827.12 78.97 359.96 119.04 240.92 0.00 0.00
October 854.99 317.92 512.54 312.84 199.71 0.00 0.00
November 821.85 483.87 581.72 407.98 173.74 0.00 0.00
December 846.03 628.71 619.39 455.14 164.25 0.00 0.00
               
Annual Sum or Average 759.66 297.17 421.29 206.96 214.33 0.00 0.00
Minimum of Months 534.37 35.08 263.64 26.35 164.25 0.00 0.00
Maximum of Months 962.77 628.71 664.96 492.81 252.35 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.341766E+10 0.114183E+10 0.223838E+10 0.178821E+10 0.450171E+09 0.00 0.00
February 0.173817E+10 0.957597E+09 0.126153E+10 0.845731E+09 0.415798E+09 0.00 0.00
March 0.172247E+10 0.975281E+09 0.115623E+10 0.585894E+09 0.570335E+09 0.00 0.00
April 0.186463E+10 0.544638E+09 0.982044E+09 0.404532E+09 0.577512E+09 0.00 0.00
May 0.142779E+10 0.383879E+09 0.678057E+09 0.117952E+09 0.560105E+09 0.00 0.00
June 0.158022E+10 0.139526E+09 0.555427E+09 42376069.35 0.513050E+09 0.00 0.00
July 0.160834E+10 97997643.97 0.581591E+09 55297824.35 0.526293E+09 0.00 0.00
August 0.184841E+10 0.131700E+09 0.719166E+09 0.202544E+09 0.516622E+09 0.00 0.00
September 0.212968E+10 0.192662E+09 0.988595E+09 0.417832E+09 0.570763E+09 0.00 0.00
October 0.277078E+10 0.690407E+09 0.163976E+10 0.113516E+10 0.504604E+09 0.00 0.00
November 0.281688E+10 0.992144E+09 0.186529E+10 0.143263E+10 0.432667E+09 0.00 0.00
December 0.304886E+10 0.133758E+10 0.208454E+10 0.165152E+10 0.433026E+09 0.00 0.00
               
Annual Sum or Average 0.259739E+11 0.758524E+10 0.147506E+11 0.867966E+10 0.607095E+10 0.00 0.00
Minimum of Months 0.142779E+10 97997643.97 0.555427E+09 42376069.35 0.415798E+09 0.00 0.00
Maximum of Months 0.341766E+10 0.133758E+10 0.223838E+10 0.178821E+10 0.577512E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.960335E+10 0.322375E+10 0.630312E+10 0.503547E+10 0.126765E+10 0.00 0.00
February 0.489970E+10 0.275562E+10 0.355238E+10 0.238152E+10 0.117086E+10 0.00 0.00
March 0.490886E+10 0.274910E+10 0.325586E+10 0.164984E+10 0.160603E+10 0.00 0.00
April 0.534270E+10 0.147338E+10 0.276537E+10 0.113914E+10 0.162624E+10 0.00 0.00
May 0.418411E+10 0.101643E+10 0.190936E+10 0.332145E+09 0.157722E+10 0.00 0.00
June 0.458917E+10 0.365274E+09 0.156404E+10 0.119328E+09 0.144472E+10 0.00 0.00
July 0.466634E+10 0.255564E+09 0.163772E+10 0.155715E+09 0.148201E+10 0.00 0.00
August 0.530214E+10 0.346201E+09 0.202512E+10 0.570351E+09 0.145477E+10 0.00 0.00
September 0.606271E+10 0.519043E+09 0.278382E+10 0.117659E+10 0.160723E+10 0.00 0.00
October 0.782526E+10 0.192060E+10 0.461746E+10 0.319653E+10 0.142093E+10 0.00 0.00
November 0.793033E+10 0.278569E+10 0.525254E+10 0.403418E+10 0.121836E+10 0.00 0.00
December 0.855807E+10 0.382197E+10 0.586993E+10 0.465056E+10 0.121937E+10 0.00 0.00
               
Annual Sum or Average 0.738728E+11 0.212326E+11 0.415367E+11 0.244414E+11 0.170954E+11 0.00 0.00
Minimum of Months 0.418411E+10 0.255564E+09 0.156404E+10 0.119328E+09 0.117086E+10 0.00 0.00
Maximum of Months 0.960335E+10 0.382197E+10 0.630312E+10 0.503547E+10 0.162624E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.127261E+11 0.434062E+10 0.818812E+10 0.654136E+10 0.164675E+10 0.00 0.00
February 0.646210E+10 0.384186E+10 0.461475E+10 0.309374E+10 0.152101E+10 0.00 0.00
March 0.643483E+10 0.383924E+10 0.422955E+10 0.214323E+10 0.208632E+10 0.00 0.00
April 0.706244E+10 0.201336E+10 0.359238E+10 0.147980E+10 0.211257E+10 0.00 0.00
May 0.547407E+10 0.139946E+10 0.248037E+10 0.431476E+09 0.204890E+10 0.00 0.00
June 0.606224E+10 0.486018E+09 0.203178E+10 0.155014E+09 0.187677E+10 0.00 0.00
July 0.615815E+10 0.342447E+09 0.212749E+10 0.202283E+09 0.192521E+10 0.00 0.00
August 0.703290E+10 0.458220E+09 0.263075E+10 0.740919E+09 0.188983E+10 0.00 0.00
September 0.804133E+10 0.677155E+09 0.361634E+10 0.152845E+10 0.208788E+10 0.00 0.00
October 0.103639E+11 0.259141E+10 0.599834E+10 0.415247E+10 0.184587E+10 0.00 0.00
November 0.104896E+11 0.379255E+10 0.682335E+10 0.524063E+10 0.158272E+10 0.00 0.00
December 0.113280E+11 0.519051E+10 0.762538E+10 0.604134E+10 0.158404E+10 0.00 0.00
               
Annual Sum or Average 0.976357E+11 0.289729E+11 0.539586E+11 0.317507E+11 0.222079E+11 0.00 0.00
Minimum of Months 0.547407E+10 0.342447E+09 0.203178E+10 0.155014E+09 0.152101E+10 0.00 0.00
Maximum of Months 0.127261E+11 0.519051E+10 0.818812E+10 0.654136E+10 0.211257E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.117085E+10 0.592694E+09 0.782721E+09 0.565485E+09 0.217236E+09 0.00 0.00
February 0.635784E+09 0.516963E+09 0.498285E+09 0.287991E+09 0.210294E+09 0.00 0.00
March 0.863402E+09 0.507817E+09 0.593196E+09 0.290214E+09 0.302982E+09 0.00 0.00
April 0.136281E+10 0.228544E+09 0.734505E+09 0.388376E+09 0.346129E+09 0.00 0.00
May 0.141038E+10 0.141358E+09 0.694431E+09 0.337345E+09 0.357087E+09 0.00 0.00
June 0.167199E+10 35070086.76 0.684686E+09 0.346412E+09 0.338274E+09 0.00 0.00
July 0.143913E+10 22793010.63 0.547106E+09 0.212292E+09 0.334813E+09 0.00 0.00
August 0.140950E+10 25772735.59 0.555835E+09 0.248047E+09 0.307788E+09 0.00 0.00
September 0.125621E+10 44207256.70 0.543814E+09 0.229081E+09 0.314733E+09 0.00 0.00
October 0.120544E+10 0.317283E+09 0.694021E+09 0.436513E+09 0.257508E+09 0.00 0.00
November 0.102921E+10 0.506499E+09 0.696397E+09 0.480919E+09 0.215478E+09 0.00 0.00
December 0.945601E+09 0.730957E+09 0.683759E+09 0.480526E+09 0.203233E+09 0.00 0.00
               
Annual Sum or Average 0.144003E+11 0.366996E+10 0.770875E+10 0.430320E+10 0.340555E+10 0.00 0.00
Minimum of Months 0.635784E+09 22793010.63 0.498285E+09 0.212292E+09 0.203233E+09 0.00 0.00
Maximum of Months 0.167199E+10 0.730957E+09 0.782721E+09 0.565485E+09 0.357087E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.570725E+09 0.613502E+09 0.393828E+09 0.211926E+09 0.181903E+09 0.00 0.00
February 0.339606E+09 0.530920E+09 0.304099E+09 0.120775E+09 0.183324E+09 0.00 0.00
March 0.614517E+09 0.509076E+09 0.445884E+09 0.174376E+09 0.271508E+09 0.00 0.00
April 0.116253E+10 0.222466E+09 0.636687E+09 0.309812E+09 0.326875E+09 0.00 0.00
May 0.135842E+10 0.131644E+09 0.677152E+09 0.323940E+09 0.353213E+09 0.00 0.00
June 0.170568E+10 31703130.01 0.705388E+09 0.361882E+09 0.343505E+09 0.00 0.00
July 0.143423E+10 21240356.77 0.547489E+09 0.213756E+09 0.333733E+09 0.00 0.00
August 0.130249E+10 24539706.68 0.506479E+09 0.210280E+09 0.296199E+09 0.00 0.00
September 0.104714E+10 42965232.90 0.433071E+09 0.146521E+09 0.286550E+09 0.00 0.00
October 0.776656E+09 0.322659E+09 0.437501E+09 0.212073E+09 0.225428E+09 0.00 0.00
November 0.540683E+09 0.523914E+09 0.382175E+09 0.197665E+09 0.184511E+09 0.00 0.00
December 0.406434E+09 0.762141E+09 0.321745E+09 0.153993E+09 0.167752E+09 0.00 0.00
               
Annual Sum or Average 0.112591E+11 0.373677E+10 0.579150E+10 0.263700E+10 0.315450E+10 0.00 0.00
Minimum of Months 0.339606E+09 21240356.77 0.304099E+09 0.120775E+09 0.167752E+09 0.00 0.00
Maximum of Months 0.170568E+10 0.762141E+09 0.705388E+09 0.361882E+09 0.353213E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.543155E+09 0.187258E+09 0.353983E+09 0.282791E+09 71191720.82 0.00 0.00
February 0.273561E+09 0.162250E+09 0.199502E+09 0.133746E+09 65755807.07 0.00 0.00
March 0.272688E+09 0.161023E+09 0.182850E+09 92654621.17 90194909.73 0.00 0.00
April 0.309056E+09 78736864.57 0.155304E+09 63973596.40 91330373.15 0.00 0.00
May 0.248435E+09 51168857.69 0.107231E+09 18653222.29 88577606.46 0.00 0.00
June 0.285248E+09 15109028.51 87837819.98 6701448.63 81136371.35 0.00 0.00
July 0.288066E+09 10060622.97 91975290.32 8744924.55 83230365.76 0.00 0.00
August 0.321405E+09 13308117.55 0.113732E+09 32030806.41 81700800.92 0.00 0.00
September 0.358740E+09 21359746.01 0.156339E+09 66076882.86 90262586.66 0.00 0.00
October 0.447296E+09 0.105557E+09 0.259316E+09 0.179516E+09 79800009.62 0.00 0.00
November 0.447797E+09 0.161168E+09 0.294982E+09 0.226559E+09 68423598.87 0.00 0.00
December 0.483204E+09 0.226026E+09 0.329655E+09 0.261175E+09 68480327.14 0.00 0.00
               
Annual Sum or Average 0.427865E+10 0.119302E+10 0.233271E+10 0.137262E+10 0.960084E+09 0.00 0.00
Minimum of Months 0.248435E+09 10060622.97 87837819.98 6701448.63 65755807.07 0.00 0.00
Maximum of Months 0.543155E+09 0.226026E+09 0.353983E+09 0.282791E+09 91330373.15 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 46323909.69 0.170034E+09 42944949.46 0.00 42944949.46 0.00 0.00
February 27907259.34 0.153185E+09 44199004.85 0.00 44199004.85 0.00 0.00
March 77131890.78 0.143792E+09 65045237.58 2573.27 65042664.31 0.00 0.00
April 0.164098E+09 55483929.83 77090857.89 1135053.46 75955804.43 0.00 0.00
May 0.231469E+09 30738754.70 93441433.49 7934259.35 85507174.14 0.00 0.00
June 0.343104E+09 6399967.03 0.104430E+09 19081199.32 85349110.47 0.00 0.00
July 0.317857E+09 4532587.84 92312481.83 9919050.97 82393430.86 0.00 0.00
August 0.264664E+09 5046058.08 74279179.59 1823766.12 72455413.47 0.00 0.00
September 0.214126E+09 9355002.92 67785290.05 41951.47 67743338.59 0.00 0.00
October 0.108825E+09 86621851.76 54159300.98 0.00 54159300.98 0.00 0.00
November 46411450.87 0.144740E+09 43668987.75 0.00 43668987.75 0.00 0.00
December 27908009.96 0.216700E+09 40114513.77 0.00 40114513.77 0.00 0.00
               
Annual Sum or Average 0.186983E+10 0.102663E+10 0.799472E+09 39937853.95 0.759534E+09 0.00 0.00
Minimum of Months 27907259.34 4532587.84 40114513.77 0.00 40114513.77 0.00 0.00
Maximum of Months 0.343104E+09 0.216700E+09 0.104430E+09 19081199.32 85507174.14 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.111596E+10 0.570322E+09 0.766505E+09 0.556878E+09 0.209627E+09 0.00 0.00
February 0.685143E+09 0.503073E+09 0.540277E+09 0.334558E+09 0.205719E+09 0.00 0.00
March 0.884097E+09 0.478992E+09 0.628463E+09 0.321558E+09 0.306905E+09 0.00 0.00
April 0.135950E+10 0.204305E+09 0.745596E+09 0.408534E+09 0.337062E+09 0.00 0.00
May 0.144922E+10 0.123428E+09 0.725583E+09 0.374306E+09 0.351277E+09 0.00 0.00
June 0.171428E+10 30394210.23 0.705417E+09 0.378400E+09 0.327016E+09 0.00 0.00
July 0.159293E+10 20244129.22 0.635569E+09 0.304666E+09 0.330904E+09 0.00 0.00
August 0.154489E+10 24613971.55 0.636696E+09 0.322574E+09 0.314123E+09 0.00 0.00
September 0.132603E+10 41514985.58 0.587611E+09 0.271747E+09 0.315864E+09 0.00 0.00
October 0.125050E+10 0.303638E+09 0.730860E+09 0.471799E+09 0.259061E+09 0.00 0.00
November 0.965096E+09 0.488941E+09 0.671635E+09 0.464986E+09 0.206650E+09 0.00 0.00
December 0.941709E+09 0.708517E+09 0.697993E+09 0.499406E+09 0.198587E+09 0.00 0.00
               
Annual Sum or Average 0.148294E+11 0.349798E+10 0.807221E+10 0.470941E+10 0.336279E+10 0.00 0.00
Minimum of Months 0.685143E+09 20244129.22 0.540277E+09 0.271747E+09 0.198587E+09 0.00 0.00
Maximum of Months 0.171428E+10 0.708517E+09 0.766505E+09 0.556878E+09 0.351277E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.480637E+09 0.555078E+09 0.377613E+09 0.203319E+09 0.174294E+09 0.00 0.00
February 0.368241E+09 0.496410E+09 0.346092E+09 0.167343E+09 0.178749E+09 0.00 0.00
March 0.626476E+09 0.472915E+09 0.481151E+09 0.205720E+09 0.275431E+09 0.00 0.00
April 0.116036E+10 0.201085E+09 0.647778E+09 0.329970E+09 0.317808E+09 0.00 0.00
May 0.140581E+10 0.122503E+09 0.708304E+09 0.360901E+09 0.347403E+09 0.00 0.00
June 0.175147E+10 30296335.89 0.726118E+09 0.393870E+09 0.332248E+09 0.00 0.00
July 0.158959E+10 20174460.46 0.635953E+09 0.306130E+09 0.329823E+09 0.00 0.00
August 0.143822E+10 24083454.80 0.587340E+09 0.284806E+09 0.302534E+09 0.00 0.00
September 0.111626E+10 40266868.94 0.476868E+09 0.189187E+09 0.287681E+09 0.00 0.00
October 0.806501E+09 0.296744E+09 0.474341E+09 0.247359E+09 0.226982E+09 0.00 0.00
November 0.449739E+09 0.478137E+09 0.357413E+09 0.181731E+09 0.175682E+09 0.00 0.00
December 0.358865E+09 0.694237E+09 0.335979E+09 0.172873E+09 0.163106E+09 0.00 0.00
               
Annual Sum or Average 0.115522E+11 0.343193E+10 0.615495E+10 0.304321E+10 0.311174E+10 0.00 0.00
Minimum of Months 0.358865E+09 20174460.46 0.335979E+09 0.167343E+09 0.163106E+09 0.00 0.00
Maximum of Months 0.175147E+10 0.694237E+09 0.726118E+09 0.393870E+09 0.347403E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.124031E+10 0.794544E+09 0.860015E+09 0.612730E+09 0.247286E+09 0.00 0.00
February 0.634958E+09 0.696204E+09 0.528015E+09 0.289790E+09 0.238224E+09 0.00 0.00
March 0.742711E+09 0.702382E+09 0.537094E+09 0.200762E+09 0.336332E+09 0.00 0.00
April 0.973011E+09 0.351172E+09 0.503505E+09 0.141072E+09 0.362433E+09 0.00 0.00
May 0.959196E+09 0.223037E+09 0.434765E+09 57604611.69 0.377160E+09 0.00 0.00
June 0.126433E+10 66366216.43 0.416551E+09 55856451.63 0.360695E+09 0.00 0.00
July 0.120600E+10 47211411.86 0.399265E+09 40435810.09 0.358829E+09 0.00 0.00
August 0.117316E+10 65224260.59 0.407338E+09 73352738.99 0.333986E+09 0.00 0.00
September 0.116119E+10 0.105129E+09 0.485590E+09 0.143261E+09 0.342329E+09 0.00 0.00
October 0.115126E+10 0.474359E+09 0.679193E+09 0.388962E+09 0.290232E+09 0.00 0.00
November 0.103106E+10 0.697551E+09 0.733746E+09 0.490890E+09 0.242857E+09 0.00 0.00
December 0.107167E+10 0.951582E+09 0.801172E+09 0.565893E+09 0.235279E+09 0.00 0.00
               
Annual Sum or Average 0.126089E+11 0.517476E+10 0.678625E+10 0.306061E+10 0.372564E+10 0.00 0.00
Minimum of Months 0.634958E+09 47211411.86 0.399265E+09 40435810.09 0.235279E+09 0.00 0.00
Maximum of Months 0.126433E+10 0.951582E+09 0.860015E+09 0.612730E+09 0.377160E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.116767E+10 0.581680E+09 0.782721E+09 0.565485E+09 0.217236E+09 0.00 0.00
February 0.633636E+09 0.505909E+09 0.498285E+09 0.287991E+09 0.210294E+09 0.00 0.00
March 0.859289E+09 0.498841E+09 0.593196E+09 0.290214E+09 0.302982E+09 0.00 0.00
April 0.135460E+10 0.220156E+09 0.734505E+09 0.388376E+09 0.346129E+09 0.00 0.00
May 0.140650E+10 0.134064E+09 0.694431E+09 0.337345E+09 0.357087E+09 0.00 0.00
June 0.166931E+10 32011177.08 0.684686E+09 0.346412E+09 0.338274E+09 0.00 0.00
July 0.143793E+10 21363073.86 0.547106E+09 0.212292E+09 0.334813E+09 0.00 0.00
August 0.140789E+10 23583445.67 0.555835E+09 0.248047E+09 0.307788E+09 0.00 0.00
September 0.125393E+10 40315091.74 0.543814E+09 0.229081E+09 0.314733E+09 0.00 0.00
October 0.120180E+10 0.306642E+09 0.694021E+09 0.436513E+09 0.257508E+09 0.00 0.00
November 0.102581E+10 0.495512E+09 0.696397E+09 0.480919E+09 0.215478E+09 0.00 0.00
December 0.945745E+09 0.719002E+09 0.683759E+09 0.480526E+09 0.203233E+09 0.00 0.00
               
Annual Sum or Average 0.143641E+11 0.357908E+10 0.770875E+10 0.430320E+10 0.340555E+10 0.00 0.00
Minimum of Months 0.633636E+09 21363073.86 0.498285E+09 0.212292E+09 0.203233E+09 0.00 0.00
Maximum of Months 0.166931E+10 0.719002E+09 0.782721E+09 0.565485E+09 0.357087E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.574625E+09 0.595660E+09 0.393828E+09 0.211926E+09 0.181903E+09 0.00 0.00
February 0.340666E+09 0.516252E+09 0.304099E+09 0.120775E+09 0.183324E+09 0.00 0.00
March 0.614500E+09 0.497934E+09 0.445884E+09 0.174376E+09 0.271508E+09 0.00 0.00
April 0.115713E+10 0.214067E+09 0.636687E+09 0.309812E+09 0.326875E+09 0.00 0.00
May 0.135535E+10 0.125051E+09 0.677152E+09 0.323940E+09 0.353213E+09 0.00 0.00
June 0.170247E+10 29180211.42 0.705388E+09 0.361882E+09 0.343505E+09 0.00 0.00
July 0.143289E+10 20013343.90 0.547489E+09 0.213756E+09 0.333733E+09 0.00 0.00
August 0.130183E+10 22558937.96 0.506479E+09 0.210280E+09 0.296199E+09 0.00 0.00
September 0.104736E+10 39232035.28 0.433071E+09 0.146521E+09 0.286550E+09 0.00 0.00
October 0.778494E+09 0.309345E+09 0.437501E+09 0.212073E+09 0.225428E+09 0.00 0.00
November 0.543449E+09 0.507749E+09 0.382175E+09 0.197665E+09 0.184511E+09 0.00 0.00
December 0.411101E+09 0.743974E+09 0.321745E+09 0.153993E+09 0.167752E+09 0.00 0.00
               
Annual Sum or Average 0.112599E+11 0.362102E+10 0.579150E+10 0.263700E+10 0.315450E+10 0.00 0.00
Minimum of Months 0.340666E+09 20013343.90 0.304099E+09 0.120775E+09 0.167752E+09 0.00 0.00
Maximum of Months 0.170247E+10 0.743974E+09 0.705388E+09 0.361882E+09 0.353213E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.998035E+09 0.302250E+09 0.649066E+09 0.518528E+09 0.130538E+09 0.00 0.00
February 0.503781E+09 0.265620E+09 0.365808E+09 0.245238E+09 0.120570E+09 0.00 0.00
March 0.506592E+09 0.260303E+09 0.335275E+09 0.169892E+09 0.165382E+09 0.00 0.00
April 0.581477E+09 0.109700E+09 0.284767E+09 0.117303E+09 0.167464E+09 0.00 0.00
May 0.481876E+09 64390982.68 0.196619E+09 34202726.45 0.162417E+09 0.00 0.00
June 0.561837E+09 13751561.98 0.161060E+09 12287840.18 0.148772E+09 0.00 0.00
July 0.572675E+09 9720758.27 0.168647E+09 16034777.14 0.152612E+09 0.00 0.00
August 0.626776E+09 10900776.70 0.208539E+09 58731992.40 0.149807E+09 0.00 0.00
September 0.685008E+09 19199784.28 0.286666E+09 0.121159E+09 0.165506E+09 0.00 0.00
October 0.829847E+09 0.156665E+09 0.475485E+09 0.329163E+09 0.146322E+09 0.00 0.00
November 0.824347E+09 0.256810E+09 0.540882E+09 0.415420E+09 0.125462E+09 0.00 0.00
December 0.888523E+09 0.375968E+09 0.604458E+09 0.478892E+09 0.125566E+09 0.00 0.00
               
Annual Sum or Average 0.806077E+10 0.184528E+10 0.427727E+10 0.251685E+10 0.176042E+10 0.00 0.00
Minimum of Months 0.481876E+09 9720758.27 0.161060E+09 12287840.18 0.120570E+09 0.00 0.00
Maximum of Months 0.998035E+09 0.375968E+09 0.649066E+09 0.518528E+09 0.167464E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.303179E+09 0.181364E+10 0.375704E+09 0.00 0.375704E+09 0.00 0.00
February 0.172561E+09 0.164507E+10 0.386675E+09 0.00 0.386675E+09 0.00 0.00
March 0.544617E+09 0.157192E+10 0.569049E+09 22512.27 0.569026E+09 0.00 0.00
April 0.124197E+10 0.725405E+09 0.674430E+09 9930025.34 0.664500E+09 0.00 0.00
May 0.176914E+10 0.456628E+09 0.817473E+09 69412938.91 0.748060E+09 0.00 0.00
June 0.266349E+10 0.149079E+09 0.913609E+09 0.166932E+09 0.746677E+09 0.00 0.00
July 0.239449E+10 0.111296E+09 0.807597E+09 86776906.14 0.720820E+09 0.00 0.00
August 0.197186E+10 0.153600E+09 0.649832E+09 15955234.21 0.633877E+09 0.00 0.00
September 0.159299E+10 0.241582E+09 0.593020E+09 367012.78 0.592653E+09 0.00 0.00
October 0.789627E+09 0.103701E+10 0.473813E+09 0.00 0.473813E+09 0.00 0.00
November 0.304130E+09 0.158879E+10 0.382039E+09 0.00 0.382039E+09 0.00 0.00
December 0.168571E+09 0.221379E+10 0.350942E+09 0.00 0.350942E+09 0.00 0.00
               
Annual Sum or Average 0.139166E+11 0.117078E+11 0.699418E+10 0.349397E+09 0.664479E+10 0.00 0.00
Minimum of Months 0.168571E+09 0.111296E+09 0.350942E+09 0.00 0.350942E+09 0.00 0.00
Maximum of Months 0.266349E+10 0.221379E+10 0.913609E+09 0.166932E+09 0.748060E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.276913E+09 0.188281E+10 0.375704E+09 0.00 0.375704E+09 0.00 0.00
February 0.152179E+09 0.172649E+10 0.386675E+09 0.00 0.386675E+09 0.00 0.00
March 0.507919E+09 0.163647E+10 0.569049E+09 22512.27 0.569026E+09 0.00 0.00
April 0.119995E+10 0.753678E+09 0.674430E+09 9930025.34 0.664500E+09 0.00 0.00
May 0.172028E+10 0.474286E+09 0.817473E+09 69412938.91 0.748060E+09 0.00 0.00
June 0.261152E+10 0.157191E+09 0.913609E+09 0.166932E+09 0.746677E+09 0.00 0.00
July 0.234018E+10 0.119648E+09 0.807597E+09 86776906.14 0.720820E+09 0.00 0.00
August 0.192099E+10 0.165858E+09 0.649832E+09 15955234.21 0.633877E+09 0.00 0.00
September 0.154759E+10 0.257929E+09 0.593020E+09 367012.78 0.592653E+09 0.00 0.00
October 0.754872E+09 0.107972E+10 0.473813E+09 0.00 0.473813E+09 0.00 0.00
November 0.279348E+09 0.165385E+10 0.382039E+09 0.00 0.382039E+09 0.00 0.00
December 0.147627E+09 0.230279E+10 0.350942E+09 0.00 0.350942E+09 0.00 0.00
               
Annual Sum or Average 0.134594E+11 0.122107E+11 0.699418E+10 0.349397E+09 0.664479E+10 0.00 0.00
Minimum of Months 0.147627E+09 0.119648E+09 0.350942E+09 0.00 0.350942E+09 0.00 0.00
Maximum of Months 0.261152E+10 0.230279E+10 0.913609E+09 0.166932E+09 0.748060E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.159869E+10 0.140810E+10 0.114407E+10 0.760168E+09 0.383905E+09 0.00 0.00
February 0.102983E+10 0.130227E+10 0.886328E+09 0.501877E+09 0.384451E+09 0.00 0.00
March 0.150141E+10 0.125439E+10 0.110956E+10 0.527249E+09 0.582308E+09 0.00 0.00
April 0.258995E+10 0.612288E+09 0.139330E+10 0.738458E+09 0.654838E+09 0.00 0.00
May 0.292568E+10 0.435388E+09 0.143380E+10 0.735158E+09 0.698645E+09 0.00 0.00
June 0.349662E+10 0.171639E+09 0.143145E+10 0.772218E+09 0.659232E+09 0.00 0.00
July 0.317184E+10 0.135490E+09 0.127145E+10 0.610754E+09 0.660695E+09 0.00 0.00
August 0.300867E+10 0.177987E+09 0.122397E+10 0.607340E+09 0.616627E+09 0.00 0.00
September 0.247873E+10 0.245369E+09 0.106442E+10 0.460908E+09 0.603516E+09 0.00 0.00
October 0.209761E+10 0.836566E+09 0.120514E+10 0.719123E+09 0.486021E+09 0.00 0.00
November 0.141151E+10 0.124131E+10 0.102901E+10 0.646691E+09 0.382315E+09 0.00 0.00
December 0.128142E+10 0.168737E+10 0.103393E+10 0.672254E+09 0.361677E+09 0.00 0.00
               
Annual Sum or Average 0.265920E+11 0.950817E+10 0.142264E+11 0.775220E+10 0.647423E+10 0.00 0.00
Minimum of Months 0.102983E+10 0.135490E+09 0.886328E+09 0.460908E+09 0.361677E+09 0.00 0.00
Maximum of Months 0.349662E+10 0.168737E+10 0.143380E+10 0.772218E+09 0.698645E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.257869E+10 0.142735E+10 0.178102E+10 0.131994E+10 0.461083E+09 0.00 0.00
February 0.130382E+10 0.125597E+10 0.106374E+10 0.624266E+09 0.439472E+09 0.00 0.00
March 0.143126E+10 0.128109E+10 0.104853E+10 0.432478E+09 0.616053E+09 0.00 0.00
April 0.180347E+10 0.645529E+09 0.956085E+09 0.302004E+09 0.654081E+09 0.00 0.00
May 0.168463E+10 0.415118E+09 0.780737E+09 0.110860E+09 0.669877E+09 0.00 0.00
June 0.215950E+10 0.127667E+09 0.723175E+09 88503980.79 0.634671E+09 0.00 0.00
July 0.207424E+10 93964946.14 0.706145E+09 70564670.40 0.635580E+09 0.00 0.00
August 0.209078E+10 0.130568E+09 0.753612E+09 0.154975E+09 0.598637E+09 0.00 0.00
September 0.214390E+10 0.204682E+09 0.933011E+09 0.308543E+09 0.624468E+09 0.00 0.00
October 0.229001E+10 0.851523E+09 0.137280E+10 0.837901E+09 0.534895E+09 0.00 0.00
November 0.213022E+10 0.125419E+10 0.150781E+10 0.105747E+10 0.450334E+09 0.00 0.00
December 0.226601E+10 0.168395E+10 0.165898E+10 0.121905E+10 0.439939E+09 0.00 0.00
               
Annual Sum or Average 0.239565E+11 0.937159E+10 0.132856E+11 0.652656E+10 0.675909E+10 0.00 0.00
Minimum of Months 0.130382E+10 93964946.14 0.706145E+09 70564670.40 0.439472E+09 0.00 0.00
Maximum of Months 0.257869E+10 0.168395E+10 0.178102E+10 0.131994E+10 0.669877E+09 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 14.83 7.47 -0.8 2.99 -0.8 34.08 283.26 0.00
February 12.72 9.35 6.24 2.64 2.53 52.02 191.85 0.02
March 15.42 8.67 1.96 3.53 3.02 74.19 207.67 0.01
April 23.31 10.14 -4.1 3.42 6.81 72.47 350.22 0.00
May 26.31 11.07 -4.9 3.62 8.60 75.22 359.64 0.00
June 31.20 14.28 0.18 3.69 15.53 67.31 396.02 0.00
July 30.42 17.99 9.86 3.72 19.28 82.46 278.62 0.02
August 29.82 18.15 11.14 3.33 18.26 71.82 270.19 0.02
September 27.75 17.59 11.45 3.72 17.29 82.54 200.28 0.01
October 20.87 10.99 1.63 3.42 6.03 49.01 269.00 0.00
November 15.43 8.80 1.49 3.02 1.83 40.49 251.35 0.01
December 11.86 4.25 -5.9 2.21 -4.3 34.74 244.35 0.00
                 
Annual Sum or Average 21.70 11.57 2.33 3.28 7.86 61.39 275.62 0.01
Minimum of Months 11.86 4.25 -5.9 2.21 -4.3 34.08 191.85 0.00
Maximum of Months 31.20 18.15 11.45 3.72 19.28 82.54 396.02 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 29.00 31-JAN-15:00 10.73 -14.0 2.10 7.75 109.00 697.00
February 22.00 18-FEB-14:09 14.42 9.67 5.20 14.10 264.00 225.33
March 28.80 16-MAR-15:20 13.79 1.47 3.77 14.35 156.17 666.17
April 35.00 14-APR-14:00 14.57 -4.0 1.50 19.70 150.00 819.50
May 37.00 15-MAY-16:00 15.57 -2.0 4.60 20.75 127.50 679.00
June 42.00 16-JUN-15:00 16.74 -5.0 5.70 25.49 135.00 753.50
July 40.00 12-JUL-13:00 19.40 7.00 2.10 27.95 147.00 3.00
August 41.00 25-AUG-14:09 17.27 -0.7 3.43 25.74 162.33 768.67
September 38.30 08-SEP-14:00 19.81 10.00 3.00 25.82 142.00 699.00
October 37.00 01-OCT-12:00 19.01 9.00 4.10 27.14 262.50 136.00
November 29.00 01-NOV-14:00 16.20 8.00 2.60 16.49 73.50 907.50
December 26.00 21-DEC-14:00 10.90 -5.0 2.60 7.35 68.50 756.50
                 
Annual Sum or Average                
Minimum of Months 22.00   10.73 -14.0 1.50 7.35 68.50 3.00
Maximum of Months 42.00   19.81 10.00 5.70 27.95 264.00 907.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 0.50 01-JAN-07:00 -1.2 -3.3 3.30 -16.2 17.50 352.00
February 5.00 01-FEB-04:00 3.59 2.00 3.10 -10.7 0.00 0.00
March 0.50 26-MAR-03:00 -2.4 -6.7 2.50 -17.0 0.00 0.00
April 8.00 21-APR-03:00 0.42 -14.0 1.00 -11.7 0.00 0.00
May 12.00 01-MAY-03:00 3.97 -7.0 2.60 -6.2 0.00 0.00
June 18.00 21-JUN-04:00 8.24 -2.0 1.50 3.48 0.00 0.00
July 18.00 01-JUL-05:00 6.53 -9.0 3.10 -1.2 16.00 325.00
August 17.00 05-AUG-17:00 15.02 14.00 5.70 11.46 29.00 0.00
September 16.60 22-SEP-05:00 13.83 12.20 3.00 4.92 0.00 0.00
October 5.00 25-OCT-05:00 0.48 -6.0 3.10 -12.7 0.00 0.00
November 0.00 23-NOV-05:00 -2.5 -6.0 2.10 -17.3 0.00 0.00
December -1.1 07-DEC-04:00 -5.6 -16.0 3.10 -20.8 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -1.1   -5.6 -16.0 1.00 -20.8 0.00 0.00
Maximum of Months 18.00   15.02 14.00 5.70 11.46 29.00 352.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.66 08-JAN-15:00 18.00 16.00 4.60 11.46 102.00 332.00
February 14.73 18-FEB-17:00 16.00 14.00 6.20 10.50 0.00 0.00
March 15.18 17-MAR-10:00 25.50 8.30 2.50 18.46 167.50 459.00
April 15.71 11-APR-14:00 33.00 3.00 2.10 15.94 178.50 758.00
May 15.57 15-MAY-16:00 37.00 -2.0 4.60 20.75 127.50 679.00
June 23.18 17-JUN-15:00 41.00 16.00 3.60 31.13 257.00 9.00
July 23.11 13-JUL-17:00 26.00 22.00 4.60 22.13 79.00 56.50
August 22.19 16-AUG-10:00 35.00 17.00 2.10 24.33 140.50 837.00
September 22.23 01-SEP-11:00 34.40 17.20 4.60 23.82 193.50 725.50
October 21.53 01-OCT-17:00 32.00 17.00 2.10 25.33 30.50 1.50
November 18.59 12-NOV-14:00 20.00 18.00 3.10 15.39 115.00 0.00
December 12.06 12-DEC-12:00 20.00 6.00 1.50 12.60 182.50 6.00
                 
Annual Sum or Average                
Minimum of Months 12.06   16.00 -2.0 1.50 10.50 0.00 0.00
Maximum of Months 23.18   41.00 22.00 6.20 31.13 257.00 837.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.00 08-JAN-15:00 18.00 16.66 4.60 11.46 102.00 332.00
February 14.00 18-FEB-17:00 16.00 14.73 6.20 10.50 0.00 0.00
March 13.30 06-MAR-10:00 14.40 13.70 6.10 10.69 254.50 82.00
April 8.00 15-APR-20:00 23.00 14.00 6.20 7.75 0.00 0.00
May 9.00 26-MAY-02:00 21.00 13.75 3.60 16.30 0.00 0.00
June 16.00 17-JUN-15:00 41.00 23.18 3.60 31.13 257.00 9.00
July 22.00 13-JUL-17:00 26.00 23.11 4.60 22.13 79.00 56.50
August 20.00 09-AUG-17:00 25.00 21.44 5.10 19.17 35.00 0.00
September 20.50 02-SEP-22:10 22.62 21.05 3.18 20.17 0.00 0.00
October 19.00 03-OCT-02:00 23.00 20.15 2.10 10.30 0.00 0.00
November 18.00 12-NOV-14:00 20.00 18.59 3.10 15.39 115.00 0.00
December 10.00 12-DEC-23:00 12.00 10.87 1.50 7.55 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 8.00   12.00 10.87 1.50 7.55 0.00 0.00
Maximum of Months 22.00   41.00 23.18 6.20 31.13 257.00 332.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 18.65 31.23 0.00
February 18.00 13.00 16.00 19.06 29.93 0.00
March 18.00 13.00 16.00 20.99 39.76 0.00
April 18.00 13.00 16.00 24.03 60.89 0.00
May 18.00 13.00 16.00 27.32 65.75 0.00
June 18.00 13.00 16.00 29.99 69.24 0.00
July 18.00 13.00 16.00 31.31 56.42 0.00
August 18.00 13.00 16.00 30.91 52.05 0.00
September 18.00 13.00 16.00 28.91 42.71 0.00
October 18.00 13.00 16.00 25.85 39.20 0.00
November 18.00 13.00 16.00 22.56 30.64 0.00
December 18.00 13.00 16.00 19.93 27.41 0.00
             
Annual Sum or Average 18.00 13.00 16.00 24.99 45.50 0.00
Minimum of Months 18.00 13.00 16.00 18.65 27.41 0.00
Maximum of Months 18.00 13.00 16.00 31.31 69.24 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770412E+10 -0.754278E+10 0.00 0.00 744.00 0.00 -161342347.9 81.21 0.00 0.00
February 0.696172E+10 -0.681597E+10 0.00 0.00 672.00 0.00 -145753723.5 81.21 0.00 0.00
March 0.770285E+10 -0.754146E+10 0.00 0.00 744.00 0.00 -161388461.5 81.21 0.00 0.00
April 0.746480E+10 -0.730859E+10 0.00 0.00 720.00 0.00 -156206620.0 81.21 0.00 0.00
May 0.770420E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -161411967.4 81.21 0.00 0.00
June 0.745674E+10 -0.730053E+10 0.00 0.00 720.00 0.00 -156202634.1 81.21 0.00 0.00
July 0.771226E+10 -0.755085E+10 0.00 0.00 744.00 0.00 -161407948.0 81.21 0.00 0.00
August 0.770422E+10 -0.754281E+10 0.00 0.00 744.00 0.00 -161407720.1 81.21 0.00 0.00
September 0.746614E+10 -0.730994E+10 0.00 0.00 720.00 0.00 -156201104.8 81.21 0.00 0.00
October 0.770285E+10 -0.754144E+10 0.00 0.00 744.00 0.00 -161411658.4 81.21 0.00 0.00
November 0.744860E+10 -0.729242E+10 0.00 0.00 720.00 0.00 -156178681.4 81.21 0.00 0.00
December 0.771216E+10 -0.755086E+10 0.00 0.00 744.00 0.00 -161306627.6 81.21 0.00 0.00
                     
Annual Sum or Average 0.907407E+11 -0.888405E+11 0.00 0.00 8760.00 0.00 -0.190022E+10 81.21 0.00 0.00
Minimum of Months 0.696172E+10 -0.755086E+10 0.00 0.00 672.00 0.00 -161411967.4 81.21 0.00 0.00
Maximum of Months 0.771226E+10 -0.681597E+10 0.00 0.00 744.00 0.00 -145753723.5 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.107700E+12 -0.105973E+12 0.00 0.00 744.00 0.00 -0.172730E+10 81.25 0.00 0.00
February 0.966512E+11 -0.950843E+11 0.00 0.00 672.00 0.00 -0.156695E+10 81.25 0.00 0.00
March 0.103743E+12 -0.101997E+12 0.00 0.00 744.00 0.00 -0.174661E+10 81.25 0.00 0.00
April 0.954114E+11 -0.937295E+11 0.00 0.00 720.00 0.00 -0.168194E+10 81.24 0.00 0.00
May 0.930143E+11 -0.912689E+11 0.00 0.00 744.00 0.00 -0.174531E+10 81.24 0.00 0.00
June 0.856288E+11 -0.839466E+11 0.00 0.00 720.00 0.00 -0.168225E+10 81.25 0.00 0.00
July 0.862418E+11 -0.845147E+11 0.00 0.00 744.00 0.00 -0.172714E+10 81.23 0.00 0.00
August 0.869181E+11 -0.851923E+11 0.00 0.00 744.00 0.00 -0.172582E+10 81.24 0.00 0.00
September 0.873916E+11 -0.857220E+11 0.00 0.00 720.00 0.00 -0.166959E+10 81.23 0.00 0.00
October 0.954879E+11 -0.937626E+11 0.00 0.00 744.00 0.00 -0.172532E+10 81.24 0.00 0.00
November 0.978035E+11 -0.961337E+11 0.00 0.00 720.00 0.00 -0.166979E+10 81.24 0.00 0.00
December 0.105527E+12 -0.103801E+12 0.00 0.00 744.00 0.00 -0.172547E+10 81.25 0.00 0.00
                     
Annual Sum or Average 0.114152E+13 -0.112113E+13 0.00 0.00 8760.00 0.00 -0.203935E+11 81.24 0.00 0.00
Minimum of Months 0.856288E+11 -0.105973E+12 0.00 0.00 672.00 0.00 -0.174661E+10 81.23 0.00 0.00
Maximum of Months 0.107700E+12 -0.839466E+11 0.00 0.00 744.00 0.00 -0.156695E+10 81.25 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.603884E+11 -0.589243E+11 0.00 0.00 744.00 0.00 -0.146404E+10 58.98 0.00 0.00
February 0.540192E+11 -0.526874E+11 0.00 0.00 672.00 0.00 -0.133182E+10 58.98 0.00 0.00
March 0.570369E+11 -0.555464E+11 0.00 0.00 744.00 0.00 -0.149058E+10 58.98 0.00 0.00
April 0.508603E+11 -0.494289E+11 0.00 0.00 720.00 0.00 -0.143142E+10 58.98 0.00 0.00
May 0.477530E+11 -0.462641E+11 0.00 0.00 744.00 0.00 -0.148893E+10 58.98 0.00 0.00
June 0.424365E+11 -0.410050E+11 0.00 0.00 720.00 0.00 -0.143145E+10 58.97 0.00 0.00
July 0.418685E+11 -0.404044E+11 0.00 0.00 744.00 0.00 -0.146411E+10 58.97 0.00 0.00
August 0.424950E+11 -0.410331E+11 0.00 0.00 744.00 0.00 -0.146191E+10 58.97 0.00 0.00
September 0.439334E+11 -0.425190E+11 0.00 0.00 720.00 0.00 -0.141434E+10 58.98 0.00 0.00
October 0.498502E+11 -0.483886E+11 0.00 0.00 744.00 0.00 -0.146157E+10 58.98 0.00 0.00
November 0.528961E+11 -0.514816E+11 0.00 0.00 720.00 0.00 -0.141450E+10 58.98 0.00 0.00
December 0.585122E+11 -0.570506E+11 0.00 0.00 744.00 0.00 -0.146159E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.602050E+12 -0.584733E+12 0.00 0.00 8760.00 0.00 -0.173163E+11 58.98 0.00 0.00
Minimum of Months 0.418685E+11 -0.589243E+11 0.00 0.00 672.00 0.00 -0.149058E+10 58.97 0.00 0.00
Maximum of Months 0.603884E+11 -0.404044E+11 0.00 0.00 744.00 0.00 -0.133182E+10 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.93 0.93 01-JAN-07:49 7548.65 38.83 306.67 291.83 1049.88 27.72 175.83 285.67
February 241.00 0.93 0.93 01-FEB-07:49 4376.20 32.33 187.33 264.83 538.29 23.04 122.00 199.33
March 344.33 0.94 0.93 01-MAR-07:19 1012.94 19.32 11.50 321.50 384.40 20.69 124.00 245.67
April 380.33 0.94 0.93 01-APR-07:19 701.83 18.92 0.00 329.83 305.99 20.68 122.67 245.33
May 403.17 0.94 0.93 01-MAY-06:00 566.05 18.71 0.00 352.67 250.58 20.50 53.50 182.83
June 418.17 0.94 0.93 01-JUN-06:49 458.03 18.07 0.00 354.67 208.58 19.90 8.83 81.00
July 399.50 0.94 0.93 01-JUL-07:19 564.08 18.14 0.00 356.00 240.66 19.94 40.33 154.17
August 361.83 0.94 0.93 01-AUG-07:30 629.07 18.52 0.00 333.00 267.69 20.29 62.83 173.17
September 350.17 0.94 0.93 01-SEP-06:49 927.38 18.84 0.00 317.83 371.98 20.61 128.50 253.50
October 348.00 0.93 0.93 01-OCT-07:10 2543.93 25.40 135.17 318.67 414.12 21.33 111.83 263.17
November 288.50 0.93 0.93 01-NOV-07:19 7196.60 37.59 282.50 286.00 822.19 26.25 149.50 261.50
December 290.67 0.93 0.93 01-DEC-07:40 6943.82 38.65 287.33 280.17 1201.32 28.46 172.67 271.17
                         
Annual Sum or Average 4135.50 0.94     2463.19 24.24 1210.50 3807.00 470.50 22.13 1272.50 2616.50
Minimum of Months 241.00 0.93 0.93   458.03 18.07 0.00 264.83 208.58 19.90 8.83 81.00
Maximum of Months 418.17 0.94 0.93   7548.65 38.83 306.67 356.00 1201.32 28.46 175.83 285.67



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.63 0.61 01-JAN-07:49 7971.05 38.88 306.67 294.50 1469.74 27.24 157.17 291.50
February 241.00 0.63 0.61 01-FEB-07:49 4690.33 32.30 187.33 271.67 852.00 22.97 122.17 241.33
March 344.33 0.63 0.61 01-MAR-07:10 1228.41 19.82 15.00 336.17 600.44 21.02 161.17 300.83
April 380.33 0.64 0.61 01-APR-06:00 879.80 19.53 6.50 341.33 483.58 21.07 181.50 315.67
May 403.17 0.63 0.61 01-MAY-06:30 692.89 19.54 0.00 373.33 377.09 21.09 159.00 333.17
June 418.17 0.64 0.61 01-JUN-06:19 563.05 18.98 0.00 378.17 313.32 20.58 59.67 332.17
July 399.50 0.63 0.61 01-JUL-06:40 675.12 19.06 0.00 380.50 351.37 20.61 123.50 319.50
August 361.83 0.63 0.61 01-AUG-06:49 769.63 19.31 0.17 352.17 407.88 20.85 123.00 305.50
September 350.17 0.63 0.61 01-SEP-06:49 1118.13 19.48 10.00 330.33 562.20 21.03 172.67 299.33
October 348.00 0.63 0.61 01-OCT-06:00 2836.22 25.50 135.17 325.00 705.54 21.33 121.50 305.17
November 288.50 0.62 0.61 01-NOV-07:19 7574.02 37.66 282.67 290.83 1200.00 25.90 140.83 274.83
December 290.67 0.62 0.61 01-DEC-07:40 7361.07 38.71 287.67 284.50 1616.80 28.02 162.67 277.33
                         
Annual Sum or Average 4135.50 0.63     2689.86 24.74 1231.17 3958.50 696.63 22.37 1684.83 3596.33
Minimum of Months 241.00 0.62 0.61   563.05 18.98 0.00 271.67 313.32 20.58 59.67 241.33
Maximum of Months 418.17 0.64 0.61   7971.05 38.88 306.67 380.50 1616.80 28.02 181.50 333.17



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.84 0.80 01-JAN-09:20 242.49 13.26 0.00 196.50 134.54 16.92 0.00 15.67
February 241.00 0.83 0.80 01-FEB-10:30 315.97 14.16 0.00 210.00 158.01 17.58 0.00 59.00
March 344.33 0.82 0.80 01-MAR-07:40 372.30 15.40 0.00 302.83 179.12 18.67 0.00 134.83
April 380.33 0.82 0.80 01-APR-07:19 417.91 16.43 0.00 339.00 213.58 19.70 11.17 215.00
May 403.17 0.80 0.80 01-MAY-06:10 522.00 18.09 23.33 391.83 272.37 21.68 75.50 324.17
June 418.17 0.81 0.80 01-JUN-05:49 556.90 19.39 60.67 401.50 304.18 23.23 119.33 310.67
July 399.50 0.81 0.80 01-JUL-05:49 541.48 18.86 47.83 399.17 280.91 22.69 101.83 295.83
August 361.83 0.81 0.80 01-AUG-06:30 434.93 16.38 0.00 354.67 213.67 19.94 16.17 181.83
September 350.17 0.82 0.80 01-SEP-06:49 431.51 15.92 0.00 321.50 204.29 19.13 0.00 186.17
October 348.00 0.84 0.80 01-OCT-07:19 286.69 14.27 0.00 224.83 148.91 17.74 0.00 60.67
November 288.50 0.83 0.80 01-NOV-07:40 271.55 13.83 0.00 210.17 142.47 17.43 0.00 29.50
December 290.67 0.84 0.80 01-DEC-08:50 251.40 13.39 0.00 191.00 135.46 17.08 0.00 13.33
                         
Annual Sum or Average 4135.50 0.82     400.85 16.05 131.83 3543.00 206.28 19.59 324.00 1826.67
Minimum of Months 241.00 0.80 0.80   242.49 13.26 0.00 191.00 134.54 16.92 0.00 13.33
Maximum of Months 418.17 0.84 0.80   556.90 19.39 60.67 401.50 304.18 23.23 119.33 324.17



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.84 0.80 01-JAN-09:20 242.49 13.26 0.00 196.50 134.54 16.92 0.00 15.67
February 241.00 0.83 0.80 01-FEB-10:30 315.97 14.16 0.00 210.00 158.01 17.58 0.00 59.00
March 344.33 0.82 0.80 01-MAR-07:40 372.30 15.40 0.00 302.83 179.12 18.67 0.00 134.83
April 380.33 0.82 0.80 01-APR-07:19 417.91 16.43 0.00 339.00 213.58 19.70 11.17 215.00
May 403.17 0.80 0.80 01-MAY-06:10 522.00 18.09 23.33 391.83 272.37 21.68 75.50 324.17
June 418.17 0.81 0.80 01-JUN-05:49 556.90 19.39 60.67 401.50 304.18 23.23 119.33 310.67
July 399.50 0.81 0.80 01-JUL-05:49 541.48 18.86 47.83 399.17 280.91 22.69 101.83 295.83
August 361.83 0.81 0.80 01-AUG-06:30 434.93 16.38 0.00 354.67 213.67 19.94 16.17 181.83
September 350.17 0.82 0.80 01-SEP-06:49 431.51 15.92 0.00 321.50 204.29 19.13 0.00 186.17
October 348.00 0.84 0.80 01-OCT-07:19 286.69 14.27 0.00 224.83 148.91 17.74 0.00 60.67
November 288.50 0.83 0.80 01-NOV-07:40 271.55 13.83 0.00 210.17 142.47 17.43 0.00 29.50
December 290.67 0.84 0.80 01-DEC-08:50 251.40 13.39 0.00 191.00 135.46 17.08 0.00 13.33
                         
Annual Sum or Average 4135.50 0.82     400.85 16.05 131.83 3543.00 206.28 19.59 324.00 1826.67
Minimum of Months 241.00 0.80 0.80   242.49 13.26 0.00 191.00 134.54 16.92 0.00 13.33
Maximum of Months 418.17 0.84 0.80   556.90 19.39 60.67 401.50 304.18 23.23 119.33 324.17



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.179099E+11 107943.86 12-JAN-06:57 0.00 0.00 0.00 0.00 0.00
February 0.163900E+11 125941.31 25-FEB-05:23 0.00 0.00 0.00 0.00 0.00
March 0.123889E+11 106012.11 25-MAR-04:50 0.00 0.00 0.00 0.00 0.00
April 0.579522E+09 92300.84 21-APR-03:47 0.00 0.00 0.00 0.00 0.00
May 41198910.07 13401.96 01-MAY-03:30 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.423339E+10 102536.58 25-OCT-05:36 0.00 0.00 0.00 0.00 0.00
November 0.105801E+11 105313.20 04-NOV-07:00 0.00 0.00 0.00 0.00 0.00
December 0.196442E+11 138449.74 04-DEC-23:27 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.817672E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196442E+11 138449.74   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 13709974.90 674.69 01-JAN-06:00 0.00 0.00 0.00 0.00 0.00
February 89566473.90 972.18 13-FEB-05:50 0.00 0.00 0.00 0.00 0.00
March 70165983.50 898.78 27-MAR-06:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 639984.90 208.17 28-OCT-06:20 0.00 0.00 0.00 0.00 0.00
November 6761918.15 462.21 08-NOV-05:40 0.00 0.00 0.00 0.00 0.00
December 0.131201E+09 1008.59 16-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.312045E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.131201E+09 1008.59   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 3673817.51 226.30 01-JAN-06:00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 8554186.22 485.79 07-DEC-09:15 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 12228003.73     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 8554186.22 485.79   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 43637932.25 667.88 01-JAN-10:00 0.00 0.00 0.00 0.00 0.00
February 89905176.62 433.86 13-FEB-05:56 0.00 0.00 0.00 0.00 0.00
March 55584865.20 558.85 27-MAR-07:30 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 11968421.98 344.43 24-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.221730E+09 866.45 07-DEC-09:15 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.422827E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.221730E+09 866.45   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 228962.72 763.21 28-JAN-05:15 0.00 0.00 0.00 0.00 0.00
February 38908.87 129.70 02-FEB-02:35 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 605376.01 2017.92 30-NOV-05:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 873247.60     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 605376.01 2017.92   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 2184310.01 1210.60 09-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.285153E+09 3326.64 12-FEB-16:00 0.00 0.00 0.00 0.00 0.00
March 0.137920E+09 3935.58 27-MAR-08:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 6793951.80 3078.05 25-OCT-06:29 0.00 0.00 0.00 0.00 0.00
November 41237984.29 2186.74 13-NOV-11:50 0.00 0.00 0.00 0.00 0.00
December 79860740.29 2531.68 06-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.553150E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.285153E+09 3935.58   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 33913630.49 1810.73 02-JAN-07:27 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 947159.66 390.45 27-MAR-07:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.123311E+09 1768.63 07-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.158171E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.123311E+09 1810.73   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 652321.83 960.34 02-JAN-11:50 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 189590.33 251.69 27-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 149748.54 249.58 24-NOV-11:50 0.00 0.00 0.00 0.00 0.00
December 9013456.58 6525.48 07-DEC-09:15 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 10005117.28     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 9013456.58 6525.48   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 672533.33 2241.78 07-DEC-09:15 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 672533.33     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 672533.33 2241.78   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 114647.01 382.16 30-NOV-05:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 114647.01     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 114647.01 382.16   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 25624.55 0.48 07-JAN-01:10 0.00 0.00 0.00 0.00 0.00
February 18232.78 0.48 16-FEB-14:10 0.00 0.00 0.00 0.00 0.00
March 28479.89 0.48 29-MAR-14:20 0.00 0.00 0.00 0.00 0.00
April 46056.85 0.48 08-APR-15:10 0.00 0.00 0.00 0.00 0.00
May 51734.46 0.48 28-MAY-15:09 0.00 0.00 0.00 0.00 0.00
June 79239.35 0.48 01-JUN-12:40 0.00 0.00 0.00 0.00 0.00
July 36776.12 0.49 12-JUL-18:50 0.00 0.00 0.00 0.00 0.00
August 35302.66 0.49 09-AUG-22:00 0.00 0.00 0.00 0.00 0.00
September 19996.92 0.49 18-SEP-09:40 0.00 0.00 0.00 0.00 0.00
October 28439.27 0.49 24-OCT-10:08 0.00 0.00 0.00 0.00 0.00
November 31588.08 0.49 03-NOV-04:30 0.00 0.00 0.00 0.00 0.00
December 1778060.81 290.44 07-DEC-06:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2179531.73     0.00 0.00 0.00 0.00 0.00
Minimum of Months 18232.78 0.48   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1778060.81 290.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.402840E+09 8865.73 01-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.792870E+09 8765.13 12-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.535415E+09 8832.55 26-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 6208660.49 3551.82 17-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 4694949.98 3265.15 01-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 1427071.57 1742.76 13-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 2285459.35 3164.60 29-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 2733572.19 3185.48 05-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 3676049.12 3487.27 04-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 90116645.65 4958.53 25-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.291626E+09 6193.23 24-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.121702E+10 8909.59 07-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.335091E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1427071.57 1742.76   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.121702E+10 8909.59   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.930453E+09 8999.40 01-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.126601E+10 8851.77 09-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.747403E+09 8868.70 26-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 9904375.63 3720.75 10-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 4789297.36 3258.10 01-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 1149102.03 1515.03 13-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 2123958.03 3202.14 29-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 2894060.65 3075.21 05-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 4735547.83 3480.27 04-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 0.186387E+09 8794.46 25-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.637009E+09 8915.48 23-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.221473E+10 9014.35 07-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.600758E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1149102.03 1515.03   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.221473E+10 9014.35   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.288999E+10 50381.37 01-JAN-16:02 0.00 0.00 0.00 0.00 0.00
February 0.268435E+10 50140.35 03-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.165328E+10 50409.77 27-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.107028E+09 35170.21 26-APR-08:04 0.00 0.00 0.00 0.00 0.00
May 0.100388E+09 36856.50 15-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 15293331.77 15014.79 30-JUN-08:06 0.00 0.00 0.00 0.00 0.00
July 16908677.77 30059.96 27-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 25885691.78 35307.17 24-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 43976311.45 32108.48 29-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 0.357126E+09 31846.88 31-OCT-15:03 0.00 0.00 0.00 0.00 0.00
November 0.197147E+10 50491.28 24-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.797699E+10 51287.53 07-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.178427E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 15293331.77 15014.79   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.797699E+10 51287.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.459466E+09 3216.63 11-JAN-19:03 0.00 0.00 0.00 0.00 0.00
February 0.742644E+09 8528.54 12-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.498582E+09 5509.57 07-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 2873748.75 2969.44 29-APR-08:04 0.00 0.00 0.00 0.00 0.00
May 480500.61 2883.50 26-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 226008.05 1361.21 04-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 472461.69 1764.29 03-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 82314625.98 2623.21 30-OCT-18:04 0.00 0.00 0.00 0.00 0.00
November 0.340870E+09 4060.81 25-NOV-16:03 0.00 0.00 0.00 0.00 0.00
December 0.120480E+10 7905.81 11-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.333273E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.120480E+10 8528.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.949227E+09 8532.73 01-JAN-19:02 0.00 0.00 0.00 0.00 0.00
February 0.110035E+10 8536.14 04-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.673549E+09 6971.98 07-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 7039657.78 3050.74 29-APR-08:04 0.00 0.00 0.00 0.00 0.00
May 462936.15 2924.19 26-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 204349.69 1399.36 04-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 553020.20 1723.88 03-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 0.159928E+09 3676.40 25-OCT-15:03 0.00 0.00 0.00 0.00 0.00
November 0.679529E+09 6601.40 23-NOV-19:03 0.00 0.00 0.00 0.00 0.00
December 0.208912E+10 8591.45 07-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.565996E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.208912E+10 8591.45   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.249302E+09 2651.02 01-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.392381E+09 2617.16 12-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.270450E+09 2645.28 26-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 7487740.92 940.22 24-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 1248793.47 984.74 13-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 344943.43 488.87 13-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 596560.48 682.73 18-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 637468.56 811.59 05-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 1200810.65 798.91 30-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 74448379.70 2612.61 25-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.194843E+09 2632.40 23-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.558096E+09 2665.19 07-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.175104E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 344943.43 488.87   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.558096E+09 2665.19   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.470319E+09 2665.76 01-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.570425E+09 2641.22 09-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.356144E+09 2649.59 26-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 11111431.13 1034.91 24-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 1272030.34 898.95 13-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 257261.36 429.75 13-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 548524.47 732.65 29-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 677745.56 852.42 05-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 1364125.80 852.14 30-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 0.125048E+09 2631.35 25-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.351112E+09 2670.77 23-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.914896E+09 2670.80 16-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.280318E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 257261.36 429.75   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.914896E+09 2670.80   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.195551E+09 2712.92 02-JAN-09:03 0.00 0.00 0.00 0.00 0.00
February 0.622973E+09 12171.02 12-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.578964E+09 12260.62 27-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 16230530.26 4652.36 10-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 8945989.92 4561.60 08-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 6380589.07 4621.40 21-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 6480488.22 4917.46 24-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 7172625.81 4807.37 17-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 5112550.04 4342.85 29-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 70431001.96 4641.43 01-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 0.200365E+09 4040.59 24-NOV-09:03 0.00 0.00 0.00 0.00 0.00
December 0.761320E+09 4454.54 17-DEC-16:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.247993E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5112550.04 2712.92   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.761320E+09 12260.62   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.111591E+12 0.111136E+12 182073.33 31-JAN-16:40 182073.33 0.02
February 0.00 0.00 0.273384E+11 0.273197E+11 112153.73 18-FEB-14:00 112153.73 0.12
March 0.00 0.00 0.119887E+12 0.119887E+12 199609.91 20-MAR-18:10 199609.91 0.06
April 0.00 0.00 0.327386E+12 0.327386E+12 268555.58 14-APR-20:10 268555.58 0.03
May 0.00 0.00 0.425765E+12 0.425765E+12 280605.53 31-MAY-18:05 280605.53 0.01
June 0.00 0.00 0.544608E+12 0.543691E+12 350196.78 17-JUN-17:17 286583.90 0.25
July 0.00 0.00 0.633802E+12 0.555481E+12 421126.12 13-JUL-21:00 247784.56 0.80
August 0.00 0.00 0.616988E+12 0.546295E+12 452169.98 18-AUG-22:00 211422.77 0.86
September 0.00 0.00 0.565901E+12 0.489402E+12 482812.48 10-SEP-19:20 201188.21 0.86
October 0.00 0.00 0.290091E+12 0.281960E+12 347052.84 02-OCT-20:00 259729.68 0.26
November 0.00 0.00 0.128100E+12 0.113732E+12 207086.46 01-NOV-18:04 207086.46 0.21
December 0.00 0.00 0.605304E+11 0.605304E+11 162336.27 25-DEC-13:00 162336.27 0.00
                 
Annual Sum or Average 0.00 0.00 0.385199E+13 0.360258E+13       0.29
Minimum of Months 0.00 0.00 0.273384E+11 0.273197E+11 112153.73   112153.73 0.00
Maximum of Months 0.00 0.00 0.633802E+12 0.555481E+12 482812.48   286583.90 0.86



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.198588E+11 0.197255E+11 28113.38 31-JAN-16:01 28113.38 0.02
February 0.00 0.00 0.520638E+10 0.520638E+10 23245.80 18-FEB-14:00 23245.80 0.10
March 0.00 0.00 0.212817E+11 0.212817E+11 28620.15 16-MAR-15:02 28620.15 0.05
April 0.00 0.00 0.506605E+11 0.506605E+11 32711.12 14-APR-15:00 32711.12 0.01
May 0.00 0.00 0.642412E+11 0.642412E+11 33351.04 31-MAY-17:40 33351.04 0.01
June 0.00 0.00 0.748094E+11 0.747128E+11 41459.59 17-JUN-16:00 34470.08 0.11
July 0.00 0.00 0.886398E+11 0.766701E+11 50861.44 13-JUL-18:02 28087.03 0.77
August 0.00 0.00 0.877525E+11 0.756168E+11 53667.54 05-AUG-08:00 24051.13 0.85
September 0.00 0.00 0.820432E+11 0.691968E+11 57485.13 04-SEP-08:61 23263.16 0.79
October 0.00 0.00 0.443045E+11 0.428084E+11 45579.85 03-OCT-05:00 23302.79 0.25
November 0.00 0.00 0.227731E+11 0.196436E+11 43952.06 12-NOV-14:30 21062.33 0.21
December 0.00 0.00 0.111635E+11 0.111635E+11 26310.78 25-DEC-16:00 26310.78 0.00
                 
Annual Sum or Average 0.00 0.00 0.572735E+12 0.530927E+12       0.26
Minimum of Months 0.00 0.00 0.520638E+10 0.520638E+10 23245.80   21062.33 0.00
Maximum of Months 0.00 0.00 0.886398E+11 0.766701E+11 57485.13   34470.08 0.85



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.318585E+10 0.305643E+10 16162.35 14-JAN-16:02 16162.35 0.07
February 0.00 0.00 0.997826E+09 0.835567E+09 15395.95 22-FEB-16:01 15395.95 0.13
March 0.00 0.00 0.245727E+10 0.215335E+10 16192.18 18-MAR-15:02 16192.18 0.17
April 0.00 0.00 0.845913E+10 0.832734E+10 16191.97 25-APR-18:01 16191.97 0.05
May 0.00 0.00 0.101774E+11 0.101331E+11 16181.57 10-MAY-18:01 16181.57 0.01
June 0.00 0.00 0.134518E+11 0.128553E+11 16196.63 01-JUN-18:02 16196.63 0.23
July 0.00 0.00 0.132264E+11 0.973688E+10 17469.17 15-JUL-08:61 13934.53 0.76
August 0.00 0.00 0.129985E+11 0.931959E+10 17650.86 05-AUG-08:61 13043.49 0.83
September 0.00 0.00 0.112370E+11 0.768271E+10 18370.54 04-SEP-08:61 12525.80 0.86
October 0.00 0.00 0.685331E+10 0.574901E+10 16769.37 03-OCT-08:62 14228.45 0.31
November 0.00 0.00 0.329720E+10 0.272583E+10 16417.51 13-NOV-16:01 12616.22 0.24
December 0.00 0.00 0.148865E+10 0.148737E+10 16058.86 25-DEC-16:02 16058.86 0.00
                 
Annual Sum or Average 0.00 0.00 0.878304E+11 0.740625E+11       0.31
Minimum of Months 0.00 0.00 0.997826E+09 0.835567E+09 15395.95   12525.80 0.00
Maximum of Months 0.00 0.00 0.134518E+11 0.128553E+11 18370.54   16196.63 0.86



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.121057E+10 0.117117E+10 16047.37 14-JAN-16:02 16047.37 0.03
February 0.00 0.00 0.352383E+09 0.311162E+09 15286.06 22-FEB-16:01 15286.06 0.05
March 0.00 0.00 0.164078E+10 0.145187E+10 16076.28 18-MAR-15:02 16076.28 0.12
April 0.00 0.00 0.739021E+10 0.726509E+10 16077.28 25-APR-18:01 16077.28 0.05
May 0.00 0.00 0.989788E+10 0.985382E+10 16066.97 18-MAY-08:61 16066.97 0.01
June 0.00 0.00 0.136168E+11 0.130270E+11 16082.16 25-JUN-08:61 16082.16 0.23
July 0.00 0.00 0.131743E+11 0.971880E+10 17168.74 15-JUL-08:61 13943.59 0.76
August 0.00 0.00 0.123447E+11 0.870720E+10 17735.72 28-AUG-18:02 13236.04 0.82
September 0.00 0.00 0.100701E+11 0.660706E+10 18043.92 04-SEP-08:61 12524.42 0.85
October 0.00 0.00 0.496514E+10 0.396807E+10 16631.64 03-OCT-08:62 14033.86 0.29
November 0.00 0.00 0.153138E+10 0.115898E+10 16476.42 13-NOV-16:01 12415.39 0.18
December 0.00 0.00 0.386656E+09 0.386643E+09 15945.23 25-DEC-16:02 15945.23 0.00
                 
Annual Sum or Average 0.00 0.00 0.765810E+11 0.636268E+11       0.29
Minimum of Months 0.00 0.00 0.352383E+09 0.311162E+09 15286.06   12415.39 0.00
Maximum of Months 0.00 0.00 0.136168E+11 0.130270E+11 18043.92   16082.16 0.85



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.330584E+11 0.327276E+11 45145.39 14-JAN-13:50 45145.39 0.02
February 0.00 0.00 0.834135E+10 0.795809E+10 35316.13 01-FEB-15:30 35316.13 0.04
March 0.00 0.00 0.808011E+10 0.777595E+10 30489.27 18-MAR-13:50 27433.33 0.02
April 0.00 0.00 0.290360E+11 0.290317E+11 32671.32 14-APR-13:40 32671.32 0.00
May 0.00 0.00 0.290738E+11 0.290738E+11 25700.43 09-MAY-17:12 25700.43 0.00
June 0.00 0.00 0.436688E+11 0.417766E+11 34698.02 17-JUN-18:00 26448.78 0.10
July 0.00 0.00 0.464737E+11 0.291904E+11 33471.84 21-JUL-20:20 26336.85 0.76
August 0.00 0.00 0.496870E+11 0.318723E+11 42003.96 28-AUG-12:40 37111.84 0.82
September 0.00 0.00 0.496719E+11 0.341505E+11 45063.74 28-SEP-13:40 45063.74 0.76
October 0.00 0.00 0.389375E+11 0.339561E+11 46300.43 18-OCT-13:50 46300.43 0.25
November 0.00 0.00 0.264395E+11 0.246681E+11 47994.99 20-NOV-14:30 47994.99 0.13
December 0.00 0.00 0.225500E+11 0.225317E+11 44726.61 25-DEC-13:40 44726.61 0.00
                 
Annual Sum or Average 0.00 0.00 0.385018E+12 0.324713E+12       0.24
Minimum of Months 0.00 0.00 0.808011E+10 0.777595E+10 25700.43   25700.43 0.00
Maximum of Months 0.00 0.00 0.496870E+11 0.417766E+11 47994.99   47994.99 0.82



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.569310E+10 0.518570E+10 87479.22 27-JAN-16:01 87479.22 0.05
February 0.00 0.00 0.398629E+10 0.202577E+10 79923.10 18-FEB-09:02 70181.08 0.24
March 0.00 0.00 0.117544E+11 0.986548E+10 93212.72 15-MAR-18:01 93212.72 0.18
April 0.00 0.00 0.367336E+11 0.360688E+11 96908.64 25-APR-18:01 96908.64 0.05
May 0.00 0.00 0.525062E+11 0.522484E+11 96843.06 10-MAY-18:01 96843.06 0.01
June 0.00 0.00 0.744244E+11 0.712008E+11 96947.28 03-JUN-08:61 96947.28 0.21
July 0.00 0.00 0.787533E+11 0.598968E+11 97419.23 09-JUL-08:61 87295.41 0.68
August 0.00 0.00 0.715695E+11 0.514060E+11 112511.59 28-AUG-18:02 77107.39 0.72
September 0.00 0.00 0.607458E+11 0.411093E+11 105034.57 04-SEP-08:61 76762.94 0.73
October 0.00 0.00 0.285439E+11 0.230561E+11 96941.78 05-OCT-18:01 96941.78 0.24
November 0.00 0.00 0.893234E+10 0.574244E+10 88218.44 20-NOV-16:01 88218.44 0.20
December 0.00 0.00 0.212456E+10 0.210124E+10 78586.50 23-DEC-09:02 78586.50 0.00
                 
Annual Sum or Average 0.00 0.00 0.435767E+12 0.359907E+12       0.28
Minimum of Months 0.00 0.00 0.212456E+10 0.202577E+10 78586.50   70181.08 0.00
Maximum of Months 0.00 0.00 0.787533E+11 0.712008E+11 112511.59   96947.28 0.73



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.300043E+10 0.287421E+10 14127.94 14-JAN-16:02 14127.94 0.08
February 0.00 0.00 0.119198E+10 0.944717E+09 13457.26 22-FEB-16:01 13457.26 0.17
March 0.00 0.00 0.256296E+10 0.222209E+10 14154.34 18-MAR-15:02 14154.34 0.19
April 0.00 0.00 0.856871E+10 0.844488E+10 14154.55 25-APR-18:01 14154.55 0.06
May 0.00 0.00 0.105066E+11 0.104674E+11 14144.93 18-MAY-08:61 14144.93 0.02
June 0.00 0.00 0.137799E+11 0.133100E+11 14158.39 01-JUN-18:02 14158.39 0.24
July 0.00 0.00 0.141206E+11 0.108024E+11 14559.61 09-JUL-08:61 12493.44 0.78
August 0.00 0.00 0.137421E+11 0.102492E+11 15244.45 04-AUG-08:62 11045.27 0.85
September 0.00 0.00 0.116497E+11 0.823825E+10 15338.04 03-SEP-15:02 12119.84 0.88
October 0.00 0.00 0.712733E+10 0.606386E+10 14158.70 05-OCT-18:01 14158.70 0.33
November 0.00 0.00 0.301200E+10 0.253165E+10 14137.30 20-NOV-16:01 14137.30 0.23
December 0.00 0.00 0.150789E+10 0.150014E+10 14037.71 25-DEC-16:02 14037.71 0.00
                 
Annual Sum or Average 0.00 0.00 0.907702E+11 0.776487E+11       0.32
Minimum of Months 0.00 0.00 0.119198E+10 0.944717E+09 13457.26   11045.27 0.00
Maximum of Months 0.00 0.00 0.141206E+11 0.133100E+11 15338.04   14158.70 0.88



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.980001E+09 0.912336E+09 14024.96 31-JAN-16:01 14024.96 0.05
February 0.00 0.00 0.416123E+09 0.271522E+09 12502.41 22-FEB-16:01 12502.41 0.10
March 0.00 0.00 0.167905E+10 0.142803E+10 14055.31 18-MAR-15:02 14055.31 0.15
April 0.00 0.00 0.745111E+10 0.732987E+10 14056.83 25-APR-18:01 14056.83 0.06
May 0.00 0.00 0.102191E+11 0.101800E+11 14047.43 18-MAY-08:61 14047.43 0.02
June 0.00 0.00 0.139427E+11 0.134842E+11 14061.39 20-JUN-18:02 14061.39 0.24
July 0.00 0.00 0.140619E+11 0.107524E+11 14407.84 09-JUL-08:61 12437.50 0.78
August 0.00 0.00 0.130875E+11 0.955559E+10 15424.95 28-AUG-18:02 11618.59 0.84
September 0.00 0.00 0.104763E+11 0.707363E+10 15382.60 03-SEP-15:02 11943.24 0.88
October 0.00 0.00 0.513203E+10 0.413438E+10 14061.32 05-OCT-18:01 14061.32 0.31
November 0.00 0.00 0.126828E+10 0.963572E+09 14039.10 20-NOV-16:01 14039.10 0.17
December 0.00 0.00 0.326451E+09 0.324345E+09 13392.13 25-DEC-16:02 13392.13 0.00
                 
Annual Sum or Average 0.00 0.00 0.790405E+11 0.664100E+11       0.30
Minimum of Months 0.00 0.00 0.326451E+09 0.271522E+09 12502.41   11618.59 0.00
Maximum of Months 0.00 0.00 0.140619E+11 0.134842E+11 15424.95   14061.39 0.88



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.668588E+09 0.651825E+09 4291.11 14-JAN-16:02 4291.11 0.05
February 0.00 0.00 0.197808E+09 0.174850E+09 4087.64 22-FEB-16:01 4087.64 0.08
March 0.00 0.00 0.532917E+09 0.474895E+09 4299.10 18-MAR-15:02 4299.10 0.13
April 0.00 0.00 0.206197E+10 0.202866E+10 4298.94 25-APR-18:01 4298.94 0.05
May 0.00 0.00 0.254770E+10 0.253538E+10 4296.15 10-MAY-18:01 4296.15 0.02
June 0.00 0.00 0.353714E+10 0.337068E+10 4300.31 23-JUN-08:61 4300.31 0.23
July 0.00 0.00 0.345025E+10 0.252889E+10 4763.26 15-JUL-08:61 3623.09 0.76
August 0.00 0.00 0.336392E+10 0.240055E+10 4821.78 05-AUG-08:61 3351.78 0.83
September 0.00 0.00 0.282153E+10 0.189386E+10 5061.59 04-SEP-08:61 3122.53 0.86
October 0.00 0.00 0.157760E+10 0.130245E+10 4608.30 03-OCT-08:62 3654.01 0.30
November 0.00 0.00 0.672990E+09 0.566229E+09 4399.61 13-NOV-16:01 3325.22 0.18
December 0.00 0.00 0.301949E+09 0.301949E+09 4263.62 25-DEC-16:02 4263.62 0.00
                 
Annual Sum or Average 0.00 0.00 0.217344E+11 0.182302E+11       0.29
Minimum of Months 0.00 0.00 0.197808E+09 0.174850E+09 4087.64   3122.53 0.00
Maximum of Months 0.00 0.00 0.353714E+10 0.337068E+10 5061.59   4300.31 0.86



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.224364E+09 0.222246E+09 4257.25 14-JAN-16:02 4257.25 0.01
February 0.00 0.00 65767917.60 60179316.31 4055.27 22-FEB-16:01 4055.27 0.02
March 0.00 0.00 0.342457E+09 0.307900E+09 4265.22 18-MAR-15:02 4265.22 0.09
April 0.00 0.00 0.178731E+10 0.175653E+10 4265.25 25-APR-18:01 4265.25 0.05
May 0.00 0.00 0.247560E+10 0.246332E+10 4262.50 08-MAY-08:61 4262.50 0.02
June 0.00 0.00 0.357859E+10 0.341114E+10 4266.67 23-JUN-08:61 4266.67 0.23
July 0.00 0.00 0.343686E+10 0.252138E+10 4679.31 15-JUL-08:61 3623.32 0.76
August 0.00 0.00 0.319431E+10 0.223722E+10 4810.03 28-AUG-18:02 3446.86 0.83
September 0.00 0.00 0.251876E+10 0.161683E+10 4959.40 04-SEP-08:61 3122.19 0.85
October 0.00 0.00 0.111220E+10 0.864799E+09 4539.69 03-OCT-08:62 3545.38 0.27
November 0.00 0.00 0.275237E+09 0.216389E+09 4321.42 13-NOV-16:01 3206.60 0.12
December 0.00 0.00 71618469.97 71586019.37 4230.17 25-DEC-16:02 4230.17 0.00
                 
Annual Sum or Average 0.00 0.00 0.190831E+11 0.157495E+11       0.27
Minimum of Months 0.00 0.00 65767917.60 60179316.31 4055.27   3122.19 0.00
Maximum of Months 0.00 0.00 0.357859E+10 0.341114E+10 4959.40   4266.67 0.85



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.921552E+10 0.890466E+10 18831.10 14-JAN-16:02 18831.10 0.12
February 0.00 0.00 0.354369E+10 0.294074E+10 17934.76 22-FEB-16:01 17934.76 0.27
March 0.00 0.00 0.438053E+10 0.383740E+10 18863.86 18-MAR-15:02 18863.86 0.23
April 0.00 0.00 0.101656E+11 0.998560E+10 18864.30 25-APR-18:01 18864.30 0.06
May 0.00 0.00 0.108225E+11 0.107603E+11 18851.84 10-MAY-18:01 18851.84 0.02
June 0.00 0.00 0.146313E+11 0.137855E+11 18866.69 19-JUN-15:02 18866.69 0.26
July 0.00 0.00 0.160928E+11 0.118393E+11 20104.31 15-JUL-08:61 16426.91 0.76
August 0.00 0.00 0.166863E+11 0.121795E+11 21028.35 05-AUG-08:61 14962.70 0.83
September 0.00 0.00 0.159186E+11 0.114454E+11 21845.36 04-SEP-08:61 14378.11 0.89
October 0.00 0.00 0.117827E+11 0.103328E+11 19575.81 03-OCT-08:62 16590.65 0.33
November 0.00 0.00 0.807520E+10 0.720237E+10 18974.70 13-NOV-16:01 14756.69 0.27
December 0.00 0.00 0.660210E+10 0.658636E+10 18708.77 25-DEC-16:02 18708.77 0.00
                 
Annual Sum or Average 0.00 0.00 0.127917E+12 0.109800E+12       0.34
Minimum of Months 0.00 0.00 0.354369E+10 0.294074E+10 17934.76   14378.11 0.00
Maximum of Months 0.00 0.00 0.166863E+11 0.137855E+11 21845.36   18866.69 0.89



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:01 9048.62 125985.40 01-JAN-23:25
February 0.00 0.00 01-FEB-00:10 10224.37 116799.26 02-FEB-03:40
March 0.00 0.00 01-MAR-00:05 6630.43 121354.52 30-MAR-06:32
April 0.00 0.00 01-APR-00:10 280.11 91916.92 21-APR-03:56
May 0.00 0.00 01-MAY-00:10 63.03 43121.14 15-MAY-08:04
June 0.00 0.00 01-JUN-00:10 9.99 12704.33 30-JUN-08:06
July 0.00 0.00 01-JUL-00:10 10.94 24925.24 27-JUL-08:05
August 0.00 0.00 01-AUG-00:10 14.36 29949.04 24-AUG-08:04
September 0.00 0.00 01-SEP-00:10 22.95 29736.66 29-SEP-08:04
October 0.00 0.00 01-OCT-00:10 1987.15 113264.46 25-OCT-06:30
November 0.00 0.00 01-NOV-00:10 5827.58 122727.45 18-NOV-06:02
December 0.00 0.00 01-DEC-00:10 13708.56 155439.89 17-DEC-09:01
             
Annual Sum or Average 0.00     3961.25    
Minimum of Months 0.00 0.00   9.99 12704.33  
Maximum of Months 0.00 0.00   13708.56 155439.89  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 75181.67 420019.29 31-JAN-16:01 0.00 0.00 01-JAN-00:01
February 24892.27 257693.03 22-FEB-16:01 0.00 0.00 01-FEB-00:10
March 69670.52 426095.70 15-MAR-18:01 0.00 0.00 01-MAR-00:05
April 195349.90 498331.73 14-APR-18:03 0.00 0.00 01-APR-00:10
May 241294.02 508050.65 31-MAY-18:03 0.00 0.00 01-MAY-00:10
June 321300.91 581996.87 17-JUN-18:03 0.00 0.00 01-JUN-00:10
July 352809.58 669449.90 13-JUL-18:03 0.00 0.00 01-JUL-00:10
August 343917.45 618594.23 09-AUG-18:03 0.00 0.00 01-AUG-00:10
September 324872.72 663077.76 10-SEP-20:40 0.00 0.00 01-SEP-00:10
October 170508.07 557201.50 01-OCT-18:03 0.00 0.00 01-OCT-00:10
November 83821.30 423443.06 20-NOV-16:01 0.00 0.00 01-NOV-00:10
December 43787.44 371007.71 25-DEC-16:02 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 188135.78     0.00    
Minimum of Months 24892.27 257693.03   0.00 0.00  
Maximum of Months 352809.58 669449.90   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:01 23542.84 53917.80 23-JAN-07:55
February 0.00 0.00 01-FEB-00:10 23325.26 57289.21 08-FEB-07:01
March 0.00 0.00 01-MAR-00:05 22301.57 52072.06 25-MAR-07:11
April 0.00 0.00 01-APR-00:10 20648.91 43489.08 21-APR-06:25
May 0.00 0.00 01-MAY-00:10 18861.19 39398.86 01-MAY-07:00
June 0.00 0.00 01-JUN-00:10 17412.75 35832.23 01-JUN-06:50
July 0.00 0.00 01-JUL-00:10 16681.21 33439.17 03-JUL-06:10
August 0.00 0.00 01-AUG-00:10 16914.58 34388.99 31-AUG-07:00
September 0.00 0.00 01-SEP-00:10 17995.36 37196.95 29-SEP-07:00
October 0.00 0.00 01-OCT-00:10 19646.90 46691.92 13-OCT-06:55
November 0.00 0.00 01-NOV-00:10 21422.87 49574.57 04-NOV-07:41
December 0.00 0.00 01-DEC-00:10 22847.73 53735.86 29-DEC-08:61
             
Annual Sum or Average 0.00     20115.56    
Minimum of Months 0.00 0.00   16681.21 33439.17  
Maximum of Months 0.00 0.00   23542.84 57289.21  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.587890E+10 0.97 2194.93 01-JAN-00:01 0.97
February 0.530997E+10 0.96 2194.93 01-FEB-00:10 0.97
March 0.587890E+10 0.96 2194.93 01-MAR-00:05 0.96
April 0.568926E+10 0.97 2194.93 01-APR-00:10 0.97
May 0.587890E+10 0.97 2194.93 01-MAY-00:10 0.97
June 0.568926E+10 0.97 2194.93 01-JUN-00:10 0.97
July 0.587890E+10 0.96 2194.93 01-JUL-00:10 0.96
August 0.587890E+10 0.96 2194.93 01-AUG-00:10 0.96
September 0.568926E+10 0.96 2194.93 01-SEP-00:10 0.96
October 0.587890E+10 0.96 2194.93 01-OCT-00:10 0.96
November 0.568926E+10 0.96 2194.93 01-NOV-00:10 0.96
December 0.587890E+10 0.97 2194.93 01-DEC-00:10 0.97
           
Annual Sum or Average 0.692193E+11 0.96      
Minimum of Months 0.530997E+10 0.96 2194.93   0.96
Maximum of Months 0.587890E+10 0.97 2194.93   0.97



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.382663E+11 0.89 40133.88 13-JAN-04:03 1.65
February 0.322933E+11 0.85 39505.15 04-FEB-06:22 1.63
March 0.359654E+11 0.86 35201.07 24-MAR-05:03 1.52
April 0.390802E+11 0.92 36314.87 14-APR-21:10 1.55
May 0.424525E+11 0.94 34392.73 19-MAY-21:10 1.50
June 0.468266E+11 1.01 39952.11 29-JUN-21:10 1.64
July 0.489065E+11 1.01 42080.93 07-JUL-21:10 1.70
August 0.495433E+11 1.01 42998.31 25-AUG-21:10 1.72
September 0.478399E+11 1.01 44919.18 08-SEP-21:20 1.75
October 0.439060E+11 0.96 43342.79 06-OCT-21:10 1.73
November 0.390295E+11 0.91 39505.15 05-NOV-06:35 1.64
December 0.389823E+11 0.90 43350.20 04-DEC-22:45 1.74
           
Annual Sum or Average 0.503092E+12 0.94      
Minimum of Months 0.322933E+11 0.85 34392.73   1.50
Maximum of Months 0.495433E+11 1.01 44919.18   1.75



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.29 76.61 01-JAN-00:01 0.29
February 0.185347E+09 0.29 76.61 01-FEB-00:10 0.29
March 0.205205E+09 0.29 76.61 01-MAR-00:05 0.29
April 0.198586E+09 0.29 76.61 01-APR-00:10 0.29
May 0.205205E+09 0.29 76.61 01-MAY-00:10 0.29
June 0.198586E+09 0.29 76.61 01-JUN-00:10 0.29
July 0.205205E+09 0.29 76.61 01-JUL-00:10 0.29
August 0.205205E+09 0.29 76.61 01-AUG-00:10 0.29
September 0.198586E+09 0.29 76.61 01-SEP-00:10 0.29
October 0.205205E+09 0.29 76.61 01-OCT-00:10 0.29
November 0.198586E+09 0.29 76.61 01-NOV-00:10 0.29
December 0.205205E+09 0.29 76.61 01-DEC-00:10 0.29
           
Annual Sum or Average 0.241613E+10 0.29      
Minimum of Months 0.185347E+09 0.29 76.61   0.29
Maximum of Months 0.205205E+09 0.29 76.61   0.29



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:01 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:01 0.00
February 0.00 -0.0 0.00 01-FEB-00:10 0.00
March 0.00 -0.0 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:10 0.00
September 0.00 -0.0 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:10 0.00
December 0.00 -0.0 0.00 01-DEC-00:10 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:01 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:10 0.00
June 0.00 -0.0 0.00 01-JUN-00:10 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.21 612.92 01-JAN-07:10 0.29
February 0.105030E+10 0.21 612.92 01-FEB-07:05 0.29
March 0.116283E+10 0.21 612.92 01-MAR-07:03 0.29
April 0.112532E+10 0.21 612.92 01-APR-06:05 0.29
May 0.116283E+10 0.21 612.92 01-MAY-06:05 0.29
June 0.112532E+10 0.21 612.92 01-JUN-06:05 0.29
July 0.116283E+10 0.21 612.92 01-JUL-06:05 0.29
August 0.116283E+10 0.21 612.92 01-AUG-06:05 0.29
September 0.112532E+10 0.21 612.92 01-SEP-06:05 0.29
October 0.116283E+10 0.21 612.92 01-OCT-06:10 0.29
November 0.112532E+10 0.21 612.92 01-NOV-06:05 0.29
December 0.116283E+10 0.21 612.92 01-DEC-07:03 0.29
           
Annual Sum or Average 0.136914E+11 0.21      
Minimum of Months 0.105030E+10 0.21 612.92   0.29
Maximum of Months 0.116283E+10 0.21 612.92   0.29



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.236186E+09 0.54 866.85 01-JAN-09:01 0.63
February 0.141488E+09 0.47 866.85 01-FEB-16:01 0.64
March 0.206697E+09 0.50 866.85 02-MAR-16:01 0.63
April 0.469260E+09 0.59 866.85 01-APR-15:02 0.64
May 0.546529E+09 0.60 866.85 01-MAY-15:02 0.64
June 0.735934E+09 0.61 866.85 01-JUN-08:61 0.63
July 0.655451E+09 0.61 866.85 01-JUL-08:61 0.64
August 0.648081E+09 0.60 866.85 01-AUG-08:62 0.63
September 0.557966E+09 0.60 866.85 01-SEP-08:61 0.63
October 0.389041E+09 0.56 866.85 01-OCT-08:61 0.63
November 0.226495E+09 0.53 866.85 01-NOV-15:02 0.63
December 0.194213E+09 0.51 866.85 01-DEC-16:01 0.64
           
Annual Sum or Average 0.500734E+10 0.56      
Minimum of Months 0.141488E+09 0.47 866.85   0.63
Maximum of Months 0.735934E+09 0.61 866.85   0.64



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.160371E+09 0.47 860.68 01-JAN-09:01 0.63
February 0.134110E+09 0.45 860.68 01-FEB-16:01 0.64
March 0.172905E+09 0.47 860.68 02-MAR-16:01 0.63
April 0.416655E+09 0.57 860.68 01-APR-15:02 0.64
May 0.533353E+09 0.60 860.68 01-MAY-15:02 0.64
June 0.748730E+09 0.61 860.68 01-JUN-08:61 0.63
July 0.653571E+09 0.61 860.68 01-JUL-08:61 0.64
August 0.612514E+09 0.60 860.68 01-AUG-08:62 0.63
September 0.499398E+09 0.59 860.68 01-SEP-08:61 0.63
October 0.297687E+09 0.53 860.68 01-OCT-08:61 0.63
November 0.154292E+09 0.48 860.68 01-NOV-15:02 0.63
December 0.187906E+09 0.46 860.68 01-DEC-16:01 0.64
           
Annual Sum or Average 0.457149E+10 0.54      
Minimum of Months 0.134110E+09 0.45 860.68   0.63
Maximum of Months 0.748730E+09 0.61 860.68   0.64



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.165812E+10 0.40 2490.83 09-JAN-13:30 0.63
February 0.447801E+09 0.18 2031.75 01-FEB-15:30 0.64
March 0.438743E+09 0.20 1412.22 18-MAR-13:50 0.63
April 0.140077E+10 0.49 1364.09 14-APR-13:40 0.64
May 0.143711E+10 0.53 1118.19 09-MAY-17:12 0.64
June 0.204475E+10 0.63 1525.20 28-JUN-18:10 0.63
July 0.202667E+10 0.62 1345.41 11-JUL-17:13 0.63
August 0.213085E+10 0.62 2136.36 28-AUG-12:30 0.63
September 0.215988E+10 0.61 2654.64 28-SEP-12:20 0.63
October 0.187735E+10 0.50 2728.68 05-OCT-14:50 0.63
November 0.132627E+10 0.37 2557.88 15-NOV-14:10 0.63
December 0.115578E+10 0.33 2274.48 28-DEC-13:30 0.64
           
Annual Sum or Average 0.181041E+11 0.46      
Minimum of Months 0.438743E+09 0.18 1118.19   0.63
Maximum of Months 0.215988E+10 0.63 2728.68   0.64



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.719047E+09 0.45 5135.32 01-JAN-16:02 0.64
February 0.578115E+09 0.45 5135.32 03-FEB-09:02 0.63
March 0.958643E+09 0.45 5135.32 04-MAR-09:02 0.63
April 0.207100E+10 0.46 5135.32 01-APR-08:62 0.64
May 0.291514E+10 0.49 5135.32 01-MAY-08:62 0.64
June 0.418202E+10 0.56 5135.32 01-JUN-08:61 0.63
July 0.396303E+10 0.55 5135.32 01-JUL-08:61 0.64
August 0.353316E+10 0.53 5135.32 01-AUG-08:62 0.63
September 0.305299E+10 0.50 5135.32 01-SEP-08:61 0.63
October 0.163411E+10 0.46 5135.32 01-OCT-08:61 0.63
November 0.779419E+09 0.45 5135.32 01-NOV-15:02 0.63
December 0.840244E+09 0.45 5135.32 04-DEC-09:01 0.63
           
Annual Sum or Average 0.252269E+11 0.48      
Minimum of Months 0.578115E+09 0.45 5135.32   0.63
Maximum of Months 0.418202E+10 0.56 5135.32   0.64



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.220902E+09 0.55 757.32 01-JAN-16:02 0.64
February 0.139309E+09 0.48 757.32 01-FEB-09:02 0.63
March 0.200891E+09 0.52 757.32 01-MAR-16:02 0.63
April 0.474168E+09 0.62 757.32 01-APR-08:62 0.63
May 0.566120E+09 0.62 757.32 01-MAY-08:62 0.64
June 0.758718E+09 0.63 757.32 01-JUN-08:61 0.63
July 0.710089E+09 0.62 757.32 01-JUL-08:61 0.64
August 0.681809E+09 0.62 757.32 01-AUG-08:62 0.63
September 0.582114E+09 0.61 757.32 01-SEP-08:61 0.63
October 0.402773E+09 0.59 757.32 01-OCT-08:61 0.63
November 0.209755E+09 0.54 757.32 01-NOV-15:02 0.63
December 0.181885E+09 0.51 757.32 01-DEC-09:02 0.63
           
Annual Sum or Average 0.512853E+10 0.58      
Minimum of Months 0.139309E+09 0.48 757.32   0.63
Maximum of Months 0.758718E+09 0.63 757.32   0.64



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.139246E+09 0.45 752.05 01-JAN-16:02 0.64
February 0.116295E+09 0.45 752.05 04-FEB-09:02 0.63
March 0.161841E+09 0.48 752.05 02-MAR-09:02 0.63
April 0.418523E+09 0.61 752.05 01-APR-08:62 0.63
May 0.554044E+09 0.62 752.05 01-MAY-08:62 0.64
June 0.771075E+09 0.63 752.05 01-JUN-08:61 0.63
July 0.709241E+09 0.62 752.05 01-JUL-08:61 0.64
August 0.648717E+09 0.62 752.05 01-AUG-08:62 0.63
September 0.522186E+09 0.61 752.05 01-SEP-08:61 0.63
October 0.300094E+09 0.54 752.05 01-OCT-08:61 0.63
November 0.134544E+09 0.46 752.05 01-NOV-15:02 0.63
December 0.161774E+09 0.45 752.05 01-DEC-16:01 0.64
           
Annual Sum or Average 0.463758E+10 0.54      
Minimum of Months 0.116295E+09 0.45 752.05   0.63
Maximum of Months 0.771075E+09 0.63 752.05   0.64



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 60988039.00 0.52 230.19 01-JAN-09:01 0.63
February 42830433.00 0.47 230.19 01-FEB-16:01 0.64
March 54637009.01 0.49 230.19 02-MAR-16:01 0.63
April 0.115511E+09 0.59 230.19 01-APR-15:02 0.64
May 0.137698E+09 0.60 230.19 01-MAY-15:02 0.64
June 0.194363E+09 0.61 230.19 01-JUN-08:61 0.63
July 0.171581E+09 0.61 230.19 01-JUL-08:61 0.64
August 0.168602E+09 0.60 230.19 01-AUG-08:62 0.63
September 0.141119E+09 0.60 230.19 01-SEP-08:61 0.63
October 93933368.65 0.56 230.19 01-OCT-08:61 0.63
November 56250419.86 0.52 230.19 01-NOV-15:02 0.63
December 56864164.82 0.50 230.19 01-DEC-16:01 0.64
           
Annual Sum or Average 0.129438E+10 0.56      
Minimum of Months 42830433.00 0.47 230.19   0.63
Maximum of Months 0.194363E+09 0.61 230.19   0.64



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 48187928.64 0.47 228.37 01-JAN-09:01 0.63
February 44697644.13 0.45 228.37 01-FEB-09:02 0.63
March 48172082.42 0.47 228.37 02-MAR-16:01 0.63
April 0.102245E+09 0.57 228.37 01-APR-15:02 0.64
May 0.134392E+09 0.60 228.37 01-MAY-15:02 0.64
June 0.197428E+09 0.61 228.37 01-JUN-08:61 0.63
July 0.171307E+09 0.61 228.37 01-JUL-08:61 0.64
August 0.159718E+09 0.60 228.37 01-AUG-08:62 0.63
September 0.126051E+09 0.59 228.37 01-SEP-08:61 0.63
October 72767385.66 0.52 228.37 01-OCT-08:61 0.63
November 43425083.89 0.47 228.37 01-NOV-15:02 0.63
December 61041999.87 0.46 228.37 01-DEC-09:02 0.63
           
Annual Sum or Average 0.120943E+10 0.54      
Minimum of Months 43425083.89 0.45 228.37   0.63
Maximum of Months 0.197428E+09 0.61 228.37   0.64



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.540273E+09 0.58 1008.39 01-JAN-16:02 0.64
February 0.265531E+09 0.53 1008.39 01-FEB-16:01 0.64
March 0.313564E+09 0.53 1008.39 01-MAR-16:02 0.63
April 0.561678E+09 0.59 1008.39 01-APR-15:02 0.64
May 0.593198E+09 0.59 1008.39 01-MAY-15:02 0.64
June 0.798053E+09 0.60 1008.39 01-JUN-08:61 0.63
July 0.789734E+09 0.60 1008.39 01-JUL-08:61 0.64
August 0.824320E+09 0.60 1008.39 01-AUG-08:62 0.63
September 0.809253E+09 0.60 1008.39 01-SEP-08:61 0.63
October 0.659760E+09 0.59 1008.39 01-OCT-08:61 0.63
November 0.475323E+09 0.56 1008.39 01-NOV-15:02 0.63
December 0.432973E+09 0.57 1008.39 01-DEC-09:02 0.63
           
Annual Sum or Average 0.706366E+10 0.58      
Minimum of Months 0.265531E+09 0.53 1008.39   0.63
Maximum of Months 0.824320E+09 0.60 1008.39   0.64



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.175403E+09 0.157862E+09 595.66 01-JAN-09:01 536.10 536.10 60.49 0.98
February 0.199052E+09 0.179147E+09 552.11 25-FEB-05:23 496.90 496.90 47.49 0.85
March 0.135416E+09 0.121874E+09 530.01 25-MAR-04:50 477.01 477.01 44.54 0.80
April 5736604.71 5162944.24 425.37 21-APR-03:56 382.83 382.83 41.21 0.57
May 1414150.41 1272735.37 331.42 25-MAY-08:04 298.28 298.28 55.14 0.41
June 287818.09 259036.28 140.26 30-JUN-08:06 126.23 126.23 59.40 0.15
July 341861.26 307675.14 266.48 27-JUL-08:05 239.83 239.83 60.30 0.31
August 432580.99 389322.89 302.88 24-AUG-08:04 272.59 272.59 59.73 0.36
September 641170.87 577053.79 274.93 29-SEP-08:04 247.44 247.44 57.47 0.32
October 40141074.25 36126966.82 533.85 26-OCT-03:55 480.47 480.47 67.19 0.80
November 0.118413E+09 0.106571E+09 546.80 18-NOV-06:17 492.12 492.12 56.33 0.84
December 0.290068E+09 0.261061E+09 581.02 07-DEC-23:26 522.91 522.91 48.30 0.94
                 
Annual Sum or Average 0.967346E+09 0.870611E+09            
Minimum of Months 287818.09 259036.28 140.26   126.23 126.23 41.21 0.15
Maximum of Months 0.290068E+09 0.261061E+09 595.66   536.10 536.10 67.19 0.98



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.393767E+10 0.354390E+10 4265.02 27-JAN-16:01 3838.51 3838.51 6.73 11.17
February 0.171099E+10 0.153989E+10 4201.53 18-FEB-16:01 3781.37 3781.37 7.46 10.79
March 0.356961E+10 0.321265E+10 4711.12 17-MAR-18:03 4240.00 4240.00 7.11 14.79
April 0.756861E+10 0.681175E+10 4820.63 25-APR-19:00 4338.56 4338.56 6.73 16.15
May 0.885659E+10 0.797093E+10 4685.52 29-MAY-20:50 4216.97 4216.97 6.73 14.51
June 0.103268E+11 0.929411E+10 5219.27 28-JUN-18:50 4697.34 4697.34 6.73 22.41
July 0.112194E+11 0.100974E+11 5009.09 13-JUL-18:03 4508.18 4508.18 6.84 19.14
August 0.111671E+11 0.100504E+11 5081.05 27-AUG-18:02 4572.94 4572.94 6.73 20.35
September 0.106386E+11 0.957475E+10 5051.46 10-SEP-19:20 4546.32 4546.32 7.30 19.86
October 0.714994E+10 0.643494E+10 4989.10 05-OCT-19:20 4490.19 4490.19 6.73 18.79
November 0.429500E+10 0.386550E+10 4848.09 01-NOV-18:03 4363.28 4363.28 7.17 16.53
December 0.249017E+10 0.224116E+10 4060.87 23-DEC-16:02 3654.78 3654.78 7.31 10.03
                 
Annual Sum or Average 0.829304E+11 0.746374E+11            
Minimum of Months 0.171099E+10 0.153989E+10 4060.87   3654.78 3654.78 6.73 10.03
Maximum of Months 0.112194E+11 0.100974E+11 5219.27   4697.34 4697.34 7.46 22.41



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.102440E+11 0.921960E+10 4362.97 01-JAN-00:06 3926.68 3926.68 8.40 30.58
February 0.783407E+10 0.705066E+10 4362.97 01-FEB-00:10 3926.68 3926.68 8.50 30.58
March 0.985425E+10 0.886883E+10 4362.97 01-MAR-00:05 3926.68 3926.68 8.42 30.58
April 0.112840E+11 0.101556E+11 4362.97 01-APR-00:10 3926.68 3926.68 8.53 30.58
May 0.116858E+11 0.105172E+11 4362.97 01-MAY-00:10 3926.68 3926.68 8.78 30.58
June 0.113088E+11 0.101779E+11 4362.97 01-JUN-00:10 3926.68 3926.68 8.73 30.58
July 0.116858E+11 0.105172E+11 4362.97 01-JUL-00:10 3926.68 3926.68 9.02 30.58
August 0.116858E+11 0.105172E+11 4362.97 01-AUG-00:10 3926.68 3926.68 9.25 30.58
September 0.113088E+11 0.101779E+11 4362.97 01-SEP-00:10 3926.68 3926.68 8.82 30.58
October 0.112630E+11 0.101367E+11 4362.97 01-OCT-00:10 3926.68 3926.68 8.87 30.58
November 0.101162E+11 0.910459E+10 4362.97 01-NOV-00:10 3926.68 3926.68 8.67 30.58
December 0.892959E+10 0.803663E+10 4362.97 01-DEC-00:10 3926.68 3926.68 8.41 30.58
                 
Annual Sum or Average 0.127200E+12 0.114480E+12            
Minimum of Months 0.783407E+10 0.705066E+10 4362.97   3926.68 3926.68 8.40 30.58
Maximum of Months 0.116858E+11 0.105172E+11 4362.97   3926.68 3926.68 9.25 30.58



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:01 14.37 14.37 42.94 0.08
February 0.115896E+09 34768898.54 47.91 01-FEB-00:10 14.37 14.37 50.42 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:05 14.37 14.37 51.06 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 53.67 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:10 14.37 14.37 54.10 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:10 14.37 14.37 54.19 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 54.48 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:10 14.37 14.37 54.24 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:10 14.37 14.37 54.50 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 53.25 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:10 14.37 14.37 53.53 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:10 14.37 14.37 49.35 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 42.94 0.08
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 54.50 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:01 49.75 80.36 9048.62 125985.40 01-JAN-23:25
February 0.00 0.00 01-FEB-00:10 57.46 79.40 10224.37 116799.26 02-FEB-03:40
March 0.00 0.00 01-MAR-00:05 57.90 79.40 6630.43 121354.52 30-MAR-06:32
April 0.00 0.00 01-APR-00:10 64.80 79.40 280.11 91916.92 21-APR-03:56
May 0.00 0.00 01-MAY-00:10 48.33 48.33 63.03 43121.14 15-MAY-08:04
June 0.00 0.00 01-JUN-00:10 57.61 57.61 9.99 12704.33 30-JUN-08:06
July 0.00 0.00 01-JUL-00:10 59.28 59.28 10.94 24925.24 27-JUL-08:05
August 0.00 0.00 01-AUG-00:10 60.21 60.21 14.36 29949.04 24-AUG-08:04
September 0.00 0.00 01-SEP-00:10 58.31 58.31 22.95 29736.66 29-SEP-08:04
October 0.00 0.00 01-OCT-00:10 57.22 57.22 1987.15 113264.46 25-OCT-06:30
November 0.00 0.00 01-NOV-00:10 51.62 51.62 5827.58 122727.45 18-NOV-06:02
December 0.00 0.00 01-DEC-00:10 46.24 79.53 13708.56 155439.89 17-DEC-09:01
                 
Annual Sum or Average 0.00         3961.25    
Minimum of Months 0.00 0.00   46.24 48.33 9.99 12704.33  
Maximum of Months 0.00 0.00   64.80 80.36 13708.56 155439.89  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 75181.67 420019.29 31-JAN-16:01 9.98 6.70 0.00 0.00 01-JAN-00:01
February 24892.27 257693.03 22-FEB-16:01 9.59 7.58 0.00 0.00 01-FEB-00:10
March 69670.52 426095.70 15-MAR-18:01 10.05 6.72 0.00 0.00 01-MAR-00:05
April 195349.90 498331.73 14-APR-18:03 10.59 6.70 0.00 0.00 01-APR-00:10
May 241294.02 508050.65 31-MAY-18:03 10.67 6.70 0.00 0.00 01-MAY-00:10
June 321300.91 581996.87 17-JUN-18:03 11.24 6.70 0.00 0.00 01-JUN-00:10
July 352809.58 669449.90 13-JUL-18:03 12.03 6.81 0.00 0.00 01-JUL-00:10
August 343917.45 618594.23 09-AUG-18:03 11.73 6.91 0.00 0.00 01-AUG-00:10
September 324872.72 663077.76 10-SEP-20:40 12.39 7.21 0.00 0.00 01-SEP-00:10
October 170508.07 557201.50 01-OCT-18:03 11.05 6.70 0.00 0.00 01-OCT-00:10
November 83821.30 423443.06 20-NOV-16:01 10.00 6.70 0.00 0.00 01-NOV-00:10
December 43787.44 371007.71 25-DEC-16:02 9.75 6.86 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 188135.78         0.00    
Minimum of Months 24892.27 257693.03   9.59 6.70 0.00 0.00  
Maximum of Months 352809.58 669449.90   12.39 7.58 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:01 42.94 59.97 23542.84 53917.80 23-JAN-07:55
February 0.00 0.00 01-FEB-00:10 50.42 58.44 23325.26 57289.21 08-FEB-07:01
March 0.00 0.00 01-MAR-00:05 51.06 59.77 22301.57 52072.06 25-MAR-07:11
April 0.00 0.00 01-APR-00:10 53.67 59.57 20648.91 43489.08 21-APR-06:25
May 0.00 0.00 01-MAY-00:10 54.10 59.36 18861.19 39398.86 01-MAY-07:00
June 0.00 0.00 01-JUN-00:10 54.19 58.72 17412.75 35832.23 01-JUN-06:50
July 0.00 0.00 01-JUL-00:10 54.48 58.69 16681.21 33439.17 03-JUL-06:10
August 0.00 0.00 01-AUG-00:10 54.24 58.32 16914.58 34388.99 31-AUG-07:00
September 0.00 0.00 01-SEP-00:10 54.50 58.86 17995.36 37196.95 29-SEP-07:00
October 0.00 0.00 01-OCT-00:10 53.25 58.54 19646.90 46691.92 13-OCT-06:55
November 0.00 0.00 01-NOV-00:10 53.53 58.80 21422.87 49574.57 04-NOV-07:41
December 0.00 0.00 01-DEC-00:10 49.35 59.19 22847.73 53735.86 29-DEC-08:61
                 
Annual Sum or Average 0.00         20115.56    
Minimum of Months 0.00 0.00   42.94 58.32 16681.21 33439.17  
Maximum of Months 0.00 0.00   54.50 59.97 23542.84 57289.21  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.180079E+11 0.00 0.111591E+12 0.382663E+11 0.00 0.00
February 0.168547E+11 0.00 0.273384E+11 0.322933E+11 0.00 0.00
March 0.126537E+11 0.00 0.119887E+12 0.359654E+11 0.00 0.00
April 0.579522E+09 0.00 0.327386E+12 0.390802E+11 0.00 0.00
May 41198910.07 0.00 0.425765E+12 0.424525E+11 0.00 0.00
June 0.00 0.00 0.544608E+12 0.468266E+11 0.00 0.00
July 0.00 0.00 0.633802E+12 0.489065E+11 0.00 0.00
August 0.00 0.00 0.616988E+12 0.495433E+11 0.00 0.00
September 0.00 0.00 0.565901E+12 0.478399E+11 0.00 0.00
October 0.424083E+10 0.00 0.290091E+12 0.439060E+11 0.00 0.00
November 0.106409E+11 0.00 0.128100E+12 0.390295E+11 0.00 0.00
December 0.202185E+11 0.00 0.605304E+11 0.389823E+11 0.00 0.00
             
Annual Sum or Average 0.832373E+11 0.00 0.385199E+13 0.503092E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.273384E+11 0.322933E+11 0.00 0.00
Maximum of Months 0.202185E+11 0.00 0.633802E+12 0.495433E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 25624.55 0.00 0.198588E+11 0.587890E+10 0.00 0.00
February 18232.78 0.00 0.520638E+10 0.530997E+10 0.00 0.00
March 28479.89 0.00 0.212817E+11 0.587890E+10 0.00 0.00
April 46056.85 0.00 0.506605E+11 0.568926E+10 0.00 0.00
May 51734.46 0.00 0.642412E+11 0.587890E+10 0.00 0.00
June 79239.35 0.00 0.748094E+11 0.568926E+10 0.00 0.00
July 36776.12 0.00 0.886398E+11 0.587890E+10 0.00 0.00
August 35302.66 0.00 0.877525E+11 0.587890E+10 0.00 0.00
September 19996.92 0.00 0.820432E+11 0.568926E+10 0.00 0.00
October 28439.27 0.00 0.443045E+11 0.587890E+10 0.00 0.00
November 31588.08 0.00 0.227731E+11 0.568926E+10 0.00 0.00
December 1778060.81 0.00 0.111635E+11 0.587890E+10 0.00 0.00
             
Annual Sum or Average 2179531.73 0.00 0.572735E+12 0.692193E+11 0.00 0.00
Minimum of Months 18232.78 0.00 0.520638E+10 0.530997E+10 0.00 0.00
Maximum of Months 1778060.81 0.00 0.886398E+11 0.587890E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.382663E+11 0.111591E+12 0.180079E+11 0.626832E+11 0.180479E+09 0.00 0.00 0.00
February 0.322933E+11 0.273384E+11 0.168547E+11 0.573358E+11 0.00 0.00 0.00 0.00
March 0.359654E+11 0.119887E+12 0.126537E+11 0.636390E+11 0.741913E+09 0.00 0.00 0.00
April 0.390802E+11 0.327386E+12 0.579522E+09 0.143127E+11 0.202275E+11 0.00 0.00 0.00
May 0.424525E+11 0.425765E+12 41198910.07 0.140224E+11 0.403727E+11 0.00 0.00 0.00
June 0.468266E+11 0.544608E+12 0.00 0.233470E+11 0.875669E+11 0.00 0.00 0.00
July 0.489065E+11 0.633802E+12 0.00 0.118824E+11 0.119501E+12 0.00 0.00 0.00
August 0.495433E+11 0.616988E+12 0.00 0.132408E+11 0.101743E+12 0.00 0.00 0.00
September 0.478399E+11 0.565901E+12 0.00 0.103540E+11 0.713707E+11 0.00 0.00 0.00
October 0.439060E+11 0.290091E+12 0.424083E+10 0.194493E+11 0.176574E+11 0.00 0.00 0.00
November 0.390295E+11 0.128100E+12 0.106409E+11 0.447402E+11 0.379828E+09 0.00 0.00 0.00
December 0.389823E+11 0.605308E+11 0.202185E+11 0.116911E+12 6155976.13 0.00 0.00 0.00
                 
Annual Sum or Average 0.503092E+12 0.385199E+13 0.832373E+11 0.451918E+12 0.459748E+12 0.00 0.00 0.00
Minimum of Months 0.322933E+11 0.273384E+11 0.00 0.103540E+11 0.00 0.00 0.00 0.00
Maximum of Months 0.495433E+11 0.633802E+12 0.202185E+11 0.116911E+12 0.119501E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.587890E+10 0.198588E+11 25624.55 0.171621E+11 0.289273E+09 0.00 0.00 0.00
February 0.530997E+10 0.520638E+10 18232.78 0.165585E+11 0.00 0.00 0.00 0.00
March 0.587890E+10 0.212817E+11 28479.89 0.146035E+11 0.714940E+09 0.00 0.00 0.00
April 0.568926E+10 0.506605E+11 46056.85 0.142867E+10 0.915828E+10 0.00 0.00 0.00
May 0.587890E+10 0.642412E+11 51734.46 0.681966E+09 0.157162E+11 0.00 0.00 0.00
June 0.568926E+10 0.748094E+11 79239.35 0.572388E+09 0.305639E+11 0.00 0.00 0.00
July 0.587890E+10 0.886398E+11 36776.12 0.193673E+09 0.496475E+11 0.00 0.00 0.00
August 0.587890E+10 0.877525E+11 35302.66 0.149604E+09 0.454658E+11 0.00 0.00 0.00
September 0.568926E+10 0.820432E+11 19996.92 0.163399E+09 0.348908E+11 0.00 0.00 0.00
October 0.587890E+10 0.443045E+11 28439.27 0.448714E+10 0.933773E+10 0.00 0.00 0.00
November 0.568926E+10 0.227731E+11 31588.08 0.130885E+11 0.633656E+09 0.00 0.00 0.00
December 0.587890E+10 0.111635E+11 1778060.81 0.293742E+11 0.129186E+09 0.00 0.00 0.00
                 
Annual Sum or Average 0.692193E+11 0.572735E+12 2179531.73 0.984636E+11 0.196547E+12 0.00 0.00 0.00
Minimum of Months 0.530997E+10 0.520638E+10 18232.78 0.149604E+09 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.886398E+11 1778060.81 0.293742E+11 0.496475E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.382663E+11 0.180079E+11 0.111591E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.322933E+11 0.168547E+11 0.273384E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.359654E+11 0.126537E+11 0.119887E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.390802E+11 0.579522E+09 0.327386E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.424525E+11 41198910.07 0.425765E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.468266E+11 0.00 0.544608E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.489065E+11 0.00 0.633802E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.495433E+11 0.00 0.616988E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.478399E+11 0.00 0.565901E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.439060E+11 0.424083E+10 0.290091E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.390295E+11 0.106409E+11 0.128100E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.389823E+11 0.202185E+11 0.605304E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.503092E+12 0.832373E+11 0.385199E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.322933E+11 0.00 0.273384E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.495433E+11 0.202185E+11 0.633802E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.587890E+10 25624.55 0.198588E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.530997E+10 18232.78 0.520638E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.587890E+10 28479.89 0.212817E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.568926E+10 46056.85 0.506605E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.587890E+10 51734.46 0.642412E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.568926E+10 79239.35 0.748094E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.587890E+10 36776.12 0.886398E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.587890E+10 35302.66 0.877525E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.568926E+10 19996.92 0.820432E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.587890E+10 28439.27 0.443045E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.568926E+10 31588.08 0.227731E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.587890E+10 1778060.81 0.111635E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.692193E+11 2179531.73 0.572735E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.530997E+10 18232.78 0.520638E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 1778060.81 0.886398E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.256940E+09 343715.52 0.00 84379623.67 0.00 0.00 0.438171E+11 0.00 1.04
February 0.114629E+11 0.00 0.00 26956475.93 0.00 0.00 0.273522E+11 0.00 0.92
March 0.250658E+11 0.00 0.00 6651239.01 8212504.46 0.00 0.844746E+10 0.00 0.89
April 0.297322E+10 2943224.53 0.00 17717411.31 0.491529E+09 0.00 0.145409E+11 0.00 0.85
May 0.863588E+10 5962574.36 0.00 7023635.55 0.116583E+10 0.00 0.322587E+10 0.00 0.80
June 0.346333E+09 0.305877E+09 0.00 14030794.63 0.271907E+10 0.00 0.483821E+10 0.00 0.75
July 4125043.17 0.629983E+10 0.00 23552541.19 0.188468E+09 0.00 0.286343E+10 0.00 0.86
August 0.00 0.557549E+10 0.00 32301442.76 3799918.69 0.00 0.406348E+10 0.00 0.96
September 0.00 0.593628E+10 0.00 42681774.53 0.00 0.00 0.747736E+10 0.00 1.13
October 0.00 0.780067E+09 0.00 94498026.42 0.00 0.00 0.357162E+11 0.00 1.28
November 9304490.09 18292047.79 0.00 0.110097E+09 0.00 0.00 0.502561E+11 0.00 1.31
December 5350148.29 0.00 0.00 0.128086E+09 0.00 0.00 0.573562E+11 0.00 1.21
                   
Annual Sum or Average 0.487598E+11 0.189251E+11 0.00 0.587976E+09 0.457691E+10 0.00 0.259954E+12 0.00 1.00
Minimum of Months 0.00 0.00 0.00 6651239.01 0.00 0.00 0.286343E+10 0.00 0.75
Maximum of Months 0.250658E+11 0.629983E+10 0.00 0.128086E+09 0.271907E+10 0.00 0.573562E+11 0.00 1.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.192491E+10 99367.74 0.00 6183970.47 0.00 0.00 0.195439E+10 0.00 2.12
February 0.271302E+10 0.00 0.00 1576221.37 0.00 3365644.32 0.999519E+09 0.00 1.65
March 0.247556E+10 1157829.84 0.00 2387606.88 0.00 28157705.57 0.750674E+09 0.00 1.67
April 0.604206E+09 0.106162E+09 0.00 5450541.39 0.00 0.00 0.121407E+10 0.00 2.07
May 0.172664E+09 0.215248E+09 0.00 4870090.44 0.00 0.00 0.108316E+10 0.00 1.98
June 0.00 0.613058E+09 0.00 4859481.38 0.00 0.00 0.667083E+09 0.00 2.27
July 238032.56 0.100108E+10 0.00 2681573.48 0.00 0.00 0.303674E+09 0.00 2.16
August 13818290.92 0.904590E+09 0.00 3046790.83 6278.88 0.00 0.352379E+09 0.00 2.24
September 18215800.00 0.758661E+09 0.00 3560000.19 0.00 0.00 0.531677E+09 0.00 2.27
October 0.952466E+09 0.141426E+09 0.00 6068520.07 0.00 0.00 0.148205E+10 0.00 2.22
November 0.166285E+10 9631.82 0.00 5388092.55 1557277.53 0.00 0.185434E+10 0.00 2.03
December 0.255496E+10 0.00 0.00 3634577.21 0.00 78140045.14 0.141175E+10 0.00 1.83
                   
Annual Sum or Average 0.130929E+11 0.374149E+10 0.00 49707466.27 1563556.41 0.109663E+09 0.126048E+11 0.00 2.04
Minimum of Months 0.00 0.00 0.00 1576221.37 0.00 0.00 0.303674E+09 0.00 1.65
Maximum of Months 0.271302E+10 0.100108E+10 0.00 6183970.47 1557277.53 78140045.14 0.195439E+10 0.00 2.27



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.215387E+10 0.00 0.00 1459540.32 36897.67 0.00 0.170303E+10 0.00 1.49
February 0.327841E+10 0.00 0.00 435089.19 0.00 0.00 0.686333E+09 0.00 1.48
March 0.232604E+10 0.00 0.00 1146040.23 881607.89 0.00 0.130136E+10 0.00 1.52
April 0.162265E+09 47414416.42 0.00 4514915.02 5954050.00 0.00 0.187323E+10 0.00 1.56
May 8627363.36 0.123125E+09 0.00 4995606.71 4662394.88 0.00 0.144390E+10 0.00 1.54
June 27319.51 0.351365E+09 0.00 4620433.59 2613872.85 0.00 0.719905E+09 0.00 1.55
July 163622.68 0.683777E+09 0.00 2590270.58 12326211.42 0.00 0.324932E+09 0.00 1.47
August 687132.21 0.553558E+09 0.00 2970838.05 14748710.61 0.00 0.383354E+09 0.00 1.49
September 1401615.67 0.491699E+09 0.00 3144185.42 15857966.72 0.00 0.582710E+09 0.00 1.48
October 0.762514E+09 68822415.76 0.00 3505609.23 1875296.01 0.00 0.179678E+10 0.00 1.54
November 0.180078E+10 1562.67 0.00 1670258.17 1764767.24 0.00 0.171618E+10 0.00 1.51
December 0.321367E+10 0.00 0.00 604516.13 0.00 0.00 0.919635E+09 0.00 1.43
                   
Annual Sum or Average 0.137085E+11 0.231976E+10 0.00 31657302.65 60721775.31 0.00 0.134514E+11 0.00 1.51
Minimum of Months 27319.51 0.00 0.00 435089.19 0.00 0.00 0.324932E+09 0.00 1.43
Maximum of Months 0.327841E+10 0.683777E+09 0.00 4995606.71 15857966.72 0.00 0.187323E+10 0.00 1.56



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.255527E+10 0.00 0.00 3600.84 25033.39 0.00 10887304.42 0.00 0.47
February 0.268642E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.47
March 0.233295E+10 0.00 0.00 176459.18 598130.64 0.00 0.110441E+09 0.00 0.48
April 0.457669E+09 30172621.76 0.00 3066389.52 8644367.86 0.00 0.954476E+09 0.00 0.53
May 414914.11 0.110142E+09 0.00 4966515.07 0.00 0.00 0.113868E+10 0.00 0.61
June 0.00 0.395242E+09 0.00 4743355.77 0.00 0.00 0.676799E+09 0.00 0.76
July 0.00 0.739298E+09 0.00 2629116.82 0.00 0.00 0.308165E+09 0.00 0.71
August 0.00 0.576945E+09 0.00 2853764.51 171747.92 0.00 0.334380E+09 0.00 0.68
September 0.00 0.478535E+09 0.00 3077970.38 0.00 0.00 0.489787E+09 0.00 0.64
October 0.107643E+10 62278006.34 0.00 2020583.41 2695754.58 0.00 0.679382E+09 0.00 0.53
November 0.223715E+10 0.00 0.00 120882.62 1198374.07 0.00 0.101062E+09 0.00 0.47
December 0.279070E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45
                   
Annual Sum or Average 0.141370E+11 0.239261E+10 0.00 23658638.13 13333408.46 0.00 0.480406E+10 0.00 0.57
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45
Maximum of Months 0.279070E+10 0.739298E+09 0.00 4966515.07 8644367.86 0.00 0.113868E+10 0.00 0.76



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.238394E+10 0.00 0.00 0.00 23271.66 1619903.44 0.00 0.00 0.75
February 0.249736E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.76
March 0.226453E+10 0.00 0.00 0.00 556037.16 252204.46 0.00 0.00 0.77
April 0.116373E+10 0.00 0.00 6694.03 33478785.35 0.00 3732965.27 0.00 0.72
May 0.753417E+09 281207.65 0.00 134285.87 79056482.52 0.00 48614027.65 0.00 0.70
June 51392702.99 0.180674E+09 0.00 1320097.29 28460845.76 0.00 0.304249E+09 0.00 0.67
July 22439054.25 0.294660E+09 0.00 652318.57 95395095.57 0.00 0.141927E+09 0.00 0.64
August 97269841.10 0.193562E+09 0.00 528986.63 0.126681E+09 0.00 99828239.84 0.00 0.65
September 0.251042E+09 95635164.72 0.00 196849.83 0.192250E+09 0.00 66077995.79 0.00 0.66
October 0.150936E+10 8646817.85 0.00 48321.47 32860545.39 0.00 14837145.92 0.00 0.74
November 0.216783E+10 0.00 0.00 0.00 1114038.41 0.00 0.00 0.00 0.76
December 0.258531E+10 0.00 0.00 0.00 0.00 8993666.58 0.00 0.00 0.73
                   
Annual Sum or Average 0.157476E+11 0.773459E+09 0.00 2887553.69 0.589877E+09 10865774.48 0.679267E+09 0.00 0.71
Minimum of Months 22439054.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.64
Maximum of Months 0.258531E+10 0.294660E+09 0.00 1320097.29 0.192250E+09 8993666.58 0.304249E+09 0.00 0.77



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 21429405.90 452069.89 0.00 0.127628E+09 0.00 0.00 0.560131E+11 0.00 21.24
February 11964603.96 0.00 0.00 0.108297E+09 0.00 0.00 0.569969E+11 0.00 20.91
March 4724531.61 10652109.59 0.00 0.116384E+09 0.00 0.00 0.518981E+11 0.00 21.70
April 0.00 0.637126E+09 0.00 93588036.73 0.00 0.00 0.252232E+11 0.00 20.35
May 0.00 0.156895E+10 0.00 81234089.71 0.00 0.00 0.165641E+11 0.00 19.37
June 0.00 0.432167E+10 0.00 53865535.81 0.00 0.00 0.686180E+10 0.00 17.87
July 0.00 0.887560E+10 0.00 29999770.87 0.00 0.00 0.319672E+10 0.00 17.47
August 0.00 0.733770E+10 0.00 35818173.53 0.00 0.00 0.393089E+10 0.00 17.85
September 0.00 0.663644E+10 0.00 44442881.26 0.00 0.00 0.653243E+10 0.00 18.27
October 1373567.23 0.877142E+09 0.00 0.100580E+09 0.00 0.00 0.348728E+11 0.00 20.83
November 12927465.35 17566549.60 0.00 0.113029E+09 0.00 0.00 0.507042E+11 0.00 21.36
December 3721965.63 0.00 0.00 0.136022E+09 0.00 0.00 0.604909E+11 0.00 20.05
                   
Annual Sum or Average 56141539.67 0.302833E+11 0.00 0.104089E+10 0.00 0.00 0.373285E+12 0.00 19.77
Minimum of Months 0.00 0.00 0.00 29999770.87 0.00 0.00 0.319672E+10 0.00 17.47
Maximum of Months 21429405.90 0.887560E+10 0.00 0.136022E+09 0.00 0.00 0.604909E+11 0.00 21.70



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.736190E+10 338482.25 0.00 25620789.44 0.00 0.00 0.207264E+11 0.00 4.58
February 0.141370E+11 0.00 0.00 7561764.47 0.00 0.00 0.150823E+11 0.00 4.49
March 0.117892E+11 4509783.53 0.00 9609230.48 1999491.20 0.00 0.147057E+11 0.00 4.55
April 0.227234E+10 0.385525E+09 0.00 19087753.50 11604948.75 0.00 0.114346E+11 0.00 4.30
May 0.874614E+09 0.859263E+09 0.00 17864167.04 68885611.28 0.00 0.855520E+10 0.00 4.12
June 76265487.84 0.229609E+10 0.00 18627353.08 0.104386E+09 0.00 0.415643E+10 0.00 3.90
July 29726365.54 0.420434E+10 0.00 11571224.99 0.349149E+09 0.00 0.193930E+10 0.00 3.83
August 55972206.19 0.355043E+10 0.00 13747766.37 0.259133E+09 0.00 0.234280E+10 0.00 3.92
September 0.175862E+09 0.322401E+10 0.00 14668278.19 0.246608E+09 0.00 0.363435E+10 0.00 4.05
October 0.378900E+10 0.519811E+09 0.00 23508738.47 13961069.55 0.00 0.141503E+11 0.00 4.48
November 0.639085E+10 15603.36 0.00 22032178.78 13021278.47 0.00 0.190966E+11 0.00 4.56
December 0.132946E+11 0.00 0.00 15502516.57 0.00 0.00 0.171737E+11 0.00 4.38
                   
Annual Sum or Average 0.602474E+11 0.150443E+11 0.00 0.199402E+09 0.106875E+10 0.00 0.132998E+12 0.00 4.26
Minimum of Months 29726365.54 0.00 0.00 7561764.47 0.00 0.00 0.193930E+10 0.00 3.83
Maximum of Months 0.141370E+11 0.420434E+10 0.00 25620789.44 0.349149E+09 0.00 0.207264E+11 0.00 4.58



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.224042E+11 762809.29 0.00 61544077.41 0.00 0.00 0.578244E+11 0.00 1.84
February 0.438154E+11 0.00 0.00 23928955.60 0.00 0.00 0.383330E+11 0.00 1.82
March 0.314562E+11 3769074.64 0.00 39862048.10 14456970.55 0.00 0.437281E+11 0.00 1.87
April 0.311353E+10 0.100863E+10 0.00 81608024.42 89396635.94 0.00 0.387137E+11 0.00 1.87
May 0.508604E+09 0.233112E+10 0.00 84381280.84 0.277442E+09 0.00 0.294631E+11 0.00 1.84
June 24969639.76 0.664979E+10 0.00 81816303.87 0.262804E+09 0.00 0.145520E+11 0.00 1.80
July 5043629.17 0.132558E+11 0.00 50009123.85 0.611048E+09 0.00 0.663071E+10 0.00 1.75
August 15825876.60 0.107407E+11 0.00 56954099.22 0.533639E+09 0.00 0.796509E+10 0.00 1.77
September 0.101065E+09 0.977653E+10 0.00 60317908.15 0.514439E+09 0.00 0.124207E+11 0.00 1.81
October 0.913583E+10 0.142298E+10 0.00 81975288.21 36824463.11 0.00 0.443471E+11 0.00 1.90
November 0.181947E+11 32306.14 0.00 58887912.06 36484164.43 0.00 0.548585E+11 0.00 1.86
December 0.425624E+11 0.00 0.00 35056618.69 0.00 0.00 0.432369E+11 0.00 1.76
                   
Annual Sum or Average 0.171338E+12 0.451901E+11 0.00 0.716342E+09 0.237653E+10 0.00 0.392073E+12 0.00 1.82
Minimum of Months 5043629.17 0.00 0.00 23928955.60 0.00 0.00 0.663071E+10 0.00 1.75
Maximum of Months 0.438154E+11 0.132558E+11 0.00 84381280.84 0.611048E+09 0.00 0.578244E+11 0.00 1.90



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.156684E+09 897277.38 7950.48 7812326.54 226834.42 0.275419E+09 0.768796E+09 1706.56 0.47
February 0.300561E+09 89972.34 0.00 3502596.64 0.00 0.493142E+09 0.523632E+09 0.00 0.48
March 0.204437E+09 3282146.83 10935.79 5882248.60 352652.25 0.312236E+09 0.619279E+09 2485.21 0.47
April 38433390.95 57616519.72 4733.06 7903939.13 1723914.66 480865.75 0.464931E+09 2335.15 0.47
May 7976773.39 0.103478E+09 18398.74 6334154.83 2789687.98 58527.33 0.278701E+09 11037.48 0.47
June 356409.17 0.230238E+09 49199.14 4502247.47 4498964.20 0.00 67173351.89 7973.25 0.47
July 150134.62 0.627283E+09 272063.05 1195533.31 21446339.28 0.00 28234558.91 17324.62 0.47
August 595332.91 0.592377E+09 222144.42 1225609.64 23433302.04 0.00 17017693.19 22198.47 0.48
September 1979269.96 0.484822E+09 334000.97 2121910.91 21618501.92 2315.32 42991575.64 27165.66 0.48
October 83862276.11 99401263.84 78850.66 7303737.62 4165222.13 65466408.45 0.546540E+09 11328.99 0.47
November 0.139062E+09 7501239.49 63784.73 7236260.91 6656433.05 0.202852E+09 0.730704E+09 1907.34 0.47
December 0.237842E+09 351251.62 0.00 4480219.64 688689.35 0.585158E+09 0.544517E+09 0.00 0.47
                   
Annual Sum or Average 0.117194E+10 0.220734E+10 1062061.04 59500785.25 87600541.28 0.193481E+10 0.463252E+10 105462.72 0.47
Minimum of Months 150134.62 89972.34 0.00 1195533.31 0.00 0.00 17017693.19 0.00 0.47
Maximum of Months 0.300561E+09 0.627283E+09 334000.97 7903939.13 23433302.04 0.585158E+09 0.768796E+09 27165.66 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.200222E+09 610485.83 6902.62 3492804.23 513494.27 0.550855E+09 0.453999E+09 2753.28 0.47
February 0.346697E+09 89961.80 0.00 1596127.98 0.00 0.709219E+09 0.263172E+09 0.00 0.47
March 0.224985E+09 2888875.56 8997.41 4130236.76 745497.66 0.411904E+09 0.500681E+09 4422.03 0.47
April 42214735.37 56991827.60 0.00 7125259.31 2346401.30 793183.20 0.461556E+09 2320.26 0.47
May 7807411.64 0.103392E+09 20533.34 6280022.52 2861225.03 58520.47 0.278890E+09 10385.94 0.47
June 305880.80 0.230464E+09 45211.64 4614454.40 4252739.15 0.00 67103233.73 5495.41 0.47
July 133021.04 0.627487E+09 250856.80 1216964.41 21189491.63 0.00 28226775.62 16015.50 0.47
August 595263.16 0.590755E+09 220650.97 1176671.34 24982719.59 0.00 17064494.02 23663.29 0.48
September 2076278.30 0.480290E+09 325339.74 1983279.23 26092840.69 2315.05 43027681.38 33990.86 0.48
October 0.101558E+09 95679153.20 76687.10 5218932.67 7876560.99 0.141508E+09 0.454806E+09 12119.43 0.47
November 0.193346E+09 6885749.04 74263.11 3615816.17 7254700.31 0.398084E+09 0.484682E+09 6985.68 0.47
December 0.288606E+09 176555.48 0.00 1455448.74 863263.65 0.867202E+09 0.214573E+09 0.00 0.47
                   
Annual Sum or Average 0.140855E+10 0.219571E+10 1029442.74 41906017.75 98978934.25 0.307963E+10 0.326778E+10 118151.67 0.47
Minimum of Months 133021.04 89961.80 0.00 1176671.34 0.00 0.00 17064494.02 0.00 0.47
Maximum of Months 0.346697E+09 0.627487E+09 325339.74 7125259.31 26092840.69 0.867202E+09 0.500681E+09 33990.86 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.648165E+10 15372888.54 0.00 99209867.39 0.00 0.00 0.980818E+10 0.00 0.54
February 0.116654E+11 1219944.27 0.00 30084666.79 0.00 0.00 0.621394E+10 0.00 0.54
March 0.111036E+11 49466592.39 0.00 28508697.21 0.00 0.00 0.435016E+10 0.00 0.54
April 0.237039E+10 0.804699E+09 0.00 38704364.98 0.00 0.00 0.452976E+10 0.00 0.54
May 0.973331E+09 0.144129E+10 0.00 29016271.61 0.00 0.00 0.297142E+10 0.00 0.54
June 4839947.31 0.318360E+10 0.00 21988390.39 0.00 0.00 0.949861E+09 0.00 0.54
July 18781527.05 0.878604E+10 0.00 6012530.74 14076795.25 0.00 0.376287E+09 0.00 0.54
August 2805345.90 0.831865E+10 0.00 5489622.57 34487118.18 0.00 0.247140E+09 0.00 0.54
September 43075054.94 0.687178E+10 0.00 12006106.36 0.00 0.00 0.583486E+09 0.00 0.54
October 0.321750E+10 0.140549E+10 0.00 55690421.95 0.00 0.00 0.626119E+10 0.00 0.54
November 0.588000E+10 90015648.61 0.00 75436713.98 0.102840E+09 0.00 0.868642E+10 0.00 0.54
December 0.888173E+10 4762657.00 0.00 72117821.45 9338009.96 0.00 0.964921E+10 0.00 0.54
                   
Annual Sum or Average 0.506430E+11 0.309724E+11 0.00 0.474265E+09 0.160742E+09 0.00 0.546271E+11 0.00 0.54
Minimum of Months 2805345.90 1219944.27 0.00 5489622.57 0.00 0.00 0.247140E+09 0.00 0.54
Maximum of Months 0.116654E+11 0.878604E+10 0.00 99209867.39 0.102840E+09 0.00 0.980818E+10 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.282527E+10 3818301.73 96922.82 31008248.98 11408984.61 0.128631E+10 0.122509E+11 52883.07 0.53
February 0.480096E+10 1220277.86 0.00 23765808.52 0.00 0.128738E+10 0.118022E+11 0.00 0.54
March 0.316843E+10 24118051.81 278468.43 43222384.62 25020388.07 0.754079E+09 0.115207E+11 63210.63 0.54
April 0.646577E+09 0.506826E+09 3180670.13 55017549.63 0.294509E+09 6293635.49 0.623287E+10 403548.89 0.54
May 0.137127E+09 0.118211E+10 5545613.09 51962443.16 0.253707E+09 806988.96 0.378496E+10 321556.58 0.54
June 7042559.03 0.295629E+10 1451528.20 36635256.97 0.226691E+09 47592.88 0.933231E+09 40971.45 0.54
July 2744149.23 0.802597E+10 2124222.33 9449024.57 0.774361E+09 0.00 0.388998E+09 66262.47 0.54
August 8074387.61 0.742372E+10 1763108.13 8967933.03 0.929817E+09 0.00 0.238463E+09 129398.12 0.54
September 31456772.05 0.580652E+10 3765351.43 16811236.33 0.106317E+10 16291.16 0.590457E+09 199826.78 0.54
October 0.143673E+10 0.103891E+10 1820920.36 46607803.49 0.364841E+09 46433051.30 0.800722E+10 305177.45 0.54
November 0.280315E+10 74261605.43 853920.75 31781550.17 0.117689E+09 0.955639E+09 0.108553E+11 104300.99 0.54
December 0.398078E+10 785095.54 23842.55 16946526.97 13281938.17 0.551009E+10 0.910032E+10 13646.50 0.53
                   
Annual Sum or Average 0.198483E+11 0.270445E+11 20904568.22 0.372176E+09 0.407450E+10 0.984709E+10 0.757057E+11 1700782.94 0.54
Minimum of Months 2744149.23 785095.54 0.00 8967933.03 0.00 0.00 0.238463E+09 0.00 0.53
Maximum of Months 0.480096E+10 0.802597E+10 5545613.09 55017549.63 0.106317E+10 0.551009E+10 0.122509E+11 403548.89 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.127876E+09 814250.19 6941.73 8345105.70 309861.61 0.298349E+09 0.774142E+09 2715.30 0.47
February 0.265494E+09 89972.34 0.00 4308390.02 0.00 0.447713E+09 0.603323E+09 0.00 0.48
March 0.170144E+09 3295434.20 10272.00 6570950.55 336582.39 0.289041E+09 0.676078E+09 5931.50 0.47
April 14020443.19 57889152.66 0.00 9384420.34 1457081.12 28487.30 0.488316E+09 1268.80 0.47
May 2187436.58 0.104123E+09 0.00 7601372.11 2174455.19 1658.88 0.283280E+09 0.00 0.47
June 70056.44 0.232023E+09 0.00 5006958.87 2771749.74 0.00 66954993.22 0.00 0.47
July 49936.53 0.638512E+09 0.00 1290380.71 10507609.03 0.00 28239909.60 0.00 0.47
August 573978.29 0.603278E+09 16066.56 1179870.72 12758813.18 33548.73 17051237.99 876.44 0.48
September 1018551.24 0.492847E+09 78917.95 2161848.79 13873003.75 0.00 43914671.80 2989.26 0.48
October 53377540.57 0.101177E+09 8077.70 8288437.52 2470572.15 67596409.88 0.573910E+09 1360.51 0.47
November 0.121323E+09 6999433.84 77471.01 7527666.82 7144840.62 0.229238E+09 0.721766E+09 1619.14 0.47
December 0.252592E+09 351251.62 0.00 5001716.43 688689.35 0.572925E+09 0.541479E+09 0.00 0.47
                   
Annual Sum or Average 0.100873E+10 0.224140E+10 197746.96 66667118.58 54493258.14 0.190493E+10 0.481845E+10 16760.95 0.47
Minimum of Months 49936.53 89972.34 0.00 1179870.72 0.00 0.00 17051237.99 0.00 0.47
Maximum of Months 0.265494E+09 0.638512E+09 78917.95 9384420.34 13873003.75 0.572925E+09 0.774142E+09 5931.50 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.207411E+09 454252.56 7432.60 3222985.76 667430.34 0.540650E+09 0.457286E+09 4520.50 0.47
February 0.353886E+09 89961.80 0.00 1779636.25 0.00 0.593776E+09 0.371241E+09 0.00 0.48
March 0.220154E+09 3044193.26 7806.65 4500942.82 586548.74 0.364812E+09 0.552233E+09 9244.00 0.47
April 15445066.28 57569906.79 0.00 8535593.52 1769373.72 3783464.73 0.483925E+09 1268.65 0.47
May 2133237.15 0.104075E+09 0.00 7553706.60 2209715.57 1658.68 0.283347E+09 0.00 0.47
June 68098.12 0.231996E+09 0.00 5103583.72 2771169.07 0.00 66851887.09 0.00 0.47
July 46084.95 0.638517E+09 0.00 1313299.86 10425773.29 0.00 28217376.27 0.00 0.47
August 573911.04 0.602776E+09 16025.04 1129138.74 13189408.03 33544.80 17099833.93 915.98 0.48
September 1158568.22 0.491552E+09 78408.88 2015204.46 15108368.88 0.00 43915781.28 3488.73 0.48
October 94796315.25 0.100242E+09 33410.34 5878033.31 3359942.48 0.125254E+09 0.477161E+09 8714.96 0.47
November 0.205495E+09 6903582.49 68846.40 3446013.74 7235501.93 0.395388E+09 0.475398E+09 13767.31 0.47
December 0.293473E+09 57395.88 2304.80 1348852.33 979176.23 0.821913E+09 0.255102E+09 942.22 0.47
                   
Annual Sum or Average 0.139464E+10 0.223728E+10 214234.71 45826991.11 58302408.29 0.284561E+10 0.351178E+10 42862.35 0.47
Minimum of Months 46084.95 57395.88 0.00 1129138.74 0.00 0.00 17099833.93 0.00 0.47
Maximum of Months 0.353886E+09 0.638517E+09 78408.88 8535593.52 15108368.88 0.821913E+09 0.552233E+09 13767.31 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.196066E+11 0.00 0.00 0.00 191266.18 0.00 0.00 0.00 0.49
February 0.205254E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.50
March 0.186139E+11 0.00 0.00 0.00 4569983.64 0.00 0.00 0.00 0.50
April 0.457172E+10 0.236278E+09 0.00 14105147.72 56009159.28 0.00 0.534428E+10 0.00 0.50
May 0.666356E+09 0.726985E+09 0.00 20946738.25 11932229.84 0.00 0.643780E+10 0.00 0.51
June 0.00 0.230333E+10 0.00 24617396.56 588128.38 0.00 0.363179E+10 0.00 0.57
July 1395587.41 0.410849E+10 0.00 13704291.50 7021733.75 0.00 0.164845E+10 0.00 0.54
August 65770549.59 0.335342E+10 0.00 14730278.96 32035428.73 0.00 0.187991E+10 0.00 0.54
September 85646903.78 0.284695E+10 0.00 15196541.35 63870109.50 0.00 0.287075E+10 0.00 0.53
October 0.853435E+10 0.434745E+09 0.00 12310102.46 1215799.51 0.00 0.433313E+10 0.00 0.52
November 0.175901E+11 0.00 0.00 236238.79 9156109.92 0.00 0.226717E+09 0.00 0.50
December 0.213222E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.48
                   
Annual Sum or Average 0.111583E+12 0.140102E+11 0.00 0.115847E+09 0.186590E+09 0.00 0.263728E+11 0.00 0.51
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.48
Maximum of Months 0.213222E+11 0.410849E+10 0.00 24617396.56 63870109.50 0.00 0.643780E+10 0.00 0.57



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 41571077.64 213548.27 1924.62 1598962.16 67479.68 0.133078E+09 0.125930E+09 489.63 0.47
February 76706816.16 22493.09 0.00 720610.46 0.00 0.167947E+09 84834968.56 0.00 0.48
March 51971055.98 800057.26 1571.87 1245643.73 110038.34 0.120704E+09 0.111537E+09 387.55 0.47
April 9819977.91 14411475.32 1338.06 1700242.14 422065.10 4818396.43 0.111599E+09 1997.17 0.47
May 2159042.59 25875133.43 4328.92 1374697.46 691751.79 23939.24 69709841.26 3054.47 0.47
June 95175.87 57639677.74 11160.71 1047008.34 1046113.25 0.00 16865817.92 1699.60 0.47
July 37682.12 0.156791E+09 63208.13 276663.28 5396239.44 0.00 7080711.31 4626.94 0.47
August 148833.23 0.147819E+09 46997.77 285884.43 6142528.83 0.00 4274941.27 5413.93 0.48
September 529964.54 0.120651E+09 64208.36 473314.89 5975838.75 854.73 10769633.80 9018.36 0.48
October 22360223.33 24775649.70 17479.58 1500704.40 1118672.02 42927065.72 0.109005E+09 2365.11 0.47
November 37628844.87 1820931.77 17066.89 1429255.93 1716859.49 0.100046E+09 0.130859E+09 983.01 0.47
December 62546097.48 87812.91 0.00 895554.58 172172.34 0.190832E+09 88726059.63 0.00 0.47
                   
Annual Sum or Average 0.305575E+09 0.550907E+09 229284.90 12548541.81 22859759.03 0.760377E+09 0.871193E+09 30035.76 0.47
Minimum of Months 37682.12 22493.09 0.00 276663.28 0.00 0.00 4274941.27 0.00 0.47
Maximum of Months 76706816.16 0.156791E+09 64208.36 1700242.14 6142528.83 0.190832E+09 0.130859E+09 9018.36 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 50554429.69 104301.73 2073.81 639220.85 176693.30 0.190119E+09 60830183.45 340.17 0.47
February 87283976.49 0.00 22269.74 297975.76 0.00 0.210323E+09 32265546.09 220.71 0.47
March 56106561.60 710209.33 2399.93 843457.52 198383.97 0.143147E+09 85327734.32 954.93 0.47
April 10636821.21 14276023.94 578.95 1511561.41 556095.67 8119161.94 0.107655E+09 2438.73 0.47
May 2144185.81 25851655.69 4138.39 1360301.20 712116.84 23175.63 69731273.54 3244.12 0.47
June 89242.19 57683017.34 5269.69 1072345.69 1002451.01 0.00 16844304.36 1035.85 0.47
July 37094.60 0.157032E+09 62397.15 281886.63 5137288.60 0.00 7075209.04 4320.93 0.47
August 148815.79 0.147368E+09 42911.04 273341.71 6578820.74 0.00 4286949.63 5793.99 0.48
September 546427.25 0.119551E+09 63854.54 438630.04 7060425.27 1057.66 10786273.54 9854.46 0.48
October 25967562.39 23776089.19 19028.81 1019209.30 2112838.69 61956702.69 86828957.39 3173.49 0.47
November 49459336.59 1660143.15 3126.23 625396.41 1890848.30 0.147415E+09 72432172.04 1306.85 0.47
December 69906995.20 39297.76 0.00 257408.86 220657.02 0.247686E+09 25109180.48 0.00 0.47
                   
Annual Sum or Average 0.352881E+09 0.548052E+09 228048.26 8620735.37 25646619.42 0.100879E+10 0.579173E+09 32684.23 0.47
Minimum of Months 37094.60 0.00 0.00 257408.86 0.00 0.00 4286949.63 0.00 0.47
Maximum of Months 87283976.49 0.157032E+09 63854.54 1511561.41 7060425.27 0.247686E+09 0.107655E+09 9854.46 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.161811E+09 1820971.45 0.00 22194532.65 0.00 0.120870E+09 0.163646E+10 0.00 0.54
February 0.293186E+09 144506.59 0.00 10584424.25 0.00 0.398224E+09 0.141943E+10 0.00 0.54
March 0.254283E+09 5346088.29 7561.68 10582080.79 500811.20 0.353767E+09 0.121529E+10 5026.60 0.54
April 59756433.99 91712939.61 2706.11 9710989.15 3596890.69 5938929.00 0.746525E+09 6813.06 0.54
May 13964348.29 0.163730E+09 23087.22 7259827.37 6951110.79 118769.29 0.449363E+09 21808.28 0.54
June 733816.66 0.365149E+09 56501.08 5218053.36 11857758.65 6532.29 0.109734E+09 45455.05 0.54
July 297749.02 0.997949E+09 755992.08 1355252.95 43651024.77 0.00 45856461.04 47820.03 0.54
August 956177.48 0.945164E+09 832837.61 1506838.16 43404148.54 0.00 27794137.99 57000.29 0.54
September 3248553.50 0.776816E+09 546422.96 2902140.93 36589915.61 1304.51 69488447.83 33577.84 0.54
October 96776170.63 0.160749E+09 114381.87 13250364.57 5606996.37 46901503.27 0.972452E+09 15182.46 0.54
November 0.152152E+09 11742537.46 108798.29 18047005.41 10989447.09 0.135626E+09 0.142855E+10 3680.75 0.54
December 0.227323E+09 564153.08 0.00 17991376.65 1106119.35 0.438630E+09 0.151965E+10 0.00 0.54
                   
Annual Sum or Average 0.126449E+10 0.352089E+10 2448288.91 0.120603E+09 0.164254E+09 0.150008E+10 0.964061E+10 236364.35 0.54
Minimum of Months 297749.02 144506.59 0.00 1355252.95 0.00 0.00 27794137.99 0.00 0.54
Maximum of Months 0.293186E+09 0.997949E+09 832837.61 22194532.65 43651024.77 0.438630E+09 0.163646E+10 57000.29 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.965402E+10 477848.24 0.00 35995386.58 0.00 0.00 0.397276E+11 0.00 5.81
February 0.134004E+11 0.00 0.00 28906495.47 0.00 0.00 0.381044E+11 0.00 5.86
March 0.762729E+10 9013351.74 0.00 39284414.98 2404028.50 0.00 0.393781E+11 0.00 5.98
April 0.582407E+09 0.663278E+09 0.00 48783594.32 24168739.67 0.00 0.240772E+11 0.00 5.71
May 93668956.81 0.159037E+10 0.00 51245431.31 39084015.79 0.00 0.172200E+11 0.00 5.56
June 14285757.38 0.417235E+10 0.00 44209556.80 53683793.12 0.00 0.795602E+10 0.00 5.27
July 2265381.93 0.802070E+10 0.00 26857150.20 0.147147E+09 0.00 0.364165E+10 0.00 5.14
August 4815137.77 0.657229E+10 0.00 29956556.07 0.161676E+09 0.00 0.436123E+10 0.00 5.19
September 38638660.93 0.591584E+10 0.00 31192400.19 0.166361E+09 0.00 0.685034E+10 0.00 5.30
October 0.314455E+10 0.831719E+09 0.00 42794727.70 36923040.10 0.00 0.286683E+11 0.00 5.76
November 0.675180E+10 5651221.50 0.00 35492931.77 17223868.81 0.00 0.380975E+11 0.00 5.85
December 0.149895E+11 0.00 0.00 29902468.62 0.00 0.00 0.384826E+11 0.00 5.62
                   
Annual Sum or Average 0.563037E+11 0.277817E+11 0.00 0.444621E+09 0.648671E+09 0.00 0.286565E+12 0.00 5.59
Minimum of Months 2265381.93 0.00 0.00 26857150.20 0.00 0.00 0.364165E+10 0.00 5.14
Maximum of Months 0.149895E+11 0.802070E+10 0.00 51245431.31 0.166361E+09 0.00 0.397276E+11 0.00 5.98



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.438953E+10 477814.02 0.00 49422491.53 0.00 0.00 0.455912E+11 0.00 5.87
February 0.549654E+10 0.00 0.00 40956384.78 0.00 0.00 0.464650E+11 0.00 5.91
March 0.263974E+10 9131765.00 0.00 52836169.67 2284797.49 0.00 0.450760E+11 0.00 6.06
April 0.248487E+09 0.673957E+09 0.00 58769416.63 13530616.33 0.00 0.251150E+11 0.00 5.84
May 47321444.49 0.161419E+10 0.00 59218594.68 16981492.70 0.00 0.179596E+11 0.00 5.72
June 2511037.16 0.423378E+10 0.00 48979002.33 30935946.71 0.00 0.832446E+10 0.00 5.43
July 88367.54 0.826892E+10 0.00 29440534.21 65312039.64 0.00 0.379494E+10 0.00 5.29
August 1263457.32 0.674908E+10 0.00 32986346.46 81236173.69 0.00 0.454872E+10 0.00 5.34
September 15575534.99 0.610281E+10 0.00 35013884.49 79057778.63 0.00 0.715586E+10 0.00 5.44
October 0.110489E+10 0.857508E+09 0.00 52986672.36 19736091.27 0.00 0.312977E+11 0.00 5.86
November 0.310787E+10 22829297.03 0.00 47873197.43 44154.88 0.00 0.422373E+11 0.00 5.91
December 0.830682E+10 0.00 0.00 44706147.49 0.00 0.00 0.455712E+11 0.00 5.66
                   
Annual Sum or Average 0.253606E+11 0.285327E+11 0.00 0.553189E+09 0.309119E+09 0.00 0.323137E+12 0.00 5.69
Minimum of Months 88367.54 0.00 0.00 29440534.21 0.00 0.00 0.379494E+10 0.00 5.29
Maximum of Months 0.830682E+10 0.826892E+10 0.00 59218594.68 81236173.69 0.00 0.464650E+11 0.00 6.06



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 1648967.24 654552.65 0.00 0.134434E+09 0.00 0.00 0.519704E+11 0.00 21.73
February 881847.47 0.00 0.00 0.113690E+09 0.00 0.00 0.564601E+11 0.00 21.59
March 0.00 15779999.28 0.00 0.123318E+09 0.00 0.00 0.494147E+11 0.00 22.25
April 0.00 0.992166E+09 0.00 95738474.52 0.00 0.00 0.237663E+11 0.00 21.50
May 0.00 0.235119E+10 0.00 80376608.31 0.00 0.00 0.157354E+11 0.00 20.80
June 0.00 0.605672E+10 0.00 53620380.95 0.00 0.00 0.679930E+10 0.00 19.68
July 0.00 0.107627E+11 0.00 29825784.38 0.00 0.00 0.310718E+10 0.00 19.35
August 0.00 0.923075E+10 0.00 34849386.53 0.00 0.00 0.381913E+10 0.00 19.60
September 0.00 0.785832E+10 0.00 43438644.64 0.00 0.00 0.633374E+10 0.00 19.90
October 0.00 0.118045E+10 0.00 0.104218E+09 0.00 0.00 0.327428E+11 0.00 21.66
November 0.00 28702737.44 0.00 0.120011E+09 0.00 0.00 0.477071E+11 0.00 21.90
December 615346.94 0.00 0.00 0.138727E+09 0.00 0.00 0.573411E+11 0.00 20.63
                   
Annual Sum or Average 3146161.66 0.384774E+11 0.00 0.107225E+10 0.00 0.00 0.355197E+12 0.00 20.88
Minimum of Months 0.00 0.00 0.00 29825784.38 0.00 0.00 0.310718E+10 0.00 19.35
Maximum of Months 1648967.24 0.107627E+11 0.00 0.138727E+09 0.00 0.00 0.573411E+11 0.00 22.25



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.699975E+10 91125.13 0.00 1452613.45 0.00 596949.40 0.533474E+09 0.00 0.72
February 0.785465E+10 0.00 0.00 8716.05 0.00 0.00 27774977.38 0.00 0.72
March 0.660359E+10 738467.42 0.00 1925054.12 1168168.74 0.00 0.576671E+09 0.00 0.74
April 0.140936E+10 0.207337E+09 0.00 10949918.02 9855.05 0.00 0.262694E+10 0.00 0.91
May 0.213027E+09 0.503666E+09 0.00 12451786.16 0.00 0.00 0.273882E+10 0.00 0.99
June 0.00 0.149085E+10 0.00 11928370.14 0.00 0.00 0.164414E+10 0.00 1.17
July 0.00 0.243522E+10 0.00 6755175.09 0.00 0.00 0.750383E+09 0.00 1.12
August 622803.59 0.205442E+10 0.00 7451286.54 0.00 0.00 0.874498E+09 0.00 1.10
September 9815228.41 0.163183E+10 0.00 8175401.75 0.00 0.00 0.128501E+10 0.00 1.04
October 0.303842E+10 0.257992E+09 0.00 7842020.29 0.00 0.00 0.202088E+10 0.00 0.86
November 0.607698E+10 11499.84 0.00 2138360.59 3506347.83 0.00 0.793434E+09 0.00 0.73
December 0.810516E+10 0.00 0.00 178641.31 0.00 10146887.39 72936794.94 0.00 0.69
                   
Annual Sum or Average 0.403114E+11 0.858215E+10 0.00 71257343.52 4684371.62 10743836.78 0.139450E+11 0.00 0.90
Minimum of Months 0.00 0.00 0.00 8716.05 0.00 0.00 27774977.38 0.00 0.69
Maximum of Months 0.810516E+10 0.243522E+10 0.00 12451786.16 3506347.83 10146887.39 0.273882E+10 0.00 1.17



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:00:32

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.149234E+12 0.145103E+11 0.860330E+11 0.475079E+12 0.296220E+12
February 0.186278E+12 0.146167E+11 0.988793E+11 0.475763E+12 0.107235E+12
March 0.247870E+12 0.134457E+11 0.816118E+11 0.442139E+12 0.274098E+12
April 0.294696E+12 0.499019E+10 0.256083E+11 0.177621E+12 0.689079E+12
May 0.299960E+12 0.213951E+10 0.681019E+10 0.853520E+11 0.880218E+12
June 0.313525E+12 -0.223079E+10 -0.271461E+11 -0.554968E+11 0.114155E+13
July 0.297869E+12 -0.645919E+10 -0.474126E+11 -0.189466E+12 0.127315E+13
August 0.249605E+12 -0.534983E+10 -0.398045E+11 -0.151552E+12 0.124038E+13
September 0.210441E+12 -0.346190E+10 -0.235143E+11 -0.906440E+11 0.112420E+13
October 0.190699E+12 0.715456E+10 0.419597E+11 0.254804E+12 0.622926E+12
November 0.162174E+12 0.127808E+11 0.784663E+11 0.425807E+12 0.311189E+12
December 0.117967E+12 0.180808E+11 0.112185E+12 0.575343E+12 0.190993E+12
           
Annual Sum or Average 0.272032E+13 0.702168E+11 0.393676E+12 0.242475E+13 0.815125E+13
Minimum of Months 0.117967E+12 -0.645919E+10 -0.474126E+11 -0.189466E+12 0.107235E+12
Maximum of Months 0.313525E+12 0.180808E+11 0.112185E+12 0.575343E+12 0.127315E+13